Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 09:14
Tabular Output Report in Format: HTML
Building: ApartmentMidRise
Environment: RUNPERIOD 1 ** Miami Intl Ap FL USA TMY3 WMO#=722020
Simulation Timestamp: 2023-10-16 09:14:58
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 09:14:58
Values gathered over 8760.00 hours| Total Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
| Total Site Energy | 1510.29 | 481.81 | 534.81 |
| Net Site Energy | 1510.29 | 481.81 | 534.81 |
| Total Source Energy | 4779.24 | 1524.67 | 1692.38 |
| Net Source Energy | 4779.24 | 1524.67 | 1692.38 |
| Site=>Source Conversion Factor | |
| Electricity | 3.167 |
| Natural Gas | 1.084 |
| District Cooling | 1.056 |
| District Heating | 3.613 |
| Steam | 1.200 |
| Gasoline | 1.050 |
| Diesel | 1.050 |
| Coal | 1.050 |
| Fuel Oil No 1 | 1.050 |
| Fuel Oil No 2 | 1.050 |
| Propane | 1.050 |
| Other Fuel 1 | 1.000 |
| Other Fuel 2 | 1.000 |
| Area [m2] | |
| Total Building Area | 3134.61 |
| Net Conditioned Building Area | 2823.98 |
| Unconditioned Building Area | 310.64 |
| Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
| Heating | 0.00 | 1.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Cooling | 395.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Lighting | 99.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Lighting | 50.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment | 458.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans | 148.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems | 356.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1875.32 |
| Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Total End Uses | 1508.44 | 1.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1875.32 |
| Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
| Heating | General | 0.00 | 1.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Cooling | General | 395.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Lighting | LightsWired | 94.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LightsPlugIn | 4.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Exterior Lighting | General | 50.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment | MiscPlug | 388.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| ElevatorLift | 65.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| ElevatorLightsFan | 5.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| General | 148.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems | Water Heater | 356.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1875.32 |
| Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
| Heating | Unassigned | 0.00 | 1.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Cooling | Unassigned | 395.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Lighting | GENERAL | 99.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Lighting | Unassigned | 50.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment | GENERAL | 458.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans | Unassigned | 148.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Pumps | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems | Unassigned | 356.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1875.32 |
| Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
| Lighting | 52.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| HVAC | 318.86 | 0.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.66 |
| Other | 162.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Total | 534.15 | 0.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.66 |
| Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
| Lighting | 47.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| HVAC | 287.26 | 0.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.60 |
| Other | 146.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Total | 481.22 | 0.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.60 |
| Electricity [GJ] | Percent Electricity [%] | |
| Fuel-Fired Power Generation | 0.000 | 0.00 |
| High Temperature Geothermal* | 0.000 | 0.00 |
| Photovoltaic Power | 0.000 | 0.00 |
| Wind Power | 0.000 | 0.00 |
| Power Conversion | 0.000 | 0.00 |
| Net Decrease in On-Site Storage | 0.000 | 0.00 |
| Total On-Site Electric Sources | 0.000 | 0.00 |
| Electricity Coming From Utility | 1508.440 | 100.00 |
| Surplus Electricity Going To Utility | 0.000 | 0.00 |
| Net Electricity From Utility | 1508.440 | 100.00 |
| Total On-Site and Utility Electric Sources | 1508.440 | 100.00 |
| Total Electricity End Uses | 1508.440 | 100.00 |
| Heat [GJ] | Percent Heat [%] | |
| Water-Side Heat Recovery | 0.00 | 0.00 |
| Air to Air Heat Recovery for Cooling | 0.00 | 53.42 |
| Air to Air Heat Recovery for Heating | 0.00 | 46.58 |
| High-Temperature Geothermal* | 0.00 | 0.00 |
| Solar Water Thermal | 0.00 | 0.00 |
| Solar Air Thermal | 0.00 | 0.00 |
| Total On-Site Thermal Sources | 0.00 | 100.00 |
| Water [m3] | Percent Water [%] | |
| Rainwater Collection | 0.00 | 0.00 |
| Condensate Collection | 0.00 | 0.00 |
| Groundwater Well | 0.00 | 0.00 |
| Total On Site Water Sources | 0.00 | 0.00 |
| - | - | - |
| Initial Storage | 0.00 | 0.00 |
| Final Storage | 0.00 | 0.00 |
| Change in Storage | 0.00 | 0.00 |
| - | - | - |
| Water Supplied by Utility | 1875.32 | 100.00 |
| - | - | - |
| Total On Site, Change in Storage, and Utility Water Sources | 1875.32 | 100.00 |
| Total Water End Uses | 1875.32 | 100.00 |
| Degrees [deltaC] | |
| Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
| Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
| Facility [Hours] | |
| Time Setpoint Not Met During Occupied Heating | 0.00 |
| Time Setpoint Not Met During Occupied Cooling | 0.17 |
| Time Not Comfortable Based on Simple ASHRAE 55-2004 | 8672.50 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2012
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME APARTMENTMIDRISE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 1A
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_FL_MIAMI
| Environment |ZoneCoolingSummaryMonthly
| G SW APARTMENT | G NW APARTMENT | OFFICE | G NE APARTMENT | G N1 APARTMENT | G N2 APARTMENT | G S1 APARTMENT | G S2 APARTMENT | M SW APARTMENT | M NW APARTMENT | M SE APARTMENT | M NE APARTMENT | M N1 APARTMENT | M N2 APARTMENT | M S1 APARTMENT | M S2 APARTMENT | T SW APARTMENT | T NW APARTMENT | T SE APARTMENT | T NE APARTMENT | T N1 APARTMENT | T N2 APARTMENT | T S1 APARTMENT | T S2 APARTMENT | T CORRIDOR | G CORRIDOR | M CORRIDOR |ZoneHeatingSummaryMonthly
| G SW APARTMENT | G NW APARTMENT | OFFICE | G NE APARTMENT | G N1 APARTMENT | G N2 APARTMENT | G S1 APARTMENT | G S2 APARTMENT | M SW APARTMENT | M NW APARTMENT | M SE APARTMENT | M NE APARTMENT | M N1 APARTMENT | M N2 APARTMENT | M S1 APARTMENT | M S2 APARTMENT | T SW APARTMENT | T NW APARTMENT | T SE APARTMENT | T NE APARTMENT | T N1 APARTMENT | T N2 APARTMENT | T S1 APARTMENT | T S2 APARTMENT | T CORRIDOR | G CORRIDOR | M CORRIDOR |ZoneElectricSummaryMonthly
| G SW APARTMENT | G NW APARTMENT | OFFICE | G NE APARTMENT | G N1 APARTMENT | G N2 APARTMENT | G S1 APARTMENT | G S2 APARTMENT | M SW APARTMENT | M NW APARTMENT | M SE APARTMENT | M NE APARTMENT | M N1 APARTMENT | M N2 APARTMENT | M S1 APARTMENT | M S2 APARTMENT | T SW APARTMENT | T NW APARTMENT | T SE APARTMENT | T NE APARTMENT | T N1 APARTMENT | T N2 APARTMENT | T S1 APARTMENT | T S2 APARTMENT | T CORRIDOR | G CORRIDOR | M CORRIDOR |SpaceGainsMonthly
| G SW APARTMENT | G NW APARTMENT | OFFICE | G NE APARTMENT | G N1 APARTMENT | G N2 APARTMENT | G S1 APARTMENT | G S2 APARTMENT | M SW APARTMENT | M NW APARTMENT | M SE APARTMENT | M NE APARTMENT | M N1 APARTMENT | M N2 APARTMENT | M S1 APARTMENT | M S2 APARTMENT | T SW APARTMENT | T NW APARTMENT | T SE APARTMENT | T NE APARTMENT | T N1 APARTMENT | T N2 APARTMENT | T S1 APARTMENT | T S2 APARTMENT | T CORRIDOR | G CORRIDOR | M CORRIDOR |PeakSpaceGainsMonthly
| G SW APARTMENT | G NW APARTMENT | OFFICE | G NE APARTMENT | G N1 APARTMENT | G N2 APARTMENT | G S1 APARTMENT | G S2 APARTMENT | M SW APARTMENT | M NW APARTMENT | M SE APARTMENT | M NE APARTMENT | M N1 APARTMENT | M N2 APARTMENT | M S1 APARTMENT | M S2 APARTMENT | T SW APARTMENT | T NW APARTMENT | T SE APARTMENT | T NE APARTMENT | T N1 APARTMENT | T N2 APARTMENT | T S1 APARTMENT | T S2 APARTMENT | T CORRIDOR | G CORRIDOR | M CORRIDOR |SpaceGainComponentsAtCoolingPeakMonthly
| G SW APARTMENT | G NW APARTMENT | OFFICE | G NE APARTMENT | G N1 APARTMENT | G N2 APARTMENT | G S1 APARTMENT | G S2 APARTMENT | M SW APARTMENT | M NW APARTMENT | M SE APARTMENT | M NE APARTMENT | M N1 APARTMENT | M N2 APARTMENT | M S1 APARTMENT | M S2 APARTMENT | T SW APARTMENT | T NW APARTMENT | T SE APARTMENT | T NE APARTMENT | T N1 APARTMENT | T N2 APARTMENT | T S1 APARTMENT | T S2 APARTMENT | T CORRIDOR | G CORRIDOR | M CORRIDOR |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| G SW APARTMENT | G NW APARTMENT | OFFICE | G NE APARTMENT | G N1 APARTMENT | G N2 APARTMENT | G S1 APARTMENT | G S2 APARTMENT | M SW APARTMENT | M NW APARTMENT | M SE APARTMENT | M NE APARTMENT | M N1 APARTMENT | M N2 APARTMENT | M S1 APARTMENT | M S2 APARTMENT | T SW APARTMENT | T NW APARTMENT | T SE APARTMENT | T NE APARTMENT | T N1 APARTMENT | T N2 APARTMENT | T S1 APARTMENT | T S2 APARTMENT | T CORRIDOR | G CORRIDOR | M CORRIDOR |ComfortReportSimple55Monthly
| G SW APARTMENT | G NW APARTMENT | OFFICE | G NE APARTMENT | G N1 APARTMENT | G N2 APARTMENT | G S1 APARTMENT | G S2 APARTMENT | M SW APARTMENT | M NW APARTMENT | M SE APARTMENT | M NE APARTMENT | M N1 APARTMENT | M N2 APARTMENT | M S1 APARTMENT | M S2 APARTMENT | T SW APARTMENT | T NW APARTMENT | T SE APARTMENT | T NE APARTMENT | T N1 APARTMENT | T N2 APARTMENT | T S1 APARTMENT | T S2 APARTMENT | T CORRIDOR | G CORRIDOR | M CORRIDOR |OccupantComfortDataSummaryMonthly
| OCCUP_GSW | OCCUP_GNW | OCCUP_OFFICE | OCCUP_GNE | OCCUP_GN1 | OCCUP_GN2 | OCCUP_GS1 | OCCUP_GS2 | OCCUP_MSW | OCCUP_MNW | OCCUP_MSE | OCCUP_MNE | OCCUP_MN1 | OCCUP_MN2 | OCCUP_MS1 | OCCUP_MS2 | OCCUP_TSW | OCCUP_TNW | OCCUP_TSE | OCCUP_TNE | OCCUP_TN1 | OCCUP_TN2 | OCCUP_TS1 | OCCUP_TS2 | OCCUP_T CORRIDOR | OCCUP_G CORRIDOR | OCCUP_M CORRIDOR |DXReportMonthly
| SPLIT GSW COOLING COIL | SPLIT GNW COOLING COIL | SPLIT OFFICE COOLING COIL | SPLIT GNE COOLING COIL | SPLIT GN1 COOLING COIL | SPLIT GN2 COOLING COIL | SPLIT GS1 COOLING COIL | SPLIT GS2 COOLING COIL | SPLIT MSW COOLING COIL | SPLIT MNW COOLING COIL | SPLIT MSE COOLING COIL | SPLIT MNE COOLING COIL | SPLIT MN1 COOLING COIL | SPLIT MN2 COOLING COIL | SPLIT MS1 COOLING COIL | SPLIT MS2 COOLING COIL | SPLIT TSW COOLING COIL | SPLIT TNW COOLING COIL | SPLIT TSE COOLING COIL | SPLIT TNE COOLING COIL | SPLIT TN1 COOLING COIL | SPLIT TN2 COOLING COIL | SPLIT TS1 COOLING COIL | SPLIT TS2 COOLING COIL |WindowReportMonthly
| GWINDOW1 S SWA | GWINDOW1 W SWA | GWINDOW1 W NWA | GWINDOW1 N NWA | GWINDOW1 S SEA | GWINDOW1 E SEA | GWINDOW1 E NEA | GWINDOW1 N NEA | GWINDOW1 N N1A | GWINDOW1 N N2A | GWINDOW1 S S1A | GWINDOW1 S S2A | MWINDOW1 S SWA | MWINDOW1 W SWA | MWINDOW1 W NWA | MWINDOW1 N NWA | MWINDOW1 S SEA | MWINDOW1 E SEA | MWINDOW1 E NEA | MWINDOW1 N NEA | MWINDOW1 N N1A | MWINDOW1 N N2A | MWINDOW1 S S1A | MWINDOW1 S S2A | TWINDOW1 S SWA | TWINDOW1 W SWA | TWINDOW1 W NWA | TWINDOW1 N NWA | TWINDOW1 S SEA | TWINDOW1 E SEA | TWINDOW1 E NEA | TWINDOW1 N NEA | TWINDOW1 N N1A | TWINDOW1 N N2A | TWINDOW1 S S1A | TWINDOW1 S S2A | TWINDOW14 | ENTRANCE DOOR | MWINDOW14 |WindowEnergyReportMonthly
| GWINDOW1 S SWA | GWINDOW1 W SWA | GWINDOW1 W NWA | GWINDOW1 N NWA | GWINDOW1 S SEA | GWINDOW1 E SEA | GWINDOW1 E NEA | GWINDOW1 N NEA | GWINDOW1 N N1A | GWINDOW1 N N2A | GWINDOW1 S S1A | GWINDOW1 S S2A | MWINDOW1 S SWA | MWINDOW1 W SWA | MWINDOW1 W NWA | MWINDOW1 N NWA | MWINDOW1 S SEA | MWINDOW1 E SEA | MWINDOW1 E NEA | MWINDOW1 N NEA | MWINDOW1 N N1A | MWINDOW1 N N2A | MWINDOW1 S S1A | MWINDOW1 S S2A | TWINDOW1 S SWA | TWINDOW1 W SWA | TWINDOW1 W NWA | TWINDOW1 N NWA | TWINDOW1 S SEA | TWINDOW1 E SEA | TWINDOW1 E NEA | TWINDOW1 N NEA | TWINDOW1 N N1A | TWINDOW1 N N2A | TWINDOW1 S S1A | TWINDOW1 S S2A | TWINDOW14 | ENTRANCE DOOR | MWINDOW14 |WindowZoneSummaryMonthly
| G SW APARTMENT | G NW APARTMENT | OFFICE | G NE APARTMENT | G N1 APARTMENT | G N2 APARTMENT | G S1 APARTMENT | G S2 APARTMENT | M SW APARTMENT | M NW APARTMENT | M SE APARTMENT | M NE APARTMENT | M N1 APARTMENT | M N2 APARTMENT | M S1 APARTMENT | M S2 APARTMENT | T SW APARTMENT | T NW APARTMENT | T SE APARTMENT | T NE APARTMENT | T N1 APARTMENT | T N2 APARTMENT | T S1 APARTMENT | T S2 APARTMENT | T CORRIDOR | G CORRIDOR | M CORRIDOR |WindowEnergyZoneSummaryMonthly
| G SW APARTMENT | G NW APARTMENT | OFFICE | G NE APARTMENT | G N1 APARTMENT | G N2 APARTMENT | G S1 APARTMENT | G S2 APARTMENT | M SW APARTMENT | M NW APARTMENT | M SE APARTMENT | M NE APARTMENT | M N1 APARTMENT | M N2 APARTMENT | M S1 APARTMENT | M S2 APARTMENT | T SW APARTMENT | T NW APARTMENT | T SE APARTMENT | T NE APARTMENT | T N1 APARTMENT | T N2 APARTMENT | T S1 APARTMENT | T S2 APARTMENT | T CORRIDOR | G CORRIDOR | M CORRIDOR |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| G SW APARTMENT WATER HEATER | G NW APARTMENT WATER HEATER | G NE APARTMENT WATER HEATER | G N1 APARTMENT WATER HEATER | G N2 APARTMENT WATER HEATER | G S1 APARTMENT WATER HEATER | G S2 APARTMENT WATER HEATER | M SW APARTMENT WATER HEATER | M NW APARTMENT WATER HEATER | M SE APARTMENT WATER HEATER | M NE APARTMENT WATER HEATER | M N1 APARTMENT WATER HEATER | M N2 APARTMENT WATER HEATER | M S1 APARTMENT WATER HEATER | M S2 APARTMENT WATER HEATER | T SW APARTMENT WATER HEATER | T NW APARTMENT WATER HEATER | T SE APARTMENT WATER HEATER | T NE APARTMENT WATER HEATER | T N1 APARTMENT WATER HEATER | T N2 APARTMENT WATER HEATER | T S1 APARTMENT WATER HEATER | T S2 APARTMENT WATER HEATER |DaylightingReportMonthly
| Environment |CoilReportMonthly
| SPLIT GSW HEATING COIL | SPLIT GNW HEATING COIL | SPLIT OFFICE HEATING COIL | SPLIT GNE HEATING COIL | SPLIT GN1 HEATING COIL | SPLIT GN2 HEATING COIL | SPLIT GS1 HEATING COIL | SPLIT GS2 HEATING COIL | SPLIT MSW HEATING COIL | SPLIT MNW HEATING COIL | SPLIT MSE HEATING COIL | SPLIT MNE HEATING COIL | SPLIT MN1 HEATING COIL | SPLIT MN2 HEATING COIL | SPLIT MS1 HEATING COIL | SPLIT MS2 HEATING COIL | SPLIT TSW HEATING COIL | SPLIT TNW HEATING COIL | SPLIT TSE HEATING COIL | SPLIT TNE HEATING COIL | SPLIT TN1 HEATING COIL | SPLIT TN2 HEATING COIL | SPLIT TS1 HEATING COIL | SPLIT TS2 HEATING COIL | SPLIT GSW COOLING COIL | SPLIT GNW COOLING COIL | SPLIT OFFICE COOLING COIL | SPLIT GNE COOLING COIL | SPLIT GN1 COOLING COIL | SPLIT GN2 COOLING COIL | SPLIT GS1 COOLING COIL | SPLIT GS2 COOLING COIL | SPLIT MSW COOLING COIL | SPLIT MNW COOLING COIL | SPLIT MSE COOLING COIL | SPLIT MNE COOLING COIL | SPLIT MN1 COOLING COIL | SPLIT MN2 COOLING COIL | SPLIT MS1 COOLING COIL | SPLIT MS2 COOLING COIL | SPLIT TSW COOLING COIL | SPLIT TNW COOLING COIL | SPLIT TSE COOLING COIL | SPLIT TNE COOLING COIL | SPLIT TN1 COOLING COIL | SPLIT TN2 COOLING COIL | SPLIT TS1 COOLING COIL | SPLIT TS2 COOLING COIL |FanReportMonthly
| SPLIT GSW SUPPLY FAN | G SW APARTMENT ERV SUP FAN | G SW APARTMENT ERV EXH FAN | SPLIT GNW SUPPLY FAN | G NW APARTMENT ERV SUP FAN | G NW APARTMENT ERV EXH FAN | SPLIT OFFICE SUPPLY FAN | SPLIT GNE SUPPLY FAN | G NE APARTMENT ERV SUP FAN | G NE APARTMENT ERV EXH FAN | SPLIT GN1 SUPPLY FAN | G N1 APARTMENT ERV SUP FAN | G N1 APARTMENT ERV EXH FAN | SPLIT GN2 SUPPLY FAN | G N2 APARTMENT ERV SUP FAN | G N2 APARTMENT ERV EXH FAN | SPLIT GS1 SUPPLY FAN | G S1 APARTMENT ERV SUP FAN | G S1 APARTMENT ERV EXH FAN | SPLIT GS2 SUPPLY FAN | G S2 APARTMENT ERV SUP FAN | G S2 APARTMENT ERV EXH FAN | SPLIT MSW SUPPLY FAN | M SW APARTMENT ERV SUP FAN | M SW APARTMENT ERV EXH FAN | SPLIT MNW SUPPLY FAN | M NW APARTMENT ERV SUP FAN | M NW APARTMENT ERV EXH FAN | SPLIT MSE SUPPLY FAN | M SE APARTMENT ERV SUP FAN | M SE APARTMENT ERV EXH FAN | SPLIT MNE SUPPLY FAN | M NE APARTMENT ERV SUP FAN | M NE APARTMENT ERV EXH FAN | SPLIT MN1 SUPPLY FAN | M N1 APARTMENT ERV SUP FAN | M N1 APARTMENT ERV EXH FAN | SPLIT MN2 SUPPLY FAN | M N2 APARTMENT ERV SUP FAN | M N2 APARTMENT ERV EXH FAN | SPLIT MS1 SUPPLY FAN | M S1 APARTMENT ERV SUP FAN | M S1 APARTMENT ERV EXH FAN | SPLIT MS2 SUPPLY FAN | M S2 APARTMENT ERV SUP FAN | M S2 APARTMENT ERV EXH FAN | SPLIT TSW SUPPLY FAN | T SW APARTMENT ERV SUP FAN | T SW APARTMENT ERV EXH FAN | SPLIT TNW SUPPLY FAN | T NW APARTMENT ERV SUP FAN | T NW APARTMENT ERV EXH FAN | SPLIT TSE SUPPLY FAN | T SE APARTMENT ERV SUP FAN | T SE APARTMENT ERV EXH FAN | SPLIT TNE SUPPLY FAN | T NE APARTMENT ERV SUP FAN | T NE APARTMENT ERV EXH FAN | SPLIT TN1 SUPPLY FAN | T N1 APARTMENT ERV SUP FAN | T N1 APARTMENT ERV EXH FAN | SPLIT TN2 SUPPLY FAN | T N2 APARTMENT ERV SUP FAN | T N2 APARTMENT ERV EXH FAN | SPLIT TS1 SUPPLY FAN | T S1 APARTMENT ERV SUP FAN | T S1 APARTMENT ERV EXH FAN | SPLIT TS2 SUPPLY FAN | T S2 APARTMENT ERV SUP FAN | T S2 APARTMENT ERV EXH FAN |ZoneTemperatureOscillationReportMonthly
| G SW APARTMENT | G NW APARTMENT | OFFICE | G NE APARTMENT | G N1 APARTMENT | G N2 APARTMENT | G S1 APARTMENT | G S2 APARTMENT | M SW APARTMENT | M NW APARTMENT | M SE APARTMENT | M NE APARTMENT | M N1 APARTMENT | M N2 APARTMENT | M S1 APARTMENT | M S2 APARTMENT | T SW APARTMENT | T NW APARTMENT | T SE APARTMENT | T NE APARTMENT | T N1 APARTMENT | T N2 APARTMENT | T S1 APARTMENT | T S2 APARTMENT | T CORRIDOR | G CORRIDOR | M CORRIDOR |AirLoopSystemEnergyAndWaterUseMonthly
| SPLIT GSW | SPLIT GNW | SPLIT OFFICE | SPLIT GNE | SPLIT GN1 | SPLIT GN2 | SPLIT GS1 | SPLIT GS2 | SPLIT MSW | SPLIT MNW | SPLIT MSE | SPLIT MNE | SPLIT MN1 | SPLIT MN2 | SPLIT MS1 | SPLIT MS2 | SPLIT TSW | SPLIT TNW | SPLIT TSE | SPLIT TNE | SPLIT TN1 | SPLIT TN2 | SPLIT TS1 | SPLIT TS2 |AirLoopSystemComponentLoadsMonthly
| SPLIT GSW | SPLIT GNW | SPLIT OFFICE | SPLIT GNE | SPLIT GN1 | SPLIT GN2 | SPLIT GS1 | SPLIT GS2 | SPLIT MSW | SPLIT MNW | SPLIT MSE | SPLIT MNE | SPLIT MN1 | SPLIT MN2 | SPLIT MS1 | SPLIT MS2 | SPLIT TSW | SPLIT TNW | SPLIT TSE | SPLIT TNE | SPLIT TN1 | SPLIT TN2 | SPLIT TS1 | SPLIT TS2 |AirLoopSystemComponentEnergyUseMonthly
| SPLIT GSW | SPLIT GNW | SPLIT OFFICE | SPLIT GNE | SPLIT GN1 | SPLIT GN2 | SPLIT GS1 | SPLIT GS2 | SPLIT MSW | SPLIT MNW | SPLIT MSE | SPLIT MNE | SPLIT MN1 | SPLIT MN2 | SPLIT MS1 | SPLIT MS2 | SPLIT TSW | SPLIT TNW | SPLIT TSE | SPLIT TNE | SPLIT TN1 | SPLIT TN2 | SPLIT TS1 | SPLIT TS2 |MechanicalVentilationLoadsMonthly
| G SW APARTMENT | G NW APARTMENT | OFFICE | G NE APARTMENT | G N1 APARTMENT | G N2 APARTMENT | G S1 APARTMENT | G S2 APARTMENT | M SW APARTMENT | M NW APARTMENT | M SE APARTMENT | M NE APARTMENT | M N1 APARTMENT | M N2 APARTMENT | M S1 APARTMENT | M S2 APARTMENT | T SW APARTMENT | T NW APARTMENT | T SE APARTMENT | T NE APARTMENT | T N1 APARTMENT | T N2 APARTMENT | T S1 APARTMENT | T S2 APARTMENT |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 09:14:58
General| Value | |
| Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 09:14 |
| RunPeriod | RUNPERIOD 1 |
| Weather File | Miami Intl Ap FL USA TMY3 WMO#=722020 |
| Latitude [deg] | 25.82 |
| Longitude [deg] | -80.3 |
| Elevation [m] | 11.00 |
| Time Zone | -5.0 |
| North Axis Angle [deg] | 0.00 |
| Rotation for Appendix G [deg] | 0.00 |
| Hours Simulated [hrs] | 8760.00 |
| Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
| Gross Wall Area [m2] | 1542.04 | 564.80 | 206.22 | 564.80 | 206.22 |
| Above Ground Wall Area [m2] | 1542.04 | 564.80 | 206.22 | 564.80 | 206.22 |
| Window Opening Area [m2] | 306.92 | 112.97 | 43.82 | 112.97 | 37.16 |
| Gross Window-Wall Ratio [%] | 19.90 | 20.00 | 21.25 | 20.00 | 18.02 |
| Above Ground Window-Wall Ratio [%] | 19.90 | 20.00 | 21.25 | 20.00 | 18.02 |
| Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
| Gross Wall Area [m2] | 1501.17 | 564.80 | 185.79 | 564.80 | 185.79 |
| Above Ground Wall Area [m2] | 1501.17 | 564.80 | 185.79 | 564.80 | 185.79 |
| Window Opening Area [m2] | 300.26 | 112.97 | 37.16 | 112.97 | 37.16 |
| Gross Window-Wall Ratio [%] | 20.00 | 20.00 | 20.00 | 20.00 | 20.00 |
| Above Ground Window-Wall Ratio [%] | 20.00 | 20.00 | 20.00 | 20.00 | 20.00 |
| Total | |
| Gross Roof Area [m2] | 783.65 |
| Skylight Area [m2] | 0.00 |
| Skylight-Roof Ratio [%] | 0.00 |
| Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
| G SW APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 0.00 | 11.71 | 11.71 | 8.6918 | 35.30 | 6.6700 |
| G NW APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 0.00 | 11.71 | 11.71 | 8.6918 | 35.30 | 6.6700 |
| OFFICE | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 0.00 | 11.71 | 11.71 | 9.7532 | 18.58 | 6.6700 |
| G NE APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 0.00 | 11.71 | 11.71 | 8.6918 | 35.30 | 6.6700 |
| G N1 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 0.00 | 7.06 | 7.06 | 8.6918 | 35.30 | 6.6700 |
| G N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 0.00 | 7.06 | 7.06 | 8.6918 | 35.30 | 6.6700 |
| G S1 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 0.00 | 7.06 | 7.06 | 8.6918 | 35.30 | 6.6700 |
| G S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 0.00 | 7.06 | 7.06 | 8.6918 | 35.30 | 6.6700 |
| M SW APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 58.52 | 0.00 | 11.71 | 11.71 | 8.6918 | 35.30 | 6.6700 |
| M NW APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 58.52 | 0.00 | 11.71 | 11.71 | 8.6918 | 35.30 | 6.6700 |
| M SE APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 58.52 | 0.00 | 11.71 | 11.71 | 8.6918 | 35.30 | 6.6700 |
| M NE APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 58.52 | 0.00 | 11.71 | 11.71 | 8.6918 | 35.30 | 6.6700 |
| M N1 APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 35.30 | 0.00 | 7.06 | 7.06 | 8.6918 | 35.30 | 6.6700 |
| M N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 35.30 | 0.00 | 7.06 | 7.06 | 8.6918 | 35.30 | 6.6700 |
| M S1 APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 35.30 | 0.00 | 7.06 | 7.06 | 8.6918 | 35.30 | 6.6700 |
| M S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 35.30 | 0.00 | 7.06 | 7.06 | 8.6918 | 35.30 | 6.6700 |
| T SW APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 0.00 | 11.71 | 11.71 | 8.6918 | 35.30 | 6.6700 |
| T NW APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 0.00 | 11.71 | 11.71 | 8.6918 | 35.30 | 6.6700 |
| T SE APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 0.00 | 11.71 | 11.71 | 8.6918 | 35.30 | 6.6700 |
| T NE APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 0.00 | 11.71 | 11.71 | 8.6918 | 35.30 | 6.6700 |
| T N1 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 0.00 | 7.06 | 7.06 | 8.6918 | 35.30 | 6.6700 |
| T N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 0.00 | 7.06 | 7.06 | 8.6918 | 35.30 | 6.6700 |
| T S1 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 0.00 | 7.06 | 7.06 | 8.6918 | 35.30 | 6.6700 |
| T S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 0.00 | 7.06 | 7.06 | 8.6918 | 35.30 | 6.6700 |
| T CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 0.00 | 1.11 | 1.11 | 4.7725 | 18.58 | 0.0000 |
| G CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 0.00 | 3.32 | 3.32 | 4.7725 | 18.58 | 105.2565 |
| M CORRIDOR | 77.66 | No | Yes | 236.69 | 2.00 | 10.22 | 0.00 | 1.11 | 1.11 | 4.7725 | 18.58 | 0.0000 |
| Total | 3134.61 | 9553.84 | 1542.04 | 0.00 | 306.92 | 306.92 | 8.3333 | 31.67 | 8.6167 | |||
| Conditioned Total | 2823.98 | 8607.06 | 1501.17 | 0.00 | 300.26 | 300.26 | 8.7250 | 34.33 | 6.6700 | |||
| Unconditioned Total | 310.64 | 946.78 | 40.87 | 0.00 | 6.66 | 6.66 | 4.7725 | 18.58 | 26.3141 | |||
| Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
| G SW APARTMENT | 88.25 | Yes | Yes | 1.00 | G SW APARTMENT | GENERAL | G SW APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| G NW APARTMENT | 88.25 | Yes | Yes | 1.00 | G NW APARTMENT | GENERAL | G NW APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| OFFICE | 88.25 | Yes | Yes | 1.00 | OFFICE | GENERAL | OFFICE | 9.7532 | 18.58 | 6.6700 | |
| G NE APARTMENT | 88.25 | Yes | Yes | 1.00 | G NE APARTMENT | GENERAL | G NE APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| G N1 APARTMENT | 88.25 | Yes | Yes | 1.00 | G N1 APARTMENT | GENERAL | G N1 APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| G N2 APARTMENT | 88.25 | Yes | Yes | 1.00 | G N2 APARTMENT | GENERAL | G N2 APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| G S1 APARTMENT | 88.25 | Yes | Yes | 1.00 | G S1 APARTMENT | GENERAL | G S1 APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| G S2 APARTMENT | 88.25 | Yes | Yes | 1.00 | G S2 APARTMENT | GENERAL | G S2 APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| M SW APARTMENT | 88.25 | Yes | Yes | 2.00 | M SW APARTMENT | GENERAL | M SW APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| M NW APARTMENT | 88.25 | Yes | Yes | 2.00 | M NW APARTMENT | GENERAL | M NW APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| M SE APARTMENT | 88.25 | Yes | Yes | 2.00 | M SE APARTMENT | GENERAL | M SE APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| M NE APARTMENT | 88.25 | Yes | Yes | 2.00 | M NE APARTMENT | GENERAL | M NE APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| M N1 APARTMENT | 88.25 | Yes | Yes | 2.00 | M N1 APARTMENT | GENERAL | M N1 APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| M N2 APARTMENT | 88.25 | Yes | Yes | 2.00 | M N2 APARTMENT | GENERAL | M N2 APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| M S1 APARTMENT | 88.25 | Yes | Yes | 2.00 | M S1 APARTMENT | GENERAL | M S1 APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| M S2 APARTMENT | 88.25 | Yes | Yes | 2.00 | M S2 APARTMENT | GENERAL | M S2 APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| T SW APARTMENT | 88.25 | Yes | Yes | 1.00 | T SW APARTMENT | GENERAL | T SW APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| T NW APARTMENT | 88.25 | Yes | Yes | 1.00 | T NW APARTMENT | GENERAL | T NW APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| T SE APARTMENT | 88.25 | Yes | Yes | 1.00 | T SE APARTMENT | GENERAL | T SE APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| T NE APARTMENT | 88.25 | Yes | Yes | 1.00 | T NE APARTMENT | GENERAL | T NE APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| T N1 APARTMENT | 88.25 | Yes | Yes | 1.00 | T N1 APARTMENT | GENERAL | T N1 APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| T N2 APARTMENT | 88.25 | Yes | Yes | 1.00 | T N2 APARTMENT | GENERAL | T N2 APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| T S1 APARTMENT | 88.25 | Yes | Yes | 1.00 | T S1 APARTMENT | GENERAL | T S1 APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| T S2 APARTMENT | 88.25 | Yes | Yes | 1.00 | T S2 APARTMENT | GENERAL | T S2 APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| T CORRIDOR | 77.66 | No | Yes | 1.00 | T CORRIDOR | GENERAL | T CORRIDOR | 4.7725 | 18.58 | 0.0000 | |
| G CORRIDOR | 77.66 | No | Yes | 1.00 | G CORRIDOR | GENERAL | G CORRIDOR | 4.7725 | 18.58 | 105.2565 | |
| M CORRIDOR | 77.66 | No | Yes | 2.00 | M CORRIDOR | GENERAL | M CORRIDOR | 4.7725 | 18.58 | 0.0000 | |
| Total | 3134.61 | 8.3333 | 15.84 | 8.6167 | |||||||
| Conditioned Total | 2823.98 | 8.7250 | 17.17 | 6.6700 | |||||||
| Unconditioned Total | 310.64 | 4.7725 | 9.29 | 26.3141 | |||||||
| Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
| Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
| GENERAL | 3134.61 | 2823.98 | 310.64 | 0.00 | 6.2575 | 41.91 | 7.1145 |
| Total | 3134.61 | 2823.98 | 310.64 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 09:14:58
End Uses| Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
| Time of Peak | 27-JUL-17:40 | 04-FEB-06:00 | - | - | - | - | - | - | - | - | - | - | 01-JAN-07:10 |
| Heating | 0.00 | 15306.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Cooling | 28417.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Lighting | 5231.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment | 22609.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans | 8308.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems | 27576.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Total End Uses | 92145.00 | 15306.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
| Heating | General | 0.00 | 15306.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Cooling | General | 28417.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Lighting | LightsWired | 4887.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LightsPlugIn | 344.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment | MiscPlug | 18441.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| ElevatorLift | 4006.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| ElevatorLightsFan | 162.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| General | 8308.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems | Water Heater | 27576.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 09:14:58
Values gathered over 8760.00 hours| Source Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
| Heating | 0.00 | 2.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Cooling | 1251.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Lighting | 314.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Lighting | 158.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment | 1452.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans | 471.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems | 1128.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Total Source Energy End Use Components | 4777.23 | 2.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
| Heating | 0.00 | 0.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Cooling | 443.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Lighting | 111.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Lighting | 56.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment | 514.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans | 167.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems | 399.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Total Source Energy End Use Components | 1691.67 | 0.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
| Heating | 0.00 | 0.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Cooling | 399.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Lighting | 100.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Lighting | 50.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment | 463.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans | 150.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems | 360.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Total Source Energy End Use Components | 1524.02 | 0.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 09:14:58
ZoneHVAC:EnergyRecoveryVentilator| User-Specified Supply Air Flow Rate [m3/s] | User-Specified Exhaust Air Flow Rate [m3/s] | |
| G SW APARTMENT ERV | 0.025955 | 0.025955 |
| G NW APARTMENT ERV | 0.025955 | 0.025955 |
| G NE APARTMENT ERV | 0.025955 | 0.025955 |
| G N1 APARTMENT ERV | 0.025955 | 0.025955 |
| G N2 APARTMENT ERV | 0.025955 | 0.025955 |
| G S1 APARTMENT ERV | 0.025955 | 0.025955 |
| G S2 APARTMENT ERV | 0.025955 | 0.025955 |
| M SW APARTMENT ERV | 0.051909 | 0.051909 |
| M NW APARTMENT ERV | 0.051909 | 0.051909 |
| M SE APARTMENT ERV | 0.051909 | 0.051909 |
| M NE APARTMENT ERV | 0.051909 | 0.051909 |
| M N1 APARTMENT ERV | 0.051909 | 0.051909 |
| M N2 APARTMENT ERV | 0.051909 | 0.051909 |
| M S1 APARTMENT ERV | 0.051909 | 0.051909 |
| M S2 APARTMENT ERV | 0.051909 | 0.051909 |
| T SW APARTMENT ERV | 0.025955 | 0.025955 |
| T NW APARTMENT ERV | 0.025955 | 0.025955 |
| T SE APARTMENT ERV | 0.025955 | 0.025955 |
| T NE APARTMENT ERV | 0.025955 | 0.025955 |
| T N1 APARTMENT ERV | 0.025955 | 0.025955 |
| T N2 APARTMENT ERV | 0.025955 | 0.025955 |
| T S1 APARTMENT ERV | 0.025955 | 0.025955 |
| T S2 APARTMENT ERV | 0.025955 | 0.025955 |
| Design Size Maximum Flow Rate [m3/s] | |
| G SW APARTMENT ERV SUP FAN | 0.025955 |
| G SW APARTMENT ERV EXH FAN | 0.025955 |
| G NW APARTMENT ERV SUP FAN | 0.025955 |
| G NW APARTMENT ERV EXH FAN | 0.025955 |
| G NE APARTMENT ERV SUP FAN | 0.025955 |
| G NE APARTMENT ERV EXH FAN | 0.025955 |
| G N1 APARTMENT ERV SUP FAN | 0.025955 |
| G N1 APARTMENT ERV EXH FAN | 0.025955 |
| G N2 APARTMENT ERV SUP FAN | 0.025955 |
| G N2 APARTMENT ERV EXH FAN | 0.025955 |
| G S1 APARTMENT ERV SUP FAN | 0.025955 |
| G S1 APARTMENT ERV EXH FAN | 0.025955 |
| G S2 APARTMENT ERV SUP FAN | 0.025955 |
| G S2 APARTMENT ERV EXH FAN | 0.025955 |
| M SW APARTMENT ERV SUP FAN | 0.051909 |
| M SW APARTMENT ERV EXH FAN | 0.051909 |
| M NW APARTMENT ERV SUP FAN | 0.051909 |
| M NW APARTMENT ERV EXH FAN | 0.051909 |
| M SE APARTMENT ERV SUP FAN | 0.051909 |
| M SE APARTMENT ERV EXH FAN | 0.051909 |
| M NE APARTMENT ERV SUP FAN | 0.051909 |
| M NE APARTMENT ERV EXH FAN | 0.051909 |
| M N1 APARTMENT ERV SUP FAN | 0.051909 |
| M N1 APARTMENT ERV EXH FAN | 0.051909 |
| M N2 APARTMENT ERV SUP FAN | 0.051909 |
| M N2 APARTMENT ERV EXH FAN | 0.051909 |
| M S1 APARTMENT ERV SUP FAN | 0.051909 |
| M S1 APARTMENT ERV EXH FAN | 0.051909 |
| M S2 APARTMENT ERV SUP FAN | 0.051909 |
| M S2 APARTMENT ERV EXH FAN | 0.051909 |
| T SW APARTMENT ERV SUP FAN | 0.025955 |
| T SW APARTMENT ERV EXH FAN | 0.025955 |
| T NW APARTMENT ERV SUP FAN | 0.025955 |
| T NW APARTMENT ERV EXH FAN | 0.025955 |
| T SE APARTMENT ERV SUP FAN | 0.025955 |
| T SE APARTMENT ERV EXH FAN | 0.025955 |
| T NE APARTMENT ERV SUP FAN | 0.025955 |
| T NE APARTMENT ERV EXH FAN | 0.025955 |
| T N1 APARTMENT ERV SUP FAN | 0.025955 |
| T N1 APARTMENT ERV EXH FAN | 0.025955 |
| T N2 APARTMENT ERV SUP FAN | 0.025955 |
| T N2 APARTMENT ERV EXH FAN | 0.025955 |
| T S1 APARTMENT ERV SUP FAN | 0.025955 |
| T S1 APARTMENT ERV EXH FAN | 0.025955 |
| T S2 APARTMENT ERV SUP FAN | 0.025955 |
| T S2 APARTMENT ERV EXH FAN | 0.025955 |
| SPLIT GSW SUPPLY FAN | 0.347314 |
| SPLIT GNW SUPPLY FAN | 0.352146 |
| SPLIT OFFICE SUPPLY FAN | 0.373383 |
| SPLIT GNE SUPPLY FAN | 0.325582 |
| SPLIT GN1 SUPPLY FAN | 0.294860 |
| SPLIT GN2 SUPPLY FAN | 0.294355 |
| SPLIT GS1 SUPPLY FAN | 0.290438 |
| SPLIT GS2 SUPPLY FAN | 0.292539 |
| SPLIT MSW SUPPLY FAN | 0.796260 |
| SPLIT MNW SUPPLY FAN | 0.808398 |
| SPLIT MSE SUPPLY FAN | 0.726434 |
| SPLIT MNE SUPPLY FAN | 0.738490 |
| SPLIT MN1 SUPPLY FAN | 0.666444 |
| SPLIT MN2 SUPPLY FAN | 0.665207 |
| SPLIT MS1 SUPPLY FAN | 0.654884 |
| SPLIT MS2 SUPPLY FAN | 0.653637 |
| SPLIT TSW SUPPLY FAN | 0.445392 |
| SPLIT TNW SUPPLY FAN | 0.456796 |
| SPLIT TSE SUPPLY FAN | 0.393009 |
| SPLIT TNE SUPPLY FAN | 0.404206 |
| SPLIT TN1 SUPPLY FAN | 0.375824 |
| SPLIT TN2 SUPPLY FAN | 0.374180 |
| SPLIT TS1 SUPPLY FAN | 0.364671 |
| SPLIT TS2 SUPPLY FAN | 0.363033 |
| Design Size Nominal Supply Air Flow Rate [m3/s] | |
| G SW APARTMENT OA HEAT EXCHANGER | 0.025955 |
| G NW APARTMENT OA HEAT EXCHANGER | 0.025955 |
| G NE APARTMENT OA HEAT EXCHANGER | 0.025955 |
| G N1 APARTMENT OA HEAT EXCHANGER | 0.025955 |
| G N2 APARTMENT OA HEAT EXCHANGER | 0.025955 |
| G S1 APARTMENT OA HEAT EXCHANGER | 0.025955 |
| G S2 APARTMENT OA HEAT EXCHANGER | 0.025955 |
| M SW APARTMENT OA HEAT EXCHANGER | 0.051909 |
| M NW APARTMENT OA HEAT EXCHANGER | 0.051909 |
| M SE APARTMENT OA HEAT EXCHANGER | 0.051909 |
| M NE APARTMENT OA HEAT EXCHANGER | 0.051909 |
| M N1 APARTMENT OA HEAT EXCHANGER | 0.051909 |
| M N2 APARTMENT OA HEAT EXCHANGER | 0.051909 |
| M S1 APARTMENT OA HEAT EXCHANGER | 0.051909 |
| M S2 APARTMENT OA HEAT EXCHANGER | 0.051909 |
| T SW APARTMENT OA HEAT EXCHANGER | 0.025955 |
| T NW APARTMENT OA HEAT EXCHANGER | 0.025955 |
| T SE APARTMENT OA HEAT EXCHANGER | 0.025955 |
| T NE APARTMENT OA HEAT EXCHANGER | 0.025955 |
| T N1 APARTMENT OA HEAT EXCHANGER | 0.025955 |
| T N2 APARTMENT OA HEAT EXCHANGER | 0.025955 |
| T S1 APARTMENT OA HEAT EXCHANGER | 0.025955 |
| T S2 APARTMENT OA HEAT EXCHANGER | 0.025955 |
| Design Size Maximum Air Flow Rate [m3/s] | |
| G SW APARTMENT DIRECT AIR | 0.347314 |
| G NW APARTMENT DIRECT AIR | 0.352146 |
| OFFICE DIRECT AIR | 0.373383 |
| G NE APARTMENT DIRECT AIR | 0.325582 |
| G N1 APARTMENT DIRECT AIR | 0.294860 |
| G N2 APARTMENT DIRECT AIR | 0.294355 |
| G S1 APARTMENT DIRECT AIR | 0.290438 |
| G S2 APARTMENT DIRECT AIR | 0.292539 |
| M SW APARTMENT DIRECT AIR | 0.796260 |
| M NW APARTMENT DIRECT AIR | 0.808398 |
| M SE APARTMENT DIRECT AIR | 0.726434 |
| M NE APARTMENT DIRECT AIR | 0.738490 |
| M N1 APARTMENT DIRECT AIR | 0.666444 |
| M N2 APARTMENT DIRECT AIR | 0.665207 |
| M S1 APARTMENT DIRECT AIR | 0.654884 |
| M S2 APARTMENT DIRECT AIR | 0.653637 |
| T SW APARTMENT DIRECT AIR | 0.445392 |
| T NW APARTMENT DIRECT AIR | 0.456796 |
| T SE APARTMENT DIRECT AIR | 0.393009 |
| T NE APARTMENT DIRECT AIR | 0.404206 |
| T N1 APARTMENT DIRECT AIR | 0.375824 |
| T N2 APARTMENT DIRECT AIR | 0.374180 |
| T S1 APARTMENT DIRECT AIR | 0.364671 |
| T S2 APARTMENT DIRECT AIR | 0.363033 |
| Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
| SPLIT GSW | 0.347314 | 0.347314 | 0.347314 | 0.347314 | 0.347314 | 0.347314 | 1.00 | 1.00 | 0.347314 |
| SPLIT GNW | 0.352146 | 0.352146 | 0.352146 | 0.352146 | 0.352146 | 0.352146 | 1.00 | 1.00 | 0.352146 |
| SPLIT OFFICE | 0.373383 | 0.373383 | 0.373383 | 0.373383 | 0.373383 | 0.373383 | 1.00 | 1.000000 | 0.373383 |
| SPLIT GNE | 0.325582 | 0.325582 | 0.325582 | 0.325582 | 0.325582 | 0.325582 | 1.00 | 1.000000 | 0.325582 |
| SPLIT GN1 | 0.294860 | 0.294860 | 0.294860 | 0.294860 | 0.294860 | 0.294860 | 1.00 | 1.00 | 0.294860 |
| SPLIT GN2 | 0.294355 | 0.294355 | 0.294355 | 0.294355 | 0.294355 | 0.294355 | 1.00 | 1.00 | 0.294355 |
| SPLIT GS1 | 0.290438 | 0.290438 | 0.290438 | 0.290438 | 0.290438 | 0.290438 | 1.00 | 1.00 | 0.290438 |
| SPLIT GS2 | 0.292539 | 0.292539 | 0.292539 | 0.292539 | 0.292539 | 0.292539 | 1.00 | 1.00 | 0.292539 |
| SPLIT MSW | 0.796260 | 0.796260 | 0.796260 | 0.796260 | 0.796260 | 0.796260 | 1.00 | 1.000000 | 0.796260 |
| SPLIT MNW | 0.808398 | 0.808398 | 0.808398 | 0.808398 | 0.808398 | 0.808398 | 1.00 | 1.00 | 0.808398 |
| SPLIT MSE | 0.726434 | 0.726434 | 0.726434 | 0.726434 | 0.726434 | 0.726434 | 1.00 | 1.00 | 0.726434 |
| SPLIT MNE | 0.738490 | 0.738490 | 0.738490 | 0.738490 | 0.738490 | 0.738490 | 1.00 | 1.00 | 0.738490 |
| SPLIT MN1 | 0.666444 | 0.666444 | 0.666444 | 0.666444 | 0.666444 | 0.666444 | 1.00 | 1.00 | 0.666444 |
| SPLIT MN2 | 0.665207 | 0.665207 | 0.665207 | 0.665207 | 0.665207 | 0.665207 | 1.00 | 1.000000 | 0.665207 |
| SPLIT MS1 | 0.654884 | 0.654884 | 0.654884 | 0.654884 | 0.654884 | 0.654884 | 1.00 | 1.00 | 0.654884 |
| SPLIT MS2 | 0.653637 | 0.653637 | 0.653637 | 0.653637 | 0.653637 | 0.653637 | 1.00 | 1.00 | 0.653637 |
| SPLIT TSW | 0.445392 | 0.445392 | 0.445392 | 0.445392 | 0.445392 | 0.445392 | 1.00 | 1.000000 | 0.445392 |
| SPLIT TNW | 0.456796 | 0.456796 | 0.456796 | 0.456796 | 0.456796 | 0.456796 | 1.00 | 1.00 | 0.456796 |
| SPLIT TSE | 0.393009 | 0.393009 | 0.393009 | 0.393009 | 0.393009 | 0.393009 | 1.00 | 1.00 | 0.393009 |
| SPLIT TNE | 0.404206 | 0.404206 | 0.404206 | 0.404206 | 0.404206 | 0.404206 | 1.00 | 1.00 | 0.404206 |
| SPLIT TN1 | 0.375824 | 0.375824 | 0.375824 | 0.375824 | 0.375824 | 0.375824 | 1.00 | 1.00 | 0.375824 |
| SPLIT TN2 | 0.374180 | 0.374180 | 0.374180 | 0.374180 | 0.374180 | 0.374180 | 1.00 | 1.00 | 0.374180 |
| SPLIT TS1 | 0.364671 | 0.364671 | 0.364671 | 0.364671 | 0.364671 | 0.364671 | 1.00 | 1.00 | 0.364671 |
| SPLIT TS2 | 0.363033 | 0.363033 | 0.363033 | 0.363033 | 0.363033 | 0.363033 | 1.00 | 1.00 | 0.363033 |
| Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
| SPLIT GSW_OA_CONTROLLER | 0.347314 | 0.025955 |
| SPLIT GNW_OA_CONTROLLER | 0.352146 | 0.025955 |
| SPLIT OFFICE_OA_CONTROLLER | 0.373383 | 0.038106 |
| SPLIT GNE_OA_CONTROLLER | 0.325582 | 0.025955 |
| SPLIT GN1_OA_CONTROLLER | 0.294860 | 0.025955 |
| SPLIT GN2_OA_CONTROLLER | 0.294355 | 0.025955 |
| SPLIT GS1_OA_CONTROLLER | 0.290438 | 0.025955 |
| SPLIT GS2_OA_CONTROLLER | 0.292539 | 0.025955 |
| SPLIT MSW_OA_CONTROLLER | 0.796260 | 0.051909 |
| SPLIT MNW_OA_CONTROLLER | 0.808398 | 0.051909 |
| SPLIT MSE_OA_CONTROLLER | 0.726434 | 0.051909 |
| SPLIT MNE_OA_CONTROLLER | 0.738490 | 0.051909 |
| SPLIT MN1_OA_CONTROLLER | 0.666444 | 0.051909 |
| SPLIT MN2_OA_CONTROLLER | 0.665207 | 0.051909 |
| SPLIT MS1_OA_CONTROLLER | 0.654884 | 0.051909 |
| SPLIT MS2_OA_CONTROLLER | 0.653637 | 0.051909 |
| SPLIT TSW_OA_CONTROLLER | 0.445392 | 0.025955 |
| SPLIT TNW_OA_CONTROLLER | 0.456796 | 0.025955 |
| SPLIT TSE_OA_CONTROLLER | 0.393009 | 0.025955 |
| SPLIT TNE_OA_CONTROLLER | 0.404206 | 0.025955 |
| SPLIT TN1_OA_CONTROLLER | 0.375824 | 0.025955 |
| SPLIT TN2_OA_CONTROLLER | 0.374180 | 0.025955 |
| SPLIT TS1_OA_CONTROLLER | 0.364671 | 0.025955 |
| SPLIT TS2_OA_CONTROLLER | 0.363033 | 0.025955 |
| Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | Design Size Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
| SPLIT GSW_UNITARY_PACKAGE_DX | 0.347314 | 0.347314 | 0.347314 | 0.347314 | 6608.03 | 8322.47 | 40.00 | 1.00 |
| SPLIT GNW_UNITARY_PACKAGE_DX | 0.352146 | 0.352146 | 0.352146 | 0.352146 | 6661.49 | 8432.74 | 40.00 | 1.00 |
| SPLIT OFFICE_UNITARY_PACKAGE_DX | 0.373383 | 0.373383 | 0.373383 | 0.373383 | 7123.34 | 9100.04 | 40.00 | 1.00 |
| SPLIT GNE_UNITARY_PACKAGE_DX | 0.325582 | 0.325582 | 0.325582 | 0.325582 | 6270.12 | 7825.98 | 40.00 | 1.00 |
| SPLIT GN1_UNITARY_PACKAGE_DX | 0.294860 | 0.294860 | 0.294860 | 0.294860 | 5664.08 | 7124.20 | 40.00 | 1.00 |
| SPLIT GN2_UNITARY_PACKAGE_DX | 0.294355 | 0.294355 | 0.294355 | 0.294355 | 5656.58 | 7112.66 | 40.00 | 1.00 |
| SPLIT GS1_UNITARY_PACKAGE_DX | 0.290438 | 0.290438 | 0.290438 | 0.290438 | 5631.64 | 7023.27 | 40.00 | 1.00 |
| SPLIT GS2_UNITARY_PACKAGE_DX | 0.292539 | 0.292539 | 0.292539 | 0.292539 | 5664.10 | 7071.25 | 40.00 | 1.00 |
| SPLIT MSW_UNITARY_PACKAGE_DX | 0.796260 | 0.796260 | 0.796260 | 0.796260 | 15069.96 | 18966.56 | 40.00 | 1.00 |
| SPLIT MNW_UNITARY_PACKAGE_DX | 0.808398 | 0.808398 | 0.808398 | 0.808398 | 15225.10 | 19243.60 | 40.00 | 1.00 |
| SPLIT MSE_UNITARY_PACKAGE_DX | 0.726434 | 0.726434 | 0.726434 | 0.726434 | 14034.46 | 17371.56 | 40.00 | 1.00 |
| SPLIT MNE_UNITARY_PACKAGE_DX | 0.738490 | 0.738490 | 0.738490 | 0.738490 | 14180.79 | 17646.73 | 40.00 | 1.00 |
| SPLIT MN1_UNITARY_PACKAGE_DX | 0.666444 | 0.666444 | 0.666444 | 0.666444 | 12700.74 | 16000.98 | 40.00 | 1.00 |
| SPLIT MN2_UNITARY_PACKAGE_DX | 0.665207 | 0.665207 | 0.665207 | 0.665207 | 12682.31 | 15972.70 | 40.00 | 1.00 |
| SPLIT MS1_UNITARY_PACKAGE_DX | 0.654884 | 0.654884 | 0.654884 | 0.654884 | 12578.74 | 15737.07 | 40.00 | 1.00 |
| SPLIT MS2_UNITARY_PACKAGE_DX | 0.653637 | 0.653637 | 0.653637 | 0.653637 | 12560.38 | 15708.58 | 40.00 | 1.00 |
| SPLIT TSW_UNITARY_PACKAGE_DX | 0.445392 | 0.445392 | 0.445392 | 0.445392 | 8421.94 | 10562.93 | 40.00 | 1.00 |
| SPLIT TNW_UNITARY_PACKAGE_DX | 0.456796 | 0.456796 | 0.456796 | 0.456796 | 8585.83 | 10823.29 | 40.00 | 1.00 |
| SPLIT TSE_UNITARY_PACKAGE_DX | 0.393009 | 0.393009 | 0.393009 | 0.393009 | 7618.33 | 9366.36 | 40.00 | 1.00 |
| SPLIT TNE_UNITARY_PACKAGE_DX | 0.404206 | 0.404206 | 0.404206 | 0.404206 | 7777.14 | 9622.02 | 40.00 | 1.00 |
| SPLIT TN1_UNITARY_PACKAGE_DX | 0.375824 | 0.375824 | 0.375824 | 0.375824 | 7076.41 | 8973.63 | 40.00 | 1.00 |
| SPLIT TN2_UNITARY_PACKAGE_DX | 0.374180 | 0.374180 | 0.374180 | 0.374180 | 7051.44 | 8936.08 | 40.00 | 1.00 |
| SPLIT TS1_UNITARY_PACKAGE_DX | 0.364671 | 0.364671 | 0.364671 | 0.364671 | 6922.54 | 8718.99 | 40.00 | 1.00 |
| SPLIT TS2_UNITARY_PACKAGE_DX | 0.363033 | 0.363033 | 0.363033 | 0.363033 | 6897.77 | 8681.56 | 40.00 | 1.00 |
| Design Size Rated Air Flow Rate [m3/s] | Design Size Gross Rated Total Cooling Capacity [W] | Design Size Gross Rated Sensible Heat Ratio | |
| SPLIT GSW COOLING COIL | 0.347314 | 6608.03 | 0.796876 |
| SPLIT GNW COOLING COIL | 0.352146 | 6661.49 | 0.798724 |
| SPLIT OFFICE COOLING COIL | 0.373383 | 7123.34 | 0.795009 |
| SPLIT GNE COOLING COIL | 0.325582 | 6270.12 | 0.791022 |
| SPLIT GN1 COOLING COIL | 0.294860 | 5664.08 | 0.792825 |
| SPLIT GN2 COOLING COIL | 0.294355 | 5656.58 | 0.792701 |
| SPLIT GS1 COOLING COIL | 0.290438 | 5631.64 | 0.788871 |
| SPLIT GS2 COOLING COIL | 0.292539 | 5664.10 | 0.789329 |
| SPLIT MSW COOLING COIL | 0.796260 | 15069.96 | 0.798570 |
| SPLIT MNW COOLING COIL | 0.808398 | 15225.10 | 0.800145 |
| SPLIT MSE COOLING COIL | 0.726434 | 14034.46 | 0.790016 |
| SPLIT MNE COOLING COIL | 0.738490 | 14180.79 | 0.792939 |
| SPLIT MN1 COOLING COIL | 0.666444 | 12700.74 | 0.795350 |
| SPLIT MN2 COOLING COIL | 0.665207 | 12682.31 | 0.795220 |
| SPLIT MS1 COOLING COIL | 0.654884 | 12578.74 | 0.792854 |
| SPLIT MS2 COOLING COIL | 0.653637 | 12560.38 | 0.792713 |
| SPLIT TSW COOLING COIL | 0.445392 | 8421.94 | 0.798856 |
| SPLIT TNW COOLING COIL | 0.456796 | 8585.83 | 0.800796 |
| SPLIT TSE COOLING COIL | 0.393009 | 7618.33 | 0.788960 |
| SPLIT TNE COOLING COIL | 0.404206 | 7777.14 | 0.792312 |
| SPLIT TN1 COOLING COIL | 0.375824 | 7076.41 | 0.800225 |
| SPLIT TN2 COOLING COIL | 0.374180 | 7051.44 | 0.800950 |
| SPLIT TS1 COOLING COIL | 0.364671 | 6922.54 | 0.797604 |
| SPLIT TS2 COOLING COIL | 0.363033 | 6897.77 | 0.797309 |
| Design Size Nominal Capacity [W] | |
| SPLIT GSW HEATING COIL | 8322.47 |
| SPLIT GNW HEATING COIL | 8432.74 |
| SPLIT OFFICE HEATING COIL | 9100.04 |
| SPLIT GNE HEATING COIL | 7825.98 |
| SPLIT GN1 HEATING COIL | 7124.20 |
| SPLIT GN2 HEATING COIL | 7112.66 |
| SPLIT GS1 HEATING COIL | 7023.27 |
| SPLIT GS2 HEATING COIL | 7071.25 |
| SPLIT MSW HEATING COIL | 18966.56 |
| SPLIT MNW HEATING COIL | 19243.60 |
| SPLIT MSE HEATING COIL | 17371.56 |
| SPLIT MNE HEATING COIL | 17646.73 |
| SPLIT MN1 HEATING COIL | 16000.98 |
| SPLIT MN2 HEATING COIL | 15972.70 |
| SPLIT MS1 HEATING COIL | 15737.07 |
| SPLIT MS2 HEATING COIL | 15708.58 |
| SPLIT TSW HEATING COIL | 10562.93 |
| SPLIT TNW HEATING COIL | 10823.29 |
| SPLIT TSE HEATING COIL | 9366.36 |
| SPLIT TNE HEATING COIL | 9622.02 |
| SPLIT TN1 HEATING COIL | 8973.63 |
| SPLIT TN2 HEATING COIL | 8936.08 |
| SPLIT TS1 HEATING COIL | 8718.99 |
| SPLIT TS2 HEATING COIL | 8681.56 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 09:14:58
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other Surfaces| None |
| Possible Shadow Receivers | |
| G SWALL SWA | GWINDOW1 S SWA | |
| G WWALL SWA | GWINDOW1 W SWA | |
| G NWALL NWA | GWINDOW1 N NWA | |
| G WWALL NWA | GWINDOW1 W NWA | |
| G SWALL SEA | GWINDOW1 S SEA | |
| G EWALL SEA | GWINDOW1 E SEA | |
| G NWALL NEA | GWINDOW1 N NEA | |
| G EWALL NEA | GWINDOW1 E NEA | |
| G NWALL N1A | GWINDOW1 N N1A | |
| G NWALL N2A | GWINDOW1 N N2A | |
| G SWALL S1A | GWINDOW1 S S1A | |
| G SWALL S2A | GWINDOW1 S S2A | |
| M WWALL SWA | MWINDOW1 W SWA | |
| M SWALL SWA | MWINDOW1 S SWA | |
| M NWALL NWA | MWINDOW1 N NWA | |
| M WWALL NWA | MWINDOW1 W NWA | |
| M EWALL SEA | MWINDOW1 E SEA | |
| M SWALL SEA | MWINDOW1 S SEA | |
| M NWALL NEA | MWINDOW1 N NEA | |
| M EWALL NEA | MWINDOW1 E NEA | |
| M NWALL N1A | MWINDOW1 N N1A | |
| M NWALL N2A | MWINDOW1 N N2A | |
| M SWALL S1A | MWINDOW1 S S1A | |
| M SWALL S2A | MWINDOW1 S S2A | |
| T WWALL SWA | TWINDOW1 W SWA | |
| T SWALL SWA | TWINDOW1 S SWA | |
| T NWALL NWA | TWINDOW1 N NWA | |
| T WWALL NWA | TWINDOW1 W NWA | |
| T EWALL SEA | TWINDOW1 E SEA | |
| T SWALL SEA | TWINDOW1 S SEA | |
| T NWALL NEA | TWINDOW1 N NEA | |
| T EWALL NEA | TWINDOW1 E NEA | |
| T NWALL N1A | TWINDOW1 N N1A | |
| T NWALL N2A | TWINDOW1 N N2A | |
| T SWALL S1A | TWINDOW1 S S1A | |
| T SWALL S2A | TWINDOW1 S S2A | |
| T EWALL C | TWINDOW14 | |
| G EWALL C | ENTRANCE DOOR | |
| M EWALL C | MWINDOW14 | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 09:14:58
Time Not Meeting the Adaptive Comfort Models during Occupied Hours| ASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 09:14:58
Version| Version ID | |
| 1 | 22.1 |
| #TimeSteps | Minutes per TimeStep {minutes} | |
| 1 | 6 | 10 |
| Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
| 1 | 1 | 20 | 2 | 8 |
| Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
| 1 | Yes | Yes | No | No | Yes | No |
| Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
| 1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
| Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
| 1 | 0.556 | 0.556 |
| Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
| 1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
| Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
| 1 | 26.30 | 23.60 | 20.30 | 19.40 | 20.90 | 21.60 | 24.10 | 26.40 | 27.70 | 28.10 | 28.00 | 27.50 |
| Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
| 1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
| Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
| 1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
| Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
| 1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
| Normal | Daylighting {dimensionless} | |
| 1 | 1.000 | 1.000 |
| Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
| 1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
| Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
| 1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
| Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
| 1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
| Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
| 1 | Miami Intl Ap FL USA TMY3 WMO#=722020 | 25.82 | -80.30 | -5.00 | 11.00 | 101193 | 1.2027 |
| Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
| 1 | Correlation | NA | 24.49 | 8.70 | NA |
| Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
| 1 | ApartmentMidRise | 0.000 | City | 4.00000E-002 | 0.40000 | FullExterior | 25 | 6 |
| Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
| 1 | TARP |
| Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
| 1 | TARP |
| Value {Anisotropic} | |
| 1 | Anisotropic |
| Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
| 1 | ThirdOrderBackwardDifference |
| Simulation {Yes/No} | Carbon Dioxide Concentration | |
| 1 | No | N/A |
| Simulation {Yes/No} | Generic Contaminant Concentration | |
| 1 | No | N/A |
| Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
| 1 | No | N/A | N/A | N/A |
| Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
| 1 | RegulaFalsi |
| Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
| 1 | 0.330 | 460.000 | 6.500000E-003 |
| Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
| 1 | LowerLeftCorner | Clockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
| Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
| 1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
| Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
| 1 | 0 | 0 | 0 |
| Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
| 1 | 27 | 243 | 39 |
| Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
| 1 | G SW APARTMENT | 0.0 | 0.00 | 0.00 | 0.00 | 5.79 | 3.81 | 1.52 | 1 | 1 | 1 | 0.00 | 11.58 | 0.00 | 7.62 | 0.00 | 3.05 | 3.05 | 268.97 | TARP | TARP | 88.25 | 58.52 | 46.82 | 11.71 | 6 | 2 | 0 | Yes |
| 2 | G NW APARTMENT | 0.0 | 0.00 | 9.30 | 0.00 | 5.79 | 13.11 | 1.52 | 1 | 1 | 1 | 0.00 | 11.58 | 9.30 | 16.92 | 0.00 | 3.05 | 3.05 | 268.97 | TARP | TARP | 88.25 | 58.52 | 46.82 | 11.71 | 6 | 2 | 0 | Yes |
| 3 | OFFICE | 0.0 | 34.75 | 0.00 | 0.00 | 40.54 | 3.81 | 1.52 | 1 | 1 | 1 | 34.75 | 46.33 | 0.00 | 7.62 | 0.00 | 3.05 | 3.05 | 268.97 | TARP | TARP | 88.25 | 58.52 | 46.82 | 11.71 | 6 | 2 | 0 | Yes |
| 4 | G NE APARTMENT | 0.0 | 34.75 | 9.30 | 0.00 | 40.54 | 13.11 | 1.52 | 1 | 1 | 1 | 34.75 | 46.33 | 9.30 | 16.92 | 0.00 | 3.05 | 3.05 | 268.97 | TARP | TARP | 88.25 | 58.52 | 46.82 | 11.71 | 6 | 2 | 0 | Yes |
| 5 | G N1 APARTMENT | 0.0 | 11.58 | 9.30 | 0.00 | 17.37 | 13.11 | 1.52 | 1 | 1 | 1 | 11.58 | 23.16 | 9.30 | 16.92 | 0.00 | 3.05 | 3.05 | 268.97 | TARP | TARP | 88.25 | 35.30 | 28.24 | 7.06 | 6 | 1 | 0 | Yes |
| 6 | G N2 APARTMENT | 0.0 | 23.16 | 9.30 | 0.00 | 28.95 | 13.11 | 1.52 | 1 | 1 | 1 | 23.16 | 34.75 | 9.30 | 16.92 | 0.00 | 3.05 | 3.05 | 268.97 | TARP | TARP | 88.25 | 35.30 | 28.24 | 7.06 | 6 | 1 | 0 | Yes |
| 7 | G S1 APARTMENT | 0.0 | 11.58 | 0.00 | 0.00 | 17.37 | 3.81 | 1.52 | 1 | 1 | 1 | 11.58 | 23.16 | 0.00 | 7.62 | 0.00 | 3.05 | 3.05 | 268.97 | TARP | TARP | 88.25 | 35.30 | 28.24 | 7.06 | 6 | 1 | 0 | Yes |
| 8 | G S2 APARTMENT | 0.0 | 23.16 | 0.00 | 0.00 | 28.95 | 3.81 | 1.52 | 1 | 1 | 1 | 23.16 | 34.75 | 0.00 | 7.62 | 0.00 | 3.05 | 3.05 | 268.97 | TARP | TARP | 88.25 | 35.30 | 28.24 | 7.06 | 6 | 1 | 0 | Yes |
| 9 | M SW APARTMENT | 0.0 | 0.00 | 0.00 | 3.05 | 5.79 | 3.81 | 4.57 | 1 | 1 | 2 | 0.00 | 11.58 | 0.00 | 7.62 | 3.05 | 6.10 | 3.05 | 268.97 | TARP | TARP | 88.25 | 58.52 | 46.82 | 11.71 | 6 | 2 | 0 | Yes |
| 10 | M NW APARTMENT | 0.0 | 0.00 | 9.30 | 3.05 | 5.79 | 13.11 | 4.57 | 1 | 1 | 2 | 0.00 | 11.58 | 9.30 | 16.92 | 3.05 | 6.10 | 3.05 | 268.97 | TARP | TARP | 88.25 | 58.52 | 46.82 | 11.71 | 6 | 2 | 0 | Yes |
| 11 | M SE APARTMENT | 0.0 | 34.75 | 0.00 | 3.05 | 40.54 | 3.81 | 4.57 | 1 | 1 | 2 | 34.75 | 46.33 | 0.00 | 7.62 | 3.05 | 6.10 | 3.05 | 268.97 | TARP | TARP | 88.25 | 58.52 | 46.82 | 11.71 | 6 | 2 | 0 | Yes |
| 12 | M NE APARTMENT | 0.0 | 34.75 | 9.30 | 3.05 | 40.54 | 13.11 | 4.57 | 1 | 1 | 2 | 34.75 | 46.33 | 9.30 | 16.92 | 3.05 | 6.10 | 3.05 | 268.97 | TARP | TARP | 88.25 | 58.52 | 46.82 | 11.71 | 6 | 2 | 0 | Yes |
| 13 | M N1 APARTMENT | 0.0 | 11.58 | 9.30 | 3.05 | 17.37 | 13.11 | 4.57 | 1 | 1 | 2 | 11.58 | 23.16 | 9.30 | 16.92 | 3.05 | 6.10 | 3.05 | 268.97 | TARP | TARP | 88.25 | 35.30 | 28.24 | 7.06 | 6 | 1 | 0 | Yes |
| 14 | M N2 APARTMENT | 0.0 | 23.16 | 9.30 | 3.05 | 28.95 | 13.11 | 4.57 | 1 | 1 | 2 | 23.16 | 34.75 | 9.30 | 16.92 | 3.05 | 6.10 | 3.05 | 268.97 | TARP | TARP | 88.25 | 35.30 | 28.24 | 7.06 | 6 | 1 | 0 | Yes |
| 15 | M S1 APARTMENT | 0.0 | 11.58 | 0.00 | 3.05 | 17.37 | 3.81 | 4.57 | 1 | 1 | 2 | 11.58 | 23.16 | 0.00 | 7.62 | 3.05 | 6.10 | 3.05 | 268.97 | TARP | TARP | 88.25 | 35.30 | 28.24 | 7.06 | 6 | 1 | 0 | Yes |
| 16 | M S2 APARTMENT | 0.0 | 23.16 | 0.00 | 3.05 | 28.95 | 3.81 | 4.57 | 1 | 1 | 2 | 23.16 | 34.75 | 0.00 | 7.62 | 3.05 | 6.10 | 3.05 | 268.97 | TARP | TARP | 88.25 | 35.30 | 28.24 | 7.06 | 6 | 1 | 0 | Yes |
| 17 | T SW APARTMENT | 0.0 | 0.00 | 0.00 | 9.14 | 5.79 | 3.81 | 10.67 | 1 | 1 | 1 | 0.00 | 11.58 | 0.00 | 7.62 | 9.14 | 12.19 | 3.05 | 268.97 | TARP | TARP | 88.25 | 58.52 | 46.82 | 11.71 | 6 | 2 | 0 | Yes |
| 18 | T NW APARTMENT | 0.0 | 0.00 | 9.30 | 9.14 | 5.79 | 13.11 | 10.67 | 1 | 1 | 1 | 0.00 | 11.58 | 9.30 | 16.92 | 9.14 | 12.19 | 3.05 | 268.97 | TARP | TARP | 88.25 | 58.52 | 46.82 | 11.71 | 6 | 2 | 0 | Yes |
| 19 | T SE APARTMENT | 0.0 | 34.75 | 0.00 | 9.14 | 40.54 | 3.81 | 10.67 | 1 | 1 | 1 | 34.75 | 46.33 | 0.00 | 7.62 | 9.14 | 12.19 | 3.05 | 268.97 | TARP | TARP | 88.25 | 58.52 | 46.82 | 11.71 | 6 | 2 | 0 | Yes |
| 20 | T NE APARTMENT | 0.0 | 34.75 | 9.30 | 9.14 | 40.54 | 13.11 | 10.67 | 1 | 1 | 1 | 34.75 | 46.33 | 9.30 | 16.92 | 9.14 | 12.19 | 3.05 | 268.97 | TARP | TARP | 88.25 | 58.52 | 46.82 | 11.71 | 6 | 2 | 0 | Yes |
| 21 | T N1 APARTMENT | 0.0 | 11.58 | 9.30 | 9.14 | 17.37 | 13.11 | 10.67 | 1 | 1 | 1 | 11.58 | 23.16 | 9.30 | 16.92 | 9.14 | 12.19 | 3.05 | 268.97 | TARP | TARP | 88.25 | 35.30 | 28.24 | 7.06 | 6 | 1 | 0 | Yes |
| 22 | T N2 APARTMENT | 0.0 | 23.16 | 9.30 | 9.14 | 28.95 | 13.11 | 10.67 | 1 | 1 | 1 | 23.16 | 34.75 | 9.30 | 16.92 | 9.14 | 12.19 | 3.05 | 268.97 | TARP | TARP | 88.25 | 35.30 | 28.24 | 7.06 | 6 | 1 | 0 | Yes |
| 23 | T S1 APARTMENT | 0.0 | 11.58 | 0.00 | 9.14 | 17.37 | 3.81 | 10.67 | 1 | 1 | 1 | 11.58 | 23.16 | 0.00 | 7.62 | 9.14 | 12.19 | 3.05 | 268.97 | TARP | TARP | 88.25 | 35.30 | 28.24 | 7.06 | 6 | 1 | 0 | Yes |
| 24 | T S2 APARTMENT | 0.0 | 23.16 | 0.00 | 9.14 | 28.95 | 3.81 | 10.67 | 1 | 1 | 1 | 23.16 | 34.75 | 0.00 | 7.62 | 9.14 | 12.19 | 3.05 | 268.97 | TARP | TARP | 88.25 | 35.30 | 28.24 | 7.06 | 6 | 1 | 0 | Yes |
| 25 | T CORRIDOR | 0.0 | 0.00 | 7.62 | 9.14 | 23.16 | 8.46 | 10.67 | 1 | 1 | 1 | 0.00 | 46.33 | 7.62 | 9.30 | 9.14 | 12.19 | 3.05 | 236.69 | TARP | TARP | 77.66 | 10.22 | 9.10 | 1.11 | 12 | 1 | 0 | Yes |
| 26 | G CORRIDOR | 0.0 | 0.00 | 7.62 | 0.00 | 23.16 | 8.46 | 1.52 | 1 | 1 | 1 | 0.00 | 46.33 | 7.62 | 9.30 | 0.00 | 3.05 | 3.05 | 236.69 | TARP | TARP | 77.66 | 10.22 | 6.90 | 3.32 | 12 | 1 | 0 | Yes |
| 27 | M CORRIDOR | 0.0 | 0.00 | 7.62 | 3.05 | 23.16 | 8.46 | 4.57 | 1 | 1 | 2 | 0.00 | 46.33 | 7.62 | 9.30 | 3.05 | 6.10 | 3.05 | 236.69 | TARP | TARP | 77.66 | 10.22 | 9.10 | 1.11 | 12 | 1 | 0 | Yes |
| Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
| 1 | G SW APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 2 | G NW APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 3 | OFFICE | 88.25 | 4.7 | 18.581 | 5.382E-002 | 9.753 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 16.423 | No |
| 4 | G NE APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 5 | G N1 APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 6 | G N2 APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 7 | G S1 APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 8 | G S2 APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 9 | M SW APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 10 | M NW APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 11 | M SE APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 12 | M NE APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 13 | M N1 APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 14 | M N2 APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 15 | M S1 APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 16 | M S2 APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 17 | T SW APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 18 | T NW APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 19 | T SE APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 20 | T NE APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 21 | T N1 APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 22 | T N2 APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 23 | T S1 APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 24 | T S2 APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 25 | T CORRIDOR | 77.66 | 4.2 | 18.579 | 5.382E-002 | 4.772 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 4.772 | No |
| 26 | G CORRIDOR | 77.66 | 4.2 | 18.579 | 5.382E-002 | 4.772 | 105.256 | 0.000 | 0.000 | 0.000 | 0.000 | 110.029 | No |
| 27 | M CORRIDOR | 77.66 | 4.2 | 18.579 | 5.382E-002 | 4.772 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 4.772 | No |
| Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | |
| 1 | OCCUP_GSW | OCC_APT_SCH_WORKING_FAMILY | G SW APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 3 |
| 2 | OCCUP_GNW | OCC_APT_SCH_STAY_HOME_FAMILY | G NW APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 1 | 3 |
