Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 09:14
Tabular Output Report in Format: HTML
Building: ApartmentMidRise
Environment: RUNPERIOD 1 ** New York-John F Kennedy Intl AP NY USA TMY3 WMO#=744860
Simulation Timestamp: 2023-10-16 09:15:04
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 09:15:04
Values gathered over 8760.00 hours| Total Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
| Total Site Energy | 1670.86 | 533.03 | 591.67 |
| Net Site Energy | 1670.86 | 533.03 | 591.67 |
| Total Source Energy | 4502.41 | 1436.35 | 1594.35 |
| Net Source Energy | 4502.41 | 1436.35 | 1594.35 |
| Site=>Source Conversion Factor | |
| Electricity | 3.167 |
| Natural Gas | 1.084 |
| District Cooling | 1.056 |
| District Heating | 3.613 |
| Steam | 1.200 |
| Gasoline | 1.050 |
| Diesel | 1.050 |
| Coal | 1.050 |
| Fuel Oil No 1 | 1.050 |
| Fuel Oil No 2 | 1.050 |
| Propane | 1.050 |
| Other Fuel 1 | 1.000 |
| Other Fuel 2 | 1.000 |
| Area [m2] | |
| Total Building Area | 3134.61 |
| Net Conditioned Building Area | 2823.98 |
| Unconditioned Building Area | 310.64 |
| Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
| Heating | 0.00 | 378.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Cooling | 129.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Lighting | 99.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Lighting | 49.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment | 458.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans | 101.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems | 452.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1875.32 |
| Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Total End Uses | 1291.98 | 378.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1875.32 |
| Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
| Heating | General | 0.00 | 378.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Cooling | General | 129.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Lighting | LightsWired | 94.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LightsPlugIn | 4.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Exterior Lighting | General | 49.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment | MiscPlug | 388.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| ElevatorLift | 65.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| ElevatorLightsFan | 5.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| General | 101.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems | Water Heater | 452.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1875.32 |
| Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
| Heating | Unassigned | 0.00 | 378.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Cooling | Unassigned | 129.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Lighting | GENERAL | 99.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Lighting | Unassigned | 49.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment | GENERAL | 458.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans | Unassigned | 101.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Pumps | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems | Unassigned | 452.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1875.32 |
| Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
| Lighting | 52.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| HVAC | 242.25 | 134.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.66 |
| Other | 162.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Total | 457.50 | 134.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.66 |
| Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
| Lighting | 47.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| HVAC | 218.25 | 120.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.60 |
| Other | 146.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Total | 412.17 | 120.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.60 |
| Electricity [GJ] | Percent Electricity [%] | |
| Fuel-Fired Power Generation | 0.000 | 0.00 |
| High Temperature Geothermal* | 0.000 | 0.00 |
| Photovoltaic Power | 0.000 | 0.00 |
| Wind Power | 0.000 | 0.00 |
| Power Conversion | 0.000 | 0.00 |
| Net Decrease in On-Site Storage | 0.000 | 0.00 |
| Total On-Site Electric Sources | 0.000 | 0.00 |
| Electricity Coming From Utility | 1291.982 | 100.00 |
| Surplus Electricity Going To Utility | 0.000 | 0.00 |
| Net Electricity From Utility | 1291.982 | 100.00 |
| Total On-Site and Utility Electric Sources | 1291.982 | 100.00 |
| Total Electricity End Uses | 1291.982 | 100.00 |
| Heat [GJ] | Percent Heat [%] | |
| Water-Side Heat Recovery | 0.00 | 0.00 |
| Air to Air Heat Recovery for Cooling | 0.00 | 49.44 |
| Air to Air Heat Recovery for Heating | 0.00 | 50.56 |
| High-Temperature Geothermal* | 0.00 | 0.00 |
| Solar Water Thermal | 0.00 | 0.00 |
| Solar Air Thermal | 0.00 | 0.00 |
| Total On-Site Thermal Sources | 0.00 | 100.00 |
| Water [m3] | Percent Water [%] | |
| Rainwater Collection | 0.00 | 0.00 |
| Condensate Collection | 0.00 | 0.00 |
| Groundwater Well | 0.00 | 0.00 |
| Total On Site Water Sources | 0.00 | 0.00 |
| - | - | - |
| Initial Storage | 0.00 | 0.00 |
| Final Storage | 0.00 | 0.00 |
| Change in Storage | 0.00 | 0.00 |
| - | - | - |
| Water Supplied by Utility | 1875.32 | 100.00 |
| - | - | - |
| Total On Site, Change in Storage, and Utility Water Sources | 1875.32 | 100.00 |
| Total Water End Uses | 1875.32 | 100.00 |
| Degrees [deltaC] | |
| Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
| Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
| Facility [Hours] | |
| Time Setpoint Not Met During Occupied Heating | 0.00 |
| Time Setpoint Not Met During Occupied Cooling | 0.00 |
| Time Not Comfortable Based on Simple ASHRAE 55-2004 | 8699.00 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2012
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME APARTMENTMIDRISE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4A
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NY_NEWYORK
| Environment |ZoneCoolingSummaryMonthly
| G SW APARTMENT | G NW APARTMENT | OFFICE | G NE APARTMENT | G N1 APARTMENT | G N2 APARTMENT | G S1 APARTMENT | G S2 APARTMENT | M SW APARTMENT | M NW APARTMENT | M SE APARTMENT | M NE APARTMENT | M N1 APARTMENT | M N2 APARTMENT | M S1 APARTMENT | M S2 APARTMENT | T SW APARTMENT | T NW APARTMENT | T SE APARTMENT | T NE APARTMENT | T N1 APARTMENT | T N2 APARTMENT | T S1 APARTMENT | T S2 APARTMENT | T CORRIDOR | G CORRIDOR | M CORRIDOR |ZoneHeatingSummaryMonthly
| G SW APARTMENT | G NW APARTMENT | OFFICE | G NE APARTMENT | G N1 APARTMENT | G N2 APARTMENT | G S1 APARTMENT | G S2 APARTMENT | M SW APARTMENT | M NW APARTMENT | M SE APARTMENT | M NE APARTMENT | M N1 APARTMENT | M N2 APARTMENT | M S1 APARTMENT | M S2 APARTMENT | T SW APARTMENT | T NW APARTMENT | T SE APARTMENT | T NE APARTMENT | T N1 APARTMENT | T N2 APARTMENT | T S1 APARTMENT | T S2 APARTMENT | T CORRIDOR | G CORRIDOR | M CORRIDOR |ZoneElectricSummaryMonthly
| G SW APARTMENT | G NW APARTMENT | OFFICE | G NE APARTMENT | G N1 APARTMENT | G N2 APARTMENT | G S1 APARTMENT | G S2 APARTMENT | M SW APARTMENT | M NW APARTMENT | M SE APARTMENT | M NE APARTMENT | M N1 APARTMENT | M N2 APARTMENT | M S1 APARTMENT | M S2 APARTMENT | T SW APARTMENT | T NW APARTMENT | T SE APARTMENT | T NE APARTMENT | T N1 APARTMENT | T N2 APARTMENT | T S1 APARTMENT | T S2 APARTMENT | T CORRIDOR | G CORRIDOR | M CORRIDOR |SpaceGainsMonthly
| G SW APARTMENT | G NW APARTMENT | OFFICE | G NE APARTMENT | G N1 APARTMENT | G N2 APARTMENT | G S1 APARTMENT | G S2 APARTMENT | M SW APARTMENT | M NW APARTMENT | M SE APARTMENT | M NE APARTMENT | M N1 APARTMENT | M N2 APARTMENT | M S1 APARTMENT | M S2 APARTMENT | T SW APARTMENT | T NW APARTMENT | T SE APARTMENT | T NE APARTMENT | T N1 APARTMENT | T N2 APARTMENT | T S1 APARTMENT | T S2 APARTMENT | T CORRIDOR | G CORRIDOR | M CORRIDOR |PeakSpaceGainsMonthly
| G SW APARTMENT | G NW APARTMENT | OFFICE | G NE APARTMENT | G N1 APARTMENT | G N2 APARTMENT | G S1 APARTMENT | G S2 APARTMENT | M SW APARTMENT | M NW APARTMENT | M SE APARTMENT | M NE APARTMENT | M N1 APARTMENT | M N2 APARTMENT | M S1 APARTMENT | M S2 APARTMENT | T SW APARTMENT | T NW APARTMENT | T SE APARTMENT | T NE APARTMENT | T N1 APARTMENT | T N2 APARTMENT | T S1 APARTMENT | T S2 APARTMENT | T CORRIDOR | G CORRIDOR | M CORRIDOR |SpaceGainComponentsAtCoolingPeakMonthly
| G SW APARTMENT | G NW APARTMENT | OFFICE | G NE APARTMENT | G N1 APARTMENT | G N2 APARTMENT | G S1 APARTMENT | G S2 APARTMENT | M SW APARTMENT | M NW APARTMENT | M SE APARTMENT | M NE APARTMENT | M N1 APARTMENT | M N2 APARTMENT | M S1 APARTMENT | M S2 APARTMENT | T SW APARTMENT | T NW APARTMENT | T SE APARTMENT | T NE APARTMENT | T N1 APARTMENT | T N2 APARTMENT | T S1 APARTMENT | T S2 APARTMENT | T CORRIDOR | G CORRIDOR | M CORRIDOR |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| G SW APARTMENT | G NW APARTMENT | OFFICE | G NE APARTMENT | G N1 APARTMENT | G N2 APARTMENT | G S1 APARTMENT | G S2 APARTMENT | M SW APARTMENT | M NW APARTMENT | M SE APARTMENT | M NE APARTMENT | M N1 APARTMENT | M N2 APARTMENT | M S1 APARTMENT | M S2 APARTMENT | T SW APARTMENT | T NW APARTMENT | T SE APARTMENT | T NE APARTMENT | T N1 APARTMENT | T N2 APARTMENT | T S1 APARTMENT | T S2 APARTMENT | T CORRIDOR | G CORRIDOR | M CORRIDOR |ComfortReportSimple55Monthly
| G SW APARTMENT | G NW APARTMENT | OFFICE | G NE APARTMENT | G N1 APARTMENT | G N2 APARTMENT | G S1 APARTMENT | G S2 APARTMENT | M SW APARTMENT | M NW APARTMENT | M SE APARTMENT | M NE APARTMENT | M N1 APARTMENT | M N2 APARTMENT | M S1 APARTMENT | M S2 APARTMENT | T SW APARTMENT | T NW APARTMENT | T SE APARTMENT | T NE APARTMENT | T N1 APARTMENT | T N2 APARTMENT | T S1 APARTMENT | T S2 APARTMENT | T CORRIDOR | G CORRIDOR | M CORRIDOR |OccupantComfortDataSummaryMonthly
| OCCUP_GSW | OCCUP_GNW | OCCUP_OFFICE | OCCUP_GNE | OCCUP_GN1 | OCCUP_GN2 | OCCUP_GS1 | OCCUP_GS2 | OCCUP_MSW | OCCUP_MNW | OCCUP_MSE | OCCUP_MNE | OCCUP_MN1 | OCCUP_MN2 | OCCUP_MS1 | OCCUP_MS2 | OCCUP_TSW | OCCUP_TNW | OCCUP_TSE | OCCUP_TNE | OCCUP_TN1 | OCCUP_TN2 | OCCUP_TS1 | OCCUP_TS2 | OCCUP_T CORRIDOR | OCCUP_G CORRIDOR | OCCUP_M CORRIDOR |DXReportMonthly
| SPLIT GSW COOLING COIL | SPLIT GNW COOLING COIL | SPLIT OFFICE COOLING COIL | SPLIT GNE COOLING COIL | SPLIT GN1 COOLING COIL | SPLIT GN2 COOLING COIL | SPLIT GS1 COOLING COIL | SPLIT GS2 COOLING COIL | SPLIT MSW COOLING COIL | SPLIT MNW COOLING COIL | SPLIT MSE COOLING COIL | SPLIT MNE COOLING COIL | SPLIT MN1 COOLING COIL | SPLIT MN2 COOLING COIL | SPLIT MS1 COOLING COIL | SPLIT MS2 COOLING COIL | SPLIT TSW COOLING COIL | SPLIT TNW COOLING COIL | SPLIT TSE COOLING COIL | SPLIT TNE COOLING COIL | SPLIT TN1 COOLING COIL | SPLIT TN2 COOLING COIL | SPLIT TS1 COOLING COIL | SPLIT TS2 COOLING COIL |WindowReportMonthly
| GWINDOW1 S SWA | GWINDOW1 W SWA | GWINDOW1 W NWA | GWINDOW1 N NWA | GWINDOW1 S SEA | GWINDOW1 E SEA | GWINDOW1 E NEA | GWINDOW1 N NEA | GWINDOW1 N N1A | GWINDOW1 N N2A | GWINDOW1 S S1A | GWINDOW1 S S2A | MWINDOW1 S SWA | MWINDOW1 W SWA | MWINDOW1 W NWA | MWINDOW1 N NWA | MWINDOW1 S SEA | MWINDOW1 E SEA | MWINDOW1 E NEA | MWINDOW1 N NEA | MWINDOW1 N N1A | MWINDOW1 N N2A | MWINDOW1 S S1A | MWINDOW1 S S2A | TWINDOW1 S SWA | TWINDOW1 W SWA | TWINDOW1 W NWA | TWINDOW1 N NWA | TWINDOW1 S SEA | TWINDOW1 E SEA | TWINDOW1 E NEA | TWINDOW1 N NEA | TWINDOW1 N N1A | TWINDOW1 N N2A | TWINDOW1 S S1A | TWINDOW1 S S2A | TWINDOW14 | ENTRANCE DOOR | MWINDOW14 |WindowEnergyReportMonthly
| GWINDOW1 S SWA | GWINDOW1 W SWA | GWINDOW1 W NWA | GWINDOW1 N NWA | GWINDOW1 S SEA | GWINDOW1 E SEA | GWINDOW1 E NEA | GWINDOW1 N NEA | GWINDOW1 N N1A | GWINDOW1 N N2A | GWINDOW1 S S1A | GWINDOW1 S S2A | MWINDOW1 S SWA | MWINDOW1 W SWA | MWINDOW1 W NWA | MWINDOW1 N NWA | MWINDOW1 S SEA | MWINDOW1 E SEA | MWINDOW1 E NEA | MWINDOW1 N NEA | MWINDOW1 N N1A | MWINDOW1 N N2A | MWINDOW1 S S1A | MWINDOW1 S S2A | TWINDOW1 S SWA | TWINDOW1 W SWA | TWINDOW1 W NWA | TWINDOW1 N NWA | TWINDOW1 S SEA | TWINDOW1 E SEA | TWINDOW1 E NEA | TWINDOW1 N NEA | TWINDOW1 N N1A | TWINDOW1 N N2A | TWINDOW1 S S1A | TWINDOW1 S S2A | TWINDOW14 | ENTRANCE DOOR | MWINDOW14 |WindowZoneSummaryMonthly
| G SW APARTMENT | G NW APARTMENT | OFFICE | G NE APARTMENT | G N1 APARTMENT | G N2 APARTMENT | G S1 APARTMENT | G S2 APARTMENT | M SW APARTMENT | M NW APARTMENT | M SE APARTMENT | M NE APARTMENT | M N1 APARTMENT | M N2 APARTMENT | M S1 APARTMENT | M S2 APARTMENT | T SW APARTMENT | T NW APARTMENT | T SE APARTMENT | T NE APARTMENT | T N1 APARTMENT | T N2 APARTMENT | T S1 APARTMENT | T S2 APARTMENT | T CORRIDOR | G CORRIDOR | M CORRIDOR |WindowEnergyZoneSummaryMonthly
| G SW APARTMENT | G NW APARTMENT | OFFICE | G NE APARTMENT | G N1 APARTMENT | G N2 APARTMENT | G S1 APARTMENT | G S2 APARTMENT | M SW APARTMENT | M NW APARTMENT | M SE APARTMENT | M NE APARTMENT | M N1 APARTMENT | M N2 APARTMENT | M S1 APARTMENT | M S2 APARTMENT | T SW APARTMENT | T NW APARTMENT | T SE APARTMENT | T NE APARTMENT | T N1 APARTMENT | T N2 APARTMENT | T S1 APARTMENT | T S2 APARTMENT | T CORRIDOR | G CORRIDOR | M CORRIDOR |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| G SW APARTMENT WATER HEATER | G NW APARTMENT WATER HEATER | G NE APARTMENT WATER HEATER | G N1 APARTMENT WATER HEATER | G N2 APARTMENT WATER HEATER | G S1 APARTMENT WATER HEATER | G S2 APARTMENT WATER HEATER | M SW APARTMENT WATER HEATER | M NW APARTMENT WATER HEATER | M SE APARTMENT WATER HEATER | M NE APARTMENT WATER HEATER | M N1 APARTMENT WATER HEATER | M N2 APARTMENT WATER HEATER | M S1 APARTMENT WATER HEATER | M S2 APARTMENT WATER HEATER | T SW APARTMENT WATER HEATER | T NW APARTMENT WATER HEATER | T SE APARTMENT WATER HEATER | T NE APARTMENT WATER HEATER | T N1 APARTMENT WATER HEATER | T N2 APARTMENT WATER HEATER | T S1 APARTMENT WATER HEATER | T S2 APARTMENT WATER HEATER |DaylightingReportMonthly
| Environment |CoilReportMonthly
| SPLIT GSW HEATING COIL | SPLIT GNW HEATING COIL | SPLIT OFFICE HEATING COIL | SPLIT GNE HEATING COIL | SPLIT GN1 HEATING COIL | SPLIT GN2 HEATING COIL | SPLIT GS1 HEATING COIL | SPLIT GS2 HEATING COIL | SPLIT MSW HEATING COIL | SPLIT MNW HEATING COIL | SPLIT MSE HEATING COIL | SPLIT MNE HEATING COIL | SPLIT MN1 HEATING COIL | SPLIT MN2 HEATING COIL | SPLIT MS1 HEATING COIL | SPLIT MS2 HEATING COIL | SPLIT TSW HEATING COIL | SPLIT TNW HEATING COIL | SPLIT TSE HEATING COIL | SPLIT TNE HEATING COIL | SPLIT TN1 HEATING COIL | SPLIT TN2 HEATING COIL | SPLIT TS1 HEATING COIL | SPLIT TS2 HEATING COIL | SPLIT GSW COOLING COIL | SPLIT GNW COOLING COIL | SPLIT OFFICE COOLING COIL | SPLIT GNE COOLING COIL | SPLIT GN1 COOLING COIL | SPLIT GN2 COOLING COIL | SPLIT GS1 COOLING COIL | SPLIT GS2 COOLING COIL | SPLIT MSW COOLING COIL | SPLIT MNW COOLING COIL | SPLIT MSE COOLING COIL | SPLIT MNE COOLING COIL | SPLIT MN1 COOLING COIL | SPLIT MN2 COOLING COIL | SPLIT MS1 COOLING COIL | SPLIT MS2 COOLING COIL | SPLIT TSW COOLING COIL | SPLIT TNW COOLING COIL | SPLIT TSE COOLING COIL | SPLIT TNE COOLING COIL | SPLIT TN1 COOLING COIL | SPLIT TN2 COOLING COIL | SPLIT TS1 COOLING COIL | SPLIT TS2 COOLING COIL |FanReportMonthly
| SPLIT GSW SUPPLY FAN | G SW APARTMENT ERV SUP FAN | G SW APARTMENT ERV EXH FAN | SPLIT GNW SUPPLY FAN | G NW APARTMENT ERV SUP FAN | G NW APARTMENT ERV EXH FAN | SPLIT OFFICE SUPPLY FAN | SPLIT GNE SUPPLY FAN | G NE APARTMENT ERV SUP FAN | G NE APARTMENT ERV EXH FAN | SPLIT GN1 SUPPLY FAN | G N1 APARTMENT ERV SUP FAN | G N1 APARTMENT ERV EXH FAN | SPLIT GN2 SUPPLY FAN | G N2 APARTMENT ERV SUP FAN | G N2 APARTMENT ERV EXH FAN | SPLIT GS1 SUPPLY FAN | G S1 APARTMENT ERV SUP FAN | G S1 APARTMENT ERV EXH FAN | SPLIT GS2 SUPPLY FAN | G S2 APARTMENT ERV SUP FAN | G S2 APARTMENT ERV EXH FAN | SPLIT MSW SUPPLY FAN | M SW APARTMENT ERV SUP FAN | M SW APARTMENT ERV EXH FAN | SPLIT MNW SUPPLY FAN | M NW APARTMENT ERV SUP FAN | M NW APARTMENT ERV EXH FAN | SPLIT MSE SUPPLY FAN | M SE APARTMENT ERV SUP FAN | M SE APARTMENT ERV EXH FAN | SPLIT MNE SUPPLY FAN | M NE APARTMENT ERV SUP FAN | M NE APARTMENT ERV EXH FAN | SPLIT MN1 SUPPLY FAN | M N1 APARTMENT ERV SUP FAN | M N1 APARTMENT ERV EXH FAN | SPLIT MN2 SUPPLY FAN | M N2 APARTMENT ERV SUP FAN | M N2 APARTMENT ERV EXH FAN | SPLIT MS1 SUPPLY FAN | M S1 APARTMENT ERV SUP FAN | M S1 APARTMENT ERV EXH FAN | SPLIT MS2 SUPPLY FAN | M S2 APARTMENT ERV SUP FAN | M S2 APARTMENT ERV EXH FAN | SPLIT TSW SUPPLY FAN | T SW APARTMENT ERV SUP FAN | T SW APARTMENT ERV EXH FAN | SPLIT TNW SUPPLY FAN | T NW APARTMENT ERV SUP FAN | T NW APARTMENT ERV EXH FAN | SPLIT TSE SUPPLY FAN | T SE APARTMENT ERV SUP FAN | T SE APARTMENT ERV EXH FAN | SPLIT TNE SUPPLY FAN | T NE APARTMENT ERV SUP FAN | T NE APARTMENT ERV EXH FAN | SPLIT TN1 SUPPLY FAN | T N1 APARTMENT ERV SUP FAN | T N1 APARTMENT ERV EXH FAN | SPLIT TN2 SUPPLY FAN | T N2 APARTMENT ERV SUP FAN | T N2 APARTMENT ERV EXH FAN | SPLIT TS1 SUPPLY FAN | T S1 APARTMENT ERV SUP FAN | T S1 APARTMENT ERV EXH FAN | SPLIT TS2 SUPPLY FAN | T S2 APARTMENT ERV SUP FAN | T S2 APARTMENT ERV EXH FAN |ZoneTemperatureOscillationReportMonthly
| G SW APARTMENT | G NW APARTMENT | OFFICE | G NE APARTMENT | G N1 APARTMENT | G N2 APARTMENT | G S1 APARTMENT | G S2 APARTMENT | M SW APARTMENT | M NW APARTMENT | M SE APARTMENT | M NE APARTMENT | M N1 APARTMENT | M N2 APARTMENT | M S1 APARTMENT | M S2 APARTMENT | T SW APARTMENT | T NW APARTMENT | T SE APARTMENT | T NE APARTMENT | T N1 APARTMENT | T N2 APARTMENT | T S1 APARTMENT | T S2 APARTMENT | T CORRIDOR | G CORRIDOR | M CORRIDOR |AirLoopSystemEnergyAndWaterUseMonthly
| SPLIT GSW | SPLIT GNW | SPLIT OFFICE | SPLIT GNE | SPLIT GN1 | SPLIT GN2 | SPLIT GS1 | SPLIT GS2 | SPLIT MSW | SPLIT MNW | SPLIT MSE | SPLIT MNE | SPLIT MN1 | SPLIT MN2 | SPLIT MS1 | SPLIT MS2 | SPLIT TSW | SPLIT TNW | SPLIT TSE | SPLIT TNE | SPLIT TN1 | SPLIT TN2 | SPLIT TS1 | SPLIT TS2 |AirLoopSystemComponentLoadsMonthly
| SPLIT GSW | SPLIT GNW | SPLIT OFFICE | SPLIT GNE | SPLIT GN1 | SPLIT GN2 | SPLIT GS1 | SPLIT GS2 | SPLIT MSW | SPLIT MNW | SPLIT MSE | SPLIT MNE | SPLIT MN1 | SPLIT MN2 | SPLIT MS1 | SPLIT MS2 | SPLIT TSW | SPLIT TNW | SPLIT TSE | SPLIT TNE | SPLIT TN1 | SPLIT TN2 | SPLIT TS1 | SPLIT TS2 |AirLoopSystemComponentEnergyUseMonthly
| SPLIT GSW | SPLIT GNW | SPLIT OFFICE | SPLIT GNE | SPLIT GN1 | SPLIT GN2 | SPLIT GS1 | SPLIT GS2 | SPLIT MSW | SPLIT MNW | SPLIT MSE | SPLIT MNE | SPLIT MN1 | SPLIT MN2 | SPLIT MS1 | SPLIT MS2 | SPLIT TSW | SPLIT TNW | SPLIT TSE | SPLIT TNE | SPLIT TN1 | SPLIT TN2 | SPLIT TS1 | SPLIT TS2 |MechanicalVentilationLoadsMonthly
| G SW APARTMENT | G NW APARTMENT | OFFICE | G NE APARTMENT | G N1 APARTMENT | G N2 APARTMENT | G S1 APARTMENT | G S2 APARTMENT | M SW APARTMENT | M NW APARTMENT | M SE APARTMENT | M NE APARTMENT | M N1 APARTMENT | M N2 APARTMENT | M S1 APARTMENT | M S2 APARTMENT | T SW APARTMENT | T NW APARTMENT | T SE APARTMENT | T NE APARTMENT | T N1 APARTMENT | T N2 APARTMENT | T S1 APARTMENT | T S2 APARTMENT |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 09:15:04
General| Value | |
| Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 09:14 |
| RunPeriod | RUNPERIOD 1 |
| Weather File | New York-John F Kennedy Intl AP NY USA TMY3 WMO#=744860 |
| Latitude [deg] | 40.65 |
| Longitude [deg] | -73.8 |
| Elevation [m] | 5.00 |
| Time Zone | -5.0 |
| North Axis Angle [deg] | 0.00 |
| Rotation for Appendix G [deg] | 0.00 |
| Hours Simulated [hrs] | 8760.00 |
| Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
| Gross Wall Area [m2] | 1542.04 | 564.80 | 206.22 | 564.80 | 206.22 |
| Above Ground Wall Area [m2] | 1542.04 | 564.80 | 206.22 | 564.80 | 206.22 |
| Window Opening Area [m2] | 306.92 | 112.97 | 43.82 | 112.97 | 37.16 |
| Gross Window-Wall Ratio [%] | 19.90 | 20.00 | 21.25 | 20.00 | 18.02 |
| Above Ground Window-Wall Ratio [%] | 19.90 | 20.00 | 21.25 | 20.00 | 18.02 |
| Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
| Gross Wall Area [m2] | 1501.17 | 564.80 | 185.79 | 564.80 | 185.79 |
| Above Ground Wall Area [m2] | 1501.17 | 564.80 | 185.79 | 564.80 | 185.79 |
| Window Opening Area [m2] | 300.26 | 112.97 | 37.16 | 112.97 | 37.16 |
| Gross Window-Wall Ratio [%] | 20.00 | 20.00 | 20.00 | 20.00 | 20.00 |
| Above Ground Window-Wall Ratio [%] | 20.00 | 20.00 | 20.00 | 20.00 | 20.00 |
| Total | |
| Gross Roof Area [m2] | 783.65 |
| Skylight Area [m2] | 0.00 |
| Skylight-Roof Ratio [%] | 0.00 |
| Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
| G SW APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 0.00 | 11.71 | 11.71 | 8.6918 | 35.30 | 6.6700 |
| G NW APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 0.00 | 11.71 | 11.71 | 8.6918 | 35.30 | 6.6700 |
| OFFICE | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 0.00 | 11.71 | 11.71 | 9.7532 | 18.58 | 6.6700 |
| G NE APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 0.00 | 11.71 | 11.71 | 8.6918 | 35.30 | 6.6700 |
| G N1 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 0.00 | 7.06 | 7.06 | 8.6918 | 35.30 | 6.6700 |
| G N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 0.00 | 7.06 | 7.06 | 8.6918 | 35.30 | 6.6700 |
| G S1 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 0.00 | 7.06 | 7.06 | 8.6918 | 35.30 | 6.6700 |
| G S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 0.00 | 7.06 | 7.06 | 8.6918 | 35.30 | 6.6700 |
| M SW APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 58.52 | 0.00 | 11.71 | 11.71 | 8.6918 | 35.30 | 6.6700 |
| M NW APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 58.52 | 0.00 | 11.71 | 11.71 | 8.6918 | 35.30 | 6.6700 |
| M SE APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 58.52 | 0.00 | 11.71 | 11.71 | 8.6918 | 35.30 | 6.6700 |
| M NE APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 58.52 | 0.00 | 11.71 | 11.71 | 8.6918 | 35.30 | 6.6700 |
| M N1 APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 35.30 | 0.00 | 7.06 | 7.06 | 8.6918 | 35.30 | 6.6700 |
| M N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 35.30 | 0.00 | 7.06 | 7.06 | 8.6918 | 35.30 | 6.6700 |
| M S1 APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 35.30 | 0.00 | 7.06 | 7.06 | 8.6918 | 35.30 | 6.6700 |
| M S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 35.30 | 0.00 | 7.06 | 7.06 | 8.6918 | 35.30 | 6.6700 |
| T SW APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 0.00 | 11.71 | 11.71 | 8.6918 | 35.30 | 6.6700 |
| T NW APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 0.00 | 11.71 | 11.71 | 8.6918 | 35.30 | 6.6700 |
| T SE APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 0.00 | 11.71 | 11.71 | 8.6918 | 35.30 | 6.6700 |
| T NE APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 0.00 | 11.71 | 11.71 | 8.6918 | 35.30 | 6.6700 |
| T N1 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 0.00 | 7.06 | 7.06 | 8.6918 | 35.30 | 6.6700 |
| T N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 0.00 | 7.06 | 7.06 | 8.6918 | 35.30 | 6.6700 |
| T S1 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 0.00 | 7.06 | 7.06 | 8.6918 | 35.30 | 6.6700 |
| T S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 0.00 | 7.06 | 7.06 | 8.6918 | 35.30 | 6.6700 |
| T CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 0.00 | 1.11 | 1.11 | 4.7725 | 18.58 | 0.0000 |
| G CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 0.00 | 3.32 | 3.32 | 4.7725 | 18.58 | 105.2565 |
| M CORRIDOR | 77.66 | No | Yes | 236.69 | 2.00 | 10.22 | 0.00 | 1.11 | 1.11 | 4.7725 | 18.58 | 0.0000 |
| Total | 3134.61 | 9553.84 | 1542.04 | 0.00 | 306.92 | 306.92 | 8.3333 | 31.67 | 8.6167 | |||
| Conditioned Total | 2823.98 | 8607.06 | 1501.17 | 0.00 | 300.26 | 300.26 | 8.7250 | 34.33 | 6.6700 | |||
| Unconditioned Total | 310.64 | 946.78 | 40.87 | 0.00 | 6.66 | 6.66 | 4.7725 | 18.58 | 26.3141 | |||
| Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
| G SW APARTMENT | 88.25 | Yes | Yes | 1.00 | G SW APARTMENT | GENERAL | G SW APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| G NW APARTMENT | 88.25 | Yes | Yes | 1.00 | G NW APARTMENT | GENERAL | G NW APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| OFFICE | 88.25 | Yes | Yes | 1.00 | OFFICE | GENERAL | OFFICE | 9.7532 | 18.58 | 6.6700 | |
| G NE APARTMENT | 88.25 | Yes | Yes | 1.00 | G NE APARTMENT | GENERAL | G NE APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| G N1 APARTMENT | 88.25 | Yes | Yes | 1.00 | G N1 APARTMENT | GENERAL | G N1 APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| G N2 APARTMENT | 88.25 | Yes | Yes | 1.00 | G N2 APARTMENT | GENERAL | G N2 APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| G S1 APARTMENT | 88.25 | Yes | Yes | 1.00 | G S1 APARTMENT | GENERAL | G S1 APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| G S2 APARTMENT | 88.25 | Yes | Yes | 1.00 | G S2 APARTMENT | GENERAL | G S2 APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| M SW APARTMENT | 88.25 | Yes | Yes | 2.00 | M SW APARTMENT | GENERAL | M SW APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| M NW APARTMENT | 88.25 | Yes | Yes | 2.00 | M NW APARTMENT | GENERAL | M NW APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| M SE APARTMENT | 88.25 | Yes | Yes | 2.00 | M SE APARTMENT | GENERAL | M SE APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| M NE APARTMENT | 88.25 | Yes | Yes | 2.00 | M NE APARTMENT | GENERAL | M NE APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| M N1 APARTMENT | 88.25 | Yes | Yes | 2.00 | M N1 APARTMENT | GENERAL | M N1 APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| M N2 APARTMENT | 88.25 | Yes | Yes | 2.00 | M N2 APARTMENT | GENERAL | M N2 APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| M S1 APARTMENT | 88.25 | Yes | Yes | 2.00 | M S1 APARTMENT | GENERAL | M S1 APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| M S2 APARTMENT | 88.25 | Yes | Yes | 2.00 | M S2 APARTMENT | GENERAL | M S2 APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| T SW APARTMENT | 88.25 | Yes | Yes | 1.00 | T SW APARTMENT | GENERAL | T SW APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| T NW APARTMENT | 88.25 | Yes | Yes | 1.00 | T NW APARTMENT | GENERAL | T NW APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| T SE APARTMENT | 88.25 | Yes | Yes | 1.00 | T SE APARTMENT | GENERAL | T SE APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| T NE APARTMENT | 88.25 | Yes | Yes | 1.00 | T NE APARTMENT | GENERAL | T NE APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| T N1 APARTMENT | 88.25 | Yes | Yes | 1.00 | T N1 APARTMENT | GENERAL | T N1 APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| T N2 APARTMENT | 88.25 | Yes | Yes | 1.00 | T N2 APARTMENT | GENERAL | T N2 APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| T S1 APARTMENT | 88.25 | Yes | Yes | 1.00 | T S1 APARTMENT | GENERAL | T S1 APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| T S2 APARTMENT | 88.25 | Yes | Yes | 1.00 | T S2 APARTMENT | GENERAL | T S2 APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| T CORRIDOR | 77.66 | No | Yes | 1.00 | T CORRIDOR | GENERAL | T CORRIDOR | 4.7725 | 18.58 | 0.0000 | |
| G CORRIDOR | 77.66 | No | Yes | 1.00 | G CORRIDOR | GENERAL | G CORRIDOR | 4.7725 | 18.58 | 105.2565 | |
| M CORRIDOR | 77.66 | No | Yes | 2.00 | M CORRIDOR | GENERAL | M CORRIDOR | 4.7725 | 18.58 | 0.0000 | |
| Total | 3134.61 | 8.3333 | 15.84 | 8.6167 | |||||||
| Conditioned Total | 2823.98 | 8.7250 | 17.17 | 6.6700 | |||||||
| Unconditioned Total | 310.64 | 4.7725 | 9.29 | 26.3141 | |||||||
| Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
| Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
| GENERAL | 3134.61 | 2823.98 | 310.64 | 0.00 | 6.2575 | 41.91 | 7.1145 |
| Total | 3134.61 | 2823.98 | 310.64 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 09:15:04
End Uses| Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
| Time of Peak | 19-JUN-17:40 | 06-FEB-01:10 | - | - | - | - | - | - | - | - | - | - | 01-JAN-07:10 |
| Heating | 0.00 | 105858.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Cooling | 25892.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Lighting | 5231.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment | 22609.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans | 8357.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems | 26233.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Total End Uses | 88325.42 | 105858.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
| Heating | General | 0.00 | 105858.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Cooling | General | 25892.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Lighting | LightsWired | 4887.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LightsPlugIn | 344.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment | MiscPlug | 18441.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| ElevatorLift | 4006.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| ElevatorLightsFan | 162.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| General | 8357.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems | Water Heater | 26233.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 09:15:04
Values gathered over 8760.00 hours| Source Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
| Heating | 0.00 | 410.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Cooling | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Lighting | 314.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Lighting | 158.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment | 1452.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans | 322.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems | 1433.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Total Source Energy End Use Components | 4091.71 | 410.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
| Heating | 0.00 | 145.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Cooling | 145.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Lighting | 111.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Lighting | 56.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment | 514.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans | 114.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems | 507.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Total Source Energy End Use Components | 1448.92 | 145.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
| Heating | 0.00 | 131.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Cooling | 131.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Lighting | 100.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Lighting | 50.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment | 463.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans | 102.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems | 457.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Total Source Energy End Use Components | 1305.33 | 131.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 09:15:04
ZoneHVAC:EnergyRecoveryVentilator| User-Specified Supply Air Flow Rate [m3/s] | User-Specified Exhaust Air Flow Rate [m3/s] | |
| G SW APARTMENT ERV | 0.025955 | 0.025955 |
| G NW APARTMENT ERV | 0.025955 | 0.025955 |
| G NE APARTMENT ERV | 0.025955 | 0.025955 |
| G N1 APARTMENT ERV | 0.025955 | 0.025955 |
| G N2 APARTMENT ERV | 0.025955 | 0.025955 |
| G S1 APARTMENT ERV | 0.025955 | 0.025955 |
| G S2 APARTMENT ERV | 0.025955 | 0.025955 |
| M SW APARTMENT ERV | 0.051909 | 0.051909 |
| M NW APARTMENT ERV | 0.051909 | 0.051909 |
| M SE APARTMENT ERV | 0.051909 | 0.051909 |
| M NE APARTMENT ERV | 0.051909 | 0.051909 |
| M N1 APARTMENT ERV | 0.051909 | 0.051909 |
| M N2 APARTMENT ERV | 0.051909 | 0.051909 |
| M S1 APARTMENT ERV | 0.051909 | 0.051909 |
| M S2 APARTMENT ERV | 0.051909 | 0.051909 |
| T SW APARTMENT ERV | 0.025955 | 0.025955 |
| T NW APARTMENT ERV | 0.025955 | 0.025955 |
| T SE APARTMENT ERV | 0.025955 | 0.025955 |
| T NE APARTMENT ERV | 0.025955 | 0.025955 |
| T N1 APARTMENT ERV | 0.025955 | 0.025955 |
| T N2 APARTMENT ERV | 0.025955 | 0.025955 |
| T S1 APARTMENT ERV | 0.025955 | 0.025955 |
| T S2 APARTMENT ERV | 0.025955 | 0.025955 |
| Design Size Maximum Flow Rate [m3/s] | |
| G SW APARTMENT ERV SUP FAN | 0.025955 |
| G SW APARTMENT ERV EXH FAN | 0.025955 |
| G NW APARTMENT ERV SUP FAN | 0.025955 |
| G NW APARTMENT ERV EXH FAN | 0.025955 |
| G NE APARTMENT ERV SUP FAN | 0.025955 |
| G NE APARTMENT ERV EXH FAN | 0.025955 |
| G N1 APARTMENT ERV SUP FAN | 0.025955 |
| G N1 APARTMENT ERV EXH FAN | 0.025955 |
| G N2 APARTMENT ERV SUP FAN | 0.025955 |
| G N2 APARTMENT ERV EXH FAN | 0.025955 |
| G S1 APARTMENT ERV SUP FAN | 0.025955 |
| G S1 APARTMENT ERV EXH FAN | 0.025955 |
| G S2 APARTMENT ERV SUP FAN | 0.025955 |
| G S2 APARTMENT ERV EXH FAN | 0.025955 |
| M SW APARTMENT ERV SUP FAN | 0.051909 |
| M SW APARTMENT ERV EXH FAN | 0.051909 |
| M NW APARTMENT ERV SUP FAN | 0.051909 |
| M NW APARTMENT ERV EXH FAN | 0.051909 |
| M SE APARTMENT ERV SUP FAN | 0.051909 |
| M SE APARTMENT ERV EXH FAN | 0.051909 |
| M NE APARTMENT ERV SUP FAN | 0.051909 |
| M NE APARTMENT ERV EXH FAN | 0.051909 |
| M N1 APARTMENT ERV SUP FAN | 0.051909 |
| M N1 APARTMENT ERV EXH FAN | 0.051909 |
| M N2 APARTMENT ERV SUP FAN | 0.051909 |
| M N2 APARTMENT ERV EXH FAN | 0.051909 |
| M S1 APARTMENT ERV SUP FAN | 0.051909 |
| M S1 APARTMENT ERV EXH FAN | 0.051909 |
| M S2 APARTMENT ERV SUP FAN | 0.051909 |
| M S2 APARTMENT ERV EXH FAN | 0.051909 |
| T SW APARTMENT ERV SUP FAN | 0.025955 |
| T SW APARTMENT ERV EXH FAN | 0.025955 |
| T NW APARTMENT ERV SUP FAN | 0.025955 |
| T NW APARTMENT ERV EXH FAN | 0.025955 |
| T SE APARTMENT ERV SUP FAN | 0.025955 |
| T SE APARTMENT ERV EXH FAN | 0.025955 |
| T NE APARTMENT ERV SUP FAN | 0.025955 |
| T NE APARTMENT ERV EXH FAN | 0.025955 |
| T N1 APARTMENT ERV SUP FAN | 0.025955 |
| T N1 APARTMENT ERV EXH FAN | 0.025955 |
| T N2 APARTMENT ERV SUP FAN | 0.025955 |
| T N2 APARTMENT ERV EXH FAN | 0.025955 |
| T S1 APARTMENT ERV SUP FAN | 0.025955 |
| T S1 APARTMENT ERV EXH FAN | 0.025955 |
| T S2 APARTMENT ERV SUP FAN | 0.025955 |
| T S2 APARTMENT ERV EXH FAN | 0.025955 |
| SPLIT GSW SUPPLY FAN | 0.344011 |
| SPLIT GNW SUPPLY FAN | 0.328070 |
| SPLIT OFFICE SUPPLY FAN | 0.402412 |
| SPLIT GNE SUPPLY FAN | 0.302688 |
| SPLIT GN1 SUPPLY FAN | 0.271433 |
| SPLIT GN2 SUPPLY FAN | 0.271245 |
| SPLIT GS1 SUPPLY FAN | 0.292202 |
| SPLIT GS2 SUPPLY FAN | 0.294145 |
| SPLIT MSW SUPPLY FAN | 0.835966 |
| SPLIT MNW SUPPLY FAN | 0.810271 |
| SPLIT MSE SUPPLY FAN | 0.762479 |
| SPLIT MNE SUPPLY FAN | 0.737367 |
| SPLIT MN1 SUPPLY FAN | 0.660432 |
| SPLIT MN2 SUPPLY FAN | 0.658937 |
| SPLIT MS1 SUPPLY FAN | 0.690510 |
| SPLIT MS2 SUPPLY FAN | 0.688939 |
| SPLIT TSW SUPPLY FAN | 0.454650 |
| SPLIT TNW SUPPLY FAN | 0.450823 |
| SPLIT TSE SUPPLY FAN | 0.401017 |
| SPLIT TNE SUPPLY FAN | 0.397110 |
| SPLIT TN1 SUPPLY FAN | 0.370381 |
| SPLIT TN2 SUPPLY FAN | 0.368438 |
| SPLIT TS1 SUPPLY FAN | 0.375404 |
| SPLIT TS2 SUPPLY FAN | 0.373470 |
| Design Size Nominal Supply Air Flow Rate [m3/s] | |
| G SW APARTMENT OA HEAT EXCHANGER | 0.025955 |
| G NW APARTMENT OA HEAT EXCHANGER | 0.025955 |
| G NE APARTMENT OA HEAT EXCHANGER | 0.025955 |
| G N1 APARTMENT OA HEAT EXCHANGER | 0.025955 |
| G N2 APARTMENT OA HEAT EXCHANGER | 0.025955 |
| G S1 APARTMENT OA HEAT EXCHANGER | 0.025955 |
| G S2 APARTMENT OA HEAT EXCHANGER | 0.025955 |
| M SW APARTMENT OA HEAT EXCHANGER | 0.051909 |
| M NW APARTMENT OA HEAT EXCHANGER | 0.051909 |
| M SE APARTMENT OA HEAT EXCHANGER | 0.051909 |
| M NE APARTMENT OA HEAT EXCHANGER | 0.051909 |
| M N1 APARTMENT OA HEAT EXCHANGER | 0.051909 |
| M N2 APARTMENT OA HEAT EXCHANGER | 0.051909 |
| M S1 APARTMENT OA HEAT EXCHANGER | 0.051909 |
| M S2 APARTMENT OA HEAT EXCHANGER | 0.051909 |
| T SW APARTMENT OA HEAT EXCHANGER | 0.025955 |
| T NW APARTMENT OA HEAT EXCHANGER | 0.025955 |
| T SE APARTMENT OA HEAT EXCHANGER | 0.025955 |
| T NE APARTMENT OA HEAT EXCHANGER | 0.025955 |
| T N1 APARTMENT OA HEAT EXCHANGER | 0.025955 |
| T N2 APARTMENT OA HEAT EXCHANGER | 0.025955 |
| T S1 APARTMENT OA HEAT EXCHANGER | 0.025955 |
| T S2 APARTMENT OA HEAT EXCHANGER | 0.025955 |
| Design Size Maximum Air Flow Rate [m3/s] | |
| G SW APARTMENT DIRECT AIR | 0.344011 |
| G NW APARTMENT DIRECT AIR | 0.328070 |
| OFFICE DIRECT AIR | 0.402412 |
| G NE APARTMENT DIRECT AIR | 0.302688 |
| G N1 APARTMENT DIRECT AIR | 0.271433 |
| G N2 APARTMENT DIRECT AIR | 0.271245 |
| G S1 APARTMENT DIRECT AIR | 0.292202 |
| G S2 APARTMENT DIRECT AIR | 0.294145 |
| M SW APARTMENT DIRECT AIR | 0.835966 |
| M NW APARTMENT DIRECT AIR | 0.810271 |
| M SE APARTMENT DIRECT AIR | 0.762479 |
| M NE APARTMENT DIRECT AIR | 0.737367 |
| M N1 APARTMENT DIRECT AIR | 0.660432 |
| M N2 APARTMENT DIRECT AIR | 0.658937 |
| M S1 APARTMENT DIRECT AIR | 0.690510 |
| M S2 APARTMENT DIRECT AIR | 0.688939 |
| T SW APARTMENT DIRECT AIR | 0.454650 |
| T NW APARTMENT DIRECT AIR | 0.450823 |
| T SE APARTMENT DIRECT AIR | 0.401017 |
| T NE APARTMENT DIRECT AIR | 0.397110 |
| T N1 APARTMENT DIRECT AIR | 0.370381 |
| T N2 APARTMENT DIRECT AIR | 0.368438 |
| T S1 APARTMENT DIRECT AIR | 0.375404 |
| T S2 APARTMENT DIRECT AIR | 0.373470 |
| Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
| SPLIT GSW | 0.344011 | 0.344011 | 0.344011 | 0.344011 | 0.344011 | 0.344011 | 1.00 | 1.00 | 0.344011 |
| SPLIT GNW | 0.328070 | 0.328070 | 0.328070 | 0.328070 | 0.328070 | 0.328070 | 1.00 | 1.000000 | 0.328070 |
| SPLIT OFFICE | 0.402412 | 0.402412 | 0.402412 | 0.402412 | 0.402412 | 0.402412 | 1.00 | 1.000000 | 0.402412 |
| SPLIT GNE | 0.302688 | 0.302688 | 0.302688 | 0.302688 | 0.302688 | 0.302688 | 1.00 | 1.000000 | 0.302688 |
| SPLIT GN1 | 0.271433 | 0.271433 | 0.271433 | 0.271433 | 0.271433 | 0.271433 | 1.00 | 1.00 | 0.271433 |
| SPLIT GN2 | 0.271245 | 0.271245 | 0.271245 | 0.271245 | 0.271245 | 0.271245 | 1.00 | 1.00 | 0.271245 |
| SPLIT GS1 | 0.292202 | 0.292202 | 0.292202 | 0.292202 | 0.292202 | 0.292202 | 1.00 | 1.00 | 0.292202 |
| SPLIT GS2 | 0.294145 | 0.294145 | 0.294145 | 0.294145 | 0.294145 | 0.294145 | 1.00 | 1.00 | 0.294145 |
| SPLIT MSW | 0.835966 | 0.835966 | 0.835966 | 0.835966 | 0.835966 | 0.835966 | 1.00 | 1.00 | 0.835966 |
| SPLIT MNW | 0.810271 | 0.810271 | 0.810271 | 0.810271 | 0.810271 | 0.810271 | 1.00 | 1.00 | 0.810271 |
| SPLIT MSE | 0.762479 | 0.762479 | 0.762479 | 0.762479 | 0.762479 | 0.762479 | 1.00 | 1.00 | 0.762479 |
| SPLIT MNE | 0.737367 | 0.737367 | 0.737367 | 0.737367 | 0.737367 | 0.737367 | 1.00 | 1.000000 | 0.737367 |
| SPLIT MN1 | 0.660432 | 0.660432 | 0.660432 | 0.660432 | 0.660432 | 0.660432 | 1.00 | 1.00 | 0.660432 |
| SPLIT MN2 | 0.658937 | 0.658937 | 0.658937 | 0.658937 | 0.658937 | 0.658937 | 1.00 | 1.00 | 0.658937 |
| SPLIT MS1 | 0.690510 | 0.690510 | 0.690510 | 0.690510 | 0.690510 | 0.690510 | 1.00 | 1.00 | 0.690510 |
| SPLIT MS2 | 0.688939 | 0.688939 | 0.688939 | 0.688939 | 0.688939 | 0.688939 | 1.00 | 1.00 | 0.688939 |
| SPLIT TSW | 0.454650 | 0.454650 | 0.454650 | 0.454650 | 0.454650 | 0.454650 | 1.00 | 1.00 | 0.454650 |
| SPLIT TNW | 0.450823 | 0.450823 | 0.450823 | 0.450823 | 0.450823 | 0.450823 | 1.00 | 1.00 | 0.450823 |
| SPLIT TSE | 0.401017 | 0.401017 | 0.401017 | 0.401017 | 0.401017 | 0.401017 | 1.00 | 1.00 | 0.401017 |
| SPLIT TNE | 0.397110 | 0.397110 | 0.397110 | 0.397110 | 0.397110 | 0.397110 | 1.00 | 1.00 | 0.397110 |
| SPLIT TN1 | 0.370381 | 0.370381 | 0.370381 | 0.370381 | 0.370381 | 0.370381 | 1.00 | 1.00 | 0.370381 |
| SPLIT TN2 | 0.368438 | 0.368438 | 0.368438 | 0.368438 | 0.368438 | 0.368438 | 1.00 | 1.00 | 0.368438 |
| SPLIT TS1 | 0.375404 | 0.375404 | 0.375404 | 0.375404 | 0.375404 | 0.375404 | 1.00 | 1.00 | 0.375404 |
| SPLIT TS2 | 0.373470 | 0.373470 | 0.373470 | 0.373470 | 0.373470 | 0.373470 | 1.00 | 1.000000 | 0.373470 |
| Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
| SPLIT GSW_OA_CONTROLLER | 0.344011 | 0.025955 |
| SPLIT GNW_OA_CONTROLLER | 0.328070 | 0.025955 |
| SPLIT OFFICE_OA_CONTROLLER | 0.402412 | 0.038106 |
| SPLIT GNE_OA_CONTROLLER | 0.302688 | 0.025955 |
| SPLIT GN1_OA_CONTROLLER | 0.271433 | 0.025955 |
| SPLIT GN2_OA_CONTROLLER | 0.271245 | 0.025955 |
| SPLIT GS1_OA_CONTROLLER | 0.292202 | 0.025955 |
| SPLIT GS2_OA_CONTROLLER | 0.294145 | 0.025955 |
| SPLIT MSW_OA_CONTROLLER | 0.835966 | 0.051909 |
| SPLIT MNW_OA_CONTROLLER | 0.810271 | 0.051909 |
| SPLIT MSE_OA_CONTROLLER | 0.762479 | 0.051909 |
| SPLIT MNE_OA_CONTROLLER | 0.737367 | 0.051909 |
| SPLIT MN1_OA_CONTROLLER | 0.660432 | 0.051909 |
| SPLIT MN2_OA_CONTROLLER | 0.658937 | 0.051909 |
| SPLIT MS1_OA_CONTROLLER | 0.690510 | 0.051909 |
| SPLIT MS2_OA_CONTROLLER | 0.688939 | 0.051909 |
| SPLIT TSW_OA_CONTROLLER | 0.454650 | 0.025955 |
| SPLIT TNW_OA_CONTROLLER | 0.450823 | 0.025955 |
| SPLIT TSE_OA_CONTROLLER | 0.401017 | 0.025955 |
| SPLIT TNE_OA_CONTROLLER | 0.397110 | 0.025955 |
| SPLIT TN1_OA_CONTROLLER | 0.370381 | 0.025955 |
| SPLIT TN2_OA_CONTROLLER | 0.368438 | 0.025955 |
| SPLIT TS1_OA_CONTROLLER | 0.375404 | 0.025955 |
| SPLIT TS2_OA_CONTROLLER | 0.373470 | 0.025955 |
| Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | Design Size Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
| SPLIT GSW_UNITARY_PACKAGE_DX | 0.344011 | 0.344011 | 0.344011 | 0.344011 | 6045.53 | 8862.16 | 40.00 | 1.00 |
| SPLIT GNW_UNITARY_PACKAGE_DX | 0.328070 | 0.328070 | 0.328070 | 0.328070 | 5788.81 | 8497.72 | 40.00 | 1.00 |
| SPLIT OFFICE_UNITARY_PACKAGE_DX | 0.402412 | 0.402412 | 0.402412 | 0.402412 | 7005.52 | 10664.53 | 40.00 | 1.00 |
| SPLIT GNE_UNITARY_PACKAGE_DX | 0.302688 | 0.302688 | 0.302688 | 0.302688 | 5415.87 | 7917.48 | 40.00 | 1.00 |
| SPLIT GN1_UNITARY_PACKAGE_DX | 0.271433 | 0.271433 | 0.271433 | 0.271433 | 4875.68 | 7202.91 | 40.00 | 1.00 |
| SPLIT GN2_UNITARY_PACKAGE_DX | 0.271245 | 0.271245 | 0.271245 | 0.271245 | 4873.48 | 7198.61 | 40.00 | 1.00 |
| SPLIT GS1_UNITARY_PACKAGE_DX | 0.292202 | 0.292202 | 0.292202 | 0.292202 | 5216.19 | 7677.72 | 40.00 | 1.00 |
| SPLIT GS2_UNITARY_PACKAGE_DX | 0.294145 | 0.294145 | 0.294145 | 0.294145 | 5245.88 | 7722.14 | 40.00 | 1.00 |
| SPLIT MSW_UNITARY_PACKAGE_DX | 0.835966 | 0.835966 | 0.835966 | 0.835966 | 14460.98 | 21108.01 | 40.00 | 1.00 |
| SPLIT MNW_UNITARY_PACKAGE_DX | 0.810271 | 0.810271 | 0.810271 | 0.810271 | 14047.72 | 20520.32 | 40.00 | 1.00 |
| SPLIT MSE_UNITARY_PACKAGE_DX | 0.762479 | 0.762479 | 0.762479 | 0.762479 | 13368.00 | 19427.96 | 40.00 | 1.00 |
| SPLIT MNE_UNITARY_PACKAGE_DX | 0.737367 | 0.737367 | 0.737367 | 0.737367 | 12962.94 | 18853.62 | 40.00 | 1.00 |
| SPLIT MN1_UNITARY_PACKAGE_DX | 0.660432 | 0.660432 | 0.660432 | 0.660432 | 11620.38 | 17093.99 | 40.00 | 1.00 |
| SPLIT MN2_UNITARY_PACKAGE_DX | 0.658937 | 0.658937 | 0.658937 | 0.658937 | 11598.22 | 17059.82 | 40.00 | 1.00 |
| SPLIT MS1_UNITARY_PACKAGE_DX | 0.690510 | 0.690510 | 0.690510 | 0.690510 | 12103.84 | 17781.82 | 40.00 | 1.00 |
| SPLIT MS2_UNITARY_PACKAGE_DX | 0.688939 | 0.688939 | 0.688939 | 0.688939 | 12080.75 | 17745.90 | 40.00 | 1.00 |
| SPLIT TSW_UNITARY_PACKAGE_DX | 0.454650 | 0.454650 | 0.454650 | 0.454650 | 7867.62 | 11392.80 | 40.00 | 1.00 |
| SPLIT TNW_UNITARY_PACKAGE_DX | 0.450823 | 0.450823 | 0.450823 | 0.450823 | 7797.78 | 11305.17 | 40.00 | 1.00 |
| SPLIT TSE_UNITARY_PACKAGE_DX | 0.401017 | 0.401017 | 0.401017 | 0.401017 | 7056.71 | 10166.59 | 40.00 | 1.00 |
| SPLIT TNE_UNITARY_PACKAGE_DX | 0.397110 | 0.397110 | 0.397110 | 0.397110 | 6984.41 | 10077.14 | 40.00 | 1.00 |
| SPLIT TN1_UNITARY_PACKAGE_DX | 0.370381 | 0.370381 | 0.370381 | 0.370381 | 6449.18 | 9465.45 | 40.00 | 1.00 |
| SPLIT TN2_UNITARY_PACKAGE_DX | 0.368438 | 0.368438 | 0.368438 | 0.368438 | 6419.96 | 9421.03 | 40.00 | 1.00 |
| SPLIT TS1_UNITARY_PACKAGE_DX | 0.375404 | 0.375404 | 0.375404 | 0.375404 | 6539.89 | 9580.42 | 40.00 | 1.00 |
| SPLIT TS2_UNITARY_PACKAGE_DX | 0.373470 | 0.373470 | 0.373470 | 0.373470 | 6510.87 | 9536.20 | 40.00 | 1.00 |
| Design Size Rated Air Flow Rate [m3/s] | Design Size Gross Rated Total Cooling Capacity [W] | Design Size Gross Rated Sensible Heat Ratio | |
| SPLIT GSW COOLING COIL | 0.344011 | 6045.53 | 0.800314 |
| SPLIT GNW COOLING COIL | 0.328070 | 5788.81 | 0.800913 |
| SPLIT OFFICE COOLING COIL | 0.402412 | 7005.52 | 0.800593 |
| SPLIT GNE COOLING COIL | 0.302688 | 5415.87 | 0.800140 |
| SPLIT GN1 COOLING COIL | 0.271433 | 4875.68 | 0.800813 |
| SPLIT GN2 COOLING COIL | 0.271245 | 4873.48 | 0.800731 |
| SPLIT GS1 COOLING COIL | 0.292202 | 5216.19 | 0.800928 |
| SPLIT GS2 COOLING COIL | 0.294145 | 5245.88 | 0.800253 |
| SPLIT MSW COOLING COIL | 0.835966 | 14460.98 | 0.800822 |
| SPLIT MNW COOLING COIL | 0.810271 | 14047.72 | 0.800040 |
| SPLIT MSE COOLING COIL | 0.762479 | 13368.00 | 0.800131 |
| SPLIT MNE COOLING COIL | 0.737367 | 12962.94 | 0.800188 |
| SPLIT MN1 COOLING COIL | 0.660432 | 11620.38 | 0.800891 |
| SPLIT MN2 COOLING COIL | 0.658937 | 11598.22 | 0.800768 |
| SPLIT MS1 COOLING COIL | 0.690510 | 12103.84 | 0.800199 |
| SPLIT MS2 COOLING COIL | 0.688939 | 12080.75 | 0.800071 |
| SPLIT TSW COOLING COIL | 0.454650 | 7867.62 | 0.800695 |
| SPLIT TNW COOLING COIL | 0.450823 | 7797.78 | 0.800858 |
| SPLIT TSE COOLING COIL | 0.401017 | 7056.71 | 0.800854 |
| SPLIT TNE COOLING COIL | 0.397110 | 6984.41 | 0.800030 |
| SPLIT TN1 COOLING COIL | 0.370381 | 6449.18 | 0.800523 |
| SPLIT TN2 COOLING COIL | 0.368438 | 6419.96 | 0.800272 |
| SPLIT TS1 COOLING COIL | 0.375404 | 6539.89 | 0.800350 |
| SPLIT TS2 COOLING COIL | 0.373470 | 6510.87 | 0.800099 |
| Design Size Nominal Capacity [W] | |
| SPLIT GSW HEATING COIL | 8862.16 |
| SPLIT GNW HEATING COIL | 8497.72 |
| SPLIT OFFICE HEATING COIL | 10664.53 |
| SPLIT GNE HEATING COIL | 7917.48 |
| SPLIT GN1 HEATING COIL | 7202.91 |
| SPLIT GN2 HEATING COIL | 7198.61 |
| SPLIT GS1 HEATING COIL | 7677.72 |
| SPLIT GS2 HEATING COIL | 7722.14 |
| SPLIT MSW HEATING COIL | 21108.01 |
| SPLIT MNW HEATING COIL | 20520.32 |
| SPLIT MSE HEATING COIL | 19427.96 |
| SPLIT MNE HEATING COIL | 18853.62 |
| SPLIT MN1 HEATING COIL | 17093.99 |
| SPLIT MN2 HEATING COIL | 17059.82 |
| SPLIT MS1 HEATING COIL | 17781.82 |
| SPLIT MS2 HEATING COIL | 17745.90 |
| SPLIT TSW HEATING COIL | 11392.80 |
| SPLIT TNW HEATING COIL | 11305.17 |
| SPLIT TSE HEATING COIL | 10166.59 |
| SPLIT TNE HEATING COIL | 10077.14 |
| SPLIT TN1 HEATING COIL | 9465.45 |
| SPLIT TN2 HEATING COIL | 9421.03 |
| SPLIT TS1 HEATING COIL | 9580.42 |
| SPLIT TS2 HEATING COIL | 9536.20 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 09:15:04
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other Surfaces| None |
| Possible Shadow Receivers | |
| G SWALL SWA | GWINDOW1 S SWA | |
| G WWALL SWA | GWINDOW1 W SWA | |
| G NWALL NWA | GWINDOW1 N NWA | |
| G WWALL NWA | GWINDOW1 W NWA | |
| G SWALL SEA | GWINDOW1 S SEA | |
| G EWALL SEA | GWINDOW1 E SEA | |
| G NWALL NEA | GWINDOW1 N NEA | |
| G EWALL NEA | GWINDOW1 E NEA | |
| G NWALL N1A | GWINDOW1 N N1A | |
| G NWALL N2A | GWINDOW1 N N2A | |
| G SWALL S1A | GWINDOW1 S S1A | |
| G SWALL S2A | GWINDOW1 S S2A | |
| M WWALL SWA | MWINDOW1 W SWA | |
| M SWALL SWA | MWINDOW1 S SWA | |
| M NWALL NWA | MWINDOW1 N NWA | |
| M WWALL NWA | MWINDOW1 W NWA | |
| M EWALL SEA | MWINDOW1 E SEA | |
| M SWALL SEA | MWINDOW1 S SEA | |
| M NWALL NEA | MWINDOW1 N NEA | |
| M EWALL NEA | MWINDOW1 E NEA | |
| M NWALL N1A | MWINDOW1 N N1A | |
| M NWALL N2A | MWINDOW1 N N2A | |
| M SWALL S1A | MWINDOW1 S S1A | |
| M SWALL S2A | MWINDOW1 S S2A | |
| T WWALL SWA | TWINDOW1 W SWA | |
| T SWALL SWA | TWINDOW1 S SWA | |
| T NWALL NWA | TWINDOW1 N NWA | |
| T WWALL NWA | TWINDOW1 W NWA | |
| T EWALL SEA | TWINDOW1 E SEA | |
| T SWALL SEA | TWINDOW1 S SEA | |
| T NWALL NEA | TWINDOW1 N NEA | |
| T EWALL NEA | TWINDOW1 E NEA | |
| T NWALL N1A | TWINDOW1 N N1A | |
| T NWALL N2A | TWINDOW1 N N2A | |
| T SWALL S1A | TWINDOW1 S S1A | |
| T SWALL S2A | TWINDOW1 S S2A | |
| T EWALL C | TWINDOW14 | |
| G EWALL C | ENTRANCE DOOR | |
| M EWALL C | MWINDOW14 | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 09:15:04
Time Not Meeting the Adaptive Comfort Models during Occupied Hours| ASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 09:15:04
Version| Version ID | |
| 1 | 22.1 |
| #TimeSteps | Minutes per TimeStep {minutes} | |
| 1 | 6 | 10 |
| Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
| 1 | 1 | 20 | 2 | 8 |
| Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
| 1 | Yes | Yes | No | No | Yes | No |
| Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
| 1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
| Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
| 1 | 0.556 | 0.556 |
| Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
| 1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
| Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
| 1 | 14.00 | 7.30 | 3.30 | 1.20 | -0.20 | 5.60 | 10.90 | 16.10 | 21.70 | 25.00 | 24.80 | 19.90 |
| Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
| 1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
| Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
| 1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
| Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
| 1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
| Normal | Daylighting {dimensionless} | |
| 1 | 1.000 | 1.000 |
| Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
| 1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
| Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
| 1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
| Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
| 1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
| Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
| 1 | New York-John F Kennedy Intl AP NY USA TMY3 WMO#=744860 | 40.65 | -73.80 | -5.00 | 5.00 | 101265 | 1.2036 |
| Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
| 1 | Correlation | NA | 12.47 | 25.20 | NA |
| Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
| 1 | ApartmentMidRise | 0.000 | City | 4.00000E-002 | 0.40000 | FullExterior | 25 | 6 |
| Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
| 1 | TARP |
| Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
| 1 | TARP |
| Value {Anisotropic} | |
| 1 | Anisotropic |
| Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
| 1 | ThirdOrderBackwardDifference |
| Simulation {Yes/No} | Carbon Dioxide Concentration | |
| 1 | No | N/A |
| Simulation {Yes/No} | Generic Contaminant Concentration | |
| 1 | No | N/A |
| Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
| 1 | No | N/A | N/A | N/A |
| Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
| 1 | RegulaFalsi |
| Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
| 1 | 0.330 | 460.000 | 6.500000E-003 |
| Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
| 1 | LowerLeftCorner | Clockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
| Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
| 1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
| Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
| 1 | 0 | 0 | 0 |
| Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
| 1 | 27 | 243 | 39 |
| Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
| 1 | G SW APARTMENT | 0.0 | 0.00 | 0.00 | 0.00 | 5.79 | 3.81 | 1.52 | 1 | 1 | 1 | 0.00 | 11.58 | 0.00 | 7.62 | 0.00 | 3.05 | 3.05 | 268.97 | TARP | TARP | 88.25 | 58.52 | 46.82 | 11.71 | 6 | 2 | 0 | Yes |
| 2 | G NW APARTMENT | 0.0 | 0.00 | 9.30 | 0.00 | 5.79 | 13.11 | 1.52 | 1 | 1 | 1 | 0.00 | 11.58 | 9.30 | 16.92 | 0.00 | 3.05 | 3.05 | 268.97 | TARP | TARP | 88.25 | 58.52 | 46.82 | 11.71 | 6 | 2 | 0 | Yes |
| 3 | OFFICE | 0.0 | 34.75 | 0.00 | 0.00 | 40.54 | 3.81 | 1.52 | 1 | 1 | 1 | 34.75 | 46.33 | 0.00 | 7.62 | 0.00 | 3.05 | 3.05 | 268.97 | TARP | TARP | 88.25 | 58.52 | 46.82 | 11.71 | 6 | 2 | 0 | Yes |
| 4 | G NE APARTMENT | 0.0 | 34.75 | 9.30 | 0.00 | 40.54 | 13.11 | 1.52 | 1 | 1 | 1 | 34.75 | 46.33 | 9.30 | 16.92 | 0.00 | 3.05 | 3.05 | 268.97 | TARP | TARP | 88.25 | 58.52 | 46.82 | 11.71 | 6 | 2 | 0 | Yes |
| 5 | G N1 APARTMENT | 0.0 | 11.58 | 9.30 | 0.00 | 17.37 | 13.11 | 1.52 | 1 | 1 | 1 | 11.58 | 23.16 | 9.30 | 16.92 | 0.00 | 3.05 | 3.05 | 268.97 | TARP | TARP | 88.25 | 35.30 | 28.24 | 7.06 | 6 | 1 | 0 | Yes |
| 6 | G N2 APARTMENT | 0.0 | 23.16 | 9.30 | 0.00 | 28.95 | 13.11 | 1.52 | 1 | 1 | 1 | 23.16 | 34.75 | 9.30 | 16.92 | 0.00 | 3.05 | 3.05 | 268.97 | TARP | TARP | 88.25 | 35.30 | 28.24 | 7.06 | 6 | 1 | 0 | Yes |
| 7 | G S1 APARTMENT | 0.0 | 11.58 | 0.00 | 0.00 | 17.37 | 3.81 | 1.52 | 1 | 1 | 1 | 11.58 | 23.16 | 0.00 | 7.62 | 0.00 | 3.05 | 3.05 | 268.97 | TARP | TARP | 88.25 | 35.30 | 28.24 | 7.06 | 6 | 1 | 0 | Yes |
| 8 | G S2 APARTMENT | 0.0 | 23.16 | 0.00 | 0.00 | 28.95 | 3.81 | 1.52 | 1 | 1 | 1 | 23.16 | 34.75 | 0.00 | 7.62 | 0.00 | 3.05 | 3.05 | 268.97 | TARP | TARP | 88.25 | 35.30 | 28.24 | 7.06 | 6 | 1 | 0 | Yes |
| 9 | M SW APARTMENT | 0.0 | 0.00 | 0.00 | 3.05 | 5.79 | 3.81 | 4.57 | 1 | 1 | 2 | 0.00 | 11.58 | 0.00 | 7.62 | 3.05 | 6.10 | 3.05 | 268.97 | TARP | TARP | 88.25 | 58.52 | 46.82 | 11.71 | 6 | 2 | 0 | Yes |
| 10 | M NW APARTMENT | 0.0 | 0.00 | 9.30 | 3.05 | 5.79 | 13.11 | 4.57 | 1 | 1 | 2 | 0.00 | 11.58 | 9.30 | 16.92 | 3.05 | 6.10 | 3.05 | 268.97 | TARP | TARP | 88.25 | 58.52 | 46.82 | 11.71 | 6 | 2 | 0 | Yes |
| 11 | M SE APARTMENT | 0.0 | 34.75 | 0.00 | 3.05 | 40.54 | 3.81 | 4.57 | 1 | 1 | 2 | 34.75 | 46.33 | 0.00 | 7.62 | 3.05 | 6.10 | 3.05 | 268.97 | TARP | TARP | 88.25 | 58.52 | 46.82 | 11.71 | 6 | 2 | 0 | Yes |
| 12 | M NE APARTMENT | 0.0 | 34.75 | 9.30 | 3.05 | 40.54 | 13.11 | 4.57 | 1 | 1 | 2 | 34.75 | 46.33 | 9.30 | 16.92 | 3.05 | 6.10 | 3.05 | 268.97 | TARP | TARP | 88.25 | 58.52 | 46.82 | 11.71 | 6 | 2 | 0 | Yes |
| 13 | M N1 APARTMENT | 0.0 | 11.58 | 9.30 | 3.05 | 17.37 | 13.11 | 4.57 | 1 | 1 | 2 | 11.58 | 23.16 | 9.30 | 16.92 | 3.05 | 6.10 | 3.05 | 268.97 | TARP | TARP | 88.25 | 35.30 | 28.24 | 7.06 | 6 | 1 | 0 | Yes |
| 14 | M N2 APARTMENT | 0.0 | 23.16 | 9.30 | 3.05 | 28.95 | 13.11 | 4.57 | 1 | 1 | 2 | 23.16 | 34.75 | 9.30 | 16.92 | 3.05 | 6.10 | 3.05 | 268.97 | TARP | TARP | 88.25 | 35.30 | 28.24 | 7.06 | 6 | 1 | 0 | Yes |
| 15 | M S1 APARTMENT | 0.0 | 11.58 | 0.00 | 3.05 | 17.37 | 3.81 | 4.57 | 1 | 1 | 2 | 11.58 | 23.16 | 0.00 | 7.62 | 3.05 | 6.10 | 3.05 | 268.97 | TARP | TARP | 88.25 | 35.30 | 28.24 | 7.06 | 6 | 1 | 0 | Yes |
| 16 | M S2 APARTMENT | 0.0 | 23.16 | 0.00 | 3.05 | 28.95 | 3.81 | 4.57 | 1 | 1 | 2 | 23.16 | 34.75 | 0.00 | 7.62 | 3.05 | 6.10 | 3.05 | 268.97 | TARP | TARP | 88.25 | 35.30 | 28.24 | 7.06 | 6 | 1 | 0 | Yes |
| 17 | T SW APARTMENT | 0.0 | 0.00 | 0.00 | 9.14 | 5.79 | 3.81 | 10.67 | 1 | 1 | 1 | 0.00 | 11.58 | 0.00 | 7.62 | 9.14 | 12.19 | 3.05 | 268.97 | TARP | TARP | 88.25 | 58.52 | 46.82 | 11.71 | 6 | 2 | 0 | Yes |
| 18 | T NW APARTMENT | 0.0 | 0.00 | 9.30 | 9.14 | 5.79 | 13.11 | 10.67 | 1 | 1 | 1 | 0.00 | 11.58 | 9.30 | 16.92 | 9.14 | 12.19 | 3.05 | 268.97 | TARP | TARP | 88.25 | 58.52 | 46.82 | 11.71 | 6 | 2 | 0 | Yes |
| 19 | T SE APARTMENT | 0.0 | 34.75 | 0.00 | 9.14 | 40.54 | 3.81 | 10.67 | 1 | 1 | 1 | 34.75 | 46.33 | 0.00 | 7.62 | 9.14 | 12.19 | 3.05 | 268.97 | TARP | TARP | 88.25 | 58.52 | 46.82 | 11.71 | 6 | 2 | 0 | Yes |
| 20 | T NE APARTMENT | 0.0 | 34.75 | 9.30 | 9.14 | 40.54 | 13.11 | 10.67 | 1 | 1 | 1 | 34.75 | 46.33 | 9.30 | 16.92 | 9.14 | 12.19 | 3.05 | 268.97 | TARP | TARP | 88.25 | 58.52 | 46.82 | 11.71 | 6 | 2 | 0 | Yes |
| 21 | T N1 APARTMENT | 0.0 | 11.58 | 9.30 | 9.14 | 17.37 | 13.11 | 10.67 | 1 | 1 | 1 | 11.58 | 23.16 | 9.30 | 16.92 | 9.14 | 12.19 | 3.05 | 268.97 | TARP | TARP | 88.25 | 35.30 | 28.24 | 7.06 | 6 | 1 | 0 | Yes |
| 22 | T N2 APARTMENT | 0.0 | 23.16 | 9.30 | 9.14 | 28.95 | 13.11 | 10.67 | 1 | 1 | 1 | 23.16 | 34.75 | 9.30 | 16.92 | 9.14 | 12.19 | 3.05 | 268.97 | TARP | TARP | 88.25 | 35.30 | 28.24 | 7.06 | 6 | 1 | 0 | Yes |
| 23 | T S1 APARTMENT | 0.0 | 11.58 | 0.00 | 9.14 | 17.37 | 3.81 | 10.67 | 1 | 1 | 1 | 11.58 | 23.16 | 0.00 | 7.62 | 9.14 | 12.19 | 3.05 | 268.97 | TARP | TARP | 88.25 | 35.30 | 28.24 | 7.06 | 6 | 1 | 0 | Yes |
| 24 | T S2 APARTMENT | 0.0 | 23.16 | 0.00 | 9.14 | 28.95 | 3.81 | 10.67 | 1 | 1 | 1 | 23.16 | 34.75 | 0.00 | 7.62 | 9.14 | 12.19 | 3.05 | 268.97 | TARP | TARP | 88.25 | 35.30 | 28.24 | 7.06 | 6 | 1 | 0 | Yes |
| 25 | T CORRIDOR | 0.0 | 0.00 | 7.62 | 9.14 | 23.16 | 8.46 | 10.67 | 1 | 1 | 1 | 0.00 | 46.33 | 7.62 | 9.30 | 9.14 | 12.19 | 3.05 | 236.69 | TARP | TARP | 77.66 | 10.22 | 9.10 | 1.11 | 12 | 1 | 0 | Yes |
| 26 | G CORRIDOR | 0.0 | 0.00 | 7.62 | 0.00 | 23.16 | 8.46 | 1.52 | 1 | 1 | 1 | 0.00 | 46.33 | 7.62 | 9.30 | 0.00 | 3.05 | 3.05 | 236.69 | TARP | TARP | 77.66 | 10.22 | 6.90 | 3.32 | 12 | 1 | 0 | Yes |
| 27 | M CORRIDOR | 0.0 | 0.00 | 7.62 | 3.05 | 23.16 | 8.46 | 4.57 | 1 | 1 | 2 | 0.00 | 46.33 | 7.62 | 9.30 | 3.05 | 6.10 | 3.05 | 236.69 | TARP | TARP | 77.66 | 10.22 | 9.10 | 1.11 | 12 | 1 | 0 | Yes |
| Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
| 1 | G SW APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 2 | G NW APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 3 | OFFICE | 88.25 | 4.7 | 18.581 | 5.382E-002 | 9.753 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 16.423 | No |
| 4 | G NE APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 5 | G N1 APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 6 | G N2 APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 7 | G S1 APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 8 | G S2 APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 9 | M SW APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 10 | M NW APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 11 | M SE APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 12 | M NE APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 13 | M N1 APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 14 | M N2 APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 15 | M S1 APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 16 | M S2 APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 17 | T SW APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 18 | T NW APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 19 | T SE APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 20 | T NE APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 21 | T N1 APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 22 | T N2 APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 23 | T S1 APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 24 | T S2 APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 25 | T CORRIDOR | 77.66 | 4.2 | 18.579 | 5.382E-002 | 4.772 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 4.772 | No |
| 26 | G CORRIDOR | 77.66 | 4.2 | 18.579 | 5.382E-002 | 4.772 | 105.256 | 0.000 | 0.000 | 0.000 | 0.000 | 110.029 | No |
| 27 | M CORRIDOR | 77.66 | 4.2 | 18.579 | 5.382E-002 | 4.772 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 4.772 | No |
| Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | |
| 1 | OCCUP_GSW | OCC_APT_SCH_WORKING_FAMILY | G SW APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 3 |
| 2 | OCCUP_GNW | OCC_APT_SCH_STAY_HOME_FAMILY | G NW APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 1 | 3 |
| 3 | OCCUP_OFFICE | OCC_OFF_W_SB_SCH | OFFICE | 88.25 | 4.7 | 4.7 | 5.382E-002 | 18.581 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 5 |
| 4 | OCCUP_GNE | OCC_APT_SCH_STAY_HOME_FAMILY | G NE APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 1 | 3 |
| 5 | OCCUP_GN1 | OCC_APT_SCH_STAY_HOME_FAMILY | G N1 APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 1 | 3 |
| 6 | OCCUP_GN2 | OCC_APT_SCH_STAY_HOME_FAMILY | G N2 APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 1 | 3 |
| 7 | OCCUP_GS1 | OCC_APT_SCH_WORKING_FAMILY | G S1 APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 3 |
| 8 | OCCUP_GS2 | OCC_APT_SCH_WORKING_FAMILY | G S2 APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 3 |
| 9 | OCCUP_MSW | OCC_APT_SCH_WORKING_FAMILY | M SW APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 3 |
| 10 | OCCUP_MNW | OCC_APT_SCH_STAY_HOME_FAMILY | M NW APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 1 | 3 |
| 11 | OCCUP_MSE | OCC_APT_SCH_WORKING_FAMILY | M SE APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 3 |
| 12 | OCCUP_MNE | OCC_APT_SCH_STAY_HOME_FAMILY | M NE APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 1 | 3 |
| 13 | OCCUP_MN1 | OCC_APT_SCH_STAY_HOME_FAMILY | M N1 APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 1 | 3 |
| 14 | OCCUP_MN2 | OCC_APT_SCH_STAY_HOME_FAMILY | M N2 APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 1 | 3 |
| 15 | OCCUP_MS1 | OCC_APT_SCH_WORKING_FAMILY | M S1 APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 3 |
| 16 | OCCUP_MS2 | OCC_APT_SCH_WORKING_FAMILY | M S2 APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 3 |
| 17 | OCCUP_TSW | OCC_APT_SCH_WORKING_FAMILY | T SW APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 3 |
| 18 | OCCUP_TNW | OCC_APT_SCH_STAY_HOME_FAMILY | T NW APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 1 | 3 |
| 19 | OCCUP_TSE | OCC_APT_SCH_WORKING_FAMILY | T SE APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 3 |
| 20 | OCCUP_TNE | OCC_APT_SCH_STAY_HOME_FAMILY | T NE APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 1 | 3 |
| 21 | OCCUP_TN1 | OCC_APT_SCH_STAY_HOME_FAMILY | T N1 APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 1 | 3 |
| 22 | OCCUP_TN2 | OCC_APT_SCH_STAY_HOME_FAMILY | T N2 APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 1 | 3 |
| 23 | OCCUP_TS1 | OCC_APT_SCH_WORKING_FAMILY | T S1 APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 3 |
| 24 | OCCUP_TS2 | OCC_APT_SCH_WORKING_FAMILY | T S2 APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 3 |
| 25 | OCCUP_T CORRIDOR | OCC_APT_SCH_CORRIDOR | T CORRIDOR | 77.66 | 4.2 | 4.2 | 5.382E-002 | 18.579 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 1 | 4 |
| 26 | OCCUP_G CORRIDOR | OCC_APT_SCH_CORRIDOR | G CORRIDOR | 77.66 | 4.2 | 4.2 | 5.382E-002 | 18.579 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 1 | 4 |
| 27 | OCCUP_M CORRIDOR | OCC_APT_SCH_CORRIDOR | M CORRIDOR | 77.66 | 4.2 | 4.2 | 5.382E-002 | 18.579 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 1 | 4 |
| Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
| 1 | LIGHTING_HARDWIRED_GSW | LTG_SCH_APARTMENT_HARDWIRED | G SW APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 2 | LIGHTING_HARDWIRED_GNW | LTG_SCH_APARTMENT_HARDWIRED | G NW APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 3 | LIGHTING_HARDWIRED_OFFICE | LTG_SCH_OFFICE | OFFICE | 88.25 | 4.7 | 860.710 | 9.753 | 181.220 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 860.710 |
| 4 | LIGHTING_HARDWIRED_GNE | LTG_SCH_APARTMENT_HARDWIRED | G NE APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 5 | LIGHTING_HARDWIRED_GN1 | LTG_SCH_APARTMENT_HARDWIRED | G N1 APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 6 | LIGHTING_HARDWIRED_GN2 | LTG_SCH_APARTMENT_HARDWIRED | G N2 APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 7 | LIGHTING_HARDWIRED_GS1 | LTG_SCH_APARTMENT_HARDWIRED | G S1 APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 8 | LIGHTING_HARDWIRED_GS2 | LTG_SCH_APARTMENT_HARDWIRED | G S2 APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 9 | LIGHTING_HARDWIRED_MSW | LTG_SCH_APARTMENT_HARDWIRED | M SW APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 10 | LIGHTING_HARDWIRED_MNW | LTG_SCH_APARTMENT_HARDWIRED | M NW APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 11 | LIGHTING_HARDWIRED_MSE | LTG_SCH_APARTMENT_HARDWIRED | M SE APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 12 | LIGHTING_HARDWIRED_MNE | LTG_SCH_APARTMENT_HARDWIRED | M NE APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 13 | LIGHTING_HARDWIRED_MN1 | LTG_SCH_APARTMENT_HARDWIRED | M N1 APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 14 | LIGHTING_HARDWIRED_MN2 | LTG_SCH_APARTMENT_HARDWIRED | M N2 APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 15 | LIGHTING_HARDWIRED_MS1 | LTG_SCH_APARTMENT_HARDWIRED | M S1 APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 16 | LIGHTING_HARDWIRED_MS2 | LTG_SCH_APARTMENT_HARDWIRED | M S2 APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 17 | LIGHTING_HARDWIRED_TSW | LTG_SCH_APARTMENT_HARDWIRED | T SW APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 18 | LIGHTING_HARDWIRED_TNW | LTG_SCH_APARTMENT_HARDWIRED | T NW APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 19 | LIGHTING_HARDWIRED_TSE | LTG_SCH_APARTMENT_HARDWIRED | T SE APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 20 | LIGHTING_HARDWIRED_TNE | LTG_SCH_APARTMENT_HARDWIRED | T NE APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 21 | LIGHTING_HARDWIRED_TN1 | LTG_SCH_APARTMENT_HARDWIRED | T N1 APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 22 | LIGHTING_HARDWIRED_TN2 | LTG_SCH_APARTMENT_HARDWIRED | T N2 APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 23 | LIGHTING_HARDWIRED_TS1 | LTG_SCH_APARTMENT_HARDWIRED | T S1 APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 24 | LIGHTING_HARDWIRED_TS2 | LTG_SCH_APARTMENT_HARDWIRED | T S2 APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 25 | LIGHTING_HARDWIRED_GC | LTG_SCH_CORRIDOR | G CORRIDOR | 77.66 | 4.2 | 370.628 | 4.772 | 88.667 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 370.628 |
| 26 | LIGHTING_HARDWIRED_MC | LTG_SCH_CORRIDOR | M CORRIDOR | 77.66 | 4.2 | 370.628 | 4.772 | 88.667 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 370.628 |
| 27 | LIGHTING_HARDWIRED_TC | LTG_SCH_CORRIDOR | T CORRIDOR | 77.66 | 4.2 | 370.628 | 4.772 | 88.667 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 370.628 |
| 28 | LIGHTING_PLUGIN_GSW | LTG_SCH_APARTMENT_PLUGIN | G SW APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| 29 | LIGHTING_PLUGIN_GNW | LTG_SCH_APARTMENT_PLUGIN | G NW APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| 30 | LIGHTING_PLUGIN_GNE | LTG_SCH_APARTMENT_PLUGIN | G NE APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| 31 | LIGHTING_PLUGIN_GN1 | LTG_SCH_APARTMENT_PLUGIN | G N1 APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| 32 | LIGHTING_PLUGIN_GN2 | LTG_SCH_APARTMENT_PLUGIN | G N2 APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| 33 | LIGHTING_PLUGIN_GS1 | LTG_SCH_APARTMENT_PLUGIN | G S1 APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| 34 | LIGHTING_PLUGIN_GS2 | LTG_SCH_APARTMENT_PLUGIN | G S2 APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| 35 | LIGHTING_PLUGIN_MSW | LTG_SCH_APARTMENT_PLUGIN | M SW APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| 36 | LIGHTING_PLUGIN_MNW | LTG_SCH_APARTMENT_PLUGIN | M NW APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| 37 | LIGHTING_PLUGIN_MSE | LTG_SCH_APARTMENT_PLUGIN | M SE APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| 38 | LIGHTING_PLUGIN_MNE | LTG_SCH_APARTMENT_PLUGIN | M NE APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| 39 | LIGHTING_PLUGIN_MN1 | LTG_SCH_APARTMENT_PLUGIN | M N1 APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| 40 | LIGHTING_PLUGIN_MN2 | LTG_SCH_APARTMENT_PLUGIN | M N2 APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| 41 | LIGHTING_PLUGIN_MS1 | LTG_SCH_APARTMENT_PLUGIN | M S1 APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| 42 | LIGHTING_PLUGIN_MS2 | LTG_SCH_APARTMENT_PLUGIN | M S2 APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| 43 | LIGHTING_PLUGIN_TSW | LTG_SCH_APARTMENT_PLUGIN | T SW APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| 44 | LIGHTING_PLUGIN_TNW | LTG_SCH_APARTMENT_PLUGIN | T NW APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| 45 | LIGHTING_PLUGIN_TSE | LTG_SCH_APARTMENT_PLUGIN | T SE APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| 46 | LIGHTING_PLUGIN_TNE | LTG_SCH_APARTMENT_PLUGIN | T NE APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| 47 | LIGHTING_PLUGIN_TN1 | LTG_SCH_APARTMENT_PLUGIN | T N1 APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| 48 | LIGHTING_PLUGIN_TN2 | LTG_SCH_APARTMENT_PLUGIN | T N2 APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| 49 | LIGHTING_PLUGIN_TS1 | LTG_SCH_APARTMENT_PLUGIN | T S1 APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| 50 | LIGHTING_PLUGIN_TS2 | LTG_SCH_APARTMENT_PLUGIN | T S2 APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
| 1 | PLUG_GSW | EQP_APT_SCH | G SW APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 2 | PLUG_GNW | EQP_APT_SCH | G NW APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 3 | PLUG_OFFICE | EQP_OFF_SCH | OFFICE | 88.25 | 4.7 | 588.623 | 6.670 | 123.933 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 588.623 |
| 4 | PLUG_GNE | EQP_APT_SCH | G NE APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 5 | PLUG_GN1 | EQP_APT_SCH | G N1 APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 6 | PLUG_GN2 | EQP_APT_SCH | G N2 APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 7 | PLUG_GS1 | EQP_APT_SCH | G S1 APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 8 | PLUG_GS2 | EQP_APT_SCH | G S2 APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 9 | PLUG_MSW | EQP_APT_SCH | M SW APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 10 | PLUG_MNW | EQP_APT_SCH | M NW APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 11 | PLUG_MSE | EQP_APT_SCH | M SE APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 12 | PLUG_MNE | EQP_APT_SCH | M NE APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 13 | PLUG_MN1 | EQP_APT_SCH | M N1 APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 14 | PLUG_MN2 | EQP_APT_SCH | M N2 APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 15 | PLUG_MS1 | EQP_APT_SCH | M S1 APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 16 | PLUG_MS2 | EQP_APT_SCH | M S2 APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 17 | PLUG_TSW | EQP_APT_SCH | T SW APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 18 | PLUG_TNW | EQP_APT_SCH | T NW APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 19 | PLUG_TSE | EQP_APT_SCH | T SE APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 20 | PLUG_TNE | EQP_APT_SCH | T NE APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 21 | PLUG_TN1 | EQP_APT_SCH | T N1 APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 22 | PLUG_TN2 | EQP_APT_SCH | T N2 APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 23 | PLUG_TS1 | EQP_APT_SCH | T S1 APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 24 | PLUG_TS2 | EQP_APT_SCH | T S2 APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 25 | G CORRIDOR_ELEVATORS_EQUIP | BLDG_ELEVATORS | G CORRIDOR | 77.66 | 4.2 | 8012.150 | 103.170 | 1916.782 | 0.000 | 0.000 | 0.950 | 5.000E-002 | ElevatorLift | 961.458 | 4006.075 |
| 26 | ELEVATORS_LIGHTS_FAN | ELEV_LIGHT_FAN_SCH_24_7 | G CORRIDOR | 77.66 | 4.2 | 162.000 | 2.086 | 38.756 | 0.000 | 0.000 | 0.950 | 5.000E-002 | ElevatorLightsFan | 162.000 | 162.000 |
| Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
| 1 | PolygonClipping | Periodic | 20 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
| Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
| 1 | WaterHeater:Mixed | G SW APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.496 | 0.7729 |
| 2 | WaterHeater:Mixed | G NW APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.496 | 0.7729 |
| 3 | WaterHeater:Mixed | G NE APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.496 | 0.7729 |
| 4 | WaterHeater:Mixed | G N1 APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.496 | 0.7729 |
| 5 | WaterHeater:Mixed | G N2 APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.496 | 0.7729 |
| 6 | WaterHeater:Mixed | G S1 APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.496 | 0.7729 |
| 7 | WaterHeater:Mixed | G S2 APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.496 | 0.7729 |
| 8 | WaterHeater:Mixed | M SW APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.498 | 0.7911 |
| 9 | WaterHeater:Mixed | M NW APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.498 | 0.7911 |
| 10 | WaterHeater:Mixed | M SE APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.498 | 0.7911 |
| 11 | WaterHeater:Mixed | M NE APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.498 | 0.7911 |
| 12 | WaterHeater:Mixed | M N1 APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.498 | 0.7911 |
| 13 | WaterHeater:Mixed | M N2 APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.498 | 0.7911 |
| 14 | WaterHeater:Mixed | M S1 APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.498 | 0.7911 |
| 15 | WaterHeater:Mixed | M S2 APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.498 | 0.7911 |
| 16 | WaterHeater:Mixed | T SW APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.496 | 0.7729 |
| 17 | WaterHeater:Mixed | T NW APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.496 | 0.7729 |
| 18 | WaterHeater:Mixed | T SE APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.496 | 0.7729 |
| 19 | WaterHeater:Mixed | T NE APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.496 | 0.7729 |
| 20 | WaterHeater:Mixed | T N1 APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.496 | 0.7729 |
| 21 | WaterHeater:Mixed | T N2 APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.496 | 0.7729 |
| 22 | WaterHeater:Mixed | T S1 APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.496 | 0.7729 |
| 23 | WaterHeater:Mixed | T S2 APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.496 | 0.7729 |
| Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
| 1 | G SWALL SWA | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 2 | GWINDOW1 S SWA | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 3 | G WWALL SWA | 0 | 154.67 | 58.21 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 4 | GWINDOW1 W SWA | 0 | 154.67 | 58.21 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 5 | G NIWALL SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 6 | G EIWALL SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 7 | G GFLOOR SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 8 | G CEILIN SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 9 | G INTERNALMASS SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 10 | G NWALL NWA | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 11 | GWINDOW1 N NWA | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 12 | G WWALL NWA | 0 | 154.67 | 58.21 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 13 | GWINDOW1 W NWA | 0 | 154.67 | 58.21 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 14 | G SIWALL NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 15 | G EIWALL NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 16 | G GFLOOR NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 17 | G CEILIN NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 18 | G INTERNALMASS NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 19 | G SWALL SEA | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 20 | GWINDOW1 S SEA | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 21 | G EWALL SEA | 0 | 154.67 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 22 | GWINDOW1 E SEA | 0 | 154.67 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 23 | G NIWALL SEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 24 | iz-G EIWALL S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 25 | G GFLOOR SEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 26 | G CEILIN SEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 27 | G INTERNALMASS SEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 28 | G NWALL NEA | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 29 | GWINDOW1 N NEA | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 30 | G EWALL NEA | 0 | 154.67 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 31 | GWINDOW1 E NEA | 0 | 154.67 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 32 | G SIWALL NEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 33 | iz-G EIWALL N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 34 | G GFLOOR NEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 35 | G CEILIN NEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 36 | G INTERNALMASS NEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 37 | G NWALL N1A | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 3 | No | No |
| 38 | GWINDOW1 N N1A | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 2 | No | No |
| 39 | G SIWALL N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 40 | G EIWALL N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 41 | iz-G EIWALL NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 42 | G GFLOOR N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 43 | G CEILIN N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 44 | G INTERNALMASS N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 45 | G NWALL N2A | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 3 | No | No |
| 46 | GWINDOW1 N N2A | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 2 | No | No |
| 47 | G SIWALL N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 48 | G EIWALL N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 49 | iz-G EIWALL N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 50 | G GFLOOR N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 51 | G CEILIN N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 52 | G INTERNALMASS N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 53 | G SWALL S1A | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 3 | No | No |
| 54 | GWINDOW1 S S1A | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 2 | No | No |
| 55 | G NIWALL S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 56 | G EIWALL S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 57 | iz-G EIWALL SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 58 | G GFLOOR S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 59 | G CEILIN S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 60 | G INTERNALMASS S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 61 | G SWALL S2A | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 3 | No | No |
| 62 | GWINDOW1 S S2A | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 2 | No | No |
| 63 | G NIWALL S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 64 | G EIWALL S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 65 | iz-G EIWALL S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 66 | G GFLOOR S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 67 | G CEILIN S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 68 | G INTERNALMASS S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 69 | M WWALL SWA | 0 | 154.67 | 58.21 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 70 | MWINDOW1 W SWA | 0 | 154.67 | 58.21 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 71 | M SWALL SWA | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 72 | MWINDOW1 S SWA | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 73 | M NIWALL SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 74 | M EIWALL SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 75 | M GFLOOR SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 76 | M CEILIN SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 77 | M INTERNALMASS SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 78 | M NWALL NWA | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 79 | MWINDOW1 N NWA | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 80 | M WWALL NWA | 0 | 154.67 | 58.21 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 81 | MWINDOW1 W NWA | 0 | 154.67 | 58.21 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 82 | M SIWALL NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 83 | M EIWALL NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 84 | M GFLOOR NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 85 | M CEILIN NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 86 | M INTERNALMASS NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 87 | M EWALL SEA | 0 | 154.67 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 88 | MWINDOW1 E SEA | 0 | 154.67 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 89 | M SWALL SEA | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 90 | MWINDOW1 S SEA | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 91 | M NIWALL SEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 92 | iz-M EIWALL S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 93 | M GFLOOR SEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 94 | M CEILIN SEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 95 | M INTERNALMASS SEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 96 | M NWALL NEA | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 97 | MWINDOW1 N NEA | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 98 | M EWALL NEA | 0 | 154.67 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 99 | MWINDOW1 E NEA | 0 | 154.67 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 100 | M SIWALL NEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 101 | iz-M EIWALL N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 102 | M GFLOOR NEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 103 | M CEILIN NEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 104 | M INTERNALMASS NEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 105 | M NWALL N1A | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 3 | No | No |
| 106 | MWINDOW1 N N1A | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 2 | No | No |
| 107 | M SIWALL N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 108 | M EIWALL N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 109 | iz-M EIWALL NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 110 | M GFLOOR N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 111 | M CEILIN N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 112 | M INTERNALMASS N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 113 | M NWALL N2A | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 3 | No | No |
| 114 | MWINDOW1 N N2A | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 2 | No | No |
| 115 | M SIWALL N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 116 | M EIWALL N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 117 | iz-M EIWALL N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 118 | M GFLOOR N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 119 | M CEILIN N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 120 | M INTERNALMASS N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 121 | M SWALL S1A | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 3 | No | No |
| 122 | MWINDOW1 S S1A | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 2 | No | No |
| 123 | M NIWALL S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 124 | M EIWALL S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 125 | iz-M EIWALL SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 126 | M GFLOOR S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 127 | M CEILIN S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 128 | M INTERNALMASS S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 129 | M SWALL S2A | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 3 | No | No |
| 130 | MWINDOW1 S S2A | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 2 | No | No |
| 131 | M NIWALL S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 132 | M EIWALL S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 133 | iz-M EIWALL S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 134 | M GFLOOR S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 135 | M CEILIN S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 136 | M INTERNALMASS S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 137 | T WWALL SWA | 0 | 154.67 | 58.21 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 138 | TWINDOW1 W SWA | 0 | 154.67 | 58.21 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 139 | T SWALL SWA | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 140 | TWINDOW1 S SWA | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 141 | T NIWALL SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 142 | T EIWALL SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 143 | T GFLOOR SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 144 | T ROOF SWA | 0 | 783.65 | 155.90 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 145 | T INTERNALMASS SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 146 | T NWALL NWA | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 147 | TWINDOW1 N NWA | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 148 | T WWALL NWA | 0 | 154.67 | 58.21 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 149 | TWINDOW1 W NWA | 0 | 154.67 | 58.21 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 150 | T SIWALL NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 151 | T EIWALL NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 152 | T GFLOOR NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 153 | T ROOF NWA | 0 | 783.65 | 155.90 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 154 | T INTERNALMASS NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 155 | T EWALL SEA | 0 | 154.67 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 156 | TWINDOW1 E SEA | 0 | 154.67 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 157 | T SWALL SEA | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 158 | TWINDOW1 S SEA | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 159 | T NIWALL SEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 160 | iz-T EIWALL S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 161 | T GFLOOR SEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 162 | T ROOF SEA | 0 | 783.65 | 155.90 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 163 | T INTERNALMASS SEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 164 | T NWALL NEA | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 165 | TWINDOW1 N NEA | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 166 | T EWALL NEA | 0 | 154.67 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 167 | TWINDOW1 E NEA | 0 | 154.67 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 168 | T SIWALL NEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 169 | iz-T EIWALL N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 170 | T GFLOOR NEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 171 | T ROOF NEA | 0 | 783.65 | 155.90 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 172 | T INTERNALMASS NEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 173 | T NWALL N1A | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 3 | No | No |
| 174 | TWINDOW1 N N1A | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 2 | No | No |
| 175 | T SIWALL N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 176 | T EIWALL N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 177 | iz-T EIWALL NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 178 | T GFLOOR N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 179 | T ROOF N1A | 0 | 783.65 | 155.90 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 180 | T INTERNALMASS N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 181 | T NWALL N2A | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 3 | No | No |
| 182 | TWINDOW1 N N2A | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 2 | No | No |
| 183 | T SIWALL N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 184 | T EIWALL N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 185 | iz-T EIWALL N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 186 | T GFLOOR N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 187 | T ROOF N2A | 0 | 783.65 | 155.90 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 188 | T INTERNALMASS N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 189 | T SWALL S1A | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 3 | No | No |
| 190 | TWINDOW1 S S1A | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 2 | No | No |
| 191 | T NIWALL S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 192 | T EIWALL S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 193 | iz-T EIWALL SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 194 | T GFLOOR S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 195 | T ROOF S1A | 0 | 783.65 | 155.90 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 196 | T INTERNALMASS S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 197 | T SWALL S2A | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 3 | No | No |
| 198 | TWINDOW1 S S2A | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 2 | No | No |
| 199 | T NIWALL S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 200 | T EIWALL S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 201 | iz-T EIWALL S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 202 | T GFLOOR S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 203 | T ROOF S2A | 0 | 783.65 | 155.90 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 204 | T INTERNALMASS S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 205 | T WWALL C | 0 | 154.67 | 58.21 | 12.19 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 3 | No | No |
| 206 | T EWALL C | 0 | 154.67 | 123.02 | 12.19 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 3 | No | No |
| 207 | TWINDOW14 | 0 | 154.67 | 123.02 | 12.19 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 2 | No | No |
| 208 | iz-T NIWALL SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 209 | iz-T NIWALL S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 210 | iz-T NIWALL S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 211 | iz-T NIWALL SEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 212 | iz-T SIWALL NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 213 | iz-T SIWALL N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 214 | iz-T SIWALL N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 215 | iz-T SIWALL NEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 216 | T FLOOR C | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 217 | T ROOF C | 0 | 783.65 | 155.90 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 218 | G WWALL C | 0 | 154.67 | 58.21 | 12.19 | 0 | 3.05 | 3.35 | 3.24 | 0.32 | 4 | No | No |
| 219 | G EWALL C | 0 | 154.67 | 123.02 | 12.19 | 0 | 3.05 | 3.35 | 3.24 | 0.32 | 4 | No | No |
| 220 | ENTRANCE DOOR | 0 | 154.67 | 123.02 | 12.19 | 0 | 3.05 | 3.35 | 3.24 | 0.32 | 1 | No | No |
| 221 | iz-G NIWALL SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.32 | 0 | No | No |
| 222 | iz-G NIWALL S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.32 | 0 | No | No |
| 223 | iz-G NIWALL S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.32 | 0 | No | No |
| 224 | iz-G NIWALL SEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.32 | 0 | No | No |
| 225 | iz-G SIWALL NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.32 | 0 | No | No |
| 226 | iz-G SIWALL N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.32 | 0 | No | No |
| 227 | iz-G SIWALL N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.32 | 0 | No | No |
| 228 | iz-G SIWALL NEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.32 | 0 | No | No |
| 229 | G FLOOR C | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.32 | 0 | No | No |
| 230 | G CEILING C | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.32 | 0 | No | No |
| 231 | M WWALL C | 0 | 154.67 | 58.21 | 12.19 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 4 | No | No |
| 232 | M EWALL C | 0 | 154.67 | 123.02 | 12.19 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 3 | No | No |
| 233 | MWINDOW14 | 0 | 154.67 | 123.02 | 12.19 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 2 | No | No |
| 234 | iz-M NIWALL SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 235 | iz-M NIWALL S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 236 | iz-M NIWALL S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 237 | iz-M NIWALL SEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 238 | iz-M SIWALL NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 239 | iz-M SIWALL N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 240 | iz-M SIWALL N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 241 | iz-M SIWALL NEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 242 | M FLOOR C | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 243 | M CEILING C | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
| 1 | INFIL_GSW | INF_APT_SCH | G SW APARTMENT | 88.25 | 2.5 | 3.333E-002 | 3.777E-004 | 5.696E-004 | 0.446 | 0.000 | 0.000 | 0.224 | 0.000 |
| 2 | INFIL_GNW | INF_APT_SCH | G NW APARTMENT | 88.25 | 2.5 | 3.333E-002 | 3.777E-004 | 5.696E-004 | 0.446 | 0.000 | 0.000 | 0.224 | 0.000 |
| 3 | INFIL_OFFICE | INF_OFF_SCH | OFFICE | 88.25 | 4.7 | 3.333E-002 | 3.777E-004 | 5.696E-004 | 0.446 | 0.000 | 0.000 | 0.224 | 0.000 |
| 4 | INFIL_GNE | INF_APT_SCH | G NE APARTMENT | 88.25 | 2.5 | 3.333E-002 | 3.777E-004 | 5.696E-004 | 0.446 | 0.000 | 0.000 | 0.224 | 0.000 |
| 5 | INFIL_GN1 | INF_APT_SCH | G N1 APARTMENT | 88.25 | 2.5 | 2.011E-002 | 2.278E-004 | 5.696E-004 | 0.269 | 0.000 | 0.000 | 0.224 | 0.000 |
| 6 | INFIL_GN2 | INF_APT_SCH | G N2 APARTMENT | 88.25 | 2.5 | 2.011E-002 | 2.278E-004 | 5.696E-004 | 0.269 | 0.000 | 0.000 | 0.224 | 0.000 |
| 7 | INFIL_GS1 | INF_APT_SCH | G S1 APARTMENT | 88.25 | 2.5 | 2.011E-002 | 2.278E-004 | 5.696E-004 | 0.269 | 0.000 | 0.000 | 0.224 | 0.000 |
| 8 | INFIL_GS2 | INF_APT_SCH | G S2 APARTMENT | 88.25 | 2.5 | 2.011E-002 | 2.278E-004 | 5.696E-004 | 0.269 | 0.000 | 0.000 | 0.224 | 0.000 |
| 9 | INFIL_MSW | INF_APT_SCH | M SW APARTMENT | 88.25 | 2.5 | 3.333E-002 | 3.777E-004 | 5.696E-004 | 0.446 | 0.000 | 0.000 | 0.224 | 0.000 |
| 10 | INFIL_MNW | INF_APT_SCH | M NW APARTMENT | 88.25 | 2.5 | 3.333E-002 | 3.777E-004 | 5.696E-004 | 0.446 | 0.000 | 0.000 | 0.224 | 0.000 |
| 11 | INFIL_MSE | INF_APT_SCH | M SE APARTMENT | 88.25 | 2.5 | 3.333E-002 | 3.777E-004 | 5.696E-004 | 0.446 | 0.000 | 0.000 | 0.224 | 0.000 |
| 12 | INFIL_MNE | INF_APT_SCH | M NE APARTMENT | 88.25 | 2.5 | 3.333E-002 | 3.777E-004 | 5.696E-004 | 0.446 | 0.000 | 0.000 | 0.224 | 0.000 |
| 13 | INFIL_MN1 | INF_APT_SCH | M N1 APARTMENT | 88.25 | 2.5 | 2.011E-002 | 2.278E-004 | 5.696E-004 | 0.269 | 0.000 | 0.000 | 0.224 | 0.000 |
| 14 | INFIL_MN2 | INF_APT_SCH | M N2 APARTMENT | 88.25 | 2.5 | 2.011E-002 | 2.278E-004 | 5.696E-004 | 0.269 | 0.000 | 0.000 | 0.224 | 0.000 |
| 15 | INFIL_MS1 | INF_APT_SCH | M S1 APARTMENT | 88.25 | 2.5 | 2.011E-002 | 2.278E-004 | 5.696E-004 | 0.269 | 0.000 | 0.000 | 0.224 | 0.000 |
| 16 | INFIL_MS2 | INF_APT_SCH | M S2 APARTMENT | 88.25 | 2.5 | 2.011E-002 | 2.278E-004 | 5.696E-004 | 0.269 | 0.000 | 0.000 | 0.224 | 0.000 |
| 17 | INFIL_SW | INF_APT_SCH | T SW APARTMENT | 88.25 | 2.5 | 3.333E-002 | 3.777E-004 | 2.271E-004 | 0.446 | 0.000 | 0.000 | 0.224 | 0.000 |
| 18 | INFIL_NW | INF_APT_SCH | T NW APARTMENT | 88.25 | 2.5 | 3.333E-002 | 3.777E-004 | 2.271E-004 | 0.446 | 0.000 | 0.000 | 0.224 | 0.000 |
| 19 | INFIL_SE | INF_APT_SCH | T SE APARTMENT | 88.25 | 2.5 | 3.333E-002 | 3.777E-004 | 2.271E-004 | 0.446 | 0.000 | 0.000 | 0.224 | 0.000 |
| 20 | INFIL_NE | INF_APT_SCH | T NE APARTMENT | 88.25 | 2.5 | 3.333E-002 | 3.777E-004 | 2.271E-004 | 0.446 | 0.000 | 0.000 | 0.224 | 0.000 |
| 21 | INFIL_TN1 | INF_APT_SCH | T N1 APARTMENT | 88.25 | 2.5 | 2.011E-002 | 2.278E-004 | 1.627E-004 | 0.269 | 0.000 | 0.000 | 0.224 | 0.000 |
| 22 | INFIL_TN2 | INF_APT_SCH | T N2 APARTMENT | 88.25 | 2.5 | 2.011E-002 | 2.278E-004 | 1.627E-004 | 0.269 | 0.000 | 0.000 | 0.224 | 0.000 |
| 23 | INFIL_TS1 | INF_APT_SCH | T S1 APARTMENT | 88.25 | 2.5 | 2.011E-002 | 2.278E-004 | 1.627E-004 | 0.269 | 0.000 | 0.000 | 0.224 | 0.000 |
| 24 | INFIL_TS2 | INF_APT_SCH | T S2 APARTMENT | 88.25 | 2.5 | 2.011E-002 | 2.278E-004 | 1.627E-004 | 0.269 | 0.000 | 0.000 | 0.224 | 0.000 |
| 25 | INFIL_GC | INF_COR_SCH | G CORRIDOR | 77.66 | 4.2 | 5.820E-003 | 7.494E-005 | 5.696E-004 | 8.852E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
| 26 | DOOR_INFIL_GC | INFIL_DOOR_OPENING_SCH | G CORRIDOR | 77.66 | 4.2 | 0.521 | 6.703E-003 | 5.094E-002 | 7.917 | 1.000 | 0.000 | 0.000 | 0.000 |
| 27 | INFIL_MC | INF_COR_SCH | M CORRIDOR | 77.66 | 4.2 | 5.820E-003 | 7.494E-005 | 5.696E-004 | 8.852E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
| 28 | INFIL_TC | INF_COR_SCH | T CORRIDOR | 77.66 | 4.2 | 5.820E-003 | 7.494E-005 | 6.623E-005 | 8.852E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
| Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
| 1 | G SW APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | G SW APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 2 | G NW APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | G NW APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 3 | G NE APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | G NE APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 4 | G N1 APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | G N1 APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 5 | G N2 APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | G N2 APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 6 | G S1 APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | G S1 APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 7 | G S2 APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | G S2 APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 8 | M SW APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | M SW APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 9 | M NW APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | M NW APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 10 | M SE APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | M SE APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 11 | M NE APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | M NE APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 12 | M N1 APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | M N1 APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 13 | M N2 APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | M N2 APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 14 | M S1 APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | M S1 APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 15 | M S2 APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | M S2 APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 16 | T SW APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | T SW APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 17 | T NW APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | T NW APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 18 | T SE APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | T SE APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 19 | T NE APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | T NE APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 20 | T N1 APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | T N1 APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 21 | T N2 APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | T N2 APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 22 | T S1 APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | T S1 APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 23 | T S2 APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | T S2 APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| Simple | |
| 1 | Simple |
| Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
| 1 | G SW APARTMENT | Mixing/Well-Stirred |
| 2 | G NW APARTMENT | Mixing/Well-Stirred |
| 3 | OFFICE | Mixing/Well-Stirred |
| 4 | G NE APARTMENT | Mixing/Well-Stirred |
| 5 | G N1 APARTMENT | Mixing/Well-Stirred |
| 6 | G N2 APARTMENT | Mixing/Well-Stirred |
| 7 | G S1 APARTMENT | Mixing/Well-Stirred |
| 8 | G S2 APARTMENT | Mixing/Well-Stirred |
| 9 | M SW APARTMENT | Mixing/Well-Stirred |
| 10 | M NW APARTMENT | Mixing/Well-Stirred |
| 11 | M SE APARTMENT | Mixing/Well-Stirred |
| 12 | M NE APARTMENT | Mixing/Well-Stirred |
| 13 | M N1 APARTMENT | Mixing/Well-Stirred |
| 14 | M N2 APARTMENT | Mixing/Well-Stirred |
| 15 | M S1 APARTMENT | Mixing/Well-Stirred |
| 16 | M S2 APARTMENT | Mixing/Well-Stirred |
| 17 | T SW APARTMENT | Mixing/Well-Stirred |
| 18 | T NW APARTMENT | Mixing/Well-Stirred |
| 19 | T SE APARTMENT | Mixing/Well-Stirred |
| 20 | T NE APARTMENT | Mixing/Well-Stirred |
| 21 | T N1 APARTMENT | Mixing/Well-Stirred |
| 22 | T N2 APARTMENT | Mixing/Well-Stirred |
| 23 | T S1 APARTMENT | Mixing/Well-Stirred |
| 24 | T S2 APARTMENT | Mixing/Well-Stirred |
| 25 | T CORRIDOR | Mixing/Well-Stirred |
| 26 | G CORRIDOR | Mixing/Well-Stirred |
| 27 | M CORRIDOR | Mixing/Well-Stirred |
| No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
| 1 | NoMultizoneOrDistribution |
| Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
| 1 | 1.000 | 1.000 | 1.000 | 1.000 |
| Value | |
| 1 | 6 |
| Sizing Factor ID | Value | |
| 1 | Global | 1.2000 |
| 2 | Zone G SW APARTMENT | 1.2000 |
| 3 | Zone G NW APARTMENT | 1.2000 |
| 4 | Zone OFFICE | 1.2000 |
| 5 | Zone G NE APARTMENT | 1.2000 |
| 6 | Zone G N1 APARTMENT | 1.2000 |
| 7 | Zone G N2 APARTMENT | 1.2000 |
| 8 | Zone G S1 APARTMENT | 1.2000 |
| 9 | Zone G S2 APARTMENT | 1.2000 |
| 10 | Zone M SW APARTMENT | 1.2000 |
| 11 | Zone M NW APARTMENT | 1.2000 |
| 12 | Zone M SE APARTMENT | 1.2000 |
| 13 | Zone M NE APARTMENT | 1.2000 |
| 14 | Zone M N1 APARTMENT | 1.2000 |
| 15 | Zone M N2 APARTMENT | 1.2000 |
| 16 | Zone M S1 APARTMENT | 1.2000 |
| 17 | Zone M S2 APARTMENT | 1.2000 |
| 18 | Zone T SW APARTMENT | 1.2000 |
| 19 | Zone T NW APARTMENT | 1.2000 |
| 20 | Zone T SE APARTMENT | 1.2000 |
| 21 | Zone T NE APARTMENT | 1.2000 |
| 22 | Zone T N1 APARTMENT | 1.2000 |
| 23 | Zone T N2 APARTMENT | 1.2000 |
| 24 | Zone T S1 APARTMENT | 1.2000 |
| 25 | Zone T S2 APARTMENT | 1.2000 |
| Sizing Factor ID | Value | |
| 1 | Global | 1.2000 |
| 2 | Zone G SW APARTMENT | 1.2000 |
| 3 | Zone G NW APARTMENT | 1.2000 |
| 4 | Zone OFFICE | 1.2000 |
| 5 | Zone G NE APARTMENT | 1.2000 |
| 6 | Zone G N1 APARTMENT | 1.2000 |
| 7 | Zone G N2 APARTMENT | 1.2000 |
| 8 | Zone G S1 APARTMENT | 1.2000 |
| 9 | Zone G S2 APARTMENT | 1.2000 |
| 10 | Zone M SW APARTMENT | 1.2000 |
| 11 | Zone M NW APARTMENT | 1.2000 |
| 12 | Zone M SE APARTMENT | 1.2000 |
| 13 | Zone M NE APARTMENT | 1.2000 |
| 14 | Zone M N1 APARTMENT | 1.2000 |
| 15 | Zone M N2 APARTMENT | 1.2000 |
| 16 | Zone M S1 APARTMENT | 1.2000 |
| 17 | Zone M S2 APARTMENT | 1.2000 |
| 18 | Zone T SW APARTMENT | 1.2000 |
| 19 | Zone T NW APARTMENT | 1.2000 |
| 20 | Zone T SE APARTMENT | 1.2000 |
| 21 | Zone T NE APARTMENT | 1.2000 |
| 22 | Zone T N1 APARTMENT | 1.2000 |
| 23 | Zone T N2 APARTMENT | 1.2000 |
| 24 | Zone T S1 APARTMENT | 1.2000 |
| 25 | Zone T S2 APARTMENT | 1.2000 |
| Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
| 1 | G SW APARTMENT | Cooling | 4059.61537 | 4871.53845 | 0.28668 | 0.34401 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 29.21400 | 1.41144E-002 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 2 | G SW APARTMENT | Heating | 2233.12887 | 2679.75465 | 9.62658E-002 | 0.11552 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:50:00 | -10.70000 | 1.50390E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 3 | G NW APARTMENT | Cooling | 3876.11655 | 4651.33986 | 0.27339 | 0.32807 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 29.21400 | 1.41144E-002 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 4 | G NW APARTMENT | Heating | 2123.18000 | 2547.81600 | 9.15266E-002 | 0.10983 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -10.70000 | 1.50390E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 5 | OFFICE | Cooling | 4673.32916 | 5607.99499 | 0.33534 | 0.40241 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 28.03000 | 1.41123E-002 | 88.24927 | 4.74953 | 3.81060E-002 | 0.00000 |
| 6 | OFFICE | Heating | 2677.11467 | 3212.53761 | 0.11541 | 0.13849 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 18:50:00 | -10.70000 | 1.50390E-003 | 88.24927 | 4.74953 | 3.81060E-002 | 0.00000 |
| 7 | G NE APARTMENT | Cooling | 3582.20800 | 4298.64961 | 0.25224 | 0.30269 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 29.21400 | 1.41144E-002 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 8 | G NE APARTMENT | Heating | 2115.97145 | 2539.16574 | 9.12158E-002 | 0.10946 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -10.70000 | 1.50390E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 9 | G N1 APARTMENT | Cooling | 3222.09067 | 3866.50881 | 0.22619 | 0.27143 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 29.21400 | 1.41144E-002 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 10 | G N1 APARTMENT | Heating | 1292.35956 | 1550.83147 | 5.57125E-002 | 6.68549E-002 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -10.70000 | 1.50390E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 11 | G N2 APARTMENT | Cooling | 3220.10796 | 3864.12956 | 0.22604 | 0.27124 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 29.21400 | 1.41144E-002 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 12 | G N2 APARTMENT | Heating | 1292.14371 | 1550.57245 | 5.57032E-002 | 6.68438E-002 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -10.70000 | 1.50390E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 13 | G S1 APARTMENT | Cooling | 3461.41457 | 4153.69748 | 0.24350 | 0.29220 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 29.21400 | 1.41144E-002 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 14 | G S1 APARTMENT | Heating | 1403.59281 | 1684.31138 | 6.05072E-002 | 7.26087E-002 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:50:00 | -10.70000 | 1.50390E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 15 | G S2 APARTMENT | Cooling | 3483.70306 | 4180.44367 | 0.24512 | 0.29415 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 29.21400 | 1.41144E-002 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 16 | G S2 APARTMENT | Heating | 1411.74322 | 1694.09186 | 6.08586E-002 | 7.30303E-002 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:50:00 | -10.70000 | 1.50390E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 17 | M SW APARTMENT | Cooling | 9822.14033 | 11786.56840 | 0.69664 | 0.83597 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 29.21400 | 1.41144E-002 | 88.24927 | 2.50000 | 5.19091E-002 | 0.00000 |
| 18 | M SW APARTMENT | Heating | 4292.18916 | 5150.62700 | 0.18501 | 0.22201 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | -10.70000 | 1.50390E-003 | 88.24927 | 2.50000 | 5.19091E-002 | 0.00000 |
| 19 | M NW APARTMENT | Cooling | 9525.58936 | 11430.70723 | 0.67523 | 0.81027 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 29.21400 | 1.41144E-002 | 88.24927 | 2.50000 | 5.19091E-002 | 0.00000 |
| 20 | M NW APARTMENT | Heating | 4029.17303 | 4835.00764 | 0.17368 | 0.20841 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | -10.70000 | 1.50390E-003 | 88.24927 | 2.50000 | 5.19091E-002 | 0.00000 |
| 21 | M SE APARTMENT | Cooling | 8974.31047 | 10769.17257 | 0.63540 | 0.76248 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 29.21400 | 1.41144E-002 | 88.24927 | 2.50000 | 5.19091E-002 | 0.00000 |
| 22 | M SE APARTMENT | Heating | 4275.02747 | 5130.03296 | 0.18427 | 0.22112 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | -10.70000 | 1.50390E-003 | 88.24927 | 2.50000 | 5.19091E-002 | 0.00000 |
| 23 | M NE APARTMENT | Cooling | 8685.50534 | 10422.60641 | 0.61447 | 0.73737 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 29.21400 | 1.41144E-002 | 88.24927 | 2.50000 | 5.19091E-002 | 0.00000 |
| 24 | M NE APARTMENT | Heating | 4011.95737 | 4814.34885 | 0.17293 | 0.20752 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | -10.70000 | 1.50390E-003 | 88.24927 | 2.50000 | 5.19091E-002 | 0.00000 |
| 25 | M N1 APARTMENT | Cooling | 7802.55955 | 9363.07146 | 0.55036 | 0.66043 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 29.21400 | 1.41144E-002 | 88.24927 | 2.50000 | 5.19091E-002 | 0.00000 |
| 26 | M N1 APARTMENT | Heating | 2176.09880 | 2611.31856 | 9.38047E-002 | 0.11257 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | -10.70000 | 1.50390E-003 | 88.24927 | 2.50000 | 5.19091E-002 | 0.00000 |
| 27 | M N2 APARTMENT | Cooling | 7785.19323 | 9342.23187 | 0.54911 | 0.65894 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 29.21400 | 1.41144E-002 | 88.24927 | 2.50000 | 5.19091E-002 | 0.00000 |
| 28 | M N2 APARTMENT | Heating | 2175.64540 | 2610.77448 | 9.37852E-002 | 0.11254 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | -10.70000 | 1.50390E-003 | 88.24927 | 2.50000 | 5.19091E-002 | 0.00000 |
| 29 | M S1 APARTMENT | Cooling | 8147.69996 | 9777.23995 | 0.57542 | 0.69051 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 29.21400 | 1.41144E-002 | 88.24927 | 2.50000 | 5.19091E-002 | 0.00000 |
| 30 | M S1 APARTMENT | Heating | 2432.36760 | 2918.84112 | 0.10485 | 0.12582 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | -10.70000 | 1.50390E-003 | 88.24927 | 2.50000 | 5.19091E-002 | 0.00000 |
| 31 | M S2 APARTMENT | Cooling | 8129.68053 | 9755.61664 | 0.57412 | 0.68894 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 29.21400 | 1.41144E-002 | 88.24927 | 2.50000 | 5.19091E-002 | 0.00000 |
| 32 | M S2 APARTMENT | Heating | 2431.91991 | 2918.30390 | 0.10483 | 0.12580 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | -10.70000 | 1.50390E-003 | 88.24927 | 2.50000 | 5.19091E-002 | 0.00000 |
| 33 | T SW APARTMENT | Cooling | 5337.85260 | 6405.42312 | 0.37887 | 0.45465 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 29.21400 | 1.41144E-002 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 34 | T SW APARTMENT | Heating | 3489.27028 | 4187.12434 | 0.15039 | 0.18047 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | -10.70000 | 1.50390E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 35 | T NW APARTMENT | Cooling | 5293.83753 | 6352.60504 | 0.37569 | 0.45082 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 29.21400 | 1.41144E-002 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 36 | T NW APARTMENT | Heating | 3353.17566 | 4023.81079 | 0.14453 | 0.17343 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | -10.70000 | 1.50390E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 37 | T SE APARTMENT | Cooling | 4717.89686 | 5661.47624 | 0.33418 | 0.40102 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 29.21400 | 1.41144E-002 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 38 | T SE APARTMENT | Heating | 3477.43421 | 4172.92106 | 0.14988 | 0.17986 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | -10.70000 | 1.50390E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 39 | T NE APARTMENT | Cooling | 4672.57290 | 5607.08748 | 0.33093 | 0.39711 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 29.21400 | 1.41144E-002 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 40 | T NE APARTMENT | Heating | 3341.27765 | 4009.53318 | 0.14402 | 0.17282 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | -10.70000 | 1.50390E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 41 | T N1 APARTMENT | Cooling | 4364.27230 | 5237.12676 | 0.30865 | 0.37038 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 29.21400 | 1.41144E-002 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 42 | T N1 APARTMENT | Heating | 2226.10730 | 2671.32876 | 9.59572E-002 | 0.11515 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | -10.70000 | 1.50390E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 43 | T N2 APARTMENT | Cooling | 4341.87728 | 5210.25273 | 0.30703 | 0.36844 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 29.21400 | 1.41144E-002 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 44 | T N2 APARTMENT | Heating | 2225.77274 | 2670.92729 | 9.59427E-002 | 0.11513 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | -10.70000 | 1.50390E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 45 | T S1 APARTMENT | Cooling | 4422.33556 | 5306.80267 | 0.31284 | 0.37540 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 29.21400 | 1.41144E-002 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 46 | T S1 APARTMENT | Heating | 2362.18841 | 2834.62609 | 0.10182 | 0.12219 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | -10.70000 | 1.50390E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 47 | T S2 APARTMENT | Cooling | 4400.02724 | 5280.03269 | 0.31123 | 0.37347 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 29.21400 | 1.41144E-002 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 48 | T S2 APARTMENT | Heating | 2361.85808 | 2834.22970 | 0.10181 | 0.12217 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | -10.70000 | 1.50390E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
| 1 | SPLIT GSW | Cooling | Sensible | 4839.48 | 0.34401 | 0.34401 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 2 | SPLIT GSW | Heating | Sensible | 3638.91 | 0.11552 | 0.11552 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:50:00 |
| 3 | SPLIT GNW | Cooling | Sensible | 4621.53 | 0.32807 | 0.32807 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 4 | SPLIT GNW | Heating | Sensible | 3508.90 | 0.10983 | 0.10983 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 |
| 5 | SPLIT OFFICE | Cooling | Sensible | 5616.50 | 0.40241 | 0.40241 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 6 | SPLIT OFFICE | Heating | Sensible | 4631.27 | 0.13849 | 0.13849 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 18:50:00 |
| 7 | SPLIT GNE | Cooling | Sensible | 4273.54 | 0.30269 | 0.30269 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 8 | SPLIT GNE | Heating | Sensible | 3500.37 | 0.10946 | 0.10946 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 |
| 9 | SPLIT GN1 | Cooling | Sensible | 3844.68 | 0.27143 | 0.27143 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 10 | SPLIT GN1 | Heating | Sensible | 2526.45 | 6.68549E-002 | 6.68549E-002 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 |
| 11 | SPLIT GN2 | Cooling | Sensible | 3842.32 | 0.27124 | 0.27124 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 12 | SPLIT GN2 | Heating | Sensible | 2526.19 | 6.68438E-002 | 6.68438E-002 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 |
| 13 | SPLIT GS1 | Cooling | Sensible | 4130.14 | 0.29220 | 0.29220 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 14 | SPLIT GS1 | Heating | Sensible | 2657.98 | 7.26087E-002 | 7.26087E-002 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:50:00 |
| 15 | SPLIT GS2 | Cooling | Sensible | 4156.59 | 0.29415 | 0.29415 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 16 | SPLIT GS2 | Heating | Sensible | 2667.62 | 7.30303E-002 | 7.30303E-002 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:50:00 |
| 17 | SPLIT MSW | Cooling | Sensible | 11701.34 | 0.83597 | 0.83597 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 18 | SPLIT MSW | Heating | Sensible | 7071.87 | 0.22201 | 0.22201 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 |
| 19 | SPLIT MNW | Cooling | Sensible | 11349.94 | 0.81027 | 0.81027 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 20 | SPLIT MNW | Heating | Sensible | 6760.86 | 0.20841 | 0.20841 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 |
| 21 | SPLIT MSE | Cooling | Sensible | 10695.97 | 0.76248 | 0.76248 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 22 | SPLIT MSE | Heating | Sensible | 7051.57 | 0.22112 | 0.22112 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 |
| 23 | SPLIT MNE | Cooling | Sensible | 10352.88 | 0.73737 | 0.73737 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 24 | SPLIT MNE | Heating | Sensible | 6740.50 | 0.20752 | 0.20752 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 |
| 25 | SPLIT MN1 | Cooling | Sensible | 9302.35 | 0.66043 | 0.66043 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 26 | SPLIT MN1 | Heating | Sensible | 4569.63 | 0.11257 | 0.11257 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 |
| 27 | SPLIT MN2 | Cooling | Sensible | 9281.84 | 0.65894 | 0.65894 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 28 | SPLIT MN2 | Heating | Sensible | 4569.09 | 0.11254 | 0.11254 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 |
| 29 | SPLIT MS1 | Cooling | Sensible | 9713.21 | 0.69051 | 0.69051 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 30 | SPLIT MS1 | Heating | Sensible | 4872.65 | 0.12582 | 0.12582 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 |
| 31 | SPLIT MS2 | Cooling | Sensible | 9691.76 | 0.68894 | 0.68894 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 32 | SPLIT MS2 | Heating | Sensible | 4872.12 | 0.12580 | 0.12580 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 |
| 33 | SPLIT TSW | Cooling | Sensible | 6354.22 | 0.45465 | 0.45465 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 34 | SPLIT TSW | Heating | Sensible | 5124.23 | 0.18047 | 0.18047 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 |
| 35 | SPLIT TNW | Cooling | Sensible | 6302.01 | 0.45082 | 0.45082 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 36 | SPLIT TNW | Heating | Sensible | 4963.31 | 0.17343 | 0.17343 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 |
| 37 | SPLIT TSE | Cooling | Sensible | 5620.56 | 0.40102 | 0.40102 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 38 | SPLIT TSE | Heating | Sensible | 5110.24 | 0.17986 | 0.17986 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 |
| 39 | SPLIT TNE | Cooling | Sensible | 5567.01 | 0.39711 | 0.39711 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 40 | SPLIT TNE | Heating | Sensible | 4949.24 | 0.17282 | 0.17282 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 |
| 41 | SPLIT TN1 | Cooling | Sensible | 5201.72 | 0.37038 | 0.37038 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 42 | SPLIT TN1 | Heating | Sensible | 3630.57 | 0.11515 | 0.11515 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 |
| 43 | SPLIT TN2 | Cooling | Sensible | 5175.17 | 0.36844 | 0.36844 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 44 | SPLIT TN2 | Heating | Sensible | 3630.17 | 0.11513 | 0.11513 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 |
| 45 | SPLIT TS1 | Cooling | Sensible | 5270.49 | 0.37540 | 0.37540 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 46 | SPLIT TS1 | Heating | Sensible | 3791.48 | 0.12219 | 0.12219 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 |
| 47 | SPLIT TS2 | Cooling | Sensible | 5244.05 | 0.37347 | 0.37347 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 48 | SPLIT TS2 | Heating | Sensible | 3791.09 | 0.12217 | 0.12217 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 |
| Component Type | Component Name | Input Field Description | Value | |
| 1 | ZoneHVAC:EnergyRecoveryVentilator | G SW APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 2 | ZoneHVAC:EnergyRecoveryVentilator | G SW APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 2.59546E-002 |
| 3 | Fan:OnOff | G SW APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 4 | Fan:OnOff | G SW APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 5 | HeatExchanger:AirToAir:SensibleAndLatent | G SW APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 6 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | G SW APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.34401 |
| 7 | ZoneHVAC:EnergyRecoveryVentilator | G NW APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 8 | ZoneHVAC:EnergyRecoveryVentilator | G NW APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 2.59546E-002 |
| 9 | Fan:OnOff | G NW APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 10 | Fan:OnOff | G NW APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 11 | HeatExchanger:AirToAir:SensibleAndLatent | G NW APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 12 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | G NW APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.32807 |
| 13 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | OFFICE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.40241 |
| 14 | ZoneHVAC:EnergyRecoveryVentilator | G NE APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 15 | ZoneHVAC:EnergyRecoveryVentilator | G NE APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 2.59546E-002 |
| 16 | Fan:OnOff | G NE APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 17 | Fan:OnOff | G NE APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 18 | HeatExchanger:AirToAir:SensibleAndLatent | G NE APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 19 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | G NE APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.30269 |
| 20 | ZoneHVAC:EnergyRecoveryVentilator | G N1 APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 21 | ZoneHVAC:EnergyRecoveryVentilator | G N1 APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 2.59546E-002 |
| 22 | Fan:OnOff | G N1 APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 23 | Fan:OnOff | G N1 APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 24 | HeatExchanger:AirToAir:SensibleAndLatent | G N1 APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 25 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | G N1 APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.27143 |
| 26 | ZoneHVAC:EnergyRecoveryVentilator | G N2 APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 27 | ZoneHVAC:EnergyRecoveryVentilator | G N2 APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 2.59546E-002 |
| 28 | Fan:OnOff | G N2 APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 29 | Fan:OnOff | G N2 APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 30 | HeatExchanger:AirToAir:SensibleAndLatent | G N2 APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 31 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | G N2 APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.27124 |
| 32 | ZoneHVAC:EnergyRecoveryVentilator | G S1 APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 33 | ZoneHVAC:EnergyRecoveryVentilator | G S1 APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 2.59546E-002 |
| 34 | Fan:OnOff | G S1 APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 35 | Fan:OnOff | G S1 APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 36 | HeatExchanger:AirToAir:SensibleAndLatent | G S1 APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 37 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | G S1 APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.29220 |
| 38 | ZoneHVAC:EnergyRecoveryVentilator | G S2 APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 39 | ZoneHVAC:EnergyRecoveryVentilator | G S2 APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 2.59546E-002 |
| 40 | Fan:OnOff | G S2 APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 41 | Fan:OnOff | G S2 APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 42 | HeatExchanger:AirToAir:SensibleAndLatent | G S2 APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 43 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | G S2 APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.29415 |
| 44 | ZoneHVAC:EnergyRecoveryVentilator | M SW APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 5.19091E-002 |
| 45 | ZoneHVAC:EnergyRecoveryVentilator | M SW APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 5.19091E-002 |
| 46 | Fan:OnOff | M SW APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 5.19091E-002 |
| 47 | Fan:OnOff | M SW APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 5.19091E-002 |
| 48 | HeatExchanger:AirToAir:SensibleAndLatent | M SW APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 5.19091E-002 |
| 49 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | M SW APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.83597 |
| 50 | ZoneHVAC:EnergyRecoveryVentilator | M NW APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 5.19091E-002 |
| 51 | ZoneHVAC:EnergyRecoveryVentilator | M NW APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 5.19091E-002 |
| 52 | Fan:OnOff | M NW APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 5.19091E-002 |
| 53 | Fan:OnOff | M NW APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 5.19091E-002 |
| 54 | HeatExchanger:AirToAir:SensibleAndLatent | M NW APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 5.19091E-002 |
| 55 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | M NW APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.81027 |
| 56 | ZoneHVAC:EnergyRecoveryVentilator | M SE APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 5.19091E-002 |
| 57 | ZoneHVAC:EnergyRecoveryVentilator | M SE APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 5.19091E-002 |
| 58 | Fan:OnOff | M SE APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 5.19091E-002 |
| 59 | Fan:OnOff | M SE APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 5.19091E-002 |
| 60 | HeatExchanger:AirToAir:SensibleAndLatent | M SE APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 5.19091E-002 |
| 61 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | M SE APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.76248 |
| 62 | ZoneHVAC:EnergyRecoveryVentilator | M NE APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 5.19091E-002 |
| 63 | ZoneHVAC:EnergyRecoveryVentilator | M NE APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 5.19091E-002 |
| 64 | Fan:OnOff | M NE APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 5.19091E-002 |
| 65 | Fan:OnOff | M NE APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 5.19091E-002 |
| 66 | HeatExchanger:AirToAir:SensibleAndLatent | M NE APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 5.19091E-002 |
| 67 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | M NE APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.73737 |
| 68 | ZoneHVAC:EnergyRecoveryVentilator | M N1 APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 5.19091E-002 |
| 69 | ZoneHVAC:EnergyRecoveryVentilator | M N1 APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 5.19091E-002 |
| 70 | Fan:OnOff | M N1 APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 5.19091E-002 |
| 71 | Fan:OnOff | M N1 APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 5.19091E-002 |
| 72 | HeatExchanger:AirToAir:SensibleAndLatent | M N1 APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 5.19091E-002 |
| 73 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | M N1 APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.66043 |
| 74 | ZoneHVAC:EnergyRecoveryVentilator | M N2 APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 5.19091E-002 |
| 75 | ZoneHVAC:EnergyRecoveryVentilator | M N2 APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 5.19091E-002 |
| 76 | Fan:OnOff | M N2 APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 5.19091E-002 |
| 77 | Fan:OnOff | M N2 APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 5.19091E-002 |
| 78 | HeatExchanger:AirToAir:SensibleAndLatent | M N2 APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 5.19091E-002 |
| 79 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | M N2 APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.65894 |
| 80 | ZoneHVAC:EnergyRecoveryVentilator | M S1 APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 5.19091E-002 |
| 81 | ZoneHVAC:EnergyRecoveryVentilator | M S1 APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 5.19091E-002 |
| 82 | Fan:OnOff | M S1 APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 5.19091E-002 |
| 83 | Fan:OnOff | M S1 APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 5.19091E-002 |
| 84 | HeatExchanger:AirToAir:SensibleAndLatent | M S1 APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 5.19091E-002 |
| 85 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | M S1 APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.69051 |
| 86 | ZoneHVAC:EnergyRecoveryVentilator | M S2 APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 5.19091E-002 |
| 87 | ZoneHVAC:EnergyRecoveryVentilator | M S2 APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 5.19091E-002 |
| 88 | Fan:OnOff | M S2 APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 5.19091E-002 |
| 89 | Fan:OnOff | M S2 APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 5.19091E-002 |
| 90 | HeatExchanger:AirToAir:SensibleAndLatent | M S2 APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 5.19091E-002 |
| 91 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | M S2 APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.68894 |
| 92 | ZoneHVAC:EnergyRecoveryVentilator | T SW APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 93 | ZoneHVAC:EnergyRecoveryVentilator | T SW APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 2.59546E-002 |
| 94 | Fan:OnOff | T SW APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 95 | Fan:OnOff | T SW APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 96 | HeatExchanger:AirToAir:SensibleAndLatent | T SW APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 97 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | T SW APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.45465 |
| 98 | ZoneHVAC:EnergyRecoveryVentilator | T NW APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 99 | ZoneHVAC:EnergyRecoveryVentilator | T NW APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 2.59546E-002 |
| 100 | Fan:OnOff | T NW APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 101 | Fan:OnOff | T NW APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 102 | HeatExchanger:AirToAir:SensibleAndLatent | T NW APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 103 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | T NW APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.45082 |
| 104 | ZoneHVAC:EnergyRecoveryVentilator | T SE APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 105 | ZoneHVAC:EnergyRecoveryVentilator | T SE APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 2.59546E-002 |
| 106 | Fan:OnOff | T SE APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 107 | Fan:OnOff | T SE APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 108 | HeatExchanger:AirToAir:SensibleAndLatent | T SE APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 109 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | T SE APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.40102 |
| 110 | ZoneHVAC:EnergyRecoveryVentilator | T NE APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 111 | ZoneHVAC:EnergyRecoveryVentilator | T NE APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 2.59546E-002 |
| 112 | Fan:OnOff | T NE APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 113 | Fan:OnOff | T NE APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 114 | HeatExchanger:AirToAir:SensibleAndLatent | T NE APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 115 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | T NE APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.39711 |
| 116 | ZoneHVAC:EnergyRecoveryVentilator | T N1 APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 117 | ZoneHVAC:EnergyRecoveryVentilator | T N1 APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 2.59546E-002 |
| 118 | Fan:OnOff | T N1 APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 119 | Fan:OnOff | T N1 APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 120 | HeatExchanger:AirToAir:SensibleAndLatent | T N1 APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 121 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | T N1 APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.37038 |
| 122 | ZoneHVAC:EnergyRecoveryVentilator | T N2 APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 123 | ZoneHVAC:EnergyRecoveryVentilator | T N2 APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 2.59546E-002 |
| 124 | Fan:OnOff | T N2 APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 125 | Fan:OnOff | T N2 APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 126 | HeatExchanger:AirToAir:SensibleAndLatent | T N2 APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 127 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | T N2 APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.36844 |
| 128 | ZoneHVAC:EnergyRecoveryVentilator | T S1 APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 129 | ZoneHVAC:EnergyRecoveryVentilator | T S1 APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 2.59546E-002 |
| 130 | Fan:OnOff | T S1 APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 131 | Fan:OnOff | T S1 APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 132 | HeatExchanger:AirToAir:SensibleAndLatent | T S1 APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 133 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | T S1 APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.37540 |
| 134 | ZoneHVAC:EnergyRecoveryVentilator | T S2 APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 135 | ZoneHVAC:EnergyRecoveryVentilator | T S2 APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 2.59546E-002 |
| 136 | Fan:OnOff | T S2 APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 137 | Fan:OnOff | T S2 APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 138 | HeatExchanger:AirToAir:SensibleAndLatent | T S2 APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 139 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | T S2 APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.37347 |
| 140 | AirLoopHVAC | SPLIT GSW | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.34401 |
| 141 | AirLoopHVAC | SPLIT GSW | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.34401 |
| 142 | AirLoopHVAC | SPLIT GSW | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.34401 |
| 143 | AirLoopHVAC | SPLIT GSW | Adjusted Heating Design Air Flow Rate [m3/s] | 0.34401 |
| 144 | AirLoopHVAC | SPLIT GSW | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.34401 |
| 145 | AirLoopHVAC | SPLIT GSW | Adjusted Main Design Air Flow Rate [m3/s] | 0.34401 |
| 146 | AirLoopHVAC | SPLIT GSW | User Heating Air Flow Ratio [] | 1.00000 |
| 147 | AirLoopHVAC | SPLIT GSW | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 148 | AirLoopHVAC | SPLIT GNW | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.32807 |
| 149 | AirLoopHVAC | SPLIT GNW | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.32807 |
| 150 | AirLoopHVAC | SPLIT GNW | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.32807 |
| 151 | AirLoopHVAC | SPLIT GNW | Adjusted Heating Design Air Flow Rate [m3/s] | 0.32807 |
| 152 | AirLoopHVAC | SPLIT GNW | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.32807 |
| 153 | AirLoopHVAC | SPLIT GNW | Adjusted Main Design Air Flow Rate [m3/s] | 0.32807 |
| 154 | AirLoopHVAC | SPLIT GNW | User Heating Air Flow Ratio [] | 1.00000 |
| 155 | AirLoopHVAC | SPLIT GNW | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 156 | AirLoopHVAC | SPLIT OFFICE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.40241 |
| 157 | AirLoopHVAC | SPLIT OFFICE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.40241 |
| 158 | AirLoopHVAC | SPLIT OFFICE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.40241 |
| 159 | AirLoopHVAC | SPLIT OFFICE | Adjusted Heating Design Air Flow Rate [m3/s] | 0.40241 |
| 160 | AirLoopHVAC | SPLIT OFFICE | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.40241 |
| 161 | AirLoopHVAC | SPLIT OFFICE | Adjusted Main Design Air Flow Rate [m3/s] | 0.40241 |
| 162 | AirLoopHVAC | SPLIT OFFICE | User Heating Air Flow Ratio [] | 1.00000 |
| 163 | AirLoopHVAC | SPLIT OFFICE | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 164 | AirLoopHVAC | SPLIT GNE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.30269 |
| 165 | AirLoopHVAC | SPLIT GNE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.30269 |
| 166 | AirLoopHVAC | SPLIT GNE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.30269 |
| 167 | AirLoopHVAC | SPLIT GNE | Adjusted Heating Design Air Flow Rate [m3/s] | 0.30269 |
| 168 | AirLoopHVAC | SPLIT GNE | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.30269 |
| 169 | AirLoopHVAC | SPLIT GNE | Adjusted Main Design Air Flow Rate [m3/s] | 0.30269 |
| 170 | AirLoopHVAC | SPLIT GNE | User Heating Air Flow Ratio [] | 1.00000 |
| 171 | AirLoopHVAC | SPLIT GNE | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 172 | AirLoopHVAC | SPLIT GN1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.27143 |
| 173 | AirLoopHVAC | SPLIT GN1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.27143 |
| 174 | AirLoopHVAC | SPLIT GN1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.27143 |
| 175 | AirLoopHVAC | SPLIT GN1 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.27143 |
| 176 | AirLoopHVAC | SPLIT GN1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.27143 |
| 177 | AirLoopHVAC | SPLIT GN1 | Adjusted Main Design Air Flow Rate [m3/s] | 0.27143 |
| 178 | AirLoopHVAC | SPLIT GN1 | User Heating Air Flow Ratio [] | 1.00000 |
| 179 | AirLoopHVAC | SPLIT GN1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 180 | AirLoopHVAC | SPLIT GN2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.27124 |
| 181 | AirLoopHVAC | SPLIT GN2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.27124 |
| 182 | AirLoopHVAC | SPLIT GN2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.27124 |
| 183 | AirLoopHVAC | SPLIT GN2 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.27124 |
| 184 | AirLoopHVAC | SPLIT GN2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.27124 |
| 185 | AirLoopHVAC | SPLIT GN2 | Adjusted Main Design Air Flow Rate [m3/s] | 0.27124 |
| 186 | AirLoopHVAC | SPLIT GN2 | User Heating Air Flow Ratio [] | 1.00000 |
| 187 | AirLoopHVAC | SPLIT GN2 | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 188 | AirLoopHVAC | SPLIT GS1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.29220 |
| 189 | AirLoopHVAC | SPLIT GS1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.29220 |
| 190 | AirLoopHVAC | SPLIT GS1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.29220 |
| 191 | AirLoopHVAC | SPLIT GS1 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.29220 |
| 192 | AirLoopHVAC | SPLIT GS1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.29220 |
| 193 | AirLoopHVAC | SPLIT GS1 | Adjusted Main Design Air Flow Rate [m3/s] | 0.29220 |
| 194 | AirLoopHVAC | SPLIT GS1 | User Heating Air Flow Ratio [] | 1.00000 |
| 195 | AirLoopHVAC | SPLIT GS1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 196 | AirLoopHVAC | SPLIT GS2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.29415 |
| 197 | AirLoopHVAC | SPLIT GS2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.29415 |
| 198 | AirLoopHVAC | SPLIT GS2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.29415 |
| 199 | AirLoopHVAC | SPLIT GS2 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.29415 |
| 200 | AirLoopHVAC | SPLIT GS2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.29415 |
| 201 | AirLoopHVAC | SPLIT GS2 | Adjusted Main Design Air Flow Rate [m3/s] | 0.29415 |
| 202 | AirLoopHVAC | SPLIT GS2 | User Heating Air Flow Ratio [] | 1.00000 |
| 203 | AirLoopHVAC | SPLIT GS2 | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 204 | AirLoopHVAC | SPLIT MSW | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.83597 |
| 205 | AirLoopHVAC | SPLIT MSW | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.83597 |
| 206 | AirLoopHVAC | SPLIT MSW | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.83597 |
| 207 | AirLoopHVAC | SPLIT MSW | Adjusted Heating Design Air Flow Rate [m3/s] | 0.83597 |
| 208 | AirLoopHVAC | SPLIT MSW | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.83597 |
| 209 | AirLoopHVAC | SPLIT MSW | Adjusted Main Design Air Flow Rate [m3/s] | 0.83597 |
| 210 | AirLoopHVAC | SPLIT MSW | User Heating Air Flow Ratio [] | 1.00000 |
| 211 | AirLoopHVAC | SPLIT MSW | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 212 | AirLoopHVAC | SPLIT MNW | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.81027 |
| 213 | AirLoopHVAC | SPLIT MNW | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.81027 |
| 214 | AirLoopHVAC | SPLIT MNW | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.81027 |
| 215 | AirLoopHVAC | SPLIT MNW | Adjusted Heating Design Air Flow Rate [m3/s] | 0.81027 |
| 216 | AirLoopHVAC | SPLIT MNW | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.81027 |
| 217 | AirLoopHVAC | SPLIT MNW | Adjusted Main Design Air Flow Rate [m3/s] | 0.81027 |
| 218 | AirLoopHVAC | SPLIT MNW | User Heating Air Flow Ratio [] | 1.00000 |
| 219 | AirLoopHVAC | SPLIT MNW | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 220 | AirLoopHVAC | SPLIT MSE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.76248 |
| 221 | AirLoopHVAC | SPLIT MSE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.76248 |
| 222 | AirLoopHVAC | SPLIT MSE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.76248 |
| 223 | AirLoopHVAC | SPLIT MSE | Adjusted Heating Design Air Flow Rate [m3/s] | 0.76248 |
| 224 | AirLoopHVAC | SPLIT MSE | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.76248 |
| 225 | AirLoopHVAC | SPLIT MSE | Adjusted Main Design Air Flow Rate [m3/s] | 0.76248 |
| 226 | AirLoopHVAC | SPLIT MSE | User Heating Air Flow Ratio [] | 1.00000 |
| 227 | AirLoopHVAC | SPLIT MSE | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 228 | AirLoopHVAC | SPLIT MNE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.73737 |
| 229 | AirLoopHVAC | SPLIT MNE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.73737 |
| 230 | AirLoopHVAC | SPLIT MNE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.73737 |
| 231 | AirLoopHVAC | SPLIT MNE | Adjusted Heating Design Air Flow Rate [m3/s] | 0.73737 |
| 232 | AirLoopHVAC | SPLIT MNE | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.73737 |
| 233 | AirLoopHVAC | SPLIT MNE | Adjusted Main Design Air Flow Rate [m3/s] | 0.73737 |
| 234 | AirLoopHVAC | SPLIT MNE | User Heating Air Flow Ratio [] | 1.00000 |
| 235 | AirLoopHVAC | SPLIT MNE | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 236 | AirLoopHVAC | SPLIT MN1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.66043 |
| 237 | AirLoopHVAC | SPLIT MN1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.66043 |
| 238 | AirLoopHVAC | SPLIT MN1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.66043 |
| 239 | AirLoopHVAC | SPLIT MN1 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.66043 |
| 240 | AirLoopHVAC | SPLIT MN1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.66043 |
| 241 | AirLoopHVAC | SPLIT MN1 | Adjusted Main Design Air Flow Rate [m3/s] | 0.66043 |
| 242 | AirLoopHVAC | SPLIT MN1 | User Heating Air Flow Ratio [] | 1.00000 |
| 243 | AirLoopHVAC | SPLIT MN1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 244 | AirLoopHVAC | SPLIT MN2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.65894 |
| 245 | AirLoopHVAC | SPLIT MN2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.65894 |
| 246 | AirLoopHVAC | SPLIT MN2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.65894 |
| 247 | AirLoopHVAC | SPLIT MN2 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.65894 |
| 248 | AirLoopHVAC | SPLIT MN2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.65894 |
| 249 | AirLoopHVAC | SPLIT MN2 | Adjusted Main Design Air Flow Rate [m3/s] | 0.65894 |
| 250 | AirLoopHVAC | SPLIT MN2 | User Heating Air Flow Ratio [] | 1.00000 |
| 251 | AirLoopHVAC | SPLIT MN2 | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 252 | AirLoopHVAC | SPLIT MS1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.69051 |
| 253 | AirLoopHVAC | SPLIT MS1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.69051 |
| 254 | AirLoopHVAC | SPLIT MS1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.69051 |
| 255 | AirLoopHVAC | SPLIT MS1 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.69051 |
| 256 | AirLoopHVAC | SPLIT MS1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.69051 |
| 257 | AirLoopHVAC | SPLIT MS1 | Adjusted Main Design Air Flow Rate [m3/s] | 0.69051 |
| 258 | AirLoopHVAC | SPLIT MS1 | User Heating Air Flow Ratio [] | 1.00000 |
| 259 | AirLoopHVAC | SPLIT MS1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 260 | AirLoopHVAC | SPLIT MS2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.68894 |
| 261 | AirLoopHVAC | SPLIT MS2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.68894 |
| 262 | AirLoopHVAC | SPLIT MS2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.68894 |
| 263 | AirLoopHVAC | SPLIT MS2 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.68894 |
| 264 | AirLoopHVAC | SPLIT MS2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.68894 |
| 265 | AirLoopHVAC | SPLIT MS2 | Adjusted Main Design Air Flow Rate [m3/s] | 0.68894 |
| 266 | AirLoopHVAC | SPLIT MS2 | User Heating Air Flow Ratio [] | 1.00000 |
| 267 | AirLoopHVAC | SPLIT MS2 | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 268 | AirLoopHVAC | SPLIT TSW | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.45465 |
| 269 | AirLoopHVAC | SPLIT TSW | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.45465 |
| 270 | AirLoopHVAC | SPLIT TSW | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.45465 |
| 271 | AirLoopHVAC | SPLIT TSW | Adjusted Heating Design Air Flow Rate [m3/s] | 0.45465 |
| 272 | AirLoopHVAC | SPLIT TSW | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.45465 |
| 273 | AirLoopHVAC | SPLIT TSW | Adjusted Main Design Air Flow Rate [m3/s] | 0.45465 |
| 274 | AirLoopHVAC | SPLIT TSW | User Heating Air Flow Ratio [] | 1.00000 |
| 275 | AirLoopHVAC | SPLIT TSW | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 276 | AirLoopHVAC | SPLIT TNW | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.45082 |
| 277 | AirLoopHVAC | SPLIT TNW | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.45082 |
| 278 | AirLoopHVAC | SPLIT TNW | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.45082 |
| 279 | AirLoopHVAC | SPLIT TNW | Adjusted Heating Design Air Flow Rate [m3/s] | 0.45082 |
| 280 | AirLoopHVAC | SPLIT TNW | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.45082 |
| 281 | AirLoopHVAC | SPLIT TNW | Adjusted Main Design Air Flow Rate [m3/s] | 0.45082 |
| 282 | AirLoopHVAC | SPLIT TNW | User Heating Air Flow Ratio [] | 1.00000 |
| 283 | AirLoopHVAC | SPLIT TNW | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 284 | AirLoopHVAC | SPLIT TSE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.40102 |
| 285 | AirLoopHVAC | SPLIT TSE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.40102 |
| 286 | AirLoopHVAC | SPLIT TSE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.40102 |
| 287 | AirLoopHVAC | SPLIT TSE | Adjusted Heating Design Air Flow Rate [m3/s] | 0.40102 |
| 288 | AirLoopHVAC | SPLIT TSE | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.40102 |
| 289 | AirLoopHVAC | SPLIT TSE | Adjusted Main Design Air Flow Rate [m3/s] | 0.40102 |
| 290 | AirLoopHVAC | SPLIT TSE | User Heating Air Flow Ratio [] | 1.00000 |
| 291 | AirLoopHVAC | SPLIT TSE | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 292 | AirLoopHVAC | SPLIT TNE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.39711 |
| 293 | AirLoopHVAC | SPLIT TNE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.39711 |
| 294 | AirLoopHVAC | SPLIT TNE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.39711 |
| 295 | AirLoopHVAC | SPLIT TNE | Adjusted Heating Design Air Flow Rate [m3/s] | 0.39711 |
| 296 | AirLoopHVAC | SPLIT TNE | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.39711 |
| 297 | AirLoopHVAC | SPLIT TNE | Adjusted Main Design Air Flow Rate [m3/s] | 0.39711 |
| 298 | AirLoopHVAC | SPLIT TNE | User Heating Air Flow Ratio [] | 1.00000 |
| 299 | AirLoopHVAC | SPLIT TNE | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 300 | AirLoopHVAC | SPLIT TN1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.37038 |
| 301 | AirLoopHVAC | SPLIT TN1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.37038 |
| 302 | AirLoopHVAC | SPLIT TN1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.37038 |
| 303 | AirLoopHVAC | SPLIT TN1 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.37038 |
| 304 | AirLoopHVAC | SPLIT TN1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.37038 |
| 305 | AirLoopHVAC | SPLIT TN1 | Adjusted Main Design Air Flow Rate [m3/s] | 0.37038 |
| 306 | AirLoopHVAC | SPLIT TN1 | User Heating Air Flow Ratio [] | 1.00000 |
| 307 | AirLoopHVAC | SPLIT TN1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 308 | AirLoopHVAC | SPLIT TN2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.36844 |
| 309 | AirLoopHVAC | SPLIT TN2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.36844 |
| 310 | AirLoopHVAC | SPLIT TN2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.36844 |
| 311 | AirLoopHVAC | SPLIT TN2 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.36844 |
| 312 | AirLoopHVAC | SPLIT TN2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.36844 |
| 313 | AirLoopHVAC | SPLIT TN2 | Adjusted Main Design Air Flow Rate [m3/s] | 0.36844 |
| 314 | AirLoopHVAC | SPLIT TN2 | User Heating Air Flow Ratio [] | 1.00000 |
| 315 | AirLoopHVAC | SPLIT TN2 | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 316 | AirLoopHVAC | SPLIT TS1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.37540 |
| 317 | AirLoopHVAC | SPLIT TS1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.37540 |
| 318 | AirLoopHVAC | SPLIT TS1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.37540 |
| 319 | AirLoopHVAC | SPLIT TS1 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.37540 |
| 320 | AirLoopHVAC | SPLIT TS1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.37540 |
| 321 | AirLoopHVAC | SPLIT TS1 | Adjusted Main Design Air Flow Rate [m3/s] | 0.37540 |
| 322 | AirLoopHVAC | SPLIT TS1 | User Heating Air Flow Ratio [] | 1.00000 |
| 323 | AirLoopHVAC | SPLIT TS1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 324 | AirLoopHVAC | SPLIT TS2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.37347 |
| 325 | AirLoopHVAC | SPLIT TS2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.37347 |
| 326 | AirLoopHVAC | SPLIT TS2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.37347 |
| 327 | AirLoopHVAC | SPLIT TS2 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.37347 |
| 328 | AirLoopHVAC | SPLIT TS2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.37347 |
| 329 | AirLoopHVAC | SPLIT TS2 | Adjusted Main Design Air Flow Rate [m3/s] | 0.37347 |
| 330 | AirLoopHVAC | SPLIT TS2 | User Heating Air Flow Ratio [] | 1.00000 |
| 331 | AirLoopHVAC | SPLIT TS2 | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 332 | AirLoopHVAC | SPLIT GSW | Design Supply Air Flow Rate [m3/s] | 0.34401 |
| 333 | AirLoopHVAC | SPLIT GNW | Design Supply Air Flow Rate [m3/s] | 0.32807 |
| 334 | AirLoopHVAC | SPLIT OFFICE | Design Supply Air Flow Rate [m3/s] | 0.40241 |
| 335 | AirLoopHVAC | SPLIT GNE | Design Supply Air Flow Rate [m3/s] | 0.30269 |
| 336 | AirLoopHVAC | SPLIT GN1 | Design Supply Air Flow Rate [m3/s] | 0.27143 |
| 337 | AirLoopHVAC | SPLIT GN2 | Design Supply Air Flow Rate [m3/s] | 0.27124 |
| 338 | AirLoopHVAC | SPLIT GS1 | Design Supply Air Flow Rate [m3/s] | 0.29220 |
| 339 | AirLoopHVAC | SPLIT GS2 | Design Supply Air Flow Rate [m3/s] | 0.29415 |
| 340 | AirLoopHVAC | SPLIT MSW | Design Supply Air Flow Rate [m3/s] | 0.83597 |
| 341 | AirLoopHVAC | SPLIT MNW | Design Supply Air Flow Rate [m3/s] | 0.81027 |
| 342 | AirLoopHVAC | SPLIT MSE | Design Supply Air Flow Rate [m3/s] | 0.76248 |
| 343 | AirLoopHVAC | SPLIT MNE | Design Supply Air Flow Rate [m3/s] | 0.73737 |
| 344 | AirLoopHVAC | SPLIT MN1 | Design Supply Air Flow Rate [m3/s] | 0.66043 |
| 345 | AirLoopHVAC | SPLIT MN2 | Design Supply Air Flow Rate [m3/s] | 0.65894 |
| 346 | AirLoopHVAC | SPLIT MS1 | Design Supply Air Flow Rate [m3/s] | 0.69051 |
| 347 | AirLoopHVAC | SPLIT MS2 | Design Supply Air Flow Rate [m3/s] | 0.68894 |
| 348 | AirLoopHVAC | SPLIT TSW | Design Supply Air Flow Rate [m3/s] | 0.45465 |
| 349 | AirLoopHVAC | SPLIT TNW | Design Supply Air Flow Rate [m3/s] | 0.45082 |
| 350 | AirLoopHVAC | SPLIT TSE | Design Supply Air Flow Rate [m3/s] | 0.40102 |
| 351 | AirLoopHVAC | SPLIT TNE | Design Supply Air Flow Rate [m3/s] | 0.39711 |
| 352 | AirLoopHVAC | SPLIT TN1 | Design Supply Air Flow Rate [m3/s] | 0.37038 |
| 353 | AirLoopHVAC | SPLIT TN2 | Design Supply Air Flow Rate [m3/s] | 0.36844 |
| 354 | AirLoopHVAC | SPLIT TS1 | Design Supply Air Flow Rate [m3/s] | 0.37540 |
| 355 | AirLoopHVAC | SPLIT TS2 | Design Supply Air Flow Rate [m3/s] | 0.37347 |
| 356 | Controller:OutdoorAir | SPLIT GSW_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.34401 |
| 357 | Controller:OutdoorAir | SPLIT GSW_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.59546E-002 |
| 358 | AirLoopHVAC:UnitarySystem | SPLIT GSW_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.34401 |
| 359 | AirLoopHVAC:UnitarySystem | SPLIT GSW_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.34401 |
| 360 | AirLoopHVAC:UnitarySystem | SPLIT GSW_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.34401 |
| 361 | AirLoopHVAC:UnitarySystem | SPLIT GSW_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.34401 |
| 362 | AirLoopHVAC:UnitarySystem | SPLIT GSW_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 6045.52807 |
| 363 | AirLoopHVAC:UnitarySystem | SPLIT GSW_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 8862.16312 |
| 364 | AirLoopHVAC:UnitarySystem | SPLIT GSW_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 365 | AirLoopHVAC:UnitarySystem | SPLIT GSW_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 366 | Fan:OnOff | SPLIT GSW SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.34401 |
| 367 | Coil:Cooling:DX:SingleSpeed | SPLIT GSW COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.34401 |
| 368 | Coil:Cooling:DX:SingleSpeed | SPLIT GSW COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 6045.52807 |
| 369 | Coil:Cooling:DX:SingleSpeed | SPLIT GSW COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80031 |
| 370 | Coil:Heating:Fuel | SPLIT GSW HEATING COIL | Design Size Nominal Capacity [W] | 8862.16312 |
| 371 | Controller:OutdoorAir | SPLIT GNW_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.32807 |
| 372 | Controller:OutdoorAir | SPLIT GNW_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.59546E-002 |
| 373 | AirLoopHVAC:UnitarySystem | SPLIT GNW_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.32807 |
| 374 | AirLoopHVAC:UnitarySystem | SPLIT GNW_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.32807 |
| 375 | AirLoopHVAC:UnitarySystem | SPLIT GNW_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.32807 |
| 376 | AirLoopHVAC:UnitarySystem | SPLIT GNW_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.32807 |
| 377 | AirLoopHVAC:UnitarySystem | SPLIT GNW_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 5788.81270 |
| 378 | AirLoopHVAC:UnitarySystem | SPLIT GNW_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 8497.72359 |
| 379 | AirLoopHVAC:UnitarySystem | SPLIT GNW_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 380 | AirLoopHVAC:UnitarySystem | SPLIT GNW_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 381 | Fan:OnOff | SPLIT GNW SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.32807 |
| 382 | Coil:Cooling:DX:SingleSpeed | SPLIT GNW COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.32807 |
| 383 | Coil:Cooling:DX:SingleSpeed | SPLIT GNW COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 5788.81270 |
| 384 | Coil:Cooling:DX:SingleSpeed | SPLIT GNW COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80091 |
| 385 | Coil:Heating:Fuel | SPLIT GNW HEATING COIL | Design Size Nominal Capacity [W] | 8497.72359 |
| 386 | Controller:OutdoorAir | SPLIT OFFICE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.40241 |
| 387 | Controller:OutdoorAir | SPLIT OFFICE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 3.81060E-002 |
| 388 | AirLoopHVAC:UnitarySystem | SPLIT OFFICE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.40241 |
| 389 | AirLoopHVAC:UnitarySystem | SPLIT OFFICE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.40241 |
