Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 09:15
Tabular Output Report in Format: HTML
Building: ApartmentMidRise
Environment: RUNPERIOD 1 ** San Diego-Brown Field Muni AP CA USA TMY3 WMO#=722904
Simulation Timestamp: 2023-10-16 09:15:25
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 09:15:25
Values gathered over 8760.00 hours| Total Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
| Total Site Energy | 1216.84 | 388.19 | 430.90 |
| Net Site Energy | 1216.84 | 388.19 | 430.90 |
| Total Source Energy | 3801.20 | 1212.65 | 1346.04 |
| Net Source Energy | 3801.20 | 1212.65 | 1346.04 |
| Site=>Source Conversion Factor | |
| Electricity | 3.167 |
| Natural Gas | 1.084 |
| District Cooling | 1.056 |
| District Heating | 3.613 |
| Steam | 1.200 |
| Gasoline | 1.050 |
| Diesel | 1.050 |
| Coal | 1.050 |
| Fuel Oil No 1 | 1.050 |
| Fuel Oil No 2 | 1.050 |
| Propane | 1.050 |
| Other Fuel 1 | 1.000 |
| Other Fuel 2 | 1.000 |
| Area [m2] | |
| Total Building Area | 3134.61 |
| Net Conditioned Building Area | 2823.98 |
| Unconditioned Building Area | 310.64 |
| Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
| Heating | 0.00 | 25.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Cooling | 82.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Lighting | 99.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Lighting | 50.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment | 458.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans | 76.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems | 423.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1875.32 |
| Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Total End Uses | 1191.62 | 25.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1875.32 |
| Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
| Heating | General | 0.00 | 25.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Cooling | General | 82.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Lighting | LightsWired | 94.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LightsPlugIn | 4.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Exterior Lighting | General | 50.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment | MiscPlug | 388.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| ElevatorLift | 65.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| ElevatorLightsFan | 5.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| General | 76.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems | Water Heater | 423.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1875.32 |
| Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
| Heating | Unassigned | 0.00 | 25.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Cooling | Unassigned | 82.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Lighting | GENERAL | 99.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Lighting | Unassigned | 50.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment | GENERAL | 458.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans | Unassigned | 76.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Pumps | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems | Unassigned | 423.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1875.32 |
| Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
| Lighting | 52.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| HVAC | 206.69 | 8.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.66 |
| Other | 162.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Total | 421.97 | 8.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.66 |
| Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
| Lighting | 47.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| HVAC | 186.21 | 8.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.60 |
| Other | 146.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Total | 380.15 | 8.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.60 |
| Electricity [GJ] | Percent Electricity [%] | |
| Fuel-Fired Power Generation | 0.000 | 0.00 |
| High Temperature Geothermal* | 0.000 | 0.00 |
| Photovoltaic Power | 0.000 | 0.00 |
| Wind Power | 0.000 | 0.00 |
| Power Conversion | 0.000 | 0.00 |
| Net Decrease in On-Site Storage | 0.000 | 0.00 |
| Total On-Site Electric Sources | 0.000 | 0.00 |
| Electricity Coming From Utility | 1191.620 | 100.00 |
| Surplus Electricity Going To Utility | 0.000 | 0.00 |
| Net Electricity From Utility | 1191.620 | 100.00 |
| Total On-Site and Utility Electric Sources | 1191.620 | 100.00 |
| Total Electricity End Uses | 1191.620 | 100.00 |
| Heat [GJ] | Percent Heat [%] | |
| Water-Side Heat Recovery | 0.00 | 0.00 |
| Air to Air Heat Recovery for Cooling | 0.00 | 55.93 |
| Air to Air Heat Recovery for Heating | 0.00 | 44.07 |
| High-Temperature Geothermal* | 0.00 | 0.00 |
| Solar Water Thermal | 0.00 | 0.00 |
| Solar Air Thermal | 0.00 | 0.00 |
| Total On-Site Thermal Sources | 0.00 | 100.00 |
| Water [m3] | Percent Water [%] | |
| Rainwater Collection | 0.00 | 0.00 |
| Condensate Collection | 0.00 | 0.00 |
| Groundwater Well | 0.00 | 0.00 |
| Total On Site Water Sources | 0.00 | 0.00 |
| - | - | - |
| Initial Storage | 0.00 | 0.00 |
| Final Storage | 0.00 | 0.00 |
| Change in Storage | 0.00 | 0.00 |
| - | - | - |
| Water Supplied by Utility | 1875.32 | 100.00 |
| - | - | - |
| Total On Site, Change in Storage, and Utility Water Sources | 1875.32 | 100.00 |
| Total Water End Uses | 1875.32 | 100.00 |
| Degrees [deltaC] | |
| Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
| Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
| Facility [Hours] | |
| Time Setpoint Not Met During Occupied Heating | 0.00 |
| Time Setpoint Not Met During Occupied Cooling | 0.00 |
| Time Not Comfortable Based on Simple ASHRAE 55-2004 | 8675.00 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2012
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME APARTMENTMIDRISE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3C
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_CA_SANDIEGO
| Environment |ZoneCoolingSummaryMonthly
| G SW APARTMENT | G NW APARTMENT | OFFICE | G NE APARTMENT | G N1 APARTMENT | G N2 APARTMENT | G S1 APARTMENT | G S2 APARTMENT | M SW APARTMENT | M NW APARTMENT | M SE APARTMENT | M NE APARTMENT | M N1 APARTMENT | M N2 APARTMENT | M S1 APARTMENT | M S2 APARTMENT | T SW APARTMENT | T NW APARTMENT | T SE APARTMENT | T NE APARTMENT | T N1 APARTMENT | T N2 APARTMENT | T S1 APARTMENT | T S2 APARTMENT | T CORRIDOR | G CORRIDOR | M CORRIDOR |ZoneHeatingSummaryMonthly
| G SW APARTMENT | G NW APARTMENT | OFFICE | G NE APARTMENT | G N1 APARTMENT | G N2 APARTMENT | G S1 APARTMENT | G S2 APARTMENT | M SW APARTMENT | M NW APARTMENT | M SE APARTMENT | M NE APARTMENT | M N1 APARTMENT | M N2 APARTMENT | M S1 APARTMENT | M S2 APARTMENT | T SW APARTMENT | T NW APARTMENT | T SE APARTMENT | T NE APARTMENT | T N1 APARTMENT | T N2 APARTMENT | T S1 APARTMENT | T S2 APARTMENT | T CORRIDOR | G CORRIDOR | M CORRIDOR |ZoneElectricSummaryMonthly
| G SW APARTMENT | G NW APARTMENT | OFFICE | G NE APARTMENT | G N1 APARTMENT | G N2 APARTMENT | G S1 APARTMENT | G S2 APARTMENT | M SW APARTMENT | M NW APARTMENT | M SE APARTMENT | M NE APARTMENT | M N1 APARTMENT | M N2 APARTMENT | M S1 APARTMENT | M S2 APARTMENT | T SW APARTMENT | T NW APARTMENT | T SE APARTMENT | T NE APARTMENT | T N1 APARTMENT | T N2 APARTMENT | T S1 APARTMENT | T S2 APARTMENT | T CORRIDOR | G CORRIDOR | M CORRIDOR |SpaceGainsMonthly
| G SW APARTMENT | G NW APARTMENT | OFFICE | G NE APARTMENT | G N1 APARTMENT | G N2 APARTMENT | G S1 APARTMENT | G S2 APARTMENT | M SW APARTMENT | M NW APARTMENT | M SE APARTMENT | M NE APARTMENT | M N1 APARTMENT | M N2 APARTMENT | M S1 APARTMENT | M S2 APARTMENT | T SW APARTMENT | T NW APARTMENT | T SE APARTMENT | T NE APARTMENT | T N1 APARTMENT | T N2 APARTMENT | T S1 APARTMENT | T S2 APARTMENT | T CORRIDOR | G CORRIDOR | M CORRIDOR |PeakSpaceGainsMonthly
| G SW APARTMENT | G NW APARTMENT | OFFICE | G NE APARTMENT | G N1 APARTMENT | G N2 APARTMENT | G S1 APARTMENT | G S2 APARTMENT | M SW APARTMENT | M NW APARTMENT | M SE APARTMENT | M NE APARTMENT | M N1 APARTMENT | M N2 APARTMENT | M S1 APARTMENT | M S2 APARTMENT | T SW APARTMENT | T NW APARTMENT | T SE APARTMENT | T NE APARTMENT | T N1 APARTMENT | T N2 APARTMENT | T S1 APARTMENT | T S2 APARTMENT | T CORRIDOR | G CORRIDOR | M CORRIDOR |SpaceGainComponentsAtCoolingPeakMonthly
| G SW APARTMENT | G NW APARTMENT | OFFICE | G NE APARTMENT | G N1 APARTMENT | G N2 APARTMENT | G S1 APARTMENT | G S2 APARTMENT | M SW APARTMENT | M NW APARTMENT | M SE APARTMENT | M NE APARTMENT | M N1 APARTMENT | M N2 APARTMENT | M S1 APARTMENT | M S2 APARTMENT | T SW APARTMENT | T NW APARTMENT | T SE APARTMENT | T NE APARTMENT | T N1 APARTMENT | T N2 APARTMENT | T S1 APARTMENT | T S2 APARTMENT | T CORRIDOR | G CORRIDOR | M CORRIDOR |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| G SW APARTMENT | G NW APARTMENT | OFFICE | G NE APARTMENT | G N1 APARTMENT | G N2 APARTMENT | G S1 APARTMENT | G S2 APARTMENT | M SW APARTMENT | M NW APARTMENT | M SE APARTMENT | M NE APARTMENT | M N1 APARTMENT | M N2 APARTMENT | M S1 APARTMENT | M S2 APARTMENT | T SW APARTMENT | T NW APARTMENT | T SE APARTMENT | T NE APARTMENT | T N1 APARTMENT | T N2 APARTMENT | T S1 APARTMENT | T S2 APARTMENT | T CORRIDOR | G CORRIDOR | M CORRIDOR |ComfortReportSimple55Monthly
| G SW APARTMENT | G NW APARTMENT | OFFICE | G NE APARTMENT | G N1 APARTMENT | G N2 APARTMENT | G S1 APARTMENT | G S2 APARTMENT | M SW APARTMENT | M NW APARTMENT | M SE APARTMENT | M NE APARTMENT | M N1 APARTMENT | M N2 APARTMENT | M S1 APARTMENT | M S2 APARTMENT | T SW APARTMENT | T NW APARTMENT | T SE APARTMENT | T NE APARTMENT | T N1 APARTMENT | T N2 APARTMENT | T S1 APARTMENT | T S2 APARTMENT | T CORRIDOR | G CORRIDOR | M CORRIDOR |OccupantComfortDataSummaryMonthly
| OCCUP_GSW | OCCUP_GNW | OCCUP_OFFICE | OCCUP_GNE | OCCUP_GN1 | OCCUP_GN2 | OCCUP_GS1 | OCCUP_GS2 | OCCUP_MSW | OCCUP_MNW | OCCUP_MSE | OCCUP_MNE | OCCUP_MN1 | OCCUP_MN2 | OCCUP_MS1 | OCCUP_MS2 | OCCUP_TSW | OCCUP_TNW | OCCUP_TSE | OCCUP_TNE | OCCUP_TN1 | OCCUP_TN2 | OCCUP_TS1 | OCCUP_TS2 | OCCUP_T CORRIDOR | OCCUP_G CORRIDOR | OCCUP_M CORRIDOR |DXReportMonthly
| SPLIT GSW COOLING COIL | SPLIT GNW COOLING COIL | SPLIT OFFICE COOLING COIL | SPLIT GNE COOLING COIL | SPLIT GN1 COOLING COIL | SPLIT GN2 COOLING COIL | SPLIT GS1 COOLING COIL | SPLIT GS2 COOLING COIL | SPLIT MSW COOLING COIL | SPLIT MNW COOLING COIL | SPLIT MSE COOLING COIL | SPLIT MNE COOLING COIL | SPLIT MN1 COOLING COIL | SPLIT MN2 COOLING COIL | SPLIT MS1 COOLING COIL | SPLIT MS2 COOLING COIL | SPLIT TSW COOLING COIL | SPLIT TNW COOLING COIL | SPLIT TSE COOLING COIL | SPLIT TNE COOLING COIL | SPLIT TN1 COOLING COIL | SPLIT TN2 COOLING COIL | SPLIT TS1 COOLING COIL | SPLIT TS2 COOLING COIL |WindowReportMonthly
| GWINDOW1 S SWA | GWINDOW1 W SWA | GWINDOW1 W NWA | GWINDOW1 N NWA | GWINDOW1 S SEA | GWINDOW1 E SEA | GWINDOW1 E NEA | GWINDOW1 N NEA | GWINDOW1 N N1A | GWINDOW1 N N2A | GWINDOW1 S S1A | GWINDOW1 S S2A | MWINDOW1 S SWA | MWINDOW1 W SWA | MWINDOW1 W NWA | MWINDOW1 N NWA | MWINDOW1 S SEA | MWINDOW1 E SEA | MWINDOW1 E NEA | MWINDOW1 N NEA | MWINDOW1 N N1A | MWINDOW1 N N2A | MWINDOW1 S S1A | MWINDOW1 S S2A | TWINDOW1 S SWA | TWINDOW1 W SWA | TWINDOW1 W NWA | TWINDOW1 N NWA | TWINDOW1 S SEA | TWINDOW1 E SEA | TWINDOW1 E NEA | TWINDOW1 N NEA | TWINDOW1 N N1A | TWINDOW1 N N2A | TWINDOW1 S S1A | TWINDOW1 S S2A | TWINDOW14 | ENTRANCE DOOR | MWINDOW14 |WindowEnergyReportMonthly
| GWINDOW1 S SWA | GWINDOW1 W SWA | GWINDOW1 W NWA | GWINDOW1 N NWA | GWINDOW1 S SEA | GWINDOW1 E SEA | GWINDOW1 E NEA | GWINDOW1 N NEA | GWINDOW1 N N1A | GWINDOW1 N N2A | GWINDOW1 S S1A | GWINDOW1 S S2A | MWINDOW1 S SWA | MWINDOW1 W SWA | MWINDOW1 W NWA | MWINDOW1 N NWA | MWINDOW1 S SEA | MWINDOW1 E SEA | MWINDOW1 E NEA | MWINDOW1 N NEA | MWINDOW1 N N1A | MWINDOW1 N N2A | MWINDOW1 S S1A | MWINDOW1 S S2A | TWINDOW1 S SWA | TWINDOW1 W SWA | TWINDOW1 W NWA | TWINDOW1 N NWA | TWINDOW1 S SEA | TWINDOW1 E SEA | TWINDOW1 E NEA | TWINDOW1 N NEA | TWINDOW1 N N1A | TWINDOW1 N N2A | TWINDOW1 S S1A | TWINDOW1 S S2A | TWINDOW14 | ENTRANCE DOOR | MWINDOW14 |WindowZoneSummaryMonthly
| G SW APARTMENT | G NW APARTMENT | OFFICE | G NE APARTMENT | G N1 APARTMENT | G N2 APARTMENT | G S1 APARTMENT | G S2 APARTMENT | M SW APARTMENT | M NW APARTMENT | M SE APARTMENT | M NE APARTMENT | M N1 APARTMENT | M N2 APARTMENT | M S1 APARTMENT | M S2 APARTMENT | T SW APARTMENT | T NW APARTMENT | T SE APARTMENT | T NE APARTMENT | T N1 APARTMENT | T N2 APARTMENT | T S1 APARTMENT | T S2 APARTMENT | T CORRIDOR | G CORRIDOR | M CORRIDOR |WindowEnergyZoneSummaryMonthly
| G SW APARTMENT | G NW APARTMENT | OFFICE | G NE APARTMENT | G N1 APARTMENT | G N2 APARTMENT | G S1 APARTMENT | G S2 APARTMENT | M SW APARTMENT | M NW APARTMENT | M SE APARTMENT | M NE APARTMENT | M N1 APARTMENT | M N2 APARTMENT | M S1 APARTMENT | M S2 APARTMENT | T SW APARTMENT | T NW APARTMENT | T SE APARTMENT | T NE APARTMENT | T N1 APARTMENT | T N2 APARTMENT | T S1 APARTMENT | T S2 APARTMENT | T CORRIDOR | G CORRIDOR | M CORRIDOR |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| G SW APARTMENT WATER HEATER | G NW APARTMENT WATER HEATER | G NE APARTMENT WATER HEATER | G N1 APARTMENT WATER HEATER | G N2 APARTMENT WATER HEATER | G S1 APARTMENT WATER HEATER | G S2 APARTMENT WATER HEATER | M SW APARTMENT WATER HEATER | M NW APARTMENT WATER HEATER | M SE APARTMENT WATER HEATER | M NE APARTMENT WATER HEATER | M N1 APARTMENT WATER HEATER | M N2 APARTMENT WATER HEATER | M S1 APARTMENT WATER HEATER | M S2 APARTMENT WATER HEATER | T SW APARTMENT WATER HEATER | T NW APARTMENT WATER HEATER | T SE APARTMENT WATER HEATER | T NE APARTMENT WATER HEATER | T N1 APARTMENT WATER HEATER | T N2 APARTMENT WATER HEATER | T S1 APARTMENT WATER HEATER | T S2 APARTMENT WATER HEATER |DaylightingReportMonthly
| Environment |CoilReportMonthly
| SPLIT GSW HEATING COIL | SPLIT GNW HEATING COIL | SPLIT OFFICE HEATING COIL | SPLIT GNE HEATING COIL | SPLIT GN1 HEATING COIL | SPLIT GN2 HEATING COIL | SPLIT GS1 HEATING COIL | SPLIT GS2 HEATING COIL | SPLIT MSW HEATING COIL | SPLIT MNW HEATING COIL | SPLIT MSE HEATING COIL | SPLIT MNE HEATING COIL | SPLIT MN1 HEATING COIL | SPLIT MN2 HEATING COIL | SPLIT MS1 HEATING COIL | SPLIT MS2 HEATING COIL | SPLIT TSW HEATING COIL | SPLIT TNW HEATING COIL | SPLIT TSE HEATING COIL | SPLIT TNE HEATING COIL | SPLIT TN1 HEATING COIL | SPLIT TN2 HEATING COIL | SPLIT TS1 HEATING COIL | SPLIT TS2 HEATING COIL | SPLIT GSW COOLING COIL | SPLIT GNW COOLING COIL | SPLIT OFFICE COOLING COIL | SPLIT GNE COOLING COIL | SPLIT GN1 COOLING COIL | SPLIT GN2 COOLING COIL | SPLIT GS1 COOLING COIL | SPLIT GS2 COOLING COIL | SPLIT MSW COOLING COIL | SPLIT MNW COOLING COIL | SPLIT MSE COOLING COIL | SPLIT MNE COOLING COIL | SPLIT MN1 COOLING COIL | SPLIT MN2 COOLING COIL | SPLIT MS1 COOLING COIL | SPLIT MS2 COOLING COIL | SPLIT TSW COOLING COIL | SPLIT TNW COOLING COIL | SPLIT TSE COOLING COIL | SPLIT TNE COOLING COIL | SPLIT TN1 COOLING COIL | SPLIT TN2 COOLING COIL | SPLIT TS1 COOLING COIL | SPLIT TS2 COOLING COIL |FanReportMonthly
| SPLIT GSW SUPPLY FAN | G SW APARTMENT ERV SUP FAN | G SW APARTMENT ERV EXH FAN | SPLIT GNW SUPPLY FAN | G NW APARTMENT ERV SUP FAN | G NW APARTMENT ERV EXH FAN | SPLIT OFFICE SUPPLY FAN | SPLIT GNE SUPPLY FAN | G NE APARTMENT ERV SUP FAN | G NE APARTMENT ERV EXH FAN | SPLIT GN1 SUPPLY FAN | G N1 APARTMENT ERV SUP FAN | G N1 APARTMENT ERV EXH FAN | SPLIT GN2 SUPPLY FAN | G N2 APARTMENT ERV SUP FAN | G N2 APARTMENT ERV EXH FAN | SPLIT GS1 SUPPLY FAN | G S1 APARTMENT ERV SUP FAN | G S1 APARTMENT ERV EXH FAN | SPLIT GS2 SUPPLY FAN | G S2 APARTMENT ERV SUP FAN | G S2 APARTMENT ERV EXH FAN | SPLIT MSW SUPPLY FAN | M SW APARTMENT ERV SUP FAN | M SW APARTMENT ERV EXH FAN | SPLIT MNW SUPPLY FAN | M NW APARTMENT ERV SUP FAN | M NW APARTMENT ERV EXH FAN | SPLIT MSE SUPPLY FAN | M SE APARTMENT ERV SUP FAN | M SE APARTMENT ERV EXH FAN | SPLIT MNE SUPPLY FAN | M NE APARTMENT ERV SUP FAN | M NE APARTMENT ERV EXH FAN | SPLIT MN1 SUPPLY FAN | M N1 APARTMENT ERV SUP FAN | M N1 APARTMENT ERV EXH FAN | SPLIT MN2 SUPPLY FAN | M N2 APARTMENT ERV SUP FAN | M N2 APARTMENT ERV EXH FAN | SPLIT MS1 SUPPLY FAN | M S1 APARTMENT ERV SUP FAN | M S1 APARTMENT ERV EXH FAN | SPLIT MS2 SUPPLY FAN | M S2 APARTMENT ERV SUP FAN | M S2 APARTMENT ERV EXH FAN | SPLIT TSW SUPPLY FAN | T SW APARTMENT ERV SUP FAN | T SW APARTMENT ERV EXH FAN | SPLIT TNW SUPPLY FAN | T NW APARTMENT ERV SUP FAN | T NW APARTMENT ERV EXH FAN | SPLIT TSE SUPPLY FAN | T SE APARTMENT ERV SUP FAN | T SE APARTMENT ERV EXH FAN | SPLIT TNE SUPPLY FAN | T NE APARTMENT ERV SUP FAN | T NE APARTMENT ERV EXH FAN | SPLIT TN1 SUPPLY FAN | T N1 APARTMENT ERV SUP FAN | T N1 APARTMENT ERV EXH FAN | SPLIT TN2 SUPPLY FAN | T N2 APARTMENT ERV SUP FAN | T N2 APARTMENT ERV EXH FAN | SPLIT TS1 SUPPLY FAN | T S1 APARTMENT ERV SUP FAN | T S1 APARTMENT ERV EXH FAN | SPLIT TS2 SUPPLY FAN | T S2 APARTMENT ERV SUP FAN | T S2 APARTMENT ERV EXH FAN |ZoneTemperatureOscillationReportMonthly
| G SW APARTMENT | G NW APARTMENT | OFFICE | G NE APARTMENT | G N1 APARTMENT | G N2 APARTMENT | G S1 APARTMENT | G S2 APARTMENT | M SW APARTMENT | M NW APARTMENT | M SE APARTMENT | M NE APARTMENT | M N1 APARTMENT | M N2 APARTMENT | M S1 APARTMENT | M S2 APARTMENT | T SW APARTMENT | T NW APARTMENT | T SE APARTMENT | T NE APARTMENT | T N1 APARTMENT | T N2 APARTMENT | T S1 APARTMENT | T S2 APARTMENT | T CORRIDOR | G CORRIDOR | M CORRIDOR |AirLoopSystemEnergyAndWaterUseMonthly
| SPLIT GSW | SPLIT GNW | SPLIT OFFICE | SPLIT GNE | SPLIT GN1 | SPLIT GN2 | SPLIT GS1 | SPLIT GS2 | SPLIT MSW | SPLIT MNW | SPLIT MSE | SPLIT MNE | SPLIT MN1 | SPLIT MN2 | SPLIT MS1 | SPLIT MS2 | SPLIT TSW | SPLIT TNW | SPLIT TSE | SPLIT TNE | SPLIT TN1 | SPLIT TN2 | SPLIT TS1 | SPLIT TS2 |AirLoopSystemComponentLoadsMonthly
| SPLIT GSW | SPLIT GNW | SPLIT OFFICE | SPLIT GNE | SPLIT GN1 | SPLIT GN2 | SPLIT GS1 | SPLIT GS2 | SPLIT MSW | SPLIT MNW | SPLIT MSE | SPLIT MNE | SPLIT MN1 | SPLIT MN2 | SPLIT MS1 | SPLIT MS2 | SPLIT TSW | SPLIT TNW | SPLIT TSE | SPLIT TNE | SPLIT TN1 | SPLIT TN2 | SPLIT TS1 | SPLIT TS2 |AirLoopSystemComponentEnergyUseMonthly
| SPLIT GSW | SPLIT GNW | SPLIT OFFICE | SPLIT GNE | SPLIT GN1 | SPLIT GN2 | SPLIT GS1 | SPLIT GS2 | SPLIT MSW | SPLIT MNW | SPLIT MSE | SPLIT MNE | SPLIT MN1 | SPLIT MN2 | SPLIT MS1 | SPLIT MS2 | SPLIT TSW | SPLIT TNW | SPLIT TSE | SPLIT TNE | SPLIT TN1 | SPLIT TN2 | SPLIT TS1 | SPLIT TS2 |MechanicalVentilationLoadsMonthly
| G SW APARTMENT | G NW APARTMENT | OFFICE | G NE APARTMENT | G N1 APARTMENT | G N2 APARTMENT | G S1 APARTMENT | G S2 APARTMENT | M SW APARTMENT | M NW APARTMENT | M SE APARTMENT | M NE APARTMENT | M N1 APARTMENT | M N2 APARTMENT | M S1 APARTMENT | M S2 APARTMENT | T SW APARTMENT | T NW APARTMENT | T SE APARTMENT | T NE APARTMENT | T N1 APARTMENT | T N2 APARTMENT | T S1 APARTMENT | T S2 APARTMENT |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 09:15:25
General| Value | |
| Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 09:15 |
| RunPeriod | RUNPERIOD 1 |
| Weather File | San Diego-Brown Field Muni AP CA USA TMY3 WMO#=722904 |
| Latitude [deg] | 32.58 |
| Longitude [deg] | -117.0 |
| Elevation [m] | 159.00 |
| Time Zone | -8.0 |
| North Axis Angle [deg] | 0.00 |
| Rotation for Appendix G [deg] | 0.00 |
| Hours Simulated [hrs] | 8760.00 |
| Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
| Gross Wall Area [m2] | 1542.04 | 564.80 | 206.22 | 564.80 | 206.22 |
| Above Ground Wall Area [m2] | 1542.04 | 564.80 | 206.22 | 564.80 | 206.22 |
| Window Opening Area [m2] | 306.92 | 112.97 | 43.82 | 112.97 | 37.16 |
| Gross Window-Wall Ratio [%] | 19.90 | 20.00 | 21.25 | 20.00 | 18.02 |
| Above Ground Window-Wall Ratio [%] | 19.90 | 20.00 | 21.25 | 20.00 | 18.02 |
| Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
| Gross Wall Area [m2] | 1501.17 | 564.80 | 185.79 | 564.80 | 185.79 |
| Above Ground Wall Area [m2] | 1501.17 | 564.80 | 185.79 | 564.80 | 185.79 |
| Window Opening Area [m2] | 300.26 | 112.97 | 37.16 | 112.97 | 37.16 |
| Gross Window-Wall Ratio [%] | 20.00 | 20.00 | 20.00 | 20.00 | 20.00 |
| Above Ground Window-Wall Ratio [%] | 20.00 | 20.00 | 20.00 | 20.00 | 20.00 |
| Total | |
| Gross Roof Area [m2] | 783.65 |
| Skylight Area [m2] | 0.00 |
| Skylight-Roof Ratio [%] | 0.00 |
| Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
| G SW APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 0.00 | 11.71 | 11.71 | 8.6918 | 35.30 | 6.6700 |
| G NW APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 0.00 | 11.71 | 11.71 | 8.6918 | 35.30 | 6.6700 |
| OFFICE | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 0.00 | 11.71 | 11.71 | 9.7532 | 18.58 | 6.6700 |
| G NE APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 0.00 | 11.71 | 11.71 | 8.6918 | 35.30 | 6.6700 |
| G N1 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 0.00 | 7.06 | 7.06 | 8.6918 | 35.30 | 6.6700 |
| G N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 0.00 | 7.06 | 7.06 | 8.6918 | 35.30 | 6.6700 |
| G S1 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 0.00 | 7.06 | 7.06 | 8.6918 | 35.30 | 6.6700 |
| G S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 0.00 | 7.06 | 7.06 | 8.6918 | 35.30 | 6.6700 |
| M SW APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 58.52 | 0.00 | 11.71 | 11.71 | 8.6918 | 35.30 | 6.6700 |
| M NW APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 58.52 | 0.00 | 11.71 | 11.71 | 8.6918 | 35.30 | 6.6700 |
| M SE APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 58.52 | 0.00 | 11.71 | 11.71 | 8.6918 | 35.30 | 6.6700 |
| M NE APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 58.52 | 0.00 | 11.71 | 11.71 | 8.6918 | 35.30 | 6.6700 |
| M N1 APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 35.30 | 0.00 | 7.06 | 7.06 | 8.6918 | 35.30 | 6.6700 |
| M N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 35.30 | 0.00 | 7.06 | 7.06 | 8.6918 | 35.30 | 6.6700 |
| M S1 APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 35.30 | 0.00 | 7.06 | 7.06 | 8.6918 | 35.30 | 6.6700 |
| M S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 35.30 | 0.00 | 7.06 | 7.06 | 8.6918 | 35.30 | 6.6700 |
| T SW APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 0.00 | 11.71 | 11.71 | 8.6918 | 35.30 | 6.6700 |
| T NW APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 0.00 | 11.71 | 11.71 | 8.6918 | 35.30 | 6.6700 |
| T SE APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 0.00 | 11.71 | 11.71 | 8.6918 | 35.30 | 6.6700 |
| T NE APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 0.00 | 11.71 | 11.71 | 8.6918 | 35.30 | 6.6700 |
| T N1 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 0.00 | 7.06 | 7.06 | 8.6918 | 35.30 | 6.6700 |
| T N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 0.00 | 7.06 | 7.06 | 8.6918 | 35.30 | 6.6700 |
| T S1 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 0.00 | 7.06 | 7.06 | 8.6918 | 35.30 | 6.6700 |
| T S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 0.00 | 7.06 | 7.06 | 8.6918 | 35.30 | 6.6700 |
| T CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 0.00 | 1.11 | 1.11 | 4.7725 | 18.58 | 0.0000 |
| G CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 0.00 | 3.32 | 3.32 | 4.7725 | 18.58 | 105.2565 |
| M CORRIDOR | 77.66 | No | Yes | 236.69 | 2.00 | 10.22 | 0.00 | 1.11 | 1.11 | 4.7725 | 18.58 | 0.0000 |
| Total | 3134.61 | 9553.84 | 1542.04 | 0.00 | 306.92 | 306.92 | 8.3333 | 31.67 | 8.6167 | |||
| Conditioned Total | 2823.98 | 8607.06 | 1501.17 | 0.00 | 300.26 | 300.26 | 8.7250 | 34.33 | 6.6700 | |||
| Unconditioned Total | 310.64 | 946.78 | 40.87 | 0.00 | 6.66 | 6.66 | 4.7725 | 18.58 | 26.3141 | |||
| Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
| G SW APARTMENT | 88.25 | Yes | Yes | 1.00 | G SW APARTMENT | GENERAL | G SW APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| G NW APARTMENT | 88.25 | Yes | Yes | 1.00 | G NW APARTMENT | GENERAL | G NW APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| OFFICE | 88.25 | Yes | Yes | 1.00 | OFFICE | GENERAL | OFFICE | 9.7532 | 18.58 | 6.6700 | |
| G NE APARTMENT | 88.25 | Yes | Yes | 1.00 | G NE APARTMENT | GENERAL | G NE APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| G N1 APARTMENT | 88.25 | Yes | Yes | 1.00 | G N1 APARTMENT | GENERAL | G N1 APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| G N2 APARTMENT | 88.25 | Yes | Yes | 1.00 | G N2 APARTMENT | GENERAL | G N2 APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| G S1 APARTMENT | 88.25 | Yes | Yes | 1.00 | G S1 APARTMENT | GENERAL | G S1 APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| G S2 APARTMENT | 88.25 | Yes | Yes | 1.00 | G S2 APARTMENT | GENERAL | G S2 APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| M SW APARTMENT | 88.25 | Yes | Yes | 2.00 | M SW APARTMENT | GENERAL | M SW APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| M NW APARTMENT | 88.25 | Yes | Yes | 2.00 | M NW APARTMENT | GENERAL | M NW APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| M SE APARTMENT | 88.25 | Yes | Yes | 2.00 | M SE APARTMENT | GENERAL | M SE APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| M NE APARTMENT | 88.25 | Yes | Yes | 2.00 | M NE APARTMENT | GENERAL | M NE APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| M N1 APARTMENT | 88.25 | Yes | Yes | 2.00 | M N1 APARTMENT | GENERAL | M N1 APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| M N2 APARTMENT | 88.25 | Yes | Yes | 2.00 | M N2 APARTMENT | GENERAL | M N2 APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| M S1 APARTMENT | 88.25 | Yes | Yes | 2.00 | M S1 APARTMENT | GENERAL | M S1 APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| M S2 APARTMENT | 88.25 | Yes | Yes | 2.00 | M S2 APARTMENT | GENERAL | M S2 APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| T SW APARTMENT | 88.25 | Yes | Yes | 1.00 | T SW APARTMENT | GENERAL | T SW APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| T NW APARTMENT | 88.25 | Yes | Yes | 1.00 | T NW APARTMENT | GENERAL | T NW APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| T SE APARTMENT | 88.25 | Yes | Yes | 1.00 | T SE APARTMENT | GENERAL | T SE APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| T NE APARTMENT | 88.25 | Yes | Yes | 1.00 | T NE APARTMENT | GENERAL | T NE APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| T N1 APARTMENT | 88.25 | Yes | Yes | 1.00 | T N1 APARTMENT | GENERAL | T N1 APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| T N2 APARTMENT | 88.25 | Yes | Yes | 1.00 | T N2 APARTMENT | GENERAL | T N2 APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| T S1 APARTMENT | 88.25 | Yes | Yes | 1.00 | T S1 APARTMENT | GENERAL | T S1 APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| T S2 APARTMENT | 88.25 | Yes | Yes | 1.00 | T S2 APARTMENT | GENERAL | T S2 APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| T CORRIDOR | 77.66 | No | Yes | 1.00 | T CORRIDOR | GENERAL | T CORRIDOR | 4.7725 | 18.58 | 0.0000 | |
| G CORRIDOR | 77.66 | No | Yes | 1.00 | G CORRIDOR | GENERAL | G CORRIDOR | 4.7725 | 18.58 | 105.2565 | |
| M CORRIDOR | 77.66 | No | Yes | 2.00 | M CORRIDOR | GENERAL | M CORRIDOR | 4.7725 | 18.58 | 0.0000 | |
| Total | 3134.61 | 8.3333 | 15.84 | 8.6167 | |||||||
| Conditioned Total | 2823.98 | 8.7250 | 17.17 | 6.6700 | |||||||
| Unconditioned Total | 310.64 | 4.7725 | 9.29 | 26.3141 | |||||||
| Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
| Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
| GENERAL | 3134.61 | 2823.98 | 310.64 | 0.00 | 6.2575 | 41.91 | 7.1145 |
| Total | 3134.61 | 2823.98 | 310.64 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 09:15:25
End Uses| Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
| Time of Peak | 19-AUG-16:30 | 30-MAR-03:00 | - | - | - | - | - | - | - | - | - | - | 01-JAN-07:10 |
| Heating | 0.00 | 30396.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Cooling | 13756.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Lighting | 4289.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment | 22609.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans | 5778.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems | 30593.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Total End Uses | 77028.25 | 30396.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
| Heating | General | 0.00 | 30396.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Cooling | General | 13756.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Lighting | LightsWired | 4034.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LightsPlugIn | 254.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment | MiscPlug | 18441.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| ElevatorLift | 4006.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| ElevatorLightsFan | 162.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| General | 5778.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems | Water Heater | 30593.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 09:15:25
Values gathered over 8760.00 hours| Source Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
| Heating | 0.00 | 27.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Cooling | 262.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Lighting | 314.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Lighting | 158.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment | 1452.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans | 243.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems | 1342.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Total Source Energy End Use Components | 3773.86 | 27.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
| Heating | 0.00 | 9.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Cooling | 92.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Lighting | 111.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Lighting | 56.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment | 514.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans | 86.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems | 475.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Total Source Energy End Use Components | 1336.36 | 9.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
| Heating | 0.00 | 8.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Cooling | 83.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Lighting | 100.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Lighting | 50.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment | 463.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans | 77.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems | 428.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Total Source Energy End Use Components | 1203.93 | 8.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 09:15:25
ZoneHVAC:EnergyRecoveryVentilator| User-Specified Supply Air Flow Rate [m3/s] | User-Specified Exhaust Air Flow Rate [m3/s] | |
| G SW APARTMENT ERV | 0.025955 | 0.025955 |
| G NW APARTMENT ERV | 0.025955 | 0.025955 |
| G NE APARTMENT ERV | 0.025955 | 0.025955 |
| G N1 APARTMENT ERV | 0.025955 | 0.025955 |
| G N2 APARTMENT ERV | 0.025955 | 0.025955 |
| G S1 APARTMENT ERV | 0.025955 | 0.025955 |
| G S2 APARTMENT ERV | 0.025955 | 0.025955 |
| M SW APARTMENT ERV | 0.051909 | 0.051909 |
| M NW APARTMENT ERV | 0.051909 | 0.051909 |
| M SE APARTMENT ERV | 0.051909 | 0.051909 |
| M NE APARTMENT ERV | 0.051909 | 0.051909 |
| M N1 APARTMENT ERV | 0.051909 | 0.051909 |
| M N2 APARTMENT ERV | 0.051909 | 0.051909 |
| M S1 APARTMENT ERV | 0.051909 | 0.051909 |
| M S2 APARTMENT ERV | 0.051909 | 0.051909 |
| T SW APARTMENT ERV | 0.025955 | 0.025955 |
| T NW APARTMENT ERV | 0.025955 | 0.025955 |
| T SE APARTMENT ERV | 0.025955 | 0.025955 |
| T NE APARTMENT ERV | 0.025955 | 0.025955 |
| T N1 APARTMENT ERV | 0.025955 | 0.025955 |
| T N2 APARTMENT ERV | 0.025955 | 0.025955 |
| T S1 APARTMENT ERV | 0.025955 | 0.025955 |
| T S2 APARTMENT ERV | 0.025955 | 0.025955 |
| Design Size Maximum Flow Rate [m3/s] | |
| G SW APARTMENT ERV SUP FAN | 0.025955 |
| G SW APARTMENT ERV EXH FAN | 0.025955 |
| G NW APARTMENT ERV SUP FAN | 0.025955 |
| G NW APARTMENT ERV EXH FAN | 0.025955 |
| G NE APARTMENT ERV SUP FAN | 0.025955 |
| G NE APARTMENT ERV EXH FAN | 0.025955 |
| G N1 APARTMENT ERV SUP FAN | 0.025955 |
| G N1 APARTMENT ERV EXH FAN | 0.025955 |
| G N2 APARTMENT ERV SUP FAN | 0.025955 |
| G N2 APARTMENT ERV EXH FAN | 0.025955 |
| G S1 APARTMENT ERV SUP FAN | 0.025955 |
| G S1 APARTMENT ERV EXH FAN | 0.025955 |
| G S2 APARTMENT ERV SUP FAN | 0.025955 |
| G S2 APARTMENT ERV EXH FAN | 0.025955 |
| M SW APARTMENT ERV SUP FAN | 0.051909 |
| M SW APARTMENT ERV EXH FAN | 0.051909 |
| M NW APARTMENT ERV SUP FAN | 0.051909 |
| M NW APARTMENT ERV EXH FAN | 0.051909 |
| M SE APARTMENT ERV SUP FAN | 0.051909 |
| M SE APARTMENT ERV EXH FAN | 0.051909 |
| M NE APARTMENT ERV SUP FAN | 0.051909 |
| M NE APARTMENT ERV EXH FAN | 0.051909 |
| M N1 APARTMENT ERV SUP FAN | 0.051909 |
| M N1 APARTMENT ERV EXH FAN | 0.051909 |
| M N2 APARTMENT ERV SUP FAN | 0.051909 |
| M N2 APARTMENT ERV EXH FAN | 0.051909 |
| M S1 APARTMENT ERV SUP FAN | 0.051909 |
| M S1 APARTMENT ERV EXH FAN | 0.051909 |
| M S2 APARTMENT ERV SUP FAN | 0.051909 |
| M S2 APARTMENT ERV EXH FAN | 0.051909 |
| T SW APARTMENT ERV SUP FAN | 0.025955 |
| T SW APARTMENT ERV EXH FAN | 0.025955 |
| T NW APARTMENT ERV SUP FAN | 0.025955 |
| T NW APARTMENT ERV EXH FAN | 0.025955 |
| T SE APARTMENT ERV SUP FAN | 0.025955 |
| T SE APARTMENT ERV EXH FAN | 0.025955 |
| T NE APARTMENT ERV SUP FAN | 0.025955 |
| T NE APARTMENT ERV EXH FAN | 0.025955 |
| T N1 APARTMENT ERV SUP FAN | 0.025955 |
| T N1 APARTMENT ERV EXH FAN | 0.025955 |
| T N2 APARTMENT ERV SUP FAN | 0.025955 |
| T N2 APARTMENT ERV EXH FAN | 0.025955 |
| T S1 APARTMENT ERV SUP FAN | 0.025955 |
| T S1 APARTMENT ERV EXH FAN | 0.025955 |
| T S2 APARTMENT ERV SUP FAN | 0.025955 |
| T S2 APARTMENT ERV EXH FAN | 0.025955 |
| SPLIT GSW SUPPLY FAN | 0.305976 |
| SPLIT GNW SUPPLY FAN | 0.280728 |
| SPLIT OFFICE SUPPLY FAN | 0.359290 |
| SPLIT GNE SUPPLY FAN | 0.261816 |
| SPLIT GN1 SUPPLY FAN | 0.246856 |
| SPLIT GN2 SUPPLY FAN | 0.246422 |
| SPLIT GS1 SUPPLY FAN | 0.271117 |
| SPLIT GS2 SUPPLY FAN | 0.273101 |
| SPLIT MSW SUPPLY FAN | 0.757939 |
| SPLIT MNW SUPPLY FAN | 0.711392 |
| SPLIT MSE SUPPLY FAN | 0.706085 |
| SPLIT MNE SUPPLY FAN | 0.660142 |
| SPLIT MN1 SUPPLY FAN | 0.605732 |
| SPLIT MN2 SUPPLY FAN | 0.604686 |
| SPLIT MS1 SUPPLY FAN | 0.657390 |
| SPLIT MS2 SUPPLY FAN | 0.656271 |
| SPLIT TSW SUPPLY FAN | 0.402668 |
| SPLIT TNW SUPPLY FAN | 0.384552 |
| SPLIT TSE SUPPLY FAN | 0.362846 |
| SPLIT TNE SUPPLY FAN | 0.344729 |
| SPLIT TN1 SUPPLY FAN | 0.327037 |
| SPLIT TN2 SUPPLY FAN | 0.325524 |
| SPLIT TS1 SUPPLY FAN | 0.346569 |
| SPLIT TS2 SUPPLY FAN | 0.345056 |
| Design Size Nominal Supply Air Flow Rate [m3/s] | |
| G SW APARTMENT OA HEAT EXCHANGER | 0.025955 |
| G NW APARTMENT OA HEAT EXCHANGER | 0.025955 |
| G NE APARTMENT OA HEAT EXCHANGER | 0.025955 |
| G N1 APARTMENT OA HEAT EXCHANGER | 0.025955 |
| G N2 APARTMENT OA HEAT EXCHANGER | 0.025955 |
| G S1 APARTMENT OA HEAT EXCHANGER | 0.025955 |
| G S2 APARTMENT OA HEAT EXCHANGER | 0.025955 |
| M SW APARTMENT OA HEAT EXCHANGER | 0.051909 |
| M NW APARTMENT OA HEAT EXCHANGER | 0.051909 |
| M SE APARTMENT OA HEAT EXCHANGER | 0.051909 |
| M NE APARTMENT OA HEAT EXCHANGER | 0.051909 |
| M N1 APARTMENT OA HEAT EXCHANGER | 0.051909 |
| M N2 APARTMENT OA HEAT EXCHANGER | 0.051909 |
| M S1 APARTMENT OA HEAT EXCHANGER | 0.051909 |
| M S2 APARTMENT OA HEAT EXCHANGER | 0.051909 |
| T SW APARTMENT OA HEAT EXCHANGER | 0.025955 |
| T NW APARTMENT OA HEAT EXCHANGER | 0.025955 |
| T SE APARTMENT OA HEAT EXCHANGER | 0.025955 |
| T NE APARTMENT OA HEAT EXCHANGER | 0.025955 |
| T N1 APARTMENT OA HEAT EXCHANGER | 0.025955 |
| T N2 APARTMENT OA HEAT EXCHANGER | 0.025955 |
| T S1 APARTMENT OA HEAT EXCHANGER | 0.025955 |
| T S2 APARTMENT OA HEAT EXCHANGER | 0.025955 |
| Design Size Maximum Air Flow Rate [m3/s] | |
| G SW APARTMENT DIRECT AIR | 0.305976 |
| G NW APARTMENT DIRECT AIR | 0.280728 |
| OFFICE DIRECT AIR | 0.359290 |
| G NE APARTMENT DIRECT AIR | 0.261816 |
| G N1 APARTMENT DIRECT AIR | 0.246856 |
| G N2 APARTMENT DIRECT AIR | 0.246422 |
| G S1 APARTMENT DIRECT AIR | 0.271117 |
| G S2 APARTMENT DIRECT AIR | 0.273101 |
| M SW APARTMENT DIRECT AIR | 0.757939 |
| M NW APARTMENT DIRECT AIR | 0.711392 |
| M SE APARTMENT DIRECT AIR | 0.706085 |
| M NE APARTMENT DIRECT AIR | 0.660142 |
| M N1 APARTMENT DIRECT AIR | 0.605732 |
| M N2 APARTMENT DIRECT AIR | 0.604686 |
| M S1 APARTMENT DIRECT AIR | 0.657390 |
| M S2 APARTMENT DIRECT AIR | 0.656271 |
| T SW APARTMENT DIRECT AIR | 0.402668 |
| T NW APARTMENT DIRECT AIR | 0.384552 |
| T SE APARTMENT DIRECT AIR | 0.362846 |
| T NE APARTMENT DIRECT AIR | 0.344729 |
| T N1 APARTMENT DIRECT AIR | 0.327037 |
| T N2 APARTMENT DIRECT AIR | 0.325524 |
| T S1 APARTMENT DIRECT AIR | 0.346569 |
| T S2 APARTMENT DIRECT AIR | 0.345056 |
| Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
| SPLIT GSW | 0.305976 | 0.305976 | 0.305976 | 0.305976 | 0.305976 | 0.305976 | 1.00 | 1.00 | 0.305976 |
| SPLIT GNW | 0.280728 | 0.280728 | 0.280728 | 0.280728 | 0.280728 | 0.280728 | 1.00 | 1.00 | 0.280728 |
| SPLIT OFFICE | 0.359290 | 0.359290 | 0.359290 | 0.359290 | 0.359290 | 0.359290 | 1.00 | 1.000000 | 0.359290 |
| SPLIT GNE | 0.261816 | 0.261816 | 0.261816 | 0.261816 | 0.261816 | 0.261816 | 1.00 | 1.00 | 0.261816 |
| SPLIT GN1 | 0.246856 | 0.246856 | 0.246856 | 0.246856 | 0.246856 | 0.246856 | 1.00 | 1.00 | 0.246856 |
| SPLIT GN2 | 0.246422 | 0.246422 | 0.246422 | 0.246422 | 0.246422 | 0.246422 | 1.00 | 1.000000 | 0.246422 |
| SPLIT GS1 | 0.271117 | 0.271117 | 0.271117 | 0.271117 | 0.271117 | 0.271117 | 1.00 | 1.00 | 0.271117 |
| SPLIT GS2 | 0.273101 | 0.273101 | 0.273101 | 0.273101 | 0.273101 | 0.273101 | 1.00 | 1.000000 | 0.273101 |
| SPLIT MSW | 0.757939 | 0.757939 | 0.757939 | 0.757939 | 0.757939 | 0.757939 | 1.00 | 1.00 | 0.757939 |
| SPLIT MNW | 0.711392 | 0.711392 | 0.711392 | 0.711392 | 0.711392 | 0.711392 | 1.00 | 1.00 | 0.711392 |
| SPLIT MSE | 0.706085 | 0.706085 | 0.706085 | 0.706085 | 0.706085 | 0.706085 | 1.00 | 1.00 | 0.706085 |
| SPLIT MNE | 0.660142 | 0.660142 | 0.660142 | 0.660142 | 0.660142 | 0.660142 | 1.00 | 1.00 | 0.660142 |
| SPLIT MN1 | 0.605732 | 0.605732 | 0.605732 | 0.605732 | 0.605732 | 0.605732 | 1.00 | 1.00 | 0.605732 |
| SPLIT MN2 | 0.604686 | 0.604686 | 0.604686 | 0.604686 | 0.604686 | 0.604686 | 1.00 | 1.00 | 0.604686 |
| SPLIT MS1 | 0.657390 | 0.657390 | 0.657390 | 0.657390 | 0.657390 | 0.657390 | 1.00 | 1.00 | 0.657390 |
| SPLIT MS2 | 0.656271 | 0.656271 | 0.656271 | 0.656271 | 0.656271 | 0.656271 | 1.00 | 1.00 | 0.656271 |
| SPLIT TSW | 0.402668 | 0.402668 | 0.402668 | 0.402668 | 0.402668 | 0.402668 | 1.00 | 1.000000 | 0.402668 |
| SPLIT TNW | 0.384552 | 0.384552 | 0.384552 | 0.384552 | 0.384552 | 0.384552 | 1.00 | 1.00 | 0.384552 |
| SPLIT TSE | 0.362846 | 0.362846 | 0.362846 | 0.362846 | 0.362846 | 0.362846 | 1.00 | 1.00 | 0.362846 |
| SPLIT TNE | 0.344729 | 0.344729 | 0.344729 | 0.344729 | 0.344729 | 0.344729 | 1.00 | 1.00 | 0.344729 |
| SPLIT TN1 | 0.327037 | 0.327037 | 0.327037 | 0.327037 | 0.327037 | 0.327037 | 1.00 | 1.000000 | 0.327037 |
| SPLIT TN2 | 0.325524 | 0.325524 | 0.325524 | 0.325524 | 0.325524 | 0.325524 | 1.00 | 1.00 | 0.325524 |
| SPLIT TS1 | 0.346569 | 0.346569 | 0.346569 | 0.346569 | 0.346569 | 0.346569 | 1.00 | 1.000000 | 0.346569 |
| SPLIT TS2 | 0.345056 | 0.345056 | 0.345056 | 0.345056 | 0.345056 | 0.345056 | 1.00 | 1.00 | 0.345056 |
| Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
| SPLIT GSW_OA_CONTROLLER | 0.305976 | 0.025955 |
| SPLIT GNW_OA_CONTROLLER | 0.280728 | 0.025955 |
| SPLIT OFFICE_OA_CONTROLLER | 0.359290 | 0.038106 |
| SPLIT GNE_OA_CONTROLLER | 0.261816 | 0.025955 |
| SPLIT GN1_OA_CONTROLLER | 0.246856 | 0.025955 |
| SPLIT GN2_OA_CONTROLLER | 0.246422 | 0.025955 |
| SPLIT GS1_OA_CONTROLLER | 0.271117 | 0.025955 |
| SPLIT GS2_OA_CONTROLLER | 0.273101 | 0.025955 |
| SPLIT MSW_OA_CONTROLLER | 0.757939 | 0.051909 |
| SPLIT MNW_OA_CONTROLLER | 0.711392 | 0.051909 |
| SPLIT MSE_OA_CONTROLLER | 0.706085 | 0.051909 |
| SPLIT MNE_OA_CONTROLLER | 0.660142 | 0.051909 |
| SPLIT MN1_OA_CONTROLLER | 0.605732 | 0.051909 |
| SPLIT MN2_OA_CONTROLLER | 0.604686 | 0.051909 |
| SPLIT MS1_OA_CONTROLLER | 0.657390 | 0.051909 |
| SPLIT MS2_OA_CONTROLLER | 0.656271 | 0.051909 |
| SPLIT TSW_OA_CONTROLLER | 0.402668 | 0.025955 |
| SPLIT TNW_OA_CONTROLLER | 0.384552 | 0.025955 |
| SPLIT TSE_OA_CONTROLLER | 0.362846 | 0.025955 |
| SPLIT TNE_OA_CONTROLLER | 0.344729 | 0.025955 |
| SPLIT TN1_OA_CONTROLLER | 0.327037 | 0.025955 |
| SPLIT TN2_OA_CONTROLLER | 0.325524 | 0.025955 |
| SPLIT TS1_OA_CONTROLLER | 0.346569 | 0.025955 |
| SPLIT TS2_OA_CONTROLLER | 0.345056 | 0.025955 |
| Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | Design Size Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
| SPLIT GSW_UNITARY_PACKAGE_DX | 0.305976 | 0.305976 | 0.305976 | 0.305976 | 5064.99 | 7400.80 | 40.00 | 1.00 |
| SPLIT GNW_UNITARY_PACKAGE_DX | 0.280728 | 0.280728 | 0.280728 | 0.280728 | 4647.04 | 6834.02 | 40.00 | 1.00 |
| SPLIT OFFICE_UNITARY_PACKAGE_DX | 0.359290 | 0.359290 | 0.359290 | 0.359290 | 5947.53 | 8846.95 | 40.00 | 1.00 |
| SPLIT GNE_UNITARY_PACKAGE_DX | 0.261816 | 0.261816 | 0.261816 | 0.261816 | 4333.98 | 6409.55 | 40.00 | 1.00 |
| SPLIT GN1_UNITARY_PACKAGE_DX | 0.246856 | 0.246856 | 0.246856 | 0.246856 | 4086.35 | 6073.72 | 40.00 | 1.00 |
| SPLIT GN2_UNITARY_PACKAGE_DX | 0.246422 | 0.246422 | 0.246422 | 0.246422 | 4079.16 | 6063.97 | 40.00 | 1.00 |
| SPLIT GS1_UNITARY_PACKAGE_DX | 0.271117 | 0.271117 | 0.271117 | 0.271117 | 4487.96 | 6618.34 | 40.00 | 1.00 |
| SPLIT GS2_UNITARY_PACKAGE_DX | 0.273101 | 0.273101 | 0.273101 | 0.273101 | 4520.80 | 6662.86 | 40.00 | 1.00 |
| SPLIT MSW_UNITARY_PACKAGE_DX | 0.757939 | 0.757939 | 0.757939 | 0.757939 | 12546.58 | 18078.42 | 40.00 | 1.00 |
| SPLIT MNW_UNITARY_PACKAGE_DX | 0.711392 | 0.711392 | 0.711392 | 0.711392 | 11776.07 | 17033.45 | 40.00 | 1.00 |
| SPLIT MSE_UNITARY_PACKAGE_DX | 0.706085 | 0.706085 | 0.706085 | 0.706085 | 11688.21 | 16914.55 | 40.00 | 1.00 |
| SPLIT MNE_UNITARY_PACKAGE_DX | 0.660142 | 0.660142 | 0.660142 | 0.660142 | 10927.69 | 15883.14 | 40.00 | 1.00 |
| SPLIT MN1_UNITARY_PACKAGE_DX | 0.605732 | 0.605732 | 0.605732 | 0.605732 | 10027.02 | 14661.73 | 40.00 | 1.00 |
| SPLIT MN2_UNITARY_PACKAGE_DX | 0.604686 | 0.604686 | 0.604686 | 0.604686 | 10009.70 | 14638.25 | 40.00 | 1.00 |
| SPLIT MS1_UNITARY_PACKAGE_DX | 0.657390 | 0.657390 | 0.657390 | 0.657390 | 10882.14 | 15821.36 | 40.00 | 1.00 |
| SPLIT MS2_UNITARY_PACKAGE_DX | 0.656271 | 0.656271 | 0.656271 | 0.656271 | 10863.62 | 15796.26 | 40.00 | 1.00 |
| SPLIT TSW_UNITARY_PACKAGE_DX | 0.402668 | 0.402668 | 0.402668 | 0.402668 | 6665.58 | 9571.27 | 40.00 | 1.00 |
| SPLIT TNW_UNITARY_PACKAGE_DX | 0.384552 | 0.384552 | 0.384552 | 0.384552 | 6365.70 | 9164.52 | 40.00 | 1.00 |
| SPLIT TSE_UNITARY_PACKAGE_DX | 0.362846 | 0.362846 | 0.362846 | 0.362846 | 6006.39 | 8677.46 | 40.00 | 1.00 |
| SPLIT TNE_UNITARY_PACKAGE_DX | 0.344729 | 0.344729 | 0.344729 | 0.344729 | 5706.49 | 8270.69 | 40.00 | 1.00 |
| SPLIT TN1_UNITARY_PACKAGE_DX | 0.327037 | 0.327037 | 0.327037 | 0.327037 | 5413.63 | 7873.44 | 40.00 | 1.00 |
| SPLIT TN2_UNITARY_PACKAGE_DX | 0.325524 | 0.325524 | 0.325524 | 0.325524 | 5388.57 | 7839.47 | 40.00 | 1.00 |
| SPLIT TS1_UNITARY_PACKAGE_DX | 0.346569 | 0.346569 | 0.346569 | 0.346569 | 5736.94 | 8311.94 | 40.00 | 1.00 |
| SPLIT TS2_UNITARY_PACKAGE_DX | 0.345056 | 0.345056 | 0.345056 | 0.345056 | 5711.91 | 8277.99 | 40.00 | 1.00 |
| Design Size Rated Air Flow Rate [m3/s] | Design Size Gross Rated Total Cooling Capacity [W] | Design Size Gross Rated Sensible Heat Ratio | |
| SPLIT GSW COOLING COIL | 0.305976 | 5064.99 | 0.800655 |
| SPLIT GNW COOLING COIL | 0.280728 | 4647.04 | 0.800655 |
| SPLIT OFFICE COOLING COIL | 0.359290 | 5947.53 | 0.800655 |
| SPLIT GNE COOLING COIL | 0.261816 | 4333.98 | 0.800655 |
| SPLIT GN1 COOLING COIL | 0.246856 | 4086.35 | 0.800655 |
| SPLIT GN2 COOLING COIL | 0.246422 | 4079.16 | 0.800655 |
| SPLIT GS1 COOLING COIL | 0.271117 | 4487.96 | 0.800655 |
| SPLIT GS2 COOLING COIL | 0.273101 | 4520.80 | 0.800655 |
| SPLIT MSW COOLING COIL | 0.757939 | 12546.58 | 0.800655 |
| SPLIT MNW COOLING COIL | 0.711392 | 11776.07 | 0.800655 |
| SPLIT MSE COOLING COIL | 0.706085 | 11688.21 | 0.800655 |
| SPLIT MNE COOLING COIL | 0.660142 | 10927.69 | 0.800655 |
| SPLIT MN1 COOLING COIL | 0.605732 | 10027.02 | 0.800655 |
| SPLIT MN2 COOLING COIL | 0.604686 | 10009.70 | 0.800655 |
| SPLIT MS1 COOLING COIL | 0.657390 | 10882.14 | 0.800655 |
| SPLIT MS2 COOLING COIL | 0.656271 | 10863.62 | 0.800655 |
| SPLIT TSW COOLING COIL | 0.402668 | 6665.58 | 0.800655 |
| SPLIT TNW COOLING COIL | 0.384552 | 6365.70 | 0.800655 |
| SPLIT TSE COOLING COIL | 0.362846 | 6006.39 | 0.800655 |
| SPLIT TNE COOLING COIL | 0.344729 | 5706.49 | 0.800655 |
| SPLIT TN1 COOLING COIL | 0.327037 | 5413.63 | 0.800655 |
| SPLIT TN2 COOLING COIL | 0.325524 | 5388.57 | 0.800655 |
| SPLIT TS1 COOLING COIL | 0.346569 | 5736.94 | 0.800655 |
| SPLIT TS2 COOLING COIL | 0.345056 | 5711.91 | 0.800655 |
| Design Size Nominal Capacity [W] | |
| SPLIT GSW HEATING COIL | 7400.80 |
| SPLIT GNW HEATING COIL | 6834.02 |
| SPLIT OFFICE HEATING COIL | 8846.95 |
| SPLIT GNE HEATING COIL | 6409.55 |
| SPLIT GN1 HEATING COIL | 6073.72 |
| SPLIT GN2 HEATING COIL | 6063.97 |
| SPLIT GS1 HEATING COIL | 6618.34 |
| SPLIT GS2 HEATING COIL | 6662.86 |
| SPLIT MSW HEATING COIL | 18078.42 |
| SPLIT MNW HEATING COIL | 17033.45 |
| SPLIT MSE HEATING COIL | 16914.55 |
| SPLIT MNE HEATING COIL | 15883.14 |
| SPLIT MN1 HEATING COIL | 14661.73 |
| SPLIT MN2 HEATING COIL | 14638.25 |
| SPLIT MS1 HEATING COIL | 15821.36 |
| SPLIT MS2 HEATING COIL | 15796.26 |
| SPLIT TSW HEATING COIL | 9571.27 |
| SPLIT TNW HEATING COIL | 9164.52 |
| SPLIT TSE HEATING COIL | 8677.46 |
| SPLIT TNE HEATING COIL | 8270.69 |
| SPLIT TN1 HEATING COIL | 7873.44 |
| SPLIT TN2 HEATING COIL | 7839.47 |
| SPLIT TS1 HEATING COIL | 8311.94 |
| SPLIT TS2 HEATING COIL | 8277.99 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 09:15:25
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other Surfaces| None |
| Possible Shadow Receivers | |
| G SWALL SWA | GWINDOW1 S SWA | |
| G WWALL SWA | GWINDOW1 W SWA | |
| G NWALL NWA | GWINDOW1 N NWA | |
| G WWALL NWA | GWINDOW1 W NWA | |
| G SWALL SEA | GWINDOW1 S SEA | |
| G EWALL SEA | GWINDOW1 E SEA | |
| G NWALL NEA | GWINDOW1 N NEA | |
| G EWALL NEA | GWINDOW1 E NEA | |
| G NWALL N1A | GWINDOW1 N N1A | |
| G NWALL N2A | GWINDOW1 N N2A | |
| G SWALL S1A | GWINDOW1 S S1A | |
| G SWALL S2A | GWINDOW1 S S2A | |
| M WWALL SWA | MWINDOW1 W SWA | |
| M SWALL SWA | MWINDOW1 S SWA | |
| M NWALL NWA | MWINDOW1 N NWA | |
| M WWALL NWA | MWINDOW1 W NWA | |
| M EWALL SEA | MWINDOW1 E SEA | |
| M SWALL SEA | MWINDOW1 S SEA | |
| M NWALL NEA | MWINDOW1 N NEA | |
| M EWALL NEA | MWINDOW1 E NEA | |
| M NWALL N1A | MWINDOW1 N N1A | |
| M NWALL N2A | MWINDOW1 N N2A | |
| M SWALL S1A | MWINDOW1 S S1A | |
| M SWALL S2A | MWINDOW1 S S2A | |
| T WWALL SWA | TWINDOW1 W SWA | |
| T SWALL SWA | TWINDOW1 S SWA | |
| T NWALL NWA | TWINDOW1 N NWA | |
| T WWALL NWA | TWINDOW1 W NWA | |
| T EWALL SEA | TWINDOW1 E SEA | |
| T SWALL SEA | TWINDOW1 S SEA | |
| T NWALL NEA | TWINDOW1 N NEA | |
| T EWALL NEA | TWINDOW1 E NEA | |
| T NWALL N1A | TWINDOW1 N N1A | |
| T NWALL N2A | TWINDOW1 N N2A | |
| T SWALL S1A | TWINDOW1 S S1A | |
| T SWALL S2A | TWINDOW1 S S2A | |
| T EWALL C | TWINDOW14 | |
| G EWALL C | ENTRANCE DOOR | |
| M EWALL C | MWINDOW14 | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 09:15:25
Time Not Meeting the Adaptive Comfort Models during Occupied Hours| ASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 09:15:25
Version| Version ID | |
| 1 | 22.1 |
| #TimeSteps | Minutes per TimeStep {minutes} | |
| 1 | 6 | 10 |
| Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
| 1 | 1 | 20 | 2 | 8 |
| Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
| 1 | Yes | Yes | No | No | Yes | No |
| Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
| 1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
| Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
| 1 | 0.556 | 0.556 |
| Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
| 1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
| Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
| 1 | 18.80 | 14.30 | 13.60 | 13.20 | 13.30 | 12.60 | 15.30 | 15.60 | 17.70 | 19.40 | 19.70 | 18.50 |
| Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
| 1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
| Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
| 1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
| Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
| 1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
| Normal | Daylighting {dimensionless} | |
| 1 | 1.000 | 1.000 |
| Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
| 1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
| Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
| 1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
| Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
| 1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
| Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
| 1 | San Diego-Brown Field Muni AP CA USA TMY3 WMO#=722904 | 32.58 | -116.98 | -8.00 | 159.00 | 99429 | 1.1818 |
| Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
| 1 | Correlation | NA | 16.00 | 7.10 | NA |
| Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
| 1 | ApartmentMidRise | 0.000 | City | 4.00000E-002 | 0.40000 | FullExterior | 25 | 6 |
| Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
| 1 | TARP |
| Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
| 1 | TARP |
| Value {Anisotropic} | |
| 1 | Anisotropic |
| Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
| 1 | ThirdOrderBackwardDifference |
| Simulation {Yes/No} | Carbon Dioxide Concentration | |
| 1 | No | N/A |
| Simulation {Yes/No} | Generic Contaminant Concentration | |
| 1 | No | N/A |
| Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
| 1 | No | N/A | N/A | N/A |
| Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
| 1 | RegulaFalsi |
| Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
| 1 | 0.330 | 460.000 | 6.500000E-003 |
| Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
| 1 | LowerLeftCorner | Clockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
| Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
| 1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
| Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
| 1 | 0 | 0 | 0 |
| Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
| 1 | 27 | 243 | 39 |
| Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
| 1 | G SW APARTMENT | 0.0 | 0.00 | 0.00 | 0.00 | 5.79 | 3.81 | 1.52 | 1 | 1 | 1 | 0.00 | 11.58 | 0.00 | 7.62 | 0.00 | 3.05 | 3.05 | 268.97 | TARP | TARP | 88.25 | 58.52 | 46.82 | 11.71 | 6 | 2 | 0 | Yes |
| 2 | G NW APARTMENT | 0.0 | 0.00 | 9.30 | 0.00 | 5.79 | 13.11 | 1.52 | 1 | 1 | 1 | 0.00 | 11.58 | 9.30 | 16.92 | 0.00 | 3.05 | 3.05 | 268.97 | TARP | TARP | 88.25 | 58.52 | 46.82 | 11.71 | 6 | 2 | 0 | Yes |
| 3 | OFFICE | 0.0 | 34.75 | 0.00 | 0.00 | 40.54 | 3.81 | 1.52 | 1 | 1 | 1 | 34.75 | 46.33 | 0.00 | 7.62 | 0.00 | 3.05 | 3.05 | 268.97 | TARP | TARP | 88.25 | 58.52 | 46.82 | 11.71 | 6 | 2 | 0 | Yes |
| 4 | G NE APARTMENT | 0.0 | 34.75 | 9.30 | 0.00 | 40.54 | 13.11 | 1.52 | 1 | 1 | 1 | 34.75 | 46.33 | 9.30 | 16.92 | 0.00 | 3.05 | 3.05 | 268.97 | TARP | TARP | 88.25 | 58.52 | 46.82 | 11.71 | 6 | 2 | 0 | Yes |
| 5 | G N1 APARTMENT | 0.0 | 11.58 | 9.30 | 0.00 | 17.37 | 13.11 | 1.52 | 1 | 1 | 1 | 11.58 | 23.16 | 9.30 | 16.92 | 0.00 | 3.05 | 3.05 | 268.97 | TARP | TARP | 88.25 | 35.30 | 28.24 | 7.06 | 6 | 1 | 0 | Yes |
| 6 | G N2 APARTMENT | 0.0 | 23.16 | 9.30 | 0.00 | 28.95 | 13.11 | 1.52 | 1 | 1 | 1 | 23.16 | 34.75 | 9.30 | 16.92 | 0.00 | 3.05 | 3.05 | 268.97 | TARP | TARP | 88.25 | 35.30 | 28.24 | 7.06 | 6 | 1 | 0 | Yes |
| 7 | G S1 APARTMENT | 0.0 | 11.58 | 0.00 | 0.00 | 17.37 | 3.81 | 1.52 | 1 | 1 | 1 | 11.58 | 23.16 | 0.00 | 7.62 | 0.00 | 3.05 | 3.05 | 268.97 | TARP | TARP | 88.25 | 35.30 | 28.24 | 7.06 | 6 | 1 | 0 | Yes |
| 8 | G S2 APARTMENT | 0.0 | 23.16 | 0.00 | 0.00 | 28.95 | 3.81 | 1.52 | 1 | 1 | 1 | 23.16 | 34.75 | 0.00 | 7.62 | 0.00 | 3.05 | 3.05 | 268.97 | TARP | TARP | 88.25 | 35.30 | 28.24 | 7.06 | 6 | 1 | 0 | Yes |
| 9 | M SW APARTMENT | 0.0 | 0.00 | 0.00 | 3.05 | 5.79 | 3.81 | 4.57 | 1 | 1 | 2 | 0.00 | 11.58 | 0.00 | 7.62 | 3.05 | 6.10 | 3.05 | 268.97 | TARP | TARP | 88.25 | 58.52 | 46.82 | 11.71 | 6 | 2 | 0 | Yes |
| 10 | M NW APARTMENT | 0.0 | 0.00 | 9.30 | 3.05 | 5.79 | 13.11 | 4.57 | 1 | 1 | 2 | 0.00 | 11.58 | 9.30 | 16.92 | 3.05 | 6.10 | 3.05 | 268.97 | TARP | TARP | 88.25 | 58.52 | 46.82 | 11.71 | 6 | 2 | 0 | Yes |
| 11 | M SE APARTMENT | 0.0 | 34.75 | 0.00 | 3.05 | 40.54 | 3.81 | 4.57 | 1 | 1 | 2 | 34.75 | 46.33 | 0.00 | 7.62 | 3.05 | 6.10 | 3.05 | 268.97 | TARP | TARP | 88.25 | 58.52 | 46.82 | 11.71 | 6 | 2 | 0 | Yes |
| 12 | M NE APARTMENT | 0.0 | 34.75 | 9.30 | 3.05 | 40.54 | 13.11 | 4.57 | 1 | 1 | 2 | 34.75 | 46.33 | 9.30 | 16.92 | 3.05 | 6.10 | 3.05 | 268.97 | TARP | TARP | 88.25 | 58.52 | 46.82 | 11.71 | 6 | 2 | 0 | Yes |
| 13 | M N1 APARTMENT | 0.0 | 11.58 | 9.30 | 3.05 | 17.37 | 13.11 | 4.57 | 1 | 1 | 2 | 11.58 | 23.16 | 9.30 | 16.92 | 3.05 | 6.10 | 3.05 | 268.97 | TARP | TARP | 88.25 | 35.30 | 28.24 | 7.06 | 6 | 1 | 0 | Yes |
| 14 | M N2 APARTMENT | 0.0 | 23.16 | 9.30 | 3.05 | 28.95 | 13.11 | 4.57 | 1 | 1 | 2 | 23.16 | 34.75 | 9.30 | 16.92 | 3.05 | 6.10 | 3.05 | 268.97 | TARP | TARP | 88.25 | 35.30 | 28.24 | 7.06 | 6 | 1 | 0 | Yes |
| 15 | M S1 APARTMENT | 0.0 | 11.58 | 0.00 | 3.05 | 17.37 | 3.81 | 4.57 | 1 | 1 | 2 | 11.58 | 23.16 | 0.00 | 7.62 | 3.05 | 6.10 | 3.05 | 268.97 | TARP | TARP | 88.25 | 35.30 | 28.24 | 7.06 | 6 | 1 | 0 | Yes |
| 16 | M S2 APARTMENT | 0.0 | 23.16 | 0.00 | 3.05 | 28.95 | 3.81 | 4.57 | 1 | 1 | 2 | 23.16 | 34.75 | 0.00 | 7.62 | 3.05 | 6.10 | 3.05 | 268.97 | TARP | TARP | 88.25 | 35.30 | 28.24 | 7.06 | 6 | 1 | 0 | Yes |
| 17 | T SW APARTMENT | 0.0 | 0.00 | 0.00 | 9.14 | 5.79 | 3.81 | 10.67 | 1 | 1 | 1 | 0.00 | 11.58 | 0.00 | 7.62 | 9.14 | 12.19 | 3.05 | 268.97 | TARP | TARP | 88.25 | 58.52 | 46.82 | 11.71 | 6 | 2 | 0 | Yes |
| 18 | T NW APARTMENT | 0.0 | 0.00 | 9.30 | 9.14 | 5.79 | 13.11 | 10.67 | 1 | 1 | 1 | 0.00 | 11.58 | 9.30 | 16.92 | 9.14 | 12.19 | 3.05 | 268.97 | TARP | TARP | 88.25 | 58.52 | 46.82 | 11.71 | 6 | 2 | 0 | Yes |
| 19 | T SE APARTMENT | 0.0 | 34.75 | 0.00 | 9.14 | 40.54 | 3.81 | 10.67 | 1 | 1 | 1 | 34.75 | 46.33 | 0.00 | 7.62 | 9.14 | 12.19 | 3.05 | 268.97 | TARP | TARP | 88.25 | 58.52 | 46.82 | 11.71 | 6 | 2 | 0 | Yes |
| 20 | T NE APARTMENT | 0.0 | 34.75 | 9.30 | 9.14 | 40.54 | 13.11 | 10.67 | 1 | 1 | 1 | 34.75 | 46.33 | 9.30 | 16.92 | 9.14 | 12.19 | 3.05 | 268.97 | TARP | TARP | 88.25 | 58.52 | 46.82 | 11.71 | 6 | 2 | 0 | Yes |
| 21 | T N1 APARTMENT | 0.0 | 11.58 | 9.30 | 9.14 | 17.37 | 13.11 | 10.67 | 1 | 1 | 1 | 11.58 | 23.16 | 9.30 | 16.92 | 9.14 | 12.19 | 3.05 | 268.97 | TARP | TARP | 88.25 | 35.30 | 28.24 | 7.06 | 6 | 1 | 0 | Yes |
| 22 | T N2 APARTMENT | 0.0 | 23.16 | 9.30 | 9.14 | 28.95 | 13.11 | 10.67 | 1 | 1 | 1 | 23.16 | 34.75 | 9.30 | 16.92 | 9.14 | 12.19 | 3.05 | 268.97 | TARP | TARP | 88.25 | 35.30 | 28.24 | 7.06 | 6 | 1 | 0 | Yes |
| 23 | T S1 APARTMENT | 0.0 | 11.58 | 0.00 | 9.14 | 17.37 | 3.81 | 10.67 | 1 | 1 | 1 | 11.58 | 23.16 | 0.00 | 7.62 | 9.14 | 12.19 | 3.05 | 268.97 | TARP | TARP | 88.25 | 35.30 | 28.24 | 7.06 | 6 | 1 | 0 | Yes |
| 24 | T S2 APARTMENT | 0.0 | 23.16 | 0.00 | 9.14 | 28.95 | 3.81 | 10.67 | 1 | 1 | 1 | 23.16 | 34.75 | 0.00 | 7.62 | 9.14 | 12.19 | 3.05 | 268.97 | TARP | TARP | 88.25 | 35.30 | 28.24 | 7.06 | 6 | 1 | 0 | Yes |
| 25 | T CORRIDOR | 0.0 | 0.00 | 7.62 | 9.14 | 23.16 | 8.46 | 10.67 | 1 | 1 | 1 | 0.00 | 46.33 | 7.62 | 9.30 | 9.14 | 12.19 | 3.05 | 236.69 | TARP | TARP | 77.66 | 10.22 | 9.10 | 1.11 | 12 | 1 | 0 | Yes |
| 26 | G CORRIDOR | 0.0 | 0.00 | 7.62 | 0.00 | 23.16 | 8.46 | 1.52 | 1 | 1 | 1 | 0.00 | 46.33 | 7.62 | 9.30 | 0.00 | 3.05 | 3.05 | 236.69 | TARP | TARP | 77.66 | 10.22 | 6.90 | 3.32 | 12 | 1 | 0 | Yes |
| 27 | M CORRIDOR | 0.0 | 0.00 | 7.62 | 3.05 | 23.16 | 8.46 | 4.57 | 1 | 1 | 2 | 0.00 | 46.33 | 7.62 | 9.30 | 3.05 | 6.10 | 3.05 | 236.69 | TARP | TARP | 77.66 | 10.22 | 9.10 | 1.11 | 12 | 1 | 0 | Yes |
| Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
| 1 | G SW APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 2 | G NW APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 3 | OFFICE | 88.25 | 4.7 | 18.581 | 5.382E-002 | 9.753 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 16.423 | No |
| 4 | G NE APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 5 | G N1 APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 6 | G N2 APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 7 | G S1 APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 8 | G S2 APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 9 | M SW APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 10 | M NW APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 11 | M SE APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 12 | M NE APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 13 | M N1 APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 14 | M N2 APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 15 | M S1 APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 16 | M S2 APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 17 | T SW APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 18 | T NW APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 19 | T SE APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 20 | T NE APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 21 | T N1 APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 22 | T N2 APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 23 | T S1 APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 24 | T S2 APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 25 | T CORRIDOR | 77.66 | 4.2 | 18.579 | 5.382E-002 | 4.772 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 4.772 | No |
| 26 | G CORRIDOR | 77.66 | 4.2 | 18.579 | 5.382E-002 | 4.772 | 105.256 | 0.000 | 0.000 | 0.000 | 0.000 | 110.029 | No |
| 27 | M CORRIDOR | 77.66 | 4.2 | 18.579 | 5.382E-002 | 4.772 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 4.772 | No |
| Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | |
| 1 | OCCUP_GSW | OCC_APT_SCH_WORKING_FAMILY | G SW APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 3 |
| 2 | OCCUP_GNW | OCC_APT_SCH_STAY_HOME_FAMILY | G NW APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 1 | 3 |
| 3 | OCCUP_OFFICE | OCC_OFF_W_SB_SCH | OFFICE | 88.25 | 4.7 | 4.7 | 5.382E-002 | 18.581 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 5 |
| 4 | OCCUP_GNE | OCC_APT_SCH_STAY_HOME_FAMILY | G NE APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 1 | 3 |
| 5 | OCCUP_GN1 | OCC_APT_SCH_STAY_HOME_FAMILY | G N1 APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 1 | 3 |
| 6 | OCCUP_GN2 | OCC_APT_SCH_STAY_HOME_FAMILY | G N2 APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 1 | 3 |
| 7 | OCCUP_GS1 | OCC_APT_SCH_WORKING_FAMILY | G S1 APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 3 |
| 8 | OCCUP_GS2 | OCC_APT_SCH_WORKING_FAMILY | G S2 APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 3 |
| 9 | OCCUP_MSW | OCC_APT_SCH_WORKING_FAMILY | M SW APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 3 |
| 10 | OCCUP_MNW | OCC_APT_SCH_STAY_HOME_FAMILY | M NW APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 1 | 3 |
| 11 | OCCUP_MSE | OCC_APT_SCH_WORKING_FAMILY | M SE APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 3 |
| 12 | OCCUP_MNE | OCC_APT_SCH_STAY_HOME_FAMILY | M NE APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 1 | 3 |
| 13 | OCCUP_MN1 | OCC_APT_SCH_STAY_HOME_FAMILY | M N1 APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 1 | 3 |
| 14 | OCCUP_MN2 | OCC_APT_SCH_STAY_HOME_FAMILY | M N2 APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 1 | 3 |
| 15 | OCCUP_MS1 | OCC_APT_SCH_WORKING_FAMILY | M S1 APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 3 |
| 16 | OCCUP_MS2 | OCC_APT_SCH_WORKING_FAMILY | M S2 APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 3 |
| 17 | OCCUP_TSW | OCC_APT_SCH_WORKING_FAMILY | T SW APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 3 |
| 18 | OCCUP_TNW | OCC_APT_SCH_STAY_HOME_FAMILY | T NW APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 1 | 3 |
| 19 | OCCUP_TSE | OCC_APT_SCH_WORKING_FAMILY | T SE APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 3 |
| 20 | OCCUP_TNE | OCC_APT_SCH_STAY_HOME_FAMILY | T NE APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 1 | 3 |
| 21 | OCCUP_TN1 | OCC_APT_SCH_STAY_HOME_FAMILY | T N1 APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 1 | 3 |
| 22 | OCCUP_TN2 | OCC_APT_SCH_STAY_HOME_FAMILY | T N2 APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 1 | 3 |
| 23 | OCCUP_TS1 | OCC_APT_SCH_WORKING_FAMILY | T S1 APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 3 |
| 24 | OCCUP_TS2 | OCC_APT_SCH_WORKING_FAMILY | T S2 APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 3 |
| 25 | OCCUP_T CORRIDOR | OCC_APT_SCH_CORRIDOR | T CORRIDOR | 77.66 | 4.2 | 4.2 | 5.382E-002 | 18.579 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 1 | 4 |
| 26 | OCCUP_G CORRIDOR | OCC_APT_SCH_CORRIDOR | G CORRIDOR | 77.66 | 4.2 | 4.2 | 5.382E-002 | 18.579 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 1 | 4 |
| 27 | OCCUP_M CORRIDOR | OCC_APT_SCH_CORRIDOR | M CORRIDOR | 77.66 | 4.2 | 4.2 | 5.382E-002 | 18.579 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 1 | 4 |
| Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
| 1 | LIGHTING_HARDWIRED_GSW | LTG_SCH_APARTMENT_HARDWIRED | G SW APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 2 | LIGHTING_HARDWIRED_GNW | LTG_SCH_APARTMENT_HARDWIRED | G NW APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 3 | LIGHTING_HARDWIRED_OFFICE | LTG_SCH_OFFICE | OFFICE | 88.25 | 4.7 | 860.710 | 9.753 | 181.220 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 860.710 |
| 4 | LIGHTING_HARDWIRED_GNE | LTG_SCH_APARTMENT_HARDWIRED | G NE APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 5 | LIGHTING_HARDWIRED_GN1 | LTG_SCH_APARTMENT_HARDWIRED | G N1 APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 6 | LIGHTING_HARDWIRED_GN2 | LTG_SCH_APARTMENT_HARDWIRED | G N2 APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 7 | LIGHTING_HARDWIRED_GS1 | LTG_SCH_APARTMENT_HARDWIRED | G S1 APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 8 | LIGHTING_HARDWIRED_GS2 | LTG_SCH_APARTMENT_HARDWIRED | G S2 APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 9 | LIGHTING_HARDWIRED_MSW | LTG_SCH_APARTMENT_HARDWIRED | M SW APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 10 | LIGHTING_HARDWIRED_MNW | LTG_SCH_APARTMENT_HARDWIRED | M NW APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 11 | LIGHTING_HARDWIRED_MSE | LTG_SCH_APARTMENT_HARDWIRED | M SE APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 12 | LIGHTING_HARDWIRED_MNE | LTG_SCH_APARTMENT_HARDWIRED | M NE APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 13 | LIGHTING_HARDWIRED_MN1 | LTG_SCH_APARTMENT_HARDWIRED | M N1 APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 14 | LIGHTING_HARDWIRED_MN2 | LTG_SCH_APARTMENT_HARDWIRED | M N2 APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 15 | LIGHTING_HARDWIRED_MS1 | LTG_SCH_APARTMENT_HARDWIRED | M S1 APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 16 | LIGHTING_HARDWIRED_MS2 | LTG_SCH_APARTMENT_HARDWIRED | M S2 APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 17 | LIGHTING_HARDWIRED_TSW | LTG_SCH_APARTMENT_HARDWIRED | T SW APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 18 | LIGHTING_HARDWIRED_TNW | LTG_SCH_APARTMENT_HARDWIRED | T NW APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 19 | LIGHTING_HARDWIRED_TSE | LTG_SCH_APARTMENT_HARDWIRED | T SE APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 20 | LIGHTING_HARDWIRED_TNE | LTG_SCH_APARTMENT_HARDWIRED | T NE APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 21 | LIGHTING_HARDWIRED_TN1 | LTG_SCH_APARTMENT_HARDWIRED | T N1 APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 22 | LIGHTING_HARDWIRED_TN2 | LTG_SCH_APARTMENT_HARDWIRED | T N2 APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 23 | LIGHTING_HARDWIRED_TS1 | LTG_SCH_APARTMENT_HARDWIRED | T S1 APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 24 | LIGHTING_HARDWIRED_TS2 | LTG_SCH_APARTMENT_HARDWIRED | T S2 APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 25 | LIGHTING_HARDWIRED_GC | LTG_SCH_CORRIDOR | G CORRIDOR | 77.66 | 4.2 | 370.628 | 4.772 | 88.667 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 370.628 |
| 26 | LIGHTING_HARDWIRED_MC | LTG_SCH_CORRIDOR | M CORRIDOR | 77.66 | 4.2 | 370.628 | 4.772 | 88.667 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 370.628 |
| 27 | LIGHTING_HARDWIRED_TC | LTG_SCH_CORRIDOR | T CORRIDOR | 77.66 | 4.2 | 370.628 | 4.772 | 88.667 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 370.628 |
| 28 | LIGHTING_PLUGIN_GSW | LTG_SCH_APARTMENT_PLUGIN | G SW APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| 29 | LIGHTING_PLUGIN_GNW | LTG_SCH_APARTMENT_PLUGIN | G NW APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| 30 | LIGHTING_PLUGIN_GNE | LTG_SCH_APARTMENT_PLUGIN | G NE APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| 31 | LIGHTING_PLUGIN_GN1 | LTG_SCH_APARTMENT_PLUGIN | G N1 APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| 32 | LIGHTING_PLUGIN_GN2 | LTG_SCH_APARTMENT_PLUGIN | G N2 APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| 33 | LIGHTING_PLUGIN_GS1 | LTG_SCH_APARTMENT_PLUGIN | G S1 APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| 34 | LIGHTING_PLUGIN_GS2 | LTG_SCH_APARTMENT_PLUGIN | G S2 APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| 35 | LIGHTING_PLUGIN_MSW | LTG_SCH_APARTMENT_PLUGIN | M SW APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| 36 | LIGHTING_PLUGIN_MNW | LTG_SCH_APARTMENT_PLUGIN | M NW APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| 37 | LIGHTING_PLUGIN_MSE | LTG_SCH_APARTMENT_PLUGIN | M SE APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| 38 | LIGHTING_PLUGIN_MNE | LTG_SCH_APARTMENT_PLUGIN | M NE APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| 39 | LIGHTING_PLUGIN_MN1 | LTG_SCH_APARTMENT_PLUGIN | M N1 APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| 40 | LIGHTING_PLUGIN_MN2 | LTG_SCH_APARTMENT_PLUGIN | M N2 APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| 41 | LIGHTING_PLUGIN_MS1 | LTG_SCH_APARTMENT_PLUGIN | M S1 APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| 42 | LIGHTING_PLUGIN_MS2 | LTG_SCH_APARTMENT_PLUGIN | M S2 APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| 43 | LIGHTING_PLUGIN_TSW | LTG_SCH_APARTMENT_PLUGIN | T SW APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| 44 | LIGHTING_PLUGIN_TNW | LTG_SCH_APARTMENT_PLUGIN | T NW APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| 45 | LIGHTING_PLUGIN_TSE | LTG_SCH_APARTMENT_PLUGIN | T SE APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| 46 | LIGHTING_PLUGIN_TNE | LTG_SCH_APARTMENT_PLUGIN | T NE APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| 47 | LIGHTING_PLUGIN_TN1 | LTG_SCH_APARTMENT_PLUGIN | T N1 APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| 48 | LIGHTING_PLUGIN_TN2 | LTG_SCH_APARTMENT_PLUGIN | T N2 APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| 49 | LIGHTING_PLUGIN_TS1 | LTG_SCH_APARTMENT_PLUGIN | T S1 APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| 50 | LIGHTING_PLUGIN_TS2 | LTG_SCH_APARTMENT_PLUGIN | T S2 APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
| 1 | PLUG_GSW | EQP_APT_SCH | G SW APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 2 | PLUG_GNW | EQP_APT_SCH | G NW APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 3 | PLUG_OFFICE | EQP_OFF_SCH | OFFICE | 88.25 | 4.7 | 588.623 | 6.670 | 123.933 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 588.623 |
| 4 | PLUG_GNE | EQP_APT_SCH | G NE APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 5 | PLUG_GN1 | EQP_APT_SCH | G N1 APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 6 | PLUG_GN2 | EQP_APT_SCH | G N2 APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 7 | PLUG_GS1 | EQP_APT_SCH | G S1 APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 8 | PLUG_GS2 | EQP_APT_SCH | G S2 APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 9 | PLUG_MSW | EQP_APT_SCH | M SW APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 10 | PLUG_MNW | EQP_APT_SCH | M NW APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 11 | PLUG_MSE | EQP_APT_SCH | M SE APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 12 | PLUG_MNE | EQP_APT_SCH | M NE APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 13 | PLUG_MN1 | EQP_APT_SCH | M N1 APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 14 | PLUG_MN2 | EQP_APT_SCH | M N2 APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 15 | PLUG_MS1 | EQP_APT_SCH | M S1 APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 16 | PLUG_MS2 | EQP_APT_SCH | M S2 APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 17 | PLUG_TSW | EQP_APT_SCH | T SW APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 18 | PLUG_TNW | EQP_APT_SCH | T NW APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 19 | PLUG_TSE | EQP_APT_SCH | T SE APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 20 | PLUG_TNE | EQP_APT_SCH | T NE APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 21 | PLUG_TN1 | EQP_APT_SCH | T N1 APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 22 | PLUG_TN2 | EQP_APT_SCH | T N2 APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 23 | PLUG_TS1 | EQP_APT_SCH | T S1 APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 24 | PLUG_TS2 | EQP_APT_SCH | T S2 APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 25 | G CORRIDOR_ELEVATORS_EQUIP | BLDG_ELEVATORS | G CORRIDOR | 77.66 | 4.2 | 8012.150 | 103.170 | 1916.782 | 0.000 | 0.000 | 0.950 | 5.000E-002 | ElevatorLift | 961.458 | 4006.075 |
| 26 | ELEVATORS_LIGHTS_FAN | ELEV_LIGHT_FAN_SCH_24_7 | G CORRIDOR | 77.66 | 4.2 | 162.000 | 2.086 | 38.756 | 0.000 | 0.000 | 0.950 | 5.000E-002 | ElevatorLightsFan | 162.000 | 162.000 |
| Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
| 1 | PolygonClipping | Periodic | 20 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
| Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
| 1 | WaterHeater:Mixed | G SW APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.496 | 0.7729 |
| 2 | WaterHeater:Mixed | G NW APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.496 | 0.7729 |
| 3 | WaterHeater:Mixed | G NE APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.496 | 0.7729 |
| 4 | WaterHeater:Mixed | G N1 APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.496 | 0.7729 |
| 5 | WaterHeater:Mixed | G N2 APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.496 | 0.7729 |
| 6 | WaterHeater:Mixed | G S1 APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.496 | 0.7729 |
| 7 | WaterHeater:Mixed | G S2 APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.496 | 0.7729 |
| 8 | WaterHeater:Mixed | M SW APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.498 | 0.7911 |
| 9 | WaterHeater:Mixed | M NW APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.498 | 0.7911 |
| 10 | WaterHeater:Mixed | M SE APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.498 | 0.7911 |
| 11 | WaterHeater:Mixed | M NE APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.498 | 0.7911 |
| 12 | WaterHeater:Mixed | M N1 APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.498 | 0.7911 |
| 13 | WaterHeater:Mixed | M N2 APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.498 | 0.7911 |
| 14 | WaterHeater:Mixed | M S1 APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.498 | 0.7911 |
| 15 | WaterHeater:Mixed | M S2 APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.498 | 0.7911 |
| 16 | WaterHeater:Mixed | T SW APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.496 | 0.7729 |
| 17 | WaterHeater:Mixed | T NW APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.496 | 0.7729 |
| 18 | WaterHeater:Mixed | T SE APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.496 | 0.7729 |
| 19 | WaterHeater:Mixed | T NE APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.496 | 0.7729 |
| 20 | WaterHeater:Mixed | T N1 APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.496 | 0.7729 |
| 21 | WaterHeater:Mixed | T N2 APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.496 | 0.7729 |
| 22 | WaterHeater:Mixed | T S1 APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.496 | 0.7729 |
| 23 | WaterHeater:Mixed | T S2 APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.496 | 0.7729 |
| Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
| 1 | G SWALL SWA | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 2 | GWINDOW1 S SWA | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 3 | G WWALL SWA | 0 | 154.67 | 58.21 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 4 | GWINDOW1 W SWA | 0 | 154.67 | 58.21 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 5 | G NIWALL SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 6 | G EIWALL SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 7 | G GFLOOR SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 8 | G CEILIN SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 9 | G INTERNALMASS SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 10 | G NWALL NWA | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 11 | GWINDOW1 N NWA | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 12 | G WWALL NWA | 0 | 154.67 | 58.21 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 13 | GWINDOW1 W NWA | 0 | 154.67 | 58.21 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 14 | G SIWALL NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 15 | G EIWALL NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 16 | G GFLOOR NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 17 | G CEILIN NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 18 | G INTERNALMASS NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 19 | G SWALL SEA | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 20 | GWINDOW1 S SEA | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 21 | G EWALL SEA | 0 | 154.67 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 22 | GWINDOW1 E SEA | 0 | 154.67 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 23 | G NIWALL SEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 24 | iz-G EIWALL S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 25 | G GFLOOR SEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 26 | G CEILIN SEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 27 | G INTERNALMASS SEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 28 | G NWALL NEA | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 29 | GWINDOW1 N NEA | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 30 | G EWALL NEA | 0 | 154.67 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 31 | GWINDOW1 E NEA | 0 | 154.67 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 32 | G SIWALL NEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 33 | iz-G EIWALL N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 34 | G GFLOOR NEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 35 | G CEILIN NEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 36 | G INTERNALMASS NEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 37 | G NWALL N1A | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 3 | No | No |
| 38 | GWINDOW1 N N1A | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 2 | No | No |
| 39 | G SIWALL N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 40 | G EIWALL N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 41 | iz-G EIWALL NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 42 | G GFLOOR N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 43 | G CEILIN N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 44 | G INTERNALMASS N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 45 | G NWALL N2A | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 3 | No | No |
| 46 | GWINDOW1 N N2A | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 2 | No | No |
| 47 | G SIWALL N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 48 | G EIWALL N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 49 | iz-G EIWALL N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 50 | G GFLOOR N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 51 | G CEILIN N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 52 | G INTERNALMASS N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 53 | G SWALL S1A | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 3 | No | No |
| 54 | GWINDOW1 S S1A | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 2 | No | No |
| 55 | G NIWALL S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 56 | G EIWALL S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 57 | iz-G EIWALL SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 58 | G GFLOOR S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 59 | G CEILIN S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 60 | G INTERNALMASS S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 61 | G SWALL S2A | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 3 | No | No |
| 62 | GWINDOW1 S S2A | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 2 | No | No |
| 63 | G NIWALL S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 64 | G EIWALL S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 65 | iz-G EIWALL S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 66 | G GFLOOR S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 67 | G CEILIN S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 68 | G INTERNALMASS S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 69 | M WWALL SWA | 0 | 154.67 | 58.21 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 70 | MWINDOW1 W SWA | 0 | 154.67 | 58.21 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 71 | M SWALL SWA | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 72 | MWINDOW1 S SWA | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 73 | M NIWALL SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 74 | M EIWALL SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 75 | M GFLOOR SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 76 | M CEILIN SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 77 | M INTERNALMASS SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 78 | M NWALL NWA | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 79 | MWINDOW1 N NWA | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 80 | M WWALL NWA | 0 | 154.67 | 58.21 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 81 | MWINDOW1 W NWA | 0 | 154.67 | 58.21 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 82 | M SIWALL NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 83 | M EIWALL NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 84 | M GFLOOR NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 85 | M CEILIN NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 86 | M INTERNALMASS NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 87 | M EWALL SEA | 0 | 154.67 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 88 | MWINDOW1 E SEA | 0 | 154.67 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 89 | M SWALL SEA | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 90 | MWINDOW1 S SEA | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 91 | M NIWALL SEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 92 | iz-M EIWALL S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 93 | M GFLOOR SEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 94 | M CEILIN SEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 95 | M INTERNALMASS SEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 96 | M NWALL NEA | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 97 | MWINDOW1 N NEA | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 98 | M EWALL NEA | 0 | 154.67 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 99 | MWINDOW1 E NEA | 0 | 154.67 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 100 | M SIWALL NEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 101 | iz-M EIWALL N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 102 | M GFLOOR NEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 103 | M CEILIN NEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 104 | M INTERNALMASS NEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 105 | M NWALL N1A | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 3 | No | No |
| 106 | MWINDOW1 N N1A | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 2 | No | No |
| 107 | M SIWALL N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 108 | M EIWALL N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 109 | iz-M EIWALL NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 110 | M GFLOOR N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 111 | M CEILIN N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 112 | M INTERNALMASS N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 113 | M NWALL N2A | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 3 | No | No |
| 114 | MWINDOW1 N N2A | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 2 | No | No |
| 115 | M SIWALL N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 116 | M EIWALL N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 117 | iz-M EIWALL N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 118 | M GFLOOR N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 119 | M CEILIN N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 120 | M INTERNALMASS N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 121 | M SWALL S1A | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 3 | No | No |
| 122 | MWINDOW1 S S1A | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 2 | No | No |
| 123 | M NIWALL S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 124 | M EIWALL S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 125 | iz-M EIWALL SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 126 | M GFLOOR S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 127 | M CEILIN S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 128 | M INTERNALMASS S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 129 | M SWALL S2A | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 3 | No | No |
| 130 | MWINDOW1 S S2A | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 2 | No | No |
| 131 | M NIWALL S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 132 | M EIWALL S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 133 | iz-M EIWALL S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 134 | M GFLOOR S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 135 | M CEILIN S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 136 | M INTERNALMASS S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 137 | T WWALL SWA | 0 | 154.67 | 58.21 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 138 | TWINDOW1 W SWA | 0 | 154.67 | 58.21 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 139 | T SWALL SWA | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 140 | TWINDOW1 S SWA | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 141 | T NIWALL SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 142 | T EIWALL SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 143 | T GFLOOR SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 144 | T ROOF SWA | 0 | 783.65 | 155.90 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 145 | T INTERNALMASS SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 146 | T NWALL NWA | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 147 | TWINDOW1 N NWA | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 148 | T WWALL NWA | 0 | 154.67 | 58.21 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 149 | TWINDOW1 W NWA | 0 | 154.67 | 58.21 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 150 | T SIWALL NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 151 | T EIWALL NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 152 | T GFLOOR NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 153 | T ROOF NWA | 0 | 783.65 | 155.90 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 154 | T INTERNALMASS NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 155 | T EWALL SEA | 0 | 154.67 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 156 | TWINDOW1 E SEA | 0 | 154.67 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 157 | T SWALL SEA | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 158 | TWINDOW1 S SEA | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 159 | T NIWALL SEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 160 | iz-T EIWALL S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 161 | T GFLOOR SEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 162 | T ROOF SEA | 0 | 783.65 | 155.90 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 163 | T INTERNALMASS SEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 164 | T NWALL NEA | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 165 | TWINDOW1 N NEA | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 166 | T EWALL NEA | 0 | 154.67 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 167 | TWINDOW1 E NEA | 0 | 154.67 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 168 | T SIWALL NEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 169 | iz-T EIWALL N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 170 | T GFLOOR NEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 171 | T ROOF NEA | 0 | 783.65 | 155.90 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 172 | T INTERNALMASS NEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 173 | T NWALL N1A | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 3 | No | No |
| 174 | TWINDOW1 N N1A | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 2 | No | No |
| 175 | T SIWALL N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 176 | T EIWALL N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 177 | iz-T EIWALL NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 178 | T GFLOOR N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 179 | T ROOF N1A | 0 | 783.65 | 155.90 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 180 | T INTERNALMASS N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 181 | T NWALL N2A | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 3 | No | No |
| 182 | TWINDOW1 N N2A | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 2 | No | No |
| 183 | T SIWALL N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 184 | T EIWALL N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 185 | iz-T EIWALL N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 186 | T GFLOOR N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 187 | T ROOF N2A | 0 | 783.65 | 155.90 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 188 | T INTERNALMASS N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 189 | T SWALL S1A | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 3 | No | No |
| 190 | TWINDOW1 S S1A | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 2 | No | No |
| 191 | T NIWALL S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 192 | T EIWALL S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 193 | iz-T EIWALL SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 194 | T GFLOOR S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 195 | T ROOF S1A | 0 | 783.65 | 155.90 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 196 | T INTERNALMASS S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 197 | T SWALL S2A | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 3 | No | No |
| 198 | TWINDOW1 S S2A | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 2 | No | No |
| 199 | T NIWALL S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 200 | T EIWALL S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 201 | iz-T EIWALL S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 202 | T GFLOOR S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 203 | T ROOF S2A | 0 | 783.65 | 155.90 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 204 | T INTERNALMASS S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 205 | T WWALL C | 0 | 154.67 | 58.21 | 12.19 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 3 | No | No |
| 206 | T EWALL C | 0 | 154.67 | 123.02 | 12.19 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 3 | No | No |
| 207 | TWINDOW14 | 0 | 154.67 | 123.02 | 12.19 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 2 | No | No |
| 208 | iz-T NIWALL SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 209 | iz-T NIWALL S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 210 | iz-T NIWALL S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 211 | iz-T NIWALL SEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 212 | iz-T SIWALL NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 213 | iz-T SIWALL N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 214 | iz-T SIWALL N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 215 | iz-T SIWALL NEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 216 | T FLOOR C | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 217 | T ROOF C | 0 | 783.65 | 155.90 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 218 | G WWALL C | 0 | 154.67 | 58.21 | 12.19 | 0 | 3.05 | 3.35 | 3.24 | 0.32 | 4 | No | No |
| 219 | G EWALL C | 0 | 154.67 | 123.02 | 12.19 | 0 | 3.05 | 3.35 | 3.24 | 0.32 | 4 | No | No |
| 220 | ENTRANCE DOOR | 0 | 154.67 | 123.02 | 12.19 | 0 | 3.05 | 3.35 | 3.24 | 0.32 | 1 | No | No |
| 221 | iz-G NIWALL SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.32 | 0 | No | No |
| 222 | iz-G NIWALL S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.32 | 0 | No | No |
| 223 | iz-G NIWALL S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.32 | 0 | No | No |
| 224 | iz-G NIWALL SEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.32 | 0 | No | No |
| 225 | iz-G SIWALL NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.32 | 0 | No | No |
| 226 | iz-G SIWALL N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.32 | 0 | No | No |
| 227 | iz-G SIWALL N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.32 | 0 | No | No |
| 228 | iz-G SIWALL NEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.32 | 0 | No | No |
| 229 | G FLOOR C | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.32 | 0 | No | No |
| 230 | G CEILING C | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.32 | 0 | No | No |
| 231 | M WWALL C | 0 | 154.67 | 58.21 | 12.19 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 4 | No | No |
| 232 | M EWALL C | 0 | 154.67 | 123.02 | 12.19 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 3 | No | No |
| 233 | MWINDOW14 | 0 | 154.67 | 123.02 | 12.19 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 2 | No | No |
| 234 | iz-M NIWALL SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 235 | iz-M NIWALL S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 236 | iz-M NIWALL S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 237 | iz-M NIWALL SEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 238 | iz-M SIWALL NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 239 | iz-M SIWALL N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 240 | iz-M SIWALL N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 241 | iz-M SIWALL NEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 242 | M FLOOR C | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 243 | M CEILING C | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
| 1 | INFIL_GSW | INF_APT_SCH | G SW APARTMENT | 88.25 | 2.5 | 6.000E-002 | 6.799E-004 | 1.025E-003 | 0.803 | 0.000 | 0.000 | 0.224 | 0.000 |
| 2 | INFIL_GNW | INF_APT_SCH | G NW APARTMENT | 88.25 | 2.5 | 6.000E-002 | 6.799E-004 | 1.025E-003 | 0.803 | 0.000 | 0.000 | 0.224 | 0.000 |
| 3 | INFIL_OFFICE | INF_OFF_SCH | OFFICE | 88.25 | 4.7 | 6.000E-002 | 6.799E-004 | 1.025E-003 | 0.803 | 0.000 | 0.000 | 0.224 | 0.000 |
| 4 | INFIL_GNE | INF_APT_SCH | G NE APARTMENT | 88.25 | 2.5 | 6.000E-002 | 6.799E-004 | 1.025E-003 | 0.803 | 0.000 | 0.000 | 0.224 | 0.000 |
| 5 | INFIL_GN1 | INF_APT_SCH | G N1 APARTMENT | 88.25 | 2.5 | 3.619E-002 | 4.101E-004 | 1.025E-003 | 0.484 | 0.000 | 0.000 | 0.224 | 0.000 |
| 6 | INFIL_GN2 | INF_APT_SCH | G N2 APARTMENT | 88.25 | 2.5 | 3.619E-002 | 4.101E-004 | 1.025E-003 | 0.484 | 0.000 | 0.000 | 0.224 | 0.000 |
| 7 | INFIL_GS1 | INF_APT_SCH | G S1 APARTMENT | 88.25 | 2.5 | 3.619E-002 | 4.101E-004 | 1.025E-003 | 0.484 | 0.000 | 0.000 | 0.224 | 0.000 |
| 8 | INFIL_GS2 | INF_APT_SCH | G S2 APARTMENT | 88.25 | 2.5 | 3.619E-002 | 4.101E-004 | 1.025E-003 | 0.484 | 0.000 | 0.000 | 0.224 | 0.000 |
| 9 | INFIL_MSW | INF_APT_SCH | M SW APARTMENT | 88.25 | 2.5 | 6.000E-002 | 6.799E-004 | 1.025E-003 | 0.803 | 0.000 | 0.000 | 0.224 | 0.000 |
| 10 | INFIL_MNW | INF_APT_SCH | M NW APARTMENT | 88.25 | 2.5 | 6.000E-002 | 6.799E-004 | 1.025E-003 | 0.803 | 0.000 | 0.000 | 0.224 | 0.000 |
| 11 | INFIL_MSE | INF_APT_SCH | M SE APARTMENT | 88.25 | 2.5 | 6.000E-002 | 6.799E-004 | 1.025E-003 | 0.803 | 0.000 | 0.000 | 0.224 | 0.000 |
| 12 | INFIL_MNE | INF_APT_SCH | M NE APARTMENT | 88.25 | 2.5 | 6.000E-002 | 6.799E-004 | 1.025E-003 | 0.803 | 0.000 | 0.000 | 0.224 | 0.000 |
| 13 | INFIL_MN1 | INF_APT_SCH | M N1 APARTMENT | 88.25 | 2.5 | 3.619E-002 | 4.101E-004 | 1.025E-003 | 0.484 | 0.000 | 0.000 | 0.224 | 0.000 |
| 14 | INFIL_MN2 | INF_APT_SCH | M N2 APARTMENT | 88.25 | 2.5 | 3.619E-002 | 4.101E-004 | 1.025E-003 | 0.484 | 0.000 | 0.000 | 0.224 | 0.000 |
| 15 | INFIL_MS1 | INF_APT_SCH | M S1 APARTMENT | 88.25 | 2.5 | 3.619E-002 | 4.101E-004 | 1.025E-003 | 0.484 | 0.000 | 0.000 | 0.224 | 0.000 |
| 16 | INFIL_MS2 | INF_APT_SCH | M S2 APARTMENT | 88.25 | 2.5 | 3.619E-002 | 4.101E-004 | 1.025E-003 | 0.484 | 0.000 | 0.000 | 0.224 | 0.000 |
| 17 | INFIL_SW | INF_APT_SCH | T SW APARTMENT | 88.25 | 2.5 | 6.000E-002 | 6.799E-004 | 4.088E-004 | 0.803 | 0.000 | 0.000 | 0.224 | 0.000 |
| 18 | INFIL_NW | INF_APT_SCH | T NW APARTMENT | 88.25 | 2.5 | 6.000E-002 | 6.799E-004 | 4.088E-004 | 0.803 | 0.000 | 0.000 | 0.224 | 0.000 |
| 19 | INFIL_SE | INF_APT_SCH | T SE APARTMENT | 88.25 | 2.5 | 6.000E-002 | 6.799E-004 | 4.088E-004 | 0.803 | 0.000 | 0.000 | 0.224 | 0.000 |
| 20 | INFIL_NE | INF_APT_SCH | T NE APARTMENT | 88.25 | 2.5 | 6.000E-002 | 6.799E-004 | 4.088E-004 | 0.803 | 0.000 | 0.000 | 0.224 | 0.000 |
| 21 | INFIL_TN1 | INF_APT_SCH | T N1 APARTMENT | 88.25 | 2.5 | 3.619E-002 | 4.101E-004 | 2.929E-004 | 0.484 | 0.000 | 0.000 | 0.224 | 0.000 |
| 22 | INFIL_TN2 | INF_APT_SCH | T N2 APARTMENT | 88.25 | 2.5 | 3.619E-002 | 4.101E-004 | 2.929E-004 | 0.484 | 0.000 | 0.000 | 0.224 | 0.000 |
| 23 | INFIL_TS1 | INF_APT_SCH | T S1 APARTMENT | 88.25 | 2.5 | 3.619E-002 | 4.101E-004 | 2.929E-004 | 0.484 | 0.000 | 0.000 | 0.224 | 0.000 |
| 24 | INFIL_TS2 | INF_APT_SCH | T S2 APARTMENT | 88.25 | 2.5 | 3.619E-002 | 4.101E-004 | 2.929E-004 | 0.484 | 0.000 | 0.000 | 0.224 | 0.000 |
| 25 | INFIL_GC | INF_COR_SCH | G CORRIDOR | 77.66 | 4.2 | 1.048E-002 | 1.349E-004 | 1.025E-003 | 0.159 | 0.000 | 0.000 | 0.224 | 0.000 |
| 26 | DOOR_INFIL_GC | INFIL_DOOR_OPENING_SCH | G CORRIDOR | 77.66 | 4.2 | 0.521 | 6.703E-003 | 5.094E-002 | 7.917 | 1.000 | 0.000 | 0.000 | 0.000 |
| 27 | INFIL_MC | INF_COR_SCH | M CORRIDOR | 77.66 | 4.2 | 1.048E-002 | 1.349E-004 | 1.025E-003 | 0.159 | 0.000 | 0.000 | 0.224 | 0.000 |
| 28 | INFIL_TC | INF_COR_SCH | T CORRIDOR | 77.66 | 4.2 | 1.048E-002 | 1.349E-004 | 1.192E-004 | 0.159 | 0.000 | 0.000 | 0.224 | 0.000 |
| Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
| 1 | G SW APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | G SW APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 2 | G NW APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | G NW APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 3 | G NE APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | G NE APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 4 | G N1 APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | G N1 APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 5 | G N2 APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | G N2 APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 6 | G S1 APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | G S1 APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 7 | G S2 APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | G S2 APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 8 | M SW APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | M SW APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 9 | M NW APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | M NW APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 10 | M SE APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | M SE APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 11 | M NE APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | M NE APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 12 | M N1 APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | M N1 APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 13 | M N2 APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | M N2 APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 14 | M S1 APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | M S1 APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 15 | M S2 APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | M S2 APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 16 | T SW APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | T SW APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 17 | T NW APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | T NW APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 18 | T SE APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | T SE APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 19 | T NE APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | T NE APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 20 | T N1 APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | T N1 APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 21 | T N2 APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | T N2 APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 22 | T S1 APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | T S1 APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 23 | T S2 APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | T S2 APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| Simple | |
| 1 | Simple |
| Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
| 1 | G SW APARTMENT | Mixing/Well-Stirred |
| 2 | G NW APARTMENT | Mixing/Well-Stirred |
| 3 | OFFICE | Mixing/Well-Stirred |
| 4 | G NE APARTMENT | Mixing/Well-Stirred |
| 5 | G N1 APARTMENT | Mixing/Well-Stirred |
| 6 | G N2 APARTMENT | Mixing/Well-Stirred |
| 7 | G S1 APARTMENT | Mixing/Well-Stirred |
| 8 | G S2 APARTMENT | Mixing/Well-Stirred |
| 9 | M SW APARTMENT | Mixing/Well-Stirred |
| 10 | M NW APARTMENT | Mixing/Well-Stirred |
| 11 | M SE APARTMENT | Mixing/Well-Stirred |
| 12 | M NE APARTMENT | Mixing/Well-Stirred |
| 13 | M N1 APARTMENT | Mixing/Well-Stirred |
| 14 | M N2 APARTMENT | Mixing/Well-Stirred |
| 15 | M S1 APARTMENT | Mixing/Well-Stirred |
| 16 | M S2 APARTMENT | Mixing/Well-Stirred |
| 17 | T SW APARTMENT | Mixing/Well-Stirred |
| 18 | T NW APARTMENT | Mixing/Well-Stirred |
| 19 | T SE APARTMENT | Mixing/Well-Stirred |
| 20 | T NE APARTMENT | Mixing/Well-Stirred |
| 21 | T N1 APARTMENT | Mixing/Well-Stirred |
| 22 | T N2 APARTMENT | Mixing/Well-Stirred |
| 23 | T S1 APARTMENT | Mixing/Well-Stirred |
| 24 | T S2 APARTMENT | Mixing/Well-Stirred |
| 25 | T CORRIDOR | Mixing/Well-Stirred |
| 26 | G CORRIDOR | Mixing/Well-Stirred |
| 27 | M CORRIDOR | Mixing/Well-Stirred |
| No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
| 1 | NoMultizoneOrDistribution |
| Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
| 1 | 1.000 | 1.000 | 1.000 | 1.000 |
| Value | |
| 1 | 6 |
| Sizing Factor ID | Value | |
| 1 | Global | 1.2000 |
| 2 | Zone G SW APARTMENT | 1.2000 |
| 3 | Zone G NW APARTMENT | 1.2000 |
| 4 | Zone OFFICE | 1.2000 |
| 5 | Zone G NE APARTMENT | 1.2000 |
| 6 | Zone G N1 APARTMENT | 1.2000 |
| 7 | Zone G N2 APARTMENT | 1.2000 |
| 8 | Zone G S1 APARTMENT | 1.2000 |
| 9 | Zone G S2 APARTMENT | 1.2000 |
| 10 | Zone M SW APARTMENT | 1.2000 |
| 11 | Zone M NW APARTMENT | 1.2000 |
| 12 | Zone M SE APARTMENT | 1.2000 |
| 13 | Zone M NE APARTMENT | 1.2000 |
| 14 | Zone M N1 APARTMENT | 1.2000 |
| 15 | Zone M N2 APARTMENT | 1.2000 |
| 16 | Zone M S1 APARTMENT | 1.2000 |
| 17 | Zone M S2 APARTMENT | 1.2000 |
| 18 | Zone T SW APARTMENT | 1.2000 |
| 19 | Zone T NW APARTMENT | 1.2000 |
| 20 | Zone T SE APARTMENT | 1.2000 |
| 21 | Zone T NE APARTMENT | 1.2000 |
| 22 | Zone T N1 APARTMENT | 1.2000 |
| 23 | Zone T N2 APARTMENT | 1.2000 |
| 24 | Zone T S1 APARTMENT | 1.2000 |
| 25 | Zone T S2 APARTMENT | 1.2000 |
| Sizing Factor ID | Value | |
| 1 | Global | 1.2000 |
| 2 | Zone G SW APARTMENT | 1.2000 |
| 3 | Zone G NW APARTMENT | 1.2000 |
| 4 | Zone OFFICE | 1.2000 |
| 5 | Zone G NE APARTMENT | 1.2000 |
| 6 | Zone G N1 APARTMENT | 1.2000 |
| 7 | Zone G N2 APARTMENT | 1.2000 |
| 8 | Zone G S1 APARTMENT | 1.2000 |
| 9 | Zone G S2 APARTMENT | 1.2000 |
| 10 | Zone M SW APARTMENT | 1.2000 |
| 11 | Zone M NW APARTMENT | 1.2000 |
| 12 | Zone M SE APARTMENT | 1.2000 |
| 13 | Zone M NE APARTMENT | 1.2000 |
| 14 | Zone M N1 APARTMENT | 1.2000 |
| 15 | Zone M N2 APARTMENT | 1.2000 |
| 16 | Zone M S1 APARTMENT | 1.2000 |
| 17 | Zone M S2 APARTMENT | 1.2000 |
| 18 | Zone T SW APARTMENT | 1.2000 |
| 19 | Zone T NW APARTMENT | 1.2000 |
| 20 | Zone T SE APARTMENT | 1.2000 |
| 21 | Zone T NE APARTMENT | 1.2000 |
| 22 | Zone T N1 APARTMENT | 1.2000 |
| 23 | Zone T N2 APARTMENT | 1.2000 |
| 24 | Zone T S1 APARTMENT | 1.2000 |
| 25 | Zone T S2 APARTMENT | 1.2000 |
| Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
| 1 | G SW APARTMENT | Cooling | 3555.10079 | 4266.12095 | 0.25498 | 0.30598 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 27.82900 | 8.22799E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 2 | G SW APARTMENT | Heating | 989.94817 | 1187.93780 | 4.34632E-002 | 5.21558E-002 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 04:10:00 | 3.80000 | 5.05843E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 3 | G NW APARTMENT | Cooling | 3269.22114 | 3923.06537 | 0.23394 | 0.28073 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 27.82900 | 8.22799E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 4 | G NW APARTMENT | Heating | 863.28214 | 1035.93857 | 3.79026E-002 | 4.54832E-002 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 04:00:00 | 3.80000 | 5.05843E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 5 | OFFICE | Cooling | 4104.50733 | 4925.40880 | 0.29941 | 0.35929 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | 26.40500 | 8.22575E-003 | 88.24927 | 4.74953 | 3.81060E-002 | 0.00000 |
| 6 | OFFICE | Heating | 1391.32035 | 1669.58442 | 6.10862E-002 | 7.33035E-002 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 18:50:00 | 3.80000 | 5.05843E-003 | 88.24927 | 4.74953 | 3.81060E-002 | 0.00000 |
| 7 | G NE APARTMENT | Cooling | 3055.64383 | 3666.77260 | 0.21818 | 0.26182 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 27.82900 | 8.22799E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 8 | G NE APARTMENT | Heating | 864.65670 | 1037.58804 | 3.79630E-002 | 4.55556E-002 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 04:00:00 | 3.80000 | 5.05843E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 9 | G N1 APARTMENT | Cooling | 2885.93467 | 3463.12161 | 0.20571 | 0.24686 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 27.82900 | 8.22799E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 10 | G N1 APARTMENT | Heating | 435.47359 | 522.56831 | 1.91198E-002 | 2.59546E-002 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 04:00:00 | 3.80000 | 5.05843E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 11 | G N2 APARTMENT | Cooling | 2881.00990 | 3457.21188 | 0.20535 | 0.24642 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 27.82900 | 8.22799E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 12 | G N2 APARTMENT | Heating | 435.51396 | 522.61676 | 1.91216E-002 | 2.59546E-002 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 04:00:00 | 3.80000 | 5.05843E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 13 | G S1 APARTMENT | Cooling | 3160.99094 | 3793.18913 | 0.22593 | 0.27112 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 27.82900 | 8.22799E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 14 | G S1 APARTMENT | Heating | 562.33376 | 674.80052 | 2.46893E-002 | 2.96272E-002 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 04:10:00 | 3.80000 | 5.05843E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 15 | G S2 APARTMENT | Cooling | 3183.29112 | 3819.94935 | 0.22758 | 0.27310 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 27.82900 | 8.22799E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 16 | G S2 APARTMENT | Heating | 570.70607 | 684.84728 | 2.50569E-002 | 3.00683E-002 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 04:00:00 | 3.80000 | 5.05843E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 17 | M SW APARTMENT | Cooling | 8761.66852 | 10514.00223 | 0.63162 | 0.75794 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 27.82900 | 8.22799E-003 | 88.24927 | 2.50000 | 5.19091E-002 | 0.00000 |
| 18 | M SW APARTMENT | Heating | 1887.45789 | 2264.94947 | 8.28672E-002 | 9.94406E-002 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | 3.80000 | 5.05843E-003 | 88.24927 | 2.50000 | 5.19091E-002 | 0.00000 |
| 19 | M NW APARTMENT | Cooling | 8236.21106 | 9883.45327 | 0.59283 | 0.71139 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 27.82900 | 8.22799E-003 | 88.24927 | 2.50000 | 5.19091E-002 | 0.00000 |
| 20 | M NW APARTMENT | Heating | 1604.28745 | 1925.14494 | 7.04359E-002 | 8.45231E-002 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | 3.80000 | 5.05843E-003 | 88.24927 | 2.50000 | 5.19091E-002 | 0.00000 |
| 21 | M SE APARTMENT | Cooling | 8175.97191 | 9811.16629 | 0.58840 | 0.70608 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 27.82900 | 8.22799E-003 | 88.24927 | 2.50000 | 5.19091E-002 | 0.00000 |
| 22 | M SE APARTMENT | Heating | 1890.97488 | 2269.16985 | 8.30216E-002 | 9.96259E-002 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | 3.80000 | 5.05843E-003 | 88.24927 | 2.50000 | 5.19091E-002 | 0.00000 |
| 23 | M NE APARTMENT | Cooling | 7658.55070 | 9190.26083 | 0.55012 | 0.66014 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 27.82900 | 8.22799E-003 | 88.24927 | 2.50000 | 5.19091E-002 | 0.00000 |
| 24 | M NE APARTMENT | Heating | 1607.92709 | 1929.51250 | 7.05957E-002 | 8.47148E-002 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | 3.80000 | 5.05843E-003 | 88.24927 | 2.50000 | 5.19091E-002 | 0.00000 |
| 25 | M N1 APARTMENT | Cooling | 7039.16881 | 8447.00258 | 0.50478 | 0.60573 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 27.82900 | 8.22799E-003 | 88.24927 | 2.50000 | 5.19091E-002 | 0.00000 |
| 26 | M N1 APARTMENT | Heating | 660.02623 | 792.03148 | 2.89788E-002 | 5.19091E-002 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | 3.80000 | 5.05843E-003 | 88.24927 | 2.50000 | 5.19091E-002 | 0.00000 |
| 27 | M N2 APARTMENT | Cooling | 7027.29003 | 8432.74804 | 0.50391 | 0.60469 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 27.82900 | 8.22799E-003 | 88.24927 | 2.50000 | 5.19091E-002 | 0.00000 |
| 28 | M N2 APARTMENT | Heating | 660.12284 | 792.14740 | 2.89830E-002 | 5.19091E-002 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | 3.80000 | 5.05843E-003 | 88.24927 | 2.50000 | 5.19091E-002 | 0.00000 |
| 29 | M S1 APARTMENT | Cooling | 7626.97392 | 9152.36870 | 0.54782 | 0.65739 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 27.82900 | 8.22799E-003 | 88.24927 | 2.50000 | 5.19091E-002 | 0.00000 |
| 30 | M S1 APARTMENT | Heating | 934.06841 | 1120.88209 | 4.10101E-002 | 5.19091E-002 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | 3.80000 | 5.05843E-003 | 88.24927 | 2.50000 | 5.19091E-002 | 0.00000 |
| 31 | M S2 APARTMENT | Cooling | 7614.19754 | 9137.03705 | 0.54689 | 0.65627 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 27.82900 | 8.22799E-003 | 88.24927 | 2.50000 | 5.19091E-002 | 0.00000 |
| 32 | M S2 APARTMENT | Heating | 934.16134 | 1120.99361 | 4.10142E-002 | 5.19091E-002 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | 3.80000 | 5.05843E-003 | 88.24927 | 2.50000 | 5.19091E-002 | 0.00000 |
| 33 | T SW APARTMENT | Cooling | 4652.43098 | 5582.91717 | 0.33556 | 0.40267 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 27.82900 | 8.22799E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 34 | T SW APARTMENT | Heating | 1803.47085 | 2164.16503 | 7.91784E-002 | 9.50141E-002 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | 3.80000 | 5.05843E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 35 | T NW APARTMENT | Cooling | 4446.80756 | 5336.16907 | 0.32046 | 0.38455 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 27.82900 | 8.22799E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 36 | T NW APARTMENT | Heating | 1651.27847 | 1981.53417 | 7.24978E-002 | 8.69974E-002 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | 3.80000 | 5.05843E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 37 | T SE APARTMENT | Cooling | 4200.44452 | 5040.53342 | 0.30237 | 0.36285 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 27.82900 | 8.22799E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 38 | T SE APARTMENT | Heating | 1805.46470 | 2166.55764 | 7.92659E-002 | 9.51191E-002 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | 3.80000 | 5.05843E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 39 | T NE APARTMENT | Cooling | 3995.60631 | 4794.72757 | 0.28727 | 0.34473 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 27.82900 | 8.22799E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 40 | T NE APARTMENT | Heating | 1653.37655 | 1984.05186 | 7.25899E-002 | 8.71079E-002 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | 3.80000 | 5.05843E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 41 | T N1 APARTMENT | Cooling | 3795.90461 | 4555.08553 | 0.27253 | 0.32704 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 27.82900 | 8.22799E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 42 | T N1 APARTMENT | Heating | 1091.81991 | 1310.18389 | 4.79364E-002 | 5.75237E-002 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | 3.80000 | 5.05843E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 43 | T N2 APARTMENT | Cooling | 3778.83357 | 4534.60028 | 0.27127 | 0.32552 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 27.82900 | 8.22799E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 44 | T N2 APARTMENT | Heating | 1091.88232 | 1310.25878 | 4.79392E-002 | 5.75270E-002 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | 3.80000 | 5.05843E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 45 | T S1 APARTMENT | Cooling | 4016.36318 | 4819.63582 | 0.28881 | 0.34657 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 27.82900 | 8.22799E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 46 | T S1 APARTMENT | Heating | 1245.05099 | 1494.06118 | 5.46631E-002 | 6.55957E-002 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | 3.80000 | 5.05843E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 47 | T S2 APARTMENT | Cooling | 3999.26939 | 4799.12327 | 0.28755 | 0.34506 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 27.82900 | 8.22799E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 48 | T S2 APARTMENT | Heating | 1245.10976 | 1494.13171 | 5.46657E-002 | 6.55988E-002 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | 3.80000 | 5.05843E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
| 1 | SPLIT GSW | Cooling | Sensible | 4198.22 | 0.30598 | 0.30598 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
| 2 | SPLIT GSW | Heating | Sensible | 1703.83 | 5.21558E-002 | 5.21558E-002 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 04:10:00 |
| 3 | SPLIT GNW | Cooling | Sensible | 3858.34 | 0.28073 | 0.28073 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
| 4 | SPLIT GNW | Heating | Sensible | 1554.05 | 4.54832E-002 | 4.54832E-002 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 04:00:00 |
| 5 | SPLIT OFFICE | Cooling | Sensible | 4867.30 | 0.35929 | 0.35929 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
| 6 | SPLIT OFFICE | Heating | Sensible | 2428.10 | 7.33035E-002 | 7.33035E-002 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 18:50:00 |
| 7 | SPLIT GNE | Cooling | Sensible | 3604.28 | 0.26182 | 0.26182 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
| 8 | SPLIT GNE | Heating | Sensible | 1555.68 | 4.55556E-002 | 4.55556E-002 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 04:00:00 |
| 9 | SPLIT GN1 | Cooling | Sensible | 3402.85 | 0.24686 | 0.24686 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
| 10 | SPLIT GN1 | Heating | Sensible | 1115.74 | 2.59546E-002 | 2.59546E-002 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
| 11 | SPLIT GN2 | Cooling | Sensible | 3396.99 | 0.24642 | 0.24642 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
| 12 | SPLIT GN2 | Heating | Sensible | 1115.74 | 2.59546E-002 | 2.59546E-002 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
| 13 | SPLIT GS1 | Cooling | Sensible | 3729.18 | 0.27112 | 0.27112 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
| 14 | SPLIT GS1 | Heating | Sensible | 1198.17 | 2.96272E-002 | 2.96272E-002 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 04:10:00 |
| 15 | SPLIT GS2 | Cooling | Sensible | 3755.79 | 0.27310 | 0.27310 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
| 16 | SPLIT GS2 | Heating | Sensible | 1208.07 | 3.00683E-002 | 3.00683E-002 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 04:00:00 |
| 17 | SPLIT MSW | Cooling | Sensible | 10357.31 | 0.75794 | 0.75794 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
| 18 | SPLIT MSW | Heating | Sensible | 3298.33 | 9.94406E-002 | 9.94406E-002 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 |
| 19 | SPLIT MNW | Cooling | Sensible | 9733.03 | 0.71139 | 0.71139 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
| 20 | SPLIT MNW | Heating | Sensible | 2963.50 | 8.45231E-002 | 8.45231E-002 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 |
| 21 | SPLIT MSE | Cooling | Sensible | 9661.17 | 0.70608 | 0.70608 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
| 22 | SPLIT MSE | Heating | Sensible | 3302.49 | 9.96259E-002 | 9.96259E-002 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 |
| 23 | SPLIT MNE | Cooling | Sensible | 9045.25 | 0.66014 | 0.66014 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
| 24 | SPLIT MNE | Heating | Sensible | 2967.80 | 8.47148E-002 | 8.47148E-002 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 |
| 25 | SPLIT MN1 | Cooling | Sensible | 8312.45 | 0.60573 | 0.60573 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
| 26 | SPLIT MN1 | Heating | Sensible | 2231.48 | 5.19091E-002 | 5.19091E-002 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
| 27 | SPLIT MN2 | Cooling | Sensible | 8298.36 | 0.60469 | 0.60469 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
| 28 | SPLIT MN2 | Heating | Sensible | 2231.48 | 5.19091E-002 | 5.19091E-002 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
| 29 | SPLIT MS1 | Cooling | Sensible | 9007.96 | 0.65739 | 0.65739 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
| 30 | SPLIT MS1 | Heating | Sensible | 2231.48 | 5.19091E-002 | 5.19091E-002 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
| 31 | SPLIT MS2 | Cooling | Sensible | 8992.87 | 0.65627 | 0.65627 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
| 32 | SPLIT MS2 | Heating | Sensible | 2231.48 | 5.19091E-002 | 5.19091E-002 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
| 33 | SPLIT TSW | Cooling | Sensible | 5499.19 | 0.40267 | 0.40267 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
| 34 | SPLIT TSW | Heating | Sensible | 2665.82 | 9.50141E-002 | 9.50141E-002 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 |
| 35 | SPLIT TNW | Cooling | Sensible | 5255.87 | 0.38455 | 0.38455 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
| 36 | SPLIT TNW | Heating | Sensible | 2485.86 | 8.69974E-002 | 8.69974E-002 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 |
| 37 | SPLIT TSE | Cooling | Sensible | 4964.14 | 0.36285 | 0.36285 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
| 38 | SPLIT TSE | Heating | Sensible | 2668.18 | 9.51191E-002 | 9.51191E-002 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 |
| 39 | SPLIT TNE | Cooling | Sensible | 4721.10 | 0.34473 | 0.34473 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
| 40 | SPLIT TNE | Heating | Sensible | 2488.34 | 8.71079E-002 | 8.71079E-002 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 |
| 41 | SPLIT TN1 | Cooling | Sensible | 4483.85 | 0.32704 | 0.32704 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
| 42 | SPLIT TN1 | Heating | Sensible | 1824.30 | 5.75237E-002 | 5.75237E-002 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 |
| 43 | SPLIT TN2 | Cooling | Sensible | 4463.55 | 0.32552 | 0.32552 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
| 44 | SPLIT TN2 | Heating | Sensible | 1824.37 | 5.75270E-002 | 5.75270E-002 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 |
| 45 | SPLIT TS1 | Cooling | Sensible | 4745.74 | 0.34657 | 0.34657 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
| 46 | SPLIT TS1 | Heating | Sensible | 2005.49 | 6.55957E-002 | 6.55957E-002 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 |
| 47 | SPLIT TS2 | Cooling | Sensible | 4725.45 | 0.34506 | 0.34506 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
| 48 | SPLIT TS2 | Heating | Sensible | 2005.56 | 6.55988E-002 | 6.55988E-002 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 |
| Component Type | Component Name | Input Field Description | Value | |
| 1 | ZoneHVAC:EnergyRecoveryVentilator | G SW APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 2 | ZoneHVAC:EnergyRecoveryVentilator | G SW APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 2.59546E-002 |
| 3 | Fan:OnOff | G SW APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 4 | Fan:OnOff | G SW APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 5 | HeatExchanger:AirToAir:SensibleAndLatent | G SW APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 6 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | G SW APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.30598 |
| 7 | ZoneHVAC:EnergyRecoveryVentilator | G NW APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 8 | ZoneHVAC:EnergyRecoveryVentilator | G NW APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 2.59546E-002 |
| 9 | Fan:OnOff | G NW APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 10 | Fan:OnOff | G NW APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 11 | HeatExchanger:AirToAir:SensibleAndLatent | G NW APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 12 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | G NW APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.28073 |
| 13 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | OFFICE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.35929 |
| 14 | ZoneHVAC:EnergyRecoveryVentilator | G NE APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 15 | ZoneHVAC:EnergyRecoveryVentilator | G NE APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 2.59546E-002 |
| 16 | Fan:OnOff | G NE APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 17 | Fan:OnOff | G NE APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 18 | HeatExchanger:AirToAir:SensibleAndLatent | G NE APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 19 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | G NE APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.26182 |
| 20 | ZoneHVAC:EnergyRecoveryVentilator | G N1 APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 21 | ZoneHVAC:EnergyRecoveryVentilator | G N1 APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 2.59546E-002 |
| 22 | Fan:OnOff | G N1 APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 23 | Fan:OnOff | G N1 APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 24 | HeatExchanger:AirToAir:SensibleAndLatent | G N1 APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 25 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | G N1 APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.24686 |
| 26 | ZoneHVAC:EnergyRecoveryVentilator | G N2 APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 27 | ZoneHVAC:EnergyRecoveryVentilator | G N2 APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 2.59546E-002 |
| 28 | Fan:OnOff | G N2 APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 29 | Fan:OnOff | G N2 APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 30 | HeatExchanger:AirToAir:SensibleAndLatent | G N2 APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 31 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | G N2 APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.24642 |
| 32 | ZoneHVAC:EnergyRecoveryVentilator | G S1 APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 33 | ZoneHVAC:EnergyRecoveryVentilator | G S1 APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 2.59546E-002 |
| 34 | Fan:OnOff | G S1 APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 35 | Fan:OnOff | G S1 APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 36 | HeatExchanger:AirToAir:SensibleAndLatent | G S1 APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 37 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | G S1 APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.27112 |
| 38 | ZoneHVAC:EnergyRecoveryVentilator | G S2 APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 39 | ZoneHVAC:EnergyRecoveryVentilator | G S2 APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 2.59546E-002 |
| 40 | Fan:OnOff | G S2 APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 41 | Fan:OnOff | G S2 APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 42 | HeatExchanger:AirToAir:SensibleAndLatent | G S2 APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 43 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | G S2 APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.27310 |
| 44 | ZoneHVAC:EnergyRecoveryVentilator | M SW APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 5.19091E-002 |
| 45 | ZoneHVAC:EnergyRecoveryVentilator | M SW APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 5.19091E-002 |
| 46 | Fan:OnOff | M SW APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 5.19091E-002 |
| 47 | Fan:OnOff | M SW APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 5.19091E-002 |
| 48 | HeatExchanger:AirToAir:SensibleAndLatent | M SW APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 5.19091E-002 |
| 49 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | M SW APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.75794 |
| 50 | ZoneHVAC:EnergyRecoveryVentilator | M NW APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 5.19091E-002 |
| 51 | ZoneHVAC:EnergyRecoveryVentilator | M NW APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 5.19091E-002 |
| 52 | Fan:OnOff | M NW APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 5.19091E-002 |
| 53 | Fan:OnOff | M NW APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 5.19091E-002 |
| 54 | HeatExchanger:AirToAir:SensibleAndLatent | M NW APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 5.19091E-002 |
| 55 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | M NW APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.71139 |
| 56 | ZoneHVAC:EnergyRecoveryVentilator | M SE APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 5.19091E-002 |
| 57 | ZoneHVAC:EnergyRecoveryVentilator | M SE APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 5.19091E-002 |
| 58 | Fan:OnOff | M SE APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 5.19091E-002 |
| 59 | Fan:OnOff | M SE APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 5.19091E-002 |
| 60 | HeatExchanger:AirToAir:SensibleAndLatent | M SE APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 5.19091E-002 |
| 61 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | M SE APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.70608 |
| 62 | ZoneHVAC:EnergyRecoveryVentilator | M NE APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 5.19091E-002 |
| 63 | ZoneHVAC:EnergyRecoveryVentilator | M NE APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 5.19091E-002 |
| 64 | Fan:OnOff | M NE APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 5.19091E-002 |
| 65 | Fan:OnOff | M NE APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 5.19091E-002 |
| 66 | HeatExchanger:AirToAir:SensibleAndLatent | M NE APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 5.19091E-002 |
| 67 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | M NE APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.66014 |
| 68 | ZoneHVAC:EnergyRecoveryVentilator | M N1 APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 5.19091E-002 |
| 69 | ZoneHVAC:EnergyRecoveryVentilator | M N1 APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 5.19091E-002 |
| 70 | Fan:OnOff | M N1 APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 5.19091E-002 |
| 71 | Fan:OnOff | M N1 APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 5.19091E-002 |
| 72 | HeatExchanger:AirToAir:SensibleAndLatent | M N1 APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 5.19091E-002 |
| 73 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | M N1 APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.60573 |
| 74 | ZoneHVAC:EnergyRecoveryVentilator | M N2 APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 5.19091E-002 |
| 75 | ZoneHVAC:EnergyRecoveryVentilator | M N2 APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 5.19091E-002 |
| 76 | Fan:OnOff | M N2 APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 5.19091E-002 |
| 77 | Fan:OnOff | M N2 APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 5.19091E-002 |
| 78 | HeatExchanger:AirToAir:SensibleAndLatent | M N2 APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 5.19091E-002 |
| 79 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | M N2 APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.60469 |
| 80 | ZoneHVAC:EnergyRecoveryVentilator | M S1 APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 5.19091E-002 |
| 81 | ZoneHVAC:EnergyRecoveryVentilator | M S1 APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 5.19091E-002 |
| 82 | Fan:OnOff | M S1 APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 5.19091E-002 |
| 83 | Fan:OnOff | M S1 APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 5.19091E-002 |
| 84 | HeatExchanger:AirToAir:SensibleAndLatent | M S1 APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 5.19091E-002 |
| 85 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | M S1 APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.65739 |
| 86 | ZoneHVAC:EnergyRecoveryVentilator | M S2 APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 5.19091E-002 |
| 87 | ZoneHVAC:EnergyRecoveryVentilator | M S2 APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 5.19091E-002 |
| 88 | Fan:OnOff | M S2 APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 5.19091E-002 |
| 89 | Fan:OnOff | M S2 APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 5.19091E-002 |
| 90 | HeatExchanger:AirToAir:SensibleAndLatent | M S2 APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 5.19091E-002 |
| 91 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | M S2 APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.65627 |
| 92 | ZoneHVAC:EnergyRecoveryVentilator | T SW APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 93 | ZoneHVAC:EnergyRecoveryVentilator | T SW APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 2.59546E-002 |
| 94 | Fan:OnOff | T SW APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 95 | Fan:OnOff | T SW APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 96 | HeatExchanger:AirToAir:SensibleAndLatent | T SW APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 97 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | T SW APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.40267 |
| 98 | ZoneHVAC:EnergyRecoveryVentilator | T NW APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 99 | ZoneHVAC:EnergyRecoveryVentilator | T NW APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 2.59546E-002 |
| 100 | Fan:OnOff | T NW APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 101 | Fan:OnOff | T NW APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 102 | HeatExchanger:AirToAir:SensibleAndLatent | T NW APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 103 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | T NW APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.38455 |
| 104 | ZoneHVAC:EnergyRecoveryVentilator | T SE APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 105 | ZoneHVAC:EnergyRecoveryVentilator | T SE APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 2.59546E-002 |
| 106 | Fan:OnOff | T SE APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 107 | Fan:OnOff | T SE APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 108 | HeatExchanger:AirToAir:SensibleAndLatent | T SE APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 109 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | T SE APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.36285 |
| 110 | ZoneHVAC:EnergyRecoveryVentilator | T NE APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 111 | ZoneHVAC:EnergyRecoveryVentilator | T NE APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 2.59546E-002 |
| 112 | Fan:OnOff | T NE APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 113 | Fan:OnOff | T NE APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 114 | HeatExchanger:AirToAir:SensibleAndLatent | T NE APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 115 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | T NE APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.34473 |
| 116 | ZoneHVAC:EnergyRecoveryVentilator | T N1 APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 117 | ZoneHVAC:EnergyRecoveryVentilator | T N1 APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 2.59546E-002 |
| 118 | Fan:OnOff | T N1 APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 119 | Fan:OnOff | T N1 APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 120 | HeatExchanger:AirToAir:SensibleAndLatent | T N1 APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 121 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | T N1 APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.32704 |
| 122 | ZoneHVAC:EnergyRecoveryVentilator | T N2 APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 123 | ZoneHVAC:EnergyRecoveryVentilator | T N2 APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 2.59546E-002 |
| 124 | Fan:OnOff | T N2 APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 125 | Fan:OnOff | T N2 APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 126 | HeatExchanger:AirToAir:SensibleAndLatent | T N2 APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 127 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | T N2 APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.32552 |
| 128 | ZoneHVAC:EnergyRecoveryVentilator | T S1 APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 129 | ZoneHVAC:EnergyRecoveryVentilator | T S1 APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 2.59546E-002 |
| 130 | Fan:OnOff | T S1 APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 131 | Fan:OnOff | T S1 APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 132 | HeatExchanger:AirToAir:SensibleAndLatent | T S1 APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 133 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | T S1 APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.34657 |
| 134 | ZoneHVAC:EnergyRecoveryVentilator | T S2 APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 135 | ZoneHVAC:EnergyRecoveryVentilator | T S2 APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 2.59546E-002 |
| 136 | Fan:OnOff | T S2 APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 137 | Fan:OnOff | T S2 APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 138 | HeatExchanger:AirToAir:SensibleAndLatent | T S2 APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 139 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | T S2 APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.34506 |
| 140 | AirLoopHVAC | SPLIT GSW | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.30598 |
| 141 | AirLoopHVAC | SPLIT GSW | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.30598 |
| 142 | AirLoopHVAC | SPLIT GSW | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.30598 |
| 143 | AirLoopHVAC | SPLIT GSW | Adjusted Heating Design Air Flow Rate [m3/s] | 0.30598 |
| 144 | AirLoopHVAC | SPLIT GSW | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.30598 |
| 145 | AirLoopHVAC | SPLIT GSW | Adjusted Main Design Air Flow Rate [m3/s] | 0.30598 |
| 146 | AirLoopHVAC | SPLIT GSW | User Heating Air Flow Ratio [] | 1.00000 |
| 147 | AirLoopHVAC | SPLIT GSW | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 148 | AirLoopHVAC | SPLIT GNW | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.28073 |
| 149 | AirLoopHVAC | SPLIT GNW | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.28073 |
| 150 | AirLoopHVAC | SPLIT GNW | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.28073 |
| 151 | AirLoopHVAC | SPLIT GNW | Adjusted Heating Design Air Flow Rate [m3/s] | 0.28073 |
| 152 | AirLoopHVAC | SPLIT GNW | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.28073 |
| 153 | AirLoopHVAC | SPLIT GNW | Adjusted Main Design Air Flow Rate [m3/s] | 0.28073 |
| 154 | AirLoopHVAC | SPLIT GNW | User Heating Air Flow Ratio [] | 1.00000 |
| 155 | AirLoopHVAC | SPLIT GNW | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 156 | AirLoopHVAC | SPLIT OFFICE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.35929 |
| 157 | AirLoopHVAC | SPLIT OFFICE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.35929 |
| 158 | AirLoopHVAC | SPLIT OFFICE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.35929 |
| 159 | AirLoopHVAC | SPLIT OFFICE | Adjusted Heating Design Air Flow Rate [m3/s] | 0.35929 |
| 160 | AirLoopHVAC | SPLIT OFFICE | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.35929 |
| 161 | AirLoopHVAC | SPLIT OFFICE | Adjusted Main Design Air Flow Rate [m3/s] | 0.35929 |
| 162 | AirLoopHVAC | SPLIT OFFICE | User Heating Air Flow Ratio [] | 1.00000 |
| 163 | AirLoopHVAC | SPLIT OFFICE | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 164 | AirLoopHVAC | SPLIT GNE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.26182 |
| 165 | AirLoopHVAC | SPLIT GNE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.26182 |
| 166 | AirLoopHVAC | SPLIT GNE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.26182 |
| 167 | AirLoopHVAC | SPLIT GNE | Adjusted Heating Design Air Flow Rate [m3/s] | 0.26182 |
| 168 | AirLoopHVAC | SPLIT GNE | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.26182 |
| 169 | AirLoopHVAC | SPLIT GNE | Adjusted Main Design Air Flow Rate [m3/s] | 0.26182 |
| 170 | AirLoopHVAC | SPLIT GNE | User Heating Air Flow Ratio [] | 1.00000 |
| 171 | AirLoopHVAC | SPLIT GNE | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 172 | AirLoopHVAC | SPLIT GN1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.24686 |
| 173 | AirLoopHVAC | SPLIT GN1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.24686 |
| 174 | AirLoopHVAC | SPLIT GN1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.24686 |
| 175 | AirLoopHVAC | SPLIT GN1 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.24686 |
| 176 | AirLoopHVAC | SPLIT GN1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.24686 |
| 177 | AirLoopHVAC | SPLIT GN1 | Adjusted Main Design Air Flow Rate [m3/s] | 0.24686 |
| 178 | AirLoopHVAC | SPLIT GN1 | User Heating Air Flow Ratio [] | 1.00000 |
| 179 | AirLoopHVAC | SPLIT GN1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 180 | AirLoopHVAC | SPLIT GN2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.24642 |
| 181 | AirLoopHVAC | SPLIT GN2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.24642 |
| 182 | AirLoopHVAC | SPLIT GN2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.24642 |
| 183 | AirLoopHVAC | SPLIT GN2 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.24642 |
| 184 | AirLoopHVAC | SPLIT GN2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.24642 |
| 185 | AirLoopHVAC | SPLIT GN2 | Adjusted Main Design Air Flow Rate [m3/s] | 0.24642 |
| 186 | AirLoopHVAC | SPLIT GN2 | User Heating Air Flow Ratio [] | 1.00000 |
| 187 | AirLoopHVAC | SPLIT GN2 | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 188 | AirLoopHVAC | SPLIT GS1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.27112 |
| 189 | AirLoopHVAC | SPLIT GS1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.27112 |
| 190 | AirLoopHVAC | SPLIT GS1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.27112 |
| 191 | AirLoopHVAC | SPLIT GS1 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.27112 |
| 192 | AirLoopHVAC | SPLIT GS1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.27112 |
| 193 | AirLoopHVAC | SPLIT GS1 | Adjusted Main Design Air Flow Rate [m3/s] | 0.27112 |
| 194 | AirLoopHVAC | SPLIT GS1 | User Heating Air Flow Ratio [] | 1.00000 |
| 195 | AirLoopHVAC | SPLIT GS1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 196 | AirLoopHVAC | SPLIT GS2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.27310 |
| 197 | AirLoopHVAC | SPLIT GS2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.27310 |
| 198 | AirLoopHVAC | SPLIT GS2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.27310 |
| 199 | AirLoopHVAC | SPLIT GS2 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.27310 |
| 200 | AirLoopHVAC | SPLIT GS2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.27310 |
| 201 | AirLoopHVAC | SPLIT GS2 | Adjusted Main Design Air Flow Rate [m3/s] | 0.27310 |
| 202 | AirLoopHVAC | SPLIT GS2 | User Heating Air Flow Ratio [] | 1.00000 |
| 203 | AirLoopHVAC | SPLIT GS2 | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 204 | AirLoopHVAC | SPLIT MSW | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.75794 |
| 205 | AirLoopHVAC | SPLIT MSW | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.75794 |
| 206 | AirLoopHVAC | SPLIT MSW | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.75794 |
| 207 | AirLoopHVAC | SPLIT MSW | Adjusted Heating Design Air Flow Rate [m3/s] | 0.75794 |
| 208 | AirLoopHVAC | SPLIT MSW | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.75794 |
| 209 | AirLoopHVAC | SPLIT MSW | Adjusted Main Design Air Flow Rate [m3/s] | 0.75794 |
| 210 | AirLoopHVAC | SPLIT MSW | User Heating Air Flow Ratio [] | 1.00000 |
| 211 | AirLoopHVAC | SPLIT MSW | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 212 | AirLoopHVAC | SPLIT MNW | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.71139 |
| 213 | AirLoopHVAC | SPLIT MNW | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.71139 |
| 214 | AirLoopHVAC | SPLIT MNW | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.71139 |
| 215 | AirLoopHVAC | SPLIT MNW | Adjusted Heating Design Air Flow Rate [m3/s] | 0.71139 |
| 216 | AirLoopHVAC | SPLIT MNW | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.71139 |
| 217 | AirLoopHVAC | SPLIT MNW | Adjusted Main Design Air Flow Rate [m3/s] | 0.71139 |
| 218 | AirLoopHVAC | SPLIT MNW | User Heating Air Flow Ratio [] | 1.00000 |
| 219 | AirLoopHVAC | SPLIT MNW | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 220 | AirLoopHVAC | SPLIT MSE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.70608 |
| 221 | AirLoopHVAC | SPLIT MSE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.70608 |
| 222 | AirLoopHVAC | SPLIT MSE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.70608 |
| 223 | AirLoopHVAC | SPLIT MSE | Adjusted Heating Design Air Flow Rate [m3/s] | 0.70608 |
| 224 | AirLoopHVAC | SPLIT MSE | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.70608 |
| 225 | AirLoopHVAC | SPLIT MSE | Adjusted Main Design Air Flow Rate [m3/s] | 0.70608 |
| 226 | AirLoopHVAC | SPLIT MSE | User Heating Air Flow Ratio [] | 1.00000 |
| 227 | AirLoopHVAC | SPLIT MSE | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 228 | AirLoopHVAC | SPLIT MNE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.66014 |
| 229 | AirLoopHVAC | SPLIT MNE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.66014 |
| 230 | AirLoopHVAC | SPLIT MNE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.66014 |
| 231 | AirLoopHVAC | SPLIT MNE | Adjusted Heating Design Air Flow Rate [m3/s] | 0.66014 |
| 232 | AirLoopHVAC | SPLIT MNE | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.66014 |
| 233 | AirLoopHVAC | SPLIT MNE | Adjusted Main Design Air Flow Rate [m3/s] | 0.66014 |
| 234 | AirLoopHVAC | SPLIT MNE | User Heating Air Flow Ratio [] | 1.00000 |
| 235 | AirLoopHVAC | SPLIT MNE | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 236 | AirLoopHVAC | SPLIT MN1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.60573 |
| 237 | AirLoopHVAC | SPLIT MN1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.60573 |
| 238 | AirLoopHVAC | SPLIT MN1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.60573 |
| 239 | AirLoopHVAC | SPLIT MN1 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.60573 |
| 240 | AirLoopHVAC | SPLIT MN1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.60573 |
| 241 | AirLoopHVAC | SPLIT MN1 | Adjusted Main Design Air Flow Rate [m3/s] | 0.60573 |
| 242 | AirLoopHVAC | SPLIT MN1 | User Heating Air Flow Ratio [] | 1.00000 |
| 243 | AirLoopHVAC | SPLIT MN1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 244 | AirLoopHVAC | SPLIT MN2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.60469 |
| 245 | AirLoopHVAC | SPLIT MN2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.60469 |
| 246 | AirLoopHVAC | SPLIT MN2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.60469 |
| 247 | AirLoopHVAC | SPLIT MN2 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.60469 |
| 248 | AirLoopHVAC | SPLIT MN2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.60469 |
| 249 | AirLoopHVAC | SPLIT MN2 | Adjusted Main Design Air Flow Rate [m3/s] | 0.60469 |
| 250 | AirLoopHVAC | SPLIT MN2 | User Heating Air Flow Ratio [] | 1.00000 |
| 251 | AirLoopHVAC | SPLIT MN2 | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 252 | AirLoopHVAC | SPLIT MS1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.65739 |
| 253 | AirLoopHVAC | SPLIT MS1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.65739 |
| 254 | AirLoopHVAC | SPLIT MS1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.65739 |
| 255 | AirLoopHVAC | SPLIT MS1 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.65739 |
| 256 | AirLoopHVAC | SPLIT MS1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.65739 |
| 257 | AirLoopHVAC | SPLIT MS1 | Adjusted Main Design Air Flow Rate [m3/s] | 0.65739 |
| 258 | AirLoopHVAC | SPLIT MS1 | User Heating Air Flow Ratio [] | 1.00000 |
| 259 | AirLoopHVAC | SPLIT MS1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 260 | AirLoopHVAC | SPLIT MS2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.65627 |
| 261 | AirLoopHVAC | SPLIT MS2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.65627 |
| 262 | AirLoopHVAC | SPLIT MS2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.65627 |
| 263 | AirLoopHVAC | SPLIT MS2 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.65627 |
| 264 | AirLoopHVAC | SPLIT MS2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.65627 |
| 265 | AirLoopHVAC | SPLIT MS2 | Adjusted Main Design Air Flow Rate [m3/s] | 0.65627 |
| 266 | AirLoopHVAC | SPLIT MS2 | User Heating Air Flow Ratio [] | 1.00000 |
| 267 | AirLoopHVAC | SPLIT MS2 | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 268 | AirLoopHVAC | SPLIT TSW | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.40267 |
| 269 | AirLoopHVAC | SPLIT TSW | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.40267 |
| 270 | AirLoopHVAC | SPLIT TSW | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.40267 |
| 271 | AirLoopHVAC | SPLIT TSW | Adjusted Heating Design Air Flow Rate [m3/s] | 0.40267 |
| 272 | AirLoopHVAC | SPLIT TSW | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.40267 |
| 273 | AirLoopHVAC | SPLIT TSW | Adjusted Main Design Air Flow Rate [m3/s] | 0.40267 |
| 274 | AirLoopHVAC | SPLIT TSW | User Heating Air Flow Ratio [] | 1.00000 |
| 275 | AirLoopHVAC | SPLIT TSW | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 276 | AirLoopHVAC | SPLIT TNW | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.38455 |
| 277 | AirLoopHVAC | SPLIT TNW | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.38455 |
| 278 | AirLoopHVAC | SPLIT TNW | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.38455 |
| 279 | AirLoopHVAC | SPLIT TNW | Adjusted Heating Design Air Flow Rate [m3/s] | 0.38455 |
| 280 | AirLoopHVAC | SPLIT TNW | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.38455 |
| 281 | AirLoopHVAC | SPLIT TNW | Adjusted Main Design Air Flow Rate [m3/s] | 0.38455 |
| 282 | AirLoopHVAC | SPLIT TNW | User Heating Air Flow Ratio [] | 1.00000 |
| 283 | AirLoopHVAC | SPLIT TNW | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 284 | AirLoopHVAC | SPLIT TSE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.36285 |
| 285 | AirLoopHVAC | SPLIT TSE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.36285 |
| 286 | AirLoopHVAC | SPLIT TSE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.36285 |
| 287 | AirLoopHVAC | SPLIT TSE | Adjusted Heating Design Air Flow Rate [m3/s] | 0.36285 |
| 288 | AirLoopHVAC | SPLIT TSE | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.36285 |
| 289 | AirLoopHVAC | SPLIT TSE | Adjusted Main Design Air Flow Rate [m3/s] | 0.36285 |
| 290 | AirLoopHVAC | SPLIT TSE | User Heating Air Flow Ratio [] | 1.00000 |
| 291 | AirLoopHVAC | SPLIT TSE | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 292 | AirLoopHVAC | SPLIT TNE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.34473 |
| 293 | AirLoopHVAC | SPLIT TNE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.34473 |
| 294 | AirLoopHVAC | SPLIT TNE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.34473 |
| 295 | AirLoopHVAC | SPLIT TNE | Adjusted Heating Design Air Flow Rate [m3/s] | 0.34473 |
| 296 | AirLoopHVAC | SPLIT TNE | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.34473 |
| 297 | AirLoopHVAC | SPLIT TNE | Adjusted Main Design Air Flow Rate [m3/s] | 0.34473 |
| 298 | AirLoopHVAC | SPLIT TNE | User Heating Air Flow Ratio [] | 1.00000 |
| 299 | AirLoopHVAC | SPLIT TNE | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 300 | AirLoopHVAC | SPLIT TN1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.32704 |
| 301 | AirLoopHVAC | SPLIT TN1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.32704 |
| 302 | AirLoopHVAC | SPLIT TN1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.32704 |
| 303 | AirLoopHVAC | SPLIT TN1 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.32704 |
| 304 | AirLoopHVAC | SPLIT TN1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.32704 |
| 305 | AirLoopHVAC | SPLIT TN1 | Adjusted Main Design Air Flow Rate [m3/s] | 0.32704 |
| 306 | AirLoopHVAC | SPLIT TN1 | User Heating Air Flow Ratio [] | 1.00000 |
| 307 | AirLoopHVAC | SPLIT TN1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 308 | AirLoopHVAC | SPLIT TN2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.32552 |
| 309 | AirLoopHVAC | SPLIT TN2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.32552 |
| 310 | AirLoopHVAC | SPLIT TN2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.32552 |
| 311 | AirLoopHVAC | SPLIT TN2 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.32552 |
| 312 | AirLoopHVAC | SPLIT TN2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.32552 |
| 313 | AirLoopHVAC | SPLIT TN2 | Adjusted Main Design Air Flow Rate [m3/s] | 0.32552 |
| 314 | AirLoopHVAC | SPLIT TN2 | User Heating Air Flow Ratio [] | 1.00000 |
| 315 | AirLoopHVAC | SPLIT TN2 | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 316 | AirLoopHVAC | SPLIT TS1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.34657 |
| 317 | AirLoopHVAC | SPLIT TS1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.34657 |
| 318 | AirLoopHVAC | SPLIT TS1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.34657 |
| 319 | AirLoopHVAC | SPLIT TS1 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.34657 |
| 320 | AirLoopHVAC | SPLIT TS1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.34657 |
| 321 | AirLoopHVAC | SPLIT TS1 | Adjusted Main Design Air Flow Rate [m3/s] | 0.34657 |
| 322 | AirLoopHVAC | SPLIT TS1 | User Heating Air Flow Ratio [] | 1.00000 |
| 323 | AirLoopHVAC | SPLIT TS1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 324 | AirLoopHVAC | SPLIT TS2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.34506 |
| 325 | AirLoopHVAC | SPLIT TS2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.34506 |
| 326 | AirLoopHVAC | SPLIT TS2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.34506 |
| 327 | AirLoopHVAC | SPLIT TS2 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.34506 |
| 328 | AirLoopHVAC | SPLIT TS2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.34506 |
| 329 | AirLoopHVAC | SPLIT TS2 | Adjusted Main Design Air Flow Rate [m3/s] | 0.34506 |
| 330 | AirLoopHVAC | SPLIT TS2 | User Heating Air Flow Ratio [] | 1.00000 |
| 331 | AirLoopHVAC | SPLIT TS2 | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 332 | AirLoopHVAC | SPLIT GSW | Design Supply Air Flow Rate [m3/s] | 0.30598 |
| 333 | AirLoopHVAC | SPLIT GNW | Design Supply Air Flow Rate [m3/s] | 0.28073 |
| 334 | AirLoopHVAC | SPLIT OFFICE | Design Supply Air Flow Rate [m3/s] | 0.35929 |
| 335 | AirLoopHVAC | SPLIT GNE | Design Supply Air Flow Rate [m3/s] | 0.26182 |
| 336 | AirLoopHVAC | SPLIT GN1 | Design Supply Air Flow Rate [m3/s] | 0.24686 |
| 337 | AirLoopHVAC | SPLIT GN2 | Design Supply Air Flow Rate [m3/s] | 0.24642 |
| 338 | AirLoopHVAC | SPLIT GS1 | Design Supply Air Flow Rate [m3/s] | 0.27112 |
| 339 | AirLoopHVAC | SPLIT GS2 | Design Supply Air Flow Rate [m3/s] | 0.27310 |
| 340 | AirLoopHVAC | SPLIT MSW | Design Supply Air Flow Rate [m3/s] | 0.75794 |
| 341 | AirLoopHVAC | SPLIT MNW | Design Supply Air Flow Rate [m3/s] | 0.71139 |
| 342 | AirLoopHVAC | SPLIT MSE | Design Supply Air Flow Rate [m3/s] | 0.70608 |
| 343 | AirLoopHVAC | SPLIT MNE | Design Supply Air Flow Rate [m3/s] | 0.66014 |
| 344 | AirLoopHVAC | SPLIT MN1 | Design Supply Air Flow Rate [m3/s] | 0.60573 |
| 345 | AirLoopHVAC | SPLIT MN2 | Design Supply Air Flow Rate [m3/s] | 0.60469 |
| 346 | AirLoopHVAC | SPLIT MS1 | Design Supply Air Flow Rate [m3/s] | 0.65739 |
| 347 | AirLoopHVAC | SPLIT MS2 | Design Supply Air Flow Rate [m3/s] | 0.65627 |
| 348 | AirLoopHVAC | SPLIT TSW | Design Supply Air Flow Rate [m3/s] | 0.40267 |
| 349 | AirLoopHVAC | SPLIT TNW | Design Supply Air Flow Rate [m3/s] | 0.38455 |
| 350 | AirLoopHVAC | SPLIT TSE | Design Supply Air Flow Rate [m3/s] | 0.36285 |
| 351 | AirLoopHVAC | SPLIT TNE | Design Supply Air Flow Rate [m3/s] | 0.34473 |
| 352 | AirLoopHVAC | SPLIT TN1 | Design Supply Air Flow Rate [m3/s] | 0.32704 |
| 353 | AirLoopHVAC | SPLIT TN2 | Design Supply Air Flow Rate [m3/s] | 0.32552 |
| 354 | AirLoopHVAC | SPLIT TS1 | Design Supply Air Flow Rate [m3/s] | 0.34657 |
| 355 | AirLoopHVAC | SPLIT TS2 | Design Supply Air Flow Rate [m3/s] | 0.34506 |
| 356 | Controller:OutdoorAir | SPLIT GSW_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.30598 |
| 357 | Controller:OutdoorAir | SPLIT GSW_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.59546E-002 |
| 358 | AirLoopHVAC:UnitarySystem | SPLIT GSW_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.30598 |
| 359 | AirLoopHVAC:UnitarySystem | SPLIT GSW_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.30598 |
| 360 | AirLoopHVAC:UnitarySystem | SPLIT GSW_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.30598 |
| 361 | AirLoopHVAC:UnitarySystem | SPLIT GSW_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.30598 |
| 362 | AirLoopHVAC:UnitarySystem | SPLIT GSW_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 5064.99066 |
| 363 | AirLoopHVAC:UnitarySystem | SPLIT GSW_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 7400.80481 |
| 364 | AirLoopHVAC:UnitarySystem | SPLIT GSW_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 365 | AirLoopHVAC:UnitarySystem | SPLIT GSW_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 366 | Fan:OnOff | SPLIT GSW SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.30598 |
| 367 | Coil:Cooling:DX:SingleSpeed | SPLIT GSW COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.30598 |
| 368 | Coil:Cooling:DX:SingleSpeed | SPLIT GSW COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 5064.99066 |
| 369 | Coil:Cooling:DX:SingleSpeed | SPLIT GSW COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
| 370 | Coil:Heating:Fuel | SPLIT GSW HEATING COIL | Design Size Nominal Capacity [W] | 7400.80481 |
| 371 | Controller:OutdoorAir | SPLIT GNW_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.28073 |
| 372 | Controller:OutdoorAir | SPLIT GNW_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.59546E-002 |
| 373 | AirLoopHVAC:UnitarySystem | SPLIT GNW_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.28073 |
| 374 | AirLoopHVAC:UnitarySystem | SPLIT GNW_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.28073 |
| 375 | AirLoopHVAC:UnitarySystem | SPLIT GNW_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.28073 |
| 376 | AirLoopHVAC:UnitarySystem | SPLIT GNW_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.28073 |
| 377 | AirLoopHVAC:UnitarySystem | SPLIT GNW_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 4647.04381 |
| 378 | AirLoopHVAC:UnitarySystem | SPLIT GNW_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 6834.01528 |
| 379 | AirLoopHVAC:UnitarySystem | SPLIT GNW_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 380 | AirLoopHVAC:UnitarySystem | SPLIT GNW_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 381 | Fan:OnOff | SPLIT GNW SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.28073 |
| 382 | Coil:Cooling:DX:SingleSpeed | SPLIT GNW COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.28073 |
| 383 | Coil:Cooling:DX:SingleSpeed | SPLIT GNW COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 4647.04381 |
| 384 | Coil:Cooling:DX:SingleSpeed | SPLIT GNW COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
| 385 | Coil:Heating:Fuel | SPLIT GNW HEATING COIL | Design Size Nominal Capacity [W] | 6834.01528 |
| 386 | Controller:OutdoorAir | SPLIT OFFICE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.35929 |
| 387 | Controller:OutdoorAir | SPLIT OFFICE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 3.81060E-002 |
| 388 | AirLoopHVAC:UnitarySystem | SPLIT OFFICE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.35929 |
| 389 | AirLoopHVAC:UnitarySystem | SPLIT OFFICE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.35929 |
| 390 | AirLoopHVAC:UnitarySystem | SPLIT OFFICE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.35929 |
| 391 | AirLoopHVAC:UnitarySystem | SPLIT OFFICE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.35929 |
| 392 | AirLoopHVAC:UnitarySystem | SPLIT OFFICE_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 5947.52817 |
| 393 | AirLoopHVAC:UnitarySystem | SPLIT OFFICE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 8846.95238 |
| 394 | AirLoopHVAC:UnitarySystem | SPLIT OFFICE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 395 | AirLoopHVAC:UnitarySystem | SPLIT OFFICE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 396 | Fan:OnOff | SPLIT OFFICE SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.35929 |
| 397 | Coil:Cooling:DX:SingleSpeed | SPLIT OFFICE COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.35929 |
| 398 | Coil:Cooling:DX:SingleSpeed | SPLIT OFFICE COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 5947.52817 |
| 399 | Coil:Cooling:DX:SingleSpeed | SPLIT OFFICE COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
| 400 | Coil:Heating:Fuel | SPLIT OFFICE HEATING COIL | Design Size Nominal Capacity [W] | 8846.95238 |
| 401 | Controller:OutdoorAir | SPLIT GNE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.26182 |
| 402 | Controller:OutdoorAir | SPLIT GNE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.59546E-002 |
| 403 | AirLoopHVAC:UnitarySystem | SPLIT GNE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.26182 |
| 404 | AirLoopHVAC:UnitarySystem | SPLIT GNE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.26182 |
| 405 | AirLoopHVAC:UnitarySystem | SPLIT GNE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.26182 |
| 406 | AirLoopHVAC:UnitarySystem | SPLIT GNE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.26182 |
| 407 | AirLoopHVAC:UnitarySystem | SPLIT GNE_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 4333.98455 |
| 408 | AirLoopHVAC:UnitarySystem | SPLIT GNE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 6409.54590 |
| 409 | AirLoopHVAC:UnitarySystem | SPLIT GNE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 410 | AirLoopHVAC:UnitarySystem | SPLIT GNE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 411 | Fan:OnOff | SPLIT GNE SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.26182 |
| 412 | Coil:Cooling:DX:SingleSpeed | SPLIT GNE COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.26182 |
| 413 | Coil:Cooling:DX:SingleSpeed | SPLIT GNE COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 4333.98455 |
| 414 | Coil:Cooling:DX:SingleSpeed | SPLIT GNE COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
| 415 | Coil:Heating:Fuel | SPLIT GNE HEATING COIL | Design Size Nominal Capacity [W] | 6409.54590 |
| 416 | Controller:OutdoorAir | SPLIT GN1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.24686 |
| 417 | Controller:OutdoorAir | SPLIT GN1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.59546E-002 |
| 418 | AirLoopHVAC:UnitarySystem | SPLIT GN1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.24686 |
| 419 | AirLoopHVAC:UnitarySystem | SPLIT GN1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.24686 |
| 420 | AirLoopHVAC:UnitarySystem | SPLIT GN1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.24686 |
| 421 | AirLoopHVAC:UnitarySystem | SPLIT GN1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.24686 |