| 3 | OCCUP_OFFICE | OCC_OFF_W_SB_SCH | OFFICE | 88.25 | 4.7 | 4.7 | 5.382E-002 | 18.581 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 5 |
| 4 | OCCUP_GNE | OCC_APT_SCH_STAY_HOME_FAMILY | G NE APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 1 | 3 |
| 5 | OCCUP_GN1 | OCC_APT_SCH_STAY_HOME_FAMILY | G N1 APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 1 | 3 |
| 6 | OCCUP_GN2 | OCC_APT_SCH_STAY_HOME_FAMILY | G N2 APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 1 | 3 |
| 7 | OCCUP_GS1 | OCC_APT_SCH_WORKING_FAMILY | G S1 APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 3 |
| 8 | OCCUP_GS2 | OCC_APT_SCH_WORKING_FAMILY | G S2 APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 3 |
| 9 | OCCUP_MSW | OCC_APT_SCH_WORKING_FAMILY | M SW APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 3 |
| 10 | OCCUP_MNW | OCC_APT_SCH_STAY_HOME_FAMILY | M NW APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 1 | 3 |
| 11 | OCCUP_MSE | OCC_APT_SCH_WORKING_FAMILY | M SE APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 3 |
| 12 | OCCUP_MNE | OCC_APT_SCH_STAY_HOME_FAMILY | M NE APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 1 | 3 |
| 13 | OCCUP_MN1 | OCC_APT_SCH_STAY_HOME_FAMILY | M N1 APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 1 | 3 |
| 14 | OCCUP_MN2 | OCC_APT_SCH_STAY_HOME_FAMILY | M N2 APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 1 | 3 |
| 15 | OCCUP_MS1 | OCC_APT_SCH_WORKING_FAMILY | M S1 APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 3 |
| 16 | OCCUP_MS2 | OCC_APT_SCH_WORKING_FAMILY | M S2 APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 3 |
| 17 | OCCUP_TSW | OCC_APT_SCH_WORKING_FAMILY | T SW APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 3 |
| 18 | OCCUP_TNW | OCC_APT_SCH_STAY_HOME_FAMILY | T NW APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 1 | 3 |
| 19 | OCCUP_TSE | OCC_APT_SCH_WORKING_FAMILY | T SE APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 3 |
| 20 | OCCUP_TNE | OCC_APT_SCH_STAY_HOME_FAMILY | T NE APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 1 | 3 |
| 21 | OCCUP_TN1 | OCC_APT_SCH_STAY_HOME_FAMILY | T N1 APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 1 | 3 |
| 22 | OCCUP_TN2 | OCC_APT_SCH_STAY_HOME_FAMILY | T N2 APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 1 | 3 |
| 23 | OCCUP_TS1 | OCC_APT_SCH_WORKING_FAMILY | T S1 APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 3 |
| 24 | OCCUP_TS2 | OCC_APT_SCH_WORKING_FAMILY | T S2 APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 3 |
| 25 | OCCUP_T CORRIDOR | OCC_APT_SCH_CORRIDOR | T CORRIDOR | 77.66 | 4.2 | 4.2 | 5.382E-002 | 18.579 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 1 | 4 |
| 26 | OCCUP_G CORRIDOR | OCC_APT_SCH_CORRIDOR | G CORRIDOR | 77.66 | 4.2 | 4.2 | 5.382E-002 | 18.579 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 1 | 4 |
| 27 | OCCUP_M CORRIDOR | OCC_APT_SCH_CORRIDOR | M CORRIDOR | 77.66 | 4.2 | 4.2 | 5.382E-002 | 18.579 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 1 | 4 |
| Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
| 1 | LIGHTING_HARDWIRED_GSW | LTG_SCH_APARTMENT_HARDWIRED | G SW APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 2 | LIGHTING_HARDWIRED_GNW | LTG_SCH_APARTMENT_HARDWIRED | G NW APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 3 | LIGHTING_HARDWIRED_OFFICE | LTG_SCH_OFFICE | OFFICE | 88.25 | 4.7 | 860.710 | 9.753 | 181.220 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 860.710 |
| 4 | LIGHTING_HARDWIRED_GNE | LTG_SCH_APARTMENT_HARDWIRED | G NE APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 5 | LIGHTING_HARDWIRED_GN1 | LTG_SCH_APARTMENT_HARDWIRED | G N1 APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 6 | LIGHTING_HARDWIRED_GN2 | LTG_SCH_APARTMENT_HARDWIRED | G N2 APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 7 | LIGHTING_HARDWIRED_GS1 | LTG_SCH_APARTMENT_HARDWIRED | G S1 APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 8 | LIGHTING_HARDWIRED_GS2 | LTG_SCH_APARTMENT_HARDWIRED | G S2 APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 9 | LIGHTING_HARDWIRED_MSW | LTG_SCH_APARTMENT_HARDWIRED | M SW APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 10 | LIGHTING_HARDWIRED_MNW | LTG_SCH_APARTMENT_HARDWIRED | M NW APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 11 | LIGHTING_HARDWIRED_MSE | LTG_SCH_APARTMENT_HARDWIRED | M SE APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 12 | LIGHTING_HARDWIRED_MNE | LTG_SCH_APARTMENT_HARDWIRED | M NE APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 13 | LIGHTING_HARDWIRED_MN1 | LTG_SCH_APARTMENT_HARDWIRED | M N1 APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 14 | LIGHTING_HARDWIRED_MN2 | LTG_SCH_APARTMENT_HARDWIRED | M N2 APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 15 | LIGHTING_HARDWIRED_MS1 | LTG_SCH_APARTMENT_HARDWIRED | M S1 APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 16 | LIGHTING_HARDWIRED_MS2 | LTG_SCH_APARTMENT_HARDWIRED | M S2 APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 17 | LIGHTING_HARDWIRED_TSW | LTG_SCH_APARTMENT_HARDWIRED | T SW APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 18 | LIGHTING_HARDWIRED_TNW | LTG_SCH_APARTMENT_HARDWIRED | T NW APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 19 | LIGHTING_HARDWIRED_TSE | LTG_SCH_APARTMENT_HARDWIRED | T SE APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 20 | LIGHTING_HARDWIRED_TNE | LTG_SCH_APARTMENT_HARDWIRED | T NE APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 21 | LIGHTING_HARDWIRED_TN1 | LTG_SCH_APARTMENT_HARDWIRED | T N1 APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 22 | LIGHTING_HARDWIRED_TN2 | LTG_SCH_APARTMENT_HARDWIRED | T N2 APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 23 | LIGHTING_HARDWIRED_TS1 | LTG_SCH_APARTMENT_HARDWIRED | T S1 APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 24 | LIGHTING_HARDWIRED_TS2 | LTG_SCH_APARTMENT_HARDWIRED | T S2 APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 25 | LIGHTING_HARDWIRED_GC | LTG_SCH_CORRIDOR | G CORRIDOR | 77.66 | 4.2 | 370.628 | 4.772 | 88.667 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 370.628 |
| 26 | LIGHTING_HARDWIRED_MC | LTG_SCH_CORRIDOR | M CORRIDOR | 77.66 | 4.2 | 370.628 | 4.772 | 88.667 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 370.628 |
| 27 | LIGHTING_HARDWIRED_TC | LTG_SCH_CORRIDOR | T CORRIDOR | 77.66 | 4.2 | 370.628 | 4.772 | 88.667 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 370.628 |
| 28 | LIGHTING_PLUGIN_GSW | LTG_SCH_APARTMENT_PLUGIN | G SW APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| 29 | LIGHTING_PLUGIN_GNW | LTG_SCH_APARTMENT_PLUGIN | G NW APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| 30 | LIGHTING_PLUGIN_GNE | LTG_SCH_APARTMENT_PLUGIN | G NE APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| 31 | LIGHTING_PLUGIN_GN1 | LTG_SCH_APARTMENT_PLUGIN | G N1 APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| 32 | LIGHTING_PLUGIN_GN2 | LTG_SCH_APARTMENT_PLUGIN | G N2 APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| 33 | LIGHTING_PLUGIN_GS1 | LTG_SCH_APARTMENT_PLUGIN | G S1 APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| 34 | LIGHTING_PLUGIN_GS2 | LTG_SCH_APARTMENT_PLUGIN | G S2 APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| 35 | LIGHTING_PLUGIN_MSW | LTG_SCH_APARTMENT_PLUGIN | M SW APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| 36 | LIGHTING_PLUGIN_MNW | LTG_SCH_APARTMENT_PLUGIN | M NW APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| 37 | LIGHTING_PLUGIN_MSE | LTG_SCH_APARTMENT_PLUGIN | M SE APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| 38 | LIGHTING_PLUGIN_MNE | LTG_SCH_APARTMENT_PLUGIN | M NE APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| 39 | LIGHTING_PLUGIN_MN1 | LTG_SCH_APARTMENT_PLUGIN | M N1 APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| 40 | LIGHTING_PLUGIN_MN2 | LTG_SCH_APARTMENT_PLUGIN | M N2 APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| 41 | LIGHTING_PLUGIN_MS1 | LTG_SCH_APARTMENT_PLUGIN | M S1 APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| 42 | LIGHTING_PLUGIN_MS2 | LTG_SCH_APARTMENT_PLUGIN | M S2 APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| 43 | LIGHTING_PLUGIN_TSW | LTG_SCH_APARTMENT_PLUGIN | T SW APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| 44 | LIGHTING_PLUGIN_TNW | LTG_SCH_APARTMENT_PLUGIN | T NW APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| 45 | LIGHTING_PLUGIN_TSE | LTG_SCH_APARTMENT_PLUGIN | T SE APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| 46 | LIGHTING_PLUGIN_TNE | LTG_SCH_APARTMENT_PLUGIN | T NE APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| 47 | LIGHTING_PLUGIN_TN1 | LTG_SCH_APARTMENT_PLUGIN | T N1 APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| 48 | LIGHTING_PLUGIN_TN2 | LTG_SCH_APARTMENT_PLUGIN | T N2 APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| 49 | LIGHTING_PLUGIN_TS1 | LTG_SCH_APARTMENT_PLUGIN | T S1 APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| 50 | LIGHTING_PLUGIN_TS2 | LTG_SCH_APARTMENT_PLUGIN | T S2 APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
| 1 | PLUG_GSW | EQP_APT_SCH | G SW APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 2 | PLUG_GNW | EQP_APT_SCH | G NW APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 3 | PLUG_OFFICE | EQP_OFF_SCH | OFFICE | 88.25 | 4.7 | 588.623 | 6.670 | 123.933 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 588.623 |
| 4 | PLUG_GNE | EQP_APT_SCH | G NE APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 5 | PLUG_GN1 | EQP_APT_SCH | G N1 APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 6 | PLUG_GN2 | EQP_APT_SCH | G N2 APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 7 | PLUG_GS1 | EQP_APT_SCH | G S1 APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 8 | PLUG_GS2 | EQP_APT_SCH | G S2 APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 9 | PLUG_MSW | EQP_APT_SCH | M SW APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 10 | PLUG_MNW | EQP_APT_SCH | M NW APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 11 | PLUG_MSE | EQP_APT_SCH | M SE APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 12 | PLUG_MNE | EQP_APT_SCH | M NE APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 13 | PLUG_MN1 | EQP_APT_SCH | M N1 APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 14 | PLUG_MN2 | EQP_APT_SCH | M N2 APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 15 | PLUG_MS1 | EQP_APT_SCH | M S1 APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 16 | PLUG_MS2 | EQP_APT_SCH | M S2 APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 17 | PLUG_TSW | EQP_APT_SCH | T SW APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 18 | PLUG_TNW | EQP_APT_SCH | T NW APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 19 | PLUG_TSE | EQP_APT_SCH | T SE APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 20 | PLUG_TNE | EQP_APT_SCH | T NE APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 21 | PLUG_TN1 | EQP_APT_SCH | T N1 APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 22 | PLUG_TN2 | EQP_APT_SCH | T N2 APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 23 | PLUG_TS1 | EQP_APT_SCH | T S1 APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 24 | PLUG_TS2 | EQP_APT_SCH | T S2 APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 25 | G CORRIDOR_ELEVATORS_EQUIP | BLDG_ELEVATORS | G CORRIDOR | 77.66 | 4.2 | 8012.150 | 103.170 | 1916.782 | 0.000 | 0.000 | 0.950 | 5.000E-002 | ElevatorLift | 961.458 | 4006.075 |
| 26 | ELEVATORS_LIGHTS_FAN | ELEV_LIGHT_FAN_SCH_24_7 | G CORRIDOR | 77.66 | 4.2 | 162.000 | 2.086 | 38.756 | 0.000 | 0.000 | 0.950 | 5.000E-002 | ElevatorLightsFan | 162.000 | 162.000 |
| Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
| 1 | PolygonClipping | Periodic | 20 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
| Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
| 1 | WaterHeater:Mixed | G SW APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.496 | 0.7729 |
| 2 | WaterHeater:Mixed | G NW APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.496 | 0.7729 |
| 3 | WaterHeater:Mixed | G NE APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.496 | 0.7729 |
| 4 | WaterHeater:Mixed | G N1 APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.496 | 0.7729 |
| 5 | WaterHeater:Mixed | G N2 APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.496 | 0.7729 |
| 6 | WaterHeater:Mixed | G S1 APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.496 | 0.7729 |
| 7 | WaterHeater:Mixed | G S2 APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.496 | 0.7729 |
| 8 | WaterHeater:Mixed | M SW APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.498 | 0.7911 |
| 9 | WaterHeater:Mixed | M NW APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.498 | 0.7911 |
| 10 | WaterHeater:Mixed | M SE APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.498 | 0.7911 |
| 11 | WaterHeater:Mixed | M NE APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.498 | 0.7911 |
| 12 | WaterHeater:Mixed | M N1 APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.498 | 0.7911 |
| 13 | WaterHeater:Mixed | M N2 APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.498 | 0.7911 |
| 14 | WaterHeater:Mixed | M S1 APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.498 | 0.7911 |
| 15 | WaterHeater:Mixed | M S2 APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.498 | 0.7911 |
| 16 | WaterHeater:Mixed | T SW APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.496 | 0.7729 |
| 17 | WaterHeater:Mixed | T NW APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.496 | 0.7729 |
| 18 | WaterHeater:Mixed | T SE APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.496 | 0.7729 |
| 19 | WaterHeater:Mixed | T NE APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.496 | 0.7729 |
| 20 | WaterHeater:Mixed | T N1 APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.496 | 0.7729 |
| 21 | WaterHeater:Mixed | T N2 APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.496 | 0.7729 |
| 22 | WaterHeater:Mixed | T S1 APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.496 | 0.7729 |
| 23 | WaterHeater:Mixed | T S2 APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.496 | 0.7729 |
| Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
| 1 | G SWALL SWA | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 2 | GWINDOW1 S SWA | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 3 | G WWALL SWA | 0 | 154.67 | 58.21 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 4 | GWINDOW1 W SWA | 0 | 154.67 | 58.21 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 5 | G NIWALL SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 6 | G EIWALL SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 7 | G GFLOOR SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 8 | G CEILIN SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 9 | G INTERNALMASS SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 10 | G NWALL NWA | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 11 | GWINDOW1 N NWA | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 12 | G WWALL NWA | 0 | 154.67 | 58.21 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 13 | GWINDOW1 W NWA | 0 | 154.67 | 58.21 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 14 | G SIWALL NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 15 | G EIWALL NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 16 | G GFLOOR NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 17 | G CEILIN NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 18 | G INTERNALMASS NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 19 | G SWALL SEA | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 20 | GWINDOW1 S SEA | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 21 | G EWALL SEA | 0 | 154.67 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 22 | GWINDOW1 E SEA | 0 | 154.67 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 23 | G NIWALL SEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 24 | iz-G EIWALL S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 25 | G GFLOOR SEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 26 | G CEILIN SEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 27 | G INTERNALMASS SEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 28 | G NWALL NEA | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 29 | GWINDOW1 N NEA | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 30 | G EWALL NEA | 0 | 154.67 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 31 | GWINDOW1 E NEA | 0 | 154.67 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 32 | G SIWALL NEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 33 | iz-G EIWALL N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 34 | G GFLOOR NEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 35 | G CEILIN NEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 36 | G INTERNALMASS NEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 37 | G NWALL N1A | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 3 | No | No |
| 38 | GWINDOW1 N N1A | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 2 | No | No |
| 39 | G SIWALL N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 40 | G EIWALL N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 41 | iz-G EIWALL NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 42 | G GFLOOR N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 43 | G CEILIN N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 44 | G INTERNALMASS N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 45 | G NWALL N2A | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 3 | No | No |
| 46 | GWINDOW1 N N2A | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 2 | No | No |
| 47 | G SIWALL N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 48 | G EIWALL N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 49 | iz-G EIWALL N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 50 | G GFLOOR N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 51 | G CEILIN N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 52 | G INTERNALMASS N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 53 | G SWALL S1A | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 3 | No | No |
| 54 | GWINDOW1 S S1A | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 2 | No | No |
| 55 | G NIWALL S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 56 | G EIWALL S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 57 | iz-G EIWALL SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 58 | G GFLOOR S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 59 | G CEILIN S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 60 | G INTERNALMASS S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 61 | G SWALL S2A | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 3 | No | No |
| 62 | GWINDOW1 S S2A | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 2 | No | No |
| 63 | G NIWALL S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 64 | G EIWALL S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 65 | iz-G EIWALL S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 66 | G GFLOOR S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 67 | G CEILIN S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 68 | G INTERNALMASS S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 69 | M WWALL SWA | 0 | 154.67 | 58.21 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 70 | MWINDOW1 W SWA | 0 | 154.67 | 58.21 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 71 | M SWALL SWA | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 72 | MWINDOW1 S SWA | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 73 | M NIWALL SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 74 | M EIWALL SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 75 | M GFLOOR SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 76 | M CEILIN SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 77 | M INTERNALMASS SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 78 | M NWALL NWA | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 79 | MWINDOW1 N NWA | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 80 | M WWALL NWA | 0 | 154.67 | 58.21 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 81 | MWINDOW1 W NWA | 0 | 154.67 | 58.21 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 82 | M SIWALL NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 83 | M EIWALL NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 84 | M GFLOOR NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 85 | M CEILIN NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 86 | M INTERNALMASS NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 87 | M EWALL SEA | 0 | 154.67 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 88 | MWINDOW1 E SEA | 0 | 154.67 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 89 | M SWALL SEA | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 90 | MWINDOW1 S SEA | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 91 | M NIWALL SEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 92 | iz-M EIWALL S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 93 | M GFLOOR SEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 94 | M CEILIN SEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 95 | M INTERNALMASS SEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 96 | M NWALL NEA | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 97 | MWINDOW1 N NEA | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 98 | M EWALL NEA | 0 | 154.67 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 99 | MWINDOW1 E NEA | 0 | 154.67 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 100 | M SIWALL NEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 101 | iz-M EIWALL N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 102 | M GFLOOR NEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 103 | M CEILIN NEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 104 | M INTERNALMASS NEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 105 | M NWALL N1A | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 3 | No | No |
| 106 | MWINDOW1 N N1A | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 2 | No | No |
| 107 | M SIWALL N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 108 | M EIWALL N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 109 | iz-M EIWALL NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 110 | M GFLOOR N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 111 | M CEILIN N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 112 | M INTERNALMASS N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 113 | M NWALL N2A | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 3 | No | No |
| 114 | MWINDOW1 N N2A | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 2 | No | No |
| 115 | M SIWALL N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 116 | M EIWALL N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 117 | iz-M EIWALL N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 118 | M GFLOOR N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 119 | M CEILIN N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 120 | M INTERNALMASS N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 121 | M SWALL S1A | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 3 | No | No |
| 122 | MWINDOW1 S S1A | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 2 | No | No |
| 123 | M NIWALL S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 124 | M EIWALL S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 125 | iz-M EIWALL SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 126 | M GFLOOR S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 127 | M CEILIN S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 128 | M INTERNALMASS S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 129 | M SWALL S2A | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 3 | No | No |
| 130 | MWINDOW1 S S2A | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 2 | No | No |
| 131 | M NIWALL S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 132 | M EIWALL S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 133 | iz-M EIWALL S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 134 | M GFLOOR S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 135 | M CEILIN S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 136 | M INTERNALMASS S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 137 | T WWALL SWA | 0 | 154.67 | 58.21 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 138 | TWINDOW1 W SWA | 0 | 154.67 | 58.21 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 139 | T SWALL SWA | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 140 | TWINDOW1 S SWA | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 141 | T NIWALL SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 142 | T EIWALL SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 143 | T GFLOOR SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 144 | T ROOF SWA | 0 | 783.65 | 155.90 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 145 | T INTERNALMASS SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 146 | T NWALL NWA | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 147 | TWINDOW1 N NWA | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 148 | T WWALL NWA | 0 | 154.67 | 58.21 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 149 | TWINDOW1 W NWA | 0 | 154.67 | 58.21 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 150 | T SIWALL NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 151 | T EIWALL NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 152 | T GFLOOR NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 153 | T ROOF NWA | 0 | 783.65 | 155.90 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 154 | T INTERNALMASS NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 155 | T EWALL SEA | 0 | 154.67 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 156 | TWINDOW1 E SEA | 0 | 154.67 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 157 | T SWALL SEA | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 158 | TWINDOW1 S SEA | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 159 | T NIWALL SEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 160 | iz-T EIWALL S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 161 | T GFLOOR SEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 162 | T ROOF SEA | 0 | 783.65 | 155.90 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 163 | T INTERNALMASS SEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 164 | T NWALL NEA | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 165 | TWINDOW1 N NEA | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 166 | T EWALL NEA | 0 | 154.67 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 167 | TWINDOW1 E NEA | 0 | 154.67 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 168 | T SIWALL NEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 169 | iz-T EIWALL N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 170 | T GFLOOR NEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 171 | T ROOF NEA | 0 | 783.65 | 155.90 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 172 | T INTERNALMASS NEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 173 | T NWALL N1A | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 3 | No | No |
| 174 | TWINDOW1 N N1A | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 2 | No | No |
| 175 | T SIWALL N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 176 | T EIWALL N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 177 | iz-T EIWALL NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 178 | T GFLOOR N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 179 | T ROOF N1A | 0 | 783.65 | 155.90 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 180 | T INTERNALMASS N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 181 | T NWALL N2A | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 3 | No | No |
| 182 | TWINDOW1 N N2A | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 2 | No | No |
| 183 | T SIWALL N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 184 | T EIWALL N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 185 | iz-T EIWALL N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 186 | T GFLOOR N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 187 | T ROOF N2A | 0 | 783.65 | 155.90 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 188 | T INTERNALMASS N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 189 | T SWALL S1A | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 3 | No | No |
| 190 | TWINDOW1 S S1A | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 2 | No | No |
| 191 | T NIWALL S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 192 | T EIWALL S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 193 | iz-T EIWALL SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 194 | T GFLOOR S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 195 | T ROOF S1A | 0 | 783.65 | 155.90 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 196 | T INTERNALMASS S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 197 | T SWALL S2A | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 3 | No | No |
| 198 | TWINDOW1 S S2A | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 2 | No | No |
| 199 | T NIWALL S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 200 | T EIWALL S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 201 | iz-T EIWALL S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 202 | T GFLOOR S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 203 | T ROOF S2A | 0 | 783.65 | 155.90 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 204 | T INTERNALMASS S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 205 | T WWALL C | 0 | 154.67 | 58.21 | 12.19 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 3 | No | No |
| 206 | T EWALL C | 0 | 154.67 | 123.02 | 12.19 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 3 | No | No |
| 207 | TWINDOW14 | 0 | 154.67 | 123.02 | 12.19 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 2 | No | No |
| 208 | iz-T NIWALL SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 209 | iz-T NIWALL S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 210 | iz-T NIWALL S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 211 | iz-T NIWALL SEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 212 | iz-T SIWALL NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 213 | iz-T SIWALL N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 214 | iz-T SIWALL N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 215 | iz-T SIWALL NEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 216 | T FLOOR C | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 217 | T ROOF C | 0 | 783.65 | 155.90 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 218 | G WWALL C | 0 | 154.67 | 58.21 | 12.19 | 0 | 3.05 | 3.35 | 3.24 | 0.32 | 4 | No | No |
| 219 | G EWALL C | 0 | 154.67 | 123.02 | 12.19 | 0 | 3.05 | 3.35 | 3.24 | 0.32 | 4 | No | No |
| 220 | ENTRANCE DOOR | 0 | 154.67 | 123.02 | 12.19 | 0 | 3.05 | 3.35 | 3.24 | 0.32 | 1 | No | No |
| 221 | iz-G NIWALL SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.32 | 0 | No | No |
| 222 | iz-G NIWALL S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.32 | 0 | No | No |
| 223 | iz-G NIWALL S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.32 | 0 | No | No |
| 224 | iz-G NIWALL SEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.32 | 0 | No | No |
| 225 | iz-G SIWALL NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.32 | 0 | No | No |
| 226 | iz-G SIWALL N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.32 | 0 | No | No |
| 227 | iz-G SIWALL N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.32 | 0 | No | No |
| 228 | iz-G SIWALL NEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.32 | 0 | No | No |
| 229 | G FLOOR C | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.32 | 0 | No | No |
| 230 | G CEILING C | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.32 | 0 | No | No |
| 231 | M WWALL C | 0 | 154.67 | 58.21 | 12.19 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 4 | No | No |
| 232 | M EWALL C | 0 | 154.67 | 123.02 | 12.19 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 3 | No | No |
| 233 | MWINDOW14 | 0 | 154.67 | 123.02 | 12.19 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 2 | No | No |
| 234 | iz-M NIWALL SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 235 | iz-M NIWALL S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 236 | iz-M NIWALL S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 237 | iz-M NIWALL SEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 238 | iz-M SIWALL NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 239 | iz-M SIWALL N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 240 | iz-M SIWALL N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 241 | iz-M SIWALL NEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 242 | M FLOOR C | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 243 | M CEILING C | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
| 1 | INFIL_GSW | INF_APT_SCH | G SW APARTMENT | 88.25 | 2.5 | 6.000E-002 | 6.799E-004 | 1.025E-003 | 0.803 | 0.000 | 0.000 | 0.224 | 0.000 |
| 2 | INFIL_GNW | INF_APT_SCH | G NW APARTMENT | 88.25 | 2.5 | 6.000E-002 | 6.799E-004 | 1.025E-003 | 0.803 | 0.000 | 0.000 | 0.224 | 0.000 |
| 3 | INFIL_OFFICE | INF_OFF_SCH | OFFICE | 88.25 | 4.7 | 6.000E-002 | 6.799E-004 | 1.025E-003 | 0.803 | 0.000 | 0.000 | 0.224 | 0.000 |
| 4 | INFIL_GNE | INF_APT_SCH | G NE APARTMENT | 88.25 | 2.5 | 6.000E-002 | 6.799E-004 | 1.025E-003 | 0.803 | 0.000 | 0.000 | 0.224 | 0.000 |
| 5 | INFIL_GN1 | INF_APT_SCH | G N1 APARTMENT | 88.25 | 2.5 | 3.619E-002 | 4.101E-004 | 1.025E-003 | 0.484 | 0.000 | 0.000 | 0.224 | 0.000 |
| 6 | INFIL_GN2 | INF_APT_SCH | G N2 APARTMENT | 88.25 | 2.5 | 3.619E-002 | 4.101E-004 | 1.025E-003 | 0.484 | 0.000 | 0.000 | 0.224 | 0.000 |
| 7 | INFIL_GS1 | INF_APT_SCH | G S1 APARTMENT | 88.25 | 2.5 | 3.619E-002 | 4.101E-004 | 1.025E-003 | 0.484 | 0.000 | 0.000 | 0.224 | 0.000 |
| 8 | INFIL_GS2 | INF_APT_SCH | G S2 APARTMENT | 88.25 | 2.5 | 3.619E-002 | 4.101E-004 | 1.025E-003 | 0.484 | 0.000 | 0.000 | 0.224 | 0.000 |
| 9 | INFIL_MSW | INF_APT_SCH | M SW APARTMENT | 88.25 | 2.5 | 6.000E-002 | 6.799E-004 | 1.025E-003 | 0.803 | 0.000 | 0.000 | 0.224 | 0.000 |
| 10 | INFIL_MNW | INF_APT_SCH | M NW APARTMENT | 88.25 | 2.5 | 6.000E-002 | 6.799E-004 | 1.025E-003 | 0.803 | 0.000 | 0.000 | 0.224 | 0.000 |
| 11 | INFIL_MSE | INF_APT_SCH | M SE APARTMENT | 88.25 | 2.5 | 6.000E-002 | 6.799E-004 | 1.025E-003 | 0.803 | 0.000 | 0.000 | 0.224 | 0.000 |
| 12 | INFIL_MNE | INF_APT_SCH | M NE APARTMENT | 88.25 | 2.5 | 6.000E-002 | 6.799E-004 | 1.025E-003 | 0.803 | 0.000 | 0.000 | 0.224 | 0.000 |
| 13 | INFIL_MN1 | INF_APT_SCH | M N1 APARTMENT | 88.25 | 2.5 | 3.619E-002 | 4.101E-004 | 1.025E-003 | 0.484 | 0.000 | 0.000 | 0.224 | 0.000 |
| 14 | INFIL_MN2 | INF_APT_SCH | M N2 APARTMENT | 88.25 | 2.5 | 3.619E-002 | 4.101E-004 | 1.025E-003 | 0.484 | 0.000 | 0.000 | 0.224 | 0.000 |
| 15 | INFIL_MS1 | INF_APT_SCH | M S1 APARTMENT | 88.25 | 2.5 | 3.619E-002 | 4.101E-004 | 1.025E-003 | 0.484 | 0.000 | 0.000 | 0.224 | 0.000 |
| 16 | INFIL_MS2 | INF_APT_SCH | M S2 APARTMENT | 88.25 | 2.5 | 3.619E-002 | 4.101E-004 | 1.025E-003 | 0.484 | 0.000 | 0.000 | 0.224 | 0.000 |
| 17 | INFIL_SW | INF_APT_SCH | T SW APARTMENT | 88.25 | 2.5 | 6.000E-002 | 6.799E-004 | 4.088E-004 | 0.803 | 0.000 | 0.000 | 0.224 | 0.000 |
| 18 | INFIL_NW | INF_APT_SCH | T NW APARTMENT | 88.25 | 2.5 | 6.000E-002 | 6.799E-004 | 4.088E-004 | 0.803 | 0.000 | 0.000 | 0.224 | 0.000 |
| 19 | INFIL_SE | INF_APT_SCH | T SE APARTMENT | 88.25 | 2.5 | 6.000E-002 | 6.799E-004 | 4.088E-004 | 0.803 | 0.000 | 0.000 | 0.224 | 0.000 |
| 20 | INFIL_NE | INF_APT_SCH | T NE APARTMENT | 88.25 | 2.5 | 6.000E-002 | 6.799E-004 | 4.088E-004 | 0.803 | 0.000 | 0.000 | 0.224 | 0.000 |
| 21 | INFIL_TN1 | INF_APT_SCH | T N1 APARTMENT | 88.25 | 2.5 | 3.619E-002 | 4.101E-004 | 2.929E-004 | 0.484 | 0.000 | 0.000 | 0.224 | 0.000 |
| 22 | INFIL_TN2 | INF_APT_SCH | T N2 APARTMENT | 88.25 | 2.5 | 3.619E-002 | 4.101E-004 | 2.929E-004 | 0.484 | 0.000 | 0.000 | 0.224 | 0.000 |
| 23 | INFIL_TS1 | INF_APT_SCH | T S1 APARTMENT | 88.25 | 2.5 | 3.619E-002 | 4.101E-004 | 2.929E-004 | 0.484 | 0.000 | 0.000 | 0.224 | 0.000 |
| 24 | INFIL_TS2 | INF_APT_SCH | T S2 APARTMENT | 88.25 | 2.5 | 3.619E-002 | 4.101E-004 | 2.929E-004 | 0.484 | 0.000 | 0.000 | 0.224 | 0.000 |
| 25 | INFIL_GC | INF_COR_SCH | G CORRIDOR | 77.66 | 4.2 | 1.048E-002 | 1.349E-004 | 1.025E-003 | 0.159 | 0.000 | 0.000 | 0.224 | 0.000 |
| 26 | DOOR_INFIL_GC | INFIL_DOOR_OPENING_SCH | G CORRIDOR | 77.66 | 4.2 | 0.521 | 6.703E-003 | 5.094E-002 | 7.917 | 1.000 | 0.000 | 0.000 | 0.000 |
| 27 | INFIL_MC | INF_COR_SCH | M CORRIDOR | 77.66 | 4.2 | 1.048E-002 | 1.349E-004 | 1.025E-003 | 0.159 | 0.000 | 0.000 | 0.224 | 0.000 |
| 28 | INFIL_TC | INF_COR_SCH | T CORRIDOR | 77.66 | 4.2 | 1.048E-002 | 1.349E-004 | 1.192E-004 | 0.159 | 0.000 | 0.000 | 0.224 | 0.000 |
| Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
| 1 | G SW APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | G SW APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 2 | G NW APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | G NW APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 3 | G NE APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | G NE APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 4 | G N1 APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | G N1 APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 5 | G N2 APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | G N2 APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 6 | G S1 APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | G S1 APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 7 | G S2 APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | G S2 APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 8 | M SW APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | M SW APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 9 | M NW APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | M NW APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 10 | M SE APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | M SE APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 11 | M NE APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | M NE APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 12 | M N1 APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | M N1 APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 13 | M N2 APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | M N2 APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 14 | M S1 APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | M S1 APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 15 | M S2 APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | M S2 APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 16 | T SW APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | T SW APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 17 | T NW APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | T NW APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 18 | T SE APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | T SE APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 19 | T NE APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | T NE APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 20 | T N1 APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | T N1 APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 21 | T N2 APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | T N2 APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 22 | T S1 APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | T S1 APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 23 | T S2 APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | T S2 APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| Simple | |
| 1 | Simple |
| Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
| 1 | G SW APARTMENT | Mixing/Well-Stirred |
| 2 | G NW APARTMENT | Mixing/Well-Stirred |
| 3 | OFFICE | Mixing/Well-Stirred |
| 4 | G NE APARTMENT | Mixing/Well-Stirred |
| 5 | G N1 APARTMENT | Mixing/Well-Stirred |
| 6 | G N2 APARTMENT | Mixing/Well-Stirred |
| 7 | G S1 APARTMENT | Mixing/Well-Stirred |
| 8 | G S2 APARTMENT | Mixing/Well-Stirred |
| 9 | M SW APARTMENT | Mixing/Well-Stirred |
| 10 | M NW APARTMENT | Mixing/Well-Stirred |
| 11 | M SE APARTMENT | Mixing/Well-Stirred |
| 12 | M NE APARTMENT | Mixing/Well-Stirred |
| 13 | M N1 APARTMENT | Mixing/Well-Stirred |
| 14 | M N2 APARTMENT | Mixing/Well-Stirred |
| 15 | M S1 APARTMENT | Mixing/Well-Stirred |
| 16 | M S2 APARTMENT | Mixing/Well-Stirred |
| 17 | T SW APARTMENT | Mixing/Well-Stirred |
| 18 | T NW APARTMENT | Mixing/Well-Stirred |
| 19 | T SE APARTMENT | Mixing/Well-Stirred |
| 20 | T NE APARTMENT | Mixing/Well-Stirred |
| 21 | T N1 APARTMENT | Mixing/Well-Stirred |
| 22 | T N2 APARTMENT | Mixing/Well-Stirred |
| 23 | T S1 APARTMENT | Mixing/Well-Stirred |
| 24 | T S2 APARTMENT | Mixing/Well-Stirred |
| 25 | T CORRIDOR | Mixing/Well-Stirred |
| 26 | G CORRIDOR | Mixing/Well-Stirred |
| 27 | M CORRIDOR | Mixing/Well-Stirred |
| No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
| 1 | NoMultizoneOrDistribution |
| Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
| 1 | 1.000 | 1.000 | 1.000 | 1.000 |
| Value | |
| 1 | 6 |
| Sizing Factor ID | Value | |
| 1 | Global | 1.2000 |
| 2 | Zone G SW APARTMENT | 1.2000 |
| 3 | Zone G NW APARTMENT | 1.2000 |
| 4 | Zone OFFICE | 1.2000 |
| 5 | Zone G NE APARTMENT | 1.2000 |
| 6 | Zone G N1 APARTMENT | 1.2000 |
| 7 | Zone G N2 APARTMENT | 1.2000 |
| 8 | Zone G S1 APARTMENT | 1.2000 |
| 9 | Zone G S2 APARTMENT | 1.2000 |
| 10 | Zone M SW APARTMENT | 1.2000 |
| 11 | Zone M NW APARTMENT | 1.2000 |
| 12 | Zone M SE APARTMENT | 1.2000 |
| 13 | Zone M NE APARTMENT | 1.2000 |
| 14 | Zone M N1 APARTMENT | 1.2000 |
| 15 | Zone M N2 APARTMENT | 1.2000 |
| 16 | Zone M S1 APARTMENT | 1.2000 |
| 17 | Zone M S2 APARTMENT | 1.2000 |
| 18 | Zone T SW APARTMENT | 1.2000 |
| 19 | Zone T NW APARTMENT | 1.2000 |
| 20 | Zone T SE APARTMENT | 1.2000 |
| 21 | Zone T NE APARTMENT | 1.2000 |
| 22 | Zone T N1 APARTMENT | 1.2000 |
| 23 | Zone T N2 APARTMENT | 1.2000 |
| 24 | Zone T S1 APARTMENT | 1.2000 |
| 25 | Zone T S2 APARTMENT | 1.2000 |
| Sizing Factor ID | Value | |
| 1 | Global | 1.2000 |
| 2 | Zone G SW APARTMENT | 1.2000 |
| 3 | Zone G NW APARTMENT | 1.2000 |
| 4 | Zone OFFICE | 1.2000 |
| 5 | Zone G NE APARTMENT | 1.2000 |
| 6 | Zone G N1 APARTMENT | 1.2000 |
| 7 | Zone G N2 APARTMENT | 1.2000 |
| 8 | Zone G S1 APARTMENT | 1.2000 |
| 9 | Zone G S2 APARTMENT | 1.2000 |
| 10 | Zone M SW APARTMENT | 1.2000 |
| 11 | Zone M NW APARTMENT | 1.2000 |
| 12 | Zone M SE APARTMENT | 1.2000 |
| 13 | Zone M NE APARTMENT | 1.2000 |
| 14 | Zone M N1 APARTMENT | 1.2000 |
| 15 | Zone M N2 APARTMENT | 1.2000 |
| 16 | Zone M S1 APARTMENT | 1.2000 |
| 17 | Zone M S2 APARTMENT | 1.2000 |
| 18 | Zone T SW APARTMENT | 1.2000 |
| 19 | Zone T NW APARTMENT | 1.2000 |
| 20 | Zone T SE APARTMENT | 1.2000 |
| 21 | Zone T NE APARTMENT | 1.2000 |
| 22 | Zone T N1 APARTMENT | 1.2000 |
| 23 | Zone T N2 APARTMENT | 1.2000 |
| 24 | Zone T S1 APARTMENT | 1.2000 |
| 25 | Zone T S2 APARTMENT | 1.2000 |
| Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
| 1 | G SW APARTMENT | Cooling | 4094.26416 | 4913.11700 | 0.28943 | 0.34731 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 30.58700 | 1.71622E-002 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 2 | G SW APARTMENT | Heating | 578.26076 | 693.91292 | 2.49464E-002 | 2.99357E-002 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 8.70000 | 6.99286E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 3 | G NW APARTMENT | Cooling | 4149.67067 | 4979.60481 | 0.29345 | 0.35215 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 30.58700 | 1.71622E-002 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 4 | G NW APARTMENT | Heating | 459.59424 | 551.51309 | 1.98273E-002 | 2.59546E-002 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | 8.70000 | 6.99286E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 5 | OFFICE | Cooling | 4340.51597 | 5208.61916 | 0.31115 | 0.37338 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 29.51500 | 1.71602E-002 | 88.24927 | 4.74953 | 3.81060E-002 | 0.00000 |
| 6 | OFFICE | Heating | 943.89156 | 1132.66987 | 4.07200E-002 | 4.88640E-002 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 18:50:00 | 8.70000 | 6.99286E-003 | 88.24927 | 4.74953 | 3.81060E-002 | 0.00000 |
| 7 | G NE APARTMENT | Cooling | 3843.74695 | 4612.49634 | 0.27132 | 0.32558 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 30.58700 | 1.71622E-002 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 8 | G NE APARTMENT | Heating | 459.58656 | 551.50387 | 1.98270E-002 | 2.59546E-002 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | 8.70000 | 6.99286E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 9 | G N1 APARTMENT | Cooling | 3489.24358 | 4187.09230 | 0.24572 | 0.29486 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 30.58700 | 1.71622E-002 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 10 | G N1 APARTMENT | Heating | 162.05708 | 194.46849 | 6.99132E-003 | 2.59546E-002 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | 8.70000 | 6.99286E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 11 | G N2 APARTMENT | Cooling | 3483.43163 | 4180.11796 | 0.24530 | 0.29435 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 30.58700 | 1.71622E-002 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 12 | G N2 APARTMENT | Heating | 162.06752 | 194.48102 | 6.99177E-003 | 2.59546E-002 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | 8.70000 | 6.99286E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 13 | G S1 APARTMENT | Cooling | 3438.35732 | 4126.02878 | 0.24203 | 0.29044 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 30.58700 | 1.71622E-002 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 14 | G S1 APARTMENT | Heating | 279.54437 | 335.45325 | 1.20597E-002 | 2.59546E-002 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 8.70000 | 6.99286E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 15 | G S2 APARTMENT | Cooling | 3462.43325 | 4154.91990 | 0.24378 | 0.29254 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 30.58700 | 1.71622E-002 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 16 | G S2 APARTMENT | Heating | 288.19063 | 345.82876 | 1.24327E-002 | 2.59546E-002 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 8.70000 | 6.99286E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 17 | M SW APARTMENT | Cooling | 9356.00388 | 11227.20465 | 0.66355 | 0.79626 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 30.58700 | 1.71622E-002 | 88.24927 | 2.50000 | 5.19091E-002 | 0.00000 |
| 18 | M SW APARTMENT | Heating | 1425.85227 | 1711.02272 | 6.15116E-002 | 7.38139E-002 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 8.70000 | 6.99286E-003 | 88.24927 | 2.50000 | 5.19091E-002 | 0.00000 |
| 19 | M NW APARTMENT | Cooling | 9495.86007 | 11395.03208 | 0.67367 | 0.80840 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 30.58700 | 1.71622E-002 | 88.24927 | 2.50000 | 5.19091E-002 | 0.00000 |
| 20 | M NW APARTMENT | Heating | 1155.05505 | 1386.06606 | 4.98300E-002 | 5.97959E-002 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 8.70000 | 6.99286E-003 | 88.24927 | 2.50000 | 5.19091E-002 | 0.00000 |
| 21 | M SE APARTMENT | Cooling | 8552.81520 | 10263.37824 | 0.60536 | 0.72643 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 30.58700 | 1.71622E-002 | 88.24927 | 2.50000 | 5.19091E-002 | 0.00000 |
| 22 | M SE APARTMENT | Heating | 1425.90396 | 1711.08475 | 6.15138E-002 | 7.38166E-002 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 8.70000 | 6.99286E-003 | 88.24927 | 2.50000 | 5.19091E-002 | 0.00000 |
| 23 | M NE APARTMENT | Cooling | 8691.27254 | 10429.52705 | 0.61541 | 0.73849 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 30.58700 | 1.71622E-002 | 88.24927 | 2.50000 | 5.19091E-002 | 0.00000 |
| 24 | M NE APARTMENT | Heating | 1154.88906 | 1385.86688 | 4.98228E-002 | 5.97873E-002 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 8.70000 | 6.99286E-003 | 88.24927 | 2.50000 | 5.19091E-002 | 0.00000 |
| 25 | M N1 APARTMENT | Cooling | 7865.68115 | 9438.81738 | 0.55537 | 0.66644 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 30.58700 | 1.71622E-002 | 88.24927 | 2.50000 | 5.19091E-002 | 0.00000 |
| 26 | M N1 APARTMENT | Heating | 378.57690 | 454.29228 | 1.63322E-002 | 5.19091E-002 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 8.70000 | 6.99286E-003 | 88.24927 | 2.50000 | 5.19091E-002 | 0.00000 |
| 27 | M N2 APARTMENT | Cooling | 7851.31720 | 9421.58064 | 0.55434 | 0.66521 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 30.58700 | 1.71622E-002 | 88.24927 | 2.50000 | 5.19091E-002 | 0.00000 |
| 28 | M N2 APARTMENT | Heating | 378.59234 | 454.31081 | 1.63328E-002 | 5.19091E-002 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 8.70000 | 6.99286E-003 | 88.24927 | 2.50000 | 5.19091E-002 | 0.00000 |
| 29 | M S1 APARTMENT | Cooling | 7731.67161 | 9278.00593 | 0.54574 | 0.65488 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 30.58700 | 1.71622E-002 | 88.24927 | 2.50000 | 5.19091E-002 | 0.00000 |
| 30 | M S1 APARTMENT | Heating | 636.21000 | 763.45200 | 2.74464E-002 | 5.19091E-002 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 8.70000 | 6.99286E-003 | 88.24927 | 2.50000 | 5.19091E-002 | 0.00000 |
| 31 | M S2 APARTMENT | Cooling | 7717.21163 | 9260.65395 | 0.54470 | 0.65364 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 30.58700 | 1.71622E-002 | 88.24927 | 2.50000 | 5.19091E-002 | 0.00000 |
| 32 | M S2 APARTMENT | Heating | 636.23073 | 763.47687 | 2.74473E-002 | 5.19091E-002 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 8.70000 | 6.99286E-003 | 88.24927 | 2.50000 | 5.19091E-002 | 0.00000 |
| 33 | T SW APARTMENT | Cooling | 5227.06599 | 6272.47919 | 0.37116 | 0.44539 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 30.58700 | 1.71622E-002 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 34 | T SW APARTMENT | Heating | 1387.54657 | 1665.05588 | 5.98586E-002 | 7.18303E-002 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 8.70000 | 6.99286E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 35 | T NW APARTMENT | Cooling | 5357.99424 | 6429.59309 | 0.38066 | 0.45680 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 30.58700 | 1.71622E-002 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 36 | T NW APARTMENT | Heating | 1241.56066 | 1489.87279 | 5.35615E-002 | 6.42738E-002 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 8.70000 | 6.99286E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 37 | T SE APARTMENT | Cooling | 4621.25469 | 5545.50563 | 0.32751 | 0.39301 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 30.58700 | 1.71622E-002 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 38 | T SE APARTMENT | Heating | 1387.89853 | 1665.47823 | 5.98738E-002 | 7.18485E-002 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 8.70000 | 6.99286E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 39 | T NE APARTMENT | Cooling | 4750.39612 | 5700.47535 | 0.33684 | 0.40421 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 30.58700 | 1.71622E-002 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 40 | T NE APARTMENT | Heating | 1241.76627 | 1490.11952 | 5.35704E-002 | 6.42845E-002 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 8.70000 | 6.99286E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 41 | T N1 APARTMENT | Cooling | 4423.44201 | 5308.13041 | 0.31319 | 0.37582 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 30.58700 | 1.71622E-002 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 42 | T N1 APARTMENT | Heating | 782.52853 | 939.03424 | 3.37590E-002 | 4.05108E-002 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 8.70000 | 6.99286E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 43 | T N2 APARTMENT | Cooling | 4404.50461 | 5285.40553 | 0.31182 | 0.37418 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 30.58700 | 1.71622E-002 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 44 | T N2 APARTMENT | Heating | 782.54253 | 939.05103 | 3.37596E-002 | 4.05115E-002 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 8.70000 | 6.99286E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 45 | T S1 APARTMENT | Cooling | 4295.05938 | 5154.07125 | 0.30389 | 0.36467 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 30.58700 | 1.71622E-002 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 46 | T S1 APARTMENT | Heating | 929.18369 | 1115.02043 | 4.00852E-002 | 4.81023E-002 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 8.70000 | 6.99286E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 47 | T S2 APARTMENT | Cooling | 4276.20268 | 5131.44322 | 0.30253 | 0.36303 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 30.58700 | 1.71622E-002 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 48 | T S2 APARTMENT | Heating | 929.20155 | 1115.04186 | 4.00860E-002 | 4.81032E-002 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 8.70000 | 6.99286E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
| 1 | SPLIT GSW | Cooling | Sensible | 4923.64 | 0.34731 | 0.34731 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 2 | SPLIT GSW | Heating | Sensible | 1072.76 | 2.99357E-002 | 2.99357E-002 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 |
| 3 | SPLIT GNW | Cooling | Sensible | 4989.60 | 0.35215 | 0.35215 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 4 | SPLIT GNW | Heating | Sensible | 981.83 | 2.59546E-002 | 2.59546E-002 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
| 5 | SPLIT OFFICE | Cooling | Sensible | 5289.45 | 0.37338 | 0.37338 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 6 | SPLIT OFFICE | Heating | Sensible | 1687.24 | 4.88640E-002 | 4.88640E-002 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 18:50:00 |
| 7 | SPLIT GNE | Cooling | Sensible | 4626.41 | 0.32558 | 0.32558 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 8 | SPLIT GNE | Heating | Sensible | 981.83 | 2.59546E-002 | 2.59546E-002 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
| 9 | SPLIT GN1 | Cooling | Sensible | 4206.15 | 0.29486 | 0.29486 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 10 | SPLIT GN1 | Heating | Sensible | 981.83 | 2.59546E-002 | 2.59546E-002 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
| 11 | SPLIT GN2 | Cooling | Sensible | 4199.24 | 0.29435 | 0.29435 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 12 | SPLIT GN2 | Heating | Sensible | 981.83 | 2.59546E-002 | 2.59546E-002 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
| 13 | SPLIT GS1 | Cooling | Sensible | 4145.68 | 0.29044 | 0.29044 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 14 | SPLIT GS1 | Heating | Sensible | 981.83 | 2.59546E-002 | 2.59546E-002 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
| 15 | SPLIT GS2 | Cooling | Sensible | 4174.25 | 0.29254 | 0.29254 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 16 | SPLIT GS2 | Heating | Sensible | 981.83 | 2.59546E-002 | 2.59546E-002 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
| 17 | SPLIT MSW | Cooling | Sensible | 11235.03 | 0.79626 | 0.79626 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 18 | SPLIT MSW | Heating | Sensible | 2464.01 | 7.38139E-002 | 7.38139E-002 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 |
| 19 | SPLIT MNW | Cooling | Sensible | 11400.93 | 0.80840 | 0.80840 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 20 | SPLIT MNW | Heating | Sensible | 2143.80 | 5.97959E-002 | 5.97959E-002 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 |
| 21 | SPLIT MSE | Cooling | Sensible | 10281.05 | 0.72643 | 0.72643 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 22 | SPLIT MSE | Heating | Sensible | 2464.07 | 7.38166E-002 | 7.38166E-002 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 |
| 23 | SPLIT MNE | Cooling | Sensible | 10445.68 | 0.73849 | 0.73849 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 24 | SPLIT MNE | Heating | Sensible | 2143.61 | 5.97873E-002 | 5.97873E-002 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 |
| 25 | SPLIT MN1 | Cooling | Sensible | 9463.11 | 0.66644 | 0.66644 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 26 | SPLIT MN1 | Heating | Sensible | 1963.65 | 5.19091E-002 | 5.19091E-002 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
| 27 | SPLIT MN2 | Cooling | Sensible | 9446.15 | 0.66521 | 0.66521 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 28 | SPLIT MN2 | Heating | Sensible | 1963.65 | 5.19091E-002 | 5.19091E-002 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
| 29 | SPLIT MS1 | Cooling | Sensible | 9304.66 | 0.65488 | 0.65488 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 30 | SPLIT MS1 | Heating | Sensible | 1963.65 | 5.19091E-002 | 5.19091E-002 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
| 31 | SPLIT MS2 | Cooling | Sensible | 9287.57 | 0.65364 | 0.65364 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 32 | SPLIT MS2 | Heating | Sensible | 1963.65 | 5.19091E-002 | 5.19091E-002 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
| 33 | SPLIT TSW | Cooling | Sensible | 6265.85 | 0.44539 | 0.44539 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 34 | SPLIT TSW | Heating | Sensible | 2029.75 | 7.18303E-002 | 7.18303E-002 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 |
| 35 | SPLIT TNW | Cooling | Sensible | 6421.32 | 0.45680 | 0.45680 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 36 | SPLIT TNW | Heating | Sensible | 1857.13 | 6.42738E-002 | 6.42738E-002 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 |
| 37 | SPLIT TSE | Cooling | Sensible | 5549.35 | 0.39301 | 0.39301 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 38 | SPLIT TSE | Heating | Sensible | 2030.17 | 7.18485E-002 | 7.18485E-002 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 |
| 39 | SPLIT TNE | Cooling | Sensible | 5702.34 | 0.40421 | 0.40421 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 40 | SPLIT TNE | Heating | Sensible | 1857.37 | 6.42845E-002 | 6.42845E-002 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 |