| 390 | AirLoopHVAC:UnitarySystem | SPLIT OFFICE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.40241 |
| 391 | AirLoopHVAC:UnitarySystem | SPLIT OFFICE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.40241 |
| 392 | AirLoopHVAC:UnitarySystem | SPLIT OFFICE_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 7005.51983 |
| 393 | AirLoopHVAC:UnitarySystem | SPLIT OFFICE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 10664.53198 |
| 394 | AirLoopHVAC:UnitarySystem | SPLIT OFFICE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 395 | AirLoopHVAC:UnitarySystem | SPLIT OFFICE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 396 | Fan:OnOff | SPLIT OFFICE SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.40241 |
| 397 | Coil:Cooling:DX:SingleSpeed | SPLIT OFFICE COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.40241 |
| 398 | Coil:Cooling:DX:SingleSpeed | SPLIT OFFICE COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 7005.51983 |
| 399 | Coil:Cooling:DX:SingleSpeed | SPLIT OFFICE COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80059 |
| 400 | Coil:Heating:Fuel | SPLIT OFFICE HEATING COIL | Design Size Nominal Capacity [W] | 10664.53198 |
| 401 | Controller:OutdoorAir | SPLIT GNE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.30269 |
| 402 | Controller:OutdoorAir | SPLIT GNE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.59546E-002 |
| 403 | AirLoopHVAC:UnitarySystem | SPLIT GNE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.30269 |
| 404 | AirLoopHVAC:UnitarySystem | SPLIT GNE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.30269 |
| 405 | AirLoopHVAC:UnitarySystem | SPLIT GNE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.30269 |
| 406 | AirLoopHVAC:UnitarySystem | SPLIT GNE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.30269 |
| 407 | AirLoopHVAC:UnitarySystem | SPLIT GNE_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 5415.87496 |
| 408 | AirLoopHVAC:UnitarySystem | SPLIT GNE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 7917.48488 |
| 409 | AirLoopHVAC:UnitarySystem | SPLIT GNE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 410 | AirLoopHVAC:UnitarySystem | SPLIT GNE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 411 | Fan:OnOff | SPLIT GNE SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.30269 |
| 412 | Coil:Cooling:DX:SingleSpeed | SPLIT GNE COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.30269 |
| 413 | Coil:Cooling:DX:SingleSpeed | SPLIT GNE COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 5415.87496 |
| 414 | Coil:Cooling:DX:SingleSpeed | SPLIT GNE COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80014 |
| 415 | Coil:Heating:Fuel | SPLIT GNE HEATING COIL | Design Size Nominal Capacity [W] | 7917.48488 |
| 416 | Controller:OutdoorAir | SPLIT GN1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.27143 |
| 417 | Controller:OutdoorAir | SPLIT GN1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.59546E-002 |
| 418 | AirLoopHVAC:UnitarySystem | SPLIT GN1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.27143 |
| 419 | AirLoopHVAC:UnitarySystem | SPLIT GN1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.27143 |
| 420 | AirLoopHVAC:UnitarySystem | SPLIT GN1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.27143 |
| 421 | AirLoopHVAC:UnitarySystem | SPLIT GN1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.27143 |
| 422 | AirLoopHVAC:UnitarySystem | SPLIT GN1_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 4875.67913 |
| 423 | AirLoopHVAC:UnitarySystem | SPLIT GN1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 7202.91058 |
| 424 | AirLoopHVAC:UnitarySystem | SPLIT GN1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 425 | AirLoopHVAC:UnitarySystem | SPLIT GN1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 426 | Fan:OnOff | SPLIT GN1 SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.27143 |
| 427 | Coil:Cooling:DX:SingleSpeed | SPLIT GN1 COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.27143 |
| 428 | Coil:Cooling:DX:SingleSpeed | SPLIT GN1 COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 4875.67913 |
| 429 | Coil:Cooling:DX:SingleSpeed | SPLIT GN1 COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80081 |
| 430 | Coil:Heating:Fuel | SPLIT GN1 HEATING COIL | Design Size Nominal Capacity [W] | 7202.91058 |
| 431 | Controller:OutdoorAir | SPLIT GN2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.27124 |
| 432 | Controller:OutdoorAir | SPLIT GN2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.59546E-002 |
| 433 | AirLoopHVAC:UnitarySystem | SPLIT GN2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.27124 |
| 434 | AirLoopHVAC:UnitarySystem | SPLIT GN2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.27124 |
| 435 | AirLoopHVAC:UnitarySystem | SPLIT GN2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.27124 |
| 436 | AirLoopHVAC:UnitarySystem | SPLIT GN2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.27124 |
| 437 | AirLoopHVAC:UnitarySystem | SPLIT GN2_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 4873.47662 |
| 438 | AirLoopHVAC:UnitarySystem | SPLIT GN2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 7198.61191 |
| 439 | AirLoopHVAC:UnitarySystem | SPLIT GN2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 440 | AirLoopHVAC:UnitarySystem | SPLIT GN2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 441 | Fan:OnOff | SPLIT GN2 SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.27124 |
| 442 | Coil:Cooling:DX:SingleSpeed | SPLIT GN2 COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.27124 |
| 443 | Coil:Cooling:DX:SingleSpeed | SPLIT GN2 COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 4873.47662 |
| 444 | Coil:Cooling:DX:SingleSpeed | SPLIT GN2 COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80073 |
| 445 | Coil:Heating:Fuel | SPLIT GN2 HEATING COIL | Design Size Nominal Capacity [W] | 7198.61191 |
| 446 | Controller:OutdoorAir | SPLIT GS1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.29220 |
| 447 | Controller:OutdoorAir | SPLIT GS1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.59546E-002 |
| 448 | AirLoopHVAC:UnitarySystem | SPLIT GS1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.29220 |
| 449 | AirLoopHVAC:UnitarySystem | SPLIT GS1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.29220 |
| 450 | AirLoopHVAC:UnitarySystem | SPLIT GS1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.29220 |
| 451 | AirLoopHVAC:UnitarySystem | SPLIT GS1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.29220 |
| 452 | AirLoopHVAC:UnitarySystem | SPLIT GS1_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 5216.19031 |
| 453 | AirLoopHVAC:UnitarySystem | SPLIT GS1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 7677.71687 |
| 454 | AirLoopHVAC:UnitarySystem | SPLIT GS1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 455 | AirLoopHVAC:UnitarySystem | SPLIT GS1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 456 | Fan:OnOff | SPLIT GS1 SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.29220 |
| 457 | Coil:Cooling:DX:SingleSpeed | SPLIT GS1 COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.29220 |
| 458 | Coil:Cooling:DX:SingleSpeed | SPLIT GS1 COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 5216.19031 |
| 459 | Coil:Cooling:DX:SingleSpeed | SPLIT GS1 COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80093 |
| 460 | Coil:Heating:Fuel | SPLIT GS1 HEATING COIL | Design Size Nominal Capacity [W] | 7677.71687 |
| 461 | Controller:OutdoorAir | SPLIT GS2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.29415 |
| 462 | Controller:OutdoorAir | SPLIT GS2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.59546E-002 |
| 463 | AirLoopHVAC:UnitarySystem | SPLIT GS2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.29415 |
| 464 | AirLoopHVAC:UnitarySystem | SPLIT GS2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.29415 |
| 465 | AirLoopHVAC:UnitarySystem | SPLIT GS2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.29415 |
| 466 | AirLoopHVAC:UnitarySystem | SPLIT GS2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.29415 |
| 467 | AirLoopHVAC:UnitarySystem | SPLIT GS2_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 5245.87813 |
| 468 | AirLoopHVAC:UnitarySystem | SPLIT GS2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 7722.13522 |
| 469 | AirLoopHVAC:UnitarySystem | SPLIT GS2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 470 | AirLoopHVAC:UnitarySystem | SPLIT GS2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 471 | Fan:OnOff | SPLIT GS2 SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.29415 |
| 472 | Coil:Cooling:DX:SingleSpeed | SPLIT GS2 COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.29415 |
| 473 | Coil:Cooling:DX:SingleSpeed | SPLIT GS2 COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 5245.87813 |
| 474 | Coil:Cooling:DX:SingleSpeed | SPLIT GS2 COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80025 |
| 475 | Coil:Heating:Fuel | SPLIT GS2 HEATING COIL | Design Size Nominal Capacity [W] | 7722.13522 |
| 476 | Controller:OutdoorAir | SPLIT MSW_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.83597 |
| 477 | Controller:OutdoorAir | SPLIT MSW_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 5.19091E-002 |
| 478 | AirLoopHVAC:UnitarySystem | SPLIT MSW_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.83597 |
| 479 | AirLoopHVAC:UnitarySystem | SPLIT MSW_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.83597 |
| 480 | AirLoopHVAC:UnitarySystem | SPLIT MSW_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.83597 |
| 481 | AirLoopHVAC:UnitarySystem | SPLIT MSW_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.83597 |
| 482 | AirLoopHVAC:UnitarySystem | SPLIT MSW_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 14460.98287 |
| 483 | AirLoopHVAC:UnitarySystem | SPLIT MSW_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 21108.00856 |
| 484 | AirLoopHVAC:UnitarySystem | SPLIT MSW_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 485 | AirLoopHVAC:UnitarySystem | SPLIT MSW_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 486 | Fan:OnOff | SPLIT MSW SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.83597 |
| 487 | Coil:Cooling:DX:SingleSpeed | SPLIT MSW COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.83597 |
| 488 | Coil:Cooling:DX:SingleSpeed | SPLIT MSW COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 14460.98287 |
| 489 | Coil:Cooling:DX:SingleSpeed | SPLIT MSW COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80082 |
| 490 | Coil:Heating:Fuel | SPLIT MSW HEATING COIL | Design Size Nominal Capacity [W] | 21108.00856 |
| 491 | Controller:OutdoorAir | SPLIT MNW_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.81027 |
| 492 | Controller:OutdoorAir | SPLIT MNW_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 5.19091E-002 |
| 493 | AirLoopHVAC:UnitarySystem | SPLIT MNW_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.81027 |
| 494 | AirLoopHVAC:UnitarySystem | SPLIT MNW_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.81027 |
| 495 | AirLoopHVAC:UnitarySystem | SPLIT MNW_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.81027 |
| 496 | AirLoopHVAC:UnitarySystem | SPLIT MNW_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.81027 |
| 497 | AirLoopHVAC:UnitarySystem | SPLIT MNW_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 14047.72201 |
| 498 | AirLoopHVAC:UnitarySystem | SPLIT MNW_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 20520.32478 |
| 499 | AirLoopHVAC:UnitarySystem | SPLIT MNW_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 500 | AirLoopHVAC:UnitarySystem | SPLIT MNW_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 501 | Fan:OnOff | SPLIT MNW SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.81027 |
| 502 | Coil:Cooling:DX:SingleSpeed | SPLIT MNW COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.81027 |
| 503 | Coil:Cooling:DX:SingleSpeed | SPLIT MNW COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 14047.72201 |
| 504 | Coil:Cooling:DX:SingleSpeed | SPLIT MNW COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80004 |
| 505 | Coil:Heating:Fuel | SPLIT MNW HEATING COIL | Design Size Nominal Capacity [W] | 20520.32478 |
| 506 | Controller:OutdoorAir | SPLIT MSE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.76248 |
| 507 | Controller:OutdoorAir | SPLIT MSE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 5.19091E-002 |
| 508 | AirLoopHVAC:UnitarySystem | SPLIT MSE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.76248 |
| 509 | AirLoopHVAC:UnitarySystem | SPLIT MSE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.76248 |
| 510 | AirLoopHVAC:UnitarySystem | SPLIT MSE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.76248 |
| 511 | AirLoopHVAC:UnitarySystem | SPLIT MSE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.76248 |
| 512 | AirLoopHVAC:UnitarySystem | SPLIT MSE_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 13368.00493 |
| 513 | AirLoopHVAC:UnitarySystem | SPLIT MSE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 19427.96492 |
| 514 | AirLoopHVAC:UnitarySystem | SPLIT MSE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 515 | AirLoopHVAC:UnitarySystem | SPLIT MSE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 516 | Fan:OnOff | SPLIT MSE SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.76248 |
| 517 | Coil:Cooling:DX:SingleSpeed | SPLIT MSE COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.76248 |
| 518 | Coil:Cooling:DX:SingleSpeed | SPLIT MSE COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 13368.00493 |
| 519 | Coil:Cooling:DX:SingleSpeed | SPLIT MSE COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80013 |
| 520 | Coil:Heating:Fuel | SPLIT MSE HEATING COIL | Design Size Nominal Capacity [W] | 19427.96492 |
| 521 | Controller:OutdoorAir | SPLIT MNE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.73737 |
| 522 | Controller:OutdoorAir | SPLIT MNE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 5.19091E-002 |
| 523 | AirLoopHVAC:UnitarySystem | SPLIT MNE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.73737 |
| 524 | AirLoopHVAC:UnitarySystem | SPLIT MNE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.73737 |
| 525 | AirLoopHVAC:UnitarySystem | SPLIT MNE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.73737 |
| 526 | AirLoopHVAC:UnitarySystem | SPLIT MNE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.73737 |
| 527 | AirLoopHVAC:UnitarySystem | SPLIT MNE_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 12962.93949 |
| 528 | AirLoopHVAC:UnitarySystem | SPLIT MNE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 18853.62095 |
| 529 | AirLoopHVAC:UnitarySystem | SPLIT MNE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 530 | AirLoopHVAC:UnitarySystem | SPLIT MNE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 531 | Fan:OnOff | SPLIT MNE SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.73737 |
| 532 | Coil:Cooling:DX:SingleSpeed | SPLIT MNE COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.73737 |
| 533 | Coil:Cooling:DX:SingleSpeed | SPLIT MNE COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 12962.93949 |
| 534 | Coil:Cooling:DX:SingleSpeed | SPLIT MNE COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80019 |
| 535 | Coil:Heating:Fuel | SPLIT MNE HEATING COIL | Design Size Nominal Capacity [W] | 18853.62095 |
| 536 | Controller:OutdoorAir | SPLIT MN1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.66043 |
| 537 | Controller:OutdoorAir | SPLIT MN1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 5.19091E-002 |
| 538 | AirLoopHVAC:UnitarySystem | SPLIT MN1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.66043 |
| 539 | AirLoopHVAC:UnitarySystem | SPLIT MN1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.66043 |
| 540 | AirLoopHVAC:UnitarySystem | SPLIT MN1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.66043 |
| 541 | AirLoopHVAC:UnitarySystem | SPLIT MN1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.66043 |
| 542 | AirLoopHVAC:UnitarySystem | SPLIT MN1_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 11620.37877 |
| 543 | AirLoopHVAC:UnitarySystem | SPLIT MN1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 17093.98878 |
| 544 | AirLoopHVAC:UnitarySystem | SPLIT MN1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 545 | AirLoopHVAC:UnitarySystem | SPLIT MN1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 546 | Fan:OnOff | SPLIT MN1 SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.66043 |
| 547 | Coil:Cooling:DX:SingleSpeed | SPLIT MN1 COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.66043 |
| 548 | Coil:Cooling:DX:SingleSpeed | SPLIT MN1 COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 11620.37877 |
| 549 | Coil:Cooling:DX:SingleSpeed | SPLIT MN1 COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80089 |
| 550 | Coil:Heating:Fuel | SPLIT MN1 HEATING COIL | Design Size Nominal Capacity [W] | 17093.98878 |
| 551 | Controller:OutdoorAir | SPLIT MN2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.65894 |
| 552 | Controller:OutdoorAir | SPLIT MN2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 5.19091E-002 |
| 553 | AirLoopHVAC:UnitarySystem | SPLIT MN2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.65894 |
| 554 | AirLoopHVAC:UnitarySystem | SPLIT MN2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.65894 |
| 555 | AirLoopHVAC:UnitarySystem | SPLIT MN2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.65894 |
| 556 | AirLoopHVAC:UnitarySystem | SPLIT MN2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.65894 |
| 557 | AirLoopHVAC:UnitarySystem | SPLIT MN2_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 11598.21600 |
| 558 | AirLoopHVAC:UnitarySystem | SPLIT MN2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 17059.81884 |
| 559 | AirLoopHVAC:UnitarySystem | SPLIT MN2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 560 | AirLoopHVAC:UnitarySystem | SPLIT MN2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 561 | Fan:OnOff | SPLIT MN2 SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.65894 |
| 562 | Coil:Cooling:DX:SingleSpeed | SPLIT MN2 COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.65894 |
| 563 | Coil:Cooling:DX:SingleSpeed | SPLIT MN2 COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 11598.21600 |
| 564 | Coil:Cooling:DX:SingleSpeed | SPLIT MN2 COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80077 |
| 565 | Coil:Heating:Fuel | SPLIT MN2 HEATING COIL | Design Size Nominal Capacity [W] | 17059.81884 |
| 566 | Controller:OutdoorAir | SPLIT MS1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.69051 |
| 567 | Controller:OutdoorAir | SPLIT MS1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 5.19091E-002 |
| 568 | AirLoopHVAC:UnitarySystem | SPLIT MS1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.69051 |
| 569 | AirLoopHVAC:UnitarySystem | SPLIT MS1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.69051 |
| 570 | AirLoopHVAC:UnitarySystem | SPLIT MS1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.69051 |
| 571 | AirLoopHVAC:UnitarySystem | SPLIT MS1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.69051 |
| 572 | AirLoopHVAC:UnitarySystem | SPLIT MS1_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 12103.84099 |
| 573 | AirLoopHVAC:UnitarySystem | SPLIT MS1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 17781.81889 |
| 574 | AirLoopHVAC:UnitarySystem | SPLIT MS1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 575 | AirLoopHVAC:UnitarySystem | SPLIT MS1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 576 | Fan:OnOff | SPLIT MS1 SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.69051 |
| 577 | Coil:Cooling:DX:SingleSpeed | SPLIT MS1 COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.69051 |
| 578 | Coil:Cooling:DX:SingleSpeed | SPLIT MS1 COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 12103.84099 |
| 579 | Coil:Cooling:DX:SingleSpeed | SPLIT MS1 COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80020 |
| 580 | Coil:Heating:Fuel | SPLIT MS1 HEATING COIL | Design Size Nominal Capacity [W] | 17781.81889 |
| 581 | Controller:OutdoorAir | SPLIT MS2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.68894 |
| 582 | Controller:OutdoorAir | SPLIT MS2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 5.19091E-002 |
| 583 | AirLoopHVAC:UnitarySystem | SPLIT MS2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.68894 |
| 584 | AirLoopHVAC:UnitarySystem | SPLIT MS2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.68894 |
| 585 | AirLoopHVAC:UnitarySystem | SPLIT MS2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.68894 |
| 586 | AirLoopHVAC:UnitarySystem | SPLIT MS2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.68894 |
| 587 | AirLoopHVAC:UnitarySystem | SPLIT MS2_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 12080.74903 |
| 588 | AirLoopHVAC:UnitarySystem | SPLIT MS2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 17745.89947 |
| 589 | AirLoopHVAC:UnitarySystem | SPLIT MS2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 590 | AirLoopHVAC:UnitarySystem | SPLIT MS2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 591 | Fan:OnOff | SPLIT MS2 SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.68894 |
| 592 | Coil:Cooling:DX:SingleSpeed | SPLIT MS2 COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.68894 |
| 593 | Coil:Cooling:DX:SingleSpeed | SPLIT MS2 COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 12080.74903 |
| 594 | Coil:Cooling:DX:SingleSpeed | SPLIT MS2 COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80007 |
| 595 | Coil:Heating:Fuel | SPLIT MS2 HEATING COIL | Design Size Nominal Capacity [W] | 17745.89947 |
| 596 | Controller:OutdoorAir | SPLIT TSW_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.45465 |
| 597 | Controller:OutdoorAir | SPLIT TSW_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.59546E-002 |
| 598 | AirLoopHVAC:UnitarySystem | SPLIT TSW_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.45465 |
| 599 | AirLoopHVAC:UnitarySystem | SPLIT TSW_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.45465 |
| 600 | AirLoopHVAC:UnitarySystem | SPLIT TSW_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.45465 |
| 601 | AirLoopHVAC:UnitarySystem | SPLIT TSW_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.45465 |
| 602 | AirLoopHVAC:UnitarySystem | SPLIT TSW_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 7867.61557 |
| 603 | AirLoopHVAC:UnitarySystem | SPLIT TSW_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 11392.79932 |
| 604 | AirLoopHVAC:UnitarySystem | SPLIT TSW_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 605 | AirLoopHVAC:UnitarySystem | SPLIT TSW_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 606 | Fan:OnOff | SPLIT TSW SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.45465 |
| 607 | Coil:Cooling:DX:SingleSpeed | SPLIT TSW COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.45465 |
| 608 | Coil:Cooling:DX:SingleSpeed | SPLIT TSW COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 7867.61557 |
| 609 | Coil:Cooling:DX:SingleSpeed | SPLIT TSW COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80069 |
| 610 | Coil:Heating:Fuel | SPLIT TSW HEATING COIL | Design Size Nominal Capacity [W] | 11392.79932 |
| 611 | Controller:OutdoorAir | SPLIT TNW_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.45082 |
| 612 | Controller:OutdoorAir | SPLIT TNW_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.59546E-002 |
| 613 | AirLoopHVAC:UnitarySystem | SPLIT TNW_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.45082 |
| 614 | AirLoopHVAC:UnitarySystem | SPLIT TNW_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.45082 |
| 615 | AirLoopHVAC:UnitarySystem | SPLIT TNW_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.45082 |
| 616 | AirLoopHVAC:UnitarySystem | SPLIT TNW_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.45082 |
| 617 | AirLoopHVAC:UnitarySystem | SPLIT TNW_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 7797.78060 |
| 618 | AirLoopHVAC:UnitarySystem | SPLIT TNW_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 11305.17309 |
| 619 | AirLoopHVAC:UnitarySystem | SPLIT TNW_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 620 | AirLoopHVAC:UnitarySystem | SPLIT TNW_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 621 | Fan:OnOff | SPLIT TNW SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.45082 |
| 622 | Coil:Cooling:DX:SingleSpeed | SPLIT TNW COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.45082 |
| 623 | Coil:Cooling:DX:SingleSpeed | SPLIT TNW COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 7797.78060 |
| 624 | Coil:Cooling:DX:SingleSpeed | SPLIT TNW COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80086 |
| 625 | Coil:Heating:Fuel | SPLIT TNW HEATING COIL | Design Size Nominal Capacity [W] | 11305.17309 |
| 626 | Controller:OutdoorAir | SPLIT TSE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.40102 |
| 627 | Controller:OutdoorAir | SPLIT TSE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.59546E-002 |
| 628 | AirLoopHVAC:UnitarySystem | SPLIT TSE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.40102 |
| 629 | AirLoopHVAC:UnitarySystem | SPLIT TSE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.40102 |
| 630 | AirLoopHVAC:UnitarySystem | SPLIT TSE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.40102 |
| 631 | AirLoopHVAC:UnitarySystem | SPLIT TSE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.40102 |
| 632 | AirLoopHVAC:UnitarySystem | SPLIT TSE_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 7056.70619 |
| 633 | AirLoopHVAC:UnitarySystem | SPLIT TSE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 10166.58885 |
| 634 | AirLoopHVAC:UnitarySystem | SPLIT TSE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 635 | AirLoopHVAC:UnitarySystem | SPLIT TSE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 636 | Fan:OnOff | SPLIT TSE SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.40102 |
| 637 | Coil:Cooling:DX:SingleSpeed | SPLIT TSE COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.40102 |
| 638 | Coil:Cooling:DX:SingleSpeed | SPLIT TSE COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 7056.70619 |
| 639 | Coil:Cooling:DX:SingleSpeed | SPLIT TSE COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80085 |
| 640 | Coil:Heating:Fuel | SPLIT TSE HEATING COIL | Design Size Nominal Capacity [W] | 10166.58885 |
| 641 | Controller:OutdoorAir | SPLIT TNE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.39711 |
| 642 | Controller:OutdoorAir | SPLIT TNE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.59546E-002 |
| 643 | AirLoopHVAC:UnitarySystem | SPLIT TNE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.39711 |
| 644 | AirLoopHVAC:UnitarySystem | SPLIT TNE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.39711 |
| 645 | AirLoopHVAC:UnitarySystem | SPLIT TNE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.39711 |
| 646 | AirLoopHVAC:UnitarySystem | SPLIT TNE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.39711 |
| 647 | AirLoopHVAC:UnitarySystem | SPLIT TNE_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 6984.40841 |
| 648 | AirLoopHVAC:UnitarySystem | SPLIT TNE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 10077.14029 |
| 649 | AirLoopHVAC:UnitarySystem | SPLIT TNE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 650 | AirLoopHVAC:UnitarySystem | SPLIT TNE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 651 | Fan:OnOff | SPLIT TNE SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.39711 |
| 652 | Coil:Cooling:DX:SingleSpeed | SPLIT TNE COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.39711 |
| 653 | Coil:Cooling:DX:SingleSpeed | SPLIT TNE COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 6984.40841 |
| 654 | Coil:Cooling:DX:SingleSpeed | SPLIT TNE COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80003 |
| 655 | Coil:Heating:Fuel | SPLIT TNE HEATING COIL | Design Size Nominal Capacity [W] | 10077.14029 |
| 656 | Controller:OutdoorAir | SPLIT TN1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.37038 |
| 657 | Controller:OutdoorAir | SPLIT TN1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.59546E-002 |
| 658 | AirLoopHVAC:UnitarySystem | SPLIT TN1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.37038 |
| 659 | AirLoopHVAC:UnitarySystem | SPLIT TN1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.37038 |
| 660 | AirLoopHVAC:UnitarySystem | SPLIT TN1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.37038 |
| 661 | AirLoopHVAC:UnitarySystem | SPLIT TN1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.37038 |
| 662 | AirLoopHVAC:UnitarySystem | SPLIT TN1_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 6449.17614 |
| 663 | AirLoopHVAC:UnitarySystem | SPLIT TN1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 9465.44837 |
| 664 | AirLoopHVAC:UnitarySystem | SPLIT TN1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 665 | AirLoopHVAC:UnitarySystem | SPLIT TN1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 666 | Fan:OnOff | SPLIT TN1 SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.37038 |
| 667 | Coil:Cooling:DX:SingleSpeed | SPLIT TN1 COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.37038 |
| 668 | Coil:Cooling:DX:SingleSpeed | SPLIT TN1 COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 6449.17614 |
| 669 | Coil:Cooling:DX:SingleSpeed | SPLIT TN1 COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80052 |
| 670 | Coil:Heating:Fuel | SPLIT TN1 HEATING COIL | Design Size Nominal Capacity [W] | 9465.44837 |
| 671 | Controller:OutdoorAir | SPLIT TN2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.36844 |
| 672 | Controller:OutdoorAir | SPLIT TN2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.59546E-002 |
| 673 | AirLoopHVAC:UnitarySystem | SPLIT TN2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.36844 |
| 674 | AirLoopHVAC:UnitarySystem | SPLIT TN2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.36844 |
| 675 | AirLoopHVAC:UnitarySystem | SPLIT TN2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.36844 |
| 676 | AirLoopHVAC:UnitarySystem | SPLIT TN2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.36844 |
| 677 | AirLoopHVAC:UnitarySystem | SPLIT TN2_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 6419.95640 |
| 678 | AirLoopHVAC:UnitarySystem | SPLIT TN2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 9421.03078 |
| 679 | AirLoopHVAC:UnitarySystem | SPLIT TN2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 680 | AirLoopHVAC:UnitarySystem | SPLIT TN2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 681 | Fan:OnOff | SPLIT TN2 SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.36844 |
| 682 | Coil:Cooling:DX:SingleSpeed | SPLIT TN2 COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.36844 |
| 683 | Coil:Cooling:DX:SingleSpeed | SPLIT TN2 COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 6419.95640 |
| 684 | Coil:Cooling:DX:SingleSpeed | SPLIT TN2 COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80027 |
| 685 | Coil:Heating:Fuel | SPLIT TN2 HEATING COIL | Design Size Nominal Capacity [W] | 9421.03078 |
| 686 | Controller:OutdoorAir | SPLIT TS1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.37540 |
| 687 | Controller:OutdoorAir | SPLIT TS1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.59546E-002 |
| 688 | AirLoopHVAC:UnitarySystem | SPLIT TS1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.37540 |
| 689 | AirLoopHVAC:UnitarySystem | SPLIT TS1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.37540 |
| 690 | AirLoopHVAC:UnitarySystem | SPLIT TS1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.37540 |
| 691 | AirLoopHVAC:UnitarySystem | SPLIT TS1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.37540 |
| 692 | AirLoopHVAC:UnitarySystem | SPLIT TS1_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 6539.89410 |
| 693 | AirLoopHVAC:UnitarySystem | SPLIT TS1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 9580.42468 |
| 694 | AirLoopHVAC:UnitarySystem | SPLIT TS1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 695 | AirLoopHVAC:UnitarySystem | SPLIT TS1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 696 | Fan:OnOff | SPLIT TS1 SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.37540 |
| 697 | Coil:Cooling:DX:SingleSpeed | SPLIT TS1 COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.37540 |
| 698 | Coil:Cooling:DX:SingleSpeed | SPLIT TS1 COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 6539.89410 |
| 699 | Coil:Cooling:DX:SingleSpeed | SPLIT TS1 COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80035 |
| 700 | Coil:Heating:Fuel | SPLIT TS1 HEATING COIL | Design Size Nominal Capacity [W] | 9580.42468 |
| 701 | Controller:OutdoorAir | SPLIT TS2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.37347 |
| 702 | Controller:OutdoorAir | SPLIT TS2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.59546E-002 |
| 703 | AirLoopHVAC:UnitarySystem | SPLIT TS2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.37347 |
| 704 | AirLoopHVAC:UnitarySystem | SPLIT TS2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.37347 |
| 705 | AirLoopHVAC:UnitarySystem | SPLIT TS2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.37347 |
| 706 | AirLoopHVAC:UnitarySystem | SPLIT TS2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.37347 |
| 707 | AirLoopHVAC:UnitarySystem | SPLIT TS2_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 6510.87314 |
| 708 | AirLoopHVAC:UnitarySystem | SPLIT TS2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 9536.20403 |
| 709 | AirLoopHVAC:UnitarySystem | SPLIT TS2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 710 | AirLoopHVAC:UnitarySystem | SPLIT TS2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 711 | Fan:OnOff | SPLIT TS2 SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.37347 |
| 712 | Coil:Cooling:DX:SingleSpeed | SPLIT TS2 COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.37347 |
| 713 | Coil:Cooling:DX:SingleSpeed | SPLIT TS2 COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 6510.87314 |
| 714 | Coil:Cooling:DX:SingleSpeed | SPLIT TS2 COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80010 |
| 715 | Coil:Heating:Fuel | SPLIT TS2 HEATING COIL | Design Size Nominal Capacity [W] | 9536.20403 |
| Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
| 1 | Coil:Cooling:DX:SingleSpeed | SPLIT GSW COOLING COIL | 5775.7 | 3.16 | 10.80 | 11.23 | 10.62 | 10.56 |
| 2 | Coil:Cooling:DX:SingleSpeed | SPLIT GNW COOLING COIL | 5531.5 | 3.17 | 10.81 | 11.23 | 10.63 | 10.57 |
| 3 | Coil:Cooling:DX:SingleSpeed | SPLIT OFFICE COOLING COIL | 6689.9 | 3.16 | 10.78 | 11.20 | 10.60 | 10.53 |
| 4 | Coil:Cooling:DX:SingleSpeed | SPLIT GNE COOLING COIL | 5178.4 | 3.18 | 10.83 | 11.27 | 10.66 | 10.61 |
| 5 | Coil:Cooling:DX:SingleSpeed | SPLIT GN1 COOLING COIL | 4662.7 | 3.18 | 10.84 | 11.27 | 10.67 | 10.63 |
| 6 | Coil:Cooling:DX:SingleSpeed | SPLIT GN2 COOLING COIL | 4660.7 | 3.18 | 10.84 | 11.28 | 10.67 | 10.63 |
| 7 | Coil:Cooling:DX:SingleSpeed | SPLIT GS1 COOLING COIL | 4987.0 | 3.17 | 10.83 | 11.26 | 10.65 | 10.61 |
| 8 | Coil:Cooling:DX:SingleSpeed | SPLIT GS2 COOLING COIL | 5015.1 | 3.17 | 10.83 | 11.26 | 10.65 | 10.60 |
| 9 | Coil:Cooling:DX:SingleSpeed | SPLIT MSW COOLING COIL | 13805.5 | 3.15 | 10.76 | 11.19 | 10.59 | 10.51 |
| 10 | Coil:Cooling:DX:SingleSpeed | SPLIT MNW COOLING COIL | 13412.3 | 3.16 | 10.77 | 11.19 | 10.59 | 10.52 |
| 11 | Coil:Cooling:DX:SingleSpeed | SPLIT MSE COOLING COIL | 12770.0 | 3.16 | 10.79 | 11.22 | 10.61 | 10.55 |
| 12 | Coil:Cooling:DX:SingleSpeed | SPLIT MNE COOLING COIL | 12384.6 | 3.16 | 10.80 | 11.23 | 10.62 | 10.56 |
| 13 | Coil:Cooling:DX:SingleSpeed | SPLIT MN1 COOLING COIL | 11102.4 | 3.17 | 10.80 | 11.23 | 10.62 | 10.56 |
| 14 | Coil:Cooling:DX:SingleSpeed | SPLIT MN2 COOLING COIL | 11081.4 | 3.17 | 10.80 | 11.23 | 10.62 | 10.56 |
| 15 | Coil:Cooling:DX:SingleSpeed | SPLIT MS1 COOLING COIL | 11562.3 | 3.16 | 10.79 | 11.22 | 10.61 | 10.55 |
| 16 | Coil:Cooling:DX:SingleSpeed | SPLIT MS2 COOLING COIL | 11540.4 | 3.16 | 10.79 | 11.22 | 10.61 | 10.55 |
| 17 | Coil:Cooling:DX:SingleSpeed | SPLIT TSW COOLING COIL | 7511.1 | 3.16 | 10.77 | 11.19 | 10.59 | 10.51 |
| 18 | Coil:Cooling:DX:SingleSpeed | SPLIT TNW COOLING COIL | 7444.3 | 3.15 | 10.76 | 11.19 | 10.58 | 10.51 |
| 19 | Coil:Cooling:DX:SingleSpeed | SPLIT TSE COOLING COIL | 6742.2 | 3.17 | 10.80 | 11.23 | 10.62 | 10.56 |
| 20 | Coil:Cooling:DX:SingleSpeed | SPLIT TNE COOLING COIL | 6672.9 | 3.16 | 10.80 | 11.23 | 10.62 | 10.56 |
| 21 | Coil:Cooling:DX:SingleSpeed | SPLIT TN1 COOLING COIL | 6158.7 | 3.16 | 10.78 | 11.20 | 10.60 | 10.53 |
| 22 | Coil:Cooling:DX:SingleSpeed | SPLIT TN2 COOLING COIL | 6131.0 | 3.16 | 10.78 | 11.21 | 10.60 | 10.53 |
| 23 | Coil:Cooling:DX:SingleSpeed | SPLIT TS1 COOLING COIL | 6245.5 | 3.16 | 10.78 | 11.21 | 10.60 | 10.53 |
| 24 | Coil:Cooling:DX:SingleSpeed | SPLIT TS2 COOLING COIL | 6218.0 | 3.16 | 10.78 | 11.21 | 10.60 | 10.54 |
| Zone Name | # Surfaces | |
| 1 | G SW APARTMENT | 9 |
| 2 | G NW APARTMENT | 9 |
| 3 | OFFICE | 9 |
| 4 | G NE APARTMENT | 9 |
| 5 | G N1 APARTMENT | 8 |
| 6 | G N2 APARTMENT | 8 |
| 7 | G S1 APARTMENT | 8 |
| 8 | G S2 APARTMENT | 8 |
| 9 | M SW APARTMENT | 9 |
| 10 | M NW APARTMENT | 9 |
| 11 | M SE APARTMENT | 9 |
| 12 | M NE APARTMENT | 9 |
| 13 | M N1 APARTMENT | 8 |
| 14 | M N2 APARTMENT | 8 |
| 15 | M S1 APARTMENT | 8 |
| 16 | M S2 APARTMENT | 8 |
| 17 | T SW APARTMENT | 9 |
| 18 | T NW APARTMENT | 9 |
| 19 | T SE APARTMENT | 9 |
| 20 | T NE APARTMENT | 9 |
| 21 | T N1 APARTMENT | 8 |
| 22 | T N2 APARTMENT | 8 |
| 23 | T S1 APARTMENT | 8 |
| 24 | T S2 APARTMENT | 8 |
| 25 | T CORRIDOR | 13 |
| 26 | G CORRIDOR | 13 |
| 27 | M CORRIDOR | 13 |
| Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
| 1 | G SWALL SWA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_GRD | 0.752 | 0.676 | 28.24 | 35.30 | 28.24 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 2 | GWINDOW1 S SWA | Window | G SWALL SWA | Window5 Detailed Fenestration | RESWINDOW_U_0.3972_SHGC_0.4 | N/A | 2.257 | No | 7.06 | 7.06 | 7.06 | 180.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 3 | G WWALL SWA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_GRD | 0.752 | 0.676 | 18.58 | 23.22 | 18.58 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 4 | GWINDOW1 W SWA | Window | G WWALL SWA | Window5 Detailed Fenestration | RESWINDOW_U_0.3972_SHGC_0.4 | N/A | 2.257 | No | 4.65 | 4.65 | 4.65 | 270.00 | 90.00 | 3.81 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 5 | G NIWALL SWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-G NIWALL SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 6 | G EIWALL SWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | iz-G EIWALL SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 7 | G GFLOOR SWA | Floor | CTF - ConductionTransferFunction | GGFLOORSWA_FFACTOR | 0.210 | 0.200 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 8 | G CEILIN SWA | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | G CEILIN SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 9 | G INTERNALMASS SWA | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 88.25 | 88.25 | 88.25 | 0.00 | 90.00 | 88.25 | 1.00 | 0.00 | G INTERNALMASS SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 10 | G NWALL NWA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_GRD | 0.752 | 0.676 | 28.24 | 35.30 | 28.24 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 11 | GWINDOW1 N NWA | Window | G NWALL NWA | Window5 Detailed Fenestration | RESWINDOW_U_0.3972_SHGC_0.4 | N/A | 2.257 | No | 7.06 | 7.06 | 7.06 | 0.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 12 | G WWALL NWA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_GRD | 0.752 | 0.676 | 18.58 | 23.22 | 18.58 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 13 | GWINDOW1 W NWA | Window | G WWALL NWA | Window5 Detailed Fenestration | RESWINDOW_U_0.3972_SHGC_0.4 | N/A | 2.257 | No | 4.65 | 4.65 | 4.65 | 270.00 | 90.00 | 3.81 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 14 | G SIWALL NWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-G SIWALL NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 15 | G EIWALL NWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | iz-G EIWALL NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 16 | G GFLOOR NWA | Floor | CTF - ConductionTransferFunction | GGFLOORNWA_FFACTOR | 0.210 | 0.200 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 17 | G CEILIN NWA | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | G CEILIN NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 18 | G INTERNALMASS NWA | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 88.25 | 88.25 | 88.25 | 0.00 | 90.00 | 88.25 | 1.00 | 0.00 | G INTERNALMASS NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 19 | G SWALL SEA | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.752 | 0.676 | 28.24 | 35.30 | 28.24 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 20 | GWINDOW1 S SEA | Window | G SWALL SEA | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3972_SHGC_0.4 | N/A | 2.257 | No | 7.06 | 7.06 | 7.06 | 180.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 21 | G EWALL SEA | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.752 | 0.676 | 18.58 | 23.22 | 18.58 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 22 | GWINDOW1 E SEA | Window | G EWALL SEA | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3972_SHGC_0.4 | N/A | 2.257 | No | 4.65 | 4.65 | 4.65 | 90.00 | 90.00 | 3.81 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 23 | G NIWALL SEA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-G NIWALL SEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 24 | iz-G EIWALL S2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | G EIWALL S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 25 | G GFLOOR SEA | Floor | CTF - ConductionTransferFunction | GGFLOORSEA_FFACTOR | 0.210 | 0.200 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 26 | G CEILIN SEA | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | G CEILIN SEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 27 | G INTERNALMASS SEA | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 88.25 | 88.25 | 88.25 | 0.00 | 90.00 | 88.25 | 1.00 | 0.00 | G INTERNALMASS SEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 28 | G NWALL NEA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_GRD | 0.752 | 0.676 | 28.24 | 35.30 | 28.24 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 29 | GWINDOW1 N NEA | Window | G NWALL NEA | Window5 Detailed Fenestration | RESWINDOW_U_0.3972_SHGC_0.4 | N/A | 2.257 | No | 7.06 | 7.06 | 7.06 | 0.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 30 | G EWALL NEA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_GRD | 0.752 | 0.676 | 18.58 | 23.22 | 18.58 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 31 | GWINDOW1 E NEA | Window | G EWALL NEA | Window5 Detailed Fenestration | RESWINDOW_U_0.3972_SHGC_0.4 | N/A | 2.257 | No | 4.65 | 4.65 | 4.65 | 90.00 | 90.00 | 3.81 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 32 | G SIWALL NEA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-G SIWALL NEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 33 | iz-G EIWALL N2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | G EIWALL N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 34 | G GFLOOR NEA | Floor | CTF - ConductionTransferFunction | GGFLOORNEA_FFACTOR | 0.210 | 0.200 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 35 | G CEILIN NEA | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | G CEILIN NEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 36 | G INTERNALMASS NEA | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 88.25 | 88.25 | 88.25 | 0.00 | 90.00 | 88.25 | 1.00 | 0.00 | G INTERNALMASS NEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 37 | G NWALL N1A | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_GRD | 0.752 | 0.676 | 28.24 | 35.30 | 28.24 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 38 | GWINDOW1 N N1A | Window | G NWALL N1A | Window5 Detailed Fenestration | RESWINDOW_U_0.3972_SHGC_0.4 | N/A | 2.257 | No | 7.06 | 7.06 | 7.06 | 0.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 39 | G SIWALL N1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-G SIWALL N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 40 | G EIWALL N1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | iz-G EIWALL N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 41 | iz-G EIWALL NWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | G EIWALL NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 42 | G GFLOOR N1A | Floor | CTF - ConductionTransferFunction | GGFLOORN1A_FFACTOR | 0.125 | 0.121 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 43 | G CEILIN N1A | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | G CEILIN N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 44 | G INTERNALMASS N1A | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 88.25 | 88.25 | 88.25 | 0.00 | 90.00 | 88.25 | 1.00 | 0.00 | G INTERNALMASS N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 45 | G NWALL N2A | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_GRD | 0.752 | 0.676 | 28.24 | 35.30 | 28.24 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 46 | GWINDOW1 N N2A | Window | G NWALL N2A | Window5 Detailed Fenestration | RESWINDOW_U_0.3972_SHGC_0.4 | N/A | 2.257 | No | 7.06 | 7.06 | 7.06 | 0.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 47 | G SIWALL N2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-G SIWALL N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 48 | G EIWALL N2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | iz-G EIWALL N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 49 | iz-G EIWALL N1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | G EIWALL N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 50 | G GFLOOR N2A | Floor | CTF - ConductionTransferFunction | GGFLOORN2A_FFACTOR | 0.125 | 0.121 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 51 | G CEILIN N2A | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | G CEILIN N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 52 | G INTERNALMASS N2A | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 88.25 | 88.25 | 88.25 | 0.00 | 90.00 | 88.25 | 1.00 | 0.00 | G INTERNALMASS N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 53 | G SWALL S1A | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_GRD | 0.752 | 0.676 | 28.24 | 35.30 | 28.24 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 54 | GWINDOW1 S S1A | Window | G SWALL S1A | Window5 Detailed Fenestration | RESWINDOW_U_0.3972_SHGC_0.4 | N/A | 2.257 | No | 7.06 | 7.06 | 7.06 | 180.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 55 | G NIWALL S1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-G NIWALL S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 56 | G EIWALL S1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | iz-G EIWALL S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 57 | iz-G EIWALL SWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | G EIWALL SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 58 | G GFLOOR S1A | Floor | CTF - ConductionTransferFunction | GGFLOORS1A_FFACTOR | 0.125 | 0.121 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 59 | G CEILIN S1A | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | G CEILIN S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 60 | G INTERNALMASS S1A | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 88.25 | 88.25 | 88.25 | 0.00 | 90.00 | 88.25 | 1.00 | 0.00 | G INTERNALMASS S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 61 | G SWALL S2A | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_GRD | 0.752 | 0.676 | 28.24 | 35.30 | 28.24 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 62 | GWINDOW1 S S2A | Window | G SWALL S2A | Window5 Detailed Fenestration | RESWINDOW_U_0.3972_SHGC_0.4 | N/A | 2.257 | No | 7.06 | 7.06 | 7.06 | 180.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 63 | G NIWALL S2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-G NIWALL S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 64 | G EIWALL S2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | iz-G EIWALL S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 65 | iz-G EIWALL S1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | G EIWALL S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 66 | G GFLOOR S2A | Floor | CTF - ConductionTransferFunction | GGFLOORS2A_FFACTOR | 0.125 | 0.121 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 67 | G CEILIN S2A | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | G CEILIN S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 68 | G INTERNALMASS S2A | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 88.25 | 88.25 | 88.25 | 0.00 | 90.00 | 88.25 | 1.00 | 0.00 | G INTERNALMASS S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 69 | M WWALL SWA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.761 | 0.683 | 18.58 | 23.22 | 18.58 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 70 | MWINDOW1 W SWA | Window | M WWALL SWA | Window5 Detailed Fenestration | RESWINDOW_U_0.3972_SHGC_0.4 | N/A | 2.257 | No | 4.65 | 4.65 | 4.65 | 270.00 | 90.00 | 3.81 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 71 | M SWALL SWA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.761 | 0.683 | 28.24 | 35.30 | 28.24 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 72 | MWINDOW1 S SWA | Window | M SWALL SWA | Window5 Detailed Fenestration | RESWINDOW_U_0.3972_SHGC_0.4 | N/A | 2.257 | No | 7.06 | 7.06 | 7.06 | 180.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 73 | M NIWALL SWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-M NIWALL SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 74 | M EIWALL SWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 90.00 | 90.00 | 3.05 | 7.62 | 0.00 | iz-M EIWALL SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 75 | M GFLOOR SWA | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | M GFLOOR SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 76 | M CEILIN SWA | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | M CEILIN SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 77 | M INTERNALMASS SWA | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 176.50 | 176.50 | 176.50 | 0.00 | 90.00 | 176.50 | 1.00 | 0.00 | M INTERNALMASS SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 78 | M NWALL NWA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.761 | 0.683 | 28.24 | 35.30 | 28.24 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 79 | MWINDOW1 N NWA | Window | M NWALL NWA | Window5 Detailed Fenestration | RESWINDOW_U_0.3972_SHGC_0.4 | N/A | 2.257 | No | 7.06 | 7.06 | 7.06 | 0.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 80 | M WWALL NWA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.761 | 0.683 | 18.58 | 23.22 | 18.58 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 81 | MWINDOW1 W NWA | Window | M WWALL NWA | Window5 Detailed Fenestration | RESWINDOW_U_0.3972_SHGC_0.4 | N/A | 2.257 | No | 4.65 | 4.65 | 4.65 | 270.00 | 90.00 | 3.81 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 82 | M SIWALL NWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-M SIWALL NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 83 | M EIWALL NWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | iz-M EIWALL NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 84 | M GFLOOR NWA | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | M GFLOOR NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 85 | M CEILIN NWA | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | M CEILIN NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 86 | M INTERNALMASS NWA | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 176.50 | 176.50 | 176.50 | 0.00 | 90.00 | 176.50 | 1.00 | 0.00 | M INTERNALMASS NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 87 | M EWALL SEA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.761 | 0.683 | 18.58 | 23.22 | 18.58 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 88 | MWINDOW1 E SEA | Window | M EWALL SEA | Window5 Detailed Fenestration | RESWINDOW_U_0.3972_SHGC_0.4 | N/A | 2.257 | No | 4.65 | 4.65 | 4.65 | 90.00 | 90.00 | 3.81 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 89 | M SWALL SEA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.761 | 0.683 | 28.24 | 35.30 | 28.24 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 90 | MWINDOW1 S SEA | Window | M SWALL SEA | Window5 Detailed Fenestration | RESWINDOW_U_0.3972_SHGC_0.4 | N/A | 2.257 | No | 7.06 | 7.06 | 7.06 | 180.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 91 | M NIWALL SEA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-M NIWALL SEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 92 | iz-M EIWALL S2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | M EIWALL S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 93 | M GFLOOR SEA | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | M GFLOOR SEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 94 | M CEILIN SEA | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | M CEILIN SEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 95 | M INTERNALMASS SEA | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 176.50 | 176.50 | 176.50 | 0.00 | 90.00 | 176.50 | 1.00 | 0.00 | M INTERNALMASS SEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 96 | M NWALL NEA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.761 | 0.683 | 28.24 | 35.30 | 28.24 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 97 | MWINDOW1 N NEA | Window | M NWALL NEA | Window5 Detailed Fenestration | RESWINDOW_U_0.3972_SHGC_0.4 | N/A | 2.257 | No | 7.06 | 7.06 | 7.06 | 0.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 98 | M EWALL NEA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.761 | 0.683 | 18.58 | 23.22 | 18.58 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 99 | MWINDOW1 E NEA | Window | M EWALL NEA | Window5 Detailed Fenestration | RESWINDOW_U_0.3972_SHGC_0.4 | N/A | 2.257 | No | 4.65 | 4.65 | 4.65 | 90.00 | 90.00 | 3.81 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 100 | M SIWALL NEA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-M SIWALL NEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 101 | iz-M EIWALL N2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | M EIWALL N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 102 | M GFLOOR NEA | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | M GFLOOR NEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 103 | M CEILIN NEA | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | M CEILIN NEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 104 | M INTERNALMASS NEA | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 176.50 | 176.50 | 176.50 | 0.00 | 90.00 | 176.50 | 1.00 | 0.00 | M INTERNALMASS NEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 105 | M NWALL N1A | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.761 | 0.683 | 28.24 | 35.30 | 28.24 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 106 | MWINDOW1 N N1A | Window | M NWALL N1A | Window5 Detailed Fenestration | RESWINDOW_U_0.3972_SHGC_0.4 | N/A | 2.257 | No | 7.06 | 7.06 | 7.06 | 0.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 107 | M SIWALL N1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-M SIWALL N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 108 | M EIWALL N1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | iz-M EIWALL N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 109 | iz-M EIWALL NWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | M EIWALL NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 110 | M GFLOOR N1A | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | M GFLOOR N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 111 | M CEILIN N1A | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | M CEILIN N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 112 | M INTERNALMASS N1A | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 176.50 | 176.50 | 176.50 | 0.00 | 90.00 | 176.50 | 1.00 | 0.00 | M INTERNALMASS N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 113 | M NWALL N2A | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.761 | 0.683 | 28.24 | 35.30 | 28.24 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 114 | MWINDOW1 N N2A | Window | M NWALL N2A | Window5 Detailed Fenestration | RESWINDOW_U_0.3972_SHGC_0.4 | N/A | 2.257 | No | 7.06 | 7.06 | 7.06 | 0.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 115 | M SIWALL N2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-M SIWALL N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 116 | M EIWALL N2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | iz-M EIWALL N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 117 | iz-M EIWALL N1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | M EIWALL N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 118 | M GFLOOR N2A | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | M GFLOOR N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 119 | M CEILIN N2A | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | M CEILIN N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 120 | M INTERNALMASS N2A | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 176.50 | 176.50 | 176.50 | 0.00 | 90.00 | 176.50 | 1.00 | 0.00 | M INTERNALMASS N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 121 | M SWALL S1A | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.761 | 0.683 | 28.24 | 35.30 | 28.24 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 122 | MWINDOW1 S S1A | Window | M SWALL S1A | Window5 Detailed Fenestration | RESWINDOW_U_0.3972_SHGC_0.4 | N/A | 2.257 | No | 7.06 | 7.06 | 7.06 | 180.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 123 | M NIWALL S1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-M NIWALL S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 124 | M EIWALL S1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | iz-M EIWALL S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 125 | iz-M EIWALL SWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 270.00 | 90.00 | 3.05 | 7.62 | 0.00 | M EIWALL SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 126 | M GFLOOR S1A | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | M GFLOOR S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 127 | M CEILIN S1A | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | M CEILIN S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 128 | M INTERNALMASS S1A | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 176.50 | 176.50 | 176.50 | 0.00 | 90.00 | 176.50 | 1.00 | 0.00 | M INTERNALMASS S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 129 | M SWALL S2A | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.761 | 0.683 | 28.24 | 35.30 | 28.24 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 130 | MWINDOW1 S S2A | Window | M SWALL S2A | Window5 Detailed Fenestration | RESWINDOW_U_0.3972_SHGC_0.4 | N/A | 2.257 | No | 7.06 | 7.06 | 7.06 | 180.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 131 | M NIWALL S2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-M NIWALL S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 132 | M EIWALL S2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | iz-M EIWALL S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 133 | iz-M EIWALL S1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | M EIWALL S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 134 | M GFLOOR S2A | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | M GFLOOR S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 135 | M CEILIN S2A | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | M CEILIN S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 136 | M INTERNALMASS S2A | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 176.50 | 176.50 | 176.50 | 0.00 | 90.00 | 176.50 | 1.00 | 0.00 | M INTERNALMASS S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 137 | T WWALL SWA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.098 | 0.943 | 18.58 | 23.22 | 18.58 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 138 | TWINDOW1 W SWA | Window | T WWALL SWA | Window5 Detailed Fenestration | RESWINDOW_U_0.3972_SHGC_0.4 | N/A | 2.257 | No | 4.65 | 4.65 | 4.65 | 270.00 | 90.00 | 3.81 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 139 | T SWALL SWA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.098 | 0.943 | 28.24 | 35.30 | 28.24 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 140 | TWINDOW1 S SWA | Window | T SWALL SWA | Window5 Detailed Fenestration | RESWINDOW_U_0.3972_SHGC_0.4 | N/A | 2.257 | No | 7.06 | 7.06 | 7.06 | 180.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 141 | T NIWALL SWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-T NIWALL SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 142 | T EIWALL SWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | iz-T EIWALL SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 143 | T GFLOOR SWA | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | T GFLOOR SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 144 | T ROOF SWA | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.228 | 0.219 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 145 | T INTERNALMASS SWA | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 88.25 | 88.25 | 88.25 | 0.00 | 90.00 | 88.25 | 1.00 | 0.00 | T INTERNALMASS SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 146 | T NWALL NWA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.098 | 0.943 | 28.24 | 35.30 | 28.24 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 147 | TWINDOW1 N NWA | Window | T NWALL NWA | Window5 Detailed Fenestration | RESWINDOW_U_0.3972_SHGC_0.4 | N/A | 2.257 | No | 7.06 | 7.06 | 7.06 | 0.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 148 | T WWALL NWA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.098 | 0.943 | 18.58 | 23.22 | 18.58 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 149 | TWINDOW1 W NWA | Window | T WWALL NWA | Window5 Detailed Fenestration | RESWINDOW_U_0.3972_SHGC_0.4 | N/A | 2.257 | No | 4.65 | 4.65 | 4.65 | 270.00 | 90.00 | 3.81 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 150 | T SIWALL NWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-T SIWALL NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 151 | T EIWALL NWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | iz-T EIWALL NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 152 | T GFLOOR NWA | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | T GFLOOR NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 153 | T ROOF NWA | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.228 | 0.219 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 154 | T INTERNALMASS NWA | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 88.25 | 88.25 | 88.25 | 0.00 | 90.00 | 88.25 | 1.00 | 0.00 | T INTERNALMASS NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 155 | T EWALL SEA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.098 | 0.943 | 18.58 | 23.22 | 18.58 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 156 | TWINDOW1 E SEA | Window | T EWALL SEA | Window5 Detailed Fenestration | RESWINDOW_U_0.3972_SHGC_0.4 | N/A | 2.257 | No | 4.65 | 4.65 | 4.65 | 90.00 | 90.00 | 3.81 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 157 | T SWALL SEA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.098 | 0.943 | 28.24 | 35.30 | 28.24 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 158 | TWINDOW1 S SEA | Window | T SWALL SEA | Window5 Detailed Fenestration | RESWINDOW_U_0.3972_SHGC_0.4 | N/A | 2.257 | No | 7.06 | 7.06 | 7.06 | 180.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 159 | T NIWALL SEA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-T NIWALL SEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 160 | iz-T EIWALL S2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | T EIWALL S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 161 | T GFLOOR SEA | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | T GFLOOR SEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 162 | T ROOF SEA | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.228 | 0.219 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 163 | T INTERNALMASS SEA | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 88.25 | 88.25 | 88.25 | 0.00 | 90.00 | 88.25 | 1.00 | 0.00 | T INTERNALMASS SEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 164 | T NWALL NEA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.098 | 0.943 | 28.24 | 35.30 | 28.24 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 165 | TWINDOW1 N NEA | Window | T NWALL NEA | Window5 Detailed Fenestration | RESWINDOW_U_0.3972_SHGC_0.4 | N/A | 2.257 | No | 7.06 | 7.06 | 7.06 | 0.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 166 | T EWALL NEA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.098 | 0.943 | 18.58 | 23.22 | 18.58 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 167 | TWINDOW1 E NEA | Window | T EWALL NEA | Window5 Detailed Fenestration | RESWINDOW_U_0.3972_SHGC_0.4 | N/A | 2.257 | No | 4.65 | 4.65 | 4.65 | 90.00 | 90.00 | 3.81 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 168 | T SIWALL NEA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-T SIWALL NEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 169 | iz-T EIWALL N2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | T EIWALL N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 170 | T GFLOOR NEA | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | T GFLOOR NEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 171 | T ROOF NEA | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.228 | 0.219 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 172 | T INTERNALMASS NEA | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 88.25 | 88.25 | 88.25 | 0.00 | 90.00 | 88.25 | 1.00 | 0.00 | T INTERNALMASS NEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 173 | T NWALL N1A | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.098 | 0.943 | 28.24 | 35.30 | 28.24 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 174 | TWINDOW1 N N1A | Window | T NWALL N1A | Window5 Detailed Fenestration | RESWINDOW_U_0.3972_SHGC_0.4 | N/A | 2.257 | No | 7.06 | 7.06 | 7.06 | 0.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 175 | T SIWALL N1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-T SIWALL N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 176 | T EIWALL N1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | iz-T EIWALL N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 177 | iz-T EIWALL NWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | T EIWALL NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 178 | T GFLOOR N1A | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | T GFLOOR N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 179 | T ROOF N1A | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.228 | 0.219 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 180 | T INTERNALMASS N1A | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 88.25 | 88.25 | 88.25 | 0.00 | 90.00 | 88.25 | 1.00 | 0.00 | T INTERNALMASS N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 181 | T NWALL N2A | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.098 | 0.943 | 28.24 | 35.30 | 28.24 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 182 | TWINDOW1 N N2A | Window | T NWALL N2A | Window5 Detailed Fenestration | RESWINDOW_U_0.3972_SHGC_0.4 | N/A | 2.257 | No | 7.06 | 7.06 | 7.06 | 0.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 183 | T SIWALL N2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-T SIWALL N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 184 | T EIWALL N2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | iz-T EIWALL N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 185 | iz-T EIWALL N1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | T EIWALL N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 186 | T GFLOOR N2A | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | T GFLOOR N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 187 | T ROOF N2A | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.228 | 0.219 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 188 | T INTERNALMASS N2A | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 88.25 | 88.25 | 88.25 | 0.00 | 90.00 | 88.25 | 1.00 | 0.00 | T INTERNALMASS N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 189 | T SWALL S1A | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.098 | 0.943 | 28.24 | 35.30 | 28.24 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 190 | TWINDOW1 S S1A | Window | T SWALL S1A | Window5 Detailed Fenestration | RESWINDOW_U_0.3972_SHGC_0.4 | N/A | 2.257 | No | 7.06 | 7.06 | 7.06 | 180.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 191 | T NIWALL S1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-T NIWALL S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 192 | T EIWALL S1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | iz-T EIWALL S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 193 | iz-T EIWALL SWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | T EIWALL SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 194 | T GFLOOR S1A | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | T GFLOOR S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 195 | T ROOF S1A | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.228 | 0.219 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 196 | T INTERNALMASS S1A | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 88.25 | 88.25 | 88.25 | 0.00 | 90.00 | 88.25 | 1.00 | 0.00 | T INTERNALMASS S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 197 | T SWALL S2A | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.098 | 0.943 | 28.24 | 35.30 | 28.24 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 198 | TWINDOW1 S S2A | Window | T SWALL S2A | Window5 Detailed Fenestration | RESWINDOW_U_0.3972_SHGC_0.4 | N/A | 2.257 | No | 7.06 | 7.06 | 7.06 | 180.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 199 | T NIWALL S2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-T NIWALL S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 200 | T EIWALL S2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | iz-T EIWALL S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 201 | iz-T EIWALL S1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | T EIWALL S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 202 | T GFLOOR S2A | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | T GFLOOR S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 203 | T ROOF S2A | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.228 | 0.219 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 204 | T INTERNALMASS S2A | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 88.25 | 88.25 | 88.25 | 0.00 | 90.00 | 88.25 | 1.00 | 0.00 | T INTERNALMASS S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 205 | T WWALL C | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.098 | 0.943 | 5.11 | 5.11 | 5.11 | 270.00 | 90.00 | 1.68 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 206 | T EWALL C | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.098 | 0.943 | 3.99 | 5.11 | 3.99 | 90.00 | 90.00 | 1.68 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 207 | TWINDOW14 | Window | T EWALL C | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3972_SHGC_0.4 | N/A | 2.257 | No | 1.11 | 1.11 | 1.11 | 90.00 | 90.00 | 0.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 208 | iz-T NIWALL SWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | T NIWALL SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 209 | iz-T NIWALL S1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | T NIWALL S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 210 | iz-T NIWALL S2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | T NIWALL S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 211 | iz-T NIWALL SEA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | T NIWALL SEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 212 | iz-T SIWALL NWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | T SIWALL NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 213 | iz-T SIWALL N1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | T SIWALL N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 214 | iz-T SIWALL N2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | T SIWALL N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 215 | iz-T SIWALL NEA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | T SIWALL NEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 216 | T FLOOR C | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 77.66 | 77.66 | 77.66 | 90.00 | 180.00 | 1.68 | 46.33 | 0.00 | T FLOOR C | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 217 | T ROOF C | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 77.66 | 77.66 | 77.66 | 180.00 | 0.00 | 46.33 | 1.68 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 218 | G WWALL C | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.752 | 0.676 | 5.11 | 5.11 | 5.11 | 270.00 | 90.00 | 1.68 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 219 | G EWALL C | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.752 | 0.676 | 1.79 | 5.11 | 1.79 | 90.00 | 90.00 | 1.68 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 220 | ENTRANCE DOOR | Window | G EWALL C | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3972_SHGC_0.4 | N/A | 2.257 | No | 3.32 | 3.32 | 3.32 | 90.00 | 90.00 | 1.57 | 2.11 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 221 | iz-G NIWALL SWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | G NIWALL SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 222 | iz-G NIWALL S1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | G NIWALL S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 223 | iz-G NIWALL S2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | G NIWALL S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 224 | iz-G NIWALL SEA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | G NIWALL SEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 225 | iz-G SIWALL NWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | G SIWALL NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 226 | iz-G SIWALL N1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | G SIWALL N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 227 | iz-G SIWALL N2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | G SIWALL N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 228 | iz-G SIWALL NEA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | G SIWALL NEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 229 | G FLOOR C | Floor | CTF - ConductionTransferFunction | GFLOORC_FFACTOR | 4.061E-002 | 4.021E-002 | 77.66 | 77.66 | 77.66 | 90.00 | 180.00 | 1.68 | 46.33 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 230 | G CEILING C | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 77.66 | 77.66 | 77.66 | 180.00 | 0.00 | 46.33 | 1.68 | 0.00 | G CEILING C | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 231 | M WWALL C | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.761 | 0.683 | 5.11 | 5.11 | 5.11 | 270.00 | 90.00 | 1.68 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 232 | M EWALL C | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.761 | 0.683 | 3.99 | 5.11 | 3.99 | 90.00 | 90.00 | 1.68 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 233 | MWINDOW14 | Window | M EWALL C | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3972_SHGC_0.4 | N/A | 2.257 | No | 1.11 | 1.11 | 1.11 | 90.00 | 90.00 | 0.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 234 | iz-M NIWALL SWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | M NIWALL SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 235 | iz-M NIWALL S1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | M NIWALL S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 236 | iz-M NIWALL S2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | M NIWALL S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 237 | iz-M NIWALL SEA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | M NIWALL SEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 238 | iz-M SIWALL NWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | M SIWALL NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 239 | iz-M SIWALL N1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | M SIWALL N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 240 | iz-M SIWALL N2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | M SIWALL N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 241 | iz-M SIWALL NEA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | M SIWALL NEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 242 | M FLOOR C | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 77.66 | 77.66 | 77.66 | 90.00 | 180.00 | 1.68 | 46.33 | 0.00 | M FLOOR C | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 243 | M CEILING C | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 77.66 | 77.66 | 77.66 | 180.00 | 0.00 | 46.33 | 1.68 | 0.00 | M CEILING C | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
| Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
| 1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | Yes | Yes | Yes | Clark and Allen |
| Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
| 1 | NEW YEAR'S DAY | Holiday | InputFile | 01/02 | 1Environment:Special Days |
| Daylight Saving Indicator | Source | Start Date | End Date | |
| 1 | Yes | InputFile | 03/12 | 11/05 |
| Style | Unit Conversion | |
| 1 | Commaandhtml | commaandhtml |
| Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
| 1 | G SW APARTMENT | RunPeriod: RUNPERIOD 1 | 1.5647445147E-007 | 6.6411018303E-007 | Pass | Pass | 2.6142751260E-002 | 1.9274429821E-002 | Pass | Pass |
| 2 | G NW APARTMENT | RunPeriod: RUNPERIOD 1 | 2.5911851425E-007 | 1.3060837766E-006 | Pass | Pass | 1.4479815410E-002 | 1.0587542671E-002 | Pass | Pass |
| 3 | OFFICE | RunPeriod: RUNPERIOD 1 | 7.8587050706E-008 | 3.1299118985E-007 | Pass | Pass | 0.1307675401 | 0.2902825253 | Pass | Pass |
| 4 | G NE APARTMENT | RunPeriod: RUNPERIOD 1 | 2.4038531309E-007 | 1.1861389549E-006 | Pass | Pass | 1.4696356080E-002 | 1.0387134264E-002 | Pass | Pass |
| 5 | G N1 APARTMENT | RunPeriod: RUNPERIOD 1 | 1.3365738393E-007 | 6.8349345197E-007 | Pass | Pass | 1.7846323594E-002 | 1.4677836258E-002 | Pass | Pass |
| 6 | G N2 APARTMENT | RunPeriod: RUNPERIOD 1 | 1.3313274342E-007 | 6.8056489148E-007 | Pass | Pass | 1.7929123242E-002 | 1.4699630664E-002 | Pass | Pass |
| 7 | G S1 APARTMENT | RunPeriod: RUNPERIOD 1 | 5.6990554448E-008 | 2.4914178618E-007 | Pass | Pass | 7.9824840008E-002 | 0.1367068374 | Pass | Pass |
| 8 | G S2 APARTMENT | RunPeriod: RUNPERIOD 1 | 7.9510263756E-008 | 3.4614355665E-007 | Pass | Pass | 3.9106811428E-002 | 3.5928062422E-002 | Pass | Pass |
| 9 | M SW APARTMENT | RunPeriod: RUNPERIOD 1 | 1.5425833383E-007 | 6.5578244248E-007 | Pass | Pass | 4.4985526877E-002 | 4.0314925870E-002 | Pass | Pass |
| 10 | M NW APARTMENT | RunPeriod: RUNPERIOD 1 | 2.4665645395E-007 | 1.2675604627E-006 | Pass | Pass | 1.9870595562E-002 | 1.4490618660E-002 | Pass | Pass |
| 11 | M SE APARTMENT | RunPeriod: RUNPERIOD 1 | 1.3648620360E-007 | 5.6453974594E-007 | Pass | Pass | 6.2012265017E-002 | 6.9809707046E-002 | Pass | Pass |
| 12 | M NE APARTMENT | RunPeriod: RUNPERIOD 1 | 2.2348080885E-007 | 1.1094119669E-006 | Pass | Pass | 2.0393420422E-002 | 1.4049496035E-002 | Pass | Pass |
| 13 | M N1 APARTMENT | RunPeriod: RUNPERIOD 1 | 1.0115486912E-007 | 5.2382887418E-007 | Pass | Pass | 2.8705535728E-002 | 2.1829965867E-002 | Pass | Pass |
| 14 | M N2 APARTMENT | RunPeriod: RUNPERIOD 1 | 1.0063871013E-007 | 5.2079541203E-007 | Pass | Pass | 2.8832787014E-002 | 2.1921416669E-002 | Pass | Pass |
| 15 | M S1 APARTMENT | RunPeriod: RUNPERIOD 1 | 3.0911036817E-008 | 1.5073111539E-007 | Pass | Pass | 0.1685342163 | 0.3879294782 | Pass | Pass |
| 16 | M S2 APARTMENT | RunPeriod: RUNPERIOD 1 | 3.0453977340E-008 | 1.4933132524E-007 | Pass | Pass | 0.1573735509 | 0.3017398490 | Pass | Pass |
| 17 | T SW APARTMENT | RunPeriod: RUNPERIOD 1 | 3.4611674724E-007 | 1.4752931010E-006 | Pass | Pass | 2.6750000303E-002 | 2.2583998909E-002 | Pass | Pass |
| 18 | T NW APARTMENT | RunPeriod: RUNPERIOD 1 | 4.7344859944E-007 | 2.3754256475E-006 | Pass | Pass | 1.5415600752E-002 | 1.0670532628E-002 | Pass | Pass |
| 19 | T SE APARTMENT | RunPeriod: RUNPERIOD 1 | 3.2450865748E-007 | 1.3538362128E-006 | Pass | Pass | 3.0671442356E-002 | 2.7817645969E-002 | Pass | Pass |
| 20 | T NE APARTMENT | RunPeriod: RUNPERIOD 1 | 4.4052844254E-007 | 2.1421632828E-006 | Pass | Pass | 1.6037126250E-002 | 1.0439402255E-002 | Pass | Pass |
| 21 | T N1 APARTMENT | RunPeriod: RUNPERIOD 1 | 2.6997724498E-007 | 1.3507964388E-006 | Pass | Pass | 1.6244896422E-002 | 1.1136113213E-002 | Pass | Pass |
| 22 | T N2 APARTMENT | RunPeriod: RUNPERIOD 1 | 2.6925591677E-007 | 1.3461082463E-006 | Pass | Pass | 1.6328321018E-002 | 1.1166139083E-002 | Pass | Pass |
| 23 | T S1 APARTMENT | RunPeriod: RUNPERIOD 1 | 1.6664872689E-007 | 7.1500785946E-007 | Pass | Pass | 0.1761056561 | 1.2198030993 | Pass | Pass |
| 24 | T S2 APARTMENT | RunPeriod: RUNPERIOD 1 | 1.6614401825E-007 | 7.1282059596E-007 | Pass | Pass | 9.9654141582E-002 | 0.3272005143 | Pass | Pass |
| 25 | T CORRIDOR | RunPeriod: RUNPERIOD 1 | 1.7793089326E-002 | 1.2041280746E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
| 26 | G CORRIDOR | RunPeriod: RUNPERIOD 1 | 0.2504013632 | 0.8207909285 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
| 27 | M CORRIDOR | RunPeriod: RUNPERIOD 1 | 9.3094971497E-003 | 5.9048367966E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 09:15:04
Heat Emission by Components| Envelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
| Heat Emissions [GJ] | 1918.89 | 145.32 | 0.00 | 13.96 | 725.83 | 2803.99 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 09:15:04
SizingPeriod:DesignDay| Maximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
| NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | -10.70 | 0.00 | -10.70 | Wetbulb [C] | 7.50 | 320.00 |
| NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 32.10 | 7.40 | 23.10 | Wetbulb [C] | 5.60 | 230.00 |
| Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
| Jan | 172.00 | 59 | |||
| Feb | 49.00 | 37 | |||
| Mar | 40.00 | 38 | |||
| Apr | 70.00 | 48 | |||
| May | 70.00 | 36 | |||
| Jun | 25.00 | 15 | |||
| Jul | 64.00 | 20 | |||
| Aug | 2.00 | 4 | |||
| Sep | 73.00 | 32 | |||
| Oct | 7.00 | 8 | |||
| Nov | 88.00 | 34 | |||
| Dec | 62.00 | 39 |
| Value | |
| None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 09:15:04
Opaque Exterior| Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
| G SWALL SWA | RES_EXT_WALL_GRD | 0.30 | 0.676 | 0.752 | 35.30 | 28.24 | 180.00 | 90.00 | S |
| G WWALL SWA | RES_EXT_WALL_GRD | 0.30 | 0.676 | 0.752 | 23.22 | 18.58 | 270.00 | 90.00 | W |
| G GFLOOR SWA | GGFLOORSWA_FFACTOR | 1.00 | 0.203 | 0.210 | 88.25 | 88.25 | 90.00 | 180.00 | |
| G NWALL NWA | RES_EXT_WALL_GRD | 0.30 | 0.676 | 0.752 | 35.30 | 28.24 | 0.00 | 90.00 | N |
| G WWALL NWA | RES_EXT_WALL_GRD | 0.30 | 0.676 | 0.752 | 23.22 | 18.58 | 270.00 | 90.00 | W |
| G GFLOOR NWA | GGFLOORNWA_FFACTOR | 1.00 | 0.203 | 0.210 | 88.25 | 88.25 | 90.00 | 180.00 | |
| G SWALL SEA | NONRES_EXT_WALL_GRD | 0.30 | 0.676 | 0.752 | 35.30 | 28.24 | 180.00 | 90.00 | S |
| G EWALL SEA | NONRES_EXT_WALL_GRD | 0.30 | 0.676 | 0.752 | 23.22 | 18.58 | 90.00 | 90.00 | E |
| G GFLOOR SEA | GGFLOORSEA_FFACTOR | 1.00 | 0.203 | 0.210 | 88.25 | 88.25 | 90.00 | 180.00 | |
| G NWALL NEA | RES_EXT_WALL_GRD | 0.30 | 0.676 | 0.752 | 35.30 | 28.24 | 0.00 | 90.00 | N |
| G EWALL NEA | RES_EXT_WALL_GRD | 0.30 | 0.676 | 0.752 | 23.22 | 18.58 | 90.00 | 90.00 | E |
| G GFLOOR NEA | GGFLOORNEA_FFACTOR | 1.00 | 0.203 | 0.210 | 88.25 | 88.25 | 90.00 | 180.00 | |
| G NWALL N1A | RES_EXT_WALL_GRD | 0.30 | 0.676 | 0.752 | 35.30 | 28.24 | 0.00 | 90.00 | N |
| G GFLOOR N1A | GGFLOORN1A_FFACTOR | 1.00 | 0.123 | 0.125 | 88.25 | 88.25 | 90.00 | 180.00 | |
| G NWALL N2A | RES_EXT_WALL_GRD | 0.30 | 0.676 | 0.752 | 35.30 | 28.24 | 0.00 | 90.00 | N |
| G GFLOOR N2A | GGFLOORN2A_FFACTOR | 1.00 | 0.123 | 0.125 | 88.25 | 88.25 | 90.00 | 180.00 | |
| G SWALL S1A | RES_EXT_WALL_GRD | 0.30 | 0.676 | 0.752 | 35.30 | 28.24 | 180.00 | 90.00 | S |
| G GFLOOR S1A | GGFLOORS1A_FFACTOR | 1.00 | 0.123 | 0.125 | 88.25 | 88.25 | 90.00 | 180.00 | |
| G SWALL S2A | RES_EXT_WALL_GRD | 0.30 | 0.676 | 0.752 | 35.30 | 28.24 | 180.00 | 90.00 | S |
| G GFLOOR S2A | GGFLOORS2A_FFACTOR | 1.00 | 0.123 | 0.125 | 88.25 | 88.25 | 90.00 | 180.00 | |
| M WWALL SWA | RES_EXT_WALL_MID | 0.30 | 0.683 | 0.761 | 46.45 | 37.16 | 270.00 | 90.00 | W |
| M SWALL SWA | RES_EXT_WALL_MID | 0.30 | 0.683 | 0.761 | 70.60 | 56.48 | 180.00 | 90.00 | S |
| M NWALL NWA | RES_EXT_WALL_MID | 0.30 | 0.683 | 0.761 | 70.60 | 56.48 | 0.00 | 90.00 | N |
| M WWALL NWA | RES_EXT_WALL_MID | 0.30 | 0.683 | 0.761 | 46.45 | 37.16 | 270.00 | 90.00 | W |
| M EWALL SEA | RES_EXT_WALL_MID | 0.30 | 0.683 | 0.761 | 46.45 | 37.16 | 90.00 | 90.00 | E |
| M SWALL SEA | RES_EXT_WALL_MID | 0.30 | 0.683 | 0.761 | 70.60 | 56.48 | 180.00 | 90.00 | S |
| M NWALL NEA | RES_EXT_WALL_MID | 0.30 | 0.683 | 0.761 | 70.60 | 56.48 | 0.00 | 90.00 | N |
| M EWALL NEA | RES_EXT_WALL_MID | 0.30 | 0.683 | 0.761 | 46.45 | 37.16 | 90.00 | 90.00 | E |
| M NWALL N1A | RES_EXT_WALL_MID | 0.30 | 0.683 | 0.761 | 70.60 | 56.48 | 0.00 | 90.00 | N |
| M NWALL N2A | RES_EXT_WALL_MID | 0.30 | 0.683 | 0.761 | 70.60 | 56.48 | 0.00 | 90.00 | N |
| M SWALL S1A | RES_EXT_WALL_MID | 0.30 | 0.683 | 0.761 | 70.60 | 56.48 | 180.00 | 90.00 | S |
| M SWALL S2A | RES_EXT_WALL_MID | 0.30 | 0.683 | 0.761 | 70.60 | 56.48 | 180.00 | 90.00 | S |
| T WWALL SWA | RES_EXT_WALL_TOP | 0.30 | 0.943 | 1.098 | 23.22 | 18.58 | 270.00 | 90.00 | W |
| T SWALL SWA | RES_EXT_WALL_TOP | 0.30 | 0.943 | 1.098 | 35.30 | 28.24 | 180.00 | 90.00 | S |
| T ROOF SWA | RES_ROOF | 0.30 | 0.221 | 0.228 | 88.25 | 88.25 | 180.00 | 0.00 | |
| T NWALL NWA | RES_EXT_WALL_TOP | 0.30 | 0.943 | 1.098 | 35.30 | 28.24 | 0.00 | 90.00 | N |
| T WWALL NWA | RES_EXT_WALL_TOP | 0.30 | 0.943 | 1.098 | 23.22 | 18.58 | 270.00 | 90.00 | W |
| T ROOF NWA | RES_ROOF | 0.30 | 0.221 | 0.228 | 88.25 | 88.25 | 180.00 | 0.00 | |
| T EWALL SEA | RES_EXT_WALL_TOP | 0.30 | 0.943 | 1.098 | 23.22 | 18.58 | 90.00 | 90.00 | E |
| T SWALL SEA | RES_EXT_WALL_TOP | 0.30 | 0.943 | 1.098 | 35.30 | 28.24 | 180.00 | 90.00 | S |
| T ROOF SEA | RES_ROOF | 0.30 | 0.221 | 0.228 | 88.25 | 88.25 | 180.00 | 0.00 | |
| T NWALL NEA | RES_EXT_WALL_TOP | 0.30 | 0.943 | 1.098 | 35.30 | 28.24 | 0.00 | 90.00 | N |
| T EWALL NEA | RES_EXT_WALL_TOP | 0.30 | 0.943 | 1.098 | 23.22 | 18.58 | 90.00 | 90.00 | E |
| T ROOF NEA | RES_ROOF | 0.30 | 0.221 | 0.228 | 88.25 | 88.25 | 180.00 | 0.00 | |
| T NWALL N1A | RES_EXT_WALL_TOP | 0.30 | 0.943 | 1.098 | 35.30 | 28.24 | 0.00 | 90.00 | N |
| T ROOF N1A | RES_ROOF | 0.30 | 0.221 | 0.228 | 88.25 | 88.25 | 180.00 | 0.00 | |
| T NWALL N2A | RES_EXT_WALL_TOP | 0.30 | 0.943 | 1.098 | 35.30 | 28.24 | 0.00 | 90.00 | N |
| T ROOF N2A | RES_ROOF | 0.30 | 0.221 | 0.228 | 88.25 | 88.25 | 180.00 | 0.00 | |
| T SWALL S1A | RES_EXT_WALL_TOP | 0.30 | 0.943 | 1.098 | 35.30 | 28.24 | 180.00 | 90.00 | S |
| T ROOF S1A | RES_ROOF | 0.30 | 0.221 | 0.228 | 88.25 | 88.25 | 180.00 | 0.00 | |
| T SWALL S2A | RES_EXT_WALL_TOP | 0.30 | 0.943 | 1.098 | 35.30 | 28.24 | 180.00 | 90.00 | S |
| T ROOF S2A | RES_ROOF | 0.30 | 0.221 | 0.228 | 88.25 | 88.25 | 180.00 | 0.00 | |
| T WWALL C | NONRES_EXT_WALL_TOP | 0.30 | 0.943 | 1.098 | 5.11 | 5.11 | 270.00 | 90.00 | W |
| T EWALL C | NONRES_EXT_WALL_TOP | 0.30 | 0.943 | 1.098 | 5.11 | 3.99 | 90.00 | 90.00 | E |
| T ROOF C | NONRES_ROOF | 0.30 | 0.221 | 0.228 | 77.66 | 77.66 | 180.00 | 0.00 | |
| G WWALL C | NONRES_EXT_WALL_GRD | 0.30 | 0.676 | 0.752 | 5.11 | 5.11 | 270.00 | 90.00 | W |
| G EWALL C | NONRES_EXT_WALL_GRD | 0.30 | 0.676 | 0.752 | 5.11 | 1.79 | 90.00 | 90.00 | E |
| G FLOOR C | GFLOORC_FFACTOR | 1.00 | 0.040 | 0.041 | 77.66 | 77.66 | 90.00 | 180.00 | |
| M WWALL C | NONRES_EXT_WALL_MID | 0.30 | 0.683 | 0.761 | 10.22 | 10.22 | 270.00 | 90.00 | W |
| M EWALL C | NONRES_EXT_WALL_MID | 0.30 | 0.683 | 0.761 | 10.22 | 7.99 | 90.00 | 90.00 | E |
| Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
| G NIWALL SWA | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 0.00 | 90.00 | N |
| G EIWALL SWA | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 90.00 | 90.00 | E |
| G CEILIN SWA | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 88.25 | 88.25 | 180.00 | 0.00 | |
| G SIWALL NWA | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 180.00 | 90.00 | S |
| G EIWALL NWA | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 90.00 | 90.00 | E |
| G CEILIN NWA | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 88.25 | 88.25 | 180.00 | 0.00 | |
| G NIWALL SEA | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 0.00 | 90.00 | N |
| iz-G EIWALL S2A | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 270.00 | 90.00 | W |
| G CEILIN SEA | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 88.25 | 88.25 | 180.00 | 0.00 | |
| G SIWALL NEA | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 180.00 | 90.00 | S |
| iz-G EIWALL N2A | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 270.00 | 90.00 | W |
| G CEILIN NEA | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 88.25 | 88.25 | 180.00 | 0.00 | |
| G SIWALL N1A | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 180.00 | 90.00 | S |
| G EIWALL N1A | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 90.00 | 90.00 | E |
| iz-G EIWALL NWA | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 270.00 | 90.00 | W |
| G CEILIN N1A | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 88.25 | 88.25 | 180.00 | 0.00 | |
| G SIWALL N2A | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 180.00 | 90.00 | S |
| G EIWALL N2A | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 90.00 | 90.00 | E |
| iz-G EIWALL N1A | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 270.00 | 90.00 | W |
| G CEILIN N2A | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 88.25 | 88.25 | 180.00 | 0.00 | |
| G NIWALL S1A | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 0.00 | 90.00 | N |
| G EIWALL S1A | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 90.00 | 90.00 | E |
| iz-G EIWALL SWA | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 270.00 | 90.00 | W |
| G CEILIN S1A | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 88.25 | 88.25 | 180.00 | 0.00 | |
| G NIWALL S2A | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 0.00 | 90.00 | N |
| G EIWALL S2A | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 90.00 | 90.00 | E |
| iz-G EIWALL S1A | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 270.00 | 90.00 | W |
| G CEILIN S2A | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 88.25 | 88.25 | 180.00 | 0.00 | |
| M NIWALL SWA | INT_WALL | 0.30 | 2.511 | 6.299 | 70.60 | 70.60 | 0.00 | 90.00 | N |
| M EIWALL SWA | INT_WALL | 0.30 | 2.511 | 6.299 | 46.45 | 46.45 | 90.00 | 90.00 | E |
| M GFLOOR SWA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 176.50 | 176.50 | 90.00 | 180.00 | |
| M CEILIN SWA | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 176.50 | 176.50 | 180.00 | 0.00 | |
| M SIWALL NWA | INT_WALL | 0.30 | 2.511 | 6.299 | 70.60 | 70.60 | 180.00 | 90.00 | S |
| M EIWALL NWA | INT_WALL | 0.30 | 2.511 | 6.299 | 46.45 | 46.45 | 90.00 | 90.00 | E |
| M GFLOOR NWA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 176.50 | 176.50 | 90.00 | 180.00 | |
| M CEILIN NWA | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 176.50 | 176.50 | 180.00 | 0.00 | |
| M NIWALL SEA | INT_WALL | 0.30 | 2.511 | 6.299 | 70.60 | 70.60 | 0.00 | 90.00 | N |
| iz-M EIWALL S2A | INT_WALL | 0.30 | 2.511 | 6.299 | 46.45 | 46.45 | 270.00 | 90.00 | W |
| M GFLOOR SEA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 176.50 | 176.50 | 90.00 | 180.00 | |
| M CEILIN SEA | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 176.50 | 176.50 | 180.00 | 0.00 | |
| M SIWALL NEA | INT_WALL | 0.30 | 2.511 | 6.299 | 70.60 | 70.60 | 180.00 | 90.00 | S |
| iz-M EIWALL N2A | INT_WALL | 0.30 | 2.511 | 6.299 | 46.45 | 46.45 | 270.00 | 90.00 | W |
| M GFLOOR NEA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 176.50 | 176.50 | 90.00 | 180.00 | |
| M CEILIN NEA | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 176.50 | 176.50 | 180.00 | 0.00 | |
| M SIWALL N1A | INT_WALL | 0.30 | 2.511 | 6.299 | 70.60 | 70.60 | 180.00 | 90.00 | S |
| M EIWALL N1A | INT_WALL | 0.30 | 2.511 | 6.299 | 46.45 | 46.45 | 90.00 | 90.00 | E |
| iz-M EIWALL NWA | INT_WALL | 0.30 | 2.511 | 6.299 | 46.45 | 46.45 | 270.00 | 90.00 | W |
| M GFLOOR N1A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 176.50 | 176.50 | 90.00 | 180.00 | |
| M CEILIN N1A | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 176.50 | 176.50 | 180.00 | 0.00 | |
| M SIWALL N2A | INT_WALL | 0.30 | 2.511 | 6.299 | 70.60 | 70.60 | 180.00 | 90.00 | S |
| M EIWALL N2A | INT_WALL | 0.30 | 2.511 | 6.299 | 46.45 | 46.45 | 90.00 | 90.00 | E |
| iz-M EIWALL N1A | INT_WALL | 0.30 | 2.511 | 6.299 | 46.45 | 46.45 | 270.00 | 90.00 | W |
| M GFLOOR N2A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 176.50 | 176.50 | 90.00 | 180.00 | |
| M CEILIN N2A | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 176.50 | 176.50 | 180.00 | 0.00 | |
| M NIWALL S1A | INT_WALL | 0.30 | 2.511 | 6.299 | 70.60 | 70.60 | 0.00 | 90.00 | N |
| M EIWALL S1A | INT_WALL | 0.30 | 2.511 | 6.299 | 46.45 | 46.45 | 90.00 | 90.00 | E |
| iz-M EIWALL SWA | INT_WALL | 0.30 | 2.511 | 6.299 | 46.45 | 46.45 | 270.00 | 90.00 | W |
| M GFLOOR S1A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 176.50 | 176.50 | 90.00 | 180.00 | |
| M CEILIN S1A | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 176.50 | 176.50 | 180.00 | 0.00 | |
| M NIWALL S2A | INT_WALL | 0.30 | 2.511 | 6.299 | 70.60 | 70.60 | 0.00 | 90.00 | N |
| M EIWALL S2A | INT_WALL | 0.30 | 2.511 | 6.299 | 46.45 | 46.45 | 90.00 | 90.00 | E |
| iz-M EIWALL S1A | INT_WALL | 0.30 | 2.511 | 6.299 | 46.45 | 46.45 | 270.00 | 90.00 | W |
| M GFLOOR S2A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 176.50 | 176.50 | 90.00 | 180.00 | |
| M CEILIN S2A | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 176.50 | 176.50 | 180.00 | 0.00 | |
| T NIWALL SWA | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 0.00 | 90.00 | N |
| T EIWALL SWA | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 90.00 | 90.00 | E |
| T GFLOOR SWA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 88.25 | 88.25 | 90.00 | 180.00 | |
| T SIWALL NWA | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 180.00 | 90.00 | S |
| T EIWALL NWA | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 90.00 | 90.00 | E |
| T GFLOOR NWA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 88.25 | 88.25 | 90.00 | 180.00 | |
| T NIWALL SEA | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 0.00 | 90.00 | N |
| iz-T EIWALL S2A | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 270.00 | 90.00 | W |
| T GFLOOR SEA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 88.25 | 88.25 | 90.00 | 180.00 | |
| T SIWALL NEA | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 180.00 | 90.00 | S |
| iz-T EIWALL N2A | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 270.00 | 90.00 | W |
| T GFLOOR NEA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 88.25 | 88.25 | 90.00 | 180.00 | |
| T SIWALL N1A | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 180.00 | 90.00 | S |
| T EIWALL N1A | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 90.00 | 90.00 | E |
| iz-T EIWALL NWA | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 270.00 | 90.00 | W |
| T GFLOOR N1A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 88.25 | 88.25 | 90.00 | 180.00 | |
| T SIWALL N2A | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 180.00 | 90.00 | S |
| T EIWALL N2A | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 90.00 | 90.00 | E |
| iz-T EIWALL N1A | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 270.00 | 90.00 | W |
| T GFLOOR N2A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 88.25 | 88.25 | 90.00 | 180.00 | |
| T NIWALL S1A | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 0.00 | 90.00 | N |
| T EIWALL S1A | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 90.00 | 90.00 | E |
| iz-T EIWALL SWA | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 270.00 | 90.00 | W |
| T GFLOOR S1A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 88.25 | 88.25 | 90.00 | 180.00 | |
| T NIWALL S2A | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 0.00 | 90.00 | N |
| T EIWALL S2A | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 90.00 | 90.00 | E |
| iz-T EIWALL S1A | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 270.00 | 90.00 | W |
| T GFLOOR S2A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 88.25 | 88.25 | 90.00 | 180.00 | |
| iz-T NIWALL SWA | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 180.00 | 90.00 | S |
| iz-T NIWALL S1A | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 180.00 | 90.00 | S |
| iz-T NIWALL S2A | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 180.00 | 90.00 | S |
| iz-T NIWALL SEA | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 180.00 | 90.00 | S |
| iz-T SIWALL NWA | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 0.00 | 90.00 | N |
| iz-T SIWALL N1A | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 0.00 | 90.00 | N |
| iz-T SIWALL N2A | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 0.00 | 90.00 | N |
| iz-T SIWALL NEA | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 0.00 | 90.00 | N |
| T FLOOR C | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 77.66 | 77.66 | 90.00 | 180.00 | |
| iz-G NIWALL SWA | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 180.00 | 90.00 | S |
| iz-G NIWALL S1A | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 180.00 | 90.00 | S |
| iz-G NIWALL S2A | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 180.00 | 90.00 | S |
| iz-G NIWALL SEA | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 180.00 | 90.00 | S |
| iz-G SIWALL NWA | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 0.00 | 90.00 | N |
| iz-G SIWALL N1A | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 0.00 | 90.00 | N |
| iz-G SIWALL N2A | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 0.00 | 90.00 | N |
| iz-G SIWALL NEA | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 0.00 | 90.00 | N |
| G CEILING C | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 77.66 | 77.66 | 180.00 | 0.00 | |
| iz-M NIWALL SWA | INT_WALL | 0.30 | 2.511 | 6.299 | 70.60 | 70.60 | 180.00 | 90.00 | S |
| iz-M NIWALL S1A | INT_WALL | 0.30 | 2.511 | 6.299 | 70.60 | 70.60 | 180.00 | 90.00 | S |
| iz-M NIWALL S2A | INT_WALL | 0.30 | 2.511 | 6.299 | 70.60 | 70.60 | 180.00 | 90.00 | S |
| iz-M NIWALL SEA | INT_WALL | 0.30 | 2.511 | 6.299 | 70.60 | 70.60 | 180.00 | 90.00 | S |
| iz-M SIWALL NWA | INT_WALL | 0.30 | 2.511 | 6.299 | 70.60 | 70.60 | 0.00 | 90.00 | N |
| iz-M SIWALL N1A | INT_WALL | 0.30 | 2.511 | 6.299 | 70.60 | 70.60 | 0.00 | 90.00 | N |
| iz-M SIWALL N2A | INT_WALL | 0.30 | 2.511 | 6.299 | 70.60 | 70.60 | 0.00 | 90.00 | N |
| iz-M SIWALL NEA | INT_WALL | 0.30 | 2.511 | 6.299 | 70.60 | 70.60 | 0.00 | 90.00 | N |
| M FLOOR C | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 155.32 | 155.32 | 90.00 | 180.00 | |
| M CEILING C | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 155.32 | 155.32 | 180.00 | 0.00 | |
| G INTERNALMASS SWA | INTERIORFURNISHINGS | 0.30 | 0.800 | 88.25 | 0.00 | 90.00 | N | ||
| G INTERNALMASS NWA | INTERIORFURNISHINGS | 0.30 | 0.800 | 88.25 | 0.00 | 90.00 | N | ||
| G INTERNALMASS SEA | INTERIORFURNISHINGS | 0.30 | 0.800 | 88.25 | 0.00 | 90.00 | N | ||
| G INTERNALMASS NEA | INTERIORFURNISHINGS | 0.30 | 0.800 | 88.25 | 0.00 | 90.00 | N | ||
| G INTERNALMASS N1A | INTERIORFURNISHINGS | 0.30 | 0.800 | 88.25 | 0.00 | 90.00 | N | ||
| G INTERNALMASS N2A | INTERIORFURNISHINGS | 0.30 | 0.800 | 88.25 | 0.00 | 90.00 | N | ||
| G INTERNALMASS S1A | INTERIORFURNISHINGS | 0.30 | 0.800 | 88.25 | 0.00 | 90.00 | N | ||
| G INTERNALMASS S2A | INTERIORFURNISHINGS | 0.30 | 0.800 | 88.25 | 0.00 | 90.00 | N | ||
| M INTERNALMASS SWA | INTERIORFURNISHINGS | 0.30 | 0.800 | 353.00 | 0.00 | 90.00 | N | ||
| M INTERNALMASS NWA | INTERIORFURNISHINGS | 0.30 | 0.800 | 353.00 | 0.00 | 90.00 | N | ||
| M INTERNALMASS SEA | INTERIORFURNISHINGS | 0.30 | 0.800 | 353.00 | 0.00 | 90.00 | N | ||
| M INTERNALMASS NEA | INTERIORFURNISHINGS | 0.30 | 0.800 | 353.00 | 0.00 | 90.00 | N | ||
| M INTERNALMASS N1A | INTERIORFURNISHINGS | 0.30 | 0.800 | 353.00 | 0.00 | 90.00 | N | ||
| M INTERNALMASS N2A | INTERIORFURNISHINGS | 0.30 | 0.800 | 353.00 | 0.00 | 90.00 | N | ||
| M INTERNALMASS S1A | INTERIORFURNISHINGS | 0.30 | 0.800 | 353.00 | 0.00 | 90.00 | N | ||
| M INTERNALMASS S2A | INTERIORFURNISHINGS | 0.30 | 0.800 | 353.00 | 0.00 | 90.00 | N | ||
| T INTERNALMASS SWA | INTERIORFURNISHINGS | 0.30 | 0.800 | 88.25 | 0.00 | 90.00 | N | ||
| T INTERNALMASS NWA | INTERIORFURNISHINGS | 0.30 | 0.800 | 88.25 | 0.00 | 90.00 | N | ||
| T INTERNALMASS SEA | INTERIORFURNISHINGS | 0.30 | 0.800 | 88.25 | 0.00 | 90.00 | N | ||
| T INTERNALMASS NEA | INTERIORFURNISHINGS | 0.30 | 0.800 | 88.25 | 0.00 | 90.00 | N | ||
| T INTERNALMASS N1A | INTERIORFURNISHINGS | 0.30 | 0.800 | 88.25 | 0.00 | 90.00 | N | ||
| T INTERNALMASS N2A | INTERIORFURNISHINGS | 0.30 | 0.800 | 88.25 | 0.00 | 90.00 | N | ||
| T INTERNALMASS S1A | INTERIORFURNISHINGS | 0.30 | 0.800 | 88.25 | 0.00 | 90.00 | N | ||
| T INTERNALMASS S2A | INTERIORFURNISHINGS | 0.30 | 0.800 | 88.25 | 0.00 | 90.00 | N |
| Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
| GWINDOW1 S SWA | RESWINDOW_U_0.3972_SHGC_0.4 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.257 | 0.401 | 0.402 | No | G SWALL SWA | 180.00 | 90.00 | S | |||||||
| GWINDOW1 W SWA | RESWINDOW_U_0.3972_SHGC_0.4 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 2.257 | 0.401 | 0.402 | No | G WWALL SWA | 270.00 | 90.00 | W | |||||||
| GWINDOW1 N NWA | RESWINDOW_U_0.3972_SHGC_0.4 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.257 | 0.401 | 0.402 | No | G NWALL NWA | 0.00 | 90.00 | N | |||||||
| GWINDOW1 W NWA | RESWINDOW_U_0.3972_SHGC_0.4 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 2.257 | 0.401 | 0.402 | No | G WWALL NWA | 270.00 | 90.00 | W | |||||||
| GWINDOW1 S SEA | NONRESWINDOW_U_0.3972_SHGC_0.4 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.257 | 0.401 | 0.402 | No | G SWALL SEA | 180.00 | 90.00 | S | |||||||
| GWINDOW1 E SEA | NONRESWINDOW_U_0.3972_SHGC_0.4 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 2.257 | 0.401 | 0.402 | No | G EWALL SEA | 90.00 | 90.00 | E | |||||||
| GWINDOW1 N NEA | RESWINDOW_U_0.3972_SHGC_0.4 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.257 | 0.401 | 0.402 | No | G NWALL NEA | 0.00 | 90.00 | N | |||||||
| GWINDOW1 E NEA | RESWINDOW_U_0.3972_SHGC_0.4 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 2.257 | 0.401 | 0.402 | No | G EWALL NEA | 90.00 | 90.00 | E | |||||||
| GWINDOW1 N N1A | RESWINDOW_U_0.3972_SHGC_0.4 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.257 | 0.401 | 0.402 | No | G NWALL N1A | 0.00 | 90.00 | N | |||||||
| GWINDOW1 N N2A | RESWINDOW_U_0.3972_SHGC_0.4 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.257 | 0.401 | 0.402 | No | G NWALL N2A | 0.00 | 90.00 | N | |||||||
| GWINDOW1 S S1A | RESWINDOW_U_0.3972_SHGC_0.4 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.257 | 0.401 | 0.402 | No | G SWALL S1A | 180.00 | 90.00 | S | |||||||
| GWINDOW1 S S2A | RESWINDOW_U_0.3972_SHGC_0.4 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.257 | 0.401 | 0.402 | No | G SWALL S2A | 180.00 | 90.00 | S | |||||||
| MWINDOW1 W SWA | RESWINDOW_U_0.3972_SHGC_0.4 | 4.65 | 0.00 | 0.00 | 4.65 | 9.29 | 2.257 | 0.401 | 0.402 | No | M WWALL SWA | 270.00 | 90.00 | W | |||||||
| MWINDOW1 S SWA | RESWINDOW_U_0.3972_SHGC_0.4 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 2.257 | 0.401 | 0.402 | No | M SWALL SWA | 180.00 | 90.00 | S | |||||||
| MWINDOW1 N NWA | RESWINDOW_U_0.3972_SHGC_0.4 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 2.257 | 0.401 | 0.402 | No | M NWALL NWA | 0.00 | 90.00 | N | |||||||
| MWINDOW1 W NWA | RESWINDOW_U_0.3972_SHGC_0.4 | 4.65 | 0.00 | 0.00 | 4.65 | 9.29 | 2.257 | 0.401 | 0.402 | No | M WWALL NWA | 270.00 | 90.00 | W | |||||||
| MWINDOW1 E SEA | RESWINDOW_U_0.3972_SHGC_0.4 | 4.65 | 0.00 | 0.00 | 4.65 | 9.29 | 2.257 | 0.401 | 0.402 | No | M EWALL SEA | 90.00 | 90.00 | E | |||||||
| MWINDOW1 S SEA | RESWINDOW_U_0.3972_SHGC_0.4 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 2.257 | 0.401 | 0.402 | No | M SWALL SEA | 180.00 | 90.00 | S | |||||||
| MWINDOW1 N NEA | RESWINDOW_U_0.3972_SHGC_0.4 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 2.257 | 0.401 | 0.402 | No | M NWALL NEA | 0.00 | 90.00 | N | |||||||
| MWINDOW1 E NEA | RESWINDOW_U_0.3972_SHGC_0.4 | 4.65 | 0.00 | 0.00 | 4.65 | 9.29 | 2.257 | 0.401 | 0.402 | No | M EWALL NEA | 90.00 | 90.00 | E | |||||||
| MWINDOW1 N N1A | RESWINDOW_U_0.3972_SHGC_0.4 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 2.257 | 0.401 | 0.402 | No | M NWALL N1A | 0.00 | 90.00 | N | |||||||
| MWINDOW1 N N2A | RESWINDOW_U_0.3972_SHGC_0.4 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 2.257 | 0.401 | 0.402 | No | M NWALL N2A | 0.00 | 90.00 | N | |||||||
| MWINDOW1 S S1A | RESWINDOW_U_0.3972_SHGC_0.4 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 2.257 | 0.401 | 0.402 | No | M SWALL S1A | 180.00 | 90.00 | S | |||||||
| MWINDOW1 S S2A | RESWINDOW_U_0.3972_SHGC_0.4 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 2.257 | 0.401 | 0.402 | No | M SWALL S2A | 180.00 | 90.00 | S | |||||||
| TWINDOW1 W SWA | RESWINDOW_U_0.3972_SHGC_0.4 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 2.257 | 0.401 | 0.402 | No | T WWALL SWA | 270.00 | 90.00 | W | |||||||
| TWINDOW1 S SWA | RESWINDOW_U_0.3972_SHGC_0.4 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.257 | 0.401 | 0.402 | No | T SWALL SWA | 180.00 | 90.00 | S | |||||||
| TWINDOW1 N NWA | RESWINDOW_U_0.3972_SHGC_0.4 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.257 | 0.401 | 0.402 | No | T NWALL NWA | 0.00 | 90.00 | N | |||||||
| TWINDOW1 W NWA | RESWINDOW_U_0.3972_SHGC_0.4 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 2.257 | 0.401 | 0.402 | No | T WWALL NWA | 270.00 | 90.00 | W | |||||||
| TWINDOW1 E SEA | RESWINDOW_U_0.3972_SHGC_0.4 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 2.257 | 0.401 | 0.402 | No | T EWALL SEA | 90.00 | 90.00 | E | |||||||
| TWINDOW1 S SEA | RESWINDOW_U_0.3972_SHGC_0.4 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.257 | 0.401 | 0.402 | No | T SWALL SEA | 180.00 | 90.00 | S | |||||||
| TWINDOW1 N NEA | RESWINDOW_U_0.3972_SHGC_0.4 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.257 | 0.401 | 0.402 | No | T NWALL NEA | 0.00 | 90.00 | N | |||||||
| TWINDOW1 E NEA | RESWINDOW_U_0.3972_SHGC_0.4 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 2.257 | 0.401 | 0.402 | No | T EWALL NEA | 90.00 | 90.00 | E | |||||||
| TWINDOW1 N N1A | RESWINDOW_U_0.3972_SHGC_0.4 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.257 | 0.401 | 0.402 | No | T NWALL N1A | 0.00 | 90.00 | N | |||||||
| TWINDOW1 N N2A | RESWINDOW_U_0.3972_SHGC_0.4 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.257 | 0.401 | 0.402 | No | T NWALL N2A | 0.00 | 90.00 | N | |||||||
| TWINDOW1 S S1A | RESWINDOW_U_0.3972_SHGC_0.4 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.257 | 0.401 | 0.402 | No | T SWALL S1A | 180.00 | 90.00 | S | |||||||
| TWINDOW1 S S2A | RESWINDOW_U_0.3972_SHGC_0.4 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.257 | 0.401 | 0.402 | No | T SWALL S2A | 180.00 | 90.00 | S | |||||||
| TWINDOW14 | NONRESWINDOW_U_0.3972_SHGC_0.4 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.257 | 0.401 | 0.402 | No | T EWALL C | 90.00 | 90.00 | E | |||||||
| ENTRANCE DOOR | NONRESWINDOW_U_0.3972_SHGC_0.4 | 3.32 | 0.00 | 0.00 | 3.32 | 3.32 | 2.257 | 0.401 | 0.402 | No | G EWALL C | 90.00 | 90.00 | E | |||||||
| MWINDOW14 | NONRESWINDOW_U_0.3972_SHGC_0.4 | 1.11 | 0.00 | 0.00 | 1.11 | 2.23 | 2.257 | 0.401 | 0.402 | No | M EWALL C | 90.00 | 90.00 | E | |||||||
| Total or Average | 306.92 | 2.257 | 0.401 | 0.402 | |||||||||||||||||
| North Total or Average | 112.97 | 2.257 | 0.401 | 0.402 | |||||||||||||||||
| Non-North Total or Average | 193.95 | 2.257 | 0.401 | 0.402 |
| Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
| None |
| Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
| Total or Average | 0.00 | - | - | - |
| Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
| None |
| Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
| None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 09:15:04
Sunlit Fraction| March 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
| GWINDOW1 S SWA | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| GWINDOW1 W SWA | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
| GWINDOW1 N NWA | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| GWINDOW1 W NWA | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
| GWINDOW1 S SEA | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| GWINDOW1 E SEA | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
| GWINDOW1 N NEA | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| GWINDOW1 E NEA | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
| GWINDOW1 N N1A | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| GWINDOW1 N N2A | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| GWINDOW1 S S1A | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| GWINDOW1 S S2A | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| MWINDOW1 W SWA | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
| MWINDOW1 S SWA | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| MWINDOW1 N NWA | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| MWINDOW1 W NWA | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
| MWINDOW1 E SEA | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
| MWINDOW1 S SEA | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| MWINDOW1 N NEA | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| MWINDOW1 E NEA | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
| MWINDOW1 N N1A | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| MWINDOW1 N N2A | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| MWINDOW1 S S1A | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| MWINDOW1 S S2A | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| TWINDOW1 W SWA | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
| TWINDOW1 S SWA | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| TWINDOW1 N NWA | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| TWINDOW1 W NWA | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
| TWINDOW1 E SEA | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
| TWINDOW1 S SEA | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| TWINDOW1 N NEA | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| TWINDOW1 E NEA | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
| TWINDOW1 N N1A | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| TWINDOW1 N N2A | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| TWINDOW1 S S1A | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| TWINDOW1 S S2A | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| TWINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
| ENTRANCE DOOR | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
| MWINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
| Name | Type | Shaded Construction | Control | Glare Control | |
| None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 09:15:04
Interior Lighting| Zone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
| LIGHTING_HARDWIRED_GSW | G SW APARTMENT | G SW APARTMENT | GENERAL | 7.8684 | 88.25 | 694.38 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.32 |
| LIGHTING_HARDWIRED_GNW | G NW APARTMENT | G NW APARTMENT | GENERAL | 7.8684 | 88.25 | 694.38 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.32 |
| LIGHTING_HARDWIRED_OFFICE | OFFICE | OFFICE | GENERAL | 9.7532 | 88.25 | 860.71 | LightsWired | LTG_SCH_OFFICE | 46.69 | 168.00 | 45.77 | 0.0000 | Y | 7.40 |
| LIGHTING_HARDWIRED_GNE | G NE APARTMENT | G NE APARTMENT | GENERAL | 7.8684 | 88.25 | 694.38 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.32 |
| LIGHTING_HARDWIRED_GN1 | G N1 APARTMENT | G N1 APARTMENT | GENERAL | 7.8684 | 88.25 | 694.38 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.32 |
| LIGHTING_HARDWIRED_GN2 | G N2 APARTMENT | G N2 APARTMENT | GENERAL | 7.8684 | 88.25 | 694.38 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.32 |
| LIGHTING_HARDWIRED_GS1 | G S1 APARTMENT | G S1 APARTMENT | GENERAL | 7.8684 | 88.25 | 694.38 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.32 |
| LIGHTING_HARDWIRED_GS2 | G S2 APARTMENT | G S2 APARTMENT | GENERAL | 7.8684 | 88.25 | 694.38 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.32 |
| LIGHTING_HARDWIRED_MSW | M SW APARTMENT | M SW APARTMENT | GENERAL | 7.8684 | 176.50 | 1388.76 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 2.63 |
| LIGHTING_HARDWIRED_MNW | M NW APARTMENT | M NW APARTMENT | GENERAL | 7.8684 | 176.50 | 1388.76 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 2.63 |
| LIGHTING_HARDWIRED_MSE | M SE APARTMENT | M SE APARTMENT | GENERAL | 7.8684 | 176.50 | 1388.76 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 2.63 |
| LIGHTING_HARDWIRED_MNE | M NE APARTMENT | M NE APARTMENT | GENERAL | 7.8684 | 176.50 | 1388.76 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 2.63 |
| LIGHTING_HARDWIRED_MN1 | M N1 APARTMENT | M N1 APARTMENT | GENERAL | 7.8684 | 176.50 | 1388.76 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 2.63 |
| LIGHTING_HARDWIRED_MN2 | M N2 APARTMENT | M N2 APARTMENT | GENERAL | 7.8684 | 176.50 | 1388.76 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 2.63 |
| LIGHTING_HARDWIRED_MS1 | M S1 APARTMENT | M S1 APARTMENT | GENERAL | 7.8684 | 176.50 | 1388.76 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 2.63 |
| LIGHTING_HARDWIRED_MS2 | M S2 APARTMENT | M S2 APARTMENT | GENERAL | 7.8684 | 176.50 | 1388.76 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 2.63 |
| LIGHTING_HARDWIRED_TSW | T SW APARTMENT | T SW APARTMENT | GENERAL | 7.8684 | 88.25 | 694.38 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.32 |
| LIGHTING_HARDWIRED_TNW | T NW APARTMENT | T NW APARTMENT | GENERAL | 7.8684 | 88.25 | 694.38 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.32 |
| LIGHTING_HARDWIRED_TSE | T SE APARTMENT | T SE APARTMENT | GENERAL | 7.8684 | 88.25 | 694.38 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.32 |
| LIGHTING_HARDWIRED_TNE | T NE APARTMENT | T NE APARTMENT | GENERAL | 7.8684 | 88.25 | 694.38 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.32 |
| LIGHTING_HARDWIRED_TN1 | T N1 APARTMENT | T N1 APARTMENT | GENERAL | 7.8684 | 88.25 | 694.38 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.32 |
| LIGHTING_HARDWIRED_TN2 | T N2 APARTMENT | T N2 APARTMENT | GENERAL | 7.8684 | 88.25 | 694.38 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.32 |
| LIGHTING_HARDWIRED_TS1 | T S1 APARTMENT | T S1 APARTMENT | GENERAL | 7.8684 | 88.25 | 694.38 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.32 |
| LIGHTING_HARDWIRED_TS2 | T S2 APARTMENT | T S2 APARTMENT | GENERAL | 7.8684 | 88.25 | 694.38 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.32 |
| LIGHTING_HARDWIRED_GC | G CORRIDOR | G CORRIDOR | GENERAL | 4.7725 | 77.66 | 370.63 | LightsWired | LTG_SCH_CORRIDOR | 168.00 | 168.00 | 168.00 | 0.0000 | N | 11.69 |
| LIGHTING_HARDWIRED_MC | M CORRIDOR | M CORRIDOR | GENERAL | 4.7725 | 155.32 | 741.26 | LightsWired | LTG_SCH_CORRIDOR | 168.00 | 168.00 | 168.00 | 0.0000 | N | 23.38 |
| LIGHTING_HARDWIRED_TC | T CORRIDOR | T CORRIDOR | GENERAL | 4.7725 | 77.66 | 370.63 | LightsWired | LTG_SCH_CORRIDOR | 168.00 | 168.00 | 168.00 | 0.0000 | N | 11.69 |
| LIGHTING_PLUGIN_GSW | G SW APARTMENT | G SW APARTMENT | GENERAL | 0.8234 | 88.25 | 72.67 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.14 |
| LIGHTING_PLUGIN_GNW | G NW APARTMENT | G NW APARTMENT | GENERAL | 0.8234 | 88.25 | 72.67 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.14 |
| LIGHTING_PLUGIN_GNE | G NE APARTMENT | G NE APARTMENT | GENERAL | 0.8234 | 88.25 | 72.67 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.14 |
| LIGHTING_PLUGIN_GN1 | G N1 APARTMENT | G N1 APARTMENT | GENERAL | 0.8234 | 88.25 | 72.67 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.14 |
| LIGHTING_PLUGIN_GN2 | G N2 APARTMENT | G N2 APARTMENT | GENERAL | 0.8234 | 88.25 | 72.67 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.14 |
| LIGHTING_PLUGIN_GS1 | G S1 APARTMENT | G S1 APARTMENT | GENERAL | 0.8234 | 88.25 | 72.67 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.14 |
| LIGHTING_PLUGIN_GS2 | G S2 APARTMENT | G S2 APARTMENT | GENERAL | 0.8234 | 88.25 | 72.67 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.14 |
| LIGHTING_PLUGIN_MSW | M SW APARTMENT | M SW APARTMENT | GENERAL | 0.8234 | 176.50 | 145.34 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.28 |
| LIGHTING_PLUGIN_MNW | M NW APARTMENT | M NW APARTMENT | GENERAL | 0.8234 | 176.50 | 145.34 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.28 |
| LIGHTING_PLUGIN_MSE | M SE APARTMENT | M SE APARTMENT | GENERAL | 0.8234 | 176.50 | 145.34 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.28 |
| LIGHTING_PLUGIN_MNE | M NE APARTMENT | M NE APARTMENT | GENERAL | 0.8234 | 176.50 | 145.34 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.28 |
| LIGHTING_PLUGIN_MN1 | M N1 APARTMENT | M N1 APARTMENT | GENERAL | 0.8234 | 176.50 | 145.34 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.28 |
| LIGHTING_PLUGIN_MN2 | M N2 APARTMENT | M N2 APARTMENT | GENERAL | 0.8234 | 176.50 | 145.34 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.28 |
| LIGHTING_PLUGIN_MS1 | M S1 APARTMENT | M S1 APARTMENT | GENERAL | 0.8234 | 176.50 | 145.34 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.28 |
| LIGHTING_PLUGIN_MS2 | M S2 APARTMENT | M S2 APARTMENT | GENERAL | 0.8234 | 176.50 | 145.34 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.28 |
| LIGHTING_PLUGIN_TSW | T SW APARTMENT | T SW APARTMENT | GENERAL | 0.8234 | 88.25 | 72.67 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.14 |
| LIGHTING_PLUGIN_TNW | T NW APARTMENT | T NW APARTMENT | GENERAL | 0.8234 | 88.25 | 72.67 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.14 |
| LIGHTING_PLUGIN_TSE | T SE APARTMENT | T SE APARTMENT | GENERAL | 0.8234 | 88.25 | 72.67 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.14 |
| LIGHTING_PLUGIN_TNE | T NE APARTMENT | T NE APARTMENT | GENERAL | 0.8234 | 88.25 | 72.67 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.14 |
| LIGHTING_PLUGIN_TN1 | T N1 APARTMENT | T N1 APARTMENT | GENERAL | 0.8234 | 88.25 | 72.67 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.14 |
| LIGHTING_PLUGIN_TN2 | T N2 APARTMENT | T N2 APARTMENT | GENERAL | 0.8234 | 88.25 | 72.67 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.14 |
| LIGHTING_PLUGIN_TS1 | T S1 APARTMENT | T S1 APARTMENT | GENERAL | 0.8234 | 88.25 | 72.67 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.14 |
| LIGHTING_PLUGIN_TS2 | T S2 APARTMENT | T S2 APARTMENT | GENERAL | 0.8234 | 88.25 | 72.67 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.14 |
| Interior Lighting Total | 4.4498 | 5870.34 | 26121.74 | 75.91 |
| Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
| None |
| Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
| FACADE LIGHTING | 3183.33 | AstronomicalClock | - | 83.64 | 83.64 | 49.98 | |
| Exterior Lighting Total | 3183.33 | 49.98 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 09:15:04
Central Plant| Type | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
| None |
| Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
| SPLIT GSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 6045.53 | 4838.32 | 1207.21 | 0.80 | 3.91 | |||
| SPLIT GNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5788.81 | 4636.33 | 1152.48 | 0.80 | 3.91 | |||
| SPLIT OFFICE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7005.52 | 5608.57 | 1396.95 | 0.80 | 3.91 | |||
| SPLIT GNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5415.87 | 4333.46 | 1082.42 | 0.80 | 3.91 | |||
| SPLIT GN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 4875.68 | 3904.50 | 971.17 | 0.80 | 3.91 | |||
| SPLIT GN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 4873.48 | 3902.34 | 971.13 | 0.80 | 3.91 | |||
| SPLIT GS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5216.19 | 4177.79 | 1038.40 | 0.80 | 3.91 | |||
| SPLIT GS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5245.88 | 4198.03 | 1047.85 | 0.80 | 3.91 | |||
| SPLIT MSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 14460.98 | 11580.67 | 2880.31 | 0.80 | 3.91 | |||
| SPLIT MNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 14047.72 | 11238.74 | 2808.98 | 0.80 | 3.91 | |||
| SPLIT MSE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 13368.00 | 10696.16 | 2671.85 | 0.80 | 3.91 | |||
| SPLIT MNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 12962.94 | 10372.79 | 2590.15 | 0.80 | 3.91 | |||
| SPLIT MN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 11620.38 | 9306.66 | 2313.72 | 0.80 | 3.91 | |||
| SPLIT MN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 11598.22 | 9287.48 | 2310.74 | 0.80 | 3.91 | |||
| SPLIT MS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 12103.84 | 9685.48 | 2418.36 | 0.80 | 3.91 | |||
| SPLIT MS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 12080.75 | 9665.46 | 2415.29 | 0.80 | 3.91 | |||
| SPLIT TSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7867.62 | 6299.56 | 1568.06 | 0.80 | 3.91 | |||
| SPLIT TNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7797.78 | 6244.91 | 1552.87 | 0.80 | 3.91 | |||
| SPLIT TSE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7056.71 | 5651.39 | 1405.32 | 0.80 | 3.91 | |||
| SPLIT TNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 6984.41 | 5587.73 | 1396.67 | 0.80 | 3.91 | |||
| SPLIT TN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 6449.18 | 5162.72 | 1286.46 | 0.80 | 3.91 | |||
| SPLIT TN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 6419.96 | 5137.71 | 1282.24 | 0.80 | 3.91 | |||
| SPLIT TS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 6539.89 | 5234.20 | 1305.69 | 0.80 | 3.91 | |||
| SPLIT TS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 6510.87 | 5209.34 | 1301.53 | 0.80 | 3.91 |
| DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
| SPLIT GSW COOLING COIL | 5775.7 | 3.16 | 10.80 | 11.23 | 10.62 | 10.56 | |
| SPLIT GNW COOLING COIL | 5531.5 | 3.17 | 10.81 | 11.23 | 10.63 | 10.57 | |
| SPLIT OFFICE COOLING COIL | 6689.9 | 3.16 | 10.78 | 11.20 | 10.60 | 10.53 | |
| SPLIT GNE COOLING COIL | 5178.4 | 3.18 | 10.83 | 11.27 | 10.66 | 10.61 | |
| SPLIT GN1 COOLING COIL | 4662.7 | 3.18 | 10.84 | 11.27 | 10.67 | 10.63 | |
| SPLIT GN2 COOLING COIL | 4660.7 | 3.18 | 10.84 | 11.28 | 10.67 | 10.63 | |
| SPLIT GS1 COOLING COIL | 4987.0 | 3.17 | 10.83 | 11.26 | 10.65 | 10.61 | |
| SPLIT GS2 COOLING COIL | 5015.1 | 3.17 | 10.83 | 11.26 | 10.65 | 10.60 | |
| SPLIT MSW COOLING COIL | 13805.5 | 3.15 | 10.76 | 11.19 | 10.59 | 10.51 | |
| SPLIT MNW COOLING COIL | 13412.3 | 3.16 | 10.77 | 11.19 | 10.59 | 10.52 | |
| SPLIT MSE COOLING COIL | 12770.0 | 3.16 | 10.79 | 11.22 | 10.61 | 10.55 | |
| SPLIT MNE COOLING COIL | 12384.6 | 3.16 | 10.80 | 11.23 | 10.62 | 10.56 | |
| SPLIT MN1 COOLING COIL | 11102.4 | 3.17 | 10.80 | 11.23 | 10.62 | 10.56 | |
| SPLIT MN2 COOLING COIL | 11081.4 | 3.17 | 10.80 | 11.23 | 10.62 | 10.56 | |
| SPLIT MS1 COOLING COIL | 11562.3 | 3.16 | 10.79 | 11.22 | 10.61 | 10.55 | |
| SPLIT MS2 COOLING COIL | 11540.4 | 3.16 | 10.79 | 11.22 | 10.61 | 10.55 | |
| SPLIT TSW COOLING COIL | 7511.1 | 3.16 | 10.77 | 11.19 | 10.59 | 10.51 | |
| SPLIT TNW COOLING COIL | 7444.3 | 3.15 | 10.76 | 11.19 | 10.58 | 10.51 | |
| SPLIT TSE COOLING COIL | 6742.2 | 3.17 | 10.80 | 11.23 | 10.62 | 10.56 | |
| SPLIT TNE COOLING COIL | 6672.9 | 3.16 | 10.80 | 11.23 | 10.62 | 10.56 | |
| SPLIT TN1 COOLING COIL | 6158.7 | 3.16 | 10.78 | 11.20 | 10.60 | 10.53 | |
| SPLIT TN2 COOLING COIL | 6131.0 | 3.16 | 10.78 | 11.21 | 10.60 | 10.53 | |
| SPLIT TS1 COOLING COIL | 6245.5 | 3.16 | 10.78 | 11.21 | 10.60 | 10.53 | |
| SPLIT TS2 COOLING COIL | 6218.0 | 3.16 | 10.78 | 11.21 | 10.60 | 10.54 |
| DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
| SPLIT GSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT GNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT OFFICE COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT GNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT GN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT GN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT GS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT GS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT MSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT MNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT MSE COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT MNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT MN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT MN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT MS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT MS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT TSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT TNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT TSE COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT TNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT TN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT TN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT TS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT TS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed |
| DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
| None |
| Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
| SPLIT GSW HEATING COIL | Coil:Heating:Fuel | 8862.16 | 0.80 | |
| SPLIT GNW HEATING COIL | Coil:Heating:Fuel | 8497.72 | 0.80 | |
| SPLIT OFFICE HEATING COIL | Coil:Heating:Fuel | 10664.53 | 0.80 | |
| SPLIT GNE HEATING COIL | Coil:Heating:Fuel | 7917.48 | 0.80 | |
| SPLIT GN1 HEATING COIL | Coil:Heating:Fuel | 7202.91 | 0.80 | |
| SPLIT GN2 HEATING COIL | Coil:Heating:Fuel | 7198.61 | 0.80 | |
| SPLIT GS1 HEATING COIL | Coil:Heating:Fuel | 7677.72 | 0.80 | |
| SPLIT GS2 HEATING COIL | Coil:Heating:Fuel | 7722.14 | 0.80 | |
| SPLIT MSW HEATING COIL | Coil:Heating:Fuel | 21108.01 | 0.80 | |
| SPLIT MNW HEATING COIL | Coil:Heating:Fuel | 20520.32 | 0.80 | |
| SPLIT MSE HEATING COIL | Coil:Heating:Fuel | 19427.96 | 0.80 | |
| SPLIT MNE HEATING COIL | Coil:Heating:Fuel | 18853.62 | 0.80 | |
| SPLIT MN1 HEATING COIL | Coil:Heating:Fuel | 17093.99 | 0.80 | |
| SPLIT MN2 HEATING COIL | Coil:Heating:Fuel | 17059.82 | 0.80 | |
| SPLIT MS1 HEATING COIL | Coil:Heating:Fuel | 17781.82 | 0.80 | |
| SPLIT MS2 HEATING COIL | Coil:Heating:Fuel | 17745.90 | 0.80 | |
| SPLIT TSW HEATING COIL | Coil:Heating:Fuel | 11392.80 | 0.80 | |
| SPLIT TNW HEATING COIL | Coil:Heating:Fuel | 11305.17 | 0.80 | |
| SPLIT TSE HEATING COIL | Coil:Heating:Fuel | 10166.59 | 0.80 | |
| SPLIT TNE HEATING COIL | Coil:Heating:Fuel | 10077.14 | 0.80 | |
| SPLIT TN1 HEATING COIL | Coil:Heating:Fuel | 9465.45 | 0.80 | |
| SPLIT TN2 HEATING COIL | Coil:Heating:Fuel | 9421.03 | 0.80 | |
| SPLIT TS1 HEATING COIL | Coil:Heating:Fuel | 9580.42 | 0.80 | |
| SPLIT TS2 HEATING COIL | Coil:Heating:Fuel | 9536.20 | 0.80 |
| Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
| G SW APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| G SW APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| G NW APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| G NW APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| G NE APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| G NE APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| G N1 APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| G N1 APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| G N2 APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| G N2 APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| G S1 APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| G S1 APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| G S2 APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| G S2 APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| M SW APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.05 | 40.01 | 770.84 | 1.00 | 4.13 | General | ||
| M SW APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.05 | 40.01 | 770.84 | 1.00 | 4.13 | General | ||
| M NW APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.05 | 40.01 | 770.84 | 1.00 | 4.13 | General | ||
| M NW APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.05 | 40.01 | 770.84 | 1.00 | 4.13 | General | ||
| M SE APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.05 | 40.01 | 770.84 | 1.00 | 4.13 | General | ||
| M SE APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.05 | 40.01 | 770.84 | 1.00 | 4.13 | General | ||
| M NE APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.05 | 40.01 | 770.84 | 1.00 | 4.13 | General | ||
| M NE APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.05 | 40.01 | 770.84 | 1.00 | 4.13 | General | ||
| M N1 APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.05 | 40.01 | 770.84 | 1.00 | 4.13 | General | ||
| M N1 APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.05 | 40.01 | 770.84 | 1.00 | 4.13 | General | ||
| M N2 APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.05 | 40.01 | 770.84 | 1.00 | 4.13 | General | ||
| M N2 APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.05 | 40.01 | 770.84 | 1.00 | 4.13 | General | ||
| M S1 APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.05 | 40.01 | 770.84 | 1.00 | 4.13 | General | ||
| M S1 APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.05 | 40.01 | 770.84 | 1.00 | 4.13 | General | ||
| M S2 APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.05 | 40.01 | 770.84 | 1.00 | 4.13 | General | ||
| M S2 APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.05 | 40.01 | 770.84 | 1.00 | 4.13 | General | ||
| T SW APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| T SW APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| T NW APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| T NW APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| T SE APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| T SE APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| T NE APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| T NE APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| T N1 APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| T N1 APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| T N2 APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| T N2 APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| T S1 APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| T S1 APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| T S2 APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| T S2 APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| SPLIT GSW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.34 | 385.33 | 1120.11 | 1.00 | 1.80 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 |
| SPLIT GNW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.33 | 367.47 | 1120.11 | 1.00 | 1.83 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 |
| SPLIT OFFICE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.40 | 450.75 | 1120.11 | 1.00 | 1.71 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 |
| SPLIT GNE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.30 | 339.04 | 1120.11 | 1.00 | 1.89 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 |
| SPLIT GN1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.27 | 304.03 | 1120.11 | 1.00 | 1.97 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 |
| SPLIT GN2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.27 | 303.82 | 1120.11 | 1.00 | 1.97 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 |
| SPLIT GS1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.29 | 327.30 | 1120.11 | 1.00 | 1.91 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 |
| SPLIT GS2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.29 | 329.47 | 1120.11 | 1.00 | 1.91 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 |
| SPLIT MSW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.84 | 936.37 | 1120.11 | 1.00 | 1.42 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 |
| SPLIT MNW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.81 | 907.59 | 1120.11 | 1.00 | 1.43 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 |
| SPLIT MSE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.76 | 854.06 | 1120.11 | 1.00 | 1.45 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 |
| SPLIT MNE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.74 | 825.93 | 1120.11 | 1.00 | 1.46 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 |
| SPLIT MN1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.66 | 739.75 | 1120.11 | 1.00 | 1.50 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 |
| SPLIT MN2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.66 | 738.08 | 1120.11 | 1.00 | 1.50 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 |
| SPLIT MS1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.69 | 773.45 | 1120.11 | 1.00 | 1.48 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 |
| SPLIT MS2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.69 | 771.69 | 1120.11 | 1.00 | 1.48 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 |
| SPLIT TSW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.45 | 509.26 | 1120.11 | 1.00 | 1.65 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 |
| SPLIT TNW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.45 | 504.97 | 1120.11 | 1.00 | 1.65 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 |
| SPLIT TSE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.40 | 449.18 | 1120.11 | 1.00 | 1.71 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 |
| SPLIT TNE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.40 | 444.81 | 1120.11 | 1.00 | 1.72 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 |
| SPLIT TN1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.37 | 414.87 | 1120.11 | 1.00 | 1.76 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 |
| SPLIT TN2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.37 | 412.69 | 1120.11 | 1.00 | 1.76 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 |
| SPLIT TS1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.38 | 420.49 | 1120.11 | 1.00 | 1.75 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 |
| SPLIT TS2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.37 | 418.33 | 1120.11 | 1.00 | 1.75 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 |
| Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
| None |
| Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
| G SW APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.77 |
| G NW APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.77 |
| G NE APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.77 |
| G N1 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.77 |
| G N2 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.77 |
| G S1 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.77 |
| G S2 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.77 |
| M SW APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.79 |
| M NW APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.79 |
| M SE APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.79 |
| M NE APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.79 |
| M N1 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.79 |
| M N2 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.79 |
| M S1 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.79 |
| M S2 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.79 |
| T SW APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.77 |
| T NW APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.77 |
| T SE APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.77 |
| T NE APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.77 |
| T N1 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.77 |
| T N2 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.77 |
| T S1 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.77 |
| T S2 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.77 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 09:15:04
Zone Sensible Cooling| Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
| G SW APARTMENT | 4059.62 | 4871.54 | 55.20 | 0.287 | 0.344 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 24.00 | 24.00 | 0.00834 | 29.21 | 0.01411 | 0.026 | 0.00 |
| G NW APARTMENT | 3876.12 | 4651.34 | 52.71 | 0.273 | 0.328 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 24.00 | 24.00 | 0.00834 | 29.21 | 0.01411 | 0.026 | 0.00 |
| OFFICE | 4673.33 | 5607.99 | 63.55 | 0.335 | 0.402 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 23.90 | 23.90 | 0.00824 | 28.03 | 0.01411 | 0.038 | 0.00 |
| G NE APARTMENT | 3582.21 | 4298.65 | 48.71 | 0.252 | 0.303 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 24.00 | 24.00 | 0.00839 | 29.21 | 0.01411 | 0.026 | 0.00 |
| G N1 APARTMENT | 3222.09 | 3866.51 | 43.81 | 0.226 | 0.271 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 24.00 | 24.00 | 0.00834 | 29.21 | 0.01411 | 0.026 | 0.00 |
| G N2 APARTMENT | 3220.11 | 3864.13 | 43.79 | 0.226 | 0.271 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 24.00 | 24.00 | 0.00834 | 29.21 | 0.01411 | 0.026 | 0.00 |
| G S1 APARTMENT | 3461.41 | 4153.70 | 47.07 | 0.244 | 0.292 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 24.00 | 24.00 | 0.00834 | 29.21 | 0.01411 | 0.026 | 0.00 |
| G S2 APARTMENT | 3483.70 | 4180.44 | 47.37 | 0.245 | 0.294 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 24.00 | 24.00 | 0.00834 | 29.21 | 0.01411 | 0.026 | 0.00 |
| M SW APARTMENT | 9822.14 | 11786.57 | 133.56 | 0.697 | 0.836 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 24.00 | 24.00 | 0.00833 | 29.21 | 0.01411 | 0.052 | 0.00 |
| M NW APARTMENT | 9525.59 | 11430.71 | 129.53 | 0.675 | 0.810 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 24.00 | 24.00 | 0.00833 | 29.21 | 0.01411 | 0.052 | 0.00 |
| M SE APARTMENT | 8974.31 | 10769.17 | 122.03 | 0.635 | 0.762 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 24.00 | 24.00 | 0.00838 | 29.21 | 0.01411 | 0.052 | 0.00 |
| M NE APARTMENT | 8685.51 | 10422.61 | 118.10 | 0.614 | 0.737 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 24.00 | 24.00 | 0.00838 | 29.21 | 0.01411 | 0.052 | 0.00 |
| M N1 APARTMENT | 7802.56 | 9363.07 | 106.10 | 0.550 | 0.660 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 24.00 | 24.00 | 0.00832 | 29.21 | 0.01411 | 0.052 | 0.00 |
| M N2 APARTMENT | 7785.19 | 9342.23 | 105.86 | 0.549 | 0.659 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 24.00 | 24.00 | 0.00832 | 29.21 | 0.01411 | 0.052 | 0.00 |
| M S1 APARTMENT | 8147.70 | 9777.24 | 110.79 | 0.575 | 0.691 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 24.00 | 24.00 | 0.00832 | 29.21 | 0.01411 | 0.052 | 0.00 |
| M S2 APARTMENT | 8129.68 | 9755.62 | 110.55 | 0.574 | 0.689 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 24.00 | 24.00 | 0.00832 | 29.21 | 0.01411 | 0.052 | 0.00 |
| T SW APARTMENT | 5337.85 | 6405.42 | 72.58 | 0.379 | 0.455 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 24.00 | 24.00 | 0.00837 | 29.21 | 0.01411 | 0.026 | 0.00 |
| T NW APARTMENT | 5293.84 | 6352.61 | 71.98 | 0.376 | 0.451 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 24.00 | 24.00 | 0.00837 | 29.21 | 0.01411 | 0.026 | 0.00 |
| T SE APARTMENT | 4717.90 | 5661.48 | 64.15 | 0.334 | 0.401 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 24.00 | 24.00 | 0.00843 | 29.21 | 0.01411 | 0.026 | 0.00 |
| T NE APARTMENT | 4672.57 | 5607.09 | 63.54 | 0.331 | 0.397 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 24.00 | 24.00 | 0.00842 | 29.21 | 0.01411 | 0.026 | 0.00 |
| T N1 APARTMENT | 4364.27 | 5237.13 | 59.34 | 0.309 | 0.370 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 24.00 | 24.00 | 0.00831 | 29.21 | 0.01411 | 0.026 | 0.00 |
| T N2 APARTMENT | 4341.88 | 5210.25 | 59.04 | 0.307 | 0.368 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 24.00 | 24.00 | 0.00832 | 29.21 | 0.01411 | 0.026 | 0.00 |
| T S1 APARTMENT | 4422.34 | 5306.80 | 60.13 | 0.313 | 0.375 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 24.00 | 24.00 | 0.00832 | 29.21 | 0.01411 | 0.026 | 0.00 |
| T S2 APARTMENT | 4400.03 | 5280.03 | 59.83 | 0.311 | 0.373 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 24.00 | 24.00 | 0.00833 | 29.21 | 0.01411 | 0.026 | 0.00 |
| Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
| G SW APARTMENT | 2233.13 | 2679.75 | 30.37 | 0.096 | 0.116 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:50:00 | 21.10 | 21.10 | 0.00711 | -10.70 | 0.00150 | 0.026 | 0.00 |
| G NW APARTMENT | 2123.18 | 2547.82 | 28.87 | 0.092 | 0.110 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 21.10 | 21.10 | 0.00715 | -10.70 | 0.00150 | 0.026 | 0.00 |
| OFFICE | 2677.11 | 3212.54 | 36.40 | 0.115 | 0.138 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 18:50:00 | 21.10 | 21.10 | 0.00724 | -10.70 | 0.00150 | 0.038 | 0.00 |
| G NE APARTMENT | 2115.97 | 2539.17 | 28.77 | 0.091 | 0.109 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 21.10 | 21.10 | 0.00715 | -10.70 | 0.00150 | 0.026 | 0.00 |
| G N1 APARTMENT | 1292.36 | 1550.83 | 17.57 | 0.056 | 0.067 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 21.10 | 21.10 | 0.00722 | -10.70 | 0.00150 | 0.026 | 0.00 |
| G N2 APARTMENT | 1292.14 | 1550.57 | 17.57 | 0.056 | 0.067 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 21.10 | 21.10 | 0.00722 | -10.70 | 0.00150 | 0.026 | 0.00 |
| G S1 APARTMENT | 1403.59 | 1684.31 | 19.09 | 0.061 | 0.073 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:50:00 | 21.10 | 21.10 | 0.00713 | -10.70 | 0.00150 | 0.026 | 0.00 |
| G S2 APARTMENT | 1411.74 | 1694.09 | 19.20 | 0.061 | 0.073 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:50:00 | 21.10 | 21.10 | 0.00713 | -10.70 | 0.00150 | 0.026 | 0.00 |
| M SW APARTMENT | 4292.19 | 5150.63 | 58.36 | 0.185 | 0.222 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 21.10 | 21.10 | 0.00677 | -10.70 | 0.00150 | 0.052 | 0.00 |
| M NW APARTMENT | 4029.17 | 4835.01 | 54.79 | 0.174 | 0.208 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 21.10 | 21.10 | 0.00683 | -10.70 | 0.00150 | 0.052 | 0.00 |
| M SE APARTMENT | 4275.03 | 5130.03 | 58.13 | 0.184 | 0.221 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 21.10 | 21.10 | 0.00676 | -10.70 | 0.00150 | 0.052 | 0.00 |
| M NE APARTMENT | 4011.96 | 4814.35 | 54.55 | 0.173 | 0.208 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 21.10 | 21.10 | 0.00683 | -10.70 | 0.00150 | 0.052 | 0.00 |
| M N1 APARTMENT | 2176.10 | 2611.32 | 29.59 | 0.094 | 0.113 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 21.10 | 21.10 | 0.00681 | -10.70 | 0.00150 | 0.052 | 0.00 |
| M N2 APARTMENT | 2175.65 | 2610.77 | 29.58 | 0.094 | 0.113 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 21.10 | 21.10 | 0.00681 | -10.70 | 0.00150 | 0.052 | 0.00 |
| M S1 APARTMENT | 2432.37 | 2918.84 | 33.07 | 0.105 | 0.126 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 21.10 | 21.10 | 0.00670 | -10.70 | 0.00150 | 0.052 | 0.00 |
| M S2 APARTMENT | 2431.92 | 2918.30 | 33.07 | 0.105 | 0.126 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 21.10 | 21.10 | 0.00670 | -10.70 | 0.00150 | 0.052 | 0.00 |
| T SW APARTMENT | 3489.27 | 4187.12 | 47.45 | 0.150 | 0.180 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 21.10 | 21.10 | 0.00696 | -10.70 | 0.00150 | 0.026 | 0.00 |
| T NW APARTMENT | 3353.18 | 4023.81 | 45.60 | 0.145 | 0.173 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 21.10 | 21.10 | 0.00701 | -10.70 | 0.00150 | 0.026 | 0.00 |
| T SE APARTMENT | 3477.43 | 4172.92 | 47.29 | 0.150 | 0.180 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 21.10 | 21.10 | 0.00696 | -10.70 | 0.00150 | 0.026 | 0.00 |
| T NE APARTMENT | 3341.28 | 4009.53 | 45.43 | 0.144 | 0.173 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 21.10 | 21.10 | 0.00700 | -10.70 | 0.00150 | 0.026 | 0.00 |
| T N1 APARTMENT | 2226.11 | 2671.33 | 30.27 | 0.096 | 0.115 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 21.10 | 21.10 | 0.00713 | -10.70 | 0.00150 | 0.026 | 0.00 |
| T N2 APARTMENT | 2225.77 | 2670.93 | 30.27 | 0.096 | 0.115 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 21.10 | 21.10 | 0.00713 | -10.70 | 0.00150 | 0.026 | 0.00 |
| T S1 APARTMENT | 2362.19 | 2834.63 | 32.12 | 0.102 | 0.122 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 21.10 | 21.10 | 0.00706 | -10.70 | 0.00150 | 0.026 | 0.00 |
| T S2 APARTMENT | 2361.86 | 2834.23 | 32.12 | 0.102 | 0.122 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 21.10 | 21.10 | 0.00706 | -10.70 | 0.00150 | 0.026 | 0.00 |
| Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
| SPLIT GSW | 0.34 | 0.34 | 0.12 | 0.12 | 0.3440 | 0.3440 | 0.3440 | 1.0000 | 1.0000 |
| SPLIT GNW | 0.33 | 0.33 | 0.11 | 0.11 | 0.3281 | 0.3281 | 0.3281 | 1.0000 | 1.0000 |
| SPLIT OFFICE | 0.40 | 0.40 | 0.14 | 0.14 | 0.4024 | 0.4024 | 0.4024 | 1.0000 | 1.0000 |
| SPLIT GNE | 0.30 | 0.30 | 0.11 | 0.11 | 0.3027 | 0.3027 | 0.3027 | 1.0000 | 1.0000 |
| SPLIT GN1 | 0.27 | 0.27 | 0.07 | 0.07 | 0.2714 | 0.2714 | 0.2714 | 1.0000 | 1.0000 |
| SPLIT GN2 | 0.27 | 0.27 | 0.07 | 0.07 | 0.2712 | 0.2712 | 0.2712 | 1.0000 | 1.0000 |
| SPLIT GS1 | 0.29 | 0.29 | 0.07 | 0.07 | 0.2922 | 0.2922 | 0.2922 | 1.0000 | 1.0000 |
| SPLIT GS2 | 0.29 | 0.29 | 0.07 | 0.07 | 0.2941 | 0.2941 | 0.2941 | 1.0000 | 1.0000 |
| SPLIT MSW | 0.84 | 0.84 | 0.22 | 0.22 | 0.8360 | 0.8360 | 0.8360 | 1.0000 | 1.0000 |
| SPLIT MNW | 0.81 | 0.81 | 0.21 | 0.21 | 0.8103 | 0.8103 | 0.8103 | 1.0000 | 1.0000 |
| SPLIT MSE | 0.76 | 0.76 | 0.22 | 0.22 | 0.7625 | 0.7625 | 0.7625 | 1.0000 | 1.0000 |
| SPLIT MNE | 0.74 | 0.74 | 0.21 | 0.21 | 0.7374 | 0.7374 | 0.7374 | 1.0000 | 1.0000 |
| SPLIT MN1 | 0.66 | 0.66 | 0.11 | 0.11 | 0.6604 | 0.6604 | 0.6604 | 1.0000 | 1.0000 |
| SPLIT MN2 | 0.66 | 0.66 | 0.11 | 0.11 | 0.6589 | 0.6589 | 0.6589 | 1.0000 | 1.0000 |
| SPLIT MS1 | 0.69 | 0.69 | 0.13 | 0.13 | 0.6905 | 0.6905 | 0.6905 | 1.0000 | 1.0000 |
| SPLIT MS2 | 0.69 | 0.69 | 0.13 | 0.13 | 0.6889 | 0.6889 | 0.6889 | 1.0000 | 1.0000 |
| SPLIT TSW | 0.45 | 0.45 | 0.18 | 0.18 | 0.4546 | 0.4546 | 0.4546 | 1.0000 | 1.0000 |
| SPLIT TNW | 0.45 | 0.45 | 0.17 | 0.17 | 0.4508 | 0.4508 | 0.4508 | 1.0000 | 1.0000 |
| SPLIT TSE | 0.40 | 0.40 | 0.18 | 0.18 | 0.4010 | 0.4010 | 0.4010 | 1.0000 | 1.0000 |
| SPLIT TNE | 0.40 | 0.40 | 0.17 | 0.17 | 0.3971 | 0.3971 | 0.3971 | 1.0000 | 1.0000 |
| SPLIT TN1 | 0.37 | 0.37 | 0.12 | 0.12 | 0.3704 | 0.3704 | 0.3704 | 1.0000 | 1.0000 |
| SPLIT TN2 | 0.37 | 0.37 | 0.12 | 0.12 | 0.3684 | 0.3684 | 0.3684 | 1.0000 | 1.0000 |
| SPLIT TS1 | 0.38 | 0.38 | 0.12 | 0.12 | 0.3754 | 0.3754 | 0.3754 | 1.0000 | 1.0000 |
| SPLIT TS2 | 0.37 | 0.37 | 0.12 | 0.12 | 0.3735 | 0.3735 | 0.3735 | 1.0000 | 1.0000 |
| Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
| None |
| Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
| SPLIT GSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT GSW | 6045.528 | 4838.321 | 0.344011 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 5948.01 | 5255.00 | 0.344011 | 25.34 | 17.09 | 0.00877332 | 12.80 | 11.59 | 0.00800000 | 29.21 | 0.01411444 | 22.32 | 7.5447 | 24.00 | 0.00833746 | 44.8753 | 4059.62 | 0.00 | 6044.50 | 4832.17 |
| SPLIT GSW HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT GSW | 8862.163 | 8862.163 | -999.0 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:50:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:50:00 | 8862.16 | 8862.16 | 0.344011 | 18.70 | 12.71 | 0.00668682 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 7.5447 | 21.10 | 0.00710977 | 45.7265 | 2233.13 | 0.00 | -999.00 | -999.00 |
| SPLIT GNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT GNW | 5788.813 | 4636.335 | 0.328070 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 5698.45 | 5019.45 | 0.328070 | 25.36 | 17.11 | 0.00879409 | 12.80 | 11.59 | 0.00800000 | 29.21 | 0.01411444 | 22.32 | 7.9113 | 24.00 | 0.00833702 | 44.8727 | 3876.12 | 0.00 | 5787.83 | 4632.10 |
| SPLIT GNW HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT GNW | 8497.724 | 8497.724 | -999.0 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 8497.72 | 8497.72 | 0.328070 | 18.58 | 12.68 | 0.00670372 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 7.9113 | 21.10 | 0.00715043 | 45.9876 | 2123.18 | 0.00 | -999.00 | -999.00 |
| SPLIT OFFICE COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT OFFICE | 7005.520 | 5608.570 | 0.402412 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 6938.00 | 6107.90 | 0.402412 | 25.25 | 17.07 | 0.00879202 | 12.80 | 11.59 | 0.00800000 | 28.03 | 0.01411232 | 21.98 | 9.4694 | 23.90 | 0.00823552 | 44.6011 | 4673.33 | 0.00 | 7004.33 | 5601.81 |
| SPLIT OFFICE HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT OFFICE | 10664.532 | 10664.532 | -999.0 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 18:50:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 18:50:00 | 10664.53 | 10664.53 | 0.402412 | 18.09 | 12.47 | 0.00670009 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 9.4694 | 21.10 | 0.00724360 | 46.5774 | 2677.11 | 0.00 | -999.00 | -999.00 |
| SPLIT GNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT GNE | 5415.875 | 4333.459 | 0.302688 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 5341.01 | 4647.56 | 0.302688 | 25.38 | 17.19 | 0.00887743 | 12.80 | 11.59 | 0.00800000 | 29.21 | 0.01411444 | 22.32 | 8.5747 | 24.00 | 0.00838626 | 45.1345 | 3582.21 | 0.00 | 5414.95 | 4328.81 |
| SPLIT GNE HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT GNE | 7917.485 | 7917.485 | -999.0 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 7917.48 | 7917.48 | 0.302688 | 18.37 | 12.55 | 0.00666399 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 8.5747 | 21.10 | 0.00714795 | 45.9718 | 2115.97 | 0.00 | -999.00 | -999.00 |
| SPLIT GN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT GN1 | 4875.679 | 3904.505 | 0.271433 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 4810.84 | 4180.16 | 0.271433 | 25.42 | 17.21 | 0.00888948 | 12.80 | 11.59 | 0.00800000 | 29.21 | 0.01411444 | 22.32 | 9.5620 | 24.00 | 0.00833705 | 44.8725 | 3222.09 | 0.00 | 4874.85 | 3900.01 |
| SPLIT GN1 HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT GN1 | 7202.911 | 7202.911 | -999.0 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 7202.91 | 7202.91 | 0.271433 | 18.06 | 12.43 | 0.00667090 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 9.5620 | 21.10 | 0.00721721 | 46.4100 | 1292.36 | 0.00 | -999.00 | -999.00 |
| SPLIT GN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT GN2 | 4873.477 | 3902.343 | 0.271245 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 4808.82 | 4177.65 | 0.271245 | 25.42 | 17.21 | 0.00889076 | 12.80 | 11.59 | 0.00800000 | 29.21 | 0.01411444 | 22.32 | 9.5687 | 24.00 | 0.00833804 | 44.8778 | 3220.11 | 0.00 | 4872.65 | 3897.84 |
| SPLIT GN2 HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT GN2 | 7198.612 | 7198.612 | -999.0 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 7198.61 | 7198.61 | 0.271245 | 18.06 | 12.43 | 0.00667042 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 9.5687 | 21.10 | 0.00721710 | 46.4093 | 1292.14 | 0.00 | -999.00 | -999.00 |
| SPLIT GS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT GS1 | 5216.190 | 4177.791 | 0.292202 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 5142.59 | 4489.10 | 0.292202 | 25.40 | 17.17 | 0.00885681 | 12.80 | 11.59 | 0.00800000 | 29.21 | 0.01411444 | 22.32 | 8.8824 | 24.00 | 0.00834428 | 44.9113 | 3461.41 | 0.00 | 5215.30 | 4173.37 |
| SPLIT GS1 HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT GS1 | 7677.717 | 7677.717 | -999.0 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:50:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:50:00 | 7677.72 | 7677.72 | 0.292202 | 18.27 | 12.47 | 0.00662664 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 8.8824 | 21.10 | 0.00712602 | 45.8288 | 1403.59 | 0.00 | -999.00 | -999.00 |
| SPLIT GS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT GS2 | 5245.878 | 4198.027 | 0.294145 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 5171.21 | 4517.53 | 0.294145 | 25.40 | 17.17 | 0.00885149 | 12.80 | 11.59 | 0.00800000 | 29.21 | 0.01411444 | 22.32 | 8.8237 | 24.00 | 0.00834216 | 44.9001 | 3483.70 | 0.00 | 5244.99 | 4193.72 |
| SPLIT GS2 HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT GS2 | 7722.135 | 7722.135 | -999.0 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:50:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:50:00 | 7722.14 | 7722.14 | 0.294145 | 18.29 | 12.49 | 0.00663401 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 8.8237 | 21.10 | 0.00713049 | 45.8572 | 1411.74 | 0.00 | -999.00 | -999.00 |
| SPLIT MSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT MSW | 14460.983 | 11580.671 | 0.835966 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 14198.78 | 12694.03 | 0.835966 | 25.28 | 17.00 | 0.00869239 | 12.80 | 11.59 | 0.00800000 | 29.21 | 0.01411444 | 22.32 | 6.2095 | 24.00 | 0.00833342 | 44.8539 | 19644.28 | 0.00 | 14458.52 | 11566.97 |
| SPLIT MSW HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT MSW | 21108.009 | 21108.009 | -999.0 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 21108.01 | 21108.01 | 0.835966 | 19.12 | 12.64 | 0.00644204 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 6.2095 | 21.10 | 0.00676898 | 43.5631 | 8584.38 | 0.00 | -999.00 | -999.00 |
| SPLIT MNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT MNW | 14047.722 | 11238.739 | 0.810271 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 13796.96 | 12314.43 | 0.810271 | 25.29 | 17.01 | 0.00870359 | 12.80 | 11.59 | 0.00800000 | 29.21 | 0.01411444 | 22.32 | 6.4064 | 24.00 | 0.00833322 | 44.8527 | 19051.18 | 0.00 | 14045.33 | 11225.80 |
| SPLIT MNW HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT MNW | 20520.325 | 20520.325 | -999.0 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 20520.32 | 20520.32 | 0.810271 | 19.06 | 12.66 | 0.00649177 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 6.4064 | 21.10 | 0.00683318 | 43.9711 | 8058.35 | 0.00 | -999.00 | -999.00 |
