Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 09:17
Tabular Output Report in Format: HTML
Building: ApartmentMidRise
Environment: RUNPERIOD 1 ** Tucson-Davis Monthan AFB AZ USA TMY3 WMO#=722745
Simulation Timestamp: 2023-10-16 09:17:08
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 09:17:08
Values gathered over 8760.00 hours| Total Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
| Total Site Energy | 1412.99 | 450.77 | 500.35 |
| Net Site Energy | 1412.99 | 450.77 | 500.35 |
| Total Source Energy | 4419.12 | 1409.78 | 1564.86 |
| Net Source Energy | 4419.12 | 1409.78 | 1564.86 |
| Site=>Source Conversion Factor | |
| Electricity | 3.167 |
| Natural Gas | 1.084 |
| District Cooling | 1.056 |
| District Heating | 3.613 |
| Steam | 1.200 |
| Gasoline | 1.050 |
| Diesel | 1.050 |
| Coal | 1.050 |
| Fuel Oil No 1 | 1.050 |
| Fuel Oil No 2 | 1.050 |
| Propane | 1.050 |
| Other Fuel 1 | 1.000 |
| Other Fuel 2 | 1.000 |
| Area [m2] | |
| Total Building Area | 3134.61 |
| Net Conditioned Building Area | 2823.98 |
| Unconditioned Building Area | 310.64 |
| Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
| Heating | 0.00 | 26.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Cooling | 266.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Lighting | 99.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Lighting | 50.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment | 458.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans | 132.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems | 379.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1875.32 |
| Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Total End Uses | 1386.19 | 26.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1875.32 |
| Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
| Heating | General | 0.00 | 26.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Cooling | General | 266.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Lighting | LightsWired | 94.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LightsPlugIn | 4.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Exterior Lighting | General | 50.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment | MiscPlug | 388.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| ElevatorLift | 65.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| ElevatorLightsFan | 5.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| General | 132.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems | Water Heater | 379.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1875.32 |
| Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
| Heating | Unassigned | 0.00 | 26.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Cooling | Unassigned | 266.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Lighting | GENERAL | 99.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Lighting | Unassigned | 50.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment | GENERAL | 458.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans | Unassigned | 132.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Pumps | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems | Unassigned | 379.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1875.32 |
| Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
| Lighting | 52.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| HVAC | 275.58 | 9.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.66 |
| Other | 162.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Total | 490.87 | 9.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.66 |
| Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
| Lighting | 47.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| HVAC | 248.27 | 8.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.60 |
| Other | 146.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Total | 442.22 | 8.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.60 |
| Electricity [GJ] | Percent Electricity [%] | |
| Fuel-Fired Power Generation | 0.000 | 0.00 |
| High Temperature Geothermal* | 0.000 | 0.00 |
| Photovoltaic Power | 0.000 | 0.00 |
| Wind Power | 0.000 | 0.00 |
| Power Conversion | 0.000 | 0.00 |
| Net Decrease in On-Site Storage | 0.000 | 0.00 |
| Total On-Site Electric Sources | 0.000 | 0.00 |
| Electricity Coming From Utility | 1386.193 | 100.00 |
| Surplus Electricity Going To Utility | 0.000 | 0.00 |
| Net Electricity From Utility | 1386.193 | 100.00 |
| Total On-Site and Utility Electric Sources | 1386.193 | 100.00 |
| Total Electricity End Uses | 1386.193 | 100.00 |
| Heat [GJ] | Percent Heat [%] | |
| Water-Side Heat Recovery | 0.00 | 0.00 |
| Air to Air Heat Recovery for Cooling | 0.00 | 49.75 |
| Air to Air Heat Recovery for Heating | 0.00 | 50.25 |
| High-Temperature Geothermal* | 0.00 | 0.00 |
| Solar Water Thermal | 0.00 | 0.00 |
| Solar Air Thermal | 0.00 | 0.00 |
| Total On-Site Thermal Sources | 0.00 | 100.00 |
| Water [m3] | Percent Water [%] | |
| Rainwater Collection | 0.00 | 0.00 |
| Condensate Collection | 0.00 | 0.00 |
| Groundwater Well | 0.00 | 0.00 |
| Total On Site Water Sources | 0.00 | 0.00 |
| - | - | - |
| Initial Storage | 0.00 | 0.00 |
| Final Storage | 0.00 | 0.00 |
| Change in Storage | 0.00 | 0.00 |
| - | - | - |
| Water Supplied by Utility | 1875.32 | 100.00 |
| - | - | - |
| Total On Site, Change in Storage, and Utility Water Sources | 1875.32 | 100.00 |
| Total Water End Uses | 1875.32 | 100.00 |
| Degrees [deltaC] | |
| Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
| Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
| Facility [Hours] | |
| Time Setpoint Not Met During Occupied Heating | 0.00 |
| Time Setpoint Not Met During Occupied Cooling | 0.00 |
| Time Not Comfortable Based on Simple ASHRAE 55-2004 | 8594.67 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2012
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME APARTMENTMIDRISE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 2B
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_AZ_TUCSON
| Environment |ZoneCoolingSummaryMonthly
| G SW APARTMENT | G NW APARTMENT | OFFICE | G NE APARTMENT | G N1 APARTMENT | G N2 APARTMENT | G S1 APARTMENT | G S2 APARTMENT | M SW APARTMENT | M NW APARTMENT | M SE APARTMENT | M NE APARTMENT | M N1 APARTMENT | M N2 APARTMENT | M S1 APARTMENT | M S2 APARTMENT | T SW APARTMENT | T NW APARTMENT | T SE APARTMENT | T NE APARTMENT | T N1 APARTMENT | T N2 APARTMENT | T S1 APARTMENT | T S2 APARTMENT | T CORRIDOR | G CORRIDOR | M CORRIDOR |ZoneHeatingSummaryMonthly
| G SW APARTMENT | G NW APARTMENT | OFFICE | G NE APARTMENT | G N1 APARTMENT | G N2 APARTMENT | G S1 APARTMENT | G S2 APARTMENT | M SW APARTMENT | M NW APARTMENT | M SE APARTMENT | M NE APARTMENT | M N1 APARTMENT | M N2 APARTMENT | M S1 APARTMENT | M S2 APARTMENT | T SW APARTMENT | T NW APARTMENT | T SE APARTMENT | T NE APARTMENT | T N1 APARTMENT | T N2 APARTMENT | T S1 APARTMENT | T S2 APARTMENT | T CORRIDOR | G CORRIDOR | M CORRIDOR |ZoneElectricSummaryMonthly
| G SW APARTMENT | G NW APARTMENT | OFFICE | G NE APARTMENT | G N1 APARTMENT | G N2 APARTMENT | G S1 APARTMENT | G S2 APARTMENT | M SW APARTMENT | M NW APARTMENT | M SE APARTMENT | M NE APARTMENT | M N1 APARTMENT | M N2 APARTMENT | M S1 APARTMENT | M S2 APARTMENT | T SW APARTMENT | T NW APARTMENT | T SE APARTMENT | T NE APARTMENT | T N1 APARTMENT | T N2 APARTMENT | T S1 APARTMENT | T S2 APARTMENT | T CORRIDOR | G CORRIDOR | M CORRIDOR |SpaceGainsMonthly
| G SW APARTMENT | G NW APARTMENT | OFFICE | G NE APARTMENT | G N1 APARTMENT | G N2 APARTMENT | G S1 APARTMENT | G S2 APARTMENT | M SW APARTMENT | M NW APARTMENT | M SE APARTMENT | M NE APARTMENT | M N1 APARTMENT | M N2 APARTMENT | M S1 APARTMENT | M S2 APARTMENT | T SW APARTMENT | T NW APARTMENT | T SE APARTMENT | T NE APARTMENT | T N1 APARTMENT | T N2 APARTMENT | T S1 APARTMENT | T S2 APARTMENT | T CORRIDOR | G CORRIDOR | M CORRIDOR |PeakSpaceGainsMonthly
| G SW APARTMENT | G NW APARTMENT | OFFICE | G NE APARTMENT | G N1 APARTMENT | G N2 APARTMENT | G S1 APARTMENT | G S2 APARTMENT | M SW APARTMENT | M NW APARTMENT | M SE APARTMENT | M NE APARTMENT | M N1 APARTMENT | M N2 APARTMENT | M S1 APARTMENT | M S2 APARTMENT | T SW APARTMENT | T NW APARTMENT | T SE APARTMENT | T NE APARTMENT | T N1 APARTMENT | T N2 APARTMENT | T S1 APARTMENT | T S2 APARTMENT | T CORRIDOR | G CORRIDOR | M CORRIDOR |SpaceGainComponentsAtCoolingPeakMonthly
| G SW APARTMENT | G NW APARTMENT | OFFICE | G NE APARTMENT | G N1 APARTMENT | G N2 APARTMENT | G S1 APARTMENT | G S2 APARTMENT | M SW APARTMENT | M NW APARTMENT | M SE APARTMENT | M NE APARTMENT | M N1 APARTMENT | M N2 APARTMENT | M S1 APARTMENT | M S2 APARTMENT | T SW APARTMENT | T NW APARTMENT | T SE APARTMENT | T NE APARTMENT | T N1 APARTMENT | T N2 APARTMENT | T S1 APARTMENT | T S2 APARTMENT | T CORRIDOR | G CORRIDOR | M CORRIDOR |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| G SW APARTMENT | G NW APARTMENT | OFFICE | G NE APARTMENT | G N1 APARTMENT | G N2 APARTMENT | G S1 APARTMENT | G S2 APARTMENT | M SW APARTMENT | M NW APARTMENT | M SE APARTMENT | M NE APARTMENT | M N1 APARTMENT | M N2 APARTMENT | M S1 APARTMENT | M S2 APARTMENT | T SW APARTMENT | T NW APARTMENT | T SE APARTMENT | T NE APARTMENT | T N1 APARTMENT | T N2 APARTMENT | T S1 APARTMENT | T S2 APARTMENT | T CORRIDOR | G CORRIDOR | M CORRIDOR |ComfortReportSimple55Monthly
| G SW APARTMENT | G NW APARTMENT | OFFICE | G NE APARTMENT | G N1 APARTMENT | G N2 APARTMENT | G S1 APARTMENT | G S2 APARTMENT | M SW APARTMENT | M NW APARTMENT | M SE APARTMENT | M NE APARTMENT | M N1 APARTMENT | M N2 APARTMENT | M S1 APARTMENT | M S2 APARTMENT | T SW APARTMENT | T NW APARTMENT | T SE APARTMENT | T NE APARTMENT | T N1 APARTMENT | T N2 APARTMENT | T S1 APARTMENT | T S2 APARTMENT | T CORRIDOR | G CORRIDOR | M CORRIDOR |OccupantComfortDataSummaryMonthly
| OCCUP_GSW | OCCUP_GNW | OCCUP_OFFICE | OCCUP_GNE | OCCUP_GN1 | OCCUP_GN2 | OCCUP_GS1 | OCCUP_GS2 | OCCUP_MSW | OCCUP_MNW | OCCUP_MSE | OCCUP_MNE | OCCUP_MN1 | OCCUP_MN2 | OCCUP_MS1 | OCCUP_MS2 | OCCUP_TSW | OCCUP_TNW | OCCUP_TSE | OCCUP_TNE | OCCUP_TN1 | OCCUP_TN2 | OCCUP_TS1 | OCCUP_TS2 | OCCUP_T CORRIDOR | OCCUP_G CORRIDOR | OCCUP_M CORRIDOR |DXReportMonthly
| SPLIT GSW COOLING COIL | SPLIT GNW COOLING COIL | SPLIT OFFICE COOLING COIL | SPLIT GNE COOLING COIL | SPLIT GN1 COOLING COIL | SPLIT GN2 COOLING COIL | SPLIT GS1 COOLING COIL | SPLIT GS2 COOLING COIL | SPLIT MSW COOLING COIL | SPLIT MNW COOLING COIL | SPLIT MSE COOLING COIL | SPLIT MNE COOLING COIL | SPLIT MN1 COOLING COIL | SPLIT MN2 COOLING COIL | SPLIT MS1 COOLING COIL | SPLIT MS2 COOLING COIL | SPLIT TSW COOLING COIL | SPLIT TNW COOLING COIL | SPLIT TSE COOLING COIL | SPLIT TNE COOLING COIL | SPLIT TN1 COOLING COIL | SPLIT TN2 COOLING COIL | SPLIT TS1 COOLING COIL | SPLIT TS2 COOLING COIL |WindowReportMonthly
| GWINDOW1 S SWA | GWINDOW1 W SWA | GWINDOW1 W NWA | GWINDOW1 N NWA | GWINDOW1 S SEA | GWINDOW1 E SEA | GWINDOW1 E NEA | GWINDOW1 N NEA | GWINDOW1 N N1A | GWINDOW1 N N2A | GWINDOW1 S S1A | GWINDOW1 S S2A | MWINDOW1 S SWA | MWINDOW1 W SWA | MWINDOW1 W NWA | MWINDOW1 N NWA | MWINDOW1 S SEA | MWINDOW1 E SEA | MWINDOW1 E NEA | MWINDOW1 N NEA | MWINDOW1 N N1A | MWINDOW1 N N2A | MWINDOW1 S S1A | MWINDOW1 S S2A | TWINDOW1 S SWA | TWINDOW1 W SWA | TWINDOW1 W NWA | TWINDOW1 N NWA | TWINDOW1 S SEA | TWINDOW1 E SEA | TWINDOW1 E NEA | TWINDOW1 N NEA | TWINDOW1 N N1A | TWINDOW1 N N2A | TWINDOW1 S S1A | TWINDOW1 S S2A | TWINDOW14 | ENTRANCE DOOR | MWINDOW14 |WindowEnergyReportMonthly
| GWINDOW1 S SWA | GWINDOW1 W SWA | GWINDOW1 W NWA | GWINDOW1 N NWA | GWINDOW1 S SEA | GWINDOW1 E SEA | GWINDOW1 E NEA | GWINDOW1 N NEA | GWINDOW1 N N1A | GWINDOW1 N N2A | GWINDOW1 S S1A | GWINDOW1 S S2A | MWINDOW1 S SWA | MWINDOW1 W SWA | MWINDOW1 W NWA | MWINDOW1 N NWA | MWINDOW1 S SEA | MWINDOW1 E SEA | MWINDOW1 E NEA | MWINDOW1 N NEA | MWINDOW1 N N1A | MWINDOW1 N N2A | MWINDOW1 S S1A | MWINDOW1 S S2A | TWINDOW1 S SWA | TWINDOW1 W SWA | TWINDOW1 W NWA | TWINDOW1 N NWA | TWINDOW1 S SEA | TWINDOW1 E SEA | TWINDOW1 E NEA | TWINDOW1 N NEA | TWINDOW1 N N1A | TWINDOW1 N N2A | TWINDOW1 S S1A | TWINDOW1 S S2A | TWINDOW14 | ENTRANCE DOOR | MWINDOW14 |WindowZoneSummaryMonthly
| G SW APARTMENT | G NW APARTMENT | OFFICE | G NE APARTMENT | G N1 APARTMENT | G N2 APARTMENT | G S1 APARTMENT | G S2 APARTMENT | M SW APARTMENT | M NW APARTMENT | M SE APARTMENT | M NE APARTMENT | M N1 APARTMENT | M N2 APARTMENT | M S1 APARTMENT | M S2 APARTMENT | T SW APARTMENT | T NW APARTMENT | T SE APARTMENT | T NE APARTMENT | T N1 APARTMENT | T N2 APARTMENT | T S1 APARTMENT | T S2 APARTMENT | T CORRIDOR | G CORRIDOR | M CORRIDOR |WindowEnergyZoneSummaryMonthly
| G SW APARTMENT | G NW APARTMENT | OFFICE | G NE APARTMENT | G N1 APARTMENT | G N2 APARTMENT | G S1 APARTMENT | G S2 APARTMENT | M SW APARTMENT | M NW APARTMENT | M SE APARTMENT | M NE APARTMENT | M N1 APARTMENT | M N2 APARTMENT | M S1 APARTMENT | M S2 APARTMENT | T SW APARTMENT | T NW APARTMENT | T SE APARTMENT | T NE APARTMENT | T N1 APARTMENT | T N2 APARTMENT | T S1 APARTMENT | T S2 APARTMENT | T CORRIDOR | G CORRIDOR | M CORRIDOR |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| G SW APARTMENT WATER HEATER | G NW APARTMENT WATER HEATER | G NE APARTMENT WATER HEATER | G N1 APARTMENT WATER HEATER | G N2 APARTMENT WATER HEATER | G S1 APARTMENT WATER HEATER | G S2 APARTMENT WATER HEATER | M SW APARTMENT WATER HEATER | M NW APARTMENT WATER HEATER | M SE APARTMENT WATER HEATER | M NE APARTMENT WATER HEATER | M N1 APARTMENT WATER HEATER | M N2 APARTMENT WATER HEATER | M S1 APARTMENT WATER HEATER | M S2 APARTMENT WATER HEATER | T SW APARTMENT WATER HEATER | T NW APARTMENT WATER HEATER | T SE APARTMENT WATER HEATER | T NE APARTMENT WATER HEATER | T N1 APARTMENT WATER HEATER | T N2 APARTMENT WATER HEATER | T S1 APARTMENT WATER HEATER | T S2 APARTMENT WATER HEATER |DaylightingReportMonthly
| Environment |CoilReportMonthly
| SPLIT GSW HEATING COIL | SPLIT GNW HEATING COIL | SPLIT OFFICE HEATING COIL | SPLIT GNE HEATING COIL | SPLIT GN1 HEATING COIL | SPLIT GN2 HEATING COIL | SPLIT GS1 HEATING COIL | SPLIT GS2 HEATING COIL | SPLIT MSW HEATING COIL | SPLIT MNW HEATING COIL | SPLIT MSE HEATING COIL | SPLIT MNE HEATING COIL | SPLIT MN1 HEATING COIL | SPLIT MN2 HEATING COIL | SPLIT MS1 HEATING COIL | SPLIT MS2 HEATING COIL | SPLIT TSW HEATING COIL | SPLIT TNW HEATING COIL | SPLIT TSE HEATING COIL | SPLIT TNE HEATING COIL | SPLIT TN1 HEATING COIL | SPLIT TN2 HEATING COIL | SPLIT TS1 HEATING COIL | SPLIT TS2 HEATING COIL | SPLIT GSW COOLING COIL | SPLIT GNW COOLING COIL | SPLIT OFFICE COOLING COIL | SPLIT GNE COOLING COIL | SPLIT GN1 COOLING COIL | SPLIT GN2 COOLING COIL | SPLIT GS1 COOLING COIL | SPLIT GS2 COOLING COIL | SPLIT MSW COOLING COIL | SPLIT MNW COOLING COIL | SPLIT MSE COOLING COIL | SPLIT MNE COOLING COIL | SPLIT MN1 COOLING COIL | SPLIT MN2 COOLING COIL | SPLIT MS1 COOLING COIL | SPLIT MS2 COOLING COIL | SPLIT TSW COOLING COIL | SPLIT TNW COOLING COIL | SPLIT TSE COOLING COIL | SPLIT TNE COOLING COIL | SPLIT TN1 COOLING COIL | SPLIT TN2 COOLING COIL | SPLIT TS1 COOLING COIL | SPLIT TS2 COOLING COIL |FanReportMonthly
| SPLIT GSW SUPPLY FAN | G SW APARTMENT ERV SUP FAN | G SW APARTMENT ERV EXH FAN | SPLIT GNW SUPPLY FAN | G NW APARTMENT ERV SUP FAN | G NW APARTMENT ERV EXH FAN | SPLIT OFFICE SUPPLY FAN | SPLIT GNE SUPPLY FAN | G NE APARTMENT ERV SUP FAN | G NE APARTMENT ERV EXH FAN | SPLIT GN1 SUPPLY FAN | G N1 APARTMENT ERV SUP FAN | G N1 APARTMENT ERV EXH FAN | SPLIT GN2 SUPPLY FAN | G N2 APARTMENT ERV SUP FAN | G N2 APARTMENT ERV EXH FAN | SPLIT GS1 SUPPLY FAN | G S1 APARTMENT ERV SUP FAN | G S1 APARTMENT ERV EXH FAN | SPLIT GS2 SUPPLY FAN | G S2 APARTMENT ERV SUP FAN | G S2 APARTMENT ERV EXH FAN | SPLIT MSW SUPPLY FAN | M SW APARTMENT ERV SUP FAN | M SW APARTMENT ERV EXH FAN | SPLIT MNW SUPPLY FAN | M NW APARTMENT ERV SUP FAN | M NW APARTMENT ERV EXH FAN | SPLIT MSE SUPPLY FAN | M SE APARTMENT ERV SUP FAN | M SE APARTMENT ERV EXH FAN | SPLIT MNE SUPPLY FAN | M NE APARTMENT ERV SUP FAN | M NE APARTMENT ERV EXH FAN | SPLIT MN1 SUPPLY FAN | M N1 APARTMENT ERV SUP FAN | M N1 APARTMENT ERV EXH FAN | SPLIT MN2 SUPPLY FAN | M N2 APARTMENT ERV SUP FAN | M N2 APARTMENT ERV EXH FAN | SPLIT MS1 SUPPLY FAN | M S1 APARTMENT ERV SUP FAN | M S1 APARTMENT ERV EXH FAN | SPLIT MS2 SUPPLY FAN | M S2 APARTMENT ERV SUP FAN | M S2 APARTMENT ERV EXH FAN | SPLIT TSW SUPPLY FAN | T SW APARTMENT ERV SUP FAN | T SW APARTMENT ERV EXH FAN | SPLIT TNW SUPPLY FAN | T NW APARTMENT ERV SUP FAN | T NW APARTMENT ERV EXH FAN | SPLIT TSE SUPPLY FAN | T SE APARTMENT ERV SUP FAN | T SE APARTMENT ERV EXH FAN | SPLIT TNE SUPPLY FAN | T NE APARTMENT ERV SUP FAN | T NE APARTMENT ERV EXH FAN | SPLIT TN1 SUPPLY FAN | T N1 APARTMENT ERV SUP FAN | T N1 APARTMENT ERV EXH FAN | SPLIT TN2 SUPPLY FAN | T N2 APARTMENT ERV SUP FAN | T N2 APARTMENT ERV EXH FAN | SPLIT TS1 SUPPLY FAN | T S1 APARTMENT ERV SUP FAN | T S1 APARTMENT ERV EXH FAN | SPLIT TS2 SUPPLY FAN | T S2 APARTMENT ERV SUP FAN | T S2 APARTMENT ERV EXH FAN |ZoneTemperatureOscillationReportMonthly
| G SW APARTMENT | G NW APARTMENT | OFFICE | G NE APARTMENT | G N1 APARTMENT | G N2 APARTMENT | G S1 APARTMENT | G S2 APARTMENT | M SW APARTMENT | M NW APARTMENT | M SE APARTMENT | M NE APARTMENT | M N1 APARTMENT | M N2 APARTMENT | M S1 APARTMENT | M S2 APARTMENT | T SW APARTMENT | T NW APARTMENT | T SE APARTMENT | T NE APARTMENT | T N1 APARTMENT | T N2 APARTMENT | T S1 APARTMENT | T S2 APARTMENT | T CORRIDOR | G CORRIDOR | M CORRIDOR |AirLoopSystemEnergyAndWaterUseMonthly
| SPLIT GSW | SPLIT GNW | SPLIT OFFICE | SPLIT GNE | SPLIT GN1 | SPLIT GN2 | SPLIT GS1 | SPLIT GS2 | SPLIT MSW | SPLIT MNW | SPLIT MSE | SPLIT MNE | SPLIT MN1 | SPLIT MN2 | SPLIT MS1 | SPLIT MS2 | SPLIT TSW | SPLIT TNW | SPLIT TSE | SPLIT TNE | SPLIT TN1 | SPLIT TN2 | SPLIT TS1 | SPLIT TS2 |AirLoopSystemComponentLoadsMonthly
| SPLIT GSW | SPLIT GNW | SPLIT OFFICE | SPLIT GNE | SPLIT GN1 | SPLIT GN2 | SPLIT GS1 | SPLIT GS2 | SPLIT MSW | SPLIT MNW | SPLIT MSE | SPLIT MNE | SPLIT MN1 | SPLIT MN2 | SPLIT MS1 | SPLIT MS2 | SPLIT TSW | SPLIT TNW | SPLIT TSE | SPLIT TNE | SPLIT TN1 | SPLIT TN2 | SPLIT TS1 | SPLIT TS2 |AirLoopSystemComponentEnergyUseMonthly
| SPLIT GSW | SPLIT GNW | SPLIT OFFICE | SPLIT GNE | SPLIT GN1 | SPLIT GN2 | SPLIT GS1 | SPLIT GS2 | SPLIT MSW | SPLIT MNW | SPLIT MSE | SPLIT MNE | SPLIT MN1 | SPLIT MN2 | SPLIT MS1 | SPLIT MS2 | SPLIT TSW | SPLIT TNW | SPLIT TSE | SPLIT TNE | SPLIT TN1 | SPLIT TN2 | SPLIT TS1 | SPLIT TS2 |MechanicalVentilationLoadsMonthly
| G SW APARTMENT | G NW APARTMENT | OFFICE | G NE APARTMENT | G N1 APARTMENT | G N2 APARTMENT | G S1 APARTMENT | G S2 APARTMENT | M SW APARTMENT | M NW APARTMENT | M SE APARTMENT | M NE APARTMENT | M N1 APARTMENT | M N2 APARTMENT | M S1 APARTMENT | M S2 APARTMENT | T SW APARTMENT | T NW APARTMENT | T SE APARTMENT | T NE APARTMENT | T N1 APARTMENT | T N2 APARTMENT | T S1 APARTMENT | T S2 APARTMENT |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 09:17:08
General| Value | |
| Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 09:17 |
| RunPeriod | RUNPERIOD 1 |
| Weather File | Tucson-Davis Monthan AFB AZ USA TMY3 WMO#=722745 |
| Latitude [deg] | 32.17 |
| Longitude [deg] | -110.9 |
| Elevation [m] | 809.00 |
| Time Zone | -7.0 |
| North Axis Angle [deg] | 0.00 |
| Rotation for Appendix G [deg] | 0.00 |
| Hours Simulated [hrs] | 8760.00 |
| Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
| Gross Wall Area [m2] | 1542.04 | 564.80 | 206.22 | 564.80 | 206.22 |
| Above Ground Wall Area [m2] | 1542.04 | 564.80 | 206.22 | 564.80 | 206.22 |
| Window Opening Area [m2] | 306.92 | 112.97 | 43.82 | 112.97 | 37.16 |
| Gross Window-Wall Ratio [%] | 19.90 | 20.00 | 21.25 | 20.00 | 18.02 |
| Above Ground Window-Wall Ratio [%] | 19.90 | 20.00 | 21.25 | 20.00 | 18.02 |
| Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
| Gross Wall Area [m2] | 1501.17 | 564.80 | 185.79 | 564.80 | 185.79 |
| Above Ground Wall Area [m2] | 1501.17 | 564.80 | 185.79 | 564.80 | 185.79 |
| Window Opening Area [m2] | 300.26 | 112.97 | 37.16 | 112.97 | 37.16 |
| Gross Window-Wall Ratio [%] | 20.00 | 20.00 | 20.00 | 20.00 | 20.00 |
| Above Ground Window-Wall Ratio [%] | 20.00 | 20.00 | 20.00 | 20.00 | 20.00 |
| Total | |
| Gross Roof Area [m2] | 783.65 |
| Skylight Area [m2] | 0.00 |
| Skylight-Roof Ratio [%] | 0.00 |
| Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
| G SW APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 0.00 | 11.71 | 11.71 | 8.6918 | 35.30 | 6.6700 |
| G NW APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 0.00 | 11.71 | 11.71 | 8.6918 | 35.30 | 6.6700 |
| OFFICE | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 0.00 | 11.71 | 11.71 | 9.7532 | 18.58 | 6.6700 |
| G NE APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 0.00 | 11.71 | 11.71 | 8.6918 | 35.30 | 6.6700 |
| G N1 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 0.00 | 7.06 | 7.06 | 8.6918 | 35.30 | 6.6700 |
| G N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 0.00 | 7.06 | 7.06 | 8.6918 | 35.30 | 6.6700 |
| G S1 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 0.00 | 7.06 | 7.06 | 8.6918 | 35.30 | 6.6700 |
| G S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 0.00 | 7.06 | 7.06 | 8.6918 | 35.30 | 6.6700 |
| M SW APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 58.52 | 0.00 | 11.71 | 11.71 | 8.6918 | 35.30 | 6.6700 |
| M NW APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 58.52 | 0.00 | 11.71 | 11.71 | 8.6918 | 35.30 | 6.6700 |
| M SE APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 58.52 | 0.00 | 11.71 | 11.71 | 8.6918 | 35.30 | 6.6700 |
| M NE APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 58.52 | 0.00 | 11.71 | 11.71 | 8.6918 | 35.30 | 6.6700 |
| M N1 APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 35.30 | 0.00 | 7.06 | 7.06 | 8.6918 | 35.30 | 6.6700 |
| M N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 35.30 | 0.00 | 7.06 | 7.06 | 8.6918 | 35.30 | 6.6700 |
| M S1 APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 35.30 | 0.00 | 7.06 | 7.06 | 8.6918 | 35.30 | 6.6700 |
| M S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 35.30 | 0.00 | 7.06 | 7.06 | 8.6918 | 35.30 | 6.6700 |
| T SW APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 0.00 | 11.71 | 11.71 | 8.6918 | 35.30 | 6.6700 |
| T NW APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 0.00 | 11.71 | 11.71 | 8.6918 | 35.30 | 6.6700 |
| T SE APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 0.00 | 11.71 | 11.71 | 8.6918 | 35.30 | 6.6700 |
| T NE APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 0.00 | 11.71 | 11.71 | 8.6918 | 35.30 | 6.6700 |
| T N1 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 0.00 | 7.06 | 7.06 | 8.6918 | 35.30 | 6.6700 |
| T N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 0.00 | 7.06 | 7.06 | 8.6918 | 35.30 | 6.6700 |
| T S1 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 0.00 | 7.06 | 7.06 | 8.6918 | 35.30 | 6.6700 |
| T S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 0.00 | 7.06 | 7.06 | 8.6918 | 35.30 | 6.6700 |
| T CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 0.00 | 1.11 | 1.11 | 4.7725 | 18.58 | 0.0000 |
| G CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 0.00 | 3.32 | 3.32 | 4.7725 | 18.58 | 105.2565 |
| M CORRIDOR | 77.66 | No | Yes | 236.69 | 2.00 | 10.22 | 0.00 | 1.11 | 1.11 | 4.7725 | 18.58 | 0.0000 |
| Total | 3134.61 | 9553.84 | 1542.04 | 0.00 | 306.92 | 306.92 | 8.3333 | 31.67 | 8.6167 | |||
| Conditioned Total | 2823.98 | 8607.06 | 1501.17 | 0.00 | 300.26 | 300.26 | 8.7250 | 34.33 | 6.6700 | |||
| Unconditioned Total | 310.64 | 946.78 | 40.87 | 0.00 | 6.66 | 6.66 | 4.7725 | 18.58 | 26.3141 | |||
| Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
| G SW APARTMENT | 88.25 | Yes | Yes | 1.00 | G SW APARTMENT | GENERAL | G SW APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| G NW APARTMENT | 88.25 | Yes | Yes | 1.00 | G NW APARTMENT | GENERAL | G NW APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| OFFICE | 88.25 | Yes | Yes | 1.00 | OFFICE | GENERAL | OFFICE | 9.7532 | 18.58 | 6.6700 | |
| G NE APARTMENT | 88.25 | Yes | Yes | 1.00 | G NE APARTMENT | GENERAL | G NE APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| G N1 APARTMENT | 88.25 | Yes | Yes | 1.00 | G N1 APARTMENT | GENERAL | G N1 APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| G N2 APARTMENT | 88.25 | Yes | Yes | 1.00 | G N2 APARTMENT | GENERAL | G N2 APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| G S1 APARTMENT | 88.25 | Yes | Yes | 1.00 | G S1 APARTMENT | GENERAL | G S1 APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| G S2 APARTMENT | 88.25 | Yes | Yes | 1.00 | G S2 APARTMENT | GENERAL | G S2 APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| M SW APARTMENT | 88.25 | Yes | Yes | 2.00 | M SW APARTMENT | GENERAL | M SW APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| M NW APARTMENT | 88.25 | Yes | Yes | 2.00 | M NW APARTMENT | GENERAL | M NW APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| M SE APARTMENT | 88.25 | Yes | Yes | 2.00 | M SE APARTMENT | GENERAL | M SE APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| M NE APARTMENT | 88.25 | Yes | Yes | 2.00 | M NE APARTMENT | GENERAL | M NE APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| M N1 APARTMENT | 88.25 | Yes | Yes | 2.00 | M N1 APARTMENT | GENERAL | M N1 APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| M N2 APARTMENT | 88.25 | Yes | Yes | 2.00 | M N2 APARTMENT | GENERAL | M N2 APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| M S1 APARTMENT | 88.25 | Yes | Yes | 2.00 | M S1 APARTMENT | GENERAL | M S1 APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| M S2 APARTMENT | 88.25 | Yes | Yes | 2.00 | M S2 APARTMENT | GENERAL | M S2 APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| T SW APARTMENT | 88.25 | Yes | Yes | 1.00 | T SW APARTMENT | GENERAL | T SW APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| T NW APARTMENT | 88.25 | Yes | Yes | 1.00 | T NW APARTMENT | GENERAL | T NW APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| T SE APARTMENT | 88.25 | Yes | Yes | 1.00 | T SE APARTMENT | GENERAL | T SE APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| T NE APARTMENT | 88.25 | Yes | Yes | 1.00 | T NE APARTMENT | GENERAL | T NE APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| T N1 APARTMENT | 88.25 | Yes | Yes | 1.00 | T N1 APARTMENT | GENERAL | T N1 APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| T N2 APARTMENT | 88.25 | Yes | Yes | 1.00 | T N2 APARTMENT | GENERAL | T N2 APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| T S1 APARTMENT | 88.25 | Yes | Yes | 1.00 | T S1 APARTMENT | GENERAL | T S1 APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| T S2 APARTMENT | 88.25 | Yes | Yes | 1.00 | T S2 APARTMENT | GENERAL | T S2 APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| T CORRIDOR | 77.66 | No | Yes | 1.00 | T CORRIDOR | GENERAL | T CORRIDOR | 4.7725 | 18.58 | 0.0000 | |
| G CORRIDOR | 77.66 | No | Yes | 1.00 | G CORRIDOR | GENERAL | G CORRIDOR | 4.7725 | 18.58 | 105.2565 | |
| M CORRIDOR | 77.66 | No | Yes | 2.00 | M CORRIDOR | GENERAL | M CORRIDOR | 4.7725 | 18.58 | 0.0000 | |
| Total | 3134.61 | 8.3333 | 15.84 | 8.6167 | |||||||
| Conditioned Total | 2823.98 | 8.7250 | 17.17 | 6.6700 | |||||||
| Unconditioned Total | 310.64 | 4.7725 | 9.29 | 26.3141 | |||||||
| Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
| Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
| GENERAL | 3134.61 | 2823.98 | 310.64 | 0.00 | 6.2575 | 41.91 | 7.1145 |
| Total | 3134.61 | 2823.98 | 310.64 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 09:17:08
End Uses| Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
| Time of Peak | 07-SEP-17:10 | 07-DEC-05:00 | - | - | - | - | - | - | - | - | - | - | 01-JAN-07:10 |
| Heating | 0.00 | 34097.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Cooling | 27836.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Lighting | 5231.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment | 22609.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans | 9418.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems | 32073.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Total End Uses | 97169.37 | 34097.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
| Heating | General | 0.00 | 34097.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Cooling | General | 27836.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Lighting | LightsWired | 4887.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LightsPlugIn | 344.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment | MiscPlug | 18441.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| ElevatorLift | 4006.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| ElevatorLightsFan | 162.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| General | 9418.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems | Water Heater | 32073.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 09:17:08
Values gathered over 8760.00 hours| Source Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
| Heating | 0.00 | 29.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Cooling | 843.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Lighting | 314.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Lighting | 158.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment | 1452.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans | 419.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems | 1201.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Total Source Energy End Use Components | 4390.07 | 29.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
| Heating | 0.00 | 10.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Cooling | 298.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Lighting | 111.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Lighting | 56.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment | 514.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans | 148.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems | 425.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Total Source Energy End Use Components | 1554.57 | 10.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
| Heating | 0.00 | 9.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Cooling | 269.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Lighting | 100.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Lighting | 50.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment | 463.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans | 133.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems | 383.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Total Source Energy End Use Components | 1400.51 | 9.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 09:17:08
ZoneHVAC:EnergyRecoveryVentilator| User-Specified Supply Air Flow Rate [m3/s] | User-Specified Exhaust Air Flow Rate [m3/s] | |
| G SW APARTMENT ERV | 0.025955 | 0.025955 |
| G NW APARTMENT ERV | 0.025955 | 0.025955 |
| G NE APARTMENT ERV | 0.025955 | 0.025955 |
| G N1 APARTMENT ERV | 0.025955 | 0.025955 |
| G N2 APARTMENT ERV | 0.025955 | 0.025955 |
| G S1 APARTMENT ERV | 0.025955 | 0.025955 |
| G S2 APARTMENT ERV | 0.025955 | 0.025955 |
| M SW APARTMENT ERV | 0.051909 | 0.051909 |
| M NW APARTMENT ERV | 0.051909 | 0.051909 |
| M SE APARTMENT ERV | 0.051909 | 0.051909 |
| M NE APARTMENT ERV | 0.051909 | 0.051909 |
| M N1 APARTMENT ERV | 0.051909 | 0.051909 |
| M N2 APARTMENT ERV | 0.051909 | 0.051909 |
| M S1 APARTMENT ERV | 0.051909 | 0.051909 |
| M S2 APARTMENT ERV | 0.051909 | 0.051909 |
| T SW APARTMENT ERV | 0.025955 | 0.025955 |
| T NW APARTMENT ERV | 0.025955 | 0.025955 |
| T SE APARTMENT ERV | 0.025955 | 0.025955 |
| T NE APARTMENT ERV | 0.025955 | 0.025955 |
| T N1 APARTMENT ERV | 0.025955 | 0.025955 |
| T N2 APARTMENT ERV | 0.025955 | 0.025955 |
| T S1 APARTMENT ERV | 0.025955 | 0.025955 |
| T S2 APARTMENT ERV | 0.025955 | 0.025955 |
| Design Size Maximum Flow Rate [m3/s] | |
| G SW APARTMENT ERV SUP FAN | 0.025955 |
| G SW APARTMENT ERV EXH FAN | 0.025955 |
| G NW APARTMENT ERV SUP FAN | 0.025955 |
| G NW APARTMENT ERV EXH FAN | 0.025955 |
| G NE APARTMENT ERV SUP FAN | 0.025955 |
| G NE APARTMENT ERV EXH FAN | 0.025955 |
| G N1 APARTMENT ERV SUP FAN | 0.025955 |
| G N1 APARTMENT ERV EXH FAN | 0.025955 |
| G N2 APARTMENT ERV SUP FAN | 0.025955 |
| G N2 APARTMENT ERV EXH FAN | 0.025955 |
| G S1 APARTMENT ERV SUP FAN | 0.025955 |
| G S1 APARTMENT ERV EXH FAN | 0.025955 |
| G S2 APARTMENT ERV SUP FAN | 0.025955 |
| G S2 APARTMENT ERV EXH FAN | 0.025955 |
| M SW APARTMENT ERV SUP FAN | 0.051909 |
| M SW APARTMENT ERV EXH FAN | 0.051909 |
| M NW APARTMENT ERV SUP FAN | 0.051909 |
| M NW APARTMENT ERV EXH FAN | 0.051909 |
| M SE APARTMENT ERV SUP FAN | 0.051909 |
| M SE APARTMENT ERV EXH FAN | 0.051909 |
| M NE APARTMENT ERV SUP FAN | 0.051909 |
| M NE APARTMENT ERV EXH FAN | 0.051909 |
| M N1 APARTMENT ERV SUP FAN | 0.051909 |
| M N1 APARTMENT ERV EXH FAN | 0.051909 |
| M N2 APARTMENT ERV SUP FAN | 0.051909 |
| M N2 APARTMENT ERV EXH FAN | 0.051909 |
| M S1 APARTMENT ERV SUP FAN | 0.051909 |
| M S1 APARTMENT ERV EXH FAN | 0.051909 |
| M S2 APARTMENT ERV SUP FAN | 0.051909 |
| M S2 APARTMENT ERV EXH FAN | 0.051909 |
| T SW APARTMENT ERV SUP FAN | 0.025955 |
| T SW APARTMENT ERV EXH FAN | 0.025955 |
| T NW APARTMENT ERV SUP FAN | 0.025955 |
| T NW APARTMENT ERV EXH FAN | 0.025955 |
| T SE APARTMENT ERV SUP FAN | 0.025955 |
| T SE APARTMENT ERV EXH FAN | 0.025955 |
| T NE APARTMENT ERV SUP FAN | 0.025955 |
| T NE APARTMENT ERV EXH FAN | 0.025955 |
| T N1 APARTMENT ERV SUP FAN | 0.025955 |
| T N1 APARTMENT ERV EXH FAN | 0.025955 |
| T N2 APARTMENT ERV SUP FAN | 0.025955 |
| T N2 APARTMENT ERV EXH FAN | 0.025955 |
| T S1 APARTMENT ERV SUP FAN | 0.025955 |
| T S1 APARTMENT ERV EXH FAN | 0.025955 |
| T S2 APARTMENT ERV SUP FAN | 0.025955 |
| T S2 APARTMENT ERV EXH FAN | 0.025955 |
| SPLIT GSW SUPPLY FAN | 0.424501 |
| SPLIT GNW SUPPLY FAN | 0.419635 |
| SPLIT OFFICE SUPPLY FAN | 0.453072 |
| SPLIT GNE SUPPLY FAN | 0.394375 |
| SPLIT GN1 SUPPLY FAN | 0.348238 |
| SPLIT GN2 SUPPLY FAN | 0.347791 |
| SPLIT GS1 SUPPLY FAN | 0.354117 |
| SPLIT GS2 SUPPLY FAN | 0.356787 |
| SPLIT MSW SUPPLY FAN | 0.965720 |
| SPLIT MNW SUPPLY FAN | 0.957054 |
| SPLIT MSE SUPPLY FAN | 0.898418 |
| SPLIT MNE SUPPLY FAN | 0.889875 |
| SPLIT MN1 SUPPLY FAN | 0.777752 |
| SPLIT MN2 SUPPLY FAN | 0.776630 |
| SPLIT MS1 SUPPLY FAN | 0.788376 |
| SPLIT MS2 SUPPLY FAN | 0.787233 |
| SPLIT TSW SUPPLY FAN | 0.554194 |
| SPLIT TNW SUPPLY FAN | 0.553906 |
| SPLIT TSE SUPPLY FAN | 0.503488 |
| SPLIT TNE SUPPLY FAN | 0.503129 |
| SPLIT TN1 SUPPLY FAN | 0.451315 |
| SPLIT TN2 SUPPLY FAN | 0.449771 |
| SPLIT TS1 SUPPLY FAN | 0.452192 |
| SPLIT TS2 SUPPLY FAN | 0.450655 |
| Design Size Nominal Supply Air Flow Rate [m3/s] | |
| G SW APARTMENT OA HEAT EXCHANGER | 0.025955 |
| G NW APARTMENT OA HEAT EXCHANGER | 0.025955 |
| G NE APARTMENT OA HEAT EXCHANGER | 0.025955 |
| G N1 APARTMENT OA HEAT EXCHANGER | 0.025955 |
| G N2 APARTMENT OA HEAT EXCHANGER | 0.025955 |
| G S1 APARTMENT OA HEAT EXCHANGER | 0.025955 |
| G S2 APARTMENT OA HEAT EXCHANGER | 0.025955 |
| M SW APARTMENT OA HEAT EXCHANGER | 0.051909 |
| M NW APARTMENT OA HEAT EXCHANGER | 0.051909 |
| M SE APARTMENT OA HEAT EXCHANGER | 0.051909 |
| M NE APARTMENT OA HEAT EXCHANGER | 0.051909 |
| M N1 APARTMENT OA HEAT EXCHANGER | 0.051909 |
| M N2 APARTMENT OA HEAT EXCHANGER | 0.051909 |
| M S1 APARTMENT OA HEAT EXCHANGER | 0.051909 |
| M S2 APARTMENT OA HEAT EXCHANGER | 0.051909 |
| T SW APARTMENT OA HEAT EXCHANGER | 0.025955 |
| T NW APARTMENT OA HEAT EXCHANGER | 0.025955 |
| T SE APARTMENT OA HEAT EXCHANGER | 0.025955 |
| T NE APARTMENT OA HEAT EXCHANGER | 0.025955 |
| T N1 APARTMENT OA HEAT EXCHANGER | 0.025955 |
| T N2 APARTMENT OA HEAT EXCHANGER | 0.025955 |
| T S1 APARTMENT OA HEAT EXCHANGER | 0.025955 |
| T S2 APARTMENT OA HEAT EXCHANGER | 0.025955 |
| Design Size Maximum Air Flow Rate [m3/s] | |
| G SW APARTMENT DIRECT AIR | 0.424501 |
| G NW APARTMENT DIRECT AIR | 0.419635 |
| OFFICE DIRECT AIR | 0.453072 |
| G NE APARTMENT DIRECT AIR | 0.394375 |
| G N1 APARTMENT DIRECT AIR | 0.348238 |
| G N2 APARTMENT DIRECT AIR | 0.347791 |
| G S1 APARTMENT DIRECT AIR | 0.354117 |
| G S2 APARTMENT DIRECT AIR | 0.356787 |
| M SW APARTMENT DIRECT AIR | 0.965720 |
| M NW APARTMENT DIRECT AIR | 0.957054 |
| M SE APARTMENT DIRECT AIR | 0.898418 |
| M NE APARTMENT DIRECT AIR | 0.889875 |
| M N1 APARTMENT DIRECT AIR | 0.777752 |
| M N2 APARTMENT DIRECT AIR | 0.776630 |
| M S1 APARTMENT DIRECT AIR | 0.788376 |
| M S2 APARTMENT DIRECT AIR | 0.787233 |
| T SW APARTMENT DIRECT AIR | 0.554194 |
| T NW APARTMENT DIRECT AIR | 0.553906 |
| T SE APARTMENT DIRECT AIR | 0.503488 |
| T NE APARTMENT DIRECT AIR | 0.503129 |
| T N1 APARTMENT DIRECT AIR | 0.451315 |
| T N2 APARTMENT DIRECT AIR | 0.449771 |
| T S1 APARTMENT DIRECT AIR | 0.452192 |
| T S2 APARTMENT DIRECT AIR | 0.450655 |
| Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
| SPLIT GSW | 0.424501 | 0.424501 | 0.424501 | 0.424501 | 0.424501 | 0.424501 | 1.00 | 1.00 | 0.424501 |
| SPLIT GNW | 0.419635 | 0.419635 | 0.419635 | 0.419635 | 0.419635 | 0.419635 | 1.00 | 1.00 | 0.419635 |
| SPLIT OFFICE | 0.453072 | 0.453072 | 0.453072 | 0.453072 | 0.453072 | 0.453072 | 1.00 | 1.00 | 0.453072 |
| SPLIT GNE | 0.394375 | 0.394375 | 0.394375 | 0.394375 | 0.394375 | 0.394375 | 1.00 | 1.000000 | 0.394375 |
| SPLIT GN1 | 0.348238 | 0.348238 | 0.348238 | 0.348238 | 0.348238 | 0.348238 | 1.00 | 1.00 | 0.348238 |
| SPLIT GN2 | 0.347791 | 0.347791 | 0.347791 | 0.347791 | 0.347791 | 0.347791 | 1.00 | 1.00 | 0.347791 |
| SPLIT GS1 | 0.354117 | 0.354117 | 0.354117 | 0.354117 | 0.354117 | 0.354117 | 1.00 | 1.000000 | 0.354117 |
| SPLIT GS2 | 0.356787 | 0.356787 | 0.356787 | 0.356787 | 0.356787 | 0.356787 | 1.00 | 1.00 | 0.356787 |
| SPLIT MSW | 0.965720 | 0.965720 | 0.965720 | 0.965720 | 0.965720 | 0.965720 | 1.00 | 1.00 | 0.965720 |
| SPLIT MNW | 0.957054 | 0.957054 | 0.957054 | 0.957054 | 0.957054 | 0.957054 | 1.00 | 1.000000 | 0.957054 |
| SPLIT MSE | 0.898418 | 0.898418 | 0.898418 | 0.898418 | 0.898418 | 0.898418 | 1.00 | 1.00 | 0.898418 |
| SPLIT MNE | 0.889875 | 0.889875 | 0.889875 | 0.889875 | 0.889875 | 0.889875 | 1.00 | 1.00 | 0.889875 |
| SPLIT MN1 | 0.777752 | 0.777752 | 0.777752 | 0.777752 | 0.777752 | 0.777752 | 1.00 | 1.00 | 0.777752 |
| SPLIT MN2 | 0.776630 | 0.776630 | 0.776630 | 0.776630 | 0.776630 | 0.776630 | 1.00 | 1.00 | 0.776630 |
| SPLIT MS1 | 0.788376 | 0.788376 | 0.788376 | 0.788376 | 0.788376 | 0.788376 | 1.00 | 1.000000 | 0.788376 |
| SPLIT MS2 | 0.787233 | 0.787233 | 0.787233 | 0.787233 | 0.787233 | 0.787233 | 1.00 | 1.00 | 0.787233 |
| SPLIT TSW | 0.554194 | 0.554194 | 0.554194 | 0.554194 | 0.554194 | 0.554194 | 1.00 | 1.00 | 0.554194 |
| SPLIT TNW | 0.553906 | 0.553906 | 0.553906 | 0.553906 | 0.553906 | 0.553906 | 1.00 | 1.000000 | 0.553906 |
| SPLIT TSE | 0.503488 | 0.503488 | 0.503488 | 0.503488 | 0.503488 | 0.503488 | 1.00 | 1.00 | 0.503488 |
| SPLIT TNE | 0.503129 | 0.503129 | 0.503129 | 0.503129 | 0.503129 | 0.503129 | 1.00 | 1.00 | 0.503129 |
| SPLIT TN1 | 0.451315 | 0.451315 | 0.451315 | 0.451315 | 0.451315 | 0.451315 | 1.00 | 1.000000 | 0.451315 |
| SPLIT TN2 | 0.449771 | 0.449771 | 0.449771 | 0.449771 | 0.449771 | 0.449771 | 1.00 | 1.00 | 0.449771 |
| SPLIT TS1 | 0.452192 | 0.452192 | 0.452192 | 0.452192 | 0.452192 | 0.452192 | 1.00 | 1.00 | 0.452192 |
| SPLIT TS2 | 0.450655 | 0.450655 | 0.450655 | 0.450655 | 0.450655 | 0.450655 | 1.00 | 1.00 | 0.450655 |
| Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
| SPLIT GSW_OA_CONTROLLER | 0.424501 | 0.025955 |
| SPLIT GNW_OA_CONTROLLER | 0.419635 | 0.025955 |
| SPLIT OFFICE_OA_CONTROLLER | 0.453072 | 0.038106 |
| SPLIT GNE_OA_CONTROLLER | 0.394375 | 0.025955 |
| SPLIT GN1_OA_CONTROLLER | 0.348238 | 0.025955 |
| SPLIT GN2_OA_CONTROLLER | 0.347791 | 0.025955 |
| SPLIT GS1_OA_CONTROLLER | 0.354117 | 0.025955 |
| SPLIT GS2_OA_CONTROLLER | 0.356787 | 0.025955 |
| SPLIT MSW_OA_CONTROLLER | 0.965720 | 0.051909 |
| SPLIT MNW_OA_CONTROLLER | 0.957054 | 0.051909 |
| SPLIT MSE_OA_CONTROLLER | 0.898418 | 0.051909 |
| SPLIT MNE_OA_CONTROLLER | 0.889875 | 0.051909 |
| SPLIT MN1_OA_CONTROLLER | 0.777752 | 0.051909 |
| SPLIT MN2_OA_CONTROLLER | 0.776630 | 0.051909 |
| SPLIT MS1_OA_CONTROLLER | 0.788376 | 0.051909 |
| SPLIT MS2_OA_CONTROLLER | 0.787233 | 0.051909 |
| SPLIT TSW_OA_CONTROLLER | 0.554194 | 0.025955 |
| SPLIT TNW_OA_CONTROLLER | 0.553906 | 0.025955 |
| SPLIT TSE_OA_CONTROLLER | 0.503488 | 0.025955 |
| SPLIT TNE_OA_CONTROLLER | 0.503129 | 0.025955 |
| SPLIT TN1_OA_CONTROLLER | 0.451315 | 0.025955 |
| SPLIT TN2_OA_CONTROLLER | 0.449771 | 0.025955 |
| SPLIT TS1_OA_CONTROLLER | 0.452192 | 0.025955 |
| SPLIT TS2_OA_CONTROLLER | 0.450655 | 0.025955 |
| Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | Design Size Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
| SPLIT GSW_UNITARY_PACKAGE_DX | 0.424501 | 0.424501 | 0.424501 | 0.424501 | 7027.00 | 9401.00 | 40.00 | 1.00 |
| SPLIT GNW_UNITARY_PACKAGE_DX | 0.419635 | 0.419635 | 0.419635 | 0.419635 | 6946.45 | 9299.81 | 40.00 | 1.00 |
| SPLIT OFFICE_UNITARY_PACKAGE_DX | 0.453072 | 0.453072 | 0.453072 | 0.453072 | 7499.94 | 10269.02 | 40.00 | 1.00 |
| SPLIT GNE_UNITARY_PACKAGE_DX | 0.394375 | 0.394375 | 0.394375 | 0.394375 | 6528.31 | 8775.36 | 40.00 | 1.00 |
| SPLIT GN1_UNITARY_PACKAGE_DX | 0.348238 | 0.348238 | 0.348238 | 0.348238 | 5764.57 | 7817.38 | 40.00 | 1.00 |
| SPLIT GN2_UNITARY_PACKAGE_DX | 0.347791 | 0.347791 | 0.347791 | 0.347791 | 5757.17 | 7808.10 | 40.00 | 1.00 |
| SPLIT GS1_UNITARY_PACKAGE_DX | 0.354117 | 0.354117 | 0.354117 | 0.354117 | 5861.90 | 7939.58 | 40.00 | 1.00 |
| SPLIT GS2_UNITARY_PACKAGE_DX | 0.356787 | 0.356787 | 0.356787 | 0.356787 | 5906.10 | 7995.01 | 40.00 | 1.00 |
| SPLIT MSW_UNITARY_PACKAGE_DX | 0.965720 | 0.965720 | 0.965720 | 0.965720 | 15986.10 | 21225.52 | 40.00 | 1.00 |
| SPLIT MNW_UNITARY_PACKAGE_DX | 0.957054 | 0.957054 | 0.957054 | 0.957054 | 15842.64 | 21045.26 | 40.00 | 1.00 |
| SPLIT MSE_UNITARY_PACKAGE_DX | 0.898418 | 0.898418 | 0.898418 | 0.898418 | 14872.00 | 19828.13 | 40.00 | 1.00 |
| SPLIT MNE_UNITARY_PACKAGE_DX | 0.889875 | 0.889875 | 0.889875 | 0.889875 | 14730.59 | 19650.47 | 40.00 | 1.00 |
| SPLIT MN1_UNITARY_PACKAGE_DX | 0.777752 | 0.777752 | 0.777752 | 0.777752 | 12874.56 | 17322.32 | 40.00 | 1.00 |
| SPLIT MN2_UNITARY_PACKAGE_DX | 0.776630 | 0.776630 | 0.776630 | 0.776630 | 12855.99 | 17299.02 | 40.00 | 1.00 |
| SPLIT MS1_UNITARY_PACKAGE_DX | 0.788376 | 0.788376 | 0.788376 | 0.788376 | 13050.42 | 17543.16 | 40.00 | 1.00 |
| SPLIT MS2_UNITARY_PACKAGE_DX | 0.787233 | 0.787233 | 0.787233 | 0.787233 | 13031.50 | 17519.42 | 40.00 | 1.00 |
| SPLIT TSW_UNITARY_PACKAGE_DX | 0.554194 | 0.554194 | 0.554194 | 0.554194 | 9173.88 | 12094.01 | 40.00 | 1.00 |
| SPLIT TNW_UNITARY_PACKAGE_DX | 0.553906 | 0.553906 | 0.553906 | 0.553906 | 9169.11 | 12087.83 | 40.00 | 1.00 |
| SPLIT TSE_UNITARY_PACKAGE_DX | 0.503488 | 0.503488 | 0.503488 | 0.503488 | 8334.51 | 11041.20 | 40.00 | 1.00 |
| SPLIT TNE_UNITARY_PACKAGE_DX | 0.503129 | 0.503129 | 0.503129 | 0.503129 | 8328.58 | 11033.58 | 40.00 | 1.00 |
| SPLIT TN1_UNITARY_PACKAGE_DX | 0.451315 | 0.451315 | 0.451315 | 0.451315 | 7470.87 | 9957.59 | 40.00 | 1.00 |
| SPLIT TN2_UNITARY_PACKAGE_DX | 0.449771 | 0.449771 | 0.449771 | 0.449771 | 7445.31 | 9925.53 | 40.00 | 1.00 |
| SPLIT TS1_UNITARY_PACKAGE_DX | 0.452192 | 0.452192 | 0.452192 | 0.452192 | 7485.39 | 9975.97 | 40.00 | 1.00 |
| SPLIT TS2_UNITARY_PACKAGE_DX | 0.450655 | 0.450655 | 0.450655 | 0.450655 | 7459.95 | 9944.05 | 40.00 | 1.00 |
| Design Size Rated Air Flow Rate [m3/s] | Design Size Gross Rated Total Cooling Capacity [W] | Design Size Gross Rated Sensible Heat Ratio | |
| SPLIT GSW COOLING COIL | 0.424501 | 7027.00 | 0.800655 |
| SPLIT GNW COOLING COIL | 0.419635 | 6946.45 | 0.800655 |
| SPLIT OFFICE COOLING COIL | 0.453072 | 7499.94 | 0.800655 |
| SPLIT GNE COOLING COIL | 0.394375 | 6528.31 | 0.800655 |
| SPLIT GN1 COOLING COIL | 0.348238 | 5764.57 | 0.800655 |
| SPLIT GN2 COOLING COIL | 0.347791 | 5757.17 | 0.800655 |
| SPLIT GS1 COOLING COIL | 0.354117 | 5861.90 | 0.800655 |
| SPLIT GS2 COOLING COIL | 0.356787 | 5906.10 | 0.800655 |
| SPLIT MSW COOLING COIL | 0.965720 | 15986.10 | 0.800655 |
| SPLIT MNW COOLING COIL | 0.957054 | 15842.64 | 0.800655 |
| SPLIT MSE COOLING COIL | 0.898418 | 14872.00 | 0.800655 |
| SPLIT MNE COOLING COIL | 0.889875 | 14730.59 | 0.800655 |
| SPLIT MN1 COOLING COIL | 0.777752 | 12874.56 | 0.800655 |
| SPLIT MN2 COOLING COIL | 0.776630 | 12855.99 | 0.800655 |
| SPLIT MS1 COOLING COIL | 0.788376 | 13050.42 | 0.800655 |
| SPLIT MS2 COOLING COIL | 0.787233 | 13031.50 | 0.800655 |
| SPLIT TSW COOLING COIL | 0.554194 | 9173.88 | 0.800655 |
| SPLIT TNW COOLING COIL | 0.553906 | 9169.11 | 0.800655 |
| SPLIT TSE COOLING COIL | 0.503488 | 8334.51 | 0.800655 |
| SPLIT TNE COOLING COIL | 0.503129 | 8328.58 | 0.800655 |
| SPLIT TN1 COOLING COIL | 0.451315 | 7470.87 | 0.800655 |
| SPLIT TN2 COOLING COIL | 0.449771 | 7445.31 | 0.800655 |
| SPLIT TS1 COOLING COIL | 0.452192 | 7485.39 | 0.800655 |
| SPLIT TS2 COOLING COIL | 0.450655 | 7459.95 | 0.800655 |
| Design Size Nominal Capacity [W] | |
| SPLIT GSW HEATING COIL | 9401.00 |
| SPLIT GNW HEATING COIL | 9299.81 |
| SPLIT OFFICE HEATING COIL | 10269.02 |
| SPLIT GNE HEATING COIL | 8775.36 |
| SPLIT GN1 HEATING COIL | 7817.38 |
| SPLIT GN2 HEATING COIL | 7808.10 |
| SPLIT GS1 HEATING COIL | 7939.58 |
| SPLIT GS2 HEATING COIL | 7995.01 |
| SPLIT MSW HEATING COIL | 21225.52 |
| SPLIT MNW HEATING COIL | 21045.26 |
| SPLIT MSE HEATING COIL | 19828.13 |
| SPLIT MNE HEATING COIL | 19650.47 |
| SPLIT MN1 HEATING COIL | 17322.32 |
| SPLIT MN2 HEATING COIL | 17299.02 |
| SPLIT MS1 HEATING COIL | 17543.16 |
| SPLIT MS2 HEATING COIL | 17519.42 |
| SPLIT TSW HEATING COIL | 12094.01 |
| SPLIT TNW HEATING COIL | 12087.83 |
| SPLIT TSE HEATING COIL | 11041.20 |
| SPLIT TNE HEATING COIL | 11033.58 |
| SPLIT TN1 HEATING COIL | 9957.59 |
| SPLIT TN2 HEATING COIL | 9925.53 |
| SPLIT TS1 HEATING COIL | 9975.97 |
| SPLIT TS2 HEATING COIL | 9944.05 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 09:17:08
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other Surfaces| None |
| Possible Shadow Receivers | |
| G SWALL SWA | GWINDOW1 S SWA | |
| G WWALL SWA | GWINDOW1 W SWA | |
| G NWALL NWA | GWINDOW1 N NWA | |
| G WWALL NWA | GWINDOW1 W NWA | |
| G SWALL SEA | GWINDOW1 S SEA | |
| G EWALL SEA | GWINDOW1 E SEA | |
| G NWALL NEA | GWINDOW1 N NEA | |
| G EWALL NEA | GWINDOW1 E NEA | |
| G NWALL N1A | GWINDOW1 N N1A | |
| G NWALL N2A | GWINDOW1 N N2A | |
| G SWALL S1A | GWINDOW1 S S1A | |
| G SWALL S2A | GWINDOW1 S S2A | |
| M WWALL SWA | MWINDOW1 W SWA | |
| M SWALL SWA | MWINDOW1 S SWA | |
| M NWALL NWA | MWINDOW1 N NWA | |
| M WWALL NWA | MWINDOW1 W NWA | |
| M EWALL SEA | MWINDOW1 E SEA | |
| M SWALL SEA | MWINDOW1 S SEA | |
| M NWALL NEA | MWINDOW1 N NEA | |
| M EWALL NEA | MWINDOW1 E NEA | |
| M NWALL N1A | MWINDOW1 N N1A | |
| M NWALL N2A | MWINDOW1 N N2A | |
| M SWALL S1A | MWINDOW1 S S1A | |
| M SWALL S2A | MWINDOW1 S S2A | |
| T WWALL SWA | TWINDOW1 W SWA | |
| T SWALL SWA | TWINDOW1 S SWA | |
| T NWALL NWA | TWINDOW1 N NWA | |
| T WWALL NWA | TWINDOW1 W NWA | |
| T EWALL SEA | TWINDOW1 E SEA | |
| T SWALL SEA | TWINDOW1 S SEA | |
| T NWALL NEA | TWINDOW1 N NEA | |
| T EWALL NEA | TWINDOW1 E NEA | |
| T NWALL N1A | TWINDOW1 N N1A | |
| T NWALL N2A | TWINDOW1 N N2A | |
| T SWALL S1A | TWINDOW1 S S1A | |
| T SWALL S2A | TWINDOW1 S S2A | |
| T EWALL C | TWINDOW14 | |
| G EWALL C | ENTRANCE DOOR | |
| M EWALL C | MWINDOW14 | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 09:17:08
Time Not Meeting the Adaptive Comfort Models during Occupied Hours| ASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 09:17:08
Version| Version ID | |
| 1 | 22.1 |
| #TimeSteps | Minutes per TimeStep {minutes} | |
| 1 | 6 | 10 |
| Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
| 1 | 1 | 20 | 2 | 8 |
| Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
| 1 | Yes | Yes | No | No | Yes | No |
| Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
| 1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
| Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
| 1 | 0.556 | 0.556 |
| Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
| 1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
| Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
| 1 | 20.90 | 15.40 | 11.90 | 14.80 | 12.70 | 15.40 | 23.30 | 26.30 | 31.20 | 30.40 | 29.80 | 27.80 |
| Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
| 1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
| Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
| 1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
| Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
| 1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
| Normal | Daylighting {dimensionless} | |
| 1 | 1.000 | 1.000 |
| Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
| 1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
| Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
| 1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
| Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
| 1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
| Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
| 1 | Tucson-Davis Monthan AFB AZ USA TMY3 WMO#=722745 | 32.17 | -110.88 | -7.00 | 809.00 | 91976 | 1.0932 |
| Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
| 1 | Correlation | NA | 21.66 | 19.30 | NA |
| Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
| 1 | ApartmentMidRise | 0.000 | City | 4.00000E-002 | 0.40000 | FullExterior | 25 | 6 |
| Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
| 1 | TARP |
| Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
| 1 | TARP |
| Value {Anisotropic} | |
| 1 | Anisotropic |
| Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
| 1 | ThirdOrderBackwardDifference |
| Simulation {Yes/No} | Carbon Dioxide Concentration | |
| 1 | No | N/A |
| Simulation {Yes/No} | Generic Contaminant Concentration | |
| 1 | No | N/A |
| Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
| 1 | No | N/A | N/A | N/A |
| Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
| 1 | RegulaFalsi |
| Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
| 1 | 0.330 | 460.000 | 6.500000E-003 |
| Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
| 1 | LowerLeftCorner | Clockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
| Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
| 1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
| Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
| 1 | 0 | 0 | 0 |
| Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
| 1 | 27 | 243 | 39 |
| Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
| 1 | G SW APARTMENT | 0.0 | 0.00 | 0.00 | 0.00 | 5.79 | 3.81 | 1.52 | 1 | 1 | 1 | 0.00 | 11.58 | 0.00 | 7.62 | 0.00 | 3.05 | 3.05 | 268.97 | TARP | TARP | 88.25 | 58.52 | 46.82 | 11.71 | 6 | 2 | 0 | Yes |
| 2 | G NW APARTMENT | 0.0 | 0.00 | 9.30 | 0.00 | 5.79 | 13.11 | 1.52 | 1 | 1 | 1 | 0.00 | 11.58 | 9.30 | 16.92 | 0.00 | 3.05 | 3.05 | 268.97 | TARP | TARP | 88.25 | 58.52 | 46.82 | 11.71 | 6 | 2 | 0 | Yes |
| 3 | OFFICE | 0.0 | 34.75 | 0.00 | 0.00 | 40.54 | 3.81 | 1.52 | 1 | 1 | 1 | 34.75 | 46.33 | 0.00 | 7.62 | 0.00 | 3.05 | 3.05 | 268.97 | TARP | TARP | 88.25 | 58.52 | 46.82 | 11.71 | 6 | 2 | 0 | Yes |
| 4 | G NE APARTMENT | 0.0 | 34.75 | 9.30 | 0.00 | 40.54 | 13.11 | 1.52 | 1 | 1 | 1 | 34.75 | 46.33 | 9.30 | 16.92 | 0.00 | 3.05 | 3.05 | 268.97 | TARP | TARP | 88.25 | 58.52 | 46.82 | 11.71 | 6 | 2 | 0 | Yes |
| 5 | G N1 APARTMENT | 0.0 | 11.58 | 9.30 | 0.00 | 17.37 | 13.11 | 1.52 | 1 | 1 | 1 | 11.58 | 23.16 | 9.30 | 16.92 | 0.00 | 3.05 | 3.05 | 268.97 | TARP | TARP | 88.25 | 35.30 | 28.24 | 7.06 | 6 | 1 | 0 | Yes |
| 6 | G N2 APARTMENT | 0.0 | 23.16 | 9.30 | 0.00 | 28.95 | 13.11 | 1.52 | 1 | 1 | 1 | 23.16 | 34.75 | 9.30 | 16.92 | 0.00 | 3.05 | 3.05 | 268.97 | TARP | TARP | 88.25 | 35.30 | 28.24 | 7.06 | 6 | 1 | 0 | Yes |
| 7 | G S1 APARTMENT | 0.0 | 11.58 | 0.00 | 0.00 | 17.37 | 3.81 | 1.52 | 1 | 1 | 1 | 11.58 | 23.16 | 0.00 | 7.62 | 0.00 | 3.05 | 3.05 | 268.97 | TARP | TARP | 88.25 | 35.30 | 28.24 | 7.06 | 6 | 1 | 0 | Yes |
| 8 | G S2 APARTMENT | 0.0 | 23.16 | 0.00 | 0.00 | 28.95 | 3.81 | 1.52 | 1 | 1 | 1 | 23.16 | 34.75 | 0.00 | 7.62 | 0.00 | 3.05 | 3.05 | 268.97 | TARP | TARP | 88.25 | 35.30 | 28.24 | 7.06 | 6 | 1 | 0 | Yes |
| 9 | M SW APARTMENT | 0.0 | 0.00 | 0.00 | 3.05 | 5.79 | 3.81 | 4.57 | 1 | 1 | 2 | 0.00 | 11.58 | 0.00 | 7.62 | 3.05 | 6.10 | 3.05 | 268.97 | TARP | TARP | 88.25 | 58.52 | 46.82 | 11.71 | 6 | 2 | 0 | Yes |
| 10 | M NW APARTMENT | 0.0 | 0.00 | 9.30 | 3.05 | 5.79 | 13.11 | 4.57 | 1 | 1 | 2 | 0.00 | 11.58 | 9.30 | 16.92 | 3.05 | 6.10 | 3.05 | 268.97 | TARP | TARP | 88.25 | 58.52 | 46.82 | 11.71 | 6 | 2 | 0 | Yes |
| 11 | M SE APARTMENT | 0.0 | 34.75 | 0.00 | 3.05 | 40.54 | 3.81 | 4.57 | 1 | 1 | 2 | 34.75 | 46.33 | 0.00 | 7.62 | 3.05 | 6.10 | 3.05 | 268.97 | TARP | TARP | 88.25 | 58.52 | 46.82 | 11.71 | 6 | 2 | 0 | Yes |
| 12 | M NE APARTMENT | 0.0 | 34.75 | 9.30 | 3.05 | 40.54 | 13.11 | 4.57 | 1 | 1 | 2 | 34.75 | 46.33 | 9.30 | 16.92 | 3.05 | 6.10 | 3.05 | 268.97 | TARP | TARP | 88.25 | 58.52 | 46.82 | 11.71 | 6 | 2 | 0 | Yes |
| 13 | M N1 APARTMENT | 0.0 | 11.58 | 9.30 | 3.05 | 17.37 | 13.11 | 4.57 | 1 | 1 | 2 | 11.58 | 23.16 | 9.30 | 16.92 | 3.05 | 6.10 | 3.05 | 268.97 | TARP | TARP | 88.25 | 35.30 | 28.24 | 7.06 | 6 | 1 | 0 | Yes |
| 14 | M N2 APARTMENT | 0.0 | 23.16 | 9.30 | 3.05 | 28.95 | 13.11 | 4.57 | 1 | 1 | 2 | 23.16 | 34.75 | 9.30 | 16.92 | 3.05 | 6.10 | 3.05 | 268.97 | TARP | TARP | 88.25 | 35.30 | 28.24 | 7.06 | 6 | 1 | 0 | Yes |
| 15 | M S1 APARTMENT | 0.0 | 11.58 | 0.00 | 3.05 | 17.37 | 3.81 | 4.57 | 1 | 1 | 2 | 11.58 | 23.16 | 0.00 | 7.62 | 3.05 | 6.10 | 3.05 | 268.97 | TARP | TARP | 88.25 | 35.30 | 28.24 | 7.06 | 6 | 1 | 0 | Yes |
| 16 | M S2 APARTMENT | 0.0 | 23.16 | 0.00 | 3.05 | 28.95 | 3.81 | 4.57 | 1 | 1 | 2 | 23.16 | 34.75 | 0.00 | 7.62 | 3.05 | 6.10 | 3.05 | 268.97 | TARP | TARP | 88.25 | 35.30 | 28.24 | 7.06 | 6 | 1 | 0 | Yes |
| 17 | T SW APARTMENT | 0.0 | 0.00 | 0.00 | 9.14 | 5.79 | 3.81 | 10.67 | 1 | 1 | 1 | 0.00 | 11.58 | 0.00 | 7.62 | 9.14 | 12.19 | 3.05 | 268.97 | TARP | TARP | 88.25 | 58.52 | 46.82 | 11.71 | 6 | 2 | 0 | Yes |
| 18 | T NW APARTMENT | 0.0 | 0.00 | 9.30 | 9.14 | 5.79 | 13.11 | 10.67 | 1 | 1 | 1 | 0.00 | 11.58 | 9.30 | 16.92 | 9.14 | 12.19 | 3.05 | 268.97 | TARP | TARP | 88.25 | 58.52 | 46.82 | 11.71 | 6 | 2 | 0 | Yes |
| 19 | T SE APARTMENT | 0.0 | 34.75 | 0.00 | 9.14 | 40.54 | 3.81 | 10.67 | 1 | 1 | 1 | 34.75 | 46.33 | 0.00 | 7.62 | 9.14 | 12.19 | 3.05 | 268.97 | TARP | TARP | 88.25 | 58.52 | 46.82 | 11.71 | 6 | 2 | 0 | Yes |
| 20 | T NE APARTMENT | 0.0 | 34.75 | 9.30 | 9.14 | 40.54 | 13.11 | 10.67 | 1 | 1 | 1 | 34.75 | 46.33 | 9.30 | 16.92 | 9.14 | 12.19 | 3.05 | 268.97 | TARP | TARP | 88.25 | 58.52 | 46.82 | 11.71 | 6 | 2 | 0 | Yes |
| 21 | T N1 APARTMENT | 0.0 | 11.58 | 9.30 | 9.14 | 17.37 | 13.11 | 10.67 | 1 | 1 | 1 | 11.58 | 23.16 | 9.30 | 16.92 | 9.14 | 12.19 | 3.05 | 268.97 | TARP | TARP | 88.25 | 35.30 | 28.24 | 7.06 | 6 | 1 | 0 | Yes |
| 22 | T N2 APARTMENT | 0.0 | 23.16 | 9.30 | 9.14 | 28.95 | 13.11 | 10.67 | 1 | 1 | 1 | 23.16 | 34.75 | 9.30 | 16.92 | 9.14 | 12.19 | 3.05 | 268.97 | TARP | TARP | 88.25 | 35.30 | 28.24 | 7.06 | 6 | 1 | 0 | Yes |
| 23 | T S1 APARTMENT | 0.0 | 11.58 | 0.00 | 9.14 | 17.37 | 3.81 | 10.67 | 1 | 1 | 1 | 11.58 | 23.16 | 0.00 | 7.62 | 9.14 | 12.19 | 3.05 | 268.97 | TARP | TARP | 88.25 | 35.30 | 28.24 | 7.06 | 6 | 1 | 0 | Yes |
| 24 | T S2 APARTMENT | 0.0 | 23.16 | 0.00 | 9.14 | 28.95 | 3.81 | 10.67 | 1 | 1 | 1 | 23.16 | 34.75 | 0.00 | 7.62 | 9.14 | 12.19 | 3.05 | 268.97 | TARP | TARP | 88.25 | 35.30 | 28.24 | 7.06 | 6 | 1 | 0 | Yes |
| 25 | T CORRIDOR | 0.0 | 0.00 | 7.62 | 9.14 | 23.16 | 8.46 | 10.67 | 1 | 1 | 1 | 0.00 | 46.33 | 7.62 | 9.30 | 9.14 | 12.19 | 3.05 | 236.69 | TARP | TARP | 77.66 | 10.22 | 9.10 | 1.11 | 12 | 1 | 0 | Yes |
| 26 | G CORRIDOR | 0.0 | 0.00 | 7.62 | 0.00 | 23.16 | 8.46 | 1.52 | 1 | 1 | 1 | 0.00 | 46.33 | 7.62 | 9.30 | 0.00 | 3.05 | 3.05 | 236.69 | TARP | TARP | 77.66 | 10.22 | 6.90 | 3.32 | 12 | 1 | 0 | Yes |
| 27 | M CORRIDOR | 0.0 | 0.00 | 7.62 | 3.05 | 23.16 | 8.46 | 4.57 | 1 | 1 | 2 | 0.00 | 46.33 | 7.62 | 9.30 | 3.05 | 6.10 | 3.05 | 236.69 | TARP | TARP | 77.66 | 10.22 | 9.10 | 1.11 | 12 | 1 | 0 | Yes |
| Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
| 1 | G SW APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 2 | G NW APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 3 | OFFICE | 88.25 | 4.7 | 18.581 | 5.382E-002 | 9.753 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 16.423 | No |
| 4 | G NE APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 5 | G N1 APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 6 | G N2 APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 7 | G S1 APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 8 | G S2 APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 9 | M SW APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 10 | M NW APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 11 | M SE APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 12 | M NE APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 13 | M N1 APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 14 | M N2 APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 15 | M S1 APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 16 | M S2 APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 17 | T SW APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 18 | T NW APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 19 | T SE APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 20 | T NE APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 21 | T N1 APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 22 | T N2 APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 23 | T S1 APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 24 | T S2 APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 25 | T CORRIDOR | 77.66 | 4.2 | 18.579 | 5.382E-002 | 4.772 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 4.772 | No |
| 26 | G CORRIDOR | 77.66 | 4.2 | 18.579 | 5.382E-002 | 4.772 | 105.256 | 0.000 | 0.000 | 0.000 | 0.000 | 110.029 | No |
| 27 | M CORRIDOR | 77.66 | 4.2 | 18.579 | 5.382E-002 | 4.772 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 4.772 | No |
| Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | |
| 1 | OCCUP_GSW | OCC_APT_SCH_WORKING_FAMILY | G SW APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 3 |
| 2 | OCCUP_GNW | OCC_APT_SCH_STAY_HOME_FAMILY | G NW APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 1 | 3 |
| 3 | OCCUP_OFFICE | OCC_OFF_W_SB_SCH | OFFICE | 88.25 | 4.7 | 4.7 | 5.382E-002 | 18.581 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 5 |
| 4 | OCCUP_GNE | OCC_APT_SCH_STAY_HOME_FAMILY | G NE APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 1 | 3 |
| 5 | OCCUP_GN1 | OCC_APT_SCH_STAY_HOME_FAMILY | G N1 APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 1 | 3 |
| 6 | OCCUP_GN2 | OCC_APT_SCH_STAY_HOME_FAMILY | G N2 APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 1 | 3 |
| 7 | OCCUP_GS1 | OCC_APT_SCH_WORKING_FAMILY | G S1 APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 3 |
| 8 | OCCUP_GS2 | OCC_APT_SCH_WORKING_FAMILY | G S2 APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 3 |
| 9 | OCCUP_MSW | OCC_APT_SCH_WORKING_FAMILY | M SW APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 3 |
| 10 | OCCUP_MNW | OCC_APT_SCH_STAY_HOME_FAMILY | M NW APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 1 | 3 |
| 11 | OCCUP_MSE | OCC_APT_SCH_WORKING_FAMILY | M SE APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 3 |
| 12 | OCCUP_MNE | OCC_APT_SCH_STAY_HOME_FAMILY | M NE APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 1 | 3 |
| 13 | OCCUP_MN1 | OCC_APT_SCH_STAY_HOME_FAMILY | M N1 APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 1 | 3 |
| 14 | OCCUP_MN2 | OCC_APT_SCH_STAY_HOME_FAMILY | M N2 APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 1 | 3 |
| 15 | OCCUP_MS1 | OCC_APT_SCH_WORKING_FAMILY | M S1 APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 3 |
| 16 | OCCUP_MS2 | OCC_APT_SCH_WORKING_FAMILY | M S2 APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 3 |
| 17 | OCCUP_TSW | OCC_APT_SCH_WORKING_FAMILY | T SW APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 3 |
| 18 | OCCUP_TNW | OCC_APT_SCH_STAY_HOME_FAMILY | T NW APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 1 | 3 |
| 19 | OCCUP_TSE | OCC_APT_SCH_WORKING_FAMILY | T SE APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 3 |
| 20 | OCCUP_TNE | OCC_APT_SCH_STAY_HOME_FAMILY | T NE APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 1 | 3 |
| 21 | OCCUP_TN1 | OCC_APT_SCH_STAY_HOME_FAMILY | T N1 APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 1 | 3 |
| 22 | OCCUP_TN2 | OCC_APT_SCH_STAY_HOME_FAMILY | T N2 APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 1 | 3 |
| 23 | OCCUP_TS1 | OCC_APT_SCH_WORKING_FAMILY | T S1 APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 3 |
| 24 | OCCUP_TS2 | OCC_APT_SCH_WORKING_FAMILY | T S2 APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 3 |
| 25 | OCCUP_T CORRIDOR | OCC_APT_SCH_CORRIDOR | T CORRIDOR | 77.66 | 4.2 | 4.2 | 5.382E-002 | 18.579 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 1 | 4 |
| 26 | OCCUP_G CORRIDOR | OCC_APT_SCH_CORRIDOR | G CORRIDOR | 77.66 | 4.2 | 4.2 | 5.382E-002 | 18.579 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 1 | 4 |
| 27 | OCCUP_M CORRIDOR | OCC_APT_SCH_CORRIDOR | M CORRIDOR | 77.66 | 4.2 | 4.2 | 5.382E-002 | 18.579 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 1 | 4 |
| Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
| 1 | LIGHTING_HARDWIRED_GSW | LTG_SCH_APARTMENT_HARDWIRED | G SW APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 2 | LIGHTING_HARDWIRED_GNW | LTG_SCH_APARTMENT_HARDWIRED | G NW APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 3 | LIGHTING_HARDWIRED_OFFICE | LTG_SCH_OFFICE | OFFICE | 88.25 | 4.7 | 860.710 | 9.753 | 181.220 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 860.710 |
| 4 | LIGHTING_HARDWIRED_GNE | LTG_SCH_APARTMENT_HARDWIRED | G NE APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 5 | LIGHTING_HARDWIRED_GN1 | LTG_SCH_APARTMENT_HARDWIRED | G N1 APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 6 | LIGHTING_HARDWIRED_GN2 | LTG_SCH_APARTMENT_HARDWIRED | G N2 APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 7 | LIGHTING_HARDWIRED_GS1 | LTG_SCH_APARTMENT_HARDWIRED | G S1 APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 8 | LIGHTING_HARDWIRED_GS2 | LTG_SCH_APARTMENT_HARDWIRED | G S2 APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 9 | LIGHTING_HARDWIRED_MSW | LTG_SCH_APARTMENT_HARDWIRED | M SW APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 10 | LIGHTING_HARDWIRED_MNW | LTG_SCH_APARTMENT_HARDWIRED | M NW APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 11 | LIGHTING_HARDWIRED_MSE | LTG_SCH_APARTMENT_HARDWIRED | M SE APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 12 | LIGHTING_HARDWIRED_MNE | LTG_SCH_APARTMENT_HARDWIRED | M NE APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 13 | LIGHTING_HARDWIRED_MN1 | LTG_SCH_APARTMENT_HARDWIRED | M N1 APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 14 | LIGHTING_HARDWIRED_MN2 | LTG_SCH_APARTMENT_HARDWIRED | M N2 APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 15 | LIGHTING_HARDWIRED_MS1 | LTG_SCH_APARTMENT_HARDWIRED | M S1 APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 16 | LIGHTING_HARDWIRED_MS2 | LTG_SCH_APARTMENT_HARDWIRED | M S2 APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 17 | LIGHTING_HARDWIRED_TSW | LTG_SCH_APARTMENT_HARDWIRED | T SW APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 18 | LIGHTING_HARDWIRED_TNW | LTG_SCH_APARTMENT_HARDWIRED | T NW APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 19 | LIGHTING_HARDWIRED_TSE | LTG_SCH_APARTMENT_HARDWIRED | T SE APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 20 | LIGHTING_HARDWIRED_TNE | LTG_SCH_APARTMENT_HARDWIRED | T NE APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 21 | LIGHTING_HARDWIRED_TN1 | LTG_SCH_APARTMENT_HARDWIRED | T N1 APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 22 | LIGHTING_HARDWIRED_TN2 | LTG_SCH_APARTMENT_HARDWIRED | T N2 APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 23 | LIGHTING_HARDWIRED_TS1 | LTG_SCH_APARTMENT_HARDWIRED | T S1 APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 24 | LIGHTING_HARDWIRED_TS2 | LTG_SCH_APARTMENT_HARDWIRED | T S2 APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 25 | LIGHTING_HARDWIRED_GC | LTG_SCH_CORRIDOR | G CORRIDOR | 77.66 | 4.2 | 370.628 | 4.772 | 88.667 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 370.628 |
| 26 | LIGHTING_HARDWIRED_MC | LTG_SCH_CORRIDOR | M CORRIDOR | 77.66 | 4.2 | 370.628 | 4.772 | 88.667 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 370.628 |
| 27 | LIGHTING_HARDWIRED_TC | LTG_SCH_CORRIDOR | T CORRIDOR | 77.66 | 4.2 | 370.628 | 4.772 | 88.667 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 370.628 |
| 28 | LIGHTING_PLUGIN_GSW | LTG_SCH_APARTMENT_PLUGIN | G SW APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| 29 | LIGHTING_PLUGIN_GNW | LTG_SCH_APARTMENT_PLUGIN | G NW APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| 30 | LIGHTING_PLUGIN_GNE | LTG_SCH_APARTMENT_PLUGIN | G NE APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| 31 | LIGHTING_PLUGIN_GN1 | LTG_SCH_APARTMENT_PLUGIN | G N1 APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| 32 | LIGHTING_PLUGIN_GN2 | LTG_SCH_APARTMENT_PLUGIN | G N2 APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| 33 | LIGHTING_PLUGIN_GS1 | LTG_SCH_APARTMENT_PLUGIN | G S1 APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| 34 | LIGHTING_PLUGIN_GS2 | LTG_SCH_APARTMENT_PLUGIN | G S2 APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| 35 | LIGHTING_PLUGIN_MSW | LTG_SCH_APARTMENT_PLUGIN | M SW APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| 36 | LIGHTING_PLUGIN_MNW | LTG_SCH_APARTMENT_PLUGIN | M NW APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| 37 | LIGHTING_PLUGIN_MSE | LTG_SCH_APARTMENT_PLUGIN | M SE APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| 38 | LIGHTING_PLUGIN_MNE | LTG_SCH_APARTMENT_PLUGIN | M NE APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| 39 | LIGHTING_PLUGIN_MN1 | LTG_SCH_APARTMENT_PLUGIN | M N1 APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| 40 | LIGHTING_PLUGIN_MN2 | LTG_SCH_APARTMENT_PLUGIN | M N2 APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| 41 | LIGHTING_PLUGIN_MS1 | LTG_SCH_APARTMENT_PLUGIN | M S1 APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| 42 | LIGHTING_PLUGIN_MS2 | LTG_SCH_APARTMENT_PLUGIN | M S2 APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| 43 | LIGHTING_PLUGIN_TSW | LTG_SCH_APARTMENT_PLUGIN | T SW APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| 44 | LIGHTING_PLUGIN_TNW | LTG_SCH_APARTMENT_PLUGIN | T NW APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| 45 | LIGHTING_PLUGIN_TSE | LTG_SCH_APARTMENT_PLUGIN | T SE APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| 46 | LIGHTING_PLUGIN_TNE | LTG_SCH_APARTMENT_PLUGIN | T NE APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| 47 | LIGHTING_PLUGIN_TN1 | LTG_SCH_APARTMENT_PLUGIN | T N1 APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| 48 | LIGHTING_PLUGIN_TN2 | LTG_SCH_APARTMENT_PLUGIN | T N2 APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| 49 | LIGHTING_PLUGIN_TS1 | LTG_SCH_APARTMENT_PLUGIN | T S1 APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| 50 | LIGHTING_PLUGIN_TS2 | LTG_SCH_APARTMENT_PLUGIN | T S2 APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
| 1 | PLUG_GSW | EQP_APT_SCH | G SW APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 2 | PLUG_GNW | EQP_APT_SCH | G NW APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 3 | PLUG_OFFICE | EQP_OFF_SCH | OFFICE | 88.25 | 4.7 | 588.623 | 6.670 | 123.933 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 588.623 |
| 4 | PLUG_GNE | EQP_APT_SCH | G NE APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 5 | PLUG_GN1 | EQP_APT_SCH | G N1 APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 6 | PLUG_GN2 | EQP_APT_SCH | G N2 APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 7 | PLUG_GS1 | EQP_APT_SCH | G S1 APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 8 | PLUG_GS2 | EQP_APT_SCH | G S2 APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 9 | PLUG_MSW | EQP_APT_SCH | M SW APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 10 | PLUG_MNW | EQP_APT_SCH | M NW APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 11 | PLUG_MSE | EQP_APT_SCH | M SE APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 12 | PLUG_MNE | EQP_APT_SCH | M NE APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 13 | PLUG_MN1 | EQP_APT_SCH | M N1 APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 14 | PLUG_MN2 | EQP_APT_SCH | M N2 APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 15 | PLUG_MS1 | EQP_APT_SCH | M S1 APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 16 | PLUG_MS2 | EQP_APT_SCH | M S2 APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 17 | PLUG_TSW | EQP_APT_SCH | T SW APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 18 | PLUG_TNW | EQP_APT_SCH | T NW APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 19 | PLUG_TSE | EQP_APT_SCH | T SE APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 20 | PLUG_TNE | EQP_APT_SCH | T NE APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 21 | PLUG_TN1 | EQP_APT_SCH | T N1 APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 22 | PLUG_TN2 | EQP_APT_SCH | T N2 APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 23 | PLUG_TS1 | EQP_APT_SCH | T S1 APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 24 | PLUG_TS2 | EQP_APT_SCH | T S2 APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 25 | G CORRIDOR_ELEVATORS_EQUIP | BLDG_ELEVATORS | G CORRIDOR | 77.66 | 4.2 | 8012.150 | 103.170 | 1916.782 | 0.000 | 0.000 | 0.950 | 5.000E-002 | ElevatorLift | 961.458 | 4006.075 |
| 26 | ELEVATORS_LIGHTS_FAN | ELEV_LIGHT_FAN_SCH_24_7 | G CORRIDOR | 77.66 | 4.2 | 162.000 | 2.086 | 38.756 | 0.000 | 0.000 | 0.950 | 5.000E-002 | ElevatorLightsFan | 162.000 | 162.000 |
| Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
| 1 | PolygonClipping | Periodic | 20 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
| Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
| 1 | WaterHeater:Mixed | G SW APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.496 | 0.7729 |
| 2 | WaterHeater:Mixed | G NW APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.496 | 0.7729 |
| 3 | WaterHeater:Mixed | G NE APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.496 | 0.7729 |
| 4 | WaterHeater:Mixed | G N1 APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.496 | 0.7729 |
| 5 | WaterHeater:Mixed | G N2 APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.496 | 0.7729 |
| 6 | WaterHeater:Mixed | G S1 APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.496 | 0.7729 |
| 7 | WaterHeater:Mixed | G S2 APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.496 | 0.7729 |
| 8 | WaterHeater:Mixed | M SW APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.498 | 0.7911 |
| 9 | WaterHeater:Mixed | M NW APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.498 | 0.7911 |
| 10 | WaterHeater:Mixed | M SE APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.498 | 0.7911 |
| 11 | WaterHeater:Mixed | M NE APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.498 | 0.7911 |
| 12 | WaterHeater:Mixed | M N1 APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.498 | 0.7911 |
| 13 | WaterHeater:Mixed | M N2 APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.498 | 0.7911 |
| 14 | WaterHeater:Mixed | M S1 APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.498 | 0.7911 |
| 15 | WaterHeater:Mixed | M S2 APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.498 | 0.7911 |
| 16 | WaterHeater:Mixed | T SW APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.496 | 0.7729 |
| 17 | WaterHeater:Mixed | T NW APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.496 | 0.7729 |
| 18 | WaterHeater:Mixed | T SE APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.496 | 0.7729 |
| 19 | WaterHeater:Mixed | T NE APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.496 | 0.7729 |
| 20 | WaterHeater:Mixed | T N1 APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.496 | 0.7729 |
| 21 | WaterHeater:Mixed | T N2 APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.496 | 0.7729 |
| 22 | WaterHeater:Mixed | T S1 APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.496 | 0.7729 |
| 23 | WaterHeater:Mixed | T S2 APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.496 | 0.7729 |
| Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
| 1 | G SWALL SWA | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 2 | GWINDOW1 S SWA | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 3 | G WWALL SWA | 0 | 154.67 | 58.21 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 4 | GWINDOW1 W SWA | 0 | 154.67 | 58.21 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 5 | G NIWALL SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 6 | G EIWALL SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 7 | G GFLOOR SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 8 | G CEILIN SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 9 | G INTERNALMASS SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 10 | G NWALL NWA | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 11 | GWINDOW1 N NWA | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 12 | G WWALL NWA | 0 | 154.67 | 58.21 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 13 | GWINDOW1 W NWA | 0 | 154.67 | 58.21 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 14 | G SIWALL NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 15 | G EIWALL NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 16 | G GFLOOR NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 17 | G CEILIN NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 18 | G INTERNALMASS NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 19 | G SWALL SEA | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 20 | GWINDOW1 S SEA | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 21 | G EWALL SEA | 0 | 154.67 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 22 | GWINDOW1 E SEA | 0 | 154.67 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 23 | G NIWALL SEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 24 | iz-G EIWALL S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 25 | G GFLOOR SEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 26 | G CEILIN SEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 27 | G INTERNALMASS SEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 28 | G NWALL NEA | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 29 | GWINDOW1 N NEA | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 30 | G EWALL NEA | 0 | 154.67 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 31 | GWINDOW1 E NEA | 0 | 154.67 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 32 | G SIWALL NEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 33 | iz-G EIWALL N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 34 | G GFLOOR NEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 35 | G CEILIN NEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 36 | G INTERNALMASS NEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 37 | G NWALL N1A | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 3 | No | No |
| 38 | GWINDOW1 N N1A | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 2 | No | No |
| 39 | G SIWALL N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 40 | G EIWALL N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 41 | iz-G EIWALL NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 42 | G GFLOOR N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 43 | G CEILIN N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 44 | G INTERNALMASS N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 45 | G NWALL N2A | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 3 | No | No |
| 46 | GWINDOW1 N N2A | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 2 | No | No |
| 47 | G SIWALL N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 48 | G EIWALL N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 49 | iz-G EIWALL N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 50 | G GFLOOR N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 51 | G CEILIN N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 52 | G INTERNALMASS N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 53 | G SWALL S1A | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 3 | No | No |
| 54 | GWINDOW1 S S1A | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 2 | No | No |
| 55 | G NIWALL S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 56 | G EIWALL S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 57 | iz-G EIWALL SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 58 | G GFLOOR S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 59 | G CEILIN S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 60 | G INTERNALMASS S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 61 | G SWALL S2A | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 3 | No | No |
| 62 | GWINDOW1 S S2A | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 2 | No | No |
| 63 | G NIWALL S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 64 | G EIWALL S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 65 | iz-G EIWALL S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 66 | G GFLOOR S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 67 | G CEILIN S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 68 | G INTERNALMASS S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 69 | M WWALL SWA | 0 | 154.67 | 58.21 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 70 | MWINDOW1 W SWA | 0 | 154.67 | 58.21 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 71 | M SWALL SWA | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 72 | MWINDOW1 S SWA | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 73 | M NIWALL SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 74 | M EIWALL SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 75 | M GFLOOR SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 76 | M CEILIN SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 77 | M INTERNALMASS SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 78 | M NWALL NWA | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 79 | MWINDOW1 N NWA | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 80 | M WWALL NWA | 0 | 154.67 | 58.21 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 81 | MWINDOW1 W NWA | 0 | 154.67 | 58.21 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 82 | M SIWALL NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 83 | M EIWALL NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 84 | M GFLOOR NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 85 | M CEILIN NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 86 | M INTERNALMASS NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 87 | M EWALL SEA | 0 | 154.67 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 88 | MWINDOW1 E SEA | 0 | 154.67 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 89 | M SWALL SEA | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 90 | MWINDOW1 S SEA | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 91 | M NIWALL SEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 92 | iz-M EIWALL S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 93 | M GFLOOR SEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 94 | M CEILIN SEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 95 | M INTERNALMASS SEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 96 | M NWALL NEA | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 97 | MWINDOW1 N NEA | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 98 | M EWALL NEA | 0 | 154.67 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 99 | MWINDOW1 E NEA | 0 | 154.67 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 100 | M SIWALL NEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 101 | iz-M EIWALL N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 102 | M GFLOOR NEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 103 | M CEILIN NEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 104 | M INTERNALMASS NEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 105 | M NWALL N1A | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 3 | No | No |
| 106 | MWINDOW1 N N1A | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 2 | No | No |
| 107 | M SIWALL N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 108 | M EIWALL N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 109 | iz-M EIWALL NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 110 | M GFLOOR N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 111 | M CEILIN N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 112 | M INTERNALMASS N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 113 | M NWALL N2A | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 3 | No | No |
| 114 | MWINDOW1 N N2A | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 2 | No | No |
| 115 | M SIWALL N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 116 | M EIWALL N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 117 | iz-M EIWALL N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 118 | M GFLOOR N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 119 | M CEILIN N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 120 | M INTERNALMASS N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 121 | M SWALL S1A | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 3 | No | No |
| 122 | MWINDOW1 S S1A | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 2 | No | No |
| 123 | M NIWALL S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 124 | M EIWALL S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 125 | iz-M EIWALL SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 126 | M GFLOOR S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 127 | M CEILIN S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 128 | M INTERNALMASS S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 129 | M SWALL S2A | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 3 | No | No |
| 130 | MWINDOW1 S S2A | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 2 | No | No |
| 131 | M NIWALL S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 132 | M EIWALL S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 133 | iz-M EIWALL S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 134 | M GFLOOR S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 135 | M CEILIN S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 136 | M INTERNALMASS S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 137 | T WWALL SWA | 0 | 154.67 | 58.21 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 138 | TWINDOW1 W SWA | 0 | 154.67 | 58.21 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 139 | T SWALL SWA | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 140 | TWINDOW1 S SWA | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 141 | T NIWALL SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 142 | T EIWALL SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 143 | T GFLOOR SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 144 | T ROOF SWA | 0 | 783.65 | 155.90 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 145 | T INTERNALMASS SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 146 | T NWALL NWA | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 147 | TWINDOW1 N NWA | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 148 | T WWALL NWA | 0 | 154.67 | 58.21 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 149 | TWINDOW1 W NWA | 0 | 154.67 | 58.21 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 150 | T SIWALL NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 151 | T EIWALL NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 152 | T GFLOOR NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 153 | T ROOF NWA | 0 | 783.65 | 155.90 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 154 | T INTERNALMASS NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 155 | T EWALL SEA | 0 | 154.67 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 156 | TWINDOW1 E SEA | 0 | 154.67 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 157 | T SWALL SEA | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 158 | TWINDOW1 S SEA | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 159 | T NIWALL SEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 160 | iz-T EIWALL S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 161 | T GFLOOR SEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 162 | T ROOF SEA | 0 | 783.65 | 155.90 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 163 | T INTERNALMASS SEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 164 | T NWALL NEA | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 165 | TWINDOW1 N NEA | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 166 | T EWALL NEA | 0 | 154.67 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 167 | TWINDOW1 E NEA | 0 | 154.67 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 168 | T SIWALL NEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 169 | iz-T EIWALL N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 170 | T GFLOOR NEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 171 | T ROOF NEA | 0 | 783.65 | 155.90 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 172 | T INTERNALMASS NEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 173 | T NWALL N1A | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 3 | No | No |
| 174 | TWINDOW1 N N1A | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 2 | No | No |
| 175 | T SIWALL N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 176 | T EIWALL N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 177 | iz-T EIWALL NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 178 | T GFLOOR N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 179 | T ROOF N1A | 0 | 783.65 | 155.90 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 180 | T INTERNALMASS N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 181 | T NWALL N2A | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 3 | No | No |
| 182 | TWINDOW1 N N2A | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 2 | No | No |
| 183 | T SIWALL N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 184 | T EIWALL N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 185 | iz-T EIWALL N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 186 | T GFLOOR N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 187 | T ROOF N2A | 0 | 783.65 | 155.90 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 188 | T INTERNALMASS N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 189 | T SWALL S1A | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 3 | No | No |
| 190 | TWINDOW1 S S1A | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 2 | No | No |
| 191 | T NIWALL S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 192 | T EIWALL S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 193 | iz-T EIWALL SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 194 | T GFLOOR S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 195 | T ROOF S1A | 0 | 783.65 | 155.90 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 196 | T INTERNALMASS S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 197 | T SWALL S2A | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 3 | No | No |
| 198 | TWINDOW1 S S2A | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 2 | No | No |
| 199 | T NIWALL S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 200 | T EIWALL S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 201 | iz-T EIWALL S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 202 | T GFLOOR S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 203 | T ROOF S2A | 0 | 783.65 | 155.90 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 204 | T INTERNALMASS S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 205 | T WWALL C | 0 | 154.67 | 58.21 | 12.19 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 3 | No | No |
| 206 | T EWALL C | 0 | 154.67 | 123.02 | 12.19 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 3 | No | No |
| 207 | TWINDOW14 | 0 | 154.67 | 123.02 | 12.19 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 2 | No | No |
| 208 | iz-T NIWALL SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 209 | iz-T NIWALL S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 210 | iz-T NIWALL S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 211 | iz-T NIWALL SEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 212 | iz-T SIWALL NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 213 | iz-T SIWALL N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 214 | iz-T SIWALL N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 215 | iz-T SIWALL NEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 216 | T FLOOR C | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 217 | T ROOF C | 0 | 783.65 | 155.90 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 218 | G WWALL C | 0 | 154.67 | 58.21 | 12.19 | 0 | 3.05 | 3.35 | 3.24 | 0.32 | 4 | No | No |
| 219 | G EWALL C | 0 | 154.67 | 123.02 | 12.19 | 0 | 3.05 | 3.35 | 3.24 | 0.32 | 4 | No | No |
| 220 | ENTRANCE DOOR | 0 | 154.67 | 123.02 | 12.19 | 0 | 3.05 | 3.35 | 3.24 | 0.32 | 1 | No | No |
| 221 | iz-G NIWALL SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.32 | 0 | No | No |
| 222 | iz-G NIWALL S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.32 | 0 | No | No |
| 223 | iz-G NIWALL S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.32 | 0 | No | No |
| 224 | iz-G NIWALL SEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.32 | 0 | No | No |
| 225 | iz-G SIWALL NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.32 | 0 | No | No |
| 226 | iz-G SIWALL N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.32 | 0 | No | No |
| 227 | iz-G SIWALL N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.32 | 0 | No | No |
| 228 | iz-G SIWALL NEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.32 | 0 | No | No |
| 229 | G FLOOR C | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.32 | 0 | No | No |
| 230 | G CEILING C | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.32 | 0 | No | No |
| 231 | M WWALL C | 0 | 154.67 | 58.21 | 12.19 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 4 | No | No |
| 232 | M EWALL C | 0 | 154.67 | 123.02 | 12.19 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 3 | No | No |
| 233 | MWINDOW14 | 0 | 154.67 | 123.02 | 12.19 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 2 | No | No |
| 234 | iz-M NIWALL SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 235 | iz-M NIWALL S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 236 | iz-M NIWALL S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 237 | iz-M NIWALL SEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 238 | iz-M SIWALL NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 239 | iz-M SIWALL N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 240 | iz-M SIWALL N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 241 | iz-M SIWALL NEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 242 | M FLOOR C | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 243 | M CEILING C | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
| 1 | INFIL_GSW | INF_APT_SCH | G SW APARTMENT | 88.25 | 2.5 | 6.000E-002 | 6.799E-004 | 1.025E-003 | 0.803 | 0.000 | 0.000 | 0.224 | 0.000 |
| 2 | INFIL_GNW | INF_APT_SCH | G NW APARTMENT | 88.25 | 2.5 | 6.000E-002 | 6.799E-004 | 1.025E-003 | 0.803 | 0.000 | 0.000 | 0.224 | 0.000 |
| 3 | INFIL_OFFICE | INF_OFF_SCH | OFFICE | 88.25 | 4.7 | 6.000E-002 | 6.799E-004 | 1.025E-003 | 0.803 | 0.000 | 0.000 | 0.224 | 0.000 |
| 4 | INFIL_GNE | INF_APT_SCH | G NE APARTMENT | 88.25 | 2.5 | 6.000E-002 | 6.799E-004 | 1.025E-003 | 0.803 | 0.000 | 0.000 | 0.224 | 0.000 |
| 5 | INFIL_GN1 | INF_APT_SCH | G N1 APARTMENT | 88.25 | 2.5 | 3.619E-002 | 4.101E-004 | 1.025E-003 | 0.484 | 0.000 | 0.000 | 0.224 | 0.000 |
| 6 | INFIL_GN2 | INF_APT_SCH | G N2 APARTMENT | 88.25 | 2.5 | 3.619E-002 | 4.101E-004 | 1.025E-003 | 0.484 | 0.000 | 0.000 | 0.224 | 0.000 |
| 7 | INFIL_GS1 | INF_APT_SCH | G S1 APARTMENT | 88.25 | 2.5 | 3.619E-002 | 4.101E-004 | 1.025E-003 | 0.484 | 0.000 | 0.000 | 0.224 | 0.000 |
| 8 | INFIL_GS2 | INF_APT_SCH | G S2 APARTMENT | 88.25 | 2.5 | 3.619E-002 | 4.101E-004 | 1.025E-003 | 0.484 | 0.000 | 0.000 | 0.224 | 0.000 |
| 9 | INFIL_MSW | INF_APT_SCH | M SW APARTMENT | 88.25 | 2.5 | 6.000E-002 | 6.799E-004 | 1.025E-003 | 0.803 | 0.000 | 0.000 | 0.224 | 0.000 |
| 10 | INFIL_MNW | INF_APT_SCH | M NW APARTMENT | 88.25 | 2.5 | 6.000E-002 | 6.799E-004 | 1.025E-003 | 0.803 | 0.000 | 0.000 | 0.224 | 0.000 |
| 11 | INFIL_MSE | INF_APT_SCH | M SE APARTMENT | 88.25 | 2.5 | 6.000E-002 | 6.799E-004 | 1.025E-003 | 0.803 | 0.000 | 0.000 | 0.224 | 0.000 |
| 12 | INFIL_MNE | INF_APT_SCH | M NE APARTMENT | 88.25 | 2.5 | 6.000E-002 | 6.799E-004 | 1.025E-003 | 0.803 | 0.000 | 0.000 | 0.224 | 0.000 |
| 13 | INFIL_MN1 | INF_APT_SCH | M N1 APARTMENT | 88.25 | 2.5 | 3.619E-002 | 4.101E-004 | 1.025E-003 | 0.484 | 0.000 | 0.000 | 0.224 | 0.000 |
| 14 | INFIL_MN2 | INF_APT_SCH | M N2 APARTMENT | 88.25 | 2.5 | 3.619E-002 | 4.101E-004 | 1.025E-003 | 0.484 | 0.000 | 0.000 | 0.224 | 0.000 |
| 15 | INFIL_MS1 | INF_APT_SCH | M S1 APARTMENT | 88.25 | 2.5 | 3.619E-002 | 4.101E-004 | 1.025E-003 | 0.484 | 0.000 | 0.000 | 0.224 | 0.000 |
| 16 | INFIL_MS2 | INF_APT_SCH | M S2 APARTMENT | 88.25 | 2.5 | 3.619E-002 | 4.101E-004 | 1.025E-003 | 0.484 | 0.000 | 0.000 | 0.224 | 0.000 |
| 17 | INFIL_SW | INF_APT_SCH | T SW APARTMENT | 88.25 | 2.5 | 6.000E-002 | 6.799E-004 | 4.088E-004 | 0.803 | 0.000 | 0.000 | 0.224 | 0.000 |
| 18 | INFIL_NW | INF_APT_SCH | T NW APARTMENT | 88.25 | 2.5 | 6.000E-002 | 6.799E-004 | 4.088E-004 | 0.803 | 0.000 | 0.000 | 0.224 | 0.000 |
| 19 | INFIL_SE | INF_APT_SCH | T SE APARTMENT | 88.25 | 2.5 | 6.000E-002 | 6.799E-004 | 4.088E-004 | 0.803 | 0.000 | 0.000 | 0.224 | 0.000 |
| 20 | INFIL_NE | INF_APT_SCH | T NE APARTMENT | 88.25 | 2.5 | 6.000E-002 | 6.799E-004 | 4.088E-004 | 0.803 | 0.000 | 0.000 | 0.224 | 0.000 |
| 21 | INFIL_TN1 | INF_APT_SCH | T N1 APARTMENT | 88.25 | 2.5 | 3.619E-002 | 4.101E-004 | 2.929E-004 | 0.484 | 0.000 | 0.000 | 0.224 | 0.000 |
| 22 | INFIL_TN2 | INF_APT_SCH | T N2 APARTMENT | 88.25 | 2.5 | 3.619E-002 | 4.101E-004 | 2.929E-004 | 0.484 | 0.000 | 0.000 | 0.224 | 0.000 |
| 23 | INFIL_TS1 | INF_APT_SCH | T S1 APARTMENT | 88.25 | 2.5 | 3.619E-002 | 4.101E-004 | 2.929E-004 | 0.484 | 0.000 | 0.000 | 0.224 | 0.000 |
| 24 | INFIL_TS2 | INF_APT_SCH | T S2 APARTMENT | 88.25 | 2.5 | 3.619E-002 | 4.101E-004 | 2.929E-004 | 0.484 | 0.000 | 0.000 | 0.224 | 0.000 |
| 25 | INFIL_GC | INF_COR_SCH | G CORRIDOR | 77.66 | 4.2 | 1.048E-002 | 1.349E-004 | 1.025E-003 | 0.159 | 0.000 | 0.000 | 0.224 | 0.000 |
| 26 | DOOR_INFIL_GC | INFIL_DOOR_OPENING_SCH | G CORRIDOR | 77.66 | 4.2 | 0.521 | 6.703E-003 | 5.094E-002 | 7.917 | 1.000 | 0.000 | 0.000 | 0.000 |
| 27 | INFIL_MC | INF_COR_SCH | M CORRIDOR | 77.66 | 4.2 | 1.048E-002 | 1.349E-004 | 1.025E-003 | 0.159 | 0.000 | 0.000 | 0.224 | 0.000 |
| 28 | INFIL_TC | INF_COR_SCH | T CORRIDOR | 77.66 | 4.2 | 1.048E-002 | 1.349E-004 | 1.192E-004 | 0.159 | 0.000 | 0.000 | 0.224 | 0.000 |
| Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
| 1 | G SW APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | G SW APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 2 | G NW APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | G NW APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 3 | G NE APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | G NE APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 4 | G N1 APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | G N1 APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 5 | G N2 APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | G N2 APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 6 | G S1 APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | G S1 APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 7 | G S2 APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | G S2 APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 8 | M SW APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | M SW APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 9 | M NW APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | M NW APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 10 | M SE APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | M SE APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 11 | M NE APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | M NE APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 12 | M N1 APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | M N1 APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 13 | M N2 APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | M N2 APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 14 | M S1 APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | M S1 APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 15 | M S2 APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | M S2 APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 16 | T SW APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | T SW APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 17 | T NW APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | T NW APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 18 | T SE APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | T SE APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 19 | T NE APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | T NE APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 20 | T N1 APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | T N1 APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 21 | T N2 APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | T N2 APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 22 | T S1 APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | T S1 APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 23 | T S2 APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | T S2 APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| Simple | |
| 1 | Simple |
| Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
| 1 | G SW APARTMENT | Mixing/Well-Stirred |
| 2 | G NW APARTMENT | Mixing/Well-Stirred |
| 3 | OFFICE | Mixing/Well-Stirred |
| 4 | G NE APARTMENT | Mixing/Well-Stirred |
| 5 | G N1 APARTMENT | Mixing/Well-Stirred |
| 6 | G N2 APARTMENT | Mixing/Well-Stirred |
| 7 | G S1 APARTMENT | Mixing/Well-Stirred |
| 8 | G S2 APARTMENT | Mixing/Well-Stirred |
| 9 | M SW APARTMENT | Mixing/Well-Stirred |
| 10 | M NW APARTMENT | Mixing/Well-Stirred |
| 11 | M SE APARTMENT | Mixing/Well-Stirred |
| 12 | M NE APARTMENT | Mixing/Well-Stirred |
| 13 | M N1 APARTMENT | Mixing/Well-Stirred |
| 14 | M N2 APARTMENT | Mixing/Well-Stirred |
| 15 | M S1 APARTMENT | Mixing/Well-Stirred |
| 16 | M S2 APARTMENT | Mixing/Well-Stirred |
| 17 | T SW APARTMENT | Mixing/Well-Stirred |
| 18 | T NW APARTMENT | Mixing/Well-Stirred |
| 19 | T SE APARTMENT | Mixing/Well-Stirred |
| 20 | T NE APARTMENT | Mixing/Well-Stirred |
| 21 | T N1 APARTMENT | Mixing/Well-Stirred |
| 22 | T N2 APARTMENT | Mixing/Well-Stirred |
| 23 | T S1 APARTMENT | Mixing/Well-Stirred |
| 24 | T S2 APARTMENT | Mixing/Well-Stirred |
| 25 | T CORRIDOR | Mixing/Well-Stirred |
| 26 | G CORRIDOR | Mixing/Well-Stirred |
| 27 | M CORRIDOR | Mixing/Well-Stirred |
| No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
| 1 | NoMultizoneOrDistribution |
| Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
| 1 | 1.000 | 1.000 | 1.000 | 1.000 |
| Value | |
| 1 | 6 |
| Sizing Factor ID | Value | |
| 1 | Global | 1.2000 |
| 2 | Zone G SW APARTMENT | 1.2000 |
| 3 | Zone G NW APARTMENT | 1.2000 |
| 4 | Zone OFFICE | 1.2000 |
| 5 | Zone G NE APARTMENT | 1.2000 |
| 6 | Zone G N1 APARTMENT | 1.2000 |
| 7 | Zone G N2 APARTMENT | 1.2000 |
| 8 | Zone G S1 APARTMENT | 1.2000 |
| 9 | Zone G S2 APARTMENT | 1.2000 |
| 10 | Zone M SW APARTMENT | 1.2000 |
| 11 | Zone M NW APARTMENT | 1.2000 |
| 12 | Zone M SE APARTMENT | 1.2000 |
| 13 | Zone M NE APARTMENT | 1.2000 |
| 14 | Zone M N1 APARTMENT | 1.2000 |
| 15 | Zone M N2 APARTMENT | 1.2000 |
| 16 | Zone M S1 APARTMENT | 1.2000 |
| 17 | Zone M S2 APARTMENT | 1.2000 |
| 18 | Zone T SW APARTMENT | 1.2000 |
| 19 | Zone T NW APARTMENT | 1.2000 |
| 20 | Zone T SE APARTMENT | 1.2000 |
| 21 | Zone T NE APARTMENT | 1.2000 |
| 22 | Zone T N1 APARTMENT | 1.2000 |
| 23 | Zone T N2 APARTMENT | 1.2000 |
| 24 | Zone T S1 APARTMENT | 1.2000 |
| 25 | Zone T S2 APARTMENT | 1.2000 |
| Sizing Factor ID | Value | |
| 1 | Global | 1.2000 |
| 2 | Zone G SW APARTMENT | 1.2000 |
| 3 | Zone G NW APARTMENT | 1.2000 |
| 4 | Zone OFFICE | 1.2000 |
| 5 | Zone G NE APARTMENT | 1.2000 |
| 6 | Zone G N1 APARTMENT | 1.2000 |
| 7 | Zone G N2 APARTMENT | 1.2000 |
| 8 | Zone G S1 APARTMENT | 1.2000 |
| 9 | Zone G S2 APARTMENT | 1.2000 |
| 10 | Zone M SW APARTMENT | 1.2000 |
| 11 | Zone M NW APARTMENT | 1.2000 |
| 12 | Zone M SE APARTMENT | 1.2000 |
| 13 | Zone M NE APARTMENT | 1.2000 |
| 14 | Zone M N1 APARTMENT | 1.2000 |
| 15 | Zone M N2 APARTMENT | 1.2000 |
| 16 | Zone M S1 APARTMENT | 1.2000 |
| 17 | Zone M S2 APARTMENT | 1.2000 |
| 18 | Zone T SW APARTMENT | 1.2000 |
| 19 | Zone T NW APARTMENT | 1.2000 |
| 20 | Zone T SE APARTMENT | 1.2000 |
| 21 | Zone T NE APARTMENT | 1.2000 |
| 22 | Zone T N1 APARTMENT | 1.2000 |
| 23 | Zone T N2 APARTMENT | 1.2000 |
| 24 | Zone T S1 APARTMENT | 1.2000 |
| 25 | Zone T S2 APARTMENT | 1.2000 |
| Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
| 1 | G SW APARTMENT | Cooling | 4527.82765 | 5433.39318 | 0.35375 | 0.42450 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 35.61300 | 5.62306E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 2 | G SW APARTMENT | Heating | 957.70816 | 1149.24979 | 4.54551E-002 | 5.45461E-002 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 04:00:00 | 0.50000 | 4.31558E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 3 | G NW APARTMENT | Cooling | 4476.90276 | 5372.28331 | 0.34970 | 0.41964 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 35.61300 | 5.62306E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 4 | G NW APARTMENT | Heating | 829.65748 | 995.58898 | 3.93782E-002 | 4.72539E-002 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 04:00:00 | 0.50000 | 4.31558E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 5 | OFFICE | Cooling | 4671.98363 | 5606.38035 | 0.37756 | 0.45307 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:20:00 | 34.23867 | 5.62096E-003 | 88.24927 | 4.74953 | 3.81060E-002 | 0.00000 |
| 6 | OFFICE | Heating | 1429.94965 | 1715.93958 | 6.78698E-002 | 8.14438E-002 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 18:50:00 | 0.50000 | 4.31558E-003 | 88.24927 | 4.74953 | 3.81060E-002 | 0.00000 |
| 7 | G NE APARTMENT | Cooling | 4212.76767 | 5055.32120 | 0.32865 | 0.39438 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 35.61300 | 5.62306E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 8 | G NE APARTMENT | Heating | 832.55842 | 999.07010 | 3.95159E-002 | 4.74191E-002 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 04:00:00 | 0.50000 | 4.31558E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 9 | G N1 APARTMENT | Cooling | 3731.89719 | 4478.27663 | 0.29020 | 0.34824 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 35.61300 | 5.62306E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 10 | G N1 APARTMENT | Heating | 420.42957 | 504.51548 | 1.99552E-002 | 2.59546E-002 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 04:00:00 | 0.50000 | 4.31558E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 11 | G N2 APARTMENT | Cooling | 3727.20318 | 4472.64382 | 0.28983 | 0.34779 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 35.61300 | 5.62306E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 12 | G N2 APARTMENT | Heating | 420.52397 | 504.62876 | 1.99597E-002 | 2.59546E-002 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 04:00:00 | 0.50000 | 4.31558E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 13 | G S1 APARTMENT | Cooling | 3792.96474 | 4551.55768 | 0.29510 | 0.35412 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 35.61300 | 5.62306E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 14 | G S1 APARTMENT | Heating | 548.98190 | 658.77828 | 2.60563E-002 | 3.12675E-002 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 04:00:00 | 0.50000 | 4.31558E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 15 | G S2 APARTMENT | Cooling | 3820.74386 | 4584.89263 | 0.29732 | 0.35679 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 35.61300 | 5.62306E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 16 | G S2 APARTMENT | Heating | 559.42211 | 671.30653 | 2.65518E-002 | 3.18622E-002 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 04:00:00 | 0.50000 | 4.31558E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 17 | M SW APARTMENT | Cooling | 10282.71752 | 12339.26103 | 0.80477 | 0.96572 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 35.61300 | 5.62306E-003 | 88.24927 | 2.50000 | 5.19091E-002 | 0.00000 |
| 18 | M SW APARTMENT | Heating | 2177.19509 | 2612.63410 | 0.10333 | 0.12400 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | 0.50000 | 4.31558E-003 | 88.24927 | 2.50000 | 5.19091E-002 | 0.00000 |
| 19 | M NW APARTMENT | Cooling | 10191.37052 | 12229.64463 | 0.79755 | 0.95705 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 35.61300 | 5.62306E-003 | 88.24927 | 2.50000 | 5.19091E-002 | 0.00000 |
| 20 | M NW APARTMENT | Heating | 1885.09677 | 2262.11612 | 8.94718E-002 | 0.10737 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | 0.50000 | 4.31558E-003 | 88.24927 | 2.50000 | 5.19091E-002 | 0.00000 |
| 21 | M SE APARTMENT | Cooling | 9574.76446 | 11489.71736 | 0.74868 | 0.89842 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 35.61300 | 5.62306E-003 | 88.24927 | 2.50000 | 5.19091E-002 | 0.00000 |
| 22 | M SE APARTMENT | Heating | 2184.30156 | 2621.16187 | 0.10367 | 0.12441 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | 0.50000 | 4.31558E-003 | 88.24927 | 2.50000 | 5.19091E-002 | 0.00000 |
| 23 | M NE APARTMENT | Cooling | 9485.00249 | 11382.00299 | 0.74156 | 0.88987 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 35.61300 | 5.62306E-003 | 88.24927 | 2.50000 | 5.19091E-002 | 0.00000 |
| 24 | M NE APARTMENT | Heating | 1892.29025 | 2270.74830 | 8.98132E-002 | 0.10778 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | 0.50000 | 4.31558E-003 | 88.24927 | 2.50000 | 5.19091E-002 | 0.00000 |
| 25 | M N1 APARTMENT | Cooling | 8311.01964 | 9973.22357 | 0.64813 | 0.77775 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 35.61300 | 5.62306E-003 | 88.24927 | 2.50000 | 5.19091E-002 | 0.00000 |
| 26 | M N1 APARTMENT | Heating | 845.12069 | 1014.14483 | 4.01123E-002 | 5.19091E-002 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | 0.50000 | 4.31558E-003 | 88.24927 | 2.50000 | 5.19091E-002 | 0.00000 |
| 27 | M N2 APARTMENT | Cooling | 8299.29710 | 9959.15652 | 0.64719 | 0.77663 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 35.61300 | 5.62306E-003 | 88.24927 | 2.50000 | 5.19091E-002 | 0.00000 |
| 28 | M N2 APARTMENT | Heating | 845.32097 | 1014.38517 | 4.01218E-002 | 5.19091E-002 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | 0.50000 | 4.31558E-003 | 88.24927 | 2.50000 | 5.19091E-002 | 0.00000 |
| 29 | M S1 APARTMENT | Cooling | 8422.02474 | 10106.42969 | 0.65698 | 0.78838 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 35.61300 | 5.62306E-003 | 88.24927 | 2.50000 | 5.19091E-002 | 0.00000 |
| 30 | M S1 APARTMENT | Heating | 1130.00158 | 1356.00189 | 5.36328E-002 | 6.43594E-002 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | 0.50000 | 4.31558E-003 | 88.24927 | 2.50000 | 5.19091E-002 | 0.00000 |
| 31 | M S2 APARTMENT | Cooling | 8410.07383 | 10092.08859 | 0.65603 | 0.78723 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 35.61300 | 5.62306E-003 | 88.24927 | 2.50000 | 5.19091E-002 | 0.00000 |
| 32 | M S2 APARTMENT | Heating | 1130.19756 | 1356.23707 | 5.36421E-002 | 6.43705E-002 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | 0.50000 | 4.31558E-003 | 88.24927 | 2.50000 | 5.19091E-002 | 0.00000 |
| 33 | T SW APARTMENT | Cooling | 5888.32293 | 7065.98752 | 0.46183 | 0.55419 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 35.61300 | 5.62306E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 34 | T SW APARTMENT | Heating | 2041.86110 | 2450.23332 | 9.69091E-002 | 0.11629 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | 0.50000 | 4.31558E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 35 | T NW APARTMENT | Cooling | 5885.23187 | 7062.27824 | 0.46159 | 0.55391 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 35.61300 | 5.62306E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 36 | T NW APARTMENT | Heating | 1884.79154 | 2261.74985 | 8.94560E-002 | 0.10735 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | 0.50000 | 4.31558E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 37 | T SE APARTMENT | Cooling | 5358.16297 | 6429.79556 | 0.41957 | 0.50349 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 35.61300 | 5.62306E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 38 | T SE APARTMENT | Heating | 2046.15557 | 2455.38669 | 9.71129E-002 | 0.11654 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | 0.50000 | 4.31558E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 39 | T NE APARTMENT | Cooling | 5354.36822 | 6425.24186 | 0.41927 | 0.50313 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 35.61300 | 5.62306E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 40 | T NE APARTMENT | Heating | 1889.17846 | 2267.01416 | 8.96642E-002 | 0.10760 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | 0.50000 | 4.31558E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 41 | T N1 APARTMENT | Cooling | 4813.11008 | 5775.73209 | 0.37610 | 0.45132 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 35.61300 | 5.62306E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 42 | T N1 APARTMENT | Heating | 1280.12426 | 1536.14912 | 6.07586E-002 | 7.29103E-002 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | 0.50000 | 4.31558E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 43 | T N2 APARTMENT | Cooling | 4796.86548 | 5756.23858 | 0.37481 | 0.44977 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 35.61300 | 5.62306E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 44 | T N2 APARTMENT | Heating | 1280.25570 | 1536.30684 | 6.07648E-002 | 7.29178E-002 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | 0.50000 | 4.31558E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 45 | T S1 APARTMENT | Cooling | 4822.55631 | 5787.06757 | 0.37683 | 0.45219 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 35.61300 | 5.62306E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 46 | T S1 APARTMENT | Heating | 1438.40428 | 1726.08513 | 6.82698E-002 | 8.19237E-002 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | 0.50000 | 4.31558E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 47 | T S2 APARTMENT | Cooling | 4806.42800 | 5767.71360 | 0.37555 | 0.45066 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 35.61300 | 5.62306E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 48 | T S2 APARTMENT | Heating | 1438.53168 | 1726.23801 | 6.82758E-002 | 8.19310E-002 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | 0.50000 | 4.31558E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
| 1 | SPLIT GSW | Cooling | Sensible | 5576.77 | 0.42450 | 0.42450 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 2 | SPLIT GSW | Heating | Sensible | 1719.82 | 5.45461E-002 | 5.45461E-002 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 04:00:00 |
| 3 | SPLIT GNW | Cooling | Sensible | 5516.37 | 0.41964 | 0.41964 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 4 | SPLIT GNW | Heating | Sensible | 1568.41 | 4.72539E-002 | 4.72539E-002 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 04:00:00 |
| 5 | SPLIT OFFICE | Cooling | Sensible | 5957.47 | 0.45307 | 0.45307 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 6 | SPLIT OFFICE | Heating | Sensible | 2553.24 | 8.14438E-002 | 8.14438E-002 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 18:50:00 |
| 7 | SPLIT GNE | Cooling | Sensible | 5202.74 | 0.39438 | 0.39438 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 8 | SPLIT GNE | Heating | Sensible | 1571.84 | 4.74191E-002 | 4.74191E-002 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 04:00:00 |
| 9 | SPLIT GN1 | Cooling | Sensible | 4630.47 | 0.34824 | 0.34824 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 10 | SPLIT GN1 | Heating | Sensible | 1126.19 | 2.59546E-002 | 2.59546E-002 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
| 11 | SPLIT GN2 | Cooling | Sensible | 4624.91 | 0.34779 | 0.34779 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 12 | SPLIT GN2 | Heating | Sensible | 1126.19 | 2.59546E-002 | 2.59546E-002 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
| 13 | SPLIT GS1 | Cooling | Sensible | 4703.32 | 0.35412 | 0.35412 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 14 | SPLIT GS1 | Heating | Sensible | 1236.50 | 3.12675E-002 | 3.12675E-002 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 04:00:00 |
| 15 | SPLIT GS2 | Cooling | Sensible | 4736.33 | 0.35679 | 0.35679 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 16 | SPLIT GS2 | Heating | Sensible | 1248.85 | 3.18622E-002 | 3.18622E-002 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 04:00:00 |
| 17 | SPLIT MSW | Cooling | Sensible | 12605.54 | 0.96572 | 0.96572 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 18 | SPLIT MSW | Heating | Sensible | 3749.20 | 0.12400 | 0.12400 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 |
| 19 | SPLIT MNW | Cooling | Sensible | 12497.72 | 0.95705 | 0.95705 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 20 | SPLIT MNW | Heating | Sensible | 3403.80 | 0.10737 | 0.10737 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 |
| 21 | SPLIT MSE | Cooling | Sensible | 11768.27 | 0.89842 | 0.89842 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 22 | SPLIT MSE | Heating | Sensible | 3757.60 | 0.12441 | 0.12441 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 |
| 23 | SPLIT MNE | Cooling | Sensible | 11662.09 | 0.88987 | 0.88987 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 24 | SPLIT MNE | Heating | Sensible | 3412.31 | 0.10778 | 0.10778 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 |
| 25 | SPLIT MN1 | Cooling | Sensible | 10269.54 | 0.77775 | 0.77775 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 26 | SPLIT MN1 | Heating | Sensible | 2252.39 | 5.19091E-002 | 5.19091E-002 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
| 27 | SPLIT MN2 | Cooling | Sensible | 10255.61 | 0.77663 | 0.77663 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 28 | SPLIT MN2 | Heating | Sensible | 2252.39 | 5.19091E-002 | 5.19091E-002 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
| 29 | SPLIT MS1 | Cooling | Sensible | 10401.38 | 0.78838 | 0.78838 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 30 | SPLIT MS1 | Heating | Sensible | 2510.88 | 6.43594E-002 | 6.43594E-002 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 |
| 31 | SPLIT MS2 | Cooling | Sensible | 10387.19 | 0.78723 | 0.78723 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 32 | SPLIT MS2 | Heating | Sensible | 2511.11 | 6.43705E-002 | 6.43705E-002 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 |
| 33 | SPLIT TSW | Cooling | Sensible | 7188.07 | 0.55419 | 0.55419 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 34 | SPLIT TSW | Heating | Sensible | 3001.84 | 0.11629 | 0.11629 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 |
| 35 | SPLIT TNW | Cooling | Sensible | 7184.50 | 0.55391 | 0.55391 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 36 | SPLIT TNW | Heating | Sensible | 2816.11 | 0.10735 | 0.10735 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 |
| 37 | SPLIT TSE | Cooling | Sensible | 6559.35 | 0.50349 | 0.50349 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 38 | SPLIT TSE | Heating | Sensible | 3006.92 | 0.11654 | 0.11654 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 |
| 39 | SPLIT TNE | Cooling | Sensible | 6554.91 | 0.50313 | 0.50313 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 40 | SPLIT TNE | Heating | Sensible | 2821.30 | 0.10760 | 0.10760 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 |
| 41 | SPLIT TN1 | Cooling | Sensible | 5912.59 | 0.45132 | 0.45132 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 42 | SPLIT TN1 | Heating | Sensible | 2101.09 | 7.29103E-002 | 7.29103E-002 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 |
| 43 | SPLIT TN2 | Cooling | Sensible | 5893.39 | 0.44977 | 0.44977 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 44 | SPLIT TN2 | Heating | Sensible | 2101.25 | 7.29178E-002 | 7.29178E-002 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 |
| 45 | SPLIT TS1 | Cooling | Sensible | 5923.58 | 0.45219 | 0.45219 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 46 | SPLIT TS1 | Heating | Sensible | 2288.25 | 8.19237E-002 | 8.19237E-002 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 |
| 47 | SPLIT TS2 | Cooling | Sensible | 5904.49 | 0.45066 | 0.45066 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 48 | SPLIT TS2 | Heating | Sensible | 2288.41 | 8.19310E-002 | 8.19310E-002 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 |
| Component Type | Component Name | Input Field Description | Value | |
| 1 | ZoneHVAC:EnergyRecoveryVentilator | G SW APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 2 | ZoneHVAC:EnergyRecoveryVentilator | G SW APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 2.59546E-002 |
| 3 | Fan:OnOff | G SW APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 4 | Fan:OnOff | G SW APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 5 | HeatExchanger:AirToAir:SensibleAndLatent | G SW APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 6 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | G SW APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.42450 |
| 7 | ZoneHVAC:EnergyRecoveryVentilator | G NW APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 8 | ZoneHVAC:EnergyRecoveryVentilator | G NW APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 2.59546E-002 |
| 9 | Fan:OnOff | G NW APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 10 | Fan:OnOff | G NW APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 11 | HeatExchanger:AirToAir:SensibleAndLatent | G NW APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 12 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | G NW APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.41964 |
| 13 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | OFFICE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.45307 |
| 14 | ZoneHVAC:EnergyRecoveryVentilator | G NE APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 15 | ZoneHVAC:EnergyRecoveryVentilator | G NE APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 2.59546E-002 |
| 16 | Fan:OnOff | G NE APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 17 | Fan:OnOff | G NE APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 18 | HeatExchanger:AirToAir:SensibleAndLatent | G NE APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 19 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | G NE APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.39438 |
| 20 | ZoneHVAC:EnergyRecoveryVentilator | G N1 APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 21 | ZoneHVAC:EnergyRecoveryVentilator | G N1 APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 2.59546E-002 |
| 22 | Fan:OnOff | G N1 APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 23 | Fan:OnOff | G N1 APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 24 | HeatExchanger:AirToAir:SensibleAndLatent | G N1 APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 25 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | G N1 APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.34824 |
| 26 | ZoneHVAC:EnergyRecoveryVentilator | G N2 APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 27 | ZoneHVAC:EnergyRecoveryVentilator | G N2 APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 2.59546E-002 |
| 28 | Fan:OnOff | G N2 APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 29 | Fan:OnOff | G N2 APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 30 | HeatExchanger:AirToAir:SensibleAndLatent | G N2 APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 31 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | G N2 APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.34779 |
| 32 | ZoneHVAC:EnergyRecoveryVentilator | G S1 APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 33 | ZoneHVAC:EnergyRecoveryVentilator | G S1 APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 2.59546E-002 |
| 34 | Fan:OnOff | G S1 APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 35 | Fan:OnOff | G S1 APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 36 | HeatExchanger:AirToAir:SensibleAndLatent | G S1 APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 37 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | G S1 APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.35412 |
| 38 | ZoneHVAC:EnergyRecoveryVentilator | G S2 APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 39 | ZoneHVAC:EnergyRecoveryVentilator | G S2 APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 2.59546E-002 |
| 40 | Fan:OnOff | G S2 APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 41 | Fan:OnOff | G S2 APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 42 | HeatExchanger:AirToAir:SensibleAndLatent | G S2 APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 43 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | G S2 APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.35679 |
| 44 | ZoneHVAC:EnergyRecoveryVentilator | M SW APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 5.19091E-002 |
| 45 | ZoneHVAC:EnergyRecoveryVentilator | M SW APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 5.19091E-002 |
| 46 | Fan:OnOff | M SW APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 5.19091E-002 |
| 47 | Fan:OnOff | M SW APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 5.19091E-002 |
| 48 | HeatExchanger:AirToAir:SensibleAndLatent | M SW APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 5.19091E-002 |
| 49 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | M SW APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.96572 |
| 50 | ZoneHVAC:EnergyRecoveryVentilator | M NW APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 5.19091E-002 |
| 51 | ZoneHVAC:EnergyRecoveryVentilator | M NW APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 5.19091E-002 |
| 52 | Fan:OnOff | M NW APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 5.19091E-002 |
| 53 | Fan:OnOff | M NW APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 5.19091E-002 |
| 54 | HeatExchanger:AirToAir:SensibleAndLatent | M NW APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 5.19091E-002 |
| 55 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | M NW APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.95705 |
| 56 | ZoneHVAC:EnergyRecoveryVentilator | M SE APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 5.19091E-002 |
| 57 | ZoneHVAC:EnergyRecoveryVentilator | M SE APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 5.19091E-002 |
| 58 | Fan:OnOff | M SE APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 5.19091E-002 |
| 59 | Fan:OnOff | M SE APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 5.19091E-002 |
| 60 | HeatExchanger:AirToAir:SensibleAndLatent | M SE APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 5.19091E-002 |
| 61 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | M SE APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.89842 |
| 62 | ZoneHVAC:EnergyRecoveryVentilator | M NE APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 5.19091E-002 |
| 63 | ZoneHVAC:EnergyRecoveryVentilator | M NE APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 5.19091E-002 |
| 64 | Fan:OnOff | M NE APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 5.19091E-002 |
| 65 | Fan:OnOff | M NE APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 5.19091E-002 |
| 66 | HeatExchanger:AirToAir:SensibleAndLatent | M NE APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 5.19091E-002 |
| 67 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | M NE APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.88987 |
| 68 | ZoneHVAC:EnergyRecoveryVentilator | M N1 APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 5.19091E-002 |
| 69 | ZoneHVAC:EnergyRecoveryVentilator | M N1 APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 5.19091E-002 |
| 70 | Fan:OnOff | M N1 APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 5.19091E-002 |
| 71 | Fan:OnOff | M N1 APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 5.19091E-002 |
| 72 | HeatExchanger:AirToAir:SensibleAndLatent | M N1 APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 5.19091E-002 |
| 73 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | M N1 APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.77775 |
| 74 | ZoneHVAC:EnergyRecoveryVentilator | M N2 APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 5.19091E-002 |
| 75 | ZoneHVAC:EnergyRecoveryVentilator | M N2 APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 5.19091E-002 |
| 76 | Fan:OnOff | M N2 APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 5.19091E-002 |
| 77 | Fan:OnOff | M N2 APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 5.19091E-002 |
| 78 | HeatExchanger:AirToAir:SensibleAndLatent | M N2 APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 5.19091E-002 |
| 79 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | M N2 APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.77663 |
| 80 | ZoneHVAC:EnergyRecoveryVentilator | M S1 APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 5.19091E-002 |
| 81 | ZoneHVAC:EnergyRecoveryVentilator | M S1 APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 5.19091E-002 |
| 82 | Fan:OnOff | M S1 APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 5.19091E-002 |
| 83 | Fan:OnOff | M S1 APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 5.19091E-002 |
| 84 | HeatExchanger:AirToAir:SensibleAndLatent | M S1 APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 5.19091E-002 |
| 85 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | M S1 APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.78838 |
| 86 | ZoneHVAC:EnergyRecoveryVentilator | M S2 APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 5.19091E-002 |
| 87 | ZoneHVAC:EnergyRecoveryVentilator | M S2 APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 5.19091E-002 |
| 88 | Fan:OnOff | M S2 APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 5.19091E-002 |
| 89 | Fan:OnOff | M S2 APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 5.19091E-002 |
| 90 | HeatExchanger:AirToAir:SensibleAndLatent | M S2 APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 5.19091E-002 |
| 91 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | M S2 APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.78723 |
| 92 | ZoneHVAC:EnergyRecoveryVentilator | T SW APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 93 | ZoneHVAC:EnergyRecoveryVentilator | T SW APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 2.59546E-002 |
| 94 | Fan:OnOff | T SW APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 95 | Fan:OnOff | T SW APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 96 | HeatExchanger:AirToAir:SensibleAndLatent | T SW APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 97 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | T SW APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.55419 |
| 98 | ZoneHVAC:EnergyRecoveryVentilator | T NW APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 99 | ZoneHVAC:EnergyRecoveryVentilator | T NW APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 2.59546E-002 |
| 100 | Fan:OnOff | T NW APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 101 | Fan:OnOff | T NW APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 102 | HeatExchanger:AirToAir:SensibleAndLatent | T NW APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 103 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | T NW APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.55391 |
| 104 | ZoneHVAC:EnergyRecoveryVentilator | T SE APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 105 | ZoneHVAC:EnergyRecoveryVentilator | T SE APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 2.59546E-002 |
| 106 | Fan:OnOff | T SE APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 107 | Fan:OnOff | T SE APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 108 | HeatExchanger:AirToAir:SensibleAndLatent | T SE APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 109 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | T SE APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.50349 |
| 110 | ZoneHVAC:EnergyRecoveryVentilator | T NE APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 111 | ZoneHVAC:EnergyRecoveryVentilator | T NE APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 2.59546E-002 |
| 112 | Fan:OnOff | T NE APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 113 | Fan:OnOff | T NE APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 114 | HeatExchanger:AirToAir:SensibleAndLatent | T NE APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 115 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | T NE APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.50313 |
| 116 | ZoneHVAC:EnergyRecoveryVentilator | T N1 APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 117 | ZoneHVAC:EnergyRecoveryVentilator | T N1 APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 2.59546E-002 |
| 118 | Fan:OnOff | T N1 APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 119 | Fan:OnOff | T N1 APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 120 | HeatExchanger:AirToAir:SensibleAndLatent | T N1 APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 121 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | T N1 APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.45132 |
| 122 | ZoneHVAC:EnergyRecoveryVentilator | T N2 APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 123 | ZoneHVAC:EnergyRecoveryVentilator | T N2 APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 2.59546E-002 |
| 124 | Fan:OnOff | T N2 APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 125 | Fan:OnOff | T N2 APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 126 | HeatExchanger:AirToAir:SensibleAndLatent | T N2 APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 127 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | T N2 APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.44977 |
| 128 | ZoneHVAC:EnergyRecoveryVentilator | T S1 APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 129 | ZoneHVAC:EnergyRecoveryVentilator | T S1 APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 2.59546E-002 |
| 130 | Fan:OnOff | T S1 APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 131 | Fan:OnOff | T S1 APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 132 | HeatExchanger:AirToAir:SensibleAndLatent | T S1 APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 133 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | T S1 APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.45219 |
| 134 | ZoneHVAC:EnergyRecoveryVentilator | T S2 APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 135 | ZoneHVAC:EnergyRecoveryVentilator | T S2 APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 2.59546E-002 |
| 136 | Fan:OnOff | T S2 APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 137 | Fan:OnOff | T S2 APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 138 | HeatExchanger:AirToAir:SensibleAndLatent | T S2 APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 139 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | T S2 APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.45066 |
| 140 | AirLoopHVAC | SPLIT GSW | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.42450 |
| 141 | AirLoopHVAC | SPLIT GSW | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.42450 |
| 142 | AirLoopHVAC | SPLIT GSW | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.42450 |
| 143 | AirLoopHVAC | SPLIT GSW | Adjusted Heating Design Air Flow Rate [m3/s] | 0.42450 |
| 144 | AirLoopHVAC | SPLIT GSW | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.42450 |
| 145 | AirLoopHVAC | SPLIT GSW | Adjusted Main Design Air Flow Rate [m3/s] | 0.42450 |
| 146 | AirLoopHVAC | SPLIT GSW | User Heating Air Flow Ratio [] | 1.00000 |
| 147 | AirLoopHVAC | SPLIT GSW | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 148 | AirLoopHVAC | SPLIT GNW | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.41964 |
| 149 | AirLoopHVAC | SPLIT GNW | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.41964 |
| 150 | AirLoopHVAC | SPLIT GNW | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.41964 |
| 151 | AirLoopHVAC | SPLIT GNW | Adjusted Heating Design Air Flow Rate [m3/s] | 0.41964 |
| 152 | AirLoopHVAC | SPLIT GNW | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.41964 |
| 153 | AirLoopHVAC | SPLIT GNW | Adjusted Main Design Air Flow Rate [m3/s] | 0.41964 |
| 154 | AirLoopHVAC | SPLIT GNW | User Heating Air Flow Ratio [] | 1.00000 |
| 155 | AirLoopHVAC | SPLIT GNW | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 156 | AirLoopHVAC | SPLIT OFFICE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.45307 |
| 157 | AirLoopHVAC | SPLIT OFFICE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.45307 |
| 158 | AirLoopHVAC | SPLIT OFFICE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.45307 |
| 159 | AirLoopHVAC | SPLIT OFFICE | Adjusted Heating Design Air Flow Rate [m3/s] | 0.45307 |
| 160 | AirLoopHVAC | SPLIT OFFICE | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.45307 |
| 161 | AirLoopHVAC | SPLIT OFFICE | Adjusted Main Design Air Flow Rate [m3/s] | 0.45307 |
| 162 | AirLoopHVAC | SPLIT OFFICE | User Heating Air Flow Ratio [] | 1.00000 |
| 163 | AirLoopHVAC | SPLIT OFFICE | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 164 | AirLoopHVAC | SPLIT GNE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.39438 |
| 165 | AirLoopHVAC | SPLIT GNE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.39438 |
| 166 | AirLoopHVAC | SPLIT GNE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.39438 |
| 167 | AirLoopHVAC | SPLIT GNE | Adjusted Heating Design Air Flow Rate [m3/s] | 0.39438 |
| 168 | AirLoopHVAC | SPLIT GNE | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.39438 |
| 169 | AirLoopHVAC | SPLIT GNE | Adjusted Main Design Air Flow Rate [m3/s] | 0.39438 |
| 170 | AirLoopHVAC | SPLIT GNE | User Heating Air Flow Ratio [] | 1.00000 |
| 171 | AirLoopHVAC | SPLIT GNE | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 172 | AirLoopHVAC | SPLIT GN1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.34824 |
| 173 | AirLoopHVAC | SPLIT GN1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.34824 |
| 174 | AirLoopHVAC | SPLIT GN1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.34824 |
| 175 | AirLoopHVAC | SPLIT GN1 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.34824 |
| 176 | AirLoopHVAC | SPLIT GN1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.34824 |
| 177 | AirLoopHVAC | SPLIT GN1 | Adjusted Main Design Air Flow Rate [m3/s] | 0.34824 |
| 178 | AirLoopHVAC | SPLIT GN1 | User Heating Air Flow Ratio [] | 1.00000 |
| 179 | AirLoopHVAC | SPLIT GN1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 180 | AirLoopHVAC | SPLIT GN2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.34779 |
| 181 | AirLoopHVAC | SPLIT GN2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.34779 |
| 182 | AirLoopHVAC | SPLIT GN2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.34779 |
| 183 | AirLoopHVAC | SPLIT GN2 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.34779 |
| 184 | AirLoopHVAC | SPLIT GN2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.34779 |
| 185 | AirLoopHVAC | SPLIT GN2 | Adjusted Main Design Air Flow Rate [m3/s] | 0.34779 |
| 186 | AirLoopHVAC | SPLIT GN2 | User Heating Air Flow Ratio [] | 1.00000 |
| 187 | AirLoopHVAC | SPLIT GN2 | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 188 | AirLoopHVAC | SPLIT GS1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.35412 |
| 189 | AirLoopHVAC | SPLIT GS1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.35412 |
| 190 | AirLoopHVAC | SPLIT GS1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.35412 |
| 191 | AirLoopHVAC | SPLIT GS1 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.35412 |
| 192 | AirLoopHVAC | SPLIT GS1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.35412 |
| 193 | AirLoopHVAC | SPLIT GS1 | Adjusted Main Design Air Flow Rate [m3/s] | 0.35412 |
| 194 | AirLoopHVAC | SPLIT GS1 | User Heating Air Flow Ratio [] | 1.00000 |
| 195 | AirLoopHVAC | SPLIT GS1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 196 | AirLoopHVAC | SPLIT GS2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.35679 |
| 197 | AirLoopHVAC | SPLIT GS2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.35679 |
| 198 | AirLoopHVAC | SPLIT GS2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.35679 |
| 199 | AirLoopHVAC | SPLIT GS2 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.35679 |
| 200 | AirLoopHVAC | SPLIT GS2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.35679 |
| 201 | AirLoopHVAC | SPLIT GS2 | Adjusted Main Design Air Flow Rate [m3/s] | 0.35679 |
| 202 | AirLoopHVAC | SPLIT GS2 | User Heating Air Flow Ratio [] | 1.00000 |
| 203 | AirLoopHVAC | SPLIT GS2 | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 204 | AirLoopHVAC | SPLIT MSW | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.96572 |
| 205 | AirLoopHVAC | SPLIT MSW | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.96572 |
| 206 | AirLoopHVAC | SPLIT MSW | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.96572 |
| 207 | AirLoopHVAC | SPLIT MSW | Adjusted Heating Design Air Flow Rate [m3/s] | 0.96572 |
| 208 | AirLoopHVAC | SPLIT MSW | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.96572 |
| 209 | AirLoopHVAC | SPLIT MSW | Adjusted Main Design Air Flow Rate [m3/s] | 0.96572 |
| 210 | AirLoopHVAC | SPLIT MSW | User Heating Air Flow Ratio [] | 1.00000 |
| 211 | AirLoopHVAC | SPLIT MSW | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 212 | AirLoopHVAC | SPLIT MNW | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.95705 |
| 213 | AirLoopHVAC | SPLIT MNW | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.95705 |
| 214 | AirLoopHVAC | SPLIT MNW | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.95705 |
| 215 | AirLoopHVAC | SPLIT MNW | Adjusted Heating Design Air Flow Rate [m3/s] | 0.95705 |
| 216 | AirLoopHVAC | SPLIT MNW | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.95705 |
| 217 | AirLoopHVAC | SPLIT MNW | Adjusted Main Design Air Flow Rate [m3/s] | 0.95705 |
| 218 | AirLoopHVAC | SPLIT MNW | User Heating Air Flow Ratio [] | 1.00000 |
| 219 | AirLoopHVAC | SPLIT MNW | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 220 | AirLoopHVAC | SPLIT MSE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.89842 |
| 221 | AirLoopHVAC | SPLIT MSE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.89842 |
| 222 | AirLoopHVAC | SPLIT MSE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.89842 |
| 223 | AirLoopHVAC | SPLIT MSE | Adjusted Heating Design Air Flow Rate [m3/s] | 0.89842 |
| 224 | AirLoopHVAC | SPLIT MSE | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.89842 |
| 225 | AirLoopHVAC | SPLIT MSE | Adjusted Main Design Air Flow Rate [m3/s] | 0.89842 |
| 226 | AirLoopHVAC | SPLIT MSE | User Heating Air Flow Ratio [] | 1.00000 |
| 227 | AirLoopHVAC | SPLIT MSE | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 228 | AirLoopHVAC | SPLIT MNE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.88987 |
| 229 | AirLoopHVAC | SPLIT MNE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.88987 |
| 230 | AirLoopHVAC | SPLIT MNE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.88987 |
| 231 | AirLoopHVAC | SPLIT MNE | Adjusted Heating Design Air Flow Rate [m3/s] | 0.88987 |
| 232 | AirLoopHVAC | SPLIT MNE | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.88987 |
| 233 | AirLoopHVAC | SPLIT MNE | Adjusted Main Design Air Flow Rate [m3/s] | 0.88987 |
| 234 | AirLoopHVAC | SPLIT MNE | User Heating Air Flow Ratio [] | 1.00000 |
| 235 | AirLoopHVAC | SPLIT MNE | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 236 | AirLoopHVAC | SPLIT MN1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.77775 |
| 237 | AirLoopHVAC | SPLIT MN1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.77775 |
| 238 | AirLoopHVAC | SPLIT MN1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.77775 |
| 239 | AirLoopHVAC | SPLIT MN1 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.77775 |
| 240 | AirLoopHVAC | SPLIT MN1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.77775 |
| 241 | AirLoopHVAC | SPLIT MN1 | Adjusted Main Design Air Flow Rate [m3/s] | 0.77775 |
| 242 | AirLoopHVAC | SPLIT MN1 | User Heating Air Flow Ratio [] | 1.00000 |
| 243 | AirLoopHVAC | SPLIT MN1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 244 | AirLoopHVAC | SPLIT MN2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.77663 |
| 245 | AirLoopHVAC | SPLIT MN2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.77663 |
| 246 | AirLoopHVAC | SPLIT MN2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.77663 |
| 247 | AirLoopHVAC | SPLIT MN2 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.77663 |
| 248 | AirLoopHVAC | SPLIT MN2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.77663 |
| 249 | AirLoopHVAC | SPLIT MN2 | Adjusted Main Design Air Flow Rate [m3/s] | 0.77663 |
| 250 | AirLoopHVAC | SPLIT MN2 | User Heating Air Flow Ratio [] | 1.00000 |
| 251 | AirLoopHVAC | SPLIT MN2 | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 252 | AirLoopHVAC | SPLIT MS1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.78838 |
| 253 | AirLoopHVAC | SPLIT MS1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.78838 |
| 254 | AirLoopHVAC | SPLIT MS1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.78838 |
| 255 | AirLoopHVAC | SPLIT MS1 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.78838 |
| 256 | AirLoopHVAC | SPLIT MS1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.78838 |
| 257 | AirLoopHVAC | SPLIT MS1 | Adjusted Main Design Air Flow Rate [m3/s] | 0.78838 |
| 258 | AirLoopHVAC | SPLIT MS1 | User Heating Air Flow Ratio [] | 1.00000 |
| 259 | AirLoopHVAC | SPLIT MS1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 260 | AirLoopHVAC | SPLIT MS2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.78723 |
| 261 | AirLoopHVAC | SPLIT MS2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.78723 |
| 262 | AirLoopHVAC | SPLIT MS2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.78723 |
| 263 | AirLoopHVAC | SPLIT MS2 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.78723 |
| 264 | AirLoopHVAC | SPLIT MS2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.78723 |
| 265 | AirLoopHVAC | SPLIT MS2 | Adjusted Main Design Air Flow Rate [m3/s] | 0.78723 |
| 266 | AirLoopHVAC | SPLIT MS2 | User Heating Air Flow Ratio [] | 1.00000 |
| 267 | AirLoopHVAC | SPLIT MS2 | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 268 | AirLoopHVAC | SPLIT TSW | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.55419 |
| 269 | AirLoopHVAC | SPLIT TSW | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.55419 |
| 270 | AirLoopHVAC | SPLIT TSW | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.55419 |
| 271 | AirLoopHVAC | SPLIT TSW | Adjusted Heating Design Air Flow Rate [m3/s] | 0.55419 |
| 272 | AirLoopHVAC | SPLIT TSW | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.55419 |
| 273 | AirLoopHVAC | SPLIT TSW | Adjusted Main Design Air Flow Rate [m3/s] | 0.55419 |
| 274 | AirLoopHVAC | SPLIT TSW | User Heating Air Flow Ratio [] | 1.00000 |
| 275 | AirLoopHVAC | SPLIT TSW | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 276 | AirLoopHVAC | SPLIT TNW | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.55391 |
| 277 | AirLoopHVAC | SPLIT TNW | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.55391 |
| 278 | AirLoopHVAC | SPLIT TNW | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.55391 |
| 279 | AirLoopHVAC | SPLIT TNW | Adjusted Heating Design Air Flow Rate [m3/s] | 0.55391 |
| 280 | AirLoopHVAC | SPLIT TNW | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.55391 |
| 281 | AirLoopHVAC | SPLIT TNW | Adjusted Main Design Air Flow Rate [m3/s] | 0.55391 |
| 282 | AirLoopHVAC | SPLIT TNW | User Heating Air Flow Ratio [] | 1.00000 |
| 283 | AirLoopHVAC | SPLIT TNW | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 284 | AirLoopHVAC | SPLIT TSE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.50349 |
| 285 | AirLoopHVAC | SPLIT TSE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.50349 |
| 286 | AirLoopHVAC | SPLIT TSE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.50349 |
| 287 | AirLoopHVAC | SPLIT TSE | Adjusted Heating Design Air Flow Rate [m3/s] | 0.50349 |
| 288 | AirLoopHVAC | SPLIT TSE | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.50349 |
| 289 | AirLoopHVAC | SPLIT TSE | Adjusted Main Design Air Flow Rate [m3/s] | 0.50349 |
| 290 | AirLoopHVAC | SPLIT TSE | User Heating Air Flow Ratio [] | 1.00000 |
| 291 | AirLoopHVAC | SPLIT TSE | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 292 | AirLoopHVAC | SPLIT TNE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.50313 |
| 293 | AirLoopHVAC | SPLIT TNE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.50313 |
| 294 | AirLoopHVAC | SPLIT TNE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.50313 |
| 295 | AirLoopHVAC | SPLIT TNE | Adjusted Heating Design Air Flow Rate [m3/s] | 0.50313 |
| 296 | AirLoopHVAC | SPLIT TNE | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.50313 |
| 297 | AirLoopHVAC | SPLIT TNE | Adjusted Main Design Air Flow Rate [m3/s] | 0.50313 |
| 298 | AirLoopHVAC | SPLIT TNE | User Heating Air Flow Ratio [] | 1.00000 |
| 299 | AirLoopHVAC | SPLIT TNE | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 300 | AirLoopHVAC | SPLIT TN1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.45132 |
| 301 | AirLoopHVAC | SPLIT TN1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.45132 |
| 302 | AirLoopHVAC | SPLIT TN1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.45132 |
| 303 | AirLoopHVAC | SPLIT TN1 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.45132 |
| 304 | AirLoopHVAC | SPLIT TN1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.45132 |
| 305 | AirLoopHVAC | SPLIT TN1 | Adjusted Main Design Air Flow Rate [m3/s] | 0.45132 |
| 306 | AirLoopHVAC | SPLIT TN1 | User Heating Air Flow Ratio [] | 1.00000 |
| 307 | AirLoopHVAC | SPLIT TN1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 308 | AirLoopHVAC | SPLIT TN2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.44977 |
| 309 | AirLoopHVAC | SPLIT TN2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.44977 |
| 310 | AirLoopHVAC | SPLIT TN2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.44977 |
| 311 | AirLoopHVAC | SPLIT TN2 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.44977 |
| 312 | AirLoopHVAC | SPLIT TN2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.44977 |
| 313 | AirLoopHVAC | SPLIT TN2 | Adjusted Main Design Air Flow Rate [m3/s] | 0.44977 |
| 314 | AirLoopHVAC | SPLIT TN2 | User Heating Air Flow Ratio [] | 1.00000 |
| 315 | AirLoopHVAC | SPLIT TN2 | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 316 | AirLoopHVAC | SPLIT TS1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.45219 |
| 317 | AirLoopHVAC | SPLIT TS1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.45219 |
| 318 | AirLoopHVAC | SPLIT TS1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.45219 |
| 319 | AirLoopHVAC | SPLIT TS1 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.45219 |
| 320 | AirLoopHVAC | SPLIT TS1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.45219 |
| 321 | AirLoopHVAC | SPLIT TS1 | Adjusted Main Design Air Flow Rate [m3/s] | 0.45219 |
| 322 | AirLoopHVAC | SPLIT TS1 | User Heating Air Flow Ratio [] | 1.00000 |
| 323 | AirLoopHVAC | SPLIT TS1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 324 | AirLoopHVAC | SPLIT TS2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.45066 |
| 325 | AirLoopHVAC | SPLIT TS2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.45066 |
| 326 | AirLoopHVAC | SPLIT TS2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.45066 |
| 327 | AirLoopHVAC | SPLIT TS2 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.45066 |
| 328 | AirLoopHVAC | SPLIT TS2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.45066 |
| 329 | AirLoopHVAC | SPLIT TS2 | Adjusted Main Design Air Flow Rate [m3/s] | 0.45066 |
| 330 | AirLoopHVAC | SPLIT TS2 | User Heating Air Flow Ratio [] | 1.00000 |
| 331 | AirLoopHVAC | SPLIT TS2 | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 332 | AirLoopHVAC | SPLIT GSW | Design Supply Air Flow Rate [m3/s] | 0.42450 |
| 333 | AirLoopHVAC | SPLIT GNW | Design Supply Air Flow Rate [m3/s] | 0.41964 |
| 334 | AirLoopHVAC | SPLIT OFFICE | Design Supply Air Flow Rate [m3/s] | 0.45307 |
| 335 | AirLoopHVAC | SPLIT GNE | Design Supply Air Flow Rate [m3/s] | 0.39438 |
| 336 | AirLoopHVAC | SPLIT GN1 | Design Supply Air Flow Rate [m3/s] | 0.34824 |
| 337 | AirLoopHVAC | SPLIT GN2 | Design Supply Air Flow Rate [m3/s] | 0.34779 |
| 338 | AirLoopHVAC | SPLIT GS1 | Design Supply Air Flow Rate [m3/s] | 0.35412 |
| 339 | AirLoopHVAC | SPLIT GS2 | Design Supply Air Flow Rate [m3/s] | 0.35679 |
| 340 | AirLoopHVAC | SPLIT MSW | Design Supply Air Flow Rate [m3/s] | 0.96572 |
| 341 | AirLoopHVAC | SPLIT MNW | Design Supply Air Flow Rate [m3/s] | 0.95705 |
| 342 | AirLoopHVAC | SPLIT MSE | Design Supply Air Flow Rate [m3/s] | 0.89842 |
| 343 | AirLoopHVAC | SPLIT MNE | Design Supply Air Flow Rate [m3/s] | 0.88987 |
| 344 | AirLoopHVAC | SPLIT MN1 | Design Supply Air Flow Rate [m3/s] | 0.77775 |
| 345 | AirLoopHVAC | SPLIT MN2 | Design Supply Air Flow Rate [m3/s] | 0.77663 |
| 346 | AirLoopHVAC | SPLIT MS1 | Design Supply Air Flow Rate [m3/s] | 0.78838 |
| 347 | AirLoopHVAC | SPLIT MS2 | Design Supply Air Flow Rate [m3/s] | 0.78723 |
| 348 | AirLoopHVAC | SPLIT TSW | Design Supply Air Flow Rate [m3/s] | 0.55419 |
| 349 | AirLoopHVAC | SPLIT TNW | Design Supply Air Flow Rate [m3/s] | 0.55391 |
| 350 | AirLoopHVAC | SPLIT TSE | Design Supply Air Flow Rate [m3/s] | 0.50349 |
| 351 | AirLoopHVAC | SPLIT TNE | Design Supply Air Flow Rate [m3/s] | 0.50313 |
| 352 | AirLoopHVAC | SPLIT TN1 | Design Supply Air Flow Rate [m3/s] | 0.45132 |
| 353 | AirLoopHVAC | SPLIT TN2 | Design Supply Air Flow Rate [m3/s] | 0.44977 |
| 354 | AirLoopHVAC | SPLIT TS1 | Design Supply Air Flow Rate [m3/s] | 0.45219 |
| 355 | AirLoopHVAC | SPLIT TS2 | Design Supply Air Flow Rate [m3/s] | 0.45066 |
| 356 | Controller:OutdoorAir | SPLIT GSW_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.42450 |
| 357 | Controller:OutdoorAir | SPLIT GSW_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.59546E-002 |
| 358 | AirLoopHVAC:UnitarySystem | SPLIT GSW_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.42450 |
| 359 | AirLoopHVAC:UnitarySystem | SPLIT GSW_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.42450 |
| 360 | AirLoopHVAC:UnitarySystem | SPLIT GSW_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.42450 |
| 361 | AirLoopHVAC:UnitarySystem | SPLIT GSW_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.42450 |
| 362 | AirLoopHVAC:UnitarySystem | SPLIT GSW_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 7027.00475 |
| 363 | AirLoopHVAC:UnitarySystem | SPLIT GSW_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 9400.99712 |
| 364 | AirLoopHVAC:UnitarySystem | SPLIT GSW_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 365 | AirLoopHVAC:UnitarySystem | SPLIT GSW_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 366 | Fan:OnOff | SPLIT GSW SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.42450 |
| 367 | Coil:Cooling:DX:SingleSpeed | SPLIT GSW COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.42450 |
| 368 | Coil:Cooling:DX:SingleSpeed | SPLIT GSW COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 7027.00475 |
| 369 | Coil:Cooling:DX:SingleSpeed | SPLIT GSW COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
| 370 | Coil:Heating:Fuel | SPLIT GSW HEATING COIL | Design Size Nominal Capacity [W] | 9400.99712 |
| 371 | Controller:OutdoorAir | SPLIT GNW_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.41964 |
| 372 | Controller:OutdoorAir | SPLIT GNW_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.59546E-002 |
| 373 | AirLoopHVAC:UnitarySystem | SPLIT GNW_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.41964 |
| 374 | AirLoopHVAC:UnitarySystem | SPLIT GNW_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.41964 |
| 375 | AirLoopHVAC:UnitarySystem | SPLIT GNW_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.41964 |
| 376 | AirLoopHVAC:UnitarySystem | SPLIT GNW_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.41964 |
| 377 | AirLoopHVAC:UnitarySystem | SPLIT GNW_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 6946.45259 |
| 378 | AirLoopHVAC:UnitarySystem | SPLIT GNW_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 9299.81028 |
| 379 | AirLoopHVAC:UnitarySystem | SPLIT GNW_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 380 | AirLoopHVAC:UnitarySystem | SPLIT GNW_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 381 | Fan:OnOff | SPLIT GNW SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.41964 |
| 382 | Coil:Cooling:DX:SingleSpeed | SPLIT GNW COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.41964 |
| 383 | Coil:Cooling:DX:SingleSpeed | SPLIT GNW COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 6946.45259 |
| 384 | Coil:Cooling:DX:SingleSpeed | SPLIT GNW COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
| 385 | Coil:Heating:Fuel | SPLIT GNW HEATING COIL | Design Size Nominal Capacity [W] | 9299.81028 |
| 386 | Controller:OutdoorAir | SPLIT OFFICE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.45307 |
| 387 | Controller:OutdoorAir | SPLIT OFFICE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 3.81060E-002 |
| 388 | AirLoopHVAC:UnitarySystem | SPLIT OFFICE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.45307 |
| 389 | AirLoopHVAC:UnitarySystem | SPLIT OFFICE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.45307 |
| 390 | AirLoopHVAC:UnitarySystem | SPLIT OFFICE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.45307 |
| 391 | AirLoopHVAC:UnitarySystem | SPLIT OFFICE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.45307 |
| 392 | AirLoopHVAC:UnitarySystem | SPLIT OFFICE_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 7499.94276 |
| 393 | AirLoopHVAC:UnitarySystem | SPLIT OFFICE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 10269.02227 |
| 394 | AirLoopHVAC:UnitarySystem | SPLIT OFFICE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 395 | AirLoopHVAC:UnitarySystem | SPLIT OFFICE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 396 | Fan:OnOff | SPLIT OFFICE SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.45307 |
| 397 | Coil:Cooling:DX:SingleSpeed | SPLIT OFFICE COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.45307 |
| 398 | Coil:Cooling:DX:SingleSpeed | SPLIT OFFICE COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 7499.94276 |
| 399 | Coil:Cooling:DX:SingleSpeed | SPLIT OFFICE COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
| 400 | Coil:Heating:Fuel | SPLIT OFFICE HEATING COIL | Design Size Nominal Capacity [W] | 10269.02227 |
| 401 | Controller:OutdoorAir | SPLIT GNE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.39438 |
| 402 | Controller:OutdoorAir | SPLIT GNE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.59546E-002 |
| 403 | AirLoopHVAC:UnitarySystem | SPLIT GNE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.39438 |
| 404 | AirLoopHVAC:UnitarySystem | SPLIT GNE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.39438 |
| 405 | AirLoopHVAC:UnitarySystem | SPLIT GNE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.39438 |
| 406 | AirLoopHVAC:UnitarySystem | SPLIT GNE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.39438 |
| 407 | AirLoopHVAC:UnitarySystem | SPLIT GNE_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 6528.31114 |
| 408 | AirLoopHVAC:UnitarySystem | SPLIT GNE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 8775.36247 |
| 409 | AirLoopHVAC:UnitarySystem | SPLIT GNE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 410 | AirLoopHVAC:UnitarySystem | SPLIT GNE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 411 | Fan:OnOff | SPLIT GNE SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.39438 |
| 412 | Coil:Cooling:DX:SingleSpeed | SPLIT GNE COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.39438 |
| 413 | Coil:Cooling:DX:SingleSpeed | SPLIT GNE COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 6528.31114 |
| 414 | Coil:Cooling:DX:SingleSpeed | SPLIT GNE COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
| 415 | Coil:Heating:Fuel | SPLIT GNE HEATING COIL | Design Size Nominal Capacity [W] | 8775.36247 |
| 416 | Controller:OutdoorAir | SPLIT GN1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.34824 |
| 417 | Controller:OutdoorAir | SPLIT GN1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.59546E-002 |
| 418 | AirLoopHVAC:UnitarySystem | SPLIT GN1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.34824 |
| 419 | AirLoopHVAC:UnitarySystem | SPLIT GN1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.34824 |
| 420 | AirLoopHVAC:UnitarySystem | SPLIT GN1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.34824 |
| 421 | AirLoopHVAC:UnitarySystem | SPLIT GN1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.34824 |
| 422 | AirLoopHVAC:UnitarySystem | SPLIT GN1_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 5764.57270 |
| 423 | AirLoopHVAC:UnitarySystem | SPLIT GN1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 7817.37624 |
| 424 | AirLoopHVAC:UnitarySystem | SPLIT GN1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 425 | AirLoopHVAC:UnitarySystem | SPLIT GN1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 426 | Fan:OnOff | SPLIT GN1 SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.34824 |