| 41 | SPLIT TN1 | Cooling | Sensible | 5314.96 | 0.37582 | 0.37582 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 42 | SPLIT TN1 | Heating | Sensible | 1314.32 | 4.05108E-002 | 4.05108E-002 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 |
| 43 | SPLIT TN2 | Cooling | Sensible | 5292.50 | 0.37418 | 0.37418 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 44 | SPLIT TN2 | Heating | Sensible | 1314.34 | 4.05115E-002 | 4.05115E-002 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 |
| 45 | SPLIT TS1 | Cooling | Sensible | 5162.67 | 0.36467 | 0.36467 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 46 | SPLIT TS1 | Heating | Sensible | 1487.74 | 4.81023E-002 | 4.81023E-002 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 |
| 47 | SPLIT TS2 | Cooling | Sensible | 5140.30 | 0.36303 | 0.36303 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 48 | SPLIT TS2 | Heating | Sensible | 1487.76 | 4.81032E-002 | 4.81032E-002 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 |
| Component Type | Component Name | Input Field Description | Value | |
| 1 | ZoneHVAC:EnergyRecoveryVentilator | G SW APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 2 | ZoneHVAC:EnergyRecoveryVentilator | G SW APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 2.59546E-002 |
| 3 | Fan:OnOff | G SW APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 4 | Fan:OnOff | G SW APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 5 | HeatExchanger:AirToAir:SensibleAndLatent | G SW APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 6 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | G SW APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.34731 |
| 7 | ZoneHVAC:EnergyRecoveryVentilator | G NW APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 8 | ZoneHVAC:EnergyRecoveryVentilator | G NW APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 2.59546E-002 |
| 9 | Fan:OnOff | G NW APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 10 | Fan:OnOff | G NW APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 11 | HeatExchanger:AirToAir:SensibleAndLatent | G NW APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 12 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | G NW APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.35215 |
| 13 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | OFFICE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.37338 |
| 14 | ZoneHVAC:EnergyRecoveryVentilator | G NE APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 15 | ZoneHVAC:EnergyRecoveryVentilator | G NE APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 2.59546E-002 |
| 16 | Fan:OnOff | G NE APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 17 | Fan:OnOff | G NE APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 18 | HeatExchanger:AirToAir:SensibleAndLatent | G NE APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 19 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | G NE APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.32558 |
| 20 | ZoneHVAC:EnergyRecoveryVentilator | G N1 APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 21 | ZoneHVAC:EnergyRecoveryVentilator | G N1 APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 2.59546E-002 |
| 22 | Fan:OnOff | G N1 APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 23 | Fan:OnOff | G N1 APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 24 | HeatExchanger:AirToAir:SensibleAndLatent | G N1 APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 25 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | G N1 APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.29486 |
| 26 | ZoneHVAC:EnergyRecoveryVentilator | G N2 APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 27 | ZoneHVAC:EnergyRecoveryVentilator | G N2 APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 2.59546E-002 |
| 28 | Fan:OnOff | G N2 APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 29 | Fan:OnOff | G N2 APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 30 | HeatExchanger:AirToAir:SensibleAndLatent | G N2 APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 31 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | G N2 APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.29435 |
| 32 | ZoneHVAC:EnergyRecoveryVentilator | G S1 APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 33 | ZoneHVAC:EnergyRecoveryVentilator | G S1 APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 2.59546E-002 |
| 34 | Fan:OnOff | G S1 APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 35 | Fan:OnOff | G S1 APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 36 | HeatExchanger:AirToAir:SensibleAndLatent | G S1 APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 37 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | G S1 APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.29044 |
| 38 | ZoneHVAC:EnergyRecoveryVentilator | G S2 APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 39 | ZoneHVAC:EnergyRecoveryVentilator | G S2 APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 2.59546E-002 |
| 40 | Fan:OnOff | G S2 APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 41 | Fan:OnOff | G S2 APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 42 | HeatExchanger:AirToAir:SensibleAndLatent | G S2 APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 43 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | G S2 APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.29254 |
| 44 | ZoneHVAC:EnergyRecoveryVentilator | M SW APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 5.19091E-002 |
| 45 | ZoneHVAC:EnergyRecoveryVentilator | M SW APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 5.19091E-002 |
| 46 | Fan:OnOff | M SW APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 5.19091E-002 |
| 47 | Fan:OnOff | M SW APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 5.19091E-002 |
| 48 | HeatExchanger:AirToAir:SensibleAndLatent | M SW APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 5.19091E-002 |
| 49 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | M SW APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.79626 |
| 50 | ZoneHVAC:EnergyRecoveryVentilator | M NW APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 5.19091E-002 |
| 51 | ZoneHVAC:EnergyRecoveryVentilator | M NW APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 5.19091E-002 |
| 52 | Fan:OnOff | M NW APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 5.19091E-002 |
| 53 | Fan:OnOff | M NW APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 5.19091E-002 |
| 54 | HeatExchanger:AirToAir:SensibleAndLatent | M NW APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 5.19091E-002 |
| 55 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | M NW APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.80840 |
| 56 | ZoneHVAC:EnergyRecoveryVentilator | M SE APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 5.19091E-002 |
| 57 | ZoneHVAC:EnergyRecoveryVentilator | M SE APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 5.19091E-002 |
| 58 | Fan:OnOff | M SE APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 5.19091E-002 |
| 59 | Fan:OnOff | M SE APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 5.19091E-002 |
| 60 | HeatExchanger:AirToAir:SensibleAndLatent | M SE APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 5.19091E-002 |
| 61 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | M SE APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.72643 |
| 62 | ZoneHVAC:EnergyRecoveryVentilator | M NE APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 5.19091E-002 |
| 63 | ZoneHVAC:EnergyRecoveryVentilator | M NE APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 5.19091E-002 |
| 64 | Fan:OnOff | M NE APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 5.19091E-002 |
| 65 | Fan:OnOff | M NE APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 5.19091E-002 |
| 66 | HeatExchanger:AirToAir:SensibleAndLatent | M NE APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 5.19091E-002 |
| 67 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | M NE APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.73849 |
| 68 | ZoneHVAC:EnergyRecoveryVentilator | M N1 APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 5.19091E-002 |
| 69 | ZoneHVAC:EnergyRecoveryVentilator | M N1 APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 5.19091E-002 |
| 70 | Fan:OnOff | M N1 APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 5.19091E-002 |
| 71 | Fan:OnOff | M N1 APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 5.19091E-002 |
| 72 | HeatExchanger:AirToAir:SensibleAndLatent | M N1 APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 5.19091E-002 |
| 73 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | M N1 APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.66644 |
| 74 | ZoneHVAC:EnergyRecoveryVentilator | M N2 APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 5.19091E-002 |
| 75 | ZoneHVAC:EnergyRecoveryVentilator | M N2 APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 5.19091E-002 |
| 76 | Fan:OnOff | M N2 APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 5.19091E-002 |
| 77 | Fan:OnOff | M N2 APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 5.19091E-002 |
| 78 | HeatExchanger:AirToAir:SensibleAndLatent | M N2 APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 5.19091E-002 |
| 79 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | M N2 APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.66521 |
| 80 | ZoneHVAC:EnergyRecoveryVentilator | M S1 APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 5.19091E-002 |
| 81 | ZoneHVAC:EnergyRecoveryVentilator | M S1 APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 5.19091E-002 |
| 82 | Fan:OnOff | M S1 APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 5.19091E-002 |
| 83 | Fan:OnOff | M S1 APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 5.19091E-002 |
| 84 | HeatExchanger:AirToAir:SensibleAndLatent | M S1 APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 5.19091E-002 |
| 85 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | M S1 APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.65488 |
| 86 | ZoneHVAC:EnergyRecoveryVentilator | M S2 APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 5.19091E-002 |
| 87 | ZoneHVAC:EnergyRecoveryVentilator | M S2 APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 5.19091E-002 |
| 88 | Fan:OnOff | M S2 APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 5.19091E-002 |
| 89 | Fan:OnOff | M S2 APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 5.19091E-002 |
| 90 | HeatExchanger:AirToAir:SensibleAndLatent | M S2 APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 5.19091E-002 |
| 91 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | M S2 APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.65364 |
| 92 | ZoneHVAC:EnergyRecoveryVentilator | T SW APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 93 | ZoneHVAC:EnergyRecoveryVentilator | T SW APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 2.59546E-002 |
| 94 | Fan:OnOff | T SW APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 95 | Fan:OnOff | T SW APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 96 | HeatExchanger:AirToAir:SensibleAndLatent | T SW APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 97 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | T SW APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.44539 |
| 98 | ZoneHVAC:EnergyRecoveryVentilator | T NW APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 99 | ZoneHVAC:EnergyRecoveryVentilator | T NW APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 2.59546E-002 |
| 100 | Fan:OnOff | T NW APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 101 | Fan:OnOff | T NW APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 102 | HeatExchanger:AirToAir:SensibleAndLatent | T NW APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 103 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | T NW APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.45680 |
| 104 | ZoneHVAC:EnergyRecoveryVentilator | T SE APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 105 | ZoneHVAC:EnergyRecoveryVentilator | T SE APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 2.59546E-002 |
| 106 | Fan:OnOff | T SE APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 107 | Fan:OnOff | T SE APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 108 | HeatExchanger:AirToAir:SensibleAndLatent | T SE APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 109 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | T SE APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.39301 |
| 110 | ZoneHVAC:EnergyRecoveryVentilator | T NE APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 111 | ZoneHVAC:EnergyRecoveryVentilator | T NE APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 2.59546E-002 |
| 112 | Fan:OnOff | T NE APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 113 | Fan:OnOff | T NE APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 114 | HeatExchanger:AirToAir:SensibleAndLatent | T NE APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 115 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | T NE APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.40421 |
| 116 | ZoneHVAC:EnergyRecoveryVentilator | T N1 APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 117 | ZoneHVAC:EnergyRecoveryVentilator | T N1 APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 2.59546E-002 |
| 118 | Fan:OnOff | T N1 APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 119 | Fan:OnOff | T N1 APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 120 | HeatExchanger:AirToAir:SensibleAndLatent | T N1 APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 121 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | T N1 APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.37582 |
| 122 | ZoneHVAC:EnergyRecoveryVentilator | T N2 APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 123 | ZoneHVAC:EnergyRecoveryVentilator | T N2 APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 2.59546E-002 |
| 124 | Fan:OnOff | T N2 APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 125 | Fan:OnOff | T N2 APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 126 | HeatExchanger:AirToAir:SensibleAndLatent | T N2 APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 127 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | T N2 APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.37418 |
| 128 | ZoneHVAC:EnergyRecoveryVentilator | T S1 APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 129 | ZoneHVAC:EnergyRecoveryVentilator | T S1 APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 2.59546E-002 |
| 130 | Fan:OnOff | T S1 APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 131 | Fan:OnOff | T S1 APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 132 | HeatExchanger:AirToAir:SensibleAndLatent | T S1 APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 133 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | T S1 APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.36467 |
| 134 | ZoneHVAC:EnergyRecoveryVentilator | T S2 APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 135 | ZoneHVAC:EnergyRecoveryVentilator | T S2 APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 2.59546E-002 |
| 136 | Fan:OnOff | T S2 APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 137 | Fan:OnOff | T S2 APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 138 | HeatExchanger:AirToAir:SensibleAndLatent | T S2 APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 139 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | T S2 APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.36303 |
| 140 | AirLoopHVAC | SPLIT GSW | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.34731 |
| 141 | AirLoopHVAC | SPLIT GSW | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.34731 |
| 142 | AirLoopHVAC | SPLIT GSW | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.34731 |
| 143 | AirLoopHVAC | SPLIT GSW | Adjusted Heating Design Air Flow Rate [m3/s] | 0.34731 |
| 144 | AirLoopHVAC | SPLIT GSW | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.34731 |
| 145 | AirLoopHVAC | SPLIT GSW | Adjusted Main Design Air Flow Rate [m3/s] | 0.34731 |
| 146 | AirLoopHVAC | SPLIT GSW | User Heating Air Flow Ratio [] | 1.00000 |
| 147 | AirLoopHVAC | SPLIT GSW | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 148 | AirLoopHVAC | SPLIT GNW | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.35215 |
| 149 | AirLoopHVAC | SPLIT GNW | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.35215 |
| 150 | AirLoopHVAC | SPLIT GNW | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.35215 |
| 151 | AirLoopHVAC | SPLIT GNW | Adjusted Heating Design Air Flow Rate [m3/s] | 0.35215 |
| 152 | AirLoopHVAC | SPLIT GNW | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.35215 |
| 153 | AirLoopHVAC | SPLIT GNW | Adjusted Main Design Air Flow Rate [m3/s] | 0.35215 |
| 154 | AirLoopHVAC | SPLIT GNW | User Heating Air Flow Ratio [] | 1.00000 |
| 155 | AirLoopHVAC | SPLIT GNW | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 156 | AirLoopHVAC | SPLIT OFFICE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.37338 |
| 157 | AirLoopHVAC | SPLIT OFFICE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.37338 |
| 158 | AirLoopHVAC | SPLIT OFFICE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.37338 |
| 159 | AirLoopHVAC | SPLIT OFFICE | Adjusted Heating Design Air Flow Rate [m3/s] | 0.37338 |
| 160 | AirLoopHVAC | SPLIT OFFICE | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.37338 |
| 161 | AirLoopHVAC | SPLIT OFFICE | Adjusted Main Design Air Flow Rate [m3/s] | 0.37338 |
| 162 | AirLoopHVAC | SPLIT OFFICE | User Heating Air Flow Ratio [] | 1.00000 |
| 163 | AirLoopHVAC | SPLIT OFFICE | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 164 | AirLoopHVAC | SPLIT GNE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.32558 |
| 165 | AirLoopHVAC | SPLIT GNE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.32558 |
| 166 | AirLoopHVAC | SPLIT GNE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.32558 |
| 167 | AirLoopHVAC | SPLIT GNE | Adjusted Heating Design Air Flow Rate [m3/s] | 0.32558 |
| 168 | AirLoopHVAC | SPLIT GNE | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.32558 |
| 169 | AirLoopHVAC | SPLIT GNE | Adjusted Main Design Air Flow Rate [m3/s] | 0.32558 |
| 170 | AirLoopHVAC | SPLIT GNE | User Heating Air Flow Ratio [] | 1.00000 |
| 171 | AirLoopHVAC | SPLIT GNE | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 172 | AirLoopHVAC | SPLIT GN1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.29486 |
| 173 | AirLoopHVAC | SPLIT GN1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.29486 |
| 174 | AirLoopHVAC | SPLIT GN1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.29486 |
| 175 | AirLoopHVAC | SPLIT GN1 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.29486 |
| 176 | AirLoopHVAC | SPLIT GN1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.29486 |
| 177 | AirLoopHVAC | SPLIT GN1 | Adjusted Main Design Air Flow Rate [m3/s] | 0.29486 |
| 178 | AirLoopHVAC | SPLIT GN1 | User Heating Air Flow Ratio [] | 1.00000 |
| 179 | AirLoopHVAC | SPLIT GN1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 180 | AirLoopHVAC | SPLIT GN2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.29435 |
| 181 | AirLoopHVAC | SPLIT GN2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.29435 |
| 182 | AirLoopHVAC | SPLIT GN2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.29435 |
| 183 | AirLoopHVAC | SPLIT GN2 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.29435 |
| 184 | AirLoopHVAC | SPLIT GN2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.29435 |
| 185 | AirLoopHVAC | SPLIT GN2 | Adjusted Main Design Air Flow Rate [m3/s] | 0.29435 |
| 186 | AirLoopHVAC | SPLIT GN2 | User Heating Air Flow Ratio [] | 1.00000 |
| 187 | AirLoopHVAC | SPLIT GN2 | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 188 | AirLoopHVAC | SPLIT GS1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.29044 |
| 189 | AirLoopHVAC | SPLIT GS1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.29044 |
| 190 | AirLoopHVAC | SPLIT GS1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.29044 |
| 191 | AirLoopHVAC | SPLIT GS1 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.29044 |
| 192 | AirLoopHVAC | SPLIT GS1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.29044 |
| 193 | AirLoopHVAC | SPLIT GS1 | Adjusted Main Design Air Flow Rate [m3/s] | 0.29044 |
| 194 | AirLoopHVAC | SPLIT GS1 | User Heating Air Flow Ratio [] | 1.00000 |
| 195 | AirLoopHVAC | SPLIT GS1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 196 | AirLoopHVAC | SPLIT GS2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.29254 |
| 197 | AirLoopHVAC | SPLIT GS2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.29254 |
| 198 | AirLoopHVAC | SPLIT GS2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.29254 |
| 199 | AirLoopHVAC | SPLIT GS2 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.29254 |
| 200 | AirLoopHVAC | SPLIT GS2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.29254 |
| 201 | AirLoopHVAC | SPLIT GS2 | Adjusted Main Design Air Flow Rate [m3/s] | 0.29254 |
| 202 | AirLoopHVAC | SPLIT GS2 | User Heating Air Flow Ratio [] | 1.00000 |
| 203 | AirLoopHVAC | SPLIT GS2 | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 204 | AirLoopHVAC | SPLIT MSW | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.79626 |
| 205 | AirLoopHVAC | SPLIT MSW | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.79626 |
| 206 | AirLoopHVAC | SPLIT MSW | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.79626 |
| 207 | AirLoopHVAC | SPLIT MSW | Adjusted Heating Design Air Flow Rate [m3/s] | 0.79626 |
| 208 | AirLoopHVAC | SPLIT MSW | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.79626 |
| 209 | AirLoopHVAC | SPLIT MSW | Adjusted Main Design Air Flow Rate [m3/s] | 0.79626 |
| 210 | AirLoopHVAC | SPLIT MSW | User Heating Air Flow Ratio [] | 1.00000 |
| 211 | AirLoopHVAC | SPLIT MSW | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 212 | AirLoopHVAC | SPLIT MNW | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.80840 |
| 213 | AirLoopHVAC | SPLIT MNW | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.80840 |
| 214 | AirLoopHVAC | SPLIT MNW | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.80840 |
| 215 | AirLoopHVAC | SPLIT MNW | Adjusted Heating Design Air Flow Rate [m3/s] | 0.80840 |
| 216 | AirLoopHVAC | SPLIT MNW | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.80840 |
| 217 | AirLoopHVAC | SPLIT MNW | Adjusted Main Design Air Flow Rate [m3/s] | 0.80840 |
| 218 | AirLoopHVAC | SPLIT MNW | User Heating Air Flow Ratio [] | 1.00000 |
| 219 | AirLoopHVAC | SPLIT MNW | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 220 | AirLoopHVAC | SPLIT MSE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.72643 |
| 221 | AirLoopHVAC | SPLIT MSE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.72643 |
| 222 | AirLoopHVAC | SPLIT MSE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.72643 |
| 223 | AirLoopHVAC | SPLIT MSE | Adjusted Heating Design Air Flow Rate [m3/s] | 0.72643 |
| 224 | AirLoopHVAC | SPLIT MSE | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.72643 |
| 225 | AirLoopHVAC | SPLIT MSE | Adjusted Main Design Air Flow Rate [m3/s] | 0.72643 |
| 226 | AirLoopHVAC | SPLIT MSE | User Heating Air Flow Ratio [] | 1.00000 |
| 227 | AirLoopHVAC | SPLIT MSE | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 228 | AirLoopHVAC | SPLIT MNE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.73849 |
| 229 | AirLoopHVAC | SPLIT MNE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.73849 |
| 230 | AirLoopHVAC | SPLIT MNE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.73849 |
| 231 | AirLoopHVAC | SPLIT MNE | Adjusted Heating Design Air Flow Rate [m3/s] | 0.73849 |
| 232 | AirLoopHVAC | SPLIT MNE | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.73849 |
| 233 | AirLoopHVAC | SPLIT MNE | Adjusted Main Design Air Flow Rate [m3/s] | 0.73849 |
| 234 | AirLoopHVAC | SPLIT MNE | User Heating Air Flow Ratio [] | 1.00000 |
| 235 | AirLoopHVAC | SPLIT MNE | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 236 | AirLoopHVAC | SPLIT MN1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.66644 |
| 237 | AirLoopHVAC | SPLIT MN1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.66644 |
| 238 | AirLoopHVAC | SPLIT MN1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.66644 |
| 239 | AirLoopHVAC | SPLIT MN1 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.66644 |
| 240 | AirLoopHVAC | SPLIT MN1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.66644 |
| 241 | AirLoopHVAC | SPLIT MN1 | Adjusted Main Design Air Flow Rate [m3/s] | 0.66644 |
| 242 | AirLoopHVAC | SPLIT MN1 | User Heating Air Flow Ratio [] | 1.00000 |
| 243 | AirLoopHVAC | SPLIT MN1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 244 | AirLoopHVAC | SPLIT MN2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.66521 |
| 245 | AirLoopHVAC | SPLIT MN2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.66521 |
| 246 | AirLoopHVAC | SPLIT MN2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.66521 |
| 247 | AirLoopHVAC | SPLIT MN2 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.66521 |
| 248 | AirLoopHVAC | SPLIT MN2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.66521 |
| 249 | AirLoopHVAC | SPLIT MN2 | Adjusted Main Design Air Flow Rate [m3/s] | 0.66521 |
| 250 | AirLoopHVAC | SPLIT MN2 | User Heating Air Flow Ratio [] | 1.00000 |
| 251 | AirLoopHVAC | SPLIT MN2 | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 252 | AirLoopHVAC | SPLIT MS1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.65488 |
| 253 | AirLoopHVAC | SPLIT MS1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.65488 |
| 254 | AirLoopHVAC | SPLIT MS1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.65488 |
| 255 | AirLoopHVAC | SPLIT MS1 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.65488 |
| 256 | AirLoopHVAC | SPLIT MS1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.65488 |
| 257 | AirLoopHVAC | SPLIT MS1 | Adjusted Main Design Air Flow Rate [m3/s] | 0.65488 |
| 258 | AirLoopHVAC | SPLIT MS1 | User Heating Air Flow Ratio [] | 1.00000 |
| 259 | AirLoopHVAC | SPLIT MS1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 260 | AirLoopHVAC | SPLIT MS2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.65364 |
| 261 | AirLoopHVAC | SPLIT MS2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.65364 |
| 262 | AirLoopHVAC | SPLIT MS2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.65364 |
| 263 | AirLoopHVAC | SPLIT MS2 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.65364 |
| 264 | AirLoopHVAC | SPLIT MS2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.65364 |
| 265 | AirLoopHVAC | SPLIT MS2 | Adjusted Main Design Air Flow Rate [m3/s] | 0.65364 |
| 266 | AirLoopHVAC | SPLIT MS2 | User Heating Air Flow Ratio [] | 1.00000 |
| 267 | AirLoopHVAC | SPLIT MS2 | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 268 | AirLoopHVAC | SPLIT TSW | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.44539 |
| 269 | AirLoopHVAC | SPLIT TSW | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.44539 |
| 270 | AirLoopHVAC | SPLIT TSW | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.44539 |
| 271 | AirLoopHVAC | SPLIT TSW | Adjusted Heating Design Air Flow Rate [m3/s] | 0.44539 |
| 272 | AirLoopHVAC | SPLIT TSW | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.44539 |
| 273 | AirLoopHVAC | SPLIT TSW | Adjusted Main Design Air Flow Rate [m3/s] | 0.44539 |
| 274 | AirLoopHVAC | SPLIT TSW | User Heating Air Flow Ratio [] | 1.00000 |
| 275 | AirLoopHVAC | SPLIT TSW | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 276 | AirLoopHVAC | SPLIT TNW | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.45680 |
| 277 | AirLoopHVAC | SPLIT TNW | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.45680 |
| 278 | AirLoopHVAC | SPLIT TNW | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.45680 |
| 279 | AirLoopHVAC | SPLIT TNW | Adjusted Heating Design Air Flow Rate [m3/s] | 0.45680 |
| 280 | AirLoopHVAC | SPLIT TNW | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.45680 |
| 281 | AirLoopHVAC | SPLIT TNW | Adjusted Main Design Air Flow Rate [m3/s] | 0.45680 |
| 282 | AirLoopHVAC | SPLIT TNW | User Heating Air Flow Ratio [] | 1.00000 |
| 283 | AirLoopHVAC | SPLIT TNW | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 284 | AirLoopHVAC | SPLIT TSE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.39301 |
| 285 | AirLoopHVAC | SPLIT TSE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.39301 |
| 286 | AirLoopHVAC | SPLIT TSE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.39301 |
| 287 | AirLoopHVAC | SPLIT TSE | Adjusted Heating Design Air Flow Rate [m3/s] | 0.39301 |
| 288 | AirLoopHVAC | SPLIT TSE | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.39301 |
| 289 | AirLoopHVAC | SPLIT TSE | Adjusted Main Design Air Flow Rate [m3/s] | 0.39301 |
| 290 | AirLoopHVAC | SPLIT TSE | User Heating Air Flow Ratio [] | 1.00000 |
| 291 | AirLoopHVAC | SPLIT TSE | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 292 | AirLoopHVAC | SPLIT TNE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.40421 |
| 293 | AirLoopHVAC | SPLIT TNE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.40421 |
| 294 | AirLoopHVAC | SPLIT TNE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.40421 |
| 295 | AirLoopHVAC | SPLIT TNE | Adjusted Heating Design Air Flow Rate [m3/s] | 0.40421 |
| 296 | AirLoopHVAC | SPLIT TNE | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.40421 |
| 297 | AirLoopHVAC | SPLIT TNE | Adjusted Main Design Air Flow Rate [m3/s] | 0.40421 |
| 298 | AirLoopHVAC | SPLIT TNE | User Heating Air Flow Ratio [] | 1.00000 |
| 299 | AirLoopHVAC | SPLIT TNE | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 300 | AirLoopHVAC | SPLIT TN1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.37582 |
| 301 | AirLoopHVAC | SPLIT TN1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.37582 |
| 302 | AirLoopHVAC | SPLIT TN1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.37582 |
| 303 | AirLoopHVAC | SPLIT TN1 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.37582 |
| 304 | AirLoopHVAC | SPLIT TN1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.37582 |
| 305 | AirLoopHVAC | SPLIT TN1 | Adjusted Main Design Air Flow Rate [m3/s] | 0.37582 |
| 306 | AirLoopHVAC | SPLIT TN1 | User Heating Air Flow Ratio [] | 1.00000 |
| 307 | AirLoopHVAC | SPLIT TN1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 308 | AirLoopHVAC | SPLIT TN2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.37418 |
| 309 | AirLoopHVAC | SPLIT TN2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.37418 |
| 310 | AirLoopHVAC | SPLIT TN2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.37418 |
| 311 | AirLoopHVAC | SPLIT TN2 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.37418 |
| 312 | AirLoopHVAC | SPLIT TN2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.37418 |
| 313 | AirLoopHVAC | SPLIT TN2 | Adjusted Main Design Air Flow Rate [m3/s] | 0.37418 |
| 314 | AirLoopHVAC | SPLIT TN2 | User Heating Air Flow Ratio [] | 1.00000 |
| 315 | AirLoopHVAC | SPLIT TN2 | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 316 | AirLoopHVAC | SPLIT TS1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.36467 |
| 317 | AirLoopHVAC | SPLIT TS1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.36467 |
| 318 | AirLoopHVAC | SPLIT TS1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.36467 |
| 319 | AirLoopHVAC | SPLIT TS1 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.36467 |
| 320 | AirLoopHVAC | SPLIT TS1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.36467 |
| 321 | AirLoopHVAC | SPLIT TS1 | Adjusted Main Design Air Flow Rate [m3/s] | 0.36467 |
| 322 | AirLoopHVAC | SPLIT TS1 | User Heating Air Flow Ratio [] | 1.00000 |
| 323 | AirLoopHVAC | SPLIT TS1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 324 | AirLoopHVAC | SPLIT TS2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.36303 |
| 325 | AirLoopHVAC | SPLIT TS2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.36303 |
| 326 | AirLoopHVAC | SPLIT TS2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.36303 |
| 327 | AirLoopHVAC | SPLIT TS2 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.36303 |
| 328 | AirLoopHVAC | SPLIT TS2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.36303 |
| 329 | AirLoopHVAC | SPLIT TS2 | Adjusted Main Design Air Flow Rate [m3/s] | 0.36303 |
| 330 | AirLoopHVAC | SPLIT TS2 | User Heating Air Flow Ratio [] | 1.00000 |
| 331 | AirLoopHVAC | SPLIT TS2 | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 332 | AirLoopHVAC | SPLIT GSW | Design Supply Air Flow Rate [m3/s] | 0.34731 |
| 333 | AirLoopHVAC | SPLIT GNW | Design Supply Air Flow Rate [m3/s] | 0.35215 |
| 334 | AirLoopHVAC | SPLIT OFFICE | Design Supply Air Flow Rate [m3/s] | 0.37338 |
| 335 | AirLoopHVAC | SPLIT GNE | Design Supply Air Flow Rate [m3/s] | 0.32558 |
| 336 | AirLoopHVAC | SPLIT GN1 | Design Supply Air Flow Rate [m3/s] | 0.29486 |
| 337 | AirLoopHVAC | SPLIT GN2 | Design Supply Air Flow Rate [m3/s] | 0.29435 |
| 338 | AirLoopHVAC | SPLIT GS1 | Design Supply Air Flow Rate [m3/s] | 0.29044 |
| 339 | AirLoopHVAC | SPLIT GS2 | Design Supply Air Flow Rate [m3/s] | 0.29254 |
| 340 | AirLoopHVAC | SPLIT MSW | Design Supply Air Flow Rate [m3/s] | 0.79626 |
| 341 | AirLoopHVAC | SPLIT MNW | Design Supply Air Flow Rate [m3/s] | 0.80840 |
| 342 | AirLoopHVAC | SPLIT MSE | Design Supply Air Flow Rate [m3/s] | 0.72643 |
| 343 | AirLoopHVAC | SPLIT MNE | Design Supply Air Flow Rate [m3/s] | 0.73849 |
| 344 | AirLoopHVAC | SPLIT MN1 | Design Supply Air Flow Rate [m3/s] | 0.66644 |
| 345 | AirLoopHVAC | SPLIT MN2 | Design Supply Air Flow Rate [m3/s] | 0.66521 |
| 346 | AirLoopHVAC | SPLIT MS1 | Design Supply Air Flow Rate [m3/s] | 0.65488 |
| 347 | AirLoopHVAC | SPLIT MS2 | Design Supply Air Flow Rate [m3/s] | 0.65364 |
| 348 | AirLoopHVAC | SPLIT TSW | Design Supply Air Flow Rate [m3/s] | 0.44539 |
| 349 | AirLoopHVAC | SPLIT TNW | Design Supply Air Flow Rate [m3/s] | 0.45680 |
| 350 | AirLoopHVAC | SPLIT TSE | Design Supply Air Flow Rate [m3/s] | 0.39301 |
| 351 | AirLoopHVAC | SPLIT TNE | Design Supply Air Flow Rate [m3/s] | 0.40421 |
| 352 | AirLoopHVAC | SPLIT TN1 | Design Supply Air Flow Rate [m3/s] | 0.37582 |
| 353 | AirLoopHVAC | SPLIT TN2 | Design Supply Air Flow Rate [m3/s] | 0.37418 |
| 354 | AirLoopHVAC | SPLIT TS1 | Design Supply Air Flow Rate [m3/s] | 0.36467 |
| 355 | AirLoopHVAC | SPLIT TS2 | Design Supply Air Flow Rate [m3/s] | 0.36303 |
| 356 | Controller:OutdoorAir | SPLIT GSW_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.34731 |
| 357 | Controller:OutdoorAir | SPLIT GSW_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.59546E-002 |
| 358 | AirLoopHVAC:UnitarySystem | SPLIT GSW_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.34731 |
| 359 | AirLoopHVAC:UnitarySystem | SPLIT GSW_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.34731 |
| 360 | AirLoopHVAC:UnitarySystem | SPLIT GSW_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.34731 |
| 361 | AirLoopHVAC:UnitarySystem | SPLIT GSW_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.34731 |
| 362 | AirLoopHVAC:UnitarySystem | SPLIT GSW_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 6608.03199 |
| 363 | AirLoopHVAC:UnitarySystem | SPLIT GSW_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 8322.47218 |
| 364 | AirLoopHVAC:UnitarySystem | SPLIT GSW_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 365 | AirLoopHVAC:UnitarySystem | SPLIT GSW_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 366 | Fan:OnOff | SPLIT GSW SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.34731 |
| 367 | Coil:Cooling:DX:SingleSpeed | SPLIT GSW COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.34731 |
| 368 | Coil:Cooling:DX:SingleSpeed | SPLIT GSW COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 6608.03199 |
| 369 | Coil:Cooling:DX:SingleSpeed | SPLIT GSW COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.79688 |
| 370 | Coil:Heating:Fuel | SPLIT GSW HEATING COIL | Design Size Nominal Capacity [W] | 8322.47218 |
| 371 | Controller:OutdoorAir | SPLIT GNW_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.35215 |
| 372 | Controller:OutdoorAir | SPLIT GNW_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.59546E-002 |
| 373 | AirLoopHVAC:UnitarySystem | SPLIT GNW_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.35215 |
| 374 | AirLoopHVAC:UnitarySystem | SPLIT GNW_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.35215 |
| 375 | AirLoopHVAC:UnitarySystem | SPLIT GNW_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.35215 |
| 376 | AirLoopHVAC:UnitarySystem | SPLIT GNW_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.35215 |
| 377 | AirLoopHVAC:UnitarySystem | SPLIT GNW_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 6661.48820 |
| 378 | AirLoopHVAC:UnitarySystem | SPLIT GNW_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 8432.74442 |
| 379 | AirLoopHVAC:UnitarySystem | SPLIT GNW_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 380 | AirLoopHVAC:UnitarySystem | SPLIT GNW_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 381 | Fan:OnOff | SPLIT GNW SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.35215 |
| 382 | Coil:Cooling:DX:SingleSpeed | SPLIT GNW COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.35215 |
| 383 | Coil:Cooling:DX:SingleSpeed | SPLIT GNW COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 6661.48820 |
| 384 | Coil:Cooling:DX:SingleSpeed | SPLIT GNW COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.79872 |
| 385 | Coil:Heating:Fuel | SPLIT GNW HEATING COIL | Design Size Nominal Capacity [W] | 8432.74442 |
| 386 | Controller:OutdoorAir | SPLIT OFFICE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.37338 |
| 387 | Controller:OutdoorAir | SPLIT OFFICE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 3.81060E-002 |
| 388 | AirLoopHVAC:UnitarySystem | SPLIT OFFICE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.37338 |
| 389 | AirLoopHVAC:UnitarySystem | SPLIT OFFICE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.37338 |
| 390 | AirLoopHVAC:UnitarySystem | SPLIT OFFICE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.37338 |
| 391 | AirLoopHVAC:UnitarySystem | SPLIT OFFICE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.37338 |
| 392 | AirLoopHVAC:UnitarySystem | SPLIT OFFICE_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 7123.34200 |
| 393 | AirLoopHVAC:UnitarySystem | SPLIT OFFICE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 9100.03755 |
| 394 | AirLoopHVAC:UnitarySystem | SPLIT OFFICE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 395 | AirLoopHVAC:UnitarySystem | SPLIT OFFICE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 396 | Fan:OnOff | SPLIT OFFICE SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.37338 |
| 397 | Coil:Cooling:DX:SingleSpeed | SPLIT OFFICE COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.37338 |
| 398 | Coil:Cooling:DX:SingleSpeed | SPLIT OFFICE COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 7123.34200 |
| 399 | Coil:Cooling:DX:SingleSpeed | SPLIT OFFICE COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.79501 |
| 400 | Coil:Heating:Fuel | SPLIT OFFICE HEATING COIL | Design Size Nominal Capacity [W] | 9100.03755 |
| 401 | Controller:OutdoorAir | SPLIT GNE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.32558 |
| 402 | Controller:OutdoorAir | SPLIT GNE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.59546E-002 |
| 403 | AirLoopHVAC:UnitarySystem | SPLIT GNE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.32558 |
| 404 | AirLoopHVAC:UnitarySystem | SPLIT GNE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.32558 |
| 405 | AirLoopHVAC:UnitarySystem | SPLIT GNE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.32558 |
| 406 | AirLoopHVAC:UnitarySystem | SPLIT GNE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.32558 |
| 407 | AirLoopHVAC:UnitarySystem | SPLIT GNE_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 6270.11549 |
| 408 | AirLoopHVAC:UnitarySystem | SPLIT GNE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 7825.97520 |
| 409 | AirLoopHVAC:UnitarySystem | SPLIT GNE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 410 | AirLoopHVAC:UnitarySystem | SPLIT GNE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 411 | Fan:OnOff | SPLIT GNE SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.32558 |
| 412 | Coil:Cooling:DX:SingleSpeed | SPLIT GNE COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.32558 |
| 413 | Coil:Cooling:DX:SingleSpeed | SPLIT GNE COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 6270.11549 |
| 414 | Coil:Cooling:DX:SingleSpeed | SPLIT GNE COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.79102 |
| 415 | Coil:Heating:Fuel | SPLIT GNE HEATING COIL | Design Size Nominal Capacity [W] | 7825.97520 |
| 416 | Controller:OutdoorAir | SPLIT GN1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.29486 |
| 417 | Controller:OutdoorAir | SPLIT GN1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.59546E-002 |
| 418 | AirLoopHVAC:UnitarySystem | SPLIT GN1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.29486 |
| 419 | AirLoopHVAC:UnitarySystem | SPLIT GN1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.29486 |
| 420 | AirLoopHVAC:UnitarySystem | SPLIT GN1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.29486 |
| 421 | AirLoopHVAC:UnitarySystem | SPLIT GN1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.29486 |
| 422 | AirLoopHVAC:UnitarySystem | SPLIT GN1_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 5664.07641 |
| 423 | AirLoopHVAC:UnitarySystem | SPLIT GN1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 7124.20125 |
| 424 | AirLoopHVAC:UnitarySystem | SPLIT GN1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 425 | AirLoopHVAC:UnitarySystem | SPLIT GN1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 426 | Fan:OnOff | SPLIT GN1 SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.29486 |
| 427 | Coil:Cooling:DX:SingleSpeed | SPLIT GN1 COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.29486 |
| 428 | Coil:Cooling:DX:SingleSpeed | SPLIT GN1 COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 5664.07641 |
| 429 | Coil:Cooling:DX:SingleSpeed | SPLIT GN1 COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.79282 |
| 430 | Coil:Heating:Fuel | SPLIT GN1 HEATING COIL | Design Size Nominal Capacity [W] | 7124.20125 |
| 431 | Controller:OutdoorAir | SPLIT GN2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.29435 |
| 432 | Controller:OutdoorAir | SPLIT GN2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.59546E-002 |
| 433 | AirLoopHVAC:UnitarySystem | SPLIT GN2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.29435 |
| 434 | AirLoopHVAC:UnitarySystem | SPLIT GN2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.29435 |
| 435 | AirLoopHVAC:UnitarySystem | SPLIT GN2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.29435 |
| 436 | AirLoopHVAC:UnitarySystem | SPLIT GN2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.29435 |
| 437 | AirLoopHVAC:UnitarySystem | SPLIT GN2_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 5656.58179 |
| 438 | AirLoopHVAC:UnitarySystem | SPLIT GN2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 7112.66157 |
| 439 | AirLoopHVAC:UnitarySystem | SPLIT GN2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 440 | AirLoopHVAC:UnitarySystem | SPLIT GN2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 441 | Fan:OnOff | SPLIT GN2 SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.29435 |
| 442 | Coil:Cooling:DX:SingleSpeed | SPLIT GN2 COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.29435 |
| 443 | Coil:Cooling:DX:SingleSpeed | SPLIT GN2 COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 5656.58179 |
| 444 | Coil:Cooling:DX:SingleSpeed | SPLIT GN2 COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.79270 |
| 445 | Coil:Heating:Fuel | SPLIT GN2 HEATING COIL | Design Size Nominal Capacity [W] | 7112.66157 |
| 446 | Controller:OutdoorAir | SPLIT GS1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.29044 |
| 447 | Controller:OutdoorAir | SPLIT GS1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.59546E-002 |
| 448 | AirLoopHVAC:UnitarySystem | SPLIT GS1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.29044 |
| 449 | AirLoopHVAC:UnitarySystem | SPLIT GS1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.29044 |
| 450 | AirLoopHVAC:UnitarySystem | SPLIT GS1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.29044 |
| 451 | AirLoopHVAC:UnitarySystem | SPLIT GS1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.29044 |
| 452 | AirLoopHVAC:UnitarySystem | SPLIT GS1_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 5631.63581 |
| 453 | AirLoopHVAC:UnitarySystem | SPLIT GS1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 7023.27325 |
| 454 | AirLoopHVAC:UnitarySystem | SPLIT GS1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 455 | AirLoopHVAC:UnitarySystem | SPLIT GS1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 456 | Fan:OnOff | SPLIT GS1 SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.29044 |
| 457 | Coil:Cooling:DX:SingleSpeed | SPLIT GS1 COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.29044 |
| 458 | Coil:Cooling:DX:SingleSpeed | SPLIT GS1 COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 5631.63581 |
| 459 | Coil:Cooling:DX:SingleSpeed | SPLIT GS1 COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.78887 |
| 460 | Coil:Heating:Fuel | SPLIT GS1 HEATING COIL | Design Size Nominal Capacity [W] | 7023.27325 |
| 461 | Controller:OutdoorAir | SPLIT GS2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.29254 |
| 462 | Controller:OutdoorAir | SPLIT GS2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.59546E-002 |
| 463 | AirLoopHVAC:UnitarySystem | SPLIT GS2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.29254 |
| 464 | AirLoopHVAC:UnitarySystem | SPLIT GS2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.29254 |
| 465 | AirLoopHVAC:UnitarySystem | SPLIT GS2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.29254 |
| 466 | AirLoopHVAC:UnitarySystem | SPLIT GS2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.29254 |
| 467 | AirLoopHVAC:UnitarySystem | SPLIT GS2_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 5664.09907 |
| 468 | AirLoopHVAC:UnitarySystem | SPLIT GS2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 7071.24864 |
| 469 | AirLoopHVAC:UnitarySystem | SPLIT GS2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 470 | AirLoopHVAC:UnitarySystem | SPLIT GS2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 471 | Fan:OnOff | SPLIT GS2 SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.29254 |
| 472 | Coil:Cooling:DX:SingleSpeed | SPLIT GS2 COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.29254 |
| 473 | Coil:Cooling:DX:SingleSpeed | SPLIT GS2 COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 5664.09907 |
| 474 | Coil:Cooling:DX:SingleSpeed | SPLIT GS2 COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.78933 |
| 475 | Coil:Heating:Fuel | SPLIT GS2 HEATING COIL | Design Size Nominal Capacity [W] | 7071.24864 |
| 476 | Controller:OutdoorAir | SPLIT MSW_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.79626 |
| 477 | Controller:OutdoorAir | SPLIT MSW_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 5.19091E-002 |
| 478 | AirLoopHVAC:UnitarySystem | SPLIT MSW_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.79626 |
| 479 | AirLoopHVAC:UnitarySystem | SPLIT MSW_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.79626 |
| 480 | AirLoopHVAC:UnitarySystem | SPLIT MSW_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.79626 |
| 481 | AirLoopHVAC:UnitarySystem | SPLIT MSW_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.79626 |
| 482 | AirLoopHVAC:UnitarySystem | SPLIT MSW_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 15069.95655 |
| 483 | AirLoopHVAC:UnitarySystem | SPLIT MSW_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 18966.56192 |
| 484 | AirLoopHVAC:UnitarySystem | SPLIT MSW_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 485 | AirLoopHVAC:UnitarySystem | SPLIT MSW_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 486 | Fan:OnOff | SPLIT MSW SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.79626 |
| 487 | Coil:Cooling:DX:SingleSpeed | SPLIT MSW COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.79626 |
| 488 | Coil:Cooling:DX:SingleSpeed | SPLIT MSW COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 15069.95655 |
| 489 | Coil:Cooling:DX:SingleSpeed | SPLIT MSW COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.79857 |
| 490 | Coil:Heating:Fuel | SPLIT MSW HEATING COIL | Design Size Nominal Capacity [W] | 18966.56192 |
| 491 | Controller:OutdoorAir | SPLIT MNW_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.80840 |
| 492 | Controller:OutdoorAir | SPLIT MNW_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 5.19091E-002 |
| 493 | AirLoopHVAC:UnitarySystem | SPLIT MNW_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.80840 |
| 494 | AirLoopHVAC:UnitarySystem | SPLIT MNW_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.80840 |
| 495 | AirLoopHVAC:UnitarySystem | SPLIT MNW_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.80840 |
| 496 | AirLoopHVAC:UnitarySystem | SPLIT MNW_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.80840 |
| 497 | AirLoopHVAC:UnitarySystem | SPLIT MNW_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 15225.09540 |
| 498 | AirLoopHVAC:UnitarySystem | SPLIT MNW_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 19243.60143 |
| 499 | AirLoopHVAC:UnitarySystem | SPLIT MNW_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 500 | AirLoopHVAC:UnitarySystem | SPLIT MNW_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 501 | Fan:OnOff | SPLIT MNW SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.80840 |
| 502 | Coil:Cooling:DX:SingleSpeed | SPLIT MNW COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.80840 |
| 503 | Coil:Cooling:DX:SingleSpeed | SPLIT MNW COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 15225.09540 |
| 504 | Coil:Cooling:DX:SingleSpeed | SPLIT MNW COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80014 |
| 505 | Coil:Heating:Fuel | SPLIT MNW HEATING COIL | Design Size Nominal Capacity [W] | 19243.60143 |
| 506 | Controller:OutdoorAir | SPLIT MSE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.72643 |
| 507 | Controller:OutdoorAir | SPLIT MSE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 5.19091E-002 |
| 508 | AirLoopHVAC:UnitarySystem | SPLIT MSE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.72643 |
| 509 | AirLoopHVAC:UnitarySystem | SPLIT MSE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.72643 |
| 510 | AirLoopHVAC:UnitarySystem | SPLIT MSE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.72643 |
| 511 | AirLoopHVAC:UnitarySystem | SPLIT MSE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.72643 |
| 512 | AirLoopHVAC:UnitarySystem | SPLIT MSE_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 14034.45847 |
| 513 | AirLoopHVAC:UnitarySystem | SPLIT MSE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 17371.55552 |
| 514 | AirLoopHVAC:UnitarySystem | SPLIT MSE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 515 | AirLoopHVAC:UnitarySystem | SPLIT MSE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 516 | Fan:OnOff | SPLIT MSE SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.72643 |
| 517 | Coil:Cooling:DX:SingleSpeed | SPLIT MSE COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.72643 |
| 518 | Coil:Cooling:DX:SingleSpeed | SPLIT MSE COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 14034.45847 |
| 519 | Coil:Cooling:DX:SingleSpeed | SPLIT MSE COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.79002 |
| 520 | Coil:Heating:Fuel | SPLIT MSE HEATING COIL | Design Size Nominal Capacity [W] | 17371.55552 |
| 521 | Controller:OutdoorAir | SPLIT MNE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.73849 |
| 522 | Controller:OutdoorAir | SPLIT MNE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 5.19091E-002 |
| 523 | AirLoopHVAC:UnitarySystem | SPLIT MNE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.73849 |
| 524 | AirLoopHVAC:UnitarySystem | SPLIT MNE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.73849 |
| 525 | AirLoopHVAC:UnitarySystem | SPLIT MNE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.73849 |
| 526 | AirLoopHVAC:UnitarySystem | SPLIT MNE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.73849 |
| 527 | AirLoopHVAC:UnitarySystem | SPLIT MNE_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 14180.78514 |
| 528 | AirLoopHVAC:UnitarySystem | SPLIT MNE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 17646.73136 |
| 529 | AirLoopHVAC:UnitarySystem | SPLIT MNE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 530 | AirLoopHVAC:UnitarySystem | SPLIT MNE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 531 | Fan:OnOff | SPLIT MNE SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.73849 |
| 532 | Coil:Cooling:DX:SingleSpeed | SPLIT MNE COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.73849 |
| 533 | Coil:Cooling:DX:SingleSpeed | SPLIT MNE COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 14180.78514 |
| 534 | Coil:Cooling:DX:SingleSpeed | SPLIT MNE COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.79294 |
| 535 | Coil:Heating:Fuel | SPLIT MNE HEATING COIL | Design Size Nominal Capacity [W] | 17646.73136 |
| 536 | Controller:OutdoorAir | SPLIT MN1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.66644 |
| 537 | Controller:OutdoorAir | SPLIT MN1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 5.19091E-002 |
| 538 | AirLoopHVAC:UnitarySystem | SPLIT MN1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.66644 |
| 539 | AirLoopHVAC:UnitarySystem | SPLIT MN1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.66644 |
| 540 | AirLoopHVAC:UnitarySystem | SPLIT MN1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.66644 |
| 541 | AirLoopHVAC:UnitarySystem | SPLIT MN1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.66644 |
| 542 | AirLoopHVAC:UnitarySystem | SPLIT MN1_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 12700.73993 |
| 543 | AirLoopHVAC:UnitarySystem | SPLIT MN1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 16000.97596 |
| 544 | AirLoopHVAC:UnitarySystem | SPLIT MN1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 545 | AirLoopHVAC:UnitarySystem | SPLIT MN1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 546 | Fan:OnOff | SPLIT MN1 SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.66644 |
| 547 | Coil:Cooling:DX:SingleSpeed | SPLIT MN1 COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.66644 |
| 548 | Coil:Cooling:DX:SingleSpeed | SPLIT MN1 COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 12700.73993 |
| 549 | Coil:Cooling:DX:SingleSpeed | SPLIT MN1 COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.79535 |
| 550 | Coil:Heating:Fuel | SPLIT MN1 HEATING COIL | Design Size Nominal Capacity [W] | 16000.97596 |
| 551 | Controller:OutdoorAir | SPLIT MN2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.66521 |
| 552 | Controller:OutdoorAir | SPLIT MN2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 5.19091E-002 |
| 553 | AirLoopHVAC:UnitarySystem | SPLIT MN2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.66521 |
| 554 | AirLoopHVAC:UnitarySystem | SPLIT MN2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.66521 |
| 555 | AirLoopHVAC:UnitarySystem | SPLIT MN2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.66521 |
| 556 | AirLoopHVAC:UnitarySystem | SPLIT MN2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.66521 |
| 557 | AirLoopHVAC:UnitarySystem | SPLIT MN2_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 12682.31325 |
| 558 | AirLoopHVAC:UnitarySystem | SPLIT MN2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 15972.70466 |
| 559 | AirLoopHVAC:UnitarySystem | SPLIT MN2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 560 | AirLoopHVAC:UnitarySystem | SPLIT MN2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 561 | Fan:OnOff | SPLIT MN2 SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.66521 |
| 562 | Coil:Cooling:DX:SingleSpeed | SPLIT MN2 COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.66521 |
| 563 | Coil:Cooling:DX:SingleSpeed | SPLIT MN2 COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 12682.31325 |
| 564 | Coil:Cooling:DX:SingleSpeed | SPLIT MN2 COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.79522 |
| 565 | Coil:Heating:Fuel | SPLIT MN2 HEATING COIL | Design Size Nominal Capacity [W] | 15972.70466 |
| 566 | Controller:OutdoorAir | SPLIT MS1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.65488 |
| 567 | Controller:OutdoorAir | SPLIT MS1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 5.19091E-002 |
| 568 | AirLoopHVAC:UnitarySystem | SPLIT MS1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.65488 |
| 569 | AirLoopHVAC:UnitarySystem | SPLIT MS1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.65488 |
| 570 | AirLoopHVAC:UnitarySystem | SPLIT MS1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.65488 |
| 571 | AirLoopHVAC:UnitarySystem | SPLIT MS1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.65488 |
| 572 | AirLoopHVAC:UnitarySystem | SPLIT MS1_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 12578.74201 |
| 573 | AirLoopHVAC:UnitarySystem | SPLIT MS1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 15737.06740 |
| 574 | AirLoopHVAC:UnitarySystem | SPLIT MS1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 575 | AirLoopHVAC:UnitarySystem | SPLIT MS1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 576 | Fan:OnOff | SPLIT MS1 SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.65488 |
| 577 | Coil:Cooling:DX:SingleSpeed | SPLIT MS1 COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.65488 |
| 578 | Coil:Cooling:DX:SingleSpeed | SPLIT MS1 COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 12578.74201 |