| SPLIT MSE COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT MSE | 13368.005 | 10696.156 | 0.762479 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 13148.17 | 11618.35 | 0.762479 | 25.31 | 17.07 | 0.00877040 | 12.80 | 11.59 | 0.00800000 | 29.21 | 0.01411444 | 22.32 | 6.8079 | 24.00 | 0.00838001 | 45.1017 | 17948.62 | 0.00 | 13365.73 | 10682.89 |
| SPLIT MSE HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT MSE | 19427.965 | 19427.965 | -999.0 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 19427.96 | 19427.96 | 0.762479 | 18.93 | 12.52 | 0.00640680 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 6.8079 | 21.10 | 0.00676497 | 43.5376 | 8550.05 | 0.00 | -999.00 | -999.00 |
| SPLIT MNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT MNE | 12962.939 | 10372.791 | 0.737367 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 12754.27 | 11247.41 | 0.737367 | 25.32 | 17.09 | 0.00878441 | 12.80 | 11.59 | 0.00800000 | 29.21 | 0.01411444 | 22.32 | 7.0398 | 24.00 | 0.00838077 | 45.1056 | 17371.01 | 0.00 | 12960.73 | 10359.63 |
| SPLIT MNE HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT MNE | 18853.621 | 18853.621 | -999.0 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 18853.62 | 18853.62 | 0.737367 | 18.86 | 12.54 | 0.00645428 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 7.0398 | 21.10 | 0.00682917 | 43.9455 | 8023.91 | 0.00 | -999.00 | -999.00 |
| SPLIT MN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT MN1 | 11620.379 | 9306.658 | 0.660432 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 11434.83 | 10099.80 | 0.660432 | 25.36 | 17.09 | 0.00877588 | 12.80 | 11.59 | 0.00800000 | 29.21 | 0.01411444 | 22.32 | 7.8599 | 24.00 | 0.00832048 | 44.7846 | 15605.12 | 0.00 | 11618.40 | 9296.47 |
| SPLIT MN1 HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT MN1 | 17093.989 | 17093.989 | -999.0 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 17093.99 | 17093.99 | 0.660432 | 18.60 | 12.38 | 0.00639678 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 7.8599 | 21.10 | 0.00681416 | 43.8472 | 4352.20 | 0.00 | -999.00 | -999.00 |
| SPLIT MN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT MN2 | 11598.216 | 9287.477 | 0.658937 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 11413.55 | 10077.87 | 0.658937 | 25.36 | 17.10 | 0.00877798 | 12.80 | 11.59 | 0.00800000 | 29.21 | 0.01411444 | 22.32 | 7.8777 | 24.00 | 0.00832164 | 44.7907 | 15570.39 | 0.00 | 11596.24 | 9277.32 |
| SPLIT MN2 HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT MN2 | 17059.819 | 17059.819 | -999.0 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 17059.82 | 17059.82 | 0.658937 | 18.59 | 12.37 | 0.00639565 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 7.8777 | 21.10 | 0.00681397 | 43.8460 | 4351.29 | 0.00 | -999.00 | -999.00 |
| SPLIT MS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT MS1 | 12103.841 | 9685.483 | 0.690510 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 11904.72 | 10543.82 | 0.690510 | 25.34 | 17.07 | 0.00875682 | 12.80 | 11.59 | 0.00800000 | 29.21 | 0.01411444 | 22.32 | 7.5175 | 24.00 | 0.00832133 | 44.7893 | 16295.40 | 0.00 | 12101.78 | 9673.46 |
| SPLIT MS1 HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT MS1 | 17781.819 | 17781.819 | -999.0 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 17781.82 | 17781.82 | 0.690510 | 18.71 | 12.33 | 0.00631011 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 7.5175 | 21.10 | 0.00670078 | 43.1262 | 4864.74 | 0.00 | -999.00 | -999.00 |
| SPLIT MS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT MS2 | 12080.749 | 9665.460 | 0.688939 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 11882.57 | 10520.89 | 0.688939 | 25.34 | 17.07 | 0.00875895 | 12.80 | 11.59 | 0.00800000 | 29.21 | 0.01411444 | 22.32 | 7.5346 | 24.00 | 0.00832255 | 44.7958 | 16259.36 | 0.00 | 12078.69 | 9653.49 |
| SPLIT MS2 HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT MS2 | 17745.899 | 17745.899 | -999.0 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 17745.90 | 17745.90 | 0.688939 | 18.70 | 12.33 | 0.00630904 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 7.5346 | 21.10 | 0.00670059 | 43.1250 | 4863.84 | 0.00 | -999.00 | -999.00 |
| SPLIT TSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT TSW | 7867.616 | 6299.557 | 0.454650 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 7725.24 | 6896.05 | 0.454650 | 25.27 | 17.00 | 0.00870148 | 12.80 | 11.59 | 0.00800000 | 29.21 | 0.01411444 | 22.32 | 5.7087 | 24.00 | 0.00837376 | 45.0687 | 5337.85 | 0.00 | 7866.28 | 6292.14 |
| SPLIT TSW HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT TSW | 11392.799 | 11392.799 | -999.0 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 11392.80 | 11392.80 | 0.454650 | 19.28 | 12.90 | 0.00665075 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 5.7087 | 21.10 | 0.00696235 | 44.7967 | 3489.27 | 0.00 | -999.00 | -999.00 |
| SPLIT TNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT TNW | 7797.781 | 6244.915 | 0.450823 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 7656.23 | 6838.65 | 0.450823 | 25.27 | 17.00 | 0.00869758 | 12.80 | 11.59 | 0.00800000 | 29.21 | 0.01411444 | 22.32 | 5.7571 | 24.00 | 0.00836667 | 45.0309 | 5293.84 | 0.00 | 7796.45 | 6237.52 |
| SPLIT TNW HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT TNW | 11305.173 | 11305.173 | -999.0 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 11305.17 | 11305.17 | 0.450823 | 19.27 | 12.94 | 0.00669067 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 5.7571 | 21.10 | 0.00700752 | 45.0833 | 3353.18 | 0.00 | -999.00 | -999.00 |
| SPLIT TSE COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT TSE | 7056.706 | 5651.390 | 0.401017 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 6943.89 | 6109.46 | 0.401017 | 25.30 | 17.09 | 0.00879858 | 12.80 | 11.59 | 0.00800000 | 29.21 | 0.01411444 | 22.32 | 6.4722 | 24.00 | 0.00843071 | 45.3715 | 4717.90 | 0.00 | 7055.51 | 5645.21 |
| SPLIT TSE HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT TSE | 10166.589 | 10166.589 | -999.0 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 10166.59 | 10166.59 | 0.401017 | 19.04 | 12.76 | 0.00660630 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 6.4722 | 21.10 | 0.00695939 | 44.7778 | 3477.43 | 0.00 | -999.00 | -999.00 |
| SPLIT TNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT TNE | 6984.408 | 5587.734 | 0.397110 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 6872.31 | 6050.54 | 0.397110 | 25.30 | 17.09 | 0.00879425 | 12.80 | 11.59 | 0.00800000 | 29.21 | 0.01411444 | 22.32 | 6.5359 | 24.00 | 0.00842221 | 45.3261 | 4672.57 | 0.00 | 6983.22 | 5580.66 |
| SPLIT TNE HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT TNE | 10077.140 | 10077.140 | -999.0 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 10077.14 | 10077.14 | 0.397110 | 19.02 | 12.79 | 0.00664505 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 6.5359 | 21.10 | 0.00700457 | 45.0645 | 3341.28 | 0.00 | -999.00 | -999.00 |
| SPLIT TN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT TN1 | 6449.176 | 5162.716 | 0.370381 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 6337.63 | 5643.61 | 0.370381 | 25.32 | 17.03 | 0.00872018 | 12.80 | 11.59 | 0.00800000 | 29.21 | 0.01411444 | 22.32 | 7.0075 | 24.00 | 0.00831369 | 44.7485 | 4364.27 | 0.00 | 6448.08 | 5156.50 |
| SPLIT TN1 HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT TN1 | 9465.448 | 9465.448 | -999.0 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 9465.45 | 9465.45 | 0.370381 | 18.87 | 12.82 | 0.00673842 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 7.0075 | 21.10 | 0.00713287 | 45.8766 | 2226.11 | 0.00 | -999.00 | -999.00 |
| SPLIT TN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT TN2 | 6419.956 | 5137.713 | 0.368438 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 6309.50 | 5615.15 | 0.368438 | 25.33 | 17.04 | 0.00872425 | 12.80 | 11.59 | 0.00800000 | 29.21 | 0.01411444 | 22.32 | 7.0445 | 24.00 | 0.00831576 | 44.7595 | 4341.88 | 0.00 | 6418.86 | 5131.57 |
| SPLIT TN2 HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT TN2 | 9421.031 | 9421.031 | -999.0 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 9421.03 | 9421.03 | 0.368438 | 18.86 | 12.82 | 0.00673623 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 7.0445 | 21.10 | 0.00713276 | 45.8759 | 2225.77 | 0.00 | -999.00 | -999.00 |
| SPLIT TS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT TS1 | 6539.894 | 5234.204 | 0.375404 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 6427.17 | 5719.05 | 0.375404 | 25.32 | 17.04 | 0.00872493 | 12.80 | 11.59 | 0.00800000 | 29.21 | 0.01411444 | 22.32 | 6.9138 | 24.00 | 0.00832464 | 44.8068 | 4422.34 | 0.00 | 6538.78 | 5227.93 |
| SPLIT TS1 HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT TS1 | 9580.425 | 9580.425 | -999.0 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 9580.42 | 9580.42 | 0.375404 | 18.90 | 12.77 | 0.00667463 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 6.9138 | 21.10 | 0.00705867 | 45.4056 | 2362.19 | 0.00 | -999.00 | -999.00 |
| SPLIT TS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT TS2 | 6510.873 | 5209.343 | 0.373470 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 6399.24 | 5690.72 | 0.373470 | 25.32 | 17.04 | 0.00872902 | 12.80 | 11.59 | 0.00800000 | 29.21 | 0.01411444 | 22.32 | 6.9496 | 24.00 | 0.00832680 | 44.8184 | 4400.03 | 0.00 | 6509.77 | 5203.14 |
| SPLIT TS2 HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT TS2 | 9536.204 | 9536.204 | -999.0 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 9536.20 | 9536.20 | 0.373470 | 18.89 | 12.77 | 0.00667254 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 6.9496 | 21.10 | 0.00705856 | 45.4049 | 2361.86 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 09:15:04
Coils| Coil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
| SPLIT GSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT GSW | G SW APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 6045.528 | 4838.321 | 0.344011 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.1492 | 1004.8586 | 1.2036 | SPLIT GSW SUPPLY FAN | Fan:OnOff | 0.344011 | 0.41405006 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | Sensible | 5948.01 | 5255.00 | 0.9839 | 0.41405006 | 0.344011 | 25.34 | 17.09 | 0.00877332 | 47820.5 | 12.80 | 11.59 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 385.330 | 5562.69 | 29.21 | 0.01411444 | 22.32 | 0.02595455 | 7.5447 | 24.04 | 0.00833746 | 24.00 | 0.00833746 | 44.8753 | 4059.62 | 0.00 | 6044.50 | 4832.17 | 0.39769822 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.79 | 14.32 | 0.00998947 | 40123.7 | |
| SPLIT GSW HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT GSW | G SW APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 8862.163 | 8862.163 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | SPLIT GSW SUPPLY FAN | Fan:OnOff | 0.344011 | 0.41405006 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:50:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:50:00 | Sensible | 8862.16 | 8862.16 | 1.0000 | 0.41405006 | 0.344011 | 18.70 | 12.71 | 0.00668682 | 35746.2 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8862.16 | -10.70 | 0.00150390 | -10.70 | 0.02595455 | 7.5447 | 21.10 | 0.00710977 | 21.10 | 0.00710977 | 45.7265 | 2233.13 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT GNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT GNW | G NW APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 5788.813 | 4636.335 | 0.328070 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.1878 | 1004.8586 | 1.2036 | SPLIT GNW SUPPLY FAN | Fan:OnOff | 0.328070 | 0.39486382 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | Sensible | 5698.45 | 5019.45 | 0.9844 | 0.39486382 | 0.328070 | 25.36 | 17.11 | 0.00879409 | 47889.6 | 12.80 | 11.59 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 367.474 | 5330.98 | 29.21 | 0.01411444 | 22.32 | 0.02595455 | 7.9113 | 24.04 | 0.00833702 | 24.00 | 0.00833702 | 44.8727 | 3876.12 | 0.00 | 5787.83 | 4632.10 | 0.37926969 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.73 | 14.30 | 0.00998991 | 40061.9 | |
| SPLIT GNW HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT GNW | G NW APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 8497.724 | 8497.724 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | SPLIT GNW SUPPLY FAN | Fan:OnOff | 0.328070 | 0.39486382 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | Sensible | 8497.72 | 8497.72 | 1.0000 | 0.39486382 | 0.328070 | 18.58 | 12.68 | 0.00670372 | 35670.5 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8497.72 | -10.70 | 0.00150390 | -10.70 | 0.02595455 | 7.9113 | 21.10 | 0.00715043 | 21.10 | 0.00715043 | 45.9876 | 2123.18 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT OFFICE COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT OFFICE | OFFICE | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 7005.520 | 5608.570 | 0.402412 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.1839 | 1004.8586 | 1.2036 | SPLIT OFFICE SUPPLY FAN | Fan:OnOff | 0.402412 | 0.48434137 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | Sensible | 6938.00 | 6107.90 | 0.9904 | 0.48434137 | 0.402412 | 25.25 | 17.07 | 0.00879202 | 47774.6 | 12.80 | 11.59 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 450.745 | 6487.25 | 28.03 | 0.01411232 | 21.98 | 0.03810604 | 9.4694 | 23.95 | 0.00823552 | 23.90 | 0.00823552 | 44.6011 | 4673.33 | 0.00 | 7004.33 | 5601.81 | 0.46521355 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.90 | 14.38 | 0.01000263 | 40266.2 | |
| SPLIT OFFICE HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT OFFICE | OFFICE | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 10664.532 | 10664.532 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | SPLIT OFFICE SUPPLY FAN | Fan:OnOff | 0.402412 | 0.48434137 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 18:50:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 18:50:00 | Sensible | 10664.53 | 10664.53 | 1.0000 | 0.48434137 | 0.402412 | 18.09 | 12.47 | 0.00670009 | 35157.2 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10664.53 | -10.70 | 0.00150390 | -10.70 | 0.03810604 | 9.4694 | 21.10 | 0.00724360 | 21.10 | 0.00724360 | 46.5774 | 2677.11 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT GNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT GNE | G NE APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 5415.875 | 4333.459 | 0.302688 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.3427 | 1004.8586 | 1.2036 | SPLIT GNE SUPPLY FAN | Fan:OnOff | 0.302688 | 0.36431321 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | Sensible | 5341.01 | 4647.56 | 0.9862 | 0.36431321 | 0.302688 | 25.38 | 17.19 | 0.00887743 | 48128.6 | 12.80 | 11.59 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 339.043 | 5001.97 | 29.21 | 0.01411444 | 22.32 | 0.02595455 | 8.5747 | 24.03 | 0.00838626 | 24.00 | 0.00838626 | 45.1345 | 3582.21 | 0.00 | 5414.95 | 4328.81 | 0.34992560 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.58 | 14.22 | 0.00996769 | 39847.8 | |
| SPLIT GNE HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT GNE | G NE APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 7917.485 | 7917.485 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | SPLIT GNE SUPPLY FAN | Fan:OnOff | 0.302688 | 0.36431321 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | Sensible | 7917.48 | 7917.48 | 1.0000 | 0.36431321 | 0.302688 | 18.37 | 12.55 | 0.00666399 | 35355.2 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 7917.48 | -10.70 | 0.00150390 | -10.70 | 0.02595455 | 8.5747 | 21.10 | 0.00714795 | 21.10 | 0.00714795 | 45.9718 | 2115.97 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT GN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT GN1 | G N1 APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 4875.679 | 3904.505 | 0.271433 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.3651 | 1004.8586 | 1.2036 | SPLIT GN1 SUPPLY FAN | Fan:OnOff | 0.271433 | 0.32669536 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | Sensible | 4810.84 | 4180.16 | 0.9867 | 0.32669536 | 0.271433 | 25.42 | 17.21 | 0.00888948 | 48197.9 | 12.80 | 11.59 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 304.034 | 4506.81 | 29.21 | 0.01411444 | 22.32 | 0.02595455 | 9.5620 | 24.01 | 0.00833705 | 24.00 | 0.00833705 | 44.8725 | 3222.09 | 0.00 | 4874.85 | 3900.01 | 0.31379336 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.52 | 14.20 | 0.00996662 | 39787.2 | |
| SPLIT GN1 HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT GN1 | G N1 APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 7202.911 | 7202.911 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | SPLIT GN1 SUPPLY FAN | Fan:OnOff | 0.271433 | 0.32669536 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | Sensible | 7202.91 | 7202.91 | 1.0000 | 0.32669536 | 0.271433 | 18.06 | 12.43 | 0.00667090 | 35053.7 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 7202.91 | -10.70 | 0.00150390 | -10.70 | 0.02595455 | 9.5620 | 21.10 | 0.00721721 | 21.10 | 0.00721721 | 46.4100 | 1292.36 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT GN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT GN2 | G N2 APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 4873.477 | 3902.343 | 0.271245 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.3675 | 1004.8586 | 1.2036 | SPLIT GN2 SUPPLY FAN | Fan:OnOff | 0.271245 | 0.32646902 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | Sensible | 4808.82 | 4177.65 | 0.9867 | 0.32646902 | 0.271245 | 25.42 | 17.21 | 0.00889076 | 48202.1 | 12.80 | 11.59 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 303.824 | 4505.00 | 29.21 | 0.01411444 | 22.32 | 0.02595455 | 9.5687 | 24.01 | 0.00833804 | 24.00 | 0.00833804 | 44.8778 | 3220.11 | 0.00 | 4872.65 | 3897.84 | 0.31357596 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.52 | 14.20 | 0.00996582 | 39783.4 | |
| SPLIT GN2 HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT GN2 | G N2 APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 7198.612 | 7198.612 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | SPLIT GN2 SUPPLY FAN | Fan:OnOff | 0.271245 | 0.32646902 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | Sensible | 7198.61 | 7198.61 | 1.0000 | 0.32646902 | 0.271245 | 18.06 | 12.43 | 0.00667042 | 35050.3 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 7198.61 | -10.70 | 0.00150390 | -10.70 | 0.02595455 | 9.5687 | 21.10 | 0.00721710 | 21.10 | 0.00721710 | 46.4093 | 1292.14 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT GS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT GS1 | G S1 APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 5216.190 | 4177.791 | 0.292202 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.3044 | 1004.8586 | 1.2036 | SPLIT GS1 SUPPLY FAN | Fan:OnOff | 0.292202 | 0.35169325 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | Sensible | 5142.59 | 4489.10 | 0.9859 | 0.35169325 | 0.292202 | 25.40 | 17.17 | 0.00885681 | 48089.5 | 12.80 | 11.59 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 327.298 | 4815.29 | 29.21 | 0.01411444 | 22.32 | 0.02595455 | 8.8824 | 24.03 | 0.00834428 | 24.00 | 0.00834428 | 44.9113 | 3461.41 | 0.00 | 5215.30 | 4173.37 | 0.33780402 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.59 | 14.23 | 0.00997533 | 39883.5 | |
| SPLIT GS1 HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT GS1 | G S1 APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 7677.717 | 7677.717 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | SPLIT GS1 SUPPLY FAN | Fan:OnOff | 0.292202 | 0.35169325 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:50:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:50:00 | Sensible | 7677.72 | 7677.72 | 1.0000 | 0.35169325 | 0.292202 | 18.27 | 12.47 | 0.00662664 | 35161.2 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 7677.72 | -10.70 | 0.00150390 | -10.70 | 0.02595455 | 8.8824 | 21.10 | 0.00712602 | 21.10 | 0.00712602 | 45.8288 | 1403.59 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT GS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT GS2 | G S2 APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 5245.878 | 4198.027 | 0.294145 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.2945 | 1004.8586 | 1.2036 | SPLIT GS2 SUPPLY FAN | Fan:OnOff | 0.294145 | 0.35403198 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | Sensible | 5171.21 | 4517.53 | 0.9858 | 0.35403198 | 0.294145 | 25.40 | 17.17 | 0.00885149 | 48073.0 | 12.80 | 11.59 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 329.475 | 4841.73 | 29.21 | 0.01411444 | 22.32 | 0.02595455 | 8.8237 | 24.03 | 0.00834216 | 24.00 | 0.00834216 | 44.9001 | 3483.70 | 0.00 | 5244.99 | 4193.72 | 0.34005039 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.62 | 14.24 | 0.00997256 | 39898.2 | |
| SPLIT GS2 HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT GS2 | G S2 APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 7722.135 | 7722.135 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | SPLIT GS2 SUPPLY FAN | Fan:OnOff | 0.294145 | 0.35403198 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:50:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:50:00 | Sensible | 7722.14 | 7722.14 | 1.0000 | 0.35403198 | 0.294145 | 18.29 | 12.49 | 0.00663401 | 35198.9 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 7722.14 | -10.70 | 0.00150390 | -10.70 | 0.02595455 | 8.8237 | 21.10 | 0.00713049 | 21.10 | 0.00713049 | 45.8572 | 1411.74 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT MSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT MSW | M SW APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 14460.983 | 11580.671 | 0.835966 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.9987 | 1004.8586 | 1.2036 | SPLIT MSW SUPPLY FAN | Fan:OnOff | 0.835966 | 1.00616462 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | Sensible | 14198.78 | 12694.03 | 0.9819 | 1.00616462 | 0.835966 | 25.28 | 17.00 | 0.00869239 | 47555.0 | 12.80 | 11.59 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 936.372 | 13262.41 | 29.21 | 0.01411444 | 22.32 | 0.05190911 | 6.2095 | 24.05 | 0.00833342 | 24.00 | 0.00833342 | 44.8539 | 19644.28 | 0.00 | 14458.52 | 11566.97 | 0.96642873 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.97 | 14.41 | 0.01001157 | 40361.6 | |
| SPLIT MSW HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT MSW | M SW APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 21108.009 | 21108.009 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | SPLIT MSW SUPPLY FAN | Fan:OnOff | 0.835966 | 1.00616462 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | Sensible | 21108.01 | 21108.01 | 1.0000 | 1.00616462 | 0.835966 | 19.12 | 12.64 | 0.00644204 | 35555.5 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 21108.01 | -10.70 | 0.00150390 | -10.70 | 0.05190911 | 6.2095 | 21.10 | 0.00676898 | 21.10 | 0.00676898 | 43.5631 | 8584.38 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT MNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT MNW | M NW APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 14047.722 | 11238.739 | 0.810271 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.0195 | 1004.8586 | 1.2036 | SPLIT MNW SUPPLY FAN | Fan:OnOff | 0.810271 | 0.97523858 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | Sensible | 13796.96 | 12314.43 | 0.9821 | 0.97523858 | 0.810271 | 25.29 | 17.01 | 0.00870359 | 47592.1 | 12.80 | 11.59 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 907.591 | 12889.36 | 29.21 | 0.01411444 | 22.32 | 0.05190911 | 6.4064 | 24.05 | 0.00833322 | 24.00 | 0.00833322 | 44.8527 | 19051.18 | 0.00 | 14045.33 | 11225.80 | 0.93672403 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.96 | 14.40 | 0.01000451 | 40328.3 | |
| SPLIT MNW HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT MNW | M NW APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 20520.325 | 20520.325 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | SPLIT MNW SUPPLY FAN | Fan:OnOff | 0.810271 | 0.97523858 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | Sensible | 20520.32 | 20520.32 | 1.0000 | 0.97523858 | 0.810271 | 19.06 | 12.66 | 0.00649177 | 35618.2 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 20520.32 | -10.70 | 0.00150390 | -10.70 | 0.05190911 | 6.4064 | 21.10 | 0.00683318 | 21.10 | 0.00683318 | 43.9711 | 8058.35 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT MSE COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT MSE | M SE APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 13368.005 | 10696.156 | 0.762479 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.1437 | 1004.8586 | 1.2036 | SPLIT MSE SUPPLY FAN | Fan:OnOff | 0.762479 | 0.91771641 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | Sensible | 13148.17 | 11618.35 | 0.9836 | 0.91771641 | 0.762479 | 25.31 | 17.07 | 0.00877040 | 47779.4 | 12.80 | 11.59 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 854.059 | 12294.11 | 29.21 | 0.01411444 | 22.32 | 0.05190911 | 6.8079 | 24.05 | 0.00838001 | 24.00 | 0.00838001 | 45.1017 | 17948.62 | 0.00 | 13365.73 | 10682.89 | 0.88147355 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.82 | 14.34 | 0.00999134 | 40159.4 | |
| SPLIT MSE HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT MSE | M SE APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 19427.965 | 19427.965 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | SPLIT MSE SUPPLY FAN | Fan:OnOff | 0.762479 | 0.91771641 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | Sensible | 19427.96 | 19427.96 | 1.0000 | 0.91771641 | 0.762479 | 18.93 | 12.52 | 0.00640680 | 35272.6 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 19427.96 | -10.70 | 0.00150390 | -10.70 | 0.05190911 | 6.8079 | 21.10 | 0.00676497 | 21.10 | 0.00676497 | 43.5376 | 8550.05 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT MNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT MNE | M NE APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 12962.939 | 10372.791 | 0.737367 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.1698 | 1004.8586 | 1.2036 | SPLIT MNE SUPPLY FAN | Fan:OnOff | 0.737367 | 0.88749137 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | Sensible | 12754.27 | 11247.41 | 0.9839 | 0.88749137 | 0.737367 | 25.32 | 17.09 | 0.00878441 | 47825.6 | 12.80 | 11.59 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 825.931 | 11928.34 | 29.21 | 0.01411444 | 22.32 | 0.05190911 | 7.0398 | 24.05 | 0.00838077 | 24.00 | 0.00838077 | 45.1056 | 17371.01 | 0.00 | 12960.73 | 10359.63 | 0.85244217 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.79 | 14.32 | 0.00998829 | 40118.1 | |
| SPLIT MNE HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT MNE | M NE APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 18853.621 | 18853.621 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | SPLIT MNE SUPPLY FAN | Fan:OnOff | 0.737367 | 0.88749137 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | Sensible | 18853.62 | 18853.62 | 1.0000 | 0.88749137 | 0.737367 | 18.86 | 12.54 | 0.00645428 | 35318.3 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 18853.62 | -10.70 | 0.00150390 | -10.70 | 0.05190911 | 7.0398 | 21.10 | 0.00682917 | 21.10 | 0.00682917 | 43.9455 | 8023.91 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT MN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT MN1 | M N1 APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 11620.379 | 9306.658 | 0.660432 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.1539 | 1004.8586 | 1.2036 | SPLIT MN1 SUPPLY FAN | Fan:OnOff | 0.660432 | 0.79489205 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | Sensible | 11434.83 | 10099.80 | 0.9840 | 0.79489205 | 0.660432 | 25.36 | 17.09 | 0.00877588 | 47841.8 | 12.80 | 11.59 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 739.755 | 10695.08 | 29.21 | 0.01411444 | 22.32 | 0.05190911 | 7.8599 | 24.04 | 0.00832048 | 24.00 | 0.00832048 | 44.7846 | 15605.12 | 0.00 | 11618.40 | 9296.47 | 0.76349982 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.77 | 14.32 | 0.00999229 | 40105.1 | |
| SPLIT MN1 HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT MN1 | M N1 APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 17093.989 | 17093.989 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | SPLIT MN1 SUPPLY FAN | Fan:OnOff | 0.660432 | 0.79489205 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | Sensible | 17093.99 | 17093.99 | 1.0000 | 0.79489205 | 0.660432 | 18.60 | 12.38 | 0.00639678 | 34908.3 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 17093.99 | -10.70 | 0.00150390 | -10.70 | 0.05190911 | 7.8599 | 21.10 | 0.00681416 | 21.10 | 0.00681416 | 43.8472 | 4352.20 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT MN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT MN2 | M N2 APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 11598.216 | 9287.477 | 0.658937 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.1578 | 1004.8586 | 1.2036 | SPLIT MN2 SUPPLY FAN | Fan:OnOff | 0.658937 | 0.79309300 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | Sensible | 11413.55 | 10077.87 | 0.9841 | 0.79309300 | 0.658937 | 25.36 | 17.10 | 0.00877798 | 47847.8 | 12.80 | 11.59 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 738.080 | 10675.47 | 29.21 | 0.01411444 | 22.32 | 0.05190911 | 7.8777 | 24.04 | 0.00832164 | 24.00 | 0.00832164 | 44.7907 | 15570.39 | 0.00 | 11596.24 | 9277.32 | 0.76177182 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.77 | 14.31 | 0.00999113 | 40099.7 | |
| SPLIT MN2 HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT MN2 | M N2 APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 17059.819 | 17059.819 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | SPLIT MN2 SUPPLY FAN | Fan:OnOff | 0.658937 | 0.79309300 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | Sensible | 17059.82 | 17059.82 | 1.0000 | 0.79309300 | 0.658937 | 18.59 | 12.37 | 0.00639565 | 34899.7 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 17059.82 | -10.70 | 0.00150390 | -10.70 | 0.05190911 | 7.8777 | 21.10 | 0.00681397 | 21.10 | 0.00681397 | 43.8460 | 4351.29 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT MS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT MS1 | M S1 APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 12103.841 | 9685.483 | 0.690510 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.1185 | 1004.8586 | 1.2036 | SPLIT MS1 SUPPLY FAN | Fan:OnOff | 0.690510 | 0.83109430 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | Sensible | 11904.72 | 10543.82 | 0.9835 | 0.83109430 | 0.690510 | 25.34 | 17.07 | 0.00875682 | 47777.6 | 12.80 | 11.59 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 773.446 | 11131.28 | 29.21 | 0.01411444 | 22.32 | 0.05190911 | 7.5175 | 24.04 | 0.00832133 | 24.00 | 0.00832133 | 44.7893 | 16295.40 | 0.00 | 12101.78 | 9673.46 | 0.79827236 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.83 | 14.34 | 0.00999197 | 40162.4 | |
| SPLIT MS1 HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT MS1 | M S1 APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 17781.819 | 17781.819 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | SPLIT MS1 SUPPLY FAN | Fan:OnOff | 0.690510 | 0.83109430 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | Sensible | 17781.82 | 17781.82 | 1.0000 | 0.83109430 | 0.690510 | 18.71 | 12.33 | 0.00631011 | 34799.0 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 17781.82 | -10.70 | 0.00150390 | -10.70 | 0.05190911 | 7.5175 | 21.10 | 0.00670078 | 21.10 | 0.00670078 | 43.1262 | 4864.74 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT MS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT MS2 | M S2 APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 12080.749 | 9665.460 | 0.688939 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.1225 | 1004.8586 | 1.2036 | SPLIT MS2 SUPPLY FAN | Fan:OnOff | 0.688939 | 0.82920317 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | Sensible | 11882.57 | 10520.89 | 0.9836 | 0.82920317 | 0.688939 | 25.34 | 17.07 | 0.00875895 | 47783.8 | 12.80 | 11.59 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 771.686 | 11110.89 | 29.21 | 0.01411444 | 22.32 | 0.05190911 | 7.5346 | 24.04 | 0.00832255 | 24.00 | 0.00832255 | 44.7958 | 16259.36 | 0.00 | 12078.69 | 9653.49 | 0.79645591 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.82 | 14.34 | 0.00999079 | 40156.8 | |
| SPLIT MS2 HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT MS2 | M S2 APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 17745.899 | 17745.899 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | SPLIT MS2 SUPPLY FAN | Fan:OnOff | 0.688939 | 0.82920317 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | Sensible | 17745.90 | 17745.90 | 1.0000 | 0.82920317 | 0.688939 | 18.70 | 12.33 | 0.00630904 | 34790.7 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 17745.90 | -10.70 | 0.00150390 | -10.70 | 0.05190911 | 7.5346 | 21.10 | 0.00670059 | 21.10 | 0.00670059 | 43.1250 | 4863.84 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT TSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT TSW | T SW APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 7867.616 | 6299.557 | 0.454650 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.0156 | 1004.8586 | 1.2036 | SPLIT TSW SUPPLY FAN | Fan:OnOff | 0.454650 | 0.54721399 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | Sensible | 7725.24 | 6896.05 | 0.9819 | 0.54721399 | 0.454650 | 25.27 | 17.00 | 0.00870148 | 47560.2 | 12.80 | 11.59 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 509.257 | 7215.98 | 29.21 | 0.01411444 | 22.32 | 0.02595455 | 5.7087 | 24.06 | 0.00837376 | 24.00 | 0.00837376 | 45.0687 | 5337.85 | 0.00 | 7866.28 | 6292.14 | 0.52560318 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.97 | 14.41 | 0.01001042 | 40356.2 | |
| SPLIT TSW HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT TSW | T SW APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 11392.799 | 11392.799 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | SPLIT TSW SUPPLY FAN | Fan:OnOff | 0.454650 | 0.54721399 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | Sensible | 11392.80 | 11392.80 | 1.0000 | 0.54721399 | 0.454650 | 19.28 | 12.90 | 0.00665075 | 36245.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 11392.80 | -10.70 | 0.00150390 | -10.70 | 0.02595455 | 5.7087 | 21.10 | 0.00696235 | 21.10 | 0.00696235 | 44.7967 | 3489.27 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT TNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT TNW | T NW APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 7797.781 | 6244.915 | 0.450823 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.0084 | 1004.8586 | 1.2036 | SPLIT TNW SUPPLY FAN | Fan:OnOff | 0.450823 | 0.54260878 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | Sensible | 7656.23 | 6838.65 | 0.9818 | 0.54260878 | 0.450823 | 25.27 | 17.00 | 0.00869758 | 47552.6 | 12.80 | 11.59 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 504.971 | 7151.26 | 29.21 | 0.01411444 | 22.32 | 0.02595455 | 5.7571 | 24.06 | 0.00836667 | 24.00 | 0.00836667 | 45.0309 | 5293.84 | 0.00 | 7796.45 | 6237.52 | 0.52117984 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.97 | 14.41 | 0.01001189 | 40363.1 | |
| SPLIT TNW HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT TNW | T NW APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 11305.173 | 11305.173 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | SPLIT TNW SUPPLY FAN | Fan:OnOff | 0.450823 | 0.54260878 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | Sensible | 11305.17 | 11305.17 | 1.0000 | 0.54260878 | 0.450823 | 19.27 | 12.94 | 0.00669067 | 36331.7 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 11305.17 | -10.70 | 0.00150390 | -10.70 | 0.02595455 | 5.7571 | 21.10 | 0.00700752 | 21.10 | 0.00700752 | 45.0833 | 3353.18 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT TSE COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT TSE | T SE APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 7056.706 | 5651.390 | 0.401017 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.1961 | 1004.8586 | 1.2036 | SPLIT TSE SUPPLY FAN | Fan:OnOff | 0.401017 | 0.48266193 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | Sensible | 6943.89 | 6109.46 | 0.9840 | 0.48266193 | 0.401017 | 25.30 | 17.09 | 0.00879858 | 47840.9 | 12.80 | 11.59 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 449.182 | 6494.71 | 29.21 | 0.01411444 | 22.32 | 0.02595455 | 6.4722 | 24.05 | 0.00843071 | 24.00 | 0.00843071 | 45.3715 | 4717.90 | 0.00 | 7055.51 | 5645.21 | 0.46360043 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.77 | 14.32 | 0.00999194 | 40103.5 | |
| SPLIT TSE HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT TSE | T SE APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 10166.589 | 10166.589 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | SPLIT TSE SUPPLY FAN | Fan:OnOff | 0.401017 | 0.48266193 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | Sensible | 10166.59 | 10166.59 | 1.0000 | 0.48266193 | 0.401017 | 19.04 | 12.76 | 0.00660630 | 35886.2 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10166.59 | -10.70 | 0.00150390 | -10.70 | 0.02595455 | 6.4722 | 21.10 | 0.00695939 | 21.10 | 0.00695939 | 44.7778 | 3477.43 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT TNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT TNE | T NE APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 6984.408 | 5587.734 | 0.397110 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.1881 | 1004.8586 | 1.2036 | SPLIT TNE SUPPLY FAN | Fan:OnOff | 0.397110 | 0.47795981 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | Sensible | 6872.31 | 6050.54 | 0.9840 | 0.47795981 | 0.397110 | 25.30 | 17.09 | 0.00879425 | 47832.5 | 12.80 | 11.59 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 444.806 | 6427.50 | 29.21 | 0.01411444 | 22.32 | 0.02595455 | 6.5359 | 24.05 | 0.00842221 | 24.00 | 0.00842221 | 45.3261 | 4672.57 | 0.00 | 6983.22 | 5580.66 | 0.45908401 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.79 | 14.32 | 0.00998681 | 40111.2 | |
| SPLIT TNE HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT TNE | T NE APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 10077.140 | 10077.140 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | SPLIT TNE SUPPLY FAN | Fan:OnOff | 0.397110 | 0.47795981 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | Sensible | 10077.14 | 10077.14 | 1.0000 | 0.47795981 | 0.397110 | 19.02 | 12.79 | 0.00664505 | 35964.1 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10077.14 | -10.70 | 0.00150390 | -10.70 | 0.02595455 | 6.5359 | 21.10 | 0.00700457 | 21.10 | 0.00700457 | 45.0645 | 3341.28 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT TN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT TN1 | T N1 APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 6449.176 | 5162.716 | 0.370381 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.0504 | 1004.8586 | 1.2036 | SPLIT TN1 SUPPLY FAN | Fan:OnOff | 0.370381 | 0.44578842 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | Sensible | 6337.63 | 5643.61 | 0.9827 | 0.44578842 | 0.370381 | 25.32 | 17.03 | 0.00872018 | 47665.3 | 12.80 | 11.59 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 414.866 | 5922.77 | 29.21 | 0.01411444 | 22.32 | 0.02595455 | 7.0075 | 24.05 | 0.00831369 | 24.00 | 0.00831369 | 44.7485 | 4364.27 | 0.00 | 6448.08 | 5156.50 | 0.42818315 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.90 | 14.37 | 0.01000199 | 40263.2 | |
| SPLIT TN1 HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT TN1 | T N1 APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 9465.448 | 9465.448 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | SPLIT TN1 SUPPLY FAN | Fan:OnOff | 0.370381 | 0.44578842 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | Sensible | 9465.45 | 9465.45 | 1.0000 | 0.44578842 | 0.370381 | 18.87 | 12.82 | 0.00673842 | 36049.7 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9465.45 | -10.70 | 0.00150390 | -10.70 | 0.02595455 | 7.0075 | 21.10 | 0.00713287 | 21.10 | 0.00713287 | 45.8766 | 2226.11 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT TN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT TN2 | T N2 APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 6419.956 | 5137.713 | 0.368438 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.0579 | 1004.8586 | 1.2036 | SPLIT TN2 SUPPLY FAN | Fan:OnOff | 0.368438 | 0.44344991 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | Sensible | 6309.50 | 5615.15 | 0.9828 | 0.44344991 | 0.368438 | 25.33 | 17.04 | 0.00872425 | 47677.4 | 12.80 | 11.59 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 412.690 | 5896.81 | 29.21 | 0.01411444 | 22.32 | 0.02595455 | 7.0445 | 24.05 | 0.00831576 | 24.00 | 0.00831576 | 44.7595 | 4341.88 | 0.00 | 6418.86 | 5131.57 | 0.42593699 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.89 | 14.37 | 0.00999970 | 40252.4 | |
| SPLIT TN2 HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT TN2 | T N2 APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 9421.031 | 9421.031 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | SPLIT TN2 SUPPLY FAN | Fan:OnOff | 0.368438 | 0.44344991 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | Sensible | 9421.03 | 9421.03 | 1.0000 | 0.44344991 | 0.368438 | 18.86 | 12.82 | 0.00673623 | 36032.2 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9421.03 | -10.70 | 0.00150390 | -10.70 | 0.02595455 | 7.0445 | 21.10 | 0.00713276 | 21.10 | 0.00713276 | 45.8759 | 2225.77 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT TS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT TS1 | T S1 APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 6539.894 | 5234.204 | 0.375404 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.0592 | 1004.8586 | 1.2036 | SPLIT TS1 SUPPLY FAN | Fan:OnOff | 0.375404 | 0.45183496 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | Sensible | 6427.17 | 5719.05 | 0.9828 | 0.45183496 | 0.375404 | 25.32 | 17.04 | 0.00872493 | 47673.4 | 12.80 | 11.59 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 420.494 | 6006.68 | 29.21 | 0.01411444 | 22.32 | 0.02595455 | 6.9138 | 24.05 | 0.00832464 | 24.00 | 0.00832464 | 44.8068 | 4422.34 | 0.00 | 6538.78 | 5227.93 | 0.43399089 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.90 | 14.37 | 0.01000041 | 40255.8 | |
| SPLIT TS1 HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT TS1 | T S1 APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 9580.425 | 9580.425 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | SPLIT TS1 SUPPLY FAN | Fan:OnOff | 0.375404 | 0.45183496 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | Sensible | 9580.42 | 9580.42 | 1.0000 | 0.45183496 | 0.375404 | 18.90 | 12.77 | 0.00667463 | 35918.0 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9580.42 | -10.70 | 0.00150390 | -10.70 | 0.02595455 | 6.9138 | 21.10 | 0.00705867 | 21.10 | 0.00705867 | 45.4056 | 2362.19 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT TS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT TS2 | T S2 APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 6510.873 | 5209.343 | 0.373470 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.0668 | 1004.8586 | 1.2036 | SPLIT TS2 SUPPLY FAN | Fan:OnOff | 0.373470 | 0.44950686 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | Sensible | 6399.24 | 5690.72 | 0.9829 | 0.44950686 | 0.373470 | 25.32 | 17.04 | 0.00872902 | 47685.4 | 12.80 | 11.59 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 418.327 | 5980.91 | 29.21 | 0.01411444 | 22.32 | 0.02595455 | 6.9496 | 24.05 | 0.00832680 | 24.00 | 0.00832680 | 44.8184 | 4400.03 | 0.00 | 6509.77 | 5203.14 | 0.43175473 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.89 | 14.37 | 0.00999811 | 40244.9 | |
| SPLIT TS2 HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT TS2 | T S2 APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 9536.204 | 9536.204 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | SPLIT TS2 SUPPLY FAN | Fan:OnOff | 0.373470 | 0.44950686 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | Sensible | 9536.20 | 9536.20 | 1.0000 | 0.44950686 | 0.373470 | 18.89 | 12.77 | 0.00667254 | 35901.1 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9536.20 | -10.70 | 0.00150390 | -10.70 | 0.02595455 | 6.9496 | 21.10 | 0.00705856 | 21.10 | 0.00705856 | 45.4049 | 2361.86 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 09:15:04
Economizer| High Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
| None |
| Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
| None |
| Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
| G SW APARTMENT | 3607.00 | 4260.50 | 2228.50 |
| G NW APARTMENT | 5600.17 | 6363.33 | 3842.50 |
| OFFICE | 1246.50 | 943.33 | 569.83 |
| G NE APARTMENT | 5597.83 | 6347.67 | 3863.83 |
| G N1 APARTMENT | 5112.00 | 6392.50 | 3500.67 |
| G N2 APARTMENT | 5110.00 | 6393.33 | 3499.83 |
| G S1 APARTMENT | 3060.17 | 4187.33 | 1720.50 |
| G S2 APARTMENT | 3274.00 | 4044.67 | 1769.83 |
| M SW APARTMENT | 3049.67 | 3792.67 | 1443.17 |
| M NW APARTMENT | 4915.83 | 5655.00 | 2788.33 |
| M SE APARTMENT | 3030.67 | 3864.83 | 1490.67 |
| M NE APARTMENT | 4897.00 | 5653.17 | 2803.00 |
| M N1 APARTMENT | 4152.83 | 5631.00 | 2242.33 |
| M N2 APARTMENT | 4152.00 | 5630.50 | 2243.50 |
| M S1 APARTMENT | 2478.67 | 3651.67 | 970.33 |
| M S2 APARTMENT | 2476.33 | 3654.17 | 972.50 |
| T SW APARTMENT | 3894.00 | 4484.83 | 2659.83 |
| T NW APARTMENT | 5901.00 | 6323.67 | 4031.33 |
| T SE APARTMENT | 3888.33 | 4534.33 | 2712.83 |
| T NE APARTMENT | 5903.50 | 6293.33 | 4037.67 |
| T N1 APARTMENT | 5536.33 | 6284.83 | 3773.83 |
| T N2 APARTMENT | 5533.33 | 6284.00 | 3774.00 |
| T S1 APARTMENT | 3548.50 | 4366.33 | 2328.17 |
| T S2 APARTMENT | 3550.50 | 4370.67 | 2334.00 |
| T CORRIDOR | 6421.33 | 8673.17 | 6386.83 |
| G CORRIDOR | 6727.33 | 7545.67 | 5745.17 |
| M CORRIDOR | 6550.00 | 8639.33 | 6445.17 |
| Facility | 8755.17 | 8760.00 | 8699.00 |
| During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
| G SW APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| G NW APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| OFFICE | 0.00 | 0.00 | 0.00 | 0.00 |
| G NE APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| G N1 APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| G N2 APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| G S1 APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| G S2 APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| M SW APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| M NW APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| M SE APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| M NE APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| M N1 APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| M N2 APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| M S1 APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| M S2 APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| T SW APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| T NW APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| T SE APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| T NE APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| T N1 APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| T N2 APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| T S1 APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| T S2 APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| T CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
| G CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
| M CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
| Facility | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 09:15:04
Average Outdoor Air During Occupied Hours| Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
| G SW APARTMENT | 2.40 | 2.50 | 268.97 | 0.353 | 0.117 | 0.000 | 0.051 |
| G NW APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.123 | 0.000 | 0.065 |
| OFFICE | 4.75 | 4.75 | 268.97 | 0.518 | 0.133 | 0.000 | 0.000 |
| G NE APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.123 | 0.000 | 0.065 |
| G N1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.074 | 0.000 | 0.065 |
| G N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.074 | 0.000 | 0.065 |
| G S1 APARTMENT | 2.40 | 2.50 | 268.97 | 0.353 | 0.070 | 0.000 | 0.051 |
| G S2 APARTMENT | 2.40 | 2.50 | 268.97 | 0.353 | 0.070 | 0.000 | 0.051 |
| M SW APARTMENT | 2.40 | 2.50 | 268.97 | 0.353 | 0.168 | 0.000 | 0.064 |
| M NW APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.176 | 0.000 | 0.083 |
| M SE APARTMENT | 2.40 | 2.50 | 268.97 | 0.353 | 0.168 | 0.000 | 0.064 |
| M NE APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.176 | 0.000 | 0.083 |
| M N1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.106 | 0.000 | 0.083 |
| M N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.106 | 0.000 | 0.083 |
| M S1 APARTMENT | 2.40 | 2.50 | 268.97 | 0.353 | 0.101 | 0.000 | 0.064 |
| M S2 APARTMENT | 2.40 | 2.50 | 268.97 | 0.353 | 0.101 | 0.000 | 0.064 |
| T SW APARTMENT | 2.40 | 2.50 | 268.97 | 0.353 | 0.222 | 0.000 | 0.076 |
| T NW APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.233 | 0.000 | 0.099 |
| T SE APARTMENT | 2.40 | 2.50 | 268.97 | 0.353 | 0.222 | 0.000 | 0.076 |
| T NE APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.233 | 0.000 | 0.099 |
| T N1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.141 | 0.000 | 0.099 |
| T N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.141 | 0.000 | 0.099 |
| T S1 APARTMENT | 2.40 | 2.50 | 268.97 | 0.353 | 0.134 | 0.000 | 0.076 |
| T S2 APARTMENT | 2.40 | 2.50 | 268.97 | 0.353 | 0.134 | 0.000 | 0.076 |
| Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
| G SW APARTMENT | 2.40 | 2.50 | 268.97 | 0.339 | 0.000 | 0.000 | 0.000 |
| G NW APARTMENT | 1.71 | 2.50 | 268.97 | 0.338 | 0.000 | 0.000 | 0.000 |
| OFFICE | 4.75 | 4.75 | 268.97 | 0.492 | 0.000 | 0.000 | 0.000 |
| G NE APARTMENT | 1.71 | 2.50 | 268.97 | 0.338 | 0.000 | 0.000 | 0.000 |
| G N1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.338 | 0.000 | 0.000 | 0.000 |
| G N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.338 | 0.000 | 0.000 | 0.000 |
| G S1 APARTMENT | 2.40 | 2.50 | 268.97 | 0.339 | 0.000 | 0.000 | 0.000 |
| G S2 APARTMENT | 2.40 | 2.50 | 268.97 | 0.339 | 0.000 | 0.000 | 0.000 |
| M SW APARTMENT | 2.40 | 2.50 | 268.97 | 0.339 | 0.000 | 0.000 | 0.000 |
| M NW APARTMENT | 1.71 | 2.50 | 268.97 | 0.338 | 0.000 | 0.000 | 0.000 |
| M SE APARTMENT | 2.40 | 2.50 | 268.97 | 0.339 | 0.000 | 0.000 | 0.000 |
| M NE APARTMENT | 1.71 | 2.50 | 268.97 | 0.338 | 0.000 | 0.000 | 0.000 |
| M N1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.338 | 0.000 | 0.000 | 0.000 |
| M N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.338 | 0.000 | 0.000 | 0.000 |
| M S1 APARTMENT | 2.40 | 2.50 | 268.97 | 0.339 | 0.000 | 0.000 | 0.000 |
| M S2 APARTMENT | 2.40 | 2.50 | 268.97 | 0.339 | 0.000 | 0.000 | 0.000 |
| T SW APARTMENT | 2.40 | 2.50 | 268.97 | 0.338 | 0.000 | 0.000 | 0.000 |
| T NW APARTMENT | 1.71 | 2.50 | 268.97 | 0.338 | 0.000 | 0.000 | 0.000 |
| T SE APARTMENT | 2.40 | 2.50 | 268.97 | 0.338 | 0.000 | 0.000 | 0.000 |
| T NE APARTMENT | 1.71 | 2.50 | 268.97 | 0.338 | 0.000 | 0.000 | 0.000 |
| T N1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.338 | 0.000 | 0.000 | 0.000 |
| T N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.338 | 0.000 | 0.000 | 0.000 |
| T S1 APARTMENT | 2.40 | 2.50 | 268.97 | 0.339 | 0.000 | 0.000 | 0.000 |
| T S2 APARTMENT | 2.40 | 2.50 | 268.97 | 0.339 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 09:15:04
Mechanical Ventilation Parameters by Zone| AirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
| G SW APARTMENT | SPLIT GSW | 2.40 | 2.50 | 268.97 | 88.25 | 0.0260 | 0.026 |
| G NW APARTMENT | SPLIT GNW | 1.71 | 2.50 | 268.97 | 88.25 | 0.0260 | 0.026 |
| OFFICE | SPLIT OFFICE | 4.75 | 4.75 | 268.97 | 88.25 | 0.0381 | 0.038 |
| G NE APARTMENT | SPLIT GNE | 1.71 | 2.50 | 268.97 | 88.25 | 0.0260 | 0.026 |
| G N1 APARTMENT | SPLIT GN1 | 1.71 | 2.50 | 268.97 | 88.25 | 0.0260 | 0.026 |
| G N2 APARTMENT | SPLIT GN2 | 1.71 | 2.50 | 268.97 | 88.25 | 0.0260 | 0.026 |
| G S1 APARTMENT | SPLIT GS1 | 2.40 | 2.50 | 268.97 | 88.25 | 0.0260 | 0.026 |
| G S2 APARTMENT | SPLIT GS2 | 2.40 | 2.50 | 268.97 | 88.25 | 0.0260 | 0.026 |
| M SW APARTMENT | SPLIT MSW | 2.40 | 2.50 | 268.97 | 88.25 | 0.0519 | 0.052 |
| M NW APARTMENT | SPLIT MNW | 1.71 | 2.50 | 268.97 | 88.25 | 0.0519 | 0.052 |
| M SE APARTMENT | SPLIT MSE | 2.40 | 2.50 | 268.97 | 88.25 | 0.0519 | 0.052 |
| M NE APARTMENT | SPLIT MNE | 1.71 | 2.50 | 268.97 | 88.25 | 0.0519 | 0.052 |
| M N1 APARTMENT | SPLIT MN1 | 1.71 | 2.50 | 268.97 | 88.25 | 0.0519 | 0.052 |
| M N2 APARTMENT | SPLIT MN2 | 1.71 | 2.50 | 268.97 | 88.25 | 0.0519 | 0.052 |
| M S1 APARTMENT | SPLIT MS1 | 2.40 | 2.50 | 268.97 | 88.25 | 0.0519 | 0.052 |
| M S2 APARTMENT | SPLIT MS2 | 2.40 | 2.50 | 268.97 | 88.25 | 0.0519 | 0.052 |
| T SW APARTMENT | SPLIT TSW | 2.40 | 2.50 | 268.97 | 88.25 | 0.0260 | 0.026 |
| T NW APARTMENT | SPLIT TNW | 1.71 | 2.50 | 268.97 | 88.25 | 0.0260 | 0.026 |
| T SE APARTMENT | SPLIT TSE | 2.40 | 2.50 | 268.97 | 88.25 | 0.0260 | 0.026 |
| T NE APARTMENT | SPLIT TNE | 1.71 | 2.50 | 268.97 | 88.25 | 0.0260 | 0.026 |
| T N1 APARTMENT | SPLIT TN1 | 1.71 | 2.50 | 268.97 | 88.25 | 0.0260 | 0.026 |
| T N2 APARTMENT | SPLIT TN2 | 1.71 | 2.50 | 268.97 | 88.25 | 0.0260 | 0.026 |
| T S1 APARTMENT | SPLIT TS1 | 2.40 | 2.50 | 268.97 | 88.25 | 0.0260 | 0.026 |
| T S2 APARTMENT | SPLIT TS2 | 2.40 | 2.50 | 268.97 | 88.25 | 0.0260 | 0.026 |
| Total Facility | 68.19 | 82.25 | 8607.06 | 2823.98 | 0.8427 | 1.258 |
| Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
| G SW APARTMENT | 818502.78 | 152604.88 | 971107.66 | 284682.83 | 1255790.49 | 818502.78 | 0.00 | 7242.17 | 1517.83 | 2615.00 |
| G NW APARTMENT | 818502.78 | 148838.78 | 967341.56 | 284682.83 | 1252024.39 | 818502.78 | 0.00 | 7242.17 | 1517.83 | 0.00 |
| OFFICE | 1201711.97 | 0.00 | 1201711.97 | 284682.83 | 1486394.80 | 1201711.97 | 0.00 | 8760.00 | 0.00 | 7010.00 |
| G NE APARTMENT | 818502.78 | 149141.65 | 967644.42 | 284682.83 | 1252327.25 | 818502.78 | 0.00 | 7242.17 | 1517.83 | 0.00 |
| G N1 APARTMENT | 818502.78 | 149167.60 | 967670.37 | 171713.46 | 1139383.83 | 818502.78 | 0.00 | 7242.17 | 1517.83 | 0.00 |
| G N2 APARTMENT | 818502.78 | 149181.05 | 967683.83 | 171713.46 | 1139397.28 | 818502.78 | 0.00 | 7242.17 | 1517.83 | 0.00 |
| G S1 APARTMENT | 818502.78 | 153046.77 | 971549.55 | 171713.46 | 1143263.01 | 818502.78 | 0.00 | 7242.17 | 1517.83 | 2615.00 |
| G S2 APARTMENT | 818502.78 | 153176.84 | 971679.62 | 171713.46 | 1143393.07 | 818502.78 | 0.00 | 7242.17 | 1517.83 | 2615.00 |
| M SW APARTMENT | 1637005.55 | 195117.77 | 1832123.33 | 409111.40 | 2241234.72 | 1637005.55 | 0.00 | 7206.50 | 1553.50 | 2615.00 |
| M NW APARTMENT | 1637005.55 | 190631.44 | 1827637.00 | 409111.40 | 2236748.40 | 1637005.55 | 0.00 | 7206.50 | 1553.50 | 0.00 |
| M SE APARTMENT | 1637005.55 | 195186.95 | 1832192.51 | 409111.40 | 2241303.91 | 1637005.55 | 0.00 | 7206.50 | 1553.50 | 2615.00 |
| M NE APARTMENT | 1637005.55 | 190821.80 | 1827827.35 | 409111.40 | 2236938.75 | 1637005.55 | 0.00 | 7206.50 | 1553.50 | 0.00 |
| M N1 APARTMENT | 1637005.55 | 190779.38 | 1827784.94 | 246765.61 | 2074550.55 | 1637005.55 | 0.00 | 7206.50 | 1553.50 | 0.00 |
| M N2 APARTMENT | 1637005.55 | 190792.27 | 1827797.82 | 246765.61 | 2074563.43 | 1637005.55 | 0.00 | 7206.50 | 1553.50 | 0.00 |
| M S1 APARTMENT | 1637005.55 | 195235.57 | 1832241.12 | 246765.61 | 2079006.73 | 1637005.55 | 0.00 | 7206.50 | 1553.50 | 2615.00 |
| M S2 APARTMENT | 1637005.55 | 195238.32 | 1832243.87 | 246765.61 | 2079009.48 | 1637005.55 | 0.00 | 7206.50 | 1553.50 | 2615.00 |
| T SW APARTMENT | 818502.78 | 232793.18 | 1051295.96 | 541170.96 | 1592466.92 | 818502.78 | 0.00 | 7241.50 | 1518.50 | 2615.00 |
| T NW APARTMENT | 818502.78 | 226628.72 | 1045131.50 | 541170.96 | 1586302.46 | 818502.78 | 0.00 | 7241.50 | 1518.50 | 0.00 |
| T SE APARTMENT | 818502.78 | 233183.47 | 1051686.25 | 541170.96 | 1592857.21 | 818502.78 | 0.00 | 7241.50 | 1518.50 | 2615.00 |
| T NE APARTMENT | 818502.78 | 227228.59 | 1045731.37 | 541170.96 | 1586902.34 | 818502.78 | 0.00 | 7241.50 | 1518.50 | 0.00 |
| T N1 APARTMENT | 818502.78 | 226967.58 | 1045470.36 | 326420.59 | 1371890.94 | 818502.78 | 0.00 | 7241.50 | 1518.50 | 0.00 |
| T N2 APARTMENT | 818502.78 | 227008.26 | 1045511.03 | 326420.59 | 1371931.62 | 818502.78 | 0.00 | 7241.50 | 1518.50 | 0.00 |
| T S1 APARTMENT | 818502.78 | 233202.42 | 1051705.19 | 326420.59 | 1378125.78 | 818502.78 | 0.00 | 7241.50 | 1518.50 | 2615.00 |
| T S2 APARTMENT | 818502.78 | 233220.30 | 1051723.08 | 326420.59 | 1378143.66 | 818502.78 | 0.00 | 7241.50 | 1518.50 | 2615.00 |
| Total Facility | 39671342.50 | 5982997.09 | 45654339.59 | 10542967.42 | 56197307.01 | 39671342.50 | 0.00 | 8760.00 | 1555.00 | 8760.00 |
| Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
| G SW APARTMENT | 0.0260 | 0.0037 | 0.0297 | 0.0086 | 0.0383 | 0.0260 | 0.00 | 5301.17 | 843.83 |
| G NW APARTMENT | 0.0260 | 0.0047 | 0.0307 | 0.0090 | 0.0397 | 0.0260 | 0.00 | 7242.17 | 1517.83 |
| OFFICE | 0.0381 | 0.0000 | 0.0381 | 0.0098 | 0.0479 | 0.0381 | 0.00 | 1750.00 | 0.00 |
| G NE APARTMENT | 0.0260 | 0.0047 | 0.0307 | 0.0090 | 0.0397 | 0.0260 | 0.00 | 7242.17 | 1517.83 |
| G N1 APARTMENT | 0.0260 | 0.0047 | 0.0307 | 0.0054 | 0.0361 | 0.0260 | 0.00 | 7242.17 | 1517.83 |
| G N2 APARTMENT | 0.0260 | 0.0047 | 0.0307 | 0.0054 | 0.0361 | 0.0260 | 0.00 | 7242.17 | 1517.83 |
| G S1 APARTMENT | 0.0260 | 0.0037 | 0.0297 | 0.0052 | 0.0349 | 0.0260 | 0.00 | 5301.17 | 843.83 |
| G S2 APARTMENT | 0.0260 | 0.0037 | 0.0297 | 0.0052 | 0.0349 | 0.0260 | 0.00 | 5301.17 | 843.83 |
| M SW APARTMENT | 0.0519 | 0.0047 | 0.0566 | 0.0123 | 0.0689 | 0.0519 | 0.00 | 5277.17 | 867.83 |
| M NW APARTMENT | 0.0519 | 0.0060 | 0.0580 | 0.0130 | 0.0709 | 0.0519 | 0.00 | 7206.50 | 1553.50 |
| M SE APARTMENT | 0.0519 | 0.0047 | 0.0566 | 0.0123 | 0.0689 | 0.0519 | 0.00 | 5277.17 | 867.83 |
| M NE APARTMENT | 0.0519 | 0.0061 | 0.0580 | 0.0130 | 0.0709 | 0.0519 | 0.00 | 7206.50 | 1553.50 |
| M N1 APARTMENT | 0.0519 | 0.0060 | 0.0580 | 0.0078 | 0.0658 | 0.0519 | 0.00 | 7206.50 | 1553.50 |
| M N2 APARTMENT | 0.0519 | 0.0060 | 0.0580 | 0.0078 | 0.0658 | 0.0519 | 0.00 | 7206.50 | 1553.50 |
| M S1 APARTMENT | 0.0519 | 0.0047 | 0.0566 | 0.0074 | 0.0641 | 0.0519 | 0.00 | 5277.17 | 867.83 |
| M S2 APARTMENT | 0.0519 | 0.0047 | 0.0566 | 0.0074 | 0.0641 | 0.0519 | 0.00 | 5277.17 | 867.83 |
| T SW APARTMENT | 0.0260 | 0.0055 | 0.0315 | 0.0163 | 0.0478 | 0.0260 | 0.00 | 5298.83 | 846.17 |
| T NW APARTMENT | 0.0260 | 0.0072 | 0.0331 | 0.0172 | 0.0503 | 0.0260 | 0.00 | 7241.50 | 1518.50 |
| T SE APARTMENT | 0.0260 | 0.0056 | 0.0315 | 0.0163 | 0.0478 | 0.0260 | 0.00 | 5298.83 | 846.17 |
| T NE APARTMENT | 0.0260 | 0.0072 | 0.0332 | 0.0172 | 0.0503 | 0.0260 | 0.00 | 7241.50 | 1518.50 |
| T N1 APARTMENT | 0.0260 | 0.0072 | 0.0332 | 0.0104 | 0.0435 | 0.0260 | 0.00 | 7241.50 | 1518.50 |
| T N2 APARTMENT | 0.0260 | 0.0072 | 0.0332 | 0.0104 | 0.0435 | 0.0260 | 0.00 | 7241.50 | 1518.50 |
| T S1 APARTMENT | 0.0260 | 0.0056 | 0.0315 | 0.0098 | 0.0414 | 0.0260 | 0.00 | 5298.83 | 846.17 |
| T S2 APARTMENT | 0.0260 | 0.0056 | 0.0315 | 0.0098 | 0.0414 | 0.0260 | 0.00 | 5298.83 | 846.17 |
| Total Facility | 1.2580 | 0.1671 | 1.4250 | 0.3274 | 1.7524 | 1.2580 | 0.00 | 8760.00 | 1555.00 |
| Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
| SPLIT GSW | 0.00 | 152604.88 | 152604.88 | 818502.78 | 7848.83 | 42.50 | 868.67 | 674.00 |
| SPLIT GNW | 0.00 | 148838.78 | 148838.78 | 818502.78 | 7870.83 | 51.89 | 837.28 | 0.00 |
| SPLIT OFFICE | 1740849.09 | 0.00 | 1740849.09 | 1201711.97 | 0.00 | 0.00 | 8760.00 | 7010.00 |
| SPLIT GNE | 0.00 | 149141.65 | 149141.65 | 818502.78 | 7861.08 | 54.92 | 844.00 | 0.00 |
| SPLIT GN1 | 0.00 | 149167.60 | 149167.60 | 818502.78 | 7866.29 | 52.10 | 841.61 | 0.00 |
| SPLIT GN2 | 0.00 | 149181.05 | 149181.05 | 818502.78 | 7865.79 | 52.43 | 841.78 | 0.00 |
| SPLIT GS1 | 0.00 | 153046.77 | 153046.77 | 818502.78 | 7842.00 | 42.33 | 875.67 | 674.00 |
| SPLIT GS2 | 0.00 | 153176.84 | 153176.84 | 818502.78 | 7839.83 | 43.00 | 877.17 | 674.00 |
| SPLIT MSW | 0.00 | 195117.77 | 195117.77 | 1637005.55 | 8622.00 | 15.00 | 123.00 | 685.67 |
| SPLIT MNW | 0.00 | 190631.44 | 190631.44 | 1637005.55 | 8642.05 | 14.45 | 103.50 | 0.00 |
| SPLIT MSE | 0.00 | 195186.95 | 195186.95 | 1637005.55 | 8621.56 | 15.11 | 123.33 | 685.67 |
| SPLIT MNE | 0.00 | 190821.80 | 190821.80 | 1637005.55 | 8641.33 | 14.00 | 104.67 | 0.00 |
| SPLIT MN1 | 0.00 | 190779.38 | 190779.38 | 1637005.55 | 8642.00 | 14.36 | 103.64 | 0.00 |
| SPLIT MN2 | 0.00 | 190792.27 | 190792.27 | 1637005.55 | 8641.83 | 14.19 | 103.97 | 0.00 |
| SPLIT MS1 | 0.00 | 195235.57 | 195235.57 | 1637005.55 | 8621.17 | 15.42 | 123.42 | 685.67 |
| SPLIT MS2 | 0.00 | 195238.32 | 195238.32 | 1637005.55 | 8621.17 | 15.42 | 123.42 | 685.67 |
| SPLIT TSW | 0.00 | 232793.18 | 232793.18 | 818502.78 | 7389.88 | 15.54 | 1354.58 | 672.33 |
| SPLIT TNW | 0.00 | 226628.72 | 226628.72 | 818502.78 | 7418.67 | 12.92 | 1328.42 | 0.00 |
| SPLIT TSE | 0.00 | 233183.47 | 233183.47 | 818502.78 | 7388.33 | 15.23 | 1356.44 | 672.33 |
| SPLIT TNE | 0.00 | 227228.59 | 227228.59 | 818502.78 | 7414.17 | 13.00 | 1332.83 | 0.00 |
| SPLIT TN1 | 0.00 | 226967.58 | 226967.58 | 818502.78 | 7416.17 | 13.92 | 1329.92 | 0.00 |
| SPLIT TN2 | 0.00 | 227008.26 | 227008.26 | 818502.78 | 7416.17 | 13.25 | 1330.58 | 0.00 |
| SPLIT TS1 | 0.00 | 233202.42 | 233202.42 | 818502.78 | 7388.67 | 14.10 | 1357.23 | 672.33 |
| SPLIT TS2 | 0.00 | 233220.30 | 233220.30 | 818502.78 | 7388.67 | 14.10 | 1357.23 | 672.33 |
| Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
| SPLIT GSW | 0.0000 | 0.0037 | 0.0037 | 0.0260 | 5678.17 | 24.67 | 442.17 |
| SPLIT GNW | 0.0000 | 0.0047 | 0.0047 | 0.0260 | 7870.83 | 51.89 | 837.28 |
| SPLIT OFFICE | 0.0552 | 0.0000 | 0.0552 | 0.0381 | 0.00 | 0.00 | 1750.00 |
| SPLIT GNE | 0.0000 | 0.0047 | 0.0047 | 0.0260 | 7861.08 | 54.92 | 844.00 |
| SPLIT GN1 | 0.0000 | 0.0047 | 0.0047 | 0.0260 | 7866.29 | 52.10 | 841.61 |
| SPLIT GN2 | 0.0000 | 0.0047 | 0.0047 | 0.0260 | 7865.79 | 52.43 | 841.78 |
| SPLIT GS1 | 0.0000 | 0.0037 | 0.0037 | 0.0260 | 5677.00 | 24.17 | 443.83 |
| SPLIT GS2 | 0.0000 | 0.0037 | 0.0037 | 0.0260 | 5676.50 | 24.17 | 444.33 |
| SPLIT MSW | 0.0000 | 0.0047 | 0.0047 | 0.0519 | 6089.00 | 6.67 | 49.33 |
| SPLIT MNW | 0.0000 | 0.0060 | 0.0060 | 0.0519 | 8642.05 | 14.45 | 103.50 |
| SPLIT MSE | 0.0000 | 0.0047 | 0.0047 | 0.0519 | 6088.56 | 7.11 | 49.33 |
| SPLIT MNE | 0.0000 | 0.0061 | 0.0061 | 0.0519 | 8641.33 | 14.00 | 104.67 |
| SPLIT MN1 | 0.0000 | 0.0060 | 0.0060 | 0.0519 | 8642.00 | 14.36 | 103.64 |
| SPLIT MN2 | 0.0000 | 0.0060 | 0.0060 | 0.0519 | 8641.83 | 14.19 | 103.97 |
| SPLIT MS1 | 0.0000 | 0.0047 | 0.0047 | 0.0519 | 6088.67 | 6.92 | 49.42 |
| SPLIT MS2 | 0.0000 | 0.0047 | 0.0047 | 0.0519 | 6088.67 | 6.92 | 49.42 |
| SPLIT TSW | 0.0000 | 0.0055 | 0.0055 | 0.0260 | 5403.43 | 10.82 | 730.75 |
| SPLIT TNW | 0.0000 | 0.0072 | 0.0072 | 0.0260 | 7418.67 | 12.92 | 1328.42 |
| SPLIT TSE | 0.0000 | 0.0056 | 0.0056 | 0.0260 | 5403.00 | 10.48 | 731.52 |
| SPLIT TNE | 0.0000 | 0.0072 | 0.0072 | 0.0260 | 7414.17 | 13.00 | 1332.83 |
| SPLIT TN1 | 0.0000 | 0.0072 | 0.0072 | 0.0260 | 7416.17 | 13.92 | 1329.92 |
| SPLIT TN2 | 0.0000 | 0.0072 | 0.0072 | 0.0260 | 7416.17 | 13.25 | 1330.58 |
| SPLIT TS1 | 0.0000 | 0.0056 | 0.0056 | 0.0260 | 5403.17 | 9.43 | 732.40 |
| SPLIT TS2 | 0.0000 | 0.0056 | 0.0056 | 0.0260 | 5403.17 | 9.43 | 732.40 |
| No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
| SPLIT GSW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT GNW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT OFFICE | 0.00 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT GNE | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT GN1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT GN2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT GS1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT GS2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT MSW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT MNW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT MSE | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT MNE | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT MN1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT MN2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT MS1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT MS2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT TSW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT TNW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT TSE | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT TNE | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT TN1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT TN2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT TS1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT TS2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
| SPLIT GSW | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT GNW | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT OFFICE | 0.0000 | 0.0552 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT GNE | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT GN1 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT GN2 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT GS1 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT GS2 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT MSW | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT MNW | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT MSE | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT MNE | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT MN1 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT MN2 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT MS1 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT MS2 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT TSW | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT TNW | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT TSE | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT TNE | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT TN1 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT TN2 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT TS1 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT TS2 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 09:15:04
Surfaces by Class| Total | Outdoors | |
| Wall | 126 | 42 |
| Floor | 27 | 9 |
| Roof | 27 | 9 |
| Internal Mass | 24 | 0 |
| Building Detached Shading | 0 | 0 |
| Fixed Detached Shading | 0 | 0 |
| Window | 39 | 39 |
| Door | 0 | 0 |
| Glass Door | 0 | 0 |
| Shading | 0 | 0 |
| Overhang | 0 | 0 |
| Fin | 0 | 0 |
| Tubular Daylighting Device Dome | 0 | 0 |
| Tubular Daylighting Device Diffuser | 0 | 0 |
| Count | |
| HVAC Air Loops | 24 |
| Conditioned Zones | 24 |
| Unconditioned Zones | 3 |
| Supply Plenums | 0 |
| Return Plenums | 0 |
| Count | |
| IDF Objects | 1536 |
| Defaulted Fields | 1816 |
| Fields with Defaults | 5921 |
| Autosized Fields | 617 |
| Autosizable Fields | 759 |
| Autocalculated Fields | 331 |
| Autocalculatable Fields | 508 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 09:15:04
Annual and Peak Values - Electricity| Electricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
| Electricity:Facility | 1291.98 | 16944.45 | 17-APR-02:40 | 88325.42 | 19-JUN-17:40 |
| Electricity:Building | 557.89 | 10119.94 | 01-JAN-03:10 | 27841.36 | 01-JAN-18:10 |
| Electricity:Zone:G SW APARTMENT | 13.67 | 232.36 | 01-JAN-03:10 | 705.80 | 01-JAN-18:10 |
| Electricity:SpaceType:GENERAL | 557.89 | 10119.94 | 01-JAN-03:10 | 27841.36 | 01-JAN-18:10 |
| InteriorLights:Electricity | 99.23 | 1868.27 | 01-JAN-00:10 | 5904.43 | 01-JAN-19:10 |
| InteriorLights:Electricity:Zone:G SW APARTMENT | 1.45 | 8.68 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 |
| InteriorLights:Electricity:SpaceType:GENERAL | 99.23 | 1868.27 | 01-JAN-00:10 | 5904.43 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity | 94.96 | 1842.77 | 01-JAN-00:10 | 5496.56 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:G SW APARTMENT | 1.32 | 7.86 | 01-JAN-00:10 | 125.72 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 94.96 | 1842.77 | 01-JAN-00:10 | 5496.56 | 01-JAN-19:10 |
| Electricity:Zone:G NW APARTMENT | 13.67 | 232.36 | 01-JAN-03:10 | 705.80 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:G NW APARTMENT | 1.45 | 8.68 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:G NW APARTMENT | 1.32 | 7.86 | 01-JAN-00:10 | 125.72 | 01-JAN-19:10 |
| Electricity:Zone:OFFICE | 16.86 | 310.83 | 01-JAN-00:10 | 1171.54 | 03-JAN-08:10 |
| InteriorLights:Electricity:Zone:OFFICE | 7.40 | 116.58 | 01-JAN-00:10 | 582.92 | 03-JAN-08:10 |
| LightsWired:InteriorLights:Electricity:Zone:OFFICE | 7.40 | 116.58 | 01-JAN-00:10 | 582.92 | 03-JAN-08:10 |
| Electricity:Zone:G NE APARTMENT | 13.67 | 232.36 | 01-JAN-03:10 | 705.80 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:G NE APARTMENT | 1.45 | 8.68 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:G NE APARTMENT | 1.32 | 7.86 | 01-JAN-00:10 | 125.72 | 01-JAN-19:10 |
| Electricity:Zone:G N1 APARTMENT | 13.67 | 232.36 | 01-JAN-03:10 | 705.80 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:G N1 APARTMENT | 1.45 | 8.68 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:G N1 APARTMENT | 1.32 | 7.86 | 01-JAN-00:10 | 125.72 | 01-JAN-19:10 |
| Electricity:Zone:G N2 APARTMENT | 13.67 | 232.36 | 01-JAN-03:10 | 705.80 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:G N2 APARTMENT | 1.45 | 8.68 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:G N2 APARTMENT | 1.32 | 7.86 | 01-JAN-00:10 | 125.72 | 01-JAN-19:10 |
| Electricity:Zone:G S1 APARTMENT | 13.67 | 232.36 | 01-JAN-03:10 | 705.80 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:G S1 APARTMENT | 1.45 | 8.68 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:G S1 APARTMENT | 1.32 | 7.86 | 01-JAN-00:10 | 125.72 | 01-JAN-19:10 |
| Electricity:Zone:G S2 APARTMENT | 13.67 | 232.36 | 01-JAN-03:10 | 705.80 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:G S2 APARTMENT | 1.45 | 8.68 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:G S2 APARTMENT | 1.32 | 7.86 | 01-JAN-00:10 | 125.72 | 01-JAN-19:10 |
| Electricity:Zone:M SW APARTMENT | 27.33 | 464.72 | 01-JAN-03:10 | 1411.61 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:M SW APARTMENT | 2.91 | 17.37 | 01-JAN-00:10 | 277.76 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:M SW APARTMENT | 2.63 | 15.72 | 01-JAN-00:10 | 251.45 | 01-JAN-19:10 |
| Electricity:Zone:M NW APARTMENT | 27.33 | 464.72 | 01-JAN-03:10 | 1411.61 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:M NW APARTMENT | 2.91 | 17.37 | 01-JAN-00:10 | 277.76 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:M NW APARTMENT | 2.63 | 15.72 | 01-JAN-00:10 | 251.45 | 01-JAN-19:10 |
| Electricity:Zone:M SE APARTMENT | 27.33 | 464.72 | 01-JAN-03:10 | 1411.61 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:M SE APARTMENT | 2.91 | 17.37 | 01-JAN-00:10 | 277.76 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:M SE APARTMENT | 2.63 | 15.72 | 01-JAN-00:10 | 251.45 | 01-JAN-19:10 |
| Electricity:Zone:M NE APARTMENT | 27.33 | 464.72 | 01-JAN-03:10 | 1411.61 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:M NE APARTMENT | 2.91 | 17.37 | 01-JAN-00:10 | 277.76 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:M NE APARTMENT | 2.63 | 15.72 | 01-JAN-00:10 | 251.45 | 01-JAN-19:10 |
| Electricity:Zone:M N1 APARTMENT | 27.33 | 464.72 | 01-JAN-03:10 | 1411.61 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:M N1 APARTMENT | 2.91 | 17.37 | 01-JAN-00:10 | 277.76 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:M N1 APARTMENT | 2.63 | 15.72 | 01-JAN-00:10 | 251.45 | 01-JAN-19:10 |
| Electricity:Zone:M N2 APARTMENT | 27.33 | 464.72 | 01-JAN-03:10 | 1411.61 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:M N2 APARTMENT | 2.91 | 17.37 | 01-JAN-00:10 | 277.76 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:M N2 APARTMENT | 2.63 | 15.72 | 01-JAN-00:10 | 251.45 | 01-JAN-19:10 |
| Electricity:Zone:M S1 APARTMENT | 27.33 | 464.72 | 01-JAN-03:10 | 1411.61 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:M S1 APARTMENT | 2.91 | 17.37 | 01-JAN-00:10 | 277.76 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:M S1 APARTMENT | 2.63 | 15.72 | 01-JAN-00:10 | 251.45 | 01-JAN-19:10 |
| Electricity:Zone:M S2 APARTMENT | 27.33 | 464.72 | 01-JAN-03:10 | 1411.61 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:M S2 APARTMENT | 2.91 | 17.37 | 01-JAN-00:10 | 277.76 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:M S2 APARTMENT | 2.63 | 15.72 | 01-JAN-00:10 | 251.45 | 01-JAN-19:10 |
| Electricity:Zone:T SW APARTMENT | 13.67 | 232.36 | 01-JAN-03:10 | 705.80 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:T SW APARTMENT | 1.45 | 8.68 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:T SW APARTMENT | 1.32 | 7.86 | 01-JAN-00:10 | 125.72 | 01-JAN-19:10 |
| Electricity:Zone:T NW APARTMENT | 13.67 | 232.36 | 01-JAN-03:10 | 705.80 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:T NW APARTMENT | 1.45 | 8.68 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:T NW APARTMENT | 1.32 | 7.86 | 01-JAN-00:10 | 125.72 | 01-JAN-19:10 |
| Electricity:Zone:T SE APARTMENT | 13.67 | 232.36 | 01-JAN-03:10 | 705.80 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:T SE APARTMENT | 1.45 | 8.68 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:T SE APARTMENT | 1.32 | 7.86 | 01-JAN-00:10 | 125.72 | 01-JAN-19:10 |
| Electricity:Zone:T NE APARTMENT | 13.67 | 232.36 | 01-JAN-03:10 | 705.80 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:T NE APARTMENT | 1.45 | 8.68 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:T NE APARTMENT | 1.32 | 7.86 | 01-JAN-00:10 | 125.72 | 01-JAN-19:10 |
| Electricity:Zone:T N1 APARTMENT | 13.67 | 232.36 | 01-JAN-03:10 | 705.80 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:T N1 APARTMENT | 1.45 | 8.68 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:T N1 APARTMENT | 1.32 | 7.86 | 01-JAN-00:10 | 125.72 | 01-JAN-19:10 |
| Electricity:Zone:T N2 APARTMENT | 13.67 | 232.36 | 01-JAN-03:10 | 705.80 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:T N2 APARTMENT | 1.45 | 8.68 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:T N2 APARTMENT | 1.32 | 7.86 | 01-JAN-00:10 | 125.72 | 01-JAN-19:10 |
| Electricity:Zone:T S1 APARTMENT | 13.67 | 232.36 | 01-JAN-03:10 | 705.80 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:T S1 APARTMENT | 1.45 | 8.68 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:T S1 APARTMENT | 1.32 | 7.86 | 01-JAN-00:10 | 125.72 | 01-JAN-19:10 |
| Electricity:Zone:T S2 APARTMENT | 13.67 | 232.36 | 01-JAN-03:10 | 705.80 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:T S2 APARTMENT | 1.45 | 8.68 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:T S2 APARTMENT | 1.32 | 7.86 | 01-JAN-00:10 | 125.72 | 01-JAN-19:10 |
| Electricity:Zone:G CORRIDOR | 82.28 | 1494.09 | 01-JAN-00:10 | 4538.70 | 01-JAN-07:10 |
| InteriorLights:Electricity:Zone:G CORRIDOR | 11.69 | 370.63 | 01-JAN-00:10 | 370.63 | 01-JAN-00:10 |
| LightsWired:InteriorLights:Electricity:Zone:G CORRIDOR | 11.69 | 370.63 | 01-JAN-00:10 | 370.63 | 01-JAN-00:10 |
| Electricity:Zone:M CORRIDOR | 23.38 | 741.26 | 01-JAN-00:10 | 741.26 | 01-JAN-00:10 |
| InteriorLights:Electricity:Zone:M CORRIDOR | 23.38 | 741.26 | 01-JAN-00:10 | 741.26 | 01-JAN-00:10 |
| LightsWired:InteriorLights:Electricity:Zone:M CORRIDOR | 23.38 | 741.26 | 01-JAN-00:10 | 741.26 | 01-JAN-00:10 |
| Electricity:Zone:T CORRIDOR | 11.69 | 370.63 | 01-JAN-00:10 | 370.63 | 01-JAN-00:10 |
| InteriorLights:Electricity:Zone:T CORRIDOR | 11.69 | 370.63 | 01-JAN-00:10 | 370.63 | 01-JAN-00:10 |
| LightsWired:InteriorLights:Electricity:Zone:T CORRIDOR | 11.69 | 370.63 | 01-JAN-00:10 | 370.63 | 01-JAN-00:10 |
| LightsPlugIn:InteriorLights:Electricity | 4.27 | 25.50 | 01-JAN-00:10 | 407.87 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:G SW APARTMENT | 0.14 | 0.82 | 01-JAN-00:10 | 13.16 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:SpaceType:GENERAL | 4.27 | 25.50 | 01-JAN-00:10 | 407.87 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:G NW APARTMENT | 0.14 | 0.82 | 01-JAN-00:10 | 13.16 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:G NE APARTMENT | 0.14 | 0.82 | 01-JAN-00:10 | 13.16 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:G N1 APARTMENT | 0.14 | 0.82 | 01-JAN-00:10 | 13.16 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:G N2 APARTMENT | 0.14 | 0.82 | 01-JAN-00:10 | 13.16 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:G S1 APARTMENT | 0.14 | 0.82 | 01-JAN-00:10 | 13.16 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:G S2 APARTMENT | 0.14 | 0.82 | 01-JAN-00:10 | 13.16 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:M SW APARTMENT | 0.28 | 1.65 | 01-JAN-00:10 | 26.31 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:M NW APARTMENT | 0.28 | 1.65 | 01-JAN-00:10 | 26.31 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:M SE APARTMENT | 0.28 | 1.65 | 01-JAN-00:10 | 26.31 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:M NE APARTMENT | 0.28 | 1.65 | 01-JAN-00:10 | 26.31 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:M N1 APARTMENT | 0.28 | 1.65 | 01-JAN-00:10 | 26.31 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:M N2 APARTMENT | 0.28 | 1.65 | 01-JAN-00:10 | 26.31 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:M S1 APARTMENT | 0.28 | 1.65 | 01-JAN-00:10 | 26.31 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:M S2 APARTMENT | 0.28 | 1.65 | 01-JAN-00:10 | 26.31 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:T SW APARTMENT | 0.14 | 0.82 | 01-JAN-00:10 | 13.16 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:T NW APARTMENT | 0.14 | 0.82 | 01-JAN-00:10 | 13.16 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:T SE APARTMENT | 0.14 | 0.82 | 01-JAN-00:10 | 13.16 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:T NE APARTMENT | 0.14 | 0.82 | 01-JAN-00:10 | 13.16 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:T N1 APARTMENT | 0.14 | 0.82 | 01-JAN-00:10 | 13.16 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:T N2 APARTMENT | 0.14 | 0.82 | 01-JAN-00:10 | 13.16 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:T S1 APARTMENT | 0.14 | 0.82 | 01-JAN-00:10 | 13.16 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:T S2 APARTMENT | 0.14 | 0.82 | 01-JAN-00:10 | 13.16 | 01-JAN-19:10 |
| InteriorEquipment:Electricity | 458.66 | 8251.68 | 01-JAN-03:10 | 22709.69 | 03-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:G SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:SpaceType:GENERAL | 458.66 | 8251.68 | 01-JAN-03:10 | 22709.69 | 03-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity | 388.06 | 7128.22 | 01-JAN-03:10 | 18541.61 | 03-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:G SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 388.06 | 7128.22 | 01-JAN-03:10 | 18541.61 | 03-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:G NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:G NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:OFFICE | 9.47 | 194.25 | 01-JAN-00:10 | 588.62 | 03-JAN-08:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:OFFICE | 9.47 | 194.25 | 01-JAN-00:10 | 588.62 | 03-JAN-08:10 |
| InteriorEquipment:Electricity:Zone:G NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:G NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:G N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:G N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:G N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:G N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:G S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:G S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:G S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:G S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:M SW APARTMENT | 24.43 | 447.35 | 01-JAN-03:10 | 1177.25 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:M SW APARTMENT | 24.43 | 447.35 | 01-JAN-03:10 | 1177.25 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:M NW APARTMENT | 24.43 | 447.35 | 01-JAN-03:10 | 1177.25 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:M NW APARTMENT | 24.43 | 447.35 | 01-JAN-03:10 | 1177.25 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:M SE APARTMENT | 24.43 | 447.35 | 01-JAN-03:10 | 1177.25 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:M SE APARTMENT | 24.43 | 447.35 | 01-JAN-03:10 | 1177.25 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:M NE APARTMENT | 24.43 | 447.35 | 01-JAN-03:10 | 1177.25 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:M NE APARTMENT | 24.43 | 447.35 | 01-JAN-03:10 | 1177.25 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:M N1 APARTMENT | 24.43 | 447.35 | 01-JAN-03:10 | 1177.25 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:M N1 APARTMENT | 24.43 | 447.35 | 01-JAN-03:10 | 1177.25 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:M N2 APARTMENT | 24.43 | 447.35 | 01-JAN-03:10 | 1177.25 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:M N2 APARTMENT | 24.43 | 447.35 | 01-JAN-03:10 | 1177.25 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:M S1 APARTMENT | 24.43 | 447.35 | 01-JAN-03:10 | 1177.25 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:M S1 APARTMENT | 24.43 | 447.35 | 01-JAN-03:10 | 1177.25 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:M S2 APARTMENT | 24.43 | 447.35 | 01-JAN-03:10 | 1177.25 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:M S2 APARTMENT | 24.43 | 447.35 | 01-JAN-03:10 | 1177.25 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:T SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:T SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:T NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:T NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:T SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:T SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:T NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:T NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:T N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:T N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:T N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:T N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:T S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:T S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:T S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:T S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:G CORRIDOR | 70.59 | 1123.46 | 01-JAN-00:10 | 4168.07 | 01-JAN-07:10 |
| ElevatorLift:InteriorEquipment:Electricity | 65.48 | 961.46 | 01-JAN-00:10 | 4006.07 | 01-JAN-07:10 |
| ElevatorLift:InteriorEquipment:Electricity:Zone:G CORRIDOR | 65.48 | 961.46 | 01-JAN-00:10 | 4006.07 | 01-JAN-07:10 |
| ElevatorLift:InteriorEquipment:Electricity:SpaceType:GENERAL | 65.48 | 961.46 | 01-JAN-00:10 | 4006.07 | 01-JAN-07:10 |
| ElevatorLightsFan:InteriorEquipment:Electricity | 5.11 | 162.00 | 01-JAN-00:10 | 162.00 | 01-JAN-00:10 |
| ElevatorLightsFan:InteriorEquipment:Electricity:Zone:G CORRIDOR | 5.11 | 162.00 | 01-JAN-00:10 | 162.00 | 01-JAN-00:10 |
| ElevatorLightsFan:InteriorEquipment:Electricity:SpaceType:GENERAL | 5.11 | 162.00 | 01-JAN-00:10 | 162.00 | 01-JAN-00:10 |
| Fans:Electricity | 101.80 | 1691.17 | 10-NOV-18:10 | 8509.23 | 16-AUG-15:10 |
| Fans:Electricity:Zone:G SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:G SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:G NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:G NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:G NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:G NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:G N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:G N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:G N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:G N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:G S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:G S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:G S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:G S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:M SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:M SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:M NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:M NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:M SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:M SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:M NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:M NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:M N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:M N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:M N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:M N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:M S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:M S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:M S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:M S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:T SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:T SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:T NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:T NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:T SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:T SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:T NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:T NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:T N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:T N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:T N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:T N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:T S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:T S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:T S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:T S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| ElectricityPurchased:Facility | 1291.98 | 16944.45 | 17-APR-02:40 | 88325.42 | 19-JUN-17:40 |
| ElectricityPurchased:Plant | 1291.98 | 16944.45 | 17-APR-02:40 | 88325.42 | 19-JUN-17:40 |
| Cogeneration:ElectricityPurchased | 1291.98 | 16944.45 | 17-APR-02:40 | 88325.42 | 19-JUN-17:40 |
| General:Cogeneration:ElectricityPurchased | 1291.98 | 16944.45 | 17-APR-02:40 | 88325.42 | 19-JUN-17:40 |
| ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| ElectricityNet:Facility | 1291.98 | 16944.45 | 17-APR-02:40 | 88325.42 | 19-JUN-17:40 |
| ElectricityNet:Plant | 1291.98 | 16944.45 | 17-APR-02:40 | 88325.42 | 19-JUN-17:40 |
| Cogeneration:ElectricityNet | 1291.98 | 16944.45 | 17-APR-02:40 | 88325.42 | 19-JUN-17:40 |
| General:Cogeneration:ElectricityNet | 1291.98 | 16944.45 | 17-APR-02:40 | 88325.42 | 19-JUN-17:40 |
| Electricity:HVAC | 231.53 | 1691.17 | 10-NOV-18:10 | 36310.29 | 16-AUG-15:10 |
| HeatRecovery:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:HeatRecovery:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:Fans:Electricity | 101.80 | 1691.17 | 10-NOV-18:10 | 8509.23 | 16-AUG-15:10 |
| Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Cooling:Electricity | 129.73 | 0.00 | 01-JAN-00:10 | 27872.00 | 19-JUN-12:00 |
| General:Cooling:Electricity | 129.73 | 0.00 | 01-JAN-00:10 | 27872.00 | 19-JUN-12:00 |
| ExteriorLights:Electricity | 49.98 | 0.00 | 01-JAN-07:30 | 3183.33 | 01-JAN-00:10 |
| General:ExteriorLights:Electricity | 49.98 | 0.00 | 01-JAN-07:30 | 3183.33 | 01-JAN-00:10 |
| Electricity:Plant | 452.58 | 1950.00 | 01-JAN-00:10 | 37846.59 | 25-JAN-07:40 |
| WaterSystems:Electricity | 452.58 | 1950.00 | 01-JAN-00:10 | 37846.59 | 25-JAN-07:40 |
| Water Heater:WaterSystems:Electricity | 452.58 | 1950.00 | 01-JAN-00:10 | 37846.59 | 25-JAN-07:40 |
| Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
| NaturalGas:Facility | 378.88 | 0.00 | 03-MAR-17:10 | 105858.87 | 06-FEB-01:10 |
| NaturalGas:HVAC | 378.88 | 0.00 | 03-MAR-17:10 | 105858.87 | 06-FEB-01:10 |
| Heating:NaturalGas | 378.88 | 0.00 | 03-MAR-17:10 | 105858.87 | 06-FEB-01:10 |
| General:Heating:NaturalGas | 378.88 | 0.00 | 03-MAR-17:10 | 105858.87 | 06-FEB-01:10 |
| Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
| None |
| Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
| Water:Facility | 1875.32 | 0.00 | 01-JAN-02:10 | 0.00 | 01-JAN-07:10 |
| Water:Plant | 1875.32 | 0.00 | 01-JAN-02:10 | 0.00 | 01-JAN-07:10 |
| WaterSystems:Water | 1875.32 | 0.00 | 01-JAN-02:10 | 0.00 | 01-JAN-07:10 |
| Water Heater:WaterSystems:Water | 1875.32 | 0.00 | 01-JAN-02:10 | 0.00 | 01-JAN-07:10 |
| MainsWater:Facility | 1875.32 | 0.00 | 01-JAN-02:10 | 0.00 | 01-JAN-07:10 |
| MainsWater:Plant | 1875.32 | 0.00 | 01-JAN-02:10 | 0.00 | 01-JAN-07:10 |
| WaterSystems:MainsWater | 1875.32 | 0.00 | 01-JAN-02:10 | 0.00 | 01-JAN-07:10 |
| Water Heater:WaterSystems:MainsWater | 1875.32 | 0.00 | 01-JAN-02:10 | 0.00 | 01-JAN-07:10 |
| Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
| Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
| CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
| Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
| None |
| Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
| None |
| Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
| EnergyTransfer:Facility | 1446.58 | 2300.70 | 27-MAR-13:00 | 169762.58 | 16-AUG-15:10 |
| EnergyTransfer:Building | 623.16 | 2091.92 | 27-MAR-13:00 | 68698.03 | 18-AUG-15:10 |
| EnergyTransfer:Zone:G SW APARTMENT | 18.23 | 0.01 | 18-MAR-11:20 | 2288.60 | 18-AUG-16:10 |
| Heating:EnergyTransfer | 133.87 | 0.00 | 02-MAR-12:50 | 54539.05 | 06-FEB-01:10 |
| Heating:EnergyTransfer:Zone:G SW APARTMENT | 3.92 | 0.00 | 05-JAN-13:10 | 1680.53 | 06-FEB-05:00 |
| General:Heating:EnergyTransfer | 133.87 | 0.00 | 02-MAR-12:50 | 54539.05 | 06-FEB-01:10 |
| General:Heating:EnergyTransfer:Zone:G SW APARTMENT | 3.92 | 0.00 | 05-JAN-13:10 | 1680.53 | 06-FEB-05:00 |
| Cooling:EnergyTransfer | 489.29 | 0.00 | 01-JAN-00:10 | 68698.03 | 18-AUG-15:10 |
| Cooling:EnergyTransfer:Zone:G SW APARTMENT | 14.30 | 0.00 | 01-JAN-00:10 | 2288.60 | 18-AUG-16:10 |
| General:Cooling:EnergyTransfer | 489.29 | 0.00 | 01-JAN-00:10 | 68698.03 | 18-AUG-15:10 |
| General:Cooling:EnergyTransfer:Zone:G SW APARTMENT | 14.30 | 0.00 | 01-JAN-00:10 | 2288.60 | 18-AUG-16:10 |
| EnergyTransfer:Zone:G NW APARTMENT | 17.64 | 0.01 | 16-APR-13:00 | 2013.72 | 06-FEB-01:10 |
| Heating:EnergyTransfer:Zone:G NW APARTMENT | 6.90 | 0.00 | 17-JAN-15:20 | 2013.72 | 06-FEB-01:10 |
| General:Heating:EnergyTransfer:Zone:G NW APARTMENT | 6.90 | 0.00 | 17-JAN-15:20 | 2013.72 | 06-FEB-01:10 |
| Cooling:EnergyTransfer:Zone:G NW APARTMENT | 10.74 | 0.00 | 01-JAN-00:10 | 1927.69 | 18-AUG-16:30 |
| General:Cooling:EnergyTransfer:Zone:G NW APARTMENT | 10.74 | 0.00 | 01-JAN-00:10 | 1927.69 | 18-AUG-16:30 |
| EnergyTransfer:Zone:OFFICE | 15.18 | 0.01 | 05-JUN-02:30 | 4361.62 | 05-SEP-08:10 |
| Heating:EnergyTransfer:Zone:OFFICE | 3.13 | 0.00 | 01-JAN-09:30 | 3658.33 | 06-FEB-08:10 |
| General:Heating:EnergyTransfer:Zone:OFFICE | 3.13 | 0.00 | 01-JAN-09:30 | 3658.33 | 06-FEB-08:10 |
| Cooling:EnergyTransfer:Zone:OFFICE | 12.05 | 0.00 | 01-JAN-00:10 | 4361.62 | 05-SEP-08:10 |
| General:Cooling:EnergyTransfer:Zone:OFFICE | 12.05 | 0.00 | 01-JAN-00:10 | 4361.62 | 05-SEP-08:10 |
| EnergyTransfer:Zone:G NE APARTMENT | 17.46 | 0.00 | 18-NOV-19:50 | 1984.31 | 06-FEB-01:10 |
| Heating:EnergyTransfer:Zone:G NE APARTMENT | 6.78 | 0.00 | 01-MAR-09:50 | 1984.31 | 06-FEB-01:10 |
| General:Heating:EnergyTransfer:Zone:G NE APARTMENT | 6.78 | 0.00 | 01-MAR-09:50 | 1984.31 | 06-FEB-01:10 |
| Cooling:EnergyTransfer:Zone:G NE APARTMENT | 10.68 | 0.00 | 01-JAN-00:10 | 1642.08 | 24-AUG-17:00 |
| General:Cooling:EnergyTransfer:Zone:G NE APARTMENT | 10.68 | 0.00 | 01-JAN-00:10 | 1642.08 | 24-AUG-17:00 |
| EnergyTransfer:Zone:G N1 APARTMENT | 12.74 | 0.00 | 20-FEB-11:50 | 1295.73 | 10-JUL-17:30 |
| Heating:EnergyTransfer:Zone:G N1 APARTMENT | 2.83 | 0.00 | 17-JAN-16:10 | 1137.51 | 06-FEB-01:10 |
| General:Heating:EnergyTransfer:Zone:G N1 APARTMENT | 2.83 | 0.00 | 17-JAN-16:10 | 1137.51 | 06-FEB-01:10 |
| Cooling:EnergyTransfer:Zone:G N1 APARTMENT | 9.91 | 0.00 | 01-JAN-00:10 | 1295.73 | 10-JUL-17:30 |
| General:Cooling:EnergyTransfer:Zone:G N1 APARTMENT | 9.91 | 0.00 | 01-JAN-00:10 | 1295.73 | 10-JUL-17:30 |
| EnergyTransfer:Zone:G N2 APARTMENT | 12.74 | 0.00 | 06-APR-03:50 | 1293.53 | 10-JUL-17:40 |
| Heating:EnergyTransfer:Zone:G N2 APARTMENT | 2.83 | 0.00 | 17-JAN-16:10 | 1136.13 | 06-FEB-01:10 |
| General:Heating:EnergyTransfer:Zone:G N2 APARTMENT | 2.83 | 0.00 | 17-JAN-16:10 | 1136.13 | 06-FEB-01:10 |
| Cooling:EnergyTransfer:Zone:G N2 APARTMENT | 9.91 | 0.00 | 01-JAN-00:10 | 1293.53 | 10-JUL-17:40 |
| General:Cooling:EnergyTransfer:Zone:G N2 APARTMENT | 9.91 | 0.00 | 01-JAN-00:10 | 1293.53 | 10-JUL-17:40 |
| EnergyTransfer:Zone:G S1 APARTMENT | 15.57 | 0.01 | 26-NOV-05:20 | 1738.95 | 01-SEP-14:10 |
| Heating:EnergyTransfer:Zone:G S1 APARTMENT | 0.97 | 0.00 | 02-JAN-10:50 | 805.19 | 06-FEB-05:00 |
| General:Heating:EnergyTransfer:Zone:G S1 APARTMENT | 0.97 | 0.00 | 02-JAN-10:50 | 805.19 | 06-FEB-05:00 |
| Cooling:EnergyTransfer:Zone:G S1 APARTMENT | 14.59 | 0.00 | 01-JAN-00:10 | 1738.95 | 01-SEP-14:10 |
| General:Cooling:EnergyTransfer:Zone:G S1 APARTMENT | 14.59 | 0.00 | 01-JAN-00:10 | 1738.95 | 01-SEP-14:10 |
| EnergyTransfer:Zone:G S2 APARTMENT | 16.76 | 0.03 | 12-FEB-11:30 | 1830.43 | 04-SEP-13:30 |
| Heating:EnergyTransfer:Zone:G S2 APARTMENT | 1.38 | 0.00 | 04-JAN-13:30 | 965.51 | 06-FEB-05:00 |
| General:Heating:EnergyTransfer:Zone:G S2 APARTMENT | 1.38 | 0.00 | 04-JAN-13:30 | 965.51 | 06-FEB-05:00 |
| Cooling:EnergyTransfer:Zone:G S2 APARTMENT | 15.38 | 0.00 | 01-JAN-00:10 | 1830.43 | 04-SEP-13:30 |
| General:Cooling:EnergyTransfer:Zone:G S2 APARTMENT | 15.38 | 0.00 | 01-JAN-00:10 | 1830.43 | 04-SEP-13:30 |
| EnergyTransfer:Zone:M SW APARTMENT | 44.50 | 0.00 | 10-DEC-12:40 | 5568.94 | 18-AUG-16:10 |
| Heating:EnergyTransfer:Zone:M SW APARTMENT | 5.32 | 0.00 | 02-JAN-10:50 | 3346.18 | 06-FEB-01:10 |
| General:Heating:EnergyTransfer:Zone:M SW APARTMENT | 5.32 | 0.00 | 02-JAN-10:50 | 3346.18 | 06-FEB-01:10 |
| Cooling:EnergyTransfer:Zone:M SW APARTMENT | 39.19 | 0.00 | 01-JAN-00:10 | 5568.94 | 18-AUG-16:10 |
| General:Cooling:EnergyTransfer:Zone:M SW APARTMENT | 39.19 | 0.00 | 01-JAN-00:10 | 5568.94 | 18-AUG-16:10 |
| EnergyTransfer:Zone:M NW APARTMENT | 38.83 | 0.01 | 28-JAN-13:20 | 4932.46 | 19-JUN-17:30 |
| Heating:EnergyTransfer:Zone:M NW APARTMENT | 9.39 | 0.00 | 12-JAN-15:00 | 3994.82 | 06-FEB-01:00 |
| General:Heating:EnergyTransfer:Zone:M NW APARTMENT | 9.39 | 0.00 | 12-JAN-15:00 | 3994.82 | 06-FEB-01:00 |
| Cooling:EnergyTransfer:Zone:M NW APARTMENT | 29.44 | 0.00 | 01-JAN-00:10 | 4932.46 | 19-JUN-17:30 |
| General:Cooling:EnergyTransfer:Zone:M NW APARTMENT | 29.44 | 0.00 | 01-JAN-00:10 | 4932.46 | 19-JUN-17:30 |
| EnergyTransfer:Zone:M SE APARTMENT | 44.30 | 0.12 | 04-JAN-13:00 | 5118.07 | 18-AUG-13:00 |
| Heating:EnergyTransfer:Zone:M SE APARTMENT | 5.17 | 0.00 | 02-JAN-10:40 | 3298.14 | 06-FEB-01:10 |
| General:Heating:EnergyTransfer:Zone:M SE APARTMENT | 5.17 | 0.00 | 02-JAN-10:40 | 3298.14 | 06-FEB-01:10 |
| Cooling:EnergyTransfer:Zone:M SE APARTMENT | 39.13 | 0.00 | 01-JAN-00:10 | 5118.07 | 18-AUG-13:00 |
| General:Cooling:EnergyTransfer:Zone:M SE APARTMENT | 39.13 | 0.00 | 01-JAN-00:10 | 5118.07 | 18-AUG-13:00 |
| EnergyTransfer:Zone:M NE APARTMENT | 38.36 | 0.12 | 12-MAR-00:20 | 4075.47 | 19-JUN-17:10 |
| Heating:EnergyTransfer:Zone:M NE APARTMENT | 9.11 | 0.00 | 13-JAN-13:30 | 3931.92 | 06-FEB-01:00 |
| General:Heating:EnergyTransfer:Zone:M NE APARTMENT | 9.11 | 0.00 | 13-JAN-13:30 | 3931.92 | 06-FEB-01:00 |
| Cooling:EnergyTransfer:Zone:M NE APARTMENT | 29.25 | 0.00 | 01-JAN-00:10 | 4075.47 | 19-JUN-17:10 |
| General:Cooling:EnergyTransfer:Zone:M NE APARTMENT | 29.25 | 0.00 | 01-JAN-00:10 | 4075.47 | 19-JUN-17:10 |
| EnergyTransfer:Zone:M N1 APARTMENT | 29.45 | 0.03 | 22-JAN-02:10 | 3155.54 | 19-JUN-17:30 |
| Heating:EnergyTransfer:Zone:M N1 APARTMENT | 2.49 | 0.00 | 03-JAN-10:50 | 2001.88 | 06-FEB-01:10 |
| General:Heating:EnergyTransfer:Zone:M N1 APARTMENT | 2.49 | 0.00 | 03-JAN-10:50 | 2001.88 | 06-FEB-01:10 |
| Cooling:EnergyTransfer:Zone:M N1 APARTMENT | 26.97 | 0.00 | 01-JAN-00:10 | 3155.54 | 19-JUN-17:30 |
| General:Cooling:EnergyTransfer:Zone:M N1 APARTMENT | 26.97 | 0.00 | 01-JAN-00:10 | 3155.54 | 19-JUN-17:30 |
| EnergyTransfer:Zone:M N2 APARTMENT | 29.45 | 0.03 | 11-DEC-24:00 | 3140.83 | 19-JUN-17:30 |
| Heating:EnergyTransfer:Zone:M N2 APARTMENT | 2.48 | 0.00 | 03-JAN-10:50 | 1998.28 | 06-FEB-01:10 |
| General:Heating:EnergyTransfer:Zone:M N2 APARTMENT | 2.48 | 0.00 | 03-JAN-10:50 | 1998.28 | 06-FEB-01:10 |
| Cooling:EnergyTransfer:Zone:M N2 APARTMENT | 26.97 | 0.00 | 01-JAN-00:10 | 3140.83 | 19-JUN-17:30 |
| General:Cooling:EnergyTransfer:Zone:M N2 APARTMENT | 26.97 | 0.00 | 01-JAN-00:10 | 3140.83 | 19-JUN-17:30 |
| EnergyTransfer:Zone:M S1 APARTMENT | 39.75 | 0.03 | 27-FEB-10:40 | 4077.02 | 01-SEP-13:00 |
| Heating:EnergyTransfer:Zone:M S1 APARTMENT | 0.83 | 0.00 | 01-JAN-09:20 | 1497.22 | 06-FEB-01:10 |
| General:Heating:EnergyTransfer:Zone:M S1 APARTMENT | 0.83 | 0.00 | 01-JAN-09:20 | 1497.22 | 06-FEB-01:10 |
| Cooling:EnergyTransfer:Zone:M S1 APARTMENT | 38.92 | 0.00 | 01-JAN-00:10 | 4077.02 | 01-SEP-13:00 |
| General:Cooling:EnergyTransfer:Zone:M S1 APARTMENT | 38.92 | 0.00 | 01-JAN-00:10 | 4077.02 | 01-SEP-13:00 |
| EnergyTransfer:Zone:M S2 APARTMENT | 39.76 | 0.09 | 27-FEB-16:00 | 4087.49 | 01-SEP-13:00 |
| Heating:EnergyTransfer:Zone:M S2 APARTMENT | 0.83 | 0.00 | 01-JAN-09:20 | 1494.61 | 06-FEB-01:10 |
| General:Heating:EnergyTransfer:Zone:M S2 APARTMENT | 0.83 | 0.00 | 01-JAN-09:20 | 1494.61 | 06-FEB-01:10 |
| Cooling:EnergyTransfer:Zone:M S2 APARTMENT | 38.93 | 0.00 | 01-JAN-00:10 | 4087.49 | 01-SEP-13:00 |
| General:Cooling:EnergyTransfer:Zone:M S2 APARTMENT | 38.93 | 0.00 | 01-JAN-00:10 | 4087.49 | 01-SEP-13:00 |
| EnergyTransfer:Zone:T SW APARTMENT | 28.42 | 0.01 | 24-NOV-16:40 | 3899.50 | 18-AUG-15:10 |
| Heating:EnergyTransfer:Zone:T SW APARTMENT | 9.96 | 0.00 | 05-JAN-12:30 | 3404.89 | 06-FEB-05:00 |
| General:Heating:EnergyTransfer:Zone:T SW APARTMENT | 9.96 | 0.00 | 05-JAN-12:30 | 3404.89 | 06-FEB-05:00 |
| Cooling:EnergyTransfer:Zone:T SW APARTMENT | 18.47 | 0.00 | 01-JAN-00:10 | 3899.50 | 18-AUG-15:10 |
| General:Cooling:EnergyTransfer:Zone:T SW APARTMENT | 18.47 | 0.00 | 01-JAN-00:10 | 3899.50 | 18-AUG-15:10 |
| EnergyTransfer:Zone:T NW APARTMENT | 27.36 | 0.01 | 18-FEB-13:50 | 3604.06 | 06-FEB-01:00 |
| Heating:EnergyTransfer:Zone:T NW APARTMENT | 13.08 | 0.00 | 17-JAN-13:10 | 3604.06 | 06-FEB-01:00 |
| General:Heating:EnergyTransfer:Zone:T NW APARTMENT | 13.08 | 0.00 | 17-JAN-13:10 | 3604.06 | 06-FEB-01:00 |
| Cooling:EnergyTransfer:Zone:T NW APARTMENT | 14.28 | 0.00 | 01-JAN-00:10 | 3369.32 | 19-JUN-17:20 |
| General:Cooling:EnergyTransfer:Zone:T NW APARTMENT | 14.28 | 0.00 | 01-JAN-00:10 | 3369.32 | 19-JUN-17:20 |
| EnergyTransfer:Zone:T SE APARTMENT | 28.17 | 0.36 | 30-MAR-16:40 | 3630.62 | 18-AUG-13:00 |
| Heating:EnergyTransfer:Zone:T SE APARTMENT | 9.82 | 0.00 | 05-JAN-11:30 | 3385.13 | 06-FEB-05:00 |
| General:Heating:EnergyTransfer:Zone:T SE APARTMENT | 9.82 | 0.00 | 05-JAN-11:30 | 3385.13 | 06-FEB-05:00 |
| Cooling:EnergyTransfer:Zone:T SE APARTMENT | 18.35 | 0.00 | 01-JAN-00:10 | 3630.62 | 18-AUG-13:00 |
| General:Cooling:EnergyTransfer:Zone:T SE APARTMENT | 18.35 | 0.00 | 01-JAN-00:10 | 3630.62 | 18-AUG-13:00 |
| EnergyTransfer:Zone:T NE APARTMENT | 27.00 | 0.14 | 17-FEB-13:10 | 3580.79 | 06-FEB-01:00 |
| Heating:EnergyTransfer:Zone:T NE APARTMENT | 12.87 | 0.00 | 17-JAN-12:30 | 3580.79 | 06-FEB-01:00 |
| General:Heating:EnergyTransfer:Zone:T NE APARTMENT | 12.87 | 0.00 | 17-JAN-12:30 | 3580.79 | 06-FEB-01:00 |
| Cooling:EnergyTransfer:Zone:T NE APARTMENT | 14.13 | 0.00 | 01-JAN-00:10 | 2955.12 | 19-JUN-12:00 |
| General:Cooling:EnergyTransfer:Zone:T NE APARTMENT | 14.13 | 0.00 | 01-JAN-00:10 | 2955.12 | 19-JUN-12:00 |
| EnergyTransfer:Zone:T N1 APARTMENT | 19.24 | 0.06 | 24-MAR-22:40 | 2308.42 | 06-FEB-01:10 |
| Heating:EnergyTransfer:Zone:T N1 APARTMENT | 7.18 | 0.00 | 17-JAN-12:10 | 2308.42 | 06-FEB-01:10 |
| General:Heating:EnergyTransfer:Zone:T N1 APARTMENT | 7.18 | 0.00 | 17-JAN-12:10 | 2308.42 | 06-FEB-01:10 |
| Cooling:EnergyTransfer:Zone:T N1 APARTMENT | 12.07 | 0.00 | 01-JAN-00:10 | 2248.89 | 19-JUN-17:30 |
| General:Cooling:EnergyTransfer:Zone:T N1 APARTMENT | 12.07 | 0.00 | 01-JAN-00:10 | 2248.89 | 19-JUN-17:30 |
| EnergyTransfer:Zone:T N2 APARTMENT | 19.25 | 0.16 | 28-OCT-21:10 | 2307.31 | 06-FEB-01:10 |
| Heating:EnergyTransfer:Zone:T N2 APARTMENT | 7.17 | 0.00 | 17-JAN-12:10 | 2307.31 | 06-FEB-01:10 |
| General:Heating:EnergyTransfer:Zone:T N2 APARTMENT | 7.17 | 0.00 | 17-JAN-12:10 | 2307.31 | 06-FEB-01:10 |
| Cooling:EnergyTransfer:Zone:T N2 APARTMENT | 12.07 | 0.00 | 01-JAN-00:10 | 2248.05 | 19-JUN-14:30 |
| General:Cooling:EnergyTransfer:Zone:T N2 APARTMENT | 12.07 | 0.00 | 01-JAN-00:10 | 2248.05 | 19-JUN-14:30 |
| EnergyTransfer:Zone:T S1 APARTMENT | 21.49 | 0.09 | 25-APR-02:50 | 2957.09 | 18-AUG-13:30 |
| Heating:EnergyTransfer:Zone:T S1 APARTMENT | 4.71 | 0.00 | 01-JAN-12:30 | 2154.45 | 06-FEB-05:00 |
| General:Heating:EnergyTransfer:Zone:T S1 APARTMENT | 4.71 | 0.00 | 01-JAN-12:30 | 2154.45 | 06-FEB-05:00 |
| Cooling:EnergyTransfer:Zone:T S1 APARTMENT | 16.77 | 0.00 | 01-JAN-00:10 | 2957.09 | 18-AUG-13:30 |
| General:Cooling:EnergyTransfer:Zone:T S1 APARTMENT | 16.77 | 0.00 | 01-JAN-00:10 | 2957.09 | 18-AUG-13:30 |
| EnergyTransfer:Zone:T S2 APARTMENT | 21.50 | 0.04 | 12-JAN-11:50 | 2966.95 | 18-AUG-13:20 |
| Heating:EnergyTransfer:Zone:T S2 APARTMENT | 4.72 | 0.00 | 01-JAN-12:30 | 2153.43 | 06-FEB-05:00 |
| General:Heating:EnergyTransfer:Zone:T S2 APARTMENT | 4.72 | 0.00 | 01-JAN-12:30 | 2153.43 | 06-FEB-05:00 |
| Cooling:EnergyTransfer:Zone:T S2 APARTMENT | 16.79 | 0.00 | 01-JAN-00:10 | 2966.95 | 18-AUG-13:20 |
| General:Cooling:EnergyTransfer:Zone:T S2 APARTMENT | 16.79 | 0.00 | 01-JAN-00:10 | 2966.95 | 18-AUG-13:20 |
| EnergyTransfer:Zone:T CORRIDOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Heating:EnergyTransfer:Zone:T CORRIDOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:Heating:EnergyTransfer:Zone:T CORRIDOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Cooling:EnergyTransfer:Zone:T CORRIDOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:Cooling:EnergyTransfer:Zone:T CORRIDOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| EnergyTransfer:Zone:G CORRIDOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Heating:EnergyTransfer:Zone:G CORRIDOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:Heating:EnergyTransfer:Zone:G CORRIDOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Cooling:EnergyTransfer:Zone:G CORRIDOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:Cooling:EnergyTransfer:Zone:G CORRIDOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| EnergyTransfer:Zone:M CORRIDOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Heating:EnergyTransfer:Zone:M CORRIDOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:Heating:EnergyTransfer:Zone:M CORRIDOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Cooling:EnergyTransfer:Zone:M CORRIDOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:Cooling:EnergyTransfer:Zone:M CORRIDOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| EnergyTransfer:HVAC | 823.42 | 0.00 | 27-MAR-11:30 | 105200.48 | 02-AUG-15:10 |
| HeatRecoveryForHeating:EnergyTransfer | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 11-AUG-16:50 |
| HeatRecoveryForCooling:EnergyTransfer | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 29-MAY-17:20 |
| HeatingCoils:EnergyTransfer | 303.10 | 0.00 | 03-MAR-17:10 | 84687.10 | 06-FEB-01:10 |
| CoolingCoils:EnergyTransfer | 520.32 | 0.00 | 01-JAN-00:10 | 105200.48 | 02-AUG-15:10 |
| PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 09:15:04
Annual Building Sensible Heat Gain Components| HVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
| G SW APARTMENT | 0.490 | -9.857 | 10.349 | -11.361 | 0.000 | 0.000 | 3.860 | 1.454 | 12.213 | 12.510 | 0.000 | 0.130 | 0.000 | 0.000 | -5.284 | 0.000 | -4.737 | -9.766 |
| G NW APARTMENT | 0.491 | -9.695 | 14.180 | -8.822 | 0.000 | 0.000 | 3.941 | 1.454 | 12.213 | 6.520 | 0.000 | 0.130 | 0.000 | 0.000 | -5.389 | 0.000 | -4.625 | -10.397 |
| OFFICE | 0.000 | 0.000 | 3.127 | -12.051 | 0.000 | 0.000 | 2.126 | 7.396 | 9.469 | 12.314 | 0.000 | 0.074 | 0.000 | 0.000 | -5.232 | 0.000 | -3.891 | -13.332 |
| G NE APARTMENT | 0.491 | -9.697 | 14.055 | -8.741 | 0.000 | 0.000 | 3.942 | 1.454 | 12.213 | 6.399 | 0.000 | 0.130 | 0.000 | 0.000 | -5.288 | 0.000 | -4.633 | -10.325 |
| G N1 APARTMENT | 0.492 | -9.747 | 9.707 | -7.532 | 0.000 | 0.000 | 3.930 | 1.454 | 12.213 | 2.407 | 0.000 | 0.079 | 0.000 | 0.000 | -3.416 | 0.000 | -3.096 | -6.490 |
| G N2 APARTMENT | 0.492 | -9.747 | 9.702 | -7.531 | 0.000 | 0.000 | 3.930 | 1.454 | 12.213 | 2.407 | 0.000 | 0.079 | 0.000 | 0.000 | -3.416 | 0.000 | -3.096 | -6.486 |
| G S1 APARTMENT | 0.490 | -9.944 | 6.140 | -10.309 | 0.000 | 0.000 | 3.843 | 1.454 | 12.213 | 8.436 | 0.000 | 0.078 | 0.000 | 0.000 | -3.253 | 0.000 | -3.196 | -5.953 |
| G S2 APARTMENT | 0.490 | -9.951 | 6.793 | -11.336 | 0.000 | 0.000 | 3.841 | 1.454 | 12.213 | 8.431 | 0.000 | 0.078 | 0.000 | 0.000 | -3.251 | 0.000 | -3.202 | -5.559 |
| M SW APARTMENT | 0.980 | -20.137 | 15.376 | -30.089 | 0.000 | 0.000 | 7.642 | 2.908 | 24.426 | 24.610 | 0.000 | 0.371 | 0.000 | 0.000 | -11.046 | 0.000 | -13.596 | -1.444 |
| M NW APARTMENT | 0.980 | -19.747 | 22.603 | -23.895 | 0.000 | 0.000 | 7.805 | 2.908 | 24.426 | 12.705 | 0.000 | 0.371 | 0.000 | 0.000 | -11.310 | 0.000 | -13.293 | -3.553 |
| M SE APARTMENT | 0.980 | -20.152 | 15.150 | -29.932 | 0.000 | 0.000 | 7.644 | 2.908 | 24.426 | 24.484 | 0.000 | 0.371 | 0.000 | 0.000 | -10.955 | 0.000 | -13.611 | -1.313 |
| M NE APARTMENT | 0.980 | -19.758 | 22.346 | -23.707 | 0.000 | 0.000 | 7.807 | 2.908 | 24.426 | 12.455 | 0.000 | 0.371 | 0.000 | 0.000 | -11.096 | 0.000 | -13.313 | -3.419 |
| M N1 APARTMENT | 0.981 | -19.877 | 13.803 | -19.385 | 0.000 | 0.000 | 7.778 | 2.908 | 24.426 | 4.660 | 0.000 | 0.224 | 0.469 | 0.000 | -7.162 | 0.000 | -8.822 | -0.000 |
| M N2 APARTMENT | 0.981 | -19.879 | 13.794 | -19.386 | 0.000 | 0.000 | 7.777 | 2.908 | 24.426 | 4.659 | 0.000 | 0.224 | 0.483 | 0.000 | -7.162 | 0.000 | -8.824 | -0.000 |
| M S1 APARTMENT | 0.980 | -20.398 | 7.370 | -26.033 | 0.000 | 0.000 | 7.591 | 2.908 | 24.426 | 16.648 | 0.000 | 0.224 | 2.167 | 0.000 | -6.796 | 0.000 | -9.087 | -0.000 |
| M S2 APARTMENT | 0.980 | -20.399 | 7.364 | -26.044 | 0.000 | 0.000 | 7.591 | 2.908 | 24.426 | 16.647 | 0.000 | 0.224 | 2.187 | 0.000 | -6.796 | 0.000 | -9.088 | -0.000 |
| T SW APARTMENT | 0.490 | -9.824 | 16.655 | -15.828 | 0.000 | 0.000 | 3.879 | 1.454 | 12.213 | 12.253 | 0.000 | 0.242 | 0.000 | 0.000 | -5.210 | 0.000 | -8.656 | -7.667 |
| T NW APARTMENT | 0.490 | -9.674 | 20.678 | -12.697 | 0.000 | 0.000 | 3.948 | 1.454 | 12.213 | 6.336 | 0.000 | 0.242 | 0.000 | 0.000 | -5.373 | 0.000 | -8.474 | -9.142 |
| T SE APARTMENT | 0.490 | -9.837 | 16.465 | -15.646 | 0.000 | 0.000 | 3.882 | 1.454 | 12.213 | 12.190 | 0.000 | 0.242 | 0.000 | 0.000 | -5.167 | 0.000 | -8.682 | -7.604 |
| T NE APARTMENT | 0.490 | -9.681 | 20.465 | -12.529 | 0.000 | 0.000 | 3.950 | 1.454 | 12.213 | 6.216 | 0.000 | 0.242 | 0.000 | 0.000 | -5.271 | 0.000 | -8.501 | -9.048 |
| T N1 APARTMENT | 0.490 | -9.719 | 14.524 | -10.184 | 0.000 | 0.000 | 3.937 | 1.454 | 12.213 | 2.331 | 0.000 | 0.146 | 0.000 | 0.000 | -3.412 | 0.000 | -5.547 | -6.231 |
| T N2 APARTMENT | 0.490 | -9.720 | 14.521 | -10.191 | 0.000 | 0.000 | 3.937 | 1.454 | 12.213 | 2.329 | 0.000 | 0.146 | 0.000 | 0.000 | -3.411 | 0.000 | -5.549 | -6.220 |
| T S1 APARTMENT | 0.490 | -9.921 | 10.700 | -13.327 | 0.000 | 0.000 | 3.860 | 1.454 | 12.213 | 8.303 | 0.000 | 0.146 | 0.000 | 0.000 | -3.213 | 0.000 | -5.716 | -4.989 |
| T S2 APARTMENT | 0.490 | -9.922 | 10.700 | -13.343 | 0.000 | 0.000 | 3.861 | 1.454 | 12.213 | 8.302 | 0.000 | 0.146 | 0.000 | 0.000 | -3.211 | 0.000 | -5.717 | -4.972 |
| T CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 6.291 | 11.688 | 0.000 | 0.946 | 0.000 | 0.013 | 0.000 | 0.000 | -0.547 | 0.000 | -1.341 | -17.049 |
| G CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 6.532 | 11.688 | 3.530 | 2.885 | 0.000 | 0.345 | 2.974 | 0.000 | -1.512 | 0.000 | -26.442 | -0.000 |
| M CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 11.907 | 23.376 | 0.000 | 1.868 | 0.000 | 0.026 | 0.000 | 0.000 | -1.187 | 0.000 | -2.203 | -33.788 |
| Total Facility | 15.198 | -307.284 | 316.567 | -379.899 | 0.000 | 0.000 | 147.031 | 99.229 | 391.594 | 240.249 | 0.000 | 5.089 | 8.280 | 0.000 | -144.369 | 0.000 | -206.938 | -184.746 |
| Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
| G SW APARTMENT | 18-AUG-16:03 | 0.00 | 294.71 | 0.00 | -2583.50 | 0.00 | 0.00 | 0.00 | 86.80 | 588.62 | 1686.55 | 0.00 | 95.17 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -168.34 |
| G NW APARTMENT | 18-AUG-16:30 | 0.00 | 283.10 | 0.00 | -2210.77 | 0.00 | 0.00 | 86.96 | 86.80 | 588.62 | 1542.37 | 0.00 | 94.10 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -471.18 |
| OFFICE | 11-SEP-07:01 | 0.00 | 0.00 | 0.00 | -6669.41 | 0.00 | 0.00 | 257.38 | 582.92 | 588.62 | 847.58 | 0.00 | 0.00 | 4501.13 | 0.00 | -0.00 | 0.00 | -108.22 | 0.00 |
| G NE APARTMENT | 24-AUG-17:00 | 0.00 | 316.34 | 0.00 | -1958.07 | 0.00 | 0.00 | 86.96 | 86.80 | 588.62 | 431.34 | 0.00 | 189.56 | 258.45 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| G N1 APARTMENT | 10-JUL-17:27 | 0.00 | 211.48 | 0.00 | -1507.42 | 0.00 | 0.00 | 145.49 | 117.18 | 588.62 | 372.26 | 0.00 | 49.23 | 23.16 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| G N2 APARTMENT | 10-JUL-17:35 | 0.00 | 211.48 | 0.00 | -1505.13 | 0.00 | 0.00 | 145.49 | 117.18 | 588.62 | 362.20 | 0.00 | 49.87 | 30.29 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| G S1 APARTMENT | 01-SEP-14:10 | 0.00 | 243.44 | 0.00 | -1982.21 | 0.00 | 0.00 | 0.00 | 30.38 | 400.26 | 1278.61 | 0.00 | 42.30 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -12.79 |
| G S2 APARTMENT | 04-SEP-13:30 | 0.00 | 86.89 | 0.00 | -1917.36 | 0.00 | 0.00 | 83.61 | 17.36 | 382.60 | 1418.56 | 0.00 | 12.70 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -84.37 |
| M SW APARTMENT | 18-AUG-16:03 | 0.00 | 589.38 | 0.00 | -6159.07 | 0.00 | 0.00 | 0.00 | 173.60 | 1177.25 | 3367.83 | 0.00 | 272.89 | 578.13 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| M NW APARTMENT | 19-JUN-17:25 | 0.00 | 599.29 | 0.00 | -5532.09 | 0.00 | 0.00 | 290.97 | 234.36 | 1177.25 | 2998.49 | 0.00 | 325.75 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -94.02 |
| M SE APARTMENT | 18-AUG-13:00 | 0.00 | 632.85 | 0.00 | -5750.89 | 0.00 | 0.00 | 0.00 | 34.72 | 776.98 | 3346.24 | 0.00 | 344.53 | 615.57 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| M NE APARTMENT | 19-JUN-17:05 | 0.00 | 622.93 | 0.00 | -4699.36 | 0.00 | 0.00 | 290.97 | 234.36 | 1177.25 | 1324.79 | 0.00 | 357.29 | 691.76 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| M N1 APARTMENT | 19-JUN-17:25 | 0.00 | 599.68 | 0.00 | -3755.44 | 0.00 | 0.00 | 290.97 | 234.36 | 1177.25 | 984.75 | 0.00 | 196.48 | 271.95 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| M N2 APARTMENT | 19-JUN-17:25 | 0.00 | 599.68 | 0.00 | -3740.74 | 0.00 | 0.00 | 290.97 | 234.36 | 1177.25 | 984.87 | 0.00 | 196.48 | 257.12 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| M S1 APARTMENT | 01-SEP-13:00 | 0.00 | 460.50 | 0.00 | -4537.29 | 0.00 | 0.00 | 0.00 | 34.72 | 776.98 | 3213.51 | 0.00 | 136.09 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -84.51 |
| M S2 APARTMENT | 01-SEP-13:00 | 0.00 | 460.50 | 0.00 | -4547.75 | 0.00 | 0.00 | 0.00 | 34.72 | 776.98 | 3213.43 | 0.00 | 136.09 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -73.96 |
| T SW APARTMENT | 18-AUG-15:10 | 0.00 | 300.48 | 0.00 | -4200.03 | 0.00 | 0.00 | 0.00 | 60.76 | 470.90 | 1959.48 | 0.00 | 223.71 | 1184.70 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| T NW APARTMENT | 19-JUN-17:17 | 0.00 | 305.36 | 0.00 | -3674.90 | 0.00 | 0.00 | 145.49 | 117.18 | 588.62 | 1485.26 | 0.00 | 224.76 | 808.23 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| T SE APARTMENT | 18-AUG-13:00 | 0.00 | 316.38 | 0.00 | -3946.99 | 0.00 | 0.00 | 0.00 | 17.36 | 388.49 | 1647.45 | 0.00 | 226.90 | 1350.40 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| T NE APARTMENT | 19-JUN-12:00 | 0.00 | 425.59 | 0.00 | -3380.80 | 0.00 | 0.00 | 41.81 | 17.36 | 406.15 | 805.03 | 0.00 | 258.24 | 1426.63 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| T N1 APARTMENT | 19-JUN-17:30 | 0.00 | 299.63 | 0.00 | -2548.63 | 0.00 | 0.00 | 145.49 | 117.18 | 588.62 | 482.99 | 0.00 | 129.36 | 785.36 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| T N2 APARTMENT | 19-JUN-14:30 | 0.00 | 334.60 | 0.00 | -2582.61 | 0.00 | 0.00 | 41.81 | 30.38 | 400.26 | 599.06 | 0.00 | 120.59 | 1055.91 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| T S1 APARTMENT | 18-AUG-13:30 | 0.00 | 316.38 | 0.00 | -3273.49 | 0.00 | 0.00 | 0.00 | 17.36 | 382.60 | 1262.83 | 0.00 | 142.38 | 1151.93 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| T S2 APARTMENT | 18-AUG-13:20 | 0.00 | 316.38 | 0.00 | -3283.34 | 0.00 | 0.00 | 0.00 | 17.36 | 382.60 | 1304.93 | 0.00 | 140.54 | 1121.52 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| T CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| G CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Total Facility | 18-AUG-15:10 | 0.00 | 9318.47 | 0.00 | -78018.08 | 0.00 | 0.00 | 1382.40 | 3948.92 | 15334.78 | 29868.25 | 0.00 | 4859.31 | 13305.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
| G SW APARTMENT | 06-FEB-05:00 | -1061.50 | 0.00 | 2742.04 | 0.00 | 0.00 | 0.00 | 194.99 | 26.04 | 223.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -779.32 | 0.00 | -688.19 | -657.74 |
| G NW APARTMENT | 06-FEB-01:10 | -1061.45 | 0.00 | 3075.15 | 0.00 | 0.00 | 0.00 | 194.99 | 8.68 | 241.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -792.69 | 0.00 | -807.66 | -858.36 |
| OFFICE | 03-JAN-07:01 | 0.00 | 0.00 | 10192.46 | 0.00 | 0.00 | 0.00 | 0.00 | 116.58 | 294.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -278.60 | 0.00 | -304.44 | -10020.31 |
| G NE APARTMENT | 06-FEB-01:10 | -1061.45 | 0.00 | 3045.75 | 0.00 | 0.00 | 0.00 | 194.99 | 8.68 | 241.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -783.50 | 0.00 | -807.66 | -838.14 |
| G N1 APARTMENT | 06-FEB-08:16 | -1039.73 | 0.00 | 2177.61 | 0.00 | 0.00 | 0.00 | 76.05 | 26.04 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -353.65 | 0.00 | -356.47 | -918.34 |
| G N2 APARTMENT | 06-FEB-01:10 | -1061.59 | 0.00 | 2197.70 | 0.00 | 0.00 | 0.00 | 194.99 | 8.68 | 241.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -484.16 | 0.00 | -487.16 | -609.81 |
| G S1 APARTMENT | 06-FEB-05:00 | -1061.62 | 0.00 | 1866.81 | 0.00 | 0.00 | 0.00 | 194.99 | 26.04 | 223.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -471.61 | 0.00 | -415.10 | -363.19 |
| G S2 APARTMENT | 06-FEB-05:00 | -1061.62 | 0.00 | 2027.14 | 0.00 | 0.00 | 0.00 | 194.99 | 26.04 | 223.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -469.39 | 0.00 | -415.10 | -525.75 |
| M SW APARTMENT | 06-FEB-01:10 | -2122.69 | 0.00 | 5468.84 | 0.00 | 0.00 | 0.00 | 389.98 | 17.37 | 482.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1610.06 | 0.00 | -2322.69 | -303.42 |
| M NW APARTMENT | 06-FEB-01:00 | -2122.70 | 0.00 | 6117.48 | 0.00 | 0.00 | 0.00 | 389.98 | 17.37 | 529.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1628.52 | 0.00 | -2362.88 | -940.50 |
| M SE APARTMENT | 06-FEB-01:10 | -2122.69 | 0.00 | 5420.80 | 0.00 | 0.00 | 0.00 | 389.98 | 17.37 | 482.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1589.23 | 0.00 | -2322.69 | -276.20 |
| M NE APARTMENT | 06-FEB-01:00 | -2122.70 | 0.00 | 6054.57 | 0.00 | 0.00 | 0.00 | 389.98 | 17.37 | 529.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1607.72 | 0.00 | -2362.88 | -898.39 |
| M N1 APARTMENT | 06-FEB-01:10 | -2122.97 | 0.00 | 4124.83 | 0.00 | 0.00 | 0.00 | 389.98 | 17.37 | 482.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -992.41 | 0.00 | -1400.99 | -498.48 |
| M N2 APARTMENT | 06-FEB-01:10 | -2122.97 | 0.00 | 4121.23 | 0.00 | 0.00 | 0.00 | 389.98 | 17.37 | 482.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -992.47 | 0.00 | -1400.99 | -494.83 |
| M S1 APARTMENT | 06-FEB-01:10 | -2123.01 | 0.00 | 3620.21 | 0.00 | 0.00 | 0.00 | 389.98 | 17.37 | 482.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -969.92 | 0.00 | -1400.99 | -16.31 |
| M S2 APARTMENT | 06-FEB-01:10 | -2123.01 | 0.00 | 3617.60 | 0.00 | 0.00 | 0.00 | 389.98 | 17.37 | 482.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -969.97 | 0.00 | -1400.99 | -13.65 |
| T SW APARTMENT | 06-FEB-05:00 | -1061.34 | 0.00 | 4466.27 | 0.00 | 0.00 | 0.00 | 194.99 | 26.04 | 223.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -773.31 | 0.00 | -1310.52 | -1765.82 |
| T NW APARTMENT | 06-FEB-01:00 | -1061.27 | 0.00 | 4665.30 | 0.00 | 0.00 | 0.00 | 194.99 | 8.68 | 264.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -794.97 | 0.00 | -1564.62 | -1712.99 |
| T SE APARTMENT | 06-FEB-05:00 | -1061.34 | 0.00 | 4446.51 | 0.00 | 0.00 | 0.00 | 194.99 | 26.04 | 223.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -762.65 | 0.00 | -1310.52 | -1756.72 |
| T NE APARTMENT | 06-FEB-01:00 | -1061.27 | 0.00 | 4642.03 | 0.00 | 0.00 | 0.00 | 194.99 | 8.68 | 264.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -784.02 | 0.00 | -1564.62 | -1700.67 |
| T N1 APARTMENT | 06-FEB-01:10 | -1061.41 | 0.00 | 3369.81 | 0.00 | 0.00 | 0.00 | 194.99 | 8.68 | 241.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -485.72 | 0.00 | -927.69 | -1340.00 |
| T N2 APARTMENT | 06-FEB-01:10 | -1061.41 | 0.00 | 3368.70 | 0.00 | 0.00 | 0.00 | 194.99 | 8.68 | 241.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -485.73 | 0.00 | -927.69 | -1338.88 |
| T S1 APARTMENT | 06-FEB-05:00 | -1061.46 | 0.00 | 3215.94 | 0.00 | 0.00 | 0.00 | 194.99 | 26.04 | 223.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -466.66 | 0.00 | -790.47 | -1342.05 |
| T S2 APARTMENT | 06-FEB-05:00 | -1061.46 | 0.00 | 3214.92 | 0.00 | 0.00 | 0.00 | 194.99 | 26.04 | 223.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -466.67 | 0.00 | -790.47 | -1341.02 |
| T CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| G CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Total Facility | 06-FEB-07:01 | -32829.65 | 0.00 | 91626.87 | 0.00 | 0.00 | 0.00 | 6786.41 | 3348.00 | 12363.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -19270.64 | 0.00 | -42842.74 | -19181.71 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 09:15:04
System Ventilation Requirements for Cooling| Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
| SPLIT GSW | 0.3440 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.3440 | 0.0754 | 1.0000 | Not calculated | 0.0260 | 0.0754 | ||
| SPLIT GNW | 0.3281 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.3281 | 0.0791 | 1.0000 | Not calculated | 0.0260 | 0.0791 | ||
| SPLIT OFFICE | 0.4024 | 0.0000 | 4.7495 | 1.0000 | Calculated from schedules | 0.0381 | 0.4024 | 0.0947 | 1.0000 | Not calculated | 0.0381 | 0.0947 | ||
| SPLIT GNE | 0.3027 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.3027 | 0.0857 | 1.0000 | Not calculated | 0.0260 | 0.0857 | ||
| SPLIT GN1 | 0.2714 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.2714 | 0.0956 | 1.0000 | Not calculated | 0.0260 | 0.0956 | ||
| SPLIT GN2 | 0.2712 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.2712 | 0.0957 | 1.0000 | Not calculated | 0.0260 | 0.0957 | ||
| SPLIT GS1 | 0.2922 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.2922 | 0.0888 | 1.0000 | Not calculated | 0.0260 | 0.0888 | ||
| SPLIT GS2 | 0.2941 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.2941 | 0.0882 | 1.0000 | Not calculated | 0.0260 | 0.0882 | ||
| SPLIT MSW | 0.8360 | 0.0000 | 5.0000 | 1.0000 | Calculated from schedules | 0.0519 | 0.8360 | 0.0621 | 1.0000 | Not calculated | 0.0519 | 0.0621 | ||
| SPLIT MNW | 0.8103 | 0.0000 | 5.0000 | 1.0000 | Calculated from schedules | 0.0519 | 0.8103 | 0.0641 | 1.0000 | Not calculated | 0.0519 | 0.0641 | ||
| SPLIT MSE | 0.7625 | 0.0000 | 5.0000 | 1.0000 | Calculated from schedules | 0.0519 | 0.7625 | 0.0681 | 1.0000 | Not calculated | 0.0519 | 0.0681 | ||
| SPLIT MNE | 0.7374 | 0.0000 | 5.0000 | 1.0000 | Calculated from schedules | 0.0519 | 0.7374 | 0.0704 | 1.0000 | Not calculated | 0.0519 | 0.0704 | ||
| SPLIT MN1 | 0.6604 | 0.0000 | 5.0000 | 1.0000 | Calculated from schedules | 0.0519 | 0.6604 | 0.0786 | 1.0000 | Not calculated | 0.0519 | 0.0786 | ||
| SPLIT MN2 | 0.6589 | 0.0000 | 5.0000 | 1.0000 | Calculated from schedules | 0.0519 | 0.6589 | 0.0788 | 1.0000 | Not calculated | 0.0519 | 0.0788 | ||
| SPLIT MS1 | 0.6905 | 0.0000 | 5.0000 | 1.0000 | Calculated from schedules | 0.0519 | 0.6905 | 0.0752 | 1.0000 | Not calculated | 0.0519 | 0.0752 | ||
| SPLIT MS2 | 0.6889 | 0.0000 | 5.0000 | 1.0000 | Calculated from schedules | 0.0519 | 0.6889 | 0.0753 | 1.0000 | Not calculated | 0.0519 | 0.0753 | ||
| SPLIT TSW | 0.4546 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.4546 | 0.0571 | 1.0000 | Not calculated | 0.0260 | 0.0571 | ||
| SPLIT TNW | 0.4508 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.4508 | 0.0576 | 1.0000 | Not calculated | 0.0260 | 0.0576 | ||
| SPLIT TSE | 0.4010 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.4010 | 0.0647 | 1.0000 | Not calculated | 0.0260 | 0.0647 | ||
| SPLIT TNE | 0.3971 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.3971 | 0.0654 | 1.0000 | Not calculated | 0.0260 | 0.0654 | ||
| SPLIT TN1 | 0.3704 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.3704 | 0.0701 | 1.0000 | Not calculated | 0.0260 | 0.0701 | ||
| SPLIT TN2 | 0.3684 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.3684 | 0.0704 | 1.0000 | Not calculated | 0.0260 | 0.0704 | ||
| SPLIT TS1 | 0.3754 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.3754 | 0.0691 | 1.0000 | Not calculated | 0.0260 | 0.0691 | ||
| SPLIT TS2 | 0.3735 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.3735 | 0.0695 | 1.0000 | Not calculated | 0.0260 | 0.0695 |
| Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
| SPLIT GSW | 0.3440 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.3440 | 1.0000 | 1.0000 | Not calculated | 0.0260 | 0.0754 | ||
| SPLIT GNW | 0.3281 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.3281 | 1.0000 | 1.0000 | Not calculated | 0.0260 | 0.0791 | ||
| SPLIT OFFICE | 0.4024 | 0.0000 | 4.7495 | 1.0000 | Calculated from schedules | 0.0381 | 0.4024 | 1.0000 | 1.0000 | Not calculated | 0.0381 | 0.0947 | ||
| SPLIT GNE | 0.3027 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.3027 | 1.0000 | 1.0000 | Not calculated | 0.0260 | 0.0857 | ||
| SPLIT GN1 | 0.2714 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.2714 | 1.0000 | 1.0000 | Not calculated | 0.0260 | 0.0956 | ||
| SPLIT GN2 | 0.2712 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.2712 | 1.0000 | 1.0000 | Not calculated | 0.0260 | 0.0957 | ||
| SPLIT GS1 | 0.2922 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.2922 | 1.0000 | 1.0000 | Not calculated | 0.0260 | 0.0888 | ||
| SPLIT GS2 | 0.2941 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.2941 | 1.0000 | 1.0000 | Not calculated | 0.0260 | 0.0882 | ||
| SPLIT MSW | 0.8360 | 0.0000 | 5.0000 | 1.0000 | Calculated from schedules | 0.0519 | 0.8360 | 1.0000 | 1.0000 | Not calculated | 0.0519 | 0.0621 | ||
| SPLIT MNW | 0.8103 | 0.0000 | 5.0000 | 1.0000 | Calculated from schedules | 0.0519 | 0.8103 | 1.0000 | 1.0000 | Not calculated | 0.0519 | 0.0641 | ||
| SPLIT MSE | 0.7625 | 0.0000 | 5.0000 | 1.0000 | Calculated from schedules | 0.0519 | 0.7625 | 1.0000 | 1.0000 | Not calculated | 0.0519 | 0.0681 | ||
| SPLIT MNE | 0.7374 | 0.0000 | 5.0000 | 1.0000 | Calculated from schedules | 0.0519 | 0.7374 | 1.0000 | 1.0000 | Not calculated | 0.0519 | 0.0704 | ||
| SPLIT MN1 | 0.6604 | 0.0000 | 5.0000 | 1.0000 | Calculated from schedules | 0.0519 | 0.6604 | 1.0000 | 1.0000 | Not calculated | 0.0519 | 0.0786 | ||
| SPLIT MN2 | 0.6589 | 0.0000 | 5.0000 | 1.0000 | Calculated from schedules | 0.0519 | 0.6589 | 1.0000 | 1.0000 | Not calculated | 0.0519 | 0.0788 | ||
| SPLIT MS1 | 0.6905 | 0.0000 | 5.0000 | 1.0000 | Calculated from schedules | 0.0519 | 0.6905 | 1.0000 | 1.0000 | Not calculated | 0.0519 | 0.0752 | ||
| SPLIT MS2 | 0.6889 | 0.0000 | 5.0000 | 1.0000 | Calculated from schedules | 0.0519 | 0.6889 | 1.0000 | 1.0000 | Not calculated | 0.0519 | 0.0753 | ||
| SPLIT TSW | 0.4546 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.4546 | 1.0000 | 1.0000 | Not calculated | 0.0260 | 0.0571 | ||
| SPLIT TNW | 0.4508 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.4508 | 1.0000 | 1.0000 | Not calculated | 0.0260 | 0.0576 | ||
| SPLIT TSE | 0.4010 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.4010 | 1.0000 | 1.0000 | Not calculated | 0.0260 | 0.0647 | ||
| SPLIT TNE | 0.3971 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.3971 | 1.0000 | 1.0000 | Not calculated | 0.0260 | 0.0654 | ||
| SPLIT TN1 | 0.3704 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.3704 | 1.0000 | 1.0000 | Not calculated | 0.0260 | 0.0701 | ||
| SPLIT TN2 | 0.3684 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.3684 | 1.0000 | 1.0000 | Not calculated | 0.0260 | 0.0704 | ||
| SPLIT TS1 | 0.3754 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.3754 | 1.0000 | 1.0000 | Not calculated | 0.0260 | 0.0691 | ||
| SPLIT TS2 | 0.3735 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.3735 | 1.0000 | 1.0000 | Not calculated | 0.0260 | 0.0695 |
| AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
| G SW APARTMENT | SPLIT GSW | 0.000000 | 2.5000 | 0.000294 | 88.25 | 0.0260 | 1.0000 | 0.0260 | 1.000 | 0.0260 |
| G NW APARTMENT | SPLIT GNW | 0.000000 | 2.5000 | 0.000294 | 88.25 | 0.0260 | 1.0000 | 0.0260 | 1.000 | 0.0260 |
| OFFICE | SPLIT OFFICE | 0.000000 | 4.7495 | 0.000432 | 88.25 | 0.0381 | 1.0000 | 0.0381 | 1.000 | 0.0381 |
| G NE APARTMENT | SPLIT GNE | 0.000000 | 2.5000 | 0.000294 | 88.25 | 0.0260 | 1.0000 | 0.0260 | 1.000 | 0.0260 |
| G N1 APARTMENT | SPLIT GN1 | 0.000000 | 2.5000 | 0.000294 | 88.25 | 0.0260 | 1.0000 | 0.0260 | 1.000 | 0.0260 |
| G N2 APARTMENT | SPLIT GN2 | 0.000000 | 2.5000 | 0.000294 | 88.25 | 0.0260 | 1.0000 | 0.0260 | 1.000 | 0.0260 |
| G S1 APARTMENT | SPLIT GS1 | 0.000000 | 2.5000 | 0.000294 | 88.25 | 0.0260 | 1.0000 | 0.0260 | 1.000 | 0.0260 |
| G S2 APARTMENT | SPLIT GS2 | 0.000000 | 2.5000 | 0.000294 | 88.25 | 0.0260 | 1.0000 | 0.0260 | 1.000 | 0.0260 |
| M SW APARTMENT | SPLIT MSW | 0.000000 | 5.0000 | 0.000294 | 176.50 | 0.0519 | 1.0000 | 0.0519 | 1.000 | 0.0519 |
| M NW APARTMENT | SPLIT MNW | 0.000000 | 5.0000 | 0.000294 | 176.50 | 0.0519 | 1.0000 | 0.0519 | 1.000 | 0.0519 |
| M SE APARTMENT | SPLIT MSE | 0.000000 | 5.0000 | 0.000294 | 176.50 | 0.0519 | 1.0000 | 0.0519 | 1.000 | 0.0519 |
| M NE APARTMENT | SPLIT MNE | 0.000000 | 5.0000 | 0.000294 | 176.50 | 0.0519 | 1.0000 | 0.0519 | 1.000 | 0.0519 |
| M N1 APARTMENT | SPLIT MN1 | 0.000000 | 5.0000 | 0.000294 | 176.50 | 0.0519 | 1.0000 | 0.0519 | 1.000 | 0.0519 |
| M N2 APARTMENT | SPLIT MN2 | 0.000000 | 5.0000 | 0.000294 | 176.50 | 0.0519 | 1.0000 | 0.0519 | 1.000 | 0.0519 |
| M S1 APARTMENT | SPLIT MS1 | 0.000000 | 5.0000 | 0.000294 | 176.50 | 0.0519 | 1.0000 | 0.0519 | 1.000 | 0.0519 |
| M S2 APARTMENT | SPLIT MS2 | 0.000000 | 5.0000 | 0.000294 | 176.50 | 0.0519 | 1.0000 | 0.0519 | 1.000 | 0.0519 |
| T SW APARTMENT | SPLIT TSW | 0.000000 | 2.5000 | 0.000294 | 88.25 | 0.0260 | 1.0000 | 0.0260 | 1.000 | 0.0260 |
| T NW APARTMENT | SPLIT TNW | 0.000000 | 2.5000 | 0.000294 | 88.25 | 0.0260 | 1.0000 | 0.0260 | 1.000 | 0.0260 |
| T SE APARTMENT | SPLIT TSE | 0.000000 | 2.5000 | 0.000294 | 88.25 | 0.0260 | 1.0000 | 0.0260 | 1.000 | 0.0260 |
| T NE APARTMENT | SPLIT TNE | 0.000000 | 2.5000 | 0.000294 | 88.25 | 0.0260 | 1.0000 | 0.0260 | 1.000 | 0.0260 |
| T N1 APARTMENT | SPLIT TN1 | 0.000000 | 2.5000 | 0.000294 | 88.25 | 0.0260 | 1.0000 | 0.0260 | 1.000 | 0.0260 |
| T N2 APARTMENT | SPLIT TN2 | 0.000000 | 2.5000 | 0.000294 | 88.25 | 0.0260 | 1.0000 | 0.0260 | 1.000 | 0.0260 |
| T S1 APARTMENT | SPLIT TS1 | 0.000000 | 2.5000 | 0.000294 | 88.25 | 0.0260 | 1.0000 | 0.0260 | 1.000 | 0.0260 |
| T S2 APARTMENT | SPLIT TS2 | 0.000000 | 2.5000 | 0.000294 | 88.25 | 0.0260 | 1.0000 | 0.0260 | 1.000 | 0.0260 |
| People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
| SPLIT GSW | 0.000000 | 2.50 | 0.000294 | 88.2493 | 0.0260 | 0.0260 | 0.0260 |
| SPLIT GNW | 0.000000 | 2.50 | 0.000294 | 88.2493 | 0.0260 | 0.0260 | 0.0260 |
| SPLIT OFFICE | 0.000000 | 4.75 | 0.000432 | 88.2493 | 0.0381 | 0.0381 | 0.0381 |
| SPLIT GNE | 0.000000 | 2.50 | 0.000294 | 88.2493 | 0.0260 | 0.0260 | 0.0260 |
| SPLIT GN1 | 0.000000 | 2.50 | 0.000294 | 88.2493 | 0.0260 | 0.0260 | 0.0260 |
| SPLIT GN2 | 0.000000 | 2.50 | 0.000294 | 88.2493 | 0.0260 | 0.0260 | 0.0260 |
| SPLIT GS1 | 0.000000 | 2.50 | 0.000294 | 88.2493 | 0.0260 | 0.0260 | 0.0260 |
| SPLIT GS2 | 0.000000 | 2.50 | 0.000294 | 88.2493 | 0.0260 | 0.0260 | 0.0260 |
| SPLIT MSW | 0.000000 | 5.00 | 0.000294 | 176.4985 | 0.0519 | 0.0519 | 0.0519 |
| SPLIT MNW | 0.000000 | 5.00 | 0.000294 | 176.4985 | 0.0519 | 0.0519 | 0.0519 |
| SPLIT MSE | 0.000000 | 5.00 | 0.000294 | 176.4985 | 0.0519 | 0.0519 | 0.0519 |
| SPLIT MNE | 0.000000 | 5.00 | 0.000294 | 176.4985 | 0.0519 | 0.0519 | 0.0519 |
| SPLIT MN1 | 0.000000 | 5.00 | 0.000294 | 176.4985 | 0.0519 | 0.0519 | 0.0519 |
| SPLIT MN2 | 0.000000 | 5.00 | 0.000294 | 176.4985 | 0.0519 | 0.0519 | 0.0519 |
| SPLIT MS1 | 0.000000 | 5.00 | 0.000294 | 176.4985 | 0.0519 | 0.0519 | 0.0519 |
| SPLIT MS2 | 0.000000 | 5.00 | 0.000294 | 176.4985 | 0.0519 | 0.0519 | 0.0519 |
| SPLIT TSW | 0.000000 | 2.50 | 0.000294 | 88.2493 | 0.0260 | 0.0260 | 0.0260 |
| SPLIT TNW | 0.000000 | 2.50 | 0.000294 | 88.2493 | 0.0260 | 0.0260 | 0.0260 |
| SPLIT TSE | 0.000000 | 2.50 | 0.000294 | 88.2493 | 0.0260 | 0.0260 | 0.0260 |
| SPLIT TNE | 0.000000 | 2.50 | 0.000294 | 88.2493 | 0.0260 | 0.0260 | 0.0260 |
| SPLIT TN1 | 0.000000 | 2.50 | 0.000294 | 88.2493 | 0.0260 | 0.0260 | 0.0260 |
| SPLIT TN2 | 0.000000 | 2.50 | 0.000294 | 88.2493 | 0.0260 | 0.0260 | 0.0260 |
| SPLIT TS1 | 0.000000 | 2.50 | 0.000294 | 88.2493 | 0.0260 | 0.0260 | 0.0260 |
| SPLIT TS2 | 0.000000 | 2.50 | 0.000294 | 88.2493 | 0.0260 | 0.0260 | 0.0260 |
| AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
| G SW APARTMENT | SPLIT GSW | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.3440 | 0.3440 | 0.3440 | No | 0.0260 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| G NW APARTMENT | SPLIT GNW | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.3281 | 0.3281 | 0.3281 | No | 0.0260 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| OFFICE | SPLIT OFFICE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4024 | 0.4024 | 0.4024 | No | 0.0381 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| G NE APARTMENT | SPLIT GNE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.3027 | 0.3027 | 0.3027 | No | 0.0260 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| G N1 APARTMENT | SPLIT GN1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.2714 | 0.2714 | 0.2714 | No | 0.0260 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| G N2 APARTMENT | SPLIT GN2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.2712 | 0.2712 | 0.2712 | No | 0.0260 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| G S1 APARTMENT | SPLIT GS1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.2922 | 0.2922 | 0.2922 | No | 0.0260 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| G S2 APARTMENT | SPLIT GS2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.2941 | 0.2941 | 0.2941 | No | 0.0260 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| M SW APARTMENT | SPLIT MSW | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8360 | 0.8360 | 0.8360 | No | 0.0519 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| M NW APARTMENT | SPLIT MNW | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8103 | 0.8103 | 0.8103 | No | 0.0519 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| M SE APARTMENT | SPLIT MSE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.7625 | 0.7625 | 0.7625 | No | 0.0519 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| M NE APARTMENT | SPLIT MNE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.7374 | 0.7374 | 0.7374 | No | 0.0519 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| M N1 APARTMENT | SPLIT MN1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.6604 | 0.6604 | 0.6604 | No | 0.0519 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| M N2 APARTMENT | SPLIT MN2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.6589 | 0.6589 | 0.6589 | No | 0.0519 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| M S1 APARTMENT | SPLIT MS1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.6905 | 0.6905 | 0.6905 | No | 0.0519 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| M S2 APARTMENT | SPLIT MS2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.6889 | 0.6889 | 0.6889 | No | 0.0519 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| T SW APARTMENT | SPLIT TSW | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4546 | 0.4546 | 0.4546 | No | 0.0260 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| T NW APARTMENT | SPLIT TNW | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4508 | 0.4508 | 0.4508 | No | 0.0260 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| T SE APARTMENT | SPLIT TSE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4010 | 0.4010 | 0.4010 | No | 0.0260 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| T NE APARTMENT | SPLIT TNE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.3971 | 0.3971 | 0.3971 | No | 0.0260 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| T N1 APARTMENT | SPLIT TN1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.3704 | 0.3704 | 0.3704 | No | 0.0260 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| T N2 APARTMENT | SPLIT TN2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.3684 | 0.3684 | 0.3684 | No | 0.0260 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| T S1 APARTMENT | SPLIT TS1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.3754 | 0.3754 | 0.3754 | No | 0.0260 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| T S2 APARTMENT | SPLIT TS2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.3735 | 0.3735 | 0.3735 | No | 0.0260 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
| SPLIT GSW | 0.3440 | 0.3440 | 0.3440 | 0.3440 | 0.0260 | 1.0000 |
| SPLIT GNW | 0.3281 | 0.3281 | 0.3281 | 0.3281 | 0.0260 | 1.0000 |
| SPLIT OFFICE | 0.4024 | 0.4024 | 0.4024 | 0.4024 | 0.0381 | 1.0000 |
| SPLIT GNE | 0.3027 | 0.3027 | 0.3027 | 0.3027 | 0.0260 | 1.0000 |
| SPLIT GN1 | 0.2714 | 0.2714 | 0.2714 | 0.2714 | 0.0260 | 1.0000 |
| SPLIT GN2 | 0.2712 | 0.2712 | 0.2712 | 0.2712 | 0.0260 | 1.0000 |
| SPLIT GS1 | 0.2922 | 0.2922 | 0.2922 | 0.2922 | 0.0260 | 1.0000 |
| SPLIT GS2 | 0.2941 | 0.2941 | 0.2941 | 0.2941 | 0.0260 | 1.0000 |
| SPLIT MSW | 0.8360 | 0.8360 | 0.8360 | 0.8360 | 0.0519 | 1.0000 |
| SPLIT MNW | 0.8103 | 0.8103 | 0.8103 | 0.8103 | 0.0519 | 1.0000 |
| SPLIT MSE | 0.7625 | 0.7625 | 0.7625 | 0.7625 | 0.0519 | 1.0000 |
| SPLIT MNE | 0.7374 | 0.7374 | 0.7374 | 0.7374 | 0.0519 | 1.0000 |
| SPLIT MN1 | 0.6604 | 0.6604 | 0.6604 | 0.6604 | 0.0519 | 1.0000 |
| SPLIT MN2 | 0.6589 | 0.6589 | 0.6589 | 0.6589 | 0.0519 | 1.0000 |
| SPLIT MS1 | 0.6905 | 0.6905 | 0.6905 | 0.6905 | 0.0519 | 1.0000 |
| SPLIT MS2 | 0.6889 | 0.6889 | 0.6889 | 0.6889 | 0.0519 | 1.0000 |
| SPLIT TSW | 0.4546 | 0.4546 | 0.4546 | 0.4546 | 0.0260 | 1.0000 |
| SPLIT TNW | 0.4508 | 0.4508 | 0.4508 | 0.4508 | 0.0260 | 1.0000 |
| SPLIT TSE | 0.4010 | 0.4010 | 0.4010 | 0.4010 | 0.0260 | 1.0000 |
| SPLIT TNE | 0.3971 | 0.3971 | 0.3971 | 0.3971 | 0.0260 | 1.0000 |
| SPLIT TN1 | 0.3704 | 0.3704 | 0.3704 | 0.3704 | 0.0260 | 1.0000 |
| SPLIT TN2 | 0.3684 | 0.3684 | 0.3684 | 0.3684 | 0.0260 | 1.0000 |
| SPLIT TS1 | 0.3754 | 0.3754 | 0.3754 | 0.3754 | 0.0260 | 1.0000 |
| SPLIT TS2 | 0.3735 | 0.3735 | 0.3735 | 0.3735 | 0.0260 | 1.0000 |
| AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
| G SW APARTMENT | SPLIT GSW | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.3440 | 0.3440 | 0.3440 | No | 0.0260 | 0.2247 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| G NW APARTMENT | SPLIT GNW | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.3281 | 0.3281 | 0.3281 | No | 0.0260 | 0.2363 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| OFFICE | SPLIT OFFICE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4024 | 0.4024 | 0.4024 | No | 0.0381 | 0.2752 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| G NE APARTMENT | SPLIT GNE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.3027 | 0.3027 | 0.3027 | No | 0.0260 | 0.2371 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| G N1 APARTMENT | SPLIT GN1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.2714 | 0.2714 | 0.2714 | No | 0.0260 | 0.3882 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| G N2 APARTMENT | SPLIT GN2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.2712 | 0.2712 | 0.2712 | No | 0.0260 | 0.3883 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| G S1 APARTMENT | SPLIT GS1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.2922 | 0.2922 | 0.2922 | No | 0.0260 | 0.3575 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| G S2 APARTMENT | SPLIT GS2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.2941 | 0.2941 | 0.2941 | No | 0.0260 | 0.3554 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| M SW APARTMENT | SPLIT MSW | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8360 | 0.8360 | 0.8360 | No | 0.0519 | 0.2338 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| M NW APARTMENT | SPLIT MNW | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8103 | 0.8103 | 0.8103 | No | 0.0519 | 0.2491 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| M SE APARTMENT | SPLIT MSE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.7625 | 0.7625 | 0.7625 | No | 0.0519 | 0.2348 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| M NE APARTMENT | SPLIT MNE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.7374 | 0.7374 | 0.7374 | No | 0.0519 | 0.2501 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| M N1 APARTMENT | SPLIT MN1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.6604 | 0.6604 | 0.6604 | No | 0.0519 | 0.4611 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| M N2 APARTMENT | SPLIT MN2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.6589 | 0.6589 | 0.6589 | No | 0.0519 | 0.4612 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| M S1 APARTMENT | SPLIT MS1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.6905 | 0.6905 | 0.6905 | No | 0.0519 | 0.4126 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| M S2 APARTMENT | SPLIT MS2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.6889 | 0.6889 | 0.6889 | No | 0.0519 | 0.4126 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| T SW APARTMENT | SPLIT TSW | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4546 | 0.4546 | 0.4546 | No | 0.0260 | 0.1438 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| T NW APARTMENT | SPLIT TNW | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4508 | 0.4508 | 0.4508 | No | 0.0260 | 0.1497 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| T SE APARTMENT | SPLIT TSE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4010 | 0.4010 | 0.4010 | No | 0.0260 | 0.1443 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| T NE APARTMENT | SPLIT TNE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.3971 | 0.3971 | 0.3971 | No | 0.0260 | 0.1502 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| T N1 APARTMENT | SPLIT TN1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.3704 | 0.3704 | 0.3704 | No | 0.0260 | 0.2254 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| T N2 APARTMENT | SPLIT TN2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.3684 | 0.3684 | 0.3684 | No | 0.0260 | 0.2254 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| T S1 APARTMENT | SPLIT TS1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.3754 | 0.3754 | 0.3754 | No | 0.0260 | 0.2124 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| T S2 APARTMENT | SPLIT TS2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.3735 | 0.3735 | 0.3735 | No | 0.0260 | 0.2124 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
| SPLIT GSW | 0.3440 | 0.3440 | 0.3440 | 0.3440 | 0.0260 | 1.0000 |
| SPLIT GNW | 0.3281 | 0.3281 | 0.3281 | 0.3281 | 0.0260 | 1.0000 |
| SPLIT OFFICE | 0.4024 | 0.4024 | 0.4024 | 0.4024 | 0.0381 | 1.0000 |
| SPLIT GNE | 0.3027 | 0.3027 | 0.3027 | 0.3027 | 0.0260 | 1.0000 |
| SPLIT GN1 | 0.2714 | 0.2714 | 0.2714 | 0.2714 | 0.0260 | 1.0000 |
| SPLIT GN2 | 0.2712 | 0.2712 | 0.2712 | 0.2712 | 0.0260 | 1.0000 |
| SPLIT GS1 | 0.2922 | 0.2922 | 0.2922 | 0.2922 | 0.0260 | 1.0000 |
| SPLIT GS2 | 0.2941 | 0.2941 | 0.2941 | 0.2941 | 0.0260 | 1.0000 |
| SPLIT MSW | 0.8360 | 0.8360 | 0.8360 | 0.8360 | 0.0519 | 1.0000 |
| SPLIT MNW | 0.8103 | 0.8103 | 0.8103 | 0.8103 | 0.0519 | 1.0000 |
| SPLIT MSE | 0.7625 | 0.7625 | 0.7625 | 0.7625 | 0.0519 | 1.0000 |
| SPLIT MNE | 0.7374 | 0.7374 | 0.7374 | 0.7374 | 0.0519 | 1.0000 |
| SPLIT MN1 | 0.6604 | 0.6604 | 0.6604 | 0.6604 | 0.0519 | 1.0000 |
| SPLIT MN2 | 0.6589 | 0.6589 | 0.6589 | 0.6589 | 0.0519 | 1.0000 |
| SPLIT MS1 | 0.6905 | 0.6905 | 0.6905 | 0.6905 | 0.0519 | 1.0000 |
| SPLIT MS2 | 0.6889 | 0.6889 | 0.6889 | 0.6889 | 0.0519 | 1.0000 |
| SPLIT TSW | 0.4546 | 0.4546 | 0.4546 | 0.4546 | 0.0260 | 1.0000 |
| SPLIT TNW | 0.4508 | 0.4508 | 0.4508 | 0.4508 | 0.0260 | 1.0000 |
| SPLIT TSE | 0.4010 | 0.4010 | 0.4010 | 0.4010 | 0.0260 | 1.0000 |
| SPLIT TNE | 0.3971 | 0.3971 | 0.3971 | 0.3971 | 0.0260 | 1.0000 |
| SPLIT TN1 | 0.3704 | 0.3704 | 0.3704 | 0.3704 | 0.0260 | 1.0000 |
| SPLIT TN2 | 0.3684 | 0.3684 | 0.3684 | 0.3684 | 0.0260 | 1.0000 |
| SPLIT TS1 | 0.3754 | 0.3754 | 0.3754 | 0.3754 | 0.0260 | 1.0000 |
| SPLIT TS2 | 0.3735 | 0.3735 | 0.3735 | 0.3735 | 0.0260 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 09:15:04
Sec1.1A-General Information| Data | |
| Weather File | RUNPERIOD 1 ** New York-John F Kennedy Intl AP NY USA TMY3 WMO#=744860 |
| Total gross floor area [m2] | 3134.61 |
| Principal Heating Source | Natural Gas |
| Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
| G SW APARTMENT | 88.25 | 88.25 | 0.00 | 117.85 |
| G NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
| OFFICE | 88.25 | 88.25 | 0.00 | 33.56 |
| G NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
| G N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
| G N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
| G S1 APARTMENT | 88.25 | 88.25 | 0.00 | 117.85 |
| G S2 APARTMENT | 88.25 | 88.25 | 0.00 | 117.85 |
| M SW APARTMENT | 88.25 | 88.25 | 0.00 | 117.85 |
| M NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
| M SE APARTMENT | 88.25 | 88.25 | 0.00 | 117.85 |
| M NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
| M N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
| M N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
| M S1 APARTMENT | 88.25 | 88.25 | 0.00 | 117.85 |
| M S2 APARTMENT | 88.25 | 88.25 | 0.00 | 117.85 |
| T SW APARTMENT | 88.25 | 88.25 | 0.00 | 117.85 |
| T NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
| T SE APARTMENT | 88.25 | 88.25 | 0.00 | 117.85 |
| T NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
| T N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
| T N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
| T S1 APARTMENT | 88.25 | 88.25 | 0.00 | 117.85 |
| T S2 APARTMENT | 88.25 | 88.25 | 0.00 | 117.85 |
| T CORRIDOR | 77.66 | 0.00 | 77.66 | 168.00 |
| G CORRIDOR | 77.66 | 0.00 | 77.66 | 168.00 |
| M CORRIDOR | 77.66 | 0.00 | 77.66 | 168.00 |
| Totals | 3134.61 | 2823.98 | 310.64 |
| Data | |
| Number of hours heating loads not met | 0.00 |
| Number of hours cooling loads not met | 0.00 |
| Number of hours not met | 0.00 |
| Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
| None |
| Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
| Heating -- General | 0.00 | 0.00 | 378.88 | 105858.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Cooling -- General | 129.73 | 27872.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Lighting -- LightsWired | 94.96 | 5496.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Lighting -- LightsPlugIn | 4.27 | 407.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Lighting -- General | 49.98 | 3183.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment -- MiscPlug | 388.06 | 18541.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment -- ElevatorLift | 65.48 | 4006.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment -- ElevatorLightsFan | 5.11 | 162.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans -- Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans -- General | 101.80 | 8509.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Recovery -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems -- Water Heater | 452.58 | 37846.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Process Subtotal [GJ] | Total Energy Use [GJ] | |
| Electricity | 458.66 | 1291.98 |
| Natural Gas | 0.00 | 378.88 |
| Additional | 0.00 | 0.00 |
| Total | 458.66 | 1670.86 |
| Process Subtotal [$] | Total Energy Cost [$] | |
| Electricity | 0.00 | |
| Natural Gas | 0.00 | |
| Additional | 0.00 | |
| Total | 0.00 |
| Rated Capacity [kW] | Annual Energy Generated [GJ] | |
| Photovoltaic | 0.00 | 0.00 |
| Wind | 0.00 | 0.00 |
| Electricty [MJ/m2] | |
| Interior Lighting (All) | 31.66 |
| Space Heating | 0.00 |
| Space Cooling | 41.39 |
| Fans (All) | 32.48 |
| Service Water Heating | 144.38 |
| Receptacle Equipment | 146.32 |
| Miscellaneous (All) | 412.17 |
| Subtotal | 412.17 |
| Natural Gas [MJ/m2] | |
| Space Heating | 120.87 |
| Service Water Heating | 0.00 |
| Miscellaneous (All) | 120.87 |
| Subtotal | 120.87 |
| Additional [MJ/m2] | |
| Subtotal | 0.00 |
| Miscellaneous | 0.00 |
| Percent [%] | |
| Interior Lighting (All) | 5.94 |
| Space Heating | 22.68 |
| Space Cooling | 7.76 |
| Fans (All) | 6.09 |
| Service Water Heating | 27.09 |
| Receptacle Equipment | 27.45 |
| Miscellaneous | 2.99 |
| Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
| OCC_APT_SCH_STAY_HOME_FAMILY | 5993. | 8760. |
| OCC_APT_SCH_CORRIDOR | 5993. | 8760. |
| OCC_APT_SCH_WORKING_FAMILY | 5845. | 6055. |
| OCC_OFF_SCH | 2210. | 2340. |
| OCC_OFF_W_SB_SCH | 1820. | 1820. |
| LTG_SCH_OFFICE | 2435. | 8760. |
| LTG_SCH_CORRIDOR | 8760. | 8760. |
| LTG_SCH_APARTMENT_HARDWIRED | 527. | 8760. |
| LTG_SCH_APARTMENT_PLUGIN | 527. | 8760. |
| EQP_APT_SCH | 5763. | 8760. |
| EQP_OFF_SCH | 4531. | 8760. |
| INF_APT_SCH | 8760. | 8760. |
| INF_OFF_SCH | 8760. | 8760. |
| INF_COR_SCH | 8760. | 8760. |
| INFIL_DOOR_OPENING_SCH | 1466. | 5840. |
| ALL OFF | 0. | 0. |
| ALL ON | 8760. | 8760. |
| ALWAYS_ON | 8760. | 8760. |
| ALLON_EXCEPT_DD | 8760. | 8760. |
| EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
| FAN_OFF_W_SB_SCH | 8240. | 8240. |
| APT_DHW_SCH | 4592. | 8760. |
| EXTERIOR_LTG_SCH | 4380. | 4380. |
| BLDG_ELEVATORS | 2270. | 8760. |
| ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
| ELEV_LIGHT_FAN_SCH_ADD_DF | 2154. | 8760. |
| SLIDING_DOORS_VENTILATION_AVAILABILITY_SCH | 5840. | 5840. |
| First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
| HTGSETP_APT_SCH | APTHEATINGSETPOINT | January | 21.10 | 365 | 21.10 | 365 |
| HTGSETP_DESIGN_OFF_SCH | OFFHEATINGSETPOINT | January | 21.10 | 365 | 21.10 | 365 |
| CLGSETP_APT_SCH | APTCOOLINGSETPOINT | July | 24.00 | 365 | 24.00 | 365 |
| CLGSETP_DESIGN_OFF_SCH | OFFCOOLINGSETPOINT | July | 23.90 | 365 | 23.90 | 365 |
| S HTGSETP_APT_SCH | S APARTMENT DUAL SP CONTROL | January | 21.10 | 365 | 21.10 | 365 |
| S CLGSETP_APT_SCH | S APARTMENT DUAL SP CONTROL | July | 24.00 | 365 | 24.00 | 365 |
| N HTGSETP_APT_SCH | N APARTMENT DUAL SP CONTROL | January | 21.10 | 365 | 21.10 | 365 |
| N CLGSETP_APT_SCH | N APARTMENT DUAL SP CONTROL | July | 24.00 | 365 | 24.00 | 365 |
| HTGSETP_OFF_SCH_YES_OPTIMUM | OFFICE DUAL SP CONTROL | January | 21.10 | 365 | 15.60 | 365 |
| CLGSETP_OFF_SCH_YES_OPTIMUM | OFFICE DUAL SP CONTROL | July | 24.00 | 365 | 29.40 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 09:15:04
Heat Index Hours| Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
| G SW APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| G NW APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| OFFICE | 7013.33 | 1658.33 | 88.33 | 0.00 | 0.00 |
| G NE APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| G N1 APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| G N2 APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| G S1 APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| G S2 APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M SW APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M NW APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M SE APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M NE APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M N1 APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M N2 APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M S1 APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M S2 APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T SW APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T NW APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T SE APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T NE APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T N1 APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T N2 APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T S1 APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T S2 APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T CORRIDOR | 6482.17 | 2129.67 | 148.17 | 0.00 | 0.00 |
| G CORRIDOR | 7303.17 | 1442.83 | 14.00 | 0.00 | 0.00 |
| M CORRIDOR | 5408.83 | 3351.17 | 0.00 | 0.00 | 0.00 |
| Min | 5408.83 | 0.00 | 0.00 | 0.00 | 0.00 |
| Max | 8760.00 | 3351.17 | 148.17 | 0.00 | 0.00 |
| Average | 8432.87 | 317.85 | 9.28 | 0.00 | 0.00 |
| Sum | 227687.50 | 8582.00 | 250.50 | 0.00 | 0.00 |
| Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
| G SW APARTMENT | 11830.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| G NW APARTMENT | 10585.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| OFFICE | 6998.00 | 2.00 | 0.00 | 0.00 | 0.00 |
| G NE APARTMENT | 10585.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| G N1 APARTMENT | 10585.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| G N2 APARTMENT | 10585.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| G S1 APARTMENT | 11830.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| G S2 APARTMENT | 11830.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M SW APARTMENT | 11830.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M NW APARTMENT | 10585.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M SE APARTMENT | 11830.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M NE APARTMENT | 10585.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M N1 APARTMENT | 10585.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M N2 APARTMENT | 10585.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M S1 APARTMENT | 11830.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M S2 APARTMENT | 11830.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T SW APARTMENT | 11830.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T NW APARTMENT | 10585.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T SE APARTMENT | 11830.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T NE APARTMENT | 10585.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T N1 APARTMENT | 10585.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T N2 APARTMENT | 10585.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T S1 APARTMENT | 11830.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T S2 APARTMENT | 11830.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T CORRIDOR | 17342.50 | 5344.00 | 308.50 | 0.00 | 0.00 |
| G CORRIDOR | 19008.17 | 3935.33 | 51.50 | 0.00 | 0.00 |
| M CORRIDOR | 14281.83 | 8713.17 | 0.00 | 0.00 | 0.00 |
| Min | 6998.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Max | 19008.17 | 8713.17 | 308.50 | 0.00 | 0.00 |
| Average | 11658.54 | 666.46 | 13.33 | 0.00 | 0.00 |
| Sum | 314780.50 | 17994.50 | 360.00 | 0.00 | 0.00 |
| Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
| G SW APARTMENT | 8000.17 | 759.83 | 0.00 | 0.00 | 0.00 |
| G NW APARTMENT | 7870.67 | 889.33 | 0.00 | 0.00 | 0.00 |
| OFFICE | 6667.17 | 2089.67 | 3.17 | 0.00 | 0.00 |
| G NE APARTMENT | 7854.33 | 905.67 | 0.00 | 0.00 | 0.00 |
| G N1 APARTMENT | 7778.17 | 981.83 | 0.00 | 0.00 | 0.00 |
| G N2 APARTMENT | 7777.67 | 982.33 | 0.00 | 0.00 | 0.00 |
| G S1 APARTMENT | 7969.17 | 790.83 | 0.00 | 0.00 | 0.00 |
| G S2 APARTMENT | 8078.00 | 682.00 | 0.00 | 0.00 | 0.00 |
| M SW APARTMENT | 8125.67 | 634.33 | 0.00 | 0.00 | 0.00 |
| M NW APARTMENT | 8043.67 | 716.33 | 0.00 | 0.00 | 0.00 |
| M SE APARTMENT | 8095.67 | 664.33 | 0.00 | 0.00 | 0.00 |
| M NE APARTMENT | 8019.50 | 740.50 | 0.00 | 0.00 | 0.00 |
| M N1 APARTMENT | 7951.00 | 809.00 | 0.00 | 0.00 | 0.00 |
| M N2 APARTMENT | 7949.17 | 810.83 | 0.00 | 0.00 | 0.00 |
| M S1 APARTMENT | 8078.83 | 681.17 | 0.00 | 0.00 | 0.00 |
| M S2 APARTMENT | 8078.83 | 681.17 | 0.00 | 0.00 | 0.00 |
| T SW APARTMENT | 7922.50 | 837.50 | 0.00 | 0.00 | 0.00 |
| T NW APARTMENT | 7885.67 | 874.33 | 0.00 | 0.00 | 0.00 |
| T SE APARTMENT | 7901.17 | 858.83 | 0.00 | 0.00 | 0.00 |
| T NE APARTMENT | 7883.00 | 877.00 | 0.00 | 0.00 | 0.00 |
| T N1 APARTMENT | 7869.17 | 890.83 | 0.00 | 0.00 | 0.00 |
| T N2 APARTMENT | 7869.17 | 890.83 | 0.00 | 0.00 | 0.00 |
| T S1 APARTMENT | 7916.83 | 843.17 | 0.00 | 0.00 | 0.00 |
| T S2 APARTMENT | 7915.67 | 844.33 | 0.00 | 0.00 | 0.00 |
| T CORRIDOR | 4256.17 | 3990.00 | 513.83 | 0.00 | 0.00 |
| G CORRIDOR | 6066.33 | 2590.83 | 102.83 | 0.00 | 0.00 |
| M CORRIDOR | 2987.17 | 5404.00 | 368.83 | 0.00 | 0.00 |
| Min | 2987.17 | 634.33 | 0.00 | 0.00 | 0.00 |
| Max | 8125.67 | 5404.00 | 513.83 | 0.00 | 0.00 |
| Average | 7511.50 | 1211.88 | 36.62 | 0.00 | 0.00 |
| Sum | 202810.50 | 32720.83 | 988.67 | 0.00 | 0.00 |
| Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
| G SW APARTMENT | 10648.67 | 1181.33 | 0.00 | 0.00 | 0.00 |
| G NW APARTMENT | 9381.00 | 1204.00 | 0.00 | 0.00 | 0.00 |
| OFFICE | 6626.67 | 373.33 | 0.00 | 0.00 | 0.00 |
| G NE APARTMENT | 9272.83 | 1312.17 | 0.00 | 0.00 | 0.00 |
| G N1 APARTMENT | 9282.50 | 1302.50 | 0.00 | 0.00 | 0.00 |
| G N2 APARTMENT | 9278.50 | 1306.50 | 0.00 | 0.00 | 0.00 |
| G S1 APARTMENT | 10611.50 | 1218.50 | 0.00 | 0.00 | 0.00 |
| G S2 APARTMENT | 10773.00 | 1057.00 | 0.00 | 0.00 | 0.00 |
| M SW APARTMENT | 10851.67 | 978.33 | 0.00 | 0.00 | 0.00 |
| M NW APARTMENT | 9602.00 | 983.00 | 0.00 | 0.00 | 0.00 |
| M SE APARTMENT | 10757.00 | 1073.00 | 0.00 | 0.00 | 0.00 |
| M NE APARTMENT | 9483.00 | 1102.00 | 0.00 | 0.00 | 0.00 |
| M N1 APARTMENT | 9514.33 | 1070.67 | 0.00 | 0.00 | 0.00 |
| M N2 APARTMENT | 9509.17 | 1075.83 | 0.00 | 0.00 | 0.00 |