| 422 | AirLoopHVAC:UnitarySystem | SPLIT GN1_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 4086.35030 |
| 423 | AirLoopHVAC:UnitarySystem | SPLIT GN1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 6073.72195 |
| 424 | AirLoopHVAC:UnitarySystem | SPLIT GN1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 425 | AirLoopHVAC:UnitarySystem | SPLIT GN1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 426 | Fan:OnOff | SPLIT GN1 SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.24686 |
| 427 | Coil:Cooling:DX:SingleSpeed | SPLIT GN1 COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.24686 |
| 428 | Coil:Cooling:DX:SingleSpeed | SPLIT GN1 COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 4086.35030 |
| 429 | Coil:Cooling:DX:SingleSpeed | SPLIT GN1 COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
| 430 | Coil:Heating:Fuel | SPLIT GN1 HEATING COIL | Design Size Nominal Capacity [W] | 6073.72195 |
| 431 | Controller:OutdoorAir | SPLIT GN2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.24642 |
| 432 | Controller:OutdoorAir | SPLIT GN2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.59546E-002 |
| 433 | AirLoopHVAC:UnitarySystem | SPLIT GN2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.24642 |
| 434 | AirLoopHVAC:UnitarySystem | SPLIT GN2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.24642 |
| 435 | AirLoopHVAC:UnitarySystem | SPLIT GN2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.24642 |
| 436 | AirLoopHVAC:UnitarySystem | SPLIT GN2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.24642 |
| 437 | AirLoopHVAC:UnitarySystem | SPLIT GN2_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 4079.16108 |
| 438 | AirLoopHVAC:UnitarySystem | SPLIT GN2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 6063.97439 |
| 439 | AirLoopHVAC:UnitarySystem | SPLIT GN2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 440 | AirLoopHVAC:UnitarySystem | SPLIT GN2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 441 | Fan:OnOff | SPLIT GN2 SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.24642 |
| 442 | Coil:Cooling:DX:SingleSpeed | SPLIT GN2 COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.24642 |
| 443 | Coil:Cooling:DX:SingleSpeed | SPLIT GN2 COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 4079.16108 |
| 444 | Coil:Cooling:DX:SingleSpeed | SPLIT GN2 COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
| 445 | Coil:Heating:Fuel | SPLIT GN2 HEATING COIL | Design Size Nominal Capacity [W] | 6063.97439 |
| 446 | Controller:OutdoorAir | SPLIT GS1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.27112 |
| 447 | Controller:OutdoorAir | SPLIT GS1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.59546E-002 |
| 448 | AirLoopHVAC:UnitarySystem | SPLIT GS1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.27112 |
| 449 | AirLoopHVAC:UnitarySystem | SPLIT GS1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.27112 |
| 450 | AirLoopHVAC:UnitarySystem | SPLIT GS1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.27112 |
| 451 | AirLoopHVAC:UnitarySystem | SPLIT GS1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.27112 |
| 452 | AirLoopHVAC:UnitarySystem | SPLIT GS1_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 4487.95648 |
| 453 | AirLoopHVAC:UnitarySystem | SPLIT GS1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 6618.33605 |
| 454 | AirLoopHVAC:UnitarySystem | SPLIT GS1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 455 | AirLoopHVAC:UnitarySystem | SPLIT GS1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 456 | Fan:OnOff | SPLIT GS1 SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.27112 |
| 457 | Coil:Cooling:DX:SingleSpeed | SPLIT GS1 COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.27112 |
| 458 | Coil:Cooling:DX:SingleSpeed | SPLIT GS1 COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 4487.95648 |
| 459 | Coil:Cooling:DX:SingleSpeed | SPLIT GS1 COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
| 460 | Coil:Heating:Fuel | SPLIT GS1 HEATING COIL | Design Size Nominal Capacity [W] | 6618.33605 |
| 461 | Controller:OutdoorAir | SPLIT GS2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.27310 |
| 462 | Controller:OutdoorAir | SPLIT GS2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.59546E-002 |
| 463 | AirLoopHVAC:UnitarySystem | SPLIT GS2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.27310 |
| 464 | AirLoopHVAC:UnitarySystem | SPLIT GS2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.27310 |
| 465 | AirLoopHVAC:UnitarySystem | SPLIT GS2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.27310 |
| 466 | AirLoopHVAC:UnitarySystem | SPLIT GS2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.27310 |
| 467 | AirLoopHVAC:UnitarySystem | SPLIT GS2_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 4520.79741 |
| 468 | AirLoopHVAC:UnitarySystem | SPLIT GS2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 6662.86467 |
| 469 | AirLoopHVAC:UnitarySystem | SPLIT GS2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 470 | AirLoopHVAC:UnitarySystem | SPLIT GS2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 471 | Fan:OnOff | SPLIT GS2 SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.27310 |
| 472 | Coil:Cooling:DX:SingleSpeed | SPLIT GS2 COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.27310 |
| 473 | Coil:Cooling:DX:SingleSpeed | SPLIT GS2 COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 4520.79741 |
| 474 | Coil:Cooling:DX:SingleSpeed | SPLIT GS2 COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
| 475 | Coil:Heating:Fuel | SPLIT GS2 HEATING COIL | Design Size Nominal Capacity [W] | 6662.86467 |
| 476 | Controller:OutdoorAir | SPLIT MSW_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.75794 |
| 477 | Controller:OutdoorAir | SPLIT MSW_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 5.19091E-002 |
| 478 | AirLoopHVAC:UnitarySystem | SPLIT MSW_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.75794 |
| 479 | AirLoopHVAC:UnitarySystem | SPLIT MSW_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.75794 |
| 480 | AirLoopHVAC:UnitarySystem | SPLIT MSW_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.75794 |
| 481 | AirLoopHVAC:UnitarySystem | SPLIT MSW_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.75794 |
| 482 | AirLoopHVAC:UnitarySystem | SPLIT MSW_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 12546.58441 |
| 483 | AirLoopHVAC:UnitarySystem | SPLIT MSW_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 18078.42140 |
| 484 | AirLoopHVAC:UnitarySystem | SPLIT MSW_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 485 | AirLoopHVAC:UnitarySystem | SPLIT MSW_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 486 | Fan:OnOff | SPLIT MSW SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.75794 |
| 487 | Coil:Cooling:DX:SingleSpeed | SPLIT MSW COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.75794 |
| 488 | Coil:Cooling:DX:SingleSpeed | SPLIT MSW COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 12546.58441 |
| 489 | Coil:Cooling:DX:SingleSpeed | SPLIT MSW COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
| 490 | Coil:Heating:Fuel | SPLIT MSW HEATING COIL | Design Size Nominal Capacity [W] | 18078.42140 |
| 491 | Controller:OutdoorAir | SPLIT MNW_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.71139 |
| 492 | Controller:OutdoorAir | SPLIT MNW_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 5.19091E-002 |
| 493 | AirLoopHVAC:UnitarySystem | SPLIT MNW_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.71139 |
| 494 | AirLoopHVAC:UnitarySystem | SPLIT MNW_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.71139 |
| 495 | AirLoopHVAC:UnitarySystem | SPLIT MNW_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.71139 |
| 496 | AirLoopHVAC:UnitarySystem | SPLIT MNW_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.71139 |
| 497 | AirLoopHVAC:UnitarySystem | SPLIT MNW_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 11776.06857 |
| 498 | AirLoopHVAC:UnitarySystem | SPLIT MNW_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 17033.44649 |
| 499 | AirLoopHVAC:UnitarySystem | SPLIT MNW_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 500 | AirLoopHVAC:UnitarySystem | SPLIT MNW_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 501 | Fan:OnOff | SPLIT MNW SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.71139 |
| 502 | Coil:Cooling:DX:SingleSpeed | SPLIT MNW COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.71139 |
| 503 | Coil:Cooling:DX:SingleSpeed | SPLIT MNW COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 11776.06857 |
| 504 | Coil:Cooling:DX:SingleSpeed | SPLIT MNW COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
| 505 | Coil:Heating:Fuel | SPLIT MNW HEATING COIL | Design Size Nominal Capacity [W] | 17033.44649 |
| 506 | Controller:OutdoorAir | SPLIT MSE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.70608 |
| 507 | Controller:OutdoorAir | SPLIT MSE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 5.19091E-002 |
| 508 | AirLoopHVAC:UnitarySystem | SPLIT MSE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.70608 |
| 509 | AirLoopHVAC:UnitarySystem | SPLIT MSE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.70608 |
| 510 | AirLoopHVAC:UnitarySystem | SPLIT MSE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.70608 |
| 511 | AirLoopHVAC:UnitarySystem | SPLIT MSE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.70608 |
| 512 | AirLoopHVAC:UnitarySystem | SPLIT MSE_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 11688.21301 |
| 513 | AirLoopHVAC:UnitarySystem | SPLIT MSE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 16914.54669 |
| 514 | AirLoopHVAC:UnitarySystem | SPLIT MSE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 515 | AirLoopHVAC:UnitarySystem | SPLIT MSE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 516 | Fan:OnOff | SPLIT MSE SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.70608 |
| 517 | Coil:Cooling:DX:SingleSpeed | SPLIT MSE COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.70608 |
| 518 | Coil:Cooling:DX:SingleSpeed | SPLIT MSE COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 11688.21301 |
| 519 | Coil:Cooling:DX:SingleSpeed | SPLIT MSE COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
| 520 | Coil:Heating:Fuel | SPLIT MSE HEATING COIL | Design Size Nominal Capacity [W] | 16914.54669 |
| 521 | Controller:OutdoorAir | SPLIT MNE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.66014 |
| 522 | Controller:OutdoorAir | SPLIT MNE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 5.19091E-002 |
| 523 | AirLoopHVAC:UnitarySystem | SPLIT MNE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.66014 |
| 524 | AirLoopHVAC:UnitarySystem | SPLIT MNE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.66014 |
| 525 | AirLoopHVAC:UnitarySystem | SPLIT MNE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.66014 |
| 526 | AirLoopHVAC:UnitarySystem | SPLIT MNE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.66014 |
| 527 | AirLoopHVAC:UnitarySystem | SPLIT MNE_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 10927.69311 |
| 528 | AirLoopHVAC:UnitarySystem | SPLIT MNE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 15883.14278 |
| 529 | AirLoopHVAC:UnitarySystem | SPLIT MNE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 530 | AirLoopHVAC:UnitarySystem | SPLIT MNE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 531 | Fan:OnOff | SPLIT MNE SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.66014 |
| 532 | Coil:Cooling:DX:SingleSpeed | SPLIT MNE COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.66014 |
| 533 | Coil:Cooling:DX:SingleSpeed | SPLIT MNE COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 10927.69311 |
| 534 | Coil:Cooling:DX:SingleSpeed | SPLIT MNE COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
| 535 | Coil:Heating:Fuel | SPLIT MNE HEATING COIL | Design Size Nominal Capacity [W] | 15883.14278 |
| 536 | Controller:OutdoorAir | SPLIT MN1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.60573 |
| 537 | Controller:OutdoorAir | SPLIT MN1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 5.19091E-002 |
| 538 | AirLoopHVAC:UnitarySystem | SPLIT MN1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.60573 |
| 539 | AirLoopHVAC:UnitarySystem | SPLIT MN1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.60573 |
| 540 | AirLoopHVAC:UnitarySystem | SPLIT MN1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.60573 |
| 541 | AirLoopHVAC:UnitarySystem | SPLIT MN1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.60573 |
| 542 | AirLoopHVAC:UnitarySystem | SPLIT MN1_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 10027.01929 |
| 543 | AirLoopHVAC:UnitarySystem | SPLIT MN1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 14661.72848 |
| 544 | AirLoopHVAC:UnitarySystem | SPLIT MN1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 545 | AirLoopHVAC:UnitarySystem | SPLIT MN1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 546 | Fan:OnOff | SPLIT MN1 SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.60573 |
| 547 | Coil:Cooling:DX:SingleSpeed | SPLIT MN1 COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.60573 |
| 548 | Coil:Cooling:DX:SingleSpeed | SPLIT MN1 COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 10027.01929 |
| 549 | Coil:Cooling:DX:SingleSpeed | SPLIT MN1 COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
| 550 | Coil:Heating:Fuel | SPLIT MN1 HEATING COIL | Design Size Nominal Capacity [W] | 14661.72848 |
| 551 | Controller:OutdoorAir | SPLIT MN2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.60469 |
| 552 | Controller:OutdoorAir | SPLIT MN2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 5.19091E-002 |
| 553 | AirLoopHVAC:UnitarySystem | SPLIT MN2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.60469 |
| 554 | AirLoopHVAC:UnitarySystem | SPLIT MN2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.60469 |
| 555 | AirLoopHVAC:UnitarySystem | SPLIT MN2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.60469 |
| 556 | AirLoopHVAC:UnitarySystem | SPLIT MN2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.60469 |
| 557 | AirLoopHVAC:UnitarySystem | SPLIT MN2_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 10009.70141 |
| 558 | AirLoopHVAC:UnitarySystem | SPLIT MN2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 14638.24773 |
| 559 | AirLoopHVAC:UnitarySystem | SPLIT MN2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 560 | AirLoopHVAC:UnitarySystem | SPLIT MN2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 561 | Fan:OnOff | SPLIT MN2 SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.60469 |
| 562 | Coil:Cooling:DX:SingleSpeed | SPLIT MN2 COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.60469 |
| 563 | Coil:Cooling:DX:SingleSpeed | SPLIT MN2 COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 10009.70141 |
| 564 | Coil:Cooling:DX:SingleSpeed | SPLIT MN2 COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
| 565 | Coil:Heating:Fuel | SPLIT MN2 HEATING COIL | Design Size Nominal Capacity [W] | 14638.24773 |
| 566 | Controller:OutdoorAir | SPLIT MS1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.65739 |
| 567 | Controller:OutdoorAir | SPLIT MS1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 5.19091E-002 |
| 568 | AirLoopHVAC:UnitarySystem | SPLIT MS1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.65739 |
| 569 | AirLoopHVAC:UnitarySystem | SPLIT MS1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.65739 |
| 570 | AirLoopHVAC:UnitarySystem | SPLIT MS1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.65739 |
| 571 | AirLoopHVAC:UnitarySystem | SPLIT MS1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.65739 |
| 572 | AirLoopHVAC:UnitarySystem | SPLIT MS1_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 10882.13692 |
| 573 | AirLoopHVAC:UnitarySystem | SPLIT MS1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 15821.36232 |
| 574 | AirLoopHVAC:UnitarySystem | SPLIT MS1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 575 | AirLoopHVAC:UnitarySystem | SPLIT MS1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 576 | Fan:OnOff | SPLIT MS1 SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.65739 |
| 577 | Coil:Cooling:DX:SingleSpeed | SPLIT MS1 COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.65739 |
| 578 | Coil:Cooling:DX:SingleSpeed | SPLIT MS1 COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 10882.13692 |
| 579 | Coil:Cooling:DX:SingleSpeed | SPLIT MS1 COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
| 580 | Coil:Heating:Fuel | SPLIT MS1 HEATING COIL | Design Size Nominal Capacity [W] | 15821.36232 |
| 581 | Controller:OutdoorAir | SPLIT MS2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.65627 |
| 582 | Controller:OutdoorAir | SPLIT MS2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 5.19091E-002 |
| 583 | AirLoopHVAC:UnitarySystem | SPLIT MS2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.65627 |
| 584 | AirLoopHVAC:UnitarySystem | SPLIT MS2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.65627 |
| 585 | AirLoopHVAC:UnitarySystem | SPLIT MS2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.65627 |
| 586 | AirLoopHVAC:UnitarySystem | SPLIT MS2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.65627 |
| 587 | AirLoopHVAC:UnitarySystem | SPLIT MS2_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 10863.62274 |
| 588 | AirLoopHVAC:UnitarySystem | SPLIT MS2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 15796.25914 |
| 589 | AirLoopHVAC:UnitarySystem | SPLIT MS2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 590 | AirLoopHVAC:UnitarySystem | SPLIT MS2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 591 | Fan:OnOff | SPLIT MS2 SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.65627 |
| 592 | Coil:Cooling:DX:SingleSpeed | SPLIT MS2 COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.65627 |
| 593 | Coil:Cooling:DX:SingleSpeed | SPLIT MS2 COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 10863.62274 |
| 594 | Coil:Cooling:DX:SingleSpeed | SPLIT MS2 COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
| 595 | Coil:Heating:Fuel | SPLIT MS2 HEATING COIL | Design Size Nominal Capacity [W] | 15796.25914 |
| 596 | Controller:OutdoorAir | SPLIT TSW_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.40267 |
| 597 | Controller:OutdoorAir | SPLIT TSW_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.59546E-002 |
| 598 | AirLoopHVAC:UnitarySystem | SPLIT TSW_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.40267 |
| 599 | AirLoopHVAC:UnitarySystem | SPLIT TSW_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.40267 |
| 600 | AirLoopHVAC:UnitarySystem | SPLIT TSW_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.40267 |
| 601 | AirLoopHVAC:UnitarySystem | SPLIT TSW_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.40267 |
| 602 | AirLoopHVAC:UnitarySystem | SPLIT TSW_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 6665.58220 |
| 603 | AirLoopHVAC:UnitarySystem | SPLIT TSW_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 9571.27210 |
| 604 | AirLoopHVAC:UnitarySystem | SPLIT TSW_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 605 | AirLoopHVAC:UnitarySystem | SPLIT TSW_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 606 | Fan:OnOff | SPLIT TSW SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.40267 |
| 607 | Coil:Cooling:DX:SingleSpeed | SPLIT TSW COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.40267 |
| 608 | Coil:Cooling:DX:SingleSpeed | SPLIT TSW COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 6665.58220 |
| 609 | Coil:Cooling:DX:SingleSpeed | SPLIT TSW COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
| 610 | Coil:Heating:Fuel | SPLIT TSW HEATING COIL | Design Size Nominal Capacity [W] | 9571.27210 |
| 611 | Controller:OutdoorAir | SPLIT TNW_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.38455 |
| 612 | Controller:OutdoorAir | SPLIT TNW_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.59546E-002 |
| 613 | AirLoopHVAC:UnitarySystem | SPLIT TNW_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.38455 |
| 614 | AirLoopHVAC:UnitarySystem | SPLIT TNW_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.38455 |
| 615 | AirLoopHVAC:UnitarySystem | SPLIT TNW_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.38455 |
| 616 | AirLoopHVAC:UnitarySystem | SPLIT TNW_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.38455 |
| 617 | AirLoopHVAC:UnitarySystem | SPLIT TNW_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 6365.69659 |
| 618 | AirLoopHVAC:UnitarySystem | SPLIT TNW_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 9164.51941 |
| 619 | AirLoopHVAC:UnitarySystem | SPLIT TNW_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 620 | AirLoopHVAC:UnitarySystem | SPLIT TNW_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 621 | Fan:OnOff | SPLIT TNW SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.38455 |
| 622 | Coil:Cooling:DX:SingleSpeed | SPLIT TNW COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.38455 |
| 623 | Coil:Cooling:DX:SingleSpeed | SPLIT TNW COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 6365.69659 |
| 624 | Coil:Cooling:DX:SingleSpeed | SPLIT TNW COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
| 625 | Coil:Heating:Fuel | SPLIT TNW HEATING COIL | Design Size Nominal Capacity [W] | 9164.51941 |
| 626 | Controller:OutdoorAir | SPLIT TSE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.36285 |
| 627 | Controller:OutdoorAir | SPLIT TSE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.59546E-002 |
| 628 | AirLoopHVAC:UnitarySystem | SPLIT TSE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.36285 |
| 629 | AirLoopHVAC:UnitarySystem | SPLIT TSE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.36285 |
| 630 | AirLoopHVAC:UnitarySystem | SPLIT TSE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.36285 |
| 631 | AirLoopHVAC:UnitarySystem | SPLIT TSE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.36285 |
| 632 | AirLoopHVAC:UnitarySystem | SPLIT TSE_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 6006.39453 |
| 633 | AirLoopHVAC:UnitarySystem | SPLIT TSE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 8677.45661 |
| 634 | AirLoopHVAC:UnitarySystem | SPLIT TSE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 635 | AirLoopHVAC:UnitarySystem | SPLIT TSE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 636 | Fan:OnOff | SPLIT TSE SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.36285 |
| 637 | Coil:Cooling:DX:SingleSpeed | SPLIT TSE COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.36285 |
| 638 | Coil:Cooling:DX:SingleSpeed | SPLIT TSE COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 6006.39453 |
| 639 | Coil:Cooling:DX:SingleSpeed | SPLIT TSE COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
| 640 | Coil:Heating:Fuel | SPLIT TSE HEATING COIL | Design Size Nominal Capacity [W] | 8677.45661 |
| 641 | Controller:OutdoorAir | SPLIT TNE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.34473 |
| 642 | Controller:OutdoorAir | SPLIT TNE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.59546E-002 |
| 643 | AirLoopHVAC:UnitarySystem | SPLIT TNE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.34473 |
| 644 | AirLoopHVAC:UnitarySystem | SPLIT TNE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.34473 |
| 645 | AirLoopHVAC:UnitarySystem | SPLIT TNE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.34473 |
| 646 | AirLoopHVAC:UnitarySystem | SPLIT TNE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.34473 |
| 647 | AirLoopHVAC:UnitarySystem | SPLIT TNE_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 5706.49069 |
| 648 | AirLoopHVAC:UnitarySystem | SPLIT TNE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 8270.69334 |
| 649 | AirLoopHVAC:UnitarySystem | SPLIT TNE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 650 | AirLoopHVAC:UnitarySystem | SPLIT TNE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 651 | Fan:OnOff | SPLIT TNE SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.34473 |
| 652 | Coil:Cooling:DX:SingleSpeed | SPLIT TNE COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.34473 |
| 653 | Coil:Cooling:DX:SingleSpeed | SPLIT TNE COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 5706.49069 |
| 654 | Coil:Cooling:DX:SingleSpeed | SPLIT TNE COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
| 655 | Coil:Heating:Fuel | SPLIT TNE HEATING COIL | Design Size Nominal Capacity [W] | 8270.69334 |
| 656 | Controller:OutdoorAir | SPLIT TN1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.32704 |
| 657 | Controller:OutdoorAir | SPLIT TN1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.59546E-002 |
| 658 | AirLoopHVAC:UnitarySystem | SPLIT TN1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.32704 |
| 659 | AirLoopHVAC:UnitarySystem | SPLIT TN1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.32704 |
| 660 | AirLoopHVAC:UnitarySystem | SPLIT TN1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.32704 |
| 661 | AirLoopHVAC:UnitarySystem | SPLIT TN1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.32704 |
| 662 | AirLoopHVAC:UnitarySystem | SPLIT TN1_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 5413.63068 |
| 663 | AirLoopHVAC:UnitarySystem | SPLIT TN1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 7873.44384 |
| 664 | AirLoopHVAC:UnitarySystem | SPLIT TN1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 665 | AirLoopHVAC:UnitarySystem | SPLIT TN1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 666 | Fan:OnOff | SPLIT TN1 SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.32704 |
| 667 | Coil:Cooling:DX:SingleSpeed | SPLIT TN1 COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.32704 |
| 668 | Coil:Cooling:DX:SingleSpeed | SPLIT TN1 COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 5413.63068 |
| 669 | Coil:Cooling:DX:SingleSpeed | SPLIT TN1 COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
| 670 | Coil:Heating:Fuel | SPLIT TN1 HEATING COIL | Design Size Nominal Capacity [W] | 7873.44384 |
| 671 | Controller:OutdoorAir | SPLIT TN2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.32552 |
| 672 | Controller:OutdoorAir | SPLIT TN2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.59546E-002 |
| 673 | AirLoopHVAC:UnitarySystem | SPLIT TN2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.32552 |
| 674 | AirLoopHVAC:UnitarySystem | SPLIT TN2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.32552 |
| 675 | AirLoopHVAC:UnitarySystem | SPLIT TN2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.32552 |
| 676 | AirLoopHVAC:UnitarySystem | SPLIT TN2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.32552 |
| 677 | AirLoopHVAC:UnitarySystem | SPLIT TN2_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 5388.57449 |
| 678 | AirLoopHVAC:UnitarySystem | SPLIT TN2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 7839.47061 |
| 679 | AirLoopHVAC:UnitarySystem | SPLIT TN2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 680 | AirLoopHVAC:UnitarySystem | SPLIT TN2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 681 | Fan:OnOff | SPLIT TN2 SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.32552 |
| 682 | Coil:Cooling:DX:SingleSpeed | SPLIT TN2 COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.32552 |
| 683 | Coil:Cooling:DX:SingleSpeed | SPLIT TN2 COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 5388.57449 |
| 684 | Coil:Cooling:DX:SingleSpeed | SPLIT TN2 COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
| 685 | Coil:Heating:Fuel | SPLIT TN2 HEATING COIL | Design Size Nominal Capacity [W] | 7839.47061 |
| 686 | Controller:OutdoorAir | SPLIT TS1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.34657 |
| 687 | Controller:OutdoorAir | SPLIT TS1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.59546E-002 |
| 688 | AirLoopHVAC:UnitarySystem | SPLIT TS1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.34657 |
| 689 | AirLoopHVAC:UnitarySystem | SPLIT TS1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.34657 |
| 690 | AirLoopHVAC:UnitarySystem | SPLIT TS1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.34657 |
| 691 | AirLoopHVAC:UnitarySystem | SPLIT TS1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.34657 |
| 692 | AirLoopHVAC:UnitarySystem | SPLIT TS1_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 5736.94458 |
| 693 | AirLoopHVAC:UnitarySystem | SPLIT TS1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 8311.93945 |
| 694 | AirLoopHVAC:UnitarySystem | SPLIT TS1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 695 | AirLoopHVAC:UnitarySystem | SPLIT TS1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 696 | Fan:OnOff | SPLIT TS1 SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.34657 |
| 697 | Coil:Cooling:DX:SingleSpeed | SPLIT TS1 COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.34657 |
| 698 | Coil:Cooling:DX:SingleSpeed | SPLIT TS1 COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 5736.94458 |
| 699 | Coil:Cooling:DX:SingleSpeed | SPLIT TS1 COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
| 700 | Coil:Heating:Fuel | SPLIT TS1 HEATING COIL | Design Size Nominal Capacity [W] | 8311.93945 |
| 701 | Controller:OutdoorAir | SPLIT TS2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.34506 |
| 702 | Controller:OutdoorAir | SPLIT TS2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.59546E-002 |
| 703 | AirLoopHVAC:UnitarySystem | SPLIT TS2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.34506 |
| 704 | AirLoopHVAC:UnitarySystem | SPLIT TS2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.34506 |
| 705 | AirLoopHVAC:UnitarySystem | SPLIT TS2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.34506 |
| 706 | AirLoopHVAC:UnitarySystem | SPLIT TS2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.34506 |
| 707 | AirLoopHVAC:UnitarySystem | SPLIT TS2_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 5711.90668 |
| 708 | AirLoopHVAC:UnitarySystem | SPLIT TS2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 8277.99045 |
| 709 | AirLoopHVAC:UnitarySystem | SPLIT TS2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 710 | AirLoopHVAC:UnitarySystem | SPLIT TS2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 711 | Fan:OnOff | SPLIT TS2 SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.34506 |
| 712 | Coil:Cooling:DX:SingleSpeed | SPLIT TS2 COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.34506 |
| 713 | Coil:Cooling:DX:SingleSpeed | SPLIT TS2 COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 5711.90668 |
| 714 | Coil:Cooling:DX:SingleSpeed | SPLIT TS2 COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
| 715 | Coil:Heating:Fuel | SPLIT TS2 HEATING COIL | Design Size Nominal Capacity [W] | 8277.99045 |
| Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
| 1 | Coil:Cooling:DX:SingleSpeed | SPLIT GSW COOLING COIL | 4825.2 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 |
| 2 | Coil:Cooling:DX:SingleSpeed | SPLIT GNW COOLING COIL | 4427.0 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 |
| 3 | Coil:Cooling:DX:SingleSpeed | SPLIT OFFICE COOLING COIL | 5666.0 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 |
| 4 | Coil:Cooling:DX:SingleSpeed | SPLIT GNE COOLING COIL | 4128.8 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 |
| 5 | Coil:Cooling:DX:SingleSpeed | SPLIT GN1 COOLING COIL | 3892.9 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 |
| 6 | Coil:Cooling:DX:SingleSpeed | SPLIT GN2 COOLING COIL | 3886.0 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 |
| 7 | Coil:Cooling:DX:SingleSpeed | SPLIT GS1 COOLING COIL | 4275.5 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 |
| 8 | Coil:Cooling:DX:SingleSpeed | SPLIT GS2 COOLING COIL | 4306.8 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 |
| 9 | Coil:Cooling:DX:SingleSpeed | SPLIT MSW COOLING COIL | 11952.6 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 |
| 10 | Coil:Cooling:DX:SingleSpeed | SPLIT MNW COOLING COIL | 11218.6 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 |
| 11 | Coil:Cooling:DX:SingleSpeed | SPLIT MSE COOLING COIL | 11134.9 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 |
| 12 | Coil:Cooling:DX:SingleSpeed | SPLIT MNE COOLING COIL | 10410.3 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 |
| 13 | Coil:Cooling:DX:SingleSpeed | SPLIT MN1 COOLING COIL | 9552.3 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 |
| 14 | Coil:Cooling:DX:SingleSpeed | SPLIT MN2 COOLING COIL | 9535.8 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 |
| 15 | Coil:Cooling:DX:SingleSpeed | SPLIT MS1 COOLING COIL | 10366.9 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 |
| 16 | Coil:Cooling:DX:SingleSpeed | SPLIT MS2 COOLING COIL | 10349.3 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 |
| 17 | Coil:Cooling:DX:SingleSpeed | SPLIT TSW COOLING COIL | 6350.0 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 |
| 18 | Coil:Cooling:DX:SingleSpeed | SPLIT TNW COOLING COIL | 6064.3 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 |
| 19 | Coil:Cooling:DX:SingleSpeed | SPLIT TSE COOLING COIL | 5722.0 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 |
| 20 | Coil:Cooling:DX:SingleSpeed | SPLIT TNE COOLING COIL | 5436.3 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 |
| 21 | Coil:Cooling:DX:SingleSpeed | SPLIT TN1 COOLING COIL | 5157.3 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 |
| 22 | Coil:Cooling:DX:SingleSpeed | SPLIT TN2 COOLING COIL | 5133.5 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 |
| 23 | Coil:Cooling:DX:SingleSpeed | SPLIT TS1 COOLING COIL | 5465.3 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 |
| 24 | Coil:Cooling:DX:SingleSpeed | SPLIT TS2 COOLING COIL | 5441.5 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 |
| Zone Name | # Surfaces | |
| 1 | G SW APARTMENT | 9 |
| 2 | G NW APARTMENT | 9 |
| 3 | OFFICE | 9 |
| 4 | G NE APARTMENT | 9 |
| 5 | G N1 APARTMENT | 8 |
| 6 | G N2 APARTMENT | 8 |
| 7 | G S1 APARTMENT | 8 |
| 8 | G S2 APARTMENT | 8 |
| 9 | M SW APARTMENT | 9 |
| 10 | M NW APARTMENT | 9 |
| 11 | M SE APARTMENT | 9 |
| 12 | M NE APARTMENT | 9 |
| 13 | M N1 APARTMENT | 8 |
| 14 | M N2 APARTMENT | 8 |
| 15 | M S1 APARTMENT | 8 |
| 16 | M S2 APARTMENT | 8 |
| 17 | T SW APARTMENT | 9 |
| 18 | T NW APARTMENT | 9 |
| 19 | T SE APARTMENT | 9 |
| 20 | T NE APARTMENT | 9 |
| 21 | T N1 APARTMENT | 8 |
| 22 | T N2 APARTMENT | 8 |
| 23 | T S1 APARTMENT | 8 |
| 24 | T S2 APARTMENT | 8 |
| 25 | T CORRIDOR | 13 |
| 26 | G CORRIDOR | 13 |
| 27 | M CORRIDOR | 13 |
| Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
| 1 | G SWALL SWA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_GRD | 0.752 | 0.676 | 28.24 | 35.30 | 28.24 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 2 | GWINDOW1 S SWA | Window | G SWALL SWA | Window5 Detailed Fenestration | RESWINDOW_U_0.4945_SHGC_0.25 | N/A | 2.811 | No | 7.06 | 7.06 | 7.06 | 180.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 3 | G WWALL SWA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_GRD | 0.752 | 0.676 | 18.58 | 23.22 | 18.58 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 4 | GWINDOW1 W SWA | Window | G WWALL SWA | Window5 Detailed Fenestration | RESWINDOW_U_0.4945_SHGC_0.25 | N/A | 2.811 | No | 4.65 | 4.65 | 4.65 | 270.00 | 90.00 | 3.81 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 5 | G NIWALL SWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-G NIWALL SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 6 | G EIWALL SWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | iz-G EIWALL SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 7 | G GFLOOR SWA | Floor | CTF - ConductionTransferFunction | GGFLOORSWA_FFACTOR | 0.287 | 0.268 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 8 | G CEILIN SWA | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | G CEILIN SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 9 | G INTERNALMASS SWA | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 88.25 | 88.25 | 88.25 | 0.00 | 90.00 | 88.25 | 1.00 | 0.00 | G INTERNALMASS SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 10 | G NWALL NWA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_GRD | 0.752 | 0.676 | 28.24 | 35.30 | 28.24 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 11 | GWINDOW1 N NWA | Window | G NWALL NWA | Window5 Detailed Fenestration | RESWINDOW_U_0.4945_SHGC_0.25 | N/A | 2.811 | No | 7.06 | 7.06 | 7.06 | 0.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 12 | G WWALL NWA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_GRD | 0.752 | 0.676 | 18.58 | 23.22 | 18.58 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 13 | GWINDOW1 W NWA | Window | G WWALL NWA | Window5 Detailed Fenestration | RESWINDOW_U_0.4945_SHGC_0.25 | N/A | 2.811 | No | 4.65 | 4.65 | 4.65 | 270.00 | 90.00 | 3.81 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 14 | G SIWALL NWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-G SIWALL NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 15 | G EIWALL NWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | iz-G EIWALL NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 16 | G GFLOOR NWA | Floor | CTF - ConductionTransferFunction | GGFLOORNWA_FFACTOR | 0.287 | 0.268 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 17 | G CEILIN NWA | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | G CEILIN NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 18 | G INTERNALMASS NWA | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 88.25 | 88.25 | 88.25 | 0.00 | 90.00 | 88.25 | 1.00 | 0.00 | G INTERNALMASS NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 19 | G SWALL SEA | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.752 | 0.676 | 28.24 | 35.30 | 28.24 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 20 | GWINDOW1 S SEA | Window | G SWALL SEA | Window5 Detailed Fenestration | NONRESWINDOW_U_0.4945_SHGC_0.25 | N/A | 2.811 | No | 7.06 | 7.06 | 7.06 | 180.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 21 | G EWALL SEA | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.752 | 0.676 | 18.58 | 23.22 | 18.58 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 22 | GWINDOW1 E SEA | Window | G EWALL SEA | Window5 Detailed Fenestration | NONRESWINDOW_U_0.4945_SHGC_0.25 | N/A | 2.811 | No | 4.65 | 4.65 | 4.65 | 90.00 | 90.00 | 3.81 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 23 | G NIWALL SEA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-G NIWALL SEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 24 | iz-G EIWALL S2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | G EIWALL S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 25 | G GFLOOR SEA | Floor | CTF - ConductionTransferFunction | GGFLOORSEA_FFACTOR | 0.287 | 0.268 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 26 | G CEILIN SEA | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | G CEILIN SEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 27 | G INTERNALMASS SEA | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 88.25 | 88.25 | 88.25 | 0.00 | 90.00 | 88.25 | 1.00 | 0.00 | G INTERNALMASS SEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 28 | G NWALL NEA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_GRD | 0.752 | 0.676 | 28.24 | 35.30 | 28.24 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 29 | GWINDOW1 N NEA | Window | G NWALL NEA | Window5 Detailed Fenestration | RESWINDOW_U_0.4945_SHGC_0.25 | N/A | 2.811 | No | 7.06 | 7.06 | 7.06 | 0.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 30 | G EWALL NEA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_GRD | 0.752 | 0.676 | 18.58 | 23.22 | 18.58 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 31 | GWINDOW1 E NEA | Window | G EWALL NEA | Window5 Detailed Fenestration | RESWINDOW_U_0.4945_SHGC_0.25 | N/A | 2.811 | No | 4.65 | 4.65 | 4.65 | 90.00 | 90.00 | 3.81 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 32 | G SIWALL NEA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-G SIWALL NEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 33 | iz-G EIWALL N2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | G EIWALL N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 34 | G GFLOOR NEA | Floor | CTF - ConductionTransferFunction | GGFLOORNEA_FFACTOR | 0.287 | 0.268 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 35 | G CEILIN NEA | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | G CEILIN NEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 36 | G INTERNALMASS NEA | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 88.25 | 88.25 | 88.25 | 0.00 | 90.00 | 88.25 | 1.00 | 0.00 | G INTERNALMASS NEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 37 | G NWALL N1A | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_GRD | 0.752 | 0.676 | 28.24 | 35.30 | 28.24 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 38 | GWINDOW1 N N1A | Window | G NWALL N1A | Window5 Detailed Fenestration | RESWINDOW_U_0.4945_SHGC_0.25 | N/A | 2.811 | No | 7.06 | 7.06 | 7.06 | 0.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 39 | G SIWALL N1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-G SIWALL N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 40 | G EIWALL N1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | iz-G EIWALL N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 41 | iz-G EIWALL NWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | G EIWALL NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 42 | G GFLOOR N1A | Floor | CTF - ConductionTransferFunction | GGFLOORN1A_FFACTOR | 0.170 | 0.163 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 43 | G CEILIN N1A | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | G CEILIN N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 44 | G INTERNALMASS N1A | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 88.25 | 88.25 | 88.25 | 0.00 | 90.00 | 88.25 | 1.00 | 0.00 | G INTERNALMASS N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 45 | G NWALL N2A | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_GRD | 0.752 | 0.676 | 28.24 | 35.30 | 28.24 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 46 | GWINDOW1 N N2A | Window | G NWALL N2A | Window5 Detailed Fenestration | RESWINDOW_U_0.4945_SHGC_0.25 | N/A | 2.811 | No | 7.06 | 7.06 | 7.06 | 0.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 47 | G SIWALL N2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-G SIWALL N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 48 | G EIWALL N2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | iz-G EIWALL N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 49 | iz-G EIWALL N1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | G EIWALL N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 50 | G GFLOOR N2A | Floor | CTF - ConductionTransferFunction | GGFLOORN2A_FFACTOR | 0.170 | 0.163 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 51 | G CEILIN N2A | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | G CEILIN N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 52 | G INTERNALMASS N2A | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 88.25 | 88.25 | 88.25 | 0.00 | 90.00 | 88.25 | 1.00 | 0.00 | G INTERNALMASS N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 53 | G SWALL S1A | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_GRD | 0.752 | 0.676 | 28.24 | 35.30 | 28.24 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 54 | GWINDOW1 S S1A | Window | G SWALL S1A | Window5 Detailed Fenestration | RESWINDOW_U_0.4945_SHGC_0.25 | N/A | 2.811 | No | 7.06 | 7.06 | 7.06 | 180.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 55 | G NIWALL S1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-G NIWALL S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 56 | G EIWALL S1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | iz-G EIWALL S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 57 | iz-G EIWALL SWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | G EIWALL SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 58 | G GFLOOR S1A | Floor | CTF - ConductionTransferFunction | GGFLOORS1A_FFACTOR | 0.170 | 0.163 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 59 | G CEILIN S1A | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | G CEILIN S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 60 | G INTERNALMASS S1A | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 88.25 | 88.25 | 88.25 | 0.00 | 90.00 | 88.25 | 1.00 | 0.00 | G INTERNALMASS S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 61 | G SWALL S2A | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_GRD | 0.752 | 0.676 | 28.24 | 35.30 | 28.24 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 62 | GWINDOW1 S S2A | Window | G SWALL S2A | Window5 Detailed Fenestration | RESWINDOW_U_0.4945_SHGC_0.25 | N/A | 2.811 | No | 7.06 | 7.06 | 7.06 | 180.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 63 | G NIWALL S2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-G NIWALL S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 64 | G EIWALL S2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | iz-G EIWALL S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 65 | iz-G EIWALL S1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | G EIWALL S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 66 | G GFLOOR S2A | Floor | CTF - ConductionTransferFunction | GGFLOORS2A_FFACTOR | 0.170 | 0.163 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 67 | G CEILIN S2A | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | G CEILIN S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 68 | G INTERNALMASS S2A | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 88.25 | 88.25 | 88.25 | 0.00 | 90.00 | 88.25 | 1.00 | 0.00 | G INTERNALMASS S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 69 | M WWALL SWA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.761 | 0.683 | 18.58 | 23.22 | 18.58 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 70 | MWINDOW1 W SWA | Window | M WWALL SWA | Window5 Detailed Fenestration | RESWINDOW_U_0.4945_SHGC_0.25 | N/A | 2.811 | No | 4.65 | 4.65 | 4.65 | 270.00 | 90.00 | 3.81 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 71 | M SWALL SWA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.761 | 0.683 | 28.24 | 35.30 | 28.24 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 72 | MWINDOW1 S SWA | Window | M SWALL SWA | Window5 Detailed Fenestration | RESWINDOW_U_0.4945_SHGC_0.25 | N/A | 2.811 | No | 7.06 | 7.06 | 7.06 | 180.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 73 | M NIWALL SWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-M NIWALL SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 74 | M EIWALL SWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 90.00 | 90.00 | 3.05 | 7.62 | 0.00 | iz-M EIWALL SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 75 | M GFLOOR SWA | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | M GFLOOR SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 76 | M CEILIN SWA | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | M CEILIN SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 77 | M INTERNALMASS SWA | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 176.50 | 176.50 | 176.50 | 0.00 | 90.00 | 176.50 | 1.00 | 0.00 | M INTERNALMASS SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 78 | M NWALL NWA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.761 | 0.683 | 28.24 | 35.30 | 28.24 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 79 | MWINDOW1 N NWA | Window | M NWALL NWA | Window5 Detailed Fenestration | RESWINDOW_U_0.4945_SHGC_0.25 | N/A | 2.811 | No | 7.06 | 7.06 | 7.06 | 0.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 80 | M WWALL NWA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.761 | 0.683 | 18.58 | 23.22 | 18.58 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 81 | MWINDOW1 W NWA | Window | M WWALL NWA | Window5 Detailed Fenestration | RESWINDOW_U_0.4945_SHGC_0.25 | N/A | 2.811 | No | 4.65 | 4.65 | 4.65 | 270.00 | 90.00 | 3.81 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 82 | M SIWALL NWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-M SIWALL NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 83 | M EIWALL NWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | iz-M EIWALL NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 84 | M GFLOOR NWA | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | M GFLOOR NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 85 | M CEILIN NWA | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | M CEILIN NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 86 | M INTERNALMASS NWA | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 176.50 | 176.50 | 176.50 | 0.00 | 90.00 | 176.50 | 1.00 | 0.00 | M INTERNALMASS NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 87 | M EWALL SEA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.761 | 0.683 | 18.58 | 23.22 | 18.58 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 88 | MWINDOW1 E SEA | Window | M EWALL SEA | Window5 Detailed Fenestration | RESWINDOW_U_0.4945_SHGC_0.25 | N/A | 2.811 | No | 4.65 | 4.65 | 4.65 | 90.00 | 90.00 | 3.81 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 89 | M SWALL SEA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.761 | 0.683 | 28.24 | 35.30 | 28.24 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 90 | MWINDOW1 S SEA | Window | M SWALL SEA | Window5 Detailed Fenestration | RESWINDOW_U_0.4945_SHGC_0.25 | N/A | 2.811 | No | 7.06 | 7.06 | 7.06 | 180.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 91 | M NIWALL SEA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-M NIWALL SEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 92 | iz-M EIWALL S2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | M EIWALL S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 93 | M GFLOOR SEA | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | M GFLOOR SEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 94 | M CEILIN SEA | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | M CEILIN SEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 95 | M INTERNALMASS SEA | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 176.50 | 176.50 | 176.50 | 0.00 | 90.00 | 176.50 | 1.00 | 0.00 | M INTERNALMASS SEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 96 | M NWALL NEA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.761 | 0.683 | 28.24 | 35.30 | 28.24 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 97 | MWINDOW1 N NEA | Window | M NWALL NEA | Window5 Detailed Fenestration | RESWINDOW_U_0.4945_SHGC_0.25 | N/A | 2.811 | No | 7.06 | 7.06 | 7.06 | 0.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 98 | M EWALL NEA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.761 | 0.683 | 18.58 | 23.22 | 18.58 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 99 | MWINDOW1 E NEA | Window | M EWALL NEA | Window5 Detailed Fenestration | RESWINDOW_U_0.4945_SHGC_0.25 | N/A | 2.811 | No | 4.65 | 4.65 | 4.65 | 90.00 | 90.00 | 3.81 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 100 | M SIWALL NEA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-M SIWALL NEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 101 | iz-M EIWALL N2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | M EIWALL N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 102 | M GFLOOR NEA | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | M GFLOOR NEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 103 | M CEILIN NEA | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | M CEILIN NEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 104 | M INTERNALMASS NEA | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 176.50 | 176.50 | 176.50 | 0.00 | 90.00 | 176.50 | 1.00 | 0.00 | M INTERNALMASS NEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 105 | M NWALL N1A | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.761 | 0.683 | 28.24 | 35.30 | 28.24 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 106 | MWINDOW1 N N1A | Window | M NWALL N1A | Window5 Detailed Fenestration | RESWINDOW_U_0.4945_SHGC_0.25 | N/A | 2.811 | No | 7.06 | 7.06 | 7.06 | 0.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 107 | M SIWALL N1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-M SIWALL N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 108 | M EIWALL N1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | iz-M EIWALL N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 109 | iz-M EIWALL NWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | M EIWALL NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 110 | M GFLOOR N1A | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | M GFLOOR N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 111 | M CEILIN N1A | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | M CEILIN N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 112 | M INTERNALMASS N1A | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 176.50 | 176.50 | 176.50 | 0.00 | 90.00 | 176.50 | 1.00 | 0.00 | M INTERNALMASS N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 113 | M NWALL N2A | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.761 | 0.683 | 28.24 | 35.30 | 28.24 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 114 | MWINDOW1 N N2A | Window | M NWALL N2A | Window5 Detailed Fenestration | RESWINDOW_U_0.4945_SHGC_0.25 | N/A | 2.811 | No | 7.06 | 7.06 | 7.06 | 0.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 115 | M SIWALL N2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-M SIWALL N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 116 | M EIWALL N2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | iz-M EIWALL N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 117 | iz-M EIWALL N1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | M EIWALL N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 118 | M GFLOOR N2A | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | M GFLOOR N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 119 | M CEILIN N2A | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | M CEILIN N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 120 | M INTERNALMASS N2A | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 176.50 | 176.50 | 176.50 | 0.00 | 90.00 | 176.50 | 1.00 | 0.00 | M INTERNALMASS N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 121 | M SWALL S1A | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.761 | 0.683 | 28.24 | 35.30 | 28.24 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 122 | MWINDOW1 S S1A | Window | M SWALL S1A | Window5 Detailed Fenestration | RESWINDOW_U_0.4945_SHGC_0.25 | N/A | 2.811 | No | 7.06 | 7.06 | 7.06 | 180.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 123 | M NIWALL S1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-M NIWALL S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 124 | M EIWALL S1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | iz-M EIWALL S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 125 | iz-M EIWALL SWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 270.00 | 90.00 | 3.05 | 7.62 | 0.00 | M EIWALL SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 126 | M GFLOOR S1A | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | M GFLOOR S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 127 | M CEILIN S1A | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | M CEILIN S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 128 | M INTERNALMASS S1A | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 176.50 | 176.50 | 176.50 | 0.00 | 90.00 | 176.50 | 1.00 | 0.00 | M INTERNALMASS S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 129 | M SWALL S2A | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.761 | 0.683 | 28.24 | 35.30 | 28.24 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 130 | MWINDOW1 S S2A | Window | M SWALL S2A | Window5 Detailed Fenestration | RESWINDOW_U_0.4945_SHGC_0.25 | N/A | 2.811 | No | 7.06 | 7.06 | 7.06 | 180.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 131 | M NIWALL S2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-M NIWALL S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 132 | M EIWALL S2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | iz-M EIWALL S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 133 | iz-M EIWALL S1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | M EIWALL S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 134 | M GFLOOR S2A | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | M GFLOOR S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 135 | M CEILIN S2A | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | M CEILIN S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 136 | M INTERNALMASS S2A | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 176.50 | 176.50 | 176.50 | 0.00 | 90.00 | 176.50 | 1.00 | 0.00 | M INTERNALMASS S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 137 | T WWALL SWA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.098 | 0.943 | 18.58 | 23.22 | 18.58 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 138 | TWINDOW1 W SWA | Window | T WWALL SWA | Window5 Detailed Fenestration | RESWINDOW_U_0.4945_SHGC_0.25 | N/A | 2.811 | No | 4.65 | 4.65 | 4.65 | 270.00 | 90.00 | 3.81 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 139 | T SWALL SWA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.098 | 0.943 | 28.24 | 35.30 | 28.24 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 140 | TWINDOW1 S SWA | Window | T SWALL SWA | Window5 Detailed Fenestration | RESWINDOW_U_0.4945_SHGC_0.25 | N/A | 2.811 | No | 7.06 | 7.06 | 7.06 | 180.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 141 | T NIWALL SWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-T NIWALL SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 142 | T EIWALL SWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | iz-T EIWALL SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 143 | T GFLOOR SWA | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | T GFLOOR SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 144 | T ROOF SWA | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.283 | 0.269 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 145 | T INTERNALMASS SWA | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 88.25 | 88.25 | 88.25 | 0.00 | 90.00 | 88.25 | 1.00 | 0.00 | T INTERNALMASS SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 146 | T NWALL NWA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.098 | 0.943 | 28.24 | 35.30 | 28.24 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 147 | TWINDOW1 N NWA | Window | T NWALL NWA | Window5 Detailed Fenestration | RESWINDOW_U_0.4945_SHGC_0.25 | N/A | 2.811 | No | 7.06 | 7.06 | 7.06 | 0.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 148 | T WWALL NWA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.098 | 0.943 | 18.58 | 23.22 | 18.58 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 149 | TWINDOW1 W NWA | Window | T WWALL NWA | Window5 Detailed Fenestration | RESWINDOW_U_0.4945_SHGC_0.25 | N/A | 2.811 | No | 4.65 | 4.65 | 4.65 | 270.00 | 90.00 | 3.81 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 150 | T SIWALL NWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-T SIWALL NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 151 | T EIWALL NWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | iz-T EIWALL NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 152 | T GFLOOR NWA | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | T GFLOOR NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 153 | T ROOF NWA | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.283 | 0.269 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 154 | T INTERNALMASS NWA | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 88.25 | 88.25 | 88.25 | 0.00 | 90.00 | 88.25 | 1.00 | 0.00 | T INTERNALMASS NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 155 | T EWALL SEA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.098 | 0.943 | 18.58 | 23.22 | 18.58 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 156 | TWINDOW1 E SEA | Window | T EWALL SEA | Window5 Detailed Fenestration | RESWINDOW_U_0.4945_SHGC_0.25 | N/A | 2.811 | No | 4.65 | 4.65 | 4.65 | 90.00 | 90.00 | 3.81 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 157 | T SWALL SEA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.098 | 0.943 | 28.24 | 35.30 | 28.24 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 158 | TWINDOW1 S SEA | Window | T SWALL SEA | Window5 Detailed Fenestration | RESWINDOW_U_0.4945_SHGC_0.25 | N/A | 2.811 | No | 7.06 | 7.06 | 7.06 | 180.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 159 | T NIWALL SEA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-T NIWALL SEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 160 | iz-T EIWALL S2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | T EIWALL S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 161 | T GFLOOR SEA | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | T GFLOOR SEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 162 | T ROOF SEA | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.283 | 0.269 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 163 | T INTERNALMASS SEA | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 88.25 | 88.25 | 88.25 | 0.00 | 90.00 | 88.25 | 1.00 | 0.00 | T INTERNALMASS SEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 164 | T NWALL NEA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.098 | 0.943 | 28.24 | 35.30 | 28.24 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 165 | TWINDOW1 N NEA | Window | T NWALL NEA | Window5 Detailed Fenestration | RESWINDOW_U_0.4945_SHGC_0.25 | N/A | 2.811 | No | 7.06 | 7.06 | 7.06 | 0.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 166 | T EWALL NEA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.098 | 0.943 | 18.58 | 23.22 | 18.58 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 167 | TWINDOW1 E NEA | Window | T EWALL NEA | Window5 Detailed Fenestration | RESWINDOW_U_0.4945_SHGC_0.25 | N/A | 2.811 | No | 4.65 | 4.65 | 4.65 | 90.00 | 90.00 | 3.81 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 168 | T SIWALL NEA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-T SIWALL NEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 169 | iz-T EIWALL N2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | T EIWALL N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 170 | T GFLOOR NEA | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | T GFLOOR NEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 171 | T ROOF NEA | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.283 | 0.269 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 172 | T INTERNALMASS NEA | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 88.25 | 88.25 | 88.25 | 0.00 | 90.00 | 88.25 | 1.00 | 0.00 | T INTERNALMASS NEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 173 | T NWALL N1A | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.098 | 0.943 | 28.24 | 35.30 | 28.24 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 174 | TWINDOW1 N N1A | Window | T NWALL N1A | Window5 Detailed Fenestration | RESWINDOW_U_0.4945_SHGC_0.25 | N/A | 2.811 | No | 7.06 | 7.06 | 7.06 | 0.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 175 | T SIWALL N1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-T SIWALL N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 176 | T EIWALL N1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | iz-T EIWALL N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 177 | iz-T EIWALL NWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | T EIWALL NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 178 | T GFLOOR N1A | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | T GFLOOR N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 179 | T ROOF N1A | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.283 | 0.269 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 180 | T INTERNALMASS N1A | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 88.25 | 88.25 | 88.25 | 0.00 | 90.00 | 88.25 | 1.00 | 0.00 | T INTERNALMASS N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 181 | T NWALL N2A | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.098 | 0.943 | 28.24 | 35.30 | 28.24 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 182 | TWINDOW1 N N2A | Window | T NWALL N2A | Window5 Detailed Fenestration | RESWINDOW_U_0.4945_SHGC_0.25 | N/A | 2.811 | No | 7.06 | 7.06 | 7.06 | 0.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 183 | T SIWALL N2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-T SIWALL N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 184 | T EIWALL N2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | iz-T EIWALL N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 185 | iz-T EIWALL N1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | T EIWALL N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 186 | T GFLOOR N2A | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | T GFLOOR N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 187 | T ROOF N2A | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.283 | 0.269 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 188 | T INTERNALMASS N2A | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 88.25 | 88.25 | 88.25 | 0.00 | 90.00 | 88.25 | 1.00 | 0.00 | T INTERNALMASS N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 189 | T SWALL S1A | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.098 | 0.943 | 28.24 | 35.30 | 28.24 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 190 | TWINDOW1 S S1A | Window | T SWALL S1A | Window5 Detailed Fenestration | RESWINDOW_U_0.4945_SHGC_0.25 | N/A | 2.811 | No | 7.06 | 7.06 | 7.06 | 180.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 191 | T NIWALL S1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-T NIWALL S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 192 | T EIWALL S1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | iz-T EIWALL S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 193 | iz-T EIWALL SWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | T EIWALL SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 194 | T GFLOOR S1A | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | T GFLOOR S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 195 | T ROOF S1A | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.283 | 0.269 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 196 | T INTERNALMASS S1A | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 88.25 | 88.25 | 88.25 | 0.00 | 90.00 | 88.25 | 1.00 | 0.00 | T INTERNALMASS S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 197 | T SWALL S2A | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.098 | 0.943 | 28.24 | 35.30 | 28.24 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 198 | TWINDOW1 S S2A | Window | T SWALL S2A | Window5 Detailed Fenestration | RESWINDOW_U_0.4945_SHGC_0.25 | N/A | 2.811 | No | 7.06 | 7.06 | 7.06 | 180.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 199 | T NIWALL S2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-T NIWALL S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 200 | T EIWALL S2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | iz-T EIWALL S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 201 | iz-T EIWALL S1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | T EIWALL S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 202 | T GFLOOR S2A | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | T GFLOOR S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 203 | T ROOF S2A | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.283 | 0.269 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 204 | T INTERNALMASS S2A | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 88.25 | 88.25 | 88.25 | 0.00 | 90.00 | 88.25 | 1.00 | 0.00 | T INTERNALMASS S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 205 | T WWALL C | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.098 | 0.943 | 5.11 | 5.11 | 5.11 | 270.00 | 90.00 | 1.68 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 206 | T EWALL C | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.098 | 0.943 | 3.99 | 5.11 | 3.99 | 90.00 | 90.00 | 1.68 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 207 | TWINDOW14 | Window | T EWALL C | Window5 Detailed Fenestration | NONRESWINDOW_U_0.4945_SHGC_0.25 | N/A | 2.811 | No | 1.11 | 1.11 | 1.11 | 90.00 | 90.00 | 0.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 208 | iz-T NIWALL SWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | T NIWALL SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 209 | iz-T NIWALL S1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | T NIWALL S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 210 | iz-T NIWALL S2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | T NIWALL S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 211 | iz-T NIWALL SEA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | T NIWALL SEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 212 | iz-T SIWALL NWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | T SIWALL NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 213 | iz-T SIWALL N1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | T SIWALL N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 214 | iz-T SIWALL N2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | T SIWALL N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 215 | iz-T SIWALL NEA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | T SIWALL NEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 216 | T FLOOR C | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 77.66 | 77.66 | 77.66 | 90.00 | 180.00 | 1.68 | 46.33 | 0.00 | T FLOOR C | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 217 | T ROOF C | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 77.66 | 77.66 | 77.66 | 180.00 | 0.00 | 46.33 | 1.68 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 218 | G WWALL C | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.752 | 0.676 | 5.11 | 5.11 | 5.11 | 270.00 | 90.00 | 1.68 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 219 | G EWALL C | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.752 | 0.676 | 1.79 | 5.11 | 1.79 | 90.00 | 90.00 | 1.68 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 220 | ENTRANCE DOOR | Window | G EWALL C | Window5 Detailed Fenestration | NONRESWINDOW_U_0.4945_SHGC_0.25 | N/A | 2.811 | No | 3.32 | 3.32 | 3.32 | 90.00 | 90.00 | 1.57 | 2.11 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 221 | iz-G NIWALL SWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | G NIWALL SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 222 | iz-G NIWALL S1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | G NIWALL S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 223 | iz-G NIWALL S2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | G NIWALL S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 224 | iz-G NIWALL SEA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | G NIWALL SEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 225 | iz-G SIWALL NWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | G SIWALL NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 226 | iz-G SIWALL N1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | G SIWALL N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 227 | iz-G SIWALL N2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | G SIWALL N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 228 | iz-G SIWALL NEA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | G SIWALL NEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 229 | G FLOOR C | Floor | CTF - ConductionTransferFunction | GFLOORC_FFACTOR | 5.502E-002 | 5.429E-002 | 77.66 | 77.66 | 77.66 | 90.00 | 180.00 | 1.68 | 46.33 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 230 | G CEILING C | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 77.66 | 77.66 | 77.66 | 180.00 | 0.00 | 46.33 | 1.68 | 0.00 | G CEILING C | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 231 | M WWALL C | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.761 | 0.683 | 5.11 | 5.11 | 5.11 | 270.00 | 90.00 | 1.68 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 232 | M EWALL C | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.761 | 0.683 | 3.99 | 5.11 | 3.99 | 90.00 | 90.00 | 1.68 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 233 | MWINDOW14 | Window | M EWALL C | Window5 Detailed Fenestration | NONRESWINDOW_U_0.4945_SHGC_0.25 | N/A | 2.811 | No | 1.11 | 1.11 | 1.11 | 90.00 | 90.00 | 0.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 234 | iz-M NIWALL SWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | M NIWALL SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 235 | iz-M NIWALL S1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | M NIWALL S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 236 | iz-M NIWALL S2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | M NIWALL S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 237 | iz-M NIWALL SEA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | M NIWALL SEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 238 | iz-M SIWALL NWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | M SIWALL NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 239 | iz-M SIWALL N1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | M SIWALL N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 240 | iz-M SIWALL N2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | M SIWALL N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 241 | iz-M SIWALL NEA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | M SIWALL NEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 242 | M FLOOR C | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 77.66 | 77.66 | 77.66 | 90.00 | 180.00 | 1.68 | 46.33 | 0.00 | M FLOOR C | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 243 | M CEILING C | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 77.66 | 77.66 | 77.66 | 180.00 | 0.00 | 46.33 | 1.68 | 0.00 | M CEILING C | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
| Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
| 1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | Yes | Yes | Yes | Clark and Allen |
| Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
| 1 | NEW YEAR'S DAY | Holiday | InputFile | 01/02 | 1Environment:Special Days |
| Daylight Saving Indicator | Source | Start Date | End Date | |
| 1 | Yes | InputFile | 03/12 | 11/05 |
| Style | Unit Conversion | |
| 1 | Commaandhtml | commaandhtml |
| Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
| 1 | G SW APARTMENT | RunPeriod: RUNPERIOD 1 | 1.5929798962E-002 | 1.8654135966E-002 | Pass | Pass | 3.4528407961E-002 | 7.0993376999E-002 | Pass | Pass |
| 2 | G NW APARTMENT | RunPeriod: RUNPERIOD 1 | 9.7264698524E-003 | 1.7330672674E-002 | Pass | Pass | 0.3598687351 | 0.7300265881 | Pass | Pass |
| 3 | OFFICE | RunPeriod: RUNPERIOD 1 | 2.6451401604E-002 | 2.7663144121E-002 | Pass | Pass | 0.2141327657 | 0.5360616428 | Pass | Pass |
| 4 | G NE APARTMENT | RunPeriod: RUNPERIOD 1 | 6.4120933667E-003 | 1.0271695892E-002 | Pass | Pass | 0.2595602270 | 1.1333736334 | Pass | Pass |
| 5 | G N1 APARTMENT | RunPeriod: RUNPERIOD 1 | 7.1368377249E-003 | 1.0851604517E-002 | Pass | Pass | 2.4647914478E-002 | 5.0386275281E-002 | Pass | Pass |
| 6 | G N2 APARTMENT | RunPeriod: RUNPERIOD 1 | 7.3995194059E-003 | 1.1152276187E-002 | Pass | Pass | 2.4251743597E-002 | 4.9436235761E-002 | Pass | Pass |
| 7 | G S1 APARTMENT | RunPeriod: RUNPERIOD 1 | 2.2057078347E-002 | 2.0338933618E-002 | Pass | Pass | 7.1841662253E-003 | 8.6130692627E-003 | Pass | Pass |
| 8 | G S2 APARTMENT | RunPeriod: RUNPERIOD 1 | 2.2302016655E-002 | 2.0560491825E-002 | Pass | Pass | 7.2296418335E-003 | 8.6439392958E-003 | Pass | Pass |
| 9 | M SW APARTMENT | RunPeriod: RUNPERIOD 1 | 2.8659305152E-002 | 2.6284629107E-002 | Pass | Pass | 7.3472451821E-003 | 8.3143815506E-003 | Pass | Pass |
| 10 | M NW APARTMENT | RunPeriod: RUNPERIOD 1 | 1.0490365110E-002 | 1.4751306587E-002 | Pass | Pass | 6.6950204963E-002 | 0.1516168019 | Pass | Pass |
| 11 | M SE APARTMENT | RunPeriod: RUNPERIOD 1 | 3.1488120196E-002 | 3.5375741719E-002 | Pass | Pass | 7.0056282312E-003 | 7.9598385313E-003 | Pass | Pass |
| 12 | M NE APARTMENT | RunPeriod: RUNPERIOD 1 | 1.4435925448E-002 | 1.9871628960E-002 | Pass | Pass | 3.5173343561E-002 | 6.9954750175E-002 | Pass | Pass |
| 13 | M N1 APARTMENT | RunPeriod: RUNPERIOD 1 | 1.6685964521E-002 | 1.4762979321E-002 | Pass | Pass | 7.7687835767E-003 | 9.7938360108E-003 | Pass | Pass |
| 14 | M N2 APARTMENT | RunPeriod: RUNPERIOD 1 | 1.6757626885E-002 | 1.4791719938E-002 | Pass | Pass | 7.7319863297E-003 | 9.7438065706E-003 | Pass | Pass |
| 15 | M S1 APARTMENT | RunPeriod: RUNPERIOD 1 | 2.4548745829E-002 | 2.3749911857E-002 | Pass | Pass | 6.6264470975E-003 | 7.7585475883E-003 | Pass | Pass |
| 16 | M S2 APARTMENT | RunPeriod: RUNPERIOD 1 | 2.4594356739E-002 | 2.3848950131E-002 | Pass | Pass | 6.5894077997E-003 | 7.7136558431E-003 | Pass | Pass |
| 17 | T SW APARTMENT | RunPeriod: RUNPERIOD 1 | 1.6895076215E-002 | 2.3885503599E-002 | Pass | Pass | 0.1461511796 | 0.8683191064 | Pass | Pass |
| 18 | T NW APARTMENT | RunPeriod: RUNPERIOD 1 | 2.7304002518E-002 | 4.3744160431E-002 | Pass | Pass | 1.0912631071 | 4.7621593246 | Pass | Pass |
| 19 | T SE APARTMENT | RunPeriod: RUNPERIOD 1 | 2.2830395270E-002 | 3.2875107685E-002 | Pass | Pass | 0.3239775759 | 2.5643101905 | Pass | Pass |
| 20 | T NE APARTMENT | RunPeriod: RUNPERIOD 1 | 2.4926058999E-002 | 3.9735354925E-002 | Pass | Pass | 2.0901150543 | 7.5577004669 | Pass | Pass |
| 21 | T N1 APARTMENT | RunPeriod: RUNPERIOD 1 | 7.7076593964E-003 | 1.3412861917E-002 | Pass | Pass | 0.3606954543 | 0.8166556006 | Pass | Pass |
| 22 | T N2 APARTMENT | RunPeriod: RUNPERIOD 1 | 7.0939460611E-003 | 1.2419622798E-002 | Pass | Pass | 1.0257865495 | 8.1974048482 | Pass | Pass |
| 23 | T S1 APARTMENT | RunPeriod: RUNPERIOD 1 | 2.2560726659E-002 | 3.0126014200E-002 | Pass | Pass | 0.1517637410 | 0.6613761092 | Pass | Pass |
| 24 | T S2 APARTMENT | RunPeriod: RUNPERIOD 1 | 2.3061182696E-002 | 3.0787660279E-002 | Pass | Pass | 0.3251380585 | 2.7081686009 | Pass | Pass |
| 25 | T CORRIDOR | RunPeriod: RUNPERIOD 1 | 1.5398777915E-002 | 1.1195394964E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
| 26 | G CORRIDOR | RunPeriod: RUNPERIOD 1 | 0.1316425434 | 0.4227989295 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
| 27 | M CORRIDOR | RunPeriod: RUNPERIOD 1 | 7.7360503983E-003 | 5.9559187466E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 09:15:25
Heat Emission by Components| Envelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
| Heat Emissions [GJ] | 1759.11 | 125.72 | 0.00 | 11.71 | 417.98 | 2314.53 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 09:15:25
SizingPeriod:DesignDay| Maximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
| SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 3.80 | 0.00 | 3.80 | Wetbulb [C] | 3.00 | 120.00 |
| SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 31.30 | 8.90 | 18.40 | Wetbulb [C] | 4.10 | 280.00 |
| Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
| Jan | 2.00 | 2 | |||
| Feb | 59.00 | 53 | |||
| Mar | 58.58 | 43 | |||
| Apr | 46.42 | 14 | |||
| May | 18.00 | 12 | |||
| Jun | 0.00 | 0 | |||
| Jul | 0.00 | 0 | |||
| Aug | 0.00 | 0 | |||
| Sep | 3.00 | 6 | |||
| Oct | 0.00 | 0 | |||
| Nov | 18.00 | 12 | |||
| Dec | 4.00 | 4 |
| Value | |
| None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 09:15:25
Opaque Exterior| Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
| G SWALL SWA | RES_EXT_WALL_GRD | 0.30 | 0.676 | 0.752 | 35.30 | 28.24 | 180.00 | 90.00 | S |
| G WWALL SWA | RES_EXT_WALL_GRD | 0.30 | 0.676 | 0.752 | 23.22 | 18.58 | 270.00 | 90.00 | W |
| G GFLOOR SWA | GGFLOORSWA_FFACTOR | 1.00 | 0.274 | 0.287 | 88.25 | 88.25 | 90.00 | 180.00 | |
| G NWALL NWA | RES_EXT_WALL_GRD | 0.30 | 0.676 | 0.752 | 35.30 | 28.24 | 0.00 | 90.00 | N |
| G WWALL NWA | RES_EXT_WALL_GRD | 0.30 | 0.676 | 0.752 | 23.22 | 18.58 | 270.00 | 90.00 | W |
| G GFLOOR NWA | GGFLOORNWA_FFACTOR | 1.00 | 0.274 | 0.287 | 88.25 | 88.25 | 90.00 | 180.00 | |
| G SWALL SEA | NONRES_EXT_WALL_GRD | 0.30 | 0.676 | 0.752 | 35.30 | 28.24 | 180.00 | 90.00 | S |
| G EWALL SEA | NONRES_EXT_WALL_GRD | 0.30 | 0.676 | 0.752 | 23.22 | 18.58 | 90.00 | 90.00 | E |
| G GFLOOR SEA | GGFLOORSEA_FFACTOR | 1.00 | 0.274 | 0.287 | 88.25 | 88.25 | 90.00 | 180.00 | |
| G NWALL NEA | RES_EXT_WALL_GRD | 0.30 | 0.676 | 0.752 | 35.30 | 28.24 | 0.00 | 90.00 | N |
| G EWALL NEA | RES_EXT_WALL_GRD | 0.30 | 0.676 | 0.752 | 23.22 | 18.58 | 90.00 | 90.00 | E |
| G GFLOOR NEA | GGFLOORNEA_FFACTOR | 1.00 | 0.274 | 0.287 | 88.25 | 88.25 | 90.00 | 180.00 | |
| G NWALL N1A | RES_EXT_WALL_GRD | 0.30 | 0.676 | 0.752 | 35.30 | 28.24 | 0.00 | 90.00 | N |
| G GFLOOR N1A | GGFLOORN1A_FFACTOR | 1.00 | 0.166 | 0.170 | 88.25 | 88.25 | 90.00 | 180.00 | |
| G NWALL N2A | RES_EXT_WALL_GRD | 0.30 | 0.676 | 0.752 | 35.30 | 28.24 | 0.00 | 90.00 | N |
| G GFLOOR N2A | GGFLOORN2A_FFACTOR | 1.00 | 0.166 | 0.170 | 88.25 | 88.25 | 90.00 | 180.00 | |
| G SWALL S1A | RES_EXT_WALL_GRD | 0.30 | 0.676 | 0.752 | 35.30 | 28.24 | 180.00 | 90.00 | S |
| G GFLOOR S1A | GGFLOORS1A_FFACTOR | 1.00 | 0.166 | 0.170 | 88.25 | 88.25 | 90.00 | 180.00 | |
| G SWALL S2A | RES_EXT_WALL_GRD | 0.30 | 0.676 | 0.752 | 35.30 | 28.24 | 180.00 | 90.00 | S |
| G GFLOOR S2A | GGFLOORS2A_FFACTOR | 1.00 | 0.166 | 0.170 | 88.25 | 88.25 | 90.00 | 180.00 | |
| M WWALL SWA | RES_EXT_WALL_MID | 0.30 | 0.683 | 0.761 | 46.45 | 37.16 | 270.00 | 90.00 | W |
| M SWALL SWA | RES_EXT_WALL_MID | 0.30 | 0.683 | 0.761 | 70.60 | 56.48 | 180.00 | 90.00 | S |
| M NWALL NWA | RES_EXT_WALL_MID | 0.30 | 0.683 | 0.761 | 70.60 | 56.48 | 0.00 | 90.00 | N |
| M WWALL NWA | RES_EXT_WALL_MID | 0.30 | 0.683 | 0.761 | 46.45 | 37.16 | 270.00 | 90.00 | W |
| M EWALL SEA | RES_EXT_WALL_MID | 0.30 | 0.683 | 0.761 | 46.45 | 37.16 | 90.00 | 90.00 | E |
| M SWALL SEA | RES_EXT_WALL_MID | 0.30 | 0.683 | 0.761 | 70.60 | 56.48 | 180.00 | 90.00 | S |
| M NWALL NEA | RES_EXT_WALL_MID | 0.30 | 0.683 | 0.761 | 70.60 | 56.48 | 0.00 | 90.00 | N |
| M EWALL NEA | RES_EXT_WALL_MID | 0.30 | 0.683 | 0.761 | 46.45 | 37.16 | 90.00 | 90.00 | E |
| M NWALL N1A | RES_EXT_WALL_MID | 0.30 | 0.683 | 0.761 | 70.60 | 56.48 | 0.00 | 90.00 | N |
| M NWALL N2A | RES_EXT_WALL_MID | 0.30 | 0.683 | 0.761 | 70.60 | 56.48 | 0.00 | 90.00 | N |
| M SWALL S1A | RES_EXT_WALL_MID | 0.30 | 0.683 | 0.761 | 70.60 | 56.48 | 180.00 | 90.00 | S |
| M SWALL S2A | RES_EXT_WALL_MID | 0.30 | 0.683 | 0.761 | 70.60 | 56.48 | 180.00 | 90.00 | S |
| T WWALL SWA | RES_EXT_WALL_TOP | 0.30 | 0.943 | 1.098 | 23.22 | 18.58 | 270.00 | 90.00 | W |
| T SWALL SWA | RES_EXT_WALL_TOP | 0.30 | 0.943 | 1.098 | 35.30 | 28.24 | 180.00 | 90.00 | S |
| T ROOF SWA | RES_ROOF | 0.55 | 0.273 | 0.283 | 88.25 | 88.25 | 180.00 | 0.00 | |
| T NWALL NWA | RES_EXT_WALL_TOP | 0.30 | 0.943 | 1.098 | 35.30 | 28.24 | 0.00 | 90.00 | N |
| T WWALL NWA | RES_EXT_WALL_TOP | 0.30 | 0.943 | 1.098 | 23.22 | 18.58 | 270.00 | 90.00 | W |
| T ROOF NWA | RES_ROOF | 0.55 | 0.273 | 0.283 | 88.25 | 88.25 | 180.00 | 0.00 | |
| T EWALL SEA | RES_EXT_WALL_TOP | 0.30 | 0.943 | 1.098 | 23.22 | 18.58 | 90.00 | 90.00 | E |
| T SWALL SEA | RES_EXT_WALL_TOP | 0.30 | 0.943 | 1.098 | 35.30 | 28.24 | 180.00 | 90.00 | S |
| T ROOF SEA | RES_ROOF | 0.55 | 0.273 | 0.283 | 88.25 | 88.25 | 180.00 | 0.00 | |
| T NWALL NEA | RES_EXT_WALL_TOP | 0.30 | 0.943 | 1.098 | 35.30 | 28.24 | 0.00 | 90.00 | N |
| T EWALL NEA | RES_EXT_WALL_TOP | 0.30 | 0.943 | 1.098 | 23.22 | 18.58 | 90.00 | 90.00 | E |
| T ROOF NEA | RES_ROOF | 0.55 | 0.273 | 0.283 | 88.25 | 88.25 | 180.00 | 0.00 | |
| T NWALL N1A | RES_EXT_WALL_TOP | 0.30 | 0.943 | 1.098 | 35.30 | 28.24 | 0.00 | 90.00 | N |
| T ROOF N1A | RES_ROOF | 0.55 | 0.273 | 0.283 | 88.25 | 88.25 | 180.00 | 0.00 | |
| T NWALL N2A | RES_EXT_WALL_TOP | 0.30 | 0.943 | 1.098 | 35.30 | 28.24 | 0.00 | 90.00 | N |
| T ROOF N2A | RES_ROOF | 0.55 | 0.273 | 0.283 | 88.25 | 88.25 | 180.00 | 0.00 | |
| T SWALL S1A | RES_EXT_WALL_TOP | 0.30 | 0.943 | 1.098 | 35.30 | 28.24 | 180.00 | 90.00 | S |
| T ROOF S1A | RES_ROOF | 0.55 | 0.273 | 0.283 | 88.25 | 88.25 | 180.00 | 0.00 | |
| T SWALL S2A | RES_EXT_WALL_TOP | 0.30 | 0.943 | 1.098 | 35.30 | 28.24 | 180.00 | 90.00 | S |
| T ROOF S2A | RES_ROOF | 0.55 | 0.273 | 0.283 | 88.25 | 88.25 | 180.00 | 0.00 | |
| T WWALL C | NONRES_EXT_WALL_TOP | 0.30 | 0.943 | 1.098 | 5.11 | 5.11 | 270.00 | 90.00 | W |
| T EWALL C | NONRES_EXT_WALL_TOP | 0.30 | 0.943 | 1.098 | 5.11 | 3.99 | 90.00 | 90.00 | E |
| T ROOF C | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 77.66 | 77.66 | 180.00 | 0.00 | |
| G WWALL C | NONRES_EXT_WALL_GRD | 0.30 | 0.676 | 0.752 | 5.11 | 5.11 | 270.00 | 90.00 | W |
| G EWALL C | NONRES_EXT_WALL_GRD | 0.30 | 0.676 | 0.752 | 5.11 | 1.79 | 90.00 | 90.00 | E |
| G FLOOR C | GFLOORC_FFACTOR | 1.00 | 0.055 | 0.055 | 77.66 | 77.66 | 90.00 | 180.00 | |
| M WWALL C | NONRES_EXT_WALL_MID | 0.30 | 0.683 | 0.761 | 10.22 | 10.22 | 270.00 | 90.00 | W |
| M EWALL C | NONRES_EXT_WALL_MID | 0.30 | 0.683 | 0.761 | 10.22 | 7.99 | 90.00 | 90.00 | E |
| Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
| G NIWALL SWA | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 0.00 | 90.00 | N |
| G EIWALL SWA | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 90.00 | 90.00 | E |
| G CEILIN SWA | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 88.25 | 88.25 | 180.00 | 0.00 | |
| G SIWALL NWA | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 180.00 | 90.00 | S |
| G EIWALL NWA | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 90.00 | 90.00 | E |
| G CEILIN NWA | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 88.25 | 88.25 | 180.00 | 0.00 | |
| G NIWALL SEA | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 0.00 | 90.00 | N |
| iz-G EIWALL S2A | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 270.00 | 90.00 | W |
| G CEILIN SEA | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 88.25 | 88.25 | 180.00 | 0.00 | |
| G SIWALL NEA | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 180.00 | 90.00 | S |
| iz-G EIWALL N2A | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 270.00 | 90.00 | W |
| G CEILIN NEA | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 88.25 | 88.25 | 180.00 | 0.00 | |
| G SIWALL N1A | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 180.00 | 90.00 | S |
| G EIWALL N1A | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 90.00 | 90.00 | E |
| iz-G EIWALL NWA | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 270.00 | 90.00 | W |
| G CEILIN N1A | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 88.25 | 88.25 | 180.00 | 0.00 | |
| G SIWALL N2A | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 180.00 | 90.00 | S |
| G EIWALL N2A | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 90.00 | 90.00 | E |
| iz-G EIWALL N1A | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 270.00 | 90.00 | W |
| G CEILIN N2A | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 88.25 | 88.25 | 180.00 | 0.00 | |
| G NIWALL S1A | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 0.00 | 90.00 | N |
| G EIWALL S1A | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 90.00 | 90.00 | E |
| iz-G EIWALL SWA | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 270.00 | 90.00 | W |
| G CEILIN S1A | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 88.25 | 88.25 | 180.00 | 0.00 | |
| G NIWALL S2A | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 0.00 | 90.00 | N |
| G EIWALL S2A | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 90.00 | 90.00 | E |
| iz-G EIWALL S1A | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 270.00 | 90.00 | W |
| G CEILIN S2A | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 88.25 | 88.25 | 180.00 | 0.00 | |
| M NIWALL SWA | INT_WALL | 0.30 | 2.511 | 6.299 | 70.60 | 70.60 | 0.00 | 90.00 | N |
| M EIWALL SWA | INT_WALL | 0.30 | 2.511 | 6.299 | 46.45 | 46.45 | 90.00 | 90.00 | E |
| M GFLOOR SWA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 176.50 | 176.50 | 90.00 | 180.00 | |
| M CEILIN SWA | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 176.50 | 176.50 | 180.00 | 0.00 | |
| M SIWALL NWA | INT_WALL | 0.30 | 2.511 | 6.299 | 70.60 | 70.60 | 180.00 | 90.00 | S |
| M EIWALL NWA | INT_WALL | 0.30 | 2.511 | 6.299 | 46.45 | 46.45 | 90.00 | 90.00 | E |
| M GFLOOR NWA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 176.50 | 176.50 | 90.00 | 180.00 | |
| M CEILIN NWA | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 176.50 | 176.50 | 180.00 | 0.00 | |
| M NIWALL SEA | INT_WALL | 0.30 | 2.511 | 6.299 | 70.60 | 70.60 | 0.00 | 90.00 | N |
| iz-M EIWALL S2A | INT_WALL | 0.30 | 2.511 | 6.299 | 46.45 | 46.45 | 270.00 | 90.00 | W |
| M GFLOOR SEA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 176.50 | 176.50 | 90.00 | 180.00 | |
| M CEILIN SEA | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 176.50 | 176.50 | 180.00 | 0.00 | |
| M SIWALL NEA | INT_WALL | 0.30 | 2.511 | 6.299 | 70.60 | 70.60 | 180.00 | 90.00 | S |
| iz-M EIWALL N2A | INT_WALL | 0.30 | 2.511 | 6.299 | 46.45 | 46.45 | 270.00 | 90.00 | W |
| M GFLOOR NEA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 176.50 | 176.50 | 90.00 | 180.00 | |
| M CEILIN NEA | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 176.50 | 176.50 | 180.00 | 0.00 | |
| M SIWALL N1A | INT_WALL | 0.30 | 2.511 | 6.299 | 70.60 | 70.60 | 180.00 | 90.00 | S |
| M EIWALL N1A | INT_WALL | 0.30 | 2.511 | 6.299 | 46.45 | 46.45 | 90.00 | 90.00 | E |
| iz-M EIWALL NWA | INT_WALL | 0.30 | 2.511 | 6.299 | 46.45 | 46.45 | 270.00 | 90.00 | W |
| M GFLOOR N1A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 176.50 | 176.50 | 90.00 | 180.00 | |
| M CEILIN N1A | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 176.50 | 176.50 | 180.00 | 0.00 | |
| M SIWALL N2A | INT_WALL | 0.30 | 2.511 | 6.299 | 70.60 | 70.60 | 180.00 | 90.00 | S |
| M EIWALL N2A | INT_WALL | 0.30 | 2.511 | 6.299 | 46.45 | 46.45 | 90.00 | 90.00 | E |
| iz-M EIWALL N1A | INT_WALL | 0.30 | 2.511 | 6.299 | 46.45 | 46.45 | 270.00 | 90.00 | W |
| M GFLOOR N2A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 176.50 | 176.50 | 90.00 | 180.00 | |
| M CEILIN N2A | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 176.50 | 176.50 | 180.00 | 0.00 | |
| M NIWALL S1A | INT_WALL | 0.30 | 2.511 | 6.299 | 70.60 | 70.60 | 0.00 | 90.00 | N |
| M EIWALL S1A | INT_WALL | 0.30 | 2.511 | 6.299 | 46.45 | 46.45 | 90.00 | 90.00 | E |
| iz-M EIWALL SWA | INT_WALL | 0.30 | 2.511 | 6.299 | 46.45 | 46.45 | 270.00 | 90.00 | W |
| M GFLOOR S1A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 176.50 | 176.50 | 90.00 | 180.00 | |
| M CEILIN S1A | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 176.50 | 176.50 | 180.00 | 0.00 | |
| M NIWALL S2A | INT_WALL | 0.30 | 2.511 | 6.299 | 70.60 | 70.60 | 0.00 | 90.00 | N |
| M EIWALL S2A | INT_WALL | 0.30 | 2.511 | 6.299 | 46.45 | 46.45 | 90.00 | 90.00 | E |
| iz-M EIWALL S1A | INT_WALL | 0.30 | 2.511 | 6.299 | 46.45 | 46.45 | 270.00 | 90.00 | W |
| M GFLOOR S2A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 176.50 | 176.50 | 90.00 | 180.00 | |
| M CEILIN S2A | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 176.50 | 176.50 | 180.00 | 0.00 | |
| T NIWALL SWA | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 0.00 | 90.00 | N |
| T EIWALL SWA | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 90.00 | 90.00 | E |
| T GFLOOR SWA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 88.25 | 88.25 | 90.00 | 180.00 | |
| T SIWALL NWA | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 180.00 | 90.00 | S |
| T EIWALL NWA | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 90.00 | 90.00 | E |
| T GFLOOR NWA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 88.25 | 88.25 | 90.00 | 180.00 | |
| T NIWALL SEA | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 0.00 | 90.00 | N |
| iz-T EIWALL S2A | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 270.00 | 90.00 | W |
| T GFLOOR SEA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 88.25 | 88.25 | 90.00 | 180.00 | |
| T SIWALL NEA | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 180.00 | 90.00 | S |
| iz-T EIWALL N2A | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 270.00 | 90.00 | W |
| T GFLOOR NEA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 88.25 | 88.25 | 90.00 | 180.00 | |
| T SIWALL N1A | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 180.00 | 90.00 | S |
| T EIWALL N1A | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 90.00 | 90.00 | E |
| iz-T EIWALL NWA | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 270.00 | 90.00 | W |
| T GFLOOR N1A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 88.25 | 88.25 | 90.00 | 180.00 | |
| T SIWALL N2A | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 180.00 | 90.00 | S |
| T EIWALL N2A | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 90.00 | 90.00 | E |
| iz-T EIWALL N1A | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 270.00 | 90.00 | W |
| T GFLOOR N2A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 88.25 | 88.25 | 90.00 | 180.00 | |
| T NIWALL S1A | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 0.00 | 90.00 | N |
| T EIWALL S1A | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 90.00 | 90.00 | E |
| iz-T EIWALL SWA | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 270.00 | 90.00 | W |
| T GFLOOR S1A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 88.25 | 88.25 | 90.00 | 180.00 | |
| T NIWALL S2A | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 0.00 | 90.00 | N |
| T EIWALL S2A | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 90.00 | 90.00 | E |
| iz-T EIWALL S1A | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 270.00 | 90.00 | W |
| T GFLOOR S2A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 88.25 | 88.25 | 90.00 | 180.00 | |
| iz-T NIWALL SWA | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 180.00 | 90.00 | S |
| iz-T NIWALL S1A | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 180.00 | 90.00 | S |
| iz-T NIWALL S2A | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 180.00 | 90.00 | S |
| iz-T NIWALL SEA | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 180.00 | 90.00 | S |
| iz-T SIWALL NWA | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 0.00 | 90.00 | N |
| iz-T SIWALL N1A | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 0.00 | 90.00 | N |
| iz-T SIWALL N2A | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 0.00 | 90.00 | N |
| iz-T SIWALL NEA | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 0.00 | 90.00 | N |
| T FLOOR C | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 77.66 | 77.66 | 90.00 | 180.00 | |
| iz-G NIWALL SWA | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 180.00 | 90.00 | S |
| iz-G NIWALL S1A | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 180.00 | 90.00 | S |
| iz-G NIWALL S2A | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 180.00 | 90.00 | S |
| iz-G NIWALL SEA | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 180.00 | 90.00 | S |
| iz-G SIWALL NWA | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 0.00 | 90.00 | N |
| iz-G SIWALL N1A | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 0.00 | 90.00 | N |
| iz-G SIWALL N2A | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 0.00 | 90.00 | N |
| iz-G SIWALL NEA | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 0.00 | 90.00 | N |
| G CEILING C | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 77.66 | 77.66 | 180.00 | 0.00 | |
| iz-M NIWALL SWA | INT_WALL | 0.30 | 2.511 | 6.299 | 70.60 | 70.60 | 180.00 | 90.00 | S |
| iz-M NIWALL S1A | INT_WALL | 0.30 | 2.511 | 6.299 | 70.60 | 70.60 | 180.00 | 90.00 | S |
| iz-M NIWALL S2A | INT_WALL | 0.30 | 2.511 | 6.299 | 70.60 | 70.60 | 180.00 | 90.00 | S |
| iz-M NIWALL SEA | INT_WALL | 0.30 | 2.511 | 6.299 | 70.60 | 70.60 | 180.00 | 90.00 | S |
| iz-M SIWALL NWA | INT_WALL | 0.30 | 2.511 | 6.299 | 70.60 | 70.60 | 0.00 | 90.00 | N |
| iz-M SIWALL N1A | INT_WALL | 0.30 | 2.511 | 6.299 | 70.60 | 70.60 | 0.00 | 90.00 | N |
| iz-M SIWALL N2A | INT_WALL | 0.30 | 2.511 | 6.299 | 70.60 | 70.60 | 0.00 | 90.00 | N |
| iz-M SIWALL NEA | INT_WALL | 0.30 | 2.511 | 6.299 | 70.60 | 70.60 | 0.00 | 90.00 | N |
| M FLOOR C | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 155.32 | 155.32 | 90.00 | 180.00 | |
| M CEILING C | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 155.32 | 155.32 | 180.00 | 0.00 | |
| G INTERNALMASS SWA | INTERIORFURNISHINGS | 0.30 | 0.800 | 88.25 | 0.00 | 90.00 | N | ||
| G INTERNALMASS NWA | INTERIORFURNISHINGS | 0.30 | 0.800 | 88.25 | 0.00 | 90.00 | N | ||
| G INTERNALMASS SEA | INTERIORFURNISHINGS | 0.30 | 0.800 | 88.25 | 0.00 | 90.00 | N | ||
| G INTERNALMASS NEA | INTERIORFURNISHINGS | 0.30 | 0.800 | 88.25 | 0.00 | 90.00 | N | ||
| G INTERNALMASS N1A | INTERIORFURNISHINGS | 0.30 | 0.800 | 88.25 | 0.00 | 90.00 | N | ||
| G INTERNALMASS N2A | INTERIORFURNISHINGS | 0.30 | 0.800 | 88.25 | 0.00 | 90.00 | N | ||
| G INTERNALMASS S1A | INTERIORFURNISHINGS | 0.30 | 0.800 | 88.25 | 0.00 | 90.00 | N | ||
| G INTERNALMASS S2A | INTERIORFURNISHINGS | 0.30 | 0.800 | 88.25 | 0.00 | 90.00 | N | ||
| M INTERNALMASS SWA | INTERIORFURNISHINGS | 0.30 | 0.800 | 353.00 | 0.00 | 90.00 | N | ||
| M INTERNALMASS NWA | INTERIORFURNISHINGS | 0.30 | 0.800 | 353.00 | 0.00 | 90.00 | N | ||
| M INTERNALMASS SEA | INTERIORFURNISHINGS | 0.30 | 0.800 | 353.00 | 0.00 | 90.00 | N | ||
| M INTERNALMASS NEA | INTERIORFURNISHINGS | 0.30 | 0.800 | 353.00 | 0.00 | 90.00 | N | ||
| M INTERNALMASS N1A | INTERIORFURNISHINGS | 0.30 | 0.800 | 353.00 | 0.00 | 90.00 | N | ||
| M INTERNALMASS N2A | INTERIORFURNISHINGS | 0.30 | 0.800 | 353.00 | 0.00 | 90.00 | N | ||
| M INTERNALMASS S1A | INTERIORFURNISHINGS | 0.30 | 0.800 | 353.00 | 0.00 | 90.00 | N | ||
| M INTERNALMASS S2A | INTERIORFURNISHINGS | 0.30 | 0.800 | 353.00 | 0.00 | 90.00 | N | ||
| T INTERNALMASS SWA | INTERIORFURNISHINGS | 0.30 | 0.800 | 88.25 | 0.00 | 90.00 | N | ||
| T INTERNALMASS NWA | INTERIORFURNISHINGS | 0.30 | 0.800 | 88.25 | 0.00 | 90.00 | N | ||
| T INTERNALMASS SEA | INTERIORFURNISHINGS | 0.30 | 0.800 | 88.25 | 0.00 | 90.00 | N | ||
| T INTERNALMASS NEA | INTERIORFURNISHINGS | 0.30 | 0.800 | 88.25 | 0.00 | 90.00 | N | ||
| T INTERNALMASS N1A | INTERIORFURNISHINGS | 0.30 | 0.800 | 88.25 | 0.00 | 90.00 | N | ||
| T INTERNALMASS N2A | INTERIORFURNISHINGS | 0.30 | 0.800 | 88.25 | 0.00 | 90.00 | N | ||
| T INTERNALMASS S1A | INTERIORFURNISHINGS | 0.30 | 0.800 | 88.25 | 0.00 | 90.00 | N | ||
| T INTERNALMASS S2A | INTERIORFURNISHINGS | 0.30 | 0.800 | 88.25 | 0.00 | 90.00 | N |
| Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
| GWINDOW1 S SWA | RESWINDOW_U_0.4945_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.811 | 0.251 | 0.251 | No | G SWALL SWA | 180.00 | 90.00 | S | |||||||
| GWINDOW1 W SWA | RESWINDOW_U_0.4945_SHGC_0.25 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 2.811 | 0.251 | 0.251 | No | G WWALL SWA | 270.00 | 90.00 | W | |||||||
| GWINDOW1 N NWA | RESWINDOW_U_0.4945_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.811 | 0.251 | 0.251 | No | G NWALL NWA | 0.00 | 90.00 | N | |||||||
| GWINDOW1 W NWA | RESWINDOW_U_0.4945_SHGC_0.25 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 2.811 | 0.251 | 0.251 | No | G WWALL NWA | 270.00 | 90.00 | W | |||||||
| GWINDOW1 S SEA | NONRESWINDOW_U_0.4945_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.811 | 0.251 | 0.251 | No | G SWALL SEA | 180.00 | 90.00 | S | |||||||
| GWINDOW1 E SEA | NONRESWINDOW_U_0.4945_SHGC_0.25 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 2.811 | 0.251 | 0.251 | No | G EWALL SEA | 90.00 | 90.00 | E | |||||||
| GWINDOW1 N NEA | RESWINDOW_U_0.4945_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.811 | 0.251 | 0.251 | No | G NWALL NEA | 0.00 | 90.00 | N | |||||||
| GWINDOW1 E NEA | RESWINDOW_U_0.4945_SHGC_0.25 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 2.811 | 0.251 | 0.251 | No | G EWALL NEA | 90.00 | 90.00 | E | |||||||
| GWINDOW1 N N1A | RESWINDOW_U_0.4945_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.811 | 0.251 | 0.251 | No | G NWALL N1A | 0.00 | 90.00 | N | |||||||
| GWINDOW1 N N2A | RESWINDOW_U_0.4945_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.811 | 0.251 | 0.251 | No | G NWALL N2A | 0.00 | 90.00 | N | |||||||
| GWINDOW1 S S1A | RESWINDOW_U_0.4945_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.811 | 0.251 | 0.251 | No | G SWALL S1A | 180.00 | 90.00 | S | |||||||
| GWINDOW1 S S2A | RESWINDOW_U_0.4945_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.811 | 0.251 | 0.251 | No | G SWALL S2A | 180.00 | 90.00 | S | |||||||
| MWINDOW1 W SWA | RESWINDOW_U_0.4945_SHGC_0.25 | 4.65 | 0.00 | 0.00 | 4.65 | 9.29 | 2.811 | 0.251 | 0.251 | No | M WWALL SWA | 270.00 | 90.00 | W | |||||||
| MWINDOW1 S SWA | RESWINDOW_U_0.4945_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 2.811 | 0.251 | 0.251 | No | M SWALL SWA | 180.00 | 90.00 | S | |||||||
| MWINDOW1 N NWA | RESWINDOW_U_0.4945_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 2.811 | 0.251 | 0.251 | No | M NWALL NWA | 0.00 | 90.00 | N | |||||||
| MWINDOW1 W NWA | RESWINDOW_U_0.4945_SHGC_0.25 | 4.65 | 0.00 | 0.00 | 4.65 | 9.29 | 2.811 | 0.251 | 0.251 | No | M WWALL NWA | 270.00 | 90.00 | W | |||||||
| MWINDOW1 E SEA | RESWINDOW_U_0.4945_SHGC_0.25 | 4.65 | 0.00 | 0.00 | 4.65 | 9.29 | 2.811 | 0.251 | 0.251 | No | M EWALL SEA | 90.00 | 90.00 | E | |||||||
| MWINDOW1 S SEA | RESWINDOW_U_0.4945_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 2.811 | 0.251 | 0.251 | No | M SWALL SEA | 180.00 | 90.00 | S | |||||||
| MWINDOW1 N NEA | RESWINDOW_U_0.4945_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 2.811 | 0.251 | 0.251 | No | M NWALL NEA | 0.00 | 90.00 | N | |||||||
| MWINDOW1 E NEA | RESWINDOW_U_0.4945_SHGC_0.25 | 4.65 | 0.00 | 0.00 | 4.65 | 9.29 | 2.811 | 0.251 | 0.251 | No | M EWALL NEA | 90.00 | 90.00 | E | |||||||
| MWINDOW1 N N1A | RESWINDOW_U_0.4945_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 2.811 | 0.251 | 0.251 | No | M NWALL N1A | 0.00 | 90.00 | N | |||||||
| MWINDOW1 N N2A | RESWINDOW_U_0.4945_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 2.811 | 0.251 | 0.251 | No | M NWALL N2A | 0.00 | 90.00 | N | |||||||
| MWINDOW1 S S1A | RESWINDOW_U_0.4945_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 2.811 | 0.251 | 0.251 | No | M SWALL S1A | 180.00 | 90.00 | S | |||||||
| MWINDOW1 S S2A | RESWINDOW_U_0.4945_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 2.811 | 0.251 | 0.251 | No | M SWALL S2A | 180.00 | 90.00 | S | |||||||
| TWINDOW1 W SWA | RESWINDOW_U_0.4945_SHGC_0.25 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 2.811 | 0.251 | 0.251 | No | T WWALL SWA | 270.00 | 90.00 | W | |||||||
| TWINDOW1 S SWA | RESWINDOW_U_0.4945_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.811 | 0.251 | 0.251 | No | T SWALL SWA | 180.00 | 90.00 | S | |||||||
| TWINDOW1 N NWA | RESWINDOW_U_0.4945_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.811 | 0.251 | 0.251 | No | T NWALL NWA | 0.00 | 90.00 | N | |||||||
| TWINDOW1 W NWA | RESWINDOW_U_0.4945_SHGC_0.25 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 2.811 | 0.251 | 0.251 | No | T WWALL NWA | 270.00 | 90.00 | W | |||||||
| TWINDOW1 E SEA | RESWINDOW_U_0.4945_SHGC_0.25 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 2.811 | 0.251 | 0.251 | No | T EWALL SEA | 90.00 | 90.00 | E | |||||||
| TWINDOW1 S SEA | RESWINDOW_U_0.4945_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.811 | 0.251 | 0.251 | No | T SWALL SEA | 180.00 | 90.00 | S | |||||||
| TWINDOW1 N NEA | RESWINDOW_U_0.4945_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.811 | 0.251 | 0.251 | No | T NWALL NEA | 0.00 | 90.00 | N | |||||||
| TWINDOW1 E NEA | RESWINDOW_U_0.4945_SHGC_0.25 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 2.811 | 0.251 | 0.251 | No | T EWALL NEA | 90.00 | 90.00 | E | |||||||
| TWINDOW1 N N1A | RESWINDOW_U_0.4945_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.811 | 0.251 | 0.251 | No | T NWALL N1A | 0.00 | 90.00 | N | |||||||
| TWINDOW1 N N2A | RESWINDOW_U_0.4945_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.811 | 0.251 | 0.251 | No | T NWALL N2A | 0.00 | 90.00 | N | |||||||
| TWINDOW1 S S1A | RESWINDOW_U_0.4945_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.811 | 0.251 | 0.251 | No | T SWALL S1A | 180.00 | 90.00 | S | |||||||
| TWINDOW1 S S2A | RESWINDOW_U_0.4945_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.811 | 0.251 | 0.251 | No | T SWALL S2A | 180.00 | 90.00 | S | |||||||
| TWINDOW14 | NONRESWINDOW_U_0.4945_SHGC_0.25 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.811 | 0.251 | 0.251 | No | T EWALL C | 90.00 | 90.00 | E | |||||||
| ENTRANCE DOOR | NONRESWINDOW_U_0.4945_SHGC_0.25 | 3.32 | 0.00 | 0.00 | 3.32 | 3.32 | 2.811 | 0.251 | 0.251 | No | G EWALL C | 90.00 | 90.00 | E | |||||||
| MWINDOW14 | NONRESWINDOW_U_0.4945_SHGC_0.25 | 1.11 | 0.00 | 0.00 | 1.11 | 2.23 | 2.811 | 0.251 | 0.251 | No | M EWALL C | 90.00 | 90.00 | E | |||||||
| Total or Average | 306.92 | 2.811 | 0.251 | 0.251 | |||||||||||||||||
| North Total or Average | 112.97 | 2.811 | 0.251 | 0.251 | |||||||||||||||||
| Non-North Total or Average | 193.95 | 2.811 | 0.251 | 0.251 |
| Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
| None |
| Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
| Total or Average | 0.00 | - | - | - |
| Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
| None |
| Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
| None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 09:15:25
Sunlit Fraction| March 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
| GWINDOW1 S SWA | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| GWINDOW1 W SWA | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
| GWINDOW1 N NWA | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| GWINDOW1 W NWA | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
| GWINDOW1 S SEA | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| GWINDOW1 E SEA | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
| GWINDOW1 N NEA | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| GWINDOW1 E NEA | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
| GWINDOW1 N N1A | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| GWINDOW1 N N2A | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| GWINDOW1 S S1A | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| GWINDOW1 S S2A | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| MWINDOW1 W SWA | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
| MWINDOW1 S SWA | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| MWINDOW1 N NWA | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| MWINDOW1 W NWA | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
| MWINDOW1 E SEA | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
| MWINDOW1 S SEA | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| MWINDOW1 N NEA | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| MWINDOW1 E NEA | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
| MWINDOW1 N N1A | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| MWINDOW1 N N2A | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| MWINDOW1 S S1A | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| MWINDOW1 S S2A | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| TWINDOW1 W SWA | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
| TWINDOW1 S SWA | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| TWINDOW1 N NWA | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| TWINDOW1 W NWA | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
| TWINDOW1 E SEA | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
| TWINDOW1 S SEA | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| TWINDOW1 N NEA | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| TWINDOW1 E NEA | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
| TWINDOW1 N N1A | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| TWINDOW1 N N2A | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| TWINDOW1 S S1A | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| TWINDOW1 S S2A | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| TWINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
| ENTRANCE DOOR | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
| MWINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
| Name | Type | Shaded Construction | Control | Glare Control | |
| None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 09:15:25
Interior Lighting| Zone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
| LIGHTING_HARDWIRED_GSW | G SW APARTMENT | G SW APARTMENT | GENERAL | 7.8684 | 88.25 | 694.38 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.32 |
| LIGHTING_HARDWIRED_GNW | G NW APARTMENT | G NW APARTMENT | GENERAL | 7.8684 | 88.25 | 694.38 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.32 |
| LIGHTING_HARDWIRED_OFFICE | OFFICE | OFFICE | GENERAL | 9.7532 | 88.25 | 860.71 | LightsWired | LTG_SCH_OFFICE | 46.69 | 168.00 | 45.77 | 0.0000 | Y | 7.40 |
| LIGHTING_HARDWIRED_GNE | G NE APARTMENT | G NE APARTMENT | GENERAL | 7.8684 | 88.25 | 694.38 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.32 |
| LIGHTING_HARDWIRED_GN1 | G N1 APARTMENT | G N1 APARTMENT | GENERAL | 7.8684 | 88.25 | 694.38 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.32 |
| LIGHTING_HARDWIRED_GN2 | G N2 APARTMENT | G N2 APARTMENT | GENERAL | 7.8684 | 88.25 | 694.38 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.32 |
| LIGHTING_HARDWIRED_GS1 | G S1 APARTMENT | G S1 APARTMENT | GENERAL | 7.8684 | 88.25 | 694.38 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.32 |
| LIGHTING_HARDWIRED_GS2 | G S2 APARTMENT | G S2 APARTMENT | GENERAL | 7.8684 | 88.25 | 694.38 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.32 |
| LIGHTING_HARDWIRED_MSW | M SW APARTMENT | M SW APARTMENT | GENERAL | 7.8684 | 176.50 | 1388.76 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 2.63 |
| LIGHTING_HARDWIRED_MNW | M NW APARTMENT | M NW APARTMENT | GENERAL | 7.8684 | 176.50 | 1388.76 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 2.63 |
| LIGHTING_HARDWIRED_MSE | M SE APARTMENT | M SE APARTMENT | GENERAL | 7.8684 | 176.50 | 1388.76 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 2.63 |
| LIGHTING_HARDWIRED_MNE | M NE APARTMENT | M NE APARTMENT | GENERAL | 7.8684 | 176.50 | 1388.76 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 2.63 |
| LIGHTING_HARDWIRED_MN1 | M N1 APARTMENT | M N1 APARTMENT | GENERAL | 7.8684 | 176.50 | 1388.76 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 2.63 |
| LIGHTING_HARDWIRED_MN2 | M N2 APARTMENT | M N2 APARTMENT | GENERAL | 7.8684 | 176.50 | 1388.76 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 2.63 |
| LIGHTING_HARDWIRED_MS1 | M S1 APARTMENT | M S1 APARTMENT | GENERAL | 7.8684 | 176.50 | 1388.76 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 2.63 |
| LIGHTING_HARDWIRED_MS2 | M S2 APARTMENT | M S2 APARTMENT | GENERAL | 7.8684 | 176.50 | 1388.76 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 2.63 |
| LIGHTING_HARDWIRED_TSW | T SW APARTMENT | T SW APARTMENT | GENERAL | 7.8684 | 88.25 | 694.38 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.32 |
| LIGHTING_HARDWIRED_TNW | T NW APARTMENT | T NW APARTMENT | GENERAL | 7.8684 | 88.25 | 694.38 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.32 |
| LIGHTING_HARDWIRED_TSE | T SE APARTMENT | T SE APARTMENT | GENERAL | 7.8684 | 88.25 | 694.38 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.32 |
| LIGHTING_HARDWIRED_TNE | T NE APARTMENT | T NE APARTMENT | GENERAL | 7.8684 | 88.25 | 694.38 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.32 |
| LIGHTING_HARDWIRED_TN1 | T N1 APARTMENT | T N1 APARTMENT | GENERAL | 7.8684 | 88.25 | 694.38 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.32 |
| LIGHTING_HARDWIRED_TN2 | T N2 APARTMENT | T N2 APARTMENT | GENERAL | 7.8684 | 88.25 | 694.38 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.32 |
| LIGHTING_HARDWIRED_TS1 | T S1 APARTMENT | T S1 APARTMENT | GENERAL | 7.8684 | 88.25 | 694.38 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.32 |
| LIGHTING_HARDWIRED_TS2 | T S2 APARTMENT | T S2 APARTMENT | GENERAL | 7.8684 | 88.25 | 694.38 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.32 |
| LIGHTING_HARDWIRED_GC | G CORRIDOR | G CORRIDOR | GENERAL | 4.7725 | 77.66 | 370.63 | LightsWired | LTG_SCH_CORRIDOR | 168.00 | 168.00 | 168.00 | 0.0000 | N | 11.69 |
| LIGHTING_HARDWIRED_MC | M CORRIDOR | M CORRIDOR | GENERAL | 4.7725 | 155.32 | 741.26 | LightsWired | LTG_SCH_CORRIDOR | 168.00 | 168.00 | 168.00 | 0.0000 | N | 23.38 |
| LIGHTING_HARDWIRED_TC | T CORRIDOR | T CORRIDOR | GENERAL | 4.7725 | 77.66 | 370.63 | LightsWired | LTG_SCH_CORRIDOR | 168.00 | 168.00 | 168.00 | 0.0000 | N | 11.69 |
| LIGHTING_PLUGIN_GSW | G SW APARTMENT | G SW APARTMENT | GENERAL | 0.8234 | 88.25 | 72.67 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.14 |
| LIGHTING_PLUGIN_GNW | G NW APARTMENT | G NW APARTMENT | GENERAL | 0.8234 | 88.25 | 72.67 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.14 |
| LIGHTING_PLUGIN_GNE | G NE APARTMENT | G NE APARTMENT | GENERAL | 0.8234 | 88.25 | 72.67 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.14 |
| LIGHTING_PLUGIN_GN1 | G N1 APARTMENT | G N1 APARTMENT | GENERAL | 0.8234 | 88.25 | 72.67 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.14 |
| LIGHTING_PLUGIN_GN2 | G N2 APARTMENT | G N2 APARTMENT | GENERAL | 0.8234 | 88.25 | 72.67 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.14 |
| LIGHTING_PLUGIN_GS1 | G S1 APARTMENT | G S1 APARTMENT | GENERAL | 0.8234 | 88.25 | 72.67 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.14 |
| LIGHTING_PLUGIN_GS2 | G S2 APARTMENT | G S2 APARTMENT | GENERAL | 0.8234 | 88.25 | 72.67 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.14 |
| LIGHTING_PLUGIN_MSW | M SW APARTMENT | M SW APARTMENT | GENERAL | 0.8234 | 176.50 | 145.34 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.28 |
| LIGHTING_PLUGIN_MNW | M NW APARTMENT | M NW APARTMENT | GENERAL | 0.8234 | 176.50 | 145.34 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.28 |
| LIGHTING_PLUGIN_MSE | M SE APARTMENT | M SE APARTMENT | GENERAL | 0.8234 | 176.50 | 145.34 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.28 |
| LIGHTING_PLUGIN_MNE | M NE APARTMENT | M NE APARTMENT | GENERAL | 0.8234 | 176.50 | 145.34 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.28 |
| LIGHTING_PLUGIN_MN1 | M N1 APARTMENT | M N1 APARTMENT | GENERAL | 0.8234 | 176.50 | 145.34 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.28 |
| LIGHTING_PLUGIN_MN2 | M N2 APARTMENT | M N2 APARTMENT | GENERAL | 0.8234 | 176.50 | 145.34 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.28 |
| LIGHTING_PLUGIN_MS1 | M S1 APARTMENT | M S1 APARTMENT | GENERAL | 0.8234 | 176.50 | 145.34 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.28 |
| LIGHTING_PLUGIN_MS2 | M S2 APARTMENT | M S2 APARTMENT | GENERAL | 0.8234 | 176.50 | 145.34 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.28 |
| LIGHTING_PLUGIN_TSW | T SW APARTMENT | T SW APARTMENT | GENERAL | 0.8234 | 88.25 | 72.67 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.14 |
| LIGHTING_PLUGIN_TNW | T NW APARTMENT | T NW APARTMENT | GENERAL | 0.8234 | 88.25 | 72.67 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.14 |
| LIGHTING_PLUGIN_TSE | T SE APARTMENT | T SE APARTMENT | GENERAL | 0.8234 | 88.25 | 72.67 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.14 |
| LIGHTING_PLUGIN_TNE | T NE APARTMENT | T NE APARTMENT | GENERAL | 0.8234 | 88.25 | 72.67 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.14 |
| LIGHTING_PLUGIN_TN1 | T N1 APARTMENT | T N1 APARTMENT | GENERAL | 0.8234 | 88.25 | 72.67 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.14 |
| LIGHTING_PLUGIN_TN2 | T N2 APARTMENT | T N2 APARTMENT | GENERAL | 0.8234 | 88.25 | 72.67 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.14 |
| LIGHTING_PLUGIN_TS1 | T S1 APARTMENT | T S1 APARTMENT | GENERAL | 0.8234 | 88.25 | 72.67 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.14 |
| LIGHTING_PLUGIN_TS2 | T S2 APARTMENT | T S2 APARTMENT | GENERAL | 0.8234 | 88.25 | 72.67 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.14 |
| Interior Lighting Total | 4.4498 | 5870.34 | 26121.74 | 75.91 |
| Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
| None |
| Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
| FACADE LIGHTING | 3183.33 | AstronomicalClock | - | 83.75 | 83.75 | 50.05 | |
| Exterior Lighting Total | 3183.33 | 50.05 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 09:15:25
Central Plant| Type | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
| None |
| Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
| SPLIT GSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5064.99 | 4055.31 | 1009.68 | 0.80 | 3.91 | |||
| SPLIT GNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 4647.04 | 3720.68 | 926.36 | 0.80 | 3.91 | |||
| SPLIT OFFICE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5947.53 | 4761.92 | 1185.61 | 0.80 | 3.91 | |||
| SPLIT GNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 4333.98 | 3470.03 | 863.96 | 0.80 | 3.91 | |||
| SPLIT GN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 4086.35 | 3271.76 | 814.59 | 0.80 | 3.91 | |||
| SPLIT GN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 4079.16 | 3266.00 | 813.16 | 0.80 | 3.91 | |||
| SPLIT GS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 4487.96 | 3593.31 | 894.65 | 0.80 | 3.91 | |||
| SPLIT GS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 4520.80 | 3619.60 | 901.20 | 0.80 | 3.91 | |||
| SPLIT MSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 12546.58 | 10045.49 | 2501.10 | 0.80 | 3.91 | |||
| SPLIT MNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 11776.07 | 9428.57 | 2347.50 | 0.80 | 3.91 | |||
| SPLIT MSE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 11688.21 | 9358.23 | 2329.98 | 0.80 | 3.91 | |||
| SPLIT MNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10927.69 | 8749.31 | 2178.38 | 0.80 | 3.91 | |||
| SPLIT MN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10027.02 | 8028.19 | 1998.83 | 0.80 | 3.91 | |||
| SPLIT MN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10009.70 | 8014.32 | 1995.38 | 0.80 | 3.91 | |||
| SPLIT MS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10882.14 | 8712.84 | 2169.30 | 0.80 | 3.91 | |||
| SPLIT MS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10863.62 | 8698.02 | 2165.61 | 0.80 | 3.91 | |||
| SPLIT TSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 6665.58 | 5336.83 | 1328.75 | 0.80 | 3.91 | |||
| SPLIT TNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 6365.70 | 5096.73 | 1268.97 | 0.80 | 3.91 | |||
| SPLIT TSE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 6006.39 | 4809.05 | 1197.34 | 0.80 | 3.91 | |||
| SPLIT TNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5706.49 | 4568.93 | 1137.56 | 0.80 | 3.91 | |||
| SPLIT TN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5413.63 | 4334.45 | 1079.18 | 0.80 | 3.91 | |||
| SPLIT TN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5388.57 | 4314.39 | 1074.18 | 0.80 | 3.91 | |||
| SPLIT TS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5736.94 | 4593.31 | 1143.63 | 0.80 | 3.91 | |||
| SPLIT TS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5711.91 | 4573.27 | 1138.64 | 0.80 | 3.91 |
| DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
| SPLIT GSW COOLING COIL | 4825.2 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 | |
| SPLIT GNW COOLING COIL | 4427.0 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 | |
| SPLIT OFFICE COOLING COIL | 5666.0 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 | |
| SPLIT GNE COOLING COIL | 4128.8 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 | |
| SPLIT GN1 COOLING COIL | 3892.9 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 | |
| SPLIT GN2 COOLING COIL | 3886.0 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 | |
| SPLIT GS1 COOLING COIL | 4275.5 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 | |
| SPLIT GS2 COOLING COIL | 4306.8 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 | |
| SPLIT MSW COOLING COIL | 11952.6 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 | |
| SPLIT MNW COOLING COIL | 11218.6 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 | |
| SPLIT MSE COOLING COIL | 11134.9 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 | |
| SPLIT MNE COOLING COIL | 10410.3 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 | |
| SPLIT MN1 COOLING COIL | 9552.3 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 | |
| SPLIT MN2 COOLING COIL | 9535.8 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 | |
| SPLIT MS1 COOLING COIL | 10366.9 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 | |
| SPLIT MS2 COOLING COIL | 10349.3 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 | |
| SPLIT TSW COOLING COIL | 6350.0 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 | |
| SPLIT TNW COOLING COIL | 6064.3 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 | |
| SPLIT TSE COOLING COIL | 5722.0 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 | |
| SPLIT TNE COOLING COIL | 5436.3 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 | |
| SPLIT TN1 COOLING COIL | 5157.3 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 | |
| SPLIT TN2 COOLING COIL | 5133.5 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 | |
| SPLIT TS1 COOLING COIL | 5465.3 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 | |
| SPLIT TS2 COOLING COIL | 5441.5 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 |
| DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
| SPLIT GSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT GNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT OFFICE COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT GNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT GN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT GN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT GS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT GS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT MSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT MNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT MSE COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT MNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT MN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT MN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT MS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT MS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT TSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT TNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT TSE COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT TNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT TN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT TN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT TS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT TS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed |
| DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
| None |
| Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
| SPLIT GSW HEATING COIL | Coil:Heating:Fuel | 7400.80 | 0.80 | |
| SPLIT GNW HEATING COIL | Coil:Heating:Fuel | 6834.02 | 0.80 | |
| SPLIT OFFICE HEATING COIL | Coil:Heating:Fuel | 8846.95 | 0.80 | |
| SPLIT GNE HEATING COIL | Coil:Heating:Fuel | 6409.55 | 0.80 | |
| SPLIT GN1 HEATING COIL | Coil:Heating:Fuel | 6073.72 | 0.80 | |
| SPLIT GN2 HEATING COIL | Coil:Heating:Fuel | 6063.97 | 0.80 | |
| SPLIT GS1 HEATING COIL | Coil:Heating:Fuel | 6618.34 | 0.80 | |
| SPLIT GS2 HEATING COIL | Coil:Heating:Fuel | 6662.86 | 0.80 | |
| SPLIT MSW HEATING COIL | Coil:Heating:Fuel | 18078.42 | 0.80 | |
| SPLIT MNW HEATING COIL | Coil:Heating:Fuel | 17033.45 | 0.80 | |
| SPLIT MSE HEATING COIL | Coil:Heating:Fuel | 16914.55 | 0.80 | |
| SPLIT MNE HEATING COIL | Coil:Heating:Fuel | 15883.14 | 0.80 | |
| SPLIT MN1 HEATING COIL | Coil:Heating:Fuel | 14661.73 | 0.80 | |
| SPLIT MN2 HEATING COIL | Coil:Heating:Fuel | 14638.25 | 0.80 | |
| SPLIT MS1 HEATING COIL | Coil:Heating:Fuel | 15821.36 | 0.80 | |
| SPLIT MS2 HEATING COIL | Coil:Heating:Fuel | 15796.26 | 0.80 | |
| SPLIT TSW HEATING COIL | Coil:Heating:Fuel | 9571.27 | 0.80 | |
| SPLIT TNW HEATING COIL | Coil:Heating:Fuel | 9164.52 | 0.80 | |
| SPLIT TSE HEATING COIL | Coil:Heating:Fuel | 8677.46 | 0.80 | |
| SPLIT TNE HEATING COIL | Coil:Heating:Fuel | 8270.69 | 0.80 | |
| SPLIT TN1 HEATING COIL | Coil:Heating:Fuel | 7873.44 | 0.80 | |
| SPLIT TN2 HEATING COIL | Coil:Heating:Fuel | 7839.47 | 0.80 | |
| SPLIT TS1 HEATING COIL | Coil:Heating:Fuel | 8311.94 | 0.80 | |
| SPLIT TS2 HEATING COIL | Coil:Heating:Fuel | 8277.99 | 0.80 |
| Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
| G SW APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| G SW APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| G NW APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| G NW APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| G NE APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| G NE APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| G N1 APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| G N1 APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| G N2 APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| G N2 APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| G S1 APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| G S1 APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| G S2 APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| G S2 APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| M SW APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.05 | 40.01 | 770.84 | 1.00 | 4.13 | General | ||
| M SW APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.05 | 40.01 | 770.84 | 1.00 | 4.13 | General | ||
| M NW APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.05 | 40.01 | 770.84 | 1.00 | 4.13 | General | ||
| M NW APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.05 | 40.01 | 770.84 | 1.00 | 4.13 | General | ||
| M SE APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.05 | 40.01 | 770.84 | 1.00 | 4.13 | General | ||
| M SE APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.05 | 40.01 | 770.84 | 1.00 | 4.13 | General | ||
| M NE APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.05 | 40.01 | 770.84 | 1.00 | 4.13 | General | ||
| M NE APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.05 | 40.01 | 770.84 | 1.00 | 4.13 | General | ||
| M N1 APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.05 | 40.01 | 770.84 | 1.00 | 4.13 | General | ||
| M N1 APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.05 | 40.01 | 770.84 | 1.00 | 4.13 | General | ||
| M N2 APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.05 | 40.01 | 770.84 | 1.00 | 4.13 | General | ||
| M N2 APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.05 | 40.01 | 770.84 | 1.00 | 4.13 | General | ||
| M S1 APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.05 | 40.01 | 770.84 | 1.00 | 4.13 | General | ||
| M S1 APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.05 | 40.01 | 770.84 | 1.00 | 4.13 | General | ||
| M S2 APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.05 | 40.01 | 770.84 | 1.00 | 4.13 | General | ||
| M S2 APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.05 | 40.01 | 770.84 | 1.00 | 4.13 | General | ||
| T SW APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| T SW APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| T NW APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| T NW APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| T SE APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| T SE APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| T NE APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| T NE APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| T N1 APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| T N1 APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| T N2 APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| T N2 APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| T S1 APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| T S1 APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| T S2 APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| T S2 APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| SPLIT GSW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.31 | 342.73 | 1120.11 | 1.00 | 1.88 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 |
| SPLIT GNW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.28 | 314.45 | 1120.11 | 1.00 | 1.94 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 |
| SPLIT OFFICE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.36 | 402.44 | 1120.11 | 1.00 | 1.78 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 |
| SPLIT GNE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.26 | 293.26 | 1120.11 | 1.00 | 2.00 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 |
| SPLIT GN1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.25 | 276.51 | 1120.11 | 1.00 | 2.05 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 |
| SPLIT GN2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.25 | 276.02 | 1120.11 | 1.00 | 2.05 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 |
| SPLIT GS1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.27 | 303.68 | 1120.11 | 1.00 | 1.97 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 |
| SPLIT GS2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.27 | 305.90 | 1120.11 | 1.00 | 1.97 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 |
| SPLIT MSW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.76 | 848.97 | 1120.11 | 1.00 | 1.45 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 |
| SPLIT MNW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.71 | 796.84 | 1120.11 | 1.00 | 1.47 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 |
| SPLIT MSE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.71 | 790.89 | 1120.11 | 1.00 | 1.47 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 |
| SPLIT MNE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.66 | 739.43 | 1120.11 | 1.00 | 1.50 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 |
| SPLIT MN1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.61 | 678.49 | 1120.11 | 1.00 | 1.53 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 |
| SPLIT MN2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.60 | 677.31 | 1120.11 | 1.00 | 1.53 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 |
| SPLIT MS1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.66 | 736.35 | 1120.11 | 1.00 | 1.50 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 |
| SPLIT MS2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.66 | 735.09 | 1120.11 | 1.00 | 1.50 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 |
| SPLIT TSW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.40 | 451.03 | 1120.11 | 1.00 | 1.71 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 |
| SPLIT TNW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.38 | 430.74 | 1120.11 | 1.00 | 1.74 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 |
| SPLIT TSE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.36 | 406.43 | 1120.11 | 1.00 | 1.77 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 |
| SPLIT TNE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.34 | 386.13 | 1120.11 | 1.00 | 1.80 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 |
| SPLIT TN1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.33 | 366.32 | 1120.11 | 1.00 | 1.84 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 |
| SPLIT TN2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.33 | 364.62 | 1120.11 | 1.00 | 1.84 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 |
| SPLIT TS1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.35 | 388.19 | 1120.11 | 1.00 | 1.80 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 |
| SPLIT TS2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.35 | 386.50 | 1120.11 | 1.00 | 1.80 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 |
| Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
| None |
| Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
| G SW APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.77 |
| G NW APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.77 |
| G NE APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.77 |
| G N1 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.77 |
| G N2 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.77 |
| G S1 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.77 |
| G S2 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.77 |
| M SW APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.79 |
| M NW APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.79 |
| M SE APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.79 |
| M NE APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.79 |
| M N1 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.79 |
| M N2 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.79 |
| M S1 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.79 |
| M S2 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.79 |
| T SW APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.77 |
| T NW APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.77 |
| T SE APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.77 |
| T NE APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.77 |
| T N1 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.77 |
| T N2 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.77 |
| T S1 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.77 |
| T S2 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.77 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 09:15:25
Zone Sensible Cooling| Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
| G SW APARTMENT | 3555.10 | 4266.12 | 48.34 | 0.255 | 0.306 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 24.00 | 24.00 | 0.00814 | 27.83 | 0.00823 | 0.026 | 0.00 |
| G NW APARTMENT | 3269.22 | 3923.07 | 44.45 | 0.234 | 0.281 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 24.00 | 24.00 | 0.00812 | 27.83 | 0.00823 | 0.026 | 0.00 |
| OFFICE | 4104.51 | 4925.41 | 55.81 | 0.299 | 0.359 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | 23.90 | 23.90 | 0.00802 | 26.41 | 0.00823 | 0.038 | 0.00 |
| G NE APARTMENT | 3055.64 | 3666.77 | 41.55 | 0.218 | 0.262 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 24.00 | 24.00 | 0.00813 | 27.83 | 0.00823 | 0.026 | 0.00 |
| G N1 APARTMENT | 2885.93 | 3463.12 | 39.24 | 0.206 | 0.247 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 24.00 | 24.00 | 0.00814 | 27.83 | 0.00823 | 0.026 | 0.00 |
| G N2 APARTMENT | 2881.01 | 3457.21 | 39.18 | 0.205 | 0.246 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 24.00 | 24.00 | 0.00814 | 27.83 | 0.00823 | 0.026 | 0.00 |
| G S1 APARTMENT | 3160.99 | 3793.19 | 42.98 | 0.226 | 0.271 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 24.00 | 24.00 | 0.00819 | 27.83 | 0.00823 | 0.026 | 0.00 |
| G S2 APARTMENT | 3183.29 | 3819.95 | 43.29 | 0.228 | 0.273 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 24.00 | 24.00 | 0.00819 | 27.83 | 0.00823 | 0.026 | 0.00 |
| M SW APARTMENT | 8761.67 | 10514.00 | 119.14 | 0.632 | 0.758 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 24.00 | 24.00 | 0.00810 | 27.83 | 0.00823 | 0.052 | 0.00 |
| M NW APARTMENT | 8236.21 | 9883.45 | 111.99 | 0.593 | 0.711 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 24.00 | 24.00 | 0.00809 | 27.83 | 0.00823 | 0.052 | 0.00 |
| M SE APARTMENT | 8175.97 | 9811.17 | 111.18 | 0.588 | 0.706 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 24.00 | 24.00 | 0.00812 | 27.83 | 0.00823 | 0.052 | 0.00 |
| M NE APARTMENT | 7658.55 | 9190.26 | 104.14 | 0.550 | 0.660 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 24.00 | 24.00 | 0.00810 | 27.83 | 0.00823 | 0.052 | 0.00 |
| M N1 APARTMENT | 7039.17 | 8447.00 | 95.72 | 0.505 | 0.606 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 24.00 | 24.00 | 0.00811 | 27.83 | 0.00823 | 0.052 | 0.00 |
| M N2 APARTMENT | 7027.29 | 8432.75 | 95.56 | 0.504 | 0.605 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 24.00 | 24.00 | 0.00811 | 27.83 | 0.00823 | 0.052 | 0.00 |
| M S1 APARTMENT | 7626.97 | 9152.37 | 103.71 | 0.548 | 0.657 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 24.00 | 24.00 | 0.00814 | 27.83 | 0.00823 | 0.052 | 0.00 |
| M S2 APARTMENT | 7614.20 | 9137.04 | 103.54 | 0.547 | 0.656 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 24.00 | 24.00 | 0.00814 | 27.83 | 0.00823 | 0.052 | 0.00 |
| T SW APARTMENT | 4652.43 | 5582.92 | 63.26 | 0.336 | 0.403 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 24.00 | 24.00 | 0.00810 | 27.83 | 0.00823 | 0.026 | 0.00 |
| T NW APARTMENT | 4446.81 | 5336.17 | 60.47 | 0.320 | 0.385 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 24.00 | 24.00 | 0.00809 | 27.83 | 0.00823 | 0.026 | 0.00 |
| T SE APARTMENT | 4200.44 | 5040.53 | 57.12 | 0.302 | 0.363 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 24.00 | 24.00 | 0.00811 | 27.83 | 0.00823 | 0.026 | 0.00 |
| T NE APARTMENT | 3995.61 | 4794.73 | 54.33 | 0.287 | 0.345 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 24.00 | 24.00 | 0.00810 | 27.83 | 0.00823 | 0.026 | 0.00 |
| T N1 APARTMENT | 3795.90 | 4555.09 | 51.62 | 0.273 | 0.327 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 24.00 | 24.00 | 0.00810 | 27.83 | 0.00823 | 0.026 | 0.00 |
| T N2 APARTMENT | 3778.83 | 4534.60 | 51.38 | 0.271 | 0.326 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 24.00 | 24.00 | 0.00810 | 27.83 | 0.00823 | 0.026 | 0.00 |
| T S1 APARTMENT | 4016.36 | 4819.64 | 54.61 | 0.289 | 0.347 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 24.00 | 24.00 | 0.00811 | 27.83 | 0.00823 | 0.026 | 0.00 |
| T S2 APARTMENT | 3999.27 | 4799.12 | 54.38 | 0.288 | 0.345 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 24.00 | 24.00 | 0.00812 | 27.83 | 0.00823 | 0.026 | 0.00 |
| Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
| G SW APARTMENT | 989.95 | 1187.94 | 13.46 | 0.043 | 0.052 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 04:10:00 | 21.10 | 21.10 | 0.00744 | 3.80 | 0.00506 | 0.026 | 0.00 |
| G NW APARTMENT | 863.28 | 1035.94 | 11.74 | 0.038 | 0.045 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 04:00:00 | 21.10 | 21.10 | 0.00767 | 3.80 | 0.00506 | 0.026 | 0.00 |
| OFFICE | 1391.32 | 1669.58 | 18.92 | 0.061 | 0.073 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 18:50:00 | 21.10 | 21.10 | 0.00757 | 3.80 | 0.00506 | 0.038 | 0.00 |
| G NE APARTMENT | 864.66 | 1037.59 | 11.76 | 0.038 | 0.046 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 04:00:00 | 21.10 | 21.10 | 0.00767 | 3.80 | 0.00506 | 0.026 | 0.00 |
| G N1 APARTMENT | 435.47 | 522.57 | 5.92 | 0.019 | 0.026 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 04:00:00 | 21.10 | 21.10 | 0.00780 | 3.80 | 0.00506 | 0.026 | 0.00 |
| G N2 APARTMENT | 435.51 | 522.62 | 5.92 | 0.019 | 0.026 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 04:00:00 | 21.10 | 21.10 | 0.00781 | 3.80 | 0.00506 | 0.026 | 0.00 |
| G S1 APARTMENT | 562.33 | 674.80 | 7.65 | 0.025 | 0.030 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 04:10:00 | 21.10 | 21.10 | 0.00739 | 3.80 | 0.00506 | 0.026 | 0.00 |
| G S2 APARTMENT | 570.71 | 684.85 | 7.76 | 0.025 | 0.030 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 04:00:00 | 21.10 | 21.10 | 0.00740 | 3.80 | 0.00506 | 0.026 | 0.00 |
| M SW APARTMENT | 1887.46 | 2264.95 | 25.67 | 0.083 | 0.099 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | 21.10 | 21.10 | 0.00723 | 3.80 | 0.00506 | 0.052 | 0.00 |
| M NW APARTMENT | 1604.29 | 1925.14 | 21.81 | 0.070 | 0.085 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | 21.10 | 21.10 | 0.00741 | 3.80 | 0.00506 | 0.052 | 0.00 |
| M SE APARTMENT | 1890.97 | 2269.17 | 25.71 | 0.083 | 0.100 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | 21.10 | 21.10 | 0.00723 | 3.80 | 0.00506 | 0.052 | 0.00 |
| M NE APARTMENT | 1607.93 | 1929.51 | 21.86 | 0.071 | 0.085 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | 21.10 | 21.10 | 0.00741 | 3.80 | 0.00506 | 0.052 | 0.00 |
| M N1 APARTMENT | 660.03 | 792.03 | 8.97 | 0.029 | 0.052 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | 21.10 | 21.10 | 0.00742 | 3.80 | 0.00506 | 0.052 | 0.00 |
| M N2 APARTMENT | 660.12 | 792.15 | 8.98 | 0.029 | 0.052 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | 21.10 | 21.10 | 0.00742 | 3.80 | 0.00506 | 0.052 | 0.00 |
| M S1 APARTMENT | 934.07 | 1120.88 | 12.70 | 0.041 | 0.052 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | 21.10 | 21.10 | 0.00706 | 3.80 | 0.00506 | 0.052 | 0.00 |
| M S2 APARTMENT | 934.16 | 1120.99 | 12.70 | 0.041 | 0.052 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | 21.10 | 21.10 | 0.00706 | 3.80 | 0.00506 | 0.052 | 0.00 |
| T SW APARTMENT | 1803.47 | 2164.17 | 24.52 | 0.079 | 0.095 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | 21.10 | 21.10 | 0.00742 | 3.80 | 0.00506 | 0.026 | 0.00 |
| T NW APARTMENT | 1651.28 | 1981.53 | 22.45 | 0.072 | 0.087 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | 21.10 | 21.10 | 0.00753 | 3.80 | 0.00506 | 0.026 | 0.00 |
| T SE APARTMENT | 1805.46 | 2166.56 | 24.55 | 0.079 | 0.095 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | 21.10 | 21.10 | 0.00742 | 3.80 | 0.00506 | 0.026 | 0.00 |
| T NE APARTMENT | 1653.38 | 1984.05 | 22.48 | 0.073 | 0.087 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | 21.10 | 21.10 | 0.00753 | 3.80 | 0.00506 | 0.026 | 0.00 |
| T N1 APARTMENT | 1091.82 | 1310.18 | 14.85 | 0.048 | 0.058 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | 21.10 | 21.10 | 0.00766 | 3.80 | 0.00506 | 0.026 | 0.00 |
| T N2 APARTMENT | 1091.88 | 1310.26 | 14.85 | 0.048 | 0.058 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | 21.10 | 21.10 | 0.00766 | 3.80 | 0.00506 | 0.026 | 0.00 |
| T S1 APARTMENT | 1245.05 | 1494.06 | 16.93 | 0.055 | 0.066 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | 21.10 | 21.10 | 0.00748 | 3.80 | 0.00506 | 0.026 | 0.00 |
| T S2 APARTMENT | 1245.11 | 1494.13 | 16.93 | 0.055 | 0.066 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | 21.10 | 21.10 | 0.00748 | 3.80 | 0.00506 | 0.026 | 0.00 |
| Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
| SPLIT GSW | 0.31 | 0.31 | 0.05 | 0.05 | 0.3060 | 0.3060 | 0.3060 | 1.0000 | 1.0000 |
| SPLIT GNW | 0.28 | 0.28 | 0.05 | 0.05 | 0.2807 | 0.2807 | 0.2807 | 1.0000 | 1.0000 |
| SPLIT OFFICE | 0.36 | 0.36 | 0.07 | 0.07 | 0.3593 | 0.3593 | 0.3593 | 1.0000 | 1.0000 |
| SPLIT GNE | 0.26 | 0.26 | 0.05 | 0.05 | 0.2618 | 0.2618 | 0.2618 | 1.0000 | 1.0000 |
| SPLIT GN1 | 0.25 | 0.25 | 0.03 | 0.03 | 0.2469 | 0.2469 | 0.2469 | 1.0000 | 1.0000 |
| SPLIT GN2 | 0.25 | 0.25 | 0.03 | 0.03 | 0.2464 | 0.2464 | 0.2464 | 1.0000 | 1.0000 |
| SPLIT GS1 | 0.27 | 0.27 | 0.03 | 0.03 | 0.2711 | 0.2711 | 0.2711 | 1.0000 | 1.0000 |
| SPLIT GS2 | 0.27 | 0.27 | 0.03 | 0.03 | 0.2731 | 0.2731 | 0.2731 | 1.0000 | 1.0000 |
| SPLIT MSW | 0.76 | 0.76 | 0.10 | 0.10 | 0.7579 | 0.7579 | 0.7579 | 1.0000 | 1.0000 |
| SPLIT MNW | 0.71 | 0.71 | 0.08 | 0.08 | 0.7114 | 0.7114 | 0.7114 | 1.0000 | 1.0000 |
| SPLIT MSE | 0.71 | 0.71 | 0.10 | 0.10 | 0.7061 | 0.7061 | 0.7061 | 1.0000 | 1.0000 |
| SPLIT MNE | 0.66 | 0.66 | 0.08 | 0.08 | 0.6601 | 0.6601 | 0.6601 | 1.0000 | 1.0000 |
| SPLIT MN1 | 0.61 | 0.61 | 0.05 | 0.05 | 0.6057 | 0.6057 | 0.6057 | 1.0000 | 1.0000 |
| SPLIT MN2 | 0.60 | 0.60 | 0.05 | 0.05 | 0.6047 | 0.6047 | 0.6047 | 1.0000 | 1.0000 |
| SPLIT MS1 | 0.66 | 0.66 | 0.05 | 0.05 | 0.6574 | 0.6574 | 0.6574 | 1.0000 | 1.0000 |
| SPLIT MS2 | 0.66 | 0.66 | 0.05 | 0.05 | 0.6563 | 0.6563 | 0.6563 | 1.0000 | 1.0000 |
| SPLIT TSW | 0.40 | 0.40 | 0.10 | 0.10 | 0.4027 | 0.4027 | 0.4027 | 1.0000 | 1.0000 |
| SPLIT TNW | 0.38 | 0.38 | 0.09 | 0.09 | 0.3846 | 0.3846 | 0.3846 | 1.0000 | 1.0000 |
| SPLIT TSE | 0.36 | 0.36 | 0.10 | 0.10 | 0.3628 | 0.3628 | 0.3628 | 1.0000 | 1.0000 |
| SPLIT TNE | 0.34 | 0.34 | 0.09 | 0.09 | 0.3447 | 0.3447 | 0.3447 | 1.0000 | 1.0000 |
| SPLIT TN1 | 0.33 | 0.33 | 0.06 | 0.06 | 0.3270 | 0.3270 | 0.3270 | 1.0000 | 1.0000 |
| SPLIT TN2 | 0.33 | 0.33 | 0.06 | 0.06 | 0.3255 | 0.3255 | 0.3255 | 1.0000 | 1.0000 |
| SPLIT TS1 | 0.35 | 0.35 | 0.07 | 0.07 | 0.3466 | 0.3466 | 0.3466 | 1.0000 | 1.0000 |
| SPLIT TS2 | 0.35 | 0.35 | 0.07 | 0.07 | 0.3451 | 0.3451 | 0.3451 | 1.0000 | 1.0000 |
| Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
| None |
| Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
| SPLIT GSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT GSW | 5064.991 | 4055.311 | 0.305976 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 4940.96 | 4820.00 | 0.305976 | 25.28 | 16.35 | 0.00814931 | 12.80 | 11.43 | 0.00800000 | 27.83 | 0.00822799 | 17.29 | 8.4825 | 24.00 | 0.00814202 | 43.0396 | 3555.10 | 0.00 | 5064.13 | 4011.36 |
| SPLIT GSW HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT GSW | 7400.805 | 7400.805 | -999.0 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 04:10:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 04:10:00 | 7400.80 | 7400.80 | 0.305976 | 19.63 | 13.44 | 0.00723471 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 8.4825 | 21.10 | 0.00743642 | 46.9351 | 989.95 | 0.00 | -999.00 | -999.00 |
| SPLIT GNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT GNW | 4647.044 | 3720.680 | 0.280728 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 4532.00 | 4437.40 | 0.280728 | 25.30 | 16.34 | 0.00812701 | 12.80 | 11.43 | 0.00800000 | 27.83 | 0.00822799 | 17.29 | 9.2454 | 24.00 | 0.00811672 | 42.9074 | 3269.22 | 0.00 | 4646.25 | 3680.36 |
| SPLIT GNW HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT GNW | 6834.015 | 6834.015 | -999.0 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 04:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 04:00:00 | 6834.02 | 6834.02 | 0.280728 | 19.50 | 13.57 | 0.00742487 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 9.2454 | 21.10 | 0.00766594 | 48.3652 | 863.28 | 0.00 | -999.00 | -999.00 |
| SPLIT OFFICE COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT OFFICE | 5947.528 | 4761.920 | 0.359290 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | 5828.28 | 5791.12 | 0.359290 | 25.14 | 16.20 | 0.00803781 | 12.80 | 11.43 | 0.00800000 | 26.41 | 0.00822575 | 16.80 | 10.6059 | 23.90 | 0.00801551 | 42.6342 | 4104.51 | 0.00 | 5946.52 | 4710.31 |
| SPLIT OFFICE HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT OFFICE | 8846.952 | 8846.952 | -999.0 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 18:50:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 18:50:00 | 8846.95 | 8846.95 | 0.359290 | 19.26 | 13.36 | 0.00730577 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 10.6059 | 21.10 | 0.00757240 | 47.7823 | 1391.32 | 0.00 | -999.00 | -999.00 |
| SPLIT GNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT GNE | 4333.985 | 3470.028 | 0.261816 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 4228.45 | 4131.00 | 0.261816 | 25.32 | 16.36 | 0.00814072 | 12.80 | 11.43 | 0.00800000 | 27.83 | 0.00822799 | 17.29 | 9.9133 | 24.00 | 0.00813112 | 42.9825 | 3055.64 | 0.00 | 4333.25 | 3432.42 |
| SPLIT GNE HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT GNE | 6409.546 | 6409.546 | -999.0 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 04:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 04:00:00 | 6409.55 | 6409.55 | 0.261816 | 19.38 | 13.50 | 0.00740785 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 9.9133 | 21.10 | 0.00766638 | 48.3679 | 864.66 | 0.00 | -999.00 | -999.00 |
| SPLIT GN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT GN1 | 4086.350 | 3271.758 | 0.246856 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 3988.30 | 3888.51 | 0.246856 | 25.34 | 16.37 | 0.00815324 | 12.80 | 11.43 | 0.00800000 | 27.83 | 0.00822799 | 17.29 | 10.5140 | 24.00 | 0.00814446 | 43.0522 | 2885.93 | 0.00 | 4085.65 | 3236.30 |
| SPLIT GN1 HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT GN1 | 6073.722 | 6073.722 | -999.0 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 6073.72 | 6073.72 | 0.246856 | 19.28 | 13.57 | 0.00751622 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 10.5140 | 21.10 | 0.00770504 | 48.6082 | 389.06 | 0.00 | -999.00 | -999.00 |
| SPLIT GN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT GN2 | 4079.161 | 3266.002 | 0.246422 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 3981.32 | 3881.51 | 0.246422 | 25.34 | 16.37 | 0.00815355 | 12.80 | 11.43 | 0.00800000 | 27.83 | 0.00822799 | 17.29 | 10.5326 | 24.00 | 0.00814479 | 43.0539 | 2881.01 | 0.00 | 4078.47 | 3230.60 |
| SPLIT GN2 HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT GN2 | 6063.974 | 6063.974 | -999.0 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 6063.97 | 6063.97 | 0.246422 | 19.28 | 13.56 | 0.00751573 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 10.5326 | 21.10 | 0.00770508 | 48.6084 | 389.10 | 0.00 | -999.00 | -999.00 |
| SPLIT GS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT GS1 | 4487.956 | 3593.306 | 0.271117 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 4382.73 | 4245.50 | 0.271117 | 25.31 | 16.40 | 0.00819270 | 12.80 | 11.43 | 0.00800000 | 27.83 | 0.00822799 | 17.29 | 9.5732 | 24.00 | 0.00818896 | 43.2847 | 3160.99 | 0.00 | 4487.19 | 3554.36 |
| SPLIT GS1 HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT GS1 | 6618.336 | 6618.336 | -999.0 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 04:10:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 04:10:00 | 6618.34 | 6618.34 | 0.271117 | 19.44 | 13.30 | 0.00716653 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 9.5732 | 21.10 | 0.00738971 | 46.6431 | 562.33 | 0.00 | -999.00 | -999.00 |
| SPLIT GS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT GS2 | 4520.797 | 3619.600 | 0.273101 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 4414.66 | 4276.93 | 0.273101 | 25.31 | 16.40 | 0.00819195 | 12.80 | 11.43 | 0.00800000 | 27.83 | 0.00822799 | 17.29 | 9.5036 | 24.00 | 0.00818816 | 43.2805 | 3183.29 | 0.00 | 4520.03 | 3580.37 |
| SPLIT GS2 HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT GS2 | 6662.865 | 6662.865 | -999.0 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 04:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 04:00:00 | 6662.86 | 6662.86 | 0.273101 | 19.46 | 13.31 | 0.00717425 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 9.5036 | 21.10 | 0.00739644 | 46.6851 | 570.71 | 0.00 | -999.00 | -999.00 |
| SPLIT MSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT MSW | 12546.584 | 10045.489 | 0.757939 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 12226.18 | 11997.38 | 0.757939 | 25.24 | 16.30 | 0.00811312 | 12.80 | 11.43 | 0.00800000 | 27.83 | 0.00822799 | 17.29 | 6.8487 | 24.00 | 0.00810468 | 42.8446 | 17523.34 | 0.00 | 12544.45 | 9936.62 |
| SPLIT MSW HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT MSW | 18078.421 | 18078.421 | -999.0 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | 18078.42 | 18078.42 | 0.757939 | 19.91 | 13.40 | 0.00707695 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 6.8487 | 21.10 | 0.00722535 | 45.6187 | 3774.92 | 0.00 | -999.00 | -999.00 |
| SPLIT MNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT MNW | 11776.069 | 9428.571 | 0.711392 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 11474.04 | 11281.13 | 0.711392 | 25.25 | 16.30 | 0.00810153 | 12.80 | 11.43 | 0.00800000 | 27.83 | 0.00822799 | 17.29 | 7.2968 | 24.00 | 0.00809157 | 42.7761 | 16472.42 | 0.00 | 11774.06 | 9326.38 |
| SPLIT MNW HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT MNW | 17033.446 | 17033.446 | -999.0 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | 17033.45 | 17033.45 | 0.711392 | 19.84 | 13.52 | 0.00724196 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 7.2968 | 21.10 | 0.00741383 | 46.7939 | 3208.57 | 0.00 | -999.00 | -999.00 |
| SPLIT MSE COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT MSE | 11688.213 | 9358.229 | 0.706085 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 11394.09 | 11155.99 | 0.706085 | 25.25 | 16.32 | 0.00812672 | 12.80 | 11.43 | 0.00800000 | 27.83 | 0.00822799 | 17.29 | 7.3517 | 24.00 | 0.00811868 | 42.9177 | 16351.94 | 0.00 | 11686.22 | 9256.80 |
| SPLIT MSE HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT MSE | 16914.547 | 16914.547 | -999.0 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | 16914.55 | 16914.55 | 0.706085 | 19.83 | 13.35 | 0.00706706 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 7.3517 | 21.10 | 0.00722645 | 45.6256 | 3781.95 | 0.00 | -999.00 | -999.00 |
| SPLIT MNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT MNE | 10927.693 | 8749.315 | 0.660142 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 10650.97 | 10454.63 | 0.660142 | 25.27 | 16.31 | 0.00811163 | 12.80 | 11.43 | 0.00800000 | 27.83 | 0.00822799 | 17.29 | 7.8633 | 24.00 | 0.00810170 | 42.8289 | 15317.10 | 0.00 | 10925.83 | 8654.49 |
| SPLIT MNE HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT MNE | 15883.143 | 15883.143 | -999.0 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | 15883.14 | 15883.14 | 0.660142 | 19.74 | 13.47 | 0.00722951 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 7.8633 | 21.10 | 0.00741480 | 46.7999 | 3215.85 | 0.00 | -999.00 | -999.00 |
| SPLIT MN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT MN1 | 10027.019 | 8028.186 | 0.605732 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 9776.57 | 9579.16 | 0.605732 | 25.29 | 16.33 | 0.00812264 | 12.80 | 11.43 | 0.00800000 | 27.83 | 0.00822799 | 17.29 | 8.5696 | 24.00 | 0.00811277 | 42.8867 | 14078.34 | 0.00 | 10025.31 | 7941.18 |
| SPLIT MN1 HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT MN1 | 14661.728 | 14661.728 | -999.0 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 17:00:00 | 14661.73 | 14661.73 | 0.605732 | 19.62 | 13.41 | 0.00721548 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 8.5696 | 21.10 | 0.00718520 | 45.3666 | 1049.54 | 0.00 | -999.00 | -999.00 |
| SPLIT MN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT MN2 | 10009.701 | 8014.320 | 0.604686 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 9759.76 | 9562.29 | 0.604686 | 25.29 | 16.33 | 0.00812290 | 12.80 | 11.43 | 0.00800000 | 27.83 | 0.00822799 | 17.29 | 8.5845 | 24.00 | 0.00811303 | 42.8881 | 14054.58 | 0.00 | 10008.00 | 7927.46 |
| SPLIT MN2 HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT MN2 | 14638.248 | 14638.248 | -999.0 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 17:20:00 | 14638.25 | 14638.25 | 0.604686 | 19.61 | 13.41 | 0.00721520 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 8.5845 | 21.10 | 0.00718531 | 45.3672 | 1049.73 | 0.00 | -999.00 | -999.00 |
| SPLIT MS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT MS1 | 10882.137 | 8712.840 | 0.657390 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 10613.14 | 10363.14 | 0.657390 | 25.27 | 16.34 | 0.00814340 | 12.80 | 11.43 | 0.00800000 | 27.83 | 0.00822799 | 17.29 | 7.8962 | 24.00 | 0.00813614 | 43.0089 | 15253.95 | 0.00 | 10880.28 | 8618.41 |
| SPLIT MS1 HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT MS1 | 15821.362 | 15821.362 | -999.0 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 15821.36 | 15821.36 | 0.657390 | 19.73 | 13.16 | 0.00690625 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 7.8962 | 21.10 | 0.00686723 | 43.3815 | 1546.55 | 0.00 | -999.00 | -999.00 |
| SPLIT MS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT MS2 | 10863.623 | 8698.017 | 0.656271 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 10595.20 | 10344.93 | 0.656271 | 25.27 | 16.34 | 0.00814380 | 12.80 | 11.43 | 0.00800000 | 27.83 | 0.00822799 | 17.29 | 7.9097 | 24.00 | 0.00813657 | 43.0111 | 15228.40 | 0.00 | 10861.77 | 8603.75 |
| SPLIT MS2 HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT MS2 | 15796.259 | 15796.259 | -999.0 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 15796.26 | 15796.26 | 0.656271 | 19.73 | 13.16 | 0.00690605 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 7.9097 | 21.10 | 0.00686733 | 43.3821 | 1546.73 | 0.00 | -999.00 | -999.00 |
| SPLIT TSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT TSW | 6665.582 | 5336.833 | 0.402668 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 6493.95 | 6381.25 | 0.402668 | 25.23 | 16.29 | 0.00810471 | 12.80 | 11.43 | 0.00800000 | 27.83 | 0.00822799 | 17.29 | 6.4456 | 24.00 | 0.00809622 | 42.8004 | 4652.43 | 0.00 | 6664.45 | 5278.99 |
| SPLIT TSW HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT TSW | 9571.272 | 9571.272 | -999.0 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | 9571.27 | 9571.27 | 0.402668 | 19.98 | 13.60 | 0.00726820 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 6.4456 | 21.10 | 0.00742044 | 46.8369 | 1803.47 | 0.00 | -999.00 | -999.00 |
| SPLIT TNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT TNW | 6365.697 | 5096.728 | 0.384552 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 6201.11 | 6102.92 | 0.384552 | 25.24 | 16.29 | 0.00809545 | 12.80 | 11.43 | 0.00800000 | 27.83 | 0.00822799 | 17.29 | 6.7493 | 24.00 | 0.00808586 | 42.7462 | 4446.81 | 0.00 | 6364.61 | 5041.49 |
| SPLIT TNW HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT TNW | 9164.519 | 9164.519 | -999.0 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | 9164.52 | 9164.52 | 0.384552 | 19.93 | 13.68 | 0.00736563 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 6.7493 | 21.10 | 0.00753262 | 47.5356 | 1651.28 | 0.00 | -999.00 | -999.00 |
| SPLIT TSE COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT TSE | 6006.395 | 4809.051 | 0.362846 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 5854.25 | 5739.73 | 0.362846 | 25.25 | 16.31 | 0.00811845 | 12.80 | 11.43 | 0.00800000 | 27.83 | 0.00822799 | 17.29 | 7.1530 | 24.00 | 0.00811001 | 42.8724 | 4200.44 | 0.00 | 6005.37 | 4756.93 |
| SPLIT TSE HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT TSE | 8677.457 | 8677.457 | -999.0 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | 8677.46 | 8677.46 | 0.362846 | 19.86 | 13.54 | 0.00725197 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 7.1530 | 21.10 | 0.00742096 | 46.8402 | 1805.46 | 0.00 | -999.00 | -999.00 |
| SPLIT TNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT TNE | 5706.491 | 4568.932 | 0.344729 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 5561.19 | 5463.10 | 0.344729 | 25.26 | 16.31 | 0.00810668 | 12.80 | 11.43 | 0.00800000 | 27.83 | 0.00822799 | 17.29 | 7.5290 | 24.00 | 0.00809681 | 42.8034 | 3995.61 | 0.00 | 5705.52 | 4519.41 |