| 579 | Coil:Cooling:DX:SingleSpeed | SPLIT MS1 COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.79285 |
| 580 | Coil:Heating:Fuel | SPLIT MS1 HEATING COIL | Design Size Nominal Capacity [W] | 15737.06740 |
| 581 | Controller:OutdoorAir | SPLIT MS2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.65364 |
| 582 | Controller:OutdoorAir | SPLIT MS2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 5.19091E-002 |
| 583 | AirLoopHVAC:UnitarySystem | SPLIT MS2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.65364 |
| 584 | AirLoopHVAC:UnitarySystem | SPLIT MS2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.65364 |
| 585 | AirLoopHVAC:UnitarySystem | SPLIT MS2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.65364 |
| 586 | AirLoopHVAC:UnitarySystem | SPLIT MS2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.65364 |
| 587 | AirLoopHVAC:UnitarySystem | SPLIT MS2_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 12560.37663 |
| 588 | AirLoopHVAC:UnitarySystem | SPLIT MS2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 15708.57996 |
| 589 | AirLoopHVAC:UnitarySystem | SPLIT MS2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 590 | AirLoopHVAC:UnitarySystem | SPLIT MS2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 591 | Fan:OnOff | SPLIT MS2 SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.65364 |
| 592 | Coil:Cooling:DX:SingleSpeed | SPLIT MS2 COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.65364 |
| 593 | Coil:Cooling:DX:SingleSpeed | SPLIT MS2 COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 12560.37663 |
| 594 | Coil:Cooling:DX:SingleSpeed | SPLIT MS2 COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.79271 |
| 595 | Coil:Heating:Fuel | SPLIT MS2 HEATING COIL | Design Size Nominal Capacity [W] | 15708.57996 |
| 596 | Controller:OutdoorAir | SPLIT TSW_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.44539 |
| 597 | Controller:OutdoorAir | SPLIT TSW_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.59546E-002 |
| 598 | AirLoopHVAC:UnitarySystem | SPLIT TSW_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.44539 |
| 599 | AirLoopHVAC:UnitarySystem | SPLIT TSW_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.44539 |
| 600 | AirLoopHVAC:UnitarySystem | SPLIT TSW_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.44539 |
| 601 | AirLoopHVAC:UnitarySystem | SPLIT TSW_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.44539 |
| 602 | AirLoopHVAC:UnitarySystem | SPLIT TSW_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 8421.94431 |
| 603 | AirLoopHVAC:UnitarySystem | SPLIT TSW_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 10562.93069 |
| 604 | AirLoopHVAC:UnitarySystem | SPLIT TSW_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 605 | AirLoopHVAC:UnitarySystem | SPLIT TSW_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 606 | Fan:OnOff | SPLIT TSW SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.44539 |
| 607 | Coil:Cooling:DX:SingleSpeed | SPLIT TSW COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.44539 |
| 608 | Coil:Cooling:DX:SingleSpeed | SPLIT TSW COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 8421.94431 |
| 609 | Coil:Cooling:DX:SingleSpeed | SPLIT TSW COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.79886 |
| 610 | Coil:Heating:Fuel | SPLIT TSW HEATING COIL | Design Size Nominal Capacity [W] | 10562.93069 |
| 611 | Controller:OutdoorAir | SPLIT TNW_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.45680 |
| 612 | Controller:OutdoorAir | SPLIT TNW_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.59546E-002 |
| 613 | AirLoopHVAC:UnitarySystem | SPLIT TNW_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.45680 |
| 614 | AirLoopHVAC:UnitarySystem | SPLIT TNW_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.45680 |
| 615 | AirLoopHVAC:UnitarySystem | SPLIT TNW_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.45680 |
| 616 | AirLoopHVAC:UnitarySystem | SPLIT TNW_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.45680 |
| 617 | AirLoopHVAC:UnitarySystem | SPLIT TNW_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 8585.83183 |
| 618 | AirLoopHVAC:UnitarySystem | SPLIT TNW_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 10823.29451 |
| 619 | AirLoopHVAC:UnitarySystem | SPLIT TNW_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 620 | AirLoopHVAC:UnitarySystem | SPLIT TNW_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 621 | Fan:OnOff | SPLIT TNW SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.45680 |
| 622 | Coil:Cooling:DX:SingleSpeed | SPLIT TNW COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.45680 |
| 623 | Coil:Cooling:DX:SingleSpeed | SPLIT TNW COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 8585.83183 |
| 624 | Coil:Cooling:DX:SingleSpeed | SPLIT TNW COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80080 |
| 625 | Coil:Heating:Fuel | SPLIT TNW HEATING COIL | Design Size Nominal Capacity [W] | 10823.29451 |
| 626 | Controller:OutdoorAir | SPLIT TSE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.39301 |
| 627 | Controller:OutdoorAir | SPLIT TSE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.59546E-002 |
| 628 | AirLoopHVAC:UnitarySystem | SPLIT TSE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.39301 |
| 629 | AirLoopHVAC:UnitarySystem | SPLIT TSE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.39301 |
| 630 | AirLoopHVAC:UnitarySystem | SPLIT TSE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.39301 |
| 631 | AirLoopHVAC:UnitarySystem | SPLIT TSE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.39301 |
| 632 | AirLoopHVAC:UnitarySystem | SPLIT TSE_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 7618.32512 |
| 633 | AirLoopHVAC:UnitarySystem | SPLIT TSE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 9366.36173 |
| 634 | AirLoopHVAC:UnitarySystem | SPLIT TSE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 635 | AirLoopHVAC:UnitarySystem | SPLIT TSE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 636 | Fan:OnOff | SPLIT TSE SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.39301 |
| 637 | Coil:Cooling:DX:SingleSpeed | SPLIT TSE COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.39301 |
| 638 | Coil:Cooling:DX:SingleSpeed | SPLIT TSE COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 7618.32512 |
| 639 | Coil:Cooling:DX:SingleSpeed | SPLIT TSE COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.78896 |
| 640 | Coil:Heating:Fuel | SPLIT TSE HEATING COIL | Design Size Nominal Capacity [W] | 9366.36173 |
| 641 | Controller:OutdoorAir | SPLIT TNE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.40421 |
| 642 | Controller:OutdoorAir | SPLIT TNE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.59546E-002 |
| 643 | AirLoopHVAC:UnitarySystem | SPLIT TNE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.40421 |
| 644 | AirLoopHVAC:UnitarySystem | SPLIT TNE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.40421 |
| 645 | AirLoopHVAC:UnitarySystem | SPLIT TNE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.40421 |
| 646 | AirLoopHVAC:UnitarySystem | SPLIT TNE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.40421 |
| 647 | AirLoopHVAC:UnitarySystem | SPLIT TNE_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 7777.13561 |
| 648 | AirLoopHVAC:UnitarySystem | SPLIT TNE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 9622.01938 |
| 649 | AirLoopHVAC:UnitarySystem | SPLIT TNE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 650 | AirLoopHVAC:UnitarySystem | SPLIT TNE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 651 | Fan:OnOff | SPLIT TNE SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.40421 |
| 652 | Coil:Cooling:DX:SingleSpeed | SPLIT TNE COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.40421 |
| 653 | Coil:Cooling:DX:SingleSpeed | SPLIT TNE COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 7777.13561 |
| 654 | Coil:Cooling:DX:SingleSpeed | SPLIT TNE COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.79231 |
| 655 | Coil:Heating:Fuel | SPLIT TNE HEATING COIL | Design Size Nominal Capacity [W] | 9622.01938 |
| 656 | Controller:OutdoorAir | SPLIT TN1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.37582 |
| 657 | Controller:OutdoorAir | SPLIT TN1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.59546E-002 |
| 658 | AirLoopHVAC:UnitarySystem | SPLIT TN1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.37582 |
| 659 | AirLoopHVAC:UnitarySystem | SPLIT TN1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.37582 |
| 660 | AirLoopHVAC:UnitarySystem | SPLIT TN1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.37582 |
| 661 | AirLoopHVAC:UnitarySystem | SPLIT TN1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.37582 |
| 662 | AirLoopHVAC:UnitarySystem | SPLIT TN1_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 7076.40550 |
| 663 | AirLoopHVAC:UnitarySystem | SPLIT TN1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 8973.63356 |
| 664 | AirLoopHVAC:UnitarySystem | SPLIT TN1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 665 | AirLoopHVAC:UnitarySystem | SPLIT TN1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 666 | Fan:OnOff | SPLIT TN1 SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.37582 |
| 667 | Coil:Cooling:DX:SingleSpeed | SPLIT TN1 COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.37582 |
| 668 | Coil:Cooling:DX:SingleSpeed | SPLIT TN1 COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 7076.40550 |
| 669 | Coil:Cooling:DX:SingleSpeed | SPLIT TN1 COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80022 |
| 670 | Coil:Heating:Fuel | SPLIT TN1 HEATING COIL | Design Size Nominal Capacity [W] | 8973.63356 |
| 671 | Controller:OutdoorAir | SPLIT TN2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.37418 |
| 672 | Controller:OutdoorAir | SPLIT TN2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.59546E-002 |
| 673 | AirLoopHVAC:UnitarySystem | SPLIT TN2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.37418 |
| 674 | AirLoopHVAC:UnitarySystem | SPLIT TN2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.37418 |
| 675 | AirLoopHVAC:UnitarySystem | SPLIT TN2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.37418 |
| 676 | AirLoopHVAC:UnitarySystem | SPLIT TN2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.37418 |
| 677 | AirLoopHVAC:UnitarySystem | SPLIT TN2_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 7051.43694 |
| 678 | AirLoopHVAC:UnitarySystem | SPLIT TN2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 8936.07857 |
| 679 | AirLoopHVAC:UnitarySystem | SPLIT TN2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 680 | AirLoopHVAC:UnitarySystem | SPLIT TN2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 681 | Fan:OnOff | SPLIT TN2 SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.37418 |
| 682 | Coil:Cooling:DX:SingleSpeed | SPLIT TN2 COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.37418 |
| 683 | Coil:Cooling:DX:SingleSpeed | SPLIT TN2 COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 7051.43694 |
| 684 | Coil:Cooling:DX:SingleSpeed | SPLIT TN2 COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80095 |
| 685 | Coil:Heating:Fuel | SPLIT TN2 HEATING COIL | Design Size Nominal Capacity [W] | 8936.07857 |
| 686 | Controller:OutdoorAir | SPLIT TS1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.36467 |
| 687 | Controller:OutdoorAir | SPLIT TS1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.59546E-002 |
| 688 | AirLoopHVAC:UnitarySystem | SPLIT TS1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.36467 |
| 689 | AirLoopHVAC:UnitarySystem | SPLIT TS1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.36467 |
| 690 | AirLoopHVAC:UnitarySystem | SPLIT TS1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.36467 |
| 691 | AirLoopHVAC:UnitarySystem | SPLIT TS1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.36467 |
| 692 | AirLoopHVAC:UnitarySystem | SPLIT TS1_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 6922.53595 |
| 693 | AirLoopHVAC:UnitarySystem | SPLIT TS1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 8718.98778 |
| 694 | AirLoopHVAC:UnitarySystem | SPLIT TS1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 695 | AirLoopHVAC:UnitarySystem | SPLIT TS1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 696 | Fan:OnOff | SPLIT TS1 SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.36467 |
| 697 | Coil:Cooling:DX:SingleSpeed | SPLIT TS1 COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.36467 |
| 698 | Coil:Cooling:DX:SingleSpeed | SPLIT TS1 COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 6922.53595 |
| 699 | Coil:Cooling:DX:SingleSpeed | SPLIT TS1 COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.79760 |
| 700 | Coil:Heating:Fuel | SPLIT TS1 HEATING COIL | Design Size Nominal Capacity [W] | 8718.98778 |
| 701 | Controller:OutdoorAir | SPLIT TS2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.36303 |
| 702 | Controller:OutdoorAir | SPLIT TS2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.59546E-002 |
| 703 | AirLoopHVAC:UnitarySystem | SPLIT TS2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.36303 |
| 704 | AirLoopHVAC:UnitarySystem | SPLIT TS2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.36303 |
| 705 | AirLoopHVAC:UnitarySystem | SPLIT TS2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.36303 |
| 706 | AirLoopHVAC:UnitarySystem | SPLIT TS2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.36303 |
| 707 | AirLoopHVAC:UnitarySystem | SPLIT TS2_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 6897.77150 |
| 708 | AirLoopHVAC:UnitarySystem | SPLIT TS2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 8681.56103 |
| 709 | AirLoopHVAC:UnitarySystem | SPLIT TS2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 710 | AirLoopHVAC:UnitarySystem | SPLIT TS2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 711 | Fan:OnOff | SPLIT TS2 SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.36303 |
| 712 | Coil:Cooling:DX:SingleSpeed | SPLIT TS2 COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.36303 |
| 713 | Coil:Cooling:DX:SingleSpeed | SPLIT TS2 COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 6897.77150 |
| 714 | Coil:Cooling:DX:SingleSpeed | SPLIT TS2 COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.79731 |
| 715 | Coil:Heating:Fuel | SPLIT TS2 HEATING COIL | Design Size Nominal Capacity [W] | 8681.56103 |
| Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
| 1 | Coil:Cooling:DX:SingleSpeed | SPLIT GSW COOLING COIL | 6335.3 | 3.21 | 10.96 | 11.40 | 10.78 | 10.79 |
| 2 | Coil:Cooling:DX:SingleSpeed | SPLIT GNW COOLING COIL | 6385.0 | 3.21 | 10.95 | 11.39 | 10.77 | 10.78 |
| 3 | Coil:Cooling:DX:SingleSpeed | SPLIT OFFICE COOLING COIL | 6830.1 | 3.21 | 10.96 | 11.41 | 10.79 | 10.80 |
| 4 | Coil:Cooling:DX:SingleSpeed | SPLIT GNE COOLING COIL | 6014.4 | 3.22 | 10.98 | 11.43 | 10.81 | 10.83 |
| 5 | Coil:Cooling:DX:SingleSpeed | SPLIT GN1 COOLING COIL | 5432.5 | 3.22 | 10.98 | 11.42 | 10.80 | 10.82 |
| 6 | Coil:Cooling:DX:SingleSpeed | SPLIT GN2 COOLING COIL | 5425.4 | 3.22 | 10.98 | 11.42 | 10.80 | 10.82 |
| 7 | Coil:Cooling:DX:SingleSpeed | SPLIT GS1 COOLING COIL | 5403.5 | 3.22 | 10.99 | 11.44 | 10.82 | 10.85 |
| 8 | Coil:Cooling:DX:SingleSpeed | SPLIT GS2 COOLING COIL | 5434.3 | 3.22 | 10.99 | 11.44 | 10.82 | 10.84 |
| 9 | Coil:Cooling:DX:SingleSpeed | SPLIT MSW COOLING COIL | 14444.8 | 3.21 | 10.95 | 11.39 | 10.77 | 10.78 |
| 10 | Coil:Cooling:DX:SingleSpeed | SPLIT MNW COOLING COIL | 14590.4 | 3.21 | 10.94 | 11.38 | 10.76 | 10.76 |
| 11 | Coil:Cooling:DX:SingleSpeed | SPLIT MSE COOLING COIL | 13463.9 | 3.22 | 10.99 | 11.43 | 10.81 | 10.84 |
| 12 | Coil:Cooling:DX:SingleSpeed | SPLIT MNE COOLING COIL | 13600.8 | 3.22 | 10.98 | 11.42 | 10.80 | 10.82 |
| 13 | Coil:Cooling:DX:SingleSpeed | SPLIT MN1 COOLING COIL | 12177.4 | 3.21 | 10.96 | 11.40 | 10.79 | 10.80 |
| 14 | Coil:Cooling:DX:SingleSpeed | SPLIT MN2 COOLING COIL | 12160.0 | 3.21 | 10.96 | 11.40 | 10.79 | 10.80 |
| 15 | Coil:Cooling:DX:SingleSpeed | SPLIT MS1 COOLING COIL | 12064.4 | 3.22 | 10.98 | 11.42 | 10.80 | 10.82 |
| 16 | Coil:Cooling:DX:SingleSpeed | SPLIT MS2 COOLING COIL | 12047.0 | 3.22 | 10.98 | 11.42 | 10.80 | 10.82 |
| 17 | Coil:Cooling:DX:SingleSpeed | SPLIT TSW COOLING COIL | 8072.2 | 3.21 | 10.95 | 11.39 | 10.77 | 10.78 |
| 18 | Coil:Cooling:DX:SingleSpeed | SPLIT TNW COOLING COIL | 8227.2 | 3.20 | 10.93 | 11.37 | 10.76 | 10.76 |
| 19 | Coil:Cooling:DX:SingleSpeed | SPLIT TSE COOLING COIL | 7309.6 | 3.22 | 10.99 | 11.44 | 10.82 | 10.85 |
| 20 | Coil:Cooling:DX:SingleSpeed | SPLIT TNE COOLING COIL | 7459.7 | 3.22 | 10.98 | 11.42 | 10.81 | 10.83 |
| 21 | Coil:Cooling:DX:SingleSpeed | SPLIT TN1 COOLING COIL | 6781.3 | 3.21 | 10.94 | 11.38 | 10.76 | 10.76 |
| 22 | Coil:Cooling:DX:SingleSpeed | SPLIT TN2 COOLING COIL | 6757.7 | 3.21 | 10.94 | 11.38 | 10.76 | 10.77 |
| 23 | Coil:Cooling:DX:SingleSpeed | SPLIT TS1 COOLING COIL | 6636.2 | 3.21 | 10.95 | 11.39 | 10.78 | 10.79 |
| 24 | Coil:Cooling:DX:SingleSpeed | SPLIT TS2 COOLING COIL | 6612.7 | 3.21 | 10.95 | 11.40 | 10.78 | 10.79 |
| Zone Name | # Surfaces | |
| 1 | G SW APARTMENT | 9 |
| 2 | G NW APARTMENT | 9 |
| 3 | OFFICE | 9 |
| 4 | G NE APARTMENT | 9 |
| 5 | G N1 APARTMENT | 8 |
| 6 | G N2 APARTMENT | 8 |
| 7 | G S1 APARTMENT | 8 |
| 8 | G S2 APARTMENT | 8 |
| 9 | M SW APARTMENT | 9 |
| 10 | M NW APARTMENT | 9 |
| 11 | M SE APARTMENT | 9 |
| 12 | M NE APARTMENT | 9 |
| 13 | M N1 APARTMENT | 8 |
| 14 | M N2 APARTMENT | 8 |
| 15 | M S1 APARTMENT | 8 |
| 16 | M S2 APARTMENT | 8 |
| 17 | T SW APARTMENT | 9 |
| 18 | T NW APARTMENT | 9 |
| 19 | T SE APARTMENT | 9 |
| 20 | T NE APARTMENT | 9 |
| 21 | T N1 APARTMENT | 8 |
| 22 | T N2 APARTMENT | 8 |
| 23 | T S1 APARTMENT | 8 |
| 24 | T S2 APARTMENT | 8 |
| 25 | T CORRIDOR | 13 |
| 26 | G CORRIDOR | 13 |
| 27 | M CORRIDOR | 13 |
| Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
| 1 | G SWALL SWA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_GRD | 0.844 | 0.750 | 28.24 | 35.30 | 28.24 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 2 | GWINDOW1 S SWA | Window | G SWALL SWA | Window5 Detailed Fenestration | RESWINDOW_U_0.5369_SHGC_0.25 | N/A | 3.053 | No | 7.06 | 7.06 | 7.06 | 180.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 3 | G WWALL SWA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_GRD | 0.844 | 0.750 | 18.58 | 23.22 | 18.58 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 4 | GWINDOW1 W SWA | Window | G WWALL SWA | Window5 Detailed Fenestration | RESWINDOW_U_0.5369_SHGC_0.25 | N/A | 3.053 | No | 4.65 | 4.65 | 4.65 | 270.00 | 90.00 | 3.81 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 5 | G NIWALL SWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-G NIWALL SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 6 | G EIWALL SWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | iz-G EIWALL SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 7 | G GFLOOR SWA | Floor | CTF - ConductionTransferFunction | GGFLOORSWA_FFACTOR | 0.287 | 0.268 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 8 | G CEILIN SWA | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | G CEILIN SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 9 | G INTERNALMASS SWA | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 88.25 | 88.25 | 88.25 | 0.00 | 90.00 | 88.25 | 1.00 | 0.00 | G INTERNALMASS SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 10 | G NWALL NWA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_GRD | 0.844 | 0.750 | 28.24 | 35.30 | 28.24 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 11 | GWINDOW1 N NWA | Window | G NWALL NWA | Window5 Detailed Fenestration | RESWINDOW_U_0.5369_SHGC_0.25 | N/A | 3.053 | No | 7.06 | 7.06 | 7.06 | 0.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 12 | G WWALL NWA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_GRD | 0.844 | 0.750 | 18.58 | 23.22 | 18.58 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 13 | GWINDOW1 W NWA | Window | G WWALL NWA | Window5 Detailed Fenestration | RESWINDOW_U_0.5369_SHGC_0.25 | N/A | 3.053 | No | 4.65 | 4.65 | 4.65 | 270.00 | 90.00 | 3.81 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 14 | G SIWALL NWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-G SIWALL NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 15 | G EIWALL NWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | iz-G EIWALL NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 16 | G GFLOOR NWA | Floor | CTF - ConductionTransferFunction | GGFLOORNWA_FFACTOR | 0.287 | 0.268 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 17 | G CEILIN NWA | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | G CEILIN NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 18 | G INTERNALMASS NWA | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 88.25 | 88.25 | 88.25 | 0.00 | 90.00 | 88.25 | 1.00 | 0.00 | G INTERNALMASS NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 19 | G SWALL SEA | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.844 | 0.750 | 28.24 | 35.30 | 28.24 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 20 | GWINDOW1 S SEA | Window | G SWALL SEA | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5369_SHGC_0.25 | N/A | 3.053 | No | 7.06 | 7.06 | 7.06 | 180.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 21 | G EWALL SEA | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.844 | 0.750 | 18.58 | 23.22 | 18.58 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 22 | GWINDOW1 E SEA | Window | G EWALL SEA | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5369_SHGC_0.25 | N/A | 3.053 | No | 4.65 | 4.65 | 4.65 | 90.00 | 90.00 | 3.81 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 23 | G NIWALL SEA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-G NIWALL SEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 24 | iz-G EIWALL S2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | G EIWALL S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 25 | G GFLOOR SEA | Floor | CTF - ConductionTransferFunction | GGFLOORSEA_FFACTOR | 0.287 | 0.268 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 26 | G CEILIN SEA | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | G CEILIN SEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 27 | G INTERNALMASS SEA | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 88.25 | 88.25 | 88.25 | 0.00 | 90.00 | 88.25 | 1.00 | 0.00 | G INTERNALMASS SEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 28 | G NWALL NEA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_GRD | 0.844 | 0.750 | 28.24 | 35.30 | 28.24 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 29 | GWINDOW1 N NEA | Window | G NWALL NEA | Window5 Detailed Fenestration | RESWINDOW_U_0.5369_SHGC_0.25 | N/A | 3.053 | No | 7.06 | 7.06 | 7.06 | 0.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 30 | G EWALL NEA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_GRD | 0.844 | 0.750 | 18.58 | 23.22 | 18.58 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 31 | GWINDOW1 E NEA | Window | G EWALL NEA | Window5 Detailed Fenestration | RESWINDOW_U_0.5369_SHGC_0.25 | N/A | 3.053 | No | 4.65 | 4.65 | 4.65 | 90.00 | 90.00 | 3.81 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 32 | G SIWALL NEA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-G SIWALL NEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 33 | iz-G EIWALL N2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | G EIWALL N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 34 | G GFLOOR NEA | Floor | CTF - ConductionTransferFunction | GGFLOORNEA_FFACTOR | 0.287 | 0.268 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 35 | G CEILIN NEA | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | G CEILIN NEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 36 | G INTERNALMASS NEA | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 88.25 | 88.25 | 88.25 | 0.00 | 90.00 | 88.25 | 1.00 | 0.00 | G INTERNALMASS NEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 37 | G NWALL N1A | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_GRD | 0.844 | 0.750 | 28.24 | 35.30 | 28.24 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 38 | GWINDOW1 N N1A | Window | G NWALL N1A | Window5 Detailed Fenestration | RESWINDOW_U_0.5369_SHGC_0.25 | N/A | 3.053 | No | 7.06 | 7.06 | 7.06 | 0.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 39 | G SIWALL N1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-G SIWALL N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 40 | G EIWALL N1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | iz-G EIWALL N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 41 | iz-G EIWALL NWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | G EIWALL NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 42 | G GFLOOR N1A | Floor | CTF - ConductionTransferFunction | GGFLOORN1A_FFACTOR | 0.170 | 0.163 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 43 | G CEILIN N1A | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | G CEILIN N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 44 | G INTERNALMASS N1A | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 88.25 | 88.25 | 88.25 | 0.00 | 90.00 | 88.25 | 1.00 | 0.00 | G INTERNALMASS N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 45 | G NWALL N2A | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_GRD | 0.844 | 0.750 | 28.24 | 35.30 | 28.24 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 46 | GWINDOW1 N N2A | Window | G NWALL N2A | Window5 Detailed Fenestration | RESWINDOW_U_0.5369_SHGC_0.25 | N/A | 3.053 | No | 7.06 | 7.06 | 7.06 | 0.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 47 | G SIWALL N2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-G SIWALL N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 48 | G EIWALL N2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | iz-G EIWALL N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 49 | iz-G EIWALL N1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | G EIWALL N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 50 | G GFLOOR N2A | Floor | CTF - ConductionTransferFunction | GGFLOORN2A_FFACTOR | 0.170 | 0.163 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 51 | G CEILIN N2A | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | G CEILIN N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 52 | G INTERNALMASS N2A | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 88.25 | 88.25 | 88.25 | 0.00 | 90.00 | 88.25 | 1.00 | 0.00 | G INTERNALMASS N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 53 | G SWALL S1A | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_GRD | 0.844 | 0.750 | 28.24 | 35.30 | 28.24 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 54 | GWINDOW1 S S1A | Window | G SWALL S1A | Window5 Detailed Fenestration | RESWINDOW_U_0.5369_SHGC_0.25 | N/A | 3.053 | No | 7.06 | 7.06 | 7.06 | 180.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 55 | G NIWALL S1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-G NIWALL S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 56 | G EIWALL S1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | iz-G EIWALL S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 57 | iz-G EIWALL SWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | G EIWALL SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 58 | G GFLOOR S1A | Floor | CTF - ConductionTransferFunction | GGFLOORS1A_FFACTOR | 0.170 | 0.163 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 59 | G CEILIN S1A | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | G CEILIN S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 60 | G INTERNALMASS S1A | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 88.25 | 88.25 | 88.25 | 0.00 | 90.00 | 88.25 | 1.00 | 0.00 | G INTERNALMASS S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 61 | G SWALL S2A | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_GRD | 0.844 | 0.750 | 28.24 | 35.30 | 28.24 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 62 | GWINDOW1 S S2A | Window | G SWALL S2A | Window5 Detailed Fenestration | RESWINDOW_U_0.5369_SHGC_0.25 | N/A | 3.053 | No | 7.06 | 7.06 | 7.06 | 180.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 63 | G NIWALL S2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-G NIWALL S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 64 | G EIWALL S2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | iz-G EIWALL S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 65 | iz-G EIWALL S1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | G EIWALL S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 66 | G GFLOOR S2A | Floor | CTF - ConductionTransferFunction | GGFLOORS2A_FFACTOR | 0.170 | 0.163 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 67 | G CEILIN S2A | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | G CEILIN S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 68 | G INTERNALMASS S2A | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 88.25 | 88.25 | 88.25 | 0.00 | 90.00 | 88.25 | 1.00 | 0.00 | G INTERNALMASS S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 69 | M WWALL SWA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.854 | 0.757 | 18.58 | 23.22 | 18.58 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 70 | MWINDOW1 W SWA | Window | M WWALL SWA | Window5 Detailed Fenestration | RESWINDOW_U_0.5369_SHGC_0.25 | N/A | 3.053 | No | 4.65 | 4.65 | 4.65 | 270.00 | 90.00 | 3.81 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 71 | M SWALL SWA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.854 | 0.757 | 28.24 | 35.30 | 28.24 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 72 | MWINDOW1 S SWA | Window | M SWALL SWA | Window5 Detailed Fenestration | RESWINDOW_U_0.5369_SHGC_0.25 | N/A | 3.053 | No | 7.06 | 7.06 | 7.06 | 180.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 73 | M NIWALL SWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-M NIWALL SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 74 | M EIWALL SWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 90.00 | 90.00 | 3.05 | 7.62 | 0.00 | iz-M EIWALL SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 75 | M GFLOOR SWA | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | M GFLOOR SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 76 | M CEILIN SWA | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | M CEILIN SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 77 | M INTERNALMASS SWA | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 176.50 | 176.50 | 176.50 | 0.00 | 90.00 | 176.50 | 1.00 | 0.00 | M INTERNALMASS SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 78 | M NWALL NWA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.854 | 0.757 | 28.24 | 35.30 | 28.24 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 79 | MWINDOW1 N NWA | Window | M NWALL NWA | Window5 Detailed Fenestration | RESWINDOW_U_0.5369_SHGC_0.25 | N/A | 3.053 | No | 7.06 | 7.06 | 7.06 | 0.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 80 | M WWALL NWA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.854 | 0.757 | 18.58 | 23.22 | 18.58 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 81 | MWINDOW1 W NWA | Window | M WWALL NWA | Window5 Detailed Fenestration | RESWINDOW_U_0.5369_SHGC_0.25 | N/A | 3.053 | No | 4.65 | 4.65 | 4.65 | 270.00 | 90.00 | 3.81 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 82 | M SIWALL NWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-M SIWALL NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 83 | M EIWALL NWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | iz-M EIWALL NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 84 | M GFLOOR NWA | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | M GFLOOR NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 85 | M CEILIN NWA | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | M CEILIN NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 86 | M INTERNALMASS NWA | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 176.50 | 176.50 | 176.50 | 0.00 | 90.00 | 176.50 | 1.00 | 0.00 | M INTERNALMASS NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 87 | M EWALL SEA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.854 | 0.757 | 18.58 | 23.22 | 18.58 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 88 | MWINDOW1 E SEA | Window | M EWALL SEA | Window5 Detailed Fenestration | RESWINDOW_U_0.5369_SHGC_0.25 | N/A | 3.053 | No | 4.65 | 4.65 | 4.65 | 90.00 | 90.00 | 3.81 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 89 | M SWALL SEA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.854 | 0.757 | 28.24 | 35.30 | 28.24 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 90 | MWINDOW1 S SEA | Window | M SWALL SEA | Window5 Detailed Fenestration | RESWINDOW_U_0.5369_SHGC_0.25 | N/A | 3.053 | No | 7.06 | 7.06 | 7.06 | 180.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 91 | M NIWALL SEA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-M NIWALL SEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 92 | iz-M EIWALL S2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | M EIWALL S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 93 | M GFLOOR SEA | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | M GFLOOR SEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 94 | M CEILIN SEA | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | M CEILIN SEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 95 | M INTERNALMASS SEA | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 176.50 | 176.50 | 176.50 | 0.00 | 90.00 | 176.50 | 1.00 | 0.00 | M INTERNALMASS SEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 96 | M NWALL NEA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.854 | 0.757 | 28.24 | 35.30 | 28.24 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 97 | MWINDOW1 N NEA | Window | M NWALL NEA | Window5 Detailed Fenestration | RESWINDOW_U_0.5369_SHGC_0.25 | N/A | 3.053 | No | 7.06 | 7.06 | 7.06 | 0.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 98 | M EWALL NEA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.854 | 0.757 | 18.58 | 23.22 | 18.58 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 99 | MWINDOW1 E NEA | Window | M EWALL NEA | Window5 Detailed Fenestration | RESWINDOW_U_0.5369_SHGC_0.25 | N/A | 3.053 | No | 4.65 | 4.65 | 4.65 | 90.00 | 90.00 | 3.81 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 100 | M SIWALL NEA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-M SIWALL NEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 101 | iz-M EIWALL N2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | M EIWALL N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 102 | M GFLOOR NEA | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | M GFLOOR NEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 103 | M CEILIN NEA | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | M CEILIN NEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 104 | M INTERNALMASS NEA | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 176.50 | 176.50 | 176.50 | 0.00 | 90.00 | 176.50 | 1.00 | 0.00 | M INTERNALMASS NEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 105 | M NWALL N1A | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.854 | 0.757 | 28.24 | 35.30 | 28.24 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 106 | MWINDOW1 N N1A | Window | M NWALL N1A | Window5 Detailed Fenestration | RESWINDOW_U_0.5369_SHGC_0.25 | N/A | 3.053 | No | 7.06 | 7.06 | 7.06 | 0.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 107 | M SIWALL N1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-M SIWALL N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 108 | M EIWALL N1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | iz-M EIWALL N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 109 | iz-M EIWALL NWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | M EIWALL NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 110 | M GFLOOR N1A | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | M GFLOOR N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 111 | M CEILIN N1A | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | M CEILIN N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 112 | M INTERNALMASS N1A | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 176.50 | 176.50 | 176.50 | 0.00 | 90.00 | 176.50 | 1.00 | 0.00 | M INTERNALMASS N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 113 | M NWALL N2A | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.854 | 0.757 | 28.24 | 35.30 | 28.24 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 114 | MWINDOW1 N N2A | Window | M NWALL N2A | Window5 Detailed Fenestration | RESWINDOW_U_0.5369_SHGC_0.25 | N/A | 3.053 | No | 7.06 | 7.06 | 7.06 | 0.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 115 | M SIWALL N2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-M SIWALL N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 116 | M EIWALL N2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | iz-M EIWALL N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 117 | iz-M EIWALL N1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | M EIWALL N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 118 | M GFLOOR N2A | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | M GFLOOR N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 119 | M CEILIN N2A | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | M CEILIN N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 120 | M INTERNALMASS N2A | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 176.50 | 176.50 | 176.50 | 0.00 | 90.00 | 176.50 | 1.00 | 0.00 | M INTERNALMASS N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 121 | M SWALL S1A | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.854 | 0.757 | 28.24 | 35.30 | 28.24 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 122 | MWINDOW1 S S1A | Window | M SWALL S1A | Window5 Detailed Fenestration | RESWINDOW_U_0.5369_SHGC_0.25 | N/A | 3.053 | No | 7.06 | 7.06 | 7.06 | 180.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 123 | M NIWALL S1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-M NIWALL S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 124 | M EIWALL S1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | iz-M EIWALL S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 125 | iz-M EIWALL SWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 270.00 | 90.00 | 3.05 | 7.62 | 0.00 | M EIWALL SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 126 | M GFLOOR S1A | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | M GFLOOR S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 127 | M CEILIN S1A | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | M CEILIN S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 128 | M INTERNALMASS S1A | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 176.50 | 176.50 | 176.50 | 0.00 | 90.00 | 176.50 | 1.00 | 0.00 | M INTERNALMASS S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 129 | M SWALL S2A | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.854 | 0.757 | 28.24 | 35.30 | 28.24 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 130 | MWINDOW1 S S2A | Window | M SWALL S2A | Window5 Detailed Fenestration | RESWINDOW_U_0.5369_SHGC_0.25 | N/A | 3.053 | No | 7.06 | 7.06 | 7.06 | 180.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 131 | M NIWALL S2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-M NIWALL S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 132 | M EIWALL S2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | iz-M EIWALL S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 133 | iz-M EIWALL S1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | M EIWALL S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 134 | M GFLOOR S2A | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | M GFLOOR S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 135 | M CEILIN S2A | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | M CEILIN S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 136 | M INTERNALMASS S2A | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 176.50 | 176.50 | 176.50 | 0.00 | 90.00 | 176.50 | 1.00 | 0.00 | M INTERNALMASS S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 137 | T WWALL SWA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.200 | 1.017 | 18.58 | 23.22 | 18.58 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 138 | TWINDOW1 W SWA | Window | T WWALL SWA | Window5 Detailed Fenestration | RESWINDOW_U_0.5369_SHGC_0.25 | N/A | 3.053 | No | 4.65 | 4.65 | 4.65 | 270.00 | 90.00 | 3.81 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 139 | T SWALL SWA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.200 | 1.017 | 28.24 | 35.30 | 28.24 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 140 | TWINDOW1 S SWA | Window | T SWALL SWA | Window5 Detailed Fenestration | RESWINDOW_U_0.5369_SHGC_0.25 | N/A | 3.053 | No | 7.06 | 7.06 | 7.06 | 180.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 141 | T NIWALL SWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-T NIWALL SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 142 | T EIWALL SWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | iz-T EIWALL SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 143 | T GFLOOR SWA | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | T GFLOOR SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 144 | T ROOF SWA | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.283 | 0.269 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 145 | T INTERNALMASS SWA | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 88.25 | 88.25 | 88.25 | 0.00 | 90.00 | 88.25 | 1.00 | 0.00 | T INTERNALMASS SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 146 | T NWALL NWA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.200 | 1.017 | 28.24 | 35.30 | 28.24 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 147 | TWINDOW1 N NWA | Window | T NWALL NWA | Window5 Detailed Fenestration | RESWINDOW_U_0.5369_SHGC_0.25 | N/A | 3.053 | No | 7.06 | 7.06 | 7.06 | 0.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 148 | T WWALL NWA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.200 | 1.017 | 18.58 | 23.22 | 18.58 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 149 | TWINDOW1 W NWA | Window | T WWALL NWA | Window5 Detailed Fenestration | RESWINDOW_U_0.5369_SHGC_0.25 | N/A | 3.053 | No | 4.65 | 4.65 | 4.65 | 270.00 | 90.00 | 3.81 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 150 | T SIWALL NWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-T SIWALL NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 151 | T EIWALL NWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | iz-T EIWALL NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 152 | T GFLOOR NWA | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | T GFLOOR NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 153 | T ROOF NWA | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.283 | 0.269 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 154 | T INTERNALMASS NWA | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 88.25 | 88.25 | 88.25 | 0.00 | 90.00 | 88.25 | 1.00 | 0.00 | T INTERNALMASS NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 155 | T EWALL SEA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.200 | 1.017 | 18.58 | 23.22 | 18.58 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 156 | TWINDOW1 E SEA | Window | T EWALL SEA | Window5 Detailed Fenestration | RESWINDOW_U_0.5369_SHGC_0.25 | N/A | 3.053 | No | 4.65 | 4.65 | 4.65 | 90.00 | 90.00 | 3.81 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 157 | T SWALL SEA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.200 | 1.017 | 28.24 | 35.30 | 28.24 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 158 | TWINDOW1 S SEA | Window | T SWALL SEA | Window5 Detailed Fenestration | RESWINDOW_U_0.5369_SHGC_0.25 | N/A | 3.053 | No | 7.06 | 7.06 | 7.06 | 180.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 159 | T NIWALL SEA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-T NIWALL SEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 160 | iz-T EIWALL S2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | T EIWALL S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 161 | T GFLOOR SEA | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | T GFLOOR SEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 162 | T ROOF SEA | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.283 | 0.269 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 163 | T INTERNALMASS SEA | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 88.25 | 88.25 | 88.25 | 0.00 | 90.00 | 88.25 | 1.00 | 0.00 | T INTERNALMASS SEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 164 | T NWALL NEA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.200 | 1.017 | 28.24 | 35.30 | 28.24 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 165 | TWINDOW1 N NEA | Window | T NWALL NEA | Window5 Detailed Fenestration | RESWINDOW_U_0.5369_SHGC_0.25 | N/A | 3.053 | No | 7.06 | 7.06 | 7.06 | 0.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 166 | T EWALL NEA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.200 | 1.017 | 18.58 | 23.22 | 18.58 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 167 | TWINDOW1 E NEA | Window | T EWALL NEA | Window5 Detailed Fenestration | RESWINDOW_U_0.5369_SHGC_0.25 | N/A | 3.053 | No | 4.65 | 4.65 | 4.65 | 90.00 | 90.00 | 3.81 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 168 | T SIWALL NEA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-T SIWALL NEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 169 | iz-T EIWALL N2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | T EIWALL N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 170 | T GFLOOR NEA | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | T GFLOOR NEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 171 | T ROOF NEA | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.283 | 0.269 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 172 | T INTERNALMASS NEA | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 88.25 | 88.25 | 88.25 | 0.00 | 90.00 | 88.25 | 1.00 | 0.00 | T INTERNALMASS NEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 173 | T NWALL N1A | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.200 | 1.017 | 28.24 | 35.30 | 28.24 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 174 | TWINDOW1 N N1A | Window | T NWALL N1A | Window5 Detailed Fenestration | RESWINDOW_U_0.5369_SHGC_0.25 | N/A | 3.053 | No | 7.06 | 7.06 | 7.06 | 0.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 175 | T SIWALL N1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-T SIWALL N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 176 | T EIWALL N1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | iz-T EIWALL N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 177 | iz-T EIWALL NWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | T EIWALL NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 178 | T GFLOOR N1A | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | T GFLOOR N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 179 | T ROOF N1A | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.283 | 0.269 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 180 | T INTERNALMASS N1A | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 88.25 | 88.25 | 88.25 | 0.00 | 90.00 | 88.25 | 1.00 | 0.00 | T INTERNALMASS N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 181 | T NWALL N2A | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.200 | 1.017 | 28.24 | 35.30 | 28.24 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 182 | TWINDOW1 N N2A | Window | T NWALL N2A | Window5 Detailed Fenestration | RESWINDOW_U_0.5369_SHGC_0.25 | N/A | 3.053 | No | 7.06 | 7.06 | 7.06 | 0.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 183 | T SIWALL N2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-T SIWALL N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 184 | T EIWALL N2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | iz-T EIWALL N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 185 | iz-T EIWALL N1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | T EIWALL N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 186 | T GFLOOR N2A | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | T GFLOOR N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 187 | T ROOF N2A | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.283 | 0.269 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 188 | T INTERNALMASS N2A | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 88.25 | 88.25 | 88.25 | 0.00 | 90.00 | 88.25 | 1.00 | 0.00 | T INTERNALMASS N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 189 | T SWALL S1A | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.200 | 1.017 | 28.24 | 35.30 | 28.24 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 190 | TWINDOW1 S S1A | Window | T SWALL S1A | Window5 Detailed Fenestration | RESWINDOW_U_0.5369_SHGC_0.25 | N/A | 3.053 | No | 7.06 | 7.06 | 7.06 | 180.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 191 | T NIWALL S1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-T NIWALL S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 192 | T EIWALL S1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | iz-T EIWALL S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 193 | iz-T EIWALL SWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | T EIWALL SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 194 | T GFLOOR S1A | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | T GFLOOR S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 195 | T ROOF S1A | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.283 | 0.269 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 196 | T INTERNALMASS S1A | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 88.25 | 88.25 | 88.25 | 0.00 | 90.00 | 88.25 | 1.00 | 0.00 | T INTERNALMASS S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 197 | T SWALL S2A | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.200 | 1.017 | 28.24 | 35.30 | 28.24 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 198 | TWINDOW1 S S2A | Window | T SWALL S2A | Window5 Detailed Fenestration | RESWINDOW_U_0.5369_SHGC_0.25 | N/A | 3.053 | No | 7.06 | 7.06 | 7.06 | 180.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 199 | T NIWALL S2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-T NIWALL S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 200 | T EIWALL S2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | iz-T EIWALL S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 201 | iz-T EIWALL S1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | T EIWALL S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 202 | T GFLOOR S2A | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | T GFLOOR S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 203 | T ROOF S2A | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.283 | 0.269 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 204 | T INTERNALMASS S2A | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 88.25 | 88.25 | 88.25 | 0.00 | 90.00 | 88.25 | 1.00 | 0.00 | T INTERNALMASS S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 205 | T WWALL C | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.200 | 1.017 | 5.11 | 5.11 | 5.11 | 270.00 | 90.00 | 1.68 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 206 | T EWALL C | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.200 | 1.017 | 3.99 | 5.11 | 3.99 | 90.00 | 90.00 | 1.68 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 207 | TWINDOW14 | Window | T EWALL C | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5369_SHGC_0.25 | N/A | 3.053 | No | 1.11 | 1.11 | 1.11 | 90.00 | 90.00 | 0.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 208 | iz-T NIWALL SWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | T NIWALL SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 209 | iz-T NIWALL S1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | T NIWALL S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 210 | iz-T NIWALL S2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | T NIWALL S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 211 | iz-T NIWALL SEA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | T NIWALL SEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 212 | iz-T SIWALL NWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | T SIWALL NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 213 | iz-T SIWALL N1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | T SIWALL N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 214 | iz-T SIWALL N2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | T SIWALL N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 215 | iz-T SIWALL NEA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | T SIWALL NEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 216 | T FLOOR C | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 77.66 | 77.66 | 77.66 | 90.00 | 180.00 | 1.68 | 46.33 | 0.00 | T FLOOR C | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 217 | T ROOF C | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 77.66 | 77.66 | 77.66 | 180.00 | 0.00 | 46.33 | 1.68 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 218 | G WWALL C | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.844 | 0.750 | 5.11 | 5.11 | 5.11 | 270.00 | 90.00 | 1.68 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 219 | G EWALL C | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.844 | 0.750 | 1.79 | 5.11 | 1.79 | 90.00 | 90.00 | 1.68 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 220 | ENTRANCE DOOR | Window | G EWALL C | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5369_SHGC_0.25 | N/A | 3.053 | No | 3.32 | 3.32 | 3.32 | 90.00 | 90.00 | 1.57 | 2.11 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 221 | iz-G NIWALL SWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | G NIWALL SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 222 | iz-G NIWALL S1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | G NIWALL S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 223 | iz-G NIWALL S2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | G NIWALL S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 224 | iz-G NIWALL SEA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | G NIWALL SEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 225 | iz-G SIWALL NWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | G SIWALL NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 226 | iz-G SIWALL N1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | G SIWALL N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 227 | iz-G SIWALL N2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | G SIWALL N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 228 | iz-G SIWALL NEA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | G SIWALL NEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 229 | G FLOOR C | Floor | CTF - ConductionTransferFunction | GFLOORC_FFACTOR | 5.502E-002 | 5.429E-002 | 77.66 | 77.66 | 77.66 | 90.00 | 180.00 | 1.68 | 46.33 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 230 | G CEILING C | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 77.66 | 77.66 | 77.66 | 180.00 | 0.00 | 46.33 | 1.68 | 0.00 | G CEILING C | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 231 | M WWALL C | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.854 | 0.757 | 5.11 | 5.11 | 5.11 | 270.00 | 90.00 | 1.68 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 232 | M EWALL C | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.854 | 0.757 | 3.99 | 5.11 | 3.99 | 90.00 | 90.00 | 1.68 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 233 | MWINDOW14 | Window | M EWALL C | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5369_SHGC_0.25 | N/A | 3.053 | No | 1.11 | 1.11 | 1.11 | 90.00 | 90.00 | 0.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 234 | iz-M NIWALL SWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | M NIWALL SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 235 | iz-M NIWALL S1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | M NIWALL S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 236 | iz-M NIWALL S2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | M NIWALL S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 237 | iz-M NIWALL SEA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | M NIWALL SEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 238 | iz-M SIWALL NWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | M SIWALL NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 239 | iz-M SIWALL N1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | M SIWALL N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 240 | iz-M SIWALL N2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | M SIWALL N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 241 | iz-M SIWALL NEA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | M SIWALL NEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 242 | M FLOOR C | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 77.66 | 77.66 | 77.66 | 90.00 | 180.00 | 1.68 | 46.33 | 0.00 | M FLOOR C | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 243 | M CEILING C | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 77.66 | 77.66 | 77.66 | 180.00 | 0.00 | 46.33 | 1.68 | 0.00 | M CEILING C | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
| Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
| 1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | Yes | Yes | Yes | Clark and Allen |
| Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
| 1 | NEW YEAR'S DAY | Holiday | InputFile | 01/02 | 1Environment:Special Days |
| Daylight Saving Indicator | Source | Start Date | End Date | |
| 1 | Yes | InputFile | 03/12 | 11/05 |
| Style | Unit Conversion | |
| 1 | Commaandhtml | commaandhtml |
| Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
| 1 | G SW APARTMENT | RunPeriod: RUNPERIOD 1 | 7.3169179203E-005 | 3.4255695551E-004 | Pass | Pass | 1.8428655641E-002 | 2.4311342599E-002 | Pass | Pass |
| 2 | G NW APARTMENT | RunPeriod: RUNPERIOD 1 | 7.6582128347E-005 | 3.6199261492E-004 | Pass | Pass | 1.8217085785E-002 | 3.0353750957E-002 | Pass | Pass |
| 3 | OFFICE | RunPeriod: RUNPERIOD 1 | 2.1185949937E-002 | 3.4807465111E-002 | Pass | Pass | 0.2315595939 | 0.3657592383 | Pass | Pass |