| M S1 APARTMENT | 10787.17 | 1042.83 | 0.00 | 0.00 | 0.00 |
| M S2 APARTMENT | 10786.00 | 1044.00 | 0.00 | 0.00 | 0.00 |
| T SW APARTMENT | 10476.50 | 1353.50 | 0.00 | 0.00 | 0.00 |
| T NW APARTMENT | 9276.33 | 1308.67 | 0.00 | 0.00 | 0.00 |
| T SE APARTMENT | 10397.50 | 1432.50 | 0.00 | 0.00 | 0.00 |
| T NE APARTMENT | 9206.50 | 1378.50 | 0.00 | 0.00 | 0.00 |
| T N1 APARTMENT | 9265.33 | 1319.67 | 0.00 | 0.00 | 0.00 |
| T N2 APARTMENT | 9263.00 | 1322.00 | 0.00 | 0.00 | 0.00 |
| T S1 APARTMENT | 10481.50 | 1348.50 | 0.00 | 0.00 | 0.00 |
| T S2 APARTMENT | 10477.50 | 1352.50 | 0.00 | 0.00 | 0.00 |
| T CORRIDOR | 11122.50 | 10645.33 | 1227.17 | 0.00 | 0.00 |
| G CORRIDOR | 15395.50 | 7189.83 | 409.67 | 0.00 | 0.00 |
| M CORRIDOR | 7792.17 | 14375.00 | 827.83 | 0.00 | 0.00 |
| Min | 6626.67 | 373.33 | 0.00 | 0.00 | 0.00 |
| Max | 15395.50 | 14375.00 | 1227.17 | 0.00 | 0.00 |
| Average | 10011.83 | 2235.22 | 91.28 | 0.00 | 0.00 |
| Sum | 270319.33 | 60351.00 | 2464.67 | 0.00 | 0.00 |
| SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
| None |
| SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
| None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 09:15:04
CO2 Level Hours| Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
| None |
| Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
| None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 09:15:04
Illuminance Level Hours| A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
| None |
| A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
| None |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
| January | 1.168 |
| February | -0.18 |
| March | 5.585 |
| April | 10.941 |
| May | 16.049 |
| June | 21.711 |
| July | 25.046 |
| August | 24.788 |
| September | 19.956 |
| October | 14.024 |
| November | 7.310 |
| December | 3.332 |
| Annual Sum or Average | 12.554 |
| Minimum of Months | -0.18 |
| Maximum of Months | 25.046 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Environment
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
| January | 1.168 |
| February | -0.18 |
| March | 5.585 |
| April | 10.941 |
| May | 16.049 |
| June | 21.711 |
| July | 25.046 |
| August | 24.788 |
| September | 19.956 |
| October | 14.024 |
| November | 7.310 |
| December | 3.332 |
| Annual Sum or Average | 12.554 |
| Minimum of Months | -0.18 |
| Maximum of Months | 25.046 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2012
For: Environment
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
| January | 1.168 |
| February | -0.18 |
| March | 5.585 |
| April | 10.941 |
| May | 16.049 |
| June | 21.711 |
| July | 25.046 |
| August | 24.788 |
| September | 19.956 |
| October | 14.024 |
| November | 7.310 |
| December | 3.332 |
| Annual Sum or Average | 12.554 |
| Minimum of Months | -0.18 |
| Maximum of Months | 25.046 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
| January | 1.168 |
| February | -0.18 |
| March | 5.585 |
| April | 10.941 |
| May | 16.049 |
| June | 21.711 |
| July | 25.046 |
| August | 24.788 |
| September | 19.956 |
| October | 14.024 |
| November | 7.310 |
| December | 3.332 |
| Annual Sum or Average | 12.554 |
| Minimum of Months | -0.18 |
| Maximum of Months | 25.046 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME APARTMENTMIDRISE
For: Environment
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
| January | 1.168 |
| February | -0.18 |
| March | 5.585 |
| April | 10.941 |
| May | 16.049 |
| June | 21.711 |
| July | 25.046 |
| August | 24.788 |
| September | 19.956 |
| October | 14.024 |
| November | 7.310 |
| December | 3.332 |
| Annual Sum or Average | 12.554 |
| Minimum of Months | -0.18 |
| Maximum of Months | 25.046 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
| January | 1.168 |
| February | -0.18 |
| March | 5.585 |
| April | 10.941 |
| May | 16.049 |
| June | 21.711 |
| July | 25.046 |
| August | 24.788 |
| September | 19.956 |
| October | 14.024 |
| November | 7.310 |
| December | 3.332 |
| Annual Sum or Average | 12.554 |
| Minimum of Months | -0.18 |
| Maximum of Months | 25.046 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
| January | 1.168 |
| February | -0.18 |
| March | 5.585 |
| April | 10.941 |
| May | 16.049 |
| June | 21.711 |
| July | 25.046 |
| August | 24.788 |
| September | 19.956 |
| October | 14.024 |
| November | 7.310 |
| December | 3.332 |
| Annual Sum or Average | 12.554 |
| Minimum of Months | -0.18 |
| Maximum of Months | 25.046 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4A
For: Environment
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
| January | 1.168 |
| February | -0.18 |
| March | 5.585 |
| April | 10.941 |
| May | 16.049 |
| June | 21.711 |
| July | 25.046 |
| August | 24.788 |
| September | 19.956 |
| October | 14.024 |
| November | 7.310 |
| December | 3.332 |
| Annual Sum or Average | 12.554 |
| Minimum of Months | -0.18 |
| Maximum of Months | 25.046 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NY_NEWYORK
For: Environment
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
| January | 1.168 |
| February | -0.18 |
| March | 5.585 |
| April | 10.941 |
| May | 16.049 |
| June | 21.711 |
| July | 25.046 |
| August | 24.788 |
| September | 19.956 |
| October | 14.024 |
| November | 7.310 |
| December | 3.332 |
| Annual Sum or Average | 12.554 |
| Minimum of Months | -0.18 |
| Maximum of Months | 25.046 |
Report: ZoneCoolingSummaryMonthly
For: G SW APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 62802790.26 | 617.89 | 31-JAN-16:10 | -1.3 | -5.8 | 78199740.20 | 43.97 | 17-JAN-18:10 | -1.3 | -5.8 |
| February | 83587889.04 | 531.38 | 02-FEB-16:30 | 3.60 | -2.6 | 69698723.23 | 47.63 | 20-FEB-16:10 | 7.12 | 4.40 |
| March | 0.197223E+09 | 524.86 | 29-MAR-19:00 | 3.90 | 3.17 | 75773787.35 | 63.21 | 27-MAR-17:10 | 3.90 | 3.17 |
| April | 0.454138E+09 | 738.78 | 10-APR-16:05 | 19.90 | 10.98 | 84293757.52 | 70.37 | 08-APR-19:49 | 19.90 | 10.98 |
| May | 0.767131E+09 | 1466.83 | 30-MAY-16:05 | 27.85 | 17.79 | 0.103645E+09 | 70.38 | 12-MAY-19:00 | 27.85 | 17.79 |
| June | 0.179227E+10 | 1864.69 | 19-JUN-17:17 | 32.93 | 24.09 | 0.120135E+09 | 70.36 | 05-JUN-04:19 | 32.93 | 24.09 |
| July | 0.275710E+10 | 1917.23 | 13-JUL-16:02 | 28.72 | 23.99 | 0.129275E+09 | 70.30 | 24-JUL-19:49 | 23.40 | 19.16 |
| August | 0.325224E+10 | 2288.80 | 18-AUG-16:03 | 32.62 | 20.56 | 0.123961E+09 | 70.31 | 20-AUG-09:00 | 23.90 | 15.38 |
| September | 0.229874E+10 | 2224.38 | 01-SEP-14:30 | 30.85 | 17.41 | 0.123706E+09 | 70.36 | 25-SEP-00:00 | 14.40 | 12.83 |
| October | 0.182678E+10 | 2013.31 | 04-OCT-15:10 | 23.72 | 19.12 | 0.123133E+09 | 70.37 | 16-OCT-04:30 | 8.60 | 8.04 |
| November | 0.603628E+09 | 901.50 | 03-NOV-16:04 | 14.63 | 10.15 | 86628802.69 | 70.31 | 02-NOV-19:30 | 14.63 | 10.15 |
| December | 0.207173E+09 | 572.96 | 21-DEC-16:30 | 2.25 | -2.5 | 78588335.72 | 55.86 | 17-DEC-16:10 | 2.25 | -2.5 |
| Annual Sum or Average | 0.143028E+11 | 0.119704E+10 | ||||||||
| Minimum of Months | 62802790.26 | 524.86 | -1.3 | -5.8 | 69698723.23 | 43.97 | -1.3 | -5.8 | ||
| Maximum of Months | 0.325224E+10 | 2288.80 | 32.93 | 24.09 | 0.129275E+09 | 70.38 | 32.93 | 24.09 |
Report: ZoneCoolingSummaryMonthly
For: G NW APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 271731.19 | 56.89 | 17-JAN-17:02 | 6.60 | 2.87 | 77895344.60 | 42.51 | 14-JAN-22:00 | 6.60 | 2.87 |
| February | 53317.80 | 36.92 | 20-FEB-17:04 | 6.42 | 4.02 | 70357085.51 | 42.51 | 25-FEB-22:00 | 2.20 | -0.6 |
| March | 38411034.96 | 337.37 | 28-MAR-19:30 | 9.70 | 6.66 | 78041723.31 | 48.93 | 27-MAR-17:10 | 9.70 | 6.66 |
| April | 0.245780E+09 | 409.44 | 12-APR-21:25 | 7.50 | 2.02 | 79759488.39 | 63.40 | 07-APR-20:10 | 7.50 | 2.02 |
| May | 0.639485E+09 | 1286.77 | 30-MAY-16:40 | 26.50 | 18.22 | 0.101967E+09 | 70.35 | 30-MAY-03:49 | 26.50 | 18.22 |
| June | 0.164259E+10 | 1799.93 | 19-JUN-17:30 | 32.75 | 23.87 | 0.124260E+09 | 70.36 | 10-JUN-03:49 | 32.75 | 23.87 |
| July | 0.254469E+10 | 1780.41 | 13-JUL-16:30 | 28.35 | 23.93 | 0.128774E+09 | 70.30 | 17-JUL-00:00 | 23.30 | 20.65 |
| August | 0.269935E+10 | 1927.69 | 18-AUG-16:30 | 32.25 | 20.37 | 0.128768E+09 | 70.31 | 30-AUG-20:30 | 23.35 | 17.68 |
| September | 0.163639E+10 | 1611.12 | 07-SEP-16:15 | 26.10 | 22.11 | 0.123594E+09 | 70.37 | 19-SEP-02:39 | 14.60 | 10.92 |
| October | 0.983510E+09 | 1165.38 | 04-OCT-16:10 | 22.62 | 19.06 | 0.114545E+09 | 70.36 | 22-OCT-22:49 | 15.10 | 12.18 |
| November | 0.310875E+09 | 408.63 | 06-NOV-22:40 | 7.57 | 5.36 | 77812421.01 | 55.34 | 04-NOV-20:10 | 7.57 | 5.36 |
| December | 1350861.78 | 120.69 | 04-DEC-19:00 | 8.90 | 7.75 | 77895344.67 | 42.51 | 22-DEC-22:00 | 2.20 | 1.52 |
| Annual Sum or Average | 0.107428E+11 | 0.118367E+10 | ||||||||
| Minimum of Months | 53317.80 | 36.92 | 6.42 | 2.02 | 70357085.51 | 42.51 | 2.20 | -0.6 | ||
| Maximum of Months | 0.269935E+10 | 1927.69 | 32.75 | 23.93 | 0.128774E+09 | 70.37 | 32.75 | 23.87 |
Report: ZoneCoolingSummaryMonthly
For: OFFICE
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.487385E+09 | 1058.72 | 31-JAN-08:03 | -8.2 | -10.6 | 39003515.00 | 88.89 | 20-JAN-16:10 | -8.2 | -10.6 |
| February | 0.564691E+09 | 1165.39 | 06-FEB-08:03 | -12.7 | -14.0 | 36954061.92 | 85.08 | 02-FEB-13:00 | -12.7 | -14.0 |
| March | 0.414498E+09 | 819.00 | 23-MAR-07:03 | -2.9 | -5.5 | 48155380.98 | 126.13 | 03-MAR-15:09 | -2.9 | -5.5 |
| April | 0.323690E+09 | 3436.31 | 10-APR-08:63 | 18.35 | 15.22 | 54284629.06 | 157.68 | 10-APR-08:09 | 18.35 | 15.22 |
| May | 0.491166E+09 | 6227.44 | 30-MAY-07:02 | 23.17 | 16.07 | 72750673.18 | 203.68 | 30-MAY-07:10 | 23.17 | 16.07 |
| June | 0.134423E+10 | 6183.92 | 02-JUN-08:62 | 16.10 | 9.14 | 77430696.86 | 217.47 | 26-JUN-07:10 | 23.40 | 18.26 |
| July | 0.178843E+10 | 6514.04 | 11-JUL-07:02 | 22.30 | 16.06 | 70696518.04 | 217.84 | 07-JUL-07:10 | 22.30 | 16.06 |
| August | 0.232898E+10 | 6578.69 | 23-AUG-07:02 | 20.87 | 14.96 | 81279858.50 | 217.47 | 04-AUG-07:10 | 20.87 | 14.96 |
| September | 0.159342E+10 | 6669.28 | 11-SEP-07:01 | 14.27 | 10.17 | 70372657.01 | 217.47 | 01-SEP-07:10 | 14.27 | 10.17 |
| October | 0.144611E+10 | 6409.13 | 16-OCT-08:62 | 14.37 | 11.80 | 72715109.71 | 194.81 | 06-OCT-07:10 | 14.37 | 11.80 |
| November | 0.676304E+09 | 1584.57 | 10-NOV-09:05 | 15.18 | 15.13 | 52839035.69 | 149.28 | 10-NOV-09:09 | 15.18 | 15.13 |
| December | 0.593149E+09 | 782.99 | 22-DEC-09:07 | -2.7 | -5.3 | 40144279.11 | 108.11 | 20-DEC-11:00 | -2.7 | -5.3 |
| Annual Sum or Average | 0.120521E+11 | 0.716626E+09 | ||||||||
| Minimum of Months | 0.323690E+09 | 782.99 | -12.7 | -14.0 | 36954061.92 | 85.08 | -12.7 | -14.0 | ||
| Maximum of Months | 0.232898E+10 | 6669.28 | 23.17 | 16.07 | 81279858.50 | 217.84 | 23.40 | 18.26 |
Report: ZoneCoolingSummaryMonthly
For: G NE APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | -9.6 | -11.5 | 77895344.60 | 42.51 | 14-JAN-22:00 | -5.0 | -5.2 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | -1.1 | -4.2 | 70357085.51 | 42.51 | 25-FEB-22:00 | 2.20 | -0.6 |
| March | 27349791.21 | 336.23 | 28-MAR-19:30 | 9.70 | 6.66 | 77952410.85 | 44.39 | 27-MAR-17:10 | 9.70 | 6.66 |
| April | 0.250302E+09 | 433.40 | 12-APR-09:00 | 6.70 | 0.80 | 79435425.33 | 63.44 | 07-APR-20:10 | 6.70 | 0.80 |
| May | 0.658846E+09 | 1073.56 | 31-MAY-10:10 | 25.60 | 19.48 | 0.101238E+09 | 70.38 | 27-MAY-22:49 | 25.60 | 19.48 |
| June | 0.158485E+10 | 1500.21 | 19-JUN-17:20 | 32.93 | 24.09 | 0.124270E+09 | 70.37 | 05-JUN-01:30 | 32.93 | 24.09 |
| July | 0.253076E+10 | 1595.20 | 10-JUL-16:17 | 30.73 | 20.42 | 0.128774E+09 | 70.30 | 17-JUL-00:00 | 23.30 | 20.65 |
| August | 0.268617E+10 | 1642.08 | 24-AUG-17:00 | 33.30 | 18.04 | 0.128766E+09 | 70.31 | 29-AUG-05:40 | 17.43 | 14.67 |
| September | 0.163943E+10 | 1399.55 | 06-SEP-10:30 | 27.50 | 19.79 | 0.123672E+09 | 70.34 | 19-SEP-02:30 | 14.70 | 10.96 |
| October | 0.964688E+09 | 908.46 | 25-OCT-10:30 | 24.15 | 19.68 | 0.113880E+09 | 70.37 | 22-OCT-22:40 | 24.15 | 19.68 |
| November | 0.331061E+09 | 421.43 | 05-NOV-22:00 | 7.20 | 4.45 | 78084806.56 | 55.98 | 04-NOV-20:10 | 7.20 | 4.45 |
| December | 1768885.90 | 108.14 | 20-DEC-12:00 | 8.90 | 5.16 | 77895344.67 | 42.51 | 22-DEC-22:00 | 2.20 | 1.52 |
| Annual Sum or Average | 0.106752E+11 | 0.118222E+10 | ||||||||
| Minimum of Months | 0.00 | 0.00 | -9.6 | -11.5 | 70357085.51 | 42.51 | -5.0 | -5.2 | ||
| Maximum of Months | 0.268617E+10 | 1642.08 | 33.30 | 24.09 | 0.128774E+09 | 70.38 | 32.93 | 24.09 |
Report: ZoneCoolingSummaryMonthly
For: G N1 APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 9805522.12 | 176.78 | 23-JAN-19:00 | 9.40 | 9.40 | 77895344.64 | 42.51 | 14-JAN-22:00 | 9.40 | 9.40 |
| February | 1011870.80 | 85.80 | 20-FEB-17:04 | 6.42 | 4.02 | 70357085.51 | 42.51 | 12-FEB-22:00 | 6.42 | 4.02 |
| March | 81213306.27 | 339.52 | 28-MAR-19:30 | 9.70 | 6.66 | 78016414.03 | 46.28 | 27-MAR-20:00 | 9.70 | 6.66 |
| April | 0.364461E+09 | 461.42 | 11-APR-06:00 | 6.10 | 1.72 | 80234364.70 | 61.39 | 07-APR-20:10 | 6.10 | 1.72 |
| May | 0.673800E+09 | 868.57 | 30-MAY-17:20 | 24.67 | 17.90 | 0.105527E+09 | 70.34 | 27-MAY-23:19 | 24.67 | 17.90 |
| June | 0.146467E+10 | 1236.74 | 19-JUN-17:25 | 32.75 | 23.87 | 0.124520E+09 | 70.37 | 02-JUN-04:40 | 32.75 | 23.87 |
| July | 0.217353E+10 | 1295.90 | 10-JUL-17:27 | 30.00 | 20.85 | 0.128774E+09 | 70.30 | 17-JUL-00:00 | 23.30 | 20.65 |
| August | 0.220928E+10 | 1288.45 | 17-AUG-17:03 | 30.92 | 24.18 | 0.128772E+09 | 70.31 | 30-AUG-20:30 | 23.35 | 17.68 |
| September | 0.146083E+10 | 1099.97 | 01-SEP-16:17 | 28.13 | 17.50 | 0.124306E+09 | 70.37 | 29-SEP-00:20 | 13.90 | 9.49 |
| October | 0.955514E+09 | 761.15 | 04-OCT-16:05 | 22.62 | 19.06 | 0.118036E+09 | 70.38 | 01-OCT-20:49 | 22.62 | 19.06 |
| November | 0.483738E+09 | 490.00 | 06-NOV-04:00 | 5.00 | 2.86 | 80267711.84 | 58.96 | 04-NOV-20:10 | 5.00 | 2.86 |
| December | 31850348.50 | 256.29 | 04-DEC-19:00 | 8.90 | 7.75 | 77895344.66 | 42.51 | 22-DEC-22:00 | 2.20 | 1.52 |
| Annual Sum or Average | 0.990970E+10 | 0.119460E+10 | ||||||||
| Minimum of Months | 1011870.80 | 85.80 | 5.00 | 1.72 | 70357085.51 | 42.51 | 2.20 | 1.52 | ||
| Maximum of Months | 0.220928E+10 | 1295.90 | 32.75 | 24.18 | 0.128774E+09 | 70.38 | 32.75 | 23.87 |
Report: ZoneCoolingSummaryMonthly
For: G N2 APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 9734499.21 | 176.67 | 23-JAN-19:00 | 9.40 | 9.40 | 77895344.64 | 42.51 | 14-JAN-22:00 | 9.40 | 9.40 |
| February | 959982.26 | 82.34 | 20-FEB-17:04 | 6.42 | 4.02 | 70357085.51 | 42.51 | 12-FEB-22:00 | 6.42 | 4.02 |
| March | 80494859.03 | 339.46 | 28-MAR-19:30 | 9.70 | 6.66 | 78011690.51 | 46.13 | 27-MAR-20:00 | 9.70 | 6.66 |
| April | 0.364669E+09 | 461.38 | 11-APR-06:00 | 6.10 | 1.72 | 80254558.65 | 61.52 | 07-APR-20:10 | 6.10 | 1.72 |
| May | 0.676281E+09 | 869.34 | 30-MAY-17:20 | 24.67 | 17.90 | 0.105452E+09 | 70.38 | 27-MAY-23:19 | 24.67 | 17.90 |
| June | 0.146212E+10 | 1228.66 | 19-JUN-17:25 | 32.75 | 23.87 | 0.124521E+09 | 70.37 | 09-JUN-03:00 | 32.75 | 23.87 |
| July | 0.217283E+10 | 1293.64 | 10-JUL-17:35 | 30.00 | 20.79 | 0.128774E+09 | 70.30 | 17-JUL-00:00 | 23.30 | 20.65 |
| August | 0.220890E+10 | 1283.55 | 17-AUG-17:03 | 30.92 | 24.18 | 0.128772E+09 | 70.31 | 30-AUG-20:30 | 23.35 | 17.68 |
| September | 0.146178E+10 | 1096.82 | 01-SEP-16:17 | 28.13 | 17.50 | 0.124307E+09 | 70.37 | 29-SEP-00:49 | 13.90 | 9.05 |
| October | 0.954546E+09 | 767.59 | 06-OCT-17:05 | 15.50 | 8.95 | 0.117989E+09 | 70.36 | 22-OCT-23:40 | 14.60 | 11.99 |
| November | 0.485922E+09 | 490.59 | 06-NOV-04:00 | 5.00 | 2.86 | 80340770.93 | 59.07 | 04-NOV-20:10 | 5.00 | 2.86 |
| December | 31948251.53 | 255.93 | 04-DEC-19:00 | 8.90 | 7.75 | 77895344.66 | 42.51 | 22-DEC-22:00 | 2.20 | 1.52 |
| Annual Sum or Average | 0.991019E+10 | 0.119457E+10 | ||||||||
| Minimum of Months | 959982.26 | 82.34 | 5.00 | 1.72 | 70357085.51 | 42.51 | 2.20 | 1.52 | ||
| Maximum of Months | 0.220890E+10 | 1293.64 | 32.75 | 24.18 | 0.128774E+09 | 70.38 | 32.75 | 23.87 |
Report: ZoneCoolingSummaryMonthly
For: G S1 APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.215106E+09 | 689.58 | 31-JAN-16:20 | -1.5 | -5.9 | 78210188.55 | 45.85 | 17-JAN-18:10 | -1.5 | -5.9 |
| February | 0.234873E+09 | 704.14 | 03-FEB-12:10 | -1.9 | -5.5 | 69789768.18 | 48.68 | 20-FEB-16:10 | 7.12 | 4.40 |
| March | 0.436243E+09 | 531.00 | 29-MAR-19:00 | 3.90 | 3.17 | 76118274.97 | 60.12 | 27-MAR-17:10 | 3.90 | 3.17 |
| April | 0.615022E+09 | 620.86 | 08-APR-12:20 | 23.87 | 16.21 | 87058475.87 | 70.33 | 08-APR-17:10 | 16.93 | 13.28 |
| May | 0.802894E+09 | 1066.28 | 30-MAY-13:00 | 30.00 | 18.00 | 0.108772E+09 | 70.38 | 14-MAY-15:09 | 30.00 | 18.00 |
| June | 0.162675E+10 | 1304.81 | 19-JUN-17:10 | 33.12 | 24.31 | 0.120355E+09 | 70.34 | 07-JUN-04:10 | 33.12 | 24.31 |
| July | 0.240093E+10 | 1443.71 | 10-JUL-14:10 | 32.88 | 20.91 | 0.129275E+09 | 70.30 | 24-JUL-19:49 | 23.40 | 19.16 |
| August | 0.278089E+10 | 1696.86 | 18-AUG-14:10 | 33.22 | 20.56 | 0.123963E+09 | 70.31 | 20-AUG-09:00 | 23.90 | 15.38 |
| September | 0.216222E+10 | 1738.95 | 01-SEP-14:10 | 31.02 | 17.36 | 0.123914E+09 | 70.37 | 24-SEP-00:30 | 12.80 | 9.34 |
| October | 0.190092E+10 | 1620.72 | 04-OCT-14:10 | 24.32 | 18.98 | 0.125681E+09 | 70.37 | 17-OCT-02:00 | 10.00 | 8.29 |
| November | 0.920164E+09 | 976.04 | 02-NOV-12:50 | 15.50 | 8.17 | 92115514.84 | 70.37 | 04-NOV-01:30 | 12.25 | 9.97 |
| December | 0.498916E+09 | 662.82 | 21-DEC-19:00 | -0.6 | -3.8 | 79253307.22 | 58.15 | 17-DEC-16:10 | -0.6 | -3.8 |
| Annual Sum or Average | 0.145949E+11 | 0.121450E+10 | ||||||||
| Minimum of Months | 0.215106E+09 | 531.00 | -1.9 | -5.9 | 69789768.18 | 45.85 | -1.5 | -5.9 | ||
| Maximum of Months | 0.278089E+10 | 1738.95 | 33.22 | 24.31 | 0.129275E+09 | 70.38 | 33.12 | 24.31 |
Report: ZoneCoolingSummaryMonthly
For: G S2 APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.164650E+09 | 643.05 | 31-JAN-16:10 | -1.3 | -5.8 | 78200282.84 | 43.95 | 17-JAN-18:10 | -1.3 | -5.8 |
| February | 0.188567E+09 | 687.77 | 03-FEB-12:30 | -1.4 | -5.2 | 69733904.02 | 47.01 | 20-FEB-16:10 | 7.12 | 4.40 |
| March | 0.381609E+09 | 529.79 | 29-MAR-19:00 | 3.90 | 3.17 | 75967181.73 | 59.27 | 27-MAR-17:10 | 3.90 | 3.17 |
| April | 0.612795E+09 | 656.85 | 08-APR-12:20 | 23.87 | 16.21 | 87356909.76 | 70.35 | 08-APR-20:00 | 14.40 | 12.83 |
| May | 0.848690E+09 | 1140.89 | 30-MAY-13:00 | 30.00 | 18.00 | 0.110032E+09 | 70.37 | 21-MAY-18:00 | 30.00 | 18.00 |
| June | 0.178380E+10 | 1372.47 | 19-JUN-13:00 | 35.00 | 23.93 | 0.120384E+09 | 70.34 | 03-JUN-02:30 | 35.00 | 23.93 |
| July | 0.265322E+10 | 1551.72 | 10-JUL-14:10 | 32.88 | 20.91 | 0.129275E+09 | 70.30 | 24-JUL-19:49 | 23.40 | 19.16 |
| August | 0.304877E+10 | 1789.25 | 13-AUG-13:40 | 31.50 | 19.78 | 0.123963E+09 | 70.31 | 20-AUG-09:00 | 23.90 | 15.38 |
| September | 0.235643E+10 | 1830.43 | 04-SEP-13:30 | 26.10 | 18.39 | 0.123931E+09 | 70.30 | 02-SEP-02:49 | 26.10 | 18.39 |
| October | 0.200046E+10 | 1671.93 | 04-OCT-14:10 | 24.32 | 18.98 | 0.125900E+09 | 70.37 | 17-OCT-03:39 | 10.00 | 8.46 |
| November | 0.905938E+09 | 1022.59 | 02-NOV-12:50 | 15.50 | 8.17 | 92486587.02 | 70.36 | 09-NOV-20:40 | 12.97 | 12.72 |
| December | 0.439290E+09 | 651.09 | 21-DEC-18:50 | -0.2 | -3.6 | 79044392.87 | 56.85 | 17-DEC-16:10 | -0.2 | -3.6 |
| Annual Sum or Average | 0.153842E+11 | 0.121627E+10 | ||||||||
| Minimum of Months | 0.164650E+09 | 529.79 | -1.4 | -5.8 | 69733904.02 | 43.95 | -1.3 | -5.8 | ||
| Maximum of Months | 0.304877E+10 | 1830.43 | 35.00 | 23.93 | 0.129275E+09 | 70.37 | 35.00 | 23.93 |
Report: ZoneCoolingSummaryMonthly
For: M SW APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.240209E+09 | 756.82 | 31-JAN-13:10 | -3.6 | -7.4 | 78455943.01 | 57.43 | 17-JAN-18:10 | -3.6 | -7.4 |
| February | 0.329494E+09 | 729.17 | 03-FEB-11:10 | -2.7 | -5.9 | 70702366.15 | 62.82 | 20-FEB-16:10 | 7.12 | 4.40 |
| March | 0.738386E+09 | 683.61 | 03-MAR-14:30 | 15.00 | 8.51 | 81301055.67 | 70.28 | 11-MAR-16:40 | 11.50 | 5.63 |
| April | 0.109987E+10 | 2195.68 | 07-APR-15:30 | 25.60 | 16.04 | 98715089.94 | 70.32 | 29-APR-18:00 | 10.60 | 9.13 |
| May | 0.175933E+10 | 2315.24 | 30-MAY-16:05 | 27.85 | 17.79 | 0.122720E+09 | 70.32 | 04-MAY-19:19 | 27.85 | 17.79 |
| June | 0.267592E+10 | 2521.41 | 19-JUN-17:05 | 33.12 | 24.31 | 0.120393E+09 | 70.30 | 20-JUN-18:30 | 23.35 | 17.08 |
| July | 0.348163E+10 | 2439.54 | 13-JUL-16:04 | 28.72 | 23.99 | 0.129275E+09 | 70.30 | 24-JUL-19:49 | 23.40 | 19.16 |
| August | 0.375419E+10 | 2784.86 | 18-AUG-16:03 | 32.62 | 20.56 | 0.123961E+09 | 70.30 | 20-AUG-09:00 | 23.90 | 15.38 |
| September | 0.253742E+10 | 2710.37 | 01-SEP-14:30 | 30.85 | 17.41 | 0.123677E+09 | 70.30 | 19-SEP-05:00 | 12.80 | 9.34 |
| October | 0.194711E+10 | 2467.95 | 04-OCT-15:10 | 23.72 | 19.12 | 0.121358E+09 | 70.30 | 16-OCT-22:40 | 11.70 | 10.87 |
| November | 0.659874E+09 | 1194.96 | 03-NOV-15:50 | 15.37 | 10.39 | 86177483.64 | 70.29 | 03-NOV-22:40 | 12.80 | 10.53 |
| December | 0.369647E+09 | 667.73 | 21-DEC-19:00 | -0.6 | -3.8 | 79602838.03 | 66.13 | 17-DEC-16:10 | -0.6 | -3.8 |
| Annual Sum or Average | 0.195931E+11 | 0.123634E+10 | ||||||||
| Minimum of Months | 0.240209E+09 | 667.73 | -3.6 | -7.4 | 70702366.15 | 57.43 | -3.6 | -7.4 | ||
| Maximum of Months | 0.375419E+10 | 2784.86 | 33.12 | 24.31 | 0.129275E+09 | 70.32 | 27.85 | 19.16 |
Report: ZoneCoolingSummaryMonthly
For: M NW APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 19330262.87 | 401.37 | 17-JAN-16:40 | 7.80 | 3.64 | 77896671.94 | 42.51 | 09-JAN-22:00 | 7.80 | 3.64 |
| February | 33479535.39 | 453.21 | 20-FEB-17:12 | 6.13 | 3.88 | 70358566.22 | 42.51 | 05-FEB-06:49 | 6.13 | 3.88 |
| March | 0.305080E+09 | 537.50 | 29-MAR-19:00 | 3.90 | 3.17 | 79666937.22 | 59.67 | 27-MAR-17:10 | 3.90 | 3.17 |
| April | 0.745172E+09 | 1215.22 | 09-APR-17:30 | 15.55 | 13.44 | 93649620.82 | 70.31 | 08-APR-20:10 | 15.55 | 13.44 |
| May | 0.152992E+10 | 2142.99 | 30-MAY-16:30 | 26.95 | 18.10 | 0.124749E+09 | 70.31 | 27-MAY-02:39 | 26.95 | 18.10 |
| June | 0.251614E+10 | 2466.43 | 19-JUN-17:25 | 32.75 | 23.87 | 0.124591E+09 | 70.30 | 23-JUN-00:49 | 23.40 | 15.86 |
| July | 0.324736E+10 | 2294.55 | 06-JUL-17:17 | 28.30 | 24.27 | 0.128774E+09 | 70.29 | 17-JUL-00:00 | 23.30 | 20.65 |
| August | 0.315535E+10 | 2365.04 | 18-AUG-16:30 | 32.25 | 20.37 | 0.128765E+09 | 70.30 | 30-AUG-20:30 | 23.35 | 17.68 |
| September | 0.181624E+10 | 1936.23 | 06-SEP-16:30 | 25.00 | 20.31 | 0.123830E+09 | 70.31 | 24-SEP-22:19 | 14.23 | 12.58 |
| October | 0.103092E+10 | 1442.28 | 04-OCT-16:10 | 22.62 | 19.06 | 0.113087E+09 | 70.31 | 25-OCT-23:40 | 14.97 | 6.68 |
| November | 0.301791E+09 | 421.34 | 06-NOV-23:00 | 7.20 | 5.19 | 78387116.19 | 57.49 | 04-NOV-20:10 | 7.20 | 5.19 |
| December | 21716347.99 | 304.45 | 04-DEC-19:00 | 8.90 | 7.75 | 77895507.02 | 42.51 | 22-DEC-22:00 | 2.20 | 1.52 |
| Annual Sum or Average | 0.147225E+11 | 0.122165E+10 | ||||||||
| Minimum of Months | 19330262.87 | 304.45 | 3.90 | 3.17 | 70358566.22 | 42.51 | 2.20 | 1.52 | ||
| Maximum of Months | 0.324736E+10 | 2466.43 | 32.75 | 24.27 | 0.128774E+09 | 70.31 | 26.95 | 20.65 |
Report: ZoneCoolingSummaryMonthly
For: M SE APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.241716E+09 | 766.16 | 31-JAN-13:00 | -3.9 | -7.6 | 78367334.65 | 54.88 | 17-JAN-18:10 | -3.9 | -7.6 |
| February | 0.337579E+09 | 766.67 | 03-FEB-10:30 | -3.9 | -6.8 | 70663887.44 | 58.73 | 19-FEB-16:10 | 9.13 | 3.69 |
| March | 0.718216E+09 | 675.55 | 18-MAR-09:10 | -0.9 | -1.4 | 80301855.99 | 70.30 | 27-MAR-17:19 | 20.37 | 15.16 |
| April | 0.110355E+10 | 2050.47 | 08-APR-12:00 | 24.40 | 16.25 | 98533167.14 | 70.30 | 07-APR-19:19 | 24.40 | 16.25 |
| May | 0.178302E+10 | 2119.65 | 30-MAY-13:00 | 30.00 | 18.00 | 0.122549E+09 | 70.32 | 21-MAY-02:20 | 30.00 | 18.00 |
| June | 0.261349E+10 | 2311.22 | 19-JUN-12:50 | 35.28 | 24.00 | 0.120395E+09 | 70.30 | 20-JUN-18:30 | 23.35 | 17.08 |
| July | 0.346897E+10 | 2260.58 | 10-JUL-13:30 | 32.50 | 20.67 | 0.129275E+09 | 70.30 | 24-JUL-19:49 | 23.40 | 19.16 |
| August | 0.373916E+10 | 2559.04 | 18-AUG-13:00 | 33.30 | 20.31 | 0.123961E+09 | 70.30 | 30-AUG-20:30 | 23.35 | 17.68 |
| September | 0.254782E+10 | 2542.15 | 01-SEP-13:00 | 30.60 | 18.37 | 0.123676E+09 | 70.31 | 23-SEP-08:30 | 13.30 | 7.74 |
| October | 0.192391E+10 | 2250.06 | 04-OCT-13:00 | 25.00 | 18.54 | 0.121281E+09 | 70.31 | 08-OCT-20:10 | 8.22 | 3.80 |
| November | 0.697461E+09 | 1254.18 | 04-NOV-12:30 | 17.80 | 12.61 | 86732828.04 | 70.29 | 03-NOV-22:30 | 17.80 | 12.61 |
| December | 0.388119E+09 | 664.30 | 21-DEC-19:00 | -0.6 | -3.8 | 79642264.10 | 63.41 | 17-DEC-16:10 | -0.6 | -3.8 |
| Annual Sum or Average | 0.195630E+11 | 0.123538E+10 | ||||||||
| Minimum of Months | 0.241716E+09 | 664.30 | -3.9 | -7.6 | 70663887.44 | 54.88 | -3.9 | -7.6 | ||
| Maximum of Months | 0.373916E+10 | 2559.04 | 35.28 | 24.00 | 0.129275E+09 | 70.32 | 30.00 | 19.16 |
Report: ZoneCoolingSummaryMonthly
For: M NE APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 14273434.11 | 267.18 | 17-JAN-17:10 | 6.60 | 2.87 | 77895344.60 | 42.51 | 09-JAN-22:00 | 6.60 | 2.87 |
| February | 25363355.55 | 278.91 | 20-FEB-12:00 | 10.00 | 4.36 | 70357085.49 | 42.51 | 05-FEB-06:49 | 10.00 | 4.36 |
| March | 0.287511E+09 | 515.79 | 29-MAR-07:45 | 4.13 | 1.93 | 79133640.71 | 53.59 | 27-MAR-20:49 | 4.13 | 1.93 |
| April | 0.742729E+09 | 1077.77 | 08-APR-10:30 | 24.45 | 16.29 | 93638780.97 | 70.32 | 08-APR-02:09 | 24.45 | 16.29 |
| May | 0.154977E+10 | 1767.06 | 30-MAY-10:00 | 27.80 | 17.82 | 0.124663E+09 | 70.31 | 27-MAY-05:40 | 27.80 | 17.82 |
| June | 0.245372E+10 | 2038.15 | 19-JUN-17:05 | 33.12 | 24.31 | 0.124589E+09 | 70.30 | 23-JUN-00:49 | 23.40 | 15.86 |
| July | 0.323471E+10 | 2016.70 | 14-JUL-09:30 | 29.75 | 21.24 | 0.128774E+09 | 70.29 | 17-JUL-00:00 | 23.30 | 20.65 |
| August | 0.314049E+10 | 1959.51 | 18-AUG-10:10 | 30.78 | 19.76 | 0.128766E+09 | 70.30 | 30-AUG-20:30 | 23.35 | 17.68 |
| September | 0.182185E+10 | 1632.44 | 01-SEP-10:20 | 28.17 | 18.89 | 0.123884E+09 | 70.31 | 28-SEP-23:49 | 13.98 | 9.87 |
| October | 0.101105E+10 | 1108.09 | 25-OCT-10:30 | 24.15 | 19.68 | 0.112397E+09 | 70.31 | 15-OCT-23:30 | 24.15 | 19.68 |
| November | 0.323793E+09 | 421.27 | 06-NOV-23:00 | 7.20 | 5.19 | 78625511.54 | 58.19 | 04-NOV-20:10 | 7.20 | 5.19 |
| December | 20299646.05 | 292.94 | 20-DEC-12:00 | 8.90 | 5.16 | 77895344.66 | 42.51 | 22-DEC-22:00 | 2.20 | 1.52 |
| Annual Sum or Average | 0.146256E+11 | 0.122062E+10 | ||||||||
| Minimum of Months | 14273434.11 | 267.18 | 4.13 | 1.93 | 70357085.49 | 42.51 | 2.20 | 1.52 | ||
| Maximum of Months | 0.323471E+10 | 2038.15 | 33.12 | 24.31 | 0.128774E+09 | 70.32 | 27.80 | 20.65 |
Report: ZoneCoolingSummaryMonthly
For: M N1 APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.131188E+09 | 394.69 | 17-JAN-17:15 | 6.50 | 2.77 | 77904538.62 | 43.00 | 23-JAN-21:10 | 10.10 | 10.04 |
| February | 0.126681E+09 | 410.68 | 20-FEB-17:10 | 6.42 | 4.02 | 70357095.16 | 42.51 | 06-FEB-06:49 | 6.42 | 4.02 |
| March | 0.537527E+09 | 558.20 | 29-MAR-03:00 | 2.80 | 0.14 | 80065726.37 | 56.95 | 27-MAR-20:00 | 2.80 | 0.14 |
| April | 0.846083E+09 | 788.05 | 09-APR-17:30 | 15.55 | 13.44 | 96204373.43 | 70.31 | 28-APR-00:10 | 15.00 | 13.36 |
| May | 0.137973E+10 | 1310.21 | 30-MAY-17:30 | 24.20 | 17.64 | 0.126971E+09 | 70.32 | 11-MAY-03:09 | 24.20 | 17.64 |
| June | 0.204933E+10 | 1577.89 | 19-JUN-17:25 | 32.75 | 23.87 | 0.124610E+09 | 70.30 | 23-JUN-00:49 | 23.40 | 15.86 |
| July | 0.261179E+10 | 1510.87 | 10-JUL-17:50 | 30.00 | 20.72 | 0.128774E+09 | 70.29 | 17-JUL-00:00 | 23.30 | 20.65 |
| August | 0.247187E+10 | 1463.43 | 24-AUG-17:00 | 33.30 | 18.04 | 0.128770E+09 | 70.30 | 30-AUG-20:30 | 23.35 | 17.68 |
| September | 0.159530E+10 | 1235.86 | 01-SEP-16:17 | 28.13 | 17.50 | 0.124431E+09 | 70.32 | 24-SEP-00:00 | 12.80 | 9.34 |
| October | 0.102471E+10 | 871.69 | 04-OCT-16:10 | 22.62 | 19.06 | 0.117700E+09 | 70.31 | 26-OCT-00:00 | 13.30 | 6.79 |
| November | 0.543101E+09 | 493.16 | 06-NOV-04:00 | 5.00 | 2.86 | 81793205.47 | 62.05 | 04-NOV-20:10 | 5.00 | 2.86 |
| December | 0.166064E+09 | 383.19 | 04-DEC-18:09 | 8.40 | 7.55 | 77905786.37 | 43.07 | 04-DEC-21:10 | 8.72 | 7.92 |
| Annual Sum or Average | 0.134834E+11 | 0.123549E+10 | ||||||||
| Minimum of Months | 0.126681E+09 | 383.19 | 2.80 | 0.14 | 70357095.16 | 42.51 | 2.80 | 0.14 | ||
| Maximum of Months | 0.261179E+10 | 1577.89 | 33.30 | 23.87 | 0.128774E+09 | 70.32 | 24.20 | 20.65 |
Report: ZoneCoolingSummaryMonthly
For: M N2 APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.131213E+09 | 390.12 | 17-JAN-17:15 | 6.50 | 2.77 | 77904487.74 | 43.00 | 23-JAN-21:10 | 10.10 | 10.04 |
| February | 0.126927E+09 | 405.89 | 20-FEB-17:10 | 6.42 | 4.02 | 70357137.44 | 42.51 | 06-FEB-06:49 | 6.42 | 4.02 |
| March | 0.535224E+09 | 552.97 | 29-MAR-02:40 | 2.97 | 0.24 | 80022208.32 | 56.65 | 27-MAR-20:00 | 2.97 | 0.24 |
| April | 0.847568E+09 | 782.32 | 09-APR-17:30 | 15.55 | 13.44 | 96260297.29 | 70.32 | 27-APR-23:40 | 15.00 | 13.23 |
| May | 0.138146E+10 | 1303.91 | 30-MAY-17:30 | 24.20 | 17.64 | 0.126970E+09 | 70.32 | 21-MAY-03:20 | 24.20 | 17.64 |
| June | 0.204702E+10 | 1570.54 | 19-JUN-17:25 | 32.75 | 23.87 | 0.124610E+09 | 70.30 | 23-JUN-00:49 | 23.40 | 15.86 |
| July | 0.261135E+10 | 1506.58 | 10-JUL-17:40 | 30.00 | 20.79 | 0.128774E+09 | 70.29 | 17-JUL-00:00 | 23.30 | 20.65 |
| August | 0.247165E+10 | 1459.43 | 24-AUG-17:00 | 33.30 | 18.04 | 0.128770E+09 | 70.31 | 30-AUG-20:30 | 23.35 | 17.68 |
| September | 0.159640E+10 | 1232.89 | 01-SEP-16:17 | 28.13 | 17.50 | 0.124430E+09 | 70.31 | 20-SEP-03:09 | 12.70 | 11.40 |
| October | 0.102415E+10 | 866.23 | 04-OCT-16:10 | 22.62 | 19.06 | 0.117660E+09 | 70.31 | 23-OCT-04:30 | 13.05 | 10.91 |
| November | 0.545486E+09 | 493.91 | 06-NOV-04:00 | 5.00 | 2.86 | 81869500.86 | 62.17 | 04-NOV-20:10 | 5.00 | 2.86 |
| December | 0.166739E+09 | 383.17 | 04-DEC-18:10 | 8.40 | 7.55 | 77905529.15 | 43.04 | 04-DEC-21:10 | 8.72 | 7.92 |
| Annual Sum or Average | 0.134852E+11 | 0.123553E+10 | ||||||||
| Minimum of Months | 0.126927E+09 | 383.17 | 2.97 | 0.24 | 70357137.44 | 42.51 | 2.97 | 0.24 | ||
| Maximum of Months | 0.261135E+10 | 1570.54 | 33.30 | 23.87 | 0.128774E+09 | 70.32 | 24.20 | 20.65 |
Report: ZoneCoolingSummaryMonthly
For: M S1 APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.583731E+09 | 820.33 | 31-JAN-11:00 | -5.6 | -8.8 | 79143114.65 | 59.22 | 17-JAN-18:10 | -5.6 | -8.8 |
| February | 0.700136E+09 | 864.31 | 12-FEB-12:20 | -7.0 | -10.0 | 71919712.38 | 63.25 | 20-FEB-16:10 | 7.12 | 4.40 |
| March | 0.104766E+10 | 763.46 | 03-MAR-14:00 | 15.00 | 8.62 | 85398300.31 | 70.31 | 03-MAR-20:19 | 11.50 | 6.74 |
| April | 0.119304E+10 | 1671.07 | 08-APR-12:20 | 23.87 | 16.21 | 0.103301E+09 | 70.32 | 25-APR-20:00 | 13.30 | 10.08 |
| May | 0.161634E+10 | 1566.37 | 30-MAY-13:00 | 30.00 | 18.00 | 0.124627E+09 | 70.31 | 03-MAY-21:49 | 30.00 | 18.00 |
| June | 0.220993E+10 | 1691.69 | 19-JUN-13:00 | 35.00 | 23.93 | 0.120410E+09 | 70.30 | 20-JUN-18:30 | 23.35 | 17.08 |
| July | 0.284695E+10 | 1711.48 | 10-JUL-13:30 | 32.50 | 20.67 | 0.129275E+09 | 70.30 | 24-JUL-19:49 | 23.40 | 19.16 |
| August | 0.307206E+10 | 1979.48 | 18-AUG-13:20 | 33.30 | 20.39 | 0.123963E+09 | 70.30 | 20-AUG-09:00 | 23.90 | 15.38 |
| September | 0.233485E+10 | 2038.51 | 01-SEP-13:00 | 30.60 | 18.37 | 0.123923E+09 | 70.32 | 24-SEP-01:00 | 12.80 | 9.34 |
| October | 0.203309E+10 | 1950.70 | 04-OCT-13:30 | 24.70 | 18.75 | 0.124984E+09 | 70.32 | 26-OCT-03:39 | 12.97 | 5.81 |
| November | 0.104664E+10 | 1365.07 | 02-NOV-12:50 | 15.50 | 8.17 | 92762923.67 | 70.31 | 09-NOV-21:40 | 12.40 | 12.28 |
| December | 0.773367E+09 | 705.97 | 21-DEC-22:00 | -1.7 | -5.0 | 82088731.97 | 68.65 | 17-DEC-16:10 | -1.7 | -5.0 |
| Annual Sum or Average | 0.194578E+11 | 0.126180E+10 | ||||||||
| Minimum of Months | 0.583731E+09 | 705.97 | -7.0 | -10.0 | 71919712.38 | 59.22 | -5.6 | -8.8 | ||
| Maximum of Months | 0.307206E+10 | 2038.51 | 35.00 | 23.93 | 0.129275E+09 | 70.32 | 30.00 | 19.16 |
Report: ZoneCoolingSummaryMonthly
For: M S2 APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.584153E+09 | 824.98 | 31-JAN-10:50 | -5.8 | -8.9 | 79135566.59 | 59.09 | 17-JAN-18:10 | -5.8 | -8.9 |
| February | 0.700670E+09 | 864.48 | 12-FEB-12:20 | -7.0 | -10.0 | 71921910.28 | 63.21 | 20-FEB-16:10 | 7.12 | 4.40 |
| March | 0.104634E+10 | 772.60 | 03-MAR-14:00 | 15.00 | 8.62 | 85308874.06 | 70.31 | 03-MAR-20:19 | 11.50 | 6.74 |
| April | 0.119552E+10 | 1680.59 | 08-APR-12:20 | 23.87 | 16.21 | 0.103306E+09 | 70.32 | 25-APR-21:10 | 13.12 | 9.96 |
| May | 0.161812E+10 | 1575.76 | 30-MAY-13:00 | 30.00 | 18.00 | 0.124615E+09 | 70.32 | 03-MAY-21:00 | 30.00 | 18.00 |
| June | 0.220765E+10 | 1695.87 | 19-JUN-13:00 | 35.00 | 23.93 | 0.120411E+09 | 70.30 | 20-JUN-18:30 | 23.35 | 17.08 |
| July | 0.284655E+10 | 1715.81 | 10-JUL-13:30 | 32.50 | 20.67 | 0.129275E+09 | 70.30 | 24-JUL-19:49 | 23.40 | 19.16 |
| August | 0.307185E+10 | 1985.41 | 18-AUG-13:20 | 33.30 | 20.39 | 0.123963E+09 | 70.30 | 20-AUG-09:00 | 23.90 | 15.38 |
| September | 0.233542E+10 | 2043.74 | 01-SEP-13:00 | 30.60 | 18.37 | 0.123923E+09 | 70.32 | 24-SEP-01:00 | 12.80 | 9.34 |
| October | 0.203325E+10 | 1954.74 | 04-OCT-13:20 | 24.80 | 18.68 | 0.124976E+09 | 70.31 | 07-OCT-00:10 | 11.93 | 7.16 |
| November | 0.105180E+10 | 1376.73 | 02-NOV-12:50 | 15.50 | 8.17 | 92840125.08 | 70.31 | 04-NOV-01:00 | 11.70 | 9.61 |
| December | 0.774613E+09 | 706.18 | 21-DEC-22:00 | -1.7 | -5.0 | 82101552.73 | 68.64 | 17-DEC-16:10 | -1.7 | -5.0 |
| Annual Sum or Average | 0.194659E+11 | 0.126178E+10 | ||||||||
| Minimum of Months | 0.584153E+09 | 706.18 | -7.0 | -10.0 | 71921910.28 | 59.09 | -5.8 | -8.9 | ||
| Maximum of Months | 0.307185E+10 | 2043.74 | 35.00 | 23.93 | 0.129275E+09 | 70.32 | 30.00 | 19.16 |
Report: ZoneCoolingSummaryMonthly
For: T SW APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.127214E+09 | 1055.91 | 17-JAN-15:20 | 10.40 | 5.01 | 78375230.34 | 62.30 | 17-JAN-18:10 | 5.82 | 2.28 |
| February | 0.175205E+09 | 744.25 | 20-FEB-15:30 | 7.75 | 4.55 | 70557182.84 | 70.32 | 20-FEB-16:19 | 7.03 | 4.35 |
| March | 0.440012E+09 | 1583.39 | 03-MAR-14:30 | 15.00 | 8.51 | 79133060.41 | 70.27 | 11-MAR-16:19 | 11.30 | 5.48 |
| April | 0.867293E+09 | 3167.53 | 07-APR-15:20 | 25.60 | 16.01 | 89616241.98 | 70.36 | 28-APR-19:19 | 11.50 | 7.83 |
| May | 0.163027E+10 | 3217.16 | 30-MAY-15:10 | 28.30 | 17.27 | 0.108402E+09 | 70.36 | 10-MAY-23:40 | 28.30 | 17.27 |
| June | 0.278832E+10 | 3572.91 | 19-JUN-14:30 | 33.85 | 23.48 | 0.118754E+09 | 70.33 | 12-JUN-02:49 | 33.85 | 23.48 |
| July | 0.389037E+10 | 3422.08 | 10-JUL-15:10 | 32.93 | 20.87 | 0.129275E+09 | 70.30 | 02-JUL-05:30 | 32.93 | 20.87 |
| August | 0.413588E+10 | 3899.50 | 18-AUG-15:10 | 32.80 | 20.65 | 0.123604E+09 | 70.35 | 26-AUG-02:00 | 16.70 | 13.47 |
| September | 0.244507E+10 | 3765.93 | 01-SEP-14:30 | 30.85 | 17.41 | 0.118199E+09 | 70.37 | 23-SEP-18:49 | 15.60 | 9.87 |
| October | 0.148638E+10 | 3198.98 | 04-OCT-14:40 | 24.07 | 19.06 | 0.104569E+09 | 70.34 | 02-OCT-20:00 | 24.07 | 19.06 |
| November | 0.307944E+09 | 1329.16 | 02-NOV-13:00 | 15.60 | 8.21 | 78340187.50 | 70.30 | 03-NOV-18:00 | 13.30 | 9.77 |
| December | 0.171328E+09 | 1151.67 | 17-DEC-14:30 | 12.20 | 5.40 | 79109397.49 | 70.27 | 17-DEC-16:10 | 9.82 | 4.16 |
| Annual Sum or Average | 0.184653E+11 | 0.117793E+10 | ||||||||
| Minimum of Months | 0.127214E+09 | 744.25 | 7.75 | 4.55 | 70557182.84 | 62.30 | 5.82 | 2.28 | ||
| Maximum of Months | 0.413588E+10 | 3899.50 | 33.85 | 23.48 | 0.129275E+09 | 70.37 | 33.85 | 23.48 |
Report: ZoneCoolingSummaryMonthly
For: T NW APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 4745911.45 | 399.72 | 17-JAN-16:40 | 7.80 | 3.64 | 77896653.01 | 42.51 | 09-JAN-22:00 | 7.80 | 3.64 |
| February | 12698142.41 | 419.06 | 20-FEB-16:00 | 7.20 | 4.44 | 70357268.42 | 42.51 | 05-FEB-06:49 | 7.20 | 4.44 |
| March | 0.134820E+09 | 750.23 | 27-MAR-16:40 | 21.47 | 15.72 | 79717963.00 | 61.14 | 27-MAR-17:10 | 20.73 | 15.29 |
| April | 0.518775E+09 | 2104.26 | 07-APR-16:10 | 25.68 | 16.13 | 87699297.99 | 70.27 | 08-APR-21:19 | 14.23 | 12.77 |
| May | 0.139546E+10 | 2994.33 | 30-MAY-16:12 | 27.40 | 17.96 | 0.110428E+09 | 70.37 | 25-MAY-21:49 | 27.40 | 17.96 |
| June | 0.262007E+10 | 3369.50 | 19-JUN-17:17 | 32.93 | 24.09 | 0.123040E+09 | 70.33 | 11-JUN-00:00 | 32.93 | 24.09 |
| July | 0.364343E+10 | 3150.36 | 13-JUL-16:08 | 28.72 | 23.99 | 0.128774E+09 | 70.30 | 17-JUL-00:00 | 23.30 | 20.65 |
| August | 0.349410E+10 | 3267.86 | 18-AUG-16:17 | 32.43 | 20.46 | 0.128347E+09 | 70.34 | 29-AUG-02:30 | 17.50 | 14.13 |
| September | 0.172207E+10 | 2614.86 | 01-SEP-14:40 | 30.77 | 17.43 | 0.117519E+09 | 70.36 | 18-SEP-22:40 | 16.87 | 11.47 |
| October | 0.646399E+09 | 1875.89 | 04-OCT-15:30 | 23.35 | 19.12 | 98670575.96 | 70.31 | 04-OCT-23:19 | 17.60 | 16.10 |
| November | 88307016.52 | 330.53 | 03-NOV-18:00 | 11.70 | 8.75 | 76221452.43 | 52.79 | 03-NOV-17:10 | 11.70 | 8.75 |
| December | 1483046.24 | 200.94 | 17-DEC-15:10 | 11.83 | 5.29 | 77895344.66 | 42.51 | 22-DEC-22:00 | 2.20 | 1.52 |
| Annual Sum or Average | 0.142824E+11 | 0.117657E+10 | ||||||||
| Minimum of Months | 1483046.24 | 200.94 | 7.20 | 3.64 | 70357268.42 | 42.51 | 2.20 | 1.52 | ||
| Maximum of Months | 0.364343E+10 | 3369.50 | 32.93 | 24.09 | 0.128774E+09 | 70.37 | 32.93 | 24.09 |
Report: ZoneCoolingSummaryMonthly
For: T SE APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.126303E+09 | 794.19 | 17-JAN-14:10 | 11.02 | 5.14 | 78287553.69 | 58.20 | 17-JAN-18:10 | 5.82 | 2.28 |
| February | 0.179519E+09 | 726.44 | 03-FEB-11:20 | -2.6 | -5.9 | 70446509.23 | 66.68 | 19-FEB-16:10 | 9.13 | 3.69 |
| March | 0.418981E+09 | 1523.40 | 01-MAR-13:40 | 13.90 | 6.20 | 78333715.85 | 70.27 | 11-MAR-16:19 | 11.30 | 5.48 |
| April | 0.859137E+09 | 2885.38 | 07-APR-12:50 | 26.52 | 16.23 | 89040351.84 | 70.35 | 08-APR-00:30 | 16.65 | 13.01 |
| May | 0.162768E+10 | 3068.66 | 30-MAY-13:00 | 30.00 | 18.00 | 0.108085E+09 | 70.36 | 28-MAY-00:40 | 30.00 | 18.00 |
| June | 0.272152E+10 | 3487.72 | 19-JUN-13:00 | 35.00 | 23.93 | 0.118852E+09 | 70.36 | 05-JUN-00:20 | 35.00 | 23.93 |
| July | 0.388341E+10 | 3261.07 | 10-JUL-13:30 | 32.50 | 20.67 | 0.129275E+09 | 70.30 | 24-JUL-19:49 | 23.40 | 19.16 |
| August | 0.411869E+10 | 3630.62 | 18-AUG-13:00 | 33.30 | 20.31 | 0.123600E+09 | 70.36 | 08-AUG-00:40 | 33.30 | 20.31 |
| September | 0.244702E+10 | 3545.19 | 01-SEP-13:00 | 30.60 | 18.37 | 0.118268E+09 | 70.35 | 28-SEP-01:10 | 18.22 | 15.19 |
| October | 0.145465E+10 | 2933.28 | 04-OCT-13:00 | 25.00 | 18.54 | 0.104039E+09 | 70.35 | 02-OCT-22:00 | 25.00 | 18.54 |
| November | 0.329304E+09 | 1436.75 | 02-NOV-13:00 | 15.60 | 8.21 | 78471978.69 | 70.27 | 04-NOV-15:00 | 17.80 | 11.31 |
| December | 0.180288E+09 | 1007.69 | 17-DEC-13:30 | 12.20 | 5.12 | 79121382.27 | 68.75 | 17-DEC-16:10 | 9.82 | 4.16 |
| Annual Sum or Average | 0.183465E+11 | 0.117582E+10 | ||||||||
| Minimum of Months | 0.126303E+09 | 726.44 | -2.6 | -5.9 | 70446509.23 | 58.20 | 5.82 | 2.28 | ||
| Maximum of Months | 0.411869E+10 | 3630.62 | 35.00 | 23.93 | 0.129275E+09 | 70.36 | 35.00 | 23.93 |
Report: ZoneCoolingSummaryMonthly
For: T NE APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 1104909.45 | 90.57 | 17-JAN-14:30 | 10.85 | 5.11 | 77895344.52 | 42.51 | 09-JAN-22:00 | 10.85 | 5.11 |
| February | 3961140.93 | 156.96 | 19-FEB-15:10 | 9.40 | 3.82 | 70357085.49 | 42.51 | 05-FEB-06:49 | 9.40 | 3.82 |
| March | 0.127344E+09 | 452.88 | 29-MAR-09:30 | 6.15 | 3.19 | 79098304.33 | 61.15 | 27-MAR-17:19 | 6.15 | 3.19 |
| April | 0.506615E+09 | 1603.50 | 08-APR-12:00 | 24.40 | 16.25 | 87196707.84 | 70.30 | 09-APR-20:10 | 13.40 | 12.16 |
| May | 0.138680E+10 | 2470.18 | 30-MAY-13:00 | 30.00 | 18.00 | 0.110297E+09 | 70.36 | 29-MAY-00:20 | 30.00 | 18.00 |
| June | 0.255435E+10 | 2955.12 | 19-JUN-12:00 | 36.70 | 24.28 | 0.123091E+09 | 70.33 | 13-JUN-01:49 | 36.70 | 24.28 |
| July | 0.363651E+10 | 2769.45 | 08-JUL-12:00 | 32.20 | 26.10 | 0.128774E+09 | 70.30 | 17-JUL-00:00 | 23.30 | 20.65 |
| August | 0.347656E+10 | 2683.97 | 01-AUG-10:50 | 30.40 | 23.09 | 0.128329E+09 | 70.34 | 08-AUG-00:30 | 16.70 | 13.58 |
| September | 0.171043E+10 | 2275.13 | 01-SEP-13:00 | 30.60 | 18.37 | 0.117628E+09 | 70.36 | 27-SEP-20:30 | 20.30 | 15.67 |
| October | 0.628976E+09 | 1407.87 | 04-OCT-13:00 | 25.00 | 18.54 | 97349377.46 | 70.29 | 04-OCT-20:00 | 17.20 | 15.82 |
| November | 95426693.96 | 322.28 | 08-NOV-18:00 | 10.60 | 9.39 | 76095495.76 | 51.31 | 04-NOV-20:10 | 10.60 | 9.39 |
| December | 879569.78 | 98.03 | 20-DEC-12:00 | 8.90 | 5.16 | 77895344.67 | 42.51 | 22-DEC-22:00 | 2.20 | 1.52 |
| Annual Sum or Average | 0.141290E+11 | 0.117401E+10 | ||||||||
| Minimum of Months | 879569.78 | 90.57 | 6.15 | 3.19 | 70357085.49 | 42.51 | 2.20 | 1.52 | ||
| Maximum of Months | 0.363651E+10 | 2955.12 | 36.70 | 26.10 | 0.128774E+09 | 70.36 | 36.70 | 24.28 |
Report: ZoneCoolingSummaryMonthly
For: T N1 APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 4368179.55 | 198.75 | 17-JAN-17:02 | 6.60 | 2.87 | 77895344.60 | 42.51 | 14-JAN-22:00 | 6.60 | 2.87 |
| February | 10599428.42 | 222.58 | 19-FEB-16:10 | 9.13 | 3.69 | 70357085.49 | 42.51 | 05-FEB-06:49 | 9.13 | 3.69 |
| March | 0.166709E+09 | 466.69 | 29-MAR-17:12 | 5.73 | 4.14 | 79455419.21 | 61.14 | 27-MAR-17:10 | 5.73 | 4.14 |
| April | 0.512011E+09 | 1201.59 | 07-APR-16:17 | 25.77 | 16.13 | 88805709.39 | 70.36 | 08-APR-00:20 | 16.83 | 13.04 |
| May | 0.119198E+10 | 1874.70 | 30-MAY-16:08 | 27.85 | 17.79 | 0.114508E+09 | 70.37 | 10-MAY-23:40 | 27.85 | 17.79 |
| June | 0.215549E+10 | 2249.00 | 19-JUN-17:30 | 32.75 | 23.87 | 0.123822E+09 | 70.36 | 05-JUN-00:00 | 32.75 | 23.87 |
| July | 0.299888E+10 | 2131.81 | 07-JUL-15:10 | 31.73 | 23.66 | 0.128774E+09 | 70.30 | 17-JUL-00:00 | 23.30 | 20.65 |
| August | 0.278887E+10 | 2051.70 | 24-AUG-16:17 | 33.70 | 19.16 | 0.128556E+09 | 70.33 | 26-AUG-03:20 | 16.50 | 13.36 |
| September | 0.146719E+10 | 1750.42 | 01-SEP-15:10 | 30.22 | 17.51 | 0.119956E+09 | 70.35 | 03-SEP-04:49 | 17.20 | 12.73 |
| October | 0.628706E+09 | 1096.11 | 04-OCT-15:10 | 23.72 | 19.12 | 0.100846E+09 | 70.34 | 06-OCT-01:30 | 18.90 | 18.13 |
| November | 0.139348E+09 | 332.93 | 04-NOV-03:00 | 10.00 | 9.07 | 76561413.19 | 55.02 | 04-NOV-20:10 | 13.72 | 8.61 |
| December | 2805646.12 | 135.46 | 04-DEC-19:00 | 8.90 | 7.75 | 77895344.66 | 42.51 | 22-DEC-22:00 | 2.20 | 1.52 |
| Annual Sum or Average | 0.120670E+11 | 0.118743E+10 | ||||||||
| Minimum of Months | 2805646.12 | 135.46 | 5.73 | 2.87 | 70357085.49 | 42.51 | 2.20 | 1.52 | ||
| Maximum of Months | 0.299888E+10 | 2249.00 | 33.70 | 23.87 | 0.128774E+09 | 70.37 | 32.75 | 23.87 |
Report: ZoneCoolingSummaryMonthly
For: T N2 APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 4276283.04 | 188.16 | 17-JAN-17:02 | 6.60 | 2.87 | 77895344.60 | 42.51 | 14-JAN-22:00 | 6.60 | 2.87 |
| February | 10565195.52 | 218.41 | 19-FEB-16:10 | 9.13 | 3.69 | 70357085.49 | 42.51 | 05-FEB-06:49 | 9.13 | 3.69 |
| March | 0.165440E+09 | 449.86 | 29-MAR-16:50 | 6.28 | 4.43 | 79411582.46 | 61.20 | 27-MAR-17:19 | 6.28 | 4.43 |
| April | 0.513616E+09 | 1194.25 | 07-APR-16:17 | 25.77 | 16.13 | 88811410.54 | 70.36 | 08-APR-00:20 | 16.83 | 13.04 |
| May | 0.119587E+10 | 1860.62 | 30-MAY-16:08 | 27.85 | 17.79 | 0.114460E+09 | 70.36 | 17-MAY-22:00 | 27.85 | 17.79 |
| June | 0.215373E+10 | 2248.05 | 19-JUN-14:30 | 33.85 | 23.48 | 0.123815E+09 | 70.35 | 02-JUN-01:49 | 33.85 | 23.48 |
| July | 0.299877E+10 | 2121.97 | 07-JUL-15:10 | 31.73 | 23.66 | 0.128774E+09 | 70.30 | 17-JUL-00:00 | 23.30 | 20.65 |
| August | 0.278906E+10 | 2041.85 | 24-AUG-16:17 | 33.70 | 19.16 | 0.128552E+09 | 70.34 | 29-AUG-03:30 | 16.95 | 14.09 |
| September | 0.146920E+10 | 1744.62 | 01-SEP-14:30 | 30.85 | 17.41 | 0.119969E+09 | 70.37 | 24-SEP-20:10 | 15.60 | 11.90 |
| October | 0.629143E+09 | 1090.43 | 04-OCT-15:10 | 23.72 | 19.12 | 0.100698E+09 | 70.32 | 15-OCT-21:10 | 14.60 | 11.30 |
| November | 0.140247E+09 | 329.48 | 08-NOV-18:00 | 10.60 | 9.39 | 76556617.06 | 55.11 | 04-NOV-20:10 | 10.60 | 9.39 |
| December | 2909674.68 | 133.30 | 04-DEC-19:00 | 8.90 | 7.75 | 77895344.66 | 42.51 | 22-DEC-22:00 | 2.20 | 1.52 |
| Annual Sum or Average | 0.120728E+11 | 0.118719E+10 | ||||||||
| Minimum of Months | 2909674.68 | 133.30 | 6.28 | 2.87 | 70357085.49 | 42.51 | 2.20 | 1.52 | ||
| Maximum of Months | 0.299877E+10 | 2248.05 | 33.85 | 23.66 | 0.128774E+09 | 70.37 | 33.85 | 23.48 |
Report: ZoneCoolingSummaryMonthly
For: T S1 APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.205709E+09 | 946.39 | 17-JAN-14:30 | 10.85 | 5.11 | 78544822.96 | 63.32 | 17-JAN-18:10 | 5.82 | 2.28 |
| February | 0.273844E+09 | 747.83 | 09-FEB-12:00 | -3.3 | -6.0 | 70925915.64 | 69.71 | 19-FEB-16:10 | 9.13 | 3.69 |
| March | 0.547282E+09 | 1427.79 | 03-MAR-14:00 | 15.00 | 8.62 | 79979464.83 | 70.28 | 15-MAR-18:00 | 12.20 | 4.31 |
| April | 0.864923E+09 | 2401.22 | 07-APR-13:00 | 26.70 | 16.40 | 92061962.02 | 70.37 | 26-APR-21:10 | 13.72 | 10.80 |
| May | 0.142406E+10 | 2415.17 | 30-MAY-13:00 | 30.00 | 18.00 | 0.112799E+09 | 70.36 | 10-MAY-00:49 | 30.00 | 18.00 |
| June | 0.232412E+10 | 2713.38 | 19-JUN-13:30 | 34.70 | 23.81 | 0.119547E+09 | 70.35 | 02-JUN-01:00 | 34.70 | 23.81 |
| July | 0.324781E+10 | 2616.38 | 10-JUL-13:40 | 32.60 | 20.74 | 0.129275E+09 | 70.30 | 24-JUL-19:49 | 23.40 | 19.16 |
| August | 0.343578E+10 | 2957.09 | 18-AUG-13:30 | 33.30 | 20.43 | 0.123800E+09 | 70.36 | 26-AUG-03:49 | 16.20 | 13.20 |
| September | 0.221002E+10 | 2951.25 | 01-SEP-13:20 | 30.77 | 18.04 | 0.120670E+09 | 70.36 | 11-SEP-00:40 | 15.20 | 9.67 |
| October | 0.149857E+10 | 2584.33 | 04-OCT-13:30 | 24.70 | 18.75 | 0.109384E+09 | 70.35 | 18-OCT-18:10 | 10.68 | 5.08 |
| November | 0.459706E+09 | 1445.96 | 02-NOV-13:00 | 15.60 | 8.21 | 80385988.14 | 70.37 | 02-NOV-19:10 | 13.22 | 7.12 |
| December | 0.280862E+09 | 1164.18 | 17-DEC-14:00 | 12.20 | 5.29 | 79668626.56 | 70.27 | 17-DEC-16:10 | 9.82 | 4.16 |
| Annual Sum or Average | 0.167727E+11 | 0.119704E+10 | ||||||||
| Minimum of Months | 0.205709E+09 | 747.83 | -3.3 | -6.0 | 70925915.64 | 63.32 | 5.82 | 2.28 | ||
| Maximum of Months | 0.343578E+10 | 2957.09 | 34.70 | 23.81 | 0.129275E+09 | 70.37 | 34.70 | 23.81 |
Report: ZoneCoolingSummaryMonthly
For: T S2 APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.205947E+09 | 951.52 | 17-JAN-14:20 | 10.93 | 5.12 | 78537065.28 | 63.09 | 17-JAN-18:10 | 5.82 | 2.28 |
| February | 0.274644E+09 | 752.98 | 09-FEB-11:50 | -3.5 | -6.1 | 70916542.54 | 69.69 | 19-FEB-16:10 | 9.13 | 3.69 |
| March | 0.547702E+09 | 1442.21 | 03-MAR-14:00 | 15.00 | 8.62 | 79901484.62 | 70.36 | 03-MAR-20:10 | 11.60 | 6.75 |
| April | 0.868801E+09 | 2420.97 | 07-APR-13:00 | 26.70 | 16.40 | 92017354.89 | 70.36 | 26-APR-20:00 | 13.90 | 10.83 |
| May | 0.142841E+10 | 2429.32 | 30-MAY-13:00 | 30.00 | 18.00 | 0.112721E+09 | 70.37 | 10-MAY-00:00 | 30.00 | 18.00 |
| June | 0.232243E+10 | 2721.60 | 19-JUN-13:20 | 34.80 | 23.85 | 0.119542E+09 | 70.35 | 05-JUN-01:10 | 34.80 | 23.85 |
| July | 0.324776E+10 | 2621.25 | 10-JUL-13:30 | 32.50 | 20.67 | 0.129275E+09 | 70.30 | 24-JUL-19:49 | 23.40 | 19.16 |
| August | 0.343598E+10 | 2966.95 | 18-AUG-13:20 | 33.30 | 20.39 | 0.123796E+09 | 70.36 | 25-AUG-05:40 | 18.17 | 13.31 |
| September | 0.221215E+10 | 2959.96 | 01-SEP-13:20 | 30.77 | 18.04 | 0.120660E+09 | 70.36 | 16-SEP-00:00 | 15.60 | 11.59 |
| October | 0.150110E+10 | 2591.75 | 04-OCT-13:30 | 24.70 | 18.75 | 0.109312E+09 | 70.37 | 19-OCT-19:10 | 13.80 | 11.86 |
| November | 0.463082E+09 | 1463.85 | 02-NOV-13:00 | 15.60 | 8.21 | 80410191.03 | 70.37 | 02-NOV-19:10 | 13.22 | 7.12 |
| December | 0.281881E+09 | 1175.66 | 17-DEC-13:50 | 12.20 | 5.23 | 79666626.84 | 70.27 | 17-DEC-16:10 | 9.82 | 4.16 |
| Annual Sum or Average | 0.167899E+11 | 0.119676E+10 | ||||||||
| Minimum of Months | 0.205947E+09 | 752.98 | -3.5 | -6.1 | 70916542.54 | 63.09 | 5.82 | 2.28 | ||
| Maximum of Months | 0.343598E+10 | 2966.95 | 34.80 | 23.85 | 0.129275E+09 | 70.37 | 34.80 | 23.85 |
Report: ZoneCoolingSummaryMonthly
For: T CORRIDOR
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | -9.6 | -11.5 | 0.101796E+09 | 81.15 | 17-JAN-21:10 | 2.70 | 2.04 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | -1.1 | -4.2 | 93662293.89 | 80.13 | 19-FEB-18:10 | 5.63 | 1.96 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 5.52 | 4.35 | 0.135540E+09 | 124.68 | 27-MAR-20:10 | 15.82 | 11.86 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 5.27 | 4.90 | 0.170037E+09 | 155.32 | 07-APR-20:10 | 21.32 | 14.59 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 10.33 | 9.91 | 0.232291E+09 | 167.05 | 30-MAY-20:10 | 19.90 | 15.53 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 | 16.59 | 0.267702E+09 | 182.28 | 19-JUN-20:10 | 29.82 | 21.80 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 | 19.29 | 0.291685E+09 | 176.89 | 10-JUL-20:10 | 28.12 | 20.24 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 | 21.46 | 0.289658E+09 | 178.45 | 04-AUG-20:10 | 32.20 | 24.15 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 | 19.79 | 0.251461E+09 | 169.00 | 01-SEP-20:10 | 26.70 | 17.93 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 | 11.77 | 0.206708E+09 | 150.85 | 04-OCT-20:10 | 18.62 | 16.03 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 10.40 | 9.04 | 0.127467E+09 | 114.70 | 04-NOV-20:10 | 13.72 | 8.61 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 5.97 | 2.86 | 0.109234E+09 | 82.49 | 17-DEC-21:10 | 5.50 | 2.04 |
| Annual Sum or Average | 0.00 | 0.227724E+10 | ||||||||
| Minimum of Months | 0.00 | 0.00 | -9.6 | -11.5 | 93662293.89 | 80.13 | 2.70 | 1.96 | ||
| Maximum of Months | 0.00 | 0.00 | 23.90 | 21.46 | 0.291685E+09 | 182.28 | 32.20 | 24.15 |
Report: ZoneCoolingSummaryMonthly
For: G CORRIDOR
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | -9.6 | -11.5 | 61958432.37 | 66.99 | 20-JAN-06:10 | 4.90 | -0.5 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | -1.1 | -4.2 | 53467981.36 | 64.02 | 21-FEB-06:10 | 2.30 | 1.57 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 5.52 | 4.35 | 86005481.80 | 82.14 | 27-MAR-21:49 | 13.07 | 10.05 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 5.27 | 4.90 | 0.122672E+09 | 120.79 | 10-APR-21:49 | 11.47 | 5.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 10.33 | 9.91 | 0.188415E+09 | 156.66 | 30-MAY-21:49 | 18.98 | 14.93 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 | 16.59 | 0.259596E+09 | 206.59 | 19-JUN-17:10 | 33.12 | 24.31 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 | 19.29 | 0.298884E+09 | 185.74 | 10-JUL-20:10 | 28.12 | 20.24 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 | 21.46 | 0.303926E+09 | 210.49 | 24-AUG-17:10 | 32.93 | 18.15 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 | 19.79 | 0.254510E+09 | 175.87 | 01-SEP-20:10 | 26.70 | 17.93 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 | 11.77 | 0.212705E+09 | 154.53 | 05-OCT-21:49 | 18.90 | 17.51 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 10.40 | 9.04 | 0.116050E+09 | 117.58 | 04-NOV-23:40 | 11.30 | 7.54 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 5.97 | 2.86 | 77809408.45 | 73.75 | 20-DEC-06:10 | 3.53 | 1.84 |
| Annual Sum or Average | 0.00 | 0.203600E+10 | ||||||||
| Minimum of Months | 0.00 | 0.00 | -9.6 | -11.5 | 53467981.36 | 64.02 | 2.30 | -0.5 | ||
| Maximum of Months | 0.00 | 0.00 | 23.90 | 21.46 | 0.303926E+09 | 210.49 | 33.12 | 24.31 |
Report: ZoneCoolingSummaryMonthly
For: M CORRIDOR
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | -9.6 | -11.5 | 0.144544E+09 | 93.83 | 17-JAN-21:10 | 2.70 | 2.04 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | -1.1 | -4.2 | 0.134441E+09 | 97.52 | 20-FEB-21:10 | 3.40 | 2.38 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 5.52 | 4.35 | 0.170728E+09 | 115.17 | 28-MAR-20:10 | 9.22 | 6.43 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 5.27 | 4.90 | 0.204683E+09 | 150.46 | 09-APR-20:10 | 13.40 | 12.16 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 10.33 | 9.91 | 0.265718E+09 | 160.68 | 30-MAY-20:10 | 19.90 | 15.53 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 | 16.59 | 0.272705E+09 | 165.07 | 19-JUN-20:10 | 29.82 | 21.80 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 | 19.29 | 0.287891E+09 | 164.43 | 10-JUL-20:10 | 28.12 | 20.24 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 | 21.46 | 0.288767E+09 | 164.56 | 04-AUG-20:10 | 32.20 | 24.15 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 | 19.79 | 0.267345E+09 | 161.16 | 01-SEP-20:10 | 26.70 | 17.93 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 | 11.77 | 0.252387E+09 | 153.90 | 04-OCT-20:10 | 18.62 | 16.03 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 10.40 | 9.04 | 0.172883E+09 | 129.31 | 04-NOV-20:10 | 13.72 | 8.61 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 5.97 | 2.86 | 0.152189E+09 | 98.23 | 17-DEC-21:19 | 5.40 | 1.98 |
| Annual Sum or Average | 0.00 | 0.261428E+10 | ||||||||
| Minimum of Months | 0.00 | 0.00 | -9.6 | -11.5 | 0.134441E+09 | 93.83 | 2.70 | 1.98 | ||
| Maximum of Months | 0.00 | 0.00 | 23.90 | 21.46 | 0.288767E+09 | 165.07 | 32.20 | 24.15 |
Report: ZoneHeatingSummaryMonthly
For: G SW APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.129355E+10 | 1472.58 | 02-JAN-00:10 | -10.7 |
| February | 0.113779E+10 | 1680.53 | 06-FEB-05:00 | -13.3 |
| March | 0.501875E+09 | 1043.16 | 22-MAR-07:00 | -2.8 |
| April | 0.191755E+09 | 691.10 | 02-APR-06:00 | 3.30 |
| May | 367418.10 | 114.07 | 08-MAY-05:20 | 12.87 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 |
| November | 0.156836E+09 | 826.43 | 23-NOV-02:00 | -2.8 |
| December | 0.640682E+09 | 1176.04 | 31-DEC-22:10 | -7.3 |
| Annual Sum or Average | 0.392286E+10 | |||
| Minimum of Months | 0.00 | 0.00 | -13.3 | |
| Maximum of Months | 0.129355E+10 | 1680.53 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: G NW APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.194474E+10 | 1755.06 | 02-JAN-00:10 | -10.7 |
| February | 0.198652E+10 | 2013.72 | 06-FEB-01:10 | -13.3 |
| March | 0.102456E+10 | 1291.46 | 22-MAR-07:00 | -2.8 |
| April | 0.316459E+09 | 741.82 | 02-APR-06:00 | 3.30 |
| May | 8005611.64 | 305.53 | 03-MAY-04:00 | 11.70 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 |
| November | 0.402338E+09 | 1098.74 | 23-NOV-02:00 | -2.8 |
| December | 0.121457E+10 | 1454.79 | 31-DEC-22:08 | -7.3 |
| Annual Sum or Average | 0.689719E+10 | |||
| Minimum of Months | 0.00 | 0.00 | -13.3 | |
| Maximum of Months | 0.198652E+10 | 2013.72 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: OFFICE
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.607319E+09 | 10192.36 | 03-JAN-07:01 | 5.97 |
| February | 0.575900E+09 | 9968.44 | 28-FEB-07:01 | 1.78 |
| March | 0.175313E+09 | 9962.66 | 01-MAR-08:61 | 8.35 |
| April | 90389166.01 | 9975.52 | 03-APR-07:01 | 3.68 |
| May | 0.139400E+09 | 557.45 | 22-MAY-08:05 | 21.28 |
| June | 0.313726E+09 | 679.84 | 19-JUN-16:12 | 31.83 |
| July | 0.471080E+09 | 595.99 | 10-JUL-06:05 | 26.20 |
| August | 0.364036E+09 | 706.11 | 24-AUG-16:13 | 33.70 |
| September | 0.164185E+09 | 557.22 | 14-SEP-16:12 | 29.07 |
| October | 27956736.04 | 395.88 | 06-OCT-07:05 | 20.00 |
| November | 28842555.25 | 9899.45 | 29-NOV-08:61 | 4.18 |
| December | 0.168988E+09 | 9976.31 | 26-DEC-08:61 | 6.70 |
| Annual Sum or Average | 0.312714E+10 | |||
| Minimum of Months | 27956736.04 | 395.88 | 1.78 | |
| Maximum of Months | 0.607319E+09 | 10192.36 | 33.70 |
Report: ZoneHeatingSummaryMonthly
For: G NE APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.192566E+10 | 1715.71 | 02-JAN-00:10 | -10.7 |
| February | 0.195048E+10 | 1984.31 | 06-FEB-01:10 | -13.3 |
| March | 0.104034E+10 | 1219.64 | 22-MAR-06:00 | -2.8 |
| April | 0.307832E+09 | 897.96 | 19-APR-17:01 | 8.72 |
| May | 7680755.47 | 309.51 | 03-MAY-04:00 | 11.70 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 |
| November | 0.367415E+09 | 1067.32 | 23-NOV-02:00 | -2.8 |
| December | 0.118373E+10 | 1462.55 | 31-DEC-22:10 | -7.3 |
| Annual Sum or Average | 0.678315E+10 | |||
| Minimum of Months | 0.00 | 0.00 | -13.3 | |
| Maximum of Months | 0.195048E+10 | 1984.31 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: G N1 APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.893335E+09 | 989.91 | 02-JAN-00:10 | -10.7 |
| February | 0.988899E+09 | 1137.89 | 06-FEB-08:16 | -12.6 |
| March | 0.388398E+09 | 687.24 | 22-MAR-07:05 | -2.7 |
| April | 64735499.98 | 311.31 | 02-APR-04:00 | 3.90 |
| May | 120997.61 | 75.29 | 03-MAY-14:15 | 15.77 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 |
| November | 99392726.96 | 529.78 | 23-NOV-02:00 | -2.8 |
| December | 0.395150E+09 | 752.33 | 31-DEC-22:10 | -7.3 |
| Annual Sum or Average | 0.283003E+10 | |||
| Minimum of Months | 0.00 | 0.00 | -12.6 | |
| Maximum of Months | 0.988899E+09 | 1137.89 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: G N2 APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.892426E+09 | 987.61 | 02-JAN-00:10 | -10.7 |
| February | 0.987530E+09 | 1136.13 | 06-FEB-01:10 | -13.3 |
| March | 0.389551E+09 | 686.88 | 22-MAR-07:05 | -2.7 |
| April | 64843334.24 | 313.11 | 02-APR-04:00 | 3.90 |
| May | 117519.59 | 68.65 | 03-MAY-14:15 | 15.77 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 |
| November | 98167247.97 | 527.37 | 23-NOV-02:00 | -2.8 |
| December | 0.393840E+09 | 753.02 | 31-DEC-22:10 | -7.3 |
| Annual Sum or Average | 0.282647E+10 | |||
| Minimum of Months | 0.00 | 0.00 | -13.3 | |
| Maximum of Months | 0.987530E+09 | 1136.13 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: G S1 APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.411670E+09 | 706.93 | 02-JAN-00:10 | -10.7 |
| February | 0.318472E+09 | 805.19 | 06-FEB-05:00 | -13.3 |
| March | 88448203.00 | 445.99 | 22-MAR-07:10 | -2.7 |
| April | 26383189.36 | 245.26 | 02-APR-04:00 | 3.90 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 10.33 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 |
| November | 11085489.19 | 280.36 | 23-NOV-02:00 | -2.8 |
| December | 0.116146E+09 | 504.54 | 31-DEC-22:10 | -7.3 |
| Annual Sum or Average | 0.972204E+09 | |||
| Minimum of Months | 0.00 | 0.00 | -13.3 | |
| Maximum of Months | 0.411670E+09 | 805.19 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: G S2 APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.583260E+09 | 890.31 | 02-JAN-00:10 | -10.7 |
| February | 0.444536E+09 | 965.51 | 06-FEB-05:00 | -13.3 |
| March | 0.127216E+09 | 517.39 | 22-MAR-07:10 | -2.7 |
| April | 36303775.11 | 307.62 | 02-APR-04:00 | 3.90 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 10.33 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 |
| November | 20339238.09 | 323.52 | 23-NOV-02:00 | -2.8 |
| December | 0.168076E+09 | 623.78 | 31-DEC-22:10 | -7.3 |
| Annual Sum or Average | 0.137973E+10 | |||
| Minimum of Months | 0.00 | 0.00 | -13.3 | |
| Maximum of Months | 0.583260E+09 | 965.51 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: M SW APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.961267E+09 | 1477.12 | 14-JAN-17:00 | -6.1 |
| February | 0.683770E+09 | 1673.09 | 06-FEB-01:10 | -13.3 |
| March | 0.168183E+09 | 961.33 | 22-MAR-07:00 | -2.8 |
| April | 43030679.75 | 437.43 | 02-APR-06:00 | 3.30 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 10.33 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 |
| November | 0.206887E+09 | 1108.40 | 23-NOV-02:00 | -2.8 |
| December | 0.594834E+09 | 1318.13 | 31-DEC-22:04 | -7.3 |
| Annual Sum or Average | 0.265797E+10 | |||
| Minimum of Months | 0.00 | 0.00 | -13.3 | |
| Maximum of Months | 0.961267E+09 | 1673.09 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: M NW APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.146564E+10 | 1730.93 | 02-JAN-00:10 | -10.7 |
| February | 0.129604E+10 | 1997.41 | 06-FEB-01:00 | -13.3 |
| March | 0.381230E+09 | 1141.25 | 22-MAR-07:00 | -2.8 |
| April | 62251341.29 | 460.57 | 02-APR-06:00 | 3.30 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 10.33 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 |
| November | 0.441819E+09 | 1330.90 | 23-NOV-02:00 | -2.8 |
| December | 0.104613E+10 | 1591.16 | 31-DEC-22:08 | -7.3 |
| Annual Sum or Average | 0.469310E+10 | |||
| Minimum of Months | 0.00 | 0.00 | -13.3 | |
| Maximum of Months | 0.146564E+10 | 1997.41 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: M SE APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.941708E+09 | 1489.80 | 14-JAN-17:00 | -6.1 |
| February | 0.653826E+09 | 1649.07 | 06-FEB-01:10 | -13.3 |
| March | 0.172191E+09 | 940.73 | 22-MAR-06:00 | -2.8 |
| April | 43620997.13 | 426.51 | 02-APR-04:00 | 3.90 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 10.33 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 |
| November | 0.192226E+09 | 1091.25 | 23-NOV-02:00 | -2.8 |
| December | 0.582331E+09 | 1325.37 | 31-DEC-22:06 | -7.3 |
| Annual Sum or Average | 0.258590E+10 | |||
| Minimum of Months | 0.00 | 0.00 | -13.3 | |
| Maximum of Months | 0.941708E+09 | 1649.07 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: M NE APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.144139E+10 | 1695.22 | 02-JAN-00:10 | -10.7 |
| February | 0.125070E+10 | 1965.96 | 06-FEB-01:00 | -13.3 |
| March | 0.387252E+09 | 1091.69 | 22-MAR-06:00 | -2.8 |
| April | 62244628.47 | 456.64 | 21-APR-04:00 | 5.60 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 10.33 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 |
| November | 0.403327E+09 | 1305.68 | 23-NOV-02:00 | -2.8 |
| December | 0.101120E+10 | 1604.00 | 31-DEC-22:08 | -7.3 |
| Annual Sum or Average | 0.455611E+10 | |||
| Minimum of Months | 0.00 | 0.00 | -13.3 | |
| Maximum of Months | 0.144139E+10 | 1965.96 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: M N1 APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.460364E+09 | 846.88 | 02-JAN-00:10 | -10.7 |
| February | 0.422770E+09 | 1000.94 | 06-FEB-01:10 | -13.3 |
| March | 60754561.87 | 477.75 | 22-MAR-07:00 | -2.8 |
| April | 717996.58 | 76.09 | 02-APR-04:00 | 3.90 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 10.33 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 |
| November | 77641747.66 | 603.96 | 23-NOV-02:00 | -2.8 |
| December | 0.221668E+09 | 729.89 | 31-DEC-22:08 | -7.3 |
| Annual Sum or Average | 0.124392E+10 | |||
| Minimum of Months | 0.00 | 0.00 | -13.3 | |
| Maximum of Months | 0.460364E+09 | 1000.94 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: M N2 APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.459606E+09 | 844.65 | 02-JAN-00:10 | -10.7 |
| February | 0.421476E+09 | 999.14 | 06-FEB-01:10 | -13.3 |
| March | 60762763.45 | 477.41 | 22-MAR-07:00 | -2.8 |
| April | 739999.14 | 77.59 | 02-APR-04:00 | 3.90 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 10.33 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 |
| November | 76739653.52 | 602.07 | 23-NOV-02:00 | -2.8 |
| December | 0.220849E+09 | 730.27 | 31-DEC-22:08 | -7.3 |
| Annual Sum or Average | 0.124017E+10 | |||
| Minimum of Months | 0.00 | 0.00 | -13.3 | |
| Maximum of Months | 0.459606E+09 | 999.14 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: M S1 APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.211193E+09 | 658.37 | 14-JAN-06:00 | -7.8 |
| February | 0.105361E+09 | 748.61 | 06-FEB-01:10 | -13.3 |
| March | 4667731.24 | 220.63 | 22-MAR-07:00 | -2.8 |
| April | 63977.40 | 20.47 | 02-APR-04:00 | 3.90 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 10.33 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 |
| November | 14023417.96 | 401.58 | 23-NOV-02:00 | -2.8 |
| December | 82057534.20 | 477.03 | 31-DEC-22:06 | -7.3 |
| Annual Sum or Average | 0.417367E+09 | |||
| Minimum of Months | 0.00 | 0.00 | -13.3 | |
| Maximum of Months | 0.211193E+09 | 748.61 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: M S2 APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.210833E+09 | 659.07 | 14-JAN-06:00 | -7.8 |
| February | 0.105068E+09 | 747.30 | 06-FEB-01:10 | -13.3 |
| March | 4731302.50 | 221.32 | 22-MAR-06:50 | -2.8 |
| April | 77881.37 | 23.08 | 02-APR-04:00 | 3.90 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 10.33 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 |
| November | 13772811.19 | 399.39 | 23-NOV-02:00 | -2.8 |
| December | 81952168.43 | 477.39 | 31-DEC-22:08 | -7.3 |
| Annual Sum or Average | 0.416435E+09 | |||
| Minimum of Months | 0.00 | 0.00 | -13.3 | |
| Maximum of Months | 0.210833E+09 | 747.30 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: T SW APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.274310E+10 | 2966.95 | 02-JAN-00:10 | -10.7 |
| February | 0.228933E+10 | 3404.89 | 06-FEB-05:00 | -13.3 |
| March | 0.112143E+10 | 2208.49 | 22-MAR-06:50 | -2.8 |
| April | 0.447416E+09 | 1292.52 | 02-APR-06:00 | 3.30 |
| May | 12155976.80 | 438.00 | 01-MAY-05:00 | 6.10 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 |
| October | 99809489.26 | 856.36 | 08-OCT-06:00 | 4.40 |
| November | 0.112284E+10 | 2367.28 | 23-NOV-02:00 | -2.8 |
| December | 0.212148E+10 | 2626.97 | 31-DEC-22:10 | -7.3 |
| Annual Sum or Average | 0.995756E+10 | |||
| Minimum of Months | 0.00 | 0.00 | -13.3 | |
| Maximum of Months | 0.274310E+10 | 3404.89 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: T NW APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.339046E+10 | 3137.84 | 02-JAN-00:10 | -10.7 |
| February | 0.305334E+10 | 3604.06 | 06-FEB-01:00 | -13.3 |
| March | 0.149382E+10 | 2336.86 | 22-MAR-07:00 | -2.8 |
| April | 0.529805E+09 | 1304.01 | 02-APR-06:00 | 3.30 |
| May | 14506415.31 | 447.07 | 01-MAY-04:50 | 6.20 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 |
| September | 9796.77 | 107.15 | 24-SEP-06:05 | 10.37 |
| October | 0.221619E+09 | 1043.92 | 28-OCT-08:00 | 6.10 |
| November | 0.157960E+10 | 2519.63 | 23-NOV-02:00 | -2.8 |
| December | 0.279634E+10 | 2917.33 | 31-DEC-22:10 | -7.3 |
| Annual Sum or Average | 0.130795E+11 | |||
| Minimum of Months | 0.00 | 0.00 | -13.3 | |
| Maximum of Months | 0.339046E+10 | 3604.06 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: T SE APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.271852E+10 | 2938.17 | 02-JAN-00:10 | -10.7 |
| February | 0.224490E+10 | 3385.13 | 06-FEB-05:00 | -13.3 |
| March | 0.113038E+10 | 2219.26 | 22-MAR-06:00 | -2.8 |
| April | 0.439499E+09 | 1274.23 | 02-APR-05:40 | 3.50 |
| May | 11960455.42 | 459.15 | 01-MAY-04:50 | 6.20 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 |
| October | 97693645.29 | 859.97 | 08-OCT-06:00 | 4.40 |
| November | 0.108339E+10 | 2357.74 | 23-NOV-02:00 | -2.8 |
| December | 0.209234E+10 | 2640.23 | 31-DEC-22:10 | -7.3 |
| Annual Sum or Average | 0.981869E+10 | |||
| Minimum of Months | 0.00 | 0.00 | -13.3 | |
| Maximum of Months | 0.271852E+10 | 3385.13 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: T NE APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.336411E+10 | 3114.01 | 02-JAN-00:10 | -10.7 |
| February | 0.299595E+10 | 3580.79 | 06-FEB-01:00 | -13.3 |
| March | 0.150724E+10 | 2314.90 | 22-MAR-06:00 | -2.8 |
| April | 0.519361E+09 | 1289.82 | 02-APR-05:40 | 3.50 |
| May | 15202258.50 | 486.47 | 01-MAY-04:50 | 6.20 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 |
| September | 2442.97 | 8.14 | 24-SEP-05:30 | 10.30 |
| October | 0.212346E+09 | 1040.73 | 08-OCT-06:00 | 4.40 |
| November | 0.150681E+10 | 2509.67 | 23-NOV-02:00 | -2.8 |
| December | 0.275307E+10 | 2932.70 | 31-DEC-22:10 | -7.3 |
| Annual Sum or Average | 0.128741E+11 | |||
| Minimum of Months | 0.00 | 0.00 | -13.3 | |
| Maximum of Months | 0.336411E+10 | 3580.79 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: T N1 APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.198189E+10 | 1993.35 | 02-JAN-00:10 | -10.7 |
| February | 0.181371E+10 | 2308.42 | 06-FEB-01:10 | -13.3 |
| March | 0.755184E+09 | 1377.29 | 22-MAR-06:00 | -2.8 |
| April | 0.213500E+09 | 746.74 | 02-APR-04:00 | 3.90 |
| May | 627998.47 | 118.48 | 01-MAY-04:50 | 6.20 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 |
| October | 79751644.90 | 526.46 | 28-OCT-08:00 | 6.10 |
| November | 0.771831E+09 | 1563.87 | 23-NOV-02:00 | -2.8 |
| December | 0.156058E+10 | 1781.42 | 31-DEC-24:00 | -8.3 |
| Annual Sum or Average | 0.717708E+10 | |||
| Minimum of Months | 0.00 | 0.00 | -13.3 | |
| Maximum of Months | 0.198189E+10 | 2308.42 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: T N2 APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.198114E+10 | 1992.06 | 02-JAN-00:10 | -10.7 |
| February | 0.181219E+10 | 2307.31 | 06-FEB-01:10 | -13.3 |
| March | 0.756982E+09 | 1378.73 | 22-MAR-06:00 | -2.8 |
| April | 0.214477E+09 | 748.04 | 02-APR-04:00 | 3.90 |
| May | 663539.17 | 123.81 | 01-MAY-04:50 | 6.20 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 |
| October | 80142805.26 | 519.04 | 28-OCT-08:00 | 6.10 |
| November | 0.769158E+09 | 1563.24 | 23-NOV-02:00 | -2.8 |
| December | 0.155907E+10 | 1782.24 | 31-DEC-24:00 | -8.3 |
| Annual Sum or Average | 0.717383E+10 | |||
| Minimum of Months | 0.00 | 0.00 | -13.3 | |
| Maximum of Months | 0.198114E+10 | 2307.31 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: T S1 APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.142517E+10 | 1811.42 | 02-JAN-00:30 | -10.8 |
| February | 0.116006E+10 | 2154.45 | 06-FEB-05:00 | -13.3 |
| March | 0.480084E+09 | 1264.26 | 22-MAR-06:00 | -2.8 |
| April | 0.160583E+09 | 726.93 | 02-APR-04:00 | 3.90 |
| May | 342853.37 | 94.12 | 01-MAY-05:00 | 6.10 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 |
| October | 12761771.16 | 285.23 | 08-OCT-06:00 | 4.40 |
| November | 0.453723E+09 | 1400.95 | 23-NOV-02:00 | -2.8 |
| December | 0.102132E+10 | 1538.84 | 31-DEC-24:00 | -8.3 |
| Annual Sum or Average | 0.471404E+10 | |||
| Minimum of Months | 0.00 | 0.00 | -13.3 | |
| Maximum of Months | 0.142517E+10 | 2154.45 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: T S2 APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.142503E+10 | 1809.51 | 02-JAN-00:30 | -10.8 |
| February | 0.116008E+10 | 2153.43 | 06-FEB-05:00 | -13.3 |
| March | 0.482208E+09 | 1265.59 | 22-MAR-06:00 | -2.8 |
| April | 0.161096E+09 | 728.35 | 02-APR-04:00 | 3.90 |
| May | 386792.81 | 99.76 | 01-MAY-05:00 | 6.10 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 |
| October | 12842541.04 | 285.79 | 08-OCT-06:00 | 4.40 |
| November | 0.452465E+09 | 1400.16 | 23-NOV-02:00 | -2.8 |
| December | 0.102092E+10 | 1539.77 | 31-DEC-24:00 | -8.3 |
| Annual Sum or Average | 0.471502E+10 | |||
| Minimum of Months | 0.00 | 0.00 | -13.3 | |
| Maximum of Months | 0.142503E+10 | 2153.43 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: T CORRIDOR
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | -9.6 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | -1.1 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 5.52 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 5.27 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 10.33 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 10.40 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 5.97 |
| Annual Sum or Average | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | -9.6 | |
| Maximum of Months | 0.00 | 0.00 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: G CORRIDOR
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | -9.6 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | -1.1 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 5.52 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 5.27 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 10.33 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 10.40 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 5.97 |
| Annual Sum or Average | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | -9.6 | |
| Maximum of Months | 0.00 | 0.00 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: M CORRIDOR
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | -9.6 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | -1.1 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 5.52 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 5.27 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 10.33 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 10.40 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 5.97 |
| Annual Sum or Average | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | -9.6 | |
| Maximum of Months | 0.00 | 0.00 | 23.90 |
Report: ZoneElectricSummaryMonthly
For: G SW APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: G NW APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: OFFICE
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.609777E+09 | 582.92 | 03-JAN-08:09 | 0.787690E+09 | 588.62 | 03-JAN-08:09 |
| February | 0.564682E+09 | 582.92 | 01-FEB-08:09 | 0.723971E+09 | 588.62 | 01-FEB-08:09 |
| March | 0.654405E+09 | 582.92 | 01-MAR-08:09 | 0.827804E+09 | 588.62 | 01-MAR-08:09 |
| April | 0.599704E+09 | 582.92 | 03-APR-07:10 | 0.770907E+09 | 588.62 | 03-APR-07:10 |
| May | 0.639529E+09 | 582.92 | 01-MAY-07:10 | 0.814432E+09 | 588.62 | 01-MAY-07:10 |
| June | 0.629456E+09 | 582.92 | 01-JUN-07:10 | 0.797650E+09 | 588.62 | 01-JUN-07:10 |
| July | 0.609777E+09 | 582.92 | 03-JUL-07:10 | 0.787690E+09 | 588.62 | 03-JUL-07:10 |
| August | 0.654405E+09 | 582.92 | 01-AUG-07:10 | 0.827804E+09 | 588.62 | 01-AUG-07:10 |
| September | 0.599704E+09 | 582.92 | 01-SEP-07:10 | 0.770907E+09 | 588.62 | 01-SEP-07:10 |
| October | 0.624653E+09 | 582.92 | 02-OCT-07:10 | 0.801061E+09 | 588.62 | 02-OCT-07:10 |
| November | 0.599704E+09 | 582.92 | 01-NOV-07:10 | 0.770907E+09 | 588.62 | 01-NOV-07:10 |
| December | 0.609777E+09 | 582.92 | 01-DEC-08:09 | 0.787690E+09 | 588.62 | 01-DEC-08:09 |
| Annual Sum or Average | 0.739557E+10 | 0.946851E+10 | ||||
| Minimum of Months | 0.564682E+09 | 582.92 | 0.723971E+09 | 588.62 | ||
| Maximum of Months | 0.654405E+09 | 582.92 | 0.827804E+09 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: G NE APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: G N1 APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: G N2 APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: G S1 APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: G S2 APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: M SW APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: M NW APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: M SE APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: M NE APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: M N1 APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: M N2 APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: M S1 APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: M S2 APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: T SW APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: T NW APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: T SE APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: T NE APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: T N1 APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: T N2 APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: T S1 APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: T S2 APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: T CORRIDOR
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
| January | 0.992689E+09 | 370.63 | 01-JAN-00:10 | 0.00 | 0.00 |
| February | 0.896622E+09 | 370.63 | 01-FEB-00:10 | 0.00 | 0.00 |
| March | 0.992689E+09 | 370.63 | 01-MAR-00:10 | 0.00 | 0.00 |
| April | 0.960667E+09 | 370.63 | 01-APR-00:10 | 0.00 | 0.00 |
| May | 0.992689E+09 | 370.63 | 01-MAY-00:10 | 0.00 | 0.00 |
| June | 0.960667E+09 | 370.63 | 01-JUN-00:10 | 0.00 | 0.00 |
| July | 0.992689E+09 | 370.63 | 01-JUL-00:10 | 0.00 | 0.00 |
| August | 0.992689E+09 | 370.63 | 01-AUG-00:10 | 0.00 | 0.00 |
| September | 0.960667E+09 | 370.63 | 01-SEP-00:10 | 0.00 | 0.00 |
| October | 0.992689E+09 | 370.63 | 01-OCT-00:10 | 0.00 | 0.00 |
| November | 0.960667E+09 | 370.63 | 01-NOV-00:10 | 0.00 | 0.00 |
| December | 0.992689E+09 | 370.63 | 01-DEC-00:10 | 0.00 | 0.00 |
| Annual Sum or Average | 0.116881E+11 | 0.00 | 0.00 | ||
| Minimum of Months | 0.896622E+09 | 370.63 | 0.00 | 0.00 | |
| Maximum of Months | 0.992689E+09 | 370.63 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: G CORRIDOR
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.992689E+09 | 370.63 | 01-JAN-00:10 | 0.599555E+10 | 4168.07 | 01-JAN-07:10 |
| February | 0.896622E+09 | 370.63 | 01-FEB-00:10 | 0.541534E+10 | 4168.07 | 01-FEB-07:10 |
| March | 0.992689E+09 | 370.63 | 01-MAR-00:10 | 0.599555E+10 | 4168.07 | 01-MAR-07:10 |
| April | 0.960667E+09 | 370.63 | 01-APR-00:10 | 0.580215E+10 | 4168.07 | 01-APR-06:10 |
| May | 0.992689E+09 | 370.63 | 01-MAY-00:10 | 0.599555E+10 | 4168.07 | 01-MAY-06:10 |
| June | 0.960667E+09 | 370.63 | 01-JUN-00:10 | 0.580215E+10 | 4168.07 | 01-JUN-06:10 |
| July | 0.992689E+09 | 370.63 | 01-JUL-00:10 | 0.599555E+10 | 4168.07 | 01-JUL-06:10 |
| August | 0.992689E+09 | 370.63 | 01-AUG-00:10 | 0.599555E+10 | 4168.07 | 01-AUG-06:10 |
| September | 0.960667E+09 | 370.63 | 01-SEP-00:10 | 0.580215E+10 | 4168.07 | 01-SEP-06:10 |
| October | 0.992689E+09 | 370.63 | 01-OCT-00:10 | 0.599555E+10 | 4168.07 | 01-OCT-06:10 |
| November | 0.960667E+09 | 370.63 | 01-NOV-00:10 | 0.580215E+10 | 4168.07 | 01-NOV-06:10 |
| December | 0.992689E+09 | 370.63 | 01-DEC-00:10 | 0.599555E+10 | 4168.07 | 01-DEC-07:10 |
| Annual Sum or Average | 0.116881E+11 | 0.705928E+11 | ||||
| Minimum of Months | 0.896622E+09 | 370.63 | 0.541534E+10 | 4168.07 | ||
| Maximum of Months | 0.992689E+09 | 370.63 | 0.599555E+10 | 4168.07 |
Report: ZoneElectricSummaryMonthly
For: M CORRIDOR
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
| January | 0.992689E+09 | 370.63 | 01-JAN-00:10 | 0.00 | 0.00 |
| February | 0.896622E+09 | 370.63 | 01-FEB-00:10 | 0.00 | 0.00 |
| March | 0.992689E+09 | 370.63 | 01-MAR-00:10 | 0.00 | 0.00 |
| April | 0.960667E+09 | 370.63 | 01-APR-00:10 | 0.00 | 0.00 |
| May | 0.992689E+09 | 370.63 | 01-MAY-00:10 | 0.00 | 0.00 |
| June | 0.960667E+09 | 370.63 | 01-JUN-00:10 | 0.00 | 0.00 |
| July | 0.992689E+09 | 370.63 | 01-JUL-00:10 | 0.00 | 0.00 |
| August | 0.992689E+09 | 370.63 | 01-AUG-00:10 | 0.00 | 0.00 |
| September | 0.960667E+09 | 370.63 | 01-SEP-00:10 | 0.00 | 0.00 |
| October | 0.992689E+09 | 370.63 | 01-OCT-00:10 | 0.00 | 0.00 |
| November | 0.960667E+09 | 370.63 | 01-NOV-00:10 | 0.00 | 0.00 |
| December | 0.992689E+09 | 370.63 | 01-DEC-00:10 | 0.00 | 0.00 |
| Annual Sum or Average | 0.116881E+11 | 0.00 | 0.00 | ||
| Minimum of Months | 0.896622E+09 | 370.63 | 0.00 | 0.00 | |
| Maximum of Months | 0.992689E+09 | 370.63 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: G SW APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.715746E+09 |
| February | 0.389025E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.636290E+09 |
| March | 0.418950E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.534939E+09 |
| April | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 608890.51 | 0.317761E+09 |
| May | 0.424935E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2887622.00 | 0.170135E+09 |
| June | 0.406980E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20500122.57 | 76404638.88 |
| July | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 44845614.19 | 11689966.92 |
| August | 0.418950E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 53219403.92 | 22265811.77 |
| September | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7609680.67 | 87725474.78 |
| October | 0.430920E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 114712.35 | 0.277465E+09 |
| November | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.486035E+09 |
| December | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.623082E+09 |
| Annual Sum or Average | 0.505732E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129786E+09 | 0.395954E+10 |
| Minimum of Months | 0.389025E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11689966.92 |
| Maximum of Months | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 53219403.92 | 0.715746E+09 |
Report: SpaceGainsMonthly
For: G NW APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.715576E+09 |
| February | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.636121E+09 |
| March | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.531337E+09 |
| April | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 900969.24 | 0.306849E+09 |
| May | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2890617.80 | 0.163720E+09 |
| June | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20500124.54 | 76308598.78 |
| July | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 44845622.45 | 11689955.69 |
| August | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 53219403.72 | 22261139.88 |
| September | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7609680.68 | 86964158.97 |
| October | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 114713.43 | 0.262545E+09 |
| November | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.466379E+09 |
| December | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.621847E+09 |
| Annual Sum or Average | 0.512427E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130081E+09 | 0.390160E+10 |
| Minimum of Months | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11689955.69 |
| Maximum of Months | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 53219403.72 | 0.715576E+09 |
Report: SpaceGainsMonthly
For: OFFICE
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.227408E+09 | 0.609777E+09 | 0.787690E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.604722E+09 |
| February | 0.216037E+09 | 0.564682E+09 | 0.723971E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.552952E+09 |
| March | 0.261519E+09 | 0.654405E+09 | 0.827804E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.485872E+09 |
| April | 0.227408E+09 | 0.599704E+09 | 0.770907E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 470689.75 | 0.313319E+09 |
| May | 0.250148E+09 | 0.639529E+09 | 0.814432E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1598598.93 | 0.200034E+09 |
| June | 0.250148E+09 | 0.629456E+09 | 0.797650E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12933324.70 | 0.125621E+09 |
| July | 0.227408E+09 | 0.609777E+09 | 0.787690E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 23202818.83 | 63264388.80 |
| August | 0.261519E+09 | 0.654405E+09 | 0.827804E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 30916280.10 | 72699067.24 |
| September | 0.227408E+09 | 0.599704E+09 | 0.770907E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5210850.64 | 0.136658E+09 |
| October | 0.238778E+09 | 0.624653E+09 | 0.801061E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 114595.50 | 0.311013E+09 |
| November | 0.227408E+09 | 0.599704E+09 | 0.770907E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.472444E+09 |
| December | 0.227408E+09 | 0.609777E+09 | 0.787690E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.552052E+09 |
| Annual Sum or Average | 0.284259E+10 | 0.739557E+10 | 0.946851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 74447158.44 | 0.389065E+10 |
| Minimum of Months | 0.216037E+09 | 0.564682E+09 | 0.723971E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63264388.80 |
| Maximum of Months | 0.261519E+09 | 0.654405E+09 | 0.827804E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 30916280.10 | 0.604722E+09 |
Report: SpaceGainsMonthly
For: G NE APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.715576E+09 |
| February | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.636121E+09 |
| March | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1998.98 | 0.531115E+09 |
| April | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 794157.97 | 0.306831E+09 |
| May | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2887627.52 | 0.164190E+09 |
| June | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20500134.76 | 76385703.81 |
| July | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 44845646.99 | 11689937.94 |
| August | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 53219429.91 | 22260175.18 |
| September | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7609685.81 | 87134311.62 |
| October | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 114713.91 | 0.262549E+09 |
| November | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.467359E+09 |
| December | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.621847E+09 |
| Annual Sum or Average | 0.512427E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129973E+09 | 0.390306E+10 |
| Minimum of Months | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11689937.94 |
| Maximum of Months | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 53219429.91 | 0.715576E+09 |
Report: SpaceGainsMonthly
For: G N1 APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.431617E+09 |
| February | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.383692E+09 |
| March | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 549.76 | 0.320465E+09 |
| April | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 608945.94 | 0.185542E+09 |
| May | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1741745.74 | 0.101736E+09 |
| June | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12365167.20 | 46229184.81 |
| July | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27049764.58 | 7051067.25 |
| August | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32100620.98 | 13429355.98 |
| September | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4589972.76 | 52873264.24 |
| October | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 69192.76 | 0.161695E+09 |
| November | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.284433E+09 |
| December | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.375082E+09 |
| Annual Sum or Average | 0.512427E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 78525959.72 | 0.236385E+10 |
| Minimum of Months | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7051067.25 |
| Maximum of Months | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32100620.98 | 0.431617E+09 |
Report: SpaceGainsMonthly
For: G N2 APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.431617E+09 |
| February | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.383692E+09 |
| March | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 614.22 | 0.320457E+09 |
| April | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 600778.41 | 0.185577E+09 |
| May | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1741745.70 | 0.101720E+09 |
| June | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12365167.26 | 46231373.00 |
| July | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27049764.67 | 7051067.00 |
| August | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32100621.11 | 13429288.60 |
| September | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4589972.78 | 52876117.85 |
| October | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 69192.76 | 0.161684E+09 |
| November | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.284534E+09 |
| December | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.375082E+09 |
| Annual Sum or Average | 0.512427E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 78517856.91 | 0.236395E+10 |
| Minimum of Months | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7051067.00 |
| Maximum of Months | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32100621.11 | 0.431617E+09 |
Report: SpaceGainsMonthly
For: G S1 APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.431880E+09 |
| February | 0.389025E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.384009E+09 |
| March | 0.418950E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.323557E+09 |
| April | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 366830.65 | 0.194593E+09 |
| May | 0.424935E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1741742.72 | 0.107164E+09 |
| June | 0.406980E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12365163.34 | 46260455.51 |
| July | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27049758.27 | 7051075.22 |
| August | 0.418950E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32100616.55 | 13430785.88 |
| September | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4589971.33 | 53033007.76 |
| October | 0.430920E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 69192.18 | 0.169335E+09 |
| November | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.299321E+09 |
| December | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.376966E+09 |
| Annual Sum or Average | 0.505732E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 78283275.04 | 0.240660E+10 |
| Minimum of Months | 0.389025E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7051075.22 |
| Maximum of Months | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32100616.55 | 0.431880E+09 |
Report: SpaceGainsMonthly
For: G S2 APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.431809E+09 |
| February | 0.389025E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.383914E+09 |
| March | 0.418950E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.323280E+09 |
| April | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 366830.28 | 0.194907E+09 |
| May | 0.424935E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1741742.47 | 0.108380E+09 |
| June | 0.406980E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12365164.68 | 46287015.28 |
| July | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27049758.88 | 7051083.13 |
| August | 0.418950E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32100617.86 | 13430891.04 |
| September | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4589971.60 | 53047237.22 |
| October | 0.430920E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 69192.17 | 0.169510E+09 |
| November | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.299738E+09 |
| December | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.376690E+09 |
| Annual Sum or Average | 0.505732E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 78283277.93 | 0.240804E+10 |
| Minimum of Months | 0.389025E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7051083.13 |
| Maximum of Months | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32100617.86 | 0.431809E+09 |
Report: SpaceGainsMonthly
For: M SW APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103146E+10 |
| February | 0.389025E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.919375E+09 |
| March | 0.418950E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.790906E+09 |
| April | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 863283.38 | 0.489955E+09 |
| May | 0.424935E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4116126.60 | 0.284709E+09 |
| June | 0.406980E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29264019.63 | 0.110891E+09 |
| July | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 64005686.04 | 17024686.46 |
| August | 0.418950E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 76036295.19 | 32240085.50 |
| September | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10832488.03 | 0.126564E+09 |
| October | 0.430920E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 157350.45 | 0.395653E+09 |
| November | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.699130E+09 |
| December | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.900783E+09 |
| Annual Sum or Average | 0.505732E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.185275E+09 | 0.579869E+10 |
| Minimum of Months | 0.389025E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17024686.46 |
| Maximum of Months | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 76036295.19 | 0.103146E+10 |
Report: SpaceGainsMonthly
For: M NW APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102936E+10 |
| February | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.914985E+09 |
| March | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.770728E+09 |
| April | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 863290.16 | 0.473389E+09 |
| May | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4116130.64 | 0.282672E+09 |
| June | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29264012.94 | 0.110882E+09 |
| July | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 64005685.62 | 17024677.27 |
| August | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 76036287.19 | 32228802.88 |
| September | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10832485.27 | 0.125748E+09 |
| October | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 157351.76 | 0.372567E+09 |
| November | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.672414E+09 |
| December | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.894636E+09 |
| Annual Sum or Average | 0.512427E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.185275E+09 | 0.569663E+10 |
| Minimum of Months | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17024677.27 |
| Maximum of Months | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 76036287.19 | 0.102936E+10 |
Report: SpaceGainsMonthly
For: M SE APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103143E+10 |
| February | 0.389025E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.919121E+09 |
| March | 0.418950E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.789407E+09 |
| April | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 863286.19 | 0.491566E+09 |
| May | 0.424935E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4116131.18 | 0.285271E+09 |
| June | 0.406980E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29264039.93 | 0.110895E+09 |
| July | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 64005732.96 | 17024658.17 |
| August | 0.418950E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 76036345.58 | 32239960.90 |
| September | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10832489.56 | 0.126579E+09 |
| October | 0.430920E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 157351.67 | 0.396170E+09 |
| November | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.701833E+09 |
| December | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.901069E+09 |
| Annual Sum or Average | 0.505732E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.185275E+09 | 0.580260E+10 |
| Minimum of Months | 0.389025E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17024658.17 |
| Maximum of Months | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 76036345.58 | 0.103143E+10 |
Report: SpaceGainsMonthly
For: M NE APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102935E+10 |
| February | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.914977E+09 |
| March | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.769384E+09 |
| April | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 863289.45 | 0.475238E+09 |
| May | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4116133.92 | 0.283569E+09 |
| June | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29264027.88 | 0.110885E+09 |
| July | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 64005734.11 | 17024647.29 |
| August | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 76036335.58 | 32230108.47 |
| September | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10832494.60 | 0.125958E+09 |
| October | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 157352.74 | 0.372936E+09 |
| November | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.673893E+09 |
| December | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.894635E+09 |
| Annual Sum or Average | 0.512427E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.185275E+09 | 0.570008E+10 |
| Minimum of Months | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17024647.29 |
| Maximum of Months | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 76036335.58 | 0.102935E+10 |
Report: SpaceGainsMonthly
For: M N1 APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.620886E+09 |
| February | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.551891E+09 |
| March | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.465346E+09 |
| April | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 520717.58 | 0.289077E+09 |
| May | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2482749.92 | 0.173149E+09 |
| June | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17651329.99 | 66902520.45 |
| July | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 38606643.92 | 10268819.22 |
| August | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 45863203.80 | 19443232.04 |
| September | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6533891.28 | 76387095.79 |
| October | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 94911.62 | 0.231512E+09 |
| November | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.411721E+09 |
| December | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.539623E+09 |
| Annual Sum or Average | 0.512427E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111753E+09 | 0.345620E+10 |
| Minimum of Months | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10268819.22 |
| Maximum of Months | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 45863203.80 | 0.620886E+09 |
Report: SpaceGainsMonthly
For: M N2 APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.620886E+09 |
| February | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.551891E+09 |
| March | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.465285E+09 |
| April | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 520717.38 | 0.289204E+09 |
| May | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2482749.97 | 0.173192E+09 |
| June | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17651328.90 | 66902809.33 |
| July | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 38606644.37 | 10268818.73 |
| August | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 45863204.44 | 19443113.40 |
| September | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6533891.38 | 76389081.66 |
| October | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 94911.62 | 0.231523E+09 |
| November | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.411877E+09 |
| December | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.539623E+09 |
| Annual Sum or Average | 0.512427E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111753E+09 | 0.345649E+10 |
| Minimum of Months | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10268818.73 |
| Maximum of Months | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 45863204.44 | 0.620886E+09 |
Report: SpaceGainsMonthly
For: M S1 APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.624192E+09 |
| February | 0.389025E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.556892E+09 |
| March | 0.418950E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.484437E+09 |
| April | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 520713.16 | 0.302067E+09 |
| May | 0.424935E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2482746.97 | 0.174178E+09 |
| June | 0.406980E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17651330.16 | 66903611.11 |
| July | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 38606638.86 | 10268827.68 |
| August | 0.418950E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 45863200.85 | 19447378.55 |
| September | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6533890.37 | 76545994.55 |
| October | 0.430920E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 94911.40 | 0.242924E+09 |
| November | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.432792E+09 |
| December | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.548163E+09 |
| Annual Sum or Average | 0.505732E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111753E+09 | 0.353881E+10 |
| Minimum of Months | 0.389025E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10268827.68 |
| Maximum of Months | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 45863200.85 | 0.624192E+09 |
Report: SpaceGainsMonthly
For: M S2 APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.624196E+09 |
| February | 0.389025E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.556911E+09 |
| March | 0.418950E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.484346E+09 |
| April | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 520713.15 | 0.302127E+09 |
| May | 0.424935E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2482747.03 | 0.174188E+09 |
| June | 0.406980E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17651330.43 | 66903846.38 |
| July | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 38606639.37 | 10268827.18 |
| August | 0.418950E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 45863204.06 | 19447357.69 |
| September | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6533890.52 | 76546299.99 |
| October | 0.430920E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 94911.43 | 0.242919E+09 |
| November | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.432943E+09 |
| December | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.548215E+09 |
| Annual Sum or Average | 0.505732E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111753E+09 | 0.353901E+10 |
| Minimum of Months | 0.389025E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10268827.18 |
| Maximum of Months | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 45863204.06 | 0.624196E+09 |
Report: SpaceGainsMonthly
For: T SW APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136715E+10 |
| February | 0.389025E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121910E+10 |
| March | 0.418950E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104559E+10 |
| April | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1113674.58 | 0.628435E+09 |
| May | 0.424935E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5355888.11 | 0.342165E+09 |
| June | 0.406980E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 38195497.96 | 0.144569E+09 |
| July | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 83502037.44 | 23117826.83 |
| August | 0.418950E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 99408575.53 | 42783379.49 |
| September | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14057635.47 | 0.159263E+09 |
| October | 0.430920E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 189776.53 | 0.483721E+09 |
| November | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.901159E+09 |
| December | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119229E+10 |
| Annual Sum or Average | 0.505732E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.241823E+09 | 0.754935E+10 |
| Minimum of Months | 0.389025E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23117826.83 |
| Maximum of Months | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 99408575.53 | 0.136715E+10 |
Report: SpaceGainsMonthly
For: T NW APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136431E+10 |
| February | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121250E+10 |
| March | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102323E+10 |
| April | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1113674.03 | 0.613306E+09 |
| May | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5355887.90 | 0.339841E+09 |
| June | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 38195476.32 | 0.144814E+09 |
| July | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 83502014.63 | 23117822.43 |
| August | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 99408525.44 | 42627215.10 |
| September | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14057618.51 | 0.155262E+09 |
| October | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 189776.62 | 0.451134E+09 |
| November | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.883735E+09 |
| December | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118604E+10 |
| Annual Sum or Average | 0.512427E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.241823E+09 | 0.743993E+10 |
| Minimum of Months | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23117822.43 |
| Maximum of Months | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 99408525.44 | 0.136431E+10 |
Report: SpaceGainsMonthly
For: T SE APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136704E+10 |
| February | 0.389025E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121841E+10 |
| March | 0.418950E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104410E+10 |
| April | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1113679.60 | 0.631028E+09 |
| May | 0.424935E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5355897.03 | 0.345211E+09 |
| June | 0.406980E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 38195538.40 | 0.145106E+09 |
| July | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 83502134.79 | 23117781.39 |
| August | 0.418950E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 99408677.96 | 42805190.83 |
| September | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14057658.89 | 0.159943E+09 |
| October | 0.430920E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 189778.88 | 0.485629E+09 |
| November | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.903893E+09 |
| December | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119228E+10 |
| Annual Sum or Average | 0.505732E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.241823E+09 | 0.755857E+10 |
| Minimum of Months | 0.389025E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23117781.39 |
| Maximum of Months | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 99408677.96 | 0.136704E+10 |
Report: SpaceGainsMonthly
For: T NE APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136431E+10 |
| February | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121250E+10 |
| March | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102113E+10 |
| April | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1113676.35 | 0.615206E+09 |
| May | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5355895.99 | 0.343515E+09 |
| June | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 38195518.40 | 0.145255E+09 |
| July | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 83502107.89 | 23117779.08 |
| August | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 99408620.01 | 42667475.32 |
| September | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14057638.13 | 0.156731E+09 |
| October | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 189777.90 | 0.449688E+09 |
| November | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.883413E+09 |
| December | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118604E+10 |
| Annual Sum or Average | 0.512427E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.241823E+09 | 0.744358E+10 |
| Minimum of Months | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23117779.08 |
| Maximum of Months | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 99408620.01 | 0.136431E+10 |
Report: SpaceGainsMonthly
For: T N1 APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.822914E+09 |
| February | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.731351E+09 |
| March | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.616188E+09 |
| April | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 671742.95 | 0.370821E+09 |
| May | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3230536.04 | 0.211022E+09 |
| June | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23038562.12 | 88378694.10 |
| July | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 50366337.64 | 13944054.01 |
| August | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 59960747.40 | 25902174.59 |
| September | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8479211.63 | 96484596.87 |
| October | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 114469.60 | 0.275208E+09 |
| November | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.533736E+09 |
| December | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.715392E+09 |
| Annual Sum or Average | 0.512427E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.145862E+09 | 0.450134E+10 |
| Minimum of Months | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13944054.01 |
| Maximum of Months | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 59960747.40 | 0.822914E+09 |
Report: SpaceGainsMonthly
For: T N2 APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.822914E+09 |
| February | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.731351E+09 |
| March | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.616143E+09 |
| April | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 671742.97 | 0.371045E+09 |
| May | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3230541.00 | 0.211157E+09 |
| June | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23038563.30 | 88385899.75 |
| July | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 50366339.45 | 13944052.83 |
| August | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 59960749.26 | 25899160.04 |
| September | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8479212.02 | 96542848.48 |
| October | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 114469.61 | 0.275140E+09 |
| November | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.533758E+09 |
| December | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.715392E+09 |
| Annual Sum or Average | 0.512427E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.145862E+09 | 0.450167E+10 |
| Minimum of Months | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13944052.83 |
| Maximum of Months | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 59960749.26 | 0.822914E+09 |
Report: SpaceGainsMonthly
For: T S1 APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.825952E+09 |
| February | 0.389025E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.736937E+09 |
| March | 0.418950E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.633864E+09 |
| April | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 671743.37 | 0.383169E+09 |
| May | 0.424935E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3230539.91 | 0.213121E+09 |
| June | 0.406980E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23038573.32 | 88258083.43 |
| July | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 50366349.82 | 13944057.16 |
| August | 0.418950E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 59960774.90 | 25971329.65 |
| September | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8479219.60 | 98674651.95 |
| October | 0.430920E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 114469.81 | 0.299839E+09 |
| November | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.549552E+09 |
| December | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.722117E+09 |
| Annual Sum or Average | 0.505732E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.145862E+09 | 0.459140E+10 |
| Minimum of Months | 0.389025E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13944057.16 |
| Maximum of Months | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 59960774.90 | 0.825952E+09 |
Report: SpaceGainsMonthly
For: T S2 APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.825986E+09 |
| February | 0.389025E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.736963E+09 |
| March | 0.418950E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.633832E+09 |
| April | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 671743.32 | 0.383277E+09 |
| May | 0.424935E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3230540.19 | 0.213188E+09 |
| June | 0.406980E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23038574.38 | 88269240.60 |
| July | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 50366351.69 | 13944055.97 |
| August | 0.418950E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 59960777.23 | 25968550.56 |
| September | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8479220.34 | 98678283.55 |
| October | 0.430920E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 114469.86 | 0.299839E+09 |
| November | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.549741E+09 |
| December | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.722175E+09 |
| Annual Sum or Average | 0.505732E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.145862E+09 | 0.459186E+10 |
| Minimum of Months | 0.389025E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13944055.97 |
| Maximum of Months | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 59960777.23 | 0.825986E+09 |
Report: SpaceGainsMonthly
For: T CORRIDOR
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.727675E+09 | 0.992689E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.224562E+09 |
| February | 0.657255E+09 | 0.896622E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.201406E+09 |
| March | 0.727675E+09 | 0.992689E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.179746E+09 |
| April | 0.704201E+09 | 0.960667E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10867.33 | 0.113901E+09 |
| May | 0.727675E+09 | 0.992689E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 179824.18 | 71564594.32 |
| June | 0.704201E+09 | 0.960667E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2005135.90 | 39458167.30 |
| July | 0.727675E+09 | 0.992689E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3919793.93 | 12522970.99 |
| August | 0.727675E+09 | 0.992689E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6033836.11 | 15342190.23 |
| September | 0.704201E+09 | 0.960667E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 461147.29 | 38385602.57 |
| October | 0.727675E+09 | 0.992689E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92290072.04 |
| November | 0.704201E+09 | 0.960667E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.154276E+09 |
| December | 0.727675E+09 | 0.992689E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.197499E+09 |
| Annual Sum or Average | 0.856778E+10 | 0.116881E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12610604.74 | 0.134095E+10 |
| Minimum of Months | 0.657255E+09 | 0.896622E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12522970.99 |
| Maximum of Months | 0.727675E+09 | 0.992689E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6033836.11 | 0.224562E+09 |
Report: SpaceGainsMonthly
For: G CORRIDOR
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.727675E+09 | 0.992689E+09 | 0.299778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.410849E+10 |
| February | 0.657255E+09 | 0.896622E+09 | 0.270767E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.396291E+10 |
| March | 0.727675E+09 | 0.992689E+09 | 0.299778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 20732.50 | 0.322581E+10 |
| April | 0.704201E+09 | 0.960667E+09 | 0.290107E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6516249.08 | 0.216999E+10 |
| May | 0.727675E+09 | 0.992689E+09 | 0.299778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7720977.63 | 0.144980E+10 |
| June | 0.704201E+09 | 0.960667E+09 | 0.290107E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 61797114.54 | 0.769193E+09 |
| July | 0.727675E+09 | 0.992689E+09 | 0.299778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107323E+09 | 0.314803E+09 |
| August | 0.727675E+09 | 0.992689E+09 | 0.299778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.149667E+09 | 0.405548E+09 |
| September | 0.704201E+09 | 0.960667E+09 | 0.290107E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12184878.23 | 0.110887E+10 |
| October | 0.727675E+09 | 0.992689E+09 | 0.299778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.219181E+10 |
| November | 0.704201E+09 | 0.960667E+09 | 0.290107E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.300915E+10 |
| December | 0.727675E+09 | 0.992689E+09 | 0.299778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.372563E+10 |
| Annual Sum or Average | 0.856778E+10 | 0.116881E+11 | 0.352964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.345229E+09 | 0.264420E+11 |
| Minimum of Months | 0.657255E+09 | 0.896622E+09 | 0.270767E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.314803E+09 |
| Maximum of Months | 0.727675E+09 | 0.992689E+09 | 0.299778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.149667E+09 | 0.410849E+10 |
Report: SpaceGainsMonthly
For: M CORRIDOR
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.727675E+09 | 0.992689E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.183748E+09 |
| February | 0.657255E+09 | 0.896622E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.164194E+09 |
| March | 0.727675E+09 | 0.992689E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.145737E+09 |
| April | 0.704201E+09 | 0.960667E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39065.09 | 94263220.94 |
| May | 0.727675E+09 | 0.992689E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 202123.75 | 60203719.84 |
| June | 0.704201E+09 | 0.960667E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2057650.15 | 30229370.97 |
| July | 0.727675E+09 | 0.992689E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4145555.84 | 8829938.03 |
| August | 0.727675E+09 | 0.992689E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5828419.20 | 11591810.15 |
| September | 0.704201E+09 | 0.960667E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 521815.79 | 31067506.65 |
| October | 0.727675E+09 | 0.992689E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79448944.52 |
| November | 0.704201E+09 | 0.960667E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129577E+09 |
| December | 0.727675E+09 | 0.992689E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.162439E+09 |
| Annual Sum or Average | 0.856778E+10 | 0.116881E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12794629.82 | 0.110133E+10 |
| Minimum of Months | 0.657255E+09 | 0.896622E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8829938.03 |
| Maximum of Months | 0.727675E+09 | 0.992689E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5828419.20 | 0.183748E+09 |
Report: PeakSpaceGainsMonthly
For: G SW APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 789.54 | 31-JAN-01:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 821.63 | 06-FEB-01:00 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 731.68 | 22-MAR-07:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 35.66 | 07-APR-13:00 | 422.55 | 11-APR-04:00 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 66.33 | 30-MAY-13:00 | 217.89 | 03-MAY-04:00 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 136.49 | 19-JUN-12:00 | 143.57 | 02-JUN-22:00 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 132.51 | 10-JUL-14:00 | 52.45 | 11-JUL-05:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 189.56 | 24-AUG-17:00 | 91.39 | 20-AUG-06:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 93.01 | 14-SEP-14:00 | 133.99 | 30-SEP-24:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.33 | 25-OCT-11:00 | 393.57 | 08-OCT-08:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 641.62 | 23-NOV-02:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 850.67 | 31-DEC-22:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.45 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 189.56 | 850.67 |
Report: PeakSpaceGainsMonthly
For: G NW APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 789.54 | 31-JAN-01:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 821.63 | 06-FEB-01:00 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 731.68 | 22-MAR-07:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 48.89 | 07-APR-13:00 | 406.40 | 11-APR-04:00 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 66.33 | 30-MAY-13:00 | 217.79 | 03-MAY-04:00 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 136.49 | 19-JUN-12:00 | 143.57 | 02-JUN-22:00 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 132.51 | 10-JUL-14:00 | 52.45 | 11-JUL-05:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 189.56 | 24-AUG-17:00 | 89.80 | 20-AUG-06:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 93.01 | 14-SEP-14:00 | 130.84 | 23-SEP-04:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.33 | 25-OCT-11:00 | 374.66 | 08-OCT-08:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 641.62 | 23-NOV-02:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 850.67 | 31-DEC-22:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.45 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 189.56 | 850.67 |
Report: PeakSpaceGainsMonthly
For: OFFICE
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 451.21 | 03-JAN-08:09 | 582.92 | 03-JAN-08:09 | 588.62 | 03-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 657.44 | 11-JAN-13:00 |
| February | 451.21 | 01-FEB-08:09 | 582.92 | 01-FEB-08:09 | 588.62 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 690.27 | 06-FEB-01:00 |
| March | 451.21 | 01-MAR-08:09 | 582.92 | 01-MAR-08:09 | 588.62 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 691.00 | 22-MAR-07:03 |
| April | 451.21 | 03-APR-07:10 | 582.92 | 03-APR-07:10 | 588.62 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 35.66 | 07-APR-13:00 | 437.39 | 11-APR-04:00 |
| May | 451.21 | 01-MAY-07:10 | 582.92 | 01-MAY-07:10 | 588.62 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 66.33 | 30-MAY-13:00 | 272.20 | 03-MAY-10:00 |
| June | 451.21 | 01-JUN-07:10 | 582.92 | 01-JUN-07:10 | 588.62 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 136.48 | 19-JUN-12:00 | 183.19 | 02-JUN-18:30 |
| July | 451.21 | 03-JUL-07:10 | 582.92 | 03-JUL-07:10 | 588.62 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 132.51 | 10-JUL-14:00 | 101.86 | 02-JUL-19:00 |
| August | 451.21 | 01-AUG-07:10 | 582.92 | 01-AUG-07:10 | 588.62 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 180.77 | 24-AUG-15:00 | 128.65 | 20-AUG-06:00 |
| September | 451.21 | 01-SEP-07:10 | 582.92 | 01-SEP-07:10 | 588.62 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 93.00 | 14-SEP-14:00 | 163.55 | 17-SEP-10:00 |
| October | 451.21 | 02-OCT-07:10 | 582.92 | 02-OCT-07:10 | 588.62 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.33 | 25-OCT-11:00 | 411.18 | 08-OCT-08:00 |
| November | 451.21 | 01-NOV-07:10 | 582.92 | 01-NOV-07:10 | 588.62 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 549.31 | 23-NOV-02:00 |
| December | 451.21 | 01-DEC-08:09 | 582.92 | 01-DEC-08:09 | 588.62 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 683.35 | 31-DEC-22:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 451.21 | 582.92 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 101.86 | |||||
| Maximum of Months | 451.21 | 582.92 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 180.77 | 691.00 |
Report: PeakSpaceGainsMonthly
For: G NE APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 789.54 | 31-JAN-01:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 821.63 | 06-FEB-01:00 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 27-MAR-16:00 | 731.68 | 22-MAR-07:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 43.55 | 07-APR-13:00 | 406.40 | 11-APR-04:00 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 66.33 | 30-MAY-13:00 | 217.79 | 03-MAY-04:00 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 136.49 | 19-JUN-12:00 | 143.57 | 02-JUN-22:00 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 132.51 | 10-JUL-14:00 | 52.45 | 11-JUL-05:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 189.56 | 24-AUG-17:00 | 89.76 | 20-AUG-06:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 93.01 | 14-SEP-14:00 | 130.62 | 23-SEP-04:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.33 | 25-OCT-11:00 | 378.05 | 08-OCT-08:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 641.62 | 23-NOV-02:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 850.67 | 31-DEC-22:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.45 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 189.56 | 850.67 |
Report: PeakSpaceGainsMonthly
For: G N1 APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 476.23 | 31-JAN-01:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 495.59 | 06-FEB-01:00 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.92 | 27-MAR-16:00 | 441.33 | 22-MAR-07:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 30.21 | 07-APR-13:00 | 247.78 | 11-APR-04:00 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 40.01 | 30-MAY-13:00 | 132.99 | 03-MAY-10:00 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 82.33 | 19-JUN-12:00 | 86.60 | 02-JUN-22:00 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 79.93 | 10-JUL-14:00 | 31.64 | 11-JUL-05:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 114.34 | 24-AUG-17:00 | 54.59 | 20-AUG-06:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 56.10 | 14-SEP-14:00 | 80.28 | 23-SEP-04:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.85 | 25-OCT-11:00 | 235.41 | 08-OCT-08:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 387.01 | 23-NOV-02:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 513.10 | 31-DEC-22:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.64 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 114.34 | 513.10 |
Report: PeakSpaceGainsMonthly
For: G N2 APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 476.23 | 31-JAN-01:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 495.59 | 06-FEB-01:00 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.02 | 27-MAR-16:00 | 441.33 | 22-MAR-07:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 29.94 | 07-APR-13:00 | 247.75 | 11-APR-04:00 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 40.01 | 30-MAY-13:00 | 133.06 | 03-MAY-10:00 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 82.33 | 19-JUN-12:00 | 86.60 | 02-JUN-22:00 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 79.93 | 10-JUL-14:00 | 31.64 | 11-JUL-05:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 114.34 | 24-AUG-17:00 | 54.57 | 20-AUG-06:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 56.10 | 14-SEP-14:00 | 80.28 | 23-SEP-04:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.85 | 25-OCT-11:00 | 235.38 | 08-OCT-08:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 387.01 | 23-NOV-02:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 513.10 | 31-DEC-22:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.64 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 114.34 | 513.10 |
Report: PeakSpaceGainsMonthly
For: G S1 APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 476.23 | 31-JAN-01:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 495.59 | 06-FEB-01:00 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 441.33 | 22-MAR-07:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.51 | 07-APR-13:00 | 266.57 | 11-APR-04:00 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 40.01 | 30-MAY-13:00 | 140.72 | 03-MAY-10:00 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 82.33 | 19-JUN-12:00 | 86.60 | 02-JUN-22:00 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 79.93 | 10-JUL-14:00 | 31.64 | 11-JUL-05:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 114.34 | 24-AUG-17:00 | 55.13 | 20-AUG-06:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 56.10 | 14-SEP-14:00 | 80.82 | 30-SEP-24:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.85 | 25-OCT-11:00 | 247.16 | 08-OCT-08:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 387.01 | 23-NOV-02:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 513.10 | 31-DEC-22:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.64 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 114.34 | 513.10 |
Report: PeakSpaceGainsMonthly
For: G S2 APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 476.23 | 31-JAN-01:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 495.59 | 06-FEB-01:00 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 441.33 | 22-MAR-07:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.51 | 07-APR-13:00 | 267.45 | 11-APR-04:00 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 40.01 | 30-MAY-13:00 | 142.78 | 03-MAY-10:00 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 82.33 | 19-JUN-12:00 | 86.60 | 02-JUN-22:00 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 79.93 | 10-JUL-14:00 | 31.64 | 11-JUL-05:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 114.34 | 24-AUG-17:00 | 55.13 | 20-AUG-06:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 56.10 | 14-SEP-14:00 | 80.82 | 30-SEP-24:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.85 | 25-OCT-11:00 | 248.16 | 08-OCT-08:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 387.01 | 23-NOV-02:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 513.10 | 31-DEC-22:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.64 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 114.34 | 513.10 |
Report: PeakSpaceGainsMonthly
For: M SW APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 1135.49 | 31-JAN-01:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1181.44 | 06-FEB-01:00 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1052.36 | 22-MAR-07:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 50.87 | 07-APR-13:00 | 637.58 | 11-APR-04:00 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 95.01 | 30-MAY-13:00 | 396.73 | 03-MAY-10:00 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 195.84 | 19-JUN-12:00 | 206.81 | 02-JUN-22:00 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 190.00 | 10-JUL-14:00 | 75.71 | 11-JUL-05:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 271.84 | 24-AUG-17:00 | 131.04 | 20-AUG-06:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 133.27 | 14-SEP-14:00 | 192.89 | 30-SEP-24:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.01 | 25-OCT-11:00 | 549.82 | 08-OCT-08:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 922.83 | 23-NOV-02:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1223.34 | 31-DEC-22:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.71 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 271.84 | 1223.34 |
Report: PeakSpaceGainsMonthly
For: M NW APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 1135.49 | 31-JAN-01:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1181.44 | 06-FEB-01:00 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1052.36 | 22-MAR-07:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 50.87 | 07-APR-13:00 | 624.84 | 11-APR-04:00 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 95.01 | 30-MAY-13:00 | 386.66 | 03-MAY-10:00 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 195.84 | 19-JUN-12:00 | 206.81 | 02-JUN-22:00 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 190.00 | 10-JUL-14:00 | 75.71 | 11-JUL-05:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 271.84 | 24-AUG-17:00 | 127.77 | 20-AUG-06:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 133.27 | 14-SEP-14:00 | 188.59 | 30-SEP-24:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.01 | 25-OCT-11:00 | 520.02 | 08-OCT-08:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 922.83 | 23-NOV-02:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1223.34 | 31-DEC-22:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.71 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 271.84 | 1223.34 |
Report: PeakSpaceGainsMonthly
For: M SE APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 1135.49 | 31-JAN-01:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1181.44 | 06-FEB-01:00 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1052.36 | 22-MAR-07:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 50.87 | 07-APR-13:00 | 632.68 | 11-APR-04:00 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 95.01 | 30-MAY-13:00 | 396.88 | 03-MAY-10:00 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 195.84 | 19-JUN-12:00 | 206.81 | 02-JUN-22:00 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 190.00 | 10-JUL-14:00 | 75.71 | 11-JUL-05:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 271.84 | 24-AUG-17:00 | 131.47 | 20-AUG-06:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 133.27 | 14-SEP-14:00 | 192.89 | 30-SEP-24:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.01 | 25-OCT-11:00 | 558.84 | 08-OCT-08:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 922.83 | 23-NOV-02:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1223.34 | 31-DEC-22:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.71 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 271.84 | 1223.34 |
Report: PeakSpaceGainsMonthly
For: M NE APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 1135.49 | 31-JAN-01:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1181.44 | 06-FEB-01:00 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1052.36 | 22-MAR-07:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 50.87 | 07-APR-13:00 | 619.21 | 11-APR-04:00 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 95.01 | 30-MAY-13:00 | 387.86 | 03-MAY-10:00 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 195.84 | 19-JUN-12:00 | 206.81 | 02-JUN-22:00 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 190.00 | 10-JUL-14:00 | 75.71 | 11-JUL-05:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 271.84 | 24-AUG-17:00 | 128.15 | 20-AUG-06:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 133.27 | 14-SEP-14:00 | 187.09 | 23-SEP-04:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.01 | 25-OCT-11:00 | 528.62 | 08-OCT-08:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 922.83 | 23-NOV-02:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1223.34 | 31-DEC-22:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.71 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 271.84 | 1223.34 |
Report: PeakSpaceGainsMonthly
For: M N1 APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 684.90 | 31-JAN-01:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 712.61 | 06-FEB-01:00 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 634.76 | 22-MAR-07:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 30.68 | 07-APR-13:00 | 390.93 | 11-APR-04:00 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 57.31 | 30-MAY-13:00 | 244.89 | 03-MAY-10:00 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 118.12 | 19-JUN-12:00 | 124.74 | 02-JUN-22:00 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 114.60 | 10-JUL-14:00 | 45.66 | 11-JUL-05:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 163.97 | 24-AUG-17:00 | 77.85 | 20-AUG-06:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 80.38 | 14-SEP-14:00 | 115.61 | 23-SEP-04:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.88 | 25-OCT-11:00 | 333.06 | 08-OCT-08:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 556.63 | 23-NOV-02:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 737.89 | 31-DEC-22:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.66 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 163.97 | 737.89 |
Report: PeakSpaceGainsMonthly
For: M N2 APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 684.90 | 31-JAN-01:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 712.61 | 06-FEB-01:00 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 634.76 | 22-MAR-07:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 30.68 | 07-APR-13:00 | 390.64 | 11-APR-04:00 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 57.31 | 30-MAY-13:00 | 245.18 | 03-MAY-10:00 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 118.12 | 19-JUN-12:00 | 124.74 | 02-JUN-22:00 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 114.60 | 10-JUL-14:00 | 45.66 | 11-JUL-05:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 163.97 | 24-AUG-17:00 | 77.83 | 20-AUG-06:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 80.38 | 14-SEP-14:00 | 115.61 | 23-SEP-04:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.88 | 25-OCT-11:00 | 333.05 | 08-OCT-08:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 556.63 | 23-NOV-02:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 737.89 | 31-DEC-22:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.66 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 163.97 | 737.89 |
Report: PeakSpaceGainsMonthly
For: M S1 APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 684.90 | 31-JAN-01:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 712.61 | 06-FEB-01:00 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 634.76 | 22-MAR-07:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 30.68 | 07-APR-13:00 | 398.95 | 11-APR-04:00 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 57.31 | 30-MAY-13:00 | 251.54 | 03-MAY-10:00 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 118.12 | 19-JUN-12:00 | 124.74 | 02-JUN-22:00 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 114.60 | 10-JUL-14:00 | 45.66 | 11-JUL-05:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 163.97 | 24-AUG-17:00 | 79.42 | 20-AUG-06:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 80.38 | 14-SEP-14:00 | 116.34 | 30-SEP-24:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.88 | 25-OCT-11:00 | 350.63 | 08-OCT-08:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 556.63 | 23-NOV-02:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 737.89 | 31-DEC-22:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.66 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 163.97 | 737.89 |
Report: PeakSpaceGainsMonthly
For: M S2 APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 684.90 | 31-JAN-01:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 712.61 | 06-FEB-01:00 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 634.76 | 22-MAR-07:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 30.68 | 07-APR-13:00 | 398.72 | 11-APR-04:00 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 57.31 | 30-MAY-13:00 | 251.63 | 03-MAY-10:00 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 118.12 | 19-JUN-12:00 | 124.74 | 02-JUN-22:00 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 114.60 | 10-JUL-14:00 | 45.66 | 11-JUL-05:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 163.97 | 24-AUG-17:00 | 79.42 | 20-AUG-06:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 80.38 | 14-SEP-14:00 | 116.34 | 30-SEP-24:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.88 | 25-OCT-11:00 | 350.67 | 08-OCT-08:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 556.63 | 23-NOV-02:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 737.89 | 31-DEC-22:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.66 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 163.97 | 737.89 |
Report: PeakSpaceGainsMonthly
For: T SW APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 1504.31 | 31-JAN-01:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1564.62 | 06-FEB-01:00 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1394.37 | 22-MAR-07:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 66.29 | 07-APR-13:00 | 775.61 | 11-APR-04:00 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 124.84 | 30-MAY-13:00 | 419.93 | 03-MAY-10:00 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 258.24 | 19-JUN-12:00 | 274.86 | 02-JUN-22:00 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 250.20 | 10-JUL-14:00 | 101.00 | 11-JUL-05:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 358.05 | 24-AUG-17:00 | 147.78 | 20-AUG-06:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 175.22 | 14-SEP-14:00 | 234.51 | 30-SEP-24:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 29.20 | 25-OCT-11:00 | 685.10 | 08-OCT-08:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1222.74 | 23-NOV-02:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1620.50 | 31-DEC-22:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 101.00 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 358.05 | 1620.50 |
Report: PeakSpaceGainsMonthly
For: T NW APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 1504.31 | 31-JAN-01:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1564.62 | 06-FEB-01:00 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1394.37 | 22-MAR-07:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 66.29 | 07-APR-13:00 | 775.61 | 11-APR-04:00 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 124.84 | 30-MAY-13:00 | 416.76 | 03-MAY-04:00 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 258.24 | 19-JUN-12:00 | 274.86 | 02-JUN-22:00 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 250.20 | 10-JUL-14:00 | 101.00 | 11-JUL-05:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 358.05 | 24-AUG-17:00 | 143.17 | 20-AUG-06:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 175.22 | 14-SEP-14:00 | 220.40 | 30-SEP-24:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 29.20 | 25-OCT-11:00 | 685.10 | 08-OCT-08:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1222.74 | 23-NOV-02:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1620.50 | 31-DEC-22:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 101.00 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 358.05 | 1620.50 |
Report: PeakSpaceGainsMonthly
For: T SE APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 1504.31 | 31-JAN-01:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1564.62 | 06-FEB-01:00 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1394.37 | 22-MAR-07:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 66.29 | 07-APR-13:00 | 775.61 | 11-APR-04:00 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 124.84 | 30-MAY-13:00 | 418.78 | 03-MAY-10:00 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 258.24 | 19-JUN-12:00 | 272.50 | 02-JUN-22:00 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 250.20 | 10-JUL-14:00 | 101.00 | 11-JUL-05:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 358.05 | 24-AUG-17:00 | 148.47 | 20-AUG-06:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 175.22 | 14-SEP-14:00 | 230.86 | 30-SEP-24:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 29.20 | 25-OCT-11:00 | 685.10 | 08-OCT-08:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1222.74 | 23-NOV-02:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1620.50 | 31-DEC-22:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 101.00 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 358.05 | 1620.50 |
Report: PeakSpaceGainsMonthly
For: T NE APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 1504.31 | 31-JAN-01:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1564.62 | 06-FEB-01:00 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1394.37 | 22-MAR-07:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 66.29 | 07-APR-13:00 | 775.61 | 11-APR-04:00 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 124.84 | 30-MAY-13:00 | 416.70 | 03-MAY-04:00 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 258.24 | 19-JUN-12:00 | 271.69 | 02-JUN-19:00 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 250.20 | 10-JUL-14:00 | 101.00 | 11-JUL-05:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 358.05 | 24-AUG-17:00 | 143.77 | 20-AUG-06:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 175.22 | 14-SEP-14:00 | 218.49 | 23-SEP-04:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 29.20 | 25-OCT-11:00 | 685.10 | 08-OCT-08:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1222.74 | 23-NOV-02:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1620.50 | 31-DEC-22:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 101.00 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 358.05 | 1620.50 |
Report: PeakSpaceGainsMonthly
For: T N1 APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 907.36 | 31-JAN-01:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 943.74 | 06-FEB-01:00 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 841.05 | 22-MAR-07:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 39.99 | 07-APR-13:00 | 467.83 | 11-APR-04:00 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 75.30 | 30-MAY-13:00 | 267.05 | 03-MAY-10:00 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 155.76 | 19-JUN-12:00 | 165.79 | 02-JUN-22:00 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 150.91 | 10-JUL-14:00 | 60.92 | 11-JUL-05:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 215.96 | 24-AUG-17:00 | 90.67 | 20-AUG-06:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 105.69 | 14-SEP-14:00 | 140.93 | 23-SEP-04:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.62 | 25-OCT-11:00 | 413.23 | 08-OCT-08:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 737.53 | 23-NOV-02:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 977.45 | 31-DEC-22:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.92 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 215.96 | 977.45 |
Report: PeakSpaceGainsMonthly
For: T N2 APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 907.36 | 31-JAN-01:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 943.74 | 06-FEB-01:00 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 841.05 | 22-MAR-07:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 39.99 | 07-APR-13:00 | 467.83 | 11-APR-04:00 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 75.30 | 30-MAY-13:00 | 266.96 | 03-MAY-10:00 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 155.76 | 19-JUN-12:00 | 165.79 | 02-JUN-22:00 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 150.91 | 10-JUL-14:00 | 60.92 | 11-JUL-05:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 215.96 | 24-AUG-17:00 | 90.57 | 20-AUG-06:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 105.69 | 14-SEP-14:00 | 140.93 | 23-SEP-04:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.62 | 25-OCT-11:00 | 413.23 | 08-OCT-08:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 737.53 | 23-NOV-02:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 977.45 | 31-DEC-22:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.92 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 215.96 | 977.45 |
Report: PeakSpaceGainsMonthly
For: T S1 APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 907.36 | 31-JAN-01:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 943.74 | 06-FEB-01:00 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 841.05 | 22-MAR-07:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 39.99 | 07-APR-13:00 | 467.83 | 11-APR-04:00 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 75.30 | 30-MAY-13:00 | 274.45 | 03-MAY-10:00 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 155.76 | 19-JUN-12:00 | 165.79 | 02-JUN-22:00 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 150.91 | 10-JUL-14:00 | 60.92 | 11-JUL-05:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 215.96 | 24-AUG-17:00 | 93.67 | 20-AUG-06:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 105.69 | 14-SEP-14:00 | 147.12 | 30-SEP-24:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.62 | 25-OCT-11:00 | 415.59 | 27-OCT-18:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 737.53 | 23-NOV-02:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 977.45 | 31-DEC-22:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.92 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 215.96 | 977.45 |
Report: PeakSpaceGainsMonthly
For: T S2 APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 907.36 | 31-JAN-01:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 943.74 | 06-FEB-01:00 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 841.05 | 22-MAR-07:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 39.99 | 07-APR-13:00 | 467.83 | 11-APR-04:00 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 75.30 | 30-MAY-13:00 | 274.39 | 03-MAY-10:00 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 155.76 | 19-JUN-12:00 | 165.79 | 02-JUN-22:00 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 150.91 | 10-JUL-14:00 | 60.92 | 11-JUL-05:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 215.96 | 24-AUG-17:00 | 93.58 | 20-AUG-06:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 105.69 | 14-SEP-14:00 | 146.94 | 30-SEP-24:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.62 | 25-OCT-11:00 | 415.08 | 27-OCT-18:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 737.53 | 23-NOV-02:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 977.45 | 31-DEC-22:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.92 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 215.96 | 977.45 |
Report: PeakSpaceGainsMonthly
For: T CORRIDOR
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 397.10 | 01-JAN-00:10 | 370.63 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 244.78 | 31-JAN-01:00 |
| February | 397.10 | 01-FEB-00:10 | 370.63 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 251.86 | 06-FEB-01:00 |
| March | 397.10 | 01-MAR-00:10 | 370.63 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 227.78 | 22-MAR-07:00 |
| April | 397.10 | 01-APR-00:10 | 370.63 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.01 | 07-APR-13:00 | 145.55 | 11-APR-04:00 |
| May | 397.10 | 01-MAY-00:10 | 370.63 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.59 | 30-MAY-13:00 | 86.12 | 03-MAY-04:00 |
| June | 397.10 | 01-JUN-00:10 | 370.63 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.09 | 19-JUN-12:00 | 60.95 | 02-JUN-18:50 |
| July | 397.10 | 01-JUL-00:10 | 370.63 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.35 | 10-JUL-14:00 | 26.21 | 02-JUL-19:00 |
| August | 397.10 | 01-AUG-00:10 | 370.63 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.08 | 24-AUG-15:00 | 32.97 | 20-AUG-06:00 |
| September | 397.10 | 01-SEP-00:10 | 370.63 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.76 | 14-SEP-14:00 | 46.33 | 23-SEP-04:00 |
| October | 397.10 | 01-OCT-00:10 | 370.63 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 119.92 | 27-OCT-18:00 |
| November | 397.10 | 01-NOV-00:10 | 370.63 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 197.46 | 23-NOV-02:00 |
| December | 397.10 | 01-DEC-00:10 | 370.63 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 262.71 | 31-DEC-22:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
| Minimum of Months | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.21 | ||||
| Maximum of Months | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.08 | 262.71 |
Report: PeakSpaceGainsMonthly
For: G CORRIDOR
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 397.10 | 01-JAN-00:10 | 370.63 | 01-JAN-00:10 | 208.40 | 01-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 18093.67 | 02-JAN-07:01 |
| February | 397.10 | 01-FEB-00:10 | 370.63 | 01-FEB-00:10 | 208.40 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 18765.60 | 06-FEB-07:01 |
| March | 397.10 | 01-MAR-00:10 | 370.63 | 01-MAR-00:10 | 208.40 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.57 | 27-MAR-16:00 | 14285.07 | 23-MAR-06:01 |
| April | 397.10 | 01-APR-00:10 | 370.63 | 01-APR-00:10 | 208.40 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 854.98 | 07-APR-16:05 | 10705.92 | 12-APR-06:01 |
| May | 397.10 | 01-MAY-00:10 | 370.63 | 01-MAY-00:10 | 208.40 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 603.23 | 30-MAY-16:03 | 7825.83 | 01-MAY-06:01 |
| June | 397.10 | 01-JUN-00:10 | 370.63 | 01-JUN-00:10 | 208.40 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2138.39 | 19-JUN-16:02 | 6218.61 | 02-JUN-06:01 |
| July | 397.10 | 01-JUL-00:10 | 370.63 | 01-JUL-00:10 | 208.40 | 01-JUL-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1682.72 | 10-JUL-16:02 | 2885.45 | 11-JUL-06:02 |
| August | 397.10 | 01-AUG-00:10 | 370.63 | 01-AUG-00:10 | 208.40 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3191.21 | 24-AUG-16:02 | 5211.01 | 20-AUG-06:01 |
| September | 397.10 | 01-SEP-00:10 | 370.63 | 01-SEP-00:10 | 208.40 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1270.69 | 14-SEP-16:02 | 7924.24 | 24-SEP-06:01 |
| October | 397.10 | 01-OCT-00:10 | 370.63 | 01-OCT-00:10 | 208.40 | 01-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 12069.57 | 09-OCT-06:01 |
| November | 397.10 | 01-NOV-00:10 | 370.63 | 01-NOV-00:10 | 208.40 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 14065.56 | 24-NOV-07:01 |
| December | 397.10 | 01-DEC-00:10 | 370.63 | 01-DEC-00:10 | 208.40 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 14690.43 | 22-DEC-07:01 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 397.10 | 370.63 | 208.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2885.45 | |||||
| Maximum of Months | 397.10 | 370.63 | 208.40 | 0.00 | 0.00 | 0.00 | 0.00 | 3191.21 | 18765.60 |
Report: PeakSpaceGainsMonthly
For: M CORRIDOR
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 397.10 | 01-JAN-00:10 | 370.63 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 200.59 | 31-JAN-01:00 |
| February | 397.10 | 01-FEB-00:10 | 370.63 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 204.96 | 06-FEB-01:00 |
| March | 397.10 | 01-MAR-00:10 | 370.63 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 188.63 | 22-MAR-07:00 |
| April | 397.10 | 01-APR-00:10 | 370.63 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.74 | 07-APR-13:00 | 127.13 | 11-APR-04:00 |
| May | 397.10 | 01-MAY-00:10 | 370.63 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.09 | 30-MAY-13:00 | 79.39 | 03-MAY-10:00 |
| June | 397.10 | 01-JUN-00:10 | 370.63 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.64 | 19-JUN-12:00 | 45.72 | 02-JUN-19:00 |
| July | 397.10 | 01-JUL-00:10 | 370.63 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.59 | 10-JUL-14:00 | 18.93 | 11-JUL-05:00 |
| August | 397.10 | 01-AUG-00:10 | 370.63 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.39 | 24-AUG-17:00 | 28.16 | 20-AUG-06:00 |
| September | 397.10 | 01-SEP-00:10 | 370.63 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.42 | 14-SEP-14:00 | 38.27 | 30-SEP-24:00 |
| October | 397.10 | 01-OCT-00:10 | 370.63 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 108.03 | 08-OCT-08:00 |
| November | 397.10 | 01-NOV-00:10 | 370.63 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 162.88 | 23-NOV-02:00 |
| December | 397.10 | 01-DEC-00:10 | 370.63 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 213.40 | 31-DEC-22:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
| Minimum of Months | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.93 | ||||
| Maximum of Months | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.39 | 213.40 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: G SW APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 617.89 | 31-JAN-16:10 | 0.00 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.92 |
| February | 531.38 | 02-FEB-16:30 | 0.00 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 229.09 |
| March | 524.86 | 29-MAR-19:00 | 237.50 | 138.88 | 547.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 185.48 |
| April | 738.78 | 10-APR-16:05 | 0.00 | 347.20 | 2354.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 95.20 |
| May | 1466.83 | 30-MAY-16:05 | 0.00 | 347.20 | 2354.49 | 0.00 | 0.00 | 0.00 | 0.00 | 39.40 | 0.00 |
| June | 1864.69 | 19-JUN-17:17 | 712.50 | 351.55 | 1765.87 | 0.00 | 0.00 | 0.00 | 0.00 | 119.03 | 0.00 |
| July | 1917.23 | 13-JUL-16:02 | 0.00 | 434.00 | 2943.11 | 0.00 | 0.00 | 0.00 | 0.00 | 71.32 | 0.00 |
| August | 2288.80 | 18-AUG-16:03 | 0.00 | 520.80 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 95.17 | 0.00 |
| September | 2224.38 | 01-SEP-14:30 | 0.00 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 73.75 | 0.00 |
| October | 2013.31 | 04-OCT-15:10 | 0.00 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.12 |
| November | 901.50 | 03-NOV-16:04 | 0.00 | 694.39 | 4708.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.68 |
| December | 572.96 | 21-DEC-16:30 | 0.00 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 148.12 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 524.86 | 0.00 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 2288.80 | 712.50 | 694.39 | 4708.98 | 0.00 | 0.00 | 0.00 | 0.00 | 119.03 | 229.09 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: G NW APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 56.89 | 17-JAN-17:02 | 1235.00 | 867.99 | 5886.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 36.92 | 20-FEB-17:04 | 1235.00 | 867.99 | 5886.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 117.19 |
| March | 337.37 | 28-MAR-19:30 | 206.62 | 138.88 | 523.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 199.72 |