| SPLIT TNE HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT TNE | 8270.693 | 8270.693 | -999.0 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | 8270.69 | 8270.69 | 0.344729 | 19.80 | 13.61 | 0.00734677 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 7.5290 | 21.10 | 0.00753309 | 47.5385 | 1653.38 | 0.00 | -999.00 | -999.00 |
| SPLIT TN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT TN1 | 5413.631 | 4334.452 | 0.327037 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 5276.53 | 5181.93 | 0.327037 | 25.27 | 16.31 | 0.00810857 | 12.80 | 11.43 | 0.00800000 | 27.83 | 0.00822799 | 17.29 | 7.9363 | 24.00 | 0.00809827 | 42.8110 | 3795.90 | 0.00 | 5412.71 | 4287.47 |
| SPLIT TN1 HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT TN1 | 7873.444 | 7873.444 | -999.0 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | 7873.44 | 7873.44 | 0.327037 | 19.73 | 13.68 | 0.00745191 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 7.9363 | 21.10 | 0.00765824 | 48.3174 | 1091.82 | 0.00 | -999.00 | -999.00 |
| SPLIT TN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT TN2 | 5388.574 | 4314.391 | 0.325524 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 5252.21 | 5157.59 | 0.325524 | 25.28 | 16.31 | 0.00810911 | 12.80 | 11.43 | 0.00800000 | 27.83 | 0.00822799 | 17.29 | 7.9732 | 24.00 | 0.00809881 | 42.8138 | 3778.83 | 0.00 | 5387.66 | 4267.63 |
| SPLIT TN2 HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT TN2 | 7839.471 | 7839.471 | -999.0 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | 7839.47 | 7839.47 | 0.325524 | 19.72 | 13.67 | 0.00745097 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 7.9732 | 21.10 | 0.00765825 | 48.3175 | 1091.88 | 0.00 | -999.00 | -999.00 |
| SPLIT TS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT TS1 | 5736.945 | 4593.315 | 0.346569 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 5592.59 | 5479.10 | 0.346569 | 25.26 | 16.32 | 0.00812305 | 12.80 | 11.43 | 0.00800000 | 27.83 | 0.00822799 | 17.29 | 7.4890 | 24.00 | 0.00811456 | 42.8962 | 4016.36 | 0.00 | 5735.97 | 4543.53 |
| SPLIT TS1 HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT TS1 | 8311.939 | 8311.939 | -999.0 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | 8311.94 | 8311.94 | 0.346569 | 19.80 | 13.56 | 0.00729756 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 7.4890 | 21.10 | 0.00747883 | 47.1998 | 1245.05 | 0.00 | -999.00 | -999.00 |
| SPLIT TS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT TS2 | 5711.907 | 4573.268 | 0.345056 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 5568.30 | 5454.69 | 0.345056 | 25.26 | 16.32 | 0.00812375 | 12.80 | 11.43 | 0.00800000 | 27.83 | 0.00822799 | 17.29 | 7.5218 | 24.00 | 0.00811528 | 42.8999 | 3999.27 | 0.00 | 5710.93 | 4523.70 |
| SPLIT TS2 HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT TS2 | 8277.990 | 8277.990 | -999.0 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | 8277.99 | 8277.99 | 0.345056 | 19.80 | 13.56 | 0.00729679 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 7.5218 | 21.10 | 0.00747885 | 47.2000 | 1245.11 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 09:15:25
Coils| Coil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
| SPLIT GSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT GSW | G SW APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 5064.991 | 4055.311 | 0.305976 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.9892 | 1004.8586 | 1.1818 | SPLIT GSW SUPPLY FAN | Fan:OnOff | 0.305976 | 0.36159601 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | Sensible | 4940.96 | 4820.00 | 0.9755 | 0.36159601 | 0.305976 | 25.28 | 16.35 | 0.00814931 | 46169.7 | 12.80 | 11.43 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 342.726 | 4598.23 | 27.83 | 0.00822799 | 17.29 | 0.02595455 | 8.4825 | 24.03 | 0.00814202 | 24.00 | 0.00814202 | 43.0396 | 3555.10 | 0.00 | 5064.13 | 4011.36 | 0.34731570 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 15.38 | 14.55 | 0.00999621 | 40741.6 | |
| SPLIT GSW HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT GSW | G SW APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 7400.805 | 7400.805 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | SPLIT GSW SUPPLY FAN | Fan:OnOff | 0.305976 | 0.36159601 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 04:10:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 04:10:00 | Sensible | 7400.80 | 7400.80 | 1.0000 | 0.36159601 | 0.305976 | 19.63 | 13.44 | 0.00723471 | 38084.5 | 40.00 | 20.96 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 7400.80 | 3.80 | 0.00505843 | 3.80 | 0.02595455 | 8.4825 | 21.10 | 0.00743642 | 21.10 | 0.00743642 | 46.9351 | 989.95 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT GNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT GNW | G NW APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 4647.044 | 3720.680 | 0.280728 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.9477 | 1004.8586 | 1.1818 | SPLIT GNW SUPPLY FAN | Fan:OnOff | 0.280728 | 0.33175826 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | Sensible | 4532.00 | 4437.40 | 0.9752 | 0.33175826 | 0.280728 | 25.30 | 16.34 | 0.00812701 | 46132.9 | 12.80 | 11.43 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 314.446 | 4217.55 | 27.83 | 0.00822799 | 17.29 | 0.02595455 | 9.2454 | 24.02 | 0.00811672 | 24.00 | 0.00811672 | 42.9074 | 3269.22 | 0.00 | 4646.25 | 3680.36 | 0.31865632 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 15.38 | 14.55 | 0.00999621 | 40741.6 | |
| SPLIT GNW HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT GNW | G NW APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 6834.015 | 6834.015 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | SPLIT GNW SUPPLY FAN | Fan:OnOff | 0.280728 | 0.33175826 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 04:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 04:00:00 | Sensible | 6834.02 | 6834.02 | 1.0000 | 0.33175826 | 0.280728 | 19.50 | 13.57 | 0.00742487 | 38432.9 | 40.00 | 20.96 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 6834.02 | 3.80 | 0.00505843 | 3.80 | 0.02595455 | 9.2454 | 21.10 | 0.00766594 | 21.10 | 0.00766594 | 48.3652 | 863.28 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT OFFICE COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT OFFICE | OFFICE | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 5947.528 | 4761.920 | 0.359290 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7819 | 1004.8586 | 1.1818 | SPLIT OFFICE SUPPLY FAN | Fan:OnOff | 0.359290 | 0.42460147 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | Sensible | 5828.28 | 5791.12 | 0.9800 | 0.42460147 | 0.359290 | 25.14 | 16.20 | 0.00803781 | 45736.6 | 12.80 | 11.43 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 402.444 | 5425.84 | 26.41 | 0.00822575 | 16.80 | 0.03810604 | 10.6059 | 23.95 | 0.00801551 | 23.90 | 0.00801551 | 42.6342 | 4104.51 | 0.00 | 5946.52 | 4710.31 | 0.40783292 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 15.38 | 14.55 | 0.00999621 | 40741.6 | |
| SPLIT OFFICE HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT OFFICE | OFFICE | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 8846.952 | 8846.952 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | SPLIT OFFICE SUPPLY FAN | Fan:OnOff | 0.359290 | 0.42460147 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 18:50:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 18:50:00 | Sensible | 8846.95 | 8846.95 | 1.0000 | 0.42460147 | 0.359290 | 19.26 | 13.36 | 0.00730577 | 37891.0 | 40.00 | 20.96 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8846.95 | 3.80 | 0.00505843 | 3.80 | 0.03810604 | 10.6059 | 21.10 | 0.00757240 | 21.10 | 0.00757240 | 47.7823 | 1391.32 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT GNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT GNE | G NE APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 4333.985 | 3470.028 | 0.261816 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.9732 | 1004.8586 | 1.1818 | SPLIT GNE SUPPLY FAN | Fan:OnOff | 0.261816 | 0.30940857 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | Sensible | 4228.45 | 4131.00 | 0.9756 | 0.30940857 | 0.261816 | 25.32 | 16.36 | 0.00814072 | 46187.1 | 12.80 | 11.43 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 293.262 | 3935.19 | 27.83 | 0.00822799 | 17.29 | 0.02595455 | 9.9133 | 24.01 | 0.00813112 | 24.00 | 0.00813112 | 42.9825 | 3055.64 | 0.00 | 4333.25 | 3432.42 | 0.29718927 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 15.38 | 14.55 | 0.00999621 | 40741.6 | |
| SPLIT GNE HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT GNE | G NE APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 6409.546 | 6409.546 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | SPLIT GNE SUPPLY FAN | Fan:OnOff | 0.261816 | 0.30940857 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 04:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 04:00:00 | Sensible | 6409.55 | 6409.55 | 1.0000 | 0.30940857 | 0.261816 | 19.38 | 13.50 | 0.00740785 | 38272.0 | 40.00 | 20.96 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 6409.55 | 3.80 | 0.00505843 | 3.80 | 0.02595455 | 9.9133 | 21.10 | 0.00766638 | 21.10 | 0.00766638 | 48.3679 | 864.66 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT GN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT GN1 | G N1 APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 4086.350 | 3271.758 | 0.246856 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.9965 | 1004.8586 | 1.1818 | SPLIT GN1 SUPPLY FAN | Fan:OnOff | 0.246856 | 0.29172965 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | Sensible | 3988.30 | 3888.51 | 0.9760 | 0.29172965 | 0.246856 | 25.34 | 16.37 | 0.00815324 | 46234.7 | 12.80 | 11.43 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 276.506 | 3711.79 | 27.83 | 0.00822799 | 17.29 | 0.02595455 | 10.5140 | 24.01 | 0.00814446 | 24.00 | 0.00814446 | 43.0522 | 2885.93 | 0.00 | 4085.65 | 3236.30 | 0.28020854 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 15.38 | 14.55 | 0.00999621 | 40741.6 | |
| SPLIT GN1 HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT GN1 | G N1 APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 6073.722 | 6073.722 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | SPLIT GN1 SUPPLY FAN | Fan:OnOff | 0.246856 | 0.29172965 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 6073.72 | 6073.72 | 1.0000 | 0.29172965 | 0.246856 | 19.28 | 13.57 | 0.00751622 | 38441.3 | 40.00 | 20.96 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 6073.72 | 3.80 | 0.00505843 | 3.80 | 0.02595455 | 10.5140 | 21.10 | 0.00780499 | 21.10 | 0.00770504 | 48.6082 | 389.06 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT GN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT GN2 | G N2 APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 4079.161 | 3266.002 | 0.246422 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.9971 | 1004.8586 | 1.1818 | SPLIT GN2 SUPPLY FAN | Fan:OnOff | 0.246422 | 0.29121641 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | Sensible | 3981.32 | 3881.51 | 0.9760 | 0.29121641 | 0.246422 | 25.34 | 16.37 | 0.00815355 | 46235.9 | 12.80 | 11.43 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 276.019 | 3705.30 | 27.83 | 0.00822799 | 17.29 | 0.02595455 | 10.5326 | 24.01 | 0.00814479 | 24.00 | 0.00814479 | 43.0539 | 2881.01 | 0.00 | 4078.47 | 3230.60 | 0.27971556 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 15.38 | 14.55 | 0.00999621 | 40741.6 | |
| SPLIT GN2 HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT GN2 | G N2 APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 6063.974 | 6063.974 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | SPLIT GN2 SUPPLY FAN | Fan:OnOff | 0.246422 | 0.29121641 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 6063.97 | 6063.97 | 1.0000 | 0.29121641 | 0.246422 | 19.28 | 13.56 | 0.00751573 | 38436.8 | 40.00 | 20.96 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 6063.97 | 3.80 | 0.00505843 | 3.80 | 0.02595455 | 10.5326 | 21.10 | 0.00780501 | 21.10 | 0.00770508 | 48.6084 | 389.10 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT GS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT GS1 | G S1 APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 4487.956 | 3593.306 | 0.271117 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.0698 | 1004.8586 | 1.1818 | SPLIT GS1 SUPPLY FAN | Fan:OnOff | 0.271117 | 0.32040082 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | Sensible | 4382.73 | 4245.50 | 0.9766 | 0.32040082 | 0.271117 | 25.31 | 16.40 | 0.00819270 | 46309.5 | 12.80 | 11.43 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 303.681 | 4079.05 | 27.83 | 0.00822799 | 17.29 | 0.02595455 | 9.5732 | 24.02 | 0.00818896 | 24.00 | 0.00818896 | 43.2847 | 3160.99 | 0.00 | 4487.19 | 3554.36 | 0.30774741 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 15.38 | 14.55 | 0.00999621 | 40741.6 | |
| SPLIT GS1 HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT GS1 | G S1 APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 6618.336 | 6618.336 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | SPLIT GS1 SUPPLY FAN | Fan:OnOff | 0.271117 | 0.32040082 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 04:10:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 04:10:00 | Sensible | 6618.34 | 6618.34 | 1.0000 | 0.32040082 | 0.271117 | 19.44 | 13.30 | 0.00716653 | 37719.7 | 40.00 | 20.96 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 6618.34 | 3.80 | 0.00505843 | 3.80 | 0.02595455 | 9.5732 | 21.10 | 0.00738971 | 21.10 | 0.00738971 | 46.6431 | 562.33 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT GS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT GS2 | G S2 APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 4520.797 | 3619.600 | 0.273101 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.0684 | 1004.8586 | 1.1818 | SPLIT GS2 SUPPLY FAN | Fan:OnOff | 0.273101 | 0.32274537 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | Sensible | 4414.66 | 4276.93 | 0.9765 | 0.32274537 | 0.273101 | 25.31 | 16.40 | 0.00819195 | 46305.4 | 12.80 | 11.43 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 305.903 | 4108.76 | 27.83 | 0.00822799 | 17.29 | 0.02595455 | 9.5036 | 24.02 | 0.00818816 | 24.00 | 0.00818816 | 43.2805 | 3183.29 | 0.00 | 4520.03 | 3580.37 | 0.30999937 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 15.38 | 14.55 | 0.00999621 | 40741.6 | |
| SPLIT GS2 HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT GS2 | G S2 APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 6662.865 | 6662.865 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | SPLIT GS2 SUPPLY FAN | Fan:OnOff | 0.273101 | 0.32274537 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 04:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 04:00:00 | Sensible | 6662.86 | 6662.86 | 1.0000 | 0.32274537 | 0.273101 | 19.46 | 13.31 | 0.00717425 | 37751.5 | 40.00 | 20.96 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 6662.86 | 3.80 | 0.00505843 | 3.80 | 0.02595455 | 9.5036 | 21.10 | 0.00739644 | 21.10 | 0.00739644 | 46.6851 | 570.71 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT MSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT MSW | M SW APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 12546.584 | 10045.489 | 0.757939 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.9219 | 1004.8586 | 1.1818 | SPLIT MSW SUPPLY FAN | Fan:OnOff | 0.757939 | 0.89571633 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | Sensible | 12226.18 | 11997.38 | 0.9745 | 0.89571633 | 0.757939 | 25.24 | 16.30 | 0.00811312 | 46029.7 | 12.80 | 11.43 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 848.974 | 11377.21 | 27.83 | 0.00822799 | 17.29 | 0.05190911 | 6.8487 | 24.05 | 0.00810468 | 24.00 | 0.00810468 | 42.8446 | 17523.34 | 0.00 | 12544.45 | 9936.62 | 0.86034231 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 15.38 | 14.55 | 0.00999621 | 40741.6 | |
| SPLIT MSW HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT MSW | M SW APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 18078.421 | 18078.421 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | SPLIT MSW SUPPLY FAN | Fan:OnOff | 0.757939 | 0.89571633 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | Sensible | 18078.42 | 18078.42 | 1.0000 | 0.89571633 | 0.757939 | 19.91 | 13.40 | 0.00707695 | 37971.8 | 40.00 | 20.96 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 18078.42 | 3.80 | 0.00505843 | 3.80 | 0.05190911 | 6.8487 | 21.10 | 0.00722535 | 21.10 | 0.00722535 | 45.6187 | 3774.92 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT MNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT MNW | M NW APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 11776.069 | 9428.571 | 0.711392 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.9003 | 1004.8586 | 1.1818 | SPLIT MNW SUPPLY FAN | Fan:OnOff | 0.711392 | 0.84070824 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | Sensible | 11474.04 | 11281.13 | 0.9744 | 0.84070824 | 0.711392 | 25.25 | 16.30 | 0.00810153 | 46014.4 | 12.80 | 11.43 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 796.836 | 10677.21 | 27.83 | 0.00822799 | 17.29 | 0.05190911 | 7.2968 | 24.05 | 0.00809157 | 24.00 | 0.00809157 | 42.7761 | 16472.42 | 0.00 | 11774.06 | 9326.38 | 0.80750662 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 15.38 | 14.55 | 0.00999621 | 40741.6 | |
| SPLIT MNW HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT MNW | M NW APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 17033.446 | 17033.446 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | SPLIT MNW SUPPLY FAN | Fan:OnOff | 0.711392 | 0.84070824 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | Sensible | 17033.45 | 17033.45 | 1.0000 | 0.84070824 | 0.711392 | 19.84 | 13.52 | 0.00724196 | 38311.9 | 40.00 | 20.96 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 17033.45 | 3.80 | 0.00505843 | 3.80 | 0.05190911 | 7.2968 | 21.10 | 0.00741383 | 21.10 | 0.00741383 | 46.7939 | 3208.57 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT MSE COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT MSE | M SE APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 11688.213 | 9358.229 | 0.706085 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.9472 | 1004.8586 | 1.1818 | SPLIT MSE SUPPLY FAN | Fan:OnOff | 0.706085 | 0.83443613 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | Sensible | 11394.09 | 11155.99 | 0.9748 | 0.83443613 | 0.706085 | 25.25 | 16.32 | 0.00812672 | 46079.5 | 12.80 | 11.43 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 790.891 | 10603.20 | 27.83 | 0.00822799 | 17.29 | 0.05190911 | 7.3517 | 24.04 | 0.00811868 | 24.00 | 0.00811868 | 42.9177 | 16351.94 | 0.00 | 11686.22 | 9256.80 | 0.80148221 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 15.38 | 14.55 | 0.00999621 | 40741.6 | |
| SPLIT MSE HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT MSE | M SE APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 16914.547 | 16914.547 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | SPLIT MSE SUPPLY FAN | Fan:OnOff | 0.706085 | 0.83443613 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | Sensible | 16914.55 | 16914.55 | 1.0000 | 0.83443613 | 0.706085 | 19.83 | 13.35 | 0.00706706 | 37858.1 | 40.00 | 20.96 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 16914.55 | 3.80 | 0.00505843 | 3.80 | 0.05190911 | 7.3517 | 21.10 | 0.00722645 | 21.10 | 0.00722645 | 45.6256 | 3781.95 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT MNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT MNE | M NE APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 10927.693 | 8749.315 | 0.660142 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.9191 | 1004.8586 | 1.1818 | SPLIT MNE SUPPLY FAN | Fan:OnOff | 0.660142 | 0.78014166 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | Sensible | 10650.97 | 10454.63 | 0.9747 | 0.78014166 | 0.660142 | 25.27 | 16.31 | 0.00811163 | 46057.6 | 12.80 | 11.43 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 739.430 | 9911.54 | 27.83 | 0.00822799 | 17.29 | 0.05190911 | 7.8633 | 24.04 | 0.00810170 | 24.00 | 0.00810170 | 42.8289 | 15317.10 | 0.00 | 10925.83 | 8654.49 | 0.74933196 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 15.38 | 14.55 | 0.00999621 | 40741.6 | |
| SPLIT MNE HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT MNE | M NE APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 15883.143 | 15883.143 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | SPLIT MNE SUPPLY FAN | Fan:OnOff | 0.660142 | 0.78014166 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | Sensible | 15883.14 | 15883.14 | 1.0000 | 0.78014166 | 0.660142 | 19.74 | 13.47 | 0.00722951 | 38180.5 | 40.00 | 20.96 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 15883.14 | 3.80 | 0.00505843 | 3.80 | 0.05190911 | 7.8633 | 21.10 | 0.00741480 | 21.10 | 0.00741480 | 46.7999 | 3215.85 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT MN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT MN1 | M N1 APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 10027.019 | 8028.186 | 0.605732 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.9396 | 1004.8586 | 1.1818 | SPLIT MN1 SUPPLY FAN | Fan:OnOff | 0.605732 | 0.71584143 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | Sensible | 9776.57 | 9579.16 | 0.9750 | 0.71584143 | 0.605732 | 25.29 | 16.33 | 0.00812264 | 46103.7 | 12.80 | 11.43 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 678.485 | 9098.09 | 27.83 | 0.00822799 | 17.29 | 0.05190911 | 8.5696 | 24.03 | 0.00811277 | 24.00 | 0.00811277 | 42.8867 | 14078.34 | 0.00 | 10025.31 | 7941.18 | 0.68757111 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 15.38 | 14.55 | 0.00999621 | 40741.6 | |
| SPLIT MN1 HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT MN1 | M N1 APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 14661.728 | 14661.728 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | SPLIT MN1 SUPPLY FAN | Fan:OnOff | 0.605732 | 0.71584143 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 17:00:00 | Sensible | 14661.73 | 14661.73 | 1.0000 | 0.71584143 | 0.605732 | 19.62 | 13.41 | 0.00721548 | 38020.8 | 40.00 | 20.96 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 14661.73 | 3.80 | 0.00505843 | 3.80 | 0.05190911 | 8.5696 | 21.10 | 0.00741766 | 21.10 | 0.00718520 | 45.3666 | 1049.54 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT MN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT MN2 | M N2 APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 10009.701 | 8014.320 | 0.604686 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.9401 | 1004.8586 | 1.1818 | SPLIT MN2 SUPPLY FAN | Fan:OnOff | 0.604686 | 0.71460509 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | Sensible | 9759.76 | 9562.29 | 0.9750 | 0.71460509 | 0.604686 | 25.29 | 16.33 | 0.00812290 | 46104.7 | 12.80 | 11.43 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 677.314 | 9082.45 | 27.83 | 0.00822799 | 17.29 | 0.05190911 | 8.5845 | 24.03 | 0.00811303 | 24.00 | 0.00811303 | 42.8881 | 14054.58 | 0.00 | 10008.00 | 7927.46 | 0.68638359 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 15.38 | 14.55 | 0.00999621 | 40741.6 | |
| SPLIT MN2 HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT MN2 | M N2 APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 14638.248 | 14638.248 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | SPLIT MN2 SUPPLY FAN | Fan:OnOff | 0.604686 | 0.71460509 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 17:20:00 | Sensible | 14638.25 | 14638.25 | 1.0000 | 0.71460509 | 0.604686 | 19.61 | 13.41 | 0.00721520 | 38017.5 | 40.00 | 20.96 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 14638.25 | 3.80 | 0.00505843 | 3.80 | 0.05190911 | 8.5845 | 21.10 | 0.00741773 | 21.10 | 0.00718531 | 45.3672 | 1049.73 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT MS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT MS1 | M S1 APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 10882.137 | 8712.840 | 0.657390 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.9782 | 1004.8586 | 1.1818 | SPLIT MS1 SUPPLY FAN | Fan:OnOff | 0.657390 | 0.77688935 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | Sensible | 10613.14 | 10363.14 | 0.9753 | 0.77688935 | 0.657390 | 25.27 | 16.34 | 0.00814340 | 46139.0 | 12.80 | 11.43 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 736.348 | 9876.80 | 27.83 | 0.00822799 | 17.29 | 0.05190911 | 7.8962 | 24.04 | 0.00813614 | 24.00 | 0.00813614 | 43.0089 | 15253.95 | 0.00 | 10880.28 | 8618.41 | 0.74620809 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 15.38 | 14.55 | 0.00999621 | 40741.6 | |
| SPLIT MS1 HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT MS1 | M S1 APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 15821.362 | 15821.362 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | SPLIT MS1 SUPPLY FAN | Fan:OnOff | 0.657390 | 0.77688935 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 15821.36 | 15821.36 | 1.0000 | 0.77688935 | 0.657390 | 19.73 | 13.16 | 0.00690625 | 37354.4 | 40.00 | 20.96 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 15821.36 | 3.80 | 0.00505843 | 3.80 | 0.05190911 | 7.8962 | 21.10 | 0.00706467 | 21.10 | 0.00686723 | 43.3815 | 1546.55 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT MS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT MS2 | M S2 APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 10863.623 | 8698.017 | 0.656271 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.9789 | 1004.8586 | 1.1818 | SPLIT MS2 SUPPLY FAN | Fan:OnOff | 0.656271 | 0.77556760 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | Sensible | 10595.20 | 10344.93 | 0.9753 | 0.77556760 | 0.656271 | 25.27 | 16.34 | 0.00814380 | 46140.4 | 12.80 | 11.43 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 735.095 | 9860.10 | 27.83 | 0.00822799 | 17.29 | 0.05190911 | 7.9097 | 24.04 | 0.00813657 | 24.00 | 0.00813657 | 43.0111 | 15228.40 | 0.00 | 10861.77 | 8603.75 | 0.74493854 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 15.38 | 14.55 | 0.00999621 | 40741.6 | |
| SPLIT MS2 HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT MS2 | M S2 APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 15796.259 | 15796.259 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | SPLIT MS2 SUPPLY FAN | Fan:OnOff | 0.656271 | 0.77556760 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 15796.26 | 15796.26 | 1.0000 | 0.77556760 | 0.656271 | 19.73 | 13.16 | 0.00690605 | 37351.5 | 40.00 | 20.96 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 15796.26 | 3.80 | 0.00505843 | 3.80 | 0.05190911 | 7.9097 | 21.10 | 0.00706474 | 21.10 | 0.00686733 | 43.3821 | 1546.73 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT TSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT TSW | T SW APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 6665.582 | 5336.833 | 0.402668 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.9062 | 1004.8586 | 1.1818 | SPLIT TSW SUPPLY FAN | Fan:OnOff | 0.402668 | 0.47586424 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | Sensible | 6493.95 | 6381.25 | 0.9743 | 0.47586424 | 0.402668 | 25.23 | 16.29 | 0.00810471 | 46001.3 | 12.80 | 11.43 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 451.031 | 6042.91 | 27.83 | 0.00822799 | 17.29 | 0.02595455 | 6.4456 | 24.06 | 0.00809622 | 24.00 | 0.00809622 | 42.8004 | 4652.43 | 0.00 | 6664.45 | 5278.99 | 0.45707120 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 15.38 | 14.55 | 0.00999621 | 40741.6 | |
| SPLIT TSW HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT TSW | T SW APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 9571.272 | 9571.272 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | SPLIT TSW SUPPLY FAN | Fan:OnOff | 0.402668 | 0.47586424 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | Sensible | 9571.27 | 9571.27 | 1.0000 | 0.47586424 | 0.402668 | 19.98 | 13.60 | 0.00726820 | 38527.9 | 40.00 | 20.96 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9571.27 | 3.80 | 0.00505843 | 3.80 | 0.02595455 | 6.4456 | 21.10 | 0.00742044 | 21.10 | 0.00742044 | 46.8369 | 1803.47 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT TNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT TNW | T NW APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 6365.697 | 5096.728 | 0.384552 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.8890 | 1004.8586 | 1.1818 | SPLIT TNW SUPPLY FAN | Fan:OnOff | 0.384552 | 0.45445503 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | Sensible | 6201.11 | 6102.92 | 0.9741 | 0.45445503 | 0.384552 | 25.24 | 16.29 | 0.00809545 | 45986.8 | 12.80 | 11.43 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 430.739 | 5770.37 | 27.83 | 0.00822799 | 17.29 | 0.02595455 | 6.7493 | 24.05 | 0.00808586 | 24.00 | 0.00808586 | 42.7462 | 4446.81 | 0.00 | 6364.61 | 5041.49 | 0.43650749 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 15.38 | 14.55 | 0.00999621 | 40741.6 | |
| SPLIT TNW HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT TNW | T NW APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 9164.519 | 9164.519 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | SPLIT TNW SUPPLY FAN | Fan:OnOff | 0.384552 | 0.45445503 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | Sensible | 9164.52 | 9164.52 | 1.0000 | 0.45445503 | 0.384552 | 19.93 | 13.68 | 0.00736563 | 38721.9 | 40.00 | 20.96 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9164.52 | 3.80 | 0.00505843 | 3.80 | 0.02595455 | 6.7493 | 21.10 | 0.00753262 | 21.10 | 0.00753262 | 47.5356 | 1651.28 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT TSE COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT TSE | T SE APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 6006.395 | 4809.051 | 0.362846 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.9318 | 1004.8586 | 1.1818 | SPLIT TSE SUPPLY FAN | Fan:OnOff | 0.362846 | 0.42880401 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | Sensible | 5854.25 | 5739.73 | 0.9747 | 0.42880401 | 0.362846 | 25.25 | 16.31 | 0.00811845 | 46057.1 | 12.80 | 11.43 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 406.427 | 5447.82 | 27.83 | 0.00822799 | 17.29 | 0.02595455 | 7.1530 | 24.05 | 0.00811001 | 24.00 | 0.00811001 | 42.8724 | 4200.44 | 0.00 | 6005.37 | 4756.93 | 0.41186949 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 15.38 | 14.55 | 0.00999621 | 40741.6 | |
| SPLIT TSE HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT TSE | T SE APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 8677.457 | 8677.457 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | SPLIT TSE SUPPLY FAN | Fan:OnOff | 0.362846 | 0.42880401 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | Sensible | 8677.46 | 8677.46 | 1.0000 | 0.42880401 | 0.362846 | 19.86 | 13.54 | 0.00725197 | 38362.0 | 40.00 | 20.96 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8677.46 | 3.80 | 0.00505843 | 3.80 | 0.02595455 | 7.1530 | 21.10 | 0.00742096 | 21.10 | 0.00742096 | 46.8402 | 1805.46 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT TNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT TNE | T NE APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 5706.491 | 4568.932 | 0.344729 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.9099 | 1004.8586 | 1.1818 | SPLIT TNE SUPPLY FAN | Fan:OnOff | 0.344729 | 0.40739350 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | Sensible | 5561.19 | 5463.10 | 0.9745 | 0.40739350 | 0.344729 | 25.26 | 16.31 | 0.00810668 | 46039.1 | 12.80 | 11.43 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 386.134 | 5175.06 | 27.83 | 0.00822799 | 17.29 | 0.02595455 | 7.5290 | 24.05 | 0.00809681 | 24.00 | 0.00809681 | 42.8034 | 3995.61 | 0.00 | 5705.52 | 4519.41 | 0.39130453 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 15.38 | 14.55 | 0.00999621 | 40741.6 | |
| SPLIT TNE HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT TNE | T NE APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 8270.693 | 8270.693 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | SPLIT TNE SUPPLY FAN | Fan:OnOff | 0.344729 | 0.40739350 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | Sensible | 8270.69 | 8270.69 | 1.0000 | 0.40739350 | 0.344729 | 19.80 | 13.61 | 0.00734677 | 38536.7 | 40.00 | 20.96 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8270.69 | 3.80 | 0.00505843 | 3.80 | 0.02595455 | 7.5290 | 21.10 | 0.00753309 | 21.10 | 0.00753309 | 47.5385 | 1653.38 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT TN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT TN1 | T N1 APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 5413.631 | 4334.452 | 0.327037 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.9134 | 1004.8586 | 1.1818 | SPLIT TN1 SUPPLY FAN | Fan:OnOff | 0.327037 | 0.38648586 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | Sensible | 5276.53 | 5181.93 | 0.9747 | 0.38648586 | 0.327037 | 25.27 | 16.31 | 0.00810857 | 46057.1 | 12.80 | 11.43 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 366.317 | 4910.21 | 27.83 | 0.00822799 | 17.29 | 0.02595455 | 7.9363 | 24.05 | 0.00809827 | 24.00 | 0.00809827 | 42.8110 | 3795.90 | 0.00 | 5412.71 | 4287.47 | 0.37122259 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 15.38 | 14.55 | 0.00999621 | 40741.6 | |
| SPLIT TN1 HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT TN1 | T N1 APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 7873.444 | 7873.444 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | SPLIT TN1 SUPPLY FAN | Fan:OnOff | 0.327037 | 0.38648586 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | Sensible | 7873.44 | 7873.44 | 1.0000 | 0.38648586 | 0.327037 | 19.73 | 13.68 | 0.00745191 | 38732.1 | 40.00 | 20.96 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 7873.44 | 3.80 | 0.00505843 | 3.80 | 0.02595455 | 7.9363 | 21.10 | 0.00765824 | 21.10 | 0.00765824 | 48.3174 | 1091.82 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT TN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT TN2 | T N2 APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 5388.574 | 4314.391 | 0.325524 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.9144 | 1004.8586 | 1.1818 | SPLIT TN2 SUPPLY FAN | Fan:OnOff | 0.325524 | 0.38469706 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | Sensible | 5252.21 | 5157.59 | 0.9747 | 0.38469706 | 0.325524 | 25.28 | 16.31 | 0.00810911 | 46059.7 | 12.80 | 11.43 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 364.622 | 4887.59 | 27.83 | 0.00822799 | 17.29 | 0.02595455 | 7.9732 | 24.04 | 0.00809881 | 24.00 | 0.00809881 | 42.8138 | 3778.83 | 0.00 | 5387.66 | 4267.63 | 0.36950444 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 15.38 | 14.55 | 0.00999621 | 40741.6 | |
| SPLIT TN2 HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT TN2 | T N2 APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 7839.471 | 7839.471 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | SPLIT TN2 SUPPLY FAN | Fan:OnOff | 0.325524 | 0.38469706 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | Sensible | 7839.47 | 7839.47 | 1.0000 | 0.38469706 | 0.325524 | 19.72 | 13.67 | 0.00745097 | 38723.2 | 40.00 | 20.96 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 7839.47 | 3.80 | 0.00505843 | 3.80 | 0.02595455 | 7.9732 | 21.10 | 0.00765825 | 21.10 | 0.00765825 | 48.3175 | 1091.88 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT TS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT TS1 | T S1 APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 5736.945 | 4593.315 | 0.346569 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.9404 | 1004.8586 | 1.1818 | SPLIT TS1 SUPPLY FAN | Fan:OnOff | 0.346569 | 0.40956764 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | Sensible | 5592.59 | 5479.10 | 0.9748 | 0.40956764 | 0.346569 | 25.26 | 16.32 | 0.00812305 | 46079.4 | 12.80 | 11.43 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 388.194 | 5204.39 | 27.83 | 0.00822799 | 17.29 | 0.02595455 | 7.4890 | 24.05 | 0.00811456 | 24.00 | 0.00811456 | 42.8962 | 4016.36 | 0.00 | 5735.97 | 4543.53 | 0.39339281 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 15.38 | 14.55 | 0.00999621 | 40741.6 | |
| SPLIT TS1 HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT TS1 | T S1 APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 8311.939 | 8311.939 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | SPLIT TS1 SUPPLY FAN | Fan:OnOff | 0.346569 | 0.40956764 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | Sensible | 8311.94 | 8311.94 | 1.0000 | 0.40956764 | 0.346569 | 19.80 | 13.56 | 0.00729756 | 38419.0 | 40.00 | 20.96 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8311.94 | 3.80 | 0.00505843 | 3.80 | 0.02595455 | 7.4890 | 21.10 | 0.00747883 | 21.10 | 0.00747883 | 47.1998 | 1245.05 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT TS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT TS2 | T S2 APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 5711.907 | 4573.268 | 0.345056 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.9417 | 1004.8586 | 1.1818 | SPLIT TS2 SUPPLY FAN | Fan:OnOff | 0.345056 | 0.40778015 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | Sensible | 5568.30 | 5454.69 | 0.9749 | 0.40778015 | 0.345056 | 25.26 | 16.32 | 0.00812375 | 46082.3 | 12.80 | 11.43 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 386.500 | 5181.80 | 27.83 | 0.00822799 | 17.29 | 0.02595455 | 7.5218 | 24.05 | 0.00811528 | 24.00 | 0.00811528 | 42.8999 | 3999.27 | 0.00 | 5710.93 | 4523.70 | 0.39167592 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 15.38 | 14.55 | 0.00999621 | 40741.6 | |
| SPLIT TS2 HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT TS2 | T S2 APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 8277.990 | 8277.990 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | SPLIT TS2 SUPPLY FAN | Fan:OnOff | 0.345056 | 0.40778015 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | Sensible | 8277.99 | 8277.99 | 1.0000 | 0.40778015 | 0.345056 | 19.80 | 13.56 | 0.00729679 | 38411.2 | 40.00 | 20.96 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8277.99 | 3.80 | 0.00505843 | 3.80 | 0.02595455 | 7.5218 | 21.10 | 0.00747885 | 21.10 | 0.00747885 | 47.2000 | 1245.11 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 09:15:25
Economizer| High Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
| None |
| Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
| None |
| Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
| G SW APARTMENT | 1449.33 | 3512.33 | 116.17 |
| G NW APARTMENT | 1881.67 | 5860.17 | 287.17 |
| OFFICE | 805.00 | 381.50 | 14.33 |
| G NE APARTMENT | 1787.67 | 6056.83 | 316.17 |
| G N1 APARTMENT | 1796.00 | 5561.50 | 132.00 |
| G N2 APARTMENT | 1789.33 | 5577.83 | 133.50 |
| G S1 APARTMENT | 1525.67 | 2899.17 | 59.33 |
| G S2 APARTMENT | 1611.83 | 2766.67 | 35.17 |
| M SW APARTMENT | 1894.17 | 2232.33 | 19.83 |
| M NW APARTMENT | 2454.83 | 4300.83 | 49.50 |
| M SE APARTMENT | 1823.33 | 2261.00 | 22.67 |
| M NE APARTMENT | 2400.67 | 4308.67 | 48.83 |
| M N1 APARTMENT | 2250.83 | 3733.33 | 24.33 |
| M N2 APARTMENT | 2245.00 | 3729.33 | 24.67 |
| M S1 APARTMENT | 1873.00 | 1580.00 | 11.00 |
| M S2 APARTMENT | 1872.00 | 1581.33 | 11.17 |
| T SW APARTMENT | 1710.50 | 4154.83 | 526.00 |
| T NW APARTMENT | 2691.33 | 6115.00 | 867.17 |
| T SE APARTMENT | 1645.50 | 4295.83 | 561.67 |
| T NE APARTMENT | 2609.33 | 6199.00 | 853.83 |
| T N1 APARTMENT | 2358.83 | 5979.17 | 632.33 |
| T N2 APARTMENT | 2360.17 | 5990.33 | 635.83 |
| T S1 APARTMENT | 1572.83 | 3847.33 | 347.50 |
| T S2 APARTMENT | 1570.33 | 3862.33 | 351.33 |
| T CORRIDOR | 7746.17 | 8596.67 | 7672.33 |
| G CORRIDOR | 3708.00 | 6424.17 | 2096.33 |
| M CORRIDOR | 8742.17 | 8656.83 | 8645.50 |
| Facility | 8752.67 | 8760.00 | 8675.00 |
| During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
| G SW APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| G NW APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| OFFICE | 0.00 | 0.00 | 0.00 | 0.00 |
| G NE APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| G N1 APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| G N2 APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| G S1 APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| G S2 APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| M SW APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| M NW APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| M SE APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| M NE APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| M N1 APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| M N2 APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| M S1 APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| M S2 APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| T SW APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| T NW APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| T SE APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| T NE APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| T N1 APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| T N2 APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| T S1 APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| T S2 APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| T CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
| G CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
| M CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
| Facility | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 09:15:25
Average Outdoor Air During Occupied Hours| Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
| G SW APARTMENT | 2.40 | 2.50 | 268.97 | 0.355 | 0.096 | 0.000 | 0.095 |
| G NW APARTMENT | 1.71 | 2.50 | 268.97 | 0.355 | 0.115 | 0.000 | 0.135 |
| OFFICE | 4.75 | 4.75 | 268.97 | 0.522 | 0.149 | 0.000 | 0.000 |
| G NE APARTMENT | 1.71 | 2.50 | 268.97 | 0.355 | 0.115 | 0.000 | 0.135 |
| G N1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.355 | 0.069 | 0.000 | 0.136 |
| G N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.355 | 0.069 | 0.000 | 0.136 |
| G S1 APARTMENT | 2.40 | 2.50 | 268.97 | 0.356 | 0.058 | 0.000 | 0.096 |
| G S2 APARTMENT | 2.40 | 2.50 | 268.97 | 0.356 | 0.058 | 0.000 | 0.096 |
| M SW APARTMENT | 2.40 | 2.50 | 268.97 | 0.356 | 0.138 | 0.000 | 0.106 |
| M NW APARTMENT | 1.71 | 2.50 | 268.97 | 0.355 | 0.165 | 0.000 | 0.159 |
| M SE APARTMENT | 2.40 | 2.50 | 268.97 | 0.356 | 0.138 | 0.000 | 0.107 |
| M NE APARTMENT | 1.71 | 2.50 | 268.97 | 0.355 | 0.165 | 0.000 | 0.159 |
| M N1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.355 | 0.100 | 0.000 | 0.160 |
| M N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.355 | 0.100 | 0.000 | 0.160 |
| M S1 APARTMENT | 2.40 | 2.50 | 268.97 | 0.356 | 0.083 | 0.000 | 0.107 |
| M S2 APARTMENT | 2.40 | 2.50 | 268.97 | 0.356 | 0.083 | 0.000 | 0.107 |
| T SW APARTMENT | 2.40 | 2.50 | 268.97 | 0.355 | 0.182 | 0.000 | 0.117 |
| T NW APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.218 | 0.000 | 0.178 |
| T SE APARTMENT | 2.40 | 2.50 | 268.97 | 0.355 | 0.182 | 0.000 | 0.117 |
| T NE APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.218 | 0.000 | 0.179 |
| T N1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.131 | 0.000 | 0.179 |
| T N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.131 | 0.000 | 0.179 |
| T S1 APARTMENT | 2.40 | 2.50 | 268.97 | 0.355 | 0.110 | 0.000 | 0.118 |
| T S2 APARTMENT | 2.40 | 2.50 | 268.97 | 0.355 | 0.110 | 0.000 | 0.118 |
| Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
| G SW APARTMENT | 2.40 | 2.50 | 268.97 | 0.345 | 0.000 | 0.000 | 0.000 |
| G NW APARTMENT | 1.71 | 2.50 | 268.97 | 0.344 | 0.000 | 0.000 | 0.000 |
| OFFICE | 4.75 | 4.75 | 268.97 | 0.505 | 0.000 | 0.000 | 0.000 |
| G NE APARTMENT | 1.71 | 2.50 | 268.97 | 0.344 | 0.000 | 0.000 | 0.000 |
| G N1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.344 | 0.000 | 0.000 | 0.000 |
| G N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.344 | 0.000 | 0.000 | 0.000 |
| G S1 APARTMENT | 2.40 | 2.50 | 268.97 | 0.345 | 0.000 | 0.000 | 0.000 |
| G S2 APARTMENT | 2.40 | 2.50 | 268.97 | 0.345 | 0.000 | 0.000 | 0.000 |
| M SW APARTMENT | 2.40 | 2.50 | 268.97 | 0.345 | 0.000 | 0.000 | 0.000 |
| M NW APARTMENT | 1.71 | 2.50 | 268.97 | 0.344 | 0.000 | 0.000 | 0.000 |
| M SE APARTMENT | 2.40 | 2.50 | 268.97 | 0.345 | 0.000 | 0.000 | 0.000 |
| M NE APARTMENT | 1.71 | 2.50 | 268.97 | 0.344 | 0.000 | 0.000 | 0.000 |
| M N1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.345 | 0.000 | 0.000 | 0.000 |
| M N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.345 | 0.000 | 0.000 | 0.000 |
| M S1 APARTMENT | 2.40 | 2.50 | 268.97 | 0.346 | 0.000 | 0.000 | 0.000 |
| M S2 APARTMENT | 2.40 | 2.50 | 268.97 | 0.346 | 0.000 | 0.000 | 0.000 |
| T SW APARTMENT | 2.40 | 2.50 | 268.97 | 0.344 | 0.000 | 0.000 | 0.000 |
| T NW APARTMENT | 1.71 | 2.50 | 268.97 | 0.344 | 0.000 | 0.000 | 0.000 |
| T SE APARTMENT | 2.40 | 2.50 | 268.97 | 0.344 | 0.000 | 0.000 | 0.000 |
| T NE APARTMENT | 1.71 | 2.50 | 268.97 | 0.344 | 0.000 | 0.000 | 0.000 |
| T N1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.344 | 0.000 | 0.000 | 0.000 |
| T N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.344 | 0.000 | 0.000 | 0.000 |
| T S1 APARTMENT | 2.40 | 2.50 | 268.97 | 0.344 | 0.000 | 0.000 | 0.000 |
| T S2 APARTMENT | 2.40 | 2.50 | 268.97 | 0.344 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 09:15:25
Mechanical Ventilation Parameters by Zone| AirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
| G SW APARTMENT | SPLIT GSW | 2.40 | 2.50 | 268.97 | 88.25 | 0.0260 | 0.026 |
| G NW APARTMENT | SPLIT GNW | 1.71 | 2.50 | 268.97 | 88.25 | 0.0260 | 0.026 |
| OFFICE | SPLIT OFFICE | 4.75 | 4.75 | 268.97 | 88.25 | 0.0381 | 0.038 |
| G NE APARTMENT | SPLIT GNE | 1.71 | 2.50 | 268.97 | 88.25 | 0.0260 | 0.026 |
| G N1 APARTMENT | SPLIT GN1 | 1.71 | 2.50 | 268.97 | 88.25 | 0.0260 | 0.026 |
| G N2 APARTMENT | SPLIT GN2 | 1.71 | 2.50 | 268.97 | 88.25 | 0.0260 | 0.026 |
| G S1 APARTMENT | SPLIT GS1 | 2.40 | 2.50 | 268.97 | 88.25 | 0.0260 | 0.026 |
| G S2 APARTMENT | SPLIT GS2 | 2.40 | 2.50 | 268.97 | 88.25 | 0.0260 | 0.026 |
| M SW APARTMENT | SPLIT MSW | 2.40 | 2.50 | 268.97 | 88.25 | 0.0519 | 0.052 |
| M NW APARTMENT | SPLIT MNW | 1.71 | 2.50 | 268.97 | 88.25 | 0.0519 | 0.052 |
| M SE APARTMENT | SPLIT MSE | 2.40 | 2.50 | 268.97 | 88.25 | 0.0519 | 0.052 |
| M NE APARTMENT | SPLIT MNE | 1.71 | 2.50 | 268.97 | 88.25 | 0.0519 | 0.052 |
| M N1 APARTMENT | SPLIT MN1 | 1.71 | 2.50 | 268.97 | 88.25 | 0.0519 | 0.052 |
| M N2 APARTMENT | SPLIT MN2 | 1.71 | 2.50 | 268.97 | 88.25 | 0.0519 | 0.052 |
| M S1 APARTMENT | SPLIT MS1 | 2.40 | 2.50 | 268.97 | 88.25 | 0.0519 | 0.052 |
| M S2 APARTMENT | SPLIT MS2 | 2.40 | 2.50 | 268.97 | 88.25 | 0.0519 | 0.052 |
| T SW APARTMENT | SPLIT TSW | 2.40 | 2.50 | 268.97 | 88.25 | 0.0260 | 0.026 |
| T NW APARTMENT | SPLIT TNW | 1.71 | 2.50 | 268.97 | 88.25 | 0.0260 | 0.026 |
| T SE APARTMENT | SPLIT TSE | 2.40 | 2.50 | 268.97 | 88.25 | 0.0260 | 0.026 |
| T NE APARTMENT | SPLIT TNE | 1.71 | 2.50 | 268.97 | 88.25 | 0.0260 | 0.026 |
| T N1 APARTMENT | SPLIT TN1 | 1.71 | 2.50 | 268.97 | 88.25 | 0.0260 | 0.026 |
| T N2 APARTMENT | SPLIT TN2 | 1.71 | 2.50 | 268.97 | 88.25 | 0.0260 | 0.026 |
| T S1 APARTMENT | SPLIT TS1 | 2.40 | 2.50 | 268.97 | 88.25 | 0.0260 | 0.026 |
| T S2 APARTMENT | SPLIT TS2 | 2.40 | 2.50 | 268.97 | 88.25 | 0.0260 | 0.026 |
| Total Facility | 68.18 | 82.25 | 8607.06 | 2823.98 | 0.8427 | 1.258 |
| Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
| G SW APARTMENT | 818502.78 | 323257.81 | 1141760.59 | 264736.02 | 1406496.61 | 818502.78 | 0.00 | 5206.50 | 3553.50 | 2615.00 |
| G NW APARTMENT | 818502.78 | 311263.82 | 1129766.60 | 264736.02 | 1394502.62 | 818502.78 | 0.00 | 5206.50 | 3553.50 | 0.00 |
| OFFICE | 1201711.97 | 0.00 | 1201711.97 | 264736.02 | 1466447.99 | 1201711.97 | 0.00 | 8760.00 | 0.00 | 7010.00 |
| G NE APARTMENT | 818502.78 | 312029.38 | 1130532.15 | 264736.02 | 1395268.18 | 818502.78 | 0.00 | 5206.50 | 3553.50 | 0.00 |
| G N1 APARTMENT | 818502.78 | 313972.81 | 1132475.59 | 159682.05 | 1292157.63 | 818502.78 | 0.00 | 5206.50 | 3553.50 | 0.00 |
| G N2 APARTMENT | 818502.78 | 313983.38 | 1132486.15 | 159682.05 | 1292168.20 | 818502.78 | 0.00 | 5206.50 | 3553.50 | 0.00 |
| G S1 APARTMENT | 818502.78 | 325466.38 | 1143969.15 | 159682.05 | 1303651.20 | 818502.78 | 0.00 | 5206.50 | 3553.50 | 2615.00 |
| G S2 APARTMENT | 818502.78 | 325845.97 | 1144348.75 | 159682.05 | 1304030.80 | 818502.78 | 0.00 | 5206.50 | 3553.50 | 2615.00 |
| M SW APARTMENT | 1637005.55 | 373010.77 | 2010016.32 | 380445.76 | 2390462.08 | 1637005.55 | 0.00 | 5206.83 | 3553.17 | 2615.00 |
| M NW APARTMENT | 1637005.55 | 365294.32 | 2002299.88 | 380445.76 | 2382745.64 | 1637005.55 | 0.00 | 5206.83 | 3553.17 | 0.00 |
| M SE APARTMENT | 1637005.55 | 373316.64 | 2010322.19 | 380445.76 | 2390767.95 | 1637005.55 | 0.00 | 5206.83 | 3553.17 | 2615.00 |
| M NE APARTMENT | 1637005.55 | 366235.12 | 2003240.68 | 380445.76 | 2383686.44 | 1637005.55 | 0.00 | 5206.83 | 3553.17 | 0.00 |
| M N1 APARTMENT | 1637005.55 | 367300.77 | 2004306.32 | 229475.22 | 2233781.54 | 1637005.55 | 0.00 | 5206.83 | 3553.17 | 0.00 |
| M N2 APARTMENT | 1637005.55 | 367344.82 | 2004350.38 | 229475.22 | 2233825.60 | 1637005.55 | 0.00 | 5206.83 | 3553.17 | 0.00 |
| M S1 APARTMENT | 1637005.55 | 373683.13 | 2010688.68 | 229475.22 | 2240163.90 | 1637005.55 | 0.00 | 5206.83 | 3553.17 | 2615.00 |
| M S2 APARTMENT | 1637005.55 | 373687.63 | 2010693.18 | 229475.22 | 2240168.40 | 1637005.55 | 0.00 | 5206.83 | 3553.17 | 2615.00 |
| T SW APARTMENT | 818502.78 | 421354.74 | 1239857.52 | 503250.77 | 1743108.29 | 818502.78 | 0.00 | 5207.67 | 3552.33 | 2615.00 |
| T NW APARTMENT | 818502.78 | 410248.63 | 1228751.40 | 503250.77 | 1732002.17 | 818502.78 | 0.00 | 5207.67 | 3552.33 | 0.00 |
| T SE APARTMENT | 818502.78 | 423373.45 | 1241876.22 | 503250.77 | 1745126.99 | 818502.78 | 0.00 | 5207.67 | 3552.33 | 2615.00 |
| T NE APARTMENT | 818502.78 | 412649.16 | 1231151.93 | 503250.77 | 1734402.70 | 818502.78 | 0.00 | 5207.67 | 3552.33 | 0.00 |
| T N1 APARTMENT | 818502.78 | 411771.98 | 1230274.76 | 303548.09 | 1533822.85 | 818502.78 | 0.00 | 5207.67 | 3552.33 | 0.00 |
| T N2 APARTMENT | 818502.78 | 411896.39 | 1230399.16 | 303548.09 | 1533947.25 | 818502.78 | 0.00 | 5207.67 | 3552.33 | 0.00 |
| T S1 APARTMENT | 818502.78 | 423739.51 | 1242242.28 | 303548.09 | 1545790.37 | 818502.78 | 0.00 | 5207.67 | 3552.33 | 2615.00 |
| T S2 APARTMENT | 818502.78 | 423796.33 | 1242299.10 | 303548.09 | 1545847.19 | 818502.78 | 0.00 | 5207.67 | 3552.33 | 2615.00 |
| Total Facility | 39671342.50 | 11484396.11 | 51155738.61 | 9804235.55 | 60959974.17 | 39671342.50 | 0.00 | 8760.00 | 3553.83 | 8760.00 |
| Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
| G SW APARTMENT | 0.0260 | 0.0070 | 0.0329 | 0.0070 | 0.0399 | 0.0260 | 0.00 | 4502.67 | 1642.33 |
| G NW APARTMENT | 0.0260 | 0.0099 | 0.0358 | 0.0084 | 0.0442 | 0.0260 | 0.00 | 5206.50 | 3553.50 |
| OFFICE | 0.0381 | 0.0000 | 0.0381 | 0.0108 | 0.0490 | 0.0381 | 0.00 | 1750.00 | 0.00 |
| G NE APARTMENT | 0.0260 | 0.0099 | 0.0358 | 0.0084 | 0.0442 | 0.0260 | 0.00 | 5206.50 | 3553.50 |
| G N1 APARTMENT | 0.0260 | 0.0100 | 0.0359 | 0.0051 | 0.0410 | 0.0260 | 0.00 | 5206.50 | 3553.50 |
| G N2 APARTMENT | 0.0260 | 0.0100 | 0.0359 | 0.0051 | 0.0410 | 0.0260 | 0.00 | 5206.50 | 3553.50 |
| G S1 APARTMENT | 0.0260 | 0.0070 | 0.0329 | 0.0042 | 0.0372 | 0.0260 | 0.00 | 4502.67 | 1642.33 |
| G S2 APARTMENT | 0.0260 | 0.0070 | 0.0330 | 0.0042 | 0.0372 | 0.0260 | 0.00 | 4502.67 | 1642.33 |
| M SW APARTMENT | 0.0519 | 0.0078 | 0.0597 | 0.0101 | 0.0698 | 0.0519 | 0.00 | 4503.00 | 1642.00 |
| M NW APARTMENT | 0.0519 | 0.0116 | 0.0635 | 0.0121 | 0.0756 | 0.0519 | 0.00 | 5206.83 | 3553.17 |
| M SE APARTMENT | 0.0519 | 0.0078 | 0.0597 | 0.0101 | 0.0698 | 0.0519 | 0.00 | 4503.00 | 1642.00 |
| M NE APARTMENT | 0.0519 | 0.0116 | 0.0635 | 0.0121 | 0.0756 | 0.0519 | 0.00 | 5206.83 | 3553.17 |
| M N1 APARTMENT | 0.0519 | 0.0116 | 0.0636 | 0.0073 | 0.0708 | 0.0519 | 0.00 | 5206.83 | 3553.17 |
| M N2 APARTMENT | 0.0519 | 0.0116 | 0.0636 | 0.0073 | 0.0708 | 0.0519 | 0.00 | 5206.83 | 3553.17 |
| M S1 APARTMENT | 0.0519 | 0.0078 | 0.0597 | 0.0061 | 0.0658 | 0.0519 | 0.00 | 4503.00 | 1642.00 |
| M S2 APARTMENT | 0.0519 | 0.0078 | 0.0597 | 0.0061 | 0.0658 | 0.0519 | 0.00 | 4503.00 | 1642.00 |
| T SW APARTMENT | 0.0260 | 0.0085 | 0.0345 | 0.0134 | 0.0478 | 0.0260 | 0.00 | 4503.50 | 1641.50 |
| T NW APARTMENT | 0.0260 | 0.0130 | 0.0390 | 0.0160 | 0.0549 | 0.0260 | 0.00 | 5207.67 | 3552.33 |
| T SE APARTMENT | 0.0260 | 0.0085 | 0.0345 | 0.0134 | 0.0479 | 0.0260 | 0.00 | 4503.50 | 1641.50 |
| T NE APARTMENT | 0.0260 | 0.0131 | 0.0390 | 0.0160 | 0.0550 | 0.0260 | 0.00 | 5207.67 | 3552.33 |
| T N1 APARTMENT | 0.0260 | 0.0131 | 0.0390 | 0.0096 | 0.0486 | 0.0260 | 0.00 | 5207.67 | 3552.33 |
| T N2 APARTMENT | 0.0260 | 0.0131 | 0.0390 | 0.0096 | 0.0486 | 0.0260 | 0.00 | 5207.67 | 3552.33 |
| T S1 APARTMENT | 0.0260 | 0.0086 | 0.0345 | 0.0081 | 0.0426 | 0.0260 | 0.00 | 4503.50 | 1641.50 |
| T S2 APARTMENT | 0.0260 | 0.0086 | 0.0345 | 0.0081 | 0.0426 | 0.0260 | 0.00 | 4503.50 | 1641.50 |
| Total Facility | 1.2580 | 0.3022 | 1.5601 | 0.2895 | 1.8496 | 1.2580 | 0.00 | 8760.00 | 3553.83 |
| Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
| SPLIT GSW | 0.00 | 323257.81 | 323257.81 | 818502.78 | 6949.22 | 114.09 | 1696.69 | 1911.17 |
| SPLIT GNW | 0.00 | 311263.82 | 311263.82 | 818502.78 | 7181.47 | 140.03 | 1438.50 | 0.00 |
| SPLIT OFFICE | 1678311.91 | 0.00 | 1678311.91 | 1201711.97 | 0.00 | 0.00 | 8760.00 | 7010.00 |
| SPLIT GNE | 0.00 | 312029.38 | 312029.38 | 818502.78 | 7153.89 | 153.42 | 1452.69 | 0.00 |
| SPLIT GN1 | 0.00 | 313972.81 | 313972.81 | 818502.78 | 7109.25 | 141.83 | 1508.92 | 0.00 |
| SPLIT GN2 | 0.00 | 313983.38 | 313983.38 | 818502.78 | 7107.99 | 142.86 | 1509.15 | 0.00 |
| SPLIT GS1 | 0.00 | 325466.38 | 325466.38 | 818502.78 | 6902.22 | 110.47 | 1747.31 | 1911.17 |
| SPLIT GS2 | 0.00 | 325845.97 | 325845.97 | 818502.78 | 6895.35 | 110.98 | 1753.67 | 1911.17 |
| SPLIT MSW | 0.00 | 373010.77 | 373010.77 | 1637005.55 | 8720.58 | 2.92 | 36.50 | 1911.17 |
| SPLIT MNW | 0.00 | 365294.32 | 365294.32 | 1637005.55 | 8742.50 | 3.83 | 13.67 | 0.00 |
| SPLIT MSE | 0.00 | 373316.64 | 373316.64 | 1637005.55 | 8720.33 | 3.00 | 36.67 | 1911.17 |
| SPLIT MNE | 0.00 | 366235.12 | 366235.12 | 1637005.55 | 8741.67 | 4.50 | 13.83 | 0.00 |
| SPLIT MN1 | 0.00 | 367300.77 | 367300.77 | 1637005.55 | 8740.75 | 4.08 | 15.17 | 0.00 |
| SPLIT MN2 | 0.00 | 367344.82 | 367344.82 | 1637005.55 | 8740.75 | 4.08 | 15.17 | 0.00 |
| SPLIT MS1 | 0.00 | 373683.13 | 373683.13 | 1637005.55 | 8719.33 | 3.40 | 37.27 | 1911.17 |
| SPLIT MS2 | 0.00 | 373687.63 | 373687.63 | 1637005.55 | 8719.33 | 3.40 | 37.27 | 1911.17 |
| SPLIT TSW | 0.00 | 421354.74 | 421354.74 | 818502.78 | 5861.18 | 80.86 | 2817.96 | 1910.83 |
| SPLIT TNW | 0.00 | 410248.63 | 410248.63 | 818502.78 | 5935.84 | 87.93 | 2736.23 | 0.00 |
| SPLIT TSE | 0.00 | 423373.45 | 423373.45 | 818502.78 | 5808.95 | 93.88 | 2857.17 | 1910.83 |
| SPLIT TNE | 0.00 | 412649.16 | 412649.16 | 818502.78 | 5882.68 | 96.75 | 2780.57 | 0.00 |
| SPLIT TN1 | 0.00 | 411771.98 | 411771.98 | 818502.78 | 5892.08 | 82.14 | 2785.78 | 0.00 |
| SPLIT TN2 | 0.00 | 411896.39 | 411896.39 | 818502.78 | 5890.26 | 83.88 | 2785.86 | 0.00 |
| SPLIT TS1 | 0.00 | 423739.51 | 423739.51 | 818502.78 | 5807.61 | 77.65 | 2874.74 | 1910.83 |
| SPLIT TS2 | 0.00 | 423796.33 | 423796.33 | 818502.78 | 5807.37 | 77.32 | 2875.31 | 1910.83 |
| Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
| SPLIT GSW | 0.0000 | 0.0070 | 0.0070 | 0.0260 | 5162.43 | 63.53 | 919.04 |
| SPLIT GNW | 0.0000 | 0.0099 | 0.0099 | 0.0260 | 7181.47 | 140.03 | 1438.50 |
| SPLIT OFFICE | 0.0532 | 0.0000 | 0.0532 | 0.0381 | 0.00 | 0.00 | 1750.00 |
| SPLIT GNE | 0.0000 | 0.0099 | 0.0099 | 0.0260 | 7153.89 | 153.42 | 1452.69 |
| SPLIT GN1 | 0.0000 | 0.0100 | 0.0100 | 0.0260 | 7109.25 | 141.83 | 1508.92 |
| SPLIT GN2 | 0.0000 | 0.0100 | 0.0100 | 0.0260 | 7107.99 | 142.86 | 1509.15 |
| SPLIT GS1 | 0.0000 | 0.0070 | 0.0070 | 0.0260 | 5144.47 | 62.28 | 938.25 |
| SPLIT GS2 | 0.0000 | 0.0070 | 0.0070 | 0.0260 | 5141.75 | 62.17 | 941.08 |
| SPLIT MSW | 0.0000 | 0.0078 | 0.0078 | 0.0519 | 6133.42 | 1.25 | 10.33 |
| SPLIT MNW | 0.0000 | 0.0116 | 0.0116 | 0.0519 | 8742.50 | 3.83 | 13.67 |
| SPLIT MSE | 0.0000 | 0.0078 | 0.0078 | 0.0519 | 6133.33 | 1.33 | 10.33 |
| SPLIT MNE | 0.0000 | 0.0116 | 0.0116 | 0.0519 | 8741.67 | 4.50 | 13.83 |
| SPLIT MN1 | 0.0000 | 0.0116 | 0.0116 | 0.0519 | 8740.75 | 4.08 | 15.17 |
| SPLIT MN2 | 0.0000 | 0.0116 | 0.0116 | 0.0519 | 8740.75 | 4.08 | 15.17 |
| SPLIT MS1 | 0.0000 | 0.0078 | 0.0078 | 0.0519 | 6132.50 | 1.67 | 10.83 |
| SPLIT MS2 | 0.0000 | 0.0078 | 0.0078 | 0.0519 | 6132.50 | 1.67 | 10.83 |
| SPLIT TSW | 0.0000 | 0.0085 | 0.0085 | 0.0260 | 4793.75 | 45.40 | 1305.85 |
| SPLIT TNW | 0.0000 | 0.0130 | 0.0130 | 0.0260 | 5935.84 | 87.93 | 2736.23 |
| SPLIT TSE | 0.0000 | 0.0085 | 0.0085 | 0.0260 | 4780.00 | 51.10 | 1313.90 |
| SPLIT TNE | 0.0000 | 0.0131 | 0.0131 | 0.0260 | 5882.68 | 96.75 | 2780.57 |
| SPLIT TN1 | 0.0000 | 0.0131 | 0.0131 | 0.0260 | 5892.08 | 82.14 | 2785.78 |
| SPLIT TN2 | 0.0000 | 0.0131 | 0.0131 | 0.0260 | 5890.26 | 83.88 | 2785.86 |
| SPLIT TS1 | 0.0000 | 0.0086 | 0.0086 | 0.0260 | 4763.82 | 39.16 | 1342.02 |
| SPLIT TS2 | 0.0000 | 0.0086 | 0.0086 | 0.0260 | 4763.74 | 40.02 | 1341.25 |
| No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
| SPLIT GSW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT GNW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT OFFICE | 0.00 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT GNE | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT GN1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT GN2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT GS1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT GS2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT MSW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT MNW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT MSE | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT MNE | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT MN1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT MN2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT MS1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT MS2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT TSW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT TNW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT TSE | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT TNE | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT TN1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT TN2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT TS1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT TS2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
| SPLIT GSW | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT GNW | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT OFFICE | 0.0000 | 0.0532 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT GNE | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT GN1 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT GN2 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT GS1 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT GS2 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT MSW | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT MNW | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT MSE | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT MNE | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT MN1 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT MN2 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT MS1 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT MS2 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT TSW | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT TNW | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT TSE | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT TNE | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT TN1 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT TN2 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT TS1 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT TS2 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 09:15:25
Surfaces by Class| Total | Outdoors | |
| Wall | 126 | 42 |
| Floor | 27 | 9 |
| Roof | 27 | 9 |
| Internal Mass | 24 | 0 |
| Building Detached Shading | 0 | 0 |
| Fixed Detached Shading | 0 | 0 |
| Window | 39 | 39 |
| Door | 0 | 0 |
| Glass Door | 0 | 0 |
| Shading | 0 | 0 |
| Overhang | 0 | 0 |
| Fin | 0 | 0 |
| Tubular Daylighting Device Dome | 0 | 0 |
| Tubular Daylighting Device Diffuser | 0 | 0 |
| Count | |
| HVAC Air Loops | 24 |
| Conditioned Zones | 24 |
| Unconditioned Zones | 3 |
| Supply Plenums | 0 |
| Return Plenums | 0 |
| Count | |
| IDF Objects | 1536 |
| Defaulted Fields | 1816 |
| Fields with Defaults | 5921 |
| Autosized Fields | 617 |
| Autosizable Fields | 759 |
| Autocalculated Fields | 331 |
| Autocalculatable Fields | 508 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 09:15:25
Annual and Peak Values - Electricity| Electricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
| Electricity:Facility | 1191.62 | 16812.84 | 12-MAY-05:00 | 77028.25 | 19-AUG-16:30 |
| Electricity:Building | 557.89 | 10119.94 | 01-JAN-03:10 | 27841.36 | 01-JAN-18:10 |
| Electricity:Zone:G SW APARTMENT | 13.67 | 232.36 | 01-JAN-03:10 | 705.80 | 01-JAN-18:10 |
| Electricity:SpaceType:GENERAL | 557.89 | 10119.94 | 01-JAN-03:10 | 27841.36 | 01-JAN-18:10 |
| InteriorLights:Electricity | 99.23 | 1868.27 | 01-JAN-00:10 | 5904.43 | 01-JAN-19:10 |
| InteriorLights:Electricity:Zone:G SW APARTMENT | 1.45 | 8.68 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 |
| InteriorLights:Electricity:SpaceType:GENERAL | 99.23 | 1868.27 | 01-JAN-00:10 | 5904.43 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity | 94.96 | 1842.77 | 01-JAN-00:10 | 5496.56 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:G SW APARTMENT | 1.32 | 7.86 | 01-JAN-00:10 | 125.72 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 94.96 | 1842.77 | 01-JAN-00:10 | 5496.56 | 01-JAN-19:10 |
| Electricity:Zone:G NW APARTMENT | 13.67 | 232.36 | 01-JAN-03:10 | 705.80 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:G NW APARTMENT | 1.45 | 8.68 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:G NW APARTMENT | 1.32 | 7.86 | 01-JAN-00:10 | 125.72 | 01-JAN-19:10 |
| Electricity:Zone:OFFICE | 16.86 | 310.83 | 01-JAN-00:10 | 1171.54 | 03-JAN-08:10 |
| InteriorLights:Electricity:Zone:OFFICE | 7.40 | 116.58 | 01-JAN-00:10 | 582.92 | 03-JAN-08:10 |
| LightsWired:InteriorLights:Electricity:Zone:OFFICE | 7.40 | 116.58 | 01-JAN-00:10 | 582.92 | 03-JAN-08:10 |
| Electricity:Zone:G NE APARTMENT | 13.67 | 232.36 | 01-JAN-03:10 | 705.80 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:G NE APARTMENT | 1.45 | 8.68 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:G NE APARTMENT | 1.32 | 7.86 | 01-JAN-00:10 | 125.72 | 01-JAN-19:10 |
| Electricity:Zone:G N1 APARTMENT | 13.67 | 232.36 | 01-JAN-03:10 | 705.80 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:G N1 APARTMENT | 1.45 | 8.68 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:G N1 APARTMENT | 1.32 | 7.86 | 01-JAN-00:10 | 125.72 | 01-JAN-19:10 |
| Electricity:Zone:G N2 APARTMENT | 13.67 | 232.36 | 01-JAN-03:10 | 705.80 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:G N2 APARTMENT | 1.45 | 8.68 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:G N2 APARTMENT | 1.32 | 7.86 | 01-JAN-00:10 | 125.72 | 01-JAN-19:10 |
| Electricity:Zone:G S1 APARTMENT | 13.67 | 232.36 | 01-JAN-03:10 | 705.80 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:G S1 APARTMENT | 1.45 | 8.68 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:G S1 APARTMENT | 1.32 | 7.86 | 01-JAN-00:10 | 125.72 | 01-JAN-19:10 |
| Electricity:Zone:G S2 APARTMENT | 13.67 | 232.36 | 01-JAN-03:10 | 705.80 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:G S2 APARTMENT | 1.45 | 8.68 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:G S2 APARTMENT | 1.32 | 7.86 | 01-JAN-00:10 | 125.72 | 01-JAN-19:10 |
| Electricity:Zone:M SW APARTMENT | 27.33 | 464.72 | 01-JAN-03:10 | 1411.61 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:M SW APARTMENT | 2.91 | 17.37 | 01-JAN-00:10 | 277.76 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:M SW APARTMENT | 2.63 | 15.72 | 01-JAN-00:10 | 251.45 | 01-JAN-19:10 |
| Electricity:Zone:M NW APARTMENT | 27.33 | 464.72 | 01-JAN-03:10 | 1411.61 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:M NW APARTMENT | 2.91 | 17.37 | 01-JAN-00:10 | 277.76 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:M NW APARTMENT | 2.63 | 15.72 | 01-JAN-00:10 | 251.45 | 01-JAN-19:10 |
| Electricity:Zone:M SE APARTMENT | 27.33 | 464.72 | 01-JAN-03:10 | 1411.61 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:M SE APARTMENT | 2.91 | 17.37 | 01-JAN-00:10 | 277.76 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:M SE APARTMENT | 2.63 | 15.72 | 01-JAN-00:10 | 251.45 | 01-JAN-19:10 |
| Electricity:Zone:M NE APARTMENT | 27.33 | 464.72 | 01-JAN-03:10 | 1411.61 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:M NE APARTMENT | 2.91 | 17.37 | 01-JAN-00:10 | 277.76 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:M NE APARTMENT | 2.63 | 15.72 | 01-JAN-00:10 | 251.45 | 01-JAN-19:10 |
| Electricity:Zone:M N1 APARTMENT | 27.33 | 464.72 | 01-JAN-03:10 | 1411.61 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:M N1 APARTMENT | 2.91 | 17.37 | 01-JAN-00:10 | 277.76 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:M N1 APARTMENT | 2.63 | 15.72 | 01-JAN-00:10 | 251.45 | 01-JAN-19:10 |
| Electricity:Zone:M N2 APARTMENT | 27.33 | 464.72 | 01-JAN-03:10 | 1411.61 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:M N2 APARTMENT | 2.91 | 17.37 | 01-JAN-00:10 | 277.76 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:M N2 APARTMENT | 2.63 | 15.72 | 01-JAN-00:10 | 251.45 | 01-JAN-19:10 |
| Electricity:Zone:M S1 APARTMENT | 27.33 | 464.72 | 01-JAN-03:10 | 1411.61 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:M S1 APARTMENT | 2.91 | 17.37 | 01-JAN-00:10 | 277.76 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:M S1 APARTMENT | 2.63 | 15.72 | 01-JAN-00:10 | 251.45 | 01-JAN-19:10 |
| Electricity:Zone:M S2 APARTMENT | 27.33 | 464.72 | 01-JAN-03:10 | 1411.61 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:M S2 APARTMENT | 2.91 | 17.37 | 01-JAN-00:10 | 277.76 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:M S2 APARTMENT | 2.63 | 15.72 | 01-JAN-00:10 | 251.45 | 01-JAN-19:10 |
| Electricity:Zone:T SW APARTMENT | 13.67 | 232.36 | 01-JAN-03:10 | 705.80 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:T SW APARTMENT | 1.45 | 8.68 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:T SW APARTMENT | 1.32 | 7.86 | 01-JAN-00:10 | 125.72 | 01-JAN-19:10 |
| Electricity:Zone:T NW APARTMENT | 13.67 | 232.36 | 01-JAN-03:10 | 705.80 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:T NW APARTMENT | 1.45 | 8.68 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:T NW APARTMENT | 1.32 | 7.86 | 01-JAN-00:10 | 125.72 | 01-JAN-19:10 |
| Electricity:Zone:T SE APARTMENT | 13.67 | 232.36 | 01-JAN-03:10 | 705.80 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:T SE APARTMENT | 1.45 | 8.68 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:T SE APARTMENT | 1.32 | 7.86 | 01-JAN-00:10 | 125.72 | 01-JAN-19:10 |
| Electricity:Zone:T NE APARTMENT | 13.67 | 232.36 | 01-JAN-03:10 | 705.80 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:T NE APARTMENT | 1.45 | 8.68 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:T NE APARTMENT | 1.32 | 7.86 | 01-JAN-00:10 | 125.72 | 01-JAN-19:10 |
| Electricity:Zone:T N1 APARTMENT | 13.67 | 232.36 | 01-JAN-03:10 | 705.80 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:T N1 APARTMENT | 1.45 | 8.68 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:T N1 APARTMENT | 1.32 | 7.86 | 01-JAN-00:10 | 125.72 | 01-JAN-19:10 |
| Electricity:Zone:T N2 APARTMENT | 13.67 | 232.36 | 01-JAN-03:10 | 705.80 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:T N2 APARTMENT | 1.45 | 8.68 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:T N2 APARTMENT | 1.32 | 7.86 | 01-JAN-00:10 | 125.72 | 01-JAN-19:10 |
| Electricity:Zone:T S1 APARTMENT | 13.67 | 232.36 | 01-JAN-03:10 | 705.80 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:T S1 APARTMENT | 1.45 | 8.68 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:T S1 APARTMENT | 1.32 | 7.86 | 01-JAN-00:10 | 125.72 | 01-JAN-19:10 |
| Electricity:Zone:T S2 APARTMENT | 13.67 | 232.36 | 01-JAN-03:10 | 705.80 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:T S2 APARTMENT | 1.45 | 8.68 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:T S2 APARTMENT | 1.32 | 7.86 | 01-JAN-00:10 | 125.72 | 01-JAN-19:10 |
| Electricity:Zone:G CORRIDOR | 82.28 | 1494.09 | 01-JAN-00:10 | 4538.70 | 01-JAN-07:10 |
| InteriorLights:Electricity:Zone:G CORRIDOR | 11.69 | 370.63 | 01-JAN-00:10 | 370.63 | 01-JAN-00:10 |
| LightsWired:InteriorLights:Electricity:Zone:G CORRIDOR | 11.69 | 370.63 | 01-JAN-00:10 | 370.63 | 01-JAN-00:10 |
| Electricity:Zone:M CORRIDOR | 23.38 | 741.26 | 01-JAN-00:10 | 741.26 | 01-JAN-00:10 |
| InteriorLights:Electricity:Zone:M CORRIDOR | 23.38 | 741.26 | 01-JAN-00:10 | 741.26 | 01-JAN-00:10 |
| LightsWired:InteriorLights:Electricity:Zone:M CORRIDOR | 23.38 | 741.26 | 01-JAN-00:10 | 741.26 | 01-JAN-00:10 |
| Electricity:Zone:T CORRIDOR | 11.69 | 370.63 | 01-JAN-00:10 | 370.63 | 01-JAN-00:10 |
| InteriorLights:Electricity:Zone:T CORRIDOR | 11.69 | 370.63 | 01-JAN-00:10 | 370.63 | 01-JAN-00:10 |
| LightsWired:InteriorLights:Electricity:Zone:T CORRIDOR | 11.69 | 370.63 | 01-JAN-00:10 | 370.63 | 01-JAN-00:10 |
| LightsPlugIn:InteriorLights:Electricity | 4.27 | 25.50 | 01-JAN-00:10 | 407.87 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:G SW APARTMENT | 0.14 | 0.82 | 01-JAN-00:10 | 13.16 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:SpaceType:GENERAL | 4.27 | 25.50 | 01-JAN-00:10 | 407.87 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:G NW APARTMENT | 0.14 | 0.82 | 01-JAN-00:10 | 13.16 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:G NE APARTMENT | 0.14 | 0.82 | 01-JAN-00:10 | 13.16 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:G N1 APARTMENT | 0.14 | 0.82 | 01-JAN-00:10 | 13.16 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:G N2 APARTMENT | 0.14 | 0.82 | 01-JAN-00:10 | 13.16 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:G S1 APARTMENT | 0.14 | 0.82 | 01-JAN-00:10 | 13.16 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:G S2 APARTMENT | 0.14 | 0.82 | 01-JAN-00:10 | 13.16 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:M SW APARTMENT | 0.28 | 1.65 | 01-JAN-00:10 | 26.31 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:M NW APARTMENT | 0.28 | 1.65 | 01-JAN-00:10 | 26.31 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:M SE APARTMENT | 0.28 | 1.65 | 01-JAN-00:10 | 26.31 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:M NE APARTMENT | 0.28 | 1.65 | 01-JAN-00:10 | 26.31 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:M N1 APARTMENT | 0.28 | 1.65 | 01-JAN-00:10 | 26.31 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:M N2 APARTMENT | 0.28 | 1.65 | 01-JAN-00:10 | 26.31 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:M S1 APARTMENT | 0.28 | 1.65 | 01-JAN-00:10 | 26.31 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:M S2 APARTMENT | 0.28 | 1.65 | 01-JAN-00:10 | 26.31 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:T SW APARTMENT | 0.14 | 0.82 | 01-JAN-00:10 | 13.16 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:T NW APARTMENT | 0.14 | 0.82 | 01-JAN-00:10 | 13.16 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:T SE APARTMENT | 0.14 | 0.82 | 01-JAN-00:10 | 13.16 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:T NE APARTMENT | 0.14 | 0.82 | 01-JAN-00:10 | 13.16 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:T N1 APARTMENT | 0.14 | 0.82 | 01-JAN-00:10 | 13.16 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:T N2 APARTMENT | 0.14 | 0.82 | 01-JAN-00:10 | 13.16 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:T S1 APARTMENT | 0.14 | 0.82 | 01-JAN-00:10 | 13.16 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:T S2 APARTMENT | 0.14 | 0.82 | 01-JAN-00:10 | 13.16 | 01-JAN-19:10 |
| InteriorEquipment:Electricity | 458.66 | 8251.68 | 01-JAN-03:10 | 22709.69 | 03-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:G SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:SpaceType:GENERAL | 458.66 | 8251.68 | 01-JAN-03:10 | 22709.69 | 03-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity | 388.06 | 7128.22 | 01-JAN-03:10 | 18541.61 | 03-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:G SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 388.06 | 7128.22 | 01-JAN-03:10 | 18541.61 | 03-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:G NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:G NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:OFFICE | 9.47 | 194.25 | 01-JAN-00:10 | 588.62 | 03-JAN-08:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:OFFICE | 9.47 | 194.25 | 01-JAN-00:10 | 588.62 | 03-JAN-08:10 |
| InteriorEquipment:Electricity:Zone:G NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:G NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:G N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:G N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:G N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:G N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:G S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:G S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:G S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:G S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:M SW APARTMENT | 24.43 | 447.35 | 01-JAN-03:10 | 1177.25 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:M SW APARTMENT | 24.43 | 447.35 | 01-JAN-03:10 | 1177.25 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:M NW APARTMENT | 24.43 | 447.35 | 01-JAN-03:10 | 1177.25 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:M NW APARTMENT | 24.43 | 447.35 | 01-JAN-03:10 | 1177.25 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:M SE APARTMENT | 24.43 | 447.35 | 01-JAN-03:10 | 1177.25 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:M SE APARTMENT | 24.43 | 447.35 | 01-JAN-03:10 | 1177.25 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:M NE APARTMENT | 24.43 | 447.35 | 01-JAN-03:10 | 1177.25 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:M NE APARTMENT | 24.43 | 447.35 | 01-JAN-03:10 | 1177.25 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:M N1 APARTMENT | 24.43 | 447.35 | 01-JAN-03:10 | 1177.25 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:M N1 APARTMENT | 24.43 | 447.35 | 01-JAN-03:10 | 1177.25 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:M N2 APARTMENT | 24.43 | 447.35 | 01-JAN-03:10 | 1177.25 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:M N2 APARTMENT | 24.43 | 447.35 | 01-JAN-03:10 | 1177.25 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:M S1 APARTMENT | 24.43 | 447.35 | 01-JAN-03:10 | 1177.25 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:M S1 APARTMENT | 24.43 | 447.35 | 01-JAN-03:10 | 1177.25 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:M S2 APARTMENT | 24.43 | 447.35 | 01-JAN-03:10 | 1177.25 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:M S2 APARTMENT | 24.43 | 447.35 | 01-JAN-03:10 | 1177.25 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:T SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:T SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:T NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:T NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:T SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:T SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:T NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:T NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:T N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:T N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:T N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:T N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:T S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:T S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:T S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:T S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:G CORRIDOR | 70.59 | 1123.46 | 01-JAN-00:10 | 4168.07 | 01-JAN-07:10 |
| ElevatorLift:InteriorEquipment:Electricity | 65.48 | 961.46 | 01-JAN-00:10 | 4006.07 | 01-JAN-07:10 |
| ElevatorLift:InteriorEquipment:Electricity:Zone:G CORRIDOR | 65.48 | 961.46 | 01-JAN-00:10 | 4006.07 | 01-JAN-07:10 |
| ElevatorLift:InteriorEquipment:Electricity:SpaceType:GENERAL | 65.48 | 961.46 | 01-JAN-00:10 | 4006.07 | 01-JAN-07:10 |
| ElevatorLightsFan:InteriorEquipment:Electricity | 5.11 | 162.00 | 01-JAN-00:10 | 162.00 | 01-JAN-00:10 |
| ElevatorLightsFan:InteriorEquipment:Electricity:Zone:G CORRIDOR | 5.11 | 162.00 | 01-JAN-00:10 | 162.00 | 01-JAN-00:10 |
| ElevatorLightsFan:InteriorEquipment:Electricity:SpaceType:GENERAL | 5.11 | 162.00 | 01-JAN-00:10 | 162.00 | 01-JAN-00:10 |
| Fans:Electricity | 76.97 | 1642.87 | 13-FEB-17:10 | 8298.50 | 16-OCT-12:00 |
| Fans:Electricity:Zone:G SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:G SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:G NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:G NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:G NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:G NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:G N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:G N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:G N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:G N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:G S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:G S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:G S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:G S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:M SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:M SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:M NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:M NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:M SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:M SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:M NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:M NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:M N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:M N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:M N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:M N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:M S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:M S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:M S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:M S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:T SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:T SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:T NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:T NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:T SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:T SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:T NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:T NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:T N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:T N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:T N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:T N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:T S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:T S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:T S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:T S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| ElectricityPurchased:Facility | 1191.62 | 16812.84 | 12-MAY-05:00 | 77028.25 | 19-AUG-16:30 |
| ElectricityPurchased:Plant | 1191.62 | 16812.84 | 12-MAY-05:00 | 77028.25 | 19-AUG-16:30 |
| Cogeneration:ElectricityPurchased | 1191.62 | 16812.84 | 12-MAY-05:00 | 77028.25 | 19-AUG-16:30 |
| General:Cogeneration:ElectricityPurchased | 1191.62 | 16812.84 | 12-MAY-05:00 | 77028.25 | 19-AUG-16:30 |
| ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| ElectricityNet:Facility | 1191.62 | 16812.84 | 12-MAY-05:00 | 77028.25 | 19-AUG-16:30 |
| ElectricityNet:Plant | 1191.62 | 16812.84 | 12-MAY-05:00 | 77028.25 | 19-AUG-16:30 |
| Cogeneration:ElectricityNet | 1191.62 | 16812.84 | 12-MAY-05:00 | 77028.25 | 19-AUG-16:30 |
| General:Cogeneration:ElectricityNet | 1191.62 | 16812.84 | 12-MAY-05:00 | 77028.25 | 19-AUG-16:30 |
| Electricity:HVAC | 159.74 | 1642.87 | 13-FEB-17:10 | 32973.96 | 16-OCT-12:00 |
| HeatRecovery:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:HeatRecovery:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:Fans:Electricity | 76.97 | 1642.87 | 13-FEB-17:10 | 8298.50 | 16-OCT-12:00 |
| Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Cooling:Electricity | 82.77 | 0.00 | 01-JAN-00:10 | 24675.46 | 16-OCT-12:00 |
| General:Cooling:Electricity | 82.77 | 0.00 | 01-JAN-00:10 | 24675.46 | 16-OCT-12:00 |
| ExteriorLights:Electricity | 50.05 | 0.00 | 01-JAN-07:00 | 3183.33 | 01-JAN-00:10 |
| General:ExteriorLights:Electricity | 50.05 | 0.00 | 01-JAN-07:00 | 3183.33 | 01-JAN-00:10 |
| Electricity:Plant | 423.95 | 1950.00 | 01-JAN-00:10 | 37405.86 | 01-JAN-07:40 |
| WaterSystems:Electricity | 423.95 | 1950.00 | 01-JAN-00:10 | 37405.86 | 01-JAN-07:40 |
| Water Heater:WaterSystems:Electricity | 423.95 | 1950.00 | 01-JAN-00:10 | 37405.86 | 01-JAN-07:40 |
| Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
| NaturalGas:Facility | 25.22 | 0.00 | 03-JAN-12:00 | 30396.10 | 30-MAR-04:00 |
| NaturalGas:HVAC | 25.22 | 0.00 | 03-JAN-12:00 | 30396.10 | 30-MAR-04:00 |
| Heating:NaturalGas | 25.22 | 0.00 | 03-JAN-12:00 | 30396.10 | 30-MAR-04:00 |
| General:Heating:NaturalGas | 25.22 | 0.00 | 03-JAN-12:00 | 30396.10 | 30-MAR-04:00 |
| Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
| None |
| Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
| Water:Facility | 1875.32 | 0.00 | 01-JAN-02:10 | 0.00 | 01-JAN-07:10 |
| Water:Plant | 1875.32 | 0.00 | 01-JAN-02:10 | 0.00 | 01-JAN-07:10 |
| WaterSystems:Water | 1875.32 | 0.00 | 01-JAN-02:10 | 0.00 | 01-JAN-07:10 |
| Water Heater:WaterSystems:Water | 1875.32 | 0.00 | 01-JAN-02:10 | 0.00 | 01-JAN-07:10 |
| MainsWater:Facility | 1875.32 | 0.00 | 01-JAN-02:10 | 0.00 | 01-JAN-07:10 |
| MainsWater:Plant | 1875.32 | 0.00 | 01-JAN-02:10 | 0.00 | 01-JAN-07:10 |
| WaterSystems:MainsWater | 1875.32 | 0.00 | 01-JAN-02:10 | 0.00 | 01-JAN-07:10 |
| Water Heater:WaterSystems:MainsWater | 1875.32 | 0.00 | 01-JAN-02:10 | 0.00 | 01-JAN-07:10 |
| Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
| Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
| CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
| Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
| None |
| Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
| None |
| Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
| EnergyTransfer:Facility | 809.03 | 1563.89 | 01-APR-09:40 | 150681.73 | 16-OCT-12:00 |
| EnergyTransfer:Building | 458.69 | 1231.49 | 01-APR-10:00 | 65444.40 | 16-OCT-12:00 |
| EnergyTransfer:Zone:G SW APARTMENT | 13.12 | 0.07 | 29-MAR-21:30 | 2155.92 | 16-OCT-14:10 |
| Heating:EnergyTransfer | 8.31 | 0.00 | 01-JAN-12:30 | 12332.49 | 30-MAR-04:00 |
| Heating:EnergyTransfer:Zone:G SW APARTMENT | 0.02 | 0.00 | 01-JAN-00:10 | 373.61 | 30-MAR-04:00 |
| General:Heating:EnergyTransfer | 8.31 | 0.00 | 01-JAN-12:30 | 12332.49 | 30-MAR-04:00 |
| General:Heating:EnergyTransfer:Zone:G SW APARTMENT | 0.02 | 0.00 | 01-JAN-00:10 | 373.61 | 30-MAR-04:00 |
| Cooling:EnergyTransfer | 450.37 | 822.34 | 01-APR-10:00 | 65444.40 | 16-OCT-12:00 |
| Cooling:EnergyTransfer:Zone:G SW APARTMENT | 13.10 | 0.00 | 02-JAN-02:10 | 2155.92 | 16-OCT-14:10 |
| General:Cooling:EnergyTransfer | 450.37 | 822.34 | 01-APR-10:00 | 65444.40 | 16-OCT-12:00 |
| General:Cooling:EnergyTransfer:Zone:G SW APARTMENT | 13.10 | 0.00 | 02-JAN-02:10 | 2155.92 | 16-OCT-14:10 |
| EnergyTransfer:Zone:G NW APARTMENT | 9.17 | 0.01 | 06-JAN-23:30 | 1384.46 | 29-SEP-16:10 |
| Heating:EnergyTransfer:Zone:G NW APARTMENT | 0.12 | 0.00 | 01-JAN-07:20 | 422.76 | 30-MAR-04:00 |
| General:Heating:EnergyTransfer:Zone:G NW APARTMENT | 0.12 | 0.00 | 01-JAN-07:20 | 422.76 | 30-MAR-04:00 |
| Cooling:EnergyTransfer:Zone:G NW APARTMENT | 9.05 | 0.00 | 01-JAN-00:10 | 1384.46 | 29-SEP-16:10 |
| General:Cooling:EnergyTransfer:Zone:G NW APARTMENT | 9.05 | 0.00 | 01-JAN-00:10 | 1384.46 | 29-SEP-16:10 |
| EnergyTransfer:Zone:OFFICE | 10.65 | 0.00 | 20-APR-18:50 | 3880.86 | 16-OCT-11:00 |
| Heating:EnergyTransfer:Zone:OFFICE | 0.78 | 0.00 | 01-JAN-00:10 | 636.97 | 14-OCT-12:00 |
| General:Heating:EnergyTransfer:Zone:OFFICE | 0.78 | 0.00 | 01-JAN-00:10 | 636.97 | 14-OCT-12:00 |
| Cooling:EnergyTransfer:Zone:OFFICE | 9.87 | 0.00 | 01-JAN-10:10 | 3880.86 | 16-OCT-11:00 |
| General:Cooling:EnergyTransfer:Zone:OFFICE | 9.87 | 0.00 | 01-JAN-10:10 | 3880.86 | 16-OCT-11:00 |
| EnergyTransfer:Zone:G NE APARTMENT | 8.97 | 0.00 | 09-FEB-06:40 | 1393.29 | 16-OCT-11:00 |
| Heating:EnergyTransfer:Zone:G NE APARTMENT | 0.12 | 0.00 | 01-JAN-07:10 | 456.15 | 30-MAR-03:00 |
| General:Heating:EnergyTransfer:Zone:G NE APARTMENT | 0.12 | 0.00 | 01-JAN-07:10 | 456.15 | 30-MAR-03:00 |
| Cooling:EnergyTransfer:Zone:G NE APARTMENT | 8.85 | 0.00 | 01-JAN-00:10 | 1393.29 | 16-OCT-11:00 |
| General:Cooling:EnergyTransfer:Zone:G NE APARTMENT | 8.85 | 0.00 | 01-JAN-00:10 | 1393.29 | 16-OCT-11:00 |
| EnergyTransfer:Zone:G N1 APARTMENT | 9.34 | 0.02 | 15-JAN-09:10 | 975.38 | 16-OCT-12:00 |
| Heating:EnergyTransfer:Zone:G N1 APARTMENT | 0.01 | 0.00 | 01-JAN-00:10 | 114.65 | 13-JAN-14:00 |
| General:Heating:EnergyTransfer:Zone:G N1 APARTMENT | 0.01 | 0.00 | 01-JAN-00:10 | 114.65 | 13-JAN-14:00 |
| Cooling:EnergyTransfer:Zone:G N1 APARTMENT | 9.33 | 0.00 | 03-JAN-01:40 | 975.38 | 16-OCT-12:00 |
| General:Cooling:EnergyTransfer:Zone:G N1 APARTMENT | 9.33 | 0.00 | 03-JAN-01:40 | 975.38 | 16-OCT-12:00 |
| EnergyTransfer:Zone:G N2 APARTMENT | 9.32 | 0.01 | 15-JAN-09:10 | 980.08 | 16-OCT-12:00 |
| Heating:EnergyTransfer:Zone:G N2 APARTMENT | 0.01 | 0.00 | 01-JAN-00:10 | 114.40 | 13-JAN-14:00 |
| General:Heating:EnergyTransfer:Zone:G N2 APARTMENT | 0.01 | 0.00 | 01-JAN-00:10 | 114.40 | 13-JAN-14:00 |
| Cooling:EnergyTransfer:Zone:G N2 APARTMENT | 9.31 | 0.00 | 03-JAN-01:40 | 980.08 | 16-OCT-12:00 |
| General:Cooling:EnergyTransfer:Zone:G N2 APARTMENT | 9.31 | 0.00 | 03-JAN-01:40 | 980.08 | 16-OCT-12:00 |
| EnergyTransfer:Zone:G S1 APARTMENT | 13.88 | 0.08 | 01-APR-10:20 | 1832.15 | 16-OCT-12:30 |
| Heating:EnergyTransfer:Zone:G S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 33.04 | 01-APR-12:00 |
| General:Heating:EnergyTransfer:Zone:G S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 33.04 | 01-APR-12:00 |
| Cooling:EnergyTransfer:Zone:G S1 APARTMENT | 13.88 | 0.00 | 01-APR-10:30 | 1832.15 | 16-OCT-12:30 |
| General:Cooling:EnergyTransfer:Zone:G S1 APARTMENT | 13.88 | 0.00 | 01-APR-10:30 | 1832.15 | 16-OCT-12:30 |
| EnergyTransfer:Zone:G S2 APARTMENT | 14.55 | 0.20 | 01-APR-12:30 | 1922.65 | 16-OCT-12:00 |
| Heating:EnergyTransfer:Zone:G S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 31.57 | 01-APR-12:00 |
| General:Heating:EnergyTransfer:Zone:G S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 31.57 | 01-APR-12:00 |
| Cooling:EnergyTransfer:Zone:G S2 APARTMENT | 14.55 | 0.00 | 01-APR-10:30 | 1922.65 | 16-OCT-12:00 |
| General:Cooling:EnergyTransfer:Zone:G S2 APARTMENT | 14.55 | 0.00 | 01-APR-10:30 | 1922.65 | 16-OCT-12:00 |
| EnergyTransfer:Zone:M SW APARTMENT | 38.82 | 0.48 | 30-MAR-00:10 | 5380.88 | 15-OCT-15:10 |
| Heating:EnergyTransfer:Zone:M SW APARTMENT | 0.01 | 0.00 | 01-JAN-00:10 | 508.04 | 30-MAR-04:00 |
| General:Heating:EnergyTransfer:Zone:M SW APARTMENT | 0.01 | 0.00 | 01-JAN-00:10 | 508.04 | 30-MAR-04:00 |
| Cooling:EnergyTransfer:Zone:M SW APARTMENT | 38.81 | 0.00 | 29-MAR-04:00 | 5380.88 | 15-OCT-15:10 |
| General:Cooling:EnergyTransfer:Zone:M SW APARTMENT | 38.81 | 0.00 | 29-MAR-04:00 | 5380.88 | 15-OCT-15:10 |
| EnergyTransfer:Zone:M NW APARTMENT | 27.54 | 0.07 | 08-NOV-10:40 | 3740.61 | 29-SEP-16:10 |
| Heating:EnergyTransfer:Zone:M NW APARTMENT | 0.04 | 0.00 | 01-JAN-00:10 | 631.33 | 30-MAR-04:00 |
| General:Heating:EnergyTransfer:Zone:M NW APARTMENT | 0.04 | 0.00 | 01-JAN-00:10 | 631.33 | 30-MAR-04:00 |
| Cooling:EnergyTransfer:Zone:M NW APARTMENT | 27.49 | 0.00 | 02-JAN-01:30 | 3740.61 | 29-SEP-16:10 |
| General:Cooling:EnergyTransfer:Zone:M NW APARTMENT | 27.49 | 0.00 | 02-JAN-01:30 | 3740.61 | 29-SEP-16:10 |
| EnergyTransfer:Zone:M SE APARTMENT | 38.22 | 10.70 | 29-MAR-23:20 | 5459.72 | 16-OCT-12:00 |
| Heating:EnergyTransfer:Zone:M SE APARTMENT | 0.01 | 0.00 | 01-JAN-00:10 | 630.96 | 30-MAR-04:00 |
| General:Heating:EnergyTransfer:Zone:M SE APARTMENT | 0.01 | 0.00 | 01-JAN-00:10 | 630.96 | 30-MAR-04:00 |
| Cooling:EnergyTransfer:Zone:M SE APARTMENT | 38.21 | 0.00 | 29-MAR-04:00 | 5459.72 | 16-OCT-12:00 |
| General:Cooling:EnergyTransfer:Zone:M SE APARTMENT | 38.21 | 0.00 | 29-MAR-04:00 | 5459.72 | 16-OCT-12:00 |
| EnergyTransfer:Zone:M NE APARTMENT | 26.92 | 0.29 | 01-APR-14:10 | 3504.07 | 16-OCT-10:50 |
| Heating:EnergyTransfer:Zone:M NE APARTMENT | 0.04 | 0.00 | 01-JAN-00:10 | 742.23 | 30-MAR-04:00 |
| General:Heating:EnergyTransfer:Zone:M NE APARTMENT | 0.04 | 0.00 | 01-JAN-00:10 | 742.23 | 30-MAR-04:00 |
| Cooling:EnergyTransfer:Zone:M NE APARTMENT | 26.88 | 0.00 | 02-JAN-02:00 | 3504.07 | 16-OCT-10:50 |
| General:Cooling:EnergyTransfer:Zone:M NE APARTMENT | 26.88 | 0.00 | 02-JAN-02:00 | 3504.07 | 16-OCT-10:50 |
| EnergyTransfer:Zone:M N1 APARTMENT | 26.22 | 0.24 | 10-MAR-12:30 | 2347.36 | 29-SEP-16:10 |
| Heating:EnergyTransfer:Zone:M N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 196.89 | 13-JAN-14:00 |
| General:Heating:EnergyTransfer:Zone:M N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 196.89 | 13-JAN-14:00 |
| Cooling:EnergyTransfer:Zone:M N1 APARTMENT | 26.22 | 0.00 | 13-JAN-11:10 | 2347.36 | 29-SEP-16:10 |
| General:Cooling:EnergyTransfer:Zone:M N1 APARTMENT | 26.22 | 0.00 | 13-JAN-11:10 | 2347.36 | 29-SEP-16:10 |
| EnergyTransfer:Zone:M N2 APARTMENT | 26.21 | 0.30 | 10-MAR-12:10 | 2354.94 | 16-OCT-12:00 |
| Heating:EnergyTransfer:Zone:M N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 196.05 | 13-JAN-14:00 |
| General:Heating:EnergyTransfer:Zone:M N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 196.05 | 13-JAN-14:00 |
| Cooling:EnergyTransfer:Zone:M N2 APARTMENT | 26.21 | 0.00 | 13-JAN-11:10 | 2354.94 | 16-OCT-12:00 |
| General:Cooling:EnergyTransfer:Zone:M N2 APARTMENT | 26.21 | 0.00 | 13-JAN-11:10 | 2354.94 | 16-OCT-12:00 |
| EnergyTransfer:Zone:M S1 APARTMENT | 38.96 | 31.08 | 01-APR-10:50 | 4347.96 | 16-OCT-12:00 |
| Heating:EnergyTransfer:Zone:M S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:Heating:EnergyTransfer:Zone:M S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Cooling:EnergyTransfer:Zone:M S1 APARTMENT | 38.96 | 31.08 | 01-APR-10:50 | 4347.96 | 16-OCT-12:00 |
| General:Cooling:EnergyTransfer:Zone:M S1 APARTMENT | 38.96 | 31.08 | 01-APR-10:50 | 4347.96 | 16-OCT-12:00 |
| EnergyTransfer:Zone:M S2 APARTMENT | 38.96 | 38.58 | 01-APR-10:40 | 4360.38 | 16-OCT-12:00 |
| Heating:EnergyTransfer:Zone:M S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:Heating:EnergyTransfer:Zone:M S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Cooling:EnergyTransfer:Zone:M S2 APARTMENT | 38.96 | 38.58 | 01-APR-10:40 | 4360.38 | 16-OCT-12:00 |
| General:Cooling:EnergyTransfer:Zone:M S2 APARTMENT | 38.96 | 38.58 | 01-APR-10:40 | 4360.38 | 16-OCT-12:00 |
| EnergyTransfer:Zone:T SW APARTMENT | 16.79 | 0.03 | 12-FEB-12:50 | 3608.48 | 16-OCT-13:40 |
| Heating:EnergyTransfer:Zone:T SW APARTMENT | 0.95 | 0.00 | 01-JAN-07:50 | 1280.46 | 30-MAR-04:00 |
| General:Heating:EnergyTransfer:Zone:T SW APARTMENT | 0.95 | 0.00 | 01-JAN-07:50 | 1280.46 | 30-MAR-04:00 |
| Cooling:EnergyTransfer:Zone:T SW APARTMENT | 15.83 | 0.00 | 01-JAN-00:10 | 3608.48 | 16-OCT-13:40 |
| General:Cooling:EnergyTransfer:Zone:T SW APARTMENT | 15.83 | 0.00 | 01-JAN-00:10 | 3608.48 | 16-OCT-13:40 |
| EnergyTransfer:Zone:T NW APARTMENT | 12.35 | 0.05 | 09-OCT-09:50 | 2617.16 | 29-SEP-15:30 |
| Heating:EnergyTransfer:Zone:T NW APARTMENT | 1.80 | 0.00 | 01-JAN-12:30 | 1306.16 | 30-MAR-04:00 |
| General:Heating:EnergyTransfer:Zone:T NW APARTMENT | 1.80 | 0.00 | 01-JAN-12:30 | 1306.16 | 30-MAR-04:00 |
| Cooling:EnergyTransfer:Zone:T NW APARTMENT | 10.55 | 0.00 | 01-JAN-00:10 | 2617.16 | 29-SEP-15:30 |
| General:Cooling:EnergyTransfer:Zone:T NW APARTMENT | 10.55 | 0.00 | 01-JAN-00:10 | 2617.16 | 29-SEP-15:30 |
| EnergyTransfer:Zone:T SE APARTMENT | 16.42 | 0.04 | 17-NOV-01:00 | 3710.78 | 16-OCT-12:00 |
| Heating:EnergyTransfer:Zone:T SE APARTMENT | 0.94 | 0.00 | 01-JAN-07:40 | 1338.49 | 30-MAR-04:00 |
| General:Heating:EnergyTransfer:Zone:T SE APARTMENT | 0.94 | 0.00 | 01-JAN-07:40 | 1338.49 | 30-MAR-04:00 |
| Cooling:EnergyTransfer:Zone:T SE APARTMENT | 15.47 | 0.00 | 01-JAN-00:10 | 3710.78 | 16-OCT-12:00 |
| General:Cooling:EnergyTransfer:Zone:T SE APARTMENT | 15.47 | 0.00 | 01-JAN-00:10 | 3710.78 | 16-OCT-12:00 |
| EnergyTransfer:Zone:T NE APARTMENT | 12.00 | 0.11 | 17-DEC-12:20 | 2396.88 | 16-OCT-12:00 |
| Heating:EnergyTransfer:Zone:T NE APARTMENT | 1.75 | 0.00 | 01-JAN-08:00 | 1362.10 | 30-MAR-04:00 |
| General:Heating:EnergyTransfer:Zone:T NE APARTMENT | 1.75 | 0.00 | 01-JAN-08:00 | 1362.10 | 30-MAR-04:00 |
| Cooling:EnergyTransfer:Zone:T NE APARTMENT | 10.26 | 0.00 | 01-JAN-00:10 | 2396.88 | 16-OCT-12:00 |
| General:Cooling:EnergyTransfer:Zone:T NE APARTMENT | 10.26 | 0.00 | 01-JAN-00:10 | 2396.88 | 16-OCT-12:00 |
| EnergyTransfer:Zone:T N1 APARTMENT | 10.04 | 0.04 | 07-NOV-04:40 | 1709.32 | 29-SEP-14:10 |
| Heating:EnergyTransfer:Zone:T N1 APARTMENT | 0.65 | 0.00 | 01-JAN-08:00 | 790.60 | 30-MAR-04:00 |
| General:Heating:EnergyTransfer:Zone:T N1 APARTMENT | 0.65 | 0.00 | 01-JAN-08:00 | 790.60 | 30-MAR-04:00 |
| Cooling:EnergyTransfer:Zone:T N1 APARTMENT | 9.40 | 0.00 | 01-JAN-00:10 | 1709.32 | 29-SEP-14:10 |
| General:Cooling:EnergyTransfer:Zone:T N1 APARTMENT | 9.40 | 0.00 | 01-JAN-00:10 | 1709.32 | 29-SEP-14:10 |
| EnergyTransfer:Zone:T N2 APARTMENT | 10.05 | 0.04 | 27-NOV-11:00 | 1710.79 | 29-SEP-14:10 |
| Heating:EnergyTransfer:Zone:T N2 APARTMENT | 0.65 | 0.00 | 01-JAN-08:00 | 795.72 | 30-MAR-04:00 |
| General:Heating:EnergyTransfer:Zone:T N2 APARTMENT | 0.65 | 0.00 | 01-JAN-08:00 | 795.72 | 30-MAR-04:00 |
| Cooling:EnergyTransfer:Zone:T N2 APARTMENT | 9.40 | 0.00 | 01-JAN-00:10 | 1710.79 | 29-SEP-14:10 |
| General:Cooling:EnergyTransfer:Zone:T N2 APARTMENT | 9.40 | 0.00 | 01-JAN-00:10 | 1710.79 | 29-SEP-14:10 |
| EnergyTransfer:Zone:T S1 APARTMENT | 15.09 | 0.01 | 27-FEB-06:30 | 3006.86 | 16-OCT-12:40 |
| Heating:EnergyTransfer:Zone:T S1 APARTMENT | 0.20 | 0.00 | 01-JAN-00:10 | 763.57 | 30-MAR-04:00 |
| General:Heating:EnergyTransfer:Zone:T S1 APARTMENT | 0.20 | 0.00 | 01-JAN-00:10 | 763.57 | 30-MAR-04:00 |
| Cooling:EnergyTransfer:Zone:T S1 APARTMENT | 14.89 | 0.00 | 01-JAN-00:20 | 3006.86 | 16-OCT-12:40 |
| General:Cooling:EnergyTransfer:Zone:T S1 APARTMENT | 14.89 | 0.00 | 01-JAN-00:20 | 3006.86 | 16-OCT-12:40 |
| EnergyTransfer:Zone:T S2 APARTMENT | 15.11 | 0.05 | 13-MAY-01:20 | 3016.69 | 16-OCT-12:40 |
| Heating:EnergyTransfer:Zone:T S2 APARTMENT | 0.20 | 0.00 | 01-JAN-00:10 | 769.23 | 30-MAR-04:00 |
| General:Heating:EnergyTransfer:Zone:T S2 APARTMENT | 0.20 | 0.00 | 01-JAN-00:10 | 769.23 | 30-MAR-04:00 |
| Cooling:EnergyTransfer:Zone:T S2 APARTMENT | 14.91 | 0.00 | 01-JAN-00:20 | 3016.69 | 16-OCT-12:40 |
| General:Cooling:EnergyTransfer:Zone:T S2 APARTMENT | 14.91 | 0.00 | 01-JAN-00:20 | 3016.69 | 16-OCT-12:40 |
| EnergyTransfer:Zone:T CORRIDOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Heating:EnergyTransfer:Zone:T CORRIDOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:Heating:EnergyTransfer:Zone:T CORRIDOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Cooling:EnergyTransfer:Zone:T CORRIDOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:Cooling:EnergyTransfer:Zone:T CORRIDOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| EnergyTransfer:Zone:G CORRIDOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Heating:EnergyTransfer:Zone:G CORRIDOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:Heating:EnergyTransfer:Zone:G CORRIDOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Cooling:EnergyTransfer:Zone:G CORRIDOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:Cooling:EnergyTransfer:Zone:G CORRIDOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| EnergyTransfer:Zone:M CORRIDOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Heating:EnergyTransfer:Zone:M CORRIDOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:Heating:EnergyTransfer:Zone:M CORRIDOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Cooling:EnergyTransfer:Zone:M CORRIDOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:Cooling:EnergyTransfer:Zone:M CORRIDOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| EnergyTransfer:HVAC | 350.34 | 0.00 | 13-JAN-23:20 | 85237.33 | 16-OCT-12:00 |
| HeatRecoveryForHeating:EnergyTransfer | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 15-APR-16:50 |
| HeatRecoveryForCooling:EnergyTransfer | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 23-MAR-15:30 |
| HeatingCoils:EnergyTransfer | 20.17 | 0.00 | 03-JAN-12:00 | 24316.88 | 30-MAR-04:00 |
| CoolingCoils:EnergyTransfer | 330.17 | 0.00 | 01-JAN-00:10 | 85237.33 | 16-OCT-12:00 |
| PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 09:15:25
Annual Building Sensible Heat Gain Components| HVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
| G SW APARTMENT | 0.109 | -6.791 | 0.183 | -6.578 | 0.000 | 0.000 | 3.705 | 1.454 | 12.213 | 9.893 | 0.000 | 0.037 | 0.000 | 0.000 | -5.033 | 0.000 | -4.098 | -5.094 |
| G NW APARTMENT | 0.115 | -6.292 | 0.846 | -3.600 | 0.000 | 0.000 | 3.854 | 1.454 | 12.213 | 5.134 | 0.000 | 0.039 | 0.000 | 0.000 | -4.820 | 0.000 | -3.712 | -5.231 |
| OFFICE | 0.000 | 0.000 | 0.782 | -9.866 | 0.000 | 0.000 | 1.993 | 7.396 | 9.469 | 9.276 | 0.000 | 0.026 | 0.000 | 0.000 | -5.378 | 0.000 | -2.387 | -11.310 |
| G NE APARTMENT | 0.113 | -6.276 | 0.841 | -3.411 | 0.000 | 0.000 | 3.862 | 1.454 | 12.213 | 4.615 | 0.000 | 0.038 | 0.000 | 0.000 | -4.659 | 0.000 | -3.713 | -5.077 |
| G N1 APARTMENT | 0.114 | -6.476 | 0.267 | -3.222 | 0.000 | 0.000 | 3.811 | 1.454 | 12.213 | 1.477 | 0.000 | 0.023 | 0.000 | 0.000 | -3.041 | 0.000 | -3.020 | -3.601 |
| G N2 APARTMENT | 0.114 | -6.475 | 0.267 | -3.208 | 0.000 | 0.000 | 3.812 | 1.454 | 12.213 | 1.477 | 0.000 | 0.023 | 0.000 | 0.000 | -3.040 | 0.000 | -3.019 | -3.619 |
| G S1 APARTMENT | 0.109 | -7.020 | 0.027 | -6.994 | 0.000 | 0.000 | 3.648 | 1.454 | 12.213 | 6.351 | 0.000 | 0.022 | 0.000 | 0.000 | -3.172 | 0.000 | -3.353 | -3.285 |
| G S2 APARTMENT | 0.109 | -7.042 | 0.025 | -7.646 | 0.000 | 0.000 | 3.643 | 1.454 | 12.213 | 6.340 | 0.000 | 0.022 | 0.000 | 0.000 | -3.186 | 0.000 | -3.367 | -2.566 |
| M SW APARTMENT | 0.218 | -14.198 | 0.077 | -24.899 | 0.000 | 0.000 | 7.260 | 2.908 | 24.426 | 19.297 | 0.000 | 0.105 | 6.466 | 0.000 | -10.661 | 0.000 | -11.000 | -0.000 |
| M NW APARTMENT | 0.221 | -13.536 | 0.467 | -14.603 | 0.000 | 0.000 | 7.494 | 2.908 | 24.426 | 9.743 | 0.000 | 0.106 | 3.618 | 0.000 | -10.451 | 0.000 | -10.393 | -0.000 |
| M SE APARTMENT | 0.218 | -14.211 | 0.077 | -24.286 | 0.000 | 0.000 | 7.262 | 2.908 | 24.426 | 18.437 | 0.000 | 0.105 | 6.620 | 0.000 | -10.531 | 0.000 | -11.025 | -0.000 |
| M NE APARTMENT | 0.219 | -13.545 | 0.463 | -13.970 | 0.000 | 0.000 | 7.500 | 2.908 | 24.426 | 8.692 | 0.000 | 0.105 | 3.765 | 0.000 | -10.128 | 0.000 | -10.436 | -0.000 |
| M N1 APARTMENT | 0.220 | -13.932 | 0.043 | -12.546 | 0.000 | 0.000 | 7.401 | 2.908 | 24.426 | 2.709 | 0.000 | 0.064 | 3.495 | 0.000 | -6.590 | 0.000 | -8.199 | -0.000 |
| M N2 APARTMENT | 0.220 | -13.933 | 0.043 | -12.531 | 0.000 | 0.000 | 7.401 | 2.908 | 24.426 | 2.708 | 0.000 | 0.064 | 3.484 | 0.000 | -6.589 | 0.000 | -8.202 | -0.000 |
| M S1 APARTMENT | 0.218 | -14.492 | 0.004 | -24.687 | 0.000 | 0.000 | 7.183 | 2.908 | 24.426 | 12.472 | 0.000 | 0.063 | 7.146 | 0.000 | -6.640 | 0.000 | -8.602 | -0.000 |
| M S2 APARTMENT | 0.218 | -14.492 | 0.004 | -24.686 | 0.000 | 0.000 | 7.183 | 2.908 | 24.426 | 12.471 | 0.000 | 0.063 | 7.145 | 0.000 | -6.639 | 0.000 | -8.602 | -0.000 |
| T SW APARTMENT | 0.109 | -6.387 | 2.217 | -10.822 | 0.000 | 0.000 | 3.809 | 1.454 | 12.213 | 9.703 | 0.000 | 0.068 | 0.000 | 0.000 | -4.749 | 0.000 | -6.254 | -1.361 |
| T NW APARTMENT | 0.113 | -6.080 | 3.617 | -6.393 | 0.000 | 0.000 | 3.907 | 1.454 | 12.213 | 4.958 | 0.000 | 0.070 | 0.000 | 0.000 | -4.648 | 0.000 | -5.845 | -3.364 |
| T SE APARTMENT | 0.109 | -6.400 | 2.194 | -10.438 | 0.000 | 0.000 | 3.815 | 1.454 | 12.213 | 9.288 | 0.000 | 0.068 | 0.000 | 0.000 | -4.694 | 0.000 | -6.316 | -1.293 |
| T NE APARTMENT | 0.110 | -6.071 | 3.543 | -6.095 | 0.000 | 0.000 | 3.917 | 1.454 | 12.213 | 4.464 | 0.000 | 0.069 | 0.000 | 0.000 | -4.503 | 0.000 | -5.894 | -3.207 |
| T N1 APARTMENT | 0.112 | -6.182 | 1.999 | -4.684 | 0.000 | 0.000 | 3.880 | 1.454 | 12.213 | 1.430 | 0.000 | 0.042 | 0.000 | 0.000 | -2.916 | 0.000 | -4.442 | -2.907 |
| T N2 APARTMENT | 0.112 | -6.180 | 2.008 | -4.691 | 0.000 | 0.000 | 3.881 | 1.454 | 12.213 | 1.428 | 0.000 | 0.042 | 0.000 | 0.000 | -2.913 | 0.000 | -4.446 | -2.908 |
| T S1 APARTMENT | 0.109 | -6.573 | 0.907 | -9.131 | 0.000 | 0.000 | 3.763 | 1.454 | 12.213 | 6.287 | 0.000 | 0.041 | 0.000 | 0.000 | -2.993 | 0.000 | -4.842 | -1.236 |
| T S2 APARTMENT | 0.109 | -6.572 | 0.911 | -9.153 | 0.000 | 0.000 | 3.764 | 1.454 | 12.213 | 6.285 | 0.000 | 0.041 | 0.000 | 0.000 | -2.990 | 0.000 | -4.844 | -1.219 |
| T CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 6.095 | 11.688 | 0.000 | 0.736 | 0.000 | 0.007 | 0.000 | 0.000 | -0.506 | 0.000 | -0.759 | -17.262 |
| G CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 6.182 | 11.688 | 3.530 | 2.218 | 0.000 | 0.112 | 0.000 | 0.000 | -1.494 | 0.000 | -18.337 | -3.899 |
| M CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 11.162 | 23.376 | 0.000 | 1.404 | 0.000 | 0.009 | 0.000 | 0.000 | -1.140 | 0.000 | -1.337 | -33.474 |
| Total Facility | 3.418 | -209.154 | 21.812 | -258.139 | 0.000 | 0.000 | 141.188 | 99.229 | 391.594 | 179.296 | 0.000 | 1.477 | 41.741 | 0.000 | -134.103 | 0.000 | -166.444 | -111.913 |
| Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
| G SW APARTMENT | 16-OCT-14:10 | 0.00 | 258.43 | 0.00 | -2414.36 | 0.00 | 0.00 | 0.00 | 30.38 | 400.26 | 1837.71 | 0.00 | 125.98 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -238.41 |
| G NW APARTMENT | 29-SEP-16:04 | 0.00 | 259.05 | 0.00 | -1643.64 | 0.00 | 0.00 | 86.96 | 86.80 | 588.62 | 961.69 | 0.00 | 97.30 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -436.77 |
| OFFICE | 22-NOV-09:02 | 0.00 | 0.00 | 0.00 | -5546.15 | 0.00 | 0.00 | 284.42 | 582.92 | 588.62 | 1527.11 | 0.00 | 0.00 | 2583.96 | 0.00 | -0.00 | 0.00 | -20.88 | 0.00 |
| G NE APARTMENT | 16-OCT-11:00 | 0.00 | 424.10 | 0.00 | -1817.50 | 0.00 | 0.00 | 41.81 | 17.36 | 412.04 | 681.66 | 0.00 | 270.48 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -29.94 |
| G N1 APARTMENT | 16-OCT-12:00 | 0.00 | 393.18 | 0.00 | -1368.62 | 0.00 | 0.00 | 41.81 | 17.36 | 406.15 | 347.42 | 0.00 | 150.94 | 11.77 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| G N2 APARTMENT | 16-OCT-12:00 | 0.00 | 393.18 | 0.00 | -1373.33 | 0.00 | 0.00 | 41.81 | 17.36 | 406.15 | 347.34 | 0.00 | 150.94 | 16.55 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| G S1 APARTMENT | 16-OCT-12:30 | 0.00 | 363.58 | 0.00 | -2195.81 | 0.00 | 0.00 | 0.00 | 17.36 | 388.49 | 1448.56 | 0.00 | 132.08 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -154.25 |
| G S2 APARTMENT | 16-OCT-12:00 | 0.00 | 393.05 | 0.00 | -2315.82 | 0.00 | 0.00 | 0.00 | 17.36 | 406.15 | 1498.95 | 0.00 | 150.94 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -150.63 |
| M SW APARTMENT | 15-OCT-15:10 | 0.00 | 465.21 | 0.00 | -5846.12 | 0.00 | 0.00 | 334.45 | 121.52 | 941.80 | 3336.50 | 0.00 | 286.55 | 360.09 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| M NW APARTMENT | 29-SEP-16:08 | 0.00 | 518.10 | 0.00 | -4260.04 | 0.00 | 0.00 | 173.91 | 173.60 | 1177.25 | 1908.75 | 0.00 | 278.92 | 29.51 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| M SE APARTMENT | 16-OCT-12:00 | 0.00 | 786.19 | 0.00 | -6246.29 | 0.00 | 0.00 | 0.00 | 34.72 | 812.30 | 3434.78 | 0.00 | 718.04 | 460.26 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| M NE APARTMENT | 16-OCT-10:50 | 0.00 | 827.41 | 0.00 | -4331.78 | 0.00 | 0.00 | 83.61 | 34.72 | 824.07 | 1421.94 | 0.00 | 779.23 | 360.81 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| M N1 APARTMENT | 29-SEP-16:04 | 0.00 | 518.10 | 0.00 | -2866.09 | 0.00 | 0.00 | 173.91 | 173.60 | 1177.25 | 370.51 | 0.00 | 168.24 | 284.49 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| M N2 APARTMENT | 16-OCT-12:00 | 0.00 | 786.37 | 0.00 | -3141.47 | 0.00 | 0.00 | 83.61 | 34.72 | 812.30 | 695.68 | 0.00 | 433.10 | 295.69 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| M S1 APARTMENT | 16-OCT-12:00 | 0.00 | 786.13 | 0.00 | -5134.36 | 0.00 | 0.00 | 0.00 | 34.72 | 812.30 | 2991.15 | 0.00 | 433.10 | 76.97 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| M S2 APARTMENT | 16-OCT-12:00 | 0.00 | 786.13 | 0.00 | -5146.78 | 0.00 | 0.00 | 0.00 | 34.72 | 812.30 | 2991.02 | 0.00 | 433.10 | 89.52 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| T SW APARTMENT | 16-OCT-13:40 | 0.00 | 290.60 | 0.00 | -3899.06 | 0.00 | 0.00 | 0.00 | 17.36 | 382.60 | 1857.31 | 0.00 | 289.31 | 1061.88 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| T NW APARTMENT | 29-SEP-15:30 | 0.00 | 285.02 | 0.00 | -2902.21 | 0.00 | 0.00 | 50.17 | 60.76 | 470.90 | 1163.31 | 0.00 | 242.50 | 629.55 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| T SE APARTMENT | 16-OCT-12:00 | 0.00 | 393.10 | 0.00 | -4104.14 | 0.00 | 0.00 | 0.00 | 17.36 | 406.15 | 1688.44 | 0.00 | 473.33 | 1125.75 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| T NE APARTMENT | 16-OCT-12:00 | 0.00 | 393.21 | 0.00 | -2790.27 | 0.00 | 0.00 | 41.81 | 17.36 | 406.15 | 558.93 | 0.00 | 473.33 | 899.48 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| T N1 APARTMENT | 29-SEP-14:10 | 0.00 | 326.47 | 0.00 | -2035.90 | 0.00 | 0.00 | 41.81 | 30.38 | 400.26 | 313.92 | 0.00 | 206.36 | 716.70 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| T N2 APARTMENT | 29-SEP-14:10 | 0.00 | 326.47 | 0.00 | -2037.37 | 0.00 | 0.00 | 41.81 | 30.38 | 400.26 | 313.89 | 0.00 | 206.36 | 718.20 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| T S1 APARTMENT | 16-OCT-12:40 | 0.00 | 353.76 | 0.00 | -3360.73 | 0.00 | 0.00 | 0.00 | 17.36 | 388.49 | 1398.90 | 0.00 | 238.28 | 963.95 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| T S2 APARTMENT | 16-OCT-12:40 | 0.00 | 353.76 | 0.00 | -3370.57 | 0.00 | 0.00 | 0.00 | 17.36 | 388.49 | 1398.77 | 0.00 | 238.28 | 973.91 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| T CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| G CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Total Facility | 16-OCT-12:00 | 0.00 | 12187.33 | 0.00 | -77635.93 | 0.00 | 0.00 | 894.80 | 2538.77 | 13212.14 | 33661.11 | 0.00 | 10124.01 | 5017.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
| G SW APARTMENT | 30-MAR-04:00 | -499.62 | 0.00 | 873.22 | 0.00 | 0.00 | 0.00 | 194.99 | 26.04 | 223.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -470.17 | 0.00 | -278.99 | -69.15 |
| G NW APARTMENT | 30-MAR-04:00 | -499.62 | 0.00 | 922.37 | 0.00 | 0.00 | 0.00 | 194.99 | 26.04 | 223.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -460.32 | 0.00 | -278.99 | -128.16 |
| OFFICE | 14-OCT-12:00 | 0.00 | 0.00 | 637.00 | 0.00 | 0.00 | 0.00 | 0.00 | 116.58 | 194.25 | 1572.54 | 0.00 | 138.54 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -2658.91 |
| G NE APARTMENT | 29-MAR-16:01 | -330.94 | 0.00 | 1329.73 | 0.00 | 0.00 | 0.00 | 102.10 | 86.80 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -14.90 | 0.00 | 0.00 | -1761.42 |
| G N1 APARTMENT | 13-JAN-14:00 | 114.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.54 | 17.36 | 388.49 | 189.93 | 0.00 | 21.58 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -776.57 |
| G N2 APARTMENT | 13-JAN-14:00 | 114.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.52 | 17.36 | 388.49 | 189.80 | 0.00 | 21.52 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -776.10 |
| G S1 APARTMENT | 01-APR-12:00 | 33.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86.01 | 17.36 | 406.15 | 987.82 | 0.00 | 5.45 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -1535.81 |
| G S2 APARTMENT | 01-APR-12:00 | 31.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85.77 | 17.36 | 406.15 | 986.98 | 0.00 | 4.83 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -1532.65 |
| M SW APARTMENT | 30-MAR-04:00 | -999.12 | 0.00 | 1507.14 | 0.00 | 0.00 | 0.00 | 389.98 | 52.08 | 447.35 | 0.00 | 0.00 | 0.00 | 375.25 | 0.00 | -969.89 | 0.00 | -802.80 | 0.00 |
| M NW APARTMENT | 30-MAR-04:00 | -999.12 | 0.00 | 1630.43 | 0.00 | 0.00 | 0.00 | 389.98 | 52.08 | 447.35 | 0.00 | 0.00 | 0.00 | 232.12 | 0.00 | -950.06 | 0.00 | -802.80 | 0.00 |
| M SE APARTMENT | 30-MAR-04:00 | -999.12 | 0.00 | 1630.07 | 0.00 | 0.00 | 0.00 | 389.98 | 52.08 | 447.35 | 0.00 | 0.00 | 0.00 | 259.33 | 0.00 | -976.89 | 0.00 | -802.80 | 0.00 |
| M NE APARTMENT | 30-MAR-04:00 | -999.12 | 0.00 | 1741.34 | 0.00 | 0.00 | 0.00 | 389.98 | 52.08 | 447.35 | 0.00 | 0.00 | 0.00 | 128.30 | 0.00 | -957.14 | 0.00 | -802.80 | 0.00 |
| M N1 APARTMENT | 13-JAN-14:00 | 196.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86.52 | 34.72 | 776.98 | 358.75 | 0.00 | 50.99 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -1504.88 |
| M N2 APARTMENT | 13-JAN-14:00 | 196.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86.45 | 34.72 | 776.98 | 358.29 | 0.00 | 50.72 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -1503.23 |
| M S1 APARTMENT | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M S2 APARTMENT | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T SW APARTMENT | 30-MAR-04:00 | -499.52 | 0.00 | 1779.95 | 0.00 | 0.00 | 0.00 | 194.99 | 26.04 | 223.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -457.74 | 0.00 | -532.23 | -735.17 |
| T NW APARTMENT | 30-MAR-04:00 | -499.52 | 0.00 | 1805.65 | 0.00 | 0.00 | 0.00 | 194.99 | 26.04 | 223.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -448.84 | 0.00 | -532.23 | -769.77 |
| T SE APARTMENT | 30-MAR-04:00 | -499.52 | 0.00 | 1837.98 | 0.00 | 0.00 | 0.00 | 194.99 | 26.04 | 223.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -461.46 | 0.00 | -532.23 | -789.48 |
| T NE APARTMENT | 30-MAR-04:00 | -499.52 | 0.00 | 1861.59 | 0.00 | 0.00 | 0.00 | 194.99 | 26.04 | 223.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -452.71 | 0.00 | -532.23 | -821.84 |
| T N1 APARTMENT | 30-MAR-04:00 | -499.60 | 0.00 | 1290.18 | 0.00 | 0.00 | 0.00 | 194.99 | 26.04 | 223.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -274.95 | 0.00 | -321.03 | -639.32 |
| T N2 APARTMENT | 30-MAR-04:00 | -499.60 | 0.00 | 1295.30 | 0.00 | 0.00 | 0.00 | 194.99 | 26.04 | 223.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -274.85 | 0.00 | -321.03 | -644.53 |
| T S1 APARTMENT | 30-MAR-04:00 | -499.60 | 0.00 | 1263.15 | 0.00 | 0.00 | 0.00 | 194.99 | 26.04 | 223.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -283.76 | 0.00 | -321.03 | -603.48 |
| T S2 APARTMENT | 30-MAR-04:00 | -499.60 | 0.00 | 1268.82 | 0.00 | 0.00 | 0.00 | 194.99 | 26.04 | 223.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -283.65 | 0.00 | -321.03 | -609.25 |
| T CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| G CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Total Facility | 30-MAR-04:00 | -15772.68 | 285.06 | 25448.92 | -285.06 | 0.00 | 0.00 | 7314.98 | 2406.37 | 7184.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -12466.61 | 0.00 | -10612.95 | -3502.43 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 09:15:25
System Ventilation Requirements for Cooling| Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
| SPLIT GSW | 0.3060 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.3060 | 0.0848 | 1.0000 | Not calculated | 0.0260 | 0.0848 | ||
| SPLIT GNW | 0.2807 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.2807 | 0.0925 | 1.0000 | Not calculated | 0.0260 | 0.0925 | ||
| SPLIT OFFICE | 0.3593 | 0.0000 | 4.7495 | 1.0000 | Calculated from schedules | 0.0381 | 0.3593 | 0.1061 | 1.0000 | Not calculated | 0.0381 | 0.1061 | ||
| SPLIT GNE | 0.2618 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.2618 | 0.0991 | 1.0000 | Not calculated | 0.0260 | 0.0991 | ||
| SPLIT GN1 | 0.2469 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.2469 | 0.1051 | 1.0000 | Not calculated | 0.0260 | 0.1051 | ||
| SPLIT GN2 | 0.2464 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.2464 | 0.1053 | 1.0000 | Not calculated | 0.0260 | 0.1053 | ||
| SPLIT GS1 | 0.2711 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.2711 | 0.0957 | 1.0000 | Not calculated | 0.0260 | 0.0957 | ||
| SPLIT GS2 | 0.2731 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.2731 | 0.0950 | 1.0000 | Not calculated | 0.0260 | 0.0950 | ||
| SPLIT MSW | 0.7579 | 0.0000 | 5.0000 | 1.0000 | Calculated from schedules | 0.0519 | 0.7579 | 0.0685 | 1.0000 | Not calculated | 0.0519 | 0.0685 | ||
| SPLIT MNW | 0.7114 | 0.0000 | 5.0000 | 1.0000 | Calculated from schedules | 0.0519 | 0.7114 | 0.0730 | 1.0000 | Not calculated | 0.0519 | 0.0730 | ||
| SPLIT MSE | 0.7061 | 0.0000 | 5.0000 | 1.0000 | Calculated from schedules | 0.0519 | 0.7061 | 0.0735 | 1.0000 | Not calculated | 0.0519 | 0.0735 | ||
| SPLIT MNE | 0.6601 | 0.0000 | 5.0000 | 1.0000 | Calculated from schedules | 0.0519 | 0.6601 | 0.0786 | 1.0000 | Not calculated | 0.0519 | 0.0786 | ||
| SPLIT MN1 | 0.6057 | 0.0000 | 5.0000 | 1.0000 | Calculated from schedules | 0.0519 | 0.6057 | 0.0857 | 1.0000 | Not calculated | 0.0519 | 0.0857 | ||
| SPLIT MN2 | 0.6047 | 0.0000 | 5.0000 | 1.0000 | Calculated from schedules | 0.0519 | 0.6047 | 0.0858 | 1.0000 | Not calculated | 0.0519 | 0.0858 | ||
| SPLIT MS1 | 0.6574 | 0.0000 | 5.0000 | 1.0000 | Calculated from schedules | 0.0519 | 0.6574 | 0.0790 | 1.0000 | Not calculated | 0.0519 | 0.0790 | ||
| SPLIT MS2 | 0.6563 | 0.0000 | 5.0000 | 1.0000 | Calculated from schedules | 0.0519 | 0.6563 | 0.0791 | 1.0000 | Not calculated | 0.0519 | 0.0791 | ||
| SPLIT TSW | 0.4027 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.4027 | 0.0645 | 1.0000 | Not calculated | 0.0260 | 0.0645 | ||
| SPLIT TNW | 0.3846 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.3846 | 0.0675 | 1.0000 | Not calculated | 0.0260 | 0.0675 | ||
| SPLIT TSE | 0.3628 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.3628 | 0.0715 | 1.0000 | Not calculated | 0.0260 | 0.0715 | ||
| SPLIT TNE | 0.3447 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.3447 | 0.0753 | 1.0000 | Not calculated | 0.0260 | 0.0753 | ||
| SPLIT TN1 | 0.3270 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.3270 | 0.0794 | 1.0000 | Not calculated | 0.0260 | 0.0794 | ||
| SPLIT TN2 | 0.3255 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.3255 | 0.0797 | 1.0000 | Not calculated | 0.0260 | 0.0797 | ||
| SPLIT TS1 | 0.3466 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.3466 | 0.0749 | 1.0000 | Not calculated | 0.0260 | 0.0749 | ||
| SPLIT TS2 | 0.3451 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.3451 | 0.0752 | 1.0000 | Not calculated | 0.0260 | 0.0752 |
| Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
| SPLIT GSW | 0.3060 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.3060 | 1.0000 | 1.0000 | Not calculated | 0.0260 | 0.0848 | ||
| SPLIT GNW | 0.2807 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.2807 | 1.0000 | 1.0000 | Not calculated | 0.0260 | 0.0925 | ||
| SPLIT OFFICE | 0.3593 | 0.0000 | 4.7495 | 1.0000 | Calculated from schedules | 0.0381 | 0.3593 | 1.0000 | 1.0000 | Not calculated | 0.0381 | 0.1061 | ||
| SPLIT GNE | 0.2618 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.2618 | 1.0000 | 1.0000 | Not calculated | 0.0260 | 0.0991 | ||
| SPLIT GN1 | 0.2469 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.2469 | 1.0000 | 1.0000 | Not calculated | 0.0260 | 0.1051 | ||
| SPLIT GN2 | 0.2464 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.2464 | 1.0000 | 1.0000 | Not calculated | 0.0260 | 0.1053 | ||
| SPLIT GS1 | 0.2711 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.2711 | 1.0000 | 1.0000 | Not calculated | 0.0260 | 0.0957 | ||
| SPLIT GS2 | 0.2731 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.2731 | 1.0000 | 1.0000 | Not calculated | 0.0260 | 0.0950 | ||
| SPLIT MSW | 0.7579 | 0.0000 | 5.0000 | 1.0000 | Calculated from schedules | 0.0519 | 0.7579 | 1.0000 | 1.0000 | Not calculated | 0.0519 | 0.0685 | ||
| SPLIT MNW | 0.7114 | 0.0000 | 5.0000 | 1.0000 | Calculated from schedules | 0.0519 | 0.7114 | 1.0000 | 1.0000 | Not calculated | 0.0519 | 0.0730 | ||
| SPLIT MSE | 0.7061 | 0.0000 | 5.0000 | 1.0000 | Calculated from schedules | 0.0519 | 0.7061 | 1.0000 | 1.0000 | Not calculated | 0.0519 | 0.0735 | ||
| SPLIT MNE | 0.6601 | 0.0000 | 5.0000 | 1.0000 | Calculated from schedules | 0.0519 | 0.6601 | 1.0000 | 1.0000 | Not calculated | 0.0519 | 0.0786 | ||
| SPLIT MN1 | 0.6057 | 0.0000 | 5.0000 | 1.0000 | Calculated from schedules | 0.0519 | 0.6057 | 1.0000 | 1.0000 | Not calculated | 0.0519 | 0.0857 | ||
| SPLIT MN2 | 0.6047 | 0.0000 | 5.0000 | 1.0000 | Calculated from schedules | 0.0519 | 0.6047 | 1.0000 | 1.0000 | Not calculated | 0.0519 | 0.0858 | ||
| SPLIT MS1 | 0.6574 | 0.0000 | 5.0000 | 1.0000 | Calculated from schedules | 0.0519 | 0.6574 | 1.0000 | 1.0000 | Not calculated | 0.0519 | 0.0790 | ||
| SPLIT MS2 | 0.6563 | 0.0000 | 5.0000 | 1.0000 | Calculated from schedules | 0.0519 | 0.6563 | 1.0000 | 1.0000 | Not calculated | 0.0519 | 0.0791 | ||
| SPLIT TSW | 0.4027 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.4027 | 1.0000 | 1.0000 | Not calculated | 0.0260 | 0.0645 | ||
| SPLIT TNW | 0.3846 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.3846 | 1.0000 | 1.0000 | Not calculated | 0.0260 | 0.0675 | ||
| SPLIT TSE | 0.3628 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.3628 | 1.0000 | 1.0000 | Not calculated | 0.0260 | 0.0715 | ||
| SPLIT TNE | 0.3447 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.3447 | 1.0000 | 1.0000 | Not calculated | 0.0260 | 0.0753 | ||
| SPLIT TN1 | 0.3270 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.3270 | 1.0000 | 1.0000 | Not calculated | 0.0260 | 0.0794 | ||
| SPLIT TN2 | 0.3255 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.3255 | 1.0000 | 1.0000 | Not calculated | 0.0260 | 0.0797 | ||
| SPLIT TS1 | 0.3466 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.3466 | 1.0000 | 1.0000 | Not calculated | 0.0260 | 0.0749 | ||
| SPLIT TS2 | 0.3451 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.3451 | 1.0000 | 1.0000 | Not calculated | 0.0260 | 0.0752 |
| AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
| G SW APARTMENT | SPLIT GSW | 0.000000 | 2.5000 | 0.000294 | 88.25 | 0.0260 | 1.0000 | 0.0260 | 1.000 | 0.0260 |
| G NW APARTMENT | SPLIT GNW | 0.000000 | 2.5000 | 0.000294 | 88.25 | 0.0260 | 1.0000 | 0.0260 | 1.000 | 0.0260 |
| OFFICE | SPLIT OFFICE | 0.000000 | 4.7495 | 0.000432 | 88.25 | 0.0381 | 1.0000 | 0.0381 | 1.000 | 0.0381 |
| G NE APARTMENT | SPLIT GNE | 0.000000 | 2.5000 | 0.000294 | 88.25 | 0.0260 | 1.0000 | 0.0260 | 1.000 | 0.0260 |
| G N1 APARTMENT | SPLIT GN1 | 0.000000 | 2.5000 | 0.000294 | 88.25 | 0.0260 | 1.0000 | 0.0260 | 1.000 | 0.0260 |
| G N2 APARTMENT | SPLIT GN2 | 0.000000 | 2.5000 | 0.000294 | 88.25 | 0.0260 | 1.0000 | 0.0260 | 1.000 | 0.0260 |
| G S1 APARTMENT | SPLIT GS1 | 0.000000 | 2.5000 | 0.000294 | 88.25 | 0.0260 | 1.0000 | 0.0260 | 1.000 | 0.0260 |
| G S2 APARTMENT | SPLIT GS2 | 0.000000 | 2.5000 | 0.000294 | 88.25 | 0.0260 | 1.0000 | 0.0260 | 1.000 | 0.0260 |
| M SW APARTMENT | SPLIT MSW | 0.000000 | 5.0000 | 0.000294 | 176.50 | 0.0519 | 1.0000 | 0.0519 | 1.000 | 0.0519 |
| M NW APARTMENT | SPLIT MNW | 0.000000 | 5.0000 | 0.000294 | 176.50 | 0.0519 | 1.0000 | 0.0519 | 1.000 | 0.0519 |
| M SE APARTMENT | SPLIT MSE | 0.000000 | 5.0000 | 0.000294 | 176.50 | 0.0519 | 1.0000 | 0.0519 | 1.000 | 0.0519 |
| M NE APARTMENT | SPLIT MNE | 0.000000 | 5.0000 | 0.000294 | 176.50 | 0.0519 | 1.0000 | 0.0519 | 1.000 | 0.0519 |
| M N1 APARTMENT | SPLIT MN1 | 0.000000 | 5.0000 | 0.000294 | 176.50 | 0.0519 | 1.0000 | 0.0519 | 1.000 | 0.0519 |
| M N2 APARTMENT | SPLIT MN2 | 0.000000 | 5.0000 | 0.000294 | 176.50 | 0.0519 | 1.0000 | 0.0519 | 1.000 | 0.0519 |
| M S1 APARTMENT | SPLIT MS1 | 0.000000 | 5.0000 | 0.000294 | 176.50 | 0.0519 | 1.0000 | 0.0519 | 1.000 | 0.0519 |
| M S2 APARTMENT | SPLIT MS2 | 0.000000 | 5.0000 | 0.000294 | 176.50 | 0.0519 | 1.0000 | 0.0519 | 1.000 | 0.0519 |
| T SW APARTMENT | SPLIT TSW | 0.000000 | 2.5000 | 0.000294 | 88.25 | 0.0260 | 1.0000 | 0.0260 | 1.000 | 0.0260 |
| T NW APARTMENT | SPLIT TNW | 0.000000 | 2.5000 | 0.000294 | 88.25 | 0.0260 | 1.0000 | 0.0260 | 1.000 | 0.0260 |
| T SE APARTMENT | SPLIT TSE | 0.000000 | 2.5000 | 0.000294 | 88.25 | 0.0260 | 1.0000 | 0.0260 | 1.000 | 0.0260 |
| T NE APARTMENT | SPLIT TNE | 0.000000 | 2.5000 | 0.000294 | 88.25 | 0.0260 | 1.0000 | 0.0260 | 1.000 | 0.0260 |
| T N1 APARTMENT | SPLIT TN1 | 0.000000 | 2.5000 | 0.000294 | 88.25 | 0.0260 | 1.0000 | 0.0260 | 1.000 | 0.0260 |
| T N2 APARTMENT | SPLIT TN2 | 0.000000 | 2.5000 | 0.000294 | 88.25 | 0.0260 | 1.0000 | 0.0260 | 1.000 | 0.0260 |
| T S1 APARTMENT | SPLIT TS1 | 0.000000 | 2.5000 | 0.000294 | 88.25 | 0.0260 | 1.0000 | 0.0260 | 1.000 | 0.0260 |
| T S2 APARTMENT | SPLIT TS2 | 0.000000 | 2.5000 | 0.000294 | 88.25 | 0.0260 | 1.0000 | 0.0260 | 1.000 | 0.0260 |
| People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
| SPLIT GSW | 0.000000 | 2.50 | 0.000294 | 88.2493 | 0.0260 | 0.0260 | 0.0260 |
| SPLIT GNW | 0.000000 | 2.50 | 0.000294 | 88.2493 | 0.0260 | 0.0260 | 0.0260 |
| SPLIT OFFICE | 0.000000 | 4.75 | 0.000432 | 88.2493 | 0.0381 | 0.0381 | 0.0381 |
| SPLIT GNE | 0.000000 | 2.50 | 0.000294 | 88.2493 | 0.0260 | 0.0260 | 0.0260 |
| SPLIT GN1 | 0.000000 | 2.50 | 0.000294 | 88.2493 | 0.0260 | 0.0260 | 0.0260 |
| SPLIT GN2 | 0.000000 | 2.50 | 0.000294 | 88.2493 | 0.0260 | 0.0260 | 0.0260 |
| SPLIT GS1 | 0.000000 | 2.50 | 0.000294 | 88.2493 | 0.0260 | 0.0260 | 0.0260 |
| SPLIT GS2 | 0.000000 | 2.50 | 0.000294 | 88.2493 | 0.0260 | 0.0260 | 0.0260 |
| SPLIT MSW | 0.000000 | 5.00 | 0.000294 | 176.4985 | 0.0519 | 0.0519 | 0.0519 |
| SPLIT MNW | 0.000000 | 5.00 | 0.000294 | 176.4985 | 0.0519 | 0.0519 | 0.0519 |
| SPLIT MSE | 0.000000 | 5.00 | 0.000294 | 176.4985 | 0.0519 | 0.0519 | 0.0519 |
| SPLIT MNE | 0.000000 | 5.00 | 0.000294 | 176.4985 | 0.0519 | 0.0519 | 0.0519 |
| SPLIT MN1 | 0.000000 | 5.00 | 0.000294 | 176.4985 | 0.0519 | 0.0519 | 0.0519 |
| SPLIT MN2 | 0.000000 | 5.00 | 0.000294 | 176.4985 | 0.0519 | 0.0519 | 0.0519 |
| SPLIT MS1 | 0.000000 | 5.00 | 0.000294 | 176.4985 | 0.0519 | 0.0519 | 0.0519 |
| SPLIT MS2 | 0.000000 | 5.00 | 0.000294 | 176.4985 | 0.0519 | 0.0519 | 0.0519 |
| SPLIT TSW | 0.000000 | 2.50 | 0.000294 | 88.2493 | 0.0260 | 0.0260 | 0.0260 |
| SPLIT TNW | 0.000000 | 2.50 | 0.000294 | 88.2493 | 0.0260 | 0.0260 | 0.0260 |
| SPLIT TSE | 0.000000 | 2.50 | 0.000294 | 88.2493 | 0.0260 | 0.0260 | 0.0260 |
| SPLIT TNE | 0.000000 | 2.50 | 0.000294 | 88.2493 | 0.0260 | 0.0260 | 0.0260 |
| SPLIT TN1 | 0.000000 | 2.50 | 0.000294 | 88.2493 | 0.0260 | 0.0260 | 0.0260 |
| SPLIT TN2 | 0.000000 | 2.50 | 0.000294 | 88.2493 | 0.0260 | 0.0260 | 0.0260 |
| SPLIT TS1 | 0.000000 | 2.50 | 0.000294 | 88.2493 | 0.0260 | 0.0260 | 0.0260 |
| SPLIT TS2 | 0.000000 | 2.50 | 0.000294 | 88.2493 | 0.0260 | 0.0260 | 0.0260 |
| AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
| G SW APARTMENT | SPLIT GSW | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.3060 | 0.3060 | 0.3060 | No | 0.0260 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| G NW APARTMENT | SPLIT GNW | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.2807 | 0.2807 | 0.2807 | No | 0.0260 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| OFFICE | SPLIT OFFICE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.3593 | 0.3593 | 0.3593 | No | 0.0381 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| G NE APARTMENT | SPLIT GNE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.2618 | 0.2618 | 0.2618 | No | 0.0260 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| G N1 APARTMENT | SPLIT GN1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.2469 | 0.2469 | 0.2469 | No | 0.0260 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| G N2 APARTMENT | SPLIT GN2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.2464 | 0.2464 | 0.2464 | No | 0.0260 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| G S1 APARTMENT | SPLIT GS1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.2711 | 0.2711 | 0.2711 | No | 0.0260 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| G S2 APARTMENT | SPLIT GS2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.2731 | 0.2731 | 0.2731 | No | 0.0260 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| M SW APARTMENT | SPLIT MSW | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.7579 | 0.7579 | 0.7579 | No | 0.0519 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| M NW APARTMENT | SPLIT MNW | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.7114 | 0.7114 | 0.7114 | No | 0.0519 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| M SE APARTMENT | SPLIT MSE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.7061 | 0.7061 | 0.7061 | No | 0.0519 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| M NE APARTMENT | SPLIT MNE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.6601 | 0.6601 | 0.6601 | No | 0.0519 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| M N1 APARTMENT | SPLIT MN1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.6057 | 0.6057 | 0.6057 | No | 0.0519 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| M N2 APARTMENT | SPLIT MN2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.6047 | 0.6047 | 0.6047 | No | 0.0519 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| M S1 APARTMENT | SPLIT MS1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.6574 | 0.6574 | 0.6574 | No | 0.0519 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| M S2 APARTMENT | SPLIT MS2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.6563 | 0.6563 | 0.6563 | No | 0.0519 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| T SW APARTMENT | SPLIT TSW | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4027 | 0.4027 | 0.4027 | No | 0.0260 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| T NW APARTMENT | SPLIT TNW | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.3846 | 0.3846 | 0.3846 | No | 0.0260 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| T SE APARTMENT | SPLIT TSE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.3628 | 0.3628 | 0.3628 | No | 0.0260 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| T NE APARTMENT | SPLIT TNE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.3447 | 0.3447 | 0.3447 | No | 0.0260 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| T N1 APARTMENT | SPLIT TN1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.3270 | 0.3270 | 0.3270 | No | 0.0260 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| T N2 APARTMENT | SPLIT TN2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.3255 | 0.3255 | 0.3255 | No | 0.0260 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| T S1 APARTMENT | SPLIT TS1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.3466 | 0.3466 | 0.3466 | No | 0.0260 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| T S2 APARTMENT | SPLIT TS2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.3451 | 0.3451 | 0.3451 | No | 0.0260 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
| SPLIT GSW | 0.3060 | 0.3060 | 0.3060 | 0.3060 | 0.0260 | 1.0000 |
| SPLIT GNW | 0.2807 | 0.2807 | 0.2807 | 0.2807 | 0.0260 | 1.0000 |
| SPLIT OFFICE | 0.3593 | 0.3593 | 0.3593 | 0.3593 | 0.0381 | 1.0000 |
| SPLIT GNE | 0.2618 | 0.2618 | 0.2618 | 0.2618 | 0.0260 | 1.0000 |
| SPLIT GN1 | 0.2469 | 0.2469 | 0.2469 | 0.2469 | 0.0260 | 1.0000 |
| SPLIT GN2 | 0.2464 | 0.2464 | 0.2464 | 0.2464 | 0.0260 | 1.0000 |
| SPLIT GS1 | 0.2711 | 0.2711 | 0.2711 | 0.2711 | 0.0260 | 1.0000 |
| SPLIT GS2 | 0.2731 | 0.2731 | 0.2731 | 0.2731 | 0.0260 | 1.0000 |
| SPLIT MSW | 0.7579 | 0.7579 | 0.7579 | 0.7579 | 0.0519 | 1.0000 |
| SPLIT MNW | 0.7114 | 0.7114 | 0.7114 | 0.7114 | 0.0519 | 1.0000 |
| SPLIT MSE | 0.7061 | 0.7061 | 0.7061 | 0.7061 | 0.0519 | 1.0000 |
| SPLIT MNE | 0.6601 | 0.6601 | 0.6601 | 0.6601 | 0.0519 | 1.0000 |
| SPLIT MN1 | 0.6057 | 0.6057 | 0.6057 | 0.6057 | 0.0519 | 1.0000 |
| SPLIT MN2 | 0.6047 | 0.6047 | 0.6047 | 0.6047 | 0.0519 | 1.0000 |
| SPLIT MS1 | 0.6574 | 0.6574 | 0.6574 | 0.6574 | 0.0519 | 1.0000 |
| SPLIT MS2 | 0.6563 | 0.6563 | 0.6563 | 0.6563 | 0.0519 | 1.0000 |
| SPLIT TSW | 0.4027 | 0.4027 | 0.4027 | 0.4027 | 0.0260 | 1.0000 |
| SPLIT TNW | 0.3846 | 0.3846 | 0.3846 | 0.3846 | 0.0260 | 1.0000 |
| SPLIT TSE | 0.3628 | 0.3628 | 0.3628 | 0.3628 | 0.0260 | 1.0000 |
| SPLIT TNE | 0.3447 | 0.3447 | 0.3447 | 0.3447 | 0.0260 | 1.0000 |
| SPLIT TN1 | 0.3270 | 0.3270 | 0.3270 | 0.3270 | 0.0260 | 1.0000 |
| SPLIT TN2 | 0.3255 | 0.3255 | 0.3255 | 0.3255 | 0.0260 | 1.0000 |
| SPLIT TS1 | 0.3466 | 0.3466 | 0.3466 | 0.3466 | 0.0260 | 1.0000 |
| SPLIT TS2 | 0.3451 | 0.3451 | 0.3451 | 0.3451 | 0.0260 | 1.0000 |
| AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
| G SW APARTMENT | SPLIT GSW | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.3060 | 0.3060 | 0.3060 | No | 0.0260 | 0.4976 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| G NW APARTMENT | SPLIT GNW | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.2807 | 0.2807 | 0.2807 | No | 0.0260 | 0.5706 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| OFFICE | SPLIT OFFICE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.3593 | 0.3593 | 0.3593 | No | 0.0381 | 0.5198 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| G NE APARTMENT | SPLIT GNE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.2618 | 0.2618 | 0.2618 | No | 0.0260 | 0.5697 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| G N1 APARTMENT | SPLIT GN1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.2469 | 0.2469 | 0.2469 | No | 0.0260 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| G N2 APARTMENT | SPLIT GN2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.2464 | 0.2464 | 0.2464 | No | 0.0260 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| G S1 APARTMENT | SPLIT GS1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.2711 | 0.2711 | 0.2711 | No | 0.0260 | 0.8760 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| G S2 APARTMENT | SPLIT GS2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.2731 | 0.2731 | 0.2731 | No | 0.0260 | 0.8632 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| M SW APARTMENT | SPLIT MSW | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.7579 | 0.7579 | 0.7579 | No | 0.0519 | 0.5220 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| M NW APARTMENT | SPLIT MNW | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.7114 | 0.7114 | 0.7114 | No | 0.0519 | 0.6141 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| M SE APARTMENT | SPLIT MSE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.7061 | 0.7061 | 0.7061 | No | 0.0519 | 0.5210 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| M NE APARTMENT | SPLIT MNE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.6601 | 0.6601 | 0.6601 | No | 0.0519 | 0.6128 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| M N1 APARTMENT | SPLIT MN1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.6057 | 0.6057 | 0.6057 | No | 0.0519 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| M N2 APARTMENT | SPLIT MN2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.6047 | 0.6047 | 0.6047 | No | 0.0519 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| M S1 APARTMENT | SPLIT MS1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.6574 | 0.6574 | 0.6574 | No | 0.0519 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| M S2 APARTMENT | SPLIT MS2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.6563 | 0.6563 | 0.6563 | No | 0.0519 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| T SW APARTMENT | SPLIT TSW | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4027 | 0.4027 | 0.4027 | No | 0.0260 | 0.2732 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| T NW APARTMENT | SPLIT TNW | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.3846 | 0.3846 | 0.3846 | No | 0.0260 | 0.2983 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| T SE APARTMENT | SPLIT TSE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.3628 | 0.3628 | 0.3628 | No | 0.0260 | 0.2729 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| T NE APARTMENT | SPLIT TNE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.3447 | 0.3447 | 0.3447 | No | 0.0260 | 0.2980 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| T N1 APARTMENT | SPLIT TN1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.3270 | 0.3270 | 0.3270 | No | 0.0260 | 0.4512 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| T N2 APARTMENT | SPLIT TN2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.3255 | 0.3255 | 0.3255 | No | 0.0260 | 0.4512 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| T S1 APARTMENT | SPLIT TS1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.3466 | 0.3466 | 0.3466 | No | 0.0260 | 0.3957 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| T S2 APARTMENT | SPLIT TS2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.3451 | 0.3451 | 0.3451 | No | 0.0260 | 0.3957 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
| SPLIT GSW | 0.3060 | 0.3060 | 0.3060 | 0.3060 | 0.0260 | 1.0000 |
| SPLIT GNW | 0.2807 | 0.2807 | 0.2807 | 0.2807 | 0.0260 | 1.0000 |
| SPLIT OFFICE | 0.3593 | 0.3593 | 0.3593 | 0.3593 | 0.0381 | 1.0000 |
| SPLIT GNE | 0.2618 | 0.2618 | 0.2618 | 0.2618 | 0.0260 | 1.0000 |
| SPLIT GN1 | 0.2469 | 0.2469 | 0.2469 | 0.2469 | 0.0260 | 1.0000 |
| SPLIT GN2 | 0.2464 | 0.2464 | 0.2464 | 0.2464 | 0.0260 | 1.0000 |
| SPLIT GS1 | 0.2711 | 0.2711 | 0.2711 | 0.2711 | 0.0260 | 1.0000 |
| SPLIT GS2 | 0.2731 | 0.2731 | 0.2731 | 0.2731 | 0.0260 | 1.0000 |
| SPLIT MSW | 0.7579 | 0.7579 | 0.7579 | 0.7579 | 0.0519 | 1.0000 |
| SPLIT MNW | 0.7114 | 0.7114 | 0.7114 | 0.7114 | 0.0519 | 1.0000 |
| SPLIT MSE | 0.7061 | 0.7061 | 0.7061 | 0.7061 | 0.0519 | 1.0000 |
| SPLIT MNE | 0.6601 | 0.6601 | 0.6601 | 0.6601 | 0.0519 | 1.0000 |
| SPLIT MN1 | 0.6057 | 0.6057 | 0.6057 | 0.6057 | 0.0519 | 1.0000 |
| SPLIT MN2 | 0.6047 | 0.6047 | 0.6047 | 0.6047 | 0.0519 | 1.0000 |
| SPLIT MS1 | 0.6574 | 0.6574 | 0.6574 | 0.6574 | 0.0519 | 1.0000 |
| SPLIT MS2 | 0.6563 | 0.6563 | 0.6563 | 0.6563 | 0.0519 | 1.0000 |
| SPLIT TSW | 0.4027 | 0.4027 | 0.4027 | 0.4027 | 0.0260 | 1.0000 |
| SPLIT TNW | 0.3846 | 0.3846 | 0.3846 | 0.3846 | 0.0260 | 1.0000 |
| SPLIT TSE | 0.3628 | 0.3628 | 0.3628 | 0.3628 | 0.0260 | 1.0000 |
| SPLIT TNE | 0.3447 | 0.3447 | 0.3447 | 0.3447 | 0.0260 | 1.0000 |
| SPLIT TN1 | 0.3270 | 0.3270 | 0.3270 | 0.3270 | 0.0260 | 1.0000 |
| SPLIT TN2 | 0.3255 | 0.3255 | 0.3255 | 0.3255 | 0.0260 | 1.0000 |
| SPLIT TS1 | 0.3466 | 0.3466 | 0.3466 | 0.3466 | 0.0260 | 1.0000 |
| SPLIT TS2 | 0.3451 | 0.3451 | 0.3451 | 0.3451 | 0.0260 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 09:15:25
Sec1.1A-General Information| Data | |
| Weather File | RUNPERIOD 1 ** San Diego-Brown Field Muni AP CA USA TMY3 WMO#=722904 |
| Total gross floor area [m2] | 3134.61 |
| Principal Heating Source | Natural Gas |
| Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
| G SW APARTMENT | 88.25 | 88.25 | 0.00 | 117.85 |
| G NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
| OFFICE | 88.25 | 88.25 | 0.00 | 33.56 |
| G NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
| G N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
| G N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
| G S1 APARTMENT | 88.25 | 88.25 | 0.00 | 117.85 |
| G S2 APARTMENT | 88.25 | 88.25 | 0.00 | 117.85 |
| M SW APARTMENT | 88.25 | 88.25 | 0.00 | 117.85 |
| M NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
| M SE APARTMENT | 88.25 | 88.25 | 0.00 | 117.85 |
| M NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
| M N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
| M N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
| M S1 APARTMENT | 88.25 | 88.25 | 0.00 | 117.85 |
| M S2 APARTMENT | 88.25 | 88.25 | 0.00 | 117.85 |
| T SW APARTMENT | 88.25 | 88.25 | 0.00 | 117.85 |
| T NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
| T SE APARTMENT | 88.25 | 88.25 | 0.00 | 117.85 |
| T NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
| T N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
| T N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
| T S1 APARTMENT | 88.25 | 88.25 | 0.00 | 117.85 |
| T S2 APARTMENT | 88.25 | 88.25 | 0.00 | 117.85 |
| T CORRIDOR | 77.66 | 0.00 | 77.66 | 168.00 |
| G CORRIDOR | 77.66 | 0.00 | 77.66 | 168.00 |
| M CORRIDOR | 77.66 | 0.00 | 77.66 | 168.00 |
| Totals | 3134.61 | 2823.98 | 310.64 |
| Data | |
| Number of hours heating loads not met | 0.00 |
| Number of hours cooling loads not met | 0.00 |
| Number of hours not met | 0.00 |
| Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
| None |
| Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
| Heating -- General | 0.00 | 0.00 | 25.22 | 30396.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Cooling -- General | 82.77 | 24675.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Lighting -- LightsWired | 94.96 | 5496.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Lighting -- LightsPlugIn | 4.27 | 407.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Lighting -- General | 50.05 | 3183.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment -- MiscPlug | 388.06 | 18541.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment -- ElevatorLift | 65.48 | 4006.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment -- ElevatorLightsFan | 5.11 | 162.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans -- Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans -- General | 76.97 | 8298.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Recovery -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems -- Water Heater | 423.95 | 37405.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Process Subtotal [GJ] | Total Energy Use [GJ] | |
| Electricity | 458.66 | 1191.62 |
| Natural Gas | 0.00 | 25.22 |
| Additional | 0.00 | 0.00 |
| Total | 458.66 | 1216.84 |
| Process Subtotal [$] | Total Energy Cost [$] | |
| Electricity | 0.00 | |
| Natural Gas | 0.00 | |
| Additional | 0.00 | |
| Total | 0.00 |
| Rated Capacity [kW] | Annual Energy Generated [GJ] | |
| Photovoltaic | 0.00 | 0.00 |
| Wind | 0.00 | 0.00 |
| Electricty [MJ/m2] | |
| Interior Lighting (All) | 31.66 |
| Space Heating | 0.00 |
| Space Cooling | 26.40 |
| Fans (All) | 24.55 |
| Service Water Heating | 135.25 |
| Receptacle Equipment | 146.32 |
| Miscellaneous (All) | 380.15 |
| Subtotal | 380.15 |
| Natural Gas [MJ/m2] | |
| Space Heating | 8.05 |
| Service Water Heating | 0.00 |
| Miscellaneous (All) | 8.05 |
| Subtotal | 8.05 |
| Additional [MJ/m2] | |
| Subtotal | 0.00 |
| Miscellaneous | 0.00 |
| Percent [%] | |
| Interior Lighting (All) | 8.15 |
| Space Heating | 2.07 |
| Space Cooling | 6.80 |
| Fans (All) | 6.33 |
| Service Water Heating | 34.84 |
| Receptacle Equipment | 37.69 |
| Miscellaneous | 4.11 |
| Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
| OCC_APT_SCH_STAY_HOME_FAMILY | 5993. | 8760. |
| OCC_APT_SCH_CORRIDOR | 5993. | 8760. |
| OCC_APT_SCH_WORKING_FAMILY | 5845. | 6055. |
| OCC_OFF_SCH | 2210. | 2340. |
| OCC_OFF_W_SB_SCH | 1820. | 1820. |
| LTG_SCH_OFFICE | 2435. | 8760. |
| LTG_SCH_CORRIDOR | 8760. | 8760. |
| LTG_SCH_APARTMENT_HARDWIRED | 527. | 8760. |
| LTG_SCH_APARTMENT_PLUGIN | 527. | 8760. |
| EQP_APT_SCH | 5763. | 8760. |
| EQP_OFF_SCH | 4531. | 8760. |
| INF_APT_SCH | 8760. | 8760. |
| INF_OFF_SCH | 8760. | 8760. |
| INF_COR_SCH | 8760. | 8760. |
| INFIL_DOOR_OPENING_SCH | 1466. | 5840. |
| ALL OFF | 0. | 0. |
| ALL ON | 8760. | 8760. |
| ALWAYS_ON | 8760. | 8760. |
| ALLON_EXCEPT_DD | 8760. | 8760. |
| EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
| FAN_OFF_W_SB_SCH | 8240. | 8240. |
| APT_DHW_SCH | 4592. | 8760. |
| EXTERIOR_LTG_SCH | 4380. | 4380. |
| BLDG_ELEVATORS | 2270. | 8760. |
| ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
| ELEV_LIGHT_FAN_SCH_ADD_DF | 2154. | 8760. |
| SLIDING_DOORS_VENTILATION_AVAILABILITY_SCH | 5840. | 5840. |
| First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
| HTGSETP_APT_SCH | APTHEATINGSETPOINT | January | 21.10 | 365 | 21.10 | 365 |
| HTGSETP_DESIGN_OFF_SCH | OFFHEATINGSETPOINT | January | 21.10 | 365 | 21.10 | 365 |
| CLGSETP_APT_SCH | APTCOOLINGSETPOINT | July | 24.00 | 365 | 24.00 | 365 |
| CLGSETP_DESIGN_OFF_SCH | OFFCOOLINGSETPOINT | July | 23.90 | 365 | 23.90 | 365 |
| S HTGSETP_APT_SCH | S APARTMENT DUAL SP CONTROL | January | 21.10 | 365 | 21.10 | 365 |
| S CLGSETP_APT_SCH | S APARTMENT DUAL SP CONTROL | July | 24.00 | 365 | 24.00 | 365 |
| N HTGSETP_APT_SCH | N APARTMENT DUAL SP CONTROL | January | 21.10 | 365 | 21.10 | 365 |
| N CLGSETP_APT_SCH | N APARTMENT DUAL SP CONTROL | July | 24.00 | 365 | 24.00 | 365 |
| HTGSETP_OFF_SCH_YES_OPTIMUM | OFFICE DUAL SP CONTROL | January | 21.10 | 365 | 15.60 | 365 |
| CLGSETP_OFF_SCH_YES_OPTIMUM | OFFICE DUAL SP CONTROL | July | 24.00 | 365 | 29.40 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 09:15:25
Heat Index Hours| Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
| G SW APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| G NW APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| OFFICE | 8413.17 | 346.83 | 0.00 | 0.00 | 0.00 |
| G NE APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| G N1 APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| G N2 APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| G S1 APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| G S2 APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M SW APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M NW APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M SE APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M NE APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M N1 APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M N2 APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M S1 APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M S2 APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T SW APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T NW APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T SE APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T NE APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T N1 APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T N2 APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T S1 APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T S2 APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T CORRIDOR | 8202.67 | 557.33 | 0.00 | 0.00 | 0.00 |
| G CORRIDOR | 8738.17 | 21.83 | 0.00 | 0.00 | 0.00 |
| M CORRIDOR | 5894.17 | 2865.83 | 0.00 | 0.00 | 0.00 |
| Min | 5894.17 | 0.00 | 0.00 | 0.00 | 0.00 |
| Max | 8760.00 | 2865.83 | 0.00 | 0.00 | 0.00 |
| Average | 8619.56 | 140.44 | 0.00 | 0.00 | 0.00 |
| Sum | 232728.17 | 3791.83 | 0.00 | 0.00 | 0.00 |
| Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
| G SW APARTMENT | 11830.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| G NW APARTMENT | 10585.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| OFFICE | 7000.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| G NE APARTMENT | 10585.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| G N1 APARTMENT | 10585.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| G N2 APARTMENT | 10585.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| G S1 APARTMENT | 11830.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| G S2 APARTMENT | 11830.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M SW APARTMENT | 11830.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M NW APARTMENT | 10585.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M SE APARTMENT | 11830.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M NE APARTMENT | 10585.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M N1 APARTMENT | 10585.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M N2 APARTMENT | 10585.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M S1 APARTMENT | 11830.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M S2 APARTMENT | 11830.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T SW APARTMENT | 11830.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T NW APARTMENT | 10585.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T SE APARTMENT | 11830.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T NE APARTMENT | 10585.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T N1 APARTMENT | 10585.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T N2 APARTMENT | 10585.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T S1 APARTMENT | 11830.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T S2 APARTMENT | 11830.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T CORRIDOR | 21931.83 | 1063.17 | 0.00 | 0.00 | 0.00 |
| G CORRIDOR | 22920.17 | 74.83 | 0.00 | 0.00 | 0.00 |
| M CORRIDOR | 15471.33 | 7523.67 | 0.00 | 0.00 | 0.00 |
| Min | 7000.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Max | 22920.17 | 7523.67 | 0.00 | 0.00 | 0.00 |
| Average | 12017.53 | 320.80 | 0.00 | 0.00 | 0.00 |
| Sum | 324473.33 | 8661.67 | 0.00 | 0.00 | 0.00 |
| Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
| G SW APARTMENT | 8639.83 | 120.17 | 0.00 | 0.00 | 0.00 |
| G NW APARTMENT | 8576.17 | 183.83 | 0.00 | 0.00 | 0.00 |
| OFFICE | 7433.67 | 1326.33 | 0.00 | 0.00 | 0.00 |
| G NE APARTMENT | 8539.17 | 220.83 | 0.00 | 0.00 | 0.00 |
| G N1 APARTMENT | 8649.50 | 110.50 | 0.00 | 0.00 | 0.00 |
| G N2 APARTMENT | 8648.00 | 112.00 | 0.00 | 0.00 | 0.00 |
| G S1 APARTMENT | 8689.17 | 70.83 | 0.00 | 0.00 | 0.00 |
| G S2 APARTMENT | 8715.33 | 44.67 | 0.00 | 0.00 | 0.00 |
| M SW APARTMENT | 8734.00 | 26.00 | 0.00 | 0.00 | 0.00 |
| M NW APARTMENT | 8719.67 | 40.33 | 0.00 | 0.00 | 0.00 |
| M SE APARTMENT | 8735.83 | 24.17 | 0.00 | 0.00 | 0.00 |
| M NE APARTMENT | 8721.83 | 38.17 | 0.00 | 0.00 | 0.00 |
| M N1 APARTMENT | 8738.83 | 21.17 | 0.00 | 0.00 | 0.00 |
| M N2 APARTMENT | 8738.50 | 21.50 | 0.00 | 0.00 | 0.00 |
| M S1 APARTMENT | 8746.67 | 13.33 | 0.00 | 0.00 | 0.00 |
| M S2 APARTMENT | 8746.50 | 13.50 | 0.00 | 0.00 | 0.00 |
| T SW APARTMENT | 8528.17 | 231.83 | 0.00 | 0.00 | 0.00 |
| T NW APARTMENT | 8505.83 | 254.17 | 0.00 | 0.00 | 0.00 |
| T SE APARTMENT | 8513.50 | 246.50 | 0.00 | 0.00 | 0.00 |
| T NE APARTMENT | 8489.83 | 270.17 | 0.00 | 0.00 | 0.00 |
| T N1 APARTMENT | 8522.50 | 237.50 | 0.00 | 0.00 | 0.00 |
| T N2 APARTMENT | 8520.00 | 240.00 | 0.00 | 0.00 | 0.00 |
| T S1 APARTMENT | 8543.00 | 217.00 | 0.00 | 0.00 | 0.00 |
| T S2 APARTMENT | 8541.50 | 218.50 | 0.00 | 0.00 | 0.00 |
| T CORRIDOR | 1810.83 | 6949.17 | 0.00 | 0.00 | 0.00 |
| G CORRIDOR | 6449.67 | 2310.33 | 0.00 | 0.00 | 0.00 |
| M CORRIDOR | 125.33 | 8634.67 | 0.00 | 0.00 | 0.00 |
| Min | 125.33 | 13.33 | 0.00 | 0.00 | 0.00 |
| Max | 8746.67 | 8634.67 | 0.00 | 0.00 | 0.00 |
| Average | 7937.88 | 822.12 | 0.00 | 0.00 | 0.00 |
| Sum | 214322.83 | 22197.17 | 0.00 | 0.00 | 0.00 |
| Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
| G SW APARTMENT | 11647.50 | 182.50 | 0.00 | 0.00 | 0.00 |
| G NW APARTMENT | 10315.67 | 269.33 | 0.00 | 0.00 | 0.00 |
| OFFICE | 6784.67 | 215.33 | 0.00 | 0.00 | 0.00 |
| G NE APARTMENT | 10215.33 | 369.67 | 0.00 | 0.00 | 0.00 |
| G N1 APARTMENT | 10442.67 | 142.33 | 0.00 | 0.00 | 0.00 |
| G N2 APARTMENT | 10439.67 | 145.33 | 0.00 | 0.00 | 0.00 |
| G S1 APARTMENT | 11725.83 | 104.17 | 0.00 | 0.00 | 0.00 |
| G S2 APARTMENT | 11770.00 | 60.00 | 0.00 | 0.00 | 0.00 |
| M SW APARTMENT | 11795.17 | 34.83 | 0.00 | 0.00 | 0.00 |
| M NW APARTMENT | 10539.00 | 46.00 | 0.00 | 0.00 | 0.00 |
| M SE APARTMENT | 11791.50 | 38.50 | 0.00 | 0.00 | 0.00 |
| M NE APARTMENT | 10533.00 | 52.00 | 0.00 | 0.00 | 0.00 |
| M N1 APARTMENT | 10566.33 | 18.67 | 0.00 | 0.00 | 0.00 |
| M N2 APARTMENT | 10565.67 | 19.33 | 0.00 | 0.00 | 0.00 |
| M S1 APARTMENT | 11812.33 | 17.67 | 0.00 | 0.00 | 0.00 |
| M S2 APARTMENT | 11812.00 | 18.00 | 0.00 | 0.00 | 0.00 |
| T SW APARTMENT | 11447.00 | 383.00 | 0.00 | 0.00 | 0.00 |
| T NW APARTMENT | 10190.00 | 395.00 | 0.00 | 0.00 | 0.00 |
| T SE APARTMENT | 11394.67 | 435.33 | 0.00 | 0.00 | 0.00 |
| T NE APARTMENT | 10123.00 | 462.00 | 0.00 | 0.00 | 0.00 |
| T N1 APARTMENT | 10211.00 | 374.00 | 0.00 | 0.00 | 0.00 |
| T N2 APARTMENT | 10205.67 | 379.33 | 0.00 | 0.00 | 0.00 |
| T S1 APARTMENT | 11469.33 | 360.67 | 0.00 | 0.00 | 0.00 |
| T S2 APARTMENT | 11466.00 | 364.00 | 0.00 | 0.00 | 0.00 |
| T CORRIDOR | 4719.50 | 18275.50 | 0.00 | 0.00 | 0.00 |
| G CORRIDOR | 15645.67 | 7349.33 | 0.00 | 0.00 | 0.00 |
| M CORRIDOR | 291.67 | 22703.33 | 0.00 | 0.00 | 0.00 |
| Min | 291.67 | 17.67 | 0.00 | 0.00 | 0.00 |
| Max | 15645.67 | 22703.33 | 0.00 | 0.00 | 0.00 |
| Average | 10367.40 | 1970.93 | 0.00 | 0.00 | 0.00 |
| Sum | 279919.83 | 53215.17 | 0.00 | 0.00 | 0.00 |
| SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
| None |
| SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
| None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 09:15:25
CO2 Level Hours| Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
| None |
| Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
| None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 09:15:25
Illuminance Level Hours| A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
| None |
| A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
| None |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
| January | 13.221 |
| February | 13.282 |
| March | 12.638 |
| April | 15.303 |
| May | 15.556 |
| June | 17.667 |
| July | 19.435 |
| August | 19.664 |
| September | 18.470 |
| October | 18.770 |
| November | 14.323 |
| December | 13.589 |
| Annual Sum or Average | 16.011 |
| Minimum of Months | 12.638 |
| Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Environment
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
| January | 13.221 |
| February | 13.282 |
| March | 12.638 |
| April | 15.303 |
| May | 15.556 |
| June | 17.667 |
| July | 19.435 |
| August | 19.664 |
| September | 18.470 |
| October | 18.770 |
| November | 14.323 |
| December | 13.589 |
| Annual Sum or Average | 16.011 |
| Minimum of Months | 12.638 |
| Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2012
For: Environment
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
| January | 13.221 |
| February | 13.282 |
| March | 12.638 |
| April | 15.303 |
| May | 15.556 |
| June | 17.667 |
| July | 19.435 |
| August | 19.664 |
| September | 18.470 |
| October | 18.770 |
| November | 14.323 |
| December | 13.589 |
| Annual Sum or Average | 16.011 |
| Minimum of Months | 12.638 |
| Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
| January | 13.221 |
| February | 13.282 |
| March | 12.638 |
| April | 15.303 |
| May | 15.556 |
| June | 17.667 |
| July | 19.435 |
| August | 19.664 |
| September | 18.470 |
| October | 18.770 |
| November | 14.323 |
| December | 13.589 |
| Annual Sum or Average | 16.011 |
| Minimum of Months | 12.638 |
| Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME APARTMENTMIDRISE
For: Environment
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
| January | 13.221 |
| February | 13.282 |
| March | 12.638 |
| April | 15.303 |
| May | 15.556 |
| June | 17.667 |
| July | 19.435 |
| August | 19.664 |
| September | 18.470 |
| October | 18.770 |
| November | 14.323 |
| December | 13.589 |
| Annual Sum or Average | 16.011 |
| Minimum of Months | 12.638 |
| Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
| January | 13.221 |
| February | 13.282 |
| March | 12.638 |
| April | 15.303 |
| May | 15.556 |
| June | 17.667 |
| July | 19.435 |
| August | 19.664 |
| September | 18.470 |
| October | 18.770 |
| November | 14.323 |
| December | 13.589 |
| Annual Sum or Average | 16.011 |
| Minimum of Months | 12.638 |
| Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
| January | 13.221 |
| February | 13.282 |
| March | 12.638 |
| April | 15.303 |
| May | 15.556 |
| June | 17.667 |
| July | 19.435 |
| August | 19.664 |
| September | 18.470 |
| October | 18.770 |
| November | 14.323 |
| December | 13.589 |
| Annual Sum or Average | 16.011 |
| Minimum of Months | 12.638 |
| Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3C
For: Environment
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
| January | 13.221 |
| February | 13.282 |
| March | 12.638 |
| April | 15.303 |
| May | 15.556 |
| June | 17.667 |
| July | 19.435 |
| August | 19.664 |
| September | 18.470 |
| October | 18.770 |
| November | 14.323 |
| December | 13.589 |
| Annual Sum or Average | 16.011 |
| Minimum of Months | 12.638 |
| Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_CA_SANDIEGO
For: Environment
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
| January | 13.221 |
| February | 13.282 |
| March | 12.638 |
| April | 15.303 |
| May | 15.556 |
| June | 17.667 |
| July | 19.435 |
| August | 19.664 |
| September | 18.470 |
| October | 18.770 |
| November | 14.323 |
| December | 13.589 |
| Annual Sum or Average | 16.011 |
| Minimum of Months | 12.638 |
| Maximum of Months | 19.664 |
Report: ZoneCoolingSummaryMonthly
For: G SW APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.980014E+09 | 1237.85 | 18-JAN-14:30 | 23.80 | 14.82 | 0.109266E+09 | 70.36 | 17-JAN-21:40 | 23.80 | 14.82 |
| February | 0.742302E+09 | 1009.62 | 03-FEB-15:00 | 23.00 | 8.84 | 90418319.60 | 70.37 | 20-FEB-18:49 | 13.50 | 10.49 |
| March | 0.679066E+09 | 719.11 | 23-MAR-16:10 | 20.67 | 16.98 | 91016792.83 | 70.33 | 21-MAR-17:10 | 20.67 | 16.98 |
| April | 0.777000E+09 | 965.92 | 30-APR-16:20 | 22.00 | 15.83 | 0.107794E+09 | 70.38 | 15-APR-18:10 | 22.00 | 15.83 |
| May | 0.709125E+09 | 836.97 | 03-MAY-16:05 | 20.83 | 15.02 | 0.109473E+09 | 70.37 | 10-MAY-17:00 | 14.00 | 11.21 |
| June | 0.813415E+09 | 985.80 | 30-JUN-16:20 | 22.47 | 17.95 | 0.114350E+09 | 70.35 | 05-JUN-21:00 | 22.47 | 17.95 |
| July | 0.139585E+10 | 1291.50 | 23-JUL-16:30 | 24.00 | 19.02 | 0.128856E+09 | 70.35 | 12-JUL-03:09 | 24.00 | 19.02 |
| August | 0.156145E+10 | 1433.48 | 19-AUG-16:10 | 24.83 | 18.75 | 0.123668E+09 | 70.34 | 29-AUG-01:30 | 16.00 | 14.76 |
| September | 0.146459E+10 | 1993.65 | 30-SEP-15:10 | 31.50 | 17.45 | 0.123266E+09 | 70.36 | 29-SEP-05:40 | 31.50 | 17.45 |
| October | 0.175727E+10 | 2155.92 | 16-OCT-14:10 | 31.67 | 15.90 | 0.125428E+09 | 70.35 | 31-OCT-00:40 | 14.00 | 10.86 |
| November | 0.109915E+10 | 1500.40 | 19-NOV-13:30 | 26.00 | 15.06 | 0.115217E+09 | 70.36 | 16-NOV-19:40 | 26.00 | 15.06 |
| December | 0.111959E+10 | 1303.03 | 19-DEC-13:40 | 24.00 | 10.42 | 0.113995E+09 | 70.36 | 05-DEC-01:19 | 24.00 | 10.42 |
| Annual Sum or Average | 0.130988E+11 | 0.135275E+10 | ||||||||
| Minimum of Months | 0.679066E+09 | 719.11 | 20.67 | 8.84 | 90418319.60 | 70.33 | 13.50 | 10.42 | ||
| Maximum of Months | 0.175727E+10 | 2155.92 | 31.67 | 19.02 | 0.128856E+09 | 70.38 | 31.50 | 19.02 |
Report: ZoneCoolingSummaryMonthly
For: G NW APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.473198E+09 | 460.83 | 27-JAN-02:00 | 6.00 | 5.49 | 90766948.42 | 66.16 | 18-JAN-22:49 | 6.00 | 5.49 |
| February | 0.425115E+09 | 397.67 | 05-FEB-22:00 | 8.00 | 5.23 | 75836363.78 | 55.32 | 03-FEB-21:10 | 8.00 | 5.23 |
| March | 0.452673E+09 | 390.32 | 07-MAR-19:00 | 8.00 | 6.48 | 84184967.26 | 58.37 | 23-MAR-21:10 | 13.83 | 13.26 |
| April | 0.575267E+09 | 668.15 | 30-APR-16:30 | 22.00 | 15.83 | 99124549.77 | 69.86 | 29-APR-20:10 | 22.00 | 15.83 |
| May | 0.651175E+09 | 689.84 | 03-MAY-16:05 | 20.83 | 15.02 | 0.111198E+09 | 70.35 | 04-MAY-22:10 | 16.83 | 15.02 |
| June | 0.807778E+09 | 1023.28 | 29-JUN-17:05 | 22.83 | 18.47 | 0.118890E+09 | 70.35 | 24-JUN-21:49 | 22.83 | 18.47 |
| July | 0.132038E+10 | 1243.10 | 19-JUL-16:40 | 24.33 | 19.61 | 0.128378E+09 | 70.35 | 10-JUL-03:00 | 24.33 | 19.61 |
| August | 0.124714E+10 | 1193.83 | 19-AUG-16:30 | 24.50 | 18.31 | 0.128143E+09 | 70.34 | 02-AUG-03:49 | 24.50 | 18.31 |
| September | 0.921142E+09 | 1384.58 | 29-SEP-16:04 | 31.67 | 16.86 | 0.122618E+09 | 70.35 | 07-SEP-02:39 | 31.67 | 16.86 |
| October | 0.101199E+10 | 1357.48 | 16-OCT-16:05 | 28.67 | 15.29 | 0.123471E+09 | 70.35 | 20-OCT-02:00 | 17.00 | 13.94 |
| November | 0.619267E+09 | 448.25 | 29-NOV-23:00 | 7.00 | 4.66 | 96834928.80 | 68.84 | 01-NOV-20:10 | 7.00 | 4.66 |
| December | 0.544259E+09 | 451.70 | 03-DEC-00:30 | 6.00 | 6.00 | 90907149.00 | 63.49 | 05-DEC-23:10 | 17.33 | 9.21 |
| Annual Sum or Average | 0.904939E+10 | 0.127035E+10 | ||||||||
| Minimum of Months | 0.425115E+09 | 390.32 | 6.00 | 4.66 | 75836363.78 | 55.32 | 6.00 | 4.66 | ||
| Maximum of Months | 0.132038E+10 | 1384.58 | 31.67 | 19.61 | 0.128378E+09 | 70.35 | 31.67 | 19.61 |
Report: ZoneCoolingSummaryMonthly
For: OFFICE
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.809046E+09 | 5420.29 | 19-JAN-09:02 | 18.50 | 13.10 | 66862091.82 | 166.92 | 17-JAN-09:09 | 18.50 | 13.10 |
| February | 0.530626E+09 | 5282.30 | 02-FEB-09:02 | 15.33 | 12.18 | 62075510.88 | 166.80 | 01-FEB-09:09 | 15.33 | 12.18 |
| March | 0.458230E+09 | 2713.14 | 23-MAR-08:63 | 17.33 | 14.09 | 71683727.66 | 151.87 | 23-MAR-08:09 | 17.33 | 14.09 |
| April | 0.592174E+09 | 5213.63 | 13-APR-08:62 | 19.50 | 12.59 | 67576705.25 | 166.80 | 26-APR-08:09 | 22.17 | 16.46 |
| May | 0.560075E+09 | 5224.91 | 02-MAY-08:62 | 19.00 | 14.25 | 74794460.05 | 166.81 | 04-MAY-08:09 | 19.17 | 14.74 |
| June | 0.659123E+09 | 5104.54 | 23-JUN-08:62 | 18.50 | 14.15 | 76153842.17 | 167.67 | 30-JUN-07:10 | 18.33 | 16.73 |
| July | 0.929930E+09 | 4875.37 | 10-JUL-08:62 | 19.33 | 14.88 | 70095628.55 | 183.39 | 24-JUL-07:10 | 17.67 | 17.28 |
| August | 0.119732E+10 | 4917.50 | 22-AUG-08:62 | 17.58 | 14.22 | 80661569.91 | 190.71 | 14-AUG-07:10 | 17.58 | 14.22 |
| September | 0.990814E+09 | 5143.20 | 20-SEP-08:62 | 16.33 | 13.72 | 69937217.30 | 185.99 | 29-SEP-07:10 | 24.00 | 14.17 |
| October | 0.129207E+10 | 5390.43 | 12-OCT-08:62 | 16.50 | 9.61 | 73441119.27 | 217.69 | 16-OCT-07:10 | 25.50 | 12.31 |
| November | 0.927234E+09 | 5546.15 | 22-NOV-09:02 | 14.33 | 10.47 | 68799214.61 | 166.81 | 20-NOV-09:09 | 14.33 | 10.47 |
| December | 0.919491E+09 | 5358.10 | 07-DEC-09:02 | 18.50 | 11.61 | 67840904.88 | 166.81 | 05-DEC-09:09 | 18.50 | 11.61 |
| Annual Sum or Average | 0.986613E+10 | 0.849922E+09 | ||||||||