| 4 | G NE APARTMENT | RunPeriod: RUNPERIOD 1 | 7.6370053744E-005 | 3.6091771206E-004 | Pass | Pass | 1.7559072712E-002 | 3.0853195083E-002 | Pass | Pass |
| 5 | G N1 APARTMENT | RunPeriod: RUNPERIOD 1 | 7.7683680217E-005 | 3.6799765439E-004 | Pass | Pass | 1.3401148852E-002 | 2.6584822995E-002 | Pass | Pass |
| 6 | G N2 APARTMENT | RunPeriod: RUNPERIOD 1 | 7.7654316068E-005 | 3.6783262055E-004 | Pass | Pass | 1.3375131934E-002 | 2.6502409969E-002 | Pass | Pass |
| 7 | G S1 APARTMENT | RunPeriod: RUNPERIOD 1 | 7.3925797447E-005 | 3.4670771198E-004 | Pass | Pass | 1.5360999800E-002 | 2.1113889568E-002 | Pass | Pass |
| 8 | G S2 APARTMENT | RunPeriod: RUNPERIOD 1 | 7.2540435018E-005 | 3.3886623296E-004 | Pass | Pass | 1.3609516514E-002 | 1.7747821116E-002 | Pass | Pass |
| 9 | M SW APARTMENT | RunPeriod: RUNPERIOD 1 | 6.8729786168E-005 | 3.2197083352E-004 | Pass | Pass | 2.4788479327E-002 | 3.4123997272E-002 | Pass | Pass |
| 10 | M NW APARTMENT | RunPeriod: RUNPERIOD 1 | 7.1888291506E-005 | 3.4003333206E-004 | Pass | Pass | 2.4459818882E-002 | 4.2917457866E-002 | Pass | Pass |
| 11 | M SE APARTMENT | RunPeriod: RUNPERIOD 1 | 6.8832577635E-005 | 3.2248381720E-004 | Pass | Pass | 2.5354140669E-002 | 3.6896265464E-002 | Pass | Pass |
| 12 | M NE APARTMENT | RunPeriod: RUNPERIOD 1 | 7.1895150180E-005 | 3.4017462471E-004 | Pass | Pass | 2.3602158139E-002 | 4.4581984335E-002 | Pass | Pass |
| 13 | M N1 APARTMENT | RunPeriod: RUNPERIOD 1 | 7.3196976982E-005 | 3.4697717921E-004 | Pass | Pass | 1.6501929424E-002 | 3.2143095889E-002 | Pass | Pass |
| 14 | M N2 APARTMENT | RunPeriod: RUNPERIOD 1 | 7.3174564820E-005 | 3.4685692326E-004 | Pass | Pass | 1.6499361039E-002 | 3.2078191665E-002 | Pass | Pass |
| 15 | M S1 APARTMENT | RunPeriod: RUNPERIOD 1 | 6.9595715111E-005 | 3.2662605118E-004 | Pass | Pass | 2.0060148359E-002 | 2.7176195274E-002 | Pass | Pass |
| 16 | M S2 APARTMENT | RunPeriod: RUNPERIOD 1 | 6.9586159307E-005 | 3.2656855779E-004 | Pass | Pass | 2.0074604512E-002 | 2.7175506677E-002 | Pass | Pass |
| 17 | T SW APARTMENT | RunPeriod: RUNPERIOD 1 | 7.5083475462E-003 | 2.3505397470E-002 | Pass | Pass | 4.0036154543E-002 | 4.8225971680E-002 | Pass | Pass |
| 18 | T NW APARTMENT | RunPeriod: RUNPERIOD 1 | 9.0469382322E-003 | 2.7522686469E-002 | Pass | Pass | 5.1797698854E-002 | 0.1102630200 | Pass | Pass |
| 19 | T SE APARTMENT | RunPeriod: RUNPERIOD 1 | 7.5813221919E-003 | 2.6130133116E-002 | Pass | Pass | 4.1702600209E-002 | 5.0577322761E-002 | Pass | Pass |
| 20 | T NE APARTMENT | RunPeriod: RUNPERIOD 1 | 9.0192863597E-003 | 2.5194213092E-002 | Pass | Pass | 3.4490569983E-002 | 5.2450275987E-002 | Pass | Pass |
| 21 | T N1 APARTMENT | RunPeriod: RUNPERIOD 1 | 4.6243199307E-003 | 1.6345240759E-002 | Pass | Pass | 3.5132170787E-002 | 4.2080548984E-002 | Pass | Pass |
| 22 | T N2 APARTMENT | RunPeriod: RUNPERIOD 1 | 4.6142339587E-003 | 1.6313887916E-002 | Pass | Pass | 3.5062479803E-002 | 4.1392168863E-002 | Pass | Pass |
| 23 | T S1 APARTMENT | RunPeriod: RUNPERIOD 1 | 3.2504348069E-003 | 1.1956947522E-002 | Pass | Pass | 3.8114685725E-002 | 5.4513077421E-002 | Pass | Pass |
| 24 | T S2 APARTMENT | RunPeriod: RUNPERIOD 1 | 3.2482071778E-003 | 1.1968610744E-002 | Pass | Pass | 3.8149449223E-002 | 5.4792643058E-002 | Pass | Pass |
| 25 | T CORRIDOR | RunPeriod: RUNPERIOD 1 | 2.4496063228E-002 | 1.6154401869E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
| 26 | G CORRIDOR | RunPeriod: RUNPERIOD 1 | 7.9870794238E-002 | 0.2211587706 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
| 27 | M CORRIDOR | RunPeriod: RUNPERIOD 1 | 6.3944833880E-003 | 4.9209441044E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 09:14:58
Heat Emission by Components| Envelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
| Heat Emissions [GJ] | 1467.30 | -94.5 | 0.00 | -2.1 | 1972.67 | 3343.40 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 09:14:58
SizingPeriod:DesignDay| Maximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
| MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 8.70 | 0.00 | 8.70 | Wetbulb [C] | 3.80 | 340.00 |
| MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 33.20 | 6.70 | 25.30 | Wetbulb [C] | 4.50 | 140.00 |
| Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
| Jan | 65.00 | 29 | |||
| Feb | 0.00 | 0 | |||
| Mar | 0.00 | 0 | |||
| Apr | 38.00 | 14 | |||
| May | 0.00 | 0 | |||
| Jun | 0.00 | 0 | |||
| Jul | 0.00 | 0 | |||
| Aug | 391.00 | 83 | |||
| Sep | 0.00 | 0 | |||
| Oct | 225.00 | 40 | |||
| Nov | 0.00 | 0 | |||
| Dec | 5.00 | 10 |
| Value | |
| None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 09:14:58
Opaque Exterior| Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
| G SWALL SWA | RES_EXT_WALL_GRD | 0.30 | 0.750 | 0.844 | 35.30 | 28.24 | 180.00 | 90.00 | S |
| G WWALL SWA | RES_EXT_WALL_GRD | 0.30 | 0.750 | 0.844 | 23.22 | 18.58 | 270.00 | 90.00 | W |
| G GFLOOR SWA | GGFLOORSWA_FFACTOR | 1.00 | 0.274 | 0.287 | 88.25 | 88.25 | 90.00 | 180.00 | |
| G NWALL NWA | RES_EXT_WALL_GRD | 0.30 | 0.750 | 0.844 | 35.30 | 28.24 | 0.00 | 90.00 | N |
| G WWALL NWA | RES_EXT_WALL_GRD | 0.30 | 0.750 | 0.844 | 23.22 | 18.58 | 270.00 | 90.00 | W |
| G GFLOOR NWA | GGFLOORNWA_FFACTOR | 1.00 | 0.274 | 0.287 | 88.25 | 88.25 | 90.00 | 180.00 | |
| G SWALL SEA | NONRES_EXT_WALL_GRD | 0.30 | 0.750 | 0.844 | 35.30 | 28.24 | 180.00 | 90.00 | S |
| G EWALL SEA | NONRES_EXT_WALL_GRD | 0.30 | 0.750 | 0.844 | 23.22 | 18.58 | 90.00 | 90.00 | E |
| G GFLOOR SEA | GGFLOORSEA_FFACTOR | 1.00 | 0.274 | 0.287 | 88.25 | 88.25 | 90.00 | 180.00 | |
| G NWALL NEA | RES_EXT_WALL_GRD | 0.30 | 0.750 | 0.844 | 35.30 | 28.24 | 0.00 | 90.00 | N |
| G EWALL NEA | RES_EXT_WALL_GRD | 0.30 | 0.750 | 0.844 | 23.22 | 18.58 | 90.00 | 90.00 | E |
| G GFLOOR NEA | GGFLOORNEA_FFACTOR | 1.00 | 0.274 | 0.287 | 88.25 | 88.25 | 90.00 | 180.00 | |
| G NWALL N1A | RES_EXT_WALL_GRD | 0.30 | 0.750 | 0.844 | 35.30 | 28.24 | 0.00 | 90.00 | N |
| G GFLOOR N1A | GGFLOORN1A_FFACTOR | 1.00 | 0.166 | 0.170 | 88.25 | 88.25 | 90.00 | 180.00 | |
| G NWALL N2A | RES_EXT_WALL_GRD | 0.30 | 0.750 | 0.844 | 35.30 | 28.24 | 0.00 | 90.00 | N |
| G GFLOOR N2A | GGFLOORN2A_FFACTOR | 1.00 | 0.166 | 0.170 | 88.25 | 88.25 | 90.00 | 180.00 | |
| G SWALL S1A | RES_EXT_WALL_GRD | 0.30 | 0.750 | 0.844 | 35.30 | 28.24 | 180.00 | 90.00 | S |
| G GFLOOR S1A | GGFLOORS1A_FFACTOR | 1.00 | 0.166 | 0.170 | 88.25 | 88.25 | 90.00 | 180.00 | |
| G SWALL S2A | RES_EXT_WALL_GRD | 0.30 | 0.750 | 0.844 | 35.30 | 28.24 | 180.00 | 90.00 | S |
| G GFLOOR S2A | GGFLOORS2A_FFACTOR | 1.00 | 0.166 | 0.170 | 88.25 | 88.25 | 90.00 | 180.00 | |
| M WWALL SWA | RES_EXT_WALL_MID | 0.30 | 0.757 | 0.854 | 46.45 | 37.16 | 270.00 | 90.00 | W |
| M SWALL SWA | RES_EXT_WALL_MID | 0.30 | 0.757 | 0.854 | 70.60 | 56.48 | 180.00 | 90.00 | S |
| M NWALL NWA | RES_EXT_WALL_MID | 0.30 | 0.757 | 0.854 | 70.60 | 56.48 | 0.00 | 90.00 | N |
| M WWALL NWA | RES_EXT_WALL_MID | 0.30 | 0.757 | 0.854 | 46.45 | 37.16 | 270.00 | 90.00 | W |
| M EWALL SEA | RES_EXT_WALL_MID | 0.30 | 0.757 | 0.854 | 46.45 | 37.16 | 90.00 | 90.00 | E |
| M SWALL SEA | RES_EXT_WALL_MID | 0.30 | 0.757 | 0.854 | 70.60 | 56.48 | 180.00 | 90.00 | S |
| M NWALL NEA | RES_EXT_WALL_MID | 0.30 | 0.757 | 0.854 | 70.60 | 56.48 | 0.00 | 90.00 | N |
| M EWALL NEA | RES_EXT_WALL_MID | 0.30 | 0.757 | 0.854 | 46.45 | 37.16 | 90.00 | 90.00 | E |
| M NWALL N1A | RES_EXT_WALL_MID | 0.30 | 0.757 | 0.854 | 70.60 | 56.48 | 0.00 | 90.00 | N |
| M NWALL N2A | RES_EXT_WALL_MID | 0.30 | 0.757 | 0.854 | 70.60 | 56.48 | 0.00 | 90.00 | N |
| M SWALL S1A | RES_EXT_WALL_MID | 0.30 | 0.757 | 0.854 | 70.60 | 56.48 | 180.00 | 90.00 | S |
| M SWALL S2A | RES_EXT_WALL_MID | 0.30 | 0.757 | 0.854 | 70.60 | 56.48 | 180.00 | 90.00 | S |
| T WWALL SWA | RES_EXT_WALL_TOP | 0.30 | 1.017 | 1.200 | 23.22 | 18.58 | 270.00 | 90.00 | W |
| T SWALL SWA | RES_EXT_WALL_TOP | 0.30 | 1.017 | 1.200 | 35.30 | 28.24 | 180.00 | 90.00 | S |
| T ROOF SWA | RES_ROOF | 0.55 | 0.273 | 0.283 | 88.25 | 88.25 | 180.00 | 0.00 | |
| T NWALL NWA | RES_EXT_WALL_TOP | 0.30 | 1.017 | 1.200 | 35.30 | 28.24 | 0.00 | 90.00 | N |
| T WWALL NWA | RES_EXT_WALL_TOP | 0.30 | 1.017 | 1.200 | 23.22 | 18.58 | 270.00 | 90.00 | W |
| T ROOF NWA | RES_ROOF | 0.55 | 0.273 | 0.283 | 88.25 | 88.25 | 180.00 | 0.00 | |
| T EWALL SEA | RES_EXT_WALL_TOP | 0.30 | 1.017 | 1.200 | 23.22 | 18.58 | 90.00 | 90.00 | E |
| T SWALL SEA | RES_EXT_WALL_TOP | 0.30 | 1.017 | 1.200 | 35.30 | 28.24 | 180.00 | 90.00 | S |
| T ROOF SEA | RES_ROOF | 0.55 | 0.273 | 0.283 | 88.25 | 88.25 | 180.00 | 0.00 | |
| T NWALL NEA | RES_EXT_WALL_TOP | 0.30 | 1.017 | 1.200 | 35.30 | 28.24 | 0.00 | 90.00 | N |
| T EWALL NEA | RES_EXT_WALL_TOP | 0.30 | 1.017 | 1.200 | 23.22 | 18.58 | 90.00 | 90.00 | E |
| T ROOF NEA | RES_ROOF | 0.55 | 0.273 | 0.283 | 88.25 | 88.25 | 180.00 | 0.00 | |
| T NWALL N1A | RES_EXT_WALL_TOP | 0.30 | 1.017 | 1.200 | 35.30 | 28.24 | 0.00 | 90.00 | N |
| T ROOF N1A | RES_ROOF | 0.55 | 0.273 | 0.283 | 88.25 | 88.25 | 180.00 | 0.00 | |
| T NWALL N2A | RES_EXT_WALL_TOP | 0.30 | 1.017 | 1.200 | 35.30 | 28.24 | 0.00 | 90.00 | N |
| T ROOF N2A | RES_ROOF | 0.55 | 0.273 | 0.283 | 88.25 | 88.25 | 180.00 | 0.00 | |
| T SWALL S1A | RES_EXT_WALL_TOP | 0.30 | 1.017 | 1.200 | 35.30 | 28.24 | 180.00 | 90.00 | S |
| T ROOF S1A | RES_ROOF | 0.55 | 0.273 | 0.283 | 88.25 | 88.25 | 180.00 | 0.00 | |
| T SWALL S2A | RES_EXT_WALL_TOP | 0.30 | 1.017 | 1.200 | 35.30 | 28.24 | 180.00 | 90.00 | S |
| T ROOF S2A | RES_ROOF | 0.55 | 0.273 | 0.283 | 88.25 | 88.25 | 180.00 | 0.00 | |
| T WWALL C | NONRES_EXT_WALL_TOP | 0.30 | 1.017 | 1.200 | 5.11 | 5.11 | 270.00 | 90.00 | W |
| T EWALL C | NONRES_EXT_WALL_TOP | 0.30 | 1.017 | 1.200 | 5.11 | 3.99 | 90.00 | 90.00 | E |
| T ROOF C | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 77.66 | 77.66 | 180.00 | 0.00 | |
| G WWALL C | NONRES_EXT_WALL_GRD | 0.30 | 0.750 | 0.844 | 5.11 | 5.11 | 270.00 | 90.00 | W |
| G EWALL C | NONRES_EXT_WALL_GRD | 0.30 | 0.750 | 0.844 | 5.11 | 1.79 | 90.00 | 90.00 | E |
| G FLOOR C | GFLOORC_FFACTOR | 1.00 | 0.055 | 0.055 | 77.66 | 77.66 | 90.00 | 180.00 | |
| M WWALL C | NONRES_EXT_WALL_MID | 0.30 | 0.757 | 0.854 | 10.22 | 10.22 | 270.00 | 90.00 | W |
| M EWALL C | NONRES_EXT_WALL_MID | 0.30 | 0.757 | 0.854 | 10.22 | 7.99 | 90.00 | 90.00 | E |
| Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
| G NIWALL SWA | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 0.00 | 90.00 | N |
| G EIWALL SWA | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 90.00 | 90.00 | E |
| G CEILIN SWA | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 88.25 | 88.25 | 180.00 | 0.00 | |
| G SIWALL NWA | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 180.00 | 90.00 | S |
| G EIWALL NWA | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 90.00 | 90.00 | E |
| G CEILIN NWA | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 88.25 | 88.25 | 180.00 | 0.00 | |
| G NIWALL SEA | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 0.00 | 90.00 | N |
| iz-G EIWALL S2A | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 270.00 | 90.00 | W |
| G CEILIN SEA | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 88.25 | 88.25 | 180.00 | 0.00 | |
| G SIWALL NEA | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 180.00 | 90.00 | S |
| iz-G EIWALL N2A | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 270.00 | 90.00 | W |
| G CEILIN NEA | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 88.25 | 88.25 | 180.00 | 0.00 | |
| G SIWALL N1A | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 180.00 | 90.00 | S |
| G EIWALL N1A | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 90.00 | 90.00 | E |
| iz-G EIWALL NWA | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 270.00 | 90.00 | W |
| G CEILIN N1A | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 88.25 | 88.25 | 180.00 | 0.00 | |
| G SIWALL N2A | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 180.00 | 90.00 | S |
| G EIWALL N2A | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 90.00 | 90.00 | E |
| iz-G EIWALL N1A | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 270.00 | 90.00 | W |
| G CEILIN N2A | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 88.25 | 88.25 | 180.00 | 0.00 | |
| G NIWALL S1A | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 0.00 | 90.00 | N |
| G EIWALL S1A | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 90.00 | 90.00 | E |
| iz-G EIWALL SWA | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 270.00 | 90.00 | W |
| G CEILIN S1A | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 88.25 | 88.25 | 180.00 | 0.00 | |
| G NIWALL S2A | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 0.00 | 90.00 | N |
| G EIWALL S2A | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 90.00 | 90.00 | E |
| iz-G EIWALL S1A | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 270.00 | 90.00 | W |
| G CEILIN S2A | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 88.25 | 88.25 | 180.00 | 0.00 | |
| M NIWALL SWA | INT_WALL | 0.30 | 2.511 | 6.299 | 70.60 | 70.60 | 0.00 | 90.00 | N |
| M EIWALL SWA | INT_WALL | 0.30 | 2.511 | 6.299 | 46.45 | 46.45 | 90.00 | 90.00 | E |
| M GFLOOR SWA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 176.50 | 176.50 | 90.00 | 180.00 | |
| M CEILIN SWA | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 176.50 | 176.50 | 180.00 | 0.00 | |
| M SIWALL NWA | INT_WALL | 0.30 | 2.511 | 6.299 | 70.60 | 70.60 | 180.00 | 90.00 | S |
| M EIWALL NWA | INT_WALL | 0.30 | 2.511 | 6.299 | 46.45 | 46.45 | 90.00 | 90.00 | E |
| M GFLOOR NWA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 176.50 | 176.50 | 90.00 | 180.00 | |
| M CEILIN NWA | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 176.50 | 176.50 | 180.00 | 0.00 | |
| M NIWALL SEA | INT_WALL | 0.30 | 2.511 | 6.299 | 70.60 | 70.60 | 0.00 | 90.00 | N |
| iz-M EIWALL S2A | INT_WALL | 0.30 | 2.511 | 6.299 | 46.45 | 46.45 | 270.00 | 90.00 | W |
| M GFLOOR SEA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 176.50 | 176.50 | 90.00 | 180.00 | |
| M CEILIN SEA | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 176.50 | 176.50 | 180.00 | 0.00 | |
| M SIWALL NEA | INT_WALL | 0.30 | 2.511 | 6.299 | 70.60 | 70.60 | 180.00 | 90.00 | S |
| iz-M EIWALL N2A | INT_WALL | 0.30 | 2.511 | 6.299 | 46.45 | 46.45 | 270.00 | 90.00 | W |
| M GFLOOR NEA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 176.50 | 176.50 | 90.00 | 180.00 | |
| M CEILIN NEA | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 176.50 | 176.50 | 180.00 | 0.00 | |
| M SIWALL N1A | INT_WALL | 0.30 | 2.511 | 6.299 | 70.60 | 70.60 | 180.00 | 90.00 | S |
| M EIWALL N1A | INT_WALL | 0.30 | 2.511 | 6.299 | 46.45 | 46.45 | 90.00 | 90.00 | E |
| iz-M EIWALL NWA | INT_WALL | 0.30 | 2.511 | 6.299 | 46.45 | 46.45 | 270.00 | 90.00 | W |
| M GFLOOR N1A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 176.50 | 176.50 | 90.00 | 180.00 | |
| M CEILIN N1A | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 176.50 | 176.50 | 180.00 | 0.00 | |
| M SIWALL N2A | INT_WALL | 0.30 | 2.511 | 6.299 | 70.60 | 70.60 | 180.00 | 90.00 | S |
| M EIWALL N2A | INT_WALL | 0.30 | 2.511 | 6.299 | 46.45 | 46.45 | 90.00 | 90.00 | E |
| iz-M EIWALL N1A | INT_WALL | 0.30 | 2.511 | 6.299 | 46.45 | 46.45 | 270.00 | 90.00 | W |
| M GFLOOR N2A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 176.50 | 176.50 | 90.00 | 180.00 | |
| M CEILIN N2A | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 176.50 | 176.50 | 180.00 | 0.00 | |
| M NIWALL S1A | INT_WALL | 0.30 | 2.511 | 6.299 | 70.60 | 70.60 | 0.00 | 90.00 | N |
| M EIWALL S1A | INT_WALL | 0.30 | 2.511 | 6.299 | 46.45 | 46.45 | 90.00 | 90.00 | E |
| iz-M EIWALL SWA | INT_WALL | 0.30 | 2.511 | 6.299 | 46.45 | 46.45 | 270.00 | 90.00 | W |
| M GFLOOR S1A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 176.50 | 176.50 | 90.00 | 180.00 | |
| M CEILIN S1A | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 176.50 | 176.50 | 180.00 | 0.00 | |
| M NIWALL S2A | INT_WALL | 0.30 | 2.511 | 6.299 | 70.60 | 70.60 | 0.00 | 90.00 | N |
| M EIWALL S2A | INT_WALL | 0.30 | 2.511 | 6.299 | 46.45 | 46.45 | 90.00 | 90.00 | E |
| iz-M EIWALL S1A | INT_WALL | 0.30 | 2.511 | 6.299 | 46.45 | 46.45 | 270.00 | 90.00 | W |
| M GFLOOR S2A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 176.50 | 176.50 | 90.00 | 180.00 | |
| M CEILIN S2A | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 176.50 | 176.50 | 180.00 | 0.00 | |
| T NIWALL SWA | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 0.00 | 90.00 | N |
| T EIWALL SWA | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 90.00 | 90.00 | E |
| T GFLOOR SWA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 88.25 | 88.25 | 90.00 | 180.00 | |
| T SIWALL NWA | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 180.00 | 90.00 | S |
| T EIWALL NWA | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 90.00 | 90.00 | E |
| T GFLOOR NWA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 88.25 | 88.25 | 90.00 | 180.00 | |
| T NIWALL SEA | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 0.00 | 90.00 | N |
| iz-T EIWALL S2A | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 270.00 | 90.00 | W |
| T GFLOOR SEA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 88.25 | 88.25 | 90.00 | 180.00 | |
| T SIWALL NEA | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 180.00 | 90.00 | S |
| iz-T EIWALL N2A | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 270.00 | 90.00 | W |
| T GFLOOR NEA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 88.25 | 88.25 | 90.00 | 180.00 | |
| T SIWALL N1A | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 180.00 | 90.00 | S |
| T EIWALL N1A | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 90.00 | 90.00 | E |
| iz-T EIWALL NWA | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 270.00 | 90.00 | W |
| T GFLOOR N1A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 88.25 | 88.25 | 90.00 | 180.00 | |
| T SIWALL N2A | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 180.00 | 90.00 | S |
| T EIWALL N2A | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 90.00 | 90.00 | E |
| iz-T EIWALL N1A | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 270.00 | 90.00 | W |
| T GFLOOR N2A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 88.25 | 88.25 | 90.00 | 180.00 | |
| T NIWALL S1A | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 0.00 | 90.00 | N |
| T EIWALL S1A | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 90.00 | 90.00 | E |
| iz-T EIWALL SWA | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 270.00 | 90.00 | W |
| T GFLOOR S1A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 88.25 | 88.25 | 90.00 | 180.00 | |
| T NIWALL S2A | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 0.00 | 90.00 | N |
| T EIWALL S2A | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 90.00 | 90.00 | E |
| iz-T EIWALL S1A | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 270.00 | 90.00 | W |
| T GFLOOR S2A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 88.25 | 88.25 | 90.00 | 180.00 | |
| iz-T NIWALL SWA | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 180.00 | 90.00 | S |
| iz-T NIWALL S1A | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 180.00 | 90.00 | S |
| iz-T NIWALL S2A | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 180.00 | 90.00 | S |
| iz-T NIWALL SEA | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 180.00 | 90.00 | S |
| iz-T SIWALL NWA | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 0.00 | 90.00 | N |
| iz-T SIWALL N1A | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 0.00 | 90.00 | N |
| iz-T SIWALL N2A | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 0.00 | 90.00 | N |
| iz-T SIWALL NEA | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 0.00 | 90.00 | N |
| T FLOOR C | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 77.66 | 77.66 | 90.00 | 180.00 | |
| iz-G NIWALL SWA | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 180.00 | 90.00 | S |
| iz-G NIWALL S1A | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 180.00 | 90.00 | S |
| iz-G NIWALL S2A | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 180.00 | 90.00 | S |
| iz-G NIWALL SEA | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 180.00 | 90.00 | S |
| iz-G SIWALL NWA | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 0.00 | 90.00 | N |
| iz-G SIWALL N1A | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 0.00 | 90.00 | N |
| iz-G SIWALL N2A | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 0.00 | 90.00 | N |
| iz-G SIWALL NEA | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 0.00 | 90.00 | N |
| G CEILING C | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 77.66 | 77.66 | 180.00 | 0.00 | |
| iz-M NIWALL SWA | INT_WALL | 0.30 | 2.511 | 6.299 | 70.60 | 70.60 | 180.00 | 90.00 | S |
| iz-M NIWALL S1A | INT_WALL | 0.30 | 2.511 | 6.299 | 70.60 | 70.60 | 180.00 | 90.00 | S |
| iz-M NIWALL S2A | INT_WALL | 0.30 | 2.511 | 6.299 | 70.60 | 70.60 | 180.00 | 90.00 | S |
| iz-M NIWALL SEA | INT_WALL | 0.30 | 2.511 | 6.299 | 70.60 | 70.60 | 180.00 | 90.00 | S |
| iz-M SIWALL NWA | INT_WALL | 0.30 | 2.511 | 6.299 | 70.60 | 70.60 | 0.00 | 90.00 | N |
| iz-M SIWALL N1A | INT_WALL | 0.30 | 2.511 | 6.299 | 70.60 | 70.60 | 0.00 | 90.00 | N |
| iz-M SIWALL N2A | INT_WALL | 0.30 | 2.511 | 6.299 | 70.60 | 70.60 | 0.00 | 90.00 | N |
| iz-M SIWALL NEA | INT_WALL | 0.30 | 2.511 | 6.299 | 70.60 | 70.60 | 0.00 | 90.00 | N |
| M FLOOR C | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 155.32 | 155.32 | 90.00 | 180.00 | |
| M CEILING C | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 155.32 | 155.32 | 180.00 | 0.00 | |
| G INTERNALMASS SWA | INTERIORFURNISHINGS | 0.30 | 0.800 | 88.25 | 0.00 | 90.00 | N | ||
| G INTERNALMASS NWA | INTERIORFURNISHINGS | 0.30 | 0.800 | 88.25 | 0.00 | 90.00 | N | ||
| G INTERNALMASS SEA | INTERIORFURNISHINGS | 0.30 | 0.800 | 88.25 | 0.00 | 90.00 | N | ||
| G INTERNALMASS NEA | INTERIORFURNISHINGS | 0.30 | 0.800 | 88.25 | 0.00 | 90.00 | N | ||
| G INTERNALMASS N1A | INTERIORFURNISHINGS | 0.30 | 0.800 | 88.25 | 0.00 | 90.00 | N | ||
| G INTERNALMASS N2A | INTERIORFURNISHINGS | 0.30 | 0.800 | 88.25 | 0.00 | 90.00 | N | ||
| G INTERNALMASS S1A | INTERIORFURNISHINGS | 0.30 | 0.800 | 88.25 | 0.00 | 90.00 | N | ||
| G INTERNALMASS S2A | INTERIORFURNISHINGS | 0.30 | 0.800 | 88.25 | 0.00 | 90.00 | N | ||
| M INTERNALMASS SWA | INTERIORFURNISHINGS | 0.30 | 0.800 | 353.00 | 0.00 | 90.00 | N | ||
| M INTERNALMASS NWA | INTERIORFURNISHINGS | 0.30 | 0.800 | 353.00 | 0.00 | 90.00 | N | ||
| M INTERNALMASS SEA | INTERIORFURNISHINGS | 0.30 | 0.800 | 353.00 | 0.00 | 90.00 | N | ||
| M INTERNALMASS NEA | INTERIORFURNISHINGS | 0.30 | 0.800 | 353.00 | 0.00 | 90.00 | N | ||
| M INTERNALMASS N1A | INTERIORFURNISHINGS | 0.30 | 0.800 | 353.00 | 0.00 | 90.00 | N | ||
| M INTERNALMASS N2A | INTERIORFURNISHINGS | 0.30 | 0.800 | 353.00 | 0.00 | 90.00 | N | ||
| M INTERNALMASS S1A | INTERIORFURNISHINGS | 0.30 | 0.800 | 353.00 | 0.00 | 90.00 | N | ||
| M INTERNALMASS S2A | INTERIORFURNISHINGS | 0.30 | 0.800 | 353.00 | 0.00 | 90.00 | N | ||
| T INTERNALMASS SWA | INTERIORFURNISHINGS | 0.30 | 0.800 | 88.25 | 0.00 | 90.00 | N | ||
| T INTERNALMASS NWA | INTERIORFURNISHINGS | 0.30 | 0.800 | 88.25 | 0.00 | 90.00 | N | ||
| T INTERNALMASS SEA | INTERIORFURNISHINGS | 0.30 | 0.800 | 88.25 | 0.00 | 90.00 | N | ||
| T INTERNALMASS NEA | INTERIORFURNISHINGS | 0.30 | 0.800 | 88.25 | 0.00 | 90.00 | N | ||
| T INTERNALMASS N1A | INTERIORFURNISHINGS | 0.30 | 0.800 | 88.25 | 0.00 | 90.00 | N | ||
| T INTERNALMASS N2A | INTERIORFURNISHINGS | 0.30 | 0.800 | 88.25 | 0.00 | 90.00 | N | ||
| T INTERNALMASS S1A | INTERIORFURNISHINGS | 0.30 | 0.800 | 88.25 | 0.00 | 90.00 | N | ||
| T INTERNALMASS S2A | INTERIORFURNISHINGS | 0.30 | 0.800 | 88.25 | 0.00 | 90.00 | N |
| Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
| GWINDOW1 S SWA | RESWINDOW_U_0.5369_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 3.053 | 0.251 | 0.251 | No | G SWALL SWA | 180.00 | 90.00 | S | |||||||
| GWINDOW1 W SWA | RESWINDOW_U_0.5369_SHGC_0.25 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 3.053 | 0.251 | 0.251 | No | G WWALL SWA | 270.00 | 90.00 | W | |||||||
| GWINDOW1 N NWA | RESWINDOW_U_0.5369_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 3.053 | 0.251 | 0.251 | No | G NWALL NWA | 0.00 | 90.00 | N | |||||||
| GWINDOW1 W NWA | RESWINDOW_U_0.5369_SHGC_0.25 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 3.053 | 0.251 | 0.251 | No | G WWALL NWA | 270.00 | 90.00 | W | |||||||
| GWINDOW1 S SEA | NONRESWINDOW_U_0.5369_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 3.053 | 0.251 | 0.251 | No | G SWALL SEA | 180.00 | 90.00 | S | |||||||
| GWINDOW1 E SEA | NONRESWINDOW_U_0.5369_SHGC_0.25 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 3.053 | 0.251 | 0.251 | No | G EWALL SEA | 90.00 | 90.00 | E | |||||||
| GWINDOW1 N NEA | RESWINDOW_U_0.5369_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 3.053 | 0.251 | 0.251 | No | G NWALL NEA | 0.00 | 90.00 | N | |||||||
| GWINDOW1 E NEA | RESWINDOW_U_0.5369_SHGC_0.25 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 3.053 | 0.251 | 0.251 | No | G EWALL NEA | 90.00 | 90.00 | E | |||||||
| GWINDOW1 N N1A | RESWINDOW_U_0.5369_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 3.053 | 0.251 | 0.251 | No | G NWALL N1A | 0.00 | 90.00 | N | |||||||
| GWINDOW1 N N2A | RESWINDOW_U_0.5369_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 3.053 | 0.251 | 0.251 | No | G NWALL N2A | 0.00 | 90.00 | N | |||||||
| GWINDOW1 S S1A | RESWINDOW_U_0.5369_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 3.053 | 0.251 | 0.251 | No | G SWALL S1A | 180.00 | 90.00 | S | |||||||
| GWINDOW1 S S2A | RESWINDOW_U_0.5369_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 3.053 | 0.251 | 0.251 | No | G SWALL S2A | 180.00 | 90.00 | S | |||||||
| MWINDOW1 W SWA | RESWINDOW_U_0.5369_SHGC_0.25 | 4.65 | 0.00 | 0.00 | 4.65 | 9.29 | 3.053 | 0.251 | 0.251 | No | M WWALL SWA | 270.00 | 90.00 | W | |||||||
| MWINDOW1 S SWA | RESWINDOW_U_0.5369_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 3.053 | 0.251 | 0.251 | No | M SWALL SWA | 180.00 | 90.00 | S | |||||||
| MWINDOW1 N NWA | RESWINDOW_U_0.5369_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 3.053 | 0.251 | 0.251 | No | M NWALL NWA | 0.00 | 90.00 | N | |||||||
| MWINDOW1 W NWA | RESWINDOW_U_0.5369_SHGC_0.25 | 4.65 | 0.00 | 0.00 | 4.65 | 9.29 | 3.053 | 0.251 | 0.251 | No | M WWALL NWA | 270.00 | 90.00 | W | |||||||
| MWINDOW1 E SEA | RESWINDOW_U_0.5369_SHGC_0.25 | 4.65 | 0.00 | 0.00 | 4.65 | 9.29 | 3.053 | 0.251 | 0.251 | No | M EWALL SEA | 90.00 | 90.00 | E | |||||||
| MWINDOW1 S SEA | RESWINDOW_U_0.5369_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 3.053 | 0.251 | 0.251 | No | M SWALL SEA | 180.00 | 90.00 | S | |||||||
| MWINDOW1 N NEA | RESWINDOW_U_0.5369_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 3.053 | 0.251 | 0.251 | No | M NWALL NEA | 0.00 | 90.00 | N | |||||||
| MWINDOW1 E NEA | RESWINDOW_U_0.5369_SHGC_0.25 | 4.65 | 0.00 | 0.00 | 4.65 | 9.29 | 3.053 | 0.251 | 0.251 | No | M EWALL NEA | 90.00 | 90.00 | E | |||||||
| MWINDOW1 N N1A | RESWINDOW_U_0.5369_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 3.053 | 0.251 | 0.251 | No | M NWALL N1A | 0.00 | 90.00 | N | |||||||
| MWINDOW1 N N2A | RESWINDOW_U_0.5369_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 3.053 | 0.251 | 0.251 | No | M NWALL N2A | 0.00 | 90.00 | N | |||||||
| MWINDOW1 S S1A | RESWINDOW_U_0.5369_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 3.053 | 0.251 | 0.251 | No | M SWALL S1A | 180.00 | 90.00 | S | |||||||
| MWINDOW1 S S2A | RESWINDOW_U_0.5369_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 3.053 | 0.251 | 0.251 | No | M SWALL S2A | 180.00 | 90.00 | S | |||||||
| TWINDOW1 W SWA | RESWINDOW_U_0.5369_SHGC_0.25 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 3.053 | 0.251 | 0.251 | No | T WWALL SWA | 270.00 | 90.00 | W | |||||||
| TWINDOW1 S SWA | RESWINDOW_U_0.5369_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 3.053 | 0.251 | 0.251 | No | T SWALL SWA | 180.00 | 90.00 | S | |||||||
| TWINDOW1 N NWA | RESWINDOW_U_0.5369_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 3.053 | 0.251 | 0.251 | No | T NWALL NWA | 0.00 | 90.00 | N | |||||||
| TWINDOW1 W NWA | RESWINDOW_U_0.5369_SHGC_0.25 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 3.053 | 0.251 | 0.251 | No | T WWALL NWA | 270.00 | 90.00 | W | |||||||
| TWINDOW1 E SEA | RESWINDOW_U_0.5369_SHGC_0.25 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 3.053 | 0.251 | 0.251 | No | T EWALL SEA | 90.00 | 90.00 | E | |||||||
| TWINDOW1 S SEA | RESWINDOW_U_0.5369_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 3.053 | 0.251 | 0.251 | No | T SWALL SEA | 180.00 | 90.00 | S | |||||||
| TWINDOW1 N NEA | RESWINDOW_U_0.5369_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 3.053 | 0.251 | 0.251 | No | T NWALL NEA | 0.00 | 90.00 | N | |||||||
| TWINDOW1 E NEA | RESWINDOW_U_0.5369_SHGC_0.25 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 3.053 | 0.251 | 0.251 | No | T EWALL NEA | 90.00 | 90.00 | E | |||||||
| TWINDOW1 N N1A | RESWINDOW_U_0.5369_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 3.053 | 0.251 | 0.251 | No | T NWALL N1A | 0.00 | 90.00 | N | |||||||
| TWINDOW1 N N2A | RESWINDOW_U_0.5369_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 3.053 | 0.251 | 0.251 | No | T NWALL N2A | 0.00 | 90.00 | N | |||||||
| TWINDOW1 S S1A | RESWINDOW_U_0.5369_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 3.053 | 0.251 | 0.251 | No | T SWALL S1A | 180.00 | 90.00 | S | |||||||
| TWINDOW1 S S2A | RESWINDOW_U_0.5369_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 3.053 | 0.251 | 0.251 | No | T SWALL S2A | 180.00 | 90.00 | S | |||||||
| TWINDOW14 | NONRESWINDOW_U_0.5369_SHGC_0.25 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 3.053 | 0.251 | 0.251 | No | T EWALL C | 90.00 | 90.00 | E | |||||||
| ENTRANCE DOOR | NONRESWINDOW_U_0.5369_SHGC_0.25 | 3.32 | 0.00 | 0.00 | 3.32 | 3.32 | 3.053 | 0.251 | 0.251 | No | G EWALL C | 90.00 | 90.00 | E | |||||||
| MWINDOW14 | NONRESWINDOW_U_0.5369_SHGC_0.25 | 1.11 | 0.00 | 0.00 | 1.11 | 2.23 | 3.053 | 0.251 | 0.251 | No | M EWALL C | 90.00 | 90.00 | E | |||||||
| Total or Average | 306.92 | 3.053 | 0.251 | 0.251 | |||||||||||||||||
| North Total or Average | 112.97 | 3.053 | 0.251 | 0.251 | |||||||||||||||||
| Non-North Total or Average | 193.95 | 3.053 | 0.251 | 0.251 |
| Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
| None |
| Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
| Total or Average | 0.00 | - | - | - |
| Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
| None |
| Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
| None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 09:14:58
Sunlit Fraction| March 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
| GWINDOW1 S SWA | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
| GWINDOW1 W SWA | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
| GWINDOW1 N NWA | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
| GWINDOW1 W NWA | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
| GWINDOW1 S SEA | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
| GWINDOW1 E SEA | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
| GWINDOW1 N NEA | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
| GWINDOW1 E NEA | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
| GWINDOW1 N N1A | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
| GWINDOW1 N N2A | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
| GWINDOW1 S S1A | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
| GWINDOW1 S S2A | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
| MWINDOW1 W SWA | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
| MWINDOW1 S SWA | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
| MWINDOW1 N NWA | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
| MWINDOW1 W NWA | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
| MWINDOW1 E SEA | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
| MWINDOW1 S SEA | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
| MWINDOW1 N NEA | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
| MWINDOW1 E NEA | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
| MWINDOW1 N N1A | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
| MWINDOW1 N N2A | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
| MWINDOW1 S S1A | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
| MWINDOW1 S S2A | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
| TWINDOW1 W SWA | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
| TWINDOW1 S SWA | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
| TWINDOW1 N NWA | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
| TWINDOW1 W NWA | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
| TWINDOW1 E SEA | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
| TWINDOW1 S SEA | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
| TWINDOW1 N NEA | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
| TWINDOW1 E NEA | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
| TWINDOW1 N N1A | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
| TWINDOW1 N N2A | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
| TWINDOW1 S S1A | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
| TWINDOW1 S S2A | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
| TWINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
| ENTRANCE DOOR | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
| MWINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
| Name | Type | Shaded Construction | Control | Glare Control | |
| None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 09:14:58
Interior Lighting| Zone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
| LIGHTING_HARDWIRED_GSW | G SW APARTMENT | G SW APARTMENT | GENERAL | 7.8684 | 88.25 | 694.38 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.32 |
| LIGHTING_HARDWIRED_GNW | G NW APARTMENT | G NW APARTMENT | GENERAL | 7.8684 | 88.25 | 694.38 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.32 |
| LIGHTING_HARDWIRED_OFFICE | OFFICE | OFFICE | GENERAL | 9.7532 | 88.25 | 860.71 | LightsWired | LTG_SCH_OFFICE | 46.69 | 168.00 | 45.77 | 0.0000 | Y | 7.40 |
| LIGHTING_HARDWIRED_GNE | G NE APARTMENT | G NE APARTMENT | GENERAL | 7.8684 | 88.25 | 694.38 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.32 |
| LIGHTING_HARDWIRED_GN1 | G N1 APARTMENT | G N1 APARTMENT | GENERAL | 7.8684 | 88.25 | 694.38 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.32 |
| LIGHTING_HARDWIRED_GN2 | G N2 APARTMENT | G N2 APARTMENT | GENERAL | 7.8684 | 88.25 | 694.38 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.32 |
| LIGHTING_HARDWIRED_GS1 | G S1 APARTMENT | G S1 APARTMENT | GENERAL | 7.8684 | 88.25 | 694.38 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.32 |
| LIGHTING_HARDWIRED_GS2 | G S2 APARTMENT | G S2 APARTMENT | GENERAL | 7.8684 | 88.25 | 694.38 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.32 |
| LIGHTING_HARDWIRED_MSW | M SW APARTMENT | M SW APARTMENT | GENERAL | 7.8684 | 176.50 | 1388.76 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 2.63 |
| LIGHTING_HARDWIRED_MNW | M NW APARTMENT | M NW APARTMENT | GENERAL | 7.8684 | 176.50 | 1388.76 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 2.63 |
| LIGHTING_HARDWIRED_MSE | M SE APARTMENT | M SE APARTMENT | GENERAL | 7.8684 | 176.50 | 1388.76 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 2.63 |
| LIGHTING_HARDWIRED_MNE | M NE APARTMENT | M NE APARTMENT | GENERAL | 7.8684 | 176.50 | 1388.76 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 2.63 |
| LIGHTING_HARDWIRED_MN1 | M N1 APARTMENT | M N1 APARTMENT | GENERAL | 7.8684 | 176.50 | 1388.76 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 2.63 |
| LIGHTING_HARDWIRED_MN2 | M N2 APARTMENT | M N2 APARTMENT | GENERAL | 7.8684 | 176.50 | 1388.76 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 2.63 |
| LIGHTING_HARDWIRED_MS1 | M S1 APARTMENT | M S1 APARTMENT | GENERAL | 7.8684 | 176.50 | 1388.76 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 2.63 |
| LIGHTING_HARDWIRED_MS2 | M S2 APARTMENT | M S2 APARTMENT | GENERAL | 7.8684 | 176.50 | 1388.76 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 2.63 |
| LIGHTING_HARDWIRED_TSW | T SW APARTMENT | T SW APARTMENT | GENERAL | 7.8684 | 88.25 | 694.38 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.32 |
| LIGHTING_HARDWIRED_TNW | T NW APARTMENT | T NW APARTMENT | GENERAL | 7.8684 | 88.25 | 694.38 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.32 |
| LIGHTING_HARDWIRED_TSE | T SE APARTMENT | T SE APARTMENT | GENERAL | 7.8684 | 88.25 | 694.38 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.32 |
| LIGHTING_HARDWIRED_TNE | T NE APARTMENT | T NE APARTMENT | GENERAL | 7.8684 | 88.25 | 694.38 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.32 |
| LIGHTING_HARDWIRED_TN1 | T N1 APARTMENT | T N1 APARTMENT | GENERAL | 7.8684 | 88.25 | 694.38 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.32 |
| LIGHTING_HARDWIRED_TN2 | T N2 APARTMENT | T N2 APARTMENT | GENERAL | 7.8684 | 88.25 | 694.38 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.32 |
| LIGHTING_HARDWIRED_TS1 | T S1 APARTMENT | T S1 APARTMENT | GENERAL | 7.8684 | 88.25 | 694.38 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.32 |
| LIGHTING_HARDWIRED_TS2 | T S2 APARTMENT | T S2 APARTMENT | GENERAL | 7.8684 | 88.25 | 694.38 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.32 |
| LIGHTING_HARDWIRED_GC | G CORRIDOR | G CORRIDOR | GENERAL | 4.7725 | 77.66 | 370.63 | LightsWired | LTG_SCH_CORRIDOR | 168.00 | 168.00 | 168.00 | 0.0000 | N | 11.69 |
| LIGHTING_HARDWIRED_MC | M CORRIDOR | M CORRIDOR | GENERAL | 4.7725 | 155.32 | 741.26 | LightsWired | LTG_SCH_CORRIDOR | 168.00 | 168.00 | 168.00 | 0.0000 | N | 23.38 |
| LIGHTING_HARDWIRED_TC | T CORRIDOR | T CORRIDOR | GENERAL | 4.7725 | 77.66 | 370.63 | LightsWired | LTG_SCH_CORRIDOR | 168.00 | 168.00 | 168.00 | 0.0000 | N | 11.69 |
| LIGHTING_PLUGIN_GSW | G SW APARTMENT | G SW APARTMENT | GENERAL | 0.8234 | 88.25 | 72.67 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.14 |
| LIGHTING_PLUGIN_GNW | G NW APARTMENT | G NW APARTMENT | GENERAL | 0.8234 | 88.25 | 72.67 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.14 |
| LIGHTING_PLUGIN_GNE | G NE APARTMENT | G NE APARTMENT | GENERAL | 0.8234 | 88.25 | 72.67 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.14 |
| LIGHTING_PLUGIN_GN1 | G N1 APARTMENT | G N1 APARTMENT | GENERAL | 0.8234 | 88.25 | 72.67 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.14 |
| LIGHTING_PLUGIN_GN2 | G N2 APARTMENT | G N2 APARTMENT | GENERAL | 0.8234 | 88.25 | 72.67 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.14 |
| LIGHTING_PLUGIN_GS1 | G S1 APARTMENT | G S1 APARTMENT | GENERAL | 0.8234 | 88.25 | 72.67 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.14 |
| LIGHTING_PLUGIN_GS2 | G S2 APARTMENT | G S2 APARTMENT | GENERAL | 0.8234 | 88.25 | 72.67 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.14 |
| LIGHTING_PLUGIN_MSW | M SW APARTMENT | M SW APARTMENT | GENERAL | 0.8234 | 176.50 | 145.34 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.28 |
| LIGHTING_PLUGIN_MNW | M NW APARTMENT | M NW APARTMENT | GENERAL | 0.8234 | 176.50 | 145.34 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.28 |
| LIGHTING_PLUGIN_MSE | M SE APARTMENT | M SE APARTMENT | GENERAL | 0.8234 | 176.50 | 145.34 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.28 |
| LIGHTING_PLUGIN_MNE | M NE APARTMENT | M NE APARTMENT | GENERAL | 0.8234 | 176.50 | 145.34 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.28 |
| LIGHTING_PLUGIN_MN1 | M N1 APARTMENT | M N1 APARTMENT | GENERAL | 0.8234 | 176.50 | 145.34 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.28 |
| LIGHTING_PLUGIN_MN2 | M N2 APARTMENT | M N2 APARTMENT | GENERAL | 0.8234 | 176.50 | 145.34 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.28 |
| LIGHTING_PLUGIN_MS1 | M S1 APARTMENT | M S1 APARTMENT | GENERAL | 0.8234 | 176.50 | 145.34 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.28 |
| LIGHTING_PLUGIN_MS2 | M S2 APARTMENT | M S2 APARTMENT | GENERAL | 0.8234 | 176.50 | 145.34 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.28 |
| LIGHTING_PLUGIN_TSW | T SW APARTMENT | T SW APARTMENT | GENERAL | 0.8234 | 88.25 | 72.67 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.14 |
| LIGHTING_PLUGIN_TNW | T NW APARTMENT | T NW APARTMENT | GENERAL | 0.8234 | 88.25 | 72.67 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.14 |
| LIGHTING_PLUGIN_TSE | T SE APARTMENT | T SE APARTMENT | GENERAL | 0.8234 | 88.25 | 72.67 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.14 |
| LIGHTING_PLUGIN_TNE | T NE APARTMENT | T NE APARTMENT | GENERAL | 0.8234 | 88.25 | 72.67 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.14 |
| LIGHTING_PLUGIN_TN1 | T N1 APARTMENT | T N1 APARTMENT | GENERAL | 0.8234 | 88.25 | 72.67 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.14 |
| LIGHTING_PLUGIN_TN2 | T N2 APARTMENT | T N2 APARTMENT | GENERAL | 0.8234 | 88.25 | 72.67 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.14 |
| LIGHTING_PLUGIN_TS1 | T S1 APARTMENT | T S1 APARTMENT | GENERAL | 0.8234 | 88.25 | 72.67 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.14 |
| LIGHTING_PLUGIN_TS2 | T S2 APARTMENT | T S2 APARTMENT | GENERAL | 0.8234 | 88.25 | 72.67 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.14 |
| Interior Lighting Total | 4.4498 | 5870.34 | 26121.74 | 75.91 |
| Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
| None |
| Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
| FACADE LIGHTING | 3183.33 | AstronomicalClock | - | 83.82 | 83.82 | 50.09 | |
| Exterior Lighting Total | 3183.33 | 50.09 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 09:14:58
Central Plant| Type | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
| None |
| Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
| SPLIT GSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 6608.03 | 5265.78 | 1342.25 | 0.80 | 3.91 | |||
| SPLIT GNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 6661.49 | 5320.69 | 1340.80 | 0.80 | 3.91 | |||
| SPLIT OFFICE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7123.34 | 5663.12 | 1460.22 | 0.80 | 3.91 | |||
| SPLIT GNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 6270.12 | 4959.80 | 1310.32 | 0.79 | 3.91 | |||
| SPLIT GN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5664.08 | 4490.62 | 1173.46 | 0.79 | 3.91 | |||
| SPLIT GN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5656.58 | 4483.98 | 1172.60 | 0.79 | 3.91 | |||
| SPLIT GS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5631.64 | 4442.64 | 1189.00 | 0.79 | 3.91 | |||
| SPLIT GS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5664.10 | 4470.84 | 1193.26 | 0.79 | 3.91 | |||
| SPLIT MSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 15069.96 | 12034.41 | 3035.55 | 0.80 | 3.91 | |||
| SPLIT MNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 15225.10 | 12182.28 | 3042.81 | 0.80 | 3.91 | |||
| SPLIT MSE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 14034.46 | 11087.45 | 2947.01 | 0.79 | 3.91 | |||
| SPLIT MNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 14180.79 | 11244.50 | 2936.28 | 0.79 | 3.91 | |||
| SPLIT MN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 12700.74 | 10101.53 | 2599.21 | 0.80 | 3.91 | |||
| SPLIT MN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 12682.31 | 10085.23 | 2597.08 | 0.80 | 3.91 | |||
| SPLIT MS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 12578.74 | 9973.10 | 2605.64 | 0.79 | 3.91 | |||
| SPLIT MS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 12560.38 | 9956.77 | 2603.60 | 0.79 | 3.91 | |||
| SPLIT TSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 8421.94 | 6727.92 | 1694.02 | 0.80 | 3.91 | |||
| SPLIT TNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 8585.83 | 6875.50 | 1710.33 | 0.80 | 3.91 | |||
| SPLIT TSE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7618.33 | 6010.56 | 1607.77 | 0.79 | 3.91 | |||
| SPLIT TNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7777.14 | 6161.92 | 1615.22 | 0.79 | 3.91 | |||
| SPLIT TN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7076.41 | 5662.71 | 1413.69 | 0.80 | 3.91 | |||
| SPLIT TN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7051.44 | 5647.85 | 1403.59 | 0.80 | 3.91 | |||
| SPLIT TS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 6922.54 | 5521.44 | 1401.10 | 0.80 | 3.91 | |||
| SPLIT TS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 6897.77 | 5499.66 | 1398.12 | 0.80 | 3.91 |
| DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
| SPLIT GSW COOLING COIL | 6335.3 | 3.21 | 10.96 | 11.40 | 10.78 | 10.79 | |
| SPLIT GNW COOLING COIL | 6385.0 | 3.21 | 10.95 | 11.39 | 10.77 | 10.78 | |
| SPLIT OFFICE COOLING COIL | 6830.1 | 3.21 | 10.96 | 11.41 | 10.79 | 10.80 | |
| SPLIT GNE COOLING COIL | 6014.4 | 3.22 | 10.98 | 11.43 | 10.81 | 10.83 | |
| SPLIT GN1 COOLING COIL | 5432.5 | 3.22 | 10.98 | 11.42 | 10.80 | 10.82 | |
| SPLIT GN2 COOLING COIL | 5425.4 | 3.22 | 10.98 | 11.42 | 10.80 | 10.82 | |
| SPLIT GS1 COOLING COIL | 5403.5 | 3.22 | 10.99 | 11.44 | 10.82 | 10.85 | |
| SPLIT GS2 COOLING COIL | 5434.3 | 3.22 | 10.99 | 11.44 | 10.82 | 10.84 | |
| SPLIT MSW COOLING COIL | 14444.8 | 3.21 | 10.95 | 11.39 | 10.77 | 10.78 | |
| SPLIT MNW COOLING COIL | 14590.4 | 3.21 | 10.94 | 11.38 | 10.76 | 10.76 | |
| SPLIT MSE COOLING COIL | 13463.9 | 3.22 | 10.99 | 11.43 | 10.81 | 10.84 | |
| SPLIT MNE COOLING COIL | 13600.8 | 3.22 | 10.98 | 11.42 | 10.80 | 10.82 | |
| SPLIT MN1 COOLING COIL | 12177.4 | 3.21 | 10.96 | 11.40 | 10.79 | 10.80 | |
| SPLIT MN2 COOLING COIL | 12160.0 | 3.21 | 10.96 | 11.40 | 10.79 | 10.80 | |
| SPLIT MS1 COOLING COIL | 12064.4 | 3.22 | 10.98 | 11.42 | 10.80 | 10.82 | |
| SPLIT MS2 COOLING COIL | 12047.0 | 3.22 | 10.98 | 11.42 | 10.80 | 10.82 | |
| SPLIT TSW COOLING COIL | 8072.2 | 3.21 | 10.95 | 11.39 | 10.77 | 10.78 | |
| SPLIT TNW COOLING COIL | 8227.2 | 3.20 | 10.93 | 11.37 | 10.76 | 10.76 | |
| SPLIT TSE COOLING COIL | 7309.6 | 3.22 | 10.99 | 11.44 | 10.82 | 10.85 | |
| SPLIT TNE COOLING COIL | 7459.7 | 3.22 | 10.98 | 11.42 | 10.81 | 10.83 | |
| SPLIT TN1 COOLING COIL | 6781.3 | 3.21 | 10.94 | 11.38 | 10.76 | 10.76 | |
| SPLIT TN2 COOLING COIL | 6757.7 | 3.21 | 10.94 | 11.38 | 10.76 | 10.77 | |
| SPLIT TS1 COOLING COIL | 6636.2 | 3.21 | 10.95 | 11.39 | 10.78 | 10.79 | |
| SPLIT TS2 COOLING COIL | 6612.7 | 3.21 | 10.95 | 11.40 | 10.78 | 10.79 |
| DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
| SPLIT GSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT GNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT OFFICE COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT GNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT GN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT GN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT GS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT GS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT MSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT MNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT MSE COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT MNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT MN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT MN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT MS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT MS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT TSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT TNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT TSE COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT TNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT TN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT TN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT TS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT TS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed |
| DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
| None |
| Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
| SPLIT GSW HEATING COIL | Coil:Heating:Fuel | 8322.47 | 0.80 | |
| SPLIT GNW HEATING COIL | Coil:Heating:Fuel | 8432.74 | 0.80 | |
| SPLIT OFFICE HEATING COIL | Coil:Heating:Fuel | 9100.04 | 0.80 | |
| SPLIT GNE HEATING COIL | Coil:Heating:Fuel | 7825.98 | 0.80 | |
| SPLIT GN1 HEATING COIL | Coil:Heating:Fuel | 7124.20 | 0.80 | |
| SPLIT GN2 HEATING COIL | Coil:Heating:Fuel | 7112.66 | 0.80 | |
| SPLIT GS1 HEATING COIL | Coil:Heating:Fuel | 7023.27 | 0.80 | |
| SPLIT GS2 HEATING COIL | Coil:Heating:Fuel | 7071.25 | 0.80 | |
| SPLIT MSW HEATING COIL | Coil:Heating:Fuel | 18966.56 | 0.80 | |
| SPLIT MNW HEATING COIL | Coil:Heating:Fuel | 19243.60 | 0.80 | |
| SPLIT MSE HEATING COIL | Coil:Heating:Fuel | 17371.56 | 0.80 | |
| SPLIT MNE HEATING COIL | Coil:Heating:Fuel | 17646.73 | 0.80 | |
| SPLIT MN1 HEATING COIL | Coil:Heating:Fuel | 16000.98 | 0.80 | |
| SPLIT MN2 HEATING COIL | Coil:Heating:Fuel | 15972.70 | 0.80 | |
| SPLIT MS1 HEATING COIL | Coil:Heating:Fuel | 15737.07 | 0.80 | |
| SPLIT MS2 HEATING COIL | Coil:Heating:Fuel | 15708.58 | 0.80 | |
| SPLIT TSW HEATING COIL | Coil:Heating:Fuel | 10562.93 | 0.80 | |
| SPLIT TNW HEATING COIL | Coil:Heating:Fuel | 10823.29 | 0.80 | |
| SPLIT TSE HEATING COIL | Coil:Heating:Fuel | 9366.36 | 0.80 | |
| SPLIT TNE HEATING COIL | Coil:Heating:Fuel | 9622.02 | 0.80 | |
| SPLIT TN1 HEATING COIL | Coil:Heating:Fuel | 8973.63 | 0.80 | |
| SPLIT TN2 HEATING COIL | Coil:Heating:Fuel | 8936.08 | 0.80 | |
| SPLIT TS1 HEATING COIL | Coil:Heating:Fuel | 8718.99 | 0.80 | |
| SPLIT TS2 HEATING COIL | Coil:Heating:Fuel | 8681.56 | 0.80 |
| Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
| G SW APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| G SW APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| G NW APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| G NW APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| G NE APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| G NE APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| G N1 APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| G N1 APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| G N2 APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| G N2 APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| G S1 APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| G S1 APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| G S2 APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| G S2 APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| M SW APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.05 | 40.01 | 770.84 | 1.00 | 4.13 | General | ||
| M SW APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.05 | 40.01 | 770.84 | 1.00 | 4.13 | General | ||
| M NW APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.05 | 40.01 | 770.84 | 1.00 | 4.13 | General | ||
| M NW APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.05 | 40.01 | 770.84 | 1.00 | 4.13 | General | ||
| M SE APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.05 | 40.01 | 770.84 | 1.00 | 4.13 | General | ||
| M SE APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.05 | 40.01 | 770.84 | 1.00 | 4.13 | General | ||
| M NE APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.05 | 40.01 | 770.84 | 1.00 | 4.13 | General | ||
| M NE APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.05 | 40.01 | 770.84 | 1.00 | 4.13 | General | ||
| M N1 APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.05 | 40.01 | 770.84 | 1.00 | 4.13 | General | ||
| M N1 APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.05 | 40.01 | 770.84 | 1.00 | 4.13 | General | ||
| M N2 APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.05 | 40.01 | 770.84 | 1.00 | 4.13 | General | ||
| M N2 APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.05 | 40.01 | 770.84 | 1.00 | 4.13 | General | ||
| M S1 APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.05 | 40.01 | 770.84 | 1.00 | 4.13 | General | ||
| M S1 APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.05 | 40.01 | 770.84 | 1.00 | 4.13 | General | ||
| M S2 APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.05 | 40.01 | 770.84 | 1.00 | 4.13 | General | ||
| M S2 APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.05 | 40.01 | 770.84 | 1.00 | 4.13 | General | ||
| T SW APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| T SW APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| T NW APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| T NW APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| T SE APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| T SE APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| T NE APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| T NE APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| T N1 APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| T N1 APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| T N2 APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| T N2 APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| T S1 APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| T S1 APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| T S2 APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| T S2 APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| SPLIT GSW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.35 | 389.03 | 1120.11 | 1.00 | 1.80 | General | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 |
| SPLIT GNW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.35 | 394.44 | 1120.11 | 1.00 | 1.79 | General | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 |
| SPLIT OFFICE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.37 | 418.23 | 1120.11 | 1.00 | 1.76 | General | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 09:20:00 |
| SPLIT GNE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.33 | 364.69 | 1120.11 | 1.00 | 1.84 | General | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 |
| SPLIT GN1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.29 | 330.28 | 1120.11 | 1.00 | 1.91 | General | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 |
| SPLIT GN2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.29 | 329.71 | 1120.11 | 1.00 | 1.91 | General | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 |
| SPLIT GS1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.29 | 325.32 | 1120.11 | 1.00 | 1.92 | General | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 |
| SPLIT GS2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.29 | 327.67 | 1120.11 | 1.00 | 1.91 | General | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 |
| SPLIT MSW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.80 | 891.90 | 1120.11 | 1.00 | 1.43 | General | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 |
| SPLIT MNW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.81 | 905.49 | 1120.11 | 1.00 | 1.43 | General | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 |
| SPLIT MSE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.73 | 813.68 | 1120.11 | 1.00 | 1.46 | General | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 |
| SPLIT MNE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.74 | 827.19 | 1120.11 | 1.00 | 1.46 | General | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 |
| SPLIT MN1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.67 | 746.49 | 1120.11 | 1.00 | 1.49 | General | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 |
| SPLIT MN2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.67 | 745.10 | 1120.11 | 1.00 | 1.49 | General | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 |
| SPLIT MS1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.65 | 733.54 | 1120.11 | 1.00 | 1.50 | General | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 |
| SPLIT MS2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.65 | 732.14 | 1120.11 | 1.00 | 1.50 | General | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 |
| SPLIT TSW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.45 | 498.89 | 1120.11 | 1.00 | 1.66 | General | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 |
| SPLIT TNW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.46 | 511.66 | 1120.11 | 1.00 | 1.65 | General | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 |
| SPLIT TSE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.39 | 440.21 | 1120.11 | 1.00 | 1.73 | General | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 |
| SPLIT TNE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.40 | 452.75 | 1120.11 | 1.00 | 1.71 | General | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 |
| SPLIT TN1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.38 | 420.96 | 1120.11 | 1.00 | 1.75 | General | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 |
| SPLIT TN2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.37 | 419.12 | 1120.11 | 1.00 | 1.75 | General | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 |
| SPLIT TS1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.36 | 408.47 | 1120.11 | 1.00 | 1.77 | General | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 |
| SPLIT TS2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.36 | 406.64 | 1120.11 | 1.00 | 1.77 | General | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 |
| Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
| None |
| Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
| G SW APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.77 |
| G NW APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.77 |
| G NE APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.77 |
| G N1 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.77 |
| G N2 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.77 |
| G S1 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.77 |
| G S2 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.77 |
| M SW APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.79 |
| M NW APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.79 |
| M SE APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.79 |
| M NE APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.79 |
| M N1 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.79 |
| M N2 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.79 |
| M S1 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.79 |
| M S2 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.79 |
| T SW APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.77 |
| T NW APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.77 |
| T SE APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.77 |