| April | 409.44 | 12-APR-21:25 | 475.00 | 104.17 | 835.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74.50 |
| May | 1286.77 | 30-MAY-16:40 | 123.50 | 86.80 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 28.66 | 0.00 |
| June | 1799.93 | 19-JUN-17:30 | 413.25 | 234.36 | 1177.25 | 0.00 | 0.00 | 0.00 | 0.00 | 113.59 | 0.00 |
| July | 1780.41 | 13-JUL-16:30 | 247.00 | 173.60 | 1177.25 | 0.00 | 0.00 | 0.00 | 0.00 | 64.32 | 0.00 |
| August | 1927.69 | 18-AUG-16:30 | 123.50 | 86.80 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 94.10 | 0.00 |
| September | 1611.12 | 07-SEP-16:15 | 494.00 | 347.20 | 2354.49 | 0.00 | 0.00 | 0.00 | 0.00 | 33.08 | 0.00 |
| October | 1165.38 | 04-OCT-16:10 | 494.00 | 347.20 | 2354.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.29 |
| November | 408.63 | 06-NOV-22:40 | 237.50 | 52.08 | 417.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 111.32 |
| December | 120.69 | 04-DEC-19:00 | 206.62 | 117.18 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 36.92 | 123.50 | 52.08 | 417.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 1927.69 | 1235.00 | 867.99 | 5886.23 | 0.00 | 0.00 | 0.00 | 0.00 | 113.59 | 199.72 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: OFFICE
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 1058.72 | 31-JAN-08:03 | 4512.06 | 5829.16 | 5886.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 552.59 |
| February | 1165.39 | 06-FEB-08:03 | 4512.06 | 5829.16 | 5886.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 573.55 |
| March | 819.00 | 23-MAR-07:03 | 4512.06 | 5829.16 | 5886.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 127.11 |
| April | 3436.31 | 10-APR-08:63 | 1353.62 | 1748.75 | 1765.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80.43 |
| May | 6227.44 | 30-MAY-07:02 | 2256.03 | 2914.58 | 2943.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.25 |
| June | 6183.92 | 02-JUN-08:62 | 1804.82 | 2331.66 | 2354.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94.29 |
| July | 6514.04 | 11-JUL-07:02 | 2707.23 | 3497.50 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.63 |
| August | 6578.69 | 23-AUG-07:02 | 2707.23 | 3497.50 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.27 |
| September | 6669.28 | 11-SEP-07:01 | 3158.44 | 4080.41 | 4120.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 108.22 |
| October | 6409.13 | 16-OCT-08:62 | 1804.82 | 2331.66 | 2354.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97.69 |
| November | 1584.57 | 10-NOV-09:05 | 902.41 | 1165.83 | 1177.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 119.73 |
| December | 782.99 | 22-DEC-09:07 | 1353.62 | 1748.75 | 1765.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 179.19 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 782.99 | 902.41 | 1165.83 | 1177.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.25 | |
| Maximum of Months | 6669.28 | 4512.06 | 5829.16 | 5886.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 573.55 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: G NE APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 0.00 | 01-JAN-00:10 | 237.50 | 8.68 | 264.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 645.79 |
| February | 0.00 | 01-FEB-00:10 | 237.50 | 8.68 | 264.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 229.49 |
| March | 336.23 | 28-MAR-19:30 | 206.62 | 138.88 | 523.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 199.08 |
| April | 433.40 | 12-APR-09:00 | 59.38 | 17.36 | 394.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 258.11 |
| May | 1073.56 | 31-MAY-10:10 | 59.38 | 17.36 | 412.04 | 0.00 | 0.00 | 0.00 | 0.00 | 10.70 | 0.00 |
| June | 1500.21 | 19-JUN-17:20 | 619.87 | 351.55 | 1765.87 | 0.00 | 0.00 | 0.00 | 0.00 | 119.03 | 0.00 |
| July | 1595.20 | 10-JUL-16:17 | 370.50 | 260.40 | 1765.87 | 0.00 | 0.00 | 0.00 | 0.00 | 92.54 | 0.00 |
| August | 1642.08 | 24-AUG-17:00 | 123.50 | 86.80 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 189.56 | 0.00 |
| September | 1399.55 | 06-SEP-10:30 | 59.38 | 17.36 | 412.04 | 0.00 | 0.00 | 0.00 | 0.00 | 17.65 | 0.00 |
| October | 908.46 | 25-OCT-10:30 | 59.38 | 17.36 | 412.04 | 0.00 | 0.00 | 0.00 | 0.00 | 2.30 | 0.00 |
| November | 421.43 | 05-NOV-22:00 | 237.50 | 52.08 | 417.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 213.02 |
| December | 108.14 | 20-DEC-12:00 | 59.38 | 17.36 | 412.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.98 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 0.00 | 59.38 | 8.68 | 264.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 1642.08 | 619.87 | 351.55 | 1765.87 | 0.00 | 0.00 | 0.00 | 0.00 | 189.56 | 645.79 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: G N1 APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 176.78 | 23-JAN-19:00 | 206.62 | 117.18 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.14 |
| February | 85.80 | 20-FEB-17:04 | 1235.00 | 867.99 | 5886.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.69 |
| March | 339.52 | 28-MAR-19:30 | 206.62 | 138.88 | 523.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 121.19 |
| April | 461.42 | 11-APR-06:00 | 237.50 | 60.76 | 317.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 173.59 |
| May | 868.57 | 30-MAY-17:20 | 413.25 | 234.36 | 1177.25 | 0.00 | 0.00 | 0.00 | 0.00 | 4.64 | 0.00 |
| June | 1236.74 | 19-JUN-17:25 | 413.25 | 234.36 | 1177.25 | 0.00 | 0.00 | 0.00 | 0.00 | 68.52 | 0.00 |
| July | 1295.90 | 10-JUL-17:27 | 619.87 | 351.55 | 1765.87 | 0.00 | 0.00 | 0.00 | 0.00 | 49.23 | 0.00 |
| August | 1288.45 | 17-AUG-17:03 | 619.87 | 351.55 | 1765.87 | 0.00 | 0.00 | 0.00 | 0.00 | 67.42 | 0.00 |
| September | 1099.97 | 01-SEP-16:17 | 370.50 | 260.40 | 1765.87 | 0.00 | 0.00 | 0.00 | 0.00 | 29.11 | 0.00 |
| October | 761.15 | 04-OCT-16:05 | 494.00 | 347.20 | 2354.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.02 |
| November | 490.00 | 06-NOV-04:00 | 237.50 | 8.68 | 223.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 116.22 |
| December | 256.29 | 04-DEC-19:00 | 206.62 | 117.18 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 85.80 | 206.62 | 8.68 | 223.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 1295.90 | 1235.00 | 867.99 | 5886.23 | 0.00 | 0.00 | 0.00 | 0.00 | 68.52 | 173.59 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: G N2 APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 176.67 | 23-JAN-19:00 | 206.62 | 117.18 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.14 |
| February | 82.34 | 20-FEB-17:04 | 1235.00 | 867.99 | 5886.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.69 |
| March | 339.46 | 28-MAR-19:30 | 206.62 | 138.88 | 523.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 121.16 |
| April | 461.38 | 11-APR-06:00 | 237.50 | 60.76 | 317.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 173.58 |
| May | 869.34 | 30-MAY-17:20 | 413.25 | 234.36 | 1177.25 | 0.00 | 0.00 | 0.00 | 0.00 | 4.64 | 0.00 |
| June | 1228.66 | 19-JUN-17:25 | 413.25 | 234.36 | 1177.25 | 0.00 | 0.00 | 0.00 | 0.00 | 68.52 | 0.00 |
| July | 1293.64 | 10-JUL-17:35 | 413.25 | 234.36 | 1177.25 | 0.00 | 0.00 | 0.00 | 0.00 | 49.87 | 0.00 |
| August | 1283.55 | 17-AUG-17:03 | 619.87 | 351.55 | 1765.87 | 0.00 | 0.00 | 0.00 | 0.00 | 67.42 | 0.00 |
| September | 1096.82 | 01-SEP-16:17 | 370.50 | 260.40 | 1765.87 | 0.00 | 0.00 | 0.00 | 0.00 | 29.11 | 0.00 |
| October | 767.59 | 06-OCT-17:05 | 1239.75 | 703.09 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80.61 |
| November | 490.59 | 06-NOV-04:00 | 237.50 | 8.68 | 223.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 116.36 |
| December | 255.93 | 04-DEC-19:00 | 206.62 | 117.18 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 82.34 | 206.62 | 8.68 | 223.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 1293.64 | 1239.75 | 867.99 | 5886.23 | 0.00 | 0.00 | 0.00 | 0.00 | 68.52 | 173.58 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: G S1 APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 689.58 | 31-JAN-16:20 | 0.00 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.03 |
| February | 704.14 | 03-FEB-12:10 | 0.00 | 17.36 | 406.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85.48 |
| March | 531.00 | 29-MAR-19:00 | 237.50 | 138.88 | 547.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 113.14 |
| April | 620.86 | 08-APR-12:20 | 118.75 | 17.36 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.93 |
| May | 1066.28 | 30-MAY-13:00 | 0.00 | 17.36 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 40.01 | 0.00 |
| June | 1304.81 | 19-JUN-17:10 | 950.00 | 468.73 | 2354.49 | 0.00 | 0.00 | 0.00 | 0.00 | 75.15 | 0.00 |
| July | 1443.71 | 10-JUL-14:10 | 0.00 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 78.80 | 0.00 |
| August | 1696.86 | 18-AUG-14:10 | 0.00 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 77.63 | 0.00 |
| September | 1738.95 | 01-SEP-14:10 | 0.00 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 42.30 | 0.00 |
| October | 1620.72 | 04-OCT-14:10 | 0.00 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 1.76 | 0.00 |
| November | 976.04 | 02-NOV-12:50 | 0.00 | 17.36 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.54 |
| December | 662.82 | 21-DEC-19:00 | 237.50 | 117.18 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.61 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 531.00 | 0.00 | 17.36 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 1738.95 | 950.00 | 468.73 | 2354.49 | 0.00 | 0.00 | 0.00 | 0.00 | 78.80 | 113.14 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: G S2 APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 643.05 | 31-JAN-16:10 | 0.00 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.41 |
| February | 687.77 | 03-FEB-12:30 | 0.00 | 17.36 | 406.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83.39 |
| March | 529.79 | 29-MAR-19:00 | 237.50 | 138.88 | 547.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 112.89 |
| April | 656.85 | 08-APR-12:20 | 118.75 | 17.36 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.93 |
| May | 1140.89 | 30-MAY-13:00 | 0.00 | 17.36 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 40.01 | 0.00 |
| June | 1372.47 | 19-JUN-13:00 | 0.00 | 17.36 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 78.60 | 0.00 |
| July | 1551.72 | 10-JUL-14:10 | 0.00 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 78.80 | 0.00 |
| August | 1789.25 | 13-AUG-13:40 | 118.75 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 32.55 | 0.00 |
| September | 1830.43 | 04-SEP-13:30 | 118.75 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 12.70 | 0.00 |
| October | 1671.93 | 04-OCT-14:10 | 0.00 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 1.76 | 0.00 |
| November | 1022.59 | 02-NOV-12:50 | 0.00 | 17.36 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.54 |
| December | 651.09 | 21-DEC-18:50 | 237.50 | 117.18 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.75 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 529.79 | 0.00 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 1830.43 | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 78.80 | 112.89 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: M SW APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 756.82 | 31-JAN-13:10 | 0.00 | 17.36 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 434.89 |
| February | 729.17 | 03-FEB-11:10 | 0.00 | 17.36 | 412.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 245.77 |
| March | 683.61 | 03-MAR-14:30 | 0.00 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 246.35 |
| April | 2195.68 | 07-APR-15:30 | 0.00 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 32.48 | 0.00 |
| May | 2315.24 | 30-MAY-16:05 | 0.00 | 347.20 | 2354.49 | 0.00 | 0.00 | 0.00 | 0.00 | 56.33 | 0.00 |
| June | 2521.41 | 19-JUN-17:05 | 950.00 | 468.73 | 2354.49 | 0.00 | 0.00 | 0.00 | 0.00 | 178.65 | 0.00 |
| July | 2439.54 | 13-JUL-16:04 | 0.00 | 434.00 | 2943.11 | 0.00 | 0.00 | 0.00 | 0.00 | 102.07 | 0.00 |
| August | 2784.86 | 18-AUG-16:03 | 0.00 | 520.80 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 136.45 | 0.00 |
| September | 2710.37 | 01-SEP-14:30 | 0.00 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 105.68 | 0.00 |
| October | 2467.95 | 04-OCT-15:10 | 0.00 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.80 |
| November | 1194.96 | 03-NOV-15:50 | 0.00 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85.67 |
| December | 667.73 | 21-DEC-19:00 | 237.50 | 117.18 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 111.96 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 667.73 | 0.00 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 2784.86 | 950.00 | 520.80 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 178.65 | 434.89 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: M NW APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 401.37 | 17-JAN-16:40 | 71.25 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.89 |
| February | 453.21 | 20-FEB-17:12 | 617.50 | 434.00 | 2943.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 167.99 |
| March | 537.50 | 29-MAR-19:00 | 206.62 | 138.88 | 547.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 273.03 |
| April | 1215.22 | 09-APR-17:30 | 206.62 | 117.18 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.25 |
| May | 2142.99 | 30-MAY-16:30 | 123.50 | 86.80 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 46.54 | 0.00 |
| June | 2466.43 | 19-JUN-17:25 | 413.25 | 234.36 | 1177.25 | 0.00 | 0.00 | 0.00 | 0.00 | 162.87 | 0.00 |
| July | 2294.55 | 06-JUL-17:17 | 619.87 | 351.55 | 1765.87 | 0.00 | 0.00 | 0.00 | 0.00 | 76.72 | 0.00 |
| August | 2365.04 | 18-AUG-16:30 | 123.50 | 86.80 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 134.91 | 0.00 |
| September | 1936.23 | 06-SEP-16:30 | 123.50 | 86.80 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 15.68 | 0.00 |
| October | 1442.28 | 04-OCT-16:10 | 494.00 | 347.20 | 2354.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.37 |
| November | 421.34 | 06-NOV-23:00 | 237.50 | 52.08 | 417.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 142.23 |
| December | 304.45 | 04-DEC-19:00 | 206.62 | 117.18 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 304.45 | 71.25 | 52.08 | 417.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 2466.43 | 619.87 | 434.00 | 2943.11 | 0.00 | 0.00 | 0.00 | 0.00 | 162.87 | 273.03 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: M SE APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 766.16 | 31-JAN-13:00 | 0.00 | 17.36 | 406.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 456.68 |
| February | 766.67 | 03-FEB-10:30 | 0.00 | 17.36 | 406.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 378.00 |
| March | 675.55 | 18-MAR-09:10 | 237.50 | 17.36 | 406.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 2050.47 | 08-APR-12:00 | 118.75 | 17.36 | 406.15 | 0.00 | 0.00 | 0.00 | 0.00 | 6.10 | 0.00 |
| May | 2119.65 | 30-MAY-13:00 | 0.00 | 17.36 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 95.01 | 0.00 |
| June | 2311.22 | 19-JUN-12:50 | 0.00 | 17.36 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 188.77 | 0.00 |
| July | 2260.58 | 10-JUL-13:30 | 0.00 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 164.63 | 0.00 |
| August | 2559.04 | 18-AUG-13:00 | 0.00 | 17.36 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 172.27 | 0.00 |
| September | 2542.15 | 01-SEP-13:00 | 0.00 | 17.36 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 112.81 | 0.00 |
| October | 2250.06 | 04-OCT-13:00 | 0.00 | 17.36 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 15.75 | 0.00 |
| November | 1254.18 | 04-NOV-12:30 | 118.75 | 17.36 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.47 |
| December | 664.30 | 21-DEC-19:00 | 237.50 | 117.18 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 111.40 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 664.30 | 0.00 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 2559.04 | 237.50 | 117.18 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 188.77 | 456.68 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: M NE APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 267.18 | 17-JAN-17:10 | 1235.00 | 867.99 | 5886.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 278.91 | 20-FEB-12:00 | 59.38 | 17.36 | 412.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93.45 |
| March | 515.79 | 29-MAR-07:45 | 185.25 | 52.08 | 776.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 307.42 |
| April | 1077.77 | 08-APR-10:30 | 59.38 | 17.36 | 412.04 | 0.00 | 0.00 | 0.00 | 0.00 | 5.45 | 0.00 |
| May | 1767.06 | 30-MAY-10:00 | 59.38 | 17.36 | 406.15 | 0.00 | 0.00 | 0.00 | 0.00 | 36.11 | 0.00 |
| June | 2038.15 | 19-JUN-17:05 | 826.50 | 468.73 | 2354.49 | 0.00 | 0.00 | 0.00 | 0.00 | 178.65 | 0.00 |
| July | 2016.70 | 14-JUL-09:30 | 59.38 | 17.36 | 406.15 | 0.00 | 0.00 | 0.00 | 0.00 | 72.50 | 0.00 |
| August | 1959.51 | 18-AUG-10:10 | 59.38 | 17.36 | 412.04 | 0.00 | 0.00 | 0.00 | 0.00 | 153.98 | 0.00 |
| September | 1632.44 | 01-SEP-10:20 | 59.38 | 17.36 | 412.04 | 0.00 | 0.00 | 0.00 | 0.00 | 49.52 | 0.00 |
| October | 1108.09 | 25-OCT-10:30 | 59.38 | 17.36 | 412.04 | 0.00 | 0.00 | 0.00 | 0.00 | 2.86 | 0.00 |
| November | 421.27 | 06-NOV-23:00 | 237.50 | 52.08 | 417.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 142.21 |
| December | 292.94 | 20-DEC-12:00 | 59.38 | 17.36 | 412.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83.45 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 267.18 | 59.38 | 17.36 | 406.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 2038.15 | 1235.00 | 867.99 | 5886.23 | 0.00 | 0.00 | 0.00 | 0.00 | 178.65 | 307.42 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: M N1 APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 394.69 | 17-JAN-17:15 | 494.00 | 347.20 | 2354.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 410.68 | 20-FEB-17:10 | 1235.00 | 867.99 | 5886.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 101.72 |
| March | 558.20 | 29-MAR-03:00 | 237.50 | 8.68 | 223.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 153.41 |
| April | 788.05 | 09-APR-17:30 | 206.62 | 117.18 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.99 |
| May | 1310.21 | 30-MAY-17:30 | 206.62 | 117.18 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 1.74 | 0.00 |
| June | 1577.89 | 19-JUN-17:25 | 413.25 | 234.36 | 1177.25 | 0.00 | 0.00 | 0.00 | 0.00 | 98.24 | 0.00 |
| July | 1510.87 | 10-JUL-17:50 | 413.25 | 234.36 | 1177.25 | 0.00 | 0.00 | 0.00 | 0.00 | 72.34 | 0.00 |
| August | 1463.43 | 24-AUG-17:00 | 123.50 | 86.80 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 163.97 | 0.00 |
| September | 1235.86 | 01-SEP-16:17 | 370.50 | 260.40 | 1765.87 | 0.00 | 0.00 | 0.00 | 0.00 | 41.63 | 0.00 |
| October | 871.69 | 04-OCT-16:10 | 494.00 | 347.20 | 2354.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.68 |
| November | 493.16 | 06-NOV-04:00 | 237.50 | 8.68 | 223.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 168.27 |
| December | 383.19 | 04-DEC-18:09 | 1446.38 | 820.27 | 4120.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74.28 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 383.19 | 123.50 | 8.68 | 223.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 1577.89 | 1446.38 | 867.99 | 5886.23 | 0.00 | 0.00 | 0.00 | 0.00 | 163.97 | 168.27 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: M N2 APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 390.12 | 17-JAN-17:15 | 494.00 | 347.20 | 2354.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 405.89 | 20-FEB-17:10 | 1235.00 | 867.99 | 5886.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 101.72 |
| March | 552.97 | 29-MAR-02:40 | 237.50 | 8.68 | 223.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 158.10 |
| April | 782.32 | 09-APR-17:30 | 206.62 | 117.18 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.99 |
| May | 1303.91 | 30-MAY-17:30 | 206.62 | 117.18 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 1.74 | 0.00 |
| June | 1570.54 | 19-JUN-17:25 | 413.25 | 234.36 | 1177.25 | 0.00 | 0.00 | 0.00 | 0.00 | 98.24 | 0.00 |
| July | 1506.58 | 10-JUL-17:40 | 413.25 | 234.36 | 1177.25 | 0.00 | 0.00 | 0.00 | 0.00 | 71.43 | 0.00 |
| August | 1459.43 | 24-AUG-17:00 | 123.50 | 86.80 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 163.97 | 0.00 |
| September | 1232.89 | 01-SEP-16:17 | 370.50 | 260.40 | 1765.87 | 0.00 | 0.00 | 0.00 | 0.00 | 41.63 | 0.00 |
| October | 866.23 | 04-OCT-16:10 | 494.00 | 347.20 | 2354.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.68 |
| November | 493.91 | 06-NOV-04:00 | 237.50 | 8.68 | 223.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 168.51 |
| December | 383.17 | 04-DEC-18:10 | 1446.38 | 820.27 | 4120.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74.28 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 383.17 | 123.50 | 8.68 | 223.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 1570.54 | 1446.38 | 867.99 | 5886.23 | 0.00 | 0.00 | 0.00 | 0.00 | 163.97 | 168.51 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: M S1 APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 820.33 | 31-JAN-11:00 | 0.00 | 17.36 | 406.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 262.56 |
| February | 864.31 | 12-FEB-12:20 | 118.75 | 17.36 | 406.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 422.70 |
| March | 763.46 | 03-MAR-14:00 | 0.00 | 17.36 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 143.28 |
| April | 1671.07 | 08-APR-12:20 | 118.75 | 17.36 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.54 |
| May | 1566.37 | 30-MAY-13:00 | 0.00 | 17.36 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 57.31 | 0.00 |
| June | 1691.69 | 19-JUN-13:00 | 0.00 | 17.36 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 112.74 | 0.00 |
| July | 1711.48 | 10-JUL-13:30 | 0.00 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 99.30 | 0.00 |
| August | 1979.48 | 18-AUG-13:20 | 0.00 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 106.70 | 0.00 |
| September | 2038.51 | 01-SEP-13:00 | 0.00 | 17.36 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 68.04 | 0.00 |
| October | 1950.70 | 04-OCT-13:30 | 0.00 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 5.90 | 0.00 |
| November | 1365.07 | 02-NOV-12:50 | 0.00 | 17.36 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 104.49 |
| December | 705.97 | 21-DEC-22:00 | 237.50 | 95.48 | 500.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 147.96 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 705.97 | 0.00 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 2038.51 | 237.50 | 95.48 | 500.33 | 0.00 | 0.00 | 0.00 | 0.00 | 112.74 | 422.70 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: M S2 APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 824.98 | 31-JAN-10:50 | 0.00 | 17.36 | 406.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 274.72 |
| February | 864.48 | 12-FEB-12:20 | 118.75 | 17.36 | 406.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 422.78 |
| March | 772.60 | 03-MAR-14:00 | 0.00 | 17.36 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 143.28 |
| April | 1680.59 | 08-APR-12:20 | 118.75 | 17.36 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.54 |
| May | 1575.76 | 30-MAY-13:00 | 0.00 | 17.36 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 57.31 | 0.00 |
| June | 1695.87 | 19-JUN-13:00 | 0.00 | 17.36 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 112.74 | 0.00 |
| July | 1715.81 | 10-JUL-13:30 | 0.00 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 99.30 | 0.00 |
| August | 1985.41 | 18-AUG-13:20 | 0.00 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 106.70 | 0.00 |
| September | 2043.74 | 01-SEP-13:00 | 0.00 | 17.36 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 68.04 | 0.00 |
| October | 1954.74 | 04-OCT-13:20 | 0.00 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 7.03 | 0.00 |
| November | 1376.73 | 02-NOV-12:50 | 0.00 | 17.36 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 104.49 |
| December | 706.18 | 21-DEC-22:00 | 237.50 | 95.48 | 500.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 148.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 706.18 | 0.00 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 2043.74 | 237.50 | 95.48 | 500.33 | 0.00 | 0.00 | 0.00 | 0.00 | 112.74 | 422.78 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: T SW APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 1055.91 | 17-JAN-15:20 | 0.00 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 143.88 |
| February | 744.25 | 20-FEB-15:30 | 0.00 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 304.78 |
| March | 1583.39 | 03-MAR-14:30 | 0.00 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 327.31 |
| April | 3167.53 | 07-APR-15:20 | 0.00 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 41.89 | 0.00 |
| May | 3217.16 | 30-MAY-15:10 | 0.00 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 87.81 | 0.00 |
| June | 3572.91 | 19-JUN-14:30 | 0.00 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 199.93 | 0.00 |
| July | 3422.08 | 10-JUL-15:10 | 0.00 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 221.54 | 0.00 |
| August | 3899.50 | 18-AUG-15:10 | 0.00 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 223.71 | 0.00 |
| September | 3765.93 | 01-SEP-14:30 | 0.00 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 138.98 | 0.00 |
| October | 3198.98 | 04-OCT-14:40 | 0.00 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.14 | 0.00 |
| November | 1329.16 | 02-NOV-13:00 | 0.00 | 17.36 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 221.46 |
| December | 1151.67 | 17-DEC-14:30 | 118.75 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 273.94 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 744.25 | 0.00 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 3899.50 | 118.75 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 223.71 | 327.31 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: T NW APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 399.72 | 17-JAN-16:40 | 71.25 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.82 |
| February | 419.06 | 20-FEB-16:00 | 59.38 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 246.12 |
| March | 750.23 | 27-MAR-16:40 | 123.50 | 86.80 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.34 |
| April | 2104.26 | 07-APR-16:10 | 247.00 | 173.60 | 1177.25 | 0.00 | 0.00 | 0.00 | 0.00 | 44.12 | 0.00 |
| May | 2994.33 | 30-MAY-16:12 | 494.00 | 347.20 | 2354.49 | 0.00 | 0.00 | 0.00 | 0.00 | 67.58 | 0.00 |
| June | 3369.50 | 19-JUN-17:17 | 619.87 | 351.55 | 1765.87 | 0.00 | 0.00 | 0.00 | 0.00 | 224.76 | 0.00 |
| July | 3150.36 | 13-JUL-16:08 | 617.50 | 434.00 | 2943.11 | 0.00 | 0.00 | 0.00 | 0.00 | 133.88 | 0.00 |
| August | 3267.86 | 18-AUG-16:17 | 370.50 | 260.40 | 1765.87 | 0.00 | 0.00 | 0.00 | 0.00 | 178.69 | 0.00 |
| September | 2614.86 | 01-SEP-14:40 | 59.38 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 142.20 | 0.00 |
| October | 1875.89 | 04-OCT-15:30 | 71.25 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.27 |
| November | 330.53 | 03-NOV-18:00 | 206.62 | 117.18 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 200.94 | 17-DEC-15:10 | 59.38 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 228.93 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 200.94 | 59.38 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 3369.50 | 619.87 | 434.00 | 2943.11 | 0.00 | 0.00 | 0.00 | 0.00 | 224.76 | 246.12 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: T SE APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 794.19 | 17-JAN-14:10 | 0.00 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 169.95 |
| February | 726.44 | 03-FEB-11:20 | 0.00 | 17.36 | 412.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 315.30 |
| March | 1523.40 | 01-MAR-13:40 | 0.00 | 17.36 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 199.88 |
| April | 2885.38 | 07-APR-12:50 | 0.00 | 17.36 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 61.73 | 0.00 |
| May | 3068.66 | 30-MAY-13:00 | 0.00 | 17.36 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 124.84 | 0.00 |
| June | 3487.72 | 19-JUN-13:00 | 0.00 | 17.36 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 246.36 | 0.00 |
| July | 3261.07 | 10-JUL-13:30 | 0.00 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 216.75 | 0.00 |
| August | 3630.62 | 18-AUG-13:00 | 0.00 | 17.36 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 226.90 | 0.00 |
| September | 3545.19 | 01-SEP-13:00 | 0.00 | 17.36 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 148.33 | 0.00 |
| October | 2933.28 | 04-OCT-13:00 | 0.00 | 17.36 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 19.99 | 0.00 |
| November | 1436.75 | 02-NOV-13:00 | 0.00 | 17.36 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 221.46 |
| December | 1007.69 | 17-DEC-13:30 | 118.75 | 17.36 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 221.15 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 726.44 | 0.00 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 3630.62 | 118.75 | 17.36 | 412.04 | 0.00 | 0.00 | 0.00 | 0.00 | 246.36 | 315.30 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: T NE APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 90.57 | 17-JAN-14:30 | 59.38 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 126.99 |
| February | 156.96 | 19-FEB-15:10 | 59.38 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 182.99 |
| March | 452.88 | 29-MAR-09:30 | 59.38 | 17.36 | 406.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 272.94 |
| April | 1603.50 | 08-APR-12:00 | 59.38 | 17.36 | 406.15 | 0.00 | 0.00 | 0.00 | 0.00 | 7.23 | 0.00 |
| May | 2470.18 | 30-MAY-13:00 | 59.38 | 17.36 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 124.84 | 0.00 |
| June | 2955.12 | 19-JUN-12:00 | 59.38 | 17.36 | 406.15 | 0.00 | 0.00 | 0.00 | 0.00 | 258.24 | 0.00 |
| July | 2769.45 | 08-JUL-12:00 | 59.38 | 17.36 | 406.15 | 0.00 | 0.00 | 0.00 | 0.00 | 169.61 | 0.00 |
| August | 2683.97 | 01-AUG-10:50 | 59.38 | 17.36 | 412.04 | 0.00 | 0.00 | 0.00 | 0.00 | 143.57 | 0.00 |
| September | 2275.13 | 01-SEP-13:00 | 59.38 | 17.36 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 148.33 | 0.00 |
| October | 1407.87 | 04-OCT-13:00 | 59.38 | 17.36 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 19.99 | 0.00 |
| November | 322.28 | 08-NOV-18:00 | 123.50 | 86.80 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 98.03 | 20-DEC-12:00 | 59.38 | 17.36 | 412.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 110.75 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 90.57 | 59.38 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 2955.12 | 123.50 | 86.80 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 258.24 | 272.94 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: T N1 APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 198.75 | 17-JAN-17:02 | 1235.00 | 867.99 | 5886.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 222.58 | 19-FEB-16:10 | 71.25 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 115.58 |
| March | 466.69 | 29-MAR-17:12 | 1239.75 | 703.09 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 248.53 |
| April | 1201.59 | 07-APR-16:17 | 370.50 | 260.40 | 1765.87 | 0.00 | 0.00 | 0.00 | 0.00 | 27.97 | 0.00 |
| May | 1874.70 | 30-MAY-16:08 | 494.00 | 347.20 | 2354.49 | 0.00 | 0.00 | 0.00 | 0.00 | 44.48 | 0.00 |
| June | 2249.00 | 19-JUN-17:30 | 413.25 | 234.36 | 1177.25 | 0.00 | 0.00 | 0.00 | 0.00 | 129.36 | 0.00 |
| July | 2131.81 | 07-JUL-15:10 | 71.25 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 91.59 | 0.00 |
| August | 2051.70 | 24-AUG-16:17 | 370.50 | 260.40 | 1765.87 | 0.00 | 0.00 | 0.00 | 0.00 | 177.50 | 0.00 |
| September | 1750.42 | 01-SEP-15:10 | 71.25 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 84.31 | 0.00 |
| October | 1096.11 | 04-OCT-15:10 | 71.25 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 |
| November | 332.93 | 04-NOV-03:00 | 237.50 | 8.68 | 223.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 135.46 | 04-DEC-19:00 | 206.62 | 117.18 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 135.46 | 71.25 | 8.68 | 223.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 2249.00 | 1239.75 | 867.99 | 5886.23 | 0.00 | 0.00 | 0.00 | 0.00 | 177.50 | 248.53 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: T N2 APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 188.16 | 17-JAN-17:02 | 1235.00 | 867.99 | 5886.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 218.41 | 19-FEB-16:10 | 71.25 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 115.58 |
| March | 449.86 | 29-MAR-16:50 | 123.50 | 86.80 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 246.11 |
| April | 1194.25 | 07-APR-16:17 | 370.50 | 260.40 | 1765.87 | 0.00 | 0.00 | 0.00 | 0.00 | 27.97 | 0.00 |
| May | 1860.62 | 30-MAY-16:08 | 494.00 | 347.20 | 2354.49 | 0.00 | 0.00 | 0.00 | 0.00 | 44.48 | 0.00 |
| June | 2248.05 | 19-JUN-14:30 | 59.38 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 120.59 | 0.00 |
| July | 2121.97 | 07-JUL-15:10 | 71.25 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 91.59 | 0.00 |
| August | 2041.85 | 24-AUG-16:17 | 370.50 | 260.40 | 1765.87 | 0.00 | 0.00 | 0.00 | 0.00 | 177.50 | 0.00 |
| September | 1744.62 | 01-SEP-14:30 | 59.38 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 83.83 | 0.00 |
| October | 1090.43 | 04-OCT-15:10 | 71.25 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 |
| November | 329.48 | 08-NOV-18:00 | 123.50 | 86.80 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 133.30 | 04-DEC-19:00 | 206.62 | 117.18 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 133.30 | 59.38 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 2248.05 | 1235.00 | 867.99 | 5886.23 | 0.00 | 0.00 | 0.00 | 0.00 | 177.50 | 246.11 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: T S1 APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 946.39 | 17-JAN-14:30 | 0.00 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.14 |
| February | 747.83 | 09-FEB-12:00 | 0.00 | 17.36 | 412.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 478.36 |
| March | 1427.79 | 03-MAR-14:00 | 0.00 | 17.36 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 190.37 |
| April | 2401.22 | 07-APR-13:00 | 0.00 | 17.36 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 39.99 | 0.00 |
| May | 2415.17 | 30-MAY-13:00 | 0.00 | 17.36 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 75.30 | 0.00 |
| June | 2713.38 | 19-JUN-13:30 | 0.00 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 124.36 | 0.00 |
| July | 2616.38 | 10-JUL-13:40 | 0.00 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 137.35 | 0.00 |
| August | 2957.09 | 18-AUG-13:30 | 0.00 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 142.38 | 0.00 |
| September | 2951.25 | 01-SEP-13:20 | 0.00 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 85.79 | 0.00 |
| October | 2584.33 | 04-OCT-13:30 | 0.00 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 7.35 | 0.00 |
| November | 1445.96 | 02-NOV-13:00 | 0.00 | 17.36 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 133.58 |
| December | 1164.18 | 17-DEC-14:00 | 118.75 | 17.36 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 157.65 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 747.83 | 0.00 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 2957.09 | 118.75 | 17.36 | 412.04 | 0.00 | 0.00 | 0.00 | 0.00 | 142.38 | 478.36 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: T S2 APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 951.52 | 17-JAN-14:20 | 0.00 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 100.34 |
| February | 752.98 | 09-FEB-11:50 | 0.00 | 17.36 | 412.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 470.81 |
| March | 1442.21 | 03-MAR-14:00 | 0.00 | 17.36 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 190.37 |
| April | 2420.97 | 07-APR-13:00 | 0.00 | 17.36 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 39.99 | 0.00 |
| May | 2429.32 | 30-MAY-13:00 | 0.00 | 17.36 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 75.30 | 0.00 |
| June | 2721.60 | 19-JUN-13:20 | 0.00 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 132.32 | 0.00 |
| July | 2621.25 | 10-JUL-13:30 | 0.00 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 130.74 | 0.00 |
| August | 2966.95 | 18-AUG-13:20 | 0.00 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 140.54 | 0.00 |
| September | 2959.96 | 01-SEP-13:20 | 0.00 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 85.79 | 0.00 |
| October | 2591.75 | 04-OCT-13:30 | 0.00 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 7.35 | 0.00 |
| November | 1463.85 | 02-NOV-13:00 | 0.00 | 17.36 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 133.58 |
| December | 1175.66 | 17-DEC-13:50 | 118.75 | 17.36 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 149.56 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 752.98 | 0.00 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 2966.95 | 118.75 | 17.36 | 412.04 | 0.00 | 0.00 | 0.00 | 0.00 | 140.54 | 470.81 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: T CORRIDOR
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 0.00 | 01-JAN-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 197.47 |
| February | 0.00 | 01-FEB-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.64 |
| March | 0.00 | 01-MAR-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.78 |
| April | 0.00 | 01-APR-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.95 |
| May | 0.00 | 01-MAY-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.62 |
| June | 0.00 | 01-JUN-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.71 |
| July | 0.00 | 01-JUL-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.47 |
| August | 0.00 | 01-AUG-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.32 |
| September | 0.00 | 01-SEP-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.76 |
| October | 0.00 | 01-OCT-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.73 |
| November | 0.00 | 01-NOV-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.84 |
| December | 0.00 | 01-DEC-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93.07 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
| Minimum of Months | 0.00 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.32 | |
| Maximum of Months | 0.00 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 197.47 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: G CORRIDOR
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 0.00 | 01-JAN-00:10 | 397.10 | 370.63 | 56.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 102.41 |
| February | 0.00 | 01-FEB-00:10 | 397.10 | 370.63 | 56.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.93 |
| March | 0.00 | 01-MAR-00:10 | 397.10 | 370.63 | 56.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.22 |
| April | 0.00 | 01-APR-00:10 | 397.10 | 370.63 | 56.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.33 |
| May | 0.00 | 01-MAY-00:10 | 397.10 | 370.63 | 56.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.48 |
| June | 0.00 | 01-JUN-00:10 | 397.10 | 370.63 | 56.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.40 |
| July | 0.00 | 01-JUL-00:10 | 397.10 | 370.63 | 56.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.83 |
| August | 0.00 | 01-AUG-00:10 | 397.10 | 370.63 | 56.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.15 |
| September | 0.00 | 01-SEP-00:10 | 397.10 | 370.63 | 56.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.70 |
| October | 0.00 | 01-OCT-00:10 | 397.10 | 370.63 | 56.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.43 |
| November | 0.00 | 01-NOV-00:10 | 397.10 | 370.63 | 56.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.70 |
| December | 0.00 | 01-DEC-00:10 | 397.10 | 370.63 | 56.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.14 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 0.00 | 397.10 | 370.63 | 56.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.15 | |
| Maximum of Months | 0.00 | 397.10 | 370.63 | 56.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 102.41 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: M CORRIDOR
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 0.00 | 01-JAN-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 161.07 |
| February | 0.00 | 01-FEB-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.39 |
| March | 0.00 | 01-MAR-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.28 |
| April | 0.00 | 01-APR-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.64 |
| May | 0.00 | 01-MAY-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.71 |
| June | 0.00 | 01-JUN-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.21 |
| July | 0.00 | 01-JUL-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.46 |
| August | 0.00 | 01-AUG-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.89 |
| September | 0.00 | 01-SEP-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.88 |
| October | 0.00 | 01-OCT-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.82 |
| November | 0.00 | 01-NOV-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.02 |
| December | 0.00 | 01-DEC-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77.84 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
| Minimum of Months | 0.00 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.89 | |
| Maximum of Months | 0.00 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 161.07 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
| January | 0.103055E+12 | 72657.77 | 14-JAN-18:40 | 0.102967E+12 | 94160.03 | 02-JAN-00:10 |
| February | 0.930818E+11 | 69638.93 | 06-FEB-18:40 | 0.934239E+11 | 105858.87 | 06-FEB-01:10 |
| March | 0.100146E+12 | 69984.24 | 04-MAR-18:30 | 0.480579E+11 | 65606.35 | 22-MAR-07:10 |
| April | 0.956532E+11 | 74197.81 | 07-APR-16:40 | 0.156957E+11 | 37825.48 | 02-APR-05:00 |
| May | 0.102680E+12 | 75554.29 | 30-MAY-16:19 | 0.608020E+09 | 9991.24 | 01-MAY-04:00 |
| June | 0.117437E+12 | 88325.42 | 19-JUN-17:40 | 0.00 | 0.00 | 01-JUN-00:10 |
| July | 0.136740E+12 | 84176.27 | 06-JUL-17:40 | 0.00 | 0.00 | 01-JUL-00:10 |
| August | 0.134706E+12 | 83537.61 | 04-AUG-17:10 | 0.00 | 0.00 | 01-AUG-00:10 |
| September | 0.110763E+12 | 76097.19 | 07-SEP-16:00 | 4524842.42 | 859.09 | 24-SEP-05:30 |
| October | 0.102119E+12 | 74334.79 | 04-OCT-17:10 | 0.278857E+10 | 11919.44 | 28-OCT-04:00 |
| November | 0.946630E+11 | 62943.22 | 15-NOV-18:30 | 0.377439E+11 | 67960.67 | 23-NOV-01:00 |
| December | 0.100938E+12 | 65418.10 | 31-DEC-18:00 | 0.775868E+11 | 82216.58 | 31-DEC-22:10 |
| Annual Sum or Average | 0.129198E+13 | 0.378877E+12 | ||||
| Minimum of Months | 0.930818E+11 | 62943.22 | 0.00 | 0.00 | ||
| Maximum of Months | 0.136740E+12 | 88325.42 | 0.102967E+12 | 105858.87 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| INTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [J] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
| January | 0.840929E+10 | 0.517227E+10 | 0.389380E+11 | 0.00 | 0.808912E+10 | 0.00 | 0.00 | 6018987.90 | 0.00 | 0.00 | 0.00 | 0.424408E+11 | 0.00 |
| February | 0.760941E+10 | 0.433761E+10 | 0.351823E+11 | 0.00 | 0.731501E+10 | 0.00 | 0.00 | 1553576.11 | 0.00 | 0.00 | 0.00 | 0.386360E+11 | 0.00 |
| March | 0.845392E+10 | 0.434334E+10 | 0.389781E+11 | 0.00 | 0.623288E+10 | 0.00 | 0.00 | 0.125486E+09 | 0.00 | 0.00 | 0.00 | 0.420120E+11 | 0.00 |
| April | 0.814762E+10 | 0.374360E+10 | 0.376905E+11 | 0.00 | 0.541174E+10 | 0.00 | 0.00 | 0.169740E+10 | 0.00 | 0.00 | 0.00 | 0.389623E+11 | 0.00 |
| May | 0.843904E+10 | 0.346092E+10 | 0.389647E+11 | 0.00 | 0.658702E+10 | 0.00 | 0.00 | 0.724126E+10 | 0.00 | 0.00 | 0.00 | 0.379874E+11 | 0.00 |
| June | 0.817737E+10 | 0.313431E+10 | 0.377173E+11 | 0.00 | 0.106986E+11 | 0.00 | 0.00 | 0.229965E+11 | 0.00 | 0.00 | 0.00 | 0.347128E+11 | 0.00 |
| July | 0.840929E+10 | 0.333486E+10 | 0.389380E+11 | 0.00 | 0.145516E+11 | 0.00 | 0.00 | 0.370239E+11 | 0.00 | 0.00 | 0.00 | 0.344822E+11 | 0.00 |
| August | 0.845392E+10 | 0.368248E+10 | 0.389781E+11 | 0.00 | 0.140508E+11 | 0.00 | 0.00 | 0.354234E+11 | 0.00 | 0.00 | 0.00 | 0.341170E+11 | 0.00 |
| September | 0.814762E+10 | 0.400145E+10 | 0.376905E+11 | 0.00 | 0.930227E+10 | 0.00 | 0.00 | 0.178476E+11 | 0.00 | 0.00 | 0.00 | 0.337736E+11 | 0.00 |
| October | 0.842417E+10 | 0.461265E+10 | 0.389514E+11 | 0.00 | 0.652310E+10 | 0.00 | 0.00 | 0.694911E+10 | 0.00 | 0.00 | 0.00 | 0.366583E+11 | 0.00 |
| November | 0.814762E+10 | 0.488386E+10 | 0.376905E+11 | 0.00 | 0.580713E+10 | 0.00 | 0.00 | 0.400882E+09 | 0.00 | 0.00 | 0.00 | 0.377329E+11 | 0.00 |
| December | 0.840929E+10 | 0.527350E+10 | 0.389380E+11 | 0.00 | 0.723521E+10 | 0.00 | 0.00 | 14097533.78 | 0.00 | 0.00 | 0.00 | 0.410683E+11 | 0.00 |
| Annual Sum or Average | 0.992286E+11 | 0.499808E+11 | 0.458657E+12 | 0.00 | 0.101804E+12 | 0.00 | 0.00 | 0.129727E+12 | 0.00 | 0.00 | 0.00 | 0.452584E+12 | 0.00 |
| Minimum of Months | 0.760941E+10 | 0.313431E+10 | 0.351823E+11 | 0.00 | 0.541174E+10 | 0.00 | 0.00 | 1553576.11 | 0.00 | 0.00 | 0.00 | 0.337736E+11 | 0.00 |
| Maximum of Months | 0.845392E+10 | 0.527350E+10 | 0.389781E+11 | 0.00 | 0.145516E+11 | 0.00 | 0.00 | 0.370239E+11 | 0.00 | 0.00 | 0.00 | 0.424408E+11 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| INTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
| January | 0.00 | 0.00 | 0.102967E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.934239E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.480579E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.156957E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.608020E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 4524842.42 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.278857E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.377439E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.775868E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.378877E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.102967E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| INTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
| January | 5904.43 | 01-JAN-19:10 | 3183.33 | 01-JAN-00:10 | 22709.69 | 03-JAN-17:10 | 0.00 | 4922.27 | 02-JAN-00:10 | 0.00 | 0.00 | 01-JAN-00:10 |
| February | 5904.43 | 01-FEB-19:10 | 3183.33 | 01-FEB-00:10 | 22709.69 | 01-FEB-17:10 | 0.00 | 5329.93 | 06-FEB-01:10 | 0.00 | 0.00 | 01-FEB-00:10 |
| March | 5904.43 | 01-MAR-19:10 | 3183.33 | 01-MAR-00:10 | 22709.69 | 01-MAR-17:10 | 0.00 | 3922.25 | 22-MAR-05:00 | 0.00 | 0.00 | 01-MAR-00:10 |
| April | 5904.43 | 01-APR-18:10 | 3183.33 | 01-APR-00:10 | 22709.69 | 03-APR-16:10 | 0.00 | 4807.67 | 08-APR-11:00 | 0.00 | 0.00 | 01-APR-00:10 |
| May | 5904.43 | 01-MAY-18:10 | 3183.33 | 01-MAY-00:10 | 22709.69 | 01-MAY-16:10 | 0.00 | 6449.55 | 31-MAY-14:09 | 0.00 | 0.00 | 01-MAY-00:10 |
| June | 5904.43 | 01-JUN-18:10 | 3183.33 | 01-JUN-00:10 | 22709.69 | 01-JUN-16:10 | 0.00 | 8469.37 | 19-JUN-17:10 | 0.00 | 0.00 | 01-JUN-00:10 |
| July | 5904.43 | 01-JUL-18:10 | 3183.33 | 01-JUL-00:10 | 22709.69 | 03-JUL-16:10 | 0.00 | 8357.28 | 08-JUL-12:30 | 0.00 | 0.00 | 01-JUL-00:10 |
| August | 5904.43 | 01-AUG-18:10 | 3183.33 | 01-AUG-00:10 | 22709.69 | 01-AUG-16:10 | 0.00 | 8509.23 | 16-AUG-15:09 | 0.00 | 0.00 | 01-AUG-00:10 |
| September | 5904.43 | 01-SEP-18:10 | 3183.33 | 01-SEP-00:10 | 22709.69 | 01-SEP-16:10 | 0.00 | 7497.19 | 14-SEP-13:00 | 0.00 | 0.00 | 01-SEP-00:10 |
| October | 5904.43 | 01-OCT-18:10 | 3183.33 | 01-OCT-00:10 | 22709.69 | 02-OCT-16:10 | 0.00 | 6022.16 | 04-OCT-14:20 | 0.00 | 0.00 | 01-OCT-00:10 |
| November | 5904.43 | 01-NOV-18:10 | 3183.33 | 01-NOV-00:10 | 22709.69 | 01-NOV-16:10 | 0.00 | 4071.39 | 23-NOV-01:00 | 0.00 | 0.00 | 01-NOV-00:10 |
| December | 5904.43 | 01-DEC-19:10 | 3183.33 | 01-DEC-00:10 | 22709.69 | 01-DEC-17:10 | 0.00 | 4538.89 | 31-DEC-22:10 | 0.00 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 5904.43 | 3183.33 | 22709.69 | 0.00 | 3922.25 | 0.00 | 0.00 | |||||
| Maximum of Months | 5904.43 | 3183.33 | 22709.69 | 0.00 | 8509.23 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| COOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY {Maximum} [W] | HEATRECOVERY:ELECTRICITY {TIMESTAMP} | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
| January | 593.93 | 17-JAN-14:30 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 37846.59 | 25-JAN-07:40 | 0.00 |
| February | 124.72 | 20-FEB-15:09 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 36510.24 | 12-FEB-06:49 | 0.00 |
| March | 2324.85 | 03-MAR-14:20 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 37828.50 | 03-MAR-07:00 | 0.00 |
| April | 11190.91 | 07-APR-15:09 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 35315.03 | 08-APR-06:49 | 0.00 |
| May | 18119.99 | 31-MAY-14:09 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 33563.71 | 12-MAY-07:00 | 0.00 |
| June | 27872.00 | 19-JUN-11:00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 31205.61 | 25-JUN-06:30 | 0.00 |
| July | 26210.76 | 08-JUL-11:00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 29366.04 | 06-JUL-06:40 | 0.00 |
| August | 27801.05 | 16-AUG-15:09 | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 26655.90 | 15-AUG-06:19 | 0.00 |
| September | 23213.93 | 14-SEP-13:00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 28930.00 | 27-SEP-06:10 | 0.00 |
| October | 16062.80 | 04-OCT-14:09 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 32102.42 | 18-OCT-05:19 | 0.00 |
| November | 4398.80 | 02-NOV-12:50 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 32549.32 | 16-NOV-07:10 | 0.00 |
| December | 1145.98 | 17-DEC-14:20 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 34731.89 | 31-DEC-08:09 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
| Minimum of Months | 124.72 | 0.00 | 0.00 | 0.00 | 26655.90 | 0.00 | |||
| Maximum of Months | 27872.00 | 0.00 | 0.00 | 0.00 | 37846.59 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
| January | 72657.77 | 14-JAN-18:40 | 5231.74 | 22609.62 | 3183.33 | 0.00 | 4190.36 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 69638.93 | 06-FEB-18:40 | 5231.74 | 22609.62 | 3183.33 | 0.00 | 4179.85 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 69984.24 | 04-MAR-18:30 | 5231.74 | 22609.62 | 3183.33 | 0.00 | 1873.08 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 74197.81 | 07-APR-16:40 | 4289.87 | 22709.69 | 0.00 | 0.00 | 4656.19 | 0.00 | 0.00 | 10430.17 | 0.00 |
| May | 75554.29 | 30-MAY-16:19 | 4289.87 | 22709.69 | 0.00 | 0.00 | 6224.30 | 0.00 | 0.00 | 16415.53 | 0.00 |
| June | 88325.42 | 19-JUN-17:40 | 5231.74 | 22609.62 | 0.00 | 0.00 | 8357.96 | 0.00 | 0.00 | 25892.54 | 0.00 |
| July | 84176.27 | 06-JUL-17:40 | 5231.74 | 22609.62 | 0.00 | 0.00 | 7712.64 | 0.00 | 0.00 | 22469.95 | 0.00 |
| August | 83537.61 | 04-AUG-17:10 | 5231.74 | 22609.62 | 0.00 | 0.00 | 8100.27 | 0.00 | 0.00 | 24572.15 | 0.00 |
| September | 76097.19 | 07-SEP-16:00 | 4289.87 | 22709.69 | 0.00 | 0.00 | 6867.13 | 0.00 | 0.00 | 19062.10 | 0.00 |
| October | 74334.79 | 04-OCT-17:10 | 5231.74 | 22609.62 | 0.00 | 0.00 | 5091.26 | 0.00 | 0.00 | 11924.88 | 0.00 |
| November | 62943.22 | 15-NOV-18:30 | 5231.74 | 22609.62 | 3183.33 | 0.00 | 2263.52 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 65418.10 | 31-DEC-18:00 | 5231.74 | 22609.62 | 3183.33 | 0.00 | 3650.27 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
| Minimum of Months | 62943.22 | 4289.87 | 22609.62 | 0.00 | 0.00 | 1873.08 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 88325.42 | 5231.74 | 22709.69 | 3183.33 | 0.00 | 8357.96 | 0.00 | 0.00 | 25892.54 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| INTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | |
| January | 0.00 | 0.00 | 94160.03 | 02-JAN-00:10 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 105858.87 | 06-FEB-01:10 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 65606.35 | 22-MAR-07:10 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 37825.48 | 02-APR-05:00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 9991.24 | 01-MAY-04:00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 859.09 | 24-SEP-05:30 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 11919.44 | 28-OCT-04:00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 67960.67 | 23-NOV-01:00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 82216.58 | 31-DEC-22:10 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 105858.87 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: G SW APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: G NW APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: OFFICE
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: G NE APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: G N1 APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: G N2 APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: G S1 APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: G S2 APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: M SW APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: M NW APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: M SE APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: M NE APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: M N1 APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: M N2 APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: M S1 APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: M S2 APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: T SW APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: T NW APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: T SE APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: T NE APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: T N1 APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: T N2 APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: T S1 APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: T S2 APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: T CORRIDOR
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: G CORRIDOR
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: M CORRIDOR
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: G SW APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 533.00 | 21.10 | 438.67 | 21.10 | 438.67 | 21.10 |
| February | 473.00 | 21.11 | 443.00 | 21.10 | 443.00 | 21.10 |
| March | 506.00 | 21.15 | 232.33 | 21.13 | 232.33 | 21.13 |
| April | 493.00 | 21.60 | 113.33 | 21.50 | 113.33 | 21.44 |
| May | 442.67 | 22.55 | 21.33 | 22.61 | 6.00 | 22.62 |
| June | 199.00 | 23.97 | 363.67 | 23.98 | 170.33 | 23.98 |
| July | 226.67 | 24.00 | 531.33 | 24.00 | 226.67 | 24.00 |
| August | 68.00 | 24.00 | 453.50 | 24.00 | 68.00 | 24.00 |
| September | 59.33 | 23.93 | 321.00 | 23.99 | 31.83 | 23.99 |
| October | 225.50 | 23.48 | 198.17 | 23.72 | 7.67 | 23.72 |
| November | 501.33 | 21.78 | 108.50 | 21.66 | 108.50 | 21.57 |
| December | 533.00 | 21.13 | 382.17 | 21.12 | 382.17 | 21.11 |
| Annual Sum or Average | 4260.50 | 21.90 | 3607.00 | 22.23 | 2228.50 | 22.12 |
| Minimum of Months | 59.33 | 21.10 | 21.33 | 21.10 | 6.00 | 21.10 |
| Maximum of Months | 533.00 | 24.00 | 531.33 | 24.00 | 443.00 | 24.00 |
Report: ComfortReportSimple55Monthly
For: G NW APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 744.00 | 21.10 | 689.50 | 21.10 | 689.50 | 21.10 |
| February | 672.00 | 21.10 | 672.00 | 21.10 | 672.00 | 21.10 |
| March | 744.00 | 21.11 | 542.67 | 21.11 | 542.67 | 21.10 |
| April | 720.00 | 21.41 | 213.33 | 21.34 | 213.33 | 21.29 |
| May | 666.00 | 22.40 | 45.33 | 22.46 | 24.33 | 22.46 |
| June | 293.17 | 23.96 | 541.50 | 23.98 | 246.67 | 23.98 |
| July | 289.00 | 24.00 | 741.50 | 24.00 | 289.00 | 24.00 |
| August | 92.00 | 24.00 | 635.17 | 24.00 | 92.00 | 24.00 |
| September | 176.00 | 23.84 | 368.00 | 23.94 | 61.83 | 23.95 |
| October | 503.17 | 22.93 | 186.00 | 23.21 | 46.00 | 23.26 |
| November | 720.00 | 21.28 | 267.67 | 21.23 | 267.67 | 21.20 |
| December | 744.00 | 21.10 | 697.50 | 21.10 | 697.50 | 21.10 |
| Annual Sum or Average | 6363.33 | 21.82 | 5600.17 | 22.09 | 3842.50 | 21.99 |
| Minimum of Months | 92.00 | 21.10 | 45.33 | 21.10 | 24.33 | 21.10 |
| Maximum of Months | 744.00 | 24.00 | 741.50 | 24.00 | 697.50 | 24.00 |
Report: ComfortReportSimple55Monthly
For: OFFICE
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 140.00 | 20.95 | 125.83 | 20.94 | 125.83 | 20.94 |
| February | 133.00 | 20.94 | 132.33 | 20.94 | 132.33 | 20.94 |
| March | 161.00 | 21.28 | 99.33 | 21.13 | 99.33 | 21.06 |
| April | 129.00 | 22.52 | 20.00 | 22.33 | 18.17 | 22.15 |
| May | 68.33 | 23.55 | 39.83 | 23.80 | 0.00 | 23.80 |
| June | 15.17 | 25.30 | 147.50 | 24.34 | 15.17 | 24.43 |
| July | 22.50 | 25.32 | 140.00 | 24.39 | 22.50 | 24.51 |
| August | 11.67 | 25.41 | 161.00 | 24.32 | 11.67 | 24.39 |
| September | 8.83 | 25.42 | 140.00 | 24.30 | 8.83 | 24.37 |
| October | 11.67 | 24.17 | 102.67 | 24.21 | 1.50 | 24.22 |
| November | 102.17 | 21.88 | 33.83 | 21.70 | 30.33 | 21.54 |
| December | 140.00 | 21.08 | 104.17 | 21.01 | 104.17 | 20.98 |
| Annual Sum or Average | 943.33 | 21.84 | 1246.50 | 22.43 | 569.83 | 22.21 |
| Minimum of Months | 8.83 | 20.94 | 20.00 | 20.94 | 0.00 | 20.94 |
| Maximum of Months | 161.00 | 25.42 | 161.00 | 24.39 | 132.33 | 24.51 |
Report: ComfortReportSimple55Monthly
For: G NE APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 744.00 | 21.10 | 689.33 | 21.10 | 689.33 | 21.10 |
| February | 672.00 | 21.10 | 672.00 | 21.10 | 672.00 | 21.10 |
| March | 744.00 | 21.10 | 546.17 | 21.10 | 546.17 | 21.10 |
| April | 720.00 | 21.41 | 225.83 | 21.34 | 225.83 | 21.29 |
| May | 661.67 | 22.39 | 43.17 | 22.45 | 22.83 | 22.46 |
| June | 296.83 | 23.97 | 534.50 | 23.98 | 263.33 | 23.98 |
| July | 285.83 | 24.00 | 741.83 | 24.00 | 285.83 | 24.00 |
| August | 92.83 | 24.00 | 643.83 | 24.00 | 92.83 | 24.00 |
| September | 160.00 | 23.85 | 367.33 | 23.95 | 66.50 | 23.96 |
| October | 506.50 | 22.93 | 182.00 | 23.21 | 47.33 | 23.26 |
| November | 720.00 | 21.31 | 251.50 | 21.25 | 251.50 | 21.22 |
| December | 744.00 | 21.10 | 700.33 | 21.10 | 700.33 | 21.10 |
| Annual Sum or Average | 6347.67 | 21.82 | 5597.83 | 22.09 | 3863.83 | 21.99 |
| Minimum of Months | 92.83 | 21.10 | 43.17 | 21.10 | 22.83 | 21.10 |
| Maximum of Months | 744.00 | 24.00 | 741.83 | 24.00 | 700.33 | 24.00 |
Report: ComfortReportSimple55Monthly
For: G N1 APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 744.00 | 21.10 | 625.33 | 21.10 | 625.33 | 21.10 |
| February | 672.00 | 21.10 | 667.50 | 21.10 | 667.50 | 21.10 |
| March | 744.00 | 21.11 | 462.83 | 21.11 | 462.83 | 21.10 |
| April | 720.00 | 21.44 | 110.50 | 21.39 | 110.50 | 21.36 |
| May | 659.50 | 22.60 | 39.33 | 22.66 | 20.83 | 22.67 |
| June | 297.50 | 23.99 | 522.67 | 23.99 | 248.50 | 23.99 |
| July | 321.83 | 24.00 | 730.83 | 24.00 | 321.83 | 24.00 |
| August | 121.17 | 24.00 | 593.83 | 24.00 | 121.17 | 24.00 |
| September | 160.17 | 23.95 | 357.00 | 23.98 | 68.33 | 23.99 |
| October | 488.33 | 23.18 | 189.33 | 23.40 | 41.00 | 23.44 |
| November | 720.00 | 21.43 | 169.17 | 21.37 | 169.17 | 21.33 |
| December | 744.00 | 21.10 | 643.67 | 21.10 | 643.67 | 21.10 |
| Annual Sum or Average | 6392.50 | 21.90 | 5112.00 | 22.15 | 3500.67 | 22.07 |
| Minimum of Months | 121.17 | 21.10 | 39.33 | 21.10 | 20.83 | 21.10 |
| Maximum of Months | 744.00 | 24.00 | 730.83 | 24.00 | 667.50 | 24.00 |
Report: ComfortReportSimple55Monthly
For: G N2 APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 744.00 | 21.10 | 625.33 | 21.10 | 625.33 | 21.10 |
| February | 672.00 | 21.10 | 667.50 | 21.10 | 667.50 | 21.10 |
| March | 744.00 | 21.11 | 462.83 | 21.11 | 462.83 | 21.10 |
| April | 720.00 | 21.44 | 110.83 | 21.39 | 110.83 | 21.36 |
| May | 659.50 | 22.60 | 39.33 | 22.65 | 20.83 | 22.67 |
| June | 298.33 | 23.99 | 523.17 | 23.99 | 249.67 | 23.99 |
| July | 321.17 | 24.00 | 731.00 | 24.00 | 321.17 | 24.00 |
| August | 121.00 | 24.00 | 593.50 | 24.00 | 121.00 | 24.00 |
| September | 159.67 | 23.95 | 356.83 | 23.98 | 68.50 | 23.99 |
| October | 489.67 | 23.18 | 188.50 | 23.40 | 41.00 | 23.44 |
| November | 720.00 | 21.44 | 168.00 | 21.37 | 168.00 | 21.33 |
| December | 744.00 | 21.10 | 643.17 | 21.10 | 643.17 | 21.10 |
| Annual Sum or Average | 6393.33 | 21.90 | 5110.00 | 22.15 | 3499.83 | 22.07 |
| Minimum of Months | 121.00 | 21.10 | 39.33 | 21.10 | 20.83 | 21.10 |
| Maximum of Months | 744.00 | 24.00 | 731.00 | 24.00 | 667.50 | 24.00 |
Report: ComfortReportSimple55Monthly
For: G S1 APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 533.00 | 21.10 | 353.17 | 21.10 | 353.17 | 21.10 |
| February | 473.00 | 21.12 | 372.17 | 21.11 | 372.17 | 21.11 |
| March | 506.00 | 21.17 | 169.83 | 21.15 | 169.83 | 21.14 |
| April | 489.00 | 21.75 | 28.50 | 21.72 | 28.50 | 21.69 |
| May | 419.83 | 22.85 | 22.50 | 22.90 | 8.00 | 22.91 |
| June | 195.00 | 23.99 | 354.33 | 24.00 | 168.33 | 24.00 |
| July | 239.83 | 24.00 | 530.67 | 24.00 | 239.83 | 24.00 |
| August | 76.67 | 24.00 | 443.33 | 24.00 | 76.67 | 24.00 |
| September | 56.00 | 23.98 | 314.50 | 24.00 | 31.17 | 24.00 |
| October | 190.00 | 23.74 | 203.50 | 23.88 | 5.17 | 23.88 |
| November | 476.00 | 22.01 | 52.83 | 21.92 | 52.83 | 21.85 |
| December | 533.00 | 21.18 | 214.83 | 21.16 | 214.83 | 21.14 |
| Annual Sum or Average | 4187.33 | 21.99 | 3060.17 | 22.36 | 1720.50 | 22.29 |
| Minimum of Months | 56.00 | 21.10 | 22.50 | 21.10 | 5.17 | 21.10 |
| Maximum of Months | 533.00 | 24.00 | 530.67 | 24.00 | 372.17 | 24.00 |
Report: ComfortReportSimple55Monthly
For: G S2 APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 533.00 | 21.10 | 388.33 | 21.10 | 388.33 | 21.10 |
| February | 473.00 | 21.11 | 390.83 | 21.11 | 390.83 | 21.10 |
| March | 506.00 | 21.16 | 200.83 | 21.15 | 200.83 | 21.14 |
| April | 487.17 | 21.76 | 38.33 | 21.73 | 36.67 | 21.68 |
| May | 402.83 | 22.90 | 35.33 | 22.98 | 8.33 | 22.99 |
| June | 168.00 | 24.00 | 361.67 | 24.00 | 146.50 | 24.00 |
| July | 185.67 | 24.00 | 533.00 | 24.00 | 185.67 | 24.00 |
| August | 58.67 | 24.00 | 458.67 | 24.00 | 58.67 | 24.00 |
| September | 45.17 | 23.99 | 330.83 | 24.00 | 21.33 | 24.00 |
| October | 180.83 | 23.76 | 207.83 | 23.89 | 4.33 | 23.89 |
| November | 471.33 | 22.01 | 60.17 | 21.91 | 60.17 | 21.83 |
| December | 533.00 | 21.16 | 268.17 | 21.14 | 268.17 | 21.13 |
| Annual Sum or Average | 4044.67 | 21.93 | 3274.00 | 22.32 | 1769.83 | 22.22 |
| Minimum of Months | 45.17 | 21.10 | 35.33 | 21.10 | 4.33 | 21.10 |
| Maximum of Months | 533.00 | 24.00 | 533.00 | 24.00 | 390.83 | 24.00 |
Report: ComfortReportSimple55Monthly
For: M SW APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 533.00 | 21.12 | 322.17 | 21.11 | 322.17 | 21.11 |
| February | 473.00 | 21.19 | 299.00 | 21.15 | 299.00 | 21.14 |
| March | 504.50 | 21.48 | 76.83 | 21.43 | 76.83 | 21.39 |
| April | 402.67 | 22.14 | 24.83 | 22.23 | 2.33 | 22.23 |
| May | 170.83 | 23.55 | 99.67 | 23.71 | 1.33 | 23.72 |
| June | 101.00 | 24.00 | 398.83 | 24.00 | 89.00 | 24.00 |
| July | 178.83 | 24.00 | 529.83 | 24.00 | 178.83 | 24.00 |
| August | 64.33 | 24.00 | 445.17 | 24.00 | 64.33 | 24.00 |
| September | 78.83 | 23.93 | 315.33 | 23.98 | 38.50 | 23.98 |
| October | 258.00 | 23.35 | 180.67 | 23.61 | 13.50 | 23.63 |
| November | 494.67 | 21.72 | 92.00 | 21.62 | 92.00 | 21.55 |
| December | 533.00 | 21.20 | 265.33 | 21.17 | 265.33 | 21.15 |
| Annual Sum or Average | 3792.67 | 21.96 | 3049.67 | 22.42 | 1443.17 | 22.32 |
| Minimum of Months | 64.33 | 21.12 | 24.83 | 21.11 | 1.33 | 21.11 |
| Maximum of Months | 533.00 | 24.00 | 529.83 | 24.00 | 322.17 | 24.00 |
Report: ComfortReportSimple55Monthly
For: M NW APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 744.00 | 21.10 | 562.33 | 21.10 | 562.33 | 21.10 |
| February | 672.00 | 21.10 | 582.50 | 21.10 | 582.50 | 21.10 |
| March | 744.00 | 21.22 | 224.33 | 21.19 | 224.33 | 21.18 |
| April | 633.00 | 22.00 | 30.50 | 22.00 | 20.67 | 21.98 |
| May | 273.67 | 23.51 | 145.33 | 23.67 | 5.50 | 23.68 |
| June | 151.17 | 24.00 | 588.17 | 24.00 | 133.83 | 24.00 |
| July | 225.00 | 24.00 | 741.17 | 24.00 | 225.00 | 24.00 |
| August | 85.67 | 24.00 | 629.50 | 24.00 | 85.67 | 24.00 |
| September | 169.50 | 23.87 | 379.83 | 23.95 | 67.50 | 23.96 |
| October | 493.00 | 22.76 | 195.33 | 23.11 | 44.17 | 23.16 |
| November | 720.00 | 21.31 | 221.33 | 21.26 | 221.33 | 21.23 |
| December | 744.00 | 21.10 | 615.50 | 21.10 | 615.50 | 21.10 |
| Annual Sum or Average | 5655.00 | 21.83 | 4915.83 | 22.23 | 2788.33 | 22.11 |
| Minimum of Months | 85.67 | 21.10 | 30.50 | 21.10 | 5.50 | 21.10 |
| Maximum of Months | 744.00 | 24.00 | 741.17 | 24.00 | 615.50 | 24.00 |
Report: ComfortReportSimple55Monthly
For: M SE APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 533.00 | 21.11 | 321.00 | 21.11 | 321.00 | 21.10 |
| February | 473.00 | 21.19 | 298.00 | 21.16 | 298.00 | 21.14 |
| March | 506.00 | 21.44 | 85.17 | 21.39 | 85.17 | 21.35 |
| April | 404.83 | 22.15 | 23.67 | 22.23 | 2.83 | 22.22 |
| May | 178.33 | 23.55 | 95.83 | 23.70 | 2.00 | 23.70 |
| June | 122.83 | 24.00 | 389.83 | 24.00 | 111.67 | 24.00 |
| July | 193.67 | 24.00 | 530.50 | 24.00 | 193.67 | 24.00 |
| August | 69.33 | 24.00 | 444.17 | 24.00 | 69.33 | 24.00 |
| September | 82.67 | 23.93 | 315.50 | 23.98 | 42.17 | 23.99 |
| October | 272.50 | 23.38 | 179.17 | 23.62 | 17.00 | 23.64 |
| November | 495.67 | 21.76 | 87.50 | 21.66 | 87.50 | 21.59 |
| December | 533.00 | 21.21 | 260.33 | 21.17 | 260.33 | 21.15 |
| Annual Sum or Average | 3864.83 | 21.99 | 3030.67 | 22.43 | 1490.67 | 22.34 |
| Minimum of Months | 69.33 | 21.11 | 23.67 | 21.11 | 2.00 | 21.10 |
| Maximum of Months | 533.00 | 24.00 | 530.50 | 24.00 | 321.00 | 24.00 |
Report: ComfortReportSimple55Monthly
For: M NE APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 744.00 | 21.10 | 566.33 | 21.10 | 566.33 | 21.10 |
| February | 672.00 | 21.10 | 587.00 | 21.10 | 587.00 | 21.10 |
| March | 744.00 | 21.20 | 228.33 | 21.18 | 228.33 | 21.16 |
| April | 638.33 | 22.07 | 22.17 | 22.07 | 14.83 | 22.05 |
| May | 260.00 | 23.51 | 150.83 | 23.68 | 5.67 | 23.69 |
| June | 172.67 | 24.00 | 585.00 | 24.00 | 159.67 | 24.00 |
| July | 231.17 | 24.00 | 741.33 | 24.00 | 231.17 | 24.00 |
| August | 85.33 | 24.00 | 638.00 | 24.00 | 85.33 | 24.00 |
| September | 149.50 | 23.89 | 367.67 | 23.96 | 71.17 | 23.96 |
| October | 492.17 | 22.76 | 201.50 | 23.12 | 44.67 | 23.17 |
| November | 720.00 | 21.34 | 199.17 | 21.29 | 199.17 | 21.25 |
| December | 744.00 | 21.10 | 609.67 | 21.10 | 609.67 | 21.10 |
| Annual Sum or Average | 5653.17 | 21.83 | 4897.00 | 22.23 | 2803.00 | 22.12 |
| Minimum of Months | 85.33 | 21.10 | 22.17 | 21.10 | 5.67 | 21.10 |
| Maximum of Months | 744.00 | 24.00 | 741.33 | 24.00 | 609.67 | 24.00 |
Report: ComfortReportSimple55Monthly
For: M N1 APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 744.00 | 21.10 | 440.67 | 21.10 | 440.67 | 21.10 |
| February | 672.00 | 21.10 | 490.50 | 21.10 | 490.50 | 21.10 |
| March | 744.00 | 21.25 | 152.00 | 21.22 | 152.00 | 21.20 |
| April | 632.67 | 22.17 | 5.33 | 22.18 | 2.00 | 22.17 |
| May | 230.83 | 23.75 | 128.50 | 23.84 | 4.17 | 23.84 |
| June | 174.83 | 24.00 | 553.50 | 24.00 | 157.67 | 24.00 |
| July | 249.50 | 24.00 | 724.33 | 24.00 | 249.50 | 24.00 |
| August | 108.50 | 24.00 | 579.17 | 24.00 | 108.50 | 24.00 |
| September | 157.50 | 23.97 | 342.50 | 23.99 | 72.50 | 23.99 |
| October | 453.17 | 23.06 | 202.00 | 23.35 | 30.50 | 23.38 |
| November | 720.00 | 21.52 | 122.33 | 21.46 | 122.33 | 21.41 |
| December | 744.00 | 21.10 | 412.00 | 21.10 | 412.00 | 21.10 |
| Annual Sum or Average | 5631.00 | 21.91 | 4152.83 | 22.32 | 2242.33 | 22.24 |
| Minimum of Months | 108.50 | 21.10 | 5.33 | 21.10 | 2.00 | 21.10 |
| Maximum of Months | 744.00 | 24.00 | 724.33 | 24.00 | 490.50 | 24.00 |
Report: ComfortReportSimple55Monthly
For: M N2 APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 744.00 | 21.10 | 440.67 | 21.10 | 440.67 | 21.10 |
| February | 672.00 | 21.10 | 490.33 | 21.10 | 490.33 | 21.10 |
| March | 744.00 | 21.24 | 152.67 | 21.22 | 152.67 | 21.20 |
| April | 631.67 | 22.17 | 5.83 | 22.18 | 2.17 | 22.18 |
| May | 229.17 | 23.75 | 128.50 | 23.84 | 4.17 | 23.84 |
| June | 175.83 | 24.00 | 553.00 | 24.00 | 159.17 | 24.00 |
| July | 250.33 | 24.00 | 725.17 | 24.00 | 250.33 | 24.00 |
| August | 108.50 | 24.00 | 579.50 | 24.00 | 108.50 | 24.00 |
| September | 157.67 | 23.97 | 342.83 | 23.99 | 73.00 | 23.99 |
| October | 453.33 | 23.07 | 201.83 | 23.35 | 30.83 | 23.38 |
| November | 720.00 | 21.53 | 120.83 | 21.47 | 120.83 | 21.42 |
| December | 744.00 | 21.10 | 410.83 | 21.10 | 410.83 | 21.10 |
| Annual Sum or Average | 5630.50 | 21.92 | 4152.00 | 22.32 | 2243.50 | 22.24 |
| Minimum of Months | 108.50 | 21.10 | 5.83 | 21.10 | 2.17 | 21.10 |
| Maximum of Months | 744.00 | 24.00 | 725.17 | 24.00 | 490.33 | 24.00 |
Report: ComfortReportSimple55Monthly
For: M S1 APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 533.00 | 21.16 | 236.17 | 21.14 | 236.17 | 21.13 |
| February | 473.00 | 21.28 | 180.83 | 21.23 | 180.83 | 21.20 |
| March | 506.00 | 21.75 | 18.00 | 21.73 | 18.00 | 21.71 |
| April | 376.50 | 22.38 | 17.00 | 22.45 | 0.00 | 22.45 |
| May | 113.17 | 23.78 | 87.00 | 23.87 | 0.00 | 23.87 |
| June | 106.83 | 24.00 | 371.17 | 24.00 | 98.00 | 24.00 |
| July | 195.50 | 24.00 | 527.17 | 24.00 | 195.50 | 24.00 |
| August | 74.17 | 24.00 | 429.83 | 24.00 | 74.17 | 24.00 |
| September | 63.67 | 23.99 | 301.17 | 24.00 | 39.00 | 24.00 |
| October | 208.33 | 23.68 | 189.33 | 23.83 | 7.67 | 23.83 |
| November | 468.50 | 22.03 | 24.00 | 21.98 | 24.00 | 21.94 |
| December | 533.00 | 21.36 | 97.00 | 21.32 | 97.00 | 21.29 |
| Annual Sum or Average | 3651.67 | 22.09 | 2478.67 | 22.60 | 970.33 | 22.56 |
| Minimum of Months | 63.67 | 21.16 | 17.00 | 21.14 | 0.00 | 21.13 |
| Maximum of Months | 533.00 | 24.00 | 527.17 | 24.00 | 236.17 | 24.00 |
Report: ComfortReportSimple55Monthly
For: M S2 APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 533.00 | 21.16 | 236.17 | 21.14 | 236.17 | 21.13 |
| February | 473.00 | 21.28 | 180.50 | 21.23 | 180.50 | 21.20 |
| March | 506.00 | 21.74 | 18.17 | 21.72 | 18.17 | 21.70 |
| April | 375.83 | 22.38 | 17.17 | 22.45 | 0.00 | 22.45 |
| May | 114.17 | 23.78 | 86.67 | 23.87 | 0.00 | 23.87 |
| June | 109.00 | 24.00 | 371.00 | 24.00 | 100.00 | 24.00 |
| July | 196.50 | 24.00 | 527.00 | 24.00 | 196.50 | 24.00 |
| August | 74.33 | 24.00 | 429.00 | 24.00 | 74.33 | 24.00 |
| September | 63.83 | 23.99 | 301.33 | 24.00 | 39.17 | 24.00 |
| October | 208.83 | 23.67 | 189.33 | 23.83 | 7.67 | 23.83 |
| November | 466.67 | 22.02 | 23.33 | 21.98 | 23.33 | 21.94 |
| December | 533.00 | 21.36 | 96.67 | 21.32 | 96.67 | 21.29 |
| Annual Sum or Average | 3654.17 | 22.09 | 2476.33 | 22.60 | 972.50 | 22.57 |
| Minimum of Months | 63.83 | 21.16 | 17.17 | 21.14 | 0.00 | 21.13 |
| Maximum of Months | 533.00 | 24.00 | 527.00 | 24.00 | 236.17 | 24.00 |
Report: ComfortReportSimple55Monthly
For: T SW APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 533.00 | 21.11 | 477.33 | 21.11 | 477.33 | 21.10 |
| February | 472.83 | 21.18 | 419.00 | 21.14 | 419.00 | 21.13 |
| March | 495.50 | 21.30 | 240.83 | 21.24 | 239.67 | 21.20 |
| April | 440.83 | 21.67 | 152.67 | 21.65 | 126.17 | 21.56 |
| May | 326.83 | 22.48 | 84.50 | 22.78 | 7.33 | 22.78 |
| June | 215.67 | 23.80 | 377.83 | 23.91 | 167.17 | 23.92 |
| July | 247.83 | 24.00 | 527.50 | 24.00 | 247.83 | 24.00 |
| August | 112.50 | 23.92 | 431.17 | 23.98 | 94.83 | 23.99 |
| September | 217.83 | 23.26 | 275.17 | 23.66 | 61.17 | 23.70 |
| October | 386.33 | 22.27 | 177.83 | 22.51 | 91.17 | 22.46 |
| November | 504.33 | 21.29 | 266.17 | 21.23 | 264.17 | 21.20 |
| December | 531.33 | 21.17 | 464.00 | 21.14 | 464.00 | 21.12 |
| Annual Sum or Average | 4484.83 | 21.88 | 3894.00 | 22.16 | 2659.83 | 22.06 |
| Minimum of Months | 112.50 | 21.11 | 84.50 | 21.11 | 7.33 | 21.10 |
| Maximum of Months | 533.00 | 24.00 | 527.50 | 24.00 | 477.33 | 24.00 |
Report: ComfortReportSimple55Monthly
For: T NW APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 744.00 | 21.10 | 687.00 | 21.10 | 687.00 | 21.10 |
| February | 672.00 | 21.10 | 655.33 | 21.10 | 655.33 | 21.10 |
| March | 740.50 | 21.23 | 434.50 | 21.18 | 433.00 | 21.16 |
| April | 636.50 | 21.65 | 215.50 | 21.60 | 189.00 | 21.51 |
| May | 452.83 | 22.51 | 140.83 | 22.84 | 22.17 | 22.86 |
| June | 269.67 | 23.83 | 585.67 | 23.93 | 216.33 | 23.93 |
| July | 280.17 | 24.00 | 739.00 | 24.00 | 280.17 | 24.00 |
| August | 139.67 | 23.91 | 643.67 | 23.98 | 117.50 | 23.99 |
| September | 323.00 | 23.18 | 365.67 | 23.61 | 95.00 | 23.65 |
| October | 601.33 | 22.01 | 270.83 | 22.21 | 172.83 | 22.15 |
| November | 720.00 | 21.17 | 443.83 | 21.15 | 443.83 | 21.13 |
| December | 744.00 | 21.10 | 719.17 | 21.10 | 719.17 | 21.10 |
| Annual Sum or Average | 6323.67 | 21.78 | 5901.00 | 22.08 | 4031.33 | 21.97 |
| Minimum of Months | 139.67 | 21.10 | 140.83 | 21.10 | 22.17 | 21.10 |
| Maximum of Months | 744.00 | 24.00 | 739.00 | 24.00 | 719.17 | 24.00 |
Report: ComfortReportSimple55Monthly
For: T SE APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 533.00 | 21.11 | 480.33 | 21.10 | 480.33 | 21.10 |
| February | 473.00 | 21.18 | 416.33 | 21.14 | 416.33 | 21.13 |
| March | 498.33 | 21.27 | 256.67 | 21.21 | 256.67 | 21.19 |
| April | 443.83 | 21.66 | 158.33 | 21.64 | 132.17 | 21.54 |
| May | 333.83 | 22.49 | 74.67 | 22.75 | 7.00 | 22.76 |
| June | 231.67 | 23.83 | 378.00 | 23.92 | 184.83 | 23.92 |
| July | 252.00 | 24.00 | 528.50 | 24.00 | 252.00 | 24.00 |
| August | 118.17 | 23.92 | 426.83 | 23.98 | 101.50 | 23.99 |
| September | 220.67 | 23.28 | 270.67 | 23.67 | 64.50 | 23.70 |
| October | 394.67 | 22.28 | 173.00 | 22.50 | 95.00 | 22.45 |
| November | 504.17 | 21.30 | 259.33 | 21.24 | 256.83 | 21.21 |
| December | 531.00 | 21.17 | 465.67 | 21.14 | 465.67 | 21.13 |
| Annual Sum or Average | 4534.33 | 21.90 | 3888.33 | 22.15 | 2712.83 | 22.06 |
| Minimum of Months | 118.17 | 21.11 | 74.67 | 21.10 | 7.00 | 21.10 |
| Maximum of Months | 533.00 | 24.00 | 528.50 | 24.00 | 480.33 | 24.00 |
Report: ComfortReportSimple55Monthly
For: T NE APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 744.00 | 21.10 | 688.67 | 21.10 | 688.67 | 21.10 |
| February | 672.00 | 21.10 | 661.50 | 21.10 | 661.50 | 21.10 |
| March | 742.83 | 21.21 | 442.17 | 21.17 | 442.17 | 21.15 |
| April | 625.33 | 21.65 | 209.17 | 21.60 | 184.83 | 21.51 |
| May | 431.83 | 22.53 | 134.83 | 22.85 | 20.33 | 22.87 |
| June | 276.83 | 23.85 | 594.33 | 23.94 | 230.50 | 23.94 |
| July | 278.83 | 24.00 | 739.67 | 24.00 | 278.83 | 24.00 |
| August | 136.67 | 23.92 | 648.50 | 23.99 | 116.67 | 23.99 |
| September | 316.67 | 23.25 | 373.83 | 23.65 | 99.83 | 23.69 |
| October | 604.33 | 22.00 | 263.17 | 22.20 | 166.67 | 22.15 |
| November | 720.00 | 21.17 | 431.17 | 21.14 | 431.17 | 21.13 |
| December | 744.00 | 21.10 | 716.50 | 21.10 | 716.50 | 21.10 |
| Annual Sum or Average | 6293.33 | 21.78 | 5903.50 | 22.08 | 4037.67 | 21.97 |
| Minimum of Months | 136.67 | 21.10 | 134.83 | 21.10 | 20.33 | 21.10 |
| Maximum of Months | 744.00 | 24.00 | 739.67 | 24.00 | 716.50 | 24.00 |
Report: ComfortReportSimple55Monthly
For: T N1 APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 744.00 | 21.10 | 663.00 | 21.10 | 663.00 | 21.10 |
| February | 672.00 | 21.10 | 661.00 | 21.10 | 661.00 | 21.10 |
| March | 743.17 | 21.21 | 370.00 | 21.18 | 370.00 | 21.16 |
| April | 657.33 | 21.78 | 141.67 | 21.71 | 129.00 | 21.62 |
| May | 425.00 | 22.79 | 100.00 | 23.01 | 18.00 | 23.04 |
| June | 266.67 | 23.92 | 574.67 | 23.96 | 224.00 | 23.97 |
| July | 275.67 | 24.00 | 739.00 | 24.00 | 275.67 | 24.00 |
| August | 131.33 | 23.96 | 626.83 | 23.99 | 118.33 | 23.99 |
| September | 300.67 | 23.43 | 348.83 | 23.73 | 89.50 | 23.76 |
| October | 605.00 | 22.15 | 237.83 | 22.33 | 151.83 | 22.30 |
| November | 720.00 | 21.19 | 368.67 | 21.16 | 368.67 | 21.14 |
| December | 744.00 | 21.10 | 704.83 | 21.10 | 704.83 | 21.10 |
| Annual Sum or Average | 6284.83 | 21.83 | 5536.33 | 22.11 | 3773.83 | 22.01 |
| Minimum of Months | 131.33 | 21.10 | 100.00 | 21.10 | 18.00 | 21.10 |
| Maximum of Months | 744.00 | 24.00 | 739.00 | 24.00 | 704.83 | 24.00 |
Report: ComfortReportSimple55Monthly
For: T N2 APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 744.00 | 21.10 | 663.17 | 21.10 | 663.17 | 21.10 |
| February | 672.00 | 21.10 | 660.83 | 21.10 | 660.83 | 21.10 |
| March | 744.00 | 21.21 | 370.33 | 21.18 | 370.33 | 21.16 |
| April | 656.50 | 21.79 | 142.50 | 21.71 | 129.67 | 21.62 |
| May | 423.33 | 22.78 | 100.50 | 23.01 | 17.83 | 23.04 |
| June | 268.50 | 23.92 | 573.83 | 23.96 | 226.17 | 23.97 |
| July | 275.50 | 24.00 | 739.00 | 24.00 | 275.50 | 24.00 |
| August | 131.33 | 23.96 | 626.67 | 23.99 | 118.33 | 23.99 |
| September | 300.33 | 23.44 | 349.33 | 23.73 | 89.67 | 23.76 |
| October | 604.50 | 22.14 | 236.17 | 22.32 | 151.50 | 22.29 |
| November | 720.00 | 21.19 | 367.33 | 21.16 | 367.33 | 21.15 |
| December | 744.00 | 21.10 | 703.67 | 21.10 | 703.67 | 21.10 |
| Annual Sum or Average | 6284.00 | 21.83 | 5533.33 | 22.11 | 3774.00 | 22.01 |
| Minimum of Months | 131.33 | 21.10 | 100.50 | 21.10 | 17.83 | 21.10 |
| Maximum of Months | 744.00 | 24.00 | 739.00 | 24.00 | 703.67 | 24.00 |
Report: ComfortReportSimple55Monthly
For: T S1 APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 533.00 | 21.13 | 435.33 | 21.11 | 435.33 | 21.11 |
| February | 473.00 | 21.22 | 397.17 | 21.16 | 397.17 | 21.14 |
| March | 498.67 | 21.37 | 192.50 | 21.29 | 192.50 | 21.25 |
| April | 437.00 | 21.83 | 93.50 | 21.81 | 73.00 | 21.72 |
| May | 301.50 | 22.81 | 63.33 | 23.01 | 5.33 | 23.02 |
| June | 208.83 | 23.90 | 375.33 | 23.95 | 169.67 | 23.96 |
| July | 243.67 | 24.00 | 527.33 | 24.00 | 243.67 | 24.00 |
| August | 100.83 | 23.96 | 426.00 | 23.99 | 92.67 | 23.99 |
| September | 174.67 | 23.50 | 276.00 | 23.80 | 53.33 | 23.82 |
| October | 360.83 | 22.56 | 153.00 | 22.84 | 58.83 | 22.83 |
| November | 503.67 | 21.42 | 194.67 | 21.34 | 192.33 | 21.29 |
| December | 530.67 | 21.21 | 414.33 | 21.16 | 414.33 | 21.14 |
| Annual Sum or Average | 4366.33 | 21.96 | 3548.50 | 22.24 | 2328.17 | 22.15 |
| Minimum of Months | 100.83 | 21.13 | 63.33 | 21.11 | 5.33 | 21.11 |
| Maximum of Months | 533.00 | 24.00 | 527.33 | 24.00 | 435.33 | 24.00 |
Report: ComfortReportSimple55Monthly
For: T S2 APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 533.00 | 21.13 | 435.50 | 21.11 | 435.50 | 21.11 |
| February | 473.00 | 21.22 | 397.83 | 21.16 | 397.83 | 21.14 |
| March | 498.83 | 21.37 | 193.50 | 21.29 | 193.50 | 21.25 |
| April | 437.50 | 21.83 | 94.00 | 21.81 | 73.83 | 21.72 |
| May | 301.50 | 22.80 | 63.67 | 23.00 | 5.33 | 23.02 |
| June | 210.33 | 23.90 | 374.83 | 23.95 | 171.17 | 23.96 |
| July | 244.33 | 24.00 | 527.33 | 24.00 | 244.33 | 24.00 |
| August | 101.67 | 23.96 | 425.67 | 23.99 | 93.33 | 23.99 |
| September | 175.17 | 23.50 | 276.33 | 23.80 | 53.50 | 23.82 |
| October | 361.17 | 22.56 | 153.00 | 22.84 | 59.17 | 22.83 |
| November | 503.67 | 21.42 | 194.67 | 21.34 | 192.33 | 21.29 |
| December | 530.50 | 21.20 | 414.17 | 21.16 | 414.17 | 21.14 |
| Annual Sum or Average | 4370.67 | 21.96 | 3550.50 | 22.24 | 2334.00 | 22.15 |
| Minimum of Months | 101.67 | 21.13 | 63.67 | 21.11 | 5.33 | 21.11 |
| Maximum of Months | 533.00 | 24.00 | 527.33 | 24.00 | 435.50 | 24.00 |
Report: ComfortReportSimple55Monthly
For: T CORRIDOR
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 744.00 | 20.04 | 469.00 | 19.88 | 469.00 | 19.82 |
| February | 672.00 | 20.13 | 428.00 | 19.95 | 428.00 | 19.86 |
| March | 733.33 | 21.27 | 251.17 | 21.18 | 251.17 | 21.13 |
| April | 701.50 | 22.63 | 360.00 | 22.99 | 350.00 | 23.15 |
| May | 732.67 | 24.55 | 719.00 | 24.58 | 709.00 | 24.59 |
| June | 720.00 | 25.90 | 720.00 | 25.90 | 720.00 | 25.90 |
| July | 744.00 | 26.35 | 744.00 | 26.35 | 744.00 | 26.35 |
| August | 744.00 | 26.29 | 744.00 | 26.29 | 744.00 | 26.29 |
| September | 720.00 | 25.38 | 720.00 | 25.38 | 720.00 | 25.38 |
| October | 703.17 | 23.70 | 547.00 | 23.90 | 532.50 | 23.98 |
| November | 714.50 | 21.18 | 298.67 | 21.15 | 298.67 | 21.13 |
| December | 744.00 | 20.35 | 420.50 | 20.20 | 420.50 | 20.14 |
| Annual Sum or Average | 8673.17 | 23.17 | 6421.33 | 23.45 | 6386.83 | 23.57 |
| Minimum of Months | 672.00 | 20.04 | 251.17 | 19.88 | 251.17 | 19.82 |
| Maximum of Months | 744.00 | 26.35 | 744.00 | 26.35 | 744.00 | 26.35 |
Report: ComfortReportSimple55Monthly
For: G CORRIDOR
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 744.00 | 17.47 | 732.67 | 17.45 | 732.67 | 17.44 |
| February | 672.00 | 17.28 | 672.00 | 17.28 | 672.00 | 17.28 |
| March | 744.00 | 18.80 | 628.83 | 18.61 | 628.83 | 18.55 |
| April | 713.83 | 20.61 | 288.83 | 20.12 | 288.83 | 19.85 |
| May | 604.17 | 22.52 | 194.33 | 22.91 | 121.50 | 22.96 |
| June | 492.67 | 25.59 | 688.83 | 25.62 | 483.00 | 25.64 |
| July | 709.33 | 26.50 | 744.00 | 26.51 | 709.33 | 26.50 |
| August | 540.67 | 26.79 | 740.33 | 26.71 | 540.00 | 26.73 |
| September | 363.33 | 25.43 | 619.17 | 25.58 | 316.00 | 25.66 |
| October | 498.67 | 23.21 | 354.33 | 23.77 | 189.00 | 23.88 |
| November | 719.00 | 20.18 | 348.00 | 19.59 | 348.00 | 19.29 |
| December | 744.00 | 18.35 | 716.00 | 18.29 | 716.00 | 18.28 |
| Annual Sum or Average | 7545.67 | 21.44 | 6727.33 | 21.65 | 5745.17 | 21.54 |
| Minimum of Months | 363.33 | 17.28 | 194.33 | 17.28 | 121.50 | 17.28 |
| Maximum of Months | 744.00 | 26.79 | 744.00 | 26.71 | 732.67 | 26.73 |
Report: ComfortReportSimple55Monthly
For: M CORRIDOR
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 744.00 | 21.64 | 196.17 | 21.71 | 196.17 | 21.75 |
| February | 672.00 | 21.80 | 170.00 | 21.88 | 170.00 | 21.93 |
| March | 737.17 | 22.53 | 388.33 | 22.60 | 388.33 | 22.63 |
| April | 680.17 | 23.80 | 648.17 | 23.89 | 608.33 | 23.90 |
| May | 744.00 | 25.53 | 744.00 | 25.53 | 744.00 | 25.53 |
| June | 720.00 | 25.99 | 720.00 | 25.99 | 720.00 | 25.99 |
| July | 744.00 | 26.16 | 744.00 | 26.16 | 744.00 | 26.16 |
| August | 744.00 | 26.19 | 744.00 | 26.19 | 744.00 | 26.19 |
| September | 720.00 | 25.83 | 720.00 | 25.83 | 720.00 | 25.83 |
| October | 679.83 | 25.17 | 735.33 | 25.15 | 679.83 | 25.16 |
| November | 710.17 | 22.79 | 451.33 | 22.98 | 441.83 | 23.07 |
| December | 744.00 | 21.91 | 288.67 | 21.94 | 288.67 | 21.95 |
| Annual Sum or Average | 8639.33 | 24.12 | 6550.00 | 24.45 | 6445.17 | 24.58 |
| Minimum of Months | 672.00 | 21.64 | 170.00 | 21.71 | 170.00 | 21.75 |
| Maximum of Months | 744.00 | 26.19 | 744.00 | 26.19 | 744.00 | 26.19 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_GSW
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 515.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 492.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 524.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 6145.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_GNW
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 8760.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_OFFICE
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 140.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 133.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 161.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 140.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 154.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 154.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 140.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 161.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 140.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 147.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 140.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 140.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 1750.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 133.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 161.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_GNE
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 8760.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_GN1
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 8760.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_GN2
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 8760.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_GS1
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 515.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 492.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 524.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 6145.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_GS2
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 515.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 492.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 524.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 6145.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_MSW
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 515.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 492.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 524.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 6145.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_MNW
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 8760.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_MSE
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 515.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 492.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 524.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 6145.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_MNE
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 8760.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_MN1
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 8760.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_MN2
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 8760.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_MS1
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 515.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 492.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 524.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 6145.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_MS2
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 515.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 492.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 524.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 6145.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_TSW
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 515.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 492.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 524.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 6145.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_TNW
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 8760.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_TSE
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 515.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 492.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 524.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 6145.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_TNE
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 8760.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_TN1
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 8760.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_TN2
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 8760.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_TS1
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 515.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 492.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 524.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 6145.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_TS2
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 515.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 492.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 524.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 6145.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_T CORRIDOR
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 8760.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_G CORRIDOR
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 8760.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_M CORRIDOR
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 8760.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: DXReportMonthly
For: SPLIT GSW COOLING COIL
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
| April | 53729176.49 | 13964994.10 | 41.33 | 51095703.65 | 2633472.84 | 0.00 | 0.16 | 07-APR-16:10 | 0.00 | 01-APR-00:10 | 809.08 | 07-APR-16:10 | 809.08 | 07-APR-16:10 | 64.47 | 09-APR-17:30 | 213.18 | 07-APR-16:10 | 0.00 | 01-APR-00:10 |
| May | 0.334809E+09 | 86171245.52 | 167.71 | 0.308624E+09 | 26185550.30 | 0.00 | 0.34 | 31-MAY-14:10 | 0.00 | 01-MAY-00:10 | 1863.73 | 31-MAY-14:10 | 1736.44 | 30-MAY-16:05 | 359.38 | 31-MAY-17:50 | 475.28 | 31-MAY-14:10 | 0.00 | 01-MAY-00:10 |
| June | 0.236916E+10 | 0.589500E+09 | 665.59 | 0.181591E+10 | 0.553250E+09 | 0.00 | 0.53 | 19-JUN-17:10 | 0.00 | 01-JUN-04:00 | 2933.87 | 19-JUN-17:10 | 2374.52 | 19-JUN-17:10 | 715.26 | 27-JUN-16:10 | 800.47 | 19-JUN-17:10 | 0.00 | 01-JUN-00:10 |
| July | 0.438156E+10 | 0.108488E+10 | 744.00 | 0.318917E+10 | 0.119239E+10 | 0.00 | 0.52 | 09-JUL-14:00 | 0.05 | 01-JUL-05:05 | 3021.17 | 21-JUL-16:02 | 2408.39 | 10-JUL-15:10 | 844.09 | 21-JUL-14:30 | 787.35 | 09-JUL-14:00 | 0.00 | 01-JUL-00:10 |
| August | 0.458013E+10 | 0.115226E+10 | 743.33 | 0.368278E+10 | 0.897353E+09 | 0.00 | 0.59 | 16-AUG-15:10 | 0.00 | 08-AUG-05:15 | 3381.48 | 16-AUG-16:10 | 2795.47 | 18-AUG-16:03 | 888.15 | 03-AUG-15:10 | 889.04 | 16-AUG-15:10 | 0.00 | 01-AUG-00:10 |
| September | 0.259279E+10 | 0.643014E+09 | 653.24 | 0.219653E+10 | 0.396253E+09 | 0.00 | 0.55 | 07-SEP-15:10 | 0.00 | 16-SEP-07:00 | 3178.68 | 07-SEP-15:10 | 2655.56 | 01-SEP-14:30 | 755.88 | 14-SEP-10:10 | 771.84 | 07-SEP-15:10 | 0.00 | 01-SEP-00:10 |
| October | 0.132755E+10 | 0.330864E+09 | 509.10 | 0.114082E+10 | 0.186728E+09 | 0.00 | 0.44 | 04-OCT-15:10 | 0.00 | 01-OCT-01:40 | 2485.47 | 04-OCT-15:30 | 2192.12 | 04-OCT-15:10 | 513.51 | 25-OCT-10:30 | 597.17 | 04-OCT-15:20 | 0.00 | 01-OCT-00:10 |
| November | 39094080.50 | 10247291.08 | 42.08 | 39082431.20 | 11649.31 | 0.00 | 0.14 | 03-NOV-15:50 | 0.00 | 01-NOV-00:10 | 691.20 | 03-NOV-15:50 | 691.20 | 03-NOV-15:50 | 3.97 | 04-NOV-15:20 | 179.44 | 03-NOV-15:50 | 0.00 | 01-NOV-00:10 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.156788E+11 | 0.391090E+10 | 3566.39 | 0.124240E+11 | 0.325481E+10 | 0.00 | ||||||||||||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Maximum of Months | 0.458013E+10 | 0.115226E+10 | 744.00 | 0.368278E+10 | 0.119239E+10 | 0.00 | 0.59 | 0.05 | 3381.48 | 2795.47 | 888.15 | 889.04 | 0.00 |
Report: DXReportMonthly
For: SPLIT GNW COOLING COIL
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 |
| May | 0.235761E+09 | 60631769.01 | 118.92 | 0.212553E+09 | 23208195.47 | 0.00 | 0.31 | 31-MAY-16:20 | 0.00 | 01-MAY-00:10 | 1663.16 | 31-MAY-16:20 | 1528.51 | 30-MAY-16:05 | 338.69 | 31-MAY-17:50 | 411.09 | 30-MAY-16:10 | 0.00 | 01-MAY-00:10 |
| June | 0.218539E+10 | 0.543201E+09 | 655.40 | 0.165304E+10 | 0.532345E+09 | 0.00 | 0.54 | 19-JUN-17:20 | 0.00 | 01-JUN-03:20 | 2878.29 | 19-JUN-17:20 | 2294.60 | 19-JUN-17:17 | 709.30 | 27-JUN-16:10 | 780.66 | 19-JUN-17:10 | 0.00 | 01-JUN-00:10 |
| July | 0.411381E+10 | 0.101751E+10 | 744.00 | 0.295744E+10 | 0.115637E+10 | 0.00 | 0.52 | 06-JUL-17:25 | 0.06 | 01-JUL-05:05 | 2870.77 | 06-JUL-17:13 | 2152.99 | 10-JUL-16:03 | 852.66 | 20-JUL-16:02 | 716.12 | 13-JUL-16:04 | 0.00 | 01-JUL-00:10 |
| August | 0.393171E+10 | 0.991099E+09 | 741.83 | 0.308454E+10 | 0.847166E+09 | 0.00 | 0.56 | 16-AUG-16:07 | 0.00 | 08-AUG-05:15 | 3050.42 | 16-AUG-16:07 | 2394.24 | 18-AUG-16:30 | 886.05 | 03-AUG-16:02 | 791.96 | 16-AUG-16:07 | 0.00 | 01-AUG-00:10 |
| September | 0.182440E+10 | 0.453407E+09 | 572.86 | 0.148324E+10 | 0.341162E+09 | 0.00 | 0.45 | 07-SEP-16:02 | 0.00 | 10-SEP-05:15 | 2500.48 | 07-SEP-16:02 | 1914.47 | 14-SEP-16:04 | 673.39 | 07-SEP-15:10 | 608.03 | 07-SEP-16:02 | 0.00 | 01-SEP-00:10 |
| October | 0.352708E+09 | 87640640.51 | 225.99 | 0.278017E+09 | 74691800.18 | 0.00 | 0.29 | 04-OCT-16:10 | 0.00 | 01-OCT-00:10 | 1564.13 | 04-OCT-16:10 | 1245.84 | 04-OCT-16:10 | 374.00 | 05-OCT-16:10 | 379.71 | 04-OCT-16:10 | 0.00 | 01-OCT-00:10 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.126438E+11 | 0.315349E+10 | 3059.00 | 0.966883E+10 | 0.297495E+10 | 0.00 | ||||||||||||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Maximum of Months | 0.411381E+10 | 0.101751E+10 | 744.00 | 0.308454E+10 | 0.115637E+10 | 0.00 | 0.56 | 0.06 | 3050.42 | 2394.24 | 886.05 | 791.96 | 0.00 |
Report: DXReportMonthly
For: SPLIT OFFICE COOLING COIL
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
| April | 0.145700E+09 | 37708442.18 | 59.11 | 0.141940E+09 | 3760072.64 | 0.00 | 0.69 | 10-APR-08:63 | 0.00 | 01-APR-00:10 | 4721.32 | 10-APR-08:63 | 4070.29 | 10-APR-08:63 | 651.02 | 10-APR-08:63 | 1083.44 | 10-APR-08:63 | 0.00 | 01-APR-00:10 |
| May | 0.618647E+09 | 0.156199E+09 | 146.24 | 0.565630E+09 | 53016993.62 | 0.00 | 1.00 | 18-MAY-08:62 | 0.00 | 01-MAY-00:10 | 7382.01 | 23-MAY-08:62 | 7051.49 | 30-MAY-07:02 | 1719.21 | 23-MAY-08:62 | 1592.06 | 30-MAY-08:62 | 0.00 | 01-MAY-00:10 |
| June | 0.204726E+10 | 0.499296E+09 | 208.25 | 0.166293E+10 | 0.384329E+09 | 0.00 | 1.00 | 01-JUN-08:62 | 0.00 | 01-JUN-00:10 | 7993.66 | 19-JUN-07:02 | 6915.87 | 09-JUN-08:62 | 3343.00 | 19-JUN-07:03 | 1732.81 | 19-JUN-08:62 | 0.00 | 01-JUN-00:10 |
| July | 0.290348E+10 | 0.702599E+09 | 250.95 | 0.224861E+10 | 0.654868E+09 | 0.00 | 1.00 | 03-JUL-07:02 | 0.00 | 01-JUL-00:10 | 8083.21 | 28-JUL-07:02 | 7192.97 | 11-JUL-07:02 | 4153.12 | 20-JUL-07:05 | 1675.52 | 14-JUL-08:62 | 0.00 | 01-JUL-00:10 |
| August | 0.342857E+10 | 0.838369E+09 | 298.44 | 0.287056E+10 | 0.558007E+09 | 0.00 | 1.00 | 01-AUG-07:02 | 0.00 | 01-AUG-00:10 | 8070.42 | 03-AUG-07:02 | 7213.46 | 23-AUG-07:02 | 4131.60 | 17-AUG-07:05 | 1694.99 | 02-AUG-08:15 | 0.00 | 01-AUG-00:10 |
| September | 0.209504E+10 | 0.503251E+09 | 221.42 | 0.181716E+10 | 0.277880E+09 | 0.00 | 1.00 | 01-SEP-07:02 | 0.00 | 01-SEP-00:10 | 8033.03 | 14-SEP-07:02 | 7123.54 | 12-SEP-07:02 | 3666.88 | 14-SEP-07:03 | 1632.41 | 01-SEP-08:62 | 0.00 | 01-SEP-00:10 |
| October | 0.140888E+10 | 0.343677E+09 | 181.68 | 0.125512E+10 | 0.153763E+09 | 0.00 | 1.00 | 02-OCT-08:62 | 0.00 | 01-OCT-00:10 | 7613.96 | 06-OCT-07:03 | 6952.16 | 16-OCT-08:62 | 2165.01 | 06-OCT-08:62 | 1576.42 | 06-OCT-08:62 | 0.00 | 01-OCT-00:10 |
| November | 0.185805E+09 | 48121686.70 | 62.83 | 0.181101E+09 | 4704012.03 | 0.00 | 0.38 | 10-NOV-09:05 | 0.00 | 01-NOV-00:10 | 2534.58 | 10-NOV-09:05 | 1899.92 | 10-NOV-09:05 | 634.66 | 10-NOV-09:05 | 603.49 | 10-NOV-09:05 | 0.00 | 01-NOV-00:10 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.128334E+11 | 0.312922E+10 | 1428.93 | 0.107431E+11 | 0.209033E+10 | 0.00 | ||||||||||||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Maximum of Months | 0.342857E+10 | 0.838369E+09 | 298.44 | 0.287056E+10 | 0.654868E+09 | 0.00 | 1.00 | 0.00 | 8083.21 | 7213.46 | 4153.12 | 1732.81 | 0.00 |
Report: DXReportMonthly
For: SPLIT GNE COOLING COIL
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
| April | 17347.38 | 4532.15 | 0.17 | 16101.40 | 1245.97 | 0.00 | 0.01 | 08-APR-12:00 | 0.00 | 01-APR-00:10 | 28.91 | 08-APR-12:00 | 26.84 | 08-APR-12:00 | 2.08 | 08-APR-12:00 | 7.55 | 08-APR-12:00 | 0.00 | 01-APR-00:10 |
| May | 0.259238E+09 | 66536757.79 | 121.24 | 0.234391E+09 | 24847343.64 | 0.00 | 0.30 | 31-MAY-10:10 | 0.00 | 01-MAY-00:10 | 1494.34 | 31-MAY-10:00 | 1342.79 | 30-MAY-13:00 | 291.17 | 31-MAY-17:50 | 376.81 | 31-MAY-14:00 | 0.00 | 01-MAY-00:10 |
| June | 0.210012E+10 | 0.521856E+09 | 658.97 | 0.158718E+10 | 0.512946E+09 | 0.00 | 0.51 | 19-JUN-11:00 | 0.00 | 01-JUN-03:10 | 2519.74 | 19-JUN-17:10 | 1976.53 | 19-JUN-17:05 | 713.26 | 19-JUN-08:40 | 710.95 | 19-JUN-11:00 | 0.00 | 01-JUN-00:10 |
| July | 0.409052E+10 | 0.100941E+10 | 744.00 | 0.293728E+10 | 0.115324E+10 | 0.00 | 0.53 | 08-JUL-12:00 | 0.06 | 01-JUL-04:00 | 2700.06 | 08-JUL-12:00 | 2018.85 | 10-JUL-15:10 | 800.51 | 20-JUL-16:02 | 717.63 | 08-JUL-12:00 | 0.00 | 01-JUL-00:10 |
| August | 0.391219E+10 | 0.983566E+09 | 741.39 | 0.306547E+10 | 0.846723E+09 | 0.00 | 0.55 | 04-AUG-19:00 | 0.00 | 08-AUG-05:15 | 2790.61 | 04-AUG-19:00 | 2116.81 | 24-AUG-16:50 | 838.50 | 03-AUG-16:02 | 754.71 | 04-AUG-19:00 | 0.00 | 01-AUG-00:10 |
| September | 0.182341E+10 | 0.452444E+09 | 587.43 | 0.148353E+10 | 0.339875E+09 | 0.00 | 0.41 | 14-SEP-14:00 | 0.00 | 10-SEP-05:15 | 2073.15 | 07-SEP-15:10 | 1712.79 | 01-SEP-15:10 | 712.57 | 14-SEP-10:00 | 541.92 | 14-SEP-14:00 | 0.00 | 01-SEP-00:10 |
| October | 0.328269E+09 | 81420483.42 | 213.08 | 0.257262E+09 | 71006481.15 | 0.00 | 0.28 | 25-OCT-10:30 | 0.00 | 01-OCT-00:10 | 1424.15 | 25-OCT-10:30 | 1034.44 | 04-OCT-13:00 | 398.98 | 25-OCT-10:30 | 343.31 | 25-OCT-10:40 | 0.00 | 01-OCT-00:10 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.125138E+11 | 0.311524E+10 | 3066.28 | 0.956513E+10 | 0.294864E+10 | 0.00 | ||||||||||||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Maximum of Months | 0.409052E+10 | 0.100941E+10 | 744.00 | 0.306547E+10 | 0.115324E+10 | 0.00 | 0.55 | 0.06 | 2790.61 | 2116.81 | 838.50 | 754.71 | 0.00 |
Report: DXReportMonthly
For: SPLIT GN1 COOLING COIL
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 |
| May | 0.206158E+09 | 53009791.53 | 122.95 | 0.184519E+09 | 21639118.80 | 0.00 | 0.26 | 31-MAY-14:10 | 0.00 | 01-MAY-00:10 | 1171.16 | 31-MAY-14:10 | 1074.00 | 30-MAY-16:08 | 259.39 | 31-MAY-17:50 | 300.48 | 31-MAY-14:10 | 0.00 | 01-MAY-00:10 |
| June | 0.195241E+10 | 0.484002E+09 | 689.57 | 0.145565E+10 | 0.496760E+09 | 0.00 | 0.48 | 19-JUN-17:20 | 0.00 | 01-JUN-05:40 | 2163.35 | 19-JUN-17:25 | 1680.41 | 19-JUN-17:17 | 619.88 | 27-JUN-16:10 | 591.07 | 19-JUN-17:10 | 0.00 | 01-JUN-00:10 |
| July | 0.359719E+10 | 0.886566E+09 | 744.00 | 0.254703E+10 | 0.105016E+10 | 0.00 | 0.47 | 08-JUL-12:00 | 0.08 | 02-JUL-05:10 | 2191.39 | 20-JUL-17:10 | 1634.28 | 10-JUL-17:35 | 714.99 | 20-JUL-17:10 | 580.31 | 08-JUL-12:00 | 0.00 | 01-JUL-00:10 |
| August | 0.330429E+10 | 0.831221E+09 | 742.28 | 0.254749E+10 | 0.756799E+09 | 0.00 | 0.53 | 04-AUG-19:00 | 0.00 | 08-AUG-05:15 | 2394.59 | 04-AUG-19:00 | 1742.80 | 04-AUG-19:00 | 739.34 | 03-AUG-16:02 | 648.98 | 04-AUG-19:00 | 0.00 | 01-AUG-00:10 |
| September | 0.160309E+10 | 0.397857E+09 | 636.58 | 0.128733E+10 | 0.315761E+09 | 0.00 | 0.39 | 14-SEP-14:00 | 0.00 | 11-SEP-07:45 | 1758.42 | 07-SEP-16:12 | 1398.93 | 14-SEP-16:10 | 603.10 | 22-SEP-17:10 | 460.01 | 14-SEP-14:00 | 0.00 | 01-SEP-00:10 |
| October | 0.293450E+09 | 72918584.82 | 244.69 | 0.227432E+09 | 66018079.44 | 0.00 | 0.23 | 04-OCT-16:10 | 0.00 | 01-OCT-00:10 | 1044.08 | 25-OCT-11:00 | 805.10 | 04-OCT-16:05 | 305.89 | 25-OCT-10:30 | 256.93 | 25-OCT-11:00 | 0.00 | 01-OCT-00:10 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.109566E+11 | 0.272557E+10 | 3180.06 | 0.824945E+10 | 0.270714E+10 | 0.00 | ||||||||||||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Maximum of Months | 0.359719E+10 | 0.886566E+09 | 744.00 | 0.254749E+10 | 0.105016E+10 | 0.00 | 0.53 | 0.08 | 2394.59 | 1742.80 | 739.34 | 648.98 | 0.00 |
Report: DXReportMonthly
For: SPLIT GN2 COOLING COIL
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 |
| May | 0.209152E+09 | 53773927.61 | 123.87 | 0.187324E+09 | 21827953.62 | 0.00 | 0.27 | 31-MAY-14:10 | 0.00 | 01-MAY-00:10 | 1177.38 | 31-MAY-14:10 | 1077.10 | 30-MAY-16:08 | 258.91 | 31-MAY-17:50 | 302.05 | 31-MAY-14:10 | 0.00 | 01-MAY-00:10 |
| June | 0.194878E+10 | 0.483140E+09 | 689.65 | 0.145283E+10 | 0.495949E+09 | 0.00 | 0.48 | 19-JUN-17:20 | 0.00 | 01-JUN-05:40 | 2153.38 | 19-JUN-17:25 | 1671.74 | 19-JUN-17:17 | 620.01 | 27-JUN-16:10 | 588.62 | 19-JUN-17:10 | 0.00 | 01-JUN-00:10 |
| July | 0.359623E+10 | 0.886347E+09 | 744.00 | 0.254621E+10 | 0.105002E+10 | 0.00 | 0.48 | 08-JUL-12:00 | 0.08 | 02-JUL-05:10 | 2184.02 | 20-JUL-17:10 | 1631.89 | 10-JUL-17:35 | 713.54 | 20-JUL-17:10 | 581.37 | 08-JUL-12:00 | 0.00 | 01-JUL-00:10 |
| August | 0.330381E+10 | 0.831110E+09 | 742.28 | 0.254702E+10 | 0.756791E+09 | 0.00 | 0.53 | 04-AUG-19:00 | 0.00 | 08-AUG-05:15 | 2393.69 | 04-AUG-19:00 | 1741.68 | 04-AUG-19:00 | 737.96 | 03-AUG-16:02 | 648.72 | 04-AUG-19:00 | 0.00 | 01-AUG-00:10 |
| September | 0.160423E+10 | 0.398147E+09 | 638.94 | 0.128832E+10 | 0.315913E+09 | 0.00 | 0.39 | 14-SEP-14:00 | 0.00 | 11-SEP-07:45 | 1749.98 | 07-SEP-16:12 | 1392.91 | 14-SEP-16:10 | 602.67 | 22-SEP-17:10 | 459.48 | 14-SEP-14:00 | 0.00 | 01-SEP-00:10 |
| October | 0.292255E+09 | 72618090.05 | 243.66 | 0.226478E+09 | 65777814.44 | 0.00 | 0.23 | 25-OCT-11:00 | 0.00 | 01-OCT-00:10 | 1052.01 | 25-OCT-11:00 | 800.60 | 04-OCT-16:05 | 308.00 | 25-OCT-10:30 | 258.85 | 25-OCT-11:00 | 0.00 | 01-OCT-00:10 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.109545E+11 | 0.272514E+10 | 3182.39 | 0.824818E+10 | 0.270628E+10 | 0.00 | ||||||||||||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Maximum of Months | 0.359623E+10 | 0.886347E+09 | 744.00 | 0.254702E+10 | 0.105002E+10 | 0.00 | 0.53 | 0.08 | 2393.69 | 1741.68 | 737.96 | 648.72 | 0.00 |
Report: DXReportMonthly
For: SPLIT GS1 COOLING COIL
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
| April | 49297908.08 | 12800239.41 | 45.50 | 46585545.55 | 2712362.53 | 0.00 | 0.16 | 08-APR-12:00 | 0.00 | 01-APR-00:10 | 749.25 | 08-APR-12:00 | 697.27 | 08-APR-12:00 | 86.15 | 09-APR-11:50 | 191.18 | 08-APR-12:00 | 0.00 | 01-APR-00:10 |
| May | 0.303683E+09 | 78123025.71 | 176.51 | 0.278638E+09 | 25044861.64 | 0.00 | 0.31 | 31-MAY-14:00 | 0.00 | 01-MAY-00:10 | 1494.80 | 31-MAY-14:00 | 1378.04 | 30-MAY-13:00 | 274.40 | 31-MAY-17:50 | 383.42 | 31-MAY-14:00 | 0.00 | 01-MAY-00:10 |
| June | 0.215221E+10 | 0.534503E+09 | 696.96 | 0.163221E+10 | 0.519994E+09 | 0.00 | 0.49 | 19-JUN-12:00 | 0.00 | 01-JUN-05:40 | 2229.51 | 19-JUN-12:00 | 1832.27 | 19-JUN-12:00 | 647.51 | 24-JUN-18:00 | 651.49 | 19-JUN-12:00 | 0.00 | 01-JUN-00:10 |
| July | 0.388447E+10 | 0.959280E+09 | 744.00 | 0.279522E+10 | 0.108925E+10 | 0.00 | 0.51 | 08-JUL-12:00 | 0.07 | 02-JUL-05:05 | 2530.34 | 08-JUL-12:30 | 1892.36 | 10-JUL-14:10 | 744.56 | 09-JUL-10:00 | 672.73 | 08-JUL-12:00 | 0.00 | 01-JUL-00:10 |
| August | 0.397820E+10 | 0.999415E+09 | 743.67 | 0.316587E+10 | 0.812334E+09 | 0.00 | 0.55 | 16-AUG-13:00 | 0.00 | 08-AUG-05:15 | 2716.98 | 16-AUG-13:00 | 2174.04 | 18-AUG-14:10 | 746.53 | 04-AUG-10:50 | 721.10 | 16-AUG-13:00 | 0.00 | 01-AUG-00:10 |
| September | 0.242105E+10 | 0.600017E+09 | 702.73 | 0.204452E+10 | 0.376526E+09 | 0.00 | 0.51 | 07-SEP-14:10 | 0.00 | 20-SEP-07:35 | 2517.77 | 07-SEP-14:10 | 2136.20 | 01-SEP-14:10 | 702.85 | 14-SEP-10:10 | 620.00 | 07-SEP-14:10 | 0.00 | 01-SEP-00:10 |
| October | 0.139314E+10 | 0.348033E+09 | 600.55 | 0.120883E+10 | 0.184315E+09 | 0.00 | 0.42 | 04-OCT-13:00 | 0.00 | 01-OCT-03:10 | 2036.16 | 04-OCT-13:00 | 1790.95 | 04-OCT-13:20 | 487.33 | 25-OCT-10:30 | 499.73 | 04-OCT-13:00 | 0.00 | 01-OCT-00:10 |
| November | 88217076.11 | 23058681.67 | 87.33 | 88195762.04 | 21314.07 | 0.00 | 0.18 | 02-NOV-12:50 | 0.00 | 01-NOV-00:10 | 786.44 | 02-NOV-12:50 | 786.44 | 02-NOV-12:50 | 4.97 | 09-NOV-18:02 | 204.35 | 02-NOV-12:50 | 0.00 | 01-NOV-00:10 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.142703E+11 | 0.355523E+10 | 3797.25 | 0.112601E+11 | 0.301020E+10 | 0.00 | ||||||||||||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Maximum of Months | 0.397820E+10 | 0.999415E+09 | 744.00 | 0.316587E+10 | 0.108925E+10 | 0.00 | 0.55 | 0.07 | 2716.98 | 2174.04 | 746.53 | 721.10 | 0.00 |
Report: DXReportMonthly
For: SPLIT GS2 COOLING COIL
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
| April | 55386648.34 | 14367483.01 | 47.42 | 52278211.16 | 3108437.18 | 0.00 | 0.17 | 08-APR-12:00 | 0.00 | 01-APR-00:10 | 792.33 | 08-APR-12:00 | 737.71 | 08-APR-12:00 | 95.03 | 09-APR-11:50 | 201.96 | 08-APR-12:00 | 0.00 | 01-APR-00:10 |
| May | 0.348378E+09 | 89489947.70 | 197.54 | 0.320845E+09 | 27532935.20 | 0.00 | 0.33 | 31-MAY-14:00 | 0.00 | 01-MAY-00:10 | 1567.11 | 31-MAY-14:00 | 1458.39 | 30-MAY-13:00 | 289.09 | 31-MAY-17:50 | 401.47 | 31-MAY-14:00 | 0.00 | 01-MAY-00:10 |
| June | 0.235762E+10 | 0.584712E+09 | 707.55 | 0.180298E+10 | 0.554638E+09 | 0.00 | 0.50 | 19-JUN-12:00 | 0.00 | 01-JUN-05:40 | 2310.91 | 19-JUN-12:00 | 1911.85 | 19-JUN-12:00 | 681.63 | 24-JUN-18:00 | 674.10 | 19-JUN-12:00 | 0.00 | 01-JUN-00:10 |
| July | 0.420676E+10 | 0.103699E+10 | 744.00 | 0.306861E+10 | 0.113815E+10 | 0.00 | 0.54 | 08-JUL-12:00 | 0.09 | 02-JUL-05:05 | 2682.82 | 08-JUL-12:30 | 2008.59 | 10-JUL-14:10 | 762.64 | 09-JUL-10:00 | 710.48 | 08-JUL-12:00 | 0.00 | 01-JUL-00:10 |
| August | 0.430146E+10 | 0.107786E+10 | 744.00 | 0.345528E+10 | 0.846179E+09 | 0.00 | 0.57 | 16-AUG-13:00 | 0.01 | 08-AUG-05:20 | 2815.79 | 16-AUG-13:00 | 2262.52 | 18-AUG-14:10 | 754.74 | 04-AUG-10:50 | 746.07 | 16-AUG-13:00 | 0.00 | 01-AUG-00:10 |
| September | 0.265324E+10 | 0.656433E+09 | 706.67 | 0.225446E+10 | 0.398778E+09 | 0.00 | 0.52 | 07-SEP-14:10 | 0.00 | 24-SEP-02:70 | 2614.64 | 07-SEP-14:10 | 2214.33 | 01-SEP-14:10 | 721.07 | 14-SEP-10:10 | 642.87 | 07-SEP-14:10 | 0.00 | 01-SEP-00:10 |
| October | 0.151191E+10 | 0.377548E+09 | 614.28 | 0.131595E+10 | 0.195962E+09 | 0.00 | 0.43 | 04-OCT-13:00 | 0.00 | 01-OCT-03:50 | 2097.82 | 04-OCT-13:00 | 1851.05 | 04-OCT-13:20 | 496.94 | 25-OCT-10:30 | 514.30 | 04-OCT-13:00 | 0.00 | 01-OCT-00:10 |
| November | 0.102281E+09 | 26709945.55 | 98.85 | 0.102135E+09 | 145667.56 | 0.00 | 0.19 | 02-NOV-12:50 | 0.00 | 01-NOV-00:10 | 836.73 | 02-NOV-12:50 | 836.73 | 02-NOV-12:50 | 31.60 | 10-NOV-09:30 | 217.09 | 02-NOV-12:50 | 0.00 | 01-NOV-00:10 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.155370E+11 | 0.386411E+10 | 3860.30 | 0.123725E+11 | 0.316450E+10 | 0.00 | ||||||||||||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Maximum of Months | 0.430146E+10 | 0.107786E+10 | 744.00 | 0.345528E+10 | 0.113815E+10 | 0.00 | 0.57 | 0.09 | 2815.79 | 2262.52 | 762.64 | 746.07 | 0.00 |
Report: DXReportMonthly
For: SPLIT MSW COOLING COIL
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
| March | 22957861.68 | 5973833.80 | 13.17 | 21683594.35 | 1274267.33 | 0.00 | 0.11 | 27-MAR-16:20 | 0.00 | 01-MAR-00:10 | 1369.67 | 27-MAR-16:20 | 1184.62 | 27-MAR-16:30 | 199.12 | 27-MAR-16:10 | 345.81 | 27-MAR-16:20 | 0.00 | 01-MAR-00:10 |
| April | 0.804338E+09 | 0.205689E+09 | 167.38 | 0.770070E+09 | 34267188.97 | 0.00 | 0.38 | 07-APR-15:30 | 0.00 | 01-APR-00:10 | 4891.60 | 07-APR-15:30 | 4891.60 | 07-APR-15:30 | 480.92 | 09-APR-11:50 | 1243.29 | 07-APR-15:30 | 0.00 | 01-APR-00:10 |
| May | 0.263282E+10 | 0.672170E+09 | 481.09 | 0.249099E+10 | 0.141827E+09 | 0.00 | 0.42 | 30-MAY-16:10 | 0.00 | 01-MAY-00:10 | 5482.54 | 31-MAY-15:10 | 5304.63 | 30-MAY-16:05 | 1039.08 | 31-MAY-17:40 | 1390.19 | 30-MAY-16:10 | 0.00 | 01-MAY-00:10 |
| June | 0.706825E+10 | 0.175353E+10 | 711.66 | 0.556398E+10 | 0.150427E+10 | 0.00 | 0.57 | 19-JUN-17:10 | 0.00 | 01-JUN-05:40 | 7501.69 | 19-JUN-17:10 | 6183.20 | 19-JUN-17:05 | 2036.62 | 27-JUN-16:10 | 2038.48 | 19-JUN-17:10 | 0.00 | 01-JUN-00:10 |
| July | 0.107459E+11 | 0.266328E+10 | 744.00 | 0.797260E+10 | 0.277334E+10 | 0.00 | 0.54 | 13-JUL-15:10 | 0.09 | 01-JUL-05:05 | 7425.51 | 21-JUL-16:02 | 5908.24 | 10-JUL-15:10 | 2119.94 | 23-JUL-15:30 | 1914.65 | 09-JUL-14:00 | 0.00 | 01-JUL-00:10 |
| August | 0.104528E+11 | 0.263790E+10 | 742.60 | 0.847136E+10 | 0.198147E+10 | 0.00 | 0.58 | 16-AUG-15:10 | 0.00 | 08-AUG-05:15 | 7902.48 | 02-AUG-15:20 | 6672.41 | 18-AUG-16:03 | 2040.70 | 02-AUG-14:30 | 2077.48 | 16-AUG-15:10 | 0.00 | 01-AUG-00:10 |
| September | 0.578975E+10 | 0.143917E+10 | 659.00 | 0.491993E+10 | 0.869819E+09 | 0.00 | 0.54 | 07-SEP-15:10 | 0.00 | 11-SEP-05:00 | 7450.23 | 07-SEP-15:10 | 6367.38 | 01-SEP-14:30 | 1859.78 | 14-SEP-10:10 | 1813.38 | 07-SEP-15:10 | 0.00 | 01-SEP-00:10 |
| October | 0.296237E+10 | 0.738027E+09 | 480.83 | 0.256104E+10 | 0.401330E+09 | 0.00 | 0.45 | 04-OCT-15:20 | 0.00 | 01-OCT-01:00 | 6107.26 | 04-OCT-15:20 | 5375.66 | 04-OCT-15:10 | 1246.65 | 25-OCT-10:30 | 1464.57 | 04-OCT-15:20 | 0.00 | 01-OCT-00:10 |
| November | 0.135448E+09 | 35384773.51 | 46.36 | 0.135410E+09 | 37917.16 | 0.00 | 0.17 | 04-NOV-12:30 | 0.00 | 01-NOV-00:10 | 2133.67 | 04-NOV-12:30 | 2133.67 | 04-NOV-12:30 | 12.20 | 04-NOV-15:20 | 547.22 | 04-NOV-12:30 | 0.00 | 01-NOV-00:10 |
| December | 302356.22 | 80943.42 | 0.83 | 302356.22 | 0.00 | 0.00 | 0.01 | 17-DEC-14:40 | 0.00 | 01-DEC-00:10 | 126.87 | 17-DEC-14:40 | 126.87 | 17-DEC-14:40 | 0.00 | 17-DEC-14:20 | 33.95 | 17-DEC-14:40 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.406150E+11 | 0.101512E+11 | 4046.92 | 0.329074E+11 | 0.770763E+10 | 0.00 | ||||||||||||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Maximum of Months | 0.107459E+11 | 0.266328E+10 | 744.00 | 0.847136E+10 | 0.277334E+10 | 0.00 | 0.58 | 0.09 | 7902.48 | 6672.41 | 2119.94 | 2077.48 | 0.00 |
Report: DXReportMonthly
For: SPLIT MNW COOLING COIL
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
| April | 0.278404E+09 | 71710314.38 | 77.08 | 0.261841E+09 | 16563306.20 | 0.00 | 0.21 | 07-APR-16:17 | 0.00 | 01-APR-00:10 | 2588.00 | 07-APR-16:17 | 2588.00 | 07-APR-16:17 | 257.42 | 09-APR-11:30 | 676.16 | 07-APR-16:25 | 0.00 | 01-APR-00:10 |
| May | 0.213686E+10 | 0.546340E+09 | 451.36 | 0.200237E+10 | 0.134497E+09 | 0.00 | 0.40 | 30-MAY-16:20 | 0.00 | 01-MAY-00:10 | 5125.19 | 31-MAY-16:20 | 4900.79 | 30-MAY-16:10 | 972.07 | 31-MAY-17:50 | 1298.88 | 30-MAY-16:10 | 0.00 | 01-MAY-00:10 |
| June | 0.669473E+10 | 0.166042E+10 | 711.21 | 0.521704E+10 | 0.147769E+10 | 0.00 | 0.57 | 19-JUN-17:20 | 0.00 | 01-JUN-05:40 | 7422.06 | 19-JUN-17:25 | 6042.26 | 19-JUN-17:17 | 2023.07 | 27-JUN-16:10 | 2007.14 | 19-JUN-17:10 | 0.00 | 01-JUN-00:10 |
| July | 0.101770E+11 | 0.252127E+10 | 744.00 | 0.746351E+10 | 0.271354E+10 | 0.00 | 0.53 | 06-JUL-17:13 | 0.10 | 11-JUL-05:05 | 7176.61 | 06-JUL-17:13 | 5374.99 | 06-JUL-17:17 | 2014.79 | 23-JUL-15:30 | 1789.48 | 06-JUL-17:13 | 0.00 | 01-JUL-00:10 |
| August | 0.907049E+10 | 0.229456E+10 | 741.83 | 0.717651E+10 | 0.189398E+10 | 0.00 | 0.54 | 16-AUG-16:05 | 0.00 | 08-AUG-05:15 | 7203.05 | 02-AUG-16:02 | 5744.07 | 18-AUG-16:30 | 2026.35 | 03-AUG-15:20 | 1863.26 | 16-AUG-16:05 | 0.00 | 01-AUG-00:10 |
| September | 0.413076E+10 | 0.102951E+10 | 592.59 | 0.336355E+10 | 0.767209E+09 | 0.00 | 0.44 | 07-SEP-16:02 | 0.00 | 10-SEP-05:05 | 5852.51 | 07-SEP-16:02 | 4535.99 | 14-SEP-16:10 | 1566.46 | 07-SEP-15:10 | 1428.26 | 07-SEP-16:02 | 0.00 | 01-SEP-00:10 |
| October | 0.895223E+09 | 0.222466E+09 | 239.83 | 0.706890E+09 | 0.188332E+09 | 0.00 | 0.30 | 04-OCT-16:10 | 0.00 | 01-OCT-00:10 | 3898.91 | 04-OCT-16:10 | 3116.80 | 04-OCT-15:20 | 906.46 | 05-OCT-16:10 | 945.49 | 04-OCT-16:10 | 0.00 | 01-OCT-00:10 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.333835E+11 | 0.834628E+10 | 3557.90 | 0.261917E+11 | 0.719181E+10 | 0.00 | ||||||||||||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Maximum of Months | 0.101770E+11 | 0.252127E+10 | 744.00 | 0.746351E+10 | 0.271354E+10 | 0.00 | 0.57 | 0.10 | 7422.06 | 6042.26 | 2026.35 | 2007.14 | 0.00 |
Report: DXReportMonthly
For: SPLIT MSE COOLING COIL
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
| March | 8214704.88 | 2165665.04 | 6.83 | 8100790.92 | 113913.97 | 0.00 | 0.07 | 03-MAR-14:00 | 0.00 | 01-MAR-00:10 | 799.75 | 03-MAR-14:00 | 799.75 | 03-MAR-14:00 | 43.92 | 27-MAR-16:10 | 210.79 | 03-MAR-14:00 | 0.00 | 01-MAR-00:10 |
| April | 0.799798E+09 | 0.204185E+09 | 174.70 | 0.766741E+09 | 33056602.42 | 0.00 | 0.39 | 08-APR-12:00 | 0.00 | 01-APR-00:10 | 4693.31 | 08-APR-12:00 | 4508.59 | 07-APR-13:00 | 527.27 | 09-APR-11:50 | 1166.64 | 07-APR-13:00 | 0.00 | 01-APR-00:10 |
| May | 0.268011E+10 | 0.683423E+09 | 497.78 | 0.253806E+10 | 0.142056E+09 | 0.00 | 0.43 | 29-MAY-12:00 | 0.00 | 01-MAY-00:10 | 5130.33 | 29-MAY-12:00 | 5028.29 | 30-MAY-13:00 | 890.15 | 31-MAY-17:40 | 1352.94 | 30-MAY-13:00 | 0.00 | 01-MAY-00:10 |
| June | 0.689021E+10 | 0.170695E+10 | 713.59 | 0.541941E+10 | 0.147080E+10 | 0.00 | 0.58 | 19-JUN-12:00 | 0.00 | 03-JUN-02:00 | 6910.67 | 19-JUN-10:50 | 5924.39 | 19-JUN-12:00 | 1996.48 | 27-JUN-16:10 | 1988.06 | 19-JUN-12:00 | 0.00 | 01-JUN-00:10 |
| July | 0.107010E+11 | 0.264388E+10 | 744.00 | 0.793154E+10 | 0.276941E+10 | 0.00 | 0.58 | 08-JUL-12:00 | 0.11 | 01-JUL-04:00 | 7325.71 | 08-JUL-12:30 | 5554.84 | 08-JUL-12:00 | 2085.51 | 23-JUL-15:30 | 1932.88 | 08-JUL-12:00 | 0.00 | 01-JUL-00:10 |
| August | 0.104097E+11 | 0.261753E+10 | 742.48 | 0.842569E+10 | 0.198398E+10 | 0.00 | 0.58 | 16-AUG-13:00 | 0.00 | 08-AUG-05:15 | 7248.41 | 16-AUG-13:00 | 6221.40 | 18-AUG-13:00 | 1905.36 | 04-AUG-09:30 | 1922.91 | 16-AUG-13:00 | 0.00 | 01-AUG-00:10 |
| September | 0.580110E+10 | 0.143852E+10 | 661.87 | 0.493498E+10 | 0.866119E+09 | 0.00 | 0.52 | 07-SEP-13:40 | 0.00 | 11-SEP-04:40 | 6589.31 | 07-SEP-13:40 | 5985.33 | 01-SEP-13:00 | 2016.65 | 14-SEP-10:10 | 1642.20 | 01-SEP-13:00 | 0.00 | 01-SEP-00:10 |
| October | 0.289904E+10 | 0.721059E+09 | 488.54 | 0.250563E+10 | 0.393402E+09 | 0.00 | 0.47 | 25-OCT-10:30 | 0.00 | 01-OCT-00:30 | 5987.19 | 25-OCT-10:30 | 4984.46 | 04-OCT-13:00 | 1345.97 | 25-OCT-10:30 | 1415.05 | 25-OCT-10:30 | 0.00 | 01-OCT-00:10 |
| November | 0.155167E+09 | 40495000.39 | 55.42 | 0.155127E+09 | 40257.84 | 0.00 | 0.20 | 04-NOV-12:30 | 0.00 | 01-NOV-00:10 | 2326.58 | 04-NOV-12:30 | 2326.58 | 04-NOV-12:30 | 12.67 | 04-NOV-15:20 | 593.97 | 04-NOV-12:30 | 0.00 | 01-NOV-00:10 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.403443E+11 | 0.100582E+11 | 4085.21 | 0.326853E+11 | 0.765899E+10 | 0.00 | ||||||||||||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Maximum of Months | 0.107010E+11 | 0.264388E+10 | 744.00 | 0.842569E+10 | 0.276941E+10 | 0.00 | 0.58 | 0.11 | 7325.71 | 6221.40 | 2085.51 | 1988.06 | 0.00 |
Report: DXReportMonthly
For: SPLIT MNE COOLING COIL
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
| April | 0.265284E+09 | 68233456.82 | 74.34 | 0.249826E+09 | 15458213.04 | 0.00 | 0.23 | 08-APR-10:00 | 0.00 | 01-APR-00:10 | 2573.41 | 08-APR-10:00 | 2442.43 | 08-APR-10:10 | 337.34 | 09-APR-11:20 | 669.27 | 08-APR-10:00 | 0.00 | 01-APR-00:10 |
| May | 0.217512E+10 | 0.555641E+09 | 467.98 | 0.204061E+10 | 0.134507E+09 | 0.00 | 0.38 | 31-MAY-09:50 | 0.00 | 01-MAY-00:10 | 4478.64 | 31-MAY-09:50 | 4133.63 | 30-MAY-10:20 | 841.57 | 31-MAY-17:50 | 1119.07 | 30-MAY-13:00 | 0.00 | 01-MAY-00:10 |
| June | 0.651310E+10 | 0.161336E+10 | 712.94 | 0.507257E+10 | 0.144053E+10 | 0.00 | 0.55 | 19-JUN-10:50 | 0.00 | 03-JUN-01:20 | 6414.36 | 19-JUN-10:30 | 5202.21 | 19-JUN-11:00 | 1979.42 | 27-JUN-16:10 | 1811.78 | 19-JUN-11:00 | 0.00 | 01-JUN-00:10 |
| July | 0.101282E+11 | 0.250151E+10 | 744.00 | 0.742261E+10 | 0.270558E+10 | 0.00 | 0.53 | 08-JUL-12:00 | 0.11 | 02-JUL-03:00 | 6433.19 | 08-JUL-12:40 | 4822.29 | 14-JUL-09:30 | 1975.06 | 23-JUL-15:30 | 1709.23 | 08-JUL-12:00 | 0.00 | 01-JUL-00:10 |
| August | 0.902487E+10 | 0.227567E+10 | 741.50 | 0.713258E+10 | 0.189229E+10 | 0.00 | 0.52 | 04-AUG-19:00 | 0.00 | 08-AUG-05:15 | 6351.53 | 04-AUG-10:20 | 4892.82 | 24-AUG-16:30 | 1887.80 | 03-AUG-17:20 | 1692.59 | 04-AUG-19:00 | 0.00 | 01-AUG-00:10 |
| September | 0.413046E+10 | 0.102792E+10 | 610.54 | 0.336912E+10 | 0.761346E+09 | 0.00 | 0.39 | 14-SEP-14:00 | 0.00 | 10-SEP-05:05 | 4641.98 | 14-SEP-14:00 | 3939.89 | 01-SEP-14:10 | 1725.70 | 14-SEP-10:10 | 1236.24 | 14-SEP-14:00 | 0.00 | 01-SEP-00:10 |
| October | 0.835761E+09 | 0.207371E+09 | 229.83 | 0.656714E+09 | 0.179048E+09 | 0.00 | 0.28 | 25-OCT-10:30 | 0.00 | 01-OCT-00:10 | 3440.01 | 25-OCT-10:30 | 2492.31 | 25-OCT-10:30 | 947.70 | 25-OCT-10:30 | 829.02 | 25-OCT-10:30 | 0.00 | 01-OCT-00:10 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.330728E+11 | 0.824969E+10 | 3581.13 | 0.259440E+11 | 0.712876E+10 | 0.00 | ||||||||||||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Maximum of Months | 0.101282E+11 | 0.250151E+10 | 744.00 | 0.742261E+10 | 0.270558E+10 | 0.00 | 0.55 | 0.11 | 6433.19 | 5202.21 | 1979.42 | 1811.78 | 0.00 |
Report: DXReportMonthly
For: SPLIT MN1 COOLING COIL
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
| April | 0.179635E+09 | 46331126.85 | 84.87 | 0.166968E+09 | 12667120.69 | 0.00 | 0.16 | 08-APR-12:00 | 0.00 | 01-APR-00:10 | 1593.62 | 08-APR-12:00 | 1506.69 | 08-APR-12:00 | 247.77 | 09-APR-11:30 | 407.95 | 08-APR-12:00 | 0.00 | 01-APR-00:10 |
| May | 0.179671E+10 | 0.459871E+09 | 539.54 | 0.165640E+10 | 0.140302E+09 | 0.00 | 0.31 | 31-MAY-14:10 | 0.00 | 01-MAY-00:10 | 3267.16 | 31-MAY-14:10 | 3076.07 | 30-MAY-16:08 | 722.18 | 31-MAY-18:00 | 835.85 | 31-MAY-14:10 | 0.00 | 01-MAY-00:10 |
| June | 0.547729E+10 | 0.135709E+10 | 716.47 | 0.419298E+10 | 0.128431E+10 | 0.00 | 0.49 | 19-JUN-17:20 | 0.00 | 01-JUN-05:40 | 5198.78 | 19-JUN-17:25 | 4107.81 | 19-JUN-17:25 | 1681.82 | 27-JUN-16:10 | 1419.25 | 19-JUN-17:10 | 0.00 | 01-JUN-00:10 |
| July | 0.843365E+10 | 0.208404E+10 | 744.00 | 0.606461E+10 | 0.236904E+10 | 0.00 | 0.45 | 20-JUL-17:10 | 0.12 | 11-JUL-05:05 | 5052.59 | 20-JUL-17:10 | 3742.69 | 10-JUL-17:50 | 1786.25 | 23-JUL-15:30 | 1316.91 | 08-JUL-12:00 | 0.00 | 01-JUL-00:10 |
| August | 0.732056E+10 | 0.184928E+10 | 742.00 | 0.568013E+10 | 0.164043E+10 | 0.00 | 0.48 | 04-AUG-19:00 | 0.00 | 08-AUG-05:15 | 5211.33 | 04-AUG-19:00 | 3859.54 | 24-AUG-16:40 | 1613.63 | 03-AUG-17:20 | 1422.99 | 04-AUG-19:00 | 0.00 | 01-AUG-00:10 |
| September | 0.357425E+10 | 0.889819E+09 | 661.67 | 0.287345E+10 | 0.700803E+09 | 0.00 | 0.36 | 14-SEP-14:10 | 0.00 | 10-SEP-05:15 | 3809.33 | 14-SEP-14:00 | 3074.23 | 14-SEP-16:10 | 1399.27 | 22-SEP-17:10 | 1017.63 | 14-SEP-14:00 | 0.00 | 01-SEP-00:10 |
| October | 0.788058E+09 | 0.196043E+09 | 281.61 | 0.612956E+09 | 0.175102E+09 | 0.00 | 0.23 | 04-OCT-16:10 | 0.00 | 01-OCT-00:10 | 2412.34 | 25-OCT-11:00 | 1857.04 | 04-OCT-16:10 | 711.93 | 25-OCT-10:30 | 594.72 | 25-OCT-11:00 | 0.00 | 01-OCT-00:10 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.275701E+11 | 0.688248E+10 | 3770.15 | 0.212475E+11 | 0.632266E+10 | 0.00 | ||||||||||||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Maximum of Months | 0.843365E+10 | 0.208404E+10 | 744.00 | 0.606461E+10 | 0.236904E+10 | 0.00 | 0.49 | 0.12 | 5211.33 | 4107.81 | 1786.25 | 1422.99 | 0.00 |
Report: DXReportMonthly
For: SPLIT MN2 COOLING COIL
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
| April | 0.182772E+09 | 47133492.45 | 85.62 | 0.169952E+09 | 12819251.92 | 0.00 | 0.16 | 08-APR-12:00 | 0.00 | 01-APR-00:10 | 1630.25 | 08-APR-12:00 | 1541.80 | 08-APR-12:00 | 252.07 | 09-APR-11:30 | 417.11 | 08-APR-12:00 | 0.00 | 01-APR-00:10 |
| May | 0.180026E+10 | 0.460768E+09 | 539.73 | 0.165994E+10 | 0.140319E+09 | 0.00 | 0.31 | 31-MAY-14:10 | 0.00 | 01-MAY-00:10 | 3273.41 | 31-MAY-14:10 | 3069.29 | 30-MAY-16:08 | 719.54 | 31-MAY-18:00 | 837.37 | 31-MAY-14:10 | 0.00 | 01-MAY-00:10 |
| June | 0.547098E+10 | 0.135554E+10 | 716.47 | 0.418779E+10 | 0.128320E+10 | 0.00 | 0.49 | 19-JUN-17:20 | 0.00 | 01-JUN-05:40 | 5180.46 | 19-JUN-17:25 | 4091.90 | 19-JUN-17:17 | 1681.16 | 27-JUN-16:10 | 1414.88 | 19-JUN-17:10 | 0.00 | 01-JUN-00:10 |
| July | 0.843248E+10 | 0.208367E+10 | 744.00 | 0.606342E+10 | 0.236906E+10 | 0.00 | 0.45 | 08-JUL-12:00 | 0.12 | 11-JUL-05:05 | 5034.51 | 20-JUL-17:10 | 3732.99 | 10-JUL-17:50 | 1783.90 | 23-JUL-15:30 | 1320.22 | 08-JUL-12:00 | 0.00 | 01-JUL-00:10 |
| August | 0.732000E+10 | 0.184906E+10 | 742.00 | 0.567943E+10 | 0.164056E+10 | 0.00 | 0.48 | 04-AUG-19:00 | 0.00 | 08-AUG-05:15 | 5207.76 | 04-AUG-19:00 | 3850.94 | 24-AUG-16:40 | 1610.95 | 03-AUG-17:20 | 1421.86 | 04-AUG-19:00 | 0.00 | 01-AUG-00:10 |
| September | 0.357671E+10 | 0.890425E+09 | 662.85 | 0.287571E+10 | 0.701001E+09 | 0.00 | 0.36 | 14-SEP-14:10 | 0.00 | 10-SEP-05:15 | 3804.95 | 14-SEP-14:00 | 3059.20 | 14-SEP-16:10 | 1398.39 | 22-SEP-17:10 | 1016.44 | 14-SEP-14:00 | 0.00 | 01-SEP-00:10 |
| October | 0.786670E+09 | 0.195684E+09 | 281.56 | 0.611802E+09 | 0.174868E+09 | 0.00 | 0.23 | 25-OCT-11:00 | 0.00 | 01-OCT-00:10 | 2434.73 | 25-OCT-11:00 | 1847.05 | 04-OCT-15:10 | 718.02 | 25-OCT-10:30 | 600.12 | 25-OCT-11:00 | 0.00 | 01-OCT-00:10 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.275699E+11 | 0.688228E+10 | 3772.22 | 0.212480E+11 | 0.632182E+10 | 0.00 | ||||||||||||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Maximum of Months | 0.843248E+10 | 0.208367E+10 | 744.00 | 0.606342E+10 | 0.236906E+10 | 0.00 | 0.49 | 0.12 | 5207.76 | 4091.90 | 1783.90 | 1421.86 | 0.00 |
Report: DXReportMonthly
For: SPLIT MS1 COOLING COIL
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
| March | 21480384.22 | 5634760.38 | 15.81 | 21005825.00 | 474559.22 | 0.00 | 0.11 | 03-MAR-14:00 | 0.00 | 01-MAR-00:10 | 1080.67 | 03-MAR-14:00 | 1080.67 | 03-MAR-14:00 | 99.00 | 27-MAR-16:10 | 283.29 | 03-MAR-14:00 | 0.00 | 01-MAR-00:10 |
| April | 0.733496E+09 | 0.187855E+09 | 204.07 | 0.699119E+09 | 34376687.36 | 0.00 | 0.35 | 08-APR-12:00 | 0.00 | 01-APR-00:10 | 3829.75 | 08-APR-12:00 | 3677.64 | 07-APR-13:00 | 463.56 | 09-APR-11:50 | 957.10 | 07-APR-13:00 | 0.00 | 01-APR-00:10 |
| May | 0.231278E+10 | 0.591482E+09 | 585.40 | 0.216245E+10 | 0.150337E+09 | 0.00 | 0.37 | 30-MAY-13:00 | 0.00 | 01-MAY-00:10 | 4026.97 | 31-MAY-14:00 | 3837.87 | 30-MAY-13:00 | 763.33 | 31-MAY-17:50 | 1044.01 | 30-MAY-13:00 | 0.00 | 01-MAY-00:10 |
| June | 0.586407E+10 | 0.145412E+10 | 716.48 | 0.454265E+10 | 0.132142E+10 | 0.00 | 0.50 | 19-JUN-12:00 | 0.00 | 01-JUN-05:40 | 5396.23 | 19-JUN-12:50 | 4512.94 | 19-JUN-12:50 | 1704.68 | 27-JUN-16:10 | 1566.99 | 19-JUN-12:00 | 0.00 | 01-JUN-00:10 |
| July | 0.902047E+10 | 0.223152E+10 | 744.00 | 0.657694E+10 | 0.244353E+10 | 0.00 | 0.51 | 08-JUL-12:00 | 0.10 | 02-JUL-05:05 | 5807.50 | 08-JUL-12:30 | 4360.14 | 10-JUL-14:10 | 1895.54 | 23-JUL-15:30 | 1545.65 | 08-JUL-12:00 | 0.00 | 01-JUL-00:10 |
| August | 0.872637E+10 | 0.220019E+10 | 743.67 | 0.697879E+10 | 0.174758E+10 | 0.00 | 0.54 | 16-AUG-13:00 | 0.00 | 08-AUG-05:15 | 6097.45 | 16-AUG-13:00 | 4972.36 | 18-AUG-13:20 | 1622.56 | 04-AUG-10:50 | 1624.93 | 16-AUG-13:00 | 0.00 | 01-AUG-00:10 |
| September | 0.528813E+10 | 0.131377E+10 | 704.00 | 0.447239E+10 | 0.815746E+09 | 0.00 | 0.49 | 07-SEP-13:40 | 0.00 | 17-SEP-06:40 | 5651.69 | 07-SEP-13:40 | 4915.28 | 01-SEP-13:30 | 1716.42 | 14-SEP-10:10 | 1417.86 | 14-SEP-13:40 | 0.00 | 01-SEP-00:10 |
| October | 0.311317E+10 | 0.777572E+09 | 573.81 | 0.271409E+10 | 0.399081E+09 | 0.00 | 0.44 | 04-OCT-13:00 | 0.00 | 01-OCT-02:20 | 4887.58 | 25-OCT-10:30 | 4324.45 | 04-OCT-13:00 | 1182.78 | 25-OCT-10:30 | 1195.20 | 04-OCT-13:00 | 0.00 | 01-OCT-00:10 |
| November | 0.283536E+09 | 73835605.07 | 106.08 | 0.282856E+09 | 679793.23 | 0.00 | 0.24 | 02-NOV-12:50 | 0.00 | 01-NOV-00:10 | 2416.04 | 02-NOV-12:50 | 2416.04 | 02-NOV-12:50 | 208.42 | 10-NOV-09:30 | 622.46 | 02-NOV-12:50 | 0.00 | 01-NOV-00:10 |
| December | 4208910.13 | 1120815.63 | 3.33 | 4208910.13 | 0.00 | 0.00 | 0.05 | 17-DEC-14:20 | 0.00 | 01-DEC-00:10 | 497.77 | 17-DEC-14:20 | 497.77 | 17-DEC-14:20 | 0.00 | 17-DEC-14:30 | 132.40 | 17-DEC-14:20 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.353677E+11 | 0.883710E+10 | 4396.65 | 0.284545E+11 | 0.691323E+10 | 0.00 | ||||||||||||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Maximum of Months | 0.902047E+10 | 0.223152E+10 | 744.00 | 0.697879E+10 | 0.244353E+10 | 0.00 | 0.54 | 0.10 | 6097.45 | 4972.36 | 1895.54 | 1624.93 | 0.00 |
Report: DXReportMonthly
For: SPLIT MS2 COOLING COIL
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
| March | 21402339.39 | 5615906.29 | 15.83 | 20959120.51 | 443218.88 | 0.00 | 0.11 | 03-MAR-14:00 | 0.00 | 01-MAR-00:10 | 1100.41 | 03-MAR-14:00 | 1100.41 | 03-MAR-14:00 | 95.36 | 27-MAR-16:10 | 288.38 | 03-MAR-14:00 | 0.00 | 01-MAR-00:10 |
| April | 0.739361E+09 | 0.189345E+09 | 205.12 | 0.704905E+09 | 34455436.35 | 0.00 | 0.36 | 08-APR-12:00 | 0.00 | 01-APR-00:10 | 3852.23 | 08-APR-12:00 | 3715.51 | 07-APR-13:00 | 465.67 | 09-APR-11:50 | 966.35 | 07-APR-13:00 | 0.00 | 01-APR-00:10 |
| May | 0.231655E+10 | 0.592415E+09 | 585.17 | 0.216624E+10 | 0.150310E+09 | 0.00 | 0.37 | 30-MAY-13:00 | 0.00 | 01-MAY-00:10 | 4034.68 | 31-MAY-14:00 | 3857.93 | 30-MAY-13:00 | 760.42 | 31-MAY-17:50 | 1049.10 | 30-MAY-13:00 | 0.00 | 01-MAY-00:10 |
| June | 0.585785E+10 | 0.145256E+10 | 716.48 | 0.453751E+10 | 0.132034E+10 | 0.00 | 0.51 | 19-JUN-12:00 | 0.00 | 01-JUN-05:40 | 5406.10 | 19-JUN-12:50 | 4523.08 | 19-JUN-12:40 | 1704.05 | 27-JUN-16:10 | 1570.35 | 19-JUN-12:00 | 0.00 | 01-JUN-00:10 |
| July | 0.901933E+10 | 0.223112E+10 | 744.00 | 0.657578E+10 | 0.244355E+10 | 0.00 | 0.51 | 08-JUL-12:00 | 0.10 | 02-JUL-05:05 | 5818.90 | 08-JUL-12:30 | 4364.45 | 10-JUL-14:10 | 1893.40 | 23-JUL-15:30 | 1548.82 | 08-JUL-12:00 | 0.00 | 01-JUL-00:10 |
| August | 0.872581E+10 | 0.219989E+10 | 743.67 | 0.697804E+10 | 0.174777E+10 | 0.00 | 0.54 | 16-AUG-13:00 | 0.00 | 08-AUG-05:15 | 6097.09 | 16-AUG-13:00 | 4984.90 | 18-AUG-13:20 | 1625.00 | 04-AUG-10:50 | 1624.63 | 16-AUG-13:00 | 0.00 | 01-AUG-00:10 |
| September | 0.528929E+10 | 0.131397E+10 | 704.00 | 0.447345E+10 | 0.815848E+09 | 0.00 | 0.49 | 07-SEP-13:40 | 0.00 | 17-SEP-06:40 | 5652.81 | 07-SEP-13:40 | 4922.70 | 01-SEP-13:30 | 1720.32 | 14-SEP-10:10 | 1417.19 | 14-SEP-13:40 | 0.00 | 01-SEP-00:10 |
| October | 0.311328E+10 | 0.777551E+09 | 573.81 | 0.271437E+10 | 0.398912E+09 | 0.00 | 0.44 | 04-OCT-13:00 | 0.00 | 01-OCT-02:20 | 4911.62 | 25-OCT-10:30 | 4336.13 | 04-OCT-13:00 | 1186.34 | 25-OCT-10:30 | 1197.83 | 04-OCT-13:00 | 0.00 | 01-OCT-00:10 |
| November | 0.290154E+09 | 75545432.24 | 108.00 | 0.289387E+09 | 766630.73 | 0.00 | 0.24 | 02-NOV-12:50 | 0.00 | 01-NOV-00:10 | 2441.11 | 02-NOV-12:50 | 2441.11 | 02-NOV-12:50 | 203.79 | 10-NOV-09:30 | 628.65 | 02-NOV-12:50 | 0.00 | 01-NOV-00:10 |
| December | 4398017.23 | 1170938.99 | 3.33 | 4398017.23 | 0.00 | 0.00 | 0.05 | 17-DEC-14:20 | 0.00 | 01-DEC-00:10 | 511.36 | 17-DEC-14:20 | 511.36 | 17-DEC-14:20 | 0.00 | 17-DEC-13:20 | 135.99 | 17-DEC-14:20 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.353774E+11 | 0.883918E+10 | 4399.41 | 0.284650E+11 | 0.691239E+10 | 0.00 | ||||||||||||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Maximum of Months | 0.901933E+10 | 0.223112E+10 | 744.00 | 0.697804E+10 | 0.244355E+10 | 0.00 | 0.54 | 0.10 | 6097.09 | 4984.90 | 1893.40 | 1624.63 | 0.00 |
Report: DXReportMonthly
For: SPLIT TSW COOLING COIL
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 6395500.20 | 1687132.46 | 3.67 | 6395500.20 | 0.00 | 0.00 | 0.11 | 17-JAN-15:10 | 0.00 | 01-JAN-00:10 | 703.88 | 17-JAN-15:10 | 703.88 | 17-JAN-15:10 | 0.00 | 17-JAN-15:10 | 185.12 | 17-JAN-15:10 | 0.00 | 01-JAN-00:10 |
| February | 1541350.79 | 410537.85 | 3.33 | 1541350.79 | 0.00 | 0.00 | 0.04 | 20-FEB-15:30 | 0.00 | 01-FEB-00:10 | 272.29 | 20-FEB-15:30 | 272.29 | 20-FEB-15:30 | 0.00 | 20-FEB-15:30 | 72.34 | 20-FEB-15:30 | 0.00 | 01-FEB-00:10 |
| March | 0.118275E+09 | 30753380.38 | 52.58 | 0.116071E+09 | 2204084.53 | 0.00 | 0.23 | 27-MAR-16:20 | 0.00 | 01-MAR-00:10 | 1617.81 | 27-MAR-16:20 | 1440.39 | 27-MAR-16:30 | 195.36 | 27-MAR-16:10 | 402.56 | 27-MAR-16:20 | 0.00 | 01-MAR-00:10 |
| April | 0.501446E+09 | 0.127747E+09 | 136.33 | 0.487073E+09 | 14372898.00 | 0.00 | 0.49 | 07-APR-15:20 | 0.00 | 01-APR-00:10 | 3489.65 | 07-APR-15:20 | 3489.65 | 07-APR-15:20 | 249.23 | 09-APR-12:00 | 871.55 | 07-APR-15:20 | 0.00 | 01-APR-00:10 |
| May | 0.126144E+10 | 0.320559E+09 | 305.14 | 0.121201E+10 | 49430920.47 | 0.00 | 0.52 | 30-MAY-15:10 | 0.00 | 01-MAY-00:10 | 3767.65 | 31-MAY-14:20 | 3637.27 | 30-MAY-15:10 | 650.90 | 31-MAY-17:20 | 940.86 | 30-MAY-15:10 | 0.00 | 01-MAY-00:10 |
| June | 0.365496E+10 | 0.903808E+09 | 614.06 | 0.290723E+10 | 0.747736E+09 | 0.00 | 0.68 | 19-JUN-14:10 | 0.00 | 01-JUN-02:30 | 4855.18 | 19-JUN-14:10 | 4245.32 | 19-JUN-14:30 | 1246.46 | 27-JUN-16:10 | 1327.95 | 19-JUN-13:40 | 0.00 | 01-JUN-00:10 |
| July | 0.588673E+10 | 0.145759E+10 | 743.67 | 0.442841E+10 | 0.145832E+10 | 0.00 | 0.66 | 13-JUL-15:10 | 0.00 | 02-JUL-05:05 | 4910.46 | 13-JUL-15:10 | 4035.95 | 10-JUL-15:10 | 1178.73 | 21-JUL-14:30 | 1272.75 | 09-JUL-14:00 | 0.00 | 01-JUL-00:10 |
| August | 0.567498E+10 | 0.142925E+10 | 715.99 | 0.464748E+10 | 0.102751E+10 | 0.00 | 0.69 | 16-AUG-15:10 | 0.00 | 07-AUG-05:05 | 5191.76 | 02-AUG-15:10 | 4540.95 | 18-AUG-15:10 | 1193.21 | 02-AUG-14:20 | 1341.14 | 16-AUG-15:10 | 0.00 | 01-AUG-00:10 |
| September | 0.278537E+10 | 0.689292E+09 | 514.14 | 0.237993E+10 | 0.405436E+09 | 0.00 | 0.63 | 07-SEP-15:10 | 0.00 | 03-SEP-03:30 | 4788.41 | 07-SEP-15:10 | 4317.31 | 01-SEP-14:30 | 1179.52 | 14-SEP-10:10 | 1158.11 | 14-SEP-14:00 | 0.00 | 01-SEP-00:10 |
| October | 0.118533E+10 | 0.292678E+09 | 265.42 | 0.103064E+10 | 0.154688E+09 | 0.00 | 0.53 | 04-OCT-15:10 | 0.00 | 01-OCT-00:10 | 3889.39 | 04-OCT-15:20 | 3485.81 | 04-OCT-14:30 | 767.10 | 25-OCT-10:30 | 922.76 | 04-OCT-15:20 | 0.00 | 01-OCT-00:10 |
| November | 61718644.39 | 16105504.00 | 31.33 | 61703662.31 | 14982.08 | 0.00 | 0.18 | 02-NOV-13:00 | 0.00 | 01-NOV-00:10 | 1174.71 | 02-NOV-13:00 | 1174.71 | 02-NOV-13:00 | 4.38 | 04-NOV-15:10 | 305.37 | 02-NOV-13:00 | 0.00 | 01-NOV-00:10 |
| December | 9388507.90 | 2481453.32 | 5.83 | 9388507.90 | 0.00 | 0.00 | 0.13 | 17-DEC-14:30 | 0.00 | 01-DEC-00:10 | 867.53 | 17-DEC-14:30 | 867.53 | 17-DEC-14:30 | 0.00 | 17-DEC-15:10 | 227.95 | 17-DEC-14:30 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.211476E+11 | 0.527236E+10 | 3391.49 | 0.172879E+11 | 0.385971E+10 | 0.00 | ||||||||||||||
| Minimum of Months | 1541350.79 | 410537.85 | 3.33 | 1541350.79 | 0.00 | 0.00 | 0.04 | 0.00 | 272.29 | 272.29 | 0.00 | 72.34 | 0.00 | |||||||
| Maximum of Months | 0.588673E+10 | 0.145759E+10 | 743.67 | 0.464748E+10 | 0.145832E+10 | 0.00 | 0.69 | 0.00 | 5191.76 | 4540.95 | 1246.46 | 1341.14 | 0.00 |
Report: DXReportMonthly
For: SPLIT TNW COOLING COIL
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
| March | 5985637.52 | 1516339.90 | 2.83 | 5246182.54 | 739454.98 | 0.00 | 0.12 | 27-MAR-16:40 | 0.00 | 01-MAR-00:10 | 858.96 | 27-MAR-16:30 | 751.25 | 27-MAR-16:40 | 115.86 | 27-MAR-16:20 | 216.65 | 27-MAR-16:40 | 0.00 | 01-MAR-00:10 |
| April | 0.201795E+09 | 51840808.22 | 81.41 | 0.194075E+09 | 7720404.32 | 0.00 | 0.34 | 07-APR-16:05 | 0.00 | 01-APR-00:10 | 2350.82 | 07-APR-16:10 | 2350.82 | 07-APR-16:10 | 147.56 | 27-APR-17:40 | 601.28 | 07-APR-16:10 | 0.00 | 01-APR-00:10 |
| May | 0.101241E+10 | 0.258171E+09 | 287.22 | 0.965537E+09 | 46876233.27 | 0.00 | 0.49 | 30-MAY-16:10 | 0.00 | 01-MAY-00:10 | 3440.12 | 30-MAY-16:20 | 3380.41 | 30-MAY-16:10 | 596.08 | 31-MAY-17:20 | 882.06 | 30-MAY-16:10 | 0.00 | 01-MAY-00:10 |
| June | 0.346415E+10 | 0.857759E+09 | 618.23 | 0.272568E+10 | 0.738464E+09 | 0.00 | 0.66 | 19-JUN-17:10 | 0.00 | 01-JUN-02:30 | 4800.30 | 19-JUN-17:10 | 4006.56 | 19-JUN-17:10 | 1239.57 | 27-JUN-16:10 | 1285.35 | 19-JUN-17:10 | 0.00 | 01-JUN-00:10 |
| July | 0.559531E+10 | 0.138712E+10 | 744.00 | 0.416236E+10 | 0.143295E+10 | 0.00 | 0.62 | 13-JUL-16:08 | 0.02 | 02-JUL-05:05 | 4631.97 | 06-JUL-16:25 | 3662.62 | 07-JUL-15:10 | 1178.03 | 21-JUL-16:02 | 1164.93 | 13-JUL-15:10 | 0.00 | 01-JUL-00:10 |
| August | 0.494461E+10 | 0.125150E+10 | 710.69 | 0.395667E+10 | 0.987935E+09 | 0.00 | 0.63 | 02-AUG-15:30 | 0.00 | 07-AUG-05:05 | 4724.60 | 02-AUG-15:30 | 3851.68 | 18-AUG-16:17 | 1178.54 | 03-AUG-15:10 | 1200.22 | 02-AUG-15:30 | 0.00 | 01-AUG-00:10 |
| September | 0.196975E+10 | 0.490348E+09 | 470.83 | 0.160941E+10 | 0.360343E+09 | 0.00 | 0.50 | 07-SEP-15:30 | 0.00 | 03-SEP-03:10 | 3761.39 | 07-SEP-15:30 | 3079.42 | 01-SEP-14:40 | 967.89 | 14-SEP-10:10 | 914.30 | 07-SEP-15:30 | 0.00 | 01-SEP-00:10 |
| October | 0.355348E+09 | 87970731.90 | 120.00 | 0.284877E+09 | 70471366.99 | 0.00 | 0.34 | 04-OCT-15:30 | 0.00 | 01-OCT-00:10 | 2482.34 | 04-OCT-15:30 | 2048.01 | 04-OCT-15:20 | 551.40 | 03-OCT-15:10 | 600.79 | 04-OCT-15:30 | 0.00 | 01-OCT-00:10 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.175494E+11 | 0.438623E+10 | 3035.22 | 0.139039E+11 | 0.364550E+10 | 0.00 | ||||||||||||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Maximum of Months | 0.559531E+10 | 0.138712E+10 | 744.00 | 0.416236E+10 | 0.143295E+10 | 0.00 | 0.66 | 0.02 | 4800.30 | 4006.56 | 1239.57 | 1285.35 | 0.00 |
Report: DXReportMonthly
For: SPLIT TSE COOLING COIL
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 3856896.41 | 1020867.21 | 3.50 | 3856896.41 | -0.0 | 0.00 | 0.08 | 17-JAN-14:00 | 0.00 | 01-JAN-00:10 | 439.12 | 17-JAN-14:00 | 439.12 | 17-JAN-14:00 | 0.00 | 17-JAN-15:00 | 115.93 | 17-JAN-14:00 | 0.00 | 01-JAN-00:10 |
| February | 116920.41 | 31189.74 | 1.17 | 116920.41 | -0.0 | 0.00 | 0.01 | 19-FEB-14:20 | 0.00 | 01-FEB-00:10 | 33.14 | 19-FEB-14:20 | 33.14 | 19-FEB-14:20 | 0.00 | 19-FEB-14:40 | 8.84 | 19-FEB-14:20 | 0.00 | 01-FEB-00:10 |
| March | 94884794.21 | 24765897.50 | 50.50 | 93762728.04 | 1122066.17 | 0.00 | 0.22 | 01-MAR-13:40 | 0.00 | 01-MAR-00:10 | 1324.86 | 01-MAR-13:40 | 1324.86 | 01-MAR-13:40 | 112.54 | 27-MAR-16:10 | 342.35 | 01-MAR-13:40 | 0.00 | 01-MAR-00:10 |
| April | 0.478120E+09 | 0.121461E+09 | 143.00 | 0.464859E+09 | 13261165.98 | 0.00 | 0.51 | 07-APR-13:00 | 0.00 | 01-APR-00:10 | 3216.44 | 07-APR-13:00 | 3216.44 | 07-APR-13:00 | 288.28 | 09-APR-11:50 | 815.80 | 07-APR-13:00 | 0.00 | 01-APR-00:10 |
| May | 0.125243E+10 | 0.317434E+09 | 319.21 | 0.120345E+10 | 48976504.27 | 0.00 | 0.56 | 30-MAY-13:00 | 0.00 | 01-MAY-00:10 | 3531.13 | 30-MAY-13:00 | 3531.13 | 30-MAY-13:00 | 537.40 | 31-MAY-17:20 | 930.36 | 30-MAY-13:00 | 0.00 | 01-MAY-00:10 |
| June | 0.355332E+10 | 0.875867E+09 | 617.96 | 0.282756E+10 | 0.725763E+09 | 0.00 | 0.75 | 19-JUN-12:30 | 0.00 | 01-JUN-02:70 | 4807.47 | 19-JUN-12:50 | 4200.28 | 19-JUN-12:30 | 1199.14 | 27-JUN-16:10 | 1335.85 | 19-JUN-12:00 | 0.00 | 01-JUN-00:10 |
| July | 0.586578E+10 | 0.144475E+10 | 744.00 | 0.441091E+10 | 0.145487E+10 | 0.00 | 0.72 | 08-JUL-12:20 | 0.01 | 02-JUL-04:30 | 4890.50 | 08-JUL-12:30 | 3849.16 | 08-JUL-12:00 | 1145.65 | 23-JUL-15:30 | 1262.35 | 08-JUL-12:00 | 0.00 | 01-JUL-00:10 |
| August | 0.564731E+10 | 0.141391E+10 | 717.09 | 0.461937E+10 | 0.102794E+10 | 0.00 | 0.72 | 16-AUG-13:00 | 0.00 | 07-AUG-05:05 | 4860.48 | 16-AUG-12:50 | 4258.94 | 18-AUG-13:00 | 1133.45 | 04-AUG-08:40 | 1263.18 | 16-AUG-13:00 | 0.00 | 01-AUG-00:10 |
| September | 0.277652E+10 | 0.684191E+09 | 521.46 | 0.237584E+10 | 0.400677E+09 | 0.00 | 0.65 | 01-SEP-13:00 | 0.00 | 03-SEP-03:10 | 4317.14 | 07-SEP-13:30 | 4066.17 | 01-SEP-13:00 | 1288.37 | 14-SEP-10:10 | 1086.15 | 01-SEP-13:00 | 0.00 | 01-SEP-00:10 |
| October | 0.113598E+10 | 0.279376E+09 | 264.64 | 0.986628E+09 | 0.149355E+09 | 0.00 | 0.54 | 04-OCT-13:00 | 0.00 | 01-OCT-00:10 | 3676.81 | 25-OCT-10:30 | 3224.97 | 04-OCT-13:00 | 839.15 | 25-OCT-10:30 | 862.21 | 04-OCT-13:00 | 0.00 | 01-OCT-00:10 |
| November | 60192006.45 | 15684513.37 | 33.17 | 60179462.50 | 12543.95 | 0.00 | 0.22 | 02-NOV-13:00 | 0.00 | 01-NOV-00:10 | 1288.90 | 02-NOV-13:00 | 1288.90 | 02-NOV-13:00 | 3.82 | 04-NOV-15:10 | 333.07 | 02-NOV-13:00 | 0.00 | 01-NOV-00:10 |
| December | 8086093.43 | 2136788.02 | 5.83 | 8086093.43 | -0.0 | 0.00 | 0.12 | 17-DEC-13:30 | 0.00 | 01-DEC-00:10 | 710.35 | 17-DEC-13:30 | 710.35 | 17-DEC-13:30 | 0.00 | 17-DEC-12:50 | 186.97 | 17-DEC-13:30 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.208766E+11 | 0.518063E+10 | 3421.53 | 0.170546E+11 | 0.382197E+10 | 0.00 | ||||||||||||||
| Minimum of Months | 116920.41 | 31189.74 | 1.17 | 116920.41 | -0.0 | 0.00 | 0.01 | 0.00 | 33.14 | 33.14 | 0.00 | 8.84 | 0.00 | |||||||
| Maximum of Months | 0.586578E+10 | 0.144475E+10 | 744.00 | 0.461937E+10 | 0.145487E+10 | 0.00 | 0.75 | 0.01 | 4890.50 | 4258.94 | 1288.37 | 1335.85 | 0.00 |
Report: DXReportMonthly
For: SPLIT TNE COOLING COIL
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
| March | 259037.53 | 66230.85 | 0.83 | 222191.42 | 36846.11 | 0.00 | 0.03 | 27-MAR-16:20 | 0.00 | 01-MAR-00:10 | 188.18 | 27-MAR-16:20 | 159.90 | 27-MAR-16:20 | 28.28 | 27-MAR-16:20 | 47.97 | 27-MAR-16:20 | 0.00 | 01-MAR-00:10 |
| April | 0.173514E+09 | 44556355.70 | 83.03 | 0.167034E+09 | 6480184.40 | 0.00 | 0.30 | 08-APR-12:00 | 0.00 | 01-APR-00:10 | 1848.27 | 08-APR-12:00 | 1767.82 | 08-APR-12:00 | 163.69 | 09-APR-11:30 | 463.83 | 08-APR-12:00 | 0.00 | 01-APR-00:10 |
| May | 0.997480E+09 | 0.253998E+09 | 302.86 | 0.950272E+09 | 47208201.21 | 0.00 | 0.47 | 30-MAY-13:00 | 0.00 | 01-MAY-00:10 | 2928.45 | 31-MAY-14:00 | 2890.64 | 30-MAY-13:00 | 500.53 | 31-MAY-17:20 | 775.53 | 30-MAY-13:00 | 0.00 | 01-MAY-00:10 |
| June | 0.336736E+10 | 0.831672E+09 | 625.47 | 0.264801E+10 | 0.719352E+09 | 0.00 | 0.68 | 19-JUN-12:00 | 0.00 | 01-JUN-02:70 | 4287.21 | 19-JUN-10:40 | 3676.54 | 19-JUN-12:00 | 1193.32 | 27-JUN-16:10 | 1201.61 | 19-JUN-12:00 | 0.00 | 01-JUN-00:10 |
| July | 0.557857E+10 | 0.137631E+10 | 744.00 | 0.414579E+10 | 0.143278E+10 | 0.00 | 0.65 | 08-JUL-12:00 | 0.01 | 02-JUL-04:30 | 4300.81 | 08-JUL-12:30 | 3331.97 | 08-JUL-12:00 | 1099.27 | 21-JUL-16:10 | 1124.12 | 08-JUL-12:00 | 0.00 | 01-JUL-00:10 |
| August | 0.492119E+10 | 0.123951E+10 | 712.22 | 0.392996E+10 | 0.991225E+09 | 0.00 | 0.61 | 04-AUG-11:00 | 0.00 | 07-AUG-05:05 | 4090.23 | 04-AUG-10:30 | 3243.19 | 24-AUG-15:10 | 1120.31 | 04-AUG-08:40 | 1048.84 | 04-AUG-14:10 | 0.00 | 01-AUG-00:10 |
| September | 0.194803E+10 | 0.483635E+09 | 478.33 | 0.159060E+10 | 0.357425E+09 | 0.00 | 0.48 | 14-SEP-14:00 | 0.00 | 03-SEP-02:50 | 3092.06 | 14-SEP-14:00 | 2706.95 | 01-SEP-13:00 | 1104.83 | 14-SEP-10:10 | 815.05 | 14-SEP-14:00 | 0.00 | 01-SEP-00:10 |
| October | 0.330493E+09 | 81680073.87 | 113.08 | 0.262440E+09 | 68052999.44 | 0.00 | 0.31 | 25-OCT-10:40 | 0.00 | 01-OCT-00:10 | 2005.92 | 25-OCT-10:30 | 1587.90 | 04-OCT-13:00 | 573.36 | 25-OCT-10:30 | 483.20 | 25-OCT-10:40 | 0.00 | 01-OCT-00:10 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.173169E+11 | 0.431143E+10 | 3059.82 | 0.136943E+11 | 0.362256E+10 | 0.00 | ||||||||||||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Maximum of Months | 0.557857E+10 | 0.137631E+10 | 744.00 | 0.414579E+10 | 0.143278E+10 | 0.00 | 0.68 | 0.01 | 4300.81 | 3676.54 | 1193.32 | 1201.61 | 0.00 |
Report: DXReportMonthly
For: SPLIT TN1 COOLING COIL
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
| March | 324146.24 | 82894.48 | 1.00 | 278392.84 | 45753.40 | 0.00 | 0.03 | 27-MAR-16:20 | 0.00 | 01-MAR-00:10 | 172.54 | 27-MAR-16:20 | 146.22 | 27-MAR-16:20 | 26.32 | 27-MAR-16:20 | 43.97 | 27-MAR-16:20 | 0.00 | 01-MAR-00:10 |
| April | 0.107578E+09 | 27717336.17 | 66.92 | 0.102678E+09 | 4899707.32 | 0.00 | 0.25 | 07-APR-16:30 | 0.00 | 01-APR-00:10 | 1380.71 | 07-APR-16:30 | 1380.71 | 07-APR-16:30 | 99.41 | 09-APR-11:50 | 359.31 | 07-APR-16:30 | 0.00 | 01-APR-00:10 |
| May | 0.742277E+09 | 0.189935E+09 | 298.23 | 0.700172E+09 | 42104786.88 | 0.00 | 0.40 | 31-MAY-14:10 | 0.00 | 01-MAY-00:10 | 2353.13 | 31-MAY-14:10 | 2197.16 | 30-MAY-13:00 | 443.32 | 31-MAY-17:50 | 597.81 | 30-MAY-13:00 | 0.00 | 01-MAY-00:10 |
| June | 0.286877E+10 | 0.710495E+09 | 644.77 | 0.221580E+10 | 0.652971E+09 | 0.00 | 0.58 | 19-JUN-17:10 | 0.00 | 01-JUN-03:10 | 3411.03 | 19-JUN-17:10 | 2814.51 | 19-JUN-14:30 | 1047.43 | 27-JUN-16:10 | 936.52 | 19-JUN-12:00 | 0.00 | 01-JUN-00:10 |
| July | 0.471581E+10 | 0.116781E+10 | 744.00 | 0.345599E+10 | 0.125983E+10 | 0.00 | 0.55 | 08-JUL-12:40 | 0.03 | 02-JUL-05:10 | 3368.58 | 08-JUL-12:40 | 2623.91 | 07-JUL-14:20 | 985.55 | 23-JUL-15:30 | 886.14 | 08-JUL-12:00 | 0.00 | 01-JUL-00:10 |
| August | 0.404825E+10 | 0.102476E+10 | 721.10 | 0.318690E+10 | 0.861349E+09 | 0.00 | 0.54 | 16-AUG-15:10 | 0.00 | 08-AUG-01:40 | 3292.98 | 04-AUG-16:10 | 2580.07 | 24-AUG-16:17 | 911.93 | 03-AUG-16:10 | 866.21 | 16-AUG-15:10 | 0.00 | 01-AUG-00:10 |
| September | 0.164820E+10 | 0.409958E+09 | 486.17 | 0.131911E+10 | 0.329094E+09 | 0.00 | 0.43 | 14-SEP-14:00 | 0.00 | 03-SEP-04:00 | 2568.19 | 14-SEP-14:00 | 2144.13 | 01-SEP-14:30 | 879.85 | 14-SEP-10:10 | 681.18 | 14-SEP-14:00 | 0.00 | 01-SEP-00:10 |
| October | 0.234035E+09 | 57974066.52 | 117.33 | 0.182136E+09 | 51898890.17 | 0.00 | 0.25 | 04-OCT-16:10 | 0.00 | 01-OCT-00:10 | 1478.76 | 04-OCT-16:10 | 1209.39 | 04-OCT-14:20 | 399.55 | 25-OCT-10:40 | 359.91 | 04-OCT-16:10 | 0.00 | 01-OCT-00:10 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.143652E+11 | 0.358873E+10 | 3079.52 | 0.111631E+11 | 0.320219E+10 | 0.00 | ||||||||||||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Maximum of Months | 0.471581E+10 | 0.116781E+10 | 744.00 | 0.345599E+10 | 0.125983E+10 | 0.00 | 0.58 | 0.03 | 3411.03 | 2814.51 | 1047.43 | 936.52 | 0.00 |
Report: DXReportMonthly
For: SPLIT TN2 COOLING COIL
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
| March | 206327.56 | 52794.32 | 0.83 | 176663.56 | 29664.00 | 0.00 | 0.02 | 27-MAR-16:20 | 0.00 | 01-MAR-00:10 | 107.15 | 27-MAR-16:20 | 90.66 | 27-MAR-16:20 | 16.49 | 27-MAR-16:20 | 27.36 | 27-MAR-16:20 | 0.00 | 01-MAR-00:10 |
| April | 0.108691E+09 | 27999486.19 | 67.25 | 0.103757E+09 | 4933933.70 | 0.00 | 0.25 | 07-APR-16:17 | 0.00 | 01-APR-00:10 | 1372.25 | 07-APR-16:17 | 1372.25 | 07-APR-16:17 | 104.55 | 09-APR-11:40 | 357.03 | 07-APR-16:30 | 0.00 | 01-APR-00:10 |
| May | 0.746528E+09 | 0.191004E+09 | 299.02 | 0.704296E+09 | 42231716.03 | 0.00 | 0.40 | 31-MAY-14:10 | 0.00 | 01-MAY-00:10 | 2354.66 | 31-MAY-14:10 | 2212.10 | 30-MAY-13:00 | 440.07 | 31-MAY-17:50 | 601.51 | 30-MAY-13:00 | 0.00 | 01-MAY-00:10 |
| June | 0.286596E+10 | 0.709742E+09 | 645.36 | 0.221368E+10 | 0.652279E+09 | 0.00 | 0.58 | 19-JUN-17:10 | 0.00 | 01-JUN-03:10 | 3394.36 | 19-JUN-17:10 | 2813.41 | 19-JUN-14:30 | 1045.93 | 27-JUN-16:10 | 940.81 | 19-JUN-12:00 | 0.00 | 01-JUN-00:10 |
| July | 0.471553E+10 | 0.116755E+10 | 744.00 | 0.345555E+10 | 0.125998E+10 | 0.00 | 0.56 | 08-JUL-12:40 | 0.03 | 02-JUL-05:10 | 3380.92 | 08-JUL-12:40 | 2619.74 | 07-JUL-14:10 | 984.97 | 23-JUL-15:30 | 889.79 | 08-JUL-12:00 | 0.00 | 01-JUL-00:10 |
| August | 0.404840E+10 | 0.102463E+10 | 720.99 | 0.318685E+10 | 0.861549E+09 | 0.00 | 0.54 | 04-AUG-15:10 | 0.00 | 08-AUG-01:40 | 3281.28 | 04-AUG-16:10 | 2572.22 | 24-AUG-15:10 | 909.45 | 03-AUG-15:10 | 862.28 | 16-AUG-15:10 | 0.00 | 01-AUG-00:10 |
| September | 0.165007E+10 | 0.410394E+09 | 487.17 | 0.132096E+10 | 0.329105E+09 | 0.00 | 0.43 | 14-SEP-14:00 | 0.00 | 03-SEP-04:00 | 2564.74 | 14-SEP-14:00 | 2143.87 | 01-SEP-14:20 | 884.95 | 14-SEP-10:10 | 680.16 | 14-SEP-14:00 | 0.00 | 01-SEP-00:10 |
| October | 0.235797E+09 | 58401338.44 | 117.00 | 0.183577E+09 | 52219280.35 | 0.00 | 0.25 | 04-OCT-15:10 | 0.00 | 01-OCT-00:10 | 1461.30 | 04-OCT-16:10 | 1213.52 | 04-OCT-14:10 | 407.53 | 25-OCT-10:40 | 358.24 | 04-OCT-13:00 | 0.00 | 01-OCT-00:10 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.143712E+11 | 0.358977E+10 | 3081.61 | 0.111689E+11 | 0.320232E+10 | 0.00 | ||||||||||||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Maximum of Months | 0.471553E+10 | 0.116755E+10 | 744.00 | 0.345555E+10 | 0.125998E+10 | 0.00 | 0.58 | 0.03 | 3394.36 | 2813.41 | 1045.93 | 940.81 | 0.00 |
Report: DXReportMonthly
For: SPLIT TS1 COOLING COIL
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 6239437.06 | 1644402.94 | 4.17 | 6239437.06 | -0.0 | 0.00 | 0.11 | 17-JAN-14:20 | 0.00 | 01-JAN-00:10 | 598.21 | 17-JAN-14:20 | 598.21 | 17-JAN-14:20 | 0.00 | 17-JAN-13:50 | 157.15 | 17-JAN-14:20 | 0.00 | 01-JAN-00:10 |
| February | 1923362.30 | 512742.89 | 5.50 | 1923362.30 | -0.0 | 0.00 | 0.03 | 20-FEB-14:10 | 0.00 | 01-FEB-00:10 | 148.77 | 20-FEB-14:10 | 148.77 | 20-FEB-14:10 | 0.00 | 20-FEB-13:50 | 39.65 | 20-FEB-14:10 | 0.00 | 01-FEB-00:10 |
| March | 92625990.44 | 24164058.84 | 55.40 | 91390088.50 | 1235901.93 | 0.00 | 0.23 | 03-MAR-14:00 | 0.00 | 01-MAR-00:10 | 1258.77 | 03-MAR-14:00 | 1258.77 | 03-MAR-14:00 | 113.80 | 27-MAR-16:10 | 323.99 | 03-MAR-14:00 | 0.00 | 01-MAR-00:10 |
| April | 0.383601E+09 | 97814362.33 | 144.00 | 0.371285E+09 | 12316235.01 | 0.00 | 0.47 | 07-APR-13:00 | 0.00 | 01-APR-00:10 | 2702.89 | 07-APR-13:00 | 2702.89 | 07-APR-13:00 | 251.41 | 09-APR-12:00 | 690.51 | 07-APR-13:00 | 0.00 | 01-APR-00:10 |
| May | 0.986862E+09 | 0.251469E+09 | 323.89 | 0.942376E+09 | 44485767.18 | 0.00 | 0.49 | 30-MAY-13:00 | 0.00 | 01-MAY-00:10 | 2887.70 | 31-MAY-13:50 | 2832.26 | 30-MAY-13:00 | 474.34 | 31-MAY-17:20 | 755.05 | 30-MAY-13:00 | 0.00 | 01-MAY-00:10 |
| June | 0.306095E+10 | 0.757089E+09 | 640.46 | 0.239772E+10 | 0.663228E+09 | 0.00 | 0.65 | 19-JUN-13:00 | 0.00 | 01-JUN-03:10 | 3878.41 | 19-JUN-13:00 | 3349.03 | 19-JUN-13:00 | 1056.35 | 27-JUN-16:10 | 1079.54 | 19-JUN-12:40 | 0.00 | 01-JUN-00:10 |
| July | 0.501110E+10 | 0.123959E+10 | 744.00 | 0.372423E+10 | 0.128687E+10 | 0.00 | 0.64 | 08-JUL-12:30 | 0.01 | 02-JUL-05:05 | 3957.14 | 08-JUL-12:30 | 3150.19 | 10-JUL-13:40 | 1049.42 | 23-JUL-15:30 | 1030.05 | 08-JUL-12:20 | 0.00 | 01-JUL-00:10 |
| August | 0.478796E+10 | 0.120557E+10 | 725.92 | 0.388339E+10 | 0.904575E+09 | 0.00 | 0.67 | 16-AUG-13:00 | 0.00 | 08-AUG-01:50 | 4148.20 | 16-AUG-13:00 | 3538.40 | 18-AUG-13:30 | 954.09 | 04-AUG-10:40 | 1087.35 | 16-AUG-13:00 | 0.00 | 01-AUG-00:10 |
| September | 0.249039E+10 | 0.615845E+09 | 546.85 | 0.211293E+10 | 0.377459E+09 | 0.00 | 0.60 | 07-SEP-13:40 | 0.00 | 03-SEP-05:05 | 3777.52 | 07-SEP-13:40 | 3438.25 | 01-SEP-13:30 | 1095.02 | 14-SEP-10:10 | 946.34 | 14-SEP-13:40 | 0.00 | 01-SEP-00:10 |
| October | 0.109294E+10 | 0.269930E+09 | 312.96 | 0.947043E+09 | 0.145900E+09 | 0.00 | 0.52 | 04-OCT-13:00 | 0.00 | 01-OCT-00:10 | 3150.70 | 04-OCT-13:00 | 2841.04 | 04-OCT-13:20 | 735.60 | 25-OCT-10:30 | 764.23 | 04-OCT-13:00 | 0.00 | 01-OCT-00:10 |
| November | 67733119.91 | 17644391.62 | 38.83 | 67717158.13 | 15961.78 | 0.00 | 0.24 | 02-NOV-13:00 | 0.00 | 01-NOV-00:10 | 1299.65 | 02-NOV-13:00 | 1299.65 | 02-NOV-13:00 | 4.77 | 04-NOV-15:20 | 334.91 | 02-NOV-13:00 | 0.00 | 01-NOV-00:10 |
| December | 13297914.95 | 3500967.93 | 8.00 | 13297914.95 | -0.0 | 0.00 | 0.16 | 17-DEC-14:00 | 0.00 | 01-DEC-00:10 | 880.21 | 17-DEC-14:00 | 880.21 | 17-DEC-14:00 | 0.00 | 17-DEC-14:20 | 230.21 | 17-DEC-14:00 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.179956E+11 | 0.448478E+10 | 3549.97 | 0.145595E+11 | 0.343609E+10 | 0.00 | ||||||||||||||
| Minimum of Months | 1923362.30 | 512742.89 | 4.17 | 1923362.30 | -0.0 | 0.00 | 0.03 | 0.00 | 148.77 | 148.77 | 0.00 | 39.65 | 0.00 | |||||||
| Maximum of Months | 0.501110E+10 | 0.123959E+10 | 744.00 | 0.388339E+10 | 0.128687E+10 | 0.00 | 0.67 | 0.01 | 4148.20 | 3538.40 | 1095.02 | 1087.35 | 0.00 |
Report: DXReportMonthly
For: SPLIT TS2 COOLING COIL
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 6325273.84 | 1666585.28 | 4.17 | 6325273.84 | 0.00 | 0.00 | 0.11 | 17-JAN-14:20 | 0.00 | 01-JAN-00:10 | 605.72 | 17-JAN-14:20 | 605.72 | 17-JAN-14:20 | 0.00 | 17-JAN-13:30 | 159.08 | 17-JAN-14:20 | 0.00 | 01-JAN-00:10 |
| February | 2247794.67 | 599105.64 | 6.00 | 2247794.67 | -0.0 | 0.00 | 0.03 | 20-FEB-14:10 | 0.00 | 01-FEB-00:10 | 156.40 | 20-FEB-14:10 | 156.40 | 20-FEB-14:10 | 0.00 | 19-FEB-14:00 | 41.67 | 20-FEB-14:10 | 0.00 | 01-FEB-00:10 |
| March | 94668215.98 | 24693989.22 | 55.75 | 93469010.50 | 1199205.48 | 0.00 | 0.23 | 03-MAR-14:00 | 0.00 | 01-MAR-00:10 | 1274.25 | 03-MAR-14:00 | 1274.25 | 03-MAR-14:00 | 111.51 | 27-MAR-16:10 | 327.79 | 03-MAR-14:00 | 0.00 | 01-MAR-00:10 |
| April | 0.388084E+09 | 98941961.16 | 145.00 | 0.375727E+09 | 12357335.27 | 0.00 | 0.47 | 07-APR-13:00 | 0.00 | 01-APR-00:10 | 2723.86 | 07-APR-13:00 | 2723.86 | 07-APR-13:00 | 253.98 | 09-APR-12:00 | 695.29 | 07-APR-13:00 | 0.00 | 01-APR-00:10 |
| May | 0.991688E+09 | 0.252646E+09 | 324.75 | 0.947097E+09 | 44591352.55 | 0.00 | 0.49 | 30-MAY-13:00 | 0.00 | 01-MAY-00:10 | 2893.25 | 31-MAY-13:40 | 2847.23 | 30-MAY-13:00 | 470.88 | 31-MAY-17:20 | 758.57 | 30-MAY-13:00 | 0.00 | 01-MAY-00:10 |
| June | 0.305811E+10 | 0.756290E+09 | 640.57 | 0.239563E+10 | 0.662481E+09 | 0.00 | 0.66 | 19-JUN-13:00 | 0.00 | 01-JUN-03:10 | 3890.10 | 19-JUN-13:00 | 3360.65 | 19-JUN-13:00 | 1054.91 | 27-JUN-16:10 | 1082.69 | 19-JUN-12:30 | 0.00 | 01-JUN-00:10 |
| July | 0.501083E+10 | 0.123928E+10 | 744.00 | 0.372383E+10 | 0.128699E+10 | 0.00 | 0.64 | 08-JUL-12:30 | 0.01 | 02-JUL-05:05 | 3970.20 | 08-JUL-12:30 | 3154.95 | 10-JUL-13:40 | 1048.92 | 23-JUL-15:30 | 1033.01 | 08-JUL-12:20 | 0.00 | 01-JUL-00:10 |
| August | 0.478808E+10 | 0.120531E+10 | 725.58 | 0.388328E+10 | 0.904797E+09 | 0.00 | 0.67 | 16-AUG-13:00 | 0.00 | 08-AUG-01:50 | 4151.61 | 16-AUG-13:00 | 3548.65 | 18-AUG-13:20 | 955.56 | 04-AUG-10:40 | 1087.72 | 16-AUG-13:00 | 0.00 | 01-AUG-00:10 |
| September | 0.249251E+10 | 0.616240E+09 | 547.14 | 0.211504E+10 | 0.377466E+09 | 0.00 | 0.61 | 07-SEP-13:40 | 0.00 | 03-SEP-05:05 | 3778.19 | 07-SEP-13:40 | 3446.36 | 01-SEP-13:20 | 1099.53 | 14-SEP-10:10 | 945.77 | 14-SEP-13:40 | 0.00 | 01-SEP-00:10 |
| October | 0.109588E+10 | 0.270608E+09 | 312.54 | 0.950040E+09 | 0.145841E+09 | 0.00 | 0.52 | 04-OCT-13:00 | 0.00 | 01-OCT-00:10 | 3163.02 | 04-OCT-13:00 | 2850.37 | 04-OCT-13:20 | 739.47 | 25-OCT-10:30 | 766.79 | 04-OCT-13:00 | 0.00 | 01-OCT-00:10 |
| November | 69306301.51 | 18049372.14 | 39.50 | 69289631.08 | 16670.43 | 0.00 | 0.24 | 02-NOV-13:00 | 0.00 | 01-NOV-00:10 | 1318.88 | 02-NOV-13:00 | 1318.88 | 02-NOV-13:00 | 4.90 | 04-NOV-15:20 | 339.64 | 02-NOV-13:00 | 0.00 | 01-NOV-00:10 |
| December | 13699939.16 | 3605626.47 | 8.17 | 13699939.16 | -0.0 | 0.00 | 0.17 | 17-DEC-13:50 | 0.00 | 01-DEC-00:10 | 892.56 | 17-DEC-13:50 | 892.56 | 17-DEC-13:50 | 0.00 | 17-DEC-12:40 | 233.34 | 17-DEC-13:50 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.180114E+11 | 0.448793E+10 | 3553.17 | 0.145757E+11 | 0.343574E+10 | 0.00 | ||||||||||||||
| Minimum of Months | 2247794.67 | 599105.64 | 4.17 | 2247794.67 | -0.0 | 0.00 | 0.03 | 0.00 | 156.40 | 156.40 | 0.00 | 41.67 | 0.00 | |||||||
| Maximum of Months | 0.501083E+10 | 0.123928E+10 | 744.00 | 0.388328E+10 | 0.128699E+10 | 0.00 | 0.67 | 0.01 | 4151.61 | 3548.65 | 1099.53 | 1087.72 | 0.00 |
Report: WindowReportMonthly
For: GWINDOW1 S SWA
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 212.64 | 139.47 | 73.18 | 211.52 | 194.46 | 0.00 | 0.00 | 0.00 |
| February | 281.89 | 187.48 | 94.41 | 287.79 | 191.52 | 0.00 | 0.00 | 0.00 |
| March | 246.77 | 134.59 | 112.18 | 267.33 | 134.12 | 0.00 | 0.00 | 0.00 |
| April | 202.81 | 84.53 | 118.28 | 230.89 | 96.52 | 0.00 | 0.00 | 0.00 |
| May | 170.95 | 35.27 | 135.68 | 206.40 | 59.24 | 0.00 | 0.00 | 0.00 |
| June | 161.95 | 25.67 | 136.28 | 218.15 | 33.21 | 0.00 | 0.00 | 0.00 |
| July | 168.92 | 29.58 | 139.34 | 251.52 | 15.18 | 0.00 | 0.00 | 0.00 |
| August | 224.66 | 82.97 | 141.69 | 333.24 | 24.15 | 0.00 | 0.00 | 0.00 |
| September | 238.13 | 120.16 | 117.97 | 313.79 | 53.07 | 0.00 | 0.00 | 0.00 |
| October | 333.15 | 208.32 | 124.83 | 408.62 | 101.33 | 0.00 | 0.00 | 0.00 |
| November | 233.08 | 140.32 | 92.75 | 249.04 | 142.08 | 0.00 | 0.00 | 0.00 |
| December | 229.47 | 162.84 | 66.62 | 237.90 | 176.03 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 225.08 | 112.20 | 112.88 | 268.02 | 101.23 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 161.95 | 25.67 | 66.62 | 206.40 | 15.18 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 333.15 | 208.32 | 141.69 | 408.62 | 194.46 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: GWINDOW1 W SWA
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 55.78 | 22.92 | 32.87 | 34.79 | 137.85 | 0.00 | 0.00 | 0.00 |
| February | 81.76 | 35.87 | 45.89 | 57.59 | 138.36 | 0.00 | 0.00 | 0.00 |
| March | 121.66 | 56.40 | 65.26 | 113.67 | 87.78 | 0.00 | 0.00 | 0.00 |
| April | 131.99 | 56.35 | 75.64 | 139.73 | 61.97 | 0.00 | 0.00 | 0.00 |
| May | 154.27 | 58.62 | 95.65 | 184.20 | 37.66 | 0.00 | 0.00 | 0.00 |
| June | 168.84 | 68.25 | 100.59 | 221.37 | 21.19 | 0.00 | 0.00 | 0.00 |
| July | 157.93 | 59.47 | 98.45 | 222.18 | 9.82 | 0.00 | 0.00 | 0.00 |
| August | 174.60 | 80.77 | 93.84 | 243.38 | 15.64 | 0.00 | 0.00 | 0.00 |
| September | 124.21 | 54.27 | 69.94 | 153.88 | 34.85 | 0.00 | 0.00 | 0.00 |
| October | 122.70 | 59.56 | 63.13 | 134.87 | 68.57 | 0.00 | 0.00 | 0.00 |
| November | 57.87 | 16.79 | 41.08 | 38.88 | 99.44 | 0.00 | 0.00 | 0.00 |
| December | 51.39 | 22.26 | 29.13 | 32.78 | 127.09 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 117.17 | 49.41 | 67.76 | 131.97 | 69.63 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 51.39 | 16.79 | 29.13 | 32.78 | 9.82 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 174.60 | 80.77 | 100.59 | 243.38 | 138.36 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: GWINDOW1 W NWA
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 55.78 | 22.92 | 32.87 | 35.75 | 135.74 | 0.00 | 0.00 | 0.00 |
| February | 81.76 | 35.87 | 45.89 | 59.10 | 135.50 | 0.00 | 0.00 | 0.00 |
| March | 121.66 | 56.40 | 65.26 | 115.82 | 85.62 | 0.00 | 0.00 | 0.00 |
| April | 131.99 | 56.35 | 75.64 | 142.45 | 59.59 | 0.00 | 0.00 | 0.00 |
| May | 154.27 | 58.62 | 95.65 | 185.92 | 36.47 | 0.00 | 0.00 | 0.00 |
| June | 168.84 | 68.25 | 100.59 | 221.83 | 21.04 | 0.00 | 0.00 | 0.00 |
| July | 157.93 | 59.47 | 98.45 | 222.68 | 9.65 | 0.00 | 0.00 | 0.00 |
| August | 174.60 | 80.77 | 93.84 | 244.60 | 15.10 | 0.00 | 0.00 | 0.00 |
| September | 124.21 | 54.27 | 69.94 | 155.47 | 33.73 | 0.00 | 0.00 | 0.00 |
| October | 122.70 | 59.56 | 63.13 | 138.62 | 63.91 | 0.00 | 0.00 | 0.00 |
| November | 57.87 | 16.79 | 41.08 | 41.91 | 93.88 | 0.00 | 0.00 | 0.00 |
| December | 51.39 | 22.26 | 29.13 | 34.04 | 124.05 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 117.17 | 49.41 | 67.76 | 133.71 | 67.47 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 51.39 | 16.79 | 29.13 | 34.04 | 9.65 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 174.60 | 80.77 | 100.59 | 244.60 | 135.74 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: GWINDOW1 N NWA
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 40.95 | 0.00 | 40.95 | 3.20 | 217.58 | 0.00 | 0.00 | 0.00 |
| February | 56.04 | 0.00 | 56.04 | 6.89 | 219.65 | 0.00 | 0.00 | 0.00 |
| March | 77.74 | 0.00 | 77.73 | 34.45 | 137.56 | 0.00 | 0.00 | 0.00 |
| April | 93.40 | 0.31 | 93.09 | 69.53 | 91.83 | 0.00 | 0.00 | 0.00 |
| May | 124.33 | 4.50 | 119.83 | 128.90 | 53.80 | 0.00 | 0.00 | 0.00 |
| June | 131.10 | 6.83 | 124.27 | 163.67 | 30.94 | 0.00 | 0.00 | 0.00 |
| July | 127.21 | 4.82 | 122.38 | 181.75 | 14.74 | 0.00 | 0.00 | 0.00 |
| August | 112.65 | 1.53 | 111.13 | 157.33 | 22.80 | 0.00 | 0.00 | 0.00 |
| September | 84.81 | 0.04 | 84.77 | 90.43 | 52.28 | 0.00 | 0.00 | 0.00 |
| October | 73.35 | 0.00 | 73.35 | 54.69 | 99.78 | 0.00 | 0.00 | 0.00 |
| November | 51.45 | 0.00 | 51.45 | 17.17 | 147.92 | 0.00 | 0.00 | 0.00 |
| December | 35.72 | 0.00 | 35.72 | 2.09 | 199.16 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 84.23 | 1.51 | 82.71 | 76.31 | 106.70 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 35.72 | 0.00 | 35.72 | 2.09 | 14.74 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 131.10 | 6.83 | 124.27 | 181.75 | 219.65 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: GWINDOW1 S SEA
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 212.64 | 139.47 | 73.18 | 218.27 | 167.63 | 0.00 | 0.00 | 0.00 |
| February | 281.89 | 187.48 | 94.41 | 294.89 | 168.04 | 0.00 | 0.00 | 0.00 |
| March | 246.77 | 134.59 | 112.18 | 272.06 | 122.13 | 0.00 | 0.00 | 0.00 |
| April | 202.81 | 84.53 | 118.28 | 230.73 | 95.83 | 0.00 | 0.00 | 0.00 |
| May | 170.95 | 35.27 | 135.68 | 200.53 | 66.04 | 0.00 | 0.00 | 0.00 |
| June | 161.95 | 25.67 | 136.28 | 209.14 | 44.65 | 0.00 | 0.00 | 0.00 |
| July | 168.92 | 29.58 | 139.34 | 236.35 | 30.79 | 0.00 | 0.00 | 0.00 |
| August | 224.66 | 82.97 | 141.69 | 319.99 | 41.90 | 0.00 | 0.00 | 0.00 |
| September | 238.13 | 120.16 | 117.97 | 305.55 | 69.44 | 0.00 | 0.00 | 0.00 |
| October | 333.15 | 208.32 | 124.83 | 405.24 | 111.15 | 0.00 | 0.00 | 0.00 |
| November | 233.08 | 140.32 | 92.75 | 250.14 | 139.63 | 0.00 | 0.00 | 0.00 |