| 427 | Coil:Cooling:DX:SingleSpeed | SPLIT GN1 COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.34824 |
| 428 | Coil:Cooling:DX:SingleSpeed | SPLIT GN1 COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 5764.57270 |
| 429 | Coil:Cooling:DX:SingleSpeed | SPLIT GN1 COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
| 430 | Coil:Heating:Fuel | SPLIT GN1 HEATING COIL | Design Size Nominal Capacity [W] | 7817.37624 |
| 431 | Controller:OutdoorAir | SPLIT GN2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.34779 |
| 432 | Controller:OutdoorAir | SPLIT GN2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.59546E-002 |
| 433 | AirLoopHVAC:UnitarySystem | SPLIT GN2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.34779 |
| 434 | AirLoopHVAC:UnitarySystem | SPLIT GN2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.34779 |
| 435 | AirLoopHVAC:UnitarySystem | SPLIT GN2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.34779 |
| 436 | AirLoopHVAC:UnitarySystem | SPLIT GN2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.34779 |
| 437 | AirLoopHVAC:UnitarySystem | SPLIT GN2_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 5757.17496 |
| 438 | AirLoopHVAC:UnitarySystem | SPLIT GN2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 7808.09784 |
| 439 | AirLoopHVAC:UnitarySystem | SPLIT GN2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 440 | AirLoopHVAC:UnitarySystem | SPLIT GN2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 441 | Fan:OnOff | SPLIT GN2 SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.34779 |
| 442 | Coil:Cooling:DX:SingleSpeed | SPLIT GN2 COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.34779 |
| 443 | Coil:Cooling:DX:SingleSpeed | SPLIT GN2 COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 5757.17496 |
| 444 | Coil:Cooling:DX:SingleSpeed | SPLIT GN2 COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
| 445 | Coil:Heating:Fuel | SPLIT GN2 HEATING COIL | Design Size Nominal Capacity [W] | 7808.09784 |
| 446 | Controller:OutdoorAir | SPLIT GS1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.35412 |
| 447 | Controller:OutdoorAir | SPLIT GS1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.59546E-002 |
| 448 | AirLoopHVAC:UnitarySystem | SPLIT GS1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.35412 |
| 449 | AirLoopHVAC:UnitarySystem | SPLIT GS1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.35412 |
| 450 | AirLoopHVAC:UnitarySystem | SPLIT GS1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.35412 |
| 451 | AirLoopHVAC:UnitarySystem | SPLIT GS1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.35412 |
| 452 | AirLoopHVAC:UnitarySystem | SPLIT GS1_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 5861.90057 |
| 453 | AirLoopHVAC:UnitarySystem | SPLIT GS1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 7939.57642 |
| 454 | AirLoopHVAC:UnitarySystem | SPLIT GS1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 455 | AirLoopHVAC:UnitarySystem | SPLIT GS1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 456 | Fan:OnOff | SPLIT GS1 SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.35412 |
| 457 | Coil:Cooling:DX:SingleSpeed | SPLIT GS1 COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.35412 |
| 458 | Coil:Cooling:DX:SingleSpeed | SPLIT GS1 COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 5861.90057 |
| 459 | Coil:Cooling:DX:SingleSpeed | SPLIT GS1 COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
| 460 | Coil:Heating:Fuel | SPLIT GS1 HEATING COIL | Design Size Nominal Capacity [W] | 7939.57642 |
| 461 | Controller:OutdoorAir | SPLIT GS2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.35679 |
| 462 | Controller:OutdoorAir | SPLIT GS2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.59546E-002 |
| 463 | AirLoopHVAC:UnitarySystem | SPLIT GS2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.35679 |
| 464 | AirLoopHVAC:UnitarySystem | SPLIT GS2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.35679 |
| 465 | AirLoopHVAC:UnitarySystem | SPLIT GS2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.35679 |
| 466 | AirLoopHVAC:UnitarySystem | SPLIT GS2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.35679 |
| 467 | AirLoopHVAC:UnitarySystem | SPLIT GS2_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 5906.09940 |
| 468 | AirLoopHVAC:UnitarySystem | SPLIT GS2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 7995.01223 |
| 469 | AirLoopHVAC:UnitarySystem | SPLIT GS2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 470 | AirLoopHVAC:UnitarySystem | SPLIT GS2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 471 | Fan:OnOff | SPLIT GS2 SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.35679 |
| 472 | Coil:Cooling:DX:SingleSpeed | SPLIT GS2 COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.35679 |
| 473 | Coil:Cooling:DX:SingleSpeed | SPLIT GS2 COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 5906.09940 |
| 474 | Coil:Cooling:DX:SingleSpeed | SPLIT GS2 COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
| 475 | Coil:Heating:Fuel | SPLIT GS2 HEATING COIL | Design Size Nominal Capacity [W] | 7995.01223 |
| 476 | Controller:OutdoorAir | SPLIT MSW_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.96572 |
| 477 | Controller:OutdoorAir | SPLIT MSW_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 5.19091E-002 |
| 478 | AirLoopHVAC:UnitarySystem | SPLIT MSW_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.96572 |
| 479 | AirLoopHVAC:UnitarySystem | SPLIT MSW_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.96572 |
| 480 | AirLoopHVAC:UnitarySystem | SPLIT MSW_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.96572 |
| 481 | AirLoopHVAC:UnitarySystem | SPLIT MSW_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.96572 |
| 482 | AirLoopHVAC:UnitarySystem | SPLIT MSW_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 15986.10138 |
| 483 | AirLoopHVAC:UnitarySystem | SPLIT MSW_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 21225.51569 |
| 484 | AirLoopHVAC:UnitarySystem | SPLIT MSW_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 485 | AirLoopHVAC:UnitarySystem | SPLIT MSW_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 486 | Fan:OnOff | SPLIT MSW SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.96572 |
| 487 | Coil:Cooling:DX:SingleSpeed | SPLIT MSW COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.96572 |
| 488 | Coil:Cooling:DX:SingleSpeed | SPLIT MSW COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 15986.10138 |
| 489 | Coil:Cooling:DX:SingleSpeed | SPLIT MSW COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
| 490 | Coil:Heating:Fuel | SPLIT MSW HEATING COIL | Design Size Nominal Capacity [W] | 21225.51569 |
| 491 | Controller:OutdoorAir | SPLIT MNW_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.95705 |
| 492 | Controller:OutdoorAir | SPLIT MNW_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 5.19091E-002 |
| 493 | AirLoopHVAC:UnitarySystem | SPLIT MNW_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.95705 |
| 494 | AirLoopHVAC:UnitarySystem | SPLIT MNW_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.95705 |
| 495 | AirLoopHVAC:UnitarySystem | SPLIT MNW_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.95705 |
| 496 | AirLoopHVAC:UnitarySystem | SPLIT MNW_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.95705 |
| 497 | AirLoopHVAC:UnitarySystem | SPLIT MNW_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 15842.64203 |
| 498 | AirLoopHVAC:UnitarySystem | SPLIT MNW_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 21045.25991 |
| 499 | AirLoopHVAC:UnitarySystem | SPLIT MNW_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 500 | AirLoopHVAC:UnitarySystem | SPLIT MNW_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 501 | Fan:OnOff | SPLIT MNW SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.95705 |
| 502 | Coil:Cooling:DX:SingleSpeed | SPLIT MNW COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.95705 |
| 503 | Coil:Cooling:DX:SingleSpeed | SPLIT MNW COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 15842.64203 |
| 504 | Coil:Cooling:DX:SingleSpeed | SPLIT MNW COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
| 505 | Coil:Heating:Fuel | SPLIT MNW HEATING COIL | Design Size Nominal Capacity [W] | 21045.25991 |
| 506 | Controller:OutdoorAir | SPLIT MSE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.89842 |
| 507 | Controller:OutdoorAir | SPLIT MSE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 5.19091E-002 |
| 508 | AirLoopHVAC:UnitarySystem | SPLIT MSE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.89842 |
| 509 | AirLoopHVAC:UnitarySystem | SPLIT MSE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.89842 |
| 510 | AirLoopHVAC:UnitarySystem | SPLIT MSE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.89842 |
| 511 | AirLoopHVAC:UnitarySystem | SPLIT MSE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.89842 |
| 512 | AirLoopHVAC:UnitarySystem | SPLIT MSE_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 14872.00118 |
| 513 | AirLoopHVAC:UnitarySystem | SPLIT MSE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 19828.13256 |
| 514 | AirLoopHVAC:UnitarySystem | SPLIT MSE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 515 | AirLoopHVAC:UnitarySystem | SPLIT MSE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 516 | Fan:OnOff | SPLIT MSE SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.89842 |
| 517 | Coil:Cooling:DX:SingleSpeed | SPLIT MSE COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.89842 |
| 518 | Coil:Cooling:DX:SingleSpeed | SPLIT MSE COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 14872.00118 |
| 519 | Coil:Cooling:DX:SingleSpeed | SPLIT MSE COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
| 520 | Coil:Heating:Fuel | SPLIT MSE HEATING COIL | Design Size Nominal Capacity [W] | 19828.13256 |
| 521 | Controller:OutdoorAir | SPLIT MNE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.88987 |
| 522 | Controller:OutdoorAir | SPLIT MNE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 5.19091E-002 |
| 523 | AirLoopHVAC:UnitarySystem | SPLIT MNE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.88987 |
| 524 | AirLoopHVAC:UnitarySystem | SPLIT MNE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.88987 |
| 525 | AirLoopHVAC:UnitarySystem | SPLIT MNE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.88987 |
| 526 | AirLoopHVAC:UnitarySystem | SPLIT MNE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.88987 |
| 527 | AirLoopHVAC:UnitarySystem | SPLIT MNE_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 14730.58868 |
| 528 | AirLoopHVAC:UnitarySystem | SPLIT MNE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 19650.46773 |
| 529 | AirLoopHVAC:UnitarySystem | SPLIT MNE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 530 | AirLoopHVAC:UnitarySystem | SPLIT MNE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 531 | Fan:OnOff | SPLIT MNE SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.88987 |
| 532 | Coil:Cooling:DX:SingleSpeed | SPLIT MNE COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.88987 |
| 533 | Coil:Cooling:DX:SingleSpeed | SPLIT MNE COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 14730.58868 |
| 534 | Coil:Cooling:DX:SingleSpeed | SPLIT MNE COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
| 535 | Coil:Heating:Fuel | SPLIT MNE HEATING COIL | Design Size Nominal Capacity [W] | 19650.46773 |
| 536 | Controller:OutdoorAir | SPLIT MN1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.77775 |
| 537 | Controller:OutdoorAir | SPLIT MN1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 5.19091E-002 |
| 538 | AirLoopHVAC:UnitarySystem | SPLIT MN1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.77775 |
| 539 | AirLoopHVAC:UnitarySystem | SPLIT MN1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.77775 |
| 540 | AirLoopHVAC:UnitarySystem | SPLIT MN1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.77775 |
| 541 | AirLoopHVAC:UnitarySystem | SPLIT MN1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.77775 |
| 542 | AirLoopHVAC:UnitarySystem | SPLIT MN1_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 12874.56295 |
| 543 | AirLoopHVAC:UnitarySystem | SPLIT MN1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 17322.31954 |
| 544 | AirLoopHVAC:UnitarySystem | SPLIT MN1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 545 | AirLoopHVAC:UnitarySystem | SPLIT MN1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 546 | Fan:OnOff | SPLIT MN1 SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.77775 |
| 547 | Coil:Cooling:DX:SingleSpeed | SPLIT MN1 COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.77775 |
| 548 | Coil:Cooling:DX:SingleSpeed | SPLIT MN1 COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 12874.56295 |
| 549 | Coil:Cooling:DX:SingleSpeed | SPLIT MN1 COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
| 550 | Coil:Heating:Fuel | SPLIT MN1 HEATING COIL | Design Size Nominal Capacity [W] | 17322.31954 |
| 551 | Controller:OutdoorAir | SPLIT MN2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.77663 |
| 552 | Controller:OutdoorAir | SPLIT MN2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 5.19091E-002 |
| 553 | AirLoopHVAC:UnitarySystem | SPLIT MN2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.77663 |
| 554 | AirLoopHVAC:UnitarySystem | SPLIT MN2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.77663 |
| 555 | AirLoopHVAC:UnitarySystem | SPLIT MN2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.77663 |
| 556 | AirLoopHVAC:UnitarySystem | SPLIT MN2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.77663 |
| 557 | AirLoopHVAC:UnitarySystem | SPLIT MN2_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 12855.98633 |
| 558 | AirLoopHVAC:UnitarySystem | SPLIT MN2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 17299.02017 |
| 559 | AirLoopHVAC:UnitarySystem | SPLIT MN2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 560 | AirLoopHVAC:UnitarySystem | SPLIT MN2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 561 | Fan:OnOff | SPLIT MN2 SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.77663 |
| 562 | Coil:Cooling:DX:SingleSpeed | SPLIT MN2 COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.77663 |
| 563 | Coil:Cooling:DX:SingleSpeed | SPLIT MN2 COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 12855.98633 |
| 564 | Coil:Cooling:DX:SingleSpeed | SPLIT MN2 COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
| 565 | Coil:Heating:Fuel | SPLIT MN2 HEATING COIL | Design Size Nominal Capacity [W] | 17299.02017 |
| 566 | Controller:OutdoorAir | SPLIT MS1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.78838 |
| 567 | Controller:OutdoorAir | SPLIT MS1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 5.19091E-002 |
| 568 | AirLoopHVAC:UnitarySystem | SPLIT MS1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.78838 |
| 569 | AirLoopHVAC:UnitarySystem | SPLIT MS1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.78838 |
| 570 | AirLoopHVAC:UnitarySystem | SPLIT MS1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.78838 |
| 571 | AirLoopHVAC:UnitarySystem | SPLIT MS1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.78838 |
| 572 | AirLoopHVAC:UnitarySystem | SPLIT MS1_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 13050.42301 |
| 573 | AirLoopHVAC:UnitarySystem | SPLIT MS1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 17543.15582 |
| 574 | AirLoopHVAC:UnitarySystem | SPLIT MS1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 575 | AirLoopHVAC:UnitarySystem | SPLIT MS1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 576 | Fan:OnOff | SPLIT MS1 SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.78838 |
| 577 | Coil:Cooling:DX:SingleSpeed | SPLIT MS1 COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.78838 |
| 578 | Coil:Cooling:DX:SingleSpeed | SPLIT MS1 COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 13050.42301 |
| 579 | Coil:Cooling:DX:SingleSpeed | SPLIT MS1 COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
| 580 | Coil:Heating:Fuel | SPLIT MS1 HEATING COIL | Design Size Nominal Capacity [W] | 17543.15582 |
| 581 | Controller:OutdoorAir | SPLIT MS2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.78723 |
| 582 | Controller:OutdoorAir | SPLIT MS2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 5.19091E-002 |
| 583 | AirLoopHVAC:UnitarySystem | SPLIT MS2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.78723 |
| 584 | AirLoopHVAC:UnitarySystem | SPLIT MS2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.78723 |
| 585 | AirLoopHVAC:UnitarySystem | SPLIT MS2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.78723 |
| 586 | AirLoopHVAC:UnitarySystem | SPLIT MS2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.78723 |
| 587 | AirLoopHVAC:UnitarySystem | SPLIT MS2_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 13031.49604 |
| 588 | AirLoopHVAC:UnitarySystem | SPLIT MS2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 17519.41662 |
| 589 | AirLoopHVAC:UnitarySystem | SPLIT MS2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 590 | AirLoopHVAC:UnitarySystem | SPLIT MS2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 591 | Fan:OnOff | SPLIT MS2 SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.78723 |
| 592 | Coil:Cooling:DX:SingleSpeed | SPLIT MS2 COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.78723 |
| 593 | Coil:Cooling:DX:SingleSpeed | SPLIT MS2 COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 13031.49604 |
| 594 | Coil:Cooling:DX:SingleSpeed | SPLIT MS2 COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
| 595 | Coil:Heating:Fuel | SPLIT MS2 HEATING COIL | Design Size Nominal Capacity [W] | 17519.41662 |
| 596 | Controller:OutdoorAir | SPLIT TSW_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.55419 |
| 597 | Controller:OutdoorAir | SPLIT TSW_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.59546E-002 |
| 598 | AirLoopHVAC:UnitarySystem | SPLIT TSW_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.55419 |
| 599 | AirLoopHVAC:UnitarySystem | SPLIT TSW_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.55419 |
| 600 | AirLoopHVAC:UnitarySystem | SPLIT TSW_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.55419 |
| 601 | AirLoopHVAC:UnitarySystem | SPLIT TSW_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.55419 |
| 602 | AirLoopHVAC:UnitarySystem | SPLIT TSW_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 9173.88086 |
| 603 | AirLoopHVAC:UnitarySystem | SPLIT TSW_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 12094.00806 |
| 604 | AirLoopHVAC:UnitarySystem | SPLIT TSW_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 605 | AirLoopHVAC:UnitarySystem | SPLIT TSW_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 606 | Fan:OnOff | SPLIT TSW SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.55419 |
| 607 | Coil:Cooling:DX:SingleSpeed | SPLIT TSW COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.55419 |
| 608 | Coil:Cooling:DX:SingleSpeed | SPLIT TSW COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 9173.88086 |
| 609 | Coil:Cooling:DX:SingleSpeed | SPLIT TSW COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
| 610 | Coil:Heating:Fuel | SPLIT TSW HEATING COIL | Design Size Nominal Capacity [W] | 12094.00806 |
| 611 | Controller:OutdoorAir | SPLIT TNW_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.55391 |
| 612 | Controller:OutdoorAir | SPLIT TNW_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.59546E-002 |
| 613 | AirLoopHVAC:UnitarySystem | SPLIT TNW_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.55391 |
| 614 | AirLoopHVAC:UnitarySystem | SPLIT TNW_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.55391 |
| 615 | AirLoopHVAC:UnitarySystem | SPLIT TNW_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.55391 |
| 616 | AirLoopHVAC:UnitarySystem | SPLIT TNW_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.55391 |
| 617 | AirLoopHVAC:UnitarySystem | SPLIT TNW_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 9169.11089 |
| 618 | AirLoopHVAC:UnitarySystem | SPLIT TNW_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 12087.83376 |
| 619 | AirLoopHVAC:UnitarySystem | SPLIT TNW_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 620 | AirLoopHVAC:UnitarySystem | SPLIT TNW_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 621 | Fan:OnOff | SPLIT TNW SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.55391 |
| 622 | Coil:Cooling:DX:SingleSpeed | SPLIT TNW COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.55391 |
| 623 | Coil:Cooling:DX:SingleSpeed | SPLIT TNW COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 9169.11089 |
| 624 | Coil:Cooling:DX:SingleSpeed | SPLIT TNW COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
| 625 | Coil:Heating:Fuel | SPLIT TNW HEATING COIL | Design Size Nominal Capacity [W] | 12087.83376 |
| 626 | Controller:OutdoorAir | SPLIT TSE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.50349 |
| 627 | Controller:OutdoorAir | SPLIT TSE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.59546E-002 |
| 628 | AirLoopHVAC:UnitarySystem | SPLIT TSE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.50349 |
| 629 | AirLoopHVAC:UnitarySystem | SPLIT TSE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.50349 |
| 630 | AirLoopHVAC:UnitarySystem | SPLIT TSE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.50349 |
| 631 | AirLoopHVAC:UnitarySystem | SPLIT TSE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.50349 |
| 632 | AirLoopHVAC:UnitarySystem | SPLIT TSE_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 8334.51301 |
| 633 | AirLoopHVAC:UnitarySystem | SPLIT TSE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 11041.19731 |
| 634 | AirLoopHVAC:UnitarySystem | SPLIT TSE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 635 | AirLoopHVAC:UnitarySystem | SPLIT TSE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 636 | Fan:OnOff | SPLIT TSE SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.50349 |
| 637 | Coil:Cooling:DX:SingleSpeed | SPLIT TSE COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.50349 |
| 638 | Coil:Cooling:DX:SingleSpeed | SPLIT TSE COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 8334.51301 |
| 639 | Coil:Cooling:DX:SingleSpeed | SPLIT TSE COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
| 640 | Coil:Heating:Fuel | SPLIT TSE HEATING COIL | Design Size Nominal Capacity [W] | 11041.19731 |
| 641 | Controller:OutdoorAir | SPLIT TNE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.50313 |
| 642 | Controller:OutdoorAir | SPLIT TNE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.59546E-002 |
| 643 | AirLoopHVAC:UnitarySystem | SPLIT TNE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.50313 |
| 644 | AirLoopHVAC:UnitarySystem | SPLIT TNE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.50313 |
| 645 | AirLoopHVAC:UnitarySystem | SPLIT TNE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.50313 |
| 646 | AirLoopHVAC:UnitarySystem | SPLIT TNE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.50313 |
| 647 | AirLoopHVAC:UnitarySystem | SPLIT TNE_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 8328.57814 |
| 648 | AirLoopHVAC:UnitarySystem | SPLIT TNE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 11033.58030 |
| 649 | AirLoopHVAC:UnitarySystem | SPLIT TNE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 650 | AirLoopHVAC:UnitarySystem | SPLIT TNE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 651 | Fan:OnOff | SPLIT TNE SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.50313 |
| 652 | Coil:Cooling:DX:SingleSpeed | SPLIT TNE COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.50313 |
| 653 | Coil:Cooling:DX:SingleSpeed | SPLIT TNE COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 8328.57814 |
| 654 | Coil:Cooling:DX:SingleSpeed | SPLIT TNE COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
| 655 | Coil:Heating:Fuel | SPLIT TNE HEATING COIL | Design Size Nominal Capacity [W] | 11033.58030 |
| 656 | Controller:OutdoorAir | SPLIT TN1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.45132 |
| 657 | Controller:OutdoorAir | SPLIT TN1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.59546E-002 |
| 658 | AirLoopHVAC:UnitarySystem | SPLIT TN1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.45132 |
| 659 | AirLoopHVAC:UnitarySystem | SPLIT TN1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.45132 |
| 660 | AirLoopHVAC:UnitarySystem | SPLIT TN1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.45132 |
| 661 | AirLoopHVAC:UnitarySystem | SPLIT TN1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.45132 |
| 662 | AirLoopHVAC:UnitarySystem | SPLIT TN1_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 7470.87108 |
| 663 | AirLoopHVAC:UnitarySystem | SPLIT TN1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 9957.59198 |
| 664 | AirLoopHVAC:UnitarySystem | SPLIT TN1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 665 | AirLoopHVAC:UnitarySystem | SPLIT TN1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 666 | Fan:OnOff | SPLIT TN1 SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.45132 |
| 667 | Coil:Cooling:DX:SingleSpeed | SPLIT TN1 COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.45132 |
| 668 | Coil:Cooling:DX:SingleSpeed | SPLIT TN1 COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 7470.87108 |
| 669 | Coil:Cooling:DX:SingleSpeed | SPLIT TN1 COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
| 670 | Coil:Heating:Fuel | SPLIT TN1 HEATING COIL | Design Size Nominal Capacity [W] | 9957.59198 |
| 671 | Controller:OutdoorAir | SPLIT TN2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.44977 |
| 672 | Controller:OutdoorAir | SPLIT TN2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.59546E-002 |
| 673 | AirLoopHVAC:UnitarySystem | SPLIT TN2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.44977 |
| 674 | AirLoopHVAC:UnitarySystem | SPLIT TN2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.44977 |
| 675 | AirLoopHVAC:UnitarySystem | SPLIT TN2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.44977 |
| 676 | AirLoopHVAC:UnitarySystem | SPLIT TN2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.44977 |
| 677 | AirLoopHVAC:UnitarySystem | SPLIT TN2_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 7445.30826 |
| 678 | AirLoopHVAC:UnitarySystem | SPLIT TN2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 9925.53005 |
| 679 | AirLoopHVAC:UnitarySystem | SPLIT TN2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 680 | AirLoopHVAC:UnitarySystem | SPLIT TN2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 681 | Fan:OnOff | SPLIT TN2 SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.44977 |
| 682 | Coil:Cooling:DX:SingleSpeed | SPLIT TN2 COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.44977 |
| 683 | Coil:Cooling:DX:SingleSpeed | SPLIT TN2 COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 7445.30826 |
| 684 | Coil:Cooling:DX:SingleSpeed | SPLIT TN2 COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
| 685 | Coil:Heating:Fuel | SPLIT TN2 HEATING COIL | Design Size Nominal Capacity [W] | 9925.53005 |
| 686 | Controller:OutdoorAir | SPLIT TS1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.45219 |
| 687 | Controller:OutdoorAir | SPLIT TS1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.59546E-002 |
| 688 | AirLoopHVAC:UnitarySystem | SPLIT TS1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.45219 |
| 689 | AirLoopHVAC:UnitarySystem | SPLIT TS1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.45219 |
| 690 | AirLoopHVAC:UnitarySystem | SPLIT TS1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.45219 |
| 691 | AirLoopHVAC:UnitarySystem | SPLIT TS1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.45219 |
| 692 | AirLoopHVAC:UnitarySystem | SPLIT TS1_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 7485.39023 |
| 693 | AirLoopHVAC:UnitarySystem | SPLIT TS1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 9975.96531 |
| 694 | AirLoopHVAC:UnitarySystem | SPLIT TS1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 695 | AirLoopHVAC:UnitarySystem | SPLIT TS1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 696 | Fan:OnOff | SPLIT TS1 SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.45219 |
| 697 | Coil:Cooling:DX:SingleSpeed | SPLIT TS1 COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.45219 |
| 698 | Coil:Cooling:DX:SingleSpeed | SPLIT TS1 COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 7485.39023 |
| 699 | Coil:Cooling:DX:SingleSpeed | SPLIT TS1 COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
| 700 | Coil:Heating:Fuel | SPLIT TS1 HEATING COIL | Design Size Nominal Capacity [W] | 9975.96531 |
| 701 | Controller:OutdoorAir | SPLIT TS2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.45066 |
| 702 | Controller:OutdoorAir | SPLIT TS2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.59546E-002 |
| 703 | AirLoopHVAC:UnitarySystem | SPLIT TS2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.45066 |
| 704 | AirLoopHVAC:UnitarySystem | SPLIT TS2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.45066 |
| 705 | AirLoopHVAC:UnitarySystem | SPLIT TS2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.45066 |
| 706 | AirLoopHVAC:UnitarySystem | SPLIT TS2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.45066 |
| 707 | AirLoopHVAC:UnitarySystem | SPLIT TS2_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 7459.94857 |
| 708 | AirLoopHVAC:UnitarySystem | SPLIT TS2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 9944.05476 |
| 709 | AirLoopHVAC:UnitarySystem | SPLIT TS2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 710 | AirLoopHVAC:UnitarySystem | SPLIT TS2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 711 | Fan:OnOff | SPLIT TS2 SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.45066 |
| 712 | Coil:Cooling:DX:SingleSpeed | SPLIT TS2 COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.45066 |
| 713 | Coil:Cooling:DX:SingleSpeed | SPLIT TS2 COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 7459.94857 |
| 714 | Coil:Cooling:DX:SingleSpeed | SPLIT TS2 COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
| 715 | Coil:Heating:Fuel | SPLIT TS2 HEATING COIL | Design Size Nominal Capacity [W] | 9944.05476 |
| Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
| 1 | Coil:Cooling:DX:SingleSpeed | SPLIT GSW COOLING COIL | 6694.3 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 |
| 2 | Coil:Cooling:DX:SingleSpeed | SPLIT GNW COOLING COIL | 6617.6 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 |
| 3 | Coil:Cooling:DX:SingleSpeed | SPLIT OFFICE COOLING COIL | 7144.9 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 |
| 4 | Coil:Cooling:DX:SingleSpeed | SPLIT GNE COOLING COIL | 6219.2 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 |
| 5 | Coil:Cooling:DX:SingleSpeed | SPLIT GN1 COOLING COIL | 5491.7 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 |
| 6 | Coil:Cooling:DX:SingleSpeed | SPLIT GN2 COOLING COIL | 5484.6 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 |
| 7 | Coil:Cooling:DX:SingleSpeed | SPLIT GS1 COOLING COIL | 5584.4 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 |
| 8 | Coil:Cooling:DX:SingleSpeed | SPLIT GS2 COOLING COIL | 5626.5 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 |
| 9 | Coil:Cooling:DX:SingleSpeed | SPLIT MSW COOLING COIL | 15229.3 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 |
| 10 | Coil:Cooling:DX:SingleSpeed | SPLIT MNW COOLING COIL | 15092.6 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 |
| 11 | Coil:Cooling:DX:SingleSpeed | SPLIT MSE COOLING COIL | 14167.9 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 |
| 12 | Coil:Cooling:DX:SingleSpeed | SPLIT MNE COOLING COIL | 14033.2 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 |
| 13 | Coil:Cooling:DX:SingleSpeed | SPLIT MN1 COOLING COIL | 12265.0 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 |
| 14 | Coil:Cooling:DX:SingleSpeed | SPLIT MN2 COOLING COIL | 12247.4 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 |
| 15 | Coil:Cooling:DX:SingleSpeed | SPLIT MS1 COOLING COIL | 12432.6 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 |
| 16 | Coil:Cooling:DX:SingleSpeed | SPLIT MS2 COOLING COIL | 12414.6 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 |
| 17 | Coil:Cooling:DX:SingleSpeed | SPLIT TSW COOLING COIL | 8739.6 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 |
| 18 | Coil:Cooling:DX:SingleSpeed | SPLIT TNW COOLING COIL | 8735.0 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 |
| 19 | Coil:Cooling:DX:SingleSpeed | SPLIT TSE COOLING COIL | 7939.9 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 |
| 20 | Coil:Cooling:DX:SingleSpeed | SPLIT TNE COOLING COIL | 7934.3 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 |
| 21 | Coil:Cooling:DX:SingleSpeed | SPLIT TN1 COOLING COIL | 7117.2 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 |
| 22 | Coil:Cooling:DX:SingleSpeed | SPLIT TN2 COOLING COIL | 7092.8 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 |
| 23 | Coil:Cooling:DX:SingleSpeed | SPLIT TS1 COOLING COIL | 7131.0 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 |
| 24 | Coil:Cooling:DX:SingleSpeed | SPLIT TS2 COOLING COIL | 7106.8 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 |
| Zone Name | # Surfaces | |
| 1 | G SW APARTMENT | 9 |
| 2 | G NW APARTMENT | 9 |
| 3 | OFFICE | 9 |
| 4 | G NE APARTMENT | 9 |
| 5 | G N1 APARTMENT | 8 |
| 6 | G N2 APARTMENT | 8 |
| 7 | G S1 APARTMENT | 8 |
| 8 | G S2 APARTMENT | 8 |
| 9 | M SW APARTMENT | 9 |
| 10 | M NW APARTMENT | 9 |
| 11 | M SE APARTMENT | 9 |
| 12 | M NE APARTMENT | 9 |
| 13 | M N1 APARTMENT | 8 |
| 14 | M N2 APARTMENT | 8 |
| 15 | M S1 APARTMENT | 8 |
| 16 | M S2 APARTMENT | 8 |
| 17 | T SW APARTMENT | 9 |
| 18 | T NW APARTMENT | 9 |
| 19 | T SE APARTMENT | 9 |
| 20 | T NE APARTMENT | 9 |
| 21 | T N1 APARTMENT | 8 |
| 22 | T N2 APARTMENT | 8 |
| 23 | T S1 APARTMENT | 8 |
| 24 | T S2 APARTMENT | 8 |
| 25 | T CORRIDOR | 13 |
| 26 | G CORRIDOR | 13 |
| 27 | M CORRIDOR | 13 |
| Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
| 1 | G SWALL SWA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_GRD | 0.752 | 0.676 | 28.24 | 35.30 | 28.24 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 2 | GWINDOW1 S SWA | Window | G SWALL SWA | Window5 Detailed Fenestration | RESWINDOW_U_0.5369_SHGC_0.25 | N/A | 3.053 | No | 7.06 | 7.06 | 7.06 | 180.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 3 | G WWALL SWA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_GRD | 0.752 | 0.676 | 18.58 | 23.22 | 18.58 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 4 | GWINDOW1 W SWA | Window | G WWALL SWA | Window5 Detailed Fenestration | RESWINDOW_U_0.5369_SHGC_0.25 | N/A | 3.053 | No | 4.65 | 4.65 | 4.65 | 270.00 | 90.00 | 3.81 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 5 | G NIWALL SWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-G NIWALL SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 6 | G EIWALL SWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | iz-G EIWALL SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 7 | G GFLOOR SWA | Floor | CTF - ConductionTransferFunction | GGFLOORSWA_FFACTOR | 0.287 | 0.268 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 8 | G CEILIN SWA | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | G CEILIN SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 9 | G INTERNALMASS SWA | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 88.25 | 88.25 | 88.25 | 0.00 | 90.00 | 88.25 | 1.00 | 0.00 | G INTERNALMASS SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 10 | G NWALL NWA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_GRD | 0.752 | 0.676 | 28.24 | 35.30 | 28.24 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 11 | GWINDOW1 N NWA | Window | G NWALL NWA | Window5 Detailed Fenestration | RESWINDOW_U_0.5369_SHGC_0.25 | N/A | 3.053 | No | 7.06 | 7.06 | 7.06 | 0.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 12 | G WWALL NWA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_GRD | 0.752 | 0.676 | 18.58 | 23.22 | 18.58 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 13 | GWINDOW1 W NWA | Window | G WWALL NWA | Window5 Detailed Fenestration | RESWINDOW_U_0.5369_SHGC_0.25 | N/A | 3.053 | No | 4.65 | 4.65 | 4.65 | 270.00 | 90.00 | 3.81 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 14 | G SIWALL NWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-G SIWALL NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 15 | G EIWALL NWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | iz-G EIWALL NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 16 | G GFLOOR NWA | Floor | CTF - ConductionTransferFunction | GGFLOORNWA_FFACTOR | 0.287 | 0.268 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 17 | G CEILIN NWA | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | G CEILIN NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 18 | G INTERNALMASS NWA | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 88.25 | 88.25 | 88.25 | 0.00 | 90.00 | 88.25 | 1.00 | 0.00 | G INTERNALMASS NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 19 | G SWALL SEA | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.844 | 0.750 | 28.24 | 35.30 | 28.24 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 20 | GWINDOW1 S SEA | Window | G SWALL SEA | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5369_SHGC_0.25 | N/A | 3.053 | No | 7.06 | 7.06 | 7.06 | 180.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 21 | G EWALL SEA | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.844 | 0.750 | 18.58 | 23.22 | 18.58 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 22 | GWINDOW1 E SEA | Window | G EWALL SEA | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5369_SHGC_0.25 | N/A | 3.053 | No | 4.65 | 4.65 | 4.65 | 90.00 | 90.00 | 3.81 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 23 | G NIWALL SEA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-G NIWALL SEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 24 | iz-G EIWALL S2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | G EIWALL S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 25 | G GFLOOR SEA | Floor | CTF - ConductionTransferFunction | GGFLOORSEA_FFACTOR | 0.287 | 0.268 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 26 | G CEILIN SEA | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | G CEILIN SEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 27 | G INTERNALMASS SEA | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 88.25 | 88.25 | 88.25 | 0.00 | 90.00 | 88.25 | 1.00 | 0.00 | G INTERNALMASS SEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 28 | G NWALL NEA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_GRD | 0.752 | 0.676 | 28.24 | 35.30 | 28.24 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 29 | GWINDOW1 N NEA | Window | G NWALL NEA | Window5 Detailed Fenestration | RESWINDOW_U_0.5369_SHGC_0.25 | N/A | 3.053 | No | 7.06 | 7.06 | 7.06 | 0.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 30 | G EWALL NEA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_GRD | 0.752 | 0.676 | 18.58 | 23.22 | 18.58 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 31 | GWINDOW1 E NEA | Window | G EWALL NEA | Window5 Detailed Fenestration | RESWINDOW_U_0.5369_SHGC_0.25 | N/A | 3.053 | No | 4.65 | 4.65 | 4.65 | 90.00 | 90.00 | 3.81 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 32 | G SIWALL NEA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-G SIWALL NEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 33 | iz-G EIWALL N2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | G EIWALL N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 34 | G GFLOOR NEA | Floor | CTF - ConductionTransferFunction | GGFLOORNEA_FFACTOR | 0.287 | 0.268 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 35 | G CEILIN NEA | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | G CEILIN NEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 36 | G INTERNALMASS NEA | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 88.25 | 88.25 | 88.25 | 0.00 | 90.00 | 88.25 | 1.00 | 0.00 | G INTERNALMASS NEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 37 | G NWALL N1A | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_GRD | 0.752 | 0.676 | 28.24 | 35.30 | 28.24 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 38 | GWINDOW1 N N1A | Window | G NWALL N1A | Window5 Detailed Fenestration | RESWINDOW_U_0.5369_SHGC_0.25 | N/A | 3.053 | No | 7.06 | 7.06 | 7.06 | 0.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 39 | G SIWALL N1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-G SIWALL N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 40 | G EIWALL N1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | iz-G EIWALL N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 41 | iz-G EIWALL NWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | G EIWALL NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 42 | G GFLOOR N1A | Floor | CTF - ConductionTransferFunction | GGFLOORN1A_FFACTOR | 0.170 | 0.163 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 43 | G CEILIN N1A | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | G CEILIN N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 44 | G INTERNALMASS N1A | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 88.25 | 88.25 | 88.25 | 0.00 | 90.00 | 88.25 | 1.00 | 0.00 | G INTERNALMASS N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 45 | G NWALL N2A | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_GRD | 0.752 | 0.676 | 28.24 | 35.30 | 28.24 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 46 | GWINDOW1 N N2A | Window | G NWALL N2A | Window5 Detailed Fenestration | RESWINDOW_U_0.5369_SHGC_0.25 | N/A | 3.053 | No | 7.06 | 7.06 | 7.06 | 0.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 47 | G SIWALL N2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-G SIWALL N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 48 | G EIWALL N2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | iz-G EIWALL N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 49 | iz-G EIWALL N1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | G EIWALL N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 50 | G GFLOOR N2A | Floor | CTF - ConductionTransferFunction | GGFLOORN2A_FFACTOR | 0.170 | 0.163 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 51 | G CEILIN N2A | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | G CEILIN N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 52 | G INTERNALMASS N2A | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 88.25 | 88.25 | 88.25 | 0.00 | 90.00 | 88.25 | 1.00 | 0.00 | G INTERNALMASS N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 53 | G SWALL S1A | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_GRD | 0.752 | 0.676 | 28.24 | 35.30 | 28.24 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 54 | GWINDOW1 S S1A | Window | G SWALL S1A | Window5 Detailed Fenestration | RESWINDOW_U_0.5369_SHGC_0.25 | N/A | 3.053 | No | 7.06 | 7.06 | 7.06 | 180.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 55 | G NIWALL S1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-G NIWALL S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 56 | G EIWALL S1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | iz-G EIWALL S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 57 | iz-G EIWALL SWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | G EIWALL SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 58 | G GFLOOR S1A | Floor | CTF - ConductionTransferFunction | GGFLOORS1A_FFACTOR | 0.170 | 0.163 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 59 | G CEILIN S1A | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | G CEILIN S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 60 | G INTERNALMASS S1A | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 88.25 | 88.25 | 88.25 | 0.00 | 90.00 | 88.25 | 1.00 | 0.00 | G INTERNALMASS S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 61 | G SWALL S2A | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_GRD | 0.752 | 0.676 | 28.24 | 35.30 | 28.24 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 62 | GWINDOW1 S S2A | Window | G SWALL S2A | Window5 Detailed Fenestration | RESWINDOW_U_0.5369_SHGC_0.25 | N/A | 3.053 | No | 7.06 | 7.06 | 7.06 | 180.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 63 | G NIWALL S2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-G NIWALL S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 64 | G EIWALL S2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | iz-G EIWALL S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 65 | iz-G EIWALL S1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | G EIWALL S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 66 | G GFLOOR S2A | Floor | CTF - ConductionTransferFunction | GGFLOORS2A_FFACTOR | 0.170 | 0.163 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 67 | G CEILIN S2A | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | G CEILIN S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 68 | G INTERNALMASS S2A | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 88.25 | 88.25 | 88.25 | 0.00 | 90.00 | 88.25 | 1.00 | 0.00 | G INTERNALMASS S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 69 | M WWALL SWA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.761 | 0.683 | 18.58 | 23.22 | 18.58 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 70 | MWINDOW1 W SWA | Window | M WWALL SWA | Window5 Detailed Fenestration | RESWINDOW_U_0.5369_SHGC_0.25 | N/A | 3.053 | No | 4.65 | 4.65 | 4.65 | 270.00 | 90.00 | 3.81 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 71 | M SWALL SWA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.761 | 0.683 | 28.24 | 35.30 | 28.24 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 72 | MWINDOW1 S SWA | Window | M SWALL SWA | Window5 Detailed Fenestration | RESWINDOW_U_0.5369_SHGC_0.25 | N/A | 3.053 | No | 7.06 | 7.06 | 7.06 | 180.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 73 | M NIWALL SWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-M NIWALL SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 74 | M EIWALL SWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 90.00 | 90.00 | 3.05 | 7.62 | 0.00 | iz-M EIWALL SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 75 | M GFLOOR SWA | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | M GFLOOR SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 76 | M CEILIN SWA | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | M CEILIN SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 77 | M INTERNALMASS SWA | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 176.50 | 176.50 | 176.50 | 0.00 | 90.00 | 176.50 | 1.00 | 0.00 | M INTERNALMASS SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 78 | M NWALL NWA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.761 | 0.683 | 28.24 | 35.30 | 28.24 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 79 | MWINDOW1 N NWA | Window | M NWALL NWA | Window5 Detailed Fenestration | RESWINDOW_U_0.5369_SHGC_0.25 | N/A | 3.053 | No | 7.06 | 7.06 | 7.06 | 0.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 80 | M WWALL NWA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.761 | 0.683 | 18.58 | 23.22 | 18.58 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 81 | MWINDOW1 W NWA | Window | M WWALL NWA | Window5 Detailed Fenestration | RESWINDOW_U_0.5369_SHGC_0.25 | N/A | 3.053 | No | 4.65 | 4.65 | 4.65 | 270.00 | 90.00 | 3.81 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 82 | M SIWALL NWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-M SIWALL NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 83 | M EIWALL NWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | iz-M EIWALL NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 84 | M GFLOOR NWA | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | M GFLOOR NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 85 | M CEILIN NWA | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | M CEILIN NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 86 | M INTERNALMASS NWA | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 176.50 | 176.50 | 176.50 | 0.00 | 90.00 | 176.50 | 1.00 | 0.00 | M INTERNALMASS NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 87 | M EWALL SEA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.761 | 0.683 | 18.58 | 23.22 | 18.58 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 88 | MWINDOW1 E SEA | Window | M EWALL SEA | Window5 Detailed Fenestration | RESWINDOW_U_0.5369_SHGC_0.25 | N/A | 3.053 | No | 4.65 | 4.65 | 4.65 | 90.00 | 90.00 | 3.81 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 89 | M SWALL SEA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.761 | 0.683 | 28.24 | 35.30 | 28.24 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 90 | MWINDOW1 S SEA | Window | M SWALL SEA | Window5 Detailed Fenestration | RESWINDOW_U_0.5369_SHGC_0.25 | N/A | 3.053 | No | 7.06 | 7.06 | 7.06 | 180.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 91 | M NIWALL SEA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-M NIWALL SEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 92 | iz-M EIWALL S2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | M EIWALL S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 93 | M GFLOOR SEA | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | M GFLOOR SEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 94 | M CEILIN SEA | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | M CEILIN SEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 95 | M INTERNALMASS SEA | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 176.50 | 176.50 | 176.50 | 0.00 | 90.00 | 176.50 | 1.00 | 0.00 | M INTERNALMASS SEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 96 | M NWALL NEA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.761 | 0.683 | 28.24 | 35.30 | 28.24 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 97 | MWINDOW1 N NEA | Window | M NWALL NEA | Window5 Detailed Fenestration | RESWINDOW_U_0.5369_SHGC_0.25 | N/A | 3.053 | No | 7.06 | 7.06 | 7.06 | 0.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 98 | M EWALL NEA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.761 | 0.683 | 18.58 | 23.22 | 18.58 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 99 | MWINDOW1 E NEA | Window | M EWALL NEA | Window5 Detailed Fenestration | RESWINDOW_U_0.5369_SHGC_0.25 | N/A | 3.053 | No | 4.65 | 4.65 | 4.65 | 90.00 | 90.00 | 3.81 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 100 | M SIWALL NEA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-M SIWALL NEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 101 | iz-M EIWALL N2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | M EIWALL N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 102 | M GFLOOR NEA | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | M GFLOOR NEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 103 | M CEILIN NEA | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | M CEILIN NEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 104 | M INTERNALMASS NEA | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 176.50 | 176.50 | 176.50 | 0.00 | 90.00 | 176.50 | 1.00 | 0.00 | M INTERNALMASS NEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 105 | M NWALL N1A | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.761 | 0.683 | 28.24 | 35.30 | 28.24 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 106 | MWINDOW1 N N1A | Window | M NWALL N1A | Window5 Detailed Fenestration | RESWINDOW_U_0.5369_SHGC_0.25 | N/A | 3.053 | No | 7.06 | 7.06 | 7.06 | 0.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 107 | M SIWALL N1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-M SIWALL N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 108 | M EIWALL N1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | iz-M EIWALL N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 109 | iz-M EIWALL NWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | M EIWALL NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 110 | M GFLOOR N1A | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | M GFLOOR N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 111 | M CEILIN N1A | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | M CEILIN N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 112 | M INTERNALMASS N1A | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 176.50 | 176.50 | 176.50 | 0.00 | 90.00 | 176.50 | 1.00 | 0.00 | M INTERNALMASS N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 113 | M NWALL N2A | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.761 | 0.683 | 28.24 | 35.30 | 28.24 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 114 | MWINDOW1 N N2A | Window | M NWALL N2A | Window5 Detailed Fenestration | RESWINDOW_U_0.5369_SHGC_0.25 | N/A | 3.053 | No | 7.06 | 7.06 | 7.06 | 0.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 115 | M SIWALL N2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-M SIWALL N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 116 | M EIWALL N2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | iz-M EIWALL N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 117 | iz-M EIWALL N1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | M EIWALL N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 118 | M GFLOOR N2A | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | M GFLOOR N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 119 | M CEILIN N2A | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | M CEILIN N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 120 | M INTERNALMASS N2A | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 176.50 | 176.50 | 176.50 | 0.00 | 90.00 | 176.50 | 1.00 | 0.00 | M INTERNALMASS N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 121 | M SWALL S1A | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.761 | 0.683 | 28.24 | 35.30 | 28.24 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 122 | MWINDOW1 S S1A | Window | M SWALL S1A | Window5 Detailed Fenestration | RESWINDOW_U_0.5369_SHGC_0.25 | N/A | 3.053 | No | 7.06 | 7.06 | 7.06 | 180.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 123 | M NIWALL S1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-M NIWALL S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 124 | M EIWALL S1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | iz-M EIWALL S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 125 | iz-M EIWALL SWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 270.00 | 90.00 | 3.05 | 7.62 | 0.00 | M EIWALL SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 126 | M GFLOOR S1A | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | M GFLOOR S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 127 | M CEILIN S1A | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | M CEILIN S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 128 | M INTERNALMASS S1A | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 176.50 | 176.50 | 176.50 | 0.00 | 90.00 | 176.50 | 1.00 | 0.00 | M INTERNALMASS S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 129 | M SWALL S2A | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.761 | 0.683 | 28.24 | 35.30 | 28.24 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 130 | MWINDOW1 S S2A | Window | M SWALL S2A | Window5 Detailed Fenestration | RESWINDOW_U_0.5369_SHGC_0.25 | N/A | 3.053 | No | 7.06 | 7.06 | 7.06 | 180.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 131 | M NIWALL S2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-M NIWALL S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 132 | M EIWALL S2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | iz-M EIWALL S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 133 | iz-M EIWALL S1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | M EIWALL S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 134 | M GFLOOR S2A | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | M GFLOOR S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 135 | M CEILIN S2A | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | M CEILIN S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 136 | M INTERNALMASS S2A | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 176.50 | 176.50 | 176.50 | 0.00 | 90.00 | 176.50 | 1.00 | 0.00 | M INTERNALMASS S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 137 | T WWALL SWA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.098 | 0.943 | 18.58 | 23.22 | 18.58 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 138 | TWINDOW1 W SWA | Window | T WWALL SWA | Window5 Detailed Fenestration | RESWINDOW_U_0.5369_SHGC_0.25 | N/A | 3.053 | No | 4.65 | 4.65 | 4.65 | 270.00 | 90.00 | 3.81 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 139 | T SWALL SWA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.098 | 0.943 | 28.24 | 35.30 | 28.24 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 140 | TWINDOW1 S SWA | Window | T SWALL SWA | Window5 Detailed Fenestration | RESWINDOW_U_0.5369_SHGC_0.25 | N/A | 3.053 | No | 7.06 | 7.06 | 7.06 | 180.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 141 | T NIWALL SWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-T NIWALL SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 142 | T EIWALL SWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | iz-T EIWALL SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 143 | T GFLOOR SWA | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | T GFLOOR SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 144 | T ROOF SWA | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.283 | 0.269 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 145 | T INTERNALMASS SWA | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 88.25 | 88.25 | 88.25 | 0.00 | 90.00 | 88.25 | 1.00 | 0.00 | T INTERNALMASS SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 146 | T NWALL NWA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.098 | 0.943 | 28.24 | 35.30 | 28.24 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 147 | TWINDOW1 N NWA | Window | T NWALL NWA | Window5 Detailed Fenestration | RESWINDOW_U_0.5369_SHGC_0.25 | N/A | 3.053 | No | 7.06 | 7.06 | 7.06 | 0.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 148 | T WWALL NWA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.098 | 0.943 | 18.58 | 23.22 | 18.58 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 149 | TWINDOW1 W NWA | Window | T WWALL NWA | Window5 Detailed Fenestration | RESWINDOW_U_0.5369_SHGC_0.25 | N/A | 3.053 | No | 4.65 | 4.65 | 4.65 | 270.00 | 90.00 | 3.81 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 150 | T SIWALL NWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-T SIWALL NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 151 | T EIWALL NWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | iz-T EIWALL NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 152 | T GFLOOR NWA | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | T GFLOOR NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 153 | T ROOF NWA | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.283 | 0.269 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 154 | T INTERNALMASS NWA | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 88.25 | 88.25 | 88.25 | 0.00 | 90.00 | 88.25 | 1.00 | 0.00 | T INTERNALMASS NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 155 | T EWALL SEA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.098 | 0.943 | 18.58 | 23.22 | 18.58 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 156 | TWINDOW1 E SEA | Window | T EWALL SEA | Window5 Detailed Fenestration | RESWINDOW_U_0.5369_SHGC_0.25 | N/A | 3.053 | No | 4.65 | 4.65 | 4.65 | 90.00 | 90.00 | 3.81 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 157 | T SWALL SEA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.098 | 0.943 | 28.24 | 35.30 | 28.24 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 158 | TWINDOW1 S SEA | Window | T SWALL SEA | Window5 Detailed Fenestration | RESWINDOW_U_0.5369_SHGC_0.25 | N/A | 3.053 | No | 7.06 | 7.06 | 7.06 | 180.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 159 | T NIWALL SEA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-T NIWALL SEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 160 | iz-T EIWALL S2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | T EIWALL S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 161 | T GFLOOR SEA | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | T GFLOOR SEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 162 | T ROOF SEA | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.283 | 0.269 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 163 | T INTERNALMASS SEA | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 88.25 | 88.25 | 88.25 | 0.00 | 90.00 | 88.25 | 1.00 | 0.00 | T INTERNALMASS SEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 164 | T NWALL NEA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.098 | 0.943 | 28.24 | 35.30 | 28.24 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 165 | TWINDOW1 N NEA | Window | T NWALL NEA | Window5 Detailed Fenestration | RESWINDOW_U_0.5369_SHGC_0.25 | N/A | 3.053 | No | 7.06 | 7.06 | 7.06 | 0.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 166 | T EWALL NEA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.098 | 0.943 | 18.58 | 23.22 | 18.58 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 167 | TWINDOW1 E NEA | Window | T EWALL NEA | Window5 Detailed Fenestration | RESWINDOW_U_0.5369_SHGC_0.25 | N/A | 3.053 | No | 4.65 | 4.65 | 4.65 | 90.00 | 90.00 | 3.81 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 168 | T SIWALL NEA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-T SIWALL NEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 169 | iz-T EIWALL N2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | T EIWALL N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 170 | T GFLOOR NEA | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | T GFLOOR NEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 171 | T ROOF NEA | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.283 | 0.269 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 172 | T INTERNALMASS NEA | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 88.25 | 88.25 | 88.25 | 0.00 | 90.00 | 88.25 | 1.00 | 0.00 | T INTERNALMASS NEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 173 | T NWALL N1A | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.098 | 0.943 | 28.24 | 35.30 | 28.24 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 174 | TWINDOW1 N N1A | Window | T NWALL N1A | Window5 Detailed Fenestration | RESWINDOW_U_0.5369_SHGC_0.25 | N/A | 3.053 | No | 7.06 | 7.06 | 7.06 | 0.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 175 | T SIWALL N1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-T SIWALL N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 176 | T EIWALL N1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | iz-T EIWALL N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 177 | iz-T EIWALL NWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | T EIWALL NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 178 | T GFLOOR N1A | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | T GFLOOR N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 179 | T ROOF N1A | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.283 | 0.269 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 180 | T INTERNALMASS N1A | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 88.25 | 88.25 | 88.25 | 0.00 | 90.00 | 88.25 | 1.00 | 0.00 | T INTERNALMASS N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 181 | T NWALL N2A | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.098 | 0.943 | 28.24 | 35.30 | 28.24 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 182 | TWINDOW1 N N2A | Window | T NWALL N2A | Window5 Detailed Fenestration | RESWINDOW_U_0.5369_SHGC_0.25 | N/A | 3.053 | No | 7.06 | 7.06 | 7.06 | 0.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 183 | T SIWALL N2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-T SIWALL N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 184 | T EIWALL N2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | iz-T EIWALL N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 185 | iz-T EIWALL N1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | T EIWALL N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 186 | T GFLOOR N2A | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | T GFLOOR N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 187 | T ROOF N2A | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.283 | 0.269 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 188 | T INTERNALMASS N2A | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 88.25 | 88.25 | 88.25 | 0.00 | 90.00 | 88.25 | 1.00 | 0.00 | T INTERNALMASS N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 189 | T SWALL S1A | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.098 | 0.943 | 28.24 | 35.30 | 28.24 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 190 | TWINDOW1 S S1A | Window | T SWALL S1A | Window5 Detailed Fenestration | RESWINDOW_U_0.5369_SHGC_0.25 | N/A | 3.053 | No | 7.06 | 7.06 | 7.06 | 180.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 191 | T NIWALL S1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-T NIWALL S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 192 | T EIWALL S1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | iz-T EIWALL S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 193 | iz-T EIWALL SWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | T EIWALL SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 194 | T GFLOOR S1A | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | T GFLOOR S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 195 | T ROOF S1A | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.283 | 0.269 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 196 | T INTERNALMASS S1A | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 88.25 | 88.25 | 88.25 | 0.00 | 90.00 | 88.25 | 1.00 | 0.00 | T INTERNALMASS S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 197 | T SWALL S2A | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.098 | 0.943 | 28.24 | 35.30 | 28.24 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 198 | TWINDOW1 S S2A | Window | T SWALL S2A | Window5 Detailed Fenestration | RESWINDOW_U_0.5369_SHGC_0.25 | N/A | 3.053 | No | 7.06 | 7.06 | 7.06 | 180.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 199 | T NIWALL S2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-T NIWALL S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 200 | T EIWALL S2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | iz-T EIWALL S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 201 | iz-T EIWALL S1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | T EIWALL S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 202 | T GFLOOR S2A | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | T GFLOOR S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 203 | T ROOF S2A | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.283 | 0.269 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 204 | T INTERNALMASS S2A | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 88.25 | 88.25 | 88.25 | 0.00 | 90.00 | 88.25 | 1.00 | 0.00 | T INTERNALMASS S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 205 | T WWALL C | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.200 | 1.017 | 5.11 | 5.11 | 5.11 | 270.00 | 90.00 | 1.68 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 206 | T EWALL C | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.200 | 1.017 | 3.99 | 5.11 | 3.99 | 90.00 | 90.00 | 1.68 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 207 | TWINDOW14 | Window | T EWALL C | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5369_SHGC_0.25 | N/A | 3.053 | No | 1.11 | 1.11 | 1.11 | 90.00 | 90.00 | 0.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 208 | iz-T NIWALL SWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | T NIWALL SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 209 | iz-T NIWALL S1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | T NIWALL S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 210 | iz-T NIWALL S2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | T NIWALL S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 211 | iz-T NIWALL SEA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | T NIWALL SEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 212 | iz-T SIWALL NWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | T SIWALL NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 213 | iz-T SIWALL N1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | T SIWALL N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 214 | iz-T SIWALL N2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | T SIWALL N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 215 | iz-T SIWALL NEA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | T SIWALL NEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 216 | T FLOOR C | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 77.66 | 77.66 | 77.66 | 90.00 | 180.00 | 1.68 | 46.33 | 0.00 | T FLOOR C | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 217 | T ROOF C | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 77.66 | 77.66 | 77.66 | 180.00 | 0.00 | 46.33 | 1.68 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 218 | G WWALL C | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.844 | 0.750 | 5.11 | 5.11 | 5.11 | 270.00 | 90.00 | 1.68 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 219 | G EWALL C | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.844 | 0.750 | 1.79 | 5.11 | 1.79 | 90.00 | 90.00 | 1.68 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 220 | ENTRANCE DOOR | Window | G EWALL C | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5369_SHGC_0.25 | N/A | 3.053 | No | 3.32 | 3.32 | 3.32 | 90.00 | 90.00 | 1.57 | 2.11 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 221 | iz-G NIWALL SWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | G NIWALL SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 222 | iz-G NIWALL S1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | G NIWALL S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 223 | iz-G NIWALL S2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | G NIWALL S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 224 | iz-G NIWALL SEA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | G NIWALL SEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 225 | iz-G SIWALL NWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | G SIWALL NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 226 | iz-G SIWALL N1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | G SIWALL N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 227 | iz-G SIWALL N2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | G SIWALL N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 228 | iz-G SIWALL NEA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | G SIWALL NEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 229 | G FLOOR C | Floor | CTF - ConductionTransferFunction | GFLOORC_FFACTOR | 5.502E-002 | 5.429E-002 | 77.66 | 77.66 | 77.66 | 90.00 | 180.00 | 1.68 | 46.33 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 230 | G CEILING C | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 77.66 | 77.66 | 77.66 | 180.00 | 0.00 | 46.33 | 1.68 | 0.00 | G CEILING C | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 231 | M WWALL C | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.854 | 0.757 | 5.11 | 5.11 | 5.11 | 270.00 | 90.00 | 1.68 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 232 | M EWALL C | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.854 | 0.757 | 3.99 | 5.11 | 3.99 | 90.00 | 90.00 | 1.68 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 233 | MWINDOW14 | Window | M EWALL C | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5369_SHGC_0.25 | N/A | 3.053 | No | 1.11 | 1.11 | 1.11 | 90.00 | 90.00 | 0.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 234 | iz-M NIWALL SWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | M NIWALL SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 235 | iz-M NIWALL S1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | M NIWALL S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 236 | iz-M NIWALL S2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | M NIWALL S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 237 | iz-M NIWALL SEA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | M NIWALL SEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 238 | iz-M SIWALL NWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | M SIWALL NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 239 | iz-M SIWALL N1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | M SIWALL N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 240 | iz-M SIWALL N2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | M SIWALL N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 241 | iz-M SIWALL NEA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | M SIWALL NEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 242 | M FLOOR C | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 77.66 | 77.66 | 77.66 | 90.00 | 180.00 | 1.68 | 46.33 | 0.00 | M FLOOR C | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 243 | M CEILING C | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 77.66 | 77.66 | 77.66 | 180.00 | 0.00 | 46.33 | 1.68 | 0.00 | M CEILING C | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
| Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
| 1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | Yes | Yes | Yes | Clark and Allen |
| Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
| 1 | NEW YEAR'S DAY | Holiday | InputFile | 01/02 | 1Environment:Special Days |
| Daylight Saving Indicator | Source | Start Date | End Date | |
| 1 | Yes | InputFile | 03/12 | 11/05 |
| Style | Unit Conversion | |
| 1 | Commaandhtml | commaandhtml |
| Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
| 1 | G SW APARTMENT | RunPeriod: RUNPERIOD 1 | 4.0478723312E-002 | 3.8731774283E-002 | Pass | Pass | 3.1006684425E-002 | 3.6686728183E-002 | Pass | Pass |
| 2 | G NW APARTMENT | RunPeriod: RUNPERIOD 1 | 1.1926367195E-002 | 2.3259633100E-002 | Pass | Pass | 0.1792011209 | 0.5751714680 | Pass | Pass |
| 3 | OFFICE | RunPeriod: RUNPERIOD 1 | 5.3352170815E-002 | 3.5527861676E-002 | Pass | Pass | 2.0023758232 | 21.8392371146 | Pass | Pass |
| 4 | G NE APARTMENT | RunPeriod: RUNPERIOD 1 | 4.0619458200E-003 | 1.0098643680E-002 | Pass | Pass | 0.1312286126 | 0.3638366770 | Pass | Pass |
| 5 | G N1 APARTMENT | RunPeriod: RUNPERIOD 1 | 8.5229075359E-003 | 1.3993183784E-002 | Pass | Pass | 0.9064930884 | 8.5148731991 | Pass | Pass |
| 6 | G N2 APARTMENT | RunPeriod: RUNPERIOD 1 | 8.2785105697E-003 | 1.3537111427E-002 | Pass | Pass | 0.2706900163 | 1.2981260305 | Pass | Pass |
| 7 | G S1 APARTMENT | RunPeriod: RUNPERIOD 1 | 3.3311463164E-002 | 3.2361818976E-002 | Pass | Pass | 2.1984568337E-002 | 2.1995862695E-002 | Pass | Pass |
| 8 | G S2 APARTMENT | RunPeriod: RUNPERIOD 1 | 3.4320374045E-002 | 3.2703628927E-002 | Pass | Pass | 2.1746953763E-002 | 2.2757418715E-002 | Pass | Pass |
| 9 | M SW APARTMENT | RunPeriod: RUNPERIOD 1 | 4.0351630798E-002 | 4.0421726222E-002 | Pass | Pass | 3.4917108423E-002 | 3.9271248433E-002 | Pass | Pass |
| 10 | M NW APARTMENT | RunPeriod: RUNPERIOD 1 | 1.6718697188E-002 | 2.6439458433E-002 | Pass | Pass | 0.1453085245 | 0.4531574175 | Pass | Pass |
| 11 | M SE APARTMENT | RunPeriod: RUNPERIOD 1 | 4.0437597675E-002 | 4.0381800265E-002 | Pass | Pass | 3.2080450801E-002 | 3.3675710024E-002 | Pass | Pass |
| 12 | M NE APARTMENT | RunPeriod: RUNPERIOD 1 | 7.8313052080E-003 | 1.3143710923E-002 | Pass | Pass | 0.2583108926 | 1.9082274640 | Pass | Pass |
| 13 | M N1 APARTMENT | RunPeriod: RUNPERIOD 1 | 1.2661920298E-002 | 1.7563042848E-002 | Pass | Pass | 8.9653073878E-002 | 0.1237658411 | Pass | Pass |
| 14 | M N2 APARTMENT | RunPeriod: RUNPERIOD 1 | 1.2445566394E-002 | 1.7214551464E-002 | Pass | Pass | 0.1076358079 | 0.1615037226 | Pass | Pass |
| 15 | M S1 APARTMENT | RunPeriod: RUNPERIOD 1 | 2.9314176525E-002 | 3.4730316885E-002 | Pass | Pass | 2.4699326703E-002 | 2.2623348458E-002 | Pass | Pass |
| 16 | M S2 APARTMENT | RunPeriod: RUNPERIOD 1 | 2.9339106279E-002 | 3.4833298693E-002 | Pass | Pass | 2.4687989893E-002 | 2.2151790232E-002 | Pass | Pass |
| 17 | T SW APARTMENT | RunPeriod: RUNPERIOD 1 | 4.0279275864E-002 | 6.8372835889E-002 | Pass | Pass | 0.1657213901 | 0.6463197097 | Pass | Pass |
| 18 | T NW APARTMENT | RunPeriod: RUNPERIOD 1 | 1.8390819704E-002 | 4.0741690894E-002 | Pass | Pass | 0.1272758110 | 0.5092876635 | Pass | Pass |
| 19 | T SE APARTMENT | RunPeriod: RUNPERIOD 1 | 4.0278617120E-002 | 6.4469784839E-002 | Pass | Pass | 0.4583735507 | 3.4909610399 | Pass | Pass |
| 20 | T NE APARTMENT | RunPeriod: RUNPERIOD 1 | 1.9214256619E-003 | 6.5971819406E-003 | Pass | Pass | 0.1654768282 | 0.6007638937 | Pass | Pass |
| 21 | T N1 APARTMENT | RunPeriod: RUNPERIOD 1 | 6.4933345866E-003 | 1.5811824548E-002 | Pass | Pass | 0.3070307016 | 2.0709672482 | Pass | Pass |
| 22 | T N2 APARTMENT | RunPeriod: RUNPERIOD 1 | 6.1433237892E-003 | 1.4755181581E-002 | Pass | Pass | 1.9702266225 | 21.9833830567 | Pass | Pass |
| 23 | T S1 APARTMENT | RunPeriod: RUNPERIOD 1 | 4.0400136029E-002 | 6.4526414932E-002 | Pass | Pass | 0.1772639378 | 0.7470232550 | Pass | Pass |
| 24 | T S2 APARTMENT | RunPeriod: RUNPERIOD 1 | 4.0479257513E-002 | 6.4901658759E-002 | Pass | Pass | 0.2755162003 | 1.8648845845 | Pass | Pass |
| 25 | T CORRIDOR | RunPeriod: RUNPERIOD 1 | 4.3069180511E-002 | 2.3325001504E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
| 26 | G CORRIDOR | RunPeriod: RUNPERIOD 1 | 0.1815477376 | 0.5716015676 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
| 27 | M CORRIDOR | RunPeriod: RUNPERIOD 1 | 1.3492162142E-002 | 8.3291160488E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 09:17:08
Heat Emission by Components| Envelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
| Heat Emissions [GJ] | 1362.51 | 42.59 | 0.00 | 5.93 | 1229.74 | 2640.79 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 09:17:08
SizingPeriod:DesignDay| Maximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
| TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 0.50 | 0.00 | 0.50 | Wetbulb [C] | 2.10 | 140.00 |
| TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 40.80 | 13.30 | 18.50 | Wetbulb [C] | 4.80 | 310.00 |
| Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
| Jan | 3.00 | 2 | |||
| Feb | 34.00 | 28 | |||
| Mar | 40.00 | 18 | |||
| Apr | 0.00 | 0 | |||
| May | 0.00 | 0 | |||
| Jun | 0.00 | 0 | |||
| Jul | 81.00 | 18 | |||
| Aug | 71.00 | 20 | |||
| Sep | 27.00 | 12 | |||
| Oct | 9.00 | 6 | |||
| Nov | 35.00 | 14 | |||
| Dec | 0.00 | 0 |
| Value | |
| None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 09:17:08
Opaque Exterior| Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
| G SWALL SWA | RES_EXT_WALL_GRD | 0.30 | 0.676 | 0.752 | 35.30 | 28.24 | 180.00 | 90.00 | S |
| G WWALL SWA | RES_EXT_WALL_GRD | 0.30 | 0.676 | 0.752 | 23.22 | 18.58 | 270.00 | 90.00 | W |
| G GFLOOR SWA | GGFLOORSWA_FFACTOR | 1.00 | 0.274 | 0.287 | 88.25 | 88.25 | 90.00 | 180.00 | |
| G NWALL NWA | RES_EXT_WALL_GRD | 0.30 | 0.676 | 0.752 | 35.30 | 28.24 | 0.00 | 90.00 | N |
| G WWALL NWA | RES_EXT_WALL_GRD | 0.30 | 0.676 | 0.752 | 23.22 | 18.58 | 270.00 | 90.00 | W |
| G GFLOOR NWA | GGFLOORNWA_FFACTOR | 1.00 | 0.274 | 0.287 | 88.25 | 88.25 | 90.00 | 180.00 | |
| G SWALL SEA | NONRES_EXT_WALL_GRD | 0.30 | 0.750 | 0.844 | 35.30 | 28.24 | 180.00 | 90.00 | S |
| G EWALL SEA | NONRES_EXT_WALL_GRD | 0.30 | 0.750 | 0.844 | 23.22 | 18.58 | 90.00 | 90.00 | E |
| G GFLOOR SEA | GGFLOORSEA_FFACTOR | 1.00 | 0.274 | 0.287 | 88.25 | 88.25 | 90.00 | 180.00 | |
| G NWALL NEA | RES_EXT_WALL_GRD | 0.30 | 0.676 | 0.752 | 35.30 | 28.24 | 0.00 | 90.00 | N |
| G EWALL NEA | RES_EXT_WALL_GRD | 0.30 | 0.676 | 0.752 | 23.22 | 18.58 | 90.00 | 90.00 | E |
| G GFLOOR NEA | GGFLOORNEA_FFACTOR | 1.00 | 0.274 | 0.287 | 88.25 | 88.25 | 90.00 | 180.00 | |
| G NWALL N1A | RES_EXT_WALL_GRD | 0.30 | 0.676 | 0.752 | 35.30 | 28.24 | 0.00 | 90.00 | N |
| G GFLOOR N1A | GGFLOORN1A_FFACTOR | 1.00 | 0.166 | 0.170 | 88.25 | 88.25 | 90.00 | 180.00 | |
| G NWALL N2A | RES_EXT_WALL_GRD | 0.30 | 0.676 | 0.752 | 35.30 | 28.24 | 0.00 | 90.00 | N |
| G GFLOOR N2A | GGFLOORN2A_FFACTOR | 1.00 | 0.166 | 0.170 | 88.25 | 88.25 | 90.00 | 180.00 | |
| G SWALL S1A | RES_EXT_WALL_GRD | 0.30 | 0.676 | 0.752 | 35.30 | 28.24 | 180.00 | 90.00 | S |
| G GFLOOR S1A | GGFLOORS1A_FFACTOR | 1.00 | 0.166 | 0.170 | 88.25 | 88.25 | 90.00 | 180.00 | |
| G SWALL S2A | RES_EXT_WALL_GRD | 0.30 | 0.676 | 0.752 | 35.30 | 28.24 | 180.00 | 90.00 | S |
| G GFLOOR S2A | GGFLOORS2A_FFACTOR | 1.00 | 0.166 | 0.170 | 88.25 | 88.25 | 90.00 | 180.00 | |
| M WWALL SWA | RES_EXT_WALL_MID | 0.30 | 0.683 | 0.761 | 46.45 | 37.16 | 270.00 | 90.00 | W |
| M SWALL SWA | RES_EXT_WALL_MID | 0.30 | 0.683 | 0.761 | 70.60 | 56.48 | 180.00 | 90.00 | S |
| M NWALL NWA | RES_EXT_WALL_MID | 0.30 | 0.683 | 0.761 | 70.60 | 56.48 | 0.00 | 90.00 | N |
| M WWALL NWA | RES_EXT_WALL_MID | 0.30 | 0.683 | 0.761 | 46.45 | 37.16 | 270.00 | 90.00 | W |
| M EWALL SEA | RES_EXT_WALL_MID | 0.30 | 0.683 | 0.761 | 46.45 | 37.16 | 90.00 | 90.00 | E |
| M SWALL SEA | RES_EXT_WALL_MID | 0.30 | 0.683 | 0.761 | 70.60 | 56.48 | 180.00 | 90.00 | S |
| M NWALL NEA | RES_EXT_WALL_MID | 0.30 | 0.683 | 0.761 | 70.60 | 56.48 | 0.00 | 90.00 | N |
| M EWALL NEA | RES_EXT_WALL_MID | 0.30 | 0.683 | 0.761 | 46.45 | 37.16 | 90.00 | 90.00 | E |
| M NWALL N1A | RES_EXT_WALL_MID | 0.30 | 0.683 | 0.761 | 70.60 | 56.48 | 0.00 | 90.00 | N |
| M NWALL N2A | RES_EXT_WALL_MID | 0.30 | 0.683 | 0.761 | 70.60 | 56.48 | 0.00 | 90.00 | N |
| M SWALL S1A | RES_EXT_WALL_MID | 0.30 | 0.683 | 0.761 | 70.60 | 56.48 | 180.00 | 90.00 | S |
| M SWALL S2A | RES_EXT_WALL_MID | 0.30 | 0.683 | 0.761 | 70.60 | 56.48 | 180.00 | 90.00 | S |
| T WWALL SWA | RES_EXT_WALL_TOP | 0.30 | 0.943 | 1.098 | 23.22 | 18.58 | 270.00 | 90.00 | W |
| T SWALL SWA | RES_EXT_WALL_TOP | 0.30 | 0.943 | 1.098 | 35.30 | 28.24 | 180.00 | 90.00 | S |
| T ROOF SWA | RES_ROOF | 0.55 | 0.273 | 0.283 | 88.25 | 88.25 | 180.00 | 0.00 | |
| T NWALL NWA | RES_EXT_WALL_TOP | 0.30 | 0.943 | 1.098 | 35.30 | 28.24 | 0.00 | 90.00 | N |
| T WWALL NWA | RES_EXT_WALL_TOP | 0.30 | 0.943 | 1.098 | 23.22 | 18.58 | 270.00 | 90.00 | W |
| T ROOF NWA | RES_ROOF | 0.55 | 0.273 | 0.283 | 88.25 | 88.25 | 180.00 | 0.00 | |
| T EWALL SEA | RES_EXT_WALL_TOP | 0.30 | 0.943 | 1.098 | 23.22 | 18.58 | 90.00 | 90.00 | E |
| T SWALL SEA | RES_EXT_WALL_TOP | 0.30 | 0.943 | 1.098 | 35.30 | 28.24 | 180.00 | 90.00 | S |
| T ROOF SEA | RES_ROOF | 0.55 | 0.273 | 0.283 | 88.25 | 88.25 | 180.00 | 0.00 | |
| T NWALL NEA | RES_EXT_WALL_TOP | 0.30 | 0.943 | 1.098 | 35.30 | 28.24 | 0.00 | 90.00 | N |
| T EWALL NEA | RES_EXT_WALL_TOP | 0.30 | 0.943 | 1.098 | 23.22 | 18.58 | 90.00 | 90.00 | E |
| T ROOF NEA | RES_ROOF | 0.55 | 0.273 | 0.283 | 88.25 | 88.25 | 180.00 | 0.00 | |
| T NWALL N1A | RES_EXT_WALL_TOP | 0.30 | 0.943 | 1.098 | 35.30 | 28.24 | 0.00 | 90.00 | N |
| T ROOF N1A | RES_ROOF | 0.55 | 0.273 | 0.283 | 88.25 | 88.25 | 180.00 | 0.00 | |
| T NWALL N2A | RES_EXT_WALL_TOP | 0.30 | 0.943 | 1.098 | 35.30 | 28.24 | 0.00 | 90.00 | N |
| T ROOF N2A | RES_ROOF | 0.55 | 0.273 | 0.283 | 88.25 | 88.25 | 180.00 | 0.00 | |
| T SWALL S1A | RES_EXT_WALL_TOP | 0.30 | 0.943 | 1.098 | 35.30 | 28.24 | 180.00 | 90.00 | S |
| T ROOF S1A | RES_ROOF | 0.55 | 0.273 | 0.283 | 88.25 | 88.25 | 180.00 | 0.00 | |
| T SWALL S2A | RES_EXT_WALL_TOP | 0.30 | 0.943 | 1.098 | 35.30 | 28.24 | 180.00 | 90.00 | S |
| T ROOF S2A | RES_ROOF | 0.55 | 0.273 | 0.283 | 88.25 | 88.25 | 180.00 | 0.00 | |
| T WWALL C | NONRES_EXT_WALL_TOP | 0.30 | 1.017 | 1.200 | 5.11 | 5.11 | 270.00 | 90.00 | W |
| T EWALL C | NONRES_EXT_WALL_TOP | 0.30 | 1.017 | 1.200 | 5.11 | 3.99 | 90.00 | 90.00 | E |
| T ROOF C | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 77.66 | 77.66 | 180.00 | 0.00 | |
| G WWALL C | NONRES_EXT_WALL_GRD | 0.30 | 0.750 | 0.844 | 5.11 | 5.11 | 270.00 | 90.00 | W |
| G EWALL C | NONRES_EXT_WALL_GRD | 0.30 | 0.750 | 0.844 | 5.11 | 1.79 | 90.00 | 90.00 | E |
| G FLOOR C | GFLOORC_FFACTOR | 1.00 | 0.055 | 0.055 | 77.66 | 77.66 | 90.00 | 180.00 | |
| M WWALL C | NONRES_EXT_WALL_MID | 0.30 | 0.757 | 0.854 | 10.22 | 10.22 | 270.00 | 90.00 | W |
| M EWALL C | NONRES_EXT_WALL_MID | 0.30 | 0.757 | 0.854 | 10.22 | 7.99 | 90.00 | 90.00 | E |
| Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
| G NIWALL SWA | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 0.00 | 90.00 | N |
| G EIWALL SWA | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 90.00 | 90.00 | E |
| G CEILIN SWA | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 88.25 | 88.25 | 180.00 | 0.00 | |
| G SIWALL NWA | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 180.00 | 90.00 | S |
| G EIWALL NWA | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 90.00 | 90.00 | E |
| G CEILIN NWA | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 88.25 | 88.25 | 180.00 | 0.00 | |
| G NIWALL SEA | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 0.00 | 90.00 | N |
| iz-G EIWALL S2A | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 270.00 | 90.00 | W |
| G CEILIN SEA | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 88.25 | 88.25 | 180.00 | 0.00 | |
| G SIWALL NEA | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 180.00 | 90.00 | S |
| iz-G EIWALL N2A | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 270.00 | 90.00 | W |
| G CEILIN NEA | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 88.25 | 88.25 | 180.00 | 0.00 | |
| G SIWALL N1A | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 180.00 | 90.00 | S |
| G EIWALL N1A | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 90.00 | 90.00 | E |
| iz-G EIWALL NWA | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 270.00 | 90.00 | W |
| G CEILIN N1A | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 88.25 | 88.25 | 180.00 | 0.00 | |
| G SIWALL N2A | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 180.00 | 90.00 | S |
| G EIWALL N2A | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 90.00 | 90.00 | E |
| iz-G EIWALL N1A | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 270.00 | 90.00 | W |
| G CEILIN N2A | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 88.25 | 88.25 | 180.00 | 0.00 | |
| G NIWALL S1A | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 0.00 | 90.00 | N |
| G EIWALL S1A | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 90.00 | 90.00 | E |
| iz-G EIWALL SWA | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 270.00 | 90.00 | W |
| G CEILIN S1A | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 88.25 | 88.25 | 180.00 | 0.00 | |
| G NIWALL S2A | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 0.00 | 90.00 | N |
| G EIWALL S2A | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 90.00 | 90.00 | E |
| iz-G EIWALL S1A | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 270.00 | 90.00 | W |
| G CEILIN S2A | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 88.25 | 88.25 | 180.00 | 0.00 | |
| M NIWALL SWA | INT_WALL | 0.30 | 2.511 | 6.299 | 70.60 | 70.60 | 0.00 | 90.00 | N |
| M EIWALL SWA | INT_WALL | 0.30 | 2.511 | 6.299 | 46.45 | 46.45 | 90.00 | 90.00 | E |
| M GFLOOR SWA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 176.50 | 176.50 | 90.00 | 180.00 | |
| M CEILIN SWA | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 176.50 | 176.50 | 180.00 | 0.00 | |
| M SIWALL NWA | INT_WALL | 0.30 | 2.511 | 6.299 | 70.60 | 70.60 | 180.00 | 90.00 | S |
| M EIWALL NWA | INT_WALL | 0.30 | 2.511 | 6.299 | 46.45 | 46.45 | 90.00 | 90.00 | E |
| M GFLOOR NWA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 176.50 | 176.50 | 90.00 | 180.00 | |
| M CEILIN NWA | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 176.50 | 176.50 | 180.00 | 0.00 | |
| M NIWALL SEA | INT_WALL | 0.30 | 2.511 | 6.299 | 70.60 | 70.60 | 0.00 | 90.00 | N |
| iz-M EIWALL S2A | INT_WALL | 0.30 | 2.511 | 6.299 | 46.45 | 46.45 | 270.00 | 90.00 | W |
| M GFLOOR SEA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 176.50 | 176.50 | 90.00 | 180.00 | |
| M CEILIN SEA | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 176.50 | 176.50 | 180.00 | 0.00 | |
| M SIWALL NEA | INT_WALL | 0.30 | 2.511 | 6.299 | 70.60 | 70.60 | 180.00 | 90.00 | S |
| iz-M EIWALL N2A | INT_WALL | 0.30 | 2.511 | 6.299 | 46.45 | 46.45 | 270.00 | 90.00 | W |
| M GFLOOR NEA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 176.50 | 176.50 | 90.00 | 180.00 | |
| M CEILIN NEA | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 176.50 | 176.50 | 180.00 | 0.00 | |
| M SIWALL N1A | INT_WALL | 0.30 | 2.511 | 6.299 | 70.60 | 70.60 | 180.00 | 90.00 | S |
| M EIWALL N1A | INT_WALL | 0.30 | 2.511 | 6.299 | 46.45 | 46.45 | 90.00 | 90.00 | E |
| iz-M EIWALL NWA | INT_WALL | 0.30 | 2.511 | 6.299 | 46.45 | 46.45 | 270.00 | 90.00 | W |
| M GFLOOR N1A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 176.50 | 176.50 | 90.00 | 180.00 | |
| M CEILIN N1A | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 176.50 | 176.50 | 180.00 | 0.00 | |
| M SIWALL N2A | INT_WALL | 0.30 | 2.511 | 6.299 | 70.60 | 70.60 | 180.00 | 90.00 | S |
| M EIWALL N2A | INT_WALL | 0.30 | 2.511 | 6.299 | 46.45 | 46.45 | 90.00 | 90.00 | E |
| iz-M EIWALL N1A | INT_WALL | 0.30 | 2.511 | 6.299 | 46.45 | 46.45 | 270.00 | 90.00 | W |
| M GFLOOR N2A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 176.50 | 176.50 | 90.00 | 180.00 | |
| M CEILIN N2A | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 176.50 | 176.50 | 180.00 | 0.00 | |
| M NIWALL S1A | INT_WALL | 0.30 | 2.511 | 6.299 | 70.60 | 70.60 | 0.00 | 90.00 | N |
| M EIWALL S1A | INT_WALL | 0.30 | 2.511 | 6.299 | 46.45 | 46.45 | 90.00 | 90.00 | E |
| iz-M EIWALL SWA | INT_WALL | 0.30 | 2.511 | 6.299 | 46.45 | 46.45 | 270.00 | 90.00 | W |
| M GFLOOR S1A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 176.50 | 176.50 | 90.00 | 180.00 | |
| M CEILIN S1A | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 176.50 | 176.50 | 180.00 | 0.00 | |
| M NIWALL S2A | INT_WALL | 0.30 | 2.511 | 6.299 | 70.60 | 70.60 | 0.00 | 90.00 | N |
| M EIWALL S2A | INT_WALL | 0.30 | 2.511 | 6.299 | 46.45 | 46.45 | 90.00 | 90.00 | E |
| iz-M EIWALL S1A | INT_WALL | 0.30 | 2.511 | 6.299 | 46.45 | 46.45 | 270.00 | 90.00 | W |
| M GFLOOR S2A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 176.50 | 176.50 | 90.00 | 180.00 | |
| M CEILIN S2A | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 176.50 | 176.50 | 180.00 | 0.00 | |
| T NIWALL SWA | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 0.00 | 90.00 | N |
| T EIWALL SWA | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 90.00 | 90.00 | E |
| T GFLOOR SWA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 88.25 | 88.25 | 90.00 | 180.00 | |
| T SIWALL NWA | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 180.00 | 90.00 | S |
| T EIWALL NWA | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 90.00 | 90.00 | E |
| T GFLOOR NWA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 88.25 | 88.25 | 90.00 | 180.00 | |
| T NIWALL SEA | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 0.00 | 90.00 | N |
| iz-T EIWALL S2A | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 270.00 | 90.00 | W |
| T GFLOOR SEA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 88.25 | 88.25 | 90.00 | 180.00 | |
| T SIWALL NEA | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 180.00 | 90.00 | S |
| iz-T EIWALL N2A | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 270.00 | 90.00 | W |
| T GFLOOR NEA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 88.25 | 88.25 | 90.00 | 180.00 | |
| T SIWALL N1A | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 180.00 | 90.00 | S |
| T EIWALL N1A | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 90.00 | 90.00 | E |
| iz-T EIWALL NWA | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 270.00 | 90.00 | W |
| T GFLOOR N1A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 88.25 | 88.25 | 90.00 | 180.00 | |
| T SIWALL N2A | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 180.00 | 90.00 | S |
| T EIWALL N2A | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 90.00 | 90.00 | E |
| iz-T EIWALL N1A | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 270.00 | 90.00 | W |
| T GFLOOR N2A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 88.25 | 88.25 | 90.00 | 180.00 | |
| T NIWALL S1A | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 0.00 | 90.00 | N |
| T EIWALL S1A | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 90.00 | 90.00 | E |
| iz-T EIWALL SWA | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 270.00 | 90.00 | W |
| T GFLOOR S1A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 88.25 | 88.25 | 90.00 | 180.00 | |
| T NIWALL S2A | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 0.00 | 90.00 | N |
| T EIWALL S2A | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 90.00 | 90.00 | E |
| iz-T EIWALL S1A | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 270.00 | 90.00 | W |
| T GFLOOR S2A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 88.25 | 88.25 | 90.00 | 180.00 | |
| iz-T NIWALL SWA | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 180.00 | 90.00 | S |
| iz-T NIWALL S1A | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 180.00 | 90.00 | S |
| iz-T NIWALL S2A | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 180.00 | 90.00 | S |
| iz-T NIWALL SEA | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 180.00 | 90.00 | S |
| iz-T SIWALL NWA | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 0.00 | 90.00 | N |
| iz-T SIWALL N1A | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 0.00 | 90.00 | N |
| iz-T SIWALL N2A | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 0.00 | 90.00 | N |
| iz-T SIWALL NEA | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 0.00 | 90.00 | N |
| T FLOOR C | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 77.66 | 77.66 | 90.00 | 180.00 | |
| iz-G NIWALL SWA | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 180.00 | 90.00 | S |
| iz-G NIWALL S1A | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 180.00 | 90.00 | S |
| iz-G NIWALL S2A | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 180.00 | 90.00 | S |
| iz-G NIWALL SEA | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 180.00 | 90.00 | S |
| iz-G SIWALL NWA | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 0.00 | 90.00 | N |
| iz-G SIWALL N1A | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 0.00 | 90.00 | N |
| iz-G SIWALL N2A | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 0.00 | 90.00 | N |
| iz-G SIWALL NEA | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 0.00 | 90.00 | N |
| G CEILING C | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 77.66 | 77.66 | 180.00 | 0.00 | |
| iz-M NIWALL SWA | INT_WALL | 0.30 | 2.511 | 6.299 | 70.60 | 70.60 | 180.00 | 90.00 | S |
| iz-M NIWALL S1A | INT_WALL | 0.30 | 2.511 | 6.299 | 70.60 | 70.60 | 180.00 | 90.00 | S |
| iz-M NIWALL S2A | INT_WALL | 0.30 | 2.511 | 6.299 | 70.60 | 70.60 | 180.00 | 90.00 | S |
| iz-M NIWALL SEA | INT_WALL | 0.30 | 2.511 | 6.299 | 70.60 | 70.60 | 180.00 | 90.00 | S |
| iz-M SIWALL NWA | INT_WALL | 0.30 | 2.511 | 6.299 | 70.60 | 70.60 | 0.00 | 90.00 | N |
| iz-M SIWALL N1A | INT_WALL | 0.30 | 2.511 | 6.299 | 70.60 | 70.60 | 0.00 | 90.00 | N |
| iz-M SIWALL N2A | INT_WALL | 0.30 | 2.511 | 6.299 | 70.60 | 70.60 | 0.00 | 90.00 | N |
| iz-M SIWALL NEA | INT_WALL | 0.30 | 2.511 | 6.299 | 70.60 | 70.60 | 0.00 | 90.00 | N |
| M FLOOR C | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 155.32 | 155.32 | 90.00 | 180.00 | |
| M CEILING C | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 155.32 | 155.32 | 180.00 | 0.00 | |
| G INTERNALMASS SWA | INTERIORFURNISHINGS | 0.30 | 0.800 | 88.25 | 0.00 | 90.00 | N | ||
| G INTERNALMASS NWA | INTERIORFURNISHINGS | 0.30 | 0.800 | 88.25 | 0.00 | 90.00 | N | ||
| G INTERNALMASS SEA | INTERIORFURNISHINGS | 0.30 | 0.800 | 88.25 | 0.00 | 90.00 | N | ||
| G INTERNALMASS NEA | INTERIORFURNISHINGS | 0.30 | 0.800 | 88.25 | 0.00 | 90.00 | N | ||
| G INTERNALMASS N1A | INTERIORFURNISHINGS | 0.30 | 0.800 | 88.25 | 0.00 | 90.00 | N | ||
| G INTERNALMASS N2A | INTERIORFURNISHINGS | 0.30 | 0.800 | 88.25 | 0.00 | 90.00 | N | ||
| G INTERNALMASS S1A | INTERIORFURNISHINGS | 0.30 | 0.800 | 88.25 | 0.00 | 90.00 | N | ||
| G INTERNALMASS S2A | INTERIORFURNISHINGS | 0.30 | 0.800 | 88.25 | 0.00 | 90.00 | N | ||
| M INTERNALMASS SWA | INTERIORFURNISHINGS | 0.30 | 0.800 | 353.00 | 0.00 | 90.00 | N | ||
| M INTERNALMASS NWA | INTERIORFURNISHINGS | 0.30 | 0.800 | 353.00 | 0.00 | 90.00 | N | ||
| M INTERNALMASS SEA | INTERIORFURNISHINGS | 0.30 | 0.800 | 353.00 | 0.00 | 90.00 | N | ||
| M INTERNALMASS NEA | INTERIORFURNISHINGS | 0.30 | 0.800 | 353.00 | 0.00 | 90.00 | N | ||
| M INTERNALMASS N1A | INTERIORFURNISHINGS | 0.30 | 0.800 | 353.00 | 0.00 | 90.00 | N | ||
| M INTERNALMASS N2A | INTERIORFURNISHINGS | 0.30 | 0.800 | 353.00 | 0.00 | 90.00 | N | ||
| M INTERNALMASS S1A | INTERIORFURNISHINGS | 0.30 | 0.800 | 353.00 | 0.00 | 90.00 | N | ||
| M INTERNALMASS S2A | INTERIORFURNISHINGS | 0.30 | 0.800 | 353.00 | 0.00 | 90.00 | N | ||
| T INTERNALMASS SWA | INTERIORFURNISHINGS | 0.30 | 0.800 | 88.25 | 0.00 | 90.00 | N | ||
| T INTERNALMASS NWA | INTERIORFURNISHINGS | 0.30 | 0.800 | 88.25 | 0.00 | 90.00 | N | ||
| T INTERNALMASS SEA | INTERIORFURNISHINGS | 0.30 | 0.800 | 88.25 | 0.00 | 90.00 | N | ||
| T INTERNALMASS NEA | INTERIORFURNISHINGS | 0.30 | 0.800 | 88.25 | 0.00 | 90.00 | N | ||
| T INTERNALMASS N1A | INTERIORFURNISHINGS | 0.30 | 0.800 | 88.25 | 0.00 | 90.00 | N | ||
| T INTERNALMASS N2A | INTERIORFURNISHINGS | 0.30 | 0.800 | 88.25 | 0.00 | 90.00 | N | ||
| T INTERNALMASS S1A | INTERIORFURNISHINGS | 0.30 | 0.800 | 88.25 | 0.00 | 90.00 | N | ||
| T INTERNALMASS S2A | INTERIORFURNISHINGS | 0.30 | 0.800 | 88.25 | 0.00 | 90.00 | N |
| Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
| GWINDOW1 S SWA | RESWINDOW_U_0.5369_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 3.053 | 0.251 | 0.251 | No | G SWALL SWA | 180.00 | 90.00 | S | |||||||
| GWINDOW1 W SWA | RESWINDOW_U_0.5369_SHGC_0.25 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 3.053 | 0.251 | 0.251 | No | G WWALL SWA | 270.00 | 90.00 | W | |||||||
| GWINDOW1 N NWA | RESWINDOW_U_0.5369_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 3.053 | 0.251 | 0.251 | No | G NWALL NWA | 0.00 | 90.00 | N | |||||||
| GWINDOW1 W NWA | RESWINDOW_U_0.5369_SHGC_0.25 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 3.053 | 0.251 | 0.251 | No | G WWALL NWA | 270.00 | 90.00 | W | |||||||
| GWINDOW1 S SEA | NONRESWINDOW_U_0.5369_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 3.053 | 0.251 | 0.251 | No | G SWALL SEA | 180.00 | 90.00 | S | |||||||
| GWINDOW1 E SEA | NONRESWINDOW_U_0.5369_SHGC_0.25 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 3.053 | 0.251 | 0.251 | No | G EWALL SEA | 90.00 | 90.00 | E | |||||||
| GWINDOW1 N NEA | RESWINDOW_U_0.5369_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 3.053 | 0.251 | 0.251 | No | G NWALL NEA | 0.00 | 90.00 | N | |||||||
| GWINDOW1 E NEA | RESWINDOW_U_0.5369_SHGC_0.25 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 3.053 | 0.251 | 0.251 | No | G EWALL NEA | 90.00 | 90.00 | E | |||||||
| GWINDOW1 N N1A | RESWINDOW_U_0.5369_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 3.053 | 0.251 | 0.251 | No | G NWALL N1A | 0.00 | 90.00 | N | |||||||
| GWINDOW1 N N2A | RESWINDOW_U_0.5369_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 3.053 | 0.251 | 0.251 | No | G NWALL N2A | 0.00 | 90.00 | N | |||||||
| GWINDOW1 S S1A | RESWINDOW_U_0.5369_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 3.053 | 0.251 | 0.251 | No | G SWALL S1A | 180.00 | 90.00 | S | |||||||
| GWINDOW1 S S2A | RESWINDOW_U_0.5369_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 3.053 | 0.251 | 0.251 | No | G SWALL S2A | 180.00 | 90.00 | S | |||||||
| MWINDOW1 W SWA | RESWINDOW_U_0.5369_SHGC_0.25 | 4.65 | 0.00 | 0.00 | 4.65 | 9.29 | 3.053 | 0.251 | 0.251 | No | M WWALL SWA | 270.00 | 90.00 | W | |||||||
| MWINDOW1 S SWA | RESWINDOW_U_0.5369_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 3.053 | 0.251 | 0.251 | No | M SWALL SWA | 180.00 | 90.00 | S | |||||||
| MWINDOW1 N NWA | RESWINDOW_U_0.5369_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 3.053 | 0.251 | 0.251 | No | M NWALL NWA | 0.00 | 90.00 | N | |||||||
| MWINDOW1 W NWA | RESWINDOW_U_0.5369_SHGC_0.25 | 4.65 | 0.00 | 0.00 | 4.65 | 9.29 | 3.053 | 0.251 | 0.251 | No | M WWALL NWA | 270.00 | 90.00 | W | |||||||
| MWINDOW1 E SEA | RESWINDOW_U_0.5369_SHGC_0.25 | 4.65 | 0.00 | 0.00 | 4.65 | 9.29 | 3.053 | 0.251 | 0.251 | No | M EWALL SEA | 90.00 | 90.00 | E | |||||||
| MWINDOW1 S SEA | RESWINDOW_U_0.5369_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 3.053 | 0.251 | 0.251 | No | M SWALL SEA | 180.00 | 90.00 | S | |||||||
| MWINDOW1 N NEA | RESWINDOW_U_0.5369_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 3.053 | 0.251 | 0.251 | No | M NWALL NEA | 0.00 | 90.00 | N | |||||||
| MWINDOW1 E NEA | RESWINDOW_U_0.5369_SHGC_0.25 | 4.65 | 0.00 | 0.00 | 4.65 | 9.29 | 3.053 | 0.251 | 0.251 | No | M EWALL NEA | 90.00 | 90.00 | E | |||||||
| MWINDOW1 N N1A | RESWINDOW_U_0.5369_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 3.053 | 0.251 | 0.251 | No | M NWALL N1A | 0.00 | 90.00 | N | |||||||
| MWINDOW1 N N2A | RESWINDOW_U_0.5369_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 3.053 | 0.251 | 0.251 | No | M NWALL N2A | 0.00 | 90.00 | N | |||||||
| MWINDOW1 S S1A | RESWINDOW_U_0.5369_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 3.053 | 0.251 | 0.251 | No | M SWALL S1A | 180.00 | 90.00 | S | |||||||
| MWINDOW1 S S2A | RESWINDOW_U_0.5369_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 3.053 | 0.251 | 0.251 | No | M SWALL S2A | 180.00 | 90.00 | S | |||||||
| TWINDOW1 W SWA | RESWINDOW_U_0.5369_SHGC_0.25 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 3.053 | 0.251 | 0.251 | No | T WWALL SWA | 270.00 | 90.00 | W | |||||||
| TWINDOW1 S SWA | RESWINDOW_U_0.5369_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 3.053 | 0.251 | 0.251 | No | T SWALL SWA | 180.00 | 90.00 | S | |||||||
| TWINDOW1 N NWA | RESWINDOW_U_0.5369_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 3.053 | 0.251 | 0.251 | No | T NWALL NWA | 0.00 | 90.00 | N | |||||||
| TWINDOW1 W NWA | RESWINDOW_U_0.5369_SHGC_0.25 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 3.053 | 0.251 | 0.251 | No | T WWALL NWA | 270.00 | 90.00 | W | |||||||
| TWINDOW1 E SEA | RESWINDOW_U_0.5369_SHGC_0.25 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 3.053 | 0.251 | 0.251 | No | T EWALL SEA | 90.00 | 90.00 | E | |||||||
| TWINDOW1 S SEA | RESWINDOW_U_0.5369_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 3.053 | 0.251 | 0.251 | No | T SWALL SEA | 180.00 | 90.00 | S | |||||||
| TWINDOW1 N NEA | RESWINDOW_U_0.5369_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 3.053 | 0.251 | 0.251 | No | T NWALL NEA | 0.00 | 90.00 | N | |||||||
| TWINDOW1 E NEA | RESWINDOW_U_0.5369_SHGC_0.25 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 3.053 | 0.251 | 0.251 | No | T EWALL NEA | 90.00 | 90.00 | E | |||||||
| TWINDOW1 N N1A | RESWINDOW_U_0.5369_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 3.053 | 0.251 | 0.251 | No | T NWALL N1A | 0.00 | 90.00 | N | |||||||
| TWINDOW1 N N2A | RESWINDOW_U_0.5369_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 3.053 | 0.251 | 0.251 | No | T NWALL N2A | 0.00 | 90.00 | N | |||||||
| TWINDOW1 S S1A | RESWINDOW_U_0.5369_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 3.053 | 0.251 | 0.251 | No | T SWALL S1A | 180.00 | 90.00 | S | |||||||
| TWINDOW1 S S2A | RESWINDOW_U_0.5369_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 3.053 | 0.251 | 0.251 | No | T SWALL S2A | 180.00 | 90.00 | S | |||||||
| TWINDOW14 | NONRESWINDOW_U_0.5369_SHGC_0.25 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 3.053 | 0.251 | 0.251 | No | T EWALL C | 90.00 | 90.00 | E | |||||||
| ENTRANCE DOOR | NONRESWINDOW_U_0.5369_SHGC_0.25 | 3.32 | 0.00 | 0.00 | 3.32 | 3.32 | 3.053 | 0.251 | 0.251 | No | G EWALL C | 90.00 | 90.00 | E | |||||||
| MWINDOW14 | NONRESWINDOW_U_0.5369_SHGC_0.25 | 1.11 | 0.00 | 0.00 | 1.11 | 2.23 | 3.053 | 0.251 | 0.251 | No | M EWALL C | 90.00 | 90.00 | E | |||||||
| Total or Average | 306.92 | 3.053 | 0.251 | 0.251 | |||||||||||||||||
| North Total or Average | 112.97 | 3.053 | 0.251 | 0.251 | |||||||||||||||||
| Non-North Total or Average | 193.95 | 3.053 | 0.251 | 0.251 |
| Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
| None |
| Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
| Total or Average | 0.00 | - | - | - |
| Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
| None |
| Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
| None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 09:17:08
Sunlit Fraction| March 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
| GWINDOW1 S SWA | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| GWINDOW1 W SWA | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
| GWINDOW1 N NWA | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| GWINDOW1 W NWA | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
| GWINDOW1 S SEA | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| GWINDOW1 E SEA | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
| GWINDOW1 N NEA | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| GWINDOW1 E NEA | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
| GWINDOW1 N N1A | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| GWINDOW1 N N2A | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| GWINDOW1 S S1A | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| GWINDOW1 S S2A | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| MWINDOW1 W SWA | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
| MWINDOW1 S SWA | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| MWINDOW1 N NWA | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| MWINDOW1 W NWA | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
| MWINDOW1 E SEA | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
| MWINDOW1 S SEA | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| MWINDOW1 N NEA | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| MWINDOW1 E NEA | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
| MWINDOW1 N N1A | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| MWINDOW1 N N2A | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| MWINDOW1 S S1A | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| MWINDOW1 S S2A | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| TWINDOW1 W SWA | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
| TWINDOW1 S SWA | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| TWINDOW1 N NWA | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| TWINDOW1 W NWA | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
| TWINDOW1 E SEA | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
| TWINDOW1 S SEA | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| TWINDOW1 N NEA | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| TWINDOW1 E NEA | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
| TWINDOW1 N N1A | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| TWINDOW1 N N2A | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| TWINDOW1 S S1A | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| TWINDOW1 S S2A | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| TWINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
| ENTRANCE DOOR | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
| MWINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
| Name | Type | Shaded Construction | Control | Glare Control | |
| None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 09:17:08
Interior Lighting| Zone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
| LIGHTING_HARDWIRED_GSW | G SW APARTMENT | G SW APARTMENT | GENERAL | 7.8684 | 88.25 | 694.38 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.32 |
| LIGHTING_HARDWIRED_GNW | G NW APARTMENT | G NW APARTMENT | GENERAL | 7.8684 | 88.25 | 694.38 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.32 |
| LIGHTING_HARDWIRED_OFFICE | OFFICE | OFFICE | GENERAL | 9.7532 | 88.25 | 860.71 | LightsWired | LTG_SCH_OFFICE | 46.69 | 168.00 | 45.77 | 0.0000 | Y | 7.40 |
| LIGHTING_HARDWIRED_GNE | G NE APARTMENT | G NE APARTMENT | GENERAL | 7.8684 | 88.25 | 694.38 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.32 |
| LIGHTING_HARDWIRED_GN1 | G N1 APARTMENT | G N1 APARTMENT | GENERAL | 7.8684 | 88.25 | 694.38 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.32 |
| LIGHTING_HARDWIRED_GN2 | G N2 APARTMENT | G N2 APARTMENT | GENERAL | 7.8684 | 88.25 | 694.38 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.32 |
| LIGHTING_HARDWIRED_GS1 | G S1 APARTMENT | G S1 APARTMENT | GENERAL | 7.8684 | 88.25 | 694.38 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.32 |
| LIGHTING_HARDWIRED_GS2 | G S2 APARTMENT | G S2 APARTMENT | GENERAL | 7.8684 | 88.25 | 694.38 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.32 |
| LIGHTING_HARDWIRED_MSW | M SW APARTMENT | M SW APARTMENT | GENERAL | 7.8684 | 176.50 | 1388.76 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 2.63 |
| LIGHTING_HARDWIRED_MNW | M NW APARTMENT | M NW APARTMENT | GENERAL | 7.8684 | 176.50 | 1388.76 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 2.63 |
| LIGHTING_HARDWIRED_MSE | M SE APARTMENT | M SE APARTMENT | GENERAL | 7.8684 | 176.50 | 1388.76 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 2.63 |
| LIGHTING_HARDWIRED_MNE | M NE APARTMENT | M NE APARTMENT | GENERAL | 7.8684 | 176.50 | 1388.76 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 2.63 |
| LIGHTING_HARDWIRED_MN1 | M N1 APARTMENT | M N1 APARTMENT | GENERAL | 7.8684 | 176.50 | 1388.76 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 2.63 |
| LIGHTING_HARDWIRED_MN2 | M N2 APARTMENT | M N2 APARTMENT | GENERAL | 7.8684 | 176.50 | 1388.76 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 2.63 |
| LIGHTING_HARDWIRED_MS1 | M S1 APARTMENT | M S1 APARTMENT | GENERAL | 7.8684 | 176.50 | 1388.76 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 2.63 |
| LIGHTING_HARDWIRED_MS2 | M S2 APARTMENT | M S2 APARTMENT | GENERAL | 7.8684 | 176.50 | 1388.76 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 2.63 |
| LIGHTING_HARDWIRED_TSW | T SW APARTMENT | T SW APARTMENT | GENERAL | 7.8684 | 88.25 | 694.38 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.32 |
| LIGHTING_HARDWIRED_TNW | T NW APARTMENT | T NW APARTMENT | GENERAL | 7.8684 | 88.25 | 694.38 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.32 |
| LIGHTING_HARDWIRED_TSE | T SE APARTMENT | T SE APARTMENT | GENERAL | 7.8684 | 88.25 | 694.38 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.32 |
| LIGHTING_HARDWIRED_TNE | T NE APARTMENT | T NE APARTMENT | GENERAL | 7.8684 | 88.25 | 694.38 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.32 |
| LIGHTING_HARDWIRED_TN1 | T N1 APARTMENT | T N1 APARTMENT | GENERAL | 7.8684 | 88.25 | 694.38 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.32 |
| LIGHTING_HARDWIRED_TN2 | T N2 APARTMENT | T N2 APARTMENT | GENERAL | 7.8684 | 88.25 | 694.38 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.32 |
| LIGHTING_HARDWIRED_TS1 | T S1 APARTMENT | T S1 APARTMENT | GENERAL | 7.8684 | 88.25 | 694.38 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.32 |
| LIGHTING_HARDWIRED_TS2 | T S2 APARTMENT | T S2 APARTMENT | GENERAL | 7.8684 | 88.25 | 694.38 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.32 |
| LIGHTING_HARDWIRED_GC | G CORRIDOR | G CORRIDOR | GENERAL | 4.7725 | 77.66 | 370.63 | LightsWired | LTG_SCH_CORRIDOR | 168.00 | 168.00 | 168.00 | 0.0000 | N | 11.69 |
| LIGHTING_HARDWIRED_MC | M CORRIDOR | M CORRIDOR | GENERAL | 4.7725 | 155.32 | 741.26 | LightsWired | LTG_SCH_CORRIDOR | 168.00 | 168.00 | 168.00 | 0.0000 | N | 23.38 |
| LIGHTING_HARDWIRED_TC | T CORRIDOR | T CORRIDOR | GENERAL | 4.7725 | 77.66 | 370.63 | LightsWired | LTG_SCH_CORRIDOR | 168.00 | 168.00 | 168.00 | 0.0000 | N | 11.69 |
| LIGHTING_PLUGIN_GSW | G SW APARTMENT | G SW APARTMENT | GENERAL | 0.8234 | 88.25 | 72.67 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.14 |
| LIGHTING_PLUGIN_GNW | G NW APARTMENT | G NW APARTMENT | GENERAL | 0.8234 | 88.25 | 72.67 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.14 |
| LIGHTING_PLUGIN_GNE | G NE APARTMENT | G NE APARTMENT | GENERAL | 0.8234 | 88.25 | 72.67 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.14 |
| LIGHTING_PLUGIN_GN1 | G N1 APARTMENT | G N1 APARTMENT | GENERAL | 0.8234 | 88.25 | 72.67 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.14 |
| LIGHTING_PLUGIN_GN2 | G N2 APARTMENT | G N2 APARTMENT | GENERAL | 0.8234 | 88.25 | 72.67 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.14 |
| LIGHTING_PLUGIN_GS1 | G S1 APARTMENT | G S1 APARTMENT | GENERAL | 0.8234 | 88.25 | 72.67 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.14 |
| LIGHTING_PLUGIN_GS2 | G S2 APARTMENT | G S2 APARTMENT | GENERAL | 0.8234 | 88.25 | 72.67 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.14 |
| LIGHTING_PLUGIN_MSW | M SW APARTMENT | M SW APARTMENT | GENERAL | 0.8234 | 176.50 | 145.34 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.28 |
| LIGHTING_PLUGIN_MNW | M NW APARTMENT | M NW APARTMENT | GENERAL | 0.8234 | 176.50 | 145.34 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.28 |
| LIGHTING_PLUGIN_MSE | M SE APARTMENT | M SE APARTMENT | GENERAL | 0.8234 | 176.50 | 145.34 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.28 |
| LIGHTING_PLUGIN_MNE | M NE APARTMENT | M NE APARTMENT | GENERAL | 0.8234 | 176.50 | 145.34 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.28 |
| LIGHTING_PLUGIN_MN1 | M N1 APARTMENT | M N1 APARTMENT | GENERAL | 0.8234 | 176.50 | 145.34 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.28 |
| LIGHTING_PLUGIN_MN2 | M N2 APARTMENT | M N2 APARTMENT | GENERAL | 0.8234 | 176.50 | 145.34 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.28 |
| LIGHTING_PLUGIN_MS1 | M S1 APARTMENT | M S1 APARTMENT | GENERAL | 0.8234 | 176.50 | 145.34 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.28 |
| LIGHTING_PLUGIN_MS2 | M S2 APARTMENT | M S2 APARTMENT | GENERAL | 0.8234 | 176.50 | 145.34 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.28 |
| LIGHTING_PLUGIN_TSW | T SW APARTMENT | T SW APARTMENT | GENERAL | 0.8234 | 88.25 | 72.67 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.14 |
| LIGHTING_PLUGIN_TNW | T NW APARTMENT | T NW APARTMENT | GENERAL | 0.8234 | 88.25 | 72.67 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.14 |
| LIGHTING_PLUGIN_TSE | T SE APARTMENT | T SE APARTMENT | GENERAL | 0.8234 | 88.25 | 72.67 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.14 |
| LIGHTING_PLUGIN_TNE | T NE APARTMENT | T NE APARTMENT | GENERAL | 0.8234 | 88.25 | 72.67 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.14 |
| LIGHTING_PLUGIN_TN1 | T N1 APARTMENT | T N1 APARTMENT | GENERAL | 0.8234 | 88.25 | 72.67 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.14 |
| LIGHTING_PLUGIN_TN2 | T N2 APARTMENT | T N2 APARTMENT | GENERAL | 0.8234 | 88.25 | 72.67 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.14 |
| LIGHTING_PLUGIN_TS1 | T S1 APARTMENT | T S1 APARTMENT | GENERAL | 0.8234 | 88.25 | 72.67 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.14 |
| LIGHTING_PLUGIN_TS2 | T S2 APARTMENT | T S2 APARTMENT | GENERAL | 0.8234 | 88.25 | 72.67 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.14 |
| Interior Lighting Total | 4.4498 | 5870.34 | 26121.74 | 75.91 |
| Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
| None |
| Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
| FACADE LIGHTING | 3183.33 | AstronomicalClock | - | 83.79 | 83.79 | 50.07 | |
| Exterior Lighting Total | 3183.33 | 50.07 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 09:17:08
Central Plant| Type | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
| None |
| Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
| SPLIT GSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7027.00 | 5626.21 | 1400.80 | 0.80 | 3.91 | |||
| SPLIT GNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 6946.45 | 5561.71 | 1384.74 | 0.80 | 3.91 | |||
| SPLIT OFFICE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7499.94 | 6004.87 | 1495.07 | 0.80 | 3.91 | |||
| SPLIT GNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 6528.31 | 5226.93 | 1301.38 | 0.80 | 3.91 | |||
| SPLIT GN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5764.57 | 4615.44 | 1149.14 | 0.80 | 3.91 | |||
| SPLIT GN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5757.17 | 4609.51 | 1147.66 | 0.80 | 3.91 | |||
| SPLIT GS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5861.90 | 4693.36 | 1168.54 | 0.80 | 3.91 | |||
| SPLIT GS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5906.10 | 4728.75 | 1177.35 | 0.80 | 3.91 | |||
| SPLIT MSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 15986.10 | 12799.36 | 3186.75 | 0.80 | 3.91 | |||
| SPLIT MNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 15842.64 | 12684.49 | 3158.15 | 0.80 | 3.91 | |||
| SPLIT MSE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 14872.00 | 11907.35 | 2964.66 | 0.80 | 3.91 | |||
| SPLIT MNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 14730.59 | 11794.12 | 2936.47 | 0.80 | 3.91 | |||
| SPLIT MN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 12874.56 | 10308.09 | 2566.48 | 0.80 | 3.91 | |||
| SPLIT MN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 12855.99 | 10293.21 | 2562.77 | 0.80 | 3.91 | |||
| SPLIT MS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 13050.42 | 10448.89 | 2601.53 | 0.80 | 3.91 | |||
| SPLIT MS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 13031.50 | 10433.74 | 2597.76 | 0.80 | 3.91 | |||
| SPLIT TSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 9173.88 | 7345.12 | 1828.76 | 0.80 | 3.91 | |||
| SPLIT TNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 9169.11 | 7341.30 | 1827.81 | 0.80 | 3.91 | |||
| SPLIT TSE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 8334.51 | 6673.07 | 1661.44 | 0.80 | 3.91 | |||
| SPLIT TNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 8328.58 | 6668.32 | 1660.26 | 0.80 | 3.91 | |||
| SPLIT TN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7470.87 | 5981.59 | 1489.28 | 0.80 | 3.91 | |||
| SPLIT TN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7445.31 | 5961.13 | 1484.18 | 0.80 | 3.91 | |||
| SPLIT TS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7485.39 | 5993.22 | 1492.17 | 0.80 | 3.91 | |||
| SPLIT TS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7459.95 | 5972.85 | 1487.10 | 0.80 | 3.91 |
| DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
| SPLIT GSW COOLING COIL | 6694.3 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 | |
| SPLIT GNW COOLING COIL | 6617.6 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 | |
| SPLIT OFFICE COOLING COIL | 7144.9 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 | |
| SPLIT GNE COOLING COIL | 6219.2 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 | |
| SPLIT GN1 COOLING COIL | 5491.7 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 | |
| SPLIT GN2 COOLING COIL | 5484.6 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 | |
| SPLIT GS1 COOLING COIL | 5584.4 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 | |
| SPLIT GS2 COOLING COIL | 5626.5 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 | |
| SPLIT MSW COOLING COIL | 15229.3 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 | |
| SPLIT MNW COOLING COIL | 15092.6 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 | |
| SPLIT MSE COOLING COIL | 14167.9 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 | |
| SPLIT MNE COOLING COIL | 14033.2 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 | |
| SPLIT MN1 COOLING COIL | 12265.0 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 | |
| SPLIT MN2 COOLING COIL | 12247.4 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 | |
| SPLIT MS1 COOLING COIL | 12432.6 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 | |
| SPLIT MS2 COOLING COIL | 12414.6 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 | |
| SPLIT TSW COOLING COIL | 8739.6 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 | |
| SPLIT TNW COOLING COIL | 8735.0 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 | |
| SPLIT TSE COOLING COIL | 7939.9 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 | |
| SPLIT TNE COOLING COIL | 7934.3 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 | |
| SPLIT TN1 COOLING COIL | 7117.2 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 | |
| SPLIT TN2 COOLING COIL | 7092.8 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 | |
| SPLIT TS1 COOLING COIL | 7131.0 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 | |
| SPLIT TS2 COOLING COIL | 7106.8 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 |
| DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
| SPLIT GSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT GNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT OFFICE COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT GNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT GN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT GN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT GS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT GS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT MSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT MNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT MSE COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT MNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT MN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT MN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT MS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT MS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT TSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT TNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT TSE COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT TNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT TN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT TN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT TS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT TS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed |
| DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
| None |
| Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
| SPLIT GSW HEATING COIL | Coil:Heating:Fuel | 9401.00 | 0.80 | |
| SPLIT GNW HEATING COIL | Coil:Heating:Fuel | 9299.81 | 0.80 | |
| SPLIT OFFICE HEATING COIL | Coil:Heating:Fuel | 10269.02 | 0.80 | |
| SPLIT GNE HEATING COIL | Coil:Heating:Fuel | 8775.36 | 0.80 | |
| SPLIT GN1 HEATING COIL | Coil:Heating:Fuel | 7817.38 | 0.80 | |
| SPLIT GN2 HEATING COIL | Coil:Heating:Fuel | 7808.10 | 0.80 | |
| SPLIT GS1 HEATING COIL | Coil:Heating:Fuel | 7939.58 | 0.80 | |
| SPLIT GS2 HEATING COIL | Coil:Heating:Fuel | 7995.01 | 0.80 | |
| SPLIT MSW HEATING COIL | Coil:Heating:Fuel | 21225.52 | 0.80 | |
| SPLIT MNW HEATING COIL | Coil:Heating:Fuel | 21045.26 | 0.80 | |
| SPLIT MSE HEATING COIL | Coil:Heating:Fuel | 19828.13 | 0.80 | |
| SPLIT MNE HEATING COIL | Coil:Heating:Fuel | 19650.47 | 0.80 | |
| SPLIT MN1 HEATING COIL | Coil:Heating:Fuel | 17322.32 | 0.80 | |
| SPLIT MN2 HEATING COIL | Coil:Heating:Fuel | 17299.02 | 0.80 | |
| SPLIT MS1 HEATING COIL | Coil:Heating:Fuel | 17543.16 | 0.80 | |
| SPLIT MS2 HEATING COIL | Coil:Heating:Fuel | 17519.42 | 0.80 | |
| SPLIT TSW HEATING COIL | Coil:Heating:Fuel | 12094.01 | 0.80 | |
| SPLIT TNW HEATING COIL | Coil:Heating:Fuel | 12087.83 | 0.80 | |
| SPLIT TSE HEATING COIL | Coil:Heating:Fuel | 11041.20 | 0.80 | |
| SPLIT TNE HEATING COIL | Coil:Heating:Fuel | 11033.58 | 0.80 | |
| SPLIT TN1 HEATING COIL | Coil:Heating:Fuel | 9957.59 | 0.80 | |
| SPLIT TN2 HEATING COIL | Coil:Heating:Fuel | 9925.53 | 0.80 | |
| SPLIT TS1 HEATING COIL | Coil:Heating:Fuel | 9975.97 | 0.80 | |
| SPLIT TS2 HEATING COIL | Coil:Heating:Fuel | 9944.05 | 0.80 |
| Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
| G SW APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| G SW APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| G NW APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| G NW APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| G NE APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| G NE APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| G N1 APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| G N1 APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| G N2 APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| G N2 APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| G S1 APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| G S1 APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| G S2 APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| G S2 APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| M SW APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.05 | 40.01 | 770.84 | 1.00 | 4.13 | General | ||
| M SW APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.05 | 40.01 | 770.84 | 1.00 | 4.13 | General | ||
| M NW APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.05 | 40.01 | 770.84 | 1.00 | 4.13 | General | ||
| M NW APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.05 | 40.01 | 770.84 | 1.00 | 4.13 | General | ||
| M SE APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.05 | 40.01 | 770.84 | 1.00 | 4.13 | General | ||
| M SE APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.05 | 40.01 | 770.84 | 1.00 | 4.13 | General | ||
| M NE APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.05 | 40.01 | 770.84 | 1.00 | 4.13 | General | ||
| M NE APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.05 | 40.01 | 770.84 | 1.00 | 4.13 | General | ||
| M N1 APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.05 | 40.01 | 770.84 | 1.00 | 4.13 | General | ||
| M N1 APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.05 | 40.01 | 770.84 | 1.00 | 4.13 | General | ||
| M N2 APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.05 | 40.01 | 770.84 | 1.00 | 4.13 | General | ||
| M N2 APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.05 | 40.01 | 770.84 | 1.00 | 4.13 | General | ||
| M S1 APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.05 | 40.01 | 770.84 | 1.00 | 4.13 | General | ||
| M S1 APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.05 | 40.01 | 770.84 | 1.00 | 4.13 | General | ||
| M S2 APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.05 | 40.01 | 770.84 | 1.00 | 4.13 | General | ||
| M S2 APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.05 | 40.01 | 770.84 | 1.00 | 4.13 | General | ||
| T SW APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| T SW APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| T NW APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| T NW APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| T SE APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| T SE APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| T NE APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| T NE APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| T N1 APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| T N1 APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| T N2 APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| T N2 APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| T S1 APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| T S1 APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| T S2 APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| T S2 APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| SPLIT GSW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.42 | 475.49 | 1120.11 | 1.00 | 1.68 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 |
| SPLIT GNW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.42 | 470.04 | 1120.11 | 1.00 | 1.69 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 |
| SPLIT OFFICE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.45 | 507.49 | 1120.11 | 1.00 | 1.65 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:20:00 |
| SPLIT GNE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.39 | 441.74 | 1120.11 | 1.00 | 1.72 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 |
| SPLIT GN1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.35 | 390.06 | 1120.11 | 1.00 | 1.80 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 |
| SPLIT GN2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.35 | 389.56 | 1120.11 | 1.00 | 1.80 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 |
| SPLIT GS1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.35 | 396.65 | 1120.11 | 1.00 | 1.79 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 |
| SPLIT GS2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.36 | 399.64 | 1120.11 | 1.00 | 1.78 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 |
| SPLIT MSW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.97 | 1081.71 | 1120.11 | 1.00 | 1.38 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 |
| SPLIT MNW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.96 | 1072.00 | 1120.11 | 1.00 | 1.38 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 |
| SPLIT MSE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.90 | 1006.32 | 1120.11 | 1.00 | 1.40 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 |
| SPLIT MNE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.89 | 996.76 | 1120.11 | 1.00 | 1.40 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 |
| SPLIT MN1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.78 | 871.17 | 1120.11 | 1.00 | 1.44 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 |
| SPLIT MN2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.78 | 869.91 | 1120.11 | 1.00 | 1.44 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 |
| SPLIT MS1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.79 | 883.07 | 1120.11 | 1.00 | 1.44 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 |
| SPLIT MS2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.79 | 881.79 | 1120.11 | 1.00 | 1.44 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 |
| SPLIT TSW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.55 | 620.76 | 1120.11 | 1.00 | 1.56 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 |
| SPLIT TNW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.55 | 620.43 | 1120.11 | 1.00 | 1.56 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 |
| SPLIT TSE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.50 | 563.96 | 1120.11 | 1.00 | 1.60 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 |
| SPLIT TNE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.50 | 563.56 | 1120.11 | 1.00 | 1.60 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 |
| SPLIT TN1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.45 | 505.52 | 1120.11 | 1.00 | 1.65 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 |
| SPLIT TN2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.45 | 503.79 | 1120.11 | 1.00 | 1.66 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 |
| SPLIT TS1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.45 | 506.50 | 1120.11 | 1.00 | 1.65 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 |
| SPLIT TS2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.45 | 504.78 | 1120.11 | 1.00 | 1.65 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 |
| Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
| None |
| Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
| G SW APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.77 |
| G NW APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.77 |
| G NE APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.77 |
| G N1 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.77 |
| G N2 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.77 |
| G S1 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.77 |
| G S2 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.77 |
| M SW APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.79 |
| M NW APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.79 |
| M SE APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.79 |
| M NE APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.79 |
| M N1 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.79 |
| M N2 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.79 |
| M S1 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.79 |
| M S2 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.79 |
| T SW APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.77 |
| T NW APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.77 |
| T SE APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.77 |
| T NE APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.77 |
| T N1 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.77 |
| T N2 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.77 |
| T S1 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.77 |
| T S2 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.77 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 09:17:08
Zone Sensible Cooling| Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
| G SW APARTMENT | 4527.83 | 5433.39 | 61.57 | 0.354 | 0.425 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 24.00 | 24.00 | 0.00798 | 35.61 | 0.00562 | 0.026 | 0.00 |
| G NW APARTMENT | 4476.90 | 5372.28 | 60.88 | 0.350 | 0.420 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 24.00 | 24.00 | 0.00795 | 35.61 | 0.00562 | 0.026 | 0.00 |
| OFFICE | 4671.98 | 5606.38 | 63.53 | 0.378 | 0.453 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:20:00 | 23.90 | 23.90 | 0.00791 | 34.24 | 0.00562 | 0.038 | 0.00 |
| G NE APARTMENT | 4212.77 | 5055.32 | 57.28 | 0.329 | 0.394 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 24.00 | 24.00 | 0.00795 | 35.61 | 0.00562 | 0.026 | 0.00 |
| G N1 APARTMENT | 3731.90 | 4478.28 | 50.75 | 0.290 | 0.348 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 24.00 | 24.00 | 0.00800 | 35.61 | 0.00562 | 0.026 | 0.00 |
| G N2 APARTMENT | 3727.20 | 4472.64 | 50.68 | 0.290 | 0.348 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 24.00 | 24.00 | 0.00800 | 35.61 | 0.00562 | 0.026 | 0.00 |
| G S1 APARTMENT | 3792.96 | 4551.56 | 51.58 | 0.295 | 0.354 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 24.00 | 24.00 | 0.00804 | 35.61 | 0.00562 | 0.026 | 0.00 |
| G S2 APARTMENT | 3820.74 | 4584.89 | 51.95 | 0.297 | 0.357 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 24.00 | 24.00 | 0.00804 | 35.61 | 0.00562 | 0.026 | 0.00 |
| M SW APARTMENT | 10282.72 | 12339.26 | 139.82 | 0.805 | 0.966 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 24.00 | 24.00 | 0.00794 | 35.61 | 0.00562 | 0.052 | 0.00 |
| M NW APARTMENT | 10191.37 | 12229.64 | 138.58 | 0.798 | 0.957 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 24.00 | 24.00 | 0.00792 | 35.61 | 0.00562 | 0.052 | 0.00 |
| M SE APARTMENT | 9574.76 | 11489.72 | 130.20 | 0.749 | 0.898 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 24.00 | 24.00 | 0.00793 | 35.61 | 0.00562 | 0.052 | 0.00 |
| M NE APARTMENT | 9485.00 | 11382.00 | 128.98 | 0.742 | 0.890 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 24.00 | 24.00 | 0.00791 | 35.61 | 0.00562 | 0.052 | 0.00 |
| M N1 APARTMENT | 8311.02 | 9973.22 | 113.01 | 0.648 | 0.778 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 24.00 | 24.00 | 0.00796 | 35.61 | 0.00562 | 0.052 | 0.00 |
| M N2 APARTMENT | 8299.30 | 9959.16 | 112.85 | 0.647 | 0.777 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 24.00 | 24.00 | 0.00796 | 35.61 | 0.00562 | 0.052 | 0.00 |
| M S1 APARTMENT | 8422.02 | 10106.43 | 114.52 | 0.657 | 0.788 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 24.00 | 24.00 | 0.00800 | 35.61 | 0.00562 | 0.052 | 0.00 |
| M S2 APARTMENT | 8410.07 | 10092.09 | 114.36 | 0.656 | 0.787 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 24.00 | 24.00 | 0.00800 | 35.61 | 0.00562 | 0.052 | 0.00 |
| T SW APARTMENT | 5888.32 | 7065.99 | 80.07 | 0.462 | 0.554 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 24.00 | 24.00 | 0.00791 | 35.61 | 0.00562 | 0.026 | 0.00 |
| T NW APARTMENT | 5885.23 | 7062.28 | 80.03 | 0.462 | 0.554 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 24.00 | 24.00 | 0.00790 | 35.61 | 0.00562 | 0.026 | 0.00 |
| T SE APARTMENT | 5358.16 | 6429.80 | 72.86 | 0.420 | 0.503 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 24.00 | 24.00 | 0.00790 | 35.61 | 0.00562 | 0.026 | 0.00 |
| T NE APARTMENT | 5354.37 | 6425.24 | 72.81 | 0.419 | 0.503 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 24.00 | 24.00 | 0.00789 | 35.61 | 0.00562 | 0.026 | 0.00 |
| T N1 APARTMENT | 4813.11 | 5775.73 | 65.45 | 0.376 | 0.451 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 24.00 | 24.00 | 0.00795 | 35.61 | 0.00562 | 0.026 | 0.00 |
| T N2 APARTMENT | 4796.87 | 5756.24 | 65.23 | 0.375 | 0.450 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 24.00 | 24.00 | 0.00795 | 35.61 | 0.00562 | 0.026 | 0.00 |
| T S1 APARTMENT | 4822.56 | 5787.07 | 65.58 | 0.377 | 0.452 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 24.00 | 24.00 | 0.00796 | 35.61 | 0.00562 | 0.026 | 0.00 |
| T S2 APARTMENT | 4806.43 | 5767.71 | 65.36 | 0.376 | 0.451 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 24.00 | 24.00 | 0.00796 | 35.61 | 0.00562 | 0.026 | 0.00 |
| Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
| G SW APARTMENT | 957.71 | 1149.25 | 13.02 | 0.045 | 0.055 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 04:00:00 | 21.10 | 21.10 | 0.00749 | 0.50 | 0.00432 | 0.026 | 0.00 |
| G NW APARTMENT | 829.66 | 995.59 | 11.28 | 0.039 | 0.047 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 04:00:00 | 21.10 | 21.10 | 0.00775 | 0.50 | 0.00432 | 0.026 | 0.00 |
| OFFICE | 1429.95 | 1715.94 | 19.44 | 0.068 | 0.081 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 18:50:00 | 21.10 | 21.10 | 0.00764 | 0.50 | 0.00432 | 0.038 | 0.00 |
| G NE APARTMENT | 832.56 | 999.07 | 11.32 | 0.040 | 0.047 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 04:00:00 | 21.10 | 21.10 | 0.00775 | 0.50 | 0.00432 | 0.026 | 0.00 |
| G N1 APARTMENT | 420.43 | 504.52 | 5.72 | 0.020 | 0.026 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 04:00:00 | 21.10 | 21.10 | 0.00793 | 0.50 | 0.00432 | 0.026 | 0.00 |
| G N2 APARTMENT | 420.52 | 504.63 | 5.72 | 0.020 | 0.026 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 04:00:00 | 21.10 | 21.10 | 0.00793 | 0.50 | 0.00432 | 0.026 | 0.00 |
| G S1 APARTMENT | 548.98 | 658.78 | 7.46 | 0.026 | 0.031 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 04:00:00 | 21.10 | 21.10 | 0.00745 | 0.50 | 0.00432 | 0.026 | 0.00 |
| G S2 APARTMENT | 559.42 | 671.31 | 7.61 | 0.027 | 0.032 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 04:00:00 | 21.10 | 21.10 | 0.00746 | 0.50 | 0.00432 | 0.026 | 0.00 |
| M SW APARTMENT | 2177.20 | 2612.63 | 29.61 | 0.103 | 0.124 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | 21.10 | 21.10 | 0.00738 | 0.50 | 0.00432 | 0.052 | 0.00 |
| M NW APARTMENT | 1885.10 | 2262.12 | 25.63 | 0.089 | 0.107 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | 21.10 | 21.10 | 0.00758 | 0.50 | 0.00432 | 0.052 | 0.00 |
| M SE APARTMENT | 2184.30 | 2621.16 | 29.70 | 0.104 | 0.124 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | 21.10 | 21.10 | 0.00738 | 0.50 | 0.00432 | 0.052 | 0.00 |
| M NE APARTMENT | 1892.29 | 2270.75 | 25.73 | 0.090 | 0.108 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | 21.10 | 21.10 | 0.00758 | 0.50 | 0.00432 | 0.052 | 0.00 |
| M N1 APARTMENT | 845.12 | 1014.14 | 11.49 | 0.040 | 0.052 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | 21.10 | 21.10 | 0.00766 | 0.50 | 0.00432 | 0.052 | 0.00 |
| M N2 APARTMENT | 845.32 | 1014.39 | 11.49 | 0.040 | 0.052 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | 21.10 | 21.10 | 0.00766 | 0.50 | 0.00432 | 0.052 | 0.00 |
| M S1 APARTMENT | 1130.00 | 1356.00 | 15.37 | 0.054 | 0.064 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | 21.10 | 21.10 | 0.00727 | 0.50 | 0.00432 | 0.052 | 0.00 |
| M S2 APARTMENT | 1130.20 | 1356.24 | 15.37 | 0.054 | 0.064 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | 21.10 | 21.10 | 0.00727 | 0.50 | 0.00432 | 0.052 | 0.00 |
| T SW APARTMENT | 2041.86 | 2450.23 | 27.76 | 0.097 | 0.116 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | 21.10 | 21.10 | 0.00754 | 0.50 | 0.00432 | 0.026 | 0.00 |
| T NW APARTMENT | 1884.79 | 2261.75 | 25.63 | 0.089 | 0.107 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | 21.10 | 21.10 | 0.00766 | 0.50 | 0.00432 | 0.026 | 0.00 |
| T SE APARTMENT | 2046.16 | 2455.39 | 27.82 | 0.097 | 0.117 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | 21.10 | 21.10 | 0.00754 | 0.50 | 0.00432 | 0.026 | 0.00 |
| T NE APARTMENT | 1889.18 | 2267.01 | 25.69 | 0.090 | 0.108 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | 21.10 | 21.10 | 0.00766 | 0.50 | 0.00432 | 0.026 | 0.00 |
| T N1 APARTMENT | 1280.12 | 1536.15 | 17.41 | 0.061 | 0.073 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | 21.10 | 21.10 | 0.00778 | 0.50 | 0.00432 | 0.026 | 0.00 |
| T N2 APARTMENT | 1280.26 | 1536.31 | 17.41 | 0.061 | 0.073 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | 21.10 | 21.10 | 0.00778 | 0.50 | 0.00432 | 0.026 | 0.00 |
| T S1 APARTMENT | 1438.40 | 1726.09 | 19.56 | 0.068 | 0.082 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | 21.10 | 21.10 | 0.00760 | 0.50 | 0.00432 | 0.026 | 0.00 |
| T S2 APARTMENT | 1438.53 | 1726.24 | 19.56 | 0.068 | 0.082 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | 21.10 | 21.10 | 0.00760 | 0.50 | 0.00432 | 0.026 | 0.00 |
| Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
| SPLIT GSW | 0.42 | 0.42 | 0.05 | 0.05 | 0.4245 | 0.4245 | 0.4245 | 1.0000 | 1.0000 |
| SPLIT GNW | 0.42 | 0.42 | 0.05 | 0.05 | 0.4196 | 0.4196 | 0.4196 | 1.0000 | 1.0000 |
| SPLIT OFFICE | 0.45 | 0.45 | 0.08 | 0.08 | 0.4531 | 0.4531 | 0.4531 | 1.0000 | 1.0000 |
| SPLIT GNE | 0.39 | 0.39 | 0.05 | 0.05 | 0.3944 | 0.3944 | 0.3944 | 1.0000 | 1.0000 |
| SPLIT GN1 | 0.35 | 0.35 | 0.03 | 0.03 | 0.3482 | 0.3482 | 0.3482 | 1.0000 | 1.0000 |
| SPLIT GN2 | 0.35 | 0.35 | 0.03 | 0.03 | 0.3478 | 0.3478 | 0.3478 | 1.0000 | 1.0000 |
| SPLIT GS1 | 0.35 | 0.35 | 0.03 | 0.03 | 0.3541 | 0.3541 | 0.3541 | 1.0000 | 1.0000 |
| SPLIT GS2 | 0.36 | 0.36 | 0.03 | 0.03 | 0.3568 | 0.3568 | 0.3568 | 1.0000 | 1.0000 |
| SPLIT MSW | 0.97 | 0.97 | 0.12 | 0.12 | 0.9657 | 0.9657 | 0.9657 | 1.0000 | 1.0000 |
| SPLIT MNW | 0.96 | 0.96 | 0.11 | 0.11 | 0.9571 | 0.9571 | 0.9571 | 1.0000 | 1.0000 |
| SPLIT MSE | 0.90 | 0.90 | 0.12 | 0.12 | 0.8984 | 0.8984 | 0.8984 | 1.0000 | 1.0000 |
| SPLIT MNE | 0.89 | 0.89 | 0.11 | 0.11 | 0.8899 | 0.8899 | 0.8899 | 1.0000 | 1.0000 |
| SPLIT MN1 | 0.78 | 0.78 | 0.05 | 0.05 | 0.7778 | 0.7778 | 0.7778 | 1.0000 | 1.0000 |
| SPLIT MN2 | 0.78 | 0.78 | 0.05 | 0.05 | 0.7766 | 0.7766 | 0.7766 | 1.0000 | 1.0000 |
| SPLIT MS1 | 0.79 | 0.79 | 0.06 | 0.06 | 0.7884 | 0.7884 | 0.7884 | 1.0000 | 1.0000 |
| SPLIT MS2 | 0.79 | 0.79 | 0.06 | 0.06 | 0.7872 | 0.7872 | 0.7872 | 1.0000 | 1.0000 |
| SPLIT TSW | 0.55 | 0.55 | 0.12 | 0.12 | 0.5542 | 0.5542 | 0.5542 | 1.0000 | 1.0000 |
| SPLIT TNW | 0.55 | 0.55 | 0.11 | 0.11 | 0.5539 | 0.5539 | 0.5539 | 1.0000 | 1.0000 |
| SPLIT TSE | 0.50 | 0.50 | 0.12 | 0.12 | 0.5035 | 0.5035 | 0.5035 | 1.0000 | 1.0000 |
| SPLIT TNE | 0.50 | 0.50 | 0.11 | 0.11 | 0.5031 | 0.5031 | 0.5031 | 1.0000 | 1.0000 |
| SPLIT TN1 | 0.45 | 0.45 | 0.07 | 0.07 | 0.4513 | 0.4513 | 0.4513 | 1.0000 | 1.0000 |
| SPLIT TN2 | 0.45 | 0.45 | 0.07 | 0.07 | 0.4498 | 0.4498 | 0.4498 | 1.0000 | 1.0000 |
| SPLIT TS1 | 0.45 | 0.45 | 0.08 | 0.08 | 0.4522 | 0.4522 | 0.4522 | 1.0000 | 1.0000 |
| SPLIT TS2 | 0.45 | 0.45 | 0.08 | 0.08 | 0.4507 | 0.4507 | 0.4507 | 1.0000 | 1.0000 |
| Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
| None |
| Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
| SPLIT GSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT GSW | 7027.005 | 5626.208 | 0.424501 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 6269.52 | 6269.52 | 0.424501 | 25.76 | 15.45 | 0.00783609 | 12.80 | 10.58 | 0.00783609 | 35.61 | 0.00562306 | 16.94 | 6.1141 | 24.00 | 0.00798021 | 39.0313 | 4527.83 | 0.00 | 7025.81 | 5349.15 |
| SPLIT GSW HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT GSW | 9400.997 | 9400.997 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 04:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 04:00:00 | 9401.00 | 9401.00 | 0.424501 | 19.84 | 12.84 | 0.00729525 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 6.1141 | 21.10 | 0.00748929 | 43.7218 | 957.71 | 0.00 | -999.00 | -999.00 |
| SPLIT GNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT GNW | 6946.453 | 5561.714 | 0.419635 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 6194.29 | 6194.29 | 0.419635 | 25.77 | 15.43 | 0.00781058 | 12.80 | 10.55 | 0.00781058 | 35.61 | 0.00562306 | 16.94 | 6.1850 | 24.00 | 0.00795480 | 38.9082 | 4476.90 | 0.00 | 6945.27 | 5287.83 |
| SPLIT GNW HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT GNW | 9299.810 | 9299.810 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 04:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 04:00:00 | 9299.81 | 9299.81 | 0.419635 | 19.83 | 13.06 | 0.00753960 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 6.1850 | 21.10 | 0.00775215 | 45.2365 | 829.66 | 0.00 | -999.00 | -999.00 |
| SPLIT OFFICE COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT OFFICE | 7499.943 | 6004.869 | 0.453072 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:20:00 | 6774.32 | 6774.32 | 0.453072 | 25.78 | 15.36 | 0.00771554 | 12.80 | 10.46 | 0.00771554 | 34.24 | 0.00562096 | 16.49 | 8.4106 | 23.90 | 0.00791172 | 38.9329 | 4620.50 | 0.00 | 7498.67 | 5709.16 |
| SPLIT OFFICE HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT OFFICE | 10269.022 | 10269.022 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 18:50:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 18:50:00 | 10269.02 | 10269.02 | 0.453072 | 19.37 | 12.72 | 0.00735884 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 8.4106 | 21.10 | 0.00763830 | 44.5805 | 1429.95 | 0.00 | -999.00 | -999.00 |
| SPLIT GNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT GNE | 6528.311 | 5226.927 | 0.394375 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 5821.87 | 5821.87 | 0.394375 | 25.81 | 15.44 | 0.00779623 | 12.80 | 10.54 | 0.00779623 | 35.61 | 0.00562306 | 16.94 | 6.5812 | 24.00 | 0.00794933 | 38.8817 | 4212.77 | 0.00 | 6527.20 | 4969.53 |
| SPLIT GNE HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT GNE | 8775.362 | 8775.362 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 04:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 04:00:00 | 8775.36 | 8775.36 | 0.394375 | 19.74 | 13.01 | 0.00752671 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 6.5812 | 21.10 | 0.00775293 | 45.2410 | 832.56 | 0.00 | -999.00 | -999.00 |
| SPLIT GN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT GN1 | 5764.573 | 4615.435 | 0.348238 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 5148.41 | 5148.41 | 0.348238 | 25.91 | 15.49 | 0.00781847 | 12.80 | 10.56 | 0.00781847 | 35.61 | 0.00562306 | 16.94 | 7.4531 | 24.00 | 0.00799527 | 39.1041 | 3731.90 | 0.00 | 5763.59 | 4388.15 |
| SPLIT GN1 HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT GN1 | 7817.376 | 7817.376 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 7817.38 | 7817.38 | 0.348238 | 19.56 | 13.07 | 0.00765939 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 7.4531 | 21.10 | 0.00783126 | 45.6919 | 376.33 | 0.00 | -999.00 | -999.00 |
| SPLIT GN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT GN2 | 5757.175 | 4609.512 | 0.347791 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 5141.83 | 5141.83 | 0.347791 | 25.91 | 15.49 | 0.00781821 | 12.80 | 10.56 | 0.00781821 | 35.61 | 0.00562306 | 16.94 | 7.4627 | 24.00 | 0.00799523 | 39.1039 | 3727.20 | 0.00 | 5756.20 | 4382.52 |
| SPLIT GN2 HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT GN2 | 7808.098 | 7808.098 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 7808.10 | 7808.10 | 0.347791 | 19.56 | 13.07 | 0.00765907 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 7.4627 | 21.10 | 0.00783133 | 45.6922 | 376.42 | 0.00 | -999.00 | -999.00 |
| SPLIT GS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT GS1 | 5861.901 | 4693.362 | 0.354117 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 5240.52 | 5240.52 | 0.354117 | 25.90 | 15.52 | 0.00786509 | 12.80 | 10.61 | 0.00786509 | 35.61 | 0.00562306 | 16.94 | 7.3294 | 24.00 | 0.00804242 | 39.3324 | 3792.96 | 0.00 | 5860.90 | 4462.24 |
| SPLIT GS1 HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT GS1 | 7939.576 | 7939.576 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 04:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 04:00:00 | 7939.58 | 7939.58 | 0.354117 | 19.59 | 12.67 | 0.00721805 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 7.3294 | 21.10 | 0.00744761 | 43.4807 | 548.98 | 0.00 | -999.00 | -999.00 |
| SPLIT GS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT GS2 | 5906.099 | 4728.750 | 0.356787 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 5279.83 | 5279.83 | 0.356787 | 25.89 | 15.52 | 0.00786607 | 12.80 | 10.61 | 0.00786607 | 35.61 | 0.00562306 | 16.94 | 7.2745 | 24.00 | 0.00804204 | 39.3306 | 3820.74 | 0.00 | 5905.09 | 4495.88 |
| SPLIT GS2 HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT GS2 | 7995.012 | 7995.012 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 04:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 04:00:00 | 7995.01 | 7995.01 | 0.356787 | 19.60 | 12.68 | 0.00722927 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 7.2745 | 21.10 | 0.00745786 | 43.5399 | 559.42 | 0.00 | -999.00 | -999.00 |
| SPLIT MSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT MSW | 15986.101 | 12799.356 | 0.965720 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 14244.62 | 14244.62 | 0.965720 | 25.69 | 15.41 | 0.00781486 | 12.80 | 10.56 | 0.00781486 | 35.61 | 0.00562306 | 16.94 | 5.3752 | 24.00 | 0.00793936 | 38.8336 | 20565.44 | 0.00 | 15983.38 | 12169.05 |
| SPLIT MSW HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT MSW | 21225.516 | 21225.516 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | 21225.52 | 21225.52 | 0.965720 | 19.99 | 12.82 | 0.00721433 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 5.3752 | 21.10 | 0.00737900 | 43.0859 | 4354.39 | 0.00 | -999.00 | -999.00 |
| SPLIT MNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT MNW | 15842.642 | 12684.495 | 0.957054 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 14111.07 | 14111.07 | 0.957054 | 25.69 | 15.40 | 0.00779612 | 12.80 | 10.54 | 0.00779612 | 35.61 | 0.00562306 | 16.94 | 5.4238 | 24.00 | 0.00792074 | 38.7433 | 20382.74 | 0.00 | 15839.95 | 12059.85 |
| SPLIT MNW HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT MNW | 21045.260 | 21045.260 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | 21045.26 | 21045.26 | 0.957054 | 19.98 | 12.99 | 0.00740265 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 5.4238 | 21.10 | 0.00757969 | 44.2428 | 3770.19 | 0.00 | -999.00 | -999.00 |
| SPLIT MSE COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT MSE | 14872.001 | 11907.346 | 0.898418 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 13253.01 | 13253.01 | 0.898418 | 25.73 | 15.41 | 0.00780117 | 12.80 | 10.54 | 0.00780117 | 35.61 | 0.00562306 | 16.94 | 5.7778 | 24.00 | 0.00793473 | 38.8112 | 19149.53 | 0.00 | 14869.47 | 11320.97 |
| SPLIT MSE HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT MSE | 19828.133 | 19828.133 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | 19828.13 | 19828.13 | 0.898418 | 19.91 | 12.78 | 0.00720362 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 5.7778 | 21.10 | 0.00738071 | 43.0958 | 4368.60 | 0.00 | -999.00 | -999.00 |
| SPLIT MNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT MNE | 14730.589 | 11794.123 | 0.889875 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 13120.47 | 13120.47 | 0.889875 | 25.74 | 15.39 | 0.00777830 | 12.80 | 10.52 | 0.00777830 | 35.61 | 0.00562306 | 16.94 | 5.8333 | 24.00 | 0.00791181 | 38.7001 | 18970.00 | 0.00 | 14728.08 | 11213.32 |
| SPLIT MNE HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT MNE | 19650.468 | 19650.468 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | 19650.47 | 19650.47 | 0.889875 | 19.90 | 12.95 | 0.00739054 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 5.8333 | 21.10 | 0.00758102 | 44.2505 | 3784.58 | 0.00 | -999.00 | -999.00 |
| SPLIT MN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT MN1 | 12874.563 | 10308.087 | 0.777752 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 11485.24 | 11485.24 | 0.777752 | 25.83 | 15.45 | 0.00780570 | 12.80 | 10.55 | 0.00780570 | 35.61 | 0.00562306 | 16.94 | 6.6742 | 24.00 | 0.00796180 | 38.9421 | 16622.04 | 0.00 | 12872.37 | 9800.46 |
| SPLIT MN1 HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT MN1 | 17322.320 | 17322.320 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 17322.32 | 17322.32 | 0.777752 | 19.72 | 12.92 | 0.00743760 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 6.6742 | 21.10 | 0.00748937 | 43.7212 | 1413.81 | 0.00 | -999.00 | -999.00 |
| SPLIT MN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT MN2 | 12855.986 | 10293.213 | 0.776630 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 11468.70 | 11468.70 | 0.776630 | 25.83 | 15.45 | 0.00780538 | 12.80 | 10.55 | 0.00780538 | 35.61 | 0.00562306 | 16.94 | 6.6839 | 24.00 | 0.00796170 | 38.9416 | 16598.59 | 0.00 | 12853.80 | 9786.32 |
| SPLIT MN2 HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT MN2 | 17299.020 | 17299.020 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 17299.02 | 17299.02 | 0.776630 | 19.72 | 12.92 | 0.00743736 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 6.6839 | 21.10 | 0.00748951 | 43.7221 | 1414.20 | 0.00 | -999.00 | -999.00 |
| SPLIT MS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT MS1 | 13050.423 | 10448.890 | 0.788376 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 11651.14 | 11651.14 | 0.788376 | 25.82 | 15.48 | 0.00784171 | 12.80 | 10.58 | 0.00784171 | 35.61 | 0.00562306 | 16.94 | 6.5843 | 24.00 | 0.00799809 | 39.1179 | 16844.05 | 0.00 | 13048.20 | 9934.33 |
| SPLIT MS1 HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT MS1 | 17543.156 | 17543.156 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | 17543.16 | 17543.16 | 0.788376 | 19.74 | 12.60 | 0.00707636 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 6.5843 | 21.10 | 0.00727095 | 42.4616 | 2260.00 | 0.00 | -999.00 | -999.00 |
| SPLIT MS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT MS2 | 13031.496 | 10433.736 | 0.787233 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 11634.31 | 11634.31 | 0.787233 | 25.82 | 15.48 | 0.00784152 | 12.80 | 10.58 | 0.00784152 | 35.61 | 0.00562306 | 16.94 | 6.5939 | 24.00 | 0.00799812 | 39.1180 | 16820.15 | 0.00 | 13029.28 | 9919.93 |
| SPLIT MS2 HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT MS2 | 17519.417 | 17519.417 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | 17519.42 | 17519.42 | 0.787233 | 19.74 | 12.60 | 0.00707618 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 6.5939 | 21.10 | 0.00727106 | 42.4623 | 2260.40 | 0.00 | -999.00 | -999.00 |
| SPLIT TSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT TSW | 9173.881 | 7345.116 | 0.554194 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 8166.08 | 8166.08 | 0.554194 | 25.61 | 15.37 | 0.00780342 | 12.80 | 10.54 | 0.00780342 | 35.61 | 0.00562306 | 16.94 | 4.6833 | 24.00 | 0.00791055 | 38.6939 | 5888.32 | 0.00 | 9172.32 | 6983.41 |
| SPLIT TSW HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT TSW | 12094.008 | 12094.008 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | 12094.01 | 12094.01 | 0.554194 | 20.13 | 13.04 | 0.00739045 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 4.6833 | 21.10 | 0.00754154 | 44.0244 | 2041.86 | 0.00 | -999.00 | -999.00 |
| SPLIT TNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT TNW | 9169.111 | 7341.297 | 0.553906 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 8159.68 | 8159.68 | 0.553906 | 25.61 | 15.36 | 0.00779244 | 12.80 | 10.53 | 0.00779244 | 35.61 | 0.00562306 | 16.94 | 4.6857 | 24.00 | 0.00789909 | 38.6384 | 5885.23 | 0.00 | 9167.55 | 6979.77 |
| SPLIT TNW HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT TNW | 12087.834 | 12087.834 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | 12087.83 | 12087.83 | 0.553906 | 20.13 | 13.14 | 0.00750032 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 4.6857 | 21.10 | 0.00765689 | 44.6887 | 1884.79 | 0.00 | -999.00 | -999.00 |
| SPLIT TSE COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT TSE | 8334.513 | 6673.072 | 0.503488 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 7419.36 | 7419.36 | 0.503488 | 25.66 | 15.38 | 0.00778434 | 12.80 | 10.53 | 0.00778434 | 35.61 | 0.00562306 | 16.94 | 5.1550 | 24.00 | 0.00790181 | 38.6517 | 5358.16 | 0.00 | 8333.09 | 6344.46 |
| SPLIT TSE HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT TSE | 11041.197 | 11041.197 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | 11041.20 | 11041.20 | 0.503488 | 20.04 | 12.99 | 0.00737604 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 5.1550 | 21.10 | 0.00754238 | 44.0293 | 2046.16 | 0.00 | -999.00 | -999.00 |
| SPLIT TNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT TNE | 8328.578 | 6668.320 | 0.503129 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 7411.70 | 7411.70 | 0.503129 | 25.67 | 15.36 | 0.00777096 | 12.80 | 10.51 | 0.00777096 | 35.61 | 0.00562306 | 16.94 | 5.1586 | 24.00 | 0.00788778 | 38.5837 | 5354.37 | 0.00 | 8327.16 | 6339.94 |
| SPLIT TNE HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT TNE | 11033.580 | 11033.580 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | 11033.58 | 11033.58 | 0.503129 | 20.04 | 13.09 | 0.00748518 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 5.1586 | 21.10 | 0.00765758 | 44.6927 | 1889.18 | 0.00 | -999.00 | -999.00 |
| SPLIT TN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT TN1 | 7470.871 | 5981.592 | 0.451315 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 6659.44 | 6659.44 | 0.451315 | 25.73 | 15.42 | 0.00781200 | 12.80 | 10.55 | 0.00781200 | 35.61 | 0.00562306 | 16.94 | 5.7509 | 24.00 | 0.00794556 | 38.8635 | 4813.11 | 0.00 | 7469.60 | 5687.03 |
| SPLIT TN1 HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT TN1 | 9957.592 | 9957.592 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | 9957.59 | 9957.59 | 0.451315 | 19.91 | 13.13 | 0.00757893 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 5.7509 | 21.10 | 0.00777805 | 45.3860 | 1280.12 | 0.00 | -999.00 | -999.00 |