| T NE APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.77 |
| T N1 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.77 |
| T N2 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.77 |
| T S1 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.77 |
| T S2 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.77 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 09:14:58
Zone Sensible Cooling| Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
| G SW APARTMENT | 4094.26 | 4913.12 | 55.67 | 0.289 | 0.347 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 24.00 | 24.00 | 0.00859 | 30.59 | 0.01716 | 0.026 | 0.00 |
| G NW APARTMENT | 4149.67 | 4979.60 | 56.43 | 0.293 | 0.352 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 24.00 | 24.00 | 0.00855 | 30.59 | 0.01716 | 0.026 | 0.00 |
| OFFICE | 4340.52 | 5208.62 | 59.02 | 0.311 | 0.373 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 23.90 | 23.90 | 0.00841 | 29.52 | 0.01716 | 0.038 | 0.00 |
| G NE APARTMENT | 3843.75 | 4612.50 | 52.27 | 0.271 | 0.326 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 24.00 | 24.00 | 0.00863 | 30.59 | 0.01716 | 0.026 | 0.00 |
| G N1 APARTMENT | 3489.24 | 4187.09 | 47.45 | 0.246 | 0.295 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 24.00 | 24.00 | 0.00851 | 30.59 | 0.01716 | 0.026 | 0.00 |
| G N2 APARTMENT | 3483.43 | 4180.12 | 47.37 | 0.245 | 0.294 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 24.00 | 24.00 | 0.00851 | 30.59 | 0.01716 | 0.026 | 0.00 |
| G S1 APARTMENT | 3438.36 | 4126.03 | 46.75 | 0.242 | 0.290 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 24.00 | 24.00 | 0.00857 | 30.59 | 0.01716 | 0.026 | 0.00 |
| G S2 APARTMENT | 3462.43 | 4154.92 | 47.08 | 0.244 | 0.293 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 24.00 | 24.00 | 0.00856 | 30.59 | 0.01716 | 0.026 | 0.00 |
| M SW APARTMENT | 9356.00 | 11227.20 | 127.22 | 0.664 | 0.796 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 24.00 | 24.00 | 0.00866 | 30.59 | 0.01716 | 0.052 | 0.00 |
| M NW APARTMENT | 9495.86 | 11395.03 | 129.12 | 0.674 | 0.808 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 24.00 | 24.00 | 0.00863 | 30.59 | 0.01716 | 0.052 | 0.00 |
| M SE APARTMENT | 8552.82 | 10263.38 | 116.30 | 0.605 | 0.726 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 24.00 | 24.00 | 0.00875 | 30.59 | 0.01716 | 0.052 | 0.00 |
| M NE APARTMENT | 8691.27 | 10429.53 | 118.18 | 0.615 | 0.738 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 24.00 | 24.00 | 0.00871 | 30.59 | 0.01716 | 0.052 | 0.00 |
| M N1 APARTMENT | 7865.68 | 9438.82 | 106.96 | 0.555 | 0.666 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 24.00 | 24.00 | 0.00856 | 30.59 | 0.01716 | 0.052 | 0.00 |
| M N2 APARTMENT | 7851.32 | 9421.58 | 106.76 | 0.554 | 0.665 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 24.00 | 24.00 | 0.00856 | 30.59 | 0.01716 | 0.052 | 0.00 |
| M S1 APARTMENT | 7731.67 | 9278.01 | 105.13 | 0.546 | 0.655 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 24.00 | 24.00 | 0.00861 | 30.59 | 0.01716 | 0.052 | 0.00 |
| M S2 APARTMENT | 7717.21 | 9260.65 | 104.94 | 0.545 | 0.654 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 24.00 | 24.00 | 0.00861 | 30.59 | 0.01716 | 0.052 | 0.00 |
| T SW APARTMENT | 5227.07 | 6272.48 | 71.08 | 0.371 | 0.445 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 24.00 | 24.00 | 0.00873 | 30.59 | 0.01716 | 0.026 | 0.00 |
| T NW APARTMENT | 5357.99 | 6429.59 | 72.86 | 0.381 | 0.457 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 24.00 | 24.00 | 0.00870 | 30.59 | 0.01716 | 0.026 | 0.00 |
| T SE APARTMENT | 4621.25 | 5545.51 | 62.84 | 0.328 | 0.393 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 24.00 | 24.00 | 0.00883 | 30.59 | 0.01716 | 0.026 | 0.00 |
| T NE APARTMENT | 4750.40 | 5700.48 | 64.60 | 0.337 | 0.404 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 24.00 | 24.00 | 0.00879 | 30.59 | 0.01716 | 0.026 | 0.00 |
| T N1 APARTMENT | 4423.44 | 5308.13 | 60.15 | 0.313 | 0.376 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 24.00 | 24.00 | 0.00857 | 30.59 | 0.01716 | 0.026 | 0.00 |
| T N2 APARTMENT | 4404.50 | 5285.41 | 59.89 | 0.312 | 0.374 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 24.00 | 24.00 | 0.00857 | 30.59 | 0.01716 | 0.026 | 0.00 |
| T S1 APARTMENT | 4295.06 | 5154.07 | 58.40 | 0.304 | 0.365 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 24.00 | 24.00 | 0.00861 | 30.59 | 0.01716 | 0.026 | 0.00 |
| T S2 APARTMENT | 4276.20 | 5131.44 | 58.15 | 0.303 | 0.363 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 24.00 | 24.00 | 0.00861 | 30.59 | 0.01716 | 0.026 | 0.00 |
| Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
| G SW APARTMENT | 578.26 | 693.91 | 7.86 | 0.025 | 0.030 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 21.10 | 21.10 | 0.00766 | 8.70 | 0.00699 | 0.026 | 0.00 |
| G NW APARTMENT | 459.59 | 551.51 | 6.25 | 0.020 | 0.026 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | 21.10 | 21.10 | 0.00803 | 8.70 | 0.00699 | 0.026 | 0.00 |
| OFFICE | 943.89 | 1132.67 | 12.83 | 0.041 | 0.049 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 18:50:00 | 21.10 | 21.10 | 0.00776 | 8.70 | 0.00699 | 0.038 | 0.00 |
| G NE APARTMENT | 459.59 | 551.50 | 6.25 | 0.020 | 0.026 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | 21.10 | 21.10 | 0.00803 | 8.70 | 0.00699 | 0.026 | 0.00 |
| G N1 APARTMENT | 162.06 | 194.47 | 2.20 | 0.007 | 0.026 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | 21.10 | 21.10 | 0.00833 | 8.70 | 0.00699 | 0.026 | 0.00 |
| G N2 APARTMENT | 162.07 | 194.48 | 2.20 | 0.007 | 0.026 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | 21.10 | 21.10 | 0.00833 | 8.70 | 0.00699 | 0.026 | 0.00 |
| G S1 APARTMENT | 279.54 | 335.45 | 3.80 | 0.012 | 0.026 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 21.10 | 21.10 | 0.00757 | 8.70 | 0.00699 | 0.026 | 0.00 |
| G S2 APARTMENT | 288.19 | 345.83 | 3.92 | 0.012 | 0.026 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 21.10 | 21.10 | 0.00758 | 8.70 | 0.00699 | 0.026 | 0.00 |
| M SW APARTMENT | 1425.85 | 1711.02 | 19.39 | 0.062 | 0.074 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 21.10 | 21.10 | 0.00762 | 8.70 | 0.00699 | 0.052 | 0.00 |
| M NW APARTMENT | 1155.06 | 1386.07 | 15.71 | 0.050 | 0.060 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 21.10 | 21.10 | 0.00790 | 8.70 | 0.00699 | 0.052 | 0.00 |
| M SE APARTMENT | 1425.90 | 1711.08 | 19.39 | 0.062 | 0.074 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 21.10 | 21.10 | 0.00762 | 8.70 | 0.00699 | 0.052 | 0.00 |
| M NE APARTMENT | 1154.89 | 1385.87 | 15.70 | 0.050 | 0.060 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 21.10 | 21.10 | 0.00790 | 8.70 | 0.00699 | 0.052 | 0.00 |
| M N1 APARTMENT | 378.58 | 454.29 | 5.15 | 0.016 | 0.052 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 21.10 | 21.10 | 0.00810 | 8.70 | 0.00699 | 0.052 | 0.00 |
| M N2 APARTMENT | 378.59 | 454.31 | 5.15 | 0.016 | 0.052 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 21.10 | 21.10 | 0.00810 | 8.70 | 0.00699 | 0.052 | 0.00 |
| M S1 APARTMENT | 636.21 | 763.45 | 8.65 | 0.027 | 0.052 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 21.10 | 21.10 | 0.00752 | 8.70 | 0.00699 | 0.052 | 0.00 |
| M S2 APARTMENT | 636.23 | 763.48 | 8.65 | 0.027 | 0.052 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 21.10 | 21.10 | 0.00752 | 8.70 | 0.00699 | 0.052 | 0.00 |
| T SW APARTMENT | 1387.55 | 1665.06 | 18.87 | 0.060 | 0.072 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 21.10 | 21.10 | 0.00771 | 8.70 | 0.00699 | 0.026 | 0.00 |
| T NW APARTMENT | 1241.56 | 1489.87 | 16.88 | 0.054 | 0.064 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 21.10 | 21.10 | 0.00787 | 8.70 | 0.00699 | 0.026 | 0.00 |
| T SE APARTMENT | 1387.90 | 1665.48 | 18.87 | 0.060 | 0.072 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 21.10 | 21.10 | 0.00771 | 8.70 | 0.00699 | 0.026 | 0.00 |
| T NE APARTMENT | 1241.77 | 1490.12 | 16.89 | 0.054 | 0.064 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 21.10 | 21.10 | 0.00787 | 8.70 | 0.00699 | 0.026 | 0.00 |
| T N1 APARTMENT | 782.53 | 939.03 | 10.64 | 0.034 | 0.041 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 21.10 | 21.10 | 0.00798 | 8.70 | 0.00699 | 0.026 | 0.00 |
| T N2 APARTMENT | 782.54 | 939.05 | 10.64 | 0.034 | 0.041 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 21.10 | 21.10 | 0.00798 | 8.70 | 0.00699 | 0.026 | 0.00 |
| T S1 APARTMENT | 929.18 | 1115.02 | 12.63 | 0.040 | 0.048 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 21.10 | 21.10 | 0.00773 | 8.70 | 0.00699 | 0.026 | 0.00 |
| T S2 APARTMENT | 929.20 | 1115.04 | 12.64 | 0.040 | 0.048 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 21.10 | 21.10 | 0.00773 | 8.70 | 0.00699 | 0.026 | 0.00 |
| Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
| SPLIT GSW | 0.35 | 0.35 | 0.03 | 0.03 | 0.3473 | 0.3473 | 0.3473 | 1.0000 | 1.0000 |
| SPLIT GNW | 0.35 | 0.35 | 0.03 | 0.03 | 0.3521 | 0.3521 | 0.3521 | 1.0000 | 1.0000 |
| SPLIT OFFICE | 0.37 | 0.37 | 0.05 | 0.05 | 0.3734 | 0.3734 | 0.3734 | 1.0000 | 1.0000 |
| SPLIT GNE | 0.33 | 0.33 | 0.03 | 0.03 | 0.3256 | 0.3256 | 0.3256 | 1.0000 | 1.0000 |
| SPLIT GN1 | 0.29 | 0.29 | 0.03 | 0.03 | 0.2949 | 0.2949 | 0.2949 | 1.0000 | 1.0000 |
| SPLIT GN2 | 0.29 | 0.29 | 0.03 | 0.03 | 0.2944 | 0.2944 | 0.2944 | 1.0000 | 1.0000 |
| SPLIT GS1 | 0.29 | 0.29 | 0.03 | 0.03 | 0.2904 | 0.2904 | 0.2904 | 1.0000 | 1.0000 |
| SPLIT GS2 | 0.29 | 0.29 | 0.03 | 0.03 | 0.2925 | 0.2925 | 0.2925 | 1.0000 | 1.0000 |
| SPLIT MSW | 0.80 | 0.80 | 0.07 | 0.07 | 0.7963 | 0.7963 | 0.7963 | 1.0000 | 1.0000 |
| SPLIT MNW | 0.81 | 0.81 | 0.06 | 0.06 | 0.8084 | 0.8084 | 0.8084 | 1.0000 | 1.0000 |
| SPLIT MSE | 0.73 | 0.73 | 0.07 | 0.07 | 0.7264 | 0.7264 | 0.7264 | 1.0000 | 1.0000 |
| SPLIT MNE | 0.74 | 0.74 | 0.06 | 0.06 | 0.7385 | 0.7385 | 0.7385 | 1.0000 | 1.0000 |
| SPLIT MN1 | 0.67 | 0.67 | 0.05 | 0.05 | 0.6664 | 0.6664 | 0.6664 | 1.0000 | 1.0000 |
| SPLIT MN2 | 0.67 | 0.67 | 0.05 | 0.05 | 0.6652 | 0.6652 | 0.6652 | 1.0000 | 1.0000 |
| SPLIT MS1 | 0.65 | 0.65 | 0.05 | 0.05 | 0.6549 | 0.6549 | 0.6549 | 1.0000 | 1.0000 |
| SPLIT MS2 | 0.65 | 0.65 | 0.05 | 0.05 | 0.6536 | 0.6536 | 0.6536 | 1.0000 | 1.0000 |
| SPLIT TSW | 0.45 | 0.45 | 0.07 | 0.07 | 0.4454 | 0.4454 | 0.4454 | 1.0000 | 1.0000 |
| SPLIT TNW | 0.46 | 0.46 | 0.06 | 0.06 | 0.4568 | 0.4568 | 0.4568 | 1.0000 | 1.0000 |
| SPLIT TSE | 0.39 | 0.39 | 0.07 | 0.07 | 0.3930 | 0.3930 | 0.3930 | 1.0000 | 1.0000 |
| SPLIT TNE | 0.40 | 0.40 | 0.06 | 0.06 | 0.4042 | 0.4042 | 0.4042 | 1.0000 | 1.0000 |
| SPLIT TN1 | 0.38 | 0.38 | 0.04 | 0.04 | 0.3758 | 0.3758 | 0.3758 | 1.0000 | 1.0000 |
| SPLIT TN2 | 0.37 | 0.37 | 0.04 | 0.04 | 0.3742 | 0.3742 | 0.3742 | 1.0000 | 1.0000 |
| SPLIT TS1 | 0.36 | 0.36 | 0.05 | 0.05 | 0.3647 | 0.3647 | 0.3647 | 1.0000 | 1.0000 |
| SPLIT TS2 | 0.36 | 0.36 | 0.05 | 0.05 | 0.3630 | 0.3630 | 0.3630 | 1.0000 | 1.0000 |
| Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
| None |
| Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
| SPLIT GSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT GSW | 6608.032 | 5265.782 | 0.347314 | -999.0 | -999.000 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 6505.25 | 5385.60 | 0.347314 | 25.44 | 17.49 | 0.00922806 | 12.80 | 11.58 | 0.00800000 | 30.59 | 0.01716224 | 24.65 | 7.4729 | 24.00 | 0.00858726 | 46.1714 | 4094.26 | 0.00 | 6606.91 | 5258.47 |
| SPLIT GSW HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT GSW | 8322.472 | 8322.472 | -999.0 | -999.0 | -999.000 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 8322.47 | 8322.47 | 0.347314 | 20.17 | 14.16 | 0.00760574 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 7.4729 | 21.10 | 0.00765524 | 49.1548 | 578.26 | 0.00 | -999.00 | -999.00 |
| SPLIT GNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT GNW | 6661.488 | 5320.688 | 0.352146 | -999.0 | -999.000 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 6552.52 | 5454.49 | 0.352146 | 25.44 | 17.46 | 0.00918865 | 12.80 | 11.58 | 0.00800000 | 30.59 | 0.01716224 | 24.65 | 7.3704 | 24.00 | 0.00855421 | 45.9957 | 4149.67 | 0.00 | 6660.35 | 5312.28 |
| SPLIT GNW HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT GNW | 8432.744 | 8432.744 | -999.0 | -999.0 | -999.000 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 8432.74 | 8432.74 | 0.352146 | 20.19 | 14.49 | 0.00795104 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 7.3704 | 21.10 | 0.00798930 | 51.2719 | 406.88 | 0.00 | -999.00 | -999.00 |
| SPLIT OFFICE COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT OFFICE | 7123.342 | 5663.122 | 0.373383 | -999.0 | -999.000 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 09:20:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 09:20:00 | 7070.30 | 5793.49 | 0.373383 | 25.43 | 17.55 | 0.00930110 | 12.80 | 11.58 | 0.00800000 | 29.52 | 0.01716020 | 24.37 | 10.2056 | 23.90 | 0.00839440 | 45.4151 | 4337.40 | 0.00 | 7122.13 | 5654.65 |
| SPLIT OFFICE HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT OFFICE | 9100.038 | 9100.038 | -999.0 | -999.0 | -999.000 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 18:50:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 18:50:00 | 9100.04 | 9100.04 | 0.373383 | 19.83 | 14.10 | 0.00767957 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 10.2056 | 21.10 | 0.00775762 | 49.8038 | 943.89 | 0.00 | -999.00 | -999.00 |
| SPLIT GNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT GNE | 6270.115 | 4959.797 | 0.325582 | -999.0 | -999.000 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 6183.37 | 5065.28 | 0.325582 | 25.47 | 17.56 | 0.00930629 | 12.80 | 11.58 | 0.00800000 | 30.59 | 0.01716224 | 24.65 | 7.9717 | 24.00 | 0.00862579 | 46.3759 | 3843.75 | 0.00 | 6269.05 | 4952.66 |
| SPLIT GNE HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT GNE | 7825.975 | 7825.975 | -999.0 | -999.0 | -999.000 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 7825.98 | 7825.98 | 0.325582 | 20.11 | 14.45 | 0.00794482 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 7.9717 | 21.10 | 0.00798930 | 51.2719 | 406.87 | 0.00 | -999.00 | -999.00 |
| SPLIT GN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT GN1 | 5664.076 | 4490.619 | 0.294860 | -999.0 | -999.000 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 5583.85 | 4599.61 | 0.294860 | 25.51 | 17.55 | 0.00927021 | 12.80 | 11.58 | 0.00800000 | 30.59 | 0.01716224 | 24.65 | 8.8023 | 24.00 | 0.00850848 | 45.7521 | 3489.24 | 0.00 | 5663.11 | 4484.53 |
| SPLIT GN1 HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT GN1 | 7124.201 | 7124.201 | -999.0 | -999.0 | -999.000 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:30:00 | 7124.20 | 7124.20 | 0.294860 | 20.01 | 14.66 | 0.00821387 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 8.8023 | 21.10 | 0.00821785 | 52.7193 | 110.33 | 0.00 | -999.00 | -999.00 |
| SPLIT GN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT GN2 | 5656.582 | 4483.977 | 0.294355 | -999.0 | -999.000 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 5576.78 | 4592.20 | 0.294355 | 25.52 | 17.55 | 0.00927276 | 12.80 | 11.58 | 0.00800000 | 30.59 | 0.01716224 | 24.65 | 8.8174 | 24.00 | 0.00850984 | 45.7594 | 3483.43 | 0.00 | 5655.62 | 4477.82 |
| SPLIT GN2 HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT GN2 | 7112.662 | 7112.662 | -999.0 | -999.0 | -999.000 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 7112.66 | 7112.66 | 0.294355 | 20.01 | 14.66 | 0.00821366 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 8.8174 | 21.10 | 0.00821785 | 52.7193 | 110.34 | 0.00 | -999.00 | -999.00 |
| SPLIT GS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT GS1 | 5631.636 | 4442.636 | 0.290438 | -999.0 | -999.000 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 5559.36 | 4537.99 | 0.290438 | 25.52 | 17.61 | 0.00933667 | 12.80 | 11.58 | 0.00800000 | 30.59 | 0.01716224 | 24.65 | 8.9363 | 24.00 | 0.00856873 | 46.0725 | 3438.36 | 0.00 | 5630.68 | 4436.83 |
| SPLIT GS1 HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT GS1 | 7023.273 | 7023.273 | -999.0 | -999.0 | -999.000 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 7023.27 | 7023.27 | 0.290438 | 19.99 | 14.01 | 0.00751866 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 8.9363 | 21.10 | 0.00748480 | 48.0731 | 220.43 | 0.00 | -999.00 | -999.00 |
| SPLIT GS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT GS2 | 5664.099 | 4470.838 | 0.292539 | -999.0 | -999.000 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 5590.23 | 4568.82 | 0.292539 | 25.52 | 17.60 | 0.00932735 | 12.80 | 11.58 | 0.00800000 | 30.59 | 0.01716224 | 24.65 | 8.8722 | 24.00 | 0.00856455 | 46.0503 | 3462.43 | 0.00 | 5663.14 | 4465.25 |
| SPLIT GS2 HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT GS2 | 7071.249 | 7071.249 | -999.0 | -999.0 | -999.000 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 06:40:00 | 7071.25 | 7071.25 | 0.292539 | 20.00 | 14.02 | 0.00752838 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 8.8722 | 21.10 | 0.00749865 | 48.1610 | 230.07 | 0.00 | -999.00 | -999.00 |
| SPLIT MSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT MSW | 15069.957 | 12034.410 | 0.796260 | -999.0 | -999.000 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 14823.97 | 12294.48 | 0.796260 | 25.39 | 17.46 | 0.00921084 | 12.80 | 11.58 | 0.00800000 | 30.59 | 0.01716224 | 24.65 | 6.5191 | 24.00 | 0.00865633 | 46.5385 | 18712.01 | 0.00 | 15067.39 | 12015.18 |
| SPLIT MSW HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT MSW | 18966.562 | 18966.562 | -999.0 | -999.0 | -999.000 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 18966.56 | 18966.56 | 0.796260 | 20.29 | 14.18 | 0.00758050 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 6.5191 | 21.10 | 0.00762148 | 48.9408 | 2851.70 | 0.00 | -999.00 | -999.00 |
| SPLIT MNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT MNW | 15225.095 | 12182.282 | 0.808398 | -999.0 | -999.000 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 14966.23 | 12469.79 | 0.808398 | 25.38 | 17.43 | 0.00917779 | 12.80 | 11.58 | 0.00800000 | 30.59 | 0.01716224 | 24.65 | 6.4212 | 24.00 | 0.00862991 | 46.3981 | 18991.72 | 0.00 | 15222.50 | 12165.10 |
| SPLIT MNW HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT MNW | 19243.601 | 19243.601 | -999.0 | -999.0 | -999.000 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 19243.60 | 19243.60 | 0.808398 | 20.30 | 14.43 | 0.00783711 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 6.4212 | 21.10 | 0.00789504 | 50.6747 | 2310.11 | 0.00 | -999.00 | -999.00 |
| SPLIT MSE COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT MSE | 14034.458 | 11087.447 | 0.726434 | -999.0 | -999.000 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 13846.21 | 11271.13 | 0.726434 | 25.42 | 17.58 | 0.00934778 | 12.80 | 11.58 | 0.00800000 | 30.59 | 0.01716224 | 24.65 | 7.1457 | 24.00 | 0.00874640 | 47.0168 | 17105.63 | 0.00 | 14032.07 | 11070.10 |
| SPLIT MSE HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT MSE | 17371.556 | 17371.556 | -999.0 | -999.0 | -999.000 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 17371.56 | 17371.56 | 0.726434 | 20.21 | 14.15 | 0.00757656 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 7.1457 | 21.10 | 0.00762148 | 48.9409 | 2851.81 | 0.00 | -999.00 | -999.00 |
| SPLIT MNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT MNE | 14180.785 | 11244.502 | 0.738490 | -999.0 | -999.000 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 13978.32 | 11444.63 | 0.738490 | 25.41 | 17.54 | 0.00930543 | 12.80 | 11.58 | 0.00800000 | 30.59 | 0.01716224 | 24.65 | 7.0291 | 24.00 | 0.00871141 | 46.8309 | 17382.55 | 0.00 | 14178.37 | 11229.41 |
| SPLIT MNE HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT MNE | 17646.731 | 17646.731 | -999.0 | -999.0 | -999.000 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 17646.73 | 17646.73 | 0.738490 | 20.23 | 14.39 | 0.00783161 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 7.0291 | 21.10 | 0.00789503 | 50.6746 | 2309.78 | 0.00 | -999.00 | -999.00 |
| SPLIT MN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT MN1 | 12700.740 | 10101.532 | 0.666444 | -999.0 | -999.000 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 12506.27 | 10349.21 | 0.666444 | 25.46 | 17.50 | 0.00923276 | 12.80 | 11.58 | 0.00800000 | 30.59 | 0.01716224 | 24.65 | 7.7890 | 24.00 | 0.00856297 | 46.0418 | 15731.36 | 0.00 | 12698.58 | 10086.84 |
| SPLIT MN1 HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT MN1 | 16000.976 | 16000.976 | -999.0 | -999.0 | -999.000 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:50:00 | 16000.98 | 16000.98 | 0.666444 | 20.13 | 14.52 | 0.00801213 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 7.7890 | 21.10 | 0.00796841 | 51.1395 | 496.04 | 0.00 | -999.00 | -999.00 |
| SPLIT MN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT MN2 | 12682.313 | 10085.229 | 0.665207 | -999.0 | -999.000 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 12488.85 | 10331.02 | 0.665207 | 25.46 | 17.50 | 0.00923543 | 12.80 | 11.58 | 0.00800000 | 30.59 | 0.01716224 | 24.65 | 7.8035 | 24.00 | 0.00856451 | 46.0501 | 15702.63 | 0.00 | 12680.15 | 10070.40 |
| SPLIT MN2 HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT MN2 | 15972.705 | 15972.705 | -999.0 | -999.0 | -999.000 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 15972.70 | 15972.70 | 0.665207 | 20.13 | 14.52 | 0.00801197 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 7.8035 | 21.10 | 0.00796842 | 51.1395 | 496.07 | 0.00 | -999.00 | -999.00 |
| SPLIT MS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT MS1 | 12578.742 | 9973.104 | 0.654884 | -999.0 | -999.000 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 12400.04 | 10184.30 | 0.654884 | 25.47 | 17.55 | 0.00928742 | 12.80 | 11.58 | 0.00800000 | 30.59 | 0.01716224 | 24.65 | 7.9265 | 24.00 | 0.00860949 | 46.2891 | 15463.34 | 0.00 | 12576.60 | 9959.61 |
| SPLIT MS1 HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT MS1 | 15737.067 | 15737.067 | -999.0 | -999.0 | -999.000 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 15737.07 | 15737.07 | 0.654884 | 20.12 | 14.02 | 0.00747379 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 7.9265 | 21.10 | 0.00740424 | 47.5619 | 958.35 | 0.00 | -999.00 | -999.00 |
| SPLIT MS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT MS2 | 12560.377 | 9956.772 | 0.653637 | -999.0 | -999.000 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 12382.73 | 10165.99 | 0.653637 | 25.47 | 17.55 | 0.00929039 | 12.80 | 11.58 | 0.00800000 | 30.59 | 0.01716224 | 24.65 | 7.9416 | 24.00 | 0.00861131 | 46.2988 | 15434.42 | 0.00 | 12558.24 | 9943.12 |
| SPLIT MS2 HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT MS2 | 15708.580 | 15708.580 | -999.0 | -999.0 | -999.000 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 09:10:00 | 15708.58 | 15708.58 | 0.653637 | 20.12 | 14.02 | 0.00747372 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 7.9416 | 21.10 | 0.00740426 | 47.5619 | 958.39 | 0.00 | -999.00 | -999.00 |
| SPLIT TSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT TSW | 8421.944 | 6727.922 | 0.445392 | -999.0 | -999.000 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 8283.25 | 6860.64 | 0.445392 | 25.35 | 17.45 | 0.00921753 | 12.80 | 11.58 | 0.00800000 | 30.59 | 0.01716224 | 24.65 | 5.8274 | 24.00 | 0.00872591 | 46.9087 | 5227.07 | 0.00 | 8420.51 | 6717.40 |
| SPLIT TSW HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT TSW | 10562.931 | 10562.931 | -999.0 | -999.0 | -999.000 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 10562.93 | 10562.93 | 0.445392 | 20.38 | 14.30 | 0.00766874 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 5.8274 | 21.10 | 0.00771056 | 49.5063 | 1387.55 | 0.00 | -999.00 | -999.00 |
| SPLIT TNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT TNW | 8585.832 | 6875.502 | 0.456796 | -999.0 | -999.000 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 8437.26 | 7026.85 | 0.456796 | 25.34 | 17.42 | 0.00917782 | 12.80 | 11.58 | 0.00800000 | 30.59 | 0.01716224 | 24.65 | 5.6819 | 24.00 | 0.00869683 | 46.7542 | 5357.99 | 0.00 | 8584.37 | 6866.33 |
| SPLIT TNW HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT TNW | 10823.295 | 10823.295 | -999.0 | -999.0 | -999.000 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 10823.29 | 10823.29 | 0.456796 | 20.40 | 14.44 | 0.00781703 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 5.6819 | 21.10 | 0.00786668 | 50.4953 | 1241.56 | 0.00 | -999.00 | -999.00 |
| SPLIT TSE COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT TSE | 7618.325 | 6010.557 | 0.393009 | -999.0 | -999.000 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 7519.63 | 6089.49 | 0.393009 | 25.39 | 17.60 | 0.00938295 | 12.80 | 11.58 | 0.00800000 | 30.59 | 0.01716224 | 24.65 | 6.6041 | 24.00 | 0.00883288 | 47.4762 | 4621.25 | 0.00 | 7617.03 | 6002.77 |
| SPLIT TSE HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT TSE | 9366.362 | 9366.362 | -999.0 | -999.0 | -999.000 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 9366.36 | 9366.36 | 0.393009 | 20.28 | 14.26 | 0.00766321 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 6.6041 | 21.10 | 0.00771061 | 49.5066 | 1387.90 | 0.00 | -999.00 | -999.00 |
| SPLIT TNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT TNE | 7777.136 | 6161.916 | 0.404206 | -999.0 | -999.000 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 7668.12 | 6252.99 | 0.404206 | 25.38 | 17.56 | 0.00933172 | 12.80 | 11.58 | 0.00800000 | 30.59 | 0.01716224 | 24.65 | 6.4211 | 24.00 | 0.00879441 | 47.2720 | 4750.40 | 0.00 | 7775.81 | 6153.15 |
| SPLIT TNE HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT TNE | 9622.019 | 9622.019 | -999.0 | -999.0 | -999.000 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 9622.02 | 9622.02 | 0.404206 | 20.30 | 14.40 | 0.00781059 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 6.4211 | 21.10 | 0.00786670 | 50.4954 | 1241.77 | 0.00 | -999.00 | -999.00 |
| SPLIT TN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT TN1 | 7076.406 | 5662.713 | 0.375824 | -999.0 | -999.000 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 6955.99 | 5809.35 | 0.375824 | 25.41 | 17.43 | 0.00916371 | 12.80 | 11.58 | 0.00800000 | 30.59 | 0.01716224 | 24.65 | 6.9060 | 24.00 | 0.00857036 | 46.0812 | 4423.44 | 0.00 | 7075.20 | 5654.78 |
| SPLIT TN1 HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT TN1 | 8973.634 | 8973.634 | -999.0 | -999.0 | -999.000 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 8973.63 | 8973.63 | 0.375824 | 20.24 | 14.48 | 0.00791602 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 6.9060 | 21.10 | 0.00798450 | 51.2415 | 782.53 | 0.00 | -999.00 | -999.00 |
| SPLIT TN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT TN2 | 7051.437 | 5647.849 | 0.374180 | -999.0 | -999.000 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 6932.28 | 5785.22 | 0.374180 | 25.41 | 17.43 | 0.00916914 | 12.80 | 11.58 | 0.00800000 | 30.59 | 0.01716224 | 24.65 | 6.9364 | 24.00 | 0.00857338 | 46.0973 | 4404.50 | 0.00 | 7050.24 | 5639.87 |
| SPLIT TN2 HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT TN2 | 8936.079 | 8936.079 | -999.0 | -999.0 | -999.000 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 8936.08 | 8936.08 | 0.374180 | 20.24 | 14.47 | 0.00791572 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 6.9364 | 21.10 | 0.00798450 | 51.2415 | 782.54 | 0.00 | -999.00 | -999.00 |
| SPLIT TS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT TS1 | 6922.536 | 5521.440 | 0.364671 | -999.0 | -999.000 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 6812.60 | 5647.25 | 0.364671 | 25.43 | 17.48 | 0.00921766 | 12.80 | 11.58 | 0.00800000 | 30.59 | 0.01716224 | 24.65 | 7.1172 | 24.00 | 0.00860890 | 46.2860 | 4295.06 | 0.00 | 6921.36 | 5514.27 |
| SPLIT TS1 HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT TS1 | 8718.988 | 8718.988 | -999.0 | -999.0 | -999.000 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 8718.99 | 8718.99 | 0.364671 | 20.22 | 14.24 | 0.00767727 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 7.1172 | 21.10 | 0.00772971 | 49.6273 | 929.18 | 0.00 | -999.00 | -999.00 |
| SPLIT TS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT TS2 | 6897.772 | 5499.655 | 0.363033 | -999.0 | -999.000 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 6789.12 | 5623.21 | 0.363033 | 25.43 | 17.48 | 0.00922361 | 12.80 | 11.58 | 0.00800000 | 30.59 | 0.01716224 | 24.65 | 7.1494 | 24.00 | 0.00861234 | 46.3043 | 4276.20 | 0.00 | 6896.60 | 5492.32 |
| SPLIT TS2 HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT TS2 | 8681.561 | 8681.561 | -999.0 | -999.0 | -999.000 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 8681.56 | 8681.56 | 0.363033 | 20.21 | 14.24 | 0.00767704 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 7.1494 | 21.10 | 0.00772972 | 49.6273 | 929.20 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 09:14:58
Coils| Coil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
| SPLIT GSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT GSW | G SW APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 6608.032 | 5265.782 | 0.347314 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.9945 | 1004.8586 | 1.2027 | SPLIT GSW SUPPLY FAN | Fan:OnOff | 0.347314 | 0.41772755 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | Sensible | 6505.25 | 5385.60 | 0.9844 | 0.41772755 | 0.347314 | 25.44 | 17.49 | 0.00922806 | 49079.4 | 12.80 | 11.58 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 389.029 | 6116.22 | 30.59 | 0.01716224 | 24.65 | 0.02595455 | 7.4729 | 24.04 | 0.00858726 | 24.00 | 0.00858726 | 46.1714 | 4094.26 | 0.00 | 6606.91 | 5258.47 | 0.40123047 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 13.86 | 13.85 | 0.00986699 | 38855.8 | |
| SPLIT GSW HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT GSW | G SW APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 8322.472 | 8322.472 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | SPLIT GSW SUPPLY FAN | Fan:OnOff | 0.347314 | 0.41772755 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | Sensible | 8322.47 | 8322.47 | 1.0000 | 0.41772755 | 0.347314 | 20.17 | 14.16 | 0.00760574 | 39577.5 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8322.47 | 8.70 | 0.00699286 | 8.70 | 0.02595455 | 7.4729 | 21.10 | 0.00765524 | 21.10 | 0.00765524 | 49.1548 | 578.26 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT GNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT GNW | G NW APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 6661.488 | 5320.688 | 0.352146 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.9212 | 1004.8586 | 1.2027 | SPLIT GNW SUPPLY FAN | Fan:OnOff | 0.352146 | 0.42353924 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | Sensible | 6552.52 | 5454.49 | 0.9836 | 0.42353924 | 0.352146 | 25.44 | 17.46 | 0.00918865 | 48972.9 | 12.80 | 11.58 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 394.441 | 6158.07 | 30.59 | 0.01716224 | 24.65 | 0.02595455 | 7.3704 | 24.04 | 0.00855421 | 24.00 | 0.00855421 | 45.9957 | 4149.67 | 0.00 | 6660.35 | 5312.28 | 0.40681265 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 13.90 | 13.88 | 0.00988542 | 38950.3 | |
| SPLIT GNW HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT GNW | G NW APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 8432.744 | 8432.744 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | SPLIT GNW SUPPLY FAN | Fan:OnOff | 0.352146 | 0.42353924 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 8432.74 | 8432.74 | 1.0000 | 0.42353924 | 0.352146 | 20.19 | 14.49 | 0.00795104 | 40467.2 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8432.74 | 8.70 | 0.00699286 | 8.70 | 0.02595455 | 7.3704 | 21.10 | 0.00802728 | 21.10 | 0.00798930 | 51.2719 | 406.88 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT OFFICE COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT OFFICE | OFFICE | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 7123.342 | 5663.122 | 0.373383 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1022.1303 | 1004.8586 | 1.2027 | SPLIT OFFICE SUPPLY FAN | Fan:OnOff | 0.373383 | 0.44908281 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 09:20:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 09:20:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 09:20:00 | Sensible | 7070.30 | 5793.49 | 0.9926 | 0.44908281 | 0.373383 | 25.43 | 17.55 | 0.00930110 | 49256.8 | 12.80 | 11.58 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 418.230 | 6652.07 | 29.52 | 0.01716020 | 24.37 | 0.03810604 | 10.2056 | 23.95 | 0.00840787 | 23.90 | 0.00839440 | 45.4151 | 4337.40 | 0.00 | 7122.13 | 5654.65 | 0.43134743 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 13.85 | 13.83 | 0.00985078 | 38811.0 | |
| SPLIT OFFICE HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT OFFICE | OFFICE | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 9100.038 | 9100.038 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | SPLIT OFFICE SUPPLY FAN | Fan:OnOff | 0.373383 | 0.44908281 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 18:50:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 18:50:00 | Sensible | 9100.04 | 9100.04 | 1.0000 | 0.44908281 | 0.373383 | 19.83 | 14.10 | 0.00767957 | 39419.7 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9100.04 | 8.70 | 0.00699286 | 8.70 | 0.03810604 | 10.2056 | 21.10 | 0.00775762 | 21.10 | 0.00775762 | 49.8038 | 943.89 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT GNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT GNE | G NE APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 6270.115 | 4959.797 | 0.325582 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1022.1399 | 1004.8586 | 1.2027 | SPLIT GNE SUPPLY FAN | Fan:OnOff | 0.325582 | 0.39159026 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | Sensible | 6183.37 | 5065.28 | 0.9862 | 0.39159026 | 0.325582 | 25.47 | 17.56 | 0.00930629 | 49306.8 | 12.80 | 11.58 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 364.687 | 5818.68 | 30.59 | 0.01716224 | 24.65 | 0.02595455 | 7.9717 | 24.03 | 0.00862579 | 24.00 | 0.00862579 | 46.3759 | 3843.75 | 0.00 | 6269.05 | 4952.66 | 0.37612540 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 13.80 | 13.77 | 0.00981244 | 38654.9 | |
| SPLIT GNE HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT GNE | G NE APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 7825.975 | 7825.975 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | SPLIT GNE SUPPLY FAN | Fan:OnOff | 0.325582 | 0.39159026 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 7825.98 | 7825.98 | 1.0000 | 0.39159026 | 0.325582 | 20.11 | 14.45 | 0.00794482 | 40375.4 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 7825.98 | 8.70 | 0.00699286 | 8.70 | 0.02595455 | 7.9717 | 21.10 | 0.00802728 | 21.10 | 0.00798930 | 51.2719 | 406.87 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT GN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT GN1 | G N1 APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 5664.076 | 4490.619 | 0.294860 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1022.0729 | 1004.8586 | 1.2027 | SPLIT GN1 SUPPLY FAN | Fan:OnOff | 0.294860 | 0.35463982 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | Sensible | 5583.85 | 4599.61 | 0.9858 | 0.35463982 | 0.294860 | 25.51 | 17.55 | 0.00927021 | 49261.6 | 12.80 | 11.58 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 330.275 | 5253.58 | 30.59 | 0.01716224 | 24.65 | 0.02595455 | 8.8023 | 24.03 | 0.00850848 | 24.00 | 0.00850848 | 45.7521 | 3489.24 | 0.00 | 5663.11 | 4484.53 | 0.34063423 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 13.80 | 13.79 | 0.00982808 | 38697.2 | |
| SPLIT GN1 HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT GN1 | G N1 APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 7124.201 | 7124.201 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | SPLIT GN1 SUPPLY FAN | Fan:OnOff | 0.294860 | 0.35463982 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:30:00 | Sensible | 7124.20 | 7124.20 | 1.0000 | 0.35463982 | 0.294860 | 20.01 | 14.66 | 0.00821387 | 40953.3 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 7124.20 | 8.70 | 0.00699286 | 8.70 | 0.02595455 | 8.8023 | 21.10 | 0.00833172 | 21.10 | 0.00821785 | 52.7193 | 110.33 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT GN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT GN2 | G N2 APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 5656.582 | 4483.977 | 0.294355 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1022.0776 | 1004.8586 | 1.2027 | SPLIT GN2 SUPPLY FAN | Fan:OnOff | 0.294355 | 0.35403221 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | Sensible | 5576.78 | 4592.20 | 0.9859 | 0.35403221 | 0.294355 | 25.52 | 17.55 | 0.00927276 | 49268.9 | 12.80 | 11.58 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 329.709 | 5247.07 | 30.59 | 0.01716224 | 24.65 | 0.02595455 | 8.8174 | 24.03 | 0.00850984 | 24.00 | 0.00850984 | 45.7594 | 3483.43 | 0.00 | 5655.62 | 4477.82 | 0.34005061 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 13.80 | 13.79 | 0.00982667 | 38690.7 | |
| SPLIT GN2 HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT GN2 | G N2 APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 7112.662 | 7112.662 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | SPLIT GN2 SUPPLY FAN | Fan:OnOff | 0.294355 | 0.35403221 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 7112.66 | 7112.66 | 1.0000 | 0.35403221 | 0.294355 | 20.01 | 14.66 | 0.00821366 | 40950.9 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 7112.66 | 8.70 | 0.00699286 | 8.70 | 0.02595455 | 8.8174 | 21.10 | 0.00833172 | 21.10 | 0.00821785 | 52.7193 | 110.34 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT GS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT GS1 | G S1 APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 5631.636 | 4442.636 | 0.290438 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1022.1964 | 1004.8586 | 1.2027 | SPLIT GS1 SUPPLY FAN | Fan:OnOff | 0.290438 | 0.34932166 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | Sensible | 5559.36 | 4537.99 | 0.9872 | 0.34932166 | 0.290438 | 25.52 | 17.61 | 0.00933667 | 49438.4 | 12.80 | 11.58 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 325.322 | 5234.04 | 30.59 | 0.01716224 | 24.65 | 0.02595455 | 8.9363 | 24.02 | 0.00856873 | 24.00 | 0.00856873 | 46.0725 | 3438.36 | 0.00 | 5630.68 | 4436.83 | 0.33552610 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 13.74 | 13.73 | 0.00978959 | 38540.7 | |
| SPLIT GS1 HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT GS1 | G S1 APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 7023.273 | 7023.273 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | SPLIT GS1 SUPPLY FAN | Fan:OnOff | 0.290438 | 0.34932166 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 7023.27 | 7023.27 | 1.0000 | 0.34932166 | 0.290438 | 19.99 | 14.01 | 0.00751866 | 39171.7 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 7023.27 | 8.70 | 0.00699286 | 8.70 | 0.02595455 | 8.9363 | 21.10 | 0.00757026 | 21.10 | 0.00748480 | 48.0731 | 220.43 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT GS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT GS2 | G S2 APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 5664.099 | 4470.838 | 0.292539 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1022.1791 | 1004.8586 | 1.2027 | SPLIT GS2 SUPPLY FAN | Fan:OnOff | 0.292539 | 0.35184774 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | Sensible | 5590.23 | 4568.82 | 0.9870 | 0.35184774 | 0.292539 | 25.52 | 17.60 | 0.00932735 | 49410.6 | 12.80 | 11.58 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 327.675 | 5262.55 | 30.59 | 0.01716224 | 24.65 | 0.02595455 | 8.8722 | 24.02 | 0.00856455 | 24.00 | 0.00856455 | 46.0503 | 3462.43 | 0.00 | 5663.14 | 4465.25 | 0.33795241 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 13.75 | 13.74 | 0.00979493 | 38565.2 | |
| SPLIT GS2 HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT GS2 | G S2 APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 7071.249 | 7071.249 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | SPLIT GS2 SUPPLY FAN | Fan:OnOff | 0.292539 | 0.35184774 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 06:40:00 | Sensible | 7071.25 | 7071.25 | 1.0000 | 0.35184774 | 0.292539 | 20.00 | 14.02 | 0.00752838 | 39204.4 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 7071.25 | 8.70 | 0.00699286 | 8.70 | 0.02595455 | 8.8722 | 21.10 | 0.00758052 | 21.10 | 0.00749865 | 48.1610 | 230.07 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT MSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT MSW | M SW APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 15069.957 | 12034.410 | 0.796260 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.9625 | 1004.8586 | 1.2027 | SPLIT MSW SUPPLY FAN | Fan:OnOff | 0.796260 | 0.95769335 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | Sensible | 14823.97 | 12294.48 | 0.9837 | 0.95769335 | 0.796260 | 25.39 | 17.46 | 0.00921084 | 48979.2 | 12.80 | 11.58 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 891.898 | 13932.07 | 30.59 | 0.01716224 | 24.65 | 0.05190911 | 6.5191 | 24.05 | 0.00865633 | 24.00 | 0.00865633 | 46.5385 | 18712.01 | 0.00 | 15067.39 | 12015.18 | 0.91987170 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 13.90 | 13.88 | 0.00988371 | 38942.5 | |
| SPLIT MSW HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT MSW | M SW APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 18966.562 | 18966.562 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | SPLIT MSW SUPPLY FAN | Fan:OnOff | 0.796260 | 0.95769335 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | Sensible | 18966.56 | 18966.56 | 1.0000 | 0.95769335 | 0.796260 | 20.29 | 14.18 | 0.00758050 | 39633.9 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 18966.56 | 8.70 | 0.00699286 | 8.70 | 0.05190911 | 6.5191 | 21.10 | 0.00762148 | 21.10 | 0.00762148 | 48.9408 | 2851.70 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT MNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT MNW | M NW APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 15225.095 | 12182.282 | 0.808398 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.9010 | 1004.8586 | 1.2027 | SPLIT MNW SUPPLY FAN | Fan:OnOff | 0.808398 | 0.97229203 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | Sensible | 14966.23 | 12469.79 | 0.9830 | 0.97229203 | 0.808398 | 25.38 | 17.43 | 0.00917779 | 48889.4 | 12.80 | 11.58 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 905.493 | 14060.73 | 30.59 | 0.01716224 | 24.65 | 0.05190911 | 6.4212 | 24.05 | 0.00862991 | 24.00 | 0.00862991 | 46.3981 | 18991.72 | 0.00 | 15222.50 | 12165.10 | 0.93389385 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 13.94 | 13.91 | 0.00990107 | 39022.3 | |
| SPLIT MNW HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT MNW | M NW APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 19243.601 | 19243.601 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | SPLIT MNW SUPPLY FAN | Fan:OnOff | 0.808398 | 0.97229203 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | Sensible | 19243.60 | 19243.60 | 1.0000 | 0.97229203 | 0.808398 | 20.30 | 14.43 | 0.00783711 | 40297.9 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 19243.60 | 8.70 | 0.00699286 | 8.70 | 0.05190911 | 6.4212 | 21.10 | 0.00789504 | 21.10 | 0.00789504 | 50.6747 | 2310.11 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT MSE COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT MSE | M SE APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 14034.458 | 11087.447 | 0.726434 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1022.2170 | 1004.8586 | 1.2027 | SPLIT MSE SUPPLY FAN | Fan:OnOff | 0.726434 | 0.87371092 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | Sensible | 13846.21 | 11271.13 | 0.9866 | 0.87371092 | 0.726434 | 25.42 | 17.58 | 0.00934778 | 49364.3 | 12.80 | 11.58 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 813.685 | 13032.52 | 30.59 | 0.01716224 | 24.65 | 0.05190911 | 7.1457 | 24.04 | 0.00874640 | 24.00 | 0.00874640 | 47.0168 | 17105.63 | 0.00 | 14032.07 | 11070.10 | 0.83920594 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 13.77 | 13.75 | 0.00980083 | 38601.7 | |
| SPLIT MSE HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT MSE | M SE APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 17371.556 | 17371.556 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | SPLIT MSE SUPPLY FAN | Fan:OnOff | 0.726434 | 0.87371092 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | Sensible | 17371.56 | 17371.56 | 1.0000 | 0.87371092 | 0.726434 | 20.21 | 14.15 | 0.00757656 | 39544.7 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 17371.56 | 8.70 | 0.00699286 | 8.70 | 0.05190911 | 7.1457 | 21.10 | 0.00762148 | 21.10 | 0.00762148 | 48.9409 | 2851.81 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT MNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT MNE | M NE APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 14180.785 | 11244.502 | 0.738490 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1022.1383 | 1004.8586 | 1.2027 | SPLIT MNE SUPPLY FAN | Fan:OnOff | 0.738490 | 0.88821040 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | Sensible | 13978.32 | 11444.63 | 0.9857 | 0.88821040 | 0.738490 | 25.41 | 17.54 | 0.00930543 | 49249.6 | 12.80 | 11.58 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 827.188 | 13151.13 | 30.59 | 0.01716224 | 24.65 | 0.05190911 | 7.0291 | 24.04 | 0.00871141 | 24.00 | 0.00871141 | 46.8309 | 17382.55 | 0.00 | 14178.37 | 11229.41 | 0.85313280 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 13.80 | 13.79 | 0.00982940 | 38703.2 | |
| SPLIT MNE HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT MNE | M NE APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 17646.731 | 17646.731 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | SPLIT MNE SUPPLY FAN | Fan:OnOff | 0.738490 | 0.88821040 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | Sensible | 17646.73 | 17646.73 | 1.0000 | 0.88821040 | 0.738490 | 20.23 | 14.39 | 0.00783161 | 40207.1 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 17646.73 | 8.70 | 0.00699286 | 8.70 | 0.05190911 | 7.0291 | 21.10 | 0.00789503 | 21.10 | 0.00789503 | 50.6746 | 2309.78 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT MN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT MN1 | M N1 APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 12700.740 | 10101.532 | 0.666444 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1022.0032 | 1004.8586 | 1.2027 | SPLIT MN1 SUPPLY FAN | Fan:OnOff | 0.666444 | 0.80155851 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | Sensible | 12506.27 | 10349.21 | 0.9847 | 0.80155851 | 0.666444 | 25.46 | 17.50 | 0.00923276 | 49110.8 | 12.80 | 11.58 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 746.490 | 11759.78 | 30.59 | 0.01716224 | 24.65 | 0.05190911 | 7.7890 | 24.04 | 0.00856297 | 24.00 | 0.00856297 | 46.0418 | 15731.36 | 0.00 | 12698.58 | 10086.84 | 0.76990301 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 13.86 | 13.84 | 0.00985462 | 38828.6 | |
| SPLIT MN1 HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT MN1 | M N1 APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 16000.976 | 16000.976 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | SPLIT MN1 SUPPLY FAN | Fan:OnOff | 0.666444 | 0.80155851 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:50:00 | Sensible | 16000.98 | 16000.98 | 1.0000 | 0.80155851 | 0.666444 | 20.13 | 14.52 | 0.00801213 | 40569.4 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 16000.98 | 8.70 | 0.00699286 | 8.70 | 0.05190911 | 7.7890 | 21.10 | 0.00809822 | 21.10 | 0.00796841 | 51.1395 | 496.04 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT MN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT MN2 | M N2 APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 12682.313 | 10085.229 | 0.665207 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1022.0082 | 1004.8586 | 1.2027 | SPLIT MN2 SUPPLY FAN | Fan:OnOff | 0.665207 | 0.80006991 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | Sensible | 12488.85 | 10331.02 | 0.9847 | 0.80006991 | 0.665207 | 25.46 | 17.50 | 0.00923543 | 49118.4 | 12.80 | 11.58 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 745.103 | 11743.75 | 30.59 | 0.01716224 | 24.65 | 0.05190911 | 7.8035 | 24.04 | 0.00856451 | 24.00 | 0.00856451 | 46.0501 | 15702.63 | 0.00 | 12680.15 | 10070.40 | 0.76847319 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 13.86 | 13.84 | 0.00985316 | 38821.9 | |
| SPLIT MN2 HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT MN2 | M N2 APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 15972.705 | 15972.705 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | SPLIT MN2 SUPPLY FAN | Fan:OnOff | 0.665207 | 0.80006991 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 15972.70 | 15972.70 | 1.0000 | 0.80006991 | 0.665207 | 20.13 | 14.52 | 0.00801197 | 40567.1 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 15972.70 | 8.70 | 0.00699286 | 8.70 | 0.05190911 | 7.8035 | 21.10 | 0.00809822 | 21.10 | 0.00796842 | 51.1395 | 496.07 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT MS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT MS1 | M S1 APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 12578.742 | 9973.104 | 0.654884 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1022.1048 | 1004.8586 | 1.2027 | SPLIT MS1 SUPPLY FAN | Fan:OnOff | 0.654884 | 0.78765428 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | Sensible | 12400.04 | 10184.30 | 0.9858 | 0.78765428 | 0.654884 | 25.47 | 17.55 | 0.00928742 | 49257.4 | 12.80 | 11.58 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 733.541 | 11666.50 | 30.59 | 0.01716224 | 24.65 | 0.05190911 | 7.9265 | 24.04 | 0.00860949 | 24.00 | 0.00860949 | 46.2891 | 15463.34 | 0.00 | 12576.60 | 9959.61 | 0.75654789 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 13.80 | 13.79 | 0.00982842 | 38698.7 | |
| SPLIT MS1 HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT MS1 | M S1 APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 15737.067 | 15737.067 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | SPLIT MS1 SUPPLY FAN | Fan:OnOff | 0.654884 | 0.78765428 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 15737.07 | 15737.07 | 1.0000 | 0.78765428 | 0.654884 | 20.12 | 14.02 | 0.00747379 | 39185.3 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 15737.07 | 8.70 | 0.00699286 | 8.70 | 0.05190911 | 7.9265 | 21.10 | 0.00751519 | 21.10 | 0.00740424 | 47.5619 | 958.35 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT MS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT MS2 | M S2 APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 12560.377 | 9956.772 | 0.653637 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1022.1104 | 1004.8586 | 1.2027 | SPLIT MS2 SUPPLY FAN | Fan:OnOff | 0.653637 | 0.78615431 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | Sensible | 12382.73 | 10165.99 | 0.9859 | 0.78615431 | 0.653637 | 25.47 | 17.55 | 0.00929039 | 49265.8 | 12.80 | 11.58 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 732.144 | 11650.59 | 30.59 | 0.01716224 | 24.65 | 0.05190911 | 7.9416 | 24.04 | 0.00861131 | 24.00 | 0.00861131 | 46.2988 | 15434.42 | 0.00 | 12558.24 | 9943.12 | 0.75510715 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 13.80 | 13.79 | 0.00982680 | 38691.3 | |
| SPLIT MS2 HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT MS2 | M S2 APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 15708.580 | 15708.580 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | SPLIT MS2 SUPPLY FAN | Fan:OnOff | 0.653637 | 0.78615431 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 09:10:00 | Sensible | 15708.58 | 15708.58 | 1.0000 | 0.78615431 | 0.653637 | 20.12 | 14.02 | 0.00747372 | 39183.2 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 15708.58 | 8.70 | 0.00699286 | 8.70 | 0.05190911 | 7.9416 | 21.10 | 0.00751520 | 21.10 | 0.00740426 | 47.5619 | 958.39 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT TSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT TSW | T SW APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 8421.944 | 6727.922 | 0.445392 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.9749 | 1004.8586 | 1.2027 | SPLIT TSW SUPPLY FAN | Fan:OnOff | 0.445392 | 0.53569003 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | Sensible | 8283.25 | 6860.64 | 0.9835 | 0.53569003 | 0.445392 | 25.35 | 17.45 | 0.00921753 | 48961.1 | 12.80 | 11.58 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 498.887 | 7784.37 | 30.59 | 0.01716224 | 24.65 | 0.02595455 | 5.8274 | 24.06 | 0.00872591 | 24.00 | 0.00872591 | 46.9087 | 5227.07 | 0.00 | 8420.51 | 6717.40 | 0.51453432 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 13.91 | 13.89 | 0.00988688 | 38957.1 | |
| SPLIT TSW HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT TSW | T SW APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 10562.931 | 10562.931 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | SPLIT TSW SUPPLY FAN | Fan:OnOff | 0.445392 | 0.53569003 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | Sensible | 10562.93 | 10562.93 | 1.0000 | 0.53569003 | 0.445392 | 20.38 | 14.30 | 0.00766874 | 39945.1 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10562.93 | 8.70 | 0.00699286 | 8.70 | 0.02595455 | 5.8274 | 21.10 | 0.00771056 | 21.10 | 0.00771056 | 49.5063 | 1387.55 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT TNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT TNW | T NW APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 8585.832 | 6875.502 | 0.456796 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.9011 | 1004.8586 | 1.2027 | SPLIT TNW SUPPLY FAN | Fan:OnOff | 0.456796 | 0.54940626 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | Sensible | 8437.26 | 7026.85 | 0.9827 | 0.54940626 | 0.456796 | 25.34 | 17.42 | 0.00917782 | 48850.8 | 12.80 | 11.58 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 511.661 | 7925.60 | 30.59 | 0.01716224 | 24.65 | 0.02595455 | 5.6819 | 24.06 | 0.00869683 | 24.00 | 0.00869683 | 46.7542 | 5357.99 | 0.00 | 8584.37 | 6866.33 | 0.52770887 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 13.95 | 13.92 | 0.00990819 | 39055.1 | |
| SPLIT TNW HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT TNW | T NW APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 10823.295 | 10823.295 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | SPLIT TNW SUPPLY FAN | Fan:OnOff | 0.456796 | 0.54940626 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | Sensible | 10823.29 | 10823.29 | 1.0000 | 0.54940626 | 0.456796 | 20.40 | 14.44 | 0.00781703 | 40340.3 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10823.29 | 8.70 | 0.00699286 | 8.70 | 0.02595455 | 5.6819 | 21.10 | 0.00786668 | 21.10 | 0.00786668 | 50.4953 | 1241.56 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT TSE COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT TSE | T SE APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 7618.325 | 6010.557 | 0.393009 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1022.2824 | 1004.8586 | 1.2027 | SPLIT TSE SUPPLY FAN | Fan:OnOff | 0.393009 | 0.47268714 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | Sensible | 7519.63 | 6089.49 | 0.9870 | 0.47268714 | 0.393009 | 25.39 | 17.60 | 0.00938295 | 49426.3 | 12.80 | 11.58 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 440.212 | 7079.42 | 30.59 | 0.01716224 | 24.65 | 0.02595455 | 6.6041 | 24.05 | 0.00883288 | 24.00 | 0.00883288 | 47.4762 | 4621.25 | 0.00 | 7617.03 | 6002.77 | 0.45401957 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 13.74 | 13.73 | 0.00979063 | 38545.5 | |
| SPLIT TSE HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT TSE | T SE APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 9366.362 | 9366.362 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | SPLIT TSE SUPPLY FAN | Fan:OnOff | 0.393009 | 0.47268714 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | Sensible | 9366.36 | 9366.36 | 1.0000 | 0.47268714 | 0.393009 | 20.28 | 14.26 | 0.00766321 | 39833.0 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9366.36 | 8.70 | 0.00699286 | 8.70 | 0.02595455 | 6.6041 | 21.10 | 0.00771061 | 21.10 | 0.00771061 | 49.5066 | 1387.90 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT TNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT TNE | T NE APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 7777.136 | 6161.916 | 0.404206 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1022.1872 | 1004.8586 | 1.2027 | SPLIT TNE SUPPLY FAN | Fan:OnOff | 0.404206 | 0.48615469 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | Sensible | 7668.12 | 6252.99 | 0.9860 | 0.48615469 | 0.404206 | 25.38 | 17.56 | 0.00933172 | 49285.1 | 12.80 | 11.58 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 452.755 | 7215.37 | 30.59 | 0.01716224 | 24.65 | 0.02595455 | 6.4211 | 24.05 | 0.00879441 | 24.00 | 0.00879441 | 47.2720 | 4750.40 | 0.00 | 7775.81 | 6153.15 | 0.46695526 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 13.79 | 13.78 | 0.00982220 | 38670.2 | |
| SPLIT TNE HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT TNE | T NE APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 9622.019 | 9622.019 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | SPLIT TNE SUPPLY FAN | Fan:OnOff | 0.404206 | 0.48615469 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | Sensible | 9622.02 | 9622.02 | 1.0000 | 0.48615469 | 0.404206 | 20.30 | 14.40 | 0.00781059 | 40230.5 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9622.02 | 8.70 | 0.00699286 | 8.70 | 0.02595455 | 6.4211 | 21.10 | 0.00786670 | 21.10 | 0.00786670 | 50.4954 | 1241.77 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT TN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT TN1 | T N1 APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 7076.406 | 5662.713 | 0.375824 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.8749 | 1004.8586 | 1.2027 | SPLIT TN1 SUPPLY FAN | Fan:OnOff | 0.375824 | 0.45201871 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | Sensible | 6955.99 | 5809.35 | 0.9830 | 0.45201871 | 0.375824 | 25.41 | 17.43 | 0.00916371 | 48886.6 | 12.80 | 11.58 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 420.964 | 6535.02 | 30.59 | 0.01716224 | 24.65 | 0.02595455 | 6.9060 | 24.05 | 0.00857036 | 24.00 | 0.00857036 | 46.0812 | 4423.44 | 0.00 | 7075.20 | 5654.78 | 0.43416739 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 13.94 | 13.91 | 0.00990194 | 39026.4 | |