| December | 229.47 | 162.84 | 66.62 | 242.29 | 160.14 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 225.08 | 112.20 | 112.88 | 265.37 | 101.05 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 161.95 | 25.67 | 66.62 | 200.53 | 30.79 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 333.15 | 208.32 | 141.69 | 405.24 | 168.04 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: GWINDOW1 E SEA
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 56.28 | 22.56 | 33.72 | 37.96 | 116.28 | 0.00 | 0.00 | 0.00 |
| February | 86.74 | 40.20 | 46.54 | 65.51 | 116.27 | 0.00 | 0.00 | 0.00 |
| March | 111.75 | 47.33 | 64.43 | 104.63 | 80.91 | 0.00 | 0.00 | 0.00 |
| April | 134.14 | 59.04 | 75.10 | 142.00 | 60.40 | 0.00 | 0.00 | 0.00 |
| May | 161.87 | 64.56 | 97.31 | 189.32 | 41.40 | 0.00 | 0.00 | 0.00 |
| June | 150.24 | 54.43 | 95.81 | 189.76 | 27.97 | 0.00 | 0.00 | 0.00 |
| July | 150.77 | 54.35 | 96.42 | 202.37 | 19.62 | 0.00 | 0.00 | 0.00 |
| August | 169.73 | 76.48 | 93.25 | 226.71 | 26.49 | 0.00 | 0.00 | 0.00 |
| September | 126.97 | 57.13 | 69.84 | 150.79 | 44.54 | 0.00 | 0.00 | 0.00 |
| October | 115.02 | 52.18 | 62.84 | 122.76 | 73.95 | 0.00 | 0.00 | 0.00 |
| November | 71.16 | 27.37 | 43.79 | 57.51 | 94.42 | 0.00 | 0.00 | 0.00 |
| December | 55.62 | 26.25 | 29.38 | 39.61 | 112.03 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 116.04 | 48.55 | 67.50 | 127.84 | 67.58 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 55.62 | 22.56 | 29.38 | 37.96 | 19.62 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 169.73 | 76.48 | 97.31 | 226.71 | 116.28 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: GWINDOW1 E NEA
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 56.28 | 22.56 | 33.72 | 35.56 | 133.01 | 0.00 | 0.00 | 0.00 |
| February | 86.74 | 40.20 | 46.54 | 63.02 | 129.73 | 0.00 | 0.00 | 0.00 |
| March | 111.75 | 47.33 | 64.43 | 103.20 | 86.08 | 0.00 | 0.00 | 0.00 |
| April | 134.14 | 59.04 | 75.10 | 144.19 | 58.04 | 0.00 | 0.00 | 0.00 |
| May | 161.87 | 64.56 | 97.31 | 194.82 | 35.68 | 0.00 | 0.00 | 0.00 |
| June | 150.24 | 54.43 | 95.81 | 196.47 | 20.49 | 0.00 | 0.00 | 0.00 |
| July | 150.77 | 54.35 | 96.42 | 213.16 | 9.55 | 0.00 | 0.00 | 0.00 |
| August | 169.73 | 76.48 | 93.25 | 237.19 | 14.60 | 0.00 | 0.00 | 0.00 |
| September | 126.97 | 57.13 | 69.84 | 157.92 | 32.84 | 0.00 | 0.00 | 0.00 |
| October | 115.02 | 52.18 | 62.84 | 128.15 | 62.23 | 0.00 | 0.00 | 0.00 |
| November | 71.16 | 27.37 | 43.79 | 59.59 | 90.95 | 0.00 | 0.00 | 0.00 |
| December | 55.62 | 26.25 | 29.38 | 38.63 | 120.24 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 116.04 | 48.55 | 67.50 | 131.46 | 65.77 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 55.62 | 22.56 | 29.38 | 35.56 | 9.55 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 169.73 | 76.48 | 97.31 | 237.19 | 133.01 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: GWINDOW1 N NEA
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 40.95 | 0.00 | 40.95 | 3.14 | 217.60 | 0.00 | 0.00 | 0.00 |
| February | 56.04 | 0.00 | 56.04 | 6.77 | 219.70 | 0.00 | 0.00 | 0.00 |
| March | 77.74 | 0.00 | 77.73 | 34.23 | 137.06 | 0.00 | 0.00 | 0.00 |
| April | 93.40 | 0.31 | 93.09 | 68.97 | 91.50 | 0.00 | 0.00 | 0.00 |
| May | 124.33 | 4.50 | 119.83 | 128.27 | 53.35 | 0.00 | 0.00 | 0.00 |
| June | 131.10 | 6.83 | 124.27 | 163.63 | 30.57 | 0.00 | 0.00 | 0.00 |
| July | 127.21 | 4.82 | 122.38 | 181.61 | 14.50 | 0.00 | 0.00 | 0.00 |
| August | 112.65 | 1.53 | 111.13 | 157.09 | 22.48 | 0.00 | 0.00 | 0.00 |
| September | 84.81 | 0.04 | 84.77 | 90.07 | 52.07 | 0.00 | 0.00 | 0.00 |
| October | 73.35 | 0.00 | 73.35 | 54.22 | 99.12 | 0.00 | 0.00 | 0.00 |
| November | 51.45 | 0.00 | 51.45 | 16.76 | 148.34 | 0.00 | 0.00 | 0.00 |
| December | 35.72 | 0.00 | 35.72 | 2.02 | 199.27 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 84.23 | 1.51 | 82.71 | 76.03 | 106.49 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 35.72 | 0.00 | 35.72 | 2.02 | 14.50 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 131.10 | 6.83 | 124.27 | 181.61 | 219.70 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: GWINDOW1 N N1A
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 40.95 | 0.00 | 40.95 | 2.98 | 221.27 | 0.00 | 0.00 | 0.00 |
| February | 56.04 | 0.00 | 56.04 | 6.57 | 223.33 | 0.00 | 0.00 | 0.00 |
| March | 77.74 | 0.00 | 77.73 | 33.89 | 139.69 | 0.00 | 0.00 | 0.00 |
| April | 93.40 | 0.31 | 93.09 | 68.95 | 93.56 | 0.00 | 0.00 | 0.00 |
| May | 124.33 | 4.50 | 119.83 | 127.66 | 55.42 | 0.00 | 0.00 | 0.00 |
| June | 131.10 | 6.83 | 124.27 | 164.41 | 30.87 | 0.00 | 0.00 | 0.00 |
| July | 127.21 | 4.82 | 122.38 | 183.03 | 14.30 | 0.00 | 0.00 | 0.00 |
| August | 112.65 | 1.53 | 111.13 | 158.99 | 22.10 | 0.00 | 0.00 | 0.00 |
| September | 84.81 | 0.04 | 84.77 | 91.02 | 52.27 | 0.00 | 0.00 | 0.00 |
| October | 73.35 | 0.00 | 73.35 | 54.35 | 101.23 | 0.00 | 0.00 | 0.00 |
| November | 51.45 | 0.00 | 51.45 | 16.46 | 151.30 | 0.00 | 0.00 | 0.00 |
| December | 35.72 | 0.00 | 35.72 | 1.95 | 202.38 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 84.23 | 1.51 | 82.71 | 76.32 | 108.33 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 35.72 | 0.00 | 35.72 | 1.95 | 14.30 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 131.10 | 6.83 | 124.27 | 183.03 | 223.33 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: GWINDOW1 N N2A
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 40.95 | 0.00 | 40.95 | 2.98 | 221.27 | 0.00 | 0.00 | 0.00 |
| February | 56.04 | 0.00 | 56.04 | 6.56 | 223.34 | 0.00 | 0.00 | 0.00 |
| March | 77.74 | 0.00 | 77.73 | 33.89 | 139.67 | 0.00 | 0.00 | 0.00 |
| April | 93.40 | 0.31 | 93.09 | 68.91 | 93.56 | 0.00 | 0.00 | 0.00 |
| May | 124.33 | 4.50 | 119.83 | 127.65 | 55.39 | 0.00 | 0.00 | 0.00 |
| June | 131.10 | 6.83 | 124.27 | 164.41 | 30.85 | 0.00 | 0.00 | 0.00 |
| July | 127.21 | 4.82 | 122.38 | 183.03 | 14.29 | 0.00 | 0.00 | 0.00 |
| August | 112.65 | 1.53 | 111.13 | 158.98 | 22.09 | 0.00 | 0.00 | 0.00 |
| September | 84.81 | 0.04 | 84.77 | 91.00 | 52.27 | 0.00 | 0.00 | 0.00 |
| October | 73.35 | 0.00 | 73.35 | 54.34 | 101.20 | 0.00 | 0.00 | 0.00 |
| November | 51.45 | 0.00 | 51.45 | 16.43 | 151.37 | 0.00 | 0.00 | 0.00 |
| December | 35.72 | 0.00 | 35.72 | 1.95 | 202.39 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 84.23 | 1.51 | 82.71 | 76.31 | 108.33 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 35.72 | 0.00 | 35.72 | 1.95 | 14.29 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 131.10 | 6.83 | 124.27 | 183.03 | 223.34 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: GWINDOW1 S S1A
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 212.64 | 139.47 | 73.18 | 210.48 | 198.07 | 0.00 | 0.00 | 0.00 |
| February | 281.89 | 187.48 | 94.41 | 286.31 | 195.25 | 0.00 | 0.00 | 0.00 |
| March | 246.77 | 134.59 | 112.18 | 266.21 | 136.82 | 0.00 | 0.00 | 0.00 |
| April | 202.81 | 84.53 | 118.28 | 229.49 | 99.35 | 0.00 | 0.00 | 0.00 |
| May | 170.95 | 35.27 | 135.68 | 204.71 | 61.59 | 0.00 | 0.00 | 0.00 |
| June | 161.95 | 25.67 | 136.28 | 218.84 | 33.15 | 0.00 | 0.00 | 0.00 |
| July | 168.92 | 29.58 | 139.34 | 252.75 | 14.76 | 0.00 | 0.00 | 0.00 |
| August | 224.66 | 82.97 | 141.69 | 334.73 | 23.51 | 0.00 | 0.00 | 0.00 |
| September | 238.13 | 120.16 | 117.97 | 314.31 | 53.00 | 0.00 | 0.00 | 0.00 |
| October | 333.15 | 208.32 | 124.83 | 408.33 | 102.52 | 0.00 | 0.00 | 0.00 |
| November | 233.08 | 140.32 | 92.75 | 247.20 | 146.48 | 0.00 | 0.00 | 0.00 |
| December | 229.47 | 162.84 | 66.62 | 236.74 | 179.49 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 225.08 | 112.20 | 112.88 | 267.52 | 103.14 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 161.95 | 25.67 | 66.62 | 204.71 | 14.76 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 333.15 | 208.32 | 141.69 | 408.33 | 198.07 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: GWINDOW1 S S2A
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 212.64 | 139.47 | 73.18 | 210.85 | 196.84 | 0.00 | 0.00 | 0.00 |
| February | 281.89 | 187.48 | 94.41 | 286.74 | 194.18 | 0.00 | 0.00 | 0.00 |
| March | 246.77 | 134.59 | 112.18 | 266.51 | 136.15 | 0.00 | 0.00 | 0.00 |
| April | 202.81 | 84.53 | 118.28 | 229.40 | 99.40 | 0.00 | 0.00 | 0.00 |
| May | 170.95 | 35.27 | 135.68 | 204.00 | 62.26 | 0.00 | 0.00 | 0.00 |
| June | 161.95 | 25.67 | 136.28 | 218.31 | 33.58 | 0.00 | 0.00 | 0.00 |
| July | 168.92 | 29.58 | 139.34 | 251.98 | 15.32 | 0.00 | 0.00 | 0.00 |
| August | 224.66 | 82.97 | 141.69 | 334.01 | 24.10 | 0.00 | 0.00 | 0.00 |
| September | 238.13 | 120.16 | 117.97 | 313.84 | 53.58 | 0.00 | 0.00 | 0.00 |
| October | 333.15 | 208.32 | 124.83 | 408.07 | 102.91 | 0.00 | 0.00 | 0.00 |
| November | 233.08 | 140.32 | 92.75 | 247.15 | 146.47 | 0.00 | 0.00 | 0.00 |
| December | 229.47 | 162.84 | 66.62 | 237.01 | 178.66 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 225.08 | 112.20 | 112.88 | 267.33 | 103.10 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 161.95 | 25.67 | 66.62 | 204.00 | 15.32 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 333.15 | 208.32 | 141.69 | 408.07 | 196.84 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MWINDOW1 S SWA
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 212.64 | 139.47 | 73.18 | 208.27 | 201.21 | 0.00 | 0.00 | 0.00 |
| February | 281.89 | 187.48 | 94.41 | 282.91 | 199.27 | 0.00 | 0.00 | 0.00 |
| March | 246.77 | 134.59 | 112.18 | 261.01 | 144.21 | 0.00 | 0.00 | 0.00 |
| April | 202.81 | 84.53 | 118.28 | 222.09 | 108.94 | 0.00 | 0.00 | 0.00 |
| May | 170.95 | 35.27 | 135.68 | 195.55 | 70.71 | 0.00 | 0.00 | 0.00 |
| June | 161.95 | 25.67 | 136.28 | 215.26 | 34.90 | 0.00 | 0.00 | 0.00 |
| July | 168.92 | 29.58 | 139.34 | 249.93 | 15.63 | 0.00 | 0.00 | 0.00 |
| August | 224.66 | 82.97 | 141.69 | 332.38 | 23.88 | 0.00 | 0.00 | 0.00 |
| September | 238.13 | 120.16 | 117.97 | 312.79 | 52.93 | 0.00 | 0.00 | 0.00 |
| October | 333.15 | 208.32 | 124.83 | 407.30 | 100.72 | 0.00 | 0.00 | 0.00 |
| November | 233.08 | 140.32 | 92.75 | 247.32 | 143.68 | 0.00 | 0.00 | 0.00 |
| December | 229.47 | 162.84 | 66.62 | 235.04 | 180.75 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 225.08 | 112.20 | 112.88 | 264.16 | 105.87 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 161.95 | 25.67 | 66.62 | 195.55 | 15.63 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 333.15 | 208.32 | 141.69 | 407.30 | 201.21 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MWINDOW1 W SWA
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 55.78 | 22.92 | 32.87 | 33.53 | 143.20 | 0.00 | 0.00 | 0.00 |
| February | 81.76 | 35.87 | 45.89 | 55.39 | 144.62 | 0.00 | 0.00 | 0.00 |
| March | 121.66 | 56.40 | 65.26 | 109.44 | 94.27 | 0.00 | 0.00 | 0.00 |
| April | 131.99 | 56.35 | 75.64 | 133.70 | 69.80 | 0.00 | 0.00 | 0.00 |
| May | 154.27 | 58.62 | 95.65 | 176.67 | 44.78 | 0.00 | 0.00 | 0.00 |
| June | 168.84 | 68.25 | 100.59 | 219.24 | 22.26 | 0.00 | 0.00 | 0.00 |
| July | 157.93 | 59.47 | 98.45 | 221.03 | 10.12 | 0.00 | 0.00 | 0.00 |
| August | 174.60 | 80.77 | 93.84 | 242.86 | 15.47 | 0.00 | 0.00 | 0.00 |
| September | 124.21 | 54.27 | 69.94 | 153.40 | 34.80 | 0.00 | 0.00 | 0.00 |
| October | 122.70 | 59.56 | 63.13 | 134.27 | 68.20 | 0.00 | 0.00 | 0.00 |
| November | 57.87 | 16.79 | 41.08 | 38.11 | 100.85 | 0.00 | 0.00 | 0.00 |
| December | 51.39 | 22.26 | 29.13 | 31.68 | 131.01 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 117.17 | 49.41 | 67.76 | 129.64 | 72.88 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 51.39 | 16.79 | 29.13 | 31.68 | 10.12 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 174.60 | 80.77 | 100.59 | 242.86 | 144.62 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MWINDOW1 W NWA
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 55.78 | 22.92 | 32.87 | 34.71 | 140.99 | 0.00 | 0.00 | 0.00 |
| February | 81.76 | 35.87 | 45.89 | 57.36 | 141.49 | 0.00 | 0.00 | 0.00 |
| March | 121.66 | 56.40 | 65.26 | 112.39 | 91.22 | 0.00 | 0.00 | 0.00 |
| April | 131.99 | 56.35 | 75.64 | 136.33 | 67.37 | 0.00 | 0.00 | 0.00 |
| May | 154.27 | 58.62 | 95.65 | 177.38 | 44.44 | 0.00 | 0.00 | 0.00 |
| June | 168.84 | 68.25 | 100.59 | 219.61 | 22.19 | 0.00 | 0.00 | 0.00 |
| July | 157.93 | 59.47 | 98.45 | 221.48 | 10.01 | 0.00 | 0.00 | 0.00 |
| August | 174.60 | 80.77 | 93.84 | 243.95 | 15.10 | 0.00 | 0.00 | 0.00 |
| September | 124.21 | 54.27 | 69.94 | 154.85 | 34.01 | 0.00 | 0.00 | 0.00 |
| October | 122.70 | 59.56 | 63.13 | 138.12 | 63.98 | 0.00 | 0.00 | 0.00 |
| November | 57.87 | 16.79 | 41.08 | 41.14 | 95.94 | 0.00 | 0.00 | 0.00 |
| December | 51.39 | 22.26 | 29.13 | 33.23 | 127.92 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 117.17 | 49.41 | 67.76 | 131.41 | 70.82 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 51.39 | 16.79 | 29.13 | 33.23 | 10.01 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 174.60 | 80.77 | 100.59 | 243.95 | 141.49 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MWINDOW1 N NWA
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 40.95 | 0.00 | 40.95 | 2.62 | 226.08 | 0.00 | 0.00 | 0.00 |
| February | 56.04 | 0.00 | 56.04 | 5.82 | 229.74 | 0.00 | 0.00 | 0.00 |
| March | 77.74 | 0.00 | 77.73 | 30.84 | 147.12 | 0.00 | 0.00 | 0.00 |
| April | 93.40 | 0.31 | 93.09 | 61.51 | 104.15 | 0.00 | 0.00 | 0.00 |
| May | 124.33 | 4.50 | 119.83 | 115.69 | 65.54 | 0.00 | 0.00 | 0.00 |
| June | 131.10 | 6.83 | 124.27 | 160.83 | 32.55 | 0.00 | 0.00 | 0.00 |
| July | 127.21 | 4.82 | 122.38 | 180.39 | 15.28 | 0.00 | 0.00 | 0.00 |
| August | 112.65 | 1.53 | 111.13 | 156.92 | 22.79 | 0.00 | 0.00 | 0.00 |
| September | 84.81 | 0.04 | 84.77 | 89.95 | 52.72 | 0.00 | 0.00 | 0.00 |
| October | 73.35 | 0.00 | 73.35 | 54.54 | 99.79 | 0.00 | 0.00 | 0.00 |
| November | 51.45 | 0.00 | 51.45 | 16.52 | 151.08 | 0.00 | 0.00 | 0.00 |
| December | 35.72 | 0.00 | 35.72 | 1.77 | 205.44 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 84.23 | 1.51 | 82.71 | 73.57 | 112.03 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 35.72 | 0.00 | 35.72 | 1.77 | 15.28 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 131.10 | 6.83 | 124.27 | 180.39 | 229.74 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MWINDOW1 S SEA
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 212.64 | 139.47 | 73.18 | 208.04 | 201.07 | 0.00 | 0.00 | 0.00 |
| February | 281.89 | 187.48 | 94.41 | 282.46 | 199.00 | 0.00 | 0.00 | 0.00 |
| March | 246.77 | 134.59 | 112.18 | 260.51 | 143.31 | 0.00 | 0.00 | 0.00 |
| April | 202.81 | 84.53 | 118.28 | 221.17 | 108.56 | 0.00 | 0.00 | 0.00 |
| May | 170.95 | 35.27 | 135.68 | 194.97 | 70.30 | 0.00 | 0.00 | 0.00 |
| June | 161.95 | 25.67 | 136.28 | 215.18 | 34.52 | 0.00 | 0.00 | 0.00 |
| July | 168.92 | 29.58 | 139.34 | 249.77 | 15.37 | 0.00 | 0.00 | 0.00 |
| August | 224.66 | 82.97 | 141.69 | 332.13 | 23.54 | 0.00 | 0.00 | 0.00 |
| September | 238.13 | 120.16 | 117.97 | 312.50 | 52.65 | 0.00 | 0.00 | 0.00 |
| October | 333.15 | 208.32 | 124.83 | 406.89 | 100.30 | 0.00 | 0.00 | 0.00 |
| November | 233.08 | 140.32 | 92.75 | 246.62 | 144.02 | 0.00 | 0.00 | 0.00 |
| December | 229.47 | 162.84 | 66.62 | 234.67 | 180.68 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 225.08 | 112.20 | 112.88 | 263.75 | 105.58 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 161.95 | 25.67 | 66.62 | 194.97 | 15.37 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 333.15 | 208.32 | 141.69 | 406.89 | 201.07 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MWINDOW1 E SEA
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 56.28 | 22.56 | 33.72 | 33.62 | 140.47 | 0.00 | 0.00 | 0.00 |
| February | 86.74 | 40.20 | 46.54 | 59.72 | 138.80 | 0.00 | 0.00 | 0.00 |
| March | 111.75 | 47.33 | 64.43 | 97.49 | 95.25 | 0.00 | 0.00 | 0.00 |
| April | 134.14 | 59.04 | 75.10 | 135.40 | 68.26 | 0.00 | 0.00 | 0.00 |
| May | 161.87 | 64.56 | 97.31 | 185.21 | 43.99 | 0.00 | 0.00 | 0.00 |
| June | 150.24 | 54.43 | 95.81 | 194.05 | 21.70 | 0.00 | 0.00 | 0.00 |
| July | 150.77 | 54.35 | 96.42 | 211.62 | 10.03 | 0.00 | 0.00 | 0.00 |
| August | 169.73 | 76.48 | 93.25 | 235.44 | 14.97 | 0.00 | 0.00 | 0.00 |
| September | 126.97 | 57.13 | 69.84 | 155.84 | 33.91 | 0.00 | 0.00 | 0.00 |
| October | 115.02 | 52.18 | 62.84 | 124.13 | 66.71 | 0.00 | 0.00 | 0.00 |
| November | 71.16 | 27.37 | 43.79 | 55.90 | 97.76 | 0.00 | 0.00 | 0.00 |
| December | 55.62 | 26.25 | 29.38 | 36.75 | 127.37 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 116.04 | 48.55 | 67.50 | 127.56 | 71.23 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 55.62 | 22.56 | 29.38 | 33.62 | 10.03 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 169.73 | 76.48 | 97.31 | 235.44 | 140.47 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MWINDOW1 E NEA
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 56.28 | 22.56 | 33.72 | 34.48 | 137.99 | 0.00 | 0.00 | 0.00 |
| February | 86.74 | 40.20 | 46.54 | 61.21 | 135.30 | 0.00 | 0.00 | 0.00 |
| March | 111.75 | 47.33 | 64.43 | 100.04 | 91.81 | 0.00 | 0.00 | 0.00 |
| April | 134.14 | 59.04 | 75.10 | 137.85 | 65.77 | 0.00 | 0.00 | 0.00 |
| May | 161.87 | 64.56 | 97.31 | 185.90 | 43.64 | 0.00 | 0.00 | 0.00 |
| June | 150.24 | 54.43 | 95.81 | 194.42 | 21.63 | 0.00 | 0.00 | 0.00 |
| July | 150.77 | 54.35 | 96.42 | 212.06 | 9.92 | 0.00 | 0.00 | 0.00 |
| August | 169.73 | 76.48 | 93.25 | 236.55 | 14.60 | 0.00 | 0.00 | 0.00 |
| September | 126.97 | 57.13 | 69.84 | 157.25 | 33.11 | 0.00 | 0.00 | 0.00 |
| October | 115.02 | 52.18 | 62.84 | 127.72 | 62.25 | 0.00 | 0.00 | 0.00 |
| November | 71.16 | 27.37 | 43.79 | 58.79 | 92.72 | 0.00 | 0.00 | 0.00 |
| December | 55.62 | 26.25 | 29.38 | 37.82 | 123.85 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 116.04 | 48.55 | 67.50 | 129.14 | 69.02 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 55.62 | 22.56 | 29.38 | 34.48 | 9.92 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 169.73 | 76.48 | 97.31 | 236.55 | 137.99 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MWINDOW1 N NEA
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 40.95 | 0.00 | 40.95 | 2.55 | 226.08 | 0.00 | 0.00 | 0.00 |
| February | 56.04 | 0.00 | 56.04 | 5.69 | 229.82 | 0.00 | 0.00 | 0.00 |
| March | 77.74 | 0.00 | 77.73 | 30.51 | 146.35 | 0.00 | 0.00 | 0.00 |
| April | 93.40 | 0.31 | 93.09 | 60.55 | 103.83 | 0.00 | 0.00 | 0.00 |
| May | 124.33 | 4.50 | 119.83 | 115.07 | 65.18 | 0.00 | 0.00 | 0.00 |
| June | 131.10 | 6.83 | 124.27 | 160.75 | 32.21 | 0.00 | 0.00 | 0.00 |
| July | 127.21 | 4.82 | 122.38 | 180.22 | 15.04 | 0.00 | 0.00 | 0.00 |
| August | 112.65 | 1.53 | 111.13 | 156.65 | 22.46 | 0.00 | 0.00 | 0.00 |
| September | 84.81 | 0.04 | 84.77 | 89.56 | 52.48 | 0.00 | 0.00 | 0.00 |
| October | 73.35 | 0.00 | 73.35 | 53.88 | 99.04 | 0.00 | 0.00 | 0.00 |
| November | 51.45 | 0.00 | 51.45 | 16.07 | 151.43 | 0.00 | 0.00 | 0.00 |
| December | 35.72 | 0.00 | 35.72 | 1.69 | 205.56 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 84.23 | 1.51 | 82.71 | 73.22 | 111.80 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 35.72 | 0.00 | 35.72 | 1.69 | 15.04 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 131.10 | 6.83 | 124.27 | 180.22 | 229.82 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MWINDOW1 N N1A
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 40.95 | 0.00 | 40.95 | 2.43 | 229.64 | 0.00 | 0.00 | 0.00 |
| February | 56.04 | 0.00 | 56.04 | 5.60 | 232.93 | 0.00 | 0.00 | 0.00 |
| March | 77.74 | 0.00 | 77.73 | 30.64 | 148.56 | 0.00 | 0.00 | 0.00 |
| April | 93.40 | 0.31 | 93.09 | 61.23 | 105.86 | 0.00 | 0.00 | 0.00 |
| May | 124.33 | 4.50 | 119.83 | 115.94 | 66.21 | 0.00 | 0.00 | 0.00 |
| June | 131.10 | 6.83 | 124.27 | 162.38 | 32.02 | 0.00 | 0.00 | 0.00 |
| July | 127.21 | 4.82 | 122.38 | 182.16 | 14.63 | 0.00 | 0.00 | 0.00 |
| August | 112.65 | 1.53 | 111.13 | 158.83 | 22.05 | 0.00 | 0.00 | 0.00 |
| September | 84.81 | 0.04 | 84.77 | 90.64 | 52.70 | 0.00 | 0.00 | 0.00 |
| October | 73.35 | 0.00 | 73.35 | 53.92 | 101.93 | 0.00 | 0.00 | 0.00 |
| November | 51.45 | 0.00 | 51.45 | 15.67 | 155.26 | 0.00 | 0.00 | 0.00 |
| December | 35.72 | 0.00 | 35.72 | 1.63 | 209.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 84.23 | 1.51 | 82.71 | 73.88 | 113.56 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 35.72 | 0.00 | 35.72 | 1.63 | 14.63 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 131.10 | 6.83 | 124.27 | 182.16 | 232.93 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MWINDOW1 N N2A
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 40.95 | 0.00 | 40.95 | 2.43 | 229.64 | 0.00 | 0.00 | 0.00 |
| February | 56.04 | 0.00 | 56.04 | 5.59 | 232.94 | 0.00 | 0.00 | 0.00 |
| March | 77.74 | 0.00 | 77.73 | 30.63 | 148.51 | 0.00 | 0.00 | 0.00 |
| April | 93.40 | 0.31 | 93.09 | 61.16 | 105.87 | 0.00 | 0.00 | 0.00 |
| May | 124.33 | 4.50 | 119.83 | 115.91 | 66.20 | 0.00 | 0.00 | 0.00 |
| June | 131.10 | 6.83 | 124.27 | 162.38 | 32.01 | 0.00 | 0.00 | 0.00 |
| July | 127.21 | 4.82 | 122.38 | 182.15 | 14.62 | 0.00 | 0.00 | 0.00 |
| August | 112.65 | 1.53 | 111.13 | 158.82 | 22.04 | 0.00 | 0.00 | 0.00 |
| September | 84.81 | 0.04 | 84.77 | 90.62 | 52.69 | 0.00 | 0.00 | 0.00 |
| October | 73.35 | 0.00 | 73.35 | 53.90 | 101.90 | 0.00 | 0.00 | 0.00 |
| November | 51.45 | 0.00 | 51.45 | 15.63 | 155.32 | 0.00 | 0.00 | 0.00 |
| December | 35.72 | 0.00 | 35.72 | 1.63 | 209.02 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 84.23 | 1.51 | 82.71 | 73.86 | 113.56 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 35.72 | 0.00 | 35.72 | 1.63 | 14.62 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 131.10 | 6.83 | 124.27 | 182.15 | 232.94 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MWINDOW1 S S1A
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 212.64 | 139.47 | 73.18 | 207.12 | 204.91 | 0.00 | 0.00 | 0.00 |
| February | 281.89 | 187.48 | 94.41 | 281.54 | 202.70 | 0.00 | 0.00 | 0.00 |
| March | 246.77 | 134.59 | 112.18 | 259.89 | 147.54 | 0.00 | 0.00 | 0.00 |
| April | 202.81 | 84.53 | 118.28 | 221.18 | 111.70 | 0.00 | 0.00 | 0.00 |
| May | 170.95 | 35.27 | 135.68 | 195.79 | 71.31 | 0.00 | 0.00 | 0.00 |
| June | 161.95 | 25.67 | 136.28 | 216.74 | 34.30 | 0.00 | 0.00 | 0.00 |
| July | 168.92 | 29.58 | 139.34 | 251.68 | 14.96 | 0.00 | 0.00 | 0.00 |
| August | 224.66 | 82.97 | 141.69 | 334.15 | 23.16 | 0.00 | 0.00 | 0.00 |
| September | 238.13 | 120.16 | 117.97 | 313.45 | 52.82 | 0.00 | 0.00 | 0.00 |
| October | 333.15 | 208.32 | 124.83 | 406.88 | 102.36 | 0.00 | 0.00 | 0.00 |
| November | 233.08 | 140.32 | 92.75 | 245.24 | 148.71 | 0.00 | 0.00 | 0.00 |
| December | 229.47 | 162.84 | 66.62 | 233.57 | 185.02 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 225.08 | 112.20 | 112.88 | 263.95 | 107.75 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 161.95 | 25.67 | 66.62 | 195.79 | 14.96 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 333.15 | 208.32 | 141.69 | 406.88 | 204.91 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MWINDOW1 S S2A
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 212.64 | 139.47 | 73.18 | 207.10 | 204.91 | 0.00 | 0.00 | 0.00 |
| February | 281.89 | 187.48 | 94.41 | 281.52 | 202.69 | 0.00 | 0.00 | 0.00 |
| March | 246.77 | 134.59 | 112.18 | 259.87 | 147.47 | 0.00 | 0.00 | 0.00 |
| April | 202.81 | 84.53 | 118.28 | 221.13 | 111.70 | 0.00 | 0.00 | 0.00 |
| May | 170.95 | 35.27 | 135.68 | 195.77 | 71.30 | 0.00 | 0.00 | 0.00 |
| June | 161.95 | 25.67 | 136.28 | 216.74 | 34.29 | 0.00 | 0.00 | 0.00 |
| July | 168.92 | 29.58 | 139.34 | 251.67 | 14.95 | 0.00 | 0.00 | 0.00 |
| August | 224.66 | 82.97 | 141.69 | 334.15 | 23.15 | 0.00 | 0.00 | 0.00 |
| September | 238.13 | 120.16 | 117.97 | 313.44 | 52.81 | 0.00 | 0.00 | 0.00 |
| October | 333.15 | 208.32 | 124.83 | 406.87 | 102.35 | 0.00 | 0.00 | 0.00 |
| November | 233.08 | 140.32 | 92.75 | 245.20 | 148.77 | 0.00 | 0.00 | 0.00 |
| December | 229.47 | 162.84 | 66.62 | 233.55 | 185.03 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 225.08 | 112.20 | 112.88 | 263.93 | 107.74 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 161.95 | 25.67 | 66.62 | 195.77 | 14.95 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 333.15 | 208.32 | 141.69 | 406.87 | 204.91 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: TWINDOW1 S SWA
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 212.64 | 139.47 | 73.18 | 208.28 | 193.90 | 0.00 | 0.00 | 0.00 |
| February | 281.89 | 187.48 | 94.41 | 282.54 | 191.88 | 0.00 | 0.00 | 0.00 |
| March | 246.77 | 134.59 | 112.18 | 259.67 | 137.67 | 0.00 | 0.00 | 0.00 |
| April | 202.81 | 84.53 | 118.28 | 222.28 | 100.98 | 0.00 | 0.00 | 0.00 |
| May | 170.95 | 35.27 | 135.68 | 196.89 | 63.53 | 0.00 | 0.00 | 0.00 |
| June | 161.95 | 25.67 | 136.28 | 212.03 | 33.55 | 0.00 | 0.00 | 0.00 |
| July | 168.92 | 29.58 | 139.34 | 245.60 | 15.26 | 0.00 | 0.00 | 0.00 |
| August | 224.66 | 82.97 | 141.69 | 327.93 | 23.04 | 0.00 | 0.00 | 0.00 |
| September | 238.13 | 120.16 | 117.97 | 311.16 | 49.35 | 0.00 | 0.00 | 0.00 |
| October | 333.15 | 208.32 | 124.83 | 408.57 | 90.48 | 0.00 | 0.00 | 0.00 |
| November | 233.08 | 140.32 | 92.75 | 249.08 | 134.07 | 0.00 | 0.00 | 0.00 |
| December | 229.47 | 162.84 | 66.62 | 235.16 | 173.19 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 225.08 | 112.20 | 112.88 | 263.27 | 100.06 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 161.95 | 25.67 | 66.62 | 196.89 | 15.26 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 333.15 | 208.32 | 141.69 | 408.57 | 193.90 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: TWINDOW1 W SWA
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 55.78 | 22.92 | 32.87 | 33.19 | 137.95 | 0.00 | 0.00 | 0.00 |
| February | 81.76 | 35.87 | 45.89 | 54.59 | 139.20 | 0.00 | 0.00 | 0.00 |
| March | 121.66 | 56.40 | 65.26 | 108.30 | 89.56 | 0.00 | 0.00 | 0.00 |
| April | 131.99 | 56.35 | 75.64 | 133.60 | 64.21 | 0.00 | 0.00 | 0.00 |
| May | 154.27 | 58.62 | 95.65 | 177.58 | 39.97 | 0.00 | 0.00 | 0.00 |
| June | 168.84 | 68.25 | 100.59 | 216.97 | 21.25 | 0.00 | 0.00 | 0.00 |
| July | 157.93 | 59.47 | 98.45 | 218.10 | 9.82 | 0.00 | 0.00 | 0.00 |
| August | 174.60 | 80.77 | 93.84 | 239.93 | 14.85 | 0.00 | 0.00 | 0.00 |
| September | 124.21 | 54.27 | 69.94 | 152.21 | 32.19 | 0.00 | 0.00 | 0.00 |
| October | 122.70 | 59.56 | 63.13 | 134.67 | 60.78 | 0.00 | 0.00 | 0.00 |
| November | 57.87 | 16.79 | 41.08 | 38.63 | 93.72 | 0.00 | 0.00 | 0.00 |
| December | 51.39 | 22.26 | 29.13 | 31.33 | 125.53 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 117.17 | 49.41 | 67.76 | 128.79 | 68.69 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 51.39 | 16.79 | 29.13 | 31.33 | 9.82 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 174.60 | 80.77 | 100.59 | 239.93 | 139.20 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: TWINDOW1 W NWA
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 55.78 | 22.92 | 32.87 | 34.96 | 136.08 | 0.00 | 0.00 | 0.00 |
| February | 81.76 | 35.87 | 45.89 | 57.52 | 136.63 | 0.00 | 0.00 | 0.00 |
| March | 121.66 | 56.40 | 65.26 | 112.08 | 87.59 | 0.00 | 0.00 | 0.00 |
| April | 131.99 | 56.35 | 75.64 | 136.42 | 62.93 | 0.00 | 0.00 | 0.00 |
| May | 154.27 | 58.62 | 95.65 | 178.50 | 39.77 | 0.00 | 0.00 | 0.00 |
| June | 168.84 | 68.25 | 100.59 | 217.43 | 21.25 | 0.00 | 0.00 | 0.00 |
| July | 157.93 | 59.47 | 98.45 | 218.68 | 9.77 | 0.00 | 0.00 | 0.00 |
| August | 174.60 | 80.77 | 93.84 | 241.44 | 14.58 | 0.00 | 0.00 | 0.00 |
| September | 124.21 | 54.27 | 69.94 | 154.54 | 31.27 | 0.00 | 0.00 | 0.00 |
| October | 122.70 | 59.56 | 63.13 | 139.94 | 57.38 | 0.00 | 0.00 | 0.00 |
| November | 57.87 | 16.79 | 41.08 | 41.87 | 90.98 | 0.00 | 0.00 | 0.00 |
| December | 51.39 | 22.26 | 29.13 | 33.49 | 123.04 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 117.17 | 49.41 | 67.76 | 131.09 | 67.21 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 51.39 | 16.79 | 29.13 | 33.49 | 9.77 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 174.60 | 80.77 | 100.59 | 241.44 | 136.63 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: TWINDOW1 N NWA
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 40.95 | 0.00 | 40.95 | 2.88 | 218.60 | 0.00 | 0.00 | 0.00 |
| February | 56.04 | 0.00 | 56.04 | 6.08 | 222.42 | 0.00 | 0.00 | 0.00 |
| March | 77.74 | 0.00 | 77.73 | 30.75 | 141.92 | 0.00 | 0.00 | 0.00 |
| April | 93.40 | 0.31 | 93.09 | 62.11 | 97.70 | 0.00 | 0.00 | 0.00 |
| May | 124.33 | 4.50 | 119.83 | 118.15 | 59.10 | 0.00 | 0.00 | 0.00 |
| June | 131.10 | 6.83 | 124.27 | 158.11 | 31.40 | 0.00 | 0.00 | 0.00 |
| July | 127.21 | 4.82 | 122.38 | 176.57 | 15.02 | 0.00 | 0.00 | 0.00 |
| August | 112.65 | 1.53 | 111.13 | 153.45 | 22.13 | 0.00 | 0.00 | 0.00 |
| September | 84.81 | 0.04 | 84.77 | 89.72 | 48.64 | 0.00 | 0.00 | 0.00 |
| October | 73.35 | 0.00 | 73.35 | 57.39 | 89.85 | 0.00 | 0.00 | 0.00 |
| November | 51.45 | 0.00 | 51.45 | 17.50 | 143.47 | 0.00 | 0.00 | 0.00 |
| December | 35.72 | 0.00 | 35.72 | 1.97 | 197.91 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 84.23 | 1.51 | 82.71 | 73.34 | 106.70 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 35.72 | 0.00 | 35.72 | 1.97 | 15.02 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 131.10 | 6.83 | 124.27 | 176.57 | 222.42 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: TWINDOW1 S SEA
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 212.64 | 139.47 | 73.18 | 207.93 | 193.63 | 0.00 | 0.00 | 0.00 |
| February | 281.89 | 187.48 | 94.41 | 281.84 | 191.37 | 0.00 | 0.00 | 0.00 |
| March | 246.77 | 134.59 | 112.18 | 258.74 | 136.48 | 0.00 | 0.00 | 0.00 |
| April | 202.81 | 84.53 | 118.28 | 220.76 | 100.10 | 0.00 | 0.00 | 0.00 |
| May | 170.95 | 35.27 | 135.68 | 195.45 | 62.64 | 0.00 | 0.00 | 0.00 |
| June | 161.95 | 25.67 | 136.28 | 211.68 | 32.97 | 0.00 | 0.00 | 0.00 |
| July | 168.92 | 29.58 | 139.34 | 245.31 | 14.88 | 0.00 | 0.00 | 0.00 |
| August | 224.66 | 82.97 | 141.69 | 327.51 | 22.51 | 0.00 | 0.00 | 0.00 |
| September | 238.13 | 120.16 | 117.97 | 310.45 | 48.83 | 0.00 | 0.00 | 0.00 |
| October | 333.15 | 208.32 | 124.83 | 407.47 | 89.59 | 0.00 | 0.00 | 0.00 |
| November | 233.08 | 140.32 | 92.75 | 248.11 | 134.05 | 0.00 | 0.00 | 0.00 |
| December | 229.47 | 162.84 | 66.62 | 234.61 | 172.96 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 225.08 | 112.20 | 112.88 | 262.49 | 99.48 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 161.95 | 25.67 | 66.62 | 195.45 | 14.88 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 333.15 | 208.32 | 141.69 | 407.47 | 193.63 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: TWINDOW1 E SEA
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 56.28 | 22.56 | 33.72 | 33.90 | 135.67 | 0.00 | 0.00 | 0.00 |
| February | 86.74 | 40.20 | 46.54 | 59.97 | 134.17 | 0.00 | 0.00 | 0.00 |
| March | 111.75 | 47.33 | 64.43 | 96.75 | 91.00 | 0.00 | 0.00 | 0.00 |
| April | 134.14 | 59.04 | 75.10 | 135.70 | 63.07 | 0.00 | 0.00 | 0.00 |
| May | 161.87 | 64.56 | 97.31 | 186.19 | 39.54 | 0.00 | 0.00 | 0.00 |
| June | 150.24 | 54.43 | 95.81 | 191.98 | 20.81 | 0.00 | 0.00 | 0.00 |
| July | 150.77 | 54.35 | 96.42 | 208.82 | 9.74 | 0.00 | 0.00 | 0.00 |
| August | 169.73 | 76.48 | 93.25 | 232.49 | 14.37 | 0.00 | 0.00 | 0.00 |
| September | 126.97 | 57.13 | 69.84 | 154.77 | 31.58 | 0.00 | 0.00 | 0.00 |
| October | 115.02 | 52.18 | 62.84 | 124.99 | 59.89 | 0.00 | 0.00 | 0.00 |
| November | 71.16 | 27.37 | 43.79 | 57.01 | 91.09 | 0.00 | 0.00 | 0.00 |
| December | 55.62 | 26.25 | 29.38 | 37.08 | 122.43 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 116.04 | 48.55 | 67.50 | 127.10 | 67.41 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 55.62 | 22.56 | 29.38 | 33.90 | 9.74 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 169.73 | 76.48 | 97.31 | 232.49 | 135.67 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: TWINDOW1 E NEA
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 56.28 | 22.56 | 33.72 | 35.02 | 133.26 | 0.00 | 0.00 | 0.00 |
| February | 86.74 | 40.20 | 46.54 | 61.87 | 130.73 | 0.00 | 0.00 | 0.00 |
| March | 111.75 | 47.33 | 64.43 | 99.99 | 88.36 | 0.00 | 0.00 | 0.00 |
| April | 134.14 | 59.04 | 75.10 | 138.22 | 61.51 | 0.00 | 0.00 | 0.00 |
| May | 161.87 | 64.56 | 97.31 | 187.05 | 39.32 | 0.00 | 0.00 | 0.00 |
| June | 150.24 | 54.43 | 95.81 | 192.45 | 20.82 | 0.00 | 0.00 | 0.00 |
| July | 150.77 | 54.35 | 96.42 | 209.40 | 9.70 | 0.00 | 0.00 | 0.00 |
| August | 169.73 | 76.48 | 93.25 | 234.01 | 14.08 | 0.00 | 0.00 | 0.00 |
| September | 126.97 | 57.13 | 69.84 | 156.96 | 30.61 | 0.00 | 0.00 | 0.00 |
| October | 115.02 | 52.18 | 62.84 | 129.76 | 55.77 | 0.00 | 0.00 | 0.00 |
| November | 71.16 | 27.37 | 43.79 | 59.87 | 87.86 | 0.00 | 0.00 | 0.00 |
| December | 55.62 | 26.25 | 29.38 | 38.38 | 119.15 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 116.04 | 48.55 | 67.50 | 129.04 | 65.57 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 55.62 | 22.56 | 29.38 | 35.02 | 9.70 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 169.73 | 76.48 | 97.31 | 234.01 | 133.26 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: TWINDOW1 N NEA
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 40.95 | 0.00 | 40.95 | 2.75 | 218.55 | 0.00 | 0.00 | 0.00 |
| February | 56.04 | 0.00 | 56.04 | 5.85 | 222.41 | 0.00 | 0.00 | 0.00 |
| March | 77.74 | 0.00 | 77.73 | 30.04 | 140.74 | 0.00 | 0.00 | 0.00 |
| April | 93.40 | 0.31 | 93.09 | 60.57 | 96.77 | 0.00 | 0.00 | 0.00 |
| May | 124.33 | 4.50 | 119.83 | 116.67 | 58.33 | 0.00 | 0.00 | 0.00 |
| June | 131.10 | 6.83 | 124.27 | 157.80 | 30.90 | 0.00 | 0.00 | 0.00 |
| July | 127.21 | 4.82 | 122.38 | 176.30 | 14.69 | 0.00 | 0.00 | 0.00 |
| August | 112.65 | 1.53 | 111.13 | 152.99 | 21.61 | 0.00 | 0.00 | 0.00 |
| September | 84.81 | 0.04 | 84.77 | 88.74 | 48.15 | 0.00 | 0.00 | 0.00 |
| October | 73.35 | 0.00 | 73.35 | 56.14 | 88.35 | 0.00 | 0.00 | 0.00 |
| November | 51.45 | 0.00 | 51.45 | 16.94 | 143.43 | 0.00 | 0.00 | 0.00 |
| December | 35.72 | 0.00 | 35.72 | 1.83 | 197.99 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 84.23 | 1.51 | 82.71 | 72.67 | 106.17 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 35.72 | 0.00 | 35.72 | 1.83 | 14.69 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 131.10 | 6.83 | 124.27 | 176.30 | 222.41 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: TWINDOW1 N N1A
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 40.95 | 0.00 | 40.95 | 2.72 | 222.20 | 0.00 | 0.00 | 0.00 |
| February | 56.04 | 0.00 | 56.04 | 5.89 | 225.72 | 0.00 | 0.00 | 0.00 |
| March | 77.74 | 0.00 | 77.73 | 30.79 | 143.27 | 0.00 | 0.00 | 0.00 |
| April | 93.40 | 0.31 | 93.09 | 62.30 | 99.02 | 0.00 | 0.00 | 0.00 |
| May | 124.33 | 4.50 | 119.83 | 118.32 | 60.52 | 0.00 | 0.00 | 0.00 |
| June | 131.10 | 6.83 | 124.27 | 159.85 | 31.34 | 0.00 | 0.00 | 0.00 |
| July | 127.21 | 4.82 | 122.38 | 178.78 | 14.61 | 0.00 | 0.00 | 0.00 |
| August | 112.65 | 1.53 | 111.13 | 155.82 | 21.67 | 0.00 | 0.00 | 0.00 |
| September | 84.81 | 0.04 | 84.77 | 90.36 | 49.57 | 0.00 | 0.00 | 0.00 |
| October | 73.35 | 0.00 | 73.35 | 57.51 | 91.00 | 0.00 | 0.00 | 0.00 |
| November | 51.45 | 0.00 | 51.45 | 17.19 | 146.14 | 0.00 | 0.00 | 0.00 |
| December | 35.72 | 0.00 | 35.72 | 1.84 | 201.28 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 84.23 | 1.51 | 82.71 | 73.90 | 108.20 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 35.72 | 0.00 | 35.72 | 1.84 | 14.61 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 131.10 | 6.83 | 124.27 | 178.78 | 225.72 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: TWINDOW1 N N2A
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 40.95 | 0.00 | 40.95 | 2.71 | 222.20 | 0.00 | 0.00 | 0.00 |
| February | 56.04 | 0.00 | 56.04 | 5.88 | 225.72 | 0.00 | 0.00 | 0.00 |
| March | 77.74 | 0.00 | 77.73 | 30.73 | 143.19 | 0.00 | 0.00 | 0.00 |
| April | 93.40 | 0.31 | 93.09 | 62.16 | 98.98 | 0.00 | 0.00 | 0.00 |
| May | 124.33 | 4.50 | 119.83 | 118.22 | 60.47 | 0.00 | 0.00 | 0.00 |
| June | 131.10 | 6.83 | 124.27 | 159.83 | 31.31 | 0.00 | 0.00 | 0.00 |
| July | 127.21 | 4.82 | 122.38 | 178.76 | 14.60 | 0.00 | 0.00 | 0.00 |
| August | 112.65 | 1.53 | 111.13 | 155.80 | 21.65 | 0.00 | 0.00 | 0.00 |
| September | 84.81 | 0.04 | 84.77 | 90.29 | 49.55 | 0.00 | 0.00 | 0.00 |
| October | 73.35 | 0.00 | 73.35 | 57.42 | 90.87 | 0.00 | 0.00 | 0.00 |
| November | 51.45 | 0.00 | 51.45 | 17.15 | 146.14 | 0.00 | 0.00 | 0.00 |
| December | 35.72 | 0.00 | 35.72 | 1.83 | 201.28 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 84.23 | 1.51 | 82.71 | 73.86 | 108.17 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 35.72 | 0.00 | 35.72 | 1.83 | 14.60 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 131.10 | 6.83 | 124.27 | 178.76 | 225.72 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: TWINDOW1 S S1A
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 212.64 | 139.47 | 73.18 | 207.24 | 197.41 | 0.00 | 0.00 | 0.00 |
| February | 281.89 | 187.48 | 94.41 | 281.27 | 195.17 | 0.00 | 0.00 | 0.00 |
| March | 246.77 | 134.59 | 112.18 | 259.10 | 139.89 | 0.00 | 0.00 | 0.00 |
| April | 202.81 | 84.53 | 118.28 | 221.91 | 103.00 | 0.00 | 0.00 | 0.00 |
| May | 170.95 | 35.27 | 135.68 | 196.95 | 65.07 | 0.00 | 0.00 | 0.00 |
| June | 161.95 | 25.67 | 136.28 | 213.73 | 33.45 | 0.00 | 0.00 | 0.00 |
| July | 168.92 | 29.58 | 139.34 | 247.78 | 14.81 | 0.00 | 0.00 | 0.00 |
| August | 224.66 | 82.97 | 141.69 | 330.16 | 22.59 | 0.00 | 0.00 | 0.00 |
| September | 238.13 | 120.16 | 117.97 | 311.66 | 50.24 | 0.00 | 0.00 | 0.00 |
| October | 333.15 | 208.32 | 124.83 | 408.00 | 93.00 | 0.00 | 0.00 | 0.00 |
| November | 233.08 | 140.32 | 92.75 | 247.68 | 137.50 | 0.00 | 0.00 | 0.00 |
| December | 229.47 | 162.84 | 66.62 | 233.88 | 176.68 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 225.08 | 112.20 | 112.88 | 263.29 | 101.87 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 161.95 | 25.67 | 66.62 | 196.95 | 14.81 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 333.15 | 208.32 | 141.69 | 408.00 | 197.41 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: TWINDOW1 S S2A
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 212.64 | 139.47 | 73.18 | 207.21 | 197.39 | 0.00 | 0.00 | 0.00 |
| February | 281.89 | 187.48 | 94.41 | 281.21 | 195.14 | 0.00 | 0.00 | 0.00 |
| March | 246.77 | 134.59 | 112.18 | 259.03 | 139.80 | 0.00 | 0.00 | 0.00 |
| April | 202.81 | 84.53 | 118.28 | 221.79 | 102.95 | 0.00 | 0.00 | 0.00 |
| May | 170.95 | 35.27 | 135.68 | 196.86 | 65.01 | 0.00 | 0.00 | 0.00 |
| June | 161.95 | 25.67 | 136.28 | 213.71 | 33.42 | 0.00 | 0.00 | 0.00 |
| July | 168.92 | 29.58 | 139.34 | 247.77 | 14.79 | 0.00 | 0.00 | 0.00 |
| August | 224.66 | 82.97 | 141.69 | 330.14 | 22.56 | 0.00 | 0.00 | 0.00 |
| September | 238.13 | 120.16 | 117.97 | 311.63 | 50.21 | 0.00 | 0.00 | 0.00 |
| October | 333.15 | 208.32 | 124.83 | 407.94 | 92.93 | 0.00 | 0.00 | 0.00 |
| November | 233.08 | 140.32 | 92.75 | 247.61 | 137.51 | 0.00 | 0.00 | 0.00 |
| December | 229.47 | 162.84 | 66.62 | 233.84 | 176.67 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 225.08 | 112.20 | 112.88 | 263.24 | 101.84 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 161.95 | 25.67 | 66.62 | 196.86 | 14.79 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 333.15 | 208.32 | 141.69 | 407.94 | 197.39 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: TWINDOW14
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 13.50 | 5.41 | 8.09 | 8.17 | 33.24 | 7.33 | 0.00 | 0.00 |
| February | 20.81 | 9.65 | 11.17 | 14.49 | 32.73 | 18.00 | 0.00 | 0.00 |
| March | 26.82 | 11.36 | 15.46 | 23.32 | 23.17 | 60.67 | 0.00 | 0.00 |
| April | 32.19 | 14.17 | 18.02 | 32.32 | 16.62 | 139.67 | 0.00 | 0.00 |
| May | 38.84 | 15.49 | 23.35 | 43.63 | 11.11 | 272.67 | 0.00 | 0.00 |
| June | 36.05 | 13.06 | 22.99 | 44.63 | 6.32 | 287.50 | 0.00 | 0.00 |
| July | 36.18 | 13.04 | 23.14 | 48.44 | 3.53 | 312.33 | 0.00 | 0.00 |
| August | 40.73 | 18.35 | 22.38 | 54.36 | 4.68 | 274.67 | 0.00 | 0.00 |
| September | 30.47 | 13.71 | 16.76 | 36.37 | 9.12 | 336.67 | 0.00 | 0.00 |
| October | 27.60 | 12.52 | 15.08 | 30.09 | 15.73 | 232.00 | 0.00 | 0.00 |
| November | 17.08 | 6.57 | 10.51 | 13.77 | 22.89 | 52.50 | 0.00 | 0.00 |
| December | 13.35 | 6.30 | 7.05 | 8.93 | 30.10 | 1.50 | 0.00 | 0.00 |
| Annual Sum or Average | 27.85 | 11.65 | 16.20 | 29.98 | 17.35 | 1995.50 | 0.00 | 0.00 |
| Minimum of Months | 13.35 | 5.41 | 7.05 | 8.17 | 3.53 | 1.50 | 0.00 | 0.00 |
| Maximum of Months | 40.73 | 18.35 | 23.35 | 54.36 | 33.24 | 336.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ENTRANCE DOOR
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 40.22 | 16.12 | 24.10 | 26.82 | 88.17 | 0.00 | 0.00 | 0.00 |
| February | 61.99 | 28.73 | 33.26 | 46.98 | 86.39 | 0.00 | 0.00 | 0.00 |
| March | 79.86 | 33.82 | 46.04 | 74.40 | 60.24 | 0.00 | 0.00 | 0.00 |
| April | 95.86 | 42.19 | 53.67 | 101.51 | 43.59 | 0.00 | 0.00 | 0.00 |
| May | 115.68 | 46.14 | 69.54 | 135.34 | 29.19 | 1.50 | 0.00 | 0.00 |
| June | 107.37 | 38.90 | 68.47 | 134.63 | 18.60 | 22.50 | 0.00 | 0.00 |
| July | 107.75 | 38.84 | 68.91 | 144.50 | 11.17 | 72.00 | 0.00 | 0.00 |
| August | 121.30 | 54.66 | 66.64 | 161.60 | 15.30 | 44.17 | 0.00 | 0.00 |
| September | 90.73 | 40.83 | 49.91 | 108.50 | 28.17 | 19.33 | 0.00 | 0.00 |
| October | 82.20 | 37.29 | 44.91 | 89.20 | 48.85 | 6.17 | 0.00 | 0.00 |
| November | 50.85 | 19.56 | 31.29 | 42.15 | 66.19 | 0.00 | 0.00 | 0.00 |
| December | 39.75 | 18.76 | 20.99 | 28.45 | 82.05 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 82.93 | 34.69 | 48.24 | 91.48 | 47.94 | 165.67 | 0.00 | 0.00 |
| Minimum of Months | 39.75 | 16.12 | 20.99 | 26.82 | 11.17 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 121.30 | 54.66 | 69.54 | 161.60 | 88.17 | 72.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MWINDOW14
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 13.50 | 5.41 | 8.09 | 7.74 | 35.98 | 177.83 | 0.00 | 0.00 |
| February | 20.81 | 9.65 | 11.17 | 13.89 | 35.40 | 146.67 | 0.00 | 0.00 |
| March | 26.82 | 11.36 | 15.46 | 22.80 | 24.99 | 243.00 | 0.00 | 0.00 |
| April | 32.19 | 14.17 | 18.02 | 31.60 | 18.19 | 340.17 | 0.00 | 0.00 |
| May | 38.84 | 15.49 | 23.35 | 42.80 | 12.15 | 396.00 | 0.00 | 0.00 |
| June | 36.05 | 13.06 | 22.99 | 44.81 | 6.49 | 340.00 | 0.00 | 0.00 |
| July | 36.18 | 13.04 | 23.14 | 48.94 | 3.52 | 327.17 | 0.00 | 0.00 |
| August | 40.73 | 18.35 | 22.38 | 54.78 | 4.76 | 306.67 | 0.00 | 0.00 |
| September | 30.47 | 13.71 | 16.76 | 36.14 | 9.69 | 418.50 | 0.00 | 0.00 |
| October | 27.60 | 12.52 | 15.08 | 29.11 | 17.58 | 384.00 | 0.00 | 0.00 |
| November | 17.08 | 6.57 | 10.51 | 12.99 | 25.34 | 239.00 | 0.00 | 0.00 |
| December | 13.35 | 6.30 | 7.05 | 8.53 | 32.78 | 245.33 | 0.00 | 0.00 |
| Annual Sum or Average | 27.85 | 11.65 | 16.20 | 29.62 | 18.81 | 3564.33 | 0.00 | 0.00 |
| Minimum of Months | 13.35 | 5.41 | 7.05 | 7.74 | 3.52 | 146.67 | 0.00 | 0.00 |
| Maximum of Months | 40.73 | 18.35 | 23.35 | 54.78 | 35.98 | 418.50 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: GWINDOW1 S SWA
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.569546E+09 | 0.373547E+09 | 0.195999E+09 | 0.566536E+09 | 0.520844E+09 |
| February | 0.681952E+09 | 0.453545E+09 | 0.228408E+09 | 0.696225E+09 | 0.463315E+09 |
| March | 0.660946E+09 | 0.360494E+09 | 0.300451E+09 | 0.716007E+09 | 0.359229E+09 |
| April | 0.525692E+09 | 0.219107E+09 | 0.306586E+09 | 0.598478E+09 | 0.250174E+09 |
| May | 0.457869E+09 | 94465436.52 | 0.363404E+09 | 0.552811E+09 | 0.158666E+09 |
| June | 0.419772E+09 | 66524244.16 | 0.353248E+09 | 0.565456E+09 | 86092301.00 |
| July | 0.452427E+09 | 79225487.12 | 0.373202E+09 | 0.673665E+09 | 40659442.36 |
| August | 0.601719E+09 | 0.222227E+09 | 0.379492E+09 | 0.892541E+09 | 64689622.96 |
| September | 0.617224E+09 | 0.311444E+09 | 0.305780E+09 | 0.813344E+09 | 0.137554E+09 |
| October | 0.892308E+09 | 0.557954E+09 | 0.334354E+09 | 0.109445E+10 | 0.271390E+09 |
| November | 0.604136E+09 | 0.363715E+09 | 0.240421E+09 | 0.645505E+09 | 0.368280E+09 |
| December | 0.614602E+09 | 0.436160E+09 | 0.178442E+09 | 0.637192E+09 | 0.471487E+09 |
| Annual Sum or Average | 0.709819E+10 | 0.353841E+10 | 0.355979E+10 | 0.845221E+10 | 0.319238E+10 |
| Minimum of Months | 0.419772E+09 | 66524244.16 | 0.178442E+09 | 0.552811E+09 | 40659442.36 |
| Maximum of Months | 0.892308E+09 | 0.557954E+09 | 0.379492E+09 | 0.109445E+10 | 0.520844E+09 |
Report: WindowEnergyReportMonthly
For: GWINDOW1 W SWA
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.149414E+09 | 61382458.61 | 88031726.14 | 93179845.08 | 0.369225E+09 |
| February | 0.197803E+09 | 86777461.17 | 0.111026E+09 | 0.139325E+09 | 0.334728E+09 |
| March | 0.325860E+09 | 0.151069E+09 | 0.174792E+09 | 0.304445E+09 | 0.235102E+09 |
| April | 0.342130E+09 | 0.146061E+09 | 0.196068E+09 | 0.362193E+09 | 0.160630E+09 |
| May | 0.413202E+09 | 0.157000E+09 | 0.256202E+09 | 0.493358E+09 | 0.100882E+09 |
| June | 0.437627E+09 | 0.176908E+09 | 0.260720E+09 | 0.573797E+09 | 54932068.44 |
| July | 0.422991E+09 | 0.159290E+09 | 0.263701E+09 | 0.595095E+09 | 26311506.97 |
| August | 0.467660E+09 | 0.216322E+09 | 0.251338E+09 | 0.651859E+09 | 41880697.67 |
| September | 0.321958E+09 | 0.140660E+09 | 0.181297E+09 | 0.398844E+09 | 90341636.86 |
| October | 0.328634E+09 | 0.159534E+09 | 0.169100E+09 | 0.361243E+09 | 0.183664E+09 |
| November | 0.150005E+09 | 43522471.44 | 0.106483E+09 | 0.100788E+09 | 0.257754E+09 |
| December | 0.137651E+09 | 59633180.38 | 78017486.14 | 87798179.86 | 0.340390E+09 |
| Annual Sum or Average | 0.369494E+10 | 0.155816E+10 | 0.213678E+10 | 0.416192E+10 | 0.219584E+10 |
| Minimum of Months | 0.137651E+09 | 43522471.44 | 78017486.14 | 87798179.86 | 26311506.97 |
| Maximum of Months | 0.467660E+09 | 0.216322E+09 | 0.263701E+09 | 0.651859E+09 | 0.369225E+09 |
Report: WindowEnergyReportMonthly
For: GWINDOW1 W NWA
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.149414E+09 | 61382458.61 | 88031726.14 | 95761650.76 | 0.363557E+09 |
| February | 0.197803E+09 | 86777461.17 | 0.111026E+09 | 0.142980E+09 | 0.327798E+09 |
| March | 0.325860E+09 | 0.151069E+09 | 0.174792E+09 | 0.310203E+09 | 0.229312E+09 |
| April | 0.342130E+09 | 0.146061E+09 | 0.196068E+09 | 0.369242E+09 | 0.154449E+09 |
| May | 0.413202E+09 | 0.157000E+09 | 0.256202E+09 | 0.497974E+09 | 97690312.14 |
| June | 0.437627E+09 | 0.176908E+09 | 0.260720E+09 | 0.574974E+09 | 54523336.75 |
| July | 0.422991E+09 | 0.159290E+09 | 0.263701E+09 | 0.596432E+09 | 25840413.12 |
| August | 0.467660E+09 | 0.216322E+09 | 0.251338E+09 | 0.655124E+09 | 40441714.78 |
| September | 0.321958E+09 | 0.140660E+09 | 0.181297E+09 | 0.402976E+09 | 87430888.52 |
| October | 0.328634E+09 | 0.159534E+09 | 0.169100E+09 | 0.371274E+09 | 0.171177E+09 |
| November | 0.150005E+09 | 43522471.44 | 0.106483E+09 | 0.108632E+09 | 0.243347E+09 |
| December | 0.137651E+09 | 59633180.38 | 78017486.14 | 91186068.68 | 0.332260E+09 |
| Annual Sum or Average | 0.369494E+10 | 0.155816E+10 | 0.213678E+10 | 0.421676E+10 | 0.212783E+10 |
| Minimum of Months | 0.137651E+09 | 43522471.44 | 78017486.14 | 91186068.68 | 25840413.12 |
| Maximum of Months | 0.467660E+09 | 0.216322E+09 | 0.263701E+09 | 0.655124E+09 | 0.363557E+09 |
Report: WindowEnergyReportMonthly
For: GWINDOW1 N NWA
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.109680E+09 | 0.00 | 0.109680E+09 | 8578845.67 | 0.582757E+09 |
| February | 0.135567E+09 | 0.00 | 0.135567E+09 | 16656747.78 | 0.531370E+09 |
| March | 0.208206E+09 | 11905.41 | 0.208194E+09 | 92263397.70 | 0.368442E+09 |
| April | 0.242084E+09 | 795309.56 | 0.241288E+09 | 0.180223E+09 | 0.238016E+09 |
| May | 0.333011E+09 | 12051811.88 | 0.320959E+09 | 0.345245E+09 | 0.144101E+09 |
| June | 0.339808E+09 | 17705128.15 | 0.322103E+09 | 0.424241E+09 | 80185315.69 |
| July | 0.340710E+09 | 12916971.32 | 0.327793E+09 | 0.486800E+09 | 39479900.45 |
| August | 0.301730E+09 | 4093092.86 | 0.297637E+09 | 0.421380E+09 | 61067073.81 |
| September | 0.219832E+09 | 102291.06 | 0.219730E+09 | 0.234394E+09 | 0.135500E+09 |
| October | 0.196470E+09 | 0.00 | 0.196470E+09 | 0.146494E+09 | 0.267240E+09 |
| November | 0.133359E+09 | 0.00 | 0.133359E+09 | 44492781.65 | 0.383407E+09 |
| December | 95669840.31 | 0.00 | 95669840.31 | 5588392.94 | 0.533420E+09 |
| Annual Sum or Average | 0.265613E+10 | 47676510.25 | 0.260845E+10 | 0.240636E+10 | 0.336499E+10 |
| Minimum of Months | 95669840.31 | 0.00 | 95669840.31 | 5588392.94 | 39479900.45 |
| Maximum of Months | 0.340710E+09 | 17705128.15 | 0.327793E+09 | 0.486800E+09 | 0.582757E+09 |
Report: WindowEnergyReportMonthly
For: GWINDOW1 S SEA
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.569546E+09 | 0.373547E+09 | 0.195999E+09 | 0.584605E+09 | 0.448971E+09 |
| February | 0.681952E+09 | 0.453545E+09 | 0.228408E+09 | 0.713404E+09 | 0.406524E+09 |
| March | 0.660946E+09 | 0.360494E+09 | 0.300451E+09 | 0.728678E+09 | 0.327105E+09 |
| April | 0.525692E+09 | 0.219107E+09 | 0.306586E+09 | 0.598049E+09 | 0.248404E+09 |
| May | 0.457869E+09 | 94465436.52 | 0.363404E+09 | 0.537105E+09 | 0.176875E+09 |
| June | 0.419772E+09 | 66524244.16 | 0.353248E+09 | 0.542096E+09 | 0.115726E+09 |
| July | 0.452427E+09 | 79225487.12 | 0.373202E+09 | 0.633035E+09 | 82457180.20 |
| August | 0.601719E+09 | 0.222227E+09 | 0.379492E+09 | 0.857068E+09 | 0.112237E+09 |
| September | 0.617224E+09 | 0.311444E+09 | 0.305780E+09 | 0.791973E+09 | 0.180001E+09 |
| October | 0.892308E+09 | 0.557954E+09 | 0.334354E+09 | 0.108538E+10 | 0.297696E+09 |
| November | 0.604136E+09 | 0.363715E+09 | 0.240421E+09 | 0.648367E+09 | 0.361921E+09 |
| December | 0.614602E+09 | 0.436160E+09 | 0.178442E+09 | 0.648943E+09 | 0.428928E+09 |
| Annual Sum or Average | 0.709819E+10 | 0.353841E+10 | 0.355979E+10 | 0.836871E+10 | 0.318685E+10 |
| Minimum of Months | 0.419772E+09 | 66524244.16 | 0.178442E+09 | 0.537105E+09 | 82457180.20 |
| Maximum of Months | 0.892308E+09 | 0.557954E+09 | 0.379492E+09 | 0.108538E+10 | 0.448971E+09 |
Report: WindowEnergyReportMonthly
For: GWINDOW1 E SEA
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.150731E+09 | 60419999.06 | 90311037.59 | 0.101671E+09 | 0.311447E+09 |
| February | 0.209843E+09 | 97245285.92 | 0.112598E+09 | 0.158479E+09 | 0.281283E+09 |
| March | 0.299320E+09 | 0.126762E+09 | 0.172558E+09 | 0.280235E+09 | 0.216723E+09 |
| April | 0.347682E+09 | 0.153032E+09 | 0.194649E+09 | 0.368076E+09 | 0.156549E+09 |
| May | 0.433554E+09 | 0.172915E+09 | 0.260639E+09 | 0.507064E+09 | 0.110885E+09 |
| June | 0.389429E+09 | 0.141079E+09 | 0.248350E+09 | 0.491846E+09 | 72498054.03 |
| July | 0.403836E+09 | 0.145571E+09 | 0.258265E+09 | 0.542025E+09 | 52563358.59 |
| August | 0.454613E+09 | 0.204842E+09 | 0.249771E+09 | 0.607220E+09 | 70939143.18 |
| September | 0.329093E+09 | 0.148076E+09 | 0.181018E+09 | 0.390850E+09 | 0.115447E+09 |
| October | 0.308065E+09 | 0.139761E+09 | 0.168304E+09 | 0.328809E+09 | 0.198058E+09 |
| November | 0.184450E+09 | 70945468.93 | 0.113504E+09 | 0.149078E+09 | 0.244731E+09 |
| December | 0.148978E+09 | 70298032.80 | 78679568.95 | 0.106097E+09 | 0.300051E+09 |
| Annual Sum or Average | 0.365959E+10 | 0.153095E+10 | 0.212865E+10 | 0.403145E+10 | 0.213117E+10 |
| Minimum of Months | 0.148978E+09 | 60419999.06 | 78679568.95 | 0.101671E+09 | 52563358.59 |
| Maximum of Months | 0.454613E+09 | 0.204842E+09 | 0.260639E+09 | 0.607220E+09 | 0.311447E+09 |
Report: WindowEnergyReportMonthly
For: GWINDOW1 E NEA
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.150731E+09 | 60419999.06 | 90311037.59 | 95242071.11 | 0.356249E+09 |
| February | 0.209843E+09 | 97245285.92 | 0.112598E+09 | 0.152467E+09 | 0.313841E+09 |
| March | 0.299320E+09 | 0.126762E+09 | 0.172558E+09 | 0.276416E+09 | 0.230564E+09 |
| April | 0.347682E+09 | 0.153032E+09 | 0.194649E+09 | 0.373736E+09 | 0.150450E+09 |
| May | 0.433554E+09 | 0.172915E+09 | 0.260639E+09 | 0.521813E+09 | 95563229.08 |
| June | 0.389429E+09 | 0.141079E+09 | 0.248350E+09 | 0.509256E+09 | 53099853.33 |
| July | 0.403836E+09 | 0.145571E+09 | 0.258265E+09 | 0.570929E+09 | 25574315.50 |
| August | 0.454613E+09 | 0.204842E+09 | 0.249771E+09 | 0.635297E+09 | 39105396.25 |
| September | 0.329093E+09 | 0.148076E+09 | 0.181018E+09 | 0.409333E+09 | 85117824.40 |
| October | 0.308065E+09 | 0.139761E+09 | 0.168304E+09 | 0.343224E+09 | 0.166677E+09 |
| November | 0.184450E+09 | 70945468.93 | 0.113504E+09 | 0.154467E+09 | 0.235747E+09 |
| December | 0.148978E+09 | 70298032.80 | 78679568.95 | 0.103478E+09 | 0.322052E+09 |
| Annual Sum or Average | 0.365959E+10 | 0.153095E+10 | 0.212865E+10 | 0.414566E+10 | 0.207404E+10 |
| Minimum of Months | 0.148978E+09 | 60419999.06 | 78679568.95 | 95242071.11 | 25574315.50 |
| Maximum of Months | 0.454613E+09 | 0.204842E+09 | 0.260639E+09 | 0.635297E+09 | 0.356249E+09 |
Report: WindowEnergyReportMonthly
For: GWINDOW1 N NEA
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.109680E+09 | 0.00 | 0.109680E+09 | 8414067.00 | 0.582808E+09 |
| February | 0.135567E+09 | 0.00 | 0.135567E+09 | 16378747.77 | 0.531509E+09 |
| March | 0.208206E+09 | 11905.41 | 0.208194E+09 | 91689588.84 | 0.367093E+09 |
| April | 0.242084E+09 | 795309.56 | 0.241288E+09 | 0.178767E+09 | 0.237167E+09 |
| May | 0.333011E+09 | 12051811.88 | 0.320959E+09 | 0.343556E+09 | 0.142888E+09 |
| June | 0.339808E+09 | 17705128.15 | 0.322103E+09 | 0.424131E+09 | 79238151.91 |
| July | 0.340710E+09 | 12916971.32 | 0.327793E+09 | 0.486414E+09 | 38827606.08 |
| August | 0.301730E+09 | 4093092.86 | 0.297637E+09 | 0.420741E+09 | 60208663.69 |
| September | 0.219832E+09 | 102291.06 | 0.219730E+09 | 0.233466E+09 | 0.134974E+09 |
| October | 0.196470E+09 | 0.00 | 0.196470E+09 | 0.145223E+09 | 0.265473E+09 |
| November | 0.133359E+09 | 0.00 | 0.133359E+09 | 43446965.52 | 0.384487E+09 |
| December | 95669840.31 | 0.00 | 95669840.31 | 5408330.50 | 0.533720E+09 |
| Annual Sum or Average | 0.265613E+10 | 47676510.25 | 0.260845E+10 | 0.239764E+10 | 0.335839E+10 |
| Minimum of Months | 95669840.31 | 0.00 | 95669840.31 | 5408330.50 | 38827606.08 |
| Maximum of Months | 0.340710E+09 | 17705128.15 | 0.327793E+09 | 0.486414E+09 | 0.582808E+09 |
Report: WindowEnergyReportMonthly
For: GWINDOW1 N N1A
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.109680E+09 | 0.00 | 0.109680E+09 | 7992250.69 | 0.592639E+09 |
| February | 0.135567E+09 | 0.00 | 0.135567E+09 | 15890691.06 | 0.540291E+09 |
| March | 0.208206E+09 | 11905.41 | 0.208194E+09 | 90776256.33 | 0.374149E+09 |
| April | 0.242084E+09 | 795309.56 | 0.241288E+09 | 0.178708E+09 | 0.242508E+09 |
| May | 0.333011E+09 | 12051811.88 | 0.320959E+09 | 0.341937E+09 | 0.148448E+09 |
| June | 0.339808E+09 | 17705128.15 | 0.322103E+09 | 0.426154E+09 | 80012413.75 |
| July | 0.340710E+09 | 12916971.32 | 0.327793E+09 | 0.490239E+09 | 38295565.22 |
| August | 0.301730E+09 | 4093092.86 | 0.297637E+09 | 0.425840E+09 | 59187032.51 |
| September | 0.219832E+09 | 102291.06 | 0.219730E+09 | 0.235917E+09 | 0.135496E+09 |
| October | 0.196470E+09 | 0.00 | 0.196470E+09 | 0.145583E+09 | 0.271143E+09 |
| November | 0.133359E+09 | 0.00 | 0.133359E+09 | 42670823.42 | 0.392172E+09 |
| December | 95669840.31 | 0.00 | 95669840.31 | 5218187.48 | 0.542049E+09 |
| Annual Sum or Average | 0.265613E+10 | 47676510.25 | 0.260845E+10 | 0.240693E+10 | 0.341639E+10 |
| Minimum of Months | 95669840.31 | 0.00 | 95669840.31 | 5218187.48 | 38295565.22 |
| Maximum of Months | 0.340710E+09 | 17705128.15 | 0.327793E+09 | 0.490239E+09 | 0.592639E+09 |
Report: WindowEnergyReportMonthly
For: GWINDOW1 N N2A
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.109680E+09 | 0.00 | 0.109680E+09 | 7986893.48 | 0.592647E+09 |
| February | 0.135567E+09 | 0.00 | 0.135567E+09 | 15880404.36 | 0.540299E+09 |
| March | 0.208206E+09 | 11905.41 | 0.208194E+09 | 90763790.98 | 0.374079E+09 |
| April | 0.242084E+09 | 795309.56 | 0.241288E+09 | 0.178607E+09 | 0.242505E+09 |
| May | 0.333011E+09 | 12051811.88 | 0.320959E+09 | 0.341892E+09 | 0.148364E+09 |
| June | 0.339808E+09 | 17705128.15 | 0.322103E+09 | 0.426154E+09 | 79976023.09 |
| July | 0.340710E+09 | 12916971.32 | 0.327793E+09 | 0.490229E+09 | 38272385.79 |
| August | 0.301730E+09 | 4093092.86 | 0.297637E+09 | 0.425820E+09 | 59158758.32 |
| September | 0.219832E+09 | 102291.06 | 0.219730E+09 | 0.235880E+09 | 0.135485E+09 |
| October | 0.196470E+09 | 0.00 | 0.196470E+09 | 0.145548E+09 | 0.271049E+09 |
| November | 0.133359E+09 | 0.00 | 0.133359E+09 | 42587595.55 | 0.392354E+09 |
| December | 95669840.31 | 0.00 | 95669840.31 | 5211291.56 | 0.542070E+09 |
| Annual Sum or Average | 0.265613E+10 | 47676510.25 | 0.260845E+10 | 0.240656E+10 | 0.341626E+10 |
| Minimum of Months | 95669840.31 | 0.00 | 95669840.31 | 5211291.56 | 38272385.79 |
| Maximum of Months | 0.340710E+09 | 17705128.15 | 0.327793E+09 | 0.490229E+09 | 0.592647E+09 |
Report: WindowEnergyReportMonthly
For: GWINDOW1 S S1A
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.569546E+09 | 0.373547E+09 | 0.195999E+09 | 0.563742E+09 | 0.530522E+09 |
| February | 0.681952E+09 | 0.453545E+09 | 0.228408E+09 | 0.692651E+09 | 0.472348E+09 |
| March | 0.660946E+09 | 0.360494E+09 | 0.300451E+09 | 0.713017E+09 | 0.366459E+09 |
| April | 0.525692E+09 | 0.219107E+09 | 0.306586E+09 | 0.594844E+09 | 0.257524E+09 |
| May | 0.457869E+09 | 94465436.52 | 0.363404E+09 | 0.548287E+09 | 0.164967E+09 |
| June | 0.419772E+09 | 66524244.16 | 0.353248E+09 | 0.567232E+09 | 85933878.90 |
| July | 0.452427E+09 | 79225487.12 | 0.373202E+09 | 0.676958E+09 | 39546056.38 |
| August | 0.601719E+09 | 0.222227E+09 | 0.379492E+09 | 0.896548E+09 | 62970020.53 |
| September | 0.617224E+09 | 0.311444E+09 | 0.305780E+09 | 0.814682E+09 | 0.137372E+09 |
| October | 0.892308E+09 | 0.557954E+09 | 0.334354E+09 | 0.109368E+10 | 0.274589E+09 |
| November | 0.604136E+09 | 0.363715E+09 | 0.240421E+09 | 0.640737E+09 | 0.379670E+09 |
| December | 0.614602E+09 | 0.436160E+09 | 0.178442E+09 | 0.634089E+09 | 0.480751E+09 |
| Annual Sum or Average | 0.709819E+10 | 0.353841E+10 | 0.355979E+10 | 0.843646E+10 | 0.325265E+10 |
| Minimum of Months | 0.419772E+09 | 66524244.16 | 0.178442E+09 | 0.548287E+09 | 39546056.38 |
| Maximum of Months | 0.892308E+09 | 0.557954E+09 | 0.379492E+09 | 0.109368E+10 | 0.530522E+09 |
Report: WindowEnergyReportMonthly
For: GWINDOW1 S S2A
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.569546E+09 | 0.373547E+09 | 0.195999E+09 | 0.564744E+09 | 0.527225E+09 |
| February | 0.681952E+09 | 0.453545E+09 | 0.228408E+09 | 0.693685E+09 | 0.469769E+09 |
| March | 0.660946E+09 | 0.360494E+09 | 0.300451E+09 | 0.713829E+09 | 0.364668E+09 |
| April | 0.525692E+09 | 0.219107E+09 | 0.306586E+09 | 0.594617E+09 | 0.257647E+09 |
| May | 0.457869E+09 | 94465436.52 | 0.363404E+09 | 0.546384E+09 | 0.166756E+09 |
| June | 0.419772E+09 | 66524244.16 | 0.353248E+09 | 0.565862E+09 | 87046801.04 |
| July | 0.452427E+09 | 79225487.12 | 0.373202E+09 | 0.674904E+09 | 41025054.73 |
| August | 0.601719E+09 | 0.222227E+09 | 0.379492E+09 | 0.894614E+09 | 64557302.76 |
| September | 0.617224E+09 | 0.311444E+09 | 0.305780E+09 | 0.813483E+09 | 0.138880E+09 |
| October | 0.892308E+09 | 0.557954E+09 | 0.334354E+09 | 0.109298E+10 | 0.275627E+09 |
| November | 0.604136E+09 | 0.363715E+09 | 0.240421E+09 | 0.640612E+09 | 0.379654E+09 |
| December | 0.614602E+09 | 0.436160E+09 | 0.178442E+09 | 0.634810E+09 | 0.478524E+09 |
| Annual Sum or Average | 0.709819E+10 | 0.353841E+10 | 0.355979E+10 | 0.843053E+10 | 0.325138E+10 |
| Minimum of Months | 0.419772E+09 | 66524244.16 | 0.178442E+09 | 0.546384E+09 | 41025054.73 |
| Maximum of Months | 0.892308E+09 | 0.557954E+09 | 0.379492E+09 | 0.109298E+10 | 0.527225E+09 |
Report: WindowEnergyReportMonthly
For: MWINDOW1 S SWA
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.569546E+09 | 0.373547E+09 | 0.195999E+09 | 0.557817E+09 | 0.538932E+09 |
| February | 0.681952E+09 | 0.453545E+09 | 0.228408E+09 | 0.684411E+09 | 0.482075E+09 |
| March | 0.660946E+09 | 0.360494E+09 | 0.300451E+09 | 0.699093E+09 | 0.386246E+09 |
| April | 0.525692E+09 | 0.219107E+09 | 0.306586E+09 | 0.575668E+09 | 0.282361E+09 |
| May | 0.457869E+09 | 94465436.52 | 0.363404E+09 | 0.523748E+09 | 0.189400E+09 |
| June | 0.419772E+09 | 66524244.16 | 0.353248E+09 | 0.557966E+09 | 90471974.96 |
| July | 0.452427E+09 | 79225487.12 | 0.373202E+09 | 0.669417E+09 | 41865496.95 |
| August | 0.601719E+09 | 0.222227E+09 | 0.379492E+09 | 0.890236E+09 | 63955174.77 |
| September | 0.617224E+09 | 0.311444E+09 | 0.305780E+09 | 0.810763E+09 | 0.137194E+09 |
| October | 0.892308E+09 | 0.557954E+09 | 0.334354E+09 | 0.109091E+10 | 0.269769E+09 |
| November | 0.604136E+09 | 0.363715E+09 | 0.240421E+09 | 0.641059E+09 | 0.372431E+09 |
| December | 0.614602E+09 | 0.436160E+09 | 0.178442E+09 | 0.629543E+09 | 0.484122E+09 |
| Annual Sum or Average | 0.709819E+10 | 0.353841E+10 | 0.355979E+10 | 0.833063E+10 | 0.333882E+10 |
| Minimum of Months | 0.419772E+09 | 66524244.16 | 0.178442E+09 | 0.523748E+09 | 41865496.95 |
| Maximum of Months | 0.892308E+09 | 0.557954E+09 | 0.379492E+09 | 0.109091E+10 | 0.538932E+09 |
Report: WindowEnergyReportMonthly
For: MWINDOW1 W SWA
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.149414E+09 | 61382458.61 | 88031726.14 | 89798512.11 | 0.383557E+09 |
| February | 0.197803E+09 | 86777461.17 | 0.111026E+09 | 0.134001E+09 | 0.349867E+09 |
| March | 0.325860E+09 | 0.151069E+09 | 0.174792E+09 | 0.293128E+09 | 0.252484E+09 |
| April | 0.342130E+09 | 0.146061E+09 | 0.196068E+09 | 0.346556E+09 | 0.180912E+09 |
| May | 0.413202E+09 | 0.157000E+09 | 0.256202E+09 | 0.473197E+09 | 0.119945E+09 |
| June | 0.437627E+09 | 0.176908E+09 | 0.260720E+09 | 0.568272E+09 | 57695741.02 |
| July | 0.422991E+09 | 0.159290E+09 | 0.263701E+09 | 0.592013E+09 | 27112941.45 |
| August | 0.467660E+09 | 0.216322E+09 | 0.251338E+09 | 0.650471E+09 | 41442818.39 |
| September | 0.321958E+09 | 0.140660E+09 | 0.181297E+09 | 0.397612E+09 | 90196708.53 |
| October | 0.328634E+09 | 0.159534E+09 | 0.169100E+09 | 0.359640E+09 | 0.182679E+09 |
| November | 0.150005E+09 | 43522471.44 | 0.106483E+09 | 98789926.54 | 0.261416E+09 |
| December | 0.137651E+09 | 59633180.38 | 78017486.14 | 84854205.43 | 0.350904E+09 |
| Annual Sum or Average | 0.369494E+10 | 0.155816E+10 | 0.213678E+10 | 0.408833E+10 | 0.229821E+10 |
| Minimum of Months | 0.137651E+09 | 43522471.44 | 78017486.14 | 84854205.43 | 27112941.45 |
| Maximum of Months | 0.467660E+09 | 0.216322E+09 | 0.263701E+09 | 0.650471E+09 | 0.383557E+09 |
Report: WindowEnergyReportMonthly
For: MWINDOW1 W NWA
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.149414E+09 | 61382458.61 | 88031726.14 | 92959558.28 | 0.377626E+09 |
| February | 0.197803E+09 | 86777461.17 | 0.111026E+09 | 0.138756E+09 | 0.342288E+09 |
| March | 0.325860E+09 | 0.151069E+09 | 0.174792E+09 | 0.301030E+09 | 0.244329E+09 |
| April | 0.342130E+09 | 0.146061E+09 | 0.196068E+09 | 0.353361E+09 | 0.174628E+09 |
| May | 0.413202E+09 | 0.157000E+09 | 0.256202E+09 | 0.475100E+09 | 0.119015E+09 |
| June | 0.437627E+09 | 0.176908E+09 | 0.260720E+09 | 0.569219E+09 | 57504153.68 |
| July | 0.422991E+09 | 0.159290E+09 | 0.263701E+09 | 0.593200E+09 | 26800436.44 |
| August | 0.467660E+09 | 0.216322E+09 | 0.251338E+09 | 0.653398E+09 | 40448012.05 |
| September | 0.321958E+09 | 0.140660E+09 | 0.181297E+09 | 0.401384E+09 | 88163782.82 |
| October | 0.328634E+09 | 0.159534E+09 | 0.169100E+09 | 0.369952E+09 | 0.171351E+09 |
| November | 0.150005E+09 | 43522471.44 | 0.106483E+09 | 0.106643E+09 | 0.248664E+09 |
| December | 0.137651E+09 | 59633180.38 | 78017486.14 | 89002035.16 | 0.342628E+09 |
| Annual Sum or Average | 0.369494E+10 | 0.155816E+10 | 0.213678E+10 | 0.414401E+10 | 0.223345E+10 |
| Minimum of Months | 0.137651E+09 | 43522471.44 | 78017486.14 | 89002035.16 | 26800436.44 |
| Maximum of Months | 0.467660E+09 | 0.216322E+09 | 0.263701E+09 | 0.653398E+09 | 0.377626E+09 |
Report: WindowEnergyReportMonthly
For: MWINDOW1 N NWA
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.109680E+09 | 0.00 | 0.109680E+09 | 7018361.13 | 0.605526E+09 |
| February | 0.135567E+09 | 0.00 | 0.135567E+09 | 14080313.31 | 0.555784E+09 |
| March | 0.208206E+09 | 11905.41 | 0.208194E+09 | 82612634.86 | 0.394046E+09 |
| April | 0.242084E+09 | 795309.56 | 0.241288E+09 | 0.159435E+09 | 0.269964E+09 |
| May | 0.333011E+09 | 12051811.88 | 0.320959E+09 | 0.309876E+09 | 0.175545E+09 |
| June | 0.339808E+09 | 17705128.15 | 0.322103E+09 | 0.416868E+09 | 84376890.64 |
| July | 0.340710E+09 | 12916971.32 | 0.327793E+09 | 0.483162E+09 | 40934332.57 |
| August | 0.301730E+09 | 4093092.86 | 0.297637E+09 | 0.420283E+09 | 61047027.54 |
| September | 0.219832E+09 | 102291.06 | 0.219730E+09 | 0.233145E+09 | 0.136651E+09 |
| October | 0.196470E+09 | 0.00 | 0.196470E+09 | 0.146089E+09 | 0.267273E+09 |
| November | 0.133359E+09 | 0.00 | 0.133359E+09 | 42815005.57 | 0.391604E+09 |
| December | 95669840.31 | 0.00 | 95669840.31 | 4729692.23 | 0.550247E+09 |
| Annual Sum or Average | 0.265613E+10 | 47676510.25 | 0.260845E+10 | 0.232011E+10 | 0.353300E+10 |
| Minimum of Months | 95669840.31 | 0.00 | 95669840.31 | 4729692.23 | 40934332.57 |
| Maximum of Months | 0.340710E+09 | 17705128.15 | 0.327793E+09 | 0.483162E+09 | 0.605526E+09 |
Report: WindowEnergyReportMonthly
For: MWINDOW1 S SEA
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.569546E+09 | 0.373547E+09 | 0.195999E+09 | 0.557222E+09 | 0.538542E+09 |
| February | 0.681952E+09 | 0.453545E+09 | 0.228408E+09 | 0.683326E+09 | 0.481418E+09 |
| March | 0.660946E+09 | 0.360494E+09 | 0.300451E+09 | 0.697743E+09 | 0.383841E+09 |
| April | 0.525692E+09 | 0.219107E+09 | 0.306586E+09 | 0.573281E+09 | 0.281375E+09 |
| May | 0.457869E+09 | 94465436.52 | 0.363404E+09 | 0.522196E+09 | 0.188295E+09 |
| June | 0.419772E+09 | 66524244.16 | 0.353248E+09 | 0.557734E+09 | 89475883.35 |
| July | 0.452427E+09 | 79225487.12 | 0.373202E+09 | 0.668971E+09 | 41164501.16 |
| August | 0.601719E+09 | 0.222227E+09 | 0.379492E+09 | 0.889569E+09 | 63036415.99 |
| September | 0.617224E+09 | 0.311444E+09 | 0.305780E+09 | 0.809994E+09 | 0.136478E+09 |
| October | 0.892308E+09 | 0.557954E+09 | 0.334354E+09 | 0.108981E+10 | 0.268654E+09 |
| November | 0.604136E+09 | 0.363715E+09 | 0.240421E+09 | 0.639246E+09 | 0.373291E+09 |
| December | 0.614602E+09 | 0.436160E+09 | 0.178442E+09 | 0.628542E+09 | 0.483926E+09 |
| Annual Sum or Average | 0.709819E+10 | 0.353841E+10 | 0.355979E+10 | 0.831764E+10 | 0.332950E+10 |
| Minimum of Months | 0.419772E+09 | 66524244.16 | 0.178442E+09 | 0.522196E+09 | 41164501.16 |
| Maximum of Months | 0.892308E+09 | 0.557954E+09 | 0.379492E+09 | 0.108981E+10 | 0.538542E+09 |
Report: WindowEnergyReportMonthly
For: MWINDOW1 E SEA
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.150731E+09 | 60419999.06 | 90311037.59 | 90040502.04 | 0.376222E+09 |
| February | 0.209843E+09 | 97245285.92 | 0.112598E+09 | 0.144485E+09 | 0.335785E+09 |
| March | 0.299320E+09 | 0.126762E+09 | 0.172558E+09 | 0.261127E+09 | 0.255111E+09 |
| April | 0.347682E+09 | 0.153032E+09 | 0.194649E+09 | 0.350949E+09 | 0.176927E+09 |
| May | 0.433554E+09 | 0.172915E+09 | 0.260639E+09 | 0.496061E+09 | 0.117822E+09 |
| June | 0.389429E+09 | 0.141079E+09 | 0.248350E+09 | 0.502986E+09 | 56250739.84 |
| July | 0.403836E+09 | 0.145571E+09 | 0.258265E+09 | 0.566816E+09 | 26876997.63 |
| August | 0.454613E+09 | 0.204842E+09 | 0.249771E+09 | 0.630609E+09 | 40096501.70 |
| September | 0.329093E+09 | 0.148076E+09 | 0.181018E+09 | 0.403930E+09 | 87888353.90 |
| October | 0.308065E+09 | 0.139761E+09 | 0.168304E+09 | 0.332464E+09 | 0.178687E+09 |
| November | 0.184450E+09 | 70945468.93 | 0.113504E+09 | 0.144884E+09 | 0.253394E+09 |
| December | 0.148978E+09 | 70298032.80 | 78679568.95 | 98419464.60 | 0.341143E+09 |
| Annual Sum or Average | 0.365959E+10 | 0.153095E+10 | 0.212865E+10 | 0.402277E+10 | 0.224620E+10 |
| Minimum of Months | 0.148978E+09 | 60419999.06 | 78679568.95 | 90040502.04 | 26876997.63 |
| Maximum of Months | 0.454613E+09 | 0.204842E+09 | 0.260639E+09 | 0.630609E+09 | 0.376222E+09 |
Report: WindowEnergyReportMonthly
For: MWINDOW1 E NEA
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.150731E+09 | 60419999.06 | 90311037.59 | 92347368.54 | 0.369603E+09 |
| February | 0.209843E+09 | 97245285.92 | 0.112598E+09 | 0.148069E+09 | 0.327327E+09 |
| March | 0.299320E+09 | 0.126762E+09 | 0.172558E+09 | 0.267953E+09 | 0.245911E+09 |
| April | 0.347682E+09 | 0.153032E+09 | 0.194649E+09 | 0.357312E+09 | 0.170473E+09 |
| May | 0.433554E+09 | 0.172915E+09 | 0.260639E+09 | 0.497911E+09 | 0.116882E+09 |
| June | 0.389429E+09 | 0.141079E+09 | 0.248350E+09 | 0.503944E+09 | 56056507.88 |
| July | 0.403836E+09 | 0.145571E+09 | 0.258265E+09 | 0.567994E+09 | 26566018.12 |
| August | 0.454613E+09 | 0.204842E+09 | 0.249771E+09 | 0.633583E+09 | 39099910.61 |
| September | 0.329093E+09 | 0.148076E+09 | 0.181018E+09 | 0.407600E+09 | 85827166.60 |
| October | 0.308065E+09 | 0.139761E+09 | 0.168304E+09 | 0.342095E+09 | 0.166725E+09 |
| November | 0.184450E+09 | 70945468.93 | 0.113504E+09 | 0.152375E+09 | 0.240325E+09 |
| December | 0.148978E+09 | 70298032.80 | 78679568.95 | 0.101301E+09 | 0.331710E+09 |
| Annual Sum or Average | 0.365959E+10 | 0.153095E+10 | 0.212865E+10 | 0.407248E+10 | 0.217650E+10 |
| Minimum of Months | 0.148978E+09 | 60419999.06 | 78679568.95 | 92347368.54 | 26566018.12 |
| Maximum of Months | 0.454613E+09 | 0.204842E+09 | 0.260639E+09 | 0.633583E+09 | 0.369603E+09 |
Report: WindowEnergyReportMonthly
For: MWINDOW1 N NEA
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.109680E+09 | 0.00 | 0.109680E+09 | 6818493.61 | 0.605541E+09 |
| February | 0.135567E+09 | 0.00 | 0.135567E+09 | 13754154.63 | 0.555983E+09 |
| March | 0.208206E+09 | 11905.41 | 0.208194E+09 | 81714859.48 | 0.391992E+09 |
| April | 0.242084E+09 | 795309.56 | 0.241288E+09 | 0.156949E+09 | 0.269134E+09 |
| May | 0.333011E+09 | 12051811.88 | 0.320959E+09 | 0.308191E+09 | 0.174588E+09 |
| June | 0.339808E+09 | 17705128.15 | 0.322103E+09 | 0.416666E+09 | 83492429.51 |
| July | 0.340710E+09 | 12916971.32 | 0.327793E+09 | 0.482707E+09 | 40284637.87 |
| August | 0.301730E+09 | 4093092.86 | 0.297637E+09 | 0.419565E+09 | 60152266.06 |
| September | 0.219832E+09 | 102291.06 | 0.219730E+09 | 0.232134E+09 | 0.136032E+09 |
| October | 0.196470E+09 | 0.00 | 0.196470E+09 | 0.144323E+09 | 0.265269E+09 |
| November | 0.133359E+09 | 0.00 | 0.133359E+09 | 41660560.21 | 0.392519E+09 |
| December | 95669840.31 | 0.00 | 95669840.31 | 4529541.20 | 0.550581E+09 |
| Annual Sum or Average | 0.265613E+10 | 47676510.25 | 0.260845E+10 | 0.230901E+10 | 0.352557E+10 |
| Minimum of Months | 95669840.31 | 0.00 | 95669840.31 | 4529541.20 | 40284637.87 |
| Maximum of Months | 0.340710E+09 | 17705128.15 | 0.327793E+09 | 0.482707E+09 | 0.605541E+09 |
Report: WindowEnergyReportMonthly
For: MWINDOW1 N N1A
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.109680E+09 | 0.00 | 0.109680E+09 | 6515477.74 | 0.615070E+09 |
| February | 0.135567E+09 | 0.00 | 0.135567E+09 | 13539975.35 | 0.563510E+09 |
| March | 0.208206E+09 | 11905.41 | 0.208194E+09 | 82053866.97 | 0.397901E+09 |
| April | 0.242084E+09 | 795309.56 | 0.241288E+09 | 0.158710E+09 | 0.274381E+09 |
| May | 0.333011E+09 | 12051811.88 | 0.320959E+09 | 0.310529E+09 | 0.177324E+09 |
| June | 0.339808E+09 | 17705128.15 | 0.322103E+09 | 0.420889E+09 | 82992773.25 |
| July | 0.340710E+09 | 12916971.32 | 0.327793E+09 | 0.487892E+09 | 39181149.12 |
| August | 0.301730E+09 | 4093092.86 | 0.297637E+09 | 0.425404E+09 | 59069309.46 |
| September | 0.219832E+09 | 102291.06 | 0.219730E+09 | 0.234935E+09 | 0.136587E+09 |
| October | 0.196470E+09 | 0.00 | 0.196470E+09 | 0.144425E+09 | 0.273007E+09 |
| November | 0.133359E+09 | 0.00 | 0.133359E+09 | 40610920.93 | 0.402421E+09 |
| December | 95669840.31 | 0.00 | 95669840.31 | 4361614.15 | 0.559798E+09 |
| Annual Sum or Average | 0.265613E+10 | 47676510.25 | 0.260845E+10 | 0.232986E+10 | 0.358124E+10 |
| Minimum of Months | 95669840.31 | 0.00 | 95669840.31 | 4361614.15 | 39181149.12 |
| Maximum of Months | 0.340710E+09 | 17705128.15 | 0.327793E+09 | 0.487892E+09 | 0.615070E+09 |
Report: WindowEnergyReportMonthly
For: MWINDOW1 N N2A
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.109680E+09 | 0.00 | 0.109680E+09 | 6507792.79 | 0.615076E+09 |
| February | 0.135567E+09 | 0.00 | 0.135567E+09 | 13525636.47 | 0.563526E+09 |
| March | 0.208206E+09 | 11905.41 | 0.208194E+09 | 82026711.15 | 0.397774E+09 |
| April | 0.242084E+09 | 795309.56 | 0.241288E+09 | 0.158530E+09 | 0.274418E+09 |
| May | 0.333011E+09 | 12051811.88 | 0.320959E+09 | 0.310455E+09 | 0.177302E+09 |
| June | 0.339808E+09 | 17705128.15 | 0.322103E+09 | 0.420883E+09 | 82959210.17 |
| July | 0.340710E+09 | 12916971.32 | 0.327793E+09 | 0.487876E+09 | 39158302.79 |
| August | 0.301730E+09 | 4093092.86 | 0.297637E+09 | 0.425379E+09 | 59039210.23 |
| September | 0.219832E+09 | 102291.06 | 0.219730E+09 | 0.234896E+09 | 0.136568E+09 |
| October | 0.196470E+09 | 0.00 | 0.196470E+09 | 0.144359E+09 | 0.272916E+09 |
| November | 0.133359E+09 | 0.00 | 0.133359E+09 | 40523689.63 | 0.402593E+09 |
| December | 95669840.31 | 0.00 | 95669840.31 | 4353873.49 | 0.559826E+09 |
| Annual Sum or Average | 0.265613E+10 | 47676510.25 | 0.260845E+10 | 0.232932E+10 | 0.358115E+10 |
| Minimum of Months | 95669840.31 | 0.00 | 95669840.31 | 4353873.49 | 39158302.79 |
| Maximum of Months | 0.340710E+09 | 17705128.15 | 0.327793E+09 | 0.487876E+09 | 0.615076E+09 |
Report: WindowEnergyReportMonthly
For: MWINDOW1 S S1A
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.569546E+09 | 0.373547E+09 | 0.195999E+09 | 0.554742E+09 | 0.548833E+09 |
| February | 0.681952E+09 | 0.453545E+09 | 0.228408E+09 | 0.681111E+09 | 0.490372E+09 |
| March | 0.660946E+09 | 0.360494E+09 | 0.300451E+09 | 0.696080E+09 | 0.395163E+09 |
| April | 0.525692E+09 | 0.219107E+09 | 0.306586E+09 | 0.573311E+09 | 0.289529E+09 |
| May | 0.457869E+09 | 94465436.52 | 0.363404E+09 | 0.524394E+09 | 0.190999E+09 |
| June | 0.419772E+09 | 66524244.16 | 0.353248E+09 | 0.561788E+09 | 88904022.00 |
| July | 0.452427E+09 | 79225487.12 | 0.373202E+09 | 0.674093E+09 | 40058469.10 |
| August | 0.601719E+09 | 0.222227E+09 | 0.379492E+09 | 0.895001E+09 | 62024411.97 |
| September | 0.617224E+09 | 0.311444E+09 | 0.305780E+09 | 0.812458E+09 | 0.136918E+09 |
| October | 0.892308E+09 | 0.557954E+09 | 0.334354E+09 | 0.108980E+10 | 0.274162E+09 |
| November | 0.604136E+09 | 0.363715E+09 | 0.240421E+09 | 0.635661E+09 | 0.385467E+09 |
| December | 0.614602E+09 | 0.436160E+09 | 0.178442E+09 | 0.625605E+09 | 0.495559E+09 |
| Annual Sum or Average | 0.709819E+10 | 0.353841E+10 | 0.355979E+10 | 0.832404E+10 | 0.339799E+10 |
| Minimum of Months | 0.419772E+09 | 66524244.16 | 0.178442E+09 | 0.524394E+09 | 40058469.10 |
| Maximum of Months | 0.892308E+09 | 0.557954E+09 | 0.379492E+09 | 0.108980E+10 | 0.548833E+09 |
Report: WindowEnergyReportMonthly
For: MWINDOW1 S S2A
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.569546E+09 | 0.373547E+09 | 0.195999E+09 | 0.554707E+09 | 0.548819E+09 |
| February | 0.681952E+09 | 0.453545E+09 | 0.228408E+09 | 0.681050E+09 | 0.490352E+09 |
| March | 0.660946E+09 | 0.360494E+09 | 0.300451E+09 | 0.696037E+09 | 0.394997E+09 |
| April | 0.525692E+09 | 0.219107E+09 | 0.306586E+09 | 0.573181E+09 | 0.289522E+09 |
| May | 0.457869E+09 | 94465436.52 | 0.363404E+09 | 0.524338E+09 | 0.190959E+09 |
| June | 0.419772E+09 | 66524244.16 | 0.353248E+09 | 0.561780E+09 | 88867116.16 |
| July | 0.452427E+09 | 79225487.12 | 0.373202E+09 | 0.674078E+09 | 40034656.95 |
| August | 0.601719E+09 | 0.222227E+09 | 0.379492E+09 | 0.894978E+09 | 61993568.35 |
| September | 0.617224E+09 | 0.311444E+09 | 0.305780E+09 | 0.812434E+09 | 0.136896E+09 |
| October | 0.892308E+09 | 0.557954E+09 | 0.334354E+09 | 0.108977E+10 | 0.274122E+09 |
| November | 0.604136E+09 | 0.363715E+09 | 0.240421E+09 | 0.635551E+09 | 0.385611E+09 |
| December | 0.614602E+09 | 0.436160E+09 | 0.178442E+09 | 0.625543E+09 | 0.495584E+09 |
| Annual Sum or Average | 0.709819E+10 | 0.353841E+10 | 0.355979E+10 | 0.832344E+10 | 0.339776E+10 |
| Minimum of Months | 0.419772E+09 | 66524244.16 | 0.178442E+09 | 0.524338E+09 | 40034656.95 |
| Maximum of Months | 0.892308E+09 | 0.557954E+09 | 0.379492E+09 | 0.108977E+10 | 0.548819E+09 |
Report: WindowEnergyReportMonthly
For: TWINDOW1 S SWA
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.569546E+09 | 0.373547E+09 | 0.195999E+09 | 0.557848E+09 | 0.519352E+09 |
| February | 0.681952E+09 | 0.453545E+09 | 0.228408E+09 | 0.683531E+09 | 0.464185E+09 |
| March | 0.660946E+09 | 0.360494E+09 | 0.300451E+09 | 0.695487E+09 | 0.368731E+09 |
| April | 0.525692E+09 | 0.219107E+09 | 0.306586E+09 | 0.576137E+09 | 0.261731E+09 |
| May | 0.457869E+09 | 94465436.52 | 0.363404E+09 | 0.527359E+09 | 0.170167E+09 |
| June | 0.419772E+09 | 66524244.16 | 0.353248E+09 | 0.549581E+09 | 86962918.45 |
| July | 0.452427E+09 | 79225487.12 | 0.373202E+09 | 0.657803E+09 | 40863800.58 |
| August | 0.601719E+09 | 0.222227E+09 | 0.379492E+09 | 0.878330E+09 | 61711205.41 |
| September | 0.617224E+09 | 0.311444E+09 | 0.305780E+09 | 0.806522E+09 | 0.127920E+09 |
| October | 0.892308E+09 | 0.557954E+09 | 0.334354E+09 | 0.109432E+10 | 0.242349E+09 |
| November | 0.604136E+09 | 0.363715E+09 | 0.240421E+09 | 0.645608E+09 | 0.347513E+09 |
| December | 0.614602E+09 | 0.436160E+09 | 0.178442E+09 | 0.629851E+09 | 0.463879E+09 |
| Annual Sum or Average | 0.709819E+10 | 0.353841E+10 | 0.355979E+10 | 0.830238E+10 | 0.315536E+10 |
| Minimum of Months | 0.419772E+09 | 66524244.16 | 0.178442E+09 | 0.527359E+09 | 40863800.58 |
| Maximum of Months | 0.892308E+09 | 0.557954E+09 | 0.379492E+09 | 0.109432E+10 | 0.519352E+09 |
Report: WindowEnergyReportMonthly
For: TWINDOW1 W SWA
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.149414E+09 | 61382458.61 | 88031726.14 | 88898988.62 | 0.369494E+09 |
| February | 0.197803E+09 | 86777461.17 | 0.111026E+09 | 0.132075E+09 | 0.336757E+09 |
| March | 0.325860E+09 | 0.151069E+09 | 0.174792E+09 | 0.290063E+09 | 0.239889E+09 |
| April | 0.342130E+09 | 0.146061E+09 | 0.196068E+09 | 0.346304E+09 | 0.166430E+09 |
| May | 0.413202E+09 | 0.157000E+09 | 0.256202E+09 | 0.475627E+09 | 0.107045E+09 |
| June | 0.437627E+09 | 0.176908E+09 | 0.260720E+09 | 0.562397E+09 | 55077779.49 |
| July | 0.422991E+09 | 0.159290E+09 | 0.263701E+09 | 0.584159E+09 | 26300199.09 |
| August | 0.467660E+09 | 0.216322E+09 | 0.251338E+09 | 0.642636E+09 | 39775255.70 |
| September | 0.321958E+09 | 0.140660E+09 | 0.181297E+09 | 0.394518E+09 | 83444850.52 |
| October | 0.328634E+09 | 0.159534E+09 | 0.169100E+09 | 0.360695E+09 | 0.162796E+09 |
| November | 0.150005E+09 | 43522471.44 | 0.106483E+09 | 0.100122E+09 | 0.242917E+09 |
| December | 0.137651E+09 | 59633180.38 | 78017486.14 | 83912431.71 | 0.336226E+09 |
| Annual Sum or Average | 0.369494E+10 | 0.155816E+10 | 0.213678E+10 | 0.406141E+10 | 0.216615E+10 |
| Minimum of Months | 0.137651E+09 | 43522471.44 | 78017486.14 | 83912431.71 | 26300199.09 |
| Maximum of Months | 0.467660E+09 | 0.216322E+09 | 0.263701E+09 | 0.642636E+09 | 0.369494E+09 |
Report: WindowEnergyReportMonthly
For: TWINDOW1 W NWA
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.149414E+09 | 61382458.61 | 88031726.14 | 93625497.99 | 0.364468E+09 |
| February | 0.197803E+09 | 86777461.17 | 0.111026E+09 | 0.139140E+09 | 0.330538E+09 |
| March | 0.325860E+09 | 0.151069E+09 | 0.174792E+09 | 0.300199E+09 | 0.234603E+09 |
| April | 0.342130E+09 | 0.146061E+09 | 0.196068E+09 | 0.353603E+09 | 0.163125E+09 |
| May | 0.413202E+09 | 0.157000E+09 | 0.256202E+09 | 0.478100E+09 | 0.106520E+09 |
| June | 0.437627E+09 | 0.176908E+09 | 0.260720E+09 | 0.563573E+09 | 55087002.05 |
| July | 0.422991E+09 | 0.159290E+09 | 0.263701E+09 | 0.585720E+09 | 26174577.65 |
| August | 0.467660E+09 | 0.216322E+09 | 0.251338E+09 | 0.646665E+09 | 39043712.69 |
| September | 0.321958E+09 | 0.140660E+09 | 0.181297E+09 | 0.400564E+09 | 81056696.47 |
| October | 0.328634E+09 | 0.159534E+09 | 0.169100E+09 | 0.374804E+09 | 0.153698E+09 |
| November | 0.150005E+09 | 43522471.44 | 0.106483E+09 | 0.108515E+09 | 0.235823E+09 |
| December | 0.137651E+09 | 59633180.38 | 78017486.14 | 89695918.73 | 0.329550E+09 |
| Annual Sum or Average | 0.369494E+10 | 0.155816E+10 | 0.213678E+10 | 0.413421E+10 | 0.211969E+10 |
| Minimum of Months | 0.137651E+09 | 43522471.44 | 78017486.14 | 89695918.73 | 26174577.65 |
| Maximum of Months | 0.467660E+09 | 0.216322E+09 | 0.263701E+09 | 0.646665E+09 | 0.364468E+09 |
Report: WindowEnergyReportMonthly
For: TWINDOW1 N NWA
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.109680E+09 | 0.00 | 0.109680E+09 | 7723032.83 | 0.585511E+09 |
| February | 0.135567E+09 | 0.00 | 0.135567E+09 | 14714431.05 | 0.538086E+09 |
| March | 0.208206E+09 | 11905.41 | 0.208194E+09 | 82370602.15 | 0.380128E+09 |
| April | 0.242084E+09 | 795309.56 | 0.241288E+09 | 0.160984E+09 | 0.253244E+09 |
| May | 0.333011E+09 | 12051811.88 | 0.320959E+09 | 0.316458E+09 | 0.158292E+09 |
| June | 0.339808E+09 | 17705128.15 | 0.322103E+09 | 0.409815E+09 | 81381466.32 |
| July | 0.340710E+09 | 12916971.32 | 0.327793E+09 | 0.472937E+09 | 40239757.48 |
| August | 0.301730E+09 | 4093092.86 | 0.297637E+09 | 0.411001E+09 | 59267167.39 |
| September | 0.219832E+09 | 102291.06 | 0.219730E+09 | 0.232551E+09 | 0.126080E+09 |
| October | 0.196470E+09 | 0.00 | 0.196470E+09 | 0.153725E+09 | 0.240656E+09 |
| November | 0.133359E+09 | 0.00 | 0.133359E+09 | 45348777.27 | 0.371872E+09 |
| December | 95669840.31 | 0.00 | 95669840.31 | 5265266.62 | 0.530090E+09 |
| Annual Sum or Average | 0.265613E+10 | 47676510.25 | 0.260845E+10 | 0.231289E+10 | 0.336485E+10 |
| Minimum of Months | 95669840.31 | 0.00 | 95669840.31 | 5265266.62 | 40239757.48 |
| Maximum of Months | 0.340710E+09 | 17705128.15 | 0.327793E+09 | 0.472937E+09 | 0.585511E+09 |
Report: WindowEnergyReportMonthly
For: TWINDOW1 S SEA
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.569546E+09 | 0.373547E+09 | 0.195999E+09 | 0.556913E+09 | 0.518628E+09 |
| February | 0.681952E+09 | 0.453545E+09 | 0.228408E+09 | 0.681836E+09 | 0.462963E+09 |
| March | 0.660946E+09 | 0.360494E+09 | 0.300451E+09 | 0.693012E+09 | 0.365546E+09 |
| April | 0.525692E+09 | 0.219107E+09 | 0.306586E+09 | 0.572215E+09 | 0.259459E+09 |
| May | 0.457869E+09 | 94465436.52 | 0.363404E+09 | 0.523495E+09 | 0.167780E+09 |
| June | 0.419772E+09 | 66524244.16 | 0.353248E+09 | 0.548678E+09 | 85469854.49 |
| July | 0.452427E+09 | 79225487.12 | 0.373202E+09 | 0.657047E+09 | 39854998.51 |
| August | 0.601719E+09 | 0.222227E+09 | 0.379492E+09 | 0.877200E+09 | 60282384.49 |
| September | 0.617224E+09 | 0.311444E+09 | 0.305780E+09 | 0.804678E+09 | 0.126568E+09 |
| October | 0.892308E+09 | 0.557954E+09 | 0.334354E+09 | 0.109137E+10 | 0.239965E+09 |
| November | 0.604136E+09 | 0.363715E+09 | 0.240421E+09 | 0.643112E+09 | 0.347462E+09 |
| December | 0.614602E+09 | 0.436160E+09 | 0.178442E+09 | 0.628381E+09 | 0.463260E+09 |
| Annual Sum or Average | 0.709819E+10 | 0.353841E+10 | 0.355979E+10 | 0.827794E+10 | 0.313724E+10 |
| Minimum of Months | 0.419772E+09 | 66524244.16 | 0.178442E+09 | 0.523495E+09 | 39854998.51 |
| Maximum of Months | 0.892308E+09 | 0.557954E+09 | 0.379492E+09 | 0.109137E+10 | 0.518628E+09 |
Report: WindowEnergyReportMonthly
For: TWINDOW1 E SEA
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.150731E+09 | 60419999.06 | 90311037.59 | 90788293.18 | 0.363390E+09 |
| February | 0.209843E+09 | 97245285.92 | 0.112598E+09 | 0.145090E+09 | 0.324572E+09 |
| March | 0.299320E+09 | 0.126762E+09 | 0.172558E+09 | 0.259140E+09 | 0.243722E+09 |
| April | 0.347682E+09 | 0.153032E+09 | 0.194649E+09 | 0.351731E+09 | 0.163483E+09 |
| May | 0.433554E+09 | 0.172915E+09 | 0.260639E+09 | 0.498687E+09 | 0.105911E+09 |
| June | 0.389429E+09 | 0.141079E+09 | 0.248350E+09 | 0.497612E+09 | 53952259.18 |
| July | 0.403836E+09 | 0.145571E+09 | 0.258265E+09 | 0.559315E+09 | 26094620.01 |
| August | 0.454613E+09 | 0.204842E+09 | 0.249771E+09 | 0.622712E+09 | 38475959.81 |
| September | 0.329093E+09 | 0.148076E+09 | 0.181018E+09 | 0.401170E+09 | 81853545.43 |
| October | 0.308065E+09 | 0.139761E+09 | 0.168304E+09 | 0.334761E+09 | 0.160406E+09 |
| November | 0.184450E+09 | 70945468.93 | 0.113504E+09 | 0.147769E+09 | 0.236116E+09 |
| December | 0.148978E+09 | 70298032.80 | 78679568.95 | 99327422.31 | 0.327921E+09 |
| Annual Sum or Average | 0.365959E+10 | 0.153095E+10 | 0.212865E+10 | 0.400810E+10 | 0.212590E+10 |
| Minimum of Months | 0.148978E+09 | 60419999.06 | 78679568.95 | 90788293.18 | 26094620.01 |
| Maximum of Months | 0.454613E+09 | 0.204842E+09 | 0.260639E+09 | 0.622712E+09 | 0.363390E+09 |
Report: WindowEnergyReportMonthly
For: TWINDOW1 E NEA
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.150731E+09 | 60419999.06 | 90311037.59 | 93804417.33 | 0.356916E+09 |
| February | 0.209843E+09 | 97245285.92 | 0.112598E+09 | 0.149677E+09 | 0.316269E+09 |
| March | 0.299320E+09 | 0.126762E+09 | 0.172558E+09 | 0.267806E+09 | 0.236664E+09 |
| April | 0.347682E+09 | 0.153032E+09 | 0.194649E+09 | 0.358277E+09 | 0.159433E+09 |
| May | 0.433554E+09 | 0.172915E+09 | 0.260639E+09 | 0.500994E+09 | 0.105327E+09 |
| June | 0.389429E+09 | 0.141079E+09 | 0.248350E+09 | 0.498842E+09 | 53958902.15 |
| July | 0.403836E+09 | 0.145571E+09 | 0.258265E+09 | 0.560866E+09 | 25972005.26 |
| August | 0.454613E+09 | 0.204842E+09 | 0.249771E+09 | 0.626775E+09 | 37711537.62 |
| September | 0.329093E+09 | 0.148076E+09 | 0.181018E+09 | 0.406850E+09 | 79334601.17 |
| October | 0.308065E+09 | 0.139761E+09 | 0.168304E+09 | 0.347539E+09 | 0.149366E+09 |
| November | 0.184450E+09 | 70945468.93 | 0.113504E+09 | 0.155193E+09 | 0.227744E+09 |
| December | 0.148978E+09 | 70298032.80 | 78679568.95 | 0.102804E+09 | 0.319124E+09 |
| Annual Sum or Average | 0.365959E+10 | 0.153095E+10 | 0.212865E+10 | 0.406943E+10 | 0.206782E+10 |
| Minimum of Months | 0.148978E+09 | 60419999.06 | 78679568.95 | 93804417.33 | 25972005.26 |
| Maximum of Months | 0.454613E+09 | 0.204842E+09 | 0.260639E+09 | 0.626775E+09 | 0.356916E+09 |
Report: WindowEnergyReportMonthly
For: TWINDOW1 N NEA
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.109680E+09 | 0.00 | 0.109680E+09 | 7370849.35 | 0.585369E+09 |
| February | 0.135567E+09 | 0.00 | 0.135567E+09 | 14153013.10 | 0.538064E+09 |
| March | 0.208206E+09 | 11905.41 | 0.208194E+09 | 80451989.77 | 0.376956E+09 |
| April | 0.242084E+09 | 795309.56 | 0.241288E+09 | 0.156998E+09 | 0.250826E+09 |
| May | 0.333011E+09 | 12051811.88 | 0.320959E+09 | 0.312476E+09 | 0.156219E+09 |
| June | 0.339808E+09 | 17705128.15 | 0.322103E+09 | 0.409024E+09 | 80088939.66 |
| July | 0.340710E+09 | 12916971.32 | 0.327793E+09 | 0.472192E+09 | 39334605.21 |
| August | 0.301730E+09 | 4093092.86 | 0.297637E+09 | 0.409774E+09 | 57885606.55 |
| September | 0.219832E+09 | 102291.06 | 0.219730E+09 | 0.230007E+09 | 0.124811E+09 |
| October | 0.196470E+09 | 0.00 | 0.196470E+09 | 0.150374E+09 | 0.236626E+09 |
| November | 0.133359E+09 | 0.00 | 0.133359E+09 | 43917950.97 | 0.371782E+09 |
| December | 95669840.31 | 0.00 | 95669840.31 | 4907004.75 | 0.530288E+09 |
| Annual Sum or Average | 0.265613E+10 | 47676510.25 | 0.260845E+10 | 0.229164E+10 | 0.334825E+10 |
| Minimum of Months | 95669840.31 | 0.00 | 95669840.31 | 4907004.75 | 39334605.21 |
| Maximum of Months | 0.340710E+09 | 17705128.15 | 0.327793E+09 | 0.472192E+09 | 0.585369E+09 |
Report: WindowEnergyReportMonthly
For: TWINDOW1 N N1A
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.109680E+09 | 0.00 | 0.109680E+09 | 7276292.19 | 0.595140E+09 |
| February | 0.135567E+09 | 0.00 | 0.135567E+09 | 14251566.82 | 0.546060E+09 |
| March | 0.208206E+09 | 11905.41 | 0.208194E+09 | 82458792.92 | 0.383747E+09 |
| April | 0.242084E+09 | 795309.56 | 0.241288E+09 | 0.161471E+09 | 0.256668E+09 |
| May | 0.333011E+09 | 12051811.88 | 0.320959E+09 | 0.316917E+09 | 0.162110E+09 |
| June | 0.339808E+09 | 17705128.15 | 0.322103E+09 | 0.414343E+09 | 81240452.95 |
| July | 0.340710E+09 | 12916971.32 | 0.327793E+09 | 0.478832E+09 | 39144098.64 |
| August | 0.301730E+09 | 4093092.86 | 0.297637E+09 | 0.417346E+09 | 58053422.91 |
| September | 0.219832E+09 | 102291.06 | 0.219730E+09 | 0.234221E+09 | 0.128483E+09 |
| October | 0.196470E+09 | 0.00 | 0.196470E+09 | 0.154043E+09 | 0.243747E+09 |
| November | 0.133359E+09 | 0.00 | 0.133359E+09 | 44558450.46 | 0.378802E+09 |
| December | 95669840.31 | 0.00 | 95669840.31 | 4928559.29 | 0.539100E+09 |
| Annual Sum or Average | 0.265613E+10 | 47676510.25 | 0.260845E+10 | 0.233065E+10 | 0.341230E+10 |
| Minimum of Months | 95669840.31 | 0.00 | 95669840.31 | 4928559.29 | 39144098.64 |
| Maximum of Months | 0.340710E+09 | 17705128.15 | 0.327793E+09 | 0.478832E+09 | 0.595140E+09 |
Report: WindowEnergyReportMonthly
For: TWINDOW1 N N2A
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.109680E+09 | 0.00 | 0.109680E+09 | 7256893.91 | 0.595132E+09 |
| February | 0.135567E+09 | 0.00 | 0.135567E+09 | 14217057.86 | 0.546050E+09 |
| March | 0.208206E+09 | 11905.41 | 0.208194E+09 | 82309951.16 | 0.383521E+09 |
| April | 0.242084E+09 | 795309.56 | 0.241288E+09 | 0.161112E+09 | 0.256544E+09 |
| May | 0.333011E+09 | 12051811.88 | 0.320959E+09 | 0.316635E+09 | 0.161957E+09 |
| June | 0.339808E+09 | 17705128.15 | 0.322103E+09 | 0.414290E+09 | 81162723.52 |
| July | 0.340710E+09 | 12916971.32 | 0.327793E+09 | 0.478792E+09 | 39092754.74 |
| August | 0.301730E+09 | 4093092.86 | 0.297637E+09 | 0.417281E+09 | 57974319.24 |
| September | 0.219832E+09 | 102291.06 | 0.219730E+09 | 0.234044E+09 | 0.128430E+09 |
| October | 0.196470E+09 | 0.00 | 0.196470E+09 | 0.153806E+09 | 0.243398E+09 |
| November | 0.133359E+09 | 0.00 | 0.133359E+09 | 44459699.10 | 0.378802E+09 |
| December | 95669840.31 | 0.00 | 95669840.31 | 4908359.67 | 0.539110E+09 |
| Annual Sum or Average | 0.265613E+10 | 47676510.25 | 0.260845E+10 | 0.232911E+10 | 0.341117E+10 |
| Minimum of Months | 95669840.31 | 0.00 | 95669840.31 | 4908359.67 | 39092754.74 |
| Maximum of Months | 0.340710E+09 | 17705128.15 | 0.327793E+09 | 0.478792E+09 | 0.595132E+09 |
Report: WindowEnergyReportMonthly
For: TWINDOW1 S S1A
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.569546E+09 | 0.373547E+09 | 0.195999E+09 | 0.555075E+09 | 0.528731E+09 |
| February | 0.681952E+09 | 0.453545E+09 | 0.228408E+09 | 0.680442E+09 | 0.472161E+09 |
| March | 0.660946E+09 | 0.360494E+09 | 0.300451E+09 | 0.693986E+09 | 0.374688E+09 |
| April | 0.525692E+09 | 0.219107E+09 | 0.306586E+09 | 0.575180E+09 | 0.266979E+09 |
| May | 0.457869E+09 | 94465436.52 | 0.363404E+09 | 0.527503E+09 | 0.174292E+09 |
| June | 0.419772E+09 | 66524244.16 | 0.353248E+09 | 0.554000E+09 | 86714903.70 |
| July | 0.452427E+09 | 79225487.12 | 0.373202E+09 | 0.663666E+09 | 39676463.63 |
| August | 0.601719E+09 | 0.222227E+09 | 0.379492E+09 | 0.884309E+09 | 60495772.10 |
| September | 0.617224E+09 | 0.311444E+09 | 0.305780E+09 | 0.807829E+09 | 0.130225E+09 |
| October | 0.892308E+09 | 0.557954E+09 | 0.334354E+09 | 0.109278E+10 | 0.249085E+09 |
| November | 0.604136E+09 | 0.363715E+09 | 0.240421E+09 | 0.641984E+09 | 0.356387E+09 |
| December | 0.614602E+09 | 0.436160E+09 | 0.178442E+09 | 0.626433E+09 | 0.473232E+09 |
| Annual Sum or Average | 0.709819E+10 | 0.353841E+10 | 0.355979E+10 | 0.830319E+10 | 0.321267E+10 |
| Minimum of Months | 0.419772E+09 | 66524244.16 | 0.178442E+09 | 0.527503E+09 | 39676463.63 |
| Maximum of Months | 0.892308E+09 | 0.557954E+09 | 0.379492E+09 | 0.109278E+10 | 0.528731E+09 |
Report: WindowEnergyReportMonthly
For: TWINDOW1 S S2A
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.569546E+09 | 0.373547E+09 | 0.195999E+09 | 0.554995E+09 | 0.528684E+09 |
| February | 0.681952E+09 | 0.453545E+09 | 0.228408E+09 | 0.680306E+09 | 0.472073E+09 |
| March | 0.660946E+09 | 0.360494E+09 | 0.300451E+09 | 0.693786E+09 | 0.374439E+09 |
| April | 0.525692E+09 | 0.219107E+09 | 0.306586E+09 | 0.574890E+09 | 0.266837E+09 |
| May | 0.457869E+09 | 94465436.52 | 0.363404E+09 | 0.527260E+09 | 0.174111E+09 |
| June | 0.419772E+09 | 66524244.16 | 0.353248E+09 | 0.553934E+09 | 86624580.86 |
| July | 0.452427E+09 | 79225487.12 | 0.373202E+09 | 0.663626E+09 | 39620571.60 |
| August | 0.601719E+09 | 0.222227E+09 | 0.379492E+09 | 0.884250E+09 | 60415735.21 |
| September | 0.617224E+09 | 0.311444E+09 | 0.305780E+09 | 0.807734E+09 | 0.130149E+09 |
| October | 0.892308E+09 | 0.557954E+09 | 0.334354E+09 | 0.109262E+10 | 0.248909E+09 |
| November | 0.604136E+09 | 0.363715E+09 | 0.240421E+09 | 0.641803E+09 | 0.356438E+09 |
| December | 0.614602E+09 | 0.436160E+09 | 0.178442E+09 | 0.626313E+09 | 0.473197E+09 |
| Annual Sum or Average | 0.709819E+10 | 0.353841E+10 | 0.355979E+10 | 0.830152E+10 | 0.321150E+10 |
| Minimum of Months | 0.419772E+09 | 66524244.16 | 0.178442E+09 | 0.527260E+09 | 39620571.60 |
| Maximum of Months | 0.892308E+09 | 0.557954E+09 | 0.379492E+09 | 0.109262E+10 | 0.528684E+09 |
Report: WindowEnergyReportMonthly
For: TWINDOW14
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 36168525.78 | 14498024.71 | 21670501.07 | 21870021.65 | 89026571.97 |
| February | 50352801.23 | 23334402.18 | 27018399.04 | 35051485.27 | 79187944.47 |
| March | 71822997.42 | 30417010.95 | 41405986.47 | 62471360.44 | 62060440.78 |
| April | 83427601.15 | 36720707.64 | 46706893.51 | 83781880.72 | 43078370.74 |
| May | 0.104033E+09 | 41491661.29 | 62541299.09 | 0.116863E+09 | 29757110.56 |
| June | 93445170.34 | 33852460.79 | 59592709.55 | 0.115678E+09 | 16379849.40 |
| July | 96902034.38 | 34930391.32 | 61971643.06 | 0.129734E+09 | 9461240.98 |
| August | 0.109086E+09 | 49152640.32 | 59933675.28 | 0.145602E+09 | 12525549.14 |
| September | 78967322.58 | 35531336.66 | 43435985.91 | 94272385.06 | 23644186.92 |
| October | 73921532.48 | 33536184.50 | 40385347.98 | 80594290.60 | 42142619.64 |
| November | 44259412.10 | 17023654.05 | 27235758.06 | 35680992.43 | 59343614.09 |
| December | 35747781.94 | 16868299.11 | 18879482.83 | 23931126.60 | 80616171.33 |
| Annual Sum or Average | 0.878134E+09 | 0.367357E+09 | 0.510778E+09 | 0.945531E+09 | 0.547224E+09 |
| Minimum of Months | 35747781.94 | 14498024.71 | 18879482.83 | 21870021.65 | 9461240.98 |
| Maximum of Months | 0.109086E+09 | 49152640.32 | 62541299.09 | 0.145602E+09 | 89026571.97 |
Report: WindowEnergyReportMonthly
For: ENTRANCE DOOR
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.107719E+09 | 43178725.60 | 64540145.18 | 71840992.62 | 0.236145E+09 |
| February | 0.149963E+09 | 69495656.78 | 80467516.24 | 0.113656E+09 | 0.208983E+09 |
| March | 0.213907E+09 | 90589428.30 | 0.123317E+09 | 0.199280E+09 | 0.161350E+09 |
| April | 0.248468E+09 | 0.109363E+09 | 0.139105E+09 | 0.263115E+09 | 0.112976E+09 |
| May | 0.309836E+09 | 0.123572E+09 | 0.186264E+09 | 0.362500E+09 | 78181629.85 |
| June | 0.278303E+09 | 0.100821E+09 | 0.177482E+09 | 0.348969E+09 | 48213561.16 |
| July | 0.288598E+09 | 0.104031E+09 | 0.184567E+09 | 0.387041E+09 | 29918192.48 |
| August | 0.324886E+09 | 0.146389E+09 | 0.178497E+09 | 0.432835E+09 | 40978511.73 |
| September | 0.235184E+09 | 0.105821E+09 | 0.129363E+09 | 0.281244E+09 | 73023265.30 |
| October | 0.220157E+09 | 99879103.38 | 0.120278E+09 | 0.238904E+09 | 0.130831E+09 |
| November | 0.131816E+09 | 50700678.31 | 81114865.48 | 0.109245E+09 | 0.171556E+09 |
| December | 0.106466E+09 | 50237992.65 | 56227798.27 | 76192610.14 | 0.219752E+09 |
| Annual Sum or Average | 0.261530E+10 | 0.109408E+10 | 0.152122E+10 | 0.288482E+10 | 0.151191E+10 |
| Minimum of Months | 0.106466E+09 | 43178725.60 | 56227798.27 | 71840992.62 | 29918192.48 |
| Maximum of Months | 0.324886E+09 | 0.146389E+09 | 0.186264E+09 | 0.432835E+09 | 0.236145E+09 |
Report: WindowEnergyReportMonthly
For: MWINDOW14
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 36168525.78 | 14498024.71 | 21670501.07 | 20730915.46 | 96372554.51 |
| February | 50352801.23 | 23334402.18 | 27018399.04 | 33608401.56 | 85636923.90 |
| March | 71822997.42 | 30417010.95 | 41405986.47 | 61063894.98 | 66936638.43 |
| April | 83427601.15 | 36720707.64 | 46706893.51 | 81899969.81 | 47136534.17 |
| May | 0.104033E+09 | 41491661.29 | 62541299.09 | 0.114641E+09 | 32542522.54 |
| June | 93445170.34 | 33852460.79 | 59592709.55 | 0.116151E+09 | 16831054.60 |
| July | 96902034.38 | 34930391.32 | 61971643.06 | 0.131094E+09 | 9424848.44 |
| August | 0.109086E+09 | 49152640.32 | 59933675.28 | 0.146721E+09 | 12739804.67 |
| September | 78967322.58 | 35531336.66 | 43435985.91 | 93678792.74 | 25121861.52 |
| October | 73921532.48 | 33536184.50 | 40385347.98 | 77976195.27 | 47098595.56 |
| November | 44259412.10 | 17023654.05 | 27235758.06 | 33676511.28 | 65689702.92 |
| December | 35747781.94 | 16868299.11 | 18879482.83 | 22841983.13 | 87800803.00 |
| Annual Sum or Average | 0.878134E+09 | 0.367357E+09 | 0.510778E+09 | 0.934084E+09 | 0.593332E+09 |
| Minimum of Months | 35747781.94 | 14498024.71 | 18879482.83 | 20730915.46 | 9424848.44 |
| Maximum of Months | 0.109086E+09 | 49152640.32 | 62541299.09 | 0.146721E+09 | 96372554.51 |
Report: WindowZoneSummaryMonthly
For: G SW APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 238.93 | 324.93 | 268.43 | 162.38 | 106.04 | 0.00 | 0.00 |
| February | 335.56 | 320.06 | 363.66 | 223.35 | 140.31 | 0.00 | 0.00 |
| March | 376.57 | 217.47 | 368.43 | 191.00 | 177.44 | 0.00 | 0.00 |
| April | 368.61 | 156.47 | 334.81 | 140.88 | 193.93 | 0.00 | 0.00 |
| May | 389.09 | 95.40 | 325.22 | 93.89 | 231.33 | 0.00 | 0.00 |
| June | 438.95 | 53.83 | 330.79 | 93.92 | 236.87 | 0.00 | 0.00 |
| July | 473.60 | 24.90 | 326.84 | 89.05 | 237.79 | 0.00 | 0.00 |
| August | 576.48 | 39.66 | 399.26 | 163.74 | 235.52 | 0.00 | 0.00 |
| September | 467.00 | 87.26 | 362.34 | 174.42 | 187.92 | 0.00 | 0.00 |
| October | 541.96 | 168.37 | 455.85 | 267.88 | 187.97 | 0.00 | 0.00 |
| November | 284.01 | 237.61 | 290.95 | 157.11 | 133.84 | 0.00 | 0.00 |
| December | 262.73 | 295.17 | 280.86 | 185.11 | 95.75 | 0.00 | 0.00 |
| Annual Sum or Average | 396.69 | 167.56 | 342.25 | 161.61 | 180.64 | 0.00 | 0.00 |
| Minimum of Months | 238.93 | 24.90 | 268.43 | 89.05 | 95.75 | 0.00 | 0.00 |
| Maximum of Months | 576.48 | 324.93 | 455.85 | 267.88 | 237.79 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: G NW APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 31.06 | 345.42 | 96.73 | 22.92 | 73.82 | 0.00 | 0.00 |
| February | 56.78 | 345.94 | 137.80 | 35.87 | 101.93 | 0.00 | 0.00 |
| March | 144.64 | 217.55 | 199.40 | 56.41 | 142.99 | 0.00 | 0.00 |
| April | 210.61 | 150.04 | 225.39 | 56.66 | 168.73 | 0.00 | 0.00 |
| May | 314.03 | 89.48 | 278.60 | 63.12 | 215.49 | 0.00 | 0.00 |
| June | 385.00 | 51.47 | 299.94 | 75.08 | 224.85 | 0.00 | 0.00 |
| July | 404.26 | 24.22 | 285.13 | 64.29 | 220.84 | 0.00 | 0.00 |
| August | 401.80 | 37.78 | 287.26 | 82.29 | 204.96 | 0.00 | 0.00 |
| September | 245.39 | 85.50 | 209.02 | 54.31 | 154.72 | 0.00 | 0.00 |
| October | 191.06 | 161.43 | 196.05 | 59.56 | 136.49 | 0.00 | 0.00 |
| November | 55.69 | 238.42 | 109.32 | 16.79 | 92.53 | 0.00 | 0.00 |
| December | 28.25 | 315.32 | 87.11 | 22.26 | 64.85 | 0.00 | 0.00 |
| Annual Sum or Average | 206.74 | 170.90 | 201.39 | 50.92 | 150.47 | 0.00 | 0.00 |
| Minimum of Months | 28.25 | 24.22 | 87.11 | 16.79 | 64.85 | 0.00 | 0.00 |
| Maximum of Months | 404.26 | 345.94 | 299.94 | 82.29 | 224.85 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: OFFICE
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 251.36 | 279.04 | 268.92 | 162.02 | 106.90 | 0.00 | 0.00 |
| February | 354.96 | 278.87 | 368.63 | 227.67 | 140.96 | 0.00 | 0.00 |
| March | 374.16 | 200.52 | 358.52 | 181.92 | 176.60 | 0.00 | 0.00 |
| April | 369.83 | 153.33 | 336.95 | 143.57 | 193.38 | 0.00 | 0.00 |
| May | 387.46 | 105.05 | 332.82 | 99.83 | 232.99 | 0.00 | 0.00 |
| June | 397.53 | 71.25 | 312.19 | 80.09 | 232.10 | 0.00 | 0.00 |
| July | 437.98 | 49.68 | 319.69 | 83.93 | 235.76 | 0.00 | 0.00 |
| August | 545.37 | 67.06 | 394.39 | 159.45 | 234.94 | 0.00 | 0.00 |
| September | 454.48 | 112.13 | 365.09 | 177.28 | 187.81 | 0.00 | 0.00 |
| October | 526.20 | 183.29 | 448.17 | 260.50 | 187.67 | 0.00 | 0.00 |
| November | 305.30 | 231.69 | 304.24 | 167.69 | 136.55 | 0.00 | 0.00 |
| December | 276.42 | 266.69 | 285.09 | 189.09 | 96.00 | 0.00 | 0.00 |
| Annual Sum or Average | 390.47 | 165.89 | 341.13 | 160.75 | 180.38 | 0.00 | 0.00 |
| Minimum of Months | 251.36 | 49.68 | 268.92 | 80.09 | 96.00 | 0.00 | 0.00 |
| Maximum of Months | 545.37 | 279.04 | 448.17 | 260.50 | 235.76 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: G NE APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 28.85 | 340.75 | 97.23 | 22.56 | 74.67 | 0.00 | 0.00 |
| February | 53.94 | 333.58 | 142.78 | 40.20 | 102.58 | 0.00 | 0.00 |
| March | 132.61 | 218.31 | 189.49 | 47.33 | 142.16 | 0.00 | 0.00 |
| April | 210.38 | 146.77 | 227.53 | 59.35 | 168.19 | 0.00 | 0.00 |
| May | 322.38 | 88.31 | 286.20 | 69.06 | 217.14 | 0.00 | 0.00 |
| June | 359.78 | 50.74 | 281.34 | 61.26 | 220.08 | 0.00 | 0.00 |
| July | 394.71 | 23.99 | 277.98 | 59.17 | 218.81 | 0.00 | 0.00 |
| August | 394.06 | 36.86 | 282.39 | 78.01 | 204.38 | 0.00 | 0.00 |
| September | 246.26 | 83.17 | 211.78 | 57.17 | 154.61 | 0.00 | 0.00 |
| October | 179.51 | 158.50 | 188.37 | 52.18 | 136.19 | 0.00 | 0.00 |
| November | 70.58 | 233.51 | 122.61 | 27.37 | 95.24 | 0.00 | 0.00 |
| December | 29.87 | 308.72 | 91.34 | 26.25 | 65.09 | 0.00 | 0.00 |
| Annual Sum or Average | 202.91 | 167.69 | 200.27 | 50.06 | 150.21 | 0.00 | 0.00 |
| Minimum of Months | 28.85 | 23.99 | 91.34 | 22.56 | 65.09 | 0.00 | 0.00 |
| Maximum of Months | 394.71 | 340.75 | 286.20 | 78.01 | 220.08 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: G N1 APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 2.98 | 221.27 | 40.95 | 0.00 | 40.95 | 0.00 | 0.00 |
| February | 6.57 | 223.33 | 56.04 | 0.00 | 56.04 | 0.00 | 0.00 |
| March | 33.89 | 139.69 | 77.74 | 0.00 | 77.73 | 0.00 | 0.00 |
| April | 68.95 | 93.56 | 93.40 | 0.31 | 93.09 | 0.00 | 0.00 |
| May | 127.66 | 55.42 | 124.33 | 4.50 | 119.83 | 0.00 | 0.00 |
| June | 164.41 | 30.87 | 131.10 | 6.83 | 124.27 | 0.00 | 0.00 |
| July | 183.03 | 14.30 | 127.21 | 4.82 | 122.38 | 0.00 | 0.00 |
| August | 158.99 | 22.10 | 112.65 | 1.53 | 111.13 | 0.00 | 0.00 |
| September | 91.02 | 52.27 | 84.81 | 0.04 | 84.77 | 0.00 | 0.00 |
| October | 54.35 | 101.23 | 73.35 | 0.00 | 73.35 | 0.00 | 0.00 |
| November | 16.46 | 151.30 | 51.45 | 0.00 | 51.45 | 0.00 | 0.00 |
| December | 1.95 | 202.38 | 35.72 | 0.00 | 35.72 | 0.00 | 0.00 |
| Annual Sum or Average | 76.32 | 108.33 | 84.23 | 1.51 | 82.71 | 0.00 | 0.00 |
| Minimum of Months | 1.95 | 14.30 | 35.72 | 0.00 | 35.72 | 0.00 | 0.00 |
| Maximum of Months | 183.03 | 223.33 | 131.10 | 6.83 | 124.27 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: G N2 APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 2.98 | 221.27 | 40.95 | 0.00 | 40.95 | 0.00 | 0.00 |
| February | 6.56 | 223.34 | 56.04 | 0.00 | 56.04 | 0.00 | 0.00 |
| March | 33.89 | 139.67 | 77.74 | 0.00 | 77.73 | 0.00 | 0.00 |
| April | 68.91 | 93.56 | 93.40 | 0.31 | 93.09 | 0.00 | 0.00 |
| May | 127.65 | 55.39 | 124.33 | 4.50 | 119.83 | 0.00 | 0.00 |
| June | 164.41 | 30.85 | 131.10 | 6.83 | 124.27 | 0.00 | 0.00 |
| July | 183.03 | 14.29 | 127.21 | 4.82 | 122.38 | 0.00 | 0.00 |
| August | 158.98 | 22.09 | 112.65 | 1.53 | 111.13 | 0.00 | 0.00 |
| September | 91.00 | 52.27 | 84.81 | 0.04 | 84.77 | 0.00 | 0.00 |
| October | 54.34 | 101.20 | 73.35 | 0.00 | 73.35 | 0.00 | 0.00 |
| November | 16.43 | 151.37 | 51.45 | 0.00 | 51.45 | 0.00 | 0.00 |
| December | 1.95 | 202.39 | 35.72 | 0.00 | 35.72 | 0.00 | 0.00 |
| Annual Sum or Average | 76.31 | 108.33 | 84.23 | 1.51 | 82.71 | 0.00 | 0.00 |
| Minimum of Months | 1.95 | 14.29 | 35.72 | 0.00 | 35.72 | 0.00 | 0.00 |
| Maximum of Months | 183.03 | 223.34 | 131.10 | 6.83 | 124.27 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: G S1 APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 210.48 | 198.07 | 212.64 | 139.47 | 73.18 | 0.00 | 0.00 |
| February | 286.31 | 195.25 | 281.89 | 187.48 | 94.41 | 0.00 | 0.00 |
| March | 266.21 | 136.82 | 246.77 | 134.59 | 112.18 | 0.00 | 0.00 |
| April | 229.49 | 99.35 | 202.81 | 84.53 | 118.28 | 0.00 | 0.00 |
| May | 204.71 | 61.59 | 170.95 | 35.27 | 135.68 | 0.00 | 0.00 |
| June | 218.84 | 33.15 | 161.95 | 25.67 | 136.28 | 0.00 | 0.00 |
| July | 252.75 | 14.76 | 168.92 | 29.58 | 139.34 | 0.00 | 0.00 |
| August | 334.73 | 23.51 | 224.66 | 82.97 | 141.69 | 0.00 | 0.00 |
| September | 314.31 | 53.00 | 238.13 | 120.16 | 117.97 | 0.00 | 0.00 |
| October | 408.33 | 102.52 | 333.15 | 208.32 | 124.83 | 0.00 | 0.00 |
| November | 247.20 | 146.48 | 233.08 | 140.32 | 92.75 | 0.00 | 0.00 |
| December | 236.74 | 179.49 | 229.47 | 162.84 | 66.62 | 0.00 | 0.00 |
| Annual Sum or Average | 267.52 | 103.14 | 225.08 | 112.20 | 112.88 | 0.00 | 0.00 |
| Minimum of Months | 204.71 | 14.76 | 161.95 | 25.67 | 66.62 | 0.00 | 0.00 |
| Maximum of Months | 408.33 | 198.07 | 333.15 | 208.32 | 141.69 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: G S2 APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 210.85 | 196.84 | 212.64 | 139.47 | 73.18 | 0.00 | 0.00 |
| February | 286.74 | 194.18 | 281.89 | 187.48 | 94.41 | 0.00 | 0.00 |
| March | 266.51 | 136.15 | 246.77 | 134.59 | 112.18 | 0.00 | 0.00 |
| April | 229.40 | 99.40 | 202.81 | 84.53 | 118.28 | 0.00 | 0.00 |
| May | 204.00 | 62.26 | 170.95 | 35.27 | 135.68 | 0.00 | 0.00 |
| June | 218.31 | 33.58 | 161.95 | 25.67 | 136.28 | 0.00 | 0.00 |
| July | 251.98 | 15.32 | 168.92 | 29.58 | 139.34 | 0.00 | 0.00 |
| August | 334.01 | 24.10 | 224.66 | 82.97 | 141.69 | 0.00 | 0.00 |
| September | 313.84 | 53.58 | 238.13 | 120.16 | 117.97 | 0.00 | 0.00 |
| October | 408.07 | 102.91 | 333.15 | 208.32 | 124.83 | 0.00 | 0.00 |
| November | 247.15 | 146.47 | 233.08 | 140.32 | 92.75 | 0.00 | 0.00 |
| December | 237.01 | 178.66 | 229.47 | 162.84 | 66.62 | 0.00 | 0.00 |
| Annual Sum or Average | 267.33 | 103.10 | 225.08 | 112.20 | 112.88 | 0.00 | 0.00 |
| Minimum of Months | 204.00 | 15.32 | 161.95 | 25.67 | 66.62 | 0.00 | 0.00 |
| Maximum of Months | 408.07 | 196.84 | 333.15 | 208.32 | 141.69 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: M SW APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 233.82 | 336.45 | 268.43 | 162.38 | 106.04 | 0.00 | 0.00 |
| February | 327.59 | 333.18 | 363.66 | 223.35 | 140.31 | 0.00 | 0.00 |
| March | 365.37 | 233.40 | 368.43 | 191.00 | 177.44 | 0.00 | 0.00 |
| April | 353.28 | 176.21 | 334.81 | 140.88 | 193.93 | 0.00 | 0.00 |
| May | 370.22 | 113.50 | 325.22 | 93.89 | 231.33 | 0.00 | 0.00 |
| June | 433.87 | 56.53 | 330.79 | 93.92 | 236.87 | 0.00 | 0.00 |
| July | 470.85 | 25.64 | 326.84 | 89.05 | 237.79 | 0.00 | 0.00 |
| August | 575.10 | 39.22 | 399.26 | 163.74 | 235.52 | 0.00 | 0.00 |
| September | 465.52 | 87.06 | 362.34 | 174.42 | 187.92 | 0.00 | 0.00 |
| October | 540.05 | 167.40 | 455.85 | 267.88 | 187.97 | 0.00 | 0.00 |
| November | 281.37 | 240.47 | 290.95 | 157.11 | 133.84 | 0.00 | 0.00 |
| December | 258.29 | 303.33 | 280.86 | 185.11 | 95.75 | 0.00 | 0.00 |
| Annual Sum or Average | 390.19 | 175.13 | 342.25 | 161.61 | 180.64 | 0.00 | 0.00 |
| Minimum of Months | 233.82 | 25.64 | 268.43 | 89.05 | 95.75 | 0.00 | 0.00 |
| Maximum of Months | 575.10 | 336.45 | 455.85 | 267.88 | 237.79 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: M NW APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 29.00 | 358.74 | 96.73 | 22.92 | 73.82 | 0.00 | 0.00 |
| February | 53.26 | 361.31 | 137.80 | 35.87 | 101.93 | 0.00 | 0.00 |
| March | 136.89 | 232.00 | 199.40 | 56.41 | 142.99 | 0.00 | 0.00 |
| April | 196.02 | 169.70 | 225.39 | 56.66 | 168.73 | 0.00 | 0.00 |
| May | 292.07 | 108.97 | 278.60 | 63.12 | 215.49 | 0.00 | 0.00 |
| June | 379.90 | 54.21 | 299.94 | 75.08 | 224.85 | 0.00 | 0.00 |
| July | 401.69 | 25.11 | 285.13 | 64.29 | 220.84 | 0.00 | 0.00 |
| August | 400.75 | 37.77 | 287.26 | 82.29 | 204.96 | 0.00 | 0.00 |
| September | 244.27 | 86.20 | 209.02 | 54.31 | 154.72 | 0.00 | 0.00 |
| October | 190.39 | 161.49 | 196.05 | 59.56 | 136.49 | 0.00 | 0.00 |
| November | 54.12 | 243.47 | 109.32 | 16.79 | 92.53 | 0.00 | 0.00 |
| December | 26.73 | 325.10 | 87.11 | 22.26 | 64.85 | 0.00 | 0.00 |
| Annual Sum or Average | 201.44 | 179.31 | 201.39 | 50.92 | 150.47 | 0.00 | 0.00 |
| Minimum of Months | 26.73 | 25.11 | 87.11 | 16.79 | 64.85 | 0.00 | 0.00 |
| Maximum of Months | 401.69 | 361.31 | 299.94 | 82.29 | 224.85 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: M SE APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 235.18 | 335.05 | 268.92 | 162.02 | 106.90 | 0.00 | 0.00 |
| February | 334.82 | 330.44 | 368.63 | 227.67 | 140.96 | 0.00 | 0.00 |
| March | 354.75 | 235.31 | 358.52 | 181.92 | 176.60 | 0.00 | 0.00 |
| April | 353.11 | 173.35 | 336.95 | 143.57 | 193.38 | 0.00 | 0.00 |
| May | 377.46 | 111.58 | 332.82 | 99.83 | 232.99 | 0.00 | 0.00 |
| June | 408.19 | 55.18 | 312.19 | 80.09 | 232.10 | 0.00 | 0.00 |
| July | 461.08 | 25.09 | 319.69 | 83.93 | 235.76 | 0.00 | 0.00 |
| August | 566.92 | 37.85 | 394.39 | 159.45 | 234.94 | 0.00 | 0.00 |
| September | 467.07 | 85.29 | 365.09 | 177.28 | 187.81 | 0.00 | 0.00 |
| October | 529.45 | 165.46 | 448.17 | 260.50 | 187.67 | 0.00 | 0.00 |
| November | 299.82 | 239.07 | 304.24 | 167.69 | 136.55 | 0.00 | 0.00 |
| December | 264.51 | 301.14 | 285.09 | 189.09 | 96.00 | 0.00 | 0.00 |
| Annual Sum or Average | 388.19 | 173.68 | 341.13 | 160.75 | 180.38 | 0.00 | 0.00 |
| Minimum of Months | 235.18 | 25.09 | 268.92 | 80.09 | 96.00 | 0.00 | 0.00 |
| Maximum of Months | 566.92 | 335.05 | 448.17 | 260.50 | 235.76 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: M NE APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 26.66 | 353.72 | 97.23 | 22.56 | 74.67 | 0.00 | 0.00 |
| February | 50.01 | 348.24 | 142.78 | 40.20 | 102.58 | 0.00 | 0.00 |
| March | 125.20 | 232.82 | 189.49 | 47.33 | 142.16 | 0.00 | 0.00 |
| April | 195.08 | 166.28 | 227.53 | 59.35 | 168.19 | 0.00 | 0.00 |
| May | 299.95 | 107.81 | 286.20 | 69.06 | 217.14 | 0.00 | 0.00 |
| June | 354.83 | 53.49 | 281.34 | 61.26 | 220.08 | 0.00 | 0.00 |
| July | 392.23 | 24.90 | 277.98 | 59.17 | 218.81 | 0.00 | 0.00 |
| August | 392.98 | 36.84 | 282.39 | 78.01 | 204.38 | 0.00 | 0.00 |
| September | 245.05 | 83.83 | 211.78 | 57.17 | 154.61 | 0.00 | 0.00 |
| October | 178.77 | 158.45 | 188.37 | 52.18 | 136.19 | 0.00 | 0.00 |
| November | 68.84 | 238.13 | 122.61 | 27.37 | 95.24 | 0.00 | 0.00 |
| December | 28.23 | 318.13 | 91.34 | 26.25 | 65.09 | 0.00 | 0.00 |
| Annual Sum or Average | 197.48 | 175.93 | 200.27 | 50.06 | 150.21 | 0.00 | 0.00 |
| Minimum of Months | 26.66 | 24.90 | 91.34 | 22.56 | 65.09 | 0.00 | 0.00 |
| Maximum of Months | 392.98 | 353.72 | 286.20 | 78.01 | 220.08 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: M N1 APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 2.43 | 229.64 | 40.95 | 0.00 | 40.95 | 0.00 | 0.00 |
| February | 5.60 | 232.93 | 56.04 | 0.00 | 56.04 | 0.00 | 0.00 |
| March | 30.64 | 148.56 | 77.74 | 0.00 | 77.73 | 0.00 | 0.00 |
| April | 61.23 | 105.86 | 93.40 | 0.31 | 93.09 | 0.00 | 0.00 |
| May | 115.94 | 66.21 | 124.33 | 4.50 | 119.83 | 0.00 | 0.00 |
| June | 162.38 | 32.02 | 131.10 | 6.83 | 124.27 | 0.00 | 0.00 |
| July | 182.16 | 14.63 | 127.21 | 4.82 | 122.38 | 0.00 | 0.00 |
| August | 158.83 | 22.05 | 112.65 | 1.53 | 111.13 | 0.00 | 0.00 |
| September | 90.64 | 52.70 | 84.81 | 0.04 | 84.77 | 0.00 | 0.00 |
| October | 53.92 | 101.93 | 73.35 | 0.00 | 73.35 | 0.00 | 0.00 |
| November | 15.67 | 155.26 | 51.45 | 0.00 | 51.45 | 0.00 | 0.00 |
| December | 1.63 | 209.00 | 35.72 | 0.00 | 35.72 | 0.00 | 0.00 |
| Annual Sum or Average | 73.88 | 113.56 | 84.23 | 1.51 | 82.71 | 0.00 | 0.00 |
| Minimum of Months | 1.63 | 14.63 | 35.72 | 0.00 | 35.72 | 0.00 | 0.00 |
| Maximum of Months | 182.16 | 232.93 | 131.10 | 6.83 | 124.27 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: M N2 APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 2.43 | 229.64 | 40.95 | 0.00 | 40.95 | 0.00 | 0.00 |
| February | 5.59 | 232.94 | 56.04 | 0.00 | 56.04 | 0.00 | 0.00 |
| March | 30.63 | 148.51 | 77.74 | 0.00 | 77.73 | 0.00 | 0.00 |
| April | 61.16 | 105.87 | 93.40 | 0.31 | 93.09 | 0.00 | 0.00 |
| May | 115.91 | 66.20 | 124.33 | 4.50 | 119.83 | 0.00 | 0.00 |
| June | 162.38 | 32.01 | 131.10 | 6.83 | 124.27 | 0.00 | 0.00 |
| July | 182.15 | 14.62 | 127.21 | 4.82 | 122.38 | 0.00 | 0.00 |
| August | 158.82 | 22.04 | 112.65 | 1.53 | 111.13 | 0.00 | 0.00 |
| September | 90.62 | 52.69 | 84.81 | 0.04 | 84.77 | 0.00 | 0.00 |
| October | 53.90 | 101.90 | 73.35 | 0.00 | 73.35 | 0.00 | 0.00 |
| November | 15.63 | 155.32 | 51.45 | 0.00 | 51.45 | 0.00 | 0.00 |
| December | 1.63 | 209.02 | 35.72 | 0.00 | 35.72 | 0.00 | 0.00 |
| Annual Sum or Average | 73.86 | 113.56 | 84.23 | 1.51 | 82.71 | 0.00 | 0.00 |
| Minimum of Months | 1.63 | 14.62 | 35.72 | 0.00 | 35.72 | 0.00 | 0.00 |
| Maximum of Months | 182.15 | 232.94 | 131.10 | 6.83 | 124.27 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: M S1 APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 207.12 | 204.91 | 212.64 | 139.47 | 73.18 | 0.00 | 0.00 |
| February | 281.54 | 202.70 | 281.89 | 187.48 | 94.41 | 0.00 | 0.00 |
| March | 259.89 | 147.54 | 246.77 | 134.59 | 112.18 | 0.00 | 0.00 |
| April | 221.18 | 111.70 | 202.81 | 84.53 | 118.28 | 0.00 | 0.00 |
| May | 195.79 | 71.31 | 170.95 | 35.27 | 135.68 | 0.00 | 0.00 |
| June | 216.74 | 34.30 | 161.95 | 25.67 | 136.28 | 0.00 | 0.00 |
| July | 251.68 | 14.96 | 168.92 | 29.58 | 139.34 | 0.00 | 0.00 |
| August | 334.15 | 23.16 | 224.66 | 82.97 | 141.69 | 0.00 | 0.00 |
| September | 313.45 | 52.82 | 238.13 | 120.16 | 117.97 | 0.00 | 0.00 |
| October | 406.88 | 102.36 | 333.15 | 208.32 | 124.83 | 0.00 | 0.00 |
| November | 245.24 | 148.71 | 233.08 | 140.32 | 92.75 | 0.00 | 0.00 |
| December | 233.57 | 185.02 | 229.47 | 162.84 | 66.62 | 0.00 | 0.00 |
| Annual Sum or Average | 263.95 | 107.75 | 225.08 | 112.20 | 112.88 | 0.00 | 0.00 |
| Minimum of Months | 195.79 | 14.96 | 161.95 | 25.67 | 66.62 | 0.00 | 0.00 |
| Maximum of Months | 406.88 | 204.91 | 333.15 | 208.32 | 141.69 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: M S2 APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 207.10 | 204.91 | 212.64 | 139.47 | 73.18 | 0.00 | 0.00 |
| February | 281.52 | 202.69 | 281.89 | 187.48 | 94.41 | 0.00 | 0.00 |
| March | 259.87 | 147.47 | 246.77 | 134.59 | 112.18 | 0.00 | 0.00 |
| April | 221.13 | 111.70 | 202.81 | 84.53 | 118.28 | 0.00 | 0.00 |
| May | 195.77 | 71.30 | 170.95 | 35.27 | 135.68 | 0.00 | 0.00 |
| June | 216.74 | 34.29 | 161.95 | 25.67 | 136.28 | 0.00 | 0.00 |
| July | 251.67 | 14.95 | 168.92 | 29.58 | 139.34 | 0.00 | 0.00 |
| August | 334.15 | 23.15 | 224.66 | 82.97 | 141.69 | 0.00 | 0.00 |
| September | 313.44 | 52.81 | 238.13 | 120.16 | 117.97 | 0.00 | 0.00 |
| October | 406.87 | 102.35 | 333.15 | 208.32 | 124.83 | 0.00 | 0.00 |
| November | 245.20 | 148.77 | 233.08 | 140.32 | 92.75 | 0.00 | 0.00 |
| December | 233.55 | 185.03 | 229.47 | 162.84 | 66.62 | 0.00 | 0.00 |
| Annual Sum or Average | 263.93 | 107.74 | 225.08 | 112.20 | 112.88 | 0.00 | 0.00 |
| Minimum of Months | 195.77 | 14.95 | 161.95 | 25.67 | 66.62 | 0.00 | 0.00 |
| Maximum of Months | 406.87 | 204.91 | 333.15 | 208.32 | 141.69 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: T SW APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 233.72 | 324.11 | 268.43 | 162.38 | 106.04 | 0.00 | 0.00 |
| February | 326.65 | 320.59 | 363.66 | 223.35 | 140.31 | 0.00 | 0.00 |
| March | 362.88 | 222.15 | 368.43 | 191.00 | 177.44 | 0.00 | 0.00 |
| April | 353.21 | 162.52 | 334.81 | 140.88 | 193.93 | 0.00 | 0.00 |
| May | 372.40 | 101.43 | 325.22 | 93.89 | 231.33 | 0.00 | 0.00 |
| June | 428.30 | 54.10 | 330.79 | 93.92 | 236.87 | 0.00 | 0.00 |
| July | 463.55 | 24.93 | 326.84 | 89.05 | 237.79 | 0.00 | 0.00 |
| August | 567.69 | 37.71 | 399.26 | 163.74 | 235.52 | 0.00 | 0.00 |
| September | 462.68 | 80.86 | 362.34 | 174.42 | 187.92 | 0.00 | 0.00 |
| October | 542.05 | 150.08 | 455.85 | 267.88 | 187.97 | 0.00 | 0.00 |
| November | 284.07 | 224.16 | 290.95 | 157.11 | 133.84 | 0.00 | 0.00 |
| December | 258.31 | 290.55 | 280.86 | 185.11 | 95.75 | 0.00 | 0.00 |
| Annual Sum or Average | 388.53 | 165.22 | 342.25 | 161.61 | 180.64 | 0.00 | 0.00 |
| Minimum of Months | 233.72 | 24.93 | 268.43 | 89.05 | 95.75 | 0.00 | 0.00 |
| Maximum of Months | 567.69 | 324.11 | 455.85 | 267.88 | 237.79 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: T NW APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 29.62 | 346.46 | 96.73 | 22.92 | 73.82 | 0.00 | 0.00 |
| February | 53.74 | 349.20 | 137.80 | 35.87 | 101.93 | 0.00 | 0.00 |
| March | 136.25 | 222.93 | 199.40 | 56.41 | 142.99 | 0.00 | 0.00 |
| April | 196.50 | 158.61 | 225.39 | 56.66 | 168.73 | 0.00 | 0.00 |
| May | 295.74 | 97.95 | 278.60 | 63.12 | 215.49 | 0.00 | 0.00 |
| June | 375.07 | 52.18 | 299.94 | 75.08 | 224.85 | 0.00 | 0.00 |
| July | 395.10 | 24.64 | 285.13 | 64.29 | 220.84 | 0.00 | 0.00 |
| August | 394.77 | 36.59 | 287.26 | 82.29 | 204.96 | 0.00 | 0.00 |
| September | 243.66 | 79.32 | 209.02 | 54.31 | 154.72 | 0.00 | 0.00 |
| October | 195.12 | 145.02 | 196.05 | 59.56 | 136.49 | 0.00 | 0.00 |
| November | 55.92 | 231.01 | 109.32 | 16.79 | 92.53 | 0.00 | 0.00 |
| December | 27.34 | 312.84 | 87.11 | 22.26 | 64.85 | 0.00 | 0.00 |
| Annual Sum or Average | 200.91 | 170.38 | 201.39 | 50.92 | 150.47 | 0.00 | 0.00 |
| Minimum of Months | 27.34 | 24.64 | 87.11 | 16.79 | 64.85 | 0.00 | 0.00 |
| Maximum of Months | 395.10 | 349.20 | 299.94 | 82.29 | 224.85 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: T SE APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 235.18 | 322.67 | 268.92 | 162.02 | 106.90 | 0.00 | 0.00 |
| February | 334.15 | 317.87 | 368.63 | 227.67 | 140.96 | 0.00 | 0.00 |
| March | 352.27 | 224.25 | 358.52 | 181.92 | 176.60 | 0.00 | 0.00 |
| April | 353.37 | 160.08 | 336.95 | 143.57 | 193.38 | 0.00 | 0.00 |
| May | 379.57 | 100.12 | 332.82 | 99.83 | 232.99 | 0.00 | 0.00 |
| June | 402.78 | 52.91 | 312.19 | 80.09 | 232.10 | 0.00 | 0.00 |
| July | 453.86 | 24.34 | 319.69 | 83.93 | 235.76 | 0.00 | 0.00 |
| August | 559.45 | 36.32 | 394.39 | 159.45 | 234.94 | 0.00 | 0.00 |
| September | 464.16 | 79.35 | 365.09 | 177.28 | 187.81 | 0.00 | 0.00 |
| October | 530.95 | 147.98 | 448.17 | 260.50 | 187.67 | 0.00 | 0.00 |
| November | 302.46 | 222.48 | 304.24 | 167.69 | 136.55 | 0.00 | 0.00 |
| December | 264.55 | 288.24 | 285.09 | 189.09 | 96.00 | 0.00 | 0.00 |
| Annual Sum or Average | 386.55 | 163.85 | 341.13 | 160.75 | 180.38 | 0.00 | 0.00 |
| Minimum of Months | 235.18 | 24.34 | 268.92 | 80.09 | 96.00 | 0.00 | 0.00 |
| Maximum of Months | 559.45 | 322.67 | 448.17 | 260.50 | 235.76 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: T NE APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 27.70 | 341.74 | 97.23 | 22.56 | 74.67 | 0.00 | 0.00 |
| February | 51.31 | 336.73 | 142.78 | 40.20 | 102.58 | 0.00 | 0.00 |
| March | 124.95 | 224.03 | 189.49 | 47.33 | 142.16 | 0.00 | 0.00 |
| April | 195.89 | 155.37 | 227.53 | 59.35 | 168.19 | 0.00 | 0.00 |
| May | 302.86 | 96.79 | 286.20 | 69.06 | 217.14 | 0.00 | 0.00 |
| June | 349.90 | 51.36 | 281.34 | 61.26 | 220.08 | 0.00 | 0.00 |
| July | 385.63 | 24.31 | 277.98 | 59.17 | 218.81 | 0.00 | 0.00 |
| August | 386.84 | 35.53 | 282.39 | 78.01 | 204.38 | 0.00 | 0.00 |
| September | 244.35 | 77.41 | 211.78 | 57.17 | 154.61 | 0.00 | 0.00 |
| October | 183.66 | 141.87 | 188.37 | 52.18 | 136.19 | 0.00 | 0.00 |
| November | 71.25 | 225.73 | 122.61 | 27.37 | 95.24 | 0.00 | 0.00 |
| December | 29.35 | 306.27 | 91.34 | 26.25 | 65.09 | 0.00 | 0.00 |
| Annual Sum or Average | 197.12 | 167.15 | 200.27 | 50.06 | 150.21 | 0.00 | 0.00 |
| Minimum of Months | 27.70 | 24.31 | 91.34 | 22.56 | 65.09 | 0.00 | 0.00 |
| Maximum of Months | 386.84 | 341.74 | 286.20 | 78.01 | 220.08 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: T N1 APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 2.72 | 222.20 | 40.95 | 0.00 | 40.95 | 0.00 | 0.00 |
| February | 5.89 | 225.72 | 56.04 | 0.00 | 56.04 | 0.00 | 0.00 |
| March | 30.79 | 143.27 | 77.74 | 0.00 | 77.73 | 0.00 | 0.00 |
| April | 62.30 | 99.02 | 93.40 | 0.31 | 93.09 | 0.00 | 0.00 |
| May | 118.32 | 60.52 | 124.33 | 4.50 | 119.83 | 0.00 | 0.00 |
| June | 159.85 | 31.34 | 131.10 | 6.83 | 124.27 | 0.00 | 0.00 |
| July | 178.78 | 14.61 | 127.21 | 4.82 | 122.38 | 0.00 | 0.00 |
| August | 155.82 | 21.67 | 112.65 | 1.53 | 111.13 | 0.00 | 0.00 |
| September | 90.36 | 49.57 | 84.81 | 0.04 | 84.77 | 0.00 | 0.00 |
| October | 57.51 | 91.00 | 73.35 | 0.00 | 73.35 | 0.00 | 0.00 |
| November | 17.19 | 146.14 | 51.45 | 0.00 | 51.45 | 0.00 | 0.00 |
| December | 1.84 | 201.28 | 35.72 | 0.00 | 35.72 | 0.00 | 0.00 |
| Annual Sum or Average | 73.90 | 108.20 | 84.23 | 1.51 | 82.71 | 0.00 | 0.00 |
| Minimum of Months | 1.84 | 14.61 | 35.72 | 0.00 | 35.72 | 0.00 | 0.00 |
| Maximum of Months | 178.78 | 225.72 | 131.10 | 6.83 | 124.27 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: T N2 APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 2.71 | 222.20 | 40.95 | 0.00 | 40.95 | 0.00 | 0.00 |
| February | 5.88 | 225.72 | 56.04 | 0.00 | 56.04 | 0.00 | 0.00 |
| March | 30.73 | 143.19 | 77.74 | 0.00 | 77.73 | 0.00 | 0.00 |
| April | 62.16 | 98.98 | 93.40 | 0.31 | 93.09 | 0.00 | 0.00 |
| May | 118.22 | 60.47 | 124.33 | 4.50 | 119.83 | 0.00 | 0.00 |
| June | 159.83 | 31.31 | 131.10 | 6.83 | 124.27 | 0.00 | 0.00 |
| July | 178.76 | 14.60 | 127.21 | 4.82 | 122.38 | 0.00 | 0.00 |
| August | 155.80 | 21.65 | 112.65 | 1.53 | 111.13 | 0.00 | 0.00 |
| September | 90.29 | 49.55 | 84.81 | 0.04 | 84.77 | 0.00 | 0.00 |
| October | 57.42 | 90.87 | 73.35 | 0.00 | 73.35 | 0.00 | 0.00 |
| November | 17.15 | 146.14 | 51.45 | 0.00 | 51.45 | 0.00 | 0.00 |
| December | 1.83 | 201.28 | 35.72 | 0.00 | 35.72 | 0.00 | 0.00 |
| Annual Sum or Average | 73.86 | 108.17 | 84.23 | 1.51 | 82.71 | 0.00 | 0.00 |
| Minimum of Months | 1.83 | 14.60 | 35.72 | 0.00 | 35.72 | 0.00 | 0.00 |
| Maximum of Months | 178.76 | 225.72 | 131.10 | 6.83 | 124.27 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: T S1 APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 207.24 | 197.41 | 212.64 | 139.47 | 73.18 | 0.00 | 0.00 |
| February | 281.27 | 195.17 | 281.89 | 187.48 | 94.41 | 0.00 | 0.00 |
| March | 259.10 | 139.89 | 246.77 | 134.59 | 112.18 | 0.00 | 0.00 |
| April | 221.91 | 103.00 | 202.81 | 84.53 | 118.28 | 0.00 | 0.00 |
| May | 196.95 | 65.07 | 170.95 | 35.27 | 135.68 | 0.00 | 0.00 |
| June | 213.73 | 33.45 | 161.95 | 25.67 | 136.28 | 0.00 | 0.00 |
| July | 247.78 | 14.81 | 168.92 | 29.58 | 139.34 | 0.00 | 0.00 |
| August | 330.16 | 22.59 | 224.66 | 82.97 | 141.69 | 0.00 | 0.00 |
| September | 311.66 | 50.24 | 238.13 | 120.16 | 117.97 | 0.00 | 0.00 |
| October | 408.00 | 93.00 | 333.15 | 208.32 | 124.83 | 0.00 | 0.00 |
| November | 247.68 | 137.50 | 233.08 | 140.32 | 92.75 | 0.00 | 0.00 |
| December | 233.88 | 176.68 | 229.47 | 162.84 | 66.62 | 0.00 | 0.00 |
| Annual Sum or Average | 263.29 | 101.87 | 225.08 | 112.20 | 112.88 | 0.00 | 0.00 |
| Minimum of Months | 196.95 | 14.81 | 161.95 | 25.67 | 66.62 | 0.00 | 0.00 |
| Maximum of Months | 408.00 | 197.41 | 333.15 | 208.32 | 141.69 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: T S2 APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 207.21 | 197.39 | 212.64 | 139.47 | 73.18 | 0.00 | 0.00 |
| February | 281.21 | 195.14 | 281.89 | 187.48 | 94.41 | 0.00 | 0.00 |
| March | 259.03 | 139.80 | 246.77 | 134.59 | 112.18 | 0.00 | 0.00 |
| April | 221.79 | 102.95 | 202.81 | 84.53 | 118.28 | 0.00 | 0.00 |
| May | 196.86 | 65.01 | 170.95 | 35.27 | 135.68 | 0.00 | 0.00 |
| June | 213.71 | 33.42 | 161.95 | 25.67 | 136.28 | 0.00 | 0.00 |
| July | 247.77 | 14.79 | 168.92 | 29.58 | 139.34 | 0.00 | 0.00 |
| August | 330.14 | 22.56 | 224.66 | 82.97 | 141.69 | 0.00 | 0.00 |
| September | 311.63 | 50.21 | 238.13 | 120.16 | 117.97 | 0.00 | 0.00 |
| October | 407.94 | 92.93 | 333.15 | 208.32 | 124.83 | 0.00 | 0.00 |
| November | 247.61 | 137.51 | 233.08 | 140.32 | 92.75 | 0.00 | 0.00 |
| December | 233.84 | 176.67 | 229.47 | 162.84 | 66.62 | 0.00 | 0.00 |
| Annual Sum or Average | 263.24 | 101.84 | 225.08 | 112.20 | 112.88 | 0.00 | 0.00 |
| Minimum of Months | 196.86 | 14.79 | 161.95 | 25.67 | 66.62 | 0.00 | 0.00 |
| Maximum of Months | 407.94 | 197.39 | 333.15 | 208.32 | 141.69 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: T CORRIDOR
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 8.17 | 33.24 | 13.50 | 5.41 | 8.09 | 0.00 | 0.00 |
| February | 14.49 | 32.73 | 20.81 | 9.65 | 11.17 | 0.00 | 0.00 |
| March | 23.32 | 23.17 | 26.82 | 11.36 | 15.46 | 0.00 | 0.00 |
| April | 32.32 | 16.62 | 32.19 | 14.17 | 18.02 | 0.00 | 0.00 |
| May | 43.63 | 11.11 | 38.84 | 15.49 | 23.35 | 0.00 | 0.00 |
| June | 44.63 | 6.32 | 36.05 | 13.06 | 22.99 | 0.00 | 0.00 |
| July | 48.44 | 3.53 | 36.18 | 13.04 | 23.14 | 0.00 | 0.00 |
| August | 54.36 | 4.68 | 40.73 | 18.35 | 22.38 | 0.00 | 0.00 |
| September | 36.37 | 9.12 | 30.47 | 13.71 | 16.76 | 0.00 | 0.00 |
| October | 30.09 | 15.73 | 27.60 | 12.52 | 15.08 | 0.00 | 0.00 |
| November | 13.77 | 22.89 | 17.08 | 6.57 | 10.51 | 0.00 | 0.00 |
| December | 8.93 | 30.10 | 13.35 | 6.30 | 7.05 | 0.00 | 0.00 |
| Annual Sum or Average | 29.98 | 17.35 | 27.85 | 11.65 | 16.20 | 0.00 | 0.00 |
| Minimum of Months | 8.17 | 3.53 | 13.35 | 5.41 | 7.05 | 0.00 | 0.00 |
| Maximum of Months | 54.36 | 33.24 | 40.73 | 18.35 | 23.35 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: G CORRIDOR
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 26.82 | 88.17 | 40.22 | 16.12 | 24.10 | 0.00 | 0.00 |
| February | 46.98 | 86.39 | 61.99 | 28.73 | 33.26 | 0.00 | 0.00 |
| March | 74.40 | 60.24 | 79.86 | 33.82 | 46.04 | 0.00 | 0.00 |
| April | 101.51 | 43.59 | 95.86 | 42.19 | 53.67 | 0.00 | 0.00 |
| May | 135.34 | 29.19 | 115.68 | 46.14 | 69.54 | 0.00 | 0.00 |
| June | 134.63 | 18.60 | 107.37 | 38.90 | 68.47 | 0.00 | 0.00 |
| July | 144.50 | 11.17 | 107.75 | 38.84 | 68.91 | 0.00 | 0.00 |
| August | 161.60 | 15.30 | 121.30 | 54.66 | 66.64 | 0.00 | 0.00 |
| September | 108.50 | 28.17 | 90.73 | 40.83 | 49.91 | 0.00 | 0.00 |
| October | 89.20 | 48.85 | 82.20 | 37.29 | 44.91 | 0.00 | 0.00 |
| November | 42.15 | 66.19 | 50.85 | 19.56 | 31.29 | 0.00 | 0.00 |
| December | 28.45 | 82.05 | 39.75 | 18.76 | 20.99 | 0.00 | 0.00 |
| Annual Sum or Average | 91.48 | 47.94 | 82.93 | 34.69 | 48.24 | 0.00 | 0.00 |
| Minimum of Months | 26.82 | 11.17 | 39.75 | 16.12 | 20.99 | 0.00 | 0.00 |
| Maximum of Months | 161.60 | 88.17 | 121.30 | 54.66 | 69.54 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: M CORRIDOR
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 7.74 | 35.98 | 13.50 | 5.41 | 8.09 | 0.00 | 0.00 |
| February | 13.89 | 35.40 | 20.81 | 9.65 | 11.17 | 0.00 | 0.00 |
| March | 22.80 | 24.99 | 26.82 | 11.36 | 15.46 | 0.00 | 0.00 |
| April | 31.60 | 18.19 | 32.19 | 14.17 | 18.02 | 0.00 | 0.00 |
| May | 42.80 | 12.15 | 38.84 | 15.49 | 23.35 | 0.00 | 0.00 |
| June | 44.81 | 6.49 | 36.05 | 13.06 | 22.99 | 0.00 | 0.00 |
| July | 48.94 | 3.52 | 36.18 | 13.04 | 23.14 | 0.00 | 0.00 |
| August | 54.78 | 4.76 | 40.73 | 18.35 | 22.38 | 0.00 | 0.00 |
| September | 36.14 | 9.69 | 30.47 | 13.71 | 16.76 | 0.00 | 0.00 |
| October | 29.11 | 17.58 | 27.60 | 12.52 | 15.08 | 0.00 | 0.00 |
| November | 12.99 | 25.34 | 17.08 | 6.57 | 10.51 | 0.00 | 0.00 |
| December | 8.53 | 32.78 | 13.35 | 6.30 | 7.05 | 0.00 | 0.00 |
| Annual Sum or Average | 29.62 | 18.81 | 27.85 | 11.65 | 16.20 | 0.00 | 0.00 |
| Minimum of Months | 7.74 | 3.52 | 13.35 | 5.41 | 7.05 | 0.00 | 0.00 |
| Maximum of Months | 54.78 | 35.98 | 40.73 | 18.35 | 23.35 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: G SW APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.639950E+09 | 0.870304E+09 | 0.718960E+09 | 0.434929E+09 | 0.284031E+09 | 0.00 | 0.00 |
| February | 0.811791E+09 | 0.774283E+09 | 0.879755E+09 | 0.540322E+09 | 0.339433E+09 | 0.00 | 0.00 |
| March | 0.100860E+10 | 0.582478E+09 | 0.986806E+09 | 0.511563E+09 | 0.475243E+09 | 0.00 | 0.00 |
| April | 0.955445E+09 | 0.405579E+09 | 0.867822E+09 | 0.365168E+09 | 0.502654E+09 | 0.00 | 0.00 |
| May | 0.104213E+10 | 0.255512E+09 | 0.871071E+09 | 0.251465E+09 | 0.619606E+09 | 0.00 | 0.00 |
| June | 0.113776E+10 | 0.139534E+09 | 0.857399E+09 | 0.243432E+09 | 0.613967E+09 | 0.00 | 0.00 |
| July | 0.126849E+10 | 66697082.21 | 0.875418E+09 | 0.238516E+09 | 0.636902E+09 | 0.00 | 0.00 |
| August | 0.154405E+10 | 0.106225E+09 | 0.106938E+10 | 0.438549E+09 | 0.630830E+09 | 0.00 | 0.00 |
| September | 0.121047E+10 | 0.226180E+09 | 0.939182E+09 | 0.452105E+09 | 0.487077E+09 | 0.00 | 0.00 |
| October | 0.145159E+10 | 0.450950E+09 | 0.122094E+10 | 0.717488E+09 | 0.503454E+09 | 0.00 | 0.00 |
| November | 0.736151E+09 | 0.615892E+09 | 0.754142E+09 | 0.407238E+09 | 0.346904E+09 | 0.00 | 0.00 |
| December | 0.703707E+09 | 0.790594E+09 | 0.752252E+09 | 0.495793E+09 | 0.256459E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.125101E+11 | 0.528423E+10 | 0.107931E+11 | 0.509657E+10 | 0.569656E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.639950E+09 | 66697082.21 | 0.718960E+09 | 0.238516E+09 | 0.256459E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.154405E+10 | 0.870304E+09 | 0.122094E+10 | 0.717488E+09 | 0.636902E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: G NW APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 83204446.36 | 0.925178E+09 | 0.259094E+09 | 61382458.61 | 0.197711E+09 | 0.00 | 0.00 |
| February | 0.137369E+09 | 0.836901E+09 | 0.333370E+09 | 86777461.17 | 0.246593E+09 | 0.00 | 0.00 |
| March | 0.387411E+09 | 0.582699E+09 | 0.534066E+09 | 0.151081E+09 | 0.382985E+09 | 0.00 | 0.00 |
| April | 0.545904E+09 | 0.388904E+09 | 0.584213E+09 | 0.146857E+09 | 0.437357E+09 | 0.00 | 0.00 |
| May | 0.841094E+09 | 0.239666E+09 | 0.746213E+09 | 0.169052E+09 | 0.577161E+09 | 0.00 | 0.00 |
| June | 0.997920E+09 | 0.133413E+09 | 0.777436E+09 | 0.194613E+09 | 0.582823E+09 | 0.00 | 0.00 |
| July | 0.108278E+10 | 64867325.55 | 0.763701E+09 | 0.172207E+09 | 0.591494E+09 | 0.00 | 0.00 |
| August | 0.107618E+10 | 0.101189E+09 | 0.769391E+09 | 0.220415E+09 | 0.548975E+09 | 0.00 | 0.00 |
| September | 0.636054E+09 | 0.221614E+09 | 0.541789E+09 | 0.140763E+09 | 0.401027E+09 | 0.00 | 0.00 |
| October | 0.511736E+09 | 0.432384E+09 | 0.525104E+09 | 0.159534E+09 | 0.365570E+09 | 0.00 | 0.00 |
| November | 0.144360E+09 | 0.617989E+09 | 0.283365E+09 | 43522471.44 | 0.239842E+09 | 0.00 | 0.00 |
| December | 75658757.64 | 0.844564E+09 | 0.233321E+09 | 59633180.38 | 0.173687E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.651967E+10 | 0.538937E+10 | 0.635106E+10 | 0.160584E+10 | 0.474522E+10 | 0.00 | 0.00 |
| Minimum of Months | 75658757.64 | 64867325.55 | 0.233321E+09 | 43522471.44 | 0.173687E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.108278E+10 | 0.925178E+09 | 0.777436E+09 | 0.220415E+09 | 0.591494E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: OFFICE
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.673243E+09 | 0.747385E+09 | 0.720277E+09 | 0.433967E+09 | 0.286310E+09 | 0.00 | 0.00 |
| February | 0.858715E+09 | 0.674639E+09 | 0.891796E+09 | 0.550790E+09 | 0.341006E+09 | 0.00 | 0.00 |
| March | 0.100215E+10 | 0.537068E+09 | 0.960265E+09 | 0.487256E+09 | 0.473009E+09 | 0.00 | 0.00 |
| April | 0.958609E+09 | 0.397437E+09 | 0.873374E+09 | 0.372139E+09 | 0.501235E+09 | 0.00 | 0.00 |
| May | 0.103777E+10 | 0.281358E+09 | 0.891423E+09 | 0.267380E+09 | 0.624042E+09 | 0.00 | 0.00 |
| June | 0.103040E+10 | 0.184679E+09 | 0.809201E+09 | 0.207603E+09 | 0.601598E+09 | 0.00 | 0.00 |
| July | 0.117310E+10 | 0.133056E+09 | 0.856263E+09 | 0.224797E+09 | 0.631466E+09 | 0.00 | 0.00 |
| August | 0.146073E+10 | 0.179617E+09 | 0.105633E+10 | 0.427069E+09 | 0.629263E+09 | 0.00 | 0.00 |
| September | 0.117801E+10 | 0.290639E+09 | 0.946318E+09 | 0.459520E+09 | 0.486798E+09 | 0.00 | 0.00 |
| October | 0.140937E+10 | 0.490931E+09 | 0.120037E+10 | 0.697715E+09 | 0.502658E+09 | 0.00 | 0.00 |
| November | 0.791331E+09 | 0.600538E+09 | 0.788586E+09 | 0.434661E+09 | 0.353925E+09 | 0.00 | 0.00 |
| December | 0.740361E+09 | 0.714300E+09 | 0.763579E+09 | 0.506458E+09 | 0.257122E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.123138E+11 | 0.523165E+10 | 0.107578E+11 | 0.506935E+10 | 0.568843E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.673243E+09 | 0.133056E+09 | 0.720277E+09 | 0.207603E+09 | 0.257122E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.146073E+10 | 0.747385E+09 | 0.120037E+10 | 0.697715E+09 | 0.631466E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: G NE APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 77260986.34 | 0.912662E+09 | 0.260411E+09 | 60419999.06 | 0.199991E+09 | 0.00 | 0.00 |
| February | 0.130484E+09 | 0.806988E+09 | 0.345410E+09 | 97245285.92 | 0.248165E+09 | 0.00 | 0.00 |
| March | 0.355180E+09 | 0.584731E+09 | 0.507525E+09 | 0.126774E+09 | 0.380752E+09 | 0.00 | 0.00 |
| April | 0.545317E+09 | 0.380430E+09 | 0.589765E+09 | 0.153828E+09 | 0.435938E+09 | 0.00 | 0.00 |
| May | 0.863460E+09 | 0.236542E+09 | 0.766565E+09 | 0.184967E+09 | 0.581598E+09 | 0.00 | 0.00 |
| June | 0.932562E+09 | 0.131513E+09 | 0.729238E+09 | 0.158784E+09 | 0.570454E+09 | 0.00 | 0.00 |
| July | 0.105720E+10 | 64255383.63 | 0.744546E+09 | 0.158488E+09 | 0.586057E+09 | 0.00 | 0.00 |
| August | 0.105546E+10 | 98738952.43 | 0.756344E+09 | 0.208935E+09 | 0.547409E+09 | 0.00 | 0.00 |
| September | 0.638295E+09 | 0.215588E+09 | 0.548925E+09 | 0.148178E+09 | 0.400748E+09 | 0.00 | 0.00 |
| October | 0.480813E+09 | 0.424516E+09 | 0.504535E+09 | 0.139761E+09 | 0.364774E+09 | 0.00 | 0.00 |
| November | 0.182949E+09 | 0.605268E+09 | 0.317809E+09 | 70945468.93 | 0.246863E+09 | 0.00 | 0.00 |
| December | 80002228.79 | 0.826888E+09 | 0.244647E+09 | 70298032.80 | 0.174349E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.639898E+10 | 0.528812E+10 | 0.631572E+10 | 0.157862E+10 | 0.473710E+10 | 0.00 | 0.00 |
| Minimum of Months | 77260986.34 | 64255383.63 | 0.244647E+09 | 60419999.06 | 0.174349E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.105720E+10 | 0.912662E+09 | 0.766565E+09 | 0.208935E+09 | 0.586057E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: G N1 APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 7992250.69 | 0.592639E+09 | 0.109680E+09 | 0.00 | 0.109680E+09 | 0.00 | 0.00 |
| February | 15890691.06 | 0.540291E+09 | 0.135567E+09 | 0.00 | 0.135567E+09 | 0.00 | 0.00 |
| March | 90776256.33 | 0.374149E+09 | 0.208206E+09 | 11905.41 | 0.208194E+09 | 0.00 | 0.00 |
| April | 0.178708E+09 | 0.242508E+09 | 0.242084E+09 | 795309.56 | 0.241288E+09 | 0.00 | 0.00 |
| May | 0.341937E+09 | 0.148448E+09 | 0.333011E+09 | 12051811.88 | 0.320959E+09 | 0.00 | 0.00 |
| June | 0.426154E+09 | 80012413.75 | 0.339808E+09 | 17705128.15 | 0.322103E+09 | 0.00 | 0.00 |
| July | 0.490239E+09 | 38295565.22 | 0.340710E+09 | 12916971.32 | 0.327793E+09 | 0.00 | 0.00 |
| August | 0.425840E+09 | 59187032.51 | 0.301730E+09 | 4093092.86 | 0.297637E+09 | 0.00 | 0.00 |
| September | 0.235917E+09 | 0.135496E+09 | 0.219832E+09 | 102291.06 | 0.219730E+09 | 0.00 | 0.00 |
| October | 0.145583E+09 | 0.271143E+09 | 0.196470E+09 | 0.00 | 0.196470E+09 | 0.00 | 0.00 |
| November | 42670823.42 | 0.392172E+09 | 0.133359E+09 | 0.00 | 0.133359E+09 | 0.00 | 0.00 |
| December | 5218187.48 | 0.542049E+09 | 95669840.31 | 0.00 | 95669840.31 | 0.00 | 0.00 |
| Annual Sum or Average | 0.240693E+10 | 0.341639E+10 | 0.265613E+10 | 47676510.25 | 0.260845E+10 | 0.00 | 0.00 |
| Minimum of Months | 5218187.48 | 38295565.22 | 95669840.31 | 0.00 | 95669840.31 | 0.00 | 0.00 |
| Maximum of Months | 0.490239E+09 | 0.592639E+09 | 0.340710E+09 | 17705128.15 | 0.327793E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: G N2 APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 7986893.48 | 0.592647E+09 | 0.109680E+09 | 0.00 | 0.109680E+09 | 0.00 | 0.00 |
| February | 15880404.36 | 0.540299E+09 | 0.135567E+09 | 0.00 | 0.135567E+09 | 0.00 | 0.00 |
| March | 90763790.98 | 0.374079E+09 | 0.208206E+09 | 11905.41 | 0.208194E+09 | 0.00 | 0.00 |
| April | 0.178607E+09 | 0.242505E+09 | 0.242084E+09 | 795309.56 | 0.241288E+09 | 0.00 | 0.00 |
| May | 0.341892E+09 | 0.148364E+09 | 0.333011E+09 | 12051811.88 | 0.320959E+09 | 0.00 | 0.00 |
| June | 0.426154E+09 | 79976023.09 | 0.339808E+09 | 17705128.15 | 0.322103E+09 | 0.00 | 0.00 |
| July | 0.490229E+09 | 38272385.79 | 0.340710E+09 | 12916971.32 | 0.327793E+09 | 0.00 | 0.00 |
| August | 0.425820E+09 | 59158758.32 | 0.301730E+09 | 4093092.86 | 0.297637E+09 | 0.00 | 0.00 |
| September | 0.235880E+09 | 0.135485E+09 | 0.219832E+09 | 102291.06 | 0.219730E+09 | 0.00 | 0.00 |
| October | 0.145548E+09 | 0.271049E+09 | 0.196470E+09 | 0.00 | 0.196470E+09 | 0.00 | 0.00 |
| November | 42587595.55 | 0.392354E+09 | 0.133359E+09 | 0.00 | 0.133359E+09 | 0.00 | 0.00 |
| December | 5211291.56 | 0.542070E+09 | 95669840.31 | 0.00 | 95669840.31 | 0.00 | 0.00 |
| Annual Sum or Average | 0.240656E+10 | 0.341626E+10 | 0.265613E+10 | 47676510.25 | 0.260845E+10 | 0.00 | 0.00 |
| Minimum of Months | 5211291.56 | 38272385.79 | 95669840.31 | 0.00 | 95669840.31 | 0.00 | 0.00 |
| Maximum of Months | 0.490229E+09 | 0.592647E+09 | 0.340710E+09 | 17705128.15 | 0.327793E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: G S1 APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.563742E+09 | 0.530522E+09 | 0.569546E+09 | 0.373547E+09 | 0.195999E+09 | 0.00 | 0.00 |
| February | 0.692651E+09 | 0.472348E+09 | 0.681952E+09 | 0.453545E+09 | 0.228408E+09 | 0.00 | 0.00 |
| March | 0.713017E+09 | 0.366459E+09 | 0.660946E+09 | 0.360494E+09 | 0.300451E+09 | 0.00 | 0.00 |
| April | 0.594844E+09 | 0.257524E+09 | 0.525692E+09 | 0.219107E+09 | 0.306586E+09 | 0.00 | 0.00 |
| May | 0.548287E+09 | 0.164967E+09 | 0.457869E+09 | 94465436.52 | 0.363404E+09 | 0.00 | 0.00 |
| June | 0.567232E+09 | 85933878.90 | 0.419772E+09 | 66524244.16 | 0.353248E+09 | 0.00 | 0.00 |
| July | 0.676958E+09 | 39546056.38 | 0.452427E+09 | 79225487.12 | 0.373202E+09 | 0.00 | 0.00 |
| August | 0.896548E+09 | 62970020.53 | 0.601719E+09 | 0.222227E+09 | 0.379492E+09 | 0.00 | 0.00 |
| September | 0.814682E+09 | 0.137372E+09 | 0.617224E+09 | 0.311444E+09 | 0.305780E+09 | 0.00 | 0.00 |
| October | 0.109368E+10 | 0.274589E+09 | 0.892308E+09 | 0.557954E+09 | 0.334354E+09 | 0.00 | 0.00 |
| November | 0.640737E+09 | 0.379670E+09 | 0.604136E+09 | 0.363715E+09 | 0.240421E+09 | 0.00 | 0.00 |
| December | 0.634089E+09 | 0.480751E+09 | 0.614602E+09 | 0.436160E+09 | 0.178442E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.843646E+10 | 0.325265E+10 | 0.709819E+10 | 0.353841E+10 | 0.355979E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.548287E+09 | 39546056.38 | 0.419772E+09 | 66524244.16 | 0.178442E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.109368E+10 | 0.530522E+09 | 0.892308E+09 | 0.557954E+09 | 0.379492E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: G S2 APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.564744E+09 | 0.527225E+09 | 0.569546E+09 | 0.373547E+09 | 0.195999E+09 | 0.00 | 0.00 |
| February | 0.693685E+09 | 0.469769E+09 | 0.681952E+09 | 0.453545E+09 | 0.228408E+09 | 0.00 | 0.00 |
| March | 0.713829E+09 | 0.364668E+09 | 0.660946E+09 | 0.360494E+09 | 0.300451E+09 | 0.00 | 0.00 |
| April | 0.594617E+09 | 0.257647E+09 | 0.525692E+09 | 0.219107E+09 | 0.306586E+09 | 0.00 | 0.00 |
| May | 0.546384E+09 | 0.166756E+09 | 0.457869E+09 | 94465436.52 | 0.363404E+09 | 0.00 | 0.00 |
| June | 0.565862E+09 | 87046801.04 | 0.419772E+09 | 66524244.16 | 0.353248E+09 | 0.00 | 0.00 |
| July | 0.674904E+09 | 41025054.73 | 0.452427E+09 | 79225487.12 | 0.373202E+09 | 0.00 | 0.00 |
| August | 0.894614E+09 | 64557302.76 | 0.601719E+09 | 0.222227E+09 | 0.379492E+09 | 0.00 | 0.00 |
| September | 0.813483E+09 | 0.138880E+09 | 0.617224E+09 | 0.311444E+09 | 0.305780E+09 | 0.00 | 0.00 |
| October | 0.109298E+10 | 0.275627E+09 | 0.892308E+09 | 0.557954E+09 | 0.334354E+09 | 0.00 | 0.00 |
| November | 0.640612E+09 | 0.379654E+09 | 0.604136E+09 | 0.363715E+09 | 0.240421E+09 | 0.00 | 0.00 |
| December | 0.634810E+09 | 0.478524E+09 | 0.614602E+09 | 0.436160E+09 | 0.178442E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.843053E+10 | 0.325138E+10 | 0.709819E+10 | 0.353841E+10 | 0.355979E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.546384E+09 | 41025054.73 | 0.419772E+09 | 66524244.16 | 0.178442E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.109298E+10 | 0.527225E+09 | 0.892308E+09 | 0.557954E+09 | 0.379492E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: M SW APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.626267E+09 | 0.901140E+09 | 0.718960E+09 | 0.434929E+09 | 0.284031E+09 | 0.00 | 0.00 |
| February | 0.792494E+09 | 0.806024E+09 | 0.879755E+09 | 0.540322E+09 | 0.339433E+09 | 0.00 | 0.00 |
| March | 0.978617E+09 | 0.625126E+09 | 0.986806E+09 | 0.511563E+09 | 0.475243E+09 | 0.00 | 0.00 |
| April | 0.915697E+09 | 0.456745E+09 | 0.867822E+09 | 0.365168E+09 | 0.502654E+09 | 0.00 | 0.00 |
| May | 0.991595E+09 | 0.303995E+09 | 0.871071E+09 | 0.251465E+09 | 0.619606E+09 | 0.00 | 0.00 |
| June | 0.112459E+10 | 0.146521E+09 | 0.857399E+09 | 0.243432E+09 | 0.613967E+09 | 0.00 | 0.00 |
| July | 0.126112E+10 | 68673055.49 | 0.875418E+09 | 0.238516E+09 | 0.636902E+09 | 0.00 | 0.00 |
| August | 0.154035E+10 | 0.105042E+09 | 0.106938E+10 | 0.438549E+09 | 0.630830E+09 | 0.00 | 0.00 |
| September | 0.120664E+10 | 0.225654E+09 | 0.939182E+09 | 0.452105E+09 | 0.487077E+09 | 0.00 | 0.00 |
| October | 0.144648E+10 | 0.448377E+09 | 0.122094E+10 | 0.717488E+09 | 0.503454E+09 | 0.00 | 0.00 |
| November | 0.729302E+09 | 0.623300E+09 | 0.754142E+09 | 0.407238E+09 | 0.346904E+09 | 0.00 | 0.00 |
| December | 0.691806E+09 | 0.812435E+09 | 0.752252E+09 | 0.495793E+09 | 0.256459E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.123050E+11 | 0.552303E+10 | 0.107931E+11 | 0.509657E+10 | 0.569656E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.626267E+09 | 68673055.49 | 0.718960E+09 | 0.238516E+09 | 0.256459E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.154035E+10 | 0.901140E+09 | 0.122094E+10 | 0.717488E+09 | 0.636902E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: M NW APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 77672472.91 | 0.960847E+09 | 0.259094E+09 | 61382458.61 | 0.197711E+09 | 0.00 | 0.00 |
| February | 0.128836E+09 | 0.874072E+09 | 0.333370E+09 | 86777461.17 | 0.246593E+09 | 0.00 | 0.00 |
| March | 0.366655E+09 | 0.621388E+09 | 0.534066E+09 | 0.151081E+09 | 0.382985E+09 | 0.00 | 0.00 |
| April | 0.508076E+09 | 0.439872E+09 | 0.584213E+09 | 0.146857E+09 | 0.437357E+09 | 0.00 | 0.00 |
| May | 0.782289E+09 | 0.291873E+09 | 0.746213E+09 | 0.169052E+09 | 0.577161E+09 | 0.00 | 0.00 |
| June | 0.984707E+09 | 0.140501E+09 | 0.777436E+09 | 0.194613E+09 | 0.582823E+09 | 0.00 | 0.00 |
| July | 0.107589E+10 | 67262574.74 | 0.763701E+09 | 0.172207E+09 | 0.591494E+09 | 0.00 | 0.00 |
| August | 0.107336E+10 | 0.101169E+09 | 0.769391E+09 | 0.220415E+09 | 0.548975E+09 | 0.00 | 0.00 |
| September | 0.633155E+09 | 0.223441E+09 | 0.541789E+09 | 0.140763E+09 | 0.401027E+09 | 0.00 | 0.00 |
| October | 0.509941E+09 | 0.432523E+09 | 0.525104E+09 | 0.159534E+09 | 0.365570E+09 | 0.00 | 0.00 |
| November | 0.140275E+09 | 0.631086E+09 | 0.283365E+09 | 43522471.44 | 0.239842E+09 | 0.00 | 0.00 |
| December | 71606673.88 | 0.870750E+09 | 0.233321E+09 | 59633180.38 | 0.173687E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.635246E+10 | 0.565478E+10 | 0.635106E+10 | 0.160584E+10 | 0.474522E+10 | 0.00 | 0.00 |
| Minimum of Months | 71606673.88 | 67262574.74 | 0.233321E+09 | 43522471.44 | 0.173687E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.107589E+10 | 0.960847E+09 | 0.777436E+09 | 0.220415E+09 | 0.591494E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: M SE APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.629902E+09 | 0.897403E+09 | 0.720277E+09 | 0.433967E+09 | 0.286310E+09 | 0.00 | 0.00 |
| February | 0.810006E+09 | 0.799398E+09 | 0.891796E+09 | 0.550790E+09 | 0.341006E+09 | 0.00 | 0.00 |
| March | 0.950169E+09 | 0.630251E+09 | 0.960265E+09 | 0.487256E+09 | 0.473009E+09 | 0.00 | 0.00 |
| April | 0.915252E+09 | 0.449324E+09 | 0.873374E+09 | 0.372139E+09 | 0.501235E+09 | 0.00 | 0.00 |
| May | 0.101099E+10 | 0.298849E+09 | 0.891423E+09 | 0.267380E+09 | 0.624042E+09 | 0.00 | 0.00 |
| June | 0.105802E+10 | 0.143025E+09 | 0.809201E+09 | 0.207603E+09 | 0.601598E+09 | 0.00 | 0.00 |
| July | 0.123494E+10 | 67198443.18 | 0.856263E+09 | 0.224797E+09 | 0.631466E+09 | 0.00 | 0.00 |
| August | 0.151843E+10 | 0.101379E+09 | 0.105633E+10 | 0.427069E+09 | 0.629263E+09 | 0.00 | 0.00 |
| September | 0.121063E+10 | 0.221076E+09 | 0.946318E+09 | 0.459520E+09 | 0.486798E+09 | 0.00 | 0.00 |
| October | 0.141809E+10 | 0.443156E+09 | 0.120037E+10 | 0.697715E+09 | 0.502658E+09 | 0.00 | 0.00 |
| November | 0.777123E+09 | 0.619677E+09 | 0.788586E+09 | 0.434661E+09 | 0.353925E+09 | 0.00 | 0.00 |
| December | 0.708457E+09 | 0.806564E+09 | 0.763579E+09 | 0.506458E+09 | 0.257122E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.122420E+11 | 0.547730E+10 | 0.107578E+11 | 0.506935E+10 | 0.568843E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.629902E+09 | 67198443.18 | 0.720277E+09 | 0.207603E+09 | 0.257122E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.151843E+10 | 0.897403E+09 | 0.120037E+10 | 0.697715E+09 | 0.631466E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: M NE APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 71419143.44 | 0.947396E+09 | 0.260411E+09 | 60419999.06 | 0.199991E+09 | 0.00 | 0.00 |
| February | 0.120980E+09 | 0.842467E+09 | 0.345410E+09 | 97245285.92 | 0.248165E+09 | 0.00 | 0.00 |
| March | 0.335337E+09 | 0.623572E+09 | 0.507525E+09 | 0.126774E+09 | 0.380752E+09 | 0.00 | 0.00 |
| April | 0.505642E+09 | 0.430989E+09 | 0.589765E+09 | 0.153828E+09 | 0.435938E+09 | 0.00 | 0.00 |
| May | 0.803399E+09 | 0.288767E+09 | 0.766565E+09 | 0.184967E+09 | 0.581598E+09 | 0.00 | 0.00 |
| June | 0.919719E+09 | 0.138658E+09 | 0.729238E+09 | 0.158784E+09 | 0.570454E+09 | 0.00 | 0.00 |
| July | 0.105054E+10 | 66690002.88 | 0.744546E+09 | 0.158488E+09 | 0.586057E+09 | 0.00 | 0.00 |
| August | 0.105257E+10 | 98670002.36 | 0.756344E+09 | 0.208935E+09 | 0.547409E+09 | 0.00 | 0.00 |
| September | 0.635160E+09 | 0.217285E+09 | 0.548925E+09 | 0.148178E+09 | 0.400748E+09 | 0.00 | 0.00 |
| October | 0.478817E+09 | 0.424393E+09 | 0.504535E+09 | 0.139761E+09 | 0.364774E+09 | 0.00 | 0.00 |
| November | 0.178431E+09 | 0.617240E+09 | 0.317809E+09 | 70945468.93 | 0.246863E+09 | 0.00 | 0.00 |
| December | 75611224.27 | 0.852071E+09 | 0.244647E+09 | 70298032.80 | 0.174349E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.622762E+10 | 0.554820E+10 | 0.631572E+10 | 0.157862E+10 | 0.473710E+10 | 0.00 | 0.00 |
| Minimum of Months | 71419143.44 | 66690002.88 | 0.244647E+09 | 60419999.06 | 0.174349E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.105257E+10 | 0.947396E+09 | 0.766565E+09 | 0.208935E+09 | 0.586057E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: M N1 APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 6515477.74 | 0.615070E+09 | 0.109680E+09 | 0.00 | 0.109680E+09 | 0.00 | 0.00 |
| February | 13539975.35 | 0.563510E+09 | 0.135567E+09 | 0.00 | 0.135567E+09 | 0.00 | 0.00 |
| March | 82053866.97 | 0.397901E+09 | 0.208206E+09 | 11905.41 | 0.208194E+09 | 0.00 | 0.00 |
| April | 0.158710E+09 | 0.274381E+09 | 0.242084E+09 | 795309.56 | 0.241288E+09 | 0.00 | 0.00 |
| May | 0.310529E+09 | 0.177324E+09 | 0.333011E+09 | 12051811.88 | 0.320959E+09 | 0.00 | 0.00 |
| June | 0.420889E+09 | 82992773.25 | 0.339808E+09 | 17705128.15 | 0.322103E+09 | 0.00 | 0.00 |
| July | 0.487892E+09 | 39181149.12 | 0.340710E+09 | 12916971.32 | 0.327793E+09 | 0.00 | 0.00 |
| August | 0.425404E+09 | 59069309.46 | 0.301730E+09 | 4093092.86 | 0.297637E+09 | 0.00 | 0.00 |
| September | 0.234935E+09 | 0.136587E+09 | 0.219832E+09 | 102291.06 | 0.219730E+09 | 0.00 | 0.00 |
| October | 0.144425E+09 | 0.273007E+09 | 0.196470E+09 | 0.00 | 0.196470E+09 | 0.00 | 0.00 |
| November | 40610920.93 | 0.402421E+09 | 0.133359E+09 | 0.00 | 0.133359E+09 | 0.00 | 0.00 |
| December | 4361614.15 | 0.559798E+09 | 95669840.31 | 0.00 | 95669840.31 | 0.00 | 0.00 |
| Annual Sum or Average | 0.232986E+10 | 0.358124E+10 | 0.265613E+10 | 47676510.25 | 0.260845E+10 | 0.00 | 0.00 |
| Minimum of Months | 4361614.15 | 39181149.12 | 95669840.31 | 0.00 | 95669840.31 | 0.00 | 0.00 |
| Maximum of Months | 0.487892E+09 | 0.615070E+09 | 0.340710E+09 | 17705128.15 | 0.327793E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: M N2 APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 6507792.79 | 0.615076E+09 | 0.109680E+09 | 0.00 | 0.109680E+09 | 0.00 | 0.00 |
| February | 13525636.47 | 0.563526E+09 | 0.135567E+09 | 0.00 | 0.135567E+09 | 0.00 | 0.00 |
| March | 82026711.15 | 0.397774E+09 | 0.208206E+09 | 11905.41 | 0.208194E+09 | 0.00 | 0.00 |
| April | 0.158530E+09 | 0.274418E+09 | 0.242084E+09 | 795309.56 | 0.241288E+09 | 0.00 | 0.00 |
| May | 0.310455E+09 | 0.177302E+09 | 0.333011E+09 | 12051811.88 | 0.320959E+09 | 0.00 | 0.00 |
| June | 0.420883E+09 | 82959210.17 | 0.339808E+09 | 17705128.15 | 0.322103E+09 | 0.00 | 0.00 |
| July | 0.487876E+09 | 39158302.79 | 0.340710E+09 | 12916971.32 | 0.327793E+09 | 0.00 | 0.00 |
| August | 0.425379E+09 | 59039210.23 | 0.301730E+09 | 4093092.86 | 0.297637E+09 | 0.00 | 0.00 |
| September | 0.234896E+09 | 0.136568E+09 | 0.219832E+09 | 102291.06 | 0.219730E+09 | 0.00 | 0.00 |
| October | 0.144359E+09 | 0.272916E+09 | 0.196470E+09 | 0.00 | 0.196470E+09 | 0.00 | 0.00 |
| November | 40523689.63 | 0.402593E+09 | 0.133359E+09 | 0.00 | 0.133359E+09 | 0.00 | 0.00 |
| December | 4353873.49 | 0.559826E+09 | 95669840.31 | 0.00 | 95669840.31 | 0.00 | 0.00 |
| Annual Sum or Average | 0.232932E+10 | 0.358115E+10 | 0.265613E+10 | 47676510.25 | 0.260845E+10 | 0.00 | 0.00 |
| Minimum of Months | 4353873.49 | 39158302.79 | 95669840.31 | 0.00 | 95669840.31 | 0.00 | 0.00 |
| Maximum of Months | 0.487876E+09 | 0.615076E+09 | 0.340710E+09 | 17705128.15 | 0.327793E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: M S1 APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.554742E+09 | 0.548833E+09 | 0.569546E+09 | 0.373547E+09 | 0.195999E+09 | 0.00 | 0.00 |
| February | 0.681111E+09 | 0.490372E+09 | 0.681952E+09 | 0.453545E+09 | 0.228408E+09 | 0.00 | 0.00 |
| March | 0.696080E+09 | 0.395163E+09 | 0.660946E+09 | 0.360494E+09 | 0.300451E+09 | 0.00 | 0.00 |
| April | 0.573311E+09 | 0.289529E+09 | 0.525692E+09 | 0.219107E+09 | 0.306586E+09 | 0.00 | 0.00 |
| May | 0.524394E+09 | 0.190999E+09 | 0.457869E+09 | 94465436.52 | 0.363404E+09 | 0.00 | 0.00 |
| June | 0.561788E+09 | 88904022.00 | 0.419772E+09 | 66524244.16 | 0.353248E+09 | 0.00 | 0.00 |
| July | 0.674093E+09 | 40058469.10 | 0.452427E+09 | 79225487.12 | 0.373202E+09 | 0.00 | 0.00 |
| August | 0.895001E+09 | 62024411.97 | 0.601719E+09 | 0.222227E+09 | 0.379492E+09 | 0.00 | 0.00 |
| September | 0.812458E+09 | 0.136918E+09 | 0.617224E+09 | 0.311444E+09 | 0.305780E+09 | 0.00 | 0.00 |
| October | 0.108980E+10 | 0.274162E+09 | 0.892308E+09 | 0.557954E+09 | 0.334354E+09 | 0.00 | 0.00 |
| November | 0.635661E+09 | 0.385467E+09 | 0.604136E+09 | 0.363715E+09 | 0.240421E+09 | 0.00 | 0.00 |
| December | 0.625605E+09 | 0.495559E+09 | 0.614602E+09 | 0.436160E+09 | 0.178442E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.832404E+10 | 0.339799E+10 | 0.709819E+10 | 0.353841E+10 | 0.355979E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.524394E+09 | 40058469.10 | 0.419772E+09 | 66524244.16 | 0.178442E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.108980E+10 | 0.548833E+09 | 0.892308E+09 | 0.557954E+09 | 0.379492E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: M S2 APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.554707E+09 | 0.548819E+09 | 0.569546E+09 | 0.373547E+09 | 0.195999E+09 | 0.00 | 0.00 |
| February | 0.681050E+09 | 0.490352E+09 | 0.681952E+09 | 0.453545E+09 | 0.228408E+09 | 0.00 | 0.00 |
| March | 0.696037E+09 | 0.394997E+09 | 0.660946E+09 | 0.360494E+09 | 0.300451E+09 | 0.00 | 0.00 |
| April | 0.573181E+09 | 0.289522E+09 | 0.525692E+09 | 0.219107E+09 | 0.306586E+09 | 0.00 | 0.00 |
| May | 0.524338E+09 | 0.190959E+09 | 0.457869E+09 | 94465436.52 | 0.363404E+09 | 0.00 | 0.00 |
| June | 0.561780E+09 | 88867116.16 | 0.419772E+09 | 66524244.16 | 0.353248E+09 | 0.00 | 0.00 |
| July | 0.674078E+09 | 40034656.95 | 0.452427E+09 | 79225487.12 | 0.373202E+09 | 0.00 | 0.00 |
| August | 0.894978E+09 | 61993568.35 | 0.601719E+09 | 0.222227E+09 | 0.379492E+09 | 0.00 | 0.00 |
| September | 0.812434E+09 | 0.136896E+09 | 0.617224E+09 | 0.311444E+09 | 0.305780E+09 | 0.00 | 0.00 |
| October | 0.108977E+10 | 0.274122E+09 | 0.892308E+09 | 0.557954E+09 | 0.334354E+09 | 0.00 | 0.00 |
| November | 0.635551E+09 | 0.385611E+09 | 0.604136E+09 | 0.363715E+09 | 0.240421E+09 | 0.00 | 0.00 |
| December | 0.625543E+09 | 0.495584E+09 | 0.614602E+09 | 0.436160E+09 | 0.178442E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.832344E+10 | 0.339776E+10 | 0.709819E+10 | 0.353841E+10 | 0.355979E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.524338E+09 | 40034656.95 | 0.419772E+09 | 66524244.16 | 0.178442E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.108977E+10 | 0.548819E+09 | 0.892308E+09 | 0.557954E+09 | 0.379492E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: T SW APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.626006E+09 | 0.868105E+09 | 0.718960E+09 | 0.434929E+09 | 0.284031E+09 | 0.00 | 0.00 |
| February | 0.790236E+09 | 0.775571E+09 | 0.879755E+09 | 0.540322E+09 | 0.339433E+09 | 0.00 | 0.00 |
| March | 0.971930E+09 | 0.594999E+09 | 0.986806E+09 | 0.511563E+09 | 0.475243E+09 | 0.00 | 0.00 |
| April | 0.915524E+09 | 0.421244E+09 | 0.867822E+09 | 0.365168E+09 | 0.502654E+09 | 0.00 | 0.00 |
| May | 0.997433E+09 | 0.271659E+09 | 0.871071E+09 | 0.251465E+09 | 0.619606E+09 | 0.00 | 0.00 |
| June | 0.111016E+10 | 0.140225E+09 | 0.857399E+09 | 0.243432E+09 | 0.613967E+09 | 0.00 | 0.00 |
| July | 0.124157E+10 | 66773191.08 | 0.875418E+09 | 0.238516E+09 | 0.636902E+09 | 0.00 | 0.00 |
| August | 0.152049E+10 | 0.101015E+09 | 0.106938E+10 | 0.438549E+09 | 0.630830E+09 | 0.00 | 0.00 |
| September | 0.119927E+10 | 0.209598E+09 | 0.939182E+09 | 0.452105E+09 | 0.487077E+09 | 0.00 | 0.00 |
| October | 0.145184E+10 | 0.401961E+09 | 0.122094E+10 | 0.717488E+09 | 0.503454E+09 | 0.00 | 0.00 |
| November | 0.736317E+09 | 0.581017E+09 | 0.754142E+09 | 0.407238E+09 | 0.346904E+09 | 0.00 | 0.00 |
| December | 0.691862E+09 | 0.778204E+09 | 0.752252E+09 | 0.495793E+09 | 0.256459E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.122526E+11 | 0.521037E+10 | 0.107931E+11 | 0.509657E+10 | 0.569656E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.626006E+09 | 66773191.08 | 0.718960E+09 | 0.238516E+09 | 0.256459E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.152049E+10 | 0.868105E+09 | 0.122094E+10 | 0.717488E+09 | 0.636902E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: T NW APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 79328828.87 | 0.927960E+09 | 0.259094E+09 | 61382458.61 | 0.197711E+09 | 0.00 | 0.00 |
| February | 0.130005E+09 | 0.844774E+09 | 0.333370E+09 | 86777461.17 | 0.246593E+09 | 0.00 | 0.00 |
| March | 0.364925E+09 | 0.597085E+09 | 0.534066E+09 | 0.151081E+09 | 0.382985E+09 | 0.00 | 0.00 |
| April | 0.509329E+09 | 0.411111E+09 | 0.584213E+09 | 0.146857E+09 | 0.437357E+09 | 0.00 | 0.00 |
| May | 0.792101E+09 | 0.262355E+09 | 0.746213E+09 | 0.169052E+09 | 0.577161E+09 | 0.00 | 0.00 |
| June | 0.972177E+09 | 0.135257E+09 | 0.777436E+09 | 0.194613E+09 | 0.582823E+09 | 0.00 | 0.00 |
| July | 0.105823E+10 | 65989725.36 | 0.763701E+09 | 0.172207E+09 | 0.591494E+09 | 0.00 | 0.00 |
| August | 0.105735E+10 | 97997052.49 | 0.769391E+09 | 0.220415E+09 | 0.548975E+09 | 0.00 | 0.00 |
| September | 0.631579E+09 | 0.205600E+09 | 0.541789E+09 | 0.140763E+09 | 0.401027E+09 | 0.00 | 0.00 |
| October | 0.522597E+09 | 0.388422E+09 | 0.525104E+09 | 0.159534E+09 | 0.365570E+09 | 0.00 | 0.00 |
| November | 0.144956E+09 | 0.598787E+09 | 0.283365E+09 | 43522471.44 | 0.239842E+09 | 0.00 | 0.00 |
| December | 73238129.42 | 0.837917E+09 | 0.233321E+09 | 59633180.38 | 0.173687E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.633582E+10 | 0.537326E+10 | 0.635106E+10 | 0.160584E+10 | 0.474522E+10 | 0.00 | 0.00 |