| Minimum of Months | 0.458230E+09 | 2713.14 | 14.33 | 9.61 | 62075510.88 | 151.87 | 14.33 | 10.47 | ||
| Maximum of Months | 0.129207E+10 | 5546.15 | 19.50 | 14.88 | 80661569.91 | 217.69 | 25.50 | 17.28 |
Report: ZoneCoolingSummaryMonthly
For: G NE APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.490100E+09 | 462.51 | 27-JAN-02:00 | 6.00 | 5.49 | 90998631.44 | 65.82 | 18-JAN-22:49 | 6.00 | 5.49 |
| February | 0.418612E+09 | 394.71 | 05-FEB-22:00 | 8.00 | 5.23 | 75281456.85 | 54.41 | 03-FEB-21:10 | 8.00 | 5.23 |
| March | 0.450826E+09 | 390.31 | 20-MAR-03:00 | 8.00 | 8.00 | 84029888.34 | 57.98 | 23-MAR-21:10 | 13.83 | 13.26 |
| April | 0.569700E+09 | 517.20 | 30-APR-10:40 | 25.67 | 16.97 | 97553867.51 | 67.87 | 30-APR-21:49 | 16.50 | 15.58 |
| May | 0.634967E+09 | 597.32 | 04-MAY-12:00 | 24.00 | 16.55 | 0.109257E+09 | 70.35 | 03-MAY-22:30 | 24.00 | 16.55 |
| June | 0.764590E+09 | 795.39 | 30-JUN-10:00 | 24.00 | 18.12 | 0.117552E+09 | 70.34 | 30-JUN-02:20 | 24.00 | 18.12 |
| July | 0.127529E+10 | 1040.63 | 19-JUL-10:30 | 27.50 | 20.34 | 0.128192E+09 | 70.35 | 06-JUL-00:10 | 27.50 | 20.34 |
| August | 0.123164E+10 | 992.60 | 15-AUG-10:40 | 27.00 | 20.85 | 0.127994E+09 | 70.35 | 28-AUG-22:19 | 16.00 | 14.76 |
| September | 0.860991E+09 | 1172.24 | 30-SEP-12:00 | 32.00 | 17.11 | 0.121596E+09 | 70.36 | 29-SEP-02:39 | 32.00 | 17.11 |
| October | 0.991750E+09 | 1393.29 | 16-OCT-11:00 | 37.00 | 17.87 | 0.123097E+09 | 70.35 | 09-OCT-21:49 | 37.00 | 17.87 |
| November | 0.615474E+09 | 446.72 | 29-NOV-23:00 | 7.00 | 4.66 | 95905652.19 | 68.15 | 01-NOV-20:10 | 7.00 | 4.66 |
| December | 0.546433E+09 | 443.12 | 21-DEC-20:00 | 7.00 | 7.00 | 90758583.46 | 63.72 | 05-DEC-23:10 | 7.00 | 7.00 |
| Annual Sum or Average | 0.885037E+10 | 0.126222E+10 | ||||||||
| Minimum of Months | 0.418612E+09 | 390.31 | 6.00 | 4.66 | 75281456.85 | 54.41 | 6.00 | 4.66 | ||
| Maximum of Months | 0.127529E+10 | 1393.29 | 37.00 | 20.85 | 0.128192E+09 | 70.36 | 37.00 | 20.34 |
Report: ZoneCoolingSummaryMonthly
For: G N1 APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.600939E+09 | 550.69 | 28-JAN-07:00 | 3.00 | 2.55 | 95688860.39 | 69.54 | 18-JAN-22:00 | 3.00 | 2.55 |
| February | 0.582756E+09 | 488.43 | 04-FEB-06:00 | 5.00 | 0.22 | 80564304.28 | 59.42 | 03-FEB-21:10 | 5.00 | 0.22 |
| March | 0.597555E+09 | 404.13 | 20-MAR-03:00 | 8.00 | 8.00 | 87991929.03 | 60.49 | 23-MAR-21:10 | 13.83 | 13.26 |
| April | 0.579156E+09 | 411.65 | 30-APR-17:10 | 21.67 | 15.82 | 0.102747E+09 | 70.27 | 29-APR-20:10 | 21.67 | 15.82 |
| May | 0.652351E+09 | 513.53 | 04-MAY-16:03 | 21.67 | 15.62 | 0.116004E+09 | 70.36 | 03-MAY-23:30 | 21.67 | 15.62 |
| June | 0.770872E+09 | 703.92 | 29-JUN-17:40 | 22.33 | 18.57 | 0.121661E+09 | 70.35 | 19-JUN-02:00 | 22.33 | 18.57 |
| July | 0.118607E+10 | 853.13 | 19-JUL-17:20 | 23.67 | 19.21 | 0.128614E+09 | 70.35 | 10-JUL-20:40 | 23.67 | 19.21 |
| August | 0.113744E+10 | 793.56 | 17-AUG-16:05 | 24.72 | 20.07 | 0.128562E+09 | 70.35 | 31-AUG-02:39 | 16.00 | 14.76 |
| September | 0.883990E+09 | 932.98 | 30-SEP-16:10 | 28.50 | 18.51 | 0.123745E+09 | 70.36 | 18-SEP-21:10 | 28.50 | 18.51 |
| October | 0.100960E+10 | 975.38 | 16-OCT-12:00 | 36.00 | 17.61 | 0.126068E+09 | 70.36 | 18-OCT-04:19 | 14.33 | 8.50 |
| November | 0.651586E+09 | 463.55 | 29-NOV-23:00 | 7.00 | 4.66 | 0.104135E+09 | 70.37 | 01-NOV-20:40 | 7.00 | 4.66 |
| December | 0.676051E+09 | 500.21 | 03-DEC-01:00 | 5.00 | 5.00 | 97191399.04 | 67.49 | 07-DEC-21:10 | 13.80 | 13.31 |
| Annual Sum or Average | 0.932837E+10 | 0.131297E+10 | ||||||||
| Minimum of Months | 0.579156E+09 | 404.13 | 3.00 | 0.22 | 80564304.28 | 59.42 | 3.00 | 0.22 | ||
| Maximum of Months | 0.118607E+10 | 975.38 | 36.00 | 20.07 | 0.128614E+09 | 70.37 | 28.50 | 19.21 |
Report: ZoneCoolingSummaryMonthly
For: G N2 APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.602391E+09 | 551.12 | 28-JAN-07:00 | 3.00 | 2.55 | 95769585.51 | 69.53 | 18-JAN-22:00 | 3.00 | 2.55 |
| February | 0.582515E+09 | 488.33 | 04-FEB-06:00 | 5.00 | 0.22 | 80522232.41 | 59.37 | 03-FEB-21:10 | 5.00 | 0.22 |
| March | 0.596993E+09 | 404.62 | 20-MAR-03:00 | 8.00 | 8.00 | 88029121.29 | 60.56 | 23-MAR-21:10 | 13.83 | 13.26 |
| April | 0.578746E+09 | 408.93 | 15-APR-22:00 | 9.00 | 8.43 | 0.102630E+09 | 70.27 | 29-APR-20:10 | 14.50 | 12.91 |
| May | 0.651015E+09 | 512.37 | 04-MAY-16:10 | 21.67 | 15.62 | 0.115806E+09 | 70.33 | 03-MAY-23:30 | 21.67 | 15.62 |
| June | 0.766920E+09 | 695.86 | 29-JUN-17:40 | 22.33 | 18.57 | 0.121544E+09 | 70.36 | 08-JUN-20:40 | 22.33 | 18.57 |
| July | 0.118329E+10 | 849.03 | 19-JUL-17:20 | 23.67 | 19.21 | 0.128607E+09 | 70.35 | 02-JUL-20:30 | 23.67 | 19.21 |
| August | 0.113642E+10 | 791.10 | 17-AUG-16:05 | 24.72 | 20.07 | 0.128558E+09 | 70.35 | 23-AUG-05:10 | 16.00 | 14.13 |
| September | 0.878400E+09 | 929.19 | 30-SEP-16:10 | 28.50 | 18.51 | 0.123691E+09 | 70.35 | 15-SEP-03:09 | 28.50 | 18.51 |
| October | 0.100860E+10 | 980.08 | 16-OCT-12:00 | 36.00 | 17.61 | 0.126052E+09 | 70.35 | 30-OCT-20:00 | 14.00 | 12.24 |
| November | 0.651236E+09 | 463.47 | 29-NOV-23:00 | 7.00 | 4.66 | 0.104034E+09 | 70.37 | 01-NOV-20:40 | 7.00 | 4.66 |
| December | 0.676350E+09 | 500.17 | 03-DEC-01:00 | 5.00 | 5.00 | 97206795.02 | 67.56 | 07-DEC-21:10 | 13.80 | 13.31 |
| Annual Sum or Average | 0.931287E+10 | 0.131245E+10 | ||||||||
| Minimum of Months | 0.578746E+09 | 404.62 | 3.00 | 0.22 | 80522232.41 | 59.37 | 3.00 | 0.22 | ||
| Maximum of Months | 0.118329E+10 | 980.08 | 36.00 | 20.07 | 0.128607E+09 | 70.37 | 28.50 | 19.21 |
Report: ZoneCoolingSummaryMonthly
For: G S1 APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.120094E+10 | 1191.26 | 18-JAN-14:00 | 24.60 | 14.81 | 0.117631E+09 | 70.36 | 27-JAN-21:19 | 9.00 | 9.00 |
| February | 0.858234E+09 | 1026.26 | 01-FEB-13:00 | 24.00 | 13.82 | 0.100707E+09 | 70.37 | 09-FEB-20:10 | 11.30 | 10.71 |
| March | 0.821018E+09 | 599.44 | 11-MAR-13:50 | 24.00 | 12.91 | 99363824.63 | 70.36 | 19-MAR-18:30 | 13.50 | 12.64 |
| April | 0.796694E+09 | 751.99 | 30-APR-13:30 | 24.00 | 16.79 | 0.113142E+09 | 70.36 | 24-APR-19:30 | 24.00 | 16.79 |
| May | 0.717357E+09 | 667.80 | 04-MAY-12:00 | 24.00 | 16.55 | 0.114662E+09 | 70.37 | 08-MAY-19:10 | 14.00 | 12.24 |
| June | 0.778799E+09 | 669.31 | 30-JUN-16:10 | 22.58 | 17.92 | 0.117233E+09 | 70.36 | 02-JUN-19:00 | 22.58 | 17.92 |
| July | 0.126797E+10 | 917.47 | 23-JUL-16:10 | 24.00 | 19.22 | 0.129104E+09 | 70.34 | 06-JUL-00:49 | 24.00 | 19.22 |
| August | 0.147149E+10 | 1031.78 | 19-AUG-16:05 | 24.83 | 18.75 | 0.123876E+09 | 70.34 | 04-AUG-06:00 | 24.83 | 18.75 |
| September | 0.146840E+10 | 1564.67 | 30-SEP-13:30 | 32.00 | 17.24 | 0.123783E+09 | 70.35 | 16-SEP-01:00 | 32.00 | 17.24 |
| October | 0.183229E+10 | 1832.15 | 16-OCT-12:30 | 35.05 | 17.21 | 0.126982E+09 | 70.36 | 07-OCT-22:00 | 35.05 | 17.21 |
| November | 0.131030E+10 | 1474.89 | 19-NOV-13:00 | 27.00 | 14.96 | 0.120701E+09 | 70.36 | 28-NOV-04:40 | 16.00 | 5.40 |
| December | 0.135381E+10 | 1362.85 | 19-DEC-13:00 | 26.00 | 11.60 | 0.122438E+09 | 70.35 | 19-DEC-03:39 | 26.00 | 11.60 |
| Annual Sum or Average | 0.138773E+11 | 0.140962E+10 | ||||||||
| Minimum of Months | 0.717357E+09 | 599.44 | 22.58 | 11.60 | 99363824.63 | 70.34 | 9.00 | 5.40 | ||
| Maximum of Months | 0.183229E+10 | 1832.15 | 35.05 | 19.22 | 0.129104E+09 | 70.37 | 35.05 | 19.22 |
Report: ZoneCoolingSummaryMonthly
For: G S2 APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.123296E+10 | 1227.20 | 18-JAN-14:00 | 24.60 | 14.81 | 0.117767E+09 | 70.37 | 25-JAN-03:49 | 15.00 | 10.68 |
| February | 0.876030E+09 | 1055.24 | 01-FEB-13:00 | 24.00 | 13.82 | 0.101420E+09 | 70.37 | 18-FEB-19:40 | 13.00 | 11.87 |
| March | 0.837531E+09 | 634.36 | 23-MAR-14:10 | 22.83 | 17.30 | 0.100428E+09 | 70.36 | 11-MAR-18:00 | 22.83 | 17.30 |
| April | 0.822511E+09 | 792.04 | 30-APR-13:30 | 24.00 | 16.79 | 0.113808E+09 | 70.37 | 06-APR-18:40 | 24.00 | 16.79 |
| May | 0.739441E+09 | 704.15 | 04-MAY-12:00 | 24.00 | 16.55 | 0.115544E+09 | 70.37 | 30-MAY-18:00 | 14.00 | 12.24 |
| June | 0.822713E+09 | 698.93 | 30-JUN-16:03 | 22.58 | 17.92 | 0.117744E+09 | 70.36 | 09-JUN-17:40 | 22.58 | 17.92 |
| July | 0.136802E+10 | 983.90 | 23-JUL-16:05 | 24.00 | 19.22 | 0.129169E+09 | 70.34 | 06-JUL-01:19 | 24.00 | 19.22 |
| August | 0.158682E+10 | 1100.96 | 19-AUG-16:10 | 24.83 | 18.75 | 0.123915E+09 | 70.34 | 11-AUG-05:49 | 24.83 | 18.75 |
| September | 0.155925E+10 | 1666.61 | 30-SEP-13:40 | 32.00 | 17.36 | 0.123851E+09 | 70.35 | 16-SEP-02:49 | 32.00 | 17.36 |
| October | 0.196043E+10 | 1922.65 | 16-OCT-12:00 | 36.00 | 17.61 | 0.127113E+09 | 70.36 | 29-OCT-02:00 | 11.90 | 9.29 |
| November | 0.135648E+10 | 1533.08 | 19-NOV-13:00 | 27.00 | 14.96 | 0.120957E+09 | 70.35 | 10-NOV-02:09 | 27.00 | 14.96 |
| December | 0.139092E+10 | 1398.46 | 19-DEC-13:00 | 26.00 | 11.60 | 0.122824E+09 | 70.36 | 07-DEC-01:39 | 26.00 | 11.60 |
| Annual Sum or Average | 0.145531E+11 | 0.141454E+10 | ||||||||
| Minimum of Months | 0.739441E+09 | 634.36 | 22.58 | 11.60 | 0.100428E+09 | 70.34 | 11.90 | 9.29 | ||
| Maximum of Months | 0.196043E+10 | 1922.65 | 36.00 | 19.22 | 0.129169E+09 | 70.37 | 32.00 | 19.22 |
Report: ZoneCoolingSummaryMonthly
For: M SW APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.141729E+10 | 1936.97 | 18-JAN-14:30 | 23.80 | 14.82 | 0.116354E+09 | 70.30 | 15-JAN-09:39 | 23.80 | 14.82 |
| February | 0.112170E+10 | 1695.73 | 03-FEB-15:00 | 23.00 | 8.84 | 0.102623E+09 | 70.31 | 15-FEB-22:00 | 13.00 | 11.87 |
| March | 0.111451E+10 | 1542.96 | 23-MAR-15:30 | 21.50 | 17.30 | 0.107829E+09 | 70.30 | 11-MAR-10:39 | 21.50 | 17.30 |
| April | 0.143882E+10 | 1680.22 | 26-APR-16:03 | 22.00 | 16.48 | 0.119270E+09 | 70.31 | 24-APR-03:49 | 22.00 | 16.48 |
| May | 0.123095E+10 | 1375.72 | 03-MAY-16:05 | 20.83 | 15.02 | 0.121201E+09 | 70.31 | 15-MAY-22:10 | 13.00 | 11.97 |
| June | 0.152318E+10 | 1507.82 | 29-JUN-16:30 | 23.00 | 18.43 | 0.119886E+09 | 70.30 | 22-JUN-03:49 | 23.00 | 18.43 |
| July | 0.207795E+10 | 1763.56 | 23-JUL-16:30 | 24.00 | 19.02 | 0.129241E+09 | 70.30 | 04-JUL-05:49 | 24.00 | 19.02 |
| August | 0.221597E+10 | 1905.67 | 19-AUG-16:10 | 24.83 | 18.75 | 0.123919E+09 | 70.27 | 21-AUG-05:19 | 16.83 | 15.53 |
| September | 0.201605E+10 | 2535.08 | 29-SEP-15:10 | 32.83 | 17.39 | 0.123756E+09 | 70.31 | 07-SEP-06:00 | 32.83 | 17.39 |
| October | 0.218363E+10 | 2690.44 | 15-OCT-15:10 | 30.83 | 15.40 | 0.125892E+09 | 70.31 | 19-OCT-03:49 | 13.00 | 13.00 |
| November | 0.150008E+10 | 2128.74 | 19-NOV-13:30 | 26.00 | 15.06 | 0.117912E+09 | 70.31 | 03-NOV-21:49 | 26.00 | 15.06 |
| December | 0.156512E+10 | 1965.13 | 19-DEC-13:40 | 24.00 | 10.42 | 0.119311E+09 | 70.31 | 31-DEC-21:30 | 12.00 | 7.16 |
| Annual Sum or Average | 0.194053E+11 | 0.142719E+10 | ||||||||
| Minimum of Months | 0.111451E+10 | 1375.72 | 20.83 | 8.84 | 0.102623E+09 | 70.27 | 12.00 | 7.16 | ||
| Maximum of Months | 0.221597E+10 | 2690.44 | 32.83 | 19.02 | 0.129241E+09 | 70.31 | 32.83 | 19.02 |
Report: ZoneCoolingSummaryMonthly
For: M NW APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.668648E+09 | 769.59 | 18-JAN-14:50 | 23.27 | 14.80 | 99787254.13 | 70.28 | 17-JAN-23:19 | 23.27 | 14.80 |
| February | 0.664321E+09 | 529.63 | 03-FEB-18:20 | 15.33 | 8.53 | 91976904.21 | 67.91 | 03-FEB-21:10 | 12.33 | 6.81 |
| March | 0.759885E+09 | 953.06 | 23-MAR-16:05 | 20.67 | 16.98 | 0.102081E+09 | 70.27 | 22-MAR-21:19 | 20.67 | 16.98 |
| April | 0.999841E+09 | 1403.99 | 26-APR-16:20 | 22.00 | 16.55 | 0.117548E+09 | 70.31 | 16-APR-20:40 | 22.00 | 16.55 |
| May | 0.114039E+10 | 1264.94 | 03-MAY-16:10 | 20.83 | 15.02 | 0.124274E+09 | 70.31 | 17-MAY-23:10 | 12.83 | 11.71 |
| June | 0.152325E+10 | 1561.02 | 29-JUN-17:10 | 22.83 | 18.47 | 0.124109E+09 | 70.30 | 14-JUN-02:09 | 22.83 | 18.47 |
| July | 0.198866E+10 | 1706.71 | 19-JUL-16:40 | 24.33 | 19.61 | 0.128743E+09 | 70.31 | 10-JUL-05:49 | 24.33 | 19.61 |
| August | 0.185917E+10 | 1618.64 | 19-AUG-16:30 | 24.50 | 18.31 | 0.128699E+09 | 70.31 | 31-AUG-05:10 | 15.17 | 14.50 |
| September | 0.139588E+10 | 1870.96 | 29-SEP-16:08 | 31.67 | 16.86 | 0.124138E+09 | 70.31 | 02-SEP-23:49 | 31.67 | 16.86 |
| October | 0.131913E+10 | 1718.90 | 15-OCT-16:10 | 29.50 | 14.82 | 0.125518E+09 | 70.31 | 23-OCT-23:30 | 16.50 | 13.76 |
| November | 0.709172E+09 | 653.61 | 19-NOV-14:00 | 25.00 | 15.09 | 0.108102E+09 | 70.30 | 18-NOV-21:10 | 25.00 | 15.09 |
| December | 0.718656E+09 | 710.53 | 05-DEC-15:30 | 24.00 | 12.83 | 0.102215E+09 | 70.27 | 05-DEC-22:40 | 17.67 | 9.41 |
| Annual Sum or Average | 0.137470E+11 | 0.137719E+10 | ||||||||
| Minimum of Months | 0.664321E+09 | 529.63 | 15.33 | 8.53 | 91976904.21 | 67.91 | 12.33 | 6.81 | ||
| Maximum of Months | 0.198866E+10 | 1870.96 | 31.67 | 19.61 | 0.128743E+09 | 70.31 | 31.67 | 19.61 |
Report: ZoneCoolingSummaryMonthly
For: M SE APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.144681E+10 | 1751.84 | 18-JAN-13:50 | 24.83 | 14.80 | 0.116776E+09 | 70.31 | 16-JAN-23:00 | 24.83 | 14.80 |
| February | 0.111557E+10 | 1631.53 | 01-FEB-12:40 | 24.67 | 14.11 | 0.102217E+09 | 70.31 | 06-FEB-21:19 | 9.33 | 7.30 |
| March | 0.111403E+10 | 1429.39 | 11-MAR-13:00 | 24.00 | 13.82 | 0.107550E+09 | 70.31 | 03-MAR-20:19 | 24.00 | 13.82 |
| April | 0.141737E+10 | 1588.50 | 26-APR-13:00 | 27.00 | 17.13 | 0.119185E+09 | 70.31 | 07-APR-23:19 | 27.00 | 17.13 |
| May | 0.118123E+10 | 1305.38 | 04-MAY-12:00 | 24.00 | 16.55 | 0.121030E+09 | 70.31 | 11-MAY-18:49 | 13.17 | 10.78 |
| June | 0.145184E+10 | 1238.72 | 30-JUN-10:00 | 24.00 | 18.12 | 0.119803E+09 | 70.31 | 07-JUN-20:00 | 24.00 | 18.12 |
| July | 0.203059E+10 | 1542.11 | 23-JUL-11:00 | 26.00 | 20.47 | 0.129215E+09 | 70.30 | 07-JUL-06:10 | 26.00 | 20.47 |
| August | 0.220337E+10 | 1654.90 | 19-AUG-13:00 | 27.00 | 20.18 | 0.123918E+09 | 70.28 | 11-AUG-05:40 | 27.00 | 20.18 |
| September | 0.193302E+10 | 2421.46 | 29-SEP-13:00 | 36.00 | 18.20 | 0.123661E+09 | 70.31 | 16-SEP-00:20 | 36.00 | 18.20 |
| October | 0.216108E+10 | 2729.86 | 16-OCT-12:00 | 36.00 | 17.61 | 0.125876E+09 | 70.31 | 24-OCT-22:30 | 14.00 | 12.23 |
| November | 0.147851E+10 | 2139.13 | 19-NOV-13:00 | 27.00 | 14.96 | 0.117849E+09 | 70.32 | 02-NOV-19:49 | 27.00 | 14.96 |
| December | 0.157275E+10 | 1957.38 | 19-DEC-13:00 | 26.00 | 11.60 | 0.119323E+09 | 70.31 | 02-DEC-21:49 | 26.00 | 11.60 |
| Annual Sum or Average | 0.191062E+11 | 0.142640E+10 | ||||||||
| Minimum of Months | 0.111403E+10 | 1238.72 | 24.00 | 11.60 | 0.102217E+09 | 70.28 | 9.33 | 7.30 | ||
| Maximum of Months | 0.220337E+10 | 2729.86 | 36.00 | 20.47 | 0.129215E+09 | 70.32 | 36.00 | 20.47 |
Report: ZoneCoolingSummaryMonthly
For: M NE APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.685489E+09 | 638.67 | 18-JAN-13:00 | 26.00 | 14.69 | 0.100139E+09 | 70.27 | 18-JAN-23:10 | 15.67 | 12.73 |
| February | 0.660450E+09 | 495.94 | 04-FEB-06:00 | 5.00 | 0.22 | 91026295.18 | 67.41 | 17-FEB-22:10 | 13.67 | 12.71 |
| March | 0.757130E+09 | 651.10 | 23-MAR-10:00 | 22.00 | 16.42 | 0.101763E+09 | 70.31 | 19-MAR-20:19 | 22.00 | 16.42 |
| April | 0.973345E+09 | 1151.05 | 26-APR-11:00 | 26.00 | 18.33 | 0.117249E+09 | 70.31 | 20-APR-21:49 | 26.00 | 18.33 |
| May | 0.109205E+10 | 1082.92 | 04-MAY-12:00 | 24.00 | 16.55 | 0.123984E+09 | 70.31 | 31-MAY-22:19 | 13.60 | 12.65 |
| June | 0.145224E+10 | 1261.83 | 30-JUN-10:00 | 24.00 | 18.12 | 0.124020E+09 | 70.31 | 04-JUN-01:19 | 24.00 | 18.12 |
| July | 0.194154E+10 | 1439.80 | 19-JUL-10:10 | 27.17 | 20.23 | 0.128716E+09 | 70.29 | 06-JUL-02:39 | 27.17 | 20.23 |
| August | 0.184640E+10 | 1353.84 | 14-AUG-10:20 | 27.27 | 21.02 | 0.128692E+09 | 70.31 | 23-AUG-02:39 | 15.20 | 13.92 |
| September | 0.131446E+10 | 1601.32 | 29-SEP-13:00 | 36.00 | 18.20 | 0.123969E+09 | 70.31 | 05-SEP-00:00 | 36.00 | 18.20 |
| October | 0.129123E+10 | 1752.04 | 16-OCT-10:50 | 36.67 | 17.68 | 0.125468E+09 | 70.32 | 14-OCT-00:40 | 36.67 | 17.68 |
| November | 0.700917E+09 | 636.30 | 19-NOV-13:00 | 27.00 | 14.96 | 0.107160E+09 | 70.27 | 01-NOV-20:10 | 27.00 | 14.96 |
| December | 0.722316E+09 | 530.52 | 05-DEC-15:10 | 24.67 | 13.10 | 0.101942E+09 | 70.27 | 05-DEC-22:40 | 17.67 | 9.41 |
| Annual Sum or Average | 0.134376E+11 | 0.137413E+10 | ||||||||
| Minimum of Months | 0.660450E+09 | 495.94 | 5.00 | 0.22 | 91026295.18 | 67.41 | 13.60 | 9.41 | ||
| Maximum of Months | 0.194154E+10 | 1752.04 | 36.67 | 21.02 | 0.128716E+09 | 70.32 | 36.67 | 20.23 |
Report: ZoneCoolingSummaryMonthly
For: M N1 APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.819461E+09 | 599.93 | 18-JAN-13:00 | 26.00 | 14.69 | 0.106038E+09 | 70.31 | 19-JAN-00:00 | 14.00 | 11.21 |
| February | 0.705983E+09 | 525.16 | 03-FEB-18:17 | 15.33 | 8.53 | 0.100585E+09 | 70.27 | 03-FEB-21:10 | 12.33 | 6.81 |
| March | 0.848607E+09 | 599.62 | 24-MAR-17:06 | 15.50 | 13.31 | 0.109308E+09 | 70.31 | 17-MAR-20:19 | 15.50 | 13.31 |
| April | 0.938590E+09 | 832.65 | 26-APR-17:00 | 22.00 | 16.84 | 0.120453E+09 | 70.31 | 24-APR-00:10 | 22.00 | 16.84 |
| May | 0.108663E+10 | 816.80 | 04-MAY-16:03 | 21.67 | 15.62 | 0.126952E+09 | 70.32 | 11-MAY-22:00 | 13.00 | 10.29 |
| June | 0.135459E+10 | 1011.14 | 29-JUN-17:30 | 22.50 | 18.54 | 0.124531E+09 | 70.31 | 24-JUN-05:00 | 22.50 | 18.54 |
| July | 0.166736E+10 | 1109.50 | 18-JUL-17:50 | 24.00 | 19.89 | 0.128771E+09 | 70.31 | 12-JUL-05:40 | 24.00 | 19.89 |
| August | 0.158268E+10 | 1007.28 | 17-AUG-16:10 | 24.72 | 20.07 | 0.128752E+09 | 70.29 | 21-AUG-05:30 | 16.75 | 15.43 |
| September | 0.126392E+10 | 1173.99 | 29-SEP-16:04 | 31.67 | 16.86 | 0.124483E+09 | 70.30 | 19-SEP-03:20 | 31.67 | 16.86 |
| October | 0.126752E+10 | 1171.39 | 16-OCT-12:00 | 36.00 | 17.61 | 0.127451E+09 | 70.31 | 18-OCT-03:39 | 14.00 | 8.92 |
| November | 0.767852E+09 | 568.57 | 11-NOV-19:20 | 15.33 | 14.33 | 0.115361E+09 | 70.31 | 02-NOV-20:19 | 15.33 | 14.33 |
| December | 0.806588E+09 | 609.35 | 19-DEC-18:15 | 15.33 | 5.75 | 0.110925E+09 | 70.31 | 04-DEC-22:49 | 15.33 | 5.75 |
| Annual Sum or Average | 0.131098E+11 | 0.142361E+10 | ||||||||
| Minimum of Months | 0.705983E+09 | 525.16 | 15.33 | 5.75 | 0.100585E+09 | 70.27 | 12.33 | 5.75 | ||
| Maximum of Months | 0.166736E+10 | 1173.99 | 36.00 | 20.07 | 0.128771E+09 | 70.32 | 31.67 | 19.89 |
Report: ZoneCoolingSummaryMonthly
For: M N2 APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.821592E+09 | 603.43 | 18-JAN-13:00 | 26.00 | 14.69 | 0.106157E+09 | 70.31 | 19-JAN-00:49 | 14.00 | 11.21 |
| February | 0.705627E+09 | 521.99 | 04-FEB-06:00 | 5.00 | 0.22 | 0.100510E+09 | 70.27 | 03-FEB-21:10 | 5.00 | 0.22 |
| March | 0.850187E+09 | 613.09 | 24-MAR-17:06 | 15.50 | 13.31 | 0.109270E+09 | 70.28 | 21-MAR-21:49 | 15.50 | 13.31 |
| April | 0.938815E+09 | 826.89 | 26-APR-17:00 | 22.00 | 16.84 | 0.120459E+09 | 70.31 | 21-APR-20:30 | 22.00 | 16.84 |
| May | 0.108540E+10 | 816.96 | 04-MAY-16:03 | 21.67 | 15.62 | 0.126935E+09 | 70.32 | 11-MAY-22:00 | 13.00 | 10.29 |
| June | 0.135167E+10 | 1002.88 | 29-JUN-17:30 | 22.50 | 18.54 | 0.124528E+09 | 70.30 | 05-JUN-02:09 | 22.50 | 18.54 |
| July | 0.166547E+10 | 1103.89 | 18-JUL-17:50 | 24.00 | 19.89 | 0.128771E+09 | 70.29 | 08-JUL-05:19 | 24.00 | 19.89 |
| August | 0.158222E+10 | 1003.76 | 17-AUG-16:10 | 24.72 | 20.07 | 0.128751E+09 | 70.27 | 21-AUG-05:30 | 16.75 | 15.43 |
| September | 0.126019E+10 | 1169.57 | 29-SEP-16:04 | 31.67 | 16.86 | 0.124475E+09 | 70.30 | 21-SEP-05:00 | 31.67 | 16.86 |
| October | 0.126772E+10 | 1177.47 | 16-OCT-12:00 | 36.00 | 17.61 | 0.127448E+09 | 70.31 | 31-OCT-02:20 | 15.33 | 10.66 |
| November | 0.766375E+09 | 561.86 | 11-NOV-19:20 | 15.33 | 14.33 | 0.115296E+09 | 70.31 | 03-NOV-20:40 | 15.33 | 14.33 |
| December | 0.807393E+09 | 612.51 | 19-DEC-18:15 | 15.33 | 5.75 | 0.110924E+09 | 70.32 | 06-DEC-00:30 | 15.33 | 5.75 |
| Annual Sum or Average | 0.131026E+11 | 0.142352E+10 | ||||||||
| Minimum of Months | 0.705627E+09 | 521.99 | 5.00 | 0.22 | 0.100510E+09 | 70.27 | 5.00 | 0.22 | ||
| Maximum of Months | 0.166547E+10 | 1177.47 | 36.00 | 20.07 | 0.128771E+09 | 70.32 | 31.67 | 19.89 |
Report: ZoneCoolingSummaryMonthly
For: M S1 APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.168610E+10 | 1712.46 | 18-JAN-14:00 | 24.60 | 14.81 | 0.123334E+09 | 70.32 | 29-JAN-00:40 | 10.00 | 9.80 |
| February | 0.127718E+10 | 1543.47 | 01-FEB-13:00 | 24.00 | 13.82 | 0.109743E+09 | 70.31 | 02-FEB-03:20 | 13.00 | 11.48 |
| March | 0.125004E+10 | 1334.33 | 11-MAR-13:50 | 24.00 | 12.91 | 0.115138E+09 | 70.31 | 24-MAR-03:20 | 12.47 | 12.47 |
| April | 0.140720E+10 | 1249.77 | 26-APR-13:00 | 27.00 | 17.13 | 0.121836E+09 | 70.31 | 22-APR-16:10 | 27.00 | 17.13 |
| May | 0.117912E+10 | 1005.01 | 03-MAY-13:00 | 24.00 | 15.05 | 0.123900E+09 | 70.31 | 24-MAY-03:00 | 15.00 | 7.56 |
| June | 0.135322E+10 | 943.69 | 29-JUN-17:15 | 22.67 | 18.51 | 0.120320E+09 | 70.31 | 01-JUN-00:00 | 22.67 | 18.51 |
| July | 0.175659E+10 | 1166.87 | 23-JUL-16:05 | 24.00 | 19.22 | 0.129270E+09 | 70.30 | 09-JUL-05:40 | 24.00 | 19.22 |
| August | 0.194210E+10 | 1299.01 | 30-AUG-13:00 | 24.00 | 18.12 | 0.123955E+09 | 70.27 | 02-AUG-05:30 | 24.00 | 18.12 |
| September | 0.189558E+10 | 1923.51 | 29-SEP-13:30 | 35.00 | 18.05 | 0.123945E+09 | 70.30 | 30-SEP-17:00 | 23.00 | 16.65 |
| October | 0.217162E+10 | 2173.98 | 16-OCT-12:00 | 36.00 | 17.61 | 0.127143E+09 | 70.30 | 15-OCT-06:00 | 36.00 | 17.61 |
| November | 0.172151E+10 | 1978.63 | 19-NOV-13:00 | 27.00 | 14.96 | 0.121908E+09 | 70.30 | 10-NOV-05:10 | 27.00 | 14.96 |
| December | 0.183820E+10 | 1869.55 | 19-DEC-13:00 | 26.00 | 11.60 | 0.125183E+09 | 70.32 | 18-DEC-01:10 | 26.00 | 11.60 |
| Annual Sum or Average | 0.194785E+11 | 0.146567E+10 | ||||||||
| Minimum of Months | 0.117912E+10 | 943.69 | 22.67 | 11.60 | 0.109743E+09 | 70.27 | 10.00 | 7.56 | ||
| Maximum of Months | 0.217162E+10 | 2173.98 | 36.00 | 19.22 | 0.129270E+09 | 70.32 | 36.00 | 19.22 |
Report: ZoneCoolingSummaryMonthly
For: M S2 APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.169086E+10 | 1713.64 | 18-JAN-14:00 | 24.60 | 14.81 | 0.123402E+09 | 70.30 | 16-JAN-21:40 | 24.60 | 14.81 |
| February | 0.127766E+10 | 1546.19 | 01-FEB-13:00 | 24.00 | 13.82 | 0.109707E+09 | 70.31 | 10-FEB-21:19 | 11.83 | 10.77 |
| March | 0.125159E+10 | 1340.57 | 11-MAR-13:50 | 24.00 | 12.91 | 0.115109E+09 | 70.31 | 26-MAR-20:00 | 12.00 | 10.91 |
| April | 0.140766E+10 | 1256.10 | 26-APR-13:00 | 27.00 | 17.13 | 0.121837E+09 | 70.31 | 01-APR-18:19 | 27.00 | 17.13 |
| May | 0.117810E+10 | 1009.21 | 03-MAY-13:00 | 24.00 | 15.05 | 0.123888E+09 | 70.31 | 24-MAY-03:00 | 15.00 | 7.56 |
| June | 0.135037E+10 | 935.66 | 29-JUN-17:15 | 22.67 | 18.51 | 0.120318E+09 | 70.31 | 01-JUN-00:00 | 22.67 | 18.51 |
| July | 0.175473E+10 | 1164.33 | 23-JUL-16:05 | 24.00 | 19.22 | 0.129270E+09 | 70.29 | 09-JUL-05:40 | 24.00 | 19.22 |
| August | 0.194166E+10 | 1303.69 | 30-AUG-13:00 | 24.00 | 18.12 | 0.123954E+09 | 70.27 | 19-AUG-09:30 | 24.00 | 18.12 |
| September | 0.189198E+10 | 1926.81 | 29-SEP-13:30 | 35.00 | 18.05 | 0.123943E+09 | 70.30 | 30-SEP-17:00 | 23.00 | 16.65 |
| October | 0.217136E+10 | 2180.19 | 16-OCT-12:00 | 36.00 | 17.61 | 0.127140E+09 | 70.31 | 31-OCT-04:10 | 12.00 | 7.99 |
| November | 0.172158E+10 | 1982.58 | 19-NOV-13:00 | 27.00 | 14.96 | 0.121895E+09 | 70.31 | 01-NOV-04:10 | 27.00 | 14.96 |
| December | 0.184023E+10 | 1872.81 | 19-DEC-13:00 | 26.00 | 11.60 | 0.125175E+09 | 70.32 | 18-DEC-01:10 | 26.00 | 11.60 |
| Annual Sum or Average | 0.194778E+11 | 0.146564E+10 | ||||||||
| Minimum of Months | 0.117810E+10 | 935.66 | 22.67 | 11.60 | 0.109707E+09 | 70.27 | 11.83 | 7.56 | ||
| Maximum of Months | 0.217136E+10 | 2180.19 | 36.00 | 19.22 | 0.129270E+09 | 70.32 | 27.00 | 19.22 |
Report: ZoneCoolingSummaryMonthly
For: T SW APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.937650E+09 | 2393.26 | 18-JAN-14:30 | 23.80 | 14.82 | 96104345.83 | 70.36 | 17-JAN-20:10 | 23.80 | 14.82 |
| February | 0.673910E+09 | 1810.53 | 03-FEB-15:00 | 23.00 | 8.84 | 81532389.14 | 70.34 | 05-FEB-19:19 | 11.67 | 9.65 |
| March | 0.770573E+09 | 2044.81 | 11-MAR-15:10 | 22.00 | 13.04 | 88267614.03 | 70.34 | 18-MAR-18:40 | 14.33 | 12.96 |
| April | 0.123067E+10 | 2188.90 | 26-APR-14:30 | 24.50 | 16.53 | 0.101286E+09 | 70.35 | 10-APR-19:00 | 24.50 | 16.53 |
| May | 0.982286E+09 | 1836.86 | 03-MAY-15:10 | 21.83 | 15.33 | 0.102348E+09 | 70.35 | 17-MAY-20:40 | 15.00 | 12.48 |
| June | 0.136662E+10 | 1979.19 | 30-JUN-16:07 | 22.58 | 17.92 | 0.110734E+09 | 70.36 | 06-JUN-20:30 | 22.58 | 17.92 |
| July | 0.202185E+10 | 2324.48 | 23-JUL-16:20 | 24.00 | 19.12 | 0.125804E+09 | 70.35 | 16-JUL-22:49 | 24.00 | 19.12 |
| August | 0.214961E+10 | 2537.54 | 19-AUG-16:10 | 24.83 | 18.75 | 0.120189E+09 | 70.35 | 30-AUG-00:10 | 18.00 | 15.44 |
| September | 0.179449E+10 | 3535.84 | 29-SEP-14:10 | 33.83 | 17.79 | 0.116392E+09 | 70.35 | 03-SEP-22:19 | 33.83 | 17.79 |
| October | 0.187889E+10 | 3608.48 | 16-OCT-13:40 | 32.70 | 16.16 | 0.114642E+09 | 70.37 | 11-OCT-19:00 | 32.70 | 16.16 |
| November | 0.988248E+09 | 2621.47 | 19-NOV-13:30 | 26.00 | 15.06 | 95303037.61 | 70.36 | 01-NOV-19:00 | 26.00 | 15.06 |
| December | 0.103898E+10 | 2282.57 | 19-DEC-13:40 | 24.00 | 10.42 | 96085562.60 | 70.34 | 07-DEC-21:10 | 24.00 | 10.42 |
| Annual Sum or Average | 0.158338E+11 | 0.124869E+10 | ||||||||
| Minimum of Months | 0.673910E+09 | 1810.53 | 21.83 | 8.84 | 81532389.14 | 70.34 | 11.67 | 9.65 | ||
| Maximum of Months | 0.214961E+10 | 3608.48 | 33.83 | 19.12 | 0.125804E+09 | 70.37 | 33.83 | 19.12 |
Report: ZoneCoolingSummaryMonthly
For: T NW APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.322636E+09 | 810.26 | 18-JAN-15:10 | 22.83 | 14.90 | 85968124.29 | 67.36 | 18-JAN-21:10 | 17.83 | 13.82 |
| February | 0.274009E+09 | 459.97 | 03-FEB-15:20 | 22.33 | 9.30 | 76204701.17 | 59.74 | 01-FEB-18:10 | 22.33 | 9.30 |
| March | 0.408038E+09 | 1157.06 | 23-MAR-16:05 | 20.67 | 16.98 | 87120135.31 | 67.40 | 22-MAR-20:10 | 20.67 | 16.98 |
| April | 0.802692E+09 | 1755.50 | 26-APR-16:13 | 22.00 | 16.55 | 98980246.38 | 70.33 | 26-APR-22:19 | 16.00 | 15.18 |
| May | 0.884081E+09 | 1643.16 | 03-MAY-16:05 | 20.83 | 15.02 | 0.105491E+09 | 70.35 | 03-MAY-23:30 | 16.00 | 13.86 |
| June | 0.134631E+10 | 1978.50 | 29-JUN-16:40 | 23.00 | 18.43 | 0.115318E+09 | 70.35 | 24-JUN-00:49 | 23.00 | 18.43 |
| July | 0.190836E+10 | 2279.53 | 19-JUL-16:30 | 24.50 | 19.76 | 0.125453E+09 | 70.34 | 02-JUL-00:00 | 24.50 | 19.76 |
| August | 0.175683E+10 | 2169.82 | 17-AUG-16:05 | 24.72 | 20.07 | 0.124363E+09 | 70.34 | 20-AUG-22:30 | 16.25 | 15.63 |
| September | 0.115943E+10 | 2617.16 | 29-SEP-15:30 | 32.50 | 17.18 | 0.115138E+09 | 70.34 | 10-SEP-21:00 | 32.50 | 17.18 |
| October | 0.102572E+10 | 2338.88 | 16-OCT-15:10 | 29.83 | 15.97 | 0.112436E+09 | 70.36 | 16-OCT-02:09 | 29.83 | 15.97 |
| November | 0.362888E+09 | 816.74 | 19-NOV-14:00 | 25.00 | 15.09 | 85579202.44 | 62.79 | 18-NOV-21:10 | 25.00 | 15.09 |
| December | 0.297610E+09 | 912.16 | 05-DEC-15:30 | 24.00 | 12.83 | 85540398.66 | 64.51 | 05-DEC-22:49 | 17.83 | 9.39 |
| Annual Sum or Average | 0.105486E+11 | 0.121759E+10 | ||||||||
| Minimum of Months | 0.274009E+09 | 459.97 | 20.67 | 9.30 | 76204701.17 | 59.74 | 16.00 | 9.30 | ||
| Maximum of Months | 0.190836E+10 | 2617.16 | 32.50 | 20.07 | 0.125453E+09 | 70.36 | 32.50 | 19.76 |
Report: ZoneCoolingSummaryMonthly
For: T SE APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.949215E+09 | 2138.30 | 18-JAN-14:00 | 24.60 | 14.81 | 96123772.06 | 70.35 | 07-JAN-17:40 | 24.60 | 14.81 |
| February | 0.649152E+09 | 1797.15 | 01-FEB-13:00 | 24.00 | 13.82 | 81016333.65 | 70.34 | 21-FEB-19:40 | 13.00 | 12.44 |
| March | 0.762122E+09 | 1977.04 | 11-MAR-13:40 | 24.00 | 13.10 | 87792498.85 | 70.34 | 12-MAR-19:30 | 13.00 | 12.44 |
| April | 0.119497E+10 | 2103.66 | 26-APR-13:00 | 27.00 | 17.13 | 0.100452E+09 | 70.35 | 20-APR-20:19 | 27.00 | 17.13 |
| May | 0.924957E+09 | 1756.65 | 04-MAY-12:00 | 24.00 | 16.55 | 0.101340E+09 | 70.36 | 30-MAY-18:00 | 14.00 | 12.24 |
| June | 0.130298E+10 | 1710.57 | 30-JUN-12:00 | 24.00 | 18.12 | 0.109708E+09 | 70.35 | 06-JUN-19:49 | 24.00 | 18.12 |
| July | 0.198531E+10 | 2097.76 | 31-JUL-13:00 | 28.00 | 21.19 | 0.125177E+09 | 70.35 | 04-JUL-20:49 | 28.00 | 21.19 |
| August | 0.214648E+10 | 2293.74 | 19-AUG-13:00 | 27.00 | 20.18 | 0.119776E+09 | 70.34 | 10-AUG-23:10 | 27.00 | 20.18 |
| September | 0.171832E+10 | 3438.80 | 29-SEP-13:00 | 36.00 | 18.20 | 0.115600E+09 | 70.36 | 19-SEP-20:49 | 36.00 | 18.20 |
| October | 0.184878E+10 | 3710.78 | 16-OCT-12:00 | 36.00 | 17.61 | 0.114466E+09 | 70.35 | 15-OCT-01:49 | 36.00 | 17.61 |
| November | 0.957070E+09 | 2623.55 | 19-NOV-13:00 | 27.00 | 14.96 | 94849657.45 | 70.36 | 14-NOV-18:10 | 27.00 | 14.96 |
| December | 0.103560E+10 | 2264.55 | 19-DEC-13:00 | 26.00 | 11.60 | 95944047.61 | 70.31 | 17-DEC-17:10 | 26.00 | 11.60 |
| Annual Sum or Average | 0.154749E+11 | 0.124225E+10 | ||||||||
| Minimum of Months | 0.649152E+09 | 1710.57 | 24.00 | 11.60 | 81016333.65 | 70.31 | 13.00 | 11.60 | ||
| Maximum of Months | 0.214648E+10 | 3710.78 | 36.00 | 21.19 | 0.125177E+09 | 70.36 | 36.00 | 21.19 |
Report: ZoneCoolingSummaryMonthly
For: T NE APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.328542E+09 | 601.35 | 18-JAN-13:50 | 24.83 | 14.80 | 85587405.51 | 66.49 | 17-JAN-21:10 | 24.83 | 14.80 |
| February | 0.269806E+09 | 450.78 | 01-FEB-12:40 | 24.67 | 14.11 | 75122168.47 | 54.54 | 03-FEB-19:10 | 13.83 | 7.99 |
| March | 0.403562E+09 | 696.48 | 23-MAR-14:10 | 22.83 | 17.30 | 86432062.96 | 64.82 | 23-MAR-20:10 | 14.00 | 13.42 |
| April | 0.773264E+09 | 1452.66 | 26-APR-13:00 | 27.00 | 17.13 | 97534952.09 | 70.27 | 25-APR-21:10 | 27.00 | 17.13 |
| May | 0.827783E+09 | 1445.23 | 04-MAY-12:00 | 24.00 | 16.55 | 0.104442E+09 | 70.31 | 02-MAY-20:10 | 24.00 | 16.55 |
| June | 0.128083E+10 | 1625.64 | 30-JUN-10:10 | 23.83 | 18.08 | 0.114480E+09 | 70.34 | 29-JUN-22:10 | 23.83 | 18.08 |
| July | 0.187319E+10 | 1931.44 | 19-JUL-12:00 | 28.00 | 21.19 | 0.124828E+09 | 70.34 | 02-JUL-22:19 | 28.00 | 21.19 |
| August | 0.175549E+10 | 1793.51 | 14-AUG-11:00 | 28.00 | 21.19 | 0.123810E+09 | 70.34 | 08-AUG-23:40 | 28.00 | 21.19 |
| September | 0.109176E+10 | 2324.13 | 29-SEP-13:00 | 36.00 | 18.20 | 0.113773E+09 | 70.35 | 23-SEP-21:00 | 36.00 | 18.20 |
| October | 0.996715E+09 | 2396.88 | 16-OCT-12:00 | 36.00 | 17.61 | 0.111663E+09 | 70.36 | 16-OCT-01:49 | 36.00 | 17.61 |
| November | 0.362938E+09 | 792.71 | 19-NOV-13:00 | 27.00 | 14.96 | 84270689.88 | 61.76 | 19-NOV-21:10 | 13.83 | 13.83 |
| December | 0.294819E+09 | 645.14 | 05-DEC-15:00 | 25.00 | 13.22 | 84901009.69 | 63.98 | 05-DEC-22:49 | 17.83 | 9.39 |
| Annual Sum or Average | 0.102587E+11 | 0.120684E+10 | ||||||||
| Minimum of Months | 0.269806E+09 | 450.78 | 22.83 | 13.22 | 75122168.47 | 54.54 | 13.83 | 7.99 | ||
| Maximum of Months | 0.187319E+10 | 2396.88 | 36.00 | 21.19 | 0.124828E+09 | 70.36 | 36.00 | 21.19 |
Report: ZoneCoolingSummaryMonthly
For: T N1 APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.376265E+09 | 490.79 | 18-JAN-14:20 | 24.07 | 14.82 | 87791821.27 | 69.06 | 18-JAN-21:10 | 17.83 | 13.82 |
| February | 0.348227E+09 | 385.90 | 21-FEB-21:00 | 9.00 | 9.00 | 76864943.71 | 58.24 | 01-FEB-21:10 | 9.00 | 9.00 |
| March | 0.461979E+09 | 486.72 | 23-MAR-16:05 | 20.67 | 16.98 | 88377032.06 | 67.18 | 23-MAR-20:10 | 14.00 | 13.42 |
| April | 0.694699E+09 | 1056.07 | 26-APR-14:10 | 25.50 | 16.68 | 0.101850E+09 | 70.32 | 12-APR-20:19 | 25.50 | 16.68 |
| May | 0.767756E+09 | 1087.06 | 03-MAY-13:00 | 24.00 | 15.05 | 0.109553E+09 | 70.35 | 23-MAY-20:10 | 13.08 | 11.95 |
| June | 0.111210E+10 | 1239.75 | 29-JUN-17:20 | 22.67 | 18.51 | 0.118403E+09 | 70.35 | 19-JUN-20:00 | 22.67 | 18.51 |
| July | 0.155498E+10 | 1445.08 | 19-JUL-16:15 | 24.67 | 19.90 | 0.126985E+09 | 70.35 | 07-JUL-00:40 | 24.67 | 19.90 |
| August | 0.143717E+10 | 1367.08 | 17-AUG-15:10 | 26.42 | 20.67 | 0.126443E+09 | 70.35 | 30-AUG-01:10 | 18.00 | 15.44 |
| September | 0.960924E+09 | 1709.32 | 29-SEP-14:10 | 33.83 | 17.79 | 0.118027E+09 | 70.35 | 19-SEP-20:10 | 33.83 | 17.79 |
| October | 0.914074E+09 | 1668.90 | 16-OCT-12:30 | 35.05 | 17.21 | 0.115531E+09 | 70.34 | 06-OCT-22:00 | 35.05 | 17.21 |
| November | 0.417526E+09 | 523.24 | 19-NOV-13:50 | 25.33 | 15.09 | 87349121.38 | 65.27 | 19-NOV-21:10 | 13.83 | 13.83 |
| December | 0.353945E+09 | 494.45 | 05-DEC-15:10 | 24.67 | 13.10 | 86992969.13 | 67.41 | 05-DEC-23:10 | 17.33 | 9.21 |
| Annual Sum or Average | 0.939965E+10 | 0.124417E+10 | ||||||||
| Minimum of Months | 0.348227E+09 | 385.90 | 9.00 | 9.00 | 76864943.71 | 58.24 | 9.00 | 9.00 | ||
| Maximum of Months | 0.155498E+10 | 1709.32 | 35.05 | 20.67 | 0.126985E+09 | 70.35 | 35.05 | 19.90 |
Report: ZoneCoolingSummaryMonthly
For: T N2 APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.377420E+09 | 494.67 | 18-JAN-14:20 | 24.07 | 14.82 | 87786354.28 | 69.04 | 17-JAN-21:10 | 24.07 | 14.82 |
| February | 0.346712E+09 | 385.21 | 03-FEB-22:00 | 9.00 | 4.21 | 76774350.94 | 57.94 | 01-FEB-21:10 | 9.00 | 4.21 |
| March | 0.462472E+09 | 483.72 | 23-MAR-16:05 | 20.67 | 16.98 | 88354953.89 | 67.07 | 23-MAR-20:10 | 14.00 | 13.42 |
| April | 0.696748E+09 | 1063.77 | 26-APR-14:10 | 25.50 | 16.68 | 0.101679E+09 | 70.34 | 26-APR-22:49 | 16.00 | 14.87 |
| May | 0.768500E+09 | 1097.58 | 03-MAY-13:00 | 24.00 | 15.05 | 0.109410E+09 | 70.34 | 24-MAY-23:10 | 16.00 | 14.13 |
| June | 0.111089E+10 | 1221.96 | 29-JUN-17:20 | 22.67 | 18.51 | 0.118296E+09 | 70.35 | 07-JUN-22:19 | 22.67 | 18.51 |
| July | 0.155388E+10 | 1434.43 | 19-JUL-16:15 | 24.67 | 19.90 | 0.126926E+09 | 70.35 | 04-JUL-04:10 | 24.67 | 19.90 |
| August | 0.143828E+10 | 1363.32 | 17-AUG-15:10 | 26.42 | 20.67 | 0.126383E+09 | 70.35 | 30-AUG-00:49 | 18.00 | 15.44 |
| September | 0.959218E+09 | 1710.79 | 29-SEP-14:10 | 33.83 | 17.79 | 0.117855E+09 | 70.35 | 19-SEP-20:10 | 33.83 | 17.79 |
| October | 0.915295E+09 | 1682.10 | 16-OCT-12:00 | 36.00 | 17.61 | 0.115438E+09 | 70.37 | 16-OCT-04:49 | 36.00 | 17.61 |
| November | 0.416673E+09 | 530.71 | 19-NOV-13:50 | 25.33 | 15.09 | 87212923.93 | 65.22 | 19-NOV-21:10 | 13.83 | 13.83 |
| December | 0.354203E+09 | 496.43 | 05-DEC-15:10 | 24.67 | 13.10 | 86949664.94 | 67.41 | 05-DEC-23:10 | 17.33 | 9.21 |
| Annual Sum or Average | 0.940029E+10 | 0.124306E+10 | ||||||||
| Minimum of Months | 0.346712E+09 | 385.21 | 9.00 | 4.21 | 76774350.94 | 57.94 | 9.00 | 4.21 | ||
| Maximum of Months | 0.155388E+10 | 1710.79 | 36.00 | 20.67 | 0.126926E+09 | 70.37 | 36.00 | 19.90 |
Report: ZoneCoolingSummaryMonthly
For: T S1 APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.106330E+10 | 2049.25 | 18-JAN-14:10 | 24.33 | 14.82 | 0.101293E+09 | 70.34 | 26-JAN-19:40 | 11.33 | 10.39 |
| February | 0.777231E+09 | 1607.94 | 01-FEB-13:00 | 24.00 | 13.82 | 85450498.66 | 70.35 | 14-FEB-19:30 | 13.00 | 11.87 |
| March | 0.813618E+09 | 1701.63 | 11-MAR-13:50 | 24.00 | 12.91 | 92154785.25 | 70.35 | 12-MAR-20:30 | 12.50 | 12.23 |
| April | 0.111062E+10 | 1678.87 | 26-APR-13:40 | 26.33 | 16.87 | 0.105563E+09 | 70.36 | 01-APR-19:30 | 26.33 | 16.87 |
| May | 0.861506E+09 | 1429.27 | 03-MAY-13:00 | 24.00 | 15.05 | 0.106464E+09 | 70.36 | 24-MAY-22:30 | 16.00 | 14.13 |
| June | 0.113103E+10 | 1324.70 | 27-JUN-13:00 | 24.00 | 18.72 | 0.113799E+09 | 70.36 | 12-JUN-19:00 | 24.00 | 18.72 |
| July | 0.166754E+10 | 1660.87 | 31-JUL-13:00 | 28.00 | 21.19 | 0.127365E+09 | 70.35 | 16-JUL-23:10 | 28.00 | 21.19 |
| August | 0.183753E+10 | 1869.95 | 19-AUG-13:40 | 27.00 | 20.18 | 0.122118E+09 | 70.35 | 21-AUG-19:30 | 15.50 | 13.97 |
| September | 0.161163E+10 | 2800.63 | 29-SEP-13:30 | 35.00 | 18.05 | 0.119323E+09 | 70.36 | 02-SEP-21:00 | 35.00 | 18.05 |
| October | 0.178827E+10 | 3006.86 | 16-OCT-12:40 | 34.73 | 17.08 | 0.118455E+09 | 70.35 | 27-OCT-19:19 | 15.33 | 11.57 |
| November | 0.107268E+10 | 2374.04 | 19-NOV-13:00 | 27.00 | 14.96 | 0.100783E+09 | 70.37 | 05-NOV-18:49 | 27.00 | 14.96 |
| December | 0.115220E+10 | 2120.50 | 19-DEC-13:30 | 24.50 | 10.72 | 0.101454E+09 | 70.33 | 28-DEC-19:40 | 12.33 | 6.44 |
| Annual Sum or Average | 0.148871E+11 | 0.129422E+10 | ||||||||
| Minimum of Months | 0.777231E+09 | 1324.70 | 24.00 | 10.72 | 85450498.66 | 70.33 | 11.33 | 6.44 | ||
| Maximum of Months | 0.183753E+10 | 3006.86 | 35.00 | 21.19 | 0.127365E+09 | 70.37 | 35.00 | 21.19 |
Report: ZoneCoolingSummaryMonthly
For: T S2 APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.106855E+10 | 2051.68 | 18-JAN-14:00 | 24.60 | 14.81 | 0.101287E+09 | 70.36 | 17-JAN-21:30 | 24.60 | 14.81 |
| February | 0.778953E+09 | 1615.20 | 01-FEB-13:00 | 24.00 | 13.82 | 85381108.39 | 70.36 | 05-FEB-19:30 | 11.50 | 9.59 |
| March | 0.816805E+09 | 1713.37 | 11-MAR-13:50 | 24.00 | 12.91 | 92103600.85 | 70.35 | 12-MAR-20:30 | 12.50 | 12.23 |
| April | 0.111367E+10 | 1690.01 | 26-APR-13:40 | 26.33 | 16.87 | 0.105443E+09 | 70.36 | 01-APR-19:30 | 26.33 | 16.87 |
| May | 0.862787E+09 | 1439.83 | 03-MAY-13:00 | 24.00 | 15.05 | 0.106317E+09 | 70.36 | 19-MAY-17:00 | 16.00 | 13.03 |
| June | 0.113007E+10 | 1333.76 | 27-JUN-13:00 | 24.00 | 18.72 | 0.113670E+09 | 70.36 | 22-JUN-23:10 | 24.00 | 18.72 |
| July | 0.166669E+10 | 1669.96 | 31-JUL-13:00 | 28.00 | 21.19 | 0.127300E+09 | 70.35 | 04-JUL-23:19 | 28.00 | 21.19 |
| August | 0.183857E+10 | 1878.69 | 19-AUG-13:40 | 27.00 | 20.18 | 0.122076E+09 | 70.35 | 27-AUG-01:30 | 16.00 | 16.00 |
| September | 0.160923E+10 | 2807.06 | 29-SEP-13:30 | 35.00 | 18.05 | 0.119234E+09 | 70.36 | 29-SEP-01:00 | 35.00 | 18.05 |
| October | 0.178960E+10 | 3016.69 | 16-OCT-12:40 | 34.73 | 17.08 | 0.118419E+09 | 70.35 | 09-OCT-22:00 | 34.73 | 17.08 |
| November | 0.107430E+10 | 2384.06 | 19-NOV-13:00 | 27.00 | 14.96 | 0.100710E+09 | 70.36 | 01-NOV-20:49 | 27.00 | 14.96 |
| December | 0.115597E+10 | 2126.53 | 19-DEC-13:20 | 25.00 | 11.01 | 0.101414E+09 | 70.35 | 23-DEC-18:10 | 10.83 | 10.73 |
| Annual Sum or Average | 0.149052E+11 | 0.129336E+10 | ||||||||
| Minimum of Months | 0.778953E+09 | 1333.76 | 24.00 | 11.01 | 85381108.39 | 70.35 | 10.83 | 9.59 | ||
| Maximum of Months | 0.183857E+10 | 3016.69 | 35.00 | 21.19 | 0.127300E+09 | 70.36 | 35.00 | 21.19 |
Report: ZoneCoolingSummaryMonthly
For: T CORRIDOR
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 8.83 | 8.36 | 0.172195E+09 | 132.29 | 18-JAN-21:10 | 17.83 | 13.82 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 13.23 | 11.35 | 0.152344E+09 | 118.67 | 01-FEB-21:10 | 13.00 | 11.87 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 7.63 | 6.62 | 0.171388E+09 | 130.27 | 23-MAR-20:10 | 14.00 | 13.42 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 | 8.61 | 0.202127E+09 | 144.08 | 26-APR-20:10 | 16.83 | 15.13 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 15.20 | 14.50 | 0.212844E+09 | 146.71 | 04-MAY-20:10 | 17.00 | 15.07 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 | 12.03 | 0.233520E+09 | 149.56 | 29-JUN-20:10 | 16.00 | 14.87 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 | 15.81 | 0.256772E+09 | 154.99 | 19-JUL-20:10 | 18.83 | 18.28 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 | 17.20 | 0.255519E+09 | 153.33 | 19-AUG-20:10 | 18.83 | 17.61 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 | 14.83 | 0.234804E+09 | 161.38 | 29-SEP-20:10 | 24.93 | 13.57 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 | 17.39 | 0.232536E+09 | 156.07 | 16-OCT-20:10 | 20.50 | 12.73 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 | 11.07 | 0.176440E+09 | 126.39 | 19-NOV-21:10 | 13.83 | 13.83 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 10.63 | 5.44 | 0.171830E+09 | 131.97 | 05-DEC-21:10 | 16.17 | 9.15 |
| Annual Sum or Average | 0.00 | 0.247232E+10 | ||||||||
| Minimum of Months | 0.00 | 0.00 | 7.63 | 5.44 | 0.152344E+09 | 118.67 | 13.00 | 9.15 | ||
| Maximum of Months | 0.00 | 0.00 | 18.42 | 17.39 | 0.256772E+09 | 161.38 | 24.93 | 18.28 |
Report: ZoneCoolingSummaryMonthly
For: G CORRIDOR
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 8.83 | 8.36 | 0.168461E+09 | 133.34 | 18-JAN-22:49 | 16.17 | 13.11 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 13.23 | 11.35 | 0.144218E+09 | 117.13 | 02-FEB-05:49 | 12.17 | 10.50 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 7.63 | 6.62 | 0.150631E+09 | 117.90 | 23-MAR-22:10 | 12.83 | 12.37 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 | 8.61 | 0.181048E+09 | 136.07 | 30-APR-21:49 | 16.50 | 15.58 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 15.20 | 14.50 | 0.198441E+09 | 140.01 | 04-MAY-21:49 | 17.00 | 15.07 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 | 12.03 | 0.215941E+09 | 143.70 | 27-JUN-22:10 | 17.00 | 16.37 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 | 15.81 | 0.247057E+09 | 152.92 | 23-JUL-21:49 | 18.00 | 17.35 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 | 17.20 | 0.248775E+09 | 153.96 | 19-AUG-21:49 | 18.00 | 17.35 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 | 14.83 | 0.229324E+09 | 175.03 | 29-SEP-17:10 | 29.50 | 16.69 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 | 17.39 | 0.241030E+09 | 164.23 | 16-OCT-21:49 | 19.67 | 11.10 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 | 11.07 | 0.185127E+09 | 140.07 | 01-NOV-00:10 | 14.77 | 11.07 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 10.63 | 5.44 | 0.175971E+09 | 130.37 | 05-DEC-22:49 | 17.83 | 9.39 |
| Annual Sum or Average | 0.00 | 0.238602E+10 | ||||||||
| Minimum of Months | 0.00 | 0.00 | 7.63 | 5.44 | 0.144218E+09 | 117.13 | 12.17 | 9.39 | ||
| Maximum of Months | 0.00 | 0.00 | 18.42 | 17.39 | 0.248775E+09 | 175.03 | 29.50 | 17.35 |
Report: ZoneCoolingSummaryMonthly
For: M CORRIDOR
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 8.83 | 8.36 | 0.229610E+09 | 145.45 | 18-JAN-21:10 | 17.83 | 13.82 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 13.23 | 11.35 | 0.209603E+09 | 141.49 | 03-FEB-21:10 | 12.33 | 6.81 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 7.63 | 6.62 | 0.228428E+09 | 145.24 | 23-MAR-21:10 | 13.83 | 13.26 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 | 8.61 | 0.247731E+09 | 151.03 | 26-APR-20:10 | 16.83 | 15.13 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 15.20 | 14.50 | 0.259631E+09 | 150.93 | 03-MAY-20:10 | 16.00 | 14.23 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 | 12.03 | 0.260091E+09 | 152.09 | 30-JUN-20:10 | 16.00 | 15.29 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 | 15.81 | 0.274011E+09 | 154.61 | 23-JUL-20:10 | 18.83 | 17.61 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 | 17.20 | 0.273753E+09 | 154.38 | 19-AUG-20:10 | 18.83 | 17.61 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 | 14.83 | 0.261338E+09 | 157.52 | 30-SEP-20:10 | 18.82 | 17.71 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 | 17.39 | 0.267380E+09 | 157.47 | 16-OCT-20:10 | 20.50 | 12.73 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 | 11.07 | 0.239116E+09 | 144.63 | 01-NOV-00:10 | 14.77 | 11.07 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 10.63 | 5.44 | 0.236021E+09 | 144.39 | 07-DEC-21:30 | 13.40 | 13.07 |
| Annual Sum or Average | 0.00 | 0.298671E+10 | ||||||||
| Minimum of Months | 0.00 | 0.00 | 7.63 | 5.44 | 0.209603E+09 | 141.49 | 12.33 | 6.81 | ||
| Maximum of Months | 0.00 | 0.00 | 18.42 | 17.39 | 0.274011E+09 | 157.52 | 20.50 | 17.71 |
Report: ZoneHeatingSummaryMonthly
For: G SW APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 463369.02 | 60.78 | 02-JAN-03:00 | 11.00 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 13.23 |
| March | 18341449.22 | 373.61 | 30-MAR-04:00 | 4.40 |
| April | 2859842.72 | 185.15 | 01-APR-06:00 | 7.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 15.20 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 10.63 |
| Annual Sum or Average | 21664660.97 | |||
| Minimum of Months | 0.00 | 0.00 | 4.40 | |
| Maximum of Months | 18341449.22 | 373.61 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: G NW APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 42291451.92 | 373.92 | 03-JAN-04:00 | 4.00 |
| February | 5275556.61 | 103.00 | 27-FEB-08:00 | 9.00 |
| March | 55752762.37 | 422.76 | 30-MAR-04:00 | 4.40 |
| April | 6252800.44 | 253.00 | 01-APR-06:00 | 7.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 15.20 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
| November | 1533268.22 | 87.12 | 18-NOV-13:00 | 26.00 |
| December | 7565764.90 | 119.47 | 24-DEC-06:00 | 7.00 |
| Annual Sum or Average | 0.118672E+09 | |||
| Minimum of Months | 0.00 | 0.00 | 4.00 | |
| Maximum of Months | 55752762.37 | 422.76 | 26.00 |
Report: ZoneHeatingSummaryMonthly
For: OFFICE
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 32334957.80 | 363.83 | 14-JAN-11:30 | 26.00 |
| February | 25888447.28 | 314.64 | 03-FEB-09:05 | 18.50 |
| March | 22079151.63 | 316.30 | 11-MAR-11:20 | 24.00 |
| April | 57143938.01 | 378.07 | 01-APR-12:00 | 24.00 |
| May | 52029556.85 | 310.64 | 24-MAY-08:05 | 18.00 |
| June | 85401898.99 | 363.04 | 13-JUN-08:05 | 19.33 |
| July | 0.134406E+09 | 383.12 | 18-JUL-16:12 | 25.33 |
| August | 0.122572E+09 | 361.78 | 15-AUG-08:06 | 22.50 |
| September | 87823485.61 | 614.42 | 29-SEP-16:12 | 31.33 |
| October | 0.102555E+09 | 636.97 | 14-OCT-12:00 | 35.00 |
| November | 23658823.85 | 340.90 | 19-NOV-13:00 | 27.00 |
| December | 36329576.13 | 350.48 | 16-DEC-13:00 | 26.00 |
| Annual Sum or Average | 0.782223E+09 | |||
| Minimum of Months | 22079151.63 | 310.64 | 18.00 | |
| Maximum of Months | 0.134406E+09 | 636.97 | 35.00 |
Report: ZoneHeatingSummaryMonthly
For: G NE APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 39835593.67 | 380.15 | 03-JAN-04:00 | 4.00 |
| February | 6146223.10 | 340.93 | 28-FEB-18:02 | 11.00 |
| March | 57863907.47 | 998.79 | 29-MAR-16:01 | 9.83 |
| April | 5223376.48 | 218.97 | 01-APR-04:00 | 8.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 15.20 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
| November | 1395720.36 | 84.98 | 18-NOV-13:00 | 26.00 |
| December | 6854288.14 | 128.76 | 24-DEC-06:00 | 7.00 |
| Annual Sum or Average | 0.117319E+09 | |||
| Minimum of Months | 0.00 | 0.00 | 4.00 | |
| Maximum of Months | 57863907.47 | 998.79 | 26.00 |
Report: ZoneHeatingSummaryMonthly
For: G N1 APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 3590303.67 | 114.65 | 13-JAN-14:00 | 26.00 |
| February | 494925.99 | 86.97 | 01-FEB-12:00 | 26.00 |
| March | 2679277.72 | 80.41 | 30-MAR-04:00 | 4.40 |
| April | 1207894.84 | 63.35 | 01-APR-12:00 | 24.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 15.20 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
| November | 622774.20 | 72.41 | 18-NOV-12:40 | 25.67 |
| December | 2986809.76 | 110.61 | 16-DEC-13:00 | 26.00 |
| Annual Sum or Average | 11581986.18 | |||
| Minimum of Months | 0.00 | 0.00 | 4.40 | |
| Maximum of Months | 3590303.67 | 114.65 | 26.00 |
Report: ZoneHeatingSummaryMonthly
For: G N2 APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 3560781.69 | 114.40 | 13-JAN-14:00 | 26.00 |
| February | 489213.95 | 86.54 | 01-FEB-12:00 | 26.00 |
| March | 2725736.04 | 81.21 | 30-MAR-04:00 | 4.40 |
| April | 1175349.92 | 62.72 | 01-APR-12:00 | 24.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 15.20 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
| November | 625202.66 | 72.41 | 18-NOV-12:40 | 25.67 |
| December | 2899836.77 | 110.24 | 16-DEC-13:00 | 26.00 |
| Annual Sum or Average | 11476121.03 | |||
| Minimum of Months | 0.00 | 0.00 | 4.40 | |
| Maximum of Months | 3560781.69 | 114.40 | 26.00 |
Report: ZoneHeatingSummaryMonthly
For: G S1 APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 8.83 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 13.23 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 7.63 |
| April | 127992.90 | 33.04 | 01-APR-12:00 | 24.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 15.20 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 10.63 |
| Annual Sum or Average | 127992.90 | |||
| Minimum of Months | 0.00 | 0.00 | 7.63 | |
| Maximum of Months | 127992.90 | 33.04 | 24.00 |
Report: ZoneHeatingSummaryMonthly
For: G S2 APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 8.83 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 13.23 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 7.63 |
| April | 116586.03 | 31.57 | 01-APR-12:00 | 24.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 15.20 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 10.63 |
| Annual Sum or Average | 116586.03 | |||
| Minimum of Months | 0.00 | 0.00 | 7.63 | |
| Maximum of Months | 116586.03 | 31.57 | 24.00 |
Report: ZoneHeatingSummaryMonthly
For: M SW APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 8.83 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 13.23 |
| March | 4342036.87 | 254.02 | 30-MAR-04:00 | 4.40 |
| April | 14953.15 | 10.34 | 01-APR-11:40 | 23.67 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 15.20 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 10.63 |
| Annual Sum or Average | 4356990.02 | |||
| Minimum of Months | 0.00 | 0.00 | 4.40 | |
| Maximum of Months | 4342036.87 | 254.02 | 23.67 |
Report: ZoneHeatingSummaryMonthly
For: M NW APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 12818531.55 | 313.78 | 03-JAN-04:00 | 4.00 |
| February | 9431.27 | 11.45 | 01-FEB-09:50 | 23.67 |
| March | 6940124.11 | 315.67 | 30-MAR-04:00 | 4.40 |
| April | 474400.50 | 85.64 | 01-APR-06:00 | 7.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 15.20 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
| November | 57966.00 | 31.71 | 18-NOV-11:40 | 24.33 |
| December | 1269690.88 | 99.08 | 16-DEC-13:00 | 26.00 |
| Annual Sum or Average | 21570144.31 | |||
| Minimum of Months | 0.00 | 0.00 | 4.00 | |
| Maximum of Months | 12818531.55 | 315.67 | 26.00 |
Report: ZoneHeatingSummaryMonthly
For: M SE APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 8.83 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 13.23 |
| March | 5394800.77 | 315.48 | 30-MAR-04:00 | 4.40 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 15.20 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 10.63 |
| Annual Sum or Average | 5394800.77 | |||
| Minimum of Months | 0.00 | 0.00 | 4.40 | |
| Maximum of Months | 5394800.77 | 315.48 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: M NE APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 11911697.92 | 331.53 | 03-JAN-04:00 | 4.00 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 13.23 |
| March | 8197382.86 | 371.12 | 30-MAR-04:00 | 4.40 |
| April | 118418.58 | 31.76 | 01-APR-12:00 | 24.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 15.20 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 |
| December | 722980.02 | 93.45 | 16-DEC-13:00 | 26.00 |
| Annual Sum or Average | 20950479.38 | |||
| Minimum of Months | 0.00 | 0.00 | 4.00 | |
| Maximum of Months | 11911697.92 | 371.12 | 26.00 |
Report: ZoneHeatingSummaryMonthly
For: M N1 APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 1309405.06 | 98.45 | 13-JAN-14:00 | 26.00 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 13.23 |
| March | 70535.91 | 21.30 | 11-MAR-11:00 | 24.00 |
| April | 279919.03 | 43.45 | 01-APR-12:00 | 24.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 15.20 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 |
| December | 596588.94 | 92.55 | 16-DEC-13:00 | 26.00 |
| Annual Sum or Average | 2256448.93 | |||
| Minimum of Months | 0.00 | 0.00 | 13.07 | |
| Maximum of Months | 1309405.06 | 98.45 | 26.00 |
Report: ZoneHeatingSummaryMonthly
For: M N2 APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 1266906.98 | 98.03 | 13-JAN-14:00 | 26.00 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 13.23 |
| March | 51524.21 | 20.44 | 11-MAR-11:00 | 24.00 |
| April | 252308.26 | 42.55 | 01-APR-12:00 | 24.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 15.20 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 |
| December | 583328.37 | 92.03 | 16-DEC-13:00 | 26.00 |
| Annual Sum or Average | 2154067.82 | |||
| Minimum of Months | 0.00 | 0.00 | 13.07 | |
| Maximum of Months | 1266906.98 | 98.03 | 26.00 |
Report: ZoneHeatingSummaryMonthly
For: M S1 APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 8.83 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 13.23 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 7.63 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 15.20 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 10.63 |
| Annual Sum or Average | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 7.63 | |
| Maximum of Months | 0.00 | 0.00 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: M S2 APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 8.83 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 13.23 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 7.63 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 15.20 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 10.63 |
| Annual Sum or Average | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 7.63 | |
| Maximum of Months | 0.00 | 0.00 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: T SW APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.202656E+09 | 1050.36 | 08-JAN-07:00 | 1.00 |
| February | 0.151808E+09 | 683.58 | 05-FEB-06:00 | 5.00 |
| March | 0.280791E+09 | 1280.46 | 30-MAR-04:00 | 4.40 |
| April | 29728608.63 | 844.36 | 01-APR-06:00 | 7.00 |
| May | 22919597.61 | 538.33 | 13-MAY-05:00 | 10.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
| October | 3747391.24 | 280.34 | 12-OCT-05:50 | 9.00 |
| November | 78111812.19 | 707.60 | 24-NOV-04:50 | 7.83 |
| December | 0.181459E+09 | 1125.14 | 13-DEC-05:00 | 7.00 |
| Annual Sum or Average | 0.951222E+09 | |||
| Minimum of Months | 0.00 | 0.00 | 1.00 | |
| Maximum of Months | 0.280791E+09 | 1280.46 | 18.07 |
Report: ZoneHeatingSummaryMonthly
For: T NW APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.443242E+09 | 1304.36 | 08-JAN-07:00 | 1.00 |
| February | 0.294649E+09 | 844.41 | 05-FEB-06:00 | 5.00 |
| March | 0.370562E+09 | 1306.16 | 30-MAR-04:00 | 4.40 |
| April | 39315651.89 | 926.76 | 04-APR-06:01 | 11.17 |
| May | 20864895.71 | 524.35 | 13-MAY-04:50 | 10.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 |
| September | 25675.62 | 51.65 | 29-SEP-07:13 | 25.00 |
| October | 17963437.26 | 374.31 | 12-OCT-06:00 | 9.00 |
| November | 0.209812E+09 | 958.30 | 24-NOV-04:00 | 7.00 |
| December | 0.408374E+09 | 1175.67 | 13-DEC-05:00 | 7.00 |
| Annual Sum or Average | 0.180481E+10 | |||
| Minimum of Months | 0.00 | 0.00 | 1.00 | |
| Maximum of Months | 0.443242E+09 | 1306.16 | 25.00 |
Report: ZoneHeatingSummaryMonthly
For: T SE APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.195910E+09 | 1064.75 | 08-JAN-06:50 | 1.33 |
| February | 0.152090E+09 | 703.99 | 05-FEB-06:00 | 5.00 |
| March | 0.278563E+09 | 1338.49 | 30-MAR-04:00 | 4.40 |
| April | 27668727.91 | 755.07 | 01-APR-05:40 | 7.33 |
| May | 22794035.89 | 529.20 | 13-MAY-04:50 | 10.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
| October | 4367590.64 | 304.86 | 12-OCT-05:50 | 9.00 |
| November | 79448585.88 | 730.41 | 24-NOV-05:00 | 8.00 |
| December | 0.179574E+09 | 1137.29 | 13-DEC-05:00 | 7.00 |
| Annual Sum or Average | 0.940416E+09 | |||
| Minimum of Months | 0.00 | 0.00 | 1.33 | |
| Maximum of Months | 0.278563E+09 | 1338.49 | 18.07 |
Report: ZoneHeatingSummaryMonthly
For: T NE APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.414288E+09 | 1318.42 | 03-JAN-04:00 | 4.00 |
| February | 0.294085E+09 | 879.02 | 05-FEB-06:00 | 5.00 |
| March | 0.366263E+09 | 1362.10 | 30-MAR-04:00 | 4.40 |
| April | 38221063.23 | 809.18 | 01-APR-05:40 | 7.33 |
| May | 22338450.46 | 521.77 | 13-MAY-04:50 | 10.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
| October | 16061372.14 | 394.28 | 12-OCT-05:50 | 9.00 |
| November | 0.207972E+09 | 1003.56 | 24-NOV-04:00 | 7.00 |
| December | 0.386066E+09 | 1184.60 | 13-DEC-05:00 | 7.00 |
| Annual Sum or Average | 0.174529E+10 | |||
| Minimum of Months | 0.00 | 0.00 | 4.00 | |
| Maximum of Months | 0.414288E+09 | 1362.10 | 18.07 |
Report: ZoneHeatingSummaryMonthly
For: T N1 APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.191070E+09 | 769.33 | 03-JAN-04:00 | 4.00 |
| February | 82906138.32 | 419.21 | 06-FEB-05:00 | 8.00 |
| March | 0.139975E+09 | 790.60 | 30-MAR-04:00 | 4.40 |
| April | 7905049.17 | 429.90 | 01-APR-06:00 | 7.00 |
| May | 2004137.63 | 165.92 | 13-MAY-04:50 | 10.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
| October | 592419.26 | 68.02 | 31-OCT-09:50 | 25.50 |
| November | 60842893.62 | 513.06 | 24-NOV-04:00 | 7.00 |
| December | 0.159823E+09 | 664.58 | 13-DEC-05:00 | 7.00 |
| Annual Sum or Average | 0.645119E+09 | |||
| Minimum of Months | 0.00 | 0.00 | 4.00 | |
| Maximum of Months | 0.191070E+09 | 790.60 | 25.50 |
Report: ZoneHeatingSummaryMonthly
For: T N2 APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.191230E+09 | 772.04 | 03-JAN-04:00 | 4.00 |
| February | 83846485.76 | 423.13 | 06-FEB-05:00 | 8.00 |
| March | 0.141004E+09 | 795.72 | 30-MAR-04:00 | 4.40 |
| April | 7877015.37 | 428.79 | 01-APR-06:00 | 7.00 |
| May | 2045526.94 | 165.08 | 13-MAY-04:50 | 10.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
| October | 518108.15 | 55.77 | 31-OCT-09:40 | 25.00 |
| November | 61808773.25 | 517.74 | 24-NOV-04:00 | 7.00 |
| December | 0.160644E+09 | 665.42 | 13-DEC-05:00 | 7.00 |
| Annual Sum or Average | 0.648974E+09 | |||
| Minimum of Months | 0.00 | 0.00 | 4.00 | |
| Maximum of Months | 0.191230E+09 | 795.72 | 25.00 |
Report: ZoneHeatingSummaryMonthly
For: T S1 APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 47560480.05 | 491.89 | 08-JAN-06:50 | 1.33 |
| February | 18707508.44 | 256.57 | 26-FEB-06:00 | 11.00 |
| March | 88747669.88 | 763.57 | 30-MAR-04:00 | 4.40 |
| April | 5418649.78 | 376.30 | 01-APR-06:00 | 7.00 |
| May | 2480815.77 | 181.21 | 13-MAY-05:00 | 10.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
| November | 5512805.74 | 222.98 | 24-NOV-05:00 | 8.00 |
| December | 30797870.79 | 601.66 | 13-DEC-05:00 | 7.00 |
| Annual Sum or Average | 0.199226E+09 | |||
| Minimum of Months | 0.00 | 0.00 | 1.33 | |
| Maximum of Months | 88747669.88 | 763.57 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: T S2 APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 47512368.62 | 492.96 | 08-JAN-06:50 | 1.33 |
| February | 18983685.85 | 256.43 | 26-FEB-06:00 | 11.00 |
| March | 89483490.70 | 769.23 | 30-MAR-04:00 | 4.40 |
| April | 5360724.30 | 374.81 | 01-APR-06:00 | 7.00 |
| May | 2501201.80 | 180.40 | 13-MAY-05:00 | 10.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
| November | 5655321.03 | 224.36 | 24-NOV-05:00 | 8.00 |
| December | 31085292.97 | 603.10 | 13-DEC-05:00 | 7.00 |
| Annual Sum or Average | 0.200582E+09 | |||
| Minimum of Months | 0.00 | 0.00 | 1.33 | |
| Maximum of Months | 89483490.70 | 769.23 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: T CORRIDOR
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 8.83 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 13.23 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 7.63 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 15.20 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 10.63 |
| Annual Sum or Average | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 7.63 | |
| Maximum of Months | 0.00 | 0.00 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: G CORRIDOR
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 8.83 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 13.23 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 7.63 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 15.20 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 10.63 |
| Annual Sum or Average | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 7.63 | |
| Maximum of Months | 0.00 | 0.00 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: M CORRIDOR
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 8.83 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 13.23 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 7.63 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 15.20 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 10.63 |
| Annual Sum or Average | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 7.63 | |
| Maximum of Months | 0.00 | 0.00 | 18.42 |
Report: ZoneElectricSummaryMonthly
For: G SW APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: G NW APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: OFFICE
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.609777E+09 | 582.92 | 03-JAN-08:09 | 0.787690E+09 | 588.62 | 03-JAN-08:09 |
| February | 0.564682E+09 | 582.92 | 01-FEB-08:09 | 0.723971E+09 | 588.62 | 01-FEB-08:09 |
| March | 0.654405E+09 | 582.92 | 01-MAR-08:09 | 0.827804E+09 | 588.62 | 01-MAR-08:09 |
| April | 0.599704E+09 | 582.92 | 03-APR-07:10 | 0.770907E+09 | 588.62 | 03-APR-07:10 |
| May | 0.639529E+09 | 582.92 | 01-MAY-07:10 | 0.814432E+09 | 588.62 | 01-MAY-07:10 |
| June | 0.629456E+09 | 582.92 | 01-JUN-07:10 | 0.797650E+09 | 588.62 | 01-JUN-07:10 |
| July | 0.609777E+09 | 582.92 | 03-JUL-07:10 | 0.787690E+09 | 588.62 | 03-JUL-07:10 |
| August | 0.654405E+09 | 582.92 | 01-AUG-07:10 | 0.827804E+09 | 588.62 | 01-AUG-07:10 |
| September | 0.599704E+09 | 582.92 | 01-SEP-07:10 | 0.770907E+09 | 588.62 | 01-SEP-07:10 |
| October | 0.624653E+09 | 582.92 | 02-OCT-07:10 | 0.801061E+09 | 588.62 | 02-OCT-07:10 |
| November | 0.599704E+09 | 582.92 | 01-NOV-07:10 | 0.770907E+09 | 588.62 | 01-NOV-07:10 |
| December | 0.609777E+09 | 582.92 | 01-DEC-08:09 | 0.787690E+09 | 588.62 | 01-DEC-08:09 |
| Annual Sum or Average | 0.739557E+10 | 0.946851E+10 | ||||
| Minimum of Months | 0.564682E+09 | 582.92 | 0.723971E+09 | 588.62 | ||
| Maximum of Months | 0.654405E+09 | 582.92 | 0.827804E+09 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: G NE APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: G N1 APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: G N2 APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: G S1 APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: G S2 APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: M SW APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: M NW APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: M SE APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: M NE APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: M N1 APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: M N2 APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: M S1 APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: M S2 APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: T SW APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: T NW APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: T SE APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: T NE APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: T N1 APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: T N2 APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: T S1 APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: T S2 APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: T CORRIDOR
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
| January | 0.992689E+09 | 370.63 | 01-JAN-00:10 | 0.00 | 0.00 |
| February | 0.896622E+09 | 370.63 | 01-FEB-00:10 | 0.00 | 0.00 |
| March | 0.992689E+09 | 370.63 | 01-MAR-00:10 | 0.00 | 0.00 |
| April | 0.960667E+09 | 370.63 | 01-APR-00:10 | 0.00 | 0.00 |
| May | 0.992689E+09 | 370.63 | 01-MAY-00:10 | 0.00 | 0.00 |
| June | 0.960667E+09 | 370.63 | 01-JUN-00:10 | 0.00 | 0.00 |
| July | 0.992689E+09 | 370.63 | 01-JUL-00:10 | 0.00 | 0.00 |
| August | 0.992689E+09 | 370.63 | 01-AUG-00:10 | 0.00 | 0.00 |
| September | 0.960667E+09 | 370.63 | 01-SEP-00:10 | 0.00 | 0.00 |
| October | 0.992689E+09 | 370.63 | 01-OCT-00:10 | 0.00 | 0.00 |
| November | 0.960667E+09 | 370.63 | 01-NOV-00:10 | 0.00 | 0.00 |
| December | 0.992689E+09 | 370.63 | 01-DEC-00:10 | 0.00 | 0.00 |
| Annual Sum or Average | 0.116881E+11 | 0.00 | 0.00 | ||
| Minimum of Months | 0.896622E+09 | 370.63 | 0.00 | 0.00 | |
| Maximum of Months | 0.992689E+09 | 370.63 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: G CORRIDOR
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.992689E+09 | 370.63 | 01-JAN-00:10 | 0.599555E+10 | 4168.07 | 01-JAN-07:10 |
| February | 0.896622E+09 | 370.63 | 01-FEB-00:10 | 0.541534E+10 | 4168.07 | 01-FEB-07:10 |
| March | 0.992689E+09 | 370.63 | 01-MAR-00:10 | 0.599555E+10 | 4168.07 | 01-MAR-07:10 |
| April | 0.960667E+09 | 370.63 | 01-APR-00:10 | 0.580215E+10 | 4168.07 | 01-APR-06:10 |
| May | 0.992689E+09 | 370.63 | 01-MAY-00:10 | 0.599555E+10 | 4168.07 | 01-MAY-06:10 |
| June | 0.960667E+09 | 370.63 | 01-JUN-00:10 | 0.580215E+10 | 4168.07 | 01-JUN-06:10 |
| July | 0.992689E+09 | 370.63 | 01-JUL-00:10 | 0.599555E+10 | 4168.07 | 01-JUL-06:10 |
| August | 0.992689E+09 | 370.63 | 01-AUG-00:10 | 0.599555E+10 | 4168.07 | 01-AUG-06:10 |
| September | 0.960667E+09 | 370.63 | 01-SEP-00:10 | 0.580215E+10 | 4168.07 | 01-SEP-06:10 |
| October | 0.992689E+09 | 370.63 | 01-OCT-00:10 | 0.599555E+10 | 4168.07 | 01-OCT-06:10 |
| November | 0.960667E+09 | 370.63 | 01-NOV-00:10 | 0.580215E+10 | 4168.07 | 01-NOV-06:10 |
| December | 0.992689E+09 | 370.63 | 01-DEC-00:10 | 0.599555E+10 | 4168.07 | 01-DEC-07:10 |
| Annual Sum or Average | 0.116881E+11 | 0.705928E+11 | ||||
| Minimum of Months | 0.896622E+09 | 370.63 | 0.541534E+10 | 4168.07 | ||
| Maximum of Months | 0.992689E+09 | 370.63 | 0.599555E+10 | 4168.07 |
Report: ZoneElectricSummaryMonthly
For: M CORRIDOR
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
| January | 0.992689E+09 | 370.63 | 01-JAN-00:10 | 0.00 | 0.00 |
| February | 0.896622E+09 | 370.63 | 01-FEB-00:10 | 0.00 | 0.00 |
| March | 0.992689E+09 | 370.63 | 01-MAR-00:10 | 0.00 | 0.00 |
| April | 0.960667E+09 | 370.63 | 01-APR-00:10 | 0.00 | 0.00 |
| May | 0.992689E+09 | 370.63 | 01-MAY-00:10 | 0.00 | 0.00 |
| June | 0.960667E+09 | 370.63 | 01-JUN-00:10 | 0.00 | 0.00 |
| July | 0.992689E+09 | 370.63 | 01-JUL-00:10 | 0.00 | 0.00 |
| August | 0.992689E+09 | 370.63 | 01-AUG-00:10 | 0.00 | 0.00 |
| September | 0.960667E+09 | 370.63 | 01-SEP-00:10 | 0.00 | 0.00 |
| October | 0.992689E+09 | 370.63 | 01-OCT-00:10 | 0.00 | 0.00 |
| November | 0.960667E+09 | 370.63 | 01-NOV-00:10 | 0.00 | 0.00 |
| December | 0.992689E+09 | 370.63 | 01-DEC-00:10 | 0.00 | 0.00 |
| Annual Sum or Average | 0.116881E+11 | 0.00 | 0.00 | ||
| Minimum of Months | 0.896622E+09 | 370.63 | 0.00 | 0.00 | |
| Maximum of Months | 0.992689E+09 | 370.63 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: G SW APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 547532.36 | 0.220348E+09 |
| February | 0.389025E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 98367.92 | 0.261097E+09 |
| March | 0.418950E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.286853E+09 |
| April | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 691482.99 | 0.179626E+09 |
| May | 0.424935E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.202135E+09 |
| June | 0.406980E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 60692.54 | 0.120234E+09 |
| July | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4508240.27 | 73587014.32 |
| August | 0.418950E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4790530.80 | 88670272.52 |
| September | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6985676.13 | 98321551.66 |
| October | 0.430920E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18040481.36 | 0.140570E+09 |
| November | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 662300.77 | 0.219532E+09 |
| December | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 397634.15 | 0.232266E+09 |
| Annual Sum or Average | 0.505732E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 36782939.30 | 0.212324E+10 |
| Minimum of Months | 0.389025E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73587014.32 |
| Maximum of Months | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18040481.36 | 0.286853E+09 |
Report: SpaceGainsMonthly
For: G NW APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 962551.70 | 0.194409E+09 |
| February | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 169706.15 | 0.229208E+09 |
| March | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 222282.18 | 0.266721E+09 |
| April | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 975295.68 | 0.165573E+09 |
| May | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.199840E+09 |
| June | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 60692.64 | 0.120516E+09 |
| July | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4508243.05 | 73593965.79 |
| August | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4790533.74 | 88431139.17 |
| September | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6985673.60 | 97381688.23 |
| October | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18040477.84 | 0.136501E+09 |
| November | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 709492.92 | 0.192028E+09 |
| December | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1102000.24 | 0.199507E+09 |
| Annual Sum or Average | 0.512427E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 38526949.74 | 0.196371E+10 |
| Minimum of Months | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73593965.79 |
| Maximum of Months | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18040477.84 | 0.266721E+09 |
Report: SpaceGainsMonthly
For: OFFICE
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.227408E+09 | 0.609777E+09 | 0.787690E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 219488.92 | 0.230477E+09 |
| February | 0.216037E+09 | 0.564682E+09 | 0.723971E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 98372.35 | 0.279674E+09 |
| March | 0.261519E+09 | 0.654405E+09 | 0.827804E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.306564E+09 |
| April | 0.227408E+09 | 0.599704E+09 | 0.770907E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 452643.30 | 0.196556E+09 |
| May | 0.250148E+09 | 0.639529E+09 | 0.814432E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.223476E+09 |
| June | 0.250148E+09 | 0.629456E+09 | 0.797650E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 60693.96 | 0.140623E+09 |
| July | 0.227408E+09 | 0.609777E+09 | 0.787690E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3679551.87 | 0.104527E+09 |
| August | 0.261519E+09 | 0.654405E+09 | 0.827804E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3447872.51 | 0.124358E+09 |
| September | 0.227408E+09 | 0.599704E+09 | 0.770907E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4903233.13 | 0.123832E+09 |
| October | 0.238778E+09 | 0.624653E+09 | 0.801061E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12427264.38 | 0.174762E+09 |
| November | 0.227408E+09 | 0.599704E+09 | 0.770907E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 31383.32 | 0.233875E+09 |
| December | 0.227408E+09 | 0.609777E+09 | 0.787690E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 312939.25 | 0.247899E+09 |
| Annual Sum or Average | 0.284259E+10 | 0.739557E+10 | 0.946851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25633442.99 | 0.238662E+10 |
| Minimum of Months | 0.216037E+09 | 0.564682E+09 | 0.723971E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104527E+09 |
| Maximum of Months | 0.261519E+09 | 0.654405E+09 | 0.827804E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12427264.38 | 0.306564E+09 |
Report: SpaceGainsMonthly
For: G NE APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 928995.83 | 0.194925E+09 |
| February | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 134035.41 | 0.229020E+09 |
| March | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 128559.65 | 0.266902E+09 |
| April | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 827380.54 | 0.165007E+09 |
| May | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.198258E+09 |
| June | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 60692.62 | 0.119503E+09 |
| July | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4508245.84 | 73503067.90 |
| August | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4790537.28 | 88351695.26 |
| September | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6985676.82 | 96893764.54 |
| October | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18040486.28 | 0.136439E+09 |
| November | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 683544.09 | 0.191138E+09 |
| December | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 842077.44 | 0.199752E+09 |
| Annual Sum or Average | 0.512427E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 37930231.78 | 0.195969E+10 |
| Minimum of Months | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73503067.90 |
| Maximum of Months | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18040486.28 | 0.266902E+09 |
Report: SpaceGainsMonthly
For: G N1 APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 573959.87 | 0.120577E+09 |
| February | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 75830.20 | 0.143476E+09 |
| March | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 132486.55 | 0.164685E+09 |
| April | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 566035.55 | 0.102219E+09 |
| May | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124345E+09 |
| June | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36608.34 | 74099017.40 |
| July | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2719260.13 | 44477078.66 |
| August | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2889531.39 | 53513900.41 |
| September | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4213582.94 | 59213014.26 |
| October | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10881564.09 | 84351966.52 |
| November | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 403270.24 | 0.121378E+09 |
| December | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 508193.49 | 0.125283E+09 |
| Annual Sum or Average | 0.512427E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 23000322.78 | 0.121762E+10 |
| Minimum of Months | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44477078.66 |
| Maximum of Months | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10881564.09 | 0.164685E+09 |
Report: SpaceGainsMonthly
For: G N2 APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 571696.36 | 0.120660E+09 |
| February | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 74785.20 | 0.143464E+09 |
| March | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 129349.83 | 0.164748E+09 |
| April | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 559957.08 | 0.102182E+09 |
| May | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124214E+09 |
| June | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36608.34 | 74037129.88 |
| July | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2719260.16 | 44474086.84 |
| August | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2889531.43 | 53512066.70 |
| September | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4213582.98 | 59190704.46 |
| October | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10881565.32 | 84344274.54 |
| November | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 403136.33 | 0.121322E+09 |
| December | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 500686.05 | 0.125317E+09 |
| Annual Sum or Average | 0.512427E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 22980159.09 | 0.121747E+10 |
| Minimum of Months | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44474086.84 |
| Maximum of Months | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10881565.32 | 0.164748E+09 |
Report: SpaceGainsMonthly
For: G S1 APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 330260.12 | 0.138098E+09 |
| February | 0.389025E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 59333.27 | 0.168052E+09 |
| March | 0.418950E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.181434E+09 |
| April | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 404205.99 | 0.111914E+09 |
| May | 0.424935E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126026E+09 |
| June | 0.406980E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36608.28 | 73981081.64 |
| July | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2719258.49 | 44476680.72 |
| August | 0.418950E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2889529.54 | 53570932.92 |
| September | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4213584.41 | 59528458.75 |
| October | 0.430920E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10881569.16 | 86002694.21 |
| November | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 399484.76 | 0.136031E+09 |
| December | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 239843.90 | 0.146157E+09 |
| Annual Sum or Average | 0.505732E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 22173677.92 | 0.132527E+10 |
| Minimum of Months | 0.389025E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44476680.72 |
| Maximum of Months | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10881569.16 | 0.181434E+09 |
Report: SpaceGainsMonthly
For: G S2 APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 330260.05 | 0.138138E+09 |
| February | 0.389025E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 59333.20 | 0.168833E+09 |
| March | 0.418950E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.182573E+09 |
| April | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 402408.62 | 0.112452E+09 |
| May | 0.424935E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126906E+09 |
| June | 0.406980E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36608.26 | 74283403.19 |
| July | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2719258.45 | 44500402.72 |
| August | 0.418950E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2889529.66 | 53586577.01 |
| September | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4213584.73 | 59558960.38 |
| October | 0.430920E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10881571.12 | 86106813.84 |
| November | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 399484.85 | 0.136202E+09 |
| December | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 239843.87 | 0.146441E+09 |
| Annual Sum or Average | 0.505732E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 22171882.81 | 0.132958E+10 |
| Minimum of Months | 0.389025E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44500402.72 |
| Maximum of Months | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10881571.12 | 0.182573E+09 |
Report: SpaceGainsMonthly
For: M SW APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 771171.96 | 0.327356E+09 |
| February | 0.389025E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 138776.72 | 0.404374E+09 |
| March | 0.418950E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.449934E+09 |
| April | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 932052.16 | 0.275908E+09 |
| May | 0.424935E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.312550E+09 |
| June | 0.406980E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 84095.70 | 0.180248E+09 |
| July | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6407765.07 | 0.106694E+09 |
| August | 0.418950E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6794698.65 | 0.128330E+09 |
| September | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10004619.37 | 0.142386E+09 |
| October | 0.430920E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25825000.38 | 0.203465E+09 |
| November | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 939789.78 | 0.319861E+09 |
| December | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 559238.73 | 0.342755E+09 |
| Annual Sum or Average | 0.505732E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 52457208.51 | 0.319386E+10 |
| Minimum of Months | 0.389025E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106694E+09 |
| Maximum of Months | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25825000.38 | 0.449934E+09 |
Report: SpaceGainsMonthly
For: M NW APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 983139.30 | 0.295576E+09 |
| February | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 138780.50 | 0.371261E+09 |
| March | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8381.30 | 0.426032E+09 |
| April | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1013585.95 | 0.270894E+09 |
| May | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.312479E+09 |
| June | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 84095.83 | 0.180328E+09 |
| July | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6407768.12 | 0.106697E+09 |
| August | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6794701.13 | 0.128290E+09 |
| September | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10004613.67 | 0.142059E+09 |
| October | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25824988.53 | 0.200138E+09 |
| November | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 940514.65 | 0.297010E+09 |
| December | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 678844.45 | 0.308778E+09 |
| Annual Sum or Average | 0.512427E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 52879413.44 | 0.303954E+10 |
| Minimum of Months | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106697E+09 |
| Maximum of Months | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25824988.53 | 0.426032E+09 |
Report: SpaceGainsMonthly
For: M SE APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 771174.72 | 0.328562E+09 |
| February | 0.389025E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 138777.25 | 0.404255E+09 |
| March | 0.418950E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.450756E+09 |
| April | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 932052.73 | 0.276828E+09 |
| May | 0.424935E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.313075E+09 |
| June | 0.406980E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 84095.78 | 0.180243E+09 |
| July | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6407770.53 | 0.106674E+09 |
| August | 0.418950E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6794706.38 | 0.128323E+09 |
| September | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10004627.59 | 0.142319E+09 |
| October | 0.430920E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25825029.26 | 0.203672E+09 |
| November | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 939792.24 | 0.320019E+09 |
| December | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 559240.85 | 0.343273E+09 |
| Annual Sum or Average | 0.505732E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 52457267.34 | 0.319800E+10 |
| Minimum of Months | 0.389025E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106674E+09 |
| Maximum of Months | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25825029.26 | 0.450756E+09 |
Report: SpaceGainsMonthly
For: M NE APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 911713.98 | 0.297048E+09 |
| February | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 138779.59 | 0.370790E+09 |
| March | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.426585E+09 |
| April | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 944686.63 | 0.272215E+09 |
| May | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.312977E+09 |
| June | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 84095.94 | 0.180301E+09 |
| July | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6407773.38 | 0.106671E+09 |
| August | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6794707.42 | 0.128281E+09 |
| September | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10004619.44 | 0.141974E+09 |
| October | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25825003.29 | 0.200580E+09 |
| November | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 939800.11 | 0.296152E+09 |
| December | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 610357.10 | 0.309474E+09 |
| Annual Sum or Average | 0.512427E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 52661536.88 | 0.304305E+10 |
| Minimum of Months | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106671E+09 |
| Maximum of Months | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25825003.29 | 0.426585E+09 |
Report: SpaceGainsMonthly
For: M N1 APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 562383.88 | 0.184506E+09 |
| February | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 83708.48 | 0.237446E+09 |
| March | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 111.33 | 0.267880E+09 |
| April | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 594258.59 | 0.166502E+09 |
| May | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.191609E+09 |
| June | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 50724.65 | 0.109105E+09 |
| July | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3865007.44 | 64379403.09 |
| August | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4098396.87 | 77417574.41 |
| September | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6034532.80 | 85932123.77 |
| October | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15576992.22 | 0.123052E+09 |
| November | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 566864.13 | 0.187281E+09 |
| December | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 363079.73 | 0.196391E+09 |
| Annual Sum or Average | 0.512427E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 31796060.13 | 0.189150E+10 |
| Minimum of Months | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64379403.09 |
| Maximum of Months | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15576992.22 | 0.267880E+09 |
Report: SpaceGainsMonthly
For: M N2 APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 559570.63 | 0.184692E+09 |
| February | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 83708.48 | 0.237400E+09 |
| March | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.267895E+09 |
| April | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 591778.06 | 0.166556E+09 |
| May | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.191618E+09 |
| June | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 50724.65 | 0.109103E+09 |
| July | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3865007.50 | 64379148.46 |
| August | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4098396.94 | 77417190.05 |
| September | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6034532.89 | 85926909.63 |
| October | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15576992.30 | 0.123055E+09 |
| November | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 566864.12 | 0.187239E+09 |
| December | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 361848.04 | 0.196430E+09 |
| Annual Sum or Average | 0.512427E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 31789423.61 | 0.189171E+10 |
| Minimum of Months | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64379148.46 |
| Maximum of Months | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15576992.30 | 0.267895E+09 |
Report: SpaceGainsMonthly
For: M S1 APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 465154.69 | 0.203940E+09 |
| February | 0.389025E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 83707.15 | 0.254571E+09 |
| March | 0.418950E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.282387E+09 |
| April | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 562190.82 | 0.169231E+09 |
| May | 0.424935E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.191602E+09 |
| June | 0.406980E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 50724.56 | 0.109078E+09 |
| July | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3865005.27 | 64376906.10 |
| August | 0.418950E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4098394.62 | 77426411.27 |
| September | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6034535.28 | 86015888.00 |
| October | 0.430920E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15576998.44 | 0.124178E+09 |
| November | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 566860.02 | 0.196945E+09 |
| December | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 337321.19 | 0.213016E+09 |
| Annual Sum or Average | 0.505732E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 31640892.02 | 0.197277E+10 |
| Minimum of Months | 0.389025E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64376906.10 |
| Maximum of Months | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15576998.44 | 0.282387E+09 |
Report: SpaceGainsMonthly
For: M S2 APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 465154.74 | 0.204018E+09 |
| February | 0.389025E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 83707.15 | 0.254527E+09 |
| March | 0.418950E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.282403E+09 |
| April | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 562190.82 | 0.169247E+09 |
| May | 0.424935E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.191610E+09 |
| June | 0.406980E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 50724.56 | 0.109076E+09 |
| July | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3865005.33 | 64376647.61 |
| August | 0.418950E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4098394.73 | 77426266.58 |
| September | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6034535.42 | 86014532.52 |
| October | 0.430920E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15576998.89 | 0.124176E+09 |
| November | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 566860.07 | 0.196932E+09 |
| December | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 337321.23 | 0.213012E+09 |
| Annual Sum or Average | 0.505732E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 31640892.94 | 0.197282E+10 |
| Minimum of Months | 0.389025E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64376647.61 |
| Maximum of Months | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15576998.89 | 0.282403E+09 |
Report: SpaceGainsMonthly
For: T SW APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 988768.95 | 0.397981E+09 |
| February | 0.389025E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 176733.51 | 0.472944E+09 |
| March | 0.418950E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.543540E+09 |
| April | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1201489.44 | 0.332711E+09 |
| May | 0.424935E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.371651E+09 |
| June | 0.406980E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 102976.62 | 0.227023E+09 |
| July | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8288535.76 | 0.139649E+09 |
| August | 0.418950E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8750796.85 | 0.166733E+09 |
| September | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13143354.98 | 0.181302E+09 |
| October | 0.430920E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33895228.28 | 0.243227E+09 |
| November | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1211437.79 | 0.377594E+09 |
| December | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 707510.38 | 0.406250E+09 |
| Annual Sum or Average | 0.505732E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 68466832.58 | 0.386060E+10 |
| Minimum of Months | 0.389025E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139649E+09 |
| Maximum of Months | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33895228.28 | 0.543540E+09 |
Report: SpaceGainsMonthly
For: T NW APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1271555.17 | 0.362316E+09 |
| February | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 248185.76 | 0.441789E+09 |
| March | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9236.34 | 0.522398E+09 |
| April | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1201493.37 | 0.322304E+09 |
| May | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.371196E+09 |
| June | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 102976.77 | 0.227823E+09 |
| July | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8288536.93 | 0.139798E+09 |
| August | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8750793.10 | 0.165938E+09 |
| September | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13143337.34 | 0.178548E+09 |
| October | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33977802.18 | 0.233774E+09 |
| November | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1305222.86 | 0.340944E+09 |
| December | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1342087.97 | 0.370660E+09 |
| Annual Sum or Average | 0.512427E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 69641227.78 | 0.367749E+10 |
| Minimum of Months | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139798E+09 |
| Maximum of Months | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33977802.18 | 0.522398E+09 |
Report: SpaceGainsMonthly
For: T SE APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 982965.80 | 0.399859E+09 |
| February | 0.389025E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 176734.78 | 0.474892E+09 |
| March | 0.418950E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.545328E+09 |
| April | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1201491.02 | 0.335555E+09 |
| May | 0.424935E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.373327E+09 |
| June | 0.406980E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 102977.09 | 0.227121E+09 |
| July | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8288550.86 | 0.139542E+09 |
| August | 0.418950E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8750817.02 | 0.166569E+09 |
| September | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13143373.03 | 0.181275E+09 |
| October | 0.430920E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33895261.52 | 0.244325E+09 |
| November | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1211443.39 | 0.378926E+09 |
| December | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 707512.94 | 0.407887E+09 |
| Annual Sum or Average | 0.505732E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 68461127.44 | 0.387460E+10 |
| Minimum of Months | 0.389025E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139542E+09 |
| Maximum of Months | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33895261.52 | 0.545328E+09 |
Report: SpaceGainsMonthly
For: T NE APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1087818.05 | 0.362573E+09 |
| February | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 184851.07 | 0.441458E+09 |
| March | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.523525E+09 |
| April | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1201490.81 | 0.324685E+09 |
| May | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.372991E+09 |
| June | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 102977.27 | 0.228054E+09 |
| July | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8288551.38 | 0.139626E+09 |
| August | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8750809.89 | 0.165609E+09 |
| September | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13143351.32 | 0.178228E+09 |
| October | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33895195.13 | 0.234752E+09 |
| November | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1215836.44 | 0.339187E+09 |
| December | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 785354.71 | 0.370345E+09 |
| Annual Sum or Average | 0.512427E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 68656236.07 | 0.368103E+10 |
| Minimum of Months | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139626E+09 |
| Maximum of Months | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33895195.13 | 0.523525E+09 |
Report: SpaceGainsMonthly
For: T N1 APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 740130.38 | 0.220139E+09 |
| February | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 141596.13 | 0.267285E+09 |
| March | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2407.36 | 0.316794E+09 |
| April | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 724709.78 | 0.196996E+09 |
| May | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.229481E+09 |
| June | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 62113.26 | 0.140145E+09 |
| July | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4999440.73 | 85141429.82 |
| August | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5278263.47 | 0.101698E+09 |
| September | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7927730.89 | 0.109841E+09 |
| October | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20462060.65 | 0.145723E+09 |
| November | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 769628.63 | 0.206328E+09 |
| December | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 716278.16 | 0.224998E+09 |
| Annual Sum or Average | 0.512427E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 41824359.44 | 0.224457E+10 |
| Minimum of Months | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85141429.82 |
| Maximum of Months | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20462060.65 | 0.316794E+09 |
Report: SpaceGainsMonthly
For: T N2 APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 730945.58 | 0.220281E+09 |
| February | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 139494.58 | 0.267366E+09 |
| March | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 602.91 | 0.316995E+09 |
| April | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 724709.72 | 0.197126E+09 |
| May | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.229520E+09 |
| June | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 62113.27 | 0.140099E+09 |
| July | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4999441.06 | 85113889.41 |
| August | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5278263.86 | 0.101658E+09 |
| September | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7927731.28 | 0.109751E+09 |
| October | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20458724.98 | 0.145710E+09 |
| November | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 764854.34 | 0.206326E+09 |
| December | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 686430.72 | 0.225056E+09 |
| Annual Sum or Average | 0.512427E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 41773312.30 | 0.224500E+10 |
| Minimum of Months | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85113889.41 |
| Maximum of Months | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20458724.98 | 0.316995E+09 |
Report: SpaceGainsMonthly
For: T S1 APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 590300.18 | 0.246136E+09 |
| February | 0.389025E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 106602.04 | 0.292377E+09 |
| March | 0.418950E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.334365E+09 |
| April | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 724708.81 | 0.205353E+09 |
| May | 0.424935E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.229934E+09 |
| June | 0.406980E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 62113.16 | 0.139641E+09 |
| July | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4999439.65 | 85074139.87 |
| August | 0.418950E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5278265.18 | 0.102061E+09 |
| September | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7927741.77 | 0.111405E+09 |
| October | 0.430920E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20444743.83 | 0.152373E+09 |
| November | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 730711.88 | 0.234605E+09 |
| December | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 426754.85 | 0.251967E+09 |
| Annual Sum or Average | 0.505732E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 41291381.36 | 0.238529E+10 |
| Minimum of Months | 0.389025E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85074139.87 |
| Maximum of Months | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20444743.83 | 0.334365E+09 |
Report: SpaceGainsMonthly
For: T S2 APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 590299.70 | 0.246186E+09 |
| February | 0.389025E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 106602.07 | 0.292395E+09 |
| March | 0.418950E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.334442E+09 |
| April | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 724708.84 | 0.205441E+09 |
| May | 0.424935E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.229935E+09 |
| June | 0.406980E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 62113.16 | 0.139579E+09 |
| July | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4999440.01 | 85045938.89 |
| August | 0.418950E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5278265.72 | 0.102033E+09 |
| September | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7927742.26 | 0.111361E+09 |
| October | 0.430920E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20444745.60 | 0.152357E+09 |
| November | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 730712.09 | 0.234601E+09 |
| December | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 426754.97 | 0.251965E+09 |
| Annual Sum or Average | 0.505732E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 41291384.43 | 0.238534E+10 |
| Minimum of Months | 0.389025E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85045938.89 |
| Maximum of Months | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20444745.60 | 0.334442E+09 |
Report: SpaceGainsMonthly
For: T CORRIDOR
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.727675E+09 | 0.992689E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 171810.37 | 70598810.88 |
| February | 0.657255E+09 | 0.896622E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42527.75 | 85768807.81 |
| March | 0.727675E+09 | 0.992689E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4217.87 | 98942018.53 |
| April | 0.704201E+09 | 0.960667E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79688.46 | 65479508.12 |
| May | 0.727675E+09 | 0.992689E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75406817.67 |
| June | 0.704201E+09 | 0.960667E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51104998.57 |
| July | 0.727675E+09 | 0.992689E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 276583.88 | 36605033.87 |
| August | 0.727675E+09 | 0.992689E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 197634.90 | 41879403.24 |
| September | 0.704201E+09 | 0.960667E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1495229.54 | 40652934.88 |
| October | 0.727675E+09 | 0.992689E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4024418.21 | 51608392.88 |
| November | 0.704201E+09 | 0.960667E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 140873.80 | 68359628.39 |
| December | 0.727675E+09 | 0.992689E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 199272.36 | 72336096.97 |
| Annual Sum or Average | 0.856778E+10 | 0.116881E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6632257.14 | 0.758742E+09 |
| Minimum of Months | 0.657255E+09 | 0.896622E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36605033.87 |
| Maximum of Months | 0.727675E+09 | 0.992689E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4024418.21 | 98942018.53 |
Report: SpaceGainsMonthly
For: G CORRIDOR
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.727675E+09 | 0.992689E+09 | 0.299778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3487879.53 | 0.197487E+10 |
| February | 0.657255E+09 | 0.896622E+09 | 0.270767E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 382713.28 | 0.174240E+10 |
| March | 0.727675E+09 | 0.992689E+09 | 0.299778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 471342.31 | 0.194566E+10 |
| April | 0.704201E+09 | 0.960667E+09 | 0.290107E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2724803.92 | 0.153497E+10 |
| May | 0.727675E+09 | 0.992689E+09 | 0.299778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.156383E+10 |
| June | 0.704201E+09 | 0.960667E+09 | 0.290107E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123969E+10 |
| July | 0.727675E+09 | 0.992689E+09 | 0.299778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4800540.77 | 0.104949E+10 |
| August | 0.727675E+09 | 0.992689E+09 | 0.299778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3493063.90 | 0.103182E+10 |
| September | 0.704201E+09 | 0.960667E+09 | 0.290107E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 34953513.70 | 0.124715E+10 |
| October | 0.727675E+09 | 0.992689E+09 | 0.299778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 57595902.15 | 0.123497E+10 |
| November | 0.704201E+09 | 0.960667E+09 | 0.290107E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2394286.58 | 0.182015E+10 |
| December | 0.727675E+09 | 0.992689E+09 | 0.299778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1890552.36 | 0.195191E+10 |
| Annual Sum or Average | 0.856778E+10 | 0.116881E+11 | 0.352964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112195E+09 | 0.183369E+11 |
| Minimum of Months | 0.657255E+09 | 0.896622E+09 | 0.270767E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103182E+10 |
| Maximum of Months | 0.727675E+09 | 0.992689E+09 | 0.299778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 57595902.15 | 0.197487E+10 |
Report: SpaceGainsMonthly
For: M CORRIDOR
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.727675E+09 | 0.992689E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47638.60 | 63087144.14 |
| February | 0.657255E+09 | 0.896622E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3876.61 | 79360886.01 |
| March | 0.727675E+09 | 0.992689E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88349036.98 |
| April | 0.704201E+09 | 0.960667E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23004.26 | 57641045.77 |
| May | 0.727675E+09 | 0.992689E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66417893.43 |
| June | 0.704201E+09 | 0.960667E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42032272.00 |
| July | 0.727675E+09 | 0.992689E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 244199.18 | 28780442.41 |
| August | 0.727675E+09 | 0.992689E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 171968.84 | 33335170.54 |
| September | 0.704201E+09 | 0.960667E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1204737.66 | 33638648.31 |
| October | 0.727675E+09 | 0.992689E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2953313.85 | 45501189.20 |
| November | 0.704201E+09 | 0.960667E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43138.63 | 63498309.61 |
| December | 0.727675E+09 | 0.992689E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18478.97 | 66985636.13 |
| Annual Sum or Average | 0.856778E+10 | 0.116881E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4710356.59 | 0.668628E+09 |
| Minimum of Months | 0.657255E+09 | 0.896622E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28780442.41 |
| Maximum of Months | 0.727675E+09 | 0.992689E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2953313.85 | 88349036.98 |
Report: PeakSpaceGainsMonthly
For: G SW APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.57 | 14-JAN-11:00 | 310.88 | 02-JAN-03:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.00 | 01-FEB-12:00 | 329.33 | 25-FEB-13:00 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 371.38 | 28-MAR-08:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 46.33 | 26-APR-13:00 | 368.05 | 17-APR-17:00 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 304.31 | 12-MAY-16:00 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.46 | 29-JUN-11:00 | 142.53 | 06-JUN-21:00 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 76.53 | 31-JUL-13:00 | 162.91 | 20-JUL-18:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 61.65 | 17-AUG-14:00 | 98.23 | 21-AUG-18:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 187.09 | 29-SEP-14:00 | 128.37 | 25-SEP-19:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 272.44 | 16-OCT-10:30 | 233.25 | 30-OCT-03:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 46.35 | 19-NOV-13:00 | 312.88 | 23-NOV-04:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.35 | 05-DEC-10:00 | 331.43 | 12-DEC-13:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.23 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 272.44 | 371.38 |
Report: PeakSpaceGainsMonthly
For: G NW APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 36.37 | 14-JAN-11:00 | 310.88 | 02-JAN-03:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 37.52 | 01-FEB-12:00 | 316.19 | 25-FEB-13:00 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.63 | 11-MAR-13:00 | 371.38 | 28-MAR-08:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 46.33 | 26-APR-13:00 | 353.09 | 17-APR-17:00 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 304.06 | 12-MAY-16:00 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.46 | 29-JUN-11:00 | 142.71 | 06-JUN-21:00 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 76.53 | 31-JUL-13:00 | 162.91 | 20-JUL-18:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 61.65 | 17-AUG-14:00 | 98.23 | 21-AUG-18:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 187.09 | 29-SEP-14:00 | 126.33 | 25-SEP-19:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 272.44 | 16-OCT-10:30 | 218.23 | 30-OCT-03:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 46.35 | 19-NOV-13:00 | 278.86 | 23-NOV-04:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 44.90 | 04-DEC-10:00 | 291.32 | 12-DEC-13:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.23 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 272.44 | 371.38 |
Report: PeakSpaceGainsMonthly
For: OFFICE
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 451.21 | 03-JAN-08:09 | 582.92 | 03-JAN-08:09 | 588.62 | 03-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 23.54 | 13-JAN-14:00 | 308.19 | 27-JAN-05:00 |
| February | 451.21 | 01-FEB-08:09 | 582.92 | 01-FEB-08:09 | 588.62 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 31.01 | 01-FEB-12:00 | 346.83 | 25-FEB-13:00 |
| March | 451.21 | 01-MAR-08:09 | 582.92 | 01-MAR-08:09 | 588.62 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 427.31 | 28-MAR-15:00 |
| April | 451.21 | 03-APR-07:10 | 582.92 | 03-APR-07:10 | 588.62 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 46.32 | 26-APR-13:00 | 384.67 | 17-APR-17:00 |
| May | 451.21 | 01-MAY-07:10 | 582.92 | 01-MAY-07:10 | 588.62 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 361.85 | 12-MAY-16:00 |
| June | 451.21 | 01-JUN-07:10 | 582.92 | 01-JUN-07:10 | 588.62 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.46 | 29-JUN-11:00 | 159.02 | 06-JUN-17:00 |
| July | 451.21 | 03-JUL-07:10 | 582.92 | 03-JUL-07:10 | 588.62 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 76.53 | 31-JUL-13:00 | 213.05 | 20-JUL-18:00 |
| August | 451.21 | 01-AUG-07:10 | 582.92 | 01-AUG-07:10 | 588.62 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 61.65 | 17-AUG-14:00 | 130.55 | 21-AUG-17:00 |
| September | 451.21 | 01-SEP-07:10 | 582.92 | 01-SEP-07:10 | 588.62 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 187.10 | 29-SEP-14:00 | 163.54 | 02-SEP-15:00 |
| October | 451.21 | 02-OCT-07:10 | 582.92 | 02-OCT-07:10 | 588.62 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 272.44 | 16-OCT-10:30 | 251.93 | 11-OCT-02:00 |
| November | 451.21 | 01-NOV-07:10 | 582.92 | 01-NOV-07:10 | 588.62 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.90 | 28-NOV-14:00 | 327.78 | 23-NOV-04:00 |
| December | 451.21 | 01-DEC-08:09 | 582.92 | 01-DEC-08:09 | 588.62 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 27.35 | 05-DEC-10:00 | 374.75 | 12-DEC-13:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 451.21 | 582.92 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 130.55 | |||||
| Maximum of Months | 451.21 | 582.92 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 272.44 | 427.31 |
Report: PeakSpaceGainsMonthly
For: G NE APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 34.72 | 13-JAN-14:00 | 310.88 | 02-JAN-03:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 34.14 | 01-FEB-12:00 | 316.19 | 25-FEB-13:00 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.81 | 11-MAR-14:00 | 371.38 | 28-MAR-08:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 46.33 | 26-APR-13:00 | 348.53 | 17-APR-17:00 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 301.65 | 12-MAY-16:00 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.46 | 29-JUN-11:00 | 141.20 | 06-JUN-21:00 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 76.53 | 31-JUL-13:00 | 162.91 | 20-JUL-18:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 61.65 | 17-AUG-14:00 | 98.23 | 21-AUG-18:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 187.09 | 29-SEP-14:00 | 124.63 | 06-SEP-18:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 272.44 | 16-OCT-10:30 | 217.98 | 30-OCT-03:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 46.35 | 19-NOV-13:00 | 276.58 | 23-NOV-04:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 36.95 | 04-DEC-10:00 | 292.15 | 12-DEC-13:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.23 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 272.44 | 371.38 |
Report: PeakSpaceGainsMonthly
For: G N1 APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.58 | 13-JAN-14:00 | 187.52 | 02-JAN-03:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.12 | 01-FEB-12:00 | 194.52 | 25-FEB-13:00 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.15 | 11-MAR-14:00 | 228.06 | 28-MAR-15:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.95 | 26-APR-13:00 | 222.77 | 17-APR-17:00 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 195.94 | 12-MAY-16:00 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.53 | 29-JUN-11:00 | 87.52 | 06-JUN-21:00 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 46.16 | 31-JUL-13:00 | 98.27 | 20-JUL-18:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 37.18 | 17-AUG-14:00 | 59.25 | 21-AUG-18:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 112.85 | 29-SEP-14:00 | 76.30 | 25-SEP-19:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 164.33 | 16-OCT-10:30 | 137.04 | 30-OCT-03:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.96 | 19-NOV-13:00 | 179.34 | 23-NOV-04:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.36 | 04-DEC-10:00 | 191.51 | 12-DEC-13:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.25 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 164.33 | 228.06 |
Report: PeakSpaceGainsMonthly
For: G N2 APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.52 | 13-JAN-14:00 | 187.52 | 02-JAN-03:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.99 | 01-FEB-12:00 | 194.54 | 25-FEB-13:00 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.98 | 11-MAR-14:00 | 228.21 | 28-MAR-15:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.95 | 26-APR-13:00 | 222.52 | 17-APR-17:00 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 195.73 | 12-MAY-16:00 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.53 | 29-JUN-11:00 | 87.52 | 06-JUN-21:00 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 46.16 | 31-JUL-13:00 | 98.27 | 20-JUL-18:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 37.18 | 17-AUG-14:00 | 59.25 | 21-AUG-18:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 112.85 | 29-SEP-14:00 | 76.21 | 25-SEP-19:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 164.33 | 16-OCT-10:30 | 137.06 | 30-OCT-03:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.96 | 19-NOV-13:00 | 179.19 | 23-NOV-04:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.23 | 04-DEC-10:00 | 191.59 | 12-DEC-13:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.25 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 164.33 | 228.21 |
Report: PeakSpaceGainsMonthly
For: G S1 APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.21 | 14-JAN-11:00 | 191.33 | 02-JAN-03:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.70 | 01-FEB-12:00 | 215.05 | 25-FEB-13:00 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 242.48 | 28-MAR-15:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.95 | 26-APR-13:00 | 233.58 | 17-APR-17:00 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 196.58 | 12-MAY-16:00 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.53 | 29-JUN-11:00 | 87.52 | 06-JUN-21:00 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 46.16 | 31-JUL-13:00 | 98.27 | 20-JUL-18:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 37.18 | 17-AUG-14:00 | 59.25 | 21-AUG-18:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 112.85 | 29-SEP-14:00 | 77.43 | 25-SEP-19:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 164.33 | 16-OCT-10:30 | 145.89 | 30-OCT-03:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.96 | 19-NOV-13:00 | 199.58 | 23-NOV-04:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.50 | 05-DEC-10:00 | 216.01 | 12-DEC-13:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.25 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 164.33 | 242.48 |
Report: PeakSpaceGainsMonthly
For: G S2 APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.21 | 14-JAN-11:00 | 189.83 | 02-JAN-03:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.70 | 01-FEB-12:00 | 216.30 | 25-FEB-13:00 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 244.86 | 28-MAR-15:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.95 | 26-APR-13:00 | 234.74 | 17-APR-17:00 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 199.89 | 12-MAY-16:00 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.53 | 29-JUN-11:00 | 87.52 | 06-JUN-21:00 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 46.16 | 31-JUL-13:00 | 98.27 | 20-JUL-18:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 37.18 | 17-AUG-14:00 | 59.25 | 21-AUG-18:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 112.85 | 29-SEP-14:00 | 77.43 | 25-SEP-19:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 164.33 | 16-OCT-10:30 | 146.55 | 30-OCT-03:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.96 | 19-NOV-13:00 | 200.23 | 23-NOV-04:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.50 | 05-DEC-10:00 | 217.24 | 12-DEC-13:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.25 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 164.33 | 244.86 |
Report: PeakSpaceGainsMonthly
For: M SW APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 33.53 | 14-JAN-11:00 | 447.64 | 02-JAN-03:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 44.11 | 01-FEB-12:00 | 508.51 | 25-FEB-13:00 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 574.21 | 28-MAR-15:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 66.15 | 26-APR-13:00 | 568.52 | 17-APR-17:00 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 491.10 | 12-MAY-16:00 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.59 | 29-JUN-11:00 | 208.97 | 06-JUN-21:00 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 109.43 | 31-JUL-13:00 | 234.89 | 20-JUL-18:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 88.15 | 17-AUG-14:00 | 141.57 | 21-AUG-18:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 268.34 | 29-SEP-14:00 | 184.93 | 25-SEP-19:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 390.87 | 16-OCT-10:30 | 336.30 | 30-OCT-03:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 66.17 | 19-NOV-13:00 | 450.80 | 23-NOV-04:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.91 | 05-DEC-10:00 | 493.55 | 12-DEC-13:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 141.57 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 390.87 | 574.21 |
Report: PeakSpaceGainsMonthly
For: M NW APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 41.47 | 14-JAN-11:00 | 447.64 | 02-JAN-03:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 44.12 | 01-FEB-12:00 | 483.39 | 25-FEB-13:00 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.34 | 11-MAR-11:00 | 556.35 | 28-MAR-15:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 66.15 | 26-APR-13:00 | 561.55 | 17-APR-17:00 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 493.60 | 12-MAY-16:00 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.59 | 29-JUN-11:00 | 208.97 | 06-JUN-21:00 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 109.43 | 31-JUL-13:00 | 234.89 | 20-JUL-18:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 88.15 | 17-AUG-14:00 | 141.57 | 21-AUG-18:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 268.34 | 29-SEP-14:00 | 184.93 | 25-SEP-19:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 390.87 | 16-OCT-10:30 | 321.96 | 30-OCT-03:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 66.17 | 19-NOV-13:00 | 421.58 | 23-NOV-04:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 40.05 | 04-DEC-10:00 | 450.80 | 12-DEC-13:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 141.57 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 390.87 | 561.55 |
Report: PeakSpaceGainsMonthly
For: M SE APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 33.53 | 14-JAN-11:00 | 455.70 | 02-JAN-03:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 44.11 | 01-FEB-12:00 | 509.22 | 25-FEB-13:00 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 572.22 | 28-MAR-15:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 66.15 | 26-APR-13:00 | 564.91 | 17-APR-17:00 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 491.48 | 12-MAY-16:00 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.59 | 29-JUN-11:00 | 208.97 | 06-JUN-21:00 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 109.43 | 31-JUL-13:00 | 234.89 | 20-JUL-18:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 88.15 | 17-AUG-14:00 | 141.57 | 21-AUG-18:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 268.34 | 29-SEP-14:00 | 184.93 | 25-SEP-19:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 390.87 | 16-OCT-10:30 | 335.37 | 30-OCT-03:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 66.17 | 19-NOV-13:00 | 448.94 | 23-NOV-04:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.91 | 05-DEC-10:00 | 494.57 | 12-DEC-13:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 141.57 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 390.87 | 572.22 |
Report: PeakSpaceGainsMonthly
For: M NE APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 40.88 | 13-JAN-14:00 | 447.64 | 02-JAN-03:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 44.12 | 01-FEB-12:00 | 484.02 | 25-FEB-13:00 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 554.34 | 28-MAR-15:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 66.15 | 26-APR-13:00 | 558.16 | 17-APR-17:00 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 494.00 | 12-MAY-16:00 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.59 | 29-JUN-11:00 | 208.97 | 06-JUN-21:00 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 109.43 | 31-JUL-13:00 | 234.89 | 20-JUL-18:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 88.15 | 17-AUG-14:00 | 141.57 | 21-AUG-18:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 268.34 | 29-SEP-14:00 | 184.34 | 25-SEP-19:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 390.87 | 16-OCT-10:30 | 321.47 | 30-OCT-03:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 66.17 | 19-NOV-13:00 | 417.71 | 23-NOV-04:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.91 | 05-DEC-10:00 | 452.10 | 12-DEC-13:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 141.57 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 390.87 | 558.16 |
Report: PeakSpaceGainsMonthly
For: M N1 APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.50 | 13-JAN-14:00 | 271.77 | 02-JAN-03:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 26.61 | 01-FEB-12:00 | 313.55 | 25-FEB-13:00 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.19 | 11-MAR-11:00 | 367.83 | 28-MAR-15:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 39.90 | 26-APR-13:00 | 351.59 | 17-APR-17:00 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 312.53 | 12-MAY-16:00 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.83 | 29-JUN-11:00 | 126.04 | 06-JUN-21:00 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 66.01 | 31-JUL-13:00 | 141.68 | 20-JUL-18:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 53.17 | 17-AUG-14:00 | 85.39 | 21-AUG-18:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 161.85 | 29-SEP-14:00 | 111.54 | 25-SEP-19:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 235.76 | 16-OCT-10:30 | 202.15 | 30-OCT-03:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 39.91 | 19-NOV-13:00 | 272.60 | 23-NOV-04:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.47 | 05-DEC-10:00 | 296.97 | 12-DEC-13:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85.39 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 235.76 | 367.83 |
Report: PeakSpaceGainsMonthly
For: M N2 APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.36 | 13-JAN-14:00 | 272.50 | 02-JAN-03:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 26.61 | 01-FEB-12:00 | 313.57 | 25-FEB-13:00 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 368.26 | 28-MAR-15:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 39.90 | 26-APR-13:00 | 351.51 | 17-APR-17:00 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 312.66 | 12-MAY-16:00 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.83 | 29-JUN-11:00 | 126.04 | 06-JUN-21:00 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 66.01 | 31-JUL-13:00 | 141.68 | 20-JUL-18:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 53.17 | 17-AUG-14:00 | 85.39 | 21-AUG-18:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 161.85 | 29-SEP-14:00 | 111.54 | 25-SEP-19:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 235.76 | 16-OCT-10:30 | 202.16 | 30-OCT-03:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 39.91 | 19-NOV-13:00 | 272.33 | 23-NOV-04:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.47 | 05-DEC-10:00 | 297.09 | 12-DEC-13:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85.39 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 235.76 | 368.26 |
Report: PeakSpaceGainsMonthly
For: M S1 APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.22 | 14-JAN-11:00 | 301.09 | 02-JAN-03:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 26.61 | 01-FEB-12:00 | 328.00 | 25-FEB-13:00 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 379.36 | 28-MAR-15:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 39.90 | 26-APR-13:00 | 355.40 | 17-APR-17:00 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 311.01 | 12-MAY-16:00 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.83 | 29-JUN-11:00 | 126.04 | 06-JUN-21:00 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 66.01 | 31-JUL-13:00 | 141.68 | 20-JUL-18:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 53.17 | 17-AUG-14:00 | 85.39 | 21-AUG-18:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 161.85 | 29-SEP-14:00 | 111.54 | 25-SEP-19:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 235.76 | 16-OCT-10:30 | 210.20 | 30-OCT-03:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 39.91 | 19-NOV-13:00 | 288.31 | 23-NOV-04:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.47 | 05-DEC-10:00 | 319.73 | 12-DEC-13:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85.39 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 235.76 | 379.36 |
Report: PeakSpaceGainsMonthly
For: M S2 APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.22 | 14-JAN-11:00 | 302.29 | 02-JAN-03:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 26.61 | 01-FEB-12:00 | 328.03 | 25-FEB-13:00 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 379.78 | 28-MAR-15:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 39.90 | 26-APR-13:00 | 355.31 | 17-APR-17:00 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 311.14 | 12-MAY-16:00 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.83 | 29-JUN-11:00 | 126.04 | 06-JUN-21:00 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 66.01 | 31-JUL-13:00 | 141.68 | 20-JUL-18:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 53.17 | 17-AUG-14:00 | 85.39 | 21-AUG-18:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 161.85 | 29-SEP-14:00 | 111.54 | 25-SEP-19:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 235.76 | 16-OCT-10:30 | 210.18 | 30-OCT-03:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 39.91 | 19-NOV-13:00 | 288.22 | 23-NOV-04:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.47 | 05-DEC-10:00 | 319.81 | 12-DEC-13:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85.39 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 235.76 | 379.78 |
Report: PeakSpaceGainsMonthly
For: T SW APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 43.47 | 14-JAN-11:00 | 594.45 | 02-JAN-03:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 57.19 | 01-FEB-12:00 | 604.29 | 25-FEB-13:00 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 709.44 | 28-MAR-08:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 86.33 | 26-APR-13:00 | 665.29 | 17-APR-17:00 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 545.88 | 12-MAY-16:00 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.22 | 29-JUN-11:00 | 278.13 | 12-JUN-16:00 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 143.31 | 31-JUL-13:00 | 312.76 | 20-JUL-18:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 115.44 | 17-AUG-14:00 | 188.32 | 21-AUG-18:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 353.54 | 29-SEP-14:00 | 245.83 | 25-SEP-19:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 515.32 | 16-OCT-10:30 | 380.69 | 30-OCT-03:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 86.37 | 19-NOV-13:00 | 517.14 | 23-NOV-04:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 50.44 | 05-DEC-10:00 | 532.71 | 12-DEC-13:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 188.32 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 515.32 | 709.44 |
Report: PeakSpaceGainsMonthly
For: T NW APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 58.97 | 14-JAN-11:00 | 594.45 | 02-JAN-03:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 57.19 | 01-FEB-12:00 | 604.29 | 25-FEB-13:00 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.25 | 11-MAR-11:00 | 709.44 | 28-MAR-08:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 86.33 | 26-APR-13:00 | 662.15 | 17-APR-17:00 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 552.09 | 12-MAY-16:00 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.22 | 29-JUN-11:00 | 278.13 | 12-JUN-16:00 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 143.31 | 31-JUL-13:00 | 312.76 | 20-JUL-18:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 115.44 | 17-AUG-14:00 | 188.32 | 21-AUG-18:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 353.54 | 29-SEP-14:00 | 240.75 | 25-SEP-19:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 515.32 | 16-OCT-10:30 | 380.69 | 30-OCT-03:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 86.37 | 19-NOV-13:00 | 517.14 | 23-NOV-04:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 89.69 | 04-DEC-10:00 | 532.71 | 12-DEC-13:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 188.32 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 515.32 | 709.44 |
Report: PeakSpaceGainsMonthly
For: T SE APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 43.47 | 14-JAN-11:00 | 594.45 | 02-JAN-03:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 57.19 | 01-FEB-12:00 | 604.29 | 25-FEB-13:00 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 709.44 | 28-MAR-08:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 86.33 | 26-APR-13:00 | 658.94 | 17-APR-17:00 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 544.15 | 12-MAY-16:00 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.22 | 29-JUN-11:00 | 277.10 | 12-JUN-16:00 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 143.31 | 31-JUL-13:00 | 312.76 | 20-JUL-18:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 115.44 | 17-AUG-14:00 | 188.32 | 21-AUG-18:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 353.54 | 29-SEP-14:00 | 245.09 | 25-SEP-19:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 515.32 | 16-OCT-10:30 | 380.69 | 30-OCT-03:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 86.37 | 19-NOV-13:00 | 517.14 | 23-NOV-04:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 50.44 | 05-DEC-10:00 | 532.71 | 12-DEC-13:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 188.32 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 515.32 | 709.44 |
Report: PeakSpaceGainsMonthly
For: T NE APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 44.28 | 14-JAN-11:00 | 594.45 | 02-JAN-03:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 57.19 | 01-FEB-12:00 | 604.29 | 25-FEB-13:00 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 709.44 | 28-MAR-08:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 86.33 | 26-APR-13:00 | 655.14 | 17-APR-17:00 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 550.49 | 12-MAY-16:00 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.22 | 29-JUN-11:00 | 276.72 | 12-JUN-16:00 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 143.31 | 31-JUL-13:00 | 312.76 | 20-JUL-18:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 115.44 | 17-AUG-14:00 | 188.32 | 21-AUG-18:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 353.54 | 29-SEP-14:00 | 239.85 | 06-SEP-18:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 515.32 | 16-OCT-10:30 | 380.69 | 30-OCT-03:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 86.37 | 19-NOV-13:00 | 517.14 | 23-NOV-04:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 53.23 | 04-DEC-10:00 | 532.71 | 12-DEC-13:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 188.32 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 515.32 | 709.44 |
Report: PeakSpaceGainsMonthly
For: T N1 APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 34.51 | 14-JAN-11:00 | 358.56 | 02-JAN-03:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 34.49 | 01-FEB-12:00 | 364.49 | 25-FEB-13:00 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.63 | 11-MAR-11:00 | 427.92 | 28-MAR-08:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 52.07 | 26-APR-13:00 | 412.12 | 17-APR-17:00 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 347.97 | 12-MAY-16:00 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.83 | 29-JUN-11:00 | 167.76 | 12-JUN-16:00 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 86.44 | 31-JUL-13:00 | 188.65 | 20-JUL-18:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 69.63 | 17-AUG-14:00 | 113.59 | 21-AUG-18:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 213.25 | 29-SEP-14:00 | 144.73 | 06-SEP-18:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 310.83 | 16-OCT-10:30 | 229.62 | 30-OCT-03:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 52.10 | 19-NOV-13:00 | 311.93 | 23-NOV-04:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 52.94 | 04-DEC-10:00 | 321.32 | 12-DEC-13:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 113.59 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 310.83 | 427.92 |
Report: PeakSpaceGainsMonthly
For: T N2 APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 34.02 | 14-JAN-11:00 | 358.56 | 02-JAN-03:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 34.49 | 01-FEB-12:00 | 364.49 | 25-FEB-13:00 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.72 | 11-MAR-11:00 | 427.92 | 28-MAR-08:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 52.07 | 26-APR-13:00 | 412.18 | 17-APR-17:00 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 348.33 | 12-MAY-16:00 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.83 | 29-JUN-11:00 | 167.94 | 12-JUN-16:00 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 86.44 | 31-JUL-13:00 | 188.65 | 20-JUL-18:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 69.63 | 17-AUG-14:00 | 113.59 | 21-AUG-18:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 213.25 | 29-SEP-14:00 | 144.73 | 06-SEP-18:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 310.83 | 16-OCT-10:30 | 229.62 | 30-OCT-03:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 52.10 | 19-NOV-13:00 | 311.93 | 23-NOV-04:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 51.98 | 04-DEC-10:00 | 321.32 | 12-DEC-13:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 113.59 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 310.83 | 427.92 |
Report: PeakSpaceGainsMonthly
For: T S1 APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 26.22 | 14-JAN-11:00 | 358.56 | 02-JAN-03:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 34.49 | 01-FEB-12:00 | 364.63 | 25-FEB-13:00 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 427.92 | 28-MAR-08:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 52.07 | 26-APR-13:00 | 415.91 | 17-APR-17:00 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 343.22 | 12-MAY-16:00 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.83 | 29-JUN-11:00 | 167.76 | 12-JUN-16:00 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 86.44 | 31-JUL-13:00 | 188.65 | 20-JUL-18:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 69.63 | 17-AUG-14:00 | 113.59 | 21-AUG-18:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 213.25 | 29-SEP-14:00 | 148.28 | 25-SEP-19:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 310.83 | 16-OCT-10:30 | 237.63 | 11-OCT-02:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 52.10 | 19-NOV-13:00 | 311.93 | 23-NOV-04:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 30.43 | 05-DEC-10:00 | 327.07 | 12-DEC-13:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 113.59 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 310.83 | 427.92 |
Report: PeakSpaceGainsMonthly
For: T S2 APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 26.22 | 14-JAN-11:00 | 358.56 | 02-JAN-03:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 34.49 | 01-FEB-12:00 | 364.63 | 25-FEB-13:00 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 427.92 | 28-MAR-08:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 52.07 | 26-APR-13:00 | 416.07 | 17-APR-17:00 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 343.58 | 12-MAY-16:00 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.83 | 29-JUN-11:00 | 167.76 | 12-JUN-16:00 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 86.44 | 31-JUL-13:00 | 188.65 | 20-JUL-18:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 69.63 | 17-AUG-14:00 | 113.59 | 21-AUG-18:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 213.25 | 29-SEP-14:00 | 148.28 | 25-SEP-19:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 310.83 | 16-OCT-10:30 | 237.35 | 11-OCT-02:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 52.10 | 19-NOV-13:00 | 311.93 | 23-NOV-04:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 30.43 | 05-DEC-10:00 | 327.20 | 12-DEC-13:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 113.59 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 310.83 | 427.92 |
Report: PeakSpaceGainsMonthly
For: T CORRIDOR
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 397.10 | 01-JAN-00:10 | 370.63 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.52 | 14-JAN-11:00 | 103.06 | 02-JAN-03:00 |
| February | 397.10 | 01-FEB-00:10 | 370.63 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.22 | 01-FEB-12:00 | 110.67 | 25-FEB-13:00 |
| March | 397.10 | 01-MAR-00:10 | 370.63 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.52 | 11-MAR-11:00 | 124.97 | 28-MAR-15:00 |
| April | 397.10 | 01-APR-00:10 | 370.63 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.48 | 26-APR-13:00 | 130.62 | 17-APR-17:00 |
| May | 397.10 | 01-MAY-00:10 | 370.63 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 108.48 | 12-MAY-16:00 |
| June | 397.10 | 01-JUN-00:10 | 370.63 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 55.96 | 12-JUN-16:00 |
| July | 397.10 | 01-JUL-00:10 | 370.63 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.36 | 31-JUL-13:00 | 71.01 | 20-JUL-18:00 |
| August | 397.10 | 01-AUG-00:10 | 370.63 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.15 | 14-AUG-11:00 | 41.77 | 24-AUG-18:00 |
| September | 397.10 | 01-SEP-00:10 | 370.63 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.25 | 29-SEP-13:00 | 52.34 | 06-SEP-18:00 |
| October | 397.10 | 01-OCT-00:10 | 370.63 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.91 | 16-OCT-10:20 | 76.61 | 11-OCT-02:00 |
| November | 397.10 | 01-NOV-00:10 | 370.63 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.60 | 19-NOV-13:00 | 92.15 | 23-NOV-04:00 |
| December | 397.10 | 01-DEC-00:10 | 370.63 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.68 | 04-DEC-10:00 | 97.57 | 12-DEC-13:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
| Minimum of Months | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.77 | ||||
| Maximum of Months | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.91 | 130.62 |
Report: PeakSpaceGainsMonthly
For: G CORRIDOR
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 397.10 | 01-JAN-00:10 | 370.63 | 01-JAN-00:10 | 208.40 | 01-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 202.18 | 13-JAN-14:00 | 11331.92 | 08-JAN-07:01 |
| February | 397.10 | 01-FEB-00:10 | 370.63 | 01-FEB-00:10 | 208.40 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 144.01 | 01-FEB-12:00 | 8692.56 | 05-FEB-07:01 |
| March | 397.10 | 01-MAR-00:10 | 370.63 | 01-MAR-00:10 | 208.40 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 47.74 | 11-MAR-11:00 | 8564.60 | 30-MAR-06:01 |
| April | 397.10 | 01-APR-00:10 | 370.63 | 01-APR-00:10 | 208.40 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 164.11 | 26-APR-13:00 | 7440.81 | 01-APR-06:01 |
| May | 397.10 | 01-MAY-00:10 | 370.63 | 01-MAY-00:10 | 208.40 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 6663.53 | 27-MAY-06:01 |
| June | 397.10 | 01-JUN-00:10 | 370.63 | 01-JUN-00:10 | 208.40 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 5736.40 | 01-JUN-06:01 |
| July | 397.10 | 01-JUL-00:10 | 370.63 | 01-JUL-00:10 | 208.40 | 01-JUL-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 163.73 | 31-JUL-12:00 | 5270.43 | 27-JUL-06:01 |
| August | 397.10 | 01-AUG-00:10 | 370.63 | 01-AUG-00:10 | 208.40 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 155.47 | 17-AUG-14:00 | 5840.02 | 28-AUG-06:01 |
| September | 397.10 | 01-SEP-00:10 | 370.63 | 01-SEP-00:10 | 208.40 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2419.86 | 29-SEP-16:02 | 6585.13 | 20-SEP-06:01 |
| October | 397.10 | 01-OCT-00:10 | 370.63 | 01-OCT-00:10 | 208.40 | 01-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2084.33 | 14-OCT-16:03 | 8041.89 | 29-OCT-06:01 |
| November | 397.10 | 01-NOV-00:10 | 370.63 | 01-NOV-00:10 | 208.40 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 151.79 | 19-NOV-13:00 | 8904.41 | 05-NOV-06:01 |
| December | 397.10 | 01-DEC-00:10 | 370.63 | 01-DEC-00:10 | 208.40 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 190.16 | 16-DEC-13:00 | 9643.42 | 22-DEC-07:01 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 397.10 | 370.63 | 208.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5270.43 | |||||
| Maximum of Months | 397.10 | 370.63 | 208.40 | 0.00 | 0.00 | 0.00 | 0.00 | 2419.86 | 11331.92 |
Report: PeakSpaceGainsMonthly
For: M CORRIDOR
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 397.10 | 01-JAN-00:10 | 370.63 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.80 | 13-JAN-14:00 | 92.62 | 02-JAN-03:00 |
| February | 397.10 | 01-FEB-00:10 | 370.63 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.07 | 01-FEB-12:00 | 100.88 | 25-FEB-13:00 |
| March | 397.10 | 01-MAR-00:10 | 370.63 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 117.59 | 28-MAR-15:00 |
| April | 397.10 | 01-APR-00:10 | 370.63 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.43 | 26-APR-13:00 | 111.54 | 17-APR-17:00 |
| May | 397.10 | 01-MAY-00:10 | 370.63 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 99.32 | 12-MAY-16:00 |
| June | 397.10 | 01-JUN-00:10 | 370.63 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 45.37 | 12-JUN-16:00 |
| July | 397.10 | 01-JUL-00:10 | 370.63 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.81 | 31-JUL-13:00 | 53.52 | 20-JUL-18:00 |
| August | 397.10 | 01-AUG-00:10 | 370.63 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.68 | 17-AUG-14:00 | 31.45 | 24-AUG-18:00 |
| September | 397.10 | 01-SEP-00:10 | 370.63 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.03 | 29-SEP-13:20 | 39.60 | 06-SEP-18:00 |
| October | 397.10 | 01-OCT-00:10 | 370.63 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.81 | 16-OCT-11:00 | 66.21 | 30-OCT-03:00 |
| November | 397.10 | 01-NOV-00:10 | 370.63 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.38 | 19-NOV-13:00 | 90.91 | 23-NOV-04:00 |
| December | 397.10 | 01-DEC-00:10 | 370.63 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.78 | 16-DEC-13:00 | 97.17 | 12-DEC-13:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
| Minimum of Months | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.45 | ||||
| Maximum of Months | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.81 | 117.59 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: G SW APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 1237.85 | 18-JAN-14:30 | 0.00 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.95 |
| February | 1009.62 | 03-FEB-15:00 | 0.00 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.59 |
| March | 719.11 | 23-MAR-16:10 | 0.00 | 347.20 | 2354.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.06 |
| April | 965.92 | 30-APR-16:20 | 475.00 | 173.60 | 1177.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.08 |
| May | 836.97 | 03-MAY-16:05 | 0.00 | 347.20 | 2354.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.98 |
| June | 985.80 | 30-JUN-16:20 | 0.00 | 260.40 | 1765.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.11 |
| July | 1291.50 | 23-JUL-16:30 | 237.50 | 86.80 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 1433.48 | 19-AUG-16:10 | 475.00 | 173.60 | 1177.25 | 0.00 | 0.00 | 0.00 | 0.00 | 10.59 | 0.00 |
| September | 1993.65 | 30-SEP-15:10 | 237.50 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 60.51 | 0.00 |
| October | 2155.92 | 16-OCT-14:10 | 0.00 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 125.98 | 0.00 |
| November | 1500.40 | 19-NOV-13:30 | 118.75 | 17.36 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 29.12 | 0.00 |
| December | 1303.03 | 19-DEC-13:40 | 0.00 | 17.36 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 719.11 | 0.00 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 2155.92 | 475.00 | 347.20 | 2354.49 | 0.00 | 0.00 | 0.00 | 0.00 | 125.98 | 45.98 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: G NW APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 460.83 | 27-JAN-02:00 | 237.50 | 8.68 | 241.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 131.70 |
| February | 397.67 | 05-FEB-22:00 | 237.50 | 95.48 | 500.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 113.22 |
| March | 390.32 | 07-MAR-19:00 | 206.62 | 117.18 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 668.15 | 30-APR-16:30 | 123.50 | 86.80 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.81 |
| May | 689.84 | 03-MAY-16:05 | 494.00 | 347.20 | 2354.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.98 |
| June | 1023.28 | 29-JUN-17:05 | 413.25 | 234.36 | 1177.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.93 |
| July | 1243.10 | 19-JUL-16:40 | 247.00 | 173.60 | 1177.25 | 0.00 | 0.00 | 0.00 | 0.00 | 4.77 | 0.00 |
| August | 1193.83 | 19-AUG-16:30 | 123.50 | 86.80 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 5.41 | 0.00 |
| September | 1384.58 | 29-SEP-16:04 | 617.50 | 434.00 | 2943.11 | 0.00 | 0.00 | 0.00 | 0.00 | 97.30 | 0.00 |
| October | 1357.48 | 16-OCT-16:05 | 741.00 | 520.80 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 37.85 | 0.00 |
| November | 448.25 | 29-NOV-23:00 | 237.50 | 52.08 | 417.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 158.28 |
| December | 451.70 | 03-DEC-00:30 | 237.50 | 8.68 | 264.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 128.73 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 390.32 | 123.50 | 8.68 | 241.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 1384.58 | 741.00 | 520.80 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 97.30 | 158.28 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: OFFICE
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 5420.29 | 19-JAN-09:02 | 2256.03 | 2914.58 | 2943.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.98 |
| February | 5282.30 | 02-FEB-09:02 | 1804.82 | 2331.66 | 2354.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.05 |
| March | 2713.14 | 23-MAR-08:63 | 1353.62 | 1748.75 | 1765.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 5213.63 | 13-APR-08:62 | 2256.03 | 2914.58 | 2943.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.96 |
| May | 5224.91 | 02-MAY-08:62 | 2256.03 | 2914.58 | 2943.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.09 |
| June | 5104.54 | 23-JUN-08:62 | 2256.03 | 2914.58 | 2943.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.30 |
| July | 4875.37 | 10-JUL-08:62 | 1804.82 | 2331.66 | 2354.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.30 |
| August | 4917.50 | 22-AUG-08:62 | 1804.82 | 2331.66 | 2354.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.90 |
| September | 5143.20 | 20-SEP-08:62 | 1804.82 | 2331.66 | 2354.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81.98 |
| October | 5390.43 | 12-OCT-08:62 | 2256.03 | 2914.58 | 2943.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93.13 |
| November | 5546.15 | 22-NOV-09:02 | 2256.03 | 2914.58 | 2943.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.88 |
| December | 5358.10 | 07-DEC-09:02 | 2256.03 | 2914.58 | 2943.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.52 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 2713.14 | 1353.62 | 1748.75 | 1765.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 5546.15 | 2256.03 | 2914.58 | 2943.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93.13 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: G NE APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 462.51 | 27-JAN-02:00 | 237.50 | 8.68 | 241.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 132.16 |
| February | 394.71 | 05-FEB-22:00 | 237.50 | 95.48 | 500.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 112.42 |
| March | 390.31 | 20-MAR-03:00 | 237.50 | 8.68 | 223.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 517.20 | 30-APR-10:40 | 59.38 | 17.36 | 412.04 | 0.00 | 0.00 | 0.00 | 0.00 | 22.78 | 0.00 |
| May | 597.32 | 04-MAY-12:00 | 59.38 | 17.36 | 406.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 795.39 | 30-JUN-10:00 | 59.38 | 17.36 | 406.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 1040.63 | 19-JUL-10:30 | 59.38 | 17.36 | 412.04 | 0.00 | 0.00 | 0.00 | 0.00 | 47.43 | 0.00 |
| August | 992.60 | 15-AUG-10:40 | 59.38 | 17.36 | 412.04 | 0.00 | 0.00 | 0.00 | 0.00 | 35.07 | 0.00 |
| September | 1172.24 | 30-SEP-12:00 | 59.38 | 17.36 | 406.15 | 0.00 | 0.00 | 0.00 | 0.00 | 121.11 | 0.00 |
| October | 1393.29 | 16-OCT-11:00 | 59.38 | 17.36 | 412.04 | 0.00 | 0.00 | 0.00 | 0.00 | 270.48 | 0.00 |
| November | 446.72 | 29-NOV-23:00 | 237.50 | 52.08 | 417.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 157.76 |
| December | 443.12 | 21-DEC-20:00 | 206.62 | 138.88 | 547.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 390.31 | 59.38 | 8.68 | 223.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 1393.29 | 237.50 | 138.88 | 547.42 | 0.00 | 0.00 | 0.00 | 0.00 | 270.48 | 157.76 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: G N1 APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 550.69 | 28-JAN-07:00 | 237.50 | 60.76 | 317.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 140.78 |
| February | 488.43 | 04-FEB-06:00 | 237.50 | 56.42 | 253.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 165.17 |
| March | 404.13 | 20-MAR-03:00 | 237.50 | 8.68 | 223.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 411.65 | 30-APR-17:10 | 413.25 | 234.36 | 1177.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.07 |
| May | 513.53 | 04-MAY-16:03 | 494.00 | 347.20 | 2354.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.10 |
| June | 703.92 | 29-JUN-17:40 | 206.62 | 117.18 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.00 |
| July | 853.13 | 19-JUL-17:20 | 413.25 | 234.36 | 1177.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.89 |
| August | 793.56 | 17-AUG-16:05 | 494.00 | 347.20 | 2354.49 | 0.00 | 0.00 | 0.00 | 0.00 | 5.72 | 0.00 |
| September | 932.98 | 30-SEP-16:10 | 247.00 | 173.60 | 1177.25 | 0.00 | 0.00 | 0.00 | 0.00 | 14.87 | 0.00 |
| October | 975.38 | 16-OCT-12:00 | 59.38 | 17.36 | 406.15 | 0.00 | 0.00 | 0.00 | 0.00 | 150.94 | 0.00 |
| November | 463.55 | 29-NOV-23:00 | 237.50 | 52.08 | 417.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.58 |
| December | 500.21 | 03-DEC-01:00 | 237.50 | 8.68 | 264.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85.96 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 404.13 | 59.38 | 8.68 | 223.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 975.38 | 494.00 | 347.20 | 2354.49 | 0.00 | 0.00 | 0.00 | 0.00 | 150.94 | 165.17 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: G N2 APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 551.12 | 28-JAN-07:00 | 237.50 | 60.76 | 317.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 140.89 |
| February | 488.33 | 04-FEB-06:00 | 237.50 | 56.42 | 253.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 165.13 |
| March | 404.62 | 20-MAR-03:00 | 237.50 | 8.68 | 223.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 408.93 | 15-APR-22:00 | 237.50 | 52.08 | 417.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.78 |
| May | 512.37 | 04-MAY-16:10 | 494.00 | 347.20 | 2354.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.10 |
| June | 695.86 | 29-JUN-17:40 | 206.62 | 117.18 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.00 |
| July | 849.03 | 19-JUL-17:20 | 413.25 | 234.36 | 1177.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.89 |
| August | 791.10 | 17-AUG-16:05 | 494.00 | 347.20 | 2354.49 | 0.00 | 0.00 | 0.00 | 0.00 | 5.72 | 0.00 |
| September | 929.19 | 30-SEP-16:10 | 247.00 | 173.60 | 1177.25 | 0.00 | 0.00 | 0.00 | 0.00 | 14.87 | 0.00 |
| October | 980.08 | 16-OCT-12:00 | 59.38 | 17.36 | 406.15 | 0.00 | 0.00 | 0.00 | 0.00 | 150.94 | 0.00 |
| November | 463.47 | 29-NOV-23:00 | 237.50 | 52.08 | 417.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.56 |
| December | 500.17 | 03-DEC-01:00 | 237.50 | 8.68 | 264.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85.95 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 404.62 | 59.38 | 8.68 | 223.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 980.08 | 494.00 | 347.20 | 2354.49 | 0.00 | 0.00 | 0.00 | 0.00 | 150.94 | 165.13 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: G S1 APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 1191.26 | 18-JAN-14:00 | 0.00 | 17.36 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 4.97 | 0.00 |
| February | 1026.26 | 01-FEB-13:00 | 0.00 | 17.36 | 406.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 599.44 | 11-MAR-13:50 | 118.75 | 17.36 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 751.99 | 30-APR-13:30 | 118.75 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 667.80 | 04-MAY-12:00 | 0.00 | 17.36 | 406.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 669.31 | 30-JUN-16:10 | 0.00 | 260.40 | 1765.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.76 |
| July | 917.47 | 23-JUL-16:10 | 475.00 | 173.60 | 1177.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 1031.78 | 19-AUG-16:05 | 475.00 | 173.60 | 1177.25 | 0.00 | 0.00 | 0.00 | 0.00 | 6.39 | 0.00 |
| September | 1564.67 | 30-SEP-13:30 | 118.75 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 55.18 | 0.00 |
| October | 1832.15 | 16-OCT-12:30 | 0.00 | 17.36 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 132.08 | 0.00 |
| November | 1474.89 | 19-NOV-13:00 | 118.75 | 17.36 | 406.15 | 0.00 | 0.00 | 0.00 | 0.00 | 27.96 | 0.00 |
| December | 1362.85 | 19-DEC-13:00 | 0.00 | 17.36 | 406.15 | 0.00 | 0.00 | 0.00 | 0.00 | 16.46 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 599.44 | 0.00 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 1832.15 | 475.00 | 260.40 | 1765.87 | 0.00 | 0.00 | 0.00 | 0.00 | 132.08 | 11.76 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: G S2 APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 1227.20 | 18-JAN-14:00 | 0.00 | 17.36 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 4.97 | 0.00 |
| February | 1055.24 | 01-FEB-13:00 | 0.00 | 17.36 | 406.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 634.36 | 23-MAR-14:10 | 0.00 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.04 |
| April | 792.04 | 30-APR-13:30 | 118.75 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 704.15 | 04-MAY-12:00 | 0.00 | 17.36 | 406.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 698.93 | 30-JUN-16:03 | 0.00 | 260.40 | 1765.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.76 |
| July | 983.90 | 23-JUL-16:05 | 475.00 | 173.60 | 1177.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 1100.96 | 19-AUG-16:10 | 475.00 | 173.60 | 1177.25 | 0.00 | 0.00 | 0.00 | 0.00 | 6.39 | 0.00 |
| September | 1666.61 | 30-SEP-13:40 | 118.75 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 55.18 | 0.00 |
| October | 1922.65 | 16-OCT-12:00 | 0.00 | 17.36 | 406.15 | 0.00 | 0.00 | 0.00 | 0.00 | 150.94 | 0.00 |
| November | 1533.08 | 19-NOV-13:00 | 118.75 | 17.36 | 406.15 | 0.00 | 0.00 | 0.00 | 0.00 | 27.96 | 0.00 |
| December | 1398.46 | 19-DEC-13:00 | 0.00 | 17.36 | 406.15 | 0.00 | 0.00 | 0.00 | 0.00 | 16.46 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 634.36 | 0.00 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 1922.65 | 475.00 | 260.40 | 1765.87 | 0.00 | 0.00 | 0.00 | 0.00 | 150.94 | 11.76 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: M SW APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 1936.97 | 18-JAN-14:30 | 0.00 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.66 |
| February | 1695.73 | 03-FEB-15:00 | 0.00 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.78 |
| March | 1542.96 | 23-MAR-15:30 | 0.00 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.06 |
| April | 1680.22 | 26-APR-16:03 | 0.00 | 260.40 | 1765.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.48 |
| May | 1375.72 | 03-MAY-16:05 | 0.00 | 347.20 | 2354.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.49 |
| June | 1507.82 | 29-JUN-16:30 | 0.00 | 173.60 | 1177.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.15 |
| July | 1763.56 | 23-JUL-16:30 | 237.50 | 86.80 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.34 |
| August | 1905.67 | 19-AUG-16:10 | 475.00 | 173.60 | 1177.25 | 0.00 | 0.00 | 0.00 | 0.00 | 14.85 | 0.00 |
| September | 2535.08 | 29-SEP-15:10 | 0.00 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 206.77 | 0.00 |
| October | 2690.44 | 15-OCT-15:10 | 237.50 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 143.28 | 0.00 |
| November | 2128.74 | 19-NOV-13:30 | 118.75 | 17.36 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 41.43 | 0.00 |
| December | 1965.13 | 19-DEC-13:40 | 0.00 | 17.36 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.43 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 1375.72 | 0.00 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 2690.44 | 475.00 | 347.20 | 2354.49 | 0.00 | 0.00 | 0.00 | 0.00 | 206.77 | 66.49 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: M NW APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 769.59 | 18-JAN-14:50 | 59.38 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.63 |
| February | 529.63 | 03-FEB-18:20 | 826.50 | 468.73 | 2354.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 101.43 |