| SPLIT TN1 HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT TN1 | T N1 APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 8973.634 | 8973.634 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | SPLIT TN1 SUPPLY FAN | Fan:OnOff | 0.375824 | 0.45201871 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | Sensible | 8973.63 | 8973.63 | 1.0000 | 0.45201871 | 0.375824 | 20.24 | 14.48 | 0.00791602 | 40437.0 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8973.63 | 8.70 | 0.00699286 | 8.70 | 0.02595455 | 6.9060 | 21.10 | 0.00798450 | 21.10 | 0.00798450 | 51.2415 | 782.53 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT TN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT TN2 | T N2 APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 7051.437 | 5647.849 | 0.374180 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.8850 | 1004.8586 | 1.2027 | SPLIT TN2 SUPPLY FAN | Fan:OnOff | 0.374180 | 0.45004128 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | Sensible | 6932.28 | 5785.22 | 0.9831 | 0.45004128 | 0.374180 | 25.41 | 17.43 | 0.00916914 | 48902.2 | 12.80 | 11.58 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 419.122 | 6513.16 | 30.59 | 0.01716224 | 24.65 | 0.02595455 | 6.9364 | 24.05 | 0.00857338 | 24.00 | 0.00857338 | 46.0973 | 4404.50 | 0.00 | 7050.24 | 5639.87 | 0.43226806 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 13.92 | 13.91 | 0.00990542 | 39012.5 | |
| SPLIT TN2 HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT TN2 | T N2 APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 8936.079 | 8936.079 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | SPLIT TN2 SUPPLY FAN | Fan:OnOff | 0.374180 | 0.45004128 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | Sensible | 8936.08 | 8936.08 | 1.0000 | 0.45004128 | 0.374180 | 20.24 | 14.47 | 0.00791572 | 40432.4 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8936.08 | 8.70 | 0.00699286 | 8.70 | 0.02595455 | 6.9364 | 21.10 | 0.00798450 | 21.10 | 0.00798450 | 51.2415 | 782.54 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT TS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT TS1 | T S1 APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 6922.536 | 5521.440 | 0.364671 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.9752 | 1004.8586 | 1.2027 | SPLIT TS1 SUPPLY FAN | Fan:OnOff | 0.364671 | 0.43860446 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | Sensible | 6812.60 | 5647.25 | 0.9841 | 0.43860446 | 0.364671 | 25.43 | 17.48 | 0.00921766 | 49036.6 | 12.80 | 11.58 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 408.471 | 6404.13 | 30.59 | 0.01716224 | 24.65 | 0.02595455 | 7.1172 | 24.05 | 0.00860890 | 24.00 | 0.00860890 | 46.2860 | 4295.06 | 0.00 | 6921.36 | 5514.27 | 0.42128290 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 13.87 | 13.86 | 0.00987512 | 38893.1 | |
| SPLIT TS1 HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT TS1 | T S1 APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 8718.988 | 8718.988 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | SPLIT TS1 SUPPLY FAN | Fan:OnOff | 0.364671 | 0.43860446 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | Sensible | 8718.99 | 8718.99 | 1.0000 | 0.43860446 | 0.364671 | 20.22 | 14.24 | 0.00767727 | 39804.0 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8718.99 | 8.70 | 0.00699286 | 8.70 | 0.02595455 | 7.1172 | 21.10 | 0.00772971 | 21.10 | 0.00772971 | 49.6273 | 929.18 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT TS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT TS2 | T S2 APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 6897.772 | 5499.655 | 0.363033 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.9862 | 1004.8586 | 1.2027 | SPLIT TS2 SUPPLY FAN | Fan:OnOff | 0.363033 | 0.43663381 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | Sensible | 6789.12 | 5623.21 | 0.9842 | 0.43663381 | 0.363033 | 25.43 | 17.48 | 0.00922361 | 49053.6 | 12.80 | 11.58 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 406.636 | 6382.49 | 30.59 | 0.01716224 | 24.65 | 0.02595455 | 7.1494 | 24.05 | 0.00861234 | 24.00 | 0.00861234 | 46.3043 | 4276.20 | 0.00 | 6896.60 | 5492.32 | 0.41939008 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 13.87 | 13.86 | 0.00987183 | 38878.0 | |
| SPLIT TS2 HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT TS2 | T S2 APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 8681.561 | 8681.561 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | SPLIT TS2 SUPPLY FAN | Fan:OnOff | 0.363033 | 0.43663381 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | Sensible | 8681.56 | 8681.56 | 1.0000 | 0.43663381 | 0.363033 | 20.21 | 14.24 | 0.00767704 | 39799.3 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8681.56 | 8.70 | 0.00699286 | 8.70 | 0.02595455 | 7.1494 | 21.10 | 0.00772972 | 21.10 | 0.00772972 | 49.6273 | 929.20 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 09:14:58
Economizer| High Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
| None |
| Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
| None |
| Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
| G SW APARTMENT | 5405.67 | 2127.83 | 1897.67 |
| G NW APARTMENT | 7365.00 | 3364.17 | 2785.50 |
| OFFICE | 1697.50 | 226.17 | 224.33 |
| G NE APARTMENT | 7368.17 | 3109.33 | 2554.00 |
| G N1 APARTMENT | 7346.17 | 3226.00 | 2769.67 |
| G N2 APARTMENT | 7345.50 | 3219.33 | 2764.50 |
| G S1 APARTMENT | 5419.00 | 1933.00 | 1785.83 |
| G S2 APARTMENT | 5474.50 | 1370.33 | 1242.00 |
| M SW APARTMENT | 5308.17 | 2711.83 | 2420.00 |
| M NW APARTMENT | 7338.00 | 4080.33 | 3401.33 |
| M SE APARTMENT | 5278.67 | 2646.67 | 2353.83 |
| M NE APARTMENT | 7332.17 | 3851.00 | 3194.17 |
| M N1 APARTMENT | 7305.17 | 3841.33 | 3307.83 |
| M N2 APARTMENT | 7305.50 | 3834.00 | 3302.17 |
| M S1 APARTMENT | 5312.33 | 2475.00 | 2272.67 |
| M S2 APARTMENT | 5311.50 | 2473.83 | 2271.50 |
| T SW APARTMENT | 5206.00 | 3572.50 | 2921.83 |
| T NW APARTMENT | 7336.00 | 4856.50 | 3808.83 |
| T SE APARTMENT | 5187.83 | 3559.00 | 2899.50 |
| T NE APARTMENT | 7331.00 | 4687.17 | 3646.33 |
| T N1 APARTMENT | 7274.33 | 4606.17 | 3581.83 |
| T N2 APARTMENT | 7276.33 | 4622.17 | 3600.33 |
| T S1 APARTMENT | 5202.67 | 3282.50 | 2718.67 |
| T S2 APARTMENT | 5202.17 | 3283.67 | 2719.67 |
| T CORRIDOR | 8518.00 | 8643.33 | 8448.00 |
| G CORRIDOR | 8282.00 | 7428.50 | 7163.67 |
| M CORRIDOR | 8751.00 | 8653.67 | 8653.67 |
| Facility | 8756.83 | 8756.50 | 8672.50 |
| During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
| G SW APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| G NW APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| OFFICE | 0.00 | 0.17 | 0.00 | 0.17 |
| G NE APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| G N1 APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| G N2 APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| G S1 APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| G S2 APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| M SW APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| M NW APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| M SE APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| M NE APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| M N1 APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| M N2 APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| M S1 APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| M S2 APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| T SW APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| T NW APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| T SE APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| T NE APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| T N1 APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| T N2 APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| T S1 APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| T S2 APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| T CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
| G CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
| M CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
| Facility | 0.00 | 0.17 | 0.00 | 0.17 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 09:14:58
Average Outdoor Air During Occupied Hours| Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
| G SW APARTMENT | 2.40 | 2.50 | 268.97 | 0.356 | 0.162 | 0.000 | 0.052 |
| G NW APARTMENT | 1.71 | 2.50 | 268.97 | 0.356 | 0.177 | 0.000 | 0.055 |
| OFFICE | 4.75 | 4.75 | 268.97 | 0.522 | 0.208 | 0.000 | 0.000 |
| G NE APARTMENT | 1.71 | 2.50 | 268.97 | 0.356 | 0.177 | 0.000 | 0.056 |
| G N1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.356 | 0.107 | 0.000 | 0.056 |
| G N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.356 | 0.107 | 0.000 | 0.056 |
| G S1 APARTMENT | 2.40 | 2.50 | 268.97 | 0.356 | 0.097 | 0.000 | 0.052 |
| G S2 APARTMENT | 2.40 | 2.50 | 268.97 | 0.356 | 0.097 | 0.000 | 0.052 |
| M SW APARTMENT | 2.40 | 2.50 | 268.97 | 0.356 | 0.232 | 0.000 | 0.067 |
| M NW APARTMENT | 1.71 | 2.50 | 268.97 | 0.356 | 0.255 | 0.000 | 0.073 |
| M SE APARTMENT | 2.40 | 2.50 | 268.97 | 0.356 | 0.232 | 0.000 | 0.067 |
| M NE APARTMENT | 1.71 | 2.50 | 268.97 | 0.356 | 0.255 | 0.000 | 0.073 |
| M N1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.356 | 0.154 | 0.000 | 0.073 |
| M N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.356 | 0.154 | 0.000 | 0.073 |
| M S1 APARTMENT | 2.40 | 2.50 | 268.97 | 0.356 | 0.140 | 0.000 | 0.067 |
| M S2 APARTMENT | 2.40 | 2.50 | 268.97 | 0.356 | 0.140 | 0.000 | 0.067 |
| T SW APARTMENT | 2.40 | 2.50 | 268.97 | 0.356 | 0.307 | 0.000 | 0.081 |
| T NW APARTMENT | 1.71 | 2.50 | 268.97 | 0.356 | 0.337 | 0.000 | 0.088 |
| T SE APARTMENT | 2.40 | 2.50 | 268.97 | 0.356 | 0.307 | 0.000 | 0.081 |
| T NE APARTMENT | 1.71 | 2.50 | 268.97 | 0.356 | 0.337 | 0.000 | 0.088 |
| T N1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.356 | 0.203 | 0.000 | 0.088 |
| T N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.356 | 0.203 | 0.000 | 0.088 |
| T S1 APARTMENT | 2.40 | 2.50 | 268.97 | 0.356 | 0.185 | 0.000 | 0.081 |
| T S2 APARTMENT | 2.40 | 2.50 | 268.97 | 0.356 | 0.185 | 0.000 | 0.081 |
| Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
| G SW APARTMENT | 2.40 | 2.50 | 268.97 | 0.344 | 0.000 | 0.000 | 0.000 |
| G NW APARTMENT | 1.71 | 2.50 | 268.97 | 0.344 | 0.000 | 0.000 | 0.000 |
| OFFICE | 4.75 | 4.75 | 268.97 | 0.510 | 0.000 | 0.000 | 0.000 |
| G NE APARTMENT | 1.71 | 2.50 | 268.97 | 0.344 | 0.000 | 0.000 | 0.000 |
| G N1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.345 | 0.000 | 0.000 | 0.000 |
| G N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.345 | 0.000 | 0.000 | 0.000 |
| G S1 APARTMENT | 2.40 | 2.50 | 268.97 | 0.345 | 0.000 | 0.000 | 0.000 |
| G S2 APARTMENT | 2.40 | 2.50 | 268.97 | 0.346 | 0.000 | 0.000 | 0.000 |
| M SW APARTMENT | 2.40 | 2.50 | 268.97 | 0.344 | 0.000 | 0.000 | 0.000 |
| M NW APARTMENT | 1.71 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
| M SE APARTMENT | 2.40 | 2.50 | 268.97 | 0.344 | 0.000 | 0.000 | 0.000 |
| M NE APARTMENT | 1.71 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
| M N1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.344 | 0.000 | 0.000 | 0.000 |
| M N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.344 | 0.000 | 0.000 | 0.000 |
| M S1 APARTMENT | 2.40 | 2.50 | 268.97 | 0.345 | 0.000 | 0.000 | 0.000 |
| M S2 APARTMENT | 2.40 | 2.50 | 268.97 | 0.345 | 0.000 | 0.000 | 0.000 |
| T SW APARTMENT | 2.40 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
| T NW APARTMENT | 1.71 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
| T SE APARTMENT | 2.40 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
| T NE APARTMENT | 1.71 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
| T N1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
| T N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
| T S1 APARTMENT | 2.40 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
| T S2 APARTMENT | 2.40 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 09:14:58
Mechanical Ventilation Parameters by Zone| AirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
| G SW APARTMENT | SPLIT GSW | 2.40 | 2.50 | 268.97 | 88.25 | 0.0260 | 0.026 |
| G NW APARTMENT | SPLIT GNW | 1.71 | 2.50 | 268.97 | 88.25 | 0.0260 | 0.026 |
| OFFICE | SPLIT OFFICE | 4.75 | 4.75 | 268.97 | 88.25 | 0.0381 | 0.038 |
| G NE APARTMENT | SPLIT GNE | 1.71 | 2.50 | 268.97 | 88.25 | 0.0260 | 0.026 |
| G N1 APARTMENT | SPLIT GN1 | 1.71 | 2.50 | 268.97 | 88.25 | 0.0260 | 0.026 |
| G N2 APARTMENT | SPLIT GN2 | 1.71 | 2.50 | 268.97 | 88.25 | 0.0260 | 0.026 |
| G S1 APARTMENT | SPLIT GS1 | 2.40 | 2.50 | 268.97 | 88.25 | 0.0260 | 0.026 |
| G S2 APARTMENT | SPLIT GS2 | 2.40 | 2.50 | 268.97 | 88.25 | 0.0260 | 0.026 |
| M SW APARTMENT | SPLIT MSW | 2.40 | 2.50 | 268.97 | 88.25 | 0.0519 | 0.052 |
| M NW APARTMENT | SPLIT MNW | 1.71 | 2.50 | 268.97 | 88.25 | 0.0519 | 0.052 |
| M SE APARTMENT | SPLIT MSE | 2.40 | 2.50 | 268.97 | 88.25 | 0.0519 | 0.052 |
| M NE APARTMENT | SPLIT MNE | 1.71 | 2.50 | 268.97 | 88.25 | 0.0519 | 0.052 |
| M N1 APARTMENT | SPLIT MN1 | 1.71 | 2.50 | 268.97 | 88.25 | 0.0519 | 0.052 |
| M N2 APARTMENT | SPLIT MN2 | 1.71 | 2.50 | 268.97 | 88.25 | 0.0519 | 0.052 |
| M S1 APARTMENT | SPLIT MS1 | 2.40 | 2.50 | 268.97 | 88.25 | 0.0519 | 0.052 |
| M S2 APARTMENT | SPLIT MS2 | 2.40 | 2.50 | 268.97 | 88.25 | 0.0519 | 0.052 |
| T SW APARTMENT | SPLIT TSW | 2.40 | 2.50 | 268.97 | 88.25 | 0.0260 | 0.026 |
| T NW APARTMENT | SPLIT TNW | 1.71 | 2.50 | 268.97 | 88.25 | 0.0260 | 0.026 |
| T SE APARTMENT | SPLIT TSE | 2.40 | 2.50 | 268.97 | 88.25 | 0.0260 | 0.026 |
| T NE APARTMENT | SPLIT TNE | 1.71 | 2.50 | 268.97 | 88.25 | 0.0260 | 0.026 |
| T N1 APARTMENT | SPLIT TN1 | 1.71 | 2.50 | 268.97 | 88.25 | 0.0260 | 0.026 |
| T N2 APARTMENT | SPLIT TN2 | 1.71 | 2.50 | 268.97 | 88.25 | 0.0260 | 0.026 |
| T S1 APARTMENT | SPLIT TS1 | 2.40 | 2.50 | 268.97 | 88.25 | 0.0260 | 0.026 |
| T S2 APARTMENT | SPLIT TS2 | 2.40 | 2.50 | 268.97 | 88.25 | 0.0260 | 0.026 |
| Total Facility | 68.19 | 82.25 | 8607.06 | 2823.98 | 0.8427 | 1.258 |
| Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
| G SW APARTMENT | 818502.78 | 126103.40 | 944606.17 | 407272.42 | 1351878.60 | 818502.78 | 0.00 | 7261.67 | 1498.33 | 2615.00 |
| G NW APARTMENT | 818502.78 | 127986.15 | 946488.93 | 407272.42 | 1353761.35 | 818502.78 | 0.00 | 7261.67 | 1498.33 | 0.00 |
| OFFICE | 1201711.97 | 0.00 | 1201711.97 | 407272.42 | 1608984.40 | 1201711.97 | 0.00 | 8760.00 | 0.00 | 7010.00 |
| G NE APARTMENT | 818502.78 | 128138.65 | 946641.43 | 407272.42 | 1353913.86 | 818502.78 | 0.00 | 7261.67 | 1498.33 | 0.00 |
| G N1 APARTMENT | 818502.78 | 128267.97 | 946770.74 | 245656.39 | 1192427.13 | 818502.78 | 0.00 | 7261.67 | 1498.33 | 0.00 |
| G N2 APARTMENT | 818502.78 | 128273.89 | 946776.67 | 245656.39 | 1192433.05 | 818502.78 | 0.00 | 7261.67 | 1498.33 | 0.00 |
| G S1 APARTMENT | 818502.78 | 126164.89 | 944667.67 | 245656.39 | 1190324.05 | 818502.78 | 0.00 | 7261.67 | 1498.33 | 2615.00 |
| G S2 APARTMENT | 818502.78 | 126172.00 | 944674.78 | 245656.39 | 1190331.17 | 818502.78 | 0.00 | 7261.67 | 1498.33 | 2615.00 |
| M SW APARTMENT | 1637005.55 | 165559.08 | 1802564.64 | 585280.33 | 2387844.96 | 1637005.55 | 0.00 | 7146.50 | 1613.50 | 2615.00 |
| M NW APARTMENT | 1637005.55 | 168883.71 | 1805889.26 | 585280.33 | 2391169.59 | 1637005.55 | 0.00 | 7146.50 | 1613.50 | 0.00 |
| M SE APARTMENT | 1637005.55 | 165605.27 | 1802610.82 | 585280.33 | 2387891.15 | 1637005.55 | 0.00 | 7146.50 | 1613.50 | 2615.00 |
| M NE APARTMENT | 1637005.55 | 169079.36 | 1806084.92 | 585280.33 | 2391365.24 | 1637005.55 | 0.00 | 7146.50 | 1613.50 | 0.00 |
| M N1 APARTMENT | 1637005.55 | 169314.30 | 1806319.86 | 353026.24 | 2159346.09 | 1637005.55 | 0.00 | 7146.50 | 1613.50 | 0.00 |
| M N2 APARTMENT | 1637005.55 | 169323.13 | 1806328.69 | 353026.24 | 2159354.92 | 1637005.55 | 0.00 | 7146.50 | 1613.50 | 0.00 |
| M S1 APARTMENT | 1637005.55 | 165668.91 | 1802674.47 | 353026.24 | 2155700.70 | 1637005.55 | 0.00 | 7146.50 | 1613.50 | 2615.00 |
| M S2 APARTMENT | 1637005.55 | 165669.33 | 1802674.88 | 353026.24 | 2155701.12 | 1637005.55 | 0.00 | 7146.50 | 1613.50 | 2615.00 |
| T SW APARTMENT | 818502.78 | 199090.13 | 1017592.90 | 774201.61 | 1791794.51 | 818502.78 | 0.00 | 7158.33 | 1601.67 | 2615.00 |
| T NW APARTMENT | 818502.78 | 203242.92 | 1021745.69 | 774201.61 | 1795947.30 | 818502.78 | 0.00 | 7158.33 | 1601.67 | 0.00 |
| T SE APARTMENT | 818502.78 | 199416.29 | 1017919.07 | 774201.61 | 1792120.67 | 818502.78 | 0.00 | 7158.33 | 1601.67 | 2615.00 |
| T NE APARTMENT | 818502.78 | 203680.43 | 1022183.21 | 774201.61 | 1796384.82 | 818502.78 | 0.00 | 7158.33 | 1601.67 | 0.00 |
| T N1 APARTMENT | 818502.78 | 203829.86 | 1022332.64 | 466978.76 | 1489311.40 | 818502.78 | 0.00 | 7158.33 | 1601.67 | 0.00 |
| T N2 APARTMENT | 818502.78 | 203855.28 | 1022358.06 | 466978.76 | 1489336.81 | 818502.78 | 0.00 | 7158.33 | 1601.67 | 0.00 |
| T S1 APARTMENT | 818502.78 | 199722.09 | 1018224.87 | 466978.76 | 1485203.63 | 818502.78 | 0.00 | 7158.33 | 1601.67 | 2615.00 |
| T S2 APARTMENT | 818502.78 | 199731.44 | 1018234.22 | 466978.76 | 1485212.97 | 818502.78 | 0.00 | 7158.33 | 1601.67 | 2615.00 |
| Total Facility | 39671342.50 | 5181881.58 | 44853224.08 | 15082889.22 | 59936113.30 | 39671342.50 | 0.00 | 8760.00 | 1614.67 | 8760.00 |
| Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
| G SW APARTMENT | 0.0260 | 0.0038 | 0.0297 | 0.0118 | 0.0415 | 0.0260 | 0.00 | 5141.17 | 1003.83 |
| G NW APARTMENT | 0.0260 | 0.0041 | 0.0300 | 0.0129 | 0.0429 | 0.0260 | 0.00 | 7261.67 | 1498.33 |
| OFFICE | 0.0381 | 0.0000 | 0.0381 | 0.0152 | 0.0533 | 0.0381 | 0.00 | 1750.00 | 0.00 |
| G NE APARTMENT | 0.0260 | 0.0041 | 0.0300 | 0.0129 | 0.0429 | 0.0260 | 0.00 | 7261.67 | 1498.33 |
| G N1 APARTMENT | 0.0260 | 0.0041 | 0.0300 | 0.0078 | 0.0378 | 0.0260 | 0.00 | 7261.67 | 1498.33 |
| G N2 APARTMENT | 0.0260 | 0.0041 | 0.0300 | 0.0078 | 0.0378 | 0.0260 | 0.00 | 7261.67 | 1498.33 |
| G S1 APARTMENT | 0.0260 | 0.0038 | 0.0297 | 0.0071 | 0.0368 | 0.0260 | 0.00 | 5141.17 | 1003.83 |
| G S2 APARTMENT | 0.0260 | 0.0038 | 0.0297 | 0.0071 | 0.0368 | 0.0260 | 0.00 | 5141.17 | 1003.83 |
| M SW APARTMENT | 0.0519 | 0.0049 | 0.0568 | 0.0169 | 0.0738 | 0.0519 | 0.00 | 5056.33 | 1088.67 |
| M NW APARTMENT | 0.0519 | 0.0054 | 0.0573 | 0.0186 | 0.0758 | 0.0519 | 0.00 | 7146.50 | 1613.50 |
| M SE APARTMENT | 0.0519 | 0.0049 | 0.0568 | 0.0169 | 0.0738 | 0.0519 | 0.00 | 5056.33 | 1088.67 |
| M NE APARTMENT | 0.0519 | 0.0054 | 0.0573 | 0.0186 | 0.0758 | 0.0519 | 0.00 | 7146.50 | 1613.50 |
| M N1 APARTMENT | 0.0519 | 0.0054 | 0.0573 | 0.0112 | 0.0685 | 0.0519 | 0.00 | 7146.50 | 1613.50 |
| M N2 APARTMENT | 0.0519 | 0.0054 | 0.0573 | 0.0112 | 0.0685 | 0.0519 | 0.00 | 7146.50 | 1613.50 |
| M S1 APARTMENT | 0.0519 | 0.0049 | 0.0568 | 0.0102 | 0.0670 | 0.0519 | 0.00 | 5056.33 | 1088.67 |
| M S2 APARTMENT | 0.0519 | 0.0049 | 0.0568 | 0.0102 | 0.0670 | 0.0519 | 0.00 | 5056.33 | 1088.67 |
| T SW APARTMENT | 0.0260 | 0.0059 | 0.0319 | 0.0224 | 0.0542 | 0.0260 | 0.00 | 5065.67 | 1079.33 |
| T NW APARTMENT | 0.0260 | 0.0064 | 0.0324 | 0.0245 | 0.0569 | 0.0260 | 0.00 | 7158.33 | 1601.67 |
| T SE APARTMENT | 0.0260 | 0.0059 | 0.0319 | 0.0224 | 0.0542 | 0.0260 | 0.00 | 5065.67 | 1079.33 |
| T NE APARTMENT | 0.0260 | 0.0065 | 0.0324 | 0.0245 | 0.0570 | 0.0260 | 0.00 | 7158.33 | 1601.67 |
| T N1 APARTMENT | 0.0260 | 0.0065 | 0.0324 | 0.0148 | 0.0472 | 0.0260 | 0.00 | 7158.33 | 1601.67 |
| T N2 APARTMENT | 0.0260 | 0.0065 | 0.0324 | 0.0148 | 0.0472 | 0.0260 | 0.00 | 7158.33 | 1601.67 |
| T S1 APARTMENT | 0.0260 | 0.0059 | 0.0319 | 0.0135 | 0.0454 | 0.0260 | 0.00 | 5065.67 | 1079.33 |
| T S2 APARTMENT | 0.0260 | 0.0059 | 0.0319 | 0.0135 | 0.0454 | 0.0260 | 0.00 | 5065.67 | 1079.33 |
| Total Facility | 1.2580 | 0.1593 | 1.4173 | 0.4607 | 1.8779 | 1.2580 | 0.00 | 8760.00 | 1614.67 |
| Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
| SPLIT GSW | 0.00 | 126103.40 | 126103.40 | 818502.78 | 8163.00 | 42.08 | 554.92 | 494.50 |
| SPLIT GNW | 0.00 | 127986.15 | 127986.15 | 818502.78 | 8133.61 | 47.46 | 578.93 | 0.00 |
| SPLIT OFFICE | 1738373.64 | 0.00 | 1738373.64 | 1201711.97 | 0.00 | 0.00 | 8760.00 | 7010.00 |
| SPLIT GNE | 0.00 | 128138.65 | 128138.65 | 818502.78 | 8130.31 | 46.66 | 583.03 | 0.00 |
| SPLIT GN1 | 0.00 | 128267.97 | 128267.97 | 818502.78 | 8127.52 | 47.68 | 584.80 | 0.00 |
| SPLIT GN2 | 0.00 | 128273.89 | 128273.89 | 818502.78 | 8127.52 | 47.04 | 585.43 | 0.00 |
| SPLIT GS1 | 0.00 | 126164.89 | 126164.89 | 818502.78 | 8162.83 | 42.17 | 555.00 | 494.50 |
| SPLIT GS2 | 0.00 | 126172.00 | 126172.00 | 818502.78 | 8162.83 | 42.17 | 555.00 | 494.50 |
| SPLIT MSW | 0.00 | 165559.08 | 165559.08 | 1637005.55 | 8740.50 | 5.17 | 14.33 | 524.83 |
| SPLIT MNW | 0.00 | 168883.71 | 168883.71 | 1637005.55 | 8731.50 | 7.17 | 21.33 | 0.00 |
| SPLIT MSE | 0.00 | 165605.27 | 165605.27 | 1637005.55 | 8740.50 | 5.17 | 14.33 | 524.83 |
| SPLIT MNE | 0.00 | 169079.36 | 169079.36 | 1637005.55 | 8731.83 | 6.83 | 21.33 | 0.00 |
| SPLIT MN1 | 0.00 | 169314.30 | 169314.30 | 1637005.55 | 8731.00 | 7.17 | 21.83 | 0.00 |
| SPLIT MN2 | 0.00 | 169323.13 | 169323.13 | 1637005.55 | 8731.00 | 7.17 | 21.83 | 0.00 |
| SPLIT MS1 | 0.00 | 165668.91 | 165668.91 | 1637005.55 | 8740.50 | 5.17 | 14.33 | 524.83 |
| SPLIT MS2 | 0.00 | 165669.33 | 165669.33 | 1637005.55 | 8740.50 | 5.17 | 14.33 | 524.83 |
| SPLIT TSW | 0.00 | 199090.13 | 199090.13 | 818502.78 | 7589.30 | 21.94 | 1148.76 | 522.33 |
| SPLIT TNW | 0.00 | 203242.92 | 203242.92 | 818502.78 | 7610.01 | 22.76 | 1127.24 | 0.00 |
| SPLIT TSE | 0.00 | 199416.29 | 199416.29 | 818502.78 | 7584.32 | 21.77 | 1153.91 | 522.33 |
| SPLIT TNE | 0.00 | 203680.43 | 203680.43 | 818502.78 | 7604.57 | 23.77 | 1131.67 | 0.00 |
| SPLIT TN1 | 0.00 | 203829.86 | 203829.86 | 818502.78 | 7602.59 | 22.24 | 1135.17 | 0.00 |
| SPLIT TN2 | 0.00 | 203855.28 | 203855.28 | 818502.78 | 7602.22 | 22.44 | 1135.33 | 0.00 |
| SPLIT TS1 | 0.00 | 199722.09 | 199722.09 | 818502.78 | 7578.54 | 21.54 | 1159.92 | 522.33 |
| SPLIT TS2 | 0.00 | 199731.44 | 199731.44 | 818502.78 | 7578.54 | 21.46 | 1160.00 | 522.33 |
| Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
| SPLIT GSW | 0.0000 | 0.0038 | 0.0038 | 0.0260 | 5763.00 | 28.83 | 353.17 |
| SPLIT GNW | 0.0000 | 0.0041 | 0.0041 | 0.0260 | 8133.61 | 47.46 | 578.93 |
| SPLIT OFFICE | 0.0551 | 0.0000 | 0.0551 | 0.0381 | 0.00 | 0.00 | 1750.00 |
| SPLIT GNE | 0.0000 | 0.0041 | 0.0041 | 0.0260 | 8130.31 | 46.66 | 583.03 |
| SPLIT GN1 | 0.0000 | 0.0041 | 0.0041 | 0.0260 | 8127.52 | 47.68 | 584.80 |
| SPLIT GN2 | 0.0000 | 0.0041 | 0.0041 | 0.0260 | 8127.52 | 47.04 | 585.43 |
| SPLIT GS1 | 0.0000 | 0.0038 | 0.0038 | 0.0260 | 5762.83 | 29.00 | 353.17 |
| SPLIT GS2 | 0.0000 | 0.0038 | 0.0038 | 0.0260 | 5762.83 | 29.00 | 353.17 |
| SPLIT MSW | 0.0000 | 0.0049 | 0.0049 | 0.0519 | 6139.00 | 1.50 | 4.50 |
| SPLIT MNW | 0.0000 | 0.0054 | 0.0054 | 0.0519 | 8731.50 | 7.17 | 21.33 |
| SPLIT MSE | 0.0000 | 0.0049 | 0.0049 | 0.0519 | 6139.00 | 1.50 | 4.50 |
| SPLIT MNE | 0.0000 | 0.0054 | 0.0054 | 0.0519 | 8731.83 | 6.83 | 21.33 |
| SPLIT MN1 | 0.0000 | 0.0054 | 0.0054 | 0.0519 | 8731.00 | 7.17 | 21.83 |
| SPLIT MN2 | 0.0000 | 0.0054 | 0.0054 | 0.0519 | 8731.00 | 7.17 | 21.83 |
| SPLIT MS1 | 0.0000 | 0.0049 | 0.0049 | 0.0519 | 6139.00 | 1.50 | 4.50 |
| SPLIT MS2 | 0.0000 | 0.0049 | 0.0049 | 0.0519 | 6139.00 | 1.50 | 4.50 |
| SPLIT TSW | 0.0000 | 0.0059 | 0.0059 | 0.0260 | 5379.42 | 14.87 | 750.71 |
| SPLIT TNW | 0.0000 | 0.0064 | 0.0064 | 0.0260 | 7610.01 | 22.76 | 1127.24 |
| SPLIT TSE | 0.0000 | 0.0059 | 0.0059 | 0.0260 | 5377.13 | 15.24 | 752.63 |
| SPLIT TNE | 0.0000 | 0.0065 | 0.0065 | 0.0260 | 7604.57 | 23.77 | 1131.67 |
| SPLIT TN1 | 0.0000 | 0.0065 | 0.0065 | 0.0260 | 7602.59 | 22.24 | 1135.17 |
| SPLIT TN2 | 0.0000 | 0.0065 | 0.0065 | 0.0260 | 7602.22 | 22.44 | 1135.33 |
| SPLIT TS1 | 0.0000 | 0.0059 | 0.0059 | 0.0260 | 5371.58 | 15.08 | 758.33 |
| SPLIT TS2 | 0.0000 | 0.0059 | 0.0059 | 0.0260 | 5371.58 | 15.00 | 758.42 |
| No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
| SPLIT GSW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT GNW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT OFFICE | 0.00 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT GNE | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT GN1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT GN2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT GS1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT GS2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT MSW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT MNW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT MSE | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT MNE | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT MN1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT MN2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT MS1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT MS2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT TSW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT TNW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT TSE | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT TNE | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT TN1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT TN2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT TS1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT TS2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
| SPLIT GSW | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT GNW | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT OFFICE | 0.0000 | 0.0551 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT GNE | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT GN1 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT GN2 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT GS1 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT GS2 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT MSW | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT MNW | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT MSE | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT MNE | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT MN1 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT MN2 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT MS1 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT MS2 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT TSW | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT TNW | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT TSE | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT TNE | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT TN1 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT TN2 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT TS1 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT TS2 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 09:14:58
Surfaces by Class| Total | Outdoors | |
| Wall | 126 | 42 |
| Floor | 27 | 9 |
| Roof | 27 | 9 |
| Internal Mass | 24 | 0 |
| Building Detached Shading | 0 | 0 |
| Fixed Detached Shading | 0 | 0 |
| Window | 39 | 39 |
| Door | 0 | 0 |
| Glass Door | 0 | 0 |
| Shading | 0 | 0 |
| Overhang | 0 | 0 |
| Fin | 0 | 0 |
| Tubular Daylighting Device Dome | 0 | 0 |
| Tubular Daylighting Device Diffuser | 0 | 0 |
| Count | |
| HVAC Air Loops | 24 |
| Conditioned Zones | 24 |
| Unconditioned Zones | 3 |
| Supply Plenums | 0 |
| Return Plenums | 0 |
| Count | |
| IDF Objects | 1536 |
| Defaulted Fields | 1816 |
| Fields with Defaults | 5921 |
| Autosized Fields | 617 |
| Autosizable Fields | 759 |
| Autocalculated Fields | 331 |
| Autocalculatable Fields | 508 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 09:14:58
Annual and Peak Values - Electricity| Electricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
| Electricity:Facility | 1508.44 | 16911.93 | 03-FEB-03:20 | 92145.00 | 27-JUL-17:40 |
| Electricity:Building | 557.89 | 10119.94 | 01-JAN-03:10 | 27841.36 | 01-JAN-18:10 |
| Electricity:Zone:G SW APARTMENT | 13.67 | 232.36 | 01-JAN-03:10 | 705.80 | 01-JAN-18:10 |
| Electricity:SpaceType:GENERAL | 557.89 | 10119.94 | 01-JAN-03:10 | 27841.36 | 01-JAN-18:10 |
| InteriorLights:Electricity | 99.23 | 1868.27 | 01-JAN-00:10 | 5904.43 | 01-JAN-19:10 |
| InteriorLights:Electricity:Zone:G SW APARTMENT | 1.45 | 8.68 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 |
| InteriorLights:Electricity:SpaceType:GENERAL | 99.23 | 1868.27 | 01-JAN-00:10 | 5904.43 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity | 94.96 | 1842.77 | 01-JAN-00:10 | 5496.56 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:G SW APARTMENT | 1.32 | 7.86 | 01-JAN-00:10 | 125.72 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 94.96 | 1842.77 | 01-JAN-00:10 | 5496.56 | 01-JAN-19:10 |
| Electricity:Zone:G NW APARTMENT | 13.67 | 232.36 | 01-JAN-03:10 | 705.80 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:G NW APARTMENT | 1.45 | 8.68 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:G NW APARTMENT | 1.32 | 7.86 | 01-JAN-00:10 | 125.72 | 01-JAN-19:10 |
| Electricity:Zone:OFFICE | 16.86 | 310.83 | 01-JAN-00:10 | 1171.54 | 03-JAN-08:10 |
| InteriorLights:Electricity:Zone:OFFICE | 7.40 | 116.58 | 01-JAN-00:10 | 582.92 | 03-JAN-08:10 |
| LightsWired:InteriorLights:Electricity:Zone:OFFICE | 7.40 | 116.58 | 01-JAN-00:10 | 582.92 | 03-JAN-08:10 |
| Electricity:Zone:G NE APARTMENT | 13.67 | 232.36 | 01-JAN-03:10 | 705.80 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:G NE APARTMENT | 1.45 | 8.68 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:G NE APARTMENT | 1.32 | 7.86 | 01-JAN-00:10 | 125.72 | 01-JAN-19:10 |
| Electricity:Zone:G N1 APARTMENT | 13.67 | 232.36 | 01-JAN-03:10 | 705.80 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:G N1 APARTMENT | 1.45 | 8.68 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:G N1 APARTMENT | 1.32 | 7.86 | 01-JAN-00:10 | 125.72 | 01-JAN-19:10 |
| Electricity:Zone:G N2 APARTMENT | 13.67 | 232.36 | 01-JAN-03:10 | 705.80 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:G N2 APARTMENT | 1.45 | 8.68 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:G N2 APARTMENT | 1.32 | 7.86 | 01-JAN-00:10 | 125.72 | 01-JAN-19:10 |
| Electricity:Zone:G S1 APARTMENT | 13.67 | 232.36 | 01-JAN-03:10 | 705.80 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:G S1 APARTMENT | 1.45 | 8.68 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:G S1 APARTMENT | 1.32 | 7.86 | 01-JAN-00:10 | 125.72 | 01-JAN-19:10 |
| Electricity:Zone:G S2 APARTMENT | 13.67 | 232.36 | 01-JAN-03:10 | 705.80 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:G S2 APARTMENT | 1.45 | 8.68 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:G S2 APARTMENT | 1.32 | 7.86 | 01-JAN-00:10 | 125.72 | 01-JAN-19:10 |
| Electricity:Zone:M SW APARTMENT | 27.33 | 464.72 | 01-JAN-03:10 | 1411.61 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:M SW APARTMENT | 2.91 | 17.37 | 01-JAN-00:10 | 277.76 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:M SW APARTMENT | 2.63 | 15.72 | 01-JAN-00:10 | 251.45 | 01-JAN-19:10 |
| Electricity:Zone:M NW APARTMENT | 27.33 | 464.72 | 01-JAN-03:10 | 1411.61 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:M NW APARTMENT | 2.91 | 17.37 | 01-JAN-00:10 | 277.76 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:M NW APARTMENT | 2.63 | 15.72 | 01-JAN-00:10 | 251.45 | 01-JAN-19:10 |
| Electricity:Zone:M SE APARTMENT | 27.33 | 464.72 | 01-JAN-03:10 | 1411.61 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:M SE APARTMENT | 2.91 | 17.37 | 01-JAN-00:10 | 277.76 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:M SE APARTMENT | 2.63 | 15.72 | 01-JAN-00:10 | 251.45 | 01-JAN-19:10 |
| Electricity:Zone:M NE APARTMENT | 27.33 | 464.72 | 01-JAN-03:10 | 1411.61 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:M NE APARTMENT | 2.91 | 17.37 | 01-JAN-00:10 | 277.76 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:M NE APARTMENT | 2.63 | 15.72 | 01-JAN-00:10 | 251.45 | 01-JAN-19:10 |
| Electricity:Zone:M N1 APARTMENT | 27.33 | 464.72 | 01-JAN-03:10 | 1411.61 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:M N1 APARTMENT | 2.91 | 17.37 | 01-JAN-00:10 | 277.76 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:M N1 APARTMENT | 2.63 | 15.72 | 01-JAN-00:10 | 251.45 | 01-JAN-19:10 |
| Electricity:Zone:M N2 APARTMENT | 27.33 | 464.72 | 01-JAN-03:10 | 1411.61 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:M N2 APARTMENT | 2.91 | 17.37 | 01-JAN-00:10 | 277.76 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:M N2 APARTMENT | 2.63 | 15.72 | 01-JAN-00:10 | 251.45 | 01-JAN-19:10 |
| Electricity:Zone:M S1 APARTMENT | 27.33 | 464.72 | 01-JAN-03:10 | 1411.61 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:M S1 APARTMENT | 2.91 | 17.37 | 01-JAN-00:10 | 277.76 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:M S1 APARTMENT | 2.63 | 15.72 | 01-JAN-00:10 | 251.45 | 01-JAN-19:10 |
| Electricity:Zone:M S2 APARTMENT | 27.33 | 464.72 | 01-JAN-03:10 | 1411.61 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:M S2 APARTMENT | 2.91 | 17.37 | 01-JAN-00:10 | 277.76 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:M S2 APARTMENT | 2.63 | 15.72 | 01-JAN-00:10 | 251.45 | 01-JAN-19:10 |
| Electricity:Zone:T SW APARTMENT | 13.67 | 232.36 | 01-JAN-03:10 | 705.80 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:T SW APARTMENT | 1.45 | 8.68 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:T SW APARTMENT | 1.32 | 7.86 | 01-JAN-00:10 | 125.72 | 01-JAN-19:10 |
| Electricity:Zone:T NW APARTMENT | 13.67 | 232.36 | 01-JAN-03:10 | 705.80 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:T NW APARTMENT | 1.45 | 8.68 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:T NW APARTMENT | 1.32 | 7.86 | 01-JAN-00:10 | 125.72 | 01-JAN-19:10 |
| Electricity:Zone:T SE APARTMENT | 13.67 | 232.36 | 01-JAN-03:10 | 705.80 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:T SE APARTMENT | 1.45 | 8.68 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:T SE APARTMENT | 1.32 | 7.86 | 01-JAN-00:10 | 125.72 | 01-JAN-19:10 |
| Electricity:Zone:T NE APARTMENT | 13.67 | 232.36 | 01-JAN-03:10 | 705.80 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:T NE APARTMENT | 1.45 | 8.68 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:T NE APARTMENT | 1.32 | 7.86 | 01-JAN-00:10 | 125.72 | 01-JAN-19:10 |
| Electricity:Zone:T N1 APARTMENT | 13.67 | 232.36 | 01-JAN-03:10 | 705.80 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:T N1 APARTMENT | 1.45 | 8.68 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:T N1 APARTMENT | 1.32 | 7.86 | 01-JAN-00:10 | 125.72 | 01-JAN-19:10 |
| Electricity:Zone:T N2 APARTMENT | 13.67 | 232.36 | 01-JAN-03:10 | 705.80 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:T N2 APARTMENT | 1.45 | 8.68 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:T N2 APARTMENT | 1.32 | 7.86 | 01-JAN-00:10 | 125.72 | 01-JAN-19:10 |
| Electricity:Zone:T S1 APARTMENT | 13.67 | 232.36 | 01-JAN-03:10 | 705.80 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:T S1 APARTMENT | 1.45 | 8.68 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:T S1 APARTMENT | 1.32 | 7.86 | 01-JAN-00:10 | 125.72 | 01-JAN-19:10 |
| Electricity:Zone:T S2 APARTMENT | 13.67 | 232.36 | 01-JAN-03:10 | 705.80 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:T S2 APARTMENT | 1.45 | 8.68 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:T S2 APARTMENT | 1.32 | 7.86 | 01-JAN-00:10 | 125.72 | 01-JAN-19:10 |
| Electricity:Zone:G CORRIDOR | 82.28 | 1494.09 | 01-JAN-00:10 | 4538.70 | 01-JAN-07:10 |
| InteriorLights:Electricity:Zone:G CORRIDOR | 11.69 | 370.63 | 01-JAN-00:10 | 370.63 | 01-JAN-00:10 |
| LightsWired:InteriorLights:Electricity:Zone:G CORRIDOR | 11.69 | 370.63 | 01-JAN-00:10 | 370.63 | 01-JAN-00:10 |
| Electricity:Zone:M CORRIDOR | 23.38 | 741.26 | 01-JAN-00:10 | 741.26 | 01-JAN-00:10 |
| InteriorLights:Electricity:Zone:M CORRIDOR | 23.38 | 741.26 | 01-JAN-00:10 | 741.26 | 01-JAN-00:10 |
| LightsWired:InteriorLights:Electricity:Zone:M CORRIDOR | 23.38 | 741.26 | 01-JAN-00:10 | 741.26 | 01-JAN-00:10 |
| Electricity:Zone:T CORRIDOR | 11.69 | 370.63 | 01-JAN-00:10 | 370.63 | 01-JAN-00:10 |
| InteriorLights:Electricity:Zone:T CORRIDOR | 11.69 | 370.63 | 01-JAN-00:10 | 370.63 | 01-JAN-00:10 |
| LightsWired:InteriorLights:Electricity:Zone:T CORRIDOR | 11.69 | 370.63 | 01-JAN-00:10 | 370.63 | 01-JAN-00:10 |
| LightsPlugIn:InteriorLights:Electricity | 4.27 | 25.50 | 01-JAN-00:10 | 407.87 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:G SW APARTMENT | 0.14 | 0.82 | 01-JAN-00:10 | 13.16 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:SpaceType:GENERAL | 4.27 | 25.50 | 01-JAN-00:10 | 407.87 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:G NW APARTMENT | 0.14 | 0.82 | 01-JAN-00:10 | 13.16 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:G NE APARTMENT | 0.14 | 0.82 | 01-JAN-00:10 | 13.16 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:G N1 APARTMENT | 0.14 | 0.82 | 01-JAN-00:10 | 13.16 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:G N2 APARTMENT | 0.14 | 0.82 | 01-JAN-00:10 | 13.16 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:G S1 APARTMENT | 0.14 | 0.82 | 01-JAN-00:10 | 13.16 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:G S2 APARTMENT | 0.14 | 0.82 | 01-JAN-00:10 | 13.16 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:M SW APARTMENT | 0.28 | 1.65 | 01-JAN-00:10 | 26.31 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:M NW APARTMENT | 0.28 | 1.65 | 01-JAN-00:10 | 26.31 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:M SE APARTMENT | 0.28 | 1.65 | 01-JAN-00:10 | 26.31 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:M NE APARTMENT | 0.28 | 1.65 | 01-JAN-00:10 | 26.31 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:M N1 APARTMENT | 0.28 | 1.65 | 01-JAN-00:10 | 26.31 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:M N2 APARTMENT | 0.28 | 1.65 | 01-JAN-00:10 | 26.31 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:M S1 APARTMENT | 0.28 | 1.65 | 01-JAN-00:10 | 26.31 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:M S2 APARTMENT | 0.28 | 1.65 | 01-JAN-00:10 | 26.31 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:T SW APARTMENT | 0.14 | 0.82 | 01-JAN-00:10 | 13.16 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:T NW APARTMENT | 0.14 | 0.82 | 01-JAN-00:10 | 13.16 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:T SE APARTMENT | 0.14 | 0.82 | 01-JAN-00:10 | 13.16 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:T NE APARTMENT | 0.14 | 0.82 | 01-JAN-00:10 | 13.16 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:T N1 APARTMENT | 0.14 | 0.82 | 01-JAN-00:10 | 13.16 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:T N2 APARTMENT | 0.14 | 0.82 | 01-JAN-00:10 | 13.16 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:T S1 APARTMENT | 0.14 | 0.82 | 01-JAN-00:10 | 13.16 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:T S2 APARTMENT | 0.14 | 0.82 | 01-JAN-00:10 | 13.16 | 01-JAN-19:10 |
| InteriorEquipment:Electricity | 458.66 | 8251.68 | 01-JAN-03:10 | 22709.69 | 03-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:G SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:SpaceType:GENERAL | 458.66 | 8251.68 | 01-JAN-03:10 | 22709.69 | 03-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity | 388.06 | 7128.22 | 01-JAN-03:10 | 18541.61 | 03-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:G SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 388.06 | 7128.22 | 01-JAN-03:10 | 18541.61 | 03-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:G NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:G NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:OFFICE | 9.47 | 194.25 | 01-JAN-00:10 | 588.62 | 03-JAN-08:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:OFFICE | 9.47 | 194.25 | 01-JAN-00:10 | 588.62 | 03-JAN-08:10 |
| InteriorEquipment:Electricity:Zone:G NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:G NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:G N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:G N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:G N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:G N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:G S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:G S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:G S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:G S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:M SW APARTMENT | 24.43 | 447.35 | 01-JAN-03:10 | 1177.25 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:M SW APARTMENT | 24.43 | 447.35 | 01-JAN-03:10 | 1177.25 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:M NW APARTMENT | 24.43 | 447.35 | 01-JAN-03:10 | 1177.25 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:M NW APARTMENT | 24.43 | 447.35 | 01-JAN-03:10 | 1177.25 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:M SE APARTMENT | 24.43 | 447.35 | 01-JAN-03:10 | 1177.25 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:M SE APARTMENT | 24.43 | 447.35 | 01-JAN-03:10 | 1177.25 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:M NE APARTMENT | 24.43 | 447.35 | 01-JAN-03:10 | 1177.25 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:M NE APARTMENT | 24.43 | 447.35 | 01-JAN-03:10 | 1177.25 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:M N1 APARTMENT | 24.43 | 447.35 | 01-JAN-03:10 | 1177.25 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:M N1 APARTMENT | 24.43 | 447.35 | 01-JAN-03:10 | 1177.25 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:M N2 APARTMENT | 24.43 | 447.35 | 01-JAN-03:10 | 1177.25 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:M N2 APARTMENT | 24.43 | 447.35 | 01-JAN-03:10 | 1177.25 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:M S1 APARTMENT | 24.43 | 447.35 | 01-JAN-03:10 | 1177.25 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:M S1 APARTMENT | 24.43 | 447.35 | 01-JAN-03:10 | 1177.25 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:M S2 APARTMENT | 24.43 | 447.35 | 01-JAN-03:10 | 1177.25 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:M S2 APARTMENT | 24.43 | 447.35 | 01-JAN-03:10 | 1177.25 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:T SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:T SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:T NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:T NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:T SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:T SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:T NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:T NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:T N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:T N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:T N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:T N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:T S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:T S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:T S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:T S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:G CORRIDOR | 70.59 | 1123.46 | 01-JAN-00:10 | 4168.07 | 01-JAN-07:10 |
| ElevatorLift:InteriorEquipment:Electricity | 65.48 | 961.46 | 01-JAN-00:10 | 4006.07 | 01-JAN-07:10 |
| ElevatorLift:InteriorEquipment:Electricity:Zone:G CORRIDOR | 65.48 | 961.46 | 01-JAN-00:10 | 4006.07 | 01-JAN-07:10 |
| ElevatorLift:InteriorEquipment:Electricity:SpaceType:GENERAL | 65.48 | 961.46 | 01-JAN-00:10 | 4006.07 | 01-JAN-07:10 |
| ElevatorLightsFan:InteriorEquipment:Electricity | 5.11 | 162.00 | 01-JAN-00:10 | 162.00 | 01-JAN-00:10 |
| ElevatorLightsFan:InteriorEquipment:Electricity:Zone:G CORRIDOR | 5.11 | 162.00 | 01-JAN-00:10 | 162.00 | 01-JAN-00:10 |
| ElevatorLightsFan:InteriorEquipment:Electricity:SpaceType:GENERAL | 5.11 | 162.00 | 01-JAN-00:10 | 162.00 | 01-JAN-00:10 |
| Fans:Electricity | 148.91 | 1658.66 | 08-JAN-06:50 | 8544.64 | 27-JUL-16:10 |
| Fans:Electricity:Zone:G SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:G SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:G NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:G NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:G NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:G NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:G N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:G N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:G N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:G N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:G S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:G S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:G S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:G S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:M SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:M SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:M NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:M NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:M SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:M SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:M NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:M NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:M N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:M N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:M N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:M N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:M S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:M S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:M S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:M S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:T SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:T SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:T NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:T NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:T SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:T SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:T NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:T NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:T N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:T N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:T N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:T N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:T S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:T S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:T S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:T S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| ElectricityPurchased:Facility | 1508.44 | 16911.93 | 03-FEB-03:20 | 92145.00 | 27-JUL-17:40 |
| ElectricityPurchased:Plant | 1508.44 | 16911.93 | 03-FEB-03:20 | 92145.00 | 27-JUL-17:40 |
| Cogeneration:ElectricityPurchased | 1508.44 | 16911.93 | 03-FEB-03:20 | 92145.00 | 27-JUL-17:40 |
| General:Cogeneration:ElectricityPurchased | 1508.44 | 16911.93 | 03-FEB-03:20 | 92145.00 | 27-JUL-17:40 |
| ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| ElectricityNet:Facility | 1508.44 | 16911.93 | 03-FEB-03:20 | 92145.00 | 27-JUL-17:40 |
| ElectricityNet:Plant | 1508.44 | 16911.93 | 03-FEB-03:20 | 92145.00 | 27-JUL-17:40 |
| Cogeneration:ElectricityNet | 1508.44 | 16911.93 | 03-FEB-03:20 | 92145.00 | 27-JUL-17:40 |
| General:Cogeneration:ElectricityNet | 1508.44 | 16911.93 | 03-FEB-03:20 | 92145.00 | 27-JUL-17:40 |
| Electricity:HVAC | 544.02 | 1658.66 | 08-JAN-06:50 | 38993.78 | 27-JUL-16:00 |
| HeatRecovery:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:HeatRecovery:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:Fans:Electricity | 148.91 | 1658.66 | 08-JAN-06:50 | 8544.64 | 27-JUL-16:10 |
| Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Cooling:Electricity | 395.10 | 0.00 | 08-JAN-06:50 | 30617.47 | 27-JUL-16:00 |
| General:Cooling:Electricity | 395.10 | 0.00 | 08-JAN-06:50 | 30617.47 | 27-JUL-16:00 |
| ExteriorLights:Electricity | 50.09 | 0.00 | 01-JAN-07:20 | 3183.33 | 01-JAN-00:10 |
| General:ExteriorLights:Electricity | 50.09 | 0.00 | 01-JAN-07:20 | 3183.33 | 01-JAN-00:10 |
| Electricity:Plant | 356.45 | 1950.00 | 01-JAN-00:10 | 37016.31 | 08-JAN-07:20 |
| WaterSystems:Electricity | 356.45 | 1950.00 | 01-JAN-00:10 | 37016.31 | 08-JAN-07:20 |
| Water Heater:WaterSystems:Electricity | 356.45 | 1950.00 | 01-JAN-00:10 | 37016.31 | 08-JAN-07:20 |
| Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
| NaturalGas:Facility | 1.85 | 0.00 | 01-JAN-00:10 | 15306.27 | 04-FEB-07:00 |
| NaturalGas:HVAC | 1.85 | 0.00 | 01-JAN-00:10 | 15306.27 | 04-FEB-07:00 |
| Heating:NaturalGas | 1.85 | 0.00 | 01-JAN-00:10 | 15306.27 | 04-FEB-07:00 |
| General:Heating:NaturalGas | 1.85 | 0.00 | 01-JAN-00:10 | 15306.27 | 04-FEB-07:00 |
| Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
| None |
| Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
| Water:Facility | 1875.32 | 0.00 | 01-JAN-02:10 | 0.00 | 01-JAN-07:10 |
| Water:Plant | 1875.32 | 0.00 | 01-JAN-02:10 | 0.00 | 01-JAN-07:10 |
| WaterSystems:Water | 1875.32 | 0.00 | 01-JAN-02:10 | 0.00 | 01-JAN-07:10 |
| Water Heater:WaterSystems:Water | 1875.32 | 0.00 | 01-JAN-02:10 | 0.00 | 01-JAN-07:10 |
| MainsWater:Facility | 1875.32 | 0.00 | 01-JAN-02:10 | 0.00 | 01-JAN-07:10 |
| MainsWater:Plant | 1875.32 | 0.00 | 01-JAN-02:10 | 0.00 | 01-JAN-07:10 |
| WaterSystems:MainsWater | 1875.32 | 0.00 | 01-JAN-02:10 | 0.00 | 01-JAN-07:10 |
| Water Heater:WaterSystems:MainsWater | 1875.32 | 0.00 | 01-JAN-02:10 | 0.00 | 01-JAN-07:10 |
| Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
| Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
| CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
| Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
| None |
| Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
| None |
| Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
| EnergyTransfer:Facility | 2570.86 | 4292.45 | 18-MAR-06:00 | 181075.37 | 20-SEP-14:10 |
| EnergyTransfer:Building | 992.19 | 3907.00 | 18-MAR-06:00 | 66504.59 | 29-JUL-16:20 |
| EnergyTransfer:Zone:G SW APARTMENT | 34.18 | 110.38 | 18-MAR-06:50 | 2350.95 | 30-SEP-16:10 |
| Heating:EnergyTransfer | 4.98 | 0.00 | 01-JAN-01:00 | 7758.99 | 04-FEB-07:00 |
| Heating:EnergyTransfer:Zone:G SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:Heating:EnergyTransfer | 4.98 | 0.00 | 01-JAN-01:00 | 7758.99 | 04-FEB-07:00 |
| General:Heating:EnergyTransfer:Zone:G SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Cooling:EnergyTransfer | 987.20 | 3765.55 | 18-MAR-06:00 | 66504.59 | 29-JUL-16:20 |
| Cooling:EnergyTransfer:Zone:G SW APARTMENT | 34.18 | 110.38 | 18-MAR-06:50 | 2350.95 | 30-SEP-16:10 |
| General:Cooling:EnergyTransfer | 987.20 | 3765.55 | 18-MAR-06:00 | 66504.59 | 29-JUL-16:20 |
| General:Cooling:EnergyTransfer:Zone:G SW APARTMENT | 34.18 | 110.38 | 18-MAR-06:50 | 2350.95 | 30-SEP-16:10 |
| EnergyTransfer:Zone:G NW APARTMENT | 29.68 | 43.01 | 06-FEB-09:50 | 2173.68 | 27-JUL-17:20 |
| Heating:EnergyTransfer:Zone:G NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:Heating:EnergyTransfer:Zone:G NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Cooling:EnergyTransfer:Zone:G NW APARTMENT | 29.68 | 43.01 | 06-FEB-09:50 | 2173.68 | 27-JUL-17:20 |
| General:Cooling:EnergyTransfer:Zone:G NW APARTMENT | 29.68 | 43.01 | 06-FEB-09:50 | 2173.68 | 27-JUL-17:20 |
| EnergyTransfer:Zone:OFFICE | 26.85 | 0.03 | 16-JAN-20:30 | 4358.60 | 11-SEP-08:20 |
| Heating:EnergyTransfer:Zone:OFFICE | 4.34 | 0.00 | 01-JAN-01:00 | 611.06 | 28-JUL-17:40 |
| General:Heating:EnergyTransfer:Zone:OFFICE | 4.34 | 0.00 | 01-JAN-01:00 | 611.06 | 28-JUL-17:40 |
| Cooling:EnergyTransfer:Zone:OFFICE | 22.50 | 0.00 | 01-JAN-00:10 | 4358.60 | 11-SEP-08:20 |
| General:Cooling:EnergyTransfer:Zone:OFFICE | 22.50 | 0.00 | 01-JAN-00:10 | 4358.60 | 11-SEP-08:20 |
| EnergyTransfer:Zone:G NE APARTMENT | 29.82 | 50.42 | 05-FEB-14:00 | 1974.67 | 29-JUL-16:30 |
| Heating:EnergyTransfer:Zone:G NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:Heating:EnergyTransfer:Zone:G NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Cooling:EnergyTransfer:Zone:G NE APARTMENT | 29.82 | 50.42 | 05-FEB-14:00 | 1974.67 | 29-JUL-16:30 |
| General:Cooling:EnergyTransfer:Zone:G NE APARTMENT | 29.82 | 50.42 | 05-FEB-14:00 | 1974.67 | 29-JUL-16:30 |
| EnergyTransfer:Zone:G N1 APARTMENT | 25.55 | 56.34 | 05-FEB-13:50 | 1557.33 | 29-JUL-17:20 |
| Heating:EnergyTransfer:Zone:G N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:Heating:EnergyTransfer:Zone:G N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Cooling:EnergyTransfer:Zone:G N1 APARTMENT | 25.55 | 56.34 | 05-FEB-13:50 | 1557.33 | 29-JUL-17:20 |
| General:Cooling:EnergyTransfer:Zone:G N1 APARTMENT | 25.55 | 56.34 | 05-FEB-13:50 | 1557.33 | 29-JUL-17:20 |
| EnergyTransfer:Zone:G N2 APARTMENT | 25.56 | 59.02 | 05-FEB-13:40 | 1555.07 | 29-JUL-17:20 |
| Heating:EnergyTransfer:Zone:G N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:Heating:EnergyTransfer:Zone:G N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Cooling:EnergyTransfer:Zone:G N2 APARTMENT | 25.56 | 59.02 | 05-FEB-13:40 | 1555.07 | 29-JUL-17:20 |
| General:Cooling:EnergyTransfer:Zone:G N2 APARTMENT | 25.56 | 59.02 | 05-FEB-13:40 | 1555.07 | 29-JUL-17:20 |
| EnergyTransfer:Zone:G S1 APARTMENT | 30.40 | 167.69 | 17-MAR-09:30 | 1821.30 | 22-NOV-12:40 |
| Heating:EnergyTransfer:Zone:G S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:Heating:EnergyTransfer:Zone:G S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Cooling:EnergyTransfer:Zone:G S1 APARTMENT | 30.40 | 167.69 | 17-MAR-09:30 | 1821.30 | 22-NOV-12:40 |
| General:Cooling:EnergyTransfer:Zone:G S1 APARTMENT | 30.40 | 167.69 | 17-MAR-09:30 | 1821.30 | 22-NOV-12:40 |
| EnergyTransfer:Zone:G S2 APARTMENT | 33.27 | 182.21 | 17-MAR-09:20 | 1969.55 | 02-JAN-14:30 |
| Heating:EnergyTransfer:Zone:G S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:Heating:EnergyTransfer:Zone:G S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Cooling:EnergyTransfer:Zone:G S2 APARTMENT | 33.27 | 182.21 | 17-MAR-09:20 | 1969.55 | 02-JAN-14:30 |
| General:Cooling:EnergyTransfer:Zone:G S2 APARTMENT | 33.27 | 182.21 | 17-MAR-09:20 | 1969.55 | 02-JAN-14:30 |
| EnergyTransfer:Zone:M SW APARTMENT | 71.16 | 174.37 | 16-DEC-11:00 | 5126.92 | 30-SEP-16:10 |
| Heating:EnergyTransfer:Zone:M SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:Heating:EnergyTransfer:Zone:M SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Cooling:EnergyTransfer:Zone:M SW APARTMENT | 71.16 | 174.37 | 16-DEC-11:00 | 5126.92 | 30-SEP-16:10 |
| General:Cooling:EnergyTransfer:Zone:M SW APARTMENT | 71.16 | 174.37 | 16-DEC-11:00 | 5126.92 | 30-SEP-16:10 |
| EnergyTransfer:Zone:M NW APARTMENT | 61.56 | 56.42 | 16-DEC-13:40 | 4923.83 | 29-MAY-16:40 |
| Heating:EnergyTransfer:Zone:M NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:Heating:EnergyTransfer:Zone:M NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Cooling:EnergyTransfer:Zone:M NW APARTMENT | 61.56 | 56.42 | 16-DEC-13:40 | 4923.83 | 29-MAY-16:40 |
| General:Cooling:EnergyTransfer:Zone:M NW APARTMENT | 61.56 | 56.42 | 16-DEC-13:40 | 4923.83 | 29-MAY-16:40 |
| EnergyTransfer:Zone:M SE APARTMENT | 71.47 | 201.94 | 01-FEB-07:20 | 4767.16 | 22-NOV-12:30 |
| Heating:EnergyTransfer:Zone:M SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:Heating:EnergyTransfer:Zone:M SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Cooling:EnergyTransfer:Zone:M SE APARTMENT | 71.47 | 201.94 | 01-FEB-07:20 | 4767.16 | 22-NOV-12:30 |
| General:Cooling:EnergyTransfer:Zone:M SE APARTMENT | 71.47 | 201.94 | 01-FEB-07:20 | 4767.16 | 22-NOV-12:30 |
| EnergyTransfer:Zone:M NE APARTMENT | 61.82 | 36.05 | 16-DEC-14:00 | 4245.28 | 29-JUL-16:10 |
| Heating:EnergyTransfer:Zone:M NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:Heating:EnergyTransfer:Zone:M NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Cooling:EnergyTransfer:Zone:M NE APARTMENT | 61.82 | 36.05 | 16-DEC-14:00 | 4245.28 | 29-JUL-16:10 |
| General:Cooling:EnergyTransfer:Zone:M NE APARTMENT | 61.82 | 36.05 | 16-DEC-14:00 | 4245.28 | 29-JUL-16:10 |
| EnergyTransfer:Zone:M N1 APARTMENT | 52.10 | 85.18 | 05-FEB-14:00 | 3271.25 | 29-MAY-17:10 |
| Heating:EnergyTransfer:Zone:M N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:Heating:EnergyTransfer:Zone:M N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Cooling:EnergyTransfer:Zone:M N1 APARTMENT | 52.10 | 85.18 | 05-FEB-14:00 | 3271.25 | 29-MAY-17:10 |
| General:Cooling:EnergyTransfer:Zone:M N1 APARTMENT | 52.10 | 85.18 | 05-FEB-14:00 | 3271.25 | 29-MAY-17:10 |
| EnergyTransfer:Zone:M N2 APARTMENT | 52.13 | 86.17 | 05-FEB-14:00 | 3260.25 | 29-MAY-17:10 |
| Heating:EnergyTransfer:Zone:M N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:Heating:EnergyTransfer:Zone:M N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Cooling:EnergyTransfer:Zone:M N2 APARTMENT | 52.13 | 86.17 | 05-FEB-14:00 | 3260.25 | 29-MAY-17:10 |
| General:Cooling:EnergyTransfer:Zone:M N2 APARTMENT | 52.13 | 86.17 | 05-FEB-14:00 | 3260.25 | 29-MAY-17:10 |
| EnergyTransfer:Zone:M S1 APARTMENT | 62.11 | 318.32 | 06-FEB-06:30 | 4003.89 | 02-JAN-14:30 |
| Heating:EnergyTransfer:Zone:M S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:Heating:EnergyTransfer:Zone:M S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Cooling:EnergyTransfer:Zone:M S1 APARTMENT | 62.11 | 318.32 | 06-FEB-06:30 | 4003.89 | 02-JAN-14:30 |
| General:Cooling:EnergyTransfer:Zone:M S1 APARTMENT | 62.11 | 318.32 | 06-FEB-06:30 | 4003.89 | 02-JAN-14:30 |
| EnergyTransfer:Zone:M S2 APARTMENT | 62.13 | 318.36 | 06-FEB-06:30 | 4014.84 | 22-NOV-12:30 |
| Heating:EnergyTransfer:Zone:M S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:Heating:EnergyTransfer:Zone:M S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Cooling:EnergyTransfer:Zone:M S2 APARTMENT | 62.13 | 318.36 | 06-FEB-06:30 | 4014.84 | 22-NOV-12:30 |
| General:Cooling:EnergyTransfer:Zone:M S2 APARTMENT | 62.13 | 318.36 | 06-FEB-06:30 | 4014.84 | 22-NOV-12:30 |
| EnergyTransfer:Zone:T SW APARTMENT | 37.80 | 1.71 | 20-MAR-08:10 | 3544.26 | 30-SEP-15:30 |
| Heating:EnergyTransfer:Zone:T SW APARTMENT | 0.09 | 0.00 | 01-JAN-00:10 | 1209.56 | 04-FEB-07:00 |
| General:Heating:EnergyTransfer:Zone:T SW APARTMENT | 0.09 | 0.00 | 01-JAN-00:10 | 1209.56 | 04-FEB-07:00 |
| Cooling:EnergyTransfer:Zone:T SW APARTMENT | 37.71 | 0.00 | 25-JAN-02:50 | 3544.26 | 30-SEP-15:30 |
| General:Cooling:EnergyTransfer:Zone:T SW APARTMENT | 37.71 | 0.00 | 25-JAN-02:50 | 3544.26 | 30-SEP-15:30 |