| Minimum of Months | 73238129.42 | 65989725.36 | 0.233321E+09 | 43522471.44 | 0.173687E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.105823E+10 | 0.927960E+09 | 0.777436E+09 | 0.220415E+09 | 0.591494E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: T SE APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.629912E+09 | 0.864229E+09 | 0.720277E+09 | 0.433967E+09 | 0.286310E+09 | 0.00 | 0.00 |
| February | 0.808380E+09 | 0.768989E+09 | 0.891796E+09 | 0.550790E+09 | 0.341006E+09 | 0.00 | 0.00 |
| March | 0.943521E+09 | 0.600638E+09 | 0.960265E+09 | 0.487256E+09 | 0.473009E+09 | 0.00 | 0.00 |
| April | 0.915935E+09 | 0.414930E+09 | 0.873374E+09 | 0.372139E+09 | 0.501235E+09 | 0.00 | 0.00 |
| May | 0.101664E+10 | 0.268149E+09 | 0.891423E+09 | 0.267380E+09 | 0.624042E+09 | 0.00 | 0.00 |
| June | 0.104401E+10 | 0.137144E+09 | 0.809201E+09 | 0.207603E+09 | 0.601598E+09 | 0.00 | 0.00 |
| July | 0.121562E+10 | 65203488.11 | 0.856263E+09 | 0.224797E+09 | 0.631466E+09 | 0.00 | 0.00 |
| August | 0.149843E+10 | 97279402.93 | 0.105633E+10 | 0.427069E+09 | 0.629263E+09 | 0.00 | 0.00 |
| September | 0.120311E+10 | 0.205686E+09 | 0.946318E+09 | 0.459520E+09 | 0.486798E+09 | 0.00 | 0.00 |
| October | 0.142210E+10 | 0.396340E+09 | 0.120037E+10 | 0.697715E+09 | 0.502658E+09 | 0.00 | 0.00 |
| November | 0.783972E+09 | 0.576669E+09 | 0.788586E+09 | 0.434661E+09 | 0.353925E+09 | 0.00 | 0.00 |
| December | 0.708560E+09 | 0.772033E+09 | 0.763579E+09 | 0.506458E+09 | 0.257122E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.121902E+11 | 0.516729E+10 | 0.107578E+11 | 0.506935E+10 | 0.568843E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.629912E+09 | 65203488.11 | 0.720277E+09 | 0.207603E+09 | 0.257122E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.149843E+10 | 0.864229E+09 | 0.120037E+10 | 0.697715E+09 | 0.631466E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: T NE APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 74194138.78 | 0.915304E+09 | 0.260411E+09 | 60419999.06 | 0.199991E+09 | 0.00 | 0.00 |
| February | 0.124121E+09 | 0.814624E+09 | 0.345410E+09 | 97245285.92 | 0.248165E+09 | 0.00 | 0.00 |
| March | 0.334671E+09 | 0.600033E+09 | 0.507525E+09 | 0.126774E+09 | 0.380752E+09 | 0.00 | 0.00 |
| April | 0.507748E+09 | 0.402731E+09 | 0.589765E+09 | 0.153828E+09 | 0.435938E+09 | 0.00 | 0.00 |
| May | 0.811174E+09 | 0.259251E+09 | 0.766565E+09 | 0.184967E+09 | 0.581598E+09 | 0.00 | 0.00 |
| June | 0.906950E+09 | 0.133132E+09 | 0.729238E+09 | 0.158784E+09 | 0.570454E+09 | 0.00 | 0.00 |
| July | 0.103287E+10 | 65117384.56 | 0.744546E+09 | 0.158488E+09 | 0.586057E+09 | 0.00 | 0.00 |
| August | 0.103611E+10 | 95156726.06 | 0.756344E+09 | 0.208935E+09 | 0.547409E+09 | 0.00 | 0.00 |
| September | 0.633350E+09 | 0.200638E+09 | 0.548925E+09 | 0.148178E+09 | 0.400748E+09 | 0.00 | 0.00 |
| October | 0.491919E+09 | 0.379997E+09 | 0.504535E+09 | 0.139761E+09 | 0.364774E+09 | 0.00 | 0.00 |
| November | 0.184672E+09 | 0.585087E+09 | 0.317809E+09 | 70945468.93 | 0.246863E+09 | 0.00 | 0.00 |
| December | 78609524.34 | 0.820310E+09 | 0.244647E+09 | 70298032.80 | 0.174349E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.621639E+10 | 0.527138E+10 | 0.631572E+10 | 0.157862E+10 | 0.473710E+10 | 0.00 | 0.00 |
| Minimum of Months | 74194138.78 | 65117384.56 | 0.244647E+09 | 60419999.06 | 0.174349E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.103611E+10 | 0.915304E+09 | 0.766565E+09 | 0.208935E+09 | 0.586057E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: T N1 APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 7276292.19 | 0.595140E+09 | 0.109680E+09 | 0.00 | 0.109680E+09 | 0.00 | 0.00 |
| February | 14251566.82 | 0.546060E+09 | 0.135567E+09 | 0.00 | 0.135567E+09 | 0.00 | 0.00 |
| March | 82458792.92 | 0.383747E+09 | 0.208206E+09 | 11905.41 | 0.208194E+09 | 0.00 | 0.00 |
| April | 0.161471E+09 | 0.256668E+09 | 0.242084E+09 | 795309.56 | 0.241288E+09 | 0.00 | 0.00 |
| May | 0.316917E+09 | 0.162110E+09 | 0.333011E+09 | 12051811.88 | 0.320959E+09 | 0.00 | 0.00 |
| June | 0.414343E+09 | 81240452.95 | 0.339808E+09 | 17705128.15 | 0.322103E+09 | 0.00 | 0.00 |
| July | 0.478832E+09 | 39144098.64 | 0.340710E+09 | 12916971.32 | 0.327793E+09 | 0.00 | 0.00 |
| August | 0.417346E+09 | 58053422.91 | 0.301730E+09 | 4093092.86 | 0.297637E+09 | 0.00 | 0.00 |
| September | 0.234221E+09 | 0.128483E+09 | 0.219832E+09 | 102291.06 | 0.219730E+09 | 0.00 | 0.00 |
| October | 0.154043E+09 | 0.243747E+09 | 0.196470E+09 | 0.00 | 0.196470E+09 | 0.00 | 0.00 |
| November | 44558450.46 | 0.378802E+09 | 0.133359E+09 | 0.00 | 0.133359E+09 | 0.00 | 0.00 |
| December | 4928559.29 | 0.539100E+09 | 95669840.31 | 0.00 | 95669840.31 | 0.00 | 0.00 |
| Annual Sum or Average | 0.233065E+10 | 0.341230E+10 | 0.265613E+10 | 47676510.25 | 0.260845E+10 | 0.00 | 0.00 |
| Minimum of Months | 4928559.29 | 39144098.64 | 95669840.31 | 0.00 | 95669840.31 | 0.00 | 0.00 |
| Maximum of Months | 0.478832E+09 | 0.595140E+09 | 0.340710E+09 | 17705128.15 | 0.327793E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: T N2 APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 7256893.91 | 0.595132E+09 | 0.109680E+09 | 0.00 | 0.109680E+09 | 0.00 | 0.00 |
| February | 14217057.86 | 0.546050E+09 | 0.135567E+09 | 0.00 | 0.135567E+09 | 0.00 | 0.00 |
| March | 82309951.16 | 0.383521E+09 | 0.208206E+09 | 11905.41 | 0.208194E+09 | 0.00 | 0.00 |
| April | 0.161112E+09 | 0.256544E+09 | 0.242084E+09 | 795309.56 | 0.241288E+09 | 0.00 | 0.00 |
| May | 0.316635E+09 | 0.161957E+09 | 0.333011E+09 | 12051811.88 | 0.320959E+09 | 0.00 | 0.00 |
| June | 0.414290E+09 | 81162723.52 | 0.339808E+09 | 17705128.15 | 0.322103E+09 | 0.00 | 0.00 |
| July | 0.478792E+09 | 39092754.74 | 0.340710E+09 | 12916971.32 | 0.327793E+09 | 0.00 | 0.00 |
| August | 0.417281E+09 | 57974319.24 | 0.301730E+09 | 4093092.86 | 0.297637E+09 | 0.00 | 0.00 |
| September | 0.234044E+09 | 0.128430E+09 | 0.219832E+09 | 102291.06 | 0.219730E+09 | 0.00 | 0.00 |
| October | 0.153806E+09 | 0.243398E+09 | 0.196470E+09 | 0.00 | 0.196470E+09 | 0.00 | 0.00 |
| November | 44459699.10 | 0.378802E+09 | 0.133359E+09 | 0.00 | 0.133359E+09 | 0.00 | 0.00 |
| December | 4908359.67 | 0.539110E+09 | 95669840.31 | 0.00 | 95669840.31 | 0.00 | 0.00 |
| Annual Sum or Average | 0.232911E+10 | 0.341117E+10 | 0.265613E+10 | 47676510.25 | 0.260845E+10 | 0.00 | 0.00 |
| Minimum of Months | 4908359.67 | 39092754.74 | 95669840.31 | 0.00 | 95669840.31 | 0.00 | 0.00 |
| Maximum of Months | 0.478792E+09 | 0.595132E+09 | 0.340710E+09 | 17705128.15 | 0.327793E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: T S1 APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.555075E+09 | 0.528731E+09 | 0.569546E+09 | 0.373547E+09 | 0.195999E+09 | 0.00 | 0.00 |
| February | 0.680442E+09 | 0.472161E+09 | 0.681952E+09 | 0.453545E+09 | 0.228408E+09 | 0.00 | 0.00 |
| March | 0.693986E+09 | 0.374688E+09 | 0.660946E+09 | 0.360494E+09 | 0.300451E+09 | 0.00 | 0.00 |
| April | 0.575180E+09 | 0.266979E+09 | 0.525692E+09 | 0.219107E+09 | 0.306586E+09 | 0.00 | 0.00 |
| May | 0.527503E+09 | 0.174292E+09 | 0.457869E+09 | 94465436.52 | 0.363404E+09 | 0.00 | 0.00 |
| June | 0.554000E+09 | 86714903.70 | 0.419772E+09 | 66524244.16 | 0.353248E+09 | 0.00 | 0.00 |
| July | 0.663666E+09 | 39676463.63 | 0.452427E+09 | 79225487.12 | 0.373202E+09 | 0.00 | 0.00 |
| August | 0.884309E+09 | 60495772.10 | 0.601719E+09 | 0.222227E+09 | 0.379492E+09 | 0.00 | 0.00 |
| September | 0.807829E+09 | 0.130225E+09 | 0.617224E+09 | 0.311444E+09 | 0.305780E+09 | 0.00 | 0.00 |
| October | 0.109278E+10 | 0.249085E+09 | 0.892308E+09 | 0.557954E+09 | 0.334354E+09 | 0.00 | 0.00 |
| November | 0.641984E+09 | 0.356387E+09 | 0.604136E+09 | 0.363715E+09 | 0.240421E+09 | 0.00 | 0.00 |
| December | 0.626433E+09 | 0.473232E+09 | 0.614602E+09 | 0.436160E+09 | 0.178442E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.830319E+10 | 0.321267E+10 | 0.709819E+10 | 0.353841E+10 | 0.355979E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.527503E+09 | 39676463.63 | 0.419772E+09 | 66524244.16 | 0.178442E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.109278E+10 | 0.528731E+09 | 0.892308E+09 | 0.557954E+09 | 0.379492E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: T S2 APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.554995E+09 | 0.528684E+09 | 0.569546E+09 | 0.373547E+09 | 0.195999E+09 | 0.00 | 0.00 |
| February | 0.680306E+09 | 0.472073E+09 | 0.681952E+09 | 0.453545E+09 | 0.228408E+09 | 0.00 | 0.00 |
| March | 0.693786E+09 | 0.374439E+09 | 0.660946E+09 | 0.360494E+09 | 0.300451E+09 | 0.00 | 0.00 |
| April | 0.574890E+09 | 0.266837E+09 | 0.525692E+09 | 0.219107E+09 | 0.306586E+09 | 0.00 | 0.00 |
| May | 0.527260E+09 | 0.174111E+09 | 0.457869E+09 | 94465436.52 | 0.363404E+09 | 0.00 | 0.00 |
| June | 0.553934E+09 | 86624580.86 | 0.419772E+09 | 66524244.16 | 0.353248E+09 | 0.00 | 0.00 |
| July | 0.663626E+09 | 39620571.60 | 0.452427E+09 | 79225487.12 | 0.373202E+09 | 0.00 | 0.00 |
| August | 0.884250E+09 | 60415735.21 | 0.601719E+09 | 0.222227E+09 | 0.379492E+09 | 0.00 | 0.00 |
| September | 0.807734E+09 | 0.130149E+09 | 0.617224E+09 | 0.311444E+09 | 0.305780E+09 | 0.00 | 0.00 |
| October | 0.109262E+10 | 0.248909E+09 | 0.892308E+09 | 0.557954E+09 | 0.334354E+09 | 0.00 | 0.00 |
| November | 0.641803E+09 | 0.356438E+09 | 0.604136E+09 | 0.363715E+09 | 0.240421E+09 | 0.00 | 0.00 |
| December | 0.626313E+09 | 0.473197E+09 | 0.614602E+09 | 0.436160E+09 | 0.178442E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.830152E+10 | 0.321150E+10 | 0.709819E+10 | 0.353841E+10 | 0.355979E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.527260E+09 | 39620571.60 | 0.419772E+09 | 66524244.16 | 0.178442E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.109262E+10 | 0.528684E+09 | 0.892308E+09 | 0.557954E+09 | 0.379492E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: T CORRIDOR
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 21870021.65 | 89026571.97 | 36168525.78 | 14498024.71 | 21670501.07 | 0.00 | 0.00 |
| February | 35051485.27 | 79187944.47 | 50352801.23 | 23334402.18 | 27018399.04 | 0.00 | 0.00 |
| March | 62471360.44 | 62060440.78 | 71822997.42 | 30417010.95 | 41405986.47 | 0.00 | 0.00 |
| April | 83781880.72 | 43078370.74 | 83427601.15 | 36720707.64 | 46706893.51 | 0.00 | 0.00 |
| May | 0.116863E+09 | 29757110.56 | 0.104033E+09 | 41491661.29 | 62541299.09 | 0.00 | 0.00 |
| June | 0.115678E+09 | 16379849.40 | 93445170.34 | 33852460.79 | 59592709.55 | 0.00 | 0.00 |
| July | 0.129734E+09 | 9461240.98 | 96902034.38 | 34930391.32 | 61971643.06 | 0.00 | 0.00 |
| August | 0.145602E+09 | 12525549.14 | 0.109086E+09 | 49152640.32 | 59933675.28 | 0.00 | 0.00 |
| September | 94272385.06 | 23644186.92 | 78967322.58 | 35531336.66 | 43435985.91 | 0.00 | 0.00 |
| October | 80594290.60 | 42142619.64 | 73921532.48 | 33536184.50 | 40385347.98 | 0.00 | 0.00 |
| November | 35680992.43 | 59343614.09 | 44259412.10 | 17023654.05 | 27235758.06 | 0.00 | 0.00 |
| December | 23931126.60 | 80616171.33 | 35747781.94 | 16868299.11 | 18879482.83 | 0.00 | 0.00 |
| Annual Sum or Average | 0.945531E+09 | 0.547224E+09 | 0.878134E+09 | 0.367357E+09 | 0.510778E+09 | 0.00 | 0.00 |
| Minimum of Months | 21870021.65 | 9461240.98 | 35747781.94 | 14498024.71 | 18879482.83 | 0.00 | 0.00 |
| Maximum of Months | 0.145602E+09 | 89026571.97 | 0.109086E+09 | 49152640.32 | 62541299.09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: G CORRIDOR
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 71840992.62 | 0.236145E+09 | 0.107719E+09 | 43178725.60 | 64540145.18 | 0.00 | 0.00 |
| February | 0.113656E+09 | 0.208983E+09 | 0.149963E+09 | 69495656.78 | 80467516.24 | 0.00 | 0.00 |
| March | 0.199280E+09 | 0.161350E+09 | 0.213907E+09 | 90589428.30 | 0.123317E+09 | 0.00 | 0.00 |
| April | 0.263115E+09 | 0.112976E+09 | 0.248468E+09 | 0.109363E+09 | 0.139105E+09 | 0.00 | 0.00 |
| May | 0.362500E+09 | 78181629.85 | 0.309836E+09 | 0.123572E+09 | 0.186264E+09 | 0.00 | 0.00 |
| June | 0.348969E+09 | 48213561.16 | 0.278303E+09 | 0.100821E+09 | 0.177482E+09 | 0.00 | 0.00 |
| July | 0.387041E+09 | 29918192.48 | 0.288598E+09 | 0.104031E+09 | 0.184567E+09 | 0.00 | 0.00 |
| August | 0.432835E+09 | 40978511.73 | 0.324886E+09 | 0.146389E+09 | 0.178497E+09 | 0.00 | 0.00 |
| September | 0.281244E+09 | 73023265.30 | 0.235184E+09 | 0.105821E+09 | 0.129363E+09 | 0.00 | 0.00 |
| October | 0.238904E+09 | 0.130831E+09 | 0.220157E+09 | 99879103.38 | 0.120278E+09 | 0.00 | 0.00 |
| November | 0.109245E+09 | 0.171556E+09 | 0.131816E+09 | 50700678.31 | 81114865.48 | 0.00 | 0.00 |
| December | 76192610.14 | 0.219752E+09 | 0.106466E+09 | 50237992.65 | 56227798.27 | 0.00 | 0.00 |
| Annual Sum or Average | 0.288482E+10 | 0.151191E+10 | 0.261530E+10 | 0.109408E+10 | 0.152122E+10 | 0.00 | 0.00 |
| Minimum of Months | 71840992.62 | 29918192.48 | 0.106466E+09 | 43178725.60 | 56227798.27 | 0.00 | 0.00 |
| Maximum of Months | 0.432835E+09 | 0.236145E+09 | 0.324886E+09 | 0.146389E+09 | 0.186264E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: M CORRIDOR
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 20730915.46 | 96372554.51 | 36168525.78 | 14498024.71 | 21670501.07 | 0.00 | 0.00 |
| February | 33608401.56 | 85636923.90 | 50352801.23 | 23334402.18 | 27018399.04 | 0.00 | 0.00 |
| March | 61063894.98 | 66936638.43 | 71822997.42 | 30417010.95 | 41405986.47 | 0.00 | 0.00 |
| April | 81899969.81 | 47136534.17 | 83427601.15 | 36720707.64 | 46706893.51 | 0.00 | 0.00 |
| May | 0.114641E+09 | 32542522.54 | 0.104033E+09 | 41491661.29 | 62541299.09 | 0.00 | 0.00 |
| June | 0.116151E+09 | 16831054.60 | 93445170.34 | 33852460.79 | 59592709.55 | 0.00 | 0.00 |
| July | 0.131094E+09 | 9424848.44 | 96902034.38 | 34930391.32 | 61971643.06 | 0.00 | 0.00 |
| August | 0.146721E+09 | 12739804.67 | 0.109086E+09 | 49152640.32 | 59933675.28 | 0.00 | 0.00 |
| September | 93678792.74 | 25121861.52 | 78967322.58 | 35531336.66 | 43435985.91 | 0.00 | 0.00 |
| October | 77976195.27 | 47098595.56 | 73921532.48 | 33536184.50 | 40385347.98 | 0.00 | 0.00 |
| November | 33676511.28 | 65689702.92 | 44259412.10 | 17023654.05 | 27235758.06 | 0.00 | 0.00 |
| December | 22841983.13 | 87800803.00 | 35747781.94 | 16868299.11 | 18879482.83 | 0.00 | 0.00 |
| Annual Sum or Average | 0.934084E+09 | 0.593332E+09 | 0.878134E+09 | 0.367357E+09 | 0.510778E+09 | 0.00 | 0.00 |
| Minimum of Months | 20730915.46 | 9424848.44 | 35747781.94 | 14498024.71 | 18879482.83 | 0.00 | 0.00 |
| Maximum of Months | 0.146721E+09 | 96372554.51 | 0.109086E+09 | 49152640.32 | 62541299.09 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
| January | 1.17 | -0.7 | -4.4 | 5.65 | -10.4 | 36.91 | 88.07 | 0.05 |
| February | -0.2 | -2.6 | -7.5 | 5.07 | -13.4 | 46.98 | 136.68 | 0.04 |
| March | 5.59 | 3.43 | 0.29 | 5.58 | -4.1 | 68.24 | 153.73 | 0.03 |
| April | 10.94 | 8.00 | 4.75 | 4.99 | 0.53 | 82.64 | 161.98 | 0.05 |
| May | 16.05 | 12.31 | 9.14 | 4.42 | 7.77 | 109.28 | 173.60 | 0.03 |
| June | 21.71 | 18.08 | 15.84 | 4.92 | 13.23 | 112.36 | 186.51 | 0.01 |
| July | 25.05 | 21.76 | 20.26 | 4.06 | 17.39 | 114.46 | 172.96 | 0.02 |
| August | 24.79 | 19.84 | 17.14 | 4.19 | 14.42 | 95.56 | 226.16 | 0.00 |
| September | 19.96 | 15.96 | 13.24 | 3.91 | 10.59 | 73.65 | 166.08 | 0.03 |
| October | 14.02 | 11.03 | 7.95 | 4.86 | 2.64 | 61.34 | 179.75 | 0.00 |
| November | 7.31 | 4.98 | 2.14 | 5.60 | -4.0 | 48.23 | 90.71 | 0.03 |
| December | 3.33 | 0.91 | -2.8 | 5.64 | -8.5 | 30.23 | 98.59 | 0.04 |
| Annual Sum or Average | 12.55 | 9.49 | 6.43 | 4.91 | 2.28 | 73.48 | 153.05 | 0.03 |
| Minimum of Months | -0.2 | -2.6 | -7.5 | 3.91 | -13.4 | 30.23 | 88.07 | 0.00 |
| Maximum of Months | 25.05 | 21.76 | 20.26 | 5.65 | 17.39 | 114.46 | 226.16 | 0.05 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
| January | 12.20 | 24-JAN-12:20 | 11.81 | 11.50 | 1.00 | 8.15 | 93.67 | 0.00 |
| February | 10.00 | 20-FEB-11:00 | 4.36 | -3.3 | 2.60 | -3.9 | 151.50 | 540.00 |
| March | 22.20 | 27-MAR-15:00 | 16.34 | 12.80 | 6.70 | 11.65 | 136.50 | 590.00 |
| April | 26.70 | 07-APR-12:00 | 16.40 | 9.40 | 6.20 | 11.65 | 179.00 | 713.50 |
| May | 30.00 | 30-MAY-12:00 | 18.00 | 10.60 | 5.20 | 17.39 | 233.50 | 730.00 |
| June | 36.70 | 19-JUN-11:00 | 24.28 | 19.40 | 5.20 | 24.83 | 185.00 | 771.50 |
| July | 33.90 | 07-JUL-11:00 | 23.31 | 18.90 | 3.60 | 23.82 | 331.00 | 570.00 |
| August | 33.90 | 24-AUG-14:00 | 20.23 | 12.80 | 8.80 | 21.61 | 240.00 | 432.00 |
| September | 31.10 | 01-SEP-13:00 | 17.34 | 8.30 | 4.60 | 18.46 | 182.00 | 662.00 |
| October | 25.00 | 04-OCT-12:00 | 18.54 | 15.00 | 5.20 | 11.27 | 171.50 | 695.00 |
| November | 17.80 | 04-NOV-12:20 | 12.57 | 8.50 | 3.60 | 6.15 | 182.50 | 595.67 |
| December | 12.20 | 17-DEC-12:20 | 4.65 | -6.1 | 4.27 | -4.7 | 53.17 | 801.67 |
| Annual Sum or Average | ||||||||
| Minimum of Months | 10.00 | 4.36 | -6.1 | 1.00 | -4.7 | 53.17 | 0.00 | |
| Maximum of Months | 36.70 | 24.28 | 19.40 | 8.80 | 24.83 | 331.00 | 801.67 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
| January | -12.2 | 02-JAN-04:00 | -13.6 | -19.4 | 2.60 | -30.7 | 0.00 | 0.00 |
| February | -13.9 | 06-FEB-02:00 | -15.3 | -22.8 | 7.20 | -34.1 | 0.00 | 0.00 |
| March | -5.0 | 23-MAR-03:00 | -7.6 | -14.4 | 1.50 | -23.9 | 0.00 | 0.00 |
| April | 2.20 | 01-APR-03:00 | 0.57 | -1.7 | 3.10 | -6.6 | 0.00 | 0.00 |
| May | 6.10 | 01-MAY-04:00 | 4.33 | 2.20 | 3.60 | -9.7 | 25.50 | 0.00 |
| June | 13.30 | 03-JUN-02:00 | 9.35 | 5.60 | 4.60 | -2.1 | 0.00 | 0.00 |
| July | 18.30 | 02-JUL-02:00 | 17.54 | 17.20 | 0.00 | 5.33 | 0.00 | 0.00 |
| August | 15.00 | 08-AUG-04:00 | 12.47 | 10.60 | 3.10 | 3.06 | 0.00 | 0.00 |
| September | 10.00 | 24-SEP-05:00 | 8.56 | 7.20 | 2.60 | -3.4 | 18.50 | 158.50 |
| October | 2.20 | 09-OCT-03:00 | 1.71 | 1.10 | 0.00 | -13.7 | 0.00 | 0.00 |
| November | -4.4 | 24-NOV-05:00 | -6.2 | -10.0 | 1.50 | -19.7 | 0.00 | 0.00 |
| December | -8.3 | 31-DEC-23:00 | -10.6 | -18.9 | 9.30 | -26.2 | 0.00 | 0.00 |
| Annual Sum or Average | ||||||||
| Minimum of Months | -13.9 | -15.3 | -22.8 | 0.00 | -34.1 | 0.00 | 0.00 | |
| Maximum of Months | 18.30 | 17.54 | 17.20 | 9.30 | 5.33 | 25.50 | 158.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| SITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
| January | 11.93 | 24-JAN-11:00 | 12.20 | 11.70 | 1.50 | 8.15 | 103.00 | 0.00 |
| February | 6.67 | 28-FEB-09:00 | 7.20 | 6.10 | 4.10 | 2.01 | 101.50 | 0.00 |
| March | 16.99 | 27-MAR-12:00 | 20.60 | 15.00 | 3.60 | 10.50 | 295.50 | 565.50 |
| April | 17.70 | 09-APR-10:00 | 21.70 | 15.60 | 4.10 | 14.84 | 244.50 | 281.50 |
| May | 20.43 | 31-MAY-12:00 | 26.10 | 17.80 | 4.10 | 17.03 | 214.00 | 772.00 |
| June | 24.96 | 15-JUN-11:00 | 31.10 | 22.80 | 5.20 | 22.47 | 380.00 | 460.00 |
| July | 26.10 | 08-JUL-11:00 | 32.20 | 23.90 | 5.20 | 22.47 | 354.00 | 501.50 |
| August | 25.84 | 03-AUG-13:00 | 30.00 | 24.40 | 6.20 | 20.57 | 298.00 | 500.00 |
| September | 23.57 | 07-SEP-13:00 | 27.20 | 22.20 | 6.20 | 15.02 | 148.00 | 730.50 |
| October | 19.76 | 25-OCT-10:00 | 25.00 | 17.20 | 7.70 | 14.84 | 189.00 | 308.50 |
| November | 16.10 | 10-NOV-07:00 | 16.10 | 16.10 | 8.20 | 12.98 | 71.50 | 0.00 |
| December | 10.26 | 25-DEC-08:00 | 10.60 | 10.00 | 3.60 | 6.15 | 43.00 | 0.00 |
| Annual Sum or Average | ||||||||
| Minimum of Months | 6.67 | 7.20 | 6.10 | 1.50 | 2.01 | 43.00 | 0.00 | |
| Maximum of Months | 26.10 | 32.20 | 24.40 | 8.20 | 22.47 | 380.00 | 772.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| SITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
| January | 11.70 | 18-JAN-15:00 | 12.20 | 11.93 | 14.90 | 8.15 | 22.00 | 2.00 |
| February | 6.10 | 28-FEB-10:20 | 7.03 | 6.58 | 3.43 | 1.87 | 109.83 | 0.00 |
| March | 15.00 | 27-MAR-12:20 | 18.00 | 16.18 | 3.93 | 10.11 | 271.83 | 611.17 |
| April | 15.60 | 09-APR-10:00 | 21.70 | 17.70 | 4.10 | 14.84 | 244.50 | 281.50 |
| May | 18.00 | 18-MAY-09:00 | 18.00 | 18.00 | 4.60 | 15.39 | 265.50 | 12.00 |
| June | 22.80 | 15-JUN-11:00 | 31.10 | 24.96 | 5.20 | 22.47 | 380.00 | 460.00 |
| July | 24.40 | 09-JUL-07:00 | 27.20 | 25.17 | 2.10 | 15.39 | 195.00 | 504.00 |
| August | 25.00 | 03-AUG-19:00 | 26.10 | 25.32 | 5.70 | 19.35 | 0.00 | 0.00 |
| September | 22.20 | 07-SEP-13:00 | 27.20 | 23.57 | 6.20 | 15.02 | 148.00 | 730.50 |
| October | 18.30 | 05-OCT-18:00 | 19.40 | 18.62 | 7.70 | 6.55 | 0.00 | 0.00 |
| November | 16.10 | 10-NOV-07:00 | 16.10 | 16.10 | 8.20 | 12.98 | 71.50 | 0.00 |
| December | 10.00 | 25-DEC-08:00 | 10.60 | 10.26 | 3.60 | 6.15 | 43.00 | 0.00 |
| Annual Sum or Average | ||||||||
| Minimum of Months | 6.10 | 7.03 | 6.58 | 2.10 | 1.87 | 0.00 | 0.00 | |
| Maximum of Months | 25.00 | 31.10 | 25.32 | 14.90 | 22.47 | 380.00 | 730.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| SITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
| January | 18.00 | 13.00 | 16.00 | 10.03 | 13.58 | 0.00 |
| February | 18.00 | 13.00 | 16.00 | 9.54 | 21.42 | 0.00 |
| March | 18.00 | 13.00 | 16.00 | 10.65 | 30.29 | 0.00 |
| April | 18.00 | 13.00 | 16.00 | 13.15 | 37.02 | 0.00 |
| May | 18.00 | 13.00 | 16.00 | 16.36 | 45.86 | 0.00 |
| June | 18.00 | 13.00 | 16.00 | 19.42 | 49.74 | 0.00 |
| July | 18.00 | 13.00 | 16.00 | 21.50 | 48.12 | 0.00 |
| August | 18.00 | 13.00 | 16.00 | 22.05 | 49.54 | 0.00 |
| September | 18.00 | 13.00 | 16.00 | 20.89 | 34.71 | 0.00 |
| October | 18.00 | 13.00 | 16.00 | 18.36 | 29.93 | 0.00 |
| November | 18.00 | 13.00 | 16.00 | 15.14 | 17.00 | 0.00 |
| December | 18.00 | 13.00 | 16.00 | 12.10 | 12.41 | 0.00 |
| Annual Sum or Average | 18.00 | 13.00 | 16.00 | 15.80 | 32.53 | 0.00 |
| Minimum of Months | 18.00 | 13.00 | 16.00 | 9.54 | 12.41 | 0.00 |
| Maximum of Months | 18.00 | 13.00 | 16.00 | 22.05 | 49.74 | 0.00 |
Report: WaterHeaterReportMonthly
For: G SW APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.124900E+10 | -0.106243E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186568296.2 | 59.44 | 0.00 | 0.00 |
| February | 0.113764E+10 | -969133971.0 | 0.00 | 0.00 | 672.00 | 0.00 | -168508811.4 | 59.44 | 0.00 | 0.00 |
| March | 0.123513E+10 | -0.104903E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186101535.7 | 59.44 | 0.00 | 0.00 |
| April | 0.114078E+10 | -963305806.3 | 0.00 | 0.00 | 720.00 | 0.00 | -177477695.7 | 59.44 | 0.00 | 0.00 |
| May | 0.110466E+10 | -926355843.5 | 0.00 | 0.00 | 744.00 | 0.00 | -178302858.8 | 59.44 | 0.00 | 0.00 |
| June | 0.999737E+09 | -832747925.5 | 0.00 | 0.00 | 720.00 | 0.00 | -166989412.1 | 59.44 | 0.00 | 0.00 |
| July | 0.988202E+09 | -815717607.8 | 0.00 | 0.00 | 744.00 | 0.00 | -172484737.3 | 59.44 | 0.00 | 0.00 |
| August | 0.976473E+09 | -803988065.4 | 0.00 | 0.00 | 744.00 | 0.00 | -172484962.2 | 59.44 | 0.00 | 0.00 |
| September | 0.969087E+09 | -802092544.6 | 0.00 | 0.00 | 720.00 | 0.00 | -166993985.6 | 59.44 | 0.00 | 0.00 |
| October | 0.105669E+10 | -883303728.2 | 0.00 | 0.00 | 744.00 | 0.00 | -173386799.3 | 59.44 | 0.00 | 0.00 |
| November | 0.109859E+10 | -921787215.5 | 0.00 | 0.00 | 720.00 | 0.00 | -176798315.2 | 59.44 | 0.00 | 0.00 |
| December | 0.120429E+10 | -0.101789E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186392713.7 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.131603E+11 | -0.110478E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.211249E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.969087E+09 | -0.106243E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -186568296.2 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.124900E+10 | -802092544.6 | 0.00 | 0.00 | 744.00 | 0.00 | -166989412.1 | 59.44 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: G NW APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.124904E+10 | -0.106243E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186606033.3 | 59.44 | 0.00 | 0.00 |
| February | 0.113768E+10 | -969135093.7 | 0.00 | 0.00 | 672.00 | 0.00 | -168540056.5 | 59.44 | 0.00 | 0.00 |
| March | 0.123558E+10 | -0.104903E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186550662.6 | 59.44 | 0.00 | 0.00 |
| April | 0.114244E+10 | -963307015.4 | 0.00 | 0.00 | 720.00 | 0.00 | -179133469.4 | 59.44 | 0.00 | 0.00 |
| May | 0.110582E+10 | -926355982.8 | 0.00 | 0.00 | 744.00 | 0.00 | -179463572.7 | 59.44 | 0.00 | 0.00 |
| June | 0.999752E+09 | -832751945.5 | 0.00 | 0.00 | 720.00 | 0.00 | -166999736.2 | 59.44 | 0.00 | 0.00 |
| July | 0.988202E+09 | -815714212.9 | 0.00 | 0.00 | 744.00 | 0.00 | -172488124.9 | 59.44 | 0.00 | 0.00 |
| August | 0.976475E+09 | -803988989.0 | 0.00 | 0.00 | 744.00 | 0.00 | -172485748.1 | 59.44 | 0.00 | 0.00 |
| September | 0.969264E+09 | -802091368.7 | 0.00 | 0.00 | 720.00 | 0.00 | -167172720.9 | 59.44 | 0.00 | 0.00 |
| October | 0.105940E+10 | -883303435.2 | 0.00 | 0.00 | 744.00 | 0.00 | -176099979.0 | 59.44 | 0.00 | 0.00 |
| November | 0.110152E+10 | -921786298.3 | 0.00 | 0.00 | 720.00 | 0.00 | -179737404.1 | 59.44 | 0.00 | 0.00 |
| December | 0.120449E+10 | -0.101789E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186601269.6 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.131697E+11 | -0.110478E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.212188E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.969264E+09 | -0.106243E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -186606033.3 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.124904E+10 | -802091368.7 | 0.00 | 0.00 | 744.00 | 0.00 | -166999736.2 | 59.44 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: G NE APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.124904E+10 | -0.106243E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186606033.3 | 59.44 | 0.00 | 0.00 |
| February | 0.113768E+10 | -969135093.7 | 0.00 | 0.00 | 672.00 | 0.00 | -168540056.4 | 59.44 | 0.00 | 0.00 |
| March | 0.123561E+10 | -0.104903E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186578561.5 | 59.44 | 0.00 | 0.00 |
| April | 0.114241E+10 | -963306839.6 | 0.00 | 0.00 | 720.00 | 0.00 | -179100330.8 | 59.44 | 0.00 | 0.00 |
| May | 0.110581E+10 | -926355331.0 | 0.00 | 0.00 | 744.00 | 0.00 | -179455566.0 | 59.44 | 0.00 | 0.00 |
| June | 0.999739E+09 | -832752214.4 | 0.00 | 0.00 | 720.00 | 0.00 | -166987077.3 | 59.44 | 0.00 | 0.00 |
| July | 0.988202E+09 | -815713411.8 | 0.00 | 0.00 | 744.00 | 0.00 | -172488774.4 | 59.44 | 0.00 | 0.00 |
| August | 0.976475E+09 | -803988851.4 | 0.00 | 0.00 | 744.00 | 0.00 | -172486189.8 | 59.44 | 0.00 | 0.00 |
| September | 0.969225E+09 | -802092367.8 | 0.00 | 0.00 | 720.00 | 0.00 | -167132805.2 | 59.44 | 0.00 | 0.00 |
| October | 0.105943E+10 | -883301339.2 | 0.00 | 0.00 | 744.00 | 0.00 | -176126725.0 | 59.44 | 0.00 | 0.00 |
| November | 0.110140E+10 | -921787110.6 | 0.00 | 0.00 | 720.00 | 0.00 | -179608860.3 | 59.44 | 0.00 | 0.00 |
| December | 0.120449E+10 | -0.101789E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186601639.4 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.131695E+11 | -0.110478E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.212171E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.969225E+09 | -0.106243E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -186606033.3 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.124904E+10 | -802092367.8 | 0.00 | 0.00 | 744.00 | 0.00 | -166987077.3 | 59.44 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: G N1 APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.124904E+10 | -0.106243E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186606033.2 | 59.44 | 0.00 | 0.00 |
| February | 0.113768E+10 | -969135093.7 | 0.00 | 0.00 | 672.00 | 0.00 | -168540056.5 | 59.44 | 0.00 | 0.00 |
| March | 0.123559E+10 | -0.104903E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186557481.1 | 59.44 | 0.00 | 0.00 |
| April | 0.114230E+10 | -963306036.7 | 0.00 | 0.00 | 720.00 | 0.00 | -178991996.1 | 59.44 | 0.00 | 0.00 |
| May | 0.110488E+10 | -926357842.5 | 0.00 | 0.00 | 744.00 | 0.00 | -178522860.1 | 59.44 | 0.00 | 0.00 |
| June | 0.999696E+09 | -832750474.3 | 0.00 | 0.00 | 720.00 | 0.00 | -166945827.6 | 59.44 | 0.00 | 0.00 |
| July | 0.988201E+09 | -815719412.7 | 0.00 | 0.00 | 744.00 | 0.00 | -172481229.1 | 59.44 | 0.00 | 0.00 |
| August | 0.976476E+09 | -803987172.1 | 0.00 | 0.00 | 744.00 | 0.00 | -172489062.3 | 59.44 | 0.00 | 0.00 |
| September | 0.969100E+09 | -802094626.0 | 0.00 | 0.00 | 720.00 | 0.00 | -167005279.5 | 59.44 | 0.00 | 0.00 |
| October | 0.105849E+10 | -883302788.7 | 0.00 | 0.00 | 744.00 | 0.00 | -175187028.4 | 59.44 | 0.00 | 0.00 |
| November | 0.110081E+10 | -921789260.7 | 0.00 | 0.00 | 720.00 | 0.00 | -179019090.1 | 59.44 | 0.00 | 0.00 |
| December | 0.120449E+10 | -0.101789E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186600987.2 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.131667E+11 | -0.110478E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.211895E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.969100E+09 | -0.106243E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -186606033.2 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.124904E+10 | -802094626.0 | 0.00 | 0.00 | 744.00 | 0.00 | -166945827.6 | 59.44 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: G N2 APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.124904E+10 | -0.106243E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186606033.2 | 59.44 | 0.00 | 0.00 |
| February | 0.113768E+10 | -969135093.7 | 0.00 | 0.00 | 672.00 | 0.00 | -168540056.5 | 59.44 | 0.00 | 0.00 |
| March | 0.123559E+10 | -0.104903E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186559017.3 | 59.44 | 0.00 | 0.00 |
| April | 0.114229E+10 | -963305989.5 | 0.00 | 0.00 | 720.00 | 0.00 | -178980460.7 | 59.44 | 0.00 | 0.00 |
| May | 0.110489E+10 | -926358217.1 | 0.00 | 0.00 | 744.00 | 0.00 | -178534268.4 | 59.44 | 0.00 | 0.00 |
| June | 0.999696E+09 | -832751157.2 | 0.00 | 0.00 | 720.00 | 0.00 | -166944766.0 | 59.44 | 0.00 | 0.00 |
| July | 0.988201E+09 | -815718907.3 | 0.00 | 0.00 | 744.00 | 0.00 | -172482348.3 | 59.44 | 0.00 | 0.00 |
| August | 0.976476E+09 | -803987274.6 | 0.00 | 0.00 | 744.00 | 0.00 | -172488517.2 | 59.44 | 0.00 | 0.00 |
| September | 0.969099E+09 | -802094770.9 | 0.00 | 0.00 | 720.00 | 0.00 | -167004196.4 | 59.44 | 0.00 | 0.00 |
| October | 0.105850E+10 | -883301760.7 | 0.00 | 0.00 | 744.00 | 0.00 | -175194638.6 | 59.44 | 0.00 | 0.00 |
| November | 0.110078E+10 | -921788659.3 | 0.00 | 0.00 | 720.00 | 0.00 | -178993018.5 | 59.44 | 0.00 | 0.00 |
| December | 0.120449E+10 | -0.101789E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186601791.4 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.131667E+11 | -0.110478E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.211893E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.969099E+09 | -0.106243E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -186606033.2 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.124904E+10 | -802094770.9 | 0.00 | 0.00 | 744.00 | 0.00 | -166944766.0 | 59.44 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: G S1 APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.124896E+10 | -0.106243E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186531747.2 | 59.44 | 0.00 | 0.00 |
| February | 0.113758E+10 | -969133314.1 | 0.00 | 0.00 | 672.00 | 0.00 | -168445395.0 | 59.44 | 0.00 | 0.00 |
| March | 0.123494E+10 | -0.104903E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -185911516.2 | 59.44 | 0.00 | 0.00 |
| April | 0.113995E+10 | -963305337.9 | 0.00 | 0.00 | 720.00 | 0.00 | -176646611.0 | 59.44 | 0.00 | 0.00 |
| May | 0.110328E+10 | -926358247.5 | 0.00 | 0.00 | 744.00 | 0.00 | -176919216.2 | 59.44 | 0.00 | 0.00 |
| June | 0.999687E+09 | -832749260.4 | 0.00 | 0.00 | 720.00 | 0.00 | -166937971.8 | 59.44 | 0.00 | 0.00 |
| July | 0.988200E+09 | -815717453.4 | 0.00 | 0.00 | 744.00 | 0.00 | -172482426.6 | 59.44 | 0.00 | 0.00 |
| August | 0.976477E+09 | -803989900.0 | 0.00 | 0.00 | 744.00 | 0.00 | -172486905.8 | 59.44 | 0.00 | 0.00 |
| September | 0.969036E+09 | -802100917.8 | 0.00 | 0.00 | 720.00 | 0.00 | -166934815.5 | 59.44 | 0.00 | 0.00 |
| October | 0.105614E+10 | -883300980.8 | 0.00 | 0.00 | 744.00 | 0.00 | -172839994.1 | 59.44 | 0.00 | 0.00 |
| November | 0.109711E+10 | -921785794.4 | 0.00 | 0.00 | 720.00 | 0.00 | -175320128.8 | 59.44 | 0.00 | 0.00 |
| December | 0.120398E+10 | -0.101789E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186091542.9 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.131553E+11 | -0.110478E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.210755E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.969036E+09 | -0.106243E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -186531747.2 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.124896E+10 | -802100917.8 | 0.00 | 0.00 | 744.00 | 0.00 | -166934815.5 | 59.44 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: G S2 APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.124898E+10 | -0.106243E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186552767.4 | 59.44 | 0.00 | 0.00 |
| February | 0.113761E+10 | -969133644.0 | 0.00 | 0.00 | 672.00 | 0.00 | -168474320.3 | 59.44 | 0.00 | 0.00 |
| March | 0.123501E+10 | -0.104903E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -185971394.9 | 59.44 | 0.00 | 0.00 |
| April | 0.113986E+10 | -963305807.3 | 0.00 | 0.00 | 720.00 | 0.00 | -176557039.0 | 59.44 | 0.00 | 0.00 |
| May | 0.110291E+10 | -926359998.4 | 0.00 | 0.00 | 744.00 | 0.00 | -176554562.1 | 59.44 | 0.00 | 0.00 |
| June | 0.999681E+09 | -832749857.1 | 0.00 | 0.00 | 720.00 | 0.00 | -166931380.9 | 59.44 | 0.00 | 0.00 |
| July | 0.988202E+09 | -815716067.1 | 0.00 | 0.00 | 744.00 | 0.00 | -172486333.0 | 59.44 | 0.00 | 0.00 |
| August | 0.976473E+09 | -803988877.8 | 0.00 | 0.00 | 744.00 | 0.00 | -172484241.2 | 59.44 | 0.00 | 0.00 |
| September | 0.969031E+09 | -802092069.8 | 0.00 | 0.00 | 720.00 | 0.00 | -166938767.5 | 59.44 | 0.00 | 0.00 |
| October | 0.105609E+10 | -883296854.9 | 0.00 | 0.00 | 744.00 | 0.00 | -172798100.6 | 59.44 | 0.00 | 0.00 |
| November | 0.109702E+10 | -921787122.7 | 0.00 | 0.00 | 720.00 | 0.00 | -175230292.9 | 59.44 | 0.00 | 0.00 |
| December | 0.120406E+10 | -0.101789E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186163298.3 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.131549E+11 | -0.110478E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.210714E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.969031E+09 | -0.106243E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -186552767.4 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.124898E+10 | -802092069.8 | 0.00 | 0.00 | 744.00 | 0.00 | -166931380.9 | 59.44 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: M SW APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.231120E+10 | -0.212487E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186327978.3 | 59.44 | 0.00 | 0.00 |
| February | 0.210628E+10 | -0.193827E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -168008663.8 | 59.44 | 0.00 | 0.00 |
| March | 0.228218E+10 | -0.209807E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -184113883.8 | 59.44 | 0.00 | 0.00 |
| April | 0.209993E+10 | -0.192662E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -173308412.8 | 59.44 | 0.00 | 0.00 |
| May | 0.202595E+10 | -0.185272E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -173229587.2 | 59.44 | 0.00 | 0.00 |
| June | 0.183243E+10 | -0.166551E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -166926975.2 | 59.44 | 0.00 | 0.00 |
| July | 0.180392E+10 | -0.163144E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172486830.6 | 59.44 | 0.00 | 0.00 |
| August | 0.178047E+10 | -0.160798E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172484426.9 | 59.44 | 0.00 | 0.00 |
| September | 0.177119E+10 | -0.160420E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -166990750.3 | 59.44 | 0.00 | 0.00 |
| October | 0.194038E+10 | -0.176660E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -173777349.9 | 59.44 | 0.00 | 0.00 |
| November | 0.202040E+10 | -0.184358E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -176825663.8 | 59.44 | 0.00 | 0.00 |
| December | 0.222169E+10 | -0.203579E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -185900151.4 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.241960E+11 | -0.220957E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.210038E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.177119E+10 | -0.212487E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -186327978.3 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.231120E+10 | -0.160420E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -166926975.2 | 59.44 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: M NW APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.231147E+10 | -0.212487E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186602083.0 | 59.44 | 0.00 | 0.00 |
| February | 0.210682E+10 | -0.193827E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -168541471.3 | 59.44 | 0.00 | 0.00 |
| March | 0.228408E+10 | -0.209808E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186002066.6 | 59.44 | 0.00 | 0.00 |
| April | 0.210184E+10 | -0.192661E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -175225594.3 | 59.44 | 0.00 | 0.00 |
| May | 0.202616E+10 | -0.185272E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -173437492.1 | 59.44 | 0.00 | 0.00 |
| June | 0.183244E+10 | -0.166551E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -166928797.9 | 59.44 | 0.00 | 0.00 |
| July | 0.180392E+10 | -0.163144E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172484802.5 | 59.44 | 0.00 | 0.00 |
| August | 0.178047E+10 | -0.160798E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172485620.0 | 59.44 | 0.00 | 0.00 |
| September | 0.177132E+10 | -0.160420E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -167117403.3 | 59.44 | 0.00 | 0.00 |
| October | 0.194316E+10 | -0.176661E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -176553054.7 | 59.44 | 0.00 | 0.00 |
| November | 0.202316E+10 | -0.184358E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -179581277.6 | 59.44 | 0.00 | 0.00 |
| December | 0.222239E+10 | -0.203579E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186604283.6 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.242072E+11 | -0.220956E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.211156E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.177132E+10 | -0.212487E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -186604283.6 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.231147E+10 | -0.160420E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -166928797.9 | 59.44 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: M SE APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.231121E+10 | -0.212487E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186341111.4 | 59.44 | 0.00 | 0.00 |
| February | 0.210629E+10 | -0.193827E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -168020763.1 | 59.44 | 0.00 | 0.00 |
| March | 0.228227E+10 | -0.209807E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -184202546.0 | 59.44 | 0.00 | 0.00 |
| April | 0.209975E+10 | -0.192662E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -173135991.5 | 59.44 | 0.00 | 0.00 |
| May | 0.202593E+10 | -0.185272E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -173203653.0 | 59.44 | 0.00 | 0.00 |
| June | 0.183243E+10 | -0.166551E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -166927264.8 | 59.44 | 0.00 | 0.00 |
| July | 0.180392E+10 | -0.163144E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172486312.7 | 59.44 | 0.00 | 0.00 |
| August | 0.178047E+10 | -0.160798E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172484875.7 | 59.44 | 0.00 | 0.00 |
| September | 0.177119E+10 | -0.160420E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -166989209.1 | 59.44 | 0.00 | 0.00 |
| October | 0.194034E+10 | -0.176660E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -173739993.1 | 59.44 | 0.00 | 0.00 |
| November | 0.202016E+10 | -0.184358E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -176578550.4 | 59.44 | 0.00 | 0.00 |
| December | 0.222164E+10 | -0.203579E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -185851675.3 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.241956E+11 | -0.220956E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.209996E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.177119E+10 | -0.212487E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -186341111.4 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.231121E+10 | -0.160420E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -166927264.8 | 59.44 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: M NE APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.231147E+10 | -0.212487E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186603093.9 | 59.44 | 0.00 | 0.00 |
| February | 0.210682E+10 | -0.193827E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -168542571.1 | 59.44 | 0.00 | 0.00 |
| March | 0.228418E+10 | -0.209807E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186111243.5 | 59.44 | 0.00 | 0.00 |
| April | 0.210162E+10 | -0.192662E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -175007994.5 | 59.44 | 0.00 | 0.00 |
| May | 0.202610E+10 | -0.185272E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -173384001.7 | 59.44 | 0.00 | 0.00 |
| June | 0.183244E+10 | -0.166551E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -166927926.1 | 59.44 | 0.00 | 0.00 |
| July | 0.180392E+10 | -0.163144E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172485721.4 | 59.44 | 0.00 | 0.00 |
| August | 0.178047E+10 | -0.160798E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172487800.7 | 59.44 | 0.00 | 0.00 |
| September | 0.177128E+10 | -0.160419E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -167086902.1 | 59.44 | 0.00 | 0.00 |
| October | 0.194316E+10 | -0.176661E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -176551135.7 | 59.44 | 0.00 | 0.00 |
| November | 0.202303E+10 | -0.184358E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -179451414.2 | 59.44 | 0.00 | 0.00 |
| December | 0.222239E+10 | -0.203579E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186604302.6 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.242069E+11 | -0.220956E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.211124E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.177128E+10 | -0.212487E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -186604302.6 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.231147E+10 | -0.160419E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -166927926.1 | 59.44 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: M N1 APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.231147E+10 | -0.212487E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186599755.0 | 59.44 | 0.00 | 0.00 |
| February | 0.210682E+10 | -0.193827E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -168542573.1 | 59.44 | 0.00 | 0.00 |
| March | 0.228396E+10 | -0.209807E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -185891889.1 | 59.44 | 0.00 | 0.00 |
| April | 0.210114E+10 | -0.192662E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -174524580.8 | 59.44 | 0.00 | 0.00 |
| May | 0.202564E+10 | -0.185272E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172919135.0 | 59.44 | 0.00 | 0.00 |
| June | 0.183243E+10 | -0.166551E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -166925585.1 | 59.44 | 0.00 | 0.00 |
| July | 0.180392E+10 | -0.163144E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172484875.7 | 59.44 | 0.00 | 0.00 |
| August | 0.178047E+10 | -0.160798E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172484864.3 | 59.44 | 0.00 | 0.00 |
| September | 0.177117E+10 | -0.160420E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -166974315.6 | 59.44 | 0.00 | 0.00 |
| October | 0.194193E+10 | -0.176661E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -175327503.4 | 59.44 | 0.00 | 0.00 |
| November | 0.202218E+10 | -0.184358E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -178595658.0 | 59.44 | 0.00 | 0.00 |
| December | 0.222239E+10 | -0.203579E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186599780.3 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.242035E+11 | -0.220956E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.210787E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.177117E+10 | -0.212487E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -186599780.3 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.231147E+10 | -0.160420E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -166925585.1 | 59.44 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: M N2 APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.231147E+10 | -0.212487E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186599769.3 | 59.44 | 0.00 | 0.00 |
| February | 0.210682E+10 | -0.193827E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -168542538.2 | 59.44 | 0.00 | 0.00 |
| March | 0.228397E+10 | -0.209807E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -185900198.3 | 59.44 | 0.00 | 0.00 |
| April | 0.210112E+10 | -0.192662E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -174499556.3 | 59.44 | 0.00 | 0.00 |
| May | 0.202564E+10 | -0.185272E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172915356.9 | 59.44 | 0.00 | 0.00 |
| June | 0.183243E+10 | -0.166551E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -166925538.6 | 59.44 | 0.00 | 0.00 |
| July | 0.180392E+10 | -0.163144E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172484858.5 | 59.44 | 0.00 | 0.00 |
| August | 0.178047E+10 | -0.160798E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172484892.8 | 59.44 | 0.00 | 0.00 |
| September | 0.177117E+10 | -0.160420E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -166973826.8 | 59.44 | 0.00 | 0.00 |
| October | 0.194194E+10 | -0.176661E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -175329786.7 | 59.44 | 0.00 | 0.00 |
| November | 0.202215E+10 | -0.184358E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -178570459.5 | 59.44 | 0.00 | 0.00 |
| December | 0.222239E+10 | -0.203579E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186599851.1 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.242035E+11 | -0.220956E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.210783E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.177117E+10 | -0.212487E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -186599851.1 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.231147E+10 | -0.160420E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -166925538.6 | 59.44 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: M S1 APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.231083E+10 | -0.212487E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -185961823.2 | 59.44 | 0.00 | 0.00 |
| February | 0.210582E+10 | -0.193827E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -167554677.4 | 59.44 | 0.00 | 0.00 |
| March | 0.228091E+10 | -0.209807E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -182842296.0 | 59.44 | 0.00 | 0.00 |
| April | 0.209865E+10 | -0.192661E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -172036390.1 | 59.44 | 0.00 | 0.00 |
| May | 0.202548E+10 | -0.185272E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172760175.6 | 59.44 | 0.00 | 0.00 |
| June | 0.183243E+10 | -0.166550E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -166925217.7 | 59.44 | 0.00 | 0.00 |
| July | 0.180392E+10 | -0.163144E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172486219.0 | 59.44 | 0.00 | 0.00 |
| August | 0.178047E+10 | -0.160798E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172487477.9 | 59.44 | 0.00 | 0.00 |
| September | 0.177113E+10 | -0.160419E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -166938685.6 | 59.44 | 0.00 | 0.00 |
| October | 0.193959E+10 | -0.176660E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172985745.9 | 59.44 | 0.00 | 0.00 |
| November | 0.201858E+10 | -0.184358E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -175000364.1 | 59.44 | 0.00 | 0.00 |
| December | 0.222077E+10 | -0.203579E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -184977530.7 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.241886E+11 | -0.220956E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.209296E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.177113E+10 | -0.212487E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -185961823.2 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.231083E+10 | -0.160419E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -166925217.7 | 59.44 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: M S2 APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.231083E+10 | -0.212487E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -185961025.1 | 59.44 | 0.00 | 0.00 |
| February | 0.210582E+10 | -0.193827E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -167550984.2 | 59.44 | 0.00 | 0.00 |
| March | 0.228093E+10 | -0.209807E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -182855648.0 | 59.44 | 0.00 | 0.00 |
| April | 0.209864E+10 | -0.192661E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -172024597.8 | 59.44 | 0.00 | 0.00 |
| May | 0.202548E+10 | -0.185272E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172760552.5 | 59.44 | 0.00 | 0.00 |
| June | 0.183243E+10 | -0.166550E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -166925165.0 | 59.44 | 0.00 | 0.00 |
| July | 0.180392E+10 | -0.163144E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172486219.2 | 59.44 | 0.00 | 0.00 |
| August | 0.178047E+10 | -0.160798E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172487486.3 | 59.44 | 0.00 | 0.00 |
| September | 0.177113E+10 | -0.160419E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -166938607.4 | 59.44 | 0.00 | 0.00 |
| October | 0.193959E+10 | -0.176660E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172986745.7 | 59.44 | 0.00 | 0.00 |
| November | 0.201856E+10 | -0.184358E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -174977040.2 | 59.44 | 0.00 | 0.00 |
| December | 0.222076E+10 | -0.203579E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -184970103.0 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.241886E+11 | -0.220956E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.209292E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.177113E+10 | -0.212487E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -185961025.1 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.231083E+10 | -0.160419E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -166925165.0 | 59.44 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: T SW APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.124876E+10 | -0.106243E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186326293.6 | 59.44 | 0.00 | 0.00 |
| February | 0.113709E+10 | -969133078.6 | 0.00 | 0.00 | 672.00 | 0.00 | -167953131.5 | 59.44 | 0.00 | 0.00 |
| March | 0.123353E+10 | -0.104903E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -184494815.0 | 59.44 | 0.00 | 0.00 |
| April | 0.113886E+10 | -963305924.1 | 0.00 | 0.00 | 720.00 | 0.00 | -175555181.6 | 59.44 | 0.00 | 0.00 |
| May | 0.110313E+10 | -926352472.1 | 0.00 | 0.00 | 744.00 | 0.00 | -176775174.3 | 59.44 | 0.00 | 0.00 |
| June | 0.100002E+10 | -832746650.9 | 0.00 | 0.00 | 720.00 | 0.00 | -167275780.2 | 59.44 | 0.00 | 0.00 |
| July | 0.988200E+09 | -815717401.0 | 0.00 | 0.00 | 744.00 | 0.00 | -172482115.0 | 59.44 | 0.00 | 0.00 |
| August | 0.976542E+09 | -803990078.1 | 0.00 | 0.00 | 744.00 | 0.00 | -172552052.8 | 59.44 | 0.00 | 0.00 |
| September | 0.970279E+09 | -802097324.0 | 0.00 | 0.00 | 720.00 | 0.00 | -168181949.8 | 59.44 | 0.00 | 0.00 |
| October | 0.106109E+10 | -883298307.6 | 0.00 | 0.00 | 744.00 | 0.00 | -177792909.7 | 59.44 | 0.00 | 0.00 |
| November | 0.110064E+10 | -921788150.4 | 0.00 | 0.00 | 720.00 | 0.00 | -178851875.3 | 59.44 | 0.00 | 0.00 |
| December | 0.120398E+10 | -0.101789E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186092062.4 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.131621E+11 | -0.110478E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.211433E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.970279E+09 | -0.106243E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -186326293.6 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.124876E+10 | -802097324.0 | 0.00 | 0.00 | 744.00 | 0.00 | -167275780.2 | 59.44 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: T NW APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.124903E+10 | -0.106243E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186605018.9 | 59.44 | 0.00 | 0.00 |
| February | 0.113767E+10 | -969135070.1 | 0.00 | 0.00 | 672.00 | 0.00 | -168539923.3 | 59.44 | 0.00 | 0.00 |
| March | 0.123496E+10 | -0.104903E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -185925455.8 | 59.44 | 0.00 | 0.00 |
| April | 0.114004E+10 | -963306338.3 | 0.00 | 0.00 | 720.00 | 0.00 | -176730387.4 | 59.44 | 0.00 | 0.00 |
| May | 0.110330E+10 | -926353393.4 | 0.00 | 0.00 | 744.00 | 0.00 | -176951441.7 | 59.44 | 0.00 | 0.00 |
| June | 0.999999E+09 | -832747735.0 | 0.00 | 0.00 | 720.00 | 0.00 | -167251677.3 | 59.44 | 0.00 | 0.00 |
| July | 0.988201E+09 | -815717493.8 | 0.00 | 0.00 | 744.00 | 0.00 | -172483069.3 | 59.44 | 0.00 | 0.00 |
| August | 0.976561E+09 | -803989577.0 | 0.00 | 0.00 | 744.00 | 0.00 | -172571796.1 | 59.44 | 0.00 | 0.00 |
| September | 0.970767E+09 | -802095118.5 | 0.00 | 0.00 | 720.00 | 0.00 | -168671919.8 | 59.44 | 0.00 | 0.00 |
| October | 0.106368E+10 | -883299724.4 | 0.00 | 0.00 | 744.00 | 0.00 | -180383472.2 | 59.44 | 0.00 | 0.00 |
| November | 0.110202E+10 | -921787964.5 | 0.00 | 0.00 | 720.00 | 0.00 | -180234550.2 | 59.44 | 0.00 | 0.00 |
| December | 0.120449E+10 | -0.101789E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186602314.8 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.131707E+11 | -0.110478E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.212295E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.970767E+09 | -0.106243E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -186605018.9 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.124903E+10 | -802095118.5 | 0.00 | 0.00 | 744.00 | 0.00 | -167251677.3 | 59.44 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: T SE APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.124878E+10 | -0.106243E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186345379.7 | 59.44 | 0.00 | 0.00 |
| February | 0.113713E+10 | -969132640.4 | 0.00 | 0.00 | 672.00 | 0.00 | -167996686.5 | 59.44 | 0.00 | 0.00 |
| March | 0.123355E+10 | -0.104903E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -184519604.2 | 59.44 | 0.00 | 0.00 |
| April | 0.113866E+10 | -963306043.0 | 0.00 | 0.00 | 720.00 | 0.00 | -175355923.8 | 59.44 | 0.00 | 0.00 |
| May | 0.110294E+10 | -926353921.6 | 0.00 | 0.00 | 744.00 | 0.00 | -176581230.3 | 59.44 | 0.00 | 0.00 |
| June | 0.999972E+09 | -832750381.5 | 0.00 | 0.00 | 720.00 | 0.00 | -167221935.7 | 59.44 | 0.00 | 0.00 |
| July | 0.988202E+09 | -815718066.6 | 0.00 | 0.00 | 744.00 | 0.00 | -172484254.8 | 59.44 | 0.00 | 0.00 |
| August | 0.976539E+09 | -803990062.8 | 0.00 | 0.00 | 744.00 | 0.00 | -172549133.7 | 59.44 | 0.00 | 0.00 |
| September | 0.970205E+09 | -802098241.1 | 0.00 | 0.00 | 720.00 | 0.00 | -168107120.1 | 59.44 | 0.00 | 0.00 |
| October | 0.106097E+10 | -883298643.4 | 0.00 | 0.00 | 744.00 | 0.00 | -177668408.0 | 59.44 | 0.00 | 0.00 |
| November | 0.110046E+10 | -921786551.9 | 0.00 | 0.00 | 720.00 | 0.00 | -178678056.2 | 59.44 | 0.00 | 0.00 |
| December | 0.120396E+10 | -0.101789E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186066690.5 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.131614E+11 | -0.110478E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.211357E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.970205E+09 | -0.106243E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -186345379.7 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.124878E+10 | -802098241.1 | 0.00 | 0.00 | 744.00 | 0.00 | -167221935.7 | 59.44 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: T NE APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.124904E+10 | -0.106243E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186606033.5 | 59.44 | 0.00 | 0.00 |
| February | 0.113768E+10 | -969135093.7 | 0.00 | 0.00 | 672.00 | 0.00 | -168540056.5 | 59.44 | 0.00 | 0.00 |
| March | 0.123509E+10 | -0.104903E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186058963.8 | 59.44 | 0.00 | 0.00 |
| April | 0.113986E+10 | -963305427.4 | 0.00 | 0.00 | 720.00 | 0.00 | -176553355.8 | 59.44 | 0.00 | 0.00 |
| May | 0.110306E+10 | -926358861.2 | 0.00 | 0.00 | 744.00 | 0.00 | -176704431.2 | 59.44 | 0.00 | 0.00 |
| June | 0.999962E+09 | -832753528.0 | 0.00 | 0.00 | 720.00 | 0.00 | -167208241.8 | 59.44 | 0.00 | 0.00 |
| July | 0.988202E+09 | -815713402.4 | 0.00 | 0.00 | 744.00 | 0.00 | -172488768.3 | 59.44 | 0.00 | 0.00 |
| August | 0.976555E+09 | -803988150.0 | 0.00 | 0.00 | 744.00 | 0.00 | -172567291.7 | 59.44 | 0.00 | 0.00 |
| September | 0.970598E+09 | -802092728.0 | 0.00 | 0.00 | 720.00 | 0.00 | -168504995.2 | 59.44 | 0.00 | 0.00 |
| October | 0.106376E+10 | -883298164.2 | 0.00 | 0.00 | 744.00 | 0.00 | -180466624.3 | 59.44 | 0.00 | 0.00 |
| November | 0.110204E+10 | -921787297.1 | 0.00 | 0.00 | 720.00 | 0.00 | -180254765.5 | 59.44 | 0.00 | 0.00 |
| December | 0.120449E+10 | -0.101789E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186601483.5 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.131703E+11 | -0.110478E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.212256E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.970598E+09 | -0.106243E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -186606033.5 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.124904E+10 | -802092728.0 | 0.00 | 0.00 | 744.00 | 0.00 | -167208241.8 | 59.44 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: T N1 APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.124904E+10 | -0.106243E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186606033.3 | 59.44 | 0.00 | 0.00 |
| February | 0.113768E+10 | -969135093.7 | 0.00 | 0.00 | 672.00 | 0.00 | -168540056.5 | 59.44 | 0.00 | 0.00 |
| March | 0.123507E+10 | -0.104903E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186040122.6 | 59.44 | 0.00 | 0.00 |
| April | 0.113977E+10 | -963304717.7 | 0.00 | 0.00 | 720.00 | 0.00 | -176466169.8 | 59.44 | 0.00 | 0.00 |
| May | 0.110231E+10 | -926358031.1 | 0.00 | 0.00 | 744.00 | 0.00 | -175949141.1 | 59.44 | 0.00 | 0.00 |
| June | 0.999838E+09 | -832753975.4 | 0.00 | 0.00 | 720.00 | 0.00 | -167084005.3 | 59.44 | 0.00 | 0.00 |
| July | 0.988201E+09 | -815713841.0 | 0.00 | 0.00 | 744.00 | 0.00 | -172487226.9 | 59.44 | 0.00 | 0.00 |
| August | 0.976517E+09 | -803988998.8 | 0.00 | 0.00 | 744.00 | 0.00 | -172528359.0 | 59.44 | 0.00 | 0.00 |
| September | 0.970173E+09 | -802092646.0 | 0.00 | 0.00 | 720.00 | 0.00 | -168080306.6 | 59.44 | 0.00 | 0.00 |
| October | 0.106318E+10 | -883298349.5 | 0.00 | 0.00 | 744.00 | 0.00 | -179885346.0 | 59.44 | 0.00 | 0.00 |
| November | 0.110194E+10 | -921788687.5 | 0.00 | 0.00 | 720.00 | 0.00 | -180152263.9 | 59.44 | 0.00 | 0.00 |
| December | 0.120449E+10 | -0.101789E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186602281.0 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.131682E+11 | -0.110478E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.212042E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.970173E+09 | -0.106243E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -186606033.3 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.124904E+10 | -802092646.0 | 0.00 | 0.00 | 744.00 | 0.00 | -167084005.3 | 59.44 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: T N2 APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.124904E+10 | -0.106243E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186606033.3 | 59.44 | 0.00 | 0.00 |
| February | 0.113768E+10 | -969135093.7 | 0.00 | 0.00 | 672.00 | 0.00 | -168540056.5 | 59.44 | 0.00 | 0.00 |
| March | 0.123508E+10 | -0.104903E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186044726.5 | 59.44 | 0.00 | 0.00 |
| April | 0.113974E+10 | -963304898.3 | 0.00 | 0.00 | 720.00 | 0.00 | -176438643.4 | 59.44 | 0.00 | 0.00 |
| May | 0.110230E+10 | -926357019.2 | 0.00 | 0.00 | 744.00 | 0.00 | -175941849.4 | 59.44 | 0.00 | 0.00 |
| June | 0.999837E+09 | -832753825.3 | 0.00 | 0.00 | 720.00 | 0.00 | -167083587.6 | 59.44 | 0.00 | 0.00 |
| July | 0.988201E+09 | -815714117.1 | 0.00 | 0.00 | 744.00 | 0.00 | -172486473.8 | 59.44 | 0.00 | 0.00 |
| August | 0.976518E+09 | -803988644.6 | 0.00 | 0.00 | 744.00 | 0.00 | -172529850.3 | 59.44 | 0.00 | 0.00 |
| September | 0.970162E+09 | -802093291.0 | 0.00 | 0.00 | 720.00 | 0.00 | -168068479.0 | 59.44 | 0.00 | 0.00 |
| October | 0.106320E+10 | -883298753.2 | 0.00 | 0.00 | 744.00 | 0.00 | -179900948.5 | 59.44 | 0.00 | 0.00 |
| November | 0.110194E+10 | -921788658.8 | 0.00 | 0.00 | 720.00 | 0.00 | -180149715.3 | 59.44 | 0.00 | 0.00 |
| December | 0.120449E+10 | -0.101789E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186602297.7 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.131682E+11 | -0.110478E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.212039E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.970162E+09 | -0.106243E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -186606033.3 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.124904E+10 | -802093291.0 | 0.00 | 0.00 | 744.00 | 0.00 | -167083587.6 | 59.44 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: T S1 APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.124860E+10 | -0.106243E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186165087.5 | 59.44 | 0.00 | 0.00 |
| February | 0.113686E+10 | -969132792.2 | 0.00 | 0.00 | 672.00 | 0.00 | -167731165.3 | 59.44 | 0.00 | 0.00 |
| March | 0.123318E+10 | -0.104903E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -184149275.1 | 59.44 | 0.00 | 0.00 |
| April | 0.113819E+10 | -963306120.4 | 0.00 | 0.00 | 720.00 | 0.00 | -174884882.4 | 59.44 | 0.00 | 0.00 |
| May | 0.110206E+10 | -926359725.8 | 0.00 | 0.00 | 744.00 | 0.00 | -175699620.3 | 59.44 | 0.00 | 0.00 |
| June | 0.999855E+09 | -832749479.4 | 0.00 | 0.00 | 720.00 | 0.00 | -167105515.9 | 59.44 | 0.00 | 0.00 |
| July | 0.988202E+09 | -815717633.0 | 0.00 | 0.00 | 744.00 | 0.00 | -172484765.3 | 59.44 | 0.00 | 0.00 |
| August | 0.976501E+09 | -803988220.0 | 0.00 | 0.00 | 744.00 | 0.00 | -172512714.3 | 59.44 | 0.00 | 0.00 |
| September | 0.969735E+09 | -802099003.8 | 0.00 | 0.00 | 720.00 | 0.00 | -167636192.0 | 59.44 | 0.00 | 0.00 |
| October | 0.105990E+10 | -883301370.5 | 0.00 | 0.00 | 744.00 | 0.00 | -176603216.4 | 59.44 | 0.00 | 0.00 |
| November | 0.109992E+10 | -921789965.6 | 0.00 | 0.00 | 720.00 | 0.00 | -178129077.1 | 59.44 | 0.00 | 0.00 |
| December | 0.120363E+10 | -0.101789E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -185733727.0 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.131566E+11 | -0.110478E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.210884E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.969735E+09 | -0.106243E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -186165087.5 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.124860E+10 | -802099003.8 | 0.00 | 0.00 | 744.00 | 0.00 | -167105515.9 | 59.44 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: T S2 APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.124860E+10 | -0.106243E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186161958.9 | 59.44 | 0.00 | 0.00 |
| February | 0.113686E+10 | -969132785.2 | 0.00 | 0.00 | 672.00 | 0.00 | -167727665.9 | 59.44 | 0.00 | 0.00 |
| March | 0.123318E+10 | -0.104903E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -184151154.9 | 59.44 | 0.00 | 0.00 |
| April | 0.113818E+10 | -963306046.2 | 0.00 | 0.00 | 720.00 | 0.00 | -174871878.6 | 59.44 | 0.00 | 0.00 |
| May | 0.110206E+10 | -926359494.2 | 0.00 | 0.00 | 744.00 | 0.00 | -175699601.4 | 59.44 | 0.00 | 0.00 |
| June | 0.999854E+09 | -832749540.1 | 0.00 | 0.00 | 720.00 | 0.00 | -167104183.4 | 59.44 | 0.00 | 0.00 |
| July | 0.988203E+09 | -815717976.0 | 0.00 | 0.00 | 744.00 | 0.00 | -172484609.5 | 59.44 | 0.00 | 0.00 |
| August | 0.976502E+09 | -803988058.6 | 0.00 | 0.00 | 744.00 | 0.00 | -172513474.7 | 59.44 | 0.00 | 0.00 |
| September | 0.969735E+09 | -802098955.0 | 0.00 | 0.00 | 720.00 | 0.00 | -167635969.4 | 59.44 | 0.00 | 0.00 |
| October | 0.105991E+10 | -883301304.8 | 0.00 | 0.00 | 744.00 | 0.00 | -176608374.5 | 59.44 | 0.00 | 0.00 |
| November | 0.109990E+10 | -921790055.0 | 0.00 | 0.00 | 720.00 | 0.00 | -178109933.2 | 59.44 | 0.00 | 0.00 |
| December | 0.120362E+10 | -0.101789E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -185726373.1 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.131566E+11 | -0.110478E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.210880E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.969735E+09 | -0.106243E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -186161958.9 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.124860E+10 | -802098955.0 | 0.00 | 0.00 | 744.00 | 0.00 | -167104183.4 | 59.44 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
| January | 199.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 216.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 275.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 261.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 372.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 351.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 365.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 389.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 285.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 305.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 240.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 211.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 3472.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 199.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 389.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT GSW HEATING COIL
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.274339E+10 | 2349.60 | 02-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.251962E+10 | 2627.76 | 06-FEB-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.150848E+10 | 1701.62 | 22-MAR-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.597741E+09 | 1182.95 | 02-APR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 39990971.64 | 475.23 | 01-MAY-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.704044E+09 | 1494.58 | 23-NOV-02:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.180796E+10 | 1963.96 | 31-DEC-22:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.992122E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.274339E+10 | 2627.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT GNW HEATING COIL
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.342751E+10 | 2620.88 | 02-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.341327E+10 | 2947.71 | 06-FEB-01:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.215665E+10 | 1940.00 | 22-MAR-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.855433E+09 | 1231.83 | 02-APR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 68583686.82 | 566.32 | 01-MAY-04:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 2125075.29 | 143.88 | 29-OCT-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.113633E+10 | 1755.94 | 23-NOV-02:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.255226E+10 | 2231.55 | 31-DEC-22:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.136122E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.342751E+10 | 2947.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT OFFICE HEATING COIL
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.100664E+10 | 10664.53 | 03-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.981825E+09 | 10664.53 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.296650E+09 | 10664.53 | 01-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 30610895.54 | 10664.53 | 03-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 69201984.97 | 10664.53 | 20-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.334641E+09 | 10664.53 | 06-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.271957E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.100664E+10 | 10664.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT GNE HEATING COIL
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.341087E+10 | 2584.21 | 02-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.338014E+10 | 2920.70 | 06-FEB-01:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.218381E+10 | 1872.11 | 22-MAR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.841760E+09 | 1232.80 | 02-APR-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 69289971.72 | 586.77 | 01-MAY-04:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 1764102.07 | 93.54 | 31-OCT-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.108608E+10 | 1726.52 | 23-NOV-02:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.252332E+10 | 2239.89 | 31-DEC-22:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.134970E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.341087E+10 | 2920.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT GN1 HEATING COIL
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.241305E+10 | 1889.43 | 02-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.245861E+10 | 2110.05 | 06-FEB-01:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.150562E+10 | 1359.21 | 22-MAR-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.493125E+09 | 802.04 | 02-APR-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 14720242.41 | 308.06 | 01-MAY-04:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.693061E+09 | 1211.85 | 23-NOV-02:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.173939E+10 | 1559.85 | 31-DEC-22:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.931758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.245861E+10 | 2110.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT GN2 HEATING COIL
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.241226E+10 | 1887.24 | 02-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.245736E+10 | 2108.72 | 06-FEB-01:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.150745E+10 | 1358.87 | 22-MAR-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.493213E+09 | 803.76 | 02-APR-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 14611443.31 | 310.19 | 01-MAY-04:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.690193E+09 | 1209.54 | 23-NOV-02:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.173804E+10 | 1560.51 | 31-DEC-22:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.931313E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.245736E+10 | 2108.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT GS1 HEATING COIL
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.175445E+10 | 1617.30 | 02-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.159192E+10 | 1790.46 | 06-FEB-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.886980E+09 | 1129.83 | 22-MAR-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.293755E+09 | 740.52 | 02-APR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 686451.28 | 105.54 | 01-MAY-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.329737E+09 | 972.14 | 23-NOV-02:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.103168E+10 | 1330.76 | 31-DEC-24:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.588921E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.175445E+10 | 1790.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT GS2 HEATING COIL
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.196700E+10 | 1793.12 | 02-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.175669E+10 | 1944.17 | 06-FEB-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.975526E+09 | 1197.68 | 22-MAR-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.312044E+09 | 805.56 | 02-APR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 264172.00 | 73.27 | 01-MAY-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.366118E+09 | 1013.50 | 23-NOV-02:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.113740E+10 | 1449.58 | 31-DEC-24:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.651504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.196700E+10 | 1944.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT MSW HEATING COIL
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.451385E+10 | 4664.62 | 02-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.371134E+10 | 5236.60 | 06-FEB-01:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.142415E+10 | 3243.47 | 22-MAR-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.398962E+09 | 1877.97 | 02-APR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.144452E+10 | 3526.45 | 23-NOV-02:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.323037E+10 | 4196.53 | 31-DEC-22:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.147232E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.451385E+10 | 5236.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT MNW HEATING COIL
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.589428E+10 | 5190.41 | 02-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.543350E+10 | 5858.43 | 06-FEB-01:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.257986E+10 | 3588.44 | 22-MAR-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.602098E+09 | 1922.52 | 02-APR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 29057124.36 | 753.60 | 28-OCT-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.236869E+10 | 3953.06 | 23-NOV-02:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.473793E+10 | 4719.90 | 31-DEC-22:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.216454E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.589428E+10 | 5858.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT MSE HEATING COIL
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.447476E+10 | 4596.03 | 02-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.363944E+10 | 5192.59 | 06-FEB-01:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.145602E+10 | 3205.64 | 22-MAR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.397052E+09 | 1838.99 | 02-APR-05:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.137080E+10 | 3494.95 | 23-NOV-02:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.317361E+10 | 4212.01 | 31-DEC-22:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.145117E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.447476E+10 | 5192.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT MNE HEATING COIL
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.585986E+10 | 5124.10 | 02-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.536433E+10 | 5800.53 | 06-FEB-01:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.262249E+10 | 3495.37 | 22-MAR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.603888E+09 | 1887.57 | 02-APR-05:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 23945148.63 | 678.34 | 29-OCT-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.225805E+10 | 3906.33 | 23-NOV-02:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.467563E+10 | 4746.41 | 31-DEC-22:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.214082E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.585986E+10 | 5800.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT MN1 HEATING COIL
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.375841E+10 | 3500.64 | 02-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.358588E+10 | 3953.77 | 06-FEB-01:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.152610E+10 | 2320.02 | 22-MAR-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.231207E+09 | 1154.03 | 02-APR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.124324E+10 | 2563.31 | 23-NOV-02:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.288531E+10 | 3073.35 | 31-DEC-22:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.132302E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.375841E+10 | 3953.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT MN2 HEATING COIL
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.375695E+10 | 3496.40 | 02-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.358296E+10 | 3950.36 | 06-FEB-01:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.153027E+10 | 2319.40 | 22-MAR-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.231889E+09 | 1156.34 | 02-APR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.123780E+10 | 2559.71 | 23-NOV-02:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.288247E+10 | 3074.10 | 31-DEC-22:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.132223E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.375695E+10 | 3950.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT MS1 HEATING COIL
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.243406E+10 | 3070.25 | 02-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.191080E+10 | 3469.34 | 06-FEB-01:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.561181E+09 | 1826.77 | 22-MAR-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.119117E+09 | 1063.92 | 02-APR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.526839E+09 | 2174.88 | 23-NOV-02:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.151080E+10 | 2648.01 | 31-DEC-24:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.706280E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.243406E+10 | 3469.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT MS2 HEATING COIL
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.243261E+10 | 3066.31 | 02-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.190936E+10 | 3466.88 | 06-FEB-01:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.563347E+09 | 1828.25 | 22-MAR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.119913E+09 | 1067.88 | 02-APR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.523037E+09 | 2170.69 | 23-NOV-02:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.150869E+10 | 2648.24 | 31-DEC-24:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.705695E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.243261E+10 | 3466.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT TSW HEATING COIL
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.407549E+10 | 3777.12 | 02-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.354186E+10 | 4275.12 | 06-FEB-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.199631E+10 | 2814.97 | 22-MAR-06:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.862638E+09 | 1757.14 | 02-APR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 50680147.56 | 855.34 | 01-MAY-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 371462.54 | 190.71 | 24-SEP-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.251129E+09 | 1305.37 | 08-OCT-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.189760E+10 | 2967.61 | 23-NOV-02:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.327075E+10 | 3370.34 | 31-DEC-24:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.159468E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.407549E+10 | 4275.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT TNW HEATING COIL
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.480231E+10 | 3940.81 | 02-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.441758E+10 | 4465.87 | 06-FEB-01:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.252337E+10 | 2937.88 | 22-MAR-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.997255E+09 | 1768.19 | 02-APR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 56954519.90 | 863.44 | 01-MAY-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 1522860.14 | 410.12 | 24-SEP-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.471200E+09 | 1474.35 | 08-OCT-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.246811E+10 | 3113.54 | 23-NOV-02:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.406266E+10 | 3628.37 | 31-DEC-22:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.198010E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.480231E+10 | 4465.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT TSE HEATING COIL
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.405227E+10 | 3751.42 | 02-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.349493E+10 | 4258.32 | 06-FEB-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.200610E+10 | 2826.86 | 22-MAR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.847635E+09 | 1734.49 | 02-APR-05:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 50541374.13 | 873.03 | 01-MAY-04:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 277986.23 | 155.87 | 24-SEP-05:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.244477E+09 | 1309.48 | 08-OCT-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.184190E+10 | 2959.95 | 23-NOV-02:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.323517E+10 | 3378.28 | 31-DEC-24:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.157733E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.405227E+10 | 4258.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT TNE HEATING COIL
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.478296E+10 | 3919.97 | 02-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.437321E+10 | 4445.83 | 06-FEB-01:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.253813E+10 | 2918.56 | 22-MAR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.978592E+09 | 1749.49 | 02-APR-05:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 57980372.76 | 899.22 | 01-MAY-04:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 1447565.03 | 318.05 | 24-SEP-05:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.458358E+09 | 1482.65 | 08-OCT-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.239229E+10 | 3105.58 | 23-NOV-02:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.402384E+10 | 3644.92 | 31-DEC-22:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.196068E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.478296E+10 | 4445.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT TN1 HEATING COIL
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.345722E+10 | 2849.69 | 02-JAN-00:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.323567E+10 | 3228.35 | 06-FEB-01:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.178095E+10 | 2021.30 | 22-MAR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.624086E+09 | 1225.33 | 02-APR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 17246988.48 | 547.08 | 01-MAY-04:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.270907E+09 | 998.36 | 29-OCT-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.164739E+10 | 2200.52 | 23-NOV-02:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.288089E+10 | 2573.25 | 31-DEC-24:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.139144E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.345722E+10 | 3228.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT TN2 HEATING COIL
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.345667E+10 | 2848.53 | 02-JAN-00:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.323433E+10 | 3227.36 | 06-FEB-01:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.178376E+10 | 2022.73 | 22-MAR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.624931E+09 | 1225.83 | 02-APR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 17369256.51 | 552.20 | 01-MAY-04:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.271876E+09 | 999.77 | 29-OCT-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.164405E+10 | 2199.97 | 23-NOV-02:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.287941E+10 | 2574.10 | 31-DEC-24:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.139124E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.345667E+10 | 3227.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT TS1 HEATING COIL
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.274365E+10 | 2679.70 | 02-JAN-00:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.237242E+10 | 3080.69 | 06-FEB-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.126483E+10 | 1912.90 | 22-MAR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.499343E+09 | 1212.37 | 02-APR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 13689532.90 | 526.70 | 01-MAY-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.102858E+09 | 759.33 | 08-OCT-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.112936E+10 | 2044.32 | 23-NOV-02:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.212402E+10 | 2340.74 | 31-DEC-24:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.102502E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.274365E+10 | 3080.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT TS2 HEATING COIL
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.274347E+10 | 2677.97 | 02-JAN-00:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.237207E+10 | 3079.78 | 06-FEB-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.126831E+10 | 1914.22 | 22-MAR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.500304E+09 | 1212.97 | 02-APR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 13807213.40 | 532.12 | 01-MAY-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.103162E+09 | 759.88 | 08-OCT-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.112666E+10 | 2043.61 | 23-NOV-02:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.212318E+10 | 2341.68 | 31-DEC-24:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.102510E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.274347E+10 | 3079.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT GSW COOLING COIL
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 53729176.49 | 51095703.65 | 809.08 | 07-APR-16:10 | 809.08 | 0.00 |
| May | 0.00 | 0.00 | 0.334809E+09 | 0.308624E+09 | 1863.73 | 31-MAY-14:10 | 1550.28 | 0.00 |
| June | 0.00 | 0.00 | 0.236916E+10 | 0.181591E+10 | 2933.87 | 19-JUN-17:10 | 2374.52 | 0.00 |
| July | 0.00 | 0.00 | 0.438156E+10 | 0.318917E+10 | 3021.17 | 21-JUL-16:02 | 2180.77 | 0.00 |
| August | 0.00 | 0.00 | 0.458013E+10 | 0.368278E+10 | 3381.48 | 16-AUG-16:10 | 2611.61 | 0.00 |
| September | 0.00 | 0.00 | 0.259279E+10 | 0.219653E+10 | 3178.68 | 07-SEP-15:10 | 2460.51 | 0.00 |
| October | 0.00 | 0.00 | 0.132755E+10 | 0.114082E+10 | 2485.47 | 04-OCT-15:30 | 2156.46 | 0.00 |
| November | 0.00 | 0.00 | 39094080.50 | 39082431.20 | 691.20 | 03-NOV-15:50 | 691.20 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.156788E+11 | 0.124240E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.458013E+10 | 0.368278E+10 | 3381.48 | 2611.61 | 0.00 |
Report: CoilReportMonthly
For: SPLIT GNW COOLING COIL
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.235761E+09 | 0.212553E+09 | 1663.16 | 31-MAY-16:20 | 1362.62 | 0.00 |
| June | 0.00 | 0.00 | 0.218539E+10 | 0.165304E+10 | 2878.29 | 19-JUN-17:20 | 2294.60 | 0.00 |
| July | 0.00 | 0.00 | 0.411381E+10 | 0.295744E+10 | 2870.77 | 06-JUL-17:13 | 2093.21 | 0.00 |
| August | 0.00 | 0.00 | 0.393171E+10 | 0.308454E+10 | 3050.42 | 16-AUG-16:07 | 2277.30 | 0.00 |
| September | 0.00 | 0.00 | 0.182440E+10 | 0.148324E+10 | 2500.48 | 07-SEP-16:02 | 1856.92 | 0.00 |
| October | 0.00 | 0.00 | 0.352708E+09 | 0.278017E+09 | 1564.13 | 04-OCT-16:10 | 1245.84 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.126438E+11 | 0.966883E+10 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.411381E+10 | 0.308454E+10 | 3050.42 | 2294.60 | 0.00 |
Report: CoilReportMonthly
For: SPLIT OFFICE COOLING COIL
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.145700E+09 | 0.141940E+09 | 4721.32 | 10-APR-08:63 | 4070.29 | 0.00 |
| May | 0.00 | 0.00 | 0.618647E+09 | 0.565630E+09 | 7382.01 | 23-MAY-08:62 | 5662.81 | 0.00 |
| June | 0.00 | 0.00 | 0.204726E+10 | 0.166293E+10 | 7993.66 | 19-JUN-07:02 | 4733.38 | 0.00 |
| July | 0.00 | 0.00 | 0.290348E+10 | 0.224861E+10 | 8083.21 | 28-JUL-07:02 | 4354.40 | 0.00 |
| August | 0.00 | 0.00 | 0.342857E+10 | 0.287056E+10 | 8070.42 | 03-AUG-07:02 | 4537.88 | 0.00 |
| September | 0.00 | 0.00 | 0.209504E+10 | 0.181716E+10 | 8033.03 | 14-SEP-07:02 | 4441.75 | 0.00 |
| October | 0.00 | 0.00 | 0.140888E+10 | 0.125512E+10 | 7613.96 | 06-OCT-07:03 | 5474.19 | 0.00 |
| November | 0.00 | 0.00 | 0.185805E+09 | 0.181101E+09 | 2534.58 | 10-NOV-09:05 | 1899.92 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.128334E+11 | 0.107431E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.342857E+10 | 0.287056E+10 | 8083.21 | 5662.81 | 0.00 |
Report: CoilReportMonthly
For: SPLIT GNE COOLING COIL
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 17347.38 | 16101.40 | 28.91 | 08-APR-12:00 | 26.84 | 0.00 |
| May | 0.00 | 0.00 | 0.259238E+09 | 0.234391E+09 | 1494.34 | 31-MAY-10:00 | 1240.87 | 0.00 |
| June | 0.00 | 0.00 | 0.210012E+10 | 0.158718E+10 | 2519.74 | 19-JUN-17:10 | 1976.43 | 0.00 |
| July | 0.00 | 0.00 | 0.409052E+10 | 0.293728E+10 | 2700.06 | 08-JUL-12:00 | 1973.85 | 0.00 |
| August | 0.00 | 0.00 | 0.391219E+10 | 0.306547E+10 | 2790.61 | 04-AUG-19:00 | 2072.12 | 0.00 |
| September | 0.00 | 0.00 | 0.182341E+10 | 0.148353E+10 | 2073.15 | 07-SEP-15:10 | 1473.57 | 0.00 |
| October | 0.00 | 0.00 | 0.328269E+09 | 0.257262E+09 | 1424.15 | 25-OCT-10:30 | 1025.18 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.125138E+11 | 0.956513E+10 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.409052E+10 | 0.306547E+10 | 2790.61 | 2072.12 | 0.00 |
Report: CoilReportMonthly
For: SPLIT GN1 COOLING COIL
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.206158E+09 | 0.184519E+09 | 1171.16 | 31-MAY-14:10 | 935.34 | 0.00 |
| June | 0.00 | 0.00 | 0.195241E+10 | 0.145565E+10 | 2163.35 | 19-JUN-17:25 | 1679.51 | 0.00 |
| July | 0.00 | 0.00 | 0.359719E+10 | 0.254703E+10 | 2191.39 | 20-JUL-17:10 | 1476.40 | 0.00 |
| August | 0.00 | 0.00 | 0.330429E+10 | 0.254749E+10 | 2394.59 | 04-AUG-19:00 | 1742.80 | 0.00 |
| September | 0.00 | 0.00 | 0.160309E+10 | 0.128733E+10 | 1758.42 | 07-SEP-16:12 | 1252.73 | 0.00 |
| October | 0.00 | 0.00 | 0.293450E+09 | 0.227432E+09 | 1044.08 | 25-OCT-11:00 | 749.76 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.109566E+11 | 0.824945E+10 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.359719E+10 | 0.254749E+10 | 2394.59 | 1742.80 | 0.00 |
Report: CoilReportMonthly
For: SPLIT GN2 COOLING COIL
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.209152E+09 | 0.187324E+09 | 1177.38 | 31-MAY-14:10 | 941.27 | 0.00 |
| June | 0.00 | 0.00 | 0.194878E+10 | 0.145283E+10 | 2153.38 | 19-JUN-17:25 | 1670.76 | 0.00 |
| July | 0.00 | 0.00 | 0.359623E+10 | 0.254621E+10 | 2184.02 | 20-JUL-17:10 | 1470.48 | 0.00 |
| August | 0.00 | 0.00 | 0.330381E+10 | 0.254702E+10 | 2393.69 | 04-AUG-19:00 | 1741.68 | 0.00 |
| September | 0.00 | 0.00 | 0.160423E+10 | 0.128832E+10 | 1749.98 | 07-SEP-16:12 | 1246.07 | 0.00 |
| October | 0.00 | 0.00 | 0.292255E+09 | 0.226478E+09 | 1052.01 | 25-OCT-11:00 | 756.22 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.109545E+11 | 0.824818E+10 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.359623E+10 | 0.254702E+10 | 2393.69 | 1741.68 | 0.00 |
Report: CoilReportMonthly
For: SPLIT GS1 COOLING COIL
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 49297908.08 | 46585545.55 | 749.25 | 08-APR-12:00 | 697.27 | 0.00 |
| May | 0.00 | 0.00 | 0.303683E+09 | 0.278638E+09 | 1494.80 | 31-MAY-14:00 | 1238.35 | 0.00 |
| June | 0.00 | 0.00 | 0.215221E+10 | 0.163221E+10 | 2229.51 | 19-JUN-12:00 | 1832.27 | 0.00 |
| July | 0.00 | 0.00 | 0.388447E+10 | 0.279522E+10 | 2530.34 | 08-JUL-12:30 | 1810.24 | 0.00 |
| August | 0.00 | 0.00 | 0.397820E+10 | 0.316587E+10 | 2716.98 | 16-AUG-13:00 | 2026.91 | 0.00 |
| September | 0.00 | 0.00 | 0.242105E+10 | 0.204452E+10 | 2517.77 | 07-SEP-14:10 | 1933.51 | 0.00 |
| October | 0.00 | 0.00 | 0.139314E+10 | 0.120883E+10 | 2036.16 | 04-OCT-13:00 | 1790.68 | 0.00 |
| November | 0.00 | 0.00 | 88217076.11 | 88195762.04 | 786.44 | 02-NOV-12:50 | 786.44 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.142703E+11 | 0.112601E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.397820E+10 | 0.316587E+10 | 2716.98 | 2026.91 | 0.00 |
Report: CoilReportMonthly
For: SPLIT GS2 COOLING COIL
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 55386648.34 | 52278211.16 | 792.33 | 08-APR-12:00 | 737.71 | 0.00 |
| May | 0.00 | 0.00 | 0.348378E+09 | 0.320845E+09 | 1567.11 | 31-MAY-14:00 | 1305.35 | 0.00 |
| June | 0.00 | 0.00 | 0.235762E+10 | 0.180298E+10 | 2310.91 | 19-JUN-12:00 | 1911.85 | 0.00 |
| July | 0.00 | 0.00 | 0.420676E+10 | 0.306861E+10 | 2682.82 | 08-JUL-12:30 | 1947.50 | 0.00 |
| August | 0.00 | 0.00 | 0.430146E+10 | 0.345528E+10 | 2815.79 | 16-AUG-13:00 | 2119.53 | 0.00 |
| September | 0.00 | 0.00 | 0.265324E+10 | 0.225446E+10 | 2614.64 | 07-SEP-14:10 | 2022.68 | 0.00 |
| October | 0.00 | 0.00 | 0.151191E+10 | 0.131595E+10 | 2097.82 | 04-OCT-13:00 | 1849.82 | 0.00 |
| November | 0.00 | 0.00 | 0.102281E+09 | 0.102135E+09 | 836.73 | 02-NOV-12:50 | 836.73 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.155370E+11 | 0.123725E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.430146E+10 | 0.345528E+10 | 2815.79 | 2119.53 | 0.00 |
Report: CoilReportMonthly
For: SPLIT MSW COOLING COIL
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 22957861.68 | 21683594.35 | 1369.67 | 27-MAR-16:20 | 1179.56 | 0.00 |
| April | 0.00 | 0.00 | 0.804338E+09 | 0.770070E+09 | 4891.60 | 07-APR-15:30 | 4891.60 | 0.00 |
| May | 0.00 | 0.00 | 0.263282E+10 | 0.249099E+10 | 5482.54 | 31-MAY-15:10 | 4767.58 | 0.00 |
| June | 0.00 | 0.00 | 0.706825E+10 | 0.556398E+10 | 7501.69 | 19-JUN-17:10 | 6182.97 | 0.00 |
| July | 0.00 | 0.00 | 0.107459E+11 | 0.797260E+10 | 7425.51 | 21-JUL-16:02 | 5447.86 | 0.00 |
| August | 0.00 | 0.00 | 0.104528E+11 | 0.847136E+10 | 7902.48 | 02-AUG-15:20 | 5911.93 | 0.00 |
| September | 0.00 | 0.00 | 0.578975E+10 | 0.491993E+10 | 7450.23 | 07-SEP-15:10 | 5805.15 | 0.00 |
| October | 0.00 | 0.00 | 0.296237E+10 | 0.256104E+10 | 6107.26 | 04-OCT-15:20 | 5321.78 | 0.00 |
| November | 0.00 | 0.00 | 0.135448E+09 | 0.135410E+09 | 2133.67 | 04-NOV-12:30 | 2133.67 | 0.00 |
| December | 0.00 | 0.00 | 302356.22 | 302356.22 | 126.87 | 17-DEC-14:40 | 126.87 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.406150E+11 | 0.329074E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.107459E+11 | 0.847136E+10 | 7902.48 | 6182.97 | 0.00 |
Report: CoilReportMonthly
For: SPLIT MNW COOLING COIL
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.278404E+09 | 0.261841E+09 | 2588.00 | 07-APR-16:17 | 2588.00 | 0.00 |
| May | 0.00 | 0.00 | 0.213686E+10 | 0.200237E+10 | 5125.19 | 31-MAY-16:20 | 4324.69 | 0.00 |
| June | 0.00 | 0.00 | 0.669473E+10 | 0.521704E+10 | 7422.06 | 19-JUN-17:25 | 6040.73 | 0.00 |
| July | 0.00 | 0.00 | 0.101770E+11 | 0.746351E+10 | 7176.61 | 06-JUL-17:13 | 5374.03 | 0.00 |
| August | 0.00 | 0.00 | 0.907049E+10 | 0.717651E+10 | 7203.05 | 02-AUG-16:02 | 5339.88 | 0.00 |
| September | 0.00 | 0.00 | 0.413076E+10 | 0.336355E+10 | 5852.51 | 07-SEP-16:02 | 4380.90 | 0.00 |
| October | 0.00 | 0.00 | 0.895223E+09 | 0.706890E+09 | 3898.91 | 04-OCT-16:10 | 3101.67 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.333835E+11 | 0.261917E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.101770E+11 | 0.746351E+10 | 7422.06 | 6040.73 | 0.00 |
Report: CoilReportMonthly
For: SPLIT MSE COOLING COIL
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 8214704.88 | 8100790.92 | 799.75 | 03-MAR-14:00 | 799.75 | 0.00 |
| April | 0.00 | 0.00 | 0.799798E+09 | 0.766741E+09 | 4693.31 | 08-APR-12:00 | 4497.05 | 0.00 |
| May | 0.00 | 0.00 | 0.268011E+10 | 0.253806E+10 | 5130.33 | 29-MAY-12:00 | 4897.24 | 0.00 |
| June | 0.00 | 0.00 | 0.689021E+10 | 0.541941E+10 | 6910.67 | 19-JUN-10:50 | 5689.13 | 0.00 |
| July | 0.00 | 0.00 | 0.107010E+11 | 0.793154E+10 | 7325.71 | 08-JUL-12:30 | 5499.61 | 0.00 |
| August | 0.00 | 0.00 | 0.104097E+11 | 0.842569E+10 | 7248.41 | 16-AUG-13:00 | 5586.48 | 0.00 |
| September | 0.00 | 0.00 | 0.580110E+10 | 0.493498E+10 | 6589.31 | 07-SEP-13:40 | 5132.74 | 0.00 |
| October | 0.00 | 0.00 | 0.289904E+10 | 0.250563E+10 | 5987.19 | 25-OCT-10:30 | 4641.22 | 0.00 |
| November | 0.00 | 0.00 | 0.155167E+09 | 0.155127E+09 | 2326.58 | 04-NOV-12:30 | 2326.58 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.403443E+11 | 0.326853E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.107010E+11 | 0.842569E+10 | 7325.71 | 5689.13 | 0.00 |
Report: CoilReportMonthly
For: SPLIT MNE COOLING COIL
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.265284E+09 | 0.249826E+09 | 2573.41 | 08-APR-10:00 | 2439.66 | 0.00 |
| May | 0.00 | 0.00 | 0.217512E+10 | 0.204061E+10 | 4478.64 | 31-MAY-09:50 | 3876.98 | 0.00 |
| June | 0.00 | 0.00 | 0.651310E+10 | 0.507257E+10 | 6414.36 | 19-JUN-10:30 | 5125.31 | 0.00 |
| July | 0.00 | 0.00 | 0.101282E+11 | 0.742261E+10 | 6433.19 | 08-JUL-12:40 | 4706.82 | 0.00 |
| August | 0.00 | 0.00 | 0.902487E+10 | 0.713258E+10 | 6351.53 | 04-AUG-10:20 | 4566.94 | 0.00 |
| September | 0.00 | 0.00 | 0.413046E+10 | 0.336912E+10 | 4641.98 | 14-SEP-14:00 | 3594.64 | 0.00 |
| October | 0.00 | 0.00 | 0.835761E+09 | 0.656714E+09 | 3440.01 | 25-OCT-10:30 | 2492.31 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.330728E+11 | 0.259440E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.101282E+11 | 0.742261E+10 | 6433.19 | 5125.31 | 0.00 |
Report: CoilReportMonthly
For: SPLIT MN1 COOLING COIL
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.179635E+09 | 0.166968E+09 | 1593.62 | 08-APR-12:00 | 1506.69 | 0.00 |
| May | 0.00 | 0.00 | 0.179671E+10 | 0.165640E+10 | 3267.16 | 31-MAY-14:10 | 2692.26 | 0.00 |
| June | 0.00 | 0.00 | 0.547729E+10 | 0.419298E+10 | 5198.78 | 19-JUN-17:25 | 4107.81 | 0.00 |
| July | 0.00 | 0.00 | 0.843365E+10 | 0.606461E+10 | 5052.59 | 20-JUL-17:10 | 3474.40 | 0.00 |
| August | 0.00 | 0.00 | 0.732056E+10 | 0.568013E+10 | 5211.33 | 04-AUG-19:00 | 3820.28 | 0.00 |
| September | 0.00 | 0.00 | 0.357425E+10 | 0.287345E+10 | 3809.33 | 14-SEP-14:00 | 2899.03 | 0.00 |
| October | 0.00 | 0.00 | 0.788058E+09 | 0.612956E+09 | 2412.34 | 25-OCT-11:00 | 1741.22 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.275701E+11 | 0.212475E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.843365E+10 | 0.606461E+10 | 5211.33 | 4107.81 | 0.00 |
Report: CoilReportMonthly
For: SPLIT MN2 COOLING COIL
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.182772E+09 | 0.169952E+09 | 1630.25 | 08-APR-12:00 | 1541.80 | 0.00 |
| May | 0.00 | 0.00 | 0.180026E+10 | 0.165994E+10 | 3273.41 | 31-MAY-14:10 | 2698.82 | 0.00 |
| June | 0.00 | 0.00 | 0.547098E+10 | 0.418779E+10 | 5180.46 | 19-JUN-17:25 | 4091.75 | 0.00 |
| July | 0.00 | 0.00 | 0.843248E+10 | 0.606342E+10 | 5034.51 | 20-JUL-17:10 | 3459.47 | 0.00 |
| August | 0.00 | 0.00 | 0.732000E+10 | 0.567943E+10 | 5207.76 | 04-AUG-19:00 | 3816.41 | 0.00 |
| September | 0.00 | 0.00 | 0.357671E+10 | 0.287571E+10 | 3804.95 | 14-SEP-14:00 | 2895.99 | 0.00 |
| October | 0.00 | 0.00 | 0.786670E+09 | 0.611802E+09 | 2434.73 | 25-OCT-11:00 | 1759.43 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.275699E+11 | 0.212480E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.843248E+10 | 0.606342E+10 | 5207.76 | 4091.75 | 0.00 |
Report: CoilReportMonthly
For: SPLIT MS1 COOLING COIL
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 21480384.22 | 21005825.00 | 1080.67 | 03-MAR-14:00 | 1080.67 | 0.00 |
| April | 0.00 | 0.00 | 0.733496E+09 | 0.699119E+09 | 3829.75 | 08-APR-12:00 | 3648.73 | 0.00 |
| May | 0.00 | 0.00 | 0.231278E+10 | 0.216245E+10 | 4026.97 | 31-MAY-14:00 | 3422.29 | 0.00 |
| June | 0.00 | 0.00 | 0.586407E+10 | 0.454265E+10 | 5396.23 | 19-JUN-12:50 | 4512.94 | 0.00 |
| July | 0.00 | 0.00 | 0.902047E+10 | 0.657694E+10 | 5807.50 | 08-JUL-12:30 | 4228.98 | 0.00 |
| August | 0.00 | 0.00 | 0.872637E+10 | 0.697879E+10 | 6097.45 | 16-AUG-13:00 | 4613.64 | 0.00 |
| September | 0.00 | 0.00 | 0.528813E+10 | 0.447239E+10 | 5651.69 | 07-SEP-13:40 | 4397.11 | 0.00 |
| October | 0.00 | 0.00 | 0.311317E+10 | 0.271409E+10 | 4887.58 | 25-OCT-10:30 | 3704.80 | 0.00 |
| November | 0.00 | 0.00 | 0.283536E+09 | 0.282856E+09 | 2416.04 | 02-NOV-12:50 | 2416.04 | 0.00 |
| December | 0.00 | 0.00 | 4208910.13 | 4208910.13 | 497.77 | 17-DEC-14:20 | 497.77 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.353677E+11 | 0.284545E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.902047E+10 | 0.697879E+10 | 6097.45 | 4613.64 | 0.00 |
Report: CoilReportMonthly
For: SPLIT MS2 COOLING COIL
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 21402339.39 | 20959120.51 | 1100.41 | 03-MAR-14:00 | 1100.41 | 0.00 |
| April | 0.00 | 0.00 | 0.739361E+09 | 0.704905E+09 | 3852.23 | 08-APR-12:00 | 3670.50 | 0.00 |
| May | 0.00 | 0.00 | 0.231655E+10 | 0.216624E+10 | 4034.68 | 31-MAY-14:00 | 3430.21 | 0.00 |
| June | 0.00 | 0.00 | 0.585785E+10 | 0.453751E+10 | 5406.10 | 19-JUN-12:50 | 4522.61 | 0.00 |
| July | 0.00 | 0.00 | 0.901933E+10 | 0.657578E+10 | 5818.90 | 08-JUL-12:30 | 4239.92 | 0.00 |
| August | 0.00 | 0.00 | 0.872581E+10 | 0.697804E+10 | 6097.09 | 16-AUG-13:00 | 4613.77 | 0.00 |
| September | 0.00 | 0.00 | 0.528929E+10 | 0.447345E+10 | 5652.81 | 07-SEP-13:40 | 4398.94 | 0.00 |
| October | 0.00 | 0.00 | 0.311328E+10 | 0.271437E+10 | 4911.62 | 25-OCT-10:30 | 3725.28 | 0.00 |
| November | 0.00 | 0.00 | 0.290154E+09 | 0.289387E+09 | 2441.11 | 02-NOV-12:50 | 2441.11 | 0.00 |
| December | 0.00 | 0.00 | 4398017.23 | 4398017.23 | 511.36 | 17-DEC-14:20 | 511.36 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.353774E+11 | 0.284650E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.901933E+10 | 0.697804E+10 | 6097.09 | 4613.77 | 0.00 |
Report: CoilReportMonthly
For: SPLIT TSW COOLING COIL
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 6395500.20 | 6395500.20 | 703.88 | 17-JAN-15:10 | 703.88 | 0.00 |
| February | 0.00 | 0.00 | 1541350.79 | 1541350.79 | 272.29 | 20-FEB-15:30 | 272.29 | 0.00 |
| March | 0.00 | 0.00 | 0.118275E+09 | 0.116071E+09 | 1617.81 | 27-MAR-16:20 | 1433.41 | 0.00 |
| April | 0.00 | 0.00 | 0.501446E+09 | 0.487073E+09 | 3489.65 | 07-APR-15:20 | 3489.65 | 0.00 |
| May | 0.00 | 0.00 | 0.126144E+10 | 0.121201E+10 | 3767.65 | 31-MAY-14:20 | 3307.87 | 0.00 |
| June | 0.00 | 0.00 | 0.365496E+10 | 0.290723E+10 | 4855.18 | 19-JUN-14:10 | 4240.03 | 0.00 |
| July | 0.00 | 0.00 | 0.588673E+10 | 0.442841E+10 | 4910.46 | 13-JUL-15:10 | 3959.05 | 0.00 |
| August | 0.00 | 0.00 | 0.567498E+10 | 0.464748E+10 | 5191.76 | 02-AUG-15:10 | 4029.46 | 0.00 |
| September | 0.00 | 0.00 | 0.278537E+10 | 0.237993E+10 | 4788.41 | 07-SEP-15:10 | 3829.13 | 0.00 |
| October | 0.00 | 0.00 | 0.118533E+10 | 0.103064E+10 | 3889.39 | 04-OCT-15:20 | 3407.84 | 0.00 |
| November | 0.00 | 0.00 | 61718644.39 | 61703662.31 | 1174.71 | 02-NOV-13:00 | 1174.71 | 0.00 |
| December | 0.00 | 0.00 | 9388507.90 | 9388507.90 | 867.53 | 17-DEC-14:30 | 867.53 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.211476E+11 | 0.172879E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 1541350.79 | 1541350.79 | 272.29 | 272.29 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.588673E+10 | 0.464748E+10 | 5191.76 | 4240.03 | 0.00 |
Report: CoilReportMonthly
For: SPLIT TNW COOLING COIL
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 5985637.52 | 5246182.54 | 858.96 | 27-MAR-16:30 | 745.21 | 0.00 |
| April | 0.00 | 0.00 | 0.201795E+09 | 0.194075E+09 | 2350.82 | 07-APR-16:10 | 2350.82 | 0.00 |
| May | 0.00 | 0.00 | 0.101241E+10 | 0.965537E+09 | 3440.12 | 30-MAY-16:20 | 3368.16 | 0.00 |
| June | 0.00 | 0.00 | 0.346415E+10 | 0.272568E+10 | 4800.30 | 19-JUN-17:10 | 4006.56 | 0.00 |
| July | 0.00 | 0.00 | 0.559531E+10 | 0.416236E+10 | 4631.97 | 06-JUL-16:25 | 3578.50 | 0.00 |
| August | 0.00 | 0.00 | 0.494461E+10 | 0.395667E+10 | 4724.60 | 02-AUG-15:30 | 3579.19 | 0.00 |
| September | 0.00 | 0.00 | 0.196975E+10 | 0.160941E+10 | 3761.39 | 07-SEP-15:30 | 2851.34 | 0.00 |
| October | 0.00 | 0.00 | 0.355348E+09 | 0.284877E+09 | 2482.34 | 04-OCT-15:30 | 2044.26 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.175494E+11 | 0.139039E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.559531E+10 | 0.416236E+10 | 4800.30 | 4006.56 | 0.00 |
Report: CoilReportMonthly
For: SPLIT TSE COOLING COIL
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 3856896.41 | 3856896.41 | 439.12 | 17-JAN-14:00 | 439.12 | 0.00 |
| February | 0.00 | 0.00 | 116920.41 | 116920.41 | 33.14 | 19-FEB-14:20 | 33.14 | 0.00 |
| March | 0.00 | 0.00 | 94884794.21 | 93762728.04 | 1324.86 | 01-MAR-13:40 | 1324.86 | 0.00 |
| April | 0.00 | 0.00 | 0.478120E+09 | 0.464859E+09 | 3216.44 | 07-APR-13:00 | 3216.44 | 0.00 |
| May | 0.00 | 0.00 | 0.125243E+10 | 0.120345E+10 | 3531.13 | 30-MAY-13:00 | 3531.13 | 0.00 |
| June | 0.00 | 0.00 | 0.355332E+10 | 0.282756E+10 | 4807.47 | 19-JUN-12:50 | 4194.45 | 0.00 |
| July | 0.00 | 0.00 | 0.586578E+10 | 0.441091E+10 | 4890.50 | 08-JUL-12:30 | 3820.04 | 0.00 |
| August | 0.00 | 0.00 | 0.564731E+10 | 0.461937E+10 | 4860.48 | 16-AUG-12:50 | 3890.01 | 0.00 |
| September | 0.00 | 0.00 | 0.277652E+10 | 0.237584E+10 | 4317.14 | 07-SEP-13:30 | 3459.82 | 0.00 |
| October | 0.00 | 0.00 | 0.113598E+10 | 0.986628E+09 | 3676.81 | 25-OCT-10:30 | 2837.66 | 0.00 |
| November | 0.00 | 0.00 | 60192006.45 | 60179462.50 | 1288.90 | 02-NOV-13:00 | 1288.90 | 0.00 |
| December | 0.00 | 0.00 | 8086093.43 | 8086093.43 | 710.35 | 17-DEC-13:30 | 710.35 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.208766E+11 | 0.170546E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 116920.41 | 116920.41 | 33.14 | 33.14 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.586578E+10 | 0.461937E+10 | 4890.50 | 4194.45 | 0.00 |
Report: CoilReportMonthly
For: SPLIT TNE COOLING COIL
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 259037.53 | 222191.42 | 188.18 | 27-MAR-16:20 | 159.90 | 0.00 |
| April | 0.00 | 0.00 | 0.173514E+09 | 0.167034E+09 | 1848.27 | 08-APR-12:00 | 1767.82 | 0.00 |
| May | 0.00 | 0.00 | 0.997480E+09 | 0.950272E+09 | 2928.45 | 31-MAY-14:00 | 2516.95 | 0.00 |
| June | 0.00 | 0.00 | 0.336736E+10 | 0.264801E+10 | 4287.21 | 19-JUN-10:40 | 3568.69 | 0.00 |
| July | 0.00 | 0.00 | 0.557857E+10 | 0.414579E+10 | 4300.81 | 08-JUL-12:30 | 3291.13 | 0.00 |
| August | 0.00 | 0.00 | 0.492119E+10 | 0.392996E+10 | 4090.23 | 04-AUG-10:30 | 3055.04 | 0.00 |
| September | 0.00 | 0.00 | 0.194803E+10 | 0.159060E+10 | 3092.06 | 14-SEP-14:00 | 2480.66 | 0.00 |
| October | 0.00 | 0.00 | 0.330493E+09 | 0.262440E+09 | 2005.92 | 25-OCT-10:30 | 1432.57 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.173169E+11 | 0.136943E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.557857E+10 | 0.414579E+10 | 4300.81 | 3568.69 | 0.00 |
Report: CoilReportMonthly
For: SPLIT TN1 COOLING COIL
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 324146.24 | 278392.84 | 172.54 | 27-MAR-16:20 | 146.22 | 0.00 |
| April | 0.00 | 0.00 | 0.107578E+09 | 0.102678E+09 | 1380.71 | 07-APR-16:30 | 1380.71 | 0.00 |
| May | 0.00 | 0.00 | 0.742277E+09 | 0.700172E+09 | 2353.13 | 31-MAY-14:10 | 2001.95 | 0.00 |
| June | 0.00 | 0.00 | 0.286877E+10 | 0.221580E+10 | 3411.03 | 19-JUN-17:10 | 2791.04 | 0.00 |
| July | 0.00 | 0.00 | 0.471581E+10 | 0.345599E+10 | 3368.58 | 08-JUL-12:40 | 2508.57 | 0.00 |
| August | 0.00 | 0.00 | 0.404825E+10 | 0.318690E+10 | 3292.98 | 04-AUG-16:10 | 2456.60 | 0.00 |
| September | 0.00 | 0.00 | 0.164820E+10 | 0.131911E+10 | 2568.19 | 14-SEP-14:00 | 2039.83 | 0.00 |
| October | 0.00 | 0.00 | 0.234035E+09 | 0.182136E+09 | 1478.76 | 04-OCT-16:10 | 1142.83 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.143652E+11 | 0.111631E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.471581E+10 | 0.345599E+10 | 3411.03 | 2791.04 | 0.00 |
Report: CoilReportMonthly
For: SPLIT TN2 COOLING COIL
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 206327.56 | 176663.56 | 107.15 | 27-MAR-16:20 | 90.66 | 0.00 |
| April | 0.00 | 0.00 | 0.108691E+09 | 0.103757E+09 | 1372.25 | 07-APR-16:17 | 1372.25 | 0.00 |
| May | 0.00 | 0.00 | 0.746528E+09 | 0.704296E+09 | 2354.66 | 31-MAY-14:10 | 2004.23 | 0.00 |
| June | 0.00 | 0.00 | 0.286596E+10 | 0.221368E+10 | 3394.36 | 19-JUN-17:10 | 2775.78 | 0.00 |
| July | 0.00 | 0.00 | 0.471553E+10 | 0.345555E+10 | 3380.92 | 08-JUL-12:40 | 2520.59 | 0.00 |
| August | 0.00 | 0.00 | 0.404840E+10 | 0.318685E+10 | 3281.28 | 04-AUG-16:10 | 2446.37 | 0.00 |
| September | 0.00 | 0.00 | 0.165007E+10 | 0.132096E+10 | 2564.74 | 14-SEP-14:00 | 2037.53 | 0.00 |
| October | 0.00 | 0.00 | 0.235797E+09 | 0.183577E+09 | 1461.30 | 04-OCT-16:10 | 1128.54 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.143712E+11 | 0.111689E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.471553E+10 | 0.345555E+10 | 3394.36 | 2775.78 | 0.00 |
Report: CoilReportMonthly
For: SPLIT TS1 COOLING COIL
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 6239437.06 | 6239437.06 | 598.21 | 17-JAN-14:20 | 598.21 | 0.00 |
| February | 0.00 | 0.00 | 1923362.30 | 1923362.30 | 148.77 | 20-FEB-14:10 | 148.77 | 0.00 |
| March | 0.00 | 0.00 | 92625990.44 | 91390088.50 | 1258.77 | 03-MAR-14:00 | 1258.77 | 0.00 |
| April | 0.00 | 0.00 | 0.383601E+09 | 0.371285E+09 | 2702.89 | 07-APR-13:00 | 2702.89 | 0.00 |
| May | 0.00 | 0.00 | 0.986862E+09 | 0.942376E+09 | 2887.70 | 31-MAY-13:50 | 2523.91 | 0.00 |
| June | 0.00 | 0.00 | 0.306095E+10 | 0.239772E+10 | 3878.41 | 19-JUN-13:00 | 3349.03 | 0.00 |
| July | 0.00 | 0.00 | 0.501110E+10 | 0.372423E+10 | 3957.14 | 08-JUL-12:30 | 3036.28 | 0.00 |
| August | 0.00 | 0.00 | 0.478796E+10 | 0.388339E+10 | 4148.20 | 16-AUG-13:00 | 3299.62 | 0.00 |
| September | 0.00 | 0.00 | 0.249039E+10 | 0.211293E+10 | 3777.52 | 07-SEP-13:40 | 3040.29 | 0.00 |
| October | 0.00 | 0.00 | 0.109294E+10 | 0.947043E+09 | 3150.70 | 04-OCT-13:00 | 2833.40 | 0.00 |
| November | 0.00 | 0.00 | 67733119.91 | 67717158.13 | 1299.65 | 02-NOV-13:00 | 1299.65 | 0.00 |
| December | 0.00 | 0.00 | 13297914.95 | 13297914.95 | 880.21 | 17-DEC-14:00 | 880.21 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.179956E+11 | 0.145595E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 1923362.30 | 1923362.30 | 148.77 | 148.77 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.501110E+10 | 0.388339E+10 | 4148.20 | 3349.03 | 0.00 |
Report: CoilReportMonthly
For: SPLIT TS2 COOLING COIL
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 6325273.84 | 6325273.84 | 605.72 | 17-JAN-14:20 | 605.72 | 0.00 |
| February | 0.00 | 0.00 | 2247794.67 | 2247794.67 | 156.40 | 20-FEB-14:10 | 156.40 | 0.00 |
| March | 0.00 | 0.00 | 94668215.98 | 93469010.50 | 1274.25 | 03-MAR-14:00 | 1274.25 | 0.00 |
| April | 0.00 | 0.00 | 0.388084E+09 | 0.375727E+09 | 2723.86 | 07-APR-13:00 | 2723.86 | 0.00 |
| May | 0.00 | 0.00 | 0.991688E+09 | 0.947097E+09 | 2893.25 | 31-MAY-13:40 | 2528.67 | 0.00 |
| June | 0.00 | 0.00 | 0.305811E+10 | 0.239563E+10 | 3890.10 | 19-JUN-13:00 | 3360.65 | 0.00 |
| July | 0.00 | 0.00 | 0.501083E+10 | 0.372383E+10 | 3970.20 | 08-JUL-12:30 | 3049.15 | 0.00 |
| August | 0.00 | 0.00 | 0.478808E+10 | 0.388328E+10 | 4151.61 | 16-AUG-13:00 | 3303.41 | 0.00 |
| September | 0.00 | 0.00 | 0.249251E+10 | 0.211504E+10 | 3778.19 | 07-SEP-13:40 | 3041.68 | 0.00 |
| October | 0.00 | 0.00 | 0.109588E+10 | 0.950040E+09 | 3163.02 | 04-OCT-13:00 | 2845.77 | 0.00 |
| November | 0.00 | 0.00 | 69306301.51 | 69289631.08 | 1318.88 | 02-NOV-13:00 | 1318.88 | 0.00 |
| December | 0.00 | 0.00 | 13699939.16 | 13699939.16 | 892.56 | 17-DEC-13:50 | 892.56 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.180114E+11 | 0.145757E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 2247794.67 | 2247794.67 | 156.40 | 156.40 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.501083E+10 | 0.388328E+10 | 4151.61 | 3360.65 | 0.00 |
Report: FanReportMonthly
For: SPLIT GSW SUPPLY FAN
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.119283E+09 | 0.90 | 102.16 | 02-JAN-00:10 | 0.92 |
| February | 0.109554E+09 | 0.90 | 114.26 | 06-FEB-05:00 | 0.92 |
| March | 65589250.14 | 0.79 | 73.99 | 22-MAR-07:00 | 0.92 |
| April | 30001268.56 | 0.49 | 60.42 | 07-APR-16:10 | 1.05 |
| May | 26158440.89 | 0.32 | 130.08 | 31-MAY-14:10 | 1.02 |
| June | 0.164761E+09 | 0.96 | 204.41 | 19-JUN-17:10 | 0.98 |
| July | 0.298599E+09 | 1.02 | 202.12 | 09-JUL-14:00 | 0.98 |
| August | 0.317016E+09 | 1.02 | 228.66 | 16-AUG-15:10 | 0.97 |
| September | 0.182255E+09 | 0.94 | 211.45 | 07-SEP-15:10 | 0.98 |
| October | 94767608.08 | 0.72 | 170.67 | 04-OCT-15:10 | 1.00 |
| November | 33595442.51 | 0.52 | 64.98 | 23-NOV-02:00 | 0.92 |
| December | 78610448.81 | 0.84 | 85.39 | 31-DEC-22:10 | 0.92 |
| Annual Sum or Average | 0.152019E+10 | 0.79 | |||
| Minimum of Months | 26158440.89 | 0.32 | 60.42 | 0.92 | |
| Maximum of Months | 0.317016E+09 | 1.02 | 228.66 | 1.05 |
Report: FanReportMonthly
For: G SW APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.63 | 20.01 | 01-JAN-00:10 | 0.64 |
| February | 48400714.57 | 0.63 | 20.01 | 01-FEB-00:10 | 0.64 |
| March | 53586505.42 | 0.63 | 20.01 | 01-MAR-00:10 | 0.63 |
| April | 51857908.47 | 0.63 | 20.01 | 01-APR-00:10 | 0.63 |
| May | 53586505.42 | 0.63 | 20.01 | 01-MAY-00:10 | 0.63 |
| June | 51857908.47 | 0.62 | 20.01 | 01-JUN-00:10 | 0.62 |
| July | 53586505.42 | 0.62 | 20.01 | 01-JUL-00:10 | 0.62 |
| August | 53586505.42 | 0.62 | 20.01 | 01-AUG-00:10 | 0.62 |
| September | 51857908.47 | 0.63 | 20.01 | 01-SEP-00:10 | 0.62 |
| October | 53586505.42 | 0.63 | 20.01 | 01-OCT-00:10 | 0.63 |
| November | 51857908.47 | 0.63 | 20.01 | 01-NOV-00:10 | 0.63 |
| December | 53586505.42 | 0.63 | 20.01 | 01-DEC-00:10 | 0.63 |
| Annual Sum or Average | 0.630938E+09 | 0.63 | |||
| Minimum of Months | 48400714.57 | 0.62 | 20.01 | 0.62 | |
| Maximum of Months | 53586505.42 | 0.63 | 20.01 | 0.64 |
Report: FanReportMonthly
For: G SW APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.63 | 20.01 | 01-JAN-00:10 | 0.64 |
| February | 48400714.57 | 0.63 | 20.01 | 01-FEB-00:10 | 0.64 |
| March | 53586505.42 | 0.63 | 20.01 | 01-MAR-00:10 | 0.63 |
| April | 51857908.47 | 0.63 | 20.01 | 01-APR-00:10 | 0.63 |
| May | 53586505.42 | 0.63 | 20.01 | 01-MAY-00:10 | 0.63 |
| June | 51857908.47 | 0.63 | 20.01 | 01-JUN-00:10 | 0.63 |
| July | 53586505.42 | 0.62 | 20.01 | 01-JUL-00:10 | 0.62 |
| August | 53586505.42 | 0.63 | 20.01 | 01-AUG-00:10 | 0.62 |
| September | 51857908.47 | 0.63 | 20.01 | 01-SEP-00:10 | 0.63 |
| October | 53586505.42 | 0.63 | 20.01 | 01-OCT-00:10 | 0.63 |
| November | 51857908.47 | 0.63 | 20.01 | 01-NOV-00:10 | 0.63 |
| December | 53586505.42 | 0.63 | 20.01 | 01-DEC-00:10 | 0.63 |
| Annual Sum or Average | 0.630938E+09 | 0.63 | |||
| Minimum of Months | 48400714.57 | 0.62 | 20.01 | 0.62 | |
| Maximum of Months | 53586505.42 | 0.63 | 20.01 | 0.64 |
Report: FanReportMonthly
For: SPLIT GNW SUPPLY FAN
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.148219E+09 | 0.92 | 113.34 | 02-JAN-00:10 | 0.92 |
| February | 0.147603E+09 | 0.92 | 127.47 | 06-FEB-01:10 | 0.92 |
| March | 93261972.02 | 0.89 | 83.89 | 22-MAR-07:00 | 0.92 |
| April | 36992203.96 | 0.61 | 53.27 | 02-APR-06:00 | 0.92 |
| May | 20003553.64 | 0.28 | 114.51 | 31-MAY-16:20 | 1.02 |
| June | 0.151105E+09 | 0.95 | 198.46 | 19-JUN-17:20 | 0.98 |
| July | 0.278906E+09 | 1.02 | 190.26 | 06-JUL-17:25 | 0.98 |
| August | 0.271076E+09 | 1.02 | 204.44 | 16-AUG-16:07 | 0.98 |
| September | 0.127629E+09 | 0.83 | 166.62 | 07-SEP-16:02 | 1.00 |
| October | 24944303.03 | 0.33 | 107.52 | 04-OCT-16:10 | 1.02 |
| November | 49139362.99 | 0.63 | 75.93 | 23-NOV-02:00 | 0.92 |
| December | 0.110370E+09 | 0.92 | 96.50 | 31-DEC-22:08 | 0.92 |
| Annual Sum or Average | 0.145925E+10 | 0.78 | |||
| Minimum of Months | 20003553.64 | 0.28 | 53.27 | 0.92 | |
| Maximum of Months | 0.278906E+09 | 1.02 | 204.44 | 1.02 |
Report: FanReportMonthly
For: G NW APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.63 | 20.01 | 01-JAN-00:10 | 0.64 |
| February | 48400714.57 | 0.63 | 20.01 | 01-FEB-00:10 | 0.64 |
| March | 53586505.42 | 0.63 | 20.01 | 01-MAR-00:10 | 0.63 |
| April | 51857908.47 | 0.63 | 20.01 | 01-APR-00:10 | 0.63 |
| May | 53586505.42 | 0.63 | 20.01 | 01-MAY-00:10 | 0.63 |
| June | 51857908.47 | 0.62 | 20.01 | 01-JUN-00:10 | 0.62 |
| July | 53586505.42 | 0.62 | 20.01 | 01-JUL-00:10 | 0.62 |
| August | 53586505.42 | 0.62 | 20.01 | 01-AUG-00:10 | 0.62 |
| September | 51857908.47 | 0.63 | 20.01 | 01-SEP-00:10 | 0.62 |
| October | 53586505.42 | 0.63 | 20.01 | 01-OCT-00:10 | 0.63 |
| November | 51857908.47 | 0.63 | 20.01 | 01-NOV-00:10 | 0.63 |
| December | 53586505.42 | 0.63 | 20.01 | 01-DEC-00:10 | 0.63 |
| Annual Sum or Average | 0.630938E+09 | 0.63 | |||
| Minimum of Months | 48400714.57 | 0.62 | 20.01 | 0.62 | |
| Maximum of Months | 53586505.42 | 0.63 | 20.01 | 0.64 |
Report: FanReportMonthly
For: G NW APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.63 | 20.01 | 01-JAN-00:10 | 0.64 |
| February | 48400714.57 | 0.63 | 20.01 | 01-FEB-00:10 | 0.64 |
| March | 53586505.42 | 0.63 | 20.01 | 01-MAR-00:10 | 0.63 |
| April | 51857908.47 | 0.63 | 20.01 | 01-APR-00:10 | 0.63 |
| May | 53586505.42 | 0.63 | 20.01 | 01-MAY-00:10 | 0.63 |
| June | 51857908.47 | 0.63 | 20.01 | 01-JUN-00:10 | 0.62 |
| July | 53586505.42 | 0.62 | 20.01 | 01-JUL-00:10 | 0.62 |
| August | 53586505.42 | 0.63 | 20.01 | 01-AUG-00:10 | 0.62 |
| September | 51857908.47 | 0.63 | 20.01 | 01-SEP-00:10 | 0.62 |
| October | 53586505.42 | 0.63 | 20.01 | 01-OCT-00:10 | 0.63 |
| November | 51857908.47 | 0.63 | 20.01 | 01-NOV-00:10 | 0.63 |
| December | 53586505.42 | 0.63 | 20.01 | 01-DEC-00:10 | 0.63 |
| Annual Sum or Average | 0.630938E+09 | 0.63 | |||
| Minimum of Months | 48400714.57 | 0.62 | 20.01 | 0.62 | |
| Maximum of Months | 53586505.42 | 0.63 | 20.01 | 0.64 |
Report: FanReportMonthly
For: SPLIT OFFICE SUPPLY FAN
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.120728E+10 | 0.92 | 450.75 | 01-JAN-00:10 | 0.93 |
| February | 0.109044E+10 | 0.92 | 450.75 | 01-FEB-00:10 | 0.92 |
| March | 0.120728E+10 | 0.92 | 450.75 | 01-MAR-00:10 | 0.92 |
| April | 0.116833E+10 | 0.92 | 450.75 | 01-APR-00:10 | 0.92 |
| May | 0.120728E+10 | 0.91 | 450.75 | 01-MAY-00:10 | 0.91 |
| June | 0.116833E+10 | 0.91 | 450.75 | 01-JUN-00:10 | 0.91 |
| July | 0.120728E+10 | 0.90 | 450.75 | 01-JUL-00:10 | 0.90 |
| August | 0.120728E+10 | 0.91 | 450.75 | 01-AUG-00:10 | 0.90 |
| September | 0.116833E+10 | 0.91 | 450.75 | 01-SEP-00:10 | 0.90 |
| October | 0.120728E+10 | 0.91 | 450.75 | 01-OCT-00:10 | 0.91 |
| November | 0.116833E+10 | 0.92 | 450.75 | 01-NOV-00:10 | 0.91 |
| December | 0.120728E+10 | 0.92 | 450.75 | 01-DEC-00:10 | 0.92 |
| Annual Sum or Average | 0.142147E+11 | 0.91 | |||
| Minimum of Months | 0.109044E+10 | 0.90 | 450.75 | 0.90 | |
| Maximum of Months | 0.120728E+10 | 0.92 | 450.75 | 0.93 |
Report: FanReportMonthly
For: SPLIT GNE SUPPLY FAN
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.146060E+09 | 0.92 | 110.66 | 02-JAN-00:10 | 0.92 |
| February | 0.144745E+09 | 0.92 | 125.07 | 06-FEB-01:10 | 0.92 |
| March | 93514973.86 | 0.91 | 80.17 | 22-MAR-06:00 | 0.92 |
| April | 36047117.38 | 0.59 | 52.79 | 02-APR-04:00 | 0.92 |
| May | 21392500.32 | 0.29 | 102.39 | 31-MAY-10:10 | 1.02 |
| June | 0.143110E+09 | 0.95 | 172.98 | 19-JUN-11:00 | 0.99 |
| July | 0.272779E+09 | 1.02 | 179.61 | 08-JUL-12:00 | 0.98 |
| August | 0.265286E+09 | 1.02 | 187.05 | 04-AUG-19:00 | 0.98 |
| September | 0.125609E+09 | 0.85 | 138.83 | 14-SEP-14:00 | 1.00 |
| October | 22831951.56 | 0.31 | 95.16 | 25-OCT-10:30 | 1.02 |
| November | 46508300.31 | 0.62 | 73.93 | 23-NOV-02:00 | 0.92 |
| December | 0.108054E+09 | 0.92 | 95.92 | 31-DEC-22:10 | 0.92 |
| Annual Sum or Average | 0.142594E+10 | 0.78 | |||
| Minimum of Months | 21392500.32 | 0.29 | 52.79 | 0.92 | |
| Maximum of Months | 0.272779E+09 | 1.02 | 187.05 | 1.02 |
Report: FanReportMonthly
For: G NE APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.63 | 20.01 | 01-JAN-00:10 | 0.64 |
| February | 48400714.57 | 0.63 | 20.01 | 01-FEB-00:10 | 0.64 |
| March | 53586505.42 | 0.63 | 20.01 | 01-MAR-00:10 | 0.63 |
| April | 51857908.47 | 0.63 | 20.01 | 01-APR-00:10 | 0.63 |
| May | 53586505.42 | 0.63 | 20.01 | 01-MAY-00:10 | 0.63 |
| June | 51857908.47 | 0.62 | 20.01 | 01-JUN-00:10 | 0.62 |
| July | 53586505.42 | 0.62 | 20.01 | 01-JUL-00:10 | 0.62 |
| August | 53586505.42 | 0.62 | 20.01 | 01-AUG-00:10 | 0.62 |
| September | 51857908.47 | 0.63 | 20.01 | 01-SEP-00:10 | 0.62 |
| October | 53586505.42 | 0.63 | 20.01 | 01-OCT-00:10 | 0.63 |
| November | 51857908.47 | 0.63 | 20.01 | 01-NOV-00:10 | 0.63 |
| December | 53586505.42 | 0.63 | 20.01 | 01-DEC-00:10 | 0.63 |
| Annual Sum or Average | 0.630938E+09 | 0.63 | |||
| Minimum of Months | 48400714.57 | 0.62 | 20.01 | 0.62 | |
| Maximum of Months | 53586505.42 | 0.63 | 20.01 | 0.64 |
Report: FanReportMonthly
For: G NE APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.63 | 20.01 | 01-JAN-00:10 | 0.64 |
| February | 48400714.57 | 0.63 | 20.01 | 01-FEB-00:10 | 0.64 |
| March | 53586505.42 | 0.63 | 20.01 | 01-MAR-00:10 | 0.63 |
| April | 51857908.47 | 0.63 | 20.01 | 01-APR-00:10 | 0.63 |
| May | 53586505.42 | 0.63 | 20.01 | 01-MAY-00:10 | 0.63 |
| June | 51857908.47 | 0.63 | 20.01 | 01-JUN-00:10 | 0.62 |
| July | 53586505.42 | 0.62 | 20.01 | 01-JUL-00:10 | 0.62 |
| August | 53586505.42 | 0.63 | 20.01 | 01-AUG-00:10 | 0.62 |
| September | 51857908.47 | 0.63 | 20.01 | 01-SEP-00:10 | 0.62 |
| October | 53586505.42 | 0.63 | 20.01 | 01-OCT-00:10 | 0.63 |
| November | 51857908.47 | 0.63 | 20.01 | 01-NOV-00:10 | 0.63 |
| December | 53586505.42 | 0.63 | 20.01 | 01-DEC-00:10 | 0.63 |
| Annual Sum or Average | 0.630938E+09 | 0.63 | |||
| Minimum of Months | 48400714.57 | 0.62 | 20.01 | 0.62 | |
| Maximum of Months | 53586505.42 | 0.63 | 20.01 | 0.64 |
Report: FanReportMonthly
For: SPLIT GN1 SUPPLY FAN
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.101855E+09 | 0.92 | 79.75 | 02-JAN-00:10 | 0.92 |
| February | 0.103778E+09 | 0.92 | 89.06 | 06-FEB-01:10 | 0.92 |
| March | 63552189.17 | 0.88 | 57.37 | 22-MAR-07:05 | 0.92 |
| April | 20814747.05 | 0.52 | 33.85 | 02-APR-04:00 | 0.92 |
| May | 15252172.52 | 0.21 | 80.21 | 31-MAY-14:10 | 1.03 |
| June | 0.132365E+09 | 1.00 | 146.98 | 19-JUN-17:20 | 0.99 |
| July | 0.238862E+09 | 1.02 | 144.12 | 08-JUL-12:00 | 0.99 |
| August | 0.223355E+09 | 1.02 | 159.85 | 04-AUG-19:00 | 0.98 |
| September | 0.110032E+09 | 0.92 | 117.19 | 14-SEP-14:00 | 1.01 |
| October | 20301956.56 | 0.35 | 70.38 | 04-OCT-16:10 | 1.03 |
| November | 29254040.11 | 0.52 | 51.15 | 23-NOV-02:00 | 0.92 |
| December | 73419323.05 | 0.92 | 65.84 | 31-DEC-22:10 | 0.92 |
| Annual Sum or Average | 0.113284E+10 | 0.77 | |||
| Minimum of Months | 15252172.52 | 0.21 | 33.85 | 0.92 | |
| Maximum of Months | 0.238862E+09 | 1.02 | 159.85 | 1.03 |
Report: FanReportMonthly
For: G N1 APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.63 | 20.01 | 01-JAN-00:10 | 0.64 |
| February | 48400714.57 | 0.63 | 20.01 | 01-FEB-00:10 | 0.64 |
| March | 53586505.42 | 0.63 | 20.01 | 01-MAR-00:10 | 0.63 |
| April | 51857908.47 | 0.63 | 20.01 | 01-APR-00:10 | 0.63 |
| May | 53586505.42 | 0.63 | 20.01 | 01-MAY-00:10 | 0.63 |
| June | 51857908.47 | 0.62 | 20.01 | 01-JUN-00:10 | 0.62 |
| July | 53586505.42 | 0.62 | 20.01 | 01-JUL-00:10 | 0.62 |
| August | 53586505.42 | 0.62 | 20.01 | 01-AUG-00:10 | 0.62 |
| September | 51857908.47 | 0.63 | 20.01 | 01-SEP-00:10 | 0.62 |
| October | 53586505.42 | 0.63 | 20.01 | 01-OCT-00:10 | 0.63 |
| November | 51857908.47 | 0.63 | 20.01 | 01-NOV-00:10 | 0.63 |
| December | 53586505.42 | 0.63 | 20.01 | 01-DEC-00:10 | 0.63 |
| Annual Sum or Average | 0.630938E+09 | 0.63 | |||
| Minimum of Months | 48400714.57 | 0.62 | 20.01 | 0.62 | |
| Maximum of Months | 53586505.42 | 0.63 | 20.01 | 0.64 |
Report: FanReportMonthly
For: G N1 APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.63 | 20.01 | 01-JAN-00:10 | 0.64 |
| February | 48400714.57 | 0.63 | 20.01 | 01-FEB-00:10 | 0.64 |
| March | 53586505.42 | 0.63 | 20.01 | 01-MAR-00:10 | 0.63 |
| April | 51857908.47 | 0.63 | 20.01 | 01-APR-00:10 | 0.63 |
| May | 53586505.42 | 0.63 | 20.01 | 01-MAY-00:10 | 0.63 |
| June | 51857908.47 | 0.63 | 20.01 | 01-JUN-00:10 | 0.62 |
| July | 53586505.42 | 0.62 | 20.01 | 01-JUL-00:10 | 0.62 |
| August | 53586505.42 | 0.63 | 20.01 | 01-AUG-00:10 | 0.62 |
| September | 51857908.47 | 0.63 | 20.01 | 01-SEP-00:10 | 0.62 |
| October | 53586505.42 | 0.63 | 20.01 | 01-OCT-00:10 | 0.63 |
| November | 51857908.47 | 0.63 | 20.01 | 01-NOV-00:10 | 0.63 |
| December | 53586505.42 | 0.63 | 20.01 | 01-DEC-00:10 | 0.63 |
| Annual Sum or Average | 0.630938E+09 | 0.63 | |||
| Minimum of Months | 48400714.57 | 0.62 | 20.01 | 0.62 | |
| Maximum of Months | 53586505.42 | 0.63 | 20.01 | 0.64 |
Report: FanReportMonthly
For: SPLIT GN2 SUPPLY FAN
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.101811E+09 | 0.92 | 79.65 | 02-JAN-00:10 | 0.92 |
| February | 0.103715E+09 | 0.92 | 89.00 | 06-FEB-01:10 | 0.92 |
| March | 63623277.08 | 0.88 | 57.35 | 22-MAR-07:05 | 0.92 |
| April | 20816468.58 | 0.52 | 33.92 | 02-APR-04:00 | 0.92 |
| May | 15456197.45 | 0.21 | 80.62 | 31-MAY-14:10 | 1.03 |
| June | 0.132095E+09 | 1.00 | 146.31 | 19-JUN-17:20 | 0.99 |
| July | 0.238742E+09 | 1.02 | 144.36 | 08-JUL-12:00 | 0.99 |
| August | 0.223269E+09 | 1.02 | 159.75 | 04-AUG-19:00 | 0.98 |
| September | 0.110087E+09 | 0.93 | 117.03 | 14-SEP-14:00 | 1.01 |
| October | 20213303.26 | 0.35 | 70.64 | 25-OCT-11:00 | 1.03 |
| November | 29130174.71 | 0.51 | 51.05 | 23-NOV-02:00 | 0.92 |
| December | 73355553.86 | 0.92 | 65.86 | 31-DEC-22:10 | 0.92 |
| Annual Sum or Average | 0.113231E+10 | 0.77 | |||
| Minimum of Months | 15456197.45 | 0.21 | 33.92 | 0.92 | |
| Maximum of Months | 0.238742E+09 | 1.02 | 159.75 | 1.03 |
Report: FanReportMonthly
For: G N2 APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.63 | 20.01 | 01-JAN-00:10 | 0.64 |
| February | 48400714.57 | 0.63 | 20.01 | 01-FEB-00:10 | 0.64 |
| March | 53586505.42 | 0.63 | 20.01 | 01-MAR-00:10 | 0.63 |
| April | 51857908.47 | 0.63 | 20.01 | 01-APR-00:10 | 0.63 |
| May | 53586505.42 | 0.63 | 20.01 | 01-MAY-00:10 | 0.63 |
| June | 51857908.47 | 0.62 | 20.01 | 01-JUN-00:10 | 0.62 |
| July | 53586505.42 | 0.62 | 20.01 | 01-JUL-00:10 | 0.62 |
| August | 53586505.42 | 0.62 | 20.01 | 01-AUG-00:10 | 0.62 |
| September | 51857908.47 | 0.63 | 20.01 | 01-SEP-00:10 | 0.62 |
| October | 53586505.42 | 0.63 | 20.01 | 01-OCT-00:10 | 0.63 |
| November | 51857908.47 | 0.63 | 20.01 | 01-NOV-00:10 | 0.63 |
| December | 53586505.42 | 0.63 | 20.01 | 01-DEC-00:10 | 0.63 |
| Annual Sum or Average | 0.630938E+09 | 0.63 | |||
| Minimum of Months | 48400714.57 | 0.62 | 20.01 | 0.62 | |
| Maximum of Months | 53586505.42 | 0.63 | 20.01 | 0.64 |
Report: FanReportMonthly
For: G N2 APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.63 | 20.01 | 01-JAN-00:10 | 0.64 |
| February | 48400714.57 | 0.63 | 20.01 | 01-FEB-00:10 | 0.64 |
| March | 53586505.42 | 0.63 | 20.01 | 01-MAR-00:10 | 0.63 |
| April | 51857908.47 | 0.63 | 20.01 | 01-APR-00:10 | 0.63 |
| May | 53586505.42 | 0.63 | 20.01 | 01-MAY-00:10 | 0.63 |
| June | 51857908.47 | 0.63 | 20.01 | 01-JUN-00:10 | 0.62 |
| July | 53586505.42 | 0.62 | 20.01 | 01-JUL-00:10 | 0.62 |
| August | 53586505.42 | 0.63 | 20.01 | 01-AUG-00:10 | 0.62 |
| September | 51857908.47 | 0.63 | 20.01 | 01-SEP-00:10 | 0.62 |
| October | 53586505.42 | 0.63 | 20.01 | 01-OCT-00:10 | 0.63 |
| November | 51857908.47 | 0.63 | 20.01 | 01-NOV-00:10 | 0.63 |
| December | 53586505.42 | 0.63 | 20.01 | 01-DEC-00:10 | 0.63 |
| Annual Sum or Average | 0.630938E+09 | 0.63 | |||
| Minimum of Months | 48400714.57 | 0.62 | 20.01 | 0.62 | |
| Maximum of Months | 53586505.42 | 0.63 | 20.01 | 0.64 |
Report: FanReportMonthly
For: SPLIT GS1 SUPPLY FAN
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 74791493.02 | 0.88 | 68.94 | 02-JAN-00:10 | 0.92 |
| February | 67862907.50 | 0.85 | 76.33 | 06-FEB-05:00 | 0.92 |
| March | 37811636.50 | 0.73 | 48.16 | 22-MAR-07:00 | 0.92 |
| April | 16141829.33 | 0.41 | 53.63 | 08-APR-12:00 | 1.05 |
| May | 21818813.88 | 0.26 | 103.03 | 31-MAY-14:00 | 1.02 |
| June | 0.147192E+09 | 1.01 | 158.89 | 19-JUN-12:00 | 0.99 |
| July | 0.260066E+09 | 1.02 | 168.48 | 08-JUL-12:00 | 0.98 |
| August | 0.270772E+09 | 1.02 | 181.33 | 16-AUG-13:00 | 0.98 |
| September | 0.167496E+09 | 1.01 | 166.00 | 07-SEP-14:10 | 0.99 |
| October | 98246656.00 | 0.85 | 138.60 | 04-OCT-13:00 | 1.00 |
| November | 20669587.80 | 0.48 | 59.03 | 02-NOV-12:50 | 1.05 |
| December | 43980305.18 | 0.74 | 56.73 | 31-DEC-24:00 | 0.92 |
| Annual Sum or Average | 0.122685E+10 | 0.77 | |||
| Minimum of Months | 16141829.33 | 0.26 | 48.16 | 0.92 | |
| Maximum of Months | 0.270772E+09 | 1.02 | 181.33 | 1.05 |
Report: FanReportMonthly
For: G S1 APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.63 | 20.01 | 01-JAN-00:10 | 0.64 |
| February | 48400714.57 | 0.63 | 20.01 | 01-FEB-00:10 | 0.64 |
| March | 53586505.42 | 0.63 | 20.01 | 01-MAR-00:10 | 0.63 |
| April | 51857908.47 | 0.63 | 20.01 | 01-APR-00:10 | 0.63 |
| May | 53586505.42 | 0.63 | 20.01 | 01-MAY-00:10 | 0.63 |
| June | 51857908.47 | 0.62 | 20.01 | 01-JUN-00:10 | 0.62 |
| July | 53586505.42 | 0.62 | 20.01 | 01-JUL-00:10 | 0.62 |
| August | 53586505.42 | 0.62 | 20.01 | 01-AUG-00:10 | 0.62 |
| September | 51857908.47 | 0.63 | 20.01 | 01-SEP-00:10 | 0.62 |
| October | 53586505.42 | 0.63 | 20.01 | 01-OCT-00:10 | 0.63 |
| November | 51857908.47 | 0.63 | 20.01 | 01-NOV-00:10 | 0.63 |
| December | 53586505.42 | 0.63 | 20.01 | 01-DEC-00:10 | 0.63 |
| Annual Sum or Average | 0.630938E+09 | 0.63 | |||
| Minimum of Months | 48400714.57 | 0.62 | 20.01 | 0.62 | |
| Maximum of Months | 53586505.42 | 0.63 | 20.01 | 0.64 |
Report: FanReportMonthly
For: G S1 APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.63 | 20.01 | 01-JAN-00:10 | 0.64 |
| February | 48400714.57 | 0.63 | 20.01 | 01-FEB-00:10 | 0.64 |
| March | 53586505.42 | 0.63 | 20.01 | 01-MAR-00:10 | 0.63 |
| April | 51857908.47 | 0.63 | 20.01 | 01-APR-00:10 | 0.63 |
| May | 53586505.42 | 0.63 | 20.01 | 01-MAY-00:10 | 0.63 |
| June | 51857908.47 | 0.63 | 20.01 | 01-JUN-00:10 | 0.63 |
| July | 53586505.42 | 0.62 | 20.01 | 01-JUL-00:10 | 0.62 |
| August | 53586505.42 | 0.63 | 20.01 | 01-AUG-00:10 | 0.62 |
| September | 51857908.47 | 0.63 | 20.01 | 01-SEP-00:10 | 0.63 |
| October | 53586505.42 | 0.63 | 20.01 | 01-OCT-00:10 | 0.63 |
| November | 51857908.47 | 0.63 | 20.01 | 01-NOV-00:10 | 0.63 |
| December | 53586505.42 | 0.63 | 20.01 | 01-DEC-00:10 | 0.63 |
| Annual Sum or Average | 0.630938E+09 | 0.63 | |||
| Minimum of Months | 48400714.57 | 0.62 | 20.01 | 0.62 | |
| Maximum of Months | 53586505.42 | 0.63 | 20.01 | 0.64 |
Report: FanReportMonthly
For: SPLIT GS2 SUPPLY FAN
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 83924471.98 | 0.89 | 76.51 | 02-JAN-00:10 | 0.92 |
| February | 74951325.16 | 0.87 | 82.95 | 06-FEB-05:00 | 0.92 |
| March | 41622036.50 | 0.75 | 51.10 | 22-MAR-07:00 | 0.92 |
| April | 17381898.33 | 0.42 | 56.71 | 08-APR-12:00 | 1.05 |
| May | 25029256.84 | 0.28 | 108.04 | 31-MAY-14:00 | 1.02 |
| June | 0.161323E+09 | 1.02 | 164.76 | 19-JUN-12:00 | 0.99 |
| July | 0.281683E+09 | 1.02 | 178.37 | 08-JUL-12:00 | 0.98 |
| August | 0.292667E+09 | 1.02 | 187.97 | 16-AUG-13:00 | 0.98 |
| September | 0.183527E+09 | 1.02 | 172.38 | 07-SEP-14:10 | 0.98 |
| October | 0.106705E+09 | 0.87 | 142.81 | 04-OCT-13:00 | 1.00 |
| November | 23286996.24 | 0.51 | 62.78 | 02-NOV-12:50 | 1.05 |
| December | 48528565.72 | 0.77 | 61.85 | 31-DEC-24:00 | 0.92 |
| Annual Sum or Average | 0.134063E+10 | 0.79 | |||
| Minimum of Months | 17381898.33 | 0.28 | 51.10 | 0.92 | |
| Maximum of Months | 0.292667E+09 | 1.02 | 187.97 | 1.05 |
Report: FanReportMonthly
For: G S2 APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.63 | 20.01 | 01-JAN-00:10 | 0.64 |
| February | 48400714.57 | 0.63 | 20.01 | 01-FEB-00:10 | 0.64 |
| March | 53586505.42 | 0.63 | 20.01 | 01-MAR-00:10 | 0.63 |
| April | 51857908.47 | 0.63 | 20.01 | 01-APR-00:10 | 0.63 |
| May | 53586505.42 | 0.63 | 20.01 | 01-MAY-00:10 | 0.63 |
| June | 51857908.47 | 0.62 | 20.01 | 01-JUN-00:10 | 0.62 |
| July | 53586505.42 | 0.62 | 20.01 | 01-JUL-00:10 | 0.62 |
| August | 53586505.42 | 0.62 | 20.01 | 01-AUG-00:10 | 0.62 |
| September | 51857908.47 | 0.63 | 20.01 | 01-SEP-00:10 | 0.62 |
| October | 53586505.42 | 0.63 | 20.01 | 01-OCT-00:10 | 0.63 |
| November | 51857908.47 | 0.63 | 20.01 | 01-NOV-00:10 | 0.63 |
| December | 53586505.42 | 0.63 | 20.01 | 01-DEC-00:10 | 0.63 |
| Annual Sum or Average | 0.630938E+09 | 0.63 | |||
| Minimum of Months | 48400714.57 | 0.62 | 20.01 | 0.62 | |
| Maximum of Months | 53586505.42 | 0.63 | 20.01 | 0.64 |
Report: FanReportMonthly
For: G S2 APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.63 | 20.01 | 01-JAN-00:10 | 0.64 |
| February | 48400714.57 | 0.63 | 20.01 | 01-FEB-00:10 | 0.64 |
| March | 53586505.42 | 0.63 | 20.01 | 01-MAR-00:10 | 0.63 |
| April | 51857908.47 | 0.63 | 20.01 | 01-APR-00:10 | 0.63 |
| May | 53586505.42 | 0.63 | 20.01 | 01-MAY-00:10 | 0.63 |
| June | 51857908.47 | 0.63 | 20.01 | 01-JUN-00:10 | 0.63 |
| July | 53586505.42 | 0.62 | 20.01 | 01-JUL-00:10 | 0.62 |
| August | 53586505.42 | 0.63 | 20.01 | 01-AUG-00:10 | 0.62 |
| September | 51857908.47 | 0.63 | 20.01 | 01-SEP-00:10 | 0.63 |
| October | 53586505.42 | 0.63 | 20.01 | 01-OCT-00:10 | 0.63 |
| November | 51857908.47 | 0.63 | 20.01 | 01-NOV-00:10 | 0.63 |
| December | 53586505.42 | 0.63 | 20.01 | 01-DEC-00:10 | 0.63 |
| Annual Sum or Average | 0.630938E+09 | 0.63 | |||
| Minimum of Months | 48400714.57 | 0.62 | 20.01 | 0.62 | |
| Maximum of Months | 53586505.42 | 0.63 | 20.01 | 0.64 |
Report: FanReportMonthly
For: SPLIT MSW SUPPLY FAN
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.200239E+09 | 0.84 | 206.93 | 02-JAN-00:10 | 0.92 |
| February | 0.164639E+09 | 0.77 | 232.30 | 06-FEB-01:10 | 0.92 |
| March | 64936466.35 | 0.50 | 143.88 | 22-MAR-07:00 | 0.92 |
| April | 77936134.12 | 0.42 | 358.47 | 07-APR-15:30 | 1.01 |
| May | 0.195847E+09 | 0.68 | 389.95 | 30-MAY-16:10 | 1.01 |
| June | 0.499434E+09 | 1.02 | 530.09 | 19-JUN-17:10 | 0.98 |
| July | 0.745490E+09 | 1.02 | 505.80 | 13-JUL-15:10 | 0.98 |
| August | 0.737309E+09 | 1.02 | 543.59 | 16-AUG-15:10 | 0.98 |
| September | 0.414467E+09 | 0.95 | 504.87 | 07-SEP-15:10 | 0.98 |
| October | 0.214844E+09 | 0.68 | 424.88 | 04-OCT-15:20 | 1.00 |
| November | 74547641.72 | 0.51 | 160.92 | 04-NOV-12:30 | 1.05 |
| December | 0.143327E+09 | 0.74 | 186.16 | 31-DEC-22:04 | 0.92 |
| Annual Sum or Average | 0.353302E+10 | 0.76 | |||
| Minimum of Months | 64936466.35 | 0.42 | 143.88 | 0.92 | |
| Maximum of Months | 0.745490E+09 | 1.02 | 543.59 | 1.05 |
Report: FanReportMonthly
For: M SW APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.107173E+09 | 0.63 | 40.01 | 01-JAN-00:10 | 0.64 |
| February | 96801429.15 | 0.63 | 40.01 | 01-FEB-00:10 | 0.64 |
| March | 0.107173E+09 | 0.63 | 40.01 | 01-MAR-00:10 | 0.63 |
| April | 0.103716E+09 | 0.63 | 40.01 | 01-APR-00:10 | 0.63 |
| May | 0.107173E+09 | 0.63 | 40.01 | 01-MAY-00:10 | 0.63 |
| June | 0.103716E+09 | 0.62 | 40.01 | 01-JUN-00:10 | 0.62 |
| July | 0.107173E+09 | 0.62 | 40.01 | 01-JUL-00:10 | 0.62 |
| August | 0.107173E+09 | 0.62 | 40.01 | 01-AUG-00:10 | 0.62 |
| September | 0.103716E+09 | 0.63 | 40.01 | 01-SEP-00:10 | 0.62 |
| October | 0.107173E+09 | 0.63 | 40.01 | 01-OCT-00:10 | 0.63 |
| November | 0.103716E+09 | 0.63 | 40.01 | 01-NOV-00:10 | 0.63 |
| December | 0.107173E+09 | 0.63 | 40.01 | 01-DEC-00:10 | 0.63 |
| Annual Sum or Average | 0.126188E+10 | 0.63 | |||
| Minimum of Months | 96801429.15 | 0.62 | 40.01 | 0.62 | |
| Maximum of Months | 0.107173E+09 | 0.63 | 40.01 | 0.64 |
Report: FanReportMonthly
For: M SW APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.107173E+09 | 0.63 | 40.01 | 01-JAN-00:10 | 0.64 |
| February | 96801429.15 | 0.63 | 40.01 | 01-FEB-00:10 | 0.64 |
| March | 0.107173E+09 | 0.63 | 40.01 | 01-MAR-00:10 | 0.63 |
| April | 0.103716E+09 | 0.63 | 40.01 | 01-APR-00:10 | 0.63 |
| May | 0.107173E+09 | 0.63 | 40.01 | 01-MAY-00:10 | 0.63 |
| June | 0.103716E+09 | 0.63 | 40.01 | 01-JUN-00:10 | 0.63 |
| July | 0.107173E+09 | 0.62 | 40.01 | 01-JUL-00:10 | 0.62 |
| August | 0.107173E+09 | 0.63 | 40.01 | 01-AUG-00:10 | 0.62 |
| September | 0.103716E+09 | 0.63 | 40.01 | 01-SEP-00:10 | 0.63 |
| October | 0.107173E+09 | 0.63 | 40.01 | 01-OCT-00:10 | 0.63 |
| November | 0.103716E+09 | 0.63 | 40.01 | 01-NOV-00:10 | 0.63 |
| December | 0.107173E+09 | 0.63 | 40.01 | 01-DEC-00:10 | 0.63 |
| Annual Sum or Average | 0.126188E+10 | 0.63 | |||
| Minimum of Months | 96801429.15 | 0.62 | 40.01 | 0.62 | |
| Maximum of Months | 0.107173E+09 | 0.63 | 40.01 | 0.64 |
Report: FanReportMonthly
For: SPLIT MNW SUPPLY FAN
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.260697E+09 | 0.92 | 229.57 | 02-JAN-00:10 | 0.92 |
| February | 0.240318E+09 | 0.92 | 259.11 | 06-FEB-01:00 | 0.92 |
| March | 0.114104E+09 | 0.74 | 158.71 | 22-MAR-07:00 | 0.92 |
| April | 47504449.98 | 0.38 | 193.83 | 07-APR-16:17 | 1.04 |
| May | 0.158616E+09 | 0.64 | 363.71 | 30-MAY-16:20 | 1.01 |
| June | 0.471768E+09 | 1.02 | 520.43 | 19-JUN-17:20 | 0.98 |
| July | 0.704285E+09 | 1.02 | 485.29 | 06-JUL-17:13 | 0.98 |
| August | 0.639051E+09 | 1.02 | 490.14 | 16-AUG-16:05 | 0.98 |
| September | 0.295039E+09 | 0.86 | 398.53 | 07-SEP-16:02 | 1.00 |
| October | 65486347.18 | 0.37 | 272.50 | 04-OCT-16:10 | 1.02 |
| November | 0.104764E+09 | 0.64 | 174.84 | 23-NOV-02:00 | 0.92 |
| December | 0.209554E+09 | 0.92 | 208.76 | 31-DEC-22:08 | 0.92 |
| Annual Sum or Average | 0.331119E+10 | 0.79 | |||
| Minimum of Months | 47504449.98 | 0.37 | 158.71 | 0.92 | |
| Maximum of Months | 0.704285E+09 | 1.02 | 520.43 | 1.04 |
Report: FanReportMonthly
For: M NW APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.107173E+09 | 0.63 | 40.01 | 01-JAN-00:10 | 0.64 |
| February | 96801429.15 | 0.63 | 40.01 | 01-FEB-00:10 | 0.64 |
| March | 0.107173E+09 | 0.63 | 40.01 | 01-MAR-00:10 | 0.63 |
| April | 0.103716E+09 | 0.63 | 40.01 | 01-APR-00:10 | 0.63 |
| May | 0.107173E+09 | 0.63 | 40.01 | 01-MAY-00:10 | 0.63 |
| June | 0.103716E+09 | 0.62 | 40.01 | 01-JUN-00:10 | 0.62 |
| July | 0.107173E+09 | 0.62 | 40.01 | 01-JUL-00:10 | 0.62 |
| August | 0.107173E+09 | 0.62 | 40.01 | 01-AUG-00:10 | 0.62 |
| September | 0.103716E+09 | 0.63 | 40.01 | 01-SEP-00:10 | 0.62 |
| October | 0.107173E+09 | 0.63 | 40.01 | 01-OCT-00:10 | 0.63 |
| November | 0.103716E+09 | 0.63 | 40.01 | 01-NOV-00:10 | 0.63 |
| December | 0.107173E+09 | 0.63 | 40.01 | 01-DEC-00:10 | 0.63 |
| Annual Sum or Average | 0.126188E+10 | 0.63 | |||
| Minimum of Months | 96801429.15 | 0.62 | 40.01 | 0.62 | |
| Maximum of Months | 0.107173E+09 | 0.63 | 40.01 | 0.64 |
Report: FanReportMonthly
For: M NW APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.107173E+09 | 0.63 | 40.01 | 01-JAN-00:10 | 0.64 |
| February | 96801429.15 | 0.63 | 40.01 | 01-FEB-00:10 | 0.64 |
| March | 0.107173E+09 | 0.63 | 40.01 | 01-MAR-00:10 | 0.63 |
| April | 0.103716E+09 | 0.63 | 40.01 | 01-APR-00:10 | 0.63 |
| May | 0.107173E+09 | 0.63 | 40.01 | 01-MAY-00:10 | 0.63 |
| June | 0.103716E+09 | 0.63 | 40.01 | 01-JUN-00:10 | 0.63 |
| July | 0.107173E+09 | 0.62 | 40.01 | 01-JUL-00:10 | 0.62 |
| August | 0.107173E+09 | 0.63 | 40.01 | 01-AUG-00:10 | 0.62 |
| September | 0.103716E+09 | 0.63 | 40.01 | 01-SEP-00:10 | 0.62 |
| October | 0.107173E+09 | 0.63 | 40.01 | 01-OCT-00:10 | 0.63 |
| November | 0.103716E+09 | 0.63 | 40.01 | 01-NOV-00:10 | 0.63 |
| December | 0.107173E+09 | 0.63 | 40.01 | 01-DEC-00:10 | 0.63 |
| Annual Sum or Average | 0.126188E+10 | 0.63 | |||
| Minimum of Months | 96801429.15 | 0.62 | 40.01 | 0.62 | |
| Maximum of Months | 0.107173E+09 | 0.63 | 40.01 | 0.64 |
Report: FanReportMonthly
For: SPLIT MSE SUPPLY FAN
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.196712E+09 | 0.84 | 202.04 | 02-JAN-00:10 | 0.92 |
| February | 0.159991E+09 | 0.77 | 228.27 | 06-FEB-01:10 | 0.92 |
| March | 64640758.18 | 0.50 | 140.92 | 22-MAR-06:00 | 0.92 |
| April | 76427297.86 | 0.43 | 332.58 | 08-APR-12:00 | 1.01 |
| May | 0.196416E+09 | 0.71 | 367.87 | 29-MAY-12:00 | 1.00 |
| June | 0.479646E+09 | 1.03 | 497.67 | 19-JUN-12:00 | 0.98 |
| July | 0.730039E+09 | 1.02 | 495.76 | 08-JUL-12:00 | 0.98 |
| August | 0.721941E+09 | 1.02 | 494.10 | 16-AUG-13:00 | 0.98 |
| September | 0.408834E+09 | 0.96 | 442.74 | 07-SEP-13:40 | 0.99 |
| October | 0.207083E+09 | 0.69 | 401.56 | 25-OCT-10:30 | 0.99 |
| November | 72081435.41 | 0.51 | 172.34 | 04-NOV-12:30 | 1.04 |
| December | 0.139513E+09 | 0.74 | 185.16 | 31-DEC-22:06 | 0.92 |
| Annual Sum or Average | 0.345332E+10 | 0.77 | |||
| Minimum of Months | 64640758.18 | 0.43 | 140.92 | 0.92 | |
| Maximum of Months | 0.730039E+09 | 1.03 | 497.67 | 1.04 |
Report: FanReportMonthly
For: M SE APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.107173E+09 | 0.63 | 40.01 | 01-JAN-00:10 | 0.64 |
| February | 96801429.15 | 0.63 | 40.01 | 01-FEB-00:10 | 0.64 |
| March | 0.107173E+09 | 0.63 | 40.01 | 01-MAR-00:10 | 0.63 |
| April | 0.103716E+09 | 0.63 | 40.01 | 01-APR-00:10 | 0.63 |
| May | 0.107173E+09 | 0.63 | 40.01 | 01-MAY-00:10 | 0.63 |
| June | 0.103716E+09 | 0.62 | 40.01 | 01-JUN-00:10 | 0.62 |
| July | 0.107173E+09 | 0.62 | 40.01 | 01-JUL-00:10 | 0.62 |
| August | 0.107173E+09 | 0.62 | 40.01 | 01-AUG-00:10 | 0.62 |
| September | 0.103716E+09 | 0.63 | 40.01 | 01-SEP-00:10 | 0.62 |
| October | 0.107173E+09 | 0.63 | 40.01 | 01-OCT-00:10 | 0.63 |
| November | 0.103716E+09 | 0.63 | 40.01 | 01-NOV-00:10 | 0.63 |
| December | 0.107173E+09 | 0.63 | 40.01 | 01-DEC-00:10 | 0.63 |
| Annual Sum or Average | 0.126188E+10 | 0.63 | |||
| Minimum of Months | 96801429.15 | 0.62 | 40.01 | 0.62 | |
| Maximum of Months | 0.107173E+09 | 0.63 | 40.01 | 0.64 |
Report: FanReportMonthly
For: M SE APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.107173E+09 | 0.63 | 40.01 | 01-JAN-00:10 | 0.64 |
| February | 96801429.15 | 0.63 | 40.01 | 01-FEB-00:10 | 0.64 |
| March | 0.107173E+09 | 0.63 | 40.01 | 01-MAR-00:10 | 0.63 |
| April | 0.103716E+09 | 0.63 | 40.01 | 01-APR-00:10 | 0.63 |
| May | 0.107173E+09 | 0.63 | 40.01 | 01-MAY-00:10 | 0.63 |
| June | 0.103716E+09 | 0.63 | 40.01 | 01-JUN-00:10 | 0.63 |
| July | 0.107173E+09 | 0.62 | 40.01 | 01-JUL-00:10 | 0.62 |
| August | 0.107173E+09 | 0.63 | 40.01 | 01-AUG-00:10 | 0.62 |
| September | 0.103716E+09 | 0.63 | 40.01 | 01-SEP-00:10 | 0.63 |
| October | 0.107173E+09 | 0.63 | 40.01 | 01-OCT-00:10 | 0.63 |
| November | 0.103716E+09 | 0.63 | 40.01 | 01-NOV-00:10 | 0.63 |
| December | 0.107173E+09 | 0.63 | 40.01 | 01-DEC-00:10 | 0.63 |
| Annual Sum or Average | 0.126188E+10 | 0.63 | |||
| Minimum of Months | 96801429.15 | 0.62 | 40.01 | 0.62 | |
| Maximum of Months | 0.107173E+09 | 0.63 | 40.01 | 0.64 |
Report: FanReportMonthly
For: SPLIT MNE SUPPLY FAN
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.256706E+09 | 0.92 | 224.47 | 02-JAN-00:10 | 0.92 |
| February | 0.234998E+09 | 0.92 | 254.11 | 06-FEB-01:00 | 0.92 |
| March | 0.114885E+09 | 0.73 | 153.12 | 22-MAR-06:00 | 0.92 |
| April | 46016819.81 | 0.38 | 187.25 | 08-APR-10:00 | 1.04 |
| May | 0.159009E+09 | 0.66 | 311.20 | 31-MAY-09:50 | 1.01 |
| June | 0.452008E+09 | 1.02 | 451.31 | 19-JUN-10:50 | 0.98 |
| July | 0.688927E+09 | 1.02 | 436.34 | 08-JUL-12:00 | 0.98 |
| August | 0.625071E+09 | 1.02 | 427.24 | 04-AUG-19:00 | 0.98 |
| September | 0.290562E+09 | 0.89 | 322.54 | 14-SEP-14:00 | 1.01 |
| October | 60030238.82 | 0.35 | 234.14 | 25-OCT-10:30 | 1.02 |
| November | 98919807.98 | 0.62 | 171.13 | 23-NOV-02:00 | 0.92 |
| December | 0.204828E+09 | 0.92 | 207.93 | 31-DEC-22:08 | 0.92 |
| Annual Sum or Average | 0.323196E+10 | 0.79 | |||
| Minimum of Months | 46016819.81 | 0.35 | 153.12 | 0.92 | |
| Maximum of Months | 0.688927E+09 | 1.02 | 451.31 | 1.04 |
Report: FanReportMonthly
For: M NE APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.107173E+09 | 0.63 | 40.01 | 01-JAN-00:10 | 0.64 |
| February | 96801429.15 | 0.63 | 40.01 | 01-FEB-00:10 | 0.64 |
| March | 0.107173E+09 | 0.63 | 40.01 | 01-MAR-00:10 | 0.63 |
| April | 0.103716E+09 | 0.63 | 40.01 | 01-APR-00:10 | 0.63 |
| May | 0.107173E+09 | 0.63 | 40.01 | 01-MAY-00:10 | 0.63 |
| June | 0.103716E+09 | 0.62 | 40.01 | 01-JUN-00:10 | 0.62 |
| July | 0.107173E+09 | 0.62 | 40.01 | 01-JUL-00:10 | 0.62 |
| August | 0.107173E+09 | 0.62 | 40.01 | 01-AUG-00:10 | 0.62 |
| September | 0.103716E+09 | 0.63 | 40.01 | 01-SEP-00:10 | 0.62 |
| October | 0.107173E+09 | 0.63 | 40.01 | 01-OCT-00:10 | 0.63 |
| November | 0.103716E+09 | 0.63 | 40.01 | 01-NOV-00:10 | 0.63 |
| December | 0.107173E+09 | 0.63 | 40.01 | 01-DEC-00:10 | 0.63 |
| Annual Sum or Average | 0.126188E+10 | 0.63 | |||
| Minimum of Months | 96801429.15 | 0.62 | 40.01 | 0.62 | |
| Maximum of Months | 0.107173E+09 | 0.63 | 40.01 | 0.64 |
Report: FanReportMonthly
For: M NE APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.107173E+09 | 0.63 | 40.01 | 01-JAN-00:10 | 0.64 |
| February | 96801429.15 | 0.63 | 40.01 | 01-FEB-00:10 | 0.64 |
| March | 0.107173E+09 | 0.63 | 40.01 | 01-MAR-00:10 | 0.63 |
| April | 0.103716E+09 | 0.63 | 40.01 | 01-APR-00:10 | 0.63 |
| May | 0.107173E+09 | 0.63 | 40.01 | 01-MAY-00:10 | 0.63 |
| June | 0.103716E+09 | 0.63 | 40.01 | 01-JUN-00:10 | 0.63 |
| July | 0.107173E+09 | 0.62 | 40.01 | 01-JUL-00:10 | 0.62 |
| August | 0.107173E+09 | 0.63 | 40.01 | 01-AUG-00:10 | 0.62 |
| September | 0.103716E+09 | 0.63 | 40.01 | 01-SEP-00:10 | 0.62 |
| October | 0.107173E+09 | 0.63 | 40.01 | 01-OCT-00:10 | 0.63 |
| November | 0.103716E+09 | 0.63 | 40.01 | 01-NOV-00:10 | 0.63 |
| December | 0.107173E+09 | 0.63 | 40.01 | 01-DEC-00:10 | 0.63 |
| Annual Sum or Average | 0.126188E+10 | 0.63 | |||
| Minimum of Months | 96801429.15 | 0.62 | 40.01 | 0.62 | |
| Maximum of Months | 0.107173E+09 | 0.63 | 40.01 | 0.64 |
Report: FanReportMonthly
For: SPLIT MN1 SUPPLY FAN
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.162648E+09 | 0.91 | 151.49 | 02-JAN-00:10 | 0.92 |
| February | 0.155181E+09 | 0.92 | 171.10 | 06-FEB-01:10 | 0.92 |
| March | 66043122.89 | 0.64 | 100.40 | 22-MAR-07:00 | 0.92 |
| April | 23272010.94 | 0.28 | 116.25 | 08-APR-12:00 | 1.05 |
| May | 0.131405E+09 | 0.77 | 228.31 | 31-MAY-14:10 | 1.02 |
| June | 0.379975E+09 | 1.03 | 361.44 | 19-JUN-17:20 | 0.99 |
| July | 0.573798E+09 | 1.02 | 335.73 | 20-JUL-17:10 | 0.99 |
| August | 0.507521E+09 | 1.03 | 358.10 | 04-AUG-19:00 | 0.99 |
| September | 0.251332E+09 | 0.96 | 264.92 | 14-SEP-14:10 | 1.01 |
| October | 55715413.90 | 0.40 | 166.97 | 04-OCT-16:10 | 1.03 |
| November | 53802293.91 | 0.49 | 110.93 | 23-NOV-02:00 | 0.92 |
| December | 0.124864E+09 | 0.91 | 133.00 | 31-DEC-22:08 | 0.92 |
| Annual Sum or Average | 0.248556E+10 | 0.78 | |||
| Minimum of Months | 23272010.94 | 0.28 | 100.40 | 0.92 | |
| Maximum of Months | 0.573798E+09 | 1.03 | 361.44 | 1.05 |
Report: FanReportMonthly
For: M N1 APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.107173E+09 | 0.63 | 40.01 | 01-JAN-00:10 | 0.64 |
| February | 96801429.15 | 0.63 | 40.01 | 01-FEB-00:10 | 0.64 |
| March | 0.107173E+09 | 0.63 | 40.01 | 01-MAR-00:10 | 0.63 |
| April | 0.103716E+09 | 0.63 | 40.01 | 01-APR-00:10 | 0.63 |
| May | 0.107173E+09 | 0.63 | 40.01 | 01-MAY-00:10 | 0.63 |
| June | 0.103716E+09 | 0.62 | 40.01 | 01-JUN-00:10 | 0.62 |
| July | 0.107173E+09 | 0.62 | 40.01 | 01-JUL-00:10 | 0.62 |
| August | 0.107173E+09 | 0.62 | 40.01 | 01-AUG-00:10 | 0.62 |
| September | 0.103716E+09 | 0.63 | 40.01 | 01-SEP-00:10 | 0.62 |
| October | 0.107173E+09 | 0.63 | 40.01 | 01-OCT-00:10 | 0.63 |
| November | 0.103716E+09 | 0.63 | 40.01 | 01-NOV-00:10 | 0.63 |
| December | 0.107173E+09 | 0.63 | 40.01 | 01-DEC-00:10 | 0.63 |
| Annual Sum or Average | 0.126188E+10 | 0.63 | |||
| Minimum of Months | 96801429.15 | 0.62 | 40.01 | 0.62 | |
| Maximum of Months | 0.107173E+09 | 0.63 | 40.01 | 0.64 |
Report: FanReportMonthly
For: M N1 APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.107173E+09 | 0.63 | 40.01 | 01-JAN-00:10 | 0.64 |
| February | 96801429.15 | 0.63 | 40.01 | 01-FEB-00:10 | 0.64 |
| March | 0.107173E+09 | 0.63 | 40.01 | 01-MAR-00:10 | 0.63 |
| April | 0.103716E+09 | 0.63 | 40.01 | 01-APR-00:10 | 0.63 |
| May | 0.107173E+09 | 0.63 | 40.01 | 01-MAY-00:10 | 0.63 |
| June | 0.103716E+09 | 0.63 | 40.01 | 01-JUN-00:10 | 0.63 |
| July | 0.107173E+09 | 0.62 | 40.01 | 01-JUL-00:10 | 0.62 |
| August | 0.107173E+09 | 0.63 | 40.01 | 01-AUG-00:10 | 0.62 |
| September | 0.103716E+09 | 0.63 | 40.01 | 01-SEP-00:10 | 0.62 |
| October | 0.107173E+09 | 0.63 | 40.01 | 01-OCT-00:10 | 0.63 |
| November | 0.103716E+09 | 0.63 | 40.01 | 01-NOV-00:10 | 0.63 |
| December | 0.107173E+09 | 0.63 | 40.01 | 01-DEC-00:10 | 0.63 |
| Annual Sum or Average | 0.126188E+10 | 0.63 | |||
| Minimum of Months | 96801429.15 | 0.62 | 40.01 | 0.62 | |
| Maximum of Months | 0.107173E+09 | 0.63 | 40.01 | 0.64 |
Report: FanReportMonthly
For: SPLIT MN2 SUPPLY FAN
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.162542E+09 | 0.91 | 151.27 | 02-JAN-00:10 | 0.92 |
| February | 0.155014E+09 | 0.92 | 170.91 | 06-FEB-01:10 | 0.92 |
| March | 66205940.47 | 0.64 | 100.35 | 22-MAR-07:00 | 0.92 |
| April | 23522743.73 | 0.28 | 118.82 | 08-APR-12:00 | 1.05 |
| May | 0.131615E+09 | 0.77 | 228.65 | 31-MAY-14:10 | 1.02 |
| June | 0.379400E+09 | 1.03 | 360.12 | 19-JUN-17:20 | 0.99 |
| July | 0.573480E+09 | 1.02 | 335.13 | 08-JUL-12:00 | 0.99 |
| August | 0.507273E+09 | 1.03 | 357.68 | 04-AUG-19:00 | 0.99 |
| September | 0.251416E+09 | 0.96 | 264.45 | 14-SEP-14:10 | 1.01 |
| October | 55593515.53 | 0.40 | 167.22 | 25-OCT-11:00 | 1.03 |
| November | 53552444.81 | 0.49 | 110.74 | 23-NOV-02:00 | 0.92 |
| December | 0.124708E+09 | 0.91 | 133.00 | 31-DEC-22:08 | 0.92 |
| Annual Sum or Average | 0.248432E+10 | 0.78 | |||
| Minimum of Months | 23522743.73 | 0.28 | 100.35 | 0.92 | |
| Maximum of Months | 0.573480E+09 | 1.03 | 360.12 | 1.05 |
Report: FanReportMonthly
For: M N2 APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.107173E+09 | 0.63 | 40.01 | 01-JAN-00:10 | 0.64 |
| February | 96801429.15 | 0.63 | 40.01 | 01-FEB-00:10 | 0.64 |
| March | 0.107173E+09 | 0.63 | 40.01 | 01-MAR-00:10 | 0.63 |
| April | 0.103716E+09 | 0.63 | 40.01 | 01-APR-00:10 | 0.63 |
| May | 0.107173E+09 | 0.63 | 40.01 | 01-MAY-00:10 | 0.63 |
| June | 0.103716E+09 | 0.62 | 40.01 | 01-JUN-00:10 | 0.62 |
| July | 0.107173E+09 | 0.62 | 40.01 | 01-JUL-00:10 | 0.62 |
| August | 0.107173E+09 | 0.62 | 40.01 | 01-AUG-00:10 | 0.62 |
| September | 0.103716E+09 | 0.63 | 40.01 | 01-SEP-00:10 | 0.62 |
| October | 0.107173E+09 | 0.63 | 40.01 | 01-OCT-00:10 | 0.63 |
| November | 0.103716E+09 | 0.63 | 40.01 | 01-NOV-00:10 | 0.63 |
| December | 0.107173E+09 | 0.63 | 40.01 | 01-DEC-00:10 | 0.63 |
| Annual Sum or Average | 0.126188E+10 | 0.63 | |||
| Minimum of Months | 96801429.15 | 0.62 | 40.01 | 0.62 | |
| Maximum of Months | 0.107173E+09 | 0.63 | 40.01 | 0.64 |
Report: FanReportMonthly
For: M N2 APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.107173E+09 | 0.63 | 40.01 | 01-JAN-00:10 | 0.64 |
| February | 96801429.15 | 0.63 | 40.01 | 01-FEB-00:10 | 0.64 |
| March | 0.107173E+09 | 0.63 | 40.01 | 01-MAR-00:10 | 0.63 |
| April | 0.103716E+09 | 0.63 | 40.01 | 01-APR-00:10 | 0.63 |
| May | 0.107173E+09 | 0.63 | 40.01 | 01-MAY-00:10 | 0.63 |
| June | 0.103716E+09 | 0.63 | 40.01 | 01-JUN-00:10 | 0.63 |
| July | 0.107173E+09 | 0.62 | 40.01 | 01-JUL-00:10 | 0.62 |
| August | 0.107173E+09 | 0.63 | 40.01 | 01-AUG-00:10 | 0.62 |
| September | 0.103716E+09 | 0.63 | 40.01 | 01-SEP-00:10 | 0.62 |
| October | 0.107173E+09 | 0.63 | 40.01 | 01-OCT-00:10 | 0.63 |
| November | 0.103716E+09 | 0.63 | 40.01 | 01-NOV-00:10 | 0.63 |
| December | 0.107173E+09 | 0.63 | 40.01 | 01-DEC-00:10 | 0.63 |
| Annual Sum or Average | 0.126188E+10 | 0.63 | |||
| Minimum of Months | 96801429.15 | 0.62 | 40.01 | 0.62 | |
| Maximum of Months | 0.107173E+09 | 0.63 | 40.01 | 0.64 |
Report: FanReportMonthly
For: SPLIT MS1 SUPPLY FAN
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.105873E+09 | 0.71 | 133.54 | 02-JAN-00:10 | 0.92 |
| February | 83113162.15 | 0.63 | 150.90 | 06-FEB-01:10 | 0.92 |
| March | 26055467.11 | 0.30 | 83.11 | 03-MAR-14:00 | 1.06 |
| April | 59458656.78 | 0.40 | 272.67 | 08-APR-12:00 | 1.02 |
| May | 0.169971E+09 | 0.83 | 283.15 | 30-MAY-13:00 | 1.02 |
| June | 0.408787E+09 | 1.03 | 390.57 | 19-JUN-12:00 | 0.99 |
| July | 0.616593E+09 | 1.02 | 394.98 | 08-JUL-12:00 | 0.99 |
| August | 0.607078E+09 | 1.02 | 416.78 | 16-AUG-13:00 | 0.98 |
| September | 0.373579E+09 | 1.02 | 381.27 | 07-SEP-13:40 | 0.99 |
| October | 0.223671E+09 | 0.81 | 337.85 | 04-OCT-13:00 | 1.00 |
| November | 44476303.83 | 0.44 | 183.16 | 02-NOV-12:50 | 1.04 |
| December | 66045474.89 | 0.58 | 115.18 | 31-DEC-24:00 | 0.92 |
| Annual Sum or Average | 0.278470E+10 | 0.73 | |||
| Minimum of Months | 26055467.11 | 0.30 | 83.11 | 0.92 | |
| Maximum of Months | 0.616593E+09 | 1.03 | 416.78 | 1.06 |
Report: FanReportMonthly
For: M S1 APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.107173E+09 | 0.63 | 40.01 | 01-JAN-00:10 | 0.64 |
| February | 96801429.15 | 0.63 | 40.01 | 01-FEB-00:10 | 0.64 |
| March | 0.107173E+09 | 0.63 | 40.01 | 01-MAR-00:10 | 0.63 |
| April | 0.103716E+09 | 0.63 | 40.01 | 01-APR-00:10 | 0.63 |
| May | 0.107173E+09 | 0.63 | 40.01 | 01-MAY-00:10 | 0.63 |
| June | 0.103716E+09 | 0.62 | 40.01 | 01-JUN-00:10 | 0.62 |
| July | 0.107173E+09 | 0.62 | 40.01 | 01-JUL-00:10 | 0.62 |
| August | 0.107173E+09 | 0.62 | 40.01 | 01-AUG-00:10 | 0.62 |
| September | 0.103716E+09 | 0.63 | 40.01 | 01-SEP-00:10 | 0.62 |
| October | 0.107173E+09 | 0.63 | 40.01 | 01-OCT-00:10 | 0.63 |
| November | 0.103716E+09 | 0.63 | 40.01 | 01-NOV-00:10 | 0.63 |
| December | 0.107173E+09 | 0.63 | 40.01 | 01-DEC-00:10 | 0.63 |
| Annual Sum or Average | 0.126188E+10 | 0.63 | |||
| Minimum of Months | 96801429.15 | 0.62 | 40.01 | 0.62 | |
| Maximum of Months | 0.107173E+09 | 0.63 | 40.01 | 0.64 |
Report: FanReportMonthly
For: M S1 APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.107173E+09 | 0.63 | 40.01 | 01-JAN-00:10 | 0.64 |
| February | 96801429.15 | 0.63 | 40.01 | 01-FEB-00:10 | 0.64 |
| March | 0.107173E+09 | 0.63 | 40.01 | 01-MAR-00:10 | 0.63 |
| April | 0.103716E+09 | 0.63 | 40.01 | 01-APR-00:10 | 0.63 |
| May | 0.107173E+09 | 0.63 | 40.01 | 01-MAY-00:10 | 0.63 |
| June | 0.103716E+09 | 0.63 | 40.01 | 01-JUN-00:10 | 0.63 |
| July | 0.107173E+09 | 0.62 | 40.01 | 01-JUL-00:10 | 0.62 |
| August | 0.107173E+09 | 0.63 | 40.01 | 01-AUG-00:10 | 0.62 |
| September | 0.103716E+09 | 0.63 | 40.01 | 01-SEP-00:10 | 0.63 |
| October | 0.107173E+09 | 0.63 | 40.01 | 01-OCT-00:10 | 0.63 |
| November | 0.103716E+09 | 0.63 | 40.01 | 01-NOV-00:10 | 0.63 |
| December | 0.107173E+09 | 0.63 | 40.01 | 01-DEC-00:10 | 0.63 |
| Annual Sum or Average | 0.126188E+10 | 0.63 | |||
| Minimum of Months | 96801429.15 | 0.62 | 40.01 | 0.62 | |
| Maximum of Months | 0.107173E+09 | 0.63 | 40.01 | 0.64 |
Report: FanReportMonthly
For: SPLIT MS2 SUPPLY FAN
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.105783E+09 | 0.71 | 133.34 | 02-JAN-00:10 | 0.92 |
| February | 83029072.31 | 0.63 | 150.76 | 06-FEB-01:10 | 0.92 |
| March | 26137829.86 | 0.30 | 84.58 | 03-MAR-14:00 | 1.06 |
| April | 59904096.88 | 0.40 | 274.07 | 08-APR-12:00 | 1.02 |
| May | 0.170178E+09 | 0.83 | 284.43 | 30-MAY-13:00 | 1.01 |
| June | 0.408195E+09 | 1.03 | 391.31 | 19-JUN-12:00 | 0.99 |
| July | 0.616246E+09 | 1.02 | 395.68 | 08-JUL-12:00 | 0.99 |
| August | 0.606767E+09 | 1.02 | 416.56 | 16-AUG-13:00 | 0.98 |
| September | 0.373500E+09 | 1.02 | 381.17 | 07-SEP-13:40 | 0.99 |
| October | 0.223587E+09 | 0.81 | 338.47 | 04-OCT-13:00 | 1.00 |
| November | 44795806.51 | 0.44 | 184.92 | 02-NOV-12:50 | 1.04 |
| December | 65951556.60 | 0.58 | 115.16 | 31-DEC-24:00 | 0.92 |
| Annual Sum or Average | 0.278407E+10 | 0.73 | |||
| Minimum of Months | 26137829.86 | 0.30 | 84.58 | 0.92 | |
| Maximum of Months | 0.616246E+09 | 1.03 | 416.56 | 1.06 |
Report: FanReportMonthly
For: M S2 APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.107173E+09 | 0.63 | 40.01 | 01-JAN-00:10 | 0.64 |
| February | 96801429.15 | 0.63 | 40.01 | 01-FEB-00:10 | 0.64 |
| March | 0.107173E+09 | 0.63 | 40.01 | 01-MAR-00:10 | 0.63 |