| SPLIT TN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT TN2 | 7445.308 | 5961.125 | 0.449771 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 6636.69 | 6636.69 | 0.449771 | 25.73 | 15.42 | 0.00781131 | 12.80 | 10.55 | 0.00781131 | 35.61 | 0.00562306 | 16.94 | 5.7706 | 24.00 | 0.00794532 | 38.8623 | 4796.87 | 0.00 | 7444.04 | 5667.57 |
| SPLIT TN2 HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT TN2 | 9925.530 | 9925.530 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | 9925.53 | 9925.53 | 0.449771 | 19.91 | 13.12 | 0.00757826 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 5.7706 | 21.10 | 0.00777807 | 45.3861 | 1280.26 | 0.00 | -999.00 | -999.00 |
| SPLIT TS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT TS1 | 7485.390 | 5993.217 | 0.452192 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 6675.28 | 6675.28 | 0.452192 | 25.73 | 15.44 | 0.00783028 | 12.80 | 10.57 | 0.00783028 | 35.61 | 0.00562306 | 16.94 | 5.7397 | 24.00 | 0.00796468 | 38.9561 | 4822.56 | 0.00 | 7484.12 | 5698.08 |
| SPLIT TS1 HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT TS1 | 9975.965 | 9975.965 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | 9975.97 | 9975.97 | 0.452192 | 19.92 | 12.97 | 0.00741089 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 5.7397 | 21.10 | 0.00759937 | 44.3569 | 1438.40 | 0.00 | -999.00 | -999.00 |
| SPLIT TS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT TS2 | 7459.949 | 5972.847 | 0.450655 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 6652.64 | 6652.64 | 0.450655 | 25.73 | 15.44 | 0.00782974 | 12.80 | 10.57 | 0.00782974 | 35.61 | 0.00562306 | 16.94 | 5.7593 | 24.00 | 0.00796459 | 38.9557 | 4806.43 | 0.00 | 7458.68 | 5678.71 |
| SPLIT TS2 HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT TS2 | 9944.055 | 9944.055 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | 9944.05 | 9944.05 | 0.450655 | 19.91 | 12.97 | 0.00741028 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 5.7593 | 21.10 | 0.00759941 | 44.3571 | 1438.53 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 09:17:08
Coils| Coil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
| SPLIT GSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT GSW | G SW APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 7027.005 | 5626.208 | 0.424501 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.4069 | 1004.8586 | 1.0932 | SPLIT GSW SUPPLY FAN | Fan:OnOff | 0.424501 | 0.46406243 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | Sensible | 6269.52 | 6269.52 | 0.8922 | 0.46406243 | 0.424501 | 25.76 | 15.45 | 0.00783609 | 45861.9 | 12.80 | 10.58 | 0.00783609 | 32646.0 | -999.0 | -999.00 | -999.00 | -999.00 | 475.487 | 5794.03 | 35.61 | 0.00562306 | 16.94 | 0.02595455 | 6.1141 | 24.05 | 0.00798021 | 24.00 | 0.00798021 | 39.0313 | 4527.83 | 0.00 | 7025.81 | 5349.15 | 0.44573547 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.93 | 14.12 | 0.00970984 | 39560.1 | |
| SPLIT GSW HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT GSW | G SW APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 9400.997 | 9400.997 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | SPLIT GSW SUPPLY FAN | Fan:OnOff | 0.424501 | 0.46406243 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 04:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 04:00:00 | Sensible | 9401.00 | 9401.00 | 1.0000 | 0.46406243 | 0.424501 | 19.84 | 12.84 | 0.00729525 | 38450.0 | 40.00 | 20.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9401.00 | 0.50 | 0.00431558 | 0.50 | 0.02595455 | 6.1141 | 21.10 | 0.00748929 | 21.10 | 0.00748929 | 43.7218 | 957.71 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT GNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT GNW | G NW APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 6946.453 | 5561.714 | 0.419635 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.3595 | 1004.8586 | 1.0932 | SPLIT GNW SUPPLY FAN | Fan:OnOff | 0.419635 | 0.45874278 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | Sensible | 6194.29 | 6194.29 | 0.8917 | 0.45874278 | 0.419635 | 25.77 | 15.43 | 0.00781058 | 45804.7 | 12.80 | 10.55 | 0.00781058 | 32581.6 | -999.0 | -999.00 | -999.00 | -999.00 | 470.037 | 5724.26 | 35.61 | 0.00562306 | 16.94 | 0.02595455 | 6.1850 | 24.05 | 0.00795480 | 24.00 | 0.00795480 | 38.9082 | 4476.90 | 0.00 | 6945.27 | 5287.83 | 0.44062590 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.93 | 14.12 | 0.00970984 | 39560.1 | |
| SPLIT GNW HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT GNW | G NW APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 9299.810 | 9299.810 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | SPLIT GNW SUPPLY FAN | Fan:OnOff | 0.419635 | 0.45874278 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 04:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 04:00:00 | Sensible | 9299.81 | 9299.81 | 1.0000 | 0.45874278 | 0.419635 | 19.83 | 13.06 | 0.00753960 | 39055.5 | 40.00 | 20.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9299.81 | 0.50 | 0.00431558 | 0.50 | 0.02595455 | 6.1850 | 21.10 | 0.00775215 | 21.10 | 0.00775215 | 45.2365 | 829.66 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT OFFICE COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT OFFICE | OFFICE | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 7499.943 | 6004.869 | 0.453072 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.1828 | 1004.8586 | 1.0932 | SPLIT OFFICE SUPPLY FAN | Fan:OnOff | 0.453072 | 0.49529519 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:20:00 | Sensible | 6774.32 | 6774.32 | 0.9032 | 0.49529519 | 0.453072 | 25.78 | 15.36 | 0.00771554 | 45565.9 | 12.80 | 10.46 | 0.00771554 | 32341.7 | -999.0 | -999.00 | -999.00 | -999.00 | 507.489 | 6266.83 | 34.24 | 0.00562096 | 16.49 | 0.03810604 | 8.4106 | 23.90 | 0.00790789 | 23.90 | 0.00791172 | 38.9329 | 4620.50 | 0.00 | 7498.67 | 5709.16 | 0.47573477 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.93 | 14.12 | 0.00970984 | 39560.1 | |
| SPLIT OFFICE HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT OFFICE | OFFICE | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 10269.022 | 10269.022 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | SPLIT OFFICE SUPPLY FAN | Fan:OnOff | 0.453072 | 0.49529519 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 18:50:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 18:50:00 | Sensible | 10269.02 | 10269.02 | 1.0000 | 0.49529519 | 0.453072 | 19.37 | 12.72 | 0.00735884 | 38129.8 | 40.00 | 20.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10269.02 | 0.50 | 0.00431558 | 0.50 | 0.03810604 | 8.4106 | 21.10 | 0.00763830 | 21.10 | 0.00763830 | 44.5805 | 1429.95 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT GNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT GNE | G NE APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 6528.311 | 5226.927 | 0.394375 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.3328 | 1004.8586 | 1.0932 | SPLIT GNE SUPPLY FAN | Fan:OnOff | 0.394375 | 0.43112877 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | Sensible | 5821.87 | 5821.87 | 0.8918 | 0.43112877 | 0.394375 | 25.81 | 15.44 | 0.00779623 | 45811.5 | 12.80 | 10.54 | 0.00779623 | 32545.4 | -999.0 | -999.00 | -999.00 | -999.00 | 441.743 | 5380.13 | 35.61 | 0.00562306 | 16.94 | 0.02595455 | 6.5812 | 24.05 | 0.00794933 | 24.00 | 0.00794933 | 38.8817 | 4212.77 | 0.00 | 6527.20 | 4969.53 | 0.41410244 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.93 | 14.12 | 0.00970984 | 39560.1 | |
| SPLIT GNE HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT GNE | G NE APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 8775.362 | 8775.362 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | SPLIT GNE SUPPLY FAN | Fan:OnOff | 0.394375 | 0.43112877 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 04:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 04:00:00 | Sensible | 8775.36 | 8775.36 | 1.0000 | 0.43112877 | 0.394375 | 19.74 | 13.01 | 0.00752671 | 38939.7 | 40.00 | 20.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8775.36 | 0.50 | 0.00431558 | 0.50 | 0.02595455 | 6.5812 | 21.10 | 0.00775293 | 21.10 | 0.00775293 | 45.2410 | 832.56 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT GN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT GN1 | G N1 APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 5764.573 | 4615.435 | 0.348238 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.3741 | 1004.8586 | 1.0932 | SPLIT GN1 SUPPLY FAN | Fan:OnOff | 0.348238 | 0.38069159 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | Sensible | 5148.41 | 5148.41 | 0.8931 | 0.38069159 | 0.348238 | 25.91 | 15.49 | 0.00781847 | 45965.1 | 12.80 | 10.56 | 0.00781847 | 32601.5 | -999.0 | -999.00 | -999.00 | -999.00 | 390.064 | 4758.35 | 35.61 | 0.00562306 | 16.94 | 0.02595455 | 7.4531 | 24.04 | 0.00799527 | 24.00 | 0.00799527 | 39.1041 | 3731.90 | 0.00 | 5763.59 | 4388.15 | 0.36565715 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.93 | 14.12 | 0.00970984 | 39560.1 | |
| SPLIT GN1 HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT GN1 | G N1 APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 7817.376 | 7817.376 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | SPLIT GN1 SUPPLY FAN | Fan:OnOff | 0.348238 | 0.38069159 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 7817.38 | 7817.38 | 1.0000 | 0.38069159 | 0.348238 | 19.56 | 13.07 | 0.00765939 | 39093.6 | 40.00 | 20.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 7817.38 | 0.50 | 0.00431558 | 0.50 | 0.02595455 | 7.4531 | 21.10 | 0.00792868 | 21.10 | 0.00783126 | 45.6919 | 376.33 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT GN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT GN2 | G N2 APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 5757.175 | 4609.512 | 0.347791 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.3737 | 1004.8586 | 1.0932 | SPLIT GN2 SUPPLY FAN | Fan:OnOff | 0.347791 | 0.38020304 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | Sensible | 5141.83 | 5141.83 | 0.8931 | 0.38020304 | 0.347791 | 25.91 | 15.49 | 0.00781821 | 45965.5 | 12.80 | 10.56 | 0.00781821 | 32600.8 | -999.0 | -999.00 | -999.00 | -999.00 | 389.563 | 4752.26 | 35.61 | 0.00562306 | 16.94 | 0.02595455 | 7.4627 | 24.04 | 0.00799523 | 24.00 | 0.00799523 | 39.1039 | 3727.20 | 0.00 | 5756.20 | 4382.52 | 0.36518790 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.93 | 14.12 | 0.00970984 | 39560.1 | |
| SPLIT GN2 HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT GN2 | G N2 APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 7808.098 | 7808.098 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | SPLIT GN2 SUPPLY FAN | Fan:OnOff | 0.347791 | 0.38020304 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 7808.10 | 7808.10 | 1.0000 | 0.38020304 | 0.347791 | 19.56 | 13.07 | 0.00765907 | 39090.7 | 40.00 | 20.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 7808.10 | 0.50 | 0.00431558 | 0.50 | 0.02595455 | 7.4627 | 21.10 | 0.00792871 | 21.10 | 0.00783133 | 45.6922 | 376.42 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT GS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT GS1 | G S1 APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 5861.901 | 4693.362 | 0.354117 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.4608 | 1004.8586 | 1.0932 | SPLIT GS1 SUPPLY FAN | Fan:OnOff | 0.354117 | 0.38711911 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | Sensible | 5240.52 | 5240.52 | 0.8940 | 0.38711911 | 0.354117 | 25.90 | 15.52 | 0.00786509 | 46069.9 | 12.80 | 10.61 | 0.00786509 | 32719.2 | -999.0 | -999.00 | -999.00 | -999.00 | 396.650 | 4843.87 | 35.61 | 0.00562306 | 16.94 | 0.02595455 | 7.3294 | 24.04 | 0.00804242 | 24.00 | 0.00804242 | 39.3324 | 3792.96 | 0.00 | 5860.90 | 4462.24 | 0.37183083 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.93 | 14.12 | 0.00970984 | 39560.1 | |
| SPLIT GS1 HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT GS1 | G S1 APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 7939.576 | 7939.576 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | SPLIT GS1 SUPPLY FAN | Fan:OnOff | 0.354117 | 0.38711911 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 04:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 04:00:00 | Sensible | 7939.58 | 7939.58 | 1.0000 | 0.38711911 | 0.354117 | 19.59 | 12.67 | 0.00721805 | 37999.4 | 40.00 | 20.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 7939.58 | 0.50 | 0.00431558 | 0.50 | 0.02595455 | 7.3294 | 21.10 | 0.00744761 | 21.10 | 0.00744761 | 43.4807 | 548.98 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT GS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT GS2 | G S2 APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 5906.099 | 4728.750 | 0.356787 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.4626 | 1004.8586 | 1.0932 | SPLIT GS2 SUPPLY FAN | Fan:OnOff | 0.356787 | 0.39003799 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | Sensible | 5279.83 | 5279.83 | 0.8940 | 0.39003799 | 0.356787 | 25.89 | 15.52 | 0.00786607 | 46066.1 | 12.80 | 10.61 | 0.00786607 | 32721.7 | -999.0 | -999.00 | -999.00 | -999.00 | 399.640 | 4880.19 | 35.61 | 0.00562306 | 16.94 | 0.02595455 | 7.2745 | 24.04 | 0.00804204 | 24.00 | 0.00804204 | 39.3306 | 3820.74 | 0.00 | 5905.09 | 4495.88 | 0.37463444 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.93 | 14.12 | 0.00970984 | 39560.1 | |
| SPLIT GS2 HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT GS2 | G S2 APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 7995.012 | 7995.012 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | SPLIT GS2 SUPPLY FAN | Fan:OnOff | 0.356787 | 0.39003799 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 04:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 04:00:00 | Sensible | 7995.01 | 7995.01 | 1.0000 | 0.39003799 | 0.356787 | 19.60 | 12.68 | 0.00722927 | 38039.3 | 40.00 | 20.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 7995.01 | 0.50 | 0.00431558 | 0.50 | 0.02595455 | 7.2745 | 21.10 | 0.00745786 | 21.10 | 0.00745786 | 43.5399 | 559.42 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT MSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT MSW | M SW APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 15986.101 | 12799.356 | 0.965720 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.3674 | 1004.8586 | 1.0932 | SPLIT MSW SUPPLY FAN | Fan:OnOff | 0.965720 | 1.05571994 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | Sensible | 14244.62 | 14244.62 | 0.8911 | 1.05571994 | 0.965720 | 25.69 | 15.41 | 0.00781486 | 45729.6 | 12.80 | 10.56 | 0.00781486 | 32592.4 | -999.0 | -999.00 | -999.00 | -999.00 | 1081.711 | 13162.91 | 35.61 | 0.00562306 | 16.94 | 0.05190911 | 5.3752 | 24.06 | 0.00793936 | 24.00 | 0.00793936 | 38.8336 | 20565.44 | 0.00 | 15983.38 | 12169.05 | 1.01402698 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.93 | 14.12 | 0.00970984 | 39560.1 | |
| SPLIT MSW HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT MSW | M SW APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 21225.516 | 21225.516 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | SPLIT MSW SUPPLY FAN | Fan:OnOff | 0.965720 | 1.05571994 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | Sensible | 21225.52 | 21225.52 | 1.0000 | 1.05571994 | 0.965720 | 19.99 | 12.82 | 0.00721433 | 38399.5 | 40.00 | 20.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 21225.52 | 0.50 | 0.00431558 | 0.50 | 0.05190911 | 5.3752 | 21.10 | 0.00737900 | 21.10 | 0.00737900 | 43.0859 | 4354.39 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT MNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT MNW | M NW APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 15842.642 | 12684.495 | 0.957054 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.3326 | 1004.8586 | 1.0932 | SPLIT MNW SUPPLY FAN | Fan:OnOff | 0.957054 | 1.04624590 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | Sensible | 14111.07 | 14111.07 | 0.8907 | 1.04624590 | 0.957054 | 25.69 | 15.40 | 0.00779612 | 45687.1 | 12.80 | 10.54 | 0.00779612 | 32545.1 | -999.0 | -999.00 | -999.00 | -999.00 | 1072.004 | 13039.07 | 35.61 | 0.00562306 | 16.94 | 0.05190911 | 5.4238 | 24.06 | 0.00792074 | 24.00 | 0.00792074 | 38.7433 | 20382.74 | 0.00 | 15839.95 | 12059.85 | 1.00492710 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.93 | 14.12 | 0.00970984 | 39560.1 | |
| SPLIT MNW HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT MNW | M NW APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 21045.260 | 21045.260 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | SPLIT MNW SUPPLY FAN | Fan:OnOff | 0.957054 | 1.04624590 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | Sensible | 21045.26 | 21045.26 | 1.0000 | 1.04624590 | 0.957054 | 19.98 | 12.99 | 0.00740265 | 38867.5 | 40.00 | 20.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 21045.26 | 0.50 | 0.00431558 | 0.50 | 0.05190911 | 5.4238 | 21.10 | 0.00757969 | 21.10 | 0.00757969 | 44.2428 | 3770.19 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT MSE COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT MSE | M SE APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 14872.001 | 11907.346 | 0.898418 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.3420 | 1004.8586 | 1.0932 | SPLIT MSE SUPPLY FAN | Fan:OnOff | 0.898418 | 0.98214491 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | Sensible | 13253.01 | 13253.01 | 0.8911 | 0.98214491 | 0.898418 | 25.73 | 15.41 | 0.00780117 | 45737.4 | 12.80 | 10.54 | 0.00780117 | 32557.8 | -999.0 | -999.00 | -999.00 | -999.00 | 1006.325 | 12246.68 | 35.61 | 0.00562306 | 16.94 | 0.05190911 | 5.7778 | 24.06 | 0.00793473 | 24.00 | 0.00793473 | 38.8112 | 19149.53 | 0.00 | 14869.47 | 11320.97 | 0.94335761 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.93 | 14.12 | 0.00970984 | 39560.1 | |
| SPLIT MSE HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT MSE | M SE APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 19828.133 | 19828.133 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | SPLIT MSE SUPPLY FAN | Fan:OnOff | 0.898418 | 0.98214491 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | Sensible | 19828.13 | 19828.13 | 1.0000 | 0.98214491 | 0.898418 | 19.91 | 12.78 | 0.00720362 | 38287.8 | 40.00 | 20.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 19828.13 | 0.50 | 0.00431558 | 0.50 | 0.05190911 | 5.7778 | 21.10 | 0.00738071 | 21.10 | 0.00738071 | 43.0958 | 4368.60 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT MNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT MNE | M NE APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 14730.589 | 11794.123 | 0.889875 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.2995 | 1004.8586 | 1.0932 | SPLIT MNE SUPPLY FAN | Fan:OnOff | 0.889875 | 0.97280605 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | Sensible | 13120.47 | 13120.47 | 0.8907 | 0.97280605 | 0.889875 | 25.74 | 15.39 | 0.00777830 | 45685.1 | 12.80 | 10.52 | 0.00777830 | 32500.1 | -999.0 | -999.00 | -999.00 | -999.00 | 996.756 | 12123.71 | 35.61 | 0.00562306 | 16.94 | 0.05190911 | 5.8333 | 24.06 | 0.00791181 | 24.00 | 0.00791181 | 38.7001 | 18970.00 | 0.00 | 14728.08 | 11213.32 | 0.93438757 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.93 | 14.12 | 0.00970984 | 39560.1 | |
| SPLIT MNE HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT MNE | M NE APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 19650.468 | 19650.468 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | SPLIT MNE SUPPLY FAN | Fan:OnOff | 0.889875 | 0.97280605 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | Sensible | 19650.47 | 19650.47 | 1.0000 | 0.97280605 | 0.889875 | 19.90 | 12.95 | 0.00739054 | 38750.9 | 40.00 | 20.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 19650.47 | 0.50 | 0.00431558 | 0.50 | 0.05190911 | 5.8333 | 21.10 | 0.00758102 | 21.10 | 0.00758102 | 44.2505 | 3784.58 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT MN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT MN1 | M N1 APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 12874.563 | 10308.087 | 0.777752 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.3504 | 1004.8586 | 1.0932 | SPLIT MN1 SUPPLY FAN | Fan:OnOff | 0.777752 | 0.85023437 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | Sensible | 11485.24 | 11485.24 | 0.8921 | 0.85023437 | 0.777752 | 25.83 | 15.45 | 0.00780570 | 45846.6 | 12.80 | 10.55 | 0.00780570 | 32569.3 | -999.0 | -999.00 | -999.00 | -999.00 | 871.167 | 10614.08 | 35.61 | 0.00562306 | 16.94 | 0.05190911 | 6.6742 | 24.05 | 0.00796180 | 24.00 | 0.00796180 | 38.9421 | 16622.04 | 0.00 | 12872.37 | 9800.46 | 0.81665654 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.93 | 14.12 | 0.00970984 | 39560.1 | |
| SPLIT MN1 HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT MN1 | M N1 APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 17322.320 | 17322.320 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | SPLIT MN1 SUPPLY FAN | Fan:OnOff | 0.777752 | 0.85023437 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 17322.32 | 17322.32 | 1.0000 | 0.85023437 | 0.777752 | 19.72 | 12.92 | 0.00743760 | 38694.1 | 40.00 | 20.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 17322.32 | 0.50 | 0.00431558 | 0.50 | 0.05190911 | 6.6742 | 21.10 | 0.00766087 | 21.10 | 0.00748937 | 43.7212 | 1413.81 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT MN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT MN2 | M N2 APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 12855.986 | 10293.213 | 0.776630 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.3498 | 1004.8586 | 1.0932 | SPLIT MN2 SUPPLY FAN | Fan:OnOff | 0.776630 | 0.84900757 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | Sensible | 11468.70 | 11468.70 | 0.8921 | 0.84900757 | 0.776630 | 25.83 | 15.45 | 0.00780538 | 45846.8 | 12.80 | 10.55 | 0.00780538 | 32568.5 | -999.0 | -999.00 | -999.00 | -999.00 | 869.910 | 10598.79 | 35.61 | 0.00562306 | 16.94 | 0.05190911 | 6.6839 | 24.05 | 0.00796170 | 24.00 | 0.00796170 | 38.9416 | 16598.59 | 0.00 | 12853.80 | 9786.32 | 0.81547819 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.93 | 14.12 | 0.00970984 | 39560.1 | |
| SPLIT MN2 HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT MN2 | M N2 APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 17299.020 | 17299.020 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | SPLIT MN2 SUPPLY FAN | Fan:OnOff | 0.776630 | 0.84900757 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 17299.02 | 17299.02 | 1.0000 | 0.84900757 | 0.776630 | 19.72 | 12.92 | 0.00743736 | 38691.5 | 40.00 | 20.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 17299.02 | 0.50 | 0.00431558 | 0.50 | 0.05190911 | 6.6839 | 21.10 | 0.00766096 | 21.10 | 0.00748951 | 43.7221 | 1414.20 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT MS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT MS1 | M S1 APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 13050.423 | 10448.890 | 0.788376 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.4173 | 1004.8586 | 1.0932 | SPLIT MS1 SUPPLY FAN | Fan:OnOff | 0.788376 | 0.86184814 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | Sensible | 11651.14 | 11651.14 | 0.8928 | 0.86184814 | 0.788376 | 25.82 | 15.48 | 0.00784171 | 45928.4 | 12.80 | 10.58 | 0.00784171 | 32660.2 | -999.0 | -999.00 | -999.00 | -999.00 | 883.066 | 10768.08 | 35.61 | 0.00562306 | 16.94 | 0.05190911 | 6.5843 | 24.05 | 0.00799809 | 24.00 | 0.00799809 | 39.1179 | 16844.05 | 0.00 | 13048.20 | 9934.33 | 0.82781166 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.93 | 14.12 | 0.00970984 | 39560.1 | |
| SPLIT MS1 HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT MS1 | M S1 APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 17543.156 | 17543.156 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | SPLIT MS1 SUPPLY FAN | Fan:OnOff | 0.788376 | 0.86184814 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | Sensible | 17543.16 | 17543.16 | 1.0000 | 0.86184814 | 0.788376 | 19.74 | 12.60 | 0.00707636 | 37796.0 | 40.00 | 20.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 17543.16 | 0.50 | 0.00431558 | 0.50 | 0.05190911 | 6.5843 | 21.10 | 0.00727095 | 21.10 | 0.00727095 | 42.4616 | 2260.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT MS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT MS2 | M S2 APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 13031.496 | 10433.736 | 0.787233 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.4170 | 1004.8586 | 1.0932 | SPLIT MS2 SUPPLY FAN | Fan:OnOff | 0.787233 | 0.86059821 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | Sensible | 11634.31 | 11634.31 | 0.8928 | 0.86059821 | 0.787233 | 25.82 | 15.48 | 0.00784152 | 45928.9 | 12.80 | 10.58 | 0.00784152 | 32659.7 | -999.0 | -999.00 | -999.00 | -999.00 | 881.786 | 10752.53 | 35.61 | 0.00562306 | 16.94 | 0.05190911 | 6.5939 | 24.05 | 0.00799812 | 24.00 | 0.00799812 | 39.1180 | 16820.15 | 0.00 | 13029.28 | 9919.93 | 0.82661108 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.93 | 14.12 | 0.00970984 | 39560.1 | |
| SPLIT MS2 HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT MS2 | M S2 APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 17519.417 | 17519.417 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | SPLIT MS2 SUPPLY FAN | Fan:OnOff | 0.787233 | 0.86059821 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | Sensible | 17519.42 | 17519.42 | 1.0000 | 0.86059821 | 0.787233 | 19.74 | 12.60 | 0.00707618 | 37793.5 | 40.00 | 20.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 17519.42 | 0.50 | 0.00431558 | 0.50 | 0.05190911 | 6.5939 | 21.10 | 0.00727106 | 21.10 | 0.00727106 | 42.4623 | 2260.40 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT TSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT TSW | T SW APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 9173.881 | 7345.116 | 0.554194 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.3462 | 1004.8586 | 1.0932 | SPLIT TSW SUPPLY FAN | Fan:OnOff | 0.554194 | 0.60584183 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | Sensible | 8166.08 | 8166.08 | 0.8901 | 0.60584183 | 0.554194 | 25.61 | 15.37 | 0.00780342 | 45623.8 | 12.80 | 10.54 | 0.00780342 | 32563.5 | -999.0 | -999.00 | -999.00 | -999.00 | 620.757 | 7545.32 | 35.61 | 0.00562306 | 16.94 | 0.02595455 | 4.6833 | 24.07 | 0.00791055 | 24.00 | 0.00791055 | 38.6939 | 5888.32 | 0.00 | 9172.32 | 6983.41 | 0.58191566 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.93 | 14.12 | 0.00970984 | 39560.1 | |
| SPLIT TSW HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT TSW | T SW APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 12094.008 | 12094.008 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | SPLIT TSW SUPPLY FAN | Fan:OnOff | 0.554194 | 0.60584183 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | Sensible | 12094.01 | 12094.01 | 1.0000 | 0.60584183 | 0.554194 | 20.13 | 13.04 | 0.00739045 | 38991.3 | 40.00 | 20.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 12094.01 | 0.50 | 0.00431558 | 0.50 | 0.02595455 | 4.6833 | 21.10 | 0.00754154 | 21.10 | 0.00754154 | 44.0244 | 2041.86 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT TNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT TNW | T NW APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 9169.111 | 7341.297 | 0.553906 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.3258 | 1004.8586 | 1.0932 | SPLIT TNW SUPPLY FAN | Fan:OnOff | 0.553906 | 0.60552682 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | Sensible | 8159.68 | 8159.68 | 0.8899 | 0.60552682 | 0.553906 | 25.61 | 15.36 | 0.00779244 | 45596.1 | 12.80 | 10.53 | 0.00779244 | 32535.8 | -999.0 | -999.00 | -999.00 | -999.00 | 620.435 | 7539.24 | 35.61 | 0.00562306 | 16.94 | 0.02595455 | 4.6857 | 24.07 | 0.00789909 | 24.00 | 0.00789909 | 38.6384 | 5885.23 | 0.00 | 9167.55 | 6979.77 | 0.58161309 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.93 | 14.12 | 0.00970984 | 39560.1 | |
| SPLIT TNW HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT TNW | T NW APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 12087.834 | 12087.834 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | SPLIT TNW SUPPLY FAN | Fan:OnOff | 0.553906 | 0.60552682 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | Sensible | 12087.83 | 12087.83 | 1.0000 | 0.60552682 | 0.553906 | 20.13 | 13.14 | 0.00750032 | 39270.0 | 40.00 | 20.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 12087.83 | 0.50 | 0.00431558 | 0.50 | 0.02595455 | 4.6857 | 21.10 | 0.00765689 | 21.10 | 0.00765689 | 44.6887 | 1884.79 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT TSE COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT TSE | T SE APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 8334.513 | 6673.072 | 0.503488 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.3107 | 1004.8586 | 1.0932 | SPLIT TSE SUPPLY FAN | Fan:OnOff | 0.503488 | 0.55041009 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | Sensible | 7419.36 | 7419.36 | 0.8902 | 0.55041009 | 0.503488 | 25.66 | 15.38 | 0.00778434 | 45628.6 | 12.80 | 10.53 | 0.00778434 | 32515.3 | -999.0 | -999.00 | -999.00 | -999.00 | 563.961 | 6855.40 | 35.61 | 0.00562306 | 16.94 | 0.02595455 | 5.1550 | 24.06 | 0.00790181 | 24.00 | 0.00790181 | 38.6517 | 5358.16 | 0.00 | 8333.09 | 6344.46 | 0.52867306 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.93 | 14.12 | 0.00970984 | 39560.1 | |
| SPLIT TSE HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT TSE | T SE APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 11041.197 | 11041.197 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | SPLIT TSE SUPPLY FAN | Fan:OnOff | 0.503488 | 0.55041009 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | Sensible | 11041.20 | 11041.20 | 1.0000 | 0.55041009 | 0.503488 | 20.04 | 12.99 | 0.00737604 | 38855.8 | 40.00 | 20.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 11041.20 | 0.50 | 0.00431558 | 0.50 | 0.02595455 | 5.1550 | 21.10 | 0.00754238 | 21.10 | 0.00754238 | 44.0293 | 2046.16 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT TNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT TNE | T NE APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 8328.578 | 6668.320 | 0.503129 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.2858 | 1004.8586 | 1.0932 | SPLIT TNE SUPPLY FAN | Fan:OnOff | 0.503129 | 0.55001816 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | Sensible | 7411.70 | 7411.70 | 0.8899 | 0.55001816 | 0.503129 | 25.67 | 15.36 | 0.00777096 | 45594.9 | 12.80 | 10.51 | 0.00777096 | 32481.6 | -999.0 | -999.00 | -999.00 | -999.00 | 563.559 | 6848.14 | 35.61 | 0.00562306 | 16.94 | 0.02595455 | 5.1586 | 24.06 | 0.00788778 | 24.00 | 0.00788778 | 38.5837 | 5354.37 | 0.00 | 8327.16 | 6339.94 | 0.52829660 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.93 | 14.12 | 0.00970984 | 39560.1 | |
| SPLIT TNE HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT TNE | T NE APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 11033.580 | 11033.580 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | SPLIT TNE SUPPLY FAN | Fan:OnOff | 0.503129 | 0.55001816 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | Sensible | 11033.58 | 11033.58 | 1.0000 | 0.55001816 | 0.503129 | 20.04 | 13.09 | 0.00748518 | 39132.4 | 40.00 | 20.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 11033.58 | 0.50 | 0.00431558 | 0.50 | 0.02595455 | 5.1586 | 21.10 | 0.00765758 | 21.10 | 0.00765758 | 44.6927 | 1889.18 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT TN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT TN1 | T N1 APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 7470.871 | 5981.592 | 0.451315 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.3621 | 1004.8586 | 1.0932 | SPLIT TN1 SUPPLY FAN | Fan:OnOff | 0.451315 | 0.49337530 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | Sensible | 6659.44 | 6659.44 | 0.8914 | 0.49337530 | 0.451315 | 25.73 | 15.42 | 0.00781200 | 45766.7 | 12.80 | 10.55 | 0.00781200 | 32585.2 | -999.0 | -999.00 | -999.00 | -999.00 | 505.522 | 6153.92 | 35.61 | 0.00562306 | 16.94 | 0.02595455 | 5.7509 | 24.06 | 0.00794556 | 24.00 | 0.00794556 | 38.8635 | 4813.11 | 0.00 | 7469.60 | 5687.03 | 0.47389070 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.93 | 14.12 | 0.00970984 | 39560.1 | |
| SPLIT TN1 HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT TN1 | T N1 APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 9957.592 | 9957.592 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | SPLIT TN1 SUPPLY FAN | Fan:OnOff | 0.451315 | 0.49337530 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | Sensible | 9957.59 | 9957.59 | 1.0000 | 0.49337530 | 0.451315 | 19.91 | 13.13 | 0.00757893 | 39246.4 | 40.00 | 20.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9957.59 | 0.50 | 0.00431558 | 0.50 | 0.02595455 | 5.7509 | 21.10 | 0.00777805 | 21.10 | 0.00777805 | 45.3860 | 1280.12 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT TN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT TN2 | T N2 APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 7445.308 | 5961.125 | 0.449771 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.3608 | 1004.8586 | 1.0932 | SPLIT TN2 SUPPLY FAN | Fan:OnOff | 0.449771 | 0.49168713 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | Sensible | 6636.69 | 6636.69 | 0.8914 | 0.49168713 | 0.449771 | 25.73 | 15.42 | 0.00781131 | 45767.1 | 12.80 | 10.55 | 0.00781131 | 32583.4 | -999.0 | -999.00 | -999.00 | -999.00 | 503.792 | 6132.89 | 35.61 | 0.00562306 | 16.94 | 0.02595455 | 5.7706 | 24.06 | 0.00794532 | 24.00 | 0.00794532 | 38.8623 | 4796.87 | 0.00 | 7444.04 | 5667.57 | 0.47226921 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.93 | 14.12 | 0.00970984 | 39560.1 | |
| SPLIT TN2 HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT TN2 | T N2 APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 9925.530 | 9925.530 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | SPLIT TN2 SUPPLY FAN | Fan:OnOff | 0.449771 | 0.49168713 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | Sensible | 9925.53 | 9925.53 | 1.0000 | 0.49168713 | 0.449771 | 19.91 | 13.12 | 0.00757826 | 39240.6 | 40.00 | 20.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9925.53 | 0.50 | 0.00431558 | 0.50 | 0.02595455 | 5.7706 | 21.10 | 0.00777807 | 21.10 | 0.00777807 | 45.3861 | 1280.26 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT TS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT TS1 | T S1 APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 7485.390 | 5993.217 | 0.452192 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.3961 | 1004.8586 | 1.0932 | SPLIT TS1 SUPPLY FAN | Fan:OnOff | 0.452192 | 0.49433414 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | Sensible | 6675.28 | 6675.28 | 0.8918 | 0.49433414 | 0.452192 | 25.73 | 15.44 | 0.00783028 | 45812.3 | 12.80 | 10.57 | 0.00783028 | 32631.3 | -999.0 | -999.00 | -999.00 | -999.00 | 506.504 | 6168.78 | 35.61 | 0.00562306 | 16.94 | 0.02595455 | 5.7397 | 24.06 | 0.00796468 | 24.00 | 0.00796468 | 38.9561 | 4822.56 | 0.00 | 7484.12 | 5698.08 | 0.47481168 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.93 | 14.12 | 0.00970984 | 39560.1 | |
| SPLIT TS1 HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT TS1 | T S1 APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 9975.965 | 9975.965 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | SPLIT TS1 SUPPLY FAN | Fan:OnOff | 0.452192 | 0.49433414 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | Sensible | 9975.97 | 9975.97 | 1.0000 | 0.49433414 | 0.452192 | 19.92 | 12.97 | 0.00741089 | 38821.9 | 40.00 | 20.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9975.97 | 0.50 | 0.00431558 | 0.50 | 0.02595455 | 5.7397 | 21.10 | 0.00759937 | 21.10 | 0.00759937 | 44.3569 | 1438.40 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT TS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT TS2 | T S2 APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 7459.949 | 5972.847 | 0.450655 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.3951 | 1004.8586 | 1.0932 | SPLIT TS2 SUPPLY FAN | Fan:OnOff | 0.450655 | 0.49265398 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | Sensible | 6652.64 | 6652.64 | 0.8918 | 0.49265398 | 0.450655 | 25.73 | 15.44 | 0.00782974 | 45813.0 | 12.80 | 10.57 | 0.00782974 | 32630.0 | -999.0 | -999.00 | -999.00 | -999.00 | 504.783 | 6147.86 | 35.61 | 0.00562306 | 16.94 | 0.02595455 | 5.7593 | 24.06 | 0.00796459 | 24.00 | 0.00796459 | 38.9557 | 4806.43 | 0.00 | 7458.68 | 5678.71 | 0.47319787 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.93 | 14.12 | 0.00970984 | 39560.1 | |
| SPLIT TS2 HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT TS2 | T S2 APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 9944.055 | 9944.055 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | SPLIT TS2 SUPPLY FAN | Fan:OnOff | 0.450655 | 0.49265398 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | Sensible | 9944.05 | 9944.05 | 1.0000 | 0.49265398 | 0.450655 | 19.91 | 12.97 | 0.00741028 | 38816.3 | 40.00 | 20.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9944.05 | 0.50 | 0.00431558 | 0.50 | 0.02595455 | 5.7593 | 21.10 | 0.00759941 | 21.10 | 0.00759941 | 44.3571 | 1438.53 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 09:17:08
Economizer| High Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
| None |
| Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
| None |
| Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
| G SW APARTMENT | 1539.67 | 3130.83 | 81.67 |
| G NW APARTMENT | 2219.50 | 5031.17 | 254.67 |
| OFFICE | 977.17 | 287.17 | 32.33 |
| G NE APARTMENT | 2196.50 | 4994.67 | 226.50 |
| G N1 APARTMENT | 1944.33 | 5323.67 | 118.17 |
| G N2 APARTMENT | 1944.67 | 5324.50 | 117.00 |
| G S1 APARTMENT | 1459.50 | 3189.50 | 78.67 |
| G S2 APARTMENT | 1539.50 | 2868.67 | 56.17 |
| M SW APARTMENT | 1397.83 | 3009.00 | 121.50 |
| M NW APARTMENT | 2035.17 | 5004.33 | 293.00 |
| M SE APARTMENT | 1399.67 | 3028.50 | 122.33 |
| M NE APARTMENT | 2019.67 | 4896.00 | 265.17 |
| M N1 APARTMENT | 1753.50 | 5369.33 | 171.17 |
| M N2 APARTMENT | 1756.50 | 5356.17 | 170.67 |
| M S1 APARTMENT | 1302.17 | 3038.50 | 102.50 |
| M S2 APARTMENT | 1303.00 | 3039.33 | 102.17 |
| T SW APARTMENT | 2083.67 | 3476.67 | 674.83 |
| T NW APARTMENT | 3281.50 | 5071.50 | 1198.50 |
| T SE APARTMENT | 2009.67 | 3485.83 | 675.17 |
| T NE APARTMENT | 3212.67 | 4983.67 | 1124.33 |
| T N1 APARTMENT | 2742.83 | 5213.67 | 952.67 |
| T N2 APARTMENT | 2744.17 | 5208.00 | 953.33 |
| T S1 APARTMENT | 1660.83 | 3492.50 | 412.33 |
| T S2 APARTMENT | 1660.83 | 3491.33 | 412.33 |
| T CORRIDOR | 7429.00 | 7917.67 | 6732.33 |
| G CORRIDOR | 5322.83 | 5274.83 | 2627.83 |
| M CORRIDOR | 8725.00 | 8579.50 | 8559.17 |
| Facility | 8744.17 | 8760.00 | 8594.67 |
| During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
| G SW APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| G NW APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| OFFICE | 0.00 | 0.00 | 0.00 | 0.00 |
| G NE APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| G N1 APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| G N2 APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| G S1 APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| G S2 APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| M SW APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| M NW APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| M SE APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| M NE APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| M N1 APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| M N2 APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| M S1 APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| M S2 APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| T SW APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| T NW APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| T SE APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| T NE APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| T N1 APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| T N2 APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| T S1 APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| T S2 APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| T CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
| G CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
| M CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
| Facility | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 09:17:08
Average Outdoor Air During Occupied Hours| Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
| G SW APARTMENT | 2.41 | 2.50 | 268.97 | 0.355 | 0.138 | 0.000 | 0.049 |
| G NW APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.142 | 0.000 | 0.060 |
| OFFICE | 4.75 | 4.75 | 268.97 | 0.520 | 0.148 | 0.000 | 0.000 |
| G NE APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.142 | 0.000 | 0.060 |
| G N1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.086 | 0.000 | 0.060 |
| G N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.086 | 0.000 | 0.060 |
| G S1 APARTMENT | 2.41 | 2.50 | 268.97 | 0.355 | 0.083 | 0.000 | 0.050 |
| G S2 APARTMENT | 2.41 | 2.50 | 268.97 | 0.355 | 0.083 | 0.000 | 0.050 |
| M SW APARTMENT | 2.41 | 2.50 | 268.97 | 0.355 | 0.198 | 0.000 | 0.057 |
| M NW APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.205 | 0.000 | 0.070 |
| M SE APARTMENT | 2.41 | 2.50 | 268.97 | 0.355 | 0.198 | 0.000 | 0.057 |
| M NE APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.205 | 0.000 | 0.070 |
| M N1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.124 | 0.000 | 0.070 |
| M N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.124 | 0.000 | 0.071 |
| M S1 APARTMENT | 2.41 | 2.50 | 268.97 | 0.355 | 0.119 | 0.000 | 0.057 |
| M S2 APARTMENT | 2.41 | 2.50 | 268.97 | 0.355 | 0.119 | 0.000 | 0.057 |
| T SW APARTMENT | 2.41 | 2.50 | 268.97 | 0.354 | 0.261 | 0.000 | 0.065 |
| T NW APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.270 | 0.000 | 0.078 |
| T SE APARTMENT | 2.41 | 2.50 | 268.97 | 0.354 | 0.261 | 0.000 | 0.065 |
| T NE APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.270 | 0.000 | 0.079 |
| T N1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.163 | 0.000 | 0.078 |
| T N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.163 | 0.000 | 0.078 |
| T S1 APARTMENT | 2.41 | 2.50 | 268.97 | 0.354 | 0.158 | 0.000 | 0.065 |
| T S2 APARTMENT | 2.41 | 2.50 | 268.97 | 0.354 | 0.158 | 0.000 | 0.065 |
| Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
| G SW APARTMENT | 2.41 | 2.50 | 268.97 | 0.346 | 0.000 | 0.000 | 0.000 |
| G NW APARTMENT | 1.71 | 2.50 | 268.97 | 0.346 | 0.000 | 0.000 | 0.000 |
| OFFICE | 4.75 | 4.75 | 268.97 | 0.510 | 0.000 | 0.000 | 0.000 |
| G NE APARTMENT | 1.71 | 2.50 | 268.97 | 0.346 | 0.000 | 0.000 | 0.000 |
| G N1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.346 | 0.000 | 0.000 | 0.000 |
| G N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.346 | 0.000 | 0.000 | 0.000 |
| G S1 APARTMENT | 2.41 | 2.50 | 268.97 | 0.347 | 0.000 | 0.000 | 0.000 |
| G S2 APARTMENT | 2.41 | 2.50 | 268.97 | 0.347 | 0.000 | 0.000 | 0.000 |
| M SW APARTMENT | 2.41 | 2.50 | 268.97 | 0.346 | 0.000 | 0.000 | 0.000 |
| M NW APARTMENT | 1.71 | 2.50 | 268.97 | 0.346 | 0.000 | 0.000 | 0.000 |
| M SE APARTMENT | 2.41 | 2.50 | 268.97 | 0.346 | 0.000 | 0.000 | 0.000 |
| M NE APARTMENT | 1.71 | 2.50 | 268.97 | 0.346 | 0.000 | 0.000 | 0.000 |
| M N1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.346 | 0.000 | 0.000 | 0.000 |
| M N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.346 | 0.000 | 0.000 | 0.000 |
| M S1 APARTMENT | 2.41 | 2.50 | 268.97 | 0.348 | 0.000 | 0.000 | 0.000 |
| M S2 APARTMENT | 2.41 | 2.50 | 268.97 | 0.348 | 0.000 | 0.000 | 0.000 |
| T SW APARTMENT | 2.41 | 2.50 | 268.97 | 0.346 | 0.000 | 0.000 | 0.000 |
| T NW APARTMENT | 1.71 | 2.50 | 268.97 | 0.346 | 0.000 | 0.000 | 0.000 |
| T SE APARTMENT | 2.41 | 2.50 | 268.97 | 0.346 | 0.000 | 0.000 | 0.000 |
| T NE APARTMENT | 1.71 | 2.50 | 268.97 | 0.346 | 0.000 | 0.000 | 0.000 |
| T N1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.346 | 0.000 | 0.000 | 0.000 |
| T N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.346 | 0.000 | 0.000 | 0.000 |
| T S1 APARTMENT | 2.41 | 2.50 | 268.97 | 0.346 | 0.000 | 0.000 | 0.000 |
| T S2 APARTMENT | 2.41 | 2.50 | 268.97 | 0.346 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 09:17:08
Mechanical Ventilation Parameters by Zone| AirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
| G SW APARTMENT | SPLIT GSW | 2.41 | 2.50 | 268.97 | 88.25 | 0.0260 | 0.026 |
| G NW APARTMENT | SPLIT GNW | 1.71 | 2.50 | 268.97 | 88.25 | 0.0260 | 0.026 |
| OFFICE | SPLIT OFFICE | 4.75 | 4.75 | 268.97 | 88.25 | 0.0381 | 0.038 |
| G NE APARTMENT | SPLIT GNE | 1.71 | 2.50 | 268.97 | 88.25 | 0.0260 | 0.026 |
| G N1 APARTMENT | SPLIT GN1 | 1.71 | 2.50 | 268.97 | 88.25 | 0.0260 | 0.026 |
| G N2 APARTMENT | SPLIT GN2 | 1.71 | 2.50 | 268.97 | 88.25 | 0.0260 | 0.026 |
| G S1 APARTMENT | SPLIT GS1 | 2.41 | 2.50 | 268.97 | 88.25 | 0.0260 | 0.026 |
| G S2 APARTMENT | SPLIT GS2 | 2.41 | 2.50 | 268.97 | 88.25 | 0.0260 | 0.026 |
| M SW APARTMENT | SPLIT MSW | 2.41 | 2.50 | 268.97 | 88.25 | 0.0519 | 0.052 |
| M NW APARTMENT | SPLIT MNW | 1.71 | 2.50 | 268.97 | 88.25 | 0.0519 | 0.052 |
| M SE APARTMENT | SPLIT MSE | 2.41 | 2.50 | 268.97 | 88.25 | 0.0519 | 0.052 |
| M NE APARTMENT | SPLIT MNE | 1.71 | 2.50 | 268.97 | 88.25 | 0.0519 | 0.052 |
| M N1 APARTMENT | SPLIT MN1 | 1.71 | 2.50 | 268.97 | 88.25 | 0.0519 | 0.052 |
| M N2 APARTMENT | SPLIT MN2 | 1.71 | 2.50 | 268.97 | 88.25 | 0.0519 | 0.052 |
| M S1 APARTMENT | SPLIT MS1 | 2.41 | 2.50 | 268.97 | 88.25 | 0.0519 | 0.052 |
| M S2 APARTMENT | SPLIT MS2 | 2.41 | 2.50 | 268.97 | 88.25 | 0.0519 | 0.052 |
| T SW APARTMENT | SPLIT TSW | 2.41 | 2.50 | 268.97 | 88.25 | 0.0260 | 0.026 |
| T NW APARTMENT | SPLIT TNW | 1.71 | 2.50 | 268.97 | 88.25 | 0.0260 | 0.026 |
| T SE APARTMENT | SPLIT TSE | 2.41 | 2.50 | 268.97 | 88.25 | 0.0260 | 0.026 |
| T NE APARTMENT | SPLIT TNE | 1.71 | 2.50 | 268.97 | 88.25 | 0.0260 | 0.026 |
| T N1 APARTMENT | SPLIT TN1 | 1.71 | 2.50 | 268.97 | 88.25 | 0.0260 | 0.026 |
| T N2 APARTMENT | SPLIT TN2 | 1.71 | 2.50 | 268.97 | 88.25 | 0.0260 | 0.026 |
| T S1 APARTMENT | SPLIT TS1 | 2.41 | 2.50 | 268.97 | 88.25 | 0.0260 | 0.026 |
| T S2 APARTMENT | SPLIT TS2 | 2.41 | 2.50 | 268.97 | 88.25 | 0.0260 | 0.026 |
| Total Facility | 68.20 | 82.25 | 8607.06 | 2823.98 | 0.8427 | 1.258 |
| Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
| G SW APARTMENT | 818502.78 | 149094.93 | 967597.71 | 329069.00 | 1296666.71 | 818502.78 | 0.00 | 7080.17 | 1679.83 | 2615.00 |
| G NW APARTMENT | 818502.78 | 138355.09 | 956857.87 | 329069.00 | 1285926.87 | 818502.78 | 0.00 | 7080.17 | 1679.83 | 0.00 |
| OFFICE | 1201711.97 | 0.00 | 1201711.97 | 329069.00 | 1530780.97 | 1201711.97 | 0.00 | 8760.00 | 0.00 | 7010.00 |
| G NE APARTMENT | 818502.78 | 139121.14 | 957623.91 | 329069.00 | 1286692.91 | 818502.78 | 0.00 | 7080.17 | 1679.83 | 0.00 |
| G N1 APARTMENT | 818502.78 | 139765.87 | 958268.64 | 198486.06 | 1156754.71 | 818502.78 | 0.00 | 7080.17 | 1679.83 | 0.00 |
| G N2 APARTMENT | 818502.78 | 139820.67 | 958323.45 | 198486.06 | 1156809.51 | 818502.78 | 0.00 | 7080.17 | 1679.83 | 0.00 |
| G S1 APARTMENT | 818502.78 | 150173.91 | 968676.69 | 198486.06 | 1167162.75 | 818502.78 | 0.00 | 7080.17 | 1679.83 | 2615.00 |
| G S2 APARTMENT | 818502.78 | 150335.88 | 968838.66 | 198486.06 | 1167324.72 | 818502.78 | 0.00 | 7080.17 | 1679.83 | 2615.00 |
| M SW APARTMENT | 1637005.55 | 173313.75 | 1810319.30 | 472896.48 | 2283215.78 | 1637005.55 | 0.00 | 7079.67 | 1680.33 | 2615.00 |
| M NW APARTMENT | 1637005.55 | 161247.74 | 1798253.29 | 472896.48 | 2271149.77 | 1637005.55 | 0.00 | 7079.67 | 1680.33 | 0.00 |
| M SE APARTMENT | 1637005.55 | 173537.53 | 1810543.09 | 472896.48 | 2283439.56 | 1637005.55 | 0.00 | 7079.67 | 1680.33 | 2615.00 |
| M NE APARTMENT | 1637005.55 | 162229.58 | 1799235.13 | 472896.48 | 2272131.61 | 1637005.55 | 0.00 | 7079.67 | 1680.33 | 0.00 |
| M N1 APARTMENT | 1637005.55 | 163007.46 | 1800013.01 | 285239.15 | 2085252.16 | 1637005.55 | 0.00 | 7079.67 | 1680.33 | 0.00 |
| M N2 APARTMENT | 1637005.55 | 163072.21 | 1800077.77 | 285239.15 | 2085316.92 | 1637005.55 | 0.00 | 7079.67 | 1680.33 | 0.00 |
| M S1 APARTMENT | 1637005.55 | 173757.16 | 1810762.72 | 285239.15 | 2096001.87 | 1637005.55 | 0.00 | 7079.67 | 1680.33 | 2615.00 |
| M S2 APARTMENT | 1637005.55 | 173761.60 | 1810767.15 | 285239.15 | 2096006.30 | 1637005.55 | 0.00 | 7079.67 | 1680.33 | 2615.00 |
| T SW APARTMENT | 818502.78 | 197584.57 | 1016087.35 | 625542.18 | 1641629.53 | 818502.78 | 0.00 | 7080.00 | 1680.00 | 2615.00 |
| T NW APARTMENT | 818502.78 | 180377.38 | 998880.15 | 625542.18 | 1624422.33 | 818502.78 | 0.00 | 7080.00 | 1680.00 | 0.00 |
| T SE APARTMENT | 818502.78 | 198762.94 | 1017265.72 | 625542.18 | 1642807.90 | 818502.78 | 0.00 | 7080.00 | 1680.00 | 2615.00 |
| T NE APARTMENT | 818502.78 | 182167.97 | 1000670.75 | 625542.18 | 1626212.93 | 818502.78 | 0.00 | 7080.00 | 1680.00 | 0.00 |
| T N1 APARTMENT | 818502.78 | 180827.69 | 999330.47 | 377311.16 | 1376641.63 | 818502.78 | 0.00 | 7080.00 | 1680.00 | 0.00 |
| T N2 APARTMENT | 818502.78 | 180968.39 | 999471.17 | 377311.16 | 1376782.33 | 818502.78 | 0.00 | 7080.00 | 1680.00 | 0.00 |
| T S1 APARTMENT | 818502.78 | 198810.84 | 1017313.62 | 377311.16 | 1394624.78 | 818502.78 | 0.00 | 7080.00 | 1680.00 | 2615.00 |
| T S2 APARTMENT | 818502.78 | 198854.86 | 1017357.64 | 377311.16 | 1394668.80 | 818502.78 | 0.00 | 7080.00 | 1680.00 | 2615.00 |
| Total Facility | 39671342.50 | 5212876.19 | 44884218.70 | 12186718.64 | 57070937.33 | 39671342.50 | 0.00 | 8760.00 | 1680.83 | 8760.00 |
| Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
| G SW APARTMENT | 0.0260 | 0.0036 | 0.0296 | 0.0101 | 0.0396 | 0.0260 | 0.00 | 5249.67 | 895.33 |
| G NW APARTMENT | 0.0260 | 0.0044 | 0.0303 | 0.0104 | 0.0408 | 0.0260 | 0.00 | 7080.17 | 1679.83 |
| OFFICE | 0.0381 | 0.0000 | 0.0381 | 0.0109 | 0.0490 | 0.0381 | 0.00 | 1750.00 | 0.00 |
| G NE APARTMENT | 0.0260 | 0.0044 | 0.0304 | 0.0104 | 0.0408 | 0.0260 | 0.00 | 7080.17 | 1679.83 |
| G N1 APARTMENT | 0.0260 | 0.0044 | 0.0304 | 0.0063 | 0.0367 | 0.0260 | 0.00 | 7080.17 | 1679.83 |
| G N2 APARTMENT | 0.0260 | 0.0044 | 0.0304 | 0.0063 | 0.0367 | 0.0260 | 0.00 | 7080.17 | 1679.83 |
| G S1 APARTMENT | 0.0260 | 0.0036 | 0.0296 | 0.0061 | 0.0357 | 0.0260 | 0.00 | 5249.67 | 895.33 |
| G S2 APARTMENT | 0.0260 | 0.0036 | 0.0296 | 0.0061 | 0.0357 | 0.0260 | 0.00 | 5249.67 | 895.33 |
| M SW APARTMENT | 0.0519 | 0.0042 | 0.0561 | 0.0145 | 0.0705 | 0.0519 | 0.00 | 5249.17 | 895.83 |
| M NW APARTMENT | 0.0519 | 0.0051 | 0.0570 | 0.0150 | 0.0720 | 0.0519 | 0.00 | 7079.67 | 1680.33 |
| M SE APARTMENT | 0.0519 | 0.0042 | 0.0561 | 0.0145 | 0.0705 | 0.0519 | 0.00 | 5249.17 | 895.83 |
| M NE APARTMENT | 0.0519 | 0.0051 | 0.0571 | 0.0150 | 0.0720 | 0.0519 | 0.00 | 7079.67 | 1680.33 |
| M N1 APARTMENT | 0.0519 | 0.0052 | 0.0571 | 0.0090 | 0.0661 | 0.0519 | 0.00 | 7079.67 | 1680.33 |
| M N2 APARTMENT | 0.0519 | 0.0052 | 0.0571 | 0.0090 | 0.0661 | 0.0519 | 0.00 | 7079.67 | 1680.33 |
| M S1 APARTMENT | 0.0519 | 0.0042 | 0.0561 | 0.0087 | 0.0648 | 0.0519 | 0.00 | 5249.17 | 895.83 |
| M S2 APARTMENT | 0.0519 | 0.0042 | 0.0561 | 0.0087 | 0.0648 | 0.0519 | 0.00 | 5249.17 | 895.83 |
| T SW APARTMENT | 0.0260 | 0.0048 | 0.0307 | 0.0191 | 0.0498 | 0.0260 | 0.00 | 5249.33 | 895.67 |
| T NW APARTMENT | 0.0260 | 0.0057 | 0.0317 | 0.0198 | 0.0515 | 0.0260 | 0.00 | 7080.00 | 1680.00 |
| T SE APARTMENT | 0.0260 | 0.0048 | 0.0307 | 0.0191 | 0.0499 | 0.0260 | 0.00 | 5249.33 | 895.67 |
| T NE APARTMENT | 0.0260 | 0.0058 | 0.0317 | 0.0198 | 0.0516 | 0.0260 | 0.00 | 7080.00 | 1680.00 |
| T N1 APARTMENT | 0.0260 | 0.0057 | 0.0317 | 0.0120 | 0.0437 | 0.0260 | 0.00 | 7080.00 | 1680.00 |
| T N2 APARTMENT | 0.0260 | 0.0057 | 0.0317 | 0.0120 | 0.0437 | 0.0260 | 0.00 | 7080.00 | 1680.00 |
| T S1 APARTMENT | 0.0260 | 0.0048 | 0.0307 | 0.0115 | 0.0423 | 0.0260 | 0.00 | 5249.33 | 895.67 |
| T S2 APARTMENT | 0.0260 | 0.0048 | 0.0307 | 0.0115 | 0.0423 | 0.0260 | 0.00 | 5249.33 | 895.67 |
| Total Facility | 1.2580 | 0.1452 | 1.4031 | 0.3804 | 1.7836 | 1.2580 | 0.00 | 8760.00 | 1680.83 |
| Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
| SPLIT GSW | 0.00 | 149094.93 | 149094.93 | 818502.78 | 7987.33 | 57.67 | 715.00 | 784.50 |
| SPLIT GNW | 0.00 | 138355.09 | 138355.09 | 818502.78 | 8185.22 | 53.18 | 521.60 | 0.00 |
| SPLIT OFFICE | 1436134.25 | 0.00 | 1436134.25 | 1201711.97 | 0.00 | 0.00 | 8760.00 | 7010.00 |
| SPLIT GNE | 0.00 | 139121.14 | 139121.14 | 818502.78 | 8170.23 | 58.93 | 530.83 | 0.00 |
| SPLIT GN1 | 0.00 | 139765.87 | 139765.87 | 818502.78 | 8152.03 | 57.94 | 550.03 | 0.00 |
| SPLIT GN2 | 0.00 | 139820.67 | 139820.67 | 818502.78 | 8151.64 | 57.71 | 550.65 | 0.00 |
| SPLIT GS1 | 0.00 | 150173.91 | 150173.91 | 818502.78 | 7964.33 | 53.42 | 742.25 | 784.50 |
| SPLIT GS2 | 0.00 | 150335.88 | 150335.88 | 818502.78 | 7961.50 | 52.67 | 745.83 | 784.50 |
| SPLIT MSW | 0.00 | 173313.75 | 173313.75 | 1637005.55 | 8722.67 | 4.33 | 33.00 | 784.50 |
| SPLIT MNW | 0.00 | 161247.74 | 161247.74 | 1637005.55 | 8731.50 | 2.50 | 26.00 | 0.00 |
| SPLIT MSE | 0.00 | 173537.53 | 173537.53 | 1637005.55 | 8722.50 | 4.17 | 33.33 | 784.50 |
| SPLIT MNE | 0.00 | 162229.58 | 162229.58 | 1637005.55 | 8731.50 | 2.67 | 25.83 | 0.00 |
| SPLIT MN1 | 0.00 | 163007.46 | 163007.46 | 1637005.55 | 8731.21 | 2.46 | 26.33 | 0.00 |
| SPLIT MN2 | 0.00 | 163072.21 | 163072.21 | 1637005.55 | 8731.21 | 2.46 | 26.33 | 0.00 |
| SPLIT MS1 | 0.00 | 173757.16 | 173757.16 | 1637005.55 | 8721.33 | 4.67 | 34.00 | 784.50 |
| SPLIT MS2 | 0.00 | 173761.60 | 173761.60 | 1637005.55 | 8721.33 | 4.67 | 34.00 | 784.50 |
| SPLIT TSW | 0.00 | 197584.57 | 197584.57 | 818502.78 | 7506.58 | 37.01 | 1216.40 | 784.33 |
| SPLIT TNW | 0.00 | 180377.38 | 180377.38 | 818502.78 | 7720.08 | 47.36 | 992.56 | 0.00 |
| SPLIT TSE | 0.00 | 198762.94 | 198762.94 | 818502.78 | 7488.67 | 36.29 | 1235.05 | 784.33 |
| SPLIT TNE | 0.00 | 182167.97 | 182167.97 | 818502.78 | 7688.09 | 49.45 | 1022.46 | 0.00 |
| SPLIT TN1 | 0.00 | 180827.69 | 180827.69 | 818502.78 | 7717.36 | 46.14 | 996.50 | 0.00 |
| SPLIT TN2 | 0.00 | 180968.39 | 180968.39 | 818502.78 | 7716.15 | 45.68 | 998.17 | 0.00 |
| SPLIT TS1 | 0.00 | 198810.84 | 198810.84 | 818502.78 | 7493.42 | 35.17 | 1231.42 | 784.33 |
| SPLIT TS2 | 0.00 | 198854.86 | 198854.86 | 818502.78 | 7492.92 | 34.75 | 1232.33 | 784.33 |
| Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
| SPLIT GSW | 0.0000 | 0.0036 | 0.0036 | 0.0260 | 5709.17 | 25.42 | 410.42 |
| SPLIT GNW | 0.0000 | 0.0044 | 0.0044 | 0.0260 | 8185.22 | 53.18 | 521.60 |
| SPLIT OFFICE | 0.0455 | 0.0000 | 0.0455 | 0.0381 | 0.00 | 0.00 | 1750.00 |
| SPLIT GNE | 0.0000 | 0.0044 | 0.0044 | 0.0260 | 8170.23 | 58.93 | 530.83 |
| SPLIT GN1 | 0.0000 | 0.0044 | 0.0044 | 0.0260 | 8152.03 | 57.94 | 550.03 |
| SPLIT GN2 | 0.0000 | 0.0044 | 0.0044 | 0.0260 | 8151.64 | 57.71 | 550.65 |
| SPLIT GS1 | 0.0000 | 0.0036 | 0.0036 | 0.0260 | 5703.83 | 22.17 | 419.00 |
| SPLIT GS2 | 0.0000 | 0.0036 | 0.0036 | 0.0260 | 5702.83 | 22.50 | 419.67 |
| SPLIT MSW | 0.0000 | 0.0042 | 0.0042 | 0.0519 | 6131.00 | 1.67 | 12.33 |
| SPLIT MNW | 0.0000 | 0.0051 | 0.0051 | 0.0519 | 8731.50 | 2.50 | 26.00 |
| SPLIT MSE | 0.0000 | 0.0042 | 0.0042 | 0.0519 | 6131.00 | 1.67 | 12.33 |
| SPLIT MNE | 0.0000 | 0.0051 | 0.0051 | 0.0519 | 8731.50 | 2.67 | 25.83 |
| SPLIT MN1 | 0.0000 | 0.0052 | 0.0052 | 0.0519 | 8731.21 | 2.46 | 26.33 |
| SPLIT MN2 | 0.0000 | 0.0052 | 0.0052 | 0.0519 | 8731.21 | 2.46 | 26.33 |
| SPLIT MS1 | 0.0000 | 0.0042 | 0.0042 | 0.0519 | 6130.67 | 2.00 | 12.33 |
| SPLIT MS2 | 0.0000 | 0.0042 | 0.0042 | 0.0519 | 6130.67 | 2.00 | 12.33 |
| SPLIT TSW | 0.0000 | 0.0048 | 0.0048 | 0.0260 | 5447.67 | 17.86 | 679.47 |
| SPLIT TNW | 0.0000 | 0.0057 | 0.0057 | 0.0260 | 7720.08 | 47.36 | 992.56 |
| SPLIT TSE | 0.0000 | 0.0048 | 0.0048 | 0.0260 | 5441.50 | 17.95 | 685.55 |
| SPLIT TNE | 0.0000 | 0.0058 | 0.0058 | 0.0260 | 7688.09 | 49.45 | 1022.46 |
| SPLIT TN1 | 0.0000 | 0.0057 | 0.0057 | 0.0260 | 7717.36 | 46.14 | 996.50 |
| SPLIT TN2 | 0.0000 | 0.0057 | 0.0057 | 0.0260 | 7716.15 | 45.68 | 998.17 |
| SPLIT TS1 | 0.0000 | 0.0048 | 0.0048 | 0.0260 | 5441.92 | 17.25 | 685.83 |
| SPLIT TS2 | 0.0000 | 0.0048 | 0.0048 | 0.0260 | 5441.75 | 17.17 | 686.08 |
| No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
| SPLIT GSW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT GNW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT OFFICE | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT GNE | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT GN1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT GN2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT GS1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT GS2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT MSW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT MNW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT MSE | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT MNE | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT MN1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT MN2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT MS1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT MS2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT TSW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT TNW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT TSE | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT TNE | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT TN1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT TN2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT TS1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT TS2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
| SPLIT GSW | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT GNW | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT OFFICE | 0.0455 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT GNE | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT GN1 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT GN2 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT GS1 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT GS2 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT MSW | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT MNW | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT MSE | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT MNE | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT MN1 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT MN2 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT MS1 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT MS2 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT TSW | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT TNW | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT TSE | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT TNE | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT TN1 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT TN2 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT TS1 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT TS2 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 09:17:08
Surfaces by Class| Total | Outdoors | |
| Wall | 126 | 42 |
| Floor | 27 | 9 |
| Roof | 27 | 9 |
| Internal Mass | 24 | 0 |
| Building Detached Shading | 0 | 0 |
| Fixed Detached Shading | 0 | 0 |
| Window | 39 | 39 |
| Door | 0 | 0 |
| Glass Door | 0 | 0 |
| Shading | 0 | 0 |
| Overhang | 0 | 0 |
| Fin | 0 | 0 |
| Tubular Daylighting Device Dome | 0 | 0 |
| Tubular Daylighting Device Diffuser | 0 | 0 |
| Count | |
| HVAC Air Loops | 24 |
| Conditioned Zones | 24 |
| Unconditioned Zones | 3 |
| Supply Plenums | 0 |
| Return Plenums | 0 |
| Count | |
| IDF Objects | 1536 |
| Defaulted Fields | 1816 |
| Fields with Defaults | 5921 |
| Autosized Fields | 617 |
| Autosizable Fields | 759 |
| Autocalculated Fields | 331 |
| Autocalculatable Fields | 508 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 09:17:08
Annual and Peak Values - Electricity| Electricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
| Electricity:Facility | 1386.19 | 17001.19 | 06-MAR-03:20 | 97169.37 | 07-SEP-17:10 |
| Electricity:Building | 557.89 | 10119.94 | 01-JAN-03:10 | 27841.36 | 01-JAN-18:10 |
| Electricity:Zone:G SW APARTMENT | 13.67 | 232.36 | 01-JAN-03:10 | 705.80 | 01-JAN-18:10 |
| Electricity:SpaceType:GENERAL | 557.89 | 10119.94 | 01-JAN-03:10 | 27841.36 | 01-JAN-18:10 |
| InteriorLights:Electricity | 99.23 | 1868.27 | 01-JAN-00:10 | 5904.43 | 01-JAN-19:10 |
| InteriorLights:Electricity:Zone:G SW APARTMENT | 1.45 | 8.68 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 |
| InteriorLights:Electricity:SpaceType:GENERAL | 99.23 | 1868.27 | 01-JAN-00:10 | 5904.43 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity | 94.96 | 1842.77 | 01-JAN-00:10 | 5496.56 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:G SW APARTMENT | 1.32 | 7.86 | 01-JAN-00:10 | 125.72 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 94.96 | 1842.77 | 01-JAN-00:10 | 5496.56 | 01-JAN-19:10 |
| Electricity:Zone:G NW APARTMENT | 13.67 | 232.36 | 01-JAN-03:10 | 705.80 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:G NW APARTMENT | 1.45 | 8.68 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:G NW APARTMENT | 1.32 | 7.86 | 01-JAN-00:10 | 125.72 | 01-JAN-19:10 |
| Electricity:Zone:OFFICE | 16.86 | 310.83 | 01-JAN-00:10 | 1171.54 | 03-JAN-08:10 |
| InteriorLights:Electricity:Zone:OFFICE | 7.40 | 116.58 | 01-JAN-00:10 | 582.92 | 03-JAN-08:10 |
| LightsWired:InteriorLights:Electricity:Zone:OFFICE | 7.40 | 116.58 | 01-JAN-00:10 | 582.92 | 03-JAN-08:10 |
| Electricity:Zone:G NE APARTMENT | 13.67 | 232.36 | 01-JAN-03:10 | 705.80 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:G NE APARTMENT | 1.45 | 8.68 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:G NE APARTMENT | 1.32 | 7.86 | 01-JAN-00:10 | 125.72 | 01-JAN-19:10 |
| Electricity:Zone:G N1 APARTMENT | 13.67 | 232.36 | 01-JAN-03:10 | 705.80 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:G N1 APARTMENT | 1.45 | 8.68 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:G N1 APARTMENT | 1.32 | 7.86 | 01-JAN-00:10 | 125.72 | 01-JAN-19:10 |
| Electricity:Zone:G N2 APARTMENT | 13.67 | 232.36 | 01-JAN-03:10 | 705.80 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:G N2 APARTMENT | 1.45 | 8.68 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:G N2 APARTMENT | 1.32 | 7.86 | 01-JAN-00:10 | 125.72 | 01-JAN-19:10 |
| Electricity:Zone:G S1 APARTMENT | 13.67 | 232.36 | 01-JAN-03:10 | 705.80 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:G S1 APARTMENT | 1.45 | 8.68 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:G S1 APARTMENT | 1.32 | 7.86 | 01-JAN-00:10 | 125.72 | 01-JAN-19:10 |
| Electricity:Zone:G S2 APARTMENT | 13.67 | 232.36 | 01-JAN-03:10 | 705.80 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:G S2 APARTMENT | 1.45 | 8.68 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:G S2 APARTMENT | 1.32 | 7.86 | 01-JAN-00:10 | 125.72 | 01-JAN-19:10 |
| Electricity:Zone:M SW APARTMENT | 27.33 | 464.72 | 01-JAN-03:10 | 1411.61 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:M SW APARTMENT | 2.91 | 17.37 | 01-JAN-00:10 | 277.76 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:M SW APARTMENT | 2.63 | 15.72 | 01-JAN-00:10 | 251.45 | 01-JAN-19:10 |
| Electricity:Zone:M NW APARTMENT | 27.33 | 464.72 | 01-JAN-03:10 | 1411.61 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:M NW APARTMENT | 2.91 | 17.37 | 01-JAN-00:10 | 277.76 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:M NW APARTMENT | 2.63 | 15.72 | 01-JAN-00:10 | 251.45 | 01-JAN-19:10 |
| Electricity:Zone:M SE APARTMENT | 27.33 | 464.72 | 01-JAN-03:10 | 1411.61 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:M SE APARTMENT | 2.91 | 17.37 | 01-JAN-00:10 | 277.76 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:M SE APARTMENT | 2.63 | 15.72 | 01-JAN-00:10 | 251.45 | 01-JAN-19:10 |
| Electricity:Zone:M NE APARTMENT | 27.33 | 464.72 | 01-JAN-03:10 | 1411.61 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:M NE APARTMENT | 2.91 | 17.37 | 01-JAN-00:10 | 277.76 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:M NE APARTMENT | 2.63 | 15.72 | 01-JAN-00:10 | 251.45 | 01-JAN-19:10 |
| Electricity:Zone:M N1 APARTMENT | 27.33 | 464.72 | 01-JAN-03:10 | 1411.61 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:M N1 APARTMENT | 2.91 | 17.37 | 01-JAN-00:10 | 277.76 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:M N1 APARTMENT | 2.63 | 15.72 | 01-JAN-00:10 | 251.45 | 01-JAN-19:10 |
| Electricity:Zone:M N2 APARTMENT | 27.33 | 464.72 | 01-JAN-03:10 | 1411.61 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:M N2 APARTMENT | 2.91 | 17.37 | 01-JAN-00:10 | 277.76 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:M N2 APARTMENT | 2.63 | 15.72 | 01-JAN-00:10 | 251.45 | 01-JAN-19:10 |
| Electricity:Zone:M S1 APARTMENT | 27.33 | 464.72 | 01-JAN-03:10 | 1411.61 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:M S1 APARTMENT | 2.91 | 17.37 | 01-JAN-00:10 | 277.76 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:M S1 APARTMENT | 2.63 | 15.72 | 01-JAN-00:10 | 251.45 | 01-JAN-19:10 |
| Electricity:Zone:M S2 APARTMENT | 27.33 | 464.72 | 01-JAN-03:10 | 1411.61 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:M S2 APARTMENT | 2.91 | 17.37 | 01-JAN-00:10 | 277.76 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:M S2 APARTMENT | 2.63 | 15.72 | 01-JAN-00:10 | 251.45 | 01-JAN-19:10 |
| Electricity:Zone:T SW APARTMENT | 13.67 | 232.36 | 01-JAN-03:10 | 705.80 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:T SW APARTMENT | 1.45 | 8.68 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:T SW APARTMENT | 1.32 | 7.86 | 01-JAN-00:10 | 125.72 | 01-JAN-19:10 |
| Electricity:Zone:T NW APARTMENT | 13.67 | 232.36 | 01-JAN-03:10 | 705.80 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:T NW APARTMENT | 1.45 | 8.68 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:T NW APARTMENT | 1.32 | 7.86 | 01-JAN-00:10 | 125.72 | 01-JAN-19:10 |
| Electricity:Zone:T SE APARTMENT | 13.67 | 232.36 | 01-JAN-03:10 | 705.80 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:T SE APARTMENT | 1.45 | 8.68 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:T SE APARTMENT | 1.32 | 7.86 | 01-JAN-00:10 | 125.72 | 01-JAN-19:10 |
| Electricity:Zone:T NE APARTMENT | 13.67 | 232.36 | 01-JAN-03:10 | 705.80 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:T NE APARTMENT | 1.45 | 8.68 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:T NE APARTMENT | 1.32 | 7.86 | 01-JAN-00:10 | 125.72 | 01-JAN-19:10 |
| Electricity:Zone:T N1 APARTMENT | 13.67 | 232.36 | 01-JAN-03:10 | 705.80 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:T N1 APARTMENT | 1.45 | 8.68 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:T N1 APARTMENT | 1.32 | 7.86 | 01-JAN-00:10 | 125.72 | 01-JAN-19:10 |
| Electricity:Zone:T N2 APARTMENT | 13.67 | 232.36 | 01-JAN-03:10 | 705.80 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:T N2 APARTMENT | 1.45 | 8.68 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:T N2 APARTMENT | 1.32 | 7.86 | 01-JAN-00:10 | 125.72 | 01-JAN-19:10 |
| Electricity:Zone:T S1 APARTMENT | 13.67 | 232.36 | 01-JAN-03:10 | 705.80 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:T S1 APARTMENT | 1.45 | 8.68 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:T S1 APARTMENT | 1.32 | 7.86 | 01-JAN-00:10 | 125.72 | 01-JAN-19:10 |
| Electricity:Zone:T S2 APARTMENT | 13.67 | 232.36 | 01-JAN-03:10 | 705.80 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:T S2 APARTMENT | 1.45 | 8.68 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:T S2 APARTMENT | 1.32 | 7.86 | 01-JAN-00:10 | 125.72 | 01-JAN-19:10 |
| Electricity:Zone:G CORRIDOR | 82.28 | 1494.09 | 01-JAN-00:10 | 4538.70 | 01-JAN-07:10 |
| InteriorLights:Electricity:Zone:G CORRIDOR | 11.69 | 370.63 | 01-JAN-00:10 | 370.63 | 01-JAN-00:10 |
| LightsWired:InteriorLights:Electricity:Zone:G CORRIDOR | 11.69 | 370.63 | 01-JAN-00:10 | 370.63 | 01-JAN-00:10 |
| Electricity:Zone:M CORRIDOR | 23.38 | 741.26 | 01-JAN-00:10 | 741.26 | 01-JAN-00:10 |
| InteriorLights:Electricity:Zone:M CORRIDOR | 23.38 | 741.26 | 01-JAN-00:10 | 741.26 | 01-JAN-00:10 |
| LightsWired:InteriorLights:Electricity:Zone:M CORRIDOR | 23.38 | 741.26 | 01-JAN-00:10 | 741.26 | 01-JAN-00:10 |
| Electricity:Zone:T CORRIDOR | 11.69 | 370.63 | 01-JAN-00:10 | 370.63 | 01-JAN-00:10 |
| InteriorLights:Electricity:Zone:T CORRIDOR | 11.69 | 370.63 | 01-JAN-00:10 | 370.63 | 01-JAN-00:10 |
| LightsWired:InteriorLights:Electricity:Zone:T CORRIDOR | 11.69 | 370.63 | 01-JAN-00:10 | 370.63 | 01-JAN-00:10 |
| LightsPlugIn:InteriorLights:Electricity | 4.27 | 25.50 | 01-JAN-00:10 | 407.87 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:G SW APARTMENT | 0.14 | 0.82 | 01-JAN-00:10 | 13.16 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:SpaceType:GENERAL | 4.27 | 25.50 | 01-JAN-00:10 | 407.87 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:G NW APARTMENT | 0.14 | 0.82 | 01-JAN-00:10 | 13.16 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:G NE APARTMENT | 0.14 | 0.82 | 01-JAN-00:10 | 13.16 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:G N1 APARTMENT | 0.14 | 0.82 | 01-JAN-00:10 | 13.16 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:G N2 APARTMENT | 0.14 | 0.82 | 01-JAN-00:10 | 13.16 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:G S1 APARTMENT | 0.14 | 0.82 | 01-JAN-00:10 | 13.16 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:G S2 APARTMENT | 0.14 | 0.82 | 01-JAN-00:10 | 13.16 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:M SW APARTMENT | 0.28 | 1.65 | 01-JAN-00:10 | 26.31 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:M NW APARTMENT | 0.28 | 1.65 | 01-JAN-00:10 | 26.31 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:M SE APARTMENT | 0.28 | 1.65 | 01-JAN-00:10 | 26.31 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:M NE APARTMENT | 0.28 | 1.65 | 01-JAN-00:10 | 26.31 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:M N1 APARTMENT | 0.28 | 1.65 | 01-JAN-00:10 | 26.31 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:M N2 APARTMENT | 0.28 | 1.65 | 01-JAN-00:10 | 26.31 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:M S1 APARTMENT | 0.28 | 1.65 | 01-JAN-00:10 | 26.31 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:M S2 APARTMENT | 0.28 | 1.65 | 01-JAN-00:10 | 26.31 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:T SW APARTMENT | 0.14 | 0.82 | 01-JAN-00:10 | 13.16 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:T NW APARTMENT | 0.14 | 0.82 | 01-JAN-00:10 | 13.16 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:T SE APARTMENT | 0.14 | 0.82 | 01-JAN-00:10 | 13.16 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:T NE APARTMENT | 0.14 | 0.82 | 01-JAN-00:10 | 13.16 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:T N1 APARTMENT | 0.14 | 0.82 | 01-JAN-00:10 | 13.16 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:T N2 APARTMENT | 0.14 | 0.82 | 01-JAN-00:10 | 13.16 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:T S1 APARTMENT | 0.14 | 0.82 | 01-JAN-00:10 | 13.16 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:T S2 APARTMENT | 0.14 | 0.82 | 01-JAN-00:10 | 13.16 | 01-JAN-19:10 |
| InteriorEquipment:Electricity | 458.66 | 8251.68 | 01-JAN-03:10 | 22709.69 | 03-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:G SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:SpaceType:GENERAL | 458.66 | 8251.68 | 01-JAN-03:10 | 22709.69 | 03-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity | 388.06 | 7128.22 | 01-JAN-03:10 | 18541.61 | 03-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:G SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 388.06 | 7128.22 | 01-JAN-03:10 | 18541.61 | 03-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:G NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:G NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:OFFICE | 9.47 | 194.25 | 01-JAN-00:10 | 588.62 | 03-JAN-08:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:OFFICE | 9.47 | 194.25 | 01-JAN-00:10 | 588.62 | 03-JAN-08:10 |
| InteriorEquipment:Electricity:Zone:G NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:G NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:G N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:G N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:G N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:G N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:G S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:G S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:G S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:G S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:M SW APARTMENT | 24.43 | 447.35 | 01-JAN-03:10 | 1177.25 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:M SW APARTMENT | 24.43 | 447.35 | 01-JAN-03:10 | 1177.25 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:M NW APARTMENT | 24.43 | 447.35 | 01-JAN-03:10 | 1177.25 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:M NW APARTMENT | 24.43 | 447.35 | 01-JAN-03:10 | 1177.25 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:M SE APARTMENT | 24.43 | 447.35 | 01-JAN-03:10 | 1177.25 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:M SE APARTMENT | 24.43 | 447.35 | 01-JAN-03:10 | 1177.25 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:M NE APARTMENT | 24.43 | 447.35 | 01-JAN-03:10 | 1177.25 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:M NE APARTMENT | 24.43 | 447.35 | 01-JAN-03:10 | 1177.25 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:M N1 APARTMENT | 24.43 | 447.35 | 01-JAN-03:10 | 1177.25 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:M N1 APARTMENT | 24.43 | 447.35 | 01-JAN-03:10 | 1177.25 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:M N2 APARTMENT | 24.43 | 447.35 | 01-JAN-03:10 | 1177.25 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:M N2 APARTMENT | 24.43 | 447.35 | 01-JAN-03:10 | 1177.25 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:M S1 APARTMENT | 24.43 | 447.35 | 01-JAN-03:10 | 1177.25 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:M S1 APARTMENT | 24.43 | 447.35 | 01-JAN-03:10 | 1177.25 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:M S2 APARTMENT | 24.43 | 447.35 | 01-JAN-03:10 | 1177.25 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:M S2 APARTMENT | 24.43 | 447.35 | 01-JAN-03:10 | 1177.25 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:T SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:T SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:T NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:T NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:T SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:T SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:T NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:T NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:T N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:T N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:T N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:T N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:T S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:T S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:T S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:T S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:G CORRIDOR | 70.59 | 1123.46 | 01-JAN-00:10 | 4168.07 | 01-JAN-07:10 |
| ElevatorLift:InteriorEquipment:Electricity | 65.48 | 961.46 | 01-JAN-00:10 | 4006.07 | 01-JAN-07:10 |
| ElevatorLift:InteriorEquipment:Electricity:Zone:G CORRIDOR | 65.48 | 961.46 | 01-JAN-00:10 | 4006.07 | 01-JAN-07:10 |
| ElevatorLift:InteriorEquipment:Electricity:SpaceType:GENERAL | 65.48 | 961.46 | 01-JAN-00:10 | 4006.07 | 01-JAN-07:10 |
| ElevatorLightsFan:InteriorEquipment:Electricity | 5.11 | 162.00 | 01-JAN-00:10 | 162.00 | 01-JAN-00:10 |
| ElevatorLightsFan:InteriorEquipment:Electricity:Zone:G CORRIDOR | 5.11 | 162.00 | 01-JAN-00:10 | 162.00 | 01-JAN-00:10 |
| ElevatorLightsFan:InteriorEquipment:Electricity:SpaceType:GENERAL | 5.11 | 162.00 | 01-JAN-00:10 | 162.00 | 01-JAN-00:10 |
| Fans:Electricity | 132.58 | 1747.92 | 06-FEB-17:10 | 11397.17 | 16-JUN-17:00 |
| Fans:Electricity:Zone:G SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:G SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:G NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:G NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:G NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:G NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:G N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:G N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:G N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:G N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:G S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:G S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:G S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:G S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:M SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:M SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:M NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:M NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:M SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:M SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:M NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:M NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:M N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:M N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:M N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:M N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:M S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:M S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:M S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:M S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:T SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:T SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:T NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:T NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:T SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:T SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:T NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:T NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:T N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:T N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:T N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:T N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:T S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:T S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:T S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:T S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| ElectricityPurchased:Facility | 1386.19 | 17001.19 | 06-MAR-03:20 | 97169.37 | 07-SEP-17:10 |
| ElectricityPurchased:Plant | 1386.19 | 17001.19 | 06-MAR-03:20 | 97169.37 | 07-SEP-17:10 |
| Cogeneration:ElectricityPurchased | 1386.19 | 17001.19 | 06-MAR-03:20 | 97169.37 | 07-SEP-17:10 |
| General:Cogeneration:ElectricityPurchased | 1386.19 | 17001.19 | 06-MAR-03:20 | 97169.37 | 07-SEP-17:10 |
| ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| ElectricityNet:Facility | 1386.19 | 17001.19 | 06-MAR-03:20 | 97169.37 | 07-SEP-17:10 |
| ElectricityNet:Plant | 1386.19 | 17001.19 | 06-MAR-03:20 | 97169.37 | 07-SEP-17:10 |
| Cogeneration:ElectricityNet | 1386.19 | 17001.19 | 06-MAR-03:20 | 97169.37 | 07-SEP-17:10 |
| General:Cogeneration:ElectricityNet | 1386.19 | 17001.19 | 06-MAR-03:20 | 97169.37 | 07-SEP-17:10 |
| Electricity:HVAC | 399.02 | 1747.92 | 06-FEB-17:10 | 46008.52 | 30-JUN-16:00 |
| HeatRecovery:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:HeatRecovery:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:Fans:Electricity | 132.58 | 1747.92 | 06-FEB-17:10 | 11397.17 | 16-JUN-17:00 |
| Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Cooling:Electricity | 266.43 | 0.00 | 01-JAN-00:10 | 34911.37 | 30-JUN-16:00 |
| General:Cooling:Electricity | 266.43 | 0.00 | 01-JAN-00:10 | 34911.37 | 30-JUN-16:00 |
| ExteriorLights:Electricity | 50.07 | 0.00 | 01-JAN-07:30 | 3183.33 | 01-JAN-00:10 |
| General:ExteriorLights:Electricity | 50.07 | 0.00 | 01-JAN-07:30 | 3183.33 | 01-JAN-00:10 |
| Electricity:Plant | 379.22 | 1950.00 | 01-JAN-00:10 | 37336.19 | 02-JAN-07:20 |
| WaterSystems:Electricity | 379.22 | 1950.00 | 01-JAN-00:10 | 37336.19 | 02-JAN-07:20 |
| Water Heater:WaterSystems:Electricity | 379.22 | 1950.00 | 01-JAN-00:10 | 37336.19 | 02-JAN-07:20 |
| Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
| NaturalGas:Facility | 26.80 | 0.00 | 01-JAN-15:10 | 34097.62 | 07-DEC-06:00 |
| NaturalGas:HVAC | 26.80 | 0.00 | 01-JAN-15:10 | 34097.62 | 07-DEC-06:00 |
| Heating:NaturalGas | 26.80 | 0.00 | 01-JAN-15:10 | 34097.62 | 07-DEC-06:00 |
| General:Heating:NaturalGas | 26.80 | 0.00 | 01-JAN-15:10 | 34097.62 | 07-DEC-06:00 |
| Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
| None |
| Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
| Water:Facility | 1875.32 | 0.00 | 01-JAN-02:10 | 0.00 | 01-JAN-07:10 |
| Water:Plant | 1875.32 | 0.00 | 01-JAN-02:10 | 0.00 | 01-JAN-07:10 |
| WaterSystems:Water | 1875.32 | 0.00 | 01-JAN-02:10 | 0.00 | 01-JAN-07:10 |
| Water Heater:WaterSystems:Water | 1875.32 | 0.00 | 01-JAN-02:10 | 0.00 | 01-JAN-07:10 |
| MainsWater:Facility | 1875.32 | 0.00 | 01-JAN-02:10 | 0.00 | 01-JAN-07:10 |
| MainsWater:Plant | 1875.32 | 0.00 | 01-JAN-02:10 | 0.00 | 01-JAN-07:10 |
| WaterSystems:MainsWater | 1875.32 | 0.00 | 01-JAN-02:10 | 0.00 | 01-JAN-07:10 |
| Water Heater:WaterSystems:MainsWater | 1875.32 | 0.00 | 01-JAN-02:10 | 0.00 | 01-JAN-07:10 |
| Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
| Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
| CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
| Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
| None |
| Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
| None |
| Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
| EnergyTransfer:Facility | 1842.71 | 3557.81 | 01-APR-07:40 | 196809.98 | 30-JUN-16:00 |
| EnergyTransfer:Building | 863.32 | 2890.24 | 15-MAR-08:40 | 85204.04 | 30-JUN-16:00 |
| EnergyTransfer:Zone:G SW APARTMENT | 29.19 | 0.24 | 15-MAR-09:50 | 2839.38 | 22-JUL-17:40 |
| Heating:EnergyTransfer | 12.90 | 0.00 | 03-JAN-10:40 | 14242.60 | 07-DEC-06:00 |
| Heating:EnergyTransfer:Zone:G SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 50.98 | 01-APR-09:20 |
| General:Heating:EnergyTransfer | 12.90 | 0.00 | 03-JAN-10:40 | 14242.60 | 07-DEC-06:00 |
| General:Heating:EnergyTransfer:Zone:G SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 50.98 | 01-APR-09:20 |
| Cooling:EnergyTransfer | 850.42 | 2890.24 | 15-MAR-08:40 | 85204.04 | 30-JUN-16:00 |
| Cooling:EnergyTransfer:Zone:G SW APARTMENT | 29.19 | 0.00 | 15-MAR-09:50 | 2839.38 | 22-JUL-17:40 |
| General:Cooling:EnergyTransfer | 850.42 | 2890.24 | 15-MAR-08:40 | 85204.04 | 30-JUN-16:00 |
| General:Cooling:EnergyTransfer:Zone:G SW APARTMENT | 29.19 | 0.00 | 15-MAR-09:50 | 2839.38 | 22-JUL-17:40 |
| EnergyTransfer:Zone:G NW APARTMENT | 23.79 | 0.06 | 06-JAN-12:30 | 2798.62 | 22-JUL-18:00 |
| Heating:EnergyTransfer:Zone:G NW APARTMENT | 0.06 | 0.00 | 01-JAN-12:40 | 403.37 | 01-JAN-08:00 |
| General:Heating:EnergyTransfer:Zone:G NW APARTMENT | 0.06 | 0.00 | 01-JAN-12:40 | 403.37 | 01-JAN-08:00 |
| Cooling:EnergyTransfer:Zone:G NW APARTMENT | 23.73 | 0.00 | 01-JAN-00:10 | 2798.62 | 22-JUL-18:00 |
| General:Cooling:EnergyTransfer:Zone:G NW APARTMENT | 23.73 | 0.00 | 01-JAN-00:10 | 2798.62 | 22-JUL-18:00 |
| EnergyTransfer:Zone:OFFICE | 24.04 | 0.05 | 09-JAN-20:30 | 4873.29 | 14-AUG-08:10 |
| Heating:EnergyTransfer:Zone:OFFICE | 3.70 | 0.00 | 01-JAN-00:10 | 906.48 | 28-JUN-17:10 |
| General:Heating:EnergyTransfer:Zone:OFFICE | 3.70 | 0.00 | 01-JAN-00:10 | 906.48 | 28-JUN-17:10 |
| Cooling:EnergyTransfer:Zone:OFFICE | 20.34 | 0.00 | 01-JAN-11:50 | 4873.29 | 14-AUG-08:10 |
| General:Cooling:EnergyTransfer:Zone:OFFICE | 20.34 | 0.00 | 01-JAN-11:50 | 4873.29 | 14-AUG-08:10 |
| EnergyTransfer:Zone:G NE APARTMENT | 24.25 | 0.00 | 16-JAN-15:00 | 2441.11 | 22-JUL-18:00 |
| Heating:EnergyTransfer:Zone:G NE APARTMENT | 0.06 | 0.00 | 01-JAN-11:30 | 433.57 | 01-JAN-02:00 |
| General:Heating:EnergyTransfer:Zone:G NE APARTMENT | 0.06 | 0.00 | 01-JAN-11:30 | 433.57 | 01-JAN-02:00 |
| Cooling:EnergyTransfer:Zone:G NE APARTMENT | 24.20 | 0.00 | 01-JAN-00:10 | 2441.11 | 22-JUL-18:00 |
| General:Cooling:EnergyTransfer:Zone:G NE APARTMENT | 24.20 | 0.00 | 01-JAN-00:10 | 2441.11 | 22-JUL-18:00 |
| EnergyTransfer:Zone:G N1 APARTMENT | 20.41 | 0.01 | 10-MAR-11:10 | 1871.18 | 22-JUL-18:00 |
| Heating:EnergyTransfer:Zone:G N1 APARTMENT | 0.01 | 0.00 | 01-JAN-00:10 | 197.32 | 01-APR-12:10 |
| General:Heating:EnergyTransfer:Zone:G N1 APARTMENT | 0.01 | 0.00 | 01-JAN-00:10 | 197.32 | 01-APR-12:10 |
| Cooling:EnergyTransfer:Zone:G N1 APARTMENT | 20.40 | 0.00 | 01-JAN-00:30 | 1871.18 | 22-JUL-18:00 |
| General:Cooling:EnergyTransfer:Zone:G N1 APARTMENT | 20.40 | 0.00 | 01-JAN-00:30 | 1871.18 | 22-JUL-18:00 |
| EnergyTransfer:Zone:G N2 APARTMENT | 20.44 | 0.00 | 13-JAN-15:40 | 1866.45 | 22-JUL-18:00 |
| Heating:EnergyTransfer:Zone:G N2 APARTMENT | 0.01 | 0.00 | 01-JAN-00:10 | 192.46 | 01-APR-12:00 |
| General:Heating:EnergyTransfer:Zone:G N2 APARTMENT | 0.01 | 0.00 | 01-JAN-00:10 | 192.46 | 01-APR-12:00 |
| Cooling:EnergyTransfer:Zone:G N2 APARTMENT | 20.43 | 0.00 | 01-JAN-00:20 | 1866.45 | 22-JUL-18:00 |
| General:Cooling:EnergyTransfer:Zone:G N2 APARTMENT | 20.43 | 0.00 | 01-JAN-00:20 | 1866.45 | 22-JUL-18:00 |
| EnergyTransfer:Zone:G S1 APARTMENT | 26.33 | 1.35 | 01-APR-08:50 | 1989.81 | 08-SEP-16:10 |
| Heating:EnergyTransfer:Zone:G S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 1.35 | 01-APR-08:50 |
| General:Heating:EnergyTransfer:Zone:G S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 1.35 | 01-APR-08:50 |
| Cooling:EnergyTransfer:Zone:G S1 APARTMENT | 26.33 | 0.00 | 01-APR-08:50 | 1989.81 | 08-SEP-16:10 |
| General:Cooling:EnergyTransfer:Zone:G S1 APARTMENT | 26.33 | 0.00 | 01-APR-08:50 | 1989.81 | 08-SEP-16:10 |
| EnergyTransfer:Zone:G S2 APARTMENT | 28.65 | 17.46 | 01-APR-08:40 | 2151.54 | 13-AUG-16:10 |
| Heating:EnergyTransfer:Zone:G S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:Heating:EnergyTransfer:Zone:G S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Cooling:EnergyTransfer:Zone:G S2 APARTMENT | 28.65 | 17.46 | 01-APR-08:40 | 2151.54 | 13-AUG-16:10 |
| General:Cooling:EnergyTransfer:Zone:G S2 APARTMENT | 28.65 | 17.46 | 01-APR-08:40 | 2151.54 | 13-AUG-16:10 |
| EnergyTransfer:Zone:M SW APARTMENT | 64.26 | 3.14 | 07-DEC-05:40 | 6473.30 | 22-JUL-17:40 |
| Heating:EnergyTransfer:Zone:M SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 49.03 | 07-DEC-06:00 |
| General:Heating:EnergyTransfer:Zone:M SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 49.03 | 07-DEC-06:00 |
| Cooling:EnergyTransfer:Zone:M SW APARTMENT | 64.26 | 0.00 | 07-DEC-05:40 | 6473.30 | 22-JUL-17:40 |
| General:Cooling:EnergyTransfer:Zone:M SW APARTMENT | 64.26 | 0.00 | 07-DEC-05:40 | 6473.30 | 22-JUL-17:40 |
| EnergyTransfer:Zone:M NW APARTMENT | 52.00 | 0.09 | 14-JAN-11:50 | 6527.61 | 29-JUN-18:00 |
| Heating:EnergyTransfer:Zone:M NW APARTMENT | 0.15 | 0.00 | 01-JAN-12:20 | 1147.45 | 07-DEC-05:00 |
| General:Heating:EnergyTransfer:Zone:M NW APARTMENT | 0.15 | 0.00 | 01-JAN-12:20 | 1147.45 | 07-DEC-05:00 |
| Cooling:EnergyTransfer:Zone:M NW APARTMENT | 51.84 | 0.00 | 01-JAN-00:10 | 6527.61 | 29-JUN-18:00 |
| General:Cooling:EnergyTransfer:Zone:M NW APARTMENT | 51.84 | 0.00 | 01-JAN-00:10 | 6527.61 | 29-JUN-18:00 |
| EnergyTransfer:Zone:M SE APARTMENT | 65.36 | 10.43 | 07-DEC-05:40 | 5735.50 | 22-JUL-16:10 |
| Heating:EnergyTransfer:Zone:M SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 40.01 | 07-DEC-06:00 |
| General:Heating:EnergyTransfer:Zone:M SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 40.01 | 07-DEC-06:00 |
| Cooling:EnergyTransfer:Zone:M SE APARTMENT | 65.36 | 0.00 | 07-DEC-05:50 | 5735.50 | 22-JUL-16:10 |
| General:Cooling:EnergyTransfer:Zone:M SE APARTMENT | 65.36 | 0.00 | 07-DEC-05:50 | 5735.50 | 22-JUL-16:10 |
| EnergyTransfer:Zone:M NE APARTMENT | 52.95 | 0.01 | 13-JAN-14:10 | 5647.37 | 30-JUN-16:20 |
| Heating:EnergyTransfer:Zone:M NE APARTMENT | 0.15 | 0.00 | 01-JAN-11:10 | 1166.88 | 07-DEC-05:00 |
| General:Heating:EnergyTransfer:Zone:M NE APARTMENT | 0.15 | 0.00 | 01-JAN-11:10 | 1166.88 | 07-DEC-05:00 |
| Cooling:EnergyTransfer:Zone:M NE APARTMENT | 52.80 | 0.00 | 01-JAN-00:10 | 5647.37 | 30-JUN-16:20 |
| General:Cooling:EnergyTransfer:Zone:M NE APARTMENT | 52.80 | 0.00 | 01-JAN-00:10 | 5647.37 | 30-JUN-16:20 |
| EnergyTransfer:Zone:M N1 APARTMENT | 43.22 | 0.26 | 03-JAN-16:10 | 4107.68 | 30-JUN-18:00 |
| Heating:EnergyTransfer:Zone:M N1 APARTMENT | 0.01 | 0.00 | 01-JAN-00:10 | 177.75 | 21-DEC-15:00 |
| General:Heating:EnergyTransfer:Zone:M N1 APARTMENT | 0.01 | 0.00 | 01-JAN-00:10 | 177.75 | 21-DEC-15:00 |
| Cooling:EnergyTransfer:Zone:M N1 APARTMENT | 43.21 | 0.00 | 03-JAN-12:10 | 4107.68 | 30-JUN-18:00 |
| General:Cooling:EnergyTransfer:Zone:M N1 APARTMENT | 43.21 | 0.00 | 03-JAN-12:10 | 4107.68 | 30-JUN-18:00 |
| EnergyTransfer:Zone:M N2 APARTMENT | 43.29 | 0.07 | 03-JAN-16:10 | 4094.57 | 30-JUN-18:00 |
| Heating:EnergyTransfer:Zone:M N2 APARTMENT | 0.01 | 0.00 | 01-JAN-00:10 | 177.17 | 21-DEC-15:00 |
| General:Heating:EnergyTransfer:Zone:M N2 APARTMENT | 0.01 | 0.00 | 01-JAN-00:10 | 177.17 | 21-DEC-15:00 |
| Cooling:EnergyTransfer:Zone:M N2 APARTMENT | 43.28 | 0.00 | 03-JAN-12:10 | 4094.57 | 30-JUN-18:00 |
| General:Cooling:EnergyTransfer:Zone:M N2 APARTMENT | 43.28 | 0.00 | 03-JAN-12:10 | 4094.57 | 30-JUN-18:00 |
| EnergyTransfer:Zone:M S1 APARTMENT | 56.88 | 226.61 | 27-OCT-09:50 | 4231.16 | 10-OCT-15:10 |
| Heating:EnergyTransfer:Zone:M S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:Heating:EnergyTransfer:Zone:M S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Cooling:EnergyTransfer:Zone:M S1 APARTMENT | 56.88 | 226.61 | 27-OCT-09:50 | 4231.16 | 10-OCT-15:10 |
| General:Cooling:EnergyTransfer:Zone:M S1 APARTMENT | 56.88 | 226.61 | 27-OCT-09:50 | 4231.16 | 10-OCT-15:10 |
| EnergyTransfer:Zone:M S2 APARTMENT | 56.96 | 226.78 | 27-OCT-09:50 | 4230.19 | 10-OCT-15:10 |
| Heating:EnergyTransfer:Zone:M S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:Heating:EnergyTransfer:Zone:M S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Cooling:EnergyTransfer:Zone:M S2 APARTMENT | 56.96 | 226.78 | 27-OCT-09:50 | 4230.19 | 10-OCT-15:10 |
| General:Cooling:EnergyTransfer:Zone:M S2 APARTMENT | 56.96 | 226.78 | 27-OCT-09:50 | 4230.19 | 10-OCT-15:10 |
| EnergyTransfer:Zone:T SW APARTMENT | 34.38 | 0.00 | 06-FEB-08:50 | 4484.51 | 30-JUN-16:10 |
| Heating:EnergyTransfer:Zone:T SW APARTMENT | 1.15 | 0.00 | 01-JAN-10:50 | 1610.84 | 07-DEC-06:00 |
| General:Heating:EnergyTransfer:Zone:T SW APARTMENT | 1.15 | 0.00 | 01-JAN-10:50 | 1610.84 | 07-DEC-06:00 |
| Cooling:EnergyTransfer:Zone:T SW APARTMENT | 33.22 | 0.00 | 01-JAN-00:10 | 4484.51 | 30-JUN-16:10 |
| General:Cooling:EnergyTransfer:Zone:T SW APARTMENT | 33.22 | 0.00 | 01-JAN-00:10 | 4484.51 | 30-JUN-16:10 |
| EnergyTransfer:Zone:T NW APARTMENT | 29.48 | 0.03 | 15-MAR-06:40 | 4485.11 | 29-JUN-17:30 |
| Heating:EnergyTransfer:Zone:T NW APARTMENT | 2.21 | 0.00 | 01-JAN-13:50 | 1853.91 | 07-DEC-06:00 |
| General:Heating:EnergyTransfer:Zone:T NW APARTMENT | 2.21 | 0.00 | 01-JAN-13:50 | 1853.91 | 07-DEC-06:00 |
| Cooling:EnergyTransfer:Zone:T NW APARTMENT | 27.27 | 0.00 | 01-JAN-00:10 | 4485.11 | 29-JUN-17:30 |
| General:Cooling:EnergyTransfer:Zone:T NW APARTMENT | 27.27 | 0.00 | 01-JAN-00:10 | 4485.11 | 29-JUN-17:30 |
| EnergyTransfer:Zone:T SE APARTMENT | 34.77 | 0.03 | 11-FEB-11:40 | 3991.09 | 30-JUN-16:10 |
| Heating:EnergyTransfer:Zone:T SE APARTMENT | 1.11 | 0.00 | 01-JAN-09:40 | 1623.82 | 07-DEC-06:00 |
| General:Heating:EnergyTransfer:Zone:T SE APARTMENT | 1.11 | 0.00 | 01-JAN-09:40 | 1623.82 | 07-DEC-06:00 |
| Cooling:EnergyTransfer:Zone:T SE APARTMENT | 33.66 | 0.00 | 01-JAN-00:10 | 3991.09 | 30-JUN-16:10 |
| General:Cooling:EnergyTransfer:Zone:T SE APARTMENT | 33.66 | 0.00 | 01-JAN-00:10 | 3991.09 | 30-JUN-16:10 |
| EnergyTransfer:Zone:T NE APARTMENT | 29.73 | 0.02 | 11-FEB-19:00 | 3920.36 | 30-JUN-16:10 |
| Heating:EnergyTransfer:Zone:T NE APARTMENT | 2.05 | 0.00 | 01-JAN-13:40 | 1873.79 | 07-DEC-06:00 |
| General:Heating:EnergyTransfer:Zone:T NE APARTMENT | 2.05 | 0.00 | 01-JAN-13:40 | 1873.79 | 07-DEC-06:00 |
| Cooling:EnergyTransfer:Zone:T NE APARTMENT | 27.67 | 0.00 | 01-JAN-00:10 | 3920.36 | 30-JUN-16:10 |
| General:Cooling:EnergyTransfer:Zone:T NE APARTMENT | 27.67 | 0.00 | 01-JAN-00:10 | 3920.36 | 30-JUN-16:10 |
| EnergyTransfer:Zone:T N1 APARTMENT | 22.88 | 0.00 | 26-DEC-12:30 | 2964.71 | 30-JUN-16:20 |
| Heating:EnergyTransfer:Zone:T N1 APARTMENT | 0.85 | 0.00 | 01-JAN-13:10 | 1192.43 | 07-DEC-05:00 |
| General:Heating:EnergyTransfer:Zone:T N1 APARTMENT | 0.85 | 0.00 | 01-JAN-13:10 | 1192.43 | 07-DEC-05:00 |
| Cooling:EnergyTransfer:Zone:T N1 APARTMENT | 22.03 | 0.00 | 01-JAN-00:10 | 2964.71 | 30-JUN-16:20 |
| General:Cooling:EnergyTransfer:Zone:T N1 APARTMENT | 22.03 | 0.00 | 01-JAN-00:10 | 2964.71 | 30-JUN-16:20 |
| EnergyTransfer:Zone:T N2 APARTMENT | 22.92 | 0.02 | 28-NOV-13:50 | 2955.25 | 30-JUN-16:20 |
| Heating:EnergyTransfer:Zone:T N2 APARTMENT | 0.85 | 0.00 | 01-JAN-13:00 | 1195.03 | 07-DEC-05:00 |
| General:Heating:EnergyTransfer:Zone:T N2 APARTMENT | 0.85 | 0.00 | 01-JAN-13:00 | 1195.03 | 07-DEC-05:00 |
| Cooling:EnergyTransfer:Zone:T N2 APARTMENT | 22.07 | 0.00 | 01-JAN-00:10 | 2955.25 | 30-JUN-16:20 |
| General:Cooling:EnergyTransfer:Zone:T N2 APARTMENT | 22.07 | 0.00 | 01-JAN-00:10 | 2955.25 | 30-JUN-16:20 |
| EnergyTransfer:Zone:T S1 APARTMENT | 28.55 | 0.06 | 16-JAN-06:40 | 3053.84 | 22-JUL-16:10 |
| Heating:EnergyTransfer:Zone:T S1 APARTMENT | 0.26 | 0.00 | 01-JAN-00:10 | 912.90 | 07-DEC-06:00 |
| General:Heating:EnergyTransfer:Zone:T S1 APARTMENT | 0.26 | 0.00 | 01-JAN-00:10 | 912.90 | 07-DEC-06:00 |
| Cooling:EnergyTransfer:Zone:T S1 APARTMENT | 28.30 | 0.00 | 01-JAN-00:40 | 3053.84 | 22-JUL-16:10 |
| General:Cooling:EnergyTransfer:Zone:T S1 APARTMENT | 28.30 | 0.00 | 01-JAN-00:40 | 3053.84 | 22-JUL-16:10 |
| EnergyTransfer:Zone:T S2 APARTMENT | 28.61 | 0.02 | 13-JAN-04:20 | 3045.91 | 22-JUL-16:10 |
| Heating:EnergyTransfer:Zone:T S2 APARTMENT | 0.26 | 0.00 | 01-JAN-00:10 | 914.52 | 07-DEC-06:00 |
| General:Heating:EnergyTransfer:Zone:T S2 APARTMENT | 0.26 | 0.00 | 01-JAN-00:10 | 914.52 | 07-DEC-06:00 |
| Cooling:EnergyTransfer:Zone:T S2 APARTMENT | 28.35 | 0.00 | 01-JAN-00:40 | 3045.91 | 22-JUL-16:10 |
| General:Cooling:EnergyTransfer:Zone:T S2 APARTMENT | 28.35 | 0.00 | 01-JAN-00:40 | 3045.91 | 22-JUL-16:10 |
| EnergyTransfer:Zone:T CORRIDOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Heating:EnergyTransfer:Zone:T CORRIDOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:Heating:EnergyTransfer:Zone:T CORRIDOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Cooling:EnergyTransfer:Zone:T CORRIDOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:Cooling:EnergyTransfer:Zone:T CORRIDOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| EnergyTransfer:Zone:G CORRIDOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Heating:EnergyTransfer:Zone:G CORRIDOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:Heating:EnergyTransfer:Zone:G CORRIDOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Cooling:EnergyTransfer:Zone:G CORRIDOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:Cooling:EnergyTransfer:Zone:G CORRIDOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| EnergyTransfer:Zone:M CORRIDOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Heating:EnergyTransfer:Zone:M CORRIDOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:Heating:EnergyTransfer:Zone:M CORRIDOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Cooling:EnergyTransfer:Zone:M CORRIDOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:Cooling:EnergyTransfer:Zone:M CORRIDOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| EnergyTransfer:HVAC | 979.39 | 0.00 | 07-JAN-02:50 | 111605.94 | 30-JUN-16:00 |
| HeatRecoveryForHeating:EnergyTransfer | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 15-JUL-06:20 |
| HeatRecoveryForCooling:EnergyTransfer | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 08-JUL-22:10 |
| HeatingCoils:EnergyTransfer | 21.44 | 0.00 | 01-JAN-15:10 | 27278.10 | 07-DEC-06:00 |
| CoolingCoils:EnergyTransfer | 957.95 | 0.00 | 01-JAN-00:10 | 111605.94 | 30-JUN-16:00 |
| PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 09:17:08
Annual Building Sensible Heat Gain Components| HVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
| G SW APARTMENT | 2.751 | -3.922 | 0.044 | -28.060 | 0.000 | 0.000 | 3.638 | 1.454 | 12.213 | 12.641 | 0.000 | 1.194 | 4.508 | 0.000 | -4.194 | 0.000 | -2.266 | -0.000 |
| G NW APARTMENT | 2.754 | -3.616 | 0.536 | -23.337 | 0.000 | 0.000 | 3.754 | 1.454 | 12.213 | 7.601 | 0.000 | 1.195 | 3.595 | 0.000 | -4.123 | 0.000 | -2.026 | -0.000 |
| OFFICE | 0.000 | 0.000 | 3.701 | -20.336 | 0.000 | 0.000 | 1.975 | 7.396 | 9.469 | 11.992 | 0.000 | 0.735 | 0.000 | 0.000 | -4.931 | 0.000 | -1.954 | -8.047 |
| G NE APARTMENT | 2.754 | -3.629 | 0.495 | -23.759 | 0.000 | 0.000 | 3.755 | 1.454 | 12.213 | 7.615 | 0.000 | 1.195 | 3.798 | 0.000 | -3.849 | 0.000 | -2.041 | -0.000 |
| G N1 APARTMENT | 2.754 | -3.725 | 0.121 | -19.536 | 0.000 | 0.000 | 3.728 | 1.454 | 12.213 | 2.943 | 0.000 | 0.721 | 3.423 | 0.000 | -2.566 | 0.000 | -1.529 | -0.000 |
| G N2 APARTMENT | 2.754 | -3.726 | 0.120 | -19.564 | 0.000 | 0.000 | 3.728 | 1.454 | 12.213 | 2.942 | 0.000 | 0.721 | 3.457 | 0.000 | -2.567 | 0.000 | -1.530 | -0.000 |
| G S1 APARTMENT | 2.752 | -4.059 | 0.000 | -25.027 | 0.000 | 0.000 | 3.602 | 1.454 | 12.213 | 8.089 | 0.000 | 0.720 | 4.569 | 0.000 | -2.581 | 0.000 | -1.731 | -0.000 |
| G S2 APARTMENT | 2.751 | -4.073 | 0.000 | -27.330 | 0.000 | 0.000 | 3.598 | 1.454 | 12.213 | 8.063 | 0.000 | 0.720 | 6.946 | 0.000 | -2.604 | 0.000 | -1.738 | -0.000 |
| M SW APARTMENT | 5.503 | -7.986 | 0.053 | -61.826 | 0.000 | 0.000 | 7.242 | 2.908 | 24.426 | 25.180 | 0.000 | 3.422 | 15.759 | 0.000 | -8.515 | 0.000 | -6.166 | -0.000 |
| M NW APARTMENT | 5.505 | -7.443 | 0.757 | -50.507 | 0.000 | 0.000 | 7.458 | 2.908 | 24.426 | 15.137 | 0.000 | 3.422 | 12.418 | 0.000 | -8.451 | 0.000 | -5.629 | -0.000 |
| M SE APARTMENT | 5.502 | -8.010 | 0.048 | -62.899 | 0.000 | 0.000 | 7.241 | 2.908 | 24.426 | 25.477 | 0.000 | 3.422 | 16.317 | 0.000 | -8.242 | 0.000 | -6.190 | -0.000 |
| M NE APARTMENT | 5.504 | -7.486 | 0.719 | -51.387 | 0.000 | 0.000 | 7.457 | 2.908 | 24.426 | 15.142 | 0.000 | 3.422 | 12.872 | 0.000 | -7.896 | 0.000 | -5.682 | -0.000 |
| M N1 APARTMENT | 5.505 | -7.743 | 0.198 | -41.167 | 0.000 | 0.000 | 7.384 | 2.908 | 24.426 | 5.869 | 0.000 | 2.064 | 10.035 | 0.000 | -5.298 | 0.000 | -4.180 | -0.000 |
| M N2 APARTMENT | 5.505 | -7.747 | 0.198 | -41.231 | 0.000 | 0.000 | 7.383 | 2.908 | 24.426 | 5.866 | 0.000 | 2.064 | 10.111 | 0.000 | -5.300 | 0.000 | -4.184 | -0.000 |
| M S1 APARTMENT | 5.503 | -8.227 | 0.000 | -54.156 | 0.000 | 0.000 | 7.175 | 2.908 | 24.426 | 16.129 | 0.000 | 2.064 | 13.948 | 0.000 | -5.226 | 0.000 | -4.545 | -0.000 |
| M S2 APARTMENT | 5.503 | -8.228 | 0.000 | -54.235 | 0.000 | 0.000 | 7.175 | 2.908 | 24.426 | 16.128 | 0.000 | 2.064 | 14.030 | 0.000 | -5.226 | 0.000 | -4.546 | -0.000 |
| T SW APARTMENT | 2.751 | -3.581 | 2.471 | -33.710 | 0.000 | 0.000 | 3.729 | 1.454 | 12.213 | 12.503 | 0.000 | 2.250 | 7.303 | 0.000 | -3.833 | 0.000 | -3.550 | -0.000 |
| T NW APARTMENT | 2.754 | -3.377 | 3.978 | -28.411 | 0.000 | 0.000 | 3.812 | 1.454 | 12.213 | 7.495 | 0.000 | 2.251 | 4.882 | 0.000 | -3.823 | 0.000 | -3.229 | -0.000 |
| T SE APARTMENT | 2.751 | -3.606 | 2.379 | -34.075 | 0.000 | 0.000 | 3.729 | 1.454 | 12.213 | 12.652 | 0.000 | 2.250 | 7.563 | 0.000 | -3.712 | 0.000 | -3.599 | -0.001 |
| T NE APARTMENT | 2.751 | -3.390 | 3.775 | -28.757 | 0.000 | 0.000 | 3.815 | 1.454 | 12.213 | 7.534 | 0.000 | 2.250 | 5.196 | 0.000 | -3.579 | 0.000 | -3.264 | -0.000 |
| T N1 APARTMENT | 2.754 | -3.421 | 2.271 | -22.780 | 0.000 | 0.000 | 3.800 | 1.454 | 12.213 | 2.922 | 0.000 | 1.358 | 4.074 | 0.000 | -2.368 | 0.000 | -2.275 | -0.000 |
| T N2 APARTMENT | 2.753 | -3.422 | 2.274 | -22.821 | 0.000 | 0.000 | 3.800 | 1.454 | 12.213 | 2.919 | 0.000 | 1.358 | 4.118 | 0.000 | -2.367 | 0.000 | -2.278 | -0.000 |
| T S1 APARTMENT | 2.751 | -3.685 | 1.035 | -28.140 | 0.000 | 0.000 | 3.702 | 1.454 | 12.213 | 8.041 | 0.000 | 1.357 | 6.230 | 0.000 | -2.363 | 0.000 | -2.594 | -0.000 |
| T S2 APARTMENT | 2.751 | -3.686 | 1.036 | -28.199 | 0.000 | 0.000 | 3.703 | 1.454 | 12.213 | 8.038 | 0.000 | 1.357 | 6.291 | 0.000 | -2.362 | 0.000 | -2.596 | -0.000 |
| T CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 5.713 | 11.688 | 0.000 | 1.112 | 0.000 | 0.247 | 0.000 | 0.000 | -0.404 | 0.000 | -0.505 | -17.852 |
| G CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 5.412 | 11.688 | 3.530 | 3.228 | 0.000 | 4.540 | 0.000 | 0.000 | -1.285 | 0.000 | -11.019 | -16.093 |
| M CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 10.860 | 23.376 | 0.000 | 2.193 | 0.000 | 0.409 | 0.000 | 0.000 | -0.901 | 0.000 | -0.903 | -35.035 |
| Total Facility | 85.319 | -117.789 | 26.208 | -831.254 | 0.000 | 0.000 | 138.368 | 99.229 | 391.594 | 255.453 | 0.000 | 48.772 | 181.443 | 0.000 | -108.565 | 0.000 | -91.750 | -77.031 |
| Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
| G SW APARTMENT | 22-JUL-17:40 | 0.00 | 424.82 | 0.00 | -3264.23 | 0.00 | 0.00 | 167.23 | 117.18 | 588.62 | 1360.87 | 0.00 | 468.21 | 137.30 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| G NW APARTMENT | 22-JUL-18:00 | 0.00 | 424.73 | 0.00 | -3223.40 | 0.00 | 0.00 | 145.49 | 117.18 | 588.62 | 1391.42 | 0.00 | 483.87 | 72.09 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| OFFICE | 05-OCT-07:02 | 0.00 | 0.00 | 0.00 | -6835.20 | 0.00 | 0.00 | 233.74 | 582.92 | 588.62 | 590.44 | 0.00 | 0.00 | 4906.88 | 0.00 | -0.00 | 0.00 | -67.39 | 0.00 |
| G NE APARTMENT | 22-JUL-18:00 | 0.00 | 424.73 | 0.00 | -2865.88 | 0.00 | 0.00 | 145.49 | 117.18 | 588.62 | 658.11 | 0.00 | 483.87 | 447.88 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| G N1 APARTMENT | 22-JUL-18:00 | 0.00 | 424.80 | 0.00 | -2296.01 | 0.00 | 0.00 | 145.49 | 117.18 | 588.62 | 466.13 | 0.00 | 291.86 | 261.93 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| G N2 APARTMENT | 22-JUL-18:00 | 0.00 | 424.80 | 0.00 | -2291.29 | 0.00 | 0.00 | 145.49 | 117.18 | 588.62 | 466.19 | 0.00 | 291.86 | 257.15 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| G S1 APARTMENT | 08-SEP-16:08 | 0.00 | 425.71 | 0.00 | -2416.48 | 0.00 | 0.00 | 0.00 | 86.80 | 588.62 | 502.85 | 0.00 | 161.78 | 650.72 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| G S2 APARTMENT | 13-AUG-16:02 | 0.00 | 425.90 | 0.00 | -2577.57 | 0.00 | 0.00 | 167.23 | 86.80 | 588.62 | 420.90 | 0.00 | 256.38 | 631.74 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| M SW APARTMENT | 22-JUL-17:40 | 0.00 | 849.49 | 0.00 | -7322.89 | 0.00 | 0.00 | 334.45 | 234.36 | 1177.25 | 2725.00 | 0.00 | 1343.81 | 658.53 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| M NW APARTMENT | 29-JUN-18:00 | 0.00 | 962.22 | 0.00 | -7489.46 | 0.00 | 0.00 | 290.97 | 234.36 | 1177.25 | 3171.19 | 0.00 | 1103.19 | 550.28 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| M SE APARTMENT | 22-JUL-16:08 | 0.00 | 849.49 | 0.00 | -6592.69 | 0.00 | 0.00 | 334.45 | 173.60 | 1177.25 | 1202.75 | 0.00 | 1536.07 | 1319.09 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| M NE APARTMENT | 30-JUN-16:17 | 0.00 | 1001.38 | 0.00 | -6648.70 | 0.00 | 0.00 | 173.92 | 173.60 | 1177.25 | 1546.36 | 0.00 | 1483.86 | 1092.34 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| M N1 APARTMENT | 30-JUN-18:00 | 0.00 | 904.62 | 0.00 | -5011.92 | 0.00 | 0.00 | 290.97 | 234.36 | 1177.25 | 1062.44 | 0.00 | 756.91 | 585.36 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| M N2 APARTMENT | 30-JUN-18:00 | 0.00 | 904.62 | 0.00 | -4998.80 | 0.00 | 0.00 | 290.97 | 234.36 | 1177.25 | 1062.58 | 0.00 | 756.91 | 572.11 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| M S1 APARTMENT | 10-OCT-15:10 | 0.00 | 665.75 | 0.00 | -4896.44 | 0.00 | 0.00 | 0.00 | 121.52 | 941.80 | 2071.59 | 0.00 | 388.19 | 707.60 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| M S2 APARTMENT | 10-OCT-15:10 | 0.00 | 665.75 | 0.00 | -4895.47 | 0.00 | 0.00 | 0.00 | 121.52 | 941.80 | 2071.58 | 0.00 | 388.19 | 706.64 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| T SW APARTMENT | 30-JUN-16:01 | 0.00 | 505.51 | 0.00 | -4990.10 | 0.00 | 0.00 | 0.00 | 86.80 | 588.62 | 1403.45 | 0.00 | 988.55 | 1417.17 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| T NW APARTMENT | 29-JUN-17:30 | 0.00 | 481.13 | 0.00 | -4966.21 | 0.00 | 0.00 | 145.49 | 117.18 | 588.62 | 1629.27 | 0.00 | 753.55 | 1250.97 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| T SE APARTMENT | 30-JUN-16:01 | 0.00 | 505.50 | 0.00 | -4496.66 | 0.00 | 0.00 | 0.00 | 86.80 | 588.62 | 715.54 | 0.00 | 988.55 | 1611.65 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| T NE APARTMENT | 30-JUN-16:10 | 0.00 | 505.42 | 0.00 | -4426.80 | 0.00 | 0.00 | 86.96 | 86.80 | 588.62 | 753.50 | 0.00 | 988.55 | 1416.95 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| T N1 APARTMENT | 30-JUN-16:20 | 0.00 | 500.77 | 0.00 | -3465.51 | 0.00 | 0.00 | 86.96 | 86.80 | 588.62 | 476.96 | 0.00 | 590.55 | 1134.85 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| T N2 APARTMENT | 30-JUN-16:13 | 0.00 | 500.85 | 0.00 | -3456.28 | 0.00 | 0.00 | 86.96 | 86.80 | 588.62 | 477.07 | 0.00 | 590.55 | 1125.43 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| T S1 APARTMENT | 22-JUL-16:01 | 0.00 | 424.83 | 0.00 | -3478.85 | 0.00 | 0.00 | 167.23 | 86.80 | 588.62 | 355.30 | 0.00 | 611.05 | 1245.02 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| T S2 APARTMENT | 22-JUL-16:01 | 0.00 | 424.83 | 0.00 | -3470.93 | 0.00 | 0.00 | 167.23 | 86.80 | 588.62 | 355.39 | 0.00 | 611.05 | 1237.00 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| T CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| G CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Total Facility | 30-JUN-16:17 | 0.00 | 15522.74 | 0.00 | -101916.29 | 0.00 | 0.00 | 1763.49 | 4289.87 | 18750.02 | 25094.60 | 0.00 | 23773.52 | 12722.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
| G SW APARTMENT | 01-APR-09:20 | 50.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 169.18 | 17.36 | 406.15 | 662.79 | 0.00 | 8.55 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -1315.01 |
| G NW APARTMENT | 01-JAN-08:00 | -571.36 | 0.00 | 974.71 | 0.00 | 0.00 | 0.00 | 165.74 | 56.42 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -567.65 | 0.00 | -259.97 | -180.50 |
| OFFICE | 28-JUN-16:01 | 0.00 | 0.00 | 1043.37 | 0.00 | 0.00 | 0.00 | 0.00 | 116.58 | 294.31 | 727.03 | 0.00 | 331.68 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -2512.98 |
| G NE APARTMENT | 01-JAN-02:00 | -453.75 | 0.00 | 887.30 | 0.00 | 0.00 | 0.00 | 194.99 | 8.68 | 241.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -504.54 | 0.00 | -347.78 | -26.24 |
| G N1 APARTMENT | 01-APR-12:10 | 197.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.91 | 17.36 | 388.49 | 298.05 | 0.00 | 25.68 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -968.80 |
| G N2 APARTMENT | 01-APR-12:00 | 192.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.92 | 17.36 | 406.15 | 293.56 | 0.00 | 26.25 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -977.68 |
| G S1 APARTMENT | 01-APR-08:50 | 1.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 168.40 | 17.36 | 394.38 | 386.17 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -12.26 | -955.40 |
| G S2 APARTMENT | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M SW APARTMENT | 07-DEC-06:00 | -1223.41 | 0.00 | 1272.45 | 0.00 | 0.00 | 0.00 | 389.98 | 112.83 | 506.22 | 0.00 | 0.00 | 0.00 | 1086.96 | 0.00 | -1392.49 | 0.00 | -752.53 | 0.00 |
| M NW APARTMENT | 07-DEC-05:00 | -1229.13 | 0.00 | 2376.58 | 0.00 | 0.00 | 0.00 | 389.98 | 52.08 | 447.35 | 0.00 | 0.00 | 0.00 | 61.82 | 0.00 | -1342.48 | 0.00 | -756.21 | 0.00 |
| M SE APARTMENT | 07-DEC-06:00 | -1223.41 | 0.00 | 1263.43 | 0.00 | 0.00 | 0.00 | 389.98 | 112.83 | 506.22 | 0.00 | 0.00 | 0.00 | 1111.11 | 0.00 | -1407.62 | 0.00 | -752.53 | 0.00 |
| M NE APARTMENT | 07-DEC-05:00 | -1229.13 | 0.00 | 2396.00 | 0.00 | 0.00 | 0.00 | 389.98 | 52.08 | 447.35 | 0.00 | 0.00 | 0.00 | 56.19 | 0.00 | -1356.27 | 0.00 | -756.21 | 0.00 |
| M N1 APARTMENT | 21-DEC-15:00 | 177.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85.83 | 34.72 | 765.21 | 227.48 | 0.00 | 37.67 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -1328.66 |
| M N2 APARTMENT | 21-DEC-15:00 | 177.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85.77 | 34.72 | 765.21 | 227.12 | 0.00 | 37.51 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -1327.50 |
| M S1 APARTMENT | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M S2 APARTMENT | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T SW APARTMENT | 07-DEC-06:00 | -611.66 | 0.00 | 2222.50 | 0.00 | 0.00 | 0.00 | 194.99 | 56.42 | 253.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -653.39 | 0.00 | -498.62 | -963.35 |
| T NW APARTMENT | 07-DEC-06:00 | -611.66 | 0.00 | 2465.57 | 0.00 | 0.00 | 0.00 | 194.99 | 56.42 | 253.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -635.64 | 0.00 | -498.62 | -1224.17 |
| T SE APARTMENT | 07-DEC-06:00 | -611.66 | 0.00 | 2235.48 | 0.00 | 0.00 | 0.00 | 194.99 | 56.42 | 253.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -660.45 | 0.00 | -498.62 | -969.28 |
| T NE APARTMENT | 07-DEC-06:00 | -611.66 | 0.00 | 2485.45 | 0.00 | 0.00 | 0.00 | 194.99 | 56.42 | 253.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -642.50 | 0.00 | -498.62 | -1237.19 |
| T N1 APARTMENT | 07-DEC-05:00 | -614.60 | 0.00 | 1807.02 | 0.00 | 0.00 | 0.00 | 194.99 | 26.04 | 223.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -391.78 | 0.00 | -302.22 | -943.13 |
| T N2 APARTMENT | 07-DEC-05:00 | -614.60 | 0.00 | 1809.62 | 0.00 | 0.00 | 0.00 | 194.99 | 26.04 | 223.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -391.76 | 0.00 | -302.22 | -945.75 |
| T S1 APARTMENT | 07-DEC-06:00 | -611.74 | 0.00 | 1524.64 | 0.00 | 0.00 | 0.00 | 194.99 | 56.42 | 253.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -406.05 | 0.00 | -300.75 | -710.61 |
| T S2 APARTMENT | 07-DEC-06:00 | -611.74 | 0.00 | 1526.26 | 0.00 | 0.00 | 0.00 | 194.99 | 56.42 | 253.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -406.04 | 0.00 | -300.75 | -712.24 |
| T CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| G CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Total Facility | 07-DEC-06:00 | -19468.43 | 421.64 | 28664.86 | -421.64 | 0.00 | 0.00 | 7273.56 | 3348.00 | 8128.81 | 0.00 | 0.00 | 0.00 | 4.65 | 0.00 | -17953.25 | 0.00 | -9998.20 | 0.00 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 09:17:08
System Ventilation Requirements for Cooling| Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
| SPLIT GSW | 0.4245 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.4245 | 0.0611 | 1.0000 | Not calculated | 0.0260 | 0.0611 | ||
| SPLIT GNW | 0.4196 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.4196 | 0.0619 | 1.0000 | Not calculated | 0.0260 | 0.0619 | ||
| SPLIT OFFICE | 0.4531 | 0.0000 | 4.7495 | 1.0000 | Calculated from schedules | 0.0381 | 0.4531 | 0.0841 | 1.0000 | Not calculated | 0.0381 | 0.0841 | ||
| SPLIT GNE | 0.3944 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.3944 | 0.0658 | 1.0000 | Not calculated | 0.0260 | 0.0658 | ||
| SPLIT GN1 | 0.3482 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.3482 | 0.0745 | 1.0000 | Not calculated | 0.0260 | 0.0745 | ||
| SPLIT GN2 | 0.3478 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.3478 | 0.0746 | 1.0000 | Not calculated | 0.0260 | 0.0746 | ||
| SPLIT GS1 | 0.3541 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.3541 | 0.0733 | 1.0000 | Not calculated | 0.0260 | 0.0733 | ||
| SPLIT GS2 | 0.3568 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.3568 | 0.0727 | 1.0000 | Not calculated | 0.0260 | 0.0727 | ||
| SPLIT MSW | 0.9657 | 0.0000 | 5.0000 | 1.0000 | Calculated from schedules | 0.0519 | 0.9657 | 0.0538 | 1.0000 | Not calculated | 0.0519 | 0.0538 | ||
| SPLIT MNW | 0.9571 | 0.0000 | 5.0000 | 1.0000 | Calculated from schedules | 0.0519 | 0.9571 | 0.0542 | 1.0000 | Not calculated | 0.0519 | 0.0542 | ||
| SPLIT MSE | 0.8984 | 0.0000 | 5.0000 | 1.0000 | Calculated from schedules | 0.0519 | 0.8984 | 0.0578 | 1.0000 | Not calculated | 0.0519 | 0.0578 | ||
| SPLIT MNE | 0.8899 | 0.0000 | 5.0000 | 1.0000 | Calculated from schedules | 0.0519 | 0.8899 | 0.0583 | 1.0000 | Not calculated | 0.0519 | 0.0583 | ||
| SPLIT MN1 | 0.7778 | 0.0000 | 5.0000 | 1.0000 | Calculated from schedules | 0.0519 | 0.7778 | 0.0667 | 1.0000 | Not calculated | 0.0519 | 0.0667 | ||
| SPLIT MN2 | 0.7766 | 0.0000 | 5.0000 | 1.0000 | Calculated from schedules | 0.0519 | 0.7766 | 0.0668 | 1.0000 | Not calculated | 0.0519 | 0.0668 | ||
| SPLIT MS1 | 0.7884 | 0.0000 | 5.0000 | 1.0000 | Calculated from schedules | 0.0519 | 0.7884 | 0.0658 | 1.0000 | Not calculated | 0.0519 | 0.0658 | ||
| SPLIT MS2 | 0.7872 | 0.0000 | 5.0000 | 1.0000 | Calculated from schedules | 0.0519 | 0.7872 | 0.0659 | 1.0000 | Not calculated | 0.0519 | 0.0659 | ||
| SPLIT TSW | 0.5542 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.5542 | 0.0468 | 1.0000 | Not calculated | 0.0260 | 0.0468 | ||
| SPLIT TNW | 0.5539 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.5539 | 0.0469 | 1.0000 | Not calculated | 0.0260 | 0.0469 | ||
| SPLIT TSE | 0.5035 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.5035 | 0.0515 | 1.0000 | Not calculated | 0.0260 | 0.0515 | ||
| SPLIT TNE | 0.5031 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.5031 | 0.0516 | 1.0000 | Not calculated | 0.0260 | 0.0516 | ||
| SPLIT TN1 | 0.4513 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.4513 | 0.0575 | 1.0000 | Not calculated | 0.0260 | 0.0575 | ||
| SPLIT TN2 | 0.4498 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.4498 | 0.0577 | 1.0000 | Not calculated | 0.0260 | 0.0577 | ||
| SPLIT TS1 | 0.4522 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.4522 | 0.0574 | 1.0000 | Not calculated | 0.0260 | 0.0574 | ||
| SPLIT TS2 | 0.4507 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.4507 | 0.0576 | 1.0000 | Not calculated | 0.0260 | 0.0576 |
| Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
| SPLIT GSW | 0.4245 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.4245 | 1.0000 | 1.0000 | Not calculated | 0.0260 | 0.0611 | ||
| SPLIT GNW | 0.4196 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.4196 | 1.0000 | 1.0000 | Not calculated | 0.0260 | 0.0619 | ||
| SPLIT OFFICE | 0.4531 | 0.0000 | 4.7495 | 1.0000 | Calculated from schedules | 0.0381 | 0.4531 | 1.0000 | 1.0000 | Not calculated | 0.0381 | 0.0841 | ||
| SPLIT GNE | 0.3944 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.3944 | 1.0000 | 1.0000 | Not calculated | 0.0260 | 0.0658 | ||
| SPLIT GN1 | 0.3482 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.3482 | 1.0000 | 1.0000 | Not calculated | 0.0260 | 0.0745 | ||
| SPLIT GN2 | 0.3478 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.3478 | 1.0000 | 1.0000 | Not calculated | 0.0260 | 0.0746 | ||
| SPLIT GS1 | 0.3541 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.3541 | 1.0000 | 1.0000 | Not calculated | 0.0260 | 0.0733 | ||
| SPLIT GS2 | 0.3568 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.3568 | 1.0000 | 1.0000 | Not calculated | 0.0260 | 0.0727 | ||
| SPLIT MSW | 0.9657 | 0.0000 | 5.0000 | 1.0000 | Calculated from schedules | 0.0519 | 0.9657 | 1.0000 | 1.0000 | Not calculated | 0.0519 | 0.0538 | ||
| SPLIT MNW | 0.9571 | 0.0000 | 5.0000 | 1.0000 | Calculated from schedules | 0.0519 | 0.9571 | 1.0000 | 1.0000 | Not calculated | 0.0519 | 0.0542 | ||
| SPLIT MSE | 0.8984 | 0.0000 | 5.0000 | 1.0000 | Calculated from schedules | 0.0519 | 0.8984 | 1.0000 | 1.0000 | Not calculated | 0.0519 | 0.0578 | ||
| SPLIT MNE | 0.8899 | 0.0000 | 5.0000 | 1.0000 | Calculated from schedules | 0.0519 | 0.8899 | 1.0000 | 1.0000 | Not calculated | 0.0519 | 0.0583 | ||
| SPLIT MN1 | 0.7778 | 0.0000 | 5.0000 | 1.0000 | Calculated from schedules | 0.0519 | 0.7778 | 1.0000 | 1.0000 | Not calculated | 0.0519 | 0.0667 | ||
| SPLIT MN2 | 0.7766 | 0.0000 | 5.0000 | 1.0000 | Calculated from schedules | 0.0519 | 0.7766 | 1.0000 | 1.0000 | Not calculated | 0.0519 | 0.0668 | ||
| SPLIT MS1 | 0.7884 | 0.0000 | 5.0000 | 1.0000 | Calculated from schedules | 0.0519 | 0.7884 | 1.0000 | 1.0000 | Not calculated | 0.0519 | 0.0658 | ||
| SPLIT MS2 | 0.7872 | 0.0000 | 5.0000 | 1.0000 | Calculated from schedules | 0.0519 | 0.7872 | 1.0000 | 1.0000 | Not calculated | 0.0519 | 0.0659 | ||
| SPLIT TSW | 0.5542 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.5542 | 1.0000 | 1.0000 | Not calculated | 0.0260 | 0.0468 | ||
| SPLIT TNW | 0.5539 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.5539 | 1.0000 | 1.0000 | Not calculated | 0.0260 | 0.0469 | ||
| SPLIT TSE | 0.5035 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.5035 | 1.0000 | 1.0000 | Not calculated | 0.0260 | 0.0515 | ||
| SPLIT TNE | 0.5031 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.5031 | 1.0000 | 1.0000 | Not calculated | 0.0260 | 0.0516 | ||
| SPLIT TN1 | 0.4513 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.4513 | 1.0000 | 1.0000 | Not calculated | 0.0260 | 0.0575 | ||
| SPLIT TN2 | 0.4498 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.4498 | 1.0000 | 1.0000 | Not calculated | 0.0260 | 0.0577 | ||
| SPLIT TS1 | 0.4522 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.4522 | 1.0000 | 1.0000 | Not calculated | 0.0260 | 0.0574 | ||
| SPLIT TS2 | 0.4507 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.4507 | 1.0000 | 1.0000 | Not calculated | 0.0260 | 0.0576 |
| AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
| G SW APARTMENT | SPLIT GSW | 0.000000 | 2.5000 | 0.000294 | 88.25 | 0.0260 | 1.0000 | 0.0260 | 1.000 | 0.0260 |
| G NW APARTMENT | SPLIT GNW | 0.000000 | 2.5000 | 0.000294 | 88.25 | 0.0260 | 1.0000 | 0.0260 | 1.000 | 0.0260 |
| OFFICE | SPLIT OFFICE | 0.000000 | 4.7495 | 0.000432 | 88.25 | 0.0381 | 1.0000 | 0.0381 | 1.000 | 0.0381 |
| G NE APARTMENT | SPLIT GNE | 0.000000 | 2.5000 | 0.000294 | 88.25 | 0.0260 | 1.0000 | 0.0260 | 1.000 | 0.0260 |
| G N1 APARTMENT | SPLIT GN1 | 0.000000 | 2.5000 | 0.000294 | 88.25 | 0.0260 | 1.0000 | 0.0260 | 1.000 | 0.0260 |
| G N2 APARTMENT | SPLIT GN2 | 0.000000 | 2.5000 | 0.000294 | 88.25 | 0.0260 | 1.0000 | 0.0260 | 1.000 | 0.0260 |
| G S1 APARTMENT | SPLIT GS1 | 0.000000 | 2.5000 | 0.000294 | 88.25 | 0.0260 | 1.0000 | 0.0260 | 1.000 | 0.0260 |
| G S2 APARTMENT | SPLIT GS2 | 0.000000 | 2.5000 | 0.000294 | 88.25 | 0.0260 | 1.0000 | 0.0260 | 1.000 | 0.0260 |
| M SW APARTMENT | SPLIT MSW | 0.000000 | 5.0000 | 0.000294 | 176.50 | 0.0519 | 1.0000 | 0.0519 | 1.000 | 0.0519 |
| M NW APARTMENT | SPLIT MNW | 0.000000 | 5.0000 | 0.000294 | 176.50 | 0.0519 | 1.0000 | 0.0519 | 1.000 | 0.0519 |
| M SE APARTMENT | SPLIT MSE | 0.000000 | 5.0000 | 0.000294 | 176.50 | 0.0519 | 1.0000 | 0.0519 | 1.000 | 0.0519 |
| M NE APARTMENT | SPLIT MNE | 0.000000 | 5.0000 | 0.000294 | 176.50 | 0.0519 | 1.0000 | 0.0519 | 1.000 | 0.0519 |
| M N1 APARTMENT | SPLIT MN1 | 0.000000 | 5.0000 | 0.000294 | 176.50 | 0.0519 | 1.0000 | 0.0519 | 1.000 | 0.0519 |
| M N2 APARTMENT | SPLIT MN2 | 0.000000 | 5.0000 | 0.000294 | 176.50 | 0.0519 | 1.0000 | 0.0519 | 1.000 | 0.0519 |
| M S1 APARTMENT | SPLIT MS1 | 0.000000 | 5.0000 | 0.000294 | 176.50 | 0.0519 | 1.0000 | 0.0519 | 1.000 | 0.0519 |
| M S2 APARTMENT | SPLIT MS2 | 0.000000 | 5.0000 | 0.000294 | 176.50 | 0.0519 | 1.0000 | 0.0519 | 1.000 | 0.0519 |
| T SW APARTMENT | SPLIT TSW | 0.000000 | 2.5000 | 0.000294 | 88.25 | 0.0260 | 1.0000 | 0.0260 | 1.000 | 0.0260 |
| T NW APARTMENT | SPLIT TNW | 0.000000 | 2.5000 | 0.000294 | 88.25 | 0.0260 | 1.0000 | 0.0260 | 1.000 | 0.0260 |
| T SE APARTMENT | SPLIT TSE | 0.000000 | 2.5000 | 0.000294 | 88.25 | 0.0260 | 1.0000 | 0.0260 | 1.000 | 0.0260 |
| T NE APARTMENT | SPLIT TNE | 0.000000 | 2.5000 | 0.000294 | 88.25 | 0.0260 | 1.0000 | 0.0260 | 1.000 | 0.0260 |
| T N1 APARTMENT | SPLIT TN1 | 0.000000 | 2.5000 | 0.000294 | 88.25 | 0.0260 | 1.0000 | 0.0260 | 1.000 | 0.0260 |
| T N2 APARTMENT | SPLIT TN2 | 0.000000 | 2.5000 | 0.000294 | 88.25 | 0.0260 | 1.0000 | 0.0260 | 1.000 | 0.0260 |
| T S1 APARTMENT | SPLIT TS1 | 0.000000 | 2.5000 | 0.000294 | 88.25 | 0.0260 | 1.0000 | 0.0260 | 1.000 | 0.0260 |
| T S2 APARTMENT | SPLIT TS2 | 0.000000 | 2.5000 | 0.000294 | 88.25 | 0.0260 | 1.0000 | 0.0260 | 1.000 | 0.0260 |
| People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
| SPLIT GSW | 0.000000 | 2.50 | 0.000294 | 88.2493 | 0.0260 | 0.0260 | 0.0260 |
| SPLIT GNW | 0.000000 | 2.50 | 0.000294 | 88.2493 | 0.0260 | 0.0260 | 0.0260 |
| SPLIT OFFICE | 0.000000 | 4.75 | 0.000432 | 88.2493 | 0.0381 | 0.0381 | 0.0381 |
| SPLIT GNE | 0.000000 | 2.50 | 0.000294 | 88.2493 | 0.0260 | 0.0260 | 0.0260 |
| SPLIT GN1 | 0.000000 | 2.50 | 0.000294 | 88.2493 | 0.0260 | 0.0260 | 0.0260 |
| SPLIT GN2 | 0.000000 | 2.50 | 0.000294 | 88.2493 | 0.0260 | 0.0260 | 0.0260 |
| SPLIT GS1 | 0.000000 | 2.50 | 0.000294 | 88.2493 | 0.0260 | 0.0260 | 0.0260 |
| SPLIT GS2 | 0.000000 | 2.50 | 0.000294 | 88.2493 | 0.0260 | 0.0260 | 0.0260 |
| SPLIT MSW | 0.000000 | 5.00 | 0.000294 | 176.4985 | 0.0519 | 0.0519 | 0.0519 |
| SPLIT MNW | 0.000000 | 5.00 | 0.000294 | 176.4985 | 0.0519 | 0.0519 | 0.0519 |
| SPLIT MSE | 0.000000 | 5.00 | 0.000294 | 176.4985 | 0.0519 | 0.0519 | 0.0519 |
| SPLIT MNE | 0.000000 | 5.00 | 0.000294 | 176.4985 | 0.0519 | 0.0519 | 0.0519 |
| SPLIT MN1 | 0.000000 | 5.00 | 0.000294 | 176.4985 | 0.0519 | 0.0519 | 0.0519 |
| SPLIT MN2 | 0.000000 | 5.00 | 0.000294 | 176.4985 | 0.0519 | 0.0519 | 0.0519 |
| SPLIT MS1 | 0.000000 | 5.00 | 0.000294 | 176.4985 | 0.0519 | 0.0519 | 0.0519 |
| SPLIT MS2 | 0.000000 | 5.00 | 0.000294 | 176.4985 | 0.0519 | 0.0519 | 0.0519 |
| SPLIT TSW | 0.000000 | 2.50 | 0.000294 | 88.2493 | 0.0260 | 0.0260 | 0.0260 |
| SPLIT TNW | 0.000000 | 2.50 | 0.000294 | 88.2493 | 0.0260 | 0.0260 | 0.0260 |
| SPLIT TSE | 0.000000 | 2.50 | 0.000294 | 88.2493 | 0.0260 | 0.0260 | 0.0260 |
| SPLIT TNE | 0.000000 | 2.50 | 0.000294 | 88.2493 | 0.0260 | 0.0260 | 0.0260 |
| SPLIT TN1 | 0.000000 | 2.50 | 0.000294 | 88.2493 | 0.0260 | 0.0260 | 0.0260 |
| SPLIT TN2 | 0.000000 | 2.50 | 0.000294 | 88.2493 | 0.0260 | 0.0260 | 0.0260 |
| SPLIT TS1 | 0.000000 | 2.50 | 0.000294 | 88.2493 | 0.0260 | 0.0260 | 0.0260 |
| SPLIT TS2 | 0.000000 | 2.50 | 0.000294 | 88.2493 | 0.0260 | 0.0260 | 0.0260 |
| AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
| G SW APARTMENT | SPLIT GSW | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4245 | 0.4245 | 0.4245 | No | 0.0260 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| G NW APARTMENT | SPLIT GNW | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4196 | 0.4196 | 0.4196 | No | 0.0260 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| OFFICE | SPLIT OFFICE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4531 | 0.4531 | 0.4531 | No | 0.0381 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| G NE APARTMENT | SPLIT GNE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.3944 | 0.3944 | 0.3944 | No | 0.0260 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| G N1 APARTMENT | SPLIT GN1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.3482 | 0.3482 | 0.3482 | No | 0.0260 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| G N2 APARTMENT | SPLIT GN2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.3478 | 0.3478 | 0.3478 | No | 0.0260 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| G S1 APARTMENT | SPLIT GS1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.3541 | 0.3541 | 0.3541 | No | 0.0260 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| G S2 APARTMENT | SPLIT GS2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.3568 | 0.3568 | 0.3568 | No | 0.0260 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| M SW APARTMENT | SPLIT MSW | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9657 | 0.9657 | 0.9657 | No | 0.0519 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| M NW APARTMENT | SPLIT MNW | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9571 | 0.9571 | 0.9571 | No | 0.0519 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| M SE APARTMENT | SPLIT MSE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8984 | 0.8984 | 0.8984 | No | 0.0519 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| M NE APARTMENT | SPLIT MNE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8899 | 0.8899 | 0.8899 | No | 0.0519 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| M N1 APARTMENT | SPLIT MN1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.7778 | 0.7778 | 0.7778 | No | 0.0519 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| M N2 APARTMENT | SPLIT MN2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.7766 | 0.7766 | 0.7766 | No | 0.0519 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| M S1 APARTMENT | SPLIT MS1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.7884 | 0.7884 | 0.7884 | No | 0.0519 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| M S2 APARTMENT | SPLIT MS2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.7872 | 0.7872 | 0.7872 | No | 0.0519 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| T SW APARTMENT | SPLIT TSW | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.5542 | 0.5542 | 0.5542 | No | 0.0260 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| T NW APARTMENT | SPLIT TNW | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.5539 | 0.5539 | 0.5539 | No | 0.0260 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| T SE APARTMENT | SPLIT TSE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.5035 | 0.5035 | 0.5035 | No | 0.0260 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| T NE APARTMENT | SPLIT TNE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.5031 | 0.5031 | 0.5031 | No | 0.0260 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| T N1 APARTMENT | SPLIT TN1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4513 | 0.4513 | 0.4513 | No | 0.0260 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| T N2 APARTMENT | SPLIT TN2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4498 | 0.4498 | 0.4498 | No | 0.0260 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| T S1 APARTMENT | SPLIT TS1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4522 | 0.4522 | 0.4522 | No | 0.0260 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| T S2 APARTMENT | SPLIT TS2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4507 | 0.4507 | 0.4507 | No | 0.0260 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
| SPLIT GSW | 0.4245 | 0.4245 | 0.4245 | 0.4245 | 0.0260 | 1.0000 |
| SPLIT GNW | 0.4196 | 0.4196 | 0.4196 | 0.4196 | 0.0260 | 1.0000 |
| SPLIT OFFICE | 0.4531 | 0.4531 | 0.4531 | 0.4531 | 0.0381 | 1.0000 |
| SPLIT GNE | 0.3944 | 0.3944 | 0.3944 | 0.3944 | 0.0260 | 1.0000 |
| SPLIT GN1 | 0.3482 | 0.3482 | 0.3482 | 0.3482 | 0.0260 | 1.0000 |
| SPLIT GN2 | 0.3478 | 0.3478 | 0.3478 | 0.3478 | 0.0260 | 1.0000 |
| SPLIT GS1 | 0.3541 | 0.3541 | 0.3541 | 0.3541 | 0.0260 | 1.0000 |
| SPLIT GS2 | 0.3568 | 0.3568 | 0.3568 | 0.3568 | 0.0260 | 1.0000 |
| SPLIT MSW | 0.9657 | 0.9657 | 0.9657 | 0.9657 | 0.0519 | 1.0000 |
| SPLIT MNW | 0.9571 | 0.9571 | 0.9571 | 0.9571 | 0.0519 | 1.0000 |
| SPLIT MSE | 0.8984 | 0.8984 | 0.8984 | 0.8984 | 0.0519 | 1.0000 |
| SPLIT MNE | 0.8899 | 0.8899 | 0.8899 | 0.8899 | 0.0519 | 1.0000 |
| SPLIT MN1 | 0.7778 | 0.7778 | 0.7778 | 0.7778 | 0.0519 | 1.0000 |
| SPLIT MN2 | 0.7766 | 0.7766 | 0.7766 | 0.7766 | 0.0519 | 1.0000 |
| SPLIT MS1 | 0.7884 | 0.7884 | 0.7884 | 0.7884 | 0.0519 | 1.0000 |
| SPLIT MS2 | 0.7872 | 0.7872 | 0.7872 | 0.7872 | 0.0519 | 1.0000 |
| SPLIT TSW | 0.5542 | 0.5542 | 0.5542 | 0.5542 | 0.0260 | 1.0000 |
| SPLIT TNW | 0.5539 | 0.5539 | 0.5539 | 0.5539 | 0.0260 | 1.0000 |
| SPLIT TSE | 0.5035 | 0.5035 | 0.5035 | 0.5035 | 0.0260 | 1.0000 |
| SPLIT TNE | 0.5031 | 0.5031 | 0.5031 | 0.5031 | 0.0260 | 1.0000 |
| SPLIT TN1 | 0.4513 | 0.4513 | 0.4513 | 0.4513 | 0.0260 | 1.0000 |
| SPLIT TN2 | 0.4498 | 0.4498 | 0.4498 | 0.4498 | 0.0260 | 1.0000 |
| SPLIT TS1 | 0.4522 | 0.4522 | 0.4522 | 0.4522 | 0.0260 | 1.0000 |
| SPLIT TS2 | 0.4507 | 0.4507 | 0.4507 | 0.4507 | 0.0260 | 1.0000 |
| AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
| G SW APARTMENT | SPLIT GSW | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4245 | 0.4245 | 0.4245 | No | 0.0260 | 0.4758 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| G NW APARTMENT | SPLIT GNW | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4196 | 0.4196 | 0.4196 | No | 0.0260 | 0.5493 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| OFFICE | SPLIT OFFICE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4531 | 0.4531 | 0.4531 | No | 0.0381 | 0.4679 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| G NE APARTMENT | SPLIT GNE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.3944 | 0.3944 | 0.3944 | No | 0.0260 | 0.5473 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| G N1 APARTMENT | SPLIT GN1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.3482 | 0.3482 | 0.3482 | No | 0.0260 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| G N2 APARTMENT | SPLIT GN2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.3478 | 0.3478 | 0.3478 | No | 0.0260 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| G S1 APARTMENT | SPLIT GS1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.3541 | 0.3541 | 0.3541 | No | 0.0260 | 0.8301 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| G S2 APARTMENT | SPLIT GS2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.3568 | 0.3568 | 0.3568 | No | 0.0260 | 0.8146 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| M SW APARTMENT | SPLIT MSW | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9657 | 0.9657 | 0.9657 | No | 0.0519 | 0.4186 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| M NW APARTMENT | SPLIT MNW | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9571 | 0.9571 | 0.9571 | No | 0.0519 | 0.4835 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| M SE APARTMENT | SPLIT MSE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8984 | 0.8984 | 0.8984 | No | 0.0519 | 0.4173 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| M NE APARTMENT | SPLIT MNE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8899 | 0.8899 | 0.8899 | No | 0.0519 | 0.4816 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| M N1 APARTMENT | SPLIT MN1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.7778 | 0.7778 | 0.7778 | No | 0.0519 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| M N2 APARTMENT | SPLIT MN2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.7766 | 0.7766 | 0.7766 | No | 0.0519 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| M S1 APARTMENT | SPLIT MS1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.7884 | 0.7884 | 0.7884 | No | 0.0519 | 0.8066 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| M S2 APARTMENT | SPLIT MS2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.7872 | 0.7872 | 0.7872 | No | 0.0519 | 0.8064 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| T SW APARTMENT | SPLIT TSW | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.5542 | 0.5542 | 0.5542 | No | 0.0260 | 0.2232 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| T NW APARTMENT | SPLIT TNW | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.5539 | 0.5539 | 0.5539 | No | 0.0260 | 0.2418 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| T SE APARTMENT | SPLIT TSE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.5035 | 0.5035 | 0.5035 | No | 0.0260 | 0.2227 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| T NE APARTMENT | SPLIT TNE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.5031 | 0.5031 | 0.5031 | No | 0.0260 | 0.2412 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| T N1 APARTMENT | SPLIT TN1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4513 | 0.4513 | 0.4513 | No | 0.0260 | 0.3560 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| T N2 APARTMENT | SPLIT TN2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4498 | 0.4498 | 0.4498 | No | 0.0260 | 0.3559 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| T S1 APARTMENT | SPLIT TS1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4522 | 0.4522 | 0.4522 | No | 0.0260 | 0.3168 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| T S2 APARTMENT | SPLIT TS2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4507 | 0.4507 | 0.4507 | No | 0.0260 | 0.3168 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
| SPLIT GSW | 0.4245 | 0.4245 | 0.4245 | 0.4245 | 0.0260 | 1.0000 |
| SPLIT GNW | 0.4196 | 0.4196 | 0.4196 | 0.4196 | 0.0260 | 1.0000 |
| SPLIT OFFICE | 0.4531 | 0.4531 | 0.4531 | 0.4531 | 0.0381 | 1.0000 |
| SPLIT GNE | 0.3944 | 0.3944 | 0.3944 | 0.3944 | 0.0260 | 1.0000 |
| SPLIT GN1 | 0.3482 | 0.3482 | 0.3482 | 0.3482 | 0.0260 | 1.0000 |
| SPLIT GN2 | 0.3478 | 0.3478 | 0.3478 | 0.3478 | 0.0260 | 1.0000 |
| SPLIT GS1 | 0.3541 | 0.3541 | 0.3541 | 0.3541 | 0.0260 | 1.0000 |
| SPLIT GS2 | 0.3568 | 0.3568 | 0.3568 | 0.3568 | 0.0260 | 1.0000 |
| SPLIT MSW | 0.9657 | 0.9657 | 0.9657 | 0.9657 | 0.0519 | 1.0000 |
| SPLIT MNW | 0.9571 | 0.9571 | 0.9571 | 0.9571 | 0.0519 | 1.0000 |
| SPLIT MSE | 0.8984 | 0.8984 | 0.8984 | 0.8984 | 0.0519 | 1.0000 |
| SPLIT MNE | 0.8899 | 0.8899 | 0.8899 | 0.8899 | 0.0519 | 1.0000 |
| SPLIT MN1 | 0.7778 | 0.7778 | 0.7778 | 0.7778 | 0.0519 | 1.0000 |
| SPLIT MN2 | 0.7766 | 0.7766 | 0.7766 | 0.7766 | 0.0519 | 1.0000 |
| SPLIT MS1 | 0.7884 | 0.7884 | 0.7884 | 0.7884 | 0.0519 | 1.0000 |
| SPLIT MS2 | 0.7872 | 0.7872 | 0.7872 | 0.7872 | 0.0519 | 1.0000 |
| SPLIT TSW | 0.5542 | 0.5542 | 0.5542 | 0.5542 | 0.0260 | 1.0000 |
| SPLIT TNW | 0.5539 | 0.5539 | 0.5539 | 0.5539 | 0.0260 | 1.0000 |
| SPLIT TSE | 0.5035 | 0.5035 | 0.5035 | 0.5035 | 0.0260 | 1.0000 |
| SPLIT TNE | 0.5031 | 0.5031 | 0.5031 | 0.5031 | 0.0260 | 1.0000 |
| SPLIT TN1 | 0.4513 | 0.4513 | 0.4513 | 0.4513 | 0.0260 | 1.0000 |
| SPLIT TN2 | 0.4498 | 0.4498 | 0.4498 | 0.4498 | 0.0260 | 1.0000 |
| SPLIT TS1 | 0.4522 | 0.4522 | 0.4522 | 0.4522 | 0.0260 | 1.0000 |
| SPLIT TS2 | 0.4507 | 0.4507 | 0.4507 | 0.4507 | 0.0260 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 09:17:08
Sec1.1A-General Information| Data | |
| Weather File | RUNPERIOD 1 ** Tucson-Davis Monthan AFB AZ USA TMY3 WMO#=722745 |
| Total gross floor area [m2] | 3134.61 |
| Principal Heating Source | Natural Gas |
| Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
| G SW APARTMENT | 88.25 | 88.25 | 0.00 | 117.85 |
| G NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
| OFFICE | 88.25 | 88.25 | 0.00 | 33.56 |
| G NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
| G N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
| G N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
| G S1 APARTMENT | 88.25 | 88.25 | 0.00 | 117.85 |
| G S2 APARTMENT | 88.25 | 88.25 | 0.00 | 117.85 |
| M SW APARTMENT | 88.25 | 88.25 | 0.00 | 117.85 |
| M NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
| M SE APARTMENT | 88.25 | 88.25 | 0.00 | 117.85 |
| M NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
| M N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
| M N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
| M S1 APARTMENT | 88.25 | 88.25 | 0.00 | 117.85 |
| M S2 APARTMENT | 88.25 | 88.25 | 0.00 | 117.85 |
| T SW APARTMENT | 88.25 | 88.25 | 0.00 | 117.85 |
| T NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
| T SE APARTMENT | 88.25 | 88.25 | 0.00 | 117.85 |
| T NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
| T N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
| T N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
| T S1 APARTMENT | 88.25 | 88.25 | 0.00 | 117.85 |
| T S2 APARTMENT | 88.25 | 88.25 | 0.00 | 117.85 |
| T CORRIDOR | 77.66 | 0.00 | 77.66 | 168.00 |
| G CORRIDOR | 77.66 | 0.00 | 77.66 | 168.00 |
| M CORRIDOR | 77.66 | 0.00 | 77.66 | 168.00 |
| Totals | 3134.61 | 2823.98 | 310.64 |
| Data | |
| Number of hours heating loads not met | 0.00 |
| Number of hours cooling loads not met | 0.00 |
| Number of hours not met | 0.00 |
| Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
| None |
| Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
| Heating -- General | 0.00 | 0.00 | 26.80 | 34097.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Cooling -- General | 266.43 | 34911.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Lighting -- LightsWired | 94.96 | 5496.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Lighting -- LightsPlugIn | 4.27 | 407.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Lighting -- General | 50.07 | 3183.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment -- MiscPlug | 388.06 | 18541.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment -- ElevatorLift | 65.48 | 4006.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment -- ElevatorLightsFan | 5.11 | 162.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans -- Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans -- General | 132.58 | 11397.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Recovery -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems -- Water Heater | 379.22 | 37336.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Process Subtotal [GJ] | Total Energy Use [GJ] | |
| Electricity | 458.66 | 1386.19 |
| Natural Gas | 0.00 | 26.80 |
| Additional | 0.00 | 0.00 |
| Total | 458.66 | 1412.99 |
| Process Subtotal [$] | Total Energy Cost [$] | |
| Electricity | 0.00 | |
| Natural Gas | 0.00 | |
| Additional | 0.00 | |
| Total | 0.00 |
| Rated Capacity [kW] | Annual Energy Generated [GJ] | |
| Photovoltaic | 0.00 | 0.00 |
| Wind | 0.00 | 0.00 |
| Electricty [MJ/m2] | |
| Interior Lighting (All) | 31.66 |
| Space Heating | 0.00 |
| Space Cooling | 85.00 |
| Fans (All) | 42.30 |
| Service Water Heating | 120.98 |
| Receptacle Equipment | 146.32 |
| Miscellaneous (All) | 442.22 |
| Subtotal | 442.22 |
| Natural Gas [MJ/m2] | |
| Space Heating | 8.55 |
| Service Water Heating | 0.00 |
| Miscellaneous (All) | 8.55 |
| Subtotal | 8.55 |
| Additional [MJ/m2] | |
| Subtotal | 0.00 |
| Miscellaneous | 0.00 |
| Percent [%] | |
| Interior Lighting (All) | 7.02 |
| Space Heating | 1.90 |
| Space Cooling | 18.86 |
| Fans (All) | 9.38 |
| Service Water Heating | 26.84 |
| Receptacle Equipment | 32.46 |
| Miscellaneous | 3.54 |
| Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
| OCC_APT_SCH_STAY_HOME_FAMILY | 5993. | 8760. |
| OCC_APT_SCH_CORRIDOR | 5993. | 8760. |
| OCC_APT_SCH_WORKING_FAMILY | 5845. | 6055. |
| OCC_OFF_SCH | 2210. | 2340. |
| OCC_OFF_W_SB_SCH | 1820. | 1820. |
| LTG_SCH_OFFICE | 2435. | 8760. |
| LTG_SCH_CORRIDOR | 8760. | 8760. |
| LTG_SCH_APARTMENT_HARDWIRED | 527. | 8760. |
| LTG_SCH_APARTMENT_PLUGIN | 527. | 8760. |
| EQP_APT_SCH | 5763. | 8760. |
| EQP_OFF_SCH | 4531. | 8760. |
| INF_APT_SCH | 8760. | 8760. |
| INF_OFF_SCH | 8760. | 8760. |
| INF_COR_SCH | 8760. | 8760. |
| INFIL_DOOR_OPENING_SCH | 1466. | 5840. |
| ALL OFF | 0. | 0. |
| ALL ON | 8760. | 8760. |
| ALWAYS_ON | 8760. | 8760. |
| ALLON_EXCEPT_DD | 8760. | 8760. |
| EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
| FAN_OFF_W_SB_SCH | 8240. | 8240. |
| APT_DHW_SCH | 4592. | 8760. |
| EXTERIOR_LTG_SCH | 4380. | 4380. |
| BLDG_ELEVATORS | 2270. | 8760. |
| ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
| ELEV_LIGHT_FAN_SCH_ADD_DF | 2154. | 8760. |
| SLIDING_DOORS_VENTILATION_AVAILABILITY_SCH | 5840. | 5840. |
| First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
| HTGSETP_APT_SCH | APTHEATINGSETPOINT | January | 21.10 | 365 | 21.10 | 365 |
| HTGSETP_DESIGN_OFF_SCH | OFFHEATINGSETPOINT | January | 21.10 | 365 | 21.10 | 365 |
| CLGSETP_APT_SCH | APTCOOLINGSETPOINT | July | 24.00 | 365 | 24.00 | 365 |
| CLGSETP_DESIGN_OFF_SCH | OFFCOOLINGSETPOINT | July | 23.90 | 365 | 23.90 | 365 |
| S HTGSETP_APT_SCH | S APARTMENT DUAL SP CONTROL | January | 21.10 | 365 | 21.10 | 365 |
| S CLGSETP_APT_SCH | S APARTMENT DUAL SP CONTROL | July | 24.00 | 365 | 24.00 | 365 |
| N HTGSETP_APT_SCH | N APARTMENT DUAL SP CONTROL | January | 21.10 | 365 | 21.10 | 365 |
| N CLGSETP_APT_SCH | N APARTMENT DUAL SP CONTROL | July | 24.00 | 365 | 24.00 | 365 |
| HTGSETP_OFF_SCH_YES_OPTIMUM | OFFICE DUAL SP CONTROL | January | 21.10 | 365 | 15.60 | 365 |
| CLGSETP_OFF_SCH_YES_OPTIMUM | OFFICE DUAL SP CONTROL | July | 24.00 | 365 | 29.40 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 09:17:08
Heat Index Hours| Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
| G SW APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| G NW APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| OFFICE | 6051.50 | 2708.50 | 0.00 | 0.00 | 0.00 |
| G NE APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| G N1 APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| G N2 APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| G S1 APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| G S2 APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M SW APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M NW APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M SE APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M NE APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M N1 APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M N2 APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M S1 APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M S2 APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T SW APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T NW APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T SE APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T NE APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T N1 APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T N2 APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T S1 APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T S2 APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T CORRIDOR | 5901.00 | 2856.17 | 2.83 | 0.00 | 0.00 |
| G CORRIDOR | 6177.67 | 2581.17 | 1.17 | 0.00 | 0.00 |
| M CORRIDOR | 4971.83 | 3788.17 | 0.00 | 0.00 | 0.00 |
| Min | 4971.83 | 0.00 | 0.00 | 0.00 | 0.00 |
| Max | 8760.00 | 3788.17 | 2.83 | 0.00 | 0.00 |
| Average | 8317.85 | 442.00 | 0.15 | 0.00 | 0.00 |
| Sum | 224582.00 | 11934.00 | 4.00 | 0.00 | 0.00 |
| Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
| G SW APARTMENT | 11830.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| G NW APARTMENT | 10585.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| OFFICE | 7000.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| G NE APARTMENT | 10585.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| G N1 APARTMENT | 10585.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| G N2 APARTMENT | 10585.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| G S1 APARTMENT | 11830.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| G S2 APARTMENT | 11830.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M SW APARTMENT | 11830.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M NW APARTMENT | 10585.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M SE APARTMENT | 11830.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M NE APARTMENT | 10585.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M N1 APARTMENT | 10585.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M N2 APARTMENT | 10585.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M S1 APARTMENT | 11830.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M S2 APARTMENT | 11830.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T SW APARTMENT | 11830.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T NW APARTMENT | 10585.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T SE APARTMENT | 11830.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T NE APARTMENT | 10585.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T N1 APARTMENT | 10585.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T N2 APARTMENT | 10585.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T S1 APARTMENT | 11830.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T S2 APARTMENT | 11830.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T CORRIDOR | 15873.00 | 7116.50 | 5.50 | 0.00 | 0.00 |
| G CORRIDOR | 16263.00 | 6727.33 | 4.67 | 0.00 | 0.00 |
| M CORRIDOR | 13278.50 | 9716.50 | 0.00 | 0.00 | 0.00 |
| Min | 7000.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Max | 16263.00 | 9716.50 | 5.50 | 0.00 | 0.00 |
| Average | 11465.35 | 872.60 | 0.38 | 0.00 | 0.00 |
| Sum | 309564.50 | 23560.33 | 10.17 | 0.00 | 0.00 |
| Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
| G SW APARTMENT | 8748.17 | 11.83 | 0.00 | 0.00 | 0.00 |
| G NW APARTMENT | 8736.50 | 23.50 | 0.00 | 0.00 | 0.00 |
| OFFICE | 7243.17 | 1516.83 | 0.00 | 0.00 | 0.00 |
| G NE APARTMENT | 8729.33 | 30.67 | 0.00 | 0.00 | 0.00 |
| G N1 APARTMENT | 8745.50 | 14.50 | 0.00 | 0.00 | 0.00 |
| G N2 APARTMENT | 8745.33 | 14.67 | 0.00 | 0.00 | 0.00 |
| G S1 APARTMENT | 8753.67 | 6.33 | 0.00 | 0.00 | 0.00 |
| G S2 APARTMENT | 8757.67 | 2.33 | 0.00 | 0.00 | 0.00 |
| M SW APARTMENT | 8718.00 | 42.00 | 0.00 | 0.00 | 0.00 |
| M NW APARTMENT | 8709.83 | 50.17 | 0.00 | 0.00 | 0.00 |
| M SE APARTMENT | 8716.00 | 44.00 | 0.00 | 0.00 | 0.00 |
| M NE APARTMENT | 8707.67 | 52.33 | 0.00 | 0.00 | 0.00 |
| M N1 APARTMENT | 8728.00 | 32.00 | 0.00 | 0.00 | 0.00 |
| M N2 APARTMENT | 8728.33 | 31.67 | 0.00 | 0.00 | 0.00 |
| M S1 APARTMENT | 8737.50 | 22.50 | 0.00 | 0.00 | 0.00 |
| M S2 APARTMENT | 8737.50 | 22.50 | 0.00 | 0.00 | 0.00 |
| T SW APARTMENT | 8707.33 | 52.67 | 0.00 | 0.00 | 0.00 |
| T NW APARTMENT | 8711.83 | 48.17 | 0.00 | 0.00 | 0.00 |
| T SE APARTMENT | 8709.67 | 50.33 | 0.00 | 0.00 | 0.00 |
| T NE APARTMENT | 8718.50 | 41.50 | 0.00 | 0.00 | 0.00 |
| T N1 APARTMENT | 8703.67 | 56.33 | 0.00 | 0.00 | 0.00 |
| T N2 APARTMENT | 8704.50 | 55.50 | 0.00 | 0.00 | 0.00 |
| T S1 APARTMENT | 8700.33 | 59.67 | 0.00 | 0.00 | 0.00 |
| T S2 APARTMENT | 8700.83 | 59.17 | 0.00 | 0.00 | 0.00 |
| T CORRIDOR | 2839.50 | 5877.83 | 42.67 | 0.00 | 0.00 |
| G CORRIDOR | 6505.83 | 2249.67 | 4.50 | 0.00 | 0.00 |
| M CORRIDOR | 241.33 | 8402.67 | 116.00 | 0.00 | 0.00 |
| Min | 241.33 | 2.33 | 0.00 | 0.00 | 0.00 |
| Max | 8757.67 | 8402.67 | 116.00 | 0.00 | 0.00 |
| Average | 8055.02 | 698.94 | 6.04 | 0.00 | 0.00 |
| Sum | 217485.50 | 18871.33 | 163.17 | 0.00 | 0.00 |
| Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
| G SW APARTMENT | 11808.00 | 22.00 | 0.00 | 0.00 | 0.00 |
| G NW APARTMENT | 10558.83 | 26.17 | 0.00 | 0.00 | 0.00 |
| OFFICE | 6900.00 | 100.00 | 0.00 | 0.00 | 0.00 |
| G NE APARTMENT | 10548.50 | 36.50 | 0.00 | 0.00 | 0.00 |
| G N1 APARTMENT | 10572.33 | 12.67 | 0.00 | 0.00 | 0.00 |
| G N2 APARTMENT | 10572.17 | 12.83 | 0.00 | 0.00 | 0.00 |
| G S1 APARTMENT | 11817.67 | 12.33 | 0.00 | 0.00 | 0.00 |
| G S2 APARTMENT | 11825.33 | 4.67 | 0.00 | 0.00 | 0.00 |
| M SW APARTMENT | 11751.33 | 78.67 | 0.00 | 0.00 | 0.00 |
| M NW APARTMENT | 10518.67 | 66.33 | 0.00 | 0.00 | 0.00 |
| M SE APARTMENT | 11750.50 | 79.50 | 0.00 | 0.00 | 0.00 |
| M NE APARTMENT | 10514.67 | 70.33 | 0.00 | 0.00 | 0.00 |
| M N1 APARTMENT | 10555.83 | 29.17 | 0.00 | 0.00 | 0.00 |
| M N2 APARTMENT | 10556.33 | 28.67 | 0.00 | 0.00 | 0.00 |
| M S1 APARTMENT | 11788.33 | 41.67 | 0.00 | 0.00 | 0.00 |
| M S2 APARTMENT | 11788.33 | 41.67 | 0.00 | 0.00 | 0.00 |
| T SW APARTMENT | 11737.50 | 92.50 | 0.00 | 0.00 | 0.00 |
| T NW APARTMENT | 10516.83 | 68.17 | 0.00 | 0.00 | 0.00 |
| T SE APARTMENT | 11740.67 | 89.33 | 0.00 | 0.00 | 0.00 |
| T NE APARTMENT | 10521.00 | 64.00 | 0.00 | 0.00 | 0.00 |
| T N1 APARTMENT | 10498.17 | 86.83 | 0.00 | 0.00 | 0.00 |
| T N2 APARTMENT | 10499.67 | 85.33 | 0.00 | 0.00 | 0.00 |
| T S1 APARTMENT | 11720.83 | 109.17 | 0.00 | 0.00 | 0.00 |
| T S2 APARTMENT | 11721.83 | 108.17 | 0.00 | 0.00 | 0.00 |
| T CORRIDOR | 7404.50 | 15493.67 | 96.83 | 0.00 | 0.00 |
| G CORRIDOR | 16625.83 | 6351.17 | 18.00 | 0.00 | 0.00 |
| M CORRIDOR | 607.33 | 22104.50 | 283.17 | 0.00 | 0.00 |
| Min | 607.33 | 4.67 | 0.00 | 0.00 | 0.00 |
| Max | 16625.83 | 22104.50 | 283.17 | 0.00 | 0.00 |
| Average | 10645.22 | 1678.37 | 14.74 | 0.00 | 0.00 |
| Sum | 287421.00 | 45316.00 | 398.00 | 0.00 | 0.00 |
| SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
| None |
| SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
| None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 09:17:08
CO2 Level Hours| Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
| None |
| Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
| None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 09:17:08
Illuminance Level Hours| A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
| None |
| A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
| None |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
| January | 14.827 |
| February | 12.716 |
| March | 15.425 |
| April | 23.310 |
| May | 26.312 |
| June | 31.196 |
| July | 30.423 |
| August | 29.815 |
| September | 27.754 |
| October | 20.869 |
| November | 15.431 |
| December | 11.863 |
| Annual Sum or Average | 21.705 |
| Minimum of Months | 11.863 |
| Maximum of Months | 31.196 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Environment
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
| January | 14.827 |
| February | 12.716 |
| March | 15.425 |
| April | 23.310 |
| May | 26.312 |
| June | 31.196 |
| July | 30.423 |
| August | 29.815 |
| September | 27.754 |
| October | 20.869 |
| November | 15.431 |
| December | 11.863 |
| Annual Sum or Average | 21.705 |
| Minimum of Months | 11.863 |
| Maximum of Months | 31.196 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2012
For: Environment
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
| January | 14.827 |
| February | 12.716 |
| March | 15.425 |
| April | 23.310 |
| May | 26.312 |
| June | 31.196 |
| July | 30.423 |
| August | 29.815 |
| September | 27.754 |
| October | 20.869 |
| November | 15.431 |
| December | 11.863 |
| Annual Sum or Average | 21.705 |
| Minimum of Months | 11.863 |
| Maximum of Months | 31.196 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
| January | 14.827 |
| February | 12.716 |
| March | 15.425 |
| April | 23.310 |
| May | 26.312 |
| June | 31.196 |
| July | 30.423 |
| August | 29.815 |
| September | 27.754 |
| October | 20.869 |
| November | 15.431 |
| December | 11.863 |
| Annual Sum or Average | 21.705 |
| Minimum of Months | 11.863 |
| Maximum of Months | 31.196 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME APARTMENTMIDRISE
For: Environment
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
| January | 14.827 |
| February | 12.716 |
| March | 15.425 |
| April | 23.310 |
| May | 26.312 |
| June | 31.196 |
| July | 30.423 |
| August | 29.815 |
| September | 27.754 |
| October | 20.869 |
| November | 15.431 |
| December | 11.863 |
| Annual Sum or Average | 21.705 |
| Minimum of Months | 11.863 |
| Maximum of Months | 31.196 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
| January | 14.827 |
| February | 12.716 |
| March | 15.425 |
| April | 23.310 |
| May | 26.312 |
| June | 31.196 |
| July | 30.423 |
| August | 29.815 |
| September | 27.754 |
| October | 20.869 |
| November | 15.431 |
| December | 11.863 |
| Annual Sum or Average | 21.705 |
| Minimum of Months | 11.863 |
| Maximum of Months | 31.196 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
| January | 14.827 |
| February | 12.716 |
| March | 15.425 |
| April | 23.310 |
| May | 26.312 |
| June | 31.196 |
| July | 30.423 |
| August | 29.815 |
| September | 27.754 |
| October | 20.869 |
| November | 15.431 |
| December | 11.863 |
| Annual Sum or Average | 21.705 |
| Minimum of Months | 11.863 |
| Maximum of Months | 31.196 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 2B
For: Environment
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
| January | 14.827 |
| February | 12.716 |
| March | 15.425 |
| April | 23.310 |
| May | 26.312 |
| June | 31.196 |
| July | 30.423 |
| August | 29.815 |
| September | 27.754 |
| October | 20.869 |
| November | 15.431 |
| December | 11.863 |
| Annual Sum or Average | 21.705 |
| Minimum of Months | 11.863 |
| Maximum of Months | 31.196 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_AZ_TUCSON
For: Environment
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
| January | 14.827 |
| February | 12.716 |
| March | 15.425 |
| April | 23.310 |
| May | 26.312 |
| June | 31.196 |
| July | 30.423 |
| August | 29.815 |
| September | 27.754 |
| October | 20.869 |
| November | 15.431 |
| December | 11.863 |
| Annual Sum or Average | 21.705 |
| Minimum of Months | 11.863 |
| Maximum of Months | 31.196 |
Report: ZoneCoolingSummaryMonthly
For: G SW APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.150962E+10 | 1717.41 | 31-JAN-16:30 | 29.00 | 10.73 | 0.118836E+09 | 70.37 | 01-JAN-17:40 | 29.00 | 10.73 |
| February | 0.698627E+09 | 1148.82 | 01-FEB-15:30 | 15.50 | 6.96 | 89738299.13 | 70.36 | 25-FEB-19:30 | 14.50 | 9.61 |
| March | 0.802655E+09 | 1446.51 | 18-MAR-16:30 | 27.20 | 12.06 | 0.102441E+09 | 70.37 | 18-MAR-23:10 | 13.80 | 9.19 |
| April | 0.219387E+10 | 2089.76 | 14-APR-17:25 | 34.50 | 14.31 | 0.122770E+09 | 70.37 | 27-APR-02:00 | 13.00 | 8.24 |
| May | 0.250974E+10 | 2038.51 | 19-MAY-17:30 | 34.50 | 13.66 | 0.125670E+09 | 70.37 | 12-MAY-06:10 | 34.50 | 13.66 |
| June | 0.348854E+10 | 2666.96 | 30-JUN-17:15 | 39.67 | 17.71 | 0.120423E+09 | 70.32 | 01-JUN-06:40 | 39.67 | 17.71 |
| July | 0.383460E+10 | 2839.38 | 22-JUL-17:40 | 38.00 | 18.94 | 0.129276E+09 | 70.31 | 03-JUL-00:40 | 38.00 | 18.94 |
| August | 0.392891E+10 | 2836.74 | 13-AUG-16:30 | 38.00 | 20.26 | 0.123964E+09 | 70.31 | 25-AUG-01:19 | 23.00 | 9.55 |
| September | 0.389995E+10 | 2792.18 | 08-SEP-16:30 | 37.45 | 20.08 | 0.123964E+09 | 70.31 | 17-SEP-00:30 | 23.55 | 13.46 |
| October | 0.295366E+10 | 2586.24 | 10-OCT-15:30 | 34.50 | 16.70 | 0.126846E+09 | 70.36 | 27-OCT-23:40 | 12.33 | 6.79 |
| November | 0.193270E+10 | 2373.62 | 01-NOV-16:02 | 27.67 | 15.49 | 0.120878E+09 | 70.37 | 21-NOV-07:10 | 11.50 | 7.21 |
| December | 0.143390E+10 | 1925.94 | 25-DEC-16:30 | 25.00 | 11.60 | 0.114371E+09 | 70.37 | 14-DEC-20:19 | 25.00 | 11.60 |
| Annual Sum or Average | 0.291868E+11 | 0.141918E+10 | ||||||||
| Minimum of Months | 0.698627E+09 | 1148.82 | 15.50 | 6.96 | 89738299.13 | 70.31 | 11.50 | 6.79 | ||
| Maximum of Months | 0.392891E+10 | 2839.38 | 39.67 | 20.26 | 0.129276E+09 | 70.37 | 39.67 | 18.94 |
Report: ZoneCoolingSummaryMonthly
For: G NW APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.581735E+09 | 677.80 | 31-JAN-17:02 | 28.33 | 10.54 | 0.101340E+09 | 67.39 | 28-JAN-21:10 | 28.33 | 10.54 |
| February | 0.423373E+09 | 465.49 | 01-FEB-05:00 | 5.00 | 3.59 | 76458165.22 | 60.71 | 01-FEB-00:10 | 5.00 | 3.59 |
| March | 0.482160E+09 | 833.18 | 18-MAR-17:10 | 26.92 | 12.85 | 97144538.37 | 70.39 | 17-MAR-23:10 | 26.92 | 12.85 |
| April | 0.170481E+10 | 1873.80 | 14-APR-17:40 | 34.33 | 14.22 | 0.122664E+09 | 70.38 | 27-APR-01:49 | 14.00 | 8.73 |
| May | 0.240804E+10 | 2028.83 | 31-MAY-18:00 | 36.00 | 13.64 | 0.128703E+09 | 70.36 | 14-MAY-01:00 | 36.00 | 13.64 |
| June | 0.358563E+10 | 2719.53 | 29-JUN-17:50 | 40.00 | 17.94 | 0.124622E+09 | 70.31 | 01-JUN-02:39 | 40.00 | 17.94 |
| July | 0.381738E+10 | 2798.62 | 22-JUL-18:00 | 38.00 | 18.94 | 0.128776E+09 | 70.31 | 03-JUL-00:40 | 38.00 | 18.94 |
| August | 0.367240E+10 | 2622.67 | 13-AUG-17:30 | 38.00 | 19.94 | 0.128776E+09 | 70.31 | 25-AUG-01:19 | 23.00 | 9.55 |
| September | 0.340418E+10 | 2467.48 | 08-SEP-17:00 | 36.60 | 20.88 | 0.124621E+09 | 70.31 | 17-SEP-00:30 | 23.55 | 13.46 |
| October | 0.202326E+10 | 2033.98 | 04-OCT-16:50 | 34.00 | 17.50 | 0.126712E+09 | 70.38 | 28-OCT-22:40 | 14.33 | 7.96 |
| November | 0.981280E+09 | 1462.33 | 01-NOV-16:30 | 27.00 | 15.03 | 0.114657E+09 | 70.36 | 20-NOV-23:40 | 13.33 | 9.01 |
| December | 0.640869E+09 | 603.90 | 25-DEC-16:30 | 25.00 | 11.60 | 95439299.16 | 69.62 | 26-DEC-21:30 | 15.00 | 7.09 |
| Annual Sum or Average | 0.237251E+11 | 0.136991E+10 | ||||||||
| Minimum of Months | 0.423373E+09 | 465.49 | 5.00 | 3.59 | 76458165.22 | 60.71 | 5.00 | 3.59 | ||
| Maximum of Months | 0.381738E+10 | 2798.62 | 40.00 | 20.88 | 0.128776E+09 | 70.39 | 40.00 | 18.94 |
Report: ZoneCoolingSummaryMonthly
For: OFFICE
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.105154E+10 | 6057.53 | 30-JAN-09:02 | 13.33 | 5.50 | 68421427.16 | 166.81 | 17-JAN-09:09 | 13.33 | 5.50 |
| February | 0.458981E+09 | 2743.17 | 01-FEB-09:03 | 9.33 | 5.65 | 63183301.53 | 154.21 | 23-FEB-09:09 | 13.17 | 10.35 |
| March | 0.585914E+09 | 5628.15 | 21-MAR-08:62 | 19.68 | 11.49 | 76334492.38 | 166.81 | 21-MAR-08:09 | 19.68 | 11.49 |
| April | 0.152170E+10 | 6699.47 | 17-APR-07:02 | 17.67 | 10.67 | 70310873.72 | 217.47 | 25-APR-07:10 | 24.17 | 12.52 |
| May | 0.186006E+10 | 6559.74 | 11-MAY-07:02 | 23.17 | 12.09 | 77678124.71 | 217.47 | 08-MAY-07:10 | 23.17 | 12.09 |
| June | 0.245431E+10 | 6449.55 | 12-JUN-07:02 | 24.67 | 12.24 | 77762847.53 | 217.47 | 19-JUN-07:10 | 28.50 | 12.43 |
| July | 0.248855E+10 | 6649.09 | 31-JUL-07:02 | 25.50 | 16.35 | 70698155.71 | 217.47 | 21-JUL-07:10 | 25.50 | 16.35 |
| August | 0.287024E+10 | 6673.23 | 22-AUG-07:02 | 25.33 | 16.30 | 81302868.95 | 217.47 | 14-AUG-07:10 | 25.33 | 16.30 |
| September | 0.254800E+10 | 6815.62 | 27-SEP-07:02 | 20.13 | 13.97 | 70692814.94 | 217.47 | 01-SEP-07:10 | 20.13 | 13.97 |
| October | 0.206097E+10 | 6835.00 | 05-OCT-07:02 | 19.83 | 13.91 | 73812984.47 | 217.70 | 06-OCT-07:10 | 21.50 | 11.93 |
| November | 0.142926E+10 | 6375.17 | 21-NOV-09:02 | 18.33 | 10.28 | 69844212.01 | 202.29 | 01-NOV-07:10 | 18.33 | 10.28 |
| December | 0.100734E+10 | 6293.95 | 26-DEC-09:02 | 13.83 | 6.10 | 67422100.24 | 166.81 | 26-DEC-09:09 | 13.83 | 6.10 |
| Annual Sum or Average | 0.203369E+11 | 0.867464E+09 | ||||||||
| Minimum of Months | 0.458981E+09 | 2743.17 | 9.33 | 5.50 | 63183301.53 | 154.21 | 13.17 | 5.50 | ||
| Maximum of Months | 0.287024E+10 | 6835.00 | 25.50 | 16.35 | 81302868.95 | 217.70 | 28.50 | 16.35 |
Report: ZoneCoolingSummaryMonthly
For: G NE APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.561817E+09 | 474.95 | 31-JAN-17:02 | 28.33 | 10.54 | 0.100680E+09 | 67.00 | 31-JAN-22:10 | 14.48 | 5.13 |
| February | 0.446966E+09 | 465.22 | 01-FEB-05:00 | 5.00 | 3.59 | 76802359.45 | 60.55 | 01-FEB-00:10 | 5.00 | 3.59 |
| March | 0.498320E+09 | 631.90 | 20-MAR-17:05 | 28.53 | 14.26 | 97332513.05 | 70.35 | 20-MAR-22:30 | 18.30 | 10.37 |
| April | 0.173291E+10 | 1499.47 | 14-APR-18:00 | 34.00 | 14.05 | 0.122720E+09 | 70.37 | 02-APR-23:30 | 34.00 | 14.05 |
| May | 0.246465E+10 | 1693.33 | 31-MAY-18:00 | 36.00 | 13.64 | 0.128706E+09 | 70.36 | 27-MAY-05:10 | 36.00 | 13.64 |
| June | 0.363659E+10 | 2389.67 | 30-JUN-17:03 | 39.83 | 17.80 | 0.124622E+09 | 70.31 | 01-JUN-02:39 | 39.83 | 17.80 |
| July | 0.394135E+10 | 2441.11 | 22-JUL-18:00 | 38.00 | 18.94 | 0.128776E+09 | 70.31 | 03-JUL-00:40 | 38.00 | 18.94 |
| August | 0.378689E+10 | 2297.11 | 13-AUG-16:02 | 38.00 | 20.47 | 0.128776E+09 | 70.31 | 25-AUG-01:19 | 23.00 | 9.55 |