| March | 953.06 | 23-MAR-16:05 | 494.00 | 347.20 | 2354.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.70 |
| April | 1403.99 | 26-APR-16:20 | 370.50 | 260.40 | 1765.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.47 |
| May | 1264.94 | 03-MAY-16:10 | 494.00 | 347.20 | 2354.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.49 |
| June | 1561.02 | 29-JUN-17:10 | 413.25 | 234.36 | 1177.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.82 |
| July | 1706.71 | 19-JUL-16:40 | 247.00 | 173.60 | 1177.25 | 0.00 | 0.00 | 0.00 | 0.00 | 6.45 | 0.00 |
| August | 1618.64 | 19-AUG-16:30 | 123.50 | 86.80 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 7.47 | 0.00 |
| September | 1870.96 | 29-SEP-16:08 | 617.50 | 434.00 | 2943.11 | 0.00 | 0.00 | 0.00 | 0.00 | 139.46 | 0.00 |
| October | 1718.90 | 15-OCT-16:10 | 247.00 | 173.60 | 1177.25 | 0.00 | 0.00 | 0.00 | 0.00 | 88.77 | 0.00 |
| November | 653.61 | 19-NOV-14:00 | 59.38 | 17.36 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 19.24 | 0.00 |
| December | 710.53 | 05-DEC-15:30 | 59.38 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.34 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 529.63 | 59.38 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 1870.96 | 826.50 | 468.73 | 2943.11 | 0.00 | 0.00 | 0.00 | 0.00 | 139.46 | 101.43 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: M SE APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 1751.84 | 18-JAN-13:50 | 0.00 | 17.36 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 15.67 | 0.00 |
| February | 1631.53 | 01-FEB-12:40 | 0.00 | 17.36 | 406.15 | 0.00 | 0.00 | 0.00 | 0.00 | 18.23 | 0.00 |
| March | 1429.39 | 11-MAR-13:00 | 118.75 | 17.36 | 406.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 |
| April | 1588.50 | 26-APR-13:00 | 0.00 | 17.36 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 66.15 | 0.00 |
| May | 1305.38 | 04-MAY-12:00 | 0.00 | 17.36 | 406.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.45 |
| June | 1238.72 | 30-JUN-10:00 | 0.00 | 17.36 | 406.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.39 |
| July | 1542.11 | 23-JUL-11:00 | 118.75 | 17.36 | 412.04 | 0.00 | 0.00 | 0.00 | 0.00 | 61.56 | 0.00 |
| August | 1654.90 | 19-AUG-13:00 | 118.75 | 17.36 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 74.28 | 0.00 |
| September | 2421.46 | 29-SEP-13:00 | 0.00 | 17.36 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 257.51 | 0.00 |
| October | 2729.86 | 16-OCT-12:00 | 0.00 | 17.36 | 406.15 | 0.00 | 0.00 | 0.00 | 0.00 | 359.02 | 0.00 |
| November | 2139.13 | 19-NOV-13:00 | 118.75 | 17.36 | 406.15 | 0.00 | 0.00 | 0.00 | 0.00 | 66.17 | 0.00 |
| December | 1957.38 | 19-DEC-13:00 | 0.00 | 17.36 | 406.15 | 0.00 | 0.00 | 0.00 | 0.00 | 38.82 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 1238.72 | 0.00 | 17.36 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 2729.86 | 118.75 | 17.36 | 412.04 | 0.00 | 0.00 | 0.00 | 0.00 | 359.02 | 0.50 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: M NE APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 638.67 | 18-JAN-13:00 | 59.38 | 17.36 | 406.15 | 0.00 | 0.00 | 0.00 | 0.00 | 33.49 | 0.00 |
| February | 495.94 | 04-FEB-06:00 | 237.50 | 56.42 | 253.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 399.90 |
| March | 651.10 | 23-MAR-10:00 | 59.38 | 17.36 | 406.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.43 |
| April | 1151.05 | 26-APR-11:00 | 59.38 | 17.36 | 412.04 | 0.00 | 0.00 | 0.00 | 0.00 | 44.16 | 0.00 |
| May | 1082.92 | 04-MAY-12:00 | 59.38 | 17.36 | 406.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.45 |
| June | 1261.83 | 30-JUN-10:00 | 59.38 | 17.36 | 406.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.39 |
| July | 1439.80 | 19-JUL-10:10 | 59.38 | 17.36 | 412.04 | 0.00 | 0.00 | 0.00 | 0.00 | 61.35 | 0.00 |
| August | 1353.84 | 14-AUG-10:20 | 59.38 | 17.36 | 412.04 | 0.00 | 0.00 | 0.00 | 0.00 | 60.99 | 0.00 |
| September | 1601.32 | 29-SEP-13:00 | 59.38 | 17.36 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 257.51 | 0.00 |
| October | 1752.04 | 16-OCT-10:50 | 59.38 | 17.36 | 412.04 | 0.00 | 0.00 | 0.00 | 0.00 | 389.61 | 0.00 |
| November | 636.30 | 19-NOV-13:00 | 59.38 | 17.36 | 406.15 | 0.00 | 0.00 | 0.00 | 0.00 | 66.17 | 0.00 |
| December | 530.52 | 05-DEC-15:10 | 59.38 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 13.33 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 495.94 | 59.38 | 17.36 | 253.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 1752.04 | 237.50 | 56.42 | 412.04 | 0.00 | 0.00 | 0.00 | 0.00 | 389.61 | 399.90 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: M N1 APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 599.93 | 18-JAN-13:00 | 59.38 | 17.36 | 406.15 | 0.00 | 0.00 | 0.00 | 0.00 | 20.20 | 0.00 |
| February | 525.16 | 03-FEB-18:17 | 826.50 | 468.73 | 2354.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.18 |
| March | 599.62 | 24-MAR-17:06 | 1033.12 | 585.91 | 2943.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 149.87 |
| April | 832.65 | 26-APR-17:00 | 123.50 | 86.80 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.78 |
| May | 816.80 | 04-MAY-16:03 | 494.00 | 347.20 | 2354.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.73 |
| June | 1011.14 | 29-JUN-17:30 | 206.62 | 117.18 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.36 |
| July | 1109.50 | 18-JUL-17:50 | 206.62 | 117.18 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.23 |
| August | 1007.28 | 17-AUG-16:10 | 494.00 | 347.20 | 2354.49 | 0.00 | 0.00 | 0.00 | 0.00 | 7.99 | 0.00 |
| September | 1173.99 | 29-SEP-16:04 | 617.50 | 434.00 | 2943.11 | 0.00 | 0.00 | 0.00 | 0.00 | 84.12 | 0.00 |
| October | 1171.39 | 16-OCT-12:00 | 59.38 | 17.36 | 406.15 | 0.00 | 0.00 | 0.00 | 0.00 | 216.55 | 0.00 |
| November | 568.57 | 11-NOV-19:20 | 206.62 | 138.88 | 547.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 609.35 | 19-DEC-18:15 | 826.50 | 468.73 | 2354.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 525.16 | 59.38 | 17.36 | 406.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 1173.99 | 1033.12 | 585.91 | 2943.11 | 0.00 | 0.00 | 0.00 | 0.00 | 216.55 | 149.87 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: M N2 APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 603.43 | 18-JAN-13:00 | 59.38 | 17.36 | 406.15 | 0.00 | 0.00 | 0.00 | 0.00 | 20.20 | 0.00 |
| February | 521.99 | 04-FEB-06:00 | 237.50 | 56.42 | 253.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 253.29 |
| March | 613.09 | 24-MAR-17:06 | 1033.12 | 585.91 | 2943.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 149.87 |
| April | 826.89 | 26-APR-17:00 | 123.50 | 86.80 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.78 |
| May | 816.96 | 04-MAY-16:03 | 494.00 | 347.20 | 2354.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.73 |
| June | 1002.88 | 29-JUN-17:30 | 206.62 | 117.18 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.36 |
| July | 1103.89 | 18-JUL-17:50 | 206.62 | 117.18 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.23 |
| August | 1003.76 | 17-AUG-16:10 | 494.00 | 347.20 | 2354.49 | 0.00 | 0.00 | 0.00 | 0.00 | 7.99 | 0.00 |
| September | 1169.57 | 29-SEP-16:04 | 617.50 | 434.00 | 2943.11 | 0.00 | 0.00 | 0.00 | 0.00 | 84.12 | 0.00 |
| October | 1177.47 | 16-OCT-12:00 | 59.38 | 17.36 | 406.15 | 0.00 | 0.00 | 0.00 | 0.00 | 216.55 | 0.00 |
| November | 561.86 | 11-NOV-19:20 | 206.62 | 138.88 | 547.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 612.51 | 19-DEC-18:15 | 826.50 | 468.73 | 2354.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 521.99 | 59.38 | 17.36 | 253.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 1177.47 | 1033.12 | 585.91 | 2943.11 | 0.00 | 0.00 | 0.00 | 0.00 | 216.55 | 253.29 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: M S1 APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 1712.46 | 18-JAN-14:00 | 0.00 | 17.36 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 6.90 | 0.00 |
| February | 1543.47 | 01-FEB-13:00 | 0.00 | 17.36 | 406.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.38 |
| March | 1334.33 | 11-MAR-13:50 | 118.75 | 17.36 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 |
| April | 1249.77 | 26-APR-13:00 | 0.00 | 17.36 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 39.90 | 0.00 |
| May | 1005.01 | 03-MAY-13:00 | 0.00 | 17.36 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.27 |
| June | 943.69 | 29-JUN-17:15 | 475.00 | 234.36 | 1177.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.90 |
| July | 1166.87 | 23-JUL-16:05 | 475.00 | 173.60 | 1177.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.23 |
| August | 1299.01 | 30-AUG-13:00 | 0.00 | 17.36 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.30 |
| September | 1923.51 | 29-SEP-13:30 | 0.00 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 160.17 | 0.00 |
| October | 2173.98 | 16-OCT-12:00 | 0.00 | 17.36 | 406.15 | 0.00 | 0.00 | 0.00 | 0.00 | 216.55 | 0.00 |
| November | 1978.63 | 19-NOV-13:00 | 118.75 | 17.36 | 406.15 | 0.00 | 0.00 | 0.00 | 0.00 | 39.91 | 0.00 |
| December | 1869.55 | 19-DEC-13:00 | 0.00 | 17.36 | 406.15 | 0.00 | 0.00 | 0.00 | 0.00 | 23.42 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 943.69 | 0.00 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 2173.98 | 475.00 | 234.36 | 1177.25 | 0.00 | 0.00 | 0.00 | 0.00 | 216.55 | 13.90 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: M S2 APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 1713.64 | 18-JAN-14:00 | 0.00 | 17.36 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 6.90 | 0.00 |
| February | 1546.19 | 01-FEB-13:00 | 0.00 | 17.36 | 406.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.38 |
| March | 1340.57 | 11-MAR-13:50 | 118.75 | 17.36 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 |
| April | 1256.10 | 26-APR-13:00 | 0.00 | 17.36 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 39.90 | 0.00 |
| May | 1009.21 | 03-MAY-13:00 | 0.00 | 17.36 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.27 |
| June | 935.66 | 29-JUN-17:15 | 475.00 | 234.36 | 1177.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.90 |
| July | 1164.33 | 23-JUL-16:05 | 475.00 | 173.60 | 1177.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.23 |
| August | 1303.69 | 30-AUG-13:00 | 0.00 | 17.36 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.30 |
| September | 1926.81 | 29-SEP-13:30 | 0.00 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 160.17 | 0.00 |
| October | 2180.19 | 16-OCT-12:00 | 0.00 | 17.36 | 406.15 | 0.00 | 0.00 | 0.00 | 0.00 | 216.55 | 0.00 |
| November | 1982.58 | 19-NOV-13:00 | 118.75 | 17.36 | 406.15 | 0.00 | 0.00 | 0.00 | 0.00 | 39.91 | 0.00 |
| December | 1872.81 | 19-DEC-13:00 | 0.00 | 17.36 | 406.15 | 0.00 | 0.00 | 0.00 | 0.00 | 23.42 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 935.66 | 0.00 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 2180.19 | 475.00 | 234.36 | 1177.25 | 0.00 | 0.00 | 0.00 | 0.00 | 216.55 | 13.90 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: T SW APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 2393.26 | 18-JAN-14:30 | 0.00 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.27 |
| February | 1810.53 | 03-FEB-15:00 | 0.00 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.43 |
| March | 2044.81 | 11-MAR-15:10 | 0.00 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.72 |
| April | 2188.90 | 26-APR-14:30 | 0.00 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 12.25 | 0.00 |
| May | 1836.86 | 03-MAY-15:10 | 0.00 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.57 |
| June | 1979.19 | 30-JUN-16:07 | 0.00 | 260.40 | 1765.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.61 |
| July | 2324.48 | 23-JUL-16:20 | 475.00 | 173.60 | 1177.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.41 |
| August | 2537.54 | 19-AUG-16:10 | 475.00 | 173.60 | 1177.25 | 0.00 | 0.00 | 0.00 | 0.00 | 18.69 | 0.00 |
| September | 3535.84 | 29-SEP-14:10 | 0.00 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 342.12 | 0.00 |
| October | 3608.48 | 16-OCT-13:40 | 0.00 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 289.31 | 0.00 |
| November | 2621.47 | 19-NOV-13:30 | 118.75 | 17.36 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 53.71 | 0.00 |
| December | 2282.57 | 19-DEC-13:40 | 0.00 | 17.36 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.70 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 1810.53 | 0.00 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 3608.48 | 475.00 | 260.40 | 1765.87 | 0.00 | 0.00 | 0.00 | 0.00 | 342.12 | 58.57 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: T NW APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 810.26 | 18-JAN-15:10 | 59.38 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.69 |
| February | 459.97 | 03-FEB-15:20 | 59.38 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.66 |
| March | 1157.06 | 23-MAR-16:05 | 494.00 | 347.20 | 2354.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85.26 |
| April | 1755.50 | 26-APR-16:13 | 370.50 | 260.40 | 1765.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.50 |
| May | 1643.16 | 03-MAY-16:05 | 494.00 | 347.20 | 2354.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89.05 |
| June | 1978.50 | 29-JUN-16:40 | 123.50 | 86.80 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.69 |
| July | 2279.53 | 19-JUL-16:30 | 247.00 | 173.60 | 1177.25 | 0.00 | 0.00 | 0.00 | 0.00 | 12.24 | 0.00 |
| August | 2169.82 | 17-AUG-16:05 | 494.00 | 347.20 | 2354.49 | 0.00 | 0.00 | 0.00 | 0.00 | 16.53 | 0.00 |
| September | 2617.16 | 29-SEP-15:30 | 71.25 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 242.50 | 0.00 |
| October | 2338.88 | 16-OCT-15:10 | 71.25 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 140.55 | 0.00 |
| November | 816.74 | 19-NOV-14:00 | 59.38 | 17.36 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 24.42 | 0.00 |
| December | 912.16 | 05-DEC-15:30 | 59.38 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.34 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 459.97 | 59.38 | 17.36 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 2617.16 | 494.00 | 347.20 | 2354.49 | 0.00 | 0.00 | 0.00 | 0.00 | 242.50 | 89.05 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: T SE APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 2138.30 | 18-JAN-14:00 | 0.00 | 17.36 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 14.11 | 0.00 |
| February | 1797.15 | 01-FEB-13:00 | 0.00 | 17.36 | 406.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.46 |
| March | 1977.04 | 11-MAR-13:40 | 118.75 | 17.36 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.13 |
| April | 2103.66 | 26-APR-13:00 | 0.00 | 17.36 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 86.33 | 0.00 |
| May | 1756.65 | 04-MAY-12:00 | 0.00 | 17.36 | 406.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.77 |
| June | 1710.57 | 30-JUN-12:00 | 0.00 | 17.36 | 406.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.20 |
| July | 2097.76 | 31-JUL-13:00 | 0.00 | 17.36 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 143.31 | 0.00 |
| August | 2293.74 | 19-AUG-13:00 | 118.75 | 17.36 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 96.95 | 0.00 |
| September | 3438.80 | 29-SEP-13:00 | 0.00 | 17.36 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 339.51 | 0.00 |
| October | 3710.78 | 16-OCT-12:00 | 0.00 | 17.36 | 406.15 | 0.00 | 0.00 | 0.00 | 0.00 | 473.33 | 0.00 |
| November | 2623.55 | 19-NOV-13:00 | 118.75 | 17.36 | 406.15 | 0.00 | 0.00 | 0.00 | 0.00 | 86.37 | 0.00 |
| December | 2264.55 | 19-DEC-13:00 | 0.00 | 17.36 | 406.15 | 0.00 | 0.00 | 0.00 | 0.00 | 50.33 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 1710.57 | 0.00 | 17.36 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 3710.78 | 118.75 | 17.36 | 406.15 | 0.00 | 0.00 | 0.00 | 0.00 | 473.33 | 2.46 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: T NE APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 601.35 | 18-JAN-13:50 | 59.38 | 17.36 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 19.72 | 0.00 |
| February | 450.78 | 01-FEB-12:40 | 59.38 | 17.36 | 406.15 | 0.00 | 0.00 | 0.00 | 0.00 | 22.63 | 0.00 |
| March | 696.48 | 23-MAR-14:10 | 59.38 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.56 |
| April | 1452.66 | 26-APR-13:00 | 59.38 | 17.36 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 86.33 | 0.00 |
| May | 1445.23 | 04-MAY-12:00 | 59.38 | 17.36 | 406.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.77 |
| June | 1625.64 | 30-JUN-10:10 | 59.38 | 17.36 | 412.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.04 |
| July | 1931.44 | 19-JUL-12:00 | 59.38 | 17.36 | 406.15 | 0.00 | 0.00 | 0.00 | 0.00 | 129.52 | 0.00 |
| August | 1793.51 | 14-AUG-11:00 | 59.38 | 17.36 | 412.04 | 0.00 | 0.00 | 0.00 | 0.00 | 101.37 | 0.00 |
| September | 2324.13 | 29-SEP-13:00 | 59.38 | 17.36 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 339.50 | 0.00 |
| October | 2396.88 | 16-OCT-12:00 | 59.38 | 17.36 | 406.15 | 0.00 | 0.00 | 0.00 | 0.00 | 473.33 | 0.00 |
| November | 792.71 | 19-NOV-13:00 | 59.38 | 17.36 | 406.15 | 0.00 | 0.00 | 0.00 | 0.00 | 86.37 | 0.00 |
| December | 645.14 | 05-DEC-15:00 | 59.38 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 27.88 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 450.78 | 59.38 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 2396.88 | 59.38 | 30.38 | 412.04 | 0.00 | 0.00 | 0.00 | 0.00 | 473.33 | 36.56 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: T N1 APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 490.79 | 18-JAN-14:20 | 59.38 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.12 | 0.00 |
| February | 385.90 | 21-FEB-21:00 | 206.62 | 138.88 | 523.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 155.97 |
| March | 486.72 | 23-MAR-16:05 | 494.00 | 347.20 | 2354.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.42 |
| April | 1056.07 | 26-APR-14:10 | 59.38 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 23.03 | 0.00 |
| May | 1087.06 | 03-MAY-13:00 | 59.38 | 17.36 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.07 |
| June | 1239.75 | 29-JUN-17:20 | 413.25 | 234.36 | 1177.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.92 |
| July | 1445.08 | 19-JUL-16:15 | 494.00 | 347.20 | 2354.49 | 0.00 | 0.00 | 0.00 | 0.00 | 10.40 | 0.00 |
| August | 1367.08 | 17-AUG-15:10 | 71.25 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 39.32 | 0.00 |
| September | 1709.32 | 29-SEP-14:10 | 59.38 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 206.36 | 0.00 |
| October | 1668.90 | 16-OCT-12:30 | 59.38 | 17.36 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 249.72 | 0.00 |
| November | 523.24 | 19-NOV-13:50 | 59.38 | 17.36 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 20.39 | 0.00 |
| December | 494.45 | 05-DEC-15:10 | 59.38 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 9.99 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 385.90 | 59.38 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 1709.32 | 494.00 | 347.20 | 2354.49 | 0.00 | 0.00 | 0.00 | 0.00 | 249.72 | 155.97 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: T N2 APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 494.67 | 18-JAN-14:20 | 59.38 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.12 | 0.00 |
| February | 385.21 | 03-FEB-22:00 | 237.50 | 95.48 | 500.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 187.17 |
| March | 483.72 | 23-MAR-16:05 | 494.00 | 347.20 | 2354.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.42 |
| April | 1063.77 | 26-APR-14:10 | 59.38 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 23.03 | 0.00 |
| May | 1097.58 | 03-MAY-13:00 | 59.38 | 17.36 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.07 |
| June | 1221.96 | 29-JUN-17:20 | 413.25 | 234.36 | 1177.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.92 |
| July | 1434.43 | 19-JUL-16:15 | 494.00 | 347.20 | 2354.49 | 0.00 | 0.00 | 0.00 | 0.00 | 10.40 | 0.00 |
| August | 1363.32 | 17-AUG-15:10 | 71.25 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 39.32 | 0.00 |
| September | 1710.79 | 29-SEP-14:10 | 59.38 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 206.36 | 0.00 |
| October | 1682.10 | 16-OCT-12:00 | 59.38 | 17.36 | 406.15 | 0.00 | 0.00 | 0.00 | 0.00 | 285.50 | 0.00 |
| November | 530.71 | 19-NOV-13:50 | 59.38 | 17.36 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 20.39 | 0.00 |
| December | 496.43 | 05-DEC-15:10 | 59.38 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 9.99 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 385.21 | 59.38 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 1710.79 | 494.00 | 347.20 | 2354.49 | 0.00 | 0.00 | 0.00 | 0.00 | 285.50 | 187.17 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: T S1 APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 2049.25 | 18-JAN-14:10 | 0.00 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 4.41 | 0.00 |
| February | 1607.94 | 01-FEB-13:00 | 0.00 | 17.36 | 406.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.48 |
| March | 1701.63 | 11-MAR-13:50 | 118.75 | 17.36 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.31 |
| April | 1678.87 | 26-APR-13:40 | 0.00 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 37.08 | 0.00 |
| May | 1429.27 | 03-MAY-13:00 | 0.00 | 17.36 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.07 |
| June | 1324.70 | 27-JUN-13:00 | 0.00 | 17.36 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.07 |
| July | 1660.87 | 31-JUL-13:00 | 0.00 | 17.36 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 86.44 | 0.00 |
| August | 1869.95 | 19-AUG-13:40 | 118.75 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 58.48 | 0.00 |
| September | 2800.63 | 29-SEP-13:30 | 0.00 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 211.10 | 0.00 |
| October | 3006.86 | 16-OCT-12:40 | 0.00 | 17.36 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 238.28 | 0.00 |
| November | 2374.04 | 19-NOV-13:00 | 118.75 | 17.36 | 406.15 | 0.00 | 0.00 | 0.00 | 0.00 | 52.10 | 0.00 |
| December | 2120.50 | 19-DEC-13:30 | 0.00 | 17.36 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 7.40 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 1324.70 | 0.00 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 3006.86 | 118.75 | 17.36 | 406.15 | 0.00 | 0.00 | 0.00 | 0.00 | 238.28 | 1.48 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: T S2 APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 2051.68 | 18-JAN-14:00 | 0.00 | 17.36 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 8.51 | 0.00 |
| February | 1615.20 | 01-FEB-13:00 | 0.00 | 17.36 | 406.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.48 |
| March | 1713.37 | 11-MAR-13:50 | 118.75 | 17.36 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.31 |
| April | 1690.01 | 26-APR-13:40 | 0.00 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 37.08 | 0.00 |
| May | 1439.83 | 03-MAY-13:00 | 0.00 | 17.36 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.07 |
| June | 1333.76 | 27-JUN-13:00 | 0.00 | 17.36 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.07 |
| July | 1669.96 | 31-JUL-13:00 | 0.00 | 17.36 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 86.44 | 0.00 |
| August | 1878.69 | 19-AUG-13:40 | 118.75 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 58.48 | 0.00 |
| September | 2807.06 | 29-SEP-13:30 | 0.00 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 211.10 | 0.00 |
| October | 3016.69 | 16-OCT-12:40 | 0.00 | 17.36 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 238.28 | 0.00 |
| November | 2384.06 | 19-NOV-13:00 | 118.75 | 17.36 | 406.15 | 0.00 | 0.00 | 0.00 | 0.00 | 52.10 | 0.00 |
| December | 2126.53 | 19-DEC-13:20 | 0.00 | 17.36 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 15.44 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 1333.76 | 0.00 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 3016.69 | 118.75 | 17.36 | 406.15 | 0.00 | 0.00 | 0.00 | 0.00 | 238.28 | 1.48 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: T CORRIDOR
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 0.00 | 01-JAN-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.08 |
| February | 0.00 | 01-FEB-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 01-MAR-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.17 |
| April | 0.00 | 01-APR-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.84 |
| May | 0.00 | 01-MAY-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.71 |
| June | 0.00 | 01-JUN-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.29 |
| July | 0.00 | 01-JUL-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.96 |
| August | 0.00 | 01-AUG-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.45 |
| September | 0.00 | 01-SEP-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.17 |
| October | 0.00 | 01-OCT-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 01-NOV-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.80 |
| December | 0.00 | 01-DEC-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.90 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
| Minimum of Months | 0.00 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.84 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: G CORRIDOR
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 0.00 | 01-JAN-00:10 | 397.10 | 370.63 | 56.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.58 |
| February | 0.00 | 01-FEB-00:10 | 397.10 | 370.63 | 56.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 01-MAR-00:10 | 397.10 | 370.63 | 56.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.02 |
| April | 0.00 | 01-APR-00:10 | 397.10 | 370.63 | 56.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.23 |
| May | 0.00 | 01-MAY-00:10 | 397.10 | 370.63 | 56.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.80 |
| June | 0.00 | 01-JUN-00:10 | 397.10 | 370.63 | 56.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.77 |
| July | 0.00 | 01-JUL-00:10 | 397.10 | 370.63 | 56.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.03 |
| August | 0.00 | 01-AUG-00:10 | 397.10 | 370.63 | 56.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.32 |
| September | 0.00 | 01-SEP-00:10 | 397.10 | 370.63 | 56.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.49 |
| October | 0.00 | 01-OCT-00:10 | 397.10 | 370.63 | 56.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 01-NOV-00:10 | 397.10 | 370.63 | 56.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.39 |
| December | 0.00 | 01-DEC-00:10 | 397.10 | 370.63 | 56.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.58 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 0.00 | 397.10 | 370.63 | 56.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 397.10 | 370.63 | 56.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.23 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: M CORRIDOR
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 0.00 | 01-JAN-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.04 |
| February | 0.00 | 01-FEB-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 01-MAR-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.51 |
| April | 0.00 | 01-APR-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.44 |
| May | 0.00 | 01-MAY-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.16 |
| June | 0.00 | 01-JUN-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.31 |
| July | 0.00 | 01-JUL-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.43 |
| August | 0.00 | 01-AUG-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.46 |
| September | 0.00 | 01-SEP-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.87 |
| October | 0.00 | 01-OCT-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 01-NOV-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.38 |
| December | 0.00 | 01-DEC-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.84 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
| Minimum of Months | 0.00 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.44 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
| January | 0.980416E+11 | 68687.09 | 01-JAN-18:40 | 0.624617E+10 | 24104.85 | 03-JAN-03:00 |
| February | 0.870074E+11 | 64700.60 | 14-FEB-18:10 | 0.391225E+10 | 11250.65 | 10-FEB-06:00 |
| March | 0.953985E+11 | 63491.45 | 18-MAR-17:00 | 0.655465E+10 | 30396.10 | 30-MAR-03:00 |
| April | 0.945851E+11 | 63778.75 | 25-APR-17:19 | 0.757731E+09 | 17765.60 | 01-APR-05:00 |
| May | 0.958453E+11 | 64921.43 | 04-MAY-17:40 | 0.475624E+09 | 6807.36 | 14-MAY-04:49 |
| June | 0.978805E+11 | 66986.03 | 29-JUN-17:40 | 107403.31 | 69.82 | 13-JUN-04:40 |
| July | 0.109415E+12 | 72858.73 | 31-JUL-17:19 | 0.00 | 0.00 | 01-JUL-00:10 |
| August | 0.110832E+12 | 77028.25 | 19-AUG-16:30 | 0.00 | 0.00 | 01-AUG-00:10 |
| September | 0.102288E+12 | 73654.86 | 29-SEP-18:19 | 2390512.21 | 410.44 | 20-SEP-04:30 |
| October | 0.107421E+12 | 76488.41 | 14-OCT-16:19 | 0.252240E+09 | 4663.71 | 12-OCT-05:49 |
| November | 0.944809E+11 | 65753.05 | 07-NOV-18:00 | 0.226911E+10 | 9994.56 | 24-NOV-03:00 |
| December | 0.984241E+11 | 65479.06 | 27-DEC-18:40 | 0.474801E+10 | 15493.72 | 13-DEC-04:00 |
| Annual Sum or Average | 0.119162E+13 | 0.252183E+11 | ||||
| Minimum of Months | 0.870074E+11 | 63491.45 | 0.00 | 0.00 | ||
| Maximum of Months | 0.110832E+12 | 77028.25 | 0.655465E+10 | 30396.10 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| INTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [J] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
| January | 0.840929E+10 | 0.493161E+10 | 0.389380E+11 | 0.00 | 0.548926E+10 | 0.00 | 0.00 | 0.293978E+10 | 0.00 | 0.00 | 0.00 | 0.373337E+11 | 0.00 |
| February | 0.760941E+10 | 0.421537E+10 | 0.351823E+11 | 0.00 | 0.459191E+10 | 0.00 | 0.00 | 0.162849E+10 | 0.00 | 0.00 | 0.00 | 0.337799E+11 | 0.00 |
| March | 0.845392E+10 | 0.432042E+10 | 0.389781E+11 | 0.00 | 0.507006E+10 | 0.00 | 0.00 | 0.146818E+10 | 0.00 | 0.00 | 0.00 | 0.371079E+11 | 0.00 |
| April | 0.814762E+10 | 0.384101E+10 | 0.376905E+11 | 0.00 | 0.549941E+10 | 0.00 | 0.00 | 0.414792E+10 | 0.00 | 0.00 | 0.00 | 0.352586E+11 | 0.00 |
| May | 0.843904E+10 | 0.366720E+10 | 0.389647E+11 | 0.00 | 0.545970E+10 | 0.00 | 0.00 | 0.357605E+10 | 0.00 | 0.00 | 0.00 | 0.357385E+11 | 0.00 |
| June | 0.817737E+10 | 0.339980E+10 | 0.377173E+11 | 0.00 | 0.662040E+10 | 0.00 | 0.00 | 0.802746E+10 | 0.00 | 0.00 | 0.00 | 0.339381E+11 | 0.00 |
| July | 0.840929E+10 | 0.357934E+10 | 0.389380E+11 | 0.00 | 0.881529E+10 | 0.00 | 0.00 | 0.150026E+11 | 0.00 | 0.00 | 0.00 | 0.346708E+11 | 0.00 |
| August | 0.845392E+10 | 0.383337E+10 | 0.389781E+11 | 0.00 | 0.904818E+10 | 0.00 | 0.00 | 0.158819E+11 | 0.00 | 0.00 | 0.00 | 0.346363E+11 | 0.00 |
| September | 0.814762E+10 | 0.403583E+10 | 0.376905E+11 | 0.00 | 0.749553E+10 | 0.00 | 0.00 | 0.110904E+11 | 0.00 | 0.00 | 0.00 | 0.338283E+11 | 0.00 |
| October | 0.842417E+10 | 0.452288E+10 | 0.389514E+11 | 0.00 | 0.792618E+10 | 0.00 | 0.00 | 0.120430E+11 | 0.00 | 0.00 | 0.00 | 0.355538E+11 | 0.00 |
| November | 0.814762E+10 | 0.468523E+10 | 0.376905E+11 | 0.00 | 0.534610E+10 | 0.00 | 0.00 | 0.346344E+10 | 0.00 | 0.00 | 0.00 | 0.351479E+11 | 0.00 |
| December | 0.840929E+10 | 0.501565E+10 | 0.389380E+11 | 0.00 | 0.560684E+10 | 0.00 | 0.00 | 0.349752E+10 | 0.00 | 0.00 | 0.00 | 0.369568E+11 | 0.00 |
| Annual Sum or Average | 0.992286E+11 | 0.500477E+11 | 0.458657E+12 | 0.00 | 0.769689E+11 | 0.00 | 0.00 | 0.827667E+11 | 0.00 | 0.00 | 0.00 | 0.423951E+12 | 0.00 |
| Minimum of Months | 0.760941E+10 | 0.339980E+10 | 0.351823E+11 | 0.00 | 0.459191E+10 | 0.00 | 0.00 | 0.146818E+10 | 0.00 | 0.00 | 0.00 | 0.337799E+11 | 0.00 |
| Maximum of Months | 0.845392E+10 | 0.501565E+10 | 0.389781E+11 | 0.00 | 0.904818E+10 | 0.00 | 0.00 | 0.158819E+11 | 0.00 | 0.00 | 0.00 | 0.373337E+11 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| INTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
| January | 0.00 | 0.00 | 0.624617E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.391225E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.655465E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.757731E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.475624E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 107403.31 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 2390512.21 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.252240E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.226911E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.474801E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.252183E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.655465E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| INTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
| January | 5904.43 | 01-JAN-19:10 | 3183.33 | 01-JAN-00:10 | 22709.69 | 03-JAN-17:10 | 0.00 | 4660.59 | 18-JAN-13:50 | 0.00 | 0.00 | 01-JAN-00:10 |
| February | 5904.43 | 01-FEB-19:10 | 3183.33 | 01-FEB-00:10 | 22709.69 | 01-FEB-17:10 | 0.00 | 3941.90 | 01-FEB-12:20 | 0.00 | 0.00 | 01-FEB-00:10 |
| March | 5904.43 | 01-MAR-19:10 | 3183.33 | 01-MAR-00:10 | 22709.69 | 01-MAR-17:10 | 0.00 | 4001.06 | 23-MAR-14:09 | 0.00 | 0.00 | 01-MAR-00:10 |
| April | 5904.43 | 01-APR-18:10 | 3183.33 | 01-APR-00:10 | 22709.69 | 03-APR-16:10 | 0.00 | 5006.78 | 26-APR-12:00 | 0.00 | 0.00 | 01-APR-00:10 |
| May | 5904.43 | 01-MAY-18:10 | 3183.33 | 01-MAY-00:10 | 22709.69 | 01-MAY-16:10 | 0.00 | 4410.84 | 04-MAY-11:00 | 0.00 | 0.00 | 01-MAY-00:10 |
| June | 5904.43 | 01-JUN-18:10 | 3183.33 | 01-JUN-00:10 | 22709.69 | 01-JUN-16:10 | 0.00 | 5106.64 | 29-JUN-16:30 | 0.00 | 0.00 | 01-JUN-00:10 |
| July | 5904.43 | 01-JUL-18:10 | 3183.33 | 01-JUL-00:10 | 22709.69 | 03-JUL-16:10 | 0.00 | 5993.29 | 31-JUL-12:00 | 0.00 | 0.00 | 01-JUL-00:10 |
| August | 5904.43 | 01-AUG-18:10 | 3183.33 | 01-AUG-00:10 | 22709.69 | 01-AUG-16:10 | 0.00 | 6229.86 | 17-AUG-14:09 | 0.00 | 0.00 | 01-AUG-00:10 |
| September | 5904.43 | 01-SEP-18:10 | 3183.33 | 01-SEP-00:10 | 22709.69 | 01-SEP-16:10 | 0.00 | 7836.49 | 29-SEP-12:00 | 0.00 | 0.00 | 01-SEP-00:10 |
| October | 5904.43 | 01-OCT-18:10 | 3183.33 | 01-OCT-00:10 | 22709.69 | 02-OCT-16:10 | 0.00 | 8298.50 | 16-OCT-11:00 | 0.00 | 0.00 | 01-OCT-00:10 |
| November | 5904.43 | 01-NOV-18:10 | 3183.33 | 01-NOV-00:10 | 22709.69 | 01-NOV-16:10 | 0.00 | 5218.50 | 19-NOV-12:00 | 0.00 | 0.00 | 01-NOV-00:10 |
| December | 5904.43 | 01-DEC-19:10 | 3183.33 | 01-DEC-00:10 | 22709.69 | 01-DEC-17:10 | 0.00 | 4778.23 | 19-DEC-12:00 | 0.00 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 5904.43 | 3183.33 | 22709.69 | 0.00 | 3941.90 | 0.00 | 0.00 | |||||
| Maximum of Months | 5904.43 | 3183.33 | 22709.69 | 0.00 | 8298.50 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| COOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY {Maximum} [W] | HEATRECOVERY:ELECTRICITY {TIMESTAMP} | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
| January | 10439.78 | 18-JAN-13:39 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 37405.86 | 01-JAN-07:40 | 0.00 |
| February | 8059.46 | 01-FEB-11:00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 31346.36 | 21-FEB-07:30 | 0.00 |
| March | 8196.08 | 23-MAR-14:09 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 31080.12 | 04-MAR-08:20 | 0.00 |
| April | 11969.26 | 26-APR-12:00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 34616.09 | 20-APR-07:49 | 0.00 |
| May | 9561.64 | 04-MAY-11:00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 35646.99 | 12-MAY-07:30 | 0.00 |
| June | 11468.80 | 29-JUN-16:30 | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 32392.03 | 11-JUN-06:00 | 0.00 |
| July | 15981.42 | 31-JUL-12:00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 30690.50 | 28-JUL-06:49 | 0.00 |
| August | 16742.55 | 17-AUG-13:00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 32665.78 | 19-AUG-06:49 | 0.00 |
| September | 23007.20 | 29-SEP-12:00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 30111.81 | 30-SEP-05:00 | 0.00 |
| October | 24675.46 | 16-OCT-11:00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 33320.33 | 18-OCT-06:40 | 0.00 |
| November | 11955.87 | 19-NOV-12:00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 33256.90 | 21-NOV-07:49 | 0.00 |
| December | 10750.47 | 19-DEC-12:00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 33519.49 | 06-DEC-07:19 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
| Minimum of Months | 8059.46 | 0.00 | 0.00 | 0.00 | 30111.81 | 0.00 | |||
| Maximum of Months | 24675.46 | 0.00 | 0.00 | 0.00 | 37405.86 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
| January | 68687.09 | 01-JAN-18:40 | 5231.74 | 22609.62 | 3183.33 | 0.00 | 1660.50 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 64700.60 | 14-FEB-18:10 | 5231.74 | 22609.62 | 3183.33 | 0.00 | 1986.76 | 0.00 | 0.00 | 1128.12 | 0.00 |
| March | 63491.45 | 18-MAR-17:00 | 5231.74 | 22609.62 | 3183.33 | 0.00 | 2146.76 | 0.00 | 0.00 | 1659.76 | 0.00 |
| April | 63778.75 | 25-APR-17:19 | 5231.74 | 22609.62 | 0.00 | 0.00 | 3555.92 | 0.00 | 0.00 | 6303.52 | 0.00 |
| May | 64921.43 | 04-MAY-17:40 | 5231.74 | 22609.62 | 0.00 | 0.00 | 3391.42 | 0.00 | 0.00 | 5743.84 | 0.00 |
| June | 66986.03 | 29-JUN-17:40 | 5231.74 | 22609.62 | 0.00 | 0.00 | 5009.56 | 0.00 | 0.00 | 11146.87 | 0.00 |
| July | 72858.73 | 31-JUL-17:19 | 5231.74 | 22609.62 | 0.00 | 0.00 | 5578.51 | 0.00 | 0.00 | 13032.85 | 0.00 |
| August | 77028.25 | 19-AUG-16:30 | 4289.87 | 22609.62 | 0.00 | 0.00 | 5778.68 | 0.00 | 0.00 | 13756.60 | 0.00 |
| September | 73654.86 | 29-SEP-18:19 | 5904.43 | 20531.10 | 3183.33 | 0.00 | 5482.37 | 0.00 | 0.00 | 12952.53 | 0.00 |
| October | 76488.41 | 14-OCT-16:19 | 4289.87 | 22609.62 | 0.00 | 0.00 | 6585.10 | 0.00 | 0.00 | 16865.47 | 0.00 |
| November | 65753.05 | 07-NOV-18:00 | 5231.74 | 22609.62 | 3183.33 | 0.00 | 2223.20 | 0.00 | 0.00 | 1913.67 | 0.00 |
| December | 65479.06 | 27-DEC-18:40 | 5231.74 | 22609.62 | 3183.33 | 0.00 | 2305.62 | 0.00 | 0.00 | 2127.40 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
| Minimum of Months | 63491.45 | 4289.87 | 20531.10 | 0.00 | 0.00 | 1660.50 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 77028.25 | 5904.43 | 22609.62 | 3183.33 | 0.00 | 6585.10 | 0.00 | 0.00 | 16865.47 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| INTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | |
| January | 0.00 | 0.00 | 24104.85 | 03-JAN-03:00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 11250.65 | 10-FEB-06:00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 30396.10 | 30-MAR-03:00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 17765.60 | 01-APR-05:00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 6807.36 | 14-MAY-04:49 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 69.82 | 13-JUN-04:40 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 410.44 | 20-SEP-04:30 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 4663.71 | 12-OCT-05:49 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 9994.56 | 24-NOV-03:00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 15493.72 | 13-DEC-04:00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 30396.10 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: G SW APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: G NW APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: OFFICE
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: G NE APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: G N1 APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: G N2 APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: G S1 APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: G S2 APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: M SW APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: M NW APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: M SE APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: M NE APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: M N1 APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: M N2 APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: M S1 APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: M S2 APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: T SW APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: T NW APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: T SE APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: T NE APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: T N1 APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: T N2 APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: T S1 APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: T S2 APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: T CORRIDOR
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: G CORRIDOR
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: M CORRIDOR
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: G SW APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 452.17 | 22.73 | 5.83 | 22.75 | 0.00 | 22.75 |
| February | 460.67 | 22.44 | 0.00 | 22.44 | 0.00 | 22.44 |
| March | 490.67 | 22.05 | 0.00 | 22.05 | 0.00 | 22.05 |
| April | 401.83 | 22.87 | 2.17 | 22.87 | 0.00 | 22.87 |
| May | 417.83 | 22.91 | 1.33 | 22.91 | 0.00 | 22.91 |
| June | 229.00 | 23.32 | 81.67 | 23.50 | 7.00 | 23.51 |
| July | 31.83 | 23.98 | 398.67 | 23.99 | 31.83 | 23.99 |
| August | 48.17 | 23.97 | 472.00 | 23.99 | 47.67 | 23.99 |
| September | 39.00 | 23.79 | 311.83 | 23.97 | 19.50 | 23.97 |
| October | 147.00 | 23.65 | 167.83 | 23.84 | 10.17 | 23.84 |
| November | 327.00 | 23.30 | 8.00 | 23.31 | 0.00 | 23.31 |
| December | 467.17 | 23.09 | 0.00 | 23.09 | 0.00 | 23.09 |
| Annual Sum or Average | 3512.33 | 22.85 | 1449.33 | 23.19 | 116.17 | 23.20 |
| Minimum of Months | 31.83 | 22.05 | 0.00 | 22.05 | 0.00 | 22.05 |
| Maximum of Months | 490.67 | 23.98 | 472.00 | 23.99 | 47.67 | 23.99 |
Report: ComfortReportSimple55Monthly
For: G NW APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 744.00 | 21.98 | 41.83 | 21.93 | 41.83 | 21.89 |
| February | 672.00 | 21.55 | 14.50 | 21.54 | 14.50 | 21.54 |
| March | 744.00 | 21.57 | 2.50 | 21.57 | 2.50 | 21.56 |
| April | 673.83 | 22.57 | 0.00 | 22.57 | 0.00 | 22.57 |
| May | 623.67 | 22.98 | 0.00 | 22.98 | 0.00 | 22.98 |
| June | 277.50 | 23.35 | 143.67 | 23.57 | 4.00 | 23.58 |
| July | 42.83 | 23.99 | 557.83 | 23.99 | 42.83 | 23.99 |
| August | 103.83 | 23.94 | 631.50 | 23.98 | 99.50 | 23.98 |
| September | 128.83 | 23.67 | 305.83 | 23.89 | 47.17 | 23.90 |
| October | 385.67 | 23.57 | 172.50 | 23.70 | 23.33 | 23.72 |
| November | 720.00 | 22.55 | 0.00 | 22.55 | 0.00 | 22.55 |
| December | 744.00 | 22.04 | 11.50 | 22.02 | 11.50 | 22.01 |
| Annual Sum or Average | 5860.17 | 22.39 | 1881.67 | 22.75 | 287.17 | 22.77 |
| Minimum of Months | 42.83 | 21.55 | 0.00 | 21.54 | 0.00 | 21.54 |
| Maximum of Months | 744.00 | 23.99 | 631.50 | 23.99 | 99.50 | 23.99 |
Report: ComfortReportSimple55Monthly
For: OFFICE
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 51.83 | 23.71 | 24.67 | 23.88 | 0.17 | 23.88 |
| February | 69.50 | 23.60 | 4.17 | 23.62 | 0.00 | 23.62 |
| March | 118.50 | 23.33 | 10.67 | 23.37 | 0.50 | 23.36 |
| April | 26.50 | 23.86 | 37.83 | 24.03 | 0.00 | 24.03 |
| May | 33.33 | 23.95 | 29.17 | 24.09 | 0.00 | 24.09 |
| June | 2.33 | 23.96 | 98.50 | 24.23 | 0.00 | 24.23 |
| July | 2.83 | 25.60 | 140.00 | 24.26 | 2.83 | 24.28 |
| August | 6.67 | 25.56 | 161.00 | 24.29 | 6.67 | 24.33 |
| September | 1.50 | 25.09 | 139.50 | 24.23 | 1.50 | 24.24 |
| October | 2.67 | 25.52 | 112.83 | 24.27 | 2.67 | 24.30 |
| November | 19.33 | 24.05 | 40.17 | 24.16 | 0.00 | 24.16 |
| December | 46.50 | 23.93 | 6.50 | 23.98 | 0.00 | 23.98 |
| Annual Sum or Average | 381.50 | 23.71 | 805.00 | 24.06 | 14.33 | 24.07 |
| Minimum of Months | 1.50 | 23.33 | 4.17 | 23.37 | 0.00 | 23.36 |
| Maximum of Months | 118.50 | 25.60 | 161.00 | 24.29 | 6.67 | 24.33 |
Report: ComfortReportSimple55Monthly
For: G NE APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 744.00 | 22.01 | 27.83 | 21.98 | 27.83 | 21.95 |
| February | 672.00 | 21.54 | 11.00 | 21.53 | 11.00 | 21.53 |
| March | 744.00 | 21.59 | 2.67 | 21.59 | 2.67 | 21.58 |
| April | 691.33 | 22.58 | 0.00 | 22.58 | 0.00 | 22.58 |
| May | 661.67 | 22.98 | 0.00 | 22.98 | 0.00 | 22.98 |
| June | 312.67 | 23.31 | 118.67 | 23.50 | 10.17 | 23.51 |
| July | 61.50 | 23.96 | 547.33 | 23.99 | 57.50 | 23.99 |
| August | 116.50 | 23.94 | 629.00 | 23.98 | 113.00 | 23.98 |
| September | 173.67 | 23.61 | 279.33 | 23.84 | 52.83 | 23.85 |
| October | 415.50 | 23.59 | 161.33 | 23.71 | 30.67 | 23.72 |
| November | 720.00 | 22.52 | 0.00 | 22.52 | 0.00 | 22.52 |
| December | 744.00 | 22.05 | 10.50 | 22.03 | 10.50 | 22.02 |
| Annual Sum or Average | 6056.83 | 22.42 | 1787.67 | 22.76 | 316.17 | 22.79 |
| Minimum of Months | 61.50 | 21.54 | 0.00 | 21.53 | 0.00 | 21.53 |
| Maximum of Months | 744.00 | 23.96 | 629.00 | 23.99 | 113.00 | 23.99 |
Report: ComfortReportSimple55Monthly
For: G N1 APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 743.50 | 22.24 | 4.83 | 22.23 | 4.83 | 22.22 |
| February | 672.00 | 21.85 | 0.00 | 21.85 | 0.00 | 21.85 |
| March | 744.00 | 21.79 | 0.00 | 21.79 | 0.00 | 21.79 |
| April | 697.00 | 22.82 | 0.00 | 22.82 | 0.00 | 22.82 |
| May | 599.83 | 23.25 | 0.00 | 23.25 | 0.00 | 23.25 |
| June | 167.17 | 23.53 | 127.17 | 23.73 | 0.00 | 23.73 |
| July | 26.50 | 24.00 | 533.17 | 24.00 | 26.50 | 24.00 |
| August | 65.67 | 23.99 | 652.83 | 23.99 | 65.67 | 23.99 |
| September | 59.83 | 23.79 | 310.50 | 23.96 | 21.33 | 23.96 |
| October | 322.00 | 23.76 | 167.50 | 23.84 | 13.67 | 23.85 |
| November | 720.00 | 22.93 | 0.00 | 22.93 | 0.00 | 22.93 |
| December | 744.00 | 22.38 | 0.00 | 22.38 | 0.00 | 22.38 |
| Annual Sum or Average | 5561.50 | 22.59 | 1796.00 | 22.93 | 132.00 | 22.95 |
| Minimum of Months | 26.50 | 21.79 | 0.00 | 21.79 | 0.00 | 21.79 |
| Maximum of Months | 744.00 | 24.00 | 652.83 | 24.00 | 65.67 | 24.00 |
Report: ComfortReportSimple55Monthly
For: G N2 APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 743.33 | 22.24 | 4.33 | 22.23 | 4.33 | 22.23 |
| February | 672.00 | 21.85 | 0.00 | 21.85 | 0.00 | 21.85 |
| March | 744.00 | 21.79 | 0.00 | 21.79 | 0.00 | 21.79 |
| April | 698.50 | 22.82 | 0.00 | 22.82 | 0.00 | 22.82 |
| May | 604.17 | 23.24 | 0.00 | 23.24 | 0.00 | 23.24 |
| June | 173.50 | 23.53 | 125.67 | 23.72 | 0.00 | 23.72 |
| July | 27.00 | 24.00 | 531.83 | 24.00 | 27.00 | 24.00 |
| August | 66.50 | 23.99 | 651.67 | 23.99 | 66.50 | 23.99 |
| September | 62.67 | 23.78 | 308.33 | 23.95 | 22.00 | 23.96 |
| October | 322.17 | 23.76 | 167.50 | 23.84 | 13.67 | 23.85 |
| November | 720.00 | 22.93 | 0.00 | 22.93 | 0.00 | 22.93 |
| December | 744.00 | 22.38 | 0.00 | 22.38 | 0.00 | 22.38 |
| Annual Sum or Average | 5577.83 | 22.60 | 1789.33 | 22.93 | 133.50 | 22.95 |
| Minimum of Months | 27.00 | 21.79 | 0.00 | 21.79 | 0.00 | 21.79 |
| Maximum of Months | 744.00 | 24.00 | 651.67 | 24.00 | 66.50 | 24.00 |
Report: ComfortReportSimple55Monthly
For: G S1 APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 365.33 | 23.11 | 9.33 | 23.13 | 0.00 | 23.13 |
| February | 432.50 | 23.05 | 0.00 | 23.05 | 0.00 | 23.05 |
| March | 476.00 | 22.52 | 0.00 | 22.52 | 0.00 | 22.52 |
| April | 365.50 | 23.19 | 4.00 | 23.19 | 0.00 | 23.19 |
| May | 374.50 | 23.19 | 3.50 | 23.20 | 0.00 | 23.20 |
| June | 129.33 | 23.51 | 79.67 | 23.69 | 0.00 | 23.69 |
| July | 19.00 | 24.00 | 393.83 | 24.00 | 19.00 | 24.00 |
| August | 26.17 | 24.00 | 477.50 | 24.00 | 26.17 | 24.00 |
| September | 11.50 | 23.94 | 341.50 | 24.00 | 9.33 | 24.00 |
| October | 87.50 | 23.87 | 182.00 | 23.96 | 4.83 | 23.96 |
| November | 234.17 | 23.64 | 34.33 | 23.69 | 0.00 | 23.69 |
| December | 377.67 | 23.51 | 0.00 | 23.51 | 0.00 | 23.51 |
| Annual Sum or Average | 2899.17 | 23.18 | 1525.67 | 23.46 | 59.33 | 23.47 |
| Minimum of Months | 11.50 | 22.52 | 0.00 | 22.52 | 0.00 | 22.52 |
| Maximum of Months | 476.00 | 24.00 | 477.50 | 24.00 | 26.17 | 24.00 |
Report: ComfortReportSimple55Monthly
For: G S2 APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 350.67 | 23.08 | 11.50 | 23.11 | 0.00 | 23.11 |
| February | 427.17 | 23.09 | 0.00 | 23.09 | 0.00 | 23.09 |
| March | 471.17 | 22.58 | 0.00 | 22.58 | 0.00 | 22.58 |
| April | 350.00 | 23.21 | 11.33 | 23.23 | 0.00 | 23.23 |
| May | 361.67 | 23.23 | 12.83 | 23.26 | 0.00 | 23.26 |
| June | 107.83 | 23.53 | 92.50 | 23.74 | 0.00 | 23.74 |
| July | 10.50 | 24.00 | 406.00 | 24.00 | 10.50 | 24.00 |
| August | 15.00 | 24.00 | 484.50 | 24.00 | 15.00 | 24.00 |
| September | 7.33 | 23.94 | 354.33 | 24.00 | 5.83 | 24.00 |
| October | 71.67 | 23.89 | 199.00 | 23.97 | 3.83 | 23.97 |
| November | 225.50 | 23.66 | 39.83 | 23.71 | 0.00 | 23.71 |
| December | 368.17 | 23.53 | 0.00 | 23.53 | 0.00 | 23.53 |
| Annual Sum or Average | 2766.67 | 23.19 | 1611.83 | 23.49 | 35.17 | 23.49 |
| Minimum of Months | 7.33 | 22.58 | 0.00 | 22.58 | 0.00 | 22.58 |
| Maximum of Months | 471.17 | 24.00 | 484.50 | 24.00 | 15.00 | 24.00 |
Report: ComfortReportSimple55Monthly
For: M SW APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 357.67 | 22.98 | 10.50 | 23.01 | 0.00 | 23.01 |
| February | 357.33 | 23.01 | 5.00 | 23.02 | 0.00 | 23.02 |
| March | 370.67 | 22.78 | 20.00 | 22.84 | 0.00 | 22.84 |
| April | 164.50 | 23.28 | 75.17 | 23.50 | 0.00 | 23.50 |
| May | 181.67 | 23.36 | 60.83 | 23.52 | 0.00 | 23.52 |
| June | 12.17 | 23.57 | 219.17 | 23.98 | 0.00 | 23.98 |
| July | 0.50 | 24.00 | 450.33 | 24.00 | 0.50 | 24.00 |
| August | 12.83 | 24.00 | 484.33 | 24.00 | 12.83 | 24.00 |
| September | 6.00 | 23.78 | 343.00 | 23.99 | 2.00 | 23.99 |
| October | 125.00 | 23.69 | 178.83 | 23.87 | 4.50 | 23.87 |
| November | 260.67 | 23.38 | 39.83 | 23.46 | 0.00 | 23.46 |
| December | 383.33 | 23.28 | 7.17 | 23.29 | 0.00 | 23.29 |
| Annual Sum or Average | 2232.33 | 23.15 | 1894.17 | 23.54 | 19.83 | 23.54 |
| Minimum of Months | 0.50 | 22.78 | 5.00 | 22.84 | 0.00 | 22.84 |
| Maximum of Months | 383.33 | 24.00 | 484.33 | 24.00 | 12.83 | 24.00 |
Report: ComfortReportSimple55Monthly
For: M NW APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 689.17 | 22.37 | 1.83 | 22.36 | 1.83 | 22.36 |
| February | 663.67 | 22.57 | 0.00 | 22.57 | 0.00 | 22.57 |
| March | 675.33 | 22.47 | 11.83 | 22.49 | 0.00 | 22.49 |
| April | 336.50 | 23.28 | 70.83 | 23.41 | 0.00 | 23.41 |
| May | 247.17 | 23.44 | 72.83 | 23.56 | 0.00 | 23.56 |
| June | 15.17 | 23.60 | 341.83 | 23.98 | 0.00 | 23.98 |
| July | 0.00 | 0.00 | 633.00 | 24.00 | 0.00 | 24.00 |
| August | 25.33 | 24.00 | 704.17 | 24.00 | 25.33 | 24.00 |
| September | 34.67 | 23.80 | 424.00 | 23.98 | 14.67 | 23.98 |
| October | 274.50 | 23.64 | 190.17 | 23.79 | 7.67 | 23.79 |
| November | 609.50 | 23.04 | 4.33 | 23.04 | 0.00 | 23.04 |
| December | 729.83 | 22.64 | 0.00 | 22.64 | 0.00 | 22.64 |
| Annual Sum or Average | 4300.83 | 22.80 | 2454.83 | 23.23 | 49.50 | 23.24 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 22.36 | 0.00 | 22.36 |
| Maximum of Months | 729.83 | 24.00 | 704.17 | 24.00 | 25.33 | 24.00 |
Report: ComfortReportSimple55Monthly
For: M SE APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 358.67 | 23.02 | 11.50 | 23.05 | 0.00 | 23.05 |
| February | 361.83 | 22.99 | 3.67 | 23.00 | 0.00 | 23.00 |
| March | 376.67 | 22.78 | 23.83 | 22.85 | 0.00 | 22.85 |
| April | 169.33 | 23.30 | 69.83 | 23.50 | 0.00 | 23.50 |
| May | 193.17 | 23.38 | 37.50 | 23.48 | 0.00 | 23.48 |
| June | 13.67 | 23.55 | 200.00 | 23.97 | 0.00 | 23.97 |
| July | 1.17 | 24.00 | 444.83 | 24.00 | 1.17 | 24.00 |
| August | 12.33 | 24.00 | 483.17 | 24.00 | 12.33 | 24.00 |
| September | 13.33 | 23.76 | 331.83 | 23.99 | 4.67 | 23.99 |
| October | 123.00 | 23.69 | 175.67 | 23.87 | 4.50 | 23.87 |
| November | 260.17 | 23.38 | 36.67 | 23.45 | 0.00 | 23.45 |
| December | 377.67 | 23.27 | 4.83 | 23.28 | 0.00 | 23.28 |
| Annual Sum or Average | 2261.00 | 23.16 | 1823.33 | 23.53 | 22.67 | 23.54 |
| Minimum of Months | 1.17 | 22.78 | 3.67 | 22.85 | 0.00 | 22.85 |
| Maximum of Months | 377.67 | 24.00 | 483.17 | 24.00 | 12.33 | 24.00 |
Report: ComfortReportSimple55Monthly
For: M NE APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 672.50 | 22.39 | 1.33 | 22.38 | 1.33 | 22.38 |
| February | 670.17 | 22.56 | 0.00 | 22.56 | 0.00 | 22.56 |
| March | 654.33 | 22.44 | 7.33 | 22.46 | 0.00 | 22.46 |
| April | 336.67 | 23.33 | 44.33 | 23.41 | 0.00 | 23.41 |
| May | 244.50 | 23.44 | 49.50 | 23.53 | 0.00 | 23.53 |
| June | 15.50 | 23.57 | 342.00 | 23.98 | 0.00 | 23.98 |
| July | 3.33 | 24.00 | 652.83 | 24.00 | 3.33 | 24.00 |
| August | 21.00 | 24.00 | 709.83 | 24.00 | 21.00 | 24.00 |
| September | 37.83 | 23.75 | 401.67 | 23.98 | 15.50 | 23.98 |
| October | 274.00 | 23.67 | 191.83 | 23.81 | 7.67 | 23.81 |
| November | 648.50 | 23.07 | 0.00 | 23.07 | 0.00 | 23.07 |
| December | 730.33 | 22.66 | 0.00 | 22.66 | 0.00 | 22.66 |
| Annual Sum or Average | 4308.67 | 22.81 | 2400.67 | 23.23 | 48.83 | 23.24 |
| Minimum of Months | 3.33 | 22.39 | 0.00 | 22.38 | 0.00 | 22.38 |
| Maximum of Months | 730.33 | 24.00 | 709.83 | 24.00 | 21.00 | 24.00 |
Report: ComfortReportSimple55Monthly
For: M N1 APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 616.83 | 22.57 | 0.00 | 22.57 | 0.00 | 22.57 |
| February | 649.50 | 23.06 | 0.00 | 23.06 | 0.00 | 23.06 |
| March | 626.67 | 22.81 | 4.33 | 22.82 | 0.00 | 22.82 |
| April | 218.33 | 23.40 | 23.50 | 23.46 | 0.00 | 23.46 |
| May | 141.00 | 23.64 | 40.33 | 23.72 | 0.00 | 23.72 |
| June | 0.17 | 23.76 | 282.83 | 24.00 | 0.00 | 24.00 |
| July | 0.00 | 0.00 | 599.67 | 24.00 | 0.00 | 24.00 |
| August | 13.00 | 24.00 | 698.17 | 24.00 | 13.00 | 24.00 |
| September | 10.00 | 23.91 | 402.83 | 24.00 | 6.17 | 24.00 |
| October | 237.33 | 23.85 | 186.33 | 23.92 | 5.17 | 23.92 |
| November | 538.67 | 23.39 | 12.83 | 23.41 | 0.00 | 23.41 |
| December | 681.83 | 23.04 | 0.00 | 23.04 | 0.00 | 23.04 |
| Annual Sum or Average | 3733.33 | 23.08 | 2250.83 | 23.43 | 24.33 | 23.43 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 22.57 | 0.00 | 22.57 |
| Maximum of Months | 681.83 | 24.00 | 698.17 | 24.00 | 13.00 | 24.00 |
Report: ComfortReportSimple55Monthly
For: M N2 APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 613.83 | 22.58 | 0.00 | 22.58 | 0.00 | 22.58 |
| February | 650.17 | 23.06 | 0.00 | 23.06 | 0.00 | 23.06 |
| March | 623.67 | 22.81 | 4.17 | 22.82 | 0.00 | 22.82 |
| April | 218.00 | 23.40 | 23.33 | 23.46 | 0.00 | 23.46 |
| May | 140.83 | 23.64 | 40.17 | 23.72 | 0.00 | 23.72 |
| June | 0.33 | 23.76 | 280.50 | 24.00 | 0.00 | 24.00 |
| July | 0.00 | 0.00 | 598.50 | 24.00 | 0.00 | 24.00 |
| August | 13.17 | 24.00 | 697.83 | 24.00 | 13.17 | 24.00 |
| September | 10.50 | 23.91 | 402.17 | 24.00 | 6.33 | 24.00 |
| October | 237.83 | 23.85 | 186.00 | 23.92 | 5.17 | 23.92 |
| November | 539.67 | 23.39 | 12.33 | 23.41 | 0.00 | 23.41 |
| December | 681.33 | 23.04 | 0.00 | 23.04 | 0.00 | 23.04 |
| Annual Sum or Average | 3729.33 | 23.08 | 2245.00 | 23.43 | 24.67 | 23.43 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 22.58 | 0.00 | 22.58 |
| Maximum of Months | 681.33 | 24.00 | 697.83 | 24.00 | 13.17 | 24.00 |
Report: ComfortReportSimple55Monthly
For: M S1 APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 266.17 | 23.39 | 14.17 | 23.42 | 0.00 | 23.42 |
| February | 275.50 | 23.47 | 4.67 | 23.48 | 0.00 | 23.48 |
| March | 251.83 | 23.05 | 23.00 | 23.13 | 0.00 | 23.13 |
| April | 86.50 | 23.39 | 59.00 | 23.64 | 0.00 | 23.64 |
| May | 106.83 | 23.59 | 39.83 | 23.70 | 0.00 | 23.70 |
| June | 1.33 | 23.73 | 192.17 | 24.00 | 0.00 | 24.00 |
| July | 0.17 | 24.00 | 442.67 | 24.00 | 0.17 | 24.00 |
| August | 6.33 | 24.00 | 486.67 | 24.00 | 6.33 | 24.00 |
| September | 0.17 | 24.00 | 352.50 | 24.00 | 0.17 | 24.00 |
| October | 86.00 | 23.91 | 184.50 | 23.97 | 4.33 | 23.97 |
| November | 185.83 | 23.72 | 59.67 | 23.79 | 0.00 | 23.79 |
| December | 313.33 | 23.65 | 14.17 | 23.66 | 0.00 | 23.66 |
| Annual Sum or Average | 1580.00 | 23.49 | 1873.00 | 23.76 | 11.00 | 23.77 |
| Minimum of Months | 0.17 | 23.05 | 4.67 | 23.13 | 0.00 | 23.13 |
| Maximum of Months | 313.33 | 24.00 | 486.67 | 24.00 | 6.33 | 24.00 |
Report: ComfortReportSimple55Monthly
For: M S2 APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 266.33 | 23.40 | 14.50 | 23.43 | 0.00 | 23.43 |
| February | 276.00 | 23.47 | 4.50 | 23.48 | 0.00 | 23.48 |
| March | 251.33 | 23.05 | 23.17 | 23.13 | 0.00 | 23.13 |
| April | 86.67 | 23.40 | 59.33 | 23.64 | 0.00 | 23.64 |
| May | 107.33 | 23.59 | 40.00 | 23.70 | 0.00 | 23.70 |
| June | 1.50 | 23.74 | 191.17 | 24.00 | 0.00 | 24.00 |
| July | 0.33 | 24.00 | 442.50 | 24.00 | 0.33 | 24.00 |
| August | 6.33 | 24.00 | 486.50 | 24.00 | 6.33 | 24.00 |
| September | 0.17 | 24.00 | 351.83 | 24.00 | 0.17 | 24.00 |
| October | 86.00 | 23.91 | 184.33 | 23.97 | 4.33 | 23.97 |
| November | 186.17 | 23.72 | 59.83 | 23.79 | 0.00 | 23.79 |
| December | 313.17 | 23.65 | 14.33 | 23.66 | 0.00 | 23.66 |
| Annual Sum or Average | 1581.33 | 23.49 | 1872.00 | 23.76 | 11.17 | 23.77 |
| Minimum of Months | 0.17 | 23.05 | 4.50 | 23.13 | 0.00 | 23.13 |
| Maximum of Months | 313.17 | 24.00 | 486.50 | 24.00 | 6.33 | 24.00 |
Report: ComfortReportSimple55Monthly
For: T SW APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 473.83 | 21.96 | 73.33 | 21.90 | 62.83 | 21.82 |
| February | 434.83 | 21.72 | 35.33 | 21.71 | 28.17 | 21.68 |
| March | 449.33 | 21.67 | 62.67 | 21.73 | 39.33 | 21.69 |
| April | 362.83 | 22.19 | 69.83 | 22.45 | 4.83 | 22.43 |
| May | 381.33 | 22.22 | 56.00 | 22.45 | 0.00 | 22.45 |
| June | 246.17 | 22.93 | 148.00 | 23.33 | 9.17 | 23.34 |
| July | 174.00 | 23.50 | 360.00 | 23.80 | 81.33 | 23.80 |
| August | 187.50 | 23.50 | 394.00 | 23.77 | 126.33 | 23.75 |
| September | 230.17 | 23.11 | 224.33 | 23.52 | 38.50 | 23.53 |
| October | 308.33 | 22.81 | 162.67 | 23.21 | 42.00 | 23.27 |
| November | 431.50 | 22.08 | 49.50 | 22.11 | 27.83 | 22.06 |
| December | 475.00 | 21.98 | 74.83 | 21.91 | 65.67 | 21.82 |
| Annual Sum or Average | 4154.83 | 22.28 | 1710.50 | 22.66 | 526.00 | 22.65 |
| Minimum of Months | 174.00 | 21.67 | 35.33 | 21.71 | 0.00 | 21.68 |
| Maximum of Months | 475.00 | 23.50 | 394.00 | 23.80 | 126.33 | 23.80 |
Report: ComfortReportSimple55Monthly
For: T NW APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 729.33 | 21.69 | 138.50 | 21.60 | 138.50 | 21.53 |
| February | 667.67 | 21.59 | 55.67 | 21.56 | 55.50 | 21.52 |
| March | 700.83 | 21.64 | 79.17 | 21.65 | 61.83 | 21.61 |
| April | 523.33 | 22.19 | 102.83 | 22.45 | 8.67 | 22.43 |
| May | 498.67 | 22.30 | 115.50 | 22.62 | 0.00 | 22.62 |
| June | 292.17 | 22.95 | 290.17 | 23.47 | 8.50 | 23.47 |
| July | 191.50 | 23.52 | 554.67 | 23.85 | 93.00 | 23.85 |
| August | 239.83 | 23.48 | 599.00 | 23.79 | 152.50 | 23.78 |
| September | 332.83 | 23.04 | 330.00 | 23.49 | 53.50 | 23.50 |
| October | 497.50 | 22.84 | 193.67 | 23.15 | 66.17 | 23.21 |
| November | 701.83 | 21.86 | 67.00 | 21.81 | 63.83 | 21.76 |
| December | 739.50 | 21.74 | 165.17 | 21.62 | 165.17 | 21.54 |
| Annual Sum or Average | 6115.00 | 22.15 | 2691.33 | 22.54 | 867.17 | 22.51 |
| Minimum of Months | 191.50 | 21.59 | 55.67 | 21.56 | 0.00 | 21.52 |
| Maximum of Months | 739.50 | 23.52 | 599.00 | 23.85 | 165.17 | 23.85 |
Report: ComfortReportSimple55Monthly
For: T SE APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 473.33 | 21.97 | 75.33 | 21.92 | 61.00 | 21.84 |
| February | 437.67 | 21.70 | 31.50 | 21.69 | 27.50 | 21.65 |
| March | 453.33 | 21.67 | 65.83 | 21.74 | 40.50 | 21.69 |
| April | 375.83 | 22.20 | 56.33 | 22.41 | 3.67 | 22.40 |
| May | 397.50 | 22.24 | 37.50 | 22.39 | 0.00 | 22.39 |
| June | 268.33 | 22.93 | 132.83 | 23.27 | 10.33 | 23.28 |
| July | 199.83 | 23.49 | 357.50 | 23.78 | 98.33 | 23.78 |
| August | 208.00 | 23.50 | 392.00 | 23.75 | 141.67 | 23.74 |
| September | 245.17 | 23.08 | 215.83 | 23.48 | 41.33 | 23.49 |
| October | 322.33 | 22.85 | 160.00 | 23.22 | 45.00 | 23.28 |
| November | 437.67 | 22.09 | 47.83 | 22.10 | 28.50 | 22.05 |
| December | 476.83 | 21.98 | 73.00 | 21.91 | 63.83 | 21.83 |
| Annual Sum or Average | 4295.83 | 22.30 | 1645.50 | 22.65 | 561.67 | 22.65 |
| Minimum of Months | 199.83 | 21.67 | 31.50 | 21.69 | 0.00 | 21.65 |
| Maximum of Months | 476.83 | 23.50 | 392.00 | 23.78 | 141.67 | 23.78 |
Report: ComfortReportSimple55Monthly
For: T NE APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 727.50 | 21.69 | 122.33 | 21.60 | 122.33 | 21.54 |
| February | 669.33 | 21.57 | 50.33 | 21.54 | 50.33 | 21.51 |
| March | 701.83 | 21.67 | 75.67 | 21.67 | 59.17 | 21.63 |
| April | 530.00 | 22.24 | 91.00 | 22.47 | 5.83 | 22.46 |
| May | 503.50 | 22.35 | 88.83 | 22.60 | 0.00 | 22.60 |
| June | 302.83 | 22.95 | 299.50 | 23.47 | 9.83 | 23.47 |
| July | 206.50 | 23.50 | 562.33 | 23.84 | 104.33 | 23.83 |
| August | 251.17 | 23.47 | 608.17 | 23.78 | 163.83 | 23.77 |
| September | 342.33 | 23.00 | 322.67 | 23.45 | 57.67 | 23.47 |
| October | 510.67 | 22.89 | 176.33 | 23.16 | 68.33 | 23.23 |
| November | 710.17 | 21.85 | 59.83 | 21.79 | 59.83 | 21.74 |
| December | 743.17 | 21.74 | 152.33 | 21.63 | 152.33 | 21.55 |
| Annual Sum or Average | 6199.00 | 22.16 | 2609.33 | 22.55 | 853.83 | 22.53 |
| Minimum of Months | 206.50 | 21.57 | 50.33 | 21.54 | 0.00 | 21.51 |
| Maximum of Months | 743.17 | 23.50 | 608.17 | 23.84 | 163.83 | 23.83 |
Report: ComfortReportSimple55Monthly
For: T N1 APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 732.50 | 21.77 | 96.50 | 21.69 | 96.50 | 21.63 |
| February | 672.00 | 21.63 | 40.00 | 21.60 | 40.00 | 21.58 |
| March | 720.67 | 21.77 | 34.83 | 21.75 | 30.50 | 21.73 |
| April | 548.67 | 22.48 | 45.67 | 22.58 | 2.33 | 22.58 |
| May | 497.17 | 22.61 | 46.00 | 22.73 | 0.00 | 22.73 |
| June | 228.50 | 23.15 | 279.83 | 23.62 | 6.00 | 23.62 |
| July | 142.67 | 23.69 | 569.33 | 23.93 | 83.50 | 23.93 |
| August | 195.50 | 23.68 | 624.67 | 23.90 | 138.50 | 23.89 |
| September | 289.00 | 23.26 | 309.33 | 23.62 | 49.00 | 23.64 |
| October | 495.83 | 23.06 | 170.00 | 23.30 | 43.33 | 23.35 |
| November | 712.67 | 21.97 | 47.17 | 21.91 | 47.17 | 21.87 |
| December | 744.00 | 21.81 | 95.50 | 21.73 | 95.50 | 21.66 |
| Annual Sum or Average | 5979.17 | 22.26 | 2358.83 | 22.64 | 632.33 | 22.63 |
| Minimum of Months | 142.67 | 21.63 | 34.83 | 21.60 | 0.00 | 21.58 |
| Maximum of Months | 744.00 | 23.69 | 624.67 | 23.93 | 138.50 | 23.93 |
Report: ComfortReportSimple55Monthly
For: T N2 APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 732.17 | 21.77 | 96.67 | 21.70 | 96.67 | 21.63 |
| February | 672.00 | 21.63 | 40.33 | 21.60 | 40.33 | 21.57 |
| March | 718.50 | 21.77 | 35.17 | 21.75 | 30.50 | 21.73 |
| April | 546.67 | 22.47 | 48.00 | 22.58 | 2.33 | 22.57 |
| May | 496.83 | 22.60 | 45.83 | 22.72 | 0.00 | 22.72 |
| June | 233.17 | 23.15 | 280.00 | 23.61 | 6.33 | 23.62 |
| July | 147.00 | 23.68 | 568.67 | 23.92 | 85.17 | 23.92 |
| August | 195.83 | 23.67 | 624.00 | 23.89 | 138.67 | 23.89 |
| September | 294.83 | 23.26 | 308.67 | 23.62 | 49.50 | 23.63 |
| October | 496.50 | 23.06 | 170.00 | 23.30 | 43.50 | 23.34 |
| November | 712.83 | 21.96 | 47.33 | 21.91 | 47.33 | 21.87 |
| December | 744.00 | 21.81 | 95.50 | 21.73 | 95.50 | 21.66 |
| Annual Sum or Average | 5990.33 | 22.26 | 2360.17 | 22.64 | 635.83 | 22.63 |
| Minimum of Months | 147.00 | 21.63 | 35.17 | 21.60 | 0.00 | 21.57 |
| Maximum of Months | 744.00 | 23.68 | 624.00 | 23.92 | 138.67 | 23.92 |
Report: ComfortReportSimple55Monthly
For: T S1 APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 458.17 | 22.23 | 41.83 | 22.21 | 29.50 | 22.15 |
| February | 430.50 | 21.97 | 18.00 | 21.96 | 14.67 | 21.93 |
| March | 446.00 | 21.92 | 36.67 | 21.98 | 16.50 | 21.95 |
| April | 350.50 | 22.50 | 48.00 | 22.68 | 0.17 | 22.68 |
| May | 371.67 | 22.52 | 28.17 | 22.62 | 0.00 | 22.62 |
| June | 201.33 | 23.15 | 141.17 | 23.50 | 8.17 | 23.51 |
| July | 131.50 | 23.67 | 370.83 | 23.90 | 74.00 | 23.90 |
| August | 152.33 | 23.71 | 419.67 | 23.89 | 112.17 | 23.89 |
| September | 170.17 | 23.30 | 233.17 | 23.69 | 30.83 | 23.70 |
| October | 259.17 | 23.02 | 161.00 | 23.39 | 18.83 | 23.42 |
| November | 410.50 | 22.38 | 37.00 | 22.43 | 13.50 | 22.39 |
| December | 465.50 | 22.28 | 37.33 | 22.24 | 29.17 | 22.17 |
| Annual Sum or Average | 3847.33 | 22.50 | 1572.83 | 22.87 | 347.50 | 22.88 |
| Minimum of Months | 131.50 | 21.92 | 18.00 | 21.96 | 0.00 | 21.93 |
| Maximum of Months | 465.50 | 23.71 | 419.67 | 23.90 | 112.17 | 23.90 |
Report: ComfortReportSimple55Monthly
For: T S2 APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 457.83 | 22.23 | 42.67 | 22.21 | 29.67 | 22.15 |
| February | 430.17 | 21.97 | 18.33 | 21.95 | 14.83 | 21.93 |
| March | 445.83 | 21.92 | 37.50 | 21.98 | 16.83 | 21.95 |
| April | 352.17 | 22.49 | 47.33 | 22.67 | 0.17 | 22.67 |
| May | 372.83 | 22.51 | 28.33 | 22.62 | 0.00 | 22.62 |
| June | 206.33 | 23.15 | 140.17 | 23.49 | 8.50 | 23.50 |
| July | 135.00 | 23.67 | 369.83 | 23.90 | 75.67 | 23.90 |
| August | 154.00 | 23.71 | 418.33 | 23.89 | 113.17 | 23.88 |
| September | 171.50 | 23.29 | 232.17 | 23.68 | 31.00 | 23.69 |
| October | 260.00 | 23.02 | 160.83 | 23.39 | 18.83 | 23.42 |
| November | 410.67 | 22.38 | 37.33 | 22.43 | 13.50 | 22.39 |
| December | 466.00 | 22.28 | 37.50 | 22.24 | 29.17 | 22.18 |
| Annual Sum or Average | 3862.33 | 22.50 | 1570.33 | 22.87 | 351.33 | 22.88 |
| Minimum of Months | 135.00 | 21.92 | 18.33 | 21.95 | 0.00 | 21.93 |
| Maximum of Months | 466.00 | 23.71 | 418.33 | 23.90 | 113.17 | 23.90 |
Report: ComfortReportSimple55Monthly
For: T CORRIDOR
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 729.50 | 22.66 | 610.33 | 22.70 | 601.33 | 22.71 |
| February | 654.17 | 22.49 | 428.83 | 22.53 | 428.83 | 22.55 |
| March | 734.17 | 22.58 | 581.17 | 22.69 | 575.83 | 22.73 |
| April | 697.17 | 23.81 | 674.67 | 23.85 | 660.67 | 23.86 |
| May | 744.00 | 23.95 | 722.67 | 23.96 | 722.67 | 23.97 |
| June | 720.00 | 24.84 | 720.00 | 24.84 | 720.00 | 24.84 |
| July | 744.00 | 25.34 | 744.00 | 25.34 | 744.00 | 25.34 |
| August | 744.00 | 25.31 | 744.00 | 25.31 | 744.00 | 25.31 |
| September | 720.00 | 24.89 | 720.00 | 24.89 | 720.00 | 24.89 |
| October | 730.83 | 24.57 | 744.00 | 24.57 | 730.83 | 24.57 |
| November | 691.83 | 22.98 | 576.67 | 23.04 | 567.50 | 23.05 |
| December | 687.00 | 22.55 | 479.83 | 22.63 | 456.67 | 22.63 |
| Annual Sum or Average | 8596.67 | 23.85 | 7746.17 | 23.95 | 7672.33 | 23.98 |
| Minimum of Months | 654.17 | 22.49 | 428.83 | 22.53 | 428.83 | 22.55 |
| Maximum of Months | 744.00 | 25.34 | 744.00 | 25.34 | 744.00 | 25.34 |
Report: ComfortReportSimple55Monthly
For: G CORRIDOR
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 657.83 | 22.04 | 97.83 | 21.97 | 73.50 | 21.84 |
| February | 669.17 | 21.97 | 44.00 | 21.85 | 44.00 | 21.74 |
| March | 735.50 | 21.64 | 83.50 | 21.47 | 83.50 | 21.34 |
| April | 587.17 | 22.70 | 148.33 | 22.96 | 94.33 | 23.04 |
| May | 540.00 | 23.00 | 186.50 | 23.36 | 94.33 | 23.47 |
| June | 334.33 | 23.88 | 453.50 | 24.37 | 190.17 | 24.46 |
| July | 457.67 | 25.07 | 706.83 | 25.07 | 433.67 | 25.11 |
| August | 528.00 | 25.10 | 720.50 | 25.10 | 511.83 | 25.13 |
| September | 301.67 | 24.49 | 597.67 | 24.78 | 246.00 | 24.84 |
| October | 302.67 | 24.41 | 518.83 | 24.95 | 213.50 | 25.01 |
| November | 611.00 | 22.90 | 97.83 | 23.04 | 67.67 | 23.11 |
| December | 699.17 | 22.49 | 52.67 | 22.38 | 43.83 | 22.27 |
| Annual Sum or Average | 6424.17 | 23.05 | 3708.00 | 23.62 | 2096.33 | 23.76 |
| Minimum of Months | 301.67 | 21.64 | 44.00 | 21.47 | 43.83 | 21.34 |
| Maximum of Months | 735.50 | 25.10 | 720.50 | 25.10 | 511.83 | 25.13 |
Report: ComfortReportSimple55Monthly
For: M CORRIDOR
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 744.00 | 24.46 | 744.00 | 24.46 | 744.00 | 24.46 |
| February | 662.50 | 24.52 | 672.00 | 24.52 | 662.50 | 24.52 |
| March | 741.83 | 24.40 | 730.50 | 24.41 | 730.50 | 24.41 |
| April | 714.67 | 25.25 | 717.00 | 25.24 | 714.67 | 25.25 |
| May | 744.00 | 25.34 | 744.00 | 25.34 | 744.00 | 25.34 |
| June | 720.00 | 25.61 | 720.00 | 25.61 | 720.00 | 25.61 |
| July | 744.00 | 25.76 | 744.00 | 25.76 | 744.00 | 25.76 |
| August | 744.00 | 25.76 | 744.00 | 25.76 | 744.00 | 25.76 |
| September | 720.00 | 25.65 | 720.00 | 25.65 | 720.00 | 25.65 |
| October | 744.00 | 25.57 | 744.00 | 25.57 | 744.00 | 25.57 |
| November | 682.33 | 24.99 | 720.00 | 24.99 | 682.33 | 24.99 |
| December | 695.50 | 24.63 | 742.67 | 24.65 | 695.50 | 24.64 |
| Annual Sum or Average | 8656.83 | 25.17 | 8742.17 | 25.17 | 8645.50 | 25.17 |
| Minimum of Months | 662.50 | 24.40 | 672.00 | 24.41 | 662.50 | 24.41 |
| Maximum of Months | 744.00 | 25.76 | 744.00 | 25.76 | 744.00 | 25.76 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_GSW
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 515.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 492.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 524.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 6145.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_GNW
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 8760.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_OFFICE
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 140.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 133.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 161.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 140.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 154.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 154.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 140.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 161.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 140.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 147.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 140.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 140.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 1750.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 133.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 161.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_GNE
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 8760.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_GN1
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 8760.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_GN2
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 8760.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_GS1
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 515.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 492.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 524.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 6145.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_GS2
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 515.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 492.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 524.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 6145.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_MSW
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 515.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 492.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 524.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 6145.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_MNW
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 8760.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_MSE
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 515.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 492.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 524.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 6145.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_MNE
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 8760.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_MN1
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 8760.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_MN2
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 8760.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_MS1
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 515.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 492.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 524.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 6145.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_MS2
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 515.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 492.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 524.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 6145.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_TSW
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 515.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 492.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 524.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 6145.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_TNW
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 8760.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_TSE
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 515.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 492.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 524.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 6145.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_TNE
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 8760.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_TN1
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 8760.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_TN2
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 8760.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_TS1
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 515.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 492.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 524.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 6145.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_TS2
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 515.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 492.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 524.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 6145.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_T CORRIDOR
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 8760.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_G CORRIDOR
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 8760.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_M CORRIDOR
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 8760.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: DXReportMonthly
For: SPLIT GSW COOLING COIL
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.260405E+09 | 67158610.08 | 191.14 | 0.252564E+09 | 7840481.57 | 0.00 | 0.31 | 18-JAN-14:30 | 0.00 | 01-JAN-00:10 | 1357.13 | 18-JAN-14:30 | 1357.13 | 18-JAN-14:30 | 89.95 | 20-JAN-12:00 | 342.65 | 18-JAN-14:00 | 0.00 | 01-JAN-00:10 |
| February | 0.100713E+09 | 26243977.93 | 83.92 | 99533851.66 | 1179286.33 | 0.00 | 0.26 | 03-FEB-15:00 | 0.00 | 01-FEB-00:10 | 1087.93 | 03-FEB-15:00 | 1087.93 | 03-FEB-15:00 | 78.80 | 01-FEB-16:10 | 282.20 | 03-FEB-15:00 | 0.00 | 01-FEB-00:10 |
| March | 53896390.30 | 13765161.55 | 47.08 | 48295599.63 | 5600790.67 | 0.00 | 0.19 | 23-MAR-15:10 | 0.00 | 01-MAR-00:10 | 866.31 | 23-MAR-15:10 | 724.48 | 23-MAR-15:10 | 150.12 | 23-MAR-16:10 | 215.67 | 23-MAR-15:10 | 0.00 | 01-MAR-00:10 |
| April | 0.238091E+09 | 60512617.32 | 168.50 | 0.213429E+09 | 24662462.56 | 0.00 | 0.25 | 30-APR-16:15 | 0.00 | 01-APR-00:10 | 1123.65 | 30-APR-16:15 | 1012.56 | 26-APR-14:00 | 127.88 | 11-APR-15:30 | 279.98 | 30-APR-16:15 | 0.00 | 01-APR-00:10 |
| May | 0.143573E+09 | 36696758.48 | 145.39 | 0.131513E+09 | 12059851.10 | 0.00 | 0.20 | 03-MAY-15:10 | 0.00 | 01-MAY-00:10 | 900.04 | 03-MAY-15:10 | 836.97 | 03-MAY-15:10 | 98.09 | 04-MAY-15:20 | 227.01 | 03-MAY-15:10 | 0.00 | 01-MAY-00:10 |
| June | 0.496379E+09 | 0.124197E+09 | 321.78 | 0.410767E+09 | 85611134.11 | 0.00 | 0.29 | 29-JUN-16:30 | 0.00 | 01-JUN-00:10 | 1351.18 | 29-JUN-16:25 | 1070.95 | 29-JUN-16:30 | 285.30 | 29-JUN-16:03 | 328.72 | 29-JUN-16:30 | 0.00 | 01-JUN-00:10 |
| July | 0.150213E+10 | 0.370927E+09 | 660.01 | 0.117549E+10 | 0.326634E+09 | 0.00 | 0.38 | 23-JUL-16:30 | 0.00 | 01-JUL-05:05 | 1785.09 | 23-JUL-16:15 | 1438.27 | 23-JUL-16:30 | 429.54 | 29-JUL-16:10 | 433.54 | 19-JUL-15:10 | 0.00 | 01-JUL-00:10 |
| August | 0.177968E+10 | 0.437215E+09 | 676.06 | 0.137896E+10 | 0.400722E+09 | 0.00 | 0.42 | 17-AUG-15:10 | 0.00 | 01-AUG-05:05 | 1957.35 | 17-AUG-15:10 | 1617.09 | 19-AUG-16:10 | 406.72 | 13-AUG-17:00 | 488.36 | 17-AUG-14:10 | 0.00 | 01-AUG-00:10 |
| September | 0.139077E+10 | 0.349685E+09 | 607.89 | 0.117239E+10 | 0.218379E+09 | 0.00 | 0.57 | 29-SEP-13:30 | 0.00 | 01-SEP-02:20 | 2437.72 | 30-SEP-15:10 | 2437.72 | 30-SEP-15:10 | 400.08 | 22-SEP-12:00 | 696.53 | 29-SEP-13:00 | 0.00 | 01-SEP-00:10 |
| October | 0.167660E+10 | 0.427358E+09 | 576.72 | 0.150722E+10 | 0.169381E+09 | 0.00 | 0.64 | 16-OCT-12:00 | 0.00 | 06-OCT-23:40 | 2681.46 | 16-OCT-12:50 | 2681.46 | 16-OCT-12:50 | 470.89 | 01-OCT-12:00 | 773.54 | 16-OCT-12:00 | 0.00 | 01-OCT-00:10 |
| November | 0.447996E+09 | 0.115488E+09 | 301.47 | 0.432518E+09 | 15477860.18 | 0.00 | 0.39 | 19-NOV-13:00 | 0.00 | 01-NOV-01:20 | 1724.09 | 19-NOV-13:00 | 1724.09 | 19-NOV-13:00 | 145.94 | 10-NOV-13:20 | 449.40 | 19-NOV-13:00 | 0.00 | 01-NOV-00:10 |
| December | 0.393129E+09 | 0.102191E+09 | 226.53 | 0.389987E+09 | 3141342.01 | 0.00 | 0.35 | 19-DEC-13:00 | 0.00 | 01-DEC-00:10 | 1476.11 | 19-DEC-13:00 | 1476.11 | 19-DEC-13:00 | 95.99 | 07-DEC-15:30 | 387.69 | 19-DEC-13:00 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.848336E+10 | 0.213144E+10 | 4006.48 | 0.721267E+10 | 0.127069E+10 | 0.00 | ||||||||||||||
| Minimum of Months | 53896390.30 | 13765161.55 | 47.08 | 48295599.63 | 1179286.33 | 0.00 | 0.19 | 0.00 | 866.31 | 724.48 | 78.80 | 215.67 | 0.00 | |||||||
| Maximum of Months | 0.177968E+10 | 0.437215E+09 | 676.06 | 0.150722E+10 | 0.400722E+09 | 0.00 | 0.64 | 0.00 | 2681.46 | 2681.46 | 470.89 | 773.54 | 0.00 |
Report: DXReportMonthly
For: SPLIT GNW COOLING COIL
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 7570888.49 | 1989251.14 | 13.67 | 7502947.71 | 67940.78 | 0.00 | 0.09 | 18-JAN-14:20 | 0.00 | 01-JAN-00:10 | 348.44 | 18-JAN-14:20 | 348.44 | 18-JAN-14:20 | 10.82 | 17-JAN-14:00 | 91.07 | 18-JAN-14:20 | 0.00 | 01-JAN-00:10 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
| April | 54754696.07 | 13993201.70 | 50.07 | 48283637.52 | 6471058.55 | 0.00 | 0.19 | 30-APR-16:30 | 0.00 | 01-APR-00:10 | 764.72 | 30-APR-16:30 | 683.19 | 30-APR-16:30 | 84.12 | 26-APR-17:00 | 192.29 | 30-APR-16:30 | 0.00 | 01-APR-00:10 |
| May | 83308055.14 | 21300866.57 | 104.86 | 75611594.72 | 7696460.42 | 0.00 | 0.18 | 03-MAY-16:05 | 0.00 | 01-MAY-00:10 | 714.58 | 03-MAY-16:05 | 665.44 | 03-MAY-16:05 | 88.59 | 04-MAY-15:30 | 181.01 | 03-MAY-16:05 | 0.00 | 01-MAY-00:10 |
| June | 0.490103E+09 | 0.122385E+09 | 332.95 | 0.403150E+09 | 86952570.40 | 0.00 | 0.33 | 29-JUN-17:00 | 0.00 | 01-JUN-00:10 | 1401.20 | 29-JUN-17:00 | 1106.35 | 29-JUN-17:10 | 302.38 | 29-JUN-16:13 | 338.80 | 29-JUN-17:00 | 0.00 | 01-JUN-00:10 |
| July | 0.140540E+10 | 0.346665E+09 | 662.48 | 0.109276E+10 | 0.312637E+09 | 0.00 | 0.41 | 19-JUL-16:25 | 0.00 | 01-JUL-05:05 | 1761.89 | 19-JUL-16:25 | 1401.91 | 19-JUL-16:30 | 394.62 | 29-JUL-16:20 | 425.62 | 18-JUL-16:03 | 0.00 | 01-JUL-00:10 |
| August | 0.136645E+10 | 0.335992E+09 | 623.55 | 0.103585E+10 | 0.330597E+09 | 0.00 | 0.40 | 17-AUG-16:05 | 0.00 | 01-AUG-05:05 | 1721.36 | 17-AUG-16:05 | 1349.86 | 17-AUG-16:05 | 374.50 | 17-AUG-15:10 | 418.30 | 18-AUG-15:10 | 0.00 | 01-AUG-00:10 |
| September | 0.701614E+09 | 0.178474E+09 | 444.39 | 0.583334E+09 | 0.118281E+09 | 0.00 | 0.46 | 29-SEP-15:10 | 0.00 | 01-SEP-00:10 | 1786.18 | 29-SEP-16:04 | 1786.18 | 29-SEP-16:04 | 382.52 | 22-SEP-12:00 | 503.96 | 29-SEP-15:10 | 0.00 | 01-SEP-00:10 |
| October | 0.822472E+09 | 0.212000E+09 | 427.99 | 0.709499E+09 | 0.112973E+09 | 0.00 | 0.47 | 16-OCT-11:00 | 0.00 | 06-OCT-20:00 | 1758.11 | 16-OCT-12:00 | 1758.11 | 16-OCT-12:00 | 361.80 | 01-OCT-15:10 | 524.03 | 16-OCT-11:00 | 0.00 | 01-OCT-00:10 |
| November | 5219941.53 | 1401548.11 | 9.33 | 5218523.68 | 1417.85 | 0.00 | 0.10 | 19-NOV-13:00 | 0.00 | 01-NOV-00:10 | 373.01 | 19-NOV-13:00 | 373.01 | 19-NOV-13:00 | 1.20 | 19-NOV-15:30 | 101.84 | 19-NOV-13:00 | 0.00 | 01-NOV-00:10 |
| December | 2398259.81 | 640199.03 | 6.25 | 2398259.81 | 0.00 | 0.00 | 0.07 | 05-DEC-15:10 | 0.00 | 01-DEC-00:10 | 255.68 | 05-DEC-15:10 | 255.68 | 05-DEC-15:10 | 0.00 | 05-DEC-15:40 | 68.13 | 05-DEC-15:10 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.493929E+10 | 0.123484E+10 | 2675.54 | 0.396361E+10 | 0.975677E+09 | 0.00 | ||||||||||||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Maximum of Months | 0.140540E+10 | 0.346665E+09 | 662.48 | 0.109276E+10 | 0.330597E+09 | 0.00 | 0.47 | 0.00 | 1786.18 | 1786.18 | 394.62 | 524.03 | 0.00 |
Report: DXReportMonthly
For: SPLIT OFFICE COOLING COIL
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.608954E+09 | 0.154495E+09 | 155.39 | 0.585487E+09 | 23467347.96 | 0.00 | 1.00 | 17-JAN-09:02 | 0.00 | 01-JAN-00:10 | 6084.33 | 17-JAN-09:02 | 5939.13 | 18-JAN-09:02 | 736.64 | 26-JAN-09:02 | 1328.41 | 17-JAN-09:02 | 0.00 | 01-JAN-00:10 |
| February | 0.392005E+09 | 0.100389E+09 | 128.04 | 0.376540E+09 | 15465431.81 | 0.00 | 1.00 | 01-FEB-09:02 | 0.00 | 01-FEB-00:10 | 5920.69 | 02-FEB-09:02 | 5806.30 | 01-FEB-09:02 | 231.11 | 16-FEB-09:05 | 1315.37 | 02-FEB-09:02 | 0.00 | 01-FEB-00:10 |
| March | 0.290178E+09 | 73539514.69 | 122.53 | 0.258682E+09 | 31495320.59 | 0.00 | 0.60 | 23-MAR-08:63 | 0.00 | 01-MAR-00:10 | 3321.40 | 23-MAR-08:63 | 3111.85 | 23-MAR-08:63 | 352.97 | 24-MAR-08:65 | 787.62 | 23-MAR-08:63 | 0.00 | 01-MAR-00:10 |
| April | 0.627004E+09 | 0.157358E+09 | 159.44 | 0.562862E+09 | 64141992.27 | 0.00 | 1.00 | 13-APR-08:62 | 0.00 | 01-APR-00:10 | 6210.66 | 27-APR-08:62 | 5753.08 | 13-APR-08:62 | 1252.20 | 27-APR-08:62 | 1334.63 | 27-APR-08:62 | 0.00 | 01-APR-00:10 |
| May | 0.618533E+09 | 0.155766E+09 | 176.67 | 0.563826E+09 | 54706842.10 | 0.00 | 1.00 | 01-MAY-08:62 | 0.00 | 01-MAY-00:10 | 6206.60 | 03-MAY-08:62 | 5745.62 | 02-MAY-08:62 | 1163.09 | 03-MAY-08:62 | 1334.47 | 03-MAY-08:62 | 0.00 | 01-MAY-00:10 |
| June | 0.935915E+09 | 0.230079E+09 | 181.92 | 0.792960E+09 | 0.142955E+09 | 0.00 | 1.00 | 02-JUN-08:62 | 0.00 | 01-JUN-00:10 | 6328.98 | 28-JUN-08:62 | 5577.26 | 23-JUN-08:62 | 1786.95 | 28-JUN-08:62 | 1337.82 | 28-JUN-08:62 | 0.00 | 01-JUN-00:10 |
| July | 0.139226E+10 | 0.335532E+09 | 179.02 | 0.113102E+10 | 0.261246E+09 | 0.00 | 1.00 | 03-JUL-08:62 | 0.00 | 01-JUL-00:10 | 6376.02 | 28-JUL-08:62 | 5443.47 | 10-JUL-08:62 | 1959.17 | 20-JUL-08:62 | 1338.36 | 28-JUL-08:62 | 0.00 | 01-JUL-00:10 |
| August | 0.176969E+10 | 0.423499E+09 | 207.35 | 0.143319E+10 | 0.336503E+09 | 0.00 | 1.00 | 01-AUG-08:62 | 0.00 | 01-AUG-00:10 | 6419.17 | 07-AUG-08:62 | 5409.92 | 22-AUG-08:62 | 2070.43 | 07-AUG-08:04 | 1338.48 | 07-AUG-08:62 | 0.00 | 01-AUG-00:10 |
| September | 0.132283E+10 | 0.323781E+09 | 180.90 | 0.112732E+10 | 0.195509E+09 | 0.00 | 1.00 | 01-SEP-08:62 | 0.00 | 01-SEP-00:10 | 6441.40 | 22-SEP-08:62 | 5761.37 | 29-SEP-08:62 | 2150.65 | 22-SEP-08:62 | 1398.94 | 29-SEP-08:62 | 0.00 | 01-SEP-00:10 |
| October | 0.156966E+10 | 0.388494E+09 | 196.63 | 0.144071E+10 | 0.128949E+09 | 0.00 | 1.00 | 02-OCT-07:03 | 0.00 | 01-OCT-00:10 | 6449.96 | 02-OCT-07:03 | 5919.24 | 11-OCT-08:62 | 2081.59 | 05-OCT-08:62 | 1364.31 | 16-OCT-08:62 | 0.00 | 01-OCT-00:10 |
| November | 0.801851E+09 | 0.202494E+09 | 160.70 | 0.767437E+09 | 34414788.79 | 0.00 | 1.00 | 01-NOV-08:62 | 0.00 | 01-NOV-00:10 | 6179.96 | 10-NOV-09:02 | 5865.26 | 22-NOV-09:02 | 1071.02 | 10-NOV-09:02 | 1333.38 | 10-NOV-09:02 | 0.00 | 01-NOV-00:10 |
| December | 0.710002E+09 | 0.181098E+09 | 158.19 | 0.700033E+09 | 9969644.00 | 0.00 | 1.00 | 04-DEC-09:02 | 0.00 | 01-DEC-00:10 | 5851.94 | 07-DEC-09:02 | 5851.94 | 07-DEC-09:02 | 497.27 | 08-DEC-09:03 | 1309.66 | 05-DEC-09:02 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.110389E+11 | 0.272652E+10 | 2006.78 | 0.974006E+10 | 0.129882E+10 | 0.00 | ||||||||||||||
| Minimum of Months | 0.290178E+09 | 73539514.69 | 122.53 | 0.258682E+09 | 9969644.00 | 0.00 | 0.60 | 0.00 | 3321.40 | 3111.85 | 231.11 | 787.62 | 0.00 | |||||||
| Maximum of Months | 0.176969E+10 | 0.423499E+09 | 207.35 | 0.144071E+10 | 0.336503E+09 | 0.00 | 1.00 | 0.00 | 6449.96 | 5939.13 | 2150.65 | 1398.94 | 0.00 |
Report: DXReportMonthly
For: SPLIT GNE COOLING COIL
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 9689585.17 | 2541333.49 | 18.89 | 9532936.39 | 156648.78 | 0.00 | 0.09 | 18-JAN-13:00 | 0.00 | 01-JAN-00:10 | 343.33 | 18-JAN-13:00 | 343.33 | 18-JAN-13:00 | 18.34 | 20-JAN-12:00 | 92.30 | 18-JAN-13:00 | 0.00 | 01-JAN-00:10 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
| April | 48957503.11 | 12556140.56 | 46.05 | 43522046.54 | 5435456.57 | 0.00 | 0.18 | 30-APR-11:00 | 0.00 | 01-APR-00:10 | 695.39 | 30-APR-11:00 | 650.19 | 30-APR-11:00 | 86.25 | 26-APR-11:00 | 181.77 | 30-APR-11:00 | 0.00 | 01-APR-00:10 |
| May | 69711353.56 | 17799288.33 | 88.00 | 63371799.74 | 6339553.83 | 0.00 | 0.19 | 04-MAY-12:00 | 0.00 | 01-MAY-00:10 | 734.87 | 04-MAY-12:00 | 673.15 | 04-MAY-12:00 | 102.28 | 03-MAY-10:00 | 185.56 | 04-MAY-12:00 | 0.00 | 01-MAY-00:10 |
| June | 0.436866E+09 | 0.109060E+09 | 287.07 | 0.360083E+09 | 76782344.76 | 0.00 | 0.29 | 30-JUN-10:00 | 0.00 | 01-JUN-00:10 | 1144.68 | 30-JUN-10:00 | 897.35 | 30-JUN-10:00 | 261.48 | 28-JUN-11:00 | 278.66 | 30-JUN-10:00 | 0.00 | 01-JUN-00:10 |
| July | 0.134393E+10 | 0.331048E+09 | 633.33 | 0.104348E+10 | 0.300455E+09 | 0.00 | 0.40 | 19-JUL-10:40 | 0.00 | 01-JUL-01:10 | 1618.05 | 19-JUL-10:10 | 1293.43 | 19-JUL-11:00 | 390.72 | 19-JUL-09:00 | 410.44 | 19-JUL-10:50 | 0.00 | 01-JUL-00:10 |
| August | 0.134350E+10 | 0.329709E+09 | 614.71 | 0.101870E+10 | 0.324795E+09 | 0.00 | 0.40 | 14-AUG-11:00 | 0.00 | 01-AUG-05:05 | 1589.25 | 14-AUG-10:40 | 1235.69 | 14-AUG-11:00 | 406.40 | 18-AUG-09:30 | 405.67 | 14-AUG-11:00 | 0.00 | 01-AUG-00:10 |
| September | 0.623292E+09 | 0.158742E+09 | 384.07 | 0.520448E+09 | 0.102845E+09 | 0.00 | 0.48 | 29-SEP-13:00 | 0.00 | 01-SEP-00:10 | 1686.59 | 29-SEP-13:00 | 1686.59 | 29-SEP-13:00 | 377.08 | 22-SEP-12:00 | 499.27 | 29-SEP-13:00 | 0.00 | 01-SEP-00:10 |
| October | 0.793593E+09 | 0.204858E+09 | 411.60 | 0.687496E+09 | 0.106097E+09 | 0.00 | 0.57 | 16-OCT-11:00 | 0.00 | 06-OCT-20:00 | 1984.95 | 16-OCT-11:00 | 1984.95 | 16-OCT-11:00 | 369.04 | 01-OCT-10:40 | 589.88 | 16-OCT-11:00 | 0.00 | 01-OCT-00:10 |
| November | 5555568.99 | 1498036.26 | 6.33 | 5555568.99 | -0.0 | 0.00 | 0.11 | 19-NOV-13:00 | 0.00 | 01-NOV-00:10 | 395.51 | 19-NOV-13:00 | 395.51 | 19-NOV-13:00 | 0.00 | 19-NOV-13:10 | 107.78 | 19-NOV-13:00 | 0.00 | 01-NOV-00:10 |
| December | 2240371.32 | 603257.21 | 7.67 | 2240371.32 | 0.00 | 0.00 | 0.05 | 05-DEC-15:00 | 0.00 | 01-DEC-00:10 | 165.90 | 05-DEC-15:00 | 165.90 | 05-DEC-15:00 | 0.00 | 05-DEC-15:20 | 44.56 | 05-DEC-15:00 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.467734E+10 | 0.116842E+10 | 2497.72 | 0.375443E+10 | 0.922906E+09 | 0.00 | ||||||||||||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | -0.0 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Maximum of Months | 0.134393E+10 | 0.331048E+09 | 633.33 | 0.104348E+10 | 0.324795E+09 | 0.00 | 0.57 | 0.00 | 1984.95 | 1984.95 | 406.40 | 589.88 | 0.00 |
Report: DXReportMonthly
For: SPLIT GN1 COOLING COIL
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 13653158.95 | 3566679.83 | 26.39 | 13304281.64 | 348877.31 | 0.00 | 0.11 | 18-JAN-13:00 | 0.00 | 01-JAN-00:10 | 362.19 | 18-JAN-13:00 | 362.19 | 18-JAN-13:00 | 26.84 | 17-JAN-14:00 | 97.19 | 18-JAN-13:00 | 0.00 | 01-JAN-00:10 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
| April | 31497689.90 | 8103877.20 | 39.83 | 27843271.65 | 3654418.25 | 0.00 | 0.13 | 26-APR-13:00 | 0.00 | 01-APR-00:10 | 469.36 | 26-APR-13:00 | 424.57 | 30-APR-11:00 | 60.30 | 26-APR-11:40 | 124.74 | 26-APR-13:00 | 0.00 | 01-APR-00:10 |
| May | 61219721.24 | 15643771.78 | 100.54 | 54863297.49 | 6356423.75 | 0.00 | 0.16 | 04-MAY-12:00 | 0.00 | 01-MAY-00:10 | 575.79 | 04-MAY-12:00 | 523.30 | 04-MAY-12:00 | 70.37 | 04-MAY-15:20 | 145.94 | 04-MAY-12:00 | 0.00 | 01-MAY-00:10 |
| June | 0.430133E+09 | 0.107695E+09 | 385.13 | 0.351052E+09 | 79081783.66 | 0.00 | 0.26 | 29-JUN-17:10 | 0.00 | 01-JUN-00:10 | 977.46 | 29-JUN-17:10 | 754.01 | 29-JUN-17:10 | 225.30 | 28-JUN-11:00 | 237.97 | 29-JUN-17:10 | 0.00 | 01-JUN-00:10 |
| July | 0.122978E+10 | 0.304084E+09 | 690.99 | 0.944995E+09 | 0.284782E+09 | 0.00 | 0.33 | 18-JUL-16:07 | 0.00 | 01-JUL-05:05 | 1243.22 | 18-JUL-16:07 | 961.76 | 18-JUL-16:07 | 293.31 | 29-JUL-16:10 | 312.93 | 31-JUL-13:00 | 0.00 | 01-JUL-00:10 |
| August | 0.122093E+10 | 0.300876E+09 | 682.41 | 0.914311E+09 | 0.306622E+09 | 0.00 | 0.33 | 17-AUG-14:10 | 0.00 | 01-AUG-05:05 | 1223.72 | 17-AUG-14:10 | 934.86 | 18-AUG-15:10 | 306.15 | 18-AUG-11:00 | 314.51 | 18-AUG-12:00 | 0.00 | 01-AUG-00:10 |
| September | 0.657464E+09 | 0.167048E+09 | 543.09 | 0.538393E+09 | 0.119071E+09 | 0.00 | 0.41 | 29-SEP-13:00 | 0.00 | 01-SEP-01:40 | 1347.49 | 29-SEP-13:00 | 1347.49 | 29-SEP-13:00 | 363.88 | 22-SEP-12:00 | 403.31 | 29-SEP-13:00 | 0.00 | 01-SEP-00:10 |
| October | 0.812771E+09 | 0.208800E+09 | 500.20 | 0.696410E+09 | 0.116361E+09 | 0.00 | 0.47 | 16-OCT-11:00 | 0.00 | 07-OCT-01:50 | 1502.28 | 16-OCT-11:00 | 1502.28 | 16-OCT-11:00 | 342.02 | 01-OCT-10:30 | 454.11 | 16-OCT-11:00 | 0.00 | 01-OCT-00:10 |
| November | 6340264.20 | 1706612.45 | 14.17 | 6329512.24 | 10751.96 | 0.00 | 0.11 | 19-NOV-13:00 | 0.00 | 01-NOV-00:10 | 360.60 | 19-NOV-13:00 | 360.60 | 19-NOV-13:00 | 4.47 | 01-NOV-18:50 | 98.33 | 19-NOV-13:00 | 0.00 | 01-NOV-00:10 |
| December | 3061194.97 | 818025.31 | 10.50 | 3061194.97 | 0.00 | 0.00 | 0.06 | 05-DEC-15:00 | 0.00 | 01-DEC-00:10 | 186.25 | 05-DEC-15:00 | 186.25 | 05-DEC-15:00 | 0.00 | 05-DEC-13:40 | 49.95 | 05-DEC-15:00 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.446685E+10 | 0.111834E+10 | 2993.24 | 0.355056E+10 | 0.916288E+09 | 0.00 | ||||||||||||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Maximum of Months | 0.122978E+10 | 0.304084E+09 | 690.99 | 0.944995E+09 | 0.306622E+09 | 0.00 | 0.47 | 0.00 | 1502.28 | 1502.28 | 363.88 | 454.11 | 0.00 |
Report: DXReportMonthly
For: SPLIT GN2 COOLING COIL
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 14034592.34 | 3665972.25 | 26.89 | 13680921.83 | 353670.51 | 0.00 | 0.11 | 18-JAN-13:00 | 0.00 | 01-JAN-00:10 | 364.10 | 18-JAN-13:00 | 364.10 | 18-JAN-13:00 | 26.80 | 17-JAN-14:00 | 97.69 | 18-JAN-13:00 | 0.00 | 01-JAN-00:10 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
| April | 31330021.59 | 8061623.23 | 39.17 | 27707754.07 | 3622267.52 | 0.00 | 0.13 | 26-APR-13:00 | 0.00 | 01-APR-00:10 | 468.57 | 26-APR-13:00 | 427.60 | 30-APR-11:00 | 60.32 | 26-APR-11:40 | 124.53 | 26-APR-13:00 | 0.00 | 01-APR-00:10 |
| May | 60445941.10 | 15444517.24 | 98.81 | 54179673.51 | 6266267.59 | 0.00 | 0.16 | 04-MAY-12:00 | 0.00 | 01-MAY-00:10 | 578.87 | 04-MAY-12:00 | 526.19 | 04-MAY-12:00 | 70.97 | 03-MAY-10:00 | 146.70 | 04-MAY-12:00 | 0.00 | 01-MAY-00:10 |
| June | 0.425410E+09 | 0.106506E+09 | 380.12 | 0.347174E+09 | 78236016.62 | 0.00 | 0.26 | 29-JUN-17:10 | 0.00 | 01-JUN-00:10 | 966.77 | 29-JUN-17:10 | 745.26 | 29-JUN-17:10 | 225.67 | 28-JUN-11:00 | 235.43 | 29-JUN-17:10 | 0.00 | 01-JUN-00:10 |
| July | 0.122588E+10 | 0.303102E+09 | 690.53 | 0.941953E+09 | 0.283932E+09 | 0.00 | 0.33 | 18-JUL-16:07 | 0.00 | 01-JUL-05:05 | 1239.18 | 18-JUL-16:07 | 958.62 | 18-JUL-16:07 | 293.50 | 19-JUL-09:10 | 314.22 | 19-JUL-12:00 | 0.00 | 01-JUL-00:10 |
| August | 0.121934E+10 | 0.300457E+09 | 680.88 | 0.913175E+09 | 0.306163E+09 | 0.00 | 0.33 | 18-AUG-12:00 | 0.00 | 01-AUG-05:05 | 1230.10 | 18-AUG-12:00 | 934.84 | 17-AUG-14:10 | 307.33 | 18-AUG-11:00 | 316.21 | 18-AUG-12:00 | 0.00 | 01-AUG-00:10 |
| September | 0.650092E+09 | 0.165195E+09 | 537.75 | 0.532455E+09 | 0.117636E+09 | 0.00 | 0.41 | 29-SEP-13:00 | 0.00 | 01-SEP-01:40 | 1348.58 | 29-SEP-13:00 | 1348.58 | 29-SEP-13:00 | 362.93 | 22-SEP-12:00 | 403.57 | 29-SEP-13:00 | 0.00 | 01-SEP-00:10 |
| October | 0.811348E+09 | 0.208449E+09 | 498.80 | 0.695343E+09 | 0.116005E+09 | 0.00 | 0.47 | 16-OCT-11:00 | 0.00 | 07-OCT-01:50 | 1508.51 | 16-OCT-11:00 | 1508.51 | 16-OCT-11:00 | 341.97 | 01-OCT-10:30 | 455.80 | 16-OCT-11:00 | 0.00 | 01-OCT-00:10 |
| November | 6342989.95 | 1707536.25 | 14.00 | 6332377.84 | 10612.10 | 0.00 | 0.11 | 19-NOV-13:00 | 0.00 | 01-NOV-00:10 | 360.27 | 19-NOV-13:00 | 360.27 | 19-NOV-13:00 | 4.37 | 01-NOV-18:50 | 98.24 | 19-NOV-13:00 | 0.00 | 01-NOV-00:10 |
| December | 3294954.96 | 880624.43 | 11.50 | 3294954.96 | -0.0 | 0.00 | 0.06 | 05-DEC-15:00 | 0.00 | 01-DEC-00:10 | 189.56 | 05-DEC-15:00 | 189.56 | 05-DEC-15:00 | 0.00 | 05-DEC-13:40 | 50.83 | 05-DEC-15:00 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.444752E+10 | 0.111347E+10 | 2978.46 | 0.353530E+10 | 0.912225E+09 | 0.00 | ||||||||||||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | -0.0 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Maximum of Months | 0.122588E+10 | 0.303102E+09 | 690.53 | 0.941953E+09 | 0.306163E+09 | 0.00 | 0.47 | 0.00 | 1508.51 | 1508.51 | 362.93 | 455.80 | 0.00 |
Report: DXReportMonthly
For: SPLIT GS1 COOLING COIL
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.444219E+09 | 0.114203E+09 | 331.13 | 0.429163E+09 | 15055479.08 | 0.00 | 0.34 | 18-JAN-13:30 | 0.00 | 01-JAN-00:10 | 1340.68 | 18-JAN-13:40 | 1340.68 | 18-JAN-13:40 | 107.35 | 20-JAN-17:30 | 343.81 | 18-JAN-13:00 | 0.00 | 01-JAN-00:10 |
| February | 0.169677E+09 | 44077611.41 | 145.51 | 0.167887E+09 | 1789899.27 | 0.00 | 0.30 | 01-FEB-12:00 | 0.00 | 01-FEB-00:10 | 1162.90 | 01-FEB-12:00 | 1162.90 | 01-FEB-12:00 | 81.31 | 01-FEB-17:13 | 304.16 | 01-FEB-12:00 | 0.00 | 01-FEB-00:10 |
| March | 65614725.94 | 16758104.43 | 60.89 | 59110366.29 | 6504359.64 | 0.00 | 0.18 | 23-MAR-14:00 | 0.00 | 01-MAR-00:10 | 738.29 | 23-MAR-14:00 | 673.03 | 11-MAR-13:50 | 109.41 | 23-MAR-15:10 | 184.48 | 23-MAR-14:00 | 0.00 | 01-MAR-00:10 |
| April | 0.229314E+09 | 58343847.75 | 201.91 | 0.205148E+09 | 24166259.44 | 0.00 | 0.24 | 26-APR-13:00 | 0.00 | 01-APR-00:10 | 954.15 | 26-APR-13:00 | 875.48 | 26-APR-13:00 | 123.47 | 08-APR-12:00 | 250.50 | 26-APR-13:00 | 0.00 | 01-APR-00:10 |
| May | 0.128816E+09 | 32905478.47 | 163.65 | 0.116958E+09 | 11858141.98 | 0.00 | 0.21 | 04-MAY-12:00 | 0.00 | 01-MAY-00:10 | 812.70 | 04-MAY-12:00 | 749.54 | 04-MAY-12:00 | 91.20 | 05-MAY-19:40 | 205.00 | 04-MAY-12:00 | 0.00 | 01-MAY-00:10 |
| June | 0.438788E+09 | 0.110025E+09 | 367.55 | 0.360638E+09 | 78149893.60 | 0.00 | 0.22 | 29-JUN-16:03 | 0.00 | 01-JUN-00:10 | 922.31 | 29-JUN-16:03 | 713.90 | 29-JUN-16:10 | 234.78 | 28-JUN-11:00 | 225.85 | 29-JUN-16:03 | 0.00 | 01-JUN-00:10 |
| July | 0.133607E+10 | 0.330584E+09 | 691.19 | 0.103478E+10 | 0.301283E+09 | 0.00 | 0.35 | 31-JUL-13:00 | 0.00 | 01-JUL-05:05 | 1445.38 | 31-JUL-13:00 | 1137.84 | 31-JUL-13:00 | 333.54 | 29-JUL-12:00 | 372.16 | 31-JUL-13:00 | 0.00 | 01-JUL-00:10 |
| August | 0.166407E+10 | 0.409485E+09 | 713.46 | 0.128007E+10 | 0.383996E+09 | 0.00 | 0.38 | 19-AUG-13:00 | 0.00 | 01-AUG-05:05 | 1569.59 | 19-AUG-13:00 | 1245.06 | 19-AUG-13:40 | 347.45 | 19-AUG-11:40 | 400.14 | 17-AUG-14:00 | 0.00 | 01-AUG-00:10 |
| September | 0.140293E+10 | 0.352369E+09 | 655.19 | 0.117508E+10 | 0.227859E+09 | 0.00 | 0.56 | 29-SEP-13:00 | 0.00 | 01-SEP-06:40 | 2083.46 | 29-SEP-13:00 | 2083.46 | 29-SEP-13:00 | 380.22 | 22-SEP-12:00 | 608.49 | 29-SEP-13:00 | 0.00 | 01-SEP-00:10 |
| October | 0.176171E+10 | 0.447727E+09 | 659.96 | 0.158313E+10 | 0.178578E+09 | 0.00 | 0.66 | 16-OCT-12:00 | 0.00 | 07-OCT-02:00 | 2422.75 | 16-OCT-12:00 | 2422.75 | 16-OCT-12:00 | 448.11 | 01-OCT-11:30 | 698.87 | 16-OCT-12:00 | 0.00 | 01-OCT-00:10 |
| November | 0.668060E+09 | 0.171604E+09 | 469.72 | 0.641776E+09 | 26283994.66 | 0.00 | 0.44 | 19-NOV-13:00 | 0.00 | 02-NOV-05:13 | 1721.62 | 19-NOV-13:00 | 1721.62 | 19-NOV-13:00 | 145.75 | 10-NOV-13:00 | 445.42 | 19-NOV-13:00 | 0.00 | 01-NOV-00:10 |
| December | 0.618609E+09 | 0.159939E+09 | 389.14 | 0.610596E+09 | 8012993.74 | 0.00 | 0.42 | 19-DEC-13:00 | 0.00 | 01-DEC-00:10 | 1570.98 | 19-DEC-13:00 | 1570.98 | 19-DEC-13:00 | 88.58 | 07-DEC-17:30 | 408.35 | 19-DEC-13:00 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.892787E+10 | 0.224802E+10 | 4849.30 | 0.766434E+10 | 0.126354E+10 | 0.00 | ||||||||||||||
| Minimum of Months | 65614725.94 | 16758104.43 | 60.89 | 59110366.29 | 1789899.27 | 0.00 | 0.18 | 0.00 | 738.29 | 673.03 | 81.31 | 184.48 | 0.00 | |||||||
| Maximum of Months | 0.176171E+10 | 0.447727E+09 | 713.46 | 0.158313E+10 | 0.383996E+09 | 0.00 | 0.66 | 0.00 | 2422.75 | 2422.75 | 448.11 | 698.87 | 0.00 |
Report: DXReportMonthly
For: SPLIT GS2 COOLING COIL
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.480644E+09 | 0.123471E+09 | 344.02 | 0.464240E+09 | 16403985.85 | 0.00 | 0.35 | 18-JAN-13:30 | 0.00 | 01-JAN-00:10 | 1379.45 | 18-JAN-13:40 | 1379.45 | 18-JAN-13:40 | 111.81 | 20-JAN-17:30 | 353.40 | 18-JAN-13:00 | 0.00 | 01-JAN-00:10 |
| February | 0.185735E+09 | 48220188.86 | 159.14 | 0.183635E+09 | 2099887.32 | 0.00 | 0.31 | 01-FEB-12:00 | 0.00 | 01-FEB-00:10 | 1197.38 | 01-FEB-12:00 | 1197.38 | 01-FEB-12:00 | 84.07 | 01-FEB-17:13 | 312.86 | 01-FEB-12:00 | 0.00 | 01-FEB-00:10 |
| March | 76366977.69 | 19481677.19 | 65.55 | 68758289.34 | 7608688.35 | 0.00 | 0.20 | 23-MAR-14:00 | 0.00 | 01-MAR-00:10 | 793.64 | 23-MAR-14:00 | 710.57 | 11-MAR-13:50 | 116.13 | 23-MAR-15:10 | 198.03 | 23-MAR-14:00 | 0.00 | 01-MAR-00:10 |
| April | 0.256398E+09 | 65204980.44 | 220.02 | 0.229718E+09 | 26679765.12 | 0.00 | 0.25 | 26-APR-13:00 | 0.00 | 01-APR-00:10 | 994.46 | 26-APR-13:00 | 914.29 | 26-APR-13:00 | 128.71 | 08-APR-12:00 | 260.82 | 26-APR-13:00 | 0.00 | 01-APR-00:10 |
| May | 0.150755E+09 | 38488448.06 | 185.89 | 0.136683E+09 | 14071265.87 | 0.00 | 0.21 | 04-MAY-12:00 | 0.00 | 01-MAY-00:20 | 854.11 | 04-MAY-12:00 | 788.99 | 04-MAY-12:00 | 96.01 | 03-MAY-10:00 | 215.20 | 04-MAY-12:00 | 0.00 | 01-MAY-00:10 |
| June | 0.492923E+09 | 0.123577E+09 | 396.84 | 0.406524E+09 | 86398365.65 | 0.00 | 0.23 | 29-JUN-16:03 | 0.00 | 01-JUN-00:10 | 959.18 | 29-JUN-16:03 | 749.53 | 27-JUN-13:00 | 244.25 | 28-JUN-11:00 | 234.75 | 29-JUN-16:03 | 0.00 | 01-JUN-00:10 |
| July | 0.146990E+10 | 0.363453E+09 | 704.30 | 0.114436E+10 | 0.325542E+09 | 0.00 | 0.36 | 31-JUL-13:00 | 0.00 | 01-JUL-05:05 | 1507.70 | 31-JUL-13:00 | 1194.55 | 31-JUL-13:00 | 346.38 | 29-JUL-12:00 | 387.77 | 31-JUL-13:00 | 0.00 | 01-JUL-00:10 |
| August | 0.181863E+10 | 0.447194E+09 | 725.89 | 0.140645E+10 | 0.412178E+09 | 0.00 | 0.40 | 19-AUG-13:00 | 0.00 | 02-AUG-05:05 | 1656.45 | 19-AUG-13:00 | 1324.40 | 19-AUG-13:50 | 358.95 | 19-AUG-09:10 | 417.10 | 19-AUG-13:00 | 0.00 | 01-AUG-00:10 |
| September | 0.151798E+10 | 0.380769E+09 | 669.58 | 0.127414E+10 | 0.243845E+09 | 0.00 | 0.57 | 29-SEP-13:00 | 0.00 | 01-SEP-06:40 | 2130.54 | 29-SEP-13:00 | 2130.54 | 29-SEP-13:00 | 386.89 | 22-SEP-12:00 | 621.44 | 29-SEP-13:00 | 0.00 | 01-SEP-00:10 |
| October | 0.191369E+10 | 0.485332E+09 | 677.03 | 0.172216E+10 | 0.191526E+09 | 0.00 | 0.68 | 16-OCT-12:00 | 0.00 | 07-OCT-05:05 | 2522.44 | 16-OCT-12:00 | 2522.44 | 16-OCT-12:00 | 462.27 | 01-OCT-11:00 | 725.23 | 16-OCT-12:00 | 0.00 | 01-OCT-00:10 |
| November | 0.719682E+09 | 0.184733E+09 | 484.80 | 0.691111E+09 | 28571524.35 | 0.00 | 0.45 | 19-NOV-13:00 | 0.00 | 02-NOV-05:30 | 1784.41 | 19-NOV-13:00 | 1784.41 | 19-NOV-13:00 | 149.02 | 10-NOV-13:00 | 460.79 | 19-NOV-13:00 | 0.00 | 01-NOV-00:10 |
| December | 0.658168E+09 | 0.170060E+09 | 401.97 | 0.649397E+09 | 8770963.27 | 0.00 | 0.42 | 19-DEC-13:00 | 0.00 | 01-DEC-00:10 | 1609.57 | 19-DEC-13:00 | 1609.57 | 19-DEC-13:00 | 92.11 | 07-DEC-17:30 | 417.94 | 19-DEC-13:00 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.974087E+10 | 0.244998E+10 | 5035.02 | 0.837717E+10 | 0.136370E+10 | 0.00 | ||||||||||||||
| Minimum of Months | 76366977.69 | 19481677.19 | 65.55 | 68758289.34 | 2099887.32 | 0.00 | 0.20 | 0.00 | 793.64 | 710.57 | 84.07 | 198.03 | 0.00 | |||||||
| Maximum of Months | 0.191369E+10 | 0.485332E+09 | 725.89 | 0.172216E+10 | 0.412178E+09 | 0.00 | 0.68 | 0.00 | 2522.44 | 2522.44 | 462.27 | 725.23 | 0.00 |
Report: DXReportMonthly
For: SPLIT MSW COOLING COIL
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.137889E+10 | 0.354544E+09 | 341.89 | 0.134133E+10 | 37555639.94 | 0.00 | 0.39 | 14-JAN-15:00 | 0.00 | 01-JAN-00:10 | 4226.31 | 18-JAN-14:30 | 4226.31 | 18-JAN-14:30 | 280.18 | 20-JAN-15:30 | 1087.70 | 14-JAN-15:00 | 0.00 | 01-JAN-00:10 |
| February | 0.910510E+09 | 0.234564E+09 | 225.00 | 0.889673E+09 | 20837427.05 | 0.00 | 0.35 | 03-FEB-15:00 | 0.00 | 01-FEB-00:10 | 3666.19 | 03-FEB-15:00 | 3666.19 | 03-FEB-15:00 | 288.61 | 01-FEB-16:30 | 937.87 | 03-FEB-15:00 | 0.00 | 01-FEB-00:10 |
| March | 0.751197E+09 | 0.190452E+09 | 194.10 | 0.687025E+09 | 64171339.16 | 0.00 | 0.33 | 23-MAR-15:30 | 0.00 | 01-MAR-00:10 | 3783.93 | 23-MAR-15:30 | 3244.78 | 23-MAR-15:30 | 549.16 | 23-MAR-16:10 | 925.19 | 23-MAR-15:30 | 0.00 | 01-MAR-00:10 |
| April | 0.192868E+10 | 0.487586E+09 | 417.19 | 0.175822E+10 | 0.170467E+09 | 0.00 | 0.34 | 26-APR-14:10 | 0.00 | 01-APR-00:10 | 3860.94 | 26-APR-16:20 | 3677.77 | 26-APR-14:10 | 426.72 | 25-APR-13:30 | 979.59 | 26-APR-14:00 | 0.00 | 01-APR-00:10 |
| May | 0.140786E+10 | 0.358500E+09 | 399.23 | 0.129600E+10 | 0.111865E+09 | 0.00 | 0.27 | 03-MAY-15:10 | 0.00 | 01-MAY-02:50 | 3051.70 | 03-MAY-15:10 | 2850.17 | 03-MAY-15:10 | 306.39 | 04-MAY-15:20 | 761.72 | 03-MAY-15:10 | 0.00 | 01-MAY-00:10 |
| June | 0.273504E+10 | 0.684695E+09 | 604.75 | 0.232874E+10 | 0.406304E+09 | 0.00 | 0.35 | 29-JUN-16:25 | 0.00 | 01-JUN-00:10 | 4042.47 | 29-JUN-16:25 | 3281.99 | 29-JUN-16:30 | 778.00 | 29-JUN-16:03 | 977.96 | 29-JUN-16:25 | 0.00 | 01-JUN-00:10 |
| July | 0.481117E+10 | 0.118819E+10 | 726.44 | 0.384499E+10 | 0.966181E+09 | 0.00 | 0.41 | 23-JUL-16:30 | 0.00 | 04-JUL-05:05 | 4734.46 | 23-JUL-16:15 | 3904.03 | 23-JUL-16:30 | 1102.24 | 29-JUL-16:10 | 1149.34 | 19-JUL-15:10 | 0.00 | 01-JUL-00:10 |
| August | 0.531764E+10 | 0.130650E+10 | 728.85 | 0.419313E+10 | 0.112451E+10 | 0.00 | 0.43 | 17-AUG-15:10 | 0.00 | 02-AUG-05:05 | 5059.54 | 17-AUG-15:10 | 4260.71 | 19-AUG-16:10 | 1039.33 | 13-AUG-17:00 | 1258.65 | 17-AUG-15:10 | 0.00 | 01-AUG-00:10 |
| September | 0.418130E+10 | 0.104871E+10 | 664.42 | 0.354800E+10 | 0.633297E+09 | 0.00 | 0.58 | 29-SEP-13:30 | 0.00 | 01-SEP-06:40 | 6148.19 | 29-SEP-15:10 | 6148.19 | 29-SEP-15:10 | 958.64 | 22-SEP-12:00 | 1750.23 | 29-SEP-13:30 | 0.00 | 01-SEP-00:10 |
| October | 0.435857E+10 | 0.111058E+10 | 602.85 | 0.394088E+10 | 0.417684E+09 | 0.00 | 0.62 | 16-OCT-12:00 | 0.00 | 07-OCT-00:40 | 6411.34 | 16-OCT-13:00 | 6411.34 | 16-OCT-13:00 | 1082.21 | 01-OCT-11:30 | 1845.60 | 16-OCT-12:00 | 0.00 | 01-OCT-00:10 |
| November | 0.178724E+10 | 0.458154E+09 | 409.70 | 0.171728E+10 | 69954328.86 | 0.00 | 0.44 | 19-NOV-13:00 | 0.00 | 01-NOV-01:40 | 4796.25 | 19-NOV-13:00 | 4796.25 | 19-NOV-13:00 | 436.04 | 10-NOV-13:20 | 1241.22 | 19-NOV-13:00 | 0.00 | 01-NOV-00:10 |
| December | 0.172854E+10 | 0.446004E+09 | 366.42 | 0.170596E+10 | 22586431.31 | 0.00 | 0.41 | 19-DEC-13:00 | 0.00 | 01-DEC-00:10 | 4351.93 | 19-DEC-13:00 | 4351.93 | 19-DEC-13:00 | 302.16 | 07-DEC-15:30 | 1131.74 | 19-DEC-13:00 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.312966E+11 | 0.786848E+10 | 5680.85 | 0.272512E+11 | 0.404542E+10 | 0.00 | ||||||||||||||
| Minimum of Months | 0.751197E+09 | 0.190452E+09 | 194.10 | 0.687025E+09 | 20837427.05 | 0.00 | 0.27 | 0.00 | 3051.70 | 2850.17 | 280.18 | 761.72 | 0.00 | |||||||
| Maximum of Months | 0.531764E+10 | 0.130650E+10 | 728.85 | 0.419313E+10 | 0.112451E+10 | 0.00 | 0.62 | 0.00 | 6411.34 | 6411.34 | 1102.24 | 1845.60 | 0.00 |
Report: DXReportMonthly
For: SPLIT MNW COOLING COIL
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.137412E+09 | 35659661.71 | 68.48 | 0.131153E+09 | 6259006.28 | 0.00 | 0.17 | 18-JAN-14:30 | 0.00 | 01-JAN-00:10 | 1689.18 | 18-JAN-14:30 | 1689.18 | 18-JAN-14:30 | 169.60 | 17-JAN-14:00 | 435.01 | 18-JAN-14:30 | 0.00 | 01-JAN-00:10 |
| February | 23500397.91 | 6213772.66 | 15.74 | 22986334.63 | 514063.28 | 0.00 | 0.11 | 03-FEB-15:10 | 0.00 | 01-FEB-00:10 | 1085.96 | 03-FEB-15:10 | 1085.96 | 03-FEB-15:10 | 95.17 | 01-FEB-17:20 | 288.03 | 03-FEB-15:10 | 0.00 | 01-FEB-00:10 |
| March | 0.114865E+09 | 29109185.40 | 51.87 | 97982501.26 | 16882277.51 | 0.00 | 0.22 | 23-MAR-16:05 | 0.00 | 01-MAR-00:10 | 2330.30 | 23-MAR-16:05 | 1907.40 | 23-MAR-16:05 | 423.04 | 23-MAR-16:10 | 575.86 | 23-MAR-16:05 | 0.00 | 01-MAR-00:10 |
| April | 0.936087E+09 | 0.237457E+09 | 301.89 | 0.835282E+09 | 0.100805E+09 | 0.00 | 0.31 | 26-APR-16:20 | 0.00 | 01-APR-00:10 | 3266.26 | 26-APR-16:20 | 2965.67 | 26-APR-16:20 | 356.80 | 11-APR-15:30 | 807.82 | 26-APR-16:20 | 0.00 | 01-APR-00:10 |
| May | 0.119961E+10 | 0.305672E+09 | 387.70 | 0.109938E+10 | 0.100230E+09 | 0.00 | 0.26 | 03-MAY-16:10 | 0.00 | 01-MAY-01:00 | 2741.08 | 03-MAY-16:10 | 2579.47 | 03-MAY-16:10 | 297.82 | 04-MAY-15:20 | 686.07 | 03-MAY-16:10 | 0.00 | 01-MAY-00:10 |
| June | 0.274071E+10 | 0.685353E+09 | 615.15 | 0.232862E+10 | 0.412088E+09 | 0.00 | 0.38 | 29-JUN-17:10 | 0.00 | 01-JUN-00:10 | 4169.38 | 29-JUN-17:10 | 3385.49 | 29-JUN-17:10 | 816.23 | 29-JUN-16:13 | 1003.58 | 29-JUN-17:10 | 0.00 | 01-JUN-00:10 |
| July | 0.458922E+10 | 0.113270E+10 | 727.91 | 0.364988E+10 | 0.939348E+09 | 0.00 | 0.43 | 19-JUL-16:25 | 0.00 | 06-JUL-03:30 | 4696.89 | 19-JUL-16:25 | 3811.27 | 19-JUL-16:25 | 1026.96 | 29-JUL-16:30 | 1136.16 | 18-JUL-16:03 | 0.00 | 01-JUL-00:10 |
| August | 0.441116E+10 | 0.108539E+10 | 722.58 | 0.341400E+10 | 0.997160E+09 | 0.00 | 0.41 | 17-AUG-16:05 | 0.00 | 02-AUG-05:05 | 4524.60 | 17-AUG-16:05 | 3628.03 | 17-AUG-16:05 | 955.91 | 06-AUG-16:40 | 1099.64 | 17-AUG-15:10 | 0.00 | 01-AUG-00:10 |
| September | 0.264139E+10 | 0.667802E+09 | 623.24 | 0.219632E+10 | 0.445066E+09 | 0.00 | 0.47 | 29-SEP-15:20 | 0.00 | 01-SEP-03:50 | 4667.97 | 29-SEP-15:30 | 4667.97 | 29-SEP-15:30 | 954.00 | 22-SEP-12:00 | 1310.76 | 29-SEP-15:20 | 0.00 | 01-SEP-00:10 |
| October | 0.238168E+10 | 0.613377E+09 | 519.97 | 0.207508E+10 | 0.306607E+09 | 0.00 | 0.45 | 14-OCT-15:10 | 0.00 | 07-OCT-00:40 | 4336.29 | 14-OCT-15:10 | 4336.29 | 14-OCT-15:10 | 893.31 | 01-OCT-15:10 | 1248.29 | 16-OCT-11:00 | 0.00 | 01-OCT-00:10 |
| November | 0.102389E+09 | 26905529.37 | 73.82 | 98252767.62 | 4136515.30 | 0.00 | 0.16 | 19-NOV-13:30 | 0.00 | 01-NOV-00:10 | 1584.92 | 19-NOV-13:30 | 1584.92 | 19-NOV-13:30 | 146.80 | 10-NOV-21:40 | 423.37 | 19-NOV-13:00 | 0.00 | 01-NOV-00:10 |
| December | 90911063.46 | 24005713.58 | 52.04 | 89517605.47 | 1393457.98 | 0.00 | 0.16 | 05-DEC-15:10 | 0.00 | 01-DEC-00:10 | 1622.82 | 05-DEC-15:10 | 1622.82 | 05-DEC-15:10 | 97.53 | 07-DEC-17:40 | 426.08 | 05-DEC-15:10 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.193689E+11 | 0.484964E+10 | 4160.39 | 0.160385E+11 | 0.333049E+10 | 0.00 | ||||||||||||||
| Minimum of Months | 23500397.91 | 6213772.66 | 15.74 | 22986334.63 | 514063.28 | 0.00 | 0.11 | 0.00 | 1085.96 | 1085.96 | 95.17 | 288.03 | 0.00 | |||||||
| Maximum of Months | 0.458922E+10 | 0.113270E+10 | 727.91 | 0.364988E+10 | 0.997160E+09 | 0.00 | 0.47 | 0.00 | 4696.89 | 4667.97 | 1026.96 | 1310.76 | 0.00 |
Report: DXReportMonthly
For: SPLIT MSE COOLING COIL
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.143815E+10 | 0.369294E+09 | 358.13 | 0.139826E+10 | 39894376.94 | 0.00 | 0.38 | 18-JAN-13:30 | 0.00 | 01-JAN-00:10 | 3919.00 | 18-JAN-13:30 | 3919.00 | 18-JAN-13:30 | 323.04 | 21-JAN-09:40 | 1003.03 | 18-JAN-13:00 | 0.00 | 01-JAN-00:10 |
| February | 0.897049E+09 | 0.231238E+09 | 234.16 | 0.877796E+09 | 19252887.05 | 0.00 | 0.37 | 01-FEB-12:00 | 0.00 | 01-FEB-00:10 | 3695.53 | 01-FEB-12:00 | 3695.53 | 01-FEB-12:00 | 226.73 | 01-FEB-16:10 | 956.91 | 01-FEB-12:00 | 0.00 | 01-FEB-00:10 |
| March | 0.745900E+09 | 0.188801E+09 | 200.46 | 0.682989E+09 | 62910886.54 | 0.00 | 0.31 | 23-MAR-14:00 | 0.00 | 01-MAR-00:10 | 3329.19 | 23-MAR-14:00 | 3143.74 | 11-MAR-13:00 | 436.55 | 23-MAR-15:20 | 818.10 | 23-MAR-14:00 | 0.00 | 01-MAR-00:10 |
| April | 0.187121E+10 | 0.472886E+09 | 423.39 | 0.170781E+10 | 0.163401E+09 | 0.00 | 0.38 | 26-APR-13:00 | 0.00 | 01-APR-00:10 | 3913.00 | 26-APR-13:00 | 3700.29 | 26-APR-13:00 | 450.90 | 08-APR-12:10 | 1009.72 | 26-APR-13:00 | 0.00 | 01-APR-00:10 |
| May | 0.128797E+10 | 0.327905E+09 | 401.95 | 0.118620E+10 | 0.101770E+09 | 0.00 | 0.30 | 04-MAY-12:00 | 0.00 | 01-MAY-02:20 | 3072.81 | 04-MAY-12:00 | 2882.27 | 04-MAY-12:00 | 330.92 | 03-MAY-09:30 | 766.20 | 04-MAY-12:00 | 0.00 | 01-MAY-00:10 |
| June | 0.255343E+10 | 0.638593E+09 | 602.84 | 0.217251E+10 | 0.380915E+09 | 0.00 | 0.31 | 30-JUN-10:00 | 0.00 | 01-JUN-00:10 | 3383.12 | 30-JUN-10:00 | 2761.14 | 30-JUN-10:00 | 724.04 | 28-JUN-10:00 | 824.76 | 30-JUN-10:00 | 0.00 | 01-JUN-00:10 |
| July | 0.469044E+10 | 0.115660E+10 | 723.40 | 0.374077E+10 | 0.949671E+09 | 0.00 | 0.41 | 23-JUL-11:00 | 0.00 | 04-JUL-05:05 | 4474.50 | 23-JUL-11:00 | 3567.14 | 23-JUL-11:00 | 959.13 | 20-JUL-11:00 | 1129.72 | 31-JUL-13:00 | 0.00 | 01-JUL-00:10 |
| August | 0.528423E+10 | 0.129537E+10 | 730.31 | 0.416441E+10 | 0.111982E+10 | 0.00 | 0.44 | 14-AUG-11:00 | 0.00 | 01-AUG-05:05 | 4792.45 | 14-AUG-11:00 | 3902.43 | 14-AUG-11:00 | 1069.74 | 19-AUG-09:00 | 1221.03 | 14-AUG-11:00 | 0.00 | 01-AUG-00:10 |
| September | 0.397206E+10 | 0.995211E+09 | 657.61 | 0.336640E+10 | 0.605653E+09 | 0.00 | 0.63 | 29-SEP-13:00 | 0.00 | 01-SEP-06:40 | 6129.62 | 29-SEP-13:00 | 6129.62 | 29-SEP-13:00 | 960.13 | 22-SEP-12:00 | 1770.74 | 29-SEP-13:00 | 0.00 | 01-SEP-00:10 |
| October | 0.429364E+10 | 0.109312E+10 | 607.01 | 0.389019E+10 | 0.403458E+09 | 0.00 | 0.71 | 16-OCT-11:00 | 0.00 | 07-OCT-00:40 | 6802.15 | 16-OCT-11:50 | 6802.15 | 16-OCT-11:50 | 1089.92 | 01-OCT-11:00 | 1967.43 | 16-OCT-11:00 | 0.00 | 01-OCT-00:10 |
| November | 0.173191E+10 | 0.443919E+09 | 417.87 | 0.166924E+10 | 62671515.61 | 0.00 | 0.47 | 19-NOV-13:00 | 0.00 | 01-NOV-01:20 | 4880.82 | 19-NOV-13:00 | 4880.82 | 19-NOV-13:00 | 404.68 | 10-NOV-13:00 | 1255.60 | 19-NOV-13:00 | 0.00 | 01-NOV-00:10 |
| December | 0.174103E+10 | 0.448786E+09 | 378.41 | 0.172019E+10 | 20836820.68 | 0.00 | 0.45 | 19-DEC-13:00 | 0.00 | 01-DEC-00:10 | 4432.90 | 19-DEC-13:00 | 4432.90 | 19-DEC-13:00 | 268.83 | 07-DEC-14:00 | 1146.23 | 19-DEC-13:00 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.305070E+11 | 0.766173E+10 | 5735.55 | 0.265768E+11 | 0.393025E+10 | 0.00 | ||||||||||||||
| Minimum of Months | 0.745900E+09 | 0.188801E+09 | 200.46 | 0.682989E+09 | 19252887.05 | 0.00 | 0.30 | 0.00 | 3072.81 | 2761.14 | 226.73 | 766.20 | 0.00 | |||||||
| Maximum of Months | 0.528423E+10 | 0.129537E+10 | 730.31 | 0.416441E+10 | 0.111982E+10 | 0.00 | 0.71 | 0.00 | 6802.15 | 6802.15 | 1089.92 | 1967.43 | 0.00 |
Report: DXReportMonthly
For: SPLIT MNE COOLING COIL
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.150372E+09 | 38943865.03 | 72.96 | 0.143359E+09 | 7012541.64 | 0.00 | 0.17 | 18-JAN-13:00 | 0.00 | 01-JAN-00:10 | 1567.89 | 18-JAN-13:00 | 1567.89 | 18-JAN-13:00 | 173.12 | 17-JAN-14:00 | 416.84 | 18-JAN-13:00 | 0.00 | 01-JAN-00:10 |
| February | 20478567.89 | 5451035.77 | 12.75 | 20478567.89 | -0.0 | 0.00 | 0.11 | 01-FEB-12:00 | 0.00 | 01-FEB-00:10 | 1006.53 | 01-FEB-12:00 | 1006.53 | 01-FEB-12:00 | 0.00 | 03-FEB-14:40 | 270.96 | 01-FEB-12:00 | 0.00 | 01-FEB-00:10 |
| March | 0.114496E+09 | 29105677.35 | 62.06 | 99118802.04 | 15376981.01 | 0.00 | 0.16 | 23-MAR-14:00 | 0.00 | 01-MAR-00:10 | 1545.13 | 23-MAR-14:00 | 1329.09 | 23-MAR-10:00 | 276.17 | 23-MAR-16:10 | 386.79 | 23-MAR-14:00 | 0.00 | 01-MAR-00:10 |
| April | 0.865804E+09 | 0.219636E+09 | 296.17 | 0.772855E+09 | 92949658.58 | 0.00 | 0.31 | 26-APR-11:00 | 0.00 | 01-APR-00:10 | 2994.53 | 26-APR-11:00 | 2691.14 | 26-APR-11:00 | 367.39 | 27-APR-10:00 | 764.36 | 26-APR-11:00 | 0.00 | 01-APR-00:10 |
| May | 0.108342E+10 | 0.276146E+09 | 391.26 | 0.993090E+09 | 90333297.44 | 0.00 | 0.27 | 04-MAY-12:00 | 0.00 | 01-MAY-00:20 | 2582.47 | 04-MAY-12:00 | 2400.72 | 04-MAY-12:00 | 324.64 | 03-MAY-09:20 | 646.06 | 04-MAY-12:00 | 0.00 | 01-MAY-00:10 |
| June | 0.256055E+10 | 0.639767E+09 | 612.29 | 0.217334E+10 | 0.387206E+09 | 0.00 | 0.34 | 30-JUN-10:00 | 0.00 | 01-JUN-00:10 | 3443.87 | 30-JUN-10:00 | 2810.70 | 30-JUN-10:00 | 726.75 | 28-JUN-10:00 | 836.10 | 30-JUN-10:00 | 0.00 | 01-JUN-00:10 |
| July | 0.446848E+10 | 0.110126E+10 | 725.30 | 0.354623E+10 | 0.922248E+09 | 0.00 | 0.42 | 19-JUL-10:10 | 0.00 | 06-JUL-02:30 | 4212.85 | 19-JUL-10:10 | 3435.72 | 19-JUL-10:30 | 909.45 | 20-JUL-10:00 | 1064.61 | 19-JUL-10:30 | 0.00 | 01-JUL-00:10 |
| August | 0.437615E+10 | 0.107463E+10 | 719.33 | 0.338507E+10 | 0.991086E+09 | 0.00 | 0.41 | 14-AUG-11:00 | 0.00 | 01-AUG-05:05 | 4105.91 | 14-AUG-10:40 | 3272.02 | 14-AUG-11:00 | 980.84 | 18-AUG-09:10 | 1047.81 | 14-AUG-11:00 | 0.00 | 01-AUG-00:10 |
| September | 0.242886E+10 | 0.614132E+09 | 608.44 | 0.201830E+10 | 0.410559E+09 | 0.00 | 0.49 | 29-SEP-13:00 | 0.00 | 01-SEP-03:10 | 4352.54 | 29-SEP-13:00 | 4352.54 | 29-SEP-13:00 | 955.63 | 22-SEP-12:00 | 1286.33 | 29-SEP-13:00 | 0.00 | 01-SEP-00:10 |
| October | 0.230035E+10 | 0.593290E+09 | 513.30 | 0.201174E+10 | 0.288618E+09 | 0.00 | 0.55 | 16-OCT-11:00 | 0.00 | 07-OCT-00:40 | 4753.12 | 16-OCT-11:00 | 4753.12 | 16-OCT-11:00 | 855.39 | 01-OCT-10:40 | 1418.62 | 16-OCT-11:00 | 0.00 | 01-OCT-00:10 |
| November | 86419253.01 | 22842594.37 | 52.52 | 84544734.43 | 1874518.59 | 0.00 | 0.18 | 19-NOV-13:00 | 0.00 | 01-NOV-00:10 | 1631.27 | 19-NOV-13:00 | 1631.27 | 19-NOV-13:00 | 100.28 | 19-NOV-19:40 | 439.90 | 19-NOV-13:00 | 0.00 | 01-NOV-00:10 |
| December | 96561471.38 | 25527102.72 | 56.63 | 95792967.22 | 768504.16 | 0.00 | 0.14 | 05-DEC-10:00 | 0.00 | 01-DEC-00:10 | 1273.97 | 05-DEC-10:00 | 1273.97 | 05-DEC-10:00 | 63.94 | 07-DEC-14:00 | 343.10 | 05-DEC-10:00 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.185519E+11 | 0.464074E+10 | 4123.02 | 0.153439E+11 | 0.320803E+10 | 0.00 | ||||||||||||||
| Minimum of Months | 20478567.89 | 5451035.77 | 12.75 | 20478567.89 | -0.0 | 0.00 | 0.11 | 0.00 | 1006.53 | 1006.53 | 0.00 | 270.96 | 0.00 | |||||||
| Maximum of Months | 0.446848E+10 | 0.110126E+10 | 725.30 | 0.354623E+10 | 0.991086E+09 | 0.00 | 0.55 | 0.00 | 4753.12 | 4753.12 | 980.84 | 1418.62 | 0.00 |
Report: DXReportMonthly
For: SPLIT MN1 COOLING COIL
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.200316E+09 | 51690145.42 | 111.39 | 0.187969E+09 | 12346517.67 | 0.00 | 0.18 | 18-JAN-13:00 | 0.00 | 01-JAN-00:10 | 1483.52 | 18-JAN-13:00 | 1483.52 | 18-JAN-13:00 | 181.52 | 17-JAN-14:00 | 393.99 | 18-JAN-13:00 | 0.00 | 01-JAN-00:10 |
| February | 29903329.09 | 7916977.60 | 28.11 | 29478008.80 | 425320.29 | 0.00 | 0.11 | 01-FEB-12:00 | 0.00 | 01-FEB-00:10 | 929.07 | 01-FEB-12:00 | 929.07 | 01-FEB-12:00 | 56.20 | 01-FEB-17:40 | 250.11 | 01-FEB-12:00 | 0.00 | 01-FEB-00:10 |
| March | 0.106580E+09 | 27115598.36 | 72.95 | 90899480.56 | 15680343.09 | 0.00 | 0.14 | 23-MAR-16:05 | 0.00 | 01-MAR-00:10 | 1243.35 | 23-MAR-16:05 | 1022.98 | 23-MAR-14:10 | 246.13 | 23-MAR-16:10 | 310.17 | 23-MAR-16:05 | 0.00 | 01-MAR-00:10 |
| April | 0.745308E+09 | 0.189729E+09 | 366.16 | 0.659007E+09 | 86300984.30 | 0.00 | 0.25 | 26-APR-13:00 | 0.00 | 01-APR-00:10 | 2157.37 | 26-APR-13:00 | 1979.38 | 26-APR-13:00 | 258.42 | 25-APR-12:00 | 566.15 | 26-APR-13:00 | 0.00 | 01-APR-00:10 |
| May | 0.105786E+10 | 0.270253E+09 | 500.70 | 0.959852E+09 | 98004813.98 | 0.00 | 0.21 | 04-MAY-12:00 | 0.00 | 01-MAY-03:40 | 1896.03 | 04-MAY-12:00 | 1745.67 | 04-MAY-12:00 | 244.57 | 05-MAY-19:30 | 477.51 | 04-MAY-12:00 | 0.00 | 01-MAY-00:10 |
| June | 0.232143E+10 | 0.582667E+09 | 682.46 | 0.195736E+10 | 0.364067E+09 | 0.00 | 0.30 | 29-JUN-17:15 | 0.00 | 01-JUN-00:20 | 2759.36 | 29-JUN-17:15 | 2171.22 | 29-JUN-17:15 | 588.13 | 29-JUN-17:15 | 669.75 | 29-JUN-17:15 | 0.00 | 01-JUN-00:10 |
| July | 0.375323E+10 | 0.928871E+09 | 738.61 | 0.294662E+10 | 0.806611E+09 | 0.00 | 0.34 | 18-JUL-17:50 | 0.00 | 06-JUL-05:50 | 3162.70 | 18-JUL-18:00 | 2483.51 | 18-JUL-17:50 | 729.11 | 29-JUL-17:10 | 776.81 | 31-JUL-13:00 | 0.00 | 01-JUL-00:10 |
| August | 0.367570E+10 | 0.906763E+09 | 734.09 | 0.280789E+10 | 0.867809E+09 | 0.00 | 0.33 | 17-AUG-14:10 | 0.00 | 02-AUG-05:05 | 3008.22 | 17-AUG-14:10 | 2338.98 | 18-AUG-15:10 | 706.79 | 18-AUG-09:30 | 773.32 | 17-AUG-14:10 | 0.00 | 01-AUG-00:10 |
| September | 0.231553E+10 | 0.585732E+09 | 663.80 | 0.190525E+10 | 0.410275E+09 | 0.00 | 0.41 | 29-SEP-13:00 | 0.00 | 01-SEP-06:40 | 3279.13 | 29-SEP-13:00 | 3279.13 | 29-SEP-13:00 | 866.27 | 22-SEP-12:00 | 981.98 | 29-SEP-13:00 | 0.00 | 01-SEP-00:10 |
| October | 0.224662E+10 | 0.577302E+09 | 585.42 | 0.194649E+10 | 0.300128E+09 | 0.00 | 0.44 | 16-OCT-11:00 | 0.00 | 07-OCT-05:05 | 3431.90 | 16-OCT-11:00 | 3431.90 | 16-OCT-11:00 | 769.43 | 01-OCT-10:30 | 1042.42 | 16-OCT-11:00 | 0.00 | 01-OCT-00:10 |
| November | 0.174900E+09 | 45518000.43 | 157.56 | 0.161965E+09 | 12935381.74 | 0.00 | 0.17 | 19-NOV-13:00 | 0.00 | 01-NOV-00:10 | 1410.46 | 19-NOV-13:00 | 1410.46 | 19-NOV-13:00 | 184.87 | 11-NOV-19:20 | 381.01 | 19-NOV-13:00 | 0.00 | 01-NOV-00:10 |
| December | 0.144323E+09 | 37918473.47 | 96.71 | 0.140053E+09 | 4269884.39 | 0.00 | 0.14 | 05-DEC-15:00 | 0.00 | 01-DEC-00:10 | 1192.79 | 05-DEC-15:00 | 1192.79 | 05-DEC-15:00 | 118.30 | 07-DEC-17:40 | 315.73 | 05-DEC-15:00 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.167717E+11 | 0.421148E+10 | 4737.96 | 0.137928E+11 | 0.297885E+10 | 0.00 | ||||||||||||||
| Minimum of Months | 29903329.09 | 7916977.60 | 28.11 | 29478008.80 | 425320.29 | 0.00 | 0.11 | 0.00 | 929.07 | 929.07 | 56.20 | 250.11 | 0.00 | |||||||
| Maximum of Months | 0.375323E+10 | 0.928871E+09 | 738.61 | 0.294662E+10 | 0.867809E+09 | 0.00 | 0.44 | 0.00 | 3431.90 | 3431.90 | 866.27 | 1042.42 | 0.00 |
Report: DXReportMonthly
For: SPLIT MN2 COOLING COIL
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.203089E+09 | 52402593.38 | 112.38 | 0.190599E+09 | 12489303.90 | 0.00 | 0.18 | 18-JAN-13:00 | 0.00 | 01-JAN-00:10 | 1491.11 | 18-JAN-13:00 | 1491.11 | 18-JAN-13:00 | 181.63 | 17-JAN-14:00 | 395.93 | 18-JAN-13:00 | 0.00 | 01-JAN-00:10 |
| February | 29521816.61 | 7819138.76 | 27.84 | 29140635.74 | 381180.88 | 0.00 | 0.11 | 01-FEB-12:00 | 0.00 | 01-FEB-00:10 | 935.54 | 01-FEB-12:00 | 935.54 | 01-FEB-12:00 | 49.66 | 01-FEB-17:40 | 251.82 | 01-FEB-12:00 | 0.00 | 01-FEB-00:10 |
| March | 0.110954E+09 | 28230389.16 | 75.33 | 94767027.98 | 16187458.66 | 0.00 | 0.14 | 23-MAR-14:10 | 0.00 | 01-MAR-00:10 | 1243.32 | 23-MAR-16:05 | 1038.32 | 23-MAR-14:10 | 245.85 | 23-MAR-16:10 | 311.76 | 23-MAR-14:10 | 0.00 | 01-MAR-00:10 |
| April | 0.745447E+09 | 0.189762E+09 | 366.98 | 0.659275E+09 | 86171957.39 | 0.00 | 0.25 | 26-APR-13:00 | 0.00 | 01-APR-00:10 | 2170.19 | 26-APR-13:00 | 1991.92 | 26-APR-13:00 | 260.36 | 25-APR-12:00 | 569.38 | 26-APR-13:00 | 0.00 | 01-APR-00:10 |
| May | 0.105479E+10 | 0.269467E+09 | 499.14 | 0.957168E+09 | 97626021.72 | 0.00 | 0.22 | 04-MAY-12:00 | 0.00 | 01-MAY-03:30 | 1909.54 | 04-MAY-12:00 | 1758.54 | 04-MAY-12:00 | 244.10 | 05-MAY-19:30 | 480.79 | 04-MAY-12:00 | 0.00 | 01-MAY-00:10 |
| June | 0.231385E+10 | 0.580734E+09 | 681.84 | 0.195096E+10 | 0.362891E+09 | 0.00 | 0.30 | 29-JUN-17:15 | 0.00 | 01-JUN-00:20 | 2738.12 | 29-JUN-17:15 | 2153.47 | 29-JUN-17:15 | 586.16 | 28-JUN-11:00 | 664.73 | 29-JUN-17:15 | 0.00 | 01-JUN-00:10 |
| July | 0.374803E+10 | 0.927525E+09 | 738.09 | 0.294244E+10 | 0.805584E+09 | 0.00 | 0.34 | 18-JUL-17:50 | 0.00 | 06-JUL-05:50 | 3148.07 | 18-JUL-18:00 | 2471.27 | 18-JUL-17:50 | 725.05 | 29-JUL-17:10 | 778.94 | 19-JUL-12:00 | 0.00 | 01-JUL-00:10 |
| August | 0.367410E+10 | 0.906299E+09 | 733.92 | 0.280683E+10 | 0.867263E+09 | 0.00 | 0.33 | 17-AUG-14:10 | 0.00 | 02-AUG-05:05 | 3013.48 | 17-AUG-14:10 | 2341.43 | 17-AUG-14:10 | 712.15 | 18-AUG-09:30 | 774.82 | 17-AUG-14:00 | 0.00 | 01-AUG-00:10 |
| September | 0.230584E+10 | 0.583279E+09 | 662.89 | 0.189713E+10 | 0.408713E+09 | 0.00 | 0.41 | 29-SEP-13:00 | 0.00 | 01-SEP-06:40 | 3288.92 | 29-SEP-13:00 | 3288.92 | 29-SEP-13:00 | 866.38 | 22-SEP-12:00 | 984.63 | 29-SEP-13:00 | 0.00 | 01-SEP-00:10 |
| October | 0.224646E+10 | 0.577289E+09 | 585.84 | 0.194688E+10 | 0.299586E+09 | 0.00 | 0.44 | 16-OCT-11:00 | 0.00 | 07-OCT-05:05 | 3447.92 | 16-OCT-11:00 | 3447.92 | 16-OCT-11:00 | 769.52 | 01-OCT-10:30 | 1046.85 | 16-OCT-11:00 | 0.00 | 01-OCT-00:10 |
| November | 0.171414E+09 | 44634943.03 | 152.70 | 0.159088E+09 | 12326143.90 | 0.00 | 0.17 | 19-NOV-13:00 | 0.00 | 01-NOV-00:10 | 1414.99 | 19-NOV-13:00 | 1414.99 | 19-NOV-13:00 | 183.01 | 10-NOV-21:40 | 382.19 | 19-NOV-13:00 | 0.00 | 01-NOV-00:10 |
| December | 0.145830E+09 | 38314282.71 | 96.69 | 0.141574E+09 | 4255404.73 | 0.00 | 0.14 | 05-DEC-15:00 | 0.00 | 01-DEC-00:10 | 1197.80 | 05-DEC-15:00 | 1197.80 | 05-DEC-15:00 | 118.25 | 07-DEC-17:40 | 317.01 | 05-DEC-15:00 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.167493E+11 | 0.420576E+10 | 4733.63 | 0.137759E+11 | 0.297347E+10 | 0.00 | ||||||||||||||
| Minimum of Months | 29521816.61 | 7819138.76 | 27.84 | 29140635.74 | 381180.88 | 0.00 | 0.11 | 0.00 | 935.54 | 935.54 | 49.66 | 251.82 | 0.00 | |||||||
| Maximum of Months | 0.374803E+10 | 0.927525E+09 | 738.09 | 0.294244E+10 | 0.867263E+09 | 0.00 | 0.44 | 0.00 | 3447.92 | 3447.92 | 866.38 | 1046.85 | 0.00 |
Report: DXReportMonthly
For: SPLIT MS1 COOLING COIL
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.192211E+10 | 0.492932E+09 | 472.47 | 0.186793E+10 | 54182092.10 | 0.00 | 0.41 | 14-JAN-14:30 | 0.00 | 01-JAN-00:10 | 3813.08 | 18-JAN-13:30 | 3813.08 | 18-JAN-13:30 | 280.64 | 20-JAN-17:30 | 968.97 | 14-JAN-14:50 | 0.00 | 01-JAN-00:10 |
| February | 0.119572E+10 | 0.307521E+09 | 325.13 | 0.116656E+10 | 29160837.58 | 0.00 | 0.37 | 01-FEB-12:00 | 0.00 | 01-FEB-05:40 | 3428.59 | 01-FEB-12:10 | 3428.59 | 01-FEB-12:10 | 247.71 | 01-FEB-17:13 | 887.89 | 01-FEB-12:00 | 0.00 | 01-FEB-00:10 |
| March | 0.928970E+09 | 0.236167E+09 | 309.97 | 0.854314E+09 | 74655295.53 | 0.00 | 0.31 | 11-MAR-13:50 | 0.00 | 01-MAR-00:10 | 2993.46 | 23-MAR-14:00 | 2937.75 | 11-MAR-13:50 | 404.03 | 23-MAR-16:10 | 742.63 | 11-MAR-13:50 | 0.00 | 01-MAR-00:10 |
| April | 0.182822E+10 | 0.463645E+09 | 536.80 | 0.166082E+10 | 0.167408E+09 | 0.00 | 0.33 | 26-APR-13:00 | 0.00 | 01-APR-00:10 | 3162.07 | 26-APR-13:00 | 2967.33 | 26-APR-13:00 | 400.89 | 08-APR-12:20 | 821.35 | 26-APR-13:00 | 0.00 | 01-APR-00:10 |
| May | 0.127224E+10 | 0.324743E+09 | 511.72 | 0.116110E+10 | 0.111137E+09 | 0.00 | 0.25 | 04-MAY-12:00 | 0.00 | 01-MAY-23:20 | 2375.03 | 04-MAY-12:00 | 2224.92 | 03-MAY-13:00 | 261.78 | 02-MAY-21:05 | 596.07 | 04-MAY-12:00 | 0.00 | 01-MAY-00:10 |
| June | 0.231301E+10 | 0.581153E+09 | 677.86 | 0.195439E+10 | 0.358619E+09 | 0.00 | 0.26 | 29-JUN-16:07 | 0.00 | 01-JUN-00:50 | 2574.32 | 29-JUN-16:07 | 2071.19 | 25-JUN-13:00 | 604.76 | 28-JUN-11:00 | 628.67 | 29-JUN-16:07 | 0.00 | 01-JUN-00:10 |
| July | 0.397811E+10 | 0.985155E+09 | 738.48 | 0.314181E+10 | 0.836302E+09 | 0.00 | 0.36 | 31-JUL-13:00 | 0.00 | 06-JUL-05:50 | 3545.16 | 31-JUL-13:00 | 2834.26 | 31-JUL-13:00 | 817.74 | 29-JUL-12:00 | 913.84 | 31-JUL-13:00 | 0.00 | 01-JUL-00:10 |
| August | 0.459847E+10 | 0.113249E+10 | 739.43 | 0.359373E+10 | 0.100473E+10 | 0.00 | 0.38 | 19-AUG-13:00 | 0.00 | 02-AUG-05:05 | 3834.35 | 19-AUG-13:00 | 3095.28 | 19-AUG-13:40 | 793.23 | 19-AUG-09:10 | 974.40 | 17-AUG-14:00 | 0.00 | 01-AUG-00:10 |
| September | 0.389132E+10 | 0.976298E+09 | 706.49 | 0.328425E+10 | 0.607068E+09 | 0.00 | 0.56 | 29-SEP-13:00 | 0.00 | 01-SEP-06:40 | 5026.54 | 29-SEP-13:00 | 5026.54 | 29-SEP-13:00 | 877.35 | 22-SEP-11:50 | 1468.66 | 29-SEP-13:00 | 0.00 | 01-SEP-00:10 |
| October | 0.432139E+10 | 0.109925E+10 | 683.27 | 0.390531E+10 | 0.416079E+09 | 0.00 | 0.63 | 16-OCT-12:00 | 0.00 | 07-OCT-05:05 | 5596.26 | 16-OCT-12:00 | 5596.26 | 16-OCT-12:00 | 1014.85 | 01-OCT-11:30 | 1621.82 | 16-OCT-12:00 | 0.00 | 01-OCT-00:10 |
| November | 0.226271E+10 | 0.578801E+09 | 546.89 | 0.217036E+10 | 92347371.51 | 0.00 | 0.47 | 19-NOV-13:00 | 0.00 | 02-NOV-05:40 | 4533.14 | 19-NOV-13:00 | 4533.14 | 19-NOV-13:00 | 394.50 | 10-NOV-13:00 | 1166.37 | 19-NOV-13:00 | 0.00 | 01-NOV-00:10 |
| December | 0.228896E+10 | 0.588502E+09 | 505.43 | 0.225385E+10 | 35100637.84 | 0.00 | 0.46 | 19-DEC-13:00 | 0.00 | 01-DEC-00:10 | 4241.37 | 19-DEC-13:00 | 4241.37 | 19-DEC-13:00 | 248.87 | 07-DEC-14:00 | 1094.76 | 19-DEC-13:00 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.308012E+11 | 0.776666E+10 | 6753.93 | 0.270144E+11 | 0.378679E+10 | 0.00 | ||||||||||||||
| Minimum of Months | 0.928970E+09 | 0.236167E+09 | 309.97 | 0.854314E+09 | 29160837.58 | 0.00 | 0.25 | 0.00 | 2375.03 | 2071.19 | 247.71 | 596.07 | 0.00 | |||||||
| Maximum of Months | 0.459847E+10 | 0.113249E+10 | 739.43 | 0.390531E+10 | 0.100473E+10 | 0.00 | 0.63 | 0.00 | 5596.26 | 5596.26 | 1014.85 | 1621.82 | 0.00 |
Report: DXReportMonthly
For: SPLIT MS2 COOLING COIL
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.193199E+10 | 0.495423E+09 | 472.73 | 0.187771E+10 | 54276109.46 | 0.00 | 0.41 | 14-JAN-14:30 | 0.00 | 01-JAN-00:10 | 3818.56 | 18-JAN-13:30 | 3818.56 | 18-JAN-13:30 | 280.70 | 20-JAN-17:30 | 969.29 | 18-JAN-13:30 | 0.00 | 01-JAN-00:10 |
| February | 0.119696E+10 | 0.307826E+09 | 324.33 | 0.116788E+10 | 29077541.38 | 0.00 | 0.37 | 01-FEB-12:00 | 0.00 | 01-FEB-05:30 | 3436.50 | 01-FEB-12:10 | 3436.50 | 01-FEB-12:10 | 246.35 | 01-FEB-17:13 | 889.87 | 01-FEB-12:00 | 0.00 | 01-FEB-00:10 |
| March | 0.932822E+09 | 0.237112E+09 | 310.55 | 0.857889E+09 | 74933323.32 | 0.00 | 0.31 | 11-MAR-13:50 | 0.00 | 01-MAR-00:10 | 3003.56 | 23-MAR-14:00 | 2951.21 | 11-MAR-13:50 | 402.66 | 23-MAR-16:10 | 745.82 | 11-MAR-13:50 | 0.00 | 01-MAR-00:10 |
| April | 0.182888E+10 | 0.463780E+09 | 537.83 | 0.166171E+10 | 0.167162E+09 | 0.00 | 0.33 | 26-APR-13:00 | 0.00 | 01-APR-00:10 | 3175.71 | 26-APR-13:00 | 2980.96 | 26-APR-13:00 | 401.83 | 08-APR-12:20 | 824.68 | 26-APR-13:00 | 0.00 | 01-APR-00:10 |
| May | 0.126965E+10 | 0.324069E+09 | 511.30 | 0.115888E+10 | 0.110766E+09 | 0.00 | 0.25 | 04-MAY-12:00 | 0.00 | 01-MAY-23:20 | 2388.80 | 04-MAY-12:00 | 2233.99 | 03-MAY-13:00 | 260.81 | 02-MAY-21:05 | 599.38 | 04-MAY-12:00 | 0.00 | 01-MAY-00:10 |
| June | 0.230553E+10 | 0.579236E+09 | 677.40 | 0.194813E+10 | 0.357403E+09 | 0.00 | 0.26 | 29-JUN-16:07 | 0.00 | 01-JUN-00:50 | 2558.79 | 29-JUN-16:07 | 2082.98 | 25-JUN-13:00 | 606.25 | 28-JUN-11:00 | 624.96 | 29-JUN-16:07 | 0.00 | 01-JUN-00:10 |
| July | 0.397295E+10 | 0.983808E+09 | 738.21 | 0.313770E+10 | 0.835253E+09 | 0.00 | 0.36 | 31-JUL-13:00 | 0.00 | 06-JUL-05:50 | 3553.26 | 31-JUL-13:00 | 2842.02 | 31-JUL-13:00 | 819.72 | 29-JUL-12:00 | 915.78 | 31-JUL-13:00 | 0.00 | 01-JUL-00:10 |
| August | 0.459686E+10 | 0.113199E+10 | 739.43 | 0.359270E+10 | 0.100416E+10 | 0.00 | 0.38 | 19-AUG-13:00 | 0.00 | 02-AUG-05:05 | 3848.72 | 19-AUG-13:00 | 3105.40 | 19-AUG-13:40 | 798.55 | 19-AUG-09:10 | 975.89 | 17-AUG-14:00 | 0.00 | 01-AUG-00:10 |
| September | 0.388217E+10 | 0.973952E+09 | 705.90 | 0.327637E+10 | 0.605802E+09 | 0.00 | 0.56 | 29-SEP-13:00 | 0.00 | 01-SEP-06:40 | 5036.71 | 29-SEP-13:00 | 5036.71 | 29-SEP-13:00 | 877.52 | 22-SEP-11:50 | 1471.17 | 29-SEP-13:00 | 0.00 | 01-SEP-00:10 |
| October | 0.432030E+10 | 0.109892E+10 | 683.06 | 0.390471E+10 | 0.415587E+09 | 0.00 | 0.63 | 16-OCT-12:00 | 0.00 | 07-OCT-05:05 | 5609.61 | 16-OCT-12:00 | 5609.61 | 16-OCT-12:00 | 1015.09 | 01-OCT-11:30 | 1625.07 | 16-OCT-12:00 | 0.00 | 01-OCT-00:10 |
| November | 0.226266E+10 | 0.578756E+09 | 546.74 | 0.217057E+10 | 92095500.58 | 0.00 | 0.48 | 19-NOV-13:00 | 0.00 | 01-NOV-04:00 | 4541.61 | 19-NOV-13:00 | 4541.61 | 19-NOV-13:00 | 394.43 | 10-NOV-13:00 | 1168.26 | 19-NOV-13:00 | 0.00 | 01-NOV-00:10 |
| December | 0.229336E+10 | 0.589572E+09 | 505.43 | 0.225828E+10 | 35084749.22 | 0.00 | 0.46 | 19-DEC-13:00 | 0.00 | 01-DEC-00:10 | 4248.38 | 19-DEC-13:00 | 4248.38 | 19-DEC-13:00 | 249.06 | 07-DEC-14:00 | 1096.32 | 19-DEC-13:00 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.307941E+11 | 0.776445E+10 | 6752.90 | 0.270125E+11 | 0.378160E+10 | 0.00 | ||||||||||||||
| Minimum of Months | 0.932822E+09 | 0.237112E+09 | 310.55 | 0.857889E+09 | 29077541.38 | 0.00 | 0.25 | 0.00 | 2388.80 | 2082.98 | 246.35 | 599.38 | 0.00 | |||||||
| Maximum of Months | 0.459686E+10 | 0.113199E+10 | 739.43 | 0.390471E+10 | 0.100416E+10 | 0.00 | 0.63 | 0.00 | 5609.61 | 5609.61 | 1015.09 | 1625.07 | 0.00 |
Report: DXReportMonthly
For: SPLIT TSW COOLING COIL
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.510971E+09 | 0.131229E+09 | 197.87 | 0.502405E+09 | 8565756.23 | 0.00 | 0.46 | 14-JAN-15:00 | 0.00 | 01-JAN-00:10 | 2668.07 | 14-JAN-15:00 | 2668.07 | 14-JAN-15:00 | 138.28 | 20-JAN-13:30 | 683.47 | 14-JAN-15:00 | 0.00 | 01-JAN-00:10 |
| February | 0.307518E+09 | 79093236.79 | 121.62 | 0.300902E+09 | 6615724.56 | 0.00 | 0.35 | 03-FEB-15:00 | 0.00 | 01-FEB-00:10 | 1957.96 | 03-FEB-15:00 | 1957.96 | 03-FEB-15:00 | 159.57 | 01-FEB-16:20 | 500.76 | 03-FEB-15:00 | 0.00 | 01-FEB-00:10 |
| March | 0.372481E+09 | 93919963.31 | 127.14 | 0.343327E+09 | 29153601.92 | 0.00 | 0.38 | 23-MAR-15:30 | 0.00 | 01-MAR-00:10 | 2344.60 | 23-MAR-15:30 | 2206.45 | 11-MAR-14:00 | 331.47 | 23-MAR-15:40 | 568.72 | 23-MAR-15:30 | 0.00 | 01-MAR-00:10 |
| April | 0.851584E+09 | 0.213909E+09 | 248.00 | 0.782384E+09 | 69200045.44 | 0.00 | 0.42 | 26-APR-14:10 | 0.00 | 01-APR-00:10 | 2522.11 | 26-APR-14:10 | 2426.34 | 26-APR-14:10 | 263.26 | 25-APR-13:30 | 633.75 | 26-APR-14:00 | 0.00 | 01-APR-00:10 |
| May | 0.555606E+09 | 0.140822E+09 | 222.67 | 0.515888E+09 | 39718394.33 | 0.00 | 0.35 | 03-MAY-15:10 | 0.00 | 01-MAY-00:10 | 2077.00 | 03-MAY-15:10 | 1944.15 | 03-MAY-15:10 | 193.91 | 04-MAY-14:00 | 512.72 | 03-MAY-15:10 | 0.00 | 01-MAY-00:10 |
| June | 0.120273E+10 | 0.298170E+09 | 345.98 | 0.103061E+10 | 0.172120E+09 | 0.00 | 0.41 | 29-JUN-16:13 | 0.00 | 01-JUN-00:10 | 2579.91 | 29-JUN-16:13 | 2134.89 | 30-JUN-16:07 | 475.42 | 29-JUN-16:03 | 618.23 | 29-JUN-16:13 | 0.00 | 01-JUN-00:10 |
| July | 0.230635E+10 | 0.564305E+09 | 503.64 | 0.186947E+10 | 0.436873E+09 | 0.00 | 0.50 | 19-JUL-15:10 | 0.00 | 01-JUL-00:10 | 3088.34 | 19-JUL-15:10 | 2581.68 | 19-JUL-15:10 | 684.02 | 29-JUL-16:10 | 766.04 | 19-JUL-15:10 | 0.00 | 01-JUL-00:10 |
| August | 0.253452E+10 | 0.616520E+09 | 490.86 | 0.203257E+10 | 0.501946E+09 | 0.00 | 0.54 | 17-AUG-15:10 | 0.00 | 01-AUG-00:50 | 3388.20 | 17-AUG-15:10 | 2827.81 | 17-AUG-15:10 | 629.30 | 13-AUG-16:50 | 832.40 | 17-AUG-14:30 | 0.00 | 01-AUG-00:10 |
| September | 0.181534E+10 | 0.452886E+09 | 412.88 | 0.155858E+10 | 0.256762E+09 | 0.00 | 0.73 | 29-SEP-13:40 | 0.00 | 01-SEP-00:10 | 4189.99 | 29-SEP-14:10 | 4189.99 | 29-SEP-14:10 | 568.32 | 21-SEP-13:40 | 1164.41 | 29-SEP-13:30 | 0.00 | 01-SEP-00:10 |
| October | 0.187994E+10 | 0.477952E+09 | 420.39 | 0.171047E+10 | 0.169465E+09 | 0.00 | 0.75 | 16-OCT-12:40 | 0.00 | 02-OCT-05:05 | 4244.33 | 16-OCT-13:20 | 4244.33 | 16-OCT-13:20 | 669.40 | 01-OCT-12:00 | 1177.43 | 16-OCT-12:00 | 0.00 | 01-OCT-00:10 |
| November | 0.564335E+09 | 0.144268E+09 | 194.19 | 0.548284E+09 | 16051245.77 | 0.00 | 0.49 | 19-NOV-13:30 | 0.00 | 01-NOV-00:10 | 2927.04 | 19-NOV-13:30 | 2927.04 | 19-NOV-13:30 | 257.75 | 10-NOV-13:30 | 739.71 | 19-NOV-13:20 | 0.00 | 01-NOV-00:10 |
| December | 0.639348E+09 | 0.164360E+09 | 190.75 | 0.635231E+09 | 4117608.31 | 0.00 | 0.44 | 19-DEC-13:30 | 0.00 | 01-DEC-00:10 | 2530.28 | 05-DEC-15:00 | 2530.28 | 05-DEC-15:00 | 172.57 | 07-DEC-14:00 | 640.17 | 05-DEC-15:00 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.135407E+11 | 0.337743E+10 | 3475.98 | 0.118301E+11 | 0.171059E+10 | 0.00 | ||||||||||||||
| Minimum of Months | 0.307518E+09 | 79093236.79 | 121.62 | 0.300902E+09 | 4117608.31 | 0.00 | 0.35 | 0.00 | 1957.96 | 1944.15 | 138.28 | 500.76 | 0.00 | |||||||
| Maximum of Months | 0.253452E+10 | 0.616520E+09 | 503.64 | 0.203257E+10 | 0.501946E+09 | 0.00 | 0.75 | 0.00 | 4244.33 | 4244.33 | 684.02 | 1177.43 | 0.00 |
Report: DXReportMonthly
For: SPLIT TNW COOLING COIL
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 49393717.29 | 12946870.06 | 38.58 | 48822427.51 | 571289.78 | 0.00 | 0.16 | 14-JAN-15:10 | 0.00 | 01-JAN-00:10 | 878.46 | 18-JAN-14:30 | 878.46 | 18-JAN-14:30 | 64.63 | 17-JAN-14:00 | 231.16 | 14-JAN-15:00 | 0.00 | 01-JAN-00:10 |
| February | 7655238.84 | 2018415.79 | 7.89 | 7392805.03 | 262433.82 | 0.00 | 0.09 | 03-FEB-15:10 | 0.00 | 01-FEB-00:10 | 473.52 | 03-FEB-15:10 | 473.52 | 03-FEB-15:10 | 42.29 | 01-FEB-16:10 | 126.02 | 03-FEB-15:10 | 0.00 | 01-FEB-00:10 |
| March | 66194781.95 | 16845735.82 | 37.74 | 59180603.92 | 7014178.03 | 0.00 | 0.25 | 23-MAR-16:05 | 0.00 | 01-MAR-00:10 | 1433.87 | 23-MAR-16:05 | 1176.97 | 23-MAR-16:05 | 256.93 | 23-MAR-16:03 | 352.89 | 23-MAR-16:05 | 0.00 | 01-MAR-00:10 |
| April | 0.389261E+09 | 98399012.46 | 170.72 | 0.350772E+09 | 38488293.68 | 0.00 | 0.36 | 26-APR-16:20 | 0.00 | 01-APR-00:10 | 2048.39 | 26-APR-16:20 | 1863.94 | 26-APR-16:20 | 215.37 | 11-APR-15:30 | 503.06 | 26-APR-16:20 | 0.00 | 01-APR-00:10 |
| May | 0.441756E+09 | 0.112112E+09 | 208.72 | 0.407715E+09 | 34041046.42 | 0.00 | 0.32 | 03-MAY-15:10 | 0.00 | 01-MAY-00:10 | 1831.18 | 03-MAY-15:10 | 1705.37 | 03-MAY-15:20 | 183.31 | 04-MAY-15:20 | 453.40 | 03-MAY-15:10 | 0.00 | 01-MAY-00:10 |
| June | 0.117971E+10 | 0.292357E+09 | 357.50 | 0.100637E+10 | 0.173341E+09 | 0.00 | 0.44 | 29-JUN-16:40 | 0.00 | 01-JUN-00:10 | 2637.72 | 29-JUN-16:40 | 2153.26 | 29-JUN-16:40 | 495.12 | 29-JUN-16:13 | 629.29 | 29-JUN-16:40 | 0.00 | 01-JUN-00:10 |
| July | 0.216860E+10 | 0.531000E+09 | 507.38 | 0.174550E+10 | 0.423098E+09 | 0.00 | 0.51 | 19-JUL-16:12 | 0.00 | 01-JUL-00:10 | 3056.23 | 19-JUL-16:25 | 2529.67 | 19-JUL-16:30 | 633.86 | 29-JUL-16:20 | 733.89 | 19-JUL-15:10 | 0.00 | 01-JUL-00:10 |
| August | 0.204606E+10 | 0.499729E+09 | 468.33 | 0.160716E+10 | 0.438892E+09 | 0.00 | 0.49 | 17-AUG-15:20 | 0.00 | 01-AUG-00:40 | 2949.13 | 17-AUG-16:03 | 2419.49 | 17-AUG-16:05 | 583.47 | 06-AUG-16:40 | 724.12 | 17-AUG-15:10 | 0.00 | 01-AUG-00:10 |
| September | 0.103952E+10 | 0.263190E+09 | 348.03 | 0.876381E+09 | 0.163134E+09 | 0.00 | 0.58 | 29-SEP-15:10 | 0.00 | 01-SEP-00:10 | 3154.30 | 29-SEP-15:20 | 3154.30 | 29-SEP-15:20 | 548.91 | 22-SEP-12:00 | 872.34 | 29-SEP-15:10 | 0.00 | 01-SEP-00:10 |
| October | 0.939920E+09 | 0.243243E+09 | 322.18 | 0.822533E+09 | 0.117388E+09 | 0.00 | 0.54 | 14-OCT-15:10 | 0.00 | 02-OCT-05:05 | 2853.97 | 14-OCT-15:10 | 2853.97 | 14-OCT-15:10 | 547.44 | 01-OCT-15:10 | 803.08 | 16-OCT-12:00 | 0.00 | 01-OCT-00:10 |
| November | 38277833.73 | 10095437.54 | 33.17 | 37653054.93 | 624778.79 | 0.00 | 0.18 | 19-NOV-13:50 | 0.00 | 01-NOV-00:10 | 947.19 | 19-NOV-13:50 | 947.19 | 19-NOV-13:50 | 42.83 | 10-NOV-14:30 | 249.43 | 19-NOV-13:40 | 0.00 | 01-NOV-00:10 |
| December | 43121374.22 | 11409464.26 | 36.00 | 43121374.22 | 0.00 | 0.00 | 0.19 | 05-DEC-15:10 | 0.00 | 01-DEC-00:10 | 1027.47 | 05-DEC-15:10 | 1027.47 | 05-DEC-15:10 | 0.00 | 05-DEC-15:00 | 268.65 | 05-DEC-15:10 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.840946E+10 | 0.209334E+10 | 2536.23 | 0.701260E+10 | 0.139686E+10 | 0.00 | ||||||||||||||
| Minimum of Months | 7655238.84 | 2018415.79 | 7.89 | 7392805.03 | 0.00 | 0.00 | 0.09 | 0.00 | 473.52 | 473.52 | 0.00 | 126.02 | 0.00 | |||||||
| Maximum of Months | 0.216860E+10 | 0.531000E+09 | 507.38 | 0.174550E+10 | 0.438892E+09 | 0.00 | 0.58 | 0.00 | 3154.30 | 3154.30 | 633.86 | 872.34 | 0.00 |
Report: DXReportMonthly
For: SPLIT TSE COOLING COIL
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.512873E+09 | 0.131509E+09 | 207.36 | 0.503622E+09 | 9250288.63 | 0.00 | 0.45 | 14-JAN-14:30 | 0.00 | 01-JAN-00:10 | 2359.93 | 18-JAN-13:50 | 2359.93 | 18-JAN-13:50 | 144.42 | 20-JAN-13:30 | 592.48 | 18-JAN-13:40 | 0.00 | 01-JAN-00:10 |
| February | 0.279708E+09 | 72003313.89 | 127.31 | 0.274454E+09 | 5254480.99 | 0.00 | 0.38 | 01-FEB-12:40 | 0.00 | 01-FEB-00:10 | 1981.02 | 01-FEB-12:40 | 1981.02 | 01-FEB-12:40 | 118.06 | 01-FEB-16:10 | 502.86 | 01-FEB-12:20 | 0.00 | 01-FEB-00:10 |
| March | 0.357840E+09 | 90072884.57 | 126.50 | 0.331212E+09 | 26628440.01 | 0.00 | 0.41 | 11-MAR-13:50 | 0.00 | 01-MAR-00:10 | 2163.21 | 11-MAR-13:40 | 2163.21 | 11-MAR-13:40 | 262.73 | 23-MAR-15:20 | 538.73 | 11-MAR-13:50 | 0.00 | 01-MAR-00:10 |
| April | 0.803840E+09 | 0.201598E+09 | 240.82 | 0.739748E+09 | 64091844.05 | 0.00 | 0.47 | 26-APR-13:00 | 0.00 | 01-APR-00:10 | 2531.74 | 26-APR-13:00 | 2406.32 | 26-APR-13:00 | 274.82 | 08-APR-12:20 | 644.29 | 26-APR-13:00 | 0.00 | 01-APR-00:10 |
| May | 0.486102E+09 | 0.122998E+09 | 212.46 | 0.451439E+09 | 34663157.70 | 0.00 | 0.38 | 04-MAY-12:00 | 0.00 | 01-MAY-00:10 | 2050.58 | 04-MAY-12:00 | 1929.29 | 04-MAY-12:00 | 201.06 | 03-MAY-09:30 | 504.89 | 04-MAY-12:00 | 0.00 | 01-MAY-00:10 |
| June | 0.112304E+10 | 0.277767E+09 | 313.74 | 0.962455E+09 | 0.160584E+09 | 0.00 | 0.40 | 30-JUN-12:00 | 0.00 | 01-JUN-00:10 | 2245.00 | 30-JUN-12:00 | 1891.45 | 30-JUN-12:00 | 464.04 | 28-JUN-11:00 | 542.23 | 30-JUN-12:00 | 0.00 | 01-JUN-00:10 |
| July | 0.226114E+10 | 0.551631E+09 | 490.99 | 0.183031E+10 | 0.430831E+09 | 0.00 | 0.53 | 31-JUL-13:00 | 0.00 | 01-JUL-00:10 | 2984.47 | 31-JUL-13:00 | 2454.57 | 31-JUL-13:00 | 616.04 | 20-JUL-11:00 | 750.74 | 31-JUL-13:00 | 0.00 | 01-JUL-00:10 |
| August | 0.252998E+10 | 0.612881E+09 | 482.50 | 0.202865E+10 | 0.501335E+09 | 0.00 | 0.56 | 19-AUG-13:00 | 0.00 | 01-AUG-00:10 | 3156.74 | 19-AUG-13:00 | 2630.17 | 19-AUG-13:00 | 650.67 | 19-AUG-09:00 | 785.08 | 18-AUG-12:00 | 0.00 | 01-AUG-00:10 |
| September | 0.171896E+10 | 0.427690E+09 | 397.29 | 0.147641E+10 | 0.242552E+09 | 0.00 | 0.81 | 29-SEP-13:00 | 0.00 | 01-SEP-00:10 | 4161.61 | 29-SEP-13:00 | 4161.61 | 29-SEP-13:00 | 553.85 | 22-SEP-12:00 | 1166.79 | 29-SEP-13:00 | 0.00 | 01-SEP-00:10 |
| October | 0.183553E+10 | 0.465766E+09 | 416.98 | 0.167448E+10 | 0.161048E+09 | 0.00 | 0.87 | 16-OCT-12:00 | 0.00 | 02-OCT-05:05 | 4457.23 | 16-OCT-12:00 | 4457.23 | 16-OCT-12:00 | 667.59 | 01-OCT-12:00 | 1240.09 | 16-OCT-11:50 | 0.00 | 01-OCT-00:10 |
| November | 0.523759E+09 | 0.133735E+09 | 180.43 | 0.511020E+09 | 12738567.42 | 0.00 | 0.55 | 19-NOV-13:00 | 0.00 | 01-NOV-00:10 | 2962.13 | 19-NOV-13:00 | 2962.13 | 19-NOV-13:00 | 236.44 | 10-NOV-13:00 | 752.40 | 19-NOV-13:00 | 0.00 | 01-NOV-00:10 |
| December | 0.626559E+09 | 0.160835E+09 | 196.81 | 0.623363E+09 | 3195656.99 | 0.00 | 0.50 | 19-DEC-13:00 | 0.00 | 01-DEC-00:10 | 2548.51 | 19-DEC-13:00 | 2548.51 | 19-DEC-13:00 | 159.85 | 07-DEC-13:50 | 653.73 | 19-DEC-13:00 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.130593E+11 | 0.324849E+10 | 3393.19 | 0.114072E+11 | 0.165217E+10 | 0.00 | ||||||||||||||
| Minimum of Months | 0.279708E+09 | 72003313.89 | 126.50 | 0.274454E+09 | 3195656.99 | 0.00 | 0.38 | 0.00 | 1981.02 | 1891.45 | 118.06 | 502.86 | 0.00 | |||||||
| Maximum of Months | 0.252998E+10 | 0.612881E+09 | 490.99 | 0.202865E+10 | 0.501335E+09 | 0.00 | 0.87 | 0.00 | 4457.23 | 4457.23 | 667.59 | 1240.09 | 0.00 |
Report: DXReportMonthly
For: SPLIT TNE COOLING COIL
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 48638159.31 | 12760973.33 | 43.67 | 47843861.70 | 794297.61 | 0.00 | 0.15 | 18-JAN-13:00 | 0.00 | 01-JAN-00:10 | 726.49 | 18-JAN-13:00 | 726.49 | 18-JAN-13:00 | 71.12 | 17-JAN-14:00 | 193.78 | 18-JAN-13:00 | 0.00 | 01-JAN-00:10 |
| February | 5809033.93 | 1543657.79 | 6.67 | 5803692.03 | 5341.90 | 0.00 | 0.12 | 01-FEB-12:00 | 0.00 | 01-FEB-00:10 | 556.72 | 01-FEB-12:00 | 556.72 | 01-FEB-12:00 | 4.76 | 01-FEB-15:00 | 149.70 | 01-FEB-12:00 | 0.00 | 01-FEB-00:10 |
| March | 56515661.23 | 14455333.95 | 38.72 | 51126490.55 | 5389170.68 | 0.00 | 0.17 | 23-MAR-14:00 | 0.00 | 01-MAR-00:10 | 891.23 | 23-MAR-14:00 | 753.12 | 11-MAR-14:00 | 151.04 | 23-MAR-15:20 | 222.44 | 23-MAR-14:00 | 0.00 | 01-MAR-00:10 |
| April | 0.353020E+09 | 89377499.53 | 160.01 | 0.318537E+09 | 34483230.42 | 0.00 | 0.36 | 26-APR-13:00 | 0.00 | 01-APR-00:10 | 1822.99 | 26-APR-13:00 | 1704.08 | 26-APR-13:00 | 213.62 | 27-APR-10:00 | 471.04 | 26-APR-13:00 | 0.00 | 01-APR-00:10 |
| May | 0.373505E+09 | 94727398.63 | 192.08 | 0.344475E+09 | 29030302.80 | 0.00 | 0.33 | 04-MAY-12:00 | 0.00 | 01-MAY-00:10 | 1707.36 | 04-MAY-12:00 | 1592.87 | 04-MAY-12:00 | 195.23 | 03-MAY-09:30 | 422.88 | 04-MAY-12:00 | 0.00 | 01-MAY-00:10 |
| June | 0.109772E+10 | 0.271530E+09 | 333.60 | 0.935848E+09 | 0.161871E+09 | 0.00 | 0.41 | 30-JUN-10:00 | 0.00 | 01-JUN-00:10 | 2196.48 | 30-JUN-10:00 | 1799.11 | 30-JUN-10:00 | 449.87 | 28-JUN-11:00 | 527.59 | 30-JUN-10:00 | 0.00 | 01-JUN-00:10 |
| July | 0.212604E+10 | 0.519264E+09 | 498.09 | 0.170816E+10 | 0.417879E+09 | 0.00 | 0.51 | 19-JUL-12:00 | 0.00 | 01-JUL-00:10 | 2728.00 | 19-JUL-12:00 | 2271.27 | 19-JUL-12:00 | 570.51 | 20-JUL-11:00 | 689.13 | 19-JUL-12:00 | 0.00 | 01-JUL-00:10 |
| August | 0.204561E+10 | 0.498080E+09 | 456.61 | 0.160604E+10 | 0.439567E+09 | 0.00 | 0.49 | 14-AUG-11:00 | 0.00 | 01-AUG-00:10 | 2634.79 | 14-AUG-11:00 | 2125.67 | 14-AUG-11:00 | 586.17 | 18-AUG-09:30 | 665.10 | 14-AUG-11:00 | 0.00 | 01-AUG-00:10 |
| September | 0.954760E+09 | 0.241808E+09 | 320.31 | 0.805874E+09 | 0.148886E+09 | 0.00 | 0.62 | 29-SEP-13:00 | 0.00 | 01-SEP-00:10 | 2958.98 | 29-SEP-13:00 | 2958.98 | 29-SEP-13:00 | 551.05 | 22-SEP-12:00 | 855.56 | 29-SEP-13:00 | 0.00 | 01-SEP-00:10 |
| October | 0.896079E+09 | 0.232487E+09 | 320.17 | 0.787718E+09 | 0.108361E+09 | 0.00 | 0.65 | 16-OCT-11:00 | 0.00 | 02-OCT-05:05 | 3042.36 | 16-OCT-11:50 | 3042.36 | 16-OCT-11:50 | 504.37 | 01-OCT-12:00 | 889.35 | 16-OCT-11:00 | 0.00 | 01-OCT-00:10 |
| November | 35152265.36 | 9329415.69 | 28.17 | 35013075.47 | 139189.90 | 0.00 | 0.20 | 19-NOV-13:00 | 0.00 | 01-NOV-00:10 | 985.39 | 19-NOV-13:00 | 985.39 | 19-NOV-13:00 | 24.69 | 10-NOV-13:00 | 264.59 | 19-NOV-13:00 | 0.00 | 01-NOV-00:10 |
| December | 38814463.50 | 10295338.21 | 34.83 | 38814463.50 | 0.00 | 0.00 | 0.16 | 05-DEC-15:00 | 0.00 | 01-DEC-00:10 | 757.69 | 05-DEC-15:00 | 757.69 | 05-DEC-15:00 | 0.00 | 05-DEC-10:50 | 200.09 | 05-DEC-15:00 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.803167E+10 | 0.199566E+10 | 2432.93 | 0.668526E+10 | 0.134641E+10 | 0.00 | ||||||||||||||
| Minimum of Months | 5809033.93 | 1543657.79 | 6.67 | 5803692.03 | 0.00 | 0.00 | 0.12 | 0.00 | 556.72 | 556.72 | 0.00 | 149.70 | 0.00 | |||||||
| Maximum of Months | 0.212604E+10 | 0.519264E+09 | 498.09 | 0.170816E+10 | 0.439567E+09 | 0.00 | 0.65 | 0.00 | 3042.36 | 3042.36 | 586.17 | 889.35 | 0.00 |
Report: DXReportMonthly
For: SPLIT TN1 COOLING COIL
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 33223534.14 | 8728384.38 | 39.17 | 32612576.90 | 610957.24 | 0.00 | 0.13 | 18-JAN-13:40 | 0.00 | 01-JAN-00:10 | 574.43 | 18-JAN-13:50 | 574.43 | 18-JAN-13:50 | 57.18 | 17-JAN-14:00 | 151.45 | 18-JAN-13:40 | 0.00 | 01-JAN-00:10 |
| February | 1853939.78 | 496187.64 | 3.50 | 1853939.78 | -0.0 | 0.00 | 0.06 | 01-FEB-12:50 | 0.00 | 01-FEB-00:10 | 258.38 | 01-FEB-12:50 | 258.38 | 01-FEB-12:50 | 0.00 | 01-FEB-13:00 | 68.37 | 01-FEB-12:50 | 0.00 | 01-FEB-00:10 |
| March | 20584963.37 | 5289997.44 | 22.58 | 18476877.65 | 2108085.72 | 0.00 | 0.12 | 23-MAR-15:10 | 0.00 | 01-MAR-00:10 | 562.03 | 23-MAR-15:10 | 466.74 | 11-MAR-14:00 | 115.00 | 23-MAR-16:10 | 140.87 | 23-MAR-15:10 | 0.00 | 01-MAR-00:10 |
| April | 0.205790E+09 | 52323188.34 | 138.97 | 0.183088E+09 | 22701462.82 | 0.00 | 0.28 | 26-APR-13:00 | 0.00 | 01-APR-00:10 | 1327.78 | 26-APR-13:00 | 1232.02 | 26-APR-13:40 | 143.36 | 25-APR-13:20 | 346.72 | 26-APR-13:00 | 0.00 | 01-APR-00:10 |
| May | 0.254423E+09 | 64803786.38 | 195.84 | 0.232314E+09 | 22108667.64 | 0.00 | 0.26 | 03-MAY-13:00 | 0.00 | 01-MAY-00:10 | 1236.12 | 04-MAY-12:00 | 1201.45 | 03-MAY-13:00 | 139.87 | 04-MAY-15:20 | 309.58 | 03-MAY-13:00 | 0.00 | 01-MAY-00:10 |
| June | 0.875845E+09 | 0.218090E+09 | 387.30 | 0.737825E+09 | 0.138021E+09 | 0.00 | 0.34 | 29-JUN-17:10 | 0.00 | 01-JUN-00:10 | 1683.56 | 29-JUN-17:10 | 1339.67 | 29-JUN-17:05 | 367.48 | 28-JUN-11:00 | 406.90 | 29-JUN-17:10 | 0.00 | 01-JUN-00:10 |
| July | 0.170845E+10 | 0.420416E+09 | 568.51 | 0.135397E+10 | 0.354484E+09 | 0.00 | 0.41 | 19-JUL-15:10 | 0.00 | 01-JUL-02:70 | 2054.81 | 19-JUL-15:10 | 1681.69 | 19-JUL-15:10 | 454.28 | 29-JUL-14:00 | 523.50 | 31-JUL-13:00 | 0.00 | 01-JUL-00:10 |
| August | 0.161777E+10 | 0.397013E+09 | 528.45 | 0.124979E+10 | 0.367982E+09 | 0.00 | 0.41 | 17-AUG-14:10 | 0.00 | 01-AUG-03:00 | 2042.27 | 17-AUG-14:10 | 1629.04 | 17-AUG-14:10 | 428.14 | 18-AUG-11:00 | 520.08 | 17-AUG-14:10 | 0.00 | 01-AUG-00:10 |
| September | 0.776702E+09 | 0.197545E+09 | 364.75 | 0.646421E+09 | 0.130281E+09 | 0.00 | 0.51 | 29-SEP-13:00 | 0.00 | 01-SEP-00:10 | 2244.07 | 29-SEP-13:00 | 2244.07 | 29-SEP-13:00 | 493.64 | 22-SEP-12:00 | 661.24 | 29-SEP-13:00 | 0.00 | 01-SEP-00:10 |
| October | 0.762476E+09 | 0.197281E+09 | 329.28 | 0.653317E+09 | 0.109159E+09 | 0.00 | 0.52 | 16-OCT-12:00 | 0.00 | 02-OCT-05:40 | 2249.82 | 16-OCT-12:00 | 2249.82 | 16-OCT-12:00 | 449.24 | 01-OCT-12:00 | 663.81 | 16-OCT-12:00 | 0.00 | 01-OCT-00:10 |
| November | 17056975.06 | 4550806.60 | 18.17 | 16989149.05 | 67826.02 | 0.00 | 0.15 | 19-NOV-13:00 | 0.00 | 01-NOV-00:10 | 674.68 | 19-NOV-13:00 | 674.68 | 19-NOV-13:00 | 16.15 | 10-NOV-13:00 | 182.76 | 19-NOV-13:00 | 0.00 | 01-NOV-00:10 |
| December | 20717830.68 | 5505202.51 | 26.81 | 20717830.68 | -0.0 | 0.00 | 0.13 | 05-DEC-15:00 | 0.00 | 01-DEC-00:10 | 586.59 | 05-DEC-15:00 | 586.59 | 05-DEC-15:00 | 0.00 | 05-DEC-15:10 | 155.57 | 05-DEC-15:00 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.629490E+10 | 0.157204E+10 | 2623.32 | 0.514738E+10 | 0.114752E+10 | 0.00 | ||||||||||||||
| Minimum of Months | 1853939.78 | 496187.64 | 3.50 | 1853939.78 | -0.0 | 0.00 | 0.06 | 0.00 | 258.38 | 258.38 | 0.00 | 68.37 | 0.00 | |||||||
| Maximum of Months | 0.170845E+10 | 0.420416E+09 | 568.51 | 0.135397E+10 | 0.367982E+09 | 0.00 | 0.52 | 0.00 | 2249.82 | 2249.82 | 493.64 | 663.81 | 0.00 |
Report: DXReportMonthly
For: SPLIT TN2 COOLING COIL
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 34004412.94 | 8932060.80 | 39.50 | 33367545.37 | 636867.58 | 0.00 | 0.13 | 18-JAN-13:40 | 0.00 | 01-JAN-00:10 | 582.47 | 18-JAN-13:40 | 582.47 | 18-JAN-13:40 | 57.90 | 17-JAN-14:00 | 154.42 | 18-JAN-13:00 | 0.00 | 01-JAN-00:10 |
| February | 2009840.04 | 537758.21 | 3.83 | 2009840.04 | -0.0 | 0.00 | 0.06 | 01-FEB-12:40 | 0.00 | 01-FEB-00:10 | 269.44 | 01-FEB-12:50 | 269.44 | 01-FEB-12:50 | 0.00 | 01-FEB-12:50 | 71.49 | 01-FEB-12:40 | 0.00 | 01-FEB-00:10 |
| March | 21791810.67 | 5599326.54 | 23.38 | 19572726.41 | 2219084.26 | 0.00 | 0.12 | 23-MAR-15:10 | 0.00 | 01-MAR-00:10 | 568.68 | 23-MAR-15:10 | 479.64 | 11-MAR-14:00 | 113.94 | 23-MAR-16:10 | 142.52 | 23-MAR-15:10 | 0.00 | 01-MAR-00:10 |
| April | 0.209066E+09 | 53152171.53 | 140.38 | 0.186163E+09 | 22903835.41 | 0.00 | 0.28 | 26-APR-13:00 | 0.00 | 01-APR-00:10 | 1346.25 | 26-APR-13:00 | 1244.93 | 26-APR-13:40 | 145.75 | 25-APR-13:20 | 351.32 | 26-APR-13:00 | 0.00 | 01-APR-00:10 |
| May | 0.255867E+09 | 65159367.92 | 196.16 | 0.233722E+09 | 22145338.70 | 0.00 | 0.26 | 03-MAY-13:00 | 0.00 | 01-MAY-00:10 | 1254.11 | 04-MAY-12:00 | 1212.80 | 03-MAY-13:00 | 139.97 | 04-MAY-15:20 | 313.64 | 04-MAY-12:00 | 0.00 | 01-MAY-00:10 |
| June | 0.874308E+09 | 0.217660E+09 | 384.79 | 0.736812E+09 | 0.137495E+09 | 0.00 | 0.33 | 29-JUN-17:05 | 0.00 | 01-JUN-00:10 | 1661.15 | 29-JUN-17:10 | 1320.77 | 29-JUN-17:05 | 369.64 | 28-JUN-11:00 | 401.61 | 29-JUN-17:10 | 0.00 | 01-JUN-00:10 |
| July | 0.170662E+10 | 0.419875E+09 | 563.59 | 0.135290E+10 | 0.353729E+09 | 0.00 | 0.41 | 31-JUL-13:00 | 0.00 | 01-JUL-02:00 | 2058.93 | 31-JUL-13:00 | 1678.85 | 19-JUL-15:10 | 453.97 | 29-JUL-14:00 | 525.76 | 31-JUL-13:00 | 0.00 | 01-JUL-00:10 |
| August | 0.161878E+10 | 0.397161E+09 | 524.72 | 0.125111E+10 | 0.367663E+09 | 0.00 | 0.41 | 17-AUG-14:10 | 0.00 | 01-AUG-03:00 | 2045.83 | 17-AUG-14:10 | 1633.46 | 17-AUG-14:10 | 430.20 | 18-AUG-11:00 | 521.04 | 17-AUG-14:00 | 0.00 | 01-AUG-00:10 |
| September | 0.774916E+09 | 0.197067E+09 | 362.00 | 0.645140E+09 | 0.129776E+09 | 0.00 | 0.51 | 29-SEP-13:00 | 0.00 | 01-SEP-00:10 | 2254.46 | 29-SEP-13:00 | 2254.46 | 29-SEP-13:00 | 493.90 | 22-SEP-12:00 | 663.83 | 29-SEP-13:00 | 0.00 | 01-SEP-00:10 |
| October | 0.763985E+09 | 0.197690E+09 | 329.56 | 0.655075E+09 | 0.108910E+09 | 0.00 | 0.52 | 16-OCT-12:00 | 0.00 | 02-OCT-05:30 | 2265.17 | 16-OCT-12:00 | 2265.17 | 16-OCT-12:00 | 449.58 | 01-OCT-12:00 | 667.75 | 16-OCT-12:00 | 0.00 | 01-OCT-00:10 |
| November | 17688528.07 | 4718865.50 | 18.50 | 17618126.82 | 70401.25 | 0.00 | 0.15 | 19-NOV-13:00 | 0.00 | 01-NOV-00:10 | 686.41 | 19-NOV-13:00 | 686.41 | 19-NOV-13:00 | 17.38 | 10-NOV-13:00 | 185.85 | 19-NOV-13:00 | 0.00 | 01-NOV-00:10 |
| December | 21544856.10 | 5725042.40 | 27.64 | 21544856.10 | 0.00 | 0.00 | 0.13 | 05-DEC-15:00 | 0.00 | 01-DEC-00:10 | 589.99 | 05-DEC-15:00 | 589.99 | 05-DEC-15:00 | 0.00 | 05-DEC-15:30 | 156.44 | 05-DEC-15:00 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.630058E+10 | 0.157328E+10 | 2614.05 | 0.515503E+10 | 0.114555E+10 | 0.00 | ||||||||||||||
| Minimum of Months | 2009840.04 | 537758.21 | 3.83 | 2009840.04 | -0.0 | 0.00 | 0.06 | 0.00 | 269.44 | 269.44 | 0.00 | 71.49 | 0.00 | |||||||
| Maximum of Months | 0.170662E+10 | 0.419875E+09 | 563.59 | 0.135290E+10 | 0.367663E+09 | 0.00 | 0.52 | 0.00 | 2265.17 | 2265.17 | 493.90 | 667.75 | 0.00 |
Report: DXReportMonthly
For: SPLIT TS1 COOLING COIL
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.526687E+09 | 0.135131E+09 | 232.82 | 0.516548E+09 | 10139565.85 | 0.00 | 0.45 | 14-JAN-14:40 | 0.00 | 01-JAN-00:10 | 2259.57 | 18-JAN-14:00 | 2259.57 | 18-JAN-14:00 | 138.54 | 20-JAN-13:30 | 564.80 | 18-JAN-13:50 | 0.00 | 01-JAN-00:10 |
| February | 0.280806E+09 | 72323405.52 | 137.92 | 0.275151E+09 | 5655603.02 | 0.00 | 0.35 | 01-FEB-13:00 | 0.00 | 01-FEB-00:10 | 1765.38 | 01-FEB-13:00 | 1765.38 | 01-FEB-13:00 | 115.43 | 01-FEB-16:10 | 444.96 | 01-FEB-12:50 | 0.00 | 01-FEB-00:10 |
| March | 0.299324E+09 | 75657064.08 | 131.25 | 0.275439E+09 | 23884223.94 | 0.00 | 0.37 | 11-MAR-14:00 | 0.00 | 01-MAR-00:10 | 1865.80 | 11-MAR-13:50 | 1865.80 | 11-MAR-13:50 | 232.87 | 23-MAR-15:20 | 467.35 | 11-MAR-14:00 | 0.00 | 01-MAR-00:10 |
| April | 0.653891E+09 | 0.164844E+09 | 256.42 | 0.597955E+09 | 55935798.06 | 0.00 | 0.40 | 26-APR-13:00 | 0.00 | 01-APR-00:10 | 2040.44 | 26-APR-13:00 | 1927.95 | 26-APR-13:20 | 240.05 | 08-APR-12:20 | 524.48 | 26-APR-13:00 | 0.00 | 01-APR-00:10 |
| May | 0.362156E+09 | 92061266.38 | 218.37 | 0.333759E+09 | 28397267.38 | 0.00 | 0.31 | 03-MAY-13:00 | 0.00 | 01-MAY-00:10 | 1590.74 | 03-MAY-13:00 | 1570.91 | 03-MAY-13:00 | 156.57 | 04-MAY-14:00 | 398.21 | 03-MAY-13:00 | 0.00 | 01-MAY-00:10 |
| June | 0.896913E+09 | 0.223265E+09 | 366.46 | 0.760543E+09 | 0.136371E+09 | 0.00 | 0.34 | 27-JUN-13:00 | 0.00 | 01-JUN-00:10 | 1769.94 | 27-JUN-13:00 | 1472.44 | 27-JUN-13:00 | 384.86 | 28-JUN-11:00 | 431.30 | 27-JUN-13:00 | 0.00 | 01-JUN-00:10 |
| July | 0.184566E+10 | 0.453576E+09 | 560.29 | 0.147683E+10 | 0.368830E+09 | 0.00 | 0.46 | 31-JUL-13:00 | 0.00 | 01-JUL-01:30 | 2423.21 | 31-JUL-13:00 | 1979.72 | 31-JUL-13:00 | 523.25 | 29-JUL-12:00 | 616.43 | 31-JUL-13:00 | 0.00 | 01-JUL-00:10 |
| August | 0.212283E+10 | 0.518304E+09 | 561.93 | 0.168458E+10 | 0.438245E+09 | 0.00 | 0.49 | 17-AUG-14:00 | 0.00 | 01-AUG-03:30 | 2597.15 | 19-AUG-13:00 | 2168.79 | 19-AUG-13:40 | 490.35 | 19-AUG-11:00 | 655.97 | 17-AUG-14:00 | 0.00 | 01-AUG-00:10 |
| September | 0.158094E+10 | 0.394943E+09 | 455.26 | 0.134753E+10 | 0.233409E+09 | 0.00 | 0.71 | 29-SEP-13:00 | 0.00 | 01-SEP-00:10 | 3446.38 | 29-SEP-13:00 | 3446.38 | 29-SEP-13:00 | 497.51 | 22-SEP-11:50 | 982.11 | 29-SEP-13:00 | 0.00 | 01-SEP-00:10 |
| October | 0.173539E+10 | 0.441114E+09 | 466.58 | 0.156984E+10 | 0.165542E+09 | 0.00 | 0.76 | 16-OCT-12:00 | 0.00 | 03-OCT-05:05 | 3665.72 | 16-OCT-12:00 | 3665.72 | 16-OCT-12:00 | 615.83 | 01-OCT-11:40 | 1038.65 | 16-OCT-12:00 | 0.00 | 01-OCT-00:10 |
| November | 0.539950E+09 | 0.138027E+09 | 223.77 | 0.524456E+09 | 15494720.77 | 0.00 | 0.53 | 19-NOV-13:00 | 0.00 | 01-NOV-00:10 | 2693.01 | 19-NOV-13:00 | 2693.01 | 19-NOV-13:00 | 228.65 | 10-NOV-13:00 | 686.80 | 19-NOV-13:00 | 0.00 | 01-NOV-00:10 |
| December | 0.629466E+09 | 0.161698E+09 | 222.62 | 0.625246E+09 | 4219819.98 | 0.00 | 0.49 | 19-DEC-13:00 | 0.00 | 01-DEC-00:10 | 2384.74 | 19-DEC-13:00 | 2384.74 | 19-DEC-13:00 | 147.73 | 07-DEC-14:00 | 612.70 | 19-DEC-13:00 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.114740E+11 | 0.287094E+10 | 3833.68 | 0.998788E+10 | 0.148612E+10 | 0.00 | ||||||||||||||
| Minimum of Months | 0.280806E+09 | 72323405.52 | 131.25 | 0.275151E+09 | 4219819.98 | 0.00 | 0.31 | 0.00 | 1590.74 | 1472.44 | 115.43 | 398.21 | 0.00 | |||||||
| Maximum of Months | 0.212283E+10 | 0.518304E+09 | 561.93 | 0.168458E+10 | 0.438245E+09 | 0.00 | 0.76 | 0.00 | 3665.72 | 3665.72 | 615.83 | 1038.65 | 0.00 |
Report: DXReportMonthly
For: SPLIT TS2 COOLING COIL
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.532414E+09 | 0.136566E+09 | 233.19 | 0.522177E+09 | 10237130.17 | 0.00 | 0.45 | 14-JAN-14:30 | 0.00 | 01-JAN-00:10 | 2263.22 | 18-JAN-14:00 | 2263.22 | 18-JAN-14:00 | 139.48 | 20-JAN-13:30 | 565.79 | 18-JAN-13:50 | 0.00 | 01-JAN-00:10 |
| February | 0.283454E+09 | 72989798.84 | 138.83 | 0.277780E+09 | 5673933.68 | 0.00 | 0.36 | 01-FEB-13:00 | 0.00 | 01-FEB-00:10 | 1773.18 | 01-FEB-13:00 | 1773.18 | 01-FEB-13:00 | 114.30 | 01-FEB-16:10 | 446.92 | 01-FEB-12:50 | 0.00 | 01-FEB-00:10 |
| March | 0.303558E+09 | 76703881.41 | 132.69 | 0.279482E+09 | 24076433.93 | 0.00 | 0.38 | 11-MAR-13:50 | 0.00 | 01-MAR-00:10 | 1878.44 | 11-MAR-13:50 | 1878.44 | 11-MAR-13:50 | 232.20 | 23-MAR-15:20 | 470.18 | 11-MAR-13:50 | 0.00 | 01-MAR-00:10 |
| April | 0.657498E+09 | 0.165702E+09 | 255.25 | 0.601537E+09 | 55961831.44 | 0.00 | 0.40 | 26-APR-13:00 | 0.00 | 01-APR-00:10 | 2057.85 | 26-APR-13:00 | 1942.91 | 26-APR-13:20 | 241.45 | 08-APR-12:20 | 528.59 | 26-APR-13:00 | 0.00 | 01-APR-00:10 |
| May | 0.364224E+09 | 92564162.82 | 217.66 | 0.335811E+09 | 28413552.32 | 0.00 | 0.32 | 03-MAY-13:00 | 0.00 | 01-MAY-00:10 | 1601.92 | 03-MAY-13:00 | 1582.27 | 03-MAY-13:00 | 157.02 | 04-MAY-14:00 | 400.81 | 03-MAY-13:00 | 0.00 | 01-MAY-00:10 |
| June | 0.895685E+09 | 0.222903E+09 | 361.38 | 0.759858E+09 | 0.135827E+09 | 0.00 | 0.34 | 27-JUN-13:00 | 0.00 | 01-JUN-00:10 | 1780.08 | 27-JUN-13:00 | 1482.19 | 27-JUN-13:00 | 386.96 | 28-JUN-11:00 | 433.61 | 27-JUN-13:00 | 0.00 | 01-JUN-00:10 |
| July | 0.184410E+10 | 0.453080E+09 | 556.16 | 0.147603E+10 | 0.368061E+09 | 0.00 | 0.46 | 31-JUL-13:00 | 0.00 | 01-JUL-01:10 | 2432.99 | 31-JUL-13:00 | 1989.44 | 31-JUL-13:00 | 525.11 | 29-JUL-12:00 | 618.62 | 31-JUL-13:00 | 0.00 | 01-JUL-00:10 |
| August | 0.212349E+10 | 0.518308E+09 | 559.64 | 0.168575E+10 | 0.437746E+09 | 0.00 | 0.49 | 19-AUG-13:20 | 0.00 | 01-AUG-03:20 | 2611.16 | 19-AUG-13:00 | 2178.09 | 19-AUG-13:40 | 492.42 | 19-AUG-10:30 | 657.06 | 17-AUG-14:00 | 0.00 | 01-AUG-00:10 |
| September | 0.157790E+10 | 0.394085E+09 | 453.76 | 0.134517E+10 | 0.232727E+09 | 0.00 | 0.72 | 29-SEP-13:00 | 0.00 | 01-SEP-00:10 | 3457.06 | 29-SEP-13:00 | 3457.06 | 29-SEP-13:00 | 497.82 | 22-SEP-11:50 | 984.36 | 29-SEP-13:00 | 0.00 | 01-SEP-00:10 |
| October | 0.173656E+10 | 0.441316E+09 | 466.33 | 0.157137E+10 | 0.165194E+09 | 0.00 | 0.77 | 16-OCT-12:00 | 0.00 | 03-OCT-05:05 | 3679.86 | 16-OCT-12:00 | 3679.86 | 16-OCT-12:00 | 616.08 | 01-OCT-11:40 | 1041.68 | 16-OCT-12:00 | 0.00 | 01-OCT-00:10 |
| November | 0.542132E+09 | 0.138548E+09 | 222.54 | 0.526760E+09 | 15372132.76 | 0.00 | 0.53 | 19-NOV-13:00 | 0.00 | 01-NOV-00:10 | 2703.71 | 19-NOV-13:00 | 2703.71 | 19-NOV-13:00 | 228.60 | 10-NOV-13:00 | 689.08 | 19-NOV-13:00 | 0.00 | 01-NOV-00:10 |
| December | 0.634079E+09 | 0.162834E+09 | 223.13 | 0.629878E+09 | 4201122.33 | 0.00 | 0.49 | 19-DEC-13:00 | 0.00 | 01-DEC-00:10 | 2393.22 | 19-DEC-13:00 | 2393.22 | 19-DEC-13:00 | 147.97 | 07-DEC-14:00 | 614.52 | 19-DEC-13:00 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.114951E+11 | 0.287560E+10 | 3820.56 | 0.100116E+11 | 0.148349E+10 | 0.00 | ||||||||||||||
| Minimum of Months | 0.283454E+09 | 72989798.84 | 132.69 | 0.277780E+09 | 4201122.33 | 0.00 | 0.32 | 0.00 | 1601.92 | 1482.19 | 114.30 | 400.81 | 0.00 | |||||||
| Maximum of Months | 0.212349E+10 | 0.518308E+09 | 559.64 | 0.168575E+10 | 0.437746E+09 | 0.00 | 0.77 | 0.00 | 3679.86 | 3679.86 | 616.08 | 1041.68 | 0.00 |
Report: WindowReportMonthly
For: GWINDOW1 S SWA
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 208.37 | 152.54 | 55.84 | 309.05 | 130.05 | 0.00 | 0.00 | 0.00 |
| February | 168.40 | 105.17 | 63.23 | 237.15 | 115.62 | 0.00 | 0.00 | 0.00 |
| March | 130.02 | 62.16 | 67.86 | 182.57 | 117.07 | 0.00 | 0.00 | 0.00 |
| April | 114.46 | 46.59 | 67.87 | 170.86 | 99.92 | 0.00 | 0.00 | 0.00 |
| May | 77.58 | 9.07 | 68.51 | 92.46 | 91.12 | 0.00 | 0.00 | 0.00 |
| June | 68.60 | 4.22 | 64.38 | 82.01 | 71.07 | 0.00 | 0.00 | 0.00 |
| July | 72.70 | 8.29 | 64.41 | 101.19 | 63.52 | 0.00 | 0.00 | 0.00 |
| August | 92.81 | 28.98 | 63.84 | 149.19 | 66.54 | 0.00 | 0.00 | 0.00 |
| September | 127.74 | 63.73 | 64.01 | 205.71 | 78.69 | 0.00 | 0.00 | 0.00 |
| October | 167.71 | 113.02 | 54.69 | 271.88 | 85.49 | 0.00 | 0.00 | 0.00 |
| November | 202.16 | 143.19 | 58.96 | 297.60 | 122.01 | 0.00 | 0.00 | 0.00 |
| December | 223.90 | 170.43 | 53.47 | 333.37 | 131.91 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 137.72 | 75.49 | 62.23 | 202.62 | 97.66 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 68.60 | 4.22 | 53.47 | 82.01 | 63.52 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 223.90 | 170.43 | 68.51 | 333.37 | 131.91 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: GWINDOW1 W SWA
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 53.65 | 27.06 | 26.59 | 65.17 | 92.11 | 0.00 | 0.00 | 0.00 |
| February | 63.94 | 29.50 | 34.44 | 76.17 | 79.38 | 0.00 | 0.00 | 0.00 |
| March | 73.27 | 32.40 | 40.87 | 91.66 | 77.18 | 0.00 | 0.00 | 0.00 |
| April | 100.87 | 52.42 | 48.45 | 141.53 | 63.63 | 0.00 | 0.00 | 0.00 |
| May | 99.11 | 45.67 | 53.45 | 135.75 | 56.84 | 0.00 | 0.00 | 0.00 |
| June | 105.23 | 52.63 | 52.60 | 152.25 | 44.25 | 0.00 | 0.00 | 0.00 |
| July | 111.41 | 59.63 | 51.78 | 169.87 | 39.64 | 0.00 | 0.00 | 0.00 |
| August | 104.36 | 56.50 | 47.86 | 160.32 | 42.29 | 0.00 | 0.00 | 0.00 |
| September | 89.36 | 47.76 | 41.59 | 131.40 | 50.64 | 0.00 | 0.00 | 0.00 |
| October | 68.39 | 37.36 | 31.03 | 102.34 | 58.28 | 0.00 | 0.00 | 0.00 |
| November | 61.67 | 32.20 | 29.46 | 76.94 | 85.30 | 0.00 | 0.00 | 0.00 |
| December | 54.37 | 29.08 | 25.29 | 67.04 | 94.19 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 82.21 | 41.90 | 40.30 | 114.39 | 65.24 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 53.65 | 27.06 | 25.29 | 65.17 | 39.64 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 111.41 | 59.63 | 53.45 | 169.87 | 94.19 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: GWINDOW1 W NWA
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 53.65 | 27.06 | 26.59 | 70.70 | 82.44 | 0.00 | 0.00 | 0.00 |
| February | 63.94 | 29.50 | 34.44 | 81.72 | 70.81 | 0.00 | 0.00 | 0.00 |
| March | 73.27 | 32.40 | 40.87 | 95.77 | 72.32 | 0.00 | 0.00 | 0.00 |
| April | 100.87 | 52.42 | 48.45 | 145.02 | 59.72 | 0.00 | 0.00 | 0.00 |
| May | 99.11 | 45.67 | 53.45 | 136.47 | 56.32 | 0.00 | 0.00 | 0.00 |
| June | 105.23 | 52.63 | 52.60 | 152.25 | 44.42 | 0.00 | 0.00 | 0.00 |
| July | 111.41 | 59.63 | 51.78 | 170.11 | 39.61 | 0.00 | 0.00 | 0.00 |
| August | 104.36 | 56.50 | 47.86 | 161.28 | 41.71 | 0.00 | 0.00 | 0.00 |
| September | 89.36 | 47.76 | 41.59 | 133.14 | 49.13 | 0.00 | 0.00 | 0.00 |
| October | 68.39 | 37.36 | 31.03 | 104.63 | 55.64 | 0.00 | 0.00 | 0.00 |
| November | 61.67 | 32.20 | 29.46 | 82.15 | 76.17 | 0.00 | 0.00 | 0.00 |