| April | 0.103716E+09 | 0.63 | 40.01 | 01-APR-00:10 | 0.63 |
| May | 0.107173E+09 | 0.63 | 40.01 | 01-MAY-00:10 | 0.63 |
| June | 0.103716E+09 | 0.62 | 40.01 | 01-JUN-00:10 | 0.62 |
| July | 0.107173E+09 | 0.62 | 40.01 | 01-JUL-00:10 | 0.62 |
| August | 0.107173E+09 | 0.62 | 40.01 | 01-AUG-00:10 | 0.62 |
| September | 0.103716E+09 | 0.63 | 40.01 | 01-SEP-00:10 | 0.62 |
| October | 0.107173E+09 | 0.63 | 40.01 | 01-OCT-00:10 | 0.63 |
| November | 0.103716E+09 | 0.63 | 40.01 | 01-NOV-00:10 | 0.63 |
| December | 0.107173E+09 | 0.63 | 40.01 | 01-DEC-00:10 | 0.63 |
| Annual Sum or Average | 0.126188E+10 | 0.63 | |||
| Minimum of Months | 96801429.15 | 0.62 | 40.01 | 0.62 | |
| Maximum of Months | 0.107173E+09 | 0.63 | 40.01 | 0.64 |
Report: FanReportMonthly
For: M S2 APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.107173E+09 | 0.63 | 40.01 | 01-JAN-00:10 | 0.64 |
| February | 96801429.15 | 0.63 | 40.01 | 01-FEB-00:10 | 0.64 |
| March | 0.107173E+09 | 0.63 | 40.01 | 01-MAR-00:10 | 0.63 |
| April | 0.103716E+09 | 0.63 | 40.01 | 01-APR-00:10 | 0.63 |
| May | 0.107173E+09 | 0.63 | 40.01 | 01-MAY-00:10 | 0.63 |
| June | 0.103716E+09 | 0.63 | 40.01 | 01-JUN-00:10 | 0.63 |
| July | 0.107173E+09 | 0.62 | 40.01 | 01-JUL-00:10 | 0.62 |
| August | 0.107173E+09 | 0.63 | 40.01 | 01-AUG-00:10 | 0.62 |
| September | 0.103716E+09 | 0.63 | 40.01 | 01-SEP-00:10 | 0.63 |
| October | 0.107173E+09 | 0.63 | 40.01 | 01-OCT-00:10 | 0.63 |
| November | 0.103716E+09 | 0.63 | 40.01 | 01-NOV-00:10 | 0.63 |
| December | 0.107173E+09 | 0.63 | 40.01 | 01-DEC-00:10 | 0.63 |
| Annual Sum or Average | 0.126188E+10 | 0.63 | |||
| Minimum of Months | 96801429.15 | 0.62 | 40.01 | 0.62 | |
| Maximum of Months | 0.107173E+09 | 0.63 | 40.01 | 0.64 |
Report: FanReportMonthly
For: SPLIT TSW SUPPLY FAN
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.182677E+09 | 0.87 | 168.84 | 02-JAN-00:10 | 0.92 |
| February | 0.158443E+09 | 0.83 | 191.10 | 06-FEB-05:00 | 0.92 |
| March | 98363614.66 | 0.75 | 125.83 | 22-MAR-06:50 | 0.92 |
| April | 76004216.76 | 0.61 | 251.25 | 07-APR-15:20 | 1.00 |
| May | 95550839.13 | 0.49 | 263.28 | 30-MAY-15:10 | 0.99 |
| June | 0.256558E+09 | 0.88 | 344.25 | 19-JUN-14:10 | 0.96 |
| July | 0.406735E+09 | 1.02 | 334.17 | 13-JUL-15:10 | 0.96 |
| August | 0.397966E+09 | 0.98 | 352.27 | 16-AUG-15:10 | 0.96 |
| September | 0.198082E+09 | 0.74 | 321.21 | 07-SEP-15:10 | 0.97 |
| October | 96386326.66 | 0.54 | 267.71 | 04-OCT-15:10 | 0.99 |
| November | 89591616.18 | 0.73 | 132.65 | 23-NOV-02:00 | 0.92 |
| December | 0.146945E+09 | 0.83 | 150.65 | 31-DEC-24:00 | 0.92 |
| Annual Sum or Average | 0.220330E+10 | 0.77 | |||
| Minimum of Months | 76004216.76 | 0.49 | 125.83 | 0.92 | |
| Maximum of Months | 0.406735E+09 | 1.02 | 352.27 | 1.00 |
Report: FanReportMonthly
For: T SW APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.63 | 20.01 | 01-JAN-00:10 | 0.64 |
| February | 48400714.57 | 0.63 | 20.01 | 01-FEB-00:10 | 0.64 |
| March | 53586505.42 | 0.63 | 20.01 | 01-MAR-00:10 | 0.63 |
| April | 51857908.47 | 0.63 | 20.01 | 01-APR-00:10 | 0.63 |
| May | 53586505.42 | 0.63 | 20.01 | 01-MAY-00:10 | 0.63 |
| June | 51857908.47 | 0.62 | 20.01 | 01-JUN-00:10 | 0.62 |
| July | 53586505.42 | 0.62 | 20.01 | 01-JUL-00:10 | 0.62 |
| August | 53586505.42 | 0.62 | 20.01 | 01-AUG-00:10 | 0.62 |
| September | 51857908.47 | 0.63 | 20.01 | 01-SEP-00:10 | 0.62 |
| October | 53586505.42 | 0.63 | 20.01 | 01-OCT-00:10 | 0.63 |
| November | 51857908.47 | 0.63 | 20.01 | 01-NOV-00:10 | 0.63 |
| December | 53586505.42 | 0.63 | 20.01 | 01-DEC-00:10 | 0.63 |
| Annual Sum or Average | 0.630938E+09 | 0.63 | |||
| Minimum of Months | 48400714.57 | 0.62 | 20.01 | 0.62 | |
| Maximum of Months | 53586505.42 | 0.63 | 20.01 | 0.64 |
Report: FanReportMonthly
For: T SW APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.63 | 20.01 | 01-JAN-00:10 | 0.64 |
| February | 48400714.57 | 0.63 | 20.01 | 01-FEB-00:10 | 0.64 |
| March | 53586505.42 | 0.63 | 20.01 | 01-MAR-00:10 | 0.63 |
| April | 51857908.47 | 0.63 | 20.01 | 01-APR-00:10 | 0.63 |
| May | 53586505.42 | 0.63 | 20.01 | 01-MAY-00:10 | 0.63 |
| June | 51857908.47 | 0.63 | 20.01 | 01-JUN-00:10 | 0.63 |
| July | 53586505.42 | 0.62 | 20.01 | 01-JUL-00:10 | 0.62 |
| August | 53586505.42 | 0.63 | 20.01 | 01-AUG-00:10 | 0.62 |
| September | 51857908.47 | 0.63 | 20.01 | 01-SEP-00:10 | 0.62 |
| October | 53586505.42 | 0.63 | 20.01 | 01-OCT-00:10 | 0.63 |
| November | 51857908.47 | 0.63 | 20.01 | 01-NOV-00:10 | 0.63 |
| December | 53586505.42 | 0.63 | 20.01 | 01-DEC-00:10 | 0.63 |
| Annual Sum or Average | 0.630938E+09 | 0.63 | |||
| Minimum of Months | 48400714.57 | 0.62 | 20.01 | 0.62 | |
| Maximum of Months | 53586505.42 | 0.63 | 20.01 | 0.64 |
Report: FanReportMonthly
For: SPLIT TNW SUPPLY FAN
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.214506E+09 | 0.92 | 176.03 | 02-JAN-00:10 | 0.92 |
| February | 0.197321E+09 | 0.92 | 199.48 | 06-FEB-01:00 | 0.92 |
| March | 0.113152E+09 | 0.80 | 131.23 | 22-MAR-07:00 | 0.92 |
| April | 59671208.73 | 0.59 | 173.00 | 07-APR-16:05 | 1.02 |
| May | 77580942.93 | 0.47 | 247.21 | 30-MAY-16:10 | 1.00 |
| June | 0.243535E+09 | 0.89 | 334.89 | 19-JUN-17:10 | 0.96 |
| July | 0.387322E+09 | 1.02 | 312.41 | 13-JUL-16:08 | 0.97 |
| August | 0.348120E+09 | 0.98 | 318.58 | 02-AUG-15:30 | 0.97 |
| September | 0.140573E+09 | 0.69 | 254.85 | 07-SEP-15:30 | 0.99 |
| October | 46494854.82 | 0.45 | 173.80 | 04-OCT-15:30 | 1.01 |
| November | 0.110244E+09 | 0.81 | 139.07 | 23-NOV-02:00 | 0.92 |
| December | 0.181468E+09 | 0.92 | 162.07 | 31-DEC-22:10 | 0.92 |
| Annual Sum or Average | 0.211999E+10 | 0.79 | |||
| Minimum of Months | 46494854.82 | 0.45 | 131.23 | 0.92 | |
| Maximum of Months | 0.387322E+09 | 1.02 | 334.89 | 1.02 |
Report: FanReportMonthly
For: T NW APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.63 | 20.01 | 01-JAN-00:10 | 0.64 |
| February | 48400714.57 | 0.63 | 20.01 | 01-FEB-00:10 | 0.64 |
| March | 53586505.42 | 0.63 | 20.01 | 01-MAR-00:10 | 0.63 |
| April | 51857908.47 | 0.63 | 20.01 | 01-APR-00:10 | 0.63 |
| May | 53586505.42 | 0.63 | 20.01 | 01-MAY-00:10 | 0.63 |
| June | 51857908.47 | 0.62 | 20.01 | 01-JUN-00:10 | 0.62 |
| July | 53586505.42 | 0.62 | 20.01 | 01-JUL-00:10 | 0.62 |
| August | 53586505.42 | 0.62 | 20.01 | 01-AUG-00:10 | 0.62 |
| September | 51857908.47 | 0.63 | 20.01 | 01-SEP-00:10 | 0.62 |
| October | 53586505.42 | 0.63 | 20.01 | 01-OCT-00:10 | 0.63 |
| November | 51857908.47 | 0.63 | 20.01 | 01-NOV-00:10 | 0.63 |
| December | 53586505.42 | 0.63 | 20.01 | 01-DEC-00:10 | 0.63 |
| Annual Sum or Average | 0.630938E+09 | 0.63 | |||
| Minimum of Months | 48400714.57 | 0.62 | 20.01 | 0.62 | |
| Maximum of Months | 53586505.42 | 0.63 | 20.01 | 0.64 |
Report: FanReportMonthly
For: T NW APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.63 | 20.01 | 01-JAN-00:10 | 0.64 |
| February | 48400714.57 | 0.63 | 20.01 | 01-FEB-00:10 | 0.64 |
| March | 53586505.42 | 0.63 | 20.01 | 01-MAR-00:10 | 0.63 |
| April | 51857908.47 | 0.63 | 20.01 | 01-APR-00:10 | 0.63 |
| May | 53586505.42 | 0.63 | 20.01 | 01-MAY-00:10 | 0.63 |
| June | 51857908.47 | 0.63 | 20.01 | 01-JUN-00:10 | 0.63 |
| July | 53586505.42 | 0.62 | 20.01 | 01-JUL-00:10 | 0.62 |
| August | 53586505.42 | 0.63 | 20.01 | 01-AUG-00:10 | 0.62 |
| September | 51857908.47 | 0.63 | 20.01 | 01-SEP-00:10 | 0.62 |
| October | 53586505.42 | 0.63 | 20.01 | 01-OCT-00:10 | 0.63 |
| November | 51857908.47 | 0.63 | 20.01 | 01-NOV-00:10 | 0.63 |
| December | 53586505.42 | 0.63 | 20.01 | 01-DEC-00:10 | 0.63 |
| Annual Sum or Average | 0.630938E+09 | 0.63 | |||
| Minimum of Months | 48400714.57 | 0.62 | 20.01 | 0.62 | |
| Maximum of Months | 53586505.42 | 0.63 | 20.01 | 0.64 |
Report: FanReportMonthly
For: SPLIT TSE SUPPLY FAN
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.179337E+09 | 0.87 | 165.75 | 02-JAN-00:10 | 0.92 |
| February | 0.154423E+09 | 0.82 | 188.14 | 06-FEB-05:00 | 0.92 |
| March | 95877918.01 | 0.75 | 124.90 | 22-MAR-06:00 | 0.92 |
| April | 72438089.34 | 0.61 | 229.08 | 07-APR-13:00 | 0.99 |
| May | 93013766.89 | 0.50 | 251.47 | 30-MAY-13:00 | 0.98 |
| June | 0.244466E+09 | 0.88 | 335.12 | 19-JUN-12:30 | 0.95 |
| July | 0.396364E+09 | 1.01 | 324.18 | 08-JUL-12:20 | 0.95 |
| August | 0.387230E+09 | 0.98 | 324.91 | 16-AUG-13:00 | 0.95 |
| September | 0.193374E+09 | 0.75 | 291.58 | 01-SEP-13:00 | 0.97 |
| October | 90704116.46 | 0.53 | 243.12 | 04-OCT-13:00 | 0.99 |
| November | 85945556.96 | 0.71 | 130.78 | 23-NOV-02:00 | 0.92 |
| December | 0.143566E+09 | 0.83 | 149.26 | 31-DEC-24:00 | 0.92 |
| Annual Sum or Average | 0.213674E+10 | 0.77 | |||
| Minimum of Months | 72438089.34 | 0.50 | 124.90 | 0.92 | |
| Maximum of Months | 0.396364E+09 | 1.01 | 335.12 | 0.99 |
Report: FanReportMonthly
For: T SE APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.63 | 20.01 | 01-JAN-00:10 | 0.64 |
| February | 48400714.57 | 0.63 | 20.01 | 01-FEB-00:10 | 0.64 |
| March | 53586505.42 | 0.63 | 20.01 | 01-MAR-00:10 | 0.63 |
| April | 51857908.47 | 0.63 | 20.01 | 01-APR-00:10 | 0.63 |
| May | 53586505.42 | 0.63 | 20.01 | 01-MAY-00:10 | 0.63 |
| June | 51857908.47 | 0.62 | 20.01 | 01-JUN-00:10 | 0.62 |
| July | 53586505.42 | 0.62 | 20.01 | 01-JUL-00:10 | 0.62 |
| August | 53586505.42 | 0.62 | 20.01 | 01-AUG-00:10 | 0.62 |
| September | 51857908.47 | 0.63 | 20.01 | 01-SEP-00:10 | 0.62 |
| October | 53586505.42 | 0.63 | 20.01 | 01-OCT-00:10 | 0.63 |
| November | 51857908.47 | 0.63 | 20.01 | 01-NOV-00:10 | 0.63 |
| December | 53586505.42 | 0.63 | 20.01 | 01-DEC-00:10 | 0.63 |
| Annual Sum or Average | 0.630938E+09 | 0.63 | |||
| Minimum of Months | 48400714.57 | 0.62 | 20.01 | 0.62 | |
| Maximum of Months | 53586505.42 | 0.63 | 20.01 | 0.64 |
Report: FanReportMonthly
For: T SE APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.63 | 20.01 | 01-JAN-00:10 | 0.64 |
| February | 48400714.57 | 0.63 | 20.01 | 01-FEB-00:10 | 0.64 |
| March | 53586505.42 | 0.63 | 20.01 | 01-MAR-00:10 | 0.63 |
| April | 51857908.47 | 0.63 | 20.01 | 01-APR-00:10 | 0.63 |
| May | 53586505.42 | 0.63 | 20.01 | 01-MAY-00:10 | 0.63 |
| June | 51857908.47 | 0.63 | 20.01 | 01-JUN-00:10 | 0.63 |
| July | 53586505.42 | 0.62 | 20.01 | 01-JUL-00:10 | 0.62 |
| August | 53586505.42 | 0.63 | 20.01 | 01-AUG-00:10 | 0.62 |
| September | 51857908.47 | 0.63 | 20.01 | 01-SEP-00:10 | 0.62 |
| October | 53586505.42 | 0.63 | 20.01 | 01-OCT-00:10 | 0.63 |
| November | 51857908.47 | 0.63 | 20.01 | 01-NOV-00:10 | 0.63 |
| December | 53586505.42 | 0.63 | 20.01 | 01-DEC-00:10 | 0.63 |
| Annual Sum or Average | 0.630938E+09 | 0.63 | |||
| Minimum of Months | 48400714.57 | 0.62 | 20.01 | 0.62 | |
| Maximum of Months | 53586505.42 | 0.63 | 20.01 | 0.64 |
Report: FanReportMonthly
For: SPLIT TNE SUPPLY FAN
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.211121E+09 | 0.92 | 173.03 | 02-JAN-00:10 | 0.92 |
| February | 0.193034E+09 | 0.92 | 196.24 | 06-FEB-01:00 | 0.92 |
| March | 0.112052E+09 | 0.80 | 128.83 | 22-MAR-06:00 | 0.92 |
| April | 55969606.03 | 0.58 | 132.39 | 08-APR-12:00 | 1.03 |
| May | 75093462.41 | 0.49 | 209.57 | 30-MAY-13:00 | 1.00 |
| June | 0.232197E+09 | 0.90 | 300.53 | 19-JUN-12:00 | 0.96 |
| July | 0.377859E+09 | 1.02 | 288.11 | 08-JUL-12:00 | 0.96 |
| August | 0.339160E+09 | 0.98 | 272.19 | 04-AUG-11:00 | 0.97 |
| September | 0.136351E+09 | 0.70 | 213.32 | 14-SEP-14:00 | 0.99 |
| October | 43448208.18 | 0.44 | 135.85 | 25-OCT-10:40 | 1.02 |
| November | 0.105596E+09 | 0.80 | 137.08 | 23-NOV-02:00 | 0.92 |
| December | 0.177613E+09 | 0.92 | 160.89 | 31-DEC-22:10 | 0.92 |
| Annual Sum or Average | 0.205949E+10 | 0.79 | |||
| Minimum of Months | 43448208.18 | 0.44 | 128.83 | 0.92 | |
| Maximum of Months | 0.377859E+09 | 1.02 | 300.53 | 1.03 |
Report: FanReportMonthly
For: T NE APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.63 | 20.01 | 01-JAN-00:10 | 0.64 |
| February | 48400714.57 | 0.63 | 20.01 | 01-FEB-00:10 | 0.64 |
| March | 53586505.42 | 0.63 | 20.01 | 01-MAR-00:10 | 0.63 |
| April | 51857908.47 | 0.63 | 20.01 | 01-APR-00:10 | 0.63 |
| May | 53586505.42 | 0.63 | 20.01 | 01-MAY-00:10 | 0.63 |
| June | 51857908.47 | 0.62 | 20.01 | 01-JUN-00:10 | 0.62 |
| July | 53586505.42 | 0.62 | 20.01 | 01-JUL-00:10 | 0.62 |
| August | 53586505.42 | 0.62 | 20.01 | 01-AUG-00:10 | 0.62 |
| September | 51857908.47 | 0.63 | 20.01 | 01-SEP-00:10 | 0.62 |
| October | 53586505.42 | 0.63 | 20.01 | 01-OCT-00:10 | 0.63 |
| November | 51857908.47 | 0.63 | 20.01 | 01-NOV-00:10 | 0.63 |
| December | 53586505.42 | 0.63 | 20.01 | 01-DEC-00:10 | 0.63 |
| Annual Sum or Average | 0.630938E+09 | 0.63 | |||
| Minimum of Months | 48400714.57 | 0.62 | 20.01 | 0.62 | |
| Maximum of Months | 53586505.42 | 0.63 | 20.01 | 0.64 |
Report: FanReportMonthly
For: T NE APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.63 | 20.01 | 01-JAN-00:10 | 0.64 |
| February | 48400714.57 | 0.63 | 20.01 | 01-FEB-00:10 | 0.64 |
| March | 53586505.42 | 0.63 | 20.01 | 01-MAR-00:10 | 0.63 |
| April | 51857908.47 | 0.63 | 20.01 | 01-APR-00:10 | 0.63 |
| May | 53586505.42 | 0.63 | 20.01 | 01-MAY-00:10 | 0.63 |
| June | 51857908.47 | 0.63 | 20.01 | 01-JUN-00:10 | 0.63 |
| July | 53586505.42 | 0.62 | 20.01 | 01-JUL-00:10 | 0.62 |
| August | 53586505.42 | 0.63 | 20.01 | 01-AUG-00:10 | 0.62 |
| September | 51857908.47 | 0.63 | 20.01 | 01-SEP-00:10 | 0.62 |
| October | 53586505.42 | 0.63 | 20.01 | 01-OCT-00:10 | 0.63 |
| November | 51857908.47 | 0.63 | 20.01 | 01-NOV-00:10 | 0.63 |
| December | 53586505.42 | 0.63 | 20.01 | 01-DEC-00:10 | 0.63 |
| Annual Sum or Average | 0.630938E+09 | 0.63 | |||
| Minimum of Months | 48400714.57 | 0.62 | 20.01 | 0.62 | |
| Maximum of Months | 53586505.42 | 0.63 | 20.01 | 0.64 |
Report: FanReportMonthly
For: SPLIT TN1 SUPPLY FAN
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.151528E+09 | 0.92 | 124.90 | 02-JAN-00:20 | 0.92 |
| February | 0.141818E+09 | 0.92 | 141.50 | 06-FEB-01:10 | 0.92 |
| March | 78081946.70 | 0.79 | 88.59 | 22-MAR-06:00 | 0.92 |
| April | 35364419.27 | 0.53 | 102.48 | 07-APR-16:30 | 1.04 |
| May | 55490962.32 | 0.45 | 164.98 | 31-MAY-14:10 | 1.01 |
| June | 0.200421E+09 | 0.93 | 238.72 | 19-JUN-17:10 | 0.98 |
| July | 0.324121E+09 | 1.02 | 229.34 | 08-JUL-12:40 | 0.98 |
| August | 0.283255E+09 | 1.00 | 224.47 | 16-AUG-15:10 | 0.98 |
| September | 0.116650E+09 | 0.71 | 179.89 | 14-SEP-14:00 | 1.00 |
| October | 28508944.10 | 0.39 | 103.17 | 04-OCT-16:10 | 1.03 |
| November | 72204493.27 | 0.77 | 96.45 | 23-NOV-02:00 | 0.92 |
| December | 0.126268E+09 | 0.92 | 112.78 | 31-DEC-24:00 | 0.92 |
| Annual Sum or Average | 0.161371E+10 | 0.78 | |||
| Minimum of Months | 28508944.10 | 0.39 | 88.59 | 0.92 | |
| Maximum of Months | 0.324121E+09 | 1.02 | 238.72 | 1.04 |
Report: FanReportMonthly
For: T N1 APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.63 | 20.01 | 01-JAN-00:10 | 0.64 |
| February | 48400714.57 | 0.63 | 20.01 | 01-FEB-00:10 | 0.64 |
| March | 53586505.42 | 0.63 | 20.01 | 01-MAR-00:10 | 0.63 |
| April | 51857908.47 | 0.63 | 20.01 | 01-APR-00:10 | 0.63 |
| May | 53586505.42 | 0.63 | 20.01 | 01-MAY-00:10 | 0.63 |
| June | 51857908.47 | 0.62 | 20.01 | 01-JUN-00:10 | 0.62 |
| July | 53586505.42 | 0.62 | 20.01 | 01-JUL-00:10 | 0.62 |
| August | 53586505.42 | 0.62 | 20.01 | 01-AUG-00:10 | 0.62 |
| September | 51857908.47 | 0.63 | 20.01 | 01-SEP-00:10 | 0.62 |
| October | 53586505.42 | 0.63 | 20.01 | 01-OCT-00:10 | 0.63 |
| November | 51857908.47 | 0.63 | 20.01 | 01-NOV-00:10 | 0.63 |
| December | 53586505.42 | 0.63 | 20.01 | 01-DEC-00:10 | 0.63 |
| Annual Sum or Average | 0.630938E+09 | 0.63 | |||
| Minimum of Months | 48400714.57 | 0.62 | 20.01 | 0.62 | |
| Maximum of Months | 53586505.42 | 0.63 | 20.01 | 0.64 |
Report: FanReportMonthly
For: T N1 APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.63 | 20.01 | 01-JAN-00:10 | 0.64 |
| February | 48400714.57 | 0.63 | 20.01 | 01-FEB-00:10 | 0.64 |
| March | 53586505.42 | 0.63 | 20.01 | 01-MAR-00:10 | 0.63 |
| April | 51857908.47 | 0.63 | 20.01 | 01-APR-00:10 | 0.63 |
| May | 53586505.42 | 0.63 | 20.01 | 01-MAY-00:10 | 0.63 |
| June | 51857908.47 | 0.63 | 20.01 | 01-JUN-00:10 | 0.63 |
| July | 53586505.42 | 0.62 | 20.01 | 01-JUL-00:10 | 0.62 |
| August | 53586505.42 | 0.63 | 20.01 | 01-AUG-00:10 | 0.62 |
| September | 51857908.47 | 0.63 | 20.01 | 01-SEP-00:10 | 0.62 |
| October | 53586505.42 | 0.63 | 20.01 | 01-OCT-00:10 | 0.63 |
| November | 51857908.47 | 0.63 | 20.01 | 01-NOV-00:10 | 0.63 |
| December | 53586505.42 | 0.63 | 20.01 | 01-DEC-00:10 | 0.63 |
| Annual Sum or Average | 0.630938E+09 | 0.63 | |||
| Minimum of Months | 48400714.57 | 0.62 | 20.01 | 0.62 | |
| Maximum of Months | 53586505.42 | 0.63 | 20.01 | 0.64 |
Report: FanReportMonthly
For: SPLIT TN2 SUPPLY FAN
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.151420E+09 | 0.92 | 124.78 | 02-JAN-00:20 | 0.92 |
| February | 0.141680E+09 | 0.92 | 141.38 | 06-FEB-01:10 | 0.92 |
| March | 78153041.16 | 0.79 | 88.61 | 22-MAR-06:00 | 0.92 |
| April | 35462139.08 | 0.53 | 101.78 | 07-APR-16:17 | 1.04 |
| May | 55766333.03 | 0.45 | 164.94 | 31-MAY-14:10 | 1.01 |
| June | 0.200063E+09 | 0.93 | 237.38 | 19-JUN-17:10 | 0.98 |
| July | 0.323807E+09 | 1.02 | 229.92 | 08-JUL-12:40 | 0.98 |
| August | 0.283012E+09 | 1.00 | 223.53 | 04-AUG-15:10 | 0.98 |
| September | 0.116693E+09 | 0.71 | 179.50 | 14-SEP-14:00 | 1.00 |
| October | 28655194.25 | 0.38 | 102.34 | 04-OCT-15:10 | 1.03 |
| November | 72017878.41 | 0.77 | 96.37 | 23-NOV-02:00 | 0.92 |
| December | 0.126133E+09 | 0.92 | 112.76 | 31-DEC-24:00 | 0.92 |
| Annual Sum or Average | 0.161286E+10 | 0.78 | |||
| Minimum of Months | 28655194.25 | 0.38 | 88.61 | 0.92 | |
| Maximum of Months | 0.323807E+09 | 1.02 | 237.38 | 1.04 |
Report: FanReportMonthly
For: T N2 APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.63 | 20.01 | 01-JAN-00:10 | 0.64 |
| February | 48400714.57 | 0.63 | 20.01 | 01-FEB-00:10 | 0.64 |
| March | 53586505.42 | 0.63 | 20.01 | 01-MAR-00:10 | 0.63 |
| April | 51857908.47 | 0.63 | 20.01 | 01-APR-00:10 | 0.63 |
| May | 53586505.42 | 0.63 | 20.01 | 01-MAY-00:10 | 0.63 |
| June | 51857908.47 | 0.62 | 20.01 | 01-JUN-00:10 | 0.62 |
| July | 53586505.42 | 0.62 | 20.01 | 01-JUL-00:10 | 0.62 |
| August | 53586505.42 | 0.62 | 20.01 | 01-AUG-00:10 | 0.62 |
| September | 51857908.47 | 0.63 | 20.01 | 01-SEP-00:10 | 0.62 |
| October | 53586505.42 | 0.63 | 20.01 | 01-OCT-00:10 | 0.63 |
| November | 51857908.47 | 0.63 | 20.01 | 01-NOV-00:10 | 0.63 |
| December | 53586505.42 | 0.63 | 20.01 | 01-DEC-00:10 | 0.63 |
| Annual Sum or Average | 0.630938E+09 | 0.63 | |||
| Minimum of Months | 48400714.57 | 0.62 | 20.01 | 0.62 | |
| Maximum of Months | 53586505.42 | 0.63 | 20.01 | 0.64 |
Report: FanReportMonthly
For: T N2 APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.63 | 20.01 | 01-JAN-00:10 | 0.64 |
| February | 48400714.57 | 0.63 | 20.01 | 01-FEB-00:10 | 0.64 |
| March | 53586505.42 | 0.63 | 20.01 | 01-MAR-00:10 | 0.63 |
| April | 51857908.47 | 0.63 | 20.01 | 01-APR-00:10 | 0.63 |
| May | 53586505.42 | 0.63 | 20.01 | 01-MAY-00:10 | 0.63 |
| June | 51857908.47 | 0.63 | 20.01 | 01-JUN-00:10 | 0.63 |
| July | 53586505.42 | 0.62 | 20.01 | 01-JUL-00:10 | 0.62 |
| August | 53586505.42 | 0.63 | 20.01 | 01-AUG-00:10 | 0.62 |
| September | 51857908.47 | 0.63 | 20.01 | 01-SEP-00:10 | 0.62 |
| October | 53586505.42 | 0.63 | 20.01 | 01-OCT-00:10 | 0.63 |
| November | 51857908.47 | 0.63 | 20.01 | 01-NOV-00:10 | 0.63 |
| December | 53586505.42 | 0.63 | 20.01 | 01-DEC-00:10 | 0.63 |
| Annual Sum or Average | 0.630938E+09 | 0.63 | |||
| Minimum of Months | 48400714.57 | 0.62 | 20.01 | 0.62 | |
| Maximum of Months | 53586505.42 | 0.63 | 20.01 | 0.64 |
Report: FanReportMonthly
For: SPLIT TS1 SUPPLY FAN
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.120908E+09 | 0.84 | 117.61 | 02-JAN-00:50 | 0.92 |
| February | 0.104279E+09 | 0.79 | 135.21 | 06-FEB-05:00 | 0.92 |
| March | 62649865.65 | 0.69 | 95.66 | 03-MAR-14:00 | 1.04 |
| April | 50366662.14 | 0.56 | 195.87 | 07-APR-13:00 | 1.00 |
| May | 73212971.00 | 0.48 | 206.11 | 30-MAY-13:00 | 1.00 |
| June | 0.213520E+09 | 0.92 | 275.11 | 19-JUN-13:00 | 0.97 |
| July | 0.343776E+09 | 1.02 | 267.57 | 08-JUL-12:30 | 0.97 |
| August | 0.333627E+09 | 1.00 | 282.20 | 16-AUG-13:00 | 0.96 |
| September | 0.175832E+09 | 0.79 | 253.58 | 07-SEP-13:40 | 0.97 |
| October | 82542119.61 | 0.53 | 217.59 | 04-OCT-13:00 | 0.99 |
| November | 54759384.60 | 0.65 | 99.17 | 02-NOV-13:00 | 1.04 |
| December | 94265521.86 | 0.79 | 102.74 | 31-DEC-24:00 | 0.92 |
| Annual Sum or Average | 0.170974E+10 | 0.75 | |||
| Minimum of Months | 50366662.14 | 0.48 | 95.66 | 0.92 | |
| Maximum of Months | 0.343776E+09 | 1.02 | 282.20 | 1.04 |
Report: FanReportMonthly
For: T S1 APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.63 | 20.01 | 01-JAN-00:10 | 0.64 |
| February | 48400714.57 | 0.63 | 20.01 | 01-FEB-00:10 | 0.64 |
| March | 53586505.42 | 0.63 | 20.01 | 01-MAR-00:10 | 0.63 |
| April | 51857908.47 | 0.63 | 20.01 | 01-APR-00:10 | 0.63 |
| May | 53586505.42 | 0.63 | 20.01 | 01-MAY-00:10 | 0.63 |
| June | 51857908.47 | 0.62 | 20.01 | 01-JUN-00:10 | 0.62 |
| July | 53586505.42 | 0.62 | 20.01 | 01-JUL-00:10 | 0.62 |
| August | 53586505.42 | 0.62 | 20.01 | 01-AUG-00:10 | 0.62 |
| September | 51857908.47 | 0.63 | 20.01 | 01-SEP-00:10 | 0.62 |
| October | 53586505.42 | 0.63 | 20.01 | 01-OCT-00:10 | 0.63 |
| November | 51857908.47 | 0.63 | 20.01 | 01-NOV-00:10 | 0.63 |
| December | 53586505.42 | 0.63 | 20.01 | 01-DEC-00:10 | 0.63 |
| Annual Sum or Average | 0.630938E+09 | 0.63 | |||
| Minimum of Months | 48400714.57 | 0.62 | 20.01 | 0.62 | |
| Maximum of Months | 53586505.42 | 0.63 | 20.01 | 0.64 |
Report: FanReportMonthly
For: T S1 APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.63 | 20.01 | 01-JAN-00:10 | 0.64 |
| February | 48400714.57 | 0.63 | 20.01 | 01-FEB-00:10 | 0.64 |
| March | 53586505.42 | 0.63 | 20.01 | 01-MAR-00:10 | 0.63 |
| April | 51857908.47 | 0.63 | 20.01 | 01-APR-00:10 | 0.63 |
| May | 53586505.42 | 0.63 | 20.01 | 01-MAY-00:10 | 0.63 |
| June | 51857908.47 | 0.63 | 20.01 | 01-JUN-00:10 | 0.63 |
| July | 53586505.42 | 0.62 | 20.01 | 01-JUL-00:10 | 0.62 |
| August | 53586505.42 | 0.63 | 20.01 | 01-AUG-00:10 | 0.62 |
| September | 51857908.47 | 0.63 | 20.01 | 01-SEP-00:10 | 0.62 |
| October | 53586505.42 | 0.63 | 20.01 | 01-OCT-00:10 | 0.63 |
| November | 51857908.47 | 0.63 | 20.01 | 01-NOV-00:10 | 0.63 |
| December | 53586505.42 | 0.63 | 20.01 | 01-DEC-00:10 | 0.63 |
| Annual Sum or Average | 0.630938E+09 | 0.63 | |||
| Minimum of Months | 48400714.57 | 0.62 | 20.01 | 0.62 | |
| Maximum of Months | 53586505.42 | 0.63 | 20.01 | 0.64 |
Report: FanReportMonthly
For: SPLIT TS2 SUPPLY FAN
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.120842E+09 | 0.84 | 117.48 | 02-JAN-00:50 | 0.92 |
| February | 0.104234E+09 | 0.79 | 135.10 | 06-FEB-05:00 | 0.92 |
| March | 62924682.63 | 0.70 | 96.72 | 03-MAR-14:00 | 1.04 |
| April | 50707886.14 | 0.56 | 197.09 | 07-APR-13:00 | 1.00 |
| May | 73507774.18 | 0.48 | 206.93 | 30-MAY-13:00 | 0.99 |
| June | 0.213140E+09 | 0.92 | 275.58 | 19-JUN-13:00 | 0.96 |
| July | 0.343437E+09 | 1.02 | 268.12 | 08-JUL-12:30 | 0.97 |
| August | 0.333314E+09 | 1.00 | 282.12 | 16-AUG-13:00 | 0.96 |
| September | 0.175823E+09 | 0.79 | 253.36 | 07-SEP-13:40 | 0.97 |
| October | 82697499.27 | 0.53 | 218.17 | 04-OCT-13:00 | 0.99 |
| November | 54729709.10 | 0.65 | 100.50 | 02-NOV-13:00 | 1.04 |
| December | 94209034.30 | 0.79 | 102.72 | 31-DEC-24:00 | 0.92 |
| Annual Sum or Average | 0.170957E+10 | 0.75 | |||
| Minimum of Months | 50707886.14 | 0.48 | 96.72 | 0.92 | |
| Maximum of Months | 0.343437E+09 | 1.02 | 282.12 | 1.04 |
Report: FanReportMonthly
For: T S2 APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.63 | 20.01 | 01-JAN-00:10 | 0.64 |
| February | 48400714.57 | 0.63 | 20.01 | 01-FEB-00:10 | 0.64 |
| March | 53586505.42 | 0.63 | 20.01 | 01-MAR-00:10 | 0.63 |
| April | 51857908.47 | 0.63 | 20.01 | 01-APR-00:10 | 0.63 |
| May | 53586505.42 | 0.63 | 20.01 | 01-MAY-00:10 | 0.63 |
| June | 51857908.47 | 0.62 | 20.01 | 01-JUN-00:10 | 0.62 |
| July | 53586505.42 | 0.62 | 20.01 | 01-JUL-00:10 | 0.62 |
| August | 53586505.42 | 0.62 | 20.01 | 01-AUG-00:10 | 0.62 |
| September | 51857908.47 | 0.63 | 20.01 | 01-SEP-00:10 | 0.62 |
| October | 53586505.42 | 0.63 | 20.01 | 01-OCT-00:10 | 0.63 |
| November | 51857908.47 | 0.63 | 20.01 | 01-NOV-00:10 | 0.63 |
| December | 53586505.42 | 0.63 | 20.01 | 01-DEC-00:10 | 0.63 |
| Annual Sum or Average | 0.630938E+09 | 0.63 | |||
| Minimum of Months | 48400714.57 | 0.62 | 20.01 | 0.62 | |
| Maximum of Months | 53586505.42 | 0.63 | 20.01 | 0.64 |
Report: FanReportMonthly
For: T S2 APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.63 | 20.01 | 01-JAN-00:10 | 0.64 |
| February | 48400714.57 | 0.63 | 20.01 | 01-FEB-00:10 | 0.64 |
| March | 53586505.42 | 0.63 | 20.01 | 01-MAR-00:10 | 0.63 |
| April | 51857908.47 | 0.63 | 20.01 | 01-APR-00:10 | 0.63 |
| May | 53586505.42 | 0.63 | 20.01 | 01-MAY-00:10 | 0.63 |
| June | 51857908.47 | 0.63 | 20.01 | 01-JUN-00:10 | 0.63 |
| July | 53586505.42 | 0.62 | 20.01 | 01-JUL-00:10 | 0.62 |
| August | 53586505.42 | 0.63 | 20.01 | 01-AUG-00:10 | 0.62 |
| September | 51857908.47 | 0.63 | 20.01 | 01-SEP-00:10 | 0.62 |
| October | 53586505.42 | 0.63 | 20.01 | 01-OCT-00:10 | 0.63 |
| November | 51857908.47 | 0.63 | 20.01 | 01-NOV-00:10 | 0.63 |
| December | 53586505.42 | 0.63 | 20.01 | 01-DEC-00:10 | 0.63 |
| Annual Sum or Average | 0.630938E+09 | 0.63 | |||
| Minimum of Months | 48400714.57 | 0.62 | 20.01 | 0.62 | |
| Maximum of Months | 53586505.42 | 0.63 | 20.01 | 0.64 |
Report: ZoneTemperatureOscillationReportMonthly
For: G SW APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: G NW APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: OFFICE
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: G NE APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: G N1 APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: G N2 APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: G S1 APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: G S2 APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: M SW APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: M NW APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: M SE APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: M NE APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: M N1 APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: M N2 APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: M S1 APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: M S2 APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: T SW APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: T NW APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: T SE APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: T NE APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: T N1 APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: T N2 APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: T S1 APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: T S2 APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: T CORRIDOR
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: G CORRIDOR
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: M CORRIDOR
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT GSW
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.119283E+09 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.109554E+09 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 65589250.14 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 43966262.66 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.112330E+09 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.754261E+09 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.138347E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.146928E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.825269E+09 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.425632E+09 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 43842733.60 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 78610448.81 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.543109E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 43842733.60 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.146928E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT GNW
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.148219E+09 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.147603E+09 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 93261972.02 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 36992203.96 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 80635322.65 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.694305E+09 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.129642E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.126218E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.581037E+09 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.112585E+09 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 49139362.99 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.110370E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.461274E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 36992203.96 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.129642E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT OFFICE
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.120728E+10 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.109044E+10 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.120728E+10 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.120604E+10 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.136348E+10 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.166763E+10 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.190988E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.204565E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.167158E+10 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.155095E+10 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.121645E+10 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.120728E+10 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.173439E+11 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.109044E+10 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.204565E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT GNE
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.146060E+09 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.144745E+09 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 93514973.86 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 36051649.52 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 87929258.11 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.664967E+09 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.128219E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.124885E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.578053E+09 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.104252E+09 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 46508300.31 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.108054E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.454118E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 36051649.52 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.128219E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT GN1
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.101855E+09 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.103778E+09 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 63552189.17 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 20814747.05 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 68261964.04 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.616367E+09 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.112543E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.105458E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.507889E+09 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 93220541.38 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 29254040.11 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 73419323.05 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.385841E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 20814747.05 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.112543E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT GN2
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.101811E+09 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.103715E+09 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 63623277.08 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 20816468.58 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 69230125.06 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.615236E+09 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.112509E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.105438E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.508234E+09 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 92831393.31 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 29130174.71 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 73355553.86 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.385745E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 20816468.58 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.112509E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT GS1
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 74791493.02 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 67862907.50 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 37811636.50 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 28942068.73 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 99941839.59 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.681694E+09 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.121935E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.127019E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.767513E+09 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.446279E+09 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 43728269.48 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 43980305.18 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.478208E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 28942068.73 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.127019E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT GS2
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 83924471.98 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 74951325.16 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 41622036.50 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 31749381.34 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.114519E+09 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.746035E+09 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.131867E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.137053E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.839959E+09 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.484253E+09 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 49996941.78 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 48528565.72 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.520474E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 31749381.34 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.137053E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT MSW
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.200239E+09 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.164639E+09 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 70910300.15 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.283625E+09 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.868017E+09 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.225296E+10 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.340877E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.337521E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.185364E+10 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.952871E+09 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.109932E+09 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.143408E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.136842E+11 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 70910300.15 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.340877E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT MNW
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.260697E+09 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.240318E+09 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.114104E+09 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.119215E+09 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.704956E+09 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.213219E+10 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.322556E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.293361E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.132455E+10 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.287952E+09 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.104764E+09 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.209554E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.116575E+11 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.104764E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.322556E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT MSE
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.196712E+09 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.159991E+09 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 66806423.22 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.280612E+09 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.879839E+09 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.218659E+10 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.337392E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.333947E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.184736E+10 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.928141E+09 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.112576E+09 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.139513E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.135115E+11 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 66806423.22 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.337392E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT MNE
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.256706E+09 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.234998E+09 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.114885E+09 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.114250E+09 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.714650E+09 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.206536E+10 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.319044E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.290074E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.131848E+10 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.267401E+09 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 98919807.98 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.204828E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.114817E+11 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 98919807.98 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.319044E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT MN1
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.162648E+09 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.155181E+09 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 66043122.89 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 69603137.80 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.591276E+09 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.173706E+10 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.265784E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.235680E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.114115E+10 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.251758E+09 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 53802293.91 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.124864E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.936804E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 53802293.91 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.265784E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT MN2
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.162542E+09 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.155014E+09 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 66205940.47 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 70656236.18 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.592383E+09 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.173494E+10 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.265715E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.235634E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.114184E+10 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.251278E+09 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 53552444.81 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.124708E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.936660E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 53552444.81 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.265715E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT MS1
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.105873E+09 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 83113162.15 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 31690227.50 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.247313E+09 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.761452E+09 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.186290E+10 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.284812E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.280727E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.168734E+10 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.100124E+10 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.118312E+09 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 67166290.52 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.116218E+11 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 31690227.50 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.284812E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT MS2
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.105783E+09 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 83029072.31 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 31753736.15 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.249249E+09 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.762593E+09 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.186076E+10 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.284737E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.280666E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.168747E+10 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.100114E+10 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.120341E+09 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 67122495.58 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.116233E+11 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 31753736.15 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.284737E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT TSW
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.184364E+09 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.158854E+09 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.129117E+09 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.203751E+09 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.416110E+09 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.116037E+10 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.186433E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.182722E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.887373E+09 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.389064E+09 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.105697E+09 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.149426E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.747567E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.105697E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.186433E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT TNW
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.214506E+09 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.197321E+09 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.114668E+09 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.111512E+09 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.335752E+09 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.110129E+10 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.177444E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.159962E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.630921E+09 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.134466E+09 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.110244E+09 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.181468E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.650621E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.110244E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.177444E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT TSE
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.180358E+09 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.154454E+09 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.120644E+09 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.193899E+09 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.410448E+09 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.112033E+10 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.184111E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.180114E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.877565E+09 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.370080E+09 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.101630E+09 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.145703E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.731737E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.101630E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.184111E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT TNE
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.211121E+09 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.193034E+09 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.112119E+09 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.100526E+09 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.329091E+09 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.106387E+10 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.175417E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.157867E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.619986E+09 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.125128E+09 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.105596E+09 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.177613E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.637092E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.100526E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.175417E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT TN1
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.151528E+09 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.141818E+09 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 78164841.18 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 63081755.44 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.245426E+09 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.910916E+09 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.149193E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.130802E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.526608E+09 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 86483010.62 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 72204493.27 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.126268E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.520244E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 63081755.44 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.149193E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT TN2
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.151420E+09 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.141680E+09 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 78205835.48 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 63461625.28 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.246770E+09 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.909805E+09 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.149135E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.130764E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.527087E+09 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 87056532.69 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 72017878.41 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.126133E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.520263E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 63461625.28 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.149135E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT TS1
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.122553E+09 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.104792E+09 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 86813924.49 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.148181E+09 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.324682E+09 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.970609E+09 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.158337E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.153920E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.791677E+09 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.352472E+09 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 72403776.22 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 97766489.80 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.619452E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 72403776.22 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.158337E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT TS2
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.122508E+09 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.104833E+09 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 87618671.84 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.149650E+09 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.326154E+09 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.969431E+09 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.158272E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.153862E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.792064E+09 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.353305E+09 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 72779081.24 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 97814660.77 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.619750E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 72779081.24 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.158272E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT GSW
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 0.119283E+09 | 0.00 | 0.274339E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.109554E+09 | 0.00 | 0.251962E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 65589250.14 | 0.00 | 0.150848E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 30001268.56 | 53729176.49 | 0.597741E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 26158440.89 | 0.334809E+09 | 39990971.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.164761E+09 | 0.236916E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.298599E+09 | 0.438156E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.317016E+09 | 0.458013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.182255E+09 | 0.259279E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 94767608.08 | 0.132755E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 33595442.51 | 39094080.50 | 0.704044E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 78610448.81 | 0.00 | 0.180796E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.152019E+10 | 0.156788E+11 | 0.992122E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 26158440.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.317016E+09 | 0.458013E+10 | 0.274339E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT GNW
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 0.148219E+09 | 0.00 | 0.342751E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.147603E+09 | 0.00 | 0.341327E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 93261972.02 | 0.00 | 0.215665E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 36992203.96 | 0.00 | 0.855433E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 20003553.64 | 0.235761E+09 | 68583686.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.151105E+09 | 0.218539E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.278906E+09 | 0.411381E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.271076E+09 | 0.393171E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.127629E+09 | 0.182440E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 24944303.03 | 0.352708E+09 | 2125075.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 49139362.99 | 0.00 | 0.113633E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.110370E+09 | 0.00 | 0.255226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.145925E+10 | 0.126438E+11 | 0.136122E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 20003553.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.278906E+09 | 0.411381E+10 | 0.342751E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT OFFICE
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 0.120728E+10 | 0.00 | 0.100664E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.109044E+10 | 0.00 | 0.981825E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.120728E+10 | 0.00 | 0.296650E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.116833E+10 | 0.145700E+09 | 30610895.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.120728E+10 | 0.618647E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.116833E+10 | 0.204726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.120728E+10 | 0.290348E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.120728E+10 | 0.342857E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.116833E+10 | 0.209504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.120728E+10 | 0.140888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.116833E+10 | 0.185805E+09 | 69201984.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.120728E+10 | 0.00 | 0.334641E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.142147E+11 | 0.128334E+11 | 0.271957E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 0.109044E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.120728E+10 | 0.342857E+10 | 0.100664E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT GNE
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 0.146060E+09 | 0.00 | 0.341087E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.144745E+09 | 0.00 | 0.338014E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 93514973.86 | 0.00 | 0.218381E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 36047117.38 | 17347.38 | 0.841760E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 21392500.32 | 0.259238E+09 | 69289971.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.143110E+09 | 0.210012E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.272779E+09 | 0.409052E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.265286E+09 | 0.391219E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.125609E+09 | 0.182341E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 22831951.56 | 0.328269E+09 | 1764102.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 46508300.31 | 0.00 | 0.108608E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.108054E+09 | 0.00 | 0.252332E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.142594E+10 | 0.125138E+11 | 0.134970E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 21392500.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.272779E+09 | 0.409052E+10 | 0.341087E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT GN1
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 0.101855E+09 | 0.00 | 0.241305E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.103778E+09 | 0.00 | 0.245861E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 63552189.17 | 0.00 | 0.150562E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 20814747.05 | 0.00 | 0.493125E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 15252172.52 | 0.206158E+09 | 14720242.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.132365E+09 | 0.195241E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.238862E+09 | 0.359719E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.223355E+09 | 0.330429E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.110032E+09 | 0.160309E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 20301956.56 | 0.293450E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 29254040.11 | 0.00 | 0.693061E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 73419323.05 | 0.00 | 0.173939E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.113284E+10 | 0.109566E+11 | 0.931758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 15252172.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.238862E+09 | 0.359719E+10 | 0.245861E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT GN2
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 0.101811E+09 | 0.00 | 0.241226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.103715E+09 | 0.00 | 0.245736E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 63623277.08 | 0.00 | 0.150745E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 20816468.58 | 0.00 | 0.493213E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 15456197.45 | 0.209152E+09 | 14611443.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.132095E+09 | 0.194878E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.238742E+09 | 0.359623E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.223269E+09 | 0.330381E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.110087E+09 | 0.160423E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 20213303.26 | 0.292255E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 29130174.71 | 0.00 | 0.690193E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 73355553.86 | 0.00 | 0.173804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.113231E+10 | 0.109545E+11 | 0.931313E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 15456197.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.238742E+09 | 0.359623E+10 | 0.245736E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT GS1
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 74791493.02 | 0.00 | 0.175445E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 67862907.50 | 0.00 | 0.159192E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 37811636.50 | 0.00 | 0.886980E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 16141829.33 | 49297908.08 | 0.293755E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 21818813.88 | 0.303683E+09 | 686451.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.147192E+09 | 0.215221E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.260066E+09 | 0.388447E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.270772E+09 | 0.397820E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.167496E+09 | 0.242105E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 98246656.00 | 0.139314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 20669587.80 | 88217076.11 | 0.329737E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 43980305.18 | 0.00 | 0.103168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.122685E+10 | 0.142703E+11 | 0.588921E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 16141829.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.270772E+09 | 0.397820E+10 | 0.175445E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT GS2
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 83924471.98 | 0.00 | 0.196700E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 74951325.16 | 0.00 | 0.175669E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 41622036.50 | 0.00 | 0.975526E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 17381898.33 | 55386648.34 | 0.312044E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 25029256.84 | 0.348378E+09 | 264172.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.161323E+09 | 0.235762E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.281683E+09 | 0.420676E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.292667E+09 | 0.430146E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.183527E+09 | 0.265324E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.106705E+09 | 0.151191E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 23286996.24 | 0.102281E+09 | 0.366118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 48528565.72 | 0.00 | 0.113740E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.134063E+10 | 0.155370E+11 | 0.651504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 17381898.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.292667E+09 | 0.430146E+10 | 0.196700E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT MSW
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 0.200239E+09 | 0.00 | 0.451385E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.164639E+09 | 0.00 | 0.371134E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 64936466.35 | 22957861.68 | 0.142415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 77936134.12 | 0.804338E+09 | 0.398962E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.195847E+09 | 0.263282E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.499434E+09 | 0.706825E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.745490E+09 | 0.107459E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.737309E+09 | 0.104528E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.414467E+09 | 0.578975E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.214844E+09 | 0.296237E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 74547641.72 | 0.135448E+09 | 0.144452E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.143327E+09 | 302356.22 | 0.323037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.353302E+10 | 0.406150E+11 | 0.147232E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 64936466.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.745490E+09 | 0.107459E+11 | 0.451385E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT MNW
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 0.260697E+09 | 0.00 | 0.589428E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.240318E+09 | 0.00 | 0.543350E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.114104E+09 | 0.00 | 0.257986E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 47504449.98 | 0.278404E+09 | 0.602098E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.158616E+09 | 0.213686E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.471768E+09 | 0.669473E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.704285E+09 | 0.101770E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.639051E+09 | 0.907049E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.295039E+09 | 0.413076E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 65486347.18 | 0.895223E+09 | 29057124.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.104764E+09 | 0.00 | 0.236869E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.209554E+09 | 0.00 | 0.473793E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.331119E+10 | 0.333835E+11 | 0.216454E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 47504449.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.704285E+09 | 0.101770E+11 | 0.589428E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT MSE
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 0.196712E+09 | 0.00 | 0.447476E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.159991E+09 | 0.00 | 0.363944E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 64640758.18 | 8214704.88 | 0.145602E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 76427297.86 | 0.799798E+09 | 0.397052E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.196416E+09 | 0.268011E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.479646E+09 | 0.689021E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.730039E+09 | 0.107010E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.721941E+09 | 0.104097E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.408834E+09 | 0.580110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.207083E+09 | 0.289904E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 72081435.41 | 0.155167E+09 | 0.137080E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.139513E+09 | 0.00 | 0.317361E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.345332E+10 | 0.403443E+11 | 0.145117E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 64640758.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.730039E+09 | 0.107010E+11 | 0.447476E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT MNE
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 0.256706E+09 | 0.00 | 0.585986E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.234998E+09 | 0.00 | 0.536433E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.114885E+09 | 0.00 | 0.262249E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 46016819.81 | 0.265284E+09 | 0.603888E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.159009E+09 | 0.217512E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.452008E+09 | 0.651310E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.688927E+09 | 0.101282E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.625071E+09 | 0.902487E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.290562E+09 | 0.413046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 60030238.82 | 0.835761E+09 | 23945148.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 98919807.98 | 0.00 | 0.225805E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.204828E+09 | 0.00 | 0.467563E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.323196E+10 | 0.330728E+11 | 0.214082E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 46016819.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.688927E+09 | 0.101282E+11 | 0.585986E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT MN1
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 0.162648E+09 | 0.00 | 0.375841E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.155181E+09 | 0.00 | 0.358588E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 66043122.89 | 0.00 | 0.152610E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 23272010.94 | 0.179635E+09 | 0.231207E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.131405E+09 | 0.179671E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.379975E+09 | 0.547729E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.573798E+09 | 0.843365E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.507521E+09 | 0.732056E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.251332E+09 | 0.357425E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 55715413.90 | 0.788058E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 53802293.91 | 0.00 | 0.124324E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.124864E+09 | 0.00 | 0.288531E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.248556E+10 | 0.275701E+11 | 0.132302E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 23272010.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.573798E+09 | 0.843365E+10 | 0.375841E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT MN2
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 0.162542E+09 | 0.00 | 0.375695E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.155014E+09 | 0.00 | 0.358296E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 66205940.47 | 0.00 | 0.153027E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 23522743.73 | 0.182772E+09 | 0.231889E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.131615E+09 | 0.180026E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.379400E+09 | 0.547098E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.573480E+09 | 0.843248E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.507273E+09 | 0.732000E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.251416E+09 | 0.357671E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 55593515.53 | 0.786670E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 53552444.81 | 0.00 | 0.123780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.124708E+09 | 0.00 | 0.288247E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.248432E+10 | 0.275699E+11 | 0.132223E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 23522743.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.573480E+09 | 0.843248E+10 | 0.375695E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT MS1
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 0.105873E+09 | 0.00 | 0.243406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 83113162.15 | 0.00 | 0.191080E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 26055467.11 | 21480384.22 | 0.561181E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 59458656.78 | 0.733496E+09 | 0.119117E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.169971E+09 | 0.231278E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.408787E+09 | 0.586407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.616593E+09 | 0.902047E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.607078E+09 | 0.872637E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.373579E+09 | 0.528813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.223671E+09 | 0.311317E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 44476303.83 | 0.283536E+09 | 0.526839E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 66045474.89 | 4208910.13 | 0.151080E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.278470E+10 | 0.353677E+11 | 0.706280E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 26055467.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.616593E+09 | 0.902047E+10 | 0.243406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT MS2
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 0.105783E+09 | 0.00 | 0.243261E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 83029072.31 | 0.00 | 0.190936E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 26137829.86 | 21402339.39 | 0.563347E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 59904096.88 | 0.739361E+09 | 0.119913E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.170178E+09 | 0.231655E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.408195E+09 | 0.585785E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.616246E+09 | 0.901933E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.606767E+09 | 0.872581E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.373500E+09 | 0.528929E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.223587E+09 | 0.311328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 44795806.51 | 0.290154E+09 | 0.523037E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 65951556.60 | 4398017.23 | 0.150869E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.278407E+10 | 0.353774E+11 | 0.705695E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 26137829.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.616246E+09 | 0.901933E+10 | 0.243261E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT TSW
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 0.182677E+09 | 6395500.20 | 0.407549E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.158443E+09 | 1541350.79 | 0.354186E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 98363614.66 | 0.118275E+09 | 0.199631E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 76004216.76 | 0.501446E+09 | 0.862638E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 95550839.13 | 0.126144E+10 | 50680147.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.256558E+09 | 0.365496E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.406735E+09 | 0.588673E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.397966E+09 | 0.567498E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.198082E+09 | 0.278537E+10 | 371462.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 96386326.66 | 0.118533E+10 | 0.251129E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 89591616.18 | 61718644.39 | 0.189760E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.146945E+09 | 9388507.90 | 0.327075E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.220330E+10 | 0.211476E+11 | 0.159468E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 76004216.76 | 1541350.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.406735E+09 | 0.588673E+10 | 0.407549E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT TNW
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 0.214506E+09 | 0.00 | 0.480231E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.197321E+09 | 0.00 | 0.441758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.113152E+09 | 5985637.52 | 0.252337E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 59671208.73 | 0.201795E+09 | 0.997255E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 77580942.93 | 0.101241E+10 | 56954519.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.243535E+09 | 0.346415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.387322E+09 | 0.559531E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.348120E+09 | 0.494461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.140573E+09 | 0.196975E+10 | 1522860.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 46494854.82 | 0.355348E+09 | 0.471200E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.110244E+09 | 0.00 | 0.246811E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.181468E+09 | 0.00 | 0.406266E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.211999E+10 | 0.175494E+11 | 0.198010E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 46494854.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.387322E+09 | 0.559531E+10 | 0.480231E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT TSE
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 0.179337E+09 | 3856896.41 | 0.405227E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.154423E+09 | 116920.41 | 0.349493E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 95877918.01 | 94884794.21 | 0.200610E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 72438089.34 | 0.478120E+09 | 0.847635E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 93013766.89 | 0.125243E+10 | 50541374.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.244466E+09 | 0.355332E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.396364E+09 | 0.586578E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.387230E+09 | 0.564731E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.193374E+09 | 0.277652E+10 | 277986.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 90704116.46 | 0.113598E+10 | 0.244477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 85945556.96 | 60192006.45 | 0.184190E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.143566E+09 | 8086093.43 | 0.323517E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.213674E+10 | 0.208766E+11 | 0.157733E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 72438089.34 | 116920.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.396364E+09 | 0.586578E+10 | 0.405227E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT TNE
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 0.211121E+09 | 0.00 | 0.478296E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.193034E+09 | 0.00 | 0.437321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.112052E+09 | 259037.53 | 0.253813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 55969606.03 | 0.173514E+09 | 0.978592E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 75093462.41 | 0.997480E+09 | 57980372.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.232197E+09 | 0.336736E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.377859E+09 | 0.557857E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.339160E+09 | 0.492119E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.136351E+09 | 0.194803E+10 | 1447565.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 43448208.18 | 0.330493E+09 | 0.458358E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.105596E+09 | 0.00 | 0.239229E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.177613E+09 | 0.00 | 0.402384E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.205949E+10 | 0.173169E+11 | 0.196068E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 43448208.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.377859E+09 | 0.557857E+10 | 0.478296E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT TN1
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 0.151528E+09 | 0.00 | 0.345722E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.141818E+09 | 0.00 | 0.323567E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 78081946.70 | 324146.24 | 0.178095E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 35364419.27 | 0.107578E+09 | 0.624086E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 55490962.32 | 0.742277E+09 | 17246988.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.200421E+09 | 0.286877E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.324121E+09 | 0.471581E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.283255E+09 | 0.404825E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.116650E+09 | 0.164820E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 28508944.10 | 0.234035E+09 | 0.270907E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 72204493.27 | 0.00 | 0.164739E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.126268E+09 | 0.00 | 0.288089E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.161371E+10 | 0.143652E+11 | 0.139144E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 28508944.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.324121E+09 | 0.471581E+10 | 0.345722E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT TN2
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 0.151420E+09 | 0.00 | 0.345667E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.141680E+09 | 0.00 | 0.323433E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 78153041.16 | 206327.56 | 0.178376E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 35462139.08 | 0.108691E+09 | 0.624931E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 55766333.03 | 0.746528E+09 | 17369256.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.200063E+09 | 0.286596E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.323807E+09 | 0.471553E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.283012E+09 | 0.404840E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.116693E+09 | 0.165007E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 28655194.25 | 0.235797E+09 | 0.271876E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 72017878.41 | 0.00 | 0.164405E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.126133E+09 | 0.00 | 0.287941E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.161286E+10 | 0.143712E+11 | 0.139124E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 28655194.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.323807E+09 | 0.471553E+10 | 0.345667E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT TS1
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 0.120908E+09 | 6239437.06 | 0.274365E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.104279E+09 | 1923362.30 | 0.237242E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 62649865.65 | 92625990.44 | 0.126483E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 50366662.14 | 0.383601E+09 | 0.499343E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 73212971.00 | 0.986862E+09 | 13689532.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.213520E+09 | 0.306095E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.343776E+09 | 0.501110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.333627E+09 | 0.478796E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.175832E+09 | 0.249039E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 82542119.61 | 0.109294E+10 | 0.102858E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 54759384.60 | 67733119.91 | 0.112936E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 94265521.86 | 13297914.95 | 0.212402E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.170974E+10 | 0.179956E+11 | 0.102502E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 50366662.14 | 1923362.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.343776E+09 | 0.501110E+10 | 0.274365E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT TS2
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 0.120842E+09 | 6325273.84 | 0.274347E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.104234E+09 | 2247794.67 | 0.237207E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 62924682.63 | 94668215.98 | 0.126831E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 50707886.14 | 0.388084E+09 | 0.500304E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 73507774.18 | 0.991688E+09 | 13807213.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.213140E+09 | 0.305811E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.343437E+09 | 0.501083E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.333314E+09 | 0.478808E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.175823E+09 | 0.249251E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 82697499.27 | 0.109588E+10 | 0.103162E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 54729709.10 | 69306301.51 | 0.112666E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 94209034.30 | 13699939.16 | 0.212318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.170957E+10 | 0.180114E+11 | 0.102510E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 50707886.14 | 2247794.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.343437E+09 | 0.501083E+10 | 0.274347E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT GSW
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 0.119283E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.109554E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 65589250.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 30001268.56 | 0.00 | 0.00 | 0.00 | 13964994.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 26158440.89 | 0.00 | 0.00 | 0.00 | 86171245.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.164761E+09 | 0.00 | 0.00 | 0.00 | 0.589500E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.298599E+09 | 0.00 | 0.00 | 0.00 | 0.108488E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.317016E+09 | 0.00 | 0.00 | 0.00 | 0.115226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.182255E+09 | 0.00 | 0.00 | 0.00 | 0.643014E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 94767608.08 | 0.00 | 0.00 | 0.00 | 0.330864E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 33595442.51 | 0.00 | 0.00 | 0.00 | 10247291.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 78610448.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.152019E+10 | 0.00 | 0.00 | 0.00 | 0.391090E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 26158440.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.317016E+09 | 0.00 | 0.00 | 0.00 | 0.115226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT GNW
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 0.148219E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.147603E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 93261972.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 36992203.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 20003553.64 | 0.00 | 0.00 | 0.00 | 60631769.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.151105E+09 | 0.00 | 0.00 | 0.00 | 0.543201E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.278906E+09 | 0.00 | 0.00 | 0.00 | 0.101751E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.271076E+09 | 0.00 | 0.00 | 0.00 | 0.991099E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.127629E+09 | 0.00 | 0.00 | 0.00 | 0.453407E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 24944303.03 | 0.00 | 0.00 | 0.00 | 87640640.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 49139362.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.110370E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.145925E+10 | 0.00 | 0.00 | 0.00 | 0.315349E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 20003553.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.278906E+09 | 0.00 | 0.00 | 0.00 | 0.101751E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT OFFICE
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 0.120728E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.109044E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.120728E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.116833E+10 | 0.00 | 0.00 | 0.00 | 37708442.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.120728E+10 | 0.00 | 0.00 | 0.00 | 0.156199E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.116833E+10 | 0.00 | 0.00 | 0.00 | 0.499296E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.120728E+10 | 0.00 | 0.00 | 0.00 | 0.702599E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.120728E+10 | 0.00 | 0.00 | 0.00 | 0.838369E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.116833E+10 | 0.00 | 0.00 | 0.00 | 0.503251E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.120728E+10 | 0.00 | 0.00 | 0.00 | 0.343677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.116833E+10 | 0.00 | 0.00 | 0.00 | 48121686.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.120728E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.142147E+11 | 0.00 | 0.00 | 0.00 | 0.312922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 0.109044E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.120728E+10 | 0.00 | 0.00 | 0.00 | 0.838369E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT GNE
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 0.146060E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.144745E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 93514973.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 36047117.38 | 0.00 | 0.00 | 0.00 | 4532.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 21392500.32 | 0.00 | 0.00 | 0.00 | 66536757.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.143110E+09 | 0.00 | 0.00 | 0.00 | 0.521856E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.272779E+09 | 0.00 | 0.00 | 0.00 | 0.100941E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.265286E+09 | 0.00 | 0.00 | 0.00 | 0.983566E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.125609E+09 | 0.00 | 0.00 | 0.00 | 0.452444E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 22831951.56 | 0.00 | 0.00 | 0.00 | 81420483.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 46508300.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.108054E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.142594E+10 | 0.00 | 0.00 | 0.00 | 0.311524E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 21392500.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.272779E+09 | 0.00 | 0.00 | 0.00 | 0.100941E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT GN1
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 0.101855E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.103778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 63552189.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 20814747.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 15252172.52 | 0.00 | 0.00 | 0.00 | 53009791.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.132365E+09 | 0.00 | 0.00 | 0.00 | 0.484002E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.238862E+09 | 0.00 | 0.00 | 0.00 | 0.886566E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.223355E+09 | 0.00 | 0.00 | 0.00 | 0.831221E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.110032E+09 | 0.00 | 0.00 | 0.00 | 0.397857E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 20301956.56 | 0.00 | 0.00 | 0.00 | 72918584.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 29254040.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 73419323.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.113284E+10 | 0.00 | 0.00 | 0.00 | 0.272557E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 15252172.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.238862E+09 | 0.00 | 0.00 | 0.00 | 0.886566E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT GN2
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 0.101811E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.103715E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 63623277.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 20816468.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 15456197.45 | 0.00 | 0.00 | 0.00 | 53773927.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.132095E+09 | 0.00 | 0.00 | 0.00 | 0.483140E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.238742E+09 | 0.00 | 0.00 | 0.00 | 0.886347E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.223269E+09 | 0.00 | 0.00 | 0.00 | 0.831110E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.110087E+09 | 0.00 | 0.00 | 0.00 | 0.398147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 20213303.26 | 0.00 | 0.00 | 0.00 | 72618090.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 29130174.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 73355553.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.113231E+10 | 0.00 | 0.00 | 0.00 | 0.272514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 15456197.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.238742E+09 | 0.00 | 0.00 | 0.00 | 0.886347E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT GS1
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 74791493.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 67862907.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 37811636.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 16141829.33 | 0.00 | 0.00 | 0.00 | 12800239.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 21818813.88 | 0.00 | 0.00 | 0.00 | 78123025.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.147192E+09 | 0.00 | 0.00 | 0.00 | 0.534503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.260066E+09 | 0.00 | 0.00 | 0.00 | 0.959280E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.270772E+09 | 0.00 | 0.00 | 0.00 | 0.999415E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.167496E+09 | 0.00 | 0.00 | 0.00 | 0.600017E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 98246656.00 | 0.00 | 0.00 | 0.00 | 0.348033E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 20669587.80 | 0.00 | 0.00 | 0.00 | 23058681.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 43980305.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.122685E+10 | 0.00 | 0.00 | 0.00 | 0.355523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 16141829.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.270772E+09 | 0.00 | 0.00 | 0.00 | 0.999415E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT GS2
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 83924471.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 74951325.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 41622036.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 17381898.33 | 0.00 | 0.00 | 0.00 | 14367483.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 25029256.84 | 0.00 | 0.00 | 0.00 | 89489947.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.161323E+09 | 0.00 | 0.00 | 0.00 | 0.584712E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.281683E+09 | 0.00 | 0.00 | 0.00 | 0.103699E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.292667E+09 | 0.00 | 0.00 | 0.00 | 0.107786E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.183527E+09 | 0.00 | 0.00 | 0.00 | 0.656433E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.106705E+09 | 0.00 | 0.00 | 0.00 | 0.377548E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 23286996.24 | 0.00 | 0.00 | 0.00 | 26709945.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 48528565.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.134063E+10 | 0.00 | 0.00 | 0.00 | 0.386411E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 17381898.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.292667E+09 | 0.00 | 0.00 | 0.00 | 0.107786E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT MSW
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 0.200239E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.164639E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 64936466.35 | 0.00 | 0.00 | 0.00 | 5973833.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 77936134.12 | 0.00 | 0.00 | 0.00 | 0.205689E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.195847E+09 | 0.00 | 0.00 | 0.00 | 0.672170E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.499434E+09 | 0.00 | 0.00 | 0.00 | 0.175353E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.745490E+09 | 0.00 | 0.00 | 0.00 | 0.266328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.737309E+09 | 0.00 | 0.00 | 0.00 | 0.263790E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.414467E+09 | 0.00 | 0.00 | 0.00 | 0.143917E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.214844E+09 | 0.00 | 0.00 | 0.00 | 0.738027E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 74547641.72 | 0.00 | 0.00 | 0.00 | 35384773.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.143327E+09 | 0.00 | 0.00 | 0.00 | 80943.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.353302E+10 | 0.00 | 0.00 | 0.00 | 0.101512E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 64936466.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.745490E+09 | 0.00 | 0.00 | 0.00 | 0.266328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT MNW
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 0.260697E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.240318E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.114104E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 47504449.98 | 0.00 | 0.00 | 0.00 | 71710314.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.158616E+09 | 0.00 | 0.00 | 0.00 | 0.546340E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.471768E+09 | 0.00 | 0.00 | 0.00 | 0.166042E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.704285E+09 | 0.00 | 0.00 | 0.00 | 0.252127E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.639051E+09 | 0.00 | 0.00 | 0.00 | 0.229456E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.295039E+09 | 0.00 | 0.00 | 0.00 | 0.102951E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 65486347.18 | 0.00 | 0.00 | 0.00 | 0.222466E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.104764E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.209554E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.331119E+10 | 0.00 | 0.00 | 0.00 | 0.834628E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 47504449.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.704285E+09 | 0.00 | 0.00 | 0.00 | 0.252127E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT MSE
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 0.196712E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.159991E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 64640758.18 | 0.00 | 0.00 | 0.00 | 2165665.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 76427297.86 | 0.00 | 0.00 | 0.00 | 0.204185E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.196416E+09 | 0.00 | 0.00 | 0.00 | 0.683423E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.479646E+09 | 0.00 | 0.00 | 0.00 | 0.170695E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.730039E+09 | 0.00 | 0.00 | 0.00 | 0.264388E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.721941E+09 | 0.00 | 0.00 | 0.00 | 0.261753E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.408834E+09 | 0.00 | 0.00 | 0.00 | 0.143852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.207083E+09 | 0.00 | 0.00 | 0.00 | 0.721059E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 72081435.41 | 0.00 | 0.00 | 0.00 | 40495000.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.139513E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.345332E+10 | 0.00 | 0.00 | 0.00 | 0.100582E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 64640758.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.730039E+09 | 0.00 | 0.00 | 0.00 | 0.264388E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT MNE
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 0.256706E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.234998E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.114885E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 46016819.81 | 0.00 | 0.00 | 0.00 | 68233456.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.159009E+09 | 0.00 | 0.00 | 0.00 | 0.555641E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.452008E+09 | 0.00 | 0.00 | 0.00 | 0.161336E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.688927E+09 | 0.00 | 0.00 | 0.00 | 0.250151E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.625071E+09 | 0.00 | 0.00 | 0.00 | 0.227567E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.290562E+09 | 0.00 | 0.00 | 0.00 | 0.102792E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 60030238.82 | 0.00 | 0.00 | 0.00 | 0.207371E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 98919807.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.204828E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.323196E+10 | 0.00 | 0.00 | 0.00 | 0.824969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 46016819.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.688927E+09 | 0.00 | 0.00 | 0.00 | 0.250151E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT MN1
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 0.162648E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.155181E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 66043122.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 23272010.94 | 0.00 | 0.00 | 0.00 | 46331126.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.131405E+09 | 0.00 | 0.00 | 0.00 | 0.459871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.379975E+09 | 0.00 | 0.00 | 0.00 | 0.135709E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.573798E+09 | 0.00 | 0.00 | 0.00 | 0.208404E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.507521E+09 | 0.00 | 0.00 | 0.00 | 0.184928E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.251332E+09 | 0.00 | 0.00 | 0.00 | 0.889819E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 55715413.90 | 0.00 | 0.00 | 0.00 | 0.196043E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 53802293.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.124864E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.248556E+10 | 0.00 | 0.00 | 0.00 | 0.688248E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 23272010.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.573798E+09 | 0.00 | 0.00 | 0.00 | 0.208404E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT MN2
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 0.162542E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.155014E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 66205940.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 23522743.73 | 0.00 | 0.00 | 0.00 | 47133492.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.131615E+09 | 0.00 | 0.00 | 0.00 | 0.460768E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.379400E+09 | 0.00 | 0.00 | 0.00 | 0.135554E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.573480E+09 | 0.00 | 0.00 | 0.00 | 0.208367E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.507273E+09 | 0.00 | 0.00 | 0.00 | 0.184906E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.251416E+09 | 0.00 | 0.00 | 0.00 | 0.890425E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 55593515.53 | 0.00 | 0.00 | 0.00 | 0.195684E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 53552444.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.124708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.248432E+10 | 0.00 | 0.00 | 0.00 | 0.688228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 23522743.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.573480E+09 | 0.00 | 0.00 | 0.00 | 0.208367E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT MS1
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 0.105873E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 83113162.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 26055467.11 | 0.00 | 0.00 | 0.00 | 5634760.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 59458656.78 | 0.00 | 0.00 | 0.00 | 0.187855E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.169971E+09 | 0.00 | 0.00 | 0.00 | 0.591482E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.408787E+09 | 0.00 | 0.00 | 0.00 | 0.145412E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.616593E+09 | 0.00 | 0.00 | 0.00 | 0.223152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.607078E+09 | 0.00 | 0.00 | 0.00 | 0.220019E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.373579E+09 | 0.00 | 0.00 | 0.00 | 0.131377E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.223671E+09 | 0.00 | 0.00 | 0.00 | 0.777572E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 44476303.83 | 0.00 | 0.00 | 0.00 | 73835605.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 66045474.89 | 0.00 | 0.00 | 0.00 | 1120815.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.278470E+10 | 0.00 | 0.00 | 0.00 | 0.883710E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 26055467.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.616593E+09 | 0.00 | 0.00 | 0.00 | 0.223152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT MS2
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 0.105783E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 83029072.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 26137829.86 | 0.00 | 0.00 | 0.00 | 5615906.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 59904096.88 | 0.00 | 0.00 | 0.00 | 0.189345E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.170178E+09 | 0.00 | 0.00 | 0.00 | 0.592415E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.408195E+09 | 0.00 | 0.00 | 0.00 | 0.145256E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.616246E+09 | 0.00 | 0.00 | 0.00 | 0.223112E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.606767E+09 | 0.00 | 0.00 | 0.00 | 0.219989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.373500E+09 | 0.00 | 0.00 | 0.00 | 0.131397E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.223587E+09 | 0.00 | 0.00 | 0.00 | 0.777551E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 44795806.51 | 0.00 | 0.00 | 0.00 | 75545432.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 65951556.60 | 0.00 | 0.00 | 0.00 | 1170938.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.278407E+10 | 0.00 | 0.00 | 0.00 | 0.883918E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 26137829.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.616246E+09 | 0.00 | 0.00 | 0.00 | 0.223112E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT TSW
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 0.182677E+09 | 0.00 | 0.00 | 0.00 | 1687132.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.158443E+09 | 0.00 | 0.00 | 0.00 | 410537.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 98363614.66 | 0.00 | 0.00 | 0.00 | 30753380.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 76004216.76 | 0.00 | 0.00 | 0.00 | 0.127747E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 95550839.13 | 0.00 | 0.00 | 0.00 | 0.320559E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.256558E+09 | 0.00 | 0.00 | 0.00 | 0.903808E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.406735E+09 | 0.00 | 0.00 | 0.00 | 0.145759E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.397966E+09 | 0.00 | 0.00 | 0.00 | 0.142925E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.198082E+09 | 0.00 | 0.00 | 0.00 | 0.689292E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 96386326.66 | 0.00 | 0.00 | 0.00 | 0.292678E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 89591616.18 | 0.00 | 0.00 | 0.00 | 16105504.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.146945E+09 | 0.00 | 0.00 | 0.00 | 2481453.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.220330E+10 | 0.00 | 0.00 | 0.00 | 0.527236E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 76004216.76 | 0.00 | 0.00 | 0.00 | 410537.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.406735E+09 | 0.00 | 0.00 | 0.00 | 0.145759E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT TNW
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 0.214506E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.197321E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.113152E+09 | 0.00 | 0.00 | 0.00 | 1516339.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 59671208.73 | 0.00 | 0.00 | 0.00 | 51840808.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 77580942.93 | 0.00 | 0.00 | 0.00 | 0.258171E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.243535E+09 | 0.00 | 0.00 | 0.00 | 0.857759E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.387322E+09 | 0.00 | 0.00 | 0.00 | 0.138712E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.348120E+09 | 0.00 | 0.00 | 0.00 | 0.125150E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.140573E+09 | 0.00 | 0.00 | 0.00 | 0.490348E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 46494854.82 | 0.00 | 0.00 | 0.00 | 87970731.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.110244E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.181468E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.211999E+10 | 0.00 | 0.00 | 0.00 | 0.438623E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 46494854.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.387322E+09 | 0.00 | 0.00 | 0.00 | 0.138712E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT TSE
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 0.179337E+09 | 0.00 | 0.00 | 0.00 | 1020867.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.154423E+09 | 0.00 | 0.00 | 0.00 | 31189.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 95877918.01 | 0.00 | 0.00 | 0.00 | 24765897.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 72438089.34 | 0.00 | 0.00 | 0.00 | 0.121461E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 93013766.89 | 0.00 | 0.00 | 0.00 | 0.317434E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.244466E+09 | 0.00 | 0.00 | 0.00 | 0.875867E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.396364E+09 | 0.00 | 0.00 | 0.00 | 0.144475E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.387230E+09 | 0.00 | 0.00 | 0.00 | 0.141391E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.193374E+09 | 0.00 | 0.00 | 0.00 | 0.684191E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 90704116.46 | 0.00 | 0.00 | 0.00 | 0.279376E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 85945556.96 | 0.00 | 0.00 | 0.00 | 15684513.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.143566E+09 | 0.00 | 0.00 | 0.00 | 2136788.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.213674E+10 | 0.00 | 0.00 | 0.00 | 0.518063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 72438089.34 | 0.00 | 0.00 | 0.00 | 31189.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.396364E+09 | 0.00 | 0.00 | 0.00 | 0.144475E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT TNE
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 0.211121E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.193034E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.112052E+09 | 0.00 | 0.00 | 0.00 | 66230.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 55969606.03 | 0.00 | 0.00 | 0.00 | 44556355.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 75093462.41 | 0.00 | 0.00 | 0.00 | 0.253998E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.232197E+09 | 0.00 | 0.00 | 0.00 | 0.831672E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.377859E+09 | 0.00 | 0.00 | 0.00 | 0.137631E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.339160E+09 | 0.00 | 0.00 | 0.00 | 0.123951E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.136351E+09 | 0.00 | 0.00 | 0.00 | 0.483635E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 43448208.18 | 0.00 | 0.00 | 0.00 | 81680073.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.105596E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.177613E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.205949E+10 | 0.00 | 0.00 | 0.00 | 0.431143E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 43448208.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.377859E+09 | 0.00 | 0.00 | 0.00 | 0.137631E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT TN1
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 0.151528E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.141818E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 78081946.70 | 0.00 | 0.00 | 0.00 | 82894.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 35364419.27 | 0.00 | 0.00 | 0.00 | 27717336.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 55490962.32 | 0.00 | 0.00 | 0.00 | 0.189935E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.200421E+09 | 0.00 | 0.00 | 0.00 | 0.710495E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.324121E+09 | 0.00 | 0.00 | 0.00 | 0.116781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.283255E+09 | 0.00 | 0.00 | 0.00 | 0.102476E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.116650E+09 | 0.00 | 0.00 | 0.00 | 0.409958E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 28508944.10 | 0.00 | 0.00 | 0.00 | 57974066.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 72204493.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.126268E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.161371E+10 | 0.00 | 0.00 | 0.00 | 0.358873E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 28508944.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.324121E+09 | 0.00 | 0.00 | 0.00 | 0.116781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT TN2
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 0.151420E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.141680E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 78153041.16 | 0.00 | 0.00 | 0.00 | 52794.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 35462139.08 | 0.00 | 0.00 | 0.00 | 27999486.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 55766333.03 | 0.00 | 0.00 | 0.00 | 0.191004E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.200063E+09 | 0.00 | 0.00 | 0.00 | 0.709742E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.323807E+09 | 0.00 | 0.00 | 0.00 | 0.116755E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.283012E+09 | 0.00 | 0.00 | 0.00 | 0.102463E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.116693E+09 | 0.00 | 0.00 | 0.00 | 0.410394E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 28655194.25 | 0.00 | 0.00 | 0.00 | 58401338.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 72017878.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.126133E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.161286E+10 | 0.00 | 0.00 | 0.00 | 0.358977E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 28655194.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.323807E+09 | 0.00 | 0.00 | 0.00 | 0.116755E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT TS1
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 0.120908E+09 | 0.00 | 0.00 | 0.00 | 1644402.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.104279E+09 | 0.00 | 0.00 | 0.00 | 512742.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 62649865.65 | 0.00 | 0.00 | 0.00 | 24164058.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 50366662.14 | 0.00 | 0.00 | 0.00 | 97814362.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 73212971.00 | 0.00 | 0.00 | 0.00 | 0.251469E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.213520E+09 | 0.00 | 0.00 | 0.00 | 0.757089E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.343776E+09 | 0.00 | 0.00 | 0.00 | 0.123959E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.333627E+09 | 0.00 | 0.00 | 0.00 | 0.120557E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.175832E+09 | 0.00 | 0.00 | 0.00 | 0.615845E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 82542119.61 | 0.00 | 0.00 | 0.00 | 0.269930E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 54759384.60 | 0.00 | 0.00 | 0.00 | 17644391.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 94265521.86 | 0.00 | 0.00 | 0.00 | 3500967.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.170974E+10 | 0.00 | 0.00 | 0.00 | 0.448478E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 50366662.14 | 0.00 | 0.00 | 0.00 | 512742.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.343776E+09 | 0.00 | 0.00 | 0.00 | 0.123959E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT TS2
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 0.120842E+09 | 0.00 | 0.00 | 0.00 | 1666585.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.104234E+09 | 0.00 | 0.00 | 0.00 | 599105.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 62924682.63 | 0.00 | 0.00 | 0.00 | 24693989.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 50707886.14 | 0.00 | 0.00 | 0.00 | 98941961.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 73507774.18 | 0.00 | 0.00 | 0.00 | 0.252646E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.213140E+09 | 0.00 | 0.00 | 0.00 | 0.756290E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.343437E+09 | 0.00 | 0.00 | 0.00 | 0.123928E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.333314E+09 | 0.00 | 0.00 | 0.00 | 0.120531E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.175823E+09 | 0.00 | 0.00 | 0.00 | 0.616240E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 82697499.27 | 0.00 | 0.00 | 0.00 | 0.270608E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 54729709.10 | 0.00 | 0.00 | 0.00 | 18049372.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 94209034.30 | 0.00 | 0.00 | 0.00 | 3605626.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.170957E+10 | 0.00 | 0.00 | 0.00 | 0.448793E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 50707886.14 | 0.00 | 0.00 | 0.00 | 599105.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.343437E+09 | 0.00 | 0.00 | 0.00 | 0.123928E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: G SW APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.179518E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.150552E+10 | 0.00 | 0.00 | 0.35 |
| February | 0.181351E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.143967E+10 | 0.00 | 0.00 | 0.35 |
| March | 0.394863E+09 | 0.00 | 0.00 | 0.00 | 89513.70 | 0.925465E+09 | 0.00 | 0.00 | 0.35 |
| April | 0.506045E+09 | 2308345.93 | 0.00 | 103222.39 | 32667.41 | 0.364328E+09 | 23960178.85 | 0.00 | 0.35 |
| May | 0.508548E+09 | 19847822.63 | 0.00 | 413465.94 | 0.00 | 6455819.64 | 80307373.88 | 0.00 | 0.35 |
| June | 26581887.00 | 0.281585E+09 | 0.00 | 952483.66 | 0.00 | 0.00 | 0.134163E+09 | 0.00 | 0.36 |
| July | 0.00 | 0.927207E+09 | 0.00 | 92527.77 | 0.00 | 0.00 | 3574724.13 | 0.00 | 0.36 |
| August | 0.00 | 0.752922E+09 | 0.00 | 752209.17 | 0.00 | 0.00 | 50898224.47 | 0.00 | 0.36 |
| September | 22492861.96 | 0.193763E+09 | 0.00 | 2077895.48 | 0.00 | 0.00 | 0.279653E+09 | 0.00 | 0.35 |
| October | 0.287692E+09 | 18279580.66 | 0.00 | 2612826.56 | 0.00 | 0.00 | 0.496847E+09 | 0.00 | 0.35 |
| November | 0.714999E+09 | 0.00 | 0.00 | 184961.98 | 0.00 | 0.431187E+09 | 61772578.68 | 0.00 | 0.35 |
| December | 0.411539E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109793E+10 | 0.00 | 0.00 | 0.35 |
| Annual Sum or Average | 0.323363E+10 | 0.219591E+10 | 0.00 | 7189592.96 | 122181.10 | 0.577055E+10 | 0.113118E+10 | 0.00 | 0.35 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
| Maximum of Months | 0.714999E+09 | 0.927207E+09 | 0.00 | 2612826.56 | 89513.70 | 0.150552E+10 | 0.496847E+09 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: G NW APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 4155639.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.167997E+10 | 0.00 | 0.00 | 0.35 |
| February | 1422986.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.161943E+10 | 0.00 | 0.00 | 0.35 |
| March | 83221755.18 | 0.00 | 6435.35 | 0.00 | 147917.81 | 0.122995E+10 | 0.00 | 144.46 | 0.35 |
| April | 0.362017E+09 | 0.00 | 0.00 | 0.00 | 3193128.70 | 0.501986E+09 | 0.00 | 0.00 | 0.35 |
| May | 0.506437E+09 | 19263404.91 | 0.00 | 192566.38 | 0.00 | 33878095.76 | 33283694.34 | 0.00 | 0.35 |
| June | 32405020.15 | 0.270722E+09 | 0.00 | 851045.27 | 0.00 | 0.00 | 0.130194E+09 | 0.00 | 0.36 |
| July | 0.00 | 0.901809E+09 | 0.00 | 92159.13 | 0.00 | 0.00 | 3828514.31 | 0.00 | 0.36 |
| August | 253687.97 | 0.716568E+09 | 0.00 | 667478.87 | 0.00 | 0.00 | 54512937.99 | 0.00 | 0.36 |
| September | 99183283.52 | 0.170492E+09 | 0.00 | 1229000.87 | 0.00 | 0.00 | 0.210043E+09 | 0.00 | 0.36 |
| October | 0.601300E+09 | 8568381.45 | 0.00 | 660053.51 | 0.00 | 0.00 | 0.176812E+09 | 0.00 | 0.35 |
| November | 0.468638E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.681901E+09 | 0.00 | 0.00 | 0.35 |
| December | 12630885.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.149260E+10 | 0.00 | 0.00 | 0.35 |
| Annual Sum or Average | 0.217166E+10 | 0.208742E+10 | 6435.35 | 3692304.03 | 3341046.51 | 0.723971E+10 | 0.608673E+09 | 144.46 | 0.35 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
| Maximum of Months | 0.601300E+09 | 0.901809E+09 | 6435.35 | 1229000.87 | 3193128.70 | 0.167997E+10 | 0.210043E+09 | 144.46 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: OFFICE
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.140042E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.730849E+09 | 0.00 | 0.00 | 0.51 |
| February | 0.145833E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.634796E+09 | 0.00 | 0.00 | 0.51 |
| March | 0.148555E+10 | 0.00 | 0.00 | 0.00 | 46184.22 | 0.297416E+09 | 0.00 | 0.00 | 0.51 |
| April | 0.121967E+10 | 931526.81 | 0.00 | 167216.42 | 29365.71 | 30994637.53 | 76468198.74 | 0.00 | 0.52 |
| May | 0.894677E+09 | 16746728.65 | 0.00 | 585167.41 | 712722.36 | 0.00 | 0.123984E+09 | 0.00 | 0.52 |
| June | 0.475505E+09 | 0.203742E+09 | 0.00 | 745228.82 | 22182972.13 | 0.00 | 29964345.47 | 0.00 | 0.53 |
| July | 0.301273E+09 | 0.459698E+09 | 0.00 | 377642.25 | 71830540.75 | 0.00 | 5175662.32 | 0.00 | 0.53 |
| August | 0.362146E+09 | 0.425120E+09 | 0.00 | 838692.37 | 66000247.00 | 0.00 | 25653382.44 | 0.00 | 0.53 |
| September | 0.669745E+09 | 0.133194E+09 | 0.00 | 1653149.54 | 12058595.25 | 0.00 | 86095719.50 | 0.00 | 0.53 |
| October | 0.115780E+10 | 35984697.61 | 0.00 | 1361784.66 | 990522.34 | 0.00 | 0.177717E+09 | 0.00 | 0.52 |
| November | 0.154603E+10 | 0.00 | 0.00 | 320935.53 | 0.00 | 81841063.04 | 0.121632E+09 | 0.00 | 0.52 |
| December | 0.170821E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.297288E+09 | 0.00 | 0.00 | 0.51 |
| Annual Sum or Average | 0.126793E+11 | 0.127542E+10 | 0.00 | 6049817.02 | 0.173851E+09 | 0.207318E+10 | 0.646691E+09 | 0.00 | 0.52 |
| Minimum of Months | 0.301273E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.51 |
| Maximum of Months | 0.170821E+10 | 0.459698E+09 | 0.00 | 1653149.54 | 71830540.75 | 0.730849E+09 | 0.177717E+09 | 0.00 | 0.53 |
Report: MechanicalVentilationLoadsMonthly
For: G NE APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.168408E+10 | 0.00 | 0.00 | 0.35 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.162081E+10 | 0.00 | 0.00 | 0.35 |
| March | 76144917.17 | 0.00 | 10203.83 | 0.00 | 157288.10 | 0.123644E+10 | 0.00 | 210.49 | 0.35 |
| April | 0.376886E+09 | 0.00 | 0.00 | 0.00 | 2750137.13 | 0.486938E+09 | 0.00 | 0.00 | 0.35 |
| May | 0.506619E+09 | 20369225.21 | 0.00 | 202874.02 | 0.00 | 32572544.40 | 33588829.12 | 0.00 | 0.35 |
| June | 28102017.30 | 0.262863E+09 | 0.00 | 906000.77 | 0.00 | 0.00 | 0.138091E+09 | 0.00 | 0.36 |
| July | 0.00 | 0.899593E+09 | 0.00 | 102518.33 | 0.00 | 0.00 | 4286368.51 | 0.00 | 0.36 |
| August | 642073.28 | 0.715981E+09 | 0.00 | 694015.32 | 0.00 | 0.00 | 55014964.53 | 0.00 | 0.36 |
| September | 86839723.40 | 0.169620E+09 | 0.00 | 1274080.71 | 0.00 | 0.00 | 0.223575E+09 | 0.00 | 0.36 |
| October | 0.612775E+09 | 9240540.18 | 0.00 | 567491.44 | 0.00 | 0.00 | 0.167023E+09 | 0.00 | 0.35 |
| November | 0.500591E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.652344E+09 | 0.00 | 0.00 | 0.35 |
| December | 11693401.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.149350E+10 | 0.00 | 0.00 | 0.35 |
| Annual Sum or Average | 0.220029E+10 | 0.207767E+10 | 10203.83 | 3746980.58 | 2907425.23 | 0.720669E+10 | 0.621579E+09 | 210.49 | 0.35 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
| Maximum of Months | 0.612775E+09 | 0.899593E+09 | 10203.83 | 1274080.71 | 2750137.13 | 0.168408E+10 | 0.223575E+09 | 210.49 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: G N1 APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 76450890.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.161519E+10 | 0.00 | 0.00 | 0.35 |
| February | 21549207.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160539E+10 | 0.00 | 0.00 | 0.35 |
| March | 0.276171E+09 | 0.00 | 646.47 | 0.00 | 177639.88 | 0.104369E+10 | 0.00 | 1.83 | 0.35 |
| April | 0.609377E+09 | 0.00 | 0.00 | 0.00 | 3454577.69 | 0.263359E+09 | 0.00 | 0.00 | 0.35 |
| May | 0.553976E+09 | 18849836.98 | 0.00 | 192321.30 | 0.00 | 53793.56 | 43316341.18 | 0.00 | 0.35 |
| June | 8326477.12 | 0.264057E+09 | 0.00 | 894717.43 | 0.00 | 0.00 | 0.150015E+09 | 0.00 | 0.36 |
| July | 0.00 | 0.884295E+09 | 0.00 | 92186.33 | 0.00 | 0.00 | 3731740.21 | 0.00 | 0.36 |
| August | 78268.23 | 0.691673E+09 | 0.00 | 648282.80 | 0.00 | 0.00 | 55864164.81 | 0.00 | 0.36 |
| September | 34389633.49 | 0.163028E+09 | 0.00 | 1346989.05 | 0.00 | 0.00 | 0.277676E+09 | 0.00 | 0.36 |
| October | 0.572435E+09 | 7354654.88 | 0.00 | 665647.39 | 0.00 | 0.00 | 0.230548E+09 | 0.00 | 0.35 |
| November | 0.765049E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.407509E+09 | 0.00 | 0.00 | 0.35 |
| December | 0.226381E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128610E+10 | 0.00 | 0.00 | 0.35 |
| Annual Sum or Average | 0.314418E+10 | 0.202926E+10 | 646.47 | 3840144.29 | 3632217.57 | 0.622129E+10 | 0.761151E+09 | 1.83 | 0.35 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
| Maximum of Months | 0.765049E+09 | 0.884295E+09 | 646.47 | 1346989.05 | 3454577.69 | 0.161519E+10 | 0.277676E+09 | 1.83 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: G N2 APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 77689902.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.161395E+10 | 0.00 | 0.00 | 0.35 |
| February | 21122801.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160582E+10 | 0.00 | 0.00 | 0.35 |
| March | 0.275576E+09 | 0.00 | 650.67 | 0.00 | 178094.93 | 0.104425E+10 | 0.00 | 2.57 | 0.35 |
| April | 0.608931E+09 | 0.00 | 0.00 | 0.00 | 3406612.64 | 0.263969E+09 | 0.00 | 0.00 | 0.35 |
| May | 0.552695E+09 | 18925227.52 | 0.00 | 195830.15 | 0.00 | 53820.62 | 44251032.73 | 0.00 | 0.35 |
| June | 8525496.72 | 0.263587E+09 | 0.00 | 897773.77 | 0.00 | 0.00 | 0.149896E+09 | 0.00 | 0.36 |
| July | 0.00 | 0.884190E+09 | 0.00 | 93429.34 | 0.00 | 0.00 | 3750832.91 | 0.00 | 0.36 |
| August | 78266.17 | 0.691682E+09 | 0.00 | 648389.63 | 0.00 | 0.00 | 55900951.94 | 0.00 | 0.36 |
| September | 34192476.53 | 0.163037E+09 | 0.00 | 1349297.03 | 0.00 | 0.00 | 0.277810E+09 | 0.00 | 0.36 |
| October | 0.574098E+09 | 7392917.03 | 0.00 | 659957.56 | 0.00 | 0.00 | 0.228949E+09 | 0.00 | 0.35 |
| November | 0.766540E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.406493E+09 | 0.00 | 0.00 | 0.35 |
| December | 0.226875E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128561E+10 | 0.00 | 0.00 | 0.35 |
| Annual Sum or Average | 0.314632E+10 | 0.202882E+10 | 650.67 | 3844677.49 | 3584707.56 | 0.622014E+10 | 0.760558E+09 | 2.57 | 0.35 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
| Maximum of Months | 0.766540E+09 | 0.884190E+09 | 650.67 | 1349297.03 | 3406612.64 | 0.161395E+10 | 0.277810E+09 | 2.57 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: G S1 APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.573463E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111978E+10 | 0.00 | 0.00 | 0.35 |
| February | 0.586323E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104191E+10 | 0.00 | 0.00 | 0.35 |
| March | 0.907063E+09 | 0.00 | 0.00 | 0.00 | 84008.49 | 0.423373E+09 | 0.00 | 0.00 | 0.35 |
| April | 0.748470E+09 | 2362110.76 | 0.00 | 101979.57 | 0.00 | 0.136747E+09 | 31563793.40 | 0.00 | 0.35 |
| May | 0.525480E+09 | 19547769.43 | 0.00 | 405211.63 | 0.00 | 0.00 | 0.102460E+09 | 0.00 | 0.35 |
| June | 5709354.91 | 0.276975E+09 | 0.00 | 1005873.62 | 0.00 | 0.00 | 0.150118E+09 | 0.00 | 0.36 |
| July | 0.00 | 0.914675E+09 | 0.00 | 98318.31 | 0.00 | 0.00 | 3438087.39 | 0.00 | 0.36 |
| August | 0.00 | 0.735280E+09 | 0.00 | 744224.12 | 0.00 | 0.00 | 51400284.45 | 0.00 | 0.36 |
| September | 7748483.56 | 0.190346E+09 | 0.00 | 2180522.01 | 0.00 | 0.00 | 0.292430E+09 | 0.00 | 0.36 |
| October | 0.160487E+09 | 17582907.04 | 0.00 | 3155660.78 | 0.00 | 0.00 | 0.634820E+09 | 0.00 | 0.35 |
| November | 0.968728E+09 | 0.00 | 0.00 | 456480.32 | 0.00 | 0.102442E+09 | 0.174934E+09 | 0.00 | 0.35 |
| December | 0.100838E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.514164E+09 | 0.00 | 0.00 | 0.35 |
| Annual Sum or Average | 0.549185E+10 | 0.215677E+10 | 0.00 | 8148270.36 | 84008.49 | 0.333842E+10 | 0.144116E+10 | 0.00 | 0.35 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
| Maximum of Months | 0.100838E+10 | 0.914675E+09 | 0.00 | 3155660.78 | 84008.49 | 0.111978E+10 | 0.634820E+09 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: G S2 APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.456394E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123643E+10 | 0.00 | 0.00 | 0.35 |
| February | 0.485529E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114212E+10 | 0.00 | 0.00 | 0.35 |
| March | 0.835519E+09 | 0.00 | 0.00 | 0.00 | 96914.81 | 0.493767E+09 | 0.00 | 0.00 | 0.35 |
| April | 0.726316E+09 | 2375859.73 | 0.00 | 117073.26 | 0.00 | 0.153832E+09 | 38220788.06 | 0.00 | 0.35 |
| May | 0.515127E+09 | 20103877.10 | 0.00 | 482668.37 | 0.00 | 0.00 | 0.118703E+09 | 0.00 | 0.35 |
| June | 3302366.10 | 0.292239E+09 | 0.00 | 1073465.81 | 0.00 | 0.00 | 0.146128E+09 | 0.00 | 0.36 |
| July | 0.00 | 0.952639E+09 | 0.00 | 86608.52 | 0.00 | 0.00 | 2616471.49 | 0.00 | 0.36 |
| August | 0.00 | 0.758429E+09 | 0.00 | 791195.38 | 0.00 | 0.00 | 48019063.59 | 0.00 | 0.36 |
| September | 4979135.19 | 0.200066E+09 | 0.00 | 2352320.32 | 0.00 | 0.00 | 0.289970E+09 | 0.00 | 0.35 |
| October | 0.140069E+09 | 18453936.58 | 0.00 | 3378421.61 | 0.00 | 0.00 | 0.650258E+09 | 0.00 | 0.35 |
| November | 0.914209E+09 | 0.00 | 0.00 | 522842.25 | 0.00 | 0.142368E+09 | 0.191217E+09 | 0.00 | 0.35 |
| December | 0.896021E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.625063E+09 | 0.00 | 0.00 | 0.35 |
| Annual Sum or Average | 0.497746E+10 | 0.224431E+10 | 0.00 | 8804595.52 | 96914.81 | 0.379357E+10 | 0.148513E+10 | 0.00 | 0.35 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
| Maximum of Months | 0.914209E+09 | 0.952639E+09 | 0.00 | 3378421.61 | 96914.81 | 0.123643E+10 | 0.650258E+09 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: M SW APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.865211E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.250124E+10 | 0.00 | 0.00 | 0.35 |
| February | 0.107820E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.217313E+10 | 0.00 | 0.00 | 0.35 |
| March | 0.187749E+10 | 0.00 | 0.00 | 132495.50 | 0.00 | 0.778824E+09 | 49252724.47 | 0.00 | 0.35 |
| April | 0.134038E+10 | 5566616.15 | 0.00 | 1806137.34 | 0.00 | 0.231402E+09 | 0.354880E+09 | 0.00 | 0.35 |
| May | 0.457541E+09 | 45726547.20 | 0.00 | 5031113.64 | 0.00 | 0.00 | 0.876256E+09 | 0.00 | 0.35 |
| June | 3131498.24 | 0.646442E+09 | 0.00 | 2946031.09 | 0.00 | 0.00 | 0.271005E+09 | 0.00 | 0.36 |
| July | 0.00 | 0.194642E+10 | 0.00 | 141974.78 | 0.00 | 0.00 | 3919702.29 | 0.00 | 0.36 |
| August | 30540.39 | 0.152267E+10 | 0.00 | 1585059.65 | 0.00 | 0.00 | 98624278.03 | 0.00 | 0.36 |
| September | 56403195.41 | 0.372642E+09 | 0.00 | 4568243.95 | 0.00 | 0.00 | 0.540659E+09 | 0.00 | 0.36 |
| October | 0.699758E+09 | 37391345.49 | 0.00 | 5204162.93 | 0.00 | 0.00 | 0.852915E+09 | 0.00 | 0.35 |
| November | 0.142033E+10 | 0.00 | 0.00 | 494905.52 | 0.00 | 0.846928E+09 | 0.133058E+09 | 0.00 | 0.35 |
| December | 0.115980E+10 | 0.00 | 0.00 | 8272.99 | 0.00 | 0.185855E+10 | 6723286.02 | 0.00 | 0.35 |
| Annual Sum or Average | 0.895827E+10 | 0.457687E+10 | 0.00 | 21918397.39 | 0.00 | 0.839008E+10 | 0.318729E+10 | 0.00 | 0.35 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
| Maximum of Months | 0.187749E+10 | 0.194642E+10 | 0.00 | 5204162.93 | 0.00 | 0.250124E+10 | 0.876256E+09 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: M NW APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.158355E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.319766E+10 | 0.00 | 0.00 | 0.35 |
| February | 0.217551E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.301433E+10 | 0.00 | 0.00 | 0.35 |
| March | 0.110922E+10 | 0.00 | 0.00 | 0.00 | 15517.46 | 0.152635E+10 | 0.00 | 0.00 | 0.35 |
| April | 0.139699E+10 | 4802547.82 | 0.00 | 633071.16 | 0.00 | 0.312459E+09 | 0.151787E+09 | 0.00 | 0.35 |
| May | 0.530897E+09 | 45675831.55 | 0.00 | 4132131.03 | 0.00 | 0.00 | 0.798265E+09 | 0.00 | 0.35 |
| June | 4396180.07 | 0.633726E+09 | 0.00 | 2760339.35 | 0.00 | 0.00 | 0.268873E+09 | 0.00 | 0.36 |
| July | 0.00 | 0.191085E+10 | 0.00 | 150607.43 | 0.00 | 0.00 | 4158727.83 | 0.00 | 0.36 |
| August | 1522439.86 | 0.146336E+10 | 0.00 | 1415683.43 | 0.00 | 0.00 | 0.102118E+09 | 0.00 | 0.36 |
| September | 0.163858E+09 | 0.336326E+09 | 0.00 | 2843743.08 | 0.00 | 0.00 | 0.445138E+09 | 0.00 | 0.36 |
| October | 0.116867E+10 | 18481886.40 | 0.00 | 1513885.61 | 0.00 | 0.00 | 0.347470E+09 | 0.00 | 0.35 |
| November | 0.920823E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.137378E+10 | 0.00 | 0.00 | 0.35 |
| December | 0.206345E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.279187E+10 | 0.00 | 0.00 | 0.35 |
| Annual Sum or Average | 0.587863E+10 | 0.441323E+10 | 0.00 | 13449461.09 | 15517.46 | 0.122165E+11 | 0.211781E+10 | 0.00 | 0.35 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
| Maximum of Months | 0.139699E+10 | 0.191085E+10 | 0.00 | 4132131.03 | 15517.46 | 0.319766E+10 | 0.798265E+09 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: M SE APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.878370E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.248740E+10 | 0.00 | 0.00 | 0.35 |
| February | 0.113172E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.211902E+10 | 0.00 | 0.00 | 0.35 |
| March | 0.188154E+10 | 0.00 | 0.00 | 49434.41 | 0.00 | 0.791653E+09 | 28459738.91 | 0.00 | 0.35 |
| April | 0.132103E+10 | 5913622.63 | 0.00 | 1739460.28 | 0.00 | 0.232418E+09 | 0.381187E+09 | 0.00 | 0.35 |
| May | 0.448517E+09 | 47084247.31 | 0.00 | 5142105.06 | 0.00 | 0.00 | 0.889111E+09 | 0.00 | 0.35 |
| June | 2122000.37 | 0.633945E+09 | 0.00 | 3040393.24 | 0.00 | 0.00 | 0.274994E+09 | 0.00 | 0.36 |
| July | 0.00 | 0.194414E+10 | 0.00 | 155113.57 | 0.00 | 0.00 | 4096718.39 | 0.00 | 0.36 |
| August | 0.00 | 0.152243E+10 | 0.00 | 1713971.57 | 0.00 | 0.00 | 99838714.48 | 0.00 | 0.36 |
| September | 59637480.92 | 0.370190E+09 | 0.00 | 4689321.95 | 0.00 | 0.00 | 0.538206E+09 | 0.00 | 0.36 |
| October | 0.696482E+09 | 39032563.51 | 0.00 | 5079141.17 | 0.00 | 0.00 | 0.863523E+09 | 0.00 | 0.35 |
| November | 0.144690E+10 | 0.00 | 0.00 | 559408.50 | 0.00 | 0.797412E+09 | 0.165325E+09 | 0.00 | 0.35 |
| December | 0.119757E+10 | 0.00 | 0.00 | 6262.85 | 0.00 | 0.182205E+10 | 7192071.84 | 0.00 | 0.35 |
| Annual Sum or Average | 0.906388E+10 | 0.456274E+10 | 0.00 | 22174612.61 | 0.00 | 0.824996E+10 | 0.325193E+10 | 0.00 | 0.35 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
| Maximum of Months | 0.188154E+10 | 0.194414E+10 | 0.00 | 5142105.06 | 0.00 | 0.248740E+10 | 0.889111E+09 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: M NE APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.155398E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.320050E+10 | 0.00 | 0.00 | 0.35 |
| February | 0.197004E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.303474E+10 | 0.00 | 0.00 | 0.35 |
| March | 0.106434E+10 | 0.00 | 0.00 | 0.00 | 24801.32 | 0.156677E+10 | 0.00 | 0.00 | 0.35 |
| April | 0.141871E+10 | 5175148.67 | 0.00 | 534601.98 | 0.00 | 0.300000E+09 | 0.151781E+09 | 0.00 | 0.35 |
| May | 0.533011E+09 | 46820322.65 | 0.00 | 4241033.93 | 0.00 | 0.00 | 0.800840E+09 | 0.00 | 0.35 |
| June | 2337984.11 | 0.619410E+09 | 0.00 | 2902417.16 | 0.00 | 0.00 | 0.273993E+09 | 0.00 | 0.36 |
| July | 0.00 | 0.190569E+10 | 0.00 | 165839.28 | 0.00 | 0.00 | 4407956.16 | 0.00 | 0.36 |
| August | 1983824.98 | 0.146097E+10 | 0.00 | 1531017.05 | 0.00 | 0.00 | 0.103584E+09 | 0.00 | 0.36 |
| September | 0.135550E+09 | 0.333371E+09 | 0.00 | 3002148.87 | 0.00 | 0.00 | 0.476195E+09 | 0.00 | 0.36 |
| October | 0.117600E+10 | 19778803.22 | 0.00 | 1370969.59 | 0.00 | 0.00 | 0.345137E+09 | 0.00 | 0.35 |
| November | 0.992022E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130734E+10 | 0.00 | 0.00 | 0.35 |
| December | 0.211607E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.278653E+10 | 0.00 | 0.00 | 0.35 |
| Annual Sum or Average | 0.588797E+10 | 0.439121E+10 | 0.00 | 13748027.84 | 24801.32 | 0.121959E+11 | 0.215594E+10 | 0.00 | 0.35 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
| Maximum of Months | 0.141871E+10 | 0.190569E+10 | 0.00 | 4241033.93 | 24801.32 | 0.320050E+10 | 0.800840E+09 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: M N1 APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.102056E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.235266E+10 | 0.00 | 0.00 | 0.35 |
| February | 0.945242E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.230068E+10 | 0.00 | 0.00 | 0.35 |
| March | 0.201135E+10 | 0.00 | 0.00 | 0.00 | 33375.81 | 0.644487E+09 | 0.00 | 0.00 | 0.35 |
| April | 0.165563E+10 | 4766514.00 | 0.00 | 584928.26 | 0.00 | 18903624.73 | 0.231557E+09 | 0.00 | 0.35 |
| May | 0.306413E+09 | 42916127.33 | 0.00 | 4271546.47 | 0.00 | 0.00 | 0.104631E+10 | 0.00 | 0.35 |
| June | 2372850.03 | 0.597881E+09 | 0.00 | 2520771.27 | 0.00 | 0.00 | 0.272951E+09 | 0.00 | 0.36 |
| July | 0.00 | 0.184849E+10 | 0.00 | 155036.55 | 0.00 | 0.00 | 4875187.53 | 0.00 | 0.36 |
| August | 658214.89 | 0.140639E+10 | 0.00 | 1363480.69 | 0.00 | 0.00 | 0.106339E+09 | 0.00 | 0.36 |
| September | 49922485.15 | 0.321566E+09 | 0.00 | 3045483.24 | 0.00 | 0.00 | 0.562066E+09 | 0.00 | 0.36 |
| October | 0.113111E+10 | 15551690.55 | 0.00 | 1637036.76 | 0.00 | 0.00 | 0.440618E+09 | 0.00 | 0.35 |
| November | 0.169462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.656646E+09 | 0.00 | 0.00 | 0.35 |
| December | 0.127305E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.174201E+10 | 0.00 | 0.00 | 0.35 |
| Annual Sum or Average | 0.100909E+11 | 0.423756E+10 | 0.00 | 13578283.24 | 33375.81 | 0.771537E+10 | 0.266471E+10 | 0.00 | 0.35 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
| Maximum of Months | 0.201135E+10 | 0.184849E+10 | 0.00 | 4271546.47 | 33375.81 | 0.235266E+10 | 0.104631E+10 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: M N2 APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.102173E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.235149E+10 | 0.00 | 0.00 | 0.35 |
| February | 0.948241E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.229768E+10 | 0.00 | 0.00 | 0.35 |
| March | 0.200608E+10 | 0.00 | 0.00 | 0.00 | 34191.17 | 0.649400E+09 | 0.00 | 0.00 | 0.35 |
| April | 0.165288E+10 | 4787290.29 | 0.00 | 590392.01 | 0.00 | 18903670.40 | 0.235209E+09 | 0.00 | 0.35 |
| May | 0.308384E+09 | 42999932.40 | 0.00 | 4269245.11 | 0.00 | 0.00 | 0.104462E+10 | 0.00 | 0.35 |
| June | 2372482.19 | 0.597322E+09 | 0.00 | 2523243.26 | 0.00 | 0.00 | 0.273029E+09 | 0.00 | 0.36 |
| July | 0.00 | 0.184851E+10 | 0.00 | 155508.67 | 0.00 | 0.00 | 4886331.15 | 0.00 | 0.36 |
| August | 658202.80 | 0.140651E+10 | 0.00 | 1362680.74 | 0.00 | 0.00 | 0.106417E+09 | 0.00 | 0.36 |
| September | 50249196.05 | 0.321562E+09 | 0.00 | 3049204.64 | 0.00 | 0.00 | 0.561646E+09 | 0.00 | 0.36 |
| October | 0.113462E+10 | 15660335.39 | 0.00 | 1629529.46 | 0.00 | 0.00 | 0.437281E+09 | 0.00 | 0.35 |
| November | 0.170081E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.651452E+09 | 0.00 | 0.00 | 0.35 |
| December | 0.127755E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.173750E+10 | 0.00 | 0.00 | 0.35 |
| Annual Sum or Average | 0.101036E+11 | 0.423735E+10 | 0.00 | 13579803.88 | 34191.17 | 0.770642E+10 | 0.266309E+10 | 0.00 | 0.35 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
| Maximum of Months | 0.200608E+10 | 0.184851E+10 | 0.00 | 4269245.11 | 34191.17 | 0.235149E+10 | 0.104462E+10 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: M S1 APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.210750E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128993E+10 | 0.00 | 0.00 | 0.35 |
| February | 0.240027E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.882908E+09 | 0.00 | 0.00 | 0.35 |
| March | 0.258515E+10 | 0.00 | 0.00 | 142291.18 | 0.00 | 0.114336E+09 | 72768823.98 | 0.00 | 0.35 |
| April | 0.147415E+10 | 5653035.38 | 0.00 | 1876063.74 | 0.00 | 6305353.34 | 0.511467E+09 | 0.00 | 0.35 |
| May | 0.218559E+09 | 43650457.57 | 0.00 | 5205857.77 | 0.00 | 0.00 | 0.113511E+10 | 0.00 | 0.35 |
| June | 2024556.53 | 0.617578E+09 | 0.00 | 2686195.89 | 0.00 | 0.00 | 0.273221E+09 | 0.00 | 0.36 |
| July | 0.00 | 0.189985E+10 | 0.00 | 145598.68 | 0.00 | 0.00 | 4440168.88 | 0.00 | 0.36 |
| August | 0.00 | 0.148628E+10 | 0.00 | 1531366.47 | 0.00 | 0.00 | 0.100160E+09 | 0.00 | 0.36 |
| September | 11938151.50 | 0.367554E+09 | 0.00 | 4750078.97 | 0.00 | 0.00 | 0.581153E+09 | 0.00 | 0.36 |
| October | 0.402212E+09 | 36151963.10 | 0.00 | 6453679.23 | 0.00 | 0.00 | 0.117806E+10 | 0.00 | 0.35 |
| November | 0.195856E+10 | 0.00 | 0.00 | 1196851.59 | 0.00 | 0.151229E+09 | 0.381636E+09 | 0.00 | 0.35 |
| December | 0.233803E+10 | 0.00 | 0.00 | 30977.67 | 0.00 | 0.713301E+09 | 26564374.86 | 0.00 | 0.35 |
| Annual Sum or Average | 0.134984E+11 | 0.445671E+10 | 0.00 | 24018961.19 | 0.00 | 0.315801E+10 | 0.426458E+10 | 0.00 | 0.35 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
| Maximum of Months | 0.258515E+10 | 0.189985E+10 | 0.00 | 6453679.23 | 0.00 | 0.128993E+10 | 0.117806E+10 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: M S2 APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.210734E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129012E+10 | 0.00 | 0.00 | 0.35 |
| February | 0.239736E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.885940E+09 | 0.00 | 0.00 | 0.35 |
| March | 0.258252E+10 | 0.00 | 0.00 | 141892.26 | 0.00 | 0.116567E+09 | 72575585.54 | 0.00 | 0.35 |
| April | 0.147399E+10 | 5666330.09 | 0.00 | 1886525.90 | 0.00 | 6305357.01 | 0.512032E+09 | 0.00 | 0.35 |
| May | 0.221899E+09 | 43732026.17 | 0.00 | 5205239.81 | 0.00 | 0.00 | 0.113193E+10 | 0.00 | 0.35 |
| June | 2024191.29 | 0.617042E+09 | 0.00 | 2685844.95 | 0.00 | 0.00 | 0.273309E+09 | 0.00 | 0.36 |
| July | 0.00 | 0.189986E+10 | 0.00 | 145573.59 | 0.00 | 0.00 | 4450877.65 | 0.00 | 0.36 |
| August | 0.00 | 0.148640E+10 | 0.00 | 1531485.21 | 0.00 | 0.00 | 0.100212E+09 | 0.00 | 0.36 |
| September | 11936551.24 | 0.367539E+09 | 0.00 | 4751361.83 | 0.00 | 0.00 | 0.581108E+09 | 0.00 | 0.36 |
| October | 0.401762E+09 | 36252309.16 | 0.00 | 6443466.69 | 0.00 | 0.00 | 0.117873E+10 | 0.00 | 0.35 |
| November | 0.195733E+10 | 0.00 | 0.00 | 1226161.95 | 0.00 | 0.147245E+09 | 0.387685E+09 | 0.00 | 0.35 |
| December | 0.233772E+10 | 0.00 | 0.00 | 32346.06 | 0.00 | 0.713920E+09 | 26579414.72 | 0.00 | 0.35 |
| Annual Sum or Average | 0.134939E+11 | 0.445650E+10 | 0.00 | 24049898.23 | 0.00 | 0.316009E+10 | 0.426862E+10 | 0.00 | 0.35 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
| Maximum of Months | 0.258252E+10 | 0.189986E+10 | 0.00 | 6443466.69 | 0.00 | 0.129012E+10 | 0.117873E+10 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: T SW APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.170083E+09 | 0.00 | 0.00 | 19908.47 | 0.00 | 0.150099E+10 | 6659003.21 | 0.00 | 0.35 |
| February | 0.215061E+09 | 0.00 | 0.00 | 23956.03 | 0.00 | 0.138562E+10 | 21202416.23 | 0.00 | 0.35 |
| March | 0.350388E+09 | 0.00 | 0.00 | 386215.28 | 0.00 | 0.913581E+09 | 74979053.76 | 0.00 | 0.35 |
| April | 0.376442E+09 | 2704869.54 | 0.00 | 1004302.72 | 0.00 | 0.419593E+09 | 0.119892E+09 | 0.00 | 0.35 |
| May | 0.393247E+09 | 23023744.91 | 0.00 | 1897407.50 | 0.00 | 29197186.38 | 0.184253E+09 | 0.00 | 0.35 |
| June | 67602605.17 | 0.301937E+09 | 0.00 | 1178900.92 | 58110.20 | 0.00 | 87696257.97 | 0.00 | 0.36 |
| July | 0.00 | 0.937638E+09 | 0.00 | 79745.51 | 0.00 | 0.00 | 5267565.37 | 0.00 | 0.36 |
| August | 15454639.07 | 0.744227E+09 | 0.00 | 533654.79 | 0.00 | 0.00 | 45428131.25 | 0.00 | 0.36 |
| September | 0.175534E+09 | 0.167547E+09 | 0.00 | 1659718.50 | 0.00 | 0.00 | 0.117808E+09 | 0.00 | 0.35 |
| October | 0.406598E+09 | 18479240.19 | 0.00 | 1537546.13 | 0.00 | 0.137523E+09 | 0.182547E+09 | 0.00 | 0.35 |
| November | 0.284288E+09 | 0.00 | 0.00 | 186093.42 | 0.00 | 0.836320E+09 | 34100826.94 | 0.00 | 0.35 |
| December | 0.211729E+09 | 0.00 | 0.00 | 30756.69 | 0.00 | 0.128056E+10 | 11237054.44 | 0.00 | 0.35 |
| Annual Sum or Average | 0.266643E+10 | 0.219556E+10 | 0.00 | 8538205.95 | 58110.20 | 0.650338E+10 | 0.891071E+09 | 0.00 | 0.35 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 19908.47 | 0.00 | 0.00 | 5267565.37 | 0.00 | 0.35 |
| Maximum of Months | 0.406598E+09 | 0.937638E+09 | 0.00 | 1897407.50 | 58110.20 | 0.150099E+10 | 0.184253E+09 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: T NW APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 9844393.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.166287E+10 | 0.00 | 0.00 | 0.35 |
| February | 31027383.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.158036E+10 | 0.00 | 0.00 | 0.35 |
| March | 0.193061E+09 | 0.00 | 0.00 | 9532.08 | 5339.55 | 0.111979E+10 | 1173785.45 | 0.00 | 0.35 |
| April | 0.361040E+09 | 2397288.34 | 0.00 | 390397.69 | 0.00 | 0.477510E+09 | 57751829.30 | 0.00 | 0.35 |
| May | 0.400901E+09 | 23165554.03 | 0.00 | 1508167.01 | 0.00 | 31539216.70 | 0.171473E+09 | 0.00 | 0.35 |
| June | 67404612.72 | 0.297832E+09 | 0.00 | 1105776.59 | 50164.92 | 0.00 | 86882475.98 | 0.00 | 0.36 |
| July | 0.00 | 0.925190E+09 | 0.00 | 83535.12 | 0.00 | 0.00 | 5271625.47 | 0.00 | 0.36 |
| August | 19032744.66 | 0.720461E+09 | 0.00 | 452200.15 | 0.00 | 0.00 | 43394336.19 | 0.00 | 0.36 |
| September | 0.199655E+09 | 0.153811E+09 | 0.00 | 964505.89 | 0.00 | 60100.87 | 89905375.08 | 0.00 | 0.35 |
| October | 0.418194E+09 | 9081207.42 | 0.00 | 397127.49 | 0.00 | 0.231328E+09 | 44406524.08 | 0.00 | 0.35 |
| November | 0.118788E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101071E+10 | 0.00 | 0.00 | 0.35 |
| December | 5368328.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.148852E+10 | 0.00 | 0.00 | 0.35 |
| Annual Sum or Average | 0.182432E+10 | 0.213194E+10 | 0.00 | 4911242.02 | 55504.47 | 0.760269E+10 | 0.500259E+09 | 0.00 | 0.35 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
| Maximum of Months | 0.418194E+09 | 0.925190E+09 | 0.00 | 1508167.01 | 50164.92 | 0.166287E+10 | 0.171473E+09 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: T SE APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.167706E+09 | 0.00 | 0.00 | 15916.33 | 0.00 | 0.150276E+10 | 6804970.13 | 0.00 | 0.35 |
| February | 0.234444E+09 | 0.00 | 0.00 | 10279.85 | 0.00 | 0.137477E+10 | 11803930.37 | 0.00 | 0.35 |
| March | 0.345804E+09 | 0.00 | 0.00 | 282628.90 | 0.00 | 0.918492E+09 | 74150932.43 | 0.00 | 0.35 |
| April | 0.385580E+09 | 2873066.80 | 0.00 | 850356.22 | 0.00 | 0.413465E+09 | 0.121192E+09 | 0.00 | 0.35 |
| May | 0.388261E+09 | 23691575.29 | 0.00 | 1789703.39 | 0.00 | 28984415.63 | 0.194313E+09 | 0.00 | 0.35 |
| June | 63915222.47 | 0.297004E+09 | 0.00 | 1210426.00 | 55462.49 | 0.00 | 95845104.35 | 0.00 | 0.36 |
| July | 0.00 | 0.936136E+09 | 0.00 | 92725.91 | 0.00 | 0.00 | 5679389.19 | 0.00 | 0.36 |
| August | 16075847.52 | 0.743360E+09 | 0.00 | 613147.31 | 0.00 | 0.00 | 45732838.24 | 0.00 | 0.36 |
| September | 0.171974E+09 | 0.165802E+09 | 0.00 | 1679498.90 | 0.00 | 0.00 | 0.123887E+09 | 0.00 | 0.35 |
| October | 0.409755E+09 | 19206187.00 | 0.00 | 1345331.91 | 0.00 | 0.136658E+09 | 0.184661E+09 | 0.00 | 0.35 |
| November | 0.310384E+09 | 0.00 | 0.00 | 175260.81 | 0.00 | 0.808495E+09 | 38877822.07 | 0.00 | 0.35 |
| December | 0.222298E+09 | 0.00 | 0.00 | 28719.39 | 0.00 | 0.126958E+10 | 12097822.72 | 0.00 | 0.35 |
| Annual Sum or Average | 0.271620E+10 | 0.218807E+10 | 0.00 | 8093994.92 | 55462.49 | 0.645321E+10 | 0.915045E+09 | 0.00 | 0.35 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 10279.85 | 0.00 | 0.00 | 5679389.19 | 0.00 | 0.35 |
| Maximum of Months | 0.409755E+09 | 0.936136E+09 | 0.00 | 1789703.39 | 55462.49 | 0.150276E+10 | 0.194313E+09 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: T NE APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 6889366.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.166575E+10 | 0.00 | 0.00 | 0.35 |
| February | 19870721.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.159144E+10 | 0.00 | 0.00 | 0.35 |
| March | 0.182974E+09 | 0.00 | 0.00 | 826.93 | 8314.35 | 0.112796E+10 | 502000.60 | 0.00 | 0.35 |
| April | 0.383110E+09 | 2556179.88 | 0.00 | 273704.97 | 0.00 | 0.463641E+09 | 53484492.19 | 0.00 | 0.35 |
| May | 0.398612E+09 | 23896025.54 | 0.00 | 1396775.42 | 0.00 | 33444344.96 | 0.177297E+09 | 0.00 | 0.35 |
| June | 62658768.72 | 0.293542E+09 | 0.00 | 1166967.45 | 15198.36 | 0.00 | 95303773.43 | 0.00 | 0.36 |
| July | 0.00 | 0.925343E+09 | 0.00 | 94334.47 | 0.00 | 0.00 | 5684379.26 | 0.00 | 0.36 |
| August | 19688825.74 | 0.721242E+09 | 0.00 | 544786.80 | 0.00 | 0.00 | 43761922.65 | 0.00 | 0.36 |
| September | 0.200767E+09 | 0.152879E+09 | 0.00 | 942658.27 | 0.00 | 99506.47 | 92789479.26 | 0.00 | 0.35 |
| October | 0.434211E+09 | 9931081.74 | 0.00 | 307719.69 | 0.00 | 0.223660E+09 | 35071944.88 | 0.00 | 0.35 |
| November | 0.133337E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.995682E+09 | 0.00 | 0.00 | 0.35 |
| December | 7471302.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.148636E+10 | 0.00 | 0.00 | 0.35 |
| Annual Sum or Average | 0.184959E+10 | 0.212939E+10 | 0.00 | 4727774.00 | 23512.70 | 0.758804E+10 | 0.503895E+09 | 0.00 | 0.35 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
| Maximum of Months | 0.434211E+09 | 0.925343E+09 | 0.00 | 1396775.42 | 15198.36 | 0.166575E+10 | 0.177297E+09 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: T N1 APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 19051854.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.166278E+10 | 0.00 | 0.00 | 0.35 |
| February | 44465644.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.157454E+10 | 0.00 | 0.00 | 0.35 |
| March | 0.312476E+09 | 0.00 | 0.00 | 983.07 | 17064.83 | 0.100738E+10 | 594933.24 | 0.00 | 0.35 |
| April | 0.500132E+09 | 2398020.45 | 0.00 | 192957.60 | 0.00 | 0.359711E+09 | 51058277.06 | 0.00 | 0.35 |
| May | 0.429625E+09 | 22337303.90 | 0.00 | 1144244.85 | 0.00 | 6634981.21 | 0.195503E+09 | 0.00 | 0.35 |
| June | 46189267.35 | 0.291730E+09 | 0.00 | 1002163.40 | 0.00 | 0.00 | 0.108116E+09 | 0.00 | 0.36 |
| July | 0.00 | 0.921294E+09 | 0.00 | 84309.91 | 0.00 | 0.00 | 4572908.49 | 0.00 | 0.36 |
| August | 11894752.64 | 0.709738E+09 | 0.00 | 481776.38 | 0.00 | 0.00 | 50490098.45 | 0.00 | 0.36 |
| September | 0.190922E+09 | 0.152185E+09 | 0.00 | 819622.99 | 0.00 | 0.00 | 0.110994E+09 | 0.00 | 0.35 |
| October | 0.502777E+09 | 7542817.13 | 0.00 | 280018.28 | 0.00 | 0.155064E+09 | 56268410.25 | 0.00 | 0.35 |
| November | 0.233135E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.907136E+09 | 0.00 | 0.00 | 0.35 |
| December | 16398654.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.148656E+10 | 0.00 | 0.00 | 0.35 |
| Annual Sum or Average | 0.230707E+10 | 0.210723E+10 | 0.00 | 4006076.47 | 17064.83 | 0.715981E+10 | 0.577597E+09 | 0.00 | 0.35 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
| Maximum of Months | 0.502777E+09 | 0.921294E+09 | 0.00 | 1144244.85 | 17064.83 | 0.166278E+10 | 0.195503E+09 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: T N2 APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 18726775.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.166310E+10 | 0.00 | 0.00 | 0.35 |
| February | 44329334.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.157467E+10 | 0.00 | 0.00 | 0.35 |
| March | 0.310850E+09 | 0.00 | 0.00 | 760.41 | 17432.67 | 0.100895E+10 | 551380.10 | 0.00 | 0.35 |
| April | 0.500543E+09 | 2407399.83 | 0.00 | 192929.04 | 0.00 | 0.360780E+09 | 50074660.30 | 0.00 | 0.35 |
| May | 0.429107E+09 | 22399253.99 | 0.00 | 1147877.12 | 0.00 | 6635176.93 | 0.196161E+09 | 0.00 | 0.35 |
| June | 46261374.13 | 0.291532E+09 | 0.00 | 1005436.84 | 0.00 | 0.00 | 0.108205E+09 | 0.00 | 0.36 |
| July | 0.00 | 0.921412E+09 | 0.00 | 84365.61 | 0.00 | 0.00 | 4607545.49 | 0.00 | 0.36 |
| August | 11864198.36 | 0.709905E+09 | 0.00 | 482855.23 | 0.00 | 0.00 | 50601795.74 | 0.00 | 0.36 |
| September | 0.190517E+09 | 0.152174E+09 | 0.00 | 821722.08 | 0.00 | 0.00 | 0.111607E+09 | 0.00 | 0.35 |
| October | 0.503003E+09 | 7664560.41 | 0.00 | 277956.44 | 0.00 | 0.155766E+09 | 54972563.51 | 0.00 | 0.35 |
| November | 0.235085E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.905223E+09 | 0.00 | 0.00 | 0.35 |
| December | 16349090.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.148661E+10 | 0.00 | 0.00 | 0.35 |
| Annual Sum or Average | 0.230664E+10 | 0.210749E+10 | 0.00 | 4013902.77 | 17432.67 | 0.716173E+10 | 0.576780E+09 | 0.00 | 0.35 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
| Maximum of Months | 0.503003E+09 | 0.921412E+09 | 0.00 | 1147877.12 | 17432.67 | 0.166310E+10 | 0.196161E+09 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: T S1 APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.289146E+09 | 0.00 | 0.00 | 22488.72 | 0.00 | 0.138977E+10 | 10954835.16 | 0.00 | 0.35 |
| February | 0.359105E+09 | 0.00 | 0.00 | 36034.73 | 0.00 | 0.124459E+10 | 29896503.88 | 0.00 | 0.35 |
| March | 0.563861E+09 | 0.00 | 0.00 | 317213.89 | 0.00 | 0.708069E+09 | 82312971.98 | 0.00 | 0.35 |
| April | 0.526478E+09 | 2762536.50 | 0.00 | 757493.62 | 0.00 | 0.283916E+09 | 0.127675E+09 | 0.00 | 0.35 |
| May | 0.418927E+09 | 22330690.20 | 0.00 | 1536069.67 | 0.00 | 4205925.94 | 0.213076E+09 | 0.00 | 0.35 |
| June | 49705475.76 | 0.297289E+09 | 0.00 | 1058716.97 | 15866.52 | 0.00 | 0.106053E+09 | 0.00 | 0.36 |
| July | 0.00 | 0.937342E+09 | 0.00 | 81363.44 | 0.00 | 0.00 | 4570987.71 | 0.00 | 0.36 |
| August | 8129032.20 | 0.739521E+09 | 0.00 | 568805.42 | 0.00 | 0.00 | 52112439.39 | 0.00 | 0.36 |
| September | 0.149659E+09 | 0.169082E+09 | 0.00 | 1606141.93 | 0.00 | 0.00 | 0.154190E+09 | 0.00 | 0.35 |
| October | 0.452166E+09 | 17905817.44 | 0.00 | 1576117.61 | 0.00 | 56879340.04 | 0.245555E+09 | 0.00 | 0.35 |
| November | 0.500761E+09 | 0.00 | 0.00 | 218694.20 | 0.00 | 0.625601E+09 | 51529068.90 | 0.00 | 0.35 |
| December | 0.374094E+09 | 0.00 | 0.00 | 47696.44 | 0.00 | 0.112399E+10 | 21223320.23 | 0.00 | 0.35 |
| Annual Sum or Average | 0.369203E+10 | 0.218623E+10 | 0.00 | 7826836.65 | 15866.52 | 0.543702E+10 | 0.109915E+10 | 0.00 | 0.35 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 22488.72 | 0.00 | 0.00 | 4570987.71 | 0.00 | 0.35 |
| Maximum of Months | 0.563861E+09 | 0.937342E+09 | 0.00 | 1606141.93 | 15866.52 | 0.138977E+10 | 0.245555E+09 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: T S2 APARTMENT
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.290211E+09 | 0.00 | 0.00 | 23153.16 | 0.00 | 0.138907E+10 | 10635138.63 | 0.00 | 0.35 |
| February | 0.357914E+09 | 0.00 | 0.00 | 38344.90 | 0.00 | 0.124610E+10 | 29630422.49 | 0.00 | 0.35 |
| March | 0.562289E+09 | 0.00 | 0.00 | 318078.93 | 0.00 | 0.709443E+09 | 82439031.11 | 0.00 | 0.35 |
| April | 0.522854E+09 | 2774204.64 | 0.00 | 762769.62 | 0.00 | 0.285339E+09 | 0.130088E+09 | 0.00 | 0.35 |
| May | 0.419040E+09 | 22393467.14 | 0.00 | 1539926.14 | 0.00 | 4547417.40 | 0.212621E+09 | 0.00 | 0.35 |
| June | 49560691.15 | 0.297086E+09 | 0.00 | 1061373.27 | 15757.91 | 0.00 | 0.106388E+09 | 0.00 | 0.36 |
| July | 0.00 | 0.937449E+09 | 0.00 | 82252.44 | 0.00 | 0.00 | 4606531.32 | 0.00 | 0.36 |
| August | 8051141.75 | 0.739672E+09 | 0.00 | 569693.52 | 0.00 | 0.00 | 52252765.97 | 0.00 | 0.36 |
| September | 0.150425E+09 | 0.169064E+09 | 0.00 | 1608138.56 | 0.00 | 0.00 | 0.153434E+09 | 0.00 | 0.35 |
| October | 0.451234E+09 | 18006518.85 | 0.00 | 1573731.23 | 0.00 | 57183693.97 | 0.246236E+09 | 0.00 | 0.35 |
| November | 0.501048E+09 | 0.00 | 0.00 | 221985.78 | 0.00 | 0.624089E+09 | 53094018.80 | 0.00 | 0.35 |
| December | 0.375565E+09 | 0.00 | 0.00 | 49387.48 | 0.00 | 0.112263E+10 | 21242525.21 | 0.00 | 0.35 |
| Annual Sum or Average | 0.368819E+10 | 0.218644E+10 | 0.00 | 7848835.04 | 15757.91 | 0.543840E+10 | 0.110267E+10 | 0.00 | 0.35 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 23153.16 | 0.00 | 0.00 | 4606531.32 | 0.00 | 0.35 |
| Maximum of Months | 0.562289E+09 | 0.937449E+09 | 0.00 | 1608138.56 | 15757.91 | 0.138907E+10 | 0.246236E+09 | 0.00 | 0.36 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 09:15:04
Custom Monthly Report| SITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
| January | 0.794143E+11 | 0.253029E+11 | 0.00 | 0.213058E+10 | 0.206114E+11 |
| February | 0.116735E+12 | 0.227800E+11 | 0.00 | 0.209313E+10 | 0.186922E+11 |
| March | 0.182582E+12 | 0.197559E+11 | 0.00 | 0.178292E+10 | 0.102184E+11 |
| April | 0.184825E+12 | 0.144444E+11 | 0.00 | 0.132634E+10 | 0.114666E+11 |
| May | 0.232863E+12 | 0.125409E+11 | 0.00 | 0.100179E+10 | 0.357210E+11 |
| June | 0.222797E+12 | 0.143738E+10 | 0.00 | 0.280290E+09 | 0.115840E+12 |
| July | 0.218837E+12 | -0.762535E+10 | 0.00 | -224702670.7 | 0.186836E+12 |
| August | 0.213374E+12 | -0.396203E+10 | 0.00 | -102482741.4 | 0.176075E+12 |
| September | 0.157479E+12 | 0.575542E+10 | 0.00 | 0.612241E+09 | 0.898070E+11 |
| October | 0.160760E+12 | 0.143831E+11 | 0.00 | 0.129990E+10 | 0.354744E+11 |
| November | 0.828935E+11 | 0.181270E+11 | 0.00 | 0.174983E+10 | 0.948832E+10 |
| December | 0.663286E+11 | 0.223776E+11 | 0.00 | 0.200550E+10 | 0.155848E+11 |
| Annual Sum or Average | 0.191889E+13 | 0.145317E+12 | 0.00 | 0.139553E+11 | 0.725814E+12 |
| Minimum of Months | 0.663286E+11 | -0.762535E+10 | 0.00 | -224702670.7 | 0.948832E+10 |
| Maximum of Months | 0.232863E+12 | 0.253029E+11 | 0.00 | 0.213058E+10 | 0.186836E+12 |