| September | 0.346504E+10 | 2171.12 | 08-SEP-16:40 | 37.17 | 20.36 | 0.124621E+09 | 70.31 | 17-SEP-00:30 | 23.55 | 13.46 |
| October | 0.206643E+10 | 1853.50 | 04-OCT-17:00 | 34.00 | 17.45 | 0.126917E+09 | 70.37 | 24-OCT-23:30 | 14.00 | 4.34 |
| November | 0.949853E+09 | 1107.30 | 01-NOV-16:05 | 27.67 | 15.49 | 0.114366E+09 | 70.36 | 16-NOV-21:19 | 13.00 | 10.72 |
| December | 0.645713E+09 | 594.18 | 05-DEC-03:20 | -0.3 | -3.1 | 95352088.84 | 68.67 | 26-DEC-21:30 | 15.00 | 7.09 |
| Annual Sum or Average | 0.241965E+11 | 0.136967E+10 | ||||||||
| Minimum of Months | 0.446966E+09 | 465.22 | -0.3 | -3.1 | 76802359.45 | 60.55 | 5.00 | 3.59 | ||
| Maximum of Months | 0.394135E+10 | 2441.11 | 39.83 | 20.47 | 0.128776E+09 | 70.37 | 39.83 | 18.94 |
Report: ZoneCoolingSummaryMonthly
For: G N1 APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.611066E+09 | 464.39 | 12-JAN-07:00 | 5.00 | 4.49 | 0.107026E+09 | 70.31 | 31-JAN-22:10 | 14.48 | 5.13 |
| February | 0.578001E+09 | 482.40 | 01-FEB-05:00 | 5.00 | 3.59 | 82205824.80 | 64.28 | 01-FEB-00:10 | 5.00 | 3.59 |
| March | 0.611480E+09 | 596.21 | 20-MAR-17:10 | 28.53 | 14.26 | 0.102281E+09 | 70.38 | 21-MAR-23:40 | 17.37 | 10.24 |
| April | 0.143576E+10 | 1206.58 | 14-APR-18:00 | 34.00 | 14.05 | 0.123409E+09 | 70.39 | 02-APR-23:49 | 34.00 | 14.05 |
| May | 0.202226E+10 | 1365.43 | 31-MAY-18:00 | 36.00 | 13.64 | 0.128771E+09 | 70.36 | 01-MAY-03:00 | 36.00 | 13.64 |
| June | 0.283956E+10 | 1831.45 | 30-JUN-17:30 | 39.50 | 17.62 | 0.124622E+09 | 70.32 | 13-JUN-01:39 | 39.50 | 17.62 |
| July | 0.308568E+10 | 1871.18 | 22-JUL-18:00 | 38.00 | 18.94 | 0.128775E+09 | 70.31 | 03-JUL-00:40 | 38.00 | 18.94 |
| August | 0.295937E+10 | 1743.91 | 13-AUG-17:30 | 38.00 | 19.94 | 0.128775E+09 | 70.31 | 25-AUG-01:19 | 23.00 | 9.55 |
| September | 0.277568E+10 | 1651.68 | 08-SEP-17:04 | 36.52 | 20.72 | 0.124621E+09 | 70.31 | 17-SEP-00:30 | 23.55 | 13.46 |
| October | 0.176069E+10 | 1461.86 | 03-OCT-18:00 | 33.00 | 19.20 | 0.127741E+09 | 70.37 | 27-OCT-23:10 | 12.83 | 7.02 |
| November | 0.954499E+09 | 930.60 | 01-NOV-16:20 | 27.33 | 15.26 | 0.117997E+09 | 70.37 | 21-NOV-00:20 | 13.00 | 8.69 |
| December | 0.762809E+09 | 629.54 | 05-DEC-07:00 | -1.0 | -4.2 | 0.100044E+09 | 70.36 | 26-DEC-21:30 | 15.00 | 7.09 |
| Annual Sum or Average | 0.203969E+11 | 0.139627E+10 | ||||||||
| Minimum of Months | 0.578001E+09 | 464.39 | -1.0 | -4.2 | 82205824.80 | 64.28 | 5.00 | 3.59 | ||
| Maximum of Months | 0.308568E+10 | 1871.18 | 39.50 | 20.72 | 0.128775E+09 | 70.39 | 39.50 | 18.94 |
Report: ZoneCoolingSummaryMonthly
For: G N2 APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.611233E+09 | 464.06 | 12-JAN-07:00 | 5.00 | 4.49 | 0.106965E+09 | 70.33 | 31-JAN-22:10 | 14.48 | 5.13 |
| February | 0.579405E+09 | 482.51 | 01-FEB-05:00 | 5.00 | 3.59 | 82337335.30 | 64.32 | 01-FEB-00:10 | 5.00 | 3.59 |
| March | 0.613615E+09 | 597.01 | 20-MAR-17:10 | 28.53 | 14.26 | 0.102380E+09 | 70.39 | 21-MAR-23:30 | 17.45 | 10.36 |
| April | 0.143913E+10 | 1200.87 | 14-APR-18:00 | 34.00 | 14.05 | 0.123416E+09 | 70.38 | 28-APR-04:40 | 13.67 | 6.83 |
| May | 0.202556E+10 | 1360.41 | 31-MAY-18:00 | 36.00 | 13.64 | 0.128771E+09 | 70.36 | 01-MAY-03:00 | 36.00 | 13.64 |
| June | 0.284207E+10 | 1826.93 | 30-JUN-17:30 | 39.50 | 17.62 | 0.124622E+09 | 70.32 | 13-JUN-01:39 | 39.50 | 17.62 |
| July | 0.309081E+10 | 1866.45 | 22-JUL-18:00 | 38.00 | 18.94 | 0.128775E+09 | 70.31 | 03-JUL-00:40 | 38.00 | 18.94 |
| August | 0.296435E+10 | 1739.64 | 13-AUG-17:30 | 38.00 | 19.94 | 0.128775E+09 | 70.31 | 25-AUG-01:19 | 23.00 | 9.55 |
| September | 0.277845E+10 | 1647.70 | 08-SEP-17:04 | 36.52 | 20.72 | 0.124621E+09 | 70.31 | 17-SEP-00:30 | 23.55 | 13.46 |
| October | 0.176444E+10 | 1462.14 | 03-OCT-18:00 | 33.00 | 19.20 | 0.127760E+09 | 70.34 | 30-OCT-23:49 | 12.33 | 5.97 |
| November | 0.954500E+09 | 927.02 | 02-NOV-16:04 | 25.83 | 15.14 | 0.117968E+09 | 70.37 | 04-NOV-22:10 | 10.67 | 5.23 |
| December | 0.764049E+09 | 629.85 | 05-DEC-07:00 | -1.0 | -4.2 | 0.100081E+09 | 70.37 | 26-DEC-21:30 | 15.00 | 7.09 |
| Annual Sum or Average | 0.204276E+11 | 0.139647E+10 | ||||||||
| Minimum of Months | 0.579405E+09 | 464.06 | -1.0 | -4.2 | 82337335.30 | 64.32 | 5.00 | 3.59 | ||
| Maximum of Months | 0.309081E+10 | 1866.45 | 39.50 | 20.72 | 0.128775E+09 | 70.39 | 39.50 | 18.94 |
Report: ZoneCoolingSummaryMonthly
For: G S1 APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.171022E+10 | 1466.14 | 18-JAN-15:10 | 25.00 | 9.93 | 0.124710E+09 | 70.38 | 24-JAN-01:39 | 14.00 | 7.53 |
| February | 0.815882E+09 | 1152.21 | 01-FEB-15:30 | 15.50 | 6.96 | 0.101053E+09 | 70.39 | 21-FEB-21:40 | 14.33 | 12.39 |
| March | 0.927665E+09 | 1191.09 | 18-MAR-16:10 | 27.20 | 11.42 | 0.110982E+09 | 70.37 | 30-MAR-17:40 | 19.97 | 7.22 |
| April | 0.196114E+10 | 1487.84 | 10-APR-16:02 | 32.83 | 14.08 | 0.123423E+09 | 70.39 | 02-APR-02:30 | 32.83 | 14.08 |
| May | 0.213837E+10 | 1403.62 | 20-MAY-14:00 | 36.00 | 13.68 | 0.125724E+09 | 70.32 | 27-MAY-09:39 | 23.67 | 8.62 |
| June | 0.275398E+10 | 1791.67 | 30-JUN-17:04 | 39.83 | 17.80 | 0.120423E+09 | 70.32 | 13-JUN-01:39 | 39.83 | 17.80 |
| July | 0.311671E+10 | 1933.08 | 22-JUL-16:08 | 38.00 | 18.66 | 0.129276E+09 | 70.31 | 03-JUL-00:40 | 38.00 | 18.66 |
| August | 0.323276E+10 | 1983.69 | 13-AUG-16:02 | 38.00 | 20.47 | 0.123964E+09 | 70.31 | 25-AUG-01:19 | 23.00 | 9.55 |
| September | 0.329249E+10 | 1990.78 | 08-SEP-16:08 | 38.02 | 19.47 | 0.123963E+09 | 70.31 | 17-SEP-00:30 | 23.55 | 13.46 |
| October | 0.274482E+10 | 1980.27 | 10-OCT-15:10 | 34.83 | 17.00 | 0.127383E+09 | 70.37 | 30-OCT-06:40 | 9.00 | 5.54 |
| November | 0.201023E+10 | 1830.02 | 01-NOV-16:03 | 27.67 | 15.49 | 0.123085E+09 | 70.37 | 09-NOV-06:40 | 9.67 | 4.00 |
| December | 0.162966E+10 | 1626.22 | 25-DEC-16:10 | 25.67 | 11.87 | 0.121751E+09 | 70.37 | 28-DEC-03:00 | 8.60 | 3.77 |
| Annual Sum or Average | 0.263339E+11 | 0.145574E+10 | ||||||||
| Minimum of Months | 0.815882E+09 | 1152.21 | 15.50 | 6.96 | 0.101053E+09 | 70.31 | 8.60 | 3.77 | ||
| Maximum of Months | 0.329249E+10 | 1990.78 | 39.83 | 20.47 | 0.129276E+09 | 70.39 | 39.83 | 18.66 |
Report: ZoneCoolingSummaryMonthly
For: G S2 APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.178835E+10 | 1537.79 | 29-JAN-16:20 | 24.67 | 9.41 | 0.125042E+09 | 70.37 | 13-JAN-23:00 | 24.67 | 9.41 |
| February | 0.845361E+09 | 1204.75 | 01-FEB-15:30 | 15.50 | 6.96 | 0.102356E+09 | 70.39 | 06-FEB-18:40 | 14.33 | 8.40 |
| March | 0.983294E+09 | 1272.71 | 18-MAR-16:05 | 27.20 | 11.42 | 0.112171E+09 | 70.38 | 10-MAR-20:40 | 27.20 | 11.42 |
| April | 0.216141E+10 | 1565.62 | 10-APR-16:02 | 32.83 | 14.08 | 0.123531E+09 | 70.34 | 02-APR-04:30 | 32.83 | 14.08 |
| May | 0.238914E+10 | 1526.65 | 20-MAY-14:00 | 36.00 | 13.68 | 0.125733E+09 | 70.32 | 27-MAY-09:39 | 23.67 | 8.62 |
| June | 0.305247E+10 | 1879.89 | 30-JUN-17:15 | 39.67 | 17.71 | 0.120423E+09 | 70.31 | 13-JUN-01:39 | 39.67 | 17.71 |
| July | 0.345140E+10 | 2080.54 | 22-JUL-16:08 | 38.00 | 18.66 | 0.129276E+09 | 70.31 | 03-JUL-00:40 | 38.00 | 18.66 |
| August | 0.355292E+10 | 2151.70 | 13-AUG-16:02 | 38.00 | 20.47 | 0.123964E+09 | 70.31 | 25-AUG-01:19 | 23.00 | 9.55 |
| September | 0.361069E+10 | 2092.36 | 10-SEP-16:30 | 34.40 | 19.39 | 0.123963E+09 | 70.31 | 17-SEP-00:30 | 23.55 | 13.46 |
| October | 0.298888E+10 | 2084.94 | 10-OCT-15:10 | 34.83 | 17.00 | 0.127427E+09 | 70.37 | 27-OCT-06:10 | 11.33 | 3.91 |
| November | 0.212710E+10 | 1883.37 | 01-NOV-16:05 | 27.67 | 15.49 | 0.123318E+09 | 70.37 | 26-NOV-02:30 | 11.00 | 4.56 |
| December | 0.170045E+10 | 1714.75 | 25-DEC-16:10 | 25.67 | 11.87 | 0.122346E+09 | 70.37 | 26-DEC-06:49 | 8.17 | 2.88 |
| Annual Sum or Average | 0.286515E+11 | 0.145955E+10 | ||||||||
| Minimum of Months | 0.845361E+09 | 1204.75 | 15.50 | 6.96 | 0.102356E+09 | 70.31 | 8.17 | 2.88 | ||
| Maximum of Months | 0.361069E+10 | 2151.70 | 39.67 | 20.47 | 0.129276E+09 | 70.39 | 39.67 | 18.66 |
Report: ZoneCoolingSummaryMonthly
For: M SW APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.189303E+10 | 2203.03 | 31-JAN-16:30 | 29.00 | 10.73 | 0.119847E+09 | 70.31 | 30-JAN-23:40 | 29.00 | 10.73 |
| February | 0.101564E+10 | 1597.43 | 01-FEB-15:30 | 15.50 | 6.96 | 0.102540E+09 | 70.32 | 15-FEB-21:49 | 15.00 | 12.58 |
| March | 0.136531E+10 | 2255.04 | 18-MAR-16:30 | 27.20 | 12.06 | 0.113554E+09 | 70.32 | 03-MAR-22:00 | 27.20 | 12.06 |
| April | 0.292338E+10 | 2643.43 | 14-APR-17:30 | 34.50 | 14.31 | 0.123531E+09 | 70.32 | 22-APR-01:30 | 13.00 | 2.85 |
| May | 0.331380E+10 | 2629.93 | 19-MAY-17:30 | 34.50 | 13.66 | 0.125720E+09 | 70.32 | 01-MAY-05:10 | 34.50 | 13.66 |
| June | 0.414412E+10 | 3209.14 | 30-JUN-17:17 | 39.67 | 17.71 | 0.120423E+09 | 70.31 | 22-JUN-02:39 | 39.67 | 17.71 |
| July | 0.402482E+10 | 3236.65 | 22-JUL-17:40 | 38.00 | 18.94 | 0.129277E+09 | 70.31 | 03-JUL-00:40 | 38.00 | 18.94 |
| August | 0.391518E+10 | 3165.48 | 13-AUG-16:04 | 38.00 | 20.47 | 0.123964E+09 | 70.31 | 25-AUG-01:19 | 23.00 | 9.55 |
| September | 0.361939E+10 | 2949.17 | 08-SEP-16:10 | 38.02 | 19.47 | 0.123963E+09 | 70.31 | 22-SEP-05:40 | 16.80 | 14.02 |
| October | 0.271632E+10 | 2871.41 | 10-OCT-15:30 | 34.50 | 16.70 | 0.125510E+09 | 70.31 | 26-OCT-22:19 | 12.67 | 4.89 |
| November | 0.177986E+10 | 2659.40 | 01-NOV-16:03 | 27.67 | 15.49 | 0.117163E+09 | 70.32 | 20-NOV-02:00 | 16.00 | 8.15 |
| December | 0.141771E+10 | 2249.93 | 25-DEC-16:20 | 25.33 | 11.74 | 0.110624E+09 | 70.32 | 14-DEC-19:10 | 25.33 | 11.74 |
| Annual Sum or Average | 0.321286E+11 | 0.143611E+10 | ||||||||
| Minimum of Months | 0.101564E+10 | 1597.43 | 15.50 | 6.96 | 0.102540E+09 | 70.31 | 12.67 | 2.85 | ||
| Maximum of Months | 0.414412E+10 | 3236.65 | 39.67 | 20.47 | 0.129277E+09 | 70.32 | 39.67 | 18.94 |
Report: ZoneCoolingSummaryMonthly
For: M NW APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.713921E+09 | 965.53 | 31-JAN-17:04 | 28.33 | 10.54 | 0.107752E+09 | 70.30 | 08-JAN-01:19 | 28.33 | 10.54 |
| February | 0.621261E+09 | 573.86 | 22-FEB-16:30 | 20.50 | 11.47 | 90172050.58 | 70.11 | 18-FEB-21:10 | 20.50 | 11.47 |
| March | 0.909883E+09 | 1525.72 | 18-MAR-17:10 | 26.92 | 12.85 | 0.111831E+09 | 70.32 | 22-MAR-01:19 | 17.00 | 10.28 |
| April | 0.238897E+10 | 2410.25 | 14-APR-17:40 | 34.33 | 14.22 | 0.123893E+09 | 70.31 | 01-APR-22:19 | 34.33 | 14.22 |
| May | 0.320287E+10 | 2619.03 | 31-MAY-18:00 | 36.00 | 13.64 | 0.128766E+09 | 70.32 | 27-MAY-05:49 | 36.00 | 13.64 |
| June | 0.423409E+10 | 3263.80 | 29-JUN-18:00 | 40.00 | 17.88 | 0.124622E+09 | 70.31 | 22-JUN-02:39 | 40.00 | 17.88 |
| July | 0.399115E+10 | 3191.23 | 22-JUL-18:00 | 38.00 | 18.94 | 0.128776E+09 | 70.31 | 03-JUL-00:40 | 38.00 | 18.94 |
| August | 0.363445E+10 | 2865.96 | 13-AUG-17:30 | 38.00 | 19.94 | 0.128776E+09 | 70.31 | 27-AUG-02:39 | 23.33 | 10.07 |
| September | 0.309169E+10 | 2565.87 | 08-SEP-16:40 | 37.17 | 20.36 | 0.124620E+09 | 70.30 | 17-SEP-00:30 | 23.55 | 13.46 |
| October | 0.175619E+10 | 2117.18 | 05-OCT-16:50 | 34.00 | 14.97 | 0.124320E+09 | 70.32 | 29-OCT-21:00 | 15.00 | 8.32 |
| November | 0.824836E+09 | 1612.99 | 01-NOV-16:30 | 27.00 | 15.03 | 0.108952E+09 | 70.30 | 15-NOV-21:00 | 12.00 | 11.44 |
| December | 0.552154E+09 | 673.91 | 25-DEC-16:30 | 25.00 | 11.60 | 93004684.05 | 69.17 | 26-DEC-21:19 | 15.00 | 7.02 |
| Annual Sum or Average | 0.259215E+11 | 0.139549E+10 | ||||||||
| Minimum of Months | 0.552154E+09 | 573.86 | 20.50 | 10.54 | 90172050.58 | 69.17 | 12.00 | 7.02 | ||
| Maximum of Months | 0.423409E+10 | 3263.80 | 40.00 | 20.36 | 0.128776E+09 | 70.32 | 40.00 | 18.94 |
Report: ZoneCoolingSummaryMonthly
For: M SE APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.187121E+10 | 1867.45 | 17-JAN-14:30 | 24.50 | 9.15 | 0.119686E+09 | 70.32 | 12-JAN-21:40 | 24.50 | 9.15 |
| February | 0.105292E+10 | 1354.37 | 01-FEB-14:30 | 15.50 | 7.30 | 0.102793E+09 | 70.32 | 13-FEB-19:10 | 12.92 | 10.73 |
| March | 0.139069E+10 | 1878.57 | 18-MAR-15:10 | 27.20 | 12.30 | 0.113800E+09 | 70.32 | 18-MAR-02:09 | 27.20 | 12.30 |
| April | 0.296612E+10 | 2297.24 | 10-APR-16:02 | 32.83 | 14.08 | 0.123541E+09 | 70.31 | 20-APR-04:40 | 13.00 | 5.28 |
| May | 0.337753E+10 | 2463.05 | 20-MAY-14:00 | 36.00 | 13.68 | 0.125728E+09 | 70.31 | 25-MAY-01:39 | 23.33 | 9.59 |
| June | 0.420028E+10 | 2848.84 | 30-JUN-16:03 | 40.83 | 17.99 | 0.120423E+09 | 70.31 | 13-JUN-01:39 | 40.83 | 17.99 |
| July | 0.415842E+10 | 2871.64 | 22-JUL-16:08 | 38.00 | 18.66 | 0.129276E+09 | 70.31 | 03-JUL-00:40 | 38.00 | 18.66 |
| August | 0.403703E+10 | 2785.77 | 13-AUG-16:08 | 38.00 | 20.47 | 0.123964E+09 | 70.31 | 25-AUG-01:19 | 23.00 | 9.55 |
| September | 0.368451E+10 | 2607.42 | 18-SEP-12:00 | 34.40 | 14.98 | 0.123963E+09 | 70.31 | 22-SEP-05:40 | 16.80 | 14.02 |
| October | 0.277076E+10 | 2555.53 | 10-OCT-15:10 | 34.83 | 17.00 | 0.125545E+09 | 70.32 | 09-OCT-04:49 | 34.83 | 17.00 |
| November | 0.174988E+10 | 2154.78 | 01-NOV-15:20 | 28.67 | 16.04 | 0.117075E+09 | 70.32 | 16-NOV-23:10 | 12.00 | 10.68 |
| December | 0.142024E+10 | 1823.38 | 25-DEC-14:00 | 26.00 | 12.00 | 0.110837E+09 | 70.30 | 30-DEC-21:19 | 10.33 | 4.50 |
| Annual Sum or Average | 0.326796E+11 | 0.143663E+10 | ||||||||
| Minimum of Months | 0.105292E+10 | 1354.37 | 15.50 | 7.30 | 0.102793E+09 | 70.30 | 10.33 | 4.50 | ||
| Maximum of Months | 0.420028E+10 | 2871.64 | 40.83 | 20.47 | 0.129276E+09 | 70.32 | 40.83 | 18.66 |
Report: ZoneCoolingSummaryMonthly
For: M NE APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.680812E+09 | 677.74 | 27-JAN-17:05 | 25.50 | 9.05 | 0.107251E+09 | 70.31 | 28-JAN-21:10 | 13.67 | 5.37 |
| February | 0.630579E+09 | 472.52 | 01-FEB-05:00 | 5.00 | 3.59 | 91087734.37 | 70.27 | 18-FEB-21:10 | 13.83 | 12.84 |
| March | 0.924133E+09 | 1149.63 | 16-MAR-16:08 | 28.72 | 13.89 | 0.112195E+09 | 70.31 | 17-MAR-03:20 | 16.07 | 10.78 |
| April | 0.243029E+10 | 1903.02 | 30-APR-16:08 | 32.83 | 11.93 | 0.123903E+09 | 70.32 | 20-APR-02:09 | 32.83 | 11.93 |
| May | 0.326690E+10 | 2198.57 | 20-MAY-14:00 | 36.00 | 13.68 | 0.128766E+09 | 70.31 | 01-MAY-03:39 | 36.00 | 13.68 |
| June | 0.429066E+10 | 2823.91 | 30-JUN-16:17 | 40.67 | 17.97 | 0.124622E+09 | 70.31 | 13-JUN-01:39 | 40.67 | 17.97 |
| July | 0.412494E+10 | 2692.72 | 22-JUL-16:05 | 38.00 | 18.66 | 0.128776E+09 | 70.31 | 03-JUL-00:40 | 38.00 | 18.66 |
| August | 0.375599E+10 | 2472.55 | 13-AUG-16:04 | 38.00 | 20.47 | 0.128776E+09 | 70.31 | 25-AUG-01:19 | 23.00 | 9.55 |
| September | 0.315611E+10 | 2183.73 | 08-SEP-16:17 | 37.73 | 19.78 | 0.124620E+09 | 70.30 | 17-SEP-00:30 | 23.55 | 13.46 |
| October | 0.179308E+10 | 1848.41 | 04-OCT-17:00 | 34.00 | 17.45 | 0.124606E+09 | 70.32 | 08-OCT-03:39 | 13.47 | 7.97 |
| November | 0.787742E+09 | 1126.30 | 01-NOV-16:07 | 27.67 | 15.49 | 0.108607E+09 | 70.30 | 01-NOV-05:49 | 27.67 | 15.49 |
| December | 0.558327E+09 | 513.93 | 04-DEC-07:20 | 3.00 | 0.78 | 92791909.72 | 68.01 | 26-DEC-21:19 | 15.00 | 7.02 |
| Annual Sum or Average | 0.263996E+11 | 0.139600E+10 | ||||||||
| Minimum of Months | 0.558327E+09 | 472.52 | 3.00 | 0.78 | 91087734.37 | 68.01 | 13.47 | 5.37 | ||
| Maximum of Months | 0.429066E+10 | 2823.91 | 40.67 | 20.47 | 0.128776E+09 | 70.32 | 40.67 | 18.66 |
Report: ZoneCoolingSummaryMonthly
For: M N1 APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.749935E+09 | 652.90 | 27-JAN-17:03 | 25.50 | 9.05 | 0.114411E+09 | 70.30 | 20-JAN-22:19 | 25.50 | 9.05 |
| February | 0.687812E+09 | 513.13 | 18-FEB-18:40 | 15.33 | 14.51 | 99312407.71 | 70.29 | 16-FEB-21:00 | 15.33 | 14.51 |
| March | 0.937817E+09 | 974.60 | 20-MAR-17:05 | 28.53 | 14.26 | 0.117918E+09 | 70.31 | 16-MAR-02:00 | 28.53 | 14.26 |
| April | 0.191239E+10 | 1453.61 | 14-APR-18:00 | 34.00 | 14.05 | 0.124305E+09 | 70.32 | 27-APR-05:49 | 12.00 | 7.47 |
| May | 0.250808E+10 | 1656.07 | 31-MAY-18:00 | 36.00 | 13.64 | 0.128776E+09 | 70.31 | 25-MAY-01:39 | 36.00 | 13.64 |
| June | 0.317759E+10 | 2053.84 | 30-JUN-18:00 | 39.00 | 17.36 | 0.124622E+09 | 70.31 | 13-JUN-01:39 | 39.00 | 17.36 |
| July | 0.311802E+10 | 1997.79 | 22-JUL-18:00 | 38.00 | 18.94 | 0.128776E+09 | 70.31 | 03-JUL-00:40 | 38.00 | 18.94 |
| August | 0.286019E+10 | 1777.92 | 13-AUG-16:08 | 38.00 | 20.47 | 0.128775E+09 | 70.31 | 25-AUG-01:19 | 23.00 | 9.55 |
| September | 0.251626E+10 | 1608.41 | 08-SEP-16:30 | 37.45 | 20.08 | 0.124621E+09 | 70.31 | 17-SEP-00:30 | 23.55 | 13.46 |
| October | 0.155762E+10 | 1427.37 | 03-OCT-18:00 | 33.00 | 19.20 | 0.126624E+09 | 70.32 | 14-OCT-02:30 | 16.50 | 4.99 |
| November | 0.859113E+09 | 959.65 | 01-NOV-16:17 | 27.33 | 15.26 | 0.114708E+09 | 70.32 | 07-NOV-21:40 | 13.33 | 5.84 |
| December | 0.721330E+09 | 619.39 | 05-DEC-04:00 | -1.0 | -3.7 | 99496389.77 | 70.27 | 26-DEC-21:00 | 15.00 | 7.29 |
| Annual Sum or Average | 0.216062E+11 | 0.143235E+10 | ||||||||
| Minimum of Months | 0.687812E+09 | 513.13 | -1.0 | -3.7 | 99312407.71 | 70.27 | 12.00 | 4.99 | ||
| Maximum of Months | 0.317759E+10 | 2053.84 | 39.00 | 20.47 | 0.128776E+09 | 70.32 | 39.00 | 18.94 |
Report: ZoneCoolingSummaryMonthly
For: M N2 APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.750470E+09 | 652.60 | 27-JAN-17:03 | 25.50 | 9.05 | 0.114379E+09 | 70.32 | 19-JAN-22:49 | 25.50 | 9.05 |
| February | 0.690382E+09 | 535.79 | 18-FEB-18:40 | 15.33 | 14.51 | 99513311.83 | 70.27 | 17-FEB-22:40 | 15.33 | 14.51 |
| March | 0.941670E+09 | 974.53 | 20-MAR-17:05 | 28.53 | 14.26 | 0.118021E+09 | 70.32 | 24-MAR-20:49 | 12.80 | 5.42 |
| April | 0.191572E+10 | 1445.88 | 14-APR-18:00 | 34.00 | 14.05 | 0.124309E+09 | 70.32 | 27-APR-04:49 | 12.17 | 7.90 |
| May | 0.251109E+10 | 1649.55 | 31-MAY-18:00 | 36.00 | 13.64 | 0.128776E+09 | 70.31 | 25-MAY-01:39 | 36.00 | 13.64 |
| June | 0.317998E+10 | 2047.28 | 30-JUN-18:00 | 39.00 | 17.36 | 0.124622E+09 | 70.31 | 13-JUN-01:39 | 39.00 | 17.36 |
| July | 0.312281E+10 | 1990.90 | 22-JUL-18:00 | 38.00 | 18.94 | 0.128776E+09 | 70.31 | 03-JUL-00:40 | 38.00 | 18.94 |
| August | 0.286485E+10 | 1775.84 | 13-AUG-16:08 | 38.00 | 20.47 | 0.128775E+09 | 70.31 | 25-AUG-01:19 | 23.00 | 9.55 |
| September | 0.251892E+10 | 1604.96 | 08-SEP-16:30 | 37.45 | 20.08 | 0.124621E+09 | 70.31 | 17-SEP-00:30 | 23.55 | 13.46 |
| October | 0.156178E+10 | 1427.11 | 03-OCT-18:00 | 33.00 | 19.20 | 0.126665E+09 | 70.32 | 14-OCT-02:49 | 16.17 | 4.79 |
| November | 0.859696E+09 | 954.11 | 01-NOV-16:17 | 27.33 | 15.26 | 0.114677E+09 | 70.32 | 11-NOV-02:39 | 15.73 | 12.81 |
| December | 0.722662E+09 | 619.74 | 05-DEC-04:00 | -1.0 | -3.7 | 99520747.48 | 70.27 | 26-DEC-21:00 | 15.00 | 7.29 |
| Annual Sum or Average | 0.216400E+11 | 0.143266E+10 | ||||||||
| Minimum of Months | 0.690382E+09 | 535.79 | -1.0 | -3.7 | 99513311.83 | 70.27 | 12.17 | 4.79 | ||
| Maximum of Months | 0.317998E+10 | 2047.28 | 39.00 | 20.47 | 0.128776E+09 | 70.32 | 39.00 | 18.94 |
Report: ZoneCoolingSummaryMonthly
For: M S1 APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.207958E+10 | 1857.18 | 18-JAN-14:30 | 24.50 | 9.73 | 0.125518E+09 | 70.32 | 30-JAN-00:00 | 9.00 | 3.01 |
| February | 0.121886E+10 | 1483.22 | 01-FEB-15:30 | 15.50 | 6.96 | 0.110168E+09 | 70.32 | 10-FEB-19:10 | 13.00 | 11.33 |
| March | 0.144905E+10 | 1688.08 | 18-MAR-16:10 | 27.20 | 11.42 | 0.118815E+09 | 70.32 | 29-MAR-20:00 | 12.20 | 4.35 |
| April | 0.245427E+10 | 1821.60 | 10-APR-16:03 | 32.83 | 14.08 | 0.123866E+09 | 70.31 | 23-APR-08:39 | 24.00 | 8.96 |
| May | 0.261961E+10 | 1749.02 | 20-MAY-14:00 | 36.00 | 13.68 | 0.125731E+09 | 70.31 | 27-MAY-09:39 | 23.67 | 8.62 |
| June | 0.308723E+10 | 2032.32 | 30-JUN-16:01 | 40.83 | 17.99 | 0.120423E+09 | 70.31 | 13-JUN-01:39 | 40.83 | 17.99 |
| July | 0.315148E+10 | 2100.95 | 22-JUL-16:05 | 38.00 | 18.66 | 0.129276E+09 | 70.31 | 03-JUL-00:40 | 38.00 | 18.66 |
| August | 0.314195E+10 | 2089.19 | 13-AUG-16:04 | 38.00 | 20.47 | 0.123964E+09 | 70.31 | 25-AUG-01:19 | 23.00 | 9.55 |
| September | 0.304736E+10 | 2000.62 | 08-SEP-16:10 | 38.02 | 19.47 | 0.123963E+09 | 70.30 | 17-SEP-00:30 | 23.55 | 13.46 |
| October | 0.257072E+10 | 2115.58 | 10-OCT-15:10 | 34.83 | 17.00 | 0.126886E+09 | 70.31 | 27-OCT-01:10 | 13.83 | 5.43 |
| November | 0.193020E+10 | 1994.53 | 20-NOV-14:30 | 27.00 | 11.68 | 0.121384E+09 | 70.32 | 03-NOV-23:49 | 27.00 | 11.68 |
| December | 0.168959E+10 | 1851.89 | 25-DEC-16:10 | 25.67 | 11.87 | 0.119802E+09 | 70.32 | 20-DEC-21:40 | 25.67 | 11.87 |
| Annual Sum or Average | 0.284399E+11 | 0.146980E+10 | ||||||||
| Minimum of Months | 0.121886E+10 | 1483.22 | 15.50 | 6.96 | 0.110168E+09 | 70.30 | 9.00 | 3.01 | ||
| Maximum of Months | 0.315148E+10 | 2115.58 | 40.83 | 20.47 | 0.129276E+09 | 70.32 | 40.83 | 18.66 |
Report: ZoneCoolingSummaryMonthly
For: M S2 APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.208055E+10 | 1858.96 | 18-JAN-14:30 | 24.50 | 9.73 | 0.125501E+09 | 70.32 | 03-JAN-22:00 | 24.50 | 9.73 |
| February | 0.122433E+10 | 1483.21 | 01-FEB-15:30 | 15.50 | 6.96 | 0.110184E+09 | 70.32 | 05-FEB-21:40 | 10.33 | 7.18 |
| March | 0.145455E+10 | 1685.39 | 18-MAR-16:10 | 27.20 | 11.42 | 0.118841E+09 | 70.31 | 22-MAR-04:10 | 12.43 | 8.74 |
| April | 0.245708E+10 | 1821.48 | 10-APR-16:03 | 32.83 | 14.08 | 0.123867E+09 | 70.32 | 16-APR-06:10 | 16.17 | 11.44 |
| May | 0.262268E+10 | 1754.34 | 20-MAY-14:00 | 36.00 | 13.68 | 0.125731E+09 | 70.31 | 27-MAY-09:39 | 23.67 | 8.62 |
| June | 0.308968E+10 | 2029.93 | 30-JUN-16:01 | 40.83 | 17.99 | 0.120423E+09 | 70.31 | 13-JUN-01:39 | 40.83 | 17.99 |
| July | 0.315630E+10 | 2099.00 | 22-JUL-16:05 | 38.00 | 18.66 | 0.129276E+09 | 70.31 | 03-JUL-00:40 | 38.00 | 18.66 |
| August | 0.314658E+10 | 2086.90 | 13-AUG-16:04 | 38.00 | 20.47 | 0.123964E+09 | 70.31 | 25-AUG-01:19 | 23.00 | 9.55 |
| September | 0.304993E+10 | 2001.33 | 28-SEP-14:10 | 37.28 | 16.00 | 0.123963E+09 | 70.30 | 17-SEP-00:30 | 37.28 | 16.00 |
| October | 0.257431E+10 | 2115.10 | 10-OCT-15:10 | 34.83 | 17.00 | 0.126888E+09 | 70.32 | 27-OCT-01:10 | 13.83 | 5.43 |
| November | 0.193049E+10 | 1995.97 | 20-NOV-14:30 | 27.00 | 11.68 | 0.121371E+09 | 70.32 | 03-NOV-23:49 | 27.00 | 11.68 |
| December | 0.169348E+10 | 1850.81 | 25-DEC-14:00 | 26.00 | 12.00 | 0.119821E+09 | 70.31 | 18-DEC-20:40 | 26.00 | 12.00 |
| Annual Sum or Average | 0.284800E+11 | 0.146983E+10 | ||||||||
| Minimum of Months | 0.122433E+10 | 1483.21 | 15.50 | 6.96 | 0.110184E+09 | 70.30 | 10.33 | 5.43 | ||
| Maximum of Months | 0.315630E+10 | 2115.10 | 40.83 | 20.47 | 0.129276E+09 | 70.32 | 40.83 | 18.66 |
Report: ZoneCoolingSummaryMonthly
For: T SW APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.145460E+10 | 2687.86 | 24-JAN-16:20 | 24.67 | 10.78 | 0.100742E+09 | 70.38 | 08-JAN-00:20 | 24.67 | 10.78 |
| February | 0.611457E+09 | 1824.24 | 28-FEB-16:30 | 19.00 | 8.96 | 81897117.17 | 70.34 | 24-FEB-19:40 | 19.00 | 8.96 |
| March | 0.106687E+10 | 2901.29 | 18-MAR-16:20 | 27.20 | 11.74 | 97700779.92 | 70.35 | 03-MAR-18:49 | 27.20 | 11.74 |
| April | 0.309074E+10 | 3621.56 | 14-APR-17:30 | 34.50 | 14.31 | 0.117984E+09 | 70.37 | 18-APR-00:00 | 16.00 | 8.83 |
| May | 0.366961E+10 | 3661.90 | 20-MAY-16:30 | 34.50 | 14.34 | 0.123881E+09 | 70.36 | 04-MAY-03:09 | 34.50 | 14.34 |
| June | 0.499125E+10 | 4484.68 | 30-JUN-16:03 | 40.83 | 17.99 | 0.120413E+09 | 70.32 | 07-JUN-06:40 | 40.83 | 17.99 |
| July | 0.482334E+10 | 4483.60 | 22-JUL-16:04 | 38.00 | 18.66 | 0.129263E+09 | 70.31 | 05-JUL-02:39 | 38.00 | 18.66 |
| August | 0.459301E+10 | 4417.60 | 13-AUG-16:02 | 38.00 | 20.47 | 0.123951E+09 | 70.32 | 27-AUG-02:39 | 23.33 | 10.07 |
| September | 0.406282E+10 | 4102.65 | 08-SEP-16:01 | 38.02 | 19.47 | 0.123792E+09 | 70.31 | 17-SEP-00:30 | 23.55 | 13.46 |
| October | 0.257383E+10 | 3863.87 | 10-OCT-15:30 | 34.50 | 16.70 | 0.115657E+09 | 70.37 | 23-OCT-22:19 | 16.00 | 10.88 |
| November | 0.135110E+10 | 3457.96 | 01-NOV-16:02 | 27.67 | 15.49 | 99251743.49 | 70.38 | 03-NOV-19:00 | 14.00 | 9.20 |
| December | 0.935065E+09 | 2686.65 | 25-DEC-16:20 | 25.33 | 11.74 | 93607096.69 | 70.37 | 11-DEC-18:00 | 25.33 | 11.74 |
| Annual Sum or Average | 0.332237E+11 | 0.132814E+10 | ||||||||
| Minimum of Months | 0.611457E+09 | 1824.24 | 19.00 | 8.96 | 81897117.17 | 70.31 | 14.00 | 8.83 | ||
| Maximum of Months | 0.499125E+10 | 4484.68 | 40.83 | 20.47 | 0.129263E+09 | 70.38 | 40.83 | 18.66 |
Report: ZoneCoolingSummaryMonthly
For: T NW APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.380065E+09 | 1210.38 | 31-JAN-17:02 | 28.33 | 10.54 | 93072310.69 | 66.32 | 07-JAN-22:49 | 28.33 | 10.54 |
| February | 0.232966E+09 | 611.72 | 22-FEB-16:30 | 20.50 | 11.47 | 76781937.08 | 62.45 | 21-FEB-21:10 | 20.50 | 11.47 |
| March | 0.637741E+09 | 1922.26 | 18-MAR-17:00 | 27.20 | 12.99 | 97996238.43 | 70.35 | 23-MAR-20:10 | 15.92 | 7.66 |
| April | 0.252764E+10 | 3320.71 | 14-APR-17:30 | 34.50 | 14.31 | 0.118262E+09 | 70.38 | 28-APR-00:10 | 17.67 | 9.27 |
| May | 0.354360E+10 | 3579.19 | 15-MAY-17:30 | 36.00 | 15.07 | 0.127160E+09 | 70.38 | 30-MAY-04:40 | 18.00 | 8.82 |
| June | 0.508485E+10 | 4485.20 | 29-JUN-17:30 | 40.00 | 18.08 | 0.124620E+09 | 70.32 | 22-JUN-03:20 | 40.00 | 18.08 |
| July | 0.477951E+10 | 4326.92 | 22-JUL-18:00 | 38.00 | 18.94 | 0.128769E+09 | 70.31 | 05-JUL-02:39 | 38.00 | 18.94 |
| August | 0.427632E+10 | 4003.56 | 13-AUG-16:30 | 38.00 | 20.26 | 0.128767E+09 | 70.32 | 27-AUG-02:39 | 23.33 | 10.07 |
| September | 0.348318E+10 | 3591.40 | 08-SEP-16:30 | 37.45 | 20.08 | 0.124448E+09 | 70.37 | 16-SEP-03:00 | 19.40 | 12.33 |
| October | 0.161968E+10 | 2912.98 | 05-OCT-16:30 | 34.00 | 14.87 | 0.113557E+09 | 70.38 | 19-OCT-23:40 | 17.00 | 10.47 |
| November | 0.491101E+09 | 2133.58 | 01-NOV-16:20 | 27.33 | 15.26 | 93568761.13 | 70.27 | 01-NOV-20:10 | 20.50 | 13.68 |
| December | 0.210331E+09 | 925.61 | 22-DEC-16:30 | 24.50 | 9.81 | 84965064.39 | 63.05 | 22-DEC-21:10 | 13.67 | 5.30 |
| Annual Sum or Average | 0.272670E+11 | 0.131197E+10 | ||||||||
| Minimum of Months | 0.210331E+09 | 611.72 | 20.50 | 9.81 | 76781937.08 | 62.45 | 13.67 | 5.30 | ||
| Maximum of Months | 0.508485E+10 | 4485.20 | 40.00 | 20.26 | 0.128769E+09 | 70.38 | 40.00 | 18.94 |
Report: ZoneCoolingSummaryMonthly
For: T SE APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.140163E+10 | 2220.99 | 24-JAN-15:10 | 25.83 | 10.68 | 0.100706E+09 | 70.37 | 05-JAN-20:00 | 25.83 | 10.68 |
| February | 0.629846E+09 | 1501.02 | 23-FEB-14:00 | 18.00 | 10.78 | 82016791.59 | 70.37 | 08-FEB-18:10 | 18.00 | 10.78 |
| March | 0.106591E+10 | 2416.60 | 18-MAR-15:20 | 27.20 | 12.06 | 97674682.99 | 70.38 | 03-MAR-18:49 | 27.20 | 12.06 |
| April | 0.311473E+10 | 3121.46 | 30-APR-15:10 | 33.00 | 11.94 | 0.118105E+09 | 70.37 | 05-APR-02:49 | 33.00 | 11.94 |
| May | 0.373221E+10 | 3450.99 | 20-MAY-14:00 | 36.00 | 13.68 | 0.124047E+09 | 70.37 | 18-MAY-04:49 | 36.00 | 13.68 |
| June | 0.505642E+10 | 3991.25 | 30-JUN-16:03 | 40.83 | 17.99 | 0.120416E+09 | 70.32 | 22-JUN-03:20 | 40.83 | 17.99 |
| July | 0.497238E+10 | 3949.61 | 22-JUL-16:04 | 38.00 | 18.66 | 0.129267E+09 | 70.31 | 03-JUL-00:40 | 38.00 | 18.66 |
| August | 0.472636E+10 | 3846.24 | 13-AUG-16:08 | 38.00 | 20.47 | 0.123954E+09 | 70.32 | 27-AUG-02:39 | 23.33 | 10.07 |
| September | 0.413244E+10 | 3566.26 | 09-SEP-13:00 | 36.10 | 20.26 | 0.123796E+09 | 70.31 | 27-SEP-05:00 | 20.00 | 13.98 |
| October | 0.260836E+10 | 3483.91 | 02-OCT-13:50 | 34.83 | 19.72 | 0.115649E+09 | 70.36 | 08-OCT-23:19 | 16.67 | 8.45 |
| November | 0.130354E+10 | 2816.29 | 01-NOV-15:20 | 28.67 | 16.04 | 98739937.13 | 70.37 | 01-NOV-23:19 | 15.67 | 12.32 |
| December | 0.917806E+09 | 2106.94 | 25-DEC-14:20 | 26.00 | 11.85 | 93592893.99 | 70.36 | 26-DEC-20:30 | 16.00 | 7.54 |
| Annual Sum or Average | 0.336616E+11 | 0.132797E+10 | ||||||||
| Minimum of Months | 0.629846E+09 | 1501.02 | 18.00 | 10.68 | 82016791.59 | 70.31 | 15.67 | 7.54 | ||
| Maximum of Months | 0.505642E+10 | 3991.25 | 40.83 | 20.47 | 0.129267E+09 | 70.38 | 40.83 | 18.66 |
Report: ZoneCoolingSummaryMonthly
For: T NE APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.327381E+09 | 747.60 | 31-JAN-17:02 | 28.33 | 10.54 | 92168942.47 | 64.60 | 27-JAN-21:10 | 28.33 | 10.54 |
| February | 0.248857E+09 | 317.23 | 13-FEB-22:25 | 9.50 | 9.50 | 76399713.08 | 61.76 | 21-FEB-21:10 | 14.83 | 11.70 |
| March | 0.628364E+09 | 1470.45 | 16-MAR-16:10 | 28.72 | 13.89 | 97846023.44 | 70.38 | 16-MAR-23:40 | 17.33 | 11.44 |
| April | 0.254598E+10 | 2576.46 | 30-APR-15:10 | 33.00 | 11.94 | 0.118371E+09 | 70.37 | 16-APR-01:49 | 33.00 | 11.94 |
| May | 0.360934E+10 | 3078.00 | 20-MAY-14:00 | 36.00 | 13.68 | 0.127232E+09 | 70.37 | 05-MAY-03:30 | 36.00 | 13.68 |
| June | 0.515155E+10 | 3921.53 | 30-JUN-16:10 | 40.83 | 17.99 | 0.124620E+09 | 70.32 | 22-JUN-03:20 | 40.83 | 17.99 |
| July | 0.492925E+10 | 3695.84 | 22-JUL-16:10 | 38.00 | 18.66 | 0.128770E+09 | 70.32 | 02-JUL-05:10 | 38.00 | 18.66 |
| August | 0.440949E+10 | 3430.67 | 13-AUG-16:02 | 38.00 | 20.47 | 0.128767E+09 | 70.32 | 27-AUG-02:39 | 23.33 | 10.07 |
| September | 0.355154E+10 | 3024.91 | 08-SEP-16:01 | 38.02 | 19.47 | 0.124461E+09 | 70.38 | 16-SEP-04:40 | 19.80 | 12.45 |
| October | 0.163745E+10 | 2585.87 | 02-OCT-14:00 | 35.00 | 19.78 | 0.113556E+09 | 70.36 | 06-OCT-03:09 | 19.17 | 10.43 |
| November | 0.444082E+09 | 1450.45 | 01-NOV-16:03 | 27.67 | 15.49 | 92523906.27 | 70.32 | 03-NOV-00:20 | 18.33 | 15.35 |
| December | 0.190898E+09 | 427.97 | 25-DEC-16:10 | 25.67 | 11.87 | 84244828.46 | 61.14 | 22-DEC-18:10 | 25.67 | 11.87 |
| Annual Sum or Average | 0.276742E+11 | 0.130896E+10 | ||||||||
| Minimum of Months | 0.190898E+09 | 317.23 | 9.50 | 9.50 | 76399713.08 | 61.14 | 14.83 | 10.07 | ||
| Maximum of Months | 0.515155E+10 | 3921.53 | 40.83 | 20.47 | 0.128770E+09 | 70.38 | 40.83 | 18.66 |
Report: ZoneCoolingSummaryMonthly
For: T N1 APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.347961E+09 | 570.42 | 31-JAN-17:08 | 28.33 | 10.54 | 94308903.50 | 68.22 | 07-JAN-23:10 | 28.33 | 10.54 |
| February | 0.313017E+09 | 342.85 | 01-FEB-02:50 | 8.52 | 6.82 | 77900028.71 | 63.35 | 21-FEB-21:10 | 14.83 | 11.70 |
| March | 0.588842E+09 | 1204.29 | 16-MAR-16:12 | 28.63 | 13.84 | 0.100458E+09 | 70.35 | 21-MAR-23:10 | 17.62 | 10.58 |
| April | 0.195807E+10 | 2041.64 | 25-APR-16:17 | 33.00 | 15.00 | 0.120198E+09 | 70.38 | 16-APR-03:30 | 33.00 | 15.00 |
| May | 0.276993E+10 | 2303.80 | 31-MAY-18:00 | 36.00 | 13.64 | 0.127901E+09 | 70.37 | 13-MAY-02:39 | 36.00 | 13.64 |
| June | 0.392226E+10 | 2964.99 | 30-JUN-16:20 | 40.67 | 17.97 | 0.124622E+09 | 70.32 | 22-JUN-03:20 | 40.67 | 17.97 |
| July | 0.382103E+10 | 2802.38 | 22-JUL-18:00 | 38.00 | 18.94 | 0.128775E+09 | 70.35 | 02-JUL-05:49 | 38.00 | 18.94 |
| August | 0.343065E+10 | 2619.54 | 13-AUG-16:02 | 38.00 | 20.47 | 0.128776E+09 | 70.32 | 27-AUG-02:39 | 23.33 | 10.07 |
| September | 0.285275E+10 | 2352.74 | 08-SEP-16:17 | 37.73 | 19.78 | 0.124558E+09 | 70.31 | 17-SEP-00:30 | 23.55 | 13.46 |
| October | 0.134641E+10 | 1941.65 | 02-OCT-14:00 | 35.00 | 19.78 | 0.115863E+09 | 70.38 | 31-OCT-20:30 | 18.00 | 8.97 |
| November | 0.446856E+09 | 1236.81 | 01-NOV-16:07 | 27.67 | 15.49 | 95758748.54 | 70.31 | 03-NOV-01:10 | 17.00 | 14.34 |
| December | 0.230496E+09 | 363.29 | 13-DEC-21:00 | 8.00 | 3.84 | 85303973.35 | 63.62 | 22-DEC-21:10 | 13.67 | 5.30 |
| Annual Sum or Average | 0.220283E+11 | 0.132442E+10 | ||||||||
| Minimum of Months | 0.230496E+09 | 342.85 | 8.00 | 3.84 | 77900028.71 | 63.35 | 13.67 | 5.30 | ||
| Maximum of Months | 0.392226E+10 | 2964.99 | 40.67 | 20.47 | 0.128776E+09 | 70.38 | 40.67 | 18.94 |
Report: ZoneCoolingSummaryMonthly
For: T N2 APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.348538E+09 | 564.70 | 31-JAN-17:08 | 28.33 | 10.54 | 94231836.91 | 68.05 | 07-JAN-23:10 | 28.33 | 10.54 |
| February | 0.314177E+09 | 342.67 | 01-FEB-02:50 | 8.52 | 6.82 | 77931746.89 | 63.59 | 18-FEB-21:10 | 13.83 | 12.84 |
| March | 0.592434E+09 | 1200.08 | 16-MAR-16:14 | 28.63 | 13.84 | 0.100482E+09 | 70.36 | 21-MAR-23:10 | 17.62 | 10.58 |
| April | 0.196431E+10 | 2030.59 | 25-APR-16:02 | 33.00 | 14.90 | 0.120181E+09 | 70.38 | 06-APR-04:10 | 33.00 | 14.90 |
| May | 0.277512E+10 | 2285.97 | 31-MAY-18:00 | 36.00 | 13.64 | 0.127892E+09 | 70.37 | 19-MAY-04:00 | 36.00 | 13.64 |
| June | 0.392584E+10 | 2955.65 | 30-JUN-16:20 | 40.67 | 17.97 | 0.124622E+09 | 70.32 | 22-JUN-03:20 | 40.67 | 17.97 |
| July | 0.382721E+10 | 2789.46 | 22-JUL-16:01 | 38.00 | 18.66 | 0.128775E+09 | 70.32 | 02-JUL-05:49 | 38.00 | 18.66 |
| August | 0.343661E+10 | 2611.58 | 13-AUG-16:02 | 38.00 | 20.47 | 0.128776E+09 | 70.32 | 27-AUG-02:39 | 23.33 | 10.07 |
| September | 0.285638E+10 | 2343.13 | 08-SEP-16:20 | 37.73 | 19.78 | 0.124558E+09 | 70.33 | 16-SEP-05:19 | 19.80 | 12.45 |
| October | 0.135129E+10 | 1947.64 | 02-OCT-14:00 | 35.00 | 19.78 | 0.115870E+09 | 70.37 | 05-OCT-05:49 | 19.00 | 13.00 |
| November | 0.446797E+09 | 1223.68 | 01-NOV-16:10 | 27.67 | 15.49 | 95653329.69 | 70.31 | 03-NOV-01:10 | 17.00 | 14.34 |
| December | 0.230436E+09 | 362.40 | 13-DEC-21:00 | 8.00 | 3.84 | 85263783.35 | 63.40 | 22-DEC-21:10 | 13.67 | 5.30 |
| Annual Sum or Average | 0.220691E+11 | 0.132424E+10 | ||||||||
| Minimum of Months | 0.230436E+09 | 342.67 | 8.00 | 3.84 | 77931746.89 | 63.40 | 13.67 | 5.30 | ||
| Maximum of Months | 0.392584E+10 | 2955.65 | 40.67 | 20.47 | 0.128776E+09 | 70.38 | 40.67 | 18.66 |
Report: ZoneCoolingSummaryMonthly
For: T S1 APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.148945E+10 | 2076.99 | 24-JAN-15:20 | 25.67 | 10.70 | 0.105135E+09 | 70.36 | 01-JAN-18:49 | 25.67 | 10.70 |
| February | 0.728054E+09 | 1428.19 | 01-FEB-15:30 | 15.50 | 6.96 | 86057129.67 | 70.37 | 23-FEB-20:19 | 11.67 | 9.05 |
| March | 0.103446E+10 | 2173.32 | 18-MAR-15:20 | 27.20 | 12.06 | 0.101625E+09 | 70.37 | 25-MAR-18:10 | 13.43 | 3.92 |
| April | 0.253015E+10 | 2511.01 | 10-APR-15:20 | 33.00 | 14.43 | 0.119974E+09 | 70.38 | 17-APR-01:00 | 17.00 | 11.35 |
| May | 0.289462E+10 | 2571.88 | 20-MAY-14:00 | 36.00 | 13.68 | 0.124691E+09 | 70.36 | 28-MAY-02:20 | 17.67 | 6.36 |
| June | 0.382723E+10 | 3030.84 | 30-JUN-16:01 | 40.83 | 17.99 | 0.120421E+09 | 70.32 | 07-JUN-06:40 | 40.83 | 17.99 |
| July | 0.386457E+10 | 3054.03 | 22-JUL-16:01 | 38.00 | 18.66 | 0.129273E+09 | 70.32 | 03-JUL-00:40 | 38.00 | 18.66 |
| August | 0.374950E+10 | 3039.41 | 13-AUG-16:02 | 38.00 | 20.47 | 0.123964E+09 | 70.32 | 27-AUG-02:39 | 23.33 | 10.07 |
| September | 0.343806E+10 | 2920.88 | 28-SEP-14:10 | 37.28 | 16.00 | 0.123897E+09 | 70.36 | 22-SEP-03:39 | 37.28 | 16.00 |
| October | 0.233561E+10 | 2887.21 | 10-OCT-15:10 | 34.83 | 17.00 | 0.118718E+09 | 70.37 | 19-OCT-02:30 | 17.50 | 8.76 |
| November | 0.136521E+10 | 2604.27 | 01-NOV-15:20 | 28.67 | 16.04 | 0.103878E+09 | 70.37 | 01-NOV-03:09 | 28.67 | 16.04 |
| December | 0.103928E+10 | 2016.38 | 25-DEC-15:10 | 26.00 | 11.63 | 97193574.14 | 70.37 | 27-DEC-20:00 | 12.20 | 6.47 |
| Annual Sum or Average | 0.282962E+11 | 0.135483E+10 | ||||||||
| Minimum of Months | 0.728054E+09 | 1428.19 | 15.50 | 6.96 | 86057129.67 | 70.32 | 11.67 | 3.92 | ||
| Maximum of Months | 0.386457E+10 | 3054.03 | 40.83 | 20.47 | 0.129273E+09 | 70.38 | 40.83 | 18.66 |
Report: ZoneCoolingSummaryMonthly
For: T S2 APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.149313E+10 | 2080.21 | 24-JAN-15:20 | 25.67 | 10.70 | 0.105098E+09 | 70.37 | 26-JAN-21:00 | 13.00 | 6.06 |
| February | 0.733632E+09 | 1430.69 | 01-FEB-15:30 | 15.50 | 6.96 | 86074132.24 | 70.38 | 20-FEB-20:19 | 13.00 | 11.23 |
| March | 0.104051E+10 | 2174.25 | 18-MAR-15:20 | 27.20 | 12.06 | 0.101621E+09 | 70.36 | 14-MAR-21:00 | 27.20 | 12.06 |
| April | 0.253616E+10 | 2511.59 | 10-APR-15:20 | 33.00 | 14.43 | 0.119956E+09 | 70.38 | 18-APR-01:30 | 16.50 | 9.21 |
| May | 0.290009E+10 | 2580.95 | 20-MAY-14:00 | 36.00 | 13.68 | 0.124683E+09 | 70.36 | 29-MAY-04:49 | 17.17 | 7.67 |
| June | 0.383096E+10 | 3023.21 | 30-JUN-16:01 | 40.83 | 17.99 | 0.120421E+09 | 70.32 | 07-JUN-06:40 | 40.83 | 17.99 |
| July | 0.387084E+10 | 3046.10 | 22-JUL-16:01 | 38.00 | 18.66 | 0.129273E+09 | 70.32 | 03-JUL-00:40 | 38.00 | 18.66 |
| August | 0.375547E+10 | 3031.00 | 13-AUG-16:05 | 38.00 | 20.47 | 0.123964E+09 | 70.32 | 27-AUG-02:39 | 23.33 | 10.07 |
| September | 0.344160E+10 | 2925.81 | 28-SEP-14:10 | 37.28 | 16.00 | 0.123897E+09 | 70.36 | 22-SEP-03:39 | 37.28 | 16.00 |
| October | 0.234144E+10 | 2884.63 | 10-OCT-15:10 | 34.83 | 17.00 | 0.118707E+09 | 70.37 | 11-OCT-22:19 | 14.67 | 6.44 |
| November | 0.136749E+10 | 2594.11 | 01-NOV-15:20 | 28.67 | 16.04 | 0.103809E+09 | 70.36 | 26-NOV-20:00 | 12.00 | 6.64 |
| December | 0.104342E+10 | 2014.31 | 25-DEC-15:10 | 26.00 | 11.63 | 97176568.84 | 70.37 | 25-DEC-21:49 | 12.17 | 4.89 |
| Annual Sum or Average | 0.283548E+11 | 0.135468E+10 | ||||||||
| Minimum of Months | 0.733632E+09 | 1430.69 | 15.50 | 6.96 | 86074132.24 | 70.32 | 12.00 | 4.89 | ||
| Maximum of Months | 0.387084E+10 | 3046.10 | 40.83 | 20.47 | 0.129273E+09 | 70.38 | 40.83 | 18.66 |
Report: ZoneCoolingSummaryMonthly
For: T CORRIDOR
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 4.27 | 1.81 | 0.186761E+09 | 133.14 | 31-JAN-21:10 | 15.78 | 5.68 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 11.90 | 4.43 | 0.152065E+09 | 122.69 | 22-FEB-21:10 | 13.00 | 10.72 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 11.85 | 8.83 | 0.197191E+09 | 153.50 | 16-MAR-20:10 | 22.02 | 12.51 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 | 7.34 | 0.256107E+09 | 175.59 | 14-APR-20:10 | 30.67 | 13.61 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 19.10 | 7.18 | 0.281062E+09 | 177.94 | 31-MAY-20:10 | 30.67 | 11.82 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 25.83 | 11.09 | 0.298788E+09 | 197.08 | 28-JUN-20:10 | 36.67 | 15.41 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 | 14.60 | 0.307113E+09 | 193.60 | 20-JUL-20:10 | 35.17 | 18.52 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 29.40 | 18.35 | 0.301462E+09 | 187.88 | 10-AUG-20:10 | 35.67 | 18.37 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 26.22 | 16.66 | 0.283595E+09 | 184.43 | 08-SEP-20:10 | 33.53 | 19.71 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 25.15 | 15.51 | 0.241131E+09 | 171.99 | 01-OCT-20:10 | 28.83 | 17.55 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 17.23 | 10.27 | 0.189681E+09 | 152.75 | 01-NOV-20:10 | 20.50 | 13.68 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 9.20 | 2.98 | 0.159524E+09 | 124.99 | 22-DEC-21:10 | 13.67 | 5.30 |
| Annual Sum or Average | 0.00 | 0.285448E+10 | ||||||||
| Minimum of Months | 0.00 | 0.00 | 4.27 | 1.81 | 0.152065E+09 | 122.69 | 13.00 | 5.30 | ||
| Maximum of Months | 0.00 | 0.00 | 29.40 | 18.35 | 0.307113E+09 | 197.08 | 36.67 | 19.71 |
Report: ZoneCoolingSummaryMonthly
For: G CORRIDOR
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 4.27 | 1.81 | 0.200081E+09 | 139.62 | 31-JAN-22:49 | 13.62 | 4.37 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 11.90 | 4.43 | 0.147219E+09 | 137.01 | 01-FEB-00:10 | 11.90 | 4.43 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 11.85 | 8.83 | 0.190994E+09 | 154.93 | 20-MAR-17:10 | 28.53 | 14.26 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 | 7.34 | 0.273477E+09 | 218.21 | 14-APR-17:10 | 34.83 | 14.48 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 19.10 | 7.18 | 0.309257E+09 | 235.22 | 31-MAY-17:10 | 36.83 | 14.02 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 25.83 | 11.09 | 0.339745E+09 | 287.97 | 28-JUN-17:10 | 41.83 | 19.10 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 | 14.60 | 0.348791E+09 | 262.43 | 20-JUL-17:10 | 39.00 | 20.06 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 29.40 | 18.35 | 0.343783E+09 | 277.74 | 25-AUG-17:10 | 40.67 | 17.58 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 26.22 | 16.66 | 0.322265E+09 | 247.74 | 07-SEP-17:10 | 37.02 | 19.96 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 25.15 | 15.51 | 0.279040E+09 | 218.05 | 03-OCT-17:10 | 33.83 | 19.79 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 17.23 | 10.27 | 0.219705E+09 | 159.15 | 01-NOV-21:49 | 18.00 | 13.11 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 9.20 | 2.98 | 0.181552E+09 | 139.16 | 26-DEC-22:49 | 14.17 | 6.88 |
| Annual Sum or Average | 0.00 | 0.315591E+10 | ||||||||
| Minimum of Months | 0.00 | 0.00 | 4.27 | 1.81 | 0.147219E+09 | 137.01 | 11.90 | 4.37 | ||
| Maximum of Months | 0.00 | 0.00 | 29.40 | 18.35 | 0.348791E+09 | 287.97 | 41.83 | 20.06 |
Report: ZoneCoolingSummaryMonthly
For: M CORRIDOR
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 4.27 | 1.81 | 0.241585E+09 | 146.02 | 27-JAN-21:10 | 16.17 | 6.63 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 11.90 | 4.43 | 0.207650E+09 | 141.13 | 01-FEB-00:10 | 11.90 | 4.43 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 11.85 | 8.83 | 0.244549E+09 | 154.11 | 18-MAR-20:10 | 20.22 | 10.80 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 | 7.34 | 0.270899E+09 | 162.99 | 14-APR-20:10 | 30.67 | 13.61 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 19.10 | 7.18 | 0.286720E+09 | 164.33 | 31-MAY-20:10 | 30.67 | 11.82 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 25.83 | 11.09 | 0.288497E+09 | 172.69 | 29-JUN-20:10 | 36.67 | 16.93 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 | 14.60 | 0.295260E+09 | 171.58 | 22-JUL-20:10 | 33.83 | 20.56 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 29.40 | 18.35 | 0.292730E+09 | 168.31 | 13-AUG-20:10 | 34.83 | 18.87 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 26.22 | 16.66 | 0.279551E+09 | 166.82 | 08-SEP-20:10 | 33.53 | 19.71 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 25.15 | 15.51 | 0.271294E+09 | 161.71 | 04-OCT-20:10 | 27.83 | 16.11 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 17.23 | 10.27 | 0.240910E+09 | 153.14 | 01-NOV-20:10 | 20.50 | 13.68 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 9.20 | 2.98 | 0.218354E+09 | 141.02 | 26-DEC-21:10 | 15.00 | 6.95 |
| Annual Sum or Average | 0.00 | 0.313800E+10 | ||||||||
| Minimum of Months | 0.00 | 0.00 | 4.27 | 1.81 | 0.207650E+09 | 141.02 | 11.90 | 4.43 | ||
| Maximum of Months | 0.00 | 0.00 | 29.40 | 18.35 | 0.295260E+09 | 172.69 | 36.67 | 20.56 |
Report: ZoneHeatingSummaryMonthly
For: G SW APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 4.27 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 11.90 |
| March | 14568.26 | 10.60 | 15-MAR-10:20 | 23.67 |
| April | 94560.88 | 50.98 | 01-APR-09:20 | 25.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 19.10 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 25.83 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 29.40 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 26.22 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 25.15 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 17.23 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 9.20 |
| Annual Sum or Average | 109129.14 | |||
| Minimum of Months | 0.00 | 0.00 | 4.27 | |
| Maximum of Months | 94560.88 | 50.98 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: G NW APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 22990124.77 | 403.37 | 01-JAN-08:00 | 0.50 |
| February | 7952515.32 | 198.51 | 05-FEB-04:00 | 8.00 |
| March | 16736234.37 | 273.01 | 27-MAR-06:00 | 1.60 |
| April | 2323501.46 | 201.64 | 01-APR-12:20 | 30.33 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 19.10 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 25.83 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 29.40 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 26.22 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 25.15 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 17.23 |
| December | 12223273.65 | 250.50 | 07-DEC-05:00 | -1.1 |
| Annual Sum or Average | 62225649.57 | |||
| Minimum of Months | 0.00 | 0.00 | -1.1 | |
| Maximum of Months | 22990124.77 | 403.37 | 30.33 |
Report: ZoneHeatingSummaryMonthly
For: OFFICE
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.148359E+09 | 540.76 | 31-JAN-17:12 | 27.67 |
| February | 0.100680E+09 | 363.24 | 18-FEB-15:30 | 22.00 |
| March | 0.224674E+09 | 592.22 | 16-MAR-16:12 | 28.63 |
| April | 0.509839E+09 | 781.16 | 14-APR-16:13 | 35.00 |
| May | 0.607683E+09 | 854.86 | 31-MAY-16:13 | 37.00 |
| June | 0.491445E+09 | 1043.38 | 28-JUN-16:01 | 42.00 |
| July | 0.399965E+09 | 881.35 | 20-JUL-17:12 | 39.00 |
| August | 0.424792E+09 | 996.80 | 25-AUG-16:01 | 41.00 |
| September | 0.345375E+09 | 814.28 | 08-SEP-16:01 | 38.02 |
| October | 0.240339E+09 | 693.60 | 03-OCT-17:12 | 33.67 |
| November | 0.120759E+09 | 504.74 | 01-NOV-07:05 | 19.83 |
| December | 87215286.05 | 399.16 | 02-DEC-15:00 | 25.00 |
| Annual Sum or Average | 0.370113E+10 | |||
| Minimum of Months | 87215286.05 | 363.24 | 19.83 | |
| Maximum of Months | 0.607683E+09 | 1043.38 | 42.00 |
Report: ZoneHeatingSummaryMonthly
For: G NE APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 23815790.65 | 433.57 | 01-JAN-02:00 | 4.60 |
| February | 7356651.22 | 237.89 | 05-FEB-04:00 | 8.00 |
| March | 14372422.48 | 275.48 | 28-MAR-04:00 | 3.80 |
| April | 326606.25 | 105.93 | 01-APR-10:00 | 27.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 19.10 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 25.83 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 29.40 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 26.22 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 25.15 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 17.23 |
| December | 10489572.40 | 245.62 | 07-DEC-05:00 | -1.1 |
| Annual Sum or Average | 56361043.00 | |||
| Minimum of Months | 0.00 | 0.00 | -1.1 | |
| Maximum of Months | 23815790.65 | 433.57 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: G N1 APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 4344135.36 | 96.87 | 14-JAN-13:40 | 26.67 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 11.90 |
| March | 2846930.99 | 122.45 | 14-MAR-14:00 | 27.20 |
| April | 2470310.05 | 197.32 | 01-APR-12:10 | 30.17 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 19.10 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 25.83 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 29.40 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 26.22 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 25.15 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 17.23 |
| December | 1303496.63 | 87.81 | 21-DEC-15:00 | 26.00 |
| Annual Sum or Average | 10964873.03 | |||
| Minimum of Months | 0.00 | 0.00 | 11.90 | |
| Maximum of Months | 4344135.36 | 197.32 | 30.17 |
Report: ZoneHeatingSummaryMonthly
For: G N2 APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 4459215.35 | 96.69 | 14-JAN-13:40 | 26.67 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 11.90 |
| March | 2754237.30 | 122.04 | 14-MAR-14:00 | 27.20 |
| April | 2335003.49 | 192.46 | 01-APR-12:00 | 30.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 19.10 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 25.83 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 29.40 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 26.22 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 25.15 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 17.23 |
| December | 1284078.90 | 87.59 | 21-DEC-15:00 | 26.00 |
| Annual Sum or Average | 10832535.04 | |||
| Minimum of Months | 0.00 | 0.00 | 11.90 | |
| Maximum of Months | 4459215.35 | 192.46 | 30.00 |
Report: ZoneHeatingSummaryMonthly
For: G S1 APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 4.27 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 11.90 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 11.85 |
| April | 808.85 | 1.35 | 01-APR-08:50 | 23.33 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 19.10 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 25.83 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 29.40 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 26.22 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 25.15 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 17.23 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 9.20 |
| Annual Sum or Average | 808.85 | |||
| Minimum of Months | 0.00 | 0.00 | 4.27 | |
| Maximum of Months | 808.85 | 1.35 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: G S2 APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 4.27 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 11.90 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 11.85 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 19.10 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 25.83 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 29.40 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 26.22 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 25.15 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 17.23 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 9.20 |
| Annual Sum or Average | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 4.27 | |
| Maximum of Months | 0.00 | 0.00 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: M SW APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 4.27 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 11.90 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 11.85 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 19.10 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 25.83 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 29.40 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 26.22 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 25.15 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 17.23 |
| December | 23705.62 | 24.52 | 07-DEC-06:00 | -1.0 |
| Annual Sum or Average | 23705.62 | |||
| Minimum of Months | 0.00 | 0.00 | -1.0 | |
| Maximum of Months | 23705.62 | 24.52 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: M NW APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 18077901.07 | 402.91 | 01-JAN-02:00 | 4.60 |
| February | 198451.72 | 86.70 | 05-FEB-04:00 | 8.00 |
| March | 50477.30 | 32.76 | 27-MAR-06:00 | 1.60 |
| April | 1366.43 | 2.28 | 01-APR-08:50 | 23.33 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 19.10 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 25.83 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 29.40 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 26.22 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 25.15 |
| November | 405007.17 | 64.02 | 24-NOV-10:00 | 9.00 |
| December | 58340742.28 | 573.73 | 07-DEC-05:00 | -1.1 |
| Annual Sum or Average | 77073945.96 | |||
| Minimum of Months | 0.00 | 0.00 | -1.1 | |
| Maximum of Months | 58340742.28 | 573.73 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: M SE APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 4.27 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 11.90 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 11.85 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 19.10 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 25.83 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 29.40 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 26.22 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 25.15 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 17.23 |
| December | 16492.24 | 20.01 | 07-DEC-06:00 | -1.0 |
| Annual Sum or Average | 16492.24 | |||
| Minimum of Months | 0.00 | 0.00 | -1.0 | |
| Maximum of Months | 16492.24 | 20.01 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: M NE APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 18842972.61 | 477.85 | 01-JAN-02:00 | 4.60 |
| February | 887273.19 | 169.80 | 05-FEB-04:00 | 8.00 |
| March | 22436.21 | 24.90 | 27-MAR-06:00 | 1.60 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 19.10 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 25.83 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 29.40 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 26.22 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 25.15 |
| November | 227894.94 | 45.87 | 24-NOV-03:00 | 5.00 |
| December | 54768372.51 | 583.44 | 07-DEC-05:00 | -1.1 |
| Annual Sum or Average | 74748949.47 | |||
| Minimum of Months | 0.00 | 0.00 | -1.1 | |
| Maximum of Months | 54768372.51 | 583.44 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: M N1 APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 916707.94 | 60.19 | 04-JAN-14:00 | 25.00 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 11.90 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 11.85 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 19.10 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 25.83 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 29.40 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 26.22 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 25.15 |
| November | 39997.44 | 20.09 | 27-NOV-13:40 | 24.00 |
| December | 1636699.43 | 88.87 | 21-DEC-15:00 | 26.00 |
| Annual Sum or Average | 2593404.81 | |||
| Minimum of Months | 0.00 | 0.00 | 11.85 | |
| Maximum of Months | 1636699.43 | 88.87 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: M N2 APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 909424.67 | 59.98 | 04-JAN-14:00 | 25.00 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 11.90 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 11.85 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 19.10 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 25.83 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 29.40 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 26.22 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 25.15 |
| November | 40605.87 | 20.32 | 27-NOV-13:40 | 24.00 |
| December | 1591099.68 | 88.58 | 21-DEC-15:00 | 26.00 |
| Annual Sum or Average | 2541130.22 | |||
| Minimum of Months | 0.00 | 0.00 | 11.85 | |
| Maximum of Months | 1591099.68 | 88.58 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: M S1 APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 4.27 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 11.90 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 11.85 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 19.10 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 25.83 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 29.40 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 26.22 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 25.15 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 17.23 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 9.20 |
| Annual Sum or Average | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 4.27 | |
| Maximum of Months | 0.00 | 0.00 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: M S2 APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 4.27 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 11.90 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 11.85 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 19.10 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 25.83 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 29.40 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 26.22 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 25.15 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 17.23 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 9.20 |
| Annual Sum or Average | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 4.27 | |
| Maximum of Months | 0.00 | 0.00 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: T SW APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.168044E+09 | 1134.03 | 01-JAN-07:14 | 1.17 |
| February | 0.178020E+09 | 968.46 | 05-FEB-04:00 | 8.00 |
| March | 0.199742E+09 | 1241.29 | 26-MAR-06:35 | 1.63 |
| April | 1101380.86 | 256.59 | 21-APR-07:13 | 13.00 |
| May | 24228.38 | 25.67 | 14-MAY-08:00 | 24.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 25.83 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 29.40 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 26.22 |
| October | 24931338.82 | 520.87 | 26-OCT-04:00 | 7.00 |
| November | 0.126727E+09 | 1078.98 | 23-NOV-07:00 | 0.00 |
| December | 0.455983E+09 | 1610.84 | 07-DEC-06:00 | -1.0 |
| Annual Sum or Average | 0.115457E+10 | |||
| Minimum of Months | 0.00 | 0.00 | -1.0 | |
| Maximum of Months | 0.455983E+09 | 1610.84 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: T NW APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.380833E+09 | 1473.94 | 01-JAN-08:00 | 0.50 |
| February | 0.351991E+09 | 1040.79 | 05-FEB-04:00 | 8.00 |
| March | 0.278743E+09 | 1376.86 | 26-MAR-06:35 | 1.63 |
| April | 1613170.69 | 273.46 | 01-APR-07:02 | 16.67 |
| May | 19604.76 | 21.98 | 14-MAY-08:00 | 24.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 25.83 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 29.40 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 26.22 |
| October | 63711177.00 | 758.80 | 26-OCT-04:00 | 7.00 |
| November | 0.288177E+09 | 1428.56 | 24-NOV-03:00 | 5.00 |
| December | 0.846005E+09 | 1853.91 | 07-DEC-06:00 | -1.0 |
| Annual Sum or Average | 0.221109E+10 | |||
| Minimum of Months | 0.00 | 0.00 | -1.0 | |
| Maximum of Months | 0.846005E+09 | 1853.91 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: T SE APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.165513E+09 | 1159.32 | 01-JAN-07:14 | 1.17 |
| February | 0.171408E+09 | 1014.42 | 05-FEB-04:00 | 8.00 |
| March | 0.186089E+09 | 1257.25 | 26-MAR-06:00 | 0.50 |
| April | 789522.27 | 213.94 | 21-APR-05:50 | 8.83 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 19.10 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 25.83 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 29.40 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 26.22 |
| October | 22522353.16 | 534.00 | 26-OCT-04:00 | 7.00 |
| November | 0.121243E+09 | 1105.19 | 23-NOV-07:00 | 0.00 |
| December | 0.442379E+09 | 1623.82 | 07-DEC-06:00 | -1.0 |
| Annual Sum or Average | 0.110994E+10 | |||
| Minimum of Months | 0.00 | 0.00 | -1.0 | |
| Maximum of Months | 0.442379E+09 | 1623.82 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: T NE APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.357066E+09 | 1424.36 | 01-JAN-07:14 | 1.17 |
| February | 0.324232E+09 | 1083.63 | 05-FEB-04:00 | 8.00 |
| March | 0.257989E+09 | 1408.96 | 26-MAR-06:00 | 0.50 |
| April | 1003123.08 | 248.46 | 21-APR-05:50 | 8.83 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 19.10 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 25.83 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 29.40 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 26.22 |
| October | 53613328.03 | 775.16 | 26-OCT-04:00 | 7.00 |
| November | 0.266246E+09 | 1481.43 | 24-NOV-03:00 | 5.00 |
| December | 0.793394E+09 | 1873.79 | 07-DEC-06:00 | -1.0 |
| Annual Sum or Average | 0.205354E+10 | |||
| Minimum of Months | 0.00 | 0.00 | -1.0 | |
| Maximum of Months | 0.793394E+09 | 1873.79 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: T N1 APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.128635E+09 | 880.07 | 01-JAN-08:00 | 0.50 |
| February | 0.116174E+09 | 591.44 | 05-FEB-04:00 | 8.00 |
| March | 90337767.41 | 801.17 | 26-MAR-06:00 | 0.50 |
| April | 158383.83 | 65.94 | 01-APR-09:30 | 25.50 |
| May | 569.51 | 1.90 | 14-MAY-07:45 | 23.33 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 25.83 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 29.40 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 26.22 |
| October | 10553655.41 | 367.24 | 26-OCT-04:00 | 7.00 |
| November | 98784160.42 | 875.25 | 24-NOV-03:00 | 5.00 |
| December | 0.406888E+09 | 1192.43 | 07-DEC-05:00 | -1.1 |
| Annual Sum or Average | 0.851532E+09 | |||
| Minimum of Months | 0.00 | 0.00 | -1.1 | |
| Maximum of Months | 0.406888E+09 | 1192.43 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: T N2 APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.129461E+09 | 882.76 | 01-JAN-08:00 | 0.50 |
| February | 0.116079E+09 | 595.52 | 05-FEB-04:00 | 8.00 |
| March | 90392991.94 | 803.24 | 26-MAR-06:00 | 0.50 |
| April | 146279.03 | 63.93 | 01-APR-09:30 | 25.50 |
| May | 379.83 | 1.27 | 14-MAY-07:45 | 23.33 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 25.83 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 29.40 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 26.22 |
| October | 10467740.16 | 366.35 | 26-OCT-04:00 | 7.00 |
| November | 99133114.50 | 880.33 | 24-NOV-03:00 | 5.00 |
| December | 0.407008E+09 | 1195.03 | 07-DEC-05:00 | -1.1 |
| Annual Sum or Average | 0.852689E+09 | |||
| Minimum of Months | 0.00 | 0.00 | -1.1 | |
| Maximum of Months | 0.407008E+09 | 1195.03 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: T S1 APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 21194101.05 | 543.67 | 01-JAN-07:14 | 1.17 |
| February | 28971291.75 | 505.36 | 05-FEB-04:00 | 8.00 |
| March | 48003485.97 | 640.93 | 26-MAR-06:00 | 0.50 |
| April | 3132.62 | 5.22 | 01-APR-08:50 | 23.33 |
| May | 2195.03 | 6.21 | 14-MAY-07:45 | 23.33 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 25.83 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 29.40 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 26.22 |
| October | 296995.71 | 79.79 | 26-OCT-04:00 | 7.00 |
| November | 17796715.05 | 493.06 | 23-NOV-07:00 | 0.00 |
| December | 0.139751E+09 | 912.90 | 07-DEC-06:00 | -1.0 |
| Annual Sum or Average | 0.256019E+09 | |||
| Minimum of Months | 0.00 | 0.00 | -1.0 | |
| Maximum of Months | 0.139751E+09 | 912.90 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: T S2 APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 21447740.55 | 545.71 | 01-JAN-07:14 | 1.17 |
| February | 29133058.03 | 510.22 | 05-FEB-04:00 | 8.00 |
| March | 48015878.97 | 641.05 | 26-MAR-06:00 | 0.50 |
| April | 2409.77 | 4.02 | 01-APR-08:50 | 23.33 |
| May | 1686.67 | 5.62 | 14-MAY-07:45 | 23.33 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 25.83 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 29.40 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 26.22 |
| October | 296681.35 | 79.51 | 26-OCT-04:00 | 7.00 |
| November | 17919751.44 | 496.55 | 23-NOV-07:00 | 0.00 |
| December | 0.139868E+09 | 914.52 | 07-DEC-06:00 | -1.0 |
| Annual Sum or Average | 0.256685E+09 | |||
| Minimum of Months | 0.00 | 0.00 | -1.0 | |
| Maximum of Months | 0.139868E+09 | 914.52 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: T CORRIDOR
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 4.27 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 11.90 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 11.85 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 19.10 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 25.83 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 29.40 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 26.22 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 25.15 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 17.23 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 9.20 |
| Annual Sum or Average | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 4.27 | |
| Maximum of Months | 0.00 | 0.00 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: G CORRIDOR
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 4.27 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 11.90 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 11.85 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 19.10 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 25.83 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 29.40 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 26.22 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 25.15 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 17.23 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 9.20 |
| Annual Sum or Average | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 4.27 | |
| Maximum of Months | 0.00 | 0.00 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: M CORRIDOR
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 4.27 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 11.90 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 11.85 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 19.10 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 25.83 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 29.40 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 26.22 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 25.15 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 17.23 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 9.20 |
| Annual Sum or Average | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 4.27 | |
| Maximum of Months | 0.00 | 0.00 | 29.40 |
Report: ZoneElectricSummaryMonthly
For: G SW APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: G NW APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: OFFICE
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.609777E+09 | 582.92 | 03-JAN-08:09 | 0.787690E+09 | 588.62 | 03-JAN-08:09 |
| February | 0.564682E+09 | 582.92 | 01-FEB-08:09 | 0.723971E+09 | 588.62 | 01-FEB-08:09 |
| March | 0.654405E+09 | 582.92 | 01-MAR-08:09 | 0.827804E+09 | 588.62 | 01-MAR-08:09 |
| April | 0.599704E+09 | 582.92 | 03-APR-07:10 | 0.770907E+09 | 588.62 | 03-APR-07:10 |
| May | 0.639529E+09 | 582.92 | 01-MAY-07:10 | 0.814432E+09 | 588.62 | 01-MAY-07:10 |
| June | 0.629456E+09 | 582.92 | 01-JUN-07:10 | 0.797650E+09 | 588.62 | 01-JUN-07:10 |
| July | 0.609777E+09 | 582.92 | 03-JUL-07:10 | 0.787690E+09 | 588.62 | 03-JUL-07:10 |
| August | 0.654405E+09 | 582.92 | 01-AUG-07:10 | 0.827804E+09 | 588.62 | 01-AUG-07:10 |
| September | 0.599704E+09 | 582.92 | 01-SEP-07:10 | 0.770907E+09 | 588.62 | 01-SEP-07:10 |
| October | 0.624653E+09 | 582.92 | 02-OCT-07:10 | 0.801061E+09 | 588.62 | 02-OCT-07:10 |
| November | 0.599704E+09 | 582.92 | 01-NOV-07:10 | 0.770907E+09 | 588.62 | 01-NOV-07:10 |
| December | 0.609777E+09 | 582.92 | 01-DEC-08:09 | 0.787690E+09 | 588.62 | 01-DEC-08:09 |
| Annual Sum or Average | 0.739557E+10 | 0.946851E+10 | ||||
| Minimum of Months | 0.564682E+09 | 582.92 | 0.723971E+09 | 588.62 | ||
| Maximum of Months | 0.654405E+09 | 582.92 | 0.827804E+09 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: G NE APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: G N1 APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: G N2 APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: G S1 APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: G S2 APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: M SW APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: M NW APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: M SE APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: M NE APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: M N1 APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: M N2 APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: M S1 APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: M S2 APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: T SW APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: T NW APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: T SE APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: T NE APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: T N1 APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: T N2 APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: T S1 APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: T S2 APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: T CORRIDOR
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
| January | 0.992689E+09 | 370.63 | 01-JAN-00:10 | 0.00 | 0.00 |
| February | 0.896622E+09 | 370.63 | 01-FEB-00:10 | 0.00 | 0.00 |
| March | 0.992689E+09 | 370.63 | 01-MAR-00:10 | 0.00 | 0.00 |
| April | 0.960667E+09 | 370.63 | 01-APR-00:10 | 0.00 | 0.00 |
| May | 0.992689E+09 | 370.63 | 01-MAY-00:10 | 0.00 | 0.00 |
| June | 0.960667E+09 | 370.63 | 01-JUN-00:10 | 0.00 | 0.00 |
| July | 0.992689E+09 | 370.63 | 01-JUL-00:10 | 0.00 | 0.00 |
| August | 0.992689E+09 | 370.63 | 01-AUG-00:10 | 0.00 | 0.00 |
| September | 0.960667E+09 | 370.63 | 01-SEP-00:10 | 0.00 | 0.00 |
| October | 0.992689E+09 | 370.63 | 01-OCT-00:10 | 0.00 | 0.00 |
| November | 0.960667E+09 | 370.63 | 01-NOV-00:10 | 0.00 | 0.00 |
| December | 0.992689E+09 | 370.63 | 01-DEC-00:10 | 0.00 | 0.00 |
| Annual Sum or Average | 0.116881E+11 | 0.00 | 0.00 | ||
| Minimum of Months | 0.896622E+09 | 370.63 | 0.00 | 0.00 | |
| Maximum of Months | 0.992689E+09 | 370.63 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: G CORRIDOR
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.992689E+09 | 370.63 | 01-JAN-00:10 | 0.599555E+10 | 4168.07 | 01-JAN-07:10 |
| February | 0.896622E+09 | 370.63 | 01-FEB-00:10 | 0.541534E+10 | 4168.07 | 01-FEB-07:10 |
| March | 0.992689E+09 | 370.63 | 01-MAR-00:10 | 0.599555E+10 | 4168.07 | 01-MAR-07:10 |
| April | 0.960667E+09 | 370.63 | 01-APR-00:10 | 0.580215E+10 | 4168.07 | 01-APR-06:10 |
| May | 0.992689E+09 | 370.63 | 01-MAY-00:10 | 0.599555E+10 | 4168.07 | 01-MAY-06:10 |
| June | 0.960667E+09 | 370.63 | 01-JUN-00:10 | 0.580215E+10 | 4168.07 | 01-JUN-06:10 |
| July | 0.992689E+09 | 370.63 | 01-JUL-00:10 | 0.599555E+10 | 4168.07 | 01-JUL-06:10 |
| August | 0.992689E+09 | 370.63 | 01-AUG-00:10 | 0.599555E+10 | 4168.07 | 01-AUG-06:10 |
| September | 0.960667E+09 | 370.63 | 01-SEP-00:10 | 0.580215E+10 | 4168.07 | 01-SEP-06:10 |
| October | 0.992689E+09 | 370.63 | 01-OCT-00:10 | 0.599555E+10 | 4168.07 | 01-OCT-06:10 |
| November | 0.960667E+09 | 370.63 | 01-NOV-00:10 | 0.580215E+10 | 4168.07 | 01-NOV-06:10 |
| December | 0.992689E+09 | 370.63 | 01-DEC-00:10 | 0.599555E+10 | 4168.07 | 01-DEC-07:10 |
| Annual Sum or Average | 0.116881E+11 | 0.705928E+11 | ||||
| Minimum of Months | 0.896622E+09 | 370.63 | 0.541534E+10 | 4168.07 | ||
| Maximum of Months | 0.992689E+09 | 370.63 | 0.599555E+10 | 4168.07 |
Report: ZoneElectricSummaryMonthly
For: M CORRIDOR
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
| January | 0.992689E+09 | 370.63 | 01-JAN-00:10 | 0.00 | 0.00 |
| February | 0.896622E+09 | 370.63 | 01-FEB-00:10 | 0.00 | 0.00 |
| March | 0.992689E+09 | 370.63 | 01-MAR-00:10 | 0.00 | 0.00 |
| April | 0.960667E+09 | 370.63 | 01-APR-00:10 | 0.00 | 0.00 |
| May | 0.992689E+09 | 370.63 | 01-MAY-00:10 | 0.00 | 0.00 |
| June | 0.960667E+09 | 370.63 | 01-JUN-00:10 | 0.00 | 0.00 |
| July | 0.992689E+09 | 370.63 | 01-JUL-00:10 | 0.00 | 0.00 |
| August | 0.992689E+09 | 370.63 | 01-AUG-00:10 | 0.00 | 0.00 |
| September | 0.960667E+09 | 370.63 | 01-SEP-00:10 | 0.00 | 0.00 |
| October | 0.992689E+09 | 370.63 | 01-OCT-00:10 | 0.00 | 0.00 |
| November | 0.960667E+09 | 370.63 | 01-NOV-00:10 | 0.00 | 0.00 |
| December | 0.992689E+09 | 370.63 | 01-DEC-00:10 | 0.00 | 0.00 |
| Annual Sum or Average | 0.116881E+11 | 0.00 | 0.00 | ||
| Minimum of Months | 0.896622E+09 | 370.63 | 0.00 | 0.00 | |
| Maximum of Months | 0.992689E+09 | 370.63 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: G SW APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2145180.63 | 0.247532E+09 |
| February | 0.389025E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.220785E+09 |
| March | 0.418950E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6226393.80 | 0.248593E+09 |
| April | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 84340521.29 | 72490235.69 |
| May | 0.424935E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.161074E+09 | 35875111.18 |
| June | 0.406980E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.285481E+09 | 6400746.95 |
| July | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.255688E+09 | 4366111.72 |
| August | 0.418950E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.187481E+09 | 8250017.45 |
| September | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.151436E+09 | 16804580.10 |
| October | 0.430920E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 54990384.53 | 0.131780E+09 |
| November | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4739415.04 | 0.235659E+09 |
| December | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 368150.44 | 0.251465E+09 |
| Annual Sum or Average | 0.505732E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119397E+10 | 0.148000E+10 |
| Minimum of Months | 0.389025E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4366111.72 |
| Maximum of Months | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.285481E+09 | 0.251465E+09 |
Report: SpaceGainsMonthly
For: G NW APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2434853.33 | 0.221376E+09 |
| February | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.194079E+09 |
| March | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6479504.90 | 0.228846E+09 |
| April | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 84390961.14 | 71486431.27 |
| May | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.161075E+09 | 35866405.82 |
| June | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.285481E+09 | 6400749.96 |
| July | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.255688E+09 | 4366112.39 |
| August | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.187481E+09 | 8250014.50 |
| September | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.151436E+09 | 16804567.90 |
| October | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 54990388.25 | 0.129704E+09 |
| November | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4739450.86 | 0.225064E+09 |
| December | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 420317.26 | 0.228434E+09 |
| Annual Sum or Average | 0.512427E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119462E+10 | 0.137068E+10 |
| Minimum of Months | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4366112.39 |
| Maximum of Months | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.285481E+09 | 0.228846E+09 |
Report: SpaceGainsMonthly
For: OFFICE
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.227408E+09 | 0.609777E+09 | 0.787690E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1696519.16 | 0.280324E+09 |
| February | 0.216037E+09 | 0.564682E+09 | 0.723971E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.242664E+09 |
| March | 0.261519E+09 | 0.654405E+09 | 0.827804E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4500286.37 | 0.287172E+09 |
| April | 0.227408E+09 | 0.599704E+09 | 0.770907E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 46211445.29 | 0.117147E+09 |
| May | 0.250148E+09 | 0.639529E+09 | 0.814432E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 98437582.86 | 75720855.90 |
| June | 0.250148E+09 | 0.629456E+09 | 0.797650E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.192686E+09 | 32445115.81 |
| July | 0.227408E+09 | 0.609777E+09 | 0.787690E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.154691E+09 | 38222807.71 |
| August | 0.261519E+09 | 0.654405E+09 | 0.827804E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.117660E+09 | 52297190.86 |
| September | 0.227408E+09 | 0.599704E+09 | 0.770907E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 84250576.35 | 78809382.43 |
| October | 0.238778E+09 | 0.624653E+09 | 0.801061E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 31393587.02 | 0.197370E+09 |
| November | 0.227408E+09 | 0.599704E+09 | 0.770907E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3239977.64 | 0.277471E+09 |
| December | 0.227408E+09 | 0.609777E+09 | 0.787690E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 154896.73 | 0.274016E+09 |
| Annual Sum or Average | 0.284259E+10 | 0.739557E+10 | 0.946851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.734922E+09 | 0.195366E+10 |
| Minimum of Months | 0.216037E+09 | 0.564682E+09 | 0.723971E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32445115.81 |
| Maximum of Months | 0.261519E+09 | 0.654405E+09 | 0.827804E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.192686E+09 | 0.287172E+09 |
Report: SpaceGainsMonthly
For: G NE APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2415770.07 | 0.221181E+09 |
| February | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.194991E+09 |
| March | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6359195.40 | 0.230629E+09 |
| April | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 84346088.95 | 71745809.89 |
| May | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.161075E+09 | 35872967.27 |
| June | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.285481E+09 | 6400746.05 |
| July | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.255689E+09 | 4366109.21 |
| August | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.187481E+09 | 8250011.59 |
| September | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.151436E+09 | 16804563.09 |
| October | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 54990409.02 | 0.130337E+09 |
| November | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4739458.85 | 0.225498E+09 |
| December | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 411473.51 | 0.228839E+09 |
| Annual Sum or Average | 0.512427E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119442E+10 | 0.137492E+10 |
| Minimum of Months | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4366109.21 |
| Maximum of Months | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.285481E+09 | 0.230629E+09 |
Report: SpaceGainsMonthly
For: G N1 APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1462989.27 | 0.138386E+09 |
| February | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122342E+09 |
| March | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3834162.78 | 0.143748E+09 |
| April | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 50895150.88 | 43663673.79 |
| May | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 97156184.77 | 21677242.47 |
| June | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.172195E+09 | 3860763.10 |
| July | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.154225E+09 | 2633520.54 |
| August | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113084E+09 | 4976193.85 |
| September | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 91342271.96 | 10136070.84 |
| October | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33168861.37 | 79120392.58 |
| November | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2858729.38 | 0.138690E+09 |
| December | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 262756.81 | 0.140977E+09 |
| Annual Sum or Average | 0.512427E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.720485E+09 | 0.850211E+09 |
| Minimum of Months | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2633520.54 |
| Maximum of Months | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.172195E+09 | 0.143748E+09 |
Report: SpaceGainsMonthly
For: G N2 APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1462406.86 | 0.138343E+09 |
| February | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122474E+09 |
| March | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3829863.36 | 0.143892E+09 |
| April | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 50893425.03 | 43669463.10 |
| May | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 97156185.37 | 21677193.96 |
| June | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.172195E+09 | 3860763.03 |
| July | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.154225E+09 | 2633520.48 |
| August | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113084E+09 | 4976193.81 |
| September | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 91342272.57 | 10136070.78 |
| October | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33168861.49 | 79144087.53 |
| November | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2858729.37 | 0.138680E+09 |
| December | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 261671.97 | 0.141018E+09 |
| Annual Sum or Average | 0.512427E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.720477E+09 | 0.850505E+09 |
| Minimum of Months | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2633520.48 |
| Maximum of Months | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.172195E+09 | 0.143892E+09 |
Report: SpaceGainsMonthly
For: G S1 APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1293930.13 | 0.153916E+09 |
| February | 0.389025E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.141533E+09 |
| March | 0.418950E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3755607.27 | 0.158913E+09 |
| April | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 50870592.50 | 44165099.60 |
| May | 0.424935E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 97156166.95 | 21672345.31 |
| June | 0.406980E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.172195E+09 | 3860762.03 |
| July | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.154225E+09 | 2633520.07 |
| August | 0.418950E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113084E+09 | 4976194.76 |
| September | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 91342281.40 | 10136078.81 |
| October | 0.430920E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33168855.99 | 79870555.75 |
| November | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2858708.57 | 0.143781E+09 |
| December | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 222060.81 | 0.156285E+09 |
| Annual Sum or Average | 0.505732E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.720172E+09 | 0.921743E+09 |
| Minimum of Months | 0.389025E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2633520.07 |
| Maximum of Months | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.172195E+09 | 0.158913E+09 |
Report: SpaceGainsMonthly
For: G S2 APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1293929.96 | 0.154148E+09 |
| February | 0.389025E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.142489E+09 |
| March | 0.418950E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3755604.39 | 0.160194E+09 |
| April | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 50870587.47 | 44237232.15 |
| May | 0.424935E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 97156161.49 | 21679191.81 |
| June | 0.406980E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.172195E+09 | 3860767.18 |
| July | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.154225E+09 | 2633523.22 |
| August | 0.418950E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113084E+09 | 4976196.88 |
| September | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 91342287.20 | 10136084.69 |
| October | 0.430920E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33168851.39 | 79899588.55 |
| November | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2858708.56 | 0.143936E+09 |
| December | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 222060.77 | 0.156637E+09 |
| Annual Sum or Average | 0.505732E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.720172E+09 | 0.924826E+09 |
| Minimum of Months | 0.389025E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2633523.22 |
| Maximum of Months | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.172195E+09 | 0.160194E+09 |
Report: SpaceGainsMonthly
For: M SW APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3038843.68 | 0.358283E+09 |
| February | 0.389025E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.338640E+09 |
| March | 0.418950E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8854824.86 | 0.385298E+09 |
| April | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120712E+09 | 0.105726E+09 |
| May | 0.424935E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.230777E+09 | 51887483.45 |
| June | 0.406980E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.409425E+09 | 9296625.03 |
| July | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.366542E+09 | 6351010.41 |
| August | 0.418950E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.268685E+09 | 11994753.60 |
| September | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.216902E+09 | 24381221.99 |
| October | 0.430920E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 78699103.69 | 0.187456E+09 |
| November | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6734949.76 | 0.332423E+09 |
| December | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 519700.13 | 0.356088E+09 |
| Annual Sum or Average | 0.505732E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.171089E+10 | 0.216782E+10 |
| Minimum of Months | 0.389025E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6351010.41 |
| Maximum of Months | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.409425E+09 | 0.385298E+09 |
Report: SpaceGainsMonthly
For: M NW APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3148175.90 | 0.331734E+09 |
| February | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.306195E+09 |
| March | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8854868.67 | 0.368298E+09 |
| April | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120712E+09 | 0.105190E+09 |
| May | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.230777E+09 | 51898207.61 |
| June | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.409425E+09 | 9296629.23 |
| July | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.366542E+09 | 6351011.66 |
| August | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.268685E+09 | 11994750.18 |
| September | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.216902E+09 | 24380466.10 |
| October | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 78699133.09 | 0.181406E+09 |
| November | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6742894.34 | 0.311274E+09 |
| December | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 631316.81 | 0.323761E+09 |
| Annual Sum or Average | 0.512427E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.171112E+10 | 0.203178E+10 |
| Minimum of Months | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6351011.66 |
| Maximum of Months | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.409425E+09 | 0.368298E+09 |
Report: SpaceGainsMonthly
For: M SE APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3038855.19 | 0.358707E+09 |
| February | 0.389025E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.339787E+09 |
| March | 0.418950E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8854833.08 | 0.387507E+09 |
| April | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120712E+09 | 0.105822E+09 |
| May | 0.424935E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.230777E+09 | 51901528.37 |
| June | 0.406980E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.409425E+09 | 9296619.04 |
| July | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.366542E+09 | 6351006.53 |
| August | 0.418950E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.268685E+09 | 11994750.19 |
| September | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.216902E+09 | 24381250.82 |
| October | 0.430920E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 78699161.16 | 0.187874E+09 |
| November | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6734961.14 | 0.333064E+09 |
| December | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 519701.80 | 0.357297E+09 |
| Annual Sum or Average | 0.505732E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.171089E+10 | 0.217398E+10 |
| Minimum of Months | 0.389025E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6351006.53 |
| Maximum of Months | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.409425E+09 | 0.387507E+09 |
Report: SpaceGainsMonthly
For: M NE APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3130571.48 | 0.332319E+09 |
| February | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.308870E+09 |
| March | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8854867.22 | 0.371220E+09 |
| April | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120712E+09 | 0.105363E+09 |
| May | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.230777E+09 | 51900579.67 |
| June | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.409425E+09 | 9296622.69 |
| July | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.366542E+09 | 6351007.52 |
| August | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.268685E+09 | 11994746.71 |
| September | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.216902E+09 | 24380550.22 |
| October | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 78699161.78 | 0.183064E+09 |
| November | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6743161.99 | 0.312313E+09 |
| December | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 613165.02 | 0.324278E+09 |
| Annual Sum or Average | 0.512427E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.171108E+10 | 0.204135E+10 |
| Minimum of Months | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6351007.52 |
| Maximum of Months | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.409425E+09 | 0.371220E+09 |
Report: SpaceGainsMonthly
For: M N1 APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1889223.77 | 0.208477E+09 |
| February | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.195381E+09 |
| March | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5341049.19 | 0.231220E+09 |
| April | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 72810642.43 | 63889501.44 |
| May | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139199E+09 | 31314029.43 |
| June | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.246955E+09 | 5607477.84 |
| July | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.221089E+09 | 3830759.83 |
| August | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.162064E+09 | 7234921.65 |
| September | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130830E+09 | 14707134.41 |
| October | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 47469399.51 | 0.112428E+09 |
| November | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4062412.73 | 0.195265E+09 |
| December | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 376226.70 | 0.201913E+09 |
| Annual Sum or Average | 0.512427E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103209E+10 | 0.127127E+10 |
| Minimum of Months | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3830759.83 |
| Maximum of Months | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.246955E+09 | 0.231220E+09 |
Report: SpaceGainsMonthly
For: M N2 APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1888484.34 | 0.208461E+09 |
| February | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.195640E+09 |
| March | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5341048.90 | 0.231417E+09 |
| April | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 72810642.75 | 63894006.56 |
| May | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139199E+09 | 31313991.57 |
| June | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.246955E+09 | 5607477.69 |
| July | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.221089E+09 | 3830759.74 |
| August | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.162064E+09 | 7234921.59 |
| September | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130830E+09 | 14707134.33 |
| October | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 47469407.84 | 0.112510E+09 |
| November | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4062414.64 | 0.195262E+09 |
| December | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 374314.62 | 0.201967E+09 |
| Annual Sum or Average | 0.512427E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103208E+10 | 0.127185E+10 |
| Minimum of Months | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3830759.74 |
| Maximum of Months | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.246955E+09 | 0.231417E+09 |
Report: SpaceGainsMonthly
For: M S1 APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1832973.61 | 0.222523E+09 |
| February | 0.389025E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.212021E+09 |
| March | 0.418950E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5341027.52 | 0.240130E+09 |
| April | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 72810623.91 | 64099849.03 |
| May | 0.424935E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139199E+09 | 31308705.93 |
| June | 0.406980E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.246955E+09 | 5607475.94 |
| July | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.221089E+09 | 3830759.05 |
| August | 0.418950E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.162064E+09 | 7234923.77 |
| September | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130830E+09 | 14707146.54 |
| October | 0.430920E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 47469383.32 | 0.114650E+09 |
| November | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4062371.14 | 0.205316E+09 |
| December | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 313472.90 | 0.223229E+09 |
| Annual Sum or Average | 0.505732E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103197E+10 | 0.134466E+10 |
| Minimum of Months | 0.389025E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3830759.05 |
| Maximum of Months | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.246955E+09 | 0.240130E+09 |
Report: SpaceGainsMonthly
For: M S2 APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1832973.78 | 0.222509E+09 |
| February | 0.389025E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.212040E+09 |
| March | 0.418950E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5341027.56 | 0.240185E+09 |
| April | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 72810626.85 | 64101204.61 |
| May | 0.424935E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139199E+09 | 31308611.60 |
| June | 0.406980E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.246955E+09 | 5607475.81 |
| July | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.221089E+09 | 3830758.96 |
| August | 0.418950E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.162064E+09 | 7234923.71 |
| September | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130830E+09 | 14707146.44 |
| October | 0.430920E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 47469386.01 | 0.114653E+09 |
| November | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4062371.46 | 0.205309E+09 |
| December | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 313472.91 | 0.223253E+09 |
| Annual Sum or Average | 0.505732E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103197E+10 | 0.134474E+10 |
| Minimum of Months | 0.389025E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3830758.96 |
| Maximum of Months | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.246955E+09 | 0.240185E+09 |
Report: SpaceGainsMonthly
For: T SW APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3903471.96 | 0.424614E+09 |
| February | 0.389025E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.401516E+09 |
| March | 0.418950E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11469646.10 | 0.458917E+09 |
| April | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.158388E+09 | 0.127692E+09 |
| May | 0.424935E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.303422E+09 | 65662870.43 |
| June | 0.406980E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.539379E+09 | 12539630.30 |
| July | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.482475E+09 | 8577649.47 |
| August | 0.418950E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.353456E+09 | 16207243.01 |
| September | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.285005E+09 | 32415517.03 |
| October | 0.430920E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103240E+09 | 0.224053E+09 |
| November | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8708462.05 | 0.395350E+09 |
| December | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 662687.46 | 0.437366E+09 |
| Annual Sum or Average | 0.505732E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.225011E+10 | 0.260491E+10 |
| Minimum of Months | 0.389025E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8577649.47 |
| Maximum of Months | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.539379E+09 | 0.458917E+09 |
Report: SpaceGainsMonthly
For: T NW APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4191520.66 | 0.398841E+09 |
| February | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.372585E+09 |
| March | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11503746.04 | 0.441342E+09 |
| April | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.158412E+09 | 0.126352E+09 |
| May | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.303421E+09 | 66037126.77 |
| June | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.539379E+09 | 12553989.74 |
| July | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.482474E+09 | 8592914.67 |
| August | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.353456E+09 | 16213856.94 |
| September | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.285005E+09 | 32429096.75 |
| October | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103285E+09 | 0.210916E+09 |
| November | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8941330.53 | 0.369856E+09 |
| December | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 754105.39 | 0.411066E+09 |
| Annual Sum or Average | 0.512427E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.225082E+10 | 0.246679E+10 |
| Minimum of Months | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8592914.67 |
| Maximum of Months | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.539379E+09 | 0.441342E+09 |
Report: SpaceGainsMonthly
For: T SE APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3903494.34 | 0.426962E+09 |
| February | 0.389025E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.404221E+09 |
| March | 0.418950E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11469657.05 | 0.463124E+09 |
| April | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.158386E+09 | 0.129697E+09 |
| May | 0.424935E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.303421E+09 | 66148766.30 |
| June | 0.406980E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.539379E+09 | 12547662.06 |
| July | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.482475E+09 | 8588339.17 |
| August | 0.418950E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.353457E+09 | 16213580.95 |
| September | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.285006E+09 | 32487470.89 |
| October | 0.430920E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103240E+09 | 0.226434E+09 |
| November | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8708481.33 | 0.397202E+09 |
| December | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 662690.65 | 0.439033E+09 |
| Annual Sum or Average | 0.505732E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.225011E+10 | 0.262266E+10 |
| Minimum of Months | 0.389025E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8588339.17 |
| Maximum of Months | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.539379E+09 | 0.463124E+09 |
Report: SpaceGainsMonthly
For: T NE APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3913299.51 | 0.399058E+09 |
| February | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.372422E+09 |
| March | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11469708.24 | 0.445401E+09 |
| April | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.158386E+09 | 0.128591E+09 |
| May | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.303421E+09 | 66363638.55 |
| June | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.539379E+09 | 12554801.75 |
| July | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.482475E+09 | 8595197.04 |
| August | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.353457E+09 | 16216787.55 |
| September | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.285006E+09 | 32499409.73 |
| October | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103240E+09 | 0.213540E+09 |
| November | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8708601.20 | 0.370072E+09 |
| December | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 664383.41 | 0.409709E+09 |
| Annual Sum or Average | 0.512427E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.225012E+10 | 0.247502E+10 |
| Minimum of Months | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8595197.04 |
| Maximum of Months | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.539379E+09 | 0.445401E+09 |
Report: SpaceGainsMonthly
For: T N1 APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2489900.59 | 0.242385E+09 |
| February | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.225215E+09 |
| March | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6920332.38 | 0.270952E+09 |
| April | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 95542702.72 | 79098165.18 |
| May | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.183016E+09 | 40762383.96 |
| June | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.325340E+09 | 7574371.27 |
| July | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.291017E+09 | 5189156.07 |
| August | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.213196E+09 | 9791892.32 |
| September | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.171908E+09 | 19731168.94 |
| October | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 62285501.14 | 0.130600E+09 |
| November | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5383013.52 | 0.226440E+09 |
| December | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 452190.71 | 0.247815E+09 |
| Annual Sum or Average | 0.512427E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.135755E+10 | 0.150556E+10 |
| Minimum of Months | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5189156.07 |
| Maximum of Months | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.325340E+09 | 0.270952E+09 |
Report: SpaceGainsMonthly
For: T N2 APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2466118.89 | 0.242366E+09 |
| February | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.225383E+09 |
| March | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6918783.51 | 0.271200E+09 |
| April | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 95541109.28 | 79121523.52 |
| May | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.183016E+09 | 40753646.90 |
| June | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.325340E+09 | 7574370.92 |
| July | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.291017E+09 | 5189077.56 |
| August | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.213196E+09 | 9791892.14 |
| September | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.171908E+09 | 19731207.65 |
| October | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 62282767.68 | 0.130732E+09 |
| November | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5364266.55 | 0.226442E+09 |
| December | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 443499.80 | 0.247822E+09 |
| Annual Sum or Average | 0.512427E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.135749E+10 | 0.150611E+10 |
| Minimum of Months | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5189077.56 |
| Maximum of Months | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.325340E+09 | 0.271200E+09 |
Report: SpaceGainsMonthly
For: T S1 APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2354504.36 | 0.263501E+09 |
| February | 0.389025E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.248451E+09 |
| March | 0.418950E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6918232.03 | 0.284808E+09 |
| April | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 95534743.85 | 79849372.90 |
| May | 0.424935E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.183016E+09 | 40579758.25 |
| June | 0.406980E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.325340E+09 | 7572509.29 |
| July | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.291017E+09 | 5186098.11 |
| August | 0.418950E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.213196E+09 | 9791893.77 |
| September | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.171908E+09 | 19722742.00 |
| October | 0.430920E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 62271605.61 | 0.139866E+09 |
| November | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5252754.78 | 0.246035E+09 |
| December | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 399720.89 | 0.268394E+09 |
| Annual Sum or Average | 0.505732E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.135721E+10 | 0.161376E+10 |
| Minimum of Months | 0.389025E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5186098.11 |
| Maximum of Months | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.325340E+09 | 0.284808E+09 |
Report: SpaceGainsMonthly
For: T S2 APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2354504.91 | 0.263495E+09 |
| February | 0.389025E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.248561E+09 |
| March | 0.418950E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6918231.97 | 0.284945E+09 |
| April | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 95534748.28 | 79860895.49 |
| May | 0.424935E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.183016E+09 | 40572814.26 |
| June | 0.406980E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.325340E+09 | 7572446.50 |
| July | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.291017E+09 | 5185953.56 |
| August | 0.418950E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.213196E+09 | 9791893.60 |
| September | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.171908E+09 | 19722678.57 |
| October | 0.430920E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 62271608.53 | 0.139910E+09 |
| November | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5252755.28 | 0.246014E+09 |
| December | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 399720.95 | 0.268421E+09 |
| Annual Sum or Average | 0.505732E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.135721E+10 | 0.161405E+10 |
| Minimum of Months | 0.389025E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5185953.56 |
| Maximum of Months | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.325340E+09 | 0.284945E+09 |
Report: SpaceGainsMonthly
For: T CORRIDOR
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.727675E+09 | 0.992689E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 451658.84 | 77945200.16 |
| February | 0.657255E+09 | 0.896622E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71727233.77 |
| March | 0.727675E+09 | 0.992689E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 973604.98 | 86741644.13 |
| April | 0.704201E+09 | 0.960667E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15195516.75 | 29593321.08 |
| May | 0.727675E+09 | 0.992689E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32629094.21 | 16320440.10 |
| June | 0.704201E+09 | 0.960667E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64488556.33 | 4556262.88 |
| July | 0.727675E+09 | 0.992689E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54054537.94 | 4164936.04 |
| August | 0.727675E+09 | 0.992689E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38839105.72 | 6780522.10 |
| September | 0.704201E+09 | 0.960667E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29176812.06 | 11626641.47 |
| October | 0.727675E+09 | 0.992689E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10563637.77 | 46373884.55 |
| November | 0.704201E+09 | 0.960667E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 685862.54 | 73717259.74 |
| December | 0.727675E+09 | 0.992689E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99625.83 | 75645294.18 |
| Annual Sum or Average | 0.856778E+10 | 0.116881E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.247158E+09 | 0.505193E+09 |
| Minimum of Months | 0.657255E+09 | 0.896622E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4164936.04 |
| Maximum of Months | 0.727675E+09 | 0.992689E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64488556.33 | 86741644.13 |
Report: SpaceGainsMonthly
For: G CORRIDOR
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.727675E+09 | 0.992689E+09 | 0.299778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8859445.06 | 0.156677E+10 |
| February | 0.657255E+09 | 0.896622E+09 | 0.270767E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.170478E+10 |
| March | 0.727675E+09 | 0.992689E+09 | 0.299778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 30098109.09 | 0.141825E+10 |
| April | 0.704201E+09 | 0.960667E+09 | 0.290107E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.345254E+09 | 0.604905E+09 |
| May | 0.727675E+09 | 0.992689E+09 | 0.299778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.592990E+09 | 0.353496E+09 |
| June | 0.704201E+09 | 0.960667E+09 | 0.290107E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109382E+10 | 0.111498E+09 |
| July | 0.727675E+09 | 0.992689E+09 | 0.299778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.878126E+09 | 0.108951E+09 |
| August | 0.727675E+09 | 0.992689E+09 | 0.299778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.822545E+09 | 0.168118E+09 |
| September | 0.704201E+09 | 0.960667E+09 | 0.290107E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.557718E+09 | 0.264385E+09 |
| October | 0.727675E+09 | 0.992689E+09 | 0.299778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.201893E+09 | 0.101513E+10 |
| November | 0.704201E+09 | 0.960667E+09 | 0.290107E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6787608.15 | 0.161452E+10 |
| December | 0.727675E+09 | 0.992689E+09 | 0.299778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1738059.86 | 0.208812E+10 |
| Annual Sum or Average | 0.856778E+10 | 0.116881E+11 | 0.352964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.453982E+10 | 0.110189E+11 |
| Minimum of Months | 0.657255E+09 | 0.896622E+09 | 0.270767E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108951E+09 |
| Maximum of Months | 0.727675E+09 | 0.992689E+09 | 0.299778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109382E+10 | 0.208812E+10 |
Report: SpaceGainsMonthly
For: M CORRIDOR
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.727675E+09 | 0.992689E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 185073.44 | 70978610.50 |
| February | 0.657255E+09 | 0.896622E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65135094.52 |
| March | 0.727675E+09 | 0.992689E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 518003.88 | 78009644.80 |
| April | 0.704201E+09 | 0.960667E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12490104.90 | 25467279.51 |
| May | 0.727675E+09 | 0.992689E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26862016.20 | 13998087.35 |
| June | 0.704201E+09 | 0.960667E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53322490.40 | 3881784.74 |
| July | 0.727675E+09 | 0.992689E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45482200.34 | 3314234.47 |
| August | 0.727675E+09 | 0.992689E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32419772.15 | 5384353.33 |
| September | 0.704201E+09 | 0.960667E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24609230.36 | 9468207.85 |
| October | 0.727675E+09 | 0.992689E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8331208.45 | 41804103.81 |
| November | 0.704201E+09 | 0.960667E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 337345.76 | 66727192.48 |
| December | 0.727675E+09 | 0.992689E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34139.03 | 67344741.53 |
| Annual Sum or Average | 0.856778E+10 | 0.116881E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.204592E+09 | 0.451513E+09 |
| Minimum of Months | 0.657255E+09 | 0.896622E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3314234.47 |
| Maximum of Months | 0.727675E+09 | 0.992689E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53322490.40 | 78009644.80 |
Report: PeakSpaceGainsMonthly
For: G SW APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 43.26 | 31-JAN-14:00 | 364.85 | 01-JAN-01:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 409.82 | 02-FEB-23:00 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 91.53 | 15-MAR-13:00 | 330.85 | 28-MAR-04:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 285.02 | 30-APR-16:00 | 186.10 | 21-APR-06:00 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 439.01 | 20-MAY-14:00 | 133.25 | 23-MAY-05:00 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 565.57 | 19-JUN-14:00 | 58.22 | 13-JUN-06:00 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 554.88 | 22-JUL-16:00 | 71.59 | 26-JUL-24:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 437.61 | 13-AUG-16:00 | 144.02 | 05-AUG-18:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 347.28 | 01-SEP-16:00 | 85.78 | 15-SEP-07:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 230.76 | 10-OCT-15:00 | 297.63 | 22-OCT-14:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 70.72 | 01-NOV-16:00 | 402.77 | 24-NOV-10:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.67 | 25-DEC-16:00 | 313.99 | 07-DEC-08:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.22 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 565.57 | 409.82 |
Report: PeakSpaceGainsMonthly
For: G NW APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 43.26 | 31-JAN-14:00 | 360.40 | 01-JAN-01:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 359.29 | 02-FEB-23:00 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 91.54 | 15-MAR-13:00 | 330.85 | 28-MAR-04:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 285.02 | 30-APR-16:00 | 184.15 | 21-APR-06:00 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 439.01 | 20-MAY-14:00 | 133.16 | 23-MAY-05:00 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 565.57 | 19-JUN-14:00 | 58.22 | 13-JUN-06:00 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 554.88 | 22-JUL-16:00 | 71.59 | 26-JUL-24:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 437.61 | 13-AUG-16:00 | 144.02 | 05-AUG-18:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 347.28 | 01-SEP-16:00 | 85.78 | 15-SEP-07:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 230.76 | 10-OCT-15:00 | 289.21 | 22-OCT-14:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 70.72 | 01-NOV-16:00 | 357.04 | 24-NOV-10:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.67 | 25-DEC-16:00 | 313.99 | 07-DEC-08:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.22 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 565.57 | 360.40 |
Report: PeakSpaceGainsMonthly
For: OFFICE
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 451.21 | 03-JAN-08:09 | 582.92 | 03-JAN-08:09 | 588.62 | 03-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 43.26 | 31-JAN-14:00 | 360.37 | 01-JAN-01:00 |
| February | 451.21 | 01-FEB-08:09 | 582.92 | 01-FEB-08:09 | 588.62 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 432.68 | 02-FEB-23:00 |
| March | 451.21 | 01-MAR-08:09 | 582.92 | 01-MAR-08:09 | 588.62 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 91.53 | 15-MAR-13:00 | 331.99 | 28-MAR-04:00 |
| April | 451.21 | 03-APR-07:10 | 582.92 | 03-APR-07:10 | 588.62 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 237.41 | 10-APR-16:00 | 223.85 | 16-APR-09:00 |
| May | 451.21 | 01-MAY-07:10 | 582.92 | 01-MAY-07:10 | 588.62 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 312.72 | 19-MAY-14:00 | 168.05 | 23-MAY-05:00 |
| June | 451.21 | 01-JUN-07:10 | 582.92 | 01-JUN-07:10 | 588.62 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 565.58 | 19-JUN-14:00 | 113.27 | 13-JUN-06:00 |
| July | 451.21 | 03-JUL-07:10 | 582.92 | 03-JUL-07:10 | 588.62 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 438.06 | 21-JUL-15:00 | 210.84 | 17-JUL-20:00 |
| August | 451.21 | 01-AUG-07:10 | 582.92 | 01-AUG-07:10 | 588.62 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 386.34 | 09-AUG-15:00 | 251.48 | 05-AUG-17:05 |
| September | 451.21 | 01-SEP-07:10 | 582.92 | 01-SEP-07:10 | 588.62 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 347.26 | 01-SEP-16:00 | 208.52 | 03-SEP-05:00 |
| October | 451.21 | 02-OCT-07:10 | 582.92 | 02-OCT-07:10 | 588.62 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 230.77 | 10-OCT-15:00 | 427.89 | 22-OCT-14:00 |
| November | 451.21 | 01-NOV-07:10 | 582.92 | 01-NOV-07:10 | 588.62 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 70.72 | 01-NOV-16:00 | 428.67 | 24-NOV-10:00 |
| December | 451.21 | 01-DEC-08:09 | 582.92 | 01-DEC-08:09 | 588.62 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 18.25 | 21-DEC-15:00 | 323.42 | 07-DEC-08:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 451.21 | 582.92 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 113.27 | |||||
| Maximum of Months | 451.21 | 582.92 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 565.58 | 432.68 |
Report: PeakSpaceGainsMonthly
For: G NE APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 43.26 | 31-JAN-14:00 | 360.40 | 01-JAN-01:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 357.99 | 02-FEB-23:00 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 91.53 | 15-MAR-13:00 | 330.85 | 28-MAR-04:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 285.02 | 30-APR-15:40 | 184.11 | 21-APR-06:00 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 439.01 | 20-MAY-14:00 | 133.10 | 23-MAY-05:00 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 565.57 | 19-JUN-14:00 | 58.22 | 13-JUN-06:00 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 554.88 | 22-JUL-16:00 | 71.59 | 26-JUL-24:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 437.61 | 13-AUG-16:00 | 144.02 | 05-AUG-18:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 347.28 | 01-SEP-16:00 | 85.78 | 15-SEP-07:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 230.76 | 10-OCT-15:00 | 292.95 | 22-OCT-14:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 70.72 | 01-NOV-16:00 | 367.67 | 24-NOV-10:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.67 | 25-DEC-16:00 | 313.99 | 07-DEC-08:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.22 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 565.57 | 367.67 |
Report: PeakSpaceGainsMonthly
For: G N1 APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 26.09 | 31-JAN-14:00 | 217.38 | 01-JAN-01:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 232.27 | 02-FEB-23:00 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 55.21 | 15-MAR-13:00 | 199.56 | 28-MAR-04:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 171.92 | 30-APR-16:00 | 114.81 | 21-APR-06:00 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 264.80 | 20-MAY-14:00 | 80.32 | 23-MAY-05:00 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 341.14 | 19-JUN-14:00 | 35.11 | 13-JUN-06:00 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 334.69 | 22-JUL-16:00 | 43.18 | 26-JUL-24:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 263.95 | 13-AUG-16:00 | 86.87 | 05-AUG-18:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 209.47 | 01-SEP-16:00 | 51.74 | 15-SEP-07:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 139.19 | 10-OCT-15:00 | 176.27 | 22-OCT-14:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 42.66 | 01-NOV-16:00 | 228.01 | 24-NOV-10:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.07 | 25-DEC-16:00 | 189.39 | 07-DEC-08:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.11 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 341.14 | 232.27 |
Report: PeakSpaceGainsMonthly
For: G N2 APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 26.09 | 31-JAN-14:00 | 217.38 | 01-JAN-01:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 232.31 | 02-FEB-23:00 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 55.21 | 15-MAR-13:00 | 199.56 | 28-MAR-04:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 171.92 | 30-APR-16:00 | 114.80 | 21-APR-06:00 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 264.80 | 20-MAY-14:00 | 80.32 | 23-MAY-05:00 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 341.14 | 19-JUN-14:00 | 35.11 | 13-JUN-06:00 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 334.69 | 22-JUL-16:00 | 43.18 | 26-JUL-24:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 263.95 | 13-AUG-16:00 | 86.87 | 05-AUG-18:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 209.47 | 01-SEP-16:00 | 51.74 | 15-SEP-07:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 139.19 | 10-OCT-15:00 | 176.38 | 22-OCT-14:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 42.66 | 01-NOV-16:00 | 228.14 | 24-NOV-10:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.07 | 25-DEC-16:00 | 189.39 | 07-DEC-08:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.11 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 341.14 | 232.31 |
Report: PeakSpaceGainsMonthly
For: G S1 APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 26.09 | 31-JAN-14:00 | 233.14 | 01-JAN-01:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 262.87 | 02-FEB-23:00 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 55.21 | 15-MAR-13:00 | 203.30 | 28-MAR-04:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 171.92 | 30-APR-15:30 | 116.08 | 21-APR-06:00 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 264.80 | 20-MAY-14:00 | 80.32 | 23-MAY-05:00 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 341.14 | 19-JUN-14:00 | 35.11 | 13-JUN-06:00 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 334.69 | 22-JUL-16:00 | 43.18 | 26-JUL-24:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 263.95 | 13-AUG-16:00 | 86.87 | 05-AUG-18:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 209.47 | 01-SEP-16:00 | 51.74 | 15-SEP-07:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 139.19 | 10-OCT-15:00 | 179.52 | 22-OCT-14:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 42.66 | 01-NOV-16:00 | 256.78 | 24-NOV-10:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.07 | 25-DEC-16:00 | 200.14 | 07-DEC-08:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.11 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 341.14 | 262.87 |
Report: PeakSpaceGainsMonthly
For: G S2 APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 26.09 | 31-JAN-14:00 | 232.25 | 01-JAN-01:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 264.02 | 02-FEB-23:00 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 55.21 | 15-MAR-13:00 | 204.05 | 28-MAR-04:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 171.92 | 30-APR-15:20 | 116.84 | 21-APR-06:00 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 264.80 | 20-MAY-14:00 | 80.32 | 23-MAY-05:00 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 341.14 | 19-JUN-14:00 | 35.11 | 13-JUN-06:00 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 334.69 | 22-JUL-16:00 | 43.18 | 26-JUL-24:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 263.95 | 13-AUG-16:00 | 86.87 | 05-AUG-18:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 209.47 | 01-SEP-16:00 | 51.74 | 15-SEP-07:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 139.19 | 10-OCT-15:00 | 179.52 | 22-OCT-14:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 42.66 | 01-NOV-16:00 | 258.43 | 24-NOV-10:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.07 | 25-DEC-16:00 | 200.74 | 07-DEC-08:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.11 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 341.14 | 264.02 |
Report: PeakSpaceGainsMonthly
For: M SW APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 61.86 | 31-JAN-14:00 | 535.00 | 01-JAN-01:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 599.06 | 02-FEB-23:00 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 130.72 | 15-MAR-13:00 | 482.97 | 28-MAR-04:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 408.69 | 30-APR-16:00 | 269.89 | 21-APR-06:00 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 629.84 | 20-MAY-14:00 | 191.79 | 23-MAY-05:00 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 811.70 | 19-JUN-14:00 | 84.08 | 13-JUN-06:00 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 796.27 | 22-JUL-16:00 | 103.56 | 26-JUL-24:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 627.98 | 13-AUG-16:00 | 207.55 | 05-AUG-18:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 498.17 | 01-SEP-16:00 | 123.75 | 15-SEP-07:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 331.03 | 10-OCT-15:00 | 412.97 | 22-OCT-14:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 101.13 | 01-NOV-16:00 | 547.25 | 24-NOV-10:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 30.83 | 25-DEC-16:00 | 451.72 | 07-DEC-08:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.08 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 811.70 | 599.06 |
Report: PeakSpaceGainsMonthly
For: M NW APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 61.86 | 31-JAN-14:00 | 518.59 | 01-JAN-01:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 532.94 | 02-FEB-23:00 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 130.72 | 15-MAR-13:00 | 476.00 | 28-MAR-04:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 408.69 | 30-APR-16:00 | 268.17 | 21-APR-06:00 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 629.84 | 20-MAY-14:00 | 191.79 | 23-MAY-05:00 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 811.70 | 19-JUN-14:00 | 84.08 | 13-JUN-06:00 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 796.28 | 22-JUL-16:00 | 103.56 | 26-JUL-24:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 627.98 | 13-AUG-16:00 | 207.55 | 05-AUG-18:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 498.17 | 01-SEP-16:00 | 123.75 | 15-SEP-07:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 331.03 | 10-OCT-15:00 | 393.79 | 22-OCT-14:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 101.13 | 01-NOV-16:00 | 497.74 | 24-NOV-10:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 30.83 | 25-DEC-16:00 | 451.72 | 07-DEC-08:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.08 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 811.70 | 532.94 |
Report: PeakSpaceGainsMonthly
For: M SE APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 61.86 | 31-JAN-14:00 | 533.16 | 01-JAN-01:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 595.98 | 02-FEB-23:00 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 130.72 | 15-MAR-13:00 | 482.14 | 28-MAR-04:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 408.69 | 30-APR-15:20 | 269.72 | 21-APR-06:00 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 629.84 | 20-MAY-14:00 | 191.79 | 23-MAY-05:00 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 811.70 | 19-JUN-14:00 | 84.08 | 13-JUN-06:00 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 796.27 | 22-JUL-16:00 | 103.56 | 26-JUL-24:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 627.98 | 13-AUG-16:00 | 207.55 | 05-AUG-18:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 498.17 | 01-SEP-16:00 | 123.75 | 15-SEP-07:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 331.03 | 10-OCT-15:00 | 417.95 | 22-OCT-14:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 101.13 | 01-NOV-16:00 | 568.59 | 24-NOV-10:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 30.83 | 25-DEC-16:00 | 451.72 | 07-DEC-08:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.08 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 811.70 | 595.98 |
Report: PeakSpaceGainsMonthly
For: M NE APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 61.86 | 31-JAN-14:00 | 518.59 | 01-JAN-01:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 529.54 | 02-FEB-23:00 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 130.72 | 15-MAR-13:00 | 476.00 | 28-MAR-04:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 408.69 | 30-APR-15:30 | 267.98 | 21-APR-06:00 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 629.84 | 20-MAY-14:00 | 191.79 | 23-MAY-05:00 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 811.70 | 19-JUN-14:00 | 84.08 | 13-JUN-06:00 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 796.27 | 22-JUL-16:00 | 103.56 | 26-JUL-24:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 627.98 | 13-AUG-16:00 | 207.55 | 05-AUG-18:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 498.17 | 01-SEP-16:00 | 123.75 | 15-SEP-07:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 331.03 | 10-OCT-15:00 | 399.86 | 22-OCT-14:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 101.13 | 01-NOV-16:00 | 497.74 | 24-NOV-10:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 30.83 | 25-DEC-16:00 | 451.72 | 07-DEC-08:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.08 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 811.70 | 529.54 |
Report: PeakSpaceGainsMonthly
For: M N1 APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 37.31 | 31-JAN-14:00 | 312.80 | 01-JAN-01:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 345.23 | 02-FEB-23:00 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 78.85 | 15-MAR-13:00 | 292.20 | 28-MAR-04:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 246.51 | 30-APR-16:00 | 167.11 | 21-APR-06:00 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 379.90 | 20-MAY-14:00 | 115.68 | 23-MAY-05:00 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 489.59 | 19-JUN-14:00 | 50.71 | 13-JUN-06:00 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 480.29 | 22-JUL-16:00 | 62.47 | 26-JUL-24:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 378.78 | 13-AUG-16:00 | 125.19 | 05-AUG-18:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 300.49 | 01-SEP-16:00 | 74.64 | 15-SEP-07:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 199.67 | 10-OCT-15:00 | 243.44 | 22-OCT-14:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 61.00 | 01-NOV-16:00 | 309.08 | 24-NOV-10:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.89 | 21-DEC-14:50 | 272.47 | 07-DEC-08:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.71 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 489.59 | 345.23 |
Report: PeakSpaceGainsMonthly
For: M N2 APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 37.31 | 31-JAN-14:00 | 312.80 | 01-JAN-01:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 345.24 | 02-FEB-23:00 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 78.85 | 15-MAR-13:00 | 292.30 | 28-MAR-04:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 246.51 | 30-APR-16:00 | 167.07 | 21-APR-06:00 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 379.90 | 20-MAY-14:00 | 115.68 | 23-MAY-05:00 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 489.59 | 19-JUN-14:00 | 50.71 | 13-JUN-06:00 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 480.29 | 22-JUL-16:00 | 62.47 | 26-JUL-24:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 378.78 | 13-AUG-16:00 | 125.19 | 05-AUG-18:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 300.49 | 01-SEP-16:00 | 74.64 | 15-SEP-07:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 199.67 | 10-OCT-15:00 | 243.64 | 22-OCT-14:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 61.00 | 01-NOV-16:00 | 309.22 | 24-NOV-10:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.79 | 21-DEC-14:50 | 272.47 | 07-DEC-08:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.71 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 489.59 | 345.24 |
Report: PeakSpaceGainsMonthly
For: M S1 APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 37.31 | 31-JAN-14:00 | 343.31 | 01-JAN-01:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 382.10 | 02-FEB-23:00 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 78.85 | 15-MAR-13:00 | 305.55 | 28-MAR-04:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 246.51 | 30-APR-15:20 | 168.24 | 21-APR-06:00 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 379.90 | 20-MAY-14:00 | 115.68 | 23-MAY-05:00 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 489.59 | 19-JUN-14:00 | 50.71 | 13-JUN-06:00 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 480.29 | 22-JUL-16:00 | 62.47 | 26-JUL-24:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 378.78 | 13-AUG-16:00 | 125.19 | 05-AUG-18:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 300.49 | 01-SEP-16:00 | 74.64 | 15-SEP-07:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 199.67 | 10-OCT-15:00 | 254.74 | 22-OCT-14:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 61.00 | 01-NOV-16:00 | 358.25 | 24-NOV-10:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.59 | 25-DEC-16:00 | 280.86 | 07-DEC-08:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.71 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 489.59 | 382.10 |
Report: PeakSpaceGainsMonthly
For: M S2 APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 37.31 | 31-JAN-14:00 | 343.27 | 01-JAN-01:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 382.02 | 02-FEB-23:00 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 78.85 | 15-MAR-13:00 | 305.64 | 28-MAR-04:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 246.51 | 30-APR-15:20 | 168.20 | 21-APR-06:00 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 379.90 | 20-MAY-14:00 | 115.68 | 23-MAY-05:00 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 489.59 | 19-JUN-14:00 | 50.71 | 13-JUN-06:00 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 480.29 | 22-JUL-16:00 | 62.47 | 26-JUL-24:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 378.78 | 13-AUG-16:00 | 125.19 | 05-AUG-18:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 300.49 | 01-SEP-16:00 | 74.64 | 15-SEP-07:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 199.67 | 10-OCT-15:00 | 254.87 | 22-OCT-14:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 61.00 | 01-NOV-16:00 | 358.57 | 24-NOV-10:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.59 | 25-DEC-16:00 | 280.94 | 07-DEC-08:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.71 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 489.59 | 382.02 |
Report: PeakSpaceGainsMonthly
For: T SW APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 81.02 | 31-JAN-14:00 | 687.74 | 01-JAN-01:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 682.83 | 02-FEB-23:00 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 170.76 | 15-MAR-13:00 | 631.09 | 28-MAR-04:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 538.22 | 30-APR-16:00 | 307.83 | 21-APR-06:00 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 830.38 | 20-MAY-14:00 | 228.66 | 23-MAY-05:00 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1070.86 | 19-JUN-14:00 | 110.65 | 13-JUN-06:00 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1050.31 | 22-JUL-16:00 | 138.79 | 26-JUL-24:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 828.33 | 13-AUG-16:00 | 276.10 | 05-AUG-18:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 656.60 | 01-SEP-16:00 | 154.18 | 03-SEP-05:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 436.30 | 10-OCT-15:00 | 512.27 | 22-OCT-14:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 132.44 | 01-NOV-16:00 | 679.34 | 22-NOV-12:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 39.96 | 25-DEC-16:00 | 598.84 | 07-DEC-08:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 110.65 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 1070.86 | 687.74 |
Report: PeakSpaceGainsMonthly
For: T NW APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 81.02 | 31-JAN-14:00 | 687.74 | 01-JAN-01:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 682.83 | 02-FEB-23:00 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 170.76 | 15-MAR-13:00 | 631.09 | 28-MAR-04:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 538.22 | 30-APR-16:00 | 307.83 | 21-APR-06:00 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 830.38 | 20-MAY-14:00 | 229.36 | 23-MAY-05:00 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1070.86 | 19-JUN-14:00 | 112.31 | 13-JUN-06:00 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1050.31 | 22-JUL-16:00 | 138.79 | 26-JUL-24:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 828.33 | 13-AUG-16:00 | 276.10 | 05-AUG-18:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 656.60 | 01-SEP-16:00 | 154.18 | 03-SEP-05:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 436.30 | 10-OCT-15:00 | 466.95 | 22-OCT-14:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 132.44 | 01-NOV-16:00 | 660.56 | 24-NOV-10:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 39.96 | 25-DEC-16:00 | 598.84 | 07-DEC-08:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 112.31 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 1070.86 | 687.74 |
Report: PeakSpaceGainsMonthly
For: T SE APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 81.02 | 31-JAN-14:00 | 687.74 | 01-JAN-01:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 682.83 | 02-FEB-23:00 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 170.76 | 15-MAR-13:00 | 631.09 | 28-MAR-04:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 538.22 | 30-APR-15:20 | 307.83 | 21-APR-06:00 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 830.39 | 20-MAY-14:00 | 226.48 | 23-MAY-05:00 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1070.86 | 19-JUN-14:00 | 112.31 | 13-JUN-06:00 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1050.31 | 22-JUL-16:00 | 138.79 | 26-JUL-24:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 828.33 | 13-AUG-16:00 | 276.10 | 05-AUG-18:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 656.60 | 01-SEP-16:00 | 155.03 | 15-SEP-07:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 436.30 | 10-OCT-15:00 | 523.08 | 22-OCT-14:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 132.44 | 01-NOV-16:00 | 710.76 | 22-NOV-12:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 39.96 | 25-DEC-16:00 | 598.84 | 07-DEC-08:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 112.31 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 1070.86 | 710.76 |
Report: PeakSpaceGainsMonthly
For: T NE APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 81.02 | 31-JAN-14:00 | 687.74 | 01-JAN-01:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 682.83 | 02-FEB-23:00 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 170.76 | 15-MAR-13:00 | 631.09 | 28-MAR-04:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 538.22 | 30-APR-15:20 | 307.83 | 21-APR-06:00 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 830.39 | 20-MAY-14:00 | 227.16 | 23-MAY-05:00 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1070.86 | 19-JUN-14:00 | 112.31 | 13-JUN-06:00 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1050.31 | 22-JUL-16:00 | 138.79 | 26-JUL-24:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 828.33 | 13-AUG-16:00 | 276.10 | 05-AUG-18:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 656.60 | 01-SEP-16:00 | 156.94 | 15-SEP-07:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 436.30 | 10-OCT-15:00 | 483.05 | 22-OCT-14:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 132.44 | 01-NOV-16:00 | 660.56 | 24-NOV-10:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 39.96 | 25-DEC-16:00 | 598.84 | 07-DEC-08:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 112.31 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 1070.86 | 687.74 |
Report: PeakSpaceGainsMonthly
For: T N1 APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 48.87 | 31-JAN-14:00 | 414.83 | 01-JAN-01:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 411.86 | 02-FEB-23:00 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 103.00 | 15-MAR-13:00 | 380.66 | 28-MAR-04:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 324.64 | 30-APR-15:30 | 185.67 | 21-APR-06:00 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 500.87 | 20-MAY-14:00 | 145.03 | 23-MAY-05:00 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 645.91 | 19-JUN-14:00 | 67.74 | 13-JUN-06:00 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 633.52 | 22-JUL-16:00 | 83.72 | 26-JUL-24:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 499.63 | 13-AUG-16:00 | 166.53 | 05-AUG-18:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 396.04 | 01-SEP-16:00 | 94.95 | 15-SEP-07:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 263.16 | 10-OCT-15:00 | 294.56 | 22-OCT-14:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 79.89 | 01-NOV-16:00 | 398.44 | 24-NOV-10:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.11 | 25-DEC-16:00 | 361.21 | 07-DEC-08:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.74 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 645.91 | 414.83 |
Report: PeakSpaceGainsMonthly
For: T N2 APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 48.87 | 31-JAN-14:00 | 414.83 | 01-JAN-01:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 411.86 | 02-FEB-23:00 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 103.00 | 15-MAR-13:00 | 380.66 | 28-MAR-04:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 324.64 | 30-APR-15:30 | 185.67 | 21-APR-06:00 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 500.87 | 20-MAY-14:00 | 144.91 | 23-MAY-05:00 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 645.91 | 19-JUN-14:00 | 67.74 | 13-JUN-06:00 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 633.52 | 22-JUL-16:00 | 83.72 | 26-JUL-24:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 499.63 | 13-AUG-16:00 | 166.53 | 05-AUG-18:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 396.04 | 01-SEP-16:00 | 94.97 | 15-SEP-07:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 263.16 | 10-OCT-15:00 | 295.54 | 22-OCT-14:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 79.89 | 01-NOV-16:00 | 398.44 | 24-NOV-10:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.11 | 25-DEC-16:00 | 361.21 | 07-DEC-08:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.74 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 645.91 | 414.83 |
Report: PeakSpaceGainsMonthly
For: T S1 APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 48.87 | 31-JAN-14:00 | 414.83 | 01-JAN-01:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 426.37 | 02-FEB-23:00 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 103.00 | 15-MAR-13:00 | 380.66 | 28-MAR-04:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 324.64 | 30-APR-15:20 | 185.67 | 21-APR-06:00 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 500.87 | 20-MAY-14:00 | 144.58 | 23-MAY-05:00 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 645.91 | 19-JUN-14:00 | 67.74 | 13-JUN-06:00 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 633.52 | 22-JUL-16:00 | 83.72 | 26-JUL-24:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 499.63 | 13-AUG-16:00 | 166.53 | 05-AUG-18:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 396.04 | 01-SEP-16:00 | 93.76 | 15-SEP-07:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 263.16 | 10-OCT-15:00 | 321.84 | 22-OCT-14:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 79.89 | 01-NOV-16:00 | 429.24 | 22-NOV-12:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.10 | 25-DEC-16:00 | 361.21 | 07-DEC-08:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.74 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 645.91 | 429.24 |
Report: PeakSpaceGainsMonthly
For: T S2 APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 48.87 | 31-JAN-14:00 | 414.83 | 01-JAN-01:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 425.73 | 02-FEB-23:00 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 103.00 | 15-MAR-13:00 | 380.66 | 28-MAR-04:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 324.64 | 30-APR-15:20 | 185.67 | 21-APR-06:00 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 500.87 | 20-MAY-14:00 | 144.46 | 23-MAY-05:00 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 645.91 | 19-JUN-14:00 | 67.74 | 13-JUN-06:00 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 633.52 | 22-JUL-16:00 | 83.72 | 26-JUL-24:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 499.63 | 13-AUG-16:00 | 166.53 | 05-AUG-18:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 396.04 | 01-SEP-16:00 | 93.78 | 15-SEP-07:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 263.16 | 10-OCT-15:00 | 322.36 | 22-OCT-14:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 79.89 | 01-NOV-16:00 | 429.24 | 22-NOV-12:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.10 | 25-DEC-16:00 | 361.21 | 07-DEC-08:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.74 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 645.91 | 429.24 |
Report: PeakSpaceGainsMonthly
For: T CORRIDOR
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 397.10 | 01-JAN-00:10 | 370.63 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.15 | 31-JAN-14:00 | 119.49 | 01-JAN-01:00 |
| February | 397.10 | 01-FEB-00:10 | 370.63 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 126.86 | 02-FEB-23:00 |
| March | 397.10 | 01-MAR-00:10 | 370.63 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.99 | 15-MAR-13:00 | 110.41 | 28-MAR-04:00 |
| April | 397.10 | 01-APR-00:10 | 370.63 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.28 | 30-APR-15:00 | 63.76 | 26-APR-21:00 |
| May | 397.10 | 01-MAY-00:10 | 370.63 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 107.29 | 20-MAY-14:00 | 47.09 | 23-MAY-05:00 |
| June | 397.10 | 01-JUN-00:10 | 370.63 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 141.71 | 19-JUN-14:00 | 25.13 | 13-JUN-06:00 |
| July | 397.10 | 01-JUL-00:10 | 370.63 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 130.83 | 22-JUL-16:00 | 41.56 | 26-JUL-24:00 |
| August | 397.10 | 01-AUG-00:10 | 370.63 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 104.20 | 13-AUG-16:00 | 77.24 | 28-AUG-16:55 |
| September | 397.10 | 01-SEP-00:10 | 370.63 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.34 | 17-SEP-12:00 | 41.25 | 03-SEP-05:00 |
| October | 397.10 | 01-OCT-00:10 | 370.63 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.17 | 10-OCT-15:00 | 110.56 | 22-OCT-14:00 |
| November | 397.10 | 01-NOV-00:10 | 370.63 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.27 | 19-NOV-13:00 | 123.72 | 22-NOV-12:00 |
| December | 397.10 | 01-DEC-00:10 | 370.63 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.10 | 25-DEC-14:00 | 95.28 | 07-DEC-08:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
| Minimum of Months | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.13 | ||||
| Maximum of Months | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 141.71 | 126.86 |
Report: PeakSpaceGainsMonthly
For: G CORRIDOR
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 397.10 | 01-JAN-00:10 | 370.63 | 01-JAN-00:10 | 208.40 | 01-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1178.17 | 31-JAN-17:02 | 10569.03 | 01-JAN-07:01 |
| February | 397.10 | 01-FEB-00:10 | 370.63 | 01-FEB-00:10 | 208.40 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 9828.24 | 01-FEB-07:01 |
| March | 397.10 | 01-MAR-00:10 | 370.63 | 01-MAR-00:10 | 208.40 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1497.83 | 16-MAR-16:03 | 11281.74 | 26-MAR-06:01 |
| April | 397.10 | 01-APR-00:10 | 370.63 | 01-APR-00:10 | 208.40 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3574.30 | 14-APR-16:02 | 7820.80 | 21-APR-06:01 |
| May | 397.10 | 01-MAY-00:10 | 370.63 | 01-MAY-00:10 | 208.40 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4515.42 | 31-MAY-16:01 | 6114.79 | 01-MAY-06:01 |
| June | 397.10 | 01-JUN-00:10 | 370.63 | 01-JUN-00:10 | 208.40 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6429.47 | 16-JUN-16:01 | 3475.55 | 21-JUN-06:02 |
| July | 397.10 | 01-JUL-00:10 | 370.63 | 01-JUL-00:10 | 208.40 | 01-JUL-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5108.81 | 05-JUL-16:01 | 3857.84 | 01-JUL-06:01 |
| August | 397.10 | 01-AUG-00:10 | 370.63 | 01-AUG-00:10 | 208.40 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6046.07 | 25-AUG-16:01 | 3494.94 | 24-AUG-06:02 |
| September | 397.10 | 01-SEP-00:10 | 370.63 | 01-SEP-00:10 | 208.40 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4578.60 | 08-SEP-16:01 | 4551.10 | 22-SEP-06:01 |
| October | 397.10 | 01-OCT-00:10 | 370.63 | 01-OCT-00:10 | 208.40 | 01-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3294.08 | 06-OCT-16:01 | 10182.23 | 25-OCT-06:01 |
| November | 397.10 | 01-NOV-00:10 | 370.63 | 01-NOV-00:10 | 208.40 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 482.66 | 01-NOV-16:02 | 12522.71 | 23-NOV-07:01 |
| December | 397.10 | 01-DEC-00:10 | 370.63 | 01-DEC-00:10 | 208.40 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 128.55 | 21-DEC-15:00 | 12455.25 | 05-DEC-07:01 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 397.10 | 370.63 | 208.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3475.55 | |||||
| Maximum of Months | 397.10 | 370.63 | 208.40 | 0.00 | 0.00 | 0.00 | 0.00 | 6429.47 | 12522.71 |
Report: PeakSpaceGainsMonthly
For: M CORRIDOR
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 397.10 | 01-JAN-00:10 | 370.63 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.03 | 31-JAN-14:00 | 102.05 | 01-JAN-01:00 |
| February | 397.10 | 01-FEB-00:10 | 370.63 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 115.10 | 02-FEB-23:00 |
| March | 397.10 | 01-MAR-00:10 | 370.63 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.05 | 15-MAR-13:00 | 94.73 | 28-MAR-04:00 |
| April | 397.10 | 01-APR-00:10 | 370.63 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.68 | 30-APR-15:00 | 53.74 | 21-APR-06:00 |
| May | 397.10 | 01-MAY-00:10 | 370.63 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.20 | 20-MAY-14:00 | 39.69 | 23-MAY-05:00 |
| June | 397.10 | 01-JUN-00:10 | 370.63 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 116.19 | 19-JUN-14:00 | 21.75 | 13-JUN-06:00 |
| July | 397.10 | 01-JUL-00:10 | 370.63 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 110.57 | 22-JUL-16:00 | 30.73 | 26-JUL-24:00 |
| August | 397.10 | 01-AUG-00:10 | 370.63 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.87 | 13-AUG-16:00 | 52.84 | 28-AUG-16:55 |
| September | 397.10 | 01-SEP-00:10 | 370.63 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.69 | 01-SEP-16:00 | 32.76 | 03-SEP-05:00 |
| October | 397.10 | 01-OCT-00:10 | 370.63 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.55 | 10-OCT-15:00 | 88.64 | 22-OCT-14:00 |
| November | 397.10 | 01-NOV-00:10 | 370.63 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.84 | 19-NOV-15:00 | 108.96 | 22-NOV-12:00 |
| December | 397.10 | 01-DEC-00:10 | 370.63 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.53 | 21-DEC-15:00 | 85.13 | 07-DEC-08:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
| Minimum of Months | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.75 | ||||
| Maximum of Months | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 116.19 | 115.10 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: G SW APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 1717.41 | 31-JAN-16:30 | 0.00 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 36.47 | 0.00 |
| February | 1148.82 | 01-FEB-15:30 | 0.00 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.29 |
| March | 1446.51 | 18-MAR-16:30 | 237.50 | 86.80 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 31.32 | 0.00 |
| April | 2089.76 | 14-APR-17:25 | 475.00 | 234.36 | 1177.25 | 0.00 | 0.00 | 0.00 | 0.00 | 165.17 | 0.00 |
| May | 2038.51 | 19-MAY-17:30 | 475.00 | 234.36 | 1177.25 | 0.00 | 0.00 | 0.00 | 0.00 | 212.00 | 0.00 |
| June | 2666.96 | 30-JUN-17:15 | 950.00 | 468.73 | 2354.49 | 0.00 | 0.00 | 0.00 | 0.00 | 476.62 | 0.00 |
| July | 2839.38 | 22-JUL-17:40 | 237.50 | 117.18 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 468.21 | 0.00 |
| August | 2836.74 | 13-AUG-16:30 | 237.50 | 86.80 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 399.92 | 0.00 |
| September | 2792.18 | 08-SEP-16:30 | 0.00 | 86.80 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 265.47 | 0.00 |
| October | 2586.24 | 10-OCT-15:30 | 0.00 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 211.72 | 0.00 |
| November | 2373.62 | 01-NOV-16:02 | 0.00 | 520.80 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 68.29 | 0.00 |
| December | 1925.94 | 25-DEC-16:30 | 237.50 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 11.74 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 1148.82 | 0.00 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 2839.38 | 950.00 | 520.80 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 476.62 | 55.29 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: G NW APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 677.80 | 31-JAN-17:02 | 617.50 | 434.00 | 2943.11 | 0.00 | 0.00 | 0.00 | 0.00 | 32.93 | 0.00 |
| February | 465.49 | 01-FEB-05:00 | 237.50 | 26.04 | 223.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 195.29 |
| March | 833.18 | 18-MAR-17:10 | 206.62 | 117.18 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 39.12 | 0.00 |
| April | 1873.80 | 14-APR-17:40 | 413.25 | 234.36 | 1177.25 | 0.00 | 0.00 | 0.00 | 0.00 | 180.71 | 0.00 |
| May | 2028.83 | 31-MAY-18:00 | 206.62 | 117.18 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 250.93 | 0.00 |
| June | 2719.53 | 29-JUN-17:50 | 206.62 | 117.18 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 388.83 | 0.00 |
| July | 2798.62 | 22-JUL-18:00 | 206.62 | 117.18 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 483.87 | 0.00 |
| August | 2622.67 | 13-AUG-17:30 | 206.62 | 117.18 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 362.24 | 0.00 |
| September | 2467.48 | 08-SEP-17:00 | 123.50 | 86.80 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 260.12 | 0.00 |
| October | 2033.98 | 04-OCT-16:50 | 123.50 | 86.80 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 222.55 | 0.00 |
| November | 1462.33 | 01-NOV-16:30 | 123.50 | 86.80 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 61.56 | 0.00 |
| December | 603.90 | 25-DEC-16:30 | 71.25 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 11.75 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 465.49 | 71.25 | 26.04 | 223.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 2798.62 | 617.50 | 434.00 | 2943.11 | 0.00 | 0.00 | 0.00 | 0.00 | 483.87 | 195.29 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: OFFICE
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 6057.53 | 30-JAN-09:02 | 1804.82 | 2331.66 | 2354.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.72 |
| February | 2743.17 | 01-FEB-09:03 | 1353.62 | 1748.75 | 1765.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 196.84 |
| March | 5628.15 | 21-MAR-08:62 | 1804.82 | 2331.66 | 2354.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.06 |
| April | 6699.47 | 17-APR-07:02 | 2707.23 | 3497.50 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77.25 |
| May | 6559.74 | 11-MAY-07:02 | 2707.23 | 3497.50 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.84 |
| June | 6449.55 | 12-JUN-07:02 | 2707.23 | 3497.50 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.60 |
| July | 6649.09 | 31-JUL-07:02 | 2707.23 | 3497.50 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.60 |
| August | 6673.23 | 22-AUG-07:02 | 2707.23 | 3497.50 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.87 |
| September | 6815.62 | 27-SEP-07:02 | 2707.23 | 3497.50 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 104.71 |
| October | 6835.00 | 05-OCT-07:02 | 2707.23 | 3497.50 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.39 |
| November | 6375.17 | 21-NOV-09:02 | 1804.82 | 2331.66 | 2354.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92.73 |
| December | 6293.95 | 26-DEC-09:02 | 1804.82 | 2331.66 | 2354.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 106.93 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 2743.17 | 1353.62 | 1748.75 | 1765.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.60 | |
| Maximum of Months | 6835.00 | 2707.23 | 3497.50 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 196.84 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: G NE APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 474.95 | 31-JAN-17:02 | 617.50 | 434.00 | 2943.11 | 0.00 | 0.00 | 0.00 | 0.00 | 32.93 | 0.00 |
| February | 465.22 | 01-FEB-05:00 | 237.50 | 26.04 | 223.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 195.18 |
| March | 631.90 | 20-MAR-17:05 | 413.25 | 234.36 | 1177.25 | 0.00 | 0.00 | 0.00 | 0.00 | 40.51 | 0.00 |
| April | 1499.47 | 14-APR-18:00 | 206.62 | 117.18 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 210.08 | 0.00 |
| May | 1693.33 | 31-MAY-18:00 | 206.62 | 117.18 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 250.93 | 0.00 |
| June | 2389.67 | 30-JUN-17:03 | 1446.38 | 820.27 | 4120.36 | 0.00 | 0.00 | 0.00 | 0.00 | 486.73 | 0.00 |
| July | 2441.11 | 22-JUL-18:00 | 206.62 | 117.18 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 483.87 | 0.00 |
| August | 2297.11 | 13-AUG-16:02 | 988.00 | 694.39 | 4708.98 | 0.00 | 0.00 | 0.00 | 0.00 | 425.04 | 0.00 |
| September | 2171.12 | 08-SEP-16:40 | 123.50 | 86.80 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 263.85 | 0.00 |
| October | 1853.50 | 04-OCT-17:00 | 123.50 | 86.80 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 228.23 | 0.00 |
| November | 1107.30 | 01-NOV-16:05 | 741.00 | 520.80 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 68.29 | 0.00 |
| December | 594.18 | 05-DEC-03:20 | 237.50 | 8.68 | 223.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 139.72 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 465.22 | 123.50 | 8.68 | 223.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 2441.11 | 1446.38 | 820.27 | 4708.98 | 0.00 | 0.00 | 0.00 | 0.00 | 486.73 | 195.18 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: G N1 APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 464.39 | 12-JAN-07:00 | 237.50 | 60.76 | 317.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99.56 |
| February | 482.40 | 01-FEB-05:00 | 237.50 | 26.04 | 223.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 121.88 |
| March | 596.21 | 20-MAR-17:10 | 413.25 | 234.36 | 1177.25 | 0.00 | 0.00 | 0.00 | 0.00 | 24.44 | 0.00 |
| April | 1206.58 | 14-APR-18:00 | 206.62 | 117.18 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 126.71 | 0.00 |
| May | 1365.43 | 31-MAY-18:00 | 206.62 | 117.18 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 151.35 | 0.00 |
| June | 1831.45 | 30-JUN-17:30 | 413.25 | 234.36 | 1177.25 | 0.00 | 0.00 | 0.00 | 0.00 | 281.45 | 0.00 |
| July | 1871.18 | 22-JUL-18:00 | 206.62 | 117.18 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 291.86 | 0.00 |
| August | 1743.91 | 13-AUG-17:30 | 206.62 | 117.18 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 218.49 | 0.00 |
| September | 1651.68 | 08-SEP-17:04 | 1033.12 | 585.91 | 2943.11 | 0.00 | 0.00 | 0.00 | 0.00 | 147.35 | 0.00 |
| October | 1461.86 | 03-OCT-18:00 | 206.62 | 117.18 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 133.37 | 0.00 |
| November | 930.60 | 01-NOV-16:20 | 370.50 | 260.40 | 1765.87 | 0.00 | 0.00 | 0.00 | 0.00 | 39.35 | 0.00 |
| December | 629.54 | 05-DEC-07:00 | 237.50 | 60.76 | 317.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.57 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 464.39 | 206.62 | 26.04 | 223.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 1871.18 | 1033.12 | 585.91 | 2943.11 | 0.00 | 0.00 | 0.00 | 0.00 | 291.86 | 121.88 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: G N2 APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 464.06 | 12-JAN-07:00 | 237.50 | 60.76 | 317.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99.49 |
| February | 482.51 | 01-FEB-05:00 | 237.50 | 26.04 | 223.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 121.91 |
| March | 597.01 | 20-MAR-17:10 | 413.25 | 234.36 | 1177.25 | 0.00 | 0.00 | 0.00 | 0.00 | 24.44 | 0.00 |
| April | 1200.87 | 14-APR-18:00 | 206.62 | 117.18 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 126.71 | 0.00 |
| May | 1360.41 | 31-MAY-18:00 | 206.62 | 117.18 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 151.35 | 0.00 |
| June | 1826.93 | 30-JUN-17:30 | 413.25 | 234.36 | 1177.25 | 0.00 | 0.00 | 0.00 | 0.00 | 281.45 | 0.00 |
| July | 1866.45 | 22-JUL-18:00 | 206.62 | 117.18 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 291.86 | 0.00 |
| August | 1739.64 | 13-AUG-17:30 | 206.62 | 117.18 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 218.49 | 0.00 |
| September | 1647.70 | 08-SEP-17:04 | 1033.12 | 585.91 | 2943.11 | 0.00 | 0.00 | 0.00 | 0.00 | 147.35 | 0.00 |
| October | 1462.14 | 03-OCT-18:00 | 206.62 | 117.18 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 133.37 | 0.00 |