| December | 54.37 | 29.08 | 25.29 | 72.81 | 82.86 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 82.21 | 41.90 | 40.30 | 117.34 | 60.89 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 53.65 | 27.06 | 25.29 | 70.70 | 39.61 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 111.41 | 59.63 | 53.45 | 170.11 | 82.86 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: GWINDOW1 N NWA
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 31.75 | 0.00 | 31.75 | 21.00 | 129.07 | 0.00 | 0.00 | 0.00 |
| February | 39.85 | 0.00 | 39.85 | 27.37 | 111.04 | 0.00 | 0.00 | 0.00 |
| March | 48.84 | 0.00 | 48.84 | 40.10 | 113.06 | 0.00 | 0.00 | 0.00 |
| April | 56.41 | 0.34 | 56.08 | 52.05 | 91.69 | 0.00 | 0.00 | 0.00 |
| May | 68.03 | 3.54 | 64.49 | 64.14 | 82.61 | 0.00 | 0.00 | 0.00 |
| June | 71.93 | 6.94 | 64.99 | 79.29 | 65.16 | 0.00 | 0.00 | 0.00 |
| July | 68.12 | 5.62 | 62.51 | 82.26 | 58.90 | 0.00 | 0.00 | 0.00 |
| August | 56.86 | 1.33 | 55.53 | 66.09 | 62.69 | 0.00 | 0.00 | 0.00 |
| September | 47.96 | 0.02 | 47.94 | 50.39 | 77.32 | 0.00 | 0.00 | 0.00 |
| October | 38.03 | 0.00 | 38.03 | 44.05 | 86.93 | 0.00 | 0.00 | 0.00 |
| November | 34.43 | 0.00 | 34.43 | 23.11 | 120.13 | 0.00 | 0.00 | 0.00 |
| December | 29.55 | 0.00 | 29.55 | 18.58 | 130.38 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 49.35 | 1.49 | 47.86 | 47.49 | 94.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 29.55 | 0.00 | 29.55 | 18.58 | 58.90 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 71.93 | 6.94 | 64.99 | 82.26 | 130.38 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: GWINDOW1 S SEA
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 208.37 | 152.54 | 55.84 | 307.23 | 134.47 | 0.00 | 0.00 | 0.00 |
| February | 168.40 | 105.17 | 63.23 | 234.65 | 121.07 | 0.00 | 0.00 | 0.00 |
| March | 130.02 | 62.16 | 67.86 | 179.18 | 122.45 | 0.00 | 0.00 | 0.00 |
| April | 114.46 | 46.59 | 67.87 | 168.00 | 105.14 | 0.00 | 0.00 | 0.00 |
| May | 77.58 | 9.07 | 68.51 | 89.37 | 96.68 | 0.00 | 0.00 | 0.00 |
| June | 68.60 | 4.22 | 64.38 | 78.56 | 77.54 | 0.00 | 0.00 | 0.00 |
| July | 72.70 | 8.29 | 64.41 | 95.07 | 73.67 | 0.00 | 0.00 | 0.00 |
| August | 92.81 | 28.98 | 63.84 | 143.52 | 78.39 | 0.00 | 0.00 | 0.00 |
| September | 127.74 | 63.73 | 64.01 | 201.08 | 89.38 | 0.00 | 0.00 | 0.00 |
| October | 167.71 | 113.02 | 54.69 | 265.71 | 99.07 | 0.00 | 0.00 | 0.00 |
| November | 202.16 | 143.19 | 58.96 | 295.04 | 127.95 | 0.00 | 0.00 | 0.00 |
| December | 223.90 | 170.43 | 53.47 | 330.95 | 137.18 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 137.72 | 75.49 | 62.23 | 198.88 | 105.18 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 68.60 | 4.22 | 53.47 | 78.56 | 73.67 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 223.90 | 170.43 | 68.51 | 330.95 | 137.18 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: GWINDOW1 E SEA
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 56.59 | 30.37 | 26.22 | 65.35 | 90.89 | 0.00 | 0.00 | 0.00 |
| February | 59.06 | 26.86 | 32.21 | 64.92 | 80.85 | 0.00 | 0.00 | 0.00 |
| March | 72.41 | 32.30 | 40.11 | 86.20 | 77.85 | 0.00 | 0.00 | 0.00 |
| April | 92.67 | 46.65 | 46.02 | 125.86 | 65.17 | 0.00 | 0.00 | 0.00 |
| May | 87.05 | 36.28 | 50.77 | 113.58 | 59.03 | 0.00 | 0.00 | 0.00 |
| June | 86.61 | 37.60 | 49.00 | 120.46 | 48.38 | 0.00 | 0.00 | 0.00 |
| July | 98.14 | 48.81 | 49.33 | 145.26 | 46.48 | 0.00 | 0.00 | 0.00 |
| August | 96.85 | 51.43 | 45.42 | 144.47 | 48.77 | 0.00 | 0.00 | 0.00 |
| September | 70.69 | 32.48 | 38.21 | 97.95 | 57.39 | 0.00 | 0.00 | 0.00 |
| October | 62.15 | 31.80 | 30.35 | 86.60 | 65.72 | 0.00 | 0.00 | 0.00 |
| November | 56.68 | 28.68 | 28.00 | 64.17 | 86.75 | 0.00 | 0.00 | 0.00 |
| December | 54.43 | 30.29 | 24.14 | 61.65 | 93.69 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 74.55 | 36.20 | 38.34 | 98.27 | 68.35 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 54.43 | 26.86 | 24.14 | 61.65 | 46.48 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 98.14 | 51.43 | 50.77 | 145.26 | 93.69 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: GWINDOW1 E NEA
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 56.59 | 30.37 | 26.22 | 71.40 | 78.21 | 0.00 | 0.00 | 0.00 |
| February | 59.06 | 26.86 | 32.21 | 71.54 | 68.05 | 0.00 | 0.00 | 0.00 |
| March | 72.41 | 32.30 | 40.11 | 91.79 | 69.07 | 0.00 | 0.00 | 0.00 |
| April | 92.67 | 46.65 | 46.02 | 130.89 | 57.31 | 0.00 | 0.00 | 0.00 |
| May | 87.05 | 36.28 | 50.77 | 116.50 | 54.37 | 0.00 | 0.00 | 0.00 |
| June | 86.61 | 37.60 | 49.00 | 123.08 | 43.85 | 0.00 | 0.00 | 0.00 |
| July | 98.14 | 48.81 | 49.33 | 149.90 | 39.80 | 0.00 | 0.00 | 0.00 |
| August | 96.85 | 51.43 | 45.42 | 149.49 | 40.65 | 0.00 | 0.00 | 0.00 |
| September | 70.69 | 32.48 | 38.21 | 102.77 | 48.22 | 0.00 | 0.00 | 0.00 |
| October | 62.15 | 31.80 | 30.35 | 92.35 | 53.55 | 0.00 | 0.00 | 0.00 |
| November | 56.68 | 28.68 | 28.00 | 70.69 | 73.02 | 0.00 | 0.00 | 0.00 |
| December | 54.43 | 30.29 | 24.14 | 68.55 | 78.58 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 74.55 | 36.20 | 38.34 | 103.47 | 58.68 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 54.43 | 26.86 | 24.14 | 68.55 | 39.80 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 98.14 | 51.43 | 50.77 | 149.90 | 78.58 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: GWINDOW1 N NEA
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 31.75 | 0.00 | 31.75 | 20.30 | 129.12 | 0.00 | 0.00 | 0.00 |
| February | 39.85 | 0.00 | 39.85 | 26.90 | 110.30 | 0.00 | 0.00 | 0.00 |
| March | 48.84 | 0.00 | 48.84 | 39.38 | 112.63 | 0.00 | 0.00 | 0.00 |
| April | 56.41 | 0.34 | 56.08 | 51.40 | 90.56 | 0.00 | 0.00 | 0.00 |
| May | 68.03 | 3.54 | 64.49 | 63.99 | 81.41 | 0.00 | 0.00 | 0.00 |
| June | 71.93 | 6.94 | 64.99 | 79.38 | 64.09 | 0.00 | 0.00 | 0.00 |
| July | 68.12 | 5.62 | 62.51 | 82.03 | 58.28 | 0.00 | 0.00 | 0.00 |
| August | 56.86 | 1.33 | 55.53 | 65.67 | 62.13 | 0.00 | 0.00 | 0.00 |
| September | 47.96 | 0.02 | 47.94 | 50.34 | 76.15 | 0.00 | 0.00 | 0.00 |
| October | 38.03 | 0.00 | 38.03 | 43.69 | 86.41 | 0.00 | 0.00 | 0.00 |
| November | 34.43 | 0.00 | 34.43 | 22.67 | 119.17 | 0.00 | 0.00 | 0.00 |
| December | 29.55 | 0.00 | 29.55 | 17.98 | 130.05 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 49.35 | 1.49 | 47.86 | 47.10 | 93.28 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 29.55 | 0.00 | 29.55 | 17.98 | 58.28 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 71.93 | 6.94 | 64.99 | 82.03 | 130.05 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: GWINDOW1 N N1A
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 31.75 | 0.00 | 31.75 | 19.92 | 133.00 | 0.00 | 0.00 | 0.00 |
| February | 39.85 | 0.00 | 39.85 | 25.94 | 115.34 | 0.00 | 0.00 | 0.00 |
| March | 48.84 | 0.00 | 48.84 | 38.84 | 116.41 | 0.00 | 0.00 | 0.00 |
| April | 56.41 | 0.34 | 56.08 | 51.34 | 93.91 | 0.00 | 0.00 | 0.00 |
| May | 68.03 | 3.54 | 64.49 | 62.91 | 85.00 | 0.00 | 0.00 | 0.00 |
| June | 71.93 | 6.94 | 64.99 | 78.73 | 66.52 | 0.00 | 0.00 | 0.00 |
| July | 68.12 | 5.62 | 62.51 | 82.92 | 58.91 | 0.00 | 0.00 | 0.00 |
| August | 56.86 | 1.33 | 55.53 | 66.61 | 62.80 | 0.00 | 0.00 | 0.00 |
| September | 47.96 | 0.02 | 47.94 | 50.44 | 77.97 | 0.00 | 0.00 | 0.00 |
| October | 38.03 | 0.00 | 38.03 | 43.76 | 88.50 | 0.00 | 0.00 | 0.00 |
| November | 34.43 | 0.00 | 34.43 | 21.78 | 124.79 | 0.00 | 0.00 | 0.00 |
| December | 29.55 | 0.00 | 29.55 | 17.38 | 135.15 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 49.35 | 1.49 | 47.86 | 46.84 | 96.43 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 29.55 | 0.00 | 29.55 | 17.38 | 58.91 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 71.93 | 6.94 | 64.99 | 82.92 | 135.15 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: GWINDOW1 N N2A
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 31.75 | 0.00 | 31.75 | 19.87 | 133.06 | 0.00 | 0.00 | 0.00 |
| February | 39.85 | 0.00 | 39.85 | 25.92 | 115.29 | 0.00 | 0.00 | 0.00 |
| March | 48.84 | 0.00 | 48.84 | 38.79 | 116.42 | 0.00 | 0.00 | 0.00 |
| April | 56.41 | 0.34 | 56.08 | 51.33 | 93.83 | 0.00 | 0.00 | 0.00 |
| May | 68.03 | 3.54 | 64.49 | 62.95 | 84.89 | 0.00 | 0.00 | 0.00 |
| June | 71.93 | 6.94 | 64.99 | 78.78 | 66.44 | 0.00 | 0.00 | 0.00 |
| July | 68.12 | 5.62 | 62.51 | 82.92 | 58.88 | 0.00 | 0.00 | 0.00 |
| August | 56.86 | 1.33 | 55.53 | 66.59 | 62.78 | 0.00 | 0.00 | 0.00 |
| September | 47.96 | 0.02 | 47.94 | 50.45 | 77.90 | 0.00 | 0.00 | 0.00 |
| October | 38.03 | 0.00 | 38.03 | 43.75 | 88.48 | 0.00 | 0.00 | 0.00 |
| November | 34.43 | 0.00 | 34.43 | 21.77 | 124.70 | 0.00 | 0.00 | 0.00 |
| December | 29.55 | 0.00 | 29.55 | 17.35 | 135.15 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 49.35 | 1.49 | 47.86 | 46.83 | 96.39 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 29.55 | 0.00 | 29.55 | 17.35 | 58.88 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 71.93 | 6.94 | 64.99 | 82.92 | 135.15 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: GWINDOW1 S S1A
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 208.37 | 152.54 | 55.84 | 306.58 | 135.19 | 0.00 | 0.00 | 0.00 |
| February | 168.40 | 105.17 | 63.23 | 233.88 | 122.56 | 0.00 | 0.00 | 0.00 |
| March | 130.02 | 62.16 | 67.86 | 179.88 | 122.75 | 0.00 | 0.00 | 0.00 |
| April | 114.46 | 46.59 | 67.87 | 169.53 | 103.03 | 0.00 | 0.00 | 0.00 |
| May | 77.58 | 9.07 | 68.51 | 91.20 | 93.90 | 0.00 | 0.00 | 0.00 |
| June | 68.60 | 4.22 | 64.38 | 81.42 | 72.53 | 0.00 | 0.00 | 0.00 |
| July | 72.70 | 8.29 | 64.41 | 101.66 | 63.45 | 0.00 | 0.00 | 0.00 |
| August | 92.81 | 28.98 | 63.84 | 149.58 | 66.61 | 0.00 | 0.00 | 0.00 |
| September | 127.74 | 63.73 | 64.01 | 205.75 | 79.23 | 0.00 | 0.00 | 0.00 |
| October | 167.71 | 113.02 | 54.69 | 271.55 | 86.67 | 0.00 | 0.00 | 0.00 |
| November | 202.16 | 143.19 | 58.96 | 296.00 | 125.45 | 0.00 | 0.00 | 0.00 |
| December | 223.90 | 170.43 | 53.47 | 330.94 | 136.96 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 137.72 | 75.49 | 62.23 | 201.38 | 100.58 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 68.60 | 4.22 | 53.47 | 81.42 | 63.45 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 223.90 | 170.43 | 68.51 | 330.94 | 136.96 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: GWINDOW1 S S2A
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 208.37 | 152.54 | 55.84 | 306.45 | 135.37 | 0.00 | 0.00 | 0.00 |
| February | 168.40 | 105.17 | 63.23 | 233.52 | 123.12 | 0.00 | 0.00 | 0.00 |
| March | 130.02 | 62.16 | 67.86 | 179.38 | 123.50 | 0.00 | 0.00 | 0.00 |
| April | 114.46 | 46.59 | 67.87 | 169.18 | 103.51 | 0.00 | 0.00 | 0.00 |
| May | 77.58 | 9.07 | 68.51 | 90.74 | 94.47 | 0.00 | 0.00 | 0.00 |
| June | 68.60 | 4.22 | 64.38 | 81.03 | 72.96 | 0.00 | 0.00 | 0.00 |
| July | 72.70 | 8.29 | 64.41 | 101.29 | 63.83 | 0.00 | 0.00 | 0.00 |
| August | 92.81 | 28.98 | 63.84 | 149.20 | 67.05 | 0.00 | 0.00 | 0.00 |
| September | 127.74 | 63.73 | 64.01 | 205.47 | 79.62 | 0.00 | 0.00 | 0.00 |
| October | 167.71 | 113.02 | 54.69 | 271.18 | 87.20 | 0.00 | 0.00 | 0.00 |
| November | 202.16 | 143.19 | 58.96 | 295.80 | 125.75 | 0.00 | 0.00 | 0.00 |
| December | 223.90 | 170.43 | 53.47 | 330.72 | 137.30 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 137.72 | 75.49 | 62.23 | 201.04 | 101.02 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 68.60 | 4.22 | 53.47 | 81.03 | 63.83 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 223.90 | 170.43 | 68.51 | 330.72 | 137.30 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MWINDOW1 S SWA
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 208.37 | 152.54 | 55.84 | 304.50 | 136.16 | 0.00 | 0.00 | 0.00 |
| February | 168.40 | 105.17 | 63.23 | 230.07 | 126.34 | 0.00 | 0.00 | 0.00 |
| March | 130.02 | 62.16 | 67.86 | 174.16 | 130.64 | 0.00 | 0.00 | 0.00 |
| April | 114.46 | 46.59 | 67.87 | 164.47 | 109.59 | 0.00 | 0.00 | 0.00 |
| May | 77.58 | 9.07 | 68.51 | 86.09 | 100.39 | 0.00 | 0.00 | 0.00 |
| June | 68.60 | 4.22 | 64.38 | 77.33 | 76.83 | 0.00 | 0.00 | 0.00 |
| July | 72.70 | 8.29 | 64.41 | 98.92 | 65.66 | 0.00 | 0.00 | 0.00 |
| August | 92.81 | 28.98 | 63.84 | 147.02 | 68.55 | 0.00 | 0.00 | 0.00 |
| September | 127.74 | 63.73 | 64.01 | 203.44 | 80.64 | 0.00 | 0.00 | 0.00 |
| October | 167.71 | 113.02 | 54.69 | 269.84 | 86.79 | 0.00 | 0.00 | 0.00 |
| November | 202.16 | 143.19 | 58.96 | 294.30 | 125.23 | 0.00 | 0.00 | 0.00 |
| December | 223.90 | 170.43 | 53.47 | 329.28 | 136.66 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 137.72 | 75.49 | 62.23 | 198.17 | 103.50 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 68.60 | 4.22 | 53.47 | 77.33 | 65.66 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 223.90 | 170.43 | 68.51 | 329.28 | 136.66 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MWINDOW1 W SWA
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 53.65 | 27.06 | 26.59 | 63.07 | 96.71 | 0.00 | 0.00 | 0.00 |
| February | 63.94 | 29.50 | 34.44 | 72.39 | 86.94 | 0.00 | 0.00 | 0.00 |
| March | 73.27 | 32.40 | 40.87 | 86.25 | 86.20 | 0.00 | 0.00 | 0.00 |
| April | 100.87 | 52.42 | 48.45 | 136.70 | 69.74 | 0.00 | 0.00 | 0.00 |
| May | 99.11 | 45.67 | 53.45 | 130.57 | 62.44 | 0.00 | 0.00 | 0.00 |
| June | 105.23 | 52.63 | 52.60 | 148.17 | 47.80 | 0.00 | 0.00 | 0.00 |
| July | 111.41 | 59.63 | 51.78 | 167.62 | 40.99 | 0.00 | 0.00 | 0.00 |
| August | 104.36 | 56.50 | 47.86 | 158.36 | 43.59 | 0.00 | 0.00 | 0.00 |
| September | 89.36 | 47.76 | 41.59 | 129.68 | 51.95 | 0.00 | 0.00 | 0.00 |
| October | 68.39 | 37.36 | 31.03 | 101.27 | 59.21 | 0.00 | 0.00 | 0.00 |
| November | 61.67 | 32.20 | 29.46 | 75.40 | 87.69 | 0.00 | 0.00 | 0.00 |
| December | 54.37 | 29.08 | 25.29 | 65.35 | 97.86 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 82.21 | 41.90 | 40.30 | 111.43 | 69.17 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 53.65 | 27.06 | 25.29 | 63.07 | 40.99 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 111.41 | 59.63 | 53.45 | 167.62 | 97.86 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MWINDOW1 W NWA
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 53.65 | 27.06 | 26.59 | 68.02 | 88.10 | 0.00 | 0.00 | 0.00 |
| February | 63.94 | 29.50 | 34.44 | 76.54 | 80.54 | 0.00 | 0.00 | 0.00 |
| March | 73.27 | 32.40 | 40.87 | 89.66 | 81.88 | 0.00 | 0.00 | 0.00 |
| April | 100.87 | 52.42 | 48.45 | 138.40 | 68.27 | 0.00 | 0.00 | 0.00 |
| May | 99.11 | 45.67 | 53.45 | 130.87 | 62.38 | 0.00 | 0.00 | 0.00 |
| June | 105.23 | 52.63 | 52.60 | 148.22 | 47.89 | 0.00 | 0.00 | 0.00 |
| July | 111.41 | 59.63 | 51.78 | 167.85 | 40.97 | 0.00 | 0.00 | 0.00 |
| August | 104.36 | 56.50 | 47.86 | 159.17 | 43.24 | 0.00 | 0.00 | 0.00 |
| September | 89.36 | 47.76 | 41.59 | 131.07 | 51.09 | 0.00 | 0.00 | 0.00 |
| October | 68.39 | 37.36 | 31.03 | 103.22 | 57.48 | 0.00 | 0.00 | 0.00 |
| November | 61.67 | 32.20 | 29.46 | 79.20 | 82.04 | 0.00 | 0.00 | 0.00 |
| December | 54.37 | 29.08 | 25.29 | 69.94 | 89.24 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 82.21 | 41.90 | 40.30 | 113.70 | 66.02 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 53.65 | 27.06 | 25.29 | 68.02 | 40.97 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 111.41 | 59.63 | 53.45 | 167.85 | 89.24 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MWINDOW1 N NWA
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 31.75 | 0.00 | 31.75 | 18.17 | 138.25 | 0.00 | 0.00 | 0.00 |
| February | 39.85 | 0.00 | 39.85 | 21.61 | 126.94 | 0.00 | 0.00 | 0.00 |
| March | 48.84 | 0.00 | 48.84 | 32.81 | 128.51 | 0.00 | 0.00 | 0.00 |
| April | 56.41 | 0.34 | 56.08 | 43.92 | 105.44 | 0.00 | 0.00 | 0.00 |
| May | 68.03 | 3.54 | 64.49 | 56.30 | 91.39 | 0.00 | 0.00 | 0.00 |
| June | 71.93 | 6.94 | 64.99 | 73.74 | 70.11 | 0.00 | 0.00 | 0.00 |
| July | 68.12 | 5.62 | 62.51 | 79.63 | 60.81 | 0.00 | 0.00 | 0.00 |
| August | 56.86 | 1.33 | 55.53 | 63.89 | 64.93 | 0.00 | 0.00 | 0.00 |
| September | 47.96 | 0.02 | 47.94 | 48.34 | 80.41 | 0.00 | 0.00 | 0.00 |
| October | 38.03 | 0.00 | 38.03 | 42.78 | 89.80 | 0.00 | 0.00 | 0.00 |
| November | 34.43 | 0.00 | 34.43 | 20.11 | 129.69 | 0.00 | 0.00 | 0.00 |
| December | 29.55 | 0.00 | 29.55 | 15.65 | 140.84 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 49.35 | 1.49 | 47.86 | 43.22 | 102.12 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 29.55 | 0.00 | 29.55 | 15.65 | 60.81 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 71.93 | 6.94 | 64.99 | 79.63 | 140.84 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MWINDOW1 S SEA
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 208.37 | 152.54 | 55.84 | 303.71 | 136.13 | 0.00 | 0.00 | 0.00 |
| February | 168.40 | 105.17 | 63.23 | 229.63 | 125.73 | 0.00 | 0.00 | 0.00 |
| March | 130.02 | 62.16 | 67.86 | 173.40 | 130.17 | 0.00 | 0.00 | 0.00 |
| April | 114.46 | 46.59 | 67.87 | 163.76 | 109.01 | 0.00 | 0.00 | 0.00 |
| May | 77.58 | 9.07 | 68.51 | 85.56 | 99.74 | 0.00 | 0.00 | 0.00 |
| June | 68.60 | 4.22 | 64.38 | 77.03 | 76.14 | 0.00 | 0.00 | 0.00 |
| July | 72.70 | 8.29 | 64.41 | 98.49 | 65.00 | 0.00 | 0.00 | 0.00 |
| August | 92.81 | 28.98 | 63.84 | 146.54 | 68.00 | 0.00 | 0.00 | 0.00 |
| September | 127.74 | 63.73 | 64.01 | 203.28 | 79.98 | 0.00 | 0.00 | 0.00 |
| October | 167.71 | 113.02 | 54.69 | 269.51 | 86.40 | 0.00 | 0.00 | 0.00 |
| November | 202.16 | 143.19 | 58.96 | 293.88 | 124.78 | 0.00 | 0.00 | 0.00 |
| December | 223.90 | 170.43 | 53.47 | 328.69 | 136.34 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 137.72 | 75.49 | 62.23 | 197.67 | 102.99 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 68.60 | 4.22 | 53.47 | 77.03 | 65.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 223.90 | 170.43 | 68.51 | 328.69 | 136.34 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MWINDOW1 E SEA
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 56.59 | 30.37 | 26.22 | 63.73 | 92.40 | 0.00 | 0.00 | 0.00 |
| February | 59.06 | 26.86 | 32.21 | 62.26 | 84.18 | 0.00 | 0.00 | 0.00 |
| March | 72.41 | 32.30 | 40.11 | 82.33 | 82.68 | 0.00 | 0.00 | 0.00 |
| April | 92.67 | 46.65 | 46.02 | 122.76 | 67.39 | 0.00 | 0.00 | 0.00 |
| May | 87.05 | 36.28 | 50.77 | 110.64 | 60.68 | 0.00 | 0.00 | 0.00 |
| June | 86.61 | 37.60 | 49.00 | 119.33 | 47.45 | 0.00 | 0.00 | 0.00 |
| July | 98.14 | 48.81 | 49.33 | 147.83 | 41.20 | 0.00 | 0.00 | 0.00 |
| August | 96.85 | 51.43 | 45.42 | 146.95 | 42.48 | 0.00 | 0.00 | 0.00 |
| September | 70.69 | 32.48 | 38.21 | 99.71 | 51.35 | 0.00 | 0.00 | 0.00 |
| October | 62.15 | 31.80 | 30.35 | 89.10 | 57.17 | 0.00 | 0.00 | 0.00 |
| November | 56.68 | 28.68 | 28.00 | 63.81 | 84.71 | 0.00 | 0.00 | 0.00 |
| December | 54.43 | 30.29 | 24.14 | 60.68 | 93.31 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 74.55 | 36.20 | 38.34 | 97.67 | 66.99 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 54.43 | 26.86 | 24.14 | 60.68 | 41.20 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 98.14 | 51.43 | 50.77 | 147.83 | 93.31 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MWINDOW1 E NEA
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 56.59 | 30.37 | 26.22 | 68.50 | 83.77 | 0.00 | 0.00 | 0.00 |
| February | 59.06 | 26.86 | 32.21 | 66.28 | 77.47 | 0.00 | 0.00 | 0.00 |
| March | 72.41 | 32.30 | 40.11 | 85.57 | 78.26 | 0.00 | 0.00 | 0.00 |
| April | 92.67 | 46.65 | 46.02 | 124.35 | 65.88 | 0.00 | 0.00 | 0.00 |
| May | 87.05 | 36.28 | 50.77 | 110.92 | 60.58 | 0.00 | 0.00 | 0.00 |
| June | 86.61 | 37.60 | 49.00 | 119.40 | 47.55 | 0.00 | 0.00 | 0.00 |
| July | 98.14 | 48.81 | 49.33 | 148.07 | 41.19 | 0.00 | 0.00 | 0.00 |
| August | 96.85 | 51.43 | 45.42 | 147.71 | 42.11 | 0.00 | 0.00 | 0.00 |
| September | 70.69 | 32.48 | 38.21 | 101.01 | 50.39 | 0.00 | 0.00 | 0.00 |
| October | 62.15 | 31.80 | 30.35 | 90.97 | 55.40 | 0.00 | 0.00 | 0.00 |
| November | 56.68 | 28.68 | 28.00 | 67.62 | 78.72 | 0.00 | 0.00 | 0.00 |
| December | 54.43 | 30.29 | 24.14 | 65.41 | 84.73 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 74.55 | 36.20 | 38.34 | 99.89 | 63.76 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 54.43 | 26.86 | 24.14 | 65.41 | 41.19 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 98.14 | 51.43 | 50.77 | 148.07 | 84.73 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MWINDOW1 N NEA
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 31.75 | 0.00 | 31.75 | 17.33 | 138.39 | 0.00 | 0.00 | 0.00 |
| February | 39.85 | 0.00 | 39.85 | 21.01 | 125.93 | 0.00 | 0.00 | 0.00 |
| March | 48.84 | 0.00 | 48.84 | 31.92 | 127.94 | 0.00 | 0.00 | 0.00 |
| April | 56.41 | 0.34 | 56.08 | 43.07 | 104.81 | 0.00 | 0.00 | 0.00 |
| May | 68.03 | 3.54 | 64.49 | 55.84 | 90.78 | 0.00 | 0.00 | 0.00 |
| June | 71.93 | 6.94 | 64.99 | 73.58 | 69.55 | 0.00 | 0.00 | 0.00 |
| July | 68.12 | 5.62 | 62.51 | 79.31 | 60.26 | 0.00 | 0.00 | 0.00 |
| August | 56.86 | 1.33 | 55.53 | 63.43 | 64.43 | 0.00 | 0.00 | 0.00 |
| September | 47.96 | 0.02 | 47.94 | 48.13 | 79.67 | 0.00 | 0.00 | 0.00 |
| October | 38.03 | 0.00 | 38.03 | 42.35 | 89.43 | 0.00 | 0.00 | 0.00 |
| November | 34.43 | 0.00 | 34.43 | 19.54 | 128.69 | 0.00 | 0.00 | 0.00 |
| December | 29.55 | 0.00 | 29.55 | 14.98 | 140.46 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 49.35 | 1.49 | 47.86 | 42.68 | 101.56 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 29.55 | 0.00 | 29.55 | 14.98 | 60.26 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 71.93 | 6.94 | 64.99 | 79.31 | 140.46 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MWINDOW1 N N1A
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 31.75 | 0.00 | 31.75 | 17.06 | 142.75 | 0.00 | 0.00 | 0.00 |
| February | 39.85 | 0.00 | 39.85 | 19.92 | 133.09 | 0.00 | 0.00 | 0.00 |
| March | 48.84 | 0.00 | 48.84 | 31.37 | 133.23 | 0.00 | 0.00 | 0.00 |
| April | 56.41 | 0.34 | 56.08 | 43.79 | 106.85 | 0.00 | 0.00 | 0.00 |
| May | 68.03 | 3.54 | 64.49 | 56.23 | 92.54 | 0.00 | 0.00 | 0.00 |
| June | 71.93 | 6.94 | 64.99 | 74.58 | 70.12 | 0.00 | 0.00 | 0.00 |
| July | 68.12 | 5.62 | 62.51 | 80.89 | 60.40 | 0.00 | 0.00 | 0.00 |
| August | 56.86 | 1.33 | 55.53 | 64.98 | 64.53 | 0.00 | 0.00 | 0.00 |
| September | 47.96 | 0.02 | 47.94 | 48.87 | 80.35 | 0.00 | 0.00 | 0.00 |
| October | 38.03 | 0.00 | 38.03 | 42.80 | 90.78 | 0.00 | 0.00 | 0.00 |
| November | 34.43 | 0.00 | 34.43 | 18.87 | 134.24 | 0.00 | 0.00 | 0.00 |
| December | 29.55 | 0.00 | 29.55 | 14.36 | 146.79 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 49.35 | 1.49 | 47.86 | 42.96 | 104.48 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 29.55 | 0.00 | 29.55 | 14.36 | 60.40 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 71.93 | 6.94 | 64.99 | 80.89 | 146.79 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MWINDOW1 N N2A
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 31.75 | 0.00 | 31.75 | 17.00 | 142.84 | 0.00 | 0.00 | 0.00 |
| February | 39.85 | 0.00 | 39.85 | 19.90 | 133.02 | 0.00 | 0.00 | 0.00 |
| March | 48.84 | 0.00 | 48.84 | 31.33 | 133.19 | 0.00 | 0.00 | 0.00 |
| April | 56.41 | 0.34 | 56.08 | 43.75 | 106.84 | 0.00 | 0.00 | 0.00 |
| May | 68.03 | 3.54 | 64.49 | 56.22 | 92.52 | 0.00 | 0.00 | 0.00 |
| June | 71.93 | 6.94 | 64.99 | 74.58 | 70.10 | 0.00 | 0.00 | 0.00 |
| July | 68.12 | 5.62 | 62.51 | 80.88 | 60.38 | 0.00 | 0.00 | 0.00 |
| August | 56.86 | 1.33 | 55.53 | 64.96 | 64.51 | 0.00 | 0.00 | 0.00 |
| September | 47.96 | 0.02 | 47.94 | 48.87 | 80.32 | 0.00 | 0.00 | 0.00 |
| October | 38.03 | 0.00 | 38.03 | 42.79 | 90.77 | 0.00 | 0.00 | 0.00 |
| November | 34.43 | 0.00 | 34.43 | 18.85 | 134.17 | 0.00 | 0.00 | 0.00 |
| December | 29.55 | 0.00 | 29.55 | 14.32 | 146.79 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 49.35 | 1.49 | 47.86 | 42.93 | 104.46 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 29.55 | 0.00 | 29.55 | 14.32 | 60.38 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 71.93 | 6.94 | 64.99 | 80.88 | 146.79 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MWINDOW1 S S1A
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 208.37 | 152.54 | 55.84 | 302.70 | 140.27 | 0.00 | 0.00 | 0.00 |
| February | 168.40 | 105.17 | 63.23 | 228.25 | 131.06 | 0.00 | 0.00 | 0.00 |
| March | 130.02 | 62.16 | 67.86 | 172.38 | 135.35 | 0.00 | 0.00 | 0.00 |
| April | 114.46 | 46.59 | 67.87 | 164.30 | 110.88 | 0.00 | 0.00 | 0.00 |
| May | 77.58 | 9.07 | 68.51 | 85.98 | 101.55 | 0.00 | 0.00 | 0.00 |
| June | 68.60 | 4.22 | 64.38 | 77.97 | 76.68 | 0.00 | 0.00 | 0.00 |
| July | 72.70 | 8.29 | 64.41 | 99.93 | 65.07 | 0.00 | 0.00 | 0.00 |
| August | 92.81 | 28.98 | 63.84 | 147.90 | 68.09 | 0.00 | 0.00 | 0.00 |
| September | 127.74 | 63.73 | 64.01 | 203.92 | 80.62 | 0.00 | 0.00 | 0.00 |
| October | 167.71 | 113.02 | 54.69 | 269.87 | 87.50 | 0.00 | 0.00 | 0.00 |
| November | 202.16 | 143.19 | 58.96 | 293.31 | 127.69 | 0.00 | 0.00 | 0.00 |
| December | 223.90 | 170.43 | 53.47 | 327.71 | 140.18 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 137.72 | 75.49 | 62.23 | 197.74 | 105.27 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 68.60 | 4.22 | 53.47 | 77.97 | 65.07 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 223.90 | 170.43 | 68.51 | 327.71 | 140.27 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MWINDOW1 S S2A
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 208.37 | 152.54 | 55.84 | 302.66 | 140.31 | 0.00 | 0.00 | 0.00 |
| February | 168.40 | 105.17 | 63.23 | 228.24 | 131.02 | 0.00 | 0.00 | 0.00 |
| March | 130.02 | 62.16 | 67.86 | 172.36 | 135.33 | 0.00 | 0.00 | 0.00 |
| April | 114.46 | 46.59 | 67.87 | 164.28 | 110.87 | 0.00 | 0.00 | 0.00 |
| May | 77.58 | 9.07 | 68.51 | 85.96 | 101.53 | 0.00 | 0.00 | 0.00 |
| June | 68.60 | 4.22 | 64.38 | 77.96 | 76.65 | 0.00 | 0.00 | 0.00 |
| July | 72.70 | 8.29 | 64.41 | 99.91 | 65.05 | 0.00 | 0.00 | 0.00 |
| August | 92.81 | 28.98 | 63.84 | 147.89 | 68.07 | 0.00 | 0.00 | 0.00 |
| September | 127.74 | 63.73 | 64.01 | 203.92 | 80.60 | 0.00 | 0.00 | 0.00 |
| October | 167.71 | 113.02 | 54.69 | 269.86 | 87.48 | 0.00 | 0.00 | 0.00 |
| November | 202.16 | 143.19 | 58.96 | 293.30 | 127.67 | 0.00 | 0.00 | 0.00 |
| December | 223.90 | 170.43 | 53.47 | 327.70 | 140.17 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 137.72 | 75.49 | 62.23 | 197.73 | 105.26 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 68.60 | 4.22 | 53.47 | 77.96 | 65.05 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 223.90 | 170.43 | 68.51 | 327.70 | 140.31 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: TWINDOW1 S SWA
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 208.37 | 152.54 | 55.84 | 307.79 | 121.36 | 0.00 | 0.00 | 0.00 |
| February | 168.40 | 105.17 | 63.23 | 234.54 | 108.99 | 0.00 | 0.00 | 0.00 |
| March | 130.02 | 62.16 | 67.86 | 177.86 | 115.12 | 0.00 | 0.00 | 0.00 |
| April | 114.46 | 46.59 | 67.87 | 166.08 | 97.29 | 0.00 | 0.00 | 0.00 |
| May | 77.58 | 9.07 | 68.51 | 88.85 | 88.38 | 0.00 | 0.00 | 0.00 |
| June | 68.60 | 4.22 | 64.38 | 77.21 | 70.70 | 0.00 | 0.00 | 0.00 |
| July | 72.70 | 8.29 | 64.41 | 96.50 | 62.50 | 0.00 | 0.00 | 0.00 |
| August | 92.81 | 28.98 | 63.84 | 144.42 | 65.05 | 0.00 | 0.00 | 0.00 |
| September | 127.74 | 63.73 | 64.01 | 202.19 | 74.65 | 0.00 | 0.00 | 0.00 |
| October | 167.71 | 113.02 | 54.69 | 270.08 | 78.88 | 0.00 | 0.00 | 0.00 |
| November | 202.16 | 143.19 | 58.96 | 298.35 | 109.67 | 0.00 | 0.00 | 0.00 |
| December | 223.90 | 170.43 | 53.47 | 333.21 | 120.33 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 137.72 | 75.49 | 62.23 | 199.62 | 92.66 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 68.60 | 4.22 | 53.47 | 77.21 | 62.50 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 223.90 | 170.43 | 68.51 | 333.21 | 121.36 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: TWINDOW1 W SWA
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 53.65 | 27.06 | 26.59 | 63.20 | 85.15 | 0.00 | 0.00 | 0.00 |
| February | 63.94 | 29.50 | 34.44 | 73.89 | 74.19 | 0.00 | 0.00 | 0.00 |
| March | 73.27 | 32.40 | 40.87 | 87.76 | 75.25 | 0.00 | 0.00 | 0.00 |
| April | 100.87 | 52.42 | 48.45 | 137.16 | 61.36 | 0.00 | 0.00 | 0.00 |
| May | 99.11 | 45.67 | 53.45 | 132.06 | 54.49 | 0.00 | 0.00 | 0.00 |
| June | 105.23 | 52.63 | 52.60 | 147.47 | 43.54 | 0.00 | 0.00 | 0.00 |
| July | 111.41 | 59.63 | 51.78 | 165.36 | 38.61 | 0.00 | 0.00 | 0.00 |
| August | 104.36 | 56.50 | 47.86 | 156.06 | 41.01 | 0.00 | 0.00 | 0.00 |
| September | 89.36 | 47.76 | 41.59 | 128.31 | 47.68 | 0.00 | 0.00 | 0.00 |
| October | 68.39 | 37.36 | 31.03 | 100.52 | 53.23 | 0.00 | 0.00 | 0.00 |
| November | 61.67 | 32.20 | 29.46 | 76.12 | 75.63 | 0.00 | 0.00 | 0.00 |
| December | 54.37 | 29.08 | 25.29 | 65.62 | 84.90 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 82.21 | 41.90 | 40.30 | 111.31 | 61.19 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 53.65 | 27.06 | 25.29 | 63.20 | 38.61 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 111.41 | 59.63 | 53.45 | 165.36 | 85.15 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: TWINDOW1 W NWA
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 53.65 | 27.06 | 26.59 | 69.79 | 78.90 | 0.00 | 0.00 | 0.00 |
| February | 63.94 | 29.50 | 34.44 | 79.21 | 70.00 | 0.00 | 0.00 | 0.00 |
| March | 73.27 | 32.40 | 40.87 | 91.57 | 72.74 | 0.00 | 0.00 | 0.00 |
| April | 100.87 | 52.42 | 48.45 | 139.89 | 59.74 | 0.00 | 0.00 | 0.00 |
| May | 99.11 | 45.67 | 53.45 | 132.54 | 54.52 | 0.00 | 0.00 | 0.00 |
| June | 105.23 | 52.63 | 52.60 | 147.46 | 43.77 | 0.00 | 0.00 | 0.00 |
| July | 111.41 | 59.63 | 51.78 | 165.69 | 38.68 | 0.00 | 0.00 | 0.00 |
| August | 104.36 | 56.50 | 47.86 | 157.33 | 40.58 | 0.00 | 0.00 | 0.00 |
| September | 89.36 | 47.76 | 41.59 | 130.70 | 46.39 | 0.00 | 0.00 | 0.00 |
| October | 68.39 | 37.36 | 31.03 | 103.96 | 50.99 | 0.00 | 0.00 | 0.00 |
| November | 61.67 | 32.20 | 29.46 | 82.42 | 69.82 | 0.00 | 0.00 | 0.00 |
| December | 54.37 | 29.08 | 25.29 | 72.18 | 78.39 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 82.21 | 41.90 | 40.30 | 114.57 | 58.66 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 53.65 | 27.06 | 25.29 | 69.79 | 38.68 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 111.41 | 59.63 | 53.45 | 165.69 | 78.90 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: TWINDOW1 N NWA
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 31.75 | 0.00 | 31.75 | 20.98 | 124.22 | 0.00 | 0.00 | 0.00 |
| February | 39.85 | 0.00 | 39.85 | 25.60 | 110.69 | 0.00 | 0.00 | 0.00 |
| March | 48.84 | 0.00 | 48.84 | 36.08 | 114.79 | 0.00 | 0.00 | 0.00 |
| April | 56.41 | 0.34 | 56.08 | 46.72 | 92.65 | 0.00 | 0.00 | 0.00 |
| May | 68.03 | 3.54 | 64.49 | 60.32 | 80.55 | 0.00 | 0.00 | 0.00 |
| June | 71.93 | 6.94 | 64.99 | 73.77 | 64.64 | 0.00 | 0.00 | 0.00 |
| July | 68.12 | 5.62 | 62.51 | 77.22 | 57.81 | 0.00 | 0.00 | 0.00 |
| August | 56.86 | 1.33 | 55.53 | 61.98 | 61.35 | 0.00 | 0.00 | 0.00 |
| September | 47.96 | 0.02 | 47.94 | 48.49 | 73.58 | 0.00 | 0.00 | 0.00 |
| October | 38.03 | 0.00 | 38.03 | 44.40 | 80.06 | 0.00 | 0.00 | 0.00 |
| November | 34.43 | 0.00 | 34.43 | 24.74 | 110.72 | 0.00 | 0.00 | 0.00 |
| December | 29.55 | 0.00 | 29.55 | 18.87 | 123.97 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 49.35 | 1.49 | 47.86 | 45.05 | 91.16 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 29.55 | 0.00 | 29.55 | 18.87 | 57.81 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 71.93 | 6.94 | 64.99 | 77.22 | 124.22 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: TWINDOW1 S SEA
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 208.37 | 152.54 | 55.84 | 306.20 | 120.77 | 0.00 | 0.00 | 0.00 |
| February | 168.40 | 105.17 | 63.23 | 233.27 | 107.98 | 0.00 | 0.00 | 0.00 |
| March | 130.02 | 62.16 | 67.86 | 176.22 | 114.15 | 0.00 | 0.00 | 0.00 |
| April | 114.46 | 46.59 | 67.87 | 164.12 | 95.77 | 0.00 | 0.00 | 0.00 |
| May | 77.58 | 9.07 | 68.51 | 87.23 | 86.76 | 0.00 | 0.00 | 0.00 |
| June | 68.60 | 4.22 | 64.38 | 76.26 | 69.11 | 0.00 | 0.00 | 0.00 |
| July | 72.70 | 8.29 | 64.41 | 95.52 | 61.12 | 0.00 | 0.00 | 0.00 |
| August | 92.81 | 28.98 | 63.84 | 143.34 | 63.89 | 0.00 | 0.00 | 0.00 |
| September | 127.74 | 63.73 | 64.01 | 201.60 | 73.33 | 0.00 | 0.00 | 0.00 |
| October | 167.71 | 113.02 | 54.69 | 269.17 | 78.11 | 0.00 | 0.00 | 0.00 |
| November | 202.16 | 143.19 | 58.96 | 297.07 | 108.63 | 0.00 | 0.00 | 0.00 |
| December | 223.90 | 170.43 | 53.47 | 331.83 | 119.55 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 137.72 | 75.49 | 62.23 | 198.35 | 91.52 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 68.60 | 4.22 | 53.47 | 76.26 | 61.12 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 223.90 | 170.43 | 68.51 | 331.83 | 120.77 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: TWINDOW1 E SEA
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 56.59 | 30.37 | 26.22 | 65.92 | 82.68 | 0.00 | 0.00 | 0.00 |
| February | 59.06 | 26.86 | 32.21 | 65.19 | 72.77 | 0.00 | 0.00 | 0.00 |
| March | 72.41 | 32.30 | 40.11 | 85.15 | 72.99 | 0.00 | 0.00 | 0.00 |
| April | 92.67 | 46.65 | 46.02 | 124.18 | 59.75 | 0.00 | 0.00 | 0.00 |
| May | 87.05 | 36.28 | 50.77 | 113.11 | 53.41 | 0.00 | 0.00 | 0.00 |
| June | 86.61 | 37.60 | 49.00 | 119.47 | 43.44 | 0.00 | 0.00 | 0.00 |
| July | 98.14 | 48.81 | 49.33 | 146.14 | 38.90 | 0.00 | 0.00 | 0.00 |
| August | 96.85 | 51.43 | 45.42 | 145.23 | 40.13 | 0.00 | 0.00 | 0.00 |
| September | 70.69 | 32.48 | 38.21 | 99.07 | 47.30 | 0.00 | 0.00 | 0.00 |
| October | 62.15 | 31.80 | 30.35 | 89.43 | 52.07 | 0.00 | 0.00 | 0.00 |
| November | 56.68 | 28.68 | 28.00 | 66.50 | 74.42 | 0.00 | 0.00 | 0.00 |
| December | 54.43 | 30.29 | 24.14 | 63.21 | 82.46 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 74.55 | 36.20 | 38.34 | 98.78 | 59.96 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 54.43 | 26.86 | 24.14 | 63.21 | 38.90 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 98.14 | 51.43 | 50.77 | 146.14 | 82.68 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: TWINDOW1 E NEA
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 56.59 | 30.37 | 26.22 | 71.31 | 75.04 | 0.00 | 0.00 | 0.00 |
| February | 59.06 | 26.86 | 32.21 | 69.70 | 67.43 | 0.00 | 0.00 | 0.00 |
| March | 72.41 | 32.30 | 40.11 | 88.34 | 69.83 | 0.00 | 0.00 | 0.00 |
| April | 92.67 | 46.65 | 46.02 | 126.61 | 57.75 | 0.00 | 0.00 | 0.00 |
| May | 87.05 | 36.28 | 50.77 | 113.54 | 53.40 | 0.00 | 0.00 | 0.00 |
| June | 86.61 | 37.60 | 49.00 | 119.51 | 43.75 | 0.00 | 0.00 | 0.00 |
| July | 98.14 | 48.81 | 49.33 | 146.51 | 38.98 | 0.00 | 0.00 | 0.00 |
| August | 96.85 | 51.43 | 45.42 | 146.43 | 39.62 | 0.00 | 0.00 | 0.00 |
| September | 70.69 | 32.48 | 38.21 | 101.27 | 45.69 | 0.00 | 0.00 | 0.00 |
| October | 62.15 | 31.80 | 30.35 | 92.52 | 49.38 | 0.00 | 0.00 | 0.00 |
| November | 56.68 | 28.68 | 28.00 | 71.86 | 67.18 | 0.00 | 0.00 | 0.00 |
| December | 54.43 | 30.29 | 24.14 | 68.73 | 74.57 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 74.55 | 36.20 | 38.34 | 101.58 | 56.83 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 54.43 | 26.86 | 24.14 | 68.73 | 38.98 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 98.14 | 51.43 | 50.77 | 146.51 | 75.04 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: TWINDOW1 N NEA
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 31.75 | 0.00 | 31.75 | 19.54 | 123.28 | 0.00 | 0.00 | 0.00 |
| February | 39.85 | 0.00 | 39.85 | 24.26 | 108.93 | 0.00 | 0.00 | 0.00 |
| March | 48.84 | 0.00 | 48.84 | 34.31 | 113.50 | 0.00 | 0.00 | 0.00 |
| April | 56.41 | 0.34 | 56.08 | 44.56 | 90.73 | 0.00 | 0.00 | 0.00 |
| May | 68.03 | 3.54 | 64.49 | 58.86 | 79.11 | 0.00 | 0.00 | 0.00 |
| June | 71.93 | 6.94 | 64.99 | 73.11 | 63.40 | 0.00 | 0.00 | 0.00 |
| July | 68.12 | 5.62 | 62.51 | 76.50 | 56.69 | 0.00 | 0.00 | 0.00 |
| August | 56.86 | 1.33 | 55.53 | 60.91 | 60.20 | 0.00 | 0.00 | 0.00 |
| September | 47.96 | 0.02 | 47.94 | 47.72 | 71.87 | 0.00 | 0.00 | 0.00 |
| October | 38.03 | 0.00 | 38.03 | 43.17 | 78.88 | 0.00 | 0.00 | 0.00 |
| November | 34.43 | 0.00 | 34.43 | 23.40 | 108.79 | 0.00 | 0.00 | 0.00 |
| December | 29.55 | 0.00 | 29.55 | 17.58 | 122.71 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 49.35 | 1.49 | 47.86 | 43.78 | 89.75 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 29.55 | 0.00 | 29.55 | 17.58 | 56.69 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 71.93 | 6.94 | 64.99 | 76.50 | 123.28 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: TWINDOW1 N N1A
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 31.75 | 0.00 | 31.75 | 20.66 | 126.08 | 0.00 | 0.00 | 0.00 |
| February | 39.85 | 0.00 | 39.85 | 25.47 | 111.86 | 0.00 | 0.00 | 0.00 |
| March | 48.84 | 0.00 | 48.84 | 36.02 | 116.28 | 0.00 | 0.00 | 0.00 |
| April | 56.41 | 0.34 | 56.08 | 47.04 | 94.07 | 0.00 | 0.00 | 0.00 |
| May | 68.03 | 3.54 | 64.49 | 60.47 | 82.50 | 0.00 | 0.00 | 0.00 |
| June | 71.93 | 6.94 | 64.99 | 74.49 | 65.85 | 0.00 | 0.00 | 0.00 |
| July | 68.12 | 5.62 | 62.51 | 78.70 | 58.16 | 0.00 | 0.00 | 0.00 |
| August | 56.86 | 1.33 | 55.53 | 63.19 | 61.90 | 0.00 | 0.00 | 0.00 |
| September | 47.96 | 0.02 | 47.94 | 48.97 | 74.71 | 0.00 | 0.00 | 0.00 |
| October | 38.03 | 0.00 | 38.03 | 44.56 | 81.60 | 0.00 | 0.00 | 0.00 |
| November | 34.43 | 0.00 | 34.43 | 24.55 | 112.12 | 0.00 | 0.00 | 0.00 |
| December | 29.55 | 0.00 | 29.55 | 18.68 | 125.63 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 49.35 | 1.49 | 47.86 | 45.36 | 92.47 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 29.55 | 0.00 | 29.55 | 18.68 | 58.16 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 71.93 | 6.94 | 64.99 | 78.70 | 126.08 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: TWINDOW1 N N2A
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 31.75 | 0.00 | 31.75 | 20.55 | 126.04 | 0.00 | 0.00 | 0.00 |
| February | 39.85 | 0.00 | 39.85 | 25.36 | 111.72 | 0.00 | 0.00 | 0.00 |
| March | 48.84 | 0.00 | 48.84 | 35.87 | 116.21 | 0.00 | 0.00 | 0.00 |
| April | 56.41 | 0.34 | 56.08 | 46.89 | 93.91 | 0.00 | 0.00 | 0.00 |
| May | 68.03 | 3.54 | 64.49 | 60.37 | 82.37 | 0.00 | 0.00 | 0.00 |
| June | 71.93 | 6.94 | 64.99 | 74.46 | 65.76 | 0.00 | 0.00 | 0.00 |
| July | 68.12 | 5.62 | 62.51 | 78.68 | 58.09 | 0.00 | 0.00 | 0.00 |
| August | 56.86 | 1.33 | 55.53 | 63.14 | 61.83 | 0.00 | 0.00 | 0.00 |
| September | 47.96 | 0.02 | 47.94 | 48.94 | 74.56 | 0.00 | 0.00 | 0.00 |
| October | 38.03 | 0.00 | 38.03 | 44.48 | 81.51 | 0.00 | 0.00 | 0.00 |
| November | 34.43 | 0.00 | 34.43 | 24.45 | 111.96 | 0.00 | 0.00 | 0.00 |
| December | 29.55 | 0.00 | 29.55 | 18.58 | 125.54 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 49.35 | 1.49 | 47.86 | 45.27 | 92.36 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 29.55 | 0.00 | 29.55 | 18.58 | 58.09 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 71.93 | 6.94 | 64.99 | 78.68 | 126.04 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: TWINDOW1 S S1A
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 208.37 | 152.54 | 55.84 | 306.45 | 125.20 | 0.00 | 0.00 | 0.00 |
| February | 168.40 | 105.17 | 63.23 | 233.50 | 112.43 | 0.00 | 0.00 | 0.00 |
| March | 130.02 | 62.16 | 67.86 | 177.08 | 118.24 | 0.00 | 0.00 | 0.00 |
| April | 114.46 | 46.59 | 67.87 | 165.90 | 99.49 | 0.00 | 0.00 | 0.00 |
| May | 77.58 | 9.07 | 68.51 | 88.79 | 90.31 | 0.00 | 0.00 | 0.00 |
| June | 68.60 | 4.22 | 64.38 | 77.69 | 71.70 | 0.00 | 0.00 | 0.00 |
| July | 72.70 | 8.29 | 64.41 | 97.63 | 62.61 | 0.00 | 0.00 | 0.00 |
| August | 92.81 | 28.98 | 63.84 | 145.38 | 65.51 | 0.00 | 0.00 | 0.00 |
| September | 127.74 | 63.73 | 64.01 | 202.53 | 75.93 | 0.00 | 0.00 | 0.00 |
| October | 167.71 | 113.02 | 54.69 | 269.91 | 80.97 | 0.00 | 0.00 | 0.00 |
| November | 202.16 | 143.19 | 58.96 | 297.15 | 113.35 | 0.00 | 0.00 | 0.00 |
| December | 223.90 | 170.43 | 53.47 | 331.91 | 124.20 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 137.72 | 75.49 | 62.23 | 199.36 | 94.91 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 68.60 | 4.22 | 53.47 | 77.69 | 62.61 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 223.90 | 170.43 | 68.51 | 331.91 | 125.20 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: TWINDOW1 S S2A
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 208.37 | 152.54 | 55.84 | 306.35 | 125.17 | 0.00 | 0.00 | 0.00 |
| February | 168.40 | 105.17 | 63.23 | 233.42 | 112.35 | 0.00 | 0.00 | 0.00 |
| March | 130.02 | 62.16 | 67.86 | 176.97 | 118.17 | 0.00 | 0.00 | 0.00 |
| April | 114.46 | 46.59 | 67.87 | 165.79 | 99.38 | 0.00 | 0.00 | 0.00 |
| May | 77.58 | 9.07 | 68.51 | 88.69 | 90.17 | 0.00 | 0.00 | 0.00 |
| June | 68.60 | 4.22 | 64.38 | 77.65 | 71.58 | 0.00 | 0.00 | 0.00 |
| July | 72.70 | 8.29 | 64.41 | 97.59 | 62.52 | 0.00 | 0.00 | 0.00 |
| August | 92.81 | 28.98 | 63.84 | 145.34 | 65.43 | 0.00 | 0.00 | 0.00 |
| September | 127.74 | 63.73 | 64.01 | 202.51 | 75.83 | 0.00 | 0.00 | 0.00 |
| October | 167.71 | 113.02 | 54.69 | 269.87 | 80.92 | 0.00 | 0.00 | 0.00 |
| November | 202.16 | 143.19 | 58.96 | 297.08 | 113.27 | 0.00 | 0.00 | 0.00 |
| December | 223.90 | 170.43 | 53.47 | 331.83 | 124.15 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 137.72 | 75.49 | 62.23 | 199.29 | 94.82 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 68.60 | 4.22 | 53.47 | 77.65 | 62.52 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 223.90 | 170.43 | 68.51 | 331.83 | 125.17 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: TWINDOW14
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 13.58 | 7.29 | 6.29 | 16.21 | 20.98 | 285.33 | 0.00 | 0.00 |
| February | 14.17 | 6.44 | 7.73 | 15.72 | 19.02 | 158.50 | 0.00 | 0.00 |
| March | 17.37 | 7.75 | 9.62 | 20.28 | 19.25 | 250.50 | 0.00 | 0.00 |
| April | 22.24 | 11.19 | 11.04 | 29.48 | 16.23 | 274.17 | 0.00 | 0.00 |
| May | 20.89 | 8.71 | 12.18 | 26.32 | 14.89 | 269.00 | 0.00 | 0.00 |
| June | 20.78 | 9.02 | 11.76 | 27.59 | 12.35 | 307.50 | 0.00 | 0.00 |
| July | 23.55 | 11.71 | 11.84 | 33.94 | 11.10 | 342.83 | 0.00 | 0.00 |
| August | 23.24 | 12.34 | 10.90 | 33.86 | 11.40 | 360.83 | 0.00 | 0.00 |
| September | 16.96 | 7.79 | 9.17 | 23.23 | 13.22 | 367.33 | 0.00 | 0.00 |
| October | 14.91 | 7.63 | 7.28 | 21.18 | 14.33 | 282.83 | 0.00 | 0.00 |
| November | 13.60 | 6.88 | 6.72 | 16.22 | 19.19 | 266.33 | 0.00 | 0.00 |
| December | 13.06 | 7.27 | 5.79 | 15.57 | 20.90 | 208.50 | 0.00 | 0.00 |
| Annual Sum or Average | 17.89 | 8.69 | 9.20 | 23.35 | 16.06 | 3373.67 | 0.00 | 0.00 |
| Minimum of Months | 13.06 | 6.44 | 5.79 | 15.57 | 11.10 | 158.50 | 0.00 | 0.00 |
| Maximum of Months | 23.55 | 12.34 | 12.18 | 33.94 | 20.98 | 367.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ENTRANCE DOOR
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 40.44 | 21.70 | 18.74 | 48.33 | 62.10 | 0.00 | 0.00 | 0.00 |
| February | 42.21 | 19.19 | 23.02 | 47.57 | 55.51 | 0.00 | 0.00 | 0.00 |
| March | 51.75 | 23.08 | 28.66 | 62.54 | 54.40 | 0.00 | 0.00 | 0.00 |
| April | 66.23 | 33.34 | 32.89 | 90.02 | 45.99 | 0.67 | 0.00 | 0.00 |
| May | 62.21 | 25.93 | 36.28 | 80.00 | 43.07 | 0.33 | 0.00 | 0.00 |
| June | 61.89 | 26.87 | 35.02 | 84.32 | 35.33 | 2.17 | 0.00 | 0.00 |
| July | 70.14 | 34.88 | 35.26 | 102.66 | 32.77 | 14.33 | 0.00 | 0.00 |
| August | 69.21 | 36.75 | 32.46 | 102.08 | 33.84 | 15.83 | 0.00 | 0.00 |
| September | 50.52 | 23.21 | 27.31 | 69.67 | 39.33 | 10.67 | 0.00 | 0.00 |
| October | 44.42 | 22.73 | 21.69 | 61.95 | 44.23 | 6.83 | 0.00 | 0.00 |
| November | 40.50 | 20.49 | 20.01 | 47.20 | 59.07 | 2.00 | 0.00 | 0.00 |
| December | 38.90 | 21.65 | 17.25 | 45.78 | 63.40 | 0.33 | 0.00 | 0.00 |
| Annual Sum or Average | 53.27 | 25.87 | 27.40 | 70.33 | 47.38 | 53.17 | 0.00 | 0.00 |
| Minimum of Months | 38.90 | 19.19 | 17.25 | 45.78 | 32.77 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 70.14 | 36.75 | 36.28 | 102.66 | 63.40 | 15.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MWINDOW14
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 13.58 | 7.29 | 6.29 | 14.79 | 23.89 | 517.17 | 0.00 | 0.00 |
| February | 14.17 | 6.44 | 7.73 | 14.15 | 22.43 | 353.33 | 0.00 | 0.00 |
| March | 17.37 | 7.75 | 9.62 | 18.72 | 22.11 | 420.33 | 0.00 | 0.00 |
| April | 22.24 | 11.19 | 11.04 | 28.14 | 18.24 | 380.00 | 0.00 | 0.00 |
| May | 20.89 | 8.71 | 12.18 | 24.85 | 16.72 | 386.00 | 0.00 | 0.00 |
| June | 20.78 | 9.02 | 11.76 | 26.91 | 13.33 | 379.00 | 0.00 | 0.00 |
| July | 23.55 | 11.71 | 11.84 | 33.73 | 11.71 | 381.83 | 0.00 | 0.00 |
| August | 23.24 | 12.34 | 10.90 | 33.63 | 12.06 | 395.83 | 0.00 | 0.00 |
| September | 16.96 | 7.79 | 9.17 | 22.68 | 14.35 | 429.00 | 0.00 | 0.00 |
| October | 14.91 | 7.63 | 7.28 | 20.28 | 15.81 | 409.50 | 0.00 | 0.00 |
| November | 13.60 | 6.88 | 6.72 | 14.56 | 22.36 | 445.67 | 0.00 | 0.00 |
| December | 13.06 | 7.27 | 5.79 | 14.03 | 24.24 | 453.83 | 0.00 | 0.00 |
| Annual Sum or Average | 17.89 | 8.69 | 9.20 | 22.26 | 18.08 | 4951.50 | 0.00 | 0.00 |
| Minimum of Months | 13.06 | 6.44 | 5.79 | 14.03 | 11.71 | 353.33 | 0.00 | 0.00 |
| Maximum of Months | 23.55 | 12.34 | 12.18 | 33.73 | 24.24 | 517.17 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: GWINDOW1 S SWA
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.558100E+09 | 0.408550E+09 | 0.149550E+09 | 0.827768E+09 | 0.348316E+09 |
| February | 0.407389E+09 | 0.254418E+09 | 0.152971E+09 | 0.573717E+09 | 0.279708E+09 |
| March | 0.348235E+09 | 0.166487E+09 | 0.181748E+09 | 0.488998E+09 | 0.313563E+09 |
| April | 0.296676E+09 | 0.120757E+09 | 0.175919E+09 | 0.442864E+09 | 0.258989E+09 |
| May | 0.207778E+09 | 24292585.19 | 0.183485E+09 | 0.247656E+09 | 0.244043E+09 |
| June | 0.177817E+09 | 10947826.02 | 0.166869E+09 | 0.212558E+09 | 0.184203E+09 |
| July | 0.194710E+09 | 22191625.47 | 0.172518E+09 | 0.271024E+09 | 0.170138E+09 |
| August | 0.248589E+09 | 77611251.15 | 0.170978E+09 | 0.399596E+09 | 0.178213E+09 |
| September | 0.331094E+09 | 0.165190E+09 | 0.165904E+09 | 0.533195E+09 | 0.203958E+09 |
| October | 0.449202E+09 | 0.302718E+09 | 0.146484E+09 | 0.728202E+09 | 0.228973E+09 |
| November | 0.523988E+09 | 0.371153E+09 | 0.152836E+09 | 0.771367E+09 | 0.316254E+09 |
| December | 0.599695E+09 | 0.456477E+09 | 0.143218E+09 | 0.892909E+09 | 0.353315E+09 |
| Annual Sum or Average | 0.434327E+10 | 0.238079E+10 | 0.196248E+10 | 0.638985E+10 | 0.307967E+10 |
| Minimum of Months | 0.177817E+09 | 10947826.02 | 0.143218E+09 | 0.212558E+09 | 0.170138E+09 |
| Maximum of Months | 0.599695E+09 | 0.456477E+09 | 0.183485E+09 | 0.892909E+09 | 0.353315E+09 |
Report: WindowEnergyReportMonthly
For: GWINDOW1 W SWA
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.143689E+09 | 72468237.92 | 71221005.30 | 0.174553E+09 | 0.246709E+09 |
| February | 0.154680E+09 | 71369157.64 | 83310528.17 | 0.184272E+09 | 0.192033E+09 |
| March | 0.196253E+09 | 86790430.64 | 0.109462E+09 | 0.245505E+09 | 0.206729E+09 |
| April | 0.261451E+09 | 0.135861E+09 | 0.125590E+09 | 0.366841E+09 | 0.164924E+09 |
| May | 0.265469E+09 | 0.122310E+09 | 0.143158E+09 | 0.363601E+09 | 0.152241E+09 |
| June | 0.272765E+09 | 0.136420E+09 | 0.136345E+09 | 0.394629E+09 | 0.114691E+09 |
| July | 0.298394E+09 | 0.159707E+09 | 0.138687E+09 | 0.454982E+09 | 0.106166E+09 |
| August | 0.279518E+09 | 0.151324E+09 | 0.128193E+09 | 0.429391E+09 | 0.113264E+09 |
| September | 0.231610E+09 | 0.123800E+09 | 0.107810E+09 | 0.340587E+09 | 0.131257E+09 |
| October | 0.183177E+09 | 0.100062E+09 | 83114403.80 | 0.274118E+09 | 0.156089E+09 |
| November | 0.159839E+09 | 83472084.97 | 76367302.03 | 0.199427E+09 | 0.221101E+09 |
| December | 0.145628E+09 | 77877952.25 | 67749887.84 | 0.179550E+09 | 0.252291E+09 |
| Annual Sum or Average | 0.259247E+10 | 0.132146E+10 | 0.127101E+10 | 0.360746E+10 | 0.205749E+10 |
| Minimum of Months | 0.143689E+09 | 71369157.64 | 67749887.84 | 0.174553E+09 | 0.106166E+09 |
| Maximum of Months | 0.298394E+09 | 0.159707E+09 | 0.143158E+09 | 0.454982E+09 | 0.252291E+09 |
Report: WindowEnergyReportMonthly
For: GWINDOW1 W NWA
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.143689E+09 | 72468237.92 | 71221005.30 | 0.189371E+09 | 0.220805E+09 |
| February | 0.154680E+09 | 71369157.64 | 83310528.17 | 0.197695E+09 | 0.171306E+09 |
| March | 0.196253E+09 | 86790430.64 | 0.109462E+09 | 0.256510E+09 | 0.193692E+09 |
| April | 0.261451E+09 | 0.135861E+09 | 0.125590E+09 | 0.375883E+09 | 0.154804E+09 |
| May | 0.265469E+09 | 0.122310E+09 | 0.143158E+09 | 0.365532E+09 | 0.150853E+09 |
| June | 0.272765E+09 | 0.136420E+09 | 0.136345E+09 | 0.394632E+09 | 0.115138E+09 |
| July | 0.298394E+09 | 0.159707E+09 | 0.138687E+09 | 0.455633E+09 | 0.106087E+09 |
| August | 0.279518E+09 | 0.151324E+09 | 0.128193E+09 | 0.431982E+09 | 0.111727E+09 |
| September | 0.231610E+09 | 0.123800E+09 | 0.107810E+09 | 0.345100E+09 | 0.127352E+09 |
| October | 0.183177E+09 | 0.100062E+09 | 83114403.80 | 0.280234E+09 | 0.149026E+09 |
| November | 0.159839E+09 | 83472084.97 | 76367302.03 | 0.212935E+09 | 0.197420E+09 |
| December | 0.145628E+09 | 77877952.25 | 67749887.84 | 0.195001E+09 | 0.221927E+09 |
| Annual Sum or Average | 0.259247E+10 | 0.132146E+10 | 0.127101E+10 | 0.370051E+10 | 0.192014E+10 |
| Minimum of Months | 0.143689E+09 | 71369157.64 | 67749887.84 | 0.189371E+09 | 0.106087E+09 |
| Maximum of Months | 0.298394E+09 | 0.159707E+09 | 0.143158E+09 | 0.455633E+09 | 0.221927E+09 |
Report: WindowEnergyReportMonthly
For: GWINDOW1 N NWA
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 85027568.61 | 0.00 | 85027568.61 | 56244325.74 | 0.345698E+09 |
| February | 96403407.70 | 0.00 | 96403407.70 | 66215455.25 | 0.268638E+09 |
| March | 0.130807E+09 | 4105.79 | 0.130803E+09 | 0.107396E+09 | 0.302829E+09 |
| April | 0.146218E+09 | 871123.55 | 0.145347E+09 | 0.134914E+09 | 0.237665E+09 |
| May | 0.182204E+09 | 9470778.58 | 0.172733E+09 | 0.171800E+09 | 0.221262E+09 |
| June | 0.186449E+09 | 17985183.97 | 0.168464E+09 | 0.205526E+09 | 0.168897E+09 |
| July | 0.182464E+09 | 15043009.94 | 0.167421E+09 | 0.220334E+09 | 0.157768E+09 |
| August | 0.152292E+09 | 3553362.43 | 0.148739E+09 | 0.177003E+09 | 0.167915E+09 |
| September | 0.124304E+09 | 43830.25 | 0.124260E+09 | 0.130599E+09 | 0.200413E+09 |
| October | 0.101863E+09 | 0.00 | 0.101863E+09 | 0.117987E+09 | 0.232844E+09 |
| November | 89254512.61 | 0.00 | 89254512.61 | 59904466.02 | 0.311370E+09 |
| December | 79153413.08 | 0.00 | 79153413.08 | 49758879.55 | 0.349214E+09 |
| Annual Sum or Average | 0.155644E+10 | 46971394.51 | 0.150947E+10 | 0.149768E+10 | 0.296451E+10 |
| Minimum of Months | 79153413.08 | 0.00 | 79153413.08 | 49758879.55 | 0.157768E+09 |
| Maximum of Months | 0.186449E+09 | 17985183.97 | 0.172733E+09 | 0.220334E+09 | 0.349214E+09 |
Report: WindowEnergyReportMonthly
For: GWINDOW1 S SEA
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.558100E+09 | 0.408550E+09 | 0.149550E+09 | 0.822890E+09 | 0.360176E+09 |
| February | 0.407389E+09 | 0.254418E+09 | 0.152971E+09 | 0.567668E+09 | 0.292890E+09 |
| March | 0.348235E+09 | 0.166487E+09 | 0.181748E+09 | 0.479903E+09 | 0.327982E+09 |
| April | 0.296676E+09 | 0.120757E+09 | 0.175919E+09 | 0.435465E+09 | 0.272518E+09 |
| May | 0.207778E+09 | 24292585.19 | 0.183485E+09 | 0.239371E+09 | 0.258946E+09 |
| June | 0.177817E+09 | 10947826.02 | 0.166869E+09 | 0.203639E+09 | 0.200996E+09 |
| July | 0.194710E+09 | 22191625.47 | 0.172518E+09 | 0.254641E+09 | 0.197315E+09 |
| August | 0.248589E+09 | 77611251.15 | 0.170978E+09 | 0.384405E+09 | 0.209958E+09 |
| September | 0.331094E+09 | 0.165190E+09 | 0.165904E+09 | 0.521191E+09 | 0.231672E+09 |
| October | 0.449202E+09 | 0.302718E+09 | 0.146484E+09 | 0.711685E+09 | 0.265339E+09 |
| November | 0.523988E+09 | 0.371153E+09 | 0.152836E+09 | 0.764746E+09 | 0.331634E+09 |
| December | 0.599695E+09 | 0.456477E+09 | 0.143218E+09 | 0.886410E+09 | 0.367410E+09 |
| Annual Sum or Average | 0.434327E+10 | 0.238079E+10 | 0.196248E+10 | 0.627201E+10 | 0.331684E+10 |
| Minimum of Months | 0.177817E+09 | 10947826.02 | 0.143218E+09 | 0.203639E+09 | 0.197315E+09 |
| Maximum of Months | 0.599695E+09 | 0.456477E+09 | 0.183485E+09 | 0.886410E+09 | 0.367410E+09 |
Report: WindowEnergyReportMonthly
For: GWINDOW1 E SEA
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.151566E+09 | 81345771.80 | 70219965.56 | 0.175037E+09 | 0.243429E+09 |
| February | 0.142885E+09 | 64974608.46 | 77910475.06 | 0.157051E+09 | 0.195582E+09 |
| March | 0.193935E+09 | 86505392.46 | 0.107430E+09 | 0.230884E+09 | 0.208504E+09 |
| April | 0.240203E+09 | 0.120907E+09 | 0.119296E+09 | 0.326230E+09 | 0.168914E+09 |
| May | 0.233159E+09 | 97178220.02 | 0.135981E+09 | 0.304221E+09 | 0.158096E+09 |
| June | 0.224485E+09 | 97471532.68 | 0.127013E+09 | 0.312243E+09 | 0.125394E+09 |
| July | 0.262868E+09 | 0.130731E+09 | 0.132136E+09 | 0.389052E+09 | 0.124482E+09 |
| August | 0.259391E+09 | 0.137743E+09 | 0.121648E+09 | 0.386960E+09 | 0.130619E+09 |
| September | 0.183233E+09 | 84190753.46 | 99042488.23 | 0.253894E+09 | 0.148745E+09 |
| October | 0.166464E+09 | 85183840.87 | 81280020.36 | 0.231955E+09 | 0.176017E+09 |
| November | 0.146903E+09 | 74325622.94 | 72577234.58 | 0.166328E+09 | 0.224865E+09 |
| December | 0.145791E+09 | 81141408.66 | 64649311.14 | 0.165112E+09 | 0.250950E+09 |
| Annual Sum or Average | 0.235088E+10 | 0.114170E+10 | 0.120918E+10 | 0.309897E+10 | 0.215560E+10 |
| Minimum of Months | 0.142885E+09 | 64974608.46 | 64649311.14 | 0.157051E+09 | 0.124482E+09 |
| Maximum of Months | 0.262868E+09 | 0.137743E+09 | 0.135981E+09 | 0.389052E+09 | 0.250950E+09 |
Report: WindowEnergyReportMonthly
For: GWINDOW1 E NEA
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.151566E+09 | 81345771.80 | 70219965.56 | 0.191238E+09 | 0.209490E+09 |
| February | 0.142885E+09 | 64974608.46 | 77910475.06 | 0.173068E+09 | 0.164627E+09 |
| March | 0.193935E+09 | 86505392.46 | 0.107430E+09 | 0.245838E+09 | 0.184996E+09 |
| April | 0.240203E+09 | 0.120907E+09 | 0.119296E+09 | 0.339266E+09 | 0.148539E+09 |
| May | 0.233159E+09 | 97178220.02 | 0.135981E+09 | 0.312023E+09 | 0.145628E+09 |
| June | 0.224485E+09 | 97471532.68 | 0.127013E+09 | 0.319027E+09 | 0.113647E+09 |
| July | 0.262868E+09 | 0.130731E+09 | 0.132136E+09 | 0.401502E+09 | 0.106606E+09 |
| August | 0.259391E+09 | 0.137743E+09 | 0.121648E+09 | 0.400403E+09 | 0.108889E+09 |
| September | 0.183233E+09 | 84190753.46 | 99042488.23 | 0.266368E+09 | 0.124994E+09 |
| October | 0.166464E+09 | 85183840.87 | 81280020.36 | 0.247338E+09 | 0.143420E+09 |
| November | 0.146903E+09 | 74325622.94 | 72577234.58 | 0.183232E+09 | 0.189255E+09 |
| December | 0.145791E+09 | 81141408.66 | 64649311.14 | 0.183604E+09 | 0.210468E+09 |
| Annual Sum or Average | 0.235088E+10 | 0.114170E+10 | 0.120918E+10 | 0.326291E+10 | 0.185056E+10 |
| Minimum of Months | 0.142885E+09 | 64974608.46 | 64649311.14 | 0.173068E+09 | 0.106606E+09 |
| Maximum of Months | 0.262868E+09 | 0.137743E+09 | 0.135981E+09 | 0.401502E+09 | 0.210468E+09 |
Report: WindowEnergyReportMonthly
For: GWINDOW1 N NEA
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 85027568.61 | 0.00 | 85027568.61 | 54379483.03 | 0.345844E+09 |
| February | 96403407.70 | 0.00 | 96403407.70 | 65072367.83 | 0.266849E+09 |
| March | 0.130807E+09 | 4105.79 | 0.130803E+09 | 0.105486E+09 | 0.301662E+09 |
| April | 0.146218E+09 | 871123.55 | 0.145347E+09 | 0.133241E+09 | 0.234735E+09 |
| May | 0.182204E+09 | 9470778.58 | 0.172733E+09 | 0.171379E+09 | 0.218055E+09 |
| June | 0.186449E+09 | 17985183.97 | 0.168464E+09 | 0.205763E+09 | 0.166118E+09 |
| July | 0.182464E+09 | 15043009.94 | 0.167421E+09 | 0.219721E+09 | 0.156088E+09 |
| August | 0.152292E+09 | 3553362.43 | 0.148739E+09 | 0.175881E+09 | 0.166404E+09 |
| September | 0.124304E+09 | 43830.25 | 0.124260E+09 | 0.130481E+09 | 0.197380E+09 |
| October | 0.101863E+09 | 0.00 | 0.101863E+09 | 0.117013E+09 | 0.231431E+09 |
| November | 89254512.61 | 0.00 | 89254512.61 | 58768083.89 | 0.308886E+09 |
| December | 79153413.08 | 0.00 | 79153413.08 | 48162404.74 | 0.348326E+09 |
| Annual Sum or Average | 0.155644E+10 | 46971394.51 | 0.150947E+10 | 0.148535E+10 | 0.294178E+10 |
| Minimum of Months | 79153413.08 | 0.00 | 79153413.08 | 48162404.74 | 0.156088E+09 |
| Maximum of Months | 0.186449E+09 | 17985183.97 | 0.172733E+09 | 0.219721E+09 | 0.348326E+09 |
Report: WindowEnergyReportMonthly
For: GWINDOW1 N N1A
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 85027568.61 | 0.00 | 85027568.61 | 53358762.36 | 0.356229E+09 |
| February | 96403407.70 | 0.00 | 96403407.70 | 62749827.01 | 0.279024E+09 |
| March | 0.130807E+09 | 4105.79 | 0.130803E+09 | 0.104024E+09 | 0.311801E+09 |
| April | 0.146218E+09 | 871123.55 | 0.145347E+09 | 0.133082E+09 | 0.243408E+09 |
| May | 0.182204E+09 | 9470778.58 | 0.172733E+09 | 0.168485E+09 | 0.227665E+09 |
| June | 0.186449E+09 | 17985183.97 | 0.168464E+09 | 0.204077E+09 | 0.172431E+09 |
| July | 0.182464E+09 | 15043009.94 | 0.167421E+09 | 0.222083E+09 | 0.157781E+09 |
| August | 0.152292E+09 | 3553362.43 | 0.148739E+09 | 0.178396E+09 | 0.168213E+09 |
| September | 0.124304E+09 | 43830.25 | 0.124260E+09 | 0.130730E+09 | 0.202099E+09 |
| October | 0.101863E+09 | 0.00 | 0.101863E+09 | 0.117219E+09 | 0.237050E+09 |
| November | 89254512.61 | 0.00 | 89254512.61 | 56449964.76 | 0.323446E+09 |
| December | 79153413.08 | 0.00 | 79153413.08 | 46543839.63 | 0.361975E+09 |
| Annual Sum or Average | 0.155644E+10 | 46971394.51 | 0.150947E+10 | 0.147720E+10 | 0.304112E+10 |
| Minimum of Months | 79153413.08 | 0.00 | 79153413.08 | 46543839.63 | 0.157781E+09 |
| Maximum of Months | 0.186449E+09 | 17985183.97 | 0.172733E+09 | 0.222083E+09 | 0.361975E+09 |
Report: WindowEnergyReportMonthly
For: GWINDOW1 N N2A
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 85027568.61 | 0.00 | 85027568.61 | 53232917.34 | 0.356400E+09 |
| February | 96403407.70 | 0.00 | 96403407.70 | 62705940.49 | 0.278918E+09 |
| March | 0.130807E+09 | 4105.79 | 0.130803E+09 | 0.103904E+09 | 0.311820E+09 |
| April | 0.146218E+09 | 871123.55 | 0.145347E+09 | 0.133050E+09 | 0.243206E+09 |
| May | 0.182204E+09 | 9470778.58 | 0.172733E+09 | 0.168596E+09 | 0.227367E+09 |
| June | 0.186449E+09 | 17985183.97 | 0.168464E+09 | 0.204187E+09 | 0.172213E+09 |
| July | 0.182464E+09 | 15043009.94 | 0.167421E+09 | 0.222083E+09 | 0.157709E+09 |
| August | 0.152292E+09 | 3553362.43 | 0.148739E+09 | 0.178366E+09 | 0.168155E+09 |
| September | 0.124304E+09 | 43830.25 | 0.124260E+09 | 0.130775E+09 | 0.201907E+09 |
| October | 0.101863E+09 | 0.00 | 0.101863E+09 | 0.117189E+09 | 0.236984E+09 |
| November | 89254512.61 | 0.00 | 89254512.61 | 56429430.10 | 0.323229E+09 |
| December | 79153413.08 | 0.00 | 79153413.08 | 46457554.71 | 0.361991E+09 |
| Annual Sum or Average | 0.155644E+10 | 46971394.51 | 0.150947E+10 | 0.147698E+10 | 0.303990E+10 |
| Minimum of Months | 79153413.08 | 0.00 | 79153413.08 | 46457554.71 | 0.157709E+09 |
| Maximum of Months | 0.186449E+09 | 17985183.97 | 0.172733E+09 | 0.222083E+09 | 0.361991E+09 |
Report: WindowEnergyReportMonthly
For: GWINDOW1 S S1A
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.558100E+09 | 0.408550E+09 | 0.149550E+09 | 0.821133E+09 | 0.362095E+09 |
| February | 0.407389E+09 | 0.254418E+09 | 0.152971E+09 | 0.565799E+09 | 0.296495E+09 |
| March | 0.348235E+09 | 0.166487E+09 | 0.181748E+09 | 0.481789E+09 | 0.328787E+09 |
| April | 0.296676E+09 | 0.120757E+09 | 0.175919E+09 | 0.439429E+09 | 0.267063E+09 |
| May | 0.207778E+09 | 24292585.19 | 0.183485E+09 | 0.244283E+09 | 0.251513E+09 |
| June | 0.177817E+09 | 10947826.02 | 0.166869E+09 | 0.211053E+09 | 0.188007E+09 |
| July | 0.194710E+09 | 22191625.47 | 0.172518E+09 | 0.272299E+09 | 0.169945E+09 |
| August | 0.248589E+09 | 77611251.15 | 0.170978E+09 | 0.400631E+09 | 0.178410E+09 |
| September | 0.331094E+09 | 0.165190E+09 | 0.165904E+09 | 0.533312E+09 | 0.205366E+09 |
| October | 0.449202E+09 | 0.302718E+09 | 0.146484E+09 | 0.727310E+09 | 0.232133E+09 |
| November | 0.523988E+09 | 0.371153E+09 | 0.152836E+09 | 0.767240E+09 | 0.325166E+09 |
| December | 0.599695E+09 | 0.456477E+09 | 0.143218E+09 | 0.886378E+09 | 0.366846E+09 |
| Annual Sum or Average | 0.434327E+10 | 0.238079E+10 | 0.196248E+10 | 0.635066E+10 | 0.317183E+10 |
| Minimum of Months | 0.177817E+09 | 10947826.02 | 0.143218E+09 | 0.211053E+09 | 0.169945E+09 |
| Maximum of Months | 0.599695E+09 | 0.456477E+09 | 0.183485E+09 | 0.886378E+09 | 0.366846E+09 |
Report: WindowEnergyReportMonthly
For: GWINDOW1 S S2A
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.558100E+09 | 0.408550E+09 | 0.149550E+09 | 0.820787E+09 | 0.362578E+09 |
| February | 0.407389E+09 | 0.254418E+09 | 0.152971E+09 | 0.564932E+09 | 0.297846E+09 |
| March | 0.348235E+09 | 0.166487E+09 | 0.181748E+09 | 0.480440E+09 | 0.330789E+09 |
| April | 0.296676E+09 | 0.120757E+09 | 0.175919E+09 | 0.438511E+09 | 0.268299E+09 |
| May | 0.207778E+09 | 24292585.19 | 0.183485E+09 | 0.243045E+09 | 0.253036E+09 |
| June | 0.177817E+09 | 10947826.02 | 0.166869E+09 | 0.210035E+09 | 0.189120E+09 |
| July | 0.194710E+09 | 22191625.47 | 0.172518E+09 | 0.271285E+09 | 0.170966E+09 |
| August | 0.248589E+09 | 77611251.15 | 0.170978E+09 | 0.399617E+09 | 0.179582E+09 |
| September | 0.331094E+09 | 0.165190E+09 | 0.165904E+09 | 0.532565E+09 | 0.206369E+09 |
| October | 0.449202E+09 | 0.302718E+09 | 0.146484E+09 | 0.726334E+09 | 0.233560E+09 |
| November | 0.523988E+09 | 0.371153E+09 | 0.152836E+09 | 0.766702E+09 | 0.325939E+09 |
| December | 0.599695E+09 | 0.456477E+09 | 0.143218E+09 | 0.885792E+09 | 0.367737E+09 |
| Annual Sum or Average | 0.434327E+10 | 0.238079E+10 | 0.196248E+10 | 0.634004E+10 | 0.318582E+10 |
| Minimum of Months | 0.177817E+09 | 10947826.02 | 0.143218E+09 | 0.210035E+09 | 0.170966E+09 |
| Maximum of Months | 0.599695E+09 | 0.456477E+09 | 0.183485E+09 | 0.885792E+09 | 0.367737E+09 |
Report: WindowEnergyReportMonthly
For: MWINDOW1 S SWA
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.558100E+09 | 0.408550E+09 | 0.149550E+09 | 0.815579E+09 | 0.364699E+09 |
| February | 0.407389E+09 | 0.254418E+09 | 0.152971E+09 | 0.556581E+09 | 0.305636E+09 |
| March | 0.348235E+09 | 0.166487E+09 | 0.181748E+09 | 0.466475E+09 | 0.349910E+09 |
| April | 0.296676E+09 | 0.120757E+09 | 0.175919E+09 | 0.426301E+09 | 0.284059E+09 |
| May | 0.207778E+09 | 24292585.19 | 0.183485E+09 | 0.230574E+09 | 0.268882E+09 |
| June | 0.177817E+09 | 10947826.02 | 0.166869E+09 | 0.200442E+09 | 0.199136E+09 |
| July | 0.194710E+09 | 22191625.47 | 0.172518E+09 | 0.264942E+09 | 0.175866E+09 |
| August | 0.248589E+09 | 77611251.15 | 0.170978E+09 | 0.393776E+09 | 0.183604E+09 |
| September | 0.331094E+09 | 0.165190E+09 | 0.165904E+09 | 0.527307E+09 | 0.209012E+09 |
| October | 0.449202E+09 | 0.302718E+09 | 0.146484E+09 | 0.722734E+09 | 0.232456E+09 |
| November | 0.523988E+09 | 0.371153E+09 | 0.152836E+09 | 0.762817E+09 | 0.324606E+09 |
| December | 0.599695E+09 | 0.456477E+09 | 0.143218E+09 | 0.881932E+09 | 0.366036E+09 |
| Annual Sum or Average | 0.434327E+10 | 0.238079E+10 | 0.196248E+10 | 0.624946E+10 | 0.326390E+10 |
| Minimum of Months | 0.177817E+09 | 10947826.02 | 0.143218E+09 | 0.200442E+09 | 0.175866E+09 |
| Maximum of Months | 0.599695E+09 | 0.456477E+09 | 0.183485E+09 | 0.881932E+09 | 0.366036E+09 |
Report: WindowEnergyReportMonthly
For: MWINDOW1 W SWA
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.143689E+09 | 72468237.92 | 71221005.30 | 0.168936E+09 | 0.259032E+09 |
| February | 0.154680E+09 | 71369157.64 | 83310528.17 | 0.175128E+09 | 0.210337E+09 |
| March | 0.196253E+09 | 86790430.64 | 0.109462E+09 | 0.231008E+09 | 0.230883E+09 |
| April | 0.261451E+09 | 0.135861E+09 | 0.125590E+09 | 0.354326E+09 | 0.180778E+09 |
| May | 0.265469E+09 | 0.122310E+09 | 0.143158E+09 | 0.349720E+09 | 0.167232E+09 |
| June | 0.272765E+09 | 0.136420E+09 | 0.136345E+09 | 0.384045E+09 | 0.123910E+09 |
| July | 0.298394E+09 | 0.159707E+09 | 0.138687E+09 | 0.448951E+09 | 0.109777E+09 |
| August | 0.279518E+09 | 0.151324E+09 | 0.128193E+09 | 0.424161E+09 | 0.116742E+09 |
| September | 0.231610E+09 | 0.123800E+09 | 0.107810E+09 | 0.336132E+09 | 0.134656E+09 |
| October | 0.183177E+09 | 0.100062E+09 | 83114403.80 | 0.271232E+09 | 0.158593E+09 |
| November | 0.159839E+09 | 83472084.97 | 76367302.03 | 0.195448E+09 | 0.227289E+09 |
| December | 0.145628E+09 | 77877952.25 | 67749887.84 | 0.175041E+09 | 0.262104E+09 |
| Annual Sum or Average | 0.259247E+10 | 0.132146E+10 | 0.127101E+10 | 0.351413E+10 | 0.218133E+10 |
| Minimum of Months | 0.143689E+09 | 71369157.64 | 67749887.84 | 0.168936E+09 | 0.109777E+09 |
| Maximum of Months | 0.298394E+09 | 0.159707E+09 | 0.143158E+09 | 0.448951E+09 | 0.262104E+09 |
Report: WindowEnergyReportMonthly
For: MWINDOW1 W NWA
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.143689E+09 | 72468237.92 | 71221005.30 | 0.182186E+09 | 0.235980E+09 |
| February | 0.154680E+09 | 71369157.64 | 83310528.17 | 0.185172E+09 | 0.194850E+09 |
| March | 0.196253E+09 | 86790430.64 | 0.109462E+09 | 0.240146E+09 | 0.219313E+09 |
| April | 0.261451E+09 | 0.135861E+09 | 0.125590E+09 | 0.358736E+09 | 0.176964E+09 |
| May | 0.265469E+09 | 0.122310E+09 | 0.143158E+09 | 0.350521E+09 | 0.167067E+09 |
| June | 0.272765E+09 | 0.136420E+09 | 0.136345E+09 | 0.384174E+09 | 0.124143E+09 |
| July | 0.298394E+09 | 0.159707E+09 | 0.138687E+09 | 0.449569E+09 | 0.109740E+09 |
| August | 0.279518E+09 | 0.151324E+09 | 0.128193E+09 | 0.426313E+09 | 0.115808E+09 |
| September | 0.231610E+09 | 0.123800E+09 | 0.107810E+09 | 0.339726E+09 | 0.132417E+09 |
| October | 0.183177E+09 | 0.100062E+09 | 83114403.80 | 0.276452E+09 | 0.153951E+09 |
| November | 0.159839E+09 | 83472084.97 | 76367302.03 | 0.205294E+09 | 0.212645E+09 |
| December | 0.145628E+09 | 77877952.25 | 67749887.84 | 0.187317E+09 | 0.239015E+09 |
| Annual Sum or Average | 0.259247E+10 | 0.132146E+10 | 0.127101E+10 | 0.358561E+10 | 0.208189E+10 |
| Minimum of Months | 0.143689E+09 | 71369157.64 | 67749887.84 | 0.182186E+09 | 0.109740E+09 |
| Maximum of Months | 0.298394E+09 | 0.159707E+09 | 0.143158E+09 | 0.449569E+09 | 0.239015E+09 |
Report: WindowEnergyReportMonthly
For: MWINDOW1 N NWA
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 85027568.61 | 0.00 | 85027568.61 | 48679420.81 | 0.370283E+09 |
| February | 96403407.70 | 0.00 | 96403407.70 | 52287800.76 | 0.307090E+09 |
| March | 0.130807E+09 | 4105.79 | 0.130803E+09 | 87870160.87 | 0.344207E+09 |
| April | 0.146218E+09 | 871123.55 | 0.145347E+09 | 0.113837E+09 | 0.273299E+09 |
| May | 0.182204E+09 | 9470778.58 | 0.172733E+09 | 0.150799E+09 | 0.244782E+09 |
| June | 0.186449E+09 | 17985183.97 | 0.168464E+09 | 0.191129E+09 | 0.181725E+09 |
| July | 0.182464E+09 | 15043009.94 | 0.167421E+09 | 0.213280E+09 | 0.162865E+09 |
| August | 0.152292E+09 | 3553362.43 | 0.148739E+09 | 0.171132E+09 | 0.173917E+09 |
| September | 0.124304E+09 | 43830.25 | 0.124260E+09 | 0.125294E+09 | 0.208417E+09 |
| October | 0.101863E+09 | 0.00 | 0.101863E+09 | 0.114583E+09 | 0.240509E+09 |
| November | 89254512.61 | 0.00 | 89254512.61 | 52124249.03 | 0.336162E+09 |
| December | 79153413.08 | 0.00 | 79153413.08 | 41904262.21 | 0.377215E+09 |
| Annual Sum or Average | 0.155644E+10 | 46971394.51 | 0.150947E+10 | 0.136292E+10 | 0.322047E+10 |
| Minimum of Months | 79153413.08 | 0.00 | 79153413.08 | 41904262.21 | 0.162865E+09 |
| Maximum of Months | 0.186449E+09 | 17985183.97 | 0.172733E+09 | 0.213280E+09 | 0.377215E+09 |
Report: WindowEnergyReportMonthly
For: MWINDOW1 S SEA
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.558100E+09 | 0.408550E+09 | 0.149550E+09 | 0.813456E+09 | 0.364607E+09 |
| February | 0.407389E+09 | 0.254418E+09 | 0.152971E+09 | 0.555531E+09 | 0.304164E+09 |
| March | 0.348235E+09 | 0.166487E+09 | 0.181748E+09 | 0.464425E+09 | 0.348637E+09 |
| April | 0.296676E+09 | 0.120757E+09 | 0.175919E+09 | 0.424471E+09 | 0.282546E+09 |
| May | 0.207778E+09 | 24292585.19 | 0.183485E+09 | 0.229172E+09 | 0.267150E+09 |
| June | 0.177817E+09 | 10947826.02 | 0.166869E+09 | 0.199673E+09 | 0.197347E+09 |
| July | 0.194710E+09 | 22191625.47 | 0.172518E+09 | 0.263797E+09 | 0.174099E+09 |
| August | 0.248589E+09 | 77611251.15 | 0.170978E+09 | 0.392481E+09 | 0.182140E+09 |
| September | 0.331094E+09 | 0.165190E+09 | 0.165904E+09 | 0.526889E+09 | 0.207320E+09 |
| October | 0.449202E+09 | 0.302718E+09 | 0.146484E+09 | 0.721860E+09 | 0.231422E+09 |
| November | 0.523988E+09 | 0.371153E+09 | 0.152836E+09 | 0.761741E+09 | 0.323441E+09 |
| December | 0.599695E+09 | 0.456477E+09 | 0.143218E+09 | 0.880362E+09 | 0.365162E+09 |
| Annual Sum or Average | 0.434327E+10 | 0.238079E+10 | 0.196248E+10 | 0.623386E+10 | 0.324804E+10 |
| Minimum of Months | 0.177817E+09 | 10947826.02 | 0.143218E+09 | 0.199673E+09 | 0.174099E+09 |
| Maximum of Months | 0.599695E+09 | 0.456477E+09 | 0.183485E+09 | 0.880362E+09 | 0.365162E+09 |
Report: WindowEnergyReportMonthly
For: MWINDOW1 E SEA
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.151566E+09 | 81345771.80 | 70219965.56 | 0.170703E+09 | 0.247472E+09 |
| February | 0.142885E+09 | 64974608.46 | 77910475.06 | 0.150624E+09 | 0.203639E+09 |
| March | 0.193935E+09 | 86505392.46 | 0.107430E+09 | 0.220507E+09 | 0.221463E+09 |
| April | 0.240203E+09 | 0.120907E+09 | 0.119296E+09 | 0.318193E+09 | 0.174683E+09 |
| May | 0.233159E+09 | 97178220.02 | 0.135981E+09 | 0.296325E+09 | 0.162525E+09 |
| June | 0.224485E+09 | 97471532.68 | 0.127013E+09 | 0.309291E+09 | 0.122995E+09 |
| July | 0.262868E+09 | 0.130731E+09 | 0.132136E+09 | 0.395959E+09 | 0.110362E+09 |
| August | 0.259391E+09 | 0.137743E+09 | 0.121648E+09 | 0.393592E+09 | 0.113777E+09 |
| September | 0.183233E+09 | 84190753.46 | 99042488.23 | 0.258439E+09 | 0.133096E+09 |
| October | 0.166464E+09 | 85183840.87 | 81280020.36 | 0.238652E+09 | 0.153120E+09 |
| November | 0.146903E+09 | 74325622.94 | 72577234.58 | 0.165406E+09 | 0.219565E+09 |
| December | 0.145791E+09 | 81141408.66 | 64649311.14 | 0.162535E+09 | 0.249932E+09 |
| Annual Sum or Average | 0.235088E+10 | 0.114170E+10 | 0.120918E+10 | 0.308022E+10 | 0.211263E+10 |
| Minimum of Months | 0.142885E+09 | 64974608.46 | 64649311.14 | 0.150624E+09 | 0.110362E+09 |
| Maximum of Months | 0.262868E+09 | 0.137743E+09 | 0.135981E+09 | 0.395959E+09 | 0.249932E+09 |
Report: WindowEnergyReportMonthly
For: MWINDOW1 E NEA
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.151566E+09 | 81345771.80 | 70219965.56 | 0.183482E+09 | 0.224373E+09 |
| February | 0.142885E+09 | 64974608.46 | 77910475.06 | 0.160352E+09 | 0.187427E+09 |
| March | 0.193935E+09 | 86505392.46 | 0.107430E+09 | 0.229193E+09 | 0.209611E+09 |
| April | 0.240203E+09 | 0.120907E+09 | 0.119296E+09 | 0.322319E+09 | 0.170748E+09 |
| May | 0.233159E+09 | 97178220.02 | 0.135981E+09 | 0.297093E+09 | 0.162253E+09 |
| June | 0.224485E+09 | 97471532.68 | 0.127013E+09 | 0.309484E+09 | 0.123256E+09 |
| July | 0.262868E+09 | 0.130731E+09 | 0.132136E+09 | 0.396594E+09 | 0.110331E+09 |
| August | 0.259391E+09 | 0.137743E+09 | 0.121648E+09 | 0.395630E+09 | 0.112782E+09 |
| September | 0.183233E+09 | 84190753.46 | 99042488.23 | 0.261820E+09 | 0.130605E+09 |
| October | 0.166464E+09 | 85183840.87 | 81280020.36 | 0.243649E+09 | 0.148392E+09 |
| November | 0.146903E+09 | 74325622.94 | 72577234.58 | 0.175274E+09 | 0.204048E+09 |
| December | 0.145791E+09 | 81141408.66 | 64649311.14 | 0.175195E+09 | 0.226949E+09 |
| Annual Sum or Average | 0.235088E+10 | 0.114170E+10 | 0.120918E+10 | 0.315008E+10 | 0.201078E+10 |
| Minimum of Months | 0.142885E+09 | 64974608.46 | 64649311.14 | 0.160352E+09 | 0.110331E+09 |
| Maximum of Months | 0.262868E+09 | 0.137743E+09 | 0.135981E+09 | 0.396594E+09 | 0.226949E+09 |
Report: WindowEnergyReportMonthly
For: MWINDOW1 N NEA
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 85027568.61 | 0.00 | 85027568.61 | 46426035.10 | 0.370667E+09 |
| February | 96403407.70 | 0.00 | 96403407.70 | 50823184.48 | 0.304650E+09 |
| March | 0.130807E+09 | 4105.79 | 0.130803E+09 | 85504584.61 | 0.342683E+09 |
| April | 0.146218E+09 | 871123.55 | 0.145347E+09 | 0.111642E+09 | 0.271668E+09 |
| May | 0.182204E+09 | 9470778.58 | 0.172733E+09 | 0.149562E+09 | 0.243140E+09 |
| June | 0.186449E+09 | 17985183.97 | 0.168464E+09 | 0.190712E+09 | 0.180276E+09 |
| July | 0.182464E+09 | 15043009.94 | 0.167421E+09 | 0.212420E+09 | 0.161407E+09 |
| August | 0.152292E+09 | 3553362.43 | 0.148739E+09 | 0.169903E+09 | 0.172566E+09 |
| September | 0.124304E+09 | 43830.25 | 0.124260E+09 | 0.124755E+09 | 0.206508E+09 |
| October | 0.101863E+09 | 0.00 | 0.101863E+09 | 0.113426E+09 | 0.239519E+09 |
| November | 89254512.61 | 0.00 | 89254512.61 | 50648462.51 | 0.333569E+09 |
| December | 79153413.08 | 0.00 | 79153413.08 | 40134472.20 | 0.376197E+09 |
| Annual Sum or Average | 0.155644E+10 | 46971394.51 | 0.150947E+10 | 0.134596E+10 | 0.320285E+10 |
| Minimum of Months | 79153413.08 | 0.00 | 79153413.08 | 40134472.20 | 0.161407E+09 |
| Maximum of Months | 0.186449E+09 | 17985183.97 | 0.172733E+09 | 0.212420E+09 | 0.376197E+09 |
Report: WindowEnergyReportMonthly
For: MWINDOW1 N N1A
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 85027568.61 | 0.00 | 85027568.61 | 45687495.91 | 0.382333E+09 |
| February | 96403407.70 | 0.00 | 96403407.70 | 48187420.67 | 0.321961E+09 |
| March | 0.130807E+09 | 4105.79 | 0.130803E+09 | 84009794.47 | 0.356834E+09 |
| April | 0.146218E+09 | 871123.55 | 0.145347E+09 | 0.113496E+09 | 0.276956E+09 |
| May | 0.182204E+09 | 9470778.58 | 0.172733E+09 | 0.150617E+09 | 0.247860E+09 |
| June | 0.186449E+09 | 17985183.97 | 0.168464E+09 | 0.193315E+09 | 0.181748E+09 |
| July | 0.182464E+09 | 15043009.94 | 0.167421E+09 | 0.216662E+09 | 0.161778E+09 |
| August | 0.152292E+09 | 3553362.43 | 0.148739E+09 | 0.174032E+09 | 0.172825E+09 |
| September | 0.124304E+09 | 43830.25 | 0.124260E+09 | 0.126684E+09 | 0.208275E+09 |
| October | 0.101863E+09 | 0.00 | 0.101863E+09 | 0.114645E+09 | 0.243149E+09 |
| November | 89254512.61 | 0.00 | 89254512.61 | 48915423.15 | 0.347946E+09 |
| December | 79153413.08 | 0.00 | 79153413.08 | 38455888.82 | 0.393155E+09 |
| Annual Sum or Average | 0.155644E+10 | 46971394.51 | 0.150947E+10 | 0.135471E+10 | 0.329482E+10 |
| Minimum of Months | 79153413.08 | 0.00 | 79153413.08 | 38455888.82 | 0.161778E+09 |
| Maximum of Months | 0.186449E+09 | 17985183.97 | 0.172733E+09 | 0.216662E+09 | 0.393155E+09 |
Report: WindowEnergyReportMonthly
For: MWINDOW1 N N2A
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 85027568.61 | 0.00 | 85027568.61 | 45529360.97 | 0.382592E+09 |
| February | 96403407.70 | 0.00 | 96403407.70 | 48136076.25 | 0.321797E+09 |
| March | 0.130807E+09 | 4105.79 | 0.130803E+09 | 83902678.18 | 0.356745E+09 |
| April | 0.146218E+09 | 871123.55 | 0.145347E+09 | 0.113389E+09 | 0.276927E+09 |
| May | 0.182204E+09 | 9470778.58 | 0.172733E+09 | 0.150572E+09 | 0.247793E+09 |
| June | 0.186449E+09 | 17985183.97 | 0.168464E+09 | 0.193306E+09 | 0.181691E+09 |
| July | 0.182464E+09 | 15043009.94 | 0.167421E+09 | 0.216636E+09 | 0.161726E+09 |
| August | 0.152292E+09 | 3553362.43 | 0.148739E+09 | 0.173992E+09 | 0.172777E+09 |
| September | 0.124304E+09 | 43830.25 | 0.124260E+09 | 0.126674E+09 | 0.208190E+09 |
| October | 0.101863E+09 | 0.00 | 0.101863E+09 | 0.114598E+09 | 0.243115E+09 |
| November | 89254512.61 | 0.00 | 89254512.61 | 48863708.12 | 0.347781E+09 |
| December | 79153413.08 | 0.00 | 79153413.08 | 38368043.86 | 0.393155E+09 |
| Annual Sum or Average | 0.155644E+10 | 46971394.51 | 0.150947E+10 | 0.135397E+10 | 0.329429E+10 |
| Minimum of Months | 79153413.08 | 0.00 | 79153413.08 | 38368043.86 | 0.161726E+09 |
| Maximum of Months | 0.186449E+09 | 17985183.97 | 0.172733E+09 | 0.216636E+09 | 0.393155E+09 |
Report: WindowEnergyReportMonthly
For: MWINDOW1 S S1A
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.558100E+09 | 0.408550E+09 | 0.149550E+09 | 0.810746E+09 | 0.375707E+09 |
| February | 0.407389E+09 | 0.254418E+09 | 0.152971E+09 | 0.552183E+09 | 0.317055E+09 |
| March | 0.348235E+09 | 0.166487E+09 | 0.181748E+09 | 0.461699E+09 | 0.362515E+09 |
| April | 0.296676E+09 | 0.120757E+09 | 0.175919E+09 | 0.425878E+09 | 0.287403E+09 |
| May | 0.207778E+09 | 24292585.19 | 0.183485E+09 | 0.230277E+09 | 0.271997E+09 |
| June | 0.177817E+09 | 10947826.02 | 0.166869E+09 | 0.202092E+09 | 0.198757E+09 |
| July | 0.194710E+09 | 22191625.47 | 0.172518E+09 | 0.267640E+09 | 0.174296E+09 |
| August | 0.248589E+09 | 77611251.15 | 0.170978E+09 | 0.396138E+09 | 0.182377E+09 |
| September | 0.331094E+09 | 0.165190E+09 | 0.165904E+09 | 0.528573E+09 | 0.208972E+09 |
| October | 0.449202E+09 | 0.302718E+09 | 0.146484E+09 | 0.722820E+09 | 0.234349E+09 |
| November | 0.523988E+09 | 0.371153E+09 | 0.152836E+09 | 0.760266E+09 | 0.330964E+09 |
| December | 0.599695E+09 | 0.456477E+09 | 0.143218E+09 | 0.877747E+09 | 0.375462E+09 |
| Annual Sum or Average | 0.434327E+10 | 0.238079E+10 | 0.196248E+10 | 0.623606E+10 | 0.331985E+10 |
| Minimum of Months | 0.177817E+09 | 10947826.02 | 0.143218E+09 | 0.202092E+09 | 0.174296E+09 |
| Maximum of Months | 0.599695E+09 | 0.456477E+09 | 0.183485E+09 | 0.877747E+09 | 0.375707E+09 |
Report: WindowEnergyReportMonthly
For: MWINDOW1 S S2A
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.558100E+09 | 0.408550E+09 | 0.149550E+09 | 0.810638E+09 | 0.375810E+09 |
| February | 0.407389E+09 | 0.254418E+09 | 0.152971E+09 | 0.552165E+09 | 0.316968E+09 |
| March | 0.348235E+09 | 0.166487E+09 | 0.181748E+09 | 0.461637E+09 | 0.362463E+09 |
| April | 0.296676E+09 | 0.120757E+09 | 0.175919E+09 | 0.425809E+09 | 0.287362E+09 |
| May | 0.207778E+09 | 24292585.19 | 0.183485E+09 | 0.230225E+09 | 0.271926E+09 |
| June | 0.177817E+09 | 10947826.02 | 0.166869E+09 | 0.202072E+09 | 0.198689E+09 |
| July | 0.194710E+09 | 22191625.47 | 0.172518E+09 | 0.267607E+09 | 0.174234E+09 |
| August | 0.248589E+09 | 77611251.15 | 0.170978E+09 | 0.396097E+09 | 0.182327E+09 |
| September | 0.331094E+09 | 0.165190E+09 | 0.165904E+09 | 0.528564E+09 | 0.208906E+09 |
| October | 0.449202E+09 | 0.302718E+09 | 0.146484E+09 | 0.722795E+09 | 0.234313E+09 |
| November | 0.523988E+09 | 0.371153E+09 | 0.152836E+09 | 0.760242E+09 | 0.330918E+09 |
| December | 0.599695E+09 | 0.456477E+09 | 0.143218E+09 | 0.877706E+09 | 0.375437E+09 |
| Annual Sum or Average | 0.434327E+10 | 0.238079E+10 | 0.196248E+10 | 0.623556E+10 | 0.331935E+10 |
| Minimum of Months | 0.177817E+09 | 10947826.02 | 0.143218E+09 | 0.202072E+09 | 0.174234E+09 |
| Maximum of Months | 0.599695E+09 | 0.456477E+09 | 0.183485E+09 | 0.877706E+09 | 0.375810E+09 |
Report: WindowEnergyReportMonthly
For: TWINDOW1 S SWA
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.558100E+09 | 0.408550E+09 | 0.149550E+09 | 0.824390E+09 | 0.325056E+09 |
| February | 0.407389E+09 | 0.254418E+09 | 0.152971E+09 | 0.567406E+09 | 0.263675E+09 |
| March | 0.348235E+09 | 0.166487E+09 | 0.181748E+09 | 0.476381E+09 | 0.308346E+09 |
| April | 0.296676E+09 | 0.120757E+09 | 0.175919E+09 | 0.430478E+09 | 0.252181E+09 |
| May | 0.207778E+09 | 24292585.19 | 0.183485E+09 | 0.237971E+09 | 0.236704E+09 |
| June | 0.177817E+09 | 10947826.02 | 0.166869E+09 | 0.200137E+09 | 0.183267E+09 |
| July | 0.194710E+09 | 22191625.47 | 0.172518E+09 | 0.258460E+09 | 0.167400E+09 |
| August | 0.248589E+09 | 77611251.15 | 0.170978E+09 | 0.386825E+09 | 0.174224E+09 |
| September | 0.331094E+09 | 0.165190E+09 | 0.165904E+09 | 0.524072E+09 | 0.193481E+09 |
| October | 0.449202E+09 | 0.302718E+09 | 0.146484E+09 | 0.723395E+09 | 0.211281E+09 |
| November | 0.523988E+09 | 0.371153E+09 | 0.152836E+09 | 0.773319E+09 | 0.284256E+09 |
| December | 0.599695E+09 | 0.456477E+09 | 0.143218E+09 | 0.892474E+09 | 0.322297E+09 |
| Annual Sum or Average | 0.434327E+10 | 0.238079E+10 | 0.196248E+10 | 0.629531E+10 | 0.292217E+10 |
| Minimum of Months | 0.177817E+09 | 10947826.02 | 0.143218E+09 | 0.200137E+09 | 0.167400E+09 |
| Maximum of Months | 0.599695E+09 | 0.456477E+09 | 0.183485E+09 | 0.892474E+09 | 0.325056E+09 |
Report: WindowEnergyReportMonthly
For: TWINDOW1 W SWA
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.143689E+09 | 72468237.92 | 71221005.30 | 0.169266E+09 | 0.228068E+09 |
| February | 0.154680E+09 | 71369157.64 | 83310528.17 | 0.178748E+09 | 0.179482E+09 |
| March | 0.196253E+09 | 86790430.64 | 0.109462E+09 | 0.235066E+09 | 0.201554E+09 |
| April | 0.261451E+09 | 0.135861E+09 | 0.125590E+09 | 0.355529E+09 | 0.159041E+09 |
| May | 0.265469E+09 | 0.122310E+09 | 0.143158E+09 | 0.353703E+09 | 0.145952E+09 |
| June | 0.272765E+09 | 0.136420E+09 | 0.136345E+09 | 0.382231E+09 | 0.112844E+09 |
| July | 0.298394E+09 | 0.159707E+09 | 0.138687E+09 | 0.442892E+09 | 0.103417E+09 |
| August | 0.279518E+09 | 0.151324E+09 | 0.128193E+09 | 0.417980E+09 | 0.109842E+09 |
| September | 0.231610E+09 | 0.123800E+09 | 0.107810E+09 | 0.332581E+09 | 0.123597E+09 |
| October | 0.183177E+09 | 0.100062E+09 | 83114403.80 | 0.269219E+09 | 0.142580E+09 |
| November | 0.159839E+09 | 83472084.97 | 76367302.03 | 0.197308E+09 | 0.196040E+09 |
| December | 0.145628E+09 | 77877952.25 | 67749887.84 | 0.175746E+09 | 0.227406E+09 |
| Annual Sum or Average | 0.259247E+10 | 0.132146E+10 | 0.127101E+10 | 0.351027E+10 | 0.192982E+10 |
| Minimum of Months | 0.143689E+09 | 71369157.64 | 67749887.84 | 0.169266E+09 | 0.103417E+09 |
| Maximum of Months | 0.298394E+09 | 0.159707E+09 | 0.143158E+09 | 0.442892E+09 | 0.228068E+09 |
Report: WindowEnergyReportMonthly
For: TWINDOW1 W NWA
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.143689E+09 | 72468237.92 | 71221005.30 | 0.186936E+09 | 0.211314E+09 |
| February | 0.154680E+09 | 71369157.64 | 83310528.17 | 0.191636E+09 | 0.169339E+09 |
| March | 0.196253E+09 | 86790430.64 | 0.109462E+09 | 0.245255E+09 | 0.194824E+09 |
| April | 0.261451E+09 | 0.135861E+09 | 0.125590E+09 | 0.362594E+09 | 0.154839E+09 |
| May | 0.265469E+09 | 0.122310E+09 | 0.143158E+09 | 0.354985E+09 | 0.146021E+09 |
| June | 0.272765E+09 | 0.136420E+09 | 0.136345E+09 | 0.382214E+09 | 0.113460E+09 |
| July | 0.298394E+09 | 0.159707E+09 | 0.138687E+09 | 0.443787E+09 | 0.103601E+09 |
| August | 0.279518E+09 | 0.151324E+09 | 0.128193E+09 | 0.421394E+09 | 0.108701E+09 |
| September | 0.231610E+09 | 0.123800E+09 | 0.107810E+09 | 0.338784E+09 | 0.120236E+09 |
| October | 0.183177E+09 | 0.100062E+09 | 83114403.80 | 0.278442E+09 | 0.136564E+09 |
| November | 0.159839E+09 | 83472084.97 | 76367302.03 | 0.213632E+09 | 0.180968E+09 |
| December | 0.145628E+09 | 77877952.25 | 67749887.84 | 0.193338E+09 | 0.209958E+09 |
| Annual Sum or Average | 0.259247E+10 | 0.132146E+10 | 0.127101E+10 | 0.361300E+10 | 0.184983E+10 |
| Minimum of Months | 0.143689E+09 | 71369157.64 | 67749887.84 | 0.186936E+09 | 0.103601E+09 |
| Maximum of Months | 0.298394E+09 | 0.159707E+09 | 0.143158E+09 | 0.443787E+09 | 0.211314E+09 |
Report: WindowEnergyReportMonthly
For: TWINDOW1 N NWA
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 85027568.61 | 0.00 | 85027568.61 | 56182559.17 | 0.332714E+09 |
| February | 96403407.70 | 0.00 | 96403407.70 | 61941997.80 | 0.267779E+09 |
| March | 0.130807E+09 | 4105.79 | 0.130803E+09 | 96644367.21 | 0.307454E+09 |
| April | 0.146218E+09 | 871123.55 | 0.145347E+09 | 0.121102E+09 | 0.240139E+09 |
| May | 0.182204E+09 | 9470778.58 | 0.172733E+09 | 0.161555E+09 | 0.215747E+09 |
| June | 0.186449E+09 | 17985183.97 | 0.168464E+09 | 0.191210E+09 | 0.167537E+09 |
| July | 0.182464E+09 | 15043009.94 | 0.167421E+09 | 0.206834E+09 | 0.154839E+09 |
| August | 0.152292E+09 | 3553362.43 | 0.148739E+09 | 0.165995E+09 | 0.164321E+09 |
| September | 0.124304E+09 | 43830.25 | 0.124260E+09 | 0.125676E+09 | 0.190727E+09 |
| October | 0.101863E+09 | 0.00 | 0.101863E+09 | 0.118914E+09 | 0.214430E+09 |
| November | 89254512.61 | 0.00 | 89254512.61 | 64134336.67 | 0.286981E+09 |
| December | 79153413.08 | 0.00 | 79153413.08 | 50551420.88 | 0.332051E+09 |
| Annual Sum or Average | 0.155644E+10 | 46971394.51 | 0.150947E+10 | 0.142074E+10 | 0.287472E+10 |
| Minimum of Months | 79153413.08 | 0.00 | 79153413.08 | 50551420.88 | 0.154839E+09 |
| Maximum of Months | 0.186449E+09 | 17985183.97 | 0.172733E+09 | 0.206834E+09 | 0.332714E+09 |
Report: WindowEnergyReportMonthly
For: TWINDOW1 S SEA
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.558100E+09 | 0.408550E+09 | 0.149550E+09 | 0.820137E+09 | 0.323465E+09 |
| February | 0.407389E+09 | 0.254418E+09 | 0.152971E+09 | 0.564326E+09 | 0.261236E+09 |
| March | 0.348235E+09 | 0.166487E+09 | 0.181748E+09 | 0.471988E+09 | 0.305729E+09 |
| April | 0.296676E+09 | 0.120757E+09 | 0.175919E+09 | 0.425409E+09 | 0.248227E+09 |
| May | 0.207778E+09 | 24292585.19 | 0.183485E+09 | 0.233643E+09 | 0.232376E+09 |
| June | 0.177817E+09 | 10947826.02 | 0.166869E+09 | 0.197675E+09 | 0.179132E+09 |
| July | 0.194710E+09 | 22191625.47 | 0.172518E+09 | 0.255839E+09 | 0.163710E+09 |
| August | 0.248589E+09 | 77611251.15 | 0.170978E+09 | 0.383926E+09 | 0.171127E+09 |
| September | 0.331094E+09 | 0.165190E+09 | 0.165904E+09 | 0.522560E+09 | 0.190065E+09 |
| October | 0.449202E+09 | 0.302718E+09 | 0.146484E+09 | 0.720940E+09 | 0.209199E+09 |
| November | 0.523988E+09 | 0.371153E+09 | 0.152836E+09 | 0.770004E+09 | 0.281565E+09 |
| December | 0.599695E+09 | 0.456477E+09 | 0.143218E+09 | 0.888785E+09 | 0.320192E+09 |
| Annual Sum or Average | 0.434327E+10 | 0.238079E+10 | 0.196248E+10 | 0.625523E+10 | 0.288602E+10 |
| Minimum of Months | 0.177817E+09 | 10947826.02 | 0.143218E+09 | 0.197675E+09 | 0.163710E+09 |
| Maximum of Months | 0.599695E+09 | 0.456477E+09 | 0.183485E+09 | 0.888785E+09 | 0.323465E+09 |
Report: WindowEnergyReportMonthly
For: TWINDOW1 E SEA
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.151566E+09 | 81345771.80 | 70219965.56 | 0.176565E+09 | 0.221452E+09 |
| February | 0.142885E+09 | 64974608.46 | 77910475.06 | 0.157703E+09 | 0.176056E+09 |
| March | 0.193935E+09 | 86505392.46 | 0.107430E+09 | 0.228055E+09 | 0.195499E+09 |
| April | 0.240203E+09 | 0.120907E+09 | 0.119296E+09 | 0.321872E+09 | 0.154865E+09 |
| May | 0.233159E+09 | 97178220.02 | 0.135981E+09 | 0.302951E+09 | 0.143051E+09 |
| June | 0.224485E+09 | 97471532.68 | 0.127013E+09 | 0.309660E+09 | 0.112587E+09 |
| July | 0.262868E+09 | 0.130731E+09 | 0.132136E+09 | 0.391420E+09 | 0.104177E+09 |
| August | 0.259391E+09 | 0.137743E+09 | 0.121648E+09 | 0.388973E+09 | 0.107473E+09 |
| September | 0.183233E+09 | 84190753.46 | 99042488.23 | 0.256797E+09 | 0.122612E+09 |
| October | 0.166464E+09 | 85183840.87 | 81280020.36 | 0.239527E+09 | 0.139477E+09 |
| November | 0.146903E+09 | 74325622.94 | 72577234.58 | 0.172360E+09 | 0.192887E+09 |
| December | 0.145791E+09 | 81141408.66 | 64649311.14 | 0.169301E+09 | 0.220858E+09 |
| Annual Sum or Average | 0.235088E+10 | 0.114170E+10 | 0.120918E+10 | 0.311518E+10 | 0.189100E+10 |
| Minimum of Months | 0.142885E+09 | 64974608.46 | 64649311.14 | 0.157703E+09 | 0.104177E+09 |
| Maximum of Months | 0.262868E+09 | 0.137743E+09 | 0.135981E+09 | 0.391420E+09 | 0.221452E+09 |
Report: WindowEnergyReportMonthly
For: TWINDOW1 E NEA
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.151566E+09 | 81345771.80 | 70219965.56 | 0.191007E+09 | 0.200993E+09 |
| February | 0.142885E+09 | 64974608.46 | 77910475.06 | 0.168627E+09 | 0.163129E+09 |
| March | 0.193935E+09 | 86505392.46 | 0.107430E+09 | 0.236598E+09 | 0.187046E+09 |
| April | 0.240203E+09 | 0.120907E+09 | 0.119296E+09 | 0.328175E+09 | 0.149676E+09 |
| May | 0.233159E+09 | 97178220.02 | 0.135981E+09 | 0.304103E+09 | 0.143019E+09 |
| June | 0.224485E+09 | 97471532.68 | 0.127013E+09 | 0.309765E+09 | 0.113389E+09 |
| July | 0.262868E+09 | 0.130731E+09 | 0.132136E+09 | 0.392407E+09 | 0.104393E+09 |
| August | 0.259391E+09 | 0.137743E+09 | 0.121648E+09 | 0.392187E+09 | 0.106120E+09 |
| September | 0.183233E+09 | 84190753.46 | 99042488.23 | 0.262487E+09 | 0.118421E+09 |
| October | 0.166464E+09 | 85183840.87 | 81280020.36 | 0.247796E+09 | 0.132265E+09 |
| November | 0.146903E+09 | 74325622.94 | 72577234.58 | 0.186265E+09 | 0.174134E+09 |
| December | 0.145791E+09 | 81141408.66 | 64649311.14 | 0.184079E+09 | 0.199732E+09 |
| Annual Sum or Average | 0.235088E+10 | 0.114170E+10 | 0.120918E+10 | 0.320350E+10 | 0.179232E+10 |
| Minimum of Months | 0.142885E+09 | 64974608.46 | 64649311.14 | 0.168627E+09 | 0.104393E+09 |
| Maximum of Months | 0.262868E+09 | 0.137743E+09 | 0.135981E+09 | 0.392407E+09 | 0.200993E+09 |
Report: WindowEnergyReportMonthly
For: TWINDOW1 N NEA
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 85027568.61 | 0.00 | 85027568.61 | 52341709.60 | 0.330182E+09 |
| February | 96403407.70 | 0.00 | 96403407.70 | 58678749.18 | 0.263533E+09 |
| March | 0.130807E+09 | 4105.79 | 0.130803E+09 | 91889680.00 | 0.303987E+09 |
| April | 0.146218E+09 | 871123.55 | 0.145347E+09 | 0.115509E+09 | 0.235162E+09 |
| May | 0.182204E+09 | 9470778.58 | 0.172733E+09 | 0.157652E+09 | 0.211900E+09 |
| June | 0.186449E+09 | 17985183.97 | 0.168464E+09 | 0.189514E+09 | 0.164343E+09 |
| July | 0.182464E+09 | 15043009.94 | 0.167421E+09 | 0.204896E+09 | 0.151826E+09 |
| August | 0.152292E+09 | 3553362.43 | 0.148739E+09 | 0.163147E+09 | 0.161238E+09 |
| September | 0.124304E+09 | 43830.25 | 0.124260E+09 | 0.123692E+09 | 0.186292E+09 |
| October | 0.101863E+09 | 0.00 | 0.101863E+09 | 0.115620E+09 | 0.211283E+09 |
| November | 89254512.61 | 0.00 | 89254512.61 | 60655116.45 | 0.281993E+09 |
| December | 79153413.08 | 0.00 | 79153413.08 | 47074142.18 | 0.328663E+09 |
| Annual Sum or Average | 0.155644E+10 | 46971394.51 | 0.150947E+10 | 0.138067E+10 | 0.283040E+10 |
| Minimum of Months | 79153413.08 | 0.00 | 79153413.08 | 47074142.18 | 0.151826E+09 |
| Maximum of Months | 0.186449E+09 | 17985183.97 | 0.172733E+09 | 0.204896E+09 | 0.330182E+09 |
Report: WindowEnergyReportMonthly
For: TWINDOW1 N N1A
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 85027568.61 | 0.00 | 85027568.61 | 55348930.88 | 0.337683E+09 |
| February | 96403407.70 | 0.00 | 96403407.70 | 61616093.74 | 0.270608E+09 |
| March | 0.130807E+09 | 4105.79 | 0.130803E+09 | 96484621.73 | 0.311449E+09 |
| April | 0.146218E+09 | 871123.55 | 0.145347E+09 | 0.121933E+09 | 0.243833E+09 |
| May | 0.182204E+09 | 9470778.58 | 0.172733E+09 | 0.161962E+09 | 0.220956E+09 |
| June | 0.186449E+09 | 17985183.97 | 0.168464E+09 | 0.193069E+09 | 0.170692E+09 |
| July | 0.182464E+09 | 15043009.94 | 0.167421E+09 | 0.210802E+09 | 0.155781E+09 |
| August | 0.152292E+09 | 3553362.43 | 0.148739E+09 | 0.169238E+09 | 0.165805E+09 |
| September | 0.124304E+09 | 43830.25 | 0.124260E+09 | 0.126927E+09 | 0.193660E+09 |
| October | 0.101863E+09 | 0.00 | 0.101863E+09 | 0.119347E+09 | 0.218557E+09 |
| November | 89254512.61 | 0.00 | 89254512.61 | 63644980.52 | 0.290619E+09 |
| December | 79153413.08 | 0.00 | 79153413.08 | 50043458.07 | 0.336482E+09 |
| Annual Sum or Average | 0.155644E+10 | 46971394.51 | 0.150947E+10 | 0.143042E+10 | 0.291613E+10 |
| Minimum of Months | 79153413.08 | 0.00 | 79153413.08 | 50043458.07 | 0.155781E+09 |
| Maximum of Months | 0.186449E+09 | 17985183.97 | 0.172733E+09 | 0.210802E+09 | 0.337683E+09 |
Report: WindowEnergyReportMonthly
For: TWINDOW1 N N2A
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 85027568.61 | 0.00 | 85027568.61 | 55044197.25 | 0.337580E+09 |
| February | 96403407.70 | 0.00 | 96403407.70 | 61361411.95 | 0.270282E+09 |
| March | 0.130807E+09 | 4105.79 | 0.130803E+09 | 96084225.87 | 0.311253E+09 |
| April | 0.146218E+09 | 871123.55 | 0.145347E+09 | 0.121539E+09 | 0.243418E+09 |
| May | 0.182204E+09 | 9470778.58 | 0.172733E+09 | 0.161693E+09 | 0.220621E+09 |
| June | 0.186449E+09 | 17985183.97 | 0.168464E+09 | 0.193000E+09 | 0.170437E+09 |
| July | 0.182464E+09 | 15043009.94 | 0.167421E+09 | 0.210727E+09 | 0.155580E+09 |
| August | 0.152292E+09 | 3553362.43 | 0.148739E+09 | 0.169107E+09 | 0.165596E+09 |
| September | 0.124304E+09 | 43830.25 | 0.124260E+09 | 0.126854E+09 | 0.193262E+09 |
| October | 0.101863E+09 | 0.00 | 0.101863E+09 | 0.119123E+09 | 0.218307E+09 |
| November | 89254512.61 | 0.00 | 89254512.61 | 63377713.48 | 0.290191E+09 |
| December | 79153413.08 | 0.00 | 79153413.08 | 49766900.70 | 0.336255E+09 |
| Annual Sum or Average | 0.155644E+10 | 46971394.51 | 0.150947E+10 | 0.142768E+10 | 0.291278E+10 |
| Minimum of Months | 79153413.08 | 0.00 | 79153413.08 | 49766900.70 | 0.155580E+09 |
| Maximum of Months | 0.186449E+09 | 17985183.97 | 0.172733E+09 | 0.210727E+09 | 0.337580E+09 |
Report: WindowEnergyReportMonthly
For: TWINDOW1 S S1A
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.558100E+09 | 0.408550E+09 | 0.149550E+09 | 0.820785E+09 | 0.335325E+09 |
| February | 0.407389E+09 | 0.254418E+09 | 0.152971E+09 | 0.564887E+09 | 0.272000E+09 |
| March | 0.348235E+09 | 0.166487E+09 | 0.181748E+09 | 0.474285E+09 | 0.316689E+09 |
| April | 0.296676E+09 | 0.120757E+09 | 0.175919E+09 | 0.430019E+09 | 0.257883E+09 |
| May | 0.207778E+09 | 24292585.19 | 0.183485E+09 | 0.237824E+09 | 0.241874E+09 |
| June | 0.177817E+09 | 10947826.02 | 0.166869E+09 | 0.201384E+09 | 0.185855E+09 |
| July | 0.194710E+09 | 22191625.47 | 0.172518E+09 | 0.261494E+09 | 0.167689E+09 |
| August | 0.248589E+09 | 77611251.15 | 0.170978E+09 | 0.389399E+09 | 0.175455E+09 |
| September | 0.331094E+09 | 0.165190E+09 | 0.165904E+09 | 0.524951E+09 | 0.196818E+09 |
| October | 0.449202E+09 | 0.302718E+09 | 0.146484E+09 | 0.722932E+09 | 0.216866E+09 |
| November | 0.523988E+09 | 0.371153E+09 | 0.152836E+09 | 0.770213E+09 | 0.293812E+09 |
| December | 0.599695E+09 | 0.456477E+09 | 0.143218E+09 | 0.888986E+09 | 0.332664E+09 |
| Annual Sum or Average | 0.434327E+10 | 0.238079E+10 | 0.196248E+10 | 0.628716E+10 | 0.299293E+10 |
| Minimum of Months | 0.177817E+09 | 10947826.02 | 0.143218E+09 | 0.201384E+09 | 0.167689E+09 |
| Maximum of Months | 0.599695E+09 | 0.456477E+09 | 0.183485E+09 | 0.888986E+09 | 0.335325E+09 |
Report: WindowEnergyReportMonthly
For: TWINDOW1 S S2A
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.558100E+09 | 0.408550E+09 | 0.149550E+09 | 0.820533E+09 | 0.335262E+09 |
| February | 0.407389E+09 | 0.254418E+09 | 0.152971E+09 | 0.564694E+09 | 0.271804E+09 |
| March | 0.348235E+09 | 0.166487E+09 | 0.181748E+09 | 0.473986E+09 | 0.316508E+09 |
| April | 0.296676E+09 | 0.120757E+09 | 0.175919E+09 | 0.429718E+09 | 0.257584E+09 |
| May | 0.207778E+09 | 24292585.19 | 0.183485E+09 | 0.237550E+09 | 0.241501E+09 |
| June | 0.177817E+09 | 10947826.02 | 0.166869E+09 | 0.201279E+09 | 0.185530E+09 |
| July | 0.194710E+09 | 22191625.47 | 0.172518E+09 | 0.261386E+09 | 0.167451E+09 |
| August | 0.248589E+09 | 77611251.15 | 0.170978E+09 | 0.389267E+09 | 0.175260E+09 |
| September | 0.331094E+09 | 0.165190E+09 | 0.165904E+09 | 0.524899E+09 | 0.196561E+09 |
| October | 0.449202E+09 | 0.302718E+09 | 0.146484E+09 | 0.722808E+09 | 0.216725E+09 |
| November | 0.523988E+09 | 0.371153E+09 | 0.152836E+09 | 0.770021E+09 | 0.293608E+09 |
| December | 0.599695E+09 | 0.456477E+09 | 0.143218E+09 | 0.888784E+09 | 0.332522E+09 |
| Annual Sum or Average | 0.434327E+10 | 0.238079E+10 | 0.196248E+10 | 0.628492E+10 | 0.299032E+10 |
| Minimum of Months | 0.177817E+09 | 10947826.02 | 0.143218E+09 | 0.201279E+09 | 0.167451E+09 |
| Maximum of Months | 0.599695E+09 | 0.456477E+09 | 0.183485E+09 | 0.888784E+09 | 0.335262E+09 |
Report: WindowEnergyReportMonthly
For: TWINDOW14
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 36368815.61 | 19519249.05 | 16849566.56 | 43412861.63 | 56188066.21 |
| February | 34285857.39 | 15590921.77 | 18694935.62 | 38023358.28 | 46014687.36 |
| March | 46535560.13 | 20757321.03 | 25778239.10 | 54326009.44 | 51555971.18 |
| April | 57637664.23 | 29012075.86 | 28625588.37 | 76407274.74 | 42061296.27 |
| May | 55947388.00 | 23318309.45 | 32629078.56 | 70493474.49 | 39883465.11 |
| June | 53866036.62 | 23388691.01 | 30477345.60 | 71511509.63 | 32019434.91 |
| July | 63076129.53 | 31369520.18 | 31706609.35 | 90910459.74 | 29717499.80 |
| August | 62242017.08 | 33052100.77 | 29189916.31 | 90699467.31 | 30539358.64 |
| September | 43967562.18 | 20201913.98 | 23765648.19 | 60216058.89 | 34259427.23 |
| October | 39943681.08 | 20440209.35 | 19503471.73 | 56729501.39 | 38387446.89 |
| November | 35249938.61 | 17834735.76 | 17415202.85 | 42045251.97 | 49747002.77 |
| December | 34983076.64 | 19470211.29 | 15512865.36 | 41697699.23 | 55984634.81 |
| Annual Sum or Average | 0.564104E+09 | 0.273955E+09 | 0.290148E+09 | 0.736473E+09 | 0.506358E+09 |
| Minimum of Months | 34285857.39 | 15590921.77 | 15512865.36 | 38023358.28 | 29717499.80 |
| Maximum of Months | 63076129.53 | 33052100.77 | 32629078.56 | 90910459.74 | 56188066.21 |
Report: WindowEnergyReportMonthly
For: ENTRANCE DOOR
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.108315E+09 | 58133181.30 | 50182202.46 | 0.129447E+09 | 0.166326E+09 |
| February | 0.102112E+09 | 46433645.05 | 55678170.75 | 0.115092E+09 | 0.134301E+09 |
| March | 0.138594E+09 | 61820467.77 | 76774011.29 | 0.167516E+09 | 0.145715E+09 |
| April | 0.171659E+09 | 86405181.96 | 85254126.03 | 0.233337E+09 | 0.119216E+09 |
| May | 0.166625E+09 | 69447728.60 | 97177516.13 | 0.214266E+09 | 0.115371E+09 |
| June | 0.160426E+09 | 69657342.43 | 90769119.90 | 0.218554E+09 | 91565803.75 |
| July | 0.187856E+09 | 93426237.82 | 94430173.25 | 0.274967E+09 | 87772350.98 |
| August | 0.185372E+09 | 98437381.56 | 86934835.07 | 0.273401E+09 | 90649937.94 |
| September | 0.130946E+09 | 60166327.35 | 70780014.72 | 0.180583E+09 | 0.101933E+09 |
| October | 0.118962E+09 | 60876030.26 | 58086192.50 | 0.165925E+09 | 0.118476E+09 |
| November | 0.104983E+09 | 53116281.50 | 51866808.11 | 0.122343E+09 | 0.153105E+09 |
| December | 0.104188E+09 | 57987134.63 | 46201173.62 | 0.122620E+09 | 0.169804E+09 |
| Annual Sum or Average | 0.168004E+10 | 0.815907E+09 | 0.864134E+09 | 0.221805E+10 | 0.149423E+10 |
| Minimum of Months | 0.102112E+09 | 46433645.05 | 46201173.62 | 0.115092E+09 | 87772350.98 |
| Maximum of Months | 0.187856E+09 | 98437381.56 | 97177516.13 | 0.274967E+09 | 0.169804E+09 |
Report: WindowEnergyReportMonthly
For: MWINDOW14
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 36368815.61 | 19519249.05 | 16849566.56 | 39622705.36 | 63984002.04 |
| February | 34285857.39 | 15590921.77 | 18694935.62 | 34230588.55 | 54273297.27 |
| March | 46535560.13 | 20757321.03 | 25778239.10 | 50132654.08 | 59209857.60 |
| April | 57637664.23 | 29012075.86 | 28625588.37 | 72937112.80 | 47265937.70 |
| May | 55947388.00 | 23318309.45 | 32629078.56 | 66555933.78 | 44775080.67 |
| June | 53866036.62 | 23388691.01 | 30477345.60 | 69744039.54 | 34559732.31 |
| July | 63076129.53 | 31369520.18 | 31706609.35 | 90337890.57 | 31376158.37 |
| August | 62242017.08 | 33052100.77 | 29189916.31 | 90062279.65 | 32301689.46 |
| September | 43967562.18 | 20201913.98 | 23765648.19 | 58780367.62 | 37201479.41 |
| October | 39943681.08 | 20440209.35 | 19503471.73 | 54306091.58 | 42343506.09 |
| November | 35249938.61 | 17834735.76 | 17415202.85 | 37750021.89 | 57958925.95 |
| December | 34983076.64 | 19470211.29 | 15512865.36 | 37590712.83 | 64919584.45 |
| Annual Sum or Average | 0.564104E+09 | 0.273955E+09 | 0.290148E+09 | 0.702050E+09 | 0.570169E+09 |
| Minimum of Months | 34285857.39 | 15590921.77 | 15512865.36 | 34230588.55 | 31376158.37 |
| Maximum of Months | 63076129.53 | 33052100.77 | 32629078.56 | 90337890.57 | 64919584.45 |
Report: WindowZoneSummaryMonthly
For: G SW APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 368.90 | 216.83 | 262.02 | 179.59 | 82.43 | 0.00 | 0.00 |
| February | 310.15 | 191.83 | 232.34 | 134.67 | 97.67 | 0.00 | 0.00 |
| March | 271.63 | 191.65 | 203.29 | 94.56 | 108.73 | 0.00 | 0.00 |
| April | 309.53 | 160.69 | 215.33 | 99.00 | 116.32 | 0.00 | 0.00 |
| May | 225.37 | 145.10 | 176.69 | 54.74 | 121.95 | 0.00 | 0.00 |
| June | 230.85 | 111.91 | 173.84 | 56.85 | 116.98 | 0.00 | 0.00 |
| July | 268.07 | 100.17 | 184.10 | 67.91 | 116.19 | 0.00 | 0.00 |
| August | 307.61 | 106.92 | 197.17 | 85.47 | 111.70 | 0.00 | 0.00 |
| September | 334.97 | 127.19 | 217.09 | 111.49 | 105.60 | 0.00 | 0.00 |
| October | 372.38 | 141.92 | 236.10 | 150.38 | 85.72 | 0.00 | 0.00 |
| November | 370.09 | 202.87 | 263.82 | 175.40 | 88.43 | 0.00 | 0.00 |
| December | 394.19 | 219.89 | 278.27 | 199.51 | 78.77 | 0.00 | 0.00 |
| Annual Sum or Average | 313.70 | 159.58 | 219.93 | 117.40 | 102.53 | 0.00 | 0.00 |
| Minimum of Months | 225.37 | 100.17 | 173.84 | 54.74 | 78.77 | 0.00 | 0.00 |
| Maximum of Months | 394.19 | 219.89 | 278.27 | 199.51 | 121.95 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: G NW APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 88.76 | 208.56 | 85.39 | 27.06 | 58.34 | 0.00 | 0.00 |
| February | 106.41 | 179.17 | 103.79 | 29.50 | 74.29 | 0.00 | 0.00 |
| March | 133.21 | 182.72 | 122.11 | 32.41 | 89.70 | 0.00 | 0.00 |
| April | 195.62 | 149.97 | 157.28 | 52.75 | 104.53 | 0.00 | 0.00 |
| May | 199.49 | 137.80 | 167.14 | 49.20 | 117.94 | 0.00 | 0.00 |
| June | 230.45 | 108.49 | 177.17 | 59.57 | 117.60 | 0.00 | 0.00 |
| July | 251.52 | 97.65 | 179.53 | 65.24 | 114.29 | 0.00 | 0.00 |
| August | 226.64 | 103.68 | 161.22 | 57.82 | 103.39 | 0.00 | 0.00 |
| September | 181.28 | 124.21 | 137.31 | 47.78 | 89.53 | 0.00 | 0.00 |
| October | 146.71 | 140.61 | 106.42 | 37.36 | 69.06 | 0.00 | 0.00 |
| November | 101.63 | 192.66 | 96.10 | 32.20 | 63.90 | 0.00 | 0.00 |
| December | 88.12 | 209.98 | 83.92 | 29.08 | 54.85 | 0.00 | 0.00 |
| Annual Sum or Average | 162.79 | 152.84 | 131.56 | 43.39 | 88.17 | 0.00 | 0.00 |
| Minimum of Months | 88.12 | 97.65 | 83.92 | 27.06 | 54.85 | 0.00 | 0.00 |
| Maximum of Months | 251.52 | 209.98 | 179.53 | 65.24 | 117.94 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: OFFICE
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 369.73 | 222.50 | 264.96 | 182.91 | 82.05 | 0.00 | 0.00 |
| February | 297.09 | 199.44 | 227.46 | 132.02 | 95.44 | 0.00 | 0.00 |
| March | 261.31 | 196.23 | 202.42 | 94.46 | 107.97 | 0.00 | 0.00 |
| April | 289.69 | 166.13 | 207.13 | 93.23 | 113.89 | 0.00 | 0.00 |
| May | 198.36 | 151.11 | 164.63 | 45.35 | 119.27 | 0.00 | 0.00 |
| June | 196.38 | 123.27 | 155.21 | 41.83 | 113.38 | 0.00 | 0.00 |
| July | 238.15 | 117.97 | 170.84 | 57.09 | 113.74 | 0.00 | 0.00 |
| August | 285.17 | 124.33 | 189.66 | 80.40 | 109.25 | 0.00 | 0.00 |
| September | 297.26 | 145.00 | 198.43 | 96.21 | 102.22 | 0.00 | 0.00 |
| October | 350.14 | 162.61 | 229.86 | 144.83 | 85.04 | 0.00 | 0.00 |
| November | 356.22 | 211.71 | 258.83 | 171.87 | 86.96 | 0.00 | 0.00 |
| December | 389.31 | 227.59 | 278.33 | 200.72 | 77.61 | 0.00 | 0.00 |
| Annual Sum or Average | 294.14 | 170.52 | 212.27 | 111.70 | 100.57 | 0.00 | 0.00 |
| Minimum of Months | 196.38 | 117.97 | 155.21 | 41.83 | 77.61 | 0.00 | 0.00 |
| Maximum of Months | 389.31 | 227.59 | 278.33 | 200.72 | 119.27 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: G NE APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 83.21 | 198.85 | 88.33 | 30.37 | 57.96 | 0.00 | 0.00 |
| February | 93.04 | 172.96 | 98.91 | 26.86 | 72.05 | 0.00 | 0.00 |
| March | 125.04 | 175.56 | 121.24 | 32.30 | 88.95 | 0.00 | 0.00 |
| April | 179.04 | 144.61 | 149.08 | 46.98 | 102.10 | 0.00 | 0.00 |
| May | 178.96 | 134.26 | 155.08 | 39.82 | 115.26 | 0.00 | 0.00 |
| June | 200.88 | 106.35 | 158.54 | 44.54 | 114.00 | 0.00 | 0.00 |
| July | 230.71 | 96.85 | 166.27 | 54.43 | 111.84 | 0.00 | 0.00 |
| August | 213.97 | 101.59 | 153.71 | 52.75 | 100.95 | 0.00 | 0.00 |
| September | 151.36 | 122.63 | 118.65 | 32.50 | 86.15 | 0.00 | 0.00 |
| October | 131.72 | 135.64 | 100.18 | 31.80 | 68.38 | 0.00 | 0.00 |
| November | 86.44 | 185.26 | 91.11 | 28.68 | 62.44 | 0.00 | 0.00 |
| December | 77.73 | 199.83 | 83.98 | 30.29 | 53.69 | 0.00 | 0.00 |
| Annual Sum or Average | 146.35 | 147.75 | 123.90 | 37.69 | 86.21 | 0.00 | 0.00 |
| Minimum of Months | 77.73 | 96.85 | 83.98 | 26.86 | 53.69 | 0.00 | 0.00 |
| Maximum of Months | 230.71 | 199.83 | 166.27 | 54.43 | 115.26 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: G N1 APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 19.92 | 133.00 | 31.75 | 0.00 | 31.75 | 0.00 | 0.00 |
| February | 25.94 | 115.34 | 39.85 | 0.00 | 39.85 | 0.00 | 0.00 |
| March | 38.84 | 116.41 | 48.84 | 0.00 | 48.84 | 0.00 | 0.00 |
| April | 51.34 | 93.91 | 56.41 | 0.34 | 56.08 | 0.00 | 0.00 |
| May | 62.91 | 85.00 | 68.03 | 3.54 | 64.49 | 0.00 | 0.00 |
| June | 78.73 | 66.52 | 71.93 | 6.94 | 64.99 | 0.00 | 0.00 |
| July | 82.92 | 58.91 | 68.12 | 5.62 | 62.51 | 0.00 | 0.00 |
| August | 66.61 | 62.80 | 56.86 | 1.33 | 55.53 | 0.00 | 0.00 |
| September | 50.44 | 77.97 | 47.96 | 0.02 | 47.94 | 0.00 | 0.00 |
| October | 43.76 | 88.50 | 38.03 | 0.00 | 38.03 | 0.00 | 0.00 |
| November | 21.78 | 124.79 | 34.43 | 0.00 | 34.43 | 0.00 | 0.00 |
| December | 17.38 | 135.15 | 29.55 | 0.00 | 29.55 | 0.00 | 0.00 |
| Annual Sum or Average | 46.84 | 96.43 | 49.35 | 1.49 | 47.86 | 0.00 | 0.00 |
| Minimum of Months | 17.38 | 58.91 | 29.55 | 0.00 | 29.55 | 0.00 | 0.00 |
| Maximum of Months | 82.92 | 135.15 | 71.93 | 6.94 | 64.99 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: G N2 APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 19.87 | 133.06 | 31.75 | 0.00 | 31.75 | 0.00 | 0.00 |
| February | 25.92 | 115.29 | 39.85 | 0.00 | 39.85 | 0.00 | 0.00 |
| March | 38.79 | 116.42 | 48.84 | 0.00 | 48.84 | 0.00 | 0.00 |
| April | 51.33 | 93.83 | 56.41 | 0.34 | 56.08 | 0.00 | 0.00 |
| May | 62.95 | 84.89 | 68.03 | 3.54 | 64.49 | 0.00 | 0.00 |
| June | 78.78 | 66.44 | 71.93 | 6.94 | 64.99 | 0.00 | 0.00 |
| July | 82.92 | 58.88 | 68.12 | 5.62 | 62.51 | 0.00 | 0.00 |
| August | 66.59 | 62.78 | 56.86 | 1.33 | 55.53 | 0.00 | 0.00 |
| September | 50.45 | 77.90 | 47.96 | 0.02 | 47.94 | 0.00 | 0.00 |
| October | 43.75 | 88.48 | 38.03 | 0.00 | 38.03 | 0.00 | 0.00 |
| November | 21.77 | 124.70 | 34.43 | 0.00 | 34.43 | 0.00 | 0.00 |
| December | 17.35 | 135.15 | 29.55 | 0.00 | 29.55 | 0.00 | 0.00 |
| Annual Sum or Average | 46.83 | 96.39 | 49.35 | 1.49 | 47.86 | 0.00 | 0.00 |
| Minimum of Months | 17.35 | 58.88 | 29.55 | 0.00 | 29.55 | 0.00 | 0.00 |
| Maximum of Months | 82.92 | 135.15 | 71.93 | 6.94 | 64.99 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: G S1 APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 306.58 | 135.19 | 208.37 | 152.54 | 55.84 | 0.00 | 0.00 |
| February | 233.88 | 122.56 | 168.40 | 105.17 | 63.23 | 0.00 | 0.00 |
| March | 179.88 | 122.75 | 130.02 | 62.16 | 67.86 | 0.00 | 0.00 |
| April | 169.53 | 103.03 | 114.46 | 46.59 | 67.87 | 0.00 | 0.00 |
| May | 91.20 | 93.90 | 77.58 | 9.07 | 68.51 | 0.00 | 0.00 |
| June | 81.42 | 72.53 | 68.60 | 4.22 | 64.38 | 0.00 | 0.00 |
| July | 101.66 | 63.45 | 72.70 | 8.29 | 64.41 | 0.00 | 0.00 |
| August | 149.58 | 66.61 | 92.81 | 28.98 | 63.84 | 0.00 | 0.00 |
| September | 205.75 | 79.23 | 127.74 | 63.73 | 64.01 | 0.00 | 0.00 |
| October | 271.55 | 86.67 | 167.71 | 113.02 | 54.69 | 0.00 | 0.00 |
| November | 296.00 | 125.45 | 202.16 | 143.19 | 58.96 | 0.00 | 0.00 |
| December | 330.94 | 136.96 | 223.90 | 170.43 | 53.47 | 0.00 | 0.00 |
| Annual Sum or Average | 201.38 | 100.58 | 137.72 | 75.49 | 62.23 | 0.00 | 0.00 |
| Minimum of Months | 81.42 | 63.45 | 68.60 | 4.22 | 53.47 | 0.00 | 0.00 |
| Maximum of Months | 330.94 | 136.96 | 223.90 | 170.43 | 68.51 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: G S2 APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 306.45 | 135.37 | 208.37 | 152.54 | 55.84 | 0.00 | 0.00 |
| February | 233.52 | 123.12 | 168.40 | 105.17 | 63.23 | 0.00 | 0.00 |
| March | 179.38 | 123.50 | 130.02 | 62.16 | 67.86 | 0.00 | 0.00 |
| April | 169.18 | 103.51 | 114.46 | 46.59 | 67.87 | 0.00 | 0.00 |
| May | 90.74 | 94.47 | 77.58 | 9.07 | 68.51 | 0.00 | 0.00 |
| June | 81.03 | 72.96 | 68.60 | 4.22 | 64.38 | 0.00 | 0.00 |
| July | 101.29 | 63.83 | 72.70 | 8.29 | 64.41 | 0.00 | 0.00 |
| August | 149.20 | 67.05 | 92.81 | 28.98 | 63.84 | 0.00 | 0.00 |
| September | 205.47 | 79.62 | 127.74 | 63.73 | 64.01 | 0.00 | 0.00 |
| October | 271.18 | 87.20 | 167.71 | 113.02 | 54.69 | 0.00 | 0.00 |
| November | 295.80 | 125.75 | 202.16 | 143.19 | 58.96 | 0.00 | 0.00 |
| December | 330.72 | 137.30 | 223.90 | 170.43 | 53.47 | 0.00 | 0.00 |
| Annual Sum or Average | 201.04 | 101.02 | 137.72 | 75.49 | 62.23 | 0.00 | 0.00 |
| Minimum of Months | 81.03 | 63.83 | 68.60 | 4.22 | 53.47 | 0.00 | 0.00 |
| Maximum of Months | 330.72 | 137.30 | 223.90 | 170.43 | 68.51 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: M SW APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 361.74 | 227.04 | 262.02 | 179.59 | 82.43 | 0.00 | 0.00 |
| February | 298.78 | 209.60 | 232.34 | 134.67 | 97.67 | 0.00 | 0.00 |
| March | 257.30 | 213.73 | 203.29 | 94.56 | 108.73 | 0.00 | 0.00 |
| April | 297.88 | 176.05 | 215.33 | 99.00 | 116.32 | 0.00 | 0.00 |
| May | 213.29 | 159.46 | 176.69 | 54.74 | 121.95 | 0.00 | 0.00 |
| June | 221.76 | 120.90 | 173.84 | 56.85 | 116.98 | 0.00 | 0.00 |
| July | 263.37 | 103.48 | 184.10 | 67.91 | 116.19 | 0.00 | 0.00 |
| August | 303.36 | 110.11 | 197.17 | 85.47 | 111.70 | 0.00 | 0.00 |
| September | 330.87 | 130.34 | 217.09 | 111.49 | 105.60 | 0.00 | 0.00 |
| October | 369.20 | 144.10 | 236.10 | 150.38 | 85.72 | 0.00 | 0.00 |
| November | 365.00 | 208.22 | 263.82 | 175.40 | 88.43 | 0.00 | 0.00 |
| December | 387.95 | 227.85 | 278.27 | 199.51 | 78.77 | 0.00 | 0.00 |
| Annual Sum or Average | 305.96 | 169.02 | 219.93 | 117.40 | 102.53 | 0.00 | 0.00 |
| Minimum of Months | 213.29 | 103.48 | 173.84 | 54.74 | 78.77 | 0.00 | 0.00 |
| Maximum of Months | 387.95 | 227.85 | 278.27 | 199.51 | 121.95 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: M NW APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 82.71 | 222.87 | 85.39 | 27.06 | 58.34 | 0.00 | 0.00 |
| February | 94.47 | 203.80 | 103.79 | 29.50 | 74.29 | 0.00 | 0.00 |
| March | 119.04 | 206.97 | 122.11 | 32.41 | 89.70 | 0.00 | 0.00 |
| April | 180.26 | 171.66 | 157.28 | 52.75 | 104.53 | 0.00 | 0.00 |
| May | 186.04 | 152.64 | 167.14 | 49.20 | 117.94 | 0.00 | 0.00 |
| June | 220.73 | 116.78 | 177.17 | 59.57 | 117.60 | 0.00 | 0.00 |
| July | 246.53 | 100.83 | 179.53 | 65.24 | 114.29 | 0.00 | 0.00 |
| August | 222.28 | 107.39 | 161.22 | 57.82 | 103.39 | 0.00 | 0.00 |
| September | 177.00 | 129.09 | 137.31 | 47.78 | 89.53 | 0.00 | 0.00 |
| October | 143.88 | 145.16 | 106.42 | 37.36 | 69.06 | 0.00 | 0.00 |
| November | 95.09 | 207.51 | 96.10 | 32.20 | 63.90 | 0.00 | 0.00 |
| December | 81.69 | 226.18 | 83.92 | 29.08 | 54.85 | 0.00 | 0.00 |
| Annual Sum or Average | 154.48 | 165.70 | 131.56 | 43.39 | 88.17 | 0.00 | 0.00 |
| Minimum of Months | 81.69 | 100.83 | 83.92 | 27.06 | 54.85 | 0.00 | 0.00 |
| Maximum of Months | 246.53 | 226.18 | 179.53 | 65.24 | 117.94 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: M SE APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 364.29 | 225.37 | 264.96 | 182.91 | 82.05 | 0.00 | 0.00 |
| February | 289.15 | 207.16 | 227.46 | 132.02 | 95.44 | 0.00 | 0.00 |
| March | 251.24 | 208.36 | 202.42 | 94.46 | 107.97 | 0.00 | 0.00 |
| April | 281.96 | 171.84 | 207.13 | 93.23 | 113.89 | 0.00 | 0.00 |
| May | 191.24 | 155.46 | 164.63 | 45.35 | 119.27 | 0.00 | 0.00 |
| June | 193.66 | 120.89 | 155.21 | 41.83 | 113.38 | 0.00 | 0.00 |
| July | 244.61 | 104.49 | 170.84 | 57.09 | 113.74 | 0.00 | 0.00 |
| August | 291.19 | 108.18 | 189.66 | 80.40 | 109.25 | 0.00 | 0.00 |
| September | 301.46 | 129.81 | 198.43 | 96.21 | 102.22 | 0.00 | 0.00 |
| October | 356.79 | 141.74 | 229.86 | 144.83 | 85.04 | 0.00 | 0.00 |
| November | 354.76 | 206.56 | 258.83 | 171.87 | 86.96 | 0.00 | 0.00 |
| December | 386.04 | 226.31 | 278.33 | 200.72 | 77.61 | 0.00 | 0.00 |
| Annual Sum or Average | 292.32 | 166.96 | 212.27 | 111.70 | 100.57 | 0.00 | 0.00 |
| Minimum of Months | 191.24 | 104.49 | 155.21 | 41.83 | 77.61 | 0.00 | 0.00 |
| Maximum of Months | 386.04 | 226.31 | 278.33 | 200.72 | 119.27 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: M NE APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 76.58 | 212.91 | 88.33 | 30.37 | 57.96 | 0.00 | 0.00 |
| February | 80.92 | 197.04 | 98.91 | 26.86 | 72.05 | 0.00 | 0.00 |
| March | 110.41 | 199.11 | 121.24 | 32.30 | 88.95 | 0.00 | 0.00 |
| April | 163.21 | 166.47 | 149.08 | 46.98 | 102.10 | 0.00 | 0.00 |
| May | 164.77 | 149.36 | 155.08 | 39.82 | 115.26 | 0.00 | 0.00 |
| June | 191.26 | 115.39 | 158.54 | 44.54 | 114.00 | 0.00 | 0.00 |
| July | 226.12 | 100.19 | 166.27 | 54.43 | 111.84 | 0.00 | 0.00 |
| August | 209.83 | 105.22 | 153.71 | 52.75 | 100.95 | 0.00 | 0.00 |
| September | 147.26 | 128.18 | 118.65 | 32.50 | 86.15 | 0.00 | 0.00 |
| October | 128.77 | 140.28 | 100.18 | 31.80 | 68.38 | 0.00 | 0.00 |
| November | 79.46 | 199.71 | 91.11 | 28.68 | 62.44 | 0.00 | 0.00 |
| December | 70.69 | 215.49 | 83.98 | 30.29 | 53.69 | 0.00 | 0.00 |
| Annual Sum or Average | 137.82 | 160.57 | 123.90 | 37.69 | 86.21 | 0.00 | 0.00 |
| Minimum of Months | 70.69 | 100.19 | 83.98 | 26.86 | 53.69 | 0.00 | 0.00 |
| Maximum of Months | 226.12 | 215.49 | 166.27 | 54.43 | 115.26 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: M N1 APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 17.06 | 142.75 | 31.75 | 0.00 | 31.75 | 0.00 | 0.00 |
| February | 19.92 | 133.09 | 39.85 | 0.00 | 39.85 | 0.00 | 0.00 |
| March | 31.37 | 133.23 | 48.84 | 0.00 | 48.84 | 0.00 | 0.00 |
| April | 43.79 | 106.85 | 56.41 | 0.34 | 56.08 | 0.00 | 0.00 |
| May | 56.23 | 92.54 | 68.03 | 3.54 | 64.49 | 0.00 | 0.00 |
| June | 74.58 | 70.12 | 71.93 | 6.94 | 64.99 | 0.00 | 0.00 |
| July | 80.89 | 60.40 | 68.12 | 5.62 | 62.51 | 0.00 | 0.00 |
| August | 64.98 | 64.53 | 56.86 | 1.33 | 55.53 | 0.00 | 0.00 |
| September | 48.87 | 80.35 | 47.96 | 0.02 | 47.94 | 0.00 | 0.00 |
| October | 42.80 | 90.78 | 38.03 | 0.00 | 38.03 | 0.00 | 0.00 |
| November | 18.87 | 134.24 | 34.43 | 0.00 | 34.43 | 0.00 | 0.00 |
| December | 14.36 | 146.79 | 29.55 | 0.00 | 29.55 | 0.00 | 0.00 |
| Annual Sum or Average | 42.96 | 104.48 | 49.35 | 1.49 | 47.86 | 0.00 | 0.00 |
| Minimum of Months | 14.36 | 60.40 | 29.55 | 0.00 | 29.55 | 0.00 | 0.00 |
| Maximum of Months | 80.89 | 146.79 | 71.93 | 6.94 | 64.99 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: M N2 APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 17.00 | 142.84 | 31.75 | 0.00 | 31.75 | 0.00 | 0.00 |
| February | 19.90 | 133.02 | 39.85 | 0.00 | 39.85 | 0.00 | 0.00 |
| March | 31.33 | 133.19 | 48.84 | 0.00 | 48.84 | 0.00 | 0.00 |
| April | 43.75 | 106.84 | 56.41 | 0.34 | 56.08 | 0.00 | 0.00 |
| May | 56.22 | 92.52 | 68.03 | 3.54 | 64.49 | 0.00 | 0.00 |
| June | 74.58 | 70.10 | 71.93 | 6.94 | 64.99 | 0.00 | 0.00 |
| July | 80.88 | 60.38 | 68.12 | 5.62 | 62.51 | 0.00 | 0.00 |
| August | 64.96 | 64.51 | 56.86 | 1.33 | 55.53 | 0.00 | 0.00 |
| September | 48.87 | 80.32 | 47.96 | 0.02 | 47.94 | 0.00 | 0.00 |
| October | 42.79 | 90.77 | 38.03 | 0.00 | 38.03 | 0.00 | 0.00 |
| November | 18.85 | 134.17 | 34.43 | 0.00 | 34.43 | 0.00 | 0.00 |
| December | 14.32 | 146.79 | 29.55 | 0.00 | 29.55 | 0.00 | 0.00 |
| Annual Sum or Average | 42.93 | 104.46 | 49.35 | 1.49 | 47.86 | 0.00 | 0.00 |
| Minimum of Months | 14.32 | 60.38 | 29.55 | 0.00 | 29.55 | 0.00 | 0.00 |
| Maximum of Months | 80.88 | 146.79 | 71.93 | 6.94 | 64.99 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: M S1 APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 302.70 | 140.27 | 208.37 | 152.54 | 55.84 | 0.00 | 0.00 |
| February | 228.25 | 131.06 | 168.40 | 105.17 | 63.23 | 0.00 | 0.00 |
| March | 172.38 | 135.35 | 130.02 | 62.16 | 67.86 | 0.00 | 0.00 |
| April | 164.30 | 110.88 | 114.46 | 46.59 | 67.87 | 0.00 | 0.00 |
| May | 85.98 | 101.55 | 77.58 | 9.07 | 68.51 | 0.00 | 0.00 |
| June | 77.97 | 76.68 | 68.60 | 4.22 | 64.38 | 0.00 | 0.00 |
| July | 99.93 | 65.07 | 72.70 | 8.29 | 64.41 | 0.00 | 0.00 |
| August | 147.90 | 68.09 | 92.81 | 28.98 | 63.84 | 0.00 | 0.00 |
| September | 203.92 | 80.62 | 127.74 | 63.73 | 64.01 | 0.00 | 0.00 |
| October | 269.87 | 87.50 | 167.71 | 113.02 | 54.69 | 0.00 | 0.00 |
| November | 293.31 | 127.69 | 202.16 | 143.19 | 58.96 | 0.00 | 0.00 |
| December | 327.71 | 140.18 | 223.90 | 170.43 | 53.47 | 0.00 | 0.00 |
| Annual Sum or Average | 197.74 | 105.27 | 137.72 | 75.49 | 62.23 | 0.00 | 0.00 |
| Minimum of Months | 77.97 | 65.07 | 68.60 | 4.22 | 53.47 | 0.00 | 0.00 |
| Maximum of Months | 327.71 | 140.27 | 223.90 | 170.43 | 68.51 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: M S2 APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 302.66 | 140.31 | 208.37 | 152.54 | 55.84 | 0.00 | 0.00 |
| February | 228.24 | 131.02 | 168.40 | 105.17 | 63.23 | 0.00 | 0.00 |
| March | 172.36 | 135.33 | 130.02 | 62.16 | 67.86 | 0.00 | 0.00 |
| April | 164.28 | 110.87 | 114.46 | 46.59 | 67.87 | 0.00 | 0.00 |
| May | 85.96 | 101.53 | 77.58 | 9.07 | 68.51 | 0.00 | 0.00 |
| June | 77.96 | 76.65 | 68.60 | 4.22 | 64.38 | 0.00 | 0.00 |
| July | 99.91 | 65.05 | 72.70 | 8.29 | 64.41 | 0.00 | 0.00 |
| August | 147.89 | 68.07 | 92.81 | 28.98 | 63.84 | 0.00 | 0.00 |
| September | 203.92 | 80.60 | 127.74 | 63.73 | 64.01 | 0.00 | 0.00 |
| October | 269.86 | 87.48 | 167.71 | 113.02 | 54.69 | 0.00 | 0.00 |
| November | 293.30 | 127.67 | 202.16 | 143.19 | 58.96 | 0.00 | 0.00 |
| December | 327.70 | 140.17 | 223.90 | 170.43 | 53.47 | 0.00 | 0.00 |
| Annual Sum or Average | 197.73 | 105.26 | 137.72 | 75.49 | 62.23 | 0.00 | 0.00 |
| Minimum of Months | 77.96 | 65.05 | 68.60 | 4.22 | 53.47 | 0.00 | 0.00 |
| Maximum of Months | 327.70 | 140.31 | 223.90 | 170.43 | 68.51 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: T SW APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 366.46 | 201.99 | 262.02 | 179.59 | 82.43 | 0.00 | 0.00 |
| February | 305.64 | 180.39 | 232.34 | 134.67 | 97.67 | 0.00 | 0.00 |
| March | 262.78 | 187.54 | 203.29 | 94.56 | 108.73 | 0.00 | 0.00 |
| April | 299.79 | 155.20 | 215.33 | 99.00 | 116.32 | 0.00 | 0.00 |
| May | 217.44 | 139.40 | 176.69 | 54.74 | 121.95 | 0.00 | 0.00 |
| June | 220.71 | 110.27 | 173.84 | 56.85 | 116.98 | 0.00 | 0.00 |
| July | 258.40 | 97.66 | 184.10 | 67.91 | 116.19 | 0.00 | 0.00 |
| August | 298.23 | 103.80 | 197.17 | 85.47 | 111.70 | 0.00 | 0.00 |
| September | 328.14 | 119.97 | 217.09 | 111.49 | 105.60 | 0.00 | 0.00 |
| October | 369.12 | 130.64 | 236.10 | 150.38 | 85.72 | 0.00 | 0.00 |
| November | 371.04 | 181.87 | 263.82 | 175.40 | 88.43 | 0.00 | 0.00 |
| December | 393.83 | 200.23 | 278.27 | 199.51 | 78.77 | 0.00 | 0.00 |
| Annual Sum or Average | 307.68 | 150.60 | 219.93 | 117.40 | 102.53 | 0.00 | 0.00 |
| Minimum of Months | 217.44 | 97.66 | 173.84 | 54.74 | 78.77 | 0.00 | 0.00 |
| Maximum of Months | 393.83 | 201.99 | 278.27 | 199.51 | 121.95 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: T NW APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 87.38 | 199.73 | 85.39 | 27.06 | 58.34 | 0.00 | 0.00 |
| February | 101.36 | 177.23 | 103.79 | 29.50 | 74.29 | 0.00 | 0.00 |
| March | 124.13 | 184.00 | 122.11 | 32.41 | 89.70 | 0.00 | 0.00 |
| April | 184.43 | 150.20 | 157.28 | 52.75 | 104.53 | 0.00 | 0.00 |
| May | 191.58 | 133.79 | 167.14 | 49.20 | 117.94 | 0.00 | 0.00 |
| June | 220.10 | 107.28 | 177.17 | 59.57 | 117.60 | 0.00 | 0.00 |
| July | 242.03 | 95.60 | 179.53 | 65.24 | 114.29 | 0.00 | 0.00 |
| August | 218.39 | 101.02 | 161.22 | 57.82 | 103.39 | 0.00 | 0.00 |
| September | 176.60 | 117.38 | 137.31 | 47.78 | 89.53 | 0.00 | 0.00 |
| October | 146.15 | 128.84 | 106.42 | 37.36 | 69.06 | 0.00 | 0.00 |
| November | 103.29 | 176.67 | 96.10 | 32.20 | 63.90 | 0.00 | 0.00 |
| December | 87.43 | 198.74 | 83.92 | 29.08 | 54.85 | 0.00 | 0.00 |
| Annual Sum or Average | 157.21 | 147.40 | 131.56 | 43.39 | 88.17 | 0.00 | 0.00 |
| Minimum of Months | 87.38 | 95.60 | 83.92 | 27.06 | 54.85 | 0.00 | 0.00 |
| Maximum of Months | 242.03 | 199.73 | 179.53 | 65.24 | 117.94 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: T SE APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 368.86 | 200.18 | 264.96 | 182.91 | 82.05 | 0.00 | 0.00 |
| February | 295.86 | 178.17 | 227.46 | 132.02 | 95.44 | 0.00 | 0.00 |
| March | 257.44 | 183.21 | 202.42 | 94.46 | 107.97 | 0.00 | 0.00 |
| April | 284.84 | 152.06 | 207.13 | 93.23 | 113.89 | 0.00 | 0.00 |
| May | 196.70 | 136.52 | 164.63 | 45.35 | 119.27 | 0.00 | 0.00 |
| June | 193.62 | 110.44 | 155.21 | 41.83 | 113.38 | 0.00 | 0.00 |
| July | 240.25 | 98.61 | 170.84 | 57.09 | 113.74 | 0.00 | 0.00 |
| August | 286.68 | 102.13 | 189.66 | 80.40 | 109.25 | 0.00 | 0.00 |
| September | 299.43 | 119.39 | 198.43 | 96.21 | 102.22 | 0.00 | 0.00 |
| October | 356.99 | 128.57 | 229.86 | 144.83 | 85.04 | 0.00 | 0.00 |
| November | 360.70 | 180.17 | 258.83 | 171.87 | 86.96 | 0.00 | 0.00 |
| December | 391.69 | 198.65 | 278.33 | 200.72 | 77.61 | 0.00 | 0.00 |
| Annual Sum or Average | 294.52 | 148.86 | 212.27 | 111.70 | 100.57 | 0.00 | 0.00 |
| Minimum of Months | 193.62 | 98.61 | 155.21 | 41.83 | 77.61 | 0.00 | 0.00 |
| Maximum of Months | 391.69 | 200.18 | 278.33 | 200.72 | 119.27 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: T NE APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 83.07 | 190.53 | 88.33 | 30.37 | 57.96 | 0.00 | 0.00 |
| February | 88.81 | 171.22 | 98.91 | 26.86 | 72.05 | 0.00 | 0.00 |
| March | 116.66 | 177.34 | 121.24 | 32.30 | 88.95 | 0.00 | 0.00 |
| April | 168.30 | 145.59 | 149.08 | 46.98 | 102.10 | 0.00 | 0.00 |
| May | 171.00 | 131.11 | 155.08 | 39.82 | 115.26 | 0.00 | 0.00 |
| June | 190.97 | 105.50 | 158.54 | 44.54 | 114.00 | 0.00 | 0.00 |
| July | 221.75 | 94.40 | 166.27 | 54.43 | 111.84 | 0.00 | 0.00 |
| August | 206.34 | 98.82 | 153.71 | 52.75 | 100.95 | 0.00 | 0.00 |
| September | 147.57 | 116.14 | 118.65 | 32.50 | 86.15 | 0.00 | 0.00 |
| October | 132.40 | 124.98 | 100.18 | 31.80 | 68.38 | 0.00 | 0.00 |
| November | 89.48 | 170.19 | 91.11 | 28.68 | 62.44 | 0.00 | 0.00 |
| December | 78.34 | 189.32 | 83.98 | 30.29 | 53.69 | 0.00 | 0.00 |
| Annual Sum or Average | 141.57 | 142.79 | 123.90 | 37.69 | 86.21 | 0.00 | 0.00 |
| Minimum of Months | 78.34 | 94.40 | 83.98 | 26.86 | 53.69 | 0.00 | 0.00 |
| Maximum of Months | 221.75 | 190.53 | 166.27 | 54.43 | 115.26 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: T N1 APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 20.66 | 126.08 | 31.75 | 0.00 | 31.75 | 0.00 | 0.00 |
| February | 25.47 | 111.86 | 39.85 | 0.00 | 39.85 | 0.00 | 0.00 |
| March | 36.02 | 116.28 | 48.84 | 0.00 | 48.84 | 0.00 | 0.00 |
| April | 47.04 | 94.07 | 56.41 | 0.34 | 56.08 | 0.00 | 0.00 |
| May | 60.47 | 82.50 | 68.03 | 3.54 | 64.49 | 0.00 | 0.00 |
| June | 74.49 | 65.85 | 71.93 | 6.94 | 64.99 | 0.00 | 0.00 |
| July | 78.70 | 58.16 | 68.12 | 5.62 | 62.51 | 0.00 | 0.00 |
| August | 63.19 | 61.90 | 56.86 | 1.33 | 55.53 | 0.00 | 0.00 |
| September | 48.97 | 74.71 | 47.96 | 0.02 | 47.94 | 0.00 | 0.00 |
| October | 44.56 | 81.60 | 38.03 | 0.00 | 38.03 | 0.00 | 0.00 |
| November | 24.55 | 112.12 | 34.43 | 0.00 | 34.43 | 0.00 | 0.00 |
| December | 18.68 | 125.63 | 29.55 | 0.00 | 29.55 | 0.00 | 0.00 |
| Annual Sum or Average | 45.36 | 92.47 | 49.35 | 1.49 | 47.86 | 0.00 | 0.00 |
| Minimum of Months | 18.68 | 58.16 | 29.55 | 0.00 | 29.55 | 0.00 | 0.00 |
| Maximum of Months | 78.70 | 126.08 | 71.93 | 6.94 | 64.99 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: T N2 APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 20.55 | 126.04 | 31.75 | 0.00 | 31.75 | 0.00 | 0.00 |
| February | 25.36 | 111.72 | 39.85 | 0.00 | 39.85 | 0.00 | 0.00 |
| March | 35.87 | 116.21 | 48.84 | 0.00 | 48.84 | 0.00 | 0.00 |
| April | 46.89 | 93.91 | 56.41 | 0.34 | 56.08 | 0.00 | 0.00 |
| May | 60.37 | 82.37 | 68.03 | 3.54 | 64.49 | 0.00 | 0.00 |
| June | 74.46 | 65.76 | 71.93 | 6.94 | 64.99 | 0.00 | 0.00 |
| July | 78.68 | 58.09 | 68.12 | 5.62 | 62.51 | 0.00 | 0.00 |
| August | 63.14 | 61.83 | 56.86 | 1.33 | 55.53 | 0.00 | 0.00 |
| September | 48.94 | 74.56 | 47.96 | 0.02 | 47.94 | 0.00 | 0.00 |
| October | 44.48 | 81.51 | 38.03 | 0.00 | 38.03 | 0.00 | 0.00 |
| November | 24.45 | 111.96 | 34.43 | 0.00 | 34.43 | 0.00 | 0.00 |
| December | 18.58 | 125.54 | 29.55 | 0.00 | 29.55 | 0.00 | 0.00 |
| Annual Sum or Average | 45.27 | 92.36 | 49.35 | 1.49 | 47.86 | 0.00 | 0.00 |
| Minimum of Months | 18.58 | 58.09 | 29.55 | 0.00 | 29.55 | 0.00 | 0.00 |
| Maximum of Months | 78.68 | 126.04 | 71.93 | 6.94 | 64.99 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: T S1 APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 306.45 | 125.20 | 208.37 | 152.54 | 55.84 | 0.00 | 0.00 |
| February | 233.50 | 112.43 | 168.40 | 105.17 | 63.23 | 0.00 | 0.00 |
| March | 177.08 | 118.24 | 130.02 | 62.16 | 67.86 | 0.00 | 0.00 |
| April | 165.90 | 99.49 | 114.46 | 46.59 | 67.87 | 0.00 | 0.00 |
| May | 88.79 | 90.31 | 77.58 | 9.07 | 68.51 | 0.00 | 0.00 |
| June | 77.69 | 71.70 | 68.60 | 4.22 | 64.38 | 0.00 | 0.00 |
| July | 97.63 | 62.61 | 72.70 | 8.29 | 64.41 | 0.00 | 0.00 |
| August | 145.38 | 65.51 | 92.81 | 28.98 | 63.84 | 0.00 | 0.00 |
| September | 202.53 | 75.93 | 127.74 | 63.73 | 64.01 | 0.00 | 0.00 |
| October | 269.91 | 80.97 | 167.71 | 113.02 | 54.69 | 0.00 | 0.00 |
| November | 297.15 | 113.35 | 202.16 | 143.19 | 58.96 | 0.00 | 0.00 |
| December | 331.91 | 124.20 | 223.90 | 170.43 | 53.47 | 0.00 | 0.00 |
| Annual Sum or Average | 199.36 | 94.91 | 137.72 | 75.49 | 62.23 | 0.00 | 0.00 |
| Minimum of Months | 77.69 | 62.61 | 68.60 | 4.22 | 53.47 | 0.00 | 0.00 |
| Maximum of Months | 331.91 | 125.20 | 223.90 | 170.43 | 68.51 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: T S2 APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 306.35 | 125.17 | 208.37 | 152.54 | 55.84 | 0.00 | 0.00 |
| February | 233.42 | 112.35 | 168.40 | 105.17 | 63.23 | 0.00 | 0.00 |
| March | 176.97 | 118.17 | 130.02 | 62.16 | 67.86 | 0.00 | 0.00 |
| April | 165.79 | 99.38 | 114.46 | 46.59 | 67.87 | 0.00 | 0.00 |
| May | 88.69 | 90.17 | 77.58 | 9.07 | 68.51 | 0.00 | 0.00 |
| June | 77.65 | 71.58 | 68.60 | 4.22 | 64.38 | 0.00 | 0.00 |
| July | 97.59 | 62.52 | 72.70 | 8.29 | 64.41 | 0.00 | 0.00 |
| August | 145.34 | 65.43 | 92.81 | 28.98 | 63.84 | 0.00 | 0.00 |
| September | 202.51 | 75.83 | 127.74 | 63.73 | 64.01 | 0.00 | 0.00 |
| October | 269.87 | 80.92 | 167.71 | 113.02 | 54.69 | 0.00 | 0.00 |
| November | 297.08 | 113.27 | 202.16 | 143.19 | 58.96 | 0.00 | 0.00 |
| December | 331.83 | 124.15 | 223.90 | 170.43 | 53.47 | 0.00 | 0.00 |
| Annual Sum or Average | 199.29 | 94.82 | 137.72 | 75.49 | 62.23 | 0.00 | 0.00 |
| Minimum of Months | 77.65 | 62.52 | 68.60 | 4.22 | 53.47 | 0.00 | 0.00 |
| Maximum of Months | 331.83 | 125.17 | 223.90 | 170.43 | 68.51 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: T CORRIDOR
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 16.21 | 20.98 | 13.58 | 7.29 | 6.29 | 0.00 | 0.00 |
| February | 15.72 | 19.02 | 14.17 | 6.44 | 7.73 | 0.00 | 0.00 |
| March | 20.28 | 19.25 | 17.37 | 7.75 | 9.62 | 0.00 | 0.00 |
| April | 29.48 | 16.23 | 22.24 | 11.19 | 11.04 | 0.00 | 0.00 |
| May | 26.32 | 14.89 | 20.89 | 8.71 | 12.18 | 0.00 | 0.00 |
| June | 27.59 | 12.35 | 20.78 | 9.02 | 11.76 | 0.00 | 0.00 |
| July | 33.94 | 11.10 | 23.55 | 11.71 | 11.84 | 0.00 | 0.00 |
| August | 33.86 | 11.40 | 23.24 | 12.34 | 10.90 | 0.00 | 0.00 |
| September | 23.23 | 13.22 | 16.96 | 7.79 | 9.17 | 0.00 | 0.00 |
| October | 21.18 | 14.33 | 14.91 | 7.63 | 7.28 | 0.00 | 0.00 |
| November | 16.22 | 19.19 | 13.60 | 6.88 | 6.72 | 0.00 | 0.00 |
| December | 15.57 | 20.90 | 13.06 | 7.27 | 5.79 | 0.00 | 0.00 |
| Annual Sum or Average | 23.35 | 16.06 | 17.89 | 8.69 | 9.20 | 0.00 | 0.00 |
| Minimum of Months | 15.57 | 11.10 | 13.06 | 6.44 | 5.79 | 0.00 | 0.00 |
| Maximum of Months | 33.94 | 20.98 | 23.55 | 12.34 | 12.18 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: G CORRIDOR
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 48.33 | 62.10 | 40.44 | 21.70 | 18.74 | 0.00 | 0.00 |
| February | 47.57 | 55.51 | 42.21 | 19.19 | 23.02 | 0.00 | 0.00 |
| March | 62.54 | 54.40 | 51.75 | 23.08 | 28.66 | 0.00 | 0.00 |
| April | 90.02 | 45.99 | 66.23 | 33.34 | 32.89 | 0.00 | 0.00 |
| May | 80.00 | 43.07 | 62.21 | 25.93 | 36.28 | 0.00 | 0.00 |
| June | 84.32 | 35.33 | 61.89 | 26.87 | 35.02 | 0.00 | 0.00 |
| July | 102.66 | 32.77 | 70.14 | 34.88 | 35.26 | 0.00 | 0.00 |
| August | 102.08 | 33.84 | 69.21 | 36.75 | 32.46 | 0.00 | 0.00 |
| September | 69.67 | 39.33 | 50.52 | 23.21 | 27.31 | 0.00 | 0.00 |
| October | 61.95 | 44.23 | 44.42 | 22.73 | 21.69 | 0.00 | 0.00 |
| November | 47.20 | 59.07 | 40.50 | 20.49 | 20.01 | 0.00 | 0.00 |
| December | 45.78 | 63.40 | 38.90 | 21.65 | 17.25 | 0.00 | 0.00 |
| Annual Sum or Average | 70.33 | 47.38 | 53.27 | 25.87 | 27.40 | 0.00 | 0.00 |
| Minimum of Months | 45.78 | 32.77 | 38.90 | 19.19 | 17.25 | 0.00 | 0.00 |
| Maximum of Months | 102.66 | 63.40 | 70.14 | 36.75 | 36.28 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: M CORRIDOR
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 14.79 | 23.89 | 13.58 | 7.29 | 6.29 | 0.00 | 0.00 |
| February | 14.15 | 22.43 | 14.17 | 6.44 | 7.73 | 0.00 | 0.00 |
| March | 18.72 | 22.11 | 17.37 | 7.75 | 9.62 | 0.00 | 0.00 |
| April | 28.14 | 18.24 | 22.24 | 11.19 | 11.04 | 0.00 | 0.00 |
| May | 24.85 | 16.72 | 20.89 | 8.71 | 12.18 | 0.00 | 0.00 |
| June | 26.91 | 13.33 | 20.78 | 9.02 | 11.76 | 0.00 | 0.00 |
| July | 33.73 | 11.71 | 23.55 | 11.71 | 11.84 | 0.00 | 0.00 |
| August | 33.63 | 12.06 | 23.24 | 12.34 | 10.90 | 0.00 | 0.00 |
| September | 22.68 | 14.35 | 16.96 | 7.79 | 9.17 | 0.00 | 0.00 |
| October | 20.28 | 15.81 | 14.91 | 7.63 | 7.28 | 0.00 | 0.00 |
| November | 14.56 | 22.36 | 13.60 | 6.88 | 6.72 | 0.00 | 0.00 |
| December | 14.03 | 24.24 | 13.06 | 7.27 | 5.79 | 0.00 | 0.00 |
| Annual Sum or Average | 22.26 | 18.08 | 17.89 | 8.69 | 9.20 | 0.00 | 0.00 |
| Minimum of Months | 14.03 | 11.71 | 13.06 | 6.44 | 5.79 | 0.00 | 0.00 |
| Maximum of Months | 33.73 | 24.24 | 23.55 | 12.34 | 12.18 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: G SW APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.988051E+09 | 0.580756E+09 | 0.701790E+09 | 0.481019E+09 | 0.220771E+09 | 0.00 | 0.00 |
| February | 0.750313E+09 | 0.464065E+09 | 0.562068E+09 | 0.325787E+09 | 0.236281E+09 | 0.00 | 0.00 |
| March | 0.727528E+09 | 0.513317E+09 | 0.544488E+09 | 0.253277E+09 | 0.291211E+09 | 0.00 | 0.00 |
| April | 0.802292E+09 | 0.416500E+09 | 0.558127E+09 | 0.256618E+09 | 0.301509E+09 | 0.00 | 0.00 |
| May | 0.603621E+09 | 0.388648E+09 | 0.473247E+09 | 0.146603E+09 | 0.326644E+09 | 0.00 | 0.00 |
| June | 0.598376E+09 | 0.290083E+09 | 0.450581E+09 | 0.147368E+09 | 0.303214E+09 | 0.00 | 0.00 |
| July | 0.717992E+09 | 0.268290E+09 | 0.493104E+09 | 0.181899E+09 | 0.311205E+09 | 0.00 | 0.00 |
| August | 0.823897E+09 | 0.286387E+09 | 0.528107E+09 | 0.228936E+09 | 0.299171E+09 | 0.00 | 0.00 |
| September | 0.868240E+09 | 0.329674E+09 | 0.562704E+09 | 0.288990E+09 | 0.273714E+09 | 0.00 | 0.00 |
| October | 0.997372E+09 | 0.380114E+09 | 0.632379E+09 | 0.402780E+09 | 0.229599E+09 | 0.00 | 0.00 |
| November | 0.959283E+09 | 0.525843E+09 | 0.683827E+09 | 0.454625E+09 | 0.229203E+09 | 0.00 | 0.00 |
| December | 0.105581E+10 | 0.588956E+09 | 0.745322E+09 | 0.534355E+09 | 0.210968E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.989277E+10 | 0.503263E+10 | 0.693574E+10 | 0.370226E+10 | 0.323349E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.598376E+09 | 0.268290E+09 | 0.450581E+09 | 0.146603E+09 | 0.210968E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.105581E+10 | 0.588956E+09 | 0.745322E+09 | 0.534355E+09 | 0.326644E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: G NW APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.237730E+09 | 0.558617E+09 | 0.228717E+09 | 72468237.92 | 0.156249E+09 | 0.00 | 0.00 |
| February | 0.257423E+09 | 0.433457E+09 | 0.251083E+09 | 71369157.64 | 0.179714E+09 | 0.00 | 0.00 |
| March | 0.356780E+09 | 0.489395E+09 | 0.327060E+09 | 86794536.43 | 0.240265E+09 | 0.00 | 0.00 |
| April | 0.507044E+09 | 0.388715E+09 | 0.407669E+09 | 0.136733E+09 | 0.270937E+09 | 0.00 | 0.00 |
| May | 0.534308E+09 | 0.369091E+09 | 0.447672E+09 | 0.131781E+09 | 0.315891E+09 | 0.00 | 0.00 |
| June | 0.597331E+09 | 0.281208E+09 | 0.459214E+09 | 0.154405E+09 | 0.304809E+09 | 0.00 | 0.00 |
| July | 0.673662E+09 | 0.261550E+09 | 0.480858E+09 | 0.174750E+09 | 0.306108E+09 | 0.00 | 0.00 |
| August | 0.607039E+09 | 0.277696E+09 | 0.431810E+09 | 0.154878E+09 | 0.276932E+09 | 0.00 | 0.00 |
| September | 0.469889E+09 | 0.321954E+09 | 0.355914E+09 | 0.123844E+09 | 0.232070E+09 | 0.00 | 0.00 |
| October | 0.392955E+09 | 0.376604E+09 | 0.285040E+09 | 0.100062E+09 | 0.184977E+09 | 0.00 | 0.00 |
| November | 0.263416E+09 | 0.499366E+09 | 0.249094E+09 | 83472084.97 | 0.165622E+09 | 0.00 | 0.00 |
| December | 0.236029E+09 | 0.562409E+09 | 0.224781E+09 | 77877952.25 | 0.146903E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.513360E+10 | 0.482006E+10 | 0.414891E+10 | 0.136843E+10 | 0.278048E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.236029E+09 | 0.261550E+09 | 0.224781E+09 | 71369157.64 | 0.146903E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.673662E+09 | 0.562409E+09 | 0.480858E+09 | 0.174750E+09 | 0.315891E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: OFFICE
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.990274E+09 | 0.595953E+09 | 0.709666E+09 | 0.489896E+09 | 0.219770E+09 | 0.00 | 0.00 |
| February | 0.718723E+09 | 0.482475E+09 | 0.550274E+09 | 0.319392E+09 | 0.230881E+09 | 0.00 | 0.00 |
| March | 0.699885E+09 | 0.525584E+09 | 0.542171E+09 | 0.252992E+09 | 0.289178E+09 | 0.00 | 0.00 |
| April | 0.750865E+09 | 0.430603E+09 | 0.536879E+09 | 0.241663E+09 | 0.295215E+09 | 0.00 | 0.00 |
| May | 0.531296E+09 | 0.404746E+09 | 0.440937E+09 | 0.121471E+09 | 0.319466E+09 | 0.00 | 0.00 |
| June | 0.509018E+09 | 0.319525E+09 | 0.402302E+09 | 0.108419E+09 | 0.293882E+09 | 0.00 | 0.00 |
| July | 0.637861E+09 | 0.315965E+09 | 0.457577E+09 | 0.152923E+09 | 0.304654E+09 | 0.00 | 0.00 |
| August | 0.763788E+09 | 0.333000E+09 | 0.507981E+09 | 0.215355E+09 | 0.292626E+09 | 0.00 | 0.00 |
| September | 0.770498E+09 | 0.375830E+09 | 0.514328E+09 | 0.249381E+09 | 0.264947E+09 | 0.00 | 0.00 |
| October | 0.937826E+09 | 0.435544E+09 | 0.615666E+09 | 0.387902E+09 | 0.227764E+09 | 0.00 | 0.00 |
| November | 0.923334E+09 | 0.548759E+09 | 0.670891E+09 | 0.445478E+09 | 0.225413E+09 | 0.00 | 0.00 |
| December | 0.104273E+10 | 0.609564E+09 | 0.745485E+09 | 0.537618E+09 | 0.207867E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.927609E+10 | 0.537755E+10 | 0.669416E+10 | 0.352249E+10 | 0.317166E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.509018E+09 | 0.315965E+09 | 0.402302E+09 | 0.108419E+09 | 0.207867E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.104273E+10 | 0.609564E+09 | 0.745485E+09 | 0.537618E+09 | 0.319466E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: G NE APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.222873E+09 | 0.532590E+09 | 0.236593E+09 | 81345771.80 | 0.155248E+09 | 0.00 | 0.00 |
| February | 0.225093E+09 | 0.418428E+09 | 0.239288E+09 | 64974608.46 | 0.174314E+09 | 0.00 | 0.00 |
| March | 0.334896E+09 | 0.470230E+09 | 0.324742E+09 | 86509498.24 | 0.238233E+09 | 0.00 | 0.00 |
| April | 0.464067E+09 | 0.374834E+09 | 0.386421E+09 | 0.121778E+09 | 0.264643E+09 | 0.00 | 0.00 |
| May | 0.479317E+09 | 0.359598E+09 | 0.415363E+09 | 0.106649E+09 | 0.308714E+09 | 0.00 | 0.00 |
| June | 0.520690E+09 | 0.275665E+09 | 0.410934E+09 | 0.115457E+09 | 0.295477E+09 | 0.00 | 0.00 |
| July | 0.617929E+09 | 0.259400E+09 | 0.445332E+09 | 0.145774E+09 | 0.299557E+09 | 0.00 | 0.00 |
| August | 0.573096E+09 | 0.272104E+09 | 0.411684E+09 | 0.141297E+09 | 0.270387E+09 | 0.00 | 0.00 |
| September | 0.392336E+09 | 0.317861E+09 | 0.307537E+09 | 84234583.71 | 0.223302E+09 | 0.00 | 0.00 |
| October | 0.352787E+09 | 0.363286E+09 | 0.268327E+09 | 85183840.87 | 0.183143E+09 | 0.00 | 0.00 |
| November | 0.224049E+09 | 0.480191E+09 | 0.236157E+09 | 74325622.94 | 0.161832E+09 | 0.00 | 0.00 |
| December | 0.208193E+09 | 0.535220E+09 | 0.224944E+09 | 81141408.66 | 0.143803E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.461532E+10 | 0.465941E+10 | 0.390732E+10 | 0.118867E+10 | 0.271865E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.208193E+09 | 0.259400E+09 | 0.224944E+09 | 64974608.46 | 0.143803E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.617929E+09 | 0.535220E+09 | 0.445332E+09 | 0.145774E+09 | 0.308714E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: G N1 APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 53358762.36 | 0.356229E+09 | 85027568.61 | 0.00 | 85027568.61 | 0.00 | 0.00 |
| February | 62749827.01 | 0.279024E+09 | 96403407.70 | 0.00 | 96403407.70 | 0.00 | 0.00 |
| March | 0.104024E+09 | 0.311801E+09 | 0.130807E+09 | 4105.79 | 0.130803E+09 | 0.00 | 0.00 |
| April | 0.133082E+09 | 0.243408E+09 | 0.146218E+09 | 871123.55 | 0.145347E+09 | 0.00 | 0.00 |
| May | 0.168485E+09 | 0.227665E+09 | 0.182204E+09 | 9470778.58 | 0.172733E+09 | 0.00 | 0.00 |
| June | 0.204077E+09 | 0.172431E+09 | 0.186449E+09 | 17985183.97 | 0.168464E+09 | 0.00 | 0.00 |
| July | 0.222083E+09 | 0.157781E+09 | 0.182464E+09 | 15043009.94 | 0.167421E+09 | 0.00 | 0.00 |
| August | 0.178396E+09 | 0.168213E+09 | 0.152292E+09 | 3553362.43 | 0.148739E+09 | 0.00 | 0.00 |
| September | 0.130730E+09 | 0.202099E+09 | 0.124304E+09 | 43830.25 | 0.124260E+09 | 0.00 | 0.00 |
| October | 0.117219E+09 | 0.237050E+09 | 0.101863E+09 | 0.00 | 0.101863E+09 | 0.00 | 0.00 |
| November | 56449964.76 | 0.323446E+09 | 89254512.61 | 0.00 | 89254512.61 | 0.00 | 0.00 |
| December | 46543839.63 | 0.361975E+09 | 79153413.08 | 0.00 | 79153413.08 | 0.00 | 0.00 |
| Annual Sum or Average | 0.147720E+10 | 0.304112E+10 | 0.155644E+10 | 46971394.51 | 0.150947E+10 | 0.00 | 0.00 |
| Minimum of Months | 46543839.63 | 0.157781E+09 | 79153413.08 | 0.00 | 79153413.08 | 0.00 | 0.00 |
| Maximum of Months | 0.222083E+09 | 0.361975E+09 | 0.186449E+09 | 17985183.97 | 0.172733E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: G N2 APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 53232917.34 | 0.356400E+09 | 85027568.61 | 0.00 | 85027568.61 | 0.00 | 0.00 |
| February | 62705940.49 | 0.278918E+09 | 96403407.70 | 0.00 | 96403407.70 | 0.00 | 0.00 |
| March | 0.103904E+09 | 0.311820E+09 | 0.130807E+09 | 4105.79 | 0.130803E+09 | 0.00 | 0.00 |
| April | 0.133050E+09 | 0.243206E+09 | 0.146218E+09 | 871123.55 | 0.145347E+09 | 0.00 | 0.00 |
| May | 0.168596E+09 | 0.227367E+09 | 0.182204E+09 | 9470778.58 | 0.172733E+09 | 0.00 | 0.00 |
| June | 0.204187E+09 | 0.172213E+09 | 0.186449E+09 | 17985183.97 | 0.168464E+09 | 0.00 | 0.00 |
| July | 0.222083E+09 | 0.157709E+09 | 0.182464E+09 | 15043009.94 | 0.167421E+09 | 0.00 | 0.00 |
| August | 0.178366E+09 | 0.168155E+09 | 0.152292E+09 | 3553362.43 | 0.148739E+09 | 0.00 | 0.00 |
| September | 0.130775E+09 | 0.201907E+09 | 0.124304E+09 | 43830.25 | 0.124260E+09 | 0.00 | 0.00 |
| October | 0.117189E+09 | 0.236984E+09 | 0.101863E+09 | 0.00 | 0.101863E+09 | 0.00 | 0.00 |
| November | 56429430.10 | 0.323229E+09 | 89254512.61 | 0.00 | 89254512.61 | 0.00 | 0.00 |
| December | 46457554.71 | 0.361991E+09 | 79153413.08 | 0.00 | 79153413.08 | 0.00 | 0.00 |
| Annual Sum or Average | 0.147698E+10 | 0.303990E+10 | 0.155644E+10 | 46971394.51 | 0.150947E+10 | 0.00 | 0.00 |
| Minimum of Months | 46457554.71 | 0.157709E+09 | 79153413.08 | 0.00 | 79153413.08 | 0.00 | 0.00 |
| Maximum of Months | 0.222083E+09 | 0.361991E+09 | 0.186449E+09 | 17985183.97 | 0.172733E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: G S1 APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.821133E+09 | 0.362095E+09 | 0.558100E+09 | 0.408550E+09 | 0.149550E+09 | 0.00 | 0.00 |
| February | 0.565799E+09 | 0.296495E+09 | 0.407389E+09 | 0.254418E+09 | 0.152971E+09 | 0.00 | 0.00 |
| March | 0.481789E+09 | 0.328787E+09 | 0.348235E+09 | 0.166487E+09 | 0.181748E+09 | 0.00 | 0.00 |
| April | 0.439429E+09 | 0.267063E+09 | 0.296676E+09 | 0.120757E+09 | 0.175919E+09 | 0.00 | 0.00 |
| May | 0.244283E+09 | 0.251513E+09 | 0.207778E+09 | 24292585.19 | 0.183485E+09 | 0.00 | 0.00 |
| June | 0.211053E+09 | 0.188007E+09 | 0.177817E+09 | 10947826.02 | 0.166869E+09 | 0.00 | 0.00 |
| July | 0.272299E+09 | 0.169945E+09 | 0.194710E+09 | 22191625.47 | 0.172518E+09 | 0.00 | 0.00 |
| August | 0.400631E+09 | 0.178410E+09 | 0.248589E+09 | 77611251.15 | 0.170978E+09 | 0.00 | 0.00 |
| September | 0.533312E+09 | 0.205366E+09 | 0.331094E+09 | 0.165190E+09 | 0.165904E+09 | 0.00 | 0.00 |
| October | 0.727310E+09 | 0.232133E+09 | 0.449202E+09 | 0.302718E+09 | 0.146484E+09 | 0.00 | 0.00 |
| November | 0.767240E+09 | 0.325166E+09 | 0.523988E+09 | 0.371153E+09 | 0.152836E+09 | 0.00 | 0.00 |
| December | 0.886378E+09 | 0.366846E+09 | 0.599695E+09 | 0.456477E+09 | 0.143218E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.635066E+10 | 0.317183E+10 | 0.434327E+10 | 0.238079E+10 | 0.196248E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.211053E+09 | 0.169945E+09 | 0.177817E+09 | 10947826.02 | 0.143218E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.886378E+09 | 0.366846E+09 | 0.599695E+09 | 0.456477E+09 | 0.183485E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: G S2 APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.820787E+09 | 0.362578E+09 | 0.558100E+09 | 0.408550E+09 | 0.149550E+09 | 0.00 | 0.00 |
| February | 0.564932E+09 | 0.297846E+09 | 0.407389E+09 | 0.254418E+09 | 0.152971E+09 | 0.00 | 0.00 |
| March | 0.480440E+09 | 0.330789E+09 | 0.348235E+09 | 0.166487E+09 | 0.181748E+09 | 0.00 | 0.00 |
| April | 0.438511E+09 | 0.268299E+09 | 0.296676E+09 | 0.120757E+09 | 0.175919E+09 | 0.00 | 0.00 |
| May | 0.243045E+09 | 0.253036E+09 | 0.207778E+09 | 24292585.19 | 0.183485E+09 | 0.00 | 0.00 |
| June | 0.210035E+09 | 0.189120E+09 | 0.177817E+09 | 10947826.02 | 0.166869E+09 | 0.00 | 0.00 |
| July | 0.271285E+09 | 0.170966E+09 | 0.194710E+09 | 22191625.47 | 0.172518E+09 | 0.00 | 0.00 |
| August | 0.399617E+09 | 0.179582E+09 | 0.248589E+09 | 77611251.15 | 0.170978E+09 | 0.00 | 0.00 |
| September | 0.532565E+09 | 0.206369E+09 | 0.331094E+09 | 0.165190E+09 | 0.165904E+09 | 0.00 | 0.00 |
| October | 0.726334E+09 | 0.233560E+09 | 0.449202E+09 | 0.302718E+09 | 0.146484E+09 | 0.00 | 0.00 |
| November | 0.766702E+09 | 0.325939E+09 | 0.523988E+09 | 0.371153E+09 | 0.152836E+09 | 0.00 | 0.00 |
| December | 0.885792E+09 | 0.367737E+09 | 0.599695E+09 | 0.456477E+09 | 0.143218E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.634004E+10 | 0.318582E+10 | 0.434327E+10 | 0.238079E+10 | 0.196248E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.210035E+09 | 0.170966E+09 | 0.177817E+09 | 10947826.02 | 0.143218E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.885792E+09 | 0.367737E+09 | 0.599695E+09 | 0.456477E+09 | 0.183485E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: M SW APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.968896E+09 | 0.608111E+09 | 0.701790E+09 | 0.481019E+09 | 0.220771E+09 | 0.00 | 0.00 |
| February | 0.722807E+09 | 0.507071E+09 | 0.562068E+09 | 0.325787E+09 | 0.236281E+09 | 0.00 | 0.00 |
| March | 0.689156E+09 | 0.572466E+09 | 0.544488E+09 | 0.253277E+09 | 0.291211E+09 | 0.00 | 0.00 |
| April | 0.772101E+09 | 0.456310E+09 | 0.558127E+09 | 0.256618E+09 | 0.301509E+09 | 0.00 | 0.00 |
| May | 0.571268E+09 | 0.427088E+09 | 0.473247E+09 | 0.146603E+09 | 0.326644E+09 | 0.00 | 0.00 |
| June | 0.574806E+09 | 0.313366E+09 | 0.450581E+09 | 0.147368E+09 | 0.303214E+09 | 0.00 | 0.00 |
| July | 0.705413E+09 | 0.277162E+09 | 0.493104E+09 | 0.181899E+09 | 0.311205E+09 | 0.00 | 0.00 |
| August | 0.812521E+09 | 0.294930E+09 | 0.528107E+09 | 0.228936E+09 | 0.299171E+09 | 0.00 | 0.00 |
| September | 0.857624E+09 | 0.337852E+09 | 0.562704E+09 | 0.288990E+09 | 0.273714E+09 | 0.00 | 0.00 |
| October | 0.988863E+09 | 0.385946E+09 | 0.632379E+09 | 0.402780E+09 | 0.229599E+09 | 0.00 | 0.00 |
| November | 0.946088E+09 | 0.539718E+09 | 0.683827E+09 | 0.454625E+09 | 0.229203E+09 | 0.00 | 0.00 |
| December | 0.103909E+10 | 0.610261E+09 | 0.745322E+09 | 0.534355E+09 | 0.210968E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.964863E+10 | 0.533028E+10 | 0.693574E+10 | 0.370226E+10 | 0.323349E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.571268E+09 | 0.277162E+09 | 0.450581E+09 | 0.146603E+09 | 0.210968E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.103909E+10 | 0.610261E+09 | 0.745322E+09 | 0.534355E+09 | 0.326644E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: M NW APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.221528E+09 | 0.596925E+09 | 0.228717E+09 | 72468237.92 | 0.156249E+09 | 0.00 | 0.00 |
| February | 0.228551E+09 | 0.493031E+09 | 0.251083E+09 | 71369157.64 | 0.179714E+09 | 0.00 | 0.00 |
| March | 0.318836E+09 | 0.554340E+09 | 0.327060E+09 | 86794536.43 | 0.240265E+09 | 0.00 | 0.00 |
| April | 0.467243E+09 | 0.444934E+09 | 0.407669E+09 | 0.136733E+09 | 0.270937E+09 | 0.00 | 0.00 |
| May | 0.498302E+09 | 0.408831E+09 | 0.447672E+09 | 0.131781E+09 | 0.315891E+09 | 0.00 | 0.00 |
| June | 0.572141E+09 | 0.302706E+09 | 0.459214E+09 | 0.154405E+09 | 0.304809E+09 | 0.00 | 0.00 |
| July | 0.660311E+09 | 0.270067E+09 | 0.480858E+09 | 0.174750E+09 | 0.306108E+09 | 0.00 | 0.00 |
| August | 0.595355E+09 | 0.287634E+09 | 0.431810E+09 | 0.154878E+09 | 0.276932E+09 | 0.00 | 0.00 |
| September | 0.458775E+09 | 0.334589E+09 | 0.355914E+09 | 0.123844E+09 | 0.232070E+09 | 0.00 | 0.00 |
| October | 0.385360E+09 | 0.388785E+09 | 0.285040E+09 | 0.100062E+09 | 0.184977E+09 | 0.00 | 0.00 |
| November | 0.246478E+09 | 0.537867E+09 | 0.249094E+09 | 83472084.97 | 0.165622E+09 | 0.00 | 0.00 |
| December | 0.218801E+09 | 0.605809E+09 | 0.224781E+09 | 77877952.25 | 0.146903E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.487168E+10 | 0.522552E+10 | 0.414891E+10 | 0.136843E+10 | 0.278048E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.218801E+09 | 0.270067E+09 | 0.224781E+09 | 71369157.64 | 0.146903E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.660311E+09 | 0.605809E+09 | 0.480858E+09 | 0.174750E+09 | 0.315891E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: M SE APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.975720E+09 | 0.603640E+09 | 0.709666E+09 | 0.489896E+09 | 0.219770E+09 | 0.00 | 0.00 |
| February | 0.699504E+09 | 0.501152E+09 | 0.550274E+09 | 0.319392E+09 | 0.230881E+09 | 0.00 | 0.00 |
| March | 0.672916E+09 | 0.558084E+09 | 0.542171E+09 | 0.252992E+09 | 0.289178E+09 | 0.00 | 0.00 |
| April | 0.730845E+09 | 0.445411E+09 | 0.536879E+09 | 0.241663E+09 | 0.295215E+09 | 0.00 | 0.00 |
| May | 0.512209E+09 | 0.416386E+09 | 0.440937E+09 | 0.121471E+09 | 0.319466E+09 | 0.00 | 0.00 |
| June | 0.501964E+09 | 0.313341E+09 | 0.402302E+09 | 0.108419E+09 | 0.293882E+09 | 0.00 | 0.00 |
| July | 0.655161E+09 | 0.279866E+09 | 0.457577E+09 | 0.152923E+09 | 0.304654E+09 | 0.00 | 0.00 |
| August | 0.779918E+09 | 0.289763E+09 | 0.507981E+09 | 0.215355E+09 | 0.292626E+09 | 0.00 | 0.00 |
| September | 0.781384E+09 | 0.336471E+09 | 0.514328E+09 | 0.249381E+09 | 0.264947E+09 | 0.00 | 0.00 |
| October | 0.955619E+09 | 0.379650E+09 | 0.615666E+09 | 0.387902E+09 | 0.227764E+09 | 0.00 | 0.00 |
| November | 0.919534E+09 | 0.535393E+09 | 0.670891E+09 | 0.445478E+09 | 0.225413E+09 | 0.00 | 0.00 |
| December | 0.103396E+10 | 0.606159E+09 | 0.745485E+09 | 0.537618E+09 | 0.207867E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.921873E+10 | 0.526531E+10 | 0.669416E+10 | 0.352249E+10 | 0.317166E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.501964E+09 | 0.279866E+09 | 0.402302E+09 | 0.108419E+09 | 0.207867E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.103396E+10 | 0.606159E+09 | 0.745485E+09 | 0.537618E+09 | 0.319466E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: M NE APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.205119E+09 | 0.570251E+09 | 0.236593E+09 | 81345771.80 | 0.155248E+09 | 0.00 | 0.00 |
| February | 0.195770E+09 | 0.476672E+09 | 0.239288E+09 | 64974608.46 | 0.174314E+09 | 0.00 | 0.00 |
| March | 0.295712E+09 | 0.533309E+09 | 0.324742E+09 | 86509498.24 | 0.238233E+09 | 0.00 | 0.00 |
| April | 0.423046E+09 | 0.431501E+09 | 0.386421E+09 | 0.121778E+09 | 0.264643E+09 | 0.00 | 0.00 |
| May | 0.441309E+09 | 0.400048E+09 | 0.415363E+09 | 0.106649E+09 | 0.308714E+09 | 0.00 | 0.00 |
| June | 0.495752E+09 | 0.299088E+09 | 0.410934E+09 | 0.115457E+09 | 0.295477E+09 | 0.00 | 0.00 |
| July | 0.605630E+09 | 0.268353E+09 | 0.445332E+09 | 0.145774E+09 | 0.299557E+09 | 0.00 | 0.00 |
| August | 0.562009E+09 | 0.281824E+09 | 0.411684E+09 | 0.141297E+09 | 0.270387E+09 | 0.00 | 0.00 |
| September | 0.381695E+09 | 0.332233E+09 | 0.307537E+09 | 84234583.71 | 0.223302E+09 | 0.00 | 0.00 |
| October | 0.344887E+09 | 0.375723E+09 | 0.268327E+09 | 85183840.87 | 0.183143E+09 | 0.00 | 0.00 |
| November | 0.205957E+09 | 0.517653E+09 | 0.236157E+09 | 74325622.94 | 0.161832E+09 | 0.00 | 0.00 |
| December | 0.189342E+09 | 0.577159E+09 | 0.224944E+09 | 81141408.66 | 0.143803E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.434623E+10 | 0.506382E+10 | 0.390732E+10 | 0.118867E+10 | 0.271865E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.189342E+09 | 0.268353E+09 | 0.224944E+09 | 64974608.46 | 0.143803E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.605630E+09 | 0.577159E+09 | 0.445332E+09 | 0.145774E+09 | 0.308714E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: M N1 APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 45687495.91 | 0.382333E+09 | 85027568.61 | 0.00 | 85027568.61 | 0.00 | 0.00 |
| February | 48187420.67 | 0.321961E+09 | 96403407.70 | 0.00 | 96403407.70 | 0.00 | 0.00 |
| March | 84009794.47 | 0.356834E+09 | 0.130807E+09 | 4105.79 | 0.130803E+09 | 0.00 | 0.00 |
| April | 0.113496E+09 | 0.276956E+09 | 0.146218E+09 | 871123.55 | 0.145347E+09 | 0.00 | 0.00 |
| May | 0.150617E+09 | 0.247860E+09 | 0.182204E+09 | 9470778.58 | 0.172733E+09 | 0.00 | 0.00 |
| June | 0.193315E+09 | 0.181748E+09 | 0.186449E+09 | 17985183.97 | 0.168464E+09 | 0.00 | 0.00 |
| July | 0.216662E+09 | 0.161778E+09 | 0.182464E+09 | 15043009.94 | 0.167421E+09 | 0.00 | 0.00 |
| August | 0.174032E+09 | 0.172825E+09 | 0.152292E+09 | 3553362.43 | 0.148739E+09 | 0.00 | 0.00 |
| September | 0.126684E+09 | 0.208275E+09 | 0.124304E+09 | 43830.25 | 0.124260E+09 | 0.00 | 0.00 |
| October | 0.114645E+09 | 0.243149E+09 | 0.101863E+09 | 0.00 | 0.101863E+09 | 0.00 | 0.00 |
| November | 48915423.15 | 0.347946E+09 | 89254512.61 | 0.00 | 89254512.61 | 0.00 | 0.00 |
| December | 38455888.82 | 0.393155E+09 | 79153413.08 | 0.00 | 79153413.08 | 0.00 | 0.00 |
| Annual Sum or Average | 0.135471E+10 | 0.329482E+10 | 0.155644E+10 | 46971394.51 | 0.150947E+10 | 0.00 | 0.00 |
| Minimum of Months | 38455888.82 | 0.161778E+09 | 79153413.08 | 0.00 | 79153413.08 | 0.00 | 0.00 |
| Maximum of Months | 0.216662E+09 | 0.393155E+09 | 0.186449E+09 | 17985183.97 | 0.172733E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: M N2 APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 45529360.97 | 0.382592E+09 | 85027568.61 | 0.00 | 85027568.61 | 0.00 | 0.00 |
| February | 48136076.25 | 0.321797E+09 | 96403407.70 | 0.00 | 96403407.70 | 0.00 | 0.00 |
| March | 83902678.18 | 0.356745E+09 | 0.130807E+09 | 4105.79 | 0.130803E+09 | 0.00 | 0.00 |
| April | 0.113389E+09 | 0.276927E+09 | 0.146218E+09 | 871123.55 | 0.145347E+09 | 0.00 | 0.00 |
| May | 0.150572E+09 | 0.247793E+09 | 0.182204E+09 | 9470778.58 | 0.172733E+09 | 0.00 | 0.00 |
| June | 0.193306E+09 | 0.181691E+09 | 0.186449E+09 | 17985183.97 | 0.168464E+09 | 0.00 | 0.00 |
| July | 0.216636E+09 | 0.161726E+09 | 0.182464E+09 | 15043009.94 | 0.167421E+09 | 0.00 | 0.00 |
| August | 0.173992E+09 | 0.172777E+09 | 0.152292E+09 | 3553362.43 | 0.148739E+09 | 0.00 | 0.00 |
| September | 0.126674E+09 | 0.208190E+09 | 0.124304E+09 | 43830.25 | 0.124260E+09 | 0.00 | 0.00 |
| October | 0.114598E+09 | 0.243115E+09 | 0.101863E+09 | 0.00 | 0.101863E+09 | 0.00 | 0.00 |
| November | 48863708.12 | 0.347781E+09 | 89254512.61 | 0.00 | 89254512.61 | 0.00 | 0.00 |
| December | 38368043.86 | 0.393155E+09 | 79153413.08 | 0.00 | 79153413.08 | 0.00 | 0.00 |
| Annual Sum or Average | 0.135397E+10 | 0.329429E+10 | 0.155644E+10 | 46971394.51 | 0.150947E+10 | 0.00 | 0.00 |
| Minimum of Months | 38368043.86 | 0.161726E+09 | 79153413.08 | 0.00 | 79153413.08 | 0.00 | 0.00 |
| Maximum of Months | 0.216636E+09 | 0.393155E+09 | 0.186449E+09 | 17985183.97 | 0.172733E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: M S1 APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.810746E+09 | 0.375707E+09 | 0.558100E+09 | 0.408550E+09 | 0.149550E+09 | 0.00 | 0.00 |
| February | 0.552183E+09 | 0.317055E+09 | 0.407389E+09 | 0.254418E+09 | 0.152971E+09 | 0.00 | 0.00 |
| March | 0.461699E+09 | 0.362515E+09 | 0.348235E+09 | 0.166487E+09 | 0.181748E+09 | 0.00 | 0.00 |
| April | 0.425878E+09 | 0.287403E+09 | 0.296676E+09 | 0.120757E+09 | 0.175919E+09 | 0.00 | 0.00 |
| May | 0.230277E+09 | 0.271997E+09 | 0.207778E+09 | 24292585.19 | 0.183485E+09 | 0.00 | 0.00 |
| June | 0.202092E+09 | 0.198757E+09 | 0.177817E+09 | 10947826.02 | 0.166869E+09 | 0.00 | 0.00 |
| July | 0.267640E+09 | 0.174296E+09 | 0.194710E+09 | 22191625.47 | 0.172518E+09 | 0.00 | 0.00 |
| August | 0.396138E+09 | 0.182377E+09 | 0.248589E+09 | 77611251.15 | 0.170978E+09 | 0.00 | 0.00 |
| September | 0.528573E+09 | 0.208972E+09 | 0.331094E+09 | 0.165190E+09 | 0.165904E+09 | 0.00 | 0.00 |
| October | 0.722820E+09 | 0.234349E+09 | 0.449202E+09 | 0.302718E+09 | 0.146484E+09 | 0.00 | 0.00 |
| November | 0.760266E+09 | 0.330964E+09 | 0.523988E+09 | 0.371153E+09 | 0.152836E+09 | 0.00 | 0.00 |
| December | 0.877747E+09 | 0.375462E+09 | 0.599695E+09 | 0.456477E+09 | 0.143218E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.623606E+10 | 0.331985E+10 | 0.434327E+10 | 0.238079E+10 | 0.196248E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.202092E+09 | 0.174296E+09 | 0.177817E+09 | 10947826.02 | 0.143218E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.877747E+09 | 0.375707E+09 | 0.599695E+09 | 0.456477E+09 | 0.183485E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: M S2 APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.810638E+09 | 0.375810E+09 | 0.558100E+09 | 0.408550E+09 | 0.149550E+09 | 0.00 | 0.00 |
| February | 0.552165E+09 | 0.316968E+09 | 0.407389E+09 | 0.254418E+09 | 0.152971E+09 | 0.00 | 0.00 |
| March | 0.461637E+09 | 0.362463E+09 | 0.348235E+09 | 0.166487E+09 | 0.181748E+09 | 0.00 | 0.00 |
| April | 0.425809E+09 | 0.287362E+09 | 0.296676E+09 | 0.120757E+09 | 0.175919E+09 | 0.00 | 0.00 |
| May | 0.230225E+09 | 0.271926E+09 | 0.207778E+09 | 24292585.19 | 0.183485E+09 | 0.00 | 0.00 |
| June | 0.202072E+09 | 0.198689E+09 | 0.177817E+09 | 10947826.02 | 0.166869E+09 | 0.00 | 0.00 |
| July | 0.267607E+09 | 0.174234E+09 | 0.194710E+09 | 22191625.47 | 0.172518E+09 | 0.00 | 0.00 |
| August | 0.396097E+09 | 0.182327E+09 | 0.248589E+09 | 77611251.15 | 0.170978E+09 | 0.00 | 0.00 |
| September | 0.528564E+09 | 0.208906E+09 | 0.331094E+09 | 0.165190E+09 | 0.165904E+09 | 0.00 | 0.00 |
| October | 0.722795E+09 | 0.234313E+09 | 0.449202E+09 | 0.302718E+09 | 0.146484E+09 | 0.00 | 0.00 |
| November | 0.760242E+09 | 0.330918E+09 | 0.523988E+09 | 0.371153E+09 | 0.152836E+09 | 0.00 | 0.00 |
| December | 0.877706E+09 | 0.375437E+09 | 0.599695E+09 | 0.456477E+09 | 0.143218E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.623556E+10 | 0.331935E+10 | 0.434327E+10 | 0.238079E+10 | 0.196248E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.202072E+09 | 0.174234E+09 | 0.177817E+09 | 10947826.02 | 0.143218E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.877706E+09 | 0.375810E+09 | 0.599695E+09 | 0.456477E+09 | 0.183485E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: T SW APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.981533E+09 | 0.541001E+09 | 0.701790E+09 | 0.481019E+09 | 0.220771E+09 | 0.00 | 0.00 |
| February | 0.739396E+09 | 0.436399E+09 | 0.562068E+09 | 0.325787E+09 | 0.236281E+09 | 0.00 | 0.00 |
| March | 0.703842E+09 | 0.502295E+09 | 0.544488E+09 | 0.253277E+09 | 0.291211E+09 | 0.00 | 0.00 |
| April | 0.777064E+09 | 0.402279E+09 | 0.558127E+09 | 0.256618E+09 | 0.301509E+09 | 0.00 | 0.00 |
| May | 0.582387E+09 | 0.373369E+09 | 0.473247E+09 | 0.146603E+09 | 0.326644E+09 | 0.00 | 0.00 |
| June | 0.572084E+09 | 0.285827E+09 | 0.450581E+09 | 0.147368E+09 | 0.303214E+09 | 0.00 | 0.00 |
| July | 0.692112E+09 | 0.261577E+09 | 0.493104E+09 | 0.181899E+09 | 0.311205E+09 | 0.00 | 0.00 |
| August | 0.798766E+09 | 0.278027E+09 | 0.528107E+09 | 0.228936E+09 | 0.299171E+09 | 0.00 | 0.00 |
| September | 0.850540E+09 | 0.310965E+09 | 0.562704E+09 | 0.288990E+09 | 0.273714E+09 | 0.00 | 0.00 |
| October | 0.988661E+09 | 0.349906E+09 | 0.632379E+09 | 0.402780E+09 | 0.229599E+09 | 0.00 | 0.00 |
| November | 0.961729E+09 | 0.471398E+09 | 0.683827E+09 | 0.454625E+09 | 0.229203E+09 | 0.00 | 0.00 |
| December | 0.105482E+10 | 0.536307E+09 | 0.745322E+09 | 0.534355E+09 | 0.210968E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.970294E+10 | 0.474935E+10 | 0.693574E+10 | 0.370226E+10 | 0.323349E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.572084E+09 | 0.261577E+09 | 0.450581E+09 | 0.146603E+09 | 0.210968E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.105482E+10 | 0.541001E+09 | 0.745322E+09 | 0.534355E+09 | 0.326644E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: T NW APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.234039E+09 | 0.534948E+09 | 0.228717E+09 | 72468237.92 | 0.156249E+09 | 0.00 | 0.00 |
| February | 0.245206E+09 | 0.428745E+09 | 0.251083E+09 | 71369157.64 | 0.179714E+09 | 0.00 | 0.00 |
| March | 0.332457E+09 | 0.492836E+09 | 0.327060E+09 | 86794536.43 | 0.240265E+09 | 0.00 | 0.00 |
| April | 0.478047E+09 | 0.389328E+09 | 0.407669E+09 | 0.136733E+09 | 0.270937E+09 | 0.00 | 0.00 |
| May | 0.513118E+09 | 0.358346E+09 | 0.447672E+09 | 0.131781E+09 | 0.315891E+09 | 0.00 | 0.00 |
| June | 0.570499E+09 | 0.278072E+09 | 0.459214E+09 | 0.154405E+09 | 0.304809E+09 | 0.00 | 0.00 |
| July | 0.648246E+09 | 0.256065E+09 | 0.480858E+09 | 0.174750E+09 | 0.306108E+09 | 0.00 | 0.00 |
| August | 0.584949E+09 | 0.270582E+09 | 0.431810E+09 | 0.154878E+09 | 0.276932E+09 | 0.00 | 0.00 |
| September | 0.457747E+09 | 0.304250E+09 | 0.355914E+09 | 0.123844E+09 | 0.232070E+09 | 0.00 | 0.00 |
| October | 0.391453E+09 | 0.345090E+09 | 0.285040E+09 | 0.100062E+09 | 0.184977E+09 | 0.00 | 0.00 |
| November | 0.267740E+09 | 0.457923E+09 | 0.249094E+09 | 83472084.97 | 0.165622E+09 | 0.00 | 0.00 |
| December | 0.234183E+09 | 0.532302E+09 | 0.224781E+09 | 77877952.25 | 0.146903E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.495768E+10 | 0.464849E+10 | 0.414891E+10 | 0.136843E+10 | 0.278048E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.234039E+09 | 0.256065E+09 | 0.224781E+09 | 71369157.64 | 0.146903E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.648246E+09 | 0.534948E+09 | 0.480858E+09 | 0.174750E+09 | 0.315891E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: T SE APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.987947E+09 | 0.536163E+09 | 0.709666E+09 | 0.489896E+09 | 0.219770E+09 | 0.00 | 0.00 |
| February | 0.715754E+09 | 0.431017E+09 | 0.550274E+09 | 0.319392E+09 | 0.230881E+09 | 0.00 | 0.00 |
| March | 0.689535E+09 | 0.490721E+09 | 0.542171E+09 | 0.252992E+09 | 0.289178E+09 | 0.00 | 0.00 |
| April | 0.738318E+09 | 0.394129E+09 | 0.536879E+09 | 0.241663E+09 | 0.295215E+09 | 0.00 | 0.00 |
| May | 0.526835E+09 | 0.365668E+09 | 0.440937E+09 | 0.121471E+09 | 0.319466E+09 | 0.00 | 0.00 |
| June | 0.501872E+09 | 0.286257E+09 | 0.402302E+09 | 0.108419E+09 | 0.293882E+09 | 0.00 | 0.00 |
| July | 0.643481E+09 | 0.264108E+09 | 0.457577E+09 | 0.152923E+09 | 0.304654E+09 | 0.00 | 0.00 |
| August | 0.767830E+09 | 0.273532E+09 | 0.507981E+09 | 0.215355E+09 | 0.292626E+09 | 0.00 | 0.00 |
| September | 0.776133E+09 | 0.309453E+09 | 0.514328E+09 | 0.249381E+09 | 0.264947E+09 | 0.00 | 0.00 |
| October | 0.956163E+09 | 0.344372E+09 | 0.615666E+09 | 0.387902E+09 | 0.227764E+09 | 0.00 | 0.00 |
| November | 0.934925E+09 | 0.467012E+09 | 0.670891E+09 | 0.445478E+09 | 0.225413E+09 | 0.00 | 0.00 |
| December | 0.104910E+10 | 0.532062E+09 | 0.745485E+09 | 0.537618E+09 | 0.207867E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.928789E+10 | 0.469449E+10 | 0.669416E+10 | 0.352249E+10 | 0.317166E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.501872E+09 | 0.264108E+09 | 0.402302E+09 | 0.108419E+09 | 0.207867E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.104910E+10 | 0.536163E+09 | 0.745485E+09 | 0.537618E+09 | 0.319466E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: T NE APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.222493E+09 | 0.510319E+09 | 0.236593E+09 | 81345771.80 | 0.155248E+09 | 0.00 | 0.00 |