| November | 927.02 | 02-NOV-16:04 | 617.50 | 434.00 | 2943.11 | 0.00 | 0.00 | 0.00 | 0.00 | 25.23 | 0.00 |
| December | 629.85 | 05-DEC-07:00 | 237.50 | 60.76 | 317.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.60 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 464.06 | 206.62 | 26.04 | 223.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 1866.45 | 1033.12 | 585.91 | 2943.11 | 0.00 | 0.00 | 0.00 | 0.00 | 291.86 | 121.91 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: G S1 APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 1466.14 | 18-JAN-15:10 | 0.00 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 9.08 | 0.00 |
| February | 1152.21 | 01-FEB-15:30 | 0.00 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.35 |
| March | 1191.09 | 18-MAR-16:10 | 475.00 | 173.60 | 1177.25 | 0.00 | 0.00 | 0.00 | 0.00 | 13.04 | 0.00 |
| April | 1487.84 | 10-APR-16:02 | 0.00 | 520.80 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 136.05 | 0.00 |
| May | 1403.62 | 20-MAY-14:00 | 118.75 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 264.80 | 0.00 |
| June | 1791.67 | 30-JUN-17:04 | 1662.50 | 820.27 | 4120.36 | 0.00 | 0.00 | 0.00 | 0.00 | 293.58 | 0.00 |
| July | 1933.08 | 22-JUL-16:08 | 1900.00 | 694.39 | 4708.98 | 0.00 | 0.00 | 0.00 | 0.00 | 322.82 | 0.00 |
| August | 1983.69 | 13-AUG-16:02 | 1900.00 | 694.39 | 4708.98 | 0.00 | 0.00 | 0.00 | 0.00 | 256.38 | 0.00 |
| September | 1990.78 | 08-SEP-16:08 | 0.00 | 694.39 | 4708.98 | 0.00 | 0.00 | 0.00 | 0.00 | 161.78 | 0.00 |
| October | 1980.27 | 10-OCT-15:10 | 0.00 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 135.31 | 0.00 |
| November | 1830.02 | 01-NOV-16:03 | 0.00 | 520.80 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 41.19 | 0.00 |
| December | 1626.22 | 25-DEC-16:10 | 237.50 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 11.20 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 1152.21 | 0.00 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 1990.78 | 1900.00 | 820.27 | 4708.98 | 0.00 | 0.00 | 0.00 | 0.00 | 322.82 | 33.35 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: G S2 APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 1537.79 | 29-JAN-16:20 | 237.50 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 5.35 | 0.00 |
| February | 1204.75 | 01-FEB-15:30 | 0.00 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.35 |
| March | 1272.71 | 18-MAR-16:05 | 475.00 | 173.60 | 1177.25 | 0.00 | 0.00 | 0.00 | 0.00 | 13.04 | 0.00 |
| April | 1565.62 | 10-APR-16:02 | 0.00 | 520.80 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 136.05 | 0.00 |
| May | 1526.65 | 20-MAY-14:00 | 118.75 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 264.80 | 0.00 |
| June | 1879.89 | 30-JUN-17:15 | 950.00 | 468.73 | 2354.49 | 0.00 | 0.00 | 0.00 | 0.00 | 287.48 | 0.00 |
| July | 2080.54 | 22-JUL-16:08 | 1900.00 | 694.39 | 4708.98 | 0.00 | 0.00 | 0.00 | 0.00 | 322.82 | 0.00 |
| August | 2151.70 | 13-AUG-16:02 | 1900.00 | 694.39 | 4708.98 | 0.00 | 0.00 | 0.00 | 0.00 | 256.38 | 0.00 |
| September | 2092.36 | 10-SEP-16:30 | 237.50 | 86.80 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 152.67 | 0.00 |
| October | 2084.94 | 10-OCT-15:10 | 0.00 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 135.31 | 0.00 |
| November | 1883.37 | 01-NOV-16:05 | 0.00 | 520.80 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 41.19 | 0.00 |
| December | 1714.75 | 25-DEC-16:10 | 237.50 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 11.20 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 1204.75 | 0.00 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 2151.70 | 1900.00 | 694.39 | 4708.98 | 0.00 | 0.00 | 0.00 | 0.00 | 322.82 | 33.35 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: M SW APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 2203.03 | 31-JAN-16:30 | 0.00 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 52.20 | 0.00 |
| February | 1597.43 | 01-FEB-15:30 | 0.00 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.65 |
| March | 2255.04 | 18-MAR-16:30 | 237.50 | 86.80 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 44.73 | 0.00 |
| April | 2643.43 | 14-APR-17:30 | 475.00 | 234.36 | 1177.25 | 0.00 | 0.00 | 0.00 | 0.00 | 236.91 | 0.00 |
| May | 2629.93 | 19-MAY-17:30 | 475.00 | 234.36 | 1177.25 | 0.00 | 0.00 | 0.00 | 0.00 | 304.08 | 0.00 |
| June | 3209.14 | 30-JUN-17:17 | 950.00 | 468.73 | 2354.49 | 0.00 | 0.00 | 0.00 | 0.00 | 684.07 | 0.00 |
| July | 3236.65 | 22-JUL-17:40 | 237.50 | 117.18 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 671.90 | 0.00 |
| August | 3165.48 | 13-AUG-16:04 | 1900.00 | 694.39 | 4708.98 | 0.00 | 0.00 | 0.00 | 0.00 | 609.95 | 0.00 |
| September | 2949.17 | 08-SEP-16:10 | 0.00 | 694.39 | 4708.98 | 0.00 | 0.00 | 0.00 | 0.00 | 384.89 | 0.00 |
| October | 2871.41 | 10-OCT-15:30 | 0.00 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 303.68 | 0.00 |
| November | 2659.40 | 01-NOV-16:03 | 0.00 | 520.80 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 97.61 | 0.00 |
| December | 2249.93 | 25-DEC-16:20 | 237.50 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 21.60 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 1597.43 | 0.00 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 3236.65 | 1900.00 | 694.39 | 4708.98 | 0.00 | 0.00 | 0.00 | 0.00 | 684.07 | 79.65 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: M NW APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 965.53 | 31-JAN-17:04 | 617.50 | 434.00 | 2943.11 | 0.00 | 0.00 | 0.00 | 0.00 | 47.11 | 0.00 |
| February | 573.86 | 22-FEB-16:30 | 71.25 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91.59 |
| March | 1525.72 | 18-MAR-17:10 | 206.62 | 117.18 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 55.84 | 0.00 |
| April | 2410.25 | 14-APR-17:40 | 413.25 | 234.36 | 1177.25 | 0.00 | 0.00 | 0.00 | 0.00 | 259.19 | 0.00 |
| May | 2619.03 | 31-MAY-18:00 | 206.62 | 117.18 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 360.01 | 0.00 |
| June | 3263.80 | 29-JUN-18:00 | 206.62 | 117.18 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 551.59 | 0.00 |
| July | 3191.23 | 22-JUL-18:00 | 206.62 | 117.18 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 694.37 | 0.00 |
| August | 2865.96 | 13-AUG-17:30 | 206.62 | 117.18 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 519.83 | 0.00 |
| September | 2565.87 | 08-SEP-16:40 | 123.50 | 86.80 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 378.60 | 0.00 |
| October | 2117.18 | 05-OCT-16:50 | 123.50 | 86.80 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 195.46 | 0.00 |
| November | 1612.99 | 01-NOV-16:30 | 123.50 | 86.80 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 87.88 | 0.00 |
| December | 673.91 | 25-DEC-16:30 | 71.25 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 16.54 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 573.86 | 71.25 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 3263.80 | 617.50 | 434.00 | 2943.11 | 0.00 | 0.00 | 0.00 | 0.00 | 694.37 | 91.59 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: M SE APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 1867.45 | 17-JAN-14:30 | 0.00 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 7.53 | 0.00 |
| February | 1354.37 | 01-FEB-14:30 | 0.00 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.34 |
| March | 1878.57 | 18-MAR-15:10 | 237.50 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 30.65 | 0.00 |
| April | 2297.24 | 10-APR-16:02 | 0.00 | 520.80 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 323.42 | 0.00 |
| May | 2463.05 | 20-MAY-14:00 | 118.75 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 629.84 | 0.00 |
| June | 2848.84 | 30-JUN-16:03 | 0.00 | 781.19 | 5297.60 | 0.00 | 0.00 | 0.00 | 0.00 | 749.09 | 0.00 |
| July | 2871.64 | 22-JUL-16:08 | 1900.00 | 694.39 | 4708.98 | 0.00 | 0.00 | 0.00 | 0.00 | 768.03 | 0.00 |
| August | 2785.77 | 13-AUG-16:08 | 1900.00 | 694.39 | 4708.98 | 0.00 | 0.00 | 0.00 | 0.00 | 609.95 | 0.00 |
| September | 2607.42 | 18-SEP-12:00 | 0.00 | 17.36 | 406.15 | 0.00 | 0.00 | 0.00 | 0.00 | 443.55 | 0.00 |
| October | 2555.53 | 10-OCT-15:10 | 0.00 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 321.79 | 0.00 |
| November | 2154.78 | 01-NOV-15:20 | 0.00 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 79.37 | 0.00 |
| December | 1823.38 | 25-DEC-14:00 | 118.75 | 17.36 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 25.86 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 1354.37 | 0.00 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 2871.64 | 1900.00 | 781.19 | 5297.60 | 0.00 | 0.00 | 0.00 | 0.00 | 768.03 | 55.34 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: M NE APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 677.74 | 27-JAN-17:05 | 494.00 | 347.20 | 2354.49 | 0.00 | 0.00 | 0.00 | 0.00 | 21.25 | 0.00 |
| February | 472.52 | 01-FEB-05:00 | 237.50 | 26.04 | 223.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 285.05 |
| March | 1149.63 | 16-MAR-16:08 | 494.00 | 347.20 | 2354.49 | 0.00 | 0.00 | 0.00 | 0.00 | 87.49 | 0.00 |
| April | 1903.02 | 30-APR-16:08 | 617.50 | 434.00 | 2943.11 | 0.00 | 0.00 | 0.00 | 0.00 | 393.42 | 0.00 |
| May | 2198.57 | 20-MAY-14:00 | 59.38 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 629.84 | 0.00 |
| June | 2823.91 | 30-JUN-16:17 | 370.50 | 260.40 | 1765.87 | 0.00 | 0.00 | 0.00 | 0.00 | 741.93 | 0.00 |
| July | 2692.72 | 22-JUL-16:05 | 988.00 | 694.39 | 4708.98 | 0.00 | 0.00 | 0.00 | 0.00 | 768.03 | 0.00 |
| August | 2472.55 | 13-AUG-16:04 | 988.00 | 694.39 | 4708.98 | 0.00 | 0.00 | 0.00 | 0.00 | 609.95 | 0.00 |
| September | 2183.73 | 08-SEP-16:17 | 370.50 | 260.40 | 1765.87 | 0.00 | 0.00 | 0.00 | 0.00 | 383.03 | 0.00 |
| October | 1848.41 | 04-OCT-17:00 | 123.50 | 86.80 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 327.33 | 0.00 |
| November | 1126.30 | 01-NOV-16:07 | 741.00 | 520.80 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 97.61 | 0.00 |
| December | 513.93 | 04-DEC-07:20 | 1009.38 | 282.08 | 1913.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.74 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 472.52 | 59.38 | 17.36 | 223.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 2823.91 | 1009.38 | 694.39 | 4708.98 | 0.00 | 0.00 | 0.00 | 0.00 | 768.03 | 285.05 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: M N1 APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 652.90 | 27-JAN-17:03 | 494.00 | 347.20 | 2354.49 | 0.00 | 0.00 | 0.00 | 0.00 | 12.82 | 0.00 |
| February | 513.13 | 18-FEB-18:40 | 206.62 | 117.18 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 112.60 |
| March | 974.60 | 20-MAR-17:05 | 413.25 | 234.36 | 1177.25 | 0.00 | 0.00 | 0.00 | 0.00 | 34.96 | 0.00 |
| April | 1453.61 | 14-APR-18:00 | 206.62 | 117.18 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 181.73 | 0.00 |
| May | 1656.07 | 31-MAY-18:00 | 206.62 | 117.18 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 217.15 | 0.00 |
| June | 2053.84 | 30-JUN-18:00 | 206.62 | 117.18 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 378.46 | 0.00 |
| July | 1997.79 | 22-JUL-18:00 | 206.62 | 117.18 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 418.83 | 0.00 |
| August | 1777.92 | 13-AUG-16:08 | 988.00 | 694.39 | 4708.98 | 0.00 | 0.00 | 0.00 | 0.00 | 367.91 | 0.00 |
| September | 1608.41 | 08-SEP-16:30 | 123.50 | 86.80 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 229.77 | 0.00 |
| October | 1427.37 | 03-OCT-18:00 | 206.62 | 117.18 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 191.24 | 0.00 |
| November | 959.65 | 01-NOV-16:17 | 370.50 | 260.40 | 1765.87 | 0.00 | 0.00 | 0.00 | 0.00 | 56.21 | 0.00 |
| December | 619.39 | 05-DEC-04:00 | 237.50 | 8.68 | 223.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 156.26 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 513.13 | 123.50 | 8.68 | 223.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 2053.84 | 988.00 | 694.39 | 4708.98 | 0.00 | 0.00 | 0.00 | 0.00 | 418.83 | 156.26 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: M N2 APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 652.60 | 27-JAN-17:03 | 494.00 | 347.20 | 2354.49 | 0.00 | 0.00 | 0.00 | 0.00 | 12.82 | 0.00 |
| February | 535.79 | 18-FEB-18:40 | 206.62 | 117.18 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 112.61 |
| March | 974.53 | 20-MAR-17:05 | 413.25 | 234.36 | 1177.25 | 0.00 | 0.00 | 0.00 | 0.00 | 34.96 | 0.00 |
| April | 1445.88 | 14-APR-18:00 | 206.62 | 117.18 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 181.73 | 0.00 |
| May | 1649.55 | 31-MAY-18:00 | 206.62 | 117.18 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 217.15 | 0.00 |
| June | 2047.28 | 30-JUN-18:00 | 206.62 | 117.18 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 378.46 | 0.00 |
| July | 1990.90 | 22-JUL-18:00 | 206.62 | 117.18 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 418.83 | 0.00 |
| August | 1775.84 | 13-AUG-16:08 | 988.00 | 694.39 | 4708.98 | 0.00 | 0.00 | 0.00 | 0.00 | 367.91 | 0.00 |
| September | 1604.96 | 08-SEP-16:30 | 123.50 | 86.80 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 229.77 | 0.00 |
| October | 1427.11 | 03-OCT-18:00 | 206.62 | 117.18 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 191.24 | 0.00 |
| November | 954.11 | 01-NOV-16:17 | 370.50 | 260.40 | 1765.87 | 0.00 | 0.00 | 0.00 | 0.00 | 56.21 | 0.00 |
| December | 619.74 | 05-DEC-04:00 | 237.50 | 8.68 | 223.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 156.35 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 535.79 | 123.50 | 8.68 | 223.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 2047.28 | 988.00 | 694.39 | 4708.98 | 0.00 | 0.00 | 0.00 | 0.00 | 418.83 | 156.35 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: M S1 APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 1857.18 | 18-JAN-14:30 | 0.00 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 4.93 | 0.00 |
| February | 1483.22 | 01-FEB-15:30 | 0.00 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.04 |
| March | 1688.08 | 18-MAR-16:10 | 475.00 | 173.60 | 1177.25 | 0.00 | 0.00 | 0.00 | 0.00 | 18.63 | 0.00 |
| April | 1821.60 | 10-APR-16:03 | 0.00 | 520.80 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 195.08 | 0.00 |
| May | 1749.02 | 20-MAY-14:00 | 118.75 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 379.90 | 0.00 |
| June | 2032.32 | 30-JUN-16:01 | 0.00 | 781.19 | 5297.60 | 0.00 | 0.00 | 0.00 | 0.00 | 451.83 | 0.00 |
| July | 2100.95 | 22-JUL-16:05 | 1900.00 | 694.39 | 4708.98 | 0.00 | 0.00 | 0.00 | 0.00 | 463.26 | 0.00 |
| August | 2089.19 | 13-AUG-16:04 | 1900.00 | 694.39 | 4708.98 | 0.00 | 0.00 | 0.00 | 0.00 | 367.91 | 0.00 |
| September | 2000.62 | 08-SEP-16:10 | 0.00 | 694.39 | 4708.98 | 0.00 | 0.00 | 0.00 | 0.00 | 232.16 | 0.00 |
| October | 2115.58 | 10-OCT-15:10 | 0.00 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 194.09 | 0.00 |
| November | 1994.53 | 20-NOV-14:30 | 0.00 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 16.19 | 0.00 |
| December | 1851.89 | 25-DEC-16:10 | 237.50 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 15.90 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 1483.22 | 0.00 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 2115.58 | 1900.00 | 781.19 | 5297.60 | 0.00 | 0.00 | 0.00 | 0.00 | 463.26 | 48.04 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: M S2 APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 1858.96 | 18-JAN-14:30 | 0.00 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 4.93 | 0.00 |
| February | 1483.21 | 01-FEB-15:30 | 0.00 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.04 |
| March | 1685.39 | 18-MAR-16:10 | 475.00 | 173.60 | 1177.25 | 0.00 | 0.00 | 0.00 | 0.00 | 18.63 | 0.00 |
| April | 1821.48 | 10-APR-16:03 | 0.00 | 520.80 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 195.08 | 0.00 |
| May | 1754.34 | 20-MAY-14:00 | 118.75 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 379.90 | 0.00 |
| June | 2029.93 | 30-JUN-16:01 | 0.00 | 781.19 | 5297.60 | 0.00 | 0.00 | 0.00 | 0.00 | 451.83 | 0.00 |
| July | 2099.00 | 22-JUL-16:05 | 1900.00 | 694.39 | 4708.98 | 0.00 | 0.00 | 0.00 | 0.00 | 463.26 | 0.00 |
| August | 2086.90 | 13-AUG-16:04 | 1900.00 | 694.39 | 4708.98 | 0.00 | 0.00 | 0.00 | 0.00 | 367.91 | 0.00 |
| September | 2001.33 | 28-SEP-14:10 | 0.00 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 113.16 | 0.00 |
| October | 2115.10 | 10-OCT-15:10 | 0.00 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 194.09 | 0.00 |
| November | 1995.97 | 20-NOV-14:30 | 0.00 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 16.19 | 0.00 |
| December | 1850.81 | 25-DEC-14:00 | 118.75 | 17.36 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 15.60 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 1483.21 | 0.00 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 2115.10 | 1900.00 | 781.19 | 5297.60 | 0.00 | 0.00 | 0.00 | 0.00 | 463.26 | 48.04 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: T SW APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 2687.86 | 24-JAN-16:20 | 0.00 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 27.22 | 0.00 |
| February | 1824.24 | 28-FEB-16:30 | 0.00 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.04 |
| March | 2901.29 | 18-MAR-16:20 | 237.50 | 86.80 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 49.38 | 0.00 |
| April | 3621.56 | 14-APR-17:30 | 475.00 | 234.36 | 1177.25 | 0.00 | 0.00 | 0.00 | 0.00 | 312.20 | 0.00 |
| May | 3661.90 | 20-MAY-16:30 | 237.50 | 86.80 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 434.94 | 0.00 |
| June | 4484.68 | 30-JUN-16:03 | 0.00 | 781.19 | 5297.60 | 0.00 | 0.00 | 0.00 | 0.00 | 988.55 | 0.00 |
| July | 4483.60 | 22-JUL-16:04 | 1900.00 | 694.39 | 4708.98 | 0.00 | 0.00 | 0.00 | 0.00 | 1013.06 | 0.00 |
| August | 4417.60 | 13-AUG-16:02 | 1900.00 | 694.39 | 4708.98 | 0.00 | 0.00 | 0.00 | 0.00 | 804.55 | 0.00 |
| September | 4102.65 | 08-SEP-16:01 | 0.00 | 694.39 | 4708.98 | 0.00 | 0.00 | 0.00 | 0.00 | 507.69 | 0.00 |
| October | 3863.87 | 10-OCT-15:30 | 0.00 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 400.18 | 0.00 |
| November | 3457.96 | 01-NOV-16:02 | 0.00 | 520.80 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 127.72 | 0.00 |
| December | 2686.65 | 25-DEC-16:20 | 237.50 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 27.70 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 1824.24 | 0.00 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 4484.68 | 1900.00 | 781.19 | 5297.60 | 0.00 | 0.00 | 0.00 | 0.00 | 1013.06 | 98.04 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: T NW APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 1210.38 | 31-JAN-17:02 | 617.50 | 434.00 | 2943.11 | 0.00 | 0.00 | 0.00 | 0.00 | 61.74 | 0.00 |
| February | 611.72 | 22-FEB-16:30 | 71.25 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 122.52 |
| March | 1922.26 | 18-MAR-17:00 | 123.50 | 86.80 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 85.58 | 0.00 |
| April | 3320.71 | 14-APR-17:30 | 413.25 | 234.36 | 1177.25 | 0.00 | 0.00 | 0.00 | 0.00 | 312.20 | 0.00 |
| May | 3579.19 | 15-MAY-17:30 | 413.25 | 234.36 | 1177.25 | 0.00 | 0.00 | 0.00 | 0.00 | 413.11 | 0.00 |
| June | 4485.20 | 29-JUN-17:30 | 413.25 | 234.36 | 1177.25 | 0.00 | 0.00 | 0.00 | 0.00 | 753.55 | 0.00 |
| July | 4326.92 | 22-JUL-18:00 | 206.62 | 117.18 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 915.90 | 0.00 |
| August | 4003.56 | 13-AUG-16:30 | 123.50 | 86.80 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 756.99 | 0.00 |
| September | 3591.40 | 08-SEP-16:30 | 123.50 | 86.80 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 502.40 | 0.00 |
| October | 2912.98 | 05-OCT-16:30 | 123.50 | 86.80 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 246.83 | 0.00 |
| November | 2133.58 | 01-NOV-16:20 | 370.50 | 260.40 | 1765.87 | 0.00 | 0.00 | 0.00 | 0.00 | 121.81 | 0.00 |
| December | 925.61 | 22-DEC-16:30 | 71.25 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 611.72 | 71.25 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 4485.20 | 617.50 | 434.00 | 2943.11 | 0.00 | 0.00 | 0.00 | 0.00 | 915.90 | 122.52 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: T SE APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 2220.99 | 24-JAN-15:10 | 0.00 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 49.67 | 0.00 |
| February | 1501.02 | 23-FEB-14:00 | 0.00 | 17.36 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.60 |
| March | 2416.60 | 18-MAR-15:20 | 237.50 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 38.29 | 0.00 |
| April | 3121.46 | 30-APR-15:10 | 237.50 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 538.22 | 0.00 |
| May | 3450.99 | 20-MAY-14:00 | 118.75 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 830.39 | 0.00 |
| June | 3991.25 | 30-JUN-16:03 | 0.00 | 781.19 | 5297.60 | 0.00 | 0.00 | 0.00 | 0.00 | 988.55 | 0.00 |
| July | 3949.61 | 22-JUL-16:04 | 1900.00 | 694.39 | 4708.98 | 0.00 | 0.00 | 0.00 | 0.00 | 1013.06 | 0.00 |
| August | 3846.24 | 13-AUG-16:08 | 1900.00 | 694.39 | 4708.98 | 0.00 | 0.00 | 0.00 | 0.00 | 804.55 | 0.00 |
| September | 3566.26 | 09-SEP-13:00 | 118.75 | 17.36 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 357.61 | 0.00 |
| October | 3483.91 | 02-OCT-13:50 | 0.00 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 312.67 | 0.00 |
| November | 2816.29 | 01-NOV-15:20 | 0.00 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 104.10 | 0.00 |
| December | 2106.94 | 25-DEC-14:20 | 118.75 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 26.64 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 1501.02 | 0.00 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 3991.25 | 1900.00 | 781.19 | 5297.60 | 0.00 | 0.00 | 0.00 | 0.00 | 1013.06 | 20.60 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: T NE APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 747.60 | 31-JAN-17:02 | 617.50 | 434.00 | 2943.11 | 0.00 | 0.00 | 0.00 | 0.00 | 61.74 | 0.00 |
| February | 317.23 | 13-FEB-22:25 | 475.00 | 104.17 | 835.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 123.79 |
| March | 1470.45 | 16-MAR-16:10 | 494.00 | 347.20 | 2354.49 | 0.00 | 0.00 | 0.00 | 0.00 | 114.76 | 0.00 |
| April | 2576.46 | 30-APR-15:10 | 71.25 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 538.22 | 0.00 |
| May | 3078.00 | 20-MAY-14:00 | 59.38 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 830.39 | 0.00 |
| June | 3921.53 | 30-JUN-16:10 | 1111.50 | 781.19 | 5297.60 | 0.00 | 0.00 | 0.00 | 0.00 | 988.55 | 0.00 |
| July | 3695.84 | 22-JUL-16:10 | 988.00 | 694.39 | 4708.98 | 0.00 | 0.00 | 0.00 | 0.00 | 1013.06 | 0.00 |
| August | 3430.67 | 13-AUG-16:02 | 988.00 | 694.39 | 4708.98 | 0.00 | 0.00 | 0.00 | 0.00 | 804.55 | 0.00 |
| September | 3024.91 | 08-SEP-16:01 | 988.00 | 694.39 | 4708.98 | 0.00 | 0.00 | 0.00 | 0.00 | 507.69 | 0.00 |
| October | 2585.87 | 02-OCT-14:00 | 59.38 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 359.58 | 0.00 |
| November | 1450.45 | 01-NOV-16:03 | 741.00 | 520.80 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 127.72 | 0.00 |
| December | 427.97 | 25-DEC-16:10 | 71.25 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 34.03 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 317.23 | 59.38 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 3921.53 | 1111.50 | 781.19 | 5297.60 | 0.00 | 0.00 | 0.00 | 0.00 | 1013.06 | 123.79 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: T N1 APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 570.42 | 31-JAN-17:08 | 617.50 | 434.00 | 2943.11 | 0.00 | 0.00 | 0.00 | 0.00 | 37.24 | 0.00 |
| February | 342.85 | 01-FEB-02:50 | 237.50 | 8.68 | 229.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 180.19 |
| March | 1204.29 | 16-MAR-16:12 | 617.50 | 434.00 | 2943.11 | 0.00 | 0.00 | 0.00 | 0.00 | 61.65 | 0.00 |
| April | 2041.64 | 25-APR-16:17 | 370.50 | 260.40 | 1765.87 | 0.00 | 0.00 | 0.00 | 0.00 | 215.67 | 0.00 |
| May | 2303.80 | 31-MAY-18:00 | 206.62 | 117.18 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 286.29 | 0.00 |
| June | 2964.99 | 30-JUN-16:20 | 370.50 | 260.40 | 1765.87 | 0.00 | 0.00 | 0.00 | 0.00 | 590.55 | 0.00 |
| July | 2802.38 | 22-JUL-18:00 | 206.62 | 117.18 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 552.45 | 0.00 |
| August | 2619.54 | 13-AUG-16:02 | 988.00 | 694.39 | 4708.98 | 0.00 | 0.00 | 0.00 | 0.00 | 485.28 | 0.00 |
| September | 2352.74 | 08-SEP-16:17 | 370.50 | 260.40 | 1765.87 | 0.00 | 0.00 | 0.00 | 0.00 | 304.72 | 0.00 |
| October | 1941.65 | 02-OCT-14:00 | 59.38 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 216.89 | 0.00 |
| November | 1236.81 | 01-NOV-16:07 | 741.00 | 520.80 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 77.04 | 0.00 |
| December | 363.29 | 13-DEC-21:00 | 206.62 | 138.88 | 523.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85.53 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 342.85 | 59.38 | 8.68 | 229.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 2964.99 | 988.00 | 694.39 | 4708.98 | 0.00 | 0.00 | 0.00 | 0.00 | 590.55 | 180.19 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: T N2 APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 564.70 | 31-JAN-17:08 | 617.50 | 434.00 | 2943.11 | 0.00 | 0.00 | 0.00 | 0.00 | 37.24 | 0.00 |
| February | 342.67 | 01-FEB-02:50 | 237.50 | 8.68 | 229.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 180.10 |
| March | 1200.08 | 16-MAR-16:14 | 617.50 | 434.00 | 2943.11 | 0.00 | 0.00 | 0.00 | 0.00 | 61.65 | 0.00 |
| April | 2030.59 | 25-APR-16:02 | 741.00 | 520.80 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 224.99 | 0.00 |
| May | 2285.97 | 31-MAY-18:00 | 206.62 | 117.18 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 286.29 | 0.00 |
| June | 2955.65 | 30-JUN-16:20 | 370.50 | 260.40 | 1765.87 | 0.00 | 0.00 | 0.00 | 0.00 | 590.55 | 0.00 |
| July | 2789.46 | 22-JUL-16:01 | 988.00 | 694.39 | 4708.98 | 0.00 | 0.00 | 0.00 | 0.00 | 611.05 | 0.00 |
| August | 2611.58 | 13-AUG-16:02 | 988.00 | 694.39 | 4708.98 | 0.00 | 0.00 | 0.00 | 0.00 | 485.28 | 0.00 |
| September | 2343.13 | 08-SEP-16:20 | 370.50 | 260.40 | 1765.87 | 0.00 | 0.00 | 0.00 | 0.00 | 304.72 | 0.00 |
| October | 1947.64 | 02-OCT-14:00 | 59.38 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 216.89 | 0.00 |
| November | 1223.68 | 01-NOV-16:10 | 741.00 | 520.80 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 77.04 | 0.00 |
| December | 362.40 | 13-DEC-21:00 | 206.62 | 138.88 | 523.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85.33 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 342.67 | 59.38 | 8.68 | 229.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 2955.65 | 988.00 | 694.39 | 4708.98 | 0.00 | 0.00 | 0.00 | 0.00 | 611.05 | 180.10 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: T S1 APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 2076.99 | 24-JAN-15:20 | 0.00 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 31.04 | 0.00 |
| February | 1428.19 | 01-FEB-15:30 | 0.00 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.84 |
| March | 2173.32 | 18-MAR-15:20 | 237.50 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 23.09 | 0.00 |
| April | 2511.01 | 10-APR-15:20 | 0.00 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 174.55 | 0.00 |
| May | 2571.88 | 20-MAY-14:00 | 118.75 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 500.87 | 0.00 |
| June | 3030.84 | 30-JUN-16:01 | 0.00 | 781.19 | 5297.60 | 0.00 | 0.00 | 0.00 | 0.00 | 596.27 | 0.00 |
| July | 3054.03 | 22-JUL-16:01 | 1900.00 | 694.39 | 4708.98 | 0.00 | 0.00 | 0.00 | 0.00 | 611.05 | 0.00 |
| August | 3039.41 | 13-AUG-16:02 | 1900.00 | 694.39 | 4708.98 | 0.00 | 0.00 | 0.00 | 0.00 | 485.28 | 0.00 |
| September | 2920.88 | 28-SEP-14:10 | 0.00 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 149.23 | 0.00 |
| October | 2887.21 | 10-OCT-15:10 | 0.00 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 255.80 | 0.00 |
| November | 2604.27 | 01-NOV-15:20 | 0.00 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 62.79 | 0.00 |
| December | 2016.38 | 25-DEC-15:10 | 0.00 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 10.50 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 1428.19 | 0.00 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 3054.03 | 1900.00 | 781.19 | 5297.60 | 0.00 | 0.00 | 0.00 | 0.00 | 611.05 | 63.84 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: T S2 APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 2080.21 | 24-JAN-15:20 | 0.00 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 31.04 | 0.00 |
| February | 1430.69 | 01-FEB-15:30 | 0.00 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.84 |
| March | 2174.25 | 18-MAR-15:20 | 237.50 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 23.09 | 0.00 |
| April | 2511.59 | 10-APR-15:20 | 0.00 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 174.55 | 0.00 |
| May | 2580.95 | 20-MAY-14:00 | 118.75 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 500.87 | 0.00 |
| June | 3023.21 | 30-JUN-16:01 | 0.00 | 781.19 | 5297.60 | 0.00 | 0.00 | 0.00 | 0.00 | 596.27 | 0.00 |
| July | 3046.10 | 22-JUL-16:01 | 1900.00 | 694.39 | 4708.98 | 0.00 | 0.00 | 0.00 | 0.00 | 611.05 | 0.00 |
| August | 3031.00 | 13-AUG-16:05 | 1900.00 | 694.39 | 4708.98 | 0.00 | 0.00 | 0.00 | 0.00 | 485.28 | 0.00 |
| September | 2925.81 | 28-SEP-14:10 | 0.00 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 149.23 | 0.00 |
| October | 2884.63 | 10-OCT-15:10 | 0.00 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 255.80 | 0.00 |
| November | 2594.11 | 01-NOV-15:20 | 0.00 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 62.79 | 0.00 |
| December | 2014.31 | 25-DEC-15:10 | 0.00 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 10.50 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 1430.69 | 0.00 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 3046.10 | 1900.00 | 781.19 | 5297.60 | 0.00 | 0.00 | 0.00 | 0.00 | 611.05 | 63.84 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: T CORRIDOR
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 0.00 | 01-JAN-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77.90 |
| February | 0.00 | 01-FEB-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.35 |
| March | 0.00 | 01-MAR-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.50 |
| April | 0.00 | 01-APR-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.93 |
| May | 0.00 | 01-MAY-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.65 |
| June | 0.00 | 01-JUN-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.81 |
| July | 0.00 | 01-JUL-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.28 | 0.00 |
| August | 0.00 | 01-AUG-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.79 | 0.00 |
| September | 0.00 | 01-SEP-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.02 | 0.00 |
| October | 0.00 | 01-OCT-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.46 |
| November | 0.00 | 01-NOV-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.86 |
| December | 0.00 | 01-DEC-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.62 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
| Minimum of Months | 0.00 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.79 | 77.90 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: G CORRIDOR
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 0.00 | 01-JAN-00:10 | 397.10 | 370.63 | 56.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.71 |
| February | 0.00 | 01-FEB-00:10 | 397.10 | 370.63 | 56.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.21 |
| March | 0.00 | 01-MAR-00:10 | 397.10 | 370.63 | 56.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.61 |
| April | 0.00 | 01-APR-00:10 | 397.10 | 370.63 | 56.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.23 |
| May | 0.00 | 01-MAY-00:10 | 397.10 | 370.63 | 56.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.56 |
| June | 0.00 | 01-JUN-00:10 | 397.10 | 370.63 | 56.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.25 |
| July | 0.00 | 01-JUL-00:10 | 397.10 | 370.63 | 56.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.46 | 0.00 |
| August | 0.00 | 01-AUG-00:10 | 397.10 | 370.63 | 56.17 | 0.00 | 0.00 | 0.00 | 0.00 | 3.19 | 0.00 |
| September | 0.00 | 01-SEP-00:10 | 397.10 | 370.63 | 56.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.25 |
| October | 0.00 | 01-OCT-00:10 | 397.10 | 370.63 | 56.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.64 |
| November | 0.00 | 01-NOV-00:10 | 397.10 | 370.63 | 56.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.29 |
| December | 0.00 | 01-DEC-00:10 | 397.10 | 370.63 | 56.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.02 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 0.00 | 397.10 | 370.63 | 56.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 397.10 | 370.63 | 56.17 | 0.00 | 0.00 | 0.00 | 0.00 | 3.19 | 42.71 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: M CORRIDOR
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 0.00 | 01-JAN-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.19 |
| February | 0.00 | 01-FEB-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.95 |
| March | 0.00 | 01-MAR-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.62 |
| April | 0.00 | 01-APR-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.19 |
| May | 0.00 | 01-MAY-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.26 |
| June | 0.00 | 01-JUN-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.70 |
| July | 0.00 | 01-JUL-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.42 | 0.00 |
| August | 0.00 | 01-AUG-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.81 | 0.00 |
| September | 0.00 | 01-SEP-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.13 | 0.00 |
| October | 0.00 | 01-OCT-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.51 |
| November | 0.00 | 01-NOV-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.72 |
| December | 0.00 | 01-DEC-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.09 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
| Minimum of Months | 0.00 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.81 | 65.19 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
| January | 0.101530E+12 | 68493.56 | 01-JAN-19:30 | 0.447082E+10 | 26687.08 | 01-JAN-07:00 |
| February | 0.860966E+11 | 67236.75 | 01-FEB-18:40 | 0.439472E+10 | 14931.26 | 05-FEB-03:00 |
| March | 0.976095E+11 | 71506.02 | 20-MAR-17:49 | 0.377838E+10 | 21064.10 | 27-MAR-05:00 |
| April | 0.114735E+12 | 87357.51 | 14-APR-17:30 | 25269996.40 | 3140.31 | 21-APR-05:49 |
| May | 0.125451E+12 | 88007.34 | 15-MAY-17:10 | 0.00 | 0.00 | 01-MAY-00:10 |
| June | 0.138640E+12 | 95414.67 | 03-JUN-17:10 | 0.00 | 0.00 | 01-JUN-00:10 |
| July | 0.142741E+12 | 96571.87 | 22-JUL-16:10 | 0.00 | 0.00 | 01-JUL-00:10 |
| August | 0.140153E+12 | 94704.33 | 10-AUG-17:19 | 0.00 | 0.00 | 01-AUG-00:10 |
| September | 0.131162E+12 | 97169.37 | 07-SEP-17:10 | 0.00 | 0.00 | 01-SEP-00:10 |
| October | 0.113344E+12 | 89938.50 | 04-OCT-17:10 | 0.678976E+09 | 7798.53 | 26-OCT-03:00 |
| November | 0.972689E+11 | 72822.43 | 01-NOV-17:49 | 0.288440E+10 | 15638.76 | 24-NOV-02:00 |
| December | 0.974621E+11 | 66392.62 | 25-DEC-18:10 | 0.105638E+11 | 34097.62 | 07-DEC-05:00 |
| Annual Sum or Average | 0.138619E+13 | 0.267963E+11 | ||||
| Minimum of Months | 0.860966E+11 | 66392.62 | 0.00 | 0.00 | ||
| Maximum of Months | 0.142741E+12 | 97169.37 | 0.105638E+11 | 34097.62 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| INTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [J] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
| January | 0.840929E+10 | 0.490296E+10 | 0.389380E+11 | 0.00 | 0.668898E+10 | 0.00 | 0.00 | 0.611154E+10 | 0.00 | 0.00 | 0.00 | 0.364788E+11 | 0.00 |
| February | 0.760941E+10 | 0.420582E+10 | 0.351823E+11 | 0.00 | 0.483518E+10 | 0.00 | 0.00 | 0.149953E+10 | 0.00 | 0.00 | 0.00 | 0.327644E+11 | 0.00 |
| March | 0.845392E+10 | 0.432424E+10 | 0.389781E+11 | 0.00 | 0.622538E+10 | 0.00 | 0.00 | 0.469017E+10 | 0.00 | 0.00 | 0.00 | 0.349377E+11 | 0.00 |
| April | 0.814762E+10 | 0.384483E+10 | 0.376905E+11 | 0.00 | 0.111444E+11 | 0.00 | 0.00 | 0.221603E+11 | 0.00 | 0.00 | 0.00 | 0.317476E+11 | 0.00 |
| May | 0.843904E+10 | 0.368057E+10 | 0.389647E+11 | 0.00 | 0.136221E+11 | 0.00 | 0.00 | 0.301390E+11 | 0.00 | 0.00 | 0.00 | 0.306055E+11 | 0.00 |
| June | 0.817737E+10 | 0.343991E+10 | 0.377173E+11 | 0.00 | 0.172145E+11 | 0.00 | 0.00 | 0.441992E+11 | 0.00 | 0.00 | 0.00 | 0.278915E+11 | 0.00 |
| July | 0.840929E+10 | 0.360035E+10 | 0.389380E+11 | 0.00 | 0.176131E+11 | 0.00 | 0.00 | 0.462405E+11 | 0.00 | 0.00 | 0.00 | 0.279402E+11 | 0.00 |
| August | 0.845392E+10 | 0.384101E+10 | 0.389781E+11 | 0.00 | 0.168783E+11 | 0.00 | 0.00 | 0.437856E+11 | 0.00 | 0.00 | 0.00 | 0.282156E+11 | 0.00 |
| September | 0.814762E+10 | 0.403392E+10 | 0.376905E+11 | 0.00 | 0.151344E+11 | 0.00 | 0.00 | 0.375636E+11 | 0.00 | 0.00 | 0.00 | 0.285922E+11 | 0.00 |
| October | 0.842417E+10 | 0.452288E+10 | 0.389514E+11 | 0.00 | 0.103642E+11 | 0.00 | 0.00 | 0.194717E+11 | 0.00 | 0.00 | 0.00 | 0.316096E+11 | 0.00 |
| November | 0.814762E+10 | 0.467377E+10 | 0.376905E+11 | 0.00 | 0.676818E+10 | 0.00 | 0.00 | 0.723193E+10 | 0.00 | 0.00 | 0.00 | 0.327569E+11 | 0.00 |
| December | 0.840929E+10 | 0.499655E+10 | 0.389380E+11 | 0.00 | 0.609384E+10 | 0.00 | 0.00 | 0.334037E+10 | 0.00 | 0.00 | 0.00 | 0.356841E+11 | 0.00 |
| Annual Sum or Average | 0.992286E+11 | 0.500668E+11 | 0.458657E+12 | 0.00 | 0.132583E+12 | 0.00 | 0.00 | 0.266433E+12 | 0.00 | 0.00 | 0.00 | 0.379224E+12 | 0.00 |
| Minimum of Months | 0.760941E+10 | 0.343991E+10 | 0.351823E+11 | 0.00 | 0.483518E+10 | 0.00 | 0.00 | 0.149953E+10 | 0.00 | 0.00 | 0.00 | 0.278915E+11 | 0.00 |
| Maximum of Months | 0.845392E+10 | 0.499655E+10 | 0.389781E+11 | 0.00 | 0.176131E+11 | 0.00 | 0.00 | 0.462405E+11 | 0.00 | 0.00 | 0.00 | 0.364788E+11 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| INTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
| January | 0.00 | 0.00 | 0.447082E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.439472E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.377838E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 25269996.40 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.678976E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.288440E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.105638E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.267963E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.105638E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| INTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
| January | 5904.43 | 01-JAN-19:10 | 3183.33 | 01-JAN-00:10 | 22709.69 | 03-JAN-17:10 | 0.00 | 5766.67 | 31-JAN-16:30 | 0.00 | 0.00 | 01-JAN-00:10 |
| February | 5904.43 | 01-FEB-19:10 | 3183.33 | 01-FEB-00:10 | 22709.69 | 01-FEB-17:10 | 0.00 | 3404.64 | 22-FEB-16:10 | 0.00 | 0.00 | 01-FEB-00:10 |
| March | 5904.43 | 01-MAR-19:10 | 3183.33 | 01-MAR-00:10 | 22709.69 | 01-MAR-17:10 | 0.00 | 6058.85 | 18-MAR-16:30 | 0.00 | 0.00 | 01-MAR-00:10 |
| April | 5904.43 | 01-APR-18:10 | 3183.33 | 01-APR-00:10 | 22709.69 | 03-APR-16:10 | 0.00 | 8527.85 | 14-APR-17:30 | 0.00 | 0.00 | 01-APR-00:10 |
| May | 5904.43 | 01-MAY-18:10 | 3183.33 | 01-MAY-00:10 | 22709.69 | 01-MAY-16:10 | 0.00 | 9163.70 | 31-MAY-17:30 | 0.00 | 0.00 | 01-MAY-00:10 |
| June | 5904.43 | 01-JUN-18:10 | 3183.33 | 01-JUN-00:10 | 22709.69 | 01-JUN-16:10 | 0.00 | 11397.17 | 16-JUN-16:00 | 0.00 | 0.00 | 01-JUN-00:10 |
| July | 5904.43 | 01-JUL-18:10 | 3183.33 | 01-JUL-00:10 | 22709.69 | 03-JUL-16:10 | 0.00 | 10532.45 | 22-JUL-16:10 | 0.00 | 0.00 | 01-JUL-00:10 |
| August | 5904.43 | 01-AUG-18:10 | 3183.33 | 01-AUG-00:10 | 22709.69 | 01-AUG-16:10 | 0.00 | 10933.48 | 25-AUG-16:00 | 0.00 | 0.00 | 01-AUG-00:10 |
| September | 5904.43 | 01-SEP-18:10 | 3183.33 | 01-SEP-00:10 | 22709.69 | 01-SEP-16:10 | 0.00 | 9708.97 | 08-SEP-16:10 | 0.00 | 0.00 | 01-SEP-00:10 |
| October | 5904.43 | 01-OCT-18:10 | 3183.33 | 01-OCT-00:10 | 22709.69 | 02-OCT-16:10 | 0.00 | 8822.71 | 06-OCT-15:09 | 0.00 | 0.00 | 01-OCT-00:10 |
| November | 5904.43 | 01-NOV-18:10 | 3183.33 | 01-NOV-00:10 | 22709.69 | 01-NOV-16:10 | 0.00 | 6747.49 | 01-NOV-16:10 | 0.00 | 0.00 | 01-NOV-00:10 |
| December | 5904.43 | 01-DEC-19:10 | 3183.33 | 01-DEC-00:10 | 22709.69 | 01-DEC-17:10 | 0.00 | 5174.75 | 25-DEC-16:10 | 0.00 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 5904.43 | 3183.33 | 22709.69 | 0.00 | 3404.64 | 0.00 | 0.00 | |||||
| Maximum of Months | 5904.43 | 3183.33 | 22709.69 | 0.00 | 11397.17 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| COOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY {Maximum} [W] | HEATRECOVERY:ELECTRICITY {TIMESTAMP} | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
| January | 13938.30 | 31-JAN-16:30 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 37336.19 | 02-JAN-07:19 | 0.00 |
| February | 5694.44 | 22-FEB-16:10 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 31781.30 | 01-FEB-18:40 | 0.00 |
| March | 14314.45 | 16-MAR-15:50 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 30437.92 | 20-MAR-07:10 | 0.00 |
| April | 23224.84 | 14-APR-15:00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 33604.08 | 19-APR-06:10 | 0.00 |
| May | 25484.35 | 18-MAY-15:00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 30346.33 | 15-MAY-06:49 | 0.00 |
| June | 34911.37 | 30-JUN-15:00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 31512.41 | 24-JUN-06:00 | 0.00 |
| July | 32019.69 | 22-JUL-16:10 | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 30518.25 | 06-JUL-05:49 | 0.00 |
| August | 32745.20 | 13-AUG-16:10 | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 32240.51 | 30-AUG-06:30 | 0.00 |
| September | 29890.47 | 08-SEP-15:00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 34869.18 | 16-SEP-06:49 | 0.00 |
| October | 25861.12 | 02-OCT-13:00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 35413.79 | 09-OCT-06:49 | 0.00 |
| November | 17844.41 | 01-NOV-15:20 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 31148.44 | 24-NOV-09:50 | 0.00 |
| December | 11054.80 | 25-DEC-16:10 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 32055.15 | 16-DEC-08:30 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
| Minimum of Months | 5694.44 | 0.00 | 0.00 | 0.00 | 30346.33 | 0.00 | |||
| Maximum of Months | 34911.37 | 0.00 | 0.00 | 0.00 | 37336.19 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
| January | 68493.56 | 01-JAN-19:30 | 5904.43 | 20531.10 | 3183.33 | 0.00 | 1821.49 | 0.00 | 0.00 | 114.93 | 0.00 |
| February | 67236.75 | 01-FEB-18:40 | 5231.74 | 22609.62 | 3183.33 | 0.00 | 2390.94 | 0.00 | 0.00 | 2039.83 | 0.00 |
| March | 71506.02 | 20-MAR-17:49 | 5231.74 | 22609.62 | 0.00 | 0.00 | 5379.38 | 0.00 | 0.00 | 12034.40 | 0.00 |
| April | 87357.51 | 14-APR-17:30 | 5231.74 | 22609.62 | 0.00 | 0.00 | 8527.85 | 0.00 | 0.00 | 22946.03 | 0.00 |
| May | 88007.34 | 15-MAY-17:10 | 5231.74 | 22609.62 | 0.00 | 0.00 | 9031.32 | 0.00 | 0.00 | 24751.75 | 0.00 |
| June | 95414.67 | 03-JUN-17:10 | 5231.74 | 22609.62 | 0.00 | 0.00 | 10129.74 | 0.00 | 0.00 | 29075.67 | 0.00 |
| July | 96571.87 | 22-JUL-16:10 | 4289.87 | 22609.62 | 0.00 | 0.00 | 10532.45 | 0.00 | 0.00 | 32019.69 | 0.00 |
| August | 94704.33 | 10-AUG-17:19 | 5231.74 | 22609.62 | 0.00 | 0.00 | 9524.46 | 0.00 | 0.00 | 28301.04 | 0.00 |
| September | 97169.37 | 07-SEP-17:10 | 5231.74 | 22609.62 | 0.00 | 0.00 | 9418.28 | 0.00 | 0.00 | 27836.58 | 0.00 |
| October | 89938.50 | 04-OCT-17:10 | 5231.74 | 22609.62 | 0.00 | 0.00 | 8207.49 | 0.00 | 0.00 | 22786.90 | 0.00 |
| November | 72822.43 | 01-NOV-17:49 | 5231.74 | 22609.62 | 3183.33 | 0.00 | 5453.32 | 0.00 | 0.00 | 12045.17 | 0.00 |
| December | 66392.62 | 25-DEC-18:10 | 5231.74 | 22609.62 | 3183.33 | 0.00 | 3324.00 | 0.00 | 0.00 | 5010.15 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
| Minimum of Months | 66392.62 | 4289.87 | 20531.10 | 0.00 | 0.00 | 1821.49 | 0.00 | 0.00 | 114.93 | 0.00 | |
| Maximum of Months | 97169.37 | 5904.43 | 22609.62 | 3183.33 | 0.00 | 10532.45 | 0.00 | 0.00 | 32019.69 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| INTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | |
| January | 0.00 | 0.00 | 26687.08 | 01-JAN-07:00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 14931.26 | 05-FEB-03:00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 21064.10 | 27-MAR-05:00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 3140.31 | 21-APR-05:49 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 7798.53 | 26-OCT-03:00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 15638.76 | 24-NOV-02:00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 34097.62 | 07-DEC-05:00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 34097.62 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: G SW APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: G NW APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: OFFICE
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: G NE APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: G N1 APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: G N2 APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: G S1 APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: G S2 APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: M SW APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: M NW APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: M SE APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: M NE APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: M N1 APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: M N2 APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: M S1 APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: M S2 APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: T SW APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: T NW APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: T SE APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: T NE APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: T N1 APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: T N2 APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: T S1 APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: T S2 APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: T CORRIDOR
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: G CORRIDOR
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: M CORRIDOR
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: G SW APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 452.33 | 23.35 | 7.33 | 23.36 | 0.00 | 23.36 |
| February | 473.00 | 22.44 | 0.00 | 22.44 | 0.00 | 22.44 |
| March | 486.83 | 22.72 | 0.00 | 22.72 | 0.00 | 22.72 |
| April | 330.17 | 23.90 | 0.00 | 23.90 | 0.00 | 23.90 |
| May | 345.67 | 23.99 | 0.00 | 23.99 | 0.00 | 23.99 |
| June | 32.67 | 24.00 | 42.67 | 24.00 | 0.00 | 24.00 |
| July | 42.00 | 24.00 | 399.17 | 24.00 | 15.67 | 24.00 |
| August | 0.83 | 24.00 | 429.83 | 24.00 | 0.83 | 24.00 |
| September | 24.33 | 24.00 | 420.33 | 24.00 | 24.33 | 24.00 |
| October | 149.17 | 23.88 | 138.50 | 23.94 | 0.00 | 23.94 |
| November | 296.17 | 23.72 | 101.83 | 23.79 | 40.83 | 23.81 |
| December | 497.67 | 23.15 | 0.00 | 23.15 | 0.00 | 23.15 |
| Annual Sum or Average | 3130.83 | 23.29 | 1539.67 | 23.53 | 81.67 | 23.53 |
| Minimum of Months | 0.83 | 22.44 | 0.00 | 22.44 | 0.00 | 22.44 |
| Maximum of Months | 497.67 | 24.00 | 429.83 | 24.00 | 40.83 | 24.00 |
Report: ComfortReportSimple55Monthly
For: G NW APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 744.00 | 22.64 | 34.67 | 22.58 | 34.67 | 22.53 |
| February | 672.00 | 21.57 | 0.00 | 21.57 | 0.00 | 21.57 |
| March | 744.00 | 22.33 | 30.67 | 22.28 | 30.67 | 22.24 |
| April | 559.67 | 23.88 | 0.00 | 23.88 | 0.00 | 23.88 |
| May | 515.83 | 24.00 | 0.00 | 24.00 | 0.00 | 24.00 |
| June | 33.50 | 24.00 | 73.67 | 24.00 | 0.00 | 24.00 |
| July | 44.50 | 24.00 | 564.83 | 24.00 | 15.33 | 24.00 |
| August | 1.17 | 24.00 | 632.50 | 24.00 | 1.00 | 24.00 |
| September | 25.67 | 24.00 | 560.83 | 24.00 | 25.67 | 24.00 |
| October | 369.50 | 23.80 | 141.50 | 23.86 | 0.00 | 23.86 |
| November | 577.33 | 23.40 | 88.33 | 23.48 | 54.83 | 23.52 |
| December | 744.00 | 22.28 | 92.50 | 22.15 | 92.50 | 22.05 |
| Annual Sum or Average | 5031.17 | 22.88 | 2219.50 | 23.16 | 254.67 | 23.13 |
| Minimum of Months | 1.17 | 21.57 | 0.00 | 21.57 | 0.00 | 21.57 |
| Maximum of Months | 744.00 | 24.00 | 632.50 | 24.00 | 92.50 | 24.00 |
Report: ComfortReportSimple55Monthly
For: OFFICE
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 20.33 | 23.96 | 11.00 | 24.03 | 0.00 | 24.03 |
| February | 71.33 | 23.86 | 0.00 | 23.86 | 0.00 | 23.86 |
| March | 87.83 | 23.77 | 8.50 | 23.82 | 0.00 | 23.82 |
| April | 1.00 | 23.99 | 82.83 | 24.36 | 0.00 | 24.36 |
| May | 0.00 | 0.00 | 85.67 | 24.42 | 0.00 | 24.42 |
| June | 0.00 | 0.00 | 154.00 | 24.24 | 0.00 | 24.24 |
| July | 10.67 | 25.64 | 140.00 | 24.34 | 10.67 | 24.43 |
| August | 11.17 | 25.66 | 161.00 | 24.33 | 11.17 | 24.41 |
| September | 8.33 | 25.65 | 140.00 | 24.32 | 8.33 | 24.39 |
| October | 2.83 | 25.26 | 115.17 | 24.27 | 2.17 | 24.30 |
| November | 3.00 | 24.10 | 72.83 | 24.29 | 0.00 | 24.29 |
| December | 70.67 | 23.91 | 6.17 | 23.95 | 0.00 | 23.95 |
| Annual Sum or Average | 287.17 | 24.06 | 977.17 | 24.22 | 32.33 | 24.26 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 23.82 | 0.00 | 23.82 |
| Maximum of Months | 87.83 | 25.66 | 161.00 | 24.42 | 11.17 | 24.43 |
Report: ComfortReportSimple55Monthly
For: G NE APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 744.00 | 22.65 | 35.00 | 22.59 | 35.00 | 22.53 |
| February | 672.00 | 21.64 | 0.00 | 21.64 | 0.00 | 21.64 |
| March | 744.00 | 22.39 | 20.33 | 22.36 | 20.33 | 22.32 |
| April | 554.50 | 23.90 | 0.00 | 23.90 | 0.00 | 23.90 |
| May | 485.83 | 24.00 | 0.00 | 24.00 | 0.00 | 24.00 |
| June | 27.67 | 24.00 | 82.17 | 24.00 | 0.00 | 24.00 |
| July | 33.17 | 24.00 | 568.83 | 24.00 | 12.50 | 24.00 |
| August | 4.33 | 24.00 | 632.83 | 24.00 | 0.83 | 24.00 |
| September | 24.50 | 24.00 | 555.00 | 24.00 | 24.50 | 24.00 |
| October | 377.83 | 23.85 | 144.83 | 23.89 | 0.00 | 23.89 |
| November | 582.83 | 23.42 | 81.67 | 23.49 | 57.50 | 23.53 |
| December | 744.00 | 22.31 | 75.83 | 22.20 | 75.83 | 22.11 |
| Annual Sum or Average | 4994.67 | 22.90 | 2196.50 | 23.18 | 226.50 | 23.16 |
| Minimum of Months | 4.33 | 21.64 | 0.00 | 21.64 | 0.00 | 21.64 |
| Maximum of Months | 744.00 | 24.00 | 632.83 | 24.00 | 75.83 | 24.00 |
Report: ComfortReportSimple55Monthly
For: G N1 APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 742.17 | 22.93 | 6.83 | 22.92 | 6.83 | 22.92 |
| February | 672.00 | 21.95 | 0.00 | 21.95 | 0.00 | 21.95 |
| March | 744.00 | 22.62 | 0.00 | 22.62 | 0.00 | 22.62 |
| April | 633.83 | 23.94 | 0.00 | 23.94 | 0.00 | 23.94 |
| May | 675.00 | 24.00 | 0.00 | 24.00 | 0.00 | 24.00 |
| June | 62.17 | 24.00 | 37.17 | 24.00 | 0.00 | 24.00 |
| July | 64.33 | 24.00 | 551.33 | 24.00 | 13.83 | 24.00 |
| August | 13.33 | 24.00 | 614.00 | 24.00 | 0.67 | 24.00 |
| September | 26.50 | 24.00 | 509.00 | 24.00 | 26.50 | 24.00 |
| October | 379.50 | 23.91 | 124.17 | 23.93 | 0.00 | 23.93 |
| November | 566.83 | 23.60 | 81.00 | 23.65 | 49.50 | 23.67 |
| December | 744.00 | 22.53 | 20.83 | 22.49 | 20.83 | 22.45 |
| Annual Sum or Average | 5323.67 | 23.14 | 1944.33 | 23.36 | 118.17 | 23.36 |
| Minimum of Months | 13.33 | 21.95 | 0.00 | 21.95 | 0.00 | 21.95 |
| Maximum of Months | 744.00 | 24.00 | 614.00 | 24.00 | 49.50 | 24.00 |
Report: ComfortReportSimple55Monthly
For: G N2 APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 742.17 | 22.93 | 7.17 | 22.92 | 7.17 | 22.91 |
| February | 672.00 | 21.96 | 0.00 | 21.96 | 0.00 | 21.96 |
| March | 744.00 | 22.63 | 0.00 | 22.63 | 0.00 | 22.63 |
| April | 634.33 | 23.94 | 0.00 | 23.94 | 0.00 | 23.94 |
| May | 674.83 | 24.00 | 0.00 | 24.00 | 0.00 | 24.00 |
| June | 62.00 | 24.00 | 37.50 | 24.00 | 0.00 | 24.00 |
| July | 64.33 | 24.00 | 552.00 | 24.00 | 13.67 | 24.00 |
| August | 13.67 | 24.00 | 614.00 | 24.00 | 0.67 | 24.00 |
| September | 26.50 | 24.00 | 509.17 | 24.00 | 26.50 | 24.00 |
| October | 379.17 | 23.91 | 124.67 | 23.93 | 0.00 | 23.93 |
| November | 567.50 | 23.60 | 80.83 | 23.65 | 49.67 | 23.67 |
| December | 744.00 | 22.53 | 19.33 | 22.50 | 19.33 | 22.46 |
| Annual Sum or Average | 5324.50 | 23.14 | 1944.67 | 23.36 | 117.00 | 23.36 |
| Minimum of Months | 13.67 | 21.96 | 0.00 | 21.96 | 0.00 | 21.96 |
| Maximum of Months | 744.00 | 24.00 | 614.00 | 24.00 | 49.67 | 24.00 |
Report: ComfortReportSimple55Monthly
For: G S1 APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 405.17 | 23.69 | 9.67 | 23.70 | 0.00 | 23.70 |
| February | 463.50 | 23.14 | 0.00 | 23.14 | 0.00 | 23.14 |
| March | 467.00 | 23.21 | 0.00 | 23.21 | 0.00 | 23.21 |
| April | 383.67 | 23.96 | 0.00 | 23.96 | 0.00 | 23.96 |
| May | 447.67 | 24.00 | 0.00 | 24.00 | 0.00 | 24.00 |
| June | 55.00 | 24.00 | 23.83 | 24.00 | 0.00 | 24.00 |
| July | 52.67 | 24.00 | 387.50 | 24.00 | 14.17 | 24.00 |
| August | 4.00 | 24.00 | 416.33 | 24.00 | 0.50 | 24.00 |
| September | 23.67 | 24.00 | 390.17 | 24.00 | 23.67 | 24.00 |
| October | 144.50 | 23.98 | 126.50 | 23.99 | 0.00 | 23.99 |
| November | 260.67 | 23.91 | 105.50 | 23.94 | 40.33 | 23.94 |
| December | 482.00 | 23.57 | 0.00 | 23.57 | 0.00 | 23.57 |
| Annual Sum or Average | 3189.50 | 23.64 | 1459.50 | 23.75 | 78.67 | 23.76 |
| Minimum of Months | 4.00 | 23.14 | 0.00 | 23.14 | 0.00 | 23.14 |
| Maximum of Months | 482.00 | 24.00 | 416.33 | 24.00 | 40.33 | 24.00 |
Report: ComfortReportSimple55Monthly
For: G S2 APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 386.00 | 23.70 | 10.17 | 23.71 | 0.00 | 23.71 |
| February | 455.17 | 23.21 | 0.00 | 23.21 | 0.00 | 23.21 |
| March | 442.67 | 23.25 | 0.00 | 23.25 | 0.00 | 23.25 |
| April | 329.00 | 23.96 | 0.00 | 23.96 | 0.00 | 23.96 |
| May | 356.83 | 24.00 | 0.00 | 24.00 | 0.00 | 24.00 |
| June | 23.00 | 24.00 | 36.17 | 24.00 | 0.00 | 24.00 |
| July | 34.00 | 24.00 | 398.83 | 24.00 | 9.83 | 24.00 |
| August | 0.00 | 0.00 | 426.33 | 24.00 | 0.00 | 24.00 |
| September | 11.67 | 24.00 | 411.33 | 24.00 | 11.67 | 24.00 |
| October | 117.00 | 23.98 | 144.17 | 23.99 | 0.00 | 23.99 |
| November | 241.50 | 23.93 | 112.50 | 23.95 | 34.67 | 23.96 |
| December | 471.83 | 23.59 | 0.00 | 23.59 | 0.00 | 23.59 |
| Annual Sum or Average | 2868.67 | 23.64 | 1539.50 | 23.77 | 56.17 | 23.77 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 23.21 | 0.00 | 23.21 |
| Maximum of Months | 471.83 | 24.00 | 426.33 | 24.00 | 34.67 | 24.00 |
Report: ComfortReportSimple55Monthly
For: M SW APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 427.17 | 23.38 | 7.33 | 23.39 | 0.00 | 23.39 |
| February | 376.50 | 23.06 | 2.50 | 23.06 | 0.00 | 23.06 |
| March | 358.00 | 23.17 | 1.50 | 23.18 | 0.00 | 23.18 |
| April | 281.50 | 23.96 | 0.00 | 23.96 | 0.00 | 23.96 |
| May | 288.83 | 24.00 | 0.00 | 24.00 | 0.00 | 24.00 |
| June | 43.17 | 24.00 | 36.67 | 24.00 | 0.00 | 24.00 |
| July | 63.83 | 24.00 | 387.00 | 24.00 | 24.33 | 24.00 |
| August | 32.17 | 24.00 | 408.50 | 24.00 | 7.00 | 24.00 |
| September | 33.33 | 24.00 | 361.17 | 24.00 | 33.33 | 24.00 |
| October | 235.50 | 23.77 | 99.17 | 23.84 | 0.00 | 23.84 |
| November | 358.83 | 23.48 | 86.67 | 23.57 | 49.50 | 23.61 |
| December | 510.17 | 22.96 | 7.33 | 22.93 | 7.33 | 22.91 |
| Annual Sum or Average | 3009.00 | 23.43 | 1397.83 | 23.61 | 121.50 | 23.61 |
| Minimum of Months | 32.17 | 22.96 | 0.00 | 22.93 | 0.00 | 22.91 |
| Maximum of Months | 510.17 | 24.00 | 408.50 | 24.00 | 49.50 | 24.00 |
Report: ComfortReportSimple55Monthly
For: M NW APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 734.33 | 22.95 | 14.83 | 22.94 | 11.50 | 22.92 |
| February | 667.83 | 22.45 | 0.00 | 22.45 | 0.00 | 22.45 |
| March | 679.00 | 23.06 | 0.00 | 23.06 | 0.00 | 23.06 |
| April | 479.83 | 23.95 | 0.00 | 23.95 | 0.00 | 23.95 |
| May | 418.50 | 24.00 | 0.00 | 24.00 | 0.00 | 24.00 |
| June | 45.50 | 24.00 | 65.00 | 24.00 | 0.00 | 24.00 |
| July | 71.50 | 24.00 | 553.33 | 24.00 | 24.67 | 24.00 |
| August | 46.83 | 24.00 | 599.50 | 24.00 | 12.33 | 24.00 |
| September | 40.50 | 24.00 | 482.67 | 24.00 | 40.50 | 24.00 |
| October | 462.50 | 23.64 | 98.67 | 23.71 | 0.00 | 23.71 |
| November | 614.00 | 23.07 | 84.00 | 23.15 | 66.83 | 23.20 |
| December | 744.00 | 22.12 | 137.17 | 21.97 | 137.17 | 21.85 |
| Annual Sum or Average | 5004.33 | 23.08 | 2035.17 | 23.28 | 293.00 | 23.25 |
| Minimum of Months | 40.50 | 22.12 | 0.00 | 21.97 | 0.00 | 21.85 |
| Maximum of Months | 744.00 | 24.00 | 599.50 | 24.00 | 137.17 | 24.00 |
Report: ComfortReportSimple55Monthly
For: M SE APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 432.17 | 23.38 | 7.33 | 23.39 | 0.00 | 23.39 |
| February | 372.00 | 23.07 | 6.17 | 23.08 | 0.00 | 23.08 |
| March | 356.83 | 23.20 | 3.83 | 23.21 | 0.00 | 23.21 |
| April | 293.67 | 23.96 | 0.50 | 23.96 | 0.00 | 23.96 |
| May | 295.67 | 24.00 | 0.00 | 24.00 | 0.00 | 24.00 |
| June | 44.67 | 24.00 | 40.33 | 24.00 | 0.00 | 24.00 |
| July | 57.00 | 24.00 | 390.83 | 24.00 | 23.00 | 24.00 |
| August | 31.33 | 24.00 | 406.50 | 24.00 | 5.67 | 24.00 |
| September | 32.17 | 24.00 | 359.83 | 24.00 | 32.17 | 24.00 |
| October | 237.67 | 23.77 | 97.67 | 23.84 | 0.00 | 23.84 |
| November | 364.83 | 23.48 | 80.83 | 23.57 | 55.67 | 23.61 |
| December | 510.50 | 22.97 | 5.83 | 22.95 | 5.83 | 22.93 |
| Annual Sum or Average | 3028.50 | 23.45 | 1399.67 | 23.62 | 122.33 | 23.62 |
| Minimum of Months | 31.33 | 22.97 | 0.00 | 22.95 | 0.00 | 22.93 |
| Maximum of Months | 510.50 | 24.00 | 406.50 | 24.00 | 55.67 | 24.00 |
Report: ComfortReportSimple55Monthly
For: M NE APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 733.50 | 22.98 | 15.00 | 22.96 | 12.17 | 22.94 |
| February | 659.17 | 22.54 | 0.00 | 22.54 | 0.00 | 22.54 |
| March | 674.67 | 23.13 | 0.00 | 23.13 | 0.00 | 23.13 |
| April | 480.67 | 23.96 | 0.00 | 23.96 | 0.00 | 23.96 |
| May | 372.33 | 24.00 | 0.00 | 24.00 | 0.00 | 24.00 |
| June | 38.83 | 24.00 | 69.83 | 24.00 | 0.00 | 24.00 |
| July | 55.50 | 24.00 | 555.33 | 24.00 | 21.67 | 24.00 |
| August | 39.67 | 24.00 | 591.50 | 24.00 | 9.67 | 24.00 |
| September | 37.00 | 24.00 | 485.00 | 24.00 | 37.00 | 24.00 |
| October | 447.00 | 23.69 | 105.33 | 23.75 | 0.00 | 23.75 |
| November | 613.67 | 23.10 | 76.50 | 23.17 | 63.50 | 23.22 |
| December | 744.00 | 22.15 | 121.17 | 22.01 | 121.17 | 21.90 |
| Annual Sum or Average | 4896.00 | 23.10 | 2019.67 | 23.31 | 265.17 | 23.28 |
| Minimum of Months | 37.00 | 22.15 | 0.00 | 22.01 | 0.00 | 21.90 |
| Maximum of Months | 744.00 | 24.00 | 591.50 | 24.00 | 121.17 | 24.00 |
Report: ComfortReportSimple55Monthly
For: M N1 APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 728.00 | 23.29 | 7.67 | 23.30 | 0.33 | 23.30 |
| February | 617.17 | 22.93 | 0.00 | 22.93 | 0.00 | 22.93 |
| March | 664.17 | 23.39 | 0.00 | 23.39 | 0.00 | 23.39 |
| April | 612.33 | 23.98 | 0.00 | 23.98 | 0.00 | 23.98 |
| May | 648.67 | 24.00 | 0.00 | 24.00 | 0.00 | 24.00 |
| June | 114.83 | 24.00 | 21.17 | 24.00 | 0.00 | 24.00 |
| July | 95.50 | 24.00 | 520.17 | 24.00 | 20.83 | 24.00 |
| August | 62.17 | 24.00 | 545.83 | 24.00 | 6.33 | 24.00 |
| September | 37.33 | 24.00 | 438.17 | 24.00 | 36.00 | 24.00 |
| October | 459.50 | 23.83 | 88.67 | 23.86 | 0.00 | 23.86 |
| November | 585.67 | 23.39 | 77.33 | 23.46 | 53.17 | 23.50 |
| December | 744.00 | 22.48 | 54.50 | 22.38 | 54.50 | 22.30 |
| Annual Sum or Average | 5369.33 | 23.41 | 1753.50 | 23.53 | 171.17 | 23.52 |
| Minimum of Months | 37.33 | 22.48 | 0.00 | 22.38 | 0.00 | 22.30 |
| Maximum of Months | 744.00 | 24.00 | 545.83 | 24.00 | 54.50 | 24.00 |
Report: ComfortReportSimple55Monthly
For: M N2 APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 728.17 | 23.29 | 7.67 | 23.29 | 0.50 | 23.30 |
| February | 612.83 | 22.94 | 0.00 | 22.94 | 0.00 | 22.94 |
| March | 659.83 | 23.40 | 0.00 | 23.40 | 0.00 | 23.40 |
| April | 612.33 | 23.98 | 0.00 | 23.98 | 0.00 | 23.98 |
| May | 648.17 | 24.00 | 0.00 | 24.00 | 0.00 | 24.00 |
| June | 112.83 | 24.00 | 21.83 | 24.00 | 0.00 | 24.00 |
| July | 95.50 | 24.00 | 521.83 | 24.00 | 20.83 | 24.00 |
| August | 61.67 | 24.00 | 546.33 | 24.00 | 6.17 | 24.00 |
| September | 37.17 | 24.00 | 439.17 | 24.00 | 35.83 | 24.00 |
| October | 457.17 | 23.83 | 88.83 | 23.86 | 0.00 | 23.86 |
| November | 586.50 | 23.40 | 77.33 | 23.46 | 53.83 | 23.50 |
| December | 744.00 | 22.48 | 53.50 | 22.39 | 53.50 | 22.31 |
| Annual Sum or Average | 5356.17 | 23.41 | 1756.50 | 23.54 | 170.67 | 23.53 |
| Minimum of Months | 37.17 | 22.48 | 0.00 | 22.39 | 0.00 | 22.31 |
| Maximum of Months | 744.00 | 24.00 | 546.33 | 24.00 | 53.83 | 24.00 |
Report: ComfortReportSimple55Monthly
For: M S1 APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 385.50 | 23.73 | 8.50 | 23.74 | 0.00 | 23.74 |
| February | 269.83 | 23.52 | 12.50 | 23.54 | 0.00 | 23.54 |
| March | 296.50 | 23.52 | 0.00 | 23.52 | 0.00 | 23.52 |
| April | 357.83 | 23.99 | 0.00 | 23.99 | 0.00 | 23.99 |
| May | 432.00 | 24.00 | 0.00 | 24.00 | 0.00 | 24.00 |
| June | 89.83 | 24.00 | 15.33 | 24.00 | 0.00 | 24.00 |
| July | 88.00 | 24.00 | 372.67 | 24.00 | 22.00 | 24.00 |
| August | 41.50 | 24.00 | 373.33 | 24.00 | 3.67 | 24.00 |
| September | 32.17 | 24.00 | 346.50 | 24.00 | 32.17 | 24.00 |
| October | 228.00 | 23.93 | 88.17 | 23.95 | 0.00 | 23.95 |
| November | 320.00 | 23.78 | 85.17 | 23.83 | 44.67 | 23.85 |
| December | 497.33 | 23.47 | 0.00 | 23.47 | 0.00 | 23.47 |
| Annual Sum or Average | 3038.50 | 23.76 | 1302.17 | 23.83 | 102.50 | 23.84 |
| Minimum of Months | 32.17 | 23.47 | 0.00 | 23.47 | 0.00 | 23.47 |
| Maximum of Months | 497.33 | 24.00 | 373.33 | 24.00 | 44.67 | 24.00 |
Report: ComfortReportSimple55Monthly
For: M S2 APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 386.00 | 23.73 | 8.50 | 23.74 | 0.00 | 23.74 |
| February | 269.67 | 23.52 | 13.33 | 23.54 | 0.00 | 23.54 |
| March | 296.17 | 23.52 | 0.00 | 23.52 | 0.00 | 23.52 |
| April | 358.50 | 23.99 | 0.00 | 23.99 | 0.00 | 23.99 |
| May | 431.67 | 24.00 | 0.00 | 24.00 | 0.00 | 24.00 |
| June | 90.67 | 24.00 | 16.00 | 24.00 | 0.00 | 24.00 |
| July | 88.33 | 24.00 | 372.67 | 24.00 | 21.67 | 24.00 |
| August | 41.33 | 24.00 | 372.83 | 24.00 | 3.50 | 24.00 |
| September | 32.17 | 24.00 | 346.33 | 24.00 | 32.17 | 24.00 |
| October | 227.83 | 23.93 | 88.17 | 23.95 | 0.00 | 23.95 |
| November | 320.00 | 23.78 | 85.17 | 23.83 | 44.83 | 23.84 |
| December | 497.00 | 23.47 | 0.00 | 23.47 | 0.00 | 23.47 |
| Annual Sum or Average | 3039.33 | 23.76 | 1303.00 | 23.83 | 102.17 | 23.84 |
| Minimum of Months | 32.17 | 23.47 | 0.00 | 23.47 | 0.00 | 23.47 |
| Maximum of Months | 497.00 | 24.00 | 372.83 | 24.00 | 44.83 | 24.00 |
Report: ComfortReportSimple55Monthly
For: T SW APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 461.17 | 22.20 | 81.83 | 22.09 | 74.50 | 21.98 |
| February | 442.50 | 21.76 | 29.17 | 21.72 | 29.17 | 21.69 |
| March | 422.17 | 22.18 | 68.50 | 22.10 | 56.67 | 21.99 |
| April | 297.33 | 23.43 | 32.17 | 23.44 | 5.17 | 23.40 |
| May | 279.67 | 23.82 | 23.50 | 23.83 | 0.00 | 23.83 |
| June | 99.50 | 24.00 | 142.50 | 24.00 | 0.00 | 24.00 |
| July | 83.17 | 24.00 | 414.50 | 24.00 | 40.33 | 24.00 |
| August | 66.17 | 23.99 | 421.17 | 24.00 | 35.83 | 24.00 |
| September | 78.50 | 23.95 | 377.67 | 23.99 | 54.67 | 23.99 |
| October | 303.67 | 22.88 | 119.17 | 23.06 | 23.33 | 22.98 |
| November | 438.17 | 22.35 | 143.17 | 22.34 | 125.83 | 22.30 |
| December | 504.67 | 21.94 | 230.33 | 21.68 | 229.33 | 21.54 |
| Annual Sum or Average | 3476.67 | 22.58 | 2083.67 | 22.86 | 674.83 | 22.75 |
| Minimum of Months | 66.17 | 21.76 | 23.50 | 21.68 | 0.00 | 21.54 |
| Maximum of Months | 504.67 | 24.00 | 421.17 | 24.00 | 229.33 | 24.00 |
Report: ComfortReportSimple55Monthly
For: T NW APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 741.17 | 22.18 | 176.33 | 21.98 | 176.17 | 21.84 |
| February | 670.17 | 21.60 | 76.00 | 21.55 | 76.00 | 21.51 |
| March | 670.33 | 22.20 | 94.67 | 22.06 | 94.67 | 21.96 |
| April | 411.67 | 23.45 | 34.67 | 23.44 | 7.67 | 23.40 |
| May | 332.17 | 23.85 | 30.67 | 23.86 | 0.00 | 23.86 |
| June | 96.17 | 24.00 | 259.33 | 24.00 | 0.00 | 24.00 |
| July | 86.00 | 24.00 | 600.33 | 24.00 | 41.33 | 24.00 |
| August | 75.83 | 24.00 | 635.50 | 24.00 | 40.17 | 24.00 |
| September | 94.83 | 23.95 | 539.67 | 23.99 | 61.83 | 23.99 |
| October | 481.50 | 22.78 | 175.00 | 22.87 | 58.67 | 22.75 |
| November | 667.67 | 22.24 | 223.67 | 22.15 | 206.33 | 22.06 |
| December | 744.00 | 21.67 | 435.67 | 21.46 | 435.67 | 21.36 |
| Annual Sum or Average | 5071.50 | 22.43 | 3281.50 | 22.70 | 1198.50 | 22.56 |
| Minimum of Months | 75.83 | 21.60 | 30.67 | 21.46 | 0.00 | 21.36 |
| Maximum of Months | 744.00 | 24.00 | 635.50 | 24.00 | 435.67 | 24.00 |
Report: ComfortReportSimple55Monthly
For: T SE APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 470.83 | 22.23 | 79.83 | 22.12 | 73.33 | 22.02 |
| February | 441.00 | 21.77 | 35.00 | 21.74 | 33.00 | 21.69 |
| March | 424.33 | 22.20 | 63.67 | 22.10 | 55.83 | 22.00 |
| April | 303.67 | 23.45 | 21.00 | 23.44 | 5.33 | 23.40 |
| May | 279.67 | 23.83 | 3.17 | 23.84 | 0.00 | 23.84 |
| June | 98.67 | 24.00 | 120.67 | 24.00 | 0.00 | 24.00 |
| July | 80.17 | 24.00 | 406.83 | 24.00 | 39.17 | 24.00 |
| August | 64.50 | 24.00 | 420.00 | 24.00 | 34.67 | 24.00 |
| September | 75.67 | 23.95 | 373.17 | 23.99 | 53.67 | 23.99 |
| October | 305.33 | 22.88 | 114.00 | 23.05 | 23.50 | 22.97 |
| November | 438.83 | 22.33 | 143.67 | 22.31 | 128.00 | 22.25 |
| December | 503.17 | 21.94 | 228.67 | 21.68 | 228.67 | 21.54 |
| Annual Sum or Average | 3485.83 | 22.59 | 2009.67 | 22.84 | 675.17 | 22.74 |
| Minimum of Months | 64.50 | 21.77 | 3.17 | 21.68 | 0.00 | 21.54 |
| Maximum of Months | 503.17 | 24.00 | 420.00 | 24.00 | 228.67 | 24.00 |
Report: ComfortReportSimple55Monthly
For: T NE APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 743.83 | 22.20 | 157.50 | 22.02 | 157.50 | 21.89 |
| February | 671.00 | 21.64 | 70.00 | 21.59 | 70.00 | 21.55 |
| March | 664.33 | 22.26 | 82.00 | 22.13 | 82.00 | 22.03 |
| April | 385.83 | 23.48 | 22.33 | 23.47 | 6.17 | 23.43 |
| May | 294.83 | 23.85 | 10.83 | 23.86 | 0.00 | 23.86 |
| June | 91.17 | 24.00 | 284.83 | 24.00 | 0.00 | 24.00 |
| July | 80.67 | 24.00 | 603.00 | 24.00 | 40.50 | 24.00 |
| August | 70.33 | 24.00 | 638.50 | 24.00 | 38.33 | 24.00 |
| September | 86.67 | 23.95 | 541.33 | 23.99 | 58.00 | 23.99 |
| October | 475.17 | 22.84 | 165.17 | 22.95 | 48.17 | 22.84 |
| November | 675.83 | 22.26 | 215.00 | 22.15 | 201.50 | 22.06 |
| December | 744.00 | 21.65 | 422.17 | 21.45 | 422.17 | 21.36 |
| Annual Sum or Average | 4983.67 | 22.44 | 3212.67 | 22.72 | 1124.33 | 22.58 |
| Minimum of Months | 70.33 | 21.64 | 10.83 | 21.45 | 0.00 | 21.36 |
| Maximum of Months | 744.00 | 24.00 | 638.50 | 24.00 | 422.17 | 24.00 |
Report: ComfortReportSimple55Monthly
For: T N1 APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 742.83 | 22.23 | 111.00 | 22.10 | 111.00 | 21.99 |
| February | 672.00 | 21.66 | 50.00 | 21.62 | 50.00 | 21.59 |
| March | 701.17 | 22.41 | 69.83 | 22.30 | 69.83 | 22.20 |
| April | 471.83 | 23.67 | 2.83 | 23.65 | 2.83 | 23.64 |
| May | 366.33 | 23.93 | 0.00 | 23.93 | 0.00 | 23.93 |
| June | 105.83 | 24.00 | 125.17 | 24.00 | 0.00 | 24.00 |
| July | 83.33 | 24.00 | 557.33 | 24.00 | 32.67 | 24.00 |
| August | 60.67 | 24.00 | 606.33 | 24.00 | 22.50 | 24.00 |
| September | 77.00 | 23.98 | 499.17 | 24.00 | 54.33 | 24.00 |
| October | 514.50 | 23.02 | 138.83 | 23.09 | 37.00 | 23.00 |
| November | 674.17 | 22.37 | 188.17 | 22.29 | 178.33 | 22.22 |
| December | 744.00 | 21.67 | 394.17 | 21.47 | 394.17 | 21.38 |
| Annual Sum or Average | 5213.67 | 22.56 | 2742.83 | 22.77 | 952.67 | 22.64 |
| Minimum of Months | 60.67 | 21.66 | 0.00 | 21.47 | 0.00 | 21.38 |
| Maximum of Months | 744.00 | 24.00 | 606.33 | 24.00 | 394.17 | 24.00 |
Report: ComfortReportSimple55Monthly
For: T N2 APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 742.83 | 22.24 | 111.50 | 22.10 | 111.50 | 21.99 |
| February | 672.00 | 21.67 | 50.33 | 21.63 | 50.33 | 21.60 |
| March | 701.33 | 22.42 | 68.83 | 22.30 | 68.83 | 22.21 |
| April | 470.00 | 23.67 | 2.67 | 23.65 | 2.67 | 23.64 |
| May | 363.67 | 23.93 | 0.00 | 23.93 | 0.00 | 23.93 |
| June | 106.50 | 24.00 | 124.83 | 24.00 | 0.00 | 24.00 |
| July | 83.00 | 24.00 | 556.50 | 24.00 | 32.67 | 24.00 |
| August | 60.50 | 24.00 | 606.50 | 24.00 | 22.33 | 24.00 |
| September | 77.00 | 23.98 | 500.67 | 24.00 | 54.17 | 24.00 |
| October | 513.33 | 23.03 | 138.83 | 23.09 | 36.83 | 23.00 |
| November | 673.83 | 22.37 | 189.17 | 22.28 | 179.67 | 22.21 |
| December | 744.00 | 21.67 | 394.33 | 21.47 | 394.33 | 21.38 |
| Annual Sum or Average | 5208.00 | 22.56 | 2744.17 | 22.77 | 953.33 | 22.64 |
| Minimum of Months | 60.50 | 21.67 | 0.00 | 21.47 | 0.00 | 21.38 |
| Maximum of Months | 744.00 | 24.00 | 606.50 | 24.00 | 394.33 | 24.00 |
Report: ComfortReportSimple55Monthly
For: T S1 APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 462.50 | 22.49 | 29.83 | 22.45 | 21.50 | 22.40 |
| February | 437.67 | 22.03 | 4.83 | 22.02 | 4.83 | 22.01 |
| March | 424.50 | 22.47 | 43.50 | 22.37 | 39.00 | 22.27 |
| April | 323.00 | 23.65 | 3.67 | 23.64 | 2.00 | 23.62 |
| May | 309.17 | 23.91 | 0.00 | 23.91 | 0.00 | 23.91 |
| June | 112.17 | 24.00 | 67.83 | 24.00 | 0.00 | 24.00 |
| July | 80.50 | 24.00 | 392.33 | 24.00 | 31.17 | 24.00 |
| August | 51.67 | 24.00 | 406.33 | 24.00 | 19.17 | 24.00 |
| September | 58.83 | 23.98 | 360.00 | 24.00 | 45.33 | 24.00 |
| October | 299.00 | 23.16 | 97.33 | 23.31 | 10.67 | 23.28 |
| November | 427.17 | 22.63 | 105.00 | 22.69 | 88.50 | 22.69 |
| December | 506.33 | 22.16 | 150.17 | 21.92 | 150.17 | 21.76 |
| Annual Sum or Average | 3492.50 | 22.82 | 1660.83 | 23.05 | 412.33 | 22.98 |
| Minimum of Months | 51.67 | 22.03 | 0.00 | 21.92 | 0.00 | 21.76 |
| Maximum of Months | 506.33 | 24.00 | 406.33 | 24.00 | 150.17 | 24.00 |
Report: ComfortReportSimple55Monthly
For: T S2 APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 462.00 | 22.48 | 30.50 | 22.45 | 21.67 | 22.40 |
| February | 436.33 | 22.03 | 4.83 | 22.02 | 4.83 | 22.01 |
| March | 424.17 | 22.47 | 43.50 | 22.37 | 39.00 | 22.27 |
| April | 323.83 | 23.65 | 3.67 | 23.64 | 2.00 | 23.62 |
| May | 308.83 | 23.91 | 0.00 | 23.91 | 0.00 | 23.91 |
| June | 112.50 | 24.00 | 67.67 | 24.00 | 0.00 | 24.00 |
| July | 80.33 | 24.00 | 391.67 | 24.00 | 31.17 | 24.00 |
| August | 51.50 | 24.00 | 406.33 | 24.00 | 19.00 | 24.00 |
| September | 58.83 | 23.98 | 359.83 | 24.00 | 45.33 | 24.00 |
| October | 299.33 | 23.16 | 97.50 | 23.31 | 10.83 | 23.28 |
| November | 427.33 | 22.63 | 105.17 | 22.69 | 88.33 | 22.69 |
| December | 506.33 | 22.16 | 150.17 | 21.92 | 150.17 | 21.76 |
| Annual Sum or Average | 3491.33 | 22.82 | 1660.83 | 23.05 | 412.33 | 22.98 |
| Minimum of Months | 51.50 | 22.03 | 0.00 | 21.92 | 0.00 | 21.76 |
| Maximum of Months | 506.33 | 24.00 | 406.33 | 24.00 | 150.17 | 24.00 |
Report: ComfortReportSimple55Monthly
For: T CORRIDOR
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 604.33 | 22.71 | 470.83 | 22.99 | 371.50 | 22.98 |
| February | 667.67 | 22.45 | 543.50 | 22.49 | 543.50 | 22.51 |
| March | 653.33 | 23.11 | 520.00 | 23.38 | 451.50 | 23.41 |
| April | 566.83 | 25.36 | 702.17 | 25.45 | 552.00 | 25.44 |
| May | 595.33 | 25.86 | 744.00 | 25.92 | 595.33 | 25.90 |
| June | 719.50 | 26.74 | 720.00 | 26.74 | 719.50 | 26.74 |
| July | 744.00 | 26.71 | 744.00 | 26.71 | 744.00 | 26.71 |
| August | 744.00 | 26.57 | 744.00 | 26.57 | 744.00 | 26.57 |
| September | 714.83 | 26.31 | 720.00 | 26.32 | 714.83 | 26.32 |
| October | 608.00 | 24.63 | 612.00 | 24.89 | 496.00 | 24.95 |
| November | 624.67 | 23.21 | 492.50 | 23.44 | 436.00 | 23.48 |
| December | 675.17 | 21.97 | 416.00 | 22.12 | 364.17 | 22.10 |
| Annual Sum or Average | 7917.67 | 24.70 | 7429.00 | 24.93 | 6732.33 | 25.00 |
| Minimum of Months | 566.83 | 21.97 | 416.00 | 22.12 | 364.17 | 22.10 |
| Maximum of Months | 744.00 | 26.74 | 744.00 | 26.74 | 744.00 | 26.74 |
Report: ComfortReportSimple55Monthly
For: G CORRIDOR
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 543.00 | 22.94 | 58.50 | 22.81 | 38.50 | 22.64 |
| February | 666.00 | 22.04 | 72.83 | 21.94 | 72.83 | 21.86 |
| March | 582.17 | 22.49 | 106.50 | 22.62 | 30.00 | 22.44 |
| April | 69.83 | 23.65 | 556.83 | 26.17 | 12.67 | 26.20 |
| May | 39.67 | 27.17 | 702.00 | 26.98 | 24.83 | 27.07 |
| June | 307.17 | 28.78 | 717.67 | 28.21 | 307.17 | 28.34 |
| July | 640.33 | 27.98 | 742.00 | 27.94 | 640.33 | 27.95 |
| August | 664.00 | 27.86 | 743.17 | 27.81 | 664.00 | 27.83 |
| September | 551.83 | 27.60 | 719.00 | 27.51 | 551.83 | 27.54 |
| October | 215.17 | 25.53 | 557.00 | 26.20 | 130.50 | 26.35 |
| November | 351.17 | 23.44 | 289.00 | 24.12 | 105.50 | 24.14 |
| December | 644.50 | 22.42 | 58.33 | 22.13 | 49.67 | 21.85 |
| Annual Sum or Average | 5274.83 | 24.95 | 5322.83 | 25.93 | 2627.83 | 26.18 |
| Minimum of Months | 39.67 | 22.04 | 58.33 | 21.94 | 12.67 | 21.85 |
| Maximum of Months | 666.00 | 28.78 | 743.17 | 28.21 | 664.00 | 28.34 |
Report: ComfortReportSimple55Monthly
For: M CORRIDOR
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 719.17 | 24.81 | 723.67 | 24.83 | 698.83 | 24.84 |
| February | 654.83 | 24.45 | 668.00 | 24.45 | 654.83 | 24.45 |
| March | 711.83 | 24.90 | 738.50 | 24.89 | 711.83 | 24.89 |
| April | 708.50 | 25.92 | 720.00 | 25.92 | 708.50 | 25.92 |
| May | 733.83 | 26.11 | 744.00 | 26.12 | 733.83 | 26.12 |
| June | 720.00 | 26.43 | 720.00 | 26.43 | 720.00 | 26.43 |
| July | 744.00 | 26.35 | 744.00 | 26.35 | 744.00 | 26.35 |
| August | 744.00 | 26.29 | 744.00 | 26.29 | 744.00 | 26.29 |
| September | 720.00 | 26.17 | 720.00 | 26.17 | 720.00 | 26.17 |
| October | 700.17 | 25.66 | 744.00 | 25.67 | 700.17 | 25.66 |
| November | 683.33 | 25.05 | 719.00 | 25.04 | 683.33 | 25.05 |
| December | 739.83 | 24.10 | 739.83 | 24.10 | 739.83 | 24.10 |
| Annual Sum or Average | 8579.50 | 25.53 | 8725.00 | 25.53 | 8559.17 | 25.53 |
| Minimum of Months | 654.83 | 24.10 | 668.00 | 24.10 | 654.83 | 24.10 |
| Maximum of Months | 744.00 | 26.43 | 744.00 | 26.43 | 744.00 | 26.43 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_GSW
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 515.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 492.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 524.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 6145.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_GNW
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 8760.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_OFFICE
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 140.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 133.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 161.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 140.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 154.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 154.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 140.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 161.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 140.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 147.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 140.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 140.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 1750.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 133.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 161.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_GNE
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 8760.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_GN1
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 8760.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_GN2
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 8760.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_GS1
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 515.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 492.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 524.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 6145.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_GS2
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 515.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 492.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 524.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 6145.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_MSW
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 515.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 492.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 524.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 6145.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_MNW
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 8760.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_MSE
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 515.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 492.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 524.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 6145.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_MNE
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 8760.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_MN1
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 8760.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_MN2
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 8760.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_MS1
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 515.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 492.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 524.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 6145.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_MS2
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 515.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 492.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 524.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 6145.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_TSW
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 515.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 492.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 524.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 6145.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_TNW
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 8760.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_TSE
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 515.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 492.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 524.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 6145.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_TNE
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 8760.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_TN1
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 8760.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_TN2
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 8760.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_TS1
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 515.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 492.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 524.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 6145.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_TS2
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 515.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 492.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 524.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 6145.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_T CORRIDOR
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 8760.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_G CORRIDOR
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 8760.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_M CORRIDOR
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 8760.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: DXReportMonthly
For: SPLIT GSW COOLING COIL
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.977194E+09 | 0.256913E+09 | 373.29 | 0.974517E+09 | 2677770.82 | 0.00 | 0.36 | 31-JAN-16:30 | 0.00 | 01-JAN-00:10 | 2053.37 | 31-JAN-16:30 | 2053.37 | 31-JAN-16:30 | 137.68 | 08-JAN-19:30 | 564.42 | 31-JAN-16:30 | 0.00 | 01-JAN-00:10 |
| February | 65317716.74 | 17329912.56 | 63.52 | 65307651.75 | 10064.99 | 0.00 | 0.17 | 01-FEB-15:30 | 0.00 | 01-FEB-00:10 | 1007.90 | 01-FEB-15:30 | 1007.90 | 01-FEB-15:30 | 4.41 | 18-FEB-14:30 | 264.16 | 01-FEB-15:30 | 0.00 | 01-FEB-00:10 |
| March | 0.338969E+09 | 90741123.82 | 162.76 | 0.338762E+09 | 207663.88 | 0.00 | 0.29 | 18-MAR-16:30 | 0.00 | 01-MAR-00:10 | 1697.28 | 18-MAR-16:30 | 1697.28 | 18-MAR-16:30 | 25.46 | 18-MAR-11:00 | 456.04 | 18-MAR-16:30 | 0.00 | 01-MAR-00:10 |
| April | 0.240001E+10 | 0.661942E+09 | 627.01 | 0.240001E+10 | 2027.46 | 0.00 | 0.48 | 14-APR-17:25 | 0.00 | 01-APR-00:10 | 2638.94 | 14-APR-17:25 | 2638.94 | 14-APR-17:25 | 0.52 | 17-APR-03:10 | 770.72 | 14-APR-17:25 | 0.00 | 01-APR-00:10 |
| May | 0.299790E+10 | 0.846617E+09 | 724.08 | 0.299790E+10 | 0.00 | 0.00 | 0.49 | 31-MAY-17:30 | 0.00 | 01-MAY-03:40 | 2602.75 | 15-MAY-17:15 | 2602.75 | 15-MAY-17:15 | 0.00 | 06-MAY-18:10 | 783.03 | 15-MAY-17:05 | 0.00 | 01-MAY-00:10 |
| June | 0.446831E+10 | 0.130671E+10 | 720.00 | 0.446113E+10 | 7184277.90 | 0.00 | 0.65 | 16-JUN-17:01 | 0.05 | 21-JUN-06:00 | 3439.91 | 30-JUN-17:04 | 3439.91 | 30-JUN-17:04 | 334.33 | 17-JUN-17:02 | 1079.07 | 28-JUN-17:04 | 0.00 | 01-JUN-00:10 |
| July | 0.524850E+10 | 0.147147E+10 | 744.00 | 0.480373E+10 | 0.444767E+09 | 0.00 | 0.62 | 22-JUL-17:40 | 0.08 | 01-JUL-06:00 | 3559.83 | 22-JUL-17:40 | 3559.83 | 22-JUL-17:40 | 642.01 | 13-JUL-19:00 | 1062.07 | 22-JUL-17:40 | 0.00 | 01-JUL-00:10 |
| August | 0.528758E+10 | 0.147373E+10 | 744.00 | 0.485194E+10 | 0.435638E+09 | 0.00 | 0.68 | 25-AUG-17:00 | 0.09 | 06-AUG-05:50 | 3768.65 | 13-AUG-16:01 | 3562.89 | 13-AUG-16:30 | 589.49 | 28-AUG-18:00 | 1114.94 | 13-AUG-16:01 | 0.00 | 01-AUG-00:10 |
| September | 0.507999E+10 | 0.137291E+10 | 720.00 | 0.462843E+10 | 0.451563E+09 | 0.00 | 0.61 | 08-SEP-16:10 | 0.05 | 22-SEP-06:00 | 3527.94 | 08-SEP-17:10 | 3505.88 | 08-SEP-16:08 | 665.21 | 10-SEP-20:00 | 1046.89 | 08-SEP-16:09 | 0.00 | 01-SEP-00:10 |
| October | 0.309631E+10 | 0.827372E+09 | 671.83 | 0.301811E+10 | 78200991.28 | 0.00 | 0.56 | 06-OCT-16:10 | 0.00 | 12-OCT-02:40 | 3168.26 | 10-OCT-15:30 | 3168.26 | 10-OCT-15:30 | 425.79 | 03-OCT-09:20 | 907.68 | 10-OCT-15:30 | 0.00 | 01-OCT-00:10 |
| November | 0.153147E+10 | 0.398076E+09 | 527.24 | 0.147740E+10 | 54064456.72 | 0.00 | 0.44 | 01-NOV-16:10 | 0.00 | 03-NOV-23:40 | 2710.43 | 01-NOV-16:02 | 2710.43 | 01-NOV-16:02 | 356.74 | 13-NOV-16:20 | 708.49 | 01-NOV-16:10 | 0.00 | 01-NOV-00:10 |
| December | 0.660792E+09 | 0.173778E+09 | 285.79 | 0.660778E+09 | 13280.28 | 0.00 | 0.37 | 25-DEC-16:10 | 0.00 | 01-DEC-00:10 | 2157.68 | 25-DEC-16:20 | 2157.68 | 25-DEC-16:20 | 4.93 | 13-DEC-12:00 | 562.33 | 25-DEC-16:10 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.321523E+11 | 0.889760E+10 | 6363.52 | 0.306780E+11 | 0.147433E+10 | 0.00 | ||||||||||||||
| Minimum of Months | 65317716.74 | 17329912.56 | 63.52 | 65307651.75 | 0.00 | 0.00 | 0.17 | 0.00 | 1007.90 | 1007.90 | 0.00 | 264.16 | 0.00 | |||||||
| Maximum of Months | 0.528758E+10 | 0.147373E+10 | 744.00 | 0.485194E+10 | 0.451563E+09 | 0.00 | 0.68 | 0.09 | 3768.65 | 3562.89 | 665.21 | 1114.94 | 0.00 |
Report: DXReportMonthly
For: SPLIT GNW COOLING COIL
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 93368944.22 | 25312219.00 | 85.38 | 93365535.54 | 3408.67 | 0.00 | 0.17 | 31-JAN-17:02 | 0.00 | 01-JAN-00:10 | 899.48 | 31-JAN-17:02 | 899.48 | 31-JAN-17:02 | 1.48 | 08-JAN-13:00 | 252.58 | 31-JAN-17:02 | 0.00 | 01-JAN-00:10 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
| March | 0.144447E+09 | 39101292.57 | 95.75 | 0.144412E+09 | 35023.24 | 0.00 | 0.18 | 18-MAR-17:00 | 0.00 | 01-MAR-00:10 | 1030.30 | 18-MAR-17:00 | 1030.30 | 18-MAR-17:00 | 5.54 | 18-MAR-11:00 | 281.94 | 18-MAR-17:00 | 0.00 | 01-MAR-00:10 |
| April | 0.186800E+10 | 0.519039E+09 | 582.80 | 0.186800E+10 | 1189.13 | 0.00 | 0.44 | 14-APR-17:25 | 0.00 | 01-APR-00:10 | 2397.79 | 14-APR-17:40 | 2397.79 | 14-APR-17:40 | 0.31 | 17-APR-03:00 | 703.93 | 14-APR-17:25 | 0.00 | 01-APR-00:10 |
| May | 0.288682E+10 | 0.815496E+09 | 724.08 | 0.288682E+10 | 0.00 | 0.00 | 0.50 | 31-MAY-17:30 | 0.00 | 01-MAY-03:00 | 2626.39 | 31-MAY-18:00 | 2626.39 | 31-MAY-18:00 | 0.00 | 04-MAY-17:35 | 784.87 | 31-MAY-17:30 | 0.00 | 01-MAY-00:10 |
| June | 0.457316E+10 | 0.133376E+10 | 720.00 | 0.456626E+10 | 6902750.90 | 0.00 | 0.66 | 16-JUN-17:01 | 0.07 | 21-JUN-05:20 | 3505.44 | 29-JUN-17:50 | 3505.44 | 29-JUN-17:50 | 309.18 | 17-JUN-17:10 | 1098.13 | 28-JUN-17:04 | 0.00 | 01-JUN-00:10 |
| July | 0.523047E+10 | 0.146495E+10 | 744.00 | 0.478483E+10 | 0.445639E+09 | 0.00 | 0.62 | 22-JUL-18:00 | 0.09 | 01-JUL-06:00 | 3515.60 | 22-JUL-18:00 | 3515.60 | 22-JUL-18:00 | 648.23 | 13-JUL-19:00 | 1049.12 | 22-JUL-18:00 | 0.00 | 01-JUL-00:10 |
| August | 0.500427E+10 | 0.139607E+10 | 744.00 | 0.457323E+10 | 0.431037E+09 | 0.00 | 0.65 | 25-AUG-17:00 | 0.08 | 06-AUG-05:40 | 3445.96 | 13-AUG-16:13 | 3360.47 | 25-AUG-17:00 | 617.40 | 28-AUG-18:00 | 1053.83 | 25-AUG-17:00 | 0.00 | 01-AUG-00:10 |
| September | 0.452104E+10 | 0.122623E+10 | 720.00 | 0.409019E+10 | 0.430852E+09 | 0.00 | 0.55 | 08-SEP-17:10 | 0.04 | 22-SEP-06:00 | 3226.63 | 08-SEP-17:10 | 3119.75 | 08-SEP-16:40 | 605.81 | 10-SEP-21:00 | 946.24 | 08-SEP-17:10 | 0.00 | 01-SEP-00:10 |
| October | 0.208296E+10 | 0.564204E+09 | 592.66 | 0.201243E+10 | 70535020.58 | 0.00 | 0.46 | 06-OCT-16:10 | 0.00 | 09-OCT-07:01 | 2601.68 | 03-OCT-17:10 | 2550.83 | 04-OCT-16:50 | 392.83 | 03-OCT-09:20 | 747.06 | 06-OCT-16:01 | 0.00 | 01-OCT-00:10 |
| November | 0.502560E+09 | 0.131956E+09 | 311.27 | 0.469870E+09 | 32690469.32 | 0.00 | 0.29 | 01-NOV-16:02 | 0.00 | 02-NOV-05:03 | 1716.70 | 01-NOV-16:13 | 1709.92 | 01-NOV-16:08 | 223.15 | 13-NOV-16:20 | 459.17 | 01-NOV-16:02 | 0.00 | 01-NOV-00:10 |
| December | 45311102.95 | 12165780.98 | 50.22 | 45311102.95 | -0.0 | 0.00 | 0.13 | 25-DEC-16:10 | 0.00 | 01-DEC-00:10 | 714.28 | 25-DEC-16:20 | 714.28 | 25-DEC-16:20 | 0.00 | 25-DEC-15:50 | 192.99 | 25-DEC-16:10 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.269524E+11 | 0.752829E+10 | 5370.15 | 0.255347E+11 | 0.141770E+10 | 0.00 | ||||||||||||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | -0.0 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Maximum of Months | 0.523047E+10 | 0.146495E+10 | 744.00 | 0.478483E+10 | 0.445639E+09 | 0.00 | 0.66 | 0.09 | 3515.60 | 3515.60 | 648.23 | 1098.13 | 0.00 |
Report: DXReportMonthly
For: SPLIT OFFICE COOLING COIL
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.115160E+10 | 0.295319E+09 | 166.56 | 0.114882E+10 | 2781049.85 | 0.00 | 0.97 | 17-JAN-09:02 | 0.00 | 01-JAN-00:10 | 6936.45 | 09-JAN-09:02 | 6787.07 | 17-JAN-09:02 | 614.71 | 09-JAN-09:02 | 1562.86 | 17-JAN-09:02 | 0.00 | 01-JAN-00:10 |
| February | 0.485561E+09 | 0.126129E+09 | 147.08 | 0.474404E+09 | 11156750.37 | 0.00 | 0.46 | 01-FEB-09:03 | 0.00 | 01-FEB-00:10 | 3057.47 | 23-FEB-09:03 | 3057.47 | 23-FEB-09:03 | 244.94 | 22-FEB-09:03 | 754.70 | 23-FEB-09:03 | 0.00 | 01-FEB-00:10 |
| March | 0.745978E+09 | 0.194792E+09 | 179.81 | 0.743261E+09 | 2717663.06 | 0.00 | 0.92 | 21-MAR-08:62 | 0.00 | 01-MAR-00:10 | 6596.70 | 21-MAR-08:62 | 6596.70 | 21-MAR-08:62 | 98.22 | 06-MAR-13:40 | 1510.36 | 21-MAR-08:62 | 0.00 | 01-MAR-00:10 |
| April | 0.197261E+10 | 0.524178E+09 | 224.10 | 0.197261E+10 | -0.0 | 0.00 | 1.00 | 03-APR-08:62 | 0.00 | 01-APR-00:10 | 7383.87 | 17-APR-07:02 | 7383.87 | 17-APR-07:02 | 0.00 | 25-APR-12:00 | 1664.07 | 25-APR-08:62 | 0.00 | 01-APR-00:10 |
| May | 0.253179E+10 | 0.691985E+09 | 291.49 | 0.253179E+10 | -0.0 | 0.00 | 1.00 | 01-MAY-07:02 | 0.00 | 01-MAY-00:10 | 7432.43 | 11-MAY-07:02 | 7432.43 | 11-MAY-07:02 | 0.00 | 25-MAY-17:00 | 1684.12 | 18-MAY-08:62 | 0.00 | 01-MAY-00:10 |
| June | 0.367184E+10 | 0.105286E+10 | 498.82 | 0.366907E+10 | 2775099.30 | 0.00 | 1.00 | 01-JUN-07:02 | 0.00 | 01-JUN-00:10 | 7466.90 | 30-JUN-07:02 | 7466.90 | 30-JUN-07:02 | 446.28 | 30-JUN-08:08 | 1814.20 | 30-JUN-08:62 | 0.00 | 01-JUN-00:10 |
| July | 0.396974E+10 | 0.109294E+10 | 565.32 | 0.373207E+10 | 0.237670E+09 | 0.00 | 1.00 | 03-JUL-07:02 | 0.00 | 01-JUL-00:10 | 8371.72 | 14-JUL-07:02 | 7560.60 | 31-JUL-07:02 | 3139.82 | 14-JUL-07:03 | 1824.41 | 12-JUL-07:02 | 0.00 | 01-JUL-00:10 |
| August | 0.429706E+10 | 0.117738E+10 | 519.33 | 0.404964E+10 | 0.247414E+09 | 0.00 | 1.00 | 01-AUG-07:02 | 0.00 | 01-AUG-03:30 | 8134.05 | 01-AUG-07:02 | 7607.16 | 22-AUG-07:02 | 2160.86 | 01-AUG-07:03 | 1853.84 | 16-AUG-07:02 | 0.00 | 01-AUG-00:10 |
| September | 0.374615E+10 | 0.992646E+09 | 501.27 | 0.351107E+10 | 0.235075E+09 | 0.00 | 1.00 | 01-SEP-07:02 | 0.00 | 01-SEP-00:10 | 8198.95 | 05-SEP-06:02 | 7582.49 | 27-SEP-07:02 | 2210.84 | 05-SEP-07:03 | 1802.27 | 07-SEP-08:62 | 0.00 | 01-SEP-00:10 |
| October | 0.256185E+10 | 0.664535E+09 | 300.74 | 0.251923E+10 | 42624933.75 | 0.00 | 1.00 | 02-OCT-07:02 | 0.00 | 01-OCT-03:20 | 8110.98 | 03-OCT-07:02 | 7577.65 | 05-OCT-07:02 | 2086.58 | 03-OCT-07:03 | 1743.14 | 03-OCT-08:62 | 0.00 | 01-OCT-00:10 |
| November | 0.156540E+10 | 0.395750E+09 | 179.66 | 0.153621E+10 | 29196766.01 | 0.00 | 1.00 | 01-NOV-08:62 | 0.00 | 01-NOV-00:10 | 7812.95 | 14-NOV-09:02 | 7255.37 | 02-NOV-08:62 | 1860.66 | 14-NOV-09:02 | 1682.25 | 14-NOV-09:02 | 0.00 | 01-NOV-00:10 |
| December | 0.873606E+09 | 0.225329E+09 | 160.56 | 0.872574E+09 | 1032167.49 | 0.00 | 1.00 | 26-DEC-09:02 | 0.00 | 01-DEC-00:10 | 7017.55 | 26-DEC-09:02 | 7017.55 | 26-DEC-09:02 | 106.69 | 13-DEC-09:05 | 1606.09 | 26-DEC-09:02 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.275732E+11 | 0.743384E+10 | 3734.73 | 0.267607E+11 | 0.812444E+09 | 0.00 | ||||||||||||||
| Minimum of Months | 0.485561E+09 | 0.126129E+09 | 147.08 | 0.474404E+09 | -0.0 | 0.00 | 0.46 | 0.00 | 3057.47 | 3057.47 | 0.00 | 754.70 | 0.00 | |||||||
| Maximum of Months | 0.429706E+10 | 0.117738E+10 | 565.32 | 0.404964E+10 | 0.247414E+09 | 0.00 | 1.00 | 0.00 | 8371.72 | 7607.16 | 3139.82 | 1853.84 | 0.00 |
Report: DXReportMonthly
For: SPLIT GNE COOLING COIL
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 73183376.55 | 19901847.71 | 84.83 | 73179107.89 | 4268.66 | 0.00 | 0.13 | 31-JAN-17:02 | 0.00 | 01-JAN-00:10 | 677.78 | 31-JAN-17:02 | 677.78 | 31-JAN-17:02 | 1.71 | 08-JAN-13:00 | 191.26 | 31-JAN-17:02 | 0.00 | 01-JAN-00:10 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
| March | 0.146321E+09 | 39589564.15 | 100.78 | 0.146246E+09 | 74837.91 | 0.00 | 0.16 | 20-MAR-17:00 | 0.00 | 01-MAR-00:10 | 858.94 | 20-MAR-17:00 | 858.94 | 20-MAR-17:00 | 11.10 | 18-MAR-10:50 | 240.28 | 20-MAR-17:00 | 0.00 | 01-MAR-00:10 |
| April | 0.189975E+10 | 0.526450E+09 | 599.11 | 0.189974E+10 | 1083.88 | 0.00 | 0.39 | 14-APR-17:40 | 0.00 | 01-APR-00:10 | 1978.39 | 14-APR-18:00 | 1978.39 | 14-APR-18:00 | 0.28 | 17-APR-03:00 | 582.81 | 14-APR-17:30 | 0.00 | 01-APR-00:10 |
| May | 0.294780E+10 | 0.829333E+09 | 725.31 | 0.294780E+10 | -0.0 | 0.00 | 0.46 | 31-MAY-18:00 | 0.00 | 01-MAY-02:50 | 2259.44 | 31-MAY-18:00 | 2259.44 | 31-MAY-18:00 | 0.00 | 16-MAY-18:40 | 678.75 | 31-MAY-18:00 | 0.00 | 01-MAY-00:10 |
| June | 0.462719E+10 | 0.134327E+10 | 720.00 | 0.462008E+10 | 7104851.26 | 0.00 | 0.63 | 16-JUN-17:00 | 0.07 | 21-JUN-05:15 | 3209.45 | 17-JUN-17:10 | 3139.68 | 30-JUN-16:03 | 311.84 | 17-JUN-17:10 | 987.28 | 28-JUN-17:00 | 0.00 | 01-JUN-00:10 |
| July | 0.537225E+10 | 0.149691E+10 | 744.00 | 0.491797E+10 | 0.454275E+09 | 0.00 | 0.59 | 22-JUL-18:00 | 0.09 | 02-JUL-05:05 | 3222.97 | 23-JUL-13:00 | 3127.08 | 22-JUL-18:00 | 650.77 | 13-JUL-19:00 | 944.01 | 23-JUL-13:00 | 0.00 | 01-JUL-00:10 |
| August | 0.513752E+10 | 0.142566E+10 | 744.00 | 0.469625E+10 | 0.441266E+09 | 0.00 | 0.62 | 25-AUG-17:00 | 0.09 | 06-AUG-05:40 | 3152.39 | 13-AUG-16:01 | 2991.31 | 25-AUG-17:00 | 624.00 | 28-AUG-18:00 | 942.91 | 25-AUG-17:00 | 0.00 | 01-AUG-00:10 |
| September | 0.459360E+10 | 0.124050E+10 | 720.00 | 0.415526E+10 | 0.438340E+09 | 0.00 | 0.53 | 08-SEP-16:01 | 0.04 | 22-SEP-06:00 | 2883.01 | 08-SEP-17:10 | 2826.80 | 08-SEP-16:01 | 613.96 | 10-SEP-21:00 | 854.25 | 08-SEP-16:01 | 0.00 | 01-SEP-00:10 |
| October | 0.213003E+10 | 0.575083E+09 | 612.94 | 0.205735E+10 | 72681374.30 | 0.00 | 0.45 | 01-OCT-14:00 | 0.00 | 12-OCT-01:30 | 2501.30 | 03-OCT-17:20 | 2374.55 | 01-OCT-14:00 | 442.27 | 03-OCT-09:10 | 715.76 | 01-OCT-14:00 | 0.00 | 01-OCT-00:10 |
| November | 0.462972E+09 | 0.121722E+09 | 319.46 | 0.434760E+09 | 28212308.13 | 0.00 | 0.24 | 01-NOV-16:02 | 0.00 | 02-NOV-05:03 | 1346.49 | 01-NOV-16:02 | 1341.06 | 01-NOV-16:05 | 204.89 | 11-NOV-22:05 | 362.83 | 01-NOV-16:02 | 0.00 | 01-NOV-00:10 |
| December | 37388249.06 | 10054492.44 | 50.00 | 37388249.06 | 0.00 | 0.00 | 0.09 | 25-DEC-16:10 | 0.00 | 01-DEC-00:10 | 468.20 | 25-DEC-16:10 | 468.20 | 25-DEC-16:10 | 0.00 | 25-DEC-13:10 | 127.45 | 25-DEC-16:10 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.274280E+11 | 0.762847E+10 | 5420.44 | 0.259860E+11 | 0.144196E+10 | 0.00 | ||||||||||||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | -0.0 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Maximum of Months | 0.537225E+10 | 0.149691E+10 | 744.00 | 0.491797E+10 | 0.454275E+09 | 0.00 | 0.63 | 0.09 | 3222.97 | 3139.68 | 650.77 | 987.28 | 0.00 |
Report: DXReportMonthly
For: SPLIT GN1 COOLING COIL
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 82321760.28 | 22318863.42 | 101.17 | 82308883.42 | 12876.87 | 0.00 | 0.15 | 31-JAN-17:02 | 0.00 | 01-JAN-00:10 | 653.79 | 31-JAN-17:02 | 653.79 | 31-JAN-17:02 | 2.72 | 08-JAN-13:00 | 184.15 | 31-JAN-17:02 | 0.00 | 01-JAN-00:10 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
| March | 0.143750E+09 | 38795392.49 | 108.39 | 0.143695E+09 | 55659.83 | 0.00 | 0.17 | 20-MAR-17:00 | 0.00 | 01-MAR-00:10 | 814.60 | 20-MAR-17:10 | 814.60 | 20-MAR-17:10 | 7.70 | 18-MAR-10:50 | 227.23 | 20-MAR-17:00 | 0.00 | 01-MAR-00:10 |
| April | 0.157093E+10 | 0.435665E+09 | 623.39 | 0.157093E+10 | 3913.78 | 0.00 | 0.37 | 14-APR-17:40 | 0.00 | 01-APR-00:10 | 1658.02 | 14-APR-18:00 | 1658.02 | 14-APR-18:00 | 0.81 | 17-APR-03:10 | 489.94 | 14-APR-17:40 | 0.00 | 01-APR-00:10 |
| May | 0.246433E+10 | 0.693960E+09 | 740.15 | 0.246433E+10 | 0.00 | 0.00 | 0.44 | 31-MAY-18:00 | 0.00 | 01-MAY-03:50 | 1899.69 | 31-MAY-18:00 | 1899.69 | 31-MAY-18:00 | 0.00 | 09-MAY-14:00 | 572.53 | 31-MAY-18:00 | 0.00 | 01-MAY-00:10 |
| June | 0.375622E+10 | 0.109410E+10 | 720.00 | 0.374999E+10 | 6225492.32 | 0.00 | 0.58 | 16-JUN-17:01 | 0.08 | 21-JUN-05:15 | 2573.78 | 17-JUN-17:12 | 2529.33 | 29-JUN-18:00 | 248.92 | 17-JUN-17:10 | 808.80 | 28-JUN-17:04 | 0.00 | 01-JUN-00:10 |
| July | 0.438177E+10 | 0.122378E+10 | 744.00 | 0.398456E+10 | 0.397207E+09 | 0.00 | 0.54 | 05-JUL-18:00 | 0.10 | 02-JUL-05:10 | 2517.87 | 16-JUL-18:00 | 2507.00 | 22-JUL-18:00 | 547.36 | 13-JUL-19:20 | 757.98 | 22-JUL-18:00 | 0.00 | 01-JUL-00:10 |
| August | 0.418122E+10 | 0.116255E+10 | 744.00 | 0.379390E+10 | 0.387318E+09 | 0.00 | 0.56 | 25-AUG-17:00 | 0.12 | 24-AUG-05:50 | 2486.00 | 13-AUG-16:01 | 2395.78 | 25-AUG-17:00 | 541.85 | 28-AUG-18:00 | 761.74 | 25-AUG-17:00 | 0.00 | 01-AUG-00:10 |
| September | 0.378780E+10 | 0.102423E+10 | 720.00 | 0.340365E+10 | 0.384145E+09 | 0.00 | 0.48 | 08-SEP-17:10 | 0.06 | 22-SEP-06:00 | 2308.71 | 08-SEP-17:10 | 2236.14 | 08-SEP-16:06 | 534.47 | 10-SEP-21:00 | 684.84 | 08-SEP-17:10 | 0.00 | 01-SEP-00:10 |
| October | 0.178633E+10 | 0.482698E+09 | 625.40 | 0.172164E+10 | 64688535.76 | 0.00 | 0.42 | 03-OCT-17:20 | 0.00 | 12-OCT-02:00 | 2068.24 | 03-OCT-17:30 | 1917.18 | 03-OCT-17:12 | 351.69 | 03-OCT-09:20 | 590.25 | 03-OCT-17:20 | 0.00 | 01-OCT-00:10 |
| November | 0.463289E+09 | 0.121299E+09 | 356.83 | 0.427397E+09 | 35892684.96 | 0.00 | 0.24 | 01-NOV-16:03 | 0.00 | 02-NOV-05:03 | 1156.64 | 01-NOV-16:03 | 1147.19 | 01-NOV-16:03 | 225.83 | 11-NOV-22:05 | 311.86 | 01-NOV-16:03 | 0.00 | 01-NOV-00:10 |
| December | 36792051.72 | 9879823.06 | 53.83 | 36792051.72 | 0.00 | 0.00 | 0.10 | 25-DEC-16:10 | 0.00 | 01-DEC-00:10 | 442.99 | 25-DEC-16:10 | 442.99 | 25-DEC-16:10 | 0.00 | 25-DEC-16:00 | 120.47 | 25-DEC-16:10 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.226547E+11 | 0.630928E+10 | 5537.15 | 0.213792E+11 | 0.127555E+10 | 0.00 | ||||||||||||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Maximum of Months | 0.438177E+10 | 0.122378E+10 | 744.00 | 0.398456E+10 | 0.397207E+09 | 0.00 | 0.58 | 0.12 | 2573.78 | 2529.33 | 547.36 | 808.80 | 0.00 |
Report: DXReportMonthly
For: SPLIT GN2 COOLING COIL
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 83065576.08 | 22518706.65 | 102.00 | 83053289.90 | 12286.18 | 0.00 | 0.15 | 31-JAN-17:02 | 0.00 | 01-JAN-00:10 | 653.67 | 31-JAN-17:02 | 653.67 | 31-JAN-17:02 | 2.64 | 08-JAN-13:00 | 184.12 | 31-JAN-17:02 | 0.00 | 01-JAN-00:10 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
| March | 0.145022E+09 | 39135615.88 | 109.14 | 0.144965E+09 | 56641.30 | 0.00 | 0.17 | 20-MAR-17:00 | 0.00 | 01-MAR-00:10 | 815.47 | 20-MAR-17:10 | 815.47 | 20-MAR-17:10 | 7.81 | 18-MAR-10:50 | 227.52 | 20-MAR-17:00 | 0.00 | 01-MAR-00:10 |
| April | 0.157471E+10 | 0.436682E+09 | 623.90 | 0.157471E+10 | 3908.69 | 0.00 | 0.37 | 14-APR-17:40 | 0.00 | 01-APR-00:10 | 1651.80 | 14-APR-18:00 | 1651.80 | 14-APR-18:00 | 0.81 | 17-APR-03:10 | 488.27 | 14-APR-17:25 | 0.00 | 01-APR-00:10 |
| May | 0.246791E+10 | 0.694907E+09 | 740.15 | 0.246791E+10 | -0.0 | 0.00 | 0.44 | 31-MAY-18:00 | 0.00 | 01-MAY-03:50 | 1894.19 | 31-MAY-18:00 | 1894.19 | 31-MAY-18:00 | 0.00 | 08-MAY-18:30 | 570.94 | 31-MAY-18:00 | 0.00 | 01-MAY-00:10 |
| June | 0.375893E+10 | 0.109480E+10 | 720.00 | 0.375270E+10 | 6230594.27 | 0.00 | 0.58 | 16-JUN-17:01 | 0.08 | 21-JUN-05:15 | 2576.92 | 17-JUN-17:12 | 2523.14 | 29-JUN-18:00 | 249.08 | 17-JUN-17:10 | 807.37 | 28-JUN-17:04 | 0.00 | 01-JUN-00:10 |
| July | 0.438763E+10 | 0.122526E+10 | 744.00 | 0.399010E+10 | 0.397522E+09 | 0.00 | 0.54 | 05-JUL-18:00 | 0.10 | 02-JUL-05:10 | 2511.17 | 16-JUL-18:00 | 2501.86 | 22-JUL-18:00 | 547.93 | 13-JUL-19:20 | 756.47 | 22-JUL-18:00 | 0.00 | 01-JUL-00:10 |
| August | 0.418698E+10 | 0.116400E+10 | 744.00 | 0.379929E+10 | 0.387683E+09 | 0.00 | 0.56 | 25-AUG-17:00 | 0.12 | 24-AUG-05:50 | 2484.27 | 13-AUG-16:01 | 2391.53 | 25-AUG-17:00 | 542.29 | 28-AUG-18:00 | 760.42 | 25-AUG-17:00 | 0.00 | 01-AUG-00:10 |
| September | 0.379103E+10 | 0.102501E+10 | 720.00 | 0.340663E+10 | 0.384392E+09 | 0.00 | 0.48 | 08-SEP-17:10 | 0.06 | 22-SEP-06:00 | 2304.22 | 08-SEP-17:10 | 2233.77 | 08-SEP-16:06 | 535.08 | 10-SEP-21:00 | 683.54 | 08-SEP-17:10 | 0.00 | 01-SEP-00:10 |
| October | 0.179038E+10 | 0.483744E+09 | 626.40 | 0.172562E+10 | 64766550.90 | 0.00 | 0.42 | 03-OCT-17:20 | 0.00 | 12-OCT-02:00 | 2068.03 | 03-OCT-17:30 | 1916.95 | 03-OCT-17:12 | 352.90 | 03-OCT-09:20 | 590.12 | 03-OCT-17:20 | 0.00 | 01-OCT-00:10 |
| November | 0.463176E+09 | 0.121278E+09 | 356.92 | 0.427457E+09 | 35718997.18 | 0.00 | 0.24 | 01-NOV-16:03 | 0.00 | 02-NOV-05:03 | 1152.12 | 01-NOV-16:03 | 1142.73 | 01-NOV-16:03 | 225.70 | 11-NOV-22:05 | 310.67 | 01-NOV-16:03 | 0.00 | 01-NOV-00:10 |
| December | 37239106.97 | 9999122.93 | 53.89 | 37239106.97 | -0.0 | 0.00 | 0.10 | 25-DEC-16:10 | 0.00 | 01-DEC-00:10 | 441.38 | 25-DEC-16:10 | 441.38 | 25-DEC-16:10 | 0.00 | 01-DEC-16:40 | 120.03 | 25-DEC-16:10 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.226861E+11 | 0.631733E+10 | 5540.40 | 0.214097E+11 | 0.127639E+10 | 0.00 | ||||||||||||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | -0.0 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Maximum of Months | 0.438763E+10 | 0.122526E+10 | 744.00 | 0.399010E+10 | 0.397522E+09 | 0.00 | 0.58 | 0.12 | 2576.92 | 2523.14 | 547.93 | 807.37 | 0.00 |
Report: DXReportMonthly
For: SPLIT GS1 COOLING COIL
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.117101E+10 | 0.306346E+09 | 477.57 | 0.116668E+10 | 4328322.47 | 0.00 | 0.38 | 31-JAN-16:10 | 0.00 | 01-JAN-00:10 | 1777.79 | 31-JAN-16:10 | 1777.79 | 31-JAN-16:10 | 179.21 | 08-JAN-19:30 | 487.67 | 31-JAN-16:10 | 0.00 | 01-JAN-00:10 |
| February | 0.137501E+09 | 36348301.80 | 139.58 | 0.137100E+09 | 400980.17 | 0.00 | 0.21 | 01-FEB-15:30 | 0.00 | 01-FEB-01:50 | 1011.07 | 01-FEB-15:30 | 1011.07 | 01-FEB-15:30 | 27.41 | 18-FEB-12:00 | 263.55 | 01-FEB-15:30 | 0.00 | 01-FEB-00:10 |
| March | 0.401191E+09 | 0.106794E+09 | 247.26 | 0.400884E+09 | 306661.04 | 0.00 | 0.29 | 18-MAR-16:10 | 0.00 | 01-MAR-00:10 | 1418.92 | 18-MAR-16:10 | 1418.92 | 18-MAR-16:10 | 30.84 | 18-MAR-10:50 | 380.95 | 18-MAR-16:10 | 0.00 | 01-MAR-00:10 |
| April | 0.214340E+10 | 0.589317E+09 | 679.83 | 0.214340E+10 | 6023.24 | 0.00 | 0.42 | 14-APR-16:05 | 0.00 | 01-APR-00:10 | 1925.29 | 10-APR-16:02 | 1925.29 | 10-APR-16:02 | 1.21 | 17-APR-03:10 | 561.17 | 14-APR-16:02 | 0.00 | 01-APR-00:10 |
| May | 0.259118E+10 | 0.729402E+09 | 740.13 | 0.259118E+10 | -0.0 | 0.00 | 0.44 | 20-MAY-14:00 | 0.00 | 13-MAY-06:30 | 1940.71 | 20-MAY-14:00 | 1940.71 | 20-MAY-14:00 | 0.00 | 09-MAY-17:20 | 584.50 | 20-MAY-14:00 | 0.00 | 01-MAY-00:10 |
| June | 0.366391E+10 | 0.107053E+10 | 720.00 | 0.365738E+10 | 6529897.09 | 0.00 | 0.56 | 16-JUN-17:01 | 0.07 | 21-JUN-06:00 | 2614.03 | 17-JUN-17:02 | 2500.33 | 30-JUN-16:09 | 273.75 | 17-JUN-17:02 | 790.69 | 28-JUN-17:01 | 0.00 | 01-JUN-00:10 |
| July | 0.441576E+10 | 0.123474E+10 | 744.00 | 0.401855E+10 | 0.397207E+09 | 0.00 | 0.54 | 22-JUL-16:10 | 0.09 | 01-JUL-06:00 | 2627.41 | 23-JUL-13:00 | 2573.98 | 22-JUL-16:08 | 545.86 | 13-JUL-19:30 | 777.43 | 22-JUL-16:08 | 0.00 | 01-JUL-00:10 |
| August | 0.448453E+10 | 0.124574E+10 | 744.00 | 0.409107E+10 | 0.393459E+09 | 0.00 | 0.60 | 25-AUG-17:00 | 0.12 | 06-AUG-05:40 | 2810.93 | 13-AUG-16:01 | 2635.85 | 13-AUG-16:02 | 513.95 | 28-AUG-18:00 | 839.86 | 13-AUG-16:01 | 0.00 | 01-AUG-00:10 |
| September | 0.437217E+10 | 0.117752E+10 | 720.00 | 0.396483E+10 | 0.407339E+09 | 0.00 | 0.56 | 28-SEP-15:10 | 0.07 | 22-SEP-06:00 | 2635.89 | 08-SEP-16:09 | 2635.89 | 08-SEP-16:09 | 581.85 | 10-SEP-21:00 | 794.21 | 08-SEP-16:09 | 0.00 | 01-SEP-00:10 |
| October | 0.286122E+10 | 0.761366E+09 | 720.78 | 0.278804E+10 | 73183371.41 | 0.00 | 0.53 | 06-OCT-15:10 | 0.00 | 13-OCT-03:00 | 2520.07 | 10-OCT-15:10 | 2520.07 | 10-OCT-15:10 | 386.26 | 03-OCT-09:20 | 728.10 | 10-OCT-15:10 | 0.00 | 01-OCT-00:10 |
| November | 0.161318E+10 | 0.418159E+09 | 608.44 | 0.155443E+10 | 58753102.51 | 0.00 | 0.42 | 01-NOV-15:10 | 0.00 | 04-NOV-01:10 | 2137.56 | 01-NOV-15:10 | 2126.75 | 01-NOV-15:20 | 296.53 | 14-NOV-13:00 | 569.92 | 01-NOV-15:10 | 0.00 | 01-NOV-00:10 |
| December | 0.844493E+09 | 0.221495E+09 | 405.04 | 0.844402E+09 | 90684.09 | 0.00 | 0.37 | 25-DEC-16:10 | 0.00 | 01-DEC-01:10 | 1842.79 | 25-DEC-16:10 | 1842.79 | 25-DEC-16:10 | 13.91 | 13-DEC-11:00 | 479.79 | 25-DEC-16:10 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.286995E+11 | 0.789776E+10 | 6946.62 | 0.273579E+11 | 0.134160E+10 | 0.00 | ||||||||||||||
| Minimum of Months | 0.137501E+09 | 36348301.80 | 139.58 | 0.137100E+09 | -0.0 | 0.00 | 0.21 | 0.00 | 1011.07 | 1011.07 | 0.00 | 263.55 | 0.00 | |||||||
| Maximum of Months | 0.448453E+10 | 0.124574E+10 | 744.00 | 0.409107E+10 | 0.407339E+09 | 0.00 | 0.60 | 0.12 | 2810.93 | 2635.89 | 581.85 | 839.86 | 0.00 |
Report: DXReportMonthly
For: SPLIT GS2 COOLING COIL
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.125543E+10 | 0.328068E+09 | 496.97 | 0.125059E+10 | 4840162.31 | 0.00 | 0.39 | 31-JAN-16:10 | 0.00 | 01-JAN-00:10 | 1836.75 | 31-JAN-16:10 | 1836.75 | 31-JAN-16:10 | 190.95 | 08-JAN-19:30 | 503.12 | 31-JAN-16:10 | 0.00 | 01-JAN-00:10 |
| February | 0.164049E+09 | 43311953.26 | 156.32 | 0.163427E+09 | 621549.22 | 0.00 | 0.22 | 01-FEB-15:30 | 0.00 | 01-FEB-02:70 | 1068.15 | 01-FEB-15:30 | 1068.15 | 01-FEB-15:30 | 40.03 | 18-FEB-12:00 | 278.01 | 01-FEB-15:30 | 0.00 | 01-FEB-00:10 |
| March | 0.456534E+09 | 0.121288E+09 | 277.58 | 0.456168E+09 | 366679.60 | 0.00 | 0.31 | 18-MAR-16:05 | 0.00 | 01-MAR-00:10 | 1507.47 | 18-MAR-16:05 | 1507.47 | 18-MAR-16:05 | 33.03 | 18-MAR-10:50 | 403.75 | 18-MAR-16:05 | 0.00 | 01-MAR-00:10 |
| April | 0.236106E+10 | 0.646651E+09 | 690.42 | 0.236105E+10 | 7198.15 | 0.00 | 0.43 | 30-APR-16:02 | 0.00 | 01-APR-00:10 | 2009.89 | 10-APR-16:02 | 2009.89 | 10-APR-16:02 | 1.54 | 17-APR-03:10 | 581.04 | 14-APR-16:02 | 0.00 | 01-APR-00:10 |
| May | 0.286437E+10 | 0.802429E+09 | 742.27 | 0.286437E+10 | -0.0 | 0.00 | 0.46 | 20-MAY-14:00 | 0.00 | 14-MAY-06:01 | 2074.99 | 20-MAY-14:00 | 2074.99 | 20-MAY-14:00 | 0.00 | 07-MAY-17:50 | 622.44 | 20-MAY-14:00 | 0.00 | 01-MAY-00:10 |
| June | 0.398901E+10 | 0.115921E+10 | 720.00 | 0.398225E+10 | 6754314.55 | 0.00 | 0.58 | 16-JUN-17:01 | 0.09 | 21-JUN-06:00 | 2778.89 | 17-JUN-17:02 | 2589.85 | 30-JUN-16:08 | 282.20 | 17-JUN-17:02 | 834.26 | 17-JUN-17:12 | 0.00 | 01-JUN-00:10 |
| July | 0.479609E+10 | 0.133503E+10 | 744.00 | 0.438229E+10 | 0.413800E+09 | 0.00 | 0.57 | 22-JUL-16:10 | 0.11 | 01-JUL-06:00 | 2814.16 | 23-JUL-13:00 | 2733.85 | 22-JUL-16:08 | 566.73 | 13-JUL-19:20 | 826.57 | 23-JUL-13:00 | 0.00 | 01-JUL-00:10 |
| August | 0.484944E+10 | 0.134098E+10 | 744.00 | 0.443885E+10 | 0.410583E+09 | 0.00 | 0.62 | 26-AUG-16:10 | 0.14 | 24-AUG-06:00 | 2995.42 | 13-AUG-16:01 | 2817.78 | 13-AUG-16:02 | 539.56 | 28-AUG-18:00 | 890.68 | 13-AUG-16:01 | 0.00 | 01-AUG-00:10 |
| September | 0.473638E+10 | 0.126993E+10 | 720.00 | 0.431018E+10 | 0.426203E+09 | 0.00 | 0.58 | 28-SEP-15:10 | 0.09 | 22-SEP-06:00 | 2793.55 | 09-SEP-12:50 | 2727.72 | 08-SEP-16:08 | 617.77 | 10-SEP-21:00 | 820.04 | 08-SEP-16:08 | 0.00 | 01-SEP-00:10 |
| October | 0.313016E+10 | 0.829928E+09 | 727.47 | 0.305293E+10 | 77232597.95 | 0.00 | 0.54 | 06-OCT-15:10 | 0.00 | 25-OCT-03:30 | 2633.41 | 10-OCT-15:10 | 2633.41 | 10-OCT-15:10 | 392.18 | 03-OCT-09:20 | 758.64 | 10-OCT-15:10 | 0.00 | 01-OCT-00:10 |
| November | 0.174574E+10 | 0.451903E+09 | 625.42 | 0.168107E+10 | 64666518.09 | 0.00 | 0.43 | 01-NOV-15:10 | 0.00 | 04-NOV-01:40 | 2199.26 | 01-NOV-15:10 | 2188.09 | 01-NOV-15:20 | 307.48 | 11-NOV-22:05 | 585.61 | 01-NOV-15:10 | 0.00 | 01-NOV-00:10 |
| December | 0.919450E+09 | 0.240954E+09 | 429.96 | 0.919335E+09 | 114160.64 | 0.00 | 0.39 | 25-DEC-16:10 | 0.00 | 01-DEC-01:50 | 1938.67 | 25-DEC-16:10 | 1938.67 | 25-DEC-16:10 | 16.84 | 13-DEC-11:00 | 503.51 | 25-DEC-16:10 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.312677E+11 | 0.856968E+10 | 7074.41 | 0.298625E+11 | 0.140519E+10 | 0.00 | ||||||||||||||
| Minimum of Months | 0.164049E+09 | 43311953.26 | 156.32 | 0.163427E+09 | -0.0 | 0.00 | 0.22 | 0.00 | 1068.15 | 1068.15 | 0.00 | 278.01 | 0.00 | |||||||
| Maximum of Months | 0.484944E+10 | 0.134098E+10 | 744.00 | 0.443885E+10 | 0.426203E+09 | 0.00 | 0.62 | 0.14 | 2995.42 | 2817.78 | 617.77 | 890.68 | 0.00 |
Report: DXReportMonthly
For: SPLIT MSW COOLING COIL
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.278140E+10 | 0.727687E+09 | 402.89 | 0.277293E+10 | 8470162.38 | 0.00 | 0.40 | 31-JAN-16:30 | 0.00 | 01-JAN-00:10 | 5164.51 | 31-JAN-16:30 | 5164.51 | 31-JAN-16:30 | 366.68 | 08-JAN-19:30 | 1411.48 | 31-JAN-16:30 | 0.00 | 01-JAN-00:10 |
| February | 0.702680E+09 | 0.184318E+09 | 207.17 | 0.696347E+09 | 6332910.92 | 0.00 | 0.23 | 22-FEB-16:20 | 0.00 | 01-FEB-00:20 | 3155.73 | 22-FEB-16:20 | 3155.73 | 22-FEB-16:20 | 185.64 | 18-FEB-11:40 | 813.14 | 22-FEB-16:20 | 0.00 | 01-FEB-00:10 |
| March | 0.173801E+10 | 0.459309E+09 | 337.97 | 0.173641E+10 | 1596877.96 | 0.00 | 0.38 | 18-MAR-16:30 | 0.00 | 01-MAR-00:10 | 5149.21 | 18-MAR-16:30 | 5149.21 | 18-MAR-16:30 | 80.24 | 18-MAR-10:40 | 1363.94 | 18-MAR-16:30 | 0.00 | 01-MAR-00:10 |
| April | 0.638563E+10 | 0.175036E+10 | 666.24 | 0.638563E+10 | 217.00 | 0.00 | 0.52 | 14-APR-17:25 | 0.00 | 01-APR-00:10 | 6486.51 | 14-APR-17:30 | 6486.51 | 14-APR-17:30 | 0.18 | 17-APR-03:10 | 1883.55 | 14-APR-17:30 | 0.00 | 01-APR-00:10 |
| May | 0.775070E+10 | 0.217529E+10 | 739.99 | 0.775070E+10 | 0.00 | 0.00 | 0.53 | 15-MAY-17:02 | 0.00 | 01-MAY-05:00 | 6557.19 | 15-MAY-17:30 | 6557.19 | 15-MAY-17:30 | 0.00 | 07-MAY-18:00 | 1954.07 | 15-MAY-17:05 | 0.00 | 01-MAY-00:10 |
| June | 0.103719E+11 | 0.303014E+10 | 720.00 | 0.103562E+11 | 15676380.29 | 0.00 | 0.67 | 16-JUN-17:01 | 0.05 | 21-JUN-06:00 | 8064.90 | 30-JUN-17:03 | 8064.90 | 30-JUN-17:03 | 785.10 | 17-JUN-17:02 | 2511.87 | 30-JUN-16:07 | 0.00 | 01-JUN-00:10 |
| July | 0.109753E+11 | 0.309368E+10 | 744.00 | 0.100297E+11 | 0.945596E+09 | 0.00 | 0.61 | 22-JUL-17:50 | 0.06 | 02-JUL-05:05 | 7987.37 | 22-JUL-17:40 | 7987.37 | 22-JUL-17:40 | 1440.98 | 13-JUL-19:00 | 2386.34 | 22-JUL-17:40 | 0.00 | 01-JUL-00:10 |
| August | 0.105806E+11 | 0.297318E+10 | 744.00 | 0.968190E+10 | 0.898690E+09 | 0.00 | 0.65 | 25-AUG-17:00 | 0.05 | 06-AUG-05:40 | 8323.63 | 13-AUG-16:01 | 7848.77 | 13-AUG-16:02 | 1282.91 | 28-AUG-18:00 | 2469.28 | 13-AUG-16:01 | 0.00 | 01-AUG-00:10 |
| September | 0.954894E+10 | 0.260953E+10 | 719.06 | 0.865380E+10 | 0.895140E+09 | 0.00 | 0.57 | 08-SEP-16:10 | 0.00 | 22-SEP-05:30 | 7361.86 | 08-SEP-16:10 | 7361.86 | 08-SEP-16:10 | 1413.93 | 10-SEP-20:00 | 2213.94 | 08-SEP-16:10 | 0.00 | 01-SEP-00:10 |
| October | 0.568249E+10 | 0.153159E+10 | 614.37 | 0.553250E+10 | 0.149984E+09 | 0.00 | 0.53 | 10-OCT-15:30 | 0.00 | 08-OCT-05:50 | 6959.65 | 10-OCT-15:30 | 6959.65 | 10-OCT-15:30 | 907.67 | 03-OCT-09:30 | 1999.68 | 10-OCT-15:30 | 0.00 | 01-OCT-00:10 |
| November | 0.272884E+10 | 0.711483E+09 | 441.06 | 0.264713E+10 | 81710674.06 | 0.00 | 0.44 | 01-NOV-16:10 | 0.00 | 02-NOV-05:03 | 6041.49 | 01-NOV-16:05 | 6041.49 | 01-NOV-16:05 | 799.15 | 13-NOV-16:20 | 1581.43 | 01-NOV-16:05 | 0.00 | 01-NOV-00:10 |
| December | 0.136338E+10 | 0.358532E+09 | 255.01 | 0.136336E+10 | 16310.32 | 0.00 | 0.37 | 25-DEC-16:10 | 0.00 | 01-DEC-00:10 | 5020.92 | 25-DEC-16:20 | 5020.92 | 25-DEC-16:20 | 8.39 | 13-DEC-12:00 | 1305.00 | 25-DEC-16:10 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.706098E+11 | 0.196051E+11 | 6591.76 | 0.676066E+11 | 0.300321E+10 | 0.00 | ||||||||||||||
| Minimum of Months | 0.702680E+09 | 0.184318E+09 | 207.17 | 0.696347E+09 | 0.00 | 0.00 | 0.23 | 0.00 | 3155.73 | 3155.73 | 0.00 | 813.14 | 0.00 | |||||||
| Maximum of Months | 0.109753E+11 | 0.309368E+10 | 744.00 | 0.103562E+11 | 0.945596E+09 | 0.00 | 0.67 | 0.06 | 8323.63 | 8064.90 | 1440.98 | 2511.87 | 0.00 |
Report: DXReportMonthly
For: SPLIT MNW COOLING COIL
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.394261E+09 | 0.106083E+09 | 146.75 | 0.393541E+09 | 719945.81 | 0.00 | 0.19 | 31-JAN-17:04 | 0.00 | 01-JAN-00:10 | 2427.71 | 31-JAN-17:04 | 2427.71 | 31-JAN-17:04 | 200.52 | 08-JAN-19:40 | 678.63 | 31-JAN-17:04 | 0.00 | 01-JAN-00:10 |
| February | 15786714.02 | 4171453.14 | 12.78 | 15617142.39 | 169571.63 | 0.00 | 0.08 | 22-FEB-16:30 | 0.00 | 01-FEB-00:10 | 1074.27 | 22-FEB-16:30 | 1074.27 | 22-FEB-16:30 | 25.19 | 18-FEB-14:30 | 283.30 | 22-FEB-16:30 | 0.00 | 01-FEB-00:10 |
| March | 0.846488E+09 | 0.226122E+09 | 188.72 | 0.846140E+09 | 347509.53 | 0.00 | 0.27 | 18-MAR-17:00 | 0.00 | 01-MAR-00:10 | 3569.11 | 18-MAR-17:00 | 3569.11 | 18-MAR-17:00 | 36.07 | 11-MAR-18:06 | 963.12 | 18-MAR-17:00 | 0.00 | 01-MAR-00:10 |
| April | 0.522428E+10 | 0.144167E+10 | 645.39 | 0.522428E+10 | 191.79 | 0.00 | 0.48 | 14-APR-17:30 | 0.00 | 01-APR-00:10 | 5966.94 | 14-APR-17:40 | 5966.94 | 14-APR-17:40 | 0.15 | 17-APR-03:10 | 1739.81 | 14-APR-17:30 | 0.00 | 01-APR-00:10 |
| May | 0.750844E+10 | 0.210778E+10 | 739.11 | 0.750844E+10 | 0.00 | 0.00 | 0.54 | 31-MAY-18:00 | 0.00 | 01-MAY-03:40 | 6544.48 | 31-MAY-18:00 | 6544.48 | 31-MAY-18:00 | 0.00 | 09-MAY-14:10 | 1940.27 | 31-MAY-18:00 | 0.00 | 01-MAY-00:10 |
| June | 0.105661E+11 | 0.307979E+10 | 720.00 | 0.105510E+11 | 15150134.79 | 0.00 | 0.68 | 15-JUN-18:00 | 0.06 | 21-JUN-05:20 | 8202.27 | 29-JUN-18:00 | 8202.27 | 29-JUN-18:00 | 732.49 | 17-JUN-17:10 | 2539.40 | 28-JUN-17:10 | 0.00 | 01-JUN-00:10 |
| July | 0.109027E+11 | 0.307087E+10 | 744.00 | 0.995619E+10 | 0.946495E+09 | 0.00 | 0.61 | 22-JUL-18:00 | 0.06 | 02-JUL-05:05 | 7898.16 | 16-JUL-18:00 | 7889.25 | 22-JUL-18:00 | 1455.56 | 13-JUL-18:50 | 2358.02 | 22-JUL-18:00 | 0.00 | 01-JUL-00:10 |
| August | 0.995749E+10 | 0.280052E+10 | 744.00 | 0.907129E+10 | 0.886202E+09 | 0.00 | 0.62 | 25-AUG-17:00 | 0.05 | 06-AUG-05:40 | 7570.10 | 13-AUG-16:01 | 7293.89 | 25-AUG-17:00 | 1340.27 | 28-AUG-17:35 | 2298.13 | 25-AUG-17:00 | 0.00 | 01-AUG-00:10 |
| September | 0.835099E+10 | 0.228999E+10 | 719.00 | 0.750631E+10 | 0.844682E+09 | 0.00 | 0.51 | 08-SEP-16:10 | 0.00 | 22-SEP-05:30 | 6661.84 | 08-SEP-17:10 | 6486.46 | 08-SEP-16:17 | 1242.71 | 10-SEP-20:00 | 1968.83 | 08-SEP-17:10 | 0.00 | 01-SEP-00:10 |
| October | 0.359909E+10 | 0.985356E+09 | 512.73 | 0.346576E+10 | 0.133329E+09 | 0.00 | 0.43 | 06-OCT-16:01 | 0.00 | 08-OCT-03:50 | 5302.53 | 06-OCT-16:01 | 5302.53 | 06-OCT-16:01 | 800.50 | 03-OCT-09:20 | 1566.66 | 06-OCT-16:01 | 0.00 | 01-OCT-00:10 |
| November | 0.714419E+09 | 0.188685E+09 | 225.25 | 0.674072E+09 | 40346809.44 | 0.00 | 0.28 | 01-NOV-16:02 | 0.00 | 01-NOV-05:50 | 3751.41 | 01-NOV-16:13 | 3744.44 | 01-NOV-16:17 | 431.23 | 13-NOV-16:20 | 1004.02 | 01-NOV-16:02 | 0.00 | 01-NOV-00:10 |
| December | 66374197.18 | 17852942.03 | 37.67 | 66374197.18 | -0.0 | 0.00 | 0.12 | 25-DEC-16:30 | 0.00 | 01-DEC-00:10 | 1577.11 | 25-DEC-16:30 | 1577.11 | 25-DEC-16:30 | 0.00 | 25-DEC-15:20 | 423.09 | 25-DEC-16:30 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.581464E+11 | 0.163189E+11 | 5435.40 | 0.552790E+11 | 0.286744E+10 | 0.00 | ||||||||||||||
| Minimum of Months | 15786714.02 | 4171453.14 | 12.78 | 15617142.39 | -0.0 | 0.00 | 0.08 | 0.00 | 1074.27 | 1074.27 | 0.00 | 283.30 | 0.00 | |||||||
| Maximum of Months | 0.109027E+11 | 0.307979E+10 | 744.00 | 0.105510E+11 | 0.946495E+09 | 0.00 | 0.68 | 0.06 | 8202.27 | 8202.27 | 1455.56 | 2539.40 | 0.00 |
Report: DXReportMonthly
For: SPLIT MSE COOLING COIL
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.273294E+10 | 0.714830E+09 | 417.58 | 0.272421E+10 | 8721858.87 | 0.00 | 0.37 | 31-JAN-16:10 | 0.00 | 01-JAN-00:10 | 4378.61 | 31-JAN-16:10 | 4378.61 | 31-JAN-16:10 | 362.39 | 08-JAN-19:30 | 1203.08 | 31-JAN-16:10 | 0.00 | 01-JAN-00:10 |
| February | 0.781667E+09 | 0.204702E+09 | 233.25 | 0.770903E+09 | 10763919.35 | 0.00 | 0.21 | 23-FEB-14:00 | 0.00 | 01-FEB-00:10 | 2577.75 | 23-FEB-14:00 | 2577.75 | 23-FEB-14:00 | 275.55 | 18-FEB-11:20 | 665.46 | 23-FEB-14:00 | 0.00 | 01-FEB-00:10 |
| March | 0.178360E+10 | 0.470656E+09 | 358.74 | 0.178197E+10 | 1628129.74 | 0.00 | 0.35 | 18-MAR-15:20 | 0.00 | 01-MAR-00:10 | 4330.51 | 18-MAR-15:10 | 4330.51 | 18-MAR-15:10 | 99.98 | 18-MAR-10:40 | 1151.51 | 18-MAR-15:10 | 0.00 | 01-MAR-00:10 |
| April | 0.647690E+10 | 0.176859E+10 | 673.70 | 0.647690E+10 | 362.62 | 0.00 | 0.48 | 30-APR-15:20 | 0.00 | 01-APR-00:10 | 5615.37 | 10-APR-16:02 | 5615.37 | 10-APR-16:02 | 0.25 | 17-APR-03:10 | 1599.55 | 10-APR-16:02 | 0.00 | 01-APR-00:10 |
| May | 0.788708E+10 | 0.220300E+10 | 740.04 | 0.788708E+10 | -0.0 | 0.00 | 0.54 | 20-MAY-14:00 | 0.00 | 01-MAY-04:00 | 6199.19 | 20-MAY-14:00 | 6199.19 | 20-MAY-14:00 | 0.00 | 31-MAY-12:40 | 1836.11 | 20-MAY-14:00 | 0.00 | 01-MAY-00:10 |
| June | 0.104904E+11 | 0.304841E+10 | 720.00 | 0.104741E+11 | 16209057.94 | 0.00 | 0.64 | 30-JUN-16:10 | 0.06 | 21-JUN-05:15 | 7498.12 | 17-JUN-17:02 | 7354.10 | 30-JUN-16:03 | 791.19 | 17-JUN-17:02 | 2295.03 | 30-JUN-16:03 | 0.00 | 01-JUN-00:10 |
| July | 0.112837E+11 | 0.316295E+10 | 744.00 | 0.103168E+11 | 0.966929E+09 | 0.00 | 0.60 | 22-JUL-16:08 | 0.06 | 02-JUL-05:10 | 7517.35 | 23-JUL-13:00 | 7193.15 | 22-JUL-16:08 | 1432.62 | 13-JUL-19:00 | 2196.60 | 23-JUL-13:00 | 0.00 | 01-JUL-00:10 |
| August | 0.108679E+11 | 0.303584E+10 | 744.00 | 0.994370E+10 | 0.924224E+09 | 0.00 | 0.61 | 25-AUG-16:01 | 0.05 | 06-AUG-05:30 | 7467.93 | 13-AUG-16:01 | 7021.44 | 13-AUG-16:08 | 1297.59 | 28-AUG-18:00 | 2222.52 | 13-AUG-16:01 | 0.00 | 01-AUG-00:10 |
| September | 0.970743E+10 | 0.263930E+10 | 719.11 | 0.879290E+10 | 0.914528E+09 | 0.00 | 0.54 | 08-SEP-16:10 | 0.00 | 22-SEP-05:30 | 6715.25 | 01-SEP-16:00 | 6564.42 | 08-SEP-16:04 | 1425.24 | 10-SEP-20:00 | 1981.08 | 08-SEP-16:04 | 0.00 | 01-SEP-00:10 |
| October | 0.580295E+10 | 0.155796E+10 | 629.52 | 0.564795E+10 | 0.154993E+09 | 0.00 | 0.52 | 06-OCT-15:10 | 0.00 | 08-OCT-05:40 | 6294.66 | 10-OCT-15:10 | 6294.66 | 10-OCT-15:10 | 1025.29 | 03-OCT-09:10 | 1821.12 | 10-OCT-15:10 | 0.00 | 01-OCT-00:10 |
| November | 0.265199E+10 | 0.691491E+09 | 448.96 | 0.257995E+10 | 72045276.32 | 0.00 | 0.39 | 01-NOV-15:10 | 0.00 | 02-NOV-05:03 | 5037.75 | 01-NOV-15:10 | 5016.51 | 01-NOV-15:10 | 690.67 | 14-NOV-12:50 | 1349.37 | 01-NOV-15:10 | 0.00 | 01-NOV-00:10 |
| December | 0.135802E+10 | 0.357056E+09 | 268.74 | 0.135795E+10 | 72031.15 | 0.00 | 0.33 | 25-DEC-14:00 | 0.00 | 01-DEC-00:10 | 4138.33 | 25-DEC-14:00 | 4138.33 | 25-DEC-14:00 | 15.94 | 13-DEC-11:50 | 1089.42 | 25-DEC-14:00 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.718246E+11 | 0.198548E+11 | 6697.65 | 0.687545E+11 | 0.307011E+10 | 0.00 | ||||||||||||||
| Minimum of Months | 0.781667E+09 | 0.204702E+09 | 233.25 | 0.770903E+09 | -0.0 | 0.00 | 0.21 | 0.00 | 2577.75 | 2577.75 | 0.00 | 665.46 | 0.00 | |||||||
| Maximum of Months | 0.112837E+11 | 0.316295E+10 | 744.00 | 0.104741E+11 | 0.966929E+09 | 0.00 | 0.64 | 0.06 | 7517.35 | 7354.10 | 1432.62 | 2295.03 | 0.00 |
Report: DXReportMonthly
For: SPLIT MNE COOLING COIL
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.320437E+09 | 86492904.09 | 140.32 | 0.319946E+09 | 491226.01 | 0.00 | 0.16 | 31-JAN-17:06 | 0.00 | 01-JAN-00:10 | 1797.31 | 31-JAN-17:06 | 1797.31 | 31-JAN-17:06 | 200.40 | 08-JAN-19:40 | 505.42 | 31-JAN-17:06 | 0.00 | 01-JAN-00:10 |
| February | 16208428.92 | 4246643.11 | 18.50 | 15365204.06 | 843224.86 | 0.00 | 0.05 | 18-FEB-16:10 | 0.00 | 01-FEB-00:10 | 650.25 | 18-FEB-16:10 | 639.90 | 18-FEB-16:10 | 47.60 | 18-FEB-13:00 | 170.41 | 18-FEB-16:10 | 0.00 | 01-FEB-00:10 |
| March | 0.861135E+09 | 0.229763E+09 | 200.14 | 0.860777E+09 | 357786.56 | 0.00 | 0.24 | 16-MAR-16:08 | 0.00 | 01-MAR-00:10 | 2848.25 | 16-MAR-16:08 | 2848.25 | 16-MAR-16:08 | 45.07 | 18-MAR-10:40 | 789.53 | 16-MAR-16:08 | 0.00 | 01-MAR-00:10 |
| April | 0.531289E+10 | 0.146130E+10 | 657.95 | 0.531289E+10 | 310.54 | 0.00 | 0.42 | 14-APR-18:00 | 0.00 | 01-APR-00:10 | 4806.30 | 14-APR-18:00 | 4806.30 | 14-APR-18:00 | 0.20 | 17-APR-03:10 | 1406.60 | 14-APR-18:00 | 0.00 | 01-APR-00:10 |
| May | 0.764570E+10 | 0.213613E+10 | 738.31 | 0.764570E+10 | -0.0 | 0.00 | 0.50 | 20-MAY-14:00 | 0.00 | 01-MAY-03:30 | 5623.84 | 20-MAY-14:00 | 5623.84 | 20-MAY-14:00 | 0.00 | 07-MAY-16:00 | 1677.36 | 20-MAY-14:00 | 0.00 | 01-MAY-00:10 |
| June | 0.106852E+11 | 0.309762E+10 | 720.00 | 0.106696E+11 | 15648699.10 | 0.00 | 0.64 | 16-JUN-17:00 | 0.06 | 21-JUN-05:20 | 7359.20 | 17-JUN-17:10 | 7292.28 | 30-JUN-16:03 | 738.49 | 17-JUN-17:10 | 2275.40 | 30-JUN-16:03 | 0.00 | 01-JUN-00:10 |
| July | 0.112112E+11 | 0.314009E+10 | 744.00 | 0.102437E+11 | 0.967525E+09 | 0.00 | 0.57 | 22-JUL-16:10 | 0.06 | 02-JUL-05:05 | 7103.49 | 23-JUL-13:00 | 6805.73 | 22-JUL-16:05 | 1446.00 | 13-JUL-19:00 | 2084.11 | 23-JUL-13:00 | 0.00 | 01-JUL-00:10 |
| August | 0.102459E+11 | 0.286497E+10 | 744.00 | 0.933293E+10 | 0.912961E+09 | 0.00 | 0.58 | 25-AUG-17:00 | 0.05 | 06-AUG-05:40 | 6733.96 | 13-AUG-16:01 | 6341.58 | 13-AUG-16:04 | 1366.13 | 28-AUG-17:35 | 2020.45 | 13-AUG-16:01 | 0.00 | 01-AUG-00:10 |
| September | 0.851125E+10 | 0.232287E+10 | 718.97 | 0.764486E+10 | 0.866390E+09 | 0.00 | 0.48 | 01-SEP-16:00 | 0.00 | 22-SEP-05:15 | 6069.42 | 01-SEP-16:00 | 5696.81 | 08-SEP-16:10 | 1256.29 | 10-SEP-20:00 | 1749.33 | 01-SEP-16:00 | 0.00 | 01-SEP-00:10 |
| October | 0.367847E+10 | 0.100348E+10 | 523.94 | 0.353945E+10 | 0.139024E+09 | 0.00 | 0.40 | 02-OCT-14:00 | 0.00 | 08-OCT-03:30 | 4974.64 | 03-OCT-18:00 | 4723.96 | 01-OCT-14:10 | 946.88 | 03-OCT-09:10 | 1434.06 | 02-OCT-14:00 | 0.00 | 01-OCT-00:10 |
| November | 0.615646E+09 | 0.163097E+09 | 220.06 | 0.586950E+09 | 28695886.41 | 0.00 | 0.22 | 01-NOV-16:02 | 0.00 | 01-NOV-05:40 | 2728.55 | 01-NOV-16:02 | 2723.88 | 01-NOV-16:07 | 313.98 | 12-NOV-13:00 | 738.13 | 01-NOV-16:02 | 0.00 | 01-NOV-00:10 |
| December | 46889447.56 | 12660231.93 | 38.67 | 46889447.56 | -0.0 | 0.00 | 0.08 | 25-DEC-16:10 | 0.00 | 01-DEC-00:10 | 914.34 | 25-DEC-16:10 | 914.34 | 25-DEC-16:10 | 0.00 | 25-DEC-16:10 | 249.35 | 25-DEC-16:10 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.591510E+11 | 0.165227E+11 | 5464.84 | 0.562191E+11 | 0.293194E+10 | 0.00 | ||||||||||||||
| Minimum of Months | 16208428.92 | 4246643.11 | 18.50 | 15365204.06 | -0.0 | 0.00 | 0.05 | 0.00 | 650.25 | 639.90 | 0.00 | 170.41 | 0.00 | |||||||
| Maximum of Months | 0.112112E+11 | 0.314009E+10 | 744.00 | 0.106696E+11 | 0.967525E+09 | 0.00 | 0.64 | 0.06 | 7359.20 | 7292.28 | 1446.00 | 2275.40 | 0.00 |
Report: DXReportMonthly
For: SPLIT MN1 COOLING COIL
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.385182E+09 | 0.103450E+09 | 203.99 | 0.382286E+09 | 2895586.33 | 0.00 | 0.17 | 31-JAN-17:04 | 0.00 | 01-JAN-00:10 | 1683.83 | 31-JAN-17:04 | 1683.83 | 31-JAN-17:04 | 272.30 | 08-JAN-19:30 | 472.71 | 31-JAN-17:04 | 0.00 | 01-JAN-00:10 |
| February | 39582263.22 | 10342605.72 | 46.45 | 36899332.33 | 2682930.89 | 0.00 | 0.07 | 18-FEB-16:10 | 0.00 | 01-FEB-00:10 | 749.75 | 18-FEB-16:10 | 736.18 | 18-FEB-16:10 | 110.23 | 18-FEB-20:00 | 195.94 | 18-FEB-16:10 | 0.00 | 01-FEB-00:10 |
| March | 0.810668E+09 | 0.216074E+09 | 253.43 | 0.810101E+09 | 566560.06 | 0.00 | 0.23 | 16-MAR-16:18 | 0.00 | 01-MAR-00:10 | 2452.65 | 20-MAR-17:05 | 2452.65 | 20-MAR-17:05 | 31.91 | 11-MAR-18:08 | 676.62 | 20-MAR-17:00 | 0.00 | 01-MAR-00:10 |
| April | 0.418071E+10 | 0.115339E+10 | 684.00 | 0.418071E+10 | 4897.60 | 0.00 | 0.38 | 14-APR-18:00 | 0.00 | 01-APR-00:10 | 3856.53 | 14-APR-18:00 | 3856.53 | 14-APR-18:00 | 1.39 | 17-APR-03:10 | 1134.36 | 14-APR-18:00 | 0.00 | 01-APR-00:10 |
| May | 0.598956E+10 | 0.167990E+10 | 743.17 | 0.598956E+10 | 0.00 | 0.00 | 0.46 | 31-MAY-18:00 | 0.00 | 14-MAY-06:01 | 4437.02 | 31-MAY-18:00 | 4437.02 | 31-MAY-18:00 | 0.00 | 10-MAY-14:50 | 1333.28 | 31-MAY-18:00 | 0.00 | 01-MAY-00:10 |
| June | 0.825368E+10 | 0.240662E+10 | 720.00 | 0.824049E+10 | 13191610.19 | 0.00 | 0.58 | 15-JUN-18:00 | 0.08 | 21-JUN-05:15 | 5635.94 | 17-JUN-17:12 | 5555.18 | 29-JUN-18:00 | 564.27 | 17-JUN-17:10 | 1754.91 | 28-JUN-17:03 | 0.00 | 01-JUN-00:10 |
| July | 0.886717E+10 | 0.249068E+10 | 744.00 | 0.804535E+10 | 0.821821E+09 | 0.00 | 0.51 | 05-JUL-18:00 | 0.08 | 02-JUL-05:10 | 5383.53 | 16-JUL-18:00 | 5292.64 | 22-JUL-18:00 | 1178.83 | 13-JUL-19:00 | 1607.47 | 22-JUL-18:00 | 0.00 | 01-JUL-00:10 |
| August | 0.816105E+10 | 0.228563E+10 | 744.00 | 0.737717E+10 | 0.783878E+09 | 0.00 | 0.52 | 25-AUG-17:00 | 0.08 | 05-AUG-18:00 | 5154.02 | 13-AUG-16:01 | 4883.37 | 25-AUG-17:00 | 1177.61 | 28-AUG-18:00 | 1564.22 | 25-AUG-17:00 | 0.00 | 01-AUG-00:10 |
| September | 0.699797E+10 | 0.190984E+10 | 720.00 | 0.624711E+10 | 0.750864E+09 | 0.00 | 0.43 | 08-SEP-16:01 | 0.01 | 22-SEP-06:00 | 4682.34 | 01-SEP-16:10 | 4426.50 | 08-SEP-16:04 | 1095.68 | 10-SEP-21:00 | 1359.96 | 08-SEP-16:04 | 0.00 | 01-SEP-00:10 |
| October | 0.313497E+10 | 0.854501E+09 | 571.19 | 0.301205E+10 | 0.122915E+09 | 0.00 | 0.37 | 03-OCT-17:50 | 0.00 | 08-OCT-08:70 | 4058.65 | 03-OCT-18:00 | 3750.23 | 04-OCT-17:00 | 706.55 | 03-OCT-09:20 | 1161.89 | 03-OCT-17:20 | 0.00 | 01-OCT-00:10 |
| November | 0.734135E+09 | 0.192673E+09 | 294.06 | 0.675226E+09 | 58909127.79 | 0.00 | 0.22 | 01-NOV-16:02 | 0.00 | 02-NOV-05:03 | 2374.62 | 01-NOV-16:02 | 2360.24 | 01-NOV-16:08 | 438.89 | 11-NOV-22:05 | 642.20 | 01-NOV-16:02 | 0.00 | 01-NOV-00:10 |
| December | 68874659.25 | 18531487.60 | 52.72 | 68874659.25 | 0.00 | 0.00 | 0.09 | 25-DEC-16:10 | 0.00 | 01-DEC-00:10 | 966.35 | 25-DEC-16:10 | 966.35 | 25-DEC-16:10 | 0.00 | 25-DEC-16:10 | 262.88 | 25-DEC-16:10 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.476236E+11 | 0.133216E+11 | 5777.00 | 0.450658E+11 | 0.255773E+10 | 0.00 | ||||||||||||||
| Minimum of Months | 39582263.22 | 10342605.72 | 46.45 | 36899332.33 | 0.00 | 0.00 | 0.07 | 0.00 | 749.75 | 736.18 | 0.00 | 195.94 | 0.00 | |||||||
| Maximum of Months | 0.886717E+10 | 0.249068E+10 | 744.00 | 0.824049E+10 | 0.821821E+09 | 0.00 | 0.58 | 0.08 | 5635.94 | 5555.18 | 1178.83 | 1754.91 | 0.00 |
Report: DXReportMonthly
For: SPLIT MN2 COOLING COIL
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.387434E+09 | 0.104055E+09 | 203.42 | 0.384591E+09 | 2843146.08 | 0.00 | 0.17 | 31-JAN-17:04 | 0.00 | 01-JAN-00:10 | 1684.89 | 31-JAN-17:04 | 1684.89 | 31-JAN-17:04 | 270.79 | 08-JAN-19:30 | 472.98 | 31-JAN-17:04 | 0.00 | 01-JAN-00:10 |
| February | 43223695.87 | 11294201.04 | 48.13 | 40333214.47 | 2890481.41 | 0.00 | 0.07 | 18-FEB-16:10 | 0.00 | 01-FEB-00:10 | 785.07 | 18-FEB-18:40 | 756.27 | 18-FEB-16:10 | 117.34 | 18-FEB-18:40 | 201.22 | 18-FEB-18:40 | 0.00 | 01-FEB-00:10 |
| March | 0.817879E+09 | 0.217970E+09 | 257.32 | 0.817296E+09 | 583273.73 | 0.00 | 0.23 | 16-MAR-16:05 | 0.00 | 01-MAR-00:10 | 2452.48 | 20-MAR-17:05 | 2452.48 | 20-MAR-17:05 | 31.79 | 18-MAR-10:40 | 677.00 | 16-MAR-16:05 | 0.00 | 01-MAR-00:10 |
| April | 0.418793E+10 | 0.115530E+10 | 683.23 | 0.418793E+10 | 4895.45 | 0.00 | 0.38 | 14-APR-18:00 | 0.00 | 01-APR-00:10 | 3839.64 | 14-APR-18:00 | 3839.64 | 14-APR-18:00 | 1.39 | 17-APR-03:10 | 1129.58 | 14-APR-18:00 | 0.00 | 01-APR-00:10 |
| May | 0.599609E+10 | 0.168160E+10 | 743.17 | 0.599609E+10 | -0.0 | 0.00 | 0.46 | 31-MAY-18:00 | 0.00 | 14-MAY-06:01 | 4422.76 | 31-MAY-18:00 | 4422.76 | 31-MAY-18:00 | 0.00 | 09-MAY-11:10 | 1329.16 | 31-MAY-18:00 | 0.00 | 01-MAY-00:10 |
| June | 0.825885E+10 | 0.240793E+10 | 720.00 | 0.824565E+10 | 13203454.24 | 0.00 | 0.58 | 16-JUN-17:03 | 0.08 | 21-JUN-05:15 | 5643.91 | 17-JUN-17:12 | 5539.62 | 29-JUN-18:00 | 564.66 | 17-JUN-17:10 | 1751.40 | 28-JUN-17:04 | 0.00 | 01-JUN-00:10 |
| July | 0.887814E+10 | 0.249350E+10 | 744.00 | 0.805571E+10 | 0.822427E+09 | 0.00 | 0.51 | 05-JUL-18:00 | 0.08 | 02-JUL-05:10 | 5365.33 | 16-JUL-18:00 | 5277.65 | 22-JUL-18:00 | 1179.79 | 13-JUL-19:00 | 1603.09 | 22-JUL-18:00 | 0.00 | 01-JUL-00:10 |
| August | 0.817193E+10 | 0.228841E+10 | 744.00 | 0.738727E+10 | 0.784658E+09 | 0.00 | 0.52 | 25-AUG-17:00 | 0.08 | 05-AUG-18:00 | 5148.93 | 13-AUG-16:01 | 4873.02 | 25-AUG-17:00 | 1178.92 | 28-AUG-18:00 | 1560.99 | 25-AUG-17:00 | 0.00 | 01-AUG-00:10 |
| September | 0.700428E+10 | 0.191141E+10 | 720.00 | 0.625287E+10 | 0.751418E+09 | 0.00 | 0.43 | 08-SEP-16:01 | 0.01 | 22-SEP-06:00 | 4684.02 | 01-SEP-16:10 | 4420.93 | 08-SEP-16:04 | 1096.93 | 10-SEP-21:00 | 1358.24 | 08-SEP-16:04 | 0.00 | 01-SEP-00:10 |
| October | 0.314374E+10 | 0.856795E+09 | 572.27 | 0.302065E+10 | 0.123089E+09 | 0.00 | 0.37 | 03-OCT-17:50 | 0.00 | 08-OCT-08:70 | 4057.93 | 03-OCT-18:00 | 3745.44 | 04-OCT-17:00 | 709.85 | 03-OCT-09:20 | 1161.25 | 03-OCT-17:20 | 0.00 | 01-OCT-00:10 |
| November | 0.734972E+09 | 0.192927E+09 | 295.41 | 0.676553E+09 | 58419159.31 | 0.00 | 0.22 | 01-NOV-16:02 | 0.00 | 02-NOV-05:03 | 2363.50 | 01-NOV-16:02 | 2349.35 | 01-NOV-16:08 | 438.34 | 11-NOV-22:05 | 639.26 | 01-NOV-16:02 | 0.00 | 01-NOV-00:10 |
| December | 70302132.76 | 18913834.42 | 53.33 | 70302132.76 | -0.0 | 0.00 | 0.09 | 25-DEC-16:10 | 0.00 | 01-DEC-00:10 | 963.06 | 25-DEC-16:10 | 963.06 | 25-DEC-16:10 | 0.00 | 25-DEC-15:30 | 262.00 | 25-DEC-16:10 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.476948E+11 | 0.133401E+11 | 5784.28 | 0.451352E+11 | 0.255954E+10 | 0.00 | ||||||||||||||
| Minimum of Months | 43223695.87 | 11294201.04 | 48.13 | 40333214.47 | -0.0 | 0.00 | 0.07 | 0.00 | 785.07 | 756.27 | 0.00 | 201.22 | 0.00 | |||||||
| Maximum of Months | 0.887814E+10 | 0.249350E+10 | 744.00 | 0.824565E+10 | 0.822427E+09 | 0.00 | 0.58 | 0.08 | 5643.91 | 5539.62 | 1179.79 | 1751.40 | 0.00 |
Report: DXReportMonthly
For: SPLIT MS1 COOLING COIL
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.314274E+10 | 0.818477E+09 | 504.82 | 0.313137E+10 | 11367610.59 | 0.00 | 0.40 | 31-JAN-16:10 | 0.00 | 01-JAN-00:10 | 4237.85 | 31-JAN-16:10 | 4237.85 | 31-JAN-16:10 | 430.97 | 08-JAN-19:30 | 1157.86 | 31-JAN-16:10 | 0.00 | 01-JAN-00:10 |
| February | 0.109791E+10 | 0.286741E+09 | 338.98 | 0.107835E+10 | 19556774.75 | 0.00 | 0.25 | 01-FEB-15:30 | 0.00 | 01-FEB-01:50 | 2741.68 | 01-FEB-15:30 | 2741.68 | 01-FEB-15:30 | 264.80 | 18-FEB-11:30 | 709.87 | 01-FEB-15:30 | 0.00 | 01-FEB-00:10 |
| March | 0.187462E+10 | 0.493971E+09 | 450.56 | 0.187153E+10 | 3087352.78 | 0.00 | 0.36 | 18-MAR-16:10 | 0.00 | 01-MAR-00:50 | 3916.58 | 18-MAR-16:10 | 3916.58 | 18-MAR-16:10 | 83.83 | 18-MAR-10:40 | 1040.76 | 18-MAR-16:10 | 0.00 | 01-MAR-00:10 |
| April | 0.535929E+10 | 0.146719E+10 | 697.89 | 0.535929E+10 | 6339.94 | 0.00 | 0.44 | 10-APR-16:05 | 0.00 | 01-APR-00:20 | 4578.45 | 10-APR-16:03 | 4578.45 | 10-APR-16:03 | 1.77 | 17-APR-03:10 | 1310.68 | 10-APR-16:03 | 0.00 | 01-APR-00:10 |
| May | 0.623323E+10 | 0.174824E+10 | 741.74 | 0.623323E+10 | -0.0 | 0.00 | 0.47 | 20-MAY-14:00 | 0.00 | 14-MAY-06:01 | 4638.12 | 20-MAY-14:00 | 4638.12 | 20-MAY-14:00 | 0.00 | 07-MAY-16:09 | 1390.28 | 20-MAY-14:00 | 0.00 | 01-MAY-00:10 |
| June | 0.805859E+10 | 0.235661E+10 | 720.00 | 0.804482E+10 | 13761469.91 | 0.00 | 0.56 | 16-JUN-16:15 | 0.06 | 21-JUN-06:00 | 5762.77 | 17-JUN-17:02 | 5570.09 | 30-JUN-16:03 | 614.34 | 17-JUN-17:02 | 1761.32 | 30-JUN-16:03 | 0.00 | 01-JUN-00:10 |
| July | 0.893992E+10 | 0.251398E+10 | 744.00 | 0.811852E+10 | 0.821403E+09 | 0.00 | 0.53 | 22-JUL-16:10 | 0.07 | 01-JUL-06:00 | 5594.35 | 23-JUL-13:00 | 5516.41 | 22-JUL-16:05 | 1171.11 | 13-JUL-19:20 | 1671.44 | 22-JUL-16:05 | 0.00 | 01-JUL-00:10 |
| August | 0.878789E+10 | 0.245994E+10 | 744.00 | 0.799028E+10 | 0.797618E+09 | 0.00 | 0.55 | 25-AUG-16:01 | 0.08 | 24-AUG-06:00 | 5881.50 | 13-AUG-16:01 | 5505.55 | 13-AUG-16:04 | 1111.37 | 28-AUG-18:00 | 1766.29 | 13-AUG-16:01 | 0.00 | 01-AUG-00:10 |
| September | 0.820521E+10 | 0.223171E+10 | 720.00 | 0.740202E+10 | 0.803191E+09 | 0.00 | 0.52 | 28-SEP-15:10 | 0.01 | 22-SEP-06:00 | 5297.27 | 08-SEP-16:10 | 5297.27 | 08-SEP-16:10 | 1224.59 | 10-SEP-20:00 | 1609.13 | 08-SEP-16:10 | 0.00 | 01-SEP-00:10 |
| October | 0.534345E+10 | 0.143184E+10 | 670.78 | 0.520270E+10 | 0.140749E+09 | 0.00 | 0.50 | 10-OCT-15:10 | 0.00 | 12-OCT-02:70 | 5336.89 | 10-OCT-15:10 | 5336.89 | 10-OCT-15:10 | 811.72 | 03-OCT-09:30 | 1547.92 | 10-OCT-15:10 | 0.00 | 01-OCT-00:10 |
| November | 0.304844E+10 | 0.791541E+09 | 543.30 | 0.294520E+10 | 0.103237E+09 | 0.00 | 0.42 | 20-NOV-14:30 | 0.00 | 03-NOV-23:40 | 4644.10 | 01-NOV-15:10 | 4621.05 | 01-NOV-15:10 | 683.94 | 14-NOV-12:50 | 1240.17 | 01-NOV-15:10 | 0.00 | 01-NOV-00:10 |
| December | 0.183374E+10 | 0.480574E+09 | 376.33 | 0.183351E+10 | 235103.75 | 0.00 | 0.38 | 25-DEC-14:00 | 0.00 | 01-DEC-00:10 | 4190.00 | 25-DEC-14:00 | 4190.00 | 25-DEC-14:00 | 35.49 | 13-DEC-11:00 | 1094.55 | 25-DEC-14:00 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.619250E+11 | 0.170808E+11 | 7252.40 | 0.592108E+11 | 0.271421E+10 | 0.00 | ||||||||||||||
| Minimum of Months | 0.109791E+10 | 0.286741E+09 | 338.98 | 0.107835E+10 | -0.0 | 0.00 | 0.25 | 0.00 | 2741.68 | 2741.68 | 0.00 | 709.87 | 0.00 | |||||||
| Maximum of Months | 0.893992E+10 | 0.251398E+10 | 744.00 | 0.811852E+10 | 0.821403E+09 | 0.00 | 0.56 | 0.08 | 5881.50 | 5570.09 | 1224.59 | 1766.29 | 0.00 |
Report: DXReportMonthly
For: SPLIT MS2 COOLING COIL
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.314493E+10 | 0.818983E+09 | 504.29 | 0.313356E+10 | 11369121.86 | 0.00 | 0.40 | 31-JAN-16:10 | 0.00 | 01-JAN-00:10 | 4232.60 | 31-JAN-16:10 | 4232.60 | 31-JAN-16:10 | 430.66 | 08-JAN-19:30 | 1156.41 | 31-JAN-16:10 | 0.00 | 01-JAN-00:10 |
| February | 0.111003E+10 | 0.289857E+09 | 340.92 | 0.109008E+10 | 19948964.30 | 0.00 | 0.25 | 01-FEB-15:30 | 0.00 | 01-FEB-01:50 | 2741.65 | 01-FEB-15:30 | 2741.65 | 01-FEB-15:30 | 267.69 | 18-FEB-11:30 | 709.82 | 01-FEB-15:30 | 0.00 | 01-FEB-00:10 |
| March | 0.188630E+10 | 0.496998E+09 | 452.39 | 0.188315E+10 | 3144285.79 | 0.00 | 0.36 | 18-MAR-16:10 | 0.00 | 01-MAR-00:50 | 3910.72 | 18-MAR-16:10 | 3910.72 | 18-MAR-16:10 | 84.33 | 18-MAR-10:40 | 1039.21 | 18-MAR-16:10 | 0.00 | 01-MAR-00:10 |
| April | 0.536536E+10 | 0.146870E+10 | 697.75 | 0.536536E+10 | 6339.35 | 0.00 | 0.44 | 10-APR-16:05 | 0.00 | 01-APR-00:30 | 4578.15 | 10-APR-16:03 | 4578.15 | 10-APR-16:03 | 1.76 | 17-APR-03:10 | 1310.47 | 10-APR-16:03 | 0.00 | 01-APR-00:10 |
| May | 0.623989E+10 | 0.174995E+10 | 741.74 | 0.623989E+10 | 0.00 | 0.00 | 0.47 | 20-MAY-14:00 | 0.00 | 14-MAY-06:01 | 4649.67 | 20-MAY-14:00 | 4649.67 | 20-MAY-14:00 | 0.00 | 07-MAY-14:20 | 1393.36 | 20-MAY-14:00 | 0.00 | 01-MAY-00:10 |
| June | 0.806389E+10 | 0.235797E+10 | 720.00 | 0.805012E+10 | 13774747.87 | 0.00 | 0.56 | 16-JUN-16:15 | 0.06 | 21-JUN-06:00 | 5771.00 | 17-JUN-17:02 | 5564.81 | 30-JUN-16:03 | 614.75 | 17-JUN-17:02 | 1759.58 | 30-JUN-16:03 | 0.00 | 01-JUN-00:10 |
| July | 0.895096E+10 | 0.251680E+10 | 744.00 | 0.812895E+10 | 0.822009E+09 | 0.00 | 0.53 | 22-JUL-16:10 | 0.07 | 01-JUL-06:00 | 5605.46 | 23-JUL-13:00 | 5512.14 | 22-JUL-16:05 | 1172.02 | 13-JUL-19:20 | 1670.06 | 22-JUL-16:05 | 0.00 | 01-JUL-00:10 |
| August | 0.879863E+10 | 0.246264E+10 | 744.00 | 0.800029E+10 | 0.798334E+09 | 0.00 | 0.55 | 25-AUG-16:01 | 0.08 | 24-AUG-06:00 | 5875.98 | 13-AUG-16:01 | 5500.50 | 13-AUG-16:04 | 1112.45 | 28-AUG-18:00 | 1764.56 | 13-AUG-16:01 | 0.00 | 01-AUG-00:10 |
| September | 0.821120E+10 | 0.223311E+10 | 720.00 | 0.740756E+10 | 0.803641E+09 | 0.00 | 0.52 | 28-SEP-15:10 | 0.01 | 22-SEP-06:00 | 5311.61 | 09-SEP-12:50 | 5291.17 | 08-SEP-16:10 | 1225.73 | 10-SEP-20:00 | 1607.24 | 08-SEP-16:10 | 0.00 | 01-SEP-00:10 |
| October | 0.535134E+10 | 0.143379E+10 | 670.94 | 0.521045E+10 | 0.140886E+09 | 0.00 | 0.50 | 10-OCT-15:10 | 0.00 | 12-OCT-02:70 | 5335.80 | 10-OCT-15:10 | 5335.80 | 10-OCT-15:10 | 814.36 | 03-OCT-09:30 | 1547.45 | 10-OCT-15:10 | 0.00 | 01-OCT-00:10 |
| November | 0.304867E+10 | 0.791572E+09 | 543.17 | 0.294586E+10 | 0.102805E+09 | 0.00 | 0.42 | 20-NOV-14:30 | 0.00 | 03-NOV-23:40 | 4637.08 | 01-NOV-15:10 | 4614.11 | 01-NOV-15:10 | 683.92 | 14-NOV-12:50 | 1238.30 | 01-NOV-15:10 | 0.00 | 01-NOV-00:10 |
| December | 0.184203E+10 | 0.482713E+09 | 376.92 | 0.184179E+10 | 239418.49 | 0.00 | 0.38 | 25-DEC-14:00 | 0.00 | 01-DEC-00:10 | 4195.13 | 25-DEC-14:00 | 4195.13 | 25-DEC-14:00 | 36.19 | 13-DEC-11:00 | 1095.72 | 25-DEC-14:00 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.620132E+11 | 0.171031E+11 | 7256.12 | 0.592971E+11 | 0.271616E+10 | 0.00 | ||||||||||||||
| Minimum of Months | 0.111003E+10 | 0.289857E+09 | 340.92 | 0.109008E+10 | 0.00 | 0.00 | 0.25 | 0.00 | 2741.65 | 2741.65 | 0.00 | 709.82 | 0.00 | |||||||
| Maximum of Months | 0.895096E+10 | 0.251680E+10 | 744.00 | 0.812895E+10 | 0.822009E+09 | 0.00 | 0.56 | 0.08 | 5875.98 | 5564.81 | 1225.73 | 1764.56 | 0.00 |
Report: DXReportMonthly
For: SPLIT TSW COOLING COIL
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.122952E+10 | 0.321556E+09 | 279.75 | 0.122845E+10 | 1067407.42 | 0.00 | 0.41 | 31-JAN-16:30 | 0.00 | 01-JAN-00:10 | 3081.30 | 31-JAN-16:30 | 3081.30 | 31-JAN-16:30 | 149.48 | 08-JAN-16:10 | 840.13 | 31-JAN-16:30 | 0.00 | 01-JAN-00:10 |
| February | 0.271925E+09 | 71321544.07 | 119.04 | 0.270959E+09 | 965771.91 | 0.00 | 0.25 | 28-FEB-16:30 | 0.00 | 01-FEB-00:10 | 1853.17 | 28-FEB-16:30 | 1853.17 | 28-FEB-16:30 | 45.26 | 18-FEB-12:10 | 481.82 | 28-FEB-16:30 | 0.00 | 01-FEB-00:10 |
| March | 0.841181E+09 | 0.222380E+09 | 236.00 | 0.840775E+09 | 405376.81 | 0.00 | 0.42 | 18-MAR-16:20 | 0.00 | 01-MAR-00:10 | 3275.88 | 18-MAR-16:20 | 3275.88 | 18-MAR-16:20 | 34.14 | 18-MAR-11:00 | 862.48 | 18-MAR-16:20 | 0.00 | 01-MAR-00:10 |
| April | 0.340086E+10 | 0.935065E+09 | 524.21 | 0.340086E+10 | 0.00 | 0.00 | 0.59 | 14-APR-17:15 | 0.00 | 01-APR-00:10 | 4308.51 | 14-APR-17:30 | 4308.51 | 14-APR-17:30 | 0.00 | 25-APR-16:20 | 1237.24 | 14-APR-17:15 | 0.00 | 01-APR-00:10 |
| May | 0.427009E+10 | 0.120356E+10 | 647.89 | 0.427009E+10 | -0.0 | 0.00 | 0.61 | 15-MAY-17:02 | 0.00 | 01-MAY-01:30 | 4390.52 | 15-MAY-17:15 | 4390.52 | 15-MAY-17:15 | 0.00 | 11-MAY-16:40 | 1292.94 | 15-MAY-17:02 | 0.00 | 01-MAY-00:10 |
| June | 0.611278E+10 | 0.178981E+10 | 717.60 | 0.610409E+10 | 8688540.82 | 0.00 | 0.77 | 16-JUN-16:50 | 0.00 | 13-JUN-05:05 | 5460.65 | 30-JUN-16:06 | 5460.65 | 30-JUN-16:06 | 476.52 | 17-JUN-17:02 | 1671.45 | 30-JUN-16:10 | 0.00 | 01-JUN-00:10 |
| July | 0.639319E+10 | 0.180844E+10 | 741.50 | 0.588611E+10 | 0.507082E+09 | 0.00 | 0.71 | 22-JUL-16:10 | 0.00 | 01-JUL-05:30 | 5346.71 | 22-JUL-16:04 | 5346.71 | 22-JUL-16:04 | 839.06 | 13-JUL-18:50 | 1573.36 | 22-JUL-16:10 | 0.00 | 01-JUL-00:10 |
| August | 0.604571E+10 | 0.170800E+10 | 741.17 | 0.557976E+10 | 0.465945E+09 | 0.00 | 0.75 | 25-AUG-17:00 | 0.00 | 06-AUG-05:05 | 5558.61 | 13-AUG-16:01 | 5283.10 | 13-AUG-16:02 | 698.39 | 09-AUG-19:00 | 1624.77 | 13-AUG-16:01 | 0.00 | 01-AUG-00:10 |
| September | 0.526050E+10 | 0.144681E+10 | 704.47 | 0.480981E+10 | 0.450691E+09 | 0.00 | 0.65 | 08-SEP-16:10 | 0.00 | 15-SEP-05:05 | 4932.87 | 08-SEP-16:01 | 4932.87 | 08-SEP-16:01 | 803.60 | 10-SEP-19:50 | 1462.70 | 08-SEP-16:01 | 0.00 | 01-SEP-00:10 |
| October | 0.278453E+10 | 0.755297E+09 | 457.64 | 0.271267E+10 | 71858638.49 | 0.00 | 0.60 | 06-OCT-15:20 | 0.00 | 05-OCT-05:05 | 4556.56 | 10-OCT-15:30 | 4556.56 | 10-OCT-15:30 | 548.66 | 03-OCT-09:30 | 1294.85 | 10-OCT-15:30 | 0.00 | 01-OCT-00:10 |
| November | 0.112148E+10 | 0.292915E+09 | 259.08 | 0.110345E+10 | 18026765.28 | 0.00 | 0.48 | 01-NOV-16:10 | 0.00 | 01-NOV-00:10 | 3884.29 | 01-NOV-16:02 | 3884.29 | 01-NOV-16:02 | 421.22 | 14-NOV-13:00 | 1010.04 | 01-NOV-15:30 | 0.00 | 01-NOV-00:10 |
| December | 0.645892E+09 | 0.169752E+09 | 196.62 | 0.645892E+09 | 0.00 | 0.00 | 0.39 | 25-DEC-16:20 | 0.00 | 01-DEC-00:10 | 2984.96 | 25-DEC-16:20 | 2984.96 | 25-DEC-16:20 | 0.00 | 22-DEC-16:00 | 773.03 | 25-DEC-16:10 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.383777E+11 | 0.107249E+11 | 5624.98 | 0.368529E+11 | 0.152473E+10 | 0.00 | ||||||||||||||
| Minimum of Months | 0.271925E+09 | 71321544.07 | 119.04 | 0.270959E+09 | -0.0 | 0.00 | 0.25 | 0.00 | 1853.17 | 1853.17 | 0.00 | 481.82 | 0.00 | |||||||
| Maximum of Months | 0.639319E+10 | 0.180844E+10 | 741.50 | 0.610409E+10 | 0.507082E+09 | 0.00 | 0.77 | 0.00 | 5558.61 | 5460.65 | 839.06 | 1671.45 | 0.00 |
Report: DXReportMonthly
For: SPLIT TNW COOLING COIL
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.201590E+09 | 54326923.07 | 110.17 | 0.201584E+09 | 6018.97 | 0.00 | 0.20 | 31-JAN-17:02 | 0.00 | 01-JAN-00:10 | 1481.50 | 31-JAN-17:02 | 1481.50 | 31-JAN-17:02 | 2.15 | 08-JAN-13:00 | 413.47 | 31-JAN-17:02 | 0.00 | 01-JAN-00:10 |
| February | 6433018.14 | 1709683.10 | 10.33 | 6425026.84 | 7991.29 | 0.00 | 0.08 | 22-FEB-16:30 | 0.00 | 01-FEB-00:10 | 578.47 | 22-FEB-16:30 | 578.47 | 22-FEB-16:30 | 2.20 | 18-FEB-15:00 | 152.73 | 22-FEB-16:30 | 0.00 | 01-FEB-00:10 |
| March | 0.436953E+09 | 0.116976E+09 | 156.99 | 0.436894E+09 | 58560.57 | 0.00 | 0.30 | 16-MAR-16:30 | 0.00 | 01-MAR-00:10 | 2247.03 | 16-MAR-16:30 | 2247.03 | 16-MAR-16:30 | 8.83 | 18-MAR-11:10 | 615.61 | 16-MAR-16:14 | 0.00 | 01-MAR-00:10 |
| April | 0.279083E+10 | 0.773879E+09 | 509.38 | 0.279083E+10 | -0.0 | 0.00 | 0.55 | 14-APR-17:30 | 0.00 | 01-APR-00:10 | 3981.57 | 14-APR-17:30 | 3981.57 | 14-APR-17:30 | 0.00 | 25-APR-17:15 | 1149.75 | 14-APR-17:30 | 0.00 | 01-APR-00:10 |
| May | 0.413232E+10 | 0.116611E+10 | 651.33 | 0.413232E+10 | -0.0 | 0.00 | 0.61 | 31-MAY-17:30 | 0.00 | 01-MAY-01:20 | 4315.76 | 15-MAY-17:30 | 4315.76 | 15-MAY-17:30 | 0.00 | 09-MAY-16:08 | 1267.38 | 31-MAY-17:30 | 0.00 | 01-MAY-00:10 |
| June | 0.621410E+10 | 0.181657E+10 | 718.69 | 0.620564E+10 | 8466918.07 | 0.00 | 0.78 | 16-JUN-17:00 | 0.00 | 13-JUN-05:05 | 5431.34 | 29-JUN-17:30 | 5431.34 | 29-JUN-17:30 | 448.99 | 17-JUN-17:02 | 1681.22 | 28-JUN-17:00 | 0.00 | 01-JUN-00:10 |
| July | 0.634775E+10 | 0.179539E+10 | 742.42 | 0.583878E+10 | 0.508964E+09 | 0.00 | 0.69 | 20-JUL-17:30 | 0.00 | 01-JUL-05:50 | 5228.20 | 16-JUL-18:00 | 5191.73 | 20-JUL-17:30 | 848.61 | 13-JUL-18:50 | 1553.66 | 20-JUL-17:30 | 0.00 | 01-JUL-00:10 |
| August | 0.569760E+10 | 0.161284E+10 | 741.58 | 0.523611E+10 | 0.461493E+09 | 0.00 | 0.71 | 25-AUG-17:00 | 0.00 | 06-AUG-05:00 | 5067.36 | 13-AUG-16:01 | 4926.74 | 25-AUG-17:00 | 712.23 | 28-AUG-17:35 | 1528.56 | 25-AUG-17:00 | 0.00 | 01-AUG-00:10 |
| September | 0.460842E+10 | 0.127377E+10 | 703.67 | 0.418053E+10 | 0.427894E+09 | 0.00 | 0.58 | 08-SEP-16:01 | 0.00 | 15-SEP-05:05 | 4426.09 | 08-SEP-17:10 | 4365.06 | 08-SEP-16:17 | 710.77 | 10-SEP-19:50 | 1306.17 | 08-SEP-16:01 | 0.00 | 01-SEP-00:10 |
| October | 0.178424E+10 | 0.493080E+09 | 389.80 | 0.171922E+10 | 65018512.37 | 0.00 | 0.49 | 06-OCT-16:10 | 0.00 | 05-OCT-05:05 | 3521.16 | 06-OCT-16:01 | 3521.16 | 06-OCT-16:01 | 472.15 | 03-OCT-09:40 | 1030.69 | 06-OCT-16:01 | 0.00 | 01-OCT-00:10 |
| November | 0.291830E+09 | 77945559.42 | 122.82 | 0.285642E+09 | 6187393.25 | 0.00 | 0.31 | 01-NOV-16:10 | 0.00 | 01-NOV-00:10 | 2443.50 | 01-NOV-16:20 | 2443.50 | 01-NOV-16:20 | 154.58 | 14-NOV-16:20 | 650.92 | 01-NOV-16:10 | 0.00 | 01-NOV-00:10 |
| December | 53613100.47 | 14409276.84 | 37.67 | 53613100.47 | -0.0 | 0.00 | 0.14 | 22-DEC-16:30 | 0.00 | 01-DEC-00:10 | 1048.10 | 22-DEC-16:30 | 1048.10 | 22-DEC-16:30 | 0.00 | 25-DEC-17:00 | 279.58 | 22-DEC-16:30 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.325657E+11 | 0.919700E+10 | 4894.85 | 0.310876E+11 | 0.147810E+10 | 0.00 | ||||||||||||||
| Minimum of Months | 6433018.14 | 1709683.10 | 10.33 | 6425026.84 | -0.0 | 0.00 | 0.08 | 0.00 | 578.47 | 578.47 | 0.00 | 152.73 | 0.00 | |||||||
| Maximum of Months | 0.634775E+10 | 0.181657E+10 | 742.42 | 0.620564E+10 | 0.508964E+09 | 0.00 | 0.78 | 0.00 | 5431.34 | 5431.34 | 848.61 | 1681.22 | 0.00 |
Report: DXReportMonthly
For: SPLIT TSE COOLING COIL
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.116182E+10 | 0.303897E+09 | 285.00 | 0.116077E+10 | 1048750.60 | 0.00 | 0.38 | 31-JAN-16:10 | 0.00 | 01-JAN-00:10 | 2542.92 | 31-JAN-15:20 | 2542.92 | 31-JAN-15:20 | 90.82 | 08-JAN-16:10 | 696.44 | 31-JAN-16:10 | 0.00 | 01-JAN-00:10 |
| February | 0.272744E+09 | 71488041.65 | 133.62 | 0.270893E+09 | 1851165.74 | 0.00 | 0.21 | 23-FEB-14:00 | 0.00 | 01-FEB-00:10 | 1465.48 | 23-FEB-14:00 | 1465.48 | 23-FEB-14:00 | 101.99 | 18-FEB-11:50 | 378.23 | 23-FEB-14:00 | 0.00 | 01-FEB-00:10 |
| March | 0.824904E+09 | 0.217941E+09 | 247.07 | 0.824502E+09 | 402736.94 | 0.00 | 0.39 | 18-MAR-15:20 | 0.00 | 01-MAR-00:10 | 2749.13 | 18-MAR-15:20 | 2749.13 | 18-MAR-15:20 | 50.65 | 18-MAR-10:40 | 726.33 | 18-MAR-15:20 | 0.00 | 01-MAR-00:10 |
| April | 0.342268E+10 | 0.936847E+09 | 536.70 | 0.342268E+10 | -0.0 | 0.00 | 0.56 | 30-APR-13:10 | 0.00 | 01-APR-00:10 | 3714.41 | 30-APR-15:10 | 3714.41 | 30-APR-15:10 | 0.00 | 12-APR-16:30 | 1060.90 | 30-APR-13:10 | 0.00 | 01-APR-00:10 |
| May | 0.433583E+10 | 0.121493E+10 | 655.11 | 0.433583E+10 | 0.00 | 0.00 | 0.64 | 20-MAY-14:00 | 0.00 | 01-MAY-01:20 | 4176.73 | 20-MAY-14:00 | 4176.73 | 20-MAY-14:00 | 0.00 | 09-MAY-16:50 | 1217.10 | 20-MAY-14:00 | 0.00 | 01-MAY-00:10 |
| June | 0.618053E+10 | 0.179674E+10 | 717.69 | 0.617153E+10 | 8997829.66 | 0.00 | 0.75 | 30-JUN-16:10 | 0.00 | 11-JUN-05:05 | 4921.11 | 30-JUN-16:04 | 4921.11 | 30-JUN-16:04 | 477.69 | 17-JUN-17:02 | 1507.69 | 30-JUN-16:10 | 0.00 | 01-JUN-00:10 |
| July | 0.656461E+10 | 0.184316E+10 | 742.20 | 0.604523E+10 | 0.519385E+09 | 0.00 | 0.69 | 22-JUL-16:10 | 0.00 | 01-JUL-05:40 | 4877.86 | 23-JUL-13:00 | 4765.92 | 22-JUL-16:04 | 817.07 | 13-JUL-18:50 | 1408.57 | 21-JUL-13:10 | 0.00 | 01-JUL-00:10 |
| August | 0.620340E+10 | 0.173892E+10 | 741.84 | 0.572213E+10 | 0.481275E+09 | 0.00 | 0.72 | 25-AUG-16:01 | 0.00 | 06-AUG-05:05 | 4920.38 | 13-AUG-16:01 | 4661.18 | 13-AUG-16:01 | 701.71 | 09-AUG-19:00 | 1442.00 | 13-AUG-16:01 | 0.00 | 01-AUG-00:10 |
| September | 0.534686E+10 | 0.146035E+10 | 705.39 | 0.488348E+10 | 0.463385E+09 | 0.00 | 0.64 | 28-SEP-14:10 | 0.00 | 15-SEP-05:05 | 4522.60 | 09-SEP-12:50 | 4328.01 | 08-SEP-16:01 | 836.66 | 04-SEP-09:00 | 1298.11 | 09-SEP-13:00 | 0.00 | 01-SEP-00:10 |
| October | 0.281609E+10 | 0.760092E+09 | 468.96 | 0.274132E+10 | 74775291.18 | 0.00 | 0.61 | 06-OCT-14:10 | 0.00 | 05-OCT-05:05 | 4259.21 | 02-OCT-13:50 | 4154.02 | 02-OCT-13:50 | 628.46 | 03-OCT-09:20 | 1211.17 | 02-OCT-14:00 | 0.00 | 01-OCT-00:10 |
| November | 0.105937E+10 | 0.276821E+09 | 261.25 | 0.104473E+10 | 14644156.21 | 0.00 | 0.45 | 01-NOV-15:10 | 0.00 | 01-NOV-00:10 | 3248.57 | 01-NOV-14:30 | 3228.47 | 01-NOV-15:10 | 411.94 | 14-NOV-13:00 | 859.79 | 01-NOV-15:10 | 0.00 | 01-NOV-00:10 |
| December | 0.612213E+09 | 0.160915E+09 | 199.33 | 0.612208E+09 | 4253.30 | 0.00 | 0.34 | 25-DEC-14:20 | 0.00 | 01-DEC-00:10 | 2377.57 | 25-DEC-14:20 | 2377.57 | 25-DEC-14:20 | 3.52 | 13-DEC-12:00 | 625.10 | 25-DEC-14:20 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.388010E+11 | 0.107821E+11 | 5694.17 | 0.372353E+11 | 0.156577E+10 | 0.00 | ||||||||||||||
| Minimum of Months | 0.272744E+09 | 71488041.65 | 133.62 | 0.270893E+09 | -0.0 | 0.00 | 0.21 | 0.00 | 1465.48 | 1465.48 | 0.00 | 378.23 | 0.00 | |||||||
| Maximum of Months | 0.656461E+10 | 0.184316E+10 | 742.20 | 0.617153E+10 | 0.519385E+09 | 0.00 | 0.75 | 0.00 | 4921.11 | 4921.11 | 836.66 | 1507.69 | 0.00 |
Report: DXReportMonthly
For: SPLIT TNE COOLING COIL
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.136428E+09 | 37007644.77 | 107.58 | 0.136409E+09 | 18359.92 | 0.00 | 0.15 | 31-JAN-17:02 | 0.00 | 01-JAN-00:10 | 976.06 | 31-JAN-17:02 | 976.06 | 31-JAN-17:02 | 3.88 | 08-JAN-13:00 | 274.73 | 31-JAN-17:02 | 0.00 | 01-JAN-00:10 |
| February | 1767208.85 | 465441.12 | 5.17 | 1722277.70 | 44931.15 | 0.00 | 0.03 | 18-FEB-16:00 | 0.00 | 01-FEB-00:10 | 190.57 | 18-FEB-16:00 | 188.15 | 18-FEB-16:00 | 7.31 | 18-FEB-14:40 | 50.15 | 18-FEB-16:00 | 0.00 | 01-FEB-00:10 |
| March | 0.407533E+09 | 0.109213E+09 | 165.64 | 0.407395E+09 | 138492.88 | 0.00 | 0.26 | 16-MAR-16:10 | 0.00 | 01-MAR-00:10 | 1773.58 | 16-MAR-16:10 | 1773.58 | 16-MAR-16:10 | 20.38 | 18-MAR-10:50 | 489.87 | 16-MAR-16:10 | 0.00 | 01-MAR-00:10 |
| April | 0.280715E+10 | 0.775962E+09 | 525.61 | 0.280715E+10 | 0.00 | 0.00 | 0.48 | 14-APR-16:05 | 0.00 | 01-APR-00:10 | 3122.66 | 30-APR-15:10 | 3122.66 | 30-APR-15:10 | 0.00 | 17-APR-12:00 | 913.25 | 14-APR-16:02 | 0.00 | 01-APR-00:10 |
| May | 0.420190E+10 | 0.117895E+10 | 658.03 | 0.420190E+10 | 0.00 | 0.00 | 0.59 | 20-MAY-14:00 | 0.00 | 01-MAY-01:10 | 3772.25 | 20-MAY-14:00 | 3772.25 | 20-MAY-14:00 | 0.00 | 10-MAY-14:40 | 1109.59 | 20-MAY-14:00 | 0.00 | 01-MAY-00:10 |
| June | 0.628342E+10 | 0.182358E+10 | 719.00 | 0.627467E+10 | 8750297.20 | 0.00 | 0.74 | 30-JUN-16:09 | 0.00 | 13-JUN-05:05 | 4845.40 | 30-JUN-16:10 | 4845.40 | 30-JUN-16:10 | 450.06 | 17-JUN-17:02 | 1486.96 | 30-JUN-16:10 | 0.00 | 01-JUN-00:10 |
| July | 0.651961E+10 | 0.183039E+10 | 743.00 | 0.599871E+10 | 0.520908E+09 | 0.00 | 0.66 | 22-JUL-16:10 | 0.00 | 02-JUL-05:00 | 4608.57 | 23-JUL-13:00 | 4492.49 | 22-JUL-16:10 | 826.65 | 13-JUL-18:50 | 1343.25 | 19-JUL-13:00 | 0.00 | 01-JUL-00:10 |
| August | 0.585610E+10 | 0.164536E+10 | 741.85 | 0.537872E+10 | 0.477380E+09 | 0.00 | 0.67 | 25-AUG-16:30 | 0.00 | 06-AUG-05:00 | 4440.94 | 13-AUG-16:01 | 4212.01 | 13-AUG-16:02 | 719.78 | 28-AUG-17:35 | 1314.79 | 13-AUG-16:01 | 0.00 | 01-AUG-00:10 |
| September | 0.469567E+10 | 0.128979E+10 | 703.39 | 0.425360E+10 | 0.442069E+09 | 0.00 | 0.56 | 08-SEP-16:01 | 0.00 | 15-SEP-05:05 | 3968.59 | 01-SEP-16:00 | 3763.71 | 08-SEP-16:01 | 724.02 | 04-SEP-08:50 | 1133.53 | 08-SEP-16:01 | 0.00 | 01-SEP-00:10 |
| October | 0.179387E+10 | 0.493949E+09 | 401.96 | 0.172566E+10 | 68209851.05 | 0.00 | 0.47 | 02-OCT-14:00 | 0.00 | 05-OCT-05:05 | 3308.53 | 02-OCT-14:00 | 3190.27 | 02-OCT-14:00 | 572.72 | 03-OCT-09:20 | 959.79 | 02-OCT-14:00 | 0.00 | 01-OCT-00:10 |
| November | 0.236284E+09 | 63336405.85 | 120.17 | 0.231881E+09 | 4402625.21 | 0.00 | 0.24 | 01-NOV-15:20 | 0.00 | 01-NOV-00:10 | 1713.84 | 01-NOV-16:03 | 1713.84 | 01-NOV-16:03 | 119.45 | 01-NOV-10:50 | 467.44 | 01-NOV-15:20 | 0.00 | 01-NOV-00:10 |
| December | 33186204.91 | 8977271.75 | 38.50 | 33186204.91 | 0.00 | 0.00 | 0.08 | 25-DEC-16:10 | 0.00 | 01-DEC-00:10 | 541.59 | 25-DEC-16:10 | 541.59 | 25-DEC-16:10 | 0.00 | 25-DEC-15:20 | 147.62 | 25-DEC-16:10 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.329729E+11 | 0.925699E+10 | 4929.89 | 0.314510E+11 | 0.152192E+10 | 0.00 | ||||||||||||||
| Minimum of Months | 1767208.85 | 465441.12 | 5.17 | 1722277.70 | 0.00 | 0.00 | 0.03 | 0.00 | 190.57 | 188.15 | 0.00 | 50.15 | 0.00 | |||||||
| Maximum of Months | 0.651961E+10 | 0.183039E+10 | 743.00 | 0.627467E+10 | 0.520908E+09 | 0.00 | 0.74 | 0.00 | 4845.40 | 4845.40 | 826.65 | 1486.96 | 0.00 |
Report: DXReportMonthly
For: SPLIT TN1 COOLING COIL
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 86365781.78 | 23481982.16 | 87.83 | 86348597.10 | 17184.67 | 0.00 | 0.13 | 31-JAN-17:08 | 0.00 | 01-JAN-00:10 | 782.29 | 31-JAN-17:08 | 782.29 | 31-JAN-17:08 | 3.52 | 08-JAN-13:00 | 220.72 | 31-JAN-17:08 | 0.00 | 01-JAN-00:10 |
| February | 254287.27 | 67139.09 | 1.33 | 250143.54 | 4143.73 | 0.00 | 0.01 | 18-FEB-16:10 | 0.00 | 01-FEB-00:10 | 77.10 | 18-FEB-16:10 | 75.80 | 18-FEB-16:10 | 1.29 | 18-FEB-16:10 | 20.32 | 18-FEB-16:10 | 0.00 | 01-FEB-00:10 |
| March | 0.310017E+09 | 83236303.04 | 149.00 | 0.309947E+09 | 70494.55 | 0.00 | 0.24 | 16-MAR-16:03 | 0.00 | 01-MAR-00:10 | 1480.93 | 16-MAR-16:12 | 1480.93 | 16-MAR-16:12 | 9.69 | 18-MAR-11:10 | 409.86 | 16-MAR-16:03 | 0.00 | 01-MAR-00:10 |
| April | 0.215771E+10 | 0.600025E+09 | 534.71 | 0.215771E+10 | 0.00 | 0.00 | 0.44 | 14-APR-16:13 | 0.00 | 01-APR-00:10 | 2557.42 | 14-APR-17:40 | 2557.42 | 14-APR-17:40 | 0.00 | 14-APR-17:20 | 753.40 | 14-APR-16:13 | 0.00 | 01-APR-00:10 |
| May | 0.328463E+10 | 0.927973E+09 | 675.49 | 0.328463E+10 | 0.00 | 0.00 | 0.51 | 31-MAY-18:00 | 0.00 | 01-MAY-01:40 | 2927.51 | 31-MAY-18:00 | 2927.51 | 31-MAY-18:00 | 0.00 | 09-MAY-17:25 | 871.53 | 31-MAY-18:00 | 0.00 | 01-MAY-00:10 |
| June | 0.494206E+10 | 0.144621E+10 | 720.00 | 0.493478E+10 | 7275832.06 | 0.00 | 0.67 | 16-JUN-17:00 | 0.00 | 21-JUN-05:20 | 3797.31 | 30-JUN-16:10 | 3797.31 | 30-JUN-16:10 | 342.49 | 17-JUN-17:10 | 1191.39 | 28-JUN-17:00 | 0.00 | 01-JUN-00:10 |
| July | 0.523116E+10 | 0.147642E+10 | 743.33 | 0.479020E+10 | 0.440961E+09 | 0.00 | 0.59 | 05-JUL-18:00 | 0.00 | 02-JUL-05:05 | 3608.08 | 16-JUL-18:00 | 3521.82 | 22-JUL-18:00 | 673.10 | 13-JUL-19:00 | 1069.64 | 20-JUL-17:30 | 0.00 | 01-JUL-00:10 |
| August | 0.472119E+10 | 0.133191E+10 | 744.00 | 0.431137E+10 | 0.409823E+09 | 0.00 | 0.61 | 25-AUG-16:40 | 0.01 | 24-AUG-06:00 | 3516.57 | 13-AUG-16:01 | 3353.21 | 25-AUG-16:50 | 641.90 | 28-AUG-17:35 | 1058.99 | 25-AUG-16:50 | 0.00 | 01-AUG-00:10 |
| September | 0.387278E+10 | 0.106623E+10 | 710.58 | 0.349089E+10 | 0.381891E+09 | 0.00 | 0.50 | 08-SEP-16:01 | 0.00 | 15-SEP-05:15 | 3124.74 | 01-SEP-16:10 | 3029.72 | 08-SEP-16:01 | 611.07 | 10-SEP-20:00 | 920.25 | 08-SEP-16:01 | 0.00 | 01-SEP-00:10 |
| October | 0.143242E+10 | 0.395527E+09 | 402.75 | 0.137358E+10 | 58839641.68 | 0.00 | 0.42 | 02-OCT-14:00 | 0.00 | 05-OCT-05:50 | 2589.41 | 02-OCT-14:00 | 2489.96 | 02-OCT-14:00 | 415.02 | 03-OCT-09:40 | 757.89 | 02-OCT-14:00 | 0.00 | 01-OCT-00:10 |
| November | 0.182096E+09 | 48708531.17 | 114.38 | 0.176662E+09 | 5433696.63 | 0.00 | 0.24 | 01-NOV-16:02 | 0.00 | 01-NOV-00:10 | 1486.93 | 01-NOV-16:02 | 1481.94 | 01-NOV-16:07 | 120.24 | 11-NOV-22:10 | 401.21 | 01-NOV-16:02 | 0.00 | 01-NOV-00:10 |
| December | 17803192.37 | 4823572.43 | 28.22 | 17803192.37 | -0.0 | 0.00 | 0.07 | 25-DEC-16:10 | 0.00 | 01-DEC-00:10 | 424.55 | 25-DEC-16:10 | 424.55 | 25-DEC-16:10 | 0.00 | 22-DEC-16:40 | 115.89 | 25-DEC-16:10 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.262385E+11 | 0.740461E+10 | 4911.62 | 0.249342E+11 | 0.130432E+10 | 0.00 | ||||||||||||||
| Minimum of Months | 254287.27 | 67139.09 | 1.33 | 250143.54 | -0.0 | 0.00 | 0.01 | 0.00 | 77.10 | 75.80 | 0.00 | 20.32 | 0.00 | |||||||
| Maximum of Months | 0.523116E+10 | 0.147642E+10 | 744.00 | 0.493478E+10 | 0.440961E+09 | 0.00 | 0.67 | 0.01 | 3797.31 | 3797.31 | 673.10 | 1191.39 | 0.00 |
Report: DXReportMonthly
For: SPLIT TN2 COOLING COIL
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 87858231.45 | 23887611.64 | 89.67 | 87840213.92 | 18017.52 | 0.00 | 0.13 | 31-JAN-17:08 | 0.00 | 01-JAN-00:10 | 776.04 | 31-JAN-17:08 | 776.04 | 31-JAN-17:08 | 3.60 | 08-JAN-13:00 | 218.97 | 31-JAN-17:08 | 0.00 | 01-JAN-00:10 |
| February | 321739.86 | 84896.41 | 1.50 | 316177.37 | 5562.49 | 0.00 | 0.01 | 18-FEB-16:10 | 0.00 | 01-FEB-00:10 | 89.50 | 18-FEB-16:10 | 88.00 | 18-FEB-16:10 | 2.06 | 18-FEB-15:20 | 23.59 | 18-FEB-16:10 | 0.00 | 01-FEB-00:10 |
| March | 0.313267E+09 | 84098236.42 | 151.75 | 0.313193E+09 | 74312.47 | 0.00 | 0.24 | 16-MAR-16:03 | 0.00 | 01-MAR-00:10 | 1476.61 | 16-MAR-16:05 | 1476.61 | 16-MAR-16:05 | 10.22 | 18-MAR-11:00 | 408.94 | 16-MAR-16:05 | 0.00 | 01-MAR-00:10 |
| April | 0.216448E+10 | 0.601797E+09 | 535.17 | 0.216448E+10 | -0.0 | 0.00 | 0.44 | 14-APR-16:17 | 0.00 | 01-APR-00:10 | 2537.47 | 14-APR-17:40 | 2537.47 | 14-APR-17:40 | 0.00 | 04-APR-17:10 | 750.21 | 14-APR-16:17 | 0.00 | 01-APR-00:10 |
| May | 0.329025E+10 | 0.929369E+09 | 675.53 | 0.329025E+10 | 0.00 | 0.00 | 0.51 | 31-MAY-18:00 | 0.00 | 01-MAY-01:40 | 2908.00 | 31-MAY-18:00 | 2908.00 | 31-MAY-18:00 | 0.00 | 10-MAY-16:05 | 866.09 | 31-MAY-17:50 | 0.00 | 01-MAY-00:10 |
| June | 0.494587E+10 | 0.144700E+10 | 720.00 | 0.493858E+10 | 7284641.93 | 0.00 | 0.67 | 16-JUN-17:00 | 0.00 | 21-JUN-05:15 | 3789.02 | 30-JUN-16:10 | 3789.02 | 30-JUN-16:10 | 342.69 | 17-JUN-17:10 | 1186.94 | 28-JUN-17:00 | 0.00 | 01-JUN-00:10 |
| July | 0.523814E+10 | 0.147804E+10 | 743.33 | 0.479684E+10 | 0.441301E+09 | 0.00 | 0.59 | 05-JUL-18:00 | 0.00 | 02-JUL-05:05 | 3587.74 | 16-JUL-18:00 | 3507.62 | 22-JUL-16:01 | 672.97 | 13-JUL-19:00 | 1064.72 | 20-JUL-17:30 | 0.00 | 01-JUL-00:10 |
| August | 0.472809E+10 | 0.133354E+10 | 744.00 | 0.431778E+10 | 0.410315E+09 | 0.00 | 0.61 | 25-AUG-16:40 | 0.01 | 24-AUG-06:00 | 3507.39 | 13-AUG-16:01 | 3340.52 | 25-AUG-16:40 | 643.05 | 28-AUG-17:35 | 1055.02 | 25-AUG-16:40 | 0.00 | 01-AUG-00:10 |
| September | 0.387710E+10 | 0.106722E+10 | 710.50 | 0.349480E+10 | 0.382300E+09 | 0.00 | 0.50 | 08-SEP-16:01 | 0.00 | 15-SEP-05:15 | 3122.29 | 01-SEP-16:10 | 3020.50 | 08-SEP-16:01 | 611.19 | 10-SEP-20:00 | 917.42 | 08-SEP-16:01 | 0.00 | 01-SEP-00:10 |
| October | 0.143743E+10 | 0.396833E+09 | 404.17 | 0.137847E+10 | 58951575.75 | 0.00 | 0.42 | 02-OCT-14:00 | 0.00 | 05-OCT-05:40 | 2595.72 | 02-OCT-14:00 | 2496.39 | 02-OCT-14:00 | 418.50 | 03-OCT-09:40 | 759.47 | 02-OCT-14:00 | 0.00 | 01-OCT-00:10 |
| November | 0.182807E+09 | 48909156.33 | 114.96 | 0.177467E+09 | 5340767.07 | 0.00 | 0.23 | 01-NOV-16:02 | 0.00 | 01-NOV-00:10 | 1472.00 | 01-NOV-16:02 | 1467.61 | 01-NOV-16:10 | 125.37 | 11-NOV-22:10 | 397.27 | 01-NOV-16:02 | 0.00 | 01-NOV-00:10 |
| December | 18288177.93 | 4955705.35 | 29.47 | 18288177.93 | 0.00 | 0.00 | 0.07 | 25-DEC-16:10 | 0.00 | 01-DEC-00:10 | 421.43 | 25-DEC-16:10 | 421.43 | 25-DEC-16:10 | 0.00 | 22-DEC-16:40 | 115.04 | 25-DEC-16:10 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.262839E+11 | 0.741573E+10 | 4920.05 | 0.249783E+11 | 0.130559E+10 | 0.00 | ||||||||||||||
| Minimum of Months | 321739.86 | 84896.41 | 1.50 | 316177.37 | -0.0 | 0.00 | 0.01 | 0.00 | 89.50 | 88.00 | 0.00 | 23.59 | 0.00 | |||||||
| Maximum of Months | 0.523814E+10 | 0.147804E+10 | 744.00 | 0.493858E+10 | 0.441301E+09 | 0.00 | 0.67 | 0.01 | 3789.02 | 3789.02 | 672.97 | 1186.94 | 0.00 |
Report: DXReportMonthly
For: SPLIT TS1 COOLING COIL
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.112835E+10 | 0.294750E+09 | 312.92 | 0.112663E+10 | 1715439.25 | 0.00 | 0.39 | 31-JAN-16:10 | 0.00 | 01-JAN-00:10 | 2335.86 | 31-JAN-16:10 | 2335.86 | 31-JAN-16:10 | 125.41 | 08-JAN-16:10 | 639.71 | 31-JAN-16:10 | 0.00 | 01-JAN-00:10 |
| February | 0.255575E+09 | 67059079.33 | 144.39 | 0.254145E+09 | 1429839.74 | 0.00 | 0.21 | 01-FEB-15:30 | 0.00 | 01-FEB-00:10 | 1311.73 | 01-FEB-15:30 | 1311.73 | 01-FEB-15:30 | 67.26 | 18-FEB-12:00 | 341.82 | 01-FEB-15:30 | 0.00 | 01-FEB-00:10 |
| March | 0.706388E+09 | 0.186803E+09 | 251.83 | 0.705951E+09 | 437568.78 | 0.00 | 0.39 | 18-MAR-15:20 | 0.00 | 01-MAR-00:10 | 2484.15 | 18-MAR-15:20 | 2484.15 | 18-MAR-15:20 | 37.85 | 18-MAR-11:00 | 655.66 | 18-MAR-15:20 | 0.00 | 01-MAR-00:10 |
| April | 0.277777E+10 | 0.764366E+09 | 552.68 | 0.277777E+10 | 0.00 | 0.00 | 0.51 | 14-APR-16:10 | 0.00 | 01-APR-00:10 | 3044.94 | 10-APR-15:20 | 3044.94 | 10-APR-15:20 | 0.00 | 02-APR-16:15 | 881.43 | 14-APR-16:02 | 0.00 | 01-APR-00:10 |
| May | 0.342090E+10 | 0.965314E+09 | 669.75 | 0.342090E+10 | -0.0 | 0.00 | 0.56 | 20-MAY-14:00 | 0.00 | 01-MAY-01:50 | 3217.96 | 20-MAY-14:00 | 3217.96 | 20-MAY-14:00 | 0.00 | 09-MAY-15:00 | 950.66 | 20-MAY-14:00 | 0.00 | 01-MAY-00:10 |
| June | 0.483918E+10 | 0.141907E+10 | 718.97 | 0.483164E+10 | 7538251.71 | 0.00 | 0.67 | 16-JUN-16:15 | 0.00 | 21-JUN-05:05 | 3874.49 | 30-JUN-16:10 | 3874.49 | 30-JUN-16:10 | 369.97 | 17-JUN-17:02 | 1203.72 | 30-JUN-16:10 | 0.00 | 01-JUN-00:10 |
| July | 0.527666E+10 | 0.148970E+10 | 742.51 | 0.483728E+10 | 0.439386E+09 | 0.00 | 0.62 | 22-JUL-16:10 | 0.00 | 01-JUL-05:50 | 3793.83 | 22-JUL-16:01 | 3793.83 | 22-JUL-16:01 | 663.46 | 13-JUL-19:00 | 1131.81 | 22-JUL-16:04 | 0.00 | 01-JUL-00:10 |
| August | 0.507190E+10 | 0.142810E+10 | 744.00 | 0.465746E+10 | 0.414446E+09 | 0.00 | 0.66 | 25-AUG-16:01 | 0.00 | 24-AUG-06:00 | 3999.56 | 13-AUG-16:01 | 3785.12 | 13-AUG-16:02 | 593.63 | 28-AUG-18:00 | 1183.79 | 13-AUG-16:01 | 0.00 | 01-AUG-00:10 |
| September | 0.453133E+10 | 0.124094E+10 | 710.22 | 0.412632E+10 | 0.405009E+09 | 0.00 | 0.61 | 28-SEP-15:10 | 0.00 | 15-SEP-05:15 | 3655.94 | 09-SEP-12:50 | 3631.72 | 28-SEP-14:10 | 697.16 | 10-SEP-20:00 | 1078.98 | 08-SEP-16:04 | 0.00 | 01-SEP-00:10 |
| October | 0.246260E+10 | 0.665557E+09 | 494.96 | 0.239628E+10 | 66318411.06 | 0.00 | 0.57 | 06-OCT-14:20 | 0.00 | 06-OCT-05:05 | 3558.87 | 02-OCT-13:50 | 3506.08 | 10-OCT-15:10 | 489.41 | 03-OCT-09:30 | 1016.26 | 02-OCT-13:50 | 0.00 | 01-OCT-00:10 |
| November | 0.103341E+10 | 0.269509E+09 | 302.31 | 0.101416E+10 | 19248830.84 | 0.00 | 0.46 | 01-NOV-15:10 | 0.00 | 01-NOV-00:10 | 3003.02 | 01-NOV-15:10 | 2993.21 | 01-NOV-15:10 | 416.29 | 14-NOV-12:50 | 795.81 | 01-NOV-15:10 | 0.00 | 01-NOV-00:10 |
| December | 0.618578E+09 | 0.162410E+09 | 221.68 | 0.618575E+09 | 2591.67 | 0.00 | 0.36 | 25-DEC-15:10 | 0.00 | 01-DEC-00:10 | 2278.29 | 25-DEC-15:10 | 2278.29 | 25-DEC-15:10 | 2.34 | 13-DEC-12:10 | 596.92 | 25-DEC-15:10 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.321226E+11 | 0.895358E+10 | 5866.22 | 0.307671E+11 | 0.135553E+10 | 0.00 | ||||||||||||||
| Minimum of Months | 0.255575E+09 | 67059079.33 | 144.39 | 0.254145E+09 | -0.0 | 0.00 | 0.21 | 0.00 | 1311.73 | 1311.73 | 0.00 | 341.82 | 0.00 | |||||||
| Maximum of Months | 0.527666E+10 | 0.148970E+10 | 744.00 | 0.483728E+10 | 0.439386E+09 | 0.00 | 0.67 | 0.00 | 3999.56 | 3874.49 | 697.16 | 1203.72 | 0.00 |
Report: DXReportMonthly
For: SPLIT TS2 COOLING COIL
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.113292E+10 | 0.295877E+09 | 313.08 | 0.113119E+10 | 1725336.29 | 0.00 | 0.39 | 31-JAN-16:10 | 0.00 | 01-JAN-00:10 | 2340.69 | 24-JAN-15:10 | 2340.69 | 24-JAN-15:10 | 124.13 | 08-JAN-16:10 | 638.66 | 31-JAN-16:10 | 0.00 | 01-JAN-00:10 |
| February | 0.261301E+09 | 68539697.39 | 145.75 | 0.259788E+09 | 1513408.61 | 0.00 | 0.21 | 01-FEB-15:30 | 0.00 | 01-FEB-00:10 | 1317.47 | 23-FEB-14:00 | 1317.47 | 23-FEB-14:00 | 71.60 | 18-FEB-12:00 | 342.46 | 01-FEB-15:30 | 0.00 | 01-FEB-00:10 |
| March | 0.712670E+09 | 0.188426E+09 | 253.00 | 0.712232E+09 | 438021.93 | 0.00 | 0.39 | 18-MAR-15:20 | 0.00 | 01-MAR-00:10 | 2485.12 | 18-MAR-15:20 | 2485.12 | 18-MAR-15:20 | 38.49 | 18-MAR-11:00 | 655.77 | 18-MAR-15:20 | 0.00 | 01-MAR-00:10 |
| April | 0.278427E+10 | 0.765948E+09 | 552.09 | 0.278427E+10 | -0.0 | 0.00 | 0.51 | 14-APR-16:10 | 0.00 | 01-APR-00:10 | 3045.50 | 10-APR-15:20 | 3045.50 | 10-APR-15:20 | 0.00 | 14-APR-16:17 | 878.57 | 14-APR-16:02 | 0.00 | 01-APR-00:10 |
| May | 0.342683E+10 | 0.966757E+09 | 669.81 | 0.342683E+10 | 0.00 | 0.00 | 0.56 | 20-MAY-14:00 | 0.00 | 01-MAY-01:50 | 3227.72 | 20-MAY-14:00 | 3227.72 | 20-MAY-14:00 | 0.00 | 07-MAY-12:10 | 953.03 | 20-MAY-14:00 | 0.00 | 01-MAY-00:10 |
| June | 0.484315E+10 | 0.141990E+10 | 718.97 | 0.483560E+10 | 7548010.06 | 0.00 | 0.67 | 16-JUN-16:15 | 0.00 | 21-JUN-05:05 | 3866.08 | 30-JUN-16:10 | 3866.08 | 30-JUN-16:10 | 370.16 | 17-JUN-17:02 | 1200.96 | 30-JUN-16:10 | 0.00 | 01-JUN-00:10 |
| July | 0.528373E+10 | 0.149134E+10 | 742.51 | 0.484400E+10 | 0.439731E+09 | 0.00 | 0.62 | 22-JUL-16:10 | 0.00 | 01-JUL-05:50 | 3785.15 | 22-JUL-16:01 | 3785.15 | 22-JUL-16:01 | 663.29 | 13-JUL-19:00 | 1129.11 | 22-JUL-16:04 | 0.00 | 01-JUL-00:10 |
| August | 0.507876E+10 | 0.142965E+10 | 744.00 | 0.466386E+10 | 0.414902E+09 | 0.00 | 0.66 | 25-AUG-16:01 | 0.00 | 24-AUG-06:00 | 3989.53 | 13-AUG-16:01 | 3775.64 | 13-AUG-16:05 | 594.33 | 28-AUG-18:00 | 1180.72 | 13-AUG-16:01 | 0.00 | 01-AUG-00:10 |
| September | 0.453544E+10 | 0.124176E+10 | 710.22 | 0.413010E+10 | 0.405337E+09 | 0.00 | 0.61 | 28-SEP-15:10 | 0.00 | 15-SEP-05:15 | 3670.42 | 09-SEP-12:50 | 3636.96 | 28-SEP-14:10 | 697.36 | 10-SEP-20:00 | 1079.95 | 28-SEP-14:10 | 0.00 | 01-SEP-00:10 |
| October | 0.246892E+10 | 0.667071E+09 | 494.91 | 0.240251E+10 | 66418337.76 | 0.00 | 0.57 | 06-OCT-14:20 | 0.00 | 06-OCT-05:05 | 3565.88 | 02-OCT-13:50 | 3503.20 | 10-OCT-15:10 | 492.43 | 03-OCT-09:30 | 1017.80 | 02-OCT-13:50 | 0.00 | 01-OCT-00:10 |
| November | 0.103606E+10 | 0.270167E+09 | 302.25 | 0.101710E+10 | 18954400.04 | 0.00 | 0.46 | 01-NOV-15:10 | 0.00 | 01-NOV-00:10 | 2995.16 | 01-NOV-15:10 | 2985.41 | 01-NOV-15:10 | 415.91 | 14-NOV-13:00 | 793.68 | 01-NOV-15:10 | 0.00 | 01-NOV-00:10 |
| December | 0.623363E+09 | 0.163637E+09 | 222.48 | 0.623360E+09 | 3025.66 | 0.00 | 0.36 | 25-DEC-15:10 | 0.00 | 01-DEC-00:10 | 2276.01 | 25-DEC-15:10 | 2276.01 | 25-DEC-15:10 | 3.14 | 13-DEC-12:10 | 596.24 | 25-DEC-15:10 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.321874E+11 | 0.896909E+10 | 5869.07 | 0.308308E+11 | 0.135657E+10 | 0.00 | ||||||||||||||
| Minimum of Months | 0.261301E+09 | 68539697.39 | 145.75 | 0.259788E+09 | -0.0 | 0.00 | 0.21 | 0.00 | 1317.47 | 1317.47 | 0.00 | 342.46 | 0.00 | |||||||
| Maximum of Months | 0.528373E+10 | 0.149134E+10 | 744.00 | 0.484400E+10 | 0.439731E+09 | 0.00 | 0.67 | 0.00 | 3989.53 | 3866.08 | 697.36 | 1200.96 | 0.00 |
Report: WindowReportMonthly
For: GWINDOW1 S SWA
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 251.85 | 200.83 | 51.02 | 390.50 | 141.62 | 0.00 | 0.00 | 0.00 |
| February | 162.34 | 110.19 | 52.16 | 227.86 | 130.62 | 0.00 | 0.00 | 0.00 |
| March | 127.64 | 63.01 | 64.63 | 195.18 | 117.77 | 0.00 | 0.00 | 0.00 |
| April | 117.92 | 50.30 | 67.62 | 230.46 | 67.12 | 0.00 | 0.00 | 0.00 |
| May | 76.16 | 12.70 | 63.46 | 167.61 | 44.64 | 0.00 | 0.00 | 0.00 |
| June | 65.43 | 5.35 | 60.08 | 196.92 | 15.55 | 0.00 | 0.00 | 0.00 |
| July | 66.44 | 6.80 | 59.64 | 191.84 | 11.36 | 0.00 | 0.00 | 0.00 |
| August | 81.43 | 22.89 | 58.54 | 217.57 | 15.53 | 0.00 | 0.00 | 0.00 |
| September | 116.80 | 49.96 | 66.84 | 257.94 | 24.56 | 0.00 | 0.00 | 0.00 |
| October | 185.76 | 128.59 | 57.17 | 318.27 | 88.48 | 0.00 | 0.00 | 0.00 |
| November | 218.92 | 168.25 | 50.67 | 331.81 | 133.58 | 0.00 | 0.00 | 0.00 |
| December | 235.20 | 186.13 | 49.07 | 345.41 | 172.21 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 142.13 | 83.70 | 58.43 | 256.20 | 80.06 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 65.43 | 5.35 | 49.07 | 167.61 | 11.36 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 251.85 | 200.83 | 67.62 | 390.50 | 172.21 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: GWINDOW1 W SWA
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 68.82 | 42.91 | 25.91 | 98.15 | 101.79 | 0.00 | 0.00 | 0.00 |
| February | 55.31 | 26.70 | 28.61 | 64.48 | 92.12 | 0.00 | 0.00 | 0.00 |
| March | 73.78 | 35.35 | 38.42 | 102.73 | 77.80 | 0.00 | 0.00 | 0.00 |
| April | 112.55 | 64.15 | 48.40 | 198.45 | 43.73 | 0.00 | 0.00 | 0.00 |
| May | 113.04 | 63.28 | 49.77 | 214.93 | 29.26 | 0.00 | 0.00 | 0.00 |
| June | 120.14 | 70.73 | 49.41 | 263.50 | 10.53 | 0.00 | 0.00 | 0.00 |
| July | 87.38 | 40.79 | 46.59 | 200.04 | 7.71 | 0.00 | 0.00 | 0.00 |
| August | 83.49 | 41.95 | 41.54 | 187.11 | 10.53 | 0.00 | 0.00 | 0.00 |
| September | 72.72 | 30.59 | 42.13 | 153.29 | 16.58 | 0.00 | 0.00 | 0.00 |
| October | 74.29 | 42.46 | 31.84 | 122.40 | 62.22 | 0.00 | 0.00 | 0.00 |
| November | 68.18 | 41.06 | 27.12 | 94.06 | 95.93 | 0.00 | 0.00 | 0.00 |
| December | 55.13 | 31.37 | 23.76 | 68.42 | 124.94 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 82.17 | 44.34 | 37.82 | 147.65 | 55.96 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 55.13 | 26.70 | 23.76 | 64.48 | 7.71 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 120.14 | 70.73 | 49.77 | 263.50 | 124.94 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: GWINDOW1 W NWA
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 68.82 | 42.91 | 25.91 | 103.55 | 91.46 | 0.00 | 0.00 | 0.00 |
| February | 55.31 | 26.70 | 28.61 | 69.28 | 82.81 | 0.00 | 0.00 | 0.00 |
| March | 73.78 | 35.35 | 38.42 | 106.83 | 72.98 | 0.00 | 0.00 | 0.00 |
| April | 112.55 | 64.15 | 48.40 | 200.10 | 42.60 | 0.00 | 0.00 | 0.00 |
| May | 113.04 | 63.28 | 49.77 | 215.26 | 29.18 | 0.00 | 0.00 | 0.00 |
| June | 120.14 | 70.73 | 49.41 | 263.20 | 10.63 | 0.00 | 0.00 | 0.00 |
| July | 87.38 | 40.79 | 46.59 | 200.09 | 7.73 | 0.00 | 0.00 | 0.00 |
| August | 83.49 | 41.95 | 41.54 | 187.88 | 10.36 | 0.00 | 0.00 | 0.00 |
| September | 72.72 | 30.59 | 42.13 | 154.66 | 16.10 | 0.00 | 0.00 | 0.00 |
| October | 74.29 | 42.46 | 31.84 | 124.77 | 59.96 | 0.00 | 0.00 | 0.00 |
| November | 68.18 | 41.06 | 27.12 | 97.12 | 90.29 | 0.00 | 0.00 | 0.00 |
| December | 55.13 | 31.37 | 23.76 | 73.26 | 113.45 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 82.17 | 44.34 | 37.82 | 150.01 | 52.18 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 55.13 | 26.70 | 23.76 | 69.28 | 7.73 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 120.14 | 70.73 | 49.77 | 263.20 | 113.45 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: GWINDOW1 N NWA
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 30.77 | 0.00 | 30.77 | 24.88 | 141.06 | 0.00 | 0.00 | 0.00 |
| February | 35.06 | 0.00 | 35.06 | 20.52 | 128.80 | 0.00 | 0.00 | 0.00 |
| March | 46.60 | 0.01 | 46.60 | 49.70 | 113.79 | 0.00 | 0.00 | 0.00 |
| April | 56.95 | 0.75 | 56.19 | 99.54 | 63.69 | 0.00 | 0.00 | 0.00 |
| May | 67.07 | 5.81 | 61.26 | 138.02 | 40.14 | 0.00 | 0.00 | 0.00 |
| June | 76.92 | 13.77 | 63.16 | 216.04 | 14.47 | 0.00 | 0.00 | 0.00 |
| July | 65.65 | 6.66 | 58.99 | 185.98 | 10.93 | 0.00 | 0.00 | 0.00 |
| August | 53.32 | 1.43 | 51.89 | 152.31 | 15.19 | 0.00 | 0.00 | 0.00 |
| September | 50.18 | 0.03 | 50.15 | 125.33 | 24.54 | 0.00 | 0.00 | 0.00 |
| October | 38.80 | 0.00 | 38.80 | 57.22 | 92.89 | 0.00 | 0.00 | 0.00 |
| November | 32.33 | 0.00 | 32.33 | 21.92 | 140.12 | 0.00 | 0.00 | 0.00 |
| December | 28.74 | 0.00 | 28.74 | 13.57 | 176.14 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 48.58 | 2.38 | 46.20 | 92.42 | 79.96 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 28.74 | 0.00 | 28.74 | 13.57 | 10.93 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 76.92 | 13.77 | 63.16 | 216.04 | 176.14 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: GWINDOW1 S SEA
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 251.85 | 200.83 | 51.02 | 385.53 | 152.14 | 0.00 | 0.00 | 0.00 |
| February | 162.34 | 110.19 | 52.16 | 223.90 | 140.98 | 0.00 | 0.00 | 0.00 |
| March | 127.64 | 63.01 | 64.63 | 189.07 | 128.79 | 0.00 | 0.00 | 0.00 |
| April | 117.92 | 50.30 | 67.62 | 216.83 | 87.48 | 0.00 | 0.00 | 0.00 |
| May | 76.16 | 12.70 | 63.46 | 150.15 | 66.57 | 0.00 | 0.00 | 0.00 |
| June | 65.43 | 5.35 | 60.08 | 167.79 | 33.64 | 0.00 | 0.00 | 0.00 |
| July | 66.44 | 6.80 | 59.64 | 159.45 | 29.88 | 0.00 | 0.00 | 0.00 |
| August | 81.43 | 22.89 | 58.54 | 192.61 | 38.18 | 0.00 | 0.00 | 0.00 |
| September | 116.80 | 49.96 | 66.84 | 235.48 | 51.30 | 0.00 | 0.00 | 0.00 |
| October | 185.76 | 128.59 | 57.17 | 304.58 | 112.61 | 0.00 | 0.00 | 0.00 |
| November | 218.92 | 168.25 | 50.67 | 325.95 | 148.59 | 0.00 | 0.00 | 0.00 |
| December | 235.20 | 186.13 | 49.07 | 340.69 | 182.39 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 142.13 | 83.70 | 58.43 | 241.19 | 97.55 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 65.43 | 5.35 | 49.07 | 150.15 | 29.88 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 251.85 | 200.83 | 67.62 | 385.53 | 182.39 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: GWINDOW1 E SEA
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 65.69 | 41.32 | 24.37 | 79.42 | 101.13 | 0.00 | 0.00 | 0.00 |
| February | 64.54 | 36.92 | 27.62 | 72.28 | 94.23 | 0.00 | 0.00 | 0.00 |
| March | 80.48 | 41.29 | 39.20 | 105.24 | 80.44 | 0.00 | 0.00 | 0.00 |
| April | 115.25 | 68.75 | 46.50 | 188.11 | 51.96 | 0.00 | 0.00 | 0.00 |
| May | 119.43 | 70.83 | 48.60 | 208.09 | 38.64 | 0.00 | 0.00 | 0.00 |
| June | 124.45 | 77.35 | 47.09 | 248.33 | 19.51 | 0.00 | 0.00 | 0.00 |
| July | 105.26 | 59.44 | 45.81 | 208.13 | 17.84 | 0.00 | 0.00 | 0.00 |
| August | 99.77 | 56.95 | 42.82 | 197.05 | 23.40 | 0.00 | 0.00 | 0.00 |
| September | 81.80 | 39.42 | 42.38 | 151.52 | 31.60 | 0.00 | 0.00 | 0.00 |
| October | 82.08 | 49.92 | 32.16 | 121.47 | 73.27 | 0.00 | 0.00 | 0.00 |
| November | 63.22 | 37.94 | 25.28 | 74.01 | 99.73 | 0.00 | 0.00 | 0.00 |
| December | 57.56 | 34.75 | 22.82 | 59.18 | 123.15 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 88.40 | 51.31 | 37.10 | 143.07 | 62.78 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 57.56 | 34.75 | 22.82 | 59.18 | 17.84 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 124.45 | 77.35 | 48.60 | 248.33 | 123.15 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: GWINDOW1 E NEA
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 65.69 | 41.32 | 24.37 | 88.39 | 83.79 | 0.00 | 0.00 | 0.00 |
| February | 64.54 | 36.92 | 27.62 | 78.95 | 78.22 | 0.00 | 0.00 | 0.00 |
| March | 80.48 | 41.29 | 39.20 | 112.70 | 68.55 | 0.00 | 0.00 | 0.00 |
| April | 115.25 | 68.75 | 46.50 | 199.47 | 38.70 | 0.00 | 0.00 | 0.00 |
| May | 119.43 | 70.83 | 48.60 | 221.36 | 25.69 | 0.00 | 0.00 | 0.00 |
| June | 124.45 | 77.35 | 47.09 | 268.41 | 9.03 | 0.00 | 0.00 | 0.00 |
| July | 105.26 | 59.44 | 45.81 | 230.47 | 6.75 | 0.00 | 0.00 | 0.00 |
| August | 99.77 | 56.95 | 42.82 | 215.10 | 9.40 | 0.00 | 0.00 | 0.00 |
| September | 81.80 | 39.42 | 42.38 | 168.77 | 14.71 | 0.00 | 0.00 | 0.00 |
| October | 82.08 | 49.92 | 32.16 | 132.46 | 55.29 | 0.00 | 0.00 | 0.00 |
| November | 63.22 | 37.94 | 25.28 | 80.41 | 83.66 | 0.00 | 0.00 | 0.00 |
| December | 57.56 | 34.75 | 22.82 | 66.66 | 104.87 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 88.40 | 51.31 | 37.10 | 155.63 | 48.10 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 57.56 | 34.75 | 22.82 | 66.66 | 6.75 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 124.45 | 77.35 | 48.60 | 268.41 | 104.87 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: GWINDOW1 N NEA
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 30.77 | 0.00 | 30.77 | 24.34 | 140.39 | 0.00 | 0.00 | 0.00 |
| February | 35.06 | 0.00 | 35.06 | 19.66 | 129.27 | 0.00 | 0.00 | 0.00 |
| March | 46.60 | 0.01 | 46.60 | 48.61 | 113.84 | 0.00 | 0.00 | 0.00 |
| April | 56.95 | 0.75 | 56.19 | 98.82 | 63.50 | 0.00 | 0.00 | 0.00 |
| May | 67.07 | 5.81 | 61.26 | 137.32 | 39.89 | 0.00 | 0.00 | 0.00 |
| June | 76.92 | 13.77 | 63.16 | 215.57 | 14.33 | 0.00 | 0.00 | 0.00 |
| July | 65.65 | 6.66 | 58.99 | 185.25 | 10.90 | 0.00 | 0.00 | 0.00 |
| August | 53.32 | 1.43 | 51.89 | 151.66 | 15.20 | 0.00 | 0.00 | 0.00 |
| September | 50.18 | 0.03 | 50.15 | 124.93 | 24.51 | 0.00 | 0.00 | 0.00 |
| October | 38.80 | 0.00 | 38.80 | 56.63 | 93.00 | 0.00 | 0.00 | 0.00 |
| November | 32.33 | 0.00 | 32.33 | 21.57 | 139.74 | 0.00 | 0.00 | 0.00 |
| December | 28.74 | 0.00 | 28.74 | 13.10 | 176.22 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 48.58 | 2.38 | 46.20 | 91.78 | 79.88 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 28.74 | 0.00 | 28.74 | 13.10 | 10.90 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 76.92 | 13.77 | 63.16 | 215.57 | 176.22 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: GWINDOW1 N N1A
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 30.77 | 0.00 | 30.77 | 24.01 | 144.94 | 0.00 | 0.00 | 0.00 |
| February | 35.06 | 0.00 | 35.06 | 19.17 | 134.95 | 0.00 | 0.00 | 0.00 |
| March | 46.60 | 0.01 | 46.60 | 48.15 | 117.90 | 0.00 | 0.00 | 0.00 |
| April | 56.95 | 0.75 | 56.19 | 100.59 | 63.75 | 0.00 | 0.00 | 0.00 |
| May | 67.07 | 5.81 | 61.26 | 139.50 | 39.81 | 0.00 | 0.00 | 0.00 |
| June | 76.92 | 13.77 | 63.16 | 219.21 | 13.99 | 0.00 | 0.00 | 0.00 |
| July | 65.65 | 6.66 | 58.99 | 189.06 | 10.44 | 0.00 | 0.00 | 0.00 |
| August | 53.32 | 1.43 | 51.89 | 155.29 | 14.50 | 0.00 | 0.00 | 0.00 |
| September | 50.18 | 0.03 | 50.15 | 127.85 | 23.59 | 0.00 | 0.00 | 0.00 |
| October | 38.80 | 0.00 | 38.80 | 58.14 | 92.95 | 0.00 | 0.00 | 0.00 |
| November | 32.33 | 0.00 | 32.33 | 21.80 | 142.18 | 0.00 | 0.00 | 0.00 |
| December | 28.74 | 0.00 | 28.74 | 13.04 | 180.12 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 48.58 | 2.38 | 46.20 | 93.32 | 81.38 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 28.74 | 0.00 | 28.74 | 13.04 | 10.44 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 76.92 | 13.77 | 63.16 | 219.21 | 180.12 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: GWINDOW1 N N2A
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 30.77 | 0.00 | 30.77 | 23.99 | 144.88 | 0.00 | 0.00 | 0.00 |
| February | 35.06 | 0.00 | 35.06 | 19.10 | 135.08 | 0.00 | 0.00 | 0.00 |
| March | 46.60 | 0.01 | 46.60 | 48.06 | 117.98 | 0.00 | 0.00 | 0.00 |
| April | 56.95 | 0.75 | 56.19 | 100.56 | 63.75 | 0.00 | 0.00 | 0.00 |
| May | 67.07 | 5.81 | 61.26 | 139.47 | 39.80 | 0.00 | 0.00 | 0.00 |
| June | 76.92 | 13.77 | 63.16 | 219.19 | 13.99 | 0.00 | 0.00 | 0.00 |
| July | 65.65 | 6.66 | 58.99 | 189.03 | 10.44 | 0.00 | 0.00 | 0.00 |
| August | 53.32 | 1.43 | 51.89 | 155.26 | 14.50 | 0.00 | 0.00 | 0.00 |
| September | 50.18 | 0.03 | 50.15 | 127.83 | 23.59 | 0.00 | 0.00 | 0.00 |
| October | 38.80 | 0.00 | 38.80 | 58.11 | 92.97 | 0.00 | 0.00 | 0.00 |
| November | 32.33 | 0.00 | 32.33 | 21.79 | 142.15 | 0.00 | 0.00 | 0.00 |
| December | 28.74 | 0.00 | 28.74 | 13.01 | 180.17 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 48.58 | 2.38 | 46.20 | 93.29 | 81.40 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 28.74 | 0.00 | 28.74 | 13.01 | 10.44 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 76.92 | 13.77 | 63.16 | 219.19 | 180.17 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: GWINDOW1 S S1A
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 251.85 | 200.83 | 51.02 | 388.72 | 145.43 | 0.00 | 0.00 | 0.00 |
| February | 162.34 | 110.19 | 52.16 | 224.37 | 139.25 | 0.00 | 0.00 | 0.00 |
| March | 127.64 | 63.01 | 64.63 | 192.23 | 123.63 | 0.00 | 0.00 | 0.00 |
| April | 117.92 | 50.30 | 67.62 | 231.27 | 67.28 | 0.00 | 0.00 | 0.00 |
| May | 76.16 | 12.70 | 63.46 | 169.07 | 44.40 | 0.00 | 0.00 | 0.00 |
| June | 65.43 | 5.35 | 60.08 | 200.09 | 15.07 | 0.00 | 0.00 | 0.00 |
| July | 66.44 | 6.80 | 59.64 | 194.86 | 10.88 | 0.00 | 0.00 | 0.00 |
| August | 81.43 | 22.89 | 58.54 | 220.39 | 14.88 | 0.00 | 0.00 | 0.00 |
| September | 116.80 | 49.96 | 66.84 | 260.22 | 23.69 | 0.00 | 0.00 | 0.00 |
| October | 185.76 | 128.59 | 57.17 | 318.98 | 88.44 | 0.00 | 0.00 | 0.00 |
| November | 218.92 | 168.25 | 50.67 | 331.40 | 134.99 | 0.00 | 0.00 | 0.00 |
| December | 235.20 | 186.13 | 49.07 | 343.26 | 177.07 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 142.13 | 83.70 | 58.43 | 256.51 | 81.85 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 65.43 | 5.35 | 49.07 | 169.07 | 10.88 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 251.85 | 200.83 | 67.62 | 388.72 | 177.07 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: GWINDOW1 S S2A
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 251.85 | 200.83 | 51.02 | 388.42 | 145.89 | 0.00 | 0.00 | 0.00 |
| February | 162.34 | 110.19 | 52.16 | 223.83 | 140.41 | 0.00 | 0.00 | 0.00 |
| March | 127.64 | 63.01 | 64.63 | 191.56 | 124.64 | 0.00 | 0.00 | 0.00 |
| April | 117.92 | 50.30 | 67.62 | 230.57 | 68.08 | 0.00 | 0.00 | 0.00 |
| May | 76.16 | 12.70 | 63.46 | 168.13 | 45.19 | 0.00 | 0.00 | 0.00 |
| June | 65.43 | 5.35 | 60.08 | 198.68 | 15.63 | 0.00 | 0.00 | 0.00 |
| July | 66.44 | 6.80 | 59.64 | 193.33 | 11.40 | 0.00 | 0.00 | 0.00 |
| August | 81.43 | 22.89 | 58.54 | 219.12 | 15.55 | 0.00 | 0.00 | 0.00 |
| September | 116.80 | 49.96 | 66.84 | 259.12 | 24.54 | 0.00 | 0.00 | 0.00 |
| October | 185.76 | 128.59 | 57.17 | 318.30 | 89.28 | 0.00 | 0.00 | 0.00 |
| November | 218.92 | 168.25 | 50.67 | 331.04 | 135.58 | 0.00 | 0.00 | 0.00 |
| December | 235.20 | 186.13 | 49.07 | 342.91 | 177.68 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 142.13 | 83.70 | 58.43 | 255.68 | 82.59 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 65.43 | 5.35 | 49.07 | 168.13 | 11.40 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 251.85 | 200.83 | 67.62 | 388.42 | 177.68 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MWINDOW1 S SWA
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 251.85 | 200.83 | 51.02 | 387.29 | 143.78 | 0.00 | 0.00 | 0.00 |
| February | 162.34 | 110.19 | 52.16 | 221.13 | 143.07 | 0.00 | 0.00 | 0.00 |
| March | 127.64 | 63.01 | 64.63 | 188.13 | 128.29 | 0.00 | 0.00 | 0.00 |
| April | 117.92 | 50.30 | 67.62 | 228.18 | 68.71 | 0.00 | 0.00 | 0.00 |
| May | 76.16 | 12.70 | 63.46 | 166.42 | 45.42 | 0.00 | 0.00 | 0.00 |
| June | 65.43 | 5.35 | 60.08 | 197.76 | 15.30 | 0.00 | 0.00 | 0.00 |
| July | 66.44 | 6.80 | 59.64 | 194.35 | 10.54 | 0.00 | 0.00 | 0.00 |
| August | 81.43 | 22.89 | 58.54 | 220.25 | 14.08 | 0.00 | 0.00 | 0.00 |
| September | 116.80 | 49.96 | 66.84 | 260.39 | 22.09 | 0.00 | 0.00 | 0.00 |
| October | 185.76 | 128.59 | 57.17 | 318.69 | 85.82 | 0.00 | 0.00 | 0.00 |
| November | 218.92 | 168.25 | 50.67 | 331.58 | 130.96 | 0.00 | 0.00 | 0.00 |
| December | 235.20 | 186.13 | 49.07 | 344.74 | 170.61 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 142.13 | 83.70 | 58.43 | 255.19 | 81.29 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 65.43 | 5.35 | 49.07 | 166.42 | 10.54 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 251.85 | 200.83 | 67.62 | 387.29 | 170.61 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MWINDOW1 W SWA
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 68.82 | 42.91 | 25.91 | 97.00 | 103.35 | 0.00 | 0.00 | 0.00 |
| February | 55.31 | 26.70 | 28.61 | 61.36 | 101.10 | 0.00 | 0.00 | 0.00 |
| March | 73.78 | 35.35 | 38.42 | 98.46 | 84.74 | 0.00 | 0.00 | 0.00 |
| April | 112.55 | 64.15 | 48.40 | 196.77 | 44.79 | 0.00 | 0.00 | 0.00 |
| May | 113.04 | 63.28 | 49.77 | 213.62 | 29.80 | 0.00 | 0.00 | 0.00 |
| June | 120.14 | 70.73 | 49.41 | 263.39 | 10.43 | 0.00 | 0.00 | 0.00 |
| July | 87.38 | 40.79 | 46.59 | 201.33 | 7.22 | 0.00 | 0.00 | 0.00 |
| August | 83.49 | 41.95 | 41.54 | 188.73 | 9.65 | 0.00 | 0.00 | 0.00 |
| September | 72.72 | 30.59 | 42.13 | 155.03 | 15.05 | 0.00 | 0.00 | 0.00 |
| October | 74.29 | 42.46 | 31.84 | 122.99 | 60.34 | 0.00 | 0.00 | 0.00 |
| November | 68.18 | 41.06 | 27.12 | 94.09 | 93.82 | 0.00 | 0.00 | 0.00 |
| December | 55.13 | 31.37 | 23.76 | 68.20 | 123.46 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 82.17 | 44.34 | 37.82 | 147.11 | 56.79 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 55.13 | 26.70 | 23.76 | 61.36 | 7.22 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 120.14 | 70.73 | 49.77 | 263.39 | 123.46 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MWINDOW1 W NWA
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 68.82 | 42.91 | 25.91 | 101.56 | 95.71 | 0.00 | 0.00 | 0.00 |
| February | 55.31 | 26.70 | 28.61 | 65.42 | 92.56 | 0.00 | 0.00 | 0.00 |
| March | 73.78 | 35.35 | 38.42 | 101.33 | 81.43 | 0.00 | 0.00 | 0.00 |
| April | 112.55 | 64.15 | 48.40 | 198.06 | 44.12 | 0.00 | 0.00 | 0.00 |
| May | 113.04 | 63.28 | 49.77 | 213.91 | 29.76 | 0.00 | 0.00 | 0.00 |
| June | 120.14 | 70.73 | 49.41 | 263.16 | 10.49 | 0.00 | 0.00 | 0.00 |
| July | 87.38 | 40.79 | 46.59 | 201.41 | 7.23 | 0.00 | 0.00 | 0.00 |
| August | 83.49 | 41.95 | 41.54 | 189.44 | 9.53 | 0.00 | 0.00 | 0.00 |
| September | 72.72 | 30.59 | 42.13 | 156.33 | 14.69 | 0.00 | 0.00 | 0.00 |
| October | 74.29 | 42.46 | 31.84 | 125.55 | 58.02 | 0.00 | 0.00 | 0.00 |
| November | 68.18 | 41.06 | 27.12 | 97.67 | 87.62 | 0.00 | 0.00 | 0.00 |
| December | 55.13 | 31.37 | 23.76 | 73.35 | 112.67 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 82.17 | 44.34 | 37.82 | 149.29 | 53.49 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 55.13 | 26.70 | 23.76 | 65.42 | 7.23 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 120.14 | 70.73 | 49.77 | 263.16 | 112.67 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MWINDOW1 N NWA
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 30.77 | 0.00 | 30.77 | 22.88 | 147.65 | 0.00 | 0.00 | 0.00 |
| February | 35.06 | 0.00 | 35.06 | 16.16 | 144.33 | 0.00 | 0.00 | 0.00 |
| March | 46.60 | 0.01 | 46.60 | 43.10 | 127.46 | 0.00 | 0.00 | 0.00 |
| April | 56.95 | 0.75 | 56.19 | 97.64 | 65.99 | 0.00 | 0.00 | 0.00 |
| May | 67.07 | 5.81 | 61.26 | 136.77 | 40.92 | 0.00 | 0.00 | 0.00 |
| June | 76.92 | 13.77 | 63.16 | 216.79 | 14.29 | 0.00 | 0.00 | 0.00 |
| July | 65.65 | 6.66 | 58.99 | 188.54 | 10.20 | 0.00 | 0.00 | 0.00 |
| August | 53.32 | 1.43 | 51.89 | 155.25 | 13.95 | 0.00 | 0.00 | 0.00 |
| September | 50.18 | 0.03 | 50.15 | 128.51 | 22.38 | 0.00 | 0.00 | 0.00 |
| October | 38.80 | 0.00 | 38.80 | 59.11 | 89.69 | 0.00 | 0.00 | 0.00 |
| November | 32.33 | 0.00 | 32.33 | 23.29 | 135.63 | 0.00 | 0.00 | 0.00 |
| December | 28.74 | 0.00 | 28.74 | 14.09 | 174.57 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 48.58 | 2.38 | 46.20 | 92.20 | 81.99 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 28.74 | 0.00 | 28.74 | 14.09 | 10.20 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 76.92 | 13.77 | 63.16 | 216.79 | 174.57 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MWINDOW1 S SEA
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 251.85 | 200.83 | 51.02 | 386.64 | 143.21 | 0.00 | 0.00 | 0.00 |
| February | 162.34 | 110.19 | 52.16 | 220.08 | 143.10 | 0.00 | 0.00 | 0.00 |
| March | 127.64 | 63.01 | 64.63 | 186.91 | 128.20 | 0.00 | 0.00 | 0.00 |
| April | 117.92 | 50.30 | 67.62 | 227.55 | 68.40 | 0.00 | 0.00 | 0.00 |
| May | 76.16 | 12.70 | 63.46 | 165.85 | 45.20 | 0.00 | 0.00 | 0.00 |
| June | 65.43 | 5.35 | 60.08 | 197.32 | 15.16 | 0.00 | 0.00 | 0.00 |
| July | 66.44 | 6.80 | 59.64 | 193.71 | 10.50 | 0.00 | 0.00 | 0.00 |
| August | 81.43 | 22.89 | 58.54 | 219.66 | 14.07 | 0.00 | 0.00 | 0.00 |
| September | 116.80 | 49.96 | 66.84 | 260.00 | 22.02 | 0.00 | 0.00 | 0.00 |
| October | 185.76 | 128.59 | 57.17 | 317.97 | 85.58 | 0.00 | 0.00 | 0.00 |
| November | 218.92 | 168.25 | 50.67 | 331.01 | 130.41 | 0.00 | 0.00 | 0.00 |
| December | 235.20 | 186.13 | 49.07 | 343.75 | 170.39 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 142.13 | 83.70 | 58.43 | 254.49 | 81.09 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 65.43 | 5.35 | 49.07 | 165.85 | 10.50 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 251.85 | 200.83 | 67.62 | 386.64 | 170.39 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MWINDOW1 E SEA
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 65.69 | 41.32 | 24.37 | 80.38 | 95.00 | 0.00 | 0.00 | 0.00 |
| February | 64.54 | 36.92 | 27.62 | 70.14 | 95.73 | 0.00 | 0.00 | 0.00 |
| March | 80.48 | 41.29 | 39.20 | 103.65 | 79.86 | 0.00 | 0.00 | 0.00 |
| April | 115.25 | 68.75 | 46.50 | 196.00 | 40.61 | 0.00 | 0.00 | 0.00 |
| May | 119.43 | 70.83 | 48.60 | 219.60 | 26.21 | 0.00 | 0.00 | 0.00 |
| June | 124.45 | 77.35 | 47.09 | 268.50 | 8.81 | 0.00 | 0.00 | 0.00 |
| July | 105.26 | 59.44 | 45.81 | 231.61 | 6.24 | 0.00 | 0.00 | 0.00 |
| August | 99.77 | 56.95 | 42.82 | 215.80 | 8.66 | 0.00 | 0.00 | 0.00 |
| September | 81.80 | 39.42 | 42.38 | 169.13 | 13.66 | 0.00 | 0.00 | 0.00 |
| October | 82.08 | 49.92 | 32.16 | 130.68 | 55.62 | 0.00 | 0.00 | 0.00 |
| November | 63.22 | 37.94 | 25.28 | 77.18 | 87.14 | 0.00 | 0.00 | 0.00 |
| December | 57.56 | 34.75 | 22.82 | 61.21 | 114.92 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 88.40 | 51.31 | 37.10 | 152.38 | 52.52 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 57.56 | 34.75 | 22.82 | 61.21 | 6.24 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 124.45 | 77.35 | 48.60 | 268.50 | 114.92 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MWINDOW1 E NEA
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 65.69 | 41.32 | 24.37 | 85.75 | 87.87 | 0.00 | 0.00 | 0.00 |
| February | 64.54 | 36.92 | 27.62 | 74.25 | 87.75 | 0.00 | 0.00 | 0.00 |
| March | 80.48 | 41.29 | 39.20 | 106.52 | 76.69 | 0.00 | 0.00 | 0.00 |
| April | 115.25 | 68.75 | 46.50 | 197.30 | 39.99 | 0.00 | 0.00 | 0.00 |
| May | 119.43 | 70.83 | 48.60 | 219.87 | 26.15 | 0.00 | 0.00 | 0.00 |
| June | 124.45 | 77.35 | 47.09 | 268.28 | 8.86 | 0.00 | 0.00 | 0.00 |
| July | 105.26 | 59.44 | 45.81 | 231.69 | 6.24 | 0.00 | 0.00 | 0.00 |
| August | 99.77 | 56.95 | 42.82 | 216.51 | 8.54 | 0.00 | 0.00 | 0.00 |
| September | 81.80 | 39.42 | 42.38 | 170.44 | 13.31 | 0.00 | 0.00 | 0.00 |
| October | 82.08 | 49.92 | 32.16 | 133.30 | 53.56 | 0.00 | 0.00 | 0.00 |
| November | 63.22 | 37.94 | 25.28 | 81.25 | 81.36 | 0.00 | 0.00 | 0.00 |
| December | 57.56 | 34.75 | 22.82 | 66.74 | 104.23 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 88.40 | 51.31 | 37.10 | 154.71 | 49.38 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 57.56 | 34.75 | 22.82 | 66.74 | 6.24 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 124.45 | 77.35 | 48.60 | 268.28 | 104.23 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MWINDOW1 N NEA
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 30.77 | 0.00 | 30.77 | 22.18 | 147.12 | 0.00 | 0.00 | 0.00 |
| February | 35.06 | 0.00 | 35.06 | 15.07 | 145.24 | 0.00 | 0.00 | 0.00 |
| March | 46.60 | 0.01 | 46.60 | 41.88 | 127.63 | 0.00 | 0.00 | 0.00 |
| April | 56.95 | 0.75 | 56.19 | 97.00 | 65.75 | 0.00 | 0.00 | 0.00 |
| May | 67.07 | 5.81 | 61.26 | 136.09 | 40.61 | 0.00 | 0.00 | 0.00 |
| June | 76.92 | 13.77 | 63.16 | 216.34 | 14.12 | 0.00 | 0.00 | 0.00 |
| July | 65.65 | 6.66 | 58.99 | 187.88 | 10.14 | 0.00 | 0.00 | 0.00 |
| August | 53.32 | 1.43 | 51.89 | 154.64 | 13.92 | 0.00 | 0.00 | 0.00 |
| September | 50.18 | 0.03 | 50.15 | 128.12 | 22.32 | 0.00 | 0.00 | 0.00 |
| October | 38.80 | 0.00 | 38.80 | 58.35 | 89.85 | 0.00 | 0.00 | 0.00 |
| November | 32.33 | 0.00 | 32.33 | 22.75 | 135.21 | 0.00 | 0.00 | 0.00 |
| December | 28.74 | 0.00 | 28.74 | 13.50 | 174.49 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 48.58 | 2.38 | 46.20 | 91.50 | 81.93 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 28.74 | 0.00 | 28.74 | 13.50 | 10.14 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 76.92 | 13.77 | 63.16 | 216.34 | 174.49 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MWINDOW1 N N1A
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 30.77 | 0.00 | 30.77 | 21.88 | 152.17 | 0.00 | 0.00 | 0.00 |
| February | 35.06 | 0.00 | 35.06 | 14.63 | 152.29 | 0.00 | 0.00 | 0.00 |
| March | 46.60 | 0.01 | 46.60 | 41.98 | 131.46 | 0.00 | 0.00 | 0.00 |
| April | 56.95 | 0.75 | 56.19 | 99.23 | 65.56 | 0.00 | 0.00 | 0.00 |
| May | 67.07 | 5.81 | 61.26 | 138.98 | 40.18 | 0.00 | 0.00 | 0.00 |
| June | 76.92 | 13.77 | 63.16 | 220.41 | 13.72 | 0.00 | 0.00 | 0.00 |
| July | 65.65 | 6.66 | 58.99 | 191.54 | 9.80 | 0.00 | 0.00 | 0.00 |
| August | 53.32 | 1.43 | 51.89 | 157.95 | 13.49 | 0.00 | 0.00 | 0.00 |
| September | 50.18 | 0.03 | 50.15 | 130.52 | 21.90 | 0.00 | 0.00 | 0.00 |
| October | 38.80 | 0.00 | 38.80 | 59.49 | 91.02 | 0.00 | 0.00 | 0.00 |
| November | 32.33 | 0.00 | 32.33 | 22.57 | 139.75 | 0.00 | 0.00 | 0.00 |
| December | 28.74 | 0.00 | 28.74 | 13.06 | 180.28 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 48.58 | 2.38 | 46.20 | 93.05 | 84.01 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 28.74 | 0.00 | 28.74 | 13.06 | 9.80 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 76.92 | 13.77 | 63.16 | 220.41 | 180.28 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MWINDOW1 N N2A
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 30.77 | 0.00 | 30.77 | 21.85 | 152.14 | 0.00 | 0.00 | 0.00 |
| February | 35.06 | 0.00 | 35.06 | 14.53 | 152.48 | 0.00 | 0.00 | 0.00 |
| March | 46.60 | 0.01 | 46.60 | 41.90 | 131.54 | 0.00 | 0.00 | 0.00 |
| April | 56.95 | 0.75 | 56.19 | 99.20 | 65.55 | 0.00 | 0.00 | 0.00 |
| May | 67.07 | 5.81 | 61.26 | 138.95 | 40.17 | 0.00 | 0.00 | 0.00 |
| June | 76.92 | 13.77 | 63.16 | 220.40 | 13.71 | 0.00 | 0.00 | 0.00 |
| July | 65.65 | 6.66 | 58.99 | 191.51 | 9.80 | 0.00 | 0.00 | 0.00 |
| August | 53.32 | 1.43 | 51.89 | 157.93 | 13.49 | 0.00 | 0.00 | 0.00 |
| September | 50.18 | 0.03 | 50.15 | 130.51 | 21.90 | 0.00 | 0.00 | 0.00 |
| October | 38.80 | 0.00 | 38.80 | 59.45 | 91.06 | 0.00 | 0.00 | 0.00 |
| November | 32.33 | 0.00 | 32.33 | 22.54 | 139.72 | 0.00 | 0.00 | 0.00 |
| December | 28.74 | 0.00 | 28.74 | 13.03 | 180.31 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 48.58 | 2.38 | 46.20 | 93.01 | 84.03 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 28.74 | 0.00 | 28.74 | 13.03 | 9.80 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 76.92 | 13.77 | 63.16 | 220.40 | 180.31 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MWINDOW1 S S1A
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 251.85 | 200.83 | 51.02 | 385.82 | 147.19 | 0.00 | 0.00 | 0.00 |
| February | 162.34 | 110.19 | 52.16 | 219.14 | 148.96 | 0.00 | 0.00 | 0.00 |
| March | 127.64 | 63.01 | 64.63 | 186.76 | 131.72 | 0.00 | 0.00 | 0.00 |
| April | 117.92 | 50.30 | 67.62 | 229.62 | 68.26 | 0.00 | 0.00 | 0.00 |
| May | 76.16 | 12.70 | 63.46 | 168.60 | 44.68 | 0.00 | 0.00 | 0.00 |
| June | 65.43 | 5.35 | 60.08 | 201.45 | 14.70 | 0.00 | 0.00 | 0.00 |
| July | 66.44 | 6.80 | 59.64 | 197.35 | 10.14 | 0.00 | 0.00 | 0.00 |
| August | 81.43 | 22.89 | 58.54 | 222.85 | 13.64 | 0.00 | 0.00 | 0.00 |
| September | 116.80 | 49.96 | 66.84 | 262.23 | 21.64 | 0.00 | 0.00 | 0.00 |
| October | 185.76 | 128.59 | 57.17 | 318.94 | 86.55 | 0.00 | 0.00 | 0.00 |
| November | 218.92 | 168.25 | 50.67 | 330.50 | 133.58 | 0.00 | 0.00 | 0.00 |
| December | 235.20 | 186.13 | 49.07 | 341.97 | 176.58 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 142.13 | 83.70 | 58.43 | 255.73 | 82.85 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 65.43 | 5.35 | 49.07 | 168.60 | 10.14 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 251.85 | 200.83 | 67.62 | 385.82 | 176.58 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MWINDOW1 S S2A
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 251.85 | 200.83 | 51.02 | 385.81 | 147.16 | 0.00 | 0.00 | 0.00 |
| February | 162.34 | 110.19 | 52.16 | 219.10 | 148.98 | 0.00 | 0.00 | 0.00 |
| March | 127.64 | 63.01 | 64.63 | 186.71 | 131.75 | 0.00 | 0.00 | 0.00 |
| April | 117.92 | 50.30 | 67.62 | 229.59 | 68.25 | 0.00 | 0.00 | 0.00 |
| May | 76.16 | 12.70 | 63.46 | 168.58 | 44.67 | 0.00 | 0.00 | 0.00 |
| June | 65.43 | 5.35 | 60.08 | 201.43 | 14.69 | 0.00 | 0.00 | 0.00 |
| July | 66.44 | 6.80 | 59.64 | 197.32 | 10.14 | 0.00 | 0.00 | 0.00 |
| August | 81.43 | 22.89 | 58.54 | 222.83 | 13.64 | 0.00 | 0.00 | 0.00 |
| September | 116.80 | 49.96 | 66.84 | 262.22 | 21.64 | 0.00 | 0.00 | 0.00 |
| October | 185.76 | 128.59 | 57.17 | 318.92 | 86.55 | 0.00 | 0.00 | 0.00 |
| November | 218.92 | 168.25 | 50.67 | 330.49 | 133.56 | 0.00 | 0.00 | 0.00 |
| December | 235.20 | 186.13 | 49.07 | 341.94 | 176.59 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 142.13 | 83.70 | 58.43 | 255.70 | 82.85 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 65.43 | 5.35 | 49.07 | 168.58 | 10.14 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 251.85 | 200.83 | 67.62 | 385.81 | 176.59 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: TWINDOW1 S SWA
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 251.85 | 200.83 | 51.02 | 390.27 | 128.94 | 0.00 | 0.00 | 0.00 |
| February | 162.34 | 110.19 | 52.16 | 225.18 | 123.51 | 0.00 | 0.00 | 0.00 |
| March | 127.64 | 63.01 | 64.63 | 191.04 | 114.87 | 0.00 | 0.00 | 0.00 |
| April | 117.92 | 50.30 | 67.62 | 224.99 | 63.55 | 0.00 | 0.00 | 0.00 |
| May | 76.16 | 12.70 | 63.46 | 162.09 | 42.78 | 0.00 | 0.00 | 0.00 |
| June | 65.43 | 5.35 | 60.08 | 191.08 | 14.48 | 0.00 | 0.00 | 0.00 |
| July | 66.44 | 6.80 | 59.64 | 188.04 | 10.09 | 0.00 | 0.00 | 0.00 |
| August | 81.43 | 22.89 | 58.54 | 214.34 | 13.47 | 0.00 | 0.00 | 0.00 |
| September | 116.80 | 49.96 | 66.84 | 255.10 | 21.04 | 0.00 | 0.00 | 0.00 |
| October | 185.76 | 128.59 | 57.17 | 318.11 | 77.70 | 0.00 | 0.00 | 0.00 |
| November | 218.92 | 168.25 | 50.67 | 334.34 | 117.15 | 0.00 | 0.00 | 0.00 |
| December | 235.20 | 186.13 | 49.07 | 348.21 | 154.84 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 142.13 | 83.70 | 58.43 | 253.82 | 73.34 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 65.43 | 5.35 | 49.07 | 162.09 | 10.09 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 251.85 | 200.83 | 67.62 | 390.27 | 154.84 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: TWINDOW1 W SWA
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 68.82 | 42.91 | 25.91 | 96.47 | 91.22 | 0.00 | 0.00 | 0.00 |
| February | 55.31 | 26.70 | 28.61 | 61.96 | 86.29 | 0.00 | 0.00 | 0.00 |
| March | 73.78 | 35.35 | 38.42 | 99.28 | 75.00 | 0.00 | 0.00 | 0.00 |
| April | 112.55 | 64.15 | 48.40 | 194.22 | 41.24 | 0.00 | 0.00 | 0.00 |
| May | 113.04 | 63.28 | 49.77 | 210.36 | 28.06 | 0.00 | 0.00 | 0.00 |
| June | 120.14 | 70.73 | 49.41 | 258.55 | 9.92 | 0.00 | 0.00 | 0.00 |
| July | 87.38 | 40.79 | 46.59 | 196.88 | 6.95 | 0.00 | 0.00 | 0.00 |
| August | 83.49 | 41.95 | 41.54 | 184.60 | 9.27 | 0.00 | 0.00 | 0.00 |
| September | 72.72 | 30.59 | 42.13 | 151.44 | 14.36 | 0.00 | 0.00 | 0.00 |
| October | 74.29 | 42.46 | 31.84 | 121.45 | 53.87 | 0.00 | 0.00 | 0.00 |
| November | 68.18 | 41.06 | 27.12 | 93.72 | 82.67 | 0.00 | 0.00 | 0.00 |
| December | 55.13 | 31.37 | 23.76 | 67.95 | 110.70 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 82.17 | 44.34 | 37.82 | 145.10 | 50.66 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 55.13 | 26.70 | 23.76 | 61.96 | 6.95 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 120.14 | 70.73 | 49.77 | 258.55 | 110.70 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: TWINDOW1 W NWA
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 68.82 | 42.91 | 25.91 | 103.16 | 85.67 | 0.00 | 0.00 | 0.00 |
| February | 55.31 | 26.70 | 28.61 | 67.20 | 81.28 | 0.00 | 0.00 | 0.00 |
| March | 73.78 | 35.35 | 38.42 | 102.98 | 72.86 | 0.00 | 0.00 | 0.00 |
| April | 112.55 | 64.15 | 48.40 | 196.15 | 40.66 | 0.00 | 0.00 | 0.00 |
| May | 113.04 | 63.28 | 49.77 | 210.71 | 28.11 | 0.00 | 0.00 | 0.00 |
| June | 120.14 | 70.73 | 49.41 | 258.23 | 9.99 | 0.00 | 0.00 | 0.00 |
| July | 87.38 | 40.79 | 46.59 | 196.98 | 6.97 | 0.00 | 0.00 | 0.00 |
| August | 83.49 | 41.95 | 41.54 | 185.56 | 9.19 | 0.00 | 0.00 | 0.00 |
| September | 72.72 | 30.59 | 42.13 | 153.24 | 14.11 | 0.00 | 0.00 | 0.00 |
| October | 74.29 | 42.46 | 31.84 | 125.74 | 51.48 | 0.00 | 0.00 | 0.00 |
| November | 68.18 | 41.06 | 27.12 | 99.46 | 77.49 | 0.00 | 0.00 | 0.00 |
| December | 55.13 | 31.37 | 23.76 | 74.58 | 103.80 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 82.17 | 44.34 | 37.82 | 148.18 | 48.34 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 55.13 | 26.70 | 23.76 | 67.20 | 6.97 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 120.14 | 70.73 | 49.77 | 258.23 | 103.80 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: TWINDOW1 N NWA
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 30.77 | 0.00 | 30.77 | 25.75 | 132.66 | 0.00 | 0.00 | 0.00 |
| February | 35.06 | 0.00 | 35.06 | 18.76 | 126.98 | 0.00 | 0.00 | 0.00 |
| March | 46.60 | 0.01 | 46.60 | 45.91 | 114.54 | 0.00 | 0.00 | 0.00 |
| April | 56.95 | 0.75 | 56.19 | 95.51 | 60.96 | 0.00 | 0.00 | 0.00 |
| May | 67.07 | 5.81 | 61.26 | 133.16 | 39.18 | 0.00 | 0.00 | 0.00 |
| June | 76.92 | 13.77 | 63.16 | 210.06 | 13.79 | 0.00 | 0.00 | 0.00 |
| July | 65.65 | 6.66 | 58.99 | 182.25 | 9.93 | 0.00 | 0.00 | 0.00 |
| August | 53.32 | 1.43 | 51.89 | 149.73 | 13.56 | 0.00 | 0.00 | 0.00 |
| September | 50.18 | 0.03 | 50.15 | 124.12 | 21.55 | 0.00 | 0.00 | 0.00 |
| October | 38.80 | 0.00 | 38.80 | 59.71 | 79.86 | 0.00 | 0.00 | 0.00 |
| November | 32.33 | 0.00 | 32.33 | 26.16 | 120.26 | 0.00 | 0.00 | 0.00 |
| December | 28.74 | 0.00 | 28.74 | 16.01 | 161.07 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 48.58 | 2.38 | 46.20 | 90.93 | 74.32 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 28.74 | 0.00 | 28.74 | 16.01 | 9.93 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 76.92 | 13.77 | 63.16 | 210.06 | 161.07 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: TWINDOW1 S SEA
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 251.85 | 200.83 | 51.02 | 388.57 | 127.96 | 0.00 | 0.00 | 0.00 |
| February | 162.34 | 110.19 | 52.16 | 223.07 | 123.03 | 0.00 | 0.00 | 0.00 |
| March | 127.64 | 63.01 | 64.63 | 188.71 | 114.14 | 0.00 | 0.00 | 0.00 |
| April | 117.92 | 50.30 | 67.62 | 223.45 | 62.95 | 0.00 | 0.00 | 0.00 |
| May | 76.16 | 12.70 | 63.46 | 161.04 | 42.43 | 0.00 | 0.00 | 0.00 |
| June | 65.43 | 5.35 | 60.08 | 190.42 | 14.33 | 0.00 | 0.00 | 0.00 |
| July | 66.44 | 6.80 | 59.64 | 187.15 | 10.02 | 0.00 | 0.00 | 0.00 |
| August | 81.43 | 22.89 | 58.54 | 213.50 | 13.40 | 0.00 | 0.00 | 0.00 |
| September | 116.80 | 49.96 | 66.84 | 254.52 | 20.92 | 0.00 | 0.00 | 0.00 |
| October | 185.76 | 128.59 | 57.17 | 316.46 | 77.09 | 0.00 | 0.00 | 0.00 |
| November | 218.92 | 168.25 | 50.67 | 332.88 | 116.03 | 0.00 | 0.00 | 0.00 |
| December | 235.20 | 186.13 | 49.07 | 346.49 | 154.08 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 142.13 | 83.70 | 58.43 | 252.45 | 72.83 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 65.43 | 5.35 | 49.07 | 161.04 | 10.02 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 251.85 | 200.83 | 67.62 | 388.57 | 154.08 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: TWINDOW1 E SEA
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 65.69 | 41.32 | 24.37 | 82.40 | 85.48 | 0.00 | 0.00 | 0.00 |
| February | 64.54 | 36.92 | 27.62 | 72.55 | 82.79 | 0.00 | 0.00 | 0.00 |
| March | 80.48 | 41.29 | 39.20 | 106.00 | 71.65 | 0.00 | 0.00 | 0.00 |
| April | 115.25 | 68.75 | 46.50 | 194.16 | 37.97 | 0.00 | 0.00 | 0.00 |
| May | 119.43 | 70.83 | 48.60 | 216.61 | 24.93 | 0.00 | 0.00 | 0.00 |
| June | 124.45 | 77.35 | 47.09 | 263.64 | 8.40 | 0.00 | 0.00 | 0.00 |
| July | 105.26 | 59.44 | 45.81 | 227.02 | 5.98 | 0.00 | 0.00 | 0.00 |
| August | 99.77 | 56.95 | 42.82 | 211.50 | 8.28 | 0.00 | 0.00 | 0.00 |
| September | 81.80 | 39.42 | 42.38 | 165.47 | 13.03 | 0.00 | 0.00 | 0.00 |
| October | 82.08 | 49.92 | 32.16 | 130.28 | 50.49 | 0.00 | 0.00 | 0.00 |
| November | 63.22 | 37.94 | 25.28 | 79.00 | 78.04 | 0.00 | 0.00 | 0.00 |
| December | 57.56 | 34.75 | 22.82 | 63.61 | 104.63 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 88.40 | 51.31 | 37.10 | 151.40 | 47.50 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 57.56 | 34.75 | 22.82 | 63.61 | 5.98 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 124.45 | 77.35 | 48.60 | 263.64 | 104.63 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: TWINDOW1 E NEA
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 65.69 | 41.32 | 24.37 | 89.02 | 79.13 | 0.00 | 0.00 | 0.00 |
| February | 64.54 | 36.92 | 27.62 | 77.23 | 76.87 | 0.00 | 0.00 | 0.00 |
| March | 80.48 | 41.29 | 39.20 | 109.31 | 69.08 | 0.00 | 0.00 | 0.00 |
| April | 115.25 | 68.75 | 46.50 | 195.99 | 37.39 | 0.00 | 0.00 | 0.00 |
| May | 119.43 | 70.83 | 48.60 | 216.94 | 24.92 | 0.00 | 0.00 | 0.00 |
| June | 124.45 | 77.35 | 47.09 | 263.33 | 8.45 | 0.00 | 0.00 | 0.00 |
| July | 105.26 | 59.44 | 45.81 | 227.12 | 5.99 | 0.00 | 0.00 | 0.00 |
| August | 99.77 | 56.95 | 42.82 | 212.45 | 8.19 | 0.00 | 0.00 | 0.00 |
| September | 81.80 | 39.42 | 42.38 | 167.27 | 12.78 | 0.00 | 0.00 | 0.00 |
| October | 82.08 | 49.92 | 32.16 | 134.38 | 47.95 | 0.00 | 0.00 | 0.00 |
| November | 63.22 | 37.94 | 25.28 | 84.40 | 72.14 | 0.00 | 0.00 | 0.00 |
| December | 57.56 | 34.75 | 22.82 | 69.35 | 96.25 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 88.40 | 51.31 | 37.10 | 154.27 | 44.80 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 57.56 | 34.75 | 22.82 | 69.35 | 5.99 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 124.45 | 77.35 | 48.60 | 263.33 | 96.25 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: TWINDOW1 N NEA
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 30.77 | 0.00 | 30.77 | 24.18 | 131.18 | 0.00 | 0.00 | 0.00 |
| February | 35.06 | 0.00 | 35.06 | 17.10 | 126.38 | 0.00 | 0.00 | 0.00 |
| March | 46.60 | 0.01 | 46.60 | 43.67 | 113.75 | 0.00 | 0.00 | 0.00 |
| April | 56.95 | 0.75 | 56.19 | 93.93 | 60.45 | 0.00 | 0.00 | 0.00 |
| May | 67.07 | 5.81 | 61.26 | 131.93 | 38.62 | 0.00 | 0.00 | 0.00 |
| June | 76.92 | 13.77 | 63.16 | 209.41 | 13.57 | 0.00 | 0.00 | 0.00 |
| July | 65.65 | 6.66 | 58.99 | 181.34 | 9.82 | 0.00 | 0.00 | 0.00 |
| August | 53.32 | 1.43 | 51.89 | 148.86 | 13.46 | 0.00 | 0.00 | 0.00 |
| September | 50.18 | 0.03 | 50.15 | 123.54 | 21.45 | 0.00 | 0.00 | 0.00 |
| October | 38.80 | 0.00 | 38.80 | 58.07 | 79.40 | 0.00 | 0.00 | 0.00 |
| November | 32.33 | 0.00 | 32.33 | 24.82 | 118.70 | 0.00 | 0.00 | 0.00 |
| December | 28.74 | 0.00 | 28.74 | 14.99 | 160.03 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 48.58 | 2.38 | 46.20 | 89.65 | 73.69 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 28.74 | 0.00 | 28.74 | 14.99 | 9.82 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 76.92 | 13.77 | 63.16 | 209.41 | 160.03 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: TWINDOW1 N N1A
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 30.77 | 0.00 | 30.77 | 26.04 | 133.96 | 0.00 | 0.00 | 0.00 |
| February | 35.06 | 0.00 | 35.06 | 18.65 | 129.18 | 0.00 | 0.00 | 0.00 |
| March | 46.60 | 0.01 | 46.60 | 45.93 | 116.51 | 0.00 | 0.00 | 0.00 |
| April | 56.95 | 0.75 | 56.19 | 97.55 | 61.50 | 0.00 | 0.00 | 0.00 |
| May | 67.07 | 5.81 | 61.26 | 135.88 | 38.88 | 0.00 | 0.00 | 0.00 |
| June | 76.92 | 13.77 | 63.16 | 214.65 | 13.42 | 0.00 | 0.00 | 0.00 |
| July | 65.65 | 6.66 | 58.99 | 186.00 | 9.70 | 0.00 | 0.00 | 0.00 |
| August | 53.32 | 1.43 | 51.89 | 153.17 | 13.32 | 0.00 | 0.00 | 0.00 |
| September | 50.18 | 0.03 | 50.15 | 126.80 | 21.41 | 0.00 | 0.00 | 0.00 |
| October | 38.80 | 0.00 | 38.80 | 60.67 | 81.16 | 0.00 | 0.00 | 0.00 |
| November | 32.33 | 0.00 | 32.33 | 26.26 | 122.01 | 0.00 | 0.00 | 0.00 |
| December | 28.74 | 0.00 | 28.74 | 16.01 | 162.77 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 48.58 | 2.38 | 46.20 | 92.64 | 75.10 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 28.74 | 0.00 | 28.74 | 16.01 | 9.70 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 76.92 | 13.77 | 63.16 | 214.65 | 162.77 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: TWINDOW1 N N2A
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 30.77 | 0.00 | 30.77 | 25.90 | 133.84 | 0.00 | 0.00 | 0.00 |
| February | 35.06 | 0.00 | 35.06 | 18.50 | 129.19 | 0.00 | 0.00 | 0.00 |
| March | 46.60 | 0.01 | 46.60 | 45.75 | 116.49 | 0.00 | 0.00 | 0.00 |
| April | 56.95 | 0.75 | 56.19 | 97.44 | 61.46 | 0.00 | 0.00 | 0.00 |
| May | 67.07 | 5.81 | 61.26 | 135.82 | 38.85 | 0.00 | 0.00 | 0.00 |
| June | 76.92 | 13.77 | 63.16 | 214.62 | 13.41 | 0.00 | 0.00 | 0.00 |
| July | 65.65 | 6.66 | 58.99 | 185.96 | 9.69 | 0.00 | 0.00 | 0.00 |
| August | 53.32 | 1.43 | 51.89 | 153.13 | 13.32 | 0.00 | 0.00 | 0.00 |
| September | 50.18 | 0.03 | 50.15 | 126.77 | 21.40 | 0.00 | 0.00 | 0.00 |
| October | 38.80 | 0.00 | 38.80 | 60.54 | 81.14 | 0.00 | 0.00 | 0.00 |
| November | 32.33 | 0.00 | 32.33 | 26.15 | 121.88 | 0.00 | 0.00 | 0.00 |
| December | 28.74 | 0.00 | 28.74 | 15.91 | 162.69 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 48.58 | 2.38 | 46.20 | 92.55 | 75.06 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 28.74 | 0.00 | 28.74 | 15.91 | 9.69 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 76.92 | 13.77 | 63.16 | 214.62 | 162.69 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: TWINDOW1 S S1A
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 251.85 | 200.83 | 51.02 | 389.25 | 132.34 | 0.00 | 0.00 | 0.00 |
| February | 162.34 | 110.19 | 52.16 | 223.90 | 127.88 | 0.00 | 0.00 | 0.00 |
| March | 127.64 | 63.01 | 64.63 | 190.32 | 117.87 | 0.00 | 0.00 | 0.00 |
| April | 117.92 | 50.30 | 67.62 | 226.76 | 64.12 | 0.00 | 0.00 | 0.00 |
| May | 76.16 | 12.70 | 63.46 | 164.95 | 42.69 | 0.00 | 0.00 | 0.00 |
| June | 65.43 | 5.35 | 60.08 | 195.79 | 14.15 | 0.00 | 0.00 | 0.00 |
| July | 66.44 | 6.80 | 59.64 | 191.80 | 9.90 | 0.00 | 0.00 | 0.00 |
| August | 81.43 | 22.89 | 58.54 | 217.67 | 13.27 | 0.00 | 0.00 | 0.00 |
| September | 116.80 | 49.96 | 66.84 | 257.55 | 20.92 | 0.00 | 0.00 | 0.00 |
| October | 185.76 | 128.59 | 57.17 | 318.36 | 79.46 | 0.00 | 0.00 | 0.00 |
| November | 218.92 | 168.25 | 50.67 | 333.37 | 120.54 | 0.00 | 0.00 | 0.00 |
| December | 235.20 | 186.13 | 49.07 | 346.79 | 158.68 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 142.13 | 83.70 | 58.43 | 254.98 | 74.94 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 65.43 | 5.35 | 49.07 | 164.95 | 9.90 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 251.85 | 200.83 | 67.62 | 389.25 | 158.68 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: TWINDOW1 S S2A
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 251.85 | 200.83 | 51.02 | 389.16 | 132.28 | 0.00 | 0.00 | 0.00 |
| February | 162.34 | 110.19 | 52.16 | 223.76 | 127.88 | 0.00 | 0.00 | 0.00 |
| March | 127.64 | 63.01 | 64.63 | 190.17 | 117.84 | 0.00 | 0.00 | 0.00 |
| April | 117.92 | 50.30 | 67.62 | 226.67 | 64.08 | 0.00 | 0.00 | 0.00 |
| May | 76.16 | 12.70 | 63.46 | 164.89 | 42.66 | 0.00 | 0.00 | 0.00 |
| June | 65.43 | 5.35 | 60.08 | 195.75 | 14.14 | 0.00 | 0.00 | 0.00 |
| July | 66.44 | 6.80 | 59.64 | 191.76 | 9.89 | 0.00 | 0.00 | 0.00 |
| August | 81.43 | 22.89 | 58.54 | 217.63 | 13.27 | 0.00 | 0.00 | 0.00 |
| September | 116.80 | 49.96 | 66.84 | 257.52 | 20.92 | 0.00 | 0.00 | 0.00 |
| October | 185.76 | 128.59 | 57.17 | 318.27 | 79.43 | 0.00 | 0.00 | 0.00 |
| November | 218.92 | 168.25 | 50.67 | 333.29 | 120.46 | 0.00 | 0.00 | 0.00 |
| December | 235.20 | 186.13 | 49.07 | 346.69 | 158.64 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 142.13 | 83.70 | 58.43 | 254.90 | 74.91 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 65.43 | 5.35 | 49.07 | 164.89 | 9.89 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 251.85 | 200.83 | 67.62 | 389.16 | 158.64 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: TWINDOW14
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 15.76 | 9.92 | 5.85 | 20.34 | 22.05 | 104.67 | 0.00 | 0.00 |
| February | 15.49 | 8.86 | 6.63 | 17.62 | 21.57 | 219.67 | 0.00 | 0.00 |
| March | 19.31 | 9.91 | 9.41 | 25.25 | 19.15 | 97.00 | 0.00 | 0.00 |
| April | 27.66 | 16.50 | 11.16 | 45.47 | 10.78 | 11.00 | 0.00 | 0.00 |
| May | 28.66 | 17.00 | 11.66 | 50.22 | 7.41 | 0.83 | 0.00 | 0.00 |
| June | 29.86 | 18.56 | 11.30 | 60.26 | 2.91 | 0.00 | 0.00 | 0.00 |
| July | 25.26 | 14.26 | 10.99 | 51.38 | 2.31 | 49.33 | 0.00 | 0.00 |
| August | 23.94 | 13.67 | 10.27 | 48.19 | 3.14 | 106.33 | 0.00 | 0.00 |
| September | 19.63 | 9.46 | 10.17 | 37.66 | 4.48 | 119.67 | 0.00 | 0.00 |
| October | 19.70 | 11.98 | 7.72 | 30.77 | 13.77 | 87.83 | 0.00 | 0.00 |
| November | 15.17 | 9.10 | 6.07 | 19.18 | 20.39 | 139.50 | 0.00 | 0.00 |
| December | 13.81 | 8.34 | 5.47 | 15.78 | 26.12 | 119.00 | 0.00 | 0.00 |
| Annual Sum or Average | 21.21 | 12.31 | 8.90 | 35.26 | 12.80 | 1054.83 | 0.00 | 0.00 |
| Minimum of Months | 13.81 | 8.34 | 5.47 | 15.78 | 2.31 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 29.86 | 18.56 | 11.66 | 60.26 | 26.12 | 219.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ENTRANCE DOOR
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 46.95 | 29.53 | 17.41 | 58.96 | 67.93 | 1.50 | 0.00 | 0.00 |
| February | 46.12 | 26.39 | 19.74 | 53.29 | 63.87 | 2.33 | 0.00 | 0.00 |
| March | 57.52 | 29.51 | 28.01 | 75.93 | 55.88 | 0.00 | 0.00 | 0.00 |
| April | 82.36 | 49.13 | 33.23 | 134.10 | 33.93 | 0.00 | 0.00 | 0.00 |
| May | 85.35 | 50.62 | 34.73 | 147.02 | 24.46 | 0.00 | 0.00 | 0.00 |
| June | 88.93 | 55.28 | 33.65 | 174.37 | 10.90 | 0.00 | 0.00 | 0.00 |
| July | 75.22 | 42.48 | 32.74 | 147.85 | 9.11 | 6.33 | 0.00 | 0.00 |
| August | 71.30 | 40.70 | 30.60 | 138.78 | 12.28 | 3.33 | 0.00 | 0.00 |
| September | 58.46 | 28.17 | 30.29 | 108.23 | 16.87 | 4.50 | 0.00 | 0.00 |
| October | 58.66 | 35.67 | 22.99 | 87.94 | 46.27 | 0.00 | 0.00 | 0.00 |
| November | 45.18 | 27.11 | 18.06 | 54.19 | 66.36 | 6.83 | 0.00 | 0.00 |
| December | 41.14 | 24.83 | 16.30 | 44.95 | 82.30 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 63.18 | 36.67 | 26.51 | 102.36 | 40.76 | 24.83 | 0.00 | 0.00 |
| Minimum of Months | 41.14 | 24.83 | 16.30 | 44.95 | 9.11 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 88.93 | 55.28 | 34.73 | 174.37 | 82.30 | 6.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MWINDOW14
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 15.76 | 9.92 | 5.85 | 18.56 | 24.85 | 310.17 | 0.00 | 0.00 |
| February | 15.49 | 8.86 | 6.63 | 16.13 | 25.36 | 396.17 | 0.00 | 0.00 |
| March | 19.31 | 9.91 | 9.41 | 23.54 | 21.47 | 249.17 | 0.00 | 0.00 |
| April | 27.66 | 16.50 | 11.16 | 45.02 | 11.45 | 98.17 | 0.00 | 0.00 |
| May | 28.66 | 17.00 | 11.66 | 50.27 | 7.75 | 36.00 | 0.00 | 0.00 |
| June | 29.86 | 18.56 | 11.30 | 61.24 | 3.00 | 15.00 | 0.00 | 0.00 |
| July | 25.26 | 14.26 | 10.99 | 52.43 | 2.34 | 97.67 | 0.00 | 0.00 |
| August | 23.94 | 13.67 | 10.27 | 49.06 | 3.19 | 177.83 | 0.00 | 0.00 |
| September | 19.63 | 9.46 | 10.17 | 38.25 | 4.60 | 188.17 | 0.00 | 0.00 |
| October | 19.70 | 11.98 | 7.72 | 29.87 | 15.27 | 188.50 | 0.00 | 0.00 |
| November | 15.17 | 9.10 | 6.07 | 17.65 | 23.14 | 330.17 | 0.00 | 0.00 |
| December | 13.81 | 8.34 | 5.47 | 14.18 | 29.51 | 455.67 | 0.00 | 0.00 |
| Annual Sum or Average | 21.21 | 12.31 | 8.90 | 34.77 | 14.28 | 2542.67 | 0.00 | 0.00 |
| Minimum of Months | 13.81 | 8.34 | 5.47 | 14.18 | 2.34 | 15.00 | 0.00 | 0.00 |
| Maximum of Months | 29.86 | 18.56 | 11.66 | 61.24 | 29.51 | 455.67 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: GWINDOW1 S SWA
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.674562E+09 | 0.537910E+09 | 0.136651E+09 | 0.104592E+10 | 0.379328E+09 |
| February | 0.392743E+09 | 0.266565E+09 | 0.126178E+09 | 0.551229E+09 | 0.315997E+09 |
| March | 0.341866E+09 | 0.168768E+09 | 0.173098E+09 | 0.522780E+09 | 0.315440E+09 |
| April | 0.305655E+09 | 0.130378E+09 | 0.175278E+09 | 0.597347E+09 | 0.173969E+09 |
| May | 0.203995E+09 | 34012954.60 | 0.169982E+09 | 0.448938E+09 | 0.119555E+09 |
| June | 0.169595E+09 | 13859625.08 | 0.155735E+09 | 0.510405E+09 | 40300901.09 |
| July | 0.177966E+09 | 18215448.15 | 0.159750E+09 | 0.513822E+09 | 30423167.23 |
| August | 0.218092E+09 | 61301923.89 | 0.156790E+09 | 0.582745E+09 | 41587779.72 |
| September | 0.302743E+09 | 0.129507E+09 | 0.173237E+09 | 0.668588E+09 | 63651043.63 |
| October | 0.497543E+09 | 0.344406E+09 | 0.153137E+09 | 0.852453E+09 | 0.236991E+09 |
| November | 0.567433E+09 | 0.436105E+09 | 0.131328E+09 | 0.860047E+09 | 0.346246E+09 |
| December | 0.629958E+09 | 0.498533E+09 | 0.131424E+09 | 0.925137E+09 | 0.461247E+09 |
| Annual Sum or Average | 0.448215E+10 | 0.263956E+10 | 0.184259E+10 | 0.807941E+10 | 0.252474E+10 |
| Minimum of Months | 0.169595E+09 | 13859625.08 | 0.126178E+09 | 0.448938E+09 | 30423167.23 |
| Maximum of Months | 0.674562E+09 | 0.537910E+09 | 0.175278E+09 | 0.104592E+10 | 0.461247E+09 |
Report: WindowEnergyReportMonthly
For: GWINDOW1 W SWA
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.184317E+09 | 0.114929E+09 | 69388377.30 | 0.262886E+09 | 0.272627E+09 |
| February | 0.133802E+09 | 64581883.73 | 69220085.41 | 0.156002E+09 | 0.222845E+09 |
| March | 0.197604E+09 | 94692714.42 | 0.102911E+09 | 0.275159E+09 | 0.208374E+09 |
| April | 0.291734E+09 | 0.166288E+09 | 0.125446E+09 | 0.514370E+09 | 0.113357E+09 |
| May | 0.302777E+09 | 0.169479E+09 | 0.133298E+09 | 0.575680E+09 | 78363607.64 |
| June | 0.311415E+09 | 0.183332E+09 | 0.128084E+09 | 0.682980E+09 | 27291990.21 |
| July | 0.234046E+09 | 0.109265E+09 | 0.124781E+09 | 0.535781E+09 | 20661820.50 |
| August | 0.223611E+09 | 0.112349E+09 | 0.111262E+09 | 0.501168E+09 | 28191339.81 |
| September | 0.188486E+09 | 79291333.81 | 0.109194E+09 | 0.397336E+09 | 42977539.76 |
| October | 0.198988E+09 | 0.113716E+09 | 85272415.21 | 0.327833E+09 | 0.166661E+09 |
| November | 0.176722E+09 | 0.106415E+09 | 70306517.52 | 0.243813E+09 | 0.248658E+09 |
| December | 0.147662E+09 | 84024867.93 | 63637399.90 | 0.183256E+09 | 0.334643E+09 |
| Annual Sum or Average | 0.259116E+10 | 0.139836E+10 | 0.119280E+10 | 0.465626E+10 | 0.176465E+10 |
| Minimum of Months | 0.133802E+09 | 64581883.73 | 63637399.90 | 0.156002E+09 | 20661820.50 |
| Maximum of Months | 0.311415E+09 | 0.183332E+09 | 0.133298E+09 | 0.682980E+09 | 0.334643E+09 |
Report: WindowEnergyReportMonthly
For: GWINDOW1 W NWA
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.184317E+09 | 0.114929E+09 | 69388377.30 | 0.277351E+09 | 0.244962E+09 |
| February | 0.133802E+09 | 64581883.73 | 69220085.41 | 0.167606E+09 | 0.200332E+09 |
| March | 0.197604E+09 | 94692714.42 | 0.102911E+09 | 0.286123E+09 | 0.195461E+09 |
| April | 0.291734E+09 | 0.166288E+09 | 0.125446E+09 | 0.518647E+09 | 0.110429E+09 |
| May | 0.302777E+09 | 0.169479E+09 | 0.133298E+09 | 0.576564E+09 | 78144891.92 |
| June | 0.311415E+09 | 0.183332E+09 | 0.128084E+09 | 0.682214E+09 | 27545804.25 |
| July | 0.234046E+09 | 0.109265E+09 | 0.124781E+09 | 0.535911E+09 | 20716220.52 |
| August | 0.223611E+09 | 0.112349E+09 | 0.111262E+09 | 0.503226E+09 | 27744124.75 |
| September | 0.188486E+09 | 79291333.81 | 0.109194E+09 | 0.400879E+09 | 41729107.46 |
| October | 0.198988E+09 | 0.113716E+09 | 85272415.21 | 0.334173E+09 | 0.160603E+09 |
| November | 0.176722E+09 | 0.106415E+09 | 70306517.52 | 0.251746E+09 | 0.234024E+09 |
| December | 0.147662E+09 | 84024867.93 | 63637399.90 | 0.196230E+09 | 0.303867E+09 |
| Annual Sum or Average | 0.259116E+10 | 0.139836E+10 | 0.119280E+10 | 0.473067E+10 | 0.164556E+10 |
| Minimum of Months | 0.133802E+09 | 64581883.73 | 63637399.90 | 0.167606E+09 | 20716220.52 |
| Maximum of Months | 0.311415E+09 | 0.183332E+09 | 0.133298E+09 | 0.682214E+09 | 0.303867E+09 |
Report: WindowEnergyReportMonthly
For: GWINDOW1 N NWA
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 82402469.07 | 0.00 | 82402469.07 | 66637376.27 | 0.377815E+09 |
| February | 84808934.39 | 0.00 | 84808934.39 | 49652080.80 | 0.311593E+09 |
| March | 0.124821E+09 | 14118.42 | 0.124807E+09 | 0.133129E+09 | 0.304775E+09 |
| April | 0.147612E+09 | 1954846.33 | 0.145657E+09 | 0.258015E+09 | 0.165074E+09 |
| May | 0.179632E+09 | 15557674.50 | 0.164074E+09 | 0.369681E+09 | 0.107521E+09 |
| June | 0.199389E+09 | 35681652.83 | 0.163707E+09 | 0.559977E+09 | 37512495.50 |
| July | 0.175831E+09 | 17826399.52 | 0.158005E+09 | 0.498120E+09 | 29281216.31 |
| August | 0.142811E+09 | 3828713.07 | 0.138982E+09 | 0.407951E+09 | 40686438.23 |
| September | 0.130054E+09 | 77369.33 | 0.129977E+09 | 0.324854E+09 | 63600510.14 |
| October | 0.103920E+09 | 0.00 | 0.103920E+09 | 0.153261E+09 | 0.248806E+09 |
| November | 83791828.16 | 0.00 | 83791828.16 | 56811414.41 | 0.363188E+09 |
| December | 76971515.23 | 0.00 | 76971515.23 | 36339646.97 | 0.471778E+09 |
| Annual Sum or Average | 0.153204E+10 | 74940774.01 | 0.145710E+10 | 0.291443E+10 | 0.252163E+10 |
| Minimum of Months | 76971515.23 | 0.00 | 76971515.23 | 36339646.97 | 29281216.31 |
| Maximum of Months | 0.199389E+09 | 35681652.83 | 0.164074E+09 | 0.559977E+09 | 0.471778E+09 |
Report: WindowEnergyReportMonthly
For: GWINDOW1 S SEA
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.674562E+09 | 0.537910E+09 | 0.136651E+09 | 0.103259E+10 | 0.407498E+09 |
| February | 0.392743E+09 | 0.266565E+09 | 0.126178E+09 | 0.541653E+09 | 0.341057E+09 |
| March | 0.341866E+09 | 0.168768E+09 | 0.173098E+09 | 0.506396E+09 | 0.344939E+09 |
| April | 0.305655E+09 | 0.130378E+09 | 0.175278E+09 | 0.562018E+09 | 0.226741E+09 |
| May | 0.203995E+09 | 34012954.60 | 0.169982E+09 | 0.402151E+09 | 0.178292E+09 |
| June | 0.169595E+09 | 13859625.08 | 0.155735E+09 | 0.434901E+09 | 87189963.36 |
| July | 0.177966E+09 | 18215448.15 | 0.159750E+09 | 0.427079E+09 | 80028096.49 |
| August | 0.218092E+09 | 61301923.89 | 0.156790E+09 | 0.515877E+09 | 0.102275E+09 |
| September | 0.302743E+09 | 0.129507E+09 | 0.173237E+09 | 0.610369E+09 | 0.132971E+09 |
| October | 0.497543E+09 | 0.344406E+09 | 0.153137E+09 | 0.815790E+09 | 0.301614E+09 |
| November | 0.567433E+09 | 0.436105E+09 | 0.131328E+09 | 0.844853E+09 | 0.385145E+09 |
| December | 0.629958E+09 | 0.498533E+09 | 0.131424E+09 | 0.912513E+09 | 0.488513E+09 |
| Annual Sum or Average | 0.448215E+10 | 0.263956E+10 | 0.184259E+10 | 0.760620E+10 | 0.307626E+10 |
| Minimum of Months | 0.169595E+09 | 13859625.08 | 0.126178E+09 | 0.402151E+09 | 80028096.49 |
| Maximum of Months | 0.674562E+09 | 0.537910E+09 | 0.175278E+09 | 0.103259E+10 | 0.488513E+09 |
Report: WindowEnergyReportMonthly
For: GWINDOW1 E SEA
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.175948E+09 | 0.110679E+09 | 65268692.49 | 0.212729E+09 | 0.270860E+09 |
| February | 0.156127E+09 | 89319636.19 | 66807077.55 | 0.174855E+09 | 0.227963E+09 |
| March | 0.215568E+09 | 0.110588E+09 | 0.104980E+09 | 0.281866E+09 | 0.215446E+09 |
| April | 0.298731E+09 | 0.178199E+09 | 0.120533E+09 | 0.487571E+09 | 0.134673E+09 |
| May | 0.319881E+09 | 0.189712E+09 | 0.130170E+09 | 0.557360E+09 | 0.103484E+09 |
| June | 0.322564E+09 | 0.200503E+09 | 0.122061E+09 | 0.643668E+09 | 50561790.03 |
| July | 0.281915E+09 | 0.159217E+09 | 0.122698E+09 | 0.557463E+09 | 47770598.31 |
| August | 0.267225E+09 | 0.152538E+09 | 0.114687E+09 | 0.527773E+09 | 62682588.14 |
| September | 0.212018E+09 | 0.102165E+09 | 0.109853E+09 | 0.392730E+09 | 81899438.15 |
| October | 0.219841E+09 | 0.133694E+09 | 86146584.38 | 0.325350E+09 | 0.196247E+09 |
| November | 0.163854E+09 | 98334421.63 | 65519182.01 | 0.191836E+09 | 0.258507E+09 |
| December | 0.154182E+09 | 93073405.93 | 61108263.85 | 0.158517E+09 | 0.329834E+09 |
| Annual Sum or Average | 0.278785E+10 | 0.161802E+10 | 0.116983E+10 | 0.451172E+10 | 0.197993E+10 |
| Minimum of Months | 0.154182E+09 | 89319636.19 | 61108263.85 | 0.158517E+09 | 47770598.31 |
| Maximum of Months | 0.322564E+09 | 0.200503E+09 | 0.130170E+09 | 0.643668E+09 | 0.329834E+09 |
Report: WindowEnergyReportMonthly
For: GWINDOW1 E NEA
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.175948E+09 | 0.110679E+09 | 65268692.49 | 0.236733E+09 | 0.224411E+09 |
| February | 0.156127E+09 | 89319636.19 | 66807077.55 | 0.190987E+09 | 0.189240E+09 |
| March | 0.215568E+09 | 0.110588E+09 | 0.104980E+09 | 0.301866E+09 | 0.183594E+09 |
| April | 0.298731E+09 | 0.178199E+09 | 0.120533E+09 | 0.517016E+09 | 0.100319E+09 |
| May | 0.319881E+09 | 0.189712E+09 | 0.130170E+09 | 0.592891E+09 | 68797507.15 |
| June | 0.322564E+09 | 0.200503E+09 | 0.122061E+09 | 0.695729E+09 | 23410932.72 |
| July | 0.281915E+09 | 0.159217E+09 | 0.122698E+09 | 0.617280E+09 | 18087867.45 |
| August | 0.267225E+09 | 0.152538E+09 | 0.114687E+09 | 0.576113E+09 | 25178337.83 |
| September | 0.212018E+09 | 0.102165E+09 | 0.109853E+09 | 0.437464E+09 | 38128296.83 |
| October | 0.219841E+09 | 0.133694E+09 | 86146584.38 | 0.354770E+09 | 0.148095E+09 |
| November | 0.163854E+09 | 98334421.63 | 65519182.01 | 0.208411E+09 | 0.216855E+09 |
| December | 0.154182E+09 | 93073405.93 | 61108263.85 | 0.178539E+09 | 0.280892E+09 |
| Annual Sum or Average | 0.278785E+10 | 0.161802E+10 | 0.116983E+10 | 0.490780E+10 | 0.151701E+10 |
| Minimum of Months | 0.154182E+09 | 89319636.19 | 61108263.85 | 0.178539E+09 | 18087867.45 |
| Maximum of Months | 0.322564E+09 | 0.200503E+09 | 0.130170E+09 | 0.695729E+09 | 0.280892E+09 |
Report: WindowEnergyReportMonthly
For: GWINDOW1 N NEA
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 82402469.07 | 0.00 | 82402469.07 | 65201100.52 | 0.376032E+09 |
| February | 84808934.39 | 0.00 | 84808934.39 | 47564008.92 | 0.312723E+09 |
| March | 0.124821E+09 | 14118.42 | 0.124807E+09 | 0.130185E+09 | 0.304922E+09 |
| April | 0.147612E+09 | 1954846.33 | 0.145657E+09 | 0.256136E+09 | 0.164582E+09 |
| May | 0.179632E+09 | 15557674.50 | 0.164074E+09 | 0.367785E+09 | 0.106835E+09 |
| June | 0.199389E+09 | 35681652.83 | 0.163707E+09 | 0.558746E+09 | 37132285.48 |
| July | 0.175831E+09 | 17826399.52 | 0.158005E+09 | 0.496178E+09 | 29196916.02 |
| August | 0.142811E+09 | 3828713.07 | 0.138982E+09 | 0.406201E+09 | 40716067.06 |
| September | 0.130054E+09 | 77369.33 | 0.129977E+09 | 0.323826E+09 | 63527290.25 |
| October | 0.103920E+09 | 0.00 | 0.103920E+09 | 0.151683E+09 | 0.249100E+09 |
| November | 83791828.16 | 0.00 | 83791828.16 | 55917734.23 | 0.362207E+09 |
| December | 76971515.23 | 0.00 | 76971515.23 | 35075353.33 | 0.471998E+09 |
| Annual Sum or Average | 0.153204E+10 | 74940774.01 | 0.145710E+10 | 0.289450E+10 | 0.251897E+10 |
| Minimum of Months | 76971515.23 | 0.00 | 76971515.23 | 35075353.33 | 29196916.02 |
| Maximum of Months | 0.199389E+09 | 35681652.83 | 0.164074E+09 | 0.558746E+09 | 0.471998E+09 |
Report: WindowEnergyReportMonthly
For: GWINDOW1 N N1A
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 82402469.07 | 0.00 | 82402469.07 | 64318226.95 | 0.388205E+09 |
| February | 84808934.39 | 0.00 | 84808934.39 | 46373965.60 | 0.326475E+09 |
| March | 0.124821E+09 | 14118.42 | 0.124807E+09 | 0.128952E+09 | 0.315791E+09 |
| April | 0.147612E+09 | 1954846.33 | 0.145657E+09 | 0.260741E+09 | 0.165238E+09 |
| May | 0.179632E+09 | 15557674.50 | 0.164074E+09 | 0.373633E+09 | 0.106619E+09 |
| June | 0.199389E+09 | 35681652.83 | 0.163707E+09 | 0.568204E+09 | 36263979.42 |
| July | 0.175831E+09 | 17826399.52 | 0.158005E+09 | 0.506384E+09 | 27952620.50 |
| August | 0.142811E+09 | 3828713.07 | 0.138982E+09 | 0.415933E+09 | 38828609.68 |
| September | 0.130054E+09 | 77369.33 | 0.129977E+09 | 0.331390E+09 | 61143478.49 |
| October | 0.103920E+09 | 0.00 | 0.103920E+09 | 0.155709E+09 | 0.248961E+09 |
| November | 83791828.16 | 0.00 | 83791828.16 | 56517651.58 | 0.368537E+09 |
| December | 76971515.23 | 0.00 | 76971515.23 | 34934118.31 | 0.482442E+09 |
| Annual Sum or Average | 0.153204E+10 | 74940774.01 | 0.145710E+10 | 0.294309E+10 | 0.256646E+10 |
| Minimum of Months | 76971515.23 | 0.00 | 76971515.23 | 34934118.31 | 27952620.50 |
| Maximum of Months | 0.199389E+09 | 35681652.83 | 0.164074E+09 | 0.568204E+09 | 0.482442E+09 |
Report: WindowEnergyReportMonthly
For: GWINDOW1 N N2A
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 82402469.07 | 0.00 | 82402469.07 | 64264720.81 | 0.388054E+09 |
| February | 84808934.39 | 0.00 | 84808934.39 | 46204796.51 | 0.326781E+09 |
| March | 0.124821E+09 | 14118.42 | 0.124807E+09 | 0.128734E+09 | 0.315989E+09 |
| April | 0.147612E+09 | 1954846.33 | 0.145657E+09 | 0.260641E+09 | 0.165246E+09 |
| May | 0.179632E+09 | 15557674.50 | 0.164074E+09 | 0.373556E+09 | 0.106607E+09 |
| June | 0.199389E+09 | 35681652.83 | 0.163707E+09 | 0.568153E+09 | 36255190.88 |
| July | 0.175831E+09 | 17826399.52 | 0.158005E+09 | 0.506302E+09 | 27955454.46 |
| August | 0.142811E+09 | 3828713.07 | 0.138982E+09 | 0.415860E+09 | 38839562.19 |
| September | 0.130054E+09 | 77369.33 | 0.129977E+09 | 0.331347E+09 | 61146602.74 |
| October | 0.103920E+09 | 0.00 | 0.103920E+09 | 0.155630E+09 | 0.249019E+09 |
| November | 83791828.16 | 0.00 | 83791828.16 | 56477885.60 | 0.368465E+09 |
| December | 76971515.23 | 0.00 | 76971515.23 | 34854486.52 | 0.482559E+09 |
| Annual Sum or Average | 0.153204E+10 | 74940774.01 | 0.145710E+10 | 0.294203E+10 | 0.256692E+10 |
| Minimum of Months | 76971515.23 | 0.00 | 76971515.23 | 34854486.52 | 27955454.46 |
| Maximum of Months | 0.199389E+09 | 35681652.83 | 0.164074E+09 | 0.568153E+09 | 0.482559E+09 |
Report: WindowEnergyReportMonthly
For: GWINDOW1 S S1A
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.674562E+09 | 0.537910E+09 | 0.136651E+09 | 0.104114E+10 | 0.389514E+09 |
| February | 0.392743E+09 | 0.266565E+09 | 0.126178E+09 | 0.542801E+09 | 0.336872E+09 |
| March | 0.341866E+09 | 0.168768E+09 | 0.173098E+09 | 0.514874E+09 | 0.331134E+09 |
| April | 0.305655E+09 | 0.130378E+09 | 0.175278E+09 | 0.599454E+09 | 0.174385E+09 |
| May | 0.203995E+09 | 34012954.60 | 0.169982E+09 | 0.452832E+09 | 0.118910E+09 |
| June | 0.169595E+09 | 13859625.08 | 0.155735E+09 | 0.518628E+09 | 39059077.53 |
| July | 0.177966E+09 | 18215448.15 | 0.159750E+09 | 0.521911E+09 | 29148664.43 |
| August | 0.218092E+09 | 61301923.89 | 0.156790E+09 | 0.590305E+09 | 39855027.03 |
| September | 0.302743E+09 | 0.129507E+09 | 0.173237E+09 | 0.674488E+09 | 61395360.47 |
| October | 0.497543E+09 | 0.344406E+09 | 0.153137E+09 | 0.854369E+09 | 0.236876E+09 |
| November | 0.567433E+09 | 0.436105E+09 | 0.131328E+09 | 0.858991E+09 | 0.349884E+09 |
| December | 0.629958E+09 | 0.498533E+09 | 0.131424E+09 | 0.919381E+09 | 0.474255E+09 |
| Annual Sum or Average | 0.448215E+10 | 0.263956E+10 | 0.184259E+10 | 0.808917E+10 | 0.258129E+10 |
| Minimum of Months | 0.169595E+09 | 13859625.08 | 0.126178E+09 | 0.452832E+09 | 29148664.43 |
| Maximum of Months | 0.674562E+09 | 0.537910E+09 | 0.175278E+09 | 0.104114E+10 | 0.474255E+09 |
Report: WindowEnergyReportMonthly
For: GWINDOW1 S S2A
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.674562E+09 | 0.537910E+09 | 0.136651E+09 | 0.104034E+10 | 0.390748E+09 |
| February | 0.392743E+09 | 0.266565E+09 | 0.126178E+09 | 0.541501E+09 | 0.339673E+09 |
| March | 0.341866E+09 | 0.168768E+09 | 0.173098E+09 | 0.513081E+09 | 0.333838E+09 |
| April | 0.305655E+09 | 0.130378E+09 | 0.175278E+09 | 0.597631E+09 | 0.176454E+09 |
| May | 0.203995E+09 | 34012954.60 | 0.169982E+09 | 0.450327E+09 | 0.121037E+09 |
| June | 0.169595E+09 | 13859625.08 | 0.155735E+09 | 0.514966E+09 | 40500635.29 |
| July | 0.177966E+09 | 18215448.15 | 0.159750E+09 | 0.517811E+09 | 30526060.52 |
| August | 0.218092E+09 | 61301923.89 | 0.156790E+09 | 0.586883E+09 | 41645465.16 |
| September | 0.302743E+09 | 0.129507E+09 | 0.173237E+09 | 0.671636E+09 | 63612948.82 |
| October | 0.497543E+09 | 0.344406E+09 | 0.153137E+09 | 0.852542E+09 | 0.239138E+09 |
| November | 0.567433E+09 | 0.436105E+09 | 0.131328E+09 | 0.858050E+09 | 0.351423E+09 |
| December | 0.629958E+09 | 0.498533E+09 | 0.131424E+09 | 0.918443E+09 | 0.475897E+09 |
| Annual Sum or Average | 0.448215E+10 | 0.263956E+10 | 0.184259E+10 | 0.806321E+10 | 0.260449E+10 |
| Minimum of Months | 0.169595E+09 | 13859625.08 | 0.126178E+09 | 0.450327E+09 | 30526060.52 |
| Maximum of Months | 0.674562E+09 | 0.537910E+09 | 0.175278E+09 | 0.104034E+10 | 0.475897E+09 |
Report: WindowEnergyReportMonthly
For: MWINDOW1 S SWA
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.674562E+09 | 0.537910E+09 | 0.136651E+09 | 0.103733E+10 | 0.385103E+09 |
| February | 0.392743E+09 | 0.266565E+09 | 0.126178E+09 | 0.534959E+09 | 0.346114E+09 |
| March | 0.341866E+09 | 0.168768E+09 | 0.173098E+09 | 0.503891E+09 | 0.343608E+09 |
| April | 0.305655E+09 | 0.130378E+09 | 0.175278E+09 | 0.591444E+09 | 0.178101E+09 |
| May | 0.203995E+09 | 34012954.60 | 0.169982E+09 | 0.445743E+09 | 0.121645E+09 |
| June | 0.169595E+09 | 13859625.08 | 0.155735E+09 | 0.512604E+09 | 39651171.16 |
| July | 0.177966E+09 | 18215448.15 | 0.159750E+09 | 0.520551E+09 | 28233904.71 |
| August | 0.218092E+09 | 61301923.89 | 0.156790E+09 | 0.589907E+09 | 37719313.16 |
| September | 0.302743E+09 | 0.129507E+09 | 0.173237E+09 | 0.674932E+09 | 57254673.13 |
| October | 0.497543E+09 | 0.344406E+09 | 0.153137E+09 | 0.853579E+09 | 0.229848E+09 |
| November | 0.567433E+09 | 0.436105E+09 | 0.131328E+09 | 0.859456E+09 | 0.339436E+09 |
| December | 0.629958E+09 | 0.498533E+09 | 0.131424E+09 | 0.923347E+09 | 0.456970E+09 |
| Annual Sum or Average | 0.448215E+10 | 0.263956E+10 | 0.184259E+10 | 0.804774E+10 | 0.256368E+10 |
| Minimum of Months | 0.169595E+09 | 13859625.08 | 0.126178E+09 | 0.445743E+09 | 28233904.71 |
| Maximum of Months | 0.674562E+09 | 0.537910E+09 | 0.175278E+09 | 0.103733E+10 | 0.456970E+09 |
Report: WindowEnergyReportMonthly
For: MWINDOW1 W SWA
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.184317E+09 | 0.114929E+09 | 69388377.30 | 0.259818E+09 | 0.276799E+09 |
| February | 0.133802E+09 | 64581883.73 | 69220085.41 | 0.148447E+09 | 0.244577E+09 |
| March | 0.197604E+09 | 94692714.42 | 0.102911E+09 | 0.263727E+09 | 0.226973E+09 |
| April | 0.291734E+09 | 0.166288E+09 | 0.125446E+09 | 0.510022E+09 | 0.116092E+09 |
| May | 0.302777E+09 | 0.169479E+09 | 0.133298E+09 | 0.572172E+09 | 79810812.32 |
| June | 0.311415E+09 | 0.183332E+09 | 0.128084E+09 | 0.682696E+09 | 27022560.56 |
| July | 0.234046E+09 | 0.109265E+09 | 0.124781E+09 | 0.539255E+09 | 19351235.51 |
| August | 0.223611E+09 | 0.112349E+09 | 0.111262E+09 | 0.505482E+09 | 25854721.66 |
| September | 0.188486E+09 | 79291333.81 | 0.109194E+09 | 0.401843E+09 | 39014219.65 |
| October | 0.198988E+09 | 0.113716E+09 | 85272415.21 | 0.329406E+09 | 0.161607E+09 |
| November | 0.176722E+09 | 0.106415E+09 | 70306517.52 | 0.243869E+09 | 0.243180E+09 |
| December | 0.147662E+09 | 84024867.93 | 63637399.90 | 0.182669E+09 | 0.330683E+09 |
| Annual Sum or Average | 0.259116E+10 | 0.139836E+10 | 0.119280E+10 | 0.463940E+10 | 0.179096E+10 |
| Minimum of Months | 0.133802E+09 | 64581883.73 | 63637399.90 | 0.148447E+09 | 19351235.51 |
| Maximum of Months | 0.311415E+09 | 0.183332E+09 | 0.133298E+09 | 0.682696E+09 | 0.330683E+09 |
Report: WindowEnergyReportMonthly
For: MWINDOW1 W NWA
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.184317E+09 | 0.114929E+09 | 69388377.30 | 0.272026E+09 | 0.256337E+09 |
| February | 0.133802E+09 | 64581883.73 | 69220085.41 | 0.158272E+09 | 0.223928E+09 |
| March | 0.197604E+09 | 94692714.42 | 0.102911E+09 | 0.271397E+09 | 0.218114E+09 |
| April | 0.291734E+09 | 0.166288E+09 | 0.125446E+09 | 0.513379E+09 | 0.114366E+09 |
| May | 0.302777E+09 | 0.169479E+09 | 0.133298E+09 | 0.572940E+09 | 79699176.86 |
| June | 0.311415E+09 | 0.183332E+09 | 0.128084E+09 | 0.682122E+09 | 27191054.62 |
| July | 0.234046E+09 | 0.109265E+09 | 0.124781E+09 | 0.539463E+09 | 19370740.04 |
| August | 0.223611E+09 | 0.112349E+09 | 0.111262E+09 | 0.507389E+09 | 25520481.74 |
| September | 0.188486E+09 | 79291333.81 | 0.109194E+09 | 0.405211E+09 | 38086593.42 |
| October | 0.198988E+09 | 0.113716E+09 | 85272415.21 | 0.336275E+09 | 0.155396E+09 |
| November | 0.176722E+09 | 0.106415E+09 | 70306517.52 | 0.253171E+09 | 0.227119E+09 |
| December | 0.147662E+09 | 84024867.93 | 63637399.90 | 0.196465E+09 | 0.301788E+09 |
| Annual Sum or Average | 0.259116E+10 | 0.139836E+10 | 0.119280E+10 | 0.470811E+10 | 0.168692E+10 |
| Minimum of Months | 0.133802E+09 | 64581883.73 | 63637399.90 | 0.158272E+09 | 19370740.04 |
| Maximum of Months | 0.311415E+09 | 0.183332E+09 | 0.133298E+09 | 0.682122E+09 | 0.301788E+09 |
Report: WindowEnergyReportMonthly
For: MWINDOW1 N NWA
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 82402469.07 | 0.00 | 82402469.07 | 61285155.21 | 0.395465E+09 |
| February | 84808934.39 | 0.00 | 84808934.39 | 39098797.18 | 0.349157E+09 |
| March | 0.124821E+09 | 14118.42 | 0.124807E+09 | 0.115436E+09 | 0.341379E+09 |
| April | 0.147612E+09 | 1954846.33 | 0.145657E+09 | 0.253088E+09 | 0.171044E+09 |
| May | 0.179632E+09 | 15557674.50 | 0.164074E+09 | 0.366337E+09 | 0.109613E+09 |
| June | 0.199389E+09 | 35681652.83 | 0.163707E+09 | 0.561919E+09 | 37039897.08 |
| July | 0.175831E+09 | 17826399.52 | 0.158005E+09 | 0.504987E+09 | 27318682.35 |
| August | 0.142811E+09 | 3828713.07 | 0.138982E+09 | 0.415834E+09 | 37361422.29 |
| September | 0.130054E+09 | 77369.33 | 0.129977E+09 | 0.333105E+09 | 58002688.93 |
| October | 0.103920E+09 | 0.00 | 0.103920E+09 | 0.158311E+09 | 0.240237E+09 |
| November | 83791828.16 | 0.00 | 83791828.16 | 60373300.25 | 0.351556E+09 |
| December | 76971515.23 | 0.00 | 76971515.23 | 37729525.83 | 0.467569E+09 |
| Annual Sum or Average | 0.153204E+10 | 74940774.01 | 0.145710E+10 | 0.290750E+10 | 0.258574E+10 |
| Minimum of Months | 76971515.23 | 0.00 | 76971515.23 | 37729525.83 | 27318682.35 |
| Maximum of Months | 0.199389E+09 | 35681652.83 | 0.164074E+09 | 0.561919E+09 | 0.467569E+09 |
Report: WindowEnergyReportMonthly
For: MWINDOW1 S SEA
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.674562E+09 | 0.537910E+09 | 0.136651E+09 | 0.103557E+10 | 0.383586E+09 |
| February | 0.392743E+09 | 0.266565E+09 | 0.126178E+09 | 0.532418E+09 | 0.346179E+09 |
| March | 0.341866E+09 | 0.168768E+09 | 0.173098E+09 | 0.500618E+09 | 0.343384E+09 |
| April | 0.305655E+09 | 0.130378E+09 | 0.175278E+09 | 0.589813E+09 | 0.177288E+09 |
| May | 0.203995E+09 | 34012954.60 | 0.169982E+09 | 0.444205E+09 | 0.121059E+09 |
| June | 0.169595E+09 | 13859625.08 | 0.155735E+09 | 0.511461E+09 | 39298251.68 |
| July | 0.177966E+09 | 18215448.15 | 0.159750E+09 | 0.518824E+09 | 28127571.47 |
| August | 0.218092E+09 | 61301923.89 | 0.156790E+09 | 0.588349E+09 | 37682456.05 |
| September | 0.302743E+09 | 0.129507E+09 | 0.173237E+09 | 0.673931E+09 | 57084179.52 |
| October | 0.497543E+09 | 0.344406E+09 | 0.153137E+09 | 0.851643E+09 | 0.229217E+09 |
| November | 0.567433E+09 | 0.436105E+09 | 0.131328E+09 | 0.857968E+09 | 0.338030E+09 |
| December | 0.629958E+09 | 0.498533E+09 | 0.131424E+09 | 0.920703E+09 | 0.456379E+09 |
| Annual Sum or Average | 0.448215E+10 | 0.263956E+10 | 0.184259E+10 | 0.802550E+10 | 0.255731E+10 |
| Minimum of Months | 0.169595E+09 | 13859625.08 | 0.126178E+09 | 0.444205E+09 | 28127571.47 |
| Maximum of Months | 0.674562E+09 | 0.537910E+09 | 0.175278E+09 | 0.103557E+10 | 0.456379E+09 |
Report: WindowEnergyReportMonthly
For: MWINDOW1 E SEA
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.175948E+09 | 0.110679E+09 | 65268692.49 | 0.215301E+09 | 0.254443E+09 |
| February | 0.156127E+09 | 89319636.19 | 66807077.55 | 0.169682E+09 | 0.231581E+09 |
| March | 0.215568E+09 | 0.110588E+09 | 0.104980E+09 | 0.277620E+09 | 0.213893E+09 |
| April | 0.298731E+09 | 0.178199E+09 | 0.120533E+09 | 0.508036E+09 | 0.105249E+09 |
| May | 0.319881E+09 | 0.189712E+09 | 0.130170E+09 | 0.588175E+09 | 70202762.87 |
| June | 0.322564E+09 | 0.200503E+09 | 0.122061E+09 | 0.695955E+09 | 22845609.74 |
| July | 0.281915E+09 | 0.159217E+09 | 0.122698E+09 | 0.620346E+09 | 16705828.50 |
| August | 0.267225E+09 | 0.152538E+09 | 0.114687E+09 | 0.578005E+09 | 23196074.83 |
| September | 0.212018E+09 | 0.102165E+09 | 0.109853E+09 | 0.438384E+09 | 35407065.57 |
| October | 0.219841E+09 | 0.133694E+09 | 86146584.38 | 0.350020E+09 | 0.148981E+09 |
| November | 0.163854E+09 | 98334421.63 | 65519182.01 | 0.200053E+09 | 0.225857E+09 |
| December | 0.154182E+09 | 93073405.93 | 61108263.85 | 0.163940E+09 | 0.307814E+09 |
| Annual Sum or Average | 0.278785E+10 | 0.161802E+10 | 0.116983E+10 | 0.480552E+10 | 0.165618E+10 |
| Minimum of Months | 0.154182E+09 | 89319636.19 | 61108263.85 | 0.163940E+09 | 16705828.50 |
| Maximum of Months | 0.322564E+09 | 0.200503E+09 | 0.130170E+09 | 0.695955E+09 | 0.307814E+09 |
Report: WindowEnergyReportMonthly
For: MWINDOW1 E NEA
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.175948E+09 | 0.110679E+09 | 65268692.49 | 0.229659E+09 | 0.235345E+09 |
| February | 0.156127E+09 | 89319636.19 | 66807077.55 | 0.179634E+09 | 0.212275E+09 |
| March | 0.215568E+09 | 0.110588E+09 | 0.104980E+09 | 0.285307E+09 | 0.205403E+09 |
| April | 0.298731E+09 | 0.178199E+09 | 0.120533E+09 | 0.511394E+09 | 0.103651E+09 |
| May | 0.319881E+09 | 0.189712E+09 | 0.130170E+09 | 0.588911E+09 | 70027571.93 |
| June | 0.322564E+09 | 0.200503E+09 | 0.122061E+09 | 0.695372E+09 | 22960067.32 |
| July | 0.281915E+09 | 0.159217E+09 | 0.122698E+09 | 0.620552E+09 | 16706027.74 |
| August | 0.267225E+09 | 0.152538E+09 | 0.114687E+09 | 0.579904E+09 | 22863117.08 |
| September | 0.212018E+09 | 0.102165E+09 | 0.109853E+09 | 0.441786E+09 | 34512031.90 |
| October | 0.219841E+09 | 0.133694E+09 | 86146584.38 | 0.357029E+09 | 0.143467E+09 |
| November | 0.163854E+09 | 98334421.63 | 65519182.01 | 0.210597E+09 | 0.210879E+09 |
| December | 0.154182E+09 | 93073405.93 | 61108263.85 | 0.178766E+09 | 0.279170E+09 |
| Annual Sum or Average | 0.278785E+10 | 0.161802E+10 | 0.116983E+10 | 0.487891E+10 | 0.155726E+10 |
| Minimum of Months | 0.154182E+09 | 89319636.19 | 61108263.85 | 0.178766E+09 | 16706027.74 |
| Maximum of Months | 0.322564E+09 | 0.200503E+09 | 0.130170E+09 | 0.695372E+09 | 0.279170E+09 |
Report: WindowEnergyReportMonthly
For: MWINDOW1 N NEA
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 82402469.07 | 0.00 | 82402469.07 | 59398489.22 | 0.394045E+09 |
| February | 84808934.39 | 0.00 | 84808934.39 | 36447234.97 | 0.351360E+09 |
| March | 0.124821E+09 | 14118.42 | 0.124807E+09 | 0.112178E+09 | 0.341832E+09 |
| April | 0.147612E+09 | 1954846.33 | 0.145657E+09 | 0.251424E+09 | 0.170417E+09 |
| May | 0.179632E+09 | 15557674.50 | 0.164074E+09 | 0.364505E+09 | 0.108781E+09 |
| June | 0.199389E+09 | 35681652.83 | 0.163707E+09 | 0.560757E+09 | 36607016.87 |
| July | 0.175831E+09 | 17826399.52 | 0.158005E+09 | 0.503213E+09 | 27162785.10 |
| August | 0.142811E+09 | 3828713.07 | 0.138982E+09 | 0.414187E+09 | 37279273.53 |
| September | 0.130054E+09 | 77369.33 | 0.129977E+09 | 0.332082E+09 | 57860022.15 |
| October | 0.103920E+09 | 0.00 | 0.103920E+09 | 0.156283E+09 | 0.240668E+09 |
| November | 83791828.16 | 0.00 | 83791828.16 | 58961878.97 | 0.350455E+09 |
| December | 76971515.23 | 0.00 | 76971515.23 | 36153081.80 | 0.467351E+09 |
| Annual Sum or Average | 0.153204E+10 | 74940774.01 | 0.145710E+10 | 0.288559E+10 | 0.258382E+10 |
| Minimum of Months | 76971515.23 | 0.00 | 76971515.23 | 36153081.80 | 27162785.10 |
| Maximum of Months | 0.199389E+09 | 35681652.83 | 0.164074E+09 | 0.560757E+09 | 0.467351E+09 |
Report: WindowEnergyReportMonthly
For: MWINDOW1 N N1A
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 82402469.07 | 0.00 | 82402469.07 | 58611904.15 | 0.407570E+09 |
| February | 84808934.39 | 0.00 | 84808934.39 | 35380907.12 | 0.368421E+09 |
| March | 0.124821E+09 | 14118.42 | 0.124807E+09 | 0.112440E+09 | 0.352091E+09 |
| April | 0.147612E+09 | 1954846.33 | 0.145657E+09 | 0.257216E+09 | 0.169923E+09 |
| May | 0.179632E+09 | 15557674.50 | 0.164074E+09 | 0.372234E+09 | 0.107618E+09 |
| June | 0.199389E+09 | 35681652.83 | 0.163707E+09 | 0.571316E+09 | 35551491.65 |
| July | 0.175831E+09 | 17826399.52 | 0.158005E+09 | 0.513013E+09 | 26244127.65 |
| August | 0.142811E+09 | 3828713.07 | 0.138982E+09 | 0.423060E+09 | 36127362.98 |
| September | 0.130054E+09 | 77369.33 | 0.129977E+09 | 0.338317E+09 | 56762870.53 |
| October | 0.103920E+09 | 0.00 | 0.103920E+09 | 0.159344E+09 | 0.243789E+09 |
| November | 83791828.16 | 0.00 | 83791828.16 | 58496687.36 | 0.362233E+09 |
| December | 76971515.23 | 0.00 | 76971515.23 | 34982616.01 | 0.482855E+09 |
| Annual Sum or Average | 0.153204E+10 | 74940774.01 | 0.145710E+10 | 0.293441E+10 | 0.264919E+10 |
| Minimum of Months | 76971515.23 | 0.00 | 76971515.23 | 34982616.01 | 26244127.65 |
| Maximum of Months | 0.199389E+09 | 35681652.83 | 0.164074E+09 | 0.571316E+09 | 0.482855E+09 |
Report: WindowEnergyReportMonthly
For: MWINDOW1 N N2A
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 82402469.07 | 0.00 | 82402469.07 | 58514346.20 | 0.407485E+09 |
| February | 84808934.39 | 0.00 | 84808934.39 | 35157054.16 | 0.368882E+09 |
| March | 0.124821E+09 | 14118.42 | 0.124807E+09 | 0.112214E+09 | 0.352307E+09 |
| April | 0.147612E+09 | 1954846.33 | 0.145657E+09 | 0.257135E+09 | 0.169912E+09 |
| May | 0.179632E+09 | 15557674.50 | 0.164074E+09 | 0.372167E+09 | 0.107596E+09 |
| June | 0.199389E+09 | 35681652.83 | 0.163707E+09 | 0.571271E+09 | 35538323.13 |
| July | 0.175831E+09 | 17826399.52 | 0.158005E+09 | 0.512947E+09 | 26242326.81 |
| August | 0.142811E+09 | 3828713.07 | 0.138982E+09 | 0.422998E+09 | 36130353.68 |
| September | 0.130054E+09 | 77369.33 | 0.129977E+09 | 0.338276E+09 | 56759982.58 |
| October | 0.103920E+09 | 0.00 | 0.103920E+09 | 0.159227E+09 | 0.243887E+09 |
| November | 83791828.16 | 0.00 | 83791828.16 | 58423878.03 | 0.362162E+09 |
| December | 76971515.23 | 0.00 | 76971515.23 | 34886619.33 | 0.482938E+09 |
| Annual Sum or Average | 0.153204E+10 | 74940774.01 | 0.145710E+10 | 0.293322E+10 | 0.264984E+10 |
| Minimum of Months | 76971515.23 | 0.00 | 76971515.23 | 34886619.33 | 26242326.81 |
| Maximum of Months | 0.199389E+09 | 35681652.83 | 0.164074E+09 | 0.571271E+09 | 0.482938E+09 |
Report: WindowEnergyReportMonthly
For: MWINDOW1 S S1A
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.674562E+09 | 0.537910E+09 | 0.136651E+09 | 0.103339E+10 | 0.394223E+09 |
| February | 0.392743E+09 | 0.266565E+09 | 0.126178E+09 | 0.530133E+09 | 0.360356E+09 |
| March | 0.341866E+09 | 0.168768E+09 | 0.173098E+09 | 0.500228E+09 | 0.352807E+09 |
| April | 0.305655E+09 | 0.130378E+09 | 0.175278E+09 | 0.595163E+09 | 0.176928E+09 |
| May | 0.203995E+09 | 34012954.60 | 0.169982E+09 | 0.451583E+09 | 0.119662E+09 |
| June | 0.169595E+09 | 13859625.08 | 0.155735E+09 | 0.522158E+09 | 38091879.16 |
| July | 0.177966E+09 | 18215448.15 | 0.159750E+09 | 0.528578E+09 | 27163860.74 |
| August | 0.218092E+09 | 61301923.89 | 0.156790E+09 | 0.596883E+09 | 36525624.01 |
| September | 0.302743E+09 | 0.129507E+09 | 0.173237E+09 | 0.679710E+09 | 56092298.00 |
| October | 0.497543E+09 | 0.344406E+09 | 0.153137E+09 | 0.854254E+09 | 0.231819E+09 |
| November | 0.567433E+09 | 0.436105E+09 | 0.131328E+09 | 0.856659E+09 | 0.346231E+09 |
| December | 0.629958E+09 | 0.498533E+09 | 0.131424E+09 | 0.915942E+09 | 0.472945E+09 |
| Annual Sum or Average | 0.448215E+10 | 0.263956E+10 | 0.184259E+10 | 0.806468E+10 | 0.261284E+10 |
| Minimum of Months | 0.169595E+09 | 13859625.08 | 0.126178E+09 | 0.451583E+09 | 27163860.74 |
| Maximum of Months | 0.674562E+09 | 0.537910E+09 | 0.175278E+09 | 0.103339E+10 | 0.472945E+09 |
Report: WindowEnergyReportMonthly
For: MWINDOW1 S S2A
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.674562E+09 | 0.537910E+09 | 0.136651E+09 | 0.103335E+10 | 0.394165E+09 |
| February | 0.392743E+09 | 0.266565E+09 | 0.126178E+09 | 0.530040E+09 | 0.360415E+09 |
| March | 0.341866E+09 | 0.168768E+09 | 0.173098E+09 | 0.500083E+09 | 0.352869E+09 |
| April | 0.305655E+09 | 0.130378E+09 | 0.175278E+09 | 0.595099E+09 | 0.176904E+09 |
| May | 0.203995E+09 | 34012954.60 | 0.169982E+09 | 0.451520E+09 | 0.119640E+09 |
| June | 0.169595E+09 | 13859625.08 | 0.155735E+09 | 0.522111E+09 | 38077419.63 |
| July | 0.177966E+09 | 18215448.15 | 0.159750E+09 | 0.528512E+09 | 27161800.87 |
| August | 0.218092E+09 | 61301923.89 | 0.156790E+09 | 0.596825E+09 | 36528414.42 |
| September | 0.302743E+09 | 0.129507E+09 | 0.173237E+09 | 0.679674E+09 | 56088337.10 |
| October | 0.497543E+09 | 0.344406E+09 | 0.153137E+09 | 0.854191E+09 | 0.231812E+09 |
| November | 0.567433E+09 | 0.436105E+09 | 0.131328E+09 | 0.856623E+09 | 0.346177E+09 |
| December | 0.629958E+09 | 0.498533E+09 | 0.131424E+09 | 0.915847E+09 | 0.472978E+09 |
| Annual Sum or Average | 0.448215E+10 | 0.263956E+10 | 0.184259E+10 | 0.806387E+10 | 0.261282E+10 |
| Minimum of Months | 0.169595E+09 | 13859625.08 | 0.126178E+09 | 0.451520E+09 | 27161800.87 |
| Maximum of Months | 0.674562E+09 | 0.537910E+09 | 0.175278E+09 | 0.103335E+10 | 0.472978E+09 |
Report: WindowEnergyReportMonthly
For: TWINDOW1 S SWA
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.674562E+09 | 0.537910E+09 | 0.136651E+09 | 0.104531E+10 | 0.345352E+09 |
| February | 0.392743E+09 | 0.266565E+09 | 0.126178E+09 | 0.544748E+09 | 0.298785E+09 |
| March | 0.341866E+09 | 0.168768E+09 | 0.173098E+09 | 0.511672E+09 | 0.307658E+09 |
| April | 0.305655E+09 | 0.130378E+09 | 0.175278E+09 | 0.583176E+09 | 0.164716E+09 |
| May | 0.203995E+09 | 34012954.60 | 0.169982E+09 | 0.434134E+09 | 0.114585E+09 |
| June | 0.169595E+09 | 13859625.08 | 0.155735E+09 | 0.495271E+09 | 37540078.55 |
| July | 0.177966E+09 | 18215448.15 | 0.159750E+09 | 0.503637E+09 | 27038190.52 |
| August | 0.218092E+09 | 61301923.89 | 0.156790E+09 | 0.574077E+09 | 36074022.43 |
| September | 0.302743E+09 | 0.129507E+09 | 0.173237E+09 | 0.661231E+09 | 54531654.24 |
| October | 0.497543E+09 | 0.344406E+09 | 0.153137E+09 | 0.852017E+09 | 0.208115E+09 |
| November | 0.567433E+09 | 0.436105E+09 | 0.131328E+09 | 0.866608E+09 | 0.303665E+09 |
| December | 0.629958E+09 | 0.498533E+09 | 0.131424E+09 | 0.932654E+09 | 0.414728E+09 |
| Annual Sum or Average | 0.448215E+10 | 0.263956E+10 | 0.184259E+10 | 0.800453E+10 | 0.231279E+10 |
| Minimum of Months | 0.169595E+09 | 13859625.08 | 0.126178E+09 | 0.434134E+09 | 27038190.52 |
| Maximum of Months | 0.674562E+09 | 0.537910E+09 | 0.175278E+09 | 0.104531E+10 | 0.414728E+09 |
Report: WindowEnergyReportMonthly
For: TWINDOW1 W SWA
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.184317E+09 | 0.114929E+09 | 69388377.30 | 0.258383E+09 | 0.244328E+09 |
| February | 0.133802E+09 | 64581883.73 | 69220085.41 | 0.149900E+09 | 0.208742E+09 |
| March | 0.197604E+09 | 94692714.42 | 0.102911E+09 | 0.265924E+09 | 0.200893E+09 |
| April | 0.291734E+09 | 0.166288E+09 | 0.125446E+09 | 0.503427E+09 | 0.106884E+09 |
| May | 0.302777E+09 | 0.169479E+09 | 0.133298E+09 | 0.563424E+09 | 75145325.73 |
| June | 0.311415E+09 | 0.183332E+09 | 0.128084E+09 | 0.670157E+09 | 25716828.09 |
| July | 0.234046E+09 | 0.109265E+09 | 0.124781E+09 | 0.527335E+09 | 18624759.27 |
| August | 0.223611E+09 | 0.112349E+09 | 0.111262E+09 | 0.494438E+09 | 24839851.81 |
| September | 0.188486E+09 | 79291333.81 | 0.109194E+09 | 0.392524E+09 | 37232508.13 |
| October | 0.198988E+09 | 0.113716E+09 | 85272415.21 | 0.325282E+09 | 0.144285E+09 |
| November | 0.176722E+09 | 0.106415E+09 | 70306517.52 | 0.242932E+09 | 0.214293E+09 |
| December | 0.147662E+09 | 84024867.93 | 63637399.90 | 0.181992E+09 | 0.296493E+09 |
| Annual Sum or Average | 0.259116E+10 | 0.139836E+10 | 0.119280E+10 | 0.457572E+10 | 0.159748E+10 |
| Minimum of Months | 0.133802E+09 | 64581883.73 | 63637399.90 | 0.149900E+09 | 18624759.27 |
| Maximum of Months | 0.311415E+09 | 0.183332E+09 | 0.133298E+09 | 0.670157E+09 | 0.296493E+09 |
Report: WindowEnergyReportMonthly
For: TWINDOW1 W NWA
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.184317E+09 | 0.114929E+09 | 69388377.30 | 0.276299E+09 | 0.229467E+09 |
| February | 0.133802E+09 | 64581883.73 | 69220085.41 | 0.162574E+09 | 0.196627E+09 |
| March | 0.197604E+09 | 94692714.42 | 0.102911E+09 | 0.275822E+09 | 0.195137E+09 |
| April | 0.291734E+09 | 0.166288E+09 | 0.125446E+09 | 0.508430E+09 | 0.105381E+09 |
| May | 0.302777E+09 | 0.169479E+09 | 0.133298E+09 | 0.564375E+09 | 75280279.47 |
| June | 0.311415E+09 | 0.183332E+09 | 0.128084E+09 | 0.669330E+09 | 25899763.24 |
| July | 0.234046E+09 | 0.109265E+09 | 0.124781E+09 | 0.527594E+09 | 18676724.90 |
| August | 0.223611E+09 | 0.112349E+09 | 0.111262E+09 | 0.496999E+09 | 24607711.48 |
| September | 0.188486E+09 | 79291333.81 | 0.109194E+09 | 0.397203E+09 | 36572918.00 |
| October | 0.198988E+09 | 0.113716E+09 | 85272415.21 | 0.336788E+09 | 0.137886E+09 |
| November | 0.176722E+09 | 0.106415E+09 | 70306517.52 | 0.257801E+09 | 0.200854E+09 |
| December | 0.147662E+09 | 84024867.93 | 63637399.90 | 0.199743E+09 | 0.278008E+09 |
| Annual Sum or Average | 0.259116E+10 | 0.139836E+10 | 0.119280E+10 | 0.467296E+10 | 0.152440E+10 |
| Minimum of Months | 0.133802E+09 | 64581883.73 | 63637399.90 | 0.162574E+09 | 18676724.90 |
| Maximum of Months | 0.311415E+09 | 0.183332E+09 | 0.133298E+09 | 0.669330E+09 | 0.278008E+09 |
Report: WindowEnergyReportMonthly
For: TWINDOW1 N NWA
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 82402469.07 | 0.00 | 82402469.07 | 68977742.81 | 0.355326E+09 |
| February | 84808934.39 | 0.00 | 84808934.39 | 45385860.62 | 0.307186E+09 |
| March | 0.124821E+09 | 14118.42 | 0.124807E+09 | 0.122957E+09 | 0.306778E+09 |
| April | 0.147612E+09 | 1954846.33 | 0.145657E+09 | 0.247570E+09 | 0.158008E+09 |
| May | 0.179632E+09 | 15557674.50 | 0.164074E+09 | 0.356643E+09 | 0.104938E+09 |
| June | 0.199389E+09 | 35681652.83 | 0.163707E+09 | 0.544463E+09 | 35741852.57 |
| July | 0.175831E+09 | 17826399.52 | 0.158005E+09 | 0.488148E+09 | 26598396.10 |
| August | 0.142811E+09 | 3828713.07 | 0.138982E+09 | 0.401042E+09 | 36319994.22 |
| September | 0.130054E+09 | 77369.33 | 0.129977E+09 | 0.321717E+09 | 55847895.01 |
| October | 0.103920E+09 | 0.00 | 0.103920E+09 | 0.159927E+09 | 0.213885E+09 |
| November | 83791828.16 | 0.00 | 83791828.16 | 67807637.95 | 0.311706E+09 |
| December | 76971515.23 | 0.00 | 76971515.23 | 42870491.07 | 0.431400E+09 |
| Annual Sum or Average | 0.153204E+10 | 74940774.01 | 0.145710E+10 | 0.286751E+10 | 0.234374E+10 |
| Minimum of Months | 76971515.23 | 0.00 | 76971515.23 | 42870491.07 | 26598396.10 |
| Maximum of Months | 0.199389E+09 | 35681652.83 | 0.164074E+09 | 0.544463E+09 | 0.431400E+09 |
Report: WindowEnergyReportMonthly
For: TWINDOW1 S SEA
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.674562E+09 | 0.537910E+09 | 0.136651E+09 | 0.104073E+10 | 0.342738E+09 |
| February | 0.392743E+09 | 0.266565E+09 | 0.126178E+09 | 0.539644E+09 | 0.297637E+09 |
| March | 0.341866E+09 | 0.168768E+09 | 0.173098E+09 | 0.505449E+09 | 0.305708E+09 |
| April | 0.305655E+09 | 0.130378E+09 | 0.175278E+09 | 0.579186E+09 | 0.163157E+09 |
| May | 0.203995E+09 | 34012954.60 | 0.169982E+09 | 0.431329E+09 | 0.113653E+09 |
| June | 0.169595E+09 | 13859625.08 | 0.155735E+09 | 0.493581E+09 | 37132663.63 |
| July | 0.177966E+09 | 18215448.15 | 0.159750E+09 | 0.501258E+09 | 26826764.17 |
| August | 0.218092E+09 | 61301923.89 | 0.156790E+09 | 0.571844E+09 | 35889300.01 |
| September | 0.302743E+09 | 0.129507E+09 | 0.173237E+09 | 0.659715E+09 | 54235449.18 |
| October | 0.497543E+09 | 0.344406E+09 | 0.153137E+09 | 0.847601E+09 | 0.206475E+09 |
| November | 0.567433E+09 | 0.436105E+09 | 0.131328E+09 | 0.862835E+09 | 0.300762E+09 |
| December | 0.629958E+09 | 0.498533E+09 | 0.131424E+09 | 0.928047E+09 | 0.412684E+09 |
| Annual Sum or Average | 0.448215E+10 | 0.263956E+10 | 0.184259E+10 | 0.796122E+10 | 0.229690E+10 |
| Minimum of Months | 0.169595E+09 | 13859625.08 | 0.126178E+09 | 0.431329E+09 | 26826764.17 |
| Maximum of Months | 0.674562E+09 | 0.537910E+09 | 0.175278E+09 | 0.104073E+10 | 0.412684E+09 |
Report: WindowEnergyReportMonthly
For: TWINDOW1 E SEA
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.175948E+09 | 0.110679E+09 | 65268692.49 | 0.220708E+09 | 0.228948E+09 |
| February | 0.156127E+09 | 89319636.19 | 66807077.55 | 0.175525E+09 | 0.200281E+09 |
| March | 0.215568E+09 | 0.110588E+09 | 0.104980E+09 | 0.283902E+09 | 0.191914E+09 |
| April | 0.298731E+09 | 0.178199E+09 | 0.120533E+09 | 0.503259E+09 | 98405986.64 |
| May | 0.319881E+09 | 0.189712E+09 | 0.130170E+09 | 0.580166E+09 | 66782847.59 |
| June | 0.322564E+09 | 0.200503E+09 | 0.122061E+09 | 0.683346E+09 | 21780605.89 |
| July | 0.281915E+09 | 0.159217E+09 | 0.122698E+09 | 0.608047E+09 | 16025829.53 |
| August | 0.267225E+09 | 0.152538E+09 | 0.114687E+09 | 0.566486E+09 | 22175886.15 |
| September | 0.212018E+09 | 0.102165E+09 | 0.109853E+09 | 0.428895E+09 | 33778060.34 |
| October | 0.219841E+09 | 0.133694E+09 | 86146584.38 | 0.348936E+09 | 0.135226E+09 |
| November | 0.163854E+09 | 98334421.63 | 65519182.01 | 0.204762E+09 | 0.202287E+09 |
| December | 0.154182E+09 | 93073405.93 | 61108263.85 | 0.170386E+09 | 0.280240E+09 |
| Annual Sum or Average | 0.278785E+10 | 0.161802E+10 | 0.116983E+10 | 0.477442E+10 | 0.149785E+10 |
| Minimum of Months | 0.154182E+09 | 89319636.19 | 61108263.85 | 0.170386E+09 | 16025829.53 |
| Maximum of Months | 0.322564E+09 | 0.200503E+09 | 0.130170E+09 | 0.683346E+09 | 0.280240E+09 |
Report: WindowEnergyReportMonthly
For: TWINDOW1 E NEA
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.175948E+09 | 0.110679E+09 | 65268692.49 | 0.238423E+09 | 0.211944E+09 |
| February | 0.156127E+09 | 89319636.19 | 66807077.55 | 0.186830E+09 | 0.185962E+09 |
| March | 0.215568E+09 | 0.110588E+09 | 0.104980E+09 | 0.292787E+09 | 0.185034E+09 |
| April | 0.298731E+09 | 0.178199E+09 | 0.120533E+09 | 0.508005E+09 | 96914763.54 |
| May | 0.319881E+09 | 0.189712E+09 | 0.130170E+09 | 0.581053E+09 | 66738047.23 |
| June | 0.322564E+09 | 0.200503E+09 | 0.122061E+09 | 0.682539E+09 | 21889843.83 |
| July | 0.281915E+09 | 0.159217E+09 | 0.122698E+09 | 0.608310E+09 | 16045671.86 |
| August | 0.267225E+09 | 0.152538E+09 | 0.114687E+09 | 0.569019E+09 | 21928818.52 |
| September | 0.212018E+09 | 0.102165E+09 | 0.109853E+09 | 0.433554E+09 | 33120940.88 |
| October | 0.219841E+09 | 0.133694E+09 | 86146584.38 | 0.359925E+09 | 0.128435E+09 |
| November | 0.163854E+09 | 98334421.63 | 65519182.01 | 0.218776E+09 | 0.186996E+09 |
| December | 0.154182E+09 | 93073405.93 | 61108263.85 | 0.185744E+09 | 0.257786E+09 |
| Annual Sum or Average | 0.278785E+10 | 0.161802E+10 | 0.116983E+10 | 0.486496E+10 | 0.141280E+10 |
| Minimum of Months | 0.154182E+09 | 89319636.19 | 61108263.85 | 0.185744E+09 | 16045671.86 |
| Maximum of Months | 0.322564E+09 | 0.200503E+09 | 0.130170E+09 | 0.682539E+09 | 0.257786E+09 |
Report: WindowEnergyReportMonthly
For: TWINDOW1 N NEA
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 82402469.07 | 0.00 | 82402469.07 | 64757225.48 | 0.351364E+09 |
| February | 84808934.39 | 0.00 | 84808934.39 | 41379799.08 | 0.305731E+09 |
| March | 0.124821E+09 | 14118.42 | 0.124807E+09 | 0.116977E+09 | 0.304664E+09 |
| April | 0.147612E+09 | 1954846.33 | 0.145657E+09 | 0.243476E+09 | 0.156688E+09 |
| May | 0.179632E+09 | 15557674.50 | 0.164074E+09 | 0.353358E+09 | 0.103450E+09 |
| June | 0.199389E+09 | 35681652.83 | 0.163707E+09 | 0.542780E+09 | 35170036.39 |
| July | 0.175831E+09 | 17826399.52 | 0.158005E+09 | 0.485709E+09 | 26294581.47 |
| August | 0.142811E+09 | 3828713.07 | 0.138982E+09 | 0.398710E+09 | 36045611.33 |
| September | 0.130054E+09 | 77369.33 | 0.129977E+09 | 0.320216E+09 | 55597957.38 |
| October | 0.103920E+09 | 0.00 | 0.103920E+09 | 0.155530E+09 | 0.212659E+09 |
| November | 83791828.16 | 0.00 | 83791828.16 | 64322677.54 | 0.307668E+09 |
| December | 76971515.23 | 0.00 | 76971515.23 | 40140828.00 | 0.428627E+09 |
| Annual Sum or Average | 0.153204E+10 | 74940774.01 | 0.145710E+10 | 0.282736E+10 | 0.232396E+10 |
| Minimum of Months | 76971515.23 | 0.00 | 76971515.23 | 40140828.00 | 26294581.47 |
| Maximum of Months | 0.199389E+09 | 35681652.83 | 0.164074E+09 | 0.542780E+09 | 0.428627E+09 |
Report: WindowEnergyReportMonthly
For: TWINDOW1 N N1A
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 82402469.07 | 0.00 | 82402469.07 | 69745705.03 | 0.358792E+09 |
| February | 84808934.39 | 0.00 | 84808934.39 | 45128223.18 | 0.312522E+09 |
| March | 0.124821E+09 | 14118.42 | 0.124807E+09 | 0.123020E+09 | 0.312058E+09 |
| April | 0.147612E+09 | 1954846.33 | 0.145657E+09 | 0.252844E+09 | 0.159420E+09 |
| May | 0.179632E+09 | 15557674.50 | 0.164074E+09 | 0.363940E+09 | 0.104132E+09 |
| June | 0.199389E+09 | 35681652.83 | 0.163707E+09 | 0.556385E+09 | 34787450.18 |
| July | 0.175831E+09 | 17826399.52 | 0.158005E+09 | 0.498190E+09 | 25972072.83 |
| August | 0.142811E+09 | 3828713.07 | 0.138982E+09 | 0.410241E+09 | 35685162.15 |
| September | 0.130054E+09 | 77369.33 | 0.129977E+09 | 0.328660E+09 | 55500577.83 |
| October | 0.103920E+09 | 0.00 | 0.103920E+09 | 0.162492E+09 | 0.217387E+09 |
| November | 83791828.16 | 0.00 | 83791828.16 | 68067422.78 | 0.316249E+09 |
| December | 76971515.23 | 0.00 | 76971515.23 | 42868935.84 | 0.435950E+09 |
| Annual Sum or Average | 0.153204E+10 | 74940774.01 | 0.145710E+10 | 0.292158E+10 | 0.236846E+10 |
| Minimum of Months | 76971515.23 | 0.00 | 76971515.23 | 42868935.84 | 25972072.83 |
| Maximum of Months | 0.199389E+09 | 35681652.83 | 0.164074E+09 | 0.556385E+09 | 0.435950E+09 |
Report: WindowEnergyReportMonthly
For: TWINDOW1 N N2A
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 82402469.07 | 0.00 | 82402469.07 | 69363978.50 | 0.358481E+09 |
| February | 84808934.39 | 0.00 | 84808934.39 | 44765464.07 | 0.312532E+09 |
| March | 0.124821E+09 | 14118.42 | 0.124807E+09 | 0.122526E+09 | 0.312007E+09 |
| April | 0.147612E+09 | 1954846.33 | 0.145657E+09 | 0.252558E+09 | 0.159310E+09 |
| May | 0.179632E+09 | 15557674.50 | 0.164074E+09 | 0.363777E+09 | 0.104051E+09 |
| June | 0.199389E+09 | 35681652.83 | 0.163707E+09 | 0.556302E+09 | 34754037.58 |
| July | 0.175831E+09 | 17826399.52 | 0.158005E+09 | 0.498084E+09 | 25955794.17 |
| August | 0.142811E+09 | 3828713.07 | 0.138982E+09 | 0.410135E+09 | 35671237.48 |
| September | 0.130054E+09 | 77369.33 | 0.129977E+09 | 0.328580E+09 | 55480572.56 |
| October | 0.103920E+09 | 0.00 | 0.103920E+09 | 0.162151E+09 | 0.217338E+09 |
| November | 83791828.16 | 0.00 | 83791828.16 | 67770254.33 | 0.315901E+09 |
| December | 76971515.23 | 0.00 | 76971515.23 | 42625612.44 | 0.435754E+09 |
| Annual Sum or Average | 0.153204E+10 | 74940774.01 | 0.145710E+10 | 0.291864E+10 | 0.236723E+10 |
| Minimum of Months | 76971515.23 | 0.00 | 76971515.23 | 42625612.44 | 25955794.17 |
| Maximum of Months | 0.199389E+09 | 35681652.83 | 0.164074E+09 | 0.556302E+09 | 0.435754E+09 |
Report: WindowEnergyReportMonthly
For: TWINDOW1 S S1A
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.674562E+09 | 0.537910E+09 | 0.136651E+09 | 0.104257E+10 | 0.354462E+09 |
| February | 0.392743E+09 | 0.266565E+09 | 0.126178E+09 | 0.541661E+09 | 0.309365E+09 |
| March | 0.341866E+09 | 0.168768E+09 | 0.173098E+09 | 0.509754E+09 | 0.315700E+09 |
| April | 0.305655E+09 | 0.130378E+09 | 0.175278E+09 | 0.587764E+09 | 0.166204E+09 |
| May | 0.203995E+09 | 34012954.60 | 0.169982E+09 | 0.441813E+09 | 0.114342E+09 |
| June | 0.169595E+09 | 13859625.08 | 0.155735E+09 | 0.507481E+09 | 36683451.22 |
| July | 0.177966E+09 | 18215448.15 | 0.159750E+09 | 0.513714E+09 | 26508780.56 |
| August | 0.218092E+09 | 61301923.89 | 0.156790E+09 | 0.582998E+09 | 35546705.61 |
| September | 0.302743E+09 | 0.129507E+09 | 0.173237E+09 | 0.667561E+09 | 54234416.89 |
| October | 0.497543E+09 | 0.344406E+09 | 0.153137E+09 | 0.852701E+09 | 0.212816E+09 |
| November | 0.567433E+09 | 0.436105E+09 | 0.131328E+09 | 0.864089E+09 | 0.312441E+09 |
| December | 0.629958E+09 | 0.498533E+09 | 0.131424E+09 | 0.928855E+09 | 0.425019E+09 |
| Annual Sum or Average | 0.448215E+10 | 0.263956E+10 | 0.184259E+10 | 0.804097E+10 | 0.236332E+10 |
| Minimum of Months | 0.169595E+09 | 13859625.08 | 0.126178E+09 | 0.441813E+09 | 26508780.56 |
| Maximum of Months | 0.674562E+09 | 0.537910E+09 | 0.175278E+09 | 0.104257E+10 | 0.425019E+09 |
Report: WindowEnergyReportMonthly
For: TWINDOW1 S S2A
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.674562E+09 | 0.537910E+09 | 0.136651E+09 | 0.104232E+10 | 0.354291E+09 |
| February | 0.392743E+09 | 0.266565E+09 | 0.126178E+09 | 0.541325E+09 | 0.309360E+09 |
| March | 0.341866E+09 | 0.168768E+09 | 0.173098E+09 | 0.509339E+09 | 0.315626E+09 |
| April | 0.305655E+09 | 0.130378E+09 | 0.175278E+09 | 0.587521E+09 | 0.166084E+09 |
| May | 0.203995E+09 | 34012954.60 | 0.169982E+09 | 0.441647E+09 | 0.114261E+09 |
| June | 0.169595E+09 | 13859625.08 | 0.155735E+09 | 0.507394E+09 | 36648753.26 |
| July | 0.177966E+09 | 18215448.15 | 0.159750E+09 | 0.513609E+09 | 26492619.45 |
| August | 0.218092E+09 | 61301923.89 | 0.156790E+09 | 0.582899E+09 | 35533027.51 |
| September | 0.302743E+09 | 0.129507E+09 | 0.173237E+09 | 0.667490E+09 | 54213075.71 |
| October | 0.497543E+09 | 0.344406E+09 | 0.153137E+09 | 0.852465E+09 | 0.212735E+09 |
| November | 0.567433E+09 | 0.436105E+09 | 0.131328E+09 | 0.863891E+09 | 0.312225E+09 |
| December | 0.629958E+09 | 0.498533E+09 | 0.131424E+09 | 0.928583E+09 | 0.424910E+09 |
| Annual Sum or Average | 0.448215E+10 | 0.263956E+10 | 0.184259E+10 | 0.803848E+10 | 0.236238E+10 |
| Minimum of Months | 0.169595E+09 | 13859625.08 | 0.126178E+09 | 0.441647E+09 | 26492619.45 |
| Maximum of Months | 0.674562E+09 | 0.537910E+09 | 0.175278E+09 | 0.104232E+10 | 0.424910E+09 |
Report: WindowEnergyReportMonthly
For: TWINDOW14
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 42219423.49 | 26557935.06 | 15661488.43 | 54465856.57 | 59060437.37 |
| February | 37463240.46 | 21432610.27 | 16030630.19 | 42620350.73 | 52178775.92 |
| March | 51726474.28 | 26536036.47 | 25190437.81 | 67623300.66 | 51285312.90 |
| April | 71681838.54 | 42759533.98 | 28922304.56 | 0.117846E+09 | 27947539.42 |
| May | 76756839.06 | 45522060.77 | 31234778.29 | 0.134507E+09 | 19833989.85 |
| June | 77400548.14 | 48111558.36 | 29288989.79 | 0.156191E+09 | 7536648.09 |
| July | 67646668.88 | 38204880.19 | 29441788.69 | 0.137618E+09 | 6195275.13 |
| August | 64121703.19 | 36602037.97 | 27519665.23 | 0.129060E+09 | 8400555.79 |
| September | 50874495.05 | 24514852.10 | 26359642.94 | 97627366.30 | 11621418.97 |
| October | 52751679.28 | 32080455.71 | 20671223.57 | 82417841.75 | 36879869.80 |
| November | 39317339.14 | 23595744.73 | 15721594.41 | 49718735.09 | 52849660.32 |
| December | 36996519.24 | 22333342.60 | 14663176.65 | 42273196.02 | 69954240.63 |
| Annual Sum or Average | 0.668957E+09 | 0.388251E+09 | 0.280706E+09 | 0.111197E+10 | 0.403744E+09 |
| Minimum of Months | 36996519.24 | 21432610.27 | 14663176.65 | 42273196.02 | 6195275.13 |
| Maximum of Months | 77400548.14 | 48111558.36 | 31234778.29 | 0.156191E+09 | 69954240.63 |
Report: WindowEnergyReportMonthly
For: ENTRANCE DOOR
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.125740E+09 | 79096139.91 | 46643810.12 | 0.157925E+09 | 0.181947E+09 |
| February | 0.111575E+09 | 63831647.17 | 47743206.14 | 0.128926E+09 | 0.154525E+09 |
| March | 0.154054E+09 | 79030920.45 | 75023392.79 | 0.203360E+09 | 0.149664E+09 |
| April | 0.213486E+09 | 0.127349E+09 | 86137820.68 | 0.347575E+09 | 87955640.31 |
| May | 0.228601E+09 | 0.135576E+09 | 93024942.93 | 0.393779E+09 | 65521049.86 |
| June | 0.230518E+09 | 0.143288E+09 | 87229900.54 | 0.451962E+09 | 28258637.51 |
| July | 0.201469E+09 | 0.113784E+09 | 87684973.71 | 0.396007E+09 | 24393765.36 |
| August | 0.190970E+09 | 0.109010E+09 | 81960411.68 | 0.371702E+09 | 32903033.82 |
| September | 0.151517E+09 | 73011330.41 | 78505576.64 | 0.280543E+09 | 43730862.81 |
| October | 0.157108E+09 | 95543580.74 | 61564048.11 | 0.235539E+09 | 0.123934E+09 |
| November | 0.117097E+09 | 70273999.92 | 46822820.69 | 0.140451E+09 | 0.172001E+09 |
| December | 0.110185E+09 | 66514252.21 | 43670589.18 | 0.120381E+09 | 0.220444E+09 |
| Annual Sum or Average | 0.199232E+10 | 0.115631E+10 | 0.836011E+09 | 0.322815E+10 | 0.128528E+10 |
| Minimum of Months | 0.110185E+09 | 63831647.17 | 43670589.18 | 0.120381E+09 | 24393765.36 |
| Maximum of Months | 0.230518E+09 | 0.143288E+09 | 93024942.93 | 0.451962E+09 | 0.220444E+09 |
Report: WindowEnergyReportMonthly
For: MWINDOW14
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 42219423.49 | 26557935.06 | 15661488.43 | 49723179.56 | 66567708.06 |
| February | 37463240.46 | 21432610.27 | 16030630.19 | 39012994.21 | 61340920.60 |
| March | 51726474.28 | 26536036.47 | 25190437.81 | 63059872.49 | 57509261.80 |
| April | 71681838.54 | 42759533.98 | 28922304.56 | 0.116693E+09 | 29668863.72 |
| May | 76756839.06 | 45522060.77 | 31234778.29 | 0.134647E+09 | 20770944.46 |
| June | 77400548.14 | 48111558.36 | 29288989.79 | 0.158729E+09 | 7764608.90 |
| July | 67646668.88 | 38204880.19 | 29441788.69 | 0.140435E+09 | 6266807.90 |
| August | 64121703.19 | 36602037.97 | 27519665.23 | 0.131414E+09 | 8549844.89 |
| September | 50874495.05 | 24514852.10 | 26359642.94 | 99143769.37 | 11927615.50 |
| October | 52751679.28 | 32080455.71 | 20671223.57 | 80008125.77 | 40906588.72 |
| November | 39317339.14 | 23595744.73 | 15721594.41 | 45743839.49 | 59990445.34 |
| December | 36996519.24 | 22333342.60 | 14663176.65 | 37981924.49 | 79048348.38 |
| Annual Sum or Average | 0.668957E+09 | 0.388251E+09 | 0.280706E+09 | 0.109659E+10 | 0.450312E+09 |
| Minimum of Months | 36996519.24 | 21432610.27 | 14663176.65 | 37981924.49 | 6266807.90 |
| Maximum of Months | 77400548.14 | 48111558.36 | 31234778.29 | 0.158729E+09 | 79048348.38 |
Report: WindowZoneSummaryMonthly
For: G SW APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 481.32 | 236.08 | 320.67 | 243.74 | 76.93 | 0.00 | 0.00 |
| February | 287.06 | 217.45 | 217.65 | 136.88 | 80.77 | 0.00 | 0.00 |
| March | 294.92 | 192.57 | 201.41 | 98.36 | 103.05 | 0.00 | 0.00 |
| April | 428.46 | 110.40 | 230.47 | 114.45 | 116.02 | 0.00 | 0.00 |
| May | 382.54 | 73.89 | 189.21 | 75.98 | 113.23 | 0.00 | 0.00 |
| June | 460.41 | 26.07 | 185.57 | 76.08 | 109.50 | 0.00 | 0.00 |
| July | 391.87 | 19.07 | 153.83 | 47.60 | 106.23 | 0.00 | 0.00 |
| August | 404.63 | 26.00 | 164.91 | 64.83 | 100.08 | 0.00 | 0.00 |
| September | 411.18 | 41.08 | 189.52 | 80.55 | 108.96 | 0.00 | 0.00 |
| October | 437.54 | 147.58 | 260.05 | 171.04 | 89.01 | 0.00 | 0.00 |
| November | 419.00 | 222.64 | 287.10 | 209.31 | 77.79 | 0.00 | 0.00 |
| December | 403.75 | 287.07 | 290.33 | 217.50 | 72.83 | 0.00 | 0.00 |
| Annual Sum or Average | 400.83 | 133.00 | 224.29 | 128.04 | 96.25 | 0.00 | 0.00 |
| Minimum of Months | 287.06 | 19.07 | 153.83 | 47.60 | 72.83 | 0.00 | 0.00 |
| Maximum of Months | 481.32 | 287.07 | 320.67 | 243.74 | 116.02 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: G NW APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 126.72 | 230.80 | 99.58 | 42.91 | 56.67 | 0.00 | 0.00 |
| February | 87.64 | 209.44 | 90.36 | 26.70 | 63.67 | 0.00 | 0.00 |
| March | 154.05 | 184.29 | 120.38 | 35.36 | 85.02 | 0.00 | 0.00 |
| April | 299.49 | 106.14 | 169.50 | 64.91 | 104.59 | 0.00 | 0.00 |
| May | 351.69 | 67.73 | 180.11 | 69.08 | 111.03 | 0.00 | 0.00 |
| June | 478.16 | 24.02 | 197.07 | 84.50 | 112.57 | 0.00 | 0.00 |
| July | 385.60 | 18.20 | 153.03 | 47.45 | 105.58 | 0.00 | 0.00 |
| August | 339.89 | 25.25 | 136.81 | 43.38 | 93.43 | 0.00 | 0.00 |
| September | 279.98 | 40.63 | 122.89 | 30.62 | 92.27 | 0.00 | 0.00 |
| October | 180.78 | 151.64 | 113.09 | 42.46 | 70.64 | 0.00 | 0.00 |
| November | 116.39 | 227.75 | 100.51 | 41.06 | 59.45 | 0.00 | 0.00 |
| December | 83.88 | 286.64 | 83.87 | 31.37 | 52.50 | 0.00 | 0.00 |
| Annual Sum or Average | 241.03 | 130.74 | 130.75 | 46.72 | 84.03 | 0.00 | 0.00 |
| Minimum of Months | 83.88 | 18.20 | 83.87 | 26.70 | 52.50 | 0.00 | 0.00 |
| Maximum of Months | 478.16 | 286.64 | 197.07 | 84.50 | 112.57 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: OFFICE
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 462.33 | 250.65 | 317.54 | 242.16 | 75.39 | 0.00 | 0.00 |
| February | 293.07 | 232.11 | 226.88 | 147.11 | 79.77 | 0.00 | 0.00 |
| March | 289.18 | 204.10 | 208.12 | 104.30 | 103.82 | 0.00 | 0.00 |
| April | 396.81 | 131.31 | 233.17 | 119.05 | 114.12 | 0.00 | 0.00 |
| May | 351.42 | 98.38 | 195.59 | 83.53 | 112.06 | 0.00 | 0.00 |
| June | 412.14 | 49.17 | 189.88 | 82.70 | 107.17 | 0.00 | 0.00 |
| July | 365.23 | 45.36 | 171.70 | 66.25 | 105.45 | 0.00 | 0.00 |
| August | 387.07 | 59.00 | 181.20 | 79.84 | 101.36 | 0.00 | 0.00 |
| September | 384.46 | 80.36 | 198.60 | 89.38 | 109.22 | 0.00 | 0.00 |
| October | 423.04 | 182.86 | 267.84 | 178.50 | 89.34 | 0.00 | 0.00 |
| November | 396.54 | 244.90 | 282.13 | 206.19 | 75.94 | 0.00 | 0.00 |
| December | 395.79 | 301.45 | 292.76 | 220.88 | 71.88 | 0.00 | 0.00 |
| Annual Sum or Average | 380.27 | 156.35 | 230.53 | 135.01 | 95.52 | 0.00 | 0.00 |
| Minimum of Months | 289.18 | 45.36 | 171.70 | 66.25 | 71.88 | 0.00 | 0.00 |
| Maximum of Months | 462.33 | 301.45 | 317.54 | 242.16 | 114.12 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: G NE APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 100.97 | 212.42 | 96.46 | 41.32 | 55.13 | 0.00 | 0.00 |
| February | 88.56 | 197.45 | 99.59 | 36.92 | 62.67 | 0.00 | 0.00 |
| March | 153.51 | 174.59 | 127.09 | 41.29 | 85.79 | 0.00 | 0.00 |
| April | 293.43 | 97.34 | 172.20 | 69.50 | 102.70 | 0.00 | 0.00 |
| May | 358.22 | 65.12 | 186.50 | 76.64 | 109.86 | 0.00 | 0.00 |
| June | 483.97 | 23.35 | 201.37 | 91.12 | 110.25 | 0.00 | 0.00 |
| July | 415.65 | 17.58 | 170.90 | 66.10 | 104.80 | 0.00 | 0.00 |
| August | 366.59 | 24.44 | 153.09 | 58.38 | 94.71 | 0.00 | 0.00 |
| September | 292.41 | 37.92 | 131.97 | 39.45 | 92.53 | 0.00 | 0.00 |
| October | 181.14 | 140.35 | 120.88 | 49.92 | 70.96 | 0.00 | 0.00 |
| November | 89.95 | 211.38 | 95.54 | 37.94 | 57.60 | 0.00 | 0.00 |
| December | 64.73 | 266.07 | 86.30 | 34.75 | 51.55 | 0.00 | 0.00 |
| Annual Sum or Average | 241.47 | 122.04 | 136.98 | 53.68 | 83.30 | 0.00 | 0.00 |
| Minimum of Months | 64.73 | 17.58 | 86.30 | 34.75 | 51.55 | 0.00 | 0.00 |
| Maximum of Months | 483.97 | 266.07 | 201.37 | 91.12 | 110.25 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: G N1 APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 24.01 | 144.94 | 30.77 | 0.00 | 30.77 | 0.00 | 0.00 |
| February | 19.17 | 134.95 | 35.06 | 0.00 | 35.06 | 0.00 | 0.00 |
| March | 48.15 | 117.90 | 46.60 | 0.01 | 46.60 | 0.00 | 0.00 |
| April | 100.59 | 63.75 | 56.95 | 0.75 | 56.19 | 0.00 | 0.00 |
| May | 139.50 | 39.81 | 67.07 | 5.81 | 61.26 | 0.00 | 0.00 |
| June | 219.21 | 13.99 | 76.92 | 13.77 | 63.16 | 0.00 | 0.00 |
| July | 189.06 | 10.44 | 65.65 | 6.66 | 58.99 | 0.00 | 0.00 |
| August | 155.29 | 14.50 | 53.32 | 1.43 | 51.89 | 0.00 | 0.00 |
| September | 127.85 | 23.59 | 50.18 | 0.03 | 50.15 | 0.00 | 0.00 |
| October | 58.14 | 92.95 | 38.80 | 0.00 | 38.80 | 0.00 | 0.00 |
| November | 21.80 | 142.18 | 32.33 | 0.00 | 32.33 | 0.00 | 0.00 |
| December | 13.04 | 180.12 | 28.74 | 0.00 | 28.74 | 0.00 | 0.00 |
| Annual Sum or Average | 93.32 | 81.38 | 48.58 | 2.38 | 46.20 | 0.00 | 0.00 |
| Minimum of Months | 13.04 | 10.44 | 28.74 | 0.00 | 28.74 | 0.00 | 0.00 |
| Maximum of Months | 219.21 | 180.12 | 76.92 | 13.77 | 63.16 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: G N2 APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 23.99 | 144.88 | 30.77 | 0.00 | 30.77 | 0.00 | 0.00 |
| February | 19.10 | 135.08 | 35.06 | 0.00 | 35.06 | 0.00 | 0.00 |
| March | 48.06 | 117.98 | 46.60 | 0.01 | 46.60 | 0.00 | 0.00 |
| April | 100.56 | 63.75 | 56.95 | 0.75 | 56.19 | 0.00 | 0.00 |
| May | 139.47 | 39.80 | 67.07 | 5.81 | 61.26 | 0.00 | 0.00 |
| June | 219.19 | 13.99 | 76.92 | 13.77 | 63.16 | 0.00 | 0.00 |
| July | 189.03 | 10.44 | 65.65 | 6.66 | 58.99 | 0.00 | 0.00 |
| August | 155.26 | 14.50 | 53.32 | 1.43 | 51.89 | 0.00 | 0.00 |
| September | 127.83 | 23.59 | 50.18 | 0.03 | 50.15 | 0.00 | 0.00 |
| October | 58.11 | 92.97 | 38.80 | 0.00 | 38.80 | 0.00 | 0.00 |
| November | 21.79 | 142.15 | 32.33 | 0.00 | 32.33 | 0.00 | 0.00 |
| December | 13.01 | 180.17 | 28.74 | 0.00 | 28.74 | 0.00 | 0.00 |
| Annual Sum or Average | 93.29 | 81.40 | 48.58 | 2.38 | 46.20 | 0.00 | 0.00 |
| Minimum of Months | 13.01 | 10.44 | 28.74 | 0.00 | 28.74 | 0.00 | 0.00 |
| Maximum of Months | 219.19 | 180.17 | 76.92 | 13.77 | 63.16 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: G S1 APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 388.72 | 145.43 | 251.85 | 200.83 | 51.02 | 0.00 | 0.00 |
| February | 224.37 | 139.25 | 162.34 | 110.19 | 52.16 | 0.00 | 0.00 |
| March | 192.23 | 123.63 | 127.64 | 63.01 | 64.63 | 0.00 | 0.00 |
| April | 231.27 | 67.28 | 117.92 | 50.30 | 67.62 | 0.00 | 0.00 |
| May | 169.07 | 44.40 | 76.16 | 12.70 | 63.46 | 0.00 | 0.00 |
| June | 200.09 | 15.07 | 65.43 | 5.35 | 60.08 | 0.00 | 0.00 |
| July | 194.86 | 10.88 | 66.44 | 6.80 | 59.64 | 0.00 | 0.00 |
| August | 220.39 | 14.88 | 81.43 | 22.89 | 58.54 | 0.00 | 0.00 |
| September | 260.22 | 23.69 | 116.80 | 49.96 | 66.84 | 0.00 | 0.00 |
| October | 318.98 | 88.44 | 185.76 | 128.59 | 57.17 | 0.00 | 0.00 |
| November | 331.40 | 134.99 | 218.92 | 168.25 | 50.67 | 0.00 | 0.00 |
| December | 343.26 | 177.07 | 235.20 | 186.13 | 49.07 | 0.00 | 0.00 |
| Annual Sum or Average | 256.51 | 81.85 | 142.13 | 83.70 | 58.43 | 0.00 | 0.00 |
| Minimum of Months | 169.07 | 10.88 | 65.43 | 5.35 | 49.07 | 0.00 | 0.00 |
| Maximum of Months | 388.72 | 177.07 | 251.85 | 200.83 | 67.62 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: G S2 APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 388.42 | 145.89 | 251.85 | 200.83 | 51.02 | 0.00 | 0.00 |
| February | 223.83 | 140.41 | 162.34 | 110.19 | 52.16 | 0.00 | 0.00 |
| March | 191.56 | 124.64 | 127.64 | 63.01 | 64.63 | 0.00 | 0.00 |
| April | 230.57 | 68.08 | 117.92 | 50.30 | 67.62 | 0.00 | 0.00 |
| May | 168.13 | 45.19 | 76.16 | 12.70 | 63.46 | 0.00 | 0.00 |
| June | 198.68 | 15.63 | 65.43 | 5.35 | 60.08 | 0.00 | 0.00 |
| July | 193.33 | 11.40 | 66.44 | 6.80 | 59.64 | 0.00 | 0.00 |
| August | 219.12 | 15.55 | 81.43 | 22.89 | 58.54 | 0.00 | 0.00 |
| September | 259.12 | 24.54 | 116.80 | 49.96 | 66.84 | 0.00 | 0.00 |
| October | 318.30 | 89.28 | 185.76 | 128.59 | 57.17 | 0.00 | 0.00 |
| November | 331.04 | 135.58 | 218.92 | 168.25 | 50.67 | 0.00 | 0.00 |
| December | 342.91 | 177.68 | 235.20 | 186.13 | 49.07 | 0.00 | 0.00 |
| Annual Sum or Average | 255.68 | 82.59 | 142.13 | 83.70 | 58.43 | 0.00 | 0.00 |
| Minimum of Months | 168.13 | 11.40 | 65.43 | 5.35 | 49.07 | 0.00 | 0.00 |
| Maximum of Months | 388.42 | 177.68 | 251.85 | 200.83 | 67.62 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: M SW APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 476.78 | 239.61 | 320.67 | 243.74 | 76.93 | 0.00 | 0.00 |
| February | 276.50 | 238.18 | 217.65 | 136.88 | 80.77 | 0.00 | 0.00 |
| March | 283.03 | 209.47 | 201.41 | 98.36 | 103.05 | 0.00 | 0.00 |
| April | 424.47 | 113.02 | 230.47 | 114.45 | 116.02 | 0.00 | 0.00 |
| May | 380.04 | 75.21 | 189.21 | 75.98 | 113.23 | 0.00 | 0.00 |
| June | 461.14 | 25.72 | 185.57 | 76.08 | 109.50 | 0.00 | 0.00 |
| July | 395.68 | 17.76 | 153.83 | 47.60 | 106.23 | 0.00 | 0.00 |
| August | 408.92 | 23.69 | 164.91 | 64.83 | 100.08 | 0.00 | 0.00 |
| September | 415.38 | 37.10 | 189.52 | 80.55 | 108.96 | 0.00 | 0.00 |
| October | 438.69 | 143.16 | 260.05 | 171.04 | 89.01 | 0.00 | 0.00 |
| November | 419.07 | 218.17 | 287.10 | 209.31 | 77.79 | 0.00 | 0.00 |
| December | 403.14 | 284.27 | 290.33 | 217.50 | 72.83 | 0.00 | 0.00 |
| Annual Sum or Average | 399.23 | 135.01 | 224.29 | 128.04 | 96.25 | 0.00 | 0.00 |
| Minimum of Months | 276.50 | 17.76 | 153.83 | 47.60 | 72.83 | 0.00 | 0.00 |
| Maximum of Months | 476.78 | 284.27 | 320.67 | 243.74 | 116.02 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: M NW APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 122.44 | 241.35 | 99.58 | 42.91 | 56.67 | 0.00 | 0.00 |
| February | 78.76 | 234.07 | 90.36 | 26.70 | 63.67 | 0.00 | 0.00 |
| March | 141.19 | 205.65 | 120.38 | 35.36 | 85.02 | 0.00 | 0.00 |
| April | 295.54 | 109.95 | 169.50 | 64.91 | 104.59 | 0.00 | 0.00 |
| May | 349.08 | 69.08 | 180.11 | 69.08 | 111.03 | 0.00 | 0.00 |
| June | 478.88 | 23.70 | 197.07 | 84.50 | 112.57 | 0.00 | 0.00 |
| July | 389.52 | 17.00 | 153.03 | 47.45 | 105.58 | 0.00 | 0.00 |
| August | 344.41 | 23.19 | 136.81 | 43.38 | 93.43 | 0.00 | 0.00 |
| September | 284.84 | 37.06 | 122.89 | 30.62 | 92.27 | 0.00 | 0.00 |
| October | 183.54 | 146.59 | 113.09 | 42.46 | 70.64 | 0.00 | 0.00 |
| November | 118.53 | 220.81 | 100.51 | 41.06 | 59.45 | 0.00 | 0.00 |
| December | 84.62 | 284.43 | 83.87 | 31.37 | 52.50 | 0.00 | 0.00 |
| Annual Sum or Average | 239.99 | 133.99 | 130.75 | 46.72 | 84.03 | 0.00 | 0.00 |
| Minimum of Months | 78.76 | 17.00 | 83.87 | 26.70 | 52.50 | 0.00 | 0.00 |
| Maximum of Months | 478.88 | 284.43 | 197.07 | 84.50 | 112.57 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: M SE APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 464.67 | 235.86 | 317.54 | 242.16 | 75.39 | 0.00 | 0.00 |
| February | 286.92 | 235.52 | 226.88 | 147.11 | 79.77 | 0.00 | 0.00 |
| March | 285.31 | 202.81 | 208.12 | 104.30 | 103.82 | 0.00 | 0.00 |
| April | 416.85 | 102.30 | 233.17 | 119.05 | 114.12 | 0.00 | 0.00 |
| May | 380.53 | 66.49 | 195.59 | 83.53 | 112.06 | 0.00 | 0.00 |
| June | 463.93 | 22.08 | 189.88 | 82.70 | 107.17 | 0.00 | 0.00 |
| July | 424.46 | 15.88 | 171.70 | 66.25 | 105.45 | 0.00 | 0.00 |
| August | 434.64 | 21.90 | 181.20 | 79.84 | 101.36 | 0.00 | 0.00 |
| September | 428.07 | 34.62 | 198.60 | 89.38 | 109.22 | 0.00 | 0.00 |
| October | 446.64 | 139.20 | 267.84 | 178.50 | 89.34 | 0.00 | 0.00 |
| November | 405.68 | 215.04 | 282.13 | 206.19 | 75.94 | 0.00 | 0.00 |
| December | 401.34 | 281.70 | 292.76 | 220.88 | 71.88 | 0.00 | 0.00 |
| Annual Sum or Average | 403.93 | 130.67 | 230.53 | 135.01 | 95.52 | 0.00 | 0.00 |
| Minimum of Months | 285.31 | 15.88 | 171.70 | 66.25 | 71.88 | 0.00 | 0.00 |
| Maximum of Months | 464.67 | 281.70 | 317.54 | 242.16 | 114.12 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: M NE APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 95.45 | 222.51 | 96.46 | 41.32 | 55.13 | 0.00 | 0.00 |
| February | 77.67 | 221.34 | 99.59 | 36.92 | 62.67 | 0.00 | 0.00 |
| March | 139.50 | 195.41 | 127.09 | 41.29 | 85.79 | 0.00 | 0.00 |
| April | 289.04 | 100.48 | 172.20 | 69.50 | 102.70 | 0.00 | 0.00 |
| May | 355.49 | 66.28 | 186.50 | 76.64 | 109.86 | 0.00 | 0.00 |
| June | 484.60 | 22.96 | 201.37 | 91.12 | 110.25 | 0.00 | 0.00 |
| July | 419.49 | 16.31 | 170.90 | 66.10 | 104.80 | 0.00 | 0.00 |
| August | 371.01 | 22.32 | 153.09 | 58.38 | 94.71 | 0.00 | 0.00 |
| September | 297.39 | 34.47 | 131.97 | 39.45 | 92.53 | 0.00 | 0.00 |
| October | 184.06 | 135.83 | 120.88 | 49.92 | 70.96 | 0.00 | 0.00 |
| November | 92.62 | 205.19 | 95.54 | 37.94 | 57.60 | 0.00 | 0.00 |
| December | 65.51 | 263.99 | 86.30 | 34.75 | 51.55 | 0.00 | 0.00 |
| Annual Sum or Average | 240.08 | 125.18 | 136.98 | 53.68 | 83.30 | 0.00 | 0.00 |
| Minimum of Months | 65.51 | 16.31 | 86.30 | 34.75 | 51.55 | 0.00 | 0.00 |
| Maximum of Months | 484.60 | 263.99 | 201.37 | 91.12 | 110.25 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: M N1 APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 21.88 | 152.17 | 30.77 | 0.00 | 30.77 | 0.00 | 0.00 |
| February | 14.63 | 152.29 | 35.06 | 0.00 | 35.06 | 0.00 | 0.00 |
| March | 41.98 | 131.46 | 46.60 | 0.01 | 46.60 | 0.00 | 0.00 |
| April | 99.23 | 65.56 | 56.95 | 0.75 | 56.19 | 0.00 | 0.00 |
| May | 138.98 | 40.18 | 67.07 | 5.81 | 61.26 | 0.00 | 0.00 |
| June | 220.41 | 13.72 | 76.92 | 13.77 | 63.16 | 0.00 | 0.00 |
| July | 191.54 | 9.80 | 65.65 | 6.66 | 58.99 | 0.00 | 0.00 |
| August | 157.95 | 13.49 | 53.32 | 1.43 | 51.89 | 0.00 | 0.00 |
| September | 130.52 | 21.90 | 50.18 | 0.03 | 50.15 | 0.00 | 0.00 |
| October | 59.49 | 91.02 | 38.80 | 0.00 | 38.80 | 0.00 | 0.00 |
| November | 22.57 | 139.75 | 32.33 | 0.00 | 32.33 | 0.00 | 0.00 |
| December | 13.06 | 180.28 | 28.74 | 0.00 | 28.74 | 0.00 | 0.00 |
| Annual Sum or Average | 93.05 | 84.01 | 48.58 | 2.38 | 46.20 | 0.00 | 0.00 |
| Minimum of Months | 13.06 | 9.80 | 28.74 | 0.00 | 28.74 | 0.00 | 0.00 |
| Maximum of Months | 220.41 | 180.28 | 76.92 | 13.77 | 63.16 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: M N2 APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 21.85 | 152.14 | 30.77 | 0.00 | 30.77 | 0.00 | 0.00 |
| February | 14.53 | 152.48 | 35.06 | 0.00 | 35.06 | 0.00 | 0.00 |
| March | 41.90 | 131.54 | 46.60 | 0.01 | 46.60 | 0.00 | 0.00 |
| April | 99.20 | 65.55 | 56.95 | 0.75 | 56.19 | 0.00 | 0.00 |
| May | 138.95 | 40.17 | 67.07 | 5.81 | 61.26 | 0.00 | 0.00 |
| June | 220.40 | 13.71 | 76.92 | 13.77 | 63.16 | 0.00 | 0.00 |
| July | 191.51 | 9.80 | 65.65 | 6.66 | 58.99 | 0.00 | 0.00 |
| August | 157.93 | 13.49 | 53.32 | 1.43 | 51.89 | 0.00 | 0.00 |
| September | 130.51 | 21.90 | 50.18 | 0.03 | 50.15 | 0.00 | 0.00 |
| October | 59.45 | 91.06 | 38.80 | 0.00 | 38.80 | 0.00 | 0.00 |
| November | 22.54 | 139.72 | 32.33 | 0.00 | 32.33 | 0.00 | 0.00 |
| December | 13.03 | 180.31 | 28.74 | 0.00 | 28.74 | 0.00 | 0.00 |
| Annual Sum or Average | 93.01 | 84.03 | 48.58 | 2.38 | 46.20 | 0.00 | 0.00 |
| Minimum of Months | 13.03 | 9.80 | 28.74 | 0.00 | 28.74 | 0.00 | 0.00 |
| Maximum of Months | 220.40 | 180.31 | 76.92 | 13.77 | 63.16 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: M S1 APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 385.82 | 147.19 | 251.85 | 200.83 | 51.02 | 0.00 | 0.00 |
| February | 219.14 | 148.96 | 162.34 | 110.19 | 52.16 | 0.00 | 0.00 |
| March | 186.76 | 131.72 | 127.64 | 63.01 | 64.63 | 0.00 | 0.00 |
| April | 229.62 | 68.26 | 117.92 | 50.30 | 67.62 | 0.00 | 0.00 |
| May | 168.60 | 44.68 | 76.16 | 12.70 | 63.46 | 0.00 | 0.00 |
| June | 201.45 | 14.70 | 65.43 | 5.35 | 60.08 | 0.00 | 0.00 |
| July | 197.35 | 10.14 | 66.44 | 6.80 | 59.64 | 0.00 | 0.00 |
| August | 222.85 | 13.64 | 81.43 | 22.89 | 58.54 | 0.00 | 0.00 |
| September | 262.23 | 21.64 | 116.80 | 49.96 | 66.84 | 0.00 | 0.00 |
| October | 318.94 | 86.55 | 185.76 | 128.59 | 57.17 | 0.00 | 0.00 |
| November | 330.50 | 133.58 | 218.92 | 168.25 | 50.67 | 0.00 | 0.00 |
| December | 341.97 | 176.58 | 235.20 | 186.13 | 49.07 | 0.00 | 0.00 |
| Annual Sum or Average | 255.73 | 82.85 | 142.13 | 83.70 | 58.43 | 0.00 | 0.00 |
| Minimum of Months | 168.60 | 10.14 | 65.43 | 5.35 | 49.07 | 0.00 | 0.00 |
| Maximum of Months | 385.82 | 176.58 | 251.85 | 200.83 | 67.62 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: M S2 APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 385.81 | 147.16 | 251.85 | 200.83 | 51.02 | 0.00 | 0.00 |
| February | 219.10 | 148.98 | 162.34 | 110.19 | 52.16 | 0.00 | 0.00 |
| March | 186.71 | 131.75 | 127.64 | 63.01 | 64.63 | 0.00 | 0.00 |
| April | 229.59 | 68.25 | 117.92 | 50.30 | 67.62 | 0.00 | 0.00 |
| May | 168.58 | 44.67 | 76.16 | 12.70 | 63.46 | 0.00 | 0.00 |
| June | 201.43 | 14.69 | 65.43 | 5.35 | 60.08 | 0.00 | 0.00 |
| July | 197.32 | 10.14 | 66.44 | 6.80 | 59.64 | 0.00 | 0.00 |
| August | 222.83 | 13.64 | 81.43 | 22.89 | 58.54 | 0.00 | 0.00 |
| September | 262.22 | 21.64 | 116.80 | 49.96 | 66.84 | 0.00 | 0.00 |
| October | 318.92 | 86.55 | 185.76 | 128.59 | 57.17 | 0.00 | 0.00 |
| November | 330.49 | 133.56 | 218.92 | 168.25 | 50.67 | 0.00 | 0.00 |
| December | 341.94 | 176.59 | 235.20 | 186.13 | 49.07 | 0.00 | 0.00 |
| Annual Sum or Average | 255.70 | 82.85 | 142.13 | 83.70 | 58.43 | 0.00 | 0.00 |
| Minimum of Months | 168.58 | 10.14 | 65.43 | 5.35 | 49.07 | 0.00 | 0.00 |
| Maximum of Months | 385.81 | 176.59 | 251.85 | 200.83 | 67.62 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: T SW APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 481.04 | 214.46 | 320.67 | 243.74 | 76.93 | 0.00 | 0.00 |
| February | 282.51 | 205.16 | 217.65 | 136.88 | 80.77 | 0.00 | 0.00 |
| March | 287.15 | 186.70 | 201.41 | 98.36 | 103.05 | 0.00 | 0.00 |
| April | 418.70 | 104.27 | 230.47 | 114.45 | 116.02 | 0.00 | 0.00 |
| May | 372.43 | 70.82 | 189.21 | 75.98 | 113.23 | 0.00 | 0.00 |
| June | 449.61 | 24.39 | 185.57 | 76.08 | 109.50 | 0.00 | 0.00 |
| July | 384.91 | 17.04 | 153.83 | 47.60 | 106.23 | 0.00 | 0.00 |
| August | 398.88 | 22.69 | 164.91 | 64.83 | 100.08 | 0.00 | 0.00 |
| September | 406.49 | 35.36 | 189.52 | 80.55 | 108.96 | 0.00 | 0.00 |
| October | 437.34 | 129.36 | 260.05 | 171.04 | 89.01 | 0.00 | 0.00 |
| November | 422.94 | 194.71 | 287.10 | 209.31 | 77.79 | 0.00 | 0.00 |
| December | 408.14 | 257.52 | 290.33 | 217.50 | 72.83 | 0.00 | 0.00 |
| Annual Sum or Average | 396.46 | 121.54 | 224.29 | 128.04 | 96.25 | 0.00 | 0.00 |
| Minimum of Months | 282.51 | 17.04 | 153.83 | 47.60 | 72.83 | 0.00 | 0.00 |
| Maximum of Months | 481.04 | 257.52 | 320.67 | 243.74 | 116.02 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: T NW APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 126.82 | 216.25 | 99.58 | 42.91 | 56.67 | 0.00 | 0.00 |
| February | 83.33 | 205.63 | 90.36 | 26.70 | 63.67 | 0.00 | 0.00 |
| March | 145.65 | 184.16 | 120.38 | 35.36 | 85.02 | 0.00 | 0.00 |
| April | 291.47 | 101.42 | 169.50 | 64.91 | 104.59 | 0.00 | 0.00 |
| May | 342.34 | 65.76 | 180.11 | 69.08 | 111.03 | 0.00 | 0.00 |
| June | 467.28 | 22.78 | 197.07 | 84.50 | 112.57 | 0.00 | 0.00 |
| July | 378.83 | 16.50 | 153.03 | 47.45 | 105.58 | 0.00 | 0.00 |
| August | 335.02 | 22.48 | 136.81 | 43.38 | 93.43 | 0.00 | 0.00 |
| September | 277.35 | 35.65 | 122.89 | 30.62 | 92.27 | 0.00 | 0.00 |
| October | 184.38 | 130.26 | 113.09 | 42.46 | 70.64 | 0.00 | 0.00 |
| November | 123.38 | 195.51 | 100.51 | 41.06 | 59.45 | 0.00 | 0.00 |
| December | 87.92 | 262.21 | 83.87 | 31.37 | 52.50 | 0.00 | 0.00 |
| Annual Sum or Average | 237.67 | 121.22 | 130.75 | 46.72 | 84.03 | 0.00 | 0.00 |
| Minimum of Months | 83.33 | 16.50 | 83.87 | 26.70 | 52.50 | 0.00 | 0.00 |
| Maximum of Months | 467.28 | 262.21 | 197.07 | 84.50 | 112.57 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: T SE APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 468.56 | 211.04 | 317.54 | 242.16 | 75.39 | 0.00 | 0.00 |
| February | 292.74 | 202.94 | 226.88 | 147.11 | 79.77 | 0.00 | 0.00 |
| March | 290.09 | 181.17 | 208.12 | 104.30 | 103.82 | 0.00 | 0.00 |
| April | 412.15 | 95.45 | 233.17 | 119.05 | 114.12 | 0.00 | 0.00 |
| May | 373.36 | 63.08 | 195.59 | 83.53 | 112.06 | 0.00 | 0.00 |
| June | 452.35 | 21.01 | 189.88 | 82.70 | 107.17 | 0.00 | 0.00 |
| July | 413.38 | 15.22 | 171.70 | 66.25 | 105.45 | 0.00 | 0.00 |
| August | 424.27 | 20.94 | 181.20 | 79.84 | 101.36 | 0.00 | 0.00 |
| September | 419.05 | 33.02 | 198.60 | 89.38 | 109.22 | 0.00 | 0.00 |
| October | 445.05 | 125.89 | 267.84 | 178.50 | 89.34 | 0.00 | 0.00 |
| November | 409.51 | 191.71 | 282.13 | 206.19 | 75.94 | 0.00 | 0.00 |
| December | 406.33 | 254.93 | 292.76 | 220.88 | 71.88 | 0.00 | 0.00 |
| Annual Sum or Average | 401.21 | 117.69 | 230.53 | 135.01 | 95.52 | 0.00 | 0.00 |
| Minimum of Months | 290.09 | 15.22 | 171.70 | 66.25 | 71.88 | 0.00 | 0.00 |
| Maximum of Months | 468.56 | 254.93 | 317.54 | 242.16 | 114.12 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: T NE APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 102.98 | 200.10 | 96.46 | 41.32 | 55.13 | 0.00 | 0.00 |
| February | 84.88 | 193.79 | 99.59 | 36.92 | 62.67 | 0.00 | 0.00 |
| March | 145.61 | 175.46 | 127.09 | 41.29 | 85.79 | 0.00 | 0.00 |
| April | 286.02 | 93.94 | 172.20 | 69.50 | 102.70 | 0.00 | 0.00 |
| May | 348.50 | 63.17 | 186.50 | 76.64 | 109.86 | 0.00 | 0.00 |
| June | 472.72 | 22.00 | 201.37 | 91.12 | 110.25 | 0.00 | 0.00 |
| July | 408.39 | 15.73 | 170.90 | 66.10 | 104.80 | 0.00 | 0.00 |
| August | 361.19 | 21.53 | 153.09 | 58.38 | 94.71 | 0.00 | 0.00 |
| September | 289.77 | 33.19 | 131.97 | 39.45 | 92.53 | 0.00 | 0.00 |
| October | 186.65 | 121.55 | 120.88 | 49.92 | 70.96 | 0.00 | 0.00 |
| November | 100.13 | 181.75 | 95.54 | 37.94 | 57.60 | 0.00 | 0.00 |
| December | 71.40 | 243.34 | 86.30 | 34.75 | 51.55 | 0.00 | 0.00 |
| Annual Sum or Average | 238.91 | 113.48 | 136.98 | 53.68 | 83.30 | 0.00 | 0.00 |
| Minimum of Months | 71.40 | 15.73 | 86.30 | 34.75 | 51.55 | 0.00 | 0.00 |
| Maximum of Months | 472.72 | 243.34 | 201.37 | 91.12 | 110.25 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: T N1 APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 26.04 | 133.96 | 30.77 | 0.00 | 30.77 | 0.00 | 0.00 |
| February | 18.65 | 129.18 | 35.06 | 0.00 | 35.06 | 0.00 | 0.00 |
| March | 45.93 | 116.51 | 46.60 | 0.01 | 46.60 | 0.00 | 0.00 |
| April | 97.55 | 61.50 | 56.95 | 0.75 | 56.19 | 0.00 | 0.00 |
| May | 135.88 | 38.88 | 67.07 | 5.81 | 61.26 | 0.00 | 0.00 |
| June | 214.65 | 13.42 | 76.92 | 13.77 | 63.16 | 0.00 | 0.00 |
| July | 186.00 | 9.70 | 65.65 | 6.66 | 58.99 | 0.00 | 0.00 |
| August | 153.17 | 13.32 | 53.32 | 1.43 | 51.89 | 0.00 | 0.00 |
| September | 126.80 | 21.41 | 50.18 | 0.03 | 50.15 | 0.00 | 0.00 |
| October | 60.67 | 81.16 | 38.80 | 0.00 | 38.80 | 0.00 | 0.00 |
| November | 26.26 | 122.01 | 32.33 | 0.00 | 32.33 | 0.00 | 0.00 |
| December | 16.01 | 162.77 | 28.74 | 0.00 | 28.74 | 0.00 | 0.00 |
| Annual Sum or Average | 92.64 | 75.10 | 48.58 | 2.38 | 46.20 | 0.00 | 0.00 |
| Minimum of Months | 16.01 | 9.70 | 28.74 | 0.00 | 28.74 | 0.00 | 0.00 |
| Maximum of Months | 214.65 | 162.77 | 76.92 | 13.77 | 63.16 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: T N2 APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 25.90 | 133.84 | 30.77 | 0.00 | 30.77 | 0.00 | 0.00 |
| February | 18.50 | 129.19 | 35.06 | 0.00 | 35.06 | 0.00 | 0.00 |
| March | 45.75 | 116.49 | 46.60 | 0.01 | 46.60 | 0.00 | 0.00 |
| April | 97.44 | 61.46 | 56.95 | 0.75 | 56.19 | 0.00 | 0.00 |
| May | 135.82 | 38.85 | 67.07 | 5.81 | 61.26 | 0.00 | 0.00 |
| June | 214.62 | 13.41 | 76.92 | 13.77 | 63.16 | 0.00 | 0.00 |
| July | 185.96 | 9.69 | 65.65 | 6.66 | 58.99 | 0.00 | 0.00 |
| August | 153.13 | 13.32 | 53.32 | 1.43 | 51.89 | 0.00 | 0.00 |
| September | 126.77 | 21.40 | 50.18 | 0.03 | 50.15 | 0.00 | 0.00 |
| October | 60.54 | 81.14 | 38.80 | 0.00 | 38.80 | 0.00 | 0.00 |
| November | 26.15 | 121.88 | 32.33 | 0.00 | 32.33 | 0.00 | 0.00 |
| December | 15.91 | 162.69 | 28.74 | 0.00 | 28.74 | 0.00 | 0.00 |
| Annual Sum or Average | 92.55 | 75.06 | 48.58 | 2.38 | 46.20 | 0.00 | 0.00 |
| Minimum of Months | 15.91 | 9.69 | 28.74 | 0.00 | 28.74 | 0.00 | 0.00 |
| Maximum of Months | 214.62 | 162.69 | 76.92 | 13.77 | 63.16 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: T S1 APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 389.25 | 132.34 | 251.85 | 200.83 | 51.02 | 0.00 | 0.00 |
| February | 223.90 | 127.88 | 162.34 | 110.19 | 52.16 | 0.00 | 0.00 |
| March | 190.32 | 117.87 | 127.64 | 63.01 | 64.63 | 0.00 | 0.00 |
| April | 226.76 | 64.12 | 117.92 | 50.30 | 67.62 | 0.00 | 0.00 |
| May | 164.95 | 42.69 | 76.16 | 12.70 | 63.46 | 0.00 | 0.00 |
| June | 195.79 | 14.15 | 65.43 | 5.35 | 60.08 | 0.00 | 0.00 |
| July | 191.80 | 9.90 | 66.44 | 6.80 | 59.64 | 0.00 | 0.00 |
| August | 217.67 | 13.27 | 81.43 | 22.89 | 58.54 | 0.00 | 0.00 |
| September | 257.55 | 20.92 | 116.80 | 49.96 | 66.84 | 0.00 | 0.00 |
| October | 318.36 | 79.46 | 185.76 | 128.59 | 57.17 | 0.00 | 0.00 |
| November | 333.37 | 120.54 | 218.92 | 168.25 | 50.67 | 0.00 | 0.00 |
| December | 346.79 | 158.68 | 235.20 | 186.13 | 49.07 | 0.00 | 0.00 |
| Annual Sum or Average | 254.98 | 74.94 | 142.13 | 83.70 | 58.43 | 0.00 | 0.00 |
| Minimum of Months | 164.95 | 9.90 | 65.43 | 5.35 | 49.07 | 0.00 | 0.00 |
| Maximum of Months | 389.25 | 158.68 | 251.85 | 200.83 | 67.62 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: T S2 APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 389.16 | 132.28 | 251.85 | 200.83 | 51.02 | 0.00 | 0.00 |
| February | 223.76 | 127.88 | 162.34 | 110.19 | 52.16 | 0.00 | 0.00 |
| March | 190.17 | 117.84 | 127.64 | 63.01 | 64.63 | 0.00 | 0.00 |
| April | 226.67 | 64.08 | 117.92 | 50.30 | 67.62 | 0.00 | 0.00 |
| May | 164.89 | 42.66 | 76.16 | 12.70 | 63.46 | 0.00 | 0.00 |
| June | 195.75 | 14.14 | 65.43 | 5.35 | 60.08 | 0.00 | 0.00 |
| July | 191.76 | 9.89 | 66.44 | 6.80 | 59.64 | 0.00 | 0.00 |
| August | 217.63 | 13.27 | 81.43 | 22.89 | 58.54 | 0.00 | 0.00 |
| September | 257.52 | 20.92 | 116.80 | 49.96 | 66.84 | 0.00 | 0.00 |
| October | 318.27 | 79.43 | 185.76 | 128.59 | 57.17 | 0.00 | 0.00 |
| November | 333.29 | 120.46 | 218.92 | 168.25 | 50.67 | 0.00 | 0.00 |
| December | 346.69 | 158.64 | 235.20 | 186.13 | 49.07 | 0.00 | 0.00 |
| Annual Sum or Average | 254.90 | 74.91 | 142.13 | 83.70 | 58.43 | 0.00 | 0.00 |
| Minimum of Months | 164.89 | 9.89 | 65.43 | 5.35 | 49.07 | 0.00 | 0.00 |
| Maximum of Months | 389.16 | 158.64 | 251.85 | 200.83 | 67.62 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: T CORRIDOR
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 20.34 | 22.05 | 15.76 | 9.92 | 5.85 | 0.00 | 0.00 |
| February | 17.62 | 21.57 | 15.49 | 8.86 | 6.63 | 0.00 | 0.00 |
| March | 25.25 | 19.15 | 19.31 | 9.91 | 9.41 | 0.00 | 0.00 |
| April | 45.47 | 10.78 | 27.66 | 16.50 | 11.16 | 0.00 | 0.00 |
| May | 50.22 | 7.41 | 28.66 | 17.00 | 11.66 | 0.00 | 0.00 |
| June | 60.26 | 2.91 | 29.86 | 18.56 | 11.30 | 0.00 | 0.00 |
| July | 51.38 | 2.31 | 25.26 | 14.26 | 10.99 | 0.00 | 0.00 |
| August | 48.19 | 3.14 | 23.94 | 13.67 | 10.27 | 0.00 | 0.00 |
| September | 37.66 | 4.48 | 19.63 | 9.46 | 10.17 | 0.00 | 0.00 |
| October | 30.77 | 13.77 | 19.70 | 11.98 | 7.72 | 0.00 | 0.00 |
| November | 19.18 | 20.39 | 15.17 | 9.10 | 6.07 | 0.00 | 0.00 |
| December | 15.78 | 26.12 | 13.81 | 8.34 | 5.47 | 0.00 | 0.00 |
| Annual Sum or Average | 35.26 | 12.80 | 21.21 | 12.31 | 8.90 | 0.00 | 0.00 |
| Minimum of Months | 15.78 | 2.31 | 13.81 | 8.34 | 5.47 | 0.00 | 0.00 |
| Maximum of Months | 60.26 | 26.12 | 29.86 | 18.56 | 11.66 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: G CORRIDOR
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 58.96 | 67.93 | 46.95 | 29.53 | 17.41 | 0.00 | 0.00 |
| February | 53.29 | 63.87 | 46.12 | 26.39 | 19.74 | 0.00 | 0.00 |
| March | 75.93 | 55.88 | 57.52 | 29.51 | 28.01 | 0.00 | 0.00 |
| April | 134.10 | 33.93 | 82.36 | 49.13 | 33.23 | 0.00 | 0.00 |
| May | 147.02 | 24.46 | 85.35 | 50.62 | 34.73 | 0.00 | 0.00 |
| June | 174.37 | 10.90 | 88.93 | 55.28 | 33.65 | 0.00 | 0.00 |
| July | 147.85 | 9.11 | 75.22 | 42.48 | 32.74 | 0.00 | 0.00 |
| August | 138.78 | 12.28 | 71.30 | 40.70 | 30.60 | 0.00 | 0.00 |
| September | 108.23 | 16.87 | 58.46 | 28.17 | 30.29 | 0.00 | 0.00 |
| October | 87.94 | 46.27 | 58.66 | 35.67 | 22.99 | 0.00 | 0.00 |
| November | 54.19 | 66.36 | 45.18 | 27.11 | 18.06 | 0.00 | 0.00 |
| December | 44.95 | 82.30 | 41.14 | 24.83 | 16.30 | 0.00 | 0.00 |
| Annual Sum or Average | 102.36 | 40.76 | 63.18 | 36.67 | 26.51 | 0.00 | 0.00 |
| Minimum of Months | 44.95 | 9.11 | 41.14 | 24.83 | 16.30 | 0.00 | 0.00 |
| Maximum of Months | 174.37 | 82.30 | 88.93 | 55.28 | 34.73 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: M CORRIDOR
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 18.56 | 24.85 | 15.76 | 9.92 | 5.85 | 0.00 | 0.00 |
| February | 16.13 | 25.36 | 15.49 | 8.86 | 6.63 | 0.00 | 0.00 |
| March | 23.54 | 21.47 | 19.31 | 9.91 | 9.41 | 0.00 | 0.00 |
| April | 45.02 | 11.45 | 27.66 | 16.50 | 11.16 | 0.00 | 0.00 |
| May | 50.27 | 7.75 | 28.66 | 17.00 | 11.66 | 0.00 | 0.00 |
| June | 61.24 | 3.00 | 29.86 | 18.56 | 11.30 | 0.00 | 0.00 |
| July | 52.43 | 2.34 | 25.26 | 14.26 | 10.99 | 0.00 | 0.00 |
| August | 49.06 | 3.19 | 23.94 | 13.67 | 10.27 | 0.00 | 0.00 |
| September | 38.25 | 4.60 | 19.63 | 9.46 | 10.17 | 0.00 | 0.00 |
| October | 29.87 | 15.27 | 19.70 | 11.98 | 7.72 | 0.00 | 0.00 |
| November | 17.65 | 23.14 | 15.17 | 9.10 | 6.07 | 0.00 | 0.00 |
| December | 14.18 | 29.51 | 13.81 | 8.34 | 5.47 | 0.00 | 0.00 |
| Annual Sum or Average | 34.77 | 14.28 | 21.21 | 12.31 | 8.90 | 0.00 | 0.00 |
| Minimum of Months | 14.18 | 2.34 | 13.81 | 8.34 | 5.47 | 0.00 | 0.00 |
| Maximum of Months | 61.24 | 29.51 | 29.86 | 18.56 | 11.66 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: G SW APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.128916E+10 | 0.632313E+09 | 0.858879E+09 | 0.652839E+09 | 0.206039E+09 | 0.00 | 0.00 |
| February | 0.694447E+09 | 0.526057E+09 | 0.526545E+09 | 0.331147E+09 | 0.195398E+09 | 0.00 | 0.00 |
| March | 0.789910E+09 | 0.515784E+09 | 0.539469E+09 | 0.263460E+09 | 0.276009E+09 | 0.00 | 0.00 |
| April | 0.111056E+10 | 0.286168E+09 | 0.597389E+09 | 0.296666E+09 | 0.300723E+09 | 0.00 | 0.00 |
| May | 0.102460E+10 | 0.197900E+09 | 0.506772E+09 | 0.203492E+09 | 0.303280E+09 | 0.00 | 0.00 |
| June | 0.119337E+10 | 67579792.08 | 0.481010E+09 | 0.197191E+09 | 0.283819E+09 | 0.00 | 0.00 |
| July | 0.104958E+10 | 51064908.85 | 0.412012E+09 | 0.127481E+09 | 0.284531E+09 | 0.00 | 0.00 |
| August | 0.108376E+10 | 69630030.15 | 0.441703E+09 | 0.173651E+09 | 0.268052E+09 | 0.00 | 0.00 |
| September | 0.106579E+10 | 0.106491E+09 | 0.491229E+09 | 0.208798E+09 | 0.282431E+09 | 0.00 | 0.00 |
| October | 0.117190E+10 | 0.395265E+09 | 0.696531E+09 | 0.458121E+09 | 0.238410E+09 | 0.00 | 0.00 |
| November | 0.108604E+10 | 0.577087E+09 | 0.744155E+09 | 0.542521E+09 | 0.201635E+09 | 0.00 | 0.00 |
| December | 0.108140E+10 | 0.768901E+09 | 0.777620E+09 | 0.582558E+09 | 0.195062E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.126405E+11 | 0.419424E+10 | 0.707331E+10 | 0.403793E+10 | 0.303539E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.694447E+09 | 51064908.85 | 0.412012E+09 | 0.127481E+09 | 0.195062E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.128916E+10 | 0.768901E+09 | 0.858879E+09 | 0.652839E+09 | 0.303280E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: G NW APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.339398E+09 | 0.618188E+09 | 0.266720E+09 | 0.114929E+09 | 0.151791E+09 | 0.00 | 0.00 |
| February | 0.212019E+09 | 0.506686E+09 | 0.218611E+09 | 64581883.73 | 0.154029E+09 | 0.00 | 0.00 |
| March | 0.412619E+09 | 0.493603E+09 | 0.322424E+09 | 94706832.85 | 0.227718E+09 | 0.00 | 0.00 |
| April | 0.776272E+09 | 0.275112E+09 | 0.439346E+09 | 0.168243E+09 | 0.271103E+09 | 0.00 | 0.00 |
| May | 0.941977E+09 | 0.181398E+09 | 0.482409E+09 | 0.185037E+09 | 0.297372E+09 | 0.00 | 0.00 |
| June | 0.123939E+10 | 62258625.02 | 0.510804E+09 | 0.219013E+09 | 0.291791E+09 | 0.00 | 0.00 |
| July | 0.103278E+10 | 48751559.24 | 0.409877E+09 | 0.127091E+09 | 0.282786E+09 | 0.00 | 0.00 |
| August | 0.910368E+09 | 67621099.39 | 0.366423E+09 | 0.116178E+09 | 0.250244E+09 | 0.00 | 0.00 |
| September | 0.725711E+09 | 0.105308E+09 | 0.318540E+09 | 79368703.14 | 0.239171E+09 | 0.00 | 0.00 |
| October | 0.484189E+09 | 0.406163E+09 | 0.302908E+09 | 0.113716E+09 | 0.189193E+09 | 0.00 | 0.00 |
| November | 0.301672E+09 | 0.590327E+09 | 0.260514E+09 | 0.106415E+09 | 0.154098E+09 | 0.00 | 0.00 |
| December | 0.224653E+09 | 0.767728E+09 | 0.224634E+09 | 84024867.93 | 0.140609E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.760105E+10 | 0.412314E+10 | 0.412321E+10 | 0.147330E+10 | 0.264990E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.212019E+09 | 48751559.24 | 0.218611E+09 | 64581883.73 | 0.140609E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.123939E+10 | 0.767728E+09 | 0.510804E+09 | 0.219013E+09 | 0.297372E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: OFFICE
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.123831E+10 | 0.671350E+09 | 0.850509E+09 | 0.648590E+09 | 0.201920E+09 | 0.00 | 0.00 |
| February | 0.709004E+09 | 0.561516E+09 | 0.548869E+09 | 0.355884E+09 | 0.192985E+09 | 0.00 | 0.00 |
| March | 0.774529E+09 | 0.546653E+09 | 0.557434E+09 | 0.279356E+09 | 0.278078E+09 | 0.00 | 0.00 |
| April | 0.102853E+10 | 0.340351E+09 | 0.604387E+09 | 0.308576E+09 | 0.295810E+09 | 0.00 | 0.00 |
| May | 0.941249E+09 | 0.263514E+09 | 0.523876E+09 | 0.223725E+09 | 0.300152E+09 | 0.00 | 0.00 |
| June | 0.106826E+10 | 0.127446E+09 | 0.492159E+09 | 0.214363E+09 | 0.277796E+09 | 0.00 | 0.00 |
| July | 0.978232E+09 | 0.121489E+09 | 0.459881E+09 | 0.177433E+09 | 0.282448E+09 | 0.00 | 0.00 |
| August | 0.103672E+10 | 0.158031E+09 | 0.485317E+09 | 0.213840E+09 | 0.271477E+09 | 0.00 | 0.00 |
| September | 0.996510E+09 | 0.208282E+09 | 0.514761E+09 | 0.231671E+09 | 0.283089E+09 | 0.00 | 0.00 |
| October | 0.113306E+10 | 0.489781E+09 | 0.717384E+09 | 0.478100E+09 | 0.239284E+09 | 0.00 | 0.00 |
| November | 0.102783E+10 | 0.634791E+09 | 0.731287E+09 | 0.534440E+09 | 0.196847E+09 | 0.00 | 0.00 |
| December | 0.106008E+10 | 0.807398E+09 | 0.784139E+09 | 0.591607E+09 | 0.192533E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.119923E+11 | 0.493060E+10 | 0.727000E+10 | 0.425758E+10 | 0.301242E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.709004E+09 | 0.121489E+09 | 0.459881E+09 | 0.177433E+09 | 0.192533E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.123831E+10 | 0.807398E+09 | 0.850509E+09 | 0.648590E+09 | 0.300152E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: G NE APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.270430E+09 | 0.568939E+09 | 0.258350E+09 | 0.110679E+09 | 0.147671E+09 | 0.00 | 0.00 |
| February | 0.214251E+09 | 0.477662E+09 | 0.240936E+09 | 89319636.19 | 0.151616E+09 | 0.00 | 0.00 |
| March | 0.411152E+09 | 0.467618E+09 | 0.340389E+09 | 0.110602E+09 | 0.229787E+09 | 0.00 | 0.00 |
| April | 0.760569E+09 | 0.252317E+09 | 0.446343E+09 | 0.180154E+09 | 0.266190E+09 | 0.00 | 0.00 |
| May | 0.959460E+09 | 0.174416E+09 | 0.499513E+09 | 0.205269E+09 | 0.294244E+09 | 0.00 | 0.00 |
| June | 0.125444E+10 | 60512133.66 | 0.521953E+09 | 0.236185E+09 | 0.285768E+09 | 0.00 | 0.00 |
| July | 0.111327E+10 | 47096702.42 | 0.457746E+09 | 0.177044E+09 | 0.280703E+09 | 0.00 | 0.00 |
| August | 0.981868E+09 | 65448151.81 | 0.410036E+09 | 0.156366E+09 | 0.253670E+09 | 0.00 | 0.00 |
| September | 0.757932E+09 | 98298666.70 | 0.342072E+09 | 0.102242E+09 | 0.239829E+09 | 0.00 | 0.00 |
| October | 0.485174E+09 | 0.375917E+09 | 0.323761E+09 | 0.133694E+09 | 0.190067E+09 | 0.00 | 0.00 |
| November | 0.233159E+09 | 0.547891E+09 | 0.247645E+09 | 98334421.63 | 0.149311E+09 | 0.00 | 0.00 |
| December | 0.173377E+09 | 0.712653E+09 | 0.231153E+09 | 93073405.93 | 0.138080E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.761509E+10 | 0.384877E+10 | 0.431990E+10 | 0.169296E+10 | 0.262694E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.173377E+09 | 47096702.42 | 0.231153E+09 | 89319636.19 | 0.138080E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.125444E+10 | 0.712653E+09 | 0.521953E+09 | 0.236185E+09 | 0.294244E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: G N1 APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 64318226.95 | 0.388205E+09 | 82402469.07 | 0.00 | 82402469.07 | 0.00 | 0.00 |
| February | 46373965.60 | 0.326475E+09 | 84808934.39 | 0.00 | 84808934.39 | 0.00 | 0.00 |
| March | 0.128952E+09 | 0.315791E+09 | 0.124821E+09 | 14118.42 | 0.124807E+09 | 0.00 | 0.00 |
| April | 0.260741E+09 | 0.165238E+09 | 0.147612E+09 | 1954846.33 | 0.145657E+09 | 0.00 | 0.00 |
| May | 0.373633E+09 | 0.106619E+09 | 0.179632E+09 | 15557674.50 | 0.164074E+09 | 0.00 | 0.00 |
| June | 0.568204E+09 | 36263979.42 | 0.199389E+09 | 35681652.83 | 0.163707E+09 | 0.00 | 0.00 |
| July | 0.506384E+09 | 27952620.50 | 0.175831E+09 | 17826399.52 | 0.158005E+09 | 0.00 | 0.00 |
| August | 0.415933E+09 | 38828609.68 | 0.142811E+09 | 3828713.07 | 0.138982E+09 | 0.00 | 0.00 |
| September | 0.331390E+09 | 61143478.49 | 0.130054E+09 | 77369.33 | 0.129977E+09 | 0.00 | 0.00 |
| October | 0.155709E+09 | 0.248961E+09 | 0.103920E+09 | 0.00 | 0.103920E+09 | 0.00 | 0.00 |
| November | 56517651.58 | 0.368537E+09 | 83791828.16 | 0.00 | 83791828.16 | 0.00 | 0.00 |
| December | 34934118.31 | 0.482442E+09 | 76971515.23 | 0.00 | 76971515.23 | 0.00 | 0.00 |
| Annual Sum or Average | 0.294309E+10 | 0.256646E+10 | 0.153204E+10 | 74940774.01 | 0.145710E+10 | 0.00 | 0.00 |
| Minimum of Months | 34934118.31 | 27952620.50 | 76971515.23 | 0.00 | 76971515.23 | 0.00 | 0.00 |
| Maximum of Months | 0.568204E+09 | 0.482442E+09 | 0.199389E+09 | 35681652.83 | 0.164074E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: G N2 APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 64264720.81 | 0.388054E+09 | 82402469.07 | 0.00 | 82402469.07 | 0.00 | 0.00 |
| February | 46204796.51 | 0.326781E+09 | 84808934.39 | 0.00 | 84808934.39 | 0.00 | 0.00 |
| March | 0.128734E+09 | 0.315989E+09 | 0.124821E+09 | 14118.42 | 0.124807E+09 | 0.00 | 0.00 |
| April | 0.260641E+09 | 0.165246E+09 | 0.147612E+09 | 1954846.33 | 0.145657E+09 | 0.00 | 0.00 |
| May | 0.373556E+09 | 0.106607E+09 | 0.179632E+09 | 15557674.50 | 0.164074E+09 | 0.00 | 0.00 |
| June | 0.568153E+09 | 36255190.88 | 0.199389E+09 | 35681652.83 | 0.163707E+09 | 0.00 | 0.00 |
| July | 0.506302E+09 | 27955454.46 | 0.175831E+09 | 17826399.52 | 0.158005E+09 | 0.00 | 0.00 |
| August | 0.415860E+09 | 38839562.19 | 0.142811E+09 | 3828713.07 | 0.138982E+09 | 0.00 | 0.00 |
| September | 0.331347E+09 | 61146602.74 | 0.130054E+09 | 77369.33 | 0.129977E+09 | 0.00 | 0.00 |
| October | 0.155630E+09 | 0.249019E+09 | 0.103920E+09 | 0.00 | 0.103920E+09 | 0.00 | 0.00 |
| November | 56477885.60 | 0.368465E+09 | 83791828.16 | 0.00 | 83791828.16 | 0.00 | 0.00 |
| December | 34854486.52 | 0.482559E+09 | 76971515.23 | 0.00 | 76971515.23 | 0.00 | 0.00 |
| Annual Sum or Average | 0.294203E+10 | 0.256692E+10 | 0.153204E+10 | 74940774.01 | 0.145710E+10 | 0.00 | 0.00 |
| Minimum of Months | 34854486.52 | 27955454.46 | 76971515.23 | 0.00 | 76971515.23 | 0.00 | 0.00 |
| Maximum of Months | 0.568153E+09 | 0.482559E+09 | 0.199389E+09 | 35681652.83 | 0.164074E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: G S1 APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.104114E+10 | 0.389514E+09 | 0.674562E+09 | 0.537910E+09 | 0.136651E+09 | 0.00 | 0.00 |
| February | 0.542801E+09 | 0.336872E+09 | 0.392743E+09 | 0.266565E+09 | 0.126178E+09 | 0.00 | 0.00 |
| March | 0.514874E+09 | 0.331134E+09 | 0.341866E+09 | 0.168768E+09 | 0.173098E+09 | 0.00 | 0.00 |
| April | 0.599454E+09 | 0.174385E+09 | 0.305655E+09 | 0.130378E+09 | 0.175278E+09 | 0.00 | 0.00 |
| May | 0.452832E+09 | 0.118910E+09 | 0.203995E+09 | 34012954.60 | 0.169982E+09 | 0.00 | 0.00 |
| June | 0.518628E+09 | 39059077.53 | 0.169595E+09 | 13859625.08 | 0.155735E+09 | 0.00 | 0.00 |
| July | 0.521911E+09 | 29148664.43 | 0.177966E+09 | 18215448.15 | 0.159750E+09 | 0.00 | 0.00 |
| August | 0.590305E+09 | 39855027.03 | 0.218092E+09 | 61301923.89 | 0.156790E+09 | 0.00 | 0.00 |
| September | 0.674488E+09 | 61395360.47 | 0.302743E+09 | 0.129507E+09 | 0.173237E+09 | 0.00 | 0.00 |
| October | 0.854369E+09 | 0.236876E+09 | 0.497543E+09 | 0.344406E+09 | 0.153137E+09 | 0.00 | 0.00 |
| November | 0.858991E+09 | 0.349884E+09 | 0.567433E+09 | 0.436105E+09 | 0.131328E+09 | 0.00 | 0.00 |
| December | 0.919381E+09 | 0.474255E+09 | 0.629958E+09 | 0.498533E+09 | 0.131424E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.808917E+10 | 0.258129E+10 | 0.448215E+10 | 0.263956E+10 | 0.184259E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.452832E+09 | 29148664.43 | 0.169595E+09 | 13859625.08 | 0.126178E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.104114E+10 | 0.474255E+09 | 0.674562E+09 | 0.537910E+09 | 0.175278E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: G S2 APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.104034E+10 | 0.390748E+09 | 0.674562E+09 | 0.537910E+09 | 0.136651E+09 | 0.00 | 0.00 |
| February | 0.541501E+09 | 0.339673E+09 | 0.392743E+09 | 0.266565E+09 | 0.126178E+09 | 0.00 | 0.00 |
| March | 0.513081E+09 | 0.333838E+09 | 0.341866E+09 | 0.168768E+09 | 0.173098E+09 | 0.00 | 0.00 |
| April | 0.597631E+09 | 0.176454E+09 | 0.305655E+09 | 0.130378E+09 | 0.175278E+09 | 0.00 | 0.00 |
| May | 0.450327E+09 | 0.121037E+09 | 0.203995E+09 | 34012954.60 | 0.169982E+09 | 0.00 | 0.00 |
| June | 0.514966E+09 | 40500635.29 | 0.169595E+09 | 13859625.08 | 0.155735E+09 | 0.00 | 0.00 |
| July | 0.517811E+09 | 30526060.52 | 0.177966E+09 | 18215448.15 | 0.159750E+09 | 0.00 | 0.00 |
| August | 0.586883E+09 | 41645465.16 | 0.218092E+09 | 61301923.89 | 0.156790E+09 | 0.00 | 0.00 |
| September | 0.671636E+09 | 63612948.82 | 0.302743E+09 | 0.129507E+09 | 0.173237E+09 | 0.00 | 0.00 |
| October | 0.852542E+09 | 0.239138E+09 | 0.497543E+09 | 0.344406E+09 | 0.153137E+09 | 0.00 | 0.00 |
| November | 0.858050E+09 | 0.351423E+09 | 0.567433E+09 | 0.436105E+09 | 0.131328E+09 | 0.00 | 0.00 |
| December | 0.918443E+09 | 0.475897E+09 | 0.629958E+09 | 0.498533E+09 | 0.131424E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.806321E+10 | 0.260449E+10 | 0.448215E+10 | 0.263956E+10 | 0.184259E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.450327E+09 | 30526060.52 | 0.169595E+09 | 13859625.08 | 0.126178E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.104034E+10 | 0.475897E+09 | 0.674562E+09 | 0.537910E+09 | 0.175278E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: M SW APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.127702E+10 | 0.641773E+09 | 0.858879E+09 | 0.652839E+09 | 0.206039E+09 | 0.00 | 0.00 |
| February | 0.668916E+09 | 0.576202E+09 | 0.526545E+09 | 0.331147E+09 | 0.195398E+09 | 0.00 | 0.00 |
| March | 0.758080E+09 | 0.561043E+09 | 0.539469E+09 | 0.263460E+09 | 0.276009E+09 | 0.00 | 0.00 |
| April | 0.110022E+10 | 0.292951E+09 | 0.597389E+09 | 0.296666E+09 | 0.300723E+09 | 0.00 | 0.00 |
| May | 0.101789E+10 | 0.201434E+09 | 0.506772E+09 | 0.203492E+09 | 0.303280E+09 | 0.00 | 0.00 |
| June | 0.119528E+10 | 66653496.57 | 0.481010E+09 | 0.197191E+09 | 0.283819E+09 | 0.00 | 0.00 |
| July | 0.105978E+10 | 47562729.83 | 0.412012E+09 | 0.127481E+09 | 0.284531E+09 | 0.00 | 0.00 |
| August | 0.109525E+10 | 63438722.22 | 0.441703E+09 | 0.173651E+09 | 0.268052E+09 | 0.00 | 0.00 |
| September | 0.107666E+10 | 96151812.20 | 0.491229E+09 | 0.208798E+09 | 0.282431E+09 | 0.00 | 0.00 |
| October | 0.117498E+10 | 0.383448E+09 | 0.696531E+09 | 0.458121E+09 | 0.238410E+09 | 0.00 | 0.00 |
| November | 0.108622E+10 | 0.565507E+09 | 0.744155E+09 | 0.542521E+09 | 0.201635E+09 | 0.00 | 0.00 |
| December | 0.107976E+10 | 0.761396E+09 | 0.777620E+09 | 0.582558E+09 | 0.195062E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.125901E+11 | 0.425756E+10 | 0.707331E+10 | 0.403793E+10 | 0.303539E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.668916E+09 | 47562729.83 | 0.412012E+09 | 0.127481E+09 | 0.195062E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.127702E+10 | 0.761396E+09 | 0.858879E+09 | 0.652839E+09 | 0.303280E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: M NW APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.327931E+09 | 0.646421E+09 | 0.266720E+09 | 0.114929E+09 | 0.151791E+09 | 0.00 | 0.00 |
| February | 0.190537E+09 | 0.566250E+09 | 0.218611E+09 | 64581883.73 | 0.154029E+09 | 0.00 | 0.00 |
| March | 0.378152E+09 | 0.550812E+09 | 0.322424E+09 | 94706832.85 | 0.227718E+09 | 0.00 | 0.00 |
| April | 0.766042E+09 | 0.284985E+09 | 0.439346E+09 | 0.168243E+09 | 0.271103E+09 | 0.00 | 0.00 |
| May | 0.934979E+09 | 0.185014E+09 | 0.482409E+09 | 0.185037E+09 | 0.297372E+09 | 0.00 | 0.00 |
| June | 0.124125E+10 | 61438857.19 | 0.510804E+09 | 0.219013E+09 | 0.291791E+09 | 0.00 | 0.00 |
| July | 0.104328E+10 | 45519747.89 | 0.409877E+09 | 0.127091E+09 | 0.282786E+09 | 0.00 | 0.00 |
| August | 0.922459E+09 | 62118514.42 | 0.366423E+09 | 0.116178E+09 | 0.250244E+09 | 0.00 | 0.00 |
| September | 0.738294E+09 | 96068192.11 | 0.318540E+09 | 79368703.14 | 0.239171E+09 | 0.00 | 0.00 |
| October | 0.491587E+09 | 0.392635E+09 | 0.302908E+09 | 0.113716E+09 | 0.189193E+09 | 0.00 | 0.00 |
| November | 0.307219E+09 | 0.572351E+09 | 0.260514E+09 | 0.106415E+09 | 0.154098E+09 | 0.00 | 0.00 |
| December | 0.226649E+09 | 0.761811E+09 | 0.224634E+09 | 84024867.93 | 0.140609E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.756838E+10 | 0.422542E+10 | 0.412321E+10 | 0.147330E+10 | 0.264990E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.190537E+09 | 45519747.89 | 0.218611E+09 | 64581883.73 | 0.140609E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.124125E+10 | 0.761811E+09 | 0.510804E+09 | 0.219013E+09 | 0.297372E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: M SE APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.124457E+10 | 0.631729E+09 | 0.850509E+09 | 0.648590E+09 | 0.201920E+09 | 0.00 | 0.00 |
| February | 0.694105E+09 | 0.569765E+09 | 0.548869E+09 | 0.355884E+09 | 0.192985E+09 | 0.00 | 0.00 |
| March | 0.764166E+09 | 0.543206E+09 | 0.557434E+09 | 0.279356E+09 | 0.278078E+09 | 0.00 | 0.00 |
| April | 0.108047E+10 | 0.265157E+09 | 0.604387E+09 | 0.308576E+09 | 0.295810E+09 | 0.00 | 0.00 |
| May | 0.101922E+10 | 0.178099E+09 | 0.523876E+09 | 0.223725E+09 | 0.300152E+09 | 0.00 | 0.00 |
| June | 0.120251E+10 | 57240513.09 | 0.492159E+09 | 0.214363E+09 | 0.277796E+09 | 0.00 | 0.00 |
| July | 0.113688E+10 | 42539514.95 | 0.459881E+09 | 0.177433E+09 | 0.282448E+09 | 0.00 | 0.00 |
| August | 0.116413E+10 | 58652038.82 | 0.485317E+09 | 0.213840E+09 | 0.271477E+09 | 0.00 | 0.00 |
| September | 0.110955E+10 | 89724746.66 | 0.514761E+09 | 0.231671E+09 | 0.283089E+09 | 0.00 | 0.00 |
| October | 0.119629E+10 | 0.372824E+09 | 0.717384E+09 | 0.478100E+09 | 0.239284E+09 | 0.00 | 0.00 |
| November | 0.105152E+10 | 0.557383E+09 | 0.731287E+09 | 0.534440E+09 | 0.196847E+09 | 0.00 | 0.00 |
| December | 0.107495E+10 | 0.754498E+09 | 0.784139E+09 | 0.591607E+09 | 0.192533E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.127383E+11 | 0.412082E+10 | 0.727000E+10 | 0.425758E+10 | 0.301242E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.694105E+09 | 42539514.95 | 0.459881E+09 | 0.177433E+09 | 0.192533E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.124457E+10 | 0.754498E+09 | 0.850509E+09 | 0.648590E+09 | 0.300152E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: M NE APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.255645E+09 | 0.595977E+09 | 0.258350E+09 | 0.110679E+09 | 0.147671E+09 | 0.00 | 0.00 |
| February | 0.187904E+09 | 0.535457E+09 | 0.240936E+09 | 89319636.19 | 0.151616E+09 | 0.00 | 0.00 |
| March | 0.373638E+09 | 0.523387E+09 | 0.340389E+09 | 0.110602E+09 | 0.229787E+09 | 0.00 | 0.00 |
| April | 0.749186E+09 | 0.260437E+09 | 0.446343E+09 | 0.180154E+09 | 0.266190E+09 | 0.00 | 0.00 |
| May | 0.952134E+09 | 0.177527E+09 | 0.499513E+09 | 0.205269E+09 | 0.294244E+09 | 0.00 | 0.00 |
| June | 0.125609E+10 | 59524531.44 | 0.521953E+09 | 0.236185E+09 | 0.285768E+09 | 0.00 | 0.00 |
| July | 0.112357E+10 | 43673886.28 | 0.457746E+09 | 0.177044E+09 | 0.280703E+09 | 0.00 | 0.00 |
| August | 0.993723E+09 | 59774437.90 | 0.410036E+09 | 0.156366E+09 | 0.253670E+09 | 0.00 | 0.00 |
| September | 0.770847E+09 | 89351230.74 | 0.342072E+09 | 0.102242E+09 | 0.239829E+09 | 0.00 | 0.00 |
| October | 0.492986E+09 | 0.363808E+09 | 0.323761E+09 | 0.133694E+09 | 0.190067E+09 | 0.00 | 0.00 |
| November | 0.240073E+09 | 0.531848E+09 | 0.247645E+09 | 98334421.63 | 0.149311E+09 | 0.00 | 0.00 |
| December | 0.175457E+09 | 0.707059E+09 | 0.231153E+09 | 93073405.93 | 0.138080E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.757125E+10 | 0.394783E+10 | 0.431990E+10 | 0.169296E+10 | 0.262694E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.175457E+09 | 43673886.28 | 0.231153E+09 | 89319636.19 | 0.138080E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.125609E+10 | 0.707059E+09 | 0.521953E+09 | 0.236185E+09 | 0.294244E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: M N1 APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 58611904.15 | 0.407570E+09 | 82402469.07 | 0.00 | 82402469.07 | 0.00 | 0.00 |
| February | 35380907.12 | 0.368421E+09 | 84808934.39 | 0.00 | 84808934.39 | 0.00 | 0.00 |
| March | 0.112440E+09 | 0.352091E+09 | 0.124821E+09 | 14118.42 | 0.124807E+09 | 0.00 | 0.00 |
| April | 0.257216E+09 | 0.169923E+09 | 0.147612E+09 | 1954846.33 | 0.145657E+09 | 0.00 | 0.00 |
| May | 0.372234E+09 | 0.107618E+09 | 0.179632E+09 | 15557674.50 | 0.164074E+09 | 0.00 | 0.00 |
| June | 0.571316E+09 | 35551491.65 | 0.199389E+09 | 35681652.83 | 0.163707E+09 | 0.00 | 0.00 |
| July | 0.513013E+09 | 26244127.65 | 0.175831E+09 | 17826399.52 | 0.158005E+09 | 0.00 | 0.00 |
| August | 0.423060E+09 | 36127362.98 | 0.142811E+09 | 3828713.07 | 0.138982E+09 | 0.00 | 0.00 |
| September | 0.338317E+09 | 56762870.53 | 0.130054E+09 | 77369.33 | 0.129977E+09 | 0.00 | 0.00 |
| October | 0.159344E+09 | 0.243789E+09 | 0.103920E+09 | 0.00 | 0.103920E+09 | 0.00 | 0.00 |
| November | 58496687.36 | 0.362233E+09 | 83791828.16 | 0.00 | 83791828.16 | 0.00 | 0.00 |
| December | 34982616.01 | 0.482855E+09 | 76971515.23 | 0.00 | 76971515.23 | 0.00 | 0.00 |
| Annual Sum or Average | 0.293441E+10 | 0.264919E+10 | 0.153204E+10 | 74940774.01 | 0.145710E+10 | 0.00 | 0.00 |
| Minimum of Months | 34982616.01 | 26244127.65 | 76971515.23 | 0.00 | 76971515.23 | 0.00 | 0.00 |
| Maximum of Months | 0.571316E+09 | 0.482855E+09 | 0.199389E+09 | 35681652.83 | 0.164074E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: M N2 APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 58514346.20 | 0.407485E+09 | 82402469.07 | 0.00 | 82402469.07 | 0.00 | 0.00 |
| February | 35157054.16 | 0.368882E+09 | 84808934.39 | 0.00 | 84808934.39 | 0.00 | 0.00 |
| March | 0.112214E+09 | 0.352307E+09 | 0.124821E+09 | 14118.42 | 0.124807E+09 | 0.00 | 0.00 |
| April | 0.257135E+09 | 0.169912E+09 | 0.147612E+09 | 1954846.33 | 0.145657E+09 | 0.00 | 0.00 |
| May | 0.372167E+09 | 0.107596E+09 | 0.179632E+09 | 15557674.50 | 0.164074E+09 | 0.00 | 0.00 |
| June | 0.571271E+09 | 35538323.13 | 0.199389E+09 | 35681652.83 | 0.163707E+09 | 0.00 | 0.00 |
| July | 0.512947E+09 | 26242326.81 | 0.175831E+09 | 17826399.52 | 0.158005E+09 | 0.00 | 0.00 |
| August | 0.422998E+09 | 36130353.68 | 0.142811E+09 | 3828713.07 | 0.138982E+09 | 0.00 | 0.00 |
| September | 0.338276E+09 | 56759982.58 | 0.130054E+09 | 77369.33 | 0.129977E+09 | 0.00 | 0.00 |
| October | 0.159227E+09 | 0.243887E+09 | 0.103920E+09 | 0.00 | 0.103920E+09 | 0.00 | 0.00 |
| November | 58423878.03 | 0.362162E+09 | 83791828.16 | 0.00 | 83791828.16 | 0.00 | 0.00 |
| December | 34886619.33 | 0.482938E+09 | 76971515.23 | 0.00 | 76971515.23 | 0.00 | 0.00 |
| Annual Sum or Average | 0.293322E+10 | 0.264984E+10 | 0.153204E+10 | 74940774.01 | 0.145710E+10 | 0.00 | 0.00 |
| Minimum of Months | 34886619.33 | 26242326.81 | 76971515.23 | 0.00 | 76971515.23 | 0.00 | 0.00 |
| Maximum of Months | 0.571271E+09 | 0.482938E+09 | 0.199389E+09 | 35681652.83 | 0.164074E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: M S1 APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.103339E+10 | 0.394223E+09 | 0.674562E+09 | 0.537910E+09 | 0.136651E+09 | 0.00 | 0.00 |
| February | 0.530133E+09 | 0.360356E+09 | 0.392743E+09 | 0.266565E+09 | 0.126178E+09 | 0.00 | 0.00 |
| March | 0.500228E+09 | 0.352807E+09 | 0.341866E+09 | 0.168768E+09 | 0.173098E+09 | 0.00 | 0.00 |
| April | 0.595163E+09 | 0.176928E+09 | 0.305655E+09 | 0.130378E+09 | 0.175278E+09 | 0.00 | 0.00 |
| May | 0.451583E+09 | 0.119662E+09 | 0.203995E+09 | 34012954.60 | 0.169982E+09 | 0.00 | 0.00 |
| June | 0.522158E+09 | 38091879.16 | 0.169595E+09 | 13859625.08 | 0.155735E+09 | 0.00 | 0.00 |
| July | 0.528578E+09 | 27163860.74 | 0.177966E+09 | 18215448.15 | 0.159750E+09 | 0.00 | 0.00 |
| August | 0.596883E+09 | 36525624.01 | 0.218092E+09 | 61301923.89 | 0.156790E+09 | 0.00 | 0.00 |
| September | 0.679710E+09 | 56092298.00 | 0.302743E+09 | 0.129507E+09 | 0.173237E+09 | 0.00 | 0.00 |
| October | 0.854254E+09 | 0.231819E+09 | 0.497543E+09 | 0.344406E+09 | 0.153137E+09 | 0.00 | 0.00 |
| November | 0.856659E+09 | 0.346231E+09 | 0.567433E+09 | 0.436105E+09 | 0.131328E+09 | 0.00 | 0.00 |
| December | 0.915942E+09 | 0.472945E+09 | 0.629958E+09 | 0.498533E+09 | 0.131424E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.806468E+10 | 0.261284E+10 | 0.448215E+10 | 0.263956E+10 | 0.184259E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.451583E+09 | 27163860.74 | 0.169595E+09 | 13859625.08 | 0.126178E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.103339E+10 | 0.472945E+09 | 0.674562E+09 | 0.537910E+09 | 0.175278E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: M S2 APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.103335E+10 | 0.394165E+09 | 0.674562E+09 | 0.537910E+09 | 0.136651E+09 | 0.00 | 0.00 |
| February | 0.530040E+09 | 0.360415E+09 | 0.392743E+09 | 0.266565E+09 | 0.126178E+09 | 0.00 | 0.00 |
| March | 0.500083E+09 | 0.352869E+09 | 0.341866E+09 | 0.168768E+09 | 0.173098E+09 | 0.00 | 0.00 |
| April | 0.595099E+09 | 0.176904E+09 | 0.305655E+09 | 0.130378E+09 | 0.175278E+09 | 0.00 | 0.00 |
| May | 0.451520E+09 | 0.119640E+09 | 0.203995E+09 | 34012954.60 | 0.169982E+09 | 0.00 | 0.00 |
| June | 0.522111E+09 | 38077419.63 | 0.169595E+09 | 13859625.08 | 0.155735E+09 | 0.00 | 0.00 |
| July | 0.528512E+09 | 27161800.87 | 0.177966E+09 | 18215448.15 | 0.159750E+09 | 0.00 | 0.00 |
| August | 0.596825E+09 | 36528414.42 | 0.218092E+09 | 61301923.89 | 0.156790E+09 | 0.00 | 0.00 |
| September | 0.679674E+09 | 56088337.10 | 0.302743E+09 | 0.129507E+09 | 0.173237E+09 | 0.00 | 0.00 |
| October | 0.854191E+09 | 0.231812E+09 | 0.497543E+09 | 0.344406E+09 | 0.153137E+09 | 0.00 | 0.00 |