| February | 0.214857E+09 | 0.414212E+09 | 0.239288E+09 | 64974608.46 | 0.174314E+09 | 0.00 | 0.00 |
| March | 0.312452E+09 | 0.474998E+09 | 0.324742E+09 | 86509498.24 | 0.238233E+09 | 0.00 | 0.00 |
| April | 0.436223E+09 | 0.377378E+09 | 0.386421E+09 | 0.121778E+09 | 0.264643E+09 | 0.00 | 0.00 |
| May | 0.458010E+09 | 0.351173E+09 | 0.415363E+09 | 0.106649E+09 | 0.308714E+09 | 0.00 | 0.00 |
| June | 0.494991E+09 | 0.273445E+09 | 0.410934E+09 | 0.115457E+09 | 0.295477E+09 | 0.00 | 0.00 |
| July | 0.593931E+09 | 0.252847E+09 | 0.445332E+09 | 0.145774E+09 | 0.299557E+09 | 0.00 | 0.00 |
| August | 0.552653E+09 | 0.264676E+09 | 0.411684E+09 | 0.141297E+09 | 0.270387E+09 | 0.00 | 0.00 |
| September | 0.382498E+09 | 0.301032E+09 | 0.307537E+09 | 84234583.71 | 0.223302E+09 | 0.00 | 0.00 |
| October | 0.354622E+09 | 0.334754E+09 | 0.268327E+09 | 85183840.87 | 0.183143E+09 | 0.00 | 0.00 |
| November | 0.231920E+09 | 0.441127E+09 | 0.236157E+09 | 74325622.94 | 0.161832E+09 | 0.00 | 0.00 |
| December | 0.209823E+09 | 0.507065E+09 | 0.224944E+09 | 81141408.66 | 0.143803E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.446447E+10 | 0.450303E+10 | 0.390732E+10 | 0.118867E+10 | 0.271865E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.209823E+09 | 0.252847E+09 | 0.224944E+09 | 64974608.46 | 0.143803E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.593931E+09 | 0.510319E+09 | 0.445332E+09 | 0.145774E+09 | 0.308714E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: T N1 APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 55348930.88 | 0.337683E+09 | 85027568.61 | 0.00 | 85027568.61 | 0.00 | 0.00 |
| February | 61616093.74 | 0.270608E+09 | 96403407.70 | 0.00 | 96403407.70 | 0.00 | 0.00 |
| March | 96484621.73 | 0.311449E+09 | 0.130807E+09 | 4105.79 | 0.130803E+09 | 0.00 | 0.00 |
| April | 0.121933E+09 | 0.243833E+09 | 0.146218E+09 | 871123.55 | 0.145347E+09 | 0.00 | 0.00 |
| May | 0.161962E+09 | 0.220956E+09 | 0.182204E+09 | 9470778.58 | 0.172733E+09 | 0.00 | 0.00 |
| June | 0.193069E+09 | 0.170692E+09 | 0.186449E+09 | 17985183.97 | 0.168464E+09 | 0.00 | 0.00 |
| July | 0.210802E+09 | 0.155781E+09 | 0.182464E+09 | 15043009.94 | 0.167421E+09 | 0.00 | 0.00 |
| August | 0.169238E+09 | 0.165805E+09 | 0.152292E+09 | 3553362.43 | 0.148739E+09 | 0.00 | 0.00 |
| September | 0.126927E+09 | 0.193660E+09 | 0.124304E+09 | 43830.25 | 0.124260E+09 | 0.00 | 0.00 |
| October | 0.119347E+09 | 0.218557E+09 | 0.101863E+09 | 0.00 | 0.101863E+09 | 0.00 | 0.00 |
| November | 63644980.52 | 0.290619E+09 | 89254512.61 | 0.00 | 89254512.61 | 0.00 | 0.00 |
| December | 50043458.07 | 0.336482E+09 | 79153413.08 | 0.00 | 79153413.08 | 0.00 | 0.00 |
| Annual Sum or Average | 0.143042E+10 | 0.291613E+10 | 0.155644E+10 | 46971394.51 | 0.150947E+10 | 0.00 | 0.00 |
| Minimum of Months | 50043458.07 | 0.155781E+09 | 79153413.08 | 0.00 | 79153413.08 | 0.00 | 0.00 |
| Maximum of Months | 0.210802E+09 | 0.337683E+09 | 0.186449E+09 | 17985183.97 | 0.172733E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: T N2 APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 55044197.25 | 0.337580E+09 | 85027568.61 | 0.00 | 85027568.61 | 0.00 | 0.00 |
| February | 61361411.95 | 0.270282E+09 | 96403407.70 | 0.00 | 96403407.70 | 0.00 | 0.00 |
| March | 96084225.87 | 0.311253E+09 | 0.130807E+09 | 4105.79 | 0.130803E+09 | 0.00 | 0.00 |
| April | 0.121539E+09 | 0.243418E+09 | 0.146218E+09 | 871123.55 | 0.145347E+09 | 0.00 | 0.00 |
| May | 0.161693E+09 | 0.220621E+09 | 0.182204E+09 | 9470778.58 | 0.172733E+09 | 0.00 | 0.00 |
| June | 0.193000E+09 | 0.170437E+09 | 0.186449E+09 | 17985183.97 | 0.168464E+09 | 0.00 | 0.00 |
| July | 0.210727E+09 | 0.155580E+09 | 0.182464E+09 | 15043009.94 | 0.167421E+09 | 0.00 | 0.00 |
| August | 0.169107E+09 | 0.165596E+09 | 0.152292E+09 | 3553362.43 | 0.148739E+09 | 0.00 | 0.00 |
| September | 0.126854E+09 | 0.193262E+09 | 0.124304E+09 | 43830.25 | 0.124260E+09 | 0.00 | 0.00 |
| October | 0.119123E+09 | 0.218307E+09 | 0.101863E+09 | 0.00 | 0.101863E+09 | 0.00 | 0.00 |
| November | 63377713.48 | 0.290191E+09 | 89254512.61 | 0.00 | 89254512.61 | 0.00 | 0.00 |
| December | 49766900.70 | 0.336255E+09 | 79153413.08 | 0.00 | 79153413.08 | 0.00 | 0.00 |
| Annual Sum or Average | 0.142768E+10 | 0.291278E+10 | 0.155644E+10 | 46971394.51 | 0.150947E+10 | 0.00 | 0.00 |
| Minimum of Months | 49766900.70 | 0.155580E+09 | 79153413.08 | 0.00 | 79153413.08 | 0.00 | 0.00 |
| Maximum of Months | 0.210727E+09 | 0.337580E+09 | 0.186449E+09 | 17985183.97 | 0.172733E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: T S1 APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.820785E+09 | 0.335325E+09 | 0.558100E+09 | 0.408550E+09 | 0.149550E+09 | 0.00 | 0.00 |
| February | 0.564887E+09 | 0.272000E+09 | 0.407389E+09 | 0.254418E+09 | 0.152971E+09 | 0.00 | 0.00 |
| March | 0.474285E+09 | 0.316689E+09 | 0.348235E+09 | 0.166487E+09 | 0.181748E+09 | 0.00 | 0.00 |
| April | 0.430019E+09 | 0.257883E+09 | 0.296676E+09 | 0.120757E+09 | 0.175919E+09 | 0.00 | 0.00 |
| May | 0.237824E+09 | 0.241874E+09 | 0.207778E+09 | 24292585.19 | 0.183485E+09 | 0.00 | 0.00 |
| June | 0.201384E+09 | 0.185855E+09 | 0.177817E+09 | 10947826.02 | 0.166869E+09 | 0.00 | 0.00 |
| July | 0.261494E+09 | 0.167689E+09 | 0.194710E+09 | 22191625.47 | 0.172518E+09 | 0.00 | 0.00 |
| August | 0.389399E+09 | 0.175455E+09 | 0.248589E+09 | 77611251.15 | 0.170978E+09 | 0.00 | 0.00 |
| September | 0.524951E+09 | 0.196818E+09 | 0.331094E+09 | 0.165190E+09 | 0.165904E+09 | 0.00 | 0.00 |
| October | 0.722932E+09 | 0.216866E+09 | 0.449202E+09 | 0.302718E+09 | 0.146484E+09 | 0.00 | 0.00 |
| November | 0.770213E+09 | 0.293812E+09 | 0.523988E+09 | 0.371153E+09 | 0.152836E+09 | 0.00 | 0.00 |
| December | 0.888986E+09 | 0.332664E+09 | 0.599695E+09 | 0.456477E+09 | 0.143218E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.628716E+10 | 0.299293E+10 | 0.434327E+10 | 0.238079E+10 | 0.196248E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.201384E+09 | 0.167689E+09 | 0.177817E+09 | 10947826.02 | 0.143218E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.888986E+09 | 0.335325E+09 | 0.599695E+09 | 0.456477E+09 | 0.183485E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: T S2 APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.820533E+09 | 0.335262E+09 | 0.558100E+09 | 0.408550E+09 | 0.149550E+09 | 0.00 | 0.00 |
| February | 0.564694E+09 | 0.271804E+09 | 0.407389E+09 | 0.254418E+09 | 0.152971E+09 | 0.00 | 0.00 |
| March | 0.473986E+09 | 0.316508E+09 | 0.348235E+09 | 0.166487E+09 | 0.181748E+09 | 0.00 | 0.00 |
| April | 0.429718E+09 | 0.257584E+09 | 0.296676E+09 | 0.120757E+09 | 0.175919E+09 | 0.00 | 0.00 |
| May | 0.237550E+09 | 0.241501E+09 | 0.207778E+09 | 24292585.19 | 0.183485E+09 | 0.00 | 0.00 |
| June | 0.201279E+09 | 0.185530E+09 | 0.177817E+09 | 10947826.02 | 0.166869E+09 | 0.00 | 0.00 |
| July | 0.261386E+09 | 0.167451E+09 | 0.194710E+09 | 22191625.47 | 0.172518E+09 | 0.00 | 0.00 |
| August | 0.389267E+09 | 0.175260E+09 | 0.248589E+09 | 77611251.15 | 0.170978E+09 | 0.00 | 0.00 |
| September | 0.524899E+09 | 0.196561E+09 | 0.331094E+09 | 0.165190E+09 | 0.165904E+09 | 0.00 | 0.00 |
| October | 0.722808E+09 | 0.216725E+09 | 0.449202E+09 | 0.302718E+09 | 0.146484E+09 | 0.00 | 0.00 |
| November | 0.770021E+09 | 0.293608E+09 | 0.523988E+09 | 0.371153E+09 | 0.152836E+09 | 0.00 | 0.00 |
| December | 0.888784E+09 | 0.332522E+09 | 0.599695E+09 | 0.456477E+09 | 0.143218E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.628492E+10 | 0.299032E+10 | 0.434327E+10 | 0.238079E+10 | 0.196248E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.201279E+09 | 0.167451E+09 | 0.177817E+09 | 10947826.02 | 0.143218E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.888784E+09 | 0.335262E+09 | 0.599695E+09 | 0.456477E+09 | 0.183485E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: T CORRIDOR
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 43412861.63 | 56188066.21 | 36368815.61 | 19519249.05 | 16849566.56 | 0.00 | 0.00 |
| February | 38023358.28 | 46014687.36 | 34285857.39 | 15590921.77 | 18694935.62 | 0.00 | 0.00 |
| March | 54326009.44 | 51555971.18 | 46535560.13 | 20757321.03 | 25778239.10 | 0.00 | 0.00 |
| April | 76407274.74 | 42061296.27 | 57637664.23 | 29012075.86 | 28625588.37 | 0.00 | 0.00 |
| May | 70493474.49 | 39883465.11 | 55947388.00 | 23318309.45 | 32629078.56 | 0.00 | 0.00 |
| June | 71511509.63 | 32019434.91 | 53866036.62 | 23388691.01 | 30477345.60 | 0.00 | 0.00 |
| July | 90910459.74 | 29717499.80 | 63076129.53 | 31369520.18 | 31706609.35 | 0.00 | 0.00 |
| August | 90699467.31 | 30539358.64 | 62242017.08 | 33052100.77 | 29189916.31 | 0.00 | 0.00 |
| September | 60216058.89 | 34259427.23 | 43967562.18 | 20201913.98 | 23765648.19 | 0.00 | 0.00 |
| October | 56729501.39 | 38387446.89 | 39943681.08 | 20440209.35 | 19503471.73 | 0.00 | 0.00 |
| November | 42045251.97 | 49747002.77 | 35249938.61 | 17834735.76 | 17415202.85 | 0.00 | 0.00 |
| December | 41697699.23 | 55984634.81 | 34983076.64 | 19470211.29 | 15512865.36 | 0.00 | 0.00 |
| Annual Sum or Average | 0.736473E+09 | 0.506358E+09 | 0.564104E+09 | 0.273955E+09 | 0.290148E+09 | 0.00 | 0.00 |
| Minimum of Months | 38023358.28 | 29717499.80 | 34285857.39 | 15590921.77 | 15512865.36 | 0.00 | 0.00 |
| Maximum of Months | 90910459.74 | 56188066.21 | 63076129.53 | 33052100.77 | 32629078.56 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: G CORRIDOR
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.129447E+09 | 0.166326E+09 | 0.108315E+09 | 58133181.30 | 50182202.46 | 0.00 | 0.00 |
| February | 0.115092E+09 | 0.134301E+09 | 0.102112E+09 | 46433645.05 | 55678170.75 | 0.00 | 0.00 |
| March | 0.167516E+09 | 0.145715E+09 | 0.138594E+09 | 61820467.77 | 76774011.29 | 0.00 | 0.00 |
| April | 0.233337E+09 | 0.119216E+09 | 0.171659E+09 | 86405181.96 | 85254126.03 | 0.00 | 0.00 |
| May | 0.214266E+09 | 0.115371E+09 | 0.166625E+09 | 69447728.60 | 97177516.13 | 0.00 | 0.00 |
| June | 0.218554E+09 | 91565803.75 | 0.160426E+09 | 69657342.43 | 90769119.90 | 0.00 | 0.00 |
| July | 0.274967E+09 | 87772350.98 | 0.187856E+09 | 93426237.82 | 94430173.25 | 0.00 | 0.00 |
| August | 0.273401E+09 | 90649937.94 | 0.185372E+09 | 98437381.56 | 86934835.07 | 0.00 | 0.00 |
| September | 0.180583E+09 | 0.101933E+09 | 0.130946E+09 | 60166327.35 | 70780014.72 | 0.00 | 0.00 |
| October | 0.165925E+09 | 0.118476E+09 | 0.118962E+09 | 60876030.26 | 58086192.50 | 0.00 | 0.00 |
| November | 0.122343E+09 | 0.153105E+09 | 0.104983E+09 | 53116281.50 | 51866808.11 | 0.00 | 0.00 |
| December | 0.122620E+09 | 0.169804E+09 | 0.104188E+09 | 57987134.63 | 46201173.62 | 0.00 | 0.00 |
| Annual Sum or Average | 0.221805E+10 | 0.149423E+10 | 0.168004E+10 | 0.815907E+09 | 0.864134E+09 | 0.00 | 0.00 |
| Minimum of Months | 0.115092E+09 | 87772350.98 | 0.102112E+09 | 46433645.05 | 46201173.62 | 0.00 | 0.00 |
| Maximum of Months | 0.274967E+09 | 0.169804E+09 | 0.187856E+09 | 98437381.56 | 97177516.13 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: M CORRIDOR
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 39622705.36 | 63984002.04 | 36368815.61 | 19519249.05 | 16849566.56 | 0.00 | 0.00 |
| February | 34230588.55 | 54273297.27 | 34285857.39 | 15590921.77 | 18694935.62 | 0.00 | 0.00 |
| March | 50132654.08 | 59209857.60 | 46535560.13 | 20757321.03 | 25778239.10 | 0.00 | 0.00 |
| April | 72937112.80 | 47265937.70 | 57637664.23 | 29012075.86 | 28625588.37 | 0.00 | 0.00 |
| May | 66555933.78 | 44775080.67 | 55947388.00 | 23318309.45 | 32629078.56 | 0.00 | 0.00 |
| June | 69744039.54 | 34559732.31 | 53866036.62 | 23388691.01 | 30477345.60 | 0.00 | 0.00 |
| July | 90337890.57 | 31376158.37 | 63076129.53 | 31369520.18 | 31706609.35 | 0.00 | 0.00 |
| August | 90062279.65 | 32301689.46 | 62242017.08 | 33052100.77 | 29189916.31 | 0.00 | 0.00 |
| September | 58780367.62 | 37201479.41 | 43967562.18 | 20201913.98 | 23765648.19 | 0.00 | 0.00 |
| October | 54306091.58 | 42343506.09 | 39943681.08 | 20440209.35 | 19503471.73 | 0.00 | 0.00 |
| November | 37750021.89 | 57958925.95 | 35249938.61 | 17834735.76 | 17415202.85 | 0.00 | 0.00 |
| December | 37590712.83 | 64919584.45 | 34983076.64 | 19470211.29 | 15512865.36 | 0.00 | 0.00 |
| Annual Sum or Average | 0.702050E+09 | 0.570169E+09 | 0.564104E+09 | 0.273955E+09 | 0.290148E+09 | 0.00 | 0.00 |
| Minimum of Months | 34230588.55 | 31376158.37 | 34285857.39 | 15590921.77 | 15512865.36 | 0.00 | 0.00 |
| Maximum of Months | 90337890.57 | 64919584.45 | 63076129.53 | 33052100.77 | 32629078.56 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
| January | 13.22 | 9.61 | 5.99 | 2.23 | 0.81 | 45.19 | 208.20 | 0.00 |
| February | 13.28 | 10.20 | 7.03 | 3.12 | 2.96 | 66.07 | 175.60 | 0.04 |
| March | 12.64 | 10.61 | 8.97 | 2.93 | 3.55 | 84.90 | 179.28 | 0.03 |
| April | 15.30 | 12.62 | 10.61 | 2.62 | 4.76 | 81.20 | 282.81 | 0.02 |
| May | 15.56 | 12.65 | 10.56 | 2.92 | 6.17 | 105.80 | 234.18 | 0.01 |
| June | 17.67 | 14.80 | 13.02 | 2.53 | 9.03 | 98.05 | 261.27 | 0.00 |
| July | 19.43 | 16.76 | 15.28 | 2.35 | 9.62 | 86.54 | 312.15 | 0.00 |
| August | 19.66 | 17.23 | 15.95 | 2.55 | 9.62 | 74.58 | 307.55 | 0.00 |
| September | 18.47 | 15.50 | 13.65 | 2.19 | 8.99 | 70.75 | 240.05 | 0.00 |
| October | 18.77 | 13.72 | 9.60 | 2.71 | 7.74 | 53.88 | 216.36 | 0.00 |
| November | 14.32 | 10.43 | 6.22 | 2.47 | 2.41 | 50.75 | 207.87 | 0.01 |
| December | 13.59 | 8.82 | 3.19 | 2.50 | 0.05 | 39.49 | 221.83 | 0.00 |
| Annual Sum or Average | 16.01 | 12.76 | 10.02 | 2.59 | 5.49 | 71.44 | 237.65 | 0.01 |
| Minimum of Months | 12.64 | 8.82 | 3.19 | 2.19 | 0.05 | 39.49 | 175.60 | 0.00 |
| Maximum of Months | 19.66 | 17.23 | 15.95 | 3.12 | 9.62 | 105.80 | 312.15 | 0.04 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
| January | 26.00 | 13-JAN-13:00 | 15.46 | 8.00 | 3.10 | 11.84 | 120.00 | 725.00 |
| February | 26.00 | 01-FEB-11:00 | 14.67 | 6.00 | 4.10 | 10.11 | 166.00 | 715.50 |
| March | 24.00 | 11-MAR-10:00 | 13.82 | 6.00 | 2.60 | 8.15 | 120.00 | 907.00 |
| April | 27.00 | 26-APR-12:00 | 17.13 | 11.00 | 4.10 | 12.22 | 159.00 | 884.00 |
| May | 24.00 | 03-MAY-11:00 | 15.05 | 9.00 | 4.10 | 12.98 | 187.00 | 842.50 |
| June | 25.00 | 29-JUN-10:00 | 19.59 | 17.00 | 4.60 | 11.65 | 177.50 | 829.00 |
| July | 28.00 | 19-JUL-10:00 | 20.49 | 17.00 | 3.60 | 14.65 | 173.00 | 813.00 |
| August | 28.00 | 14-AUG-10:00 | 21.19 | 18.00 | 3.60 | 14.84 | 148.00 | 840.00 |
| September | 36.00 | 29-SEP-10:00 | 17.91 | 5.00 | 3.60 | 19.35 | 159.50 | 790.00 |
| October | 37.00 | 16-OCT-10:00 | 17.87 | 4.00 | 5.70 | 20.05 | 122.00 | 871.50 |
| November | 27.00 | 19-NOV-12:00 | 14.96 | 6.00 | 4.10 | 11.07 | 128.50 | 796.00 |
| December | 26.00 | 05-DEC-09:00 | 13.09 | 1.00 | 3.60 | 8.94 | 75.50 | 857.00 |
| Annual Sum or Average | ||||||||
| Minimum of Months | 24.00 | 13.09 | 1.00 | 2.60 | 8.15 | 75.50 | 715.50 | |
| Maximum of Months | 37.00 | 21.19 | 18.00 | 5.70 | 20.05 | 187.00 | 907.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
| January | 1.00 | 08-JAN-06:00 | -0.3 | -2.0 | 3.10 | -15.5 | 11.50 | 193.50 |
| February | 5.00 | 04-FEB-05:00 | 0.22 | -8.0 | 4.10 | -10.9 | 0.00 | 0.00 |
| March | 4.00 | 07-MAR-04:00 | 3.53 | 3.00 | 0.00 | -11.4 | 0.00 | 0.00 |
| April | 7.00 | 01-APR-05:00 | 4.33 | 1.00 | 4.10 | -9.0 | 23.50 | 211.00 |
| May | 8.00 | 14-MAY-03:00 | 7.45 | 7.00 | 1.50 | -6.6 | 0.00 | 0.00 |
| June | 11.00 | 13-JUN-03:00 | 9.85 | 9.00 | 2.10 | -3.4 | 0.00 | 0.00 |
| July | 13.00 | 06-JUL-00:00 | 13.00 | 13.00 | 0.00 | -0.6 | 0.00 | 0.00 |
| August | 14.00 | 24-AUG-01:00 | 14.00 | 14.00 | 0.00 | 0.51 | 0.00 | 0.00 |
| September | 11.00 | 20-SEP-02:00 | 9.85 | 9.00 | 1.50 | -3.4 | 0.00 | 0.00 |
| October | 9.00 | 12-OCT-04:00 | 6.56 | 4.00 | 3.10 | -6.4 | 0.00 | 0.00 |
| November | 7.00 | 05-NOV-01:00 | 5.54 | 4.00 | 3.10 | -8.3 | 0.00 | 0.00 |
| December | 5.00 | 03-DEC-00:00 | 5.00 | 5.00 | 2.10 | -0.4 | 0.00 | 0.00 |
| Annual Sum or Average | ||||||||
| Minimum of Months | 1.00 | -0.3 | -8.0 | 0.00 | -15.5 | 0.00 | 0.00 | |
| Maximum of Months | 14.00 | 14.00 | 14.00 | 4.10 | 0.51 | 23.50 | 211.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| SITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
| January | 17.04 | 17-JAN-11:00 | 24.00 | 13.00 | 3.10 | 12.79 | 223.50 | 9.00 |
| February | 16.80 | 11-FEB-13:00 | 18.00 | 16.20 | 1.10 | 15.02 | 241.00 | 12.50 |
| March | 17.41 | 22-MAR-12:00 | 22.00 | 15.00 | 3.10 | 8.35 | 145.50 | 876.00 |
| April | 18.33 | 26-APR-10:00 | 26.00 | 14.00 | 4.10 | 12.03 | 141.50 | 915.50 |
| May | 16.69 | 05-MAY-14:00 | 18.00 | 16.00 | 5.10 | 8.74 | 303.50 | 269.00 |
| June | 19.59 | 29-JUN-10:00 | 25.00 | 17.00 | 4.60 | 11.65 | 177.50 | 829.00 |
| July | 21.19 | 19-JUL-11:00 | 28.00 | 18.00 | 4.60 | 14.84 | 182.50 | 808.00 |
| August | 21.20 | 18-AUG-11:00 | 28.00 | 18.00 | 3.60 | 17.21 | 244.00 | 667.50 |
| September | 21.85 | 22-SEP-11:00 | 26.00 | 20.00 | 2.60 | 20.05 | 284.00 | 21.00 |
| October | 21.09 | 01-OCT-11:00 | 26.00 | 19.00 | 3.60 | 13.16 | 102.00 | 899.50 |
| November | 16.52 | 10-NOV-12:00 | 21.00 | 14.00 | 5.10 | 7.15 | 131.00 | 808.50 |
| December | 15.64 | 07-DEC-12:00 | 20.00 | 13.00 | 5.10 | 5.94 | 89.00 | 868.50 |
| Annual Sum or Average | ||||||||
| Minimum of Months | 15.64 | 18.00 | 13.00 | 1.10 | 5.94 | 89.00 | 9.00 | |
| Maximum of Months | 21.85 | 28.00 | 20.00 | 5.10 | 20.05 | 303.50 | 915.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| SITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
| January | 14.00 | 17-JAN-12:00 | 22.00 | 16.85 | 2.10 | 11.65 | 241.50 | 67.50 |
| February | 16.20 | 11-FEB-13:00 | 18.00 | 16.80 | 1.10 | 15.02 | 241.00 | 12.50 |
| March | 15.00 | 23-MAR-15:20 | 21.67 | 17.34 | 3.77 | 8.02 | 112.00 | 809.83 |
| April | 15.00 | 26-APR-21:19 | 16.00 | 15.39 | 2.23 | 6.15 | 0.00 | 0.00 |
| May | 16.00 | 05-MAY-14:00 | 18.00 | 16.69 | 5.10 | 8.74 | 303.50 | 269.00 |
| June | 17.00 | 28-JUN-08:00 | 19.00 | 17.66 | 1.50 | 16.12 | 285.00 | 428.50 |
| July | 18.00 | 18-JUL-10:00 | 26.00 | 20.47 | 4.60 | 12.79 | 169.00 | 819.00 |
| August | 18.10 | 14-AUG-09:00 | 26.90 | 20.93 | 3.40 | 13.73 | 139.00 | 817.00 |
| September | 20.00 | 22-SEP-09:00 | 22.00 | 20.55 | 1.50 | 16.30 | 296.00 | 18.00 |
| October | 19.00 | 01-OCT-07:10 | 19.17 | 19.06 | 0.25 | 16.82 | 53.33 | 0.00 |
| November | 15.00 | 10-NOV-17:19 | 16.67 | 15.62 | 2.77 | 3.34 | 0.00 | 0.00 |
| December | 13.00 | 07-DEC-12:00 | 20.00 | 15.64 | 5.10 | 5.94 | 89.00 | 868.50 |
| Annual Sum or Average | ||||||||
| Minimum of Months | 13.00 | 16.00 | 15.39 | 0.25 | 3.34 | 0.00 | 0.00 | |
| Maximum of Months | 20.00 | 26.90 | 20.93 | 5.10 | 16.82 | 303.50 | 868.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| SITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
| January | 18.00 | 13.00 | 16.00 | 17.43 | 27.46 | 0.00 |
| February | 18.00 | 13.00 | 16.00 | 17.38 | 30.87 | 0.00 |
| March | 18.00 | 13.00 | 16.00 | 17.83 | 38.09 | 0.00 |
| April | 18.00 | 13.00 | 16.00 | 18.69 | 55.75 | 0.00 |
| May | 18.00 | 13.00 | 16.00 | 19.73 | 55.13 | 0.00 |
| June | 18.00 | 13.00 | 16.00 | 20.65 | 58.21 | 0.00 |
| July | 18.00 | 13.00 | 16.00 | 21.22 | 63.49 | 0.00 |
| August | 18.00 | 13.00 | 16.00 | 21.28 | 59.02 | 0.00 |
| September | 18.00 | 13.00 | 16.00 | 20.81 | 46.26 | 0.00 |
| October | 18.00 | 13.00 | 16.00 | 19.94 | 34.64 | 0.00 |
| November | 18.00 | 13.00 | 16.00 | 18.91 | 29.25 | 0.00 |
| December | 18.00 | 13.00 | 16.00 | 17.99 | 26.27 | 0.00 |
| Annual Sum or Average | 18.00 | 13.00 | 16.00 | 19.33 | 43.77 | 0.00 |
| Minimum of Months | 18.00 | 13.00 | 16.00 | 17.38 | 26.27 | 0.00 |
| Maximum of Months | 18.00 | 13.00 | 16.00 | 21.28 | 63.49 | 0.00 |
Report: WaterHeaterReportMonthly
For: G SW APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.108005E+10 | -903347417.9 | 0.00 | 0.00 | 744.00 | 0.00 | -176699497.1 | 59.44 | 0.00 | 0.00 |
| February | 0.978486E+09 | -816831062.5 | 0.00 | 0.00 | 672.00 | 0.00 | -161654633.5 | 59.44 | 0.00 | 0.00 |
| March | 0.107559E+10 | -894596580.8 | 0.00 | 0.00 | 744.00 | 0.00 | -180994480.2 | 59.44 | 0.00 | 0.00 |
| April | 0.101842E+10 | -847863418.3 | 0.00 | 0.00 | 720.00 | 0.00 | -170556367.6 | 59.44 | 0.00 | 0.00 |
| May | 0.103022E+10 | -853920194.4 | 0.00 | 0.00 | 744.00 | 0.00 | -176298300.6 | 59.44 | 0.00 | 0.00 |
| June | 0.975383E+09 | -807089083.6 | 0.00 | 0.00 | 720.00 | 0.00 | -168294301.6 | 59.44 | 0.00 | 0.00 |
| July | 0.994306E+09 | -821735507.1 | 0.00 | 0.00 | 744.00 | 0.00 | -172570887.8 | 59.44 | 0.00 | 0.00 |
| August | 0.993018E+09 | -820466330.1 | 0.00 | 0.00 | 744.00 | 0.00 | -172551879.8 | 59.44 | 0.00 | 0.00 |
| September | 0.970862E+09 | -803778210.8 | 0.00 | 0.00 | 720.00 | 0.00 | -167083521.7 | 59.44 | 0.00 | 0.00 |
| October | 0.102218E+10 | -849279145.1 | 0.00 | 0.00 | 744.00 | 0.00 | -172897755.6 | 59.44 | 0.00 | 0.00 |
| November | 0.101199E+10 | -843376492.6 | 0.00 | 0.00 | 720.00 | 0.00 | -168616403.7 | 59.44 | 0.00 | 0.00 |
| December | 0.106686E+10 | -891236720.8 | 0.00 | 0.00 | 744.00 | 0.00 | -175624251.7 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.122174E+11 | -0.101535E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.206384E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.970862E+09 | -903347417.9 | 0.00 | 0.00 | 672.00 | 0.00 | -180994480.2 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.108005E+10 | -803778210.8 | 0.00 | 0.00 | 744.00 | 0.00 | -161654633.5 | 59.44 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: G NW APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.108567E+10 | -903346838.0 | 0.00 | 0.00 | 744.00 | 0.00 | -182325245.9 | 59.44 | 0.00 | 0.00 |
| February | 0.983373E+09 | -816829582.1 | 0.00 | 0.00 | 672.00 | 0.00 | -166543373.8 | 59.44 | 0.00 | 0.00 |
| March | 0.107892E+10 | -894594614.7 | 0.00 | 0.00 | 744.00 | 0.00 | -184326239.6 | 59.44 | 0.00 | 0.00 |
| April | 0.102108E+10 | -847851164.0 | 0.00 | 0.00 | 720.00 | 0.00 | -173227891.9 | 59.44 | 0.00 | 0.00 |
| May | 0.103061E+10 | -853924314.5 | 0.00 | 0.00 | 744.00 | 0.00 | -176682457.6 | 59.44 | 0.00 | 0.00 |
| June | 0.975298E+09 | -807086966.6 | 0.00 | 0.00 | 720.00 | 0.00 | -168211442.1 | 59.44 | 0.00 | 0.00 |
| July | 0.994306E+09 | -821736878.0 | 0.00 | 0.00 | 744.00 | 0.00 | -172569241.1 | 59.44 | 0.00 | 0.00 |
| August | 0.993087E+09 | -820470502.1 | 0.00 | 0.00 | 744.00 | 0.00 | -172616655.1 | 59.44 | 0.00 | 0.00 |
| September | 0.971174E+09 | -803785939.6 | 0.00 | 0.00 | 720.00 | 0.00 | -167388181.2 | 59.44 | 0.00 | 0.00 |
| October | 0.102290E+10 | -849279658.4 | 0.00 | 0.00 | 744.00 | 0.00 | -173622945.6 | 59.44 | 0.00 | 0.00 |
| November | 0.101710E+10 | -843375705.8 | 0.00 | 0.00 | 720.00 | 0.00 | -173725353.6 | 59.44 | 0.00 | 0.00 |
| December | 0.107327E+10 | -891238118.5 | 0.00 | 0.00 | 744.00 | 0.00 | -182030600.6 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.122468E+11 | -0.101535E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.209327E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.971174E+09 | -903346838.0 | 0.00 | 0.00 | 672.00 | 0.00 | -184326239.6 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.108567E+10 | -803785939.6 | 0.00 | 0.00 | 744.00 | 0.00 | -166543373.8 | 59.44 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: G NE APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.108552E+10 | -903347925.2 | 0.00 | 0.00 | 744.00 | 0.00 | -182167453.3 | 59.44 | 0.00 | 0.00 |
| February | 0.983430E+09 | -816828946.1 | 0.00 | 0.00 | 672.00 | 0.00 | -166601470.1 | 59.44 | 0.00 | 0.00 |
| March | 0.107882E+10 | -894593069.2 | 0.00 | 0.00 | 744.00 | 0.00 | -184224660.4 | 59.44 | 0.00 | 0.00 |
| April | 0.102121E+10 | -847855725.6 | 0.00 | 0.00 | 720.00 | 0.00 | -173354592.2 | 59.44 | 0.00 | 0.00 |
| May | 0.103088E+10 | -853927033.1 | 0.00 | 0.00 | 744.00 | 0.00 | -176951969.0 | 59.44 | 0.00 | 0.00 |
| June | 0.975535E+09 | -807085657.9 | 0.00 | 0.00 | 720.00 | 0.00 | -168448943.7 | 59.44 | 0.00 | 0.00 |
| July | 0.994332E+09 | -821725071.5 | 0.00 | 0.00 | 744.00 | 0.00 | -172606849.5 | 59.44 | 0.00 | 0.00 |
| August | 0.993107E+09 | -820466496.9 | 0.00 | 0.00 | 744.00 | 0.00 | -172640455.2 | 59.44 | 0.00 | 0.00 |
| September | 0.971358E+09 | -803776627.8 | 0.00 | 0.00 | 720.00 | 0.00 | -167581015.5 | 59.44 | 0.00 | 0.00 |
| October | 0.102292E+10 | -849279538.2 | 0.00 | 0.00 | 744.00 | 0.00 | -173639965.6 | 59.44 | 0.00 | 0.00 |
| November | 0.101725E+10 | -843376118.9 | 0.00 | 0.00 | 720.00 | 0.00 | -173878075.8 | 59.44 | 0.00 | 0.00 |
| December | 0.107321E+10 | -891237765.9 | 0.00 | 0.00 | 744.00 | 0.00 | -181969388.1 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.122476E+11 | -0.101535E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.209406E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.971358E+09 | -903347925.2 | 0.00 | 0.00 | 672.00 | 0.00 | -184224660.4 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.108552E+10 | -803776627.8 | 0.00 | 0.00 | 744.00 | 0.00 | -166601470.1 | 59.44 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: G N1 APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.108441E+10 | -903353346.3 | 0.00 | 0.00 | 744.00 | 0.00 | -181058443.2 | 59.44 | 0.00 | 0.00 |
| February | 0.982056E+09 | -816826298.8 | 0.00 | 0.00 | 672.00 | 0.00 | -165229752.6 | 59.44 | 0.00 | 0.00 |
| March | 0.107785E+10 | -894596424.4 | 0.00 | 0.00 | 744.00 | 0.00 | -183257731.6 | 59.44 | 0.00 | 0.00 |
| April | 0.102018E+10 | -847854286.2 | 0.00 | 0.00 | 720.00 | 0.00 | -172324887.8 | 59.44 | 0.00 | 0.00 |
| May | 0.102944E+10 | -853927871.8 | 0.00 | 0.00 | 744.00 | 0.00 | -175513425.4 | 59.44 | 0.00 | 0.00 |
| June | 0.974675E+09 | -807087325.1 | 0.00 | 0.00 | 720.00 | 0.00 | -167587873.4 | 59.44 | 0.00 | 0.00 |
| July | 0.994252E+09 | -821724246.6 | 0.00 | 0.00 | 744.00 | 0.00 | -172528090.4 | 59.44 | 0.00 | 0.00 |
| August | 0.992999E+09 | -820466915.7 | 0.00 | 0.00 | 744.00 | 0.00 | -172532155.3 | 59.44 | 0.00 | 0.00 |
| September | 0.970920E+09 | -803781596.1 | 0.00 | 0.00 | 720.00 | 0.00 | -167138350.6 | 59.44 | 0.00 | 0.00 |
| October | 0.102234E+10 | -849277059.1 | 0.00 | 0.00 | 744.00 | 0.00 | -173061175.5 | 59.44 | 0.00 | 0.00 |
| November | 0.101531E+10 | -843382134.3 | 0.00 | 0.00 | 720.00 | 0.00 | -171925745.8 | 59.44 | 0.00 | 0.00 |
| December | 0.107160E+10 | -891235159.7 | 0.00 | 0.00 | 744.00 | 0.00 | -180369535.4 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.122360E+11 | -0.101535E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.208253E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.970920E+09 | -903353346.3 | 0.00 | 0.00 | 672.00 | 0.00 | -183257731.6 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.108441E+10 | -803781596.1 | 0.00 | 0.00 | 744.00 | 0.00 | -165229752.6 | 59.44 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: G N2 APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.108438E+10 | -903353404.0 | 0.00 | 0.00 | 744.00 | 0.00 | -181030655.8 | 59.44 | 0.00 | 0.00 |
| February | 0.982062E+09 | -816826229.3 | 0.00 | 0.00 | 672.00 | 0.00 | -165235896.8 | 59.44 | 0.00 | 0.00 |
| March | 0.107784E+10 | -894596660.1 | 0.00 | 0.00 | 744.00 | 0.00 | -183240797.1 | 59.44 | 0.00 | 0.00 |
| April | 0.102020E+10 | -847854459.4 | 0.00 | 0.00 | 720.00 | 0.00 | -172342972.8 | 59.44 | 0.00 | 0.00 |
| May | 0.102948E+10 | -853927485.0 | 0.00 | 0.00 | 744.00 | 0.00 | -175555584.1 | 59.44 | 0.00 | 0.00 |
| June | 0.974700E+09 | -807084477.3 | 0.00 | 0.00 | 720.00 | 0.00 | -167615284.9 | 59.44 | 0.00 | 0.00 |
| July | 0.994254E+09 | -821724723.5 | 0.00 | 0.00 | 744.00 | 0.00 | -172528962.1 | 59.44 | 0.00 | 0.00 |
| August | 0.993000E+09 | -820466973.1 | 0.00 | 0.00 | 744.00 | 0.00 | -172532966.6 | 59.44 | 0.00 | 0.00 |
| September | 0.970932E+09 | -803781732.4 | 0.00 | 0.00 | 720.00 | 0.00 | -167150062.8 | 59.44 | 0.00 | 0.00 |
| October | 0.102234E+10 | -849277207.5 | 0.00 | 0.00 | 744.00 | 0.00 | -173063597.4 | 59.44 | 0.00 | 0.00 |
| November | 0.101533E+10 | -843381988.5 | 0.00 | 0.00 | 720.00 | 0.00 | -171946656.3 | 59.44 | 0.00 | 0.00 |
| December | 0.107159E+10 | -891235109.7 | 0.00 | 0.00 | 744.00 | 0.00 | -180359368.5 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.122361E+11 | -0.101535E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.208260E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.970932E+09 | -903353404.0 | 0.00 | 0.00 | 672.00 | 0.00 | -183240797.1 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.108438E+10 | -803781732.4 | 0.00 | 0.00 | 744.00 | 0.00 | -165235896.8 | 59.44 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: G S1 APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.107817E+10 | -903347679.3 | 0.00 | 0.00 | 744.00 | 0.00 | -174825590.0 | 59.44 | 0.00 | 0.00 |
| February | 0.975952E+09 | -816830025.4 | 0.00 | 0.00 | 672.00 | 0.00 | -159122466.3 | 59.44 | 0.00 | 0.00 |
| March | 0.107334E+10 | -894593511.2 | 0.00 | 0.00 | 744.00 | 0.00 | -178743172.6 | 59.44 | 0.00 | 0.00 |
| April | 0.101716E+10 | -847853374.6 | 0.00 | 0.00 | 720.00 | 0.00 | -169305180.1 | 59.44 | 0.00 | 0.00 |
| May | 0.102897E+10 | -853927938.6 | 0.00 | 0.00 | 744.00 | 0.00 | -175042130.4 | 59.44 | 0.00 | 0.00 |
| June | 0.974729E+09 | -807088061.0 | 0.00 | 0.00 | 720.00 | 0.00 | -167641399.5 | 59.44 | 0.00 | 0.00 |
| July | 0.994258E+09 | -821735841.6 | 0.00 | 0.00 | 744.00 | 0.00 | -172521882.7 | 59.44 | 0.00 | 0.00 |
| August | 0.992970E+09 | -820469002.4 | 0.00 | 0.00 | 744.00 | 0.00 | -172501334.2 | 59.44 | 0.00 | 0.00 |
| September | 0.970747E+09 | -803787097.7 | 0.00 | 0.00 | 720.00 | 0.00 | -166960166.6 | 59.44 | 0.00 | 0.00 |
| October | 0.102186E+10 | -849282524.3 | 0.00 | 0.00 | 744.00 | 0.00 | -172581553.6 | 59.44 | 0.00 | 0.00 |
| November | 0.101089E+10 | -843378234.4 | 0.00 | 0.00 | 720.00 | 0.00 | -167513873.5 | 59.44 | 0.00 | 0.00 |
| December | 0.106504E+10 | -891232063.2 | 0.00 | 0.00 | 744.00 | 0.00 | -173809765.8 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.122041E+11 | -0.101535E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.205057E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.970747E+09 | -903347679.3 | 0.00 | 0.00 | 672.00 | 0.00 | -178743172.6 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.107817E+10 | -803787097.7 | 0.00 | 0.00 | 744.00 | 0.00 | -159122466.3 | 59.44 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: G S2 APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.107815E+10 | -903347741.4 | 0.00 | 0.00 | 744.00 | 0.00 | -174802249.7 | 59.44 | 0.00 | 0.00 |
| February | 0.975758E+09 | -816830236.5 | 0.00 | 0.00 | 672.00 | 0.00 | -158928083.4 | 59.44 | 0.00 | 0.00 |
| March | 0.107302E+10 | -894593595.8 | 0.00 | 0.00 | 744.00 | 0.00 | -178428786.4 | 59.44 | 0.00 | 0.00 |
| April | 0.101699E+10 | -847863027.2 | 0.00 | 0.00 | 720.00 | 0.00 | -169126273.3 | 59.44 | 0.00 | 0.00 |
| May | 0.102873E+10 | -853926670.1 | 0.00 | 0.00 | 744.00 | 0.00 | -174805998.2 | 59.44 | 0.00 | 0.00 |
| June | 0.974609E+09 | -807088133.3 | 0.00 | 0.00 | 720.00 | 0.00 | -167521182.0 | 59.44 | 0.00 | 0.00 |
| July | 0.994244E+09 | -821736971.2 | 0.00 | 0.00 | 744.00 | 0.00 | -172506657.5 | 59.44 | 0.00 | 0.00 |
| August | 0.992963E+09 | -820467965.4 | 0.00 | 0.00 | 744.00 | 0.00 | -172494807.5 | 59.44 | 0.00 | 0.00 |
| September | 0.970729E+09 | -803775445.7 | 0.00 | 0.00 | 720.00 | 0.00 | -166953281.0 | 59.44 | 0.00 | 0.00 |
| October | 0.102184E+10 | -849279280.5 | 0.00 | 0.00 | 744.00 | 0.00 | -172560682.1 | 59.44 | 0.00 | 0.00 |
| November | 0.101084E+10 | -843382795.2 | 0.00 | 0.00 | 720.00 | 0.00 | -167459068.6 | 59.44 | 0.00 | 0.00 |
| December | 0.106496E+10 | -891235320.9 | 0.00 | 0.00 | 744.00 | 0.00 | -173720841.1 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.122028E+11 | -0.101535E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.204931E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.970729E+09 | -903347741.4 | 0.00 | 0.00 | 672.00 | 0.00 | -178428786.4 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.107815E+10 | -803775445.7 | 0.00 | 0.00 | 744.00 | 0.00 | -158928083.4 | 59.44 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: M SW APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.198177E+10 | -0.180670E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -175068201.4 | 59.44 | 0.00 | 0.00 |
| February | 0.179226E+10 | -0.163366E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -158596456.9 | 59.44 | 0.00 | 0.00 |
| March | 0.196570E+10 | -0.178919E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -176501758.4 | 59.44 | 0.00 | 0.00 |
| April | 0.186363E+10 | -0.169572E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -167901788.4 | 59.44 | 0.00 | 0.00 |
| May | 0.188134E+10 | -0.170785E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -173485064.6 | 59.44 | 0.00 | 0.00 |
| June | 0.178123E+10 | -0.161418E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -167046528.7 | 59.44 | 0.00 | 0.00 |
| July | 0.181596E+10 | -0.164347E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172495180.5 | 59.44 | 0.00 | 0.00 |
| August | 0.181343E+10 | -0.164094E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172495181.8 | 59.44 | 0.00 | 0.00 |
| September | 0.177453E+10 | -0.160757E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -166967316.7 | 59.44 | 0.00 | 0.00 |
| October | 0.187137E+10 | -0.169857E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172800015.7 | 59.44 | 0.00 | 0.00 |
| November | 0.185482E+10 | -0.168677E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -168055228.5 | 59.44 | 0.00 | 0.00 |
| December | 0.195694E+10 | -0.178248E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -174466549.1 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.223530E+11 | -0.203071E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.204588E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.177453E+10 | -0.180670E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -176501758.4 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.198177E+10 | -0.160757E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -158596456.9 | 59.44 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: M NW APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.198657E+10 | -0.180670E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -179867652.3 | 59.44 | 0.00 | 0.00 |
| February | 0.179566E+10 | -0.163366E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -162002093.1 | 59.44 | 0.00 | 0.00 |
| March | 0.196848E+10 | -0.178920E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -179279286.3 | 59.44 | 0.00 | 0.00 |
| April | 0.186429E+10 | -0.169572E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -168572531.4 | 59.44 | 0.00 | 0.00 |
| May | 0.188135E+10 | -0.170786E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -173492569.2 | 59.44 | 0.00 | 0.00 |
| June | 0.178121E+10 | -0.161418E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -167031637.1 | 59.44 | 0.00 | 0.00 |
| July | 0.181596E+10 | -0.164347E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172495745.3 | 59.44 | 0.00 | 0.00 |
| August | 0.181344E+10 | -0.164094E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172502268.9 | 59.44 | 0.00 | 0.00 |
| September | 0.177460E+10 | -0.160757E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -167038268.1 | 59.44 | 0.00 | 0.00 |
| October | 0.187175E+10 | -0.169856E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -173189851.4 | 59.44 | 0.00 | 0.00 |
| November | 0.185759E+10 | -0.168677E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -170821450.3 | 59.44 | 0.00 | 0.00 |
| December | 0.196143E+10 | -0.178248E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -178952996.2 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.223723E+11 | -0.203071E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.206525E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.177460E+10 | -0.180670E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -179867652.3 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.198657E+10 | -0.160757E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -162002093.1 | 59.44 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: M SE APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.198159E+10 | -0.180670E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -174897582.1 | 59.44 | 0.00 | 0.00 |
| February | 0.179229E+10 | -0.163366E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -158629063.8 | 59.44 | 0.00 | 0.00 |
| March | 0.196561E+10 | -0.178920E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -176413804.2 | 59.44 | 0.00 | 0.00 |
| April | 0.186357E+10 | -0.169572E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -167849652.7 | 59.44 | 0.00 | 0.00 |
| May | 0.188130E+10 | -0.170786E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -173445776.2 | 59.44 | 0.00 | 0.00 |
| June | 0.178124E+10 | -0.161418E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -167054266.6 | 59.44 | 0.00 | 0.00 |
| July | 0.181597E+10 | -0.164347E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172499759.0 | 59.44 | 0.00 | 0.00 |
| August | 0.181344E+10 | -0.164094E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172494321.2 | 59.44 | 0.00 | 0.00 |
| September | 0.177455E+10 | -0.160757E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -166984816.2 | 59.44 | 0.00 | 0.00 |
| October | 0.187135E+10 | -0.169857E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172788102.5 | 59.44 | 0.00 | 0.00 |
| November | 0.185480E+10 | -0.168676E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -168037803.6 | 59.44 | 0.00 | 0.00 |
| December | 0.195689E+10 | -0.178248E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -174409904.0 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.223526E+11 | -0.203071E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.204550E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.177455E+10 | -0.180670E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -176413804.2 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.198159E+10 | -0.160757E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -158629063.8 | 59.44 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: M NE APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.198631E+10 | -0.180670E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -179612082.5 | 59.44 | 0.00 | 0.00 |
| February | 0.179577E+10 | -0.163366E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -162103058.0 | 59.44 | 0.00 | 0.00 |
| March | 0.196838E+10 | -0.178920E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -179181640.6 | 59.44 | 0.00 | 0.00 |
| April | 0.186420E+10 | -0.169572E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -168483288.1 | 59.44 | 0.00 | 0.00 |
| May | 0.188133E+10 | -0.170786E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -173474365.9 | 59.44 | 0.00 | 0.00 |
| June | 0.178123E+10 | -0.161418E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -167047059.1 | 59.44 | 0.00 | 0.00 |
| July | 0.181597E+10 | -0.164347E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172500241.7 | 59.44 | 0.00 | 0.00 |
| August | 0.181344E+10 | -0.164094E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172502012.9 | 59.44 | 0.00 | 0.00 |
| September | 0.177463E+10 | -0.160757E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -167065591.8 | 59.44 | 0.00 | 0.00 |
| October | 0.187171E+10 | -0.169856E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -173144447.3 | 59.44 | 0.00 | 0.00 |
| November | 0.185769E+10 | -0.168677E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -170928730.5 | 59.44 | 0.00 | 0.00 |
| December | 0.196136E+10 | -0.178248E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -178884945.0 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.223720E+11 | -0.203071E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.206493E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.177463E+10 | -0.180670E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -179612082.5 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.198631E+10 | -0.160757E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -162103058.0 | 59.44 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: M N1 APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.198498E+10 | -0.180670E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -178287741.6 | 59.44 | 0.00 | 0.00 |
| February | 0.179346E+10 | -0.163366E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -159795953.1 | 59.44 | 0.00 | 0.00 |
| March | 0.196658E+10 | -0.178919E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -177387248.0 | 59.44 | 0.00 | 0.00 |
| April | 0.186361E+10 | -0.169572E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -167888647.2 | 59.44 | 0.00 | 0.00 |
| May | 0.188074E+10 | -0.170785E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172886935.8 | 59.44 | 0.00 | 0.00 |
| June | 0.178113E+10 | -0.161418E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -166945344.4 | 59.44 | 0.00 | 0.00 |
| July | 0.181595E+10 | -0.164347E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172488438.3 | 59.44 | 0.00 | 0.00 |
| August | 0.181343E+10 | -0.164094E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172491848.6 | 59.44 | 0.00 | 0.00 |
| September | 0.177452E+10 | -0.160757E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -166957367.1 | 59.44 | 0.00 | 0.00 |
| October | 0.187133E+10 | -0.169857E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172758761.9 | 59.44 | 0.00 | 0.00 |
| November | 0.185586E+10 | -0.168676E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -169100380.4 | 59.44 | 0.00 | 0.00 |
| December | 0.195925E+10 | -0.178248E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -176770202.6 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.223608E+11 | -0.203071E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.205376E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.177452E+10 | -0.180670E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -178287741.6 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.198498E+10 | -0.160757E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -159795953.1 | 59.44 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: M N2 APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.198494E+10 | -0.180670E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -178247515.1 | 59.44 | 0.00 | 0.00 |
| February | 0.179347E+10 | -0.163366E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -159807062.7 | 59.44 | 0.00 | 0.00 |
| March | 0.196658E+10 | -0.178919E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -177389363.2 | 59.44 | 0.00 | 0.00 |
| April | 0.186360E+10 | -0.169572E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -167882131.5 | 59.44 | 0.00 | 0.00 |
| May | 0.188074E+10 | -0.170785E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172887709.6 | 59.44 | 0.00 | 0.00 |
| June | 0.178113E+10 | -0.161418E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -166945903.7 | 59.44 | 0.00 | 0.00 |
| July | 0.181595E+10 | -0.164347E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172488514.3 | 59.44 | 0.00 | 0.00 |
| August | 0.181343E+10 | -0.164094E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172491961.3 | 59.44 | 0.00 | 0.00 |
| September | 0.177452E+10 | -0.160757E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -166959219.3 | 59.44 | 0.00 | 0.00 |
| October | 0.187133E+10 | -0.169857E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172758382.2 | 59.44 | 0.00 | 0.00 |
| November | 0.185587E+10 | -0.168676E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -169110248.9 | 59.44 | 0.00 | 0.00 |
| December | 0.195924E+10 | -0.178248E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -176763107.0 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.223608E+11 | -0.203071E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.205373E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.177452E+10 | -0.180670E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -178247515.1 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.198494E+10 | -0.160757E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -159807062.7 | 59.44 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: M S1 APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.198031E+10 | -0.180670E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -173605073.5 | 59.44 | 0.00 | 0.00 |
| February | 0.179063E+10 | -0.163366E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -156967385.0 | 59.44 | 0.00 | 0.00 |
| March | 0.196384E+10 | -0.178920E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -174638968.9 | 59.44 | 0.00 | 0.00 |
| April | 0.186307E+10 | -0.169572E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -167347000.6 | 59.44 | 0.00 | 0.00 |
| May | 0.188073E+10 | -0.170785E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172880538.1 | 59.44 | 0.00 | 0.00 |
| June | 0.178113E+10 | -0.161418E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -166950832.7 | 59.44 | 0.00 | 0.00 |
| July | 0.181595E+10 | -0.164347E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172488849.1 | 59.44 | 0.00 | 0.00 |
| August | 0.181343E+10 | -0.164094E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172489036.0 | 59.44 | 0.00 | 0.00 |
| September | 0.177449E+10 | -0.160757E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -166929355.3 | 59.44 | 0.00 | 0.00 |
| October | 0.187112E+10 | -0.169857E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172552064.5 | 59.44 | 0.00 | 0.00 |
| November | 0.185405E+10 | -0.168677E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -167283031.1 | 59.44 | 0.00 | 0.00 |
| December | 0.195573E+10 | -0.178248E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -173249678.1 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.223445E+11 | -0.203071E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.203738E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.177449E+10 | -0.180670E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -174638968.9 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.198031E+10 | -0.160757E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -156967385.0 | 59.44 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: M S2 APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.198029E+10 | -0.180670E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -173590576.0 | 59.44 | 0.00 | 0.00 |
| February | 0.179063E+10 | -0.163366E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -156974987.6 | 59.44 | 0.00 | 0.00 |
| March | 0.196384E+10 | -0.178920E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -174641272.7 | 59.44 | 0.00 | 0.00 |
| April | 0.186307E+10 | -0.169572E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -167344758.1 | 59.44 | 0.00 | 0.00 |
| May | 0.188073E+10 | -0.170785E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172881266.6 | 59.44 | 0.00 | 0.00 |
| June | 0.178113E+10 | -0.161418E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -166951403.0 | 59.44 | 0.00 | 0.00 |
| July | 0.181595E+10 | -0.164347E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172488919.0 | 59.44 | 0.00 | 0.00 |
| August | 0.181343E+10 | -0.164094E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172489082.6 | 59.44 | 0.00 | 0.00 |
| September | 0.177449E+10 | -0.160757E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -166929718.2 | 59.44 | 0.00 | 0.00 |
| October | 0.187112E+10 | -0.169857E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172552476.5 | 59.44 | 0.00 | 0.00 |
| November | 0.185405E+10 | -0.168677E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -167285278.5 | 59.44 | 0.00 | 0.00 |
| December | 0.195573E+10 | -0.178248E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -173250837.6 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.223445E+11 | -0.203071E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.203738E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.177449E+10 | -0.180670E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -174641272.7 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.198029E+10 | -0.160757E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -156974987.6 | 59.44 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: T SW APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.108300E+10 | -903345404.0 | 0.00 | 0.00 | 744.00 | 0.00 | -179656860.3 | 59.44 | 0.00 | 0.00 |
| February | 0.980561E+09 | -816832108.0 | 0.00 | 0.00 | 672.00 | 0.00 | -163728801.7 | 59.44 | 0.00 | 0.00 |
| March | 0.107612E+10 | -894595429.6 | 0.00 | 0.00 | 744.00 | 0.00 | -181527672.7 | 59.44 | 0.00 | 0.00 |
| April | 0.101996E+10 | -847854910.2 | 0.00 | 0.00 | 720.00 | 0.00 | -172102949.9 | 59.44 | 0.00 | 0.00 |
| May | 0.103196E+10 | -853923188.1 | 0.00 | 0.00 | 744.00 | 0.00 | -178035740.9 | 59.44 | 0.00 | 0.00 |
| June | 0.976219E+09 | -807090389.8 | 0.00 | 0.00 | 720.00 | 0.00 | -169128350.6 | 59.44 | 0.00 | 0.00 |
| July | 0.994923E+09 | -821724013.7 | 0.00 | 0.00 | 744.00 | 0.00 | -173198808.9 | 59.44 | 0.00 | 0.00 |
| August | 0.993732E+09 | -820464501.4 | 0.00 | 0.00 | 744.00 | 0.00 | -173267621.9 | 59.44 | 0.00 | 0.00 |
| September | 0.972349E+09 | -803779777.1 | 0.00 | 0.00 | 720.00 | 0.00 | -168568860.6 | 59.44 | 0.00 | 0.00 |
| October | 0.102454E+10 | -849278032.5 | 0.00 | 0.00 | 744.00 | 0.00 | -175263005.6 | 59.44 | 0.00 | 0.00 |
| November | 0.101653E+10 | -843382177.9 | 0.00 | 0.00 | 720.00 | 0.00 | -173144650.8 | 59.44 | 0.00 | 0.00 |
| December | 0.107090E+10 | -891235994.9 | 0.00 | 0.00 | 744.00 | 0.00 | -179667828.8 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.122408E+11 | -0.101535E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.208729E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.972349E+09 | -903345404.0 | 0.00 | 0.00 | 672.00 | 0.00 | -181527672.7 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.108300E+10 | -803779777.1 | 0.00 | 0.00 | 744.00 | 0.00 | -163728801.7 | 59.44 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: T NW APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.108686E+10 | -903350191.6 | 0.00 | 0.00 | 744.00 | 0.00 | -183514127.1 | 59.44 | 0.00 | 0.00 |
| February | 0.983134E+09 | -816827427.2 | 0.00 | 0.00 | 672.00 | 0.00 | -166307010.2 | 59.44 | 0.00 | 0.00 |
| March | 0.107793E+10 | -894593615.1 | 0.00 | 0.00 | 744.00 | 0.00 | -183335161.7 | 59.44 | 0.00 | 0.00 |
| April | 0.102099E+10 | -847856215.2 | 0.00 | 0.00 | 720.00 | 0.00 | -173137871.6 | 59.44 | 0.00 | 0.00 |
| May | 0.103198E+10 | -853923088.5 | 0.00 | 0.00 | 744.00 | 0.00 | -178052559.4 | 59.44 | 0.00 | 0.00 |
| June | 0.976094E+09 | -807087911.2 | 0.00 | 0.00 | 720.00 | 0.00 | -169006486.8 | 59.44 | 0.00 | 0.00 |
| July | 0.994890E+09 | -821721964.0 | 0.00 | 0.00 | 744.00 | 0.00 | -173167811.9 | 59.44 | 0.00 | 0.00 |
| August | 0.993854E+09 | -820465297.3 | 0.00 | 0.00 | 744.00 | 0.00 | -173388254.6 | 59.44 | 0.00 | 0.00 |
| September | 0.972861E+09 | -803782042.4 | 0.00 | 0.00 | 720.00 | 0.00 | -169078723.3 | 59.44 | 0.00 | 0.00 |
| October | 0.102554E+10 | -849281224.2 | 0.00 | 0.00 | 744.00 | 0.00 | -176260653.5 | 59.44 | 0.00 | 0.00 |
| November | 0.102011E+10 | -843378328.9 | 0.00 | 0.00 | 720.00 | 0.00 | -176735714.3 | 59.44 | 0.00 | 0.00 |
| December | 0.107465E+10 | -891237385.0 | 0.00 | 0.00 | 744.00 | 0.00 | -183415038.4 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.122589E+11 | -0.101535E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.210540E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.972861E+09 | -903350191.6 | 0.00 | 0.00 | 672.00 | 0.00 | -183514127.1 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.108686E+10 | -803782042.4 | 0.00 | 0.00 | 744.00 | 0.00 | -166307010.2 | 59.44 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: T SE APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.108277E+10 | -903346159.3 | 0.00 | 0.00 | 744.00 | 0.00 | -179420481.1 | 59.44 | 0.00 | 0.00 |
| February | 0.980461E+09 | -816825942.7 | 0.00 | 0.00 | 672.00 | 0.00 | -163635368.7 | 59.44 | 0.00 | 0.00 |
| March | 0.107593E+10 | -894593977.8 | 0.00 | 0.00 | 744.00 | 0.00 | -181338644.4 | 59.44 | 0.00 | 0.00 |
| April | 0.101981E+10 | -847863606.7 | 0.00 | 0.00 | 720.00 | 0.00 | -171947755.1 | 59.44 | 0.00 | 0.00 |
| May | 0.103187E+10 | -853923757.0 | 0.00 | 0.00 | 744.00 | 0.00 | -177945316.8 | 59.44 | 0.00 | 0.00 |
| June | 0.976304E+09 | -807085515.5 | 0.00 | 0.00 | 720.00 | 0.00 | -169218499.3 | 59.44 | 0.00 | 0.00 |
| July | 0.994994E+09 | -821728315.0 | 0.00 | 0.00 | 744.00 | 0.00 | -173265877.7 | 59.44 | 0.00 | 0.00 |
| August | 0.993754E+09 | -820469083.8 | 0.00 | 0.00 | 744.00 | 0.00 | -173284907.2 | 59.44 | 0.00 | 0.00 |
| September | 0.972431E+09 | -803784692.9 | 0.00 | 0.00 | 720.00 | 0.00 | -168646286.8 | 59.44 | 0.00 | 0.00 |
| October | 0.102447E+10 | -849286314.2 | 0.00 | 0.00 | 744.00 | 0.00 | -175185572.5 | 59.44 | 0.00 | 0.00 |
| November | 0.101642E+10 | -843382101.2 | 0.00 | 0.00 | 720.00 | 0.00 | -173037981.6 | 59.44 | 0.00 | 0.00 |
| December | 0.107076E+10 | -891235394.4 | 0.00 | 0.00 | 744.00 | 0.00 | -179523093.7 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.122400E+11 | -0.101535E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.208645E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.972431E+09 | -903346159.3 | 0.00 | 0.00 | 672.00 | 0.00 | -181338644.4 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.108277E+10 | -803784692.9 | 0.00 | 0.00 | 744.00 | 0.00 | -163635368.7 | 59.44 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: T NE APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.108683E+10 | -903350258.7 | 0.00 | 0.00 | 744.00 | 0.00 | -183477398.8 | 59.44 | 0.00 | 0.00 |
| February | 0.983246E+09 | -816827145.5 | 0.00 | 0.00 | 672.00 | 0.00 | -166418380.9 | 59.44 | 0.00 | 0.00 |
| March | 0.107780E+10 | -894597202.1 | 0.00 | 0.00 | 744.00 | 0.00 | -183204957.7 | 59.44 | 0.00 | 0.00 |
| April | 0.102091E+10 | -847858423.1 | 0.00 | 0.00 | 720.00 | 0.00 | -173048489.6 | 59.44 | 0.00 | 0.00 |
| May | 0.103188E+10 | -853921465.8 | 0.00 | 0.00 | 744.00 | 0.00 | -177960983.3 | 59.44 | 0.00 | 0.00 |
| June | 0.976159E+09 | -807090142.1 | 0.00 | 0.00 | 720.00 | 0.00 | -169069115.9 | 59.44 | 0.00 | 0.00 |
| July | 0.994974E+09 | -821725376.6 | 0.00 | 0.00 | 744.00 | 0.00 | -173248901.3 | 59.44 | 0.00 | 0.00 |
| August | 0.993899E+09 | -820467616.2 | 0.00 | 0.00 | 744.00 | 0.00 | -173431183.0 | 59.44 | 0.00 | 0.00 |
| September | 0.973021E+09 | -803781936.2 | 0.00 | 0.00 | 720.00 | 0.00 | -169239464.4 | 59.44 | 0.00 | 0.00 |
| October | 0.102550E+10 | -849281640.4 | 0.00 | 0.00 | 744.00 | 0.00 | -176213391.2 | 59.44 | 0.00 | 0.00 |
| November | 0.102030E+10 | -843377693.3 | 0.00 | 0.00 | 720.00 | 0.00 | -176922921.7 | 59.44 | 0.00 | 0.00 |
| December | 0.107471E+10 | -891236429.9 | 0.00 | 0.00 | 744.00 | 0.00 | -183474675.4 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.122592E+11 | -0.101535E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.210571E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.973021E+09 | -903350258.7 | 0.00 | 0.00 | 672.00 | 0.00 | -183477398.8 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.108683E+10 | -803781936.2 | 0.00 | 0.00 | 744.00 | 0.00 | -166418380.9 | 59.44 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: T N1 APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.108650E+10 | -903350110.2 | 0.00 | 0.00 | 744.00 | 0.00 | -183153289.6 | 59.44 | 0.00 | 0.00 |
| February | 0.983034E+09 | -816829173.2 | 0.00 | 0.00 | 672.00 | 0.00 | -166204657.1 | 59.44 | 0.00 | 0.00 |
| March | 0.107761E+10 | -894595164.2 | 0.00 | 0.00 | 744.00 | 0.00 | -183014650.3 | 59.44 | 0.00 | 0.00 |
| April | 0.102027E+10 | -847861408.2 | 0.00 | 0.00 | 720.00 | 0.00 | -172412371.9 | 59.44 | 0.00 | 0.00 |
| May | 0.103098E+10 | -853922690.7 | 0.00 | 0.00 | 744.00 | 0.00 | -177055300.1 | 59.44 | 0.00 | 0.00 |
| June | 0.975397E+09 | -807086761.0 | 0.00 | 0.00 | 720.00 | 0.00 | -168310088.7 | 59.44 | 0.00 | 0.00 |
| July | 0.994585E+09 | -821737812.2 | 0.00 | 0.00 | 744.00 | 0.00 | -172847311.5 | 59.44 | 0.00 | 0.00 |
| August | 0.993433E+09 | -820464901.1 | 0.00 | 0.00 | 744.00 | 0.00 | -172967862.3 | 59.44 | 0.00 | 0.00 |
| September | 0.972202E+09 | -803781061.5 | 0.00 | 0.00 | 720.00 | 0.00 | -168421373.5 | 59.44 | 0.00 | 0.00 |
| October | 0.102482E+10 | -849279212.5 | 0.00 | 0.00 | 744.00 | 0.00 | -175537005.5 | 59.44 | 0.00 | 0.00 |
| November | 0.101977E+10 | -843376271.6 | 0.00 | 0.00 | 720.00 | 0.00 | -176396249.9 | 59.44 | 0.00 | 0.00 |
| December | 0.107439E+10 | -891236576.7 | 0.00 | 0.00 | 744.00 | 0.00 | -183154033.0 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.122530E+11 | -0.101535E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.209947E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.972202E+09 | -903350110.2 | 0.00 | 0.00 | 672.00 | 0.00 | -183154033.0 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.108650E+10 | -803781061.5 | 0.00 | 0.00 | 744.00 | 0.00 | -166204657.1 | 59.44 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: T N2 APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.108649E+10 | -903350289.6 | 0.00 | 0.00 | 744.00 | 0.00 | -183137716.3 | 59.44 | 0.00 | 0.00 |
| February | 0.983038E+09 | -816828923.4 | 0.00 | 0.00 | 672.00 | 0.00 | -166208741.9 | 59.44 | 0.00 | 0.00 |
| March | 0.107759E+10 | -894594926.3 | 0.00 | 0.00 | 744.00 | 0.00 | -182995583.5 | 59.44 | 0.00 | 0.00 |
| April | 0.102029E+10 | -847862073.3 | 0.00 | 0.00 | 720.00 | 0.00 | -172424287.2 | 59.44 | 0.00 | 0.00 |
| May | 0.103099E+10 | -853922808.2 | 0.00 | 0.00 | 744.00 | 0.00 | -177067150.6 | 59.44 | 0.00 | 0.00 |
| June | 0.975415E+09 | -807086633.3 | 0.00 | 0.00 | 720.00 | 0.00 | -168328455.0 | 59.44 | 0.00 | 0.00 |
| July | 0.994596E+09 | -821737481.2 | 0.00 | 0.00 | 744.00 | 0.00 | -172858694.7 | 59.44 | 0.00 | 0.00 |
| August | 0.993443E+09 | -820465174.3 | 0.00 | 0.00 | 744.00 | 0.00 | -172978000.3 | 59.44 | 0.00 | 0.00 |
| September | 0.972235E+09 | -803780629.8 | 0.00 | 0.00 | 720.00 | 0.00 | -168454195.3 | 59.44 | 0.00 | 0.00 |
| October | 0.102483E+10 | -849279010.0 | 0.00 | 0.00 | 744.00 | 0.00 | -175546896.0 | 59.44 | 0.00 | 0.00 |
| November | 0.101979E+10 | -843375638.9 | 0.00 | 0.00 | 720.00 | 0.00 | -176412459.1 | 59.44 | 0.00 | 0.00 |
| December | 0.107439E+10 | -891236403.2 | 0.00 | 0.00 | 744.00 | 0.00 | -183149555.5 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.122531E+11 | -0.101535E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.209956E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.972235E+09 | -903350289.6 | 0.00 | 0.00 | 672.00 | 0.00 | -183149555.5 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.108649E+10 | -803780629.8 | 0.00 | 0.00 | 744.00 | 0.00 | -166208741.9 | 59.44 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: T S1 APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.108176E+10 | -903346532.1 | 0.00 | 0.00 | 744.00 | 0.00 | -178417812.0 | 59.44 | 0.00 | 0.00 |
| February | 0.979552E+09 | -816829363.3 | 0.00 | 0.00 | 672.00 | 0.00 | -162722191.6 | 59.44 | 0.00 | 0.00 |
| March | 0.107508E+10 | -894595007.9 | 0.00 | 0.00 | 744.00 | 0.00 | -180483338.9 | 59.44 | 0.00 | 0.00 |
| April | 0.101893E+10 | -847852635.3 | 0.00 | 0.00 | 720.00 | 0.00 | -171081165.6 | 59.44 | 0.00 | 0.00 |
| May | 0.103094E+10 | -853928355.0 | 0.00 | 0.00 | 744.00 | 0.00 | -177008816.1 | 59.44 | 0.00 | 0.00 |
| June | 0.975527E+09 | -807089056.8 | 0.00 | 0.00 | 720.00 | 0.00 | -168437843.1 | 59.44 | 0.00 | 0.00 |
| July | 0.994608E+09 | -821739868.7 | 0.00 | 0.00 | 744.00 | 0.00 | -172868307.0 | 59.44 | 0.00 | 0.00 |
| August | 0.993338E+09 | -820465673.5 | 0.00 | 0.00 | 744.00 | 0.00 | -172872737.6 | 59.44 | 0.00 | 0.00 |
| September | 0.971717E+09 | -803776569.7 | 0.00 | 0.00 | 720.00 | 0.00 | -167940310.3 | 59.44 | 0.00 | 0.00 |
| October | 0.102370E+10 | -849279904.9 | 0.00 | 0.00 | 744.00 | 0.00 | -174415661.2 | 59.44 | 0.00 | 0.00 |
| November | 0.101521E+10 | -843381594.2 | 0.00 | 0.00 | 720.00 | 0.00 | -171830447.9 | 59.44 | 0.00 | 0.00 |
| December | 0.106964E+10 | -891237917.1 | 0.00 | 0.00 | 744.00 | 0.00 | -178397319.1 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.122300E+11 | -0.101535E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.207648E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.971717E+09 | -903346532.1 | 0.00 | 0.00 | 672.00 | 0.00 | -180483338.9 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.108176E+10 | -803776569.7 | 0.00 | 0.00 | 744.00 | 0.00 | -162722191.6 | 59.44 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: T S2 APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.108176E+10 | -903346619.8 | 0.00 | 0.00 | 744.00 | 0.00 | -178409416.4 | 59.44 | 0.00 | 0.00 |
| February | 0.979555E+09 | -816829394.3 | 0.00 | 0.00 | 672.00 | 0.00 | -162726060.7 | 59.44 | 0.00 | 0.00 |
| March | 0.107507E+10 | -894594860.0 | 0.00 | 0.00 | 744.00 | 0.00 | -180476542.7 | 59.44 | 0.00 | 0.00 |
| April | 0.101894E+10 | -847852883.9 | 0.00 | 0.00 | 720.00 | 0.00 | -171089845.4 | 59.44 | 0.00 | 0.00 |
| May | 0.103095E+10 | -853928165.1 | 0.00 | 0.00 | 744.00 | 0.00 | -177024462.0 | 59.44 | 0.00 | 0.00 |
| June | 0.975549E+09 | -807090027.6 | 0.00 | 0.00 | 720.00 | 0.00 | -168458669.2 | 59.44 | 0.00 | 0.00 |
| July | 0.994620E+09 | -821738015.4 | 0.00 | 0.00 | 744.00 | 0.00 | -172881545.7 | 59.44 | 0.00 | 0.00 |
| August | 0.993346E+09 | -820465434.1 | 0.00 | 0.00 | 744.00 | 0.00 | -172880568.7 | 59.44 | 0.00 | 0.00 |
| September | 0.971733E+09 | -803776488.6 | 0.00 | 0.00 | 720.00 | 0.00 | -167956042.5 | 59.44 | 0.00 | 0.00 |
| October | 0.102370E+10 | -849280737.2 | 0.00 | 0.00 | 744.00 | 0.00 | -174420331.6 | 59.44 | 0.00 | 0.00 |
| November | 0.101522E+10 | -843379627.2 | 0.00 | 0.00 | 720.00 | 0.00 | -171836166.2 | 59.44 | 0.00 | 0.00 |
| December | 0.106964E+10 | -891236394.5 | 0.00 | 0.00 | 744.00 | 0.00 | -178401099.3 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.122301E+11 | -0.101535E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.207656E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.971733E+09 | -903346619.8 | 0.00 | 0.00 | 672.00 | 0.00 | -180476542.7 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.108176E+10 | -803776488.6 | 0.00 | 0.00 | 744.00 | 0.00 | -162726060.7 | 59.44 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
| January | 293.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 279.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 338.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 358.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 393.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 381.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 408.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 390.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 328.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 296.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 300.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 297.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 4065.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 279.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 408.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT GSW HEATING COIL
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 25853546.88 | 513.24 | 03-JAN-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 9010868.26 | 257.86 | 28-FEB-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.128573E+09 | 846.15 | 30-MAR-03:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 11879597.50 | 577.18 | 01-APR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 25377.39 | 42.30 | 14-MAY-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 62246.79 | 45.33 | 13-DEC-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.175405E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.128573E+09 | 846.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT GNW HEATING COIL
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.243358E+09 | 863.79 | 03-JAN-02:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.150055E+09 | 489.25 | 10-FEB-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.287211E+09 | 892.05 | 30-MAR-03:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 20092824.33 | 642.20 | 01-APR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 28873.09 | 48.12 | 14-MAY-04:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 1260220.85 | 109.82 | 27-NOV-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.111930E+09 | 515.85 | 15-DEC-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.813936E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.287211E+09 | 892.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT OFFICE HEATING COIL
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 22818.81 | 304.25 | 30-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 22818.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 22818.81 | 304.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT GNE HEATING COIL
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.228904E+09 | 870.44 | 03-JAN-02:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.157548E+09 | 611.41 | 28-FEB-18:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.293062E+09 | 1280.93 | 29-MAR-16:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 17967656.20 | 595.19 | 01-APR-05:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 297142.61 | 80.49 | 15-MAY-04:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 2478812.18 | 155.31 | 24-NOV-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.109945E+09 | 523.93 | 24-DEC-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.810202E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.293062E+09 | 1280.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT GN1 HEATING COIL
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.109634E+09 | 568.67 | 03-JAN-02:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 15997333.00 | 206.47 | 10-FEB-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.112182E+09 | 566.43 | 30-MAR-03:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 8114432.19 | 370.24 | 01-APR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 9407339.59 | 196.89 | 15-DEC-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.255335E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.112182E+09 | 568.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT GN2 HEATING COIL
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.109008E+09 | 567.04 | 03-JAN-02:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 16120705.42 | 205.93 | 10-FEB-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.113034E+09 | 567.24 | 30-MAR-03:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 8049287.70 | 370.23 | 01-APR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 9407011.04 | 196.61 | 15-DEC-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.255618E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.113034E+09 | 567.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT GS1 HEATING COIL
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 149846.38 | 42.54 | 03-JAN-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 21893047.62 | 464.09 | 30-MAR-03:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 3976252.31 | 252.41 | 01-APR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 26019146.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 21893047.62 | 464.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT GS2 HEATING COIL
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 749596.38 | 100.62 | 03-JAN-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 19746714.43 | 451.38 | 30-MAR-03:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 3584205.04 | 240.68 | 01-APR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 24080515.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 19746714.43 | 451.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT MSW HEATING COIL
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 2999499.08 | 302.28 | 03-JAN-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 62857758.59 | 1439.57 | 30-MAR-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 7354244.03 | 706.66 | 01-APR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 73211501.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 62857758.59 | 1439.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT MNW HEATING COIL
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.237956E+09 | 1577.34 | 03-JAN-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 1295798.76 | 227.38 | 10-FEB-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.137984E+09 | 1558.66 | 30-MAR-03:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 15607447.91 | 963.52 | 01-APR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 53375338.13 | 761.49 | 15-DEC-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.446219E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.237956E+09 | 1577.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT MSE HEATING COIL
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 2163383.77 | 289.39 | 03-JAN-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 65171073.57 | 1562.53 | 30-MAR-03:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 6155404.47 | 552.69 | 01-APR-05:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 73489861.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 65171073.57 | 1562.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT MNE HEATING COIL
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.222911E+09 | 1611.60 | 03-JAN-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 2968595.48 | 262.27 | 10-FEB-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.149891E+09 | 1679.58 | 30-MAR-03:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 13911926.52 | 823.71 | 01-APR-05:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 52956122.79 | 782.64 | 15-DEC-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.442639E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.222911E+09 | 1679.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT MN1 HEATING COIL
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 29584866.62 | 675.78 | 03-JAN-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 11558402.49 | 511.62 | 30-MAR-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 262797.31 | 164.27 | 01-APR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 41406066.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 29584866.62 | 675.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT MN2 HEATING COIL
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 29055578.58 | 664.88 | 03-JAN-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 11808194.93 | 517.81 | 30-MAR-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 252079.54 | 160.91 | 01-APR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 41115853.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 29055578.58 | 664.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT MS1 HEATING COIL
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 3379281.92 | 284.34 | 30-MAR-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 3379281.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 3379281.92 | 284.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT MS2 HEATING COIL
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 3510817.34 | 291.91 | 30-MAR-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 3510817.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 3510817.34 | 291.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT TSW HEATING COIL
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.430771E+09 | 1580.37 | 08-JAN-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.364202E+09 | 1110.87 | 05-FEB-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.542871E+09 | 1699.89 | 30-MAR-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 79771131.63 | 1206.12 | 01-APR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 74279595.32 | 826.28 | 13-MAY-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 28234839.29 | 608.62 | 12-OCT-05:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.208033E+09 | 1060.10 | 24-NOV-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.399644E+09 | 1474.96 | 13-DEC-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.212781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.542871E+09 | 1699.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT TNW HEATING COIL
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.788263E+09 | 1823.16 | 08-JAN-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.585210E+09 | 1264.61 | 05-FEB-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.701858E+09 | 1724.63 | 30-MAR-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.103813E+09 | 1251.36 | 01-APR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 69954692.87 | 813.03 | 13-MAY-04:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 571593.97 | 110.56 | 20-SEP-04:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 59879433.06 | 698.42 | 12-OCT-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.424054E+09 | 1313.11 | 24-NOV-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.743425E+09 | 1523.39 | 13-DEC-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.347703E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.788263E+09 | 1823.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT TSE HEATING COIL
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.418251E+09 | 1584.71 | 08-JAN-06:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.366597E+09 | 1130.67 | 05-FEB-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.541263E+09 | 1755.79 | 30-MAR-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 76557703.12 | 1111.32 | 01-APR-05:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 74644408.93 | 837.03 | 14-MAY-04:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 85922.65 | 55.85 | 13-JUN-04:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 112276.15 | 46.81 | 20-SEP-04:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 27805783.91 | 632.21 | 12-OCT-05:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.208249E+09 | 1088.49 | 24-NOV-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.393158E+09 | 1486.96 | 13-DEC-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.210672E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.541263E+09 | 1755.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT TNE HEATING COIL
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.754685E+09 | 1789.70 | 08-JAN-06:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.587091E+09 | 1298.06 | 05-FEB-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.697086E+09 | 1778.59 | 30-MAR-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.103332E+09 | 1163.18 | 01-APR-05:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 72903644.76 | 838.24 | 14-MAY-04:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 1228539.65 | 188.21 | 20-SEP-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 56184850.68 | 717.73 | 12-OCT-05:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.416891E+09 | 1356.74 | 24-NOV-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.719903E+09 | 1532.38 | 13-DEC-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.340931E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.754685E+09 | 1789.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT TN1 HEATING COIL
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.486235E+09 | 1288.71 | 08-JAN-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.304894E+09 | 846.82 | 05-FEB-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.393232E+09 | 1232.85 | 30-MAR-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 38139366.64 | 810.90 | 01-APR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 21668627.63 | 511.85 | 14-MAY-04:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 13349411.73 | 335.92 | 12-OCT-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.217156E+09 | 888.30 | 24-NOV-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.436804E+09 | 1035.79 | 13-DEC-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.191148E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.486235E+09 | 1288.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT TN2 HEATING COIL
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.486154E+09 | 1289.90 | 08-JAN-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.307320E+09 | 850.13 | 05-FEB-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.395043E+09 | 1237.76 | 30-MAR-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 38665074.35 | 809.85 | 01-APR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 21993844.03 | 516.09 | 14-MAY-04:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 13520196.67 | 340.81 | 12-OCT-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.219184E+09 | 892.78 | 24-NOV-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.438138E+09 | 1036.60 | 13-DEC-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.192002E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.486154E+09 | 1289.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT TS1 HEATING COIL
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.195112E+09 | 1037.75 | 08-JAN-06:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.130324E+09 | 631.76 | 05-FEB-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.274577E+09 | 1206.81 | 30-MAR-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 24322085.95 | 759.55 | 01-APR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 22176271.39 | 521.92 | 14-MAY-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 1388482.10 | 212.59 | 12-OCT-05:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 58718367.48 | 587.43 | 05-NOV-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.159759E+09 | 975.50 | 13-DEC-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.866377E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.274577E+09 | 1206.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT TS2 HEATING COIL
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.195137E+09 | 1038.78 | 08-JAN-06:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.131167E+09 | 634.12 | 05-FEB-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.275906E+09 | 1212.24 | 30-MAR-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 24376580.40 | 758.14 | 01-APR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 22526518.38 | 525.96 | 14-MAY-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 1428902.24 | 215.95 | 12-OCT-05:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 59264795.50 | 589.32 | 05-NOV-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.160490E+09 | 976.88 | 13-DEC-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.870297E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.275906E+09 | 1212.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT GSW COOLING COIL
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.260405E+09 | 0.252564E+09 | 1357.13 | 18-JAN-14:30 | 1357.13 | 0.00 |
| February | 0.00 | 0.00 | 0.100713E+09 | 99533851.66 | 1087.93 | 03-FEB-15:00 | 1087.93 | 0.00 |
| March | 0.00 | 0.00 | 53896390.30 | 48295599.63 | 866.31 | 23-MAR-15:10 | 724.48 | 0.00 |
| April | 0.00 | 0.00 | 0.238091E+09 | 0.213429E+09 | 1123.65 | 30-APR-16:15 | 1007.13 | 0.00 |
| May | 0.00 | 0.00 | 0.143573E+09 | 0.131513E+09 | 900.04 | 03-MAY-15:10 | 836.97 | 0.00 |
| June | 0.00 | 0.00 | 0.496379E+09 | 0.410767E+09 | 1351.18 | 29-JUN-16:25 | 1070.78 | 0.00 |
| July | 0.00 | 0.00 | 0.150213E+10 | 0.117549E+10 | 1785.09 | 23-JUL-16:15 | 1433.26 | 0.00 |
| August | 0.00 | 0.00 | 0.177968E+10 | 0.137896E+10 | 1957.35 | 17-AUG-15:10 | 1571.35 | 0.00 |
| September | 0.00 | 0.00 | 0.139077E+10 | 0.117239E+10 | 2437.72 | 30-SEP-15:10 | 2437.72 | 0.00 |
| October | 0.00 | 0.00 | 0.167660E+10 | 0.150722E+10 | 2681.46 | 16-OCT-12:50 | 2681.46 | 0.00 |
| November | 0.00 | 0.00 | 0.447996E+09 | 0.432518E+09 | 1724.09 | 19-NOV-13:00 | 1724.09 | 0.00 |
| December | 0.00 | 0.00 | 0.393129E+09 | 0.389987E+09 | 1476.11 | 19-DEC-13:00 | 1476.11 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.848336E+10 | 0.721267E+10 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 53896390.30 | 48295599.63 | 866.31 | 724.48 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.177968E+10 | 0.150722E+10 | 2681.46 | 2681.46 | 0.00 |
Report: CoilReportMonthly
For: SPLIT GNW COOLING COIL
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 7570888.49 | 7502947.71 | 348.44 | 18-JAN-14:20 | 348.44 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 54754696.07 | 48283637.52 | 764.72 | 30-APR-16:30 | 683.19 | 0.00 |
| May | 0.00 | 0.00 | 83308055.14 | 75611594.72 | 714.58 | 03-MAY-16:05 | 665.44 | 0.00 |
| June | 0.00 | 0.00 | 0.490103E+09 | 0.403150E+09 | 1401.20 | 29-JUN-17:00 | 1105.71 | 0.00 |
| July | 0.00 | 0.00 | 0.140540E+10 | 0.109276E+10 | 1761.89 | 19-JUL-16:25 | 1401.75 | 0.00 |
| August | 0.00 | 0.00 | 0.136645E+10 | 0.103585E+10 | 1721.36 | 17-AUG-16:05 | 1349.86 | 0.00 |
| September | 0.00 | 0.00 | 0.701614E+09 | 0.583334E+09 | 1786.18 | 29-SEP-16:04 | 1786.18 | 0.00 |
| October | 0.00 | 0.00 | 0.822472E+09 | 0.709499E+09 | 1758.11 | 16-OCT-12:00 | 1758.11 | 0.00 |
| November | 0.00 | 0.00 | 5219941.53 | 5218523.68 | 373.01 | 19-NOV-13:00 | 373.01 | 0.00 |
| December | 0.00 | 0.00 | 2398259.81 | 2398259.81 | 255.68 | 05-DEC-15:10 | 255.68 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.493929E+10 | 0.396361E+10 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.140540E+10 | 0.109276E+10 | 1786.18 | 1786.18 | 0.00 |
Report: CoilReportMonthly
For: SPLIT OFFICE COOLING COIL
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.608954E+09 | 0.585487E+09 | 6084.33 | 17-JAN-09:02 | 5449.31 | 0.00 |
| February | 0.00 | 0.00 | 0.392005E+09 | 0.376540E+09 | 5920.69 | 02-FEB-09:02 | 5745.90 | 0.00 |
| March | 0.00 | 0.00 | 0.290178E+09 | 0.258682E+09 | 3321.40 | 23-MAR-08:63 | 3111.85 | 0.00 |
| April | 0.00 | 0.00 | 0.627004E+09 | 0.562862E+09 | 6210.66 | 27-APR-08:62 | 4958.46 | 0.00 |
| May | 0.00 | 0.00 | 0.618533E+09 | 0.563826E+09 | 6206.60 | 03-MAY-08:62 | 5043.51 | 0.00 |
| June | 0.00 | 0.00 | 0.935915E+09 | 0.792960E+09 | 6328.98 | 28-JUN-08:62 | 4542.04 | 0.00 |
| July | 0.00 | 0.00 | 0.139226E+10 | 0.113102E+10 | 6376.02 | 28-JUL-08:62 | 4498.97 | 0.00 |
| August | 0.00 | 0.00 | 0.176969E+10 | 0.143319E+10 | 6419.17 | 07-AUG-08:62 | 4420.09 | 0.00 |
| September | 0.00 | 0.00 | 0.132283E+10 | 0.112732E+10 | 6441.40 | 22-SEP-08:62 | 4290.75 | 0.00 |
| October | 0.00 | 0.00 | 0.156966E+10 | 0.144071E+10 | 6449.96 | 02-OCT-07:03 | 4760.65 | 0.00 |
| November | 0.00 | 0.00 | 0.801851E+09 | 0.767437E+09 | 6179.96 | 10-NOV-09:02 | 5108.94 | 0.00 |
| December | 0.00 | 0.00 | 0.710002E+09 | 0.700033E+09 | 5851.94 | 07-DEC-09:02 | 5851.94 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.110389E+11 | 0.974006E+10 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.290178E+09 | 0.258682E+09 | 3321.40 | 3111.85 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.176969E+10 | 0.144071E+10 | 6449.96 | 5851.94 | 0.00 |
Report: CoilReportMonthly
For: SPLIT GNE COOLING COIL
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 9689585.17 | 9532936.39 | 343.33 | 18-JAN-13:00 | 343.33 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 48957503.11 | 43522046.54 | 695.39 | 30-APR-11:00 | 650.19 | 0.00 |
| May | 0.00 | 0.00 | 69711353.56 | 63371799.74 | 734.87 | 04-MAY-12:00 | 673.15 | 0.00 |
| June | 0.00 | 0.00 | 0.436866E+09 | 0.360083E+09 | 1144.68 | 30-JUN-10:00 | 897.35 | 0.00 |
| July | 0.00 | 0.00 | 0.134393E+10 | 0.104348E+10 | 1618.05 | 19-JUL-10:10 | 1273.45 | 0.00 |
| August | 0.00 | 0.00 | 0.134350E+10 | 0.101870E+10 | 1589.25 | 14-AUG-10:40 | 1228.58 | 0.00 |
| September | 0.00 | 0.00 | 0.623292E+09 | 0.520448E+09 | 1686.59 | 29-SEP-13:00 | 1686.59 | 0.00 |
| October | 0.00 | 0.00 | 0.793593E+09 | 0.687496E+09 | 1984.95 | 16-OCT-11:00 | 1984.95 | 0.00 |
| November | 0.00 | 0.00 | 5555568.99 | 5555568.99 | 395.51 | 19-NOV-13:00 | 395.51 | 0.00 |
| December | 0.00 | 0.00 | 2240371.32 | 2240371.32 | 165.90 | 05-DEC-15:00 | 165.90 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.467734E+10 | 0.375443E+10 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.134393E+10 | 0.104348E+10 | 1984.95 | 1984.95 | 0.00 |
Report: CoilReportMonthly
For: SPLIT GN1 COOLING COIL
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 13653158.95 | 13304281.64 | 362.19 | 18-JAN-13:00 | 362.19 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 31497689.90 | 27843271.65 | 469.36 | 26-APR-13:00 | 414.48 | 0.00 |
| May | 0.00 | 0.00 | 61219721.24 | 54863297.49 | 575.79 | 04-MAY-12:00 | 523.30 | 0.00 |
| June | 0.00 | 0.00 | 0.430133E+09 | 0.351052E+09 | 977.46 | 29-JUN-17:10 | 754.01 | 0.00 |
| July | 0.00 | 0.00 | 0.122978E+10 | 0.944995E+09 | 1243.22 | 18-JUL-16:07 | 961.76 | 0.00 |
| August | 0.00 | 0.00 | 0.122093E+10 | 0.914311E+09 | 1223.72 | 17-AUG-14:10 | 932.71 | 0.00 |
| September | 0.00 | 0.00 | 0.657464E+09 | 0.538393E+09 | 1347.49 | 29-SEP-13:00 | 1347.49 | 0.00 |
| October | 0.00 | 0.00 | 0.812771E+09 | 0.696410E+09 | 1502.28 | 16-OCT-11:00 | 1502.28 | 0.00 |
| November | 0.00 | 0.00 | 6340264.20 | 6329512.24 | 360.60 | 19-NOV-13:00 | 360.60 | 0.00 |
| December | 0.00 | 0.00 | 3061194.97 | 3061194.97 | 186.25 | 05-DEC-15:00 | 186.25 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.446685E+10 | 0.355056E+10 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.122978E+10 | 0.944995E+09 | 1502.28 | 1502.28 | 0.00 |
Report: CoilReportMonthly
For: SPLIT GN2 COOLING COIL
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 14034592.34 | 13680921.83 | 364.10 | 18-JAN-13:00 | 364.10 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 31330021.59 | 27707754.07 | 468.57 | 26-APR-13:00 | 413.80 | 0.00 |
| May | 0.00 | 0.00 | 60445941.10 | 54179673.51 | 578.87 | 04-MAY-12:00 | 526.19 | 0.00 |
| June | 0.00 | 0.00 | 0.425410E+09 | 0.347174E+09 | 966.77 | 29-JUN-17:10 | 745.26 | 0.00 |
| July | 0.00 | 0.00 | 0.122588E+10 | 0.941953E+09 | 1239.18 | 18-JUL-16:07 | 958.62 | 0.00 |
| August | 0.00 | 0.00 | 0.121934E+10 | 0.913175E+09 | 1230.10 | 18-AUG-12:00 | 928.33 | 0.00 |
| September | 0.00 | 0.00 | 0.650092E+09 | 0.532455E+09 | 1348.58 | 29-SEP-13:00 | 1348.58 | 0.00 |
| October | 0.00 | 0.00 | 0.811348E+09 | 0.695343E+09 | 1508.51 | 16-OCT-11:00 | 1508.51 | 0.00 |
| November | 0.00 | 0.00 | 6342989.95 | 6332377.84 | 360.27 | 19-NOV-13:00 | 360.27 | 0.00 |
| December | 0.00 | 0.00 | 3294954.96 | 3294954.96 | 189.56 | 05-DEC-15:00 | 189.56 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.444752E+10 | 0.353530E+10 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.122588E+10 | 0.941953E+09 | 1508.51 | 1508.51 | 0.00 |
Report: CoilReportMonthly
For: SPLIT GS1 COOLING COIL
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.444219E+09 | 0.429163E+09 | 1340.68 | 18-JAN-13:40 | 1340.68 | 0.00 |
| February | 0.00 | 0.00 | 0.169677E+09 | 0.167887E+09 | 1162.90 | 01-FEB-12:00 | 1162.90 | 0.00 |
| March | 0.00 | 0.00 | 65614725.94 | 59110366.29 | 738.29 | 23-MAR-14:00 | 629.55 | 0.00 |
| April | 0.00 | 0.00 | 0.229314E+09 | 0.205148E+09 | 954.15 | 26-APR-13:00 | 875.48 | 0.00 |
| May | 0.00 | 0.00 | 0.128816E+09 | 0.116958E+09 | 812.70 | 04-MAY-12:00 | 749.54 | 0.00 |
| June | 0.00 | 0.00 | 0.438788E+09 | 0.360638E+09 | 922.31 | 29-JUN-16:03 | 713.43 | 0.00 |
| July | 0.00 | 0.00 | 0.133607E+10 | 0.103478E+10 | 1445.38 | 31-JUL-13:00 | 1137.84 | 0.00 |
| August | 0.00 | 0.00 | 0.166407E+10 | 0.128007E+10 | 1569.59 | 19-AUG-13:00 | 1237.64 | 0.00 |
| September | 0.00 | 0.00 | 0.140293E+10 | 0.117508E+10 | 2083.46 | 29-SEP-13:00 | 2083.46 | 0.00 |
| October | 0.00 | 0.00 | 0.176171E+10 | 0.158313E+10 | 2422.75 | 16-OCT-12:00 | 2422.75 | 0.00 |
| November | 0.00 | 0.00 | 0.668060E+09 | 0.641776E+09 | 1721.62 | 19-NOV-13:00 | 1721.62 | 0.00 |
| December | 0.00 | 0.00 | 0.618609E+09 | 0.610596E+09 | 1570.98 | 19-DEC-13:00 | 1570.98 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.892787E+10 | 0.766434E+10 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 65614725.94 | 59110366.29 | 738.29 | 629.55 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.176171E+10 | 0.158313E+10 | 2422.75 | 2422.75 | 0.00 |
Report: CoilReportMonthly
For: SPLIT GS2 COOLING COIL
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.480644E+09 | 0.464240E+09 | 1379.45 | 18-JAN-13:40 | 1379.45 | 0.00 |
| February | 0.00 | 0.00 | 0.185735E+09 | 0.183635E+09 | 1197.38 | 01-FEB-12:00 | 1197.38 | 0.00 |
| March | 0.00 | 0.00 | 76366977.69 | 68758289.34 | 793.64 | 23-MAR-14:00 | 678.65 | 0.00 |
| April | 0.00 | 0.00 | 0.256398E+09 | 0.229718E+09 | 994.46 | 26-APR-13:00 | 914.29 | 0.00 |
| May | 0.00 | 0.00 | 0.150755E+09 | 0.136683E+09 | 854.11 | 04-MAY-12:00 | 788.99 | 0.00 |
| June | 0.00 | 0.00 | 0.492923E+09 | 0.406524E+09 | 959.18 | 29-JUN-16:03 | 744.73 | 0.00 |
| July | 0.00 | 0.00 | 0.146990E+10 | 0.114436E+10 | 1507.70 | 31-JUL-13:00 | 1194.55 | 0.00 |
| August | 0.00 | 0.00 | 0.181863E+10 | 0.140645E+10 | 1656.45 | 19-AUG-13:00 | 1316.94 | 0.00 |
| September | 0.00 | 0.00 | 0.151798E+10 | 0.127414E+10 | 2130.54 | 29-SEP-13:00 | 2130.54 | 0.00 |
| October | 0.00 | 0.00 | 0.191369E+10 | 0.172216E+10 | 2522.44 | 16-OCT-12:00 | 2522.44 | 0.00 |
| November | 0.00 | 0.00 | 0.719682E+09 | 0.691111E+09 | 1784.41 | 19-NOV-13:00 | 1784.41 | 0.00 |
| December | 0.00 | 0.00 | 0.658168E+09 | 0.649397E+09 | 1609.57 | 19-DEC-13:00 | 1609.57 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.974087E+10 | 0.837717E+10 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 76366977.69 | 68758289.34 | 793.64 | 678.65 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.191369E+10 | 0.172216E+10 | 2522.44 | 2522.44 | 0.00 |
Report: CoilReportMonthly
For: SPLIT MSW COOLING COIL
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.137889E+10 | 0.134133E+10 | 4226.31 | 18-JAN-14:30 | 4226.31 | 0.00 |
| February | 0.00 | 0.00 | 0.910510E+09 | 0.889673E+09 | 3666.19 | 03-FEB-15:00 | 3666.19 | 0.00 |
| March | 0.00 | 0.00 | 0.751197E+09 | 0.687025E+09 | 3783.93 | 23-MAR-15:30 | 3244.78 | 0.00 |
| April | 0.00 | 0.00 | 0.192868E+10 | 0.175822E+10 | 3860.94 | 26-APR-16:20 | 3553.96 | 0.00 |
| May | 0.00 | 0.00 | 0.140786E+10 | 0.129600E+10 | 3051.70 | 03-MAY-15:10 | 2850.17 | 0.00 |
| June | 0.00 | 0.00 | 0.273504E+10 | 0.232874E+10 | 4042.47 | 29-JUN-16:25 | 3281.82 | 0.00 |
| July | 0.00 | 0.00 | 0.481117E+10 | 0.384499E+10 | 4734.46 | 23-JUL-16:15 | 3889.02 | 0.00 |
| August | 0.00 | 0.00 | 0.531764E+10 | 0.419313E+10 | 5059.54 | 17-AUG-15:10 | 4131.99 | 0.00 |
| September | 0.00 | 0.00 | 0.418130E+10 | 0.354800E+10 | 6148.19 | 29-SEP-15:10 | 6148.19 | 0.00 |
| October | 0.00 | 0.00 | 0.435857E+10 | 0.394088E+10 | 6411.34 | 16-OCT-13:00 | 6411.34 | 0.00 |
| November | 0.00 | 0.00 | 0.178724E+10 | 0.171728E+10 | 4796.25 | 19-NOV-13:00 | 4796.25 | 0.00 |
| December | 0.00 | 0.00 | 0.172854E+10 | 0.170596E+10 | 4351.93 | 19-DEC-13:00 | 4351.93 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.312966E+11 | 0.272512E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.751197E+09 | 0.687025E+09 | 3051.70 | 2850.17 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.531764E+10 | 0.419313E+10 | 6411.34 | 6411.34 | 0.00 |
Report: CoilReportMonthly
For: SPLIT MNW COOLING COIL
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.137412E+09 | 0.131153E+09 | 1689.18 | 18-JAN-14:30 | 1689.18 | 0.00 |
| February | 0.00 | 0.00 | 23500397.91 | 22986334.63 | 1085.96 | 03-FEB-15:10 | 1085.96 | 0.00 |
| March | 0.00 | 0.00 | 0.114865E+09 | 97982501.26 | 2330.30 | 23-MAR-16:05 | 1907.40 | 0.00 |
| April | 0.00 | 0.00 | 0.936087E+09 | 0.835282E+09 | 3266.26 | 26-APR-16:20 | 2965.67 | 0.00 |
| May | 0.00 | 0.00 | 0.119961E+10 | 0.109938E+10 | 2741.08 | 03-MAY-16:10 | 2579.47 | 0.00 |
| June | 0.00 | 0.00 | 0.274071E+10 | 0.232862E+10 | 4169.38 | 29-JUN-17:10 | 3385.49 | 0.00 |
| July | 0.00 | 0.00 | 0.458922E+10 | 0.364988E+10 | 4696.89 | 19-JUL-16:25 | 3811.27 | 0.00 |
| August | 0.00 | 0.00 | 0.441116E+10 | 0.341400E+10 | 4524.60 | 17-AUG-16:05 | 3628.03 | 0.00 |
| September | 0.00 | 0.00 | 0.264139E+10 | 0.219632E+10 | 4667.97 | 29-SEP-15:30 | 4667.97 | 0.00 |
| October | 0.00 | 0.00 | 0.238168E+10 | 0.207508E+10 | 4336.29 | 14-OCT-15:10 | 4336.29 | 0.00 |
| November | 0.00 | 0.00 | 0.102389E+09 | 98252767.62 | 1584.92 | 19-NOV-13:30 | 1584.92 | 0.00 |
| December | 0.00 | 0.00 | 90911063.46 | 89517605.47 | 1622.82 | 05-DEC-15:10 | 1622.82 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.193689E+11 | 0.160385E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 23500397.91 | 22986334.63 | 1085.96 | 1085.96 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.458922E+10 | 0.364988E+10 | 4696.89 | 4667.97 | 0.00 |
Report: CoilReportMonthly
For: SPLIT MSE COOLING COIL
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.143815E+10 | 0.139826E+10 | 3919.00 | 18-JAN-13:30 | 3919.00 | 0.00 |
| February | 0.00 | 0.00 | 0.897049E+09 | 0.877796E+09 | 3695.53 | 01-FEB-12:00 | 3695.53 | 0.00 |
| March | 0.00 | 0.00 | 0.745900E+09 | 0.682989E+09 | 3329.19 | 23-MAR-14:00 | 2905.42 | 0.00 |
| April | 0.00 | 0.00 | 0.187121E+10 | 0.170781E+10 | 3913.00 | 26-APR-13:00 | 3700.29 | 0.00 |
| May | 0.00 | 0.00 | 0.128797E+10 | 0.118620E+10 | 3072.81 | 04-MAY-12:00 | 2882.27 | 0.00 |
| June | 0.00 | 0.00 | 0.255343E+10 | 0.217251E+10 | 3383.12 | 30-JUN-10:00 | 2761.14 | 0.00 |
| July | 0.00 | 0.00 | 0.469044E+10 | 0.374077E+10 | 4474.50 | 23-JUL-11:00 | 3567.14 | 0.00 |
| August | 0.00 | 0.00 | 0.528423E+10 | 0.416441E+10 | 4792.45 | 14-AUG-11:00 | 3902.43 | 0.00 |
| September | 0.00 | 0.00 | 0.397206E+10 | 0.336640E+10 | 6129.62 | 29-SEP-13:00 | 6129.62 | 0.00 |
| October | 0.00 | 0.00 | 0.429364E+10 | 0.389019E+10 | 6802.15 | 16-OCT-11:50 | 6802.15 | 0.00 |
| November | 0.00 | 0.00 | 0.173191E+10 | 0.166924E+10 | 4880.82 | 19-NOV-13:00 | 4880.82 | 0.00 |
| December | 0.00 | 0.00 | 0.174103E+10 | 0.172019E+10 | 4432.90 | 19-DEC-13:00 | 4432.90 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.305070E+11 | 0.265768E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.745900E+09 | 0.682989E+09 | 3072.81 | 2761.14 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.528423E+10 | 0.416441E+10 | 6802.15 | 6802.15 | 0.00 |
Report: CoilReportMonthly
For: SPLIT MNE COOLING COIL
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.150372E+09 | 0.143359E+09 | 1567.89 | 18-JAN-13:00 | 1567.89 | 0.00 |
| February | 0.00 | 0.00 | 20478567.89 | 20478567.89 | 1006.53 | 01-FEB-12:00 | 1006.53 | 0.00 |
| March | 0.00 | 0.00 | 0.114496E+09 | 99118802.04 | 1545.13 | 23-MAR-14:00 | 1298.36 | 0.00 |
| April | 0.00 | 0.00 | 0.865804E+09 | 0.772855E+09 | 2994.53 | 26-APR-11:00 | 2691.14 | 0.00 |
| May | 0.00 | 0.00 | 0.108342E+10 | 0.993090E+09 | 2582.47 | 04-MAY-12:00 | 2400.72 | 0.00 |
| June | 0.00 | 0.00 | 0.256055E+10 | 0.217334E+10 | 3443.87 | 30-JUN-10:00 | 2810.70 | 0.00 |
| July | 0.00 | 0.00 | 0.446848E+10 | 0.354623E+10 | 4212.85 | 19-JUL-10:10 | 3419.90 | 0.00 |
| August | 0.00 | 0.00 | 0.437615E+10 | 0.338507E+10 | 4105.91 | 14-AUG-10:40 | 3266.69 | 0.00 |
| September | 0.00 | 0.00 | 0.242886E+10 | 0.201830E+10 | 4352.54 | 29-SEP-13:00 | 4352.54 | 0.00 |
| October | 0.00 | 0.00 | 0.230035E+10 | 0.201174E+10 | 4753.12 | 16-OCT-11:00 | 4753.12 | 0.00 |
| November | 0.00 | 0.00 | 86419253.01 | 84544734.43 | 1631.27 | 19-NOV-13:00 | 1631.27 | 0.00 |
| December | 0.00 | 0.00 | 96561471.38 | 95792967.22 | 1273.97 | 05-DEC-10:00 | 1273.97 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.185519E+11 | 0.153439E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 20478567.89 | 20478567.89 | 1006.53 | 1006.53 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.446848E+10 | 0.354623E+10 | 4753.12 | 4753.12 | 0.00 |
Report: CoilReportMonthly
For: SPLIT MN1 COOLING COIL
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.200316E+09 | 0.187969E+09 | 1483.52 | 18-JAN-13:00 | 1483.52 | 0.00 |
| February | 0.00 | 0.00 | 29903329.09 | 29478008.80 | 929.07 | 01-FEB-12:00 | 929.07 | 0.00 |
| March | 0.00 | 0.00 | 0.106580E+09 | 90899480.56 | 1243.35 | 23-MAR-16:05 | 998.19 | 0.00 |
| April | 0.00 | 0.00 | 0.745308E+09 | 0.659007E+09 | 2157.37 | 26-APR-13:00 | 1979.38 | 0.00 |
| May | 0.00 | 0.00 | 0.105786E+10 | 0.959852E+09 | 1896.03 | 04-MAY-12:00 | 1745.67 | 0.00 |
| June | 0.00 | 0.00 | 0.232143E+10 | 0.195736E+10 | 2759.36 | 29-JUN-17:15 | 2171.22 | 0.00 |
| July | 0.00 | 0.00 | 0.375323E+10 | 0.294662E+10 | 3162.70 | 18-JUL-18:00 | 2481.87 | 0.00 |
| August | 0.00 | 0.00 | 0.367570E+10 | 0.280789E+10 | 3008.22 | 17-AUG-14:10 | 2335.81 | 0.00 |
| September | 0.00 | 0.00 | 0.231553E+10 | 0.190525E+10 | 3279.13 | 29-SEP-13:00 | 3279.13 | 0.00 |
| October | 0.00 | 0.00 | 0.224662E+10 | 0.194649E+10 | 3431.90 | 16-OCT-11:00 | 3431.90 | 0.00 |
| November | 0.00 | 0.00 | 0.174900E+09 | 0.161965E+09 | 1410.46 | 19-NOV-13:00 | 1410.46 | 0.00 |
| December | 0.00 | 0.00 | 0.144323E+09 | 0.140053E+09 | 1192.79 | 05-DEC-15:00 | 1192.79 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.167717E+11 | 0.137928E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 29903329.09 | 29478008.80 | 929.07 | 929.07 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.375323E+10 | 0.294662E+10 | 3431.90 | 3431.90 | 0.00 |
Report: CoilReportMonthly
For: SPLIT MN2 COOLING COIL
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.203089E+09 | 0.190599E+09 | 1491.11 | 18-JAN-13:00 | 1491.11 | 0.00 |
| February | 0.00 | 0.00 | 29521816.61 | 29140635.74 | 935.54 | 01-FEB-12:00 | 935.54 | 0.00 |
| March | 0.00 | 0.00 | 0.110954E+09 | 94767027.98 | 1243.32 | 23-MAR-16:05 | 998.48 | 0.00 |
| April | 0.00 | 0.00 | 0.745447E+09 | 0.659275E+09 | 2170.19 | 26-APR-13:00 | 1991.92 | 0.00 |
| May | 0.00 | 0.00 | 0.105479E+10 | 0.957168E+09 | 1909.54 | 04-MAY-12:00 | 1758.54 | 0.00 |
| June | 0.00 | 0.00 | 0.231385E+10 | 0.195096E+10 | 2738.12 | 29-JUN-17:15 | 2153.47 | 0.00 |
| July | 0.00 | 0.00 | 0.374803E+10 | 0.294244E+10 | 3148.07 | 18-JUL-18:00 | 2469.49 | 0.00 |
| August | 0.00 | 0.00 | 0.367410E+10 | 0.280683E+10 | 3013.48 | 17-AUG-14:10 | 2341.43 | 0.00 |
| September | 0.00 | 0.00 | 0.230584E+10 | 0.189713E+10 | 3288.92 | 29-SEP-13:00 | 3288.92 | 0.00 |
| October | 0.00 | 0.00 | 0.224646E+10 | 0.194688E+10 | 3447.92 | 16-OCT-11:00 | 3447.92 | 0.00 |
| November | 0.00 | 0.00 | 0.171414E+09 | 0.159088E+09 | 1414.99 | 19-NOV-13:00 | 1414.99 | 0.00 |
| December | 0.00 | 0.00 | 0.145830E+09 | 0.141574E+09 | 1197.80 | 05-DEC-15:00 | 1197.80 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.167493E+11 | 0.137759E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 29521816.61 | 29140635.74 | 935.54 | 935.54 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.374803E+10 | 0.294244E+10 | 3447.92 | 3447.92 | 0.00 |
Report: CoilReportMonthly
For: SPLIT MS1 COOLING COIL
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.192211E+10 | 0.186793E+10 | 3813.08 | 18-JAN-13:30 | 3813.08 | 0.00 |
| February | 0.00 | 0.00 | 0.119572E+10 | 0.116656E+10 | 3428.59 | 01-FEB-12:10 | 3428.59 | 0.00 |
| March | 0.00 | 0.00 | 0.928970E+09 | 0.854314E+09 | 2993.46 | 23-MAR-14:00 | 2612.64 | 0.00 |
| April | 0.00 | 0.00 | 0.182822E+10 | 0.166082E+10 | 3162.07 | 26-APR-13:00 | 2967.33 | 0.00 |
| May | 0.00 | 0.00 | 0.127224E+10 | 0.116110E+10 | 2375.03 | 04-MAY-12:00 | 2210.84 | 0.00 |
| June | 0.00 | 0.00 | 0.231301E+10 | 0.195439E+10 | 2574.32 | 29-JUN-16:07 | 2024.44 | 0.00 |
| July | 0.00 | 0.00 | 0.397811E+10 | 0.314181E+10 | 3545.16 | 31-JUL-13:00 | 2834.26 | 0.00 |
| August | 0.00 | 0.00 | 0.459847E+10 | 0.359373E+10 | 3834.35 | 19-AUG-13:00 | 3082.51 | 0.00 |
| September | 0.00 | 0.00 | 0.389132E+10 | 0.328425E+10 | 5026.54 | 29-SEP-13:00 | 5026.54 | 0.00 |
| October | 0.00 | 0.00 | 0.432139E+10 | 0.390531E+10 | 5596.26 | 16-OCT-12:00 | 5596.26 | 0.00 |
| November | 0.00 | 0.00 | 0.226271E+10 | 0.217036E+10 | 4533.14 | 19-NOV-13:00 | 4533.14 | 0.00 |
| December | 0.00 | 0.00 | 0.228896E+10 | 0.225385E+10 | 4241.37 | 19-DEC-13:00 | 4241.37 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.308012E+11 | 0.270144E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.928970E+09 | 0.854314E+09 | 2375.03 | 2024.44 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.459847E+10 | 0.390531E+10 | 5596.26 | 5596.26 | 0.00 |
Report: CoilReportMonthly
For: SPLIT MS2 COOLING COIL
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.193199E+10 | 0.187771E+10 | 3818.56 | 18-JAN-13:30 | 3818.56 | 0.00 |
| February | 0.00 | 0.00 | 0.119696E+10 | 0.116788E+10 | 3436.50 | 01-FEB-12:10 | 3436.50 | 0.00 |
| March | 0.00 | 0.00 | 0.932822E+09 | 0.857889E+09 | 3003.56 | 23-MAR-14:00 | 2622.19 | 0.00 |
| April | 0.00 | 0.00 | 0.182888E+10 | 0.166171E+10 | 3175.71 | 26-APR-13:00 | 2980.96 | 0.00 |
| May | 0.00 | 0.00 | 0.126965E+10 | 0.115888E+10 | 2388.80 | 04-MAY-12:00 | 2224.12 | 0.00 |
| June | 0.00 | 0.00 | 0.230553E+10 | 0.194813E+10 | 2558.79 | 29-JUN-16:07 | 2011.68 | 0.00 |
| July | 0.00 | 0.00 | 0.397295E+10 | 0.313770E+10 | 3553.26 | 31-JUL-13:00 | 2842.02 | 0.00 |
| August | 0.00 | 0.00 | 0.459686E+10 | 0.359270E+10 | 3848.72 | 19-AUG-13:00 | 3096.43 | 0.00 |
| September | 0.00 | 0.00 | 0.388217E+10 | 0.327637E+10 | 5036.71 | 29-SEP-13:00 | 5036.71 | 0.00 |
| October | 0.00 | 0.00 | 0.432030E+10 | 0.390471E+10 | 5609.61 | 16-OCT-12:00 | 5609.61 | 0.00 |
| November | 0.00 | 0.00 | 0.226266E+10 | 0.217057E+10 | 4541.61 | 19-NOV-13:00 | 4541.61 | 0.00 |
| December | 0.00 | 0.00 | 0.229336E+10 | 0.225828E+10 | 4248.38 | 19-DEC-13:00 | 4248.38 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.307941E+11 | 0.270125E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.932822E+09 | 0.857889E+09 | 2388.80 | 2011.68 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.459686E+10 | 0.390471E+10 | 5609.61 | 5609.61 | 0.00 |
Report: CoilReportMonthly
For: SPLIT TSW COOLING COIL
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.510971E+09 | 0.502405E+09 | 2668.07 | 14-JAN-15:00 | 2668.07 | 0.00 |
| February | 0.00 | 0.00 | 0.307518E+09 | 0.300902E+09 | 1957.96 | 03-FEB-15:00 | 1957.96 | 0.00 |
| March | 0.00 | 0.00 | 0.372481E+09 | 0.343327E+09 | 2344.60 | 23-MAR-15:30 | 2013.15 | 0.00 |
| April | 0.00 | 0.00 | 0.851584E+09 | 0.782384E+09 | 2522.11 | 26-APR-14:10 | 2426.34 | 0.00 |
| May | 0.00 | 0.00 | 0.555606E+09 | 0.515888E+09 | 2077.00 | 03-MAY-15:10 | 1944.15 | 0.00 |
| June | 0.00 | 0.00 | 0.120273E+10 | 0.103061E+10 | 2579.91 | 29-JUN-16:13 | 2108.06 | 0.00 |
| July | 0.00 | 0.00 | 0.230635E+10 | 0.186947E+10 | 3088.34 | 19-JUL-15:10 | 2581.68 | 0.00 |
| August | 0.00 | 0.00 | 0.253452E+10 | 0.203257E+10 | 3388.20 | 17-AUG-15:10 | 2827.81 | 0.00 |
| September | 0.00 | 0.00 | 0.181534E+10 | 0.155858E+10 | 4189.99 | 29-SEP-14:10 | 4189.99 | 0.00 |
| October | 0.00 | 0.00 | 0.187994E+10 | 0.171047E+10 | 4244.33 | 16-OCT-13:20 | 4244.33 | 0.00 |
| November | 0.00 | 0.00 | 0.564335E+09 | 0.548284E+09 | 2927.04 | 19-NOV-13:30 | 2927.04 | 0.00 |
| December | 0.00 | 0.00 | 0.639348E+09 | 0.635231E+09 | 2530.28 | 05-DEC-15:00 | 2530.28 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.135407E+11 | 0.118301E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.307518E+09 | 0.300902E+09 | 1957.96 | 1944.15 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.253452E+10 | 0.203257E+10 | 4244.33 | 4244.33 | 0.00 |
Report: CoilReportMonthly
For: SPLIT TNW COOLING COIL
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 49393717.29 | 48822427.51 | 878.46 | 18-JAN-14:30 | 878.46 | 0.00 |
| February | 0.00 | 0.00 | 7655238.84 | 7392805.03 | 473.52 | 03-FEB-15:10 | 473.52 | 0.00 |
| March | 0.00 | 0.00 | 66194781.95 | 59180603.92 | 1433.87 | 23-MAR-16:05 | 1176.97 | 0.00 |
| April | 0.00 | 0.00 | 0.389261E+09 | 0.350772E+09 | 2048.39 | 26-APR-16:20 | 1863.94 | 0.00 |
| May | 0.00 | 0.00 | 0.441756E+09 | 0.407715E+09 | 1831.18 | 03-MAY-15:10 | 1701.18 | 0.00 |
| June | 0.00 | 0.00 | 0.117971E+10 | 0.100637E+10 | 2637.72 | 29-JUN-16:40 | 2153.26 | 0.00 |
| July | 0.00 | 0.00 | 0.216860E+10 | 0.174550E+10 | 3056.23 | 19-JUL-16:25 | 2529.57 | 0.00 |
| August | 0.00 | 0.00 | 0.204606E+10 | 0.160716E+10 | 2949.13 | 17-AUG-16:03 | 2419.30 | 0.00 |
| September | 0.00 | 0.00 | 0.103952E+10 | 0.876381E+09 | 3154.30 | 29-SEP-15:20 | 3154.30 | 0.00 |
| October | 0.00 | 0.00 | 0.939920E+09 | 0.822533E+09 | 2853.97 | 14-OCT-15:10 | 2853.97 | 0.00 |
| November | 0.00 | 0.00 | 38277833.73 | 37653054.93 | 947.19 | 19-NOV-13:50 | 947.19 | 0.00 |
| December | 0.00 | 0.00 | 43121374.22 | 43121374.22 | 1027.47 | 05-DEC-15:10 | 1027.47 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.840946E+10 | 0.701260E+10 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 7655238.84 | 7392805.03 | 473.52 | 473.52 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.216860E+10 | 0.174550E+10 | 3154.30 | 3154.30 | 0.00 |
Report: CoilReportMonthly
For: SPLIT TSE COOLING COIL
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.512873E+09 | 0.503622E+09 | 2359.93 | 18-JAN-13:50 | 2359.93 | 0.00 |
| February | 0.00 | 0.00 | 0.279708E+09 | 0.274454E+09 | 1981.02 | 01-FEB-12:40 | 1981.02 | 0.00 |
| March | 0.00 | 0.00 | 0.357840E+09 | 0.331212E+09 | 2163.21 | 11-MAR-13:40 | 2163.21 | 0.00 |
| April | 0.00 | 0.00 | 0.803840E+09 | 0.739748E+09 | 2531.74 | 26-APR-13:00 | 2406.32 | 0.00 |
| May | 0.00 | 0.00 | 0.486102E+09 | 0.451439E+09 | 2050.58 | 04-MAY-12:00 | 1929.29 | 0.00 |
| June | 0.00 | 0.00 | 0.112304E+10 | 0.962455E+09 | 2245.00 | 30-JUN-12:00 | 1891.45 | 0.00 |
| July | 0.00 | 0.00 | 0.226114E+10 | 0.183031E+10 | 2984.47 | 31-JUL-13:00 | 2454.57 | 0.00 |
| August | 0.00 | 0.00 | 0.252998E+10 | 0.202865E+10 | 3156.74 | 19-AUG-13:00 | 2630.17 | 0.00 |
| September | 0.00 | 0.00 | 0.171896E+10 | 0.147641E+10 | 4161.61 | 29-SEP-13:00 | 4161.61 | 0.00 |
| October | 0.00 | 0.00 | 0.183553E+10 | 0.167448E+10 | 4457.23 | 16-OCT-12:00 | 4457.23 | 0.00 |
| November | 0.00 | 0.00 | 0.523759E+09 | 0.511020E+09 | 2962.13 | 19-NOV-13:00 | 2962.13 | 0.00 |
| December | 0.00 | 0.00 | 0.626559E+09 | 0.623363E+09 | 2548.51 | 19-DEC-13:00 | 2548.51 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.130593E+11 | 0.114072E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.279708E+09 | 0.274454E+09 | 1981.02 | 1891.45 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.252998E+10 | 0.202865E+10 | 4457.23 | 4457.23 | 0.00 |
Report: CoilReportMonthly
For: SPLIT TNE COOLING COIL
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 48638159.31 | 47843861.70 | 726.49 | 18-JAN-13:00 | 726.49 | 0.00 |
| February | 0.00 | 0.00 | 5809033.93 | 5803692.03 | 556.72 | 01-FEB-12:00 | 556.72 | 0.00 |
| March | 0.00 | 0.00 | 56515661.23 | 51126490.55 | 891.23 | 23-MAR-14:00 | 746.07 | 0.00 |
| April | 0.00 | 0.00 | 0.353020E+09 | 0.318537E+09 | 1822.99 | 26-APR-13:00 | 1704.08 | 0.00 |
| May | 0.00 | 0.00 | 0.373505E+09 | 0.344475E+09 | 1707.36 | 04-MAY-12:00 | 1592.87 | 0.00 |
| June | 0.00 | 0.00 | 0.109772E+10 | 0.935848E+09 | 2196.48 | 30-JUN-10:00 | 1799.11 | 0.00 |
| July | 0.00 | 0.00 | 0.212604E+10 | 0.170816E+10 | 2728.00 | 19-JUL-12:00 | 2271.27 | 0.00 |
| August | 0.00 | 0.00 | 0.204561E+10 | 0.160604E+10 | 2634.79 | 14-AUG-11:00 | 2125.67 | 0.00 |
| September | 0.00 | 0.00 | 0.954760E+09 | 0.805874E+09 | 2958.98 | 29-SEP-13:00 | 2958.98 | 0.00 |
| October | 0.00 | 0.00 | 0.896079E+09 | 0.787718E+09 | 3042.36 | 16-OCT-11:50 | 3042.36 | 0.00 |
| November | 0.00 | 0.00 | 35152265.36 | 35013075.47 | 985.39 | 19-NOV-13:00 | 985.39 | 0.00 |
| December | 0.00 | 0.00 | 38814463.50 | 38814463.50 | 757.69 | 05-DEC-15:00 | 757.69 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.803167E+10 | 0.668526E+10 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 5809033.93 | 5803692.03 | 556.72 | 556.72 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.212604E+10 | 0.170816E+10 | 3042.36 | 3042.36 | 0.00 |
Report: CoilReportMonthly
For: SPLIT TN1 COOLING COIL
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 33223534.14 | 32612576.90 | 574.43 | 18-JAN-13:50 | 574.43 | 0.00 |
| February | 0.00 | 0.00 | 1853939.78 | 1853939.78 | 258.38 | 01-FEB-12:50 | 258.38 | 0.00 |
| March | 0.00 | 0.00 | 20584963.37 | 18476877.65 | 562.03 | 23-MAR-15:10 | 455.73 | 0.00 |
| April | 0.00 | 0.00 | 0.205790E+09 | 0.183088E+09 | 1327.78 | 26-APR-13:00 | 1219.60 | 0.00 |
| May | 0.00 | 0.00 | 0.254423E+09 | 0.232314E+09 | 1236.12 | 04-MAY-12:00 | 1140.11 | 0.00 |
| June | 0.00 | 0.00 | 0.875845E+09 | 0.737825E+09 | 1683.56 | 29-JUN-17:10 | 1339.09 | 0.00 |
| July | 0.00 | 0.00 | 0.170845E+10 | 0.135397E+10 | 2054.81 | 19-JUL-15:10 | 1681.69 | 0.00 |
| August | 0.00 | 0.00 | 0.161777E+10 | 0.124979E+10 | 2042.27 | 17-AUG-14:10 | 1629.04 | 0.00 |
| September | 0.00 | 0.00 | 0.776702E+09 | 0.646421E+09 | 2244.07 | 29-SEP-13:00 | 2244.07 | 0.00 |
| October | 0.00 | 0.00 | 0.762476E+09 | 0.653317E+09 | 2249.82 | 16-OCT-12:00 | 2249.82 | 0.00 |
| November | 0.00 | 0.00 | 17056975.06 | 16989149.05 | 674.68 | 19-NOV-13:00 | 674.68 | 0.00 |
| December | 0.00 | 0.00 | 20717830.68 | 20717830.68 | 586.59 | 05-DEC-15:00 | 586.59 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.629490E+10 | 0.514738E+10 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 1853939.78 | 1853939.78 | 258.38 | 258.38 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.170845E+10 | 0.135397E+10 | 2249.82 | 2249.82 | 0.00 |
Report: CoilReportMonthly
For: SPLIT TN2 COOLING COIL
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 34004412.94 | 33367545.37 | 582.47 | 18-JAN-13:40 | 582.47 | 0.00 |
| February | 0.00 | 0.00 | 2009840.04 | 2009840.04 | 269.44 | 01-FEB-12:50 | 269.44 | 0.00 |
| March | 0.00 | 0.00 | 21791810.67 | 19572726.41 | 568.68 | 23-MAR-15:10 | 461.57 | 0.00 |
| April | 0.00 | 0.00 | 0.209066E+09 | 0.186163E+09 | 1346.25 | 26-APR-13:00 | 1237.96 | 0.00 |
| May | 0.00 | 0.00 | 0.255867E+09 | 0.233722E+09 | 1254.11 | 04-MAY-12:00 | 1157.40 | 0.00 |
| June | 0.00 | 0.00 | 0.874308E+09 | 0.736812E+09 | 1661.15 | 29-JUN-17:10 | 1320.12 | 0.00 |
| July | 0.00 | 0.00 | 0.170662E+10 | 0.135290E+10 | 2058.93 | 31-JUL-13:00 | 1641.38 | 0.00 |
| August | 0.00 | 0.00 | 0.161878E+10 | 0.125111E+10 | 2045.83 | 17-AUG-14:10 | 1633.46 | 0.00 |
| September | 0.00 | 0.00 | 0.774916E+09 | 0.645140E+09 | 2254.46 | 29-SEP-13:00 | 2254.46 | 0.00 |
| October | 0.00 | 0.00 | 0.763985E+09 | 0.655075E+09 | 2265.17 | 16-OCT-12:00 | 2265.17 | 0.00 |
| November | 0.00 | 0.00 | 17688528.07 | 17618126.82 | 686.41 | 19-NOV-13:00 | 686.41 | 0.00 |
| December | 0.00 | 0.00 | 21544856.10 | 21544856.10 | 589.99 | 05-DEC-15:00 | 589.99 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.630058E+10 | 0.515503E+10 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 2009840.04 | 2009840.04 | 269.44 | 269.44 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.170662E+10 | 0.135290E+10 | 2265.17 | 2265.17 | 0.00 |
Report: CoilReportMonthly
For: SPLIT TS1 COOLING COIL
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.526687E+09 | 0.516548E+09 | 2259.57 | 18-JAN-14:00 | 2259.57 | 0.00 |
| February | 0.00 | 0.00 | 0.280806E+09 | 0.275151E+09 | 1765.38 | 01-FEB-13:00 | 1765.38 | 0.00 |
| March | 0.00 | 0.00 | 0.299324E+09 | 0.275439E+09 | 1865.80 | 11-MAR-13:50 | 1865.80 | 0.00 |
| April | 0.00 | 0.00 | 0.653891E+09 | 0.597955E+09 | 2040.44 | 26-APR-13:00 | 1922.29 | 0.00 |
| May | 0.00 | 0.00 | 0.362156E+09 | 0.333759E+09 | 1590.74 | 03-MAY-13:00 | 1570.91 | 0.00 |
| June | 0.00 | 0.00 | 0.896913E+09 | 0.760543E+09 | 1769.94 | 27-JUN-13:00 | 1472.44 | 0.00 |
| July | 0.00 | 0.00 | 0.184566E+10 | 0.147683E+10 | 2423.21 | 31-JUL-13:00 | 1979.72 | 0.00 |
| August | 0.00 | 0.00 | 0.212283E+10 | 0.168458E+10 | 2597.15 | 19-AUG-13:00 | 2141.18 | 0.00 |
| September | 0.00 | 0.00 | 0.158094E+10 | 0.134753E+10 | 3446.38 | 29-SEP-13:00 | 3446.38 | 0.00 |
| October | 0.00 | 0.00 | 0.173539E+10 | 0.156984E+10 | 3665.72 | 16-OCT-12:00 | 3665.72 | 0.00 |
| November | 0.00 | 0.00 | 0.539950E+09 | 0.524456E+09 | 2693.01 | 19-NOV-13:00 | 2693.01 | 0.00 |
| December | 0.00 | 0.00 | 0.629466E+09 | 0.625246E+09 | 2384.74 | 19-DEC-13:00 | 2384.74 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.114740E+11 | 0.998788E+10 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.280806E+09 | 0.275151E+09 | 1590.74 | 1472.44 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.212283E+10 | 0.168458E+10 | 3665.72 | 3665.72 | 0.00 |
Report: CoilReportMonthly
For: SPLIT TS2 COOLING COIL
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.532414E+09 | 0.522177E+09 | 2263.22 | 18-JAN-14:00 | 2263.22 | 0.00 |
| February | 0.00 | 0.00 | 0.283454E+09 | 0.277780E+09 | 1773.18 | 01-FEB-13:00 | 1773.18 | 0.00 |
| March | 0.00 | 0.00 | 0.303558E+09 | 0.279482E+09 | 1878.44 | 11-MAR-13:50 | 1878.44 | 0.00 |
| April | 0.00 | 0.00 | 0.657498E+09 | 0.601537E+09 | 2057.85 | 26-APR-13:00 | 1940.01 | 0.00 |
| May | 0.00 | 0.00 | 0.364224E+09 | 0.335811E+09 | 1601.92 | 03-MAY-13:00 | 1582.27 | 0.00 |
| June | 0.00 | 0.00 | 0.895685E+09 | 0.759858E+09 | 1780.08 | 27-JUN-13:00 | 1482.19 | 0.00 |
| July | 0.00 | 0.00 | 0.184410E+10 | 0.147603E+10 | 2432.99 | 31-JUL-13:00 | 1989.44 | 0.00 |
| August | 0.00 | 0.00 | 0.212349E+10 | 0.168575E+10 | 2611.16 | 19-AUG-13:00 | 2155.41 | 0.00 |
| September | 0.00 | 0.00 | 0.157790E+10 | 0.134517E+10 | 3457.06 | 29-SEP-13:00 | 3457.06 | 0.00 |
| October | 0.00 | 0.00 | 0.173656E+10 | 0.157137E+10 | 3679.86 | 16-OCT-12:00 | 3679.86 | 0.00 |
| November | 0.00 | 0.00 | 0.542132E+09 | 0.526760E+09 | 2703.71 | 19-NOV-13:00 | 2703.71 | 0.00 |
| December | 0.00 | 0.00 | 0.634079E+09 | 0.629878E+09 | 2393.22 | 19-DEC-13:00 | 2393.22 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.114951E+11 | 0.100116E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.283454E+09 | 0.277780E+09 | 1601.92 | 1482.19 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.212349E+10 | 0.168575E+10 | 3679.86 | 3679.86 | 0.00 |
Report: FanReportMonthly
For: SPLIT GSW SUPPLY FAN
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 21808544.97 | 0.31 | 105.54 | 18-JAN-14:30 | 1.05 |
| February | 8550278.69 | 0.17 | 89.21 | 03-FEB-15:00 | 1.06 |
| March | 10152226.96 | 0.21 | 65.28 | 23-MAR-15:10 | 1.06 |
| April | 18905659.06 | 0.26 | 85.09 | 30-APR-16:15 | 1.05 |
| May | 11173607.30 | 0.21 | 69.18 | 03-MAY-15:10 | 1.06 |
| June | 37579707.72 | 0.48 | 99.27 | 29-JUN-16:30 | 1.04 |
| July | 0.111568E+09 | 0.95 | 129.71 | 23-JUL-16:30 | 1.03 |
| August | 0.131421E+09 | 0.97 | 142.47 | 17-AUG-15:10 | 1.02 |
| September | 0.105159E+09 | 0.90 | 197.01 | 29-SEP-13:30 | 1.00 |
| October | 0.129090E+09 | 0.82 | 220.41 | 16-OCT-12:00 | 0.99 |
| November | 35554210.71 | 0.45 | 134.40 | 19-NOV-13:00 | 1.03 |
| December | 31790055.04 | 0.33 | 119.82 | 19-DEC-13:00 | 1.05 |
| Annual Sum or Average | 0.652753E+09 | 0.51 | |||
| Minimum of Months | 8550278.69 | 0.17 | 65.28 | 0.99 | |
| Maximum of Months | 0.131421E+09 | 0.97 | 220.41 | 1.06 |
Report: FanReportMonthly
For: G SW APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.64 | 20.01 | 01-JAN-00:10 | 0.64 |
| February | 48400714.57 | 0.64 | 20.01 | 01-FEB-00:10 | 0.64 |
| March | 53586505.42 | 0.64 | 20.01 | 01-MAR-00:10 | 0.64 |
| April | 51857908.47 | 0.64 | 20.01 | 01-APR-00:10 | 0.64 |
| May | 53586505.42 | 0.64 | 20.01 | 01-MAY-00:10 | 0.64 |
| June | 51857908.47 | 0.64 | 20.01 | 01-JUN-00:10 | 0.64 |
| July | 53586505.42 | 0.64 | 20.01 | 01-JUL-00:10 | 0.64 |
| August | 53586505.42 | 0.64 | 20.01 | 01-AUG-00:10 | 0.63 |
| September | 51857908.47 | 0.64 | 20.01 | 01-SEP-00:10 | 0.64 |
| October | 53586505.42 | 0.64 | 20.01 | 01-OCT-00:10 | 0.63 |
| November | 51857908.47 | 0.64 | 20.01 | 01-NOV-00:10 | 0.64 |
| December | 53586505.42 | 0.64 | 20.01 | 01-DEC-00:10 | 0.64 |
| Annual Sum or Average | 0.630938E+09 | 0.64 | |||
| Minimum of Months | 48400714.57 | 0.64 | 20.01 | 0.63 | |
| Maximum of Months | 53586505.42 | 0.64 | 20.01 | 0.64 |
Report: FanReportMonthly
For: G SW APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.64 | 20.01 | 01-JAN-00:10 | 0.64 |
| February | 48400714.57 | 0.64 | 20.01 | 01-FEB-00:10 | 0.64 |
| March | 53586505.42 | 0.64 | 20.01 | 01-MAR-00:10 | 0.64 |
| April | 51857908.47 | 0.64 | 20.01 | 01-APR-00:10 | 0.64 |
| May | 53586505.42 | 0.64 | 20.01 | 01-MAY-00:10 | 0.64 |
| June | 51857908.47 | 0.64 | 20.01 | 01-JUN-00:10 | 0.64 |
| July | 53586505.42 | 0.64 | 20.01 | 01-JUL-00:10 | 0.64 |
| August | 53586505.42 | 0.64 | 20.01 | 01-AUG-00:10 | 0.64 |
| September | 51857908.47 | 0.64 | 20.01 | 01-SEP-00:10 | 0.64 |
| October | 53586505.42 | 0.64 | 20.01 | 01-OCT-00:10 | 0.64 |
| November | 51857908.47 | 0.64 | 20.01 | 01-NOV-00:10 | 0.64 |
| December | 53586505.42 | 0.64 | 20.01 | 01-DEC-00:10 | 0.64 |
| Annual Sum or Average | 0.630938E+09 | 0.64 | |||
| Minimum of Months | 48400714.57 | 0.64 | 20.01 | 0.64 | |
| Maximum of Months | 53586505.42 | 0.64 | 20.01 | 0.64 |
Report: FanReportMonthly
For: SPLIT GNW SUPPLY FAN
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 11805720.26 | 0.28 | 39.74 | 03-JAN-02:00 | 0.93 |
| February | 6904299.22 | 0.29 | 22.51 | 10-FEB-07:00 | 0.93 |
| March | 13215089.35 | 0.32 | 41.04 | 30-MAR-03:00 | 0.93 |
| April | 5151982.11 | 0.10 | 58.43 | 30-APR-16:30 | 1.06 |
| May | 6481652.94 | 0.15 | 55.16 | 03-MAY-16:05 | 1.06 |
| June | 37021357.05 | 0.50 | 102.30 | 29-JUN-17:00 | 1.04 |
| July | 0.104253E+09 | 0.95 | 127.43 | 19-JUL-16:25 | 1.02 |
| August | 0.100889E+09 | 0.89 | 124.42 | 17-AUG-16:05 | 1.02 |
| September | 53479623.36 | 0.66 | 143.92 | 29-SEP-15:10 | 1.02 |
| October | 63711971.01 | 0.62 | 148.85 | 16-OCT-11:00 | 1.02 |
| November | 484239.37 | 0.02 | 30.47 | 19-NOV-13:00 | 1.08 |
| December | 5348467.34 | 0.18 | 23.74 | 15-DEC-06:00 | 0.93 |
| Annual Sum or Average | 0.408746E+09 | 0.41 | |||
| Minimum of Months | 484239.37 | 0.02 | 22.51 | 0.93 | |
| Maximum of Months | 0.104253E+09 | 0.95 | 148.85 | 1.08 |
Report: FanReportMonthly
For: G NW APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.64 | 20.01 | 01-JAN-00:10 | 0.64 |
| February | 48400714.57 | 0.64 | 20.01 | 01-FEB-00:10 | 0.64 |
| March | 53586505.42 | 0.64 | 20.01 | 01-MAR-00:10 | 0.64 |
| April | 51857908.47 | 0.64 | 20.01 | 01-APR-00:10 | 0.64 |
| May | 53586505.42 | 0.64 | 20.01 | 01-MAY-00:10 | 0.64 |
| June | 51857908.47 | 0.64 | 20.01 | 01-JUN-00:10 | 0.64 |
| July | 53586505.42 | 0.64 | 20.01 | 01-JUL-00:10 | 0.64 |
| August | 53586505.42 | 0.64 | 20.01 | 01-AUG-00:10 | 0.63 |
| September | 51857908.47 | 0.64 | 20.01 | 01-SEP-00:10 | 0.64 |
| October | 53586505.42 | 0.64 | 20.01 | 01-OCT-00:10 | 0.63 |
| November | 51857908.47 | 0.64 | 20.01 | 01-NOV-00:10 | 0.64 |
| December | 53586505.42 | 0.64 | 20.01 | 01-DEC-00:10 | 0.64 |
| Annual Sum or Average | 0.630938E+09 | 0.64 | |||
| Minimum of Months | 48400714.57 | 0.64 | 20.01 | 0.63 | |
| Maximum of Months | 53586505.42 | 0.64 | 20.01 | 0.64 |
Report: FanReportMonthly
For: G NW APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.64 | 20.01 | 01-JAN-00:10 | 0.64 |
| February | 48400714.57 | 0.64 | 20.01 | 01-FEB-00:10 | 0.64 |
| March | 53586505.42 | 0.64 | 20.01 | 01-MAR-00:10 | 0.64 |
| April | 51857908.47 | 0.64 | 20.01 | 01-APR-00:10 | 0.64 |
| May | 53586505.42 | 0.64 | 20.01 | 01-MAY-00:10 | 0.64 |
| June | 51857908.47 | 0.64 | 20.01 | 01-JUN-00:10 | 0.64 |
| July | 53586505.42 | 0.64 | 20.01 | 01-JUL-00:10 | 0.64 |
| August | 53586505.42 | 0.64 | 20.01 | 01-AUG-00:10 | 0.64 |
| September | 51857908.47 | 0.64 | 20.01 | 01-SEP-00:10 | 0.64 |
| October | 53586505.42 | 0.64 | 20.01 | 01-OCT-00:10 | 0.64 |
| November | 51857908.47 | 0.64 | 20.01 | 01-NOV-00:10 | 0.64 |
| December | 53586505.42 | 0.64 | 20.01 | 01-DEC-00:10 | 0.64 |
| Annual Sum or Average | 0.630938E+09 | 0.64 | |||
| Minimum of Months | 48400714.57 | 0.64 | 20.01 | 0.64 | |
| Maximum of Months | 53586505.42 | 0.64 | 20.01 | 0.64 |
Report: FanReportMonthly
For: SPLIT OFFICE SUPPLY FAN
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.107791E+10 | 0.93 | 402.44 | 01-JAN-00:10 | 0.93 |
| February | 0.973592E+09 | 0.93 | 402.44 | 01-FEB-00:10 | 0.93 |
| March | 0.107791E+10 | 0.93 | 402.44 | 01-MAR-00:10 | 0.93 |
| April | 0.104313E+10 | 0.93 | 402.44 | 01-APR-00:10 | 0.93 |
| May | 0.107791E+10 | 0.93 | 402.44 | 01-MAY-00:10 | 0.93 |
| June | 0.104313E+10 | 0.93 | 402.44 | 01-JUN-00:10 | 0.93 |
| July | 0.107791E+10 | 0.92 | 402.44 | 01-JUL-00:10 | 0.92 |
| August | 0.107791E+10 | 0.92 | 402.44 | 01-AUG-00:10 | 0.92 |
| September | 0.104313E+10 | 0.93 | 402.44 | 01-SEP-00:10 | 0.92 |
| October | 0.107791E+10 | 0.93 | 402.44 | 01-OCT-00:10 | 0.92 |
| November | 0.104313E+10 | 0.93 | 402.44 | 01-NOV-00:10 | 0.93 |
| December | 0.107791E+10 | 0.93 | 402.44 | 01-DEC-00:10 | 0.94 |
| Annual Sum or Average | 0.126915E+11 | 0.93 | |||
| Minimum of Months | 0.973592E+09 | 0.92 | 402.44 | 0.92 | |
| Maximum of Months | 0.107791E+10 | 0.93 | 402.44 | 0.94 |
Report: FanReportMonthly
For: SPLIT GNE SUPPLY FAN
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 11249952.76 | 0.26 | 39.83 | 03-JAN-02:00 | 0.93 |
| February | 7208469.71 | 0.31 | 27.97 | 28-FEB-18:02 | 0.93 |
| March | 13408737.29 | 0.32 | 58.61 | 29-MAR-16:01 | 0.93 |
| April | 4609230.65 | 0.09 | 54.07 | 30-APR-11:00 | 1.06 |
| May | 5430719.83 | 0.13 | 56.40 | 04-MAY-12:00 | 1.06 |
| June | 32992221.34 | 0.43 | 83.99 | 30-JUN-10:00 | 1.04 |
| July | 99515627.82 | 0.91 | 118.10 | 19-JUL-10:40 | 1.02 |
| August | 98969030.45 | 0.88 | 116.05 | 14-AUG-11:00 | 1.02 |
| September | 47506104.85 | 0.57 | 140.57 | 29-SEP-13:00 | 1.02 |
| October | 61538879.78 | 0.59 | 167.61 | 16-OCT-11:00 | 1.01 |
| November | 567376.37 | 0.02 | 32.24 | 19-NOV-13:00 | 1.08 |
| December | 5216947.41 | 0.17 | 23.97 | 24-DEC-06:00 | 0.93 |
| Annual Sum or Average | 0.388213E+09 | 0.39 | |||
| Minimum of Months | 567376.37 | 0.02 | 23.97 | 0.93 | |
| Maximum of Months | 99515627.82 | 0.91 | 167.61 | 1.08 |
Report: FanReportMonthly
For: G NE APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.64 | 20.01 | 01-JAN-00:10 | 0.64 |
| February | 48400714.57 | 0.64 | 20.01 | 01-FEB-00:10 | 0.64 |
| March | 53586505.42 | 0.64 | 20.01 | 01-MAR-00:10 | 0.64 |
| April | 51857908.47 | 0.64 | 20.01 | 01-APR-00:10 | 0.64 |
| May | 53586505.42 | 0.64 | 20.01 | 01-MAY-00:10 | 0.64 |
| June | 51857908.47 | 0.64 | 20.01 | 01-JUN-00:10 | 0.64 |
| July | 53586505.42 | 0.64 | 20.01 | 01-JUL-00:10 | 0.64 |
| August | 53586505.42 | 0.64 | 20.01 | 01-AUG-00:10 | 0.63 |
| September | 51857908.47 | 0.64 | 20.01 | 01-SEP-00:10 | 0.64 |
| October | 53586505.42 | 0.64 | 20.01 | 01-OCT-00:10 | 0.63 |
| November | 51857908.47 | 0.64 | 20.01 | 01-NOV-00:10 | 0.64 |
| December | 53586505.42 | 0.64 | 20.01 | 01-DEC-00:10 | 0.64 |
| Annual Sum or Average | 0.630938E+09 | 0.64 | |||
| Minimum of Months | 48400714.57 | 0.64 | 20.01 | 0.63 | |
| Maximum of Months | 53586505.42 | 0.64 | 20.01 | 0.64 |
Report: FanReportMonthly
For: G NE APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.64 | 20.01 | 01-JAN-00:10 | 0.64 |
| February | 48400714.57 | 0.64 | 20.01 | 01-FEB-00:10 | 0.64 |
| March | 53586505.42 | 0.64 | 20.01 | 01-MAR-00:10 | 0.64 |
| April | 51857908.47 | 0.64 | 20.01 | 01-APR-00:10 | 0.64 |
| May | 53586505.42 | 0.64 | 20.01 | 01-MAY-00:10 | 0.64 |
| June | 51857908.47 | 0.64 | 20.01 | 01-JUN-00:10 | 0.64 |
| July | 53586505.42 | 0.64 | 20.01 | 01-JUL-00:10 | 0.64 |
| August | 53586505.42 | 0.64 | 20.01 | 01-AUG-00:10 | 0.64 |
| September | 51857908.47 | 0.64 | 20.01 | 01-SEP-00:10 | 0.64 |
| October | 53586505.42 | 0.64 | 20.01 | 01-OCT-00:10 | 0.64 |
| November | 51857908.47 | 0.64 | 20.01 | 01-NOV-00:10 | 0.64 |
| December | 53586505.42 | 0.64 | 20.01 | 01-DEC-00:10 | 0.64 |
| Annual Sum or Average | 0.630938E+09 | 0.64 | |||
| Minimum of Months | 48400714.57 | 0.64 | 20.01 | 0.64 | |
| Maximum of Months | 53586505.42 | 0.64 | 20.01 | 0.64 |
Report: FanReportMonthly
For: SPLIT GN1 SUPPLY FAN
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 6080840.67 | 0.21 | 29.32 | 18-JAN-13:00 | 1.08 |
| February | 728277.67 | 0.07 | 9.40 | 10-FEB-05:00 | 0.93 |
| March | 5107059.00 | 0.18 | 25.79 | 30-MAR-03:00 | 0.93 |
| April | 2811272.87 | 0.07 | 36.49 | 26-APR-13:00 | 1.07 |
| May | 4755657.78 | 0.15 | 44.34 | 04-MAY-12:00 | 1.07 |
| June | 32565676.34 | 0.58 | 71.79 | 29-JUN-17:10 | 1.05 |
| July | 91420668.91 | 0.99 | 90.84 | 18-JUL-16:07 | 1.03 |
| August | 90330652.07 | 0.98 | 89.92 | 17-AUG-14:10 | 1.03 |
| September | 50085649.28 | 0.81 | 113.53 | 29-SEP-13:00 | 1.03 |
| October | 62854467.87 | 0.72 | 128.99 | 16-OCT-11:00 | 1.02 |
| November | 519246.53 | 0.02 | 29.43 | 19-NOV-13:00 | 1.08 |
| December | 681590.06 | 0.05 | 15.34 | 05-DEC-15:00 | 1.09 |
| Annual Sum or Average | 0.347941E+09 | 0.41 | |||
| Minimum of Months | 519246.53 | 0.02 | 9.40 | 0.93 | |
| Maximum of Months | 91420668.91 | 0.99 | 128.99 | 1.09 |
Report: FanReportMonthly
For: G N1 APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.64 | 20.01 | 01-JAN-00:10 | 0.64 |
| February | 48400714.57 | 0.64 | 20.01 | 01-FEB-00:10 | 0.64 |
| March | 53586505.42 | 0.64 | 20.01 | 01-MAR-00:10 | 0.64 |
| April | 51857908.47 | 0.64 | 20.01 | 01-APR-00:10 | 0.64 |
| May | 53586505.42 | 0.64 | 20.01 | 01-MAY-00:10 | 0.64 |
| June | 51857908.47 | 0.64 | 20.01 | 01-JUN-00:10 | 0.64 |
| July | 53586505.42 | 0.64 | 20.01 | 01-JUL-00:10 | 0.64 |
| August | 53586505.42 | 0.64 | 20.01 | 01-AUG-00:10 | 0.63 |
| September | 51857908.47 | 0.64 | 20.01 | 01-SEP-00:10 | 0.64 |
| October | 53586505.42 | 0.64 | 20.01 | 01-OCT-00:10 | 0.63 |
| November | 51857908.47 | 0.64 | 20.01 | 01-NOV-00:10 | 0.64 |
| December | 53586505.42 | 0.64 | 20.01 | 01-DEC-00:10 | 0.64 |
| Annual Sum or Average | 0.630938E+09 | 0.64 | |||
| Minimum of Months | 48400714.57 | 0.64 | 20.01 | 0.63 | |
| Maximum of Months | 53586505.42 | 0.64 | 20.01 | 0.64 |
Report: FanReportMonthly
For: G N1 APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.64 | 20.01 | 01-JAN-00:10 | 0.64 |
| February | 48400714.57 | 0.64 | 20.01 | 01-FEB-00:10 | 0.64 |
| March | 53586505.42 | 0.64 | 20.01 | 01-MAR-00:10 | 0.64 |
| April | 51857908.47 | 0.64 | 20.01 | 01-APR-00:10 | 0.64 |
| May | 53586505.42 | 0.64 | 20.01 | 01-MAY-00:10 | 0.64 |
| June | 51857908.47 | 0.64 | 20.01 | 01-JUN-00:10 | 0.64 |
| July | 53586505.42 | 0.64 | 20.01 | 01-JUL-00:10 | 0.64 |
| August | 53586505.42 | 0.64 | 20.01 | 01-AUG-00:10 | 0.64 |
| September | 51857908.47 | 0.64 | 20.01 | 01-SEP-00:10 | 0.64 |
| October | 53586505.42 | 0.64 | 20.01 | 01-OCT-00:10 | 0.64 |
| November | 51857908.47 | 0.64 | 20.01 | 01-NOV-00:10 | 0.64 |
| December | 53586505.42 | 0.64 | 20.01 | 01-DEC-00:10 | 0.64 |
| Annual Sum or Average | 0.630938E+09 | 0.64 | |||
| Minimum of Months | 48400714.57 | 0.64 | 20.01 | 0.64 | |
| Maximum of Months | 53586505.42 | 0.64 | 20.01 | 0.64 |
Report: FanReportMonthly
For: SPLIT GN2 SUPPLY FAN
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 6081969.24 | 0.21 | 29.47 | 18-JAN-13:00 | 1.08 |
| February | 733780.66 | 0.07 | 9.37 | 10-FEB-05:00 | 0.93 |
| March | 5145055.04 | 0.18 | 25.82 | 30-MAR-03:00 | 0.93 |
| April | 2795463.22 | 0.07 | 36.43 | 26-APR-13:00 | 1.07 |
| May | 4695144.06 | 0.14 | 44.57 | 04-MAY-12:00 | 1.07 |
| June | 32205814.91 | 0.57 | 71.02 | 29-JUN-17:10 | 1.05 |
| July | 91123197.72 | 0.99 | 90.55 | 18-JUL-16:07 | 1.03 |
| August | 90203140.12 | 0.98 | 90.26 | 18-AUG-12:00 | 1.03 |
| September | 49525526.47 | 0.80 | 113.61 | 29-SEP-13:00 | 1.03 |
| October | 62747188.58 | 0.72 | 129.48 | 16-OCT-11:00 | 1.02 |
| November | 519627.73 | 0.02 | 29.40 | 19-NOV-13:00 | 1.08 |
| December | 700894.42 | 0.05 | 15.61 | 05-DEC-15:00 | 1.09 |
| Annual Sum or Average | 0.346477E+09 | 0.40 | |||
| Minimum of Months | 519627.73 | 0.02 | 9.37 | 0.93 | |
| Maximum of Months | 91123197.72 | 0.99 | 129.48 | 1.09 |
Report: FanReportMonthly
For: G N2 APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.64 | 20.01 | 01-JAN-00:10 | 0.64 |
| February | 48400714.57 | 0.64 | 20.01 | 01-FEB-00:10 | 0.64 |
| March | 53586505.42 | 0.64 | 20.01 | 01-MAR-00:10 | 0.64 |
| April | 51857908.47 | 0.64 | 20.01 | 01-APR-00:10 | 0.64 |
| May | 53586505.42 | 0.64 | 20.01 | 01-MAY-00:10 | 0.64 |
| June | 51857908.47 | 0.64 | 20.01 | 01-JUN-00:10 | 0.64 |
| July | 53586505.42 | 0.64 | 20.01 | 01-JUL-00:10 | 0.64 |
| August | 53586505.42 | 0.64 | 20.01 | 01-AUG-00:10 | 0.63 |
| September | 51857908.47 | 0.64 | 20.01 | 01-SEP-00:10 | 0.64 |
| October | 53586505.42 | 0.64 | 20.01 | 01-OCT-00:10 | 0.63 |
| November | 51857908.47 | 0.64 | 20.01 | 01-NOV-00:10 | 0.64 |
| December | 53586505.42 | 0.64 | 20.01 | 01-DEC-00:10 | 0.64 |
| Annual Sum or Average | 0.630938E+09 | 0.64 | |||
| Minimum of Months | 48400714.57 | 0.64 | 20.01 | 0.63 | |
| Maximum of Months | 53586505.42 | 0.64 | 20.01 | 0.64 |
Report: FanReportMonthly
For: G N2 APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.64 | 20.01 | 01-JAN-00:10 | 0.64 |
| February | 48400714.57 | 0.64 | 20.01 | 01-FEB-00:10 | 0.64 |
| March | 53586505.42 | 0.64 | 20.01 | 01-MAR-00:10 | 0.64 |
| April | 51857908.47 | 0.64 | 20.01 | 01-APR-00:10 | 0.64 |
| May | 53586505.42 | 0.64 | 20.01 | 01-MAY-00:10 | 0.64 |
| June | 51857908.47 | 0.64 | 20.01 | 01-JUN-00:10 | 0.64 |
| July | 53586505.42 | 0.64 | 20.01 | 01-JUL-00:10 | 0.64 |
| August | 53586505.42 | 0.64 | 20.01 | 01-AUG-00:10 | 0.64 |
| September | 51857908.47 | 0.64 | 20.01 | 01-SEP-00:10 | 0.64 |
| October | 53586505.42 | 0.64 | 20.01 | 01-OCT-00:10 | 0.64 |
| November | 51857908.47 | 0.64 | 20.01 | 01-NOV-00:10 | 0.64 |
| December | 53586505.42 | 0.64 | 20.01 | 01-DEC-00:10 | 0.64 |
| Annual Sum or Average | 0.630938E+09 | 0.64 | |||
| Minimum of Months | 48400714.57 | 0.64 | 20.01 | 0.64 | |
| Maximum of Months | 53586505.42 | 0.64 | 20.01 | 0.64 |
Report: FanReportMonthly
For: SPLIT GS1 SUPPLY FAN
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 35059244.49 | 0.48 | 104.31 | 18-JAN-13:30 | 1.04 |
| February | 13650927.85 | 0.23 | 92.33 | 01-FEB-12:00 | 1.05 |
| March | 6114395.61 | 0.13 | 55.90 | 23-MAR-14:00 | 1.06 |
| April | 17878784.59 | 0.31 | 73.56 | 26-APR-13:00 | 1.05 |
| May | 10012995.22 | 0.24 | 62.35 | 04-MAY-12:00 | 1.06 |
| June | 33280845.94 | 0.55 | 68.14 | 29-JUN-16:03 | 1.05 |
| July | 99408298.86 | 0.99 | 106.57 | 31-JUL-13:00 | 1.03 |
| August | 0.123084E+09 | 1.02 | 114.78 | 19-AUG-13:00 | 1.03 |
| September | 0.106033E+09 | 0.97 | 171.54 | 29-SEP-13:00 | 1.01 |
| October | 0.135443E+09 | 0.94 | 199.22 | 16-OCT-12:00 | 0.99 |
| November | 52787062.60 | 0.70 | 133.16 | 19-NOV-13:00 | 1.02 |
| December | 49640451.11 | 0.56 | 126.25 | 19-DEC-13:00 | 1.04 |
| Annual Sum or Average | 0.682392E+09 | 0.60 | |||
| Minimum of Months | 6114395.61 | 0.13 | 55.90 | 0.99 | |
| Maximum of Months | 0.135443E+09 | 1.02 | 199.22 | 1.06 |
Report: FanReportMonthly
For: G S1 APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.64 | 20.01 | 01-JAN-00:10 | 0.64 |
| February | 48400714.57 | 0.64 | 20.01 | 01-FEB-00:10 | 0.64 |
| March | 53586505.42 | 0.64 | 20.01 | 01-MAR-00:10 | 0.64 |
| April | 51857908.47 | 0.64 | 20.01 | 01-APR-00:10 | 0.64 |
| May | 53586505.42 | 0.64 | 20.01 | 01-MAY-00:10 | 0.64 |
| June | 51857908.47 | 0.64 | 20.01 | 01-JUN-00:10 | 0.64 |
| July | 53586505.42 | 0.64 | 20.01 | 01-JUL-00:10 | 0.64 |
| August | 53586505.42 | 0.64 | 20.01 | 01-AUG-00:10 | 0.63 |
| September | 51857908.47 | 0.64 | 20.01 | 01-SEP-00:10 | 0.64 |
| October | 53586505.42 | 0.64 | 20.01 | 01-OCT-00:10 | 0.63 |
| November | 51857908.47 | 0.64 | 20.01 | 01-NOV-00:10 | 0.64 |
| December | 53586505.42 | 0.64 | 20.01 | 01-DEC-00:10 | 0.64 |
| Annual Sum or Average | 0.630938E+09 | 0.64 | |||
| Minimum of Months | 48400714.57 | 0.64 | 20.01 | 0.63 | |
| Maximum of Months | 53586505.42 | 0.64 | 20.01 | 0.64 |
Report: FanReportMonthly
For: G S1 APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.64 | 20.01 | 01-JAN-00:10 | 0.64 |
| February | 48400714.57 | 0.64 | 20.01 | 01-FEB-00:10 | 0.64 |
| March | 53586505.42 | 0.64 | 20.01 | 01-MAR-00:10 | 0.64 |
| April | 51857908.47 | 0.64 | 20.01 | 01-APR-00:10 | 0.64 |
| May | 53586505.42 | 0.64 | 20.01 | 01-MAY-00:10 | 0.64 |
| June | 51857908.47 | 0.64 | 20.01 | 01-JUN-00:10 | 0.64 |
| July | 53586505.42 | 0.64 | 20.01 | 01-JUL-00:10 | 0.64 |
| August | 53586505.42 | 0.64 | 20.01 | 01-AUG-00:10 | 0.64 |
| September | 51857908.47 | 0.64 | 20.01 | 01-SEP-00:10 | 0.64 |
| October | 53586505.42 | 0.64 | 20.01 | 01-OCT-00:10 | 0.64 |
| November | 51857908.47 | 0.64 | 20.01 | 01-NOV-00:10 | 0.64 |
| December | 53586505.42 | 0.64 | 20.01 | 01-DEC-00:10 | 0.64 |
| Annual Sum or Average | 0.630938E+09 | 0.64 | |||
| Minimum of Months | 48400714.57 | 0.64 | 20.01 | 0.64 | |
| Maximum of Months | 53586505.42 | 0.64 | 20.01 | 0.64 |
Report: FanReportMonthly
For: SPLIT GS2 SUPPLY FAN
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 37929191.71 | 0.50 | 107.19 | 18-JAN-13:30 | 1.04 |
| February | 14929369.19 | 0.26 | 94.97 | 01-FEB-12:00 | 1.05 |
| March | 6846009.58 | 0.13 | 60.01 | 23-MAR-14:00 | 1.06 |
| April | 19947170.79 | 0.34 | 76.61 | 26-APR-13:00 | 1.05 |
| May | 11711045.96 | 0.27 | 65.46 | 04-MAY-12:00 | 1.06 |
| June | 37386337.08 | 0.59 | 70.83 | 29-JUN-16:03 | 1.05 |
| July | 0.109331E+09 | 1.01 | 111.09 | 31-JUL-13:00 | 1.03 |
| August | 0.134465E+09 | 1.03 | 121.00 | 19-AUG-13:00 | 1.02 |
| September | 0.114620E+09 | 0.99 | 175.20 | 29-SEP-13:00 | 1.00 |
| October | 0.146871E+09 | 0.97 | 206.76 | 16-OCT-12:00 | 0.99 |
| November | 56818793.77 | 0.73 | 137.77 | 19-NOV-13:00 | 1.02 |
| December | 52772842.52 | 0.58 | 129.21 | 19-DEC-13:00 | 1.04 |
| Annual Sum or Average | 0.743627E+09 | 0.62 | |||
| Minimum of Months | 6846009.58 | 0.13 | 60.01 | 0.99 | |
| Maximum of Months | 0.146871E+09 | 1.03 | 206.76 | 1.06 |
Report: FanReportMonthly
For: G S2 APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.64 | 20.01 | 01-JAN-00:10 | 0.64 |
| February | 48400714.57 | 0.64 | 20.01 | 01-FEB-00:10 | 0.64 |
| March | 53586505.42 | 0.64 | 20.01 | 01-MAR-00:10 | 0.64 |
| April | 51857908.47 | 0.64 | 20.01 | 01-APR-00:10 | 0.64 |
| May | 53586505.42 | 0.64 | 20.01 | 01-MAY-00:10 | 0.64 |
| June | 51857908.47 | 0.64 | 20.01 | 01-JUN-00:10 | 0.64 |
| July | 53586505.42 | 0.64 | 20.01 | 01-JUL-00:10 | 0.64 |
| August | 53586505.42 | 0.64 | 20.01 | 01-AUG-00:10 | 0.63 |
| September | 51857908.47 | 0.64 | 20.01 | 01-SEP-00:10 | 0.64 |
| October | 53586505.42 | 0.64 | 20.01 | 01-OCT-00:10 | 0.63 |
| November | 51857908.47 | 0.64 | 20.01 | 01-NOV-00:10 | 0.64 |
| December | 53586505.42 | 0.64 | 20.01 | 01-DEC-00:10 | 0.64 |
| Annual Sum or Average | 0.630938E+09 | 0.64 | |||
| Minimum of Months | 48400714.57 | 0.64 | 20.01 | 0.63 | |
| Maximum of Months | 53586505.42 | 0.64 | 20.01 | 0.64 |
Report: FanReportMonthly
For: G S2 APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.64 | 20.01 | 01-JAN-00:10 | 0.64 |
| February | 48400714.57 | 0.64 | 20.01 | 01-FEB-00:10 | 0.64 |
| March | 53586505.42 | 0.64 | 20.01 | 01-MAR-00:10 | 0.64 |
| April | 51857908.47 | 0.64 | 20.01 | 01-APR-00:10 | 0.64 |
| May | 53586505.42 | 0.64 | 20.01 | 01-MAY-00:10 | 0.64 |
| June | 51857908.47 | 0.64 | 20.01 | 01-JUN-00:10 | 0.64 |
| July | 53586505.42 | 0.64 | 20.01 | 01-JUL-00:10 | 0.64 |
| August | 53586505.42 | 0.64 | 20.01 | 01-AUG-00:10 | 0.64 |
| September | 51857908.47 | 0.64 | 20.01 | 01-SEP-00:10 | 0.64 |
| October | 53586505.42 | 0.64 | 20.01 | 01-OCT-00:10 | 0.64 |
| November | 51857908.47 | 0.64 | 20.01 | 01-NOV-00:10 | 0.64 |
| December | 53586505.42 | 0.64 | 20.01 | 01-DEC-00:10 | 0.64 |
| Annual Sum or Average | 0.630938E+09 | 0.64 | |||
| Minimum of Months | 48400714.57 | 0.64 | 20.01 | 0.64 | |
| Maximum of Months | 53586505.42 | 0.64 | 20.01 | 0.64 |
Report: FanReportMonthly
For: SPLIT MSW SUPPLY FAN
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.109098E+09 | 0.50 | 332.28 | 14-JAN-15:00 | 1.04 |
| February | 72297751.21 | 0.36 | 296.52 | 03-FEB-15:00 | 1.05 |
| March | 61042646.44 | 0.32 | 280.45 | 23-MAR-15:30 | 1.04 |
| April | 0.148653E+09 | 0.63 | 292.30 | 26-APR-14:10 | 1.04 |
| May | 0.109214E+09 | 0.58 | 232.20 | 03-MAY-15:10 | 1.05 |
| June | 0.207495E+09 | 0.90 | 295.63 | 29-JUN-16:25 | 1.03 |
| July | 0.357921E+09 | 1.04 | 344.09 | 23-JUL-16:30 | 1.02 |
| August | 0.393186E+09 | 1.04 | 368.47 | 17-AUG-15:10 | 1.02 |
| September | 0.315865E+09 | 0.98 | 495.53 | 29-SEP-13:30 | 1.00 |
| October | 0.335780E+09 | 0.86 | 525.67 | 16-OCT-12:00 | 1.00 |
| November | 0.140870E+09 | 0.61 | 371.11 | 19-NOV-13:00 | 1.03 |
| December | 0.138383E+09 | 0.53 | 349.81 | 19-DEC-13:00 | 1.04 |
| Annual Sum or Average | 0.238980E+10 | 0.70 | |||
| Minimum of Months | 61042646.44 | 0.32 | 232.20 | 1.00 | |
| Maximum of Months | 0.393186E+09 | 1.04 | 525.67 | 1.05 |
Report: FanReportMonthly
For: M SW APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.107173E+09 | 0.64 | 40.01 | 01-JAN-00:10 | 0.64 |
| February | 96801429.15 | 0.64 | 40.01 | 01-FEB-00:10 | 0.64 |
| March | 0.107173E+09 | 0.64 | 40.01 | 01-MAR-00:10 | 0.64 |
| April | 0.103716E+09 | 0.64 | 40.01 | 01-APR-00:10 | 0.64 |
| May | 0.107173E+09 | 0.64 | 40.01 | 01-MAY-00:10 | 0.64 |
| June | 0.103716E+09 | 0.64 | 40.01 | 01-JUN-00:10 | 0.64 |
| July | 0.107173E+09 | 0.64 | 40.01 | 01-JUL-00:10 | 0.64 |
| August | 0.107173E+09 | 0.64 | 40.01 | 01-AUG-00:10 | 0.63 |
| September | 0.103716E+09 | 0.64 | 40.01 | 01-SEP-00:10 | 0.64 |
| October | 0.107173E+09 | 0.64 | 40.01 | 01-OCT-00:10 | 0.63 |
| November | 0.103716E+09 | 0.64 | 40.01 | 01-NOV-00:10 | 0.64 |
| December | 0.107173E+09 | 0.64 | 40.01 | 01-DEC-00:10 | 0.64 |
| Annual Sum or Average | 0.126188E+10 | 0.64 | |||
| Minimum of Months | 96801429.15 | 0.64 | 40.01 | 0.63 | |
| Maximum of Months | 0.107173E+09 | 0.64 | 40.01 | 0.64 |
Report: FanReportMonthly
For: M SW APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.107173E+09 | 0.64 | 40.01 | 01-JAN-00:10 | 0.64 |
| February | 96801429.15 | 0.64 | 40.01 | 01-FEB-00:10 | 0.64 |
| March | 0.107173E+09 | 0.64 | 40.01 | 01-MAR-00:10 | 0.64 |
| April | 0.103716E+09 | 0.64 | 40.01 | 01-APR-00:10 | 0.64 |
| May | 0.107173E+09 | 0.64 | 40.01 | 01-MAY-00:10 | 0.64 |
| June | 0.103716E+09 | 0.64 | 40.01 | 01-JUN-00:10 | 0.64 |
| July | 0.107173E+09 | 0.64 | 40.01 | 01-JUL-00:10 | 0.64 |
| August | 0.107173E+09 | 0.64 | 40.01 | 01-AUG-00:10 | 0.64 |
| September | 0.103716E+09 | 0.64 | 40.01 | 01-SEP-00:10 | 0.64 |
| October | 0.107173E+09 | 0.64 | 40.01 | 01-OCT-00:10 | 0.64 |
| November | 0.103716E+09 | 0.64 | 40.01 | 01-NOV-00:10 | 0.64 |
| December | 0.107173E+09 | 0.64 | 40.01 | 01-DEC-00:10 | 0.64 |
| Annual Sum or Average | 0.126188E+10 | 0.64 | |||
| Minimum of Months | 96801429.15 | 0.64 | 40.01 | 0.64 | |
| Maximum of Months | 0.107173E+09 | 0.64 | 40.01 | 0.64 |
Report: FanReportMonthly
For: SPLIT MNW SUPPLY FAN
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 22043111.44 | 0.25 | 134.06 | 18-JAN-14:30 | 1.07 |
| February | 1992823.46 | 0.03 | 91.01 | 03-FEB-15:10 | 1.09 |
| March | 15285971.38 | 0.17 | 174.13 | 23-MAR-16:05 | 1.05 |
| April | 72799210.17 | 0.46 | 245.77 | 26-APR-16:20 | 1.04 |
| May | 93090380.50 | 0.56 | 209.27 | 03-MAY-16:10 | 1.05 |
| June | 0.207671E+09 | 0.92 | 303.39 | 29-JUN-17:10 | 1.03 |
| July | 0.341167E+09 | 1.04 | 339.85 | 19-JUL-16:25 | 1.02 |
| August | 0.326397E+09 | 1.03 | 327.62 | 17-AUG-16:05 | 1.02 |
| September | 0.200752E+09 | 0.93 | 374.67 | 29-SEP-15:20 | 1.02 |
| October | 0.184732E+09 | 0.75 | 355.44 | 14-OCT-15:10 | 1.03 |
| November | 8247913.20 | 0.11 | 127.50 | 19-NOV-13:30 | 1.07 |
| December | 9947479.43 | 0.13 | 131.26 | 05-DEC-15:10 | 1.07 |
| Annual Sum or Average | 0.148413E+10 | 0.53 | |||
| Minimum of Months | 1992823.46 | 0.03 | 91.01 | 1.02 | |
| Maximum of Months | 0.341167E+09 | 1.04 | 374.67 | 1.09 |
Report: FanReportMonthly
For: M NW APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.107173E+09 | 0.64 | 40.01 | 01-JAN-00:10 | 0.64 |
| February | 96801429.15 | 0.64 | 40.01 | 01-FEB-00:10 | 0.64 |
| March | 0.107173E+09 | 0.64 | 40.01 | 01-MAR-00:10 | 0.64 |
| April | 0.103716E+09 | 0.64 | 40.01 | 01-APR-00:10 | 0.64 |
| May | 0.107173E+09 | 0.64 | 40.01 | 01-MAY-00:10 | 0.64 |
| June | 0.103716E+09 | 0.64 | 40.01 | 01-JUN-00:10 | 0.64 |
| July | 0.107173E+09 | 0.64 | 40.01 | 01-JUL-00:10 | 0.64 |
| August | 0.107173E+09 | 0.64 | 40.01 | 01-AUG-00:10 | 0.63 |
| September | 0.103716E+09 | 0.64 | 40.01 | 01-SEP-00:10 | 0.64 |
| October | 0.107173E+09 | 0.64 | 40.01 | 01-OCT-00:10 | 0.63 |
| November | 0.103716E+09 | 0.64 | 40.01 | 01-NOV-00:10 | 0.64 |
| December | 0.107173E+09 | 0.64 | 40.01 | 01-DEC-00:10 | 0.64 |
| Annual Sum or Average | 0.126188E+10 | 0.64 | |||
| Minimum of Months | 96801429.15 | 0.64 | 40.01 | 0.63 | |
| Maximum of Months | 0.107173E+09 | 0.64 | 40.01 | 0.64 |
Report: FanReportMonthly
For: M NW APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.107173E+09 | 0.64 | 40.01 | 01-JAN-00:10 | 0.64 |
| February | 96801429.15 | 0.64 | 40.01 | 01-FEB-00:10 | 0.64 |
| March | 0.107173E+09 | 0.64 | 40.01 | 01-MAR-00:10 | 0.64 |
| April | 0.103716E+09 | 0.64 | 40.01 | 01-APR-00:10 | 0.64 |
| May | 0.107173E+09 | 0.64 | 40.01 | 01-MAY-00:10 | 0.64 |
| June | 0.103716E+09 | 0.64 | 40.01 | 01-JUN-00:10 | 0.64 |
| July | 0.107173E+09 | 0.64 | 40.01 | 01-JUL-00:10 | 0.64 |
| August | 0.107173E+09 | 0.64 | 40.01 | 01-AUG-00:10 | 0.64 |
| September | 0.103716E+09 | 0.64 | 40.01 | 01-SEP-00:10 | 0.64 |
| October | 0.107173E+09 | 0.64 | 40.01 | 01-OCT-00:10 | 0.64 |
| November | 0.103716E+09 | 0.64 | 40.01 | 01-NOV-00:10 | 0.64 |
| December | 0.107173E+09 | 0.64 | 40.01 | 01-DEC-00:10 | 0.64 |
| Annual Sum or Average | 0.126188E+10 | 0.64 | |||
| Minimum of Months | 96801429.15 | 0.64 | 40.01 | 0.64 | |
| Maximum of Months | 0.107173E+09 | 0.64 | 40.01 | 0.64 |
Report: FanReportMonthly
For: SPLIT MSE SUPPLY FAN
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.113628E+09 | 0.52 | 303.48 | 18-JAN-13:30 | 1.03 |
| February | 71339864.11 | 0.38 | 290.45 | 01-FEB-12:00 | 1.04 |
| March | 60642181.64 | 0.33 | 248.24 | 23-MAR-14:00 | 1.04 |
| April | 0.144133E+09 | 0.64 | 297.54 | 26-APR-13:00 | 1.03 |
| May | 99910714.10 | 0.58 | 233.35 | 04-MAY-12:00 | 1.04 |
| June | 0.193514E+09 | 0.90 | 249.00 | 30-JUN-10:00 | 1.04 |
| July | 0.348300E+09 | 1.03 | 324.94 | 23-JUL-11:00 | 1.02 |
| August | 0.389761E+09 | 1.04 | 350.62 | 14-AUG-11:00 | 1.02 |
| September | 0.299598E+09 | 0.97 | 499.20 | 29-SEP-13:00 | 0.99 |
| October | 0.330511E+09 | 0.87 | 559.68 | 16-OCT-11:00 | 0.98 |
| November | 0.136564E+09 | 0.62 | 375.46 | 19-NOV-13:00 | 1.02 |
| December | 0.139314E+09 | 0.55 | 354.33 | 19-DEC-13:00 | 1.03 |
| Annual Sum or Average | 0.232722E+10 | 0.70 | |||
| Minimum of Months | 60642181.64 | 0.33 | 233.35 | 0.98 | |
| Maximum of Months | 0.389761E+09 | 1.04 | 559.68 | 1.04 |
Report: FanReportMonthly
For: M SE APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.107173E+09 | 0.64 | 40.01 | 01-JAN-00:10 | 0.64 |
| February | 96801429.15 | 0.64 | 40.01 | 01-FEB-00:10 | 0.64 |
| March | 0.107173E+09 | 0.64 | 40.01 | 01-MAR-00:10 | 0.64 |
| April | 0.103716E+09 | 0.64 | 40.01 | 01-APR-00:10 | 0.64 |
| May | 0.107173E+09 | 0.64 | 40.01 | 01-MAY-00:10 | 0.64 |
| June | 0.103716E+09 | 0.64 | 40.01 | 01-JUN-00:10 | 0.64 |
| July | 0.107173E+09 | 0.64 | 40.01 | 01-JUL-00:10 | 0.64 |
| August | 0.107173E+09 | 0.64 | 40.01 | 01-AUG-00:10 | 0.63 |
| September | 0.103716E+09 | 0.64 | 40.01 | 01-SEP-00:10 | 0.64 |
| October | 0.107173E+09 | 0.64 | 40.01 | 01-OCT-00:10 | 0.63 |
| November | 0.103716E+09 | 0.64 | 40.01 | 01-NOV-00:10 | 0.64 |
| December | 0.107173E+09 | 0.64 | 40.01 | 01-DEC-00:10 | 0.64 |
| Annual Sum or Average | 0.126188E+10 | 0.64 | |||
| Minimum of Months | 96801429.15 | 0.64 | 40.01 | 0.63 | |
| Maximum of Months | 0.107173E+09 | 0.64 | 40.01 | 0.64 |
Report: FanReportMonthly
For: M SE APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.107173E+09 | 0.64 | 40.01 | 01-JAN-00:10 | 0.64 |
| February | 96801429.15 | 0.64 | 40.01 | 01-FEB-00:10 | 0.64 |
| March | 0.107173E+09 | 0.64 | 40.01 | 01-MAR-00:10 | 0.64 |
| April | 0.103716E+09 | 0.64 | 40.01 | 01-APR-00:10 | 0.64 |
| May | 0.107173E+09 | 0.64 | 40.01 | 01-MAY-00:10 | 0.64 |
| June | 0.103716E+09 | 0.64 | 40.01 | 01-JUN-00:10 | 0.64 |
| July | 0.107173E+09 | 0.64 | 40.01 | 01-JUL-00:10 | 0.64 |
| August | 0.107173E+09 | 0.64 | 40.01 | 01-AUG-00:10 | 0.64 |
| September | 0.103716E+09 | 0.64 | 40.01 | 01-SEP-00:10 | 0.64 |
| October | 0.107173E+09 | 0.64 | 40.01 | 01-OCT-00:10 | 0.64 |
| November | 0.103716E+09 | 0.64 | 40.01 | 01-NOV-00:10 | 0.64 |
| December | 0.107173E+09 | 0.64 | 40.01 | 01-DEC-00:10 | 0.64 |
| Annual Sum or Average | 0.126188E+10 | 0.64 | |||
| Minimum of Months | 96801429.15 | 0.64 | 40.01 | 0.64 | |
| Maximum of Months | 0.107173E+09 | 0.64 | 40.01 | 0.64 |
Report: FanReportMonthly
For: SPLIT MNE SUPPLY FAN
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 22287933.60 | 0.24 | 125.82 | 18-JAN-13:00 | 1.07 |
| February | 1838089.23 | 0.03 | 82.14 | 01-FEB-12:00 | 1.08 |
| March | 15814676.48 | 0.18 | 117.10 | 23-MAR-14:00 | 1.06 |
| April | 67287904.40 | 0.45 | 226.57 | 26-APR-11:00 | 1.04 |
| May | 84115380.62 | 0.57 | 196.61 | 04-MAY-12:00 | 1.05 |
| June | 0.193845E+09 | 0.91 | 252.43 | 30-JUN-10:00 | 1.03 |
| July | 0.331595E+09 | 1.03 | 308.19 | 19-JUL-10:10 | 1.02 |
| August | 0.323084E+09 | 1.03 | 300.38 | 14-AUG-11:00 | 1.02 |
| September | 0.184462E+09 | 0.91 | 362.21 | 29-SEP-13:00 | 1.02 |
| October | 0.178639E+09 | 0.74 | 403.06 | 16-OCT-11:00 | 1.01 |
| November | 7012976.75 | 0.08 | 131.60 | 19-NOV-13:00 | 1.07 |
| December | 10386417.04 | 0.14 | 104.74 | 05-DEC-10:00 | 1.08 |
| Annual Sum or Average | 0.142037E+10 | 0.53 | |||
| Minimum of Months | 1838089.23 | 0.03 | 82.14 | 1.01 | |
| Maximum of Months | 0.331595E+09 | 1.03 | 403.06 | 1.08 |
Report: FanReportMonthly
For: M NE APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.107173E+09 | 0.64 | 40.01 | 01-JAN-00:10 | 0.64 |
| February | 96801429.15 | 0.64 | 40.01 | 01-FEB-00:10 | 0.64 |
| March | 0.107173E+09 | 0.64 | 40.01 | 01-MAR-00:10 | 0.64 |
| April | 0.103716E+09 | 0.64 | 40.01 | 01-APR-00:10 | 0.64 |
| May | 0.107173E+09 | 0.64 | 40.01 | 01-MAY-00:10 | 0.64 |
| June | 0.103716E+09 | 0.64 | 40.01 | 01-JUN-00:10 | 0.64 |
| July | 0.107173E+09 | 0.64 | 40.01 | 01-JUL-00:10 | 0.64 |
| August | 0.107173E+09 | 0.64 | 40.01 | 01-AUG-00:10 | 0.63 |
| September | 0.103716E+09 | 0.64 | 40.01 | 01-SEP-00:10 | 0.64 |
| October | 0.107173E+09 | 0.64 | 40.01 | 01-OCT-00:10 | 0.63 |
| November | 0.103716E+09 | 0.64 | 40.01 | 01-NOV-00:10 | 0.64 |
| December | 0.107173E+09 | 0.64 | 40.01 | 01-DEC-00:10 | 0.64 |
| Annual Sum or Average | 0.126188E+10 | 0.64 | |||
| Minimum of Months | 96801429.15 | 0.64 | 40.01 | 0.63 | |
| Maximum of Months | 0.107173E+09 | 0.64 | 40.01 | 0.64 |
Report: FanReportMonthly
For: M NE APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.107173E+09 | 0.64 | 40.01 | 01-JAN-00:10 | 0.64 |
| February | 96801429.15 | 0.64 | 40.01 | 01-FEB-00:10 | 0.64 |
| March | 0.107173E+09 | 0.64 | 40.01 | 01-MAR-00:10 | 0.64 |
| April | 0.103716E+09 | 0.64 | 40.01 | 01-APR-00:10 | 0.64 |
| May | 0.107173E+09 | 0.64 | 40.01 | 01-MAY-00:10 | 0.64 |
| June | 0.103716E+09 | 0.64 | 40.01 | 01-JUN-00:10 | 0.64 |
| July | 0.107173E+09 | 0.64 | 40.01 | 01-JUL-00:10 | 0.64 |
| August | 0.107173E+09 | 0.64 | 40.01 | 01-AUG-00:10 | 0.64 |
| September | 0.103716E+09 | 0.64 | 40.01 | 01-SEP-00:10 | 0.64 |
| October | 0.107173E+09 | 0.64 | 40.01 | 01-OCT-00:10 | 0.64 |
| November | 0.103716E+09 | 0.64 | 40.01 | 01-NOV-00:10 | 0.64 |
| December | 0.107173E+09 | 0.64 | 40.01 | 01-DEC-00:10 | 0.64 |
| Annual Sum or Average | 0.126188E+10 | 0.64 | |||
| Minimum of Months | 96801429.15 | 0.64 | 40.01 | 0.64 | |
| Maximum of Months | 0.107173E+09 | 0.64 | 40.01 | 0.64 |
Report: FanReportMonthly
For: SPLIT MN1 SUPPLY FAN
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 17159594.08 | 0.20 | 118.91 | 18-JAN-13:00 | 1.07 |
| February | 2461527.18 | 0.05 | 75.83 | 01-FEB-12:00 | 1.08 |
| March | 8754821.89 | 0.12 | 93.71 | 23-MAR-16:05 | 1.07 |
| April | 57553375.81 | 0.55 | 166.26 | 26-APR-13:00 | 1.05 |
| May | 82248709.45 | 0.73 | 145.21 | 04-MAY-12:00 | 1.06 |
| June | 0.176482E+09 | 1.02 | 202.20 | 29-JUN-17:15 | 1.04 |
| July | 0.279648E+09 | 1.06 | 230.23 | 18-JUL-17:50 | 1.03 |
| August | 0.272590E+09 | 1.05 | 221.78 | 17-AUG-14:10 | 1.03 |
| September | 0.176122E+09 | 0.99 | 276.47 | 29-SEP-13:00 | 1.03 |
| October | 0.174132E+09 | 0.84 | 296.10 | 16-OCT-11:00 | 1.03 |
| November | 13918720.98 | 0.24 | 114.02 | 19-NOV-13:00 | 1.07 |
| December | 11727876.74 | 0.14 | 96.94 | 05-DEC-15:00 | 1.08 |
| Annual Sum or Average | 0.127280E+10 | 0.58 | |||
| Minimum of Months | 2461527.18 | 0.05 | 75.83 | 1.03 | |
| Maximum of Months | 0.279648E+09 | 1.06 | 296.10 | 1.08 |
Report: FanReportMonthly
For: M N1 APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.107173E+09 | 0.64 | 40.01 | 01-JAN-00:10 | 0.64 |
| February | 96801429.15 | 0.64 | 40.01 | 01-FEB-00:10 | 0.64 |
| March | 0.107173E+09 | 0.64 | 40.01 | 01-MAR-00:10 | 0.64 |
| April | 0.103716E+09 | 0.64 | 40.01 | 01-APR-00:10 | 0.64 |
| May | 0.107173E+09 | 0.64 | 40.01 | 01-MAY-00:10 | 0.64 |
| June | 0.103716E+09 | 0.64 | 40.01 | 01-JUN-00:10 | 0.64 |
| July | 0.107173E+09 | 0.64 | 40.01 | 01-JUL-00:10 | 0.64 |
| August | 0.107173E+09 | 0.64 | 40.01 | 01-AUG-00:10 | 0.63 |
| September | 0.103716E+09 | 0.64 | 40.01 | 01-SEP-00:10 | 0.64 |
| October | 0.107173E+09 | 0.64 | 40.01 | 01-OCT-00:10 | 0.63 |
| November | 0.103716E+09 | 0.64 | 40.01 | 01-NOV-00:10 | 0.64 |
| December | 0.107173E+09 | 0.64 | 40.01 | 01-DEC-00:10 | 0.64 |
| Annual Sum or Average | 0.126188E+10 | 0.64 | |||
| Minimum of Months | 96801429.15 | 0.64 | 40.01 | 0.63 | |
| Maximum of Months | 0.107173E+09 | 0.64 | 40.01 | 0.64 |
Report: FanReportMonthly
For: M N1 APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.107173E+09 | 0.64 | 40.01 | 01-JAN-00:10 | 0.64 |
| February | 96801429.15 | 0.64 | 40.01 | 01-FEB-00:10 | 0.64 |
| March | 0.107173E+09 | 0.64 | 40.01 | 01-MAR-00:10 | 0.64 |
| April | 0.103716E+09 | 0.64 | 40.01 | 01-APR-00:10 | 0.64 |
| May | 0.107173E+09 | 0.64 | 40.01 | 01-MAY-00:10 | 0.64 |
| June | 0.103716E+09 | 0.64 | 40.01 | 01-JUN-00:10 | 0.64 |
| July | 0.107173E+09 | 0.64 | 40.01 | 01-JUL-00:10 | 0.64 |
| August | 0.107173E+09 | 0.64 | 40.01 | 01-AUG-00:10 | 0.64 |
| September | 0.103716E+09 | 0.64 | 40.01 | 01-SEP-00:10 | 0.64 |
| October | 0.107173E+09 | 0.64 | 40.01 | 01-OCT-00:10 | 0.64 |
| November | 0.103716E+09 | 0.64 | 40.01 | 01-NOV-00:10 | 0.64 |
| December | 0.107173E+09 | 0.64 | 40.01 | 01-DEC-00:10 | 0.64 |
| Annual Sum or Average | 0.126188E+10 | 0.64 | |||
| Minimum of Months | 96801429.15 | 0.64 | 40.01 | 0.64 | |
| Maximum of Months | 0.107173E+09 | 0.64 | 40.01 | 0.64 |
Report: FanReportMonthly
For: SPLIT MN2 SUPPLY FAN
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 17352651.61 | 0.20 | 119.50 | 18-JAN-13:00 | 1.07 |
| February | 2432057.69 | 0.05 | 76.35 | 01-FEB-12:00 | 1.08 |
| March | 9105059.69 | 0.13 | 94.36 | 23-MAR-14:10 | 1.07 |
| April | 57563355.38 | 0.55 | 167.21 | 26-APR-13:00 | 1.05 |
| May | 82010501.54 | 0.73 | 146.21 | 04-MAY-12:00 | 1.06 |
| June | 0.175897E+09 | 1.02 | 200.68 | 29-JUN-17:15 | 1.04 |
| July | 0.279239E+09 | 1.05 | 229.19 | 18-JUL-17:50 | 1.03 |
| August | 0.272447E+09 | 1.05 | 222.16 | 17-AUG-14:10 | 1.03 |
| September | 0.175377E+09 | 0.99 | 277.21 | 29-SEP-13:00 | 1.03 |
| October | 0.174128E+09 | 0.84 | 297.36 | 16-OCT-11:00 | 1.03 |
| November | 13651999.36 | 0.23 | 114.37 | 19-NOV-13:00 | 1.07 |
| December | 11851112.37 | 0.14 | 97.34 | 05-DEC-15:00 | 1.08 |
| Annual Sum or Average | 0.127105E+10 | 0.58 | |||
| Minimum of Months | 2432057.69 | 0.05 | 76.35 | 1.03 | |
| Maximum of Months | 0.279239E+09 | 1.05 | 297.36 | 1.08 |
Report: FanReportMonthly
For: M N2 APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.107173E+09 | 0.64 | 40.01 | 01-JAN-00:10 | 0.64 |
| February | 96801429.15 | 0.64 | 40.01 | 01-FEB-00:10 | 0.64 |
| March | 0.107173E+09 | 0.64 | 40.01 | 01-MAR-00:10 | 0.64 |
| April | 0.103716E+09 | 0.64 | 40.01 | 01-APR-00:10 | 0.64 |
| May | 0.107173E+09 | 0.64 | 40.01 | 01-MAY-00:10 | 0.64 |
| June | 0.103716E+09 | 0.64 | 40.01 | 01-JUN-00:10 | 0.64 |
| July | 0.107173E+09 | 0.64 | 40.01 | 01-JUL-00:10 | 0.64 |
| August | 0.107173E+09 | 0.64 | 40.01 | 01-AUG-00:10 | 0.63 |
| September | 0.103716E+09 | 0.64 | 40.01 | 01-SEP-00:10 | 0.64 |
| October | 0.107173E+09 | 0.64 | 40.01 | 01-OCT-00:10 | 0.63 |
| November | 0.103716E+09 | 0.64 | 40.01 | 01-NOV-00:10 | 0.64 |
| December | 0.107173E+09 | 0.64 | 40.01 | 01-DEC-00:10 | 0.64 |
| Annual Sum or Average | 0.126188E+10 | 0.64 | |||
| Minimum of Months | 96801429.15 | 0.64 | 40.01 | 0.63 | |
| Maximum of Months | 0.107173E+09 | 0.64 | 40.01 | 0.64 |
Report: FanReportMonthly
For: M N2 APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.107173E+09 | 0.64 | 40.01 | 01-JAN-00:10 | 0.64 |
| February | 96801429.15 | 0.64 | 40.01 | 01-FEB-00:10 | 0.64 |
| March | 0.107173E+09 | 0.64 | 40.01 | 01-MAR-00:10 | 0.64 |
| April | 0.103716E+09 | 0.64 | 40.01 | 01-APR-00:10 | 0.64 |
| May | 0.107173E+09 | 0.64 | 40.01 | 01-MAY-00:10 | 0.64 |
| June | 0.103716E+09 | 0.64 | 40.01 | 01-JUN-00:10 | 0.64 |
| July | 0.107173E+09 | 0.64 | 40.01 | 01-JUL-00:10 | 0.64 |
| August | 0.107173E+09 | 0.64 | 40.01 | 01-AUG-00:10 | 0.64 |
| September | 0.103716E+09 | 0.64 | 40.01 | 01-SEP-00:10 | 0.64 |
| October | 0.107173E+09 | 0.64 | 40.01 | 01-OCT-00:10 | 0.64 |
| November | 0.103716E+09 | 0.64 | 40.01 | 01-NOV-00:10 | 0.64 |
| December | 0.107173E+09 | 0.64 | 40.01 | 01-DEC-00:10 | 0.64 |
| Annual Sum or Average | 0.126188E+10 | 0.64 | |||
| Minimum of Months | 96801429.15 | 0.64 | 40.01 | 0.64 | |
| Maximum of Months | 0.107173E+09 | 0.64 | 40.01 | 0.64 |
Report: FanReportMonthly
For: SPLIT MS1 SUPPLY FAN
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.151549E+09 | 0.68 | 298.66 | 14-JAN-14:30 | 1.03 |
| February | 94747710.64 | 0.52 | 269.54 | 01-FEB-12:00 | 1.04 |
| March | 72204759.69 | 0.46 | 228.98 | 11-MAR-13:50 | 1.05 |
| April | 0.141001E+09 | 0.80 | 241.81 | 26-APR-13:00 | 1.04 |
| May | 98871158.86 | 0.74 | 181.42 | 04-MAY-12:00 | 1.05 |
| June | 0.176042E+09 | 1.01 | 189.78 | 29-JUN-16:07 | 1.05 |
| July | 0.296629E+09 | 1.06 | 262.00 | 31-JUL-13:00 | 1.03 |
| August | 0.340738E+09 | 1.05 | 281.30 | 19-AUG-13:00 | 1.03 |
| September | 0.294143E+09 | 1.04 | 414.05 | 29-SEP-13:00 | 1.01 |
| October | 0.332781E+09 | 0.98 | 462.23 | 16-OCT-12:00 | 1.00 |
| November | 0.177938E+09 | 0.82 | 348.78 | 19-NOV-13:00 | 1.02 |
| December | 0.182382E+09 | 0.73 | 338.49 | 19-DEC-13:00 | 1.03 |
| Annual Sum or Average | 0.235903E+10 | 0.83 | |||
| Minimum of Months | 72204759.69 | 0.46 | 181.42 | 1.00 | |
| Maximum of Months | 0.340738E+09 | 1.06 | 462.23 | 1.05 |
Report: FanReportMonthly
For: M S1 APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.107173E+09 | 0.64 | 40.01 | 01-JAN-00:10 | 0.64 |
| February | 96801429.15 | 0.64 | 40.01 | 01-FEB-00:10 | 0.64 |
| March | 0.107173E+09 | 0.64 | 40.01 | 01-MAR-00:10 | 0.64 |
| April | 0.103716E+09 | 0.64 | 40.01 | 01-APR-00:10 | 0.64 |
| May | 0.107173E+09 | 0.64 | 40.01 | 01-MAY-00:10 | 0.64 |
| June | 0.103716E+09 | 0.64 | 40.01 | 01-JUN-00:10 | 0.64 |
| July | 0.107173E+09 | 0.64 | 40.01 | 01-JUL-00:10 | 0.64 |
| August | 0.107173E+09 | 0.64 | 40.01 | 01-AUG-00:10 | 0.63 |
| September | 0.103716E+09 | 0.64 | 40.01 | 01-SEP-00:10 | 0.64 |
| October | 0.107173E+09 | 0.64 | 40.01 | 01-OCT-00:10 | 0.63 |
| November | 0.103716E+09 | 0.64 | 40.01 | 01-NOV-00:10 | 0.64 |
| December | 0.107173E+09 | 0.64 | 40.01 | 01-DEC-00:10 | 0.64 |
| Annual Sum or Average | 0.126188E+10 | 0.64 | |||
| Minimum of Months | 96801429.15 | 0.64 | 40.01 | 0.63 | |
| Maximum of Months | 0.107173E+09 | 0.64 | 40.01 | 0.64 |
Report: FanReportMonthly
For: M S1 APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.107173E+09 | 0.64 | 40.01 | 01-JAN-00:10 | 0.64 |
| February | 96801429.15 | 0.64 | 40.01 | 01-FEB-00:10 | 0.64 |
| March | 0.107173E+09 | 0.64 | 40.01 | 01-MAR-00:10 | 0.64 |
| April | 0.103716E+09 | 0.64 | 40.01 | 01-APR-00:10 | 0.64 |
| May | 0.107173E+09 | 0.64 | 40.01 | 01-MAY-00:10 | 0.64 |
| June | 0.103716E+09 | 0.64 | 40.01 | 01-JUN-00:10 | 0.64 |
| July | 0.107173E+09 | 0.64 | 40.01 | 01-JUL-00:10 | 0.64 |
| August | 0.107173E+09 | 0.64 | 40.01 | 01-AUG-00:10 | 0.64 |
| September | 0.103716E+09 | 0.64 | 40.01 | 01-SEP-00:10 | 0.64 |
| October | 0.107173E+09 | 0.64 | 40.01 | 01-OCT-00:10 | 0.64 |
| November | 0.103716E+09 | 0.64 | 40.01 | 01-NOV-00:10 | 0.64 |
| December | 0.107173E+09 | 0.64 | 40.01 | 01-DEC-00:10 | 0.64 |
| Annual Sum or Average | 0.126188E+10 | 0.64 | |||
| Minimum of Months | 96801429.15 | 0.64 | 40.01 | 0.64 | |
| Maximum of Months | 0.107173E+09 | 0.64 | 40.01 | 0.64 |
Report: FanReportMonthly
For: SPLIT MS2 SUPPLY FAN
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.152320E+09 | 0.68 | 298.68 | 14-JAN-14:30 | 1.03 |
| February | 94844856.65 | 0.52 | 270.14 | 01-FEB-12:00 | 1.04 |
| March | 72499133.09 | 0.46 | 229.97 | 11-MAR-13:50 | 1.05 |
| April | 0.141045E+09 | 0.80 | 242.79 | 26-APR-13:00 | 1.04 |
| May | 98667001.82 | 0.74 | 182.43 | 04-MAY-12:00 | 1.05 |
| June | 0.175462E+09 | 1.01 | 188.66 | 29-JUN-16:07 | 1.05 |
| July | 0.296219E+09 | 1.06 | 262.57 | 31-JUL-13:00 | 1.03 |
| August | 0.340585E+09 | 1.05 | 282.30 | 19-AUG-13:00 | 1.03 |
| September | 0.293429E+09 | 1.04 | 414.76 | 29-SEP-13:00 | 1.01 |
| October | 0.332679E+09 | 0.98 | 463.16 | 16-OCT-12:00 | 1.00 |
| November | 0.177926E+09 | 0.82 | 349.35 | 19-NOV-13:00 | 1.02 |
| December | 0.182714E+09 | 0.73 | 338.97 | 19-DEC-13:00 | 1.03 |
| Annual Sum or Average | 0.235839E+10 | 0.83 | |||
| Minimum of Months | 72499133.09 | 0.46 | 182.43 | 1.00 | |
| Maximum of Months | 0.340585E+09 | 1.06 | 463.16 | 1.05 |
Report: FanReportMonthly
For: M S2 APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.107173E+09 | 0.64 | 40.01 | 01-JAN-00:10 | 0.64 |
| February | 96801429.15 | 0.64 | 40.01 | 01-FEB-00:10 | 0.64 |
| March | 0.107173E+09 | 0.64 | 40.01 | 01-MAR-00:10 | 0.64 |
| April | 0.103716E+09 | 0.64 | 40.01 | 01-APR-00:10 | 0.64 |
| May | 0.107173E+09 | 0.64 | 40.01 | 01-MAY-00:10 | 0.64 |
| June | 0.103716E+09 | 0.64 | 40.01 | 01-JUN-00:10 | 0.64 |
| July | 0.107173E+09 | 0.64 | 40.01 | 01-JUL-00:10 | 0.64 |
| August | 0.107173E+09 | 0.64 | 40.01 | 01-AUG-00:10 | 0.63 |
| September | 0.103716E+09 | 0.64 | 40.01 | 01-SEP-00:10 | 0.64 |
| October | 0.107173E+09 | 0.64 | 40.01 | 01-OCT-00:10 | 0.63 |
| November | 0.103716E+09 | 0.64 | 40.01 | 01-NOV-00:10 | 0.64 |
| December | 0.107173E+09 | 0.64 | 40.01 | 01-DEC-00:10 | 0.64 |
| Annual Sum or Average | 0.126188E+10 | 0.64 | |||
| Minimum of Months | 96801429.15 | 0.64 | 40.01 | 0.63 | |
| Maximum of Months | 0.107173E+09 | 0.64 | 40.01 | 0.64 |
Report: FanReportMonthly
For: M S2 APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.107173E+09 | 0.64 | 40.01 | 01-JAN-00:10 | 0.64 |
| February | 96801429.15 | 0.64 | 40.01 | 01-FEB-00:10 | 0.64 |
| March | 0.107173E+09 | 0.64 | 40.01 | 01-MAR-00:10 | 0.64 |
| April | 0.103716E+09 | 0.64 | 40.01 | 01-APR-00:10 | 0.64 |
| May | 0.107173E+09 | 0.64 | 40.01 | 01-MAY-00:10 | 0.64 |
| June | 0.103716E+09 | 0.64 | 40.01 | 01-JUN-00:10 | 0.64 |
| July | 0.107173E+09 | 0.64 | 40.01 | 01-JUL-00:10 | 0.64 |
| August | 0.107173E+09 | 0.64 | 40.01 | 01-AUG-00:10 | 0.64 |
| September | 0.103716E+09 | 0.64 | 40.01 | 01-SEP-00:10 | 0.64 |
| October | 0.107173E+09 | 0.64 | 40.01 | 01-OCT-00:10 | 0.64 |