| November | 0.856623E+09 | 0.346177E+09 | 0.567433E+09 | 0.436105E+09 | 0.131328E+09 | 0.00 | 0.00 |
| December | 0.915847E+09 | 0.472978E+09 | 0.629958E+09 | 0.498533E+09 | 0.131424E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.806387E+10 | 0.261282E+10 | 0.448215E+10 | 0.263956E+10 | 0.184259E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.451520E+09 | 27161800.87 | 0.169595E+09 | 13859625.08 | 0.126178E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.103335E+10 | 0.472978E+09 | 0.674562E+09 | 0.537910E+09 | 0.175278E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: T SW APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.128841E+10 | 0.574402E+09 | 0.858879E+09 | 0.652839E+09 | 0.206039E+09 | 0.00 | 0.00 |
| February | 0.683449E+09 | 0.496328E+09 | 0.526545E+09 | 0.331147E+09 | 0.195398E+09 | 0.00 | 0.00 |
| March | 0.769107E+09 | 0.500062E+09 | 0.539469E+09 | 0.263460E+09 | 0.276009E+09 | 0.00 | 0.00 |
| April | 0.108527E+10 | 0.270272E+09 | 0.597389E+09 | 0.296666E+09 | 0.300723E+09 | 0.00 | 0.00 |
| May | 0.997521E+09 | 0.189693E+09 | 0.506772E+09 | 0.203492E+09 | 0.303280E+09 | 0.00 | 0.00 |
| June | 0.116540E+10 | 63229625.15 | 0.481010E+09 | 0.197191E+09 | 0.283819E+09 | 0.00 | 0.00 |
| July | 0.103094E+10 | 45634154.12 | 0.412012E+09 | 0.127481E+09 | 0.284531E+09 | 0.00 | 0.00 |
| August | 0.106836E+10 | 60761838.92 | 0.441703E+09 | 0.173651E+09 | 0.268052E+09 | 0.00 | 0.00 |
| September | 0.105363E+10 | 91642069.93 | 0.491229E+09 | 0.208798E+09 | 0.282431E+09 | 0.00 | 0.00 |
| October | 0.117138E+10 | 0.346484E+09 | 0.696531E+09 | 0.458121E+09 | 0.238410E+09 | 0.00 | 0.00 |
| November | 0.109627E+10 | 0.504683E+09 | 0.744155E+09 | 0.542521E+09 | 0.201635E+09 | 0.00 | 0.00 |
| December | 0.109316E+10 | 0.689739E+09 | 0.777620E+09 | 0.582558E+09 | 0.195062E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.125029E+11 | 0.383293E+10 | 0.707331E+10 | 0.403793E+10 | 0.303539E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.683449E+09 | 45634154.12 | 0.412012E+09 | 0.127481E+09 | 0.195062E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.128841E+10 | 0.689739E+09 | 0.858879E+09 | 0.652839E+09 | 0.303280E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: T NW APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.339678E+09 | 0.579193E+09 | 0.266720E+09 | 0.114929E+09 | 0.151791E+09 | 0.00 | 0.00 |
| February | 0.201595E+09 | 0.497448E+09 | 0.218611E+09 | 64581883.73 | 0.154029E+09 | 0.00 | 0.00 |
| March | 0.390111E+09 | 0.493248E+09 | 0.322424E+09 | 94706832.85 | 0.227718E+09 | 0.00 | 0.00 |
| April | 0.755492E+09 | 0.262882E+09 | 0.439346E+09 | 0.168243E+09 | 0.271103E+09 | 0.00 | 0.00 |
| May | 0.916923E+09 | 0.176123E+09 | 0.482409E+09 | 0.185037E+09 | 0.297372E+09 | 0.00 | 0.00 |
| June | 0.121120E+10 | 59043782.26 | 0.510804E+09 | 0.219013E+09 | 0.291791E+09 | 0.00 | 0.00 |
| July | 0.101466E+10 | 44198314.13 | 0.409877E+09 | 0.127091E+09 | 0.282786E+09 | 0.00 | 0.00 |
| August | 0.897310E+09 | 60197301.36 | 0.366423E+09 | 0.116178E+09 | 0.250244E+09 | 0.00 | 0.00 |
| September | 0.718894E+09 | 92395089.85 | 0.318540E+09 | 79368703.14 | 0.239171E+09 | 0.00 | 0.00 |
| October | 0.493846E+09 | 0.348902E+09 | 0.302908E+09 | 0.113716E+09 | 0.189193E+09 | 0.00 | 0.00 |
| November | 0.319800E+09 | 0.506751E+09 | 0.260514E+09 | 0.106415E+09 | 0.154098E+09 | 0.00 | 0.00 |
| December | 0.235495E+09 | 0.702291E+09 | 0.224634E+09 | 84024867.93 | 0.140609E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.749500E+10 | 0.382267E+10 | 0.412321E+10 | 0.147330E+10 | 0.264990E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.201595E+09 | 44198314.13 | 0.218611E+09 | 64581883.73 | 0.140609E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.121120E+10 | 0.702291E+09 | 0.510804E+09 | 0.219013E+09 | 0.297372E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: T SE APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.125500E+10 | 0.565242E+09 | 0.850509E+09 | 0.648590E+09 | 0.201920E+09 | 0.00 | 0.00 |
| February | 0.708203E+09 | 0.490953E+09 | 0.548869E+09 | 0.355884E+09 | 0.192985E+09 | 0.00 | 0.00 |
| March | 0.776974E+09 | 0.485245E+09 | 0.557434E+09 | 0.279356E+09 | 0.278078E+09 | 0.00 | 0.00 |
| April | 0.106830E+10 | 0.247414E+09 | 0.604387E+09 | 0.308576E+09 | 0.295810E+09 | 0.00 | 0.00 |
| May | 0.100002E+10 | 0.168960E+09 | 0.523876E+09 | 0.223725E+09 | 0.300152E+09 | 0.00 | 0.00 |
| June | 0.117248E+10 | 54467295.82 | 0.492159E+09 | 0.214363E+09 | 0.277796E+09 | 0.00 | 0.00 |
| July | 0.110720E+10 | 40752622.56 | 0.459881E+09 | 0.177433E+09 | 0.282448E+09 | 0.00 | 0.00 |
| August | 0.113635E+10 | 56089026.15 | 0.485317E+09 | 0.213840E+09 | 0.271477E+09 | 0.00 | 0.00 |
| September | 0.108617E+10 | 85577090.48 | 0.514761E+09 | 0.231671E+09 | 0.283089E+09 | 0.00 | 0.00 |
| October | 0.119201E+10 | 0.337176E+09 | 0.717384E+09 | 0.478100E+09 | 0.239284E+09 | 0.00 | 0.00 |
| November | 0.106145E+10 | 0.496903E+09 | 0.731287E+09 | 0.534440E+09 | 0.196847E+09 | 0.00 | 0.00 |
| December | 0.108831E+10 | 0.682802E+09 | 0.784139E+09 | 0.591607E+09 | 0.192533E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.126525E+11 | 0.371158E+10 | 0.727000E+10 | 0.425758E+10 | 0.301242E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.708203E+09 | 40752622.56 | 0.459881E+09 | 0.177433E+09 | 0.192533E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.125500E+10 | 0.682802E+09 | 0.850509E+09 | 0.648590E+09 | 0.300152E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: T NE APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.275820E+09 | 0.535947E+09 | 0.258350E+09 | 0.110679E+09 | 0.147671E+09 | 0.00 | 0.00 |
| February | 0.205343E+09 | 0.468825E+09 | 0.240936E+09 | 89319636.19 | 0.151616E+09 | 0.00 | 0.00 |
| March | 0.390008E+09 | 0.469943E+09 | 0.340389E+09 | 0.110602E+09 | 0.229787E+09 | 0.00 | 0.00 |
| April | 0.741375E+09 | 0.243497E+09 | 0.446343E+09 | 0.180154E+09 | 0.266190E+09 | 0.00 | 0.00 |
| May | 0.933412E+09 | 0.169189E+09 | 0.499513E+09 | 0.205269E+09 | 0.294244E+09 | 0.00 | 0.00 |
| June | 0.122528E+10 | 57021946.22 | 0.521953E+09 | 0.236185E+09 | 0.285768E+09 | 0.00 | 0.00 |
| July | 0.109382E+10 | 42140106.60 | 0.457746E+09 | 0.177044E+09 | 0.280703E+09 | 0.00 | 0.00 |
| August | 0.967410E+09 | 57654330.13 | 0.410036E+09 | 0.156366E+09 | 0.253670E+09 | 0.00 | 0.00 |
| September | 0.751078E+09 | 86027321.06 | 0.342072E+09 | 0.102242E+09 | 0.239829E+09 | 0.00 | 0.00 |
| October | 0.499921E+09 | 0.325561E+09 | 0.323761E+09 | 0.133694E+09 | 0.190067E+09 | 0.00 | 0.00 |
| November | 0.259528E+09 | 0.471093E+09 | 0.247645E+09 | 98334421.63 | 0.149311E+09 | 0.00 | 0.00 |
| December | 0.191241E+09 | 0.651769E+09 | 0.231153E+09 | 93073405.93 | 0.138080E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.753423E+10 | 0.357867E+10 | 0.431990E+10 | 0.169296E+10 | 0.262694E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.191241E+09 | 42140106.60 | 0.231153E+09 | 89319636.19 | 0.138080E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.122528E+10 | 0.651769E+09 | 0.521953E+09 | 0.236185E+09 | 0.294244E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: T N1 APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 69745705.03 | 0.358792E+09 | 82402469.07 | 0.00 | 82402469.07 | 0.00 | 0.00 |
| February | 45128223.18 | 0.312522E+09 | 84808934.39 | 0.00 | 84808934.39 | 0.00 | 0.00 |
| March | 0.123020E+09 | 0.312058E+09 | 0.124821E+09 | 14118.42 | 0.124807E+09 | 0.00 | 0.00 |
| April | 0.252844E+09 | 0.159420E+09 | 0.147612E+09 | 1954846.33 | 0.145657E+09 | 0.00 | 0.00 |
| May | 0.363940E+09 | 0.104132E+09 | 0.179632E+09 | 15557674.50 | 0.164074E+09 | 0.00 | 0.00 |
| June | 0.556385E+09 | 34787450.18 | 0.199389E+09 | 35681652.83 | 0.163707E+09 | 0.00 | 0.00 |
| July | 0.498190E+09 | 25972072.83 | 0.175831E+09 | 17826399.52 | 0.158005E+09 | 0.00 | 0.00 |
| August | 0.410241E+09 | 35685162.15 | 0.142811E+09 | 3828713.07 | 0.138982E+09 | 0.00 | 0.00 |
| September | 0.328660E+09 | 55500577.83 | 0.130054E+09 | 77369.33 | 0.129977E+09 | 0.00 | 0.00 |
| October | 0.162492E+09 | 0.217387E+09 | 0.103920E+09 | 0.00 | 0.103920E+09 | 0.00 | 0.00 |
| November | 68067422.78 | 0.316249E+09 | 83791828.16 | 0.00 | 83791828.16 | 0.00 | 0.00 |
| December | 42868935.84 | 0.435950E+09 | 76971515.23 | 0.00 | 76971515.23 | 0.00 | 0.00 |
| Annual Sum or Average | 0.292158E+10 | 0.236846E+10 | 0.153204E+10 | 74940774.01 | 0.145710E+10 | 0.00 | 0.00 |
| Minimum of Months | 42868935.84 | 25972072.83 | 76971515.23 | 0.00 | 76971515.23 | 0.00 | 0.00 |
| Maximum of Months | 0.556385E+09 | 0.435950E+09 | 0.199389E+09 | 35681652.83 | 0.164074E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: T N2 APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 69363978.50 | 0.358481E+09 | 82402469.07 | 0.00 | 82402469.07 | 0.00 | 0.00 |
| February | 44765464.07 | 0.312532E+09 | 84808934.39 | 0.00 | 84808934.39 | 0.00 | 0.00 |
| March | 0.122526E+09 | 0.312007E+09 | 0.124821E+09 | 14118.42 | 0.124807E+09 | 0.00 | 0.00 |
| April | 0.252558E+09 | 0.159310E+09 | 0.147612E+09 | 1954846.33 | 0.145657E+09 | 0.00 | 0.00 |
| May | 0.363777E+09 | 0.104051E+09 | 0.179632E+09 | 15557674.50 | 0.164074E+09 | 0.00 | 0.00 |
| June | 0.556302E+09 | 34754037.58 | 0.199389E+09 | 35681652.83 | 0.163707E+09 | 0.00 | 0.00 |
| July | 0.498084E+09 | 25955794.17 | 0.175831E+09 | 17826399.52 | 0.158005E+09 | 0.00 | 0.00 |
| August | 0.410135E+09 | 35671237.48 | 0.142811E+09 | 3828713.07 | 0.138982E+09 | 0.00 | 0.00 |
| September | 0.328580E+09 | 55480572.56 | 0.130054E+09 | 77369.33 | 0.129977E+09 | 0.00 | 0.00 |
| October | 0.162151E+09 | 0.217338E+09 | 0.103920E+09 | 0.00 | 0.103920E+09 | 0.00 | 0.00 |
| November | 67770254.33 | 0.315901E+09 | 83791828.16 | 0.00 | 83791828.16 | 0.00 | 0.00 |
| December | 42625612.44 | 0.435754E+09 | 76971515.23 | 0.00 | 76971515.23 | 0.00 | 0.00 |
| Annual Sum or Average | 0.291864E+10 | 0.236723E+10 | 0.153204E+10 | 74940774.01 | 0.145710E+10 | 0.00 | 0.00 |
| Minimum of Months | 42625612.44 | 25955794.17 | 76971515.23 | 0.00 | 76971515.23 | 0.00 | 0.00 |
| Maximum of Months | 0.556302E+09 | 0.435754E+09 | 0.199389E+09 | 35681652.83 | 0.164074E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: T S1 APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.104257E+10 | 0.354462E+09 | 0.674562E+09 | 0.537910E+09 | 0.136651E+09 | 0.00 | 0.00 |
| February | 0.541661E+09 | 0.309365E+09 | 0.392743E+09 | 0.266565E+09 | 0.126178E+09 | 0.00 | 0.00 |
| March | 0.509754E+09 | 0.315700E+09 | 0.341866E+09 | 0.168768E+09 | 0.173098E+09 | 0.00 | 0.00 |
| April | 0.587764E+09 | 0.166204E+09 | 0.305655E+09 | 0.130378E+09 | 0.175278E+09 | 0.00 | 0.00 |
| May | 0.441813E+09 | 0.114342E+09 | 0.203995E+09 | 34012954.60 | 0.169982E+09 | 0.00 | 0.00 |
| June | 0.507481E+09 | 36683451.22 | 0.169595E+09 | 13859625.08 | 0.155735E+09 | 0.00 | 0.00 |
| July | 0.513714E+09 | 26508780.56 | 0.177966E+09 | 18215448.15 | 0.159750E+09 | 0.00 | 0.00 |
| August | 0.582998E+09 | 35546705.61 | 0.218092E+09 | 61301923.89 | 0.156790E+09 | 0.00 | 0.00 |
| September | 0.667561E+09 | 54234416.89 | 0.302743E+09 | 0.129507E+09 | 0.173237E+09 | 0.00 | 0.00 |
| October | 0.852701E+09 | 0.212816E+09 | 0.497543E+09 | 0.344406E+09 | 0.153137E+09 | 0.00 | 0.00 |
| November | 0.864089E+09 | 0.312441E+09 | 0.567433E+09 | 0.436105E+09 | 0.131328E+09 | 0.00 | 0.00 |
| December | 0.928855E+09 | 0.425019E+09 | 0.629958E+09 | 0.498533E+09 | 0.131424E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.804097E+10 | 0.236332E+10 | 0.448215E+10 | 0.263956E+10 | 0.184259E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.441813E+09 | 26508780.56 | 0.169595E+09 | 13859625.08 | 0.126178E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.104257E+10 | 0.425019E+09 | 0.674562E+09 | 0.537910E+09 | 0.175278E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: T S2 APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.104232E+10 | 0.354291E+09 | 0.674562E+09 | 0.537910E+09 | 0.136651E+09 | 0.00 | 0.00 |
| February | 0.541325E+09 | 0.309360E+09 | 0.392743E+09 | 0.266565E+09 | 0.126178E+09 | 0.00 | 0.00 |
| March | 0.509339E+09 | 0.315626E+09 | 0.341866E+09 | 0.168768E+09 | 0.173098E+09 | 0.00 | 0.00 |
| April | 0.587521E+09 | 0.166084E+09 | 0.305655E+09 | 0.130378E+09 | 0.175278E+09 | 0.00 | 0.00 |
| May | 0.441647E+09 | 0.114261E+09 | 0.203995E+09 | 34012954.60 | 0.169982E+09 | 0.00 | 0.00 |
| June | 0.507394E+09 | 36648753.26 | 0.169595E+09 | 13859625.08 | 0.155735E+09 | 0.00 | 0.00 |
| July | 0.513609E+09 | 26492619.45 | 0.177966E+09 | 18215448.15 | 0.159750E+09 | 0.00 | 0.00 |
| August | 0.582899E+09 | 35533027.51 | 0.218092E+09 | 61301923.89 | 0.156790E+09 | 0.00 | 0.00 |
| September | 0.667490E+09 | 54213075.71 | 0.302743E+09 | 0.129507E+09 | 0.173237E+09 | 0.00 | 0.00 |
| October | 0.852465E+09 | 0.212735E+09 | 0.497543E+09 | 0.344406E+09 | 0.153137E+09 | 0.00 | 0.00 |
| November | 0.863891E+09 | 0.312225E+09 | 0.567433E+09 | 0.436105E+09 | 0.131328E+09 | 0.00 | 0.00 |
| December | 0.928583E+09 | 0.424910E+09 | 0.629958E+09 | 0.498533E+09 | 0.131424E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.803848E+10 | 0.236238E+10 | 0.448215E+10 | 0.263956E+10 | 0.184259E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.441647E+09 | 26492619.45 | 0.169595E+09 | 13859625.08 | 0.126178E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.104232E+10 | 0.424910E+09 | 0.674562E+09 | 0.537910E+09 | 0.175278E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: T CORRIDOR
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 54465856.57 | 59060437.37 | 42219423.49 | 26557935.06 | 15661488.43 | 0.00 | 0.00 |
| February | 42620350.73 | 52178775.92 | 37463240.46 | 21432610.27 | 16030630.19 | 0.00 | 0.00 |
| March | 67623300.66 | 51285312.90 | 51726474.28 | 26536036.47 | 25190437.81 | 0.00 | 0.00 |
| April | 0.117846E+09 | 27947539.42 | 71681838.54 | 42759533.98 | 28922304.56 | 0.00 | 0.00 |
| May | 0.134507E+09 | 19833989.85 | 76756839.06 | 45522060.77 | 31234778.29 | 0.00 | 0.00 |
| June | 0.156191E+09 | 7536648.09 | 77400548.14 | 48111558.36 | 29288989.79 | 0.00 | 0.00 |
| July | 0.137618E+09 | 6195275.13 | 67646668.88 | 38204880.19 | 29441788.69 | 0.00 | 0.00 |
| August | 0.129060E+09 | 8400555.79 | 64121703.19 | 36602037.97 | 27519665.23 | 0.00 | 0.00 |
| September | 97627366.30 | 11621418.97 | 50874495.05 | 24514852.10 | 26359642.94 | 0.00 | 0.00 |
| October | 82417841.75 | 36879869.80 | 52751679.28 | 32080455.71 | 20671223.57 | 0.00 | 0.00 |
| November | 49718735.09 | 52849660.32 | 39317339.14 | 23595744.73 | 15721594.41 | 0.00 | 0.00 |
| December | 42273196.02 | 69954240.63 | 36996519.24 | 22333342.60 | 14663176.65 | 0.00 | 0.00 |
| Annual Sum or Average | 0.111197E+10 | 0.403744E+09 | 0.668957E+09 | 0.388251E+09 | 0.280706E+09 | 0.00 | 0.00 |
| Minimum of Months | 42273196.02 | 6195275.13 | 36996519.24 | 21432610.27 | 14663176.65 | 0.00 | 0.00 |
| Maximum of Months | 0.156191E+09 | 69954240.63 | 77400548.14 | 48111558.36 | 31234778.29 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: G CORRIDOR
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.157925E+09 | 0.181947E+09 | 0.125740E+09 | 79096139.91 | 46643810.12 | 0.00 | 0.00 |
| February | 0.128926E+09 | 0.154525E+09 | 0.111575E+09 | 63831647.17 | 47743206.14 | 0.00 | 0.00 |
| March | 0.203360E+09 | 0.149664E+09 | 0.154054E+09 | 79030920.45 | 75023392.79 | 0.00 | 0.00 |
| April | 0.347575E+09 | 87955640.31 | 0.213486E+09 | 0.127349E+09 | 86137820.68 | 0.00 | 0.00 |
| May | 0.393779E+09 | 65521049.86 | 0.228601E+09 | 0.135576E+09 | 93024942.93 | 0.00 | 0.00 |
| June | 0.451962E+09 | 28258637.51 | 0.230518E+09 | 0.143288E+09 | 87229900.54 | 0.00 | 0.00 |
| July | 0.396007E+09 | 24393765.36 | 0.201469E+09 | 0.113784E+09 | 87684973.71 | 0.00 | 0.00 |
| August | 0.371702E+09 | 32903033.82 | 0.190970E+09 | 0.109010E+09 | 81960411.68 | 0.00 | 0.00 |
| September | 0.280543E+09 | 43730862.81 | 0.151517E+09 | 73011330.41 | 78505576.64 | 0.00 | 0.00 |
| October | 0.235539E+09 | 0.123934E+09 | 0.157108E+09 | 95543580.74 | 61564048.11 | 0.00 | 0.00 |
| November | 0.140451E+09 | 0.172001E+09 | 0.117097E+09 | 70273999.92 | 46822820.69 | 0.00 | 0.00 |
| December | 0.120381E+09 | 0.220444E+09 | 0.110185E+09 | 66514252.21 | 43670589.18 | 0.00 | 0.00 |
| Annual Sum or Average | 0.322815E+10 | 0.128528E+10 | 0.199232E+10 | 0.115631E+10 | 0.836011E+09 | 0.00 | 0.00 |
| Minimum of Months | 0.120381E+09 | 24393765.36 | 0.110185E+09 | 63831647.17 | 43670589.18 | 0.00 | 0.00 |
| Maximum of Months | 0.451962E+09 | 0.220444E+09 | 0.230518E+09 | 0.143288E+09 | 93024942.93 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: M CORRIDOR
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 49723179.56 | 66567708.06 | 42219423.49 | 26557935.06 | 15661488.43 | 0.00 | 0.00 |
| February | 39012994.21 | 61340920.60 | 37463240.46 | 21432610.27 | 16030630.19 | 0.00 | 0.00 |
| March | 63059872.49 | 57509261.80 | 51726474.28 | 26536036.47 | 25190437.81 | 0.00 | 0.00 |
| April | 0.116693E+09 | 29668863.72 | 71681838.54 | 42759533.98 | 28922304.56 | 0.00 | 0.00 |
| May | 0.134647E+09 | 20770944.46 | 76756839.06 | 45522060.77 | 31234778.29 | 0.00 | 0.00 |
| June | 0.158729E+09 | 7764608.90 | 77400548.14 | 48111558.36 | 29288989.79 | 0.00 | 0.00 |
| July | 0.140435E+09 | 6266807.90 | 67646668.88 | 38204880.19 | 29441788.69 | 0.00 | 0.00 |
| August | 0.131414E+09 | 8549844.89 | 64121703.19 | 36602037.97 | 27519665.23 | 0.00 | 0.00 |
| September | 99143769.37 | 11927615.50 | 50874495.05 | 24514852.10 | 26359642.94 | 0.00 | 0.00 |
| October | 80008125.77 | 40906588.72 | 52751679.28 | 32080455.71 | 20671223.57 | 0.00 | 0.00 |
| November | 45743839.49 | 59990445.34 | 39317339.14 | 23595744.73 | 15721594.41 | 0.00 | 0.00 |
| December | 37981924.49 | 79048348.38 | 36996519.24 | 22333342.60 | 14663176.65 | 0.00 | 0.00 |
| Annual Sum or Average | 0.109659E+10 | 0.450312E+09 | 0.668957E+09 | 0.388251E+09 | 0.280706E+09 | 0.00 | 0.00 |
| Minimum of Months | 37981924.49 | 6266807.90 | 36996519.24 | 21432610.27 | 14663176.65 | 0.00 | 0.00 |
| Maximum of Months | 0.158729E+09 | 79048348.38 | 77400548.14 | 48111558.36 | 31234778.29 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
| January | 14.83 | 7.47 | -0.8 | 2.99 | -0.8 | 34.08 | 283.26 | 0.00 |
| February | 12.72 | 9.35 | 6.24 | 2.64 | 2.53 | 52.02 | 191.85 | 0.02 |
| March | 15.42 | 8.67 | 1.96 | 3.53 | 3.02 | 74.19 | 207.67 | 0.01 |
| April | 23.31 | 10.14 | -4.1 | 3.42 | 6.81 | 72.47 | 350.22 | 0.00 |
| May | 26.31 | 11.07 | -4.9 | 3.62 | 8.60 | 75.22 | 359.64 | 0.00 |
| June | 31.20 | 14.28 | 0.18 | 3.69 | 15.53 | 67.31 | 396.02 | 0.00 |
| July | 30.42 | 17.99 | 9.86 | 3.72 | 19.28 | 82.46 | 278.62 | 0.02 |
| August | 29.82 | 18.15 | 11.14 | 3.33 | 18.26 | 71.82 | 270.19 | 0.02 |
| September | 27.75 | 17.59 | 11.45 | 3.72 | 17.29 | 82.54 | 200.28 | 0.01 |
| October | 20.87 | 10.99 | 1.63 | 3.42 | 6.03 | 49.01 | 269.00 | 0.00 |
| November | 15.43 | 8.80 | 1.49 | 3.02 | 1.83 | 40.49 | 251.35 | 0.01 |
| December | 11.86 | 4.25 | -5.9 | 2.21 | -4.3 | 34.74 | 244.35 | 0.00 |
| Annual Sum or Average | 21.70 | 11.57 | 2.33 | 3.28 | 7.86 | 61.39 | 275.62 | 0.01 |
| Minimum of Months | 11.86 | 4.25 | -5.9 | 2.21 | -4.3 | 34.08 | 191.85 | 0.00 |
| Maximum of Months | 31.20 | 18.15 | 11.45 | 3.72 | 19.28 | 82.54 | 396.02 | 0.02 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
| January | 29.00 | 31-JAN-15:00 | 10.73 | -14.0 | 2.10 | 7.75 | 109.00 | 697.00 |
| February | 22.00 | 18-FEB-14:09 | 14.42 | 9.67 | 5.20 | 14.10 | 264.00 | 225.33 |
| March | 28.80 | 16-MAR-15:20 | 13.79 | 1.47 | 3.77 | 14.35 | 156.17 | 666.17 |
| April | 35.00 | 14-APR-14:00 | 14.57 | -4.0 | 1.50 | 19.70 | 150.00 | 819.50 |
| May | 37.00 | 15-MAY-16:00 | 15.57 | -2.0 | 4.60 | 20.75 | 127.50 | 679.00 |
| June | 42.00 | 16-JUN-15:00 | 16.74 | -5.0 | 5.70 | 25.49 | 135.00 | 753.50 |
| July | 40.00 | 12-JUL-13:00 | 19.40 | 7.00 | 2.10 | 27.95 | 147.00 | 3.00 |
| August | 41.00 | 25-AUG-14:09 | 17.27 | -0.7 | 3.43 | 25.74 | 162.33 | 768.67 |
| September | 38.30 | 08-SEP-14:00 | 19.81 | 10.00 | 3.00 | 25.82 | 142.00 | 699.00 |
| October | 37.00 | 01-OCT-12:00 | 19.01 | 9.00 | 4.10 | 27.14 | 262.50 | 136.00 |
| November | 29.00 | 01-NOV-14:00 | 16.20 | 8.00 | 2.60 | 16.49 | 73.50 | 907.50 |
| December | 26.00 | 21-DEC-14:00 | 10.90 | -5.0 | 2.60 | 7.35 | 68.50 | 756.50 |
| Annual Sum or Average | ||||||||
| Minimum of Months | 22.00 | 10.73 | -14.0 | 1.50 | 7.35 | 68.50 | 3.00 | |
| Maximum of Months | 42.00 | 19.81 | 10.00 | 5.70 | 27.95 | 264.00 | 907.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
| January | 0.50 | 01-JAN-07:00 | -1.2 | -3.3 | 3.30 | -16.2 | 17.50 | 352.00 |
| February | 5.00 | 01-FEB-04:00 | 3.59 | 2.00 | 3.10 | -10.7 | 0.00 | 0.00 |
| March | 0.50 | 26-MAR-03:00 | -2.4 | -6.7 | 2.50 | -17.0 | 0.00 | 0.00 |
| April | 8.00 | 21-APR-03:00 | 0.42 | -14.0 | 1.00 | -11.7 | 0.00 | 0.00 |
| May | 12.00 | 01-MAY-03:00 | 3.97 | -7.0 | 2.60 | -6.2 | 0.00 | 0.00 |
| June | 18.00 | 21-JUN-04:00 | 8.24 | -2.0 | 1.50 | 3.48 | 0.00 | 0.00 |
| July | 18.00 | 01-JUL-05:00 | 6.53 | -9.0 | 3.10 | -1.2 | 16.00 | 325.00 |
| August | 17.00 | 05-AUG-17:00 | 15.02 | 14.00 | 5.70 | 11.46 | 29.00 | 0.00 |
| September | 16.60 | 22-SEP-05:00 | 13.83 | 12.20 | 3.00 | 4.92 | 0.00 | 0.00 |
| October | 5.00 | 25-OCT-05:00 | 0.48 | -6.0 | 3.10 | -12.7 | 0.00 | 0.00 |
| November | 0.00 | 23-NOV-05:00 | -2.5 | -6.0 | 2.10 | -17.3 | 0.00 | 0.00 |
| December | -1.1 | 07-DEC-04:00 | -5.6 | -16.0 | 3.10 | -20.8 | 0.00 | 0.00 |
| Annual Sum or Average | ||||||||
| Minimum of Months | -1.1 | -5.6 | -16.0 | 1.00 | -20.8 | 0.00 | 0.00 | |
| Maximum of Months | 18.00 | 15.02 | 14.00 | 5.70 | 11.46 | 29.00 | 352.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| SITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
| January | 16.66 | 08-JAN-15:00 | 18.00 | 16.00 | 4.60 | 11.46 | 102.00 | 332.00 |
| February | 14.73 | 18-FEB-17:00 | 16.00 | 14.00 | 6.20 | 10.50 | 0.00 | 0.00 |
| March | 15.18 | 17-MAR-10:00 | 25.50 | 8.30 | 2.50 | 18.46 | 167.50 | 459.00 |
| April | 15.71 | 11-APR-14:00 | 33.00 | 3.00 | 2.10 | 15.94 | 178.50 | 758.00 |
| May | 15.57 | 15-MAY-16:00 | 37.00 | -2.0 | 4.60 | 20.75 | 127.50 | 679.00 |
| June | 23.18 | 17-JUN-15:00 | 41.00 | 16.00 | 3.60 | 31.13 | 257.00 | 9.00 |
| July | 23.11 | 13-JUL-17:00 | 26.00 | 22.00 | 4.60 | 22.13 | 79.00 | 56.50 |
| August | 22.19 | 16-AUG-10:00 | 35.00 | 17.00 | 2.10 | 24.33 | 140.50 | 837.00 |
| September | 22.23 | 01-SEP-11:00 | 34.40 | 17.20 | 4.60 | 23.82 | 193.50 | 725.50 |
| October | 21.53 | 01-OCT-17:00 | 32.00 | 17.00 | 2.10 | 25.33 | 30.50 | 1.50 |
| November | 18.59 | 12-NOV-14:00 | 20.00 | 18.00 | 3.10 | 15.39 | 115.00 | 0.00 |
| December | 12.06 | 12-DEC-12:00 | 20.00 | 6.00 | 1.50 | 12.60 | 182.50 | 6.00 |
| Annual Sum or Average | ||||||||
| Minimum of Months | 12.06 | 16.00 | -2.0 | 1.50 | 10.50 | 0.00 | 0.00 | |
| Maximum of Months | 23.18 | 41.00 | 22.00 | 6.20 | 31.13 | 257.00 | 837.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| SITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
| January | 16.00 | 08-JAN-15:00 | 18.00 | 16.66 | 4.60 | 11.46 | 102.00 | 332.00 |
| February | 14.00 | 18-FEB-17:00 | 16.00 | 14.73 | 6.20 | 10.50 | 0.00 | 0.00 |
| March | 13.30 | 06-MAR-10:00 | 14.40 | 13.70 | 6.10 | 10.69 | 254.50 | 82.00 |
| April | 8.00 | 15-APR-20:00 | 23.00 | 14.00 | 6.20 | 7.75 | 0.00 | 0.00 |
| May | 9.00 | 26-MAY-02:00 | 21.00 | 13.75 | 3.60 | 16.30 | 0.00 | 0.00 |
| June | 16.00 | 17-JUN-15:00 | 41.00 | 23.18 | 3.60 | 31.13 | 257.00 | 9.00 |
| July | 22.00 | 13-JUL-17:00 | 26.00 | 23.11 | 4.60 | 22.13 | 79.00 | 56.50 |
| August | 20.00 | 09-AUG-17:00 | 25.00 | 21.44 | 5.10 | 19.17 | 35.00 | 0.00 |
| September | 20.50 | 02-SEP-22:10 | 22.62 | 21.05 | 3.18 | 20.17 | 0.00 | 0.00 |
| October | 19.00 | 03-OCT-02:00 | 23.00 | 20.15 | 2.10 | 10.30 | 0.00 | 0.00 |
| November | 18.00 | 12-NOV-14:00 | 20.00 | 18.59 | 3.10 | 15.39 | 115.00 | 0.00 |
| December | 10.00 | 12-DEC-23:00 | 12.00 | 10.87 | 1.50 | 7.55 | 0.00 | 0.00 |
| Annual Sum or Average | ||||||||
| Minimum of Months | 8.00 | 12.00 | 10.87 | 1.50 | 7.55 | 0.00 | 0.00 | |
| Maximum of Months | 22.00 | 41.00 | 23.18 | 6.20 | 31.13 | 257.00 | 332.00 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| SITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
| January | 18.00 | 13.00 | 16.00 | 18.65 | 31.23 | 0.00 |
| February | 18.00 | 13.00 | 16.00 | 19.06 | 29.93 | 0.00 |
| March | 18.00 | 13.00 | 16.00 | 20.99 | 39.76 | 0.00 |
| April | 18.00 | 13.00 | 16.00 | 24.03 | 60.89 | 0.00 |
| May | 18.00 | 13.00 | 16.00 | 27.32 | 65.75 | 0.00 |
| June | 18.00 | 13.00 | 16.00 | 29.99 | 69.24 | 0.00 |
| July | 18.00 | 13.00 | 16.00 | 31.31 | 56.42 | 0.00 |
| August | 18.00 | 13.00 | 16.00 | 30.91 | 52.05 | 0.00 |
| September | 18.00 | 13.00 | 16.00 | 28.91 | 42.71 | 0.00 |
| October | 18.00 | 13.00 | 16.00 | 25.85 | 39.20 | 0.00 |
| November | 18.00 | 13.00 | 16.00 | 22.56 | 30.64 | 0.00 |
| December | 18.00 | 13.00 | 16.00 | 19.93 | 27.41 | 0.00 |
| Annual Sum or Average | 18.00 | 13.00 | 16.00 | 24.99 | 45.50 | 0.00 |
| Minimum of Months | 18.00 | 13.00 | 16.00 | 18.65 | 27.41 | 0.00 |
| Maximum of Months | 18.00 | 13.00 | 16.00 | 31.31 | 69.24 | 0.00 |
Report: WaterHeaterReportMonthly
For: G SW APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.105163E+10 | -877049235.7 | 0.00 | 0.00 | 744.00 | 0.00 | -174584793.7 | 59.44 | 0.00 | 0.00 |
| February | 0.945936E+09 | -784163283.8 | 0.00 | 0.00 | 672.00 | 0.00 | -161772401.6 | 59.44 | 0.00 | 0.00 |
| March | 0.100437E+10 | -826658245.1 | 0.00 | 0.00 | 744.00 | 0.00 | -177716436.1 | 59.44 | 0.00 | 0.00 |
| April | 0.904004E+09 | -736853354.5 | 0.00 | 0.00 | 720.00 | 0.00 | -167150445.0 | 59.44 | 0.00 | 0.00 |
| May | 0.863069E+09 | -690572221.6 | 0.00 | 0.00 | 744.00 | 0.00 | -172496896.0 | 59.44 | 0.00 | 0.00 |
| June | 0.779655E+09 | -612730924.6 | 0.00 | 0.00 | 720.00 | 0.00 | -166923739.5 | 59.44 | 0.00 | 0.00 |
| July | 0.777320E+09 | -604837140.8 | 0.00 | 0.00 | 744.00 | 0.00 | -172482441.1 | 59.44 | 0.00 | 0.00 |
| August | 0.785933E+09 | -613445952.4 | 0.00 | 0.00 | 744.00 | 0.00 | -172486876.7 | 59.44 | 0.00 | 0.00 |
| September | 0.802172E+09 | -635249058.6 | 0.00 | 0.00 | 720.00 | 0.00 | -166922484.0 | 59.44 | 0.00 | 0.00 |
| October | 0.894819E+09 | -722204740.8 | 0.00 | 0.00 | 744.00 | 0.00 | -172614112.1 | 59.44 | 0.00 | 0.00 |
| November | 0.934855E+09 | -767349139.7 | 0.00 | 0.00 | 720.00 | 0.00 | -167506144.9 | 59.44 | 0.00 | 0.00 |
| December | 0.102515E+10 | -849531395.2 | 0.00 | 0.00 | 744.00 | 0.00 | -175615849.2 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.107689E+11 | -0.872064E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.204827E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.777320E+09 | -877049235.7 | 0.00 | 0.00 | 672.00 | 0.00 | -177716436.1 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.105163E+10 | -604837140.8 | 0.00 | 0.00 | 744.00 | 0.00 | -161772401.6 | 59.44 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: G NW APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.105613E+10 | -877043991.3 | 0.00 | 0.00 | 744.00 | 0.00 | -179088575.8 | 59.44 | 0.00 | 0.00 |
| February | 0.950617E+09 | -784158067.7 | 0.00 | 0.00 | 672.00 | 0.00 | -166459097.2 | 59.44 | 0.00 | 0.00 |
| March | 0.100726E+10 | -826653008.9 | 0.00 | 0.00 | 744.00 | 0.00 | -180608066.1 | 59.44 | 0.00 | 0.00 |
| April | 0.904202E+09 | -736855619.9 | 0.00 | 0.00 | 720.00 | 0.00 | -167346073.5 | 59.44 | 0.00 | 0.00 |
| May | 0.863072E+09 | -690572054.0 | 0.00 | 0.00 | 744.00 | 0.00 | -172499499.2 | 59.44 | 0.00 | 0.00 |
| June | 0.779655E+09 | -612732048.2 | 0.00 | 0.00 | 720.00 | 0.00 | -166922907.3 | 59.44 | 0.00 | 0.00 |
| July | 0.777320E+09 | -604836948.5 | 0.00 | 0.00 | 744.00 | 0.00 | -172482590.4 | 59.44 | 0.00 | 0.00 |
| August | 0.785933E+09 | -613445887.8 | 0.00 | 0.00 | 744.00 | 0.00 | -172486942.3 | 59.44 | 0.00 | 0.00 |
| September | 0.802172E+09 | -635249335.1 | 0.00 | 0.00 | 720.00 | 0.00 | -166922352.7 | 59.44 | 0.00 | 0.00 |
| October | 0.895165E+09 | -722204757.4 | 0.00 | 0.00 | 744.00 | 0.00 | -172959962.9 | 59.44 | 0.00 | 0.00 |
| November | 0.936542E+09 | -767357592.3 | 0.00 | 0.00 | 720.00 | 0.00 | -169184663.3 | 59.44 | 0.00 | 0.00 |
| December | 0.103037E+10 | -849530838.4 | 0.00 | 0.00 | 744.00 | 0.00 | -180835853.5 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.107884E+11 | -0.872064E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.206780E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.777320E+09 | -877043991.3 | 0.00 | 0.00 | 672.00 | 0.00 | -180835853.5 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.105613E+10 | -604836948.5 | 0.00 | 0.00 | 744.00 | 0.00 | -166459097.2 | 59.44 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: G NE APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.105611E+10 | -877042436.8 | 0.00 | 0.00 | 744.00 | 0.00 | -179063006.7 | 59.44 | 0.00 | 0.00 |
| February | 0.950338E+09 | -784155750.3 | 0.00 | 0.00 | 672.00 | 0.00 | -166182294.0 | 59.44 | 0.00 | 0.00 |
| March | 0.100697E+10 | -826660198.0 | 0.00 | 0.00 | 744.00 | 0.00 | -180312349.3 | 59.44 | 0.00 | 0.00 |
| April | 0.904153E+09 | -736856548.1 | 0.00 | 0.00 | 720.00 | 0.00 | -167296132.4 | 59.44 | 0.00 | 0.00 |
| May | 0.863072E+09 | -690579047.8 | 0.00 | 0.00 | 744.00 | 0.00 | -172492712.2 | 59.44 | 0.00 | 0.00 |
| June | 0.779654E+09 | -612734797.2 | 0.00 | 0.00 | 720.00 | 0.00 | -166919257.1 | 59.44 | 0.00 | 0.00 |
| July | 0.777316E+09 | -604835999.4 | 0.00 | 0.00 | 744.00 | 0.00 | -172479929.3 | 59.44 | 0.00 | 0.00 |
| August | 0.785935E+09 | -613450068.0 | 0.00 | 0.00 | 744.00 | 0.00 | -172484998.7 | 59.44 | 0.00 | 0.00 |
| September | 0.802174E+09 | -635255660.7 | 0.00 | 0.00 | 720.00 | 0.00 | -166918442.3 | 59.44 | 0.00 | 0.00 |
| October | 0.895067E+09 | -722202798.6 | 0.00 | 0.00 | 744.00 | 0.00 | -172864407.2 | 59.44 | 0.00 | 0.00 |
| November | 0.936504E+09 | -767356164.7 | 0.00 | 0.00 | 720.00 | 0.00 | -169147928.9 | 59.44 | 0.00 | 0.00 |
| December | 0.103023E+10 | -849529682.4 | 0.00 | 0.00 | 744.00 | 0.00 | -180698207.6 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.107875E+11 | -0.872066E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.206686E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.777316E+09 | -877042436.8 | 0.00 | 0.00 | 672.00 | 0.00 | -180698207.6 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.105611E+10 | -604835999.4 | 0.00 | 0.00 | 744.00 | 0.00 | -166182294.0 | 59.44 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: G N1 APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.105473E+10 | -877043001.4 | 0.00 | 0.00 | 744.00 | 0.00 | -177686154.4 | 59.44 | 0.00 | 0.00 |
| February | 0.948950E+09 | -784150540.6 | 0.00 | 0.00 | 672.00 | 0.00 | -164799707.5 | 59.44 | 0.00 | 0.00 |
| March | 0.100586E+10 | -826652805.5 | 0.00 | 0.00 | 744.00 | 0.00 | -179204212.5 | 59.44 | 0.00 | 0.00 |
| April | 0.904035E+09 | -736852950.9 | 0.00 | 0.00 | 720.00 | 0.00 | -167181616.9 | 59.44 | 0.00 | 0.00 |
| May | 0.863061E+09 | -690572955.0 | 0.00 | 0.00 | 744.00 | 0.00 | -172487651.0 | 59.44 | 0.00 | 0.00 |
| June | 0.779654E+09 | -612731316.1 | 0.00 | 0.00 | 720.00 | 0.00 | -166922941.9 | 59.44 | 0.00 | 0.00 |
| July | 0.777319E+09 | -604835164.8 | 0.00 | 0.00 | 744.00 | 0.00 | -172483653.3 | 59.44 | 0.00 | 0.00 |
| August | 0.785933E+09 | -613445546.7 | 0.00 | 0.00 | 744.00 | 0.00 | -172487254.7 | 59.44 | 0.00 | 0.00 |
| September | 0.802172E+09 | -635249905.1 | 0.00 | 0.00 | 720.00 | 0.00 | -166921846.8 | 59.44 | 0.00 | 0.00 |
| October | 0.894915E+09 | -722203357.4 | 0.00 | 0.00 | 744.00 | 0.00 | -172711214.1 | 59.44 | 0.00 | 0.00 |
| November | 0.935765E+09 | -767352491.1 | 0.00 | 0.00 | 720.00 | 0.00 | -168412306.2 | 59.44 | 0.00 | 0.00 |
| December | 0.102917E+10 | -849530355.7 | 0.00 | 0.00 | 744.00 | 0.00 | -179636398.1 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.107816E+11 | -0.872062E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.206093E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.777319E+09 | -877043001.4 | 0.00 | 0.00 | 672.00 | 0.00 | -179636398.1 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.105473E+10 | -604835164.8 | 0.00 | 0.00 | 744.00 | 0.00 | -164799707.5 | 59.44 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: G N2 APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.105474E+10 | -877042590.4 | 0.00 | 0.00 | 744.00 | 0.00 | -177696767.4 | 59.44 | 0.00 | 0.00 |
| February | 0.948906E+09 | -784150242.6 | 0.00 | 0.00 | 672.00 | 0.00 | -164755379.1 | 59.44 | 0.00 | 0.00 |
| March | 0.100582E+10 | -826651545.9 | 0.00 | 0.00 | 744.00 | 0.00 | -179169742.8 | 59.44 | 0.00 | 0.00 |
| April | 0.904032E+09 | -736852791.6 | 0.00 | 0.00 | 720.00 | 0.00 | -167179616.2 | 59.44 | 0.00 | 0.00 |
| May | 0.863061E+09 | -690572872.1 | 0.00 | 0.00 | 744.00 | 0.00 | -172487666.4 | 59.44 | 0.00 | 0.00 |
| June | 0.779654E+09 | -612731540.3 | 0.00 | 0.00 | 720.00 | 0.00 | -166922844.2 | 59.44 | 0.00 | 0.00 |
| July | 0.777319E+09 | -604835240.7 | 0.00 | 0.00 | 744.00 | 0.00 | -172483623.7 | 59.44 | 0.00 | 0.00 |
| August | 0.785933E+09 | -613445526.4 | 0.00 | 0.00 | 744.00 | 0.00 | -172487191.1 | 59.44 | 0.00 | 0.00 |
| September | 0.802172E+09 | -635249870.3 | 0.00 | 0.00 | 720.00 | 0.00 | -166921880.5 | 59.44 | 0.00 | 0.00 |
| October | 0.894909E+09 | -722203387.4 | 0.00 | 0.00 | 744.00 | 0.00 | -172705438.6 | 59.44 | 0.00 | 0.00 |
| November | 0.935769E+09 | -767352481.3 | 0.00 | 0.00 | 720.00 | 0.00 | -168416349.8 | 59.44 | 0.00 | 0.00 |
| December | 0.102915E+10 | -849530404.5 | 0.00 | 0.00 | 744.00 | 0.00 | -179619358.8 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.107815E+11 | -0.872062E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.206085E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.777319E+09 | -877042590.4 | 0.00 | 0.00 | 672.00 | 0.00 | -179619358.8 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.105474E+10 | -604835240.7 | 0.00 | 0.00 | 744.00 | 0.00 | -164755379.1 | 59.44 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: G S1 APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.105040E+10 | -877050018.3 | 0.00 | 0.00 | 744.00 | 0.00 | -173351397.9 | 59.44 | 0.00 | 0.00 |
| February | 0.943097E+09 | -784158112.2 | 0.00 | 0.00 | 672.00 | 0.00 | -158938566.9 | 59.44 | 0.00 | 0.00 |
| March | 0.100218E+10 | -826658343.5 | 0.00 | 0.00 | 744.00 | 0.00 | -175519984.7 | 59.44 | 0.00 | 0.00 |
| April | 0.903874E+09 | -736853953.5 | 0.00 | 0.00 | 720.00 | 0.00 | -167020275.4 | 59.44 | 0.00 | 0.00 |
| May | 0.863060E+09 | -690572281.3 | 0.00 | 0.00 | 744.00 | 0.00 | -172487417.1 | 59.44 | 0.00 | 0.00 |
| June | 0.779655E+09 | -612731186.2 | 0.00 | 0.00 | 720.00 | 0.00 | -166923750.0 | 59.44 | 0.00 | 0.00 |
| July | 0.777320E+09 | -604837180.8 | 0.00 | 0.00 | 744.00 | 0.00 | -172482436.5 | 59.44 | 0.00 | 0.00 |
| August | 0.785933E+09 | -613445968.9 | 0.00 | 0.00 | 744.00 | 0.00 | -172486881.0 | 59.44 | 0.00 | 0.00 |
| September | 0.802172E+09 | -635249001.5 | 0.00 | 0.00 | 720.00 | 0.00 | -166922538.3 | 59.44 | 0.00 | 0.00 |
| October | 0.894709E+09 | -722205948.2 | 0.00 | 0.00 | 744.00 | 0.00 | -172502797.7 | 59.44 | 0.00 | 0.00 |
| November | 0.934437E+09 | -767351915.7 | 0.00 | 0.00 | 720.00 | 0.00 | -167084880.6 | 59.44 | 0.00 | 0.00 |
| December | 0.102351E+10 | -849530349.5 | 0.00 | 0.00 | 744.00 | 0.00 | -173976809.2 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.107603E+11 | -0.872064E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.203970E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.777320E+09 | -877050018.3 | 0.00 | 0.00 | 672.00 | 0.00 | -175519984.7 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.105040E+10 | -604837180.8 | 0.00 | 0.00 | 744.00 | 0.00 | -158938566.9 | 59.44 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: G S2 APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.105034E+10 | -877050319.9 | 0.00 | 0.00 | 744.00 | 0.00 | -173288285.8 | 59.44 | 0.00 | 0.00 |
| February | 0.942760E+09 | -784156390.1 | 0.00 | 0.00 | 672.00 | 0.00 | -158603998.2 | 59.44 | 0.00 | 0.00 |
| March | 0.100188E+10 | -826658421.4 | 0.00 | 0.00 | 744.00 | 0.00 | -175217183.0 | 59.44 | 0.00 | 0.00 |
| April | 0.903853E+09 | -736854825.3 | 0.00 | 0.00 | 720.00 | 0.00 | -166997802.8 | 59.44 | 0.00 | 0.00 |
| May | 0.863059E+09 | -690572373.9 | 0.00 | 0.00 | 744.00 | 0.00 | -172486345.1 | 59.44 | 0.00 | 0.00 |
| June | 0.779655E+09 | -612730914.0 | 0.00 | 0.00 | 720.00 | 0.00 | -166923768.8 | 59.44 | 0.00 | 0.00 |
| July | 0.777320E+09 | -604837137.9 | 0.00 | 0.00 | 744.00 | 0.00 | -172482462.8 | 59.44 | 0.00 | 0.00 |
| August | 0.785933E+09 | -613445950.5 | 0.00 | 0.00 | 744.00 | 0.00 | -172486894.1 | 59.44 | 0.00 | 0.00 |
| September | 0.802172E+09 | -635249063.6 | 0.00 | 0.00 | 720.00 | 0.00 | -166922499.1 | 59.44 | 0.00 | 0.00 |
| October | 0.894700E+09 | -722206004.8 | 0.00 | 0.00 | 744.00 | 0.00 | -172494000.9 | 59.44 | 0.00 | 0.00 |
| November | 0.934394E+09 | -767352446.5 | 0.00 | 0.00 | 720.00 | 0.00 | -167041960.6 | 59.44 | 0.00 | 0.00 |
| December | 0.102338E+10 | -849532463.8 | 0.00 | 0.00 | 744.00 | 0.00 | -173849631.0 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.107594E+11 | -0.872065E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.203879E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.777320E+09 | -877050319.9 | 0.00 | 0.00 | 672.00 | 0.00 | -175217183.0 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.105034E+10 | -604837137.9 | 0.00 | 0.00 | 744.00 | 0.00 | -158603998.2 | 59.44 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: M SW APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.192847E+10 | -0.175410E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -174362913.9 | 59.44 | 0.00 | 0.00 |
| February | 0.172688E+10 | -0.156832E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -158558831.0 | 59.44 | 0.00 | 0.00 |
| March | 0.182825E+10 | -0.165332E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -174931316.4 | 59.44 | 0.00 | 0.00 |
| April | 0.164072E+10 | -0.147372E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -167001762.5 | 59.44 | 0.00 | 0.00 |
| May | 0.155364E+10 | -0.138115E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172487744.9 | 59.44 | 0.00 | 0.00 |
| June | 0.139239E+10 | -0.122547E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -166917806.2 | 59.44 | 0.00 | 0.00 |
| July | 0.138216E+10 | -0.120967E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172485774.6 | 59.44 | 0.00 | 0.00 |
| August | 0.139938E+10 | -0.122690E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172480732.2 | 59.44 | 0.00 | 0.00 |
| September | 0.143743E+10 | -0.127051E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -166921631.6 | 59.44 | 0.00 | 0.00 |
| October | 0.161733E+10 | -0.144441E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172918667.5 | 59.44 | 0.00 | 0.00 |
| November | 0.170297E+10 | -0.153471E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -168257230.4 | 59.44 | 0.00 | 0.00 |
| December | 0.187555E+10 | -0.169907E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -176486930.6 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.194852E+11 | -0.174413E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.204381E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.138216E+10 | -0.175410E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -176486930.6 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.192847E+10 | -0.120967E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -158558831.0 | 59.44 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: M NW APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.193162E+10 | -0.175411E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -177515891.2 | 59.44 | 0.00 | 0.00 |
| February | 0.173091E+10 | -0.156832E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -162586650.5 | 59.44 | 0.00 | 0.00 |
| March | 0.183000E+10 | -0.165332E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -176680512.5 | 59.44 | 0.00 | 0.00 |
| April | 0.164079E+10 | -0.147372E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -167069647.4 | 59.44 | 0.00 | 0.00 |
| May | 0.155364E+10 | -0.138115E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172486992.4 | 59.44 | 0.00 | 0.00 |
| June | 0.139239E+10 | -0.122547E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -166917805.5 | 59.44 | 0.00 | 0.00 |
| July | 0.138216E+10 | -0.120967E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172485771.4 | 59.44 | 0.00 | 0.00 |
| August | 0.139938E+10 | -0.122690E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172480731.7 | 59.44 | 0.00 | 0.00 |
| September | 0.143743E+10 | -0.127051E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -166921718.9 | 59.44 | 0.00 | 0.00 |
| October | 0.161798E+10 | -0.144441E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -173569377.4 | 59.44 | 0.00 | 0.00 |
| November | 0.170537E+10 | -0.153471E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -170662833.1 | 59.44 | 0.00 | 0.00 |
| December | 0.188069E+10 | -0.169907E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -181622220.8 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.195024E+11 | -0.174414E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.206100E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.138216E+10 | -0.175411E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -181622220.8 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.193162E+10 | -0.120967E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -162586650.5 | 59.44 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: M SE APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.192843E+10 | -0.175410E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -174326818.2 | 59.44 | 0.00 | 0.00 |
| February | 0.172668E+10 | -0.156832E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -158358613.5 | 59.44 | 0.00 | 0.00 |
| March | 0.182800E+10 | -0.165332E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -174684604.7 | 59.44 | 0.00 | 0.00 |
| April | 0.164072E+10 | -0.147372E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -166997421.4 | 59.44 | 0.00 | 0.00 |
| May | 0.155364E+10 | -0.138115E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172485534.1 | 59.44 | 0.00 | 0.00 |
| June | 0.139239E+10 | -0.122547E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -166919649.7 | 59.44 | 0.00 | 0.00 |
| July | 0.138215E+10 | -0.120967E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172484042.7 | 59.44 | 0.00 | 0.00 |
| August | 0.139939E+10 | -0.122690E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172481627.3 | 59.44 | 0.00 | 0.00 |
| September | 0.143743E+10 | -0.127051E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -166918876.3 | 59.44 | 0.00 | 0.00 |
| October | 0.161728E+10 | -0.144441E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172868425.2 | 59.44 | 0.00 | 0.00 |
| November | 0.170293E+10 | -0.153471E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -168222902.8 | 59.44 | 0.00 | 0.00 |
| December | 0.187535E+10 | -0.169906E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -176292743.7 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.194844E+11 | -0.174413E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.204304E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.138215E+10 | -0.175410E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -176292743.7 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.192843E+10 | -0.120967E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -158358613.5 | 59.44 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: M NE APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.193150E+10 | -0.175410E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -177396051.9 | 59.44 | 0.00 | 0.00 |
| February | 0.173042E+10 | -0.156832E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -162097415.6 | 59.44 | 0.00 | 0.00 |
| March | 0.182964E+10 | -0.165332E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -176322517.8 | 59.44 | 0.00 | 0.00 |
| April | 0.164077E+10 | -0.147372E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -167054268.7 | 59.44 | 0.00 | 0.00 |
| May | 0.155364E+10 | -0.138115E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172486386.8 | 59.44 | 0.00 | 0.00 |
| June | 0.139239E+10 | -0.122547E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -166917809.6 | 59.44 | 0.00 | 0.00 |
| July | 0.138216E+10 | -0.120967E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172485778.8 | 59.44 | 0.00 | 0.00 |
| August | 0.139938E+10 | -0.122690E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172480739.1 | 59.44 | 0.00 | 0.00 |
| September | 0.143743E+10 | -0.127051E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -166921710.3 | 59.44 | 0.00 | 0.00 |
| October | 0.161780E+10 | -0.144441E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -173392370.1 | 59.44 | 0.00 | 0.00 |
| November | 0.170528E+10 | -0.153471E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -170568358.9 | 59.44 | 0.00 | 0.00 |
| December | 0.188055E+10 | -0.169907E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -181486379.3 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.195010E+11 | -0.174414E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.205961E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.138216E+10 | -0.175410E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -181486379.3 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.193150E+10 | -0.120967E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -162097415.6 | 59.44 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: M N1 APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.192998E+10 | -0.175410E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -175879009.4 | 59.44 | 0.00 | 0.00 |
| February | 0.172847E+10 | -0.156832E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -160149317.5 | 59.44 | 0.00 | 0.00 |
| March | 0.182844E+10 | -0.165332E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -175123398.2 | 59.44 | 0.00 | 0.00 |
| April | 0.164070E+10 | -0.147372E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -166985459.4 | 59.44 | 0.00 | 0.00 |
| May | 0.155363E+10 | -0.138115E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172482830.2 | 59.44 | 0.00 | 0.00 |
| June | 0.139239E+10 | -0.122547E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -166919533.5 | 59.44 | 0.00 | 0.00 |
| July | 0.138215E+10 | -0.120967E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172484209.9 | 59.44 | 0.00 | 0.00 |
| August | 0.139939E+10 | -0.122690E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172481629.7 | 59.44 | 0.00 | 0.00 |
| September | 0.143743E+10 | -0.127051E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -166918757.5 | 59.44 | 0.00 | 0.00 |
| October | 0.161741E+10 | -0.144441E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172997490.4 | 59.44 | 0.00 | 0.00 |
| November | 0.170397E+10 | -0.153472E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -169249991.8 | 59.44 | 0.00 | 0.00 |
| December | 0.187896E+10 | -0.169906E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -179890901.7 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.194929E+11 | -0.174414E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.205156E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.138215E+10 | -0.175410E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -179890901.7 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.192998E+10 | -0.120967E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -160149317.5 | 59.44 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: M N2 APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.192999E+10 | -0.175410E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -175880289.8 | 59.44 | 0.00 | 0.00 |
| February | 0.172840E+10 | -0.156832E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -160087610.5 | 59.44 | 0.00 | 0.00 |
| March | 0.182841E+10 | -0.165332E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -175088367.9 | 59.44 | 0.00 | 0.00 |
| April | 0.164070E+10 | -0.147372E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -166984603.9 | 59.44 | 0.00 | 0.00 |
| May | 0.155363E+10 | -0.138115E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172482843.3 | 59.44 | 0.00 | 0.00 |
| June | 0.139239E+10 | -0.122547E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -166919540.9 | 59.44 | 0.00 | 0.00 |
| July | 0.138215E+10 | -0.120967E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172484211.5 | 59.44 | 0.00 | 0.00 |
| August | 0.139939E+10 | -0.122690E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172481629.8 | 59.44 | 0.00 | 0.00 |
| September | 0.143743E+10 | -0.127051E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -166918757.6 | 59.44 | 0.00 | 0.00 |
| October | 0.161739E+10 | -0.144441E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172984293.4 | 59.44 | 0.00 | 0.00 |
| November | 0.170397E+10 | -0.153472E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -169252768.5 | 59.44 | 0.00 | 0.00 |
| December | 0.187894E+10 | -0.169906E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -179875586.4 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.194928E+11 | -0.174414E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.205144E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.138215E+10 | -0.175410E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -179875586.4 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.192999E+10 | -0.120967E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -160087610.5 | 59.44 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: M S1 APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.192729E+10 | -0.175411E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -173184231.7 | 59.44 | 0.00 | 0.00 |
| February | 0.172512E+10 | -0.156832E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -156799985.0 | 59.44 | 0.00 | 0.00 |
| March | 0.182695E+10 | -0.165332E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -173631840.9 | 59.44 | 0.00 | 0.00 |
| April | 0.164065E+10 | -0.147372E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -166936109.3 | 59.44 | 0.00 | 0.00 |
| May | 0.155364E+10 | -0.138115E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172485769.9 | 59.44 | 0.00 | 0.00 |
| June | 0.139239E+10 | -0.122547E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -166917831.4 | 59.44 | 0.00 | 0.00 |
| July | 0.138216E+10 | -0.120967E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172485792.5 | 59.44 | 0.00 | 0.00 |
| August | 0.139938E+10 | -0.122690E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172480750.9 | 59.44 | 0.00 | 0.00 |
| September | 0.143743E+10 | -0.127051E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -166921510.9 | 59.44 | 0.00 | 0.00 |
| October | 0.161701E+10 | -0.144441E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172604284.7 | 59.44 | 0.00 | 0.00 |
| November | 0.170211E+10 | -0.153471E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -167399857.8 | 59.44 | 0.00 | 0.00 |
| December | 0.187345E+10 | -0.169906E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -174384754.2 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.194776E+11 | -0.174414E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.203623E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.138216E+10 | -0.175411E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -174384754.2 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.192729E+10 | -0.120967E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -156799985.0 | 59.44 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: M S2 APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.192729E+10 | -0.175411E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -173187198.2 | 59.44 | 0.00 | 0.00 |
| February | 0.172511E+10 | -0.156832E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -156794076.4 | 59.44 | 0.00 | 0.00 |
| March | 0.182694E+10 | -0.165332E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -173621587.2 | 59.44 | 0.00 | 0.00 |
| April | 0.164065E+10 | -0.147372E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -166935877.6 | 59.44 | 0.00 | 0.00 |
| May | 0.155364E+10 | -0.138115E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172485779.4 | 59.44 | 0.00 | 0.00 |
| June | 0.139239E+10 | -0.122547E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -166917830.8 | 59.44 | 0.00 | 0.00 |
| July | 0.138216E+10 | -0.120967E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172485792.7 | 59.44 | 0.00 | 0.00 |
| August | 0.139938E+10 | -0.122690E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172480749.8 | 59.44 | 0.00 | 0.00 |
| September | 0.143743E+10 | -0.127051E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -166921511.1 | 59.44 | 0.00 | 0.00 |
| October | 0.161701E+10 | -0.144441E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172603536.2 | 59.44 | 0.00 | 0.00 |
| November | 0.170211E+10 | -0.153471E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -167401881.8 | 59.44 | 0.00 | 0.00 |
| December | 0.187344E+10 | -0.169906E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -174378788.3 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.194776E+11 | -0.174414E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.203621E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.138216E+10 | -0.175411E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -174378788.3 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.192729E+10 | -0.120967E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -156794076.4 | 59.44 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: T SW APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.105587E+10 | -877051147.4 | 0.00 | 0.00 | 744.00 | 0.00 | -178820691.9 | 59.44 | 0.00 | 0.00 |
| February | 0.947905E+09 | -784155350.8 | 0.00 | 0.00 | 672.00 | 0.00 | -163749854.7 | 59.44 | 0.00 | 0.00 |
| March | 0.100572E+10 | -826653354.0 | 0.00 | 0.00 | 744.00 | 0.00 | -179067958.5 | 59.44 | 0.00 | 0.00 |
| April | 0.905116E+09 | -736850692.2 | 0.00 | 0.00 | 720.00 | 0.00 | -168264935.7 | 59.44 | 0.00 | 0.00 |
| May | 0.863408E+09 | -690580655.6 | 0.00 | 0.00 | 744.00 | 0.00 | -172827317.6 | 59.44 | 0.00 | 0.00 |
| June | 0.779654E+09 | -612733464.0 | 0.00 | 0.00 | 720.00 | 0.00 | -166920997.5 | 59.44 | 0.00 | 0.00 |
| July | 0.777324E+09 | -604837678.6 | 0.00 | 0.00 | 744.00 | 0.00 | -172486515.7 | 59.44 | 0.00 | 0.00 |
| August | 0.785934E+09 | -613446209.8 | 0.00 | 0.00 | 744.00 | 0.00 | -172488145.7 | 59.44 | 0.00 | 0.00 |
| September | 0.802208E+09 | -635246023.1 | 0.00 | 0.00 | 720.00 | 0.00 | -166961495.0 | 59.44 | 0.00 | 0.00 |
| October | 0.897478E+09 | -722201316.4 | 0.00 | 0.00 | 744.00 | 0.00 | -175276927.7 | 59.44 | 0.00 | 0.00 |
| November | 0.939629E+09 | -767351319.1 | 0.00 | 0.00 | 720.00 | 0.00 | -172277783.8 | 59.44 | 0.00 | 0.00 |
| December | 0.103012E+10 | -849531709.3 | 0.00 | 0.00 | 744.00 | 0.00 | -180587379.4 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.107904E+11 | -0.872064E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.206973E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.777324E+09 | -877051147.4 | 0.00 | 0.00 | 672.00 | 0.00 | -180587379.4 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.105587E+10 | -604837678.6 | 0.00 | 0.00 | 744.00 | 0.00 | -163749854.7 | 59.44 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: T NW APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.105839E+10 | -877048706.9 | 0.00 | 0.00 | 744.00 | 0.00 | -181342409.9 | 59.44 | 0.00 | 0.00 |
| February | 0.950467E+09 | -784152919.7 | 0.00 | 0.00 | 672.00 | 0.00 | -166314181.9 | 59.44 | 0.00 | 0.00 |
| March | 0.100704E+10 | -826654051.7 | 0.00 | 0.00 | 744.00 | 0.00 | -180388028.2 | 59.44 | 0.00 | 0.00 |
| April | 0.905255E+09 | -736848427.6 | 0.00 | 0.00 | 720.00 | 0.00 | -168406478.1 | 59.44 | 0.00 | 0.00 |
| May | 0.863374E+09 | -690577801.7 | 0.00 | 0.00 | 744.00 | 0.00 | -172796208.8 | 59.44 | 0.00 | 0.00 |
| June | 0.779654E+09 | -612732858.0 | 0.00 | 0.00 | 720.00 | 0.00 | -166921069.9 | 59.44 | 0.00 | 0.00 |
| July | 0.777322E+09 | -604837885.5 | 0.00 | 0.00 | 744.00 | 0.00 | -172484613.6 | 59.44 | 0.00 | 0.00 |
| August | 0.785934E+09 | -613446146.2 | 0.00 | 0.00 | 744.00 | 0.00 | -172487652.1 | 59.44 | 0.00 | 0.00 |
| September | 0.802207E+09 | -635246039.3 | 0.00 | 0.00 | 720.00 | 0.00 | -166961115.7 | 59.44 | 0.00 | 0.00 |
| October | 0.898517E+09 | -722204108.9 | 0.00 | 0.00 | 744.00 | 0.00 | -176313285.0 | 59.44 | 0.00 | 0.00 |
| November | 0.941953E+09 | -767355765.9 | 0.00 | 0.00 | 720.00 | 0.00 | -174596804.0 | 59.44 | 0.00 | 0.00 |
| December | 0.103338E+10 | -849532217.3 | 0.00 | 0.00 | 744.00 | 0.00 | -183851266.8 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.108035E+11 | -0.872064E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.208286E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.777322E+09 | -877048706.9 | 0.00 | 0.00 | 672.00 | 0.00 | -183851266.8 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.105839E+10 | -604837885.5 | 0.00 | 0.00 | 744.00 | 0.00 | -166314181.9 | 59.44 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: T SE APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.105565E+10 | -877052808.8 | 0.00 | 0.00 | 744.00 | 0.00 | -178596646.7 | 59.44 | 0.00 | 0.00 |
| February | 0.947583E+09 | -784153151.0 | 0.00 | 0.00 | 672.00 | 0.00 | -163429502.9 | 59.44 | 0.00 | 0.00 |
| March | 0.100538E+10 | -826655318.3 | 0.00 | 0.00 | 744.00 | 0.00 | -178725159.2 | 59.44 | 0.00 | 0.00 |
| April | 0.904950E+09 | -736851810.5 | 0.00 | 0.00 | 720.00 | 0.00 | -168097750.1 | 59.44 | 0.00 | 0.00 |
| May | 0.863365E+09 | -690580831.6 | 0.00 | 0.00 | 744.00 | 0.00 | -172784082.9 | 59.44 | 0.00 | 0.00 |
| June | 0.779654E+09 | -612739301.7 | 0.00 | 0.00 | 720.00 | 0.00 | -166914432.5 | 59.44 | 0.00 | 0.00 |
| July | 0.777323E+09 | -604838319.8 | 0.00 | 0.00 | 744.00 | 0.00 | -172485105.0 | 59.44 | 0.00 | 0.00 |
| August | 0.785935E+09 | -613454983.4 | 0.00 | 0.00 | 744.00 | 0.00 | -172479947.8 | 59.44 | 0.00 | 0.00 |
| September | 0.802203E+09 | -635251748.3 | 0.00 | 0.00 | 720.00 | 0.00 | -166951151.3 | 59.44 | 0.00 | 0.00 |
| October | 0.897304E+09 | -722209615.7 | 0.00 | 0.00 | 744.00 | 0.00 | -175094661.3 | 59.44 | 0.00 | 0.00 |
| November | 0.939515E+09 | -767352830.6 | 0.00 | 0.00 | 720.00 | 0.00 | -172162244.9 | 59.44 | 0.00 | 0.00 |
| December | 0.102990E+10 | -849529719.3 | 0.00 | 0.00 | 744.00 | 0.00 | -180365575.1 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.107888E+11 | -0.872067E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.206809E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.777323E+09 | -877052808.8 | 0.00 | 0.00 | 672.00 | 0.00 | -180365575.1 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.105565E+10 | -604838319.8 | 0.00 | 0.00 | 744.00 | 0.00 | -163429502.9 | 59.44 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: T NE APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.105828E+10 | -877049117.9 | 0.00 | 0.00 | 744.00 | 0.00 | -181230178.4 | 59.44 | 0.00 | 0.00 |
| February | 0.950312E+09 | -784154550.8 | 0.00 | 0.00 | 672.00 | 0.00 | -166157408.2 | 59.44 | 0.00 | 0.00 |
| March | 0.100669E+10 | -826658759.6 | 0.00 | 0.00 | 744.00 | 0.00 | -180035992.9 | 59.44 | 0.00 | 0.00 |
| April | 0.905068E+09 | -736855215.2 | 0.00 | 0.00 | 720.00 | 0.00 | -168213009.7 | 59.44 | 0.00 | 0.00 |
| May | 0.863343E+09 | -690573673.4 | 0.00 | 0.00 | 744.00 | 0.00 | -172769032.4 | 59.44 | 0.00 | 0.00 |
| June | 0.779655E+09 | -612731574.7 | 0.00 | 0.00 | 720.00 | 0.00 | -166923645.6 | 59.44 | 0.00 | 0.00 |
| July | 0.777322E+09 | -604838474.0 | 0.00 | 0.00 | 744.00 | 0.00 | -172483258.6 | 59.44 | 0.00 | 0.00 |
| August | 0.785934E+09 | -613446353.8 | 0.00 | 0.00 | 744.00 | 0.00 | -172487805.3 | 59.44 | 0.00 | 0.00 |
| September | 0.802202E+09 | -635246063.4 | 0.00 | 0.00 | 720.00 | 0.00 | -166956337.7 | 59.44 | 0.00 | 0.00 |
| October | 0.898276E+09 | -722205405.6 | 0.00 | 0.00 | 744.00 | 0.00 | -176070552.1 | 59.44 | 0.00 | 0.00 |
| November | 0.941959E+09 | -767355243.3 | 0.00 | 0.00 | 720.00 | 0.00 | -174604026.5 | 59.44 | 0.00 | 0.00 |
| December | 0.103345E+10 | -849530872.4 | 0.00 | 0.00 | 744.00 | 0.00 | -183919403.0 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.108025E+11 | -0.872065E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.208185E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.777322E+09 | -877049117.9 | 0.00 | 0.00 | 672.00 | 0.00 | -183919403.0 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.105828E+10 | -604838474.0 | 0.00 | 0.00 | 744.00 | 0.00 | -166157408.2 | 59.44 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: T N1 APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.105812E+10 | -877048045.9 | 0.00 | 0.00 | 744.00 | 0.00 | -181071578.0 | 59.44 | 0.00 | 0.00 |
| February | 0.950229E+09 | -784159098.3 | 0.00 | 0.00 | 672.00 | 0.00 | -166070048.1 | 59.44 | 0.00 | 0.00 |
| March | 0.100641E+10 | -826656917.4 | 0.00 | 0.00 | 744.00 | 0.00 | -179753117.7 | 59.44 | 0.00 | 0.00 |
| April | 0.904794E+09 | -736861139.4 | 0.00 | 0.00 | 720.00 | 0.00 | -167932637.9 | 59.44 | 0.00 | 0.00 |
| May | 0.863225E+09 | -690573338.7 | 0.00 | 0.00 | 744.00 | 0.00 | -172651811.3 | 59.44 | 0.00 | 0.00 |
| June | 0.779653E+09 | -612732857.7 | 0.00 | 0.00 | 720.00 | 0.00 | -166920568.4 | 59.44 | 0.00 | 0.00 |
| July | 0.777321E+09 | -604837752.4 | 0.00 | 0.00 | 744.00 | 0.00 | -172483729.5 | 59.44 | 0.00 | 0.00 |
| August | 0.785932E+09 | -613446163.9 | 0.00 | 0.00 | 744.00 | 0.00 | -172485951.8 | 59.44 | 0.00 | 0.00 |
| September | 0.802184E+09 | -635246148.8 | 0.00 | 0.00 | 720.00 | 0.00 | -166937519.6 | 59.44 | 0.00 | 0.00 |
| October | 0.897969E+09 | -722202878.1 | 0.00 | 0.00 | 744.00 | 0.00 | -175766486.9 | 59.44 | 0.00 | 0.00 |
| November | 0.941468E+09 | -767350599.9 | 0.00 | 0.00 | 720.00 | 0.00 | -174117241.7 | 59.44 | 0.00 | 0.00 |
| December | 0.103337E+10 | -849531919.6 | 0.00 | 0.00 | 744.00 | 0.00 | -183842410.1 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.108007E+11 | -0.872065E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.208003E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.777321E+09 | -877048045.9 | 0.00 | 0.00 | 672.00 | 0.00 | -183842410.1 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.105812E+10 | -604837752.4 | 0.00 | 0.00 | 744.00 | 0.00 | -166070048.1 | 59.44 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: T N2 APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.105811E+10 | -877047941.3 | 0.00 | 0.00 | 744.00 | 0.00 | -181065418.8 | 59.44 | 0.00 | 0.00 |
| February | 0.950197E+09 | -784158992.8 | 0.00 | 0.00 | 672.00 | 0.00 | -166038194.0 | 59.44 | 0.00 | 0.00 |
| March | 0.100638E+10 | -826651583.6 | 0.00 | 0.00 | 744.00 | 0.00 | -179726799.8 | 59.44 | 0.00 | 0.00 |
| April | 0.904792E+09 | -736856257.6 | 0.00 | 0.00 | 720.00 | 0.00 | -167936215.3 | 59.44 | 0.00 | 0.00 |
| May | 0.863228E+09 | -690577784.6 | 0.00 | 0.00 | 744.00 | 0.00 | -172650141.7 | 59.44 | 0.00 | 0.00 |
| June | 0.779652E+09 | -612735642.9 | 0.00 | 0.00 | 720.00 | 0.00 | -166915909.6 | 59.44 | 0.00 | 0.00 |
| July | 0.777323E+09 | -604838345.3 | 0.00 | 0.00 | 744.00 | 0.00 | -172484507.0 | 59.44 | 0.00 | 0.00 |
| August | 0.785933E+09 | -613450717.6 | 0.00 | 0.00 | 744.00 | 0.00 | -172482457.3 | 59.44 | 0.00 | 0.00 |
| September | 0.802184E+09 | -635246791.9 | 0.00 | 0.00 | 720.00 | 0.00 | -166936950.9 | 59.44 | 0.00 | 0.00 |
| October | 0.897955E+09 | -722204191.8 | 0.00 | 0.00 | 744.00 | 0.00 | -175750374.4 | 59.44 | 0.00 | 0.00 |
| November | 0.941474E+09 | -767351619.4 | 0.00 | 0.00 | 720.00 | 0.00 | -174122544.2 | 59.44 | 0.00 | 0.00 |
| December | 0.103337E+10 | -849528403.4 | 0.00 | 0.00 | 744.00 | 0.00 | -183840965.5 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.108006E+11 | -0.872065E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.207995E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.777323E+09 | -877047941.3 | 0.00 | 0.00 | 672.00 | 0.00 | -183840965.5 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.105811E+10 | -604838345.3 | 0.00 | 0.00 | 744.00 | 0.00 | -166038194.0 | 59.44 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: T S1 APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.105482E+10 | -877046885.9 | 0.00 | 0.00 | 744.00 | 0.00 | -177770857.7 | 59.44 | 0.00 | 0.00 |
| February | 0.946792E+09 | -784158402.1 | 0.00 | 0.00 | 672.00 | 0.00 | -162633209.4 | 59.44 | 0.00 | 0.00 |
| March | 0.100469E+10 | -826654672.4 | 0.00 | 0.00 | 744.00 | 0.00 | -178034982.0 | 59.44 | 0.00 | 0.00 |
| April | 0.904665E+09 | -736853616.6 | 0.00 | 0.00 | 720.00 | 0.00 | -167811642.4 | 59.44 | 0.00 | 0.00 |
| May | 0.863252E+09 | -690578510.2 | 0.00 | 0.00 | 744.00 | 0.00 | -172673898.8 | 59.44 | 0.00 | 0.00 |
| June | 0.779652E+09 | -612736394.8 | 0.00 | 0.00 | 720.00 | 0.00 | -166915517.7 | 59.44 | 0.00 | 0.00 |
| July | 0.777323E+09 | -604838430.1 | 0.00 | 0.00 | 744.00 | 0.00 | -172484831.4 | 59.44 | 0.00 | 0.00 |
| August | 0.785933E+09 | -613450973.0 | 0.00 | 0.00 | 744.00 | 0.00 | -172482247.8 | 59.44 | 0.00 | 0.00 |
| September | 0.802184E+09 | -635246878.3 | 0.00 | 0.00 | 720.00 | 0.00 | -166937588.0 | 59.44 | 0.00 | 0.00 |
| October | 0.896762E+09 | -722208226.1 | 0.00 | 0.00 | 744.00 | 0.00 | -174554226.3 | 59.44 | 0.00 | 0.00 |
| November | 0.938545E+09 | -767355725.7 | 0.00 | 0.00 | 720.00 | 0.00 | -171189571.0 | 59.44 | 0.00 | 0.00 |
| December | 0.102920E+10 | -849530997.0 | 0.00 | 0.00 | 744.00 | 0.00 | -179669684.2 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.107838E+11 | -0.872066E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.206316E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.777323E+09 | -877046885.9 | 0.00 | 0.00 | 672.00 | 0.00 | -179669684.2 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.105482E+10 | -604838430.1 | 0.00 | 0.00 | 744.00 | 0.00 | -162633209.4 | 59.44 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: T S2 APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.105482E+10 | -877046880.2 | 0.00 | 0.00 | 744.00 | 0.00 | -177771350.5 | 59.44 | 0.00 | 0.00 |
| February | 0.946772E+09 | -784158043.2 | 0.00 | 0.00 | 672.00 | 0.00 | -162613997.4 | 59.44 | 0.00 | 0.00 |
| March | 0.100467E+10 | -826655889.6 | 0.00 | 0.00 | 744.00 | 0.00 | -178016903.0 | 59.44 | 0.00 | 0.00 |
| April | 0.904664E+09 | -736852573.0 | 0.00 | 0.00 | 720.00 | 0.00 | -167811728.6 | 59.44 | 0.00 | 0.00 |
| May | 0.863254E+09 | -690579490.7 | 0.00 | 0.00 | 744.00 | 0.00 | -172674662.7 | 59.44 | 0.00 | 0.00 |
| June | 0.779653E+09 | -612738990.6 | 0.00 | 0.00 | 720.00 | 0.00 | -166913627.7 | 59.44 | 0.00 | 0.00 |
| July | 0.777323E+09 | -604838459.2 | 0.00 | 0.00 | 744.00 | 0.00 | -172484274.1 | 59.44 | 0.00 | 0.00 |
| August | 0.785933E+09 | -613454149.4 | 0.00 | 0.00 | 744.00 | 0.00 | -172478822.5 | 59.44 | 0.00 | 0.00 |
| September | 0.802185E+09 | -635251302.6 | 0.00 | 0.00 | 720.00 | 0.00 | -166933300.5 | 59.44 | 0.00 | 0.00 |
| October | 0.896761E+09 | -722206378.0 | 0.00 | 0.00 | 744.00 | 0.00 | -174554414.1 | 59.44 | 0.00 | 0.00 |
| November | 0.938551E+09 | -767353597.3 | 0.00 | 0.00 | 720.00 | 0.00 | -171197510.2 | 59.44 | 0.00 | 0.00 |
| December | 0.102919E+10 | -849531683.5 | 0.00 | 0.00 | 744.00 | 0.00 | -179659977.0 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.107838E+11 | -0.872067E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.206311E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.777323E+09 | -877046880.2 | 0.00 | 0.00 | 672.00 | 0.00 | -179659977.0 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.105482E+10 | -604838459.2 | 0.00 | 0.00 | 744.00 | 0.00 | -162613997.4 | 59.44 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
| January | 309.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 241.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 344.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 380.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 403.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 418.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 399.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 361.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 350.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 348.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 288.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 290.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 4135.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 241.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 418.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT GSW HEATING COIL
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 4039582.75 | 307.56 | 01-JAN-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 5757110.75 | 275.38 | 13-FEB-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 31430230.73 | 493.30 | 27-MAR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 1127156.99 | 147.09 | 07-DEC-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 42354081.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 31430230.73 | 493.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT GNW HEATING COIL
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 71747028.96 | 927.85 | 01-JAN-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.147636E+09 | 558.09 | 09-FEB-03:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.139597E+09 | 773.12 | 27-MAR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.151748E+09 | 823.50 | 07-DEC-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.510728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.151748E+09 | 927.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT OFFICE HEATING COIL
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT GNE HEATING COIL
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 74222875.05 | 900.01 | 01-JAN-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.128784E+09 | 566.84 | 05-FEB-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.127905E+09 | 767.55 | 27-MAR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.140631E+09 | 819.01 | 07-DEC-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.471542E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.140631E+09 | 900.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT GN1 HEATING COIL
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 37732870.56 | 615.00 | 01-JAN-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 18092934.79 | 266.72 | 09-FEB-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 23346759.04 | 330.21 | 27-MAR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 36008012.99 | 393.09 | 07-DEC-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.115181E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 37732870.56 | 615.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT GN2 HEATING COIL
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 38178103.24 | 617.89 | 01-JAN-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 17432937.26 | 261.87 | 09-FEB-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 22868018.13 | 326.39 | 27-MAR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 35450668.98 | 389.63 | 07-DEC-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.113930E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 38178103.24 | 617.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT GS1 HEATING COIL
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT GS2 HEATING COIL
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT MSW HEATING COIL
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 5201935.63 | 516.87 | 01-JAN-07:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 1501693.65 | 280.64 | 27-MAR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 43278583.28 | 1210.74 | 07-DEC-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 49982212.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 43278583.28 | 1210.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT MNW HEATING COIL
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.109983E+09 | 1842.46 | 01-JAN-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 34673767.34 | 845.26 | 05-FEB-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 37446043.71 | 1088.40 | 27-MAR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 23254274.89 | 823.33 | 24-NOV-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.515187E+09 | 2261.40 | 07-DEC-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.720544E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.515187E+09 | 2261.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT MSE HEATING COIL
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 5274006.56 | 555.67 | 01-JAN-07:18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 633746.68 | 244.63 | 27-MAR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 39412998.28 | 1202.41 | 07-DEC-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 45320751.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 39412998.28 | 1202.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT MNE HEATING COIL
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.113666E+09 | 1831.18 | 01-JAN-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 32709151.62 | 1003.60 | 05-FEB-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 33641916.53 | 1073.65 | 27-MAR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 20676834.59 | 926.38 | 24-NOV-03:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.483696E+09 | 2280.34 | 07-DEC-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.684390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.483696E+09 | 2280.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT MN1 HEATING COIL
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 48442397.01 | 1029.00 | 01-JAN-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.139768E+09 | 1280.90 | 07-DEC-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.188210E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.139768E+09 | 1280.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT MN2 HEATING COIL
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 49373744.13 | 1039.14 | 01-JAN-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.138840E+09 | 1278.16 | 07-DEC-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.188214E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.138840E+09 | 1278.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT MS1 HEATING COIL
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT MS2 HEATING COIL
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT TSW HEATING COIL
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.374275E+09 | 1612.74 | 01-JAN-07:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.409963E+09 | 1261.16 | 05-FEB-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.388729E+09 | 1720.13 | 26-MAR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 4689579.20 | 492.89 | 21-APR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 77296570.42 | 865.52 | 25-OCT-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.276576E+09 | 1582.49 | 23-NOV-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.821603E+09 | 2113.99 | 07-DEC-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.235313E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.821603E+09 | 2113.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT TNW HEATING COIL
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.664234E+09 | 1945.37 | 01-JAN-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.667626E+09 | 1329.96 | 05-FEB-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.503041E+09 | 1850.89 | 26-MAR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 5390322.75 | 524.07 | 21-APR-05:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.137065E+09 | 1087.40 | 26-OCT-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.499161E+09 | 1781.13 | 23-NOV-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.131652E+10 | 2345.20 | 07-DEC-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.379304E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.131652E+10 | 2345.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT TSE HEATING COIL
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.366599E+09 | 1628.36 | 01-JAN-07:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.390997E+09 | 1305.18 | 05-FEB-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.367579E+09 | 1738.71 | 26-MAR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 3859541.19 | 518.25 | 21-APR-05:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 70699643.22 | 873.79 | 26-OCT-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.267159E+09 | 1607.80 | 23-NOV-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.799235E+09 | 2126.85 | 07-DEC-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.226613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.799235E+09 | 2126.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT TNE HEATING COIL
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.636569E+09 | 1880.52 | 01-JAN-07:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.624193E+09 | 1371.03 | 05-FEB-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.469592E+09 | 1883.05 | 26-MAR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 4686355.27 | 551.09 | 21-APR-05:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.120080E+09 | 1103.22 | 26-OCT-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.476078E+09 | 1828.79 | 24-NOV-03:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.126632E+10 | 2364.67 | 07-DEC-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.359751E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.126632E+10 | 2364.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT TN1 HEATING COIL
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.358748E+09 | 1381.31 | 01-JAN-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.361790E+09 | 903.06 | 05-FEB-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.264974E+09 | 1305.23 | 26-MAR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 530183.50 | 130.73 | 21-APR-05:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 53528082.75 | 715.38 | 26-OCT-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.273559E+09 | 1252.50 | 24-NOV-03:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.848722E+09 | 1719.72 | 07-DEC-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.216185E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.848722E+09 | 1719.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT TN2 HEATING COIL
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.360373E+09 | 1383.88 | 01-JAN-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.361151E+09 | 906.95 | 05-FEB-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.264899E+09 | 1307.22 | 26-MAR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 544967.39 | 133.28 | 21-APR-05:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 53308043.69 | 714.54 | 26-OCT-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.274562E+09 | 1257.35 | 24-NOV-03:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.849395E+09 | 1722.21 | 07-DEC-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.216423E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.849395E+09 | 1722.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT TS1 HEATING COIL
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.128628E+09 | 1043.00 | 01-JAN-07:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.157450E+09 | 821.14 | 05-FEB-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.172754E+09 | 1152.73 | 26-MAR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 251532.09 | 92.59 | 21-APR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 15602369.74 | 441.83 | 26-OCT-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 98024593.02 | 1025.77 | 23-NOV-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.411813E+09 | 1450.97 | 07-DEC-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.984523E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.411813E+09 | 1450.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT TS2 HEATING COIL
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.129372E+09 | 1044.96 | 01-JAN-07:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.157523E+09 | 825.77 | 05-FEB-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.172761E+09 | 1152.86 | 26-MAR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 263515.73 | 95.36 | 21-APR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 15600790.28 | 441.57 | 26-OCT-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 98468936.23 | 1029.11 | 23-NOV-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.412266E+09 | 1452.53 | 07-DEC-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.986255E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.412266E+09 | 1452.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT GSW COOLING COIL
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.977194E+09 | 0.974517E+09 | 2053.37 | 31-JAN-16:30 | 2053.37 | 0.00 |
| February | 0.00 | 0.00 | 65317716.74 | 65307651.75 | 1007.90 | 01-FEB-15:30 | 1007.90 | 0.00 |
| March | 0.00 | 0.00 | 0.338969E+09 | 0.338762E+09 | 1697.28 | 18-MAR-16:30 | 1697.28 | 0.00 |
| April | 0.00 | 0.00 | 0.240001E+10 | 0.240001E+10 | 2638.94 | 14-APR-17:25 | 2638.94 | 0.00 |
| May | 0.00 | 0.00 | 0.299790E+10 | 0.299790E+10 | 2602.75 | 15-MAY-17:15 | 2602.75 | 0.00 |
| June | 0.00 | 0.00 | 0.446831E+10 | 0.446113E+10 | 3439.91 | 30-JUN-17:04 | 3439.91 | 0.00 |
| July | 0.00 | 0.00 | 0.524850E+10 | 0.480373E+10 | 3559.83 | 22-JUL-17:40 | 3559.83 | 0.00 |
| August | 0.00 | 0.00 | 0.528758E+10 | 0.485194E+10 | 3768.65 | 13-AUG-16:01 | 3556.92 | 0.00 |
| September | 0.00 | 0.00 | 0.507999E+10 | 0.462843E+10 | 3527.94 | 08-SEP-17:10 | 3426.67 | 0.00 |
| October | 0.00 | 0.00 | 0.309631E+10 | 0.301811E+10 | 3168.26 | 10-OCT-15:30 | 3168.26 | 0.00 |
| November | 0.00 | 0.00 | 0.153147E+10 | 0.147740E+10 | 2710.43 | 01-NOV-16:02 | 2710.43 | 0.00 |
| December | 0.00 | 0.00 | 0.660792E+09 | 0.660778E+09 | 2157.68 | 25-DEC-16:20 | 2157.68 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.321523E+11 | 0.306780E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 65317716.74 | 65307651.75 | 1007.90 | 1007.90 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.528758E+10 | 0.485194E+10 | 3768.65 | 3559.83 | 0.00 |
Report: CoilReportMonthly
For: SPLIT GNW COOLING COIL
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 93368944.22 | 93365535.54 | 899.48 | 31-JAN-17:02 | 899.48 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.144447E+09 | 0.144412E+09 | 1030.30 | 18-MAR-17:00 | 1030.30 | 0.00 |
| April | 0.00 | 0.00 | 0.186800E+10 | 0.186800E+10 | 2397.79 | 14-APR-17:40 | 2397.79 | 0.00 |
| May | 0.00 | 0.00 | 0.288682E+10 | 0.288682E+10 | 2626.39 | 31-MAY-18:00 | 2626.39 | 0.00 |
| June | 0.00 | 0.00 | 0.457316E+10 | 0.456626E+10 | 3505.44 | 29-JUN-17:50 | 3505.44 | 0.00 |
| July | 0.00 | 0.00 | 0.523047E+10 | 0.478483E+10 | 3515.60 | 22-JUL-18:00 | 3515.60 | 0.00 |
| August | 0.00 | 0.00 | 0.500427E+10 | 0.457323E+10 | 3445.96 | 13-AUG-16:13 | 3269.53 | 0.00 |
| September | 0.00 | 0.00 | 0.452104E+10 | 0.409019E+10 | 3226.63 | 08-SEP-17:10 | 3107.03 | 0.00 |
| October | 0.00 | 0.00 | 0.208296E+10 | 0.201243E+10 | 2601.68 | 03-OCT-17:10 | 2431.91 | 0.00 |
| November | 0.00 | 0.00 | 0.502560E+09 | 0.469870E+09 | 1716.70 | 01-NOV-16:13 | 1709.67 | 0.00 |
| December | 0.00 | 0.00 | 45311102.95 | 45311102.95 | 714.28 | 25-DEC-16:20 | 714.28 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.269524E+11 | 0.255347E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.523047E+10 | 0.478483E+10 | 3515.60 | 3515.60 | 0.00 |
Report: CoilReportMonthly
For: SPLIT OFFICE COOLING COIL
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.115160E+10 | 0.114882E+10 | 6936.45 | 09-JAN-09:02 | 6321.74 | 0.00 |
| February | 0.00 | 0.00 | 0.485561E+09 | 0.474404E+09 | 3057.47 | 23-FEB-09:03 | 3057.47 | 0.00 |
| March | 0.00 | 0.00 | 0.745978E+09 | 0.743261E+09 | 6596.70 | 21-MAR-08:62 | 6596.70 | 0.00 |
| April | 0.00 | 0.00 | 0.197261E+10 | 0.197261E+10 | 7383.87 | 17-APR-07:02 | 7383.87 | 0.00 |
| May | 0.00 | 0.00 | 0.253179E+10 | 0.253179E+10 | 7432.43 | 11-MAY-07:02 | 7432.43 | 0.00 |
| June | 0.00 | 0.00 | 0.367184E+10 | 0.366907E+10 | 7466.90 | 30-JUN-07:02 | 7466.90 | 0.00 |
| July | 0.00 | 0.00 | 0.396974E+10 | 0.373207E+10 | 8371.72 | 14-JUL-07:02 | 5344.41 | 0.00 |
| August | 0.00 | 0.00 | 0.429706E+10 | 0.404964E+10 | 8134.05 | 01-AUG-07:02 | 6118.81 | 0.00 |
| September | 0.00 | 0.00 | 0.374615E+10 | 0.351107E+10 | 8198.95 | 05-SEP-06:02 | 6413.12 | 0.00 |
| October | 0.00 | 0.00 | 0.256185E+10 | 0.251923E+10 | 8110.98 | 03-OCT-07:02 | 6179.46 | 0.00 |
| November | 0.00 | 0.00 | 0.156540E+10 | 0.153621E+10 | 7812.95 | 14-NOV-09:02 | 5952.29 | 0.00 |
| December | 0.00 | 0.00 | 0.873606E+09 | 0.872574E+09 | 7017.55 | 26-DEC-09:02 | 7017.55 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.275732E+11 | 0.267607E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.485561E+09 | 0.474404E+09 | 3057.47 | 3057.47 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.429706E+10 | 0.404964E+10 | 8371.72 | 7466.90 | 0.00 |
Report: CoilReportMonthly
For: SPLIT GNE COOLING COIL
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 73183376.55 | 73179107.89 | 677.78 | 31-JAN-17:02 | 677.78 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.146321E+09 | 0.146246E+09 | 858.94 | 20-MAR-17:00 | 858.94 | 0.00 |
| April | 0.00 | 0.00 | 0.189975E+10 | 0.189974E+10 | 1978.39 | 14-APR-18:00 | 1978.39 | 0.00 |
| May | 0.00 | 0.00 | 0.294780E+10 | 0.294780E+10 | 2259.44 | 31-MAY-18:00 | 2259.44 | 0.00 |
| June | 0.00 | 0.00 | 0.462719E+10 | 0.462008E+10 | 3209.45 | 17-JUN-17:10 | 2897.61 | 0.00 |
| July | 0.00 | 0.00 | 0.537225E+10 | 0.491797E+10 | 3222.97 | 23-JUL-13:00 | 2883.15 | 0.00 |
| August | 0.00 | 0.00 | 0.513752E+10 | 0.469625E+10 | 3152.39 | 13-AUG-16:01 | 2977.11 | 0.00 |
| September | 0.00 | 0.00 | 0.459360E+10 | 0.415526E+10 | 2883.01 | 08-SEP-17:10 | 2773.19 | 0.00 |
| October | 0.00 | 0.00 | 0.213003E+10 | 0.205735E+10 | 2501.30 | 03-OCT-17:20 | 2330.83 | 0.00 |
| November | 0.00 | 0.00 | 0.462972E+09 | 0.434760E+09 | 1346.49 | 01-NOV-16:02 | 1340.77 | 0.00 |
| December | 0.00 | 0.00 | 37388249.06 | 37388249.06 | 468.20 | 25-DEC-16:10 | 468.20 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.274280E+11 | 0.259860E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.537225E+10 | 0.491797E+10 | 3222.97 | 2977.11 | 0.00 |
Report: CoilReportMonthly
For: SPLIT GN1 COOLING COIL
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 82321760.28 | 82308883.42 | 653.79 | 31-JAN-17:02 | 653.79 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.143750E+09 | 0.143695E+09 | 814.60 | 20-MAR-17:10 | 814.60 | 0.00 |
| April | 0.00 | 0.00 | 0.157093E+10 | 0.157093E+10 | 1658.02 | 14-APR-18:00 | 1658.02 | 0.00 |
| May | 0.00 | 0.00 | 0.246433E+10 | 0.246433E+10 | 1899.69 | 31-MAY-18:00 | 1899.69 | 0.00 |
| June | 0.00 | 0.00 | 0.375622E+10 | 0.374999E+10 | 2573.78 | 17-JUN-17:12 | 2327.95 | 0.00 |
| July | 0.00 | 0.00 | 0.438177E+10 | 0.398456E+10 | 2517.87 | 16-JUL-18:00 | 2312.75 | 0.00 |
| August | 0.00 | 0.00 | 0.418122E+10 | 0.379390E+10 | 2486.00 | 13-AUG-16:01 | 2334.84 | 0.00 |
| September | 0.00 | 0.00 | 0.378780E+10 | 0.340365E+10 | 2308.71 | 08-SEP-17:10 | 2221.55 | 0.00 |
| October | 0.00 | 0.00 | 0.178633E+10 | 0.172164E+10 | 2068.24 | 03-OCT-17:30 | 1916.27 | 0.00 |
| November | 0.00 | 0.00 | 0.463289E+09 | 0.427397E+09 | 1156.64 | 01-NOV-16:03 | 1147.19 | 0.00 |
| December | 0.00 | 0.00 | 36792051.72 | 36792051.72 | 442.99 | 25-DEC-16:10 | 442.99 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.226547E+11 | 0.213792E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.438177E+10 | 0.398456E+10 | 2573.78 | 2334.84 | 0.00 |
Report: CoilReportMonthly
For: SPLIT GN2 COOLING COIL
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 83065576.08 | 83053289.90 | 653.67 | 31-JAN-17:02 | 653.67 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.145022E+09 | 0.144965E+09 | 815.47 | 20-MAR-17:10 | 815.47 | 0.00 |
| April | 0.00 | 0.00 | 0.157471E+10 | 0.157471E+10 | 1651.80 | 14-APR-18:00 | 1651.80 | 0.00 |
| May | 0.00 | 0.00 | 0.246791E+10 | 0.246791E+10 | 1894.19 | 31-MAY-18:00 | 1894.19 | 0.00 |
| June | 0.00 | 0.00 | 0.375893E+10 | 0.375270E+10 | 2576.92 | 17-JUN-17:12 | 2330.95 | 0.00 |
| July | 0.00 | 0.00 | 0.438763E+10 | 0.399010E+10 | 2511.17 | 16-JUL-18:00 | 2306.42 | 0.00 |
| August | 0.00 | 0.00 | 0.418698E+10 | 0.379929E+10 | 2484.27 | 13-AUG-16:01 | 2333.30 | 0.00 |
| September | 0.00 | 0.00 | 0.379103E+10 | 0.340663E+10 | 2304.22 | 08-SEP-17:10 | 2217.21 | 0.00 |
| October | 0.00 | 0.00 | 0.179038E+10 | 0.172562E+10 | 2068.03 | 03-OCT-17:30 | 1916.15 | 0.00 |
| November | 0.00 | 0.00 | 0.463176E+09 | 0.427457E+09 | 1152.12 | 01-NOV-16:03 | 1142.73 | 0.00 |
| December | 0.00 | 0.00 | 37239106.97 | 37239106.97 | 441.38 | 25-DEC-16:10 | 441.38 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.226861E+11 | 0.214097E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.438763E+10 | 0.399010E+10 | 2576.92 | 2333.30 | 0.00 |
Report: CoilReportMonthly
For: SPLIT GS1 COOLING COIL
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.117101E+10 | 0.116668E+10 | 1777.79 | 31-JAN-16:10 | 1777.79 | 0.00 |
| February | 0.00 | 0.00 | 0.137501E+09 | 0.137100E+09 | 1011.07 | 01-FEB-15:30 | 1011.07 | 0.00 |
| March | 0.00 | 0.00 | 0.401191E+09 | 0.400884E+09 | 1418.92 | 18-MAR-16:10 | 1418.92 | 0.00 |
| April | 0.00 | 0.00 | 0.214340E+10 | 0.214340E+10 | 1925.29 | 10-APR-16:02 | 1925.29 | 0.00 |
| May | 0.00 | 0.00 | 0.259118E+10 | 0.259118E+10 | 1940.71 | 20-MAY-14:00 | 1940.71 | 0.00 |
| June | 0.00 | 0.00 | 0.366391E+10 | 0.365738E+10 | 2614.03 | 17-JUN-17:02 | 2340.28 | 0.00 |
| July | 0.00 | 0.00 | 0.441576E+10 | 0.401855E+10 | 2627.41 | 23-JUL-13:00 | 2322.94 | 0.00 |
| August | 0.00 | 0.00 | 0.448453E+10 | 0.409107E+10 | 2810.93 | 13-AUG-16:01 | 2635.74 | 0.00 |
| September | 0.00 | 0.00 | 0.437217E+10 | 0.396483E+10 | 2635.89 | 08-SEP-16:09 | 2635.89 | 0.00 |
| October | 0.00 | 0.00 | 0.286122E+10 | 0.278804E+10 | 2520.07 | 10-OCT-15:10 | 2520.07 | 0.00 |
| November | 0.00 | 0.00 | 0.161318E+10 | 0.155443E+10 | 2137.56 | 01-NOV-15:10 | 2125.59 | 0.00 |
| December | 0.00 | 0.00 | 0.844493E+09 | 0.844402E+09 | 1842.79 | 25-DEC-16:10 | 1842.79 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.286995E+11 | 0.273579E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.137501E+09 | 0.137100E+09 | 1011.07 | 1011.07 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.448453E+10 | 0.409107E+10 | 2810.93 | 2635.89 | 0.00 |
Report: CoilReportMonthly
For: SPLIT GS2 COOLING COIL
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.125543E+10 | 0.125059E+10 | 1836.75 | 31-JAN-16:10 | 1836.75 | 0.00 |
| February | 0.00 | 0.00 | 0.164049E+09 | 0.163427E+09 | 1068.15 | 01-FEB-15:30 | 1068.15 | 0.00 |
| March | 0.00 | 0.00 | 0.456534E+09 | 0.456168E+09 | 1507.47 | 18-MAR-16:05 | 1507.47 | 0.00 |
| April | 0.00 | 0.00 | 0.236106E+10 | 0.236105E+10 | 2009.89 | 10-APR-16:02 | 2009.89 | 0.00 |
| May | 0.00 | 0.00 | 0.286437E+10 | 0.286437E+10 | 2074.99 | 20-MAY-14:00 | 2074.99 | 0.00 |
| June | 0.00 | 0.00 | 0.398901E+10 | 0.398225E+10 | 2778.89 | 17-JUN-17:02 | 2496.69 | 0.00 |
| July | 0.00 | 0.00 | 0.479609E+10 | 0.438229E+10 | 2814.16 | 23-JUL-13:00 | 2505.64 | 0.00 |
| August | 0.00 | 0.00 | 0.484944E+10 | 0.443885E+10 | 2995.42 | 13-AUG-16:01 | 2817.66 | 0.00 |
| September | 0.00 | 0.00 | 0.473638E+10 | 0.431018E+10 | 2793.55 | 09-SEP-12:50 | 2609.92 | 0.00 |
| October | 0.00 | 0.00 | 0.313016E+10 | 0.305293E+10 | 2633.41 | 10-OCT-15:10 | 2633.41 | 0.00 |
| November | 0.00 | 0.00 | 0.174574E+10 | 0.168107E+10 | 2199.26 | 01-NOV-15:10 | 2187.64 | 0.00 |
| December | 0.00 | 0.00 | 0.919450E+09 | 0.919335E+09 | 1938.67 | 25-DEC-16:10 | 1938.67 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.312677E+11 | 0.298625E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.164049E+09 | 0.163427E+09 | 1068.15 | 1068.15 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.484944E+10 | 0.443885E+10 | 2995.42 | 2817.66 | 0.00 |
Report: CoilReportMonthly
For: SPLIT MSW COOLING COIL
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.278140E+10 | 0.277293E+10 | 5164.51 | 31-JAN-16:30 | 5164.51 | 0.00 |
| February | 0.00 | 0.00 | 0.702680E+09 | 0.696347E+09 | 3155.73 | 22-FEB-16:20 | 3155.73 | 0.00 |
| March | 0.00 | 0.00 | 0.173801E+10 | 0.173641E+10 | 5149.21 | 18-MAR-16:30 | 5149.21 | 0.00 |
| April | 0.00 | 0.00 | 0.638563E+10 | 0.638563E+10 | 6486.51 | 14-APR-17:30 | 6486.51 | 0.00 |
| May | 0.00 | 0.00 | 0.775070E+10 | 0.775070E+10 | 6557.19 | 15-MAY-17:30 | 6557.19 | 0.00 |
| June | 0.00 | 0.00 | 0.103719E+11 | 0.103562E+11 | 8064.90 | 30-JUN-17:03 | 8064.90 | 0.00 |
| July | 0.00 | 0.00 | 0.109753E+11 | 0.100297E+11 | 7987.37 | 22-JUL-17:40 | 7987.37 | 0.00 |
| August | 0.00 | 0.00 | 0.105806E+11 | 0.968190E+10 | 8323.63 | 13-AUG-16:01 | 7848.61 | 0.00 |
| September | 0.00 | 0.00 | 0.954894E+10 | 0.865380E+10 | 7361.86 | 08-SEP-16:10 | 7361.86 | 0.00 |
| October | 0.00 | 0.00 | 0.568249E+10 | 0.553250E+10 | 6959.65 | 10-OCT-15:30 | 6959.65 | 0.00 |
| November | 0.00 | 0.00 | 0.272884E+10 | 0.264713E+10 | 6041.49 | 01-NOV-16:05 | 6041.49 | 0.00 |
| December | 0.00 | 0.00 | 0.136338E+10 | 0.136336E+10 | 5020.92 | 25-DEC-16:20 | 5020.92 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.706098E+11 | 0.676066E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.702680E+09 | 0.696347E+09 | 3155.73 | 3155.73 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.109753E+11 | 0.103562E+11 | 8323.63 | 8064.90 | 0.00 |
Report: CoilReportMonthly
For: SPLIT MNW COOLING COIL
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.394261E+09 | 0.393541E+09 | 2427.71 | 31-JAN-17:04 | 2427.71 | 0.00 |
| February | 0.00 | 0.00 | 15786714.02 | 15617142.39 | 1074.27 | 22-FEB-16:30 | 1074.27 | 0.00 |
| March | 0.00 | 0.00 | 0.846488E+09 | 0.846140E+09 | 3569.11 | 18-MAR-17:00 | 3569.11 | 0.00 |
| April | 0.00 | 0.00 | 0.522428E+10 | 0.522428E+10 | 5966.94 | 14-APR-17:40 | 5966.94 | 0.00 |
| May | 0.00 | 0.00 | 0.750844E+10 | 0.750844E+10 | 6544.48 | 31-MAY-18:00 | 6544.48 | 0.00 |
| June | 0.00 | 0.00 | 0.105661E+11 | 0.105510E+11 | 8202.27 | 29-JUN-18:00 | 8202.27 | 0.00 |
| July | 0.00 | 0.00 | 0.109027E+11 | 0.995619E+10 | 7898.16 | 16-JUL-18:00 | 7236.85 | 0.00 |
| August | 0.00 | 0.00 | 0.995749E+10 | 0.907129E+10 | 7570.10 | 13-AUG-16:01 | 7149.84 | 0.00 |
| September | 0.00 | 0.00 | 0.835099E+10 | 0.750631E+10 | 6661.84 | 08-SEP-17:10 | 6396.66 | 0.00 |
| October | 0.00 | 0.00 | 0.359909E+10 | 0.346576E+10 | 5302.53 | 06-OCT-16:01 | 5302.53 | 0.00 |
| November | 0.00 | 0.00 | 0.714419E+09 | 0.674072E+09 | 3751.41 | 01-NOV-16:13 | 3744.36 | 0.00 |
| December | 0.00 | 0.00 | 66374197.18 | 66374197.18 | 1577.11 | 25-DEC-16:30 | 1577.11 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.581464E+11 | 0.552790E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 15786714.02 | 15617142.39 | 1074.27 | 1074.27 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.109027E+11 | 0.105510E+11 | 8202.27 | 8202.27 | 0.00 |
Report: CoilReportMonthly
For: SPLIT MSE COOLING COIL
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.273294E+10 | 0.272421E+10 | 4378.61 | 31-JAN-16:10 | 4378.61 | 0.00 |
| February | 0.00 | 0.00 | 0.781667E+09 | 0.770903E+09 | 2577.75 | 23-FEB-14:00 | 2577.75 | 0.00 |
| March | 0.00 | 0.00 | 0.178360E+10 | 0.178197E+10 | 4330.51 | 18-MAR-15:10 | 4330.51 | 0.00 |
| April | 0.00 | 0.00 | 0.647690E+10 | 0.647690E+10 | 5615.37 | 10-APR-16:02 | 5615.37 | 0.00 |
| May | 0.00 | 0.00 | 0.788708E+10 | 0.788708E+10 | 6199.19 | 20-MAY-14:00 | 6199.19 | 0.00 |
| June | 0.00 | 0.00 | 0.104904E+11 | 0.104741E+11 | 7498.12 | 17-JUN-17:02 | 6706.93 | 0.00 |
| July | 0.00 | 0.00 | 0.112837E+11 | 0.103168E+11 | 7517.35 | 23-JUL-13:00 | 6679.02 | 0.00 |
| August | 0.00 | 0.00 | 0.108679E+11 | 0.994370E+10 | 7467.93 | 13-AUG-16:01 | 7021.16 | 0.00 |
| September | 0.00 | 0.00 | 0.970743E+10 | 0.879290E+10 | 6715.25 | 01-SEP-16:00 | 6139.16 | 0.00 |
| October | 0.00 | 0.00 | 0.580295E+10 | 0.564795E+10 | 6294.66 | 10-OCT-15:10 | 6294.66 | 0.00 |
| November | 0.00 | 0.00 | 0.265199E+10 | 0.257995E+10 | 5037.75 | 01-NOV-15:10 | 5016.51 | 0.00 |
| December | 0.00 | 0.00 | 0.135802E+10 | 0.135795E+10 | 4138.33 | 25-DEC-14:00 | 4138.33 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.718246E+11 | 0.687545E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.781667E+09 | 0.770903E+09 | 2577.75 | 2577.75 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.112837E+11 | 0.104741E+11 | 7517.35 | 7021.16 | 0.00 |
Report: CoilReportMonthly
For: SPLIT MNE COOLING COIL
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.320437E+09 | 0.319946E+09 | 1797.31 | 31-JAN-17:06 | 1797.31 | 0.00 |
| February | 0.00 | 0.00 | 16208428.92 | 15365204.06 | 650.25 | 18-FEB-16:10 | 639.90 | 0.00 |
| March | 0.00 | 0.00 | 0.861135E+09 | 0.860777E+09 | 2848.25 | 16-MAR-16:08 | 2848.25 | 0.00 |
| April | 0.00 | 0.00 | 0.531289E+10 | 0.531289E+10 | 4806.30 | 14-APR-18:00 | 4806.30 | 0.00 |
| May | 0.00 | 0.00 | 0.764570E+10 | 0.764570E+10 | 5623.84 | 20-MAY-14:00 | 5623.84 | 0.00 |
| June | 0.00 | 0.00 | 0.106852E+11 | 0.106696E+11 | 7359.20 | 17-JUN-17:10 | 6620.71 | 0.00 |
| July | 0.00 | 0.00 | 0.112112E+11 | 0.102437E+11 | 7103.49 | 23-JUL-13:00 | 6311.89 | 0.00 |
| August | 0.00 | 0.00 | 0.102459E+11 | 0.933293E+10 | 6733.96 | 13-AUG-16:01 | 6341.37 | 0.00 |
| September | 0.00 | 0.00 | 0.851125E+10 | 0.764486E+10 | 6069.42 | 01-SEP-16:00 | 5472.89 | 0.00 |
| October | 0.00 | 0.00 | 0.367847E+10 | 0.353945E+10 | 4974.64 | 03-OCT-18:00 | 4596.73 | 0.00 |
| November | 0.00 | 0.00 | 0.615646E+09 | 0.586950E+09 | 2728.55 | 01-NOV-16:02 | 2722.70 | 0.00 |
| December | 0.00 | 0.00 | 46889447.56 | 46889447.56 | 914.34 | 25-DEC-16:10 | 914.34 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.591510E+11 | 0.562191E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 16208428.92 | 15365204.06 | 650.25 | 639.90 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.112112E+11 | 0.106696E+11 | 7359.20 | 6620.71 | 0.00 |
Report: CoilReportMonthly
For: SPLIT MN1 COOLING COIL
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.385182E+09 | 0.382286E+09 | 1683.83 | 31-JAN-17:04 | 1683.83 | 0.00 |
| February | 0.00 | 0.00 | 39582263.22 | 36899332.33 | 749.75 | 18-FEB-16:10 | 736.18 | 0.00 |
| March | 0.00 | 0.00 | 0.810668E+09 | 0.810101E+09 | 2452.65 | 20-MAR-17:05 | 2452.65 | 0.00 |
| April | 0.00 | 0.00 | 0.418071E+10 | 0.418071E+10 | 3856.53 | 14-APR-18:00 | 3856.53 | 0.00 |
| May | 0.00 | 0.00 | 0.598956E+10 | 0.598956E+10 | 4437.02 | 31-MAY-18:00 | 4437.02 | 0.00 |
| June | 0.00 | 0.00 | 0.825368E+10 | 0.824049E+10 | 5635.94 | 17-JUN-17:12 | 5078.73 | 0.00 |
| July | 0.00 | 0.00 | 0.886717E+10 | 0.804535E+10 | 5383.53 | 16-JUL-18:00 | 4920.89 | 0.00 |
| August | 0.00 | 0.00 | 0.816105E+10 | 0.737717E+10 | 5154.02 | 13-AUG-16:01 | 4826.86 | 0.00 |
| September | 0.00 | 0.00 | 0.699797E+10 | 0.624711E+10 | 4682.34 | 01-SEP-16:10 | 4149.17 | 0.00 |
| October | 0.00 | 0.00 | 0.313497E+10 | 0.301205E+10 | 4058.65 | 03-OCT-18:00 | 3736.66 | 0.00 |
| November | 0.00 | 0.00 | 0.734135E+09 | 0.675226E+09 | 2374.62 | 01-NOV-16:02 | 2359.04 | 0.00 |
| December | 0.00 | 0.00 | 68874659.25 | 68874659.25 | 966.35 | 25-DEC-16:10 | 966.35 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.476236E+11 | 0.450658E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 39582263.22 | 36899332.33 | 749.75 | 736.18 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.886717E+10 | 0.824049E+10 | 5635.94 | 5078.73 | 0.00 |
Report: CoilReportMonthly
For: SPLIT MN2 COOLING COIL
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.387434E+09 | 0.384591E+09 | 1684.89 | 31-JAN-17:04 | 1684.89 | 0.00 |
| February | 0.00 | 0.00 | 43223695.87 | 40333214.47 | 785.07 | 18-FEB-18:40 | 667.73 | 0.00 |
| March | 0.00 | 0.00 | 0.817879E+09 | 0.817296E+09 | 2452.48 | 20-MAR-17:05 | 2452.48 | 0.00 |
| April | 0.00 | 0.00 | 0.418793E+10 | 0.418793E+10 | 3839.64 | 14-APR-18:00 | 3839.64 | 0.00 |
| May | 0.00 | 0.00 | 0.599609E+10 | 0.599609E+10 | 4422.76 | 31-MAY-18:00 | 4422.76 | 0.00 |
| June | 0.00 | 0.00 | 0.825885E+10 | 0.824565E+10 | 5643.91 | 17-JUN-17:12 | 5086.35 | 0.00 |
| July | 0.00 | 0.00 | 0.887814E+10 | 0.805571E+10 | 5365.33 | 16-JUL-18:00 | 4903.74 | 0.00 |
| August | 0.00 | 0.00 | 0.817193E+10 | 0.738727E+10 | 5148.93 | 13-AUG-16:01 | 4822.26 | 0.00 |
| September | 0.00 | 0.00 | 0.700428E+10 | 0.625287E+10 | 4684.02 | 01-SEP-16:10 | 4151.01 | 0.00 |
| October | 0.00 | 0.00 | 0.314374E+10 | 0.302065E+10 | 4057.93 | 03-OCT-18:00 | 3736.05 | 0.00 |
| November | 0.00 | 0.00 | 0.734972E+09 | 0.676553E+09 | 2363.50 | 01-NOV-16:02 | 2348.05 | 0.00 |
| December | 0.00 | 0.00 | 70302132.76 | 70302132.76 | 963.06 | 25-DEC-16:10 | 963.06 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.476948E+11 | 0.451352E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 43223695.87 | 40333214.47 | 785.07 | 667.73 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.887814E+10 | 0.824565E+10 | 5643.91 | 5086.35 | 0.00 |
Report: CoilReportMonthly
For: SPLIT MS1 COOLING COIL
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.314274E+10 | 0.313137E+10 | 4237.85 | 31-JAN-16:10 | 4237.85 | 0.00 |
| February | 0.00 | 0.00 | 0.109791E+10 | 0.107835E+10 | 2741.68 | 01-FEB-15:30 | 2741.68 | 0.00 |
| March | 0.00 | 0.00 | 0.187462E+10 | 0.187153E+10 | 3916.58 | 18-MAR-16:10 | 3916.58 | 0.00 |
| April | 0.00 | 0.00 | 0.535929E+10 | 0.535929E+10 | 4578.45 | 10-APR-16:03 | 4578.45 | 0.00 |
| May | 0.00 | 0.00 | 0.623323E+10 | 0.623323E+10 | 4638.12 | 20-MAY-14:00 | 4638.12 | 0.00 |
| June | 0.00 | 0.00 | 0.805859E+10 | 0.804482E+10 | 5762.77 | 17-JUN-17:02 | 5148.43 | 0.00 |
| July | 0.00 | 0.00 | 0.893992E+10 | 0.811852E+10 | 5594.35 | 23-JUL-13:00 | 4918.95 | 0.00 |
| August | 0.00 | 0.00 | 0.878789E+10 | 0.799028E+10 | 5881.50 | 13-AUG-16:01 | 5505.23 | 0.00 |
| September | 0.00 | 0.00 | 0.820521E+10 | 0.740202E+10 | 5297.27 | 08-SEP-16:10 | 5297.27 | 0.00 |
| October | 0.00 | 0.00 | 0.534345E+10 | 0.520270E+10 | 5336.89 | 10-OCT-15:10 | 5336.89 | 0.00 |
| November | 0.00 | 0.00 | 0.304844E+10 | 0.294520E+10 | 4644.10 | 01-NOV-15:10 | 4621.05 | 0.00 |
| December | 0.00 | 0.00 | 0.183374E+10 | 0.183351E+10 | 4190.00 | 25-DEC-14:00 | 4190.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.619250E+11 | 0.592108E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.109791E+10 | 0.107835E+10 | 2741.68 | 2741.68 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.893992E+10 | 0.811852E+10 | 5881.50 | 5505.23 | 0.00 |
Report: CoilReportMonthly
For: SPLIT MS2 COOLING COIL
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.314493E+10 | 0.313356E+10 | 4232.60 | 31-JAN-16:10 | 4232.60 | 0.00 |
| February | 0.00 | 0.00 | 0.111003E+10 | 0.109008E+10 | 2741.65 | 01-FEB-15:30 | 2741.65 | 0.00 |
| March | 0.00 | 0.00 | 0.188630E+10 | 0.188315E+10 | 3910.72 | 18-MAR-16:10 | 3910.72 | 0.00 |
| April | 0.00 | 0.00 | 0.536536E+10 | 0.536536E+10 | 4578.15 | 10-APR-16:03 | 4578.15 | 0.00 |
| May | 0.00 | 0.00 | 0.623989E+10 | 0.623989E+10 | 4649.67 | 20-MAY-14:00 | 4649.67 | 0.00 |
| June | 0.00 | 0.00 | 0.806389E+10 | 0.805012E+10 | 5771.00 | 17-JUN-17:02 | 5156.25 | 0.00 |
| July | 0.00 | 0.00 | 0.895096E+10 | 0.812895E+10 | 5605.46 | 23-JUL-13:00 | 4930.05 | 0.00 |
| August | 0.00 | 0.00 | 0.879863E+10 | 0.800029E+10 | 5875.98 | 13-AUG-16:01 | 5500.19 | 0.00 |
| September | 0.00 | 0.00 | 0.821120E+10 | 0.740756E+10 | 5311.61 | 09-SEP-12:50 | 4927.64 | 0.00 |
| October | 0.00 | 0.00 | 0.535134E+10 | 0.521045E+10 | 5335.80 | 10-OCT-15:10 | 5335.80 | 0.00 |
| November | 0.00 | 0.00 | 0.304867E+10 | 0.294586E+10 | 4637.08 | 01-NOV-15:10 | 4614.11 | 0.00 |
| December | 0.00 | 0.00 | 0.184203E+10 | 0.184179E+10 | 4195.13 | 25-DEC-14:00 | 4195.13 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.620132E+11 | 0.592971E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.111003E+10 | 0.109008E+10 | 2741.65 | 2741.65 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.895096E+10 | 0.812895E+10 | 5875.98 | 5500.19 | 0.00 |
Report: CoilReportMonthly
For: SPLIT TSW COOLING COIL
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.122952E+10 | 0.122845E+10 | 3081.30 | 31-JAN-16:30 | 3081.30 | 0.00 |
| February | 0.00 | 0.00 | 0.271925E+09 | 0.270959E+09 | 1853.17 | 28-FEB-16:30 | 1853.17 | 0.00 |
| March | 0.00 | 0.00 | 0.841181E+09 | 0.840775E+09 | 3275.88 | 18-MAR-16:20 | 3275.88 | 0.00 |
| April | 0.00 | 0.00 | 0.340086E+10 | 0.340086E+10 | 4308.51 | 14-APR-17:30 | 4308.51 | 0.00 |
| May | 0.00 | 0.00 | 0.427009E+10 | 0.427009E+10 | 4390.52 | 15-MAY-17:15 | 4390.52 | 0.00 |
| June | 0.00 | 0.00 | 0.611278E+10 | 0.610409E+10 | 5460.65 | 30-JUN-16:06 | 5460.65 | 0.00 |
| July | 0.00 | 0.00 | 0.639319E+10 | 0.588611E+10 | 5346.71 | 22-JUL-16:04 | 5346.71 | 0.00 |
| August | 0.00 | 0.00 | 0.604571E+10 | 0.557976E+10 | 5558.61 | 13-AUG-16:01 | 5283.01 | 0.00 |
| September | 0.00 | 0.00 | 0.526050E+10 | 0.480981E+10 | 4932.87 | 08-SEP-16:01 | 4932.87 | 0.00 |
| October | 0.00 | 0.00 | 0.278453E+10 | 0.271267E+10 | 4556.56 | 10-OCT-15:30 | 4556.56 | 0.00 |
| November | 0.00 | 0.00 | 0.112148E+10 | 0.110345E+10 | 3884.29 | 01-NOV-16:02 | 3884.29 | 0.00 |
| December | 0.00 | 0.00 | 0.645892E+09 | 0.645892E+09 | 2984.96 | 25-DEC-16:20 | 2984.96 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.383777E+11 | 0.368529E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.271925E+09 | 0.270959E+09 | 1853.17 | 1853.17 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.639319E+10 | 0.610409E+10 | 5558.61 | 5460.65 | 0.00 |
Report: CoilReportMonthly
For: SPLIT TNW COOLING COIL
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.201590E+09 | 0.201584E+09 | 1481.50 | 31-JAN-17:02 | 1481.50 | 0.00 |
| February | 0.00 | 0.00 | 6433018.14 | 6425026.84 | 578.47 | 22-FEB-16:30 | 578.47 | 0.00 |
| March | 0.00 | 0.00 | 0.436953E+09 | 0.436894E+09 | 2247.03 | 16-MAR-16:30 | 2247.03 | 0.00 |
| April | 0.00 | 0.00 | 0.279083E+10 | 0.279083E+10 | 3981.57 | 14-APR-17:30 | 3981.57 | 0.00 |
| May | 0.00 | 0.00 | 0.413232E+10 | 0.413232E+10 | 4315.76 | 15-MAY-17:30 | 4315.76 | 0.00 |
| June | 0.00 | 0.00 | 0.621410E+10 | 0.620564E+10 | 5431.34 | 29-JUN-17:30 | 5431.34 | 0.00 |
| July | 0.00 | 0.00 | 0.634775E+10 | 0.583878E+10 | 5228.20 | 16-JUL-18:00 | 4807.79 | 0.00 |
| August | 0.00 | 0.00 | 0.569760E+10 | 0.523611E+10 | 5067.36 | 13-AUG-16:01 | 4822.17 | 0.00 |
| September | 0.00 | 0.00 | 0.460842E+10 | 0.418053E+10 | 4426.09 | 08-SEP-17:10 | 4252.86 | 0.00 |
| October | 0.00 | 0.00 | 0.178424E+10 | 0.171922E+10 | 3521.16 | 06-OCT-16:01 | 3521.16 | 0.00 |
| November | 0.00 | 0.00 | 0.291830E+09 | 0.285642E+09 | 2443.50 | 01-NOV-16:20 | 2443.50 | 0.00 |
| December | 0.00 | 0.00 | 53613100.47 | 53613100.47 | 1048.10 | 22-DEC-16:30 | 1048.10 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.325657E+11 | 0.310876E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 6433018.14 | 6425026.84 | 578.47 | 578.47 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.634775E+10 | 0.620564E+10 | 5431.34 | 5431.34 | 0.00 |
Report: CoilReportMonthly
For: SPLIT TSE COOLING COIL
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.116182E+10 | 0.116077E+10 | 2542.92 | 31-JAN-15:20 | 2542.92 | 0.00 |
| February | 0.00 | 0.00 | 0.272744E+09 | 0.270893E+09 | 1465.48 | 23-FEB-14:00 | 1465.48 | 0.00 |
| March | 0.00 | 0.00 | 0.824904E+09 | 0.824502E+09 | 2749.13 | 18-MAR-15:20 | 2749.13 | 0.00 |
| April | 0.00 | 0.00 | 0.342268E+10 | 0.342268E+10 | 3714.41 | 30-APR-15:10 | 3714.41 | 0.00 |
| May | 0.00 | 0.00 | 0.433583E+10 | 0.433583E+10 | 4176.73 | 20-MAY-14:00 | 4176.73 | 0.00 |
| June | 0.00 | 0.00 | 0.618053E+10 | 0.617153E+10 | 4921.11 | 30-JUN-16:04 | 4921.11 | 0.00 |
| July | 0.00 | 0.00 | 0.656461E+10 | 0.604523E+10 | 4877.86 | 23-JUL-13:00 | 4374.45 | 0.00 |
| August | 0.00 | 0.00 | 0.620340E+10 | 0.572213E+10 | 4920.38 | 13-AUG-16:01 | 4661.18 | 0.00 |
| September | 0.00 | 0.00 | 0.534686E+10 | 0.488348E+10 | 4522.60 | 09-SEP-12:50 | 4285.64 | 0.00 |
| October | 0.00 | 0.00 | 0.281609E+10 | 0.274132E+10 | 4259.21 | 02-OCT-13:50 | 4154.02 | 0.00 |
| November | 0.00 | 0.00 | 0.105937E+10 | 0.104473E+10 | 3248.57 | 01-NOV-14:30 | 3206.30 | 0.00 |
| December | 0.00 | 0.00 | 0.612213E+09 | 0.612208E+09 | 2377.57 | 25-DEC-14:20 | 2377.57 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.388010E+11 | 0.372353E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.272744E+09 | 0.270893E+09 | 1465.48 | 1465.48 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.656461E+10 | 0.617153E+10 | 4921.11 | 4921.11 | 0.00 |
Report: CoilReportMonthly
For: SPLIT TNE COOLING COIL
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.136428E+09 | 0.136409E+09 | 976.06 | 31-JAN-17:02 | 976.06 | 0.00 |
| February | 0.00 | 0.00 | 1767208.85 | 1722277.70 | 190.57 | 18-FEB-16:00 | 188.15 | 0.00 |
| March | 0.00 | 0.00 | 0.407533E+09 | 0.407395E+09 | 1773.58 | 16-MAR-16:10 | 1773.58 | 0.00 |
| April | 0.00 | 0.00 | 0.280715E+10 | 0.280715E+10 | 3122.66 | 30-APR-15:10 | 3122.66 | 0.00 |
| May | 0.00 | 0.00 | 0.420190E+10 | 0.420190E+10 | 3772.25 | 20-MAY-14:00 | 3772.25 | 0.00 |
| June | 0.00 | 0.00 | 0.628342E+10 | 0.627467E+10 | 4845.40 | 30-JUN-16:10 | 4845.40 | 0.00 |
| July | 0.00 | 0.00 | 0.651961E+10 | 0.599871E+10 | 4608.57 | 23-JUL-13:00 | 4130.35 | 0.00 |
| August | 0.00 | 0.00 | 0.585610E+10 | 0.537872E+10 | 4440.94 | 13-AUG-16:01 | 4211.93 | 0.00 |
| September | 0.00 | 0.00 | 0.469567E+10 | 0.425360E+10 | 3968.59 | 01-SEP-16:00 | 3618.97 | 0.00 |
| October | 0.00 | 0.00 | 0.179387E+10 | 0.172566E+10 | 3308.53 | 02-OCT-14:00 | 3190.27 | 0.00 |
| November | 0.00 | 0.00 | 0.236284E+09 | 0.231881E+09 | 1713.84 | 01-NOV-16:03 | 1713.84 | 0.00 |
| December | 0.00 | 0.00 | 33186204.91 | 33186204.91 | 541.59 | 25-DEC-16:10 | 541.59 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.329729E+11 | 0.314510E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 1767208.85 | 1722277.70 | 190.57 | 188.15 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.651961E+10 | 0.627467E+10 | 4845.40 | 4845.40 | 0.00 |
Report: CoilReportMonthly
For: SPLIT TN1 COOLING COIL
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 86365781.78 | 86348597.10 | 782.29 | 31-JAN-17:08 | 782.29 | 0.00 |
| February | 0.00 | 0.00 | 254287.27 | 250143.54 | 77.10 | 18-FEB-16:10 | 75.80 | 0.00 |
| March | 0.00 | 0.00 | 0.310017E+09 | 0.309947E+09 | 1480.93 | 16-MAR-16:12 | 1480.93 | 0.00 |
| April | 0.00 | 0.00 | 0.215771E+10 | 0.215771E+10 | 2557.42 | 14-APR-17:40 | 2557.42 | 0.00 |
| May | 0.00 | 0.00 | 0.328463E+10 | 0.328463E+10 | 2927.51 | 31-MAY-18:00 | 2927.51 | 0.00 |
| June | 0.00 | 0.00 | 0.494206E+10 | 0.493478E+10 | 3797.31 | 30-JUN-16:10 | 3797.31 | 0.00 |
| July | 0.00 | 0.00 | 0.523116E+10 | 0.479020E+10 | 3608.08 | 16-JUL-18:00 | 3316.91 | 0.00 |
| August | 0.00 | 0.00 | 0.472119E+10 | 0.431137E+10 | 3516.57 | 13-AUG-16:01 | 3329.79 | 0.00 |
| September | 0.00 | 0.00 | 0.387278E+10 | 0.349089E+10 | 3124.74 | 01-SEP-16:10 | 2808.03 | 0.00 |
| October | 0.00 | 0.00 | 0.143242E+10 | 0.137358E+10 | 2589.41 | 02-OCT-14:00 | 2489.96 | 0.00 |
| November | 0.00 | 0.00 | 0.182096E+09 | 0.176662E+09 | 1486.93 | 01-NOV-16:02 | 1481.52 | 0.00 |
| December | 0.00 | 0.00 | 17803192.37 | 17803192.37 | 424.55 | 25-DEC-16:10 | 424.55 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.262385E+11 | 0.249342E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 254287.27 | 250143.54 | 77.10 | 75.80 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.523116E+10 | 0.493478E+10 | 3797.31 | 3797.31 | 0.00 |
Report: CoilReportMonthly
For: SPLIT TN2 COOLING COIL
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 87858231.45 | 87840213.92 | 776.04 | 31-JAN-17:08 | 776.04 | 0.00 |
| February | 0.00 | 0.00 | 321739.86 | 316177.37 | 89.50 | 18-FEB-16:10 | 88.00 | 0.00 |
| March | 0.00 | 0.00 | 0.313267E+09 | 0.313193E+09 | 1476.61 | 16-MAR-16:05 | 1476.61 | 0.00 |
| April | 0.00 | 0.00 | 0.216448E+10 | 0.216448E+10 | 2537.47 | 14-APR-17:40 | 2537.47 | 0.00 |
| May | 0.00 | 0.00 | 0.329025E+10 | 0.329025E+10 | 2908.00 | 31-MAY-18:00 | 2908.00 | 0.00 |
| June | 0.00 | 0.00 | 0.494587E+10 | 0.493858E+10 | 3789.02 | 30-JUN-16:10 | 3789.02 | 0.00 |
| July | 0.00 | 0.00 | 0.523814E+10 | 0.479684E+10 | 3587.74 | 16-JUL-18:00 | 3297.55 | 0.00 |
| August | 0.00 | 0.00 | 0.472809E+10 | 0.431778E+10 | 3507.39 | 13-AUG-16:01 | 3321.07 | 0.00 |
| September | 0.00 | 0.00 | 0.387710E+10 | 0.349480E+10 | 3122.29 | 01-SEP-16:10 | 2805.85 | 0.00 |
| October | 0.00 | 0.00 | 0.143743E+10 | 0.137847E+10 | 2595.72 | 02-OCT-14:00 | 2496.39 | 0.00 |
| November | 0.00 | 0.00 | 0.182807E+09 | 0.177467E+09 | 1472.00 | 01-NOV-16:02 | 1466.69 | 0.00 |
| December | 0.00 | 0.00 | 18288177.93 | 18288177.93 | 421.43 | 25-DEC-16:10 | 421.43 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.262839E+11 | 0.249783E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 321739.86 | 316177.37 | 89.50 | 88.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.523814E+10 | 0.493858E+10 | 3789.02 | 3789.02 | 0.00 |
Report: CoilReportMonthly
For: SPLIT TS1 COOLING COIL
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.112835E+10 | 0.112663E+10 | 2335.86 | 31-JAN-16:10 | 2335.86 | 0.00 |
| February | 0.00 | 0.00 | 0.255575E+09 | 0.254145E+09 | 1311.73 | 01-FEB-15:30 | 1311.73 | 0.00 |
| March | 0.00 | 0.00 | 0.706388E+09 | 0.705951E+09 | 2484.15 | 18-MAR-15:20 | 2484.15 | 0.00 |
| April | 0.00 | 0.00 | 0.277777E+10 | 0.277777E+10 | 3044.94 | 10-APR-15:20 | 3044.94 | 0.00 |
| May | 0.00 | 0.00 | 0.342090E+10 | 0.342090E+10 | 3217.96 | 20-MAY-14:00 | 3217.96 | 0.00 |
| June | 0.00 | 0.00 | 0.483918E+10 | 0.483164E+10 | 3874.49 | 30-JUN-16:10 | 3874.49 | 0.00 |
| July | 0.00 | 0.00 | 0.527666E+10 | 0.483728E+10 | 3793.83 | 22-JUL-16:01 | 3793.83 | 0.00 |
| August | 0.00 | 0.00 | 0.507190E+10 | 0.465746E+10 | 3999.56 | 13-AUG-16:01 | 3785.02 | 0.00 |
| September | 0.00 | 0.00 | 0.453133E+10 | 0.412632E+10 | 3655.94 | 09-SEP-12:50 | 3439.06 | 0.00 |
| October | 0.00 | 0.00 | 0.246260E+10 | 0.239628E+10 | 3558.87 | 02-OCT-13:50 | 3469.99 | 0.00 |
| November | 0.00 | 0.00 | 0.103341E+10 | 0.101416E+10 | 3003.02 | 01-NOV-15:10 | 2993.21 | 0.00 |
| December | 0.00 | 0.00 | 0.618578E+09 | 0.618575E+09 | 2278.29 | 25-DEC-15:10 | 2278.29 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.321226E+11 | 0.307671E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.255575E+09 | 0.254145E+09 | 1311.73 | 1311.73 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.527666E+10 | 0.483728E+10 | 3999.56 | 3874.49 | 0.00 |
Report: CoilReportMonthly
For: SPLIT TS2 COOLING COIL
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.113292E+10 | 0.113119E+10 | 2340.69 | 24-JAN-15:10 | 2340.69 | 0.00 |
| February | 0.00 | 0.00 | 0.261301E+09 | 0.259788E+09 | 1317.47 | 23-FEB-14:00 | 1317.47 | 0.00 |
| March | 0.00 | 0.00 | 0.712670E+09 | 0.712232E+09 | 2485.12 | 18-MAR-15:20 | 2485.12 | 0.00 |
| April | 0.00 | 0.00 | 0.278427E+10 | 0.278427E+10 | 3045.50 | 10-APR-15:20 | 3045.50 | 0.00 |
| May | 0.00 | 0.00 | 0.342683E+10 | 0.342683E+10 | 3227.72 | 20-MAY-14:00 | 3227.72 | 0.00 |
| June | 0.00 | 0.00 | 0.484315E+10 | 0.483560E+10 | 3866.08 | 30-JUN-16:10 | 3866.08 | 0.00 |
| July | 0.00 | 0.00 | 0.528373E+10 | 0.484400E+10 | 3785.15 | 22-JUL-16:01 | 3785.15 | 0.00 |
| August | 0.00 | 0.00 | 0.507876E+10 | 0.466386E+10 | 3989.53 | 13-AUG-16:01 | 3775.45 | 0.00 |
| September | 0.00 | 0.00 | 0.453544E+10 | 0.413010E+10 | 3670.42 | 09-SEP-12:50 | 3453.81 | 0.00 |
| October | 0.00 | 0.00 | 0.246892E+10 | 0.240251E+10 | 3565.88 | 02-OCT-13:50 | 3477.09 | 0.00 |
| November | 0.00 | 0.00 | 0.103606E+10 | 0.101710E+10 | 2995.16 | 01-NOV-15:10 | 2985.41 | 0.00 |
| December | 0.00 | 0.00 | 0.623363E+09 | 0.623360E+09 | 2276.01 | 25-DEC-15:10 | 2276.01 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.321874E+11 | 0.308308E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.261301E+09 | 0.259788E+09 | 1317.47 | 1317.47 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.528373E+10 | 0.484400E+10 | 3989.53 | 3866.08 | 0.00 |
Report: FanReportMonthly
For: SPLIT GSW SUPPLY FAN
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 80838239.64 | 0.60 | 172.83 | 31-JAN-16:30 | 1.13 |
| February | 5725791.28 | 0.13 | 83.14 | 01-FEB-15:30 | 1.16 |
| March | 29553144.17 | 0.31 | 138.65 | 18-MAR-16:30 | 1.14 |
| April | 0.202256E+09 | 1.01 | 227.97 | 14-APR-17:25 | 1.11 |
| May | 0.256906E+09 | 1.12 | 230.88 | 31-MAY-17:30 | 1.11 |
| June | 0.384274E+09 | 1.13 | 307.55 | 16-JUN-17:01 | 1.08 |
| July | 0.422029E+09 | 1.12 | 295.63 | 22-JUL-17:40 | 1.07 |
| August | 0.422794E+09 | 1.12 | 321.00 | 25-AUG-17:00 | 1.07 |
| September | 0.399363E+09 | 1.12 | 289.38 | 08-SEP-16:10 | 1.07 |
| October | 0.250368E+09 | 1.04 | 265.50 | 06-OCT-16:10 | 1.09 |
| November | 0.123657E+09 | 0.85 | 210.87 | 01-NOV-16:10 | 1.10 |
| December | 54810231.66 | 0.46 | 174.29 | 25-DEC-16:10 | 1.13 |
| Annual Sum or Average | 0.263257E+10 | 0.84 | |||
| Minimum of Months | 5725791.28 | 0.13 | 83.14 | 1.07 | |
| Maximum of Months | 0.422794E+09 | 1.13 | 321.00 | 1.16 |
Report: FanReportMonthly
For: G SW APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.70 | 20.01 | 01-JAN-00:10 | 0.70 |
| February | 48400714.57 | 0.69 | 20.01 | 01-FEB-00:10 | 0.70 |
| March | 53586505.42 | 0.70 | 20.01 | 01-MAR-00:10 | 0.69 |
| April | 51857908.47 | 0.70 | 20.01 | 01-APR-00:10 | 0.70 |
| May | 53586505.42 | 0.70 | 20.01 | 01-MAY-00:10 | 0.70 |
| June | 51857908.47 | 0.70 | 20.01 | 01-JUN-00:10 | 0.70 |
| July | 53586505.42 | 0.69 | 20.01 | 01-JUL-00:10 | 0.69 |
| August | 53586505.42 | 0.69 | 20.01 | 01-AUG-00:10 | 0.69 |
| September | 51857908.47 | 0.69 | 20.01 | 01-SEP-00:10 | 0.69 |
| October | 53586505.42 | 0.69 | 20.01 | 01-OCT-00:10 | 0.69 |
| November | 51857908.47 | 0.69 | 20.01 | 01-NOV-00:10 | 0.69 |
| December | 53586505.42 | 0.70 | 20.01 | 01-DEC-00:10 | 0.70 |
| Annual Sum or Average | 0.630938E+09 | 0.69 | |||
| Minimum of Months | 48400714.57 | 0.69 | 20.01 | 0.69 | |
| Maximum of Months | 53586505.42 | 0.70 | 20.01 | 0.70 |
Report: FanReportMonthly
For: G SW APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.70 | 20.01 | 01-JAN-00:10 | 0.70 |
| February | 48400714.57 | 0.69 | 20.01 | 01-FEB-00:10 | 0.70 |
| March | 53586505.42 | 0.69 | 20.01 | 01-MAR-00:10 | 0.69 |
| April | 51857908.47 | 0.70 | 20.01 | 01-APR-00:10 | 0.70 |
| May | 53586505.42 | 0.70 | 20.01 | 01-MAY-00:10 | 0.70 |
| June | 51857908.47 | 0.70 | 20.01 | 01-JUN-00:10 | 0.70 |
| July | 53586505.42 | 0.69 | 20.01 | 01-JUL-00:10 | 0.69 |
| August | 53586505.42 | 0.69 | 20.01 | 01-AUG-00:10 | 0.69 |
| September | 51857908.47 | 0.69 | 20.01 | 01-SEP-00:10 | 0.69 |
| October | 53586505.42 | 0.69 | 20.01 | 01-OCT-00:10 | 0.69 |
| November | 51857908.47 | 0.69 | 20.01 | 01-NOV-00:10 | 0.70 |
| December | 53586505.42 | 0.70 | 20.01 | 01-DEC-00:10 | 0.70 |
| Annual Sum or Average | 0.630938E+09 | 0.69 | |||
| Minimum of Months | 48400714.57 | 0.69 | 20.01 | 0.69 | |
| Maximum of Months | 53586505.42 | 0.70 | 20.01 | 0.70 |
Report: FanReportMonthly
For: SPLIT GNW SUPPLY FAN
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 11569710.55 | 0.21 | 77.64 | 31-JAN-17:02 | 1.17 |
| February | 7461889.37 | 0.29 | 28.21 | 09-FEB-03:00 | 1.01 |
| March | 19072057.34 | 0.34 | 85.96 | 18-MAR-17:00 | 1.16 |
| April | 0.158415E+09 | 0.94 | 207.72 | 14-APR-17:25 | 1.11 |
| May | 0.247470E+09 | 1.13 | 234.17 | 31-MAY-17:30 | 1.11 |
| June | 0.392275E+09 | 1.13 | 311.70 | 16-JUN-17:01 | 1.07 |
| July | 0.420356E+09 | 1.12 | 292.26 | 22-JUL-18:00 | 1.07 |
| August | 0.400510E+09 | 1.12 | 304.51 | 25-AUG-17:00 | 1.07 |
| September | 0.356633E+09 | 1.13 | 260.49 | 08-SEP-17:10 | 1.08 |
| October | 0.169549E+09 | 0.92 | 218.35 | 06-OCT-16:10 | 1.11 |
| November | 40651304.95 | 0.51 | 136.38 | 01-NOV-16:02 | 1.13 |
| December | 11494327.14 | 0.27 | 59.83 | 25-DEC-16:10 | 1.17 |
| Annual Sum or Average | 0.223546E+10 | 0.76 | |||
| Minimum of Months | 7461889.37 | 0.21 | 28.21 | 1.01 | |
| Maximum of Months | 0.420356E+09 | 1.13 | 311.70 | 1.17 |
Report: FanReportMonthly
For: G NW APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.70 | 20.01 | 01-JAN-00:10 | 0.70 |
| February | 48400714.57 | 0.69 | 20.01 | 01-FEB-00:10 | 0.70 |
| March | 53586505.42 | 0.70 | 20.01 | 01-MAR-00:10 | 0.69 |
| April | 51857908.47 | 0.70 | 20.01 | 01-APR-00:10 | 0.70 |
| May | 53586505.42 | 0.70 | 20.01 | 01-MAY-00:10 | 0.70 |
| June | 51857908.47 | 0.70 | 20.01 | 01-JUN-00:10 | 0.70 |
| July | 53586505.42 | 0.69 | 20.01 | 01-JUL-00:10 | 0.69 |
| August | 53586505.42 | 0.69 | 20.01 | 01-AUG-00:10 | 0.69 |
| September | 51857908.47 | 0.69 | 20.01 | 01-SEP-00:10 | 0.69 |
| October | 53586505.42 | 0.69 | 20.01 | 01-OCT-00:10 | 0.69 |
| November | 51857908.47 | 0.69 | 20.01 | 01-NOV-00:10 | 0.69 |
| December | 53586505.42 | 0.70 | 20.01 | 01-DEC-00:10 | 0.70 |
| Annual Sum or Average | 0.630938E+09 | 0.69 | |||
| Minimum of Months | 48400714.57 | 0.69 | 20.01 | 0.69 | |
| Maximum of Months | 53586505.42 | 0.70 | 20.01 | 0.70 |
Report: FanReportMonthly
For: G NW APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.70 | 20.01 | 01-JAN-00:10 | 0.70 |
| February | 48400714.57 | 0.69 | 20.01 | 01-FEB-00:10 | 0.70 |
| March | 53586505.42 | 0.69 | 20.01 | 01-MAR-00:10 | 0.69 |
| April | 51857908.47 | 0.70 | 20.01 | 01-APR-00:10 | 0.70 |
| May | 53586505.42 | 0.70 | 20.01 | 01-MAY-00:10 | 0.70 |
| June | 51857908.47 | 0.70 | 20.01 | 01-JUN-00:10 | 0.70 |
| July | 53586505.42 | 0.69 | 20.01 | 01-JUL-00:10 | 0.69 |
| August | 53586505.42 | 0.69 | 20.01 | 01-AUG-00:10 | 0.69 |
| September | 51857908.47 | 0.69 | 20.01 | 01-SEP-00:10 | 0.69 |
| October | 53586505.42 | 0.69 | 20.01 | 01-OCT-00:10 | 0.69 |
| November | 51857908.47 | 0.69 | 20.01 | 01-NOV-00:10 | 0.70 |
| December | 53586505.42 | 0.70 | 20.01 | 01-DEC-00:10 | 0.70 |
| Annual Sum or Average | 0.630938E+09 | 0.69 | |||
| Minimum of Months | 48400714.57 | 0.69 | 20.01 | 0.69 | |
| Maximum of Months | 53586505.42 | 0.70 | 20.01 | 0.70 |
Report: FanReportMonthly
For: SPLIT OFFICE SUPPLY FAN
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.135926E+10 | 1.01 | 507.49 | 01-JAN-00:10 | 1.01 |
| February | 0.122772E+10 | 1.01 | 507.49 | 01-FEB-00:10 | 1.02 |
| March | 0.135926E+10 | 1.01 | 507.49 | 01-MAR-00:10 | 1.01 |
| April | 0.131541E+10 | 1.01 | 507.49 | 01-APR-00:10 | 1.01 |
| May | 0.135926E+10 | 1.01 | 507.49 | 01-MAY-00:10 | 1.02 |
| June | 0.131541E+10 | 1.01 | 507.49 | 01-JUN-00:10 | 1.02 |
| July | 0.135926E+10 | 1.00 | 507.49 | 01-JUL-00:10 | 1.01 |
| August | 0.135926E+10 | 1.00 | 507.49 | 01-AUG-00:10 | 1.00 |
| September | 0.131541E+10 | 1.00 | 507.49 | 01-SEP-00:10 | 1.00 |
| October | 0.135926E+10 | 1.01 | 507.49 | 01-OCT-00:10 | 1.01 |
| November | 0.131541E+10 | 1.01 | 507.49 | 01-NOV-00:10 | 1.01 |
| December | 0.135926E+10 | 1.01 | 507.49 | 01-DEC-00:10 | 1.01 |
| Annual Sum or Average | 0.160042E+11 | 1.01 | |||
| Minimum of Months | 0.122772E+10 | 1.00 | 507.49 | 1.00 | |
| Maximum of Months | 0.135926E+10 | 1.01 | 507.49 | 1.02 |
Report: FanReportMonthly
For: SPLIT GNE SUPPLY FAN
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 9981619.79 | 0.22 | 58.79 | 31-JAN-17:02 | 1.17 |
| February | 6482861.61 | 0.25 | 28.53 | 05-FEB-04:00 | 1.01 |
| March | 18605959.25 | 0.34 | 71.66 | 20-MAR-17:00 | 1.16 |
| April | 0.160822E+09 | 0.97 | 172.03 | 14-APR-17:40 | 1.12 |
| May | 0.251860E+09 | 1.12 | 202.64 | 31-MAY-18:00 | 1.11 |
| June | 0.395131E+09 | 1.13 | 278.52 | 16-JUN-17:00 | 1.08 |
| July | 0.429643E+09 | 1.12 | 261.25 | 22-JUL-18:00 | 1.08 |
| August | 0.409169E+09 | 1.12 | 272.41 | 25-AUG-17:00 | 1.08 |
| September | 0.360936E+09 | 1.12 | 235.79 | 08-SEP-16:01 | 1.09 |
| October | 0.172860E+09 | 0.95 | 198.52 | 01-OCT-14:00 | 1.10 |
| November | 37512196.55 | 0.52 | 107.75 | 01-NOV-16:02 | 1.14 |
| December | 10241786.86 | 0.26 | 41.23 | 07-DEC-05:00 | 1.02 |
| Annual Sum or Average | 0.226325E+10 | 0.76 | |||
| Minimum of Months | 6482861.61 | 0.22 | 28.53 | 1.01 | |
| Maximum of Months | 0.429643E+09 | 1.13 | 278.52 | 1.17 |
Report: FanReportMonthly
For: G NE APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.70 | 20.01 | 01-JAN-00:10 | 0.70 |
| February | 48400714.57 | 0.69 | 20.01 | 01-FEB-00:10 | 0.70 |
| March | 53586505.42 | 0.70 | 20.01 | 01-MAR-00:10 | 0.69 |
| April | 51857908.47 | 0.70 | 20.01 | 01-APR-00:10 | 0.70 |
| May | 53586505.42 | 0.70 | 20.01 | 01-MAY-00:10 | 0.70 |
| June | 51857908.47 | 0.70 | 20.01 | 01-JUN-00:10 | 0.70 |
| July | 53586505.42 | 0.69 | 20.01 | 01-JUL-00:10 | 0.69 |
| August | 53586505.42 | 0.69 | 20.01 | 01-AUG-00:10 | 0.69 |
| September | 51857908.47 | 0.69 | 20.01 | 01-SEP-00:10 | 0.69 |
| October | 53586505.42 | 0.69 | 20.01 | 01-OCT-00:10 | 0.69 |
| November | 51857908.47 | 0.69 | 20.01 | 01-NOV-00:10 | 0.69 |
| December | 53586505.42 | 0.70 | 20.01 | 01-DEC-00:10 | 0.70 |
| Annual Sum or Average | 0.630938E+09 | 0.69 | |||
| Minimum of Months | 48400714.57 | 0.69 | 20.01 | 0.69 | |
| Maximum of Months | 53586505.42 | 0.70 | 20.01 | 0.70 |
Report: FanReportMonthly
For: G NE APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.70 | 20.01 | 01-JAN-00:10 | 0.70 |
| February | 48400714.57 | 0.69 | 20.01 | 01-FEB-00:10 | 0.70 |
| March | 53586505.42 | 0.69 | 20.01 | 01-MAR-00:10 | 0.69 |
| April | 51857908.47 | 0.70 | 20.01 | 01-APR-00:10 | 0.70 |
| May | 53586505.42 | 0.70 | 20.01 | 01-MAY-00:10 | 0.70 |
| June | 51857908.47 | 0.70 | 20.01 | 01-JUN-00:10 | 0.70 |
| July | 53586505.42 | 0.69 | 20.01 | 01-JUL-00:10 | 0.69 |
| August | 53586505.42 | 0.69 | 20.01 | 01-AUG-00:10 | 0.69 |
| September | 51857908.47 | 0.69 | 20.01 | 01-SEP-00:10 | 0.69 |
| October | 53586505.42 | 0.69 | 20.01 | 01-OCT-00:10 | 0.69 |
| November | 51857908.47 | 0.69 | 20.01 | 01-NOV-00:10 | 0.70 |
| December | 53586505.42 | 0.70 | 20.01 | 01-DEC-00:10 | 0.70 |
| Annual Sum or Average | 0.630938E+09 | 0.69 | |||
| Minimum of Months | 48400714.57 | 0.69 | 20.01 | 0.69 | |
| Maximum of Months | 53586505.42 | 0.70 | 20.01 | 0.70 |
Report: FanReportMonthly
For: SPLIT GN1 SUPPLY FAN
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 8889548.24 | 0.21 | 56.61 | 31-JAN-17:02 | 1.17 |
| February | 902783.98 | 0.07 | 13.31 | 09-FEB-05:00 | 1.01 |
| March | 13099328.32 | 0.22 | 67.76 | 20-MAR-17:00 | 1.16 |
| April | 0.133178E+09 | 1.01 | 144.59 | 14-APR-17:40 | 1.13 |
| May | 0.210940E+09 | 1.15 | 170.75 | 31-MAY-18:00 | 1.12 |
| June | 0.322013E+09 | 1.13 | 227.56 | 16-JUN-17:01 | 1.09 |
| July | 0.351287E+09 | 1.12 | 211.12 | 05-JUL-18:00 | 1.09 |
| August | 0.333757E+09 | 1.12 | 220.00 | 25-AUG-17:00 | 1.09 |
| September | 0.298122E+09 | 1.13 | 188.47 | 08-SEP-17:10 | 1.09 |
| October | 0.145237E+09 | 0.97 | 164.48 | 03-OCT-17:20 | 1.11 |
| November | 37339567.54 | 0.58 | 92.56 | 01-NOV-16:03 | 1.14 |
| December | 4904088.92 | 0.17 | 37.34 | 25-DEC-16:10 | 1.17 |
| Annual Sum or Average | 0.185967E+10 | 0.74 | |||
| Minimum of Months | 902783.98 | 0.07 | 13.31 | 1.01 | |
| Maximum of Months | 0.351287E+09 | 1.15 | 227.56 | 1.17 |
Report: FanReportMonthly
For: G N1 APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.70 | 20.01 | 01-JAN-00:10 | 0.70 |
| February | 48400714.57 | 0.69 | 20.01 | 01-FEB-00:10 | 0.70 |
| March | 53586505.42 | 0.70 | 20.01 | 01-MAR-00:10 | 0.69 |
| April | 51857908.47 | 0.70 | 20.01 | 01-APR-00:10 | 0.70 |
| May | 53586505.42 | 0.70 | 20.01 | 01-MAY-00:10 | 0.70 |
| June | 51857908.47 | 0.70 | 20.01 | 01-JUN-00:10 | 0.70 |
| July | 53586505.42 | 0.69 | 20.01 | 01-JUL-00:10 | 0.69 |
| August | 53586505.42 | 0.69 | 20.01 | 01-AUG-00:10 | 0.69 |
| September | 51857908.47 | 0.69 | 20.01 | 01-SEP-00:10 | 0.69 |
| October | 53586505.42 | 0.69 | 20.01 | 01-OCT-00:10 | 0.69 |
| November | 51857908.47 | 0.69 | 20.01 | 01-NOV-00:10 | 0.69 |
| December | 53586505.42 | 0.70 | 20.01 | 01-DEC-00:10 | 0.70 |
| Annual Sum or Average | 0.630938E+09 | 0.69 | |||
| Minimum of Months | 48400714.57 | 0.69 | 20.01 | 0.69 | |
| Maximum of Months | 53586505.42 | 0.70 | 20.01 | 0.70 |
Report: FanReportMonthly
For: G N1 APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.70 | 20.01 | 01-JAN-00:10 | 0.70 |
| February | 48400714.57 | 0.69 | 20.01 | 01-FEB-00:10 | 0.70 |
| March | 53586505.42 | 0.69 | 20.01 | 01-MAR-00:10 | 0.69 |
| April | 51857908.47 | 0.70 | 20.01 | 01-APR-00:10 | 0.70 |
| May | 53586505.42 | 0.70 | 20.01 | 01-MAY-00:10 | 0.70 |
| June | 51857908.47 | 0.70 | 20.01 | 01-JUN-00:10 | 0.70 |
| July | 53586505.42 | 0.69 | 20.01 | 01-JUL-00:10 | 0.69 |
| August | 53586505.42 | 0.69 | 20.01 | 01-AUG-00:10 | 0.69 |
| September | 51857908.47 | 0.69 | 20.01 | 01-SEP-00:10 | 0.69 |
| October | 53586505.42 | 0.69 | 20.01 | 01-OCT-00:10 | 0.69 |
| November | 51857908.47 | 0.69 | 20.01 | 01-NOV-00:10 | 0.70 |
| December | 53586505.42 | 0.70 | 20.01 | 01-DEC-00:10 | 0.70 |
| Annual Sum or Average | 0.630938E+09 | 0.69 | |||
| Minimum of Months | 48400714.57 | 0.69 | 20.01 | 0.69 | |
| Maximum of Months | 53586505.42 | 0.70 | 20.01 | 0.70 |
Report: FanReportMonthly
For: SPLIT GN2 SUPPLY FAN
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 8974510.34 | 0.21 | 56.59 | 31-JAN-17:02 | 1.17 |
| February | 869768.09 | 0.07 | 13.07 | 09-FEB-05:00 | 1.01 |
| March | 13180124.36 | 0.23 | 67.84 | 20-MAR-17:00 | 1.16 |
| April | 0.133489E+09 | 1.01 | 144.09 | 14-APR-17:40 | 1.13 |
| May | 0.211227E+09 | 1.15 | 170.27 | 31-MAY-18:00 | 1.12 |
| June | 0.322213E+09 | 1.13 | 227.15 | 16-JUN-17:01 | 1.09 |
| July | 0.351712E+09 | 1.12 | 210.64 | 05-JUL-18:00 | 1.09 |
| August | 0.334173E+09 | 1.12 | 219.62 | 25-AUG-17:00 | 1.09 |
| September | 0.298348E+09 | 1.13 | 188.11 | 08-SEP-17:10 | 1.10 |
| October | 0.145557E+09 | 0.97 | 164.44 | 03-OCT-17:20 | 1.11 |
| November | 37335433.24 | 0.58 | 92.21 | 01-NOV-16:03 | 1.14 |
| December | 4913693.45 | 0.17 | 37.21 | 25-DEC-16:10 | 1.17 |
| Annual Sum or Average | 0.186199E+10 | 0.74 | |||
| Minimum of Months | 869768.09 | 0.07 | 13.07 | 1.01 | |
| Maximum of Months | 0.351712E+09 | 1.15 | 227.15 | 1.17 |
Report: FanReportMonthly
For: G N2 APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.70 | 20.01 | 01-JAN-00:10 | 0.70 |
| February | 48400714.57 | 0.69 | 20.01 | 01-FEB-00:10 | 0.70 |
| March | 53586505.42 | 0.70 | 20.01 | 01-MAR-00:10 | 0.69 |
| April | 51857908.47 | 0.70 | 20.01 | 01-APR-00:10 | 0.70 |
| May | 53586505.42 | 0.70 | 20.01 | 01-MAY-00:10 | 0.70 |
| June | 51857908.47 | 0.70 | 20.01 | 01-JUN-00:10 | 0.70 |
| July | 53586505.42 | 0.69 | 20.01 | 01-JUL-00:10 | 0.69 |
| August | 53586505.42 | 0.69 | 20.01 | 01-AUG-00:10 | 0.69 |
| September | 51857908.47 | 0.69 | 20.01 | 01-SEP-00:10 | 0.69 |
| October | 53586505.42 | 0.69 | 20.01 | 01-OCT-00:10 | 0.69 |
| November | 51857908.47 | 0.69 | 20.01 | 01-NOV-00:10 | 0.69 |
| December | 53586505.42 | 0.70 | 20.01 | 01-DEC-00:10 | 0.70 |
| Annual Sum or Average | 0.630938E+09 | 0.69 | |||
| Minimum of Months | 48400714.57 | 0.69 | 20.01 | 0.69 | |
| Maximum of Months | 53586505.42 | 0.70 | 20.01 | 0.70 |
Report: FanReportMonthly
For: G N2 APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.70 | 20.01 | 01-JAN-00:10 | 0.70 |
| February | 48400714.57 | 0.69 | 20.01 | 01-FEB-00:10 | 0.70 |
| March | 53586505.42 | 0.69 | 20.01 | 01-MAR-00:10 | 0.69 |
| April | 51857908.47 | 0.70 | 20.01 | 01-APR-00:10 | 0.70 |
| May | 53586505.42 | 0.70 | 20.01 | 01-MAY-00:10 | 0.70 |
| June | 51857908.47 | 0.70 | 20.01 | 01-JUN-00:10 | 0.70 |
| July | 53586505.42 | 0.69 | 20.01 | 01-JUL-00:10 | 0.69 |
| August | 53586505.42 | 0.69 | 20.01 | 01-AUG-00:10 | 0.69 |
| September | 51857908.47 | 0.69 | 20.01 | 01-SEP-00:10 | 0.69 |
| October | 53586505.42 | 0.69 | 20.01 | 01-OCT-00:10 | 0.69 |
| November | 51857908.47 | 0.69 | 20.01 | 01-NOV-00:10 | 0.70 |
| December | 53586505.42 | 0.70 | 20.01 | 01-DEC-00:10 | 0.70 |
| Annual Sum or Average | 0.630938E+09 | 0.69 | |||
| Minimum of Months | 48400714.57 | 0.69 | 20.01 | 0.69 | |
| Maximum of Months | 53586505.42 | 0.70 | 20.01 | 0.70 |
Report: FanReportMonthly
For: SPLIT GS1 SUPPLY FAN
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 96092831.69 | 0.75 | 149.33 | 31-JAN-16:10 | 1.13 |
| February | 11369556.76 | 0.24 | 82.93 | 01-FEB-15:30 | 1.15 |
| March | 32961469.28 | 0.39 | 115.65 | 18-MAR-16:10 | 1.14 |
| April | 0.180353E+09 | 1.09 | 165.57 | 14-APR-16:05 | 1.12 |
| May | 0.221696E+09 | 1.15 | 173.30 | 20-MAY-14:00 | 1.12 |
| June | 0.315029E+09 | 1.13 | 223.51 | 16-JUN-17:01 | 1.09 |
| July | 0.354255E+09 | 1.12 | 215.99 | 22-JUL-16:10 | 1.09 |
| August | 0.357644E+09 | 1.12 | 236.82 | 25-AUG-17:00 | 1.08 |
| September | 0.342791E+09 | 1.12 | 222.69 | 28-SEP-15:10 | 1.09 |
| October | 0.230874E+09 | 1.11 | 209.19 | 06-OCT-15:10 | 1.10 |
| November | 0.129956E+09 | 0.98 | 167.45 | 01-NOV-15:10 | 1.11 |
| December | 69809831.10 | 0.64 | 148.70 | 25-DEC-16:10 | 1.12 |
| Annual Sum or Average | 0.234283E+10 | 0.91 | |||
| Minimum of Months | 11369556.76 | 0.24 | 82.93 | 1.08 | |
| Maximum of Months | 0.357644E+09 | 1.15 | 236.82 | 1.15 |
Report: FanReportMonthly
For: G S1 APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.70 | 20.01 | 01-JAN-00:10 | 0.70 |
| February | 48400714.57 | 0.69 | 20.01 | 01-FEB-00:10 | 0.70 |
| March | 53586505.42 | 0.70 | 20.01 | 01-MAR-00:10 | 0.69 |
| April | 51857908.47 | 0.70 | 20.01 | 01-APR-00:10 | 0.70 |
| May | 53586505.42 | 0.70 | 20.01 | 01-MAY-00:10 | 0.70 |
| June | 51857908.47 | 0.70 | 20.01 | 01-JUN-00:10 | 0.70 |
| July | 53586505.42 | 0.69 | 20.01 | 01-JUL-00:10 | 0.69 |
| August | 53586505.42 | 0.69 | 20.01 | 01-AUG-00:10 | 0.69 |
| September | 51857908.47 | 0.69 | 20.01 | 01-SEP-00:10 | 0.69 |
| October | 53586505.42 | 0.69 | 20.01 | 01-OCT-00:10 | 0.69 |
| November | 51857908.47 | 0.69 | 20.01 | 01-NOV-00:10 | 0.69 |
| December | 53586505.42 | 0.70 | 20.01 | 01-DEC-00:10 | 0.70 |
| Annual Sum or Average | 0.630938E+09 | 0.69 | |||
| Minimum of Months | 48400714.57 | 0.69 | 20.01 | 0.69 | |
| Maximum of Months | 53586505.42 | 0.70 | 20.01 | 0.70 |
Report: FanReportMonthly
For: G S1 APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.70 | 20.01 | 01-JAN-00:10 | 0.70 |
| February | 48400714.57 | 0.69 | 20.01 | 01-FEB-00:10 | 0.70 |
| March | 53586505.42 | 0.69 | 20.01 | 01-MAR-00:10 | 0.69 |
| April | 51857908.47 | 0.70 | 20.01 | 01-APR-00:10 | 0.70 |
| May | 53586505.42 | 0.70 | 20.01 | 01-MAY-00:10 | 0.70 |
| June | 51857908.47 | 0.70 | 20.01 | 01-JUN-00:10 | 0.70 |
| July | 53586505.42 | 0.69 | 20.01 | 01-JUL-00:10 | 0.69 |
| August | 53586505.42 | 0.69 | 20.01 | 01-AUG-00:10 | 0.69 |
| September | 51857908.47 | 0.69 | 20.01 | 01-SEP-00:10 | 0.69 |
| October | 53586505.42 | 0.69 | 20.01 | 01-OCT-00:10 | 0.69 |
| November | 51857908.47 | 0.69 | 20.01 | 01-NOV-00:10 | 0.70 |
| December | 53586505.42 | 0.70 | 20.01 | 01-DEC-00:10 | 0.70 |
| Annual Sum or Average | 0.630938E+09 | 0.69 | |||
| Minimum of Months | 48400714.57 | 0.69 | 20.01 | 0.69 | |
| Maximum of Months | 53586505.42 | 0.70 | 20.01 | 0.70 |
Report: FanReportMonthly
For: SPLIT GS2 SUPPLY FAN
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.102898E+09 | 0.78 | 154.06 | 31-JAN-16:10 | 1.13 |
| February | 13540111.08 | 0.27 | 87.47 | 01-FEB-15:30 | 1.15 |
| March | 37459328.32 | 0.44 | 122.56 | 18-MAR-16:05 | 1.13 |
| April | 0.198067E+09 | 1.11 | 173.53 | 30-APR-16:02 | 1.12 |
| May | 0.244131E+09 | 1.15 | 184.54 | 20-MAY-14:00 | 1.11 |
| June | 0.341411E+09 | 1.13 | 231.37 | 16-JUN-17:01 | 1.09 |
| July | 0.383531E+09 | 1.12 | 228.40 | 22-JUL-16:10 | 1.08 |
| August | 0.385479E+09 | 1.12 | 248.58 | 26-AUG-16:10 | 1.08 |
| September | 0.370156E+09 | 1.12 | 230.11 | 28-SEP-15:10 | 1.09 |
| October | 0.251882E+09 | 1.12 | 216.25 | 06-OCT-15:10 | 1.09 |
| November | 0.140435E+09 | 1.01 | 172.07 | 01-NOV-15:10 | 1.11 |
| December | 75944246.92 | 0.68 | 156.05 | 25-DEC-16:10 | 1.12 |
| Annual Sum or Average | 0.254493E+10 | 0.92 | |||
| Minimum of Months | 13540111.08 | 0.27 | 87.47 | 1.08 | |
| Maximum of Months | 0.385479E+09 | 1.15 | 248.58 | 1.15 |
Report: FanReportMonthly
For: G S2 APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.70 | 20.01 | 01-JAN-00:10 | 0.70 |
| February | 48400714.57 | 0.69 | 20.01 | 01-FEB-00:10 | 0.70 |
| March | 53586505.42 | 0.70 | 20.01 | 01-MAR-00:10 | 0.69 |
| April | 51857908.47 | 0.70 | 20.01 | 01-APR-00:10 | 0.70 |
| May | 53586505.42 | 0.70 | 20.01 | 01-MAY-00:10 | 0.70 |
| June | 51857908.47 | 0.70 | 20.01 | 01-JUN-00:10 | 0.70 |
| July | 53586505.42 | 0.69 | 20.01 | 01-JUL-00:10 | 0.69 |
| August | 53586505.42 | 0.69 | 20.01 | 01-AUG-00:10 | 0.69 |
| September | 51857908.47 | 0.69 | 20.01 | 01-SEP-00:10 | 0.69 |
| October | 53586505.42 | 0.69 | 20.01 | 01-OCT-00:10 | 0.69 |
| November | 51857908.47 | 0.69 | 20.01 | 01-NOV-00:10 | 0.69 |
| December | 53586505.42 | 0.70 | 20.01 | 01-DEC-00:10 | 0.70 |
| Annual Sum or Average | 0.630938E+09 | 0.69 | |||
| Minimum of Months | 48400714.57 | 0.69 | 20.01 | 0.69 | |
| Maximum of Months | 53586505.42 | 0.70 | 20.01 | 0.70 |
Report: FanReportMonthly
For: G S2 APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.70 | 20.01 | 01-JAN-00:10 | 0.70 |
| February | 48400714.57 | 0.69 | 20.01 | 01-FEB-00:10 | 0.70 |
| March | 53586505.42 | 0.69 | 20.01 | 01-MAR-00:10 | 0.69 |
| April | 51857908.47 | 0.70 | 20.01 | 01-APR-00:10 | 0.70 |
| May | 53586505.42 | 0.70 | 20.01 | 01-MAY-00:10 | 0.70 |
| June | 51857908.47 | 0.70 | 20.01 | 01-JUN-00:10 | 0.70 |
| July | 53586505.42 | 0.69 | 20.01 | 01-JUL-00:10 | 0.69 |
| August | 53586505.42 | 0.69 | 20.01 | 01-AUG-00:10 | 0.69 |
| September | 51857908.47 | 0.69 | 20.01 | 01-SEP-00:10 | 0.69 |
| October | 53586505.42 | 0.69 | 20.01 | 01-OCT-00:10 | 0.69 |
| November | 51857908.47 | 0.69 | 20.01 | 01-NOV-00:10 | 0.70 |
| December | 53586505.42 | 0.70 | 20.01 | 01-DEC-00:10 | 0.70 |
| Annual Sum or Average | 0.630938E+09 | 0.69 | |||
| Minimum of Months | 48400714.57 | 0.69 | 20.01 | 0.69 | |
| Maximum of Months | 53586505.42 | 0.70 | 20.01 | 0.70 |
Report: FanReportMonthly
For: SPLIT MSW SUPPLY FAN
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.228623E+09 | 0.64 | 432.21 | 31-JAN-16:30 | 1.12 |
| February | 57423300.34 | 0.36 | 253.31 | 22-FEB-16:20 | 1.15 |
| March | 0.142274E+09 | 0.54 | 414.91 | 18-MAR-16:30 | 1.12 |
| April | 0.535505E+09 | 1.07 | 557.23 | 14-APR-17:25 | 1.10 |
| May | 0.660906E+09 | 1.15 | 575.73 | 15-MAY-17:02 | 1.10 |
| June | 0.891461E+09 | 1.13 | 723.67 | 16-JUN-17:01 | 1.07 |
| July | 0.886229E+09 | 1.13 | 664.60 | 22-JUL-17:50 | 1.07 |
| August | 0.851185E+09 | 1.13 | 699.42 | 25-AUG-17:00 | 1.08 |
| September | 0.756536E+09 | 1.13 | 612.18 | 08-SEP-16:10 | 1.08 |
| October | 0.462027E+09 | 0.95 | 570.46 | 10-OCT-15:30 | 1.09 |
| November | 0.221048E+09 | 0.71 | 470.79 | 01-NOV-16:10 | 1.11 |
| December | 0.115164E+09 | 0.44 | 404.54 | 25-DEC-16:10 | 1.12 |
| Annual Sum or Average | 0.580838E+10 | 0.87 | |||
| Minimum of Months | 57423300.34 | 0.36 | 253.31 | 1.07 | |
| Maximum of Months | 0.891461E+09 | 1.15 | 723.67 | 1.15 |
Report: FanReportMonthly
For: M SW APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.107173E+09 | 0.70 | 40.01 | 01-JAN-00:10 | 0.70 |
| February | 96801429.15 | 0.69 | 40.01 | 01-FEB-00:10 | 0.70 |
| March | 0.107173E+09 | 0.70 | 40.01 | 01-MAR-00:10 | 0.69 |
| April | 0.103716E+09 | 0.70 | 40.01 | 01-APR-00:10 | 0.70 |
| May | 0.107173E+09 | 0.70 | 40.01 | 01-MAY-00:10 | 0.70 |
| June | 0.103716E+09 | 0.70 | 40.01 | 01-JUN-00:10 | 0.70 |
| July | 0.107173E+09 | 0.69 | 40.01 | 01-JUL-00:10 | 0.69 |
| August | 0.107173E+09 | 0.69 | 40.01 | 01-AUG-00:10 | 0.69 |
| September | 0.103716E+09 | 0.69 | 40.01 | 01-SEP-00:10 | 0.69 |
| October | 0.107173E+09 | 0.69 | 40.01 | 01-OCT-00:10 | 0.69 |
| November | 0.103716E+09 | 0.69 | 40.01 | 01-NOV-00:10 | 0.69 |
| December | 0.107173E+09 | 0.70 | 40.01 | 01-DEC-00:10 | 0.70 |
| Annual Sum or Average | 0.126188E+10 | 0.69 | |||
| Minimum of Months | 96801429.15 | 0.69 | 40.01 | 0.69 | |
| Maximum of Months | 0.107173E+09 | 0.70 | 40.01 | 0.70 |
Report: FanReportMonthly
For: M SW APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.107173E+09 | 0.70 | 40.01 | 01-JAN-00:10 | 0.70 |
| February | 96801429.15 | 0.69 | 40.01 | 01-FEB-00:10 | 0.70 |
| March | 0.107173E+09 | 0.69 | 40.01 | 01-MAR-00:10 | 0.69 |
| April | 0.103716E+09 | 0.70 | 40.01 | 01-APR-00:10 | 0.70 |
| May | 0.107173E+09 | 0.70 | 40.01 | 01-MAY-00:10 | 0.70 |
| June | 0.103716E+09 | 0.70 | 40.01 | 01-JUN-00:10 | 0.70 |
| July | 0.107173E+09 | 0.69 | 40.01 | 01-JUL-00:10 | 0.69 |
| August | 0.107173E+09 | 0.69 | 40.01 | 01-AUG-00:10 | 0.69 |
| September | 0.103716E+09 | 0.69 | 40.01 | 01-SEP-00:10 | 0.69 |
| October | 0.107173E+09 | 0.69 | 40.01 | 01-OCT-00:10 | 0.69 |
| November | 0.103716E+09 | 0.69 | 40.01 | 01-NOV-00:10 | 0.70 |
| December | 0.107173E+09 | 0.70 | 40.01 | 01-DEC-00:10 | 0.70 |
| Annual Sum or Average | 0.126188E+10 | 0.69 | |||
| Minimum of Months | 96801429.15 | 0.69 | 40.01 | 0.69 | |
| Maximum of Months | 0.107173E+09 | 0.70 | 40.01 | 0.70 |
Report: FanReportMonthly
For: SPLIT MNW SUPPLY FAN
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 38902221.85 | 0.28 | 208.60 | 31-JAN-17:04 | 1.16 |
| February | 3060197.84 | 0.07 | 88.24 | 22-FEB-16:30 | 1.17 |
| March | 71660531.44 | 0.33 | 293.69 | 18-MAR-17:00 | 1.14 |
| April | 0.440860E+09 | 1.04 | 513.61 | 14-APR-17:30 | 1.11 |
| May | 0.640507E+09 | 1.14 | 579.60 | 31-MAY-18:00 | 1.10 |
| June | 0.906180E+09 | 1.13 | 732.41 | 15-JUN-18:00 | 1.07 |
| July | 0.880118E+09 | 1.13 | 657.46 | 22-JUL-18:00 | 1.07 |
| August | 0.801819E+09 | 1.13 | 664.03 | 25-AUG-17:00 | 1.08 |
| September | 0.663842E+09 | 1.14 | 542.49 | 08-SEP-16:10 | 1.09 |
| October | 0.294734E+09 | 0.80 | 458.47 | 06-OCT-16:01 | 1.11 |
| November | 59190224.77 | 0.38 | 298.29 | 01-NOV-16:02 | 1.13 |
| December | 31849563.33 | 0.30 | 131.86 | 25-DEC-16:30 | 1.17 |
| Annual Sum or Average | 0.483272E+10 | 0.74 | |||
| Minimum of Months | 3060197.84 | 0.07 | 88.24 | 1.07 | |
| Maximum of Months | 0.906180E+09 | 1.14 | 732.41 | 1.17 |
Report: FanReportMonthly
For: M NW APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.107173E+09 | 0.70 | 40.01 | 01-JAN-00:10 | 0.70 |
| February | 96801429.15 | 0.69 | 40.01 | 01-FEB-00:10 | 0.70 |
| March | 0.107173E+09 | 0.70 | 40.01 | 01-MAR-00:10 | 0.69 |
| April | 0.103716E+09 | 0.70 | 40.01 | 01-APR-00:10 | 0.70 |
| May | 0.107173E+09 | 0.70 | 40.01 | 01-MAY-00:10 | 0.70 |
| June | 0.103716E+09 | 0.70 | 40.01 | 01-JUN-00:10 | 0.70 |
| July | 0.107173E+09 | 0.69 | 40.01 | 01-JUL-00:10 | 0.69 |
| August | 0.107173E+09 | 0.69 | 40.01 | 01-AUG-00:10 | 0.69 |
| September | 0.103716E+09 | 0.69 | 40.01 | 01-SEP-00:10 | 0.69 |
| October | 0.107173E+09 | 0.69 | 40.01 | 01-OCT-00:10 | 0.69 |
| November | 0.103716E+09 | 0.69 | 40.01 | 01-NOV-00:10 | 0.69 |
| December | 0.107173E+09 | 0.70 | 40.01 | 01-DEC-00:10 | 0.70 |
| Annual Sum or Average | 0.126188E+10 | 0.69 | |||
| Minimum of Months | 96801429.15 | 0.69 | 40.01 | 0.69 | |
| Maximum of Months | 0.107173E+09 | 0.70 | 40.01 | 0.70 |
Report: FanReportMonthly
For: M NW APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.107173E+09 | 0.70 | 40.01 | 01-JAN-00:10 | 0.70 |
| February | 96801429.15 | 0.69 | 40.01 | 01-FEB-00:10 | 0.70 |
| March | 0.107173E+09 | 0.69 | 40.01 | 01-MAR-00:10 | 0.69 |
| April | 0.103716E+09 | 0.70 | 40.01 | 01-APR-00:10 | 0.70 |
| May | 0.107173E+09 | 0.70 | 40.01 | 01-MAY-00:10 | 0.70 |
| June | 0.103716E+09 | 0.70 | 40.01 | 01-JUN-00:10 | 0.70 |
| July | 0.107173E+09 | 0.69 | 40.01 | 01-JUL-00:10 | 0.69 |
| August | 0.107173E+09 | 0.69 | 40.01 | 01-AUG-00:10 | 0.69 |
| September | 0.103716E+09 | 0.69 | 40.01 | 01-SEP-00:10 | 0.69 |
| October | 0.107173E+09 | 0.69 | 40.01 | 01-OCT-00:10 | 0.69 |
| November | 0.103716E+09 | 0.69 | 40.01 | 01-NOV-00:10 | 0.70 |
| December | 0.107173E+09 | 0.70 | 40.01 | 01-DEC-00:10 | 0.70 |
| Annual Sum or Average | 0.126188E+10 | 0.69 | |||
| Minimum of Months | 96801429.15 | 0.69 | 40.01 | 0.69 | |
| Maximum of Months | 0.107173E+09 | 0.70 | 40.01 | 0.70 |
Report: FanReportMonthly
For: SPLIT MSE SUPPLY FAN
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.224565E+09 | 0.66 | 368.40 | 31-JAN-16:10 | 1.13 |
| February | 63636353.41 | 0.41 | 206.71 | 23-FEB-14:00 | 1.15 |
| March | 0.145736E+09 | 0.56 | 349.09 | 18-MAR-15:20 | 1.13 |
| April | 0.541572E+09 | 1.08 | 479.52 | 30-APR-15:20 | 1.11 |
| May | 0.669879E+09 | 1.14 | 545.74 | 20-MAY-14:00 | 1.10 |
| June | 0.897054E+09 | 1.13 | 645.99 | 30-JUN-16:10 | 1.07 |
| July | 0.906447E+09 | 1.12 | 600.18 | 22-JUL-16:08 | 1.08 |
| August | 0.869616E+09 | 1.12 | 613.21 | 25-AUG-16:01 | 1.08 |
| September | 0.765636E+09 | 1.13 | 547.77 | 08-SEP-16:10 | 1.09 |
| October | 0.470175E+09 | 0.97 | 522.59 | 06-OCT-15:10 | 1.10 |
| November | 0.214925E+09 | 0.73 | 396.54 | 01-NOV-15:10 | 1.11 |
| December | 0.114504E+09 | 0.46 | 336.68 | 25-DEC-14:00 | 1.13 |
| Annual Sum or Average | 0.588374E+10 | 0.88 | |||
| Minimum of Months | 63636353.41 | 0.41 | 206.71 | 1.07 | |
| Maximum of Months | 0.906447E+09 | 1.14 | 645.99 | 1.15 |
Report: FanReportMonthly
For: M SE APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.107173E+09 | 0.70 | 40.01 | 01-JAN-00:10 | 0.70 |
| February | 96801429.15 | 0.69 | 40.01 | 01-FEB-00:10 | 0.70 |
| March | 0.107173E+09 | 0.70 | 40.01 | 01-MAR-00:10 | 0.69 |
| April | 0.103716E+09 | 0.70 | 40.01 | 01-APR-00:10 | 0.70 |
| May | 0.107173E+09 | 0.70 | 40.01 | 01-MAY-00:10 | 0.70 |
| June | 0.103716E+09 | 0.70 | 40.01 | 01-JUN-00:10 | 0.70 |
| July | 0.107173E+09 | 0.69 | 40.01 | 01-JUL-00:10 | 0.69 |
| August | 0.107173E+09 | 0.69 | 40.01 | 01-AUG-00:10 | 0.69 |
| September | 0.103716E+09 | 0.69 | 40.01 | 01-SEP-00:10 | 0.69 |
| October | 0.107173E+09 | 0.69 | 40.01 | 01-OCT-00:10 | 0.69 |
| November | 0.103716E+09 | 0.69 | 40.01 | 01-NOV-00:10 | 0.69 |
| December | 0.107173E+09 | 0.70 | 40.01 | 01-DEC-00:10 | 0.70 |
| Annual Sum or Average | 0.126188E+10 | 0.69 | |||
| Minimum of Months | 96801429.15 | 0.69 | 40.01 | 0.69 | |
| Maximum of Months | 0.107173E+09 | 0.70 | 40.01 | 0.70 |
Report: FanReportMonthly
For: M SE APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.107173E+09 | 0.70 | 40.01 | 01-JAN-00:10 | 0.70 |
| February | 96801429.15 | 0.69 | 40.01 | 01-FEB-00:10 | 0.70 |
| March | 0.107173E+09 | 0.69 | 40.01 | 01-MAR-00:10 | 0.69 |
| April | 0.103716E+09 | 0.70 | 40.01 | 01-APR-00:10 | 0.70 |
| May | 0.107173E+09 | 0.70 | 40.01 | 01-MAY-00:10 | 0.70 |
| June | 0.103716E+09 | 0.70 | 40.01 | 01-JUN-00:10 | 0.70 |
| July | 0.107173E+09 | 0.69 | 40.01 | 01-JUL-00:10 | 0.69 |
| August | 0.107173E+09 | 0.69 | 40.01 | 01-AUG-00:10 | 0.69 |
| September | 0.103716E+09 | 0.69 | 40.01 | 01-SEP-00:10 | 0.69 |
| October | 0.107173E+09 | 0.69 | 40.01 | 01-OCT-00:10 | 0.69 |
| November | 0.103716E+09 | 0.69 | 40.01 | 01-NOV-00:10 | 0.70 |
| December | 0.107173E+09 | 0.70 | 40.01 | 01-DEC-00:10 | 0.70 |
| Annual Sum or Average | 0.126188E+10 | 0.69 | |||
| Minimum of Months | 96801429.15 | 0.69 | 40.01 | 0.69 | |
| Maximum of Months | 0.107173E+09 | 0.70 | 40.01 | 0.70 |
Report: FanReportMonthly
For: SPLIT MNE SUPPLY FAN
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 32921884.73 | 0.27 | 155.36 | 31-JAN-17:06 | 1.17 |
| February | 2965447.37 | 0.07 | 52.48 | 18-FEB-16:10 | 1.17 |
| March | 72580758.04 | 0.34 | 237.65 | 16-MAR-16:08 | 1.15 |
| April | 0.447340E+09 | 1.06 | 416.07 | 14-APR-18:00 | 1.12 |
| May | 0.649692E+09 | 1.14 | 499.60 | 20-MAY-14:00 | 1.10 |
| June | 0.911676E+09 | 1.13 | 640.10 | 16-JUN-17:00 | 1.08 |
| July | 0.900324E+09 | 1.12 | 571.12 | 22-JUL-16:10 | 1.08 |
| August | 0.820745E+09 | 1.13 | 575.09 | 25-AUG-17:00 | 1.09 |
| September | 0.673806E+09 | 1.13 | 480.03 | 01-SEP-16:00 | 1.09 |
| October | 0.300236E+09 | 0.82 | 398.32 | 02-OCT-14:00 | 1.11 |
| November | 51210693.75 | 0.37 | 219.27 | 01-NOV-16:02 | 1.14 |
| December | 28512848.42 | 0.28 | 115.67 | 07-DEC-05:00 | 1.02 |
| Annual Sum or Average | 0.489201E+10 | 0.74 | |||
| Minimum of Months | 2965447.37 | 0.07 | 52.48 | 1.02 | |
| Maximum of Months | 0.911676E+09 | 1.14 | 640.10 | 1.17 |
Report: FanReportMonthly
For: M NE APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.107173E+09 | 0.70 | 40.01 | 01-JAN-00:10 | 0.70 |
| February | 96801429.15 | 0.69 | 40.01 | 01-FEB-00:10 | 0.70 |
| March | 0.107173E+09 | 0.70 | 40.01 | 01-MAR-00:10 | 0.69 |
| April | 0.103716E+09 | 0.70 | 40.01 | 01-APR-00:10 | 0.70 |
| May | 0.107173E+09 | 0.70 | 40.01 | 01-MAY-00:10 | 0.70 |
| June | 0.103716E+09 | 0.70 | 40.01 | 01-JUN-00:10 | 0.70 |
| July | 0.107173E+09 | 0.69 | 40.01 | 01-JUL-00:10 | 0.69 |
| August | 0.107173E+09 | 0.69 | 40.01 | 01-AUG-00:10 | 0.69 |
| September | 0.103716E+09 | 0.69 | 40.01 | 01-SEP-00:10 | 0.69 |
| October | 0.107173E+09 | 0.69 | 40.01 | 01-OCT-00:10 | 0.69 |
| November | 0.103716E+09 | 0.69 | 40.01 | 01-NOV-00:10 | 0.69 |
| December | 0.107173E+09 | 0.70 | 40.01 | 01-DEC-00:10 | 0.70 |
| Annual Sum or Average | 0.126188E+10 | 0.69 | |||
| Minimum of Months | 96801429.15 | 0.69 | 40.01 | 0.69 | |
| Maximum of Months | 0.107173E+09 | 0.70 | 40.01 | 0.70 |
Report: FanReportMonthly
For: M NE APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.107173E+09 | 0.70 | 40.01 | 01-JAN-00:10 | 0.70 |
| February | 96801429.15 | 0.69 | 40.01 | 01-FEB-00:10 | 0.70 |
| March | 0.107173E+09 | 0.69 | 40.01 | 01-MAR-00:10 | 0.69 |
| April | 0.103716E+09 | 0.70 | 40.01 | 01-APR-00:10 | 0.70 |
| May | 0.107173E+09 | 0.70 | 40.01 | 01-MAY-00:10 | 0.70 |
| June | 0.103716E+09 | 0.70 | 40.01 | 01-JUN-00:10 | 0.70 |
| July | 0.107173E+09 | 0.69 | 40.01 | 01-JUL-00:10 | 0.69 |
| August | 0.107173E+09 | 0.69 | 40.01 | 01-AUG-00:10 | 0.69 |
| September | 0.103716E+09 | 0.69 | 40.01 | 01-SEP-00:10 | 0.69 |
| October | 0.107173E+09 | 0.69 | 40.01 | 01-OCT-00:10 | 0.69 |
| November | 0.103716E+09 | 0.69 | 40.01 | 01-NOV-00:10 | 0.70 |
| December | 0.107173E+09 | 0.70 | 40.01 | 01-DEC-00:10 | 0.70 |
| Annual Sum or Average | 0.126188E+10 | 0.69 | |||
| Minimum of Months | 96801429.15 | 0.69 | 40.01 | 0.69 | |
| Maximum of Months | 0.107173E+09 | 0.70 | 40.01 | 0.70 |
Report: FanReportMonthly
For: SPLIT MN1 SUPPLY FAN
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 34883208.18 | 0.35 | 145.30 | 31-JAN-17:04 | 1.17 |
| February | 3177424.21 | 0.08 | 60.33 | 18-FEB-16:10 | 1.17 |
| March | 66688249.05 | 0.40 | 203.56 | 16-MAR-16:18 | 1.15 |
| April | 0.353251E+09 | 1.10 | 335.31 | 14-APR-18:00 | 1.12 |
| May | 0.511214E+09 | 1.15 | 397.94 | 31-MAY-18:00 | 1.11 |
| June | 0.708572E+09 | 1.13 | 502.05 | 15-JUN-18:00 | 1.09 |
| July | 0.714295E+09 | 1.13 | 448.29 | 05-JUL-18:00 | 1.10 |
| August | 0.655208E+09 | 1.13 | 451.72 | 25-AUG-17:00 | 1.10 |
| September | 0.554595E+09 | 1.14 | 375.08 | 08-SEP-16:01 | 1.11 |
| October | 0.256263E+09 | 0.89 | 323.57 | 03-OCT-17:50 | 1.11 |
| November | 59183144.41 | 0.48 | 190.64 | 01-NOV-16:02 | 1.14 |
| December | 12855618.76 | 0.20 | 81.49 | 25-DEC-16:10 | 1.17 |
| Annual Sum or Average | 0.393019E+10 | 0.77 | |||
| Minimum of Months | 3177424.21 | 0.08 | 60.33 | 1.09 | |
| Maximum of Months | 0.714295E+09 | 1.15 | 502.05 | 1.17 |
Report: FanReportMonthly
For: M N1 APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.107173E+09 | 0.70 | 40.01 | 01-JAN-00:10 | 0.70 |
| February | 96801429.15 | 0.69 | 40.01 | 01-FEB-00:10 | 0.70 |
| March | 0.107173E+09 | 0.70 | 40.01 | 01-MAR-00:10 | 0.69 |
| April | 0.103716E+09 | 0.70 | 40.01 | 01-APR-00:10 | 0.70 |
| May | 0.107173E+09 | 0.70 | 40.01 | 01-MAY-00:10 | 0.70 |
| June | 0.103716E+09 | 0.70 | 40.01 | 01-JUN-00:10 | 0.70 |
| July | 0.107173E+09 | 0.69 | 40.01 | 01-JUL-00:10 | 0.69 |
| August | 0.107173E+09 | 0.69 | 40.01 | 01-AUG-00:10 | 0.69 |
| September | 0.103716E+09 | 0.69 | 40.01 | 01-SEP-00:10 | 0.69 |
| October | 0.107173E+09 | 0.69 | 40.01 | 01-OCT-00:10 | 0.69 |
| November | 0.103716E+09 | 0.69 | 40.01 | 01-NOV-00:10 | 0.69 |
| December | 0.107173E+09 | 0.70 | 40.01 | 01-DEC-00:10 | 0.70 |
| Annual Sum or Average | 0.126188E+10 | 0.69 | |||
| Minimum of Months | 96801429.15 | 0.69 | 40.01 | 0.69 | |
| Maximum of Months | 0.107173E+09 | 0.70 | 40.01 | 0.70 |
Report: FanReportMonthly
For: M N1 APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.107173E+09 | 0.70 | 40.01 | 01-JAN-00:10 | 0.70 |
| February | 96801429.15 | 0.69 | 40.01 | 01-FEB-00:10 | 0.70 |
| March | 0.107173E+09 | 0.69 | 40.01 | 01-MAR-00:10 | 0.69 |
| April | 0.103716E+09 | 0.70 | 40.01 | 01-APR-00:10 | 0.70 |
| May | 0.107173E+09 | 0.70 | 40.01 | 01-MAY-00:10 | 0.70 |
| June | 0.103716E+09 | 0.70 | 40.01 | 01-JUN-00:10 | 0.70 |
| July | 0.107173E+09 | 0.69 | 40.01 | 01-JUL-00:10 | 0.69 |
| August | 0.107173E+09 | 0.69 | 40.01 | 01-AUG-00:10 | 0.69 |
| September | 0.103716E+09 | 0.69 | 40.01 | 01-SEP-00:10 | 0.69 |
| October | 0.107173E+09 | 0.69 | 40.01 | 01-OCT-00:10 | 0.69 |
| November | 0.103716E+09 | 0.69 | 40.01 | 01-NOV-00:10 | 0.70 |
| December | 0.107173E+09 | 0.70 | 40.01 | 01-DEC-00:10 | 0.70 |
| Annual Sum or Average | 0.126188E+10 | 0.69 | |||
| Minimum of Months | 96801429.15 | 0.69 | 40.01 | 0.69 | |
| Maximum of Months | 0.107173E+09 | 0.70 | 40.01 | 0.70 |
Report: FanReportMonthly
For: SPLIT MN2 SUPPLY FAN
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 35121046.43 | 0.35 | 145.39 | 31-JAN-17:04 | 1.17 |
| February | 3470158.76 | 0.08 | 61.96 | 18-FEB-16:10 | 1.17 |
| March | 67275560.15 | 0.41 | 203.75 | 16-MAR-16:05 | 1.15 |
| April | 0.353837E+09 | 1.10 | 333.90 | 14-APR-18:00 | 1.12 |
| May | 0.511725E+09 | 1.15 | 396.71 | 31-MAY-18:00 | 1.11 |
| June | 0.708945E+09 | 1.13 | 500.70 | 16-JUN-17:03 | 1.09 |
| July | 0.715095E+09 | 1.13 | 447.06 | 05-JUL-18:00 | 1.10 |
| August | 0.656004E+09 | 1.13 | 450.79 | 25-AUG-17:00 | 1.10 |
| September | 0.555047E+09 | 1.14 | 374.60 | 08-SEP-16:01 | 1.11 |
| October | 0.256962E+09 | 0.89 | 323.47 | 03-OCT-17:50 | 1.11 |
| November | 59268495.89 | 0.48 | 189.77 | 01-NOV-16:02 | 1.14 |
| December | 12928781.15 | 0.20 | 81.22 | 25-DEC-16:10 | 1.17 |
| Annual Sum or Average | 0.393568E+10 | 0.77 | |||
| Minimum of Months | 3470158.76 | 0.08 | 61.96 | 1.09 | |
| Maximum of Months | 0.715095E+09 | 1.15 | 500.70 | 1.17 |
Report: FanReportMonthly
For: M N2 APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.107173E+09 | 0.70 | 40.01 | 01-JAN-00:10 | 0.70 |
| February | 96801429.15 | 0.69 | 40.01 | 01-FEB-00:10 | 0.70 |
| March | 0.107173E+09 | 0.70 | 40.01 | 01-MAR-00:10 | 0.69 |
| April | 0.103716E+09 | 0.70 | 40.01 | 01-APR-00:10 | 0.70 |
| May | 0.107173E+09 | 0.70 | 40.01 | 01-MAY-00:10 | 0.70 |
| June | 0.103716E+09 | 0.70 | 40.01 | 01-JUN-00:10 | 0.70 |
| July | 0.107173E+09 | 0.69 | 40.01 | 01-JUL-00:10 | 0.69 |
| August | 0.107173E+09 | 0.69 | 40.01 | 01-AUG-00:10 | 0.69 |
| September | 0.103716E+09 | 0.69 | 40.01 | 01-SEP-00:10 | 0.69 |
| October | 0.107173E+09 | 0.69 | 40.01 | 01-OCT-00:10 | 0.69 |
| November | 0.103716E+09 | 0.69 | 40.01 | 01-NOV-00:10 | 0.69 |
| December | 0.107173E+09 | 0.70 | 40.01 | 01-DEC-00:10 | 0.70 |
| Annual Sum or Average | 0.126188E+10 | 0.69 | |||
| Minimum of Months | 96801429.15 | 0.69 | 40.01 | 0.69 | |
| Maximum of Months | 0.107173E+09 | 0.70 | 40.01 | 0.70 |
Report: FanReportMonthly
For: M N2 APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.107173E+09 | 0.70 | 40.01 | 01-JAN-00:10 | 0.70 |
| February | 96801429.15 | 0.69 | 40.01 | 01-FEB-00:10 | 0.70 |
| March | 0.107173E+09 | 0.69 | 40.01 | 01-MAR-00:10 | 0.69 |
| April | 0.103716E+09 | 0.70 | 40.01 | 01-APR-00:10 | 0.70 |
| May | 0.107173E+09 | 0.70 | 40.01 | 01-MAY-00:10 | 0.70 |
| June | 0.103716E+09 | 0.70 | 40.01 | 01-JUN-00:10 | 0.70 |
| July | 0.107173E+09 | 0.69 | 40.01 | 01-JUL-00:10 | 0.69 |
| August | 0.107173E+09 | 0.69 | 40.01 | 01-AUG-00:10 | 0.69 |
| September | 0.103716E+09 | 0.69 | 40.01 | 01-SEP-00:10 | 0.69 |
| October | 0.107173E+09 | 0.69 | 40.01 | 01-OCT-00:10 | 0.69 |
| November | 0.103716E+09 | 0.69 | 40.01 | 01-NOV-00:10 | 0.70 |
| December | 0.107173E+09 | 0.70 | 40.01 | 01-DEC-00:10 | 0.70 |
| Annual Sum or Average | 0.126188E+10 | 0.69 | |||
| Minimum of Months | 96801429.15 | 0.69 | 40.01 | 0.69 | |
| Maximum of Months | 0.107173E+09 | 0.70 | 40.01 | 0.70 |
Report: FanReportMonthly
For: SPLIT MS1 SUPPLY FAN
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.256729E+09 | 0.79 | 354.55 | 31-JAN-16:10 | 1.12 |
| February | 89098668.72 | 0.59 | 223.38 | 01-FEB-15:30 | 1.15 |
| March | 0.153040E+09 | 0.71 | 316.06 | 18-MAR-16:10 | 1.12 |
| April | 0.449479E+09 | 1.12 | 388.02 | 10-APR-16:05 | 1.11 |
| May | 0.531848E+09 | 1.15 | 412.60 | 20-MAY-14:00 | 1.11 |
| June | 0.693705E+09 | 1.13 | 496.24 | 16-JUN-16:15 | 1.09 |
| July | 0.720547E+09 | 1.13 | 464.86 | 22-JUL-16:10 | 1.09 |
| August | 0.705036E+09 | 1.13 | 489.41 | 25-AUG-16:01 | 1.09 |
| September | 0.647970E+09 | 1.13 | 458.44 | 28-SEP-15:10 | 1.10 |
| October | 0.433328E+09 | 1.04 | 439.91 | 10-OCT-15:10 | 1.10 |
| November | 0.246037E+09 | 0.88 | 370.09 | 20-NOV-14:30 | 1.12 |
| December | 0.151478E+09 | 0.59 | 338.25 | 25-DEC-14:00 | 1.12 |
| Annual Sum or Average | 0.507830E+10 | 0.95 | |||
| Minimum of Months | 89098668.72 | 0.59 | 223.38 | 1.09 | |
| Maximum of Months | 0.720547E+09 | 1.15 | 496.24 | 1.15 |
Report: FanReportMonthly
For: M S1 APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.107173E+09 | 0.70 | 40.01 | 01-JAN-00:10 | 0.70 |
| February | 96801429.15 | 0.69 | 40.01 | 01-FEB-00:10 | 0.70 |
| March | 0.107173E+09 | 0.70 | 40.01 | 01-MAR-00:10 | 0.69 |
| April | 0.103716E+09 | 0.70 | 40.01 | 01-APR-00:10 | 0.70 |
| May | 0.107173E+09 | 0.70 | 40.01 | 01-MAY-00:10 | 0.70 |
| June | 0.103716E+09 | 0.70 | 40.01 | 01-JUN-00:10 | 0.70 |
| July | 0.107173E+09 | 0.69 | 40.01 | 01-JUL-00:10 | 0.69 |
| August | 0.107173E+09 | 0.69 | 40.01 | 01-AUG-00:10 | 0.69 |
| September | 0.103716E+09 | 0.69 | 40.01 | 01-SEP-00:10 | 0.69 |
| October | 0.107173E+09 | 0.69 | 40.01 | 01-OCT-00:10 | 0.69 |
| November | 0.103716E+09 | 0.69 | 40.01 | 01-NOV-00:10 | 0.69 |
| December | 0.107173E+09 | 0.70 | 40.01 | 01-DEC-00:10 | 0.70 |
| Annual Sum or Average | 0.126188E+10 | 0.69 | |||
| Minimum of Months | 96801429.15 | 0.69 | 40.01 | 0.69 | |
| Maximum of Months | 0.107173E+09 | 0.70 | 40.01 | 0.70 |
Report: FanReportMonthly
For: M S1 APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.107173E+09 | 0.70 | 40.01 | 01-JAN-00:10 | 0.70 |
| February | 96801429.15 | 0.69 | 40.01 | 01-FEB-00:10 | 0.70 |
| March | 0.107173E+09 | 0.69 | 40.01 | 01-MAR-00:10 | 0.69 |
| April | 0.103716E+09 | 0.70 | 40.01 | 01-APR-00:10 | 0.70 |
| May | 0.107173E+09 | 0.70 | 40.01 | 01-MAY-00:10 | 0.70 |
| June | 0.103716E+09 | 0.70 | 40.01 | 01-JUN-00:10 | 0.70 |
| July | 0.107173E+09 | 0.69 | 40.01 | 01-JUL-00:10 | 0.69 |
| August | 0.107173E+09 | 0.69 | 40.01 | 01-AUG-00:10 | 0.69 |
| September | 0.103716E+09 | 0.69 | 40.01 | 01-SEP-00:10 | 0.69 |
| October | 0.107173E+09 | 0.69 | 40.01 | 01-OCT-00:10 | 0.69 |
| November | 0.103716E+09 | 0.69 | 40.01 | 01-NOV-00:10 | 0.70 |
| December | 0.107173E+09 | 0.70 | 40.01 | 01-DEC-00:10 | 0.70 |
| Annual Sum or Average | 0.126188E+10 | 0.69 | |||
| Minimum of Months | 96801429.15 | 0.69 | 40.01 | 0.69 | |
| Maximum of Months | 0.107173E+09 | 0.70 | 40.01 | 0.70 |
Report: FanReportMonthly
For: SPLIT MS2 SUPPLY FAN
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.256888E+09 | 0.79 | 354.11 | 31-JAN-16:10 | 1.12 |
| February | 90061426.86 | 0.59 | 223.36 | 01-FEB-15:30 | 1.15 |
| March | 0.153986E+09 | 0.71 | 315.58 | 18-MAR-16:10 | 1.12 |
| April | 0.449942E+09 | 1.12 | 387.96 | 10-APR-16:05 | 1.11 |
| May | 0.532363E+09 | 1.15 | 413.51 | 20-MAY-14:00 | 1.11 |
| June | 0.694090E+09 | 1.13 | 495.65 | 16-JUN-16:15 | 1.09 |
| July | 0.721351E+09 | 1.13 | 464.48 | 22-JUL-16:10 | 1.09 |
| August | 0.705806E+09 | 1.13 | 488.91 | 25-AUG-16:01 | 1.09 |
| September | 0.648375E+09 | 1.13 | 458.46 | 28-SEP-15:10 | 1.10 |
| October | 0.433921E+09 | 1.04 | 439.78 | 10-OCT-15:10 | 1.10 |
| November | 0.246053E+09 | 0.88 | 370.29 | 20-NOV-14:30 | 1.12 |
| December | 0.152154E+09 | 0.59 | 338.61 | 25-DEC-14:00 | 1.12 |
| Annual Sum or Average | 0.508499E+10 | 0.95 | |||
| Minimum of Months | 90061426.86 | 0.59 | 223.36 | 1.09 | |
| Maximum of Months | 0.721351E+09 | 1.15 | 495.65 | 1.15 |
Report: FanReportMonthly
For: M S2 APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.107173E+09 | 0.70 | 40.01 | 01-JAN-00:10 | 0.70 |
| February | 96801429.15 | 0.69 | 40.01 | 01-FEB-00:10 | 0.70 |
| March | 0.107173E+09 | 0.70 | 40.01 | 01-MAR-00:10 | 0.69 |
| April | 0.103716E+09 | 0.70 | 40.01 | 01-APR-00:10 | 0.70 |
| May | 0.107173E+09 | 0.70 | 40.01 | 01-MAY-00:10 | 0.70 |
| June | 0.103716E+09 | 0.70 | 40.01 | 01-JUN-00:10 | 0.70 |
| July | 0.107173E+09 | 0.69 | 40.01 | 01-JUL-00:10 | 0.69 |
| August | 0.107173E+09 | 0.69 | 40.01 | 01-AUG-00:10 | 0.69 |
| September | 0.103716E+09 | 0.69 | 40.01 | 01-SEP-00:10 | 0.69 |
| October | 0.107173E+09 | 0.69 | 40.01 | 01-OCT-00:10 | 0.69 |
| November | 0.103716E+09 | 0.69 | 40.01 | 01-NOV-00:10 | 0.69 |
| December | 0.107173E+09 | 0.70 | 40.01 | 01-DEC-00:10 | 0.70 |
| Annual Sum or Average | 0.126188E+10 | 0.69 | |||
| Minimum of Months | 96801429.15 | 0.69 | 40.01 | 0.69 | |
| Maximum of Months | 0.107173E+09 | 0.70 | 40.01 | 0.70 |
Report: FanReportMonthly
For: M S2 APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.107173E+09 | 0.70 | 40.01 | 01-JAN-00:10 | 0.70 |
| February | 96801429.15 | 0.69 | 40.01 | 01-FEB-00:10 | 0.70 |
| March | 0.107173E+09 | 0.69 | 40.01 | 01-MAR-00:10 | 0.69 |
| April | 0.103716E+09 | 0.70 | 40.01 | 01-APR-00:10 | 0.70 |
| May | 0.107173E+09 | 0.70 | 40.01 | 01-MAY-00:10 | 0.70 |
| June | 0.103716E+09 | 0.70 | 40.01 | 01-JUN-00:10 | 0.70 |
| July | 0.107173E+09 | 0.69 | 40.01 | 01-JUL-00:10 | 0.69 |
| August | 0.107173E+09 | 0.69 | 40.01 | 01-AUG-00:10 | 0.69 |
| September | 0.103716E+09 | 0.69 | 40.01 | 01-SEP-00:10 | 0.69 |
| October | 0.107173E+09 | 0.69 | 40.01 | 01-OCT-00:10 | 0.69 |
| November | 0.103716E+09 | 0.69 | 40.01 | 01-NOV-00:10 | 0.70 |
| December | 0.107173E+09 | 0.70 | 40.01 | 01-DEC-00:10 | 0.70 |
| Annual Sum or Average | 0.126188E+10 | 0.69 | |||
| Minimum of Months | 96801429.15 | 0.69 | 40.01 | 0.69 | |
| Maximum of Months | 0.107173E+09 | 0.70 | 40.01 | 0.70 |
Report: FanReportMonthly
For: SPLIT TSW SUPPLY FAN
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.120189E+09 | 0.71 | 257.26 | 31-JAN-16:30 | 1.12 |
| February | 43305417.17 | 0.60 | 152.31 | 28-FEB-16:30 | 1.15 |
| March | 88794643.76 | 0.62 | 262.48 | 18-MAR-16:20 | 1.11 |
| April | 0.284949E+09 | 0.84 | 365.91 | 14-APR-17:15 | 1.09 |
| May | 0.363873E+09 | 1.00 | 381.06 | 15-MAY-17:02 | 1.08 |
| June | 0.524587E+09 | 1.13 | 480.28 | 16-JUN-16:50 | 1.05 |
| July | 0.516166E+09 | 1.12 | 438.61 | 22-JUL-16:10 | 1.06 |
| August | 0.486712E+09 | 1.12 | 463.02 | 25-AUG-17:00 | 1.06 |
| September | 0.417194E+09 | 1.11 | 404.65 | 08-SEP-16:10 | 1.07 |
| October | 0.230054E+09 | 0.79 | 373.52 | 06-OCT-15:20 | 1.08 |
| November | 0.105233E+09 | 0.63 | 300.50 | 01-NOV-16:10 | 1.10 |
| December | 95663236.01 | 0.72 | 240.02 | 25-DEC-16:20 | 1.12 |
| Annual Sum or Average | 0.327672E+10 | 0.87 | |||
| Minimum of Months | 43305417.17 | 0.60 | 152.31 | 1.05 | |
| Maximum of Months | 0.524587E+09 | 1.13 | 480.28 | 1.15 |
Report: FanReportMonthly
For: T SW APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.70 | 20.01 | 01-JAN-00:10 | 0.70 |
| February | 48400714.57 | 0.69 | 20.01 | 01-FEB-00:10 | 0.70 |
| March | 53586505.42 | 0.70 | 20.01 | 01-MAR-00:10 | 0.69 |
| April | 51857908.47 | 0.70 | 20.01 | 01-APR-00:10 | 0.70 |
| May | 53586505.42 | 0.70 | 20.01 | 01-MAY-00:10 | 0.70 |
| June | 51857908.47 | 0.70 | 20.01 | 01-JUN-00:10 | 0.70 |
| July | 53586505.42 | 0.69 | 20.01 | 01-JUL-00:10 | 0.69 |
| August | 53586505.42 | 0.69 | 20.01 | 01-AUG-00:10 | 0.69 |
| September | 51857908.47 | 0.69 | 20.01 | 01-SEP-00:10 | 0.69 |
| October | 53586505.42 | 0.69 | 20.01 | 01-OCT-00:10 | 0.69 |
| November | 51857908.47 | 0.69 | 20.01 | 01-NOV-00:10 | 0.69 |
| December | 53586505.42 | 0.70 | 20.01 | 01-DEC-00:10 | 0.70 |
| Annual Sum or Average | 0.630938E+09 | 0.69 | |||
| Minimum of Months | 48400714.57 | 0.69 | 20.01 | 0.69 | |
| Maximum of Months | 53586505.42 | 0.70 | 20.01 | 0.70 |
Report: FanReportMonthly
For: T SW APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.70 | 20.01 | 01-JAN-00:10 | 0.70 |
| February | 48400714.57 | 0.69 | 20.01 | 01-FEB-00:10 | 0.70 |
| March | 53586505.42 | 0.69 | 20.01 | 01-MAR-00:10 | 0.69 |
| April | 51857908.47 | 0.70 | 20.01 | 01-APR-00:10 | 0.70 |
| May | 53586505.42 | 0.70 | 20.01 | 01-MAY-00:10 | 0.70 |
| June | 51857908.47 | 0.70 | 20.01 | 01-JUN-00:10 | 0.70 |
| July | 53586505.42 | 0.69 | 20.01 | 01-JUL-00:10 | 0.69 |
| August | 53586505.42 | 0.69 | 20.01 | 01-AUG-00:10 | 0.69 |
| September | 51857908.47 | 0.69 | 20.01 | 01-SEP-00:10 | 0.69 |
| October | 53586505.42 | 0.69 | 20.01 | 01-OCT-00:10 | 0.69 |
| November | 51857908.47 | 0.69 | 20.01 | 01-NOV-00:10 | 0.70 |
| December | 53586505.42 | 0.70 | 20.01 | 01-DEC-00:10 | 0.70 |
| Annual Sum or Average | 0.630938E+09 | 0.69 | |||
| Minimum of Months | 48400714.57 | 0.69 | 20.01 | 0.69 | |
| Maximum of Months | 53586505.42 | 0.70 | 20.01 | 0.70 |
Report: FanReportMonthly
For: SPLIT TNW SUPPLY FAN
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 51151900.42 | 0.59 | 127.09 | 31-JAN-17:02 | 1.16 |
| February | 34800897.66 | 0.58 | 68.26 | 05-FEB-04:00 | 1.01 |
| March | 61908988.71 | 0.56 | 185.49 | 16-MAR-16:30 | 1.14 |
| April | 0.235782E+09 | 0.82 | 339.55 | 14-APR-17:30 | 1.09 |
| May | 0.352625E+09 | 1.01 | 378.55 | 31-MAY-17:30 | 1.09 |
| June | 0.532526E+09 | 1.13 | 483.56 | 16-JUN-17:00 | 1.05 |
| July | 0.512714E+09 | 1.12 | 427.16 | 20-JUL-17:30 | 1.06 |
| August | 0.459670E+09 | 1.13 | 441.89 | 25-AUG-17:00 | 1.06 |
| September | 0.367284E+09 | 1.11 | 360.94 | 08-SEP-16:01 | 1.08 |
| October | 0.153329E+09 | 0.72 | 301.90 | 06-OCT-16:10 | 1.10 |
| November | 49620125.93 | 0.52 | 193.55 | 01-NOV-16:10 | 1.13 |
| December | 72100421.26 | 0.67 | 120.37 | 07-DEC-06:00 | 1.02 |
| Annual Sum or Average | 0.288351E+10 | 0.83 | |||
| Minimum of Months | 34800897.66 | 0.52 | 68.26 | 1.01 | |
| Maximum of Months | 0.532526E+09 | 1.13 | 483.56 | 1.16 |
Report: FanReportMonthly
For: T NW APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.70 | 20.01 | 01-JAN-00:10 | 0.70 |
| February | 48400714.57 | 0.69 | 20.01 | 01-FEB-00:10 | 0.70 |
| March | 53586505.42 | 0.70 | 20.01 | 01-MAR-00:10 | 0.69 |
| April | 51857908.47 | 0.70 | 20.01 | 01-APR-00:10 | 0.70 |
| May | 53586505.42 | 0.70 | 20.01 | 01-MAY-00:10 | 0.70 |
| June | 51857908.47 | 0.70 | 20.01 | 01-JUN-00:10 | 0.70 |
| July | 53586505.42 | 0.69 | 20.01 | 01-JUL-00:10 | 0.69 |
| August | 53586505.42 | 0.69 | 20.01 | 01-AUG-00:10 | 0.69 |
| September | 51857908.47 | 0.69 | 20.01 | 01-SEP-00:10 | 0.69 |
| October | 53586505.42 | 0.69 | 20.01 | 01-OCT-00:10 | 0.69 |
| November | 51857908.47 | 0.69 | 20.01 | 01-NOV-00:10 | 0.69 |
| December | 53586505.42 | 0.70 | 20.01 | 01-DEC-00:10 | 0.70 |
| Annual Sum or Average | 0.630938E+09 | 0.69 | |||
| Minimum of Months | 48400714.57 | 0.69 | 20.01 | 0.69 | |
| Maximum of Months | 53586505.42 | 0.70 | 20.01 | 0.70 |
Report: FanReportMonthly
For: T NW APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.70 | 20.01 | 01-JAN-00:10 | 0.70 |
| February | 48400714.57 | 0.69 | 20.01 | 01-FEB-00:10 | 0.70 |
| March | 53586505.42 | 0.69 | 20.01 | 01-MAR-00:10 | 0.69 |
| April | 51857908.47 | 0.70 | 20.01 | 01-APR-00:10 | 0.70 |
| May | 53586505.42 | 0.70 | 20.01 | 01-MAY-00:10 | 0.70 |
| June | 51857908.47 | 0.70 | 20.01 | 01-JUN-00:10 | 0.70 |
| July | 53586505.42 | 0.69 | 20.01 | 01-JUL-00:10 | 0.69 |
| August | 53586505.42 | 0.69 | 20.01 | 01-AUG-00:10 | 0.69 |
| September | 51857908.47 | 0.69 | 20.01 | 01-SEP-00:10 | 0.69 |
| October | 53586505.42 | 0.69 | 20.01 | 01-OCT-00:10 | 0.69 |
| November | 51857908.47 | 0.69 | 20.01 | 01-NOV-00:10 | 0.70 |
| December | 53586505.42 | 0.70 | 20.01 | 01-DEC-00:10 | 0.70 |
| Annual Sum or Average | 0.630938E+09 | 0.69 | |||
| Minimum of Months | 48400714.57 | 0.69 | 20.01 | 0.69 | |
| Maximum of Months | 53586505.42 | 0.70 | 20.01 | 0.70 |
Report: FanReportMonthly
For: SPLIT TSE SUPPLY FAN
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.114146E+09 | 0.71 | 213.26 | 31-JAN-16:10 | 1.13 |
| February | 42234340.57 | 0.60 | 117.52 | 23-FEB-14:00 | 1.15 |
| March | 86216102.85 | 0.62 | 220.34 | 18-MAR-15:20 | 1.12 |
| April | 0.285732E+09 | 0.86 | 318.30 | 30-APR-13:10 | 1.09 |
| May | 0.367717E+09 | 1.01 | 362.11 | 20-MAY-14:00 | 1.08 |
| June | 0.526871E+09 | 1.12 | 424.86 | 30-JUN-16:10 | 1.05 |
| July | 0.526419E+09 | 1.12 | 391.78 | 22-JUL-16:10 | 1.06 |
| August | 0.495924E+09 | 1.12 | 405.56 | 25-AUG-16:01 | 1.06 |
| September | 0.421472E+09 | 1.11 | 362.57 | 28-SEP-14:10 | 1.07 |
| October | 0.231187E+09 | 0.80 | 343.02 | 06-OCT-14:10 | 1.08 |
| November | 99698437.15 | 0.62 | 252.75 | 01-NOV-15:10 | 1.10 |
| December | 91532916.12 | 0.71 | 193.18 | 25-DEC-14:20 | 1.13 |
| Annual Sum or Average | 0.328915E+10 | 0.87 | |||
| Minimum of Months | 42234340.57 | 0.60 | 117.52 | 1.05 | |
| Maximum of Months | 0.526871E+09 | 1.12 | 424.86 | 1.15 |
Report: FanReportMonthly
For: T SE APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.70 | 20.01 | 01-JAN-00:10 | 0.70 |
| February | 48400714.57 | 0.69 | 20.01 | 01-FEB-00:10 | 0.70 |
| March | 53586505.42 | 0.70 | 20.01 | 01-MAR-00:10 | 0.69 |
| April | 51857908.47 | 0.70 | 20.01 | 01-APR-00:10 | 0.70 |
| May | 53586505.42 | 0.70 | 20.01 | 01-MAY-00:10 | 0.70 |
| June | 51857908.47 | 0.70 | 20.01 | 01-JUN-00:10 | 0.70 |
| July | 53586505.42 | 0.69 | 20.01 | 01-JUL-00:10 | 0.69 |
| August | 53586505.42 | 0.69 | 20.01 | 01-AUG-00:10 | 0.69 |
| September | 51857908.47 | 0.69 | 20.01 | 01-SEP-00:10 | 0.69 |
| October | 53586505.42 | 0.69 | 20.01 | 01-OCT-00:10 | 0.69 |
| November | 51857908.47 | 0.69 | 20.01 | 01-NOV-00:10 | 0.69 |
| December | 53586505.42 | 0.70 | 20.01 | 01-DEC-00:10 | 0.70 |
| Annual Sum or Average | 0.630938E+09 | 0.69 | |||
| Minimum of Months | 48400714.57 | 0.69 | 20.01 | 0.69 | |
| Maximum of Months | 53586505.42 | 0.70 | 20.01 | 0.70 |
Report: FanReportMonthly
For: T SE APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.70 | 20.01 | 01-JAN-00:10 | 0.70 |
| February | 48400714.57 | 0.69 | 20.01 | 01-FEB-00:10 | 0.70 |
| March | 53586505.42 | 0.69 | 20.01 | 01-MAR-00:10 | 0.69 |
| April | 51857908.47 | 0.70 | 20.01 | 01-APR-00:10 | 0.70 |
| May | 53586505.42 | 0.70 | 20.01 | 01-MAY-00:10 | 0.70 |
| June | 51857908.47 | 0.70 | 20.01 | 01-JUN-00:10 | 0.70 |
| July | 53586505.42 | 0.69 | 20.01 | 01-JUL-00:10 | 0.69 |
| August | 53586505.42 | 0.69 | 20.01 | 01-AUG-00:10 | 0.69 |
| September | 51857908.47 | 0.69 | 20.01 | 01-SEP-00:10 | 0.69 |
| October | 53586505.42 | 0.69 | 20.01 | 01-OCT-00:10 | 0.69 |
| November | 51857908.47 | 0.69 | 20.01 | 01-NOV-00:10 | 0.70 |
| December | 53586505.42 | 0.70 | 20.01 | 01-DEC-00:10 | 0.70 |
| Annual Sum or Average | 0.630938E+09 | 0.69 | |||
| Minimum of Months | 48400714.57 | 0.69 | 20.01 | 0.69 | |
| Maximum of Months | 53586505.42 | 0.70 | 20.01 | 0.70 |
Report: FanReportMonthly
For: SPLIT TNE SUPPLY FAN
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 44121731.69 | 0.56 | 96.05 | 01-JAN-07:14 | 1.01 |
| February | 32025136.32 | 0.54 | 70.03 | 05-FEB-04:00 | 1.01 |
| March | 57639792.44 | 0.54 | 147.46 | 16-MAR-16:10 | 1.14 |
| April | 0.236640E+09 | 0.85 | 269.03 | 14-APR-16:05 | 1.11 |
| May | 0.356939E+09 | 1.01 | 330.73 | 20-MAY-14:00 | 1.09 |
| June | 0.534858E+09 | 1.12 | 418.52 | 30-JUN-16:09 | 1.05 |
| July | 0.523053E+09 | 1.12 | 372.04 | 22-JUL-16:10 | 1.07 |
| August | 0.469329E+09 | 1.12 | 377.48 | 25-AUG-16:30 | 1.07 |
| September | 0.372246E+09 | 1.11 | 313.05 | 08-SEP-16:01 | 1.08 |
| October | 0.152635E+09 | 0.72 | 266.94 | 02-OCT-14:00 | 1.10 |
| November | 43786306.48 | 0.50 | 137.40 | 01-NOV-15:20 | 1.14 |
| December | 67498388.43 | 0.66 | 120.78 | 07-DEC-06:00 | 1.02 |
| Annual Sum or Average | 0.289077E+10 | 0.82 | |||
| Minimum of Months | 32025136.32 | 0.50 | 70.03 | 1.01 | |
| Maximum of Months | 0.534858E+09 | 1.12 | 418.52 | 1.14 |
Report: FanReportMonthly
For: T NE APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.70 | 20.01 | 01-JAN-00:10 | 0.70 |
| February | 48400714.57 | 0.69 | 20.01 | 01-FEB-00:10 | 0.70 |
| March | 53586505.42 | 0.70 | 20.01 | 01-MAR-00:10 | 0.69 |
| April | 51857908.47 | 0.70 | 20.01 | 01-APR-00:10 | 0.70 |
| May | 53586505.42 | 0.70 | 20.01 | 01-MAY-00:10 | 0.70 |
| June | 51857908.47 | 0.70 | 20.01 | 01-JUN-00:10 | 0.70 |
| July | 53586505.42 | 0.69 | 20.01 | 01-JUL-00:10 | 0.69 |
| August | 53586505.42 | 0.69 | 20.01 | 01-AUG-00:10 | 0.69 |
| September | 51857908.47 | 0.69 | 20.01 | 01-SEP-00:10 | 0.69 |
| October | 53586505.42 | 0.69 | 20.01 | 01-OCT-00:10 | 0.69 |
| November | 51857908.47 | 0.69 | 20.01 | 01-NOV-00:10 | 0.69 |
| December | 53586505.42 | 0.70 | 20.01 | 01-DEC-00:10 | 0.70 |
| Annual Sum or Average | 0.630938E+09 | 0.69 | |||
| Minimum of Months | 48400714.57 | 0.69 | 20.01 | 0.69 | |
| Maximum of Months | 53586505.42 | 0.70 | 20.01 | 0.70 |
Report: FanReportMonthly
For: T NE APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.70 | 20.01 | 01-JAN-00:10 | 0.70 |
| February | 48400714.57 | 0.69 | 20.01 | 01-FEB-00:10 | 0.70 |
| March | 53586505.42 | 0.69 | 20.01 | 01-MAR-00:10 | 0.69 |
| April | 51857908.47 | 0.70 | 20.01 | 01-APR-00:10 | 0.70 |
| May | 53586505.42 | 0.70 | 20.01 | 01-MAY-00:10 | 0.70 |
| June | 51857908.47 | 0.70 | 20.01 | 01-JUN-00:10 | 0.70 |
| July | 53586505.42 | 0.69 | 20.01 | 01-JUL-00:10 | 0.69 |
| August | 53586505.42 | 0.69 | 20.01 | 01-AUG-00:10 | 0.69 |
| September | 51857908.47 | 0.69 | 20.01 | 01-SEP-00:10 | 0.69 |
| October | 53586505.42 | 0.69 | 20.01 | 01-OCT-00:10 | 0.69 |
| November | 51857908.47 | 0.69 | 20.01 | 01-NOV-00:10 | 0.70 |
| December | 53586505.42 | 0.70 | 20.01 | 01-DEC-00:10 | 0.70 |
| Annual Sum or Average | 0.630938E+09 | 0.69 | |||
| Minimum of Months | 48400714.57 | 0.69 | 20.01 | 0.69 | |
| Maximum of Months | 53586505.42 | 0.70 | 20.01 | 0.70 |
Report: FanReportMonthly
For: SPLIT TN1 SUPPLY FAN
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 25575028.58 | 0.48 | 70.13 | 01-JAN-08:00 | 1.01 |
| February | 18387848.88 | 0.42 | 45.85 | 05-FEB-04:00 | 1.01 |
| March | 39079845.32 | 0.47 | 123.37 | 16-MAR-16:03 | 1.15 |
| April | 0.182754E+09 | 0.86 | 221.84 | 14-APR-16:13 | 1.11 |
| May | 0.280916E+09 | 1.05 | 260.25 | 31-MAY-18:00 | 1.10 |
| June | 0.424182E+09 | 1.13 | 337.88 | 16-JUN-17:00 | 1.07 |
| July | 0.421999E+09 | 1.13 | 296.63 | 05-JUL-18:00 | 1.09 |
| August | 0.380143E+09 | 1.13 | 306.13 | 25-AUG-16:40 | 1.08 |
| September | 0.308027E+09 | 1.12 | 254.03 | 08-SEP-16:01 | 1.09 |
| October | 0.120004E+09 | 0.71 | 210.64 | 02-OCT-14:00 | 1.11 |
| November | 28817389.66 | 0.44 | 119.16 | 01-NOV-16:02 | 1.14 |
| December | 44600981.35 | 0.60 | 87.31 | 07-DEC-05:00 | 1.02 |
| Annual Sum or Average | 0.227449E+10 | 0.80 | |||
| Minimum of Months | 18387848.88 | 0.42 | 45.85 | 1.01 | |
| Maximum of Months | 0.424182E+09 | 1.13 | 337.88 | 1.15 |
Report: FanReportMonthly
For: T N1 APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.70 | 20.01 | 01-JAN-00:10 | 0.70 |
| February | 48400714.57 | 0.69 | 20.01 | 01-FEB-00:10 | 0.70 |
| March | 53586505.42 | 0.70 | 20.01 | 01-MAR-00:10 | 0.69 |
| April | 51857908.47 | 0.70 | 20.01 | 01-APR-00:10 | 0.70 |
| May | 53586505.42 | 0.70 | 20.01 | 01-MAY-00:10 | 0.70 |
| June | 51857908.47 | 0.70 | 20.01 | 01-JUN-00:10 | 0.70 |
| July | 53586505.42 | 0.69 | 20.01 | 01-JUL-00:10 | 0.69 |
| August | 53586505.42 | 0.69 | 20.01 | 01-AUG-00:10 | 0.69 |
| September | 51857908.47 | 0.69 | 20.01 | 01-SEP-00:10 | 0.69 |
| October | 53586505.42 | 0.69 | 20.01 | 01-OCT-00:10 | 0.69 |
| November | 51857908.47 | 0.69 | 20.01 | 01-NOV-00:10 | 0.69 |
| December | 53586505.42 | 0.70 | 20.01 | 01-DEC-00:10 | 0.70 |
| Annual Sum or Average | 0.630938E+09 | 0.69 | |||
| Minimum of Months | 48400714.57 | 0.69 | 20.01 | 0.69 | |
| Maximum of Months | 53586505.42 | 0.70 | 20.01 | 0.70 |
Report: FanReportMonthly
For: T N1 APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.70 | 20.01 | 01-JAN-00:10 | 0.70 |
| February | 48400714.57 | 0.69 | 20.01 | 01-FEB-00:10 | 0.70 |
| March | 53586505.42 | 0.69 | 20.01 | 01-MAR-00:10 | 0.69 |
| April | 51857908.47 | 0.70 | 20.01 | 01-APR-00:10 | 0.70 |
| May | 53586505.42 | 0.70 | 20.01 | 01-MAY-00:10 | 0.70 |
| June | 51857908.47 | 0.70 | 20.01 | 01-JUN-00:10 | 0.70 |
| July | 53586505.42 | 0.69 | 20.01 | 01-JUL-00:10 | 0.69 |
| August | 53586505.42 | 0.69 | 20.01 | 01-AUG-00:10 | 0.69 |
| September | 51857908.47 | 0.69 | 20.01 | 01-SEP-00:10 | 0.69 |
| October | 53586505.42 | 0.69 | 20.01 | 01-OCT-00:10 | 0.69 |
| November | 51857908.47 | 0.69 | 20.01 | 01-NOV-00:10 | 0.70 |
| December | 53586505.42 | 0.70 | 20.01 | 01-DEC-00:10 | 0.70 |
| Annual Sum or Average | 0.630938E+09 | 0.69 | |||
| Minimum of Months | 48400714.57 | 0.69 | 20.01 | 0.69 | |
| Maximum of Months | 53586505.42 | 0.70 | 20.01 | 0.70 |
Report: FanReportMonthly
For: SPLIT TN2 SUPPLY FAN
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 25780632.45 | 0.48 | 70.24 | 01-JAN-08:00 | 1.01 |
| February | 18357164.63 | 0.41 | 46.03 | 05-FEB-04:00 | 1.01 |
| March | 39339998.45 | 0.47 | 123.09 | 16-MAR-16:03 | 1.15 |
| April | 0.183298E+09 | 0.86 | 220.91 | 14-APR-16:17 | 1.11 |
| May | 0.281340E+09 | 1.05 | 258.58 | 31-MAY-18:00 | 1.10 |
| June | 0.424406E+09 | 1.13 | 336.54 | 16-JUN-17:00 | 1.07 |
| July | 0.422461E+09 | 1.13 | 294.98 | 05-JUL-18:00 | 1.09 |
| August | 0.380609E+09 | 1.13 | 305.04 | 25-AUG-16:40 | 1.08 |
| September | 0.308313E+09 | 1.12 | 253.25 | 08-SEP-16:01 | 1.09 |
| October | 0.120385E+09 | 0.71 | 211.08 | 02-OCT-14:00 | 1.11 |
| November | 28928778.07 | 0.45 | 117.99 | 01-NOV-16:02 | 1.14 |
| December | 44667875.89 | 0.60 | 87.41 | 07-DEC-05:00 | 1.02 |
| Annual Sum or Average | 0.227789E+10 | 0.80 | |||
| Minimum of Months | 18357164.63 | 0.41 | 46.03 | 1.01 | |
| Maximum of Months | 0.424406E+09 | 1.13 | 336.54 | 1.15 |
Report: FanReportMonthly
For: T N2 APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.70 | 20.01 | 01-JAN-00:10 | 0.70 |
| February | 48400714.57 | 0.69 | 20.01 | 01-FEB-00:10 | 0.70 |
| March | 53586505.42 | 0.70 | 20.01 | 01-MAR-00:10 | 0.69 |
| April | 51857908.47 | 0.70 | 20.01 | 01-APR-00:10 | 0.70 |
| May | 53586505.42 | 0.70 | 20.01 | 01-MAY-00:10 | 0.70 |
| June | 51857908.47 | 0.70 | 20.01 | 01-JUN-00:10 | 0.70 |
| July | 53586505.42 | 0.69 | 20.01 | 01-JUL-00:10 | 0.69 |
| August | 53586505.42 | 0.69 | 20.01 | 01-AUG-00:10 | 0.69 |
| September | 51857908.47 | 0.69 | 20.01 | 01-SEP-00:10 | 0.69 |
| October | 53586505.42 | 0.69 | 20.01 | 01-OCT-00:10 | 0.69 |
| November | 51857908.47 | 0.69 | 20.01 | 01-NOV-00:10 | 0.69 |
| December | 53586505.42 | 0.70 | 20.01 | 01-DEC-00:10 | 0.70 |
| Annual Sum or Average | 0.630938E+09 | 0.69 | |||
| Minimum of Months | 48400714.57 | 0.69 | 20.01 | 0.69 | |
| Maximum of Months | 53586505.42 | 0.70 | 20.01 | 0.70 |
Report: FanReportMonthly
For: T N2 APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.70 | 20.01 | 01-JAN-00:10 | 0.70 |
| February | 48400714.57 | 0.69 | 20.01 | 01-FEB-00:10 | 0.70 |
| March | 53586505.42 | 0.69 | 20.01 | 01-MAR-00:10 | 0.69 |
| April | 51857908.47 | 0.70 | 20.01 | 01-APR-00:10 | 0.70 |
| May | 53586505.42 | 0.70 | 20.01 | 01-MAY-00:10 | 0.70 |
| June | 51857908.47 | 0.70 | 20.01 | 01-JUN-00:10 | 0.70 |
| July | 53586505.42 | 0.69 | 20.01 | 01-JUL-00:10 | 0.69 |
| August | 53586505.42 | 0.69 | 20.01 | 01-AUG-00:10 | 0.69 |
| September | 51857908.47 | 0.69 | 20.01 | 01-SEP-00:10 | 0.69 |
| October | 53586505.42 | 0.69 | 20.01 | 01-OCT-00:10 | 0.69 |
| November | 51857908.47 | 0.69 | 20.01 | 01-NOV-00:10 | 0.70 |
| December | 53586505.42 | 0.70 | 20.01 | 01-DEC-00:10 | 0.70 |
| Annual Sum or Average | 0.630938E+09 | 0.69 | |||
| Minimum of Months | 48400714.57 | 0.69 | 20.01 | 0.69 | |
| Maximum of Months | 53586505.42 | 0.70 | 20.01 | 0.70 |
Report: FanReportMonthly
For: SPLIT TS1 SUPPLY FAN
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 99061252.18 | 0.65 | 195.89 | 31-JAN-16:10 | 1.13 |
| February | 28902588.42 | 0.48 | 107.59 | 01-FEB-15:30 | 1.15 |
| March | 66548577.62 | 0.56 | 198.61 | 18-MAR-15:20 | 1.12 |
| April | 0.232908E+09 | 0.88 | 260.11 | 14-APR-16:10 | 1.10 |
| May | 0.292111E+09 | 1.03 | 282.36 | 20-MAY-14:00 | 1.09 |
| June | 0.416105E+09 | 1.13 | 339.65 | 16-JUN-16:15 | 1.07 |
| July | 0.425509E+09 | 1.12 | 315.12 | 22-JUL-16:10 | 1.07 |
| August | 0.407472E+09 | 1.13 | 334.20 | 25-AUG-16:01 | 1.07 |
| September | 0.358423E+09 | 1.12 | 309.22 | 28-SEP-15:10 | 1.08 |
| October | 0.200292E+09 | 0.79 | 288.48 | 06-OCT-14:20 | 1.09 |
| November | 88728127.39 | 0.61 | 233.93 | 01-NOV-15:10 | 1.10 |
| December | 72092385.91 | 0.66 | 184.45 | 25-DEC-15:10 | 1.13 |
| Annual Sum or Average | 0.268815E+10 | 0.85 | |||
| Minimum of Months | 28902588.42 | 0.48 | 107.59 | 1.07 | |
| Maximum of Months | 0.425509E+09 | 1.13 | 339.65 | 1.15 |
Report: FanReportMonthly
For: T S1 APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.70 | 20.01 | 01-JAN-00:10 | 0.70 |
| February | 48400714.57 | 0.69 | 20.01 | 01-FEB-00:10 | 0.70 |
| March | 53586505.42 | 0.70 | 20.01 | 01-MAR-00:10 | 0.69 |
| April | 51857908.47 | 0.70 | 20.01 | 01-APR-00:10 | 0.70 |
| May | 53586505.42 | 0.70 | 20.01 | 01-MAY-00:10 | 0.70 |
| June | 51857908.47 | 0.70 | 20.01 | 01-JUN-00:10 | 0.70 |
| July | 53586505.42 | 0.69 | 20.01 | 01-JUL-00:10 | 0.69 |
| August | 53586505.42 | 0.69 | 20.01 | 01-AUG-00:10 | 0.69 |
| September | 51857908.47 | 0.69 | 20.01 | 01-SEP-00:10 | 0.69 |
| October | 53586505.42 | 0.69 | 20.01 | 01-OCT-00:10 | 0.69 |
| November | 51857908.47 | 0.69 | 20.01 | 01-NOV-00:10 | 0.69 |
| December | 53586505.42 | 0.70 | 20.01 | 01-DEC-00:10 | 0.70 |
| Annual Sum or Average | 0.630938E+09 | 0.69 | |||
| Minimum of Months | 48400714.57 | 0.69 | 20.01 | 0.69 | |
| Maximum of Months | 53586505.42 | 0.70 | 20.01 | 0.70 |
Report: FanReportMonthly
For: T S1 APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.70 | 20.01 | 01-JAN-00:10 | 0.70 |
| February | 48400714.57 | 0.69 | 20.01 | 01-FEB-00:10 | 0.70 |
| March | 53586505.42 | 0.69 | 20.01 | 01-MAR-00:10 | 0.69 |
| April | 51857908.47 | 0.70 | 20.01 | 01-APR-00:10 | 0.70 |
| May | 53586505.42 | 0.70 | 20.01 | 01-MAY-00:10 | 0.70 |
| June | 51857908.47 | 0.70 | 20.01 | 01-JUN-00:10 | 0.70 |
| July | 53586505.42 | 0.69 | 20.01 | 01-JUL-00:10 | 0.69 |
| August | 53586505.42 | 0.69 | 20.01 | 01-AUG-00:10 | 0.69 |
| September | 51857908.47 | 0.69 | 20.01 | 01-SEP-00:10 | 0.69 |
| October | 53586505.42 | 0.69 | 20.01 | 01-OCT-00:10 | 0.69 |
| November | 51857908.47 | 0.69 | 20.01 | 01-NOV-00:10 | 0.70 |
| December | 53586505.42 | 0.70 | 20.01 | 01-DEC-00:10 | 0.70 |
| Annual Sum or Average | 0.630938E+09 | 0.69 | |||
| Minimum of Months | 48400714.57 | 0.69 | 20.01 | 0.69 | |
| Maximum of Months | 53586505.42 | 0.70 | 20.01 | 0.70 |
Report: FanReportMonthly
For: SPLIT TS2 SUPPLY FAN
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 99450267.25 | 0.65 | 195.57 | 31-JAN-16:10 | 1.13 |
| February | 29363860.07 | 0.48 | 107.79 | 01-FEB-15:30 | 1.15 |
| March | 67053320.71 | 0.56 | 198.64 | 18-MAR-15:20 | 1.12 |
| April | 0.233395E+09 | 0.88 | 259.26 | 14-APR-16:10 | 1.10 |
| May | 0.292549E+09 | 1.03 | 283.06 | 20-MAY-14:00 | 1.09 |
| June | 0.416342E+09 | 1.13 | 338.67 | 16-JUN-16:15 | 1.07 |
| July | 0.425975E+09 | 1.12 | 314.37 | 22-JUL-16:10 | 1.07 |
| August | 0.407916E+09 | 1.13 | 333.39 | 25-AUG-16:01 | 1.07 |
| September | 0.358663E+09 | 1.12 | 308.95 | 28-SEP-15:10 | 1.08 |
| October | 0.200756E+09 | 0.79 | 288.76 | 06-OCT-14:20 | 1.09 |
| November | 88959273.75 | 0.61 | 233.30 | 01-NOV-15:10 | 1.10 |
| December | 72498600.40 | 0.66 | 184.24 | 25-DEC-15:10 | 1.13 |
| Annual Sum or Average | 0.269292E+10 | 0.85 | |||
| Minimum of Months | 29363860.07 | 0.48 | 107.79 | 1.07 | |
| Maximum of Months | 0.425975E+09 | 1.13 | 338.67 | 1.15 |
Report: FanReportMonthly
For: T S2 APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.70 | 20.01 | 01-JAN-00:10 | 0.70 |
| February | 48400714.57 | 0.69 | 20.01 | 01-FEB-00:10 | 0.70 |
| March | 53586505.42 | 0.70 | 20.01 | 01-MAR-00:10 | 0.69 |
| April | 51857908.47 | 0.70 | 20.01 | 01-APR-00:10 | 0.70 |
| May | 53586505.42 | 0.70 | 20.01 | 01-MAY-00:10 | 0.70 |
| June | 51857908.47 | 0.70 | 20.01 | 01-JUN-00:10 | 0.70 |
| July | 53586505.42 | 0.69 | 20.01 | 01-JUL-00:10 | 0.69 |
| August | 53586505.42 | 0.69 | 20.01 | 01-AUG-00:10 | 0.69 |
| September | 51857908.47 | 0.69 | 20.01 | 01-SEP-00:10 | 0.69 |
| October | 53586505.42 | 0.69 | 20.01 | 01-OCT-00:10 | 0.69 |
| November | 51857908.47 | 0.69 | 20.01 | 01-NOV-00:10 | 0.69 |
| December | 53586505.42 | 0.70 | 20.01 | 01-DEC-00:10 | 0.70 |
| Annual Sum or Average | 0.630938E+09 | 0.69 | |||
| Minimum of Months | 48400714.57 | 0.69 | 20.01 | 0.69 | |
| Maximum of Months | 53586505.42 | 0.70 | 20.01 | 0.70 |
Report: FanReportMonthly
For: T S2 APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.70 | 20.01 | 01-JAN-00:10 | 0.70 |
| February | 48400714.57 | 0.69 | 20.01 | 01-FEB-00:10 | 0.70 |
| March | 53586505.42 | 0.69 | 20.01 | 01-MAR-00:10 | 0.69 |
| April | 51857908.47 | 0.70 | 20.01 | 01-APR-00:10 | 0.70 |
| May | 53586505.42 | 0.70 | 20.01 | 01-MAY-00:10 | 0.70 |
| June | 51857908.47 | 0.70 | 20.01 | 01-JUN-00:10 | 0.70 |
| July | 53586505.42 | 0.69 | 20.01 | 01-JUL-00:10 | 0.69 |
| August | 53586505.42 | 0.69 | 20.01 | 01-AUG-00:10 | 0.69 |
| September | 51857908.47 | 0.69 | 20.01 | 01-SEP-00:10 | 0.69 |
| October | 53586505.42 | 0.69 | 20.01 | 01-OCT-00:10 | 0.69 |
| November | 51857908.47 | 0.69 | 20.01 | 01-NOV-00:10 | 0.70 |
| December | 53586505.42 | 0.70 | 20.01 | 01-DEC-00:10 | 0.70 |
| Annual Sum or Average | 0.630938E+09 | 0.69 | |||
| Minimum of Months | 48400714.57 | 0.69 | 20.01 | 0.69 | |
| Maximum of Months | 53586505.42 | 0.70 | 20.01 | 0.70 |
Report: ZoneTemperatureOscillationReportMonthly
For: G SW APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: G NW APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: OFFICE
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: G NE APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: G N1 APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: G N2 APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: G S1 APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: G S2 APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: M SW APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: M NW APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: M SE APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: M NE APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: M N1 APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: M N2 APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: M S1 APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: M S2 APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: T SW APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: T NW APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: T SE APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: T NE APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: T N1 APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: T N2 APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: T S1 APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: T S2 APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: T CORRIDOR
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: G CORRIDOR
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: M CORRIDOR
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT GSW
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.337752E+09 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 23055703.84 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.120294E+09 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.864198E+09 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.110352E+10 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.169098E+10 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.189350E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.189652E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.177228E+10 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.107774E+10 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.521733E+09 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.228588E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.115302E+11 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 23055703.84 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.189652E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT GNW
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 36881929.55 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 7461889.37 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 58173349.91 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.677454E+09 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.106297E+10 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.172604E+10 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.188531E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.179658E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.158286E+10 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.733752E+09 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.172608E+09 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 23660108.12 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.976375E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 7461889.37 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.188531E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT OFFICE
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.165458E+10 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.135385E+10 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.155405E+10 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.183959E+10 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.205124E+10 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.236827E+10 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.245220E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.253663E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.230806E+10 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.202379E+10 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.171116E+10 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.158459E+10 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.234380E+11 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.135385E+10 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.253663E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT GNE
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 29883467.50 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 6482861.61 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 58195523.40 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.687271E+09 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.108119E+10 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.173840E+10 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.192655E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.183483E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.160144E+10 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.747942E+09 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.159234E+09 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 20296279.30 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.989172E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 6482861.61 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.192655E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT GN1
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 31208411.66 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 902783.98 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 51894720.80 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.568842E+09 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.904899E+09 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.141612E+10 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.157506E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.149631E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.132235E+10 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.627935E+09 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.158638E+09 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 14783911.99 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.816894E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 902783.98 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.157506E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT GN2
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 31493216.99 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 869768.09 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 52315740.24 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.570172E+09 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.906134E+09 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.141701E+10 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.157697E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.149817E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.132335E+10 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.629301E+09 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.158614E+09 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 14912816.38 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.817932E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 869768.09 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.157697E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT GS1
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.402438E+09 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 47717858.55 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.139756E+09 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.769669E+09 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.951098E+09 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.138556E+10 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.158900E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.160339E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.152031E+10 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.992240E+09 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.548116E+09 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.291305E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.102406E+11 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 47717858.55 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.160339E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT GS2
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.430966E+09 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 56852064.34 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.158747E+09 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.844719E+09 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.104656E+10 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.150062E+10 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.171856E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.172646E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.164009E+10 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.108181E+10 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.592338E+09 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.316898E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.111146E+11 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 56852064.34 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.172646E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT MSW
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.956310E+09 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.241741E+09 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.601582E+09 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.228587E+10 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.283619E+10 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.392160E+10 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.397991E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.382437E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.336607E+10 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.199362E+10 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.932531E+09 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.473696E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.254135E+11 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.241741E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.397991E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT MNW
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.144985E+09 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 7231650.98 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.297783E+09 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.188253E+10 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.274829E+10 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.398597E+10 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.395099E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.360234E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.295383E+10 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.128009E+10 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.247875E+09 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 49702505.36 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.211516E+11 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 7231650.98 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.398597E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT MSE
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.939394E+09 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.268338E+09 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.616391E+09 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.231016E+10 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.287288E+10 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.394546E+10 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.406940E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.390546E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.340493E+10 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.202813E+10 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.906416E+09 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.471560E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.257385E+11 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.268338E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.406940E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT MNE
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.119415E+09 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 7212090.48 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.302344E+09 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.190864E+10 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.278582E+10 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.400930E+10 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.404042E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.368572E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.299668E+10 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.130372E+10 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.214308E+09 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 41173080.35 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.214147E+11 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 7212090.48 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.404042E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT MN1
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.138333E+09 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 13520029.93 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.282762E+09 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.150664E+10 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.219111E+10 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.311519E+10 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.320498E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.294084E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.246444E+10 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.111076E+10 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.251856E+09 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 31387106.36 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.172518E+11 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 13520029.93 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.320498E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT MN2
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.139176E+09 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 14764359.81 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.285245E+09 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.150914E+10 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.219332E+10 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.311688E+10 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.320859E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.294442E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.246645E+10 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.111376E+10 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.252196E+09 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 31842615.57 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.172758E+11 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 14764359.81 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.320859E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT MS1
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.107521E+10 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.375840E+09 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.647011E+09 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.191666E+10 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.228009E+10 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.305032E+10 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.323453E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.316498E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.287968E+10 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.186517E+10 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.103758E+10 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.632052E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.221591E+11 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.375840E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.323453E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT MS2
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.107587E+10 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.379919E+09 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.650984E+09 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.191864E+10 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.228232E+10 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.305206E+10 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.323816E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.316845E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.288149E+10 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.186771E+10 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.103763E+10 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.634867E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.221881E+11 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.379919E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.323816E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT TSW
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.441745E+09 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.114627E+09 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.311174E+09 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.122001E+10 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.156743E+10 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.231439E+10 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.232461E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.219471E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.186400E+10 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.985350E+09 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.398148E+09 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.265415E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.140016E+11 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.114627E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.232461E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT TNW
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.105479E+09 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 36510580.76 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.178885E+09 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.100966E+10 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.151873E+10 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.234909E+10 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.230810E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.207251E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.164106E+10 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.646409E+09 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.127566E+09 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 86509698.09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.120805E+11 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 36510580.76 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.234909E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT TSE
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.418043E+09 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.113722E+09 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.304158E+09 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.122258E+10 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.158265E+10 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.232361E+10 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.236958E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.223484E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.188182E+10 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.991280E+09 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.376520E+09 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.252447E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.140713E+11 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.113722E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.236958E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT TNE
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 81129376.47 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 32490577.44 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.166853E+09 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.101260E+10 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.153589E+10 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.235844E+10 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.235345E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.211469E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.166204E+10 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.646584E+09 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.107123E+09 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 76475660.18 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.121478E+11 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 32490577.44 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.235844E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT TN1
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 49057010.74 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 18454987.97 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.122316E+09 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.782779E+09 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.120889E+10 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.187040E+10 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.189842E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.171205E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.137426E+10 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.515531E+09 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 77525920.84 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 49424553.78 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.967910E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 18454987.97 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.189842E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT TN2
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 49668244.09 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 18442061.05 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.123438E+09 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.785095E+09 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.121071E+10 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.187141E+10 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.190050E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.171415E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.137553E+10 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.517218E+09 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 77837934.40 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 49623581.24 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.969362E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 18442061.05 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.190050E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT TS1
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.393812E+09 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 95961667.76 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.253351E+09 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.997274E+09 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.125742E+10 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.183517E+10 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.191521E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.183557E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.159936E+10 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.865850E+09 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.358237E+09 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.234503E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.116417E+11 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 95961667.76 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.191521E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT TS2
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.395327E+09 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 97903557.47 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.255479E+09 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.999344E+09 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.125931E+10 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.183624E+10 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.191731E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.183757E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.160043E+10 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.867827E+09 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.359126E+09 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.236136E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.116620E+11 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 97903557.47 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.191731E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT GSW
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 80838239.64 | 0.977194E+09 | 4039582.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 5725791.28 | 65317716.74 | 5757110.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 29553144.17 | 0.338969E+09 | 31430230.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.202256E+09 | 0.240001E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.256906E+09 | 0.299790E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.384274E+09 | 0.446831E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.422029E+09 | 0.524850E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.422794E+09 | 0.528758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.399363E+09 | 0.507999E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.250368E+09 | 0.309631E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.123657E+09 | 0.153147E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 54810231.66 | 0.660792E+09 | 1127156.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.263257E+10 | 0.321523E+11 | 42354081.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 5725791.28 | 65317716.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.422794E+09 | 0.528758E+10 | 31430230.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT GNW
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 11569710.55 | 93368944.22 | 71747028.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 7461889.37 | 0.00 | 0.147636E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 19072057.34 | 0.144447E+09 | 0.139597E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.158415E+09 | 0.186800E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.247470E+09 | 0.288682E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.392275E+09 | 0.457316E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.420356E+09 | 0.523047E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.400510E+09 | 0.500427E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.356633E+09 | 0.452104E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.169549E+09 | 0.208296E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 40651304.95 | 0.502560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 11494327.14 | 45311102.95 | 0.151748E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.223546E+10 | 0.269524E+11 | 0.510728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 7461889.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.420356E+09 | 0.523047E+10 | 0.151748E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT OFFICE
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 0.135926E+10 | 0.115160E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.122772E+10 | 0.485561E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.135926E+10 | 0.745978E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.131541E+10 | 0.197261E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.135926E+10 | 0.253179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.131541E+10 | 0.367184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.135926E+10 | 0.396974E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.135926E+10 | 0.429706E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.131541E+10 | 0.374615E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.135926E+10 | 0.256185E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.131541E+10 | 0.156540E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.135926E+10 | 0.873606E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.160042E+11 | 0.275732E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 0.122772E+10 | 0.485561E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.135926E+10 | 0.429706E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT GNE
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 9981619.79 | 73183376.55 | 74222875.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 6482861.61 | 0.00 | 0.128784E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 18605959.25 | 0.146321E+09 | 0.127905E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.160822E+09 | 0.189975E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.251860E+09 | 0.294780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.395131E+09 | 0.462719E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.429643E+09 | 0.537225E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.409169E+09 | 0.513752E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.360936E+09 | 0.459360E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.172860E+09 | 0.213003E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 37512196.55 | 0.462972E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 10241786.86 | 37388249.06 | 0.140631E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.226325E+10 | 0.274280E+11 | 0.471542E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 6482861.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.429643E+09 | 0.537225E+10 | 0.140631E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT GN1
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 8889548.24 | 82321760.28 | 37732870.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 902783.98 | 0.00 | 18092934.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 13099328.32 | 0.143750E+09 | 23346759.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.133178E+09 | 0.157093E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.210940E+09 | 0.246433E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.322013E+09 | 0.375622E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.351287E+09 | 0.438177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.333757E+09 | 0.418122E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.298122E+09 | 0.378780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.145237E+09 | 0.178633E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 37339567.54 | 0.463289E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 4904088.92 | 36792051.72 | 36008012.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.185967E+10 | 0.226547E+11 | 0.115181E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 902783.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.351287E+09 | 0.438177E+10 | 37732870.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT GN2
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 8974510.34 | 83065576.08 | 38178103.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 869768.09 | 0.00 | 17432937.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 13180124.36 | 0.145022E+09 | 22868018.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.133489E+09 | 0.157471E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.211227E+09 | 0.246791E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.322213E+09 | 0.375893E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.351712E+09 | 0.438763E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.334173E+09 | 0.418698E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.298348E+09 | 0.379103E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.145557E+09 | 0.179038E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 37335433.24 | 0.463176E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 4913693.45 | 37239106.97 | 35450668.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.186199E+10 | 0.226861E+11 | 0.113930E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 869768.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.351712E+09 | 0.438763E+10 | 38178103.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT GS1
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 96092831.69 | 0.117101E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 11369556.76 | 0.137501E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 32961469.28 | 0.401191E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.180353E+09 | 0.214340E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.221696E+09 | 0.259118E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.315029E+09 | 0.366391E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.354255E+09 | 0.441576E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.357644E+09 | 0.448453E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.342791E+09 | 0.437217E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.230874E+09 | 0.286122E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.129956E+09 | 0.161318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 69809831.10 | 0.844493E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.234283E+10 | 0.286995E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 11369556.76 | 0.137501E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.357644E+09 | 0.448453E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT GS2
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 0.102898E+09 | 0.125543E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 13540111.08 | 0.164049E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 37459328.32 | 0.456534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.198067E+09 | 0.236106E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.244131E+09 | 0.286437E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.341411E+09 | 0.398901E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.383531E+09 | 0.479609E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.385479E+09 | 0.484944E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.370156E+09 | 0.473638E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.251882E+09 | 0.313016E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.140435E+09 | 0.174574E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 75944246.92 | 0.919450E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.254493E+10 | 0.312677E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 13540111.08 | 0.164049E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.385479E+09 | 0.484944E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT MSW
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 0.228623E+09 | 0.278140E+10 | 5201935.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 57423300.34 | 0.702680E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.142274E+09 | 0.173801E+10 | 1501693.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.535505E+09 | 0.638563E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.660906E+09 | 0.775070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.891461E+09 | 0.103719E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.886229E+09 | 0.109753E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.851185E+09 | 0.105806E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.756536E+09 | 0.954894E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.462027E+09 | 0.568249E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.221048E+09 | 0.272884E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.115164E+09 | 0.136338E+10 | 43278583.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.580838E+10 | 0.706098E+11 | 49982212.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 57423300.34 | 0.702680E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.891461E+09 | 0.109753E+11 | 43278583.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT MNW
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 38902221.85 | 0.394261E+09 | 0.109983E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 3060197.84 | 15786714.02 | 34673767.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 71660531.44 | 0.846488E+09 | 37446043.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.440860E+09 | 0.522428E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.640507E+09 | 0.750844E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.906180E+09 | 0.105661E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.880118E+09 | 0.109027E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.801819E+09 | 0.995749E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.663842E+09 | 0.835099E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.294734E+09 | 0.359909E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 59190224.77 | 0.714419E+09 | 23254274.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 31849563.33 | 66374197.18 | 0.515187E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.483272E+10 | 0.581464E+11 | 0.720544E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 3060197.84 | 15786714.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.906180E+09 | 0.109027E+11 | 0.515187E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT MSE
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 0.224565E+09 | 0.273294E+10 | 5274006.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 63636353.41 | 0.781667E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.145736E+09 | 0.178360E+10 | 633746.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.541572E+09 | 0.647690E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.669879E+09 | 0.788708E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.897054E+09 | 0.104904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.906447E+09 | 0.112837E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.869616E+09 | 0.108679E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.765636E+09 | 0.970743E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.470175E+09 | 0.580295E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.214925E+09 | 0.265199E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.114504E+09 | 0.135802E+10 | 39412998.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.588374E+10 | 0.718246E+11 | 45320751.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 63636353.41 | 0.781667E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.906447E+09 | 0.112837E+11 | 39412998.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT MNE
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 32921884.73 | 0.320437E+09 | 0.113666E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 2965447.37 | 16208428.92 | 32709151.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 72580758.04 | 0.861135E+09 | 33641916.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.447340E+09 | 0.531289E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.649692E+09 | 0.764570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.911676E+09 | 0.106852E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.900324E+09 | 0.112112E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.820745E+09 | 0.102459E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.673806E+09 | 0.851125E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.300236E+09 | 0.367847E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 51210693.75 | 0.615646E+09 | 20676834.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 28512848.42 | 46889447.56 | 0.483696E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.489201E+10 | 0.591510E+11 | 0.684390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 2965447.37 | 16208428.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.911676E+09 | 0.112112E+11 | 0.483696E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT MN1
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 34883208.18 | 0.385182E+09 | 48442397.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 3177424.21 | 39582263.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 66688249.05 | 0.810668E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.353251E+09 | 0.418071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.511214E+09 | 0.598956E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.708572E+09 | 0.825368E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.714295E+09 | 0.886717E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.655208E+09 | 0.816105E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.554595E+09 | 0.699797E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.256263E+09 | 0.313497E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 59183144.41 | 0.734135E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 12855618.76 | 68874659.25 | 0.139768E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.393019E+10 | 0.476236E+11 | 0.188210E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 3177424.21 | 39582263.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.714295E+09 | 0.886717E+10 | 0.139768E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT MN2
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 35121046.43 | 0.387434E+09 | 49373744.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 3470158.76 | 43223695.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 67275560.15 | 0.817879E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.353837E+09 | 0.418793E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.511725E+09 | 0.599609E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.708945E+09 | 0.825885E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.715095E+09 | 0.887814E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.656004E+09 | 0.817193E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.555047E+09 | 0.700428E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.256962E+09 | 0.314374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 59268495.89 | 0.734972E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 12928781.15 | 70302132.76 | 0.138840E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.393568E+10 | 0.476948E+11 | 0.188214E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 3470158.76 | 43223695.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.715095E+09 | 0.887814E+10 | 0.138840E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT MS1
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 0.256729E+09 | 0.314274E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 89098668.72 | 0.109791E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.153040E+09 | 0.187462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.449479E+09 | 0.535929E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.531848E+09 | 0.623323E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.693705E+09 | 0.805859E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.720547E+09 | 0.893992E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.705036E+09 | 0.878789E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.647970E+09 | 0.820521E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.433328E+09 | 0.534345E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.246037E+09 | 0.304844E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.151478E+09 | 0.183374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.507830E+10 | 0.619250E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 89098668.72 | 0.109791E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.720547E+09 | 0.893992E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT MS2
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 0.256888E+09 | 0.314493E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 90061426.86 | 0.111003E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.153986E+09 | 0.188630E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.449942E+09 | 0.536536E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.532363E+09 | 0.623989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.694090E+09 | 0.806389E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.721351E+09 | 0.895096E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.705806E+09 | 0.879863E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.648375E+09 | 0.821120E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.433921E+09 | 0.535134E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.246053E+09 | 0.304867E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.152154E+09 | 0.184203E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.508499E+10 | 0.620132E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 90061426.86 | 0.111003E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.721351E+09 | 0.895096E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT TSW
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 0.120189E+09 | 0.122952E+10 | 0.374275E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 43305417.17 | 0.271925E+09 | 0.409963E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 88794643.76 | 0.841181E+09 | 0.388729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.284949E+09 | 0.340086E+10 | 4689579.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.363873E+09 | 0.427009E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.524587E+09 | 0.611278E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.516166E+09 | 0.639319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.486712E+09 | 0.604571E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.417194E+09 | 0.526050E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.230054E+09 | 0.278453E+10 | 77296570.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.105233E+09 | 0.112148E+10 | 0.276576E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 95663236.01 | 0.645892E+09 | 0.821603E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.327672E+10 | 0.383777E+11 | 0.235313E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 43305417.17 | 0.271925E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.524587E+09 | 0.639319E+10 | 0.821603E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT TNW
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 51151900.42 | 0.201590E+09 | 0.664234E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 34800897.66 | 6433018.14 | 0.667626E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 61908988.71 | 0.436953E+09 | 0.503041E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.235782E+09 | 0.279083E+10 | 5390322.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.352625E+09 | 0.413232E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.532526E+09 | 0.621410E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.512714E+09 | 0.634775E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.459670E+09 | 0.569760E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.367284E+09 | 0.460842E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.153329E+09 | 0.178424E+10 | 0.137065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 49620125.93 | 0.291830E+09 | 0.499161E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 72100421.26 | 53613100.47 | 0.131652E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.288351E+10 | 0.325657E+11 | 0.379304E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 34800897.66 | 6433018.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.532526E+09 | 0.634775E+10 | 0.131652E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT TSE
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 0.114146E+09 | 0.116182E+10 | 0.366599E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 42234340.57 | 0.272744E+09 | 0.390997E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 86216102.85 | 0.824904E+09 | 0.367579E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.285732E+09 | 0.342268E+10 | 3859541.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.367717E+09 | 0.433583E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.526871E+09 | 0.618053E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.526419E+09 | 0.656461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.495924E+09 | 0.620340E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.421472E+09 | 0.534686E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.231187E+09 | 0.281609E+10 | 70699643.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 99698437.15 | 0.105937E+10 | 0.267159E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 91532916.12 | 0.612213E+09 | 0.799235E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.328915E+10 | 0.388010E+11 | 0.226613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 42234340.57 | 0.272744E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.526871E+09 | 0.656461E+10 | 0.799235E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT TNE
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 44121731.69 | 0.136428E+09 | 0.636569E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 32025136.32 | 1767208.85 | 0.624193E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 57639792.44 | 0.407533E+09 | 0.469592E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.236640E+09 | 0.280715E+10 | 4686355.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.356939E+09 | 0.420190E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.534858E+09 | 0.628342E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.523053E+09 | 0.651961E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.469329E+09 | 0.585610E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.372246E+09 | 0.469567E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.152635E+09 | 0.179387E+10 | 0.120080E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 43786306.48 | 0.236284E+09 | 0.476078E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 67498388.43 | 33186204.91 | 0.126632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.289077E+10 | 0.329729E+11 | 0.359751E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 32025136.32 | 1767208.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.534858E+09 | 0.651961E+10 | 0.126632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT TN1
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 25575028.58 | 86365781.78 | 0.358748E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 18387848.88 | 254287.27 | 0.361790E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 39079845.32 | 0.310017E+09 | 0.264974E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.182754E+09 | 0.215771E+10 | 530183.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.280916E+09 | 0.328463E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.424182E+09 | 0.494206E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.421999E+09 | 0.523116E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.380143E+09 | 0.472119E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.308027E+09 | 0.387278E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.120004E+09 | 0.143242E+10 | 53528082.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 28817389.66 | 0.182096E+09 | 0.273559E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 44600981.35 | 17803192.37 | 0.848722E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.227449E+10 | 0.262385E+11 | 0.216185E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 18387848.88 | 254287.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.424182E+09 | 0.523116E+10 | 0.848722E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT TN2
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 25780632.45 | 87858231.45 | 0.360373E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 18357164.63 | 321739.86 | 0.361151E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 39339998.45 | 0.313267E+09 | 0.264899E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.183298E+09 | 0.216448E+10 | 544967.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.281340E+09 | 0.329025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.424406E+09 | 0.494587E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.422461E+09 | 0.523814E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.380609E+09 | 0.472809E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.308313E+09 | 0.387710E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.120385E+09 | 0.143743E+10 | 53308043.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 28928778.07 | 0.182807E+09 | 0.274562E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 44667875.89 | 18288177.93 | 0.849395E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.227789E+10 | 0.262839E+11 | 0.216423E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 18357164.63 | 321739.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.424406E+09 | 0.523814E+10 | 0.849395E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT TS1
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 99061252.18 | 0.112835E+10 | 0.128628E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 28902588.42 | 0.255575E+09 | 0.157450E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 66548577.62 | 0.706388E+09 | 0.172754E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.232908E+09 | 0.277777E+10 | 251532.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.292111E+09 | 0.342090E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.416105E+09 | 0.483918E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.425509E+09 | 0.527666E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.407472E+09 | 0.507190E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.358423E+09 | 0.453133E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.200292E+09 | 0.246260E+10 | 15602369.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 88728127.39 | 0.103341E+10 | 98024593.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 72092385.91 | 0.618578E+09 | 0.411813E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.268815E+10 | 0.321226E+11 | 0.984523E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 28902588.42 | 0.255575E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.425509E+09 | 0.527666E+10 | 0.411813E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT TS2
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 99450267.25 | 0.113292E+10 | 0.129372E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 29363860.07 | 0.261301E+09 | 0.157523E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 67053320.71 | 0.712670E+09 | 0.172761E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.233395E+09 | 0.278427E+10 | 263515.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.292549E+09 | 0.342683E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.416342E+09 | 0.484315E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.425975E+09 | 0.528373E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.407916E+09 | 0.507876E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.358663E+09 | 0.453544E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.200756E+09 | 0.246892E+10 | 15600790.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 88959273.75 | 0.103606E+10 | 98468936.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 72498600.40 | 0.623363E+09 | 0.412266E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.269292E+10 | 0.321874E+11 | 0.986255E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 29363860.07 | 0.261301E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.425975E+09 | 0.528373E+10 | 0.412266E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT GSW
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 80838239.64 | 0.00 | 0.00 | 0.00 | 0.256913E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 5725791.28 | 0.00 | 0.00 | 0.00 | 17329912.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 29553144.17 | 0.00 | 0.00 | 0.00 | 90741123.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.202256E+09 | 0.00 | 0.00 | 0.00 | 0.661942E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.256906E+09 | 0.00 | 0.00 | 0.00 | 0.846617E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.384274E+09 | 0.00 | 0.00 | 0.00 | 0.130671E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.422029E+09 | 0.00 | 0.00 | 0.00 | 0.147147E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.422794E+09 | 0.00 | 0.00 | 0.00 | 0.147373E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.399363E+09 | 0.00 | 0.00 | 0.00 | 0.137291E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.250368E+09 | 0.00 | 0.00 | 0.00 | 0.827372E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.123657E+09 | 0.00 | 0.00 | 0.00 | 0.398076E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 54810231.66 | 0.00 | 0.00 | 0.00 | 0.173778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.263257E+10 | 0.00 | 0.00 | 0.00 | 0.889760E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 5725791.28 | 0.00 | 0.00 | 0.00 | 17329912.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.422794E+09 | 0.00 | 0.00 | 0.00 | 0.147373E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT GNW
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 11569710.55 | 0.00 | 0.00 | 0.00 | 25312219.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 7461889.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 19072057.34 | 0.00 | 0.00 | 0.00 | 39101292.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.158415E+09 | 0.00 | 0.00 | 0.00 | 0.519039E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.247470E+09 | 0.00 | 0.00 | 0.00 | 0.815496E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.392275E+09 | 0.00 | 0.00 | 0.00 | 0.133376E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.420356E+09 | 0.00 | 0.00 | 0.00 | 0.146495E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.400510E+09 | 0.00 | 0.00 | 0.00 | 0.139607E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.356633E+09 | 0.00 | 0.00 | 0.00 | 0.122623E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.169549E+09 | 0.00 | 0.00 | 0.00 | 0.564204E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 40651304.95 | 0.00 | 0.00 | 0.00 | 0.131956E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 11494327.14 | 0.00 | 0.00 | 0.00 | 12165780.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.223546E+10 | 0.00 | 0.00 | 0.00 | 0.752829E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 7461889.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.420356E+09 | 0.00 | 0.00 | 0.00 | 0.146495E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT OFFICE
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 0.135926E+10 | 0.00 | 0.00 | 0.00 | 0.295319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.122772E+10 | 0.00 | 0.00 | 0.00 | 0.126129E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.135926E+10 | 0.00 | 0.00 | 0.00 | 0.194792E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.131541E+10 | 0.00 | 0.00 | 0.00 | 0.524178E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.135926E+10 | 0.00 | 0.00 | 0.00 | 0.691985E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.131541E+10 | 0.00 | 0.00 | 0.00 | 0.105286E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.135926E+10 | 0.00 | 0.00 | 0.00 | 0.109294E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.135926E+10 | 0.00 | 0.00 | 0.00 | 0.117738E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.131541E+10 | 0.00 | 0.00 | 0.00 | 0.992646E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.135926E+10 | 0.00 | 0.00 | 0.00 | 0.664535E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.131541E+10 | 0.00 | 0.00 | 0.00 | 0.395750E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.135926E+10 | 0.00 | 0.00 | 0.00 | 0.225329E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.160042E+11 | 0.00 | 0.00 | 0.00 | 0.743384E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 0.122772E+10 | 0.00 | 0.00 | 0.00 | 0.126129E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.135926E+10 | 0.00 | 0.00 | 0.00 | 0.117738E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT GNE
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 9981619.79 | 0.00 | 0.00 | 0.00 | 19901847.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 6482861.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 18605959.25 | 0.00 | 0.00 | 0.00 | 39589564.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.160822E+09 | 0.00 | 0.00 | 0.00 | 0.526450E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.251860E+09 | 0.00 | 0.00 | 0.00 | 0.829333E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.395131E+09 | 0.00 | 0.00 | 0.00 | 0.134327E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.429643E+09 | 0.00 | 0.00 | 0.00 | 0.149691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.409169E+09 | 0.00 | 0.00 | 0.00 | 0.142566E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.360936E+09 | 0.00 | 0.00 | 0.00 | 0.124050E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.172860E+09 | 0.00 | 0.00 | 0.00 | 0.575083E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 37512196.55 | 0.00 | 0.00 | 0.00 | 0.121722E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 10241786.86 | 0.00 | 0.00 | 0.00 | 10054492.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.226325E+10 | 0.00 | 0.00 | 0.00 | 0.762847E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 6482861.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.429643E+09 | 0.00 | 0.00 | 0.00 | 0.149691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT GN1
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 8889548.24 | 0.00 | 0.00 | 0.00 | 22318863.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 902783.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 13099328.32 | 0.00 | 0.00 | 0.00 | 38795392.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.133178E+09 | 0.00 | 0.00 | 0.00 | 0.435665E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.210940E+09 | 0.00 | 0.00 | 0.00 | 0.693960E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.322013E+09 | 0.00 | 0.00 | 0.00 | 0.109410E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.351287E+09 | 0.00 | 0.00 | 0.00 | 0.122378E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.333757E+09 | 0.00 | 0.00 | 0.00 | 0.116255E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.298122E+09 | 0.00 | 0.00 | 0.00 | 0.102423E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.145237E+09 | 0.00 | 0.00 | 0.00 | 0.482698E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 37339567.54 | 0.00 | 0.00 | 0.00 | 0.121299E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 4904088.92 | 0.00 | 0.00 | 0.00 | 9879823.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.185967E+10 | 0.00 | 0.00 | 0.00 | 0.630928E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 902783.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.351287E+09 | 0.00 | 0.00 | 0.00 | 0.122378E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT GN2
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 8974510.34 | 0.00 | 0.00 | 0.00 | 22518706.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 869768.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 13180124.36 | 0.00 | 0.00 | 0.00 | 39135615.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.133489E+09 | 0.00 | 0.00 | 0.00 | 0.436682E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.211227E+09 | 0.00 | 0.00 | 0.00 | 0.694907E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.322213E+09 | 0.00 | 0.00 | 0.00 | 0.109480E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.351712E+09 | 0.00 | 0.00 | 0.00 | 0.122526E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.334173E+09 | 0.00 | 0.00 | 0.00 | 0.116400E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.298348E+09 | 0.00 | 0.00 | 0.00 | 0.102501E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.145557E+09 | 0.00 | 0.00 | 0.00 | 0.483744E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 37335433.24 | 0.00 | 0.00 | 0.00 | 0.121278E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 4913693.45 | 0.00 | 0.00 | 0.00 | 9999122.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.186199E+10 | 0.00 | 0.00 | 0.00 | 0.631733E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 869768.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.351712E+09 | 0.00 | 0.00 | 0.00 | 0.122526E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT GS1
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 96092831.69 | 0.00 | 0.00 | 0.00 | 0.306346E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 11369556.76 | 0.00 | 0.00 | 0.00 | 36348301.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 32961469.28 | 0.00 | 0.00 | 0.00 | 0.106794E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.180353E+09 | 0.00 | 0.00 | 0.00 | 0.589317E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.221696E+09 | 0.00 | 0.00 | 0.00 | 0.729402E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.315029E+09 | 0.00 | 0.00 | 0.00 | 0.107053E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.354255E+09 | 0.00 | 0.00 | 0.00 | 0.123474E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.357644E+09 | 0.00 | 0.00 | 0.00 | 0.124574E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.342791E+09 | 0.00 | 0.00 | 0.00 | 0.117752E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.230874E+09 | 0.00 | 0.00 | 0.00 | 0.761366E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.129956E+09 | 0.00 | 0.00 | 0.00 | 0.418159E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 69809831.10 | 0.00 | 0.00 | 0.00 | 0.221495E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.234283E+10 | 0.00 | 0.00 | 0.00 | 0.789776E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 11369556.76 | 0.00 | 0.00 | 0.00 | 36348301.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.357644E+09 | 0.00 | 0.00 | 0.00 | 0.124574E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT GS2
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 0.102898E+09 | 0.00 | 0.00 | 0.00 | 0.328068E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 13540111.08 | 0.00 | 0.00 | 0.00 | 43311953.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 37459328.32 | 0.00 | 0.00 | 0.00 | 0.121288E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.198067E+09 | 0.00 | 0.00 | 0.00 | 0.646651E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.244131E+09 | 0.00 | 0.00 | 0.00 | 0.802429E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.341411E+09 | 0.00 | 0.00 | 0.00 | 0.115921E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.383531E+09 | 0.00 | 0.00 | 0.00 | 0.133503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.385479E+09 | 0.00 | 0.00 | 0.00 | 0.134098E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.370156E+09 | 0.00 | 0.00 | 0.00 | 0.126993E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.251882E+09 | 0.00 | 0.00 | 0.00 | 0.829928E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.140435E+09 | 0.00 | 0.00 | 0.00 | 0.451903E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 75944246.92 | 0.00 | 0.00 | 0.00 | 0.240954E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.254493E+10 | 0.00 | 0.00 | 0.00 | 0.856968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 13540111.08 | 0.00 | 0.00 | 0.00 | 43311953.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.385479E+09 | 0.00 | 0.00 | 0.00 | 0.134098E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT MSW
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 0.228623E+09 | 0.00 | 0.00 | 0.00 | 0.727687E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 57423300.34 | 0.00 | 0.00 | 0.00 | 0.184318E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.142274E+09 | 0.00 | 0.00 | 0.00 | 0.459309E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.535505E+09 | 0.00 | 0.00 | 0.00 | 0.175036E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.660906E+09 | 0.00 | 0.00 | 0.00 | 0.217529E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.891461E+09 | 0.00 | 0.00 | 0.00 | 0.303014E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.886229E+09 | 0.00 | 0.00 | 0.00 | 0.309368E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.851185E+09 | 0.00 | 0.00 | 0.00 | 0.297318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.756536E+09 | 0.00 | 0.00 | 0.00 | 0.260953E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.462027E+09 | 0.00 | 0.00 | 0.00 | 0.153159E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.221048E+09 | 0.00 | 0.00 | 0.00 | 0.711483E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.115164E+09 | 0.00 | 0.00 | 0.00 | 0.358532E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.580838E+10 | 0.00 | 0.00 | 0.00 | 0.196051E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 57423300.34 | 0.00 | 0.00 | 0.00 | 0.184318E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.891461E+09 | 0.00 | 0.00 | 0.00 | 0.309368E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT MNW
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 38902221.85 | 0.00 | 0.00 | 0.00 | 0.106083E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 3060197.84 | 0.00 | 0.00 | 0.00 | 4171453.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 71660531.44 | 0.00 | 0.00 | 0.00 | 0.226122E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.440860E+09 | 0.00 | 0.00 | 0.00 | 0.144167E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.640507E+09 | 0.00 | 0.00 | 0.00 | 0.210778E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.906180E+09 | 0.00 | 0.00 | 0.00 | 0.307979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.880118E+09 | 0.00 | 0.00 | 0.00 | 0.307087E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.801819E+09 | 0.00 | 0.00 | 0.00 | 0.280052E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.663842E+09 | 0.00 | 0.00 | 0.00 | 0.228999E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.294734E+09 | 0.00 | 0.00 | 0.00 | 0.985356E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 59190224.77 | 0.00 | 0.00 | 0.00 | 0.188685E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 31849563.33 | 0.00 | 0.00 | 0.00 | 17852942.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.483272E+10 | 0.00 | 0.00 | 0.00 | 0.163189E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 3060197.84 | 0.00 | 0.00 | 0.00 | 4171453.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.906180E+09 | 0.00 | 0.00 | 0.00 | 0.307979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT MSE
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 0.224565E+09 | 0.00 | 0.00 | 0.00 | 0.714830E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 63636353.41 | 0.00 | 0.00 | 0.00 | 0.204702E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.145736E+09 | 0.00 | 0.00 | 0.00 | 0.470656E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.541572E+09 | 0.00 | 0.00 | 0.00 | 0.176859E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.669879E+09 | 0.00 | 0.00 | 0.00 | 0.220300E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.897054E+09 | 0.00 | 0.00 | 0.00 | 0.304841E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.906447E+09 | 0.00 | 0.00 | 0.00 | 0.316295E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.869616E+09 | 0.00 | 0.00 | 0.00 | 0.303584E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.765636E+09 | 0.00 | 0.00 | 0.00 | 0.263930E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.470175E+09 | 0.00 | 0.00 | 0.00 | 0.155796E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.214925E+09 | 0.00 | 0.00 | 0.00 | 0.691491E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.114504E+09 | 0.00 | 0.00 | 0.00 | 0.357056E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.588374E+10 | 0.00 | 0.00 | 0.00 | 0.198548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 63636353.41 | 0.00 | 0.00 | 0.00 | 0.204702E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.906447E+09 | 0.00 | 0.00 | 0.00 | 0.316295E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT MNE
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 32921884.73 | 0.00 | 0.00 | 0.00 | 86492904.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 2965447.37 | 0.00 | 0.00 | 0.00 | 4246643.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 72580758.04 | 0.00 | 0.00 | 0.00 | 0.229763E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.447340E+09 | 0.00 | 0.00 | 0.00 | 0.146130E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.649692E+09 | 0.00 | 0.00 | 0.00 | 0.213613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.911676E+09 | 0.00 | 0.00 | 0.00 | 0.309762E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.900324E+09 | 0.00 | 0.00 | 0.00 | 0.314009E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.820745E+09 | 0.00 | 0.00 | 0.00 | 0.286497E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.673806E+09 | 0.00 | 0.00 | 0.00 | 0.232287E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.300236E+09 | 0.00 | 0.00 | 0.00 | 0.100348E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 51210693.75 | 0.00 | 0.00 | 0.00 | 0.163097E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 28512848.42 | 0.00 | 0.00 | 0.00 | 12660231.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.489201E+10 | 0.00 | 0.00 | 0.00 | 0.165227E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 2965447.37 | 0.00 | 0.00 | 0.00 | 4246643.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.911676E+09 | 0.00 | 0.00 | 0.00 | 0.314009E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT MN1
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 34883208.18 | 0.00 | 0.00 | 0.00 | 0.103450E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 3177424.21 | 0.00 | 0.00 | 0.00 | 10342605.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 66688249.05 | 0.00 | 0.00 | 0.00 | 0.216074E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.353251E+09 | 0.00 | 0.00 | 0.00 | 0.115339E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.511214E+09 | 0.00 | 0.00 | 0.00 | 0.167990E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.708572E+09 | 0.00 | 0.00 | 0.00 | 0.240662E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.714295E+09 | 0.00 | 0.00 | 0.00 | 0.249068E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.655208E+09 | 0.00 | 0.00 | 0.00 | 0.228563E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.554595E+09 | 0.00 | 0.00 | 0.00 | 0.190984E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.256263E+09 | 0.00 | 0.00 | 0.00 | 0.854501E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 59183144.41 | 0.00 | 0.00 | 0.00 | 0.192673E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 12855618.76 | 0.00 | 0.00 | 0.00 | 18531487.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.393019E+10 | 0.00 | 0.00 | 0.00 | 0.133216E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 3177424.21 | 0.00 | 0.00 | 0.00 | 10342605.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.714295E+09 | 0.00 | 0.00 | 0.00 | 0.249068E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT MN2
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 35121046.43 | 0.00 | 0.00 | 0.00 | 0.104055E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 3470158.76 | 0.00 | 0.00 | 0.00 | 11294201.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 67275560.15 | 0.00 | 0.00 | 0.00 | 0.217970E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.353837E+09 | 0.00 | 0.00 | 0.00 | 0.115530E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.511725E+09 | 0.00 | 0.00 | 0.00 | 0.168160E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.708945E+09 | 0.00 | 0.00 | 0.00 | 0.240793E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.715095E+09 | 0.00 | 0.00 | 0.00 | 0.249350E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.656004E+09 | 0.00 | 0.00 | 0.00 | 0.228841E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.555047E+09 | 0.00 | 0.00 | 0.00 | 0.191141E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.256962E+09 | 0.00 | 0.00 | 0.00 | 0.856795E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 59268495.89 | 0.00 | 0.00 | 0.00 | 0.192927E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 12928781.15 | 0.00 | 0.00 | 0.00 | 18913834.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.393568E+10 | 0.00 | 0.00 | 0.00 | 0.133401E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 3470158.76 | 0.00 | 0.00 | 0.00 | 11294201.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.715095E+09 | 0.00 | 0.00 | 0.00 | 0.249350E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT MS1
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 0.256729E+09 | 0.00 | 0.00 | 0.00 | 0.818477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 89098668.72 | 0.00 | 0.00 | 0.00 | 0.286741E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.153040E+09 | 0.00 | 0.00 | 0.00 | 0.493971E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.449479E+09 | 0.00 | 0.00 | 0.00 | 0.146719E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.531848E+09 | 0.00 | 0.00 | 0.00 | 0.174824E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.693705E+09 | 0.00 | 0.00 | 0.00 | 0.235661E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.720547E+09 | 0.00 | 0.00 | 0.00 | 0.251398E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.705036E+09 | 0.00 | 0.00 | 0.00 | 0.245994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.647970E+09 | 0.00 | 0.00 | 0.00 | 0.223171E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.433328E+09 | 0.00 | 0.00 | 0.00 | 0.143184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.246037E+09 | 0.00 | 0.00 | 0.00 | 0.791541E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.151478E+09 | 0.00 | 0.00 | 0.00 | 0.480574E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.507830E+10 | 0.00 | 0.00 | 0.00 | 0.170808E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 89098668.72 | 0.00 | 0.00 | 0.00 | 0.286741E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.720547E+09 | 0.00 | 0.00 | 0.00 | 0.251398E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT MS2
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 0.256888E+09 | 0.00 | 0.00 | 0.00 | 0.818983E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 90061426.86 | 0.00 | 0.00 | 0.00 | 0.289857E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.153986E+09 | 0.00 | 0.00 | 0.00 | 0.496998E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.449942E+09 | 0.00 | 0.00 | 0.00 | 0.146870E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.532363E+09 | 0.00 | 0.00 | 0.00 | 0.174995E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.694090E+09 | 0.00 | 0.00 | 0.00 | 0.235797E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.721351E+09 | 0.00 | 0.00 | 0.00 | 0.251680E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.705806E+09 | 0.00 | 0.00 | 0.00 | 0.246264E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.648375E+09 | 0.00 | 0.00 | 0.00 | 0.223311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.433921E+09 | 0.00 | 0.00 | 0.00 | 0.143379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.246053E+09 | 0.00 | 0.00 | 0.00 | 0.791572E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.152154E+09 | 0.00 | 0.00 | 0.00 | 0.482713E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.508499E+10 | 0.00 | 0.00 | 0.00 | 0.171031E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 90061426.86 | 0.00 | 0.00 | 0.00 | 0.289857E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.721351E+09 | 0.00 | 0.00 | 0.00 | 0.251680E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT TSW
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 0.120189E+09 | 0.00 | 0.00 | 0.00 | 0.321556E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 43305417.17 | 0.00 | 0.00 | 0.00 | 71321544.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 88794643.76 | 0.00 | 0.00 | 0.00 | 0.222380E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.284949E+09 | 0.00 | 0.00 | 0.00 | 0.935065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.363873E+09 | 0.00 | 0.00 | 0.00 | 0.120356E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.524587E+09 | 0.00 | 0.00 | 0.00 | 0.178981E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.516166E+09 | 0.00 | 0.00 | 0.00 | 0.180844E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.486712E+09 | 0.00 | 0.00 | 0.00 | 0.170800E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.417194E+09 | 0.00 | 0.00 | 0.00 | 0.144681E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.230054E+09 | 0.00 | 0.00 | 0.00 | 0.755297E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.105233E+09 | 0.00 | 0.00 | 0.00 | 0.292915E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 95663236.01 | 0.00 | 0.00 | 0.00 | 0.169752E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.327672E+10 | 0.00 | 0.00 | 0.00 | 0.107249E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 43305417.17 | 0.00 | 0.00 | 0.00 | 71321544.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.524587E+09 | 0.00 | 0.00 | 0.00 | 0.180844E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT TNW
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 51151900.42 | 0.00 | 0.00 | 0.00 | 54326923.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 34800897.66 | 0.00 | 0.00 | 0.00 | 1709683.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 61908988.71 | 0.00 | 0.00 | 0.00 | 0.116976E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.235782E+09 | 0.00 | 0.00 | 0.00 | 0.773879E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.352625E+09 | 0.00 | 0.00 | 0.00 | 0.116611E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.532526E+09 | 0.00 | 0.00 | 0.00 | 0.181657E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.512714E+09 | 0.00 | 0.00 | 0.00 | 0.179539E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.459670E+09 | 0.00 | 0.00 | 0.00 | 0.161284E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.367284E+09 | 0.00 | 0.00 | 0.00 | 0.127377E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.153329E+09 | 0.00 | 0.00 | 0.00 | 0.493080E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 49620125.93 | 0.00 | 0.00 | 0.00 | 77945559.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 72100421.26 | 0.00 | 0.00 | 0.00 | 14409276.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.288351E+10 | 0.00 | 0.00 | 0.00 | 0.919700E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 34800897.66 | 0.00 | 0.00 | 0.00 | 1709683.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.532526E+09 | 0.00 | 0.00 | 0.00 | 0.181657E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT TSE
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 0.114146E+09 | 0.00 | 0.00 | 0.00 | 0.303897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 42234340.57 | 0.00 | 0.00 | 0.00 | 71488041.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 86216102.85 | 0.00 | 0.00 | 0.00 | 0.217941E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.285732E+09 | 0.00 | 0.00 | 0.00 | 0.936847E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.367717E+09 | 0.00 | 0.00 | 0.00 | 0.121493E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.526871E+09 | 0.00 | 0.00 | 0.00 | 0.179674E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.526419E+09 | 0.00 | 0.00 | 0.00 | 0.184316E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.495924E+09 | 0.00 | 0.00 | 0.00 | 0.173892E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.421472E+09 | 0.00 | 0.00 | 0.00 | 0.146035E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.231187E+09 | 0.00 | 0.00 | 0.00 | 0.760092E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 99698437.15 | 0.00 | 0.00 | 0.00 | 0.276821E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 91532916.12 | 0.00 | 0.00 | 0.00 | 0.160915E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.328915E+10 | 0.00 | 0.00 | 0.00 | 0.107821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 42234340.57 | 0.00 | 0.00 | 0.00 | 71488041.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.526871E+09 | 0.00 | 0.00 | 0.00 | 0.184316E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT TNE
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 44121731.69 | 0.00 | 0.00 | 0.00 | 37007644.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 32025136.32 | 0.00 | 0.00 | 0.00 | 465441.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 57639792.44 | 0.00 | 0.00 | 0.00 | 0.109213E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.236640E+09 | 0.00 | 0.00 | 0.00 | 0.775962E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.356939E+09 | 0.00 | 0.00 | 0.00 | 0.117895E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.534858E+09 | 0.00 | 0.00 | 0.00 | 0.182358E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.523053E+09 | 0.00 | 0.00 | 0.00 | 0.183039E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.469329E+09 | 0.00 | 0.00 | 0.00 | 0.164536E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.372246E+09 | 0.00 | 0.00 | 0.00 | 0.128979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.152635E+09 | 0.00 | 0.00 | 0.00 | 0.493949E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 43786306.48 | 0.00 | 0.00 | 0.00 | 63336405.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 67498388.43 | 0.00 | 0.00 | 0.00 | 8977271.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.289077E+10 | 0.00 | 0.00 | 0.00 | 0.925699E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 32025136.32 | 0.00 | 0.00 | 0.00 | 465441.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.534858E+09 | 0.00 | 0.00 | 0.00 | 0.183039E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT TN1
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 25575028.58 | 0.00 | 0.00 | 0.00 | 23481982.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 18387848.88 | 0.00 | 0.00 | 0.00 | 67139.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 39079845.32 | 0.00 | 0.00 | 0.00 | 83236303.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.182754E+09 | 0.00 | 0.00 | 0.00 | 0.600025E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.280916E+09 | 0.00 | 0.00 | 0.00 | 0.927973E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.424182E+09 | 0.00 | 0.00 | 0.00 | 0.144621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.421999E+09 | 0.00 | 0.00 | 0.00 | 0.147642E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.380143E+09 | 0.00 | 0.00 | 0.00 | 0.133191E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.308027E+09 | 0.00 | 0.00 | 0.00 | 0.106623E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.120004E+09 | 0.00 | 0.00 | 0.00 | 0.395527E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 28817389.66 | 0.00 | 0.00 | 0.00 | 48708531.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 44600981.35 | 0.00 | 0.00 | 0.00 | 4823572.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.227449E+10 | 0.00 | 0.00 | 0.00 | 0.740461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 18387848.88 | 0.00 | 0.00 | 0.00 | 67139.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.424182E+09 | 0.00 | 0.00 | 0.00 | 0.147642E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT TN2
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 25780632.45 | 0.00 | 0.00 | 0.00 | 23887611.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 18357164.63 | 0.00 | 0.00 | 0.00 | 84896.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 39339998.45 | 0.00 | 0.00 | 0.00 | 84098236.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.183298E+09 | 0.00 | 0.00 | 0.00 | 0.601797E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.281340E+09 | 0.00 | 0.00 | 0.00 | 0.929369E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.424406E+09 | 0.00 | 0.00 | 0.00 | 0.144700E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.422461E+09 | 0.00 | 0.00 | 0.00 | 0.147804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.380609E+09 | 0.00 | 0.00 | 0.00 | 0.133354E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.308313E+09 | 0.00 | 0.00 | 0.00 | 0.106722E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.120385E+09 | 0.00 | 0.00 | 0.00 | 0.396833E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 28928778.07 | 0.00 | 0.00 | 0.00 | 48909156.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 44667875.89 | 0.00 | 0.00 | 0.00 | 4955705.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.227789E+10 | 0.00 | 0.00 | 0.00 | 0.741573E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 18357164.63 | 0.00 | 0.00 | 0.00 | 84896.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.424406E+09 | 0.00 | 0.00 | 0.00 | 0.147804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT TS1
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 99061252.18 | 0.00 | 0.00 | 0.00 | 0.294750E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 28902588.42 | 0.00 | 0.00 | 0.00 | 67059079.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 66548577.62 | 0.00 | 0.00 | 0.00 | 0.186803E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.232908E+09 | 0.00 | 0.00 | 0.00 | 0.764366E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.292111E+09 | 0.00 | 0.00 | 0.00 | 0.965314E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.416105E+09 | 0.00 | 0.00 | 0.00 | 0.141907E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.425509E+09 | 0.00 | 0.00 | 0.00 | 0.148970E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.407472E+09 | 0.00 | 0.00 | 0.00 | 0.142810E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.358423E+09 | 0.00 | 0.00 | 0.00 | 0.124094E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.200292E+09 | 0.00 | 0.00 | 0.00 | 0.665557E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 88728127.39 | 0.00 | 0.00 | 0.00 | 0.269509E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 72092385.91 | 0.00 | 0.00 | 0.00 | 0.162410E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.268815E+10 | 0.00 | 0.00 | 0.00 | 0.895358E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 28902588.42 | 0.00 | 0.00 | 0.00 | 67059079.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.425509E+09 | 0.00 | 0.00 | 0.00 | 0.148970E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT TS2
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 99450267.25 | 0.00 | 0.00 | 0.00 | 0.295877E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 29363860.07 | 0.00 | 0.00 | 0.00 | 68539697.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 67053320.71 | 0.00 | 0.00 | 0.00 | 0.188426E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.233395E+09 | 0.00 | 0.00 | 0.00 | 0.765948E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.292549E+09 | 0.00 | 0.00 | 0.00 | 0.966757E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.416342E+09 | 0.00 | 0.00 | 0.00 | 0.141990E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.425975E+09 | 0.00 | 0.00 | 0.00 | 0.149134E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.407916E+09 | 0.00 | 0.00 | 0.00 | 0.142965E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.358663E+09 | 0.00 | 0.00 | 0.00 | 0.124176E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.200756E+09 | 0.00 | 0.00 | 0.00 | 0.667071E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 88959273.75 | 0.00 | 0.00 | 0.00 | 0.270167E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 72498600.40 | 0.00 | 0.00 | 0.00 | 0.163637E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.269292E+10 | 0.00 | 0.00 | 0.00 | 0.896909E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 29363860.07 | 0.00 | 0.00 | 0.00 | 68539697.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.425975E+09 | 0.00 | 0.00 | 0.00 | 0.149134E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: G SW APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.471280E+09 | 6039398.81 | 0.00 | 1690079.45 | 0.00 | 0.00 | 0.231754E+09 | 0.00 | 0.35 |
| February | 0.635015E+09 | 24025.41 | 0.00 | 256213.35 | 4069.04 | 0.00 | 68131799.01 | 0.00 | 0.35 |
| March | 0.562099E+09 | 15075535.31 | 0.00 | 294922.23 | 0.00 | 0.00 | 44019373.92 | 0.00 | 0.35 |
| April | 57533803.42 | 0.165570E+09 | 0.00 | 1114884.04 | 3561.55 | 0.00 | 0.186053E+09 | 0.00 | 0.35 |
| May | 4151125.53 | 0.284626E+09 | 0.00 | 1027904.14 | 0.00 | 0.00 | 0.133214E+09 | 0.00 | 0.35 |
| June | 0.00 | 0.540159E+09 | 0.00 | 615456.26 | 0.00 | 0.00 | 29719801.12 | 0.00 | 0.36 |
| July | 0.00 | 0.788295E+09 | 0.00 | 243570.05 | 0.00 | 0.00 | 13500791.31 | 0.00 | 0.36 |
| August | 0.00 | 0.725960E+09 | 0.00 | 263990.11 | 0.00 | 0.00 | 8949408.12 | 0.00 | 0.36 |
| September | 0.00 | 0.569960E+09 | 0.00 | 615626.43 | 0.00 | 0.00 | 20744532.90 | 0.00 | 0.36 |
| October | 53940576.06 | 0.157439E+09 | 0.00 | 2562678.66 | 0.00 | 0.00 | 0.316157E+09 | 0.00 | 0.35 |
| November | 0.223040E+09 | 14767224.85 | 0.00 | 2767899.11 | 0.00 | 0.00 | 0.417145E+09 | 0.00 | 0.35 |
| December | 0.636869E+09 | 2156867.81 | 0.00 | 1553611.49 | 26593.97 | 0.00 | 0.275862E+09 | 0.00 | 0.35 |
| Annual Sum or Average | 0.264393E+10 | 0.327007E+10 | 0.00 | 13006835.32 | 34224.56 | 0.00 | 0.174525E+10 | 0.00 | 0.35 |
| Minimum of Months | 0.00 | 24025.41 | 0.00 | 243570.05 | 0.00 | 0.00 | 8949408.12 | 0.00 | 0.35 |
| Maximum of Months | 0.636869E+09 | 0.788295E+09 | 0.00 | 2767899.11 | 26593.97 | 0.00 | 0.417145E+09 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: G NW APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.567245E+09 | 4880883.57 | 0.00 | 92568.32 | 1322902.26 | 43858537.93 | 12008624.17 | 0.00 | 0.35 |
| February | 0.562790E+09 | 0.00 | 0.00 | 0.00 | 93524.60 | 55991721.43 | 0.00 | 0.00 | 0.35 |
| March | 0.479014E+09 | 10943154.40 | 0.00 | 101394.10 | 3417669.50 | 61521441.95 | 15402653.70 | 0.00 | 0.35 |
| April | 89961780.92 | 0.163289E+09 | 0.00 | 805428.48 | 1922500.20 | 0.00 | 0.150179E+09 | 0.00 | 0.35 |
| May | 4407947.52 | 0.281853E+09 | 0.00 | 1014963.99 | 0.00 | 0.00 | 0.132165E+09 | 0.00 | 0.35 |
| June | 0.00 | 0.536998E+09 | 0.00 | 649521.87 | 0.00 | 0.00 | 29572703.80 | 0.00 | 0.36 |
| July | 0.00 | 0.789506E+09 | 0.00 | 251033.32 | 0.00 | 0.00 | 13430727.91 | 0.00 | 0.36 |
| August | 0.00 | 0.719862E+09 | 0.00 | 250805.00 | 0.00 | 0.00 | 9044179.38 | 0.00 | 0.36 |
| September | 0.00 | 0.557812E+09 | 0.00 | 564736.99 | 0.00 | 0.00 | 21363275.59 | 0.00 | 0.36 |
| October | 0.147873E+09 | 0.154152E+09 | 0.00 | 1460316.33 | 0.00 | 0.00 | 0.218789E+09 | 0.00 | 0.35 |
| November | 0.431749E+09 | 12942591.65 | 0.00 | 810939.19 | 0.00 | 0.00 | 0.188595E+09 | 0.00 | 0.35 |
| December | 0.742018E+09 | 1505285.87 | 0.00 | 88551.57 | 985537.00 | 56227991.75 | 20261885.68 | 0.00 | 0.35 |
| Annual Sum or Average | 0.302506E+10 | 0.323374E+10 | 0.00 | 6090259.16 | 7742133.56 | 0.217600E+09 | 0.810812E+09 | 0.00 | 0.35 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
| Maximum of Months | 0.742018E+09 | 0.789506E+09 | 0.00 | 1460316.33 | 3417669.50 | 61521441.95 | 0.218789E+09 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: OFFICE
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.103662E+10 | 944806.24 | 0.00 | 1625959.98 | 9838.36 | 0.00 | 0.135663E+09 | 0.00 | 0.52 |
| February | 0.929994E+09 | 0.00 | 0.00 | 652181.83 | 38417.87 | 0.00 | 0.220994E+09 | 0.00 | 0.52 |
| March | 0.898814E+09 | 4481770.92 | 0.00 | 735348.41 | 449411.13 | 0.00 | 0.149417E+09 | 0.00 | 0.52 |
| April | 0.459548E+09 | 68860703.45 | 0.00 | 1183472.78 | 26647388.33 | 0.00 | 46594272.40 | 0.00 | 0.52 |
| May | 0.323119E+09 | 0.139779E+09 | 0.00 | 930445.97 | 56326427.78 | 0.00 | 12166578.75 | 0.00 | 0.52 |
| June | 0.134108E+09 | 0.364853E+09 | 0.00 | 241584.95 | 0.111927E+09 | 0.00 | 5650537.62 | 0.00 | 0.53 |
| July | 0.119151E+09 | 0.449201E+09 | 0.00 | 213933.20 | 99984753.05 | 0.00 | 4479540.12 | 0.00 | 0.53 |
| August | 0.153903E+09 | 0.465405E+09 | 0.00 | 365383.10 | 80382162.22 | 0.00 | 10135726.47 | 0.00 | 0.53 |
| September | 0.207278E+09 | 0.303570E+09 | 0.00 | 669383.91 | 45486348.70 | 0.00 | 18664844.16 | 0.00 | 0.53 |
| October | 0.673750E+09 | 89433067.06 | 0.00 | 1992276.33 | 10094819.84 | 0.00 | 0.109995E+09 | 0.00 | 0.53 |
| November | 0.988550E+09 | 6531204.07 | 0.00 | 2126865.25 | 275665.43 | 0.00 | 0.140476E+09 | 0.00 | 0.52 |
| December | 0.126257E+10 | 167857.33 | 0.00 | 1350614.94 | 0.00 | 0.00 | 0.205583E+09 | 0.00 | 0.52 |
| Annual Sum or Average | 0.718741E+10 | 0.189323E+10 | 0.00 | 12087450.66 | 0.431622E+09 | 0.00 | 0.105982E+10 | 0.00 | 0.52 |
| Minimum of Months | 0.119151E+09 | 0.00 | 0.00 | 213933.20 | 0.00 | 0.00 | 4479540.12 | 0.00 | 0.52 |
| Maximum of Months | 0.126257E+10 | 0.465405E+09 | 0.00 | 2126865.25 | 0.111927E+09 | 0.00 | 0.220994E+09 | 0.00 | 0.53 |
Report: MechanicalVentilationLoadsMonthly
For: G NE APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.564662E+09 | 4747167.23 | 0.00 | 65427.24 | 1466962.07 | 47125854.82 | 11116289.22 | 0.00 | 0.35 |
| February | 0.579035E+09 | 0.00 | 0.00 | 0.00 | 92171.98 | 44231947.36 | 0.00 | 0.00 | 0.35 |
| March | 0.485580E+09 | 11588149.44 | 0.00 | 103959.30 | 2591460.78 | 57768526.19 | 16992283.22 | 0.00 | 0.35 |
| April | 83007661.06 | 0.164434E+09 | 0.00 | 930045.89 | 237008.41 | 0.00 | 0.157801E+09 | 0.00 | 0.35 |
| May | 4832844.02 | 0.281103E+09 | 0.00 | 1136829.04 | 0.00 | 0.00 | 0.131775E+09 | 0.00 | 0.35 |
| June | 0.00 | 0.536488E+09 | 0.00 | 668006.54 | 0.00 | 0.00 | 29608715.92 | 0.00 | 0.36 |
| July | 0.00 | 0.795087E+09 | 0.00 | 253921.74 | 0.00 | 0.00 | 13410084.09 | 0.00 | 0.36 |
| August | 0.00 | 0.726634E+09 | 0.00 | 250396.14 | 0.00 | 0.00 | 8958268.01 | 0.00 | 0.36 |
| September | 0.00 | 0.562553E+09 | 0.00 | 570686.37 | 0.00 | 0.00 | 21381585.09 | 0.00 | 0.36 |
| October | 0.127733E+09 | 0.155224E+09 | 0.00 | 1553988.45 | 0.00 | 0.00 | 0.240309E+09 | 0.00 | 0.35 |
| November | 0.431810E+09 | 12976690.17 | 0.00 | 761457.23 | 0.00 | 0.00 | 0.191481E+09 | 0.00 | 0.35 |
| December | 0.759537E+09 | 1468546.00 | 0.00 | 64749.61 | 928590.47 | 48453028.88 | 12520712.90 | 0.00 | 0.35 |
| Annual Sum or Average | 0.303620E+10 | 0.325231E+10 | 0.00 | 6359467.55 | 5316193.70 | 0.197579E+09 | 0.835354E+09 | 0.00 | 0.35 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
| Maximum of Months | 0.759537E+09 | 0.795087E+09 | 0.00 | 1553988.45 | 2591460.78 | 57768526.19 | 0.240309E+09 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: G N1 APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.608859E+09 | 4593203.93 | 0.00 | 100542.57 | 1037919.36 | 20749253.42 | 26408578.18 | 0.00 | 0.35 |
| February | 0.653711E+09 | 0.00 | 0.00 | 0.00 | 65943.12 | 0.00 | 0.00 | 0.00 | 0.35 |
| March | 0.562131E+09 | 11076250.24 | 0.00 | 124849.61 | 2378139.80 | 0.00 | 25956140.53 | 0.00 | 0.35 |
| April | 47817045.80 | 0.158663E+09 | 0.00 | 965129.10 | 2394135.73 | 0.00 | 0.200054E+09 | 0.00 | 0.35 |
| May | 261552.50 | 0.275745E+09 | 0.00 | 1124448.06 | 0.00 | 0.00 | 0.140294E+09 | 0.00 | 0.35 |
| June | 0.00 | 0.528849E+09 | 0.00 | 631876.24 | 0.00 | 0.00 | 31660041.72 | 0.00 | 0.36 |
| July | 0.00 | 0.781382E+09 | 0.00 | 231470.05 | 0.00 | 0.00 | 14218825.27 | 0.00 | 0.36 |
| August | 0.00 | 0.712438E+09 | 0.00 | 229257.44 | 0.00 | 0.00 | 9362416.98 | 0.00 | 0.36 |
| September | 0.00 | 0.549064E+09 | 0.00 | 546163.56 | 0.00 | 0.00 | 22369072.37 | 0.00 | 0.36 |
| October | 0.101295E+09 | 0.151560E+09 | 0.00 | 1507245.87 | 0.00 | 0.00 | 0.275339E+09 | 0.00 | 0.35 |
| November | 0.395364E+09 | 12515018.84 | 0.00 | 899606.65 | 0.00 | 0.00 | 0.243153E+09 | 0.00 | 0.35 |
| December | 0.815223E+09 | 1300447.06 | 0.00 | 90500.82 | 1096807.64 | 0.00 | 31969703.68 | 0.00 | 0.35 |
| Annual Sum or Average | 0.318466E+10 | 0.318719E+10 | 0.00 | 6451089.97 | 6972945.64 | 20749253.42 | 0.102079E+10 | 0.00 | 0.35 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
| Maximum of Months | 0.815223E+09 | 0.781382E+09 | 0.00 | 1507245.87 | 2394135.73 | 20749253.42 | 0.275339E+09 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: G N2 APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.607783E+09 | 4608325.62 | 0.00 | 100980.23 | 1023003.97 | 21656185.36 | 26366885.80 | 0.00 | 0.35 |
| February | 0.654512E+09 | 0.00 | 0.00 | 0.00 | 65553.89 | 0.00 | 0.00 | 0.00 | 0.35 |
| March | 0.562695E+09 | 11144105.17 | 0.00 | 125888.03 | 2290995.65 | 0.00 | 25993701.75 | 0.00 | 0.35 |
| April | 47547927.49 | 0.158770E+09 | 0.00 | 966952.87 | 2263049.38 | 0.00 | 0.200358E+09 | 0.00 | 0.35 |
| May | 280604.26 | 0.275725E+09 | 0.00 | 1125998.50 | 0.00 | 0.00 | 0.140277E+09 | 0.00 | 0.35 |
| June | 0.00 | 0.528835E+09 | 0.00 | 631841.86 | 0.00 | 0.00 | 31662413.99 | 0.00 | 0.36 |
| July | 0.00 | 0.781618E+09 | 0.00 | 231231.83 | 0.00 | 0.00 | 14217717.64 | 0.00 | 0.36 |
| August | 0.00 | 0.712707E+09 | 0.00 | 229184.04 | 0.00 | 0.00 | 9357695.70 | 0.00 | 0.36 |
| September | 0.00 | 0.549240E+09 | 0.00 | 546197.91 | 0.00 | 0.00 | 22369935.41 | 0.00 | 0.36 |
| October | 99843089.62 | 0.151598E+09 | 0.00 | 1513938.86 | 0.00 | 0.00 | 0.276876E+09 | 0.00 | 0.35 |
| November | 0.396506E+09 | 12516068.34 | 0.00 | 898164.06 | 0.00 | 0.00 | 0.242042E+09 | 0.00 | 0.35 |
| December | 0.815000E+09 | 1300285.30 | 0.00 | 91082.85 | 1087431.98 | 0.00 | 32473058.31 | 0.00 | 0.35 |
| Annual Sum or Average | 0.318417E+10 | 0.318806E+10 | 0.00 | 6461461.04 | 6730034.87 | 21656185.36 | 0.102199E+10 | 0.00 | 0.35 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
| Maximum of Months | 0.815000E+09 | 0.781618E+09 | 0.00 | 1513938.86 | 2290995.65 | 21656185.36 | 0.276876E+09 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: G S1 APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.286124E+09 | 5525635.49 | 0.00 | 2402935.42 | 0.00 | 0.00 | 0.446748E+09 | 0.00 | 0.35 |
| February | 0.588785E+09 | 23344.89 | 0.00 | 546939.69 | 0.00 | 0.00 | 0.173300E+09 | 0.00 | 0.36 |
| March | 0.513630E+09 | 14612446.33 | 0.00 | 536825.41 | 0.00 | 0.00 | 0.140244E+09 | 0.00 | 0.35 |
| April | 25193133.52 | 0.161585E+09 | 0.00 | 1368397.42 | 0.00 | 0.00 | 0.225535E+09 | 0.00 | 0.35 |
| May | 1273557.49 | 0.278990E+09 | 0.00 | 1136359.06 | 0.00 | 0.00 | 0.140058E+09 | 0.00 | 0.35 |
| June | 0.00 | 0.532495E+09 | 0.00 | 601431.19 | 0.00 | 0.00 | 31817994.86 | 0.00 | 0.36 |
| July | 0.00 | 0.780851E+09 | 0.00 | 224838.63 | 0.00 | 0.00 | 14306469.48 | 0.00 | 0.36 |
| August | 0.00 | 0.720487E+09 | 0.00 | 243871.64 | 0.00 | 0.00 | 9238157.98 | 0.00 | 0.36 |
| September | 0.00 | 0.564471E+09 | 0.00 | 610094.80 | 0.00 | 0.00 | 21562290.09 | 0.00 | 0.36 |
| October | 10879122.88 | 0.155475E+09 | 0.00 | 2841091.77 | 0.00 | 0.00 | 0.366019E+09 | 0.00 | 0.35 |
| November | 50433667.93 | 14470272.67 | 0.00 | 3333687.64 | 0.00 | 0.00 | 0.600037E+09 | 0.00 | 0.35 |
| December | 0.441435E+09 | 2098157.74 | 0.00 | 2300564.22 | 0.00 | 0.00 | 0.509559E+09 | 0.00 | 0.35 |
| Annual Sum or Average | 0.191775E+10 | 0.323108E+10 | 0.00 | 16147036.89 | 0.00 | 0.00 | 0.267842E+10 | 0.00 | 0.35 |
| Minimum of Months | 0.00 | 23344.89 | 0.00 | 224838.63 | 0.00 | 0.00 | 9238157.98 | 0.00 | 0.35 |
| Maximum of Months | 0.588785E+09 | 0.780851E+09 | 0.00 | 3333687.64 | 0.00 | 0.00 | 0.600037E+09 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: G S2 APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.250227E+09 | 5500370.43 | 0.00 | 2611992.30 | 0.00 | 0.00 | 0.483321E+09 | 0.00 | 0.35 |
| February | 0.572683E+09 | 23560.54 | 0.00 | 630312.93 | 0.00 | 0.00 | 0.195585E+09 | 0.00 | 0.36 |
| March | 0.490042E+09 | 14583520.29 | 0.00 | 652218.59 | 0.00 | 0.00 | 0.169338E+09 | 0.00 | 0.35 |
| April | 17017318.26 | 0.161493E+09 | 0.00 | 1588704.47 | 0.00 | 0.00 | 0.233765E+09 | 0.00 | 0.35 |
| May | 139964.89 | 0.278850E+09 | 0.00 | 1344720.14 | 0.00 | 0.00 | 0.140840E+09 | 0.00 | 0.35 |
| June | 0.00 | 0.532634E+09 | 0.00 | 698923.72 | 0.00 | 0.00 | 31682186.97 | 0.00 | 0.36 |
| July | 0.00 | 0.794158E+09 | 0.00 | 255024.00 | 0.00 | 0.00 | 14265386.32 | 0.00 | 0.36 |
| August | 0.00 | 0.733312E+09 | 0.00 | 264380.75 | 0.00 | 0.00 | 8851099.76 | 0.00 | 0.36 |
| September | 0.00 | 0.577374E+09 | 0.00 | 669396.26 | 0.00 | 0.00 | 20594348.32 | 0.00 | 0.36 |
| October | 4051020.04 | 0.157470E+09 | 0.00 | 3155471.80 | 0.00 | 0.00 | 0.371670E+09 | 0.00 | 0.35 |
| November | 41554410.03 | 14632445.02 | 0.00 | 3616669.23 | 0.00 | 0.00 | 0.606083E+09 | 0.00 | 0.35 |
| December | 0.412842E+09 | 2097106.79 | 0.00 | 2529756.80 | 0.00 | 0.00 | 0.540371E+09 | 0.00 | 0.35 |
| Annual Sum or Average | 0.178856E+10 | 0.327213E+10 | 0.00 | 18017571.00 | 0.00 | 0.00 | 0.281637E+10 | 0.00 | 0.35 |
| Minimum of Months | 0.00 | 23560.54 | 0.00 | 255024.00 | 0.00 | 0.00 | 8851099.76 | 0.00 | 0.35 |
| Maximum of Months | 0.572683E+09 | 0.794158E+09 | 0.00 | 3616669.23 | 0.00 | 0.00 | 0.606083E+09 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: M SW APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.883327E+09 | 12804959.47 | 0.00 | 4642055.83 | 0.00 | 0.00 | 0.513227E+09 | 0.00 | 0.35 |
| February | 0.107786E+10 | 43618.66 | 0.00 | 2116395.51 | 0.00 | 0.00 | 0.434641E+09 | 0.00 | 0.36 |
| March | 0.897922E+09 | 30645896.30 | 0.00 | 2365305.16 | 0.00 | 0.00 | 0.398879E+09 | 0.00 | 0.35 |
| April | 63128485.23 | 0.337682E+09 | 0.00 | 3144596.44 | 0.00 | 0.00 | 0.418234E+09 | 0.00 | 0.35 |
| May | 2715289.57 | 0.578844E+09 | 0.00 | 2772424.76 | 0.00 | 0.00 | 0.263478E+09 | 0.00 | 0.35 |
| June | 0.00 | 0.109412E+10 | 0.00 | 1359865.43 | 0.00 | 0.00 | 55420408.84 | 0.00 | 0.36 |
| July | 0.00 | 0.155854E+10 | 0.00 | 460407.01 | 0.00 | 0.00 | 25679542.97 | 0.00 | 0.36 |
| August | 0.00 | 0.142108E+10 | 0.00 | 487191.13 | 0.00 | 0.00 | 18615872.16 | 0.00 | 0.36 |
| September | 258447.79 | 0.108959E+10 | 0.00 | 954635.44 | 0.00 | 0.00 | 45623116.28 | 0.00 | 0.36 |
| October | 0.263415E+09 | 0.309929E+09 | 0.00 | 3852232.67 | 0.00 | 0.00 | 0.459680E+09 | 0.00 | 0.35 |
| November | 0.664102E+09 | 29249493.40 | 0.00 | 4367312.24 | 0.00 | 0.00 | 0.592982E+09 | 0.00 | 0.35 |
| December | 0.134896E+10 | 4178971.87 | 0.00 | 2923447.79 | 356652.16 | 2300278.56 | 0.428163E+09 | 0.00 | 0.35 |
| Annual Sum or Average | 0.520169E+10 | 0.646671E+10 | 0.00 | 29445869.42 | 356652.16 | 2300278.56 | 0.365462E+10 | 0.00 | 0.35 |
| Minimum of Months | 0.00 | 43618.66 | 0.00 | 460407.01 | 0.00 | 0.00 | 18615872.16 | 0.00 | 0.35 |
| Maximum of Months | 0.134896E+10 | 0.155854E+10 | 0.00 | 4642055.83 | 356652.16 | 2300278.56 | 0.592982E+09 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: M NW APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.110404E+10 | 11640674.42 | 0.00 | 552157.45 | 904520.15 | 74040121.03 | 0.111059E+09 | 0.00 | 0.35 |
| February | 0.133461E+10 | 0.00 | 0.00 | 79639.83 | 90925.47 | 3542236.82 | 32564489.18 | 0.00 | 0.35 |
| March | 0.107771E+10 | 28001412.60 | 0.00 | 833100.25 | 0.00 | 5225042.93 | 0.154154E+09 | 0.00 | 0.35 |
| April | 95349739.60 | 0.336906E+09 | 0.00 | 2574239.97 | 0.00 | 0.00 | 0.383615E+09 | 0.00 | 0.35 |
| May | 502199.15 | 0.573965E+09 | 0.00 | 2805878.44 | 0.00 | 0.00 | 0.264466E+09 | 0.00 | 0.35 |
| June | 0.00 | 0.108850E+10 | 0.00 | 1418482.58 | 0.00 | 0.00 | 55265982.44 | 0.00 | 0.36 |
| July | 0.00 | 0.156045E+10 | 0.00 | 476465.15 | 0.00 | 0.00 | 25597353.75 | 0.00 | 0.36 |
| August | 0.00 | 0.140868E+10 | 0.00 | 477621.63 | 0.00 | 0.00 | 18931996.55 | 0.00 | 0.36 |
| September | 260518.95 | 0.106350E+10 | 0.00 | 869829.17 | 0.00 | 0.00 | 46961593.59 | 0.00 | 0.36 |
| October | 0.407551E+09 | 0.303111E+09 | 0.00 | 1852729.39 | 0.00 | 0.00 | 0.296926E+09 | 0.00 | 0.35 |
| November | 0.966275E+09 | 25850957.01 | 0.00 | 923354.04 | 0.00 | 4896874.24 | 0.218780E+09 | 0.00 | 0.35 |
| December | 0.128345E+10 | 2945373.50 | 0.00 | 115118.00 | 2533884.17 | 0.292606E+09 | 22003430.11 | 0.00 | 0.35 |
| Annual Sum or Average | 0.626974E+10 | 0.640354E+10 | 0.00 | 12978615.90 | 3529329.78 | 0.380310E+09 | 0.163032E+10 | 0.00 | 0.35 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 79639.83 | 0.00 | 0.00 | 18931996.55 | 0.00 | 0.35 |
| Maximum of Months | 0.133461E+10 | 0.156045E+10 | 0.00 | 2805878.44 | 2533884.17 | 0.292606E+09 | 0.383615E+09 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: M SE APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.868366E+09 | 12718203.41 | 0.00 | 4686050.61 | 0.00 | 0.00 | 0.529599E+09 | 0.00 | 0.35 |
| February | 0.102980E+10 | 45516.06 | 0.00 | 2240370.03 | 0.00 | 0.00 | 0.487767E+09 | 0.00 | 0.36 |
| March | 0.873750E+09 | 30542958.13 | 0.00 | 2473218.96 | 0.00 | 0.00 | 0.431470E+09 | 0.00 | 0.35 |
| April | 58005958.09 | 0.336652E+09 | 0.00 | 3565902.06 | 0.00 | 0.00 | 0.423865E+09 | 0.00 | 0.35 |
| May | 1701659.71 | 0.576943E+09 | 0.00 | 3114373.43 | 0.00 | 0.00 | 0.264556E+09 | 0.00 | 0.35 |
| June | 0.00 | 0.109274E+10 | 0.00 | 1416382.27 | 0.00 | 0.00 | 55478176.17 | 0.00 | 0.36 |
| July | 0.00 | 0.157089E+10 | 0.00 | 472747.17 | 0.00 | 0.00 | 25635686.95 | 0.00 | 0.36 |
| August | 0.00 | 0.143608E+10 | 0.00 | 489101.76 | 0.00 | 0.00 | 18397067.41 | 0.00 | 0.36 |
| September | 258504.64 | 0.110040E+10 | 0.00 | 972029.98 | 0.00 | 0.00 | 45648316.06 | 0.00 | 0.36 |
| October | 0.234202E+09 | 0.312084E+09 | 0.00 | 4110597.96 | 0.00 | 0.00 | 0.489982E+09 | 0.00 | 0.35 |
| November | 0.650827E+09 | 29237679.56 | 0.00 | 4382570.06 | 0.00 | 0.00 | 0.612828E+09 | 0.00 | 0.35 |
| December | 0.132742E+10 | 4176033.62 | 0.00 | 2947325.64 | 363125.94 | 1532764.44 | 0.456646E+09 | 0.00 | 0.35 |
| Annual Sum or Average | 0.504433E+10 | 0.650251E+10 | 0.00 | 30870669.94 | 363125.94 | 1532764.44 | 0.384187E+10 | 0.00 | 0.35 |
| Minimum of Months | 0.00 | 45516.06 | 0.00 | 472747.17 | 0.00 | 0.00 | 18397067.41 | 0.00 | 0.35 |
| Maximum of Months | 0.132742E+10 | 0.157089E+10 | 0.00 | 4686050.61 | 363125.94 | 1532764.44 | 0.612828E+09 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: M NE APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.112308E+10 | 11782459.23 | 0.00 | 405550.84 | 739581.44 | 72799887.70 | 96283490.29 | 0.00 | 0.35 |
| February | 0.133797E+10 | 0.00 | 0.00 | 72548.24 | 93850.09 | 7965610.92 | 40999001.37 | 0.00 | 0.35 |
| March | 0.108129E+10 | 27947461.96 | 0.00 | 860919.51 | 0.00 | 2006201.96 | 0.165270E+09 | 0.00 | 0.35 |
| April | 85286912.23 | 0.335966E+09 | 0.00 | 2963284.09 | 0.00 | 0.00 | 0.394394E+09 | 0.00 | 0.35 |
| May | 267006.41 | 0.572178E+09 | 0.00 | 3152086.53 | 0.00 | 0.00 | 0.264721E+09 | 0.00 | 0.35 |
| June | 0.00 | 0.108730E+10 | 0.00 | 1470529.84 | 0.00 | 0.00 | 55318107.37 | 0.00 | 0.36 |
| July | 0.00 | 0.157261E+10 | 0.00 | 490851.19 | 0.00 | 0.00 | 25554964.70 | 0.00 | 0.36 |
| August | 0.00 | 0.142455E+10 | 0.00 | 473880.19 | 0.00 | 0.00 | 18711137.75 | 0.00 | 0.36 |
| September | 260570.75 | 0.107599E+10 | 0.00 | 895281.58 | 0.00 | 0.00 | 46983660.50 | 0.00 | 0.36 |
| October | 0.401558E+09 | 0.305863E+09 | 0.00 | 1966883.89 | 0.00 | 0.00 | 0.308248E+09 | 0.00 | 0.35 |
| November | 0.973615E+09 | 25983866.85 | 0.00 | 774583.55 | 0.00 | 2282928.74 | 0.222222E+09 | 0.00 | 0.35 |
| December | 0.131773E+10 | 2871453.11 | 0.00 | 73024.81 | 2337074.03 | 0.271821E+09 | 12148984.83 | 0.00 | 0.35 |
| Annual Sum or Average | 0.632105E+10 | 0.644304E+10 | 0.00 | 13599424.25 | 3170505.57 | 0.356875E+09 | 0.165085E+10 | 0.00 | 0.35 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 72548.24 | 0.00 | 0.00 | 12148984.83 | 0.00 | 0.35 |
| Maximum of Months | 0.133797E+10 | 0.157261E+10 | 0.00 | 3152086.53 | 2337074.03 | 0.271821E+09 | 0.394394E+09 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: M N1 APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.113983E+10 | 10657375.57 | 0.00 | 744164.53 | 641342.87 | 0.00 | 0.224919E+09 | 0.00 | 0.35 |
| February | 0.134365E+10 | 0.00 | 0.00 | 250571.70 | 64757.76 | 0.00 | 0.127468E+09 | 0.00 | 0.36 |
| March | 0.968158E+09 | 26607097.80 | 0.00 | 1193904.30 | 0.00 | 0.00 | 0.343382E+09 | 0.00 | 0.35 |
| April | 38670457.34 | 0.327517E+09 | 0.00 | 2819292.63 | 0.00 | 0.00 | 0.455178E+09 | 0.00 | 0.35 |
| May | 0.00 | 0.560199E+09 | 0.00 | 2805443.89 | 0.00 | 0.00 | 0.274323E+09 | 0.00 | 0.35 |
| June | 0.00 | 0.106952E+10 | 0.00 | 1337966.00 | 0.00 | 0.00 | 60164766.42 | 0.00 | 0.36 |
| July | 0.00 | 0.154630E+10 | 0.00 | 443930.78 | 0.00 | 0.00 | 27423234.56 | 0.00 | 0.36 |
| August | 0.00 | 0.139908E+10 | 0.00 | 435974.26 | 0.00 | 0.00 | 19225868.74 | 0.00 | 0.36 |
| September | 0.00 | 0.105676E+10 | 0.00 | 884296.57 | 0.00 | 0.00 | 47724169.45 | 0.00 | 0.36 |
| October | 0.320212E+09 | 0.299033E+09 | 0.00 | 2231673.55 | 0.00 | 0.00 | 0.416351E+09 | 0.00 | 0.35 |
| November | 0.885723E+09 | 25111448.11 | 0.00 | 1266194.74 | 0.00 | 0.00 | 0.358705E+09 | 0.00 | 0.35 |
| December | 0.159588E+10 | 2826698.99 | 0.00 | 169729.09 | 2117402.47 | 18060074.72 | 62601039.02 | 0.00 | 0.35 |
| Annual Sum or Average | 0.629212E+10 | 0.632362E+10 | 0.00 | 14583142.07 | 2823503.10 | 18060074.72 | 0.241747E+10 | 0.00 | 0.35 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 169729.09 | 0.00 | 0.00 | 19225868.74 | 0.00 | 0.35 |
| Maximum of Months | 0.159588E+10 | 0.154630E+10 | 0.00 | 2819292.63 | 2117402.47 | 18060074.72 | 0.455178E+09 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: M N2 APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.113978E+10 | 10652663.68 | 0.00 | 745612.47 | 640571.85 | 0.00 | 0.224899E+09 | 0.00 | 0.35 |
| February | 0.133981E+10 | 0.00 | 0.00 | 267577.28 | 64503.36 | 0.00 | 0.133409E+09 | 0.00 | 0.36 |
| March | 0.967665E+09 | 26603805.29 | 0.00 | 1210120.72 | 0.00 | 0.00 | 0.345065E+09 | 0.00 | 0.35 |
| April | 39597744.90 | 0.327487E+09 | 0.00 | 2821555.00 | 0.00 | 0.00 | 0.454298E+09 | 0.00 | 0.35 |
| May | 0.00 | 0.560151E+09 | 0.00 | 2807130.33 | 0.00 | 0.00 | 0.274331E+09 | 0.00 | 0.35 |
| June | 0.00 | 0.106948E+10 | 0.00 | 1337102.86 | 0.00 | 0.00 | 60170348.83 | 0.00 | 0.36 |
| July | 0.00 | 0.154671E+10 | 0.00 | 443172.49 | 0.00 | 0.00 | 27421486.65 | 0.00 | 0.36 |
| August | 0.00 | 0.139960E+10 | 0.00 | 435281.96 | 0.00 | 0.00 | 19216736.24 | 0.00 | 0.36 |
| September | 0.00 | 0.105713E+10 | 0.00 | 884032.19 | 0.00 | 0.00 | 47731954.68 | 0.00 | 0.36 |
| October | 0.316818E+09 | 0.299115E+09 | 0.00 | 2243914.89 | 0.00 | 0.00 | 0.420175E+09 | 0.00 | 0.35 |
| November | 0.883709E+09 | 25114188.66 | 0.00 | 1266343.15 | 0.00 | 0.00 | 0.360893E+09 | 0.00 | 0.35 |
| December | 0.159680E+10 | 2857357.49 | 0.00 | 171975.39 | 2065351.24 | 18060118.31 | 62159689.04 | 0.00 | 0.35 |
| Annual Sum or Average | 0.628418E+10 | 0.632491E+10 | 0.00 | 14633818.72 | 2770426.46 | 18060118.31 | 0.242977E+10 | 0.00 | 0.35 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 171975.39 | 0.00 | 0.00 | 19216736.24 | 0.00 | 0.35 |
| Maximum of Months | 0.159680E+10 | 0.154671E+10 | 0.00 | 2821555.00 | 2065351.24 | 18060118.31 | 0.454298E+09 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: M S1 APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.527777E+09 | 11652933.70 | 0.00 | 6120868.52 | 0.00 | 0.00 | 0.929192E+09 | 0.00 | 0.35 |
| February | 0.721597E+09 | 45064.90 | 0.00 | 3420300.89 | 0.00 | 0.00 | 0.861566E+09 | 0.00 | 0.36 |
| March | 0.663717E+09 | 29712151.87 | 0.00 | 3247661.15 | 0.00 | 0.00 | 0.698221E+09 | 0.00 | 0.35 |
| April | 15889230.42 | 0.328729E+09 | 0.00 | 3431265.11 | 0.00 | 0.00 | 0.479662E+09 | 0.00 | 0.35 |
| May | 844337.54 | 0.566204E+09 | 0.00 | 2765566.52 | 0.00 | 0.00 | 0.274816E+09 | 0.00 | 0.35 |
| June | 0.00 | 0.107625E+10 | 0.00 | 1267108.91 | 0.00 | 0.00 | 60368280.06 | 0.00 | 0.36 |
| July | 0.00 | 0.154473E+10 | 0.00 | 430343.76 | 0.00 | 0.00 | 27536078.95 | 0.00 | 0.36 |
| August | 0.00 | 0.141450E+10 | 0.00 | 448266.70 | 0.00 | 0.00 | 18929798.41 | 0.00 | 0.36 |
| September | 0.00 | 0.108822E+10 | 0.00 | 975907.10 | 0.00 | 0.00 | 46202480.45 | 0.00 | 0.36 |
| October | 0.113182E+09 | 0.306965E+09 | 0.00 | 4576696.81 | 0.00 | 0.00 | 0.631626E+09 | 0.00 | 0.35 |
| November | 0.398872E+09 | 28725140.28 | 0.00 | 5705774.94 | 0.00 | 0.00 | 0.890979E+09 | 0.00 | 0.35 |
| December | 0.104981E+10 | 4300097.68 | 0.00 | 4500534.71 | 0.00 | 0.00 | 0.825489E+09 | 0.00 | 0.35 |
| Annual Sum or Average | 0.349169E+10 | 0.640004E+10 | 0.00 | 36890295.10 | 0.00 | 0.00 | 0.574459E+10 | 0.00 | 0.35 |
| Minimum of Months | 0.00 | 45064.90 | 0.00 | 430343.76 | 0.00 | 0.00 | 18929798.41 | 0.00 | 0.35 |
| Maximum of Months | 0.104981E+10 | 0.154473E+10 | 0.00 | 6120868.52 | 0.00 | 0.00 | 0.929192E+09 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: M S2 APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.529069E+09 | 11648555.92 | 0.00 | 6119814.26 | 0.00 | 0.00 | 0.927814E+09 | 0.00 | 0.35 |
| February | 0.718598E+09 | 45051.61 | 0.00 | 3445653.54 | 0.00 | 0.00 | 0.864532E+09 | 0.00 | 0.36 |
| March | 0.661097E+09 | 29707580.49 | 0.00 | 3269888.83 | 0.00 | 0.00 | 0.701163E+09 | 0.00 | 0.35 |
| April | 15779154.39 | 0.328696E+09 | 0.00 | 3434937.57 | 0.00 | 0.00 | 0.479794E+09 | 0.00 | 0.35 |
| May | 844245.85 | 0.566151E+09 | 0.00 | 2767046.44 | 0.00 | 0.00 | 0.274824E+09 | 0.00 | 0.35 |
| June | 0.00 | 0.107621E+10 | 0.00 | 1266238.52 | 0.00 | 0.00 | 60374048.32 | 0.00 | 0.36 |
| July | 0.00 | 0.154514E+10 | 0.00 | 429843.45 | 0.00 | 0.00 | 27533911.04 | 0.00 | 0.36 |
| August | 0.00 | 0.141498E+10 | 0.00 | 447710.83 | 0.00 | 0.00 | 18922325.83 | 0.00 | 0.36 |
| September | 0.00 | 0.108851E+10 | 0.00 | 975762.11 | 0.00 | 0.00 | 46209968.05 | 0.00 | 0.36 |
| October | 0.113420E+09 | 0.307022E+09 | 0.00 | 4585176.72 | 0.00 | 0.00 | 0.631396E+09 | 0.00 | 0.35 |
| November | 0.401051E+09 | 28721416.41 | 0.00 | 5703530.80 | 0.00 | 0.00 | 0.889005E+09 | 0.00 | 0.35 |
| December | 0.104895E+10 | 4299848.16 | 0.00 | 4516664.63 | 0.00 | 0.00 | 0.826555E+09 | 0.00 | 0.35 |
| Annual Sum or Average | 0.348881E+10 | 0.640113E+10 | 0.00 | 36962267.69 | 0.00 | 0.00 | 0.574812E+10 | 0.00 | 0.35 |
| Minimum of Months | 0.00 | 45051.61 | 0.00 | 429843.45 | 0.00 | 0.00 | 18922325.83 | 0.00 | 0.35 |
| Maximum of Months | 0.104895E+10 | 0.154514E+10 | 0.00 | 6119814.26 | 0.00 | 0.00 | 0.927814E+09 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: T SW APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.293380E+09 | 6867116.83 | 0.00 | 1699232.15 | 0.00 | 0.203697E+09 | 0.116501E+09 | 0.00 | 0.35 |
| February | 0.325781E+09 | 0.00 | 0.00 | 733118.02 | 86660.92 | 0.229161E+09 | 0.102990E+09 | 0.00 | 0.35 |
| March | 0.293212E+09 | 15632612.84 | 0.00 | 885695.71 | 62670.53 | 0.196097E+09 | 79500195.59 | 0.00 | 0.35 |
| April | 0.133072E+09 | 0.171777E+09 | 0.00 | 716004.17 | 7298.75 | 3299339.61 | 78768502.70 | 0.00 | 0.35 |
| May | 51932984.10 | 0.293376E+09 | 0.00 | 599719.92 | 6220.96 | 0.00 | 72760292.80 | 0.00 | 0.35 |
| June | 677439.31 | 0.551973E+09 | 0.00 | 423212.20 | 0.00 | 0.00 | 25725747.33 | 0.00 | 0.36 |
| July | 989175.59 | 0.773235E+09 | 0.00 | 125162.11 | 0.00 | 0.00 | 11750060.88 | 0.00 | 0.36 |
| August | 867046.56 | 0.700498E+09 | 0.00 | 167885.95 | 0.00 | 0.00 | 10783012.01 | 0.00 | 0.36 |
| September | 6597677.16 | 0.530145E+09 | 0.00 | 263554.95 | 0.00 | 0.00 | 20512069.63 | 0.00 | 0.36 |
| October | 0.192378E+09 | 0.153179E+09 | 0.00 | 1056100.53 | 2844.74 | 44385192.23 | 80992971.41 | 0.00 | 0.35 |
| November | 0.294761E+09 | 14445888.91 | 0.00 | 1340063.00 | 0.00 | 0.152996E+09 | 0.115229E+09 | 0.00 | 0.35 |
| December | 0.294623E+09 | 2165174.68 | 0.00 | 1175709.15 | 420829.49 | 0.397515E+09 | 0.116950E+09 | 0.00 | 0.35 |
| Annual Sum or Average | 0.188827E+10 | 0.321329E+10 | 0.00 | 9185457.84 | 586525.39 | 0.122715E+10 | 0.832463E+09 | 0.00 | 0.35 |
| Minimum of Months | 677439.31 | 0.00 | 0.00 | 125162.11 | 0.00 | 0.00 | 10783012.01 | 0.00 | 0.35 |
| Maximum of Months | 0.325781E+09 | 0.773235E+09 | 0.00 | 1699232.15 | 420829.49 | 0.397515E+09 | 0.116950E+09 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: T NW APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.233126E+09 | 6052608.54 | 0.00 | 219038.00 | 1026209.03 | 0.320749E+09 | 17528455.24 | 0.00 | 0.35 |
| February | 0.273974E+09 | 0.00 | 0.00 | 24917.66 | 135404.52 | 0.333849E+09 | 6036970.64 | 0.00 | 0.35 |
| March | 0.271578E+09 | 14432440.64 | 0.00 | 346998.02 | 255222.56 | 0.242602E+09 | 32724165.55 | 0.00 | 0.35 |
| April | 0.139624E+09 | 0.171495E+09 | 0.00 | 586324.12 | 167953.98 | 3570329.78 | 69583853.62 | 0.00 | 0.35 |
| May | 50777224.61 | 0.291230E+09 | 0.00 | 628238.11 | 0.00 | 0.00 | 73964679.24 | 0.00 | 0.35 |
| June | 70756.35 | 0.549441E+09 | 0.00 | 453075.97 | 0.00 | 0.00 | 26349089.26 | 0.00 | 0.36 |
| July | 590591.99 | 0.775025E+09 | 0.00 | 135817.72 | 0.00 | 0.00 | 12137369.68 | 0.00 | 0.36 |
| August | 752247.18 | 0.696002E+09 | 0.00 | 164803.86 | 0.00 | 0.00 | 11053501.99 | 0.00 | 0.36 |
| September | 6792824.72 | 0.519729E+09 | 0.00 | 242342.99 | 0.00 | 0.00 | 20855099.83 | 0.00 | 0.36 |
| October | 0.177831E+09 | 0.150071E+09 | 0.00 | 446083.10 | 640919.20 | 79025822.94 | 44125938.29 | 0.00 | 0.35 |
| November | 0.267042E+09 | 12818778.73 | 0.00 | 194110.53 | 289436.23 | 0.237284E+09 | 22483359.47 | 0.00 | 0.35 |
| December | 0.207749E+09 | 1733298.73 | 0.00 | 75918.00 | 1583993.80 | 0.540969E+09 | 5791547.44 | 0.00 | 0.35 |
| Annual Sum or Average | 0.162991E+10 | 0.318803E+10 | 0.00 | 3517668.09 | 4099139.32 | 0.175805E+10 | 0.342634E+09 | 0.00 | 0.35 |
| Minimum of Months | 70756.35 | 0.00 | 0.00 | 24917.66 | 0.00 | 0.00 | 5791547.44 | 0.00 | 0.35 |
| Maximum of Months | 0.273974E+09 | 0.775025E+09 | 0.00 | 628238.11 | 1583993.80 | 0.540969E+09 | 73964679.24 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: T SE APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.300281E+09 | 6806414.39 | 0.00 | 1588589.74 | 0.00 | 0.198181E+09 | 0.119014E+09 | 0.00 | 0.35 |
| February | 0.328324E+09 | 0.00 | 0.00 | 684699.40 | 92206.99 | 0.217990E+09 | 0.116593E+09 | 0.00 | 0.35 |
| March | 0.301501E+09 | 15592093.45 | 0.00 | 847062.02 | 1420.29 | 0.186901E+09 | 85930865.29 | 0.00 | 0.35 |
| April | 0.135083E+09 | 0.171129E+09 | 0.00 | 831150.24 | 0.00 | 2234316.62 | 80455786.67 | 0.00 | 0.35 |
| May | 50710134.91 | 0.292131E+09 | 0.00 | 760687.94 | 0.00 | 0.00 | 74738817.45 | 0.00 | 0.35 |
| June | 617351.49 | 0.551088E+09 | 0.00 | 460815.62 | 0.00 | 0.00 | 25804237.06 | 0.00 | 0.36 |
| July | 633301.53 | 0.779685E+09 | 0.00 | 137044.58 | 0.00 | 0.00 | 12101988.48 | 0.00 | 0.36 |
| August | 723950.01 | 0.708723E+09 | 0.00 | 179842.96 | 0.00 | 0.00 | 10840868.57 | 0.00 | 0.36 |
| September | 6093081.31 | 0.536607E+09 | 0.00 | 282689.68 | 0.00 | 0.00 | 21075545.32 | 0.00 | 0.36 |
| October | 0.193678E+09 | 0.154406E+09 | 0.00 | 1080147.40 | 0.00 | 41210348.47 | 85491626.96 | 0.00 | 0.35 |
| November | 0.306921E+09 | 14485086.87 | 0.00 | 1236500.72 | 0.00 | 0.146974E+09 | 0.112214E+09 | 0.00 | 0.35 |
| December | 0.305813E+09 | 2157634.37 | 0.00 | 1077410.87 | 420681.73 | 0.388420E+09 | 0.118325E+09 | 0.00 | 0.35 |
| Annual Sum or Average | 0.193038E+10 | 0.323281E+10 | 0.00 | 9166641.15 | 514309.01 | 0.118191E+10 | 0.862587E+09 | 0.00 | 0.35 |
| Minimum of Months | 617351.49 | 0.00 | 0.00 | 137044.58 | 0.00 | 0.00 | 10840868.57 | 0.00 | 0.35 |
| Maximum of Months | 0.328324E+09 | 0.779685E+09 | 0.00 | 1588589.74 | 420681.73 | 0.388420E+09 | 0.119014E+09 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: T NE APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.251882E+09 | 6486775.78 | 0.00 | 108053.31 | 68090.01 | 0.309858E+09 | 10247094.88 | 0.00 | 0.35 |
| February | 0.301991E+09 | 0.00 | 0.00 | 5343.61 | 146443.80 | 0.310874E+09 | 3037423.97 | 0.00 | 0.35 |
| March | 0.293171E+09 | 14486066.03 | 0.00 | 296780.87 | 11861.03 | 0.226647E+09 | 32196987.14 | 0.00 | 0.35 |
| April | 0.141951E+09 | 0.170991E+09 | 0.00 | 674651.42 | 0.00 | 2465928.71 | 71201516.34 | 0.00 | 0.35 |
| May | 49876425.05 | 0.290072E+09 | 0.00 | 812171.41 | 0.00 | 0.00 | 75349031.19 | 0.00 | 0.35 |
| June | 115879.30 | 0.548663E+09 | 0.00 | 487384.97 | 0.00 | 0.00 | 26310601.25 | 0.00 | 0.36 |
| July | 343119.34 | 0.781243E+09 | 0.00 | 147575.07 | 0.00 | 0.00 | 12371196.12 | 0.00 | 0.36 |
| August | 697964.07 | 0.704592E+09 | 0.00 | 177651.58 | 0.00 | 0.00 | 11021047.13 | 0.00 | 0.36 |
| September | 6308632.57 | 0.527174E+09 | 0.00 | 265835.30 | 0.00 | 0.00 | 21384874.22 | 0.00 | 0.36 |
| October | 0.191307E+09 | 0.151939E+09 | 0.00 | 426565.23 | 7214.35 | 68106643.09 | 44855556.66 | 0.00 | 0.35 |
| November | 0.279724E+09 | 12994803.43 | 0.00 | 109488.05 | 26192.30 | 0.229845E+09 | 16920747.70 | 0.00 | 0.35 |
| December | 0.215906E+09 | 1984963.25 | 0.00 | 36422.97 | 616659.09 | 0.532940E+09 | 3397555.92 | 0.00 | 0.35 |
| Annual Sum or Average | 0.173327E+10 | 0.321063E+10 | 0.00 | 3547923.78 | 876460.58 | 0.168074E+10 | 0.328294E+09 | 0.00 | 0.35 |
| Minimum of Months | 115879.30 | 0.00 | 0.00 | 5343.61 | 0.00 | 0.00 | 3037423.97 | 0.00 | 0.35 |
| Maximum of Months | 0.301991E+09 | 0.781243E+09 | 0.00 | 812171.41 | 616659.09 | 0.532940E+09 | 75349031.19 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: T N1 APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.357945E+09 | 5391933.08 | 0.00 | 78702.94 | 959439.84 | 0.216730E+09 | 9617025.82 | 0.00 | 0.35 |
| February | 0.398916E+09 | 0.00 | 0.00 | 1079.37 | 122511.72 | 0.224326E+09 | 628074.11 | 0.00 | 0.35 |
| March | 0.375094E+09 | 13730990.48 | 0.00 | 244632.09 | 141602.48 | 0.157907E+09 | 33714361.43 | 0.00 | 0.35 |
| April | 0.134686E+09 | 0.166523E+09 | 0.00 | 592189.97 | 41664.67 | 0.00 | 92519384.52 | 0.00 | 0.35 |
| May | 40443864.15 | 0.283800E+09 | 0.00 | 713848.11 | 0.00 | 0.00 | 91888922.38 | 0.00 | 0.35 |
| June | 0.00 | 0.539228E+09 | 0.00 | 472095.13 | 0.00 | 0.00 | 28983925.27 | 0.00 | 0.36 |
| July | 0.00 | 0.775380E+09 | 0.00 | 149942.66 | 0.00 | 0.00 | 13601005.55 | 0.00 | 0.36 |
| August | 0.00 | 0.697595E+09 | 0.00 | 174585.36 | 0.00 | 0.00 | 11220760.60 | 0.00 | 0.36 |
| September | 2941071.73 | 0.522155E+09 | 0.00 | 289827.38 | 0.00 | 0.00 | 24443894.84 | 0.00 | 0.36 |
| October | 0.229398E+09 | 0.148867E+09 | 0.00 | 415301.16 | 257902.28 | 29553773.04 | 58073515.22 | 0.00 | 0.35 |
| November | 0.352305E+09 | 12281848.54 | 0.00 | 110781.58 | 173794.08 | 0.166520E+09 | 24411542.77 | 0.00 | 0.35 |
| December | 0.303966E+09 | 1615486.69 | 0.00 | 24949.98 | 1418779.94 | 0.454975E+09 | 3415837.09 | 0.00 | 0.35 |
| Annual Sum or Average | 0.219570E+10 | 0.316657E+10 | 0.00 | 3267935.72 | 3115695.01 | 0.125001E+10 | 0.392518E+09 | 0.00 | 0.35 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 1079.37 | 0.00 | 0.00 | 628074.11 | 0.00 | 0.35 |
| Maximum of Months | 0.398916E+09 | 0.775380E+09 | 0.00 | 713848.11 | 1418779.94 | 0.454975E+09 | 92519384.52 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: T N2 APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.357475E+09 | 5497326.88 | 0.00 | 78421.44 | 781840.34 | 0.217149E+09 | 9623936.68 | 0.00 | 0.35 |
| February | 0.400392E+09 | 0.00 | 0.00 | 1236.01 | 123047.50 | 0.223309E+09 | 679469.66 | 0.00 | 0.35 |
| March | 0.376469E+09 | 13780417.98 | 0.00 | 247974.26 | 78734.51 | 0.156460E+09 | 34264978.02 | 0.00 | 0.35 |
| April | 0.134680E+09 | 0.166491E+09 | 0.00 | 593697.68 | 37698.11 | 0.00 | 92556410.08 | 0.00 | 0.35 |
| May | 40758111.26 | 0.283750E+09 | 0.00 | 715744.79 | 0.00 | 0.00 | 91557234.97 | 0.00 | 0.35 |
| June | 0.00 | 0.539190E+09 | 0.00 | 471382.25 | 0.00 | 0.00 | 28987286.95 | 0.00 | 0.36 |
| July | 0.00 | 0.775580E+09 | 0.00 | 149658.85 | 0.00 | 0.00 | 13601513.41 | 0.00 | 0.36 |
| August | 0.00 | 0.697902E+09 | 0.00 | 174380.55 | 0.00 | 0.00 | 11222097.99 | 0.00 | 0.36 |
| September | 3028167.85 | 0.522410E+09 | 0.00 | 289849.97 | 0.00 | 0.00 | 24366350.34 | 0.00 | 0.36 |
| October | 0.229407E+09 | 0.148978E+09 | 0.00 | 416464.03 | 184535.25 | 29607987.56 | 58227334.26 | 0.00 | 0.35 |
| November | 0.351991E+09 | 12307507.68 | 0.00 | 110009.16 | 131070.68 | 0.167144E+09 | 23949297.14 | 0.00 | 0.35 |
| December | 0.303441E+09 | 1634790.62 | 0.00 | 24526.45 | 1337520.27 | 0.455649E+09 | 3244707.90 | 0.00 | 0.35 |
| Annual Sum or Average | 0.219764E+10 | 0.316752E+10 | 0.00 | 3273345.43 | 2674446.65 | 0.124932E+10 | 0.392281E+09 | 0.00 | 0.35 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 1236.01 | 0.00 | 0.00 | 679469.66 | 0.00 | 0.35 |
| Maximum of Months | 0.400392E+09 | 0.775580E+09 | 0.00 | 715744.79 | 1337520.27 | 0.455649E+09 | 92556410.08 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: T S1 APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.436327E+09 | 6340690.09 | 0.00 | 1669080.40 | 0.00 | 56556242.62 | 0.148507E+09 | 0.00 | 0.35 |
| February | 0.465648E+09 | 0.00 | 0.00 | 719085.68 | 64097.40 | 84881046.66 | 0.133708E+09 | 0.00 | 0.35 |
| March | 0.393883E+09 | 15203004.84 | 0.00 | 791055.69 | 0.00 | 0.101102E+09 | 0.101350E+09 | 0.00 | 0.35 |
| April | 0.125079E+09 | 0.166973E+09 | 0.00 | 757169.98 | 0.00 | 0.00 | 0.104498E+09 | 0.00 | 0.35 |
| May | 42830034.00 | 0.286525E+09 | 0.00 | 672395.20 | 0.00 | 0.00 | 89644859.22 | 0.00 | 0.35 |
| June | 39820.95 | 0.542365E+09 | 0.00 | 437705.91 | 0.00 | 0.00 | 28979548.58 | 0.00 | 0.36 |
| July | 148993.31 | 0.773578E+09 | 0.00 | 137896.09 | 0.00 | 0.00 | 13485909.18 | 0.00 | 0.36 |
| August | 0.00 | 0.703121E+09 | 0.00 | 177502.01 | 0.00 | 0.00 | 11084229.23 | 0.00 | 0.36 |
| September | 3330713.81 | 0.534640E+09 | 0.00 | 307271.51 | 0.00 | 0.00 | 23493268.21 | 0.00 | 0.36 |
| October | 0.217455E+09 | 0.152286E+09 | 0.00 | 1101121.18 | 0.00 | 3902231.82 | 0.115475E+09 | 0.00 | 0.35 |
| November | 0.384982E+09 | 14095730.98 | 0.00 | 1376457.56 | 0.00 | 45575965.88 | 0.159104E+09 | 0.00 | 0.35 |
| December | 0.449731E+09 | 2098904.08 | 0.00 | 1202000.06 | 402156.63 | 0.233755E+09 | 0.150800E+09 | 0.00 | 0.35 |
| Annual Sum or Average | 0.251946E+10 | 0.319723E+10 | 0.00 | 9348741.27 | 466254.04 | 0.525772E+09 | 0.108013E+10 | 0.00 | 0.35 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 137896.09 | 0.00 | 0.00 | 11084229.23 | 0.00 | 0.35 |
| Maximum of Months | 0.465648E+09 | 0.773578E+09 | 0.00 | 1669080.40 | 402156.63 | 0.233755E+09 | 0.159104E+09 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: T S2 APARTMENT
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.434518E+09 | 6334677.23 | 0.00 | 1673488.29 | 0.00 | 58064847.84 | 0.148790E+09 | 0.00 | 0.35 |
| February | 0.464340E+09 | 0.00 | 0.00 | 728884.50 | 64483.12 | 84866058.49 | 0.135320E+09 | 0.00 | 0.35 |
| March | 0.392182E+09 | 15197838.15 | 0.00 | 799715.89 | 0.00 | 0.102026E+09 | 0.102390E+09 | 0.00 | 0.35 |
| April | 0.125306E+09 | 0.166940E+09 | 0.00 | 759452.21 | 0.00 | 0.00 | 0.104282E+09 | 0.00 | 0.35 |
| May | 43201114.33 | 0.286470E+09 | 0.00 | 674236.91 | 0.00 | 0.00 | 89262049.67 | 0.00 | 0.35 |
| June | 39806.06 | 0.542323E+09 | 0.00 | 437041.13 | 0.00 | 0.00 | 28982919.46 | 0.00 | 0.36 |
| July | 148935.14 | 0.773783E+09 | 0.00 | 137592.14 | 0.00 | 0.00 | 13486285.39 | 0.00 | 0.36 |
| August | 0.00 | 0.703404E+09 | 0.00 | 177361.81 | 0.00 | 0.00 | 11085460.87 | 0.00 | 0.36 |
| September | 3330915.83 | 0.534835E+09 | 0.00 | 307403.45 | 0.00 | 0.00 | 23501155.46 | 0.00 | 0.36 |
| October | 0.217461E+09 | 0.152322E+09 | 0.00 | 1105649.68 | 0.00 | 3902186.43 | 0.115515E+09 | 0.00 | 0.35 |
| November | 0.384917E+09 | 14094894.52 | 0.00 | 1376581.31 | 0.00 | 45829649.59 | 0.158923E+09 | 0.00 | 0.35 |
| December | 0.450635E+09 | 2098701.08 | 0.00 | 1207638.58 | 403361.79 | 0.233374E+09 | 0.150353E+09 | 0.00 | 0.35 |
| Annual Sum or Average | 0.251608E+10 | 0.319780E+10 | 0.00 | 9385045.93 | 467844.91 | 0.528063E+09 | 0.108189E+10 | 0.00 | 0.35 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 137592.14 | 0.00 | 0.00 | 11085460.87 | 0.00 | 0.35 |
| Maximum of Months | 0.464340E+09 | 0.773783E+09 | 0.00 | 1673488.29 | 403361.79 | 0.233374E+09 | 0.158923E+09 | 0.00 | 0.36 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 09:17:08
Custom Monthly Report| SITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
| January | 0.106139E+12 | 0.124024E+11 | 0.00 | 0.117253E+10 | 0.303451E+11 |
| February | 0.105392E+12 | 0.113662E+11 | 0.00 | 0.115160E+10 | 0.810831E+10 |
| March | 0.125418E+12 | 0.130814E+11 | 0.00 | 0.104404E+10 | 0.231397E+11 |
| April | 0.136437E+12 | 0.322490E+10 | 0.00 | 0.411818E+09 | 0.102755E+12 |
| May | 0.123877E+12 | -871520711.2 | 0.00 | 0.140110E+09 | 0.137505E+12 |
| June | 0.126804E+12 | -0.670051E+10 | 0.00 | -336779455.3 | 0.195817E+12 |
| July | 0.123691E+12 | -0.918949E+10 | 0.00 | -425341859.0 | 0.210907E+12 |
| August | 0.111765E+12 | -0.687011E+10 | 0.00 | -381383440.6 | 0.200188E+12 |
| September | 0.103090E+12 | -0.505355E+10 | 0.00 | -122443522.8 | 0.175457E+12 |
| October | 0.106912E+12 | 0.663200E+10 | 0.00 | 0.686209E+09 | 0.917633E+11 |
| November | 0.104529E+12 | 0.124465E+11 | 0.00 | 0.112435E+10 | 0.355770E+11 |
| December | 0.884526E+11 | 0.121204E+11 | 0.00 | 0.146934E+10 | 0.181807E+11 |
| Annual Sum or Average | 0.136251E+13 | 0.425887E+11 | 0.00 | 0.593404E+10 | 0.122974E+13 |
| Minimum of Months | 0.884526E+11 | -0.918949E+10 | 0.00 | -425341859.0 | 0.810831E+10 |
| Maximum of Months | 0.136437E+12 | 0.130814E+11 | 0.00 | 0.146934E+10 | 0.210907E+12 |