| November | 0.103716E+09 | 0.64 | 40.01 | 01-NOV-00:10 | 0.64 |
| December | 0.107173E+09 | 0.64 | 40.01 | 01-DEC-00:10 | 0.64 |
| Annual Sum or Average | 0.126188E+10 | 0.64 | |||
| Minimum of Months | 96801429.15 | 0.64 | 40.01 | 0.64 | |
| Maximum of Months | 0.107173E+09 | 0.64 | 40.01 | 0.64 |
Report: FanReportMonthly
For: SPLIT TSW SUPPLY FAN
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 60711211.58 | 0.54 | 208.79 | 14-JAN-15:00 | 1.02 |
| February | 41549882.34 | 0.53 | 158.33 | 03-FEB-15:00 | 1.05 |
| March | 54266255.97 | 0.52 | 172.42 | 23-MAR-15:30 | 1.03 |
| April | 68874476.83 | 0.45 | 189.92 | 26-APR-14:10 | 1.02 |
| May | 46422929.33 | 0.40 | 156.33 | 03-MAY-15:10 | 1.04 |
| June | 90390247.67 | 0.51 | 186.95 | 29-JUN-16:13 | 1.02 |
| July | 0.169923E+09 | 0.71 | 223.98 | 19-JUL-15:10 | 1.01 |
| August | 0.185459E+09 | 0.69 | 243.68 | 17-AUG-15:10 | 1.00 |
| September | 0.136116E+09 | 0.61 | 330.03 | 29-SEP-13:40 | 0.98 |
| October | 0.145297E+09 | 0.64 | 336.04 | 16-OCT-12:40 | 0.98 |
| November | 54232294.63 | 0.47 | 223.22 | 19-NOV-13:30 | 1.02 |
| December | 69931338.53 | 0.53 | 198.22 | 19-DEC-13:30 | 1.03 |
| Annual Sum or Average | 0.112317E+10 | 0.55 | |||
| Minimum of Months | 41549882.34 | 0.40 | 156.33 | 0.98 | |
| Maximum of Months | 0.185459E+09 | 0.71 | 336.04 | 1.05 |
Report: FanReportMonthly
For: T SW APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.64 | 20.01 | 01-JAN-00:10 | 0.64 |
| February | 48400714.57 | 0.64 | 20.01 | 01-FEB-00:10 | 0.64 |
| March | 53586505.42 | 0.64 | 20.01 | 01-MAR-00:10 | 0.64 |
| April | 51857908.47 | 0.64 | 20.01 | 01-APR-00:10 | 0.64 |
| May | 53586505.42 | 0.64 | 20.01 | 01-MAY-00:10 | 0.64 |
| June | 51857908.47 | 0.64 | 20.01 | 01-JUN-00:10 | 0.64 |
| July | 53586505.42 | 0.64 | 20.01 | 01-JUL-00:10 | 0.64 |
| August | 53586505.42 | 0.64 | 20.01 | 01-AUG-00:10 | 0.63 |
| September | 51857908.47 | 0.64 | 20.01 | 01-SEP-00:10 | 0.64 |
| October | 53586505.42 | 0.64 | 20.01 | 01-OCT-00:10 | 0.63 |
| November | 51857908.47 | 0.64 | 20.01 | 01-NOV-00:10 | 0.64 |
| December | 53586505.42 | 0.64 | 20.01 | 01-DEC-00:10 | 0.64 |
| Annual Sum or Average | 0.630938E+09 | 0.64 | |||
| Minimum of Months | 48400714.57 | 0.64 | 20.01 | 0.63 | |
| Maximum of Months | 53586505.42 | 0.64 | 20.01 | 0.64 |
Report: FanReportMonthly
For: T SW APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.64 | 20.01 | 01-JAN-00:10 | 0.64 |
| February | 48400714.57 | 0.64 | 20.01 | 01-FEB-00:10 | 0.64 |
| March | 53586505.42 | 0.64 | 20.01 | 01-MAR-00:10 | 0.64 |
| April | 51857908.47 | 0.64 | 20.01 | 01-APR-00:10 | 0.64 |
| May | 53586505.42 | 0.64 | 20.01 | 01-MAY-00:10 | 0.64 |
| June | 51857908.47 | 0.64 | 20.01 | 01-JUN-00:10 | 0.64 |
| July | 53586505.42 | 0.64 | 20.01 | 01-JUL-00:10 | 0.64 |
| August | 53586505.42 | 0.64 | 20.01 | 01-AUG-00:10 | 0.64 |
| September | 51857908.47 | 0.64 | 20.01 | 01-SEP-00:10 | 0.64 |
| October | 53586505.42 | 0.64 | 20.01 | 01-OCT-00:10 | 0.64 |
| November | 51857908.47 | 0.64 | 20.01 | 01-NOV-00:10 | 0.64 |
| December | 53586505.42 | 0.64 | 20.01 | 01-DEC-00:10 | 0.64 |
| Annual Sum or Average | 0.630938E+09 | 0.64 | |||
| Minimum of Months | 48400714.57 | 0.64 | 20.01 | 0.64 | |
| Maximum of Months | 53586505.42 | 0.64 | 20.01 | 0.64 |
Report: FanReportMonthly
For: SPLIT TNW SUPPLY FAN
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 41029473.57 | 0.50 | 85.69 | 08-JAN-07:00 | 0.94 |
| February | 28131217.06 | 0.49 | 59.44 | 05-FEB-06:00 | 0.94 |
| March | 38128558.87 | 0.49 | 106.72 | 23-MAR-16:05 | 1.05 |
| April | 34767207.90 | 0.37 | 153.08 | 26-APR-16:20 | 1.03 |
| May | 37442922.77 | 0.38 | 138.16 | 03-MAY-15:10 | 1.04 |
| June | 88606970.40 | 0.53 | 190.29 | 29-JUN-16:40 | 1.02 |
| July | 0.159857E+09 | 0.72 | 219.14 | 19-JUL-16:12 | 1.01 |
| August | 0.150176E+09 | 0.66 | 212.14 | 17-AUG-15:20 | 1.01 |
| September | 78871647.90 | 0.52 | 249.17 | 29-SEP-15:10 | 1.00 |
| October | 75652419.61 | 0.54 | 230.61 | 14-OCT-15:10 | 1.01 |
| November | 23029242.68 | 0.38 | 75.70 | 19-NOV-13:50 | 1.07 |
| December | 38494706.79 | 0.50 | 82.77 | 05-DEC-15:10 | 1.07 |
| Annual Sum or Average | 0.794188E+09 | 0.51 | |||
| Minimum of Months | 23029242.68 | 0.37 | 59.44 | 0.94 | |
| Maximum of Months | 0.159857E+09 | 0.72 | 249.17 | 1.07 |
Report: FanReportMonthly
For: T NW APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.64 | 20.01 | 01-JAN-00:10 | 0.64 |
| February | 48400714.57 | 0.64 | 20.01 | 01-FEB-00:10 | 0.64 |
| March | 53586505.42 | 0.64 | 20.01 | 01-MAR-00:10 | 0.64 |
| April | 51857908.47 | 0.64 | 20.01 | 01-APR-00:10 | 0.64 |
| May | 53586505.42 | 0.64 | 20.01 | 01-MAY-00:10 | 0.64 |
| June | 51857908.47 | 0.64 | 20.01 | 01-JUN-00:10 | 0.64 |
| July | 53586505.42 | 0.64 | 20.01 | 01-JUL-00:10 | 0.64 |
| August | 53586505.42 | 0.64 | 20.01 | 01-AUG-00:10 | 0.63 |
| September | 51857908.47 | 0.64 | 20.01 | 01-SEP-00:10 | 0.64 |
| October | 53586505.42 | 0.64 | 20.01 | 01-OCT-00:10 | 0.63 |
| November | 51857908.47 | 0.64 | 20.01 | 01-NOV-00:10 | 0.64 |
| December | 53586505.42 | 0.64 | 20.01 | 01-DEC-00:10 | 0.64 |
| Annual Sum or Average | 0.630938E+09 | 0.64 | |||
| Minimum of Months | 48400714.57 | 0.64 | 20.01 | 0.63 | |
| Maximum of Months | 53586505.42 | 0.64 | 20.01 | 0.64 |
Report: FanReportMonthly
For: T NW APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.64 | 20.01 | 01-JAN-00:10 | 0.64 |
| February | 48400714.57 | 0.64 | 20.01 | 01-FEB-00:10 | 0.64 |
| March | 53586505.42 | 0.64 | 20.01 | 01-MAR-00:10 | 0.64 |
| April | 51857908.47 | 0.64 | 20.01 | 01-APR-00:10 | 0.64 |
| May | 53586505.42 | 0.64 | 20.01 | 01-MAY-00:10 | 0.64 |
| June | 51857908.47 | 0.64 | 20.01 | 01-JUN-00:10 | 0.64 |
| July | 53586505.42 | 0.64 | 20.01 | 01-JUL-00:10 | 0.64 |
| August | 53586505.42 | 0.64 | 20.01 | 01-AUG-00:10 | 0.64 |
| September | 51857908.47 | 0.64 | 20.01 | 01-SEP-00:10 | 0.64 |
| October | 53586505.42 | 0.64 | 20.01 | 01-OCT-00:10 | 0.64 |
| November | 51857908.47 | 0.64 | 20.01 | 01-NOV-00:10 | 0.64 |
| December | 53586505.42 | 0.64 | 20.01 | 01-DEC-00:10 | 0.64 |
| Annual Sum or Average | 0.630938E+09 | 0.64 | |||
| Minimum of Months | 48400714.57 | 0.64 | 20.01 | 0.64 | |
| Maximum of Months | 53586505.42 | 0.64 | 20.01 | 0.64 |
Report: FanReportMonthly
For: SPLIT TSE SUPPLY FAN
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 60099276.71 | 0.54 | 182.21 | 14-JAN-14:30 | 1.03 |
| February | 39401724.71 | 0.54 | 154.10 | 01-FEB-12:40 | 1.04 |
| March | 52871695.11 | 0.51 | 166.22 | 11-MAR-13:50 | 1.03 |
| April | 64953576.64 | 0.44 | 189.98 | 26-APR-13:00 | 1.02 |
| May | 40991288.90 | 0.39 | 153.81 | 04-MAY-12:00 | 1.03 |
| June | 84205745.84 | 0.46 | 163.98 | 30-JUN-12:00 | 1.02 |
| July | 0.166046E+09 | 0.69 | 215.79 | 31-JUL-13:00 | 1.00 |
| August | 0.184320E+09 | 0.68 | 226.84 | 19-AUG-13:00 | 1.00 |
| September | 0.128460E+09 | 0.58 | 329.06 | 29-SEP-13:00 | 0.96 |
| October | 0.141572E+09 | 0.63 | 353.37 | 16-OCT-12:00 | 0.96 |
| November | 50973184.85 | 0.45 | 225.03 | 19-NOV-13:00 | 1.01 |
| December | 68450578.05 | 0.53 | 202.06 | 19-DEC-13:00 | 1.02 |
| Annual Sum or Average | 0.108234E+10 | 0.54 | |||
| Minimum of Months | 39401724.71 | 0.39 | 153.81 | 0.96 | |
| Maximum of Months | 0.184320E+09 | 0.69 | 353.37 | 1.04 |
Report: FanReportMonthly
For: T SE APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.64 | 20.01 | 01-JAN-00:10 | 0.64 |
| February | 48400714.57 | 0.64 | 20.01 | 01-FEB-00:10 | 0.64 |
| March | 53586505.42 | 0.64 | 20.01 | 01-MAR-00:10 | 0.64 |
| April | 51857908.47 | 0.64 | 20.01 | 01-APR-00:10 | 0.64 |
| May | 53586505.42 | 0.64 | 20.01 | 01-MAY-00:10 | 0.64 |
| June | 51857908.47 | 0.64 | 20.01 | 01-JUN-00:10 | 0.64 |
| July | 53586505.42 | 0.64 | 20.01 | 01-JUL-00:10 | 0.64 |
| August | 53586505.42 | 0.64 | 20.01 | 01-AUG-00:10 | 0.63 |
| September | 51857908.47 | 0.64 | 20.01 | 01-SEP-00:10 | 0.64 |
| October | 53586505.42 | 0.64 | 20.01 | 01-OCT-00:10 | 0.63 |
| November | 51857908.47 | 0.64 | 20.01 | 01-NOV-00:10 | 0.64 |
| December | 53586505.42 | 0.64 | 20.01 | 01-DEC-00:10 | 0.64 |
| Annual Sum or Average | 0.630938E+09 | 0.64 | |||
| Minimum of Months | 48400714.57 | 0.64 | 20.01 | 0.63 | |
| Maximum of Months | 53586505.42 | 0.64 | 20.01 | 0.64 |
Report: FanReportMonthly
For: T SE APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.64 | 20.01 | 01-JAN-00:10 | 0.64 |
| February | 48400714.57 | 0.64 | 20.01 | 01-FEB-00:10 | 0.64 |
| March | 53586505.42 | 0.64 | 20.01 | 01-MAR-00:10 | 0.64 |
| April | 51857908.47 | 0.64 | 20.01 | 01-APR-00:10 | 0.64 |
| May | 53586505.42 | 0.64 | 20.01 | 01-MAY-00:10 | 0.64 |
| June | 51857908.47 | 0.64 | 20.01 | 01-JUN-00:10 | 0.64 |
| July | 53586505.42 | 0.64 | 20.01 | 01-JUL-00:10 | 0.64 |
| August | 53586505.42 | 0.64 | 20.01 | 01-AUG-00:10 | 0.63 |
| September | 51857908.47 | 0.64 | 20.01 | 01-SEP-00:10 | 0.64 |
| October | 53586505.42 | 0.64 | 20.01 | 01-OCT-00:10 | 0.64 |
| November | 51857908.47 | 0.64 | 20.01 | 01-NOV-00:10 | 0.64 |
| December | 53586505.42 | 0.64 | 20.01 | 01-DEC-00:10 | 0.64 |
| Annual Sum or Average | 0.630938E+09 | 0.64 | |||
| Minimum of Months | 48400714.57 | 0.64 | 20.01 | 0.63 | |
| Maximum of Months | 53586505.42 | 0.64 | 20.01 | 0.64 |
Report: FanReportMonthly
For: SPLIT TNE SUPPLY FAN
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 39152172.17 | 0.48 | 83.56 | 08-JAN-06:50 | 0.94 |
| February | 27887042.04 | 0.48 | 60.60 | 05-FEB-06:00 | 0.94 |
| March | 36959785.94 | 0.48 | 83.04 | 30-MAR-04:00 | 0.93 |
| April | 31960779.28 | 0.35 | 138.62 | 26-APR-13:00 | 1.03 |
| May | 32267445.96 | 0.35 | 128.74 | 04-MAY-12:00 | 1.04 |
| June | 82287653.12 | 0.49 | 159.32 | 30-JUN-10:00 | 1.02 |
| July | 0.156263E+09 | 0.70 | 198.28 | 19-JUL-12:00 | 1.01 |
| August | 0.149630E+09 | 0.64 | 190.85 | 14-AUG-11:00 | 1.01 |
| September | 72401193.21 | 0.48 | 241.02 | 29-SEP-13:00 | 1.00 |
| October | 72162307.71 | 0.53 | 252.74 | 16-OCT-11:00 | 0.99 |
| November | 22324924.63 | 0.35 | 79.15 | 19-NOV-13:00 | 1.06 |
| December | 36809109.66 | 0.48 | 71.54 | 13-DEC-05:00 | 0.93 |
| Annual Sum or Average | 0.760105E+09 | 0.49 | |||
| Minimum of Months | 22324924.63 | 0.35 | 60.60 | 0.93 | |
| Maximum of Months | 0.156263E+09 | 0.70 | 252.74 | 1.06 |
Report: FanReportMonthly
For: T NE APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.64 | 20.01 | 01-JAN-00:10 | 0.64 |
| February | 48400714.57 | 0.64 | 20.01 | 01-FEB-00:10 | 0.64 |
| March | 53586505.42 | 0.64 | 20.01 | 01-MAR-00:10 | 0.64 |
| April | 51857908.47 | 0.64 | 20.01 | 01-APR-00:10 | 0.64 |
| May | 53586505.42 | 0.64 | 20.01 | 01-MAY-00:10 | 0.64 |
| June | 51857908.47 | 0.64 | 20.01 | 01-JUN-00:10 | 0.64 |
| July | 53586505.42 | 0.64 | 20.01 | 01-JUL-00:10 | 0.64 |
| August | 53586505.42 | 0.64 | 20.01 | 01-AUG-00:10 | 0.63 |
| September | 51857908.47 | 0.64 | 20.01 | 01-SEP-00:10 | 0.64 |
| October | 53586505.42 | 0.64 | 20.01 | 01-OCT-00:10 | 0.63 |
| November | 51857908.47 | 0.64 | 20.01 | 01-NOV-00:10 | 0.64 |
| December | 53586505.42 | 0.64 | 20.01 | 01-DEC-00:10 | 0.64 |
| Annual Sum or Average | 0.630938E+09 | 0.64 | |||
| Minimum of Months | 48400714.57 | 0.64 | 20.01 | 0.63 | |
| Maximum of Months | 53586505.42 | 0.64 | 20.01 | 0.64 |
Report: FanReportMonthly
For: T NE APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.64 | 20.01 | 01-JAN-00:10 | 0.64 |
| February | 48400714.57 | 0.64 | 20.01 | 01-FEB-00:10 | 0.64 |
| March | 53586505.42 | 0.64 | 20.01 | 01-MAR-00:10 | 0.64 |
| April | 51857908.47 | 0.64 | 20.01 | 01-APR-00:10 | 0.64 |
| May | 53586505.42 | 0.64 | 20.01 | 01-MAY-00:10 | 0.64 |
| June | 51857908.47 | 0.64 | 20.01 | 01-JUN-00:10 | 0.64 |
| July | 53586505.42 | 0.64 | 20.01 | 01-JUL-00:10 | 0.64 |
| August | 53586505.42 | 0.64 | 20.01 | 01-AUG-00:10 | 0.63 |
| September | 51857908.47 | 0.64 | 20.01 | 01-SEP-00:10 | 0.64 |
| October | 53586505.42 | 0.64 | 20.01 | 01-OCT-00:10 | 0.64 |
| November | 51857908.47 | 0.64 | 20.01 | 01-NOV-00:10 | 0.64 |
| December | 53586505.42 | 0.64 | 20.01 | 01-DEC-00:10 | 0.64 |
| Annual Sum or Average | 0.630938E+09 | 0.64 | |||
| Minimum of Months | 48400714.57 | 0.64 | 20.01 | 0.63 | |
| Maximum of Months | 53586505.42 | 0.64 | 20.01 | 0.64 |
Report: FanReportMonthly
For: SPLIT TN1 SUPPLY FAN
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 25303324.02 | 0.42 | 59.96 | 08-JAN-07:00 | 0.94 |
| February | 14338886.85 | 0.38 | 39.40 | 05-FEB-06:00 | 0.94 |
| March | 19911107.59 | 0.36 | 57.36 | 30-MAR-04:00 | 0.93 |
| April | 17635166.88 | 0.27 | 101.83 | 26-APR-13:00 | 1.05 |
| May | 20735019.79 | 0.32 | 94.62 | 03-MAY-13:00 | 1.05 |
| June | 66051008.54 | 0.58 | 122.90 | 29-JUN-17:10 | 1.03 |
| July | 0.126469E+09 | 0.81 | 150.42 | 19-JUL-15:10 | 1.02 |
| August | 0.119220E+09 | 0.75 | 149.47 | 17-AUG-14:10 | 1.02 |
| September | 59114479.35 | 0.54 | 186.22 | 29-SEP-13:00 | 1.01 |
| October | 59670803.03 | 0.50 | 188.78 | 16-OCT-12:00 | 1.01 |
| November | 11496623.19 | 0.26 | 54.68 | 19-NOV-13:00 | 1.07 |
| December | 22033744.48 | 0.40 | 48.19 | 13-DEC-05:00 | 0.93 |
| Annual Sum or Average | 0.561980E+09 | 0.47 | |||
| Minimum of Months | 11496623.19 | 0.26 | 39.40 | 0.93 | |
| Maximum of Months | 0.126469E+09 | 0.81 | 188.78 | 1.07 |
Report: FanReportMonthly
For: T N1 APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.64 | 20.01 | 01-JAN-00:10 | 0.64 |
| February | 48400714.57 | 0.64 | 20.01 | 01-FEB-00:10 | 0.64 |
| March | 53586505.42 | 0.64 | 20.01 | 01-MAR-00:10 | 0.64 |
| April | 51857908.47 | 0.64 | 20.01 | 01-APR-00:10 | 0.64 |
| May | 53586505.42 | 0.64 | 20.01 | 01-MAY-00:10 | 0.64 |
| June | 51857908.47 | 0.64 | 20.01 | 01-JUN-00:10 | 0.64 |
| July | 53586505.42 | 0.64 | 20.01 | 01-JUL-00:10 | 0.64 |
| August | 53586505.42 | 0.64 | 20.01 | 01-AUG-00:10 | 0.63 |
| September | 51857908.47 | 0.64 | 20.01 | 01-SEP-00:10 | 0.64 |
| October | 53586505.42 | 0.64 | 20.01 | 01-OCT-00:10 | 0.63 |
| November | 51857908.47 | 0.64 | 20.01 | 01-NOV-00:10 | 0.64 |
| December | 53586505.42 | 0.64 | 20.01 | 01-DEC-00:10 | 0.64 |
| Annual Sum or Average | 0.630938E+09 | 0.64 | |||
| Minimum of Months | 48400714.57 | 0.64 | 20.01 | 0.63 | |
| Maximum of Months | 53586505.42 | 0.64 | 20.01 | 0.64 |
Report: FanReportMonthly
For: T N1 APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.64 | 20.01 | 01-JAN-00:10 | 0.64 |
| February | 48400714.57 | 0.64 | 20.01 | 01-FEB-00:10 | 0.64 |
| March | 53586505.42 | 0.64 | 20.01 | 01-MAR-00:10 | 0.64 |
| April | 51857908.47 | 0.64 | 20.01 | 01-APR-00:10 | 0.64 |
| May | 53586505.42 | 0.64 | 20.01 | 01-MAY-00:10 | 0.64 |
| June | 51857908.47 | 0.64 | 20.01 | 01-JUN-00:10 | 0.64 |
| July | 53586505.42 | 0.64 | 20.01 | 01-JUL-00:10 | 0.64 |
| August | 53586505.42 | 0.64 | 20.01 | 01-AUG-00:10 | 0.64 |
| September | 51857908.47 | 0.64 | 20.01 | 01-SEP-00:10 | 0.64 |
| October | 53586505.42 | 0.64 | 20.01 | 01-OCT-00:10 | 0.64 |
| November | 51857908.47 | 0.64 | 20.01 | 01-NOV-00:10 | 0.64 |
| December | 53586505.42 | 0.64 | 20.01 | 01-DEC-00:10 | 0.64 |
| Annual Sum or Average | 0.630938E+09 | 0.64 | |||
| Minimum of Months | 48400714.57 | 0.64 | 20.01 | 0.64 | |
| Maximum of Months | 53586505.42 | 0.64 | 20.01 | 0.64 |
Report: FanReportMonthly
For: SPLIT TN2 SUPPLY FAN
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 25354641.62 | 0.42 | 59.99 | 08-JAN-07:00 | 0.94 |
| February | 14460099.49 | 0.38 | 39.54 | 05-FEB-06:00 | 0.94 |
| March | 20084095.19 | 0.36 | 57.57 | 30-MAR-04:00 | 0.93 |
| April | 17911448.12 | 0.27 | 103.20 | 26-APR-13:00 | 1.05 |
| May | 20858753.62 | 0.32 | 95.44 | 03-MAY-13:00 | 1.05 |
| June | 65922252.51 | 0.57 | 121.30 | 29-JUN-17:05 | 1.03 |
| July | 0.126305E+09 | 0.80 | 150.71 | 31-JUL-13:00 | 1.02 |
| August | 0.119263E+09 | 0.75 | 149.70 | 17-AUG-14:10 | 1.02 |
| September | 58968339.07 | 0.54 | 186.96 | 29-SEP-13:00 | 1.01 |
| October | 59800515.24 | 0.50 | 189.90 | 16-OCT-12:00 | 1.01 |
| November | 11639343.21 | 0.26 | 55.61 | 19-NOV-13:00 | 1.07 |
| December | 22157577.24 | 0.41 | 48.21 | 13-DEC-05:00 | 0.93 |
| Annual Sum or Average | 0.562725E+09 | 0.47 | |||
| Minimum of Months | 11639343.21 | 0.26 | 39.54 | 0.93 | |
| Maximum of Months | 0.126305E+09 | 0.80 | 189.90 | 1.07 |
Report: FanReportMonthly
For: T N2 APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.64 | 20.01 | 01-JAN-00:10 | 0.64 |
| February | 48400714.57 | 0.64 | 20.01 | 01-FEB-00:10 | 0.64 |
| March | 53586505.42 | 0.64 | 20.01 | 01-MAR-00:10 | 0.64 |
| April | 51857908.47 | 0.64 | 20.01 | 01-APR-00:10 | 0.64 |
| May | 53586505.42 | 0.64 | 20.01 | 01-MAY-00:10 | 0.64 |
| June | 51857908.47 | 0.64 | 20.01 | 01-JUN-00:10 | 0.64 |
| July | 53586505.42 | 0.64 | 20.01 | 01-JUL-00:10 | 0.64 |
| August | 53586505.42 | 0.64 | 20.01 | 01-AUG-00:10 | 0.63 |
| September | 51857908.47 | 0.64 | 20.01 | 01-SEP-00:10 | 0.64 |
| October | 53586505.42 | 0.64 | 20.01 | 01-OCT-00:10 | 0.63 |
| November | 51857908.47 | 0.64 | 20.01 | 01-NOV-00:10 | 0.64 |
| December | 53586505.42 | 0.64 | 20.01 | 01-DEC-00:10 | 0.64 |
| Annual Sum or Average | 0.630938E+09 | 0.64 | |||
| Minimum of Months | 48400714.57 | 0.64 | 20.01 | 0.63 | |
| Maximum of Months | 53586505.42 | 0.64 | 20.01 | 0.64 |
Report: FanReportMonthly
For: T N2 APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.64 | 20.01 | 01-JAN-00:10 | 0.64 |
| February | 48400714.57 | 0.64 | 20.01 | 01-FEB-00:10 | 0.64 |
| March | 53586505.42 | 0.64 | 20.01 | 01-MAR-00:10 | 0.64 |
| April | 51857908.47 | 0.64 | 20.01 | 01-APR-00:10 | 0.64 |
| May | 53586505.42 | 0.64 | 20.01 | 01-MAY-00:10 | 0.64 |
| June | 51857908.47 | 0.64 | 20.01 | 01-JUN-00:10 | 0.64 |
| July | 53586505.42 | 0.64 | 20.01 | 01-JUL-00:10 | 0.64 |
| August | 53586505.42 | 0.64 | 20.01 | 01-AUG-00:10 | 0.64 |
| September | 51857908.47 | 0.64 | 20.01 | 01-SEP-00:10 | 0.64 |
| October | 53586505.42 | 0.64 | 20.01 | 01-OCT-00:10 | 0.64 |
| November | 51857908.47 | 0.64 | 20.01 | 01-NOV-00:10 | 0.64 |
| December | 53586505.42 | 0.64 | 20.01 | 01-DEC-00:10 | 0.64 |
| Annual Sum or Average | 0.630938E+09 | 0.64 | |||
| Minimum of Months | 48400714.57 | 0.64 | 20.01 | 0.64 | |
| Maximum of Months | 53586505.42 | 0.64 | 20.01 | 0.64 |
Report: FanReportMonthly
For: SPLIT TS1 SUPPLY FAN
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 50721647.60 | 0.50 | 173.82 | 14-JAN-14:40 | 1.03 |
| February | 28399726.10 | 0.41 | 137.44 | 01-FEB-13:00 | 1.04 |
| March | 35925875.61 | 0.42 | 144.19 | 11-MAR-14:00 | 1.04 |
| April | 51288962.82 | 0.42 | 154.49 | 26-APR-13:00 | 1.03 |
| May | 29078969.15 | 0.35 | 121.82 | 03-MAY-13:00 | 1.04 |
| June | 67641644.16 | 0.54 | 130.34 | 27-JUN-13:00 | 1.04 |
| July | 0.136487E+09 | 0.80 | 177.07 | 31-JUL-13:00 | 1.01 |
| August | 0.155845E+09 | 0.80 | 188.66 | 17-AUG-14:00 | 1.01 |
| September | 0.118689E+09 | 0.67 | 276.97 | 29-SEP-13:00 | 0.98 |
| October | 0.133026E+09 | 0.67 | 296.09 | 16-OCT-12:00 | 0.97 |
| November | 45255355.47 | 0.42 | 205.42 | 19-NOV-13:00 | 1.01 |
| December | 57724455.24 | 0.48 | 189.42 | 19-DEC-13:00 | 1.02 |
| Annual Sum or Average | 0.910084E+09 | 0.54 | |||
| Minimum of Months | 28399726.10 | 0.35 | 121.82 | 0.97 | |
| Maximum of Months | 0.155845E+09 | 0.80 | 296.09 | 1.04 |
Report: FanReportMonthly
For: T S1 APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.64 | 20.01 | 01-JAN-00:10 | 0.64 |
| February | 48400714.57 | 0.64 | 20.01 | 01-FEB-00:10 | 0.64 |
| March | 53586505.42 | 0.64 | 20.01 | 01-MAR-00:10 | 0.64 |
| April | 51857908.47 | 0.64 | 20.01 | 01-APR-00:10 | 0.64 |
| May | 53586505.42 | 0.64 | 20.01 | 01-MAY-00:10 | 0.64 |
| June | 51857908.47 | 0.64 | 20.01 | 01-JUN-00:10 | 0.64 |
| July | 53586505.42 | 0.64 | 20.01 | 01-JUL-00:10 | 0.64 |
| August | 53586505.42 | 0.64 | 20.01 | 01-AUG-00:10 | 0.63 |
| September | 51857908.47 | 0.64 | 20.01 | 01-SEP-00:10 | 0.64 |
| October | 53586505.42 | 0.64 | 20.01 | 01-OCT-00:10 | 0.63 |
| November | 51857908.47 | 0.64 | 20.01 | 01-NOV-00:10 | 0.64 |
| December | 53586505.42 | 0.64 | 20.01 | 01-DEC-00:10 | 0.64 |
| Annual Sum or Average | 0.630938E+09 | 0.64 | |||
| Minimum of Months | 48400714.57 | 0.64 | 20.01 | 0.63 | |
| Maximum of Months | 53586505.42 | 0.64 | 20.01 | 0.64 |
Report: FanReportMonthly
For: T S1 APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.64 | 20.01 | 01-JAN-00:10 | 0.64 |
| February | 48400714.57 | 0.64 | 20.01 | 01-FEB-00:10 | 0.64 |
| March | 53586505.42 | 0.64 | 20.01 | 01-MAR-00:10 | 0.64 |
| April | 51857908.47 | 0.64 | 20.01 | 01-APR-00:10 | 0.64 |
| May | 53586505.42 | 0.64 | 20.01 | 01-MAY-00:10 | 0.64 |
| June | 51857908.47 | 0.64 | 20.01 | 01-JUN-00:10 | 0.64 |
| July | 53586505.42 | 0.64 | 20.01 | 01-JUL-00:10 | 0.64 |
| August | 53586505.42 | 0.64 | 20.01 | 01-AUG-00:10 | 0.64 |
| September | 51857908.47 | 0.64 | 20.01 | 01-SEP-00:10 | 0.64 |
| October | 53586505.42 | 0.64 | 20.01 | 01-OCT-00:10 | 0.64 |
| November | 51857908.47 | 0.64 | 20.01 | 01-NOV-00:10 | 0.64 |
| December | 53586505.42 | 0.64 | 20.01 | 01-DEC-00:10 | 0.64 |
| Annual Sum or Average | 0.630938E+09 | 0.64 | |||
| Minimum of Months | 48400714.57 | 0.64 | 20.01 | 0.64 | |
| Maximum of Months | 53586505.42 | 0.64 | 20.01 | 0.64 |
Report: FanReportMonthly
For: SPLIT TS2 SUPPLY FAN
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 51163380.84 | 0.50 | 173.66 | 14-JAN-14:30 | 1.03 |
| February | 28644080.31 | 0.41 | 137.99 | 01-FEB-13:00 | 1.04 |
| March | 36304894.82 | 0.42 | 145.02 | 11-MAR-13:50 | 1.04 |
| April | 51554253.25 | 0.41 | 155.71 | 26-APR-13:00 | 1.03 |
| May | 29249384.70 | 0.35 | 122.61 | 03-MAY-13:00 | 1.04 |
| June | 67533718.39 | 0.54 | 131.04 | 27-JUN-13:00 | 1.03 |
| July | 0.136336E+09 | 0.79 | 177.71 | 31-JUL-13:00 | 1.01 |
| August | 0.155845E+09 | 0.79 | 189.35 | 19-AUG-13:20 | 1.01 |
| September | 0.118428E+09 | 0.67 | 277.61 | 29-SEP-13:00 | 0.98 |
| October | 0.133090E+09 | 0.67 | 296.96 | 16-OCT-12:00 | 0.97 |
| November | 45442671.02 | 0.42 | 206.10 | 19-NOV-13:00 | 1.01 |
| December | 58109954.00 | 0.48 | 189.99 | 19-DEC-13:00 | 1.02 |
| Annual Sum or Average | 0.911702E+09 | 0.54 | |||
| Minimum of Months | 28644080.31 | 0.35 | 122.61 | 0.97 | |
| Maximum of Months | 0.155845E+09 | 0.79 | 296.96 | 1.04 |
Report: FanReportMonthly
For: T S2 APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.64 | 20.01 | 01-JAN-00:10 | 0.64 |
| February | 48400714.57 | 0.64 | 20.01 | 01-FEB-00:10 | 0.64 |
| March | 53586505.42 | 0.64 | 20.01 | 01-MAR-00:10 | 0.64 |
| April | 51857908.47 | 0.64 | 20.01 | 01-APR-00:10 | 0.64 |
| May | 53586505.42 | 0.64 | 20.01 | 01-MAY-00:10 | 0.64 |
| June | 51857908.47 | 0.64 | 20.01 | 01-JUN-00:10 | 0.64 |
| July | 53586505.42 | 0.64 | 20.01 | 01-JUL-00:10 | 0.64 |
| August | 53586505.42 | 0.64 | 20.01 | 01-AUG-00:10 | 0.63 |
| September | 51857908.47 | 0.64 | 20.01 | 01-SEP-00:10 | 0.64 |
| October | 53586505.42 | 0.64 | 20.01 | 01-OCT-00:10 | 0.63 |
| November | 51857908.47 | 0.64 | 20.01 | 01-NOV-00:10 | 0.64 |
| December | 53586505.42 | 0.64 | 20.01 | 01-DEC-00:10 | 0.64 |
| Annual Sum or Average | 0.630938E+09 | 0.64 | |||
| Minimum of Months | 48400714.57 | 0.64 | 20.01 | 0.63 | |
| Maximum of Months | 53586505.42 | 0.64 | 20.01 | 0.64 |
Report: FanReportMonthly
For: T S2 APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.64 | 20.01 | 01-JAN-00:10 | 0.64 |
| February | 48400714.57 | 0.64 | 20.01 | 01-FEB-00:10 | 0.64 |
| March | 53586505.42 | 0.64 | 20.01 | 01-MAR-00:10 | 0.64 |
| April | 51857908.47 | 0.64 | 20.01 | 01-APR-00:10 | 0.64 |
| May | 53586505.42 | 0.64 | 20.01 | 01-MAY-00:10 | 0.64 |
| June | 51857908.47 | 0.64 | 20.01 | 01-JUN-00:10 | 0.64 |
| July | 53586505.42 | 0.64 | 20.01 | 01-JUL-00:10 | 0.64 |
| August | 53586505.42 | 0.64 | 20.01 | 01-AUG-00:10 | 0.64 |
| September | 51857908.47 | 0.64 | 20.01 | 01-SEP-00:10 | 0.64 |
| October | 53586505.42 | 0.64 | 20.01 | 01-OCT-00:10 | 0.64 |
| November | 51857908.47 | 0.64 | 20.01 | 01-NOV-00:10 | 0.64 |
| December | 53586505.42 | 0.64 | 20.01 | 01-DEC-00:10 | 0.64 |
| Annual Sum or Average | 0.630938E+09 | 0.64 | |||
| Minimum of Months | 48400714.57 | 0.64 | 20.01 | 0.64 | |
| Maximum of Months | 53586505.42 | 0.64 | 20.01 | 0.64 |
Report: ZoneTemperatureOscillationReportMonthly
For: G SW APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: G NW APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: OFFICE
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: G NE APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: G N1 APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: G N2 APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: G S1 APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: G S2 APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: M SW APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: M NW APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: M SE APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: M NE APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: M N1 APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: M N2 APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: M S1 APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: M S2 APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: T SW APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: T NW APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: T SE APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: T NE APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: T N1 APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: T N2 APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: T S1 APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: T S2 APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: T CORRIDOR
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: G CORRIDOR
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: M CORRIDOR
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT GSW
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 88967155.05 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 34794256.61 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 23917388.51 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 79418276.37 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 47870365.79 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.161777E+09 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.482495E+09 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.568636E+09 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.454844E+09 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.556449E+09 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.151042E+09 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.133981E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.278419E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 23917388.51 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.568636E+09 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT GNW
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 13794971.40 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 6904299.22 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 13215089.35 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 19145183.81 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 27782519.51 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.159406E+09 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.450917E+09 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.436882E+09 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.231954E+09 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.275712E+09 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 1885787.48 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 5988666.37 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.164359E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 1885787.48 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.450917E+09 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT OFFICE
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.123240E+10 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.107398E+10 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.115144E+10 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.120049E+10 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.123367E+10 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.127321E+10 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.141344E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.150140E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.136691E+10 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.146640E+10 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.124563E+10 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.125900E+10 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.154180E+11 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.107398E+10 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.150140E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT GNE
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 13791286.25 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 7208469.71 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 13408737.29 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 17165371.21 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 23230008.15 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.142053E+09 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.430564E+09 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.428678E+09 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.206248E+09 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.266397E+09 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 2065412.64 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 5820204.62 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.155663E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 2065412.64 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.430564E+09 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT GN1
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 9647520.49 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 728277.67 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 5107059.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 10915150.07 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 20399429.55 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.140261E+09 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.395505E+09 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.391207E+09 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.217134E+09 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.271655E+09 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 2225858.98 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 1499615.37 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.146628E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 728277.67 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.395505E+09 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT GN2
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 9747941.49 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 733780.66 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 5145055.04 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 10857086.45 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 20139661.30 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.138712E+09 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.394225E+09 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.390660E+09 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.214720E+09 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.271196E+09 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 2227163.98 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 1581518.85 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.145995E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 733780.66 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.394225E+09 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT GS1
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.149262E+09 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 57728539.26 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 22872500.04 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 76222632.35 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 42918473.69 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.143306E+09 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.429992E+09 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.532568E+09 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.458402E+09 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.583170E+09 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.224391E+09 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.209579E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.293041E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 22872500.04 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.583170E+09 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT GS2
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.161401E+09 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 63149558.05 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 26327686.77 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 85152151.23 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 50199494.01 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.160963E+09 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.472784E+09 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.581659E+09 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.495389E+09 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.632203E+09 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.241552E+09 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.222833E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.319361E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 26327686.77 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.632203E+09 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT MSW
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.463642E+09 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.306862E+09 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.251494E+09 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.636239E+09 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.467714E+09 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.892190E+09 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.154611E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.169969E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.136457E+10 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.144636E+10 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.599024E+09 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.584387E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.102583E+11 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.251494E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.169969E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT MNW
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 57702773.15 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 8206596.12 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 44395156.77 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.310257E+09 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.398762E+09 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.893024E+09 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.147387E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.141178E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.868554E+09 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.798109E+09 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 35153442.57 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 33953193.01 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.633377E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 8206596.12 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.147387E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT MSE
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.482922E+09 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.302578E+09 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.249443E+09 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.617018E+09 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.427815E+09 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.832107E+09 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.150490E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.168513E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.129481E+10 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.142363E+10 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.580483E+09 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.588100E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.998894E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.249443E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.168513E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT MNE
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 61231798.63 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 7289125.01 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 44920353.82 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.286924E+09 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.360261E+09 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.833612E+09 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.143286E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.139772E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.798594E+09 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.771928E+09 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 29855571.12 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 35913519.76 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.606110E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 7289125.01 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.143286E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT MN1
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 68849739.50 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 10378504.79 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 35870420.25 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.247282E+09 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.352502E+09 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.759148E+09 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.120852E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.117935E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.761854E+09 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.751434E+09 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 59436721.41 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 49646350.20 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.548427E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 10378504.79 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.120852E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT MN2
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 69755244.99 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 10251196.45 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 37335448.86 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.247325E+09 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.351478E+09 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.756631E+09 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.120676E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.117875E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.758656E+09 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.751417E+09 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 58286942.39 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 50165395.08 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.547681E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 10251196.45 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.120676E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT MS1
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.644481E+09 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.402269E+09 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.308372E+09 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.604646E+09 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.423615E+09 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.757196E+09 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.128178E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.147323E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.127044E+10 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.143204E+10 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.756738E+09 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.770884E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.101257E+11 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.308372E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.147323E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT MS2
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.647743E+09 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.402671E+09 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.309611E+09 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.604825E+09 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.422736E+09 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.754697E+09 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.128003E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.147258E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.126738E+10 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.143160E+10 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.756682E+09 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.772287E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.101228E+11 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.309611E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.147258E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT TSW
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.191940E+09 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.120643E+09 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.148186E+09 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.282784E+09 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.187245E+09 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.388560E+09 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.734228E+09 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.801979E+09 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.589003E+09 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.623249E+09 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.198500E+09 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.234291E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.450061E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.120643E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.801979E+09 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT TNW
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 53976343.64 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 30149632.85 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 54974294.69 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.133166E+09 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.149555E+09 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.380964E+09 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.690857E+09 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.649905E+09 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.342061E+09 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.318895E+09 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 33124680.22 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 49904171.05 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.288753E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 30149632.85 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.690857E+09 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT TSE
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.191608E+09 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.111405E+09 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.142945E+09 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.266551E+09 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.163989E+09 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.361972E+09 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.717676E+09 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.797201E+09 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.556150E+09 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.607338E+09 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.184708E+09 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.229286E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.433083E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.111405E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.797201E+09 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT TNE
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 51913145.50 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 29430699.83 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 51415119.89 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.121338E+09 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.126995E+09 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.353817E+09 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.675526E+09 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.647710E+09 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.314210E+09 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.304649E+09 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 31654340.32 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 47104447.87 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.275576E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 29430699.83 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.675526E+09 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT TN1
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 34031708.40 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 14835074.49 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 25201105.03 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 69958355.22 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 85538806.16 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.284141E+09 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.546885E+09 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.516233E+09 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.256659E+09 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.256952E+09 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 16047429.79 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 27538946.99 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.213402E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 14835074.49 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.546885E+09 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT TN2
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 34286702.42 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 14997857.69 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 25683421.73 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 71063619.65 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 86018121.54 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.283583E+09 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.546179E+09 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.516424E+09 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.256035E+09 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.257490E+09 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 16358208.71 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 27882619.65 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.213600E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 14997857.69 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.546179E+09 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT TS1
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.185853E+09 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.100723E+09 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.111583E+09 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.216133E+09 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.121140E+09 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.290907E+09 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.590063E+09 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.674148E+09 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.513633E+09 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.574141E+09 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.183282E+09 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.219423E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.378103E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.100723E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.674148E+09 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT TS2
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.187729E+09 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.101634E+09 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.113009E+09 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.217256E+09 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.121814E+09 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.290437E+09 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.589416E+09 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.674153E+09 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.512513E+09 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.574406E+09 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.183990E+09 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.220944E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.378730E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.101634E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.674153E+09 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT GSW
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 21808544.97 | 0.260405E+09 | 25853546.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 8550278.69 | 0.100713E+09 | 9010868.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 10152226.96 | 53896390.30 | 0.128573E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 18905659.06 | 0.238091E+09 | 11879597.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 11173607.30 | 0.143573E+09 | 25377.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 37579707.72 | 0.496379E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.111568E+09 | 0.150213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.131421E+09 | 0.177968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.105159E+09 | 0.139077E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.129090E+09 | 0.167660E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 35554210.71 | 0.447996E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 31790055.04 | 0.393129E+09 | 62246.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.652753E+09 | 0.848336E+10 | 0.175405E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 8550278.69 | 53896390.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.131421E+09 | 0.177968E+10 | 0.128573E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT GNW
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 11805720.26 | 7570888.49 | 0.243358E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 6904299.22 | 0.00 | 0.150055E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 13215089.35 | 0.00 | 0.287211E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 5151982.11 | 54754696.07 | 20092824.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 6481652.94 | 83308055.14 | 28873.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 37021357.05 | 0.490103E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.104253E+09 | 0.140540E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.100889E+09 | 0.136645E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 53479623.36 | 0.701614E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 63711971.01 | 0.822472E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 484239.37 | 5219941.53 | 1260220.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 5348467.34 | 2398259.81 | 0.111930E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.408746E+09 | 0.493929E+10 | 0.813936E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 484239.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.104253E+09 | 0.140540E+10 | 0.287211E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT OFFICE
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 0.107791E+10 | 0.608954E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.973592E+09 | 0.392005E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.107791E+10 | 0.290178E+09 | 22818.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.104313E+10 | 0.627004E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.107791E+10 | 0.618533E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.104313E+10 | 0.935915E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.107791E+10 | 0.139226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.107791E+10 | 0.176969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.104313E+10 | 0.132283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.107791E+10 | 0.156966E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.104313E+10 | 0.801851E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.107791E+10 | 0.710002E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.126915E+11 | 0.110389E+11 | 22818.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 0.973592E+09 | 0.290178E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.107791E+10 | 0.176969E+10 | 22818.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT GNE
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 11249952.76 | 9689585.17 | 0.228904E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 7208469.71 | 0.00 | 0.157548E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 13408737.29 | 0.00 | 0.293062E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 4609230.65 | 48957503.11 | 17967656.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 5430719.83 | 69711353.56 | 297142.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 32992221.34 | 0.436866E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 99515627.82 | 0.134393E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 98969030.45 | 0.134350E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 47506104.85 | 0.623292E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 61538879.78 | 0.793593E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 567376.37 | 5555568.99 | 2478812.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 5216947.41 | 2240371.32 | 0.109945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.388213E+09 | 0.467734E+10 | 0.810202E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 567376.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 99515627.82 | 0.134393E+10 | 0.293062E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT GN1
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 6080840.67 | 13653158.95 | 0.109634E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 728277.67 | 0.00 | 15997333.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 5107059.00 | 0.00 | 0.112182E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 2811272.87 | 31497689.90 | 8114432.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 4755657.78 | 61219721.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 32565676.34 | 0.430133E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 91420668.91 | 0.122978E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 90330652.07 | 0.122093E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 50085649.28 | 0.657464E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 62854467.87 | 0.812771E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 519246.53 | 6340264.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 681590.06 | 3061194.97 | 9407339.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.347941E+09 | 0.446685E+10 | 0.255335E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 519246.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 91420668.91 | 0.122978E+10 | 0.112182E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT GN2
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 6081969.24 | 14034592.34 | 0.109008E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 733780.66 | 0.00 | 16120705.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 5145055.04 | 0.00 | 0.113034E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 2795463.22 | 31330021.59 | 8049287.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 4695144.06 | 60445941.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 32205814.91 | 0.425410E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 91123197.72 | 0.122588E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 90203140.12 | 0.121934E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 49525526.47 | 0.650092E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 62747188.58 | 0.811348E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 519627.73 | 6342989.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 700894.42 | 3294954.96 | 9407011.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.346477E+09 | 0.444752E+10 | 0.255618E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 519627.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 91123197.72 | 0.122588E+10 | 0.113034E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT GS1
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 35059244.49 | 0.444219E+09 | 149846.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 13650927.85 | 0.169677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 6114395.61 | 65614725.94 | 21893047.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 17878784.59 | 0.229314E+09 | 3976252.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 10012995.22 | 0.128816E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 33280845.94 | 0.438788E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 99408298.86 | 0.133607E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.123084E+09 | 0.166407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.106033E+09 | 0.140293E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.135443E+09 | 0.176171E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 52787062.60 | 0.668060E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 49640451.11 | 0.618609E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.682392E+09 | 0.892787E+10 | 26019146.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 6114395.61 | 65614725.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.135443E+09 | 0.176171E+10 | 21893047.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT GS2
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 37929191.71 | 0.480644E+09 | 749596.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 14929369.19 | 0.185735E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 6846009.58 | 76366977.69 | 19746714.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 19947170.79 | 0.256398E+09 | 3584205.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 11711045.96 | 0.150755E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 37386337.08 | 0.492923E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.109331E+09 | 0.146990E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.134465E+09 | 0.181863E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.114620E+09 | 0.151798E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.146871E+09 | 0.191369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 56818793.77 | 0.719682E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 52772842.52 | 0.658168E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.743627E+09 | 0.974087E+10 | 24080515.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 6846009.58 | 76366977.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.146871E+09 | 0.191369E+10 | 19746714.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT MSW
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 0.109098E+09 | 0.137889E+10 | 2999499.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 72297751.21 | 0.910510E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 61042646.44 | 0.751197E+09 | 62857758.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.148653E+09 | 0.192868E+10 | 7354244.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.109214E+09 | 0.140786E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.207495E+09 | 0.273504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.357921E+09 | 0.481117E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.393186E+09 | 0.531764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.315865E+09 | 0.418130E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.335780E+09 | 0.435857E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.140870E+09 | 0.178724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.138383E+09 | 0.172854E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.238980E+10 | 0.312966E+11 | 73211501.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 61042646.44 | 0.751197E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.393186E+09 | 0.531764E+10 | 62857758.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT MNW
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 22043111.44 | 0.137412E+09 | 0.237956E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 1992823.46 | 23500397.91 | 1295798.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 15285971.38 | 0.114865E+09 | 0.137984E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 72799210.17 | 0.936087E+09 | 15607447.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 93090380.50 | 0.119961E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.207671E+09 | 0.274071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.341167E+09 | 0.458922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.326397E+09 | 0.441116E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.200752E+09 | 0.264139E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.184732E+09 | 0.238168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 8247913.20 | 0.102389E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 9947479.43 | 90911063.46 | 53375338.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.148413E+10 | 0.193689E+11 | 0.446219E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 1992823.46 | 23500397.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.341167E+09 | 0.458922E+10 | 0.237956E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT MSE
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 0.113628E+09 | 0.143815E+10 | 2163383.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 71339864.11 | 0.897049E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 60642181.64 | 0.745900E+09 | 65171073.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.144133E+09 | 0.187121E+10 | 6155404.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 99910714.10 | 0.128797E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.193514E+09 | 0.255343E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.348300E+09 | 0.469044E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.389761E+09 | 0.528423E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.299598E+09 | 0.397206E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.330511E+09 | 0.429364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.136564E+09 | 0.173191E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.139314E+09 | 0.174103E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.232722E+10 | 0.305070E+11 | 73489861.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 60642181.64 | 0.745900E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.389761E+09 | 0.528423E+10 | 65171073.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT MNE
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 22287933.60 | 0.150372E+09 | 0.222911E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 1838089.23 | 20478567.89 | 2968595.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 15814676.48 | 0.114496E+09 | 0.149891E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 67287904.40 | 0.865804E+09 | 13911926.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 84115380.62 | 0.108342E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.193845E+09 | 0.256055E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.331595E+09 | 0.446848E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.323084E+09 | 0.437615E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.184462E+09 | 0.242886E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.178639E+09 | 0.230035E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 7012976.75 | 86419253.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 10386417.04 | 96561471.38 | 52956122.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.142037E+10 | 0.185519E+11 | 0.442639E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 1838089.23 | 20478567.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.331595E+09 | 0.446848E+10 | 0.222911E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT MN1
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 17159594.08 | 0.200316E+09 | 29584866.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 2461527.18 | 29903329.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 8754821.89 | 0.106580E+09 | 11558402.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 57553375.81 | 0.745308E+09 | 262797.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 82248709.45 | 0.105786E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.176482E+09 | 0.232143E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.279648E+09 | 0.375323E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.272590E+09 | 0.367570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.176122E+09 | 0.231553E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.174132E+09 | 0.224662E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 13918720.98 | 0.174900E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 11727876.74 | 0.144323E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.127280E+10 | 0.167717E+11 | 41406066.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 2461527.18 | 29903329.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.279648E+09 | 0.375323E+10 | 29584866.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT MN2
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 17352651.61 | 0.203089E+09 | 29055578.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 2432057.69 | 29521816.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 9105059.69 | 0.110954E+09 | 11808194.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 57563355.38 | 0.745447E+09 | 252079.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 82010501.54 | 0.105479E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.175897E+09 | 0.231385E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.279239E+09 | 0.374803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.272447E+09 | 0.367410E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.175377E+09 | 0.230584E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.174128E+09 | 0.224646E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 13651999.36 | 0.171414E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 11851112.37 | 0.145830E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.127105E+10 | 0.167493E+11 | 41115853.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 2432057.69 | 29521816.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.279239E+09 | 0.374803E+10 | 29055578.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT MS1
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 0.151549E+09 | 0.192211E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 94747710.64 | 0.119572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 72204759.69 | 0.928970E+09 | 3379281.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.141001E+09 | 0.182822E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 98871158.86 | 0.127224E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.176042E+09 | 0.231301E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.296629E+09 | 0.397811E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.340738E+09 | 0.459847E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.294143E+09 | 0.389132E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.332781E+09 | 0.432139E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.177938E+09 | 0.226271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.182382E+09 | 0.228896E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.235903E+10 | 0.308012E+11 | 3379281.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 72204759.69 | 0.928970E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.340738E+09 | 0.459847E+10 | 3379281.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT MS2
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 0.152320E+09 | 0.193199E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 94844856.65 | 0.119696E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 72499133.09 | 0.932822E+09 | 3510817.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.141045E+09 | 0.182888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 98667001.82 | 0.126965E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.175462E+09 | 0.230553E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.296219E+09 | 0.397295E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.340585E+09 | 0.459686E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.293429E+09 | 0.388217E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.332679E+09 | 0.432030E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.177926E+09 | 0.226266E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.182714E+09 | 0.229336E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.235839E+10 | 0.307941E+11 | 3510817.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 72499133.09 | 0.932822E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.340585E+09 | 0.459686E+10 | 3510817.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT TSW
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 60711211.58 | 0.510971E+09 | 0.430771E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 41549882.34 | 0.307518E+09 | 0.364202E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 54266255.97 | 0.372481E+09 | 0.542871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 68874476.83 | 0.851584E+09 | 79771131.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 46422929.33 | 0.555606E+09 | 74279595.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 90390247.67 | 0.120273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.169923E+09 | 0.230635E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.185459E+09 | 0.253452E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.136116E+09 | 0.181534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.145297E+09 | 0.187994E+10 | 28234839.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 54232294.63 | 0.564335E+09 | 0.208033E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 69931338.53 | 0.639348E+09 | 0.399644E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.112317E+10 | 0.135407E+11 | 0.212781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 41549882.34 | 0.307518E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.185459E+09 | 0.253452E+10 | 0.542871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT TNW
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 41029473.57 | 49393717.29 | 0.788263E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 28131217.06 | 7655238.84 | 0.585210E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 38128558.87 | 66194781.95 | 0.701858E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 34767207.90 | 0.389261E+09 | 0.103813E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 37442922.77 | 0.441756E+09 | 69954692.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 88606970.40 | 0.117971E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.159857E+09 | 0.216860E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.150176E+09 | 0.204606E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 78871647.90 | 0.103952E+10 | 571593.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 75652419.61 | 0.939920E+09 | 59879433.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 23029242.68 | 38277833.73 | 0.424054E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 38494706.79 | 43121374.22 | 0.743425E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.794188E+09 | 0.840946E+10 | 0.347703E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 23029242.68 | 7655238.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.159857E+09 | 0.216860E+10 | 0.788263E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT TSE
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 60099276.71 | 0.512873E+09 | 0.418251E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 39401724.71 | 0.279708E+09 | 0.366597E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 52871695.11 | 0.357840E+09 | 0.541263E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 64953576.64 | 0.803840E+09 | 76557703.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 40991288.90 | 0.486102E+09 | 74644408.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 84205745.84 | 0.112304E+10 | 85922.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.166046E+09 | 0.226114E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.184320E+09 | 0.252998E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.128460E+09 | 0.171896E+10 | 112276.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.141572E+09 | 0.183553E+10 | 27805783.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 50973184.85 | 0.523759E+09 | 0.208249E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 68450578.05 | 0.626559E+09 | 0.393158E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.108234E+10 | 0.130593E+11 | 0.210672E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 39401724.71 | 0.279708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.184320E+09 | 0.252998E+10 | 0.541263E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT TNE
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 39152172.17 | 48638159.31 | 0.754685E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 27887042.04 | 5809033.93 | 0.587091E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 36959785.94 | 56515661.23 | 0.697086E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 31960779.28 | 0.353020E+09 | 0.103332E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 32267445.96 | 0.373505E+09 | 72903644.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 82287653.12 | 0.109772E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.156263E+09 | 0.212604E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.149630E+09 | 0.204561E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 72401193.21 | 0.954760E+09 | 1228539.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 72162307.71 | 0.896079E+09 | 56184850.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 22324924.63 | 35152265.36 | 0.416891E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 36809109.66 | 38814463.50 | 0.719903E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.760105E+09 | 0.803167E+10 | 0.340931E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 22324924.63 | 5809033.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.156263E+09 | 0.212604E+10 | 0.754685E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT TN1
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 25303324.02 | 33223534.14 | 0.486235E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 14338886.85 | 1853939.78 | 0.304894E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 19911107.59 | 20584963.37 | 0.393232E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 17635166.88 | 0.205790E+09 | 38139366.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 20735019.79 | 0.254423E+09 | 21668627.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 66051008.54 | 0.875845E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.126469E+09 | 0.170845E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.119220E+09 | 0.161777E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 59114479.35 | 0.776702E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 59670803.03 | 0.762476E+09 | 13349411.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 11496623.19 | 17056975.06 | 0.217156E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 22033744.48 | 20717830.68 | 0.436804E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.561980E+09 | 0.629490E+10 | 0.191148E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 11496623.19 | 1853939.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.126469E+09 | 0.170845E+10 | 0.486235E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT TN2
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 25354641.62 | 34004412.94 | 0.486154E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 14460099.49 | 2009840.04 | 0.307320E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 20084095.19 | 21791810.67 | 0.395043E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 17911448.12 | 0.209066E+09 | 38665074.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 20858753.62 | 0.255867E+09 | 21993844.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 65922252.51 | 0.874308E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.126305E+09 | 0.170662E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.119263E+09 | 0.161878E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 58968339.07 | 0.774916E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 59800515.24 | 0.763985E+09 | 13520196.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 11639343.21 | 17688528.07 | 0.219184E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 22157577.24 | 21544856.10 | 0.438138E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.562725E+09 | 0.630058E+10 | 0.192002E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 11639343.21 | 2009840.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.126305E+09 | 0.170662E+10 | 0.486154E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT TS1
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 50721647.60 | 0.526687E+09 | 0.195112E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 28399726.10 | 0.280806E+09 | 0.130324E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 35925875.61 | 0.299324E+09 | 0.274577E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 51288962.82 | 0.653891E+09 | 24322085.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 29078969.15 | 0.362156E+09 | 22176271.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 67641644.16 | 0.896913E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.136487E+09 | 0.184566E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.155845E+09 | 0.212283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.118689E+09 | 0.158094E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.133026E+09 | 0.173539E+10 | 1388482.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 45255355.47 | 0.539950E+09 | 58718367.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 57724455.24 | 0.629466E+09 | 0.159759E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.910084E+09 | 0.114740E+11 | 0.866377E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 28399726.10 | 0.280806E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.155845E+09 | 0.212283E+10 | 0.274577E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT TS2
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 51163380.84 | 0.532414E+09 | 0.195137E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 28644080.31 | 0.283454E+09 | 0.131167E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 36304894.82 | 0.303558E+09 | 0.275906E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 51554253.25 | 0.657498E+09 | 24376580.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 29249384.70 | 0.364224E+09 | 22526518.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 67533718.39 | 0.895685E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.136336E+09 | 0.184410E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.155845E+09 | 0.212349E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.118428E+09 | 0.157790E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.133090E+09 | 0.173656E+10 | 1428902.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 45442671.02 | 0.542132E+09 | 59264795.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 58109954.00 | 0.634079E+09 | 0.160490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.911702E+09 | 0.114951E+11 | 0.870297E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 28644080.31 | 0.283454E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.155845E+09 | 0.212349E+10 | 0.275906E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT GSW
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 21808544.97 | 0.00 | 0.00 | 0.00 | 67158610.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 8550278.69 | 0.00 | 0.00 | 0.00 | 26243977.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 10152226.96 | 0.00 | 0.00 | 0.00 | 13765161.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 18905659.06 | 0.00 | 0.00 | 0.00 | 60512617.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 11173607.30 | 0.00 | 0.00 | 0.00 | 36696758.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 37579707.72 | 0.00 | 0.00 | 0.00 | 0.124197E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.111568E+09 | 0.00 | 0.00 | 0.00 | 0.370927E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.131421E+09 | 0.00 | 0.00 | 0.00 | 0.437215E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.105159E+09 | 0.00 | 0.00 | 0.00 | 0.349685E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.129090E+09 | 0.00 | 0.00 | 0.00 | 0.427358E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 35554210.71 | 0.00 | 0.00 | 0.00 | 0.115488E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 31790055.04 | 0.00 | 0.00 | 0.00 | 0.102191E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.652753E+09 | 0.00 | 0.00 | 0.00 | 0.213144E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 8550278.69 | 0.00 | 0.00 | 0.00 | 13765161.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.131421E+09 | 0.00 | 0.00 | 0.00 | 0.437215E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT GNW
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 11805720.26 | 0.00 | 0.00 | 0.00 | 1989251.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 6904299.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 13215089.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 5151982.11 | 0.00 | 0.00 | 0.00 | 13993201.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 6481652.94 | 0.00 | 0.00 | 0.00 | 21300866.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 37021357.05 | 0.00 | 0.00 | 0.00 | 0.122385E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.104253E+09 | 0.00 | 0.00 | 0.00 | 0.346665E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.100889E+09 | 0.00 | 0.00 | 0.00 | 0.335992E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 53479623.36 | 0.00 | 0.00 | 0.00 | 0.178474E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 63711971.01 | 0.00 | 0.00 | 0.00 | 0.212000E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 484239.37 | 0.00 | 0.00 | 0.00 | 1401548.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 5348467.34 | 0.00 | 0.00 | 0.00 | 640199.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.408746E+09 | 0.00 | 0.00 | 0.00 | 0.123484E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 484239.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.104253E+09 | 0.00 | 0.00 | 0.00 | 0.346665E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT OFFICE
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 0.107791E+10 | 0.00 | 0.00 | 0.00 | 0.154495E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.973592E+09 | 0.00 | 0.00 | 0.00 | 0.100389E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.107791E+10 | 0.00 | 0.00 | 0.00 | 73539514.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.104313E+10 | 0.00 | 0.00 | 0.00 | 0.157358E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.107791E+10 | 0.00 | 0.00 | 0.00 | 0.155766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.104313E+10 | 0.00 | 0.00 | 0.00 | 0.230079E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.107791E+10 | 0.00 | 0.00 | 0.00 | 0.335532E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.107791E+10 | 0.00 | 0.00 | 0.00 | 0.423499E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.104313E+10 | 0.00 | 0.00 | 0.00 | 0.323781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.107791E+10 | 0.00 | 0.00 | 0.00 | 0.388494E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.104313E+10 | 0.00 | 0.00 | 0.00 | 0.202494E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.107791E+10 | 0.00 | 0.00 | 0.00 | 0.181098E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.126915E+11 | 0.00 | 0.00 | 0.00 | 0.272652E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 0.973592E+09 | 0.00 | 0.00 | 0.00 | 73539514.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.107791E+10 | 0.00 | 0.00 | 0.00 | 0.423499E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT GNE
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 11249952.76 | 0.00 | 0.00 | 0.00 | 2541333.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 7208469.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 13408737.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 4609230.65 | 0.00 | 0.00 | 0.00 | 12556140.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 5430719.83 | 0.00 | 0.00 | 0.00 | 17799288.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 32992221.34 | 0.00 | 0.00 | 0.00 | 0.109060E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 99515627.82 | 0.00 | 0.00 | 0.00 | 0.331048E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 98969030.45 | 0.00 | 0.00 | 0.00 | 0.329709E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 47506104.85 | 0.00 | 0.00 | 0.00 | 0.158742E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 61538879.78 | 0.00 | 0.00 | 0.00 | 0.204858E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 567376.37 | 0.00 | 0.00 | 0.00 | 1498036.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 5216947.41 | 0.00 | 0.00 | 0.00 | 603257.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.388213E+09 | 0.00 | 0.00 | 0.00 | 0.116842E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 567376.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 99515627.82 | 0.00 | 0.00 | 0.00 | 0.331048E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT GN1
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 6080840.67 | 0.00 | 0.00 | 0.00 | 3566679.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 728277.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 5107059.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 2811272.87 | 0.00 | 0.00 | 0.00 | 8103877.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 4755657.78 | 0.00 | 0.00 | 0.00 | 15643771.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 32565676.34 | 0.00 | 0.00 | 0.00 | 0.107695E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 91420668.91 | 0.00 | 0.00 | 0.00 | 0.304084E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 90330652.07 | 0.00 | 0.00 | 0.00 | 0.300876E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 50085649.28 | 0.00 | 0.00 | 0.00 | 0.167048E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 62854467.87 | 0.00 | 0.00 | 0.00 | 0.208800E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 519246.53 | 0.00 | 0.00 | 0.00 | 1706612.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 681590.06 | 0.00 | 0.00 | 0.00 | 818025.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.347941E+09 | 0.00 | 0.00 | 0.00 | 0.111834E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 519246.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 91420668.91 | 0.00 | 0.00 | 0.00 | 0.304084E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT GN2
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 6081969.24 | 0.00 | 0.00 | 0.00 | 3665972.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 733780.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 5145055.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 2795463.22 | 0.00 | 0.00 | 0.00 | 8061623.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 4695144.06 | 0.00 | 0.00 | 0.00 | 15444517.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 32205814.91 | 0.00 | 0.00 | 0.00 | 0.106506E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 91123197.72 | 0.00 | 0.00 | 0.00 | 0.303102E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 90203140.12 | 0.00 | 0.00 | 0.00 | 0.300457E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 49525526.47 | 0.00 | 0.00 | 0.00 | 0.165195E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 62747188.58 | 0.00 | 0.00 | 0.00 | 0.208449E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 519627.73 | 0.00 | 0.00 | 0.00 | 1707536.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 700894.42 | 0.00 | 0.00 | 0.00 | 880624.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.346477E+09 | 0.00 | 0.00 | 0.00 | 0.111347E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 519627.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 91123197.72 | 0.00 | 0.00 | 0.00 | 0.303102E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT GS1
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 35059244.49 | 0.00 | 0.00 | 0.00 | 0.114203E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 13650927.85 | 0.00 | 0.00 | 0.00 | 44077611.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 6114395.61 | 0.00 | 0.00 | 0.00 | 16758104.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 17878784.59 | 0.00 | 0.00 | 0.00 | 58343847.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 10012995.22 | 0.00 | 0.00 | 0.00 | 32905478.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 33280845.94 | 0.00 | 0.00 | 0.00 | 0.110025E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 99408298.86 | 0.00 | 0.00 | 0.00 | 0.330584E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.123084E+09 | 0.00 | 0.00 | 0.00 | 0.409485E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.106033E+09 | 0.00 | 0.00 | 0.00 | 0.352369E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.135443E+09 | 0.00 | 0.00 | 0.00 | 0.447727E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 52787062.60 | 0.00 | 0.00 | 0.00 | 0.171604E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 49640451.11 | 0.00 | 0.00 | 0.00 | 0.159939E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.682392E+09 | 0.00 | 0.00 | 0.00 | 0.224802E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 6114395.61 | 0.00 | 0.00 | 0.00 | 16758104.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.135443E+09 | 0.00 | 0.00 | 0.00 | 0.447727E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT GS2
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 37929191.71 | 0.00 | 0.00 | 0.00 | 0.123471E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 14929369.19 | 0.00 | 0.00 | 0.00 | 48220188.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 6846009.58 | 0.00 | 0.00 | 0.00 | 19481677.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 19947170.79 | 0.00 | 0.00 | 0.00 | 65204980.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 11711045.96 | 0.00 | 0.00 | 0.00 | 38488448.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 37386337.08 | 0.00 | 0.00 | 0.00 | 0.123577E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.109331E+09 | 0.00 | 0.00 | 0.00 | 0.363453E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.134465E+09 | 0.00 | 0.00 | 0.00 | 0.447194E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.114620E+09 | 0.00 | 0.00 | 0.00 | 0.380769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.146871E+09 | 0.00 | 0.00 | 0.00 | 0.485332E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 56818793.77 | 0.00 | 0.00 | 0.00 | 0.184733E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 52772842.52 | 0.00 | 0.00 | 0.00 | 0.170060E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.743627E+09 | 0.00 | 0.00 | 0.00 | 0.244998E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 6846009.58 | 0.00 | 0.00 | 0.00 | 19481677.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.146871E+09 | 0.00 | 0.00 | 0.00 | 0.485332E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT MSW
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 0.109098E+09 | 0.00 | 0.00 | 0.00 | 0.354544E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 72297751.21 | 0.00 | 0.00 | 0.00 | 0.234564E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 61042646.44 | 0.00 | 0.00 | 0.00 | 0.190452E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.148653E+09 | 0.00 | 0.00 | 0.00 | 0.487586E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.109214E+09 | 0.00 | 0.00 | 0.00 | 0.358500E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.207495E+09 | 0.00 | 0.00 | 0.00 | 0.684695E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.357921E+09 | 0.00 | 0.00 | 0.00 | 0.118819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.393186E+09 | 0.00 | 0.00 | 0.00 | 0.130650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.315865E+09 | 0.00 | 0.00 | 0.00 | 0.104871E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.335780E+09 | 0.00 | 0.00 | 0.00 | 0.111058E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.140870E+09 | 0.00 | 0.00 | 0.00 | 0.458154E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.138383E+09 | 0.00 | 0.00 | 0.00 | 0.446004E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.238980E+10 | 0.00 | 0.00 | 0.00 | 0.786848E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 61042646.44 | 0.00 | 0.00 | 0.00 | 0.190452E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.393186E+09 | 0.00 | 0.00 | 0.00 | 0.130650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT MNW
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 22043111.44 | 0.00 | 0.00 | 0.00 | 35659661.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 1992823.46 | 0.00 | 0.00 | 0.00 | 6213772.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 15285971.38 | 0.00 | 0.00 | 0.00 | 29109185.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 72799210.17 | 0.00 | 0.00 | 0.00 | 0.237457E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 93090380.50 | 0.00 | 0.00 | 0.00 | 0.305672E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.207671E+09 | 0.00 | 0.00 | 0.00 | 0.685353E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.341167E+09 | 0.00 | 0.00 | 0.00 | 0.113270E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.326397E+09 | 0.00 | 0.00 | 0.00 | 0.108539E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.200752E+09 | 0.00 | 0.00 | 0.00 | 0.667802E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.184732E+09 | 0.00 | 0.00 | 0.00 | 0.613377E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 8247913.20 | 0.00 | 0.00 | 0.00 | 26905529.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 9947479.43 | 0.00 | 0.00 | 0.00 | 24005713.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.148413E+10 | 0.00 | 0.00 | 0.00 | 0.484964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 1992823.46 | 0.00 | 0.00 | 0.00 | 6213772.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.341167E+09 | 0.00 | 0.00 | 0.00 | 0.113270E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT MSE
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 0.113628E+09 | 0.00 | 0.00 | 0.00 | 0.369294E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 71339864.11 | 0.00 | 0.00 | 0.00 | 0.231238E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 60642181.64 | 0.00 | 0.00 | 0.00 | 0.188801E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.144133E+09 | 0.00 | 0.00 | 0.00 | 0.472886E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 99910714.10 | 0.00 | 0.00 | 0.00 | 0.327905E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.193514E+09 | 0.00 | 0.00 | 0.00 | 0.638593E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.348300E+09 | 0.00 | 0.00 | 0.00 | 0.115660E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.389761E+09 | 0.00 | 0.00 | 0.00 | 0.129537E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.299598E+09 | 0.00 | 0.00 | 0.00 | 0.995211E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.330511E+09 | 0.00 | 0.00 | 0.00 | 0.109312E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.136564E+09 | 0.00 | 0.00 | 0.00 | 0.443919E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.139314E+09 | 0.00 | 0.00 | 0.00 | 0.448786E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.232722E+10 | 0.00 | 0.00 | 0.00 | 0.766173E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 60642181.64 | 0.00 | 0.00 | 0.00 | 0.188801E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.389761E+09 | 0.00 | 0.00 | 0.00 | 0.129537E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT MNE
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 22287933.60 | 0.00 | 0.00 | 0.00 | 38943865.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 1838089.23 | 0.00 | 0.00 | 0.00 | 5451035.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 15814676.48 | 0.00 | 0.00 | 0.00 | 29105677.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 67287904.40 | 0.00 | 0.00 | 0.00 | 0.219636E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 84115380.62 | 0.00 | 0.00 | 0.00 | 0.276146E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.193845E+09 | 0.00 | 0.00 | 0.00 | 0.639767E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.331595E+09 | 0.00 | 0.00 | 0.00 | 0.110126E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.323084E+09 | 0.00 | 0.00 | 0.00 | 0.107463E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.184462E+09 | 0.00 | 0.00 | 0.00 | 0.614132E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.178639E+09 | 0.00 | 0.00 | 0.00 | 0.593290E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 7012976.75 | 0.00 | 0.00 | 0.00 | 22842594.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 10386417.04 | 0.00 | 0.00 | 0.00 | 25527102.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.142037E+10 | 0.00 | 0.00 | 0.00 | 0.464074E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 1838089.23 | 0.00 | 0.00 | 0.00 | 5451035.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.331595E+09 | 0.00 | 0.00 | 0.00 | 0.110126E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT MN1
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 17159594.08 | 0.00 | 0.00 | 0.00 | 51690145.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 2461527.18 | 0.00 | 0.00 | 0.00 | 7916977.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 8754821.89 | 0.00 | 0.00 | 0.00 | 27115598.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 57553375.81 | 0.00 | 0.00 | 0.00 | 0.189729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 82248709.45 | 0.00 | 0.00 | 0.00 | 0.270253E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.176482E+09 | 0.00 | 0.00 | 0.00 | 0.582667E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.279648E+09 | 0.00 | 0.00 | 0.00 | 0.928871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.272590E+09 | 0.00 | 0.00 | 0.00 | 0.906763E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.176122E+09 | 0.00 | 0.00 | 0.00 | 0.585732E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.174132E+09 | 0.00 | 0.00 | 0.00 | 0.577302E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 13918720.98 | 0.00 | 0.00 | 0.00 | 45518000.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 11727876.74 | 0.00 | 0.00 | 0.00 | 37918473.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.127280E+10 | 0.00 | 0.00 | 0.00 | 0.421148E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 2461527.18 | 0.00 | 0.00 | 0.00 | 7916977.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.279648E+09 | 0.00 | 0.00 | 0.00 | 0.928871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT MN2
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 17352651.61 | 0.00 | 0.00 | 0.00 | 52402593.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 2432057.69 | 0.00 | 0.00 | 0.00 | 7819138.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 9105059.69 | 0.00 | 0.00 | 0.00 | 28230389.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 57563355.38 | 0.00 | 0.00 | 0.00 | 0.189762E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 82010501.54 | 0.00 | 0.00 | 0.00 | 0.269467E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.175897E+09 | 0.00 | 0.00 | 0.00 | 0.580734E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.279239E+09 | 0.00 | 0.00 | 0.00 | 0.927525E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.272447E+09 | 0.00 | 0.00 | 0.00 | 0.906299E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.175377E+09 | 0.00 | 0.00 | 0.00 | 0.583279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.174128E+09 | 0.00 | 0.00 | 0.00 | 0.577289E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 13651999.36 | 0.00 | 0.00 | 0.00 | 44634943.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 11851112.37 | 0.00 | 0.00 | 0.00 | 38314282.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.127105E+10 | 0.00 | 0.00 | 0.00 | 0.420576E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 2432057.69 | 0.00 | 0.00 | 0.00 | 7819138.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.279239E+09 | 0.00 | 0.00 | 0.00 | 0.927525E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT MS1
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 0.151549E+09 | 0.00 | 0.00 | 0.00 | 0.492932E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 94747710.64 | 0.00 | 0.00 | 0.00 | 0.307521E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 72204759.69 | 0.00 | 0.00 | 0.00 | 0.236167E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.141001E+09 | 0.00 | 0.00 | 0.00 | 0.463645E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 98871158.86 | 0.00 | 0.00 | 0.00 | 0.324743E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.176042E+09 | 0.00 | 0.00 | 0.00 | 0.581153E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.296629E+09 | 0.00 | 0.00 | 0.00 | 0.985155E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.340738E+09 | 0.00 | 0.00 | 0.00 | 0.113249E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.294143E+09 | 0.00 | 0.00 | 0.00 | 0.976298E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.332781E+09 | 0.00 | 0.00 | 0.00 | 0.109925E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.177938E+09 | 0.00 | 0.00 | 0.00 | 0.578801E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.182382E+09 | 0.00 | 0.00 | 0.00 | 0.588502E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.235903E+10 | 0.00 | 0.00 | 0.00 | 0.776666E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 72204759.69 | 0.00 | 0.00 | 0.00 | 0.236167E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.340738E+09 | 0.00 | 0.00 | 0.00 | 0.113249E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT MS2
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 0.152320E+09 | 0.00 | 0.00 | 0.00 | 0.495423E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 94844856.65 | 0.00 | 0.00 | 0.00 | 0.307826E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 72499133.09 | 0.00 | 0.00 | 0.00 | 0.237112E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.141045E+09 | 0.00 | 0.00 | 0.00 | 0.463780E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 98667001.82 | 0.00 | 0.00 | 0.00 | 0.324069E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.175462E+09 | 0.00 | 0.00 | 0.00 | 0.579236E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.296219E+09 | 0.00 | 0.00 | 0.00 | 0.983808E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.340585E+09 | 0.00 | 0.00 | 0.00 | 0.113199E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.293429E+09 | 0.00 | 0.00 | 0.00 | 0.973952E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.332679E+09 | 0.00 | 0.00 | 0.00 | 0.109892E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.177926E+09 | 0.00 | 0.00 | 0.00 | 0.578756E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.182714E+09 | 0.00 | 0.00 | 0.00 | 0.589572E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.235839E+10 | 0.00 | 0.00 | 0.00 | 0.776445E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 72499133.09 | 0.00 | 0.00 | 0.00 | 0.237112E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.340585E+09 | 0.00 | 0.00 | 0.00 | 0.113199E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT TSW
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 60711211.58 | 0.00 | 0.00 | 0.00 | 0.131229E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 41549882.34 | 0.00 | 0.00 | 0.00 | 79093236.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 54266255.97 | 0.00 | 0.00 | 0.00 | 93919963.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 68874476.83 | 0.00 | 0.00 | 0.00 | 0.213909E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 46422929.33 | 0.00 | 0.00 | 0.00 | 0.140822E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 90390247.67 | 0.00 | 0.00 | 0.00 | 0.298170E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.169923E+09 | 0.00 | 0.00 | 0.00 | 0.564305E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.185459E+09 | 0.00 | 0.00 | 0.00 | 0.616520E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.136116E+09 | 0.00 | 0.00 | 0.00 | 0.452886E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.145297E+09 | 0.00 | 0.00 | 0.00 | 0.477952E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 54232294.63 | 0.00 | 0.00 | 0.00 | 0.144268E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 69931338.53 | 0.00 | 0.00 | 0.00 | 0.164360E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.112317E+10 | 0.00 | 0.00 | 0.00 | 0.337743E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 41549882.34 | 0.00 | 0.00 | 0.00 | 79093236.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.185459E+09 | 0.00 | 0.00 | 0.00 | 0.616520E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT TNW
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 41029473.57 | 0.00 | 0.00 | 0.00 | 12946870.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 28131217.06 | 0.00 | 0.00 | 0.00 | 2018415.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 38128558.87 | 0.00 | 0.00 | 0.00 | 16845735.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 34767207.90 | 0.00 | 0.00 | 0.00 | 98399012.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 37442922.77 | 0.00 | 0.00 | 0.00 | 0.112112E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 88606970.40 | 0.00 | 0.00 | 0.00 | 0.292357E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.159857E+09 | 0.00 | 0.00 | 0.00 | 0.531000E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.150176E+09 | 0.00 | 0.00 | 0.00 | 0.499729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 78871647.90 | 0.00 | 0.00 | 0.00 | 0.263190E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 75652419.61 | 0.00 | 0.00 | 0.00 | 0.243243E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 23029242.68 | 0.00 | 0.00 | 0.00 | 10095437.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 38494706.79 | 0.00 | 0.00 | 0.00 | 11409464.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.794188E+09 | 0.00 | 0.00 | 0.00 | 0.209334E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 23029242.68 | 0.00 | 0.00 | 0.00 | 2018415.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.159857E+09 | 0.00 | 0.00 | 0.00 | 0.531000E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT TSE
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 60099276.71 | 0.00 | 0.00 | 0.00 | 0.131509E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 39401724.71 | 0.00 | 0.00 | 0.00 | 72003313.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 52871695.11 | 0.00 | 0.00 | 0.00 | 90072884.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 64953576.64 | 0.00 | 0.00 | 0.00 | 0.201598E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 40991288.90 | 0.00 | 0.00 | 0.00 | 0.122998E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 84205745.84 | 0.00 | 0.00 | 0.00 | 0.277767E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.166046E+09 | 0.00 | 0.00 | 0.00 | 0.551631E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.184320E+09 | 0.00 | 0.00 | 0.00 | 0.612881E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.128460E+09 | 0.00 | 0.00 | 0.00 | 0.427690E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.141572E+09 | 0.00 | 0.00 | 0.00 | 0.465766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 50973184.85 | 0.00 | 0.00 | 0.00 | 0.133735E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 68450578.05 | 0.00 | 0.00 | 0.00 | 0.160835E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.108234E+10 | 0.00 | 0.00 | 0.00 | 0.324849E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 39401724.71 | 0.00 | 0.00 | 0.00 | 72003313.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.184320E+09 | 0.00 | 0.00 | 0.00 | 0.612881E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT TNE
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 39152172.17 | 0.00 | 0.00 | 0.00 | 12760973.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 27887042.04 | 0.00 | 0.00 | 0.00 | 1543657.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 36959785.94 | 0.00 | 0.00 | 0.00 | 14455333.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 31960779.28 | 0.00 | 0.00 | 0.00 | 89377499.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 32267445.96 | 0.00 | 0.00 | 0.00 | 94727398.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 82287653.12 | 0.00 | 0.00 | 0.00 | 0.271530E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.156263E+09 | 0.00 | 0.00 | 0.00 | 0.519264E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.149630E+09 | 0.00 | 0.00 | 0.00 | 0.498080E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 72401193.21 | 0.00 | 0.00 | 0.00 | 0.241808E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 72162307.71 | 0.00 | 0.00 | 0.00 | 0.232487E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 22324924.63 | 0.00 | 0.00 | 0.00 | 9329415.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 36809109.66 | 0.00 | 0.00 | 0.00 | 10295338.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.760105E+09 | 0.00 | 0.00 | 0.00 | 0.199566E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 22324924.63 | 0.00 | 0.00 | 0.00 | 1543657.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.156263E+09 | 0.00 | 0.00 | 0.00 | 0.519264E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT TN1
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 25303324.02 | 0.00 | 0.00 | 0.00 | 8728384.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 14338886.85 | 0.00 | 0.00 | 0.00 | 496187.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 19911107.59 | 0.00 | 0.00 | 0.00 | 5289997.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 17635166.88 | 0.00 | 0.00 | 0.00 | 52323188.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 20735019.79 | 0.00 | 0.00 | 0.00 | 64803786.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 66051008.54 | 0.00 | 0.00 | 0.00 | 0.218090E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.126469E+09 | 0.00 | 0.00 | 0.00 | 0.420416E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.119220E+09 | 0.00 | 0.00 | 0.00 | 0.397013E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 59114479.35 | 0.00 | 0.00 | 0.00 | 0.197545E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 59670803.03 | 0.00 | 0.00 | 0.00 | 0.197281E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 11496623.19 | 0.00 | 0.00 | 0.00 | 4550806.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 22033744.48 | 0.00 | 0.00 | 0.00 | 5505202.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.561980E+09 | 0.00 | 0.00 | 0.00 | 0.157204E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 11496623.19 | 0.00 | 0.00 | 0.00 | 496187.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.126469E+09 | 0.00 | 0.00 | 0.00 | 0.420416E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT TN2
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 25354641.62 | 0.00 | 0.00 | 0.00 | 8932060.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 14460099.49 | 0.00 | 0.00 | 0.00 | 537758.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 20084095.19 | 0.00 | 0.00 | 0.00 | 5599326.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 17911448.12 | 0.00 | 0.00 | 0.00 | 53152171.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 20858753.62 | 0.00 | 0.00 | 0.00 | 65159367.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 65922252.51 | 0.00 | 0.00 | 0.00 | 0.217660E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.126305E+09 | 0.00 | 0.00 | 0.00 | 0.419875E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.119263E+09 | 0.00 | 0.00 | 0.00 | 0.397161E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 58968339.07 | 0.00 | 0.00 | 0.00 | 0.197067E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 59800515.24 | 0.00 | 0.00 | 0.00 | 0.197690E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 11639343.21 | 0.00 | 0.00 | 0.00 | 4718865.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 22157577.24 | 0.00 | 0.00 | 0.00 | 5725042.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.562725E+09 | 0.00 | 0.00 | 0.00 | 0.157328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 11639343.21 | 0.00 | 0.00 | 0.00 | 537758.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.126305E+09 | 0.00 | 0.00 | 0.00 | 0.419875E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT TS1
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 50721647.60 | 0.00 | 0.00 | 0.00 | 0.135131E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 28399726.10 | 0.00 | 0.00 | 0.00 | 72323405.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 35925875.61 | 0.00 | 0.00 | 0.00 | 75657064.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 51288962.82 | 0.00 | 0.00 | 0.00 | 0.164844E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 29078969.15 | 0.00 | 0.00 | 0.00 | 92061266.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 67641644.16 | 0.00 | 0.00 | 0.00 | 0.223265E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.136487E+09 | 0.00 | 0.00 | 0.00 | 0.453576E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.155845E+09 | 0.00 | 0.00 | 0.00 | 0.518304E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.118689E+09 | 0.00 | 0.00 | 0.00 | 0.394943E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.133026E+09 | 0.00 | 0.00 | 0.00 | 0.441114E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 45255355.47 | 0.00 | 0.00 | 0.00 | 0.138027E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 57724455.24 | 0.00 | 0.00 | 0.00 | 0.161698E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.910084E+09 | 0.00 | 0.00 | 0.00 | 0.287094E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 28399726.10 | 0.00 | 0.00 | 0.00 | 72323405.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.155845E+09 | 0.00 | 0.00 | 0.00 | 0.518304E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT TS2
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 51163380.84 | 0.00 | 0.00 | 0.00 | 0.136566E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 28644080.31 | 0.00 | 0.00 | 0.00 | 72989798.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 36304894.82 | 0.00 | 0.00 | 0.00 | 76703881.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 51554253.25 | 0.00 | 0.00 | 0.00 | 0.165702E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 29249384.70 | 0.00 | 0.00 | 0.00 | 92564162.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 67533718.39 | 0.00 | 0.00 | 0.00 | 0.222903E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.136336E+09 | 0.00 | 0.00 | 0.00 | 0.453080E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.155845E+09 | 0.00 | 0.00 | 0.00 | 0.518308E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.118428E+09 | 0.00 | 0.00 | 0.00 | 0.394085E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.133090E+09 | 0.00 | 0.00 | 0.00 | 0.441316E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 45442671.02 | 0.00 | 0.00 | 0.00 | 0.138548E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 58109954.00 | 0.00 | 0.00 | 0.00 | 0.162834E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.911702E+09 | 0.00 | 0.00 | 0.00 | 0.287560E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 28644080.31 | 0.00 | 0.00 | 0.00 | 72989798.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.155845E+09 | 0.00 | 0.00 | 0.00 | 0.518308E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: G SW APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.671402E+09 | 5808399.31 | 0.00 | 674618.22 | 0.00 | 5373890.38 | 0.187187E+09 | 0.00 | 0.35 |
| February | 0.659988E+09 | 1478393.47 | 0.00 | 336930.92 | 0.00 | 0.00 | 72383277.50 | 0.00 | 0.35 |
| March | 0.726197E+09 | 682705.84 | 0.00 | 123730.58 | 17346.30 | 65894463.05 | 28512530.28 | 0.00 | 0.35 |
| April | 0.536490E+09 | 4785726.00 | 0.00 | 506749.99 | 944352.15 | 11465498.24 | 0.118268E+09 | 0.00 | 0.35 |
| May | 0.560730E+09 | 1670543.02 | 0.00 | 386784.63 | 35015.73 | 0.00 | 0.104255E+09 | 0.00 | 0.35 |
| June | 0.303606E+09 | 13802104.28 | 0.00 | 769183.35 | 0.00 | 0.00 | 0.184408E+09 | 0.00 | 0.36 |
| July | 38543083.60 | 87078544.87 | 0.00 | 1456220.18 | 0.00 | 0.00 | 0.276564E+09 | 0.00 | 0.36 |
| August | 26448684.61 | 0.113312E+09 | 0.00 | 1284358.07 | 0.00 | 0.00 | 0.250645E+09 | 0.00 | 0.36 |
| September | 71181186.16 | 43467227.65 | 0.00 | 1871487.55 | 0.00 | 0.00 | 0.336810E+09 | 0.00 | 0.36 |
| October | 0.156893E+09 | 83746349.40 | 0.00 | 1739288.42 | 0.00 | 0.00 | 0.293105E+09 | 0.00 | 0.36 |
| November | 0.469528E+09 | 4299029.25 | 0.00 | 1252482.42 | 0.00 | 0.00 | 0.318832E+09 | 0.00 | 0.35 |
| December | 0.639610E+09 | 4229908.11 | 0.00 | 953272.90 | 0.00 | 0.00 | 0.211941E+09 | 0.00 | 0.35 |
| Annual Sum or Average | 0.486062E+10 | 0.364361E+09 | 0.00 | 11355107.22 | 996714.17 | 82733851.67 | 0.238291E+10 | 0.00 | 0.36 |
| Minimum of Months | 26448684.61 | 682705.84 | 0.00 | 123730.58 | 0.00 | 0.00 | 28512530.28 | 0.00 | 0.35 |
| Maximum of Months | 0.726197E+09 | 0.113312E+09 | 0.00 | 1871487.55 | 944352.15 | 65894463.05 | 0.336810E+09 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: G NW APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.604075E+09 | 1039585.59 | 0.00 | 7235.40 | 6167919.41 | 0.154199E+09 | 2176025.84 | 0.00 | 0.35 |
| February | 0.591953E+09 | 0.00 | 0.00 | 0.00 | 1976653.02 | 47645271.01 | 0.00 | 0.00 | 0.35 |
| March | 0.595949E+09 | 0.00 | 0.00 | 0.00 | 2537878.03 | 0.165936E+09 | 0.00 | 0.00 | 0.35 |
| April | 0.582754E+09 | 2650663.64 | 0.00 | 101310.61 | 3354078.36 | 13124358.73 | 26413837.88 | 0.00 | 0.35 |
| May | 0.579696E+09 | 1273001.66 | 0.00 | 263378.74 | 45188.29 | 0.00 | 79881195.58 | 0.00 | 0.35 |
| June | 0.293576E+09 | 12298553.49 | 0.00 | 816249.10 | 0.00 | 0.00 | 0.194591E+09 | 0.00 | 0.36 |
| July | 36034212.73 | 80683440.91 | 0.00 | 1464669.55 | 0.00 | 0.00 | 0.280363E+09 | 0.00 | 0.36 |
| August | 55773705.00 | 93184674.62 | 0.00 | 1071034.51 | 0.00 | 0.00 | 0.242920E+09 | 0.00 | 0.36 |
| September | 0.158646E+09 | 32383405.80 | 0.00 | 1111980.79 | 0.00 | 0.00 | 0.288566E+09 | 0.00 | 0.36 |
| October | 0.278310E+09 | 73158910.18 | 0.00 | 819701.43 | 185926.89 | 0.00 | 0.181663E+09 | 0.00 | 0.36 |
| November | 0.697038E+09 | 2403250.52 | 0.00 | 1613.59 | 2629506.03 | 0.00 | 2034334.42 | 0.00 | 0.35 |
| December | 0.697563E+09 | 344655.04 | 0.00 | 2762.32 | 6505813.31 | 33110512.27 | 1095244.71 | 0.00 | 0.35 |
| Annual Sum or Average | 0.517137E+10 | 0.299420E+09 | 0.00 | 5659936.04 | 23402963.34 | 0.414015E+09 | 0.129970E+10 | 0.00 | 0.35 |
| Minimum of Months | 36034212.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
| Maximum of Months | 0.697563E+09 | 93184674.62 | 0.00 | 1464669.55 | 6505813.31 | 0.165936E+09 | 0.288566E+09 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: OFFICE
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.115360E+10 | 1367689.81 | 0.00 | 870191.11 | 1318868.95 | 0.00 | 0.155856E+09 | 0.00 | 0.52 |
| February | 0.995322E+09 | 952388.44 | 0.00 | 568650.78 | 0.00 | 0.00 | 0.148101E+09 | 0.00 | 0.52 |
| March | 0.115721E+10 | 1535956.88 | 0.00 | 316009.20 | 261705.42 | 42209.60 | 0.133858E+09 | 0.00 | 0.52 |
| April | 0.893585E+09 | 3431106.97 | 0.00 | 717648.79 | 1838159.81 | 0.00 | 0.127617E+09 | 0.00 | 0.52 |
| May | 0.897997E+09 | 2142100.00 | 0.00 | 751439.25 | 0.00 | 0.00 | 0.145786E+09 | 0.00 | 0.52 |
| June | 0.715229E+09 | 25017702.79 | 0.00 | 736111.59 | 479293.98 | 0.00 | 78521061.91 | 0.00 | 0.52 |
| July | 0.669040E+09 | 98759081.41 | 0.00 | 575699.09 | 5810636.07 | 0.00 | 30598054.30 | 0.00 | 0.53 |
| August | 0.623630E+09 | 0.135248E+09 | 0.00 | 596637.07 | 4729805.23 | 0.00 | 34693064.51 | 0.00 | 0.53 |
| September | 0.719187E+09 | 53028264.89 | 0.00 | 857361.77 | 4930090.86 | 0.00 | 57594883.30 | 0.00 | 0.53 |
| October | 0.806494E+09 | 71797251.53 | 0.00 | 1095831.08 | 13471857.93 | 0.00 | 65618392.20 | 0.00 | 0.53 |
| November | 0.105699E+10 | 482435.58 | 0.00 | 1249998.20 | 560783.57 | 0.00 | 0.156432E+09 | 0.00 | 0.52 |
| December | 0.115835E+10 | 1371706.54 | 0.00 | 1073168.58 | 0.00 | 0.00 | 0.151534E+09 | 0.00 | 0.52 |
| Annual Sum or Average | 0.108466E+11 | 0.395133E+09 | 0.00 | 9408746.51 | 33401201.83 | 42209.60 | 0.128621E+10 | 0.00 | 0.52 |
| Minimum of Months | 0.623630E+09 | 482435.58 | 0.00 | 316009.20 | 0.00 | 0.00 | 30598054.30 | 0.00 | 0.52 |
| Maximum of Months | 0.115835E+10 | 0.135248E+09 | 0.00 | 1249998.20 | 13471857.93 | 42209.60 | 0.156432E+09 | 0.00 | 0.53 |
Report: MechanicalVentilationLoadsMonthly
For: G NE APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.613375E+09 | 1182833.90 | 0.00 | 8927.00 | 5780199.03 | 0.147096E+09 | 2405377.36 | 0.00 | 0.35 |
| February | 0.586490E+09 | 0.00 | 0.00 | 0.00 | 1827656.37 | 51423297.17 | 0.00 | 0.00 | 0.35 |
| March | 0.595936E+09 | 0.00 | 0.00 | 0.00 | 1616688.65 | 0.166700E+09 | 0.00 | 0.00 | 0.35 |
| April | 0.596058E+09 | 3086724.72 | 0.00 | 48988.15 | 2597818.05 | 11928206.41 | 10745664.39 | 0.00 | 0.35 |
| May | 0.607887E+09 | 1369648.85 | 0.00 | 154885.96 | 4750.18 | 0.00 | 46368036.36 | 0.00 | 0.35 |
| June | 0.335100E+09 | 14352380.25 | 0.00 | 624900.17 | 0.00 | 0.00 | 0.156232E+09 | 0.00 | 0.36 |
| July | 45613163.18 | 86606136.38 | 0.00 | 1342222.50 | 0.00 | 0.00 | 0.285675E+09 | 0.00 | 0.36 |
| August | 63559504.22 | 0.103627E+09 | 0.00 | 1057121.09 | 0.00 | 0.00 | 0.249134E+09 | 0.00 | 0.36 |
| September | 0.206232E+09 | 33806972.73 | 0.00 | 842646.20 | 11549.98 | 0.00 | 0.248162E+09 | 0.00 | 0.36 |
| October | 0.299363E+09 | 72890974.36 | 0.00 | 739466.70 | 114674.36 | 0.00 | 0.163474E+09 | 0.00 | 0.36 |
| November | 0.694864E+09 | 2475109.05 | 0.00 | 30.11 | 2354446.62 | 0.00 | 551965.57 | 0.00 | 0.35 |
| December | 0.699047E+09 | 1021747.02 | 0.00 | 836.38 | 4896022.34 | 31966116.26 | 564204.34 | 0.00 | 0.35 |
| Annual Sum or Average | 0.534352E+10 | 0.320419E+09 | 0.00 | 4820024.24 | 19203805.57 | 0.409113E+09 | 0.116331E+10 | 0.00 | 0.35 |
| Minimum of Months | 45613163.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
| Maximum of Months | 0.699047E+09 | 0.103627E+09 | 0.00 | 1342222.50 | 5780199.03 | 0.166700E+09 | 0.285675E+09 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: G N1 APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.773072E+09 | 1339138.89 | 0.00 | 21711.63 | 5634373.24 | 7206005.81 | 10807967.60 | 0.00 | 0.35 |
| February | 0.671223E+09 | 0.00 | 0.00 | 0.00 | 1749857.91 | 0.00 | 0.00 | 0.00 | 0.35 |
| March | 0.770067E+09 | 0.00 | 0.00 | 0.00 | 2266569.29 | 19231647.25 | 0.00 | 0.00 | 0.35 |
| April | 0.624491E+09 | 2616312.79 | 0.00 | 44065.01 | 3189374.66 | 0.00 | 21439455.12 | 0.00 | 0.35 |
| May | 0.588836E+09 | 1325190.09 | 0.00 | 215492.89 | 11002.61 | 0.00 | 0.100321E+09 | 0.00 | 0.36 |
| June | 0.227187E+09 | 12441023.13 | 0.00 | 844734.33 | 0.00 | 0.00 | 0.275804E+09 | 0.00 | 0.36 |
| July | 18659951.31 | 78064069.31 | 0.00 | 1478901.51 | 0.00 | 0.00 | 0.298061E+09 | 0.00 | 0.36 |
| August | 20635906.46 | 90761130.34 | 0.00 | 1234475.16 | 0.00 | 0.00 | 0.275025E+09 | 0.00 | 0.36 |
| September | 90566714.66 | 33540886.94 | 0.00 | 1198119.98 | 0.00 | 0.00 | 0.356865E+09 | 0.00 | 0.36 |
| October | 0.209927E+09 | 74524545.81 | 0.00 | 993715.76 | 107900.83 | 0.00 | 0.261733E+09 | 0.00 | 0.36 |
| November | 0.735441E+09 | 3105307.32 | 0.00 | 5136.62 | 1501032.52 | 0.00 | 5620302.39 | 0.00 | 0.35 |
| December | 0.765680E+09 | 790532.34 | 0.00 | 7565.37 | 4960384.72 | 0.00 | 3865386.30 | 0.00 | 0.35 |
| Annual Sum or Average | 0.549579E+10 | 0.298508E+09 | 0.00 | 6043918.28 | 19420495.78 | 26437653.06 | 0.160954E+10 | 0.00 | 0.35 |
| Minimum of Months | 18659951.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
| Maximum of Months | 0.773072E+09 | 90761130.34 | 0.00 | 1478901.51 | 5634373.24 | 19231647.25 | 0.356865E+09 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: G N2 APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.773200E+09 | 1339691.90 | 0.00 | 22084.92 | 5621857.92 | 7205987.15 | 11207097.30 | 0.00 | 0.35 |
| February | 0.671074E+09 | 0.00 | 0.00 | 0.00 | 1740468.67 | 0.00 | 0.00 | 0.00 | 0.35 |
| March | 0.770332E+09 | 0.00 | 0.00 | 0.00 | 2219324.06 | 19231552.10 | 0.00 | 0.00 | 0.35 |
| April | 0.625186E+09 | 2614615.71 | 0.00 | 41779.18 | 3153406.27 | 0.00 | 20311355.02 | 0.00 | 0.35 |
| May | 0.591989E+09 | 1327317.89 | 0.00 | 208118.20 | 10499.96 | 0.00 | 96381449.59 | 0.00 | 0.36 |
| June | 0.233633E+09 | 12459132.91 | 0.00 | 827887.41 | 0.00 | 0.00 | 0.269451E+09 | 0.00 | 0.36 |
| July | 19238311.88 | 78238388.49 | 0.00 | 1471102.97 | 0.00 | 0.00 | 0.298245E+09 | 0.00 | 0.36 |
| August | 20800139.67 | 91096232.82 | 0.00 | 1228785.13 | 0.00 | 0.00 | 0.275503E+09 | 0.00 | 0.36 |
| September | 94521337.72 | 33488947.02 | 0.00 | 1179346.83 | 0.00 | 0.00 | 0.353621E+09 | 0.00 | 0.36 |
| October | 0.211394E+09 | 74509334.93 | 0.00 | 990001.14 | 106511.02 | 0.00 | 0.260425E+09 | 0.00 | 0.36 |
| November | 0.735510E+09 | 3114954.07 | 0.00 | 4967.81 | 1485224.28 | 0.00 | 5109112.43 | 0.00 | 0.35 |
| December | 0.765518E+09 | 886131.21 | 0.00 | 8092.05 | 4822085.72 | 0.00 | 4166081.23 | 0.00 | 0.35 |
| Annual Sum or Average | 0.551240E+10 | 0.299075E+09 | 0.00 | 5982165.65 | 19159377.90 | 26437539.25 | 0.159442E+10 | 0.00 | 0.35 |
| Minimum of Months | 19238311.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
| Maximum of Months | 0.773200E+09 | 91096232.82 | 0.00 | 1471102.97 | 5621857.92 | 19231552.10 | 0.353621E+09 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: G S1 APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.537055E+09 | 5885508.09 | 0.00 | 1354483.92 | 0.00 | 0.00 | 0.366136E+09 | 0.00 | 0.35 |
| February | 0.598199E+09 | 1524139.90 | 0.00 | 642681.57 | 0.00 | 0.00 | 0.191295E+09 | 0.00 | 0.35 |
| March | 0.821790E+09 | 914375.14 | 0.00 | 154164.88 | 0.00 | 0.00 | 50330927.87 | 0.00 | 0.35 |
| April | 0.502903E+09 | 5292003.73 | 0.00 | 546244.84 | 523312.96 | 0.00 | 0.192659E+09 | 0.00 | 0.36 |
| May | 0.537075E+09 | 1783366.86 | 0.00 | 397452.39 | 6039.75 | 0.00 | 0.158109E+09 | 0.00 | 0.36 |
| June | 0.255075E+09 | 14087309.16 | 0.00 | 797489.70 | 0.00 | 0.00 | 0.248145E+09 | 0.00 | 0.36 |
| July | 18837281.98 | 85558175.45 | 0.00 | 1479866.43 | 0.00 | 0.00 | 0.295312E+09 | 0.00 | 0.36 |
| August | 8852099.46 | 0.113317E+09 | 0.00 | 1439903.34 | 0.00 | 0.00 | 0.258928E+09 | 0.00 | 0.36 |
| September | 19773765.17 | 45552754.56 | 0.00 | 2038861.94 | 0.00 | 0.00 | 0.377703E+09 | 0.00 | 0.36 |
| October | 52961681.29 | 86429561.21 | 0.00 | 2155028.56 | 0.00 | 0.00 | 0.399003E+09 | 0.00 | 0.36 |
| November | 0.263596E+09 | 4317118.45 | 0.00 | 2103438.03 | 0.00 | 0.00 | 0.544781E+09 | 0.00 | 0.35 |
| December | 0.446091E+09 | 4288513.93 | 0.00 | 1782823.26 | 0.00 | 0.00 | 0.444420E+09 | 0.00 | 0.35 |
| Annual Sum or Average | 0.406221E+10 | 0.368950E+09 | 0.00 | 14892438.85 | 529352.70 | 0.00 | 0.352682E+10 | 0.00 | 0.36 |
| Minimum of Months | 8852099.46 | 914375.14 | 0.00 | 154164.88 | 0.00 | 0.00 | 50330927.87 | 0.00 | 0.35 |
| Maximum of Months | 0.821790E+09 | 0.113317E+09 | 0.00 | 2155028.56 | 523312.96 | 0.00 | 0.544781E+09 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: G S2 APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.521341E+09 | 5909706.60 | 0.00 | 1448162.74 | 0.00 | 0.00 | 0.381282E+09 | 0.00 | 0.35 |
| February | 0.586861E+09 | 1526045.91 | 0.00 | 702059.38 | 0.00 | 0.00 | 0.206195E+09 | 0.00 | 0.35 |
| March | 0.818884E+09 | 985155.94 | 0.00 | 182308.55 | 0.00 | 0.00 | 58945031.93 | 0.00 | 0.35 |
| April | 0.486001E+09 | 5507654.37 | 0.00 | 617317.14 | 440134.94 | 0.00 | 0.211549E+09 | 0.00 | 0.36 |
| May | 0.516503E+09 | 1826920.64 | 0.00 | 464598.79 | 3893.16 | 0.00 | 0.182005E+09 | 0.00 | 0.36 |
| June | 0.216411E+09 | 14998129.47 | 0.00 | 901788.03 | 0.00 | 0.00 | 0.285012E+09 | 0.00 | 0.36 |
| July | 11961968.71 | 89607543.21 | 0.00 | 1606782.20 | 0.00 | 0.00 | 0.290426E+09 | 0.00 | 0.36 |
| August | 4608232.85 | 0.118624E+09 | 0.00 | 1588429.43 | 0.00 | 0.00 | 0.250146E+09 | 0.00 | 0.36 |
| September | 11869624.83 | 47242167.30 | 0.00 | 2201835.16 | 0.00 | 0.00 | 0.377386E+09 | 0.00 | 0.36 |
| October | 37874839.55 | 89615404.51 | 0.00 | 2312830.45 | 0.00 | 0.00 | 0.409253E+09 | 0.00 | 0.36 |
| November | 0.244494E+09 | 4325314.38 | 0.00 | 2234950.89 | 0.00 | 0.00 | 0.563094E+09 | 0.00 | 0.35 |
| December | 0.421387E+09 | 4294591.84 | 0.00 | 1895216.45 | 0.00 | 0.00 | 0.470043E+09 | 0.00 | 0.35 |
| Annual Sum or Average | 0.387820E+10 | 0.384463E+09 | 0.00 | 16156279.22 | 444028.11 | 0.00 | 0.368533E+10 | 0.00 | 0.36 |
| Minimum of Months | 4608232.85 | 985155.94 | 0.00 | 182308.55 | 0.00 | 0.00 | 58945031.93 | 0.00 | 0.35 |
| Maximum of Months | 0.818884E+09 | 0.118624E+09 | 0.00 | 2312830.45 | 440134.94 | 0.00 | 0.563094E+09 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: M SW APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.109514E+10 | 12049709.13 | 0.00 | 3490825.43 | 0.00 | 0.00 | 0.670481E+09 | 0.00 | 0.35 |
| February | 0.104329E+10 | 2880796.72 | 0.00 | 2680975.02 | 0.00 | 0.00 | 0.516634E+09 | 0.00 | 0.35 |
| March | 0.131146E+10 | 2793171.75 | 0.00 | 2007400.63 | 0.00 | 28013862.62 | 0.440987E+09 | 0.00 | 0.35 |
| April | 0.534702E+09 | 14772637.78 | 0.00 | 4149501.05 | 192135.87 | 0.00 | 0.831270E+09 | 0.00 | 0.36 |
| May | 0.618959E+09 | 3658630.89 | 0.00 | 3585014.19 | 0.00 | 0.00 | 0.764755E+09 | 0.00 | 0.36 |
| June | 0.107971E+09 | 40553392.43 | 0.00 | 4541100.21 | 0.00 | 0.00 | 0.804466E+09 | 0.00 | 0.36 |
| July | 5140774.16 | 0.201031E+09 | 0.00 | 4542101.16 | 0.00 | 0.00 | 0.508942E+09 | 0.00 | 0.36 |
| August | 8894196.06 | 0.259257E+09 | 0.00 | 3835128.67 | 0.00 | 0.00 | 0.445148E+09 | 0.00 | 0.36 |
| September | 40992613.35 | 98817835.42 | 0.00 | 5348038.52 | 0.00 | 0.00 | 0.700155E+09 | 0.00 | 0.36 |
| October | 0.253638E+09 | 0.173207E+09 | 0.00 | 4382586.81 | 0.00 | 0.00 | 0.618118E+09 | 0.00 | 0.36 |
| November | 0.707795E+09 | 8541346.60 | 0.00 | 4479792.65 | 0.00 | 0.00 | 0.853625E+09 | 0.00 | 0.35 |
| December | 0.989520E+09 | 8347903.33 | 0.00 | 4127227.89 | 0.00 | 0.00 | 0.732230E+09 | 0.00 | 0.35 |
| Annual Sum or Average | 0.671750E+10 | 0.825911E+09 | 0.00 | 47169692.23 | 192135.87 | 28013862.62 | 0.788681E+10 | 0.00 | 0.36 |
| Minimum of Months | 5140774.16 | 2793171.75 | 0.00 | 2007400.63 | 0.00 | 0.00 | 0.440987E+09 | 0.00 | 0.35 |
| Maximum of Months | 0.131146E+10 | 0.259257E+09 | 0.00 | 5348038.52 | 192135.87 | 28013862.62 | 0.853625E+09 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: M NW APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.141059E+10 | 7074409.90 | 0.00 | 256060.19 | 5068630.97 | 0.108060E+09 | 82433530.07 | 0.00 | 0.35 |
| February | 0.140810E+10 | 2404976.01 | 0.00 | 77969.66 | 146301.72 | 0.00 | 36204464.27 | 0.00 | 0.35 |
| March | 0.154502E+10 | 786302.64 | 0.00 | 344027.86 | 1029845.18 | 42174786.11 | 0.111961E+09 | 0.00 | 0.35 |
| April | 0.791621E+09 | 10315817.97 | 0.00 | 2342733.68 | 2088914.81 | 3453369.85 | 0.578682E+09 | 0.00 | 0.36 |
| May | 0.627209E+09 | 2939009.04 | 0.00 | 3269265.65 | 0.00 | 0.00 | 0.761276E+09 | 0.00 | 0.36 |
| June | 99810544.86 | 37465954.07 | 0.00 | 4755184.58 | 0.00 | 0.00 | 0.807670E+09 | 0.00 | 0.36 |
| July | 4993271.38 | 0.189157E+09 | 0.00 | 4642553.66 | 0.00 | 0.00 | 0.509274E+09 | 0.00 | 0.36 |
| August | 16321652.55 | 0.222999E+09 | 0.00 | 3522930.15 | 0.00 | 0.00 | 0.469697E+09 | 0.00 | 0.36 |
| September | 0.114720E+09 | 77049564.27 | 0.00 | 4041779.74 | 0.00 | 0.00 | 0.693424E+09 | 0.00 | 0.36 |
| October | 0.417052E+09 | 0.151911E+09 | 0.00 | 2515274.02 | 242825.98 | 0.00 | 0.479661E+09 | 0.00 | 0.36 |
| November | 0.130917E+10 | 7927287.91 | 0.00 | 354885.77 | 742393.94 | 0.00 | 0.188438E+09 | 0.00 | 0.35 |
| December | 0.150083E+10 | 4765107.78 | 0.00 | 195474.49 | 3902065.97 | 0.00 | 67162114.55 | 0.00 | 0.35 |
| Annual Sum or Average | 0.924542E+10 | 0.714795E+09 | 0.00 | 26318139.46 | 13220978.57 | 0.153688E+09 | 0.478588E+10 | 0.00 | 0.36 |
| Minimum of Months | 4993271.38 | 786302.64 | 0.00 | 77969.66 | 0.00 | 0.00 | 36204464.27 | 0.00 | 0.35 |
| Maximum of Months | 0.154502E+10 | 0.222999E+09 | 0.00 | 4755184.58 | 5068630.97 | 0.108060E+09 | 0.807670E+09 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: M SE APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.106855E+10 | 12146964.50 | 0.00 | 3613819.43 | 0.00 | 0.00 | 0.702982E+09 | 0.00 | 0.35 |
| February | 0.104780E+10 | 2889382.95 | 0.00 | 2627775.06 | 0.00 | 0.00 | 0.512299E+09 | 0.00 | 0.35 |
| March | 0.130903E+10 | 3386941.48 | 0.00 | 1867437.21 | 0.00 | 27698881.06 | 0.448433E+09 | 0.00 | 0.35 |
| April | 0.542725E+09 | 16544397.52 | 0.00 | 3917043.17 | 0.00 | 0.00 | 0.833952E+09 | 0.00 | 0.36 |
| May | 0.625303E+09 | 4197880.65 | 0.00 | 3241423.97 | 0.00 | 0.00 | 0.767645E+09 | 0.00 | 0.36 |
| June | 0.115826E+09 | 45840601.84 | 0.00 | 4204037.64 | 0.00 | 0.00 | 0.819486E+09 | 0.00 | 0.36 |
| July | 10517097.22 | 0.213781E+09 | 0.00 | 4309843.69 | 0.00 | 0.00 | 0.531803E+09 | 0.00 | 0.36 |
| August | 8392297.32 | 0.278278E+09 | 0.00 | 3846446.71 | 0.00 | 0.00 | 0.470575E+09 | 0.00 | 0.36 |
| September | 62391306.70 | 0.102600E+09 | 0.00 | 4950029.11 | 0.00 | 0.00 | 0.700335E+09 | 0.00 | 0.36 |
| October | 0.243294E+09 | 0.172050E+09 | 0.00 | 4408228.43 | 0.00 | 0.00 | 0.635128E+09 | 0.00 | 0.36 |
| November | 0.686377E+09 | 8575774.60 | 0.00 | 4445100.09 | 0.00 | 0.00 | 0.880771E+09 | 0.00 | 0.35 |
| December | 0.974506E+09 | 8408477.75 | 0.00 | 4146667.01 | 0.00 | 0.00 | 0.751114E+09 | 0.00 | 0.35 |
| Annual Sum or Average | 0.669472E+10 | 0.868699E+09 | 0.00 | 45577851.53 | 0.00 | 27698881.06 | 0.805452E+10 | 0.00 | 0.36 |
| Minimum of Months | 8392297.32 | 2889382.95 | 0.00 | 1867437.21 | 0.00 | 0.00 | 0.448433E+09 | 0.00 | 0.35 |
| Maximum of Months | 0.130903E+10 | 0.278278E+09 | 0.00 | 4950029.11 | 0.00 | 27698881.06 | 0.880771E+09 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: M NE APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.141709E+10 | 7798792.90 | 0.00 | 277972.13 | 4011411.53 | 0.100799E+09 | 91376910.10 | 0.00 | 0.35 |
| February | 0.143162E+10 | 2251823.32 | 0.00 | 25450.89 | 252168.01 | 0.00 | 7977623.55 | 0.00 | 0.35 |
| March | 0.151945E+10 | 1811231.03 | 0.00 | 303310.37 | 123.53 | 60406602.17 | 0.123329E+09 | 0.00 | 0.35 |
| April | 0.818548E+09 | 13085991.55 | 0.00 | 2011650.62 | 469444.99 | 578421.51 | 0.565638E+09 | 0.00 | 0.36 |
| May | 0.638901E+09 | 3315264.25 | 0.00 | 2944549.01 | 0.00 | 0.00 | 0.757834E+09 | 0.00 | 0.36 |
| June | 0.111266E+09 | 42736696.11 | 0.00 | 4388865.03 | 0.00 | 0.00 | 0.818484E+09 | 0.00 | 0.36 |
| July | 11333510.60 | 0.202471E+09 | 0.00 | 4342636.26 | 0.00 | 0.00 | 0.531958E+09 | 0.00 | 0.36 |
| August | 17470905.63 | 0.244448E+09 | 0.00 | 3501686.02 | 0.00 | 0.00 | 0.496570E+09 | 0.00 | 0.36 |
| September | 0.126937E+09 | 81918613.09 | 0.00 | 3494061.95 | 0.00 | 0.00 | 0.707665E+09 | 0.00 | 0.36 |
| October | 0.419211E+09 | 0.151114E+09 | 0.00 | 2373588.60 | 104742.39 | 0.00 | 0.487292E+09 | 0.00 | 0.36 |
| November | 0.138181E+10 | 8192625.64 | 0.00 | 163118.87 | 347201.79 | 0.00 | 0.111923E+09 | 0.00 | 0.35 |
| December | 0.151118E+10 | 5313261.19 | 0.00 | 178525.09 | 2529402.46 | 0.00 | 57927123.28 | 0.00 | 0.35 |
| Annual Sum or Average | 0.940481E+10 | 0.764458E+09 | 0.00 | 24005414.85 | 7714494.69 | 0.161784E+09 | 0.475797E+10 | 0.00 | 0.36 |
| Minimum of Months | 11333510.60 | 1811231.03 | 0.00 | 25450.89 | 0.00 | 0.00 | 7977623.55 | 0.00 | 0.35 |
| Maximum of Months | 0.151945E+10 | 0.244448E+09 | 0.00 | 4388865.03 | 4011411.53 | 0.100799E+09 | 0.818484E+09 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: M N1 APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.142710E+10 | 7719805.61 | 0.00 | 619992.55 | 4328946.45 | 0.00 | 0.247955E+09 | 0.00 | 0.35 |
| February | 0.144546E+10 | 2491220.18 | 0.00 | 180292.05 | 69332.41 | 0.00 | 0.103226E+09 | 0.00 | 0.35 |
| March | 0.156074E+10 | 1011714.70 | 0.00 | 442574.01 | 661808.85 | 0.00 | 0.230423E+09 | 0.00 | 0.35 |
| April | 0.514862E+09 | 10107148.15 | 0.00 | 2492239.90 | 2128955.60 | 0.00 | 0.899786E+09 | 0.00 | 0.36 |
| May | 0.319480E+09 | 3012615.06 | 0.00 | 3599941.19 | 0.00 | 0.00 | 0.110223E+10 | 0.00 | 0.36 |
| June | 13957718.56 | 34876104.91 | 0.00 | 4685485.06 | 0.00 | 0.00 | 0.904571E+09 | 0.00 | 0.36 |
| July | 725746.48 | 0.177896E+09 | 0.00 | 4308050.80 | 0.00 | 0.00 | 0.531767E+09 | 0.00 | 0.36 |
| August | 4323384.86 | 0.210056E+09 | 0.00 | 3565002.21 | 0.00 | 0.00 | 0.487614E+09 | 0.00 | 0.36 |
| September | 28106246.37 | 77229838.44 | 0.00 | 3922476.73 | 0.00 | 0.00 | 0.783149E+09 | 0.00 | 0.36 |
| October | 0.259205E+09 | 0.153443E+09 | 0.00 | 2813238.30 | 133862.68 | 0.00 | 0.659779E+09 | 0.00 | 0.36 |
| November | 0.110042E+10 | 8521169.69 | 0.00 | 960410.23 | 0.00 | 0.00 | 0.474516E+09 | 0.00 | 0.35 |
| December | 0.145547E+10 | 5700587.09 | 0.00 | 483065.09 | 1761998.43 | 0.00 | 0.211135E+09 | 0.00 | 0.35 |
| Annual Sum or Average | 0.812985E+10 | 0.692065E+09 | 0.00 | 28072768.12 | 9084904.42 | 0.00 | 0.663615E+10 | 0.00 | 0.36 |
| Minimum of Months | 725746.48 | 1011714.70 | 0.00 | 180292.05 | 0.00 | 0.00 | 0.103226E+09 | 0.00 | 0.35 |
| Maximum of Months | 0.156074E+10 | 0.210056E+09 | 0.00 | 4685485.06 | 4328946.45 | 0.00 | 0.110223E+10 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: M N2 APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.142385E+10 | 7812655.57 | 0.00 | 632238.75 | 4215371.02 | 0.00 | 0.252637E+09 | 0.00 | 0.35 |
| February | 0.144949E+10 | 2491510.27 | 0.00 | 172161.55 | 67866.55 | 0.00 | 98729504.11 | 0.00 | 0.35 |
| March | 0.155498E+10 | 1078745.55 | 0.00 | 454513.28 | 602005.47 | 0.00 | 0.235749E+09 | 0.00 | 0.35 |
| April | 0.514022E+09 | 10161516.16 | 0.00 | 2477787.18 | 2092680.31 | 0.00 | 0.901147E+09 | 0.00 | 0.36 |
| May | 0.320764E+09 | 3022490.11 | 0.00 | 3587081.66 | 0.00 | 0.00 | 0.110127E+10 | 0.00 | 0.36 |
| June | 15200410.03 | 35023987.83 | 0.00 | 4666777.88 | 0.00 | 0.00 | 0.904353E+09 | 0.00 | 0.36 |
| July | 812314.35 | 0.178367E+09 | 0.00 | 4290901.87 | 0.00 | 0.00 | 0.532955E+09 | 0.00 | 0.36 |
| August | 4326299.41 | 0.210819E+09 | 0.00 | 3555724.92 | 0.00 | 0.00 | 0.488813E+09 | 0.00 | 0.36 |
| September | 29141321.76 | 77354677.71 | 0.00 | 3893793.12 | 0.00 | 0.00 | 0.783307E+09 | 0.00 | 0.36 |
| October | 0.258599E+09 | 0.153424E+09 | 0.00 | 2813421.06 | 131007.92 | 0.00 | 0.660685E+09 | 0.00 | 0.36 |
| November | 0.110173E+10 | 8522880.34 | 0.00 | 937881.35 | 0.00 | 0.00 | 0.473246E+09 | 0.00 | 0.35 |
| December | 0.145524E+10 | 5944477.21 | 0.00 | 484445.29 | 1490516.72 | 0.00 | 0.211585E+09 | 0.00 | 0.35 |
| Annual Sum or Average | 0.812815E+10 | 0.694022E+09 | 0.00 | 27966727.92 | 8599447.99 | 0.00 | 0.664447E+10 | 0.00 | 0.36 |
| Minimum of Months | 812314.35 | 1078745.55 | 0.00 | 172161.55 | 0.00 | 0.00 | 98729504.11 | 0.00 | 0.35 |
| Maximum of Months | 0.155498E+10 | 0.210819E+09 | 0.00 | 4666777.88 | 4215371.02 | 0.00 | 0.110127E+10 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: M S1 APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.728238E+09 | 12246652.39 | 0.00 | 5257935.28 | 0.00 | 0.00 | 0.110023E+10 | 0.00 | 0.35 |
| February | 0.735668E+09 | 2986906.42 | 0.00 | 3821296.96 | 0.00 | 0.00 | 0.900197E+09 | 0.00 | 0.36 |
| March | 0.960945E+09 | 3194231.60 | 0.00 | 3036740.19 | 0.00 | 0.00 | 0.900431E+09 | 0.00 | 0.36 |
| April | 0.243871E+09 | 15077421.17 | 0.00 | 4701697.98 | 42156.13 | 0.00 | 0.114623E+10 | 0.00 | 0.36 |
| May | 0.318608E+09 | 3890411.45 | 0.00 | 3873722.20 | 0.00 | 0.00 | 0.109658E+10 | 0.00 | 0.36 |
| June | 25961656.47 | 38202125.15 | 0.00 | 4454678.04 | 0.00 | 0.00 | 0.897713E+09 | 0.00 | 0.36 |
| July | 1194344.72 | 0.192014E+09 | 0.00 | 4261711.39 | 0.00 | 0.00 | 0.529954E+09 | 0.00 | 0.36 |
| August | 581724.83 | 0.251790E+09 | 0.00 | 3914562.73 | 0.00 | 0.00 | 0.452455E+09 | 0.00 | 0.36 |
| September | 1298045.36 | 0.100111E+09 | 0.00 | 5472174.44 | 0.00 | 0.00 | 0.730837E+09 | 0.00 | 0.36 |
| October | 76451462.87 | 0.177076E+09 | 0.00 | 5099146.05 | 0.00 | 0.00 | 0.804487E+09 | 0.00 | 0.36 |
| November | 0.351300E+09 | 8627741.99 | 0.00 | 6253856.83 | 0.00 | 0.00 | 0.123770E+10 | 0.00 | 0.35 |
| December | 0.604148E+09 | 8525578.74 | 0.00 | 6112669.56 | 0.00 | 0.00 | 0.117203E+10 | 0.00 | 0.35 |
| Annual Sum or Average | 0.404827E+10 | 0.813741E+09 | 0.00 | 56260191.65 | 42156.13 | 0.00 | 0.109688E+11 | 0.00 | 0.36 |
| Minimum of Months | 581724.83 | 2986906.42 | 0.00 | 3036740.19 | 0.00 | 0.00 | 0.452455E+09 | 0.00 | 0.35 |
| Maximum of Months | 0.960945E+09 | 0.251790E+09 | 0.00 | 6253856.83 | 42156.13 | 0.00 | 0.123770E+10 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: M S2 APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.727148E+09 | 12250176.85 | 0.00 | 5276394.99 | 0.00 | 0.00 | 0.110186E+10 | 0.00 | 0.35 |
| February | 0.738713E+09 | 2987242.93 | 0.00 | 3819152.03 | 0.00 | 0.00 | 0.896932E+09 | 0.00 | 0.36 |
| March | 0.959227E+09 | 3218445.11 | 0.00 | 3046729.13 | 0.00 | 0.00 | 0.901940E+09 | 0.00 | 0.36 |
| April | 0.243937E+09 | 15166500.82 | 0.00 | 4693966.32 | 6606.37 | 0.00 | 0.114661E+10 | 0.00 | 0.36 |
| May | 0.320601E+09 | 3906258.97 | 0.00 | 3860255.91 | 0.00 | 0.00 | 0.109492E+10 | 0.00 | 0.36 |
| June | 25657867.13 | 38356334.95 | 0.00 | 4435947.79 | 0.00 | 0.00 | 0.899081E+09 | 0.00 | 0.36 |
| July | 1232817.79 | 0.192453E+09 | 0.00 | 4247060.62 | 0.00 | 0.00 | 0.531175E+09 | 0.00 | 0.36 |
| August | 581896.25 | 0.252423E+09 | 0.00 | 3904158.49 | 0.00 | 0.00 | 0.453545E+09 | 0.00 | 0.36 |
| September | 1360948.90 | 0.100224E+09 | 0.00 | 5449783.02 | 0.00 | 0.00 | 0.731784E+09 | 0.00 | 0.36 |
| October | 76962926.81 | 0.177037E+09 | 0.00 | 5094450.07 | 0.00 | 0.00 | 0.804209E+09 | 0.00 | 0.36 |
| November | 0.353727E+09 | 8629246.14 | 0.00 | 6250636.70 | 0.00 | 0.00 | 0.123538E+10 | 0.00 | 0.35 |
| December | 0.605243E+09 | 8527669.81 | 0.00 | 6118355.28 | 0.00 | 0.00 | 0.117091E+10 | 0.00 | 0.35 |
| Annual Sum or Average | 0.405439E+10 | 0.815179E+09 | 0.00 | 56196890.35 | 6606.37 | 0.00 | 0.109683E+11 | 0.00 | 0.36 |
| Minimum of Months | 581896.25 | 2987242.93 | 0.00 | 3046729.13 | 0.00 | 0.00 | 0.453545E+09 | 0.00 | 0.35 |
| Maximum of Months | 0.959227E+09 | 0.252423E+09 | 0.00 | 6250636.70 | 6606.37 | 0.00 | 0.123538E+10 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: T SW APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.415888E+09 | 5722014.02 | 0.00 | 981097.27 | 161886.20 | 0.236941E+09 | 0.141373E+09 | 0.00 | 0.35 |
| February | 0.374002E+09 | 1371344.85 | 0.00 | 793990.06 | 2221.85 | 0.203488E+09 | 0.100419E+09 | 0.00 | 0.35 |
| March | 0.428848E+09 | 1174598.60 | 0.00 | 802894.30 | 23142.84 | 0.262326E+09 | 99018413.60 | 0.00 | 0.35 |
| April | 0.419361E+09 | 7092444.95 | 0.00 | 1426149.59 | 0.00 | 42642337.87 | 0.149896E+09 | 0.00 | 0.35 |
| May | 0.430991E+09 | 1662492.56 | 0.00 | 1186259.85 | 3308.11 | 41383280.61 | 0.138452E+09 | 0.00 | 0.35 |
| June | 0.296385E+09 | 20616601.18 | 0.00 | 1386343.40 | 0.00 | 0.00 | 0.153251E+09 | 0.00 | 0.36 |
| July | 0.157907E+09 | 0.103026E+09 | 0.00 | 1293598.36 | 0.00 | 0.00 | 0.155719E+09 | 0.00 | 0.36 |
| August | 0.155192E+09 | 0.130745E+09 | 0.00 | 883973.10 | 0.00 | 0.00 | 0.134506E+09 | 0.00 | 0.36 |
| September | 0.237397E+09 | 45990560.42 | 0.00 | 1682408.41 | 140483.52 | 0.00 | 0.157575E+09 | 0.00 | 0.36 |
| October | 0.257597E+09 | 81114027.54 | 0.00 | 1335166.88 | 309277.97 | 15566997.49 | 0.139511E+09 | 0.00 | 0.36 |
| November | 0.426278E+09 | 4182304.86 | 0.00 | 1049742.75 | 150409.79 | 0.122706E+09 | 0.140810E+09 | 0.00 | 0.35 |
| December | 0.417575E+09 | 4041291.30 | 0.00 | 1116824.08 | 19461.49 | 0.223618E+09 | 0.118218E+09 | 0.00 | 0.35 |
| Annual Sum or Average | 0.401742E+10 | 0.406738E+09 | 0.00 | 13938448.04 | 810191.77 | 0.114867E+10 | 0.162875E+10 | 0.00 | 0.35 |
| Minimum of Months | 0.155192E+09 | 1174598.60 | 0.00 | 793990.06 | 0.00 | 0.00 | 99018413.60 | 0.00 | 0.35 |
| Maximum of Months | 0.430991E+09 | 0.130745E+09 | 0.00 | 1682408.41 | 309277.97 | 0.262326E+09 | 0.157575E+09 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: T NW APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.329964E+09 | 3897648.06 | 0.00 | 47701.99 | 2493880.76 | 0.390184E+09 | 7219639.74 | 0.00 | 0.35 |
| February | 0.319846E+09 | 807561.92 | 0.00 | 10250.89 | 913971.62 | 0.313067E+09 | 2202612.91 | 0.00 | 0.35 |
| March | 0.408828E+09 | 330910.16 | 0.00 | 157862.27 | 982111.61 | 0.331291E+09 | 26789374.15 | 0.00 | 0.35 |
| April | 0.440725E+09 | 4847678.79 | 0.00 | 748803.73 | 834216.87 | 57584156.94 | 0.104204E+09 | 0.00 | 0.35 |
| May | 0.439639E+09 | 1349076.31 | 0.00 | 1010479.79 | 2759.46 | 36838757.02 | 0.135583E+09 | 0.00 | 0.35 |
| June | 0.286635E+09 | 18981171.82 | 0.00 | 1449608.14 | 0.00 | 0.00 | 0.162866E+09 | 0.00 | 0.36 |
| July | 0.155074E+09 | 96702171.12 | 0.00 | 1416216.62 | 0.00 | 0.00 | 0.157043E+09 | 0.00 | 0.36 |
| August | 0.172474E+09 | 0.111796E+09 | 0.00 | 809438.12 | 0.00 | 0.00 | 0.123481E+09 | 0.00 | 0.36 |
| September | 0.276271E+09 | 34558091.36 | 0.00 | 1178305.48 | 222962.84 | 0.00 | 0.132327E+09 | 0.00 | 0.36 |
| October | 0.286915E+09 | 70437050.07 | 0.00 | 636361.62 | 2763424.85 | 38127032.92 | 84818684.75 | 0.00 | 0.36 |
| November | 0.391815E+09 | 3535863.38 | 0.00 | 34660.40 | 1578536.99 | 0.231723E+09 | 7069747.37 | 0.00 | 0.35 |
| December | 0.317684E+09 | 1721994.80 | 12363.64 | 53755.40 | 4492007.78 | 0.370898E+09 | 6845473.20 | 80.34 | 0.35 |
| Annual Sum or Average | 0.382587E+10 | 0.348965E+09 | 12363.64 | 7553444.44 | 14283872.79 | 0.176971E+10 | 0.950449E+09 | 80.34 | 0.35 |
| Minimum of Months | 0.155074E+09 | 330910.16 | 0.00 | 10250.89 | 0.00 | 0.00 | 2202612.91 | 0.00 | 0.35 |
| Maximum of Months | 0.440725E+09 | 0.111796E+09 | 12363.64 | 1449608.14 | 4492007.78 | 0.390184E+09 | 0.162866E+09 | 80.34 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: T SE APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.421043E+09 | 5835150.71 | 0.00 | 918686.65 | 105002.37 | 0.232545E+09 | 0.144743E+09 | 0.00 | 0.35 |
| February | 0.374724E+09 | 1382250.66 | 0.00 | 662569.99 | 0.00 | 0.205558E+09 | 0.100085E+09 | 0.00 | 0.35 |
| March | 0.444332E+09 | 1521296.09 | 0.00 | 652168.69 | 0.00 | 0.259645E+09 | 91205383.59 | 0.00 | 0.35 |
| April | 0.439002E+09 | 8124804.57 | 0.00 | 1155628.07 | 0.00 | 42461164.40 | 0.137029E+09 | 0.00 | 0.35 |
| May | 0.452474E+09 | 1920168.20 | 0.00 | 894350.18 | 0.00 | 43098890.25 | 0.119352E+09 | 0.00 | 0.35 |
| June | 0.321495E+09 | 23922604.20 | 0.00 | 1108183.21 | 0.00 | 0.00 | 0.136067E+09 | 0.00 | 0.36 |
| July | 0.176619E+09 | 0.110757E+09 | 0.00 | 1234061.75 | 0.00 | 0.00 | 0.150301E+09 | 0.00 | 0.36 |
| August | 0.167533E+09 | 0.142597E+09 | 0.00 | 874706.09 | 0.00 | 0.00 | 0.135309E+09 | 0.00 | 0.36 |
| September | 0.251534E+09 | 48542746.37 | 0.00 | 1418350.78 | 135928.41 | 0.00 | 0.152140E+09 | 0.00 | 0.36 |
| October | 0.265757E+09 | 81029240.34 | 0.00 | 1233869.75 | 129768.89 | 16838836.40 | 0.134841E+09 | 0.00 | 0.36 |
| November | 0.446040E+09 | 4207665.78 | 0.00 | 874498.02 | 131844.00 | 0.121110E+09 | 0.126096E+09 | 0.00 | 0.35 |
| December | 0.426657E+09 | 4094155.82 | 0.00 | 1000816.99 | 0.00 | 0.220530E+09 | 0.115407E+09 | 0.00 | 0.35 |
| Annual Sum or Average | 0.418721E+10 | 0.433934E+09 | 0.00 | 12027890.16 | 502543.67 | 0.114179E+10 | 0.154257E+10 | 0.00 | 0.35 |
| Minimum of Months | 0.167533E+09 | 1382250.66 | 0.00 | 652168.69 | 0.00 | 0.00 | 91205383.59 | 0.00 | 0.35 |
| Maximum of Months | 0.452474E+09 | 0.142597E+09 | 0.00 | 1418350.78 | 135928.41 | 0.259645E+09 | 0.152140E+09 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: T NE APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.345550E+09 | 4675370.75 | 0.00 | 39480.85 | 1073757.63 | 0.374332E+09 | 6936315.46 | 0.00 | 0.35 |
| February | 0.316574E+09 | 1084556.03 | 0.00 | 2937.04 | 278980.98 | 0.314810E+09 | 758547.29 | 0.00 | 0.35 |
| March | 0.423613E+09 | 694222.60 | 0.00 | 77433.12 | 81610.84 | 0.331736E+09 | 13562884.61 | 0.00 | 0.35 |
| April | 0.474127E+09 | 6401465.79 | 0.00 | 482647.13 | 0.00 | 56727714.65 | 75368575.35 | 0.00 | 0.35 |
| May | 0.462572E+09 | 1543957.08 | 0.00 | 734760.05 | 0.00 | 42305539.75 | 0.111169E+09 | 0.00 | 0.35 |
| June | 0.307729E+09 | 22349740.47 | 0.00 | 1172538.22 | 0.00 | 0.00 | 0.150294E+09 | 0.00 | 0.36 |
| July | 0.171832E+09 | 0.104838E+09 | 0.00 | 1272461.88 | 0.00 | 0.00 | 0.153490E+09 | 0.00 | 0.36 |
| August | 0.188556E+09 | 0.125127E+09 | 0.00 | 776498.31 | 0.00 | 0.00 | 0.120461E+09 | 0.00 | 0.36 |
| September | 0.301780E+09 | 37525083.47 | 0.00 | 824052.69 | 153606.85 | 0.00 | 0.113358E+09 | 0.00 | 0.36 |
| October | 0.309922E+09 | 71794961.02 | 0.00 | 496383.29 | 499469.12 | 34666153.89 | 68469548.64 | 0.00 | 0.36 |
| November | 0.396947E+09 | 3903243.27 | 0.00 | 12864.23 | 646346.14 | 0.226615E+09 | 2527648.56 | 0.00 | 0.35 |
| December | 0.324311E+09 | 2646531.19 | 0.00 | 30322.22 | 1711451.12 | 0.363659E+09 | 3945746.57 | 0.00 | 0.35 |
| Annual Sum or Average | 0.402351E+10 | 0.382584E+09 | 0.00 | 5922379.04 | 4445222.68 | 0.174485E+10 | 0.820341E+09 | 0.00 | 0.35 |
| Minimum of Months | 0.171832E+09 | 694222.60 | 0.00 | 2937.04 | 0.00 | 0.00 | 758547.29 | 0.00 | 0.35 |
| Maximum of Months | 0.474127E+09 | 0.125127E+09 | 0.00 | 1272461.88 | 1711451.12 | 0.374332E+09 | 0.153490E+09 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: T N1 APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.429326E+09 | 3917204.71 | 0.00 | 36382.49 | 2314421.86 | 0.304320E+09 | 8593746.26 | 0.00 | 0.35 |
| February | 0.458095E+09 | 720952.02 | 0.00 | 766.83 | 972728.07 | 0.186887E+09 | 65521.53 | 0.00 | 0.35 |
| March | 0.546293E+09 | 258578.73 | 0.00 | 39462.72 | 868845.68 | 0.225507E+09 | 11752717.90 | 0.00 | 0.35 |
| April | 0.523789E+09 | 4758746.33 | 0.00 | 373695.92 | 727386.54 | 17618877.95 | 87226836.71 | 0.00 | 0.35 |
| May | 0.490105E+09 | 1399102.39 | 0.00 | 624186.36 | 312.77 | 10424701.23 | 0.142800E+09 | 0.00 | 0.35 |
| June | 0.261789E+09 | 18068017.70 | 0.00 | 1194796.17 | 0.00 | 0.00 | 0.210804E+09 | 0.00 | 0.36 |
| July | 95594118.36 | 93017912.85 | 0.00 | 1348042.21 | 0.00 | 0.00 | 0.227450E+09 | 0.00 | 0.36 |
| August | 0.122345E+09 | 0.107622E+09 | 0.00 | 879101.82 | 0.00 | 0.00 | 0.185611E+09 | 0.00 | 0.36 |
| September | 0.264898E+09 | 34465400.61 | 0.00 | 892586.23 | 139790.76 | 0.00 | 0.165940E+09 | 0.00 | 0.36 |
| October | 0.336626E+09 | 71773328.52 | 0.00 | 535927.31 | 1919421.80 | 59389.94 | 92554807.06 | 0.00 | 0.36 |
| November | 0.502910E+09 | 3394434.46 | 0.00 | 5861.56 | 1604206.31 | 0.140315E+09 | 2101508.71 | 0.00 | 0.35 |
| December | 0.424510E+09 | 1811718.30 | 0.00 | 23098.94 | 3950394.11 | 0.278768E+09 | 4409621.11 | 0.00 | 0.35 |
| Annual Sum or Average | 0.445628E+10 | 0.341207E+09 | 0.00 | 5953908.56 | 12497507.90 | 0.116390E+10 | 0.113931E+10 | 0.00 | 0.35 |
| Minimum of Months | 95594118.36 | 258578.73 | 0.00 | 766.83 | 0.00 | 0.00 | 65521.53 | 0.00 | 0.35 |
| Maximum of Months | 0.546293E+09 | 0.107622E+09 | 0.00 | 1348042.21 | 3950394.11 | 0.304320E+09 | 0.227450E+09 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: T N2 APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.430954E+09 | 4117899.06 | 0.00 | 36579.96 | 2060805.44 | 0.303070E+09 | 8409789.08 | 0.00 | 0.35 |
| February | 0.456032E+09 | 720772.31 | 0.00 | 852.00 | 952705.08 | 0.188773E+09 | 77287.69 | 0.00 | 0.35 |
| March | 0.545963E+09 | 268787.37 | 0.00 | 39466.10 | 812493.66 | 0.226881E+09 | 10931713.28 | 0.00 | 0.35 |
| April | 0.522954E+09 | 4980387.98 | 0.00 | 372809.90 | 536839.40 | 18039343.05 | 87287522.15 | 0.00 | 0.35 |
| May | 0.491407E+09 | 1410528.81 | 0.00 | 619414.17 | 0.00 | 10663561.30 | 0.141033E+09 | 0.00 | 0.35 |
| June | 0.264005E+09 | 18244690.78 | 0.00 | 1182326.90 | 0.00 | 0.00 | 0.208864E+09 | 0.00 | 0.36 |
| July | 97686170.00 | 93485238.06 | 0.00 | 1332216.32 | 0.00 | 0.00 | 0.226338E+09 | 0.00 | 0.36 |
| August | 0.124495E+09 | 0.108399E+09 | 0.00 | 867234.52 | 0.00 | 0.00 | 0.184409E+09 | 0.00 | 0.36 |
| September | 0.269118E+09 | 34630912.55 | 0.00 | 875826.51 | 140097.35 | 0.00 | 0.161654E+09 | 0.00 | 0.36 |
| October | 0.338474E+09 | 71947781.51 | 0.00 | 530918.91 | 1715574.19 | 59390.31 | 90607174.56 | 0.00 | 0.36 |
| November | 0.501379E+09 | 3496705.33 | 0.00 | 5975.83 | 1449977.31 | 0.141323E+09 | 2194244.25 | 0.00 | 0.35 |
| December | 0.423921E+09 | 1904267.81 | 0.00 | 23037.59 | 3726815.41 | 0.279328E+09 | 4344541.16 | 0.00 | 0.35 |
| Annual Sum or Average | 0.446639E+10 | 0.343607E+09 | 0.00 | 5886658.70 | 11395307.85 | 0.116814E+10 | 0.112615E+10 | 0.00 | 0.35 |
| Minimum of Months | 97686170.00 | 268787.37 | 0.00 | 852.00 | 0.00 | 0.00 | 77287.69 | 0.00 | 0.35 |
| Maximum of Months | 0.545963E+09 | 0.108399E+09 | 0.00 | 1332216.32 | 3726815.41 | 0.303070E+09 | 0.226338E+09 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: T S1 APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.522202E+09 | 5926496.15 | 0.00 | 1111144.79 | 34306.62 | 0.121385E+09 | 0.182549E+09 | 0.00 | 0.35 |
| February | 0.505287E+09 | 1446184.78 | 0.00 | 770813.48 | 0.00 | 71144876.66 | 0.129900E+09 | 0.00 | 0.35 |
| March | 0.554329E+09 | 1254390.67 | 0.00 | 660646.16 | 5393.96 | 0.155724E+09 | 0.110423E+09 | 0.00 | 0.35 |
| April | 0.462205E+09 | 7180839.20 | 0.00 | 1101959.59 | 0.00 | 13174594.43 | 0.166348E+09 | 0.00 | 0.35 |
| May | 0.479491E+09 | 1763427.89 | 0.00 | 797872.10 | 0.00 | 10607806.55 | 0.152006E+09 | 0.00 | 0.35 |
| June | 0.272080E+09 | 19911664.37 | 0.00 | 1108167.77 | 0.00 | 0.00 | 0.201162E+09 | 0.00 | 0.36 |
| July | 0.102152E+09 | 0.100527E+09 | 0.00 | 1294884.75 | 0.00 | 0.00 | 0.222444E+09 | 0.00 | 0.36 |
| August | 0.102796E+09 | 0.129537E+09 | 0.00 | 979487.97 | 0.00 | 0.00 | 0.193339E+09 | 0.00 | 0.36 |
| September | 0.199348E+09 | 46943186.72 | 0.00 | 1547160.14 | 120013.66 | 0.00 | 0.209177E+09 | 0.00 | 0.36 |
| October | 0.253680E+09 | 83344338.95 | 0.00 | 1348205.12 | 117692.95 | 0.00 | 0.177578E+09 | 0.00 | 0.36 |
| November | 0.511173E+09 | 4233292.10 | 0.00 | 1098082.51 | 136692.60 | 24819752.04 | 0.187447E+09 | 0.00 | 0.35 |
| December | 0.539421E+09 | 4188480.52 | 0.00 | 1202094.17 | 171.89 | 89545279.19 | 0.163479E+09 | 0.00 | 0.35 |
| Annual Sum or Average | 0.450416E+10 | 0.406256E+09 | 0.00 | 13020518.56 | 414271.68 | 0.486402E+09 | 0.209585E+10 | 0.00 | 0.35 |
| Minimum of Months | 0.102152E+09 | 1254390.67 | 0.00 | 660646.16 | 0.00 | 0.00 | 0.110423E+09 | 0.00 | 0.35 |
| Maximum of Months | 0.554329E+09 | 0.129537E+09 | 0.00 | 1547160.14 | 136692.60 | 0.155724E+09 | 0.222444E+09 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: T S2 APARTMENT
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.521677E+09 | 5932383.29 | 0.00 | 1116233.83 | 34304.85 | 0.121521E+09 | 0.183037E+09 | 0.00 | 0.35 |
| February | 0.503742E+09 | 1447019.22 | 0.00 | 772464.73 | 0.00 | 72768602.50 | 0.129708E+09 | 0.00 | 0.35 |
| March | 0.554682E+09 | 1285559.19 | 0.00 | 660575.88 | 128.31 | 0.156471E+09 | 0.109370E+09 | 0.00 | 0.35 |
| April | 0.462354E+09 | 7253481.09 | 0.00 | 1098985.95 | 0.00 | 12998033.31 | 0.166305E+09 | 0.00 | 0.35 |
| May | 0.480724E+09 | 1777026.60 | 0.00 | 793512.26 | 0.00 | 10355054.38 | 0.150749E+09 | 0.00 | 0.35 |
| June | 0.274226E+09 | 20092634.15 | 0.00 | 1094394.39 | 0.00 | 0.00 | 0.199230E+09 | 0.00 | 0.36 |
| July | 0.105184E+09 | 0.100974E+09 | 0.00 | 1280005.57 | 0.00 | 0.00 | 0.220370E+09 | 0.00 | 0.36 |
| August | 0.105231E+09 | 0.130187E+09 | 0.00 | 970857.88 | 0.00 | 0.00 | 0.191886E+09 | 0.00 | 0.36 |
| September | 0.203262E+09 | 47097247.20 | 0.00 | 1529789.83 | 120251.41 | 0.00 | 0.205618E+09 | 0.00 | 0.36 |
| October | 0.255219E+09 | 83354845.80 | 0.00 | 1344845.69 | 114559.74 | 0.00 | 0.176151E+09 | 0.00 | 0.36 |
| November | 0.513364E+09 | 4235551.48 | 0.00 | 1096376.28 | 135380.54 | 24819153.66 | 0.185208E+09 | 0.00 | 0.35 |
| December | 0.537938E+09 | 4191692.72 | 0.00 | 1201856.99 | 0.00 | 91302403.75 | 0.163155E+09 | 0.00 | 0.35 |
| Annual Sum or Average | 0.451760E+10 | 0.407829E+09 | 0.00 | 12959899.28 | 404624.86 | 0.490235E+09 | 0.208079E+10 | 0.00 | 0.35 |
| Minimum of Months | 0.105184E+09 | 1285559.19 | 0.00 | 660575.88 | 0.00 | 0.00 | 0.109370E+09 | 0.00 | 0.35 |
| Maximum of Months | 0.554682E+09 | 0.130187E+09 | 0.00 | 1529789.83 | 135380.54 | 0.156471E+09 | 0.220370E+09 | 0.00 | 0.36 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 09:15:25
Custom Monthly Report| SITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
| January | 0.103741E+12 | 0.117798E+11 | 0.00 | 0.130733E+10 | 0.156377E+11 |
| February | 0.115863E+12 | 0.127986E+11 | 0.00 | 0.114304E+10 | 0.873152E+10 |
| March | 0.150207E+12 | 0.135841E+11 | 0.00 | 0.128963E+10 | 0.856924E+10 |
| April | 0.181071E+12 | 0.115847E+11 | 0.00 | 0.101665E+10 | 0.206904E+11 |
| May | 0.185294E+12 | 0.142097E+11 | 0.00 | 0.104239E+10 | 0.177146E+11 |
| June | 0.180482E+12 | 0.104765E+11 | 0.00 | 0.768989E+09 | 0.401635E+11 |
| July | 0.189836E+12 | 0.500674E+10 | 0.00 | 0.595644E+09 | 0.758866E+11 |
| August | 0.179578E+12 | 0.455511E+10 | 0.00 | 0.518942E+09 | 0.806375E+11 |
| September | 0.152203E+12 | 0.819703E+10 | 0.00 | 0.719681E+09 | 0.552153E+11 |
| October | 0.114415E+12 | 0.892408E+10 | 0.00 | 0.787939E+09 | 0.592742E+11 |
| November | 0.109302E+12 | 0.127072E+11 | 0.00 | 0.121363E+10 | 0.174363E+11 |
| December | 0.971198E+11 | 0.118924E+11 | 0.00 | 0.130958E+10 | 0.180212E+11 |
| Annual Sum or Average | 0.175911E+13 | 0.125716E+12 | 0.00 | 0.117134E+11 | 0.417978E+12 |
| Minimum of Months | 0.971198E+11 | 0.455511E+10 | 0.00 | 0.518942E+09 | 0.856924E+10 |
| Maximum of Months | 0.189836E+12 | 0.142097E+11 | 0.00 | 0.130958E+10 | 0.806375E+11 |