| EnergyTransfer:Zone:T NW APARTMENT | 33.06 | 0.08 | 17-MAR-08:00 | 3414.95 | 29-MAY-16:30 |
| Heating:EnergyTransfer:Zone:T NW APARTMENT | 0.18 | 0.00 | 01-JAN-00:10 | 1364.07 | 04-FEB-06:00 |
| General:Heating:EnergyTransfer:Zone:T NW APARTMENT | 0.18 | 0.00 | 01-JAN-00:10 | 1364.07 | 04-FEB-06:00 |
| Cooling:EnergyTransfer:Zone:T NW APARTMENT | 32.88 | 0.00 | 10-JAN-06:40 | 3414.95 | 29-MAY-16:30 |
| General:Cooling:EnergyTransfer:Zone:T NW APARTMENT | 32.88 | 0.00 | 10-JAN-06:40 | 3414.95 | 29-MAY-16:30 |
| EnergyTransfer:Zone:T SE APARTMENT | 37.86 | 0.01 | 26-JAN-04:20 | 3219.72 | 30-SEP-14:00 |
| Heating:EnergyTransfer:Zone:T SE APARTMENT | 0.09 | 0.00 | 01-JAN-00:10 | 1230.16 | 04-FEB-07:00 |
| General:Heating:EnergyTransfer:Zone:T SE APARTMENT | 0.09 | 0.00 | 01-JAN-00:10 | 1230.16 | 04-FEB-07:00 |
| Cooling:EnergyTransfer:Zone:T SE APARTMENT | 37.78 | 0.00 | 25-JAN-02:20 | 3219.72 | 30-SEP-14:00 |
| General:Cooling:EnergyTransfer:Zone:T SE APARTMENT | 37.78 | 0.00 | 25-JAN-02:20 | 3219.72 | 30-SEP-14:00 |
| EnergyTransfer:Zone:T NE APARTMENT | 33.10 | 0.05 | 03-FEB-20:50 | 2951.92 | 29-JUL-16:10 |
| Heating:EnergyTransfer:Zone:T NE APARTMENT | 0.16 | 0.00 | 01-JAN-00:10 | 1387.84 | 04-FEB-06:00 |
| General:Heating:EnergyTransfer:Zone:T NE APARTMENT | 0.16 | 0.00 | 01-JAN-00:10 | 1387.84 | 04-FEB-06:00 |
| Cooling:EnergyTransfer:Zone:T NE APARTMENT | 32.93 | 0.00 | 09-JAN-07:00 | 2951.92 | 29-JUL-16:10 |
| General:Cooling:EnergyTransfer:Zone:T NE APARTMENT | 32.93 | 0.00 | 09-JAN-07:00 | 2951.92 | 29-JUL-16:10 |
| EnergyTransfer:Zone:T N1 APARTMENT | 27.66 | 0.20 | 03-FEB-23:10 | 2336.78 | 29-JUL-16:20 |
| Heating:EnergyTransfer:Zone:T N1 APARTMENT | 0.05 | 0.00 | 01-JAN-00:10 | 730.70 | 04-FEB-06:00 |
| General:Heating:EnergyTransfer:Zone:T N1 APARTMENT | 0.05 | 0.00 | 01-JAN-00:10 | 730.70 | 04-FEB-06:00 |
| Cooling:EnergyTransfer:Zone:T N1 APARTMENT | 27.62 | 0.00 | 23-JAN-09:50 | 2336.78 | 29-JUL-16:20 |
| General:Cooling:EnergyTransfer:Zone:T N1 APARTMENT | 27.62 | 0.00 | 23-JAN-09:50 | 2336.78 | 29-JUL-16:20 |
| EnergyTransfer:Zone:T N2 APARTMENT | 27.68 | 0.03 | 27-NOV-11:00 | 2330.04 | 29-JUL-16:20 |
| Heating:EnergyTransfer:Zone:T N2 APARTMENT | 0.05 | 0.00 | 01-JAN-00:10 | 733.60 | 04-FEB-06:00 |
| General:Heating:EnergyTransfer:Zone:T N2 APARTMENT | 0.05 | 0.00 | 01-JAN-00:10 | 733.60 | 04-FEB-06:00 |
| Cooling:EnergyTransfer:Zone:T N2 APARTMENT | 27.63 | 0.00 | 23-JAN-09:50 | 2330.04 | 29-JUL-16:20 |
| General:Cooling:EnergyTransfer:Zone:T N2 APARTMENT | 27.63 | 0.00 | 23-JAN-09:50 | 2330.04 | 29-JUL-16:20 |
| EnergyTransfer:Zone:T S1 APARTMENT | 32.60 | 0.16 | 16-MAR-08:30 | 2695.88 | 30-SEP-14:00 |
| Heating:EnergyTransfer:Zone:T S1 APARTMENT | 0.01 | 0.00 | 01-JAN-00:10 | 561.71 | 04-FEB-07:00 |
| General:Heating:EnergyTransfer:Zone:T S1 APARTMENT | 0.01 | 0.00 | 01-JAN-00:10 | 561.71 | 04-FEB-07:00 |
| Cooling:EnergyTransfer:Zone:T S1 APARTMENT | 32.59 | 0.00 | 25-JAN-06:40 | 2695.88 | 30-SEP-14:00 |
| General:Cooling:EnergyTransfer:Zone:T S1 APARTMENT | 32.59 | 0.00 | 25-JAN-06:40 | 2695.88 | 30-SEP-14:00 |
| EnergyTransfer:Zone:T S2 APARTMENT | 32.62 | 1.14 | 16-MAR-03:20 | 2698.67 | 30-SEP-14:00 |
| Heating:EnergyTransfer:Zone:T S2 APARTMENT | 0.01 | 0.00 | 01-JAN-00:10 | 564.04 | 04-FEB-07:00 |
| General:Heating:EnergyTransfer:Zone:T S2 APARTMENT | 0.01 | 0.00 | 01-JAN-00:10 | 564.04 | 04-FEB-07:00 |
| Cooling:EnergyTransfer:Zone:T S2 APARTMENT | 32.61 | 0.00 | 25-JAN-06:40 | 2698.67 | 30-SEP-14:00 |
| General:Cooling:EnergyTransfer:Zone:T S2 APARTMENT | 32.61 | 0.00 | 25-JAN-06:40 | 2698.67 | 30-SEP-14:00 |
| EnergyTransfer:Zone:T CORRIDOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Heating:EnergyTransfer:Zone:T CORRIDOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:Heating:EnergyTransfer:Zone:T CORRIDOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Cooling:EnergyTransfer:Zone:T CORRIDOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:Cooling:EnergyTransfer:Zone:T CORRIDOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| EnergyTransfer:Zone:G CORRIDOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Heating:EnergyTransfer:Zone:G CORRIDOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:Heating:EnergyTransfer:Zone:G CORRIDOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Cooling:EnergyTransfer:Zone:G CORRIDOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:Cooling:EnergyTransfer:Zone:G CORRIDOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| EnergyTransfer:Zone:M CORRIDOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Heating:EnergyTransfer:Zone:M CORRIDOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:Heating:EnergyTransfer:Zone:M CORRIDOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Cooling:EnergyTransfer:Zone:M CORRIDOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:Cooling:EnergyTransfer:Zone:M CORRIDOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| EnergyTransfer:HVAC | 1578.67 | 0.00 | 08-JAN-06:50 | 115330.02 | 20-SEP-14:10 |
| HeatRecoveryForHeating:EnergyTransfer | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 21-MAY-14:40 |
| HeatRecoveryForCooling:EnergyTransfer | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 11-MAY-11:10 |
| HeatingCoils:EnergyTransfer | 1.48 | 0.00 | 01-JAN-00:10 | 12245.01 | 04-FEB-07:00 |
| CoolingCoils:EnergyTransfer | 1577.19 | 0.00 | 08-JAN-06:50 | 115330.02 | 20-SEP-14:10 |
| PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 09:14:58
Annual Building Sensible Heat Gain Components| HVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
| G SW APARTMENT | 2.445 | -1.282 | 0.000 | -35.344 | 0.000 | 0.000 | 3.565 | 1.454 | 12.213 | 10.214 | 0.000 | 1.064 | 8.609 | 0.000 | -1.717 | 0.000 | -1.221 | 0.000 |
| G NW APARTMENT | 2.446 | -1.254 | 0.000 | -30.871 | 0.000 | 0.000 | 3.618 | 1.454 | 12.213 | 6.968 | 0.000 | 1.064 | 7.290 | 0.000 | -1.721 | 0.000 | -1.207 | 0.000 |
| OFFICE | 0.000 | 0.000 | 4.342 | -22.502 | 0.000 | 0.000 | 1.962 | 7.396 | 9.469 | 9.492 | 0.000 | 0.515 | 0.000 | 0.000 | -2.768 | 0.000 | -1.517 | -6.387 |
| G NE APARTMENT | 2.445 | -1.258 | 0.000 | -31.009 | 0.000 | 0.000 | 3.618 | 1.454 | 12.213 | 7.063 | 0.000 | 1.064 | 7.263 | 0.000 | -1.640 | 0.000 | -1.213 | 0.000 |
| G N1 APARTMENT | 2.446 | -1.276 | 0.000 | -26.720 | 0.000 | 0.000 | 3.613 | 1.454 | 12.213 | 3.113 | 0.000 | 0.642 | 6.512 | 0.000 | -1.047 | 0.000 | -0.949 | 0.000 |
| G N2 APARTMENT | 2.446 | -1.277 | 0.000 | -26.732 | 0.000 | 0.000 | 3.613 | 1.454 | 12.213 | 3.112 | 0.000 | 0.642 | 6.525 | 0.000 | -1.047 | 0.000 | -0.949 | 0.000 |
| G S1 APARTMENT | 2.445 | -1.293 | 0.000 | -31.554 | 0.000 | 0.000 | 3.562 | 1.454 | 12.213 | 6.397 | 0.000 | 0.642 | 8.105 | 0.000 | -1.022 | 0.000 | -0.948 | 0.000 |
| G S2 APARTMENT | 2.444 | -1.294 | 0.000 | -34.423 | 0.000 | 0.000 | 3.562 | 1.454 | 12.213 | 6.369 | 0.000 | 0.642 | 11.026 | 0.000 | -1.043 | 0.000 | -0.949 | 0.000 |
| M SW APARTMENT | 4.892 | -2.543 | 0.000 | -73.509 | 0.000 | 0.000 | 7.136 | 2.908 | 24.426 | 20.455 | 0.000 | 3.040 | 19.759 | 0.000 | -3.342 | 0.000 | -3.221 | 0.000 |
| M NW APARTMENT | 4.893 | -2.469 | 0.006 | -63.993 | 0.000 | 0.000 | 7.245 | 2.908 | 24.426 | 13.994 | 0.000 | 3.040 | 16.478 | 0.000 | -3.364 | 0.000 | -3.164 | 0.000 |
| M SE APARTMENT | 4.891 | -2.548 | 0.000 | -73.812 | 0.000 | 0.000 | 7.136 | 2.908 | 24.426 | 20.722 | 0.000 | 3.040 | 19.718 | 0.000 | -3.250 | 0.000 | -3.229 | 0.000 |
| M NE APARTMENT | 4.892 | -2.480 | 0.006 | -64.239 | 0.000 | 0.000 | 7.245 | 2.908 | 24.426 | 14.186 | 0.000 | 3.040 | 16.404 | 0.000 | -3.201 | 0.000 | -3.186 | 0.000 |
| M N1 APARTMENT | 4.893 | -2.536 | 0.000 | -54.460 | 0.000 | 0.000 | 7.230 | 2.908 | 24.426 | 6.267 | 0.000 | 1.834 | 13.948 | 0.000 | -2.063 | 0.000 | -2.447 | 0.000 |
| M N2 APARTMENT | 4.893 | -2.537 | 0.000 | -54.485 | 0.000 | 0.000 | 7.230 | 2.908 | 24.426 | 6.266 | 0.000 | 1.834 | 13.975 | 0.000 | -2.062 | 0.000 | -2.448 | 0.000 |
| M S1 APARTMENT | 4.892 | -2.580 | 0.000 | -64.418 | 0.000 | 0.000 | 7.126 | 2.908 | 24.426 | 12.806 | 0.000 | 1.834 | 17.449 | 0.000 | -1.995 | 0.000 | -2.448 | 0.000 |
| M S2 APARTMENT | 4.892 | -2.580 | 0.000 | -64.441 | 0.000 | 0.000 | 7.126 | 2.908 | 24.426 | 12.805 | 0.000 | 1.834 | 17.472 | 0.000 | -1.995 | 0.000 | -2.448 | 0.000 |
| T SW APARTMENT | 2.446 | -1.149 | 0.214 | -39.127 | 0.000 | 0.000 | 3.598 | 1.454 | 12.213 | 10.044 | 0.000 | 1.987 | 11.760 | 0.000 | -1.547 | 0.000 | -1.894 | -0.000 |
| T NW APARTMENT | 2.447 | -1.082 | 0.374 | -34.440 | 0.000 | 0.000 | 3.658 | 1.454 | 12.213 | 6.852 | 0.000 | 1.987 | 9.874 | 0.000 | -1.536 | 0.000 | -1.800 | -0.000 |
| T SE APARTMENT | 2.445 | -1.156 | 0.198 | -39.180 | 0.000 | 0.000 | 3.598 | 1.454 | 12.213 | 10.171 | 0.000 | 1.987 | 11.686 | 0.000 | -1.503 | 0.000 | -1.914 | -0.000 |
| T NE APARTMENT | 2.446 | -1.089 | 0.337 | -34.467 | 0.000 | 0.000 | 3.658 | 1.454 | 12.213 | 6.952 | 0.000 | 1.987 | 9.796 | 0.000 | -1.465 | 0.000 | -1.823 | -0.000 |
| T N1 APARTMENT | 2.446 | -1.123 | 0.150 | -29.045 | 0.000 | 0.000 | 3.648 | 1.454 | 12.213 | 3.063 | 0.000 | 1.199 | 8.320 | 0.000 | -0.950 | 0.000 | -1.375 | -0.000 |
| T N2 APARTMENT | 2.446 | -1.123 | 0.150 | -29.058 | 0.000 | 0.000 | 3.648 | 1.454 | 12.213 | 3.062 | 0.000 | 1.199 | 8.335 | 0.000 | -0.949 | 0.000 | -1.376 | -0.000 |
| T S1 APARTMENT | 2.446 | -1.197 | 0.058 | -33.883 | 0.000 | 0.000 | 3.586 | 1.454 | 12.213 | 6.304 | 0.000 | 1.199 | 10.209 | 0.000 | -0.940 | 0.000 | -1.449 | -0.000 |
| T S2 APARTMENT | 2.446 | -1.197 | 0.058 | -33.899 | 0.000 | 0.000 | 3.586 | 1.454 | 12.213 | 6.303 | 0.000 | 1.199 | 10.226 | 0.000 | -0.939 | 0.000 | -1.449 | -0.000 |
| T CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 5.340 | 11.688 | 0.000 | 0.893 | 0.000 | 0.134 | 0.000 | 0.000 | -0.193 | 0.000 | -0.334 | -17.528 |
| G CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 5.094 | 11.688 | 3.530 | 2.616 | 0.000 | 1.768 | 0.000 | 0.000 | -0.648 | 0.000 | -5.650 | -18.396 |
| M CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 10.540 | 23.376 | 0.000 | 1.798 | 0.000 | 0.245 | 0.000 | 0.000 | -0.412 | 0.000 | -0.562 | -34.986 |
| Total Facility | 75.825 | -38.323 | 5.893 | -1025.613 | 0.000 | 0.000 | 134.543 | 99.229 | 391.594 | 218.285 | 0.000 | 40.659 | 270.738 | 0.000 | -44.360 | 0.000 | -51.171 | -77.299 |
| Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
| G SW APARTMENT | 30-SEP-16:10 | 0.00 | 244.21 | 0.00 | -2595.20 | 0.00 | 0.00 | 167.23 | 86.80 | 588.62 | 1079.45 | 0.00 | 118.08 | 310.82 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| G NW APARTMENT | 27-JUL-17:17 | 0.00 | 329.02 | 0.00 | -2502.93 | 0.00 | 0.00 | 145.49 | 117.18 | 588.62 | 896.65 | 0.00 | 212.57 | 213.39 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| OFFICE | 12-DEC-09:02 | 0.00 | 0.00 | 0.00 | -6698.23 | 0.00 | 0.00 | 284.40 | 582.92 | 588.62 | 879.89 | 0.00 | 0.00 | 4529.28 | 0.00 | -0.00 | 0.00 | -166.87 | 0.00 |
| G NE APARTMENT | 29-JUL-16:30 | 0.00 | 371.33 | 0.00 | -2346.00 | 0.00 | 0.00 | 86.96 | 86.80 | 588.62 | 643.72 | 0.00 | 147.86 | 420.70 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| G N1 APARTMENT | 29-JUL-17:20 | 0.00 | 340.56 | 0.00 | -1898.18 | 0.00 | 0.00 | 145.49 | 117.18 | 588.62 | 285.19 | 0.00 | 93.73 | 327.41 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| G N2 APARTMENT | 29-JUL-17:20 | 0.00 | 340.56 | 0.00 | -1895.93 | 0.00 | 0.00 | 145.49 | 117.18 | 588.62 | 285.22 | 0.00 | 93.73 | 325.13 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| G S1 APARTMENT | 22-NOV-12:40 | 0.00 | 134.96 | 0.00 | -1956.26 | 0.00 | 0.00 | 0.00 | 17.36 | 406.15 | 1314.88 | 0.00 | 76.51 | 6.40 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| G S2 APARTMENT | 02-JAN-14:30 | 0.00 | 176.32 | 0.00 | -2146.22 | 0.00 | 0.00 | 83.61 | 17.36 | 382.60 | 1253.74 | 0.00 | 31.79 | 200.80 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| M SW APARTMENT | 30-SEP-16:07 | 0.00 | 488.49 | 0.00 | -5615.87 | 0.00 | 0.00 | 334.45 | 173.60 | 1177.25 | 2160.26 | 0.00 | 338.41 | 943.41 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| M NW APARTMENT | 29-MAY-16:40 | 0.00 | 566.78 | 0.00 | -5490.77 | 0.00 | 0.00 | 173.92 | 173.60 | 1177.25 | 2362.43 | 0.00 | 794.04 | 242.76 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| M SE APARTMENT | 22-NOV-12:30 | 0.00 | 263.65 | 0.00 | -5030.87 | 0.00 | 0.00 | 0.00 | 34.72 | 812.30 | 3088.86 | 0.00 | 349.39 | 481.96 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| M NE APARTMENT | 29-JUL-16:03 | 0.00 | 768.37 | 0.00 | -5014.17 | 0.00 | 0.00 | 173.92 | 173.60 | 1177.25 | 1364.22 | 0.00 | 439.09 | 917.72 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| M N1 APARTMENT | 29-MAY-17:07 | 0.00 | 526.42 | 0.00 | -3798.26 | 0.00 | 0.00 | 290.97 | 234.36 | 1177.25 | 709.99 | 0.00 | 452.05 | 407.22 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| M N2 APARTMENT | 29-MAY-17:07 | 0.00 | 526.42 | 0.00 | -3787.27 | 0.00 | 0.00 | 290.97 | 234.36 | 1177.25 | 710.11 | 0.00 | 452.05 | 396.11 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| M S1 APARTMENT | 02-JAN-14:30 | 0.00 | 352.71 | 0.00 | -4357.35 | 0.00 | 0.00 | 167.23 | 34.72 | 765.21 | 2507.36 | 0.00 | 91.00 | 439.13 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| M S2 APARTMENT | 22-NOV-12:30 | 0.00 | 263.59 | 0.00 | -4278.38 | 0.00 | 0.00 | 0.00 | 34.72 | 812.30 | 2789.27 | 0.00 | 210.74 | 167.76 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| T SW APARTMENT | 30-SEP-15:30 | 0.00 | 246.73 | 0.00 | -3791.07 | 0.00 | 0.00 | 167.23 | 60.76 | 470.90 | 1388.54 | 0.00 | 208.23 | 1248.68 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| T NW APARTMENT | 29-MAY-16:30 | 0.00 | 291.79 | 0.00 | -3706.83 | 0.00 | 0.00 | 86.96 | 86.80 | 588.62 | 1199.04 | 0.00 | 528.14 | 925.47 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| T SE APARTMENT | 30-SEP-14:00 | 0.00 | 246.80 | 0.00 | -3466.74 | 0.00 | 0.00 | 83.61 | 17.36 | 382.60 | 1087.72 | 0.00 | 264.36 | 1384.29 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| T NE APARTMENT | 29-JUL-16:03 | 0.00 | 383.99 | 0.00 | -3336.08 | 0.00 | 0.00 | 86.96 | 86.80 | 588.62 | 658.90 | 0.00 | 289.40 | 1241.41 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| T N1 APARTMENT | 29-JUL-16:13 | 0.00 | 377.69 | 0.00 | -2714.71 | 0.00 | 0.00 | 86.96 | 86.80 | 588.62 | 407.41 | 0.00 | 171.59 | 995.63 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| T N2 APARTMENT | 29-JUL-16:13 | 0.00 | 377.70 | 0.00 | -2707.97 | 0.00 | 0.00 | 86.96 | 86.80 | 588.62 | 407.50 | 0.00 | 171.59 | 988.81 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| T S1 APARTMENT | 30-SEP-14:00 | 0.00 | 246.81 | 0.00 | -2942.75 | 0.00 | 0.00 | 83.61 | 17.36 | 382.60 | 896.86 | 0.00 | 159.45 | 1156.05 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| T S2 APARTMENT | 30-SEP-14:00 | 0.00 | 246.80 | 0.00 | -2945.53 | 0.00 | 0.00 | 83.61 | 17.36 | 382.60 | 896.81 | 0.00 | 159.45 | 1158.89 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| T CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| G CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Total Facility | 27-JUL-16:08 | 0.00 | 11425.19 | 0.00 | -78199.72 | 0.00 | 0.00 | 1845.53 | 4289.87 | 18750.02 | 20727.51 | 0.00 | 11008.09 | 10153.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
| G SW APARTMENT | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| G NW APARTMENT | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| OFFICE | 28-JUL-16:13 | 0.00 | 0.00 | 735.05 | 0.00 | 0.00 | 0.00 | 0.00 | 116.58 | 294.31 | 487.78 | 0.00 | 61.19 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -1694.91 |
| G NE APARTMENT | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| G N1 APARTMENT | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| G N2 APARTMENT | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| G S1 APARTMENT | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| G S2 APARTMENT | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M SW APARTMENT | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M NW APARTMENT | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M SE APARTMENT | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M NE APARTMENT | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M N1 APARTMENT | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M N2 APARTMENT | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M S1 APARTMENT | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M S2 APARTMENT | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T SW APARTMENT | 04-FEB-07:00 | -488.11 | 0.00 | 1697.65 | 0.00 | 0.00 | 0.00 | 194.99 | 60.76 | 317.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -499.79 | 0.00 | -733.78 | -549.58 |
| T NW APARTMENT | 04-FEB-06:00 | -469.23 | 0.00 | 1833.18 | 0.00 | 0.00 | 0.00 | 194.99 | 56.42 | 253.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -489.44 | 0.00 | -766.81 | -612.22 |
| T SE APARTMENT | 04-FEB-07:00 | -488.11 | 0.00 | 1718.25 | 0.00 | 0.00 | 0.00 | 194.99 | 60.76 | 317.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -493.14 | 0.00 | -733.78 | -576.83 |
| T NE APARTMENT | 04-FEB-06:00 | -469.23 | 0.00 | 1856.95 | 0.00 | 0.00 | 0.00 | 194.99 | 56.42 | 253.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -483.08 | 0.00 | -766.81 | -642.34 |
| T N1 APARTMENT | 04-FEB-06:00 | -469.34 | 0.00 | 1199.98 | 0.00 | 0.00 | 0.00 | 194.99 | 56.42 | 253.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -300.85 | 0.00 | -462.52 | -471.78 |
| T N2 APARTMENT | 04-FEB-06:00 | -469.34 | 0.00 | 1202.89 | 0.00 | 0.00 | 0.00 | 194.99 | 56.42 | 253.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -300.78 | 0.00 | -462.52 | -474.76 |
| T S1 APARTMENT | 04-FEB-07:00 | -488.22 | 0.00 | 1049.92 | 0.00 | 0.00 | 0.00 | 194.99 | 60.76 | 317.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -304.64 | 0.00 | -442.60 | -388.08 |
| T S2 APARTMENT | 04-FEB-07:00 | -488.22 | 0.00 | 1052.25 | 0.00 | 0.00 | 0.00 | 194.99 | 60.76 | 317.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -304.57 | 0.00 | -442.60 | -390.46 |
| T CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| G CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Total Facility | 04-FEB-07:00 | -15994.38 | 375.52 | 12820.72 | -375.52 | 0.00 | 0.00 | 7119.55 | 3482.59 | 10216.13 | 0.00 | 0.00 | 0.00 | 13284.24 | 0.00 | -14294.02 | 0.00 | -16634.83 | 0.00 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 09:14:58
System Ventilation Requirements for Cooling| Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
| SPLIT GSW | 0.3473 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.3473 | 0.0747 | 1.0000 | Not calculated | 0.0260 | 0.0747 | ||
| SPLIT GNW | 0.3521 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.3521 | 0.0737 | 1.0000 | Not calculated | 0.0260 | 0.0737 | ||
| SPLIT OFFICE | 0.3734 | 0.0000 | 4.7495 | 1.0000 | Calculated from schedules | 0.0381 | 0.3734 | 0.1021 | 1.0000 | Not calculated | 0.0381 | 0.1021 | ||
| SPLIT GNE | 0.3256 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.3256 | 0.0797 | 1.0000 | Not calculated | 0.0260 | 0.0797 | ||
| SPLIT GN1 | 0.2949 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.2949 | 0.0880 | 1.0000 | Not calculated | 0.0260 | 0.0880 | ||
| SPLIT GN2 | 0.2944 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.2944 | 0.0882 | 1.0000 | Not calculated | 0.0260 | 0.0882 | ||
| SPLIT GS1 | 0.2904 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.2904 | 0.0894 | 1.0000 | Not calculated | 0.0260 | 0.0894 | ||
| SPLIT GS2 | 0.2925 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.2925 | 0.0887 | 1.0000 | Not calculated | 0.0260 | 0.0887 | ||
| SPLIT MSW | 0.7963 | 0.0000 | 5.0000 | 1.0000 | Calculated from schedules | 0.0519 | 0.7963 | 0.0652 | 1.0000 | Not calculated | 0.0519 | 0.0652 | ||
| SPLIT MNW | 0.8084 | 0.0000 | 5.0000 | 1.0000 | Calculated from schedules | 0.0519 | 0.8084 | 0.0642 | 1.0000 | Not calculated | 0.0519 | 0.0642 | ||
| SPLIT MSE | 0.7264 | 0.0000 | 5.0000 | 1.0000 | Calculated from schedules | 0.0519 | 0.7264 | 0.0715 | 1.0000 | Not calculated | 0.0519 | 0.0715 | ||
| SPLIT MNE | 0.7385 | 0.0000 | 5.0000 | 1.0000 | Calculated from schedules | 0.0519 | 0.7385 | 0.0703 | 1.0000 | Not calculated | 0.0519 | 0.0703 | ||
| SPLIT MN1 | 0.6664 | 0.0000 | 5.0000 | 1.0000 | Calculated from schedules | 0.0519 | 0.6664 | 0.0779 | 1.0000 | Not calculated | 0.0519 | 0.0779 | ||
| SPLIT MN2 | 0.6652 | 0.0000 | 5.0000 | 1.0000 | Calculated from schedules | 0.0519 | 0.6652 | 0.0780 | 1.0000 | Not calculated | 0.0519 | 0.0780 | ||
| SPLIT MS1 | 0.6549 | 0.0000 | 5.0000 | 1.0000 | Calculated from schedules | 0.0519 | 0.6549 | 0.0793 | 1.0000 | Not calculated | 0.0519 | 0.0793 | ||
| SPLIT MS2 | 0.6536 | 0.0000 | 5.0000 | 1.0000 | Calculated from schedules | 0.0519 | 0.6536 | 0.0794 | 1.0000 | Not calculated | 0.0519 | 0.0794 | ||
| SPLIT TSW | 0.4454 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.4454 | 0.0583 | 1.0000 | Not calculated | 0.0260 | 0.0583 | ||
| SPLIT TNW | 0.4568 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.4568 | 0.0568 | 1.0000 | Not calculated | 0.0260 | 0.0568 | ||
| SPLIT TSE | 0.3930 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.3930 | 0.0660 | 1.0000 | Not calculated | 0.0260 | 0.0660 | ||
| SPLIT TNE | 0.4042 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.4042 | 0.0642 | 1.0000 | Not calculated | 0.0260 | 0.0642 | ||
| SPLIT TN1 | 0.3758 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.3758 | 0.0691 | 1.0000 | Not calculated | 0.0260 | 0.0691 | ||
| SPLIT TN2 | 0.3742 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.3742 | 0.0694 | 1.0000 | Not calculated | 0.0260 | 0.0694 | ||
| SPLIT TS1 | 0.3647 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.3647 | 0.0712 | 1.0000 | Not calculated | 0.0260 | 0.0712 | ||
| SPLIT TS2 | 0.3630 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.3630 | 0.0715 | 1.0000 | Not calculated | 0.0260 | 0.0715 |
| Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
| SPLIT GSW | 0.3473 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.3473 | 1.0000 | 1.0000 | Not calculated | 0.0260 | 0.0747 | ||
| SPLIT GNW | 0.3521 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.3521 | 1.0000 | 1.0000 | Not calculated | 0.0260 | 0.0737 | ||
| SPLIT OFFICE | 0.3734 | 0.0000 | 4.7495 | 1.0000 | Calculated from schedules | 0.0381 | 0.3734 | 1.0000 | 1.0000 | Not calculated | 0.0381 | 0.1021 | ||
| SPLIT GNE | 0.3256 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.3256 | 1.0000 | 1.0000 | Not calculated | 0.0260 | 0.0797 | ||
| SPLIT GN1 | 0.2949 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.2949 | 1.0000 | 1.0000 | Not calculated | 0.0260 | 0.0880 | ||
| SPLIT GN2 | 0.2944 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.2944 | 1.0000 | 1.0000 | Not calculated | 0.0260 | 0.0882 | ||
| SPLIT GS1 | 0.2904 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.2904 | 1.0000 | 1.0000 | Not calculated | 0.0260 | 0.0894 | ||
| SPLIT GS2 | 0.2925 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.2925 | 1.0000 | 1.0000 | Not calculated | 0.0260 | 0.0887 | ||
| SPLIT MSW | 0.7963 | 0.0000 | 5.0000 | 1.0000 | Calculated from schedules | 0.0519 | 0.7963 | 1.0000 | 1.0000 | Not calculated | 0.0519 | 0.0652 | ||
| SPLIT MNW | 0.8084 | 0.0000 | 5.0000 | 1.0000 | Calculated from schedules | 0.0519 | 0.8084 | 1.0000 | 1.0000 | Not calculated | 0.0519 | 0.0642 | ||
| SPLIT MSE | 0.7264 | 0.0000 | 5.0000 | 1.0000 | Calculated from schedules | 0.0519 | 0.7264 | 1.0000 | 1.0000 | Not calculated | 0.0519 | 0.0715 | ||
| SPLIT MNE | 0.7385 | 0.0000 | 5.0000 | 1.0000 | Calculated from schedules | 0.0519 | 0.7385 | 1.0000 | 1.0000 | Not calculated | 0.0519 | 0.0703 | ||
| SPLIT MN1 | 0.6664 | 0.0000 | 5.0000 | 1.0000 | Calculated from schedules | 0.0519 | 0.6664 | 1.0000 | 1.0000 | Not calculated | 0.0519 | 0.0779 | ||
| SPLIT MN2 | 0.6652 | 0.0000 | 5.0000 | 1.0000 | Calculated from schedules | 0.0519 | 0.6652 | 1.0000 | 1.0000 | Not calculated | 0.0519 | 0.0780 | ||
| SPLIT MS1 | 0.6549 | 0.0000 | 5.0000 | 1.0000 | Calculated from schedules | 0.0519 | 0.6549 | 1.0000 | 1.0000 | Not calculated | 0.0519 | 0.0793 | ||
| SPLIT MS2 | 0.6536 | 0.0000 | 5.0000 | 1.0000 | Calculated from schedules | 0.0519 | 0.6536 | 1.0000 | 1.0000 | Not calculated | 0.0519 | 0.0794 | ||
| SPLIT TSW | 0.4454 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.4454 | 1.0000 | 1.0000 | Not calculated | 0.0260 | 0.0583 | ||
| SPLIT TNW | 0.4568 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.4568 | 1.0000 | 1.0000 | Not calculated | 0.0260 | 0.0568 | ||
| SPLIT TSE | 0.3930 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.3930 | 1.0000 | 1.0000 | Not calculated | 0.0260 | 0.0660 | ||
| SPLIT TNE | 0.4042 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.4042 | 1.0000 | 1.0000 | Not calculated | 0.0260 | 0.0642 | ||
| SPLIT TN1 | 0.3758 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.3758 | 1.0000 | 1.0000 | Not calculated | 0.0260 | 0.0691 | ||
| SPLIT TN2 | 0.3742 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.3742 | 1.0000 | 1.0000 | Not calculated | 0.0260 | 0.0694 | ||
| SPLIT TS1 | 0.3647 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.3647 | 1.0000 | 1.0000 | Not calculated | 0.0260 | 0.0712 | ||
| SPLIT TS2 | 0.3630 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.3630 | 1.0000 | 1.0000 | Not calculated | 0.0260 | 0.0715 |
| AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
| G SW APARTMENT | SPLIT GSW | 0.000000 | 2.5000 | 0.000294 | 88.25 | 0.0260 | 1.0000 | 0.0260 | 1.000 | 0.0260 |
| G NW APARTMENT | SPLIT GNW | 0.000000 | 2.5000 | 0.000294 | 88.25 | 0.0260 | 1.0000 | 0.0260 | 1.000 | 0.0260 |
| OFFICE | SPLIT OFFICE | 0.000000 | 4.7495 | 0.000432 | 88.25 | 0.0381 | 1.0000 | 0.0381 | 1.000 | 0.0381 |
| G NE APARTMENT | SPLIT GNE | 0.000000 | 2.5000 | 0.000294 | 88.25 | 0.0260 | 1.0000 | 0.0260 | 1.000 | 0.0260 |
| G N1 APARTMENT | SPLIT GN1 | 0.000000 | 2.5000 | 0.000294 | 88.25 | 0.0260 | 1.0000 | 0.0260 | 1.000 | 0.0260 |
| G N2 APARTMENT | SPLIT GN2 | 0.000000 | 2.5000 | 0.000294 | 88.25 | 0.0260 | 1.0000 | 0.0260 | 1.000 | 0.0260 |
| G S1 APARTMENT | SPLIT GS1 | 0.000000 | 2.5000 | 0.000294 | 88.25 | 0.0260 | 1.0000 | 0.0260 | 1.000 | 0.0260 |
| G S2 APARTMENT | SPLIT GS2 | 0.000000 | 2.5000 | 0.000294 | 88.25 | 0.0260 | 1.0000 | 0.0260 | 1.000 | 0.0260 |
| M SW APARTMENT | SPLIT MSW | 0.000000 | 5.0000 | 0.000294 | 176.50 | 0.0519 | 1.0000 | 0.0519 | 1.000 | 0.0519 |
| M NW APARTMENT | SPLIT MNW | 0.000000 | 5.0000 | 0.000294 | 176.50 | 0.0519 | 1.0000 | 0.0519 | 1.000 | 0.0519 |
| M SE APARTMENT | SPLIT MSE | 0.000000 | 5.0000 | 0.000294 | 176.50 | 0.0519 | 1.0000 | 0.0519 | 1.000 | 0.0519 |
| M NE APARTMENT | SPLIT MNE | 0.000000 | 5.0000 | 0.000294 | 176.50 | 0.0519 | 1.0000 | 0.0519 | 1.000 | 0.0519 |
| M N1 APARTMENT | SPLIT MN1 | 0.000000 | 5.0000 | 0.000294 | 176.50 | 0.0519 | 1.0000 | 0.0519 | 1.000 | 0.0519 |
| M N2 APARTMENT | SPLIT MN2 | 0.000000 | 5.0000 | 0.000294 | 176.50 | 0.0519 | 1.0000 | 0.0519 | 1.000 | 0.0519 |
| M S1 APARTMENT | SPLIT MS1 | 0.000000 | 5.0000 | 0.000294 | 176.50 | 0.0519 | 1.0000 | 0.0519 | 1.000 | 0.0519 |
| M S2 APARTMENT | SPLIT MS2 | 0.000000 | 5.0000 | 0.000294 | 176.50 | 0.0519 | 1.0000 | 0.0519 | 1.000 | 0.0519 |
| T SW APARTMENT | SPLIT TSW | 0.000000 | 2.5000 | 0.000294 | 88.25 | 0.0260 | 1.0000 | 0.0260 | 1.000 | 0.0260 |
| T NW APARTMENT | SPLIT TNW | 0.000000 | 2.5000 | 0.000294 | 88.25 | 0.0260 | 1.0000 | 0.0260 | 1.000 | 0.0260 |
| T SE APARTMENT | SPLIT TSE | 0.000000 | 2.5000 | 0.000294 | 88.25 | 0.0260 | 1.0000 | 0.0260 | 1.000 | 0.0260 |
| T NE APARTMENT | SPLIT TNE | 0.000000 | 2.5000 | 0.000294 | 88.25 | 0.0260 | 1.0000 | 0.0260 | 1.000 | 0.0260 |
| T N1 APARTMENT | SPLIT TN1 | 0.000000 | 2.5000 | 0.000294 | 88.25 | 0.0260 | 1.0000 | 0.0260 | 1.000 | 0.0260 |
| T N2 APARTMENT | SPLIT TN2 | 0.000000 | 2.5000 | 0.000294 | 88.25 | 0.0260 | 1.0000 | 0.0260 | 1.000 | 0.0260 |
| T S1 APARTMENT | SPLIT TS1 | 0.000000 | 2.5000 | 0.000294 | 88.25 | 0.0260 | 1.0000 | 0.0260 | 1.000 | 0.0260 |
| T S2 APARTMENT | SPLIT TS2 | 0.000000 | 2.5000 | 0.000294 | 88.25 | 0.0260 | 1.0000 | 0.0260 | 1.000 | 0.0260 |
| People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
| SPLIT GSW | 0.000000 | 2.50 | 0.000294 | 88.2493 | 0.0260 | 0.0260 | 0.0260 |
| SPLIT GNW | 0.000000 | 2.50 | 0.000294 | 88.2493 | 0.0260 | 0.0260 | 0.0260 |
| SPLIT OFFICE | 0.000000 | 4.75 | 0.000432 | 88.2493 | 0.0381 | 0.0381 | 0.0381 |
| SPLIT GNE | 0.000000 | 2.50 | 0.000294 | 88.2493 | 0.0260 | 0.0260 | 0.0260 |
| SPLIT GN1 | 0.000000 | 2.50 | 0.000294 | 88.2493 | 0.0260 | 0.0260 | 0.0260 |
| SPLIT GN2 | 0.000000 | 2.50 | 0.000294 | 88.2493 | 0.0260 | 0.0260 | 0.0260 |
| SPLIT GS1 | 0.000000 | 2.50 | 0.000294 | 88.2493 | 0.0260 | 0.0260 | 0.0260 |
| SPLIT GS2 | 0.000000 | 2.50 | 0.000294 | 88.2493 | 0.0260 | 0.0260 | 0.0260 |
| SPLIT MSW | 0.000000 | 5.00 | 0.000294 | 176.4985 | 0.0519 | 0.0519 | 0.0519 |
| SPLIT MNW | 0.000000 | 5.00 | 0.000294 | 176.4985 | 0.0519 | 0.0519 | 0.0519 |
| SPLIT MSE | 0.000000 | 5.00 | 0.000294 | 176.4985 | 0.0519 | 0.0519 | 0.0519 |
| SPLIT MNE | 0.000000 | 5.00 | 0.000294 | 176.4985 | 0.0519 | 0.0519 | 0.0519 |
| SPLIT MN1 | 0.000000 | 5.00 | 0.000294 | 176.4985 | 0.0519 | 0.0519 | 0.0519 |
| SPLIT MN2 | 0.000000 | 5.00 | 0.000294 | 176.4985 | 0.0519 | 0.0519 | 0.0519 |
| SPLIT MS1 | 0.000000 | 5.00 | 0.000294 | 176.4985 | 0.0519 | 0.0519 | 0.0519 |
| SPLIT MS2 | 0.000000 | 5.00 | 0.000294 | 176.4985 | 0.0519 | 0.0519 | 0.0519 |
| SPLIT TSW | 0.000000 | 2.50 | 0.000294 | 88.2493 | 0.0260 | 0.0260 | 0.0260 |
| SPLIT TNW | 0.000000 | 2.50 | 0.000294 | 88.2493 | 0.0260 | 0.0260 | 0.0260 |
| SPLIT TSE | 0.000000 | 2.50 | 0.000294 | 88.2493 | 0.0260 | 0.0260 | 0.0260 |
| SPLIT TNE | 0.000000 | 2.50 | 0.000294 | 88.2493 | 0.0260 | 0.0260 | 0.0260 |
| SPLIT TN1 | 0.000000 | 2.50 | 0.000294 | 88.2493 | 0.0260 | 0.0260 | 0.0260 |
| SPLIT TN2 | 0.000000 | 2.50 | 0.000294 | 88.2493 | 0.0260 | 0.0260 | 0.0260 |
| SPLIT TS1 | 0.000000 | 2.50 | 0.000294 | 88.2493 | 0.0260 | 0.0260 | 0.0260 |
| SPLIT TS2 | 0.000000 | 2.50 | 0.000294 | 88.2493 | 0.0260 | 0.0260 | 0.0260 |
| AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
| G SW APARTMENT | SPLIT GSW | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.3473 | 0.3473 | 0.3473 | No | 0.0260 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| G NW APARTMENT | SPLIT GNW | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.3521 | 0.3521 | 0.3521 | No | 0.0260 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| OFFICE | SPLIT OFFICE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.3734 | 0.3734 | 0.3734 | No | 0.0381 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| G NE APARTMENT | SPLIT GNE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.3256 | 0.3256 | 0.3256 | No | 0.0260 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| G N1 APARTMENT | SPLIT GN1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.2949 | 0.2949 | 0.2949 | No | 0.0260 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| G N2 APARTMENT | SPLIT GN2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.2944 | 0.2944 | 0.2944 | No | 0.0260 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| G S1 APARTMENT | SPLIT GS1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.2904 | 0.2904 | 0.2904 | No | 0.0260 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| G S2 APARTMENT | SPLIT GS2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.2925 | 0.2925 | 0.2925 | No | 0.0260 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| M SW APARTMENT | SPLIT MSW | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.7963 | 0.7963 | 0.7963 | No | 0.0519 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| M NW APARTMENT | SPLIT MNW | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8084 | 0.8084 | 0.8084 | No | 0.0519 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| M SE APARTMENT | SPLIT MSE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.7264 | 0.7264 | 0.7264 | No | 0.0519 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| M NE APARTMENT | SPLIT MNE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.7385 | 0.7385 | 0.7385 | No | 0.0519 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| M N1 APARTMENT | SPLIT MN1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.6664 | 0.6664 | 0.6664 | No | 0.0519 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| M N2 APARTMENT | SPLIT MN2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.6652 | 0.6652 | 0.6652 | No | 0.0519 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| M S1 APARTMENT | SPLIT MS1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.6549 | 0.6549 | 0.6549 | No | 0.0519 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| M S2 APARTMENT | SPLIT MS2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.6536 | 0.6536 | 0.6536 | No | 0.0519 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| T SW APARTMENT | SPLIT TSW | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4454 | 0.4454 | 0.4454 | No | 0.0260 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| T NW APARTMENT | SPLIT TNW | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4568 | 0.4568 | 0.4568 | No | 0.0260 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| T SE APARTMENT | SPLIT TSE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.3930 | 0.3930 | 0.3930 | No | 0.0260 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| T NE APARTMENT | SPLIT TNE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4042 | 0.4042 | 0.4042 | No | 0.0260 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| T N1 APARTMENT | SPLIT TN1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.3758 | 0.3758 | 0.3758 | No | 0.0260 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| T N2 APARTMENT | SPLIT TN2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.3742 | 0.3742 | 0.3742 | No | 0.0260 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| T S1 APARTMENT | SPLIT TS1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.3647 | 0.3647 | 0.3647 | No | 0.0260 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| T S2 APARTMENT | SPLIT TS2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.3630 | 0.3630 | 0.3630 | No | 0.0260 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
| SPLIT GSW | 0.3473 | 0.3473 | 0.3473 | 0.3473 | 0.0260 | 1.0000 |
| SPLIT GNW | 0.3521 | 0.3521 | 0.3521 | 0.3521 | 0.0260 | 1.0000 |
| SPLIT OFFICE | 0.3734 | 0.3734 | 0.3734 | 0.3734 | 0.0381 | 1.0000 |
| SPLIT GNE | 0.3256 | 0.3256 | 0.3256 | 0.3256 | 0.0260 | 1.0000 |
| SPLIT GN1 | 0.2949 | 0.2949 | 0.2949 | 0.2949 | 0.0260 | 1.0000 |
| SPLIT GN2 | 0.2944 | 0.2944 | 0.2944 | 0.2944 | 0.0260 | 1.0000 |
| SPLIT GS1 | 0.2904 | 0.2904 | 0.2904 | 0.2904 | 0.0260 | 1.0000 |
| SPLIT GS2 | 0.2925 | 0.2925 | 0.2925 | 0.2925 | 0.0260 | 1.0000 |
| SPLIT MSW | 0.7963 | 0.7963 | 0.7963 | 0.7963 | 0.0519 | 1.0000 |
| SPLIT MNW | 0.8084 | 0.8084 | 0.8084 | 0.8084 | 0.0519 | 1.0000 |
| SPLIT MSE | 0.7264 | 0.7264 | 0.7264 | 0.7264 | 0.0519 | 1.0000 |
| SPLIT MNE | 0.7385 | 0.7385 | 0.7385 | 0.7385 | 0.0519 | 1.0000 |
| SPLIT MN1 | 0.6664 | 0.6664 | 0.6664 | 0.6664 | 0.0519 | 1.0000 |
| SPLIT MN2 | 0.6652 | 0.6652 | 0.6652 | 0.6652 | 0.0519 | 1.0000 |
| SPLIT MS1 | 0.6549 | 0.6549 | 0.6549 | 0.6549 | 0.0519 | 1.0000 |
| SPLIT MS2 | 0.6536 | 0.6536 | 0.6536 | 0.6536 | 0.0519 | 1.0000 |
| SPLIT TSW | 0.4454 | 0.4454 | 0.4454 | 0.4454 | 0.0260 | 1.0000 |
| SPLIT TNW | 0.4568 | 0.4568 | 0.4568 | 0.4568 | 0.0260 | 1.0000 |
| SPLIT TSE | 0.3930 | 0.3930 | 0.3930 | 0.3930 | 0.0260 | 1.0000 |
| SPLIT TNE | 0.4042 | 0.4042 | 0.4042 | 0.4042 | 0.0260 | 1.0000 |
| SPLIT TN1 | 0.3758 | 0.3758 | 0.3758 | 0.3758 | 0.0260 | 1.0000 |
| SPLIT TN2 | 0.3742 | 0.3742 | 0.3742 | 0.3742 | 0.0260 | 1.0000 |
| SPLIT TS1 | 0.3647 | 0.3647 | 0.3647 | 0.3647 | 0.0260 | 1.0000 |
| SPLIT TS2 | 0.3630 | 0.3630 | 0.3630 | 0.3630 | 0.0260 | 1.0000 |
| AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
| G SW APARTMENT | SPLIT GSW | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.3473 | 0.3473 | 0.3473 | No | 0.0260 | 0.8670 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| G NW APARTMENT | SPLIT GNW | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.3521 | 0.3521 | 0.3521 | No | 0.0260 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| OFFICE | SPLIT OFFICE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.3734 | 0.3734 | 0.3734 | No | 0.0381 | 0.7798 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| G NE APARTMENT | SPLIT GNE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.3256 | 0.3256 | 0.3256 | No | 0.0260 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| G N1 APARTMENT | SPLIT GN1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.2949 | 0.2949 | 0.2949 | No | 0.0260 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| G N2 APARTMENT | SPLIT GN2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.2944 | 0.2944 | 0.2944 | No | 0.0260 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| G S1 APARTMENT | SPLIT GS1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.2904 | 0.2904 | 0.2904 | No | 0.0260 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| G S2 APARTMENT | SPLIT GS2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.2925 | 0.2925 | 0.2925 | No | 0.0260 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| M SW APARTMENT | SPLIT MSW | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.7963 | 0.7963 | 0.7963 | No | 0.0519 | 0.7032 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| M NW APARTMENT | SPLIT MNW | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8084 | 0.8084 | 0.8084 | No | 0.0519 | 0.8681 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| M SE APARTMENT | SPLIT MSE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.7264 | 0.7264 | 0.7264 | No | 0.0519 | 0.7032 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| M NE APARTMENT | SPLIT MNE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.7385 | 0.7385 | 0.7385 | No | 0.0519 | 0.8682 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| M N1 APARTMENT | SPLIT MN1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.6664 | 0.6664 | 0.6664 | No | 0.0519 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| M N2 APARTMENT | SPLIT MN2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.6652 | 0.6652 | 0.6652 | No | 0.0519 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| M S1 APARTMENT | SPLIT MS1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.6549 | 0.6549 | 0.6549 | No | 0.0519 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| M S2 APARTMENT | SPLIT MS2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.6536 | 0.6536 | 0.6536 | No | 0.0519 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| T SW APARTMENT | SPLIT TSW | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4454 | 0.4454 | 0.4454 | No | 0.0260 | 0.3613 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| T NW APARTMENT | SPLIT TNW | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4568 | 0.4568 | 0.4568 | No | 0.0260 | 0.4038 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| T SE APARTMENT | SPLIT TSE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.3930 | 0.3930 | 0.3930 | No | 0.0260 | 0.3612 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| T NE APARTMENT | SPLIT TNE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4042 | 0.4042 | 0.4042 | No | 0.0260 | 0.4037 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| T N1 APARTMENT | SPLIT TN1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.3758 | 0.3758 | 0.3758 | No | 0.0260 | 0.6407 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| T N2 APARTMENT | SPLIT TN2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.3742 | 0.3742 | 0.3742 | No | 0.0260 | 0.6407 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| T S1 APARTMENT | SPLIT TS1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.3647 | 0.3647 | 0.3647 | No | 0.0260 | 0.5396 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| T S2 APARTMENT | SPLIT TS2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.3630 | 0.3630 | 0.3630 | No | 0.0260 | 0.5396 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
| SPLIT GSW | 0.3473 | 0.3473 | 0.3473 | 0.3473 | 0.0260 | 1.0000 |
| SPLIT GNW | 0.3521 | 0.3521 | 0.3521 | 0.3521 | 0.0260 | 1.0000 |
| SPLIT OFFICE | 0.3734 | 0.3734 | 0.3734 | 0.3734 | 0.0381 | 1.0000 |
| SPLIT GNE | 0.3256 | 0.3256 | 0.3256 | 0.3256 | 0.0260 | 1.0000 |
| SPLIT GN1 | 0.2949 | 0.2949 | 0.2949 | 0.2949 | 0.0260 | 1.0000 |
| SPLIT GN2 | 0.2944 | 0.2944 | 0.2944 | 0.2944 | 0.0260 | 1.0000 |
| SPLIT GS1 | 0.2904 | 0.2904 | 0.2904 | 0.2904 | 0.0260 | 1.0000 |
| SPLIT GS2 | 0.2925 | 0.2925 | 0.2925 | 0.2925 | 0.0260 | 1.0000 |
| SPLIT MSW | 0.7963 | 0.7963 | 0.7963 | 0.7963 | 0.0519 | 1.0000 |
| SPLIT MNW | 0.8084 | 0.8084 | 0.8084 | 0.8084 | 0.0519 | 1.0000 |
| SPLIT MSE | 0.7264 | 0.7264 | 0.7264 | 0.7264 | 0.0519 | 1.0000 |
| SPLIT MNE | 0.7385 | 0.7385 | 0.7385 | 0.7385 | 0.0519 | 1.0000 |
| SPLIT MN1 | 0.6664 | 0.6664 | 0.6664 | 0.6664 | 0.0519 | 1.0000 |
| SPLIT MN2 | 0.6652 | 0.6652 | 0.6652 | 0.6652 | 0.0519 | 1.0000 |
| SPLIT MS1 | 0.6549 | 0.6549 | 0.6549 | 0.6549 | 0.0519 | 1.0000 |
| SPLIT MS2 | 0.6536 | 0.6536 | 0.6536 | 0.6536 | 0.0519 | 1.0000 |
| SPLIT TSW | 0.4454 | 0.4454 | 0.4454 | 0.4454 | 0.0260 | 1.0000 |
| SPLIT TNW | 0.4568 | 0.4568 | 0.4568 | 0.4568 | 0.0260 | 1.0000 |
| SPLIT TSE | 0.3930 | 0.3930 | 0.3930 | 0.3930 | 0.0260 | 1.0000 |
| SPLIT TNE | 0.4042 | 0.4042 | 0.4042 | 0.4042 | 0.0260 | 1.0000 |
| SPLIT TN1 | 0.3758 | 0.3758 | 0.3758 | 0.3758 | 0.0260 | 1.0000 |
| SPLIT TN2 | 0.3742 | 0.3742 | 0.3742 | 0.3742 | 0.0260 | 1.0000 |
| SPLIT TS1 | 0.3647 | 0.3647 | 0.3647 | 0.3647 | 0.0260 | 1.0000 |
| SPLIT TS2 | 0.3630 | 0.3630 | 0.3630 | 0.3630 | 0.0260 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 09:14:58
Sec1.1A-General Information| Data | |
| Weather File | RUNPERIOD 1 ** Miami Intl Ap FL USA TMY3 WMO#=722020 |
| Total gross floor area [m2] | 3134.61 |
| Principal Heating Source | Natural Gas |
| Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
| G SW APARTMENT | 88.25 | 88.25 | 0.00 | 117.85 |
| G NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
| OFFICE | 88.25 | 88.25 | 0.00 | 33.56 |
| G NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
| G N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
| G N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
| G S1 APARTMENT | 88.25 | 88.25 | 0.00 | 117.85 |
| G S2 APARTMENT | 88.25 | 88.25 | 0.00 | 117.85 |
| M SW APARTMENT | 88.25 | 88.25 | 0.00 | 117.85 |
| M NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
| M SE APARTMENT | 88.25 | 88.25 | 0.00 | 117.85 |
| M NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
| M N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
| M N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
| M S1 APARTMENT | 88.25 | 88.25 | 0.00 | 117.85 |
| M S2 APARTMENT | 88.25 | 88.25 | 0.00 | 117.85 |
| T SW APARTMENT | 88.25 | 88.25 | 0.00 | 117.85 |
| T NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
| T SE APARTMENT | 88.25 | 88.25 | 0.00 | 117.85 |
| T NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
| T N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
| T N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
| T S1 APARTMENT | 88.25 | 88.25 | 0.00 | 117.85 |
| T S2 APARTMENT | 88.25 | 88.25 | 0.00 | 117.85 |
| T CORRIDOR | 77.66 | 0.00 | 77.66 | 168.00 |
| G CORRIDOR | 77.66 | 0.00 | 77.66 | 168.00 |
| M CORRIDOR | 77.66 | 0.00 | 77.66 | 168.00 |
| Totals | 3134.61 | 2823.98 | 310.64 |
| Data | |
| Number of hours heating loads not met | 0.00 |
| Number of hours cooling loads not met | 0.17 |
| Number of hours not met | 0.17 |
| Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
| None |
| Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
| Heating -- General | 0.00 | 0.00 | 1.85 | 15306.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Cooling -- General | 395.10 | 30617.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Lighting -- LightsWired | 94.96 | 5496.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Lighting -- LightsPlugIn | 4.27 | 407.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Lighting -- General | 50.09 | 3183.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment -- MiscPlug | 388.06 | 18541.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment -- ElevatorLift | 65.48 | 4006.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment -- ElevatorLightsFan | 5.11 | 162.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans -- Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans -- General | 148.91 | 8544.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Recovery -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems -- Water Heater | 356.45 | 37016.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Process Subtotal [GJ] | Total Energy Use [GJ] | |
| Electricity | 458.66 | 1508.44 |
| Natural Gas | 0.00 | 1.85 |
| Additional | 0.00 | 0.00 |
| Total | 458.66 | 1510.29 |
| Process Subtotal [$] | Total Energy Cost [$] | |
| Electricity | 0.00 | |
| Natural Gas | 0.00 | |
| Additional | 0.00 | |
| Total | 0.00 |
| Rated Capacity [kW] | Annual Energy Generated [GJ] | |
| Photovoltaic | 0.00 | 0.00 |
| Wind | 0.00 | 0.00 |
| Electricty [MJ/m2] | |
| Interior Lighting (All) | 31.66 |
| Space Heating | 0.00 |
| Space Cooling | 126.05 |
| Fans (All) | 47.51 |
| Service Water Heating | 113.71 |
| Receptacle Equipment | 146.32 |
| Miscellaneous (All) | 481.22 |
| Subtotal | 481.22 |
| Natural Gas [MJ/m2] | |
| Space Heating | 0.59 |
| Service Water Heating | 0.00 |
| Miscellaneous (All) | 0.59 |
| Subtotal | 0.59 |
| Additional [MJ/m2] | |
| Subtotal | 0.00 |
| Miscellaneous | 0.00 |
| Percent [%] | |
| Interior Lighting (All) | 6.57 |
| Space Heating | 0.12 |
| Space Cooling | 26.16 |
| Fans (All) | 9.86 |
| Service Water Heating | 23.60 |
| Receptacle Equipment | 30.37 |
| Miscellaneous | 3.32 |
| Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
| OCC_APT_SCH_STAY_HOME_FAMILY | 5993. | 8760. |
| OCC_APT_SCH_CORRIDOR | 5993. | 8760. |
| OCC_APT_SCH_WORKING_FAMILY | 5845. | 6055. |
| OCC_OFF_SCH | 2210. | 2340. |
| OCC_OFF_W_SB_SCH | 1820. | 1820. |
| LTG_SCH_OFFICE | 2435. | 8760. |
| LTG_SCH_CORRIDOR | 8760. | 8760. |
| LTG_SCH_APARTMENT_HARDWIRED | 527. | 8760. |
| LTG_SCH_APARTMENT_PLUGIN | 527. | 8760. |
| EQP_APT_SCH | 5763. | 8760. |
| EQP_OFF_SCH | 4531. | 8760. |
| INF_APT_SCH | 8760. | 8760. |
| INF_OFF_SCH | 8760. | 8760. |
| INF_COR_SCH | 8760. | 8760. |
| INFIL_DOOR_OPENING_SCH | 1466. | 5840. |
| ALL OFF | 0. | 0. |
| ALL ON | 8760. | 8760. |
| ALWAYS_ON | 8760. | 8760. |
| ALLON_EXCEPT_DD | 8760. | 8760. |
| EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
| FAN_OFF_W_SB_SCH | 8240. | 8240. |
| APT_DHW_SCH | 4592. | 8760. |
| EXTERIOR_LTG_SCH | 4380. | 4380. |
| BLDG_ELEVATORS | 2270. | 8760. |
| ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
| ELEV_LIGHT_FAN_SCH_ADD_DF | 2154. | 8760. |
| SLIDING_DOORS_VENTILATION_AVAILABILITY_SCH | 5840. | 5840. |
| First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
| HTGSETP_APT_SCH | APTHEATINGSETPOINT | January | 21.10 | 365 | 21.10 | 365 |
| HTGSETP_DESIGN_OFF_SCH | OFFHEATINGSETPOINT | January | 21.10 | 365 | 21.10 | 365 |
| CLGSETP_APT_SCH | APTCOOLINGSETPOINT | July | 24.00 | 365 | 24.00 | 365 |
| CLGSETP_DESIGN_OFF_SCH | OFFCOOLINGSETPOINT | July | 23.90 | 365 | 23.90 | 365 |
| S HTGSETP_APT_SCH | S APARTMENT DUAL SP CONTROL | January | 21.10 | 365 | 21.10 | 365 |
| S CLGSETP_APT_SCH | S APARTMENT DUAL SP CONTROL | July | 24.00 | 365 | 24.00 | 365 |
| N HTGSETP_APT_SCH | N APARTMENT DUAL SP CONTROL | January | 21.10 | 365 | 21.10 | 365 |
| N CLGSETP_APT_SCH | N APARTMENT DUAL SP CONTROL | July | 24.00 | 365 | 24.00 | 365 |
| HTGSETP_OFF_SCH_YES_OPTIMUM | OFFICE DUAL SP CONTROL | January | 21.10 | 365 | 15.60 | 365 |
| CLGSETP_OFF_SCH_YES_OPTIMUM | OFFICE DUAL SP CONTROL | July | 24.00 | 365 | 29.40 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 09:14:58
Heat Index Hours| Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
| G SW APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| G NW APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| OFFICE | 3335.17 | 4390.83 | 1034.00 | 0.00 | 0.00 |
| G NE APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| G N1 APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| G N2 APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| G S1 APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| G S2 APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M SW APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M NW APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M SE APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M NE APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M N1 APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M N2 APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M S1 APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M S2 APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T SW APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T NW APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T SE APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T NE APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T N1 APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T N2 APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T S1 APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T S2 APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T CORRIDOR | 2911.17 | 5540.50 | 308.33 | 0.00 | 0.00 |
| G CORRIDOR | 2987.50 | 5354.17 | 418.33 | 0.00 | 0.00 |
| M CORRIDOR | 1618.67 | 7141.33 | 0.00 | 0.00 | 0.00 |
| Min | 1618.67 | 0.00 | 0.00 | 0.00 | 0.00 |
| Max | 8760.00 | 7141.33 | 1034.00 | 0.00 | 0.00 |
| Average | 7864.17 | 830.62 | 65.21 | 0.00 | 0.00 |
| Sum | 212332.50 | 22426.83 | 1760.67 | 0.00 | 0.00 |
| Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
| G SW APARTMENT | 11830.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| G NW APARTMENT | 10585.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| OFFICE | 6985.33 | 14.67 | 0.00 | 0.00 | 0.00 |
| G NE APARTMENT | 10585.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| G N1 APARTMENT | 10585.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| G N2 APARTMENT | 10585.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| G S1 APARTMENT | 11830.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| G S2 APARTMENT | 11830.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M SW APARTMENT | 11830.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M NW APARTMENT | 10585.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M SE APARTMENT | 11830.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M NE APARTMENT | 10585.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M N1 APARTMENT | 10585.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M N2 APARTMENT | 10585.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M S1 APARTMENT | 11830.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M S2 APARTMENT | 11830.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T SW APARTMENT | 11830.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T NW APARTMENT | 10585.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T SE APARTMENT | 11830.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T NE APARTMENT | 10585.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T N1 APARTMENT | 10585.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T N2 APARTMENT | 10585.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T S1 APARTMENT | 11830.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T S2 APARTMENT | 11830.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T CORRIDOR | 8092.00 | 14054.83 | 848.17 | 0.00 | 0.00 |
| G CORRIDOR | 7533.00 | 13896.00 | 1566.00 | 0.00 | 0.00 |
| M CORRIDOR | 4290.00 | 18705.00 | 0.00 | 0.00 | 0.00 |
| Min | 4290.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Max | 11830.00 | 18705.00 | 1566.00 | 0.00 | 0.00 |
| Average | 10520.38 | 1728.54 | 89.41 | 0.00 | 0.00 |
| Sum | 284050.33 | 46670.50 | 2414.17 | 0.00 | 0.00 |
| Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
| G SW APARTMENT | 5600.17 | 3159.83 | 0.00 | 0.00 | 0.00 |
| G NW APARTMENT | 5164.83 | 3595.17 | 0.00 | 0.00 | 0.00 |
| OFFICE | 2787.00 | 5804.00 | 169.00 | 0.00 | 0.00 |
| G NE APARTMENT | 5404.50 | 3355.50 | 0.00 | 0.00 | 0.00 |
| G N1 APARTMENT | 5137.33 | 3622.67 | 0.00 | 0.00 | 0.00 |
| G N2 APARTMENT | 5143.50 | 3616.50 | 0.00 | 0.00 | 0.00 |
| G S1 APARTMENT | 5766.33 | 2993.67 | 0.00 | 0.00 | 0.00 |
| G S2 APARTMENT | 6443.00 | 2317.00 | 0.00 | 0.00 | 0.00 |
| M SW APARTMENT | 5069.33 | 3690.67 | 0.00 | 0.00 | 0.00 |
| M NW APARTMENT | 4632.33 | 4127.67 | 0.00 | 0.00 | 0.00 |
| M SE APARTMENT | 5271.17 | 3488.83 | 0.00 | 0.00 | 0.00 |
| M NE APARTMENT | 4819.00 | 3941.00 | 0.00 | 0.00 | 0.00 |
| M N1 APARTMENT | 4635.17 | 4124.83 | 0.00 | 0.00 | 0.00 |
| M N2 APARTMENT | 4641.50 | 4118.50 | 0.00 | 0.00 | 0.00 |
| M S1 APARTMENT | 5178.50 | 3581.50 | 0.00 | 0.00 | 0.00 |
| M S2 APARTMENT | 5181.83 | 3578.17 | 0.00 | 0.00 | 0.00 |
| T SW APARTMENT | 4792.00 | 3968.00 | 0.00 | 0.00 | 0.00 |
| T NW APARTMENT | 4506.00 | 4254.00 | 0.00 | 0.00 | 0.00 |
| T SE APARTMENT | 4943.00 | 3817.00 | 0.00 | 0.00 | 0.00 |
| T NE APARTMENT | 4665.83 | 4094.17 | 0.00 | 0.00 | 0.00 |
| T N1 APARTMENT | 4610.67 | 4149.33 | 0.00 | 0.00 | 0.00 |
| T N2 APARTMENT | 4595.83 | 4164.17 | 0.00 | 0.00 | 0.00 |
| T S1 APARTMENT | 4967.83 | 3792.17 | 0.00 | 0.00 | 0.00 |
| T S2 APARTMENT | 4970.17 | 3789.83 | 0.00 | 0.00 | 0.00 |
| T CORRIDOR | 326.17 | 6923.33 | 1510.50 | 0.00 | 0.00 |
| G CORRIDOR | 1120.83 | 6762.33 | 876.83 | 0.00 | 0.00 |
| M CORRIDOR | 53.50 | 8019.00 | 687.50 | 0.00 | 0.00 |
| Min | 53.50 | 2317.00 | 0.00 | 0.00 | 0.00 |
| Max | 6443.00 | 8019.00 | 1510.50 | 0.00 | 0.00 |
| Average | 4460.27 | 4179.59 | 120.14 | 0.00 | 0.00 |
| Sum | 120427.33 | 112848.83 | 3243.83 | 0.00 | 0.00 |
| Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
| G SW APARTMENT | 6879.00 | 4951.00 | 0.00 | 0.00 | 0.00 |
| G NW APARTMENT | 5709.50 | 4875.50 | 0.00 | 0.00 | 0.00 |
| OFFICE | 5886.00 | 1114.00 | 0.00 | 0.00 | 0.00 |
| G NE APARTMENT | 5689.83 | 4895.17 | 0.00 | 0.00 | 0.00 |
| G N1 APARTMENT | 5668.00 | 4917.00 | 0.00 | 0.00 | 0.00 |
| G N2 APARTMENT | 5665.83 | 4919.17 | 0.00 | 0.00 | 0.00 |
| G S1 APARTMENT | 7141.50 | 4688.50 | 0.00 | 0.00 | 0.00 |
| G S2 APARTMENT | 8186.67 | 3643.33 | 0.00 | 0.00 | 0.00 |
| M SW APARTMENT | 6150.17 | 5679.83 | 0.00 | 0.00 | 0.00 |
| M NW APARTMENT | 5101.33 | 5483.67 | 0.00 | 0.00 | 0.00 |
| M SE APARTMENT | 6191.17 | 5638.83 | 0.00 | 0.00 | 0.00 |
| M NE APARTMENT | 4958.00 | 5627.00 | 0.00 | 0.00 | 0.00 |
| M N1 APARTMENT | 5115.17 | 5469.83 | 0.00 | 0.00 | 0.00 |
| M N2 APARTMENT | 5112.50 | 5472.50 | 0.00 | 0.00 | 0.00 |
| M S1 APARTMENT | 6325.83 | 5504.17 | 0.00 | 0.00 | 0.00 |
| M S2 APARTMENT | 6322.33 | 5507.67 | 0.00 | 0.00 | 0.00 |
| T SW APARTMENT | 5475.17 | 6354.83 | 0.00 | 0.00 | 0.00 |
| T NW APARTMENT | 4647.50 | 5937.50 | 0.00 | 0.00 | 0.00 |
| T SE APARTMENT | 5452.00 | 6378.00 | 0.00 | 0.00 | 0.00 |
| T NE APARTMENT | 4457.83 | 6127.17 | 0.00 | 0.00 | 0.00 |
| T N1 APARTMENT | 4730.17 | 5854.83 | 0.00 | 0.00 | 0.00 |
| T N2 APARTMENT | 4696.50 | 5888.50 | 0.00 | 0.00 | 0.00 |
| T S1 APARTMENT | 5718.33 | 6111.67 | 0.00 | 0.00 | 0.00 |
| T S2 APARTMENT | 5712.33 | 6117.67 | 0.00 | 0.00 | 0.00 |
| T CORRIDOR | 812.33 | 18252.50 | 3930.17 | 0.00 | 0.00 |
| G CORRIDOR | 2529.00 | 16986.50 | 3479.50 | 0.00 | 0.00 |
| M CORRIDOR | 116.00 | 21095.33 | 1783.67 | 0.00 | 0.00 |
| Min | 116.00 | 1114.00 | 0.00 | 0.00 | 0.00 |
| Max | 8186.67 | 21095.33 | 3930.17 | 0.00 | 0.00 |
| Average | 5201.85 | 6795.99 | 340.49 | 0.00 | 0.00 |
| Sum | 140450.00 | 183491.67 | 9193.33 | 0.00 | 0.00 |
| SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
| None |
| SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
| None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 09:14:58
CO2 Level Hours| Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
| None |
| Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
| None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 09:14:58
Illuminance Level Hours| A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
| None |
| A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
| None |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
| January | 19.420 |
| February | 20.868 |
| March | 21.567 |
| April | 24.112 |
| May | 26.413 |
| June | 27.683 |
| July | 28.127 |
| August | 27.974 |
| September | 27.493 |
| October | 26.347 |
| November | 23.587 |
| December | 20.295 |
| Annual Sum or Average | 24.507 |
| Minimum of Months | 19.420 |
| Maximum of Months | 28.127 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Environment
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
| January | 19.420 |
| February | 20.868 |
| March | 21.567 |
| April | 24.112 |
| May | 26.413 |
| June | 27.683 |
| July | 28.127 |
| August | 27.974 |
| September | 27.493 |
| October | 26.347 |
| November | 23.587 |
| December | 20.295 |
| Annual Sum or Average | 24.507 |
| Minimum of Months | 19.420 |
| Maximum of Months | 28.127 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2012
For: Environment
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
| January | 19.420 |
| February | 20.868 |
| March | 21.567 |
| April | 24.112 |
| May | 26.413 |
| June | 27.683 |
| July | 28.127 |
| August | 27.974 |
| September | 27.493 |
| October | 26.347 |
| November | 23.587 |
| December | 20.295 |
| Annual Sum or Average | 24.507 |
| Minimum of Months | 19.420 |
| Maximum of Months | 28.127 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
| January | 19.420 |
| February | 20.868 |
| March | 21.567 |
| April | 24.112 |
| May | 26.413 |
| June | 27.683 |
| July | 28.127 |
| August | 27.974 |
| September | 27.493 |
| October | 26.347 |
| November | 23.587 |
| December | 20.295 |
| Annual Sum or Average | 24.507 |
| Minimum of Months | 19.420 |
| Maximum of Months | 28.127 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME APARTMENTMIDRISE
For: Environment
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
| January | 19.420 |
| February | 20.868 |
| March | 21.567 |
| April | 24.112 |
| May | 26.413 |
| June | 27.683 |
| July | 28.127 |
| August | 27.974 |
| September | 27.493 |
| October | 26.347 |
| November | 23.587 |
| December | 20.295 |
| Annual Sum or Average | 24.507 |
| Minimum of Months | 19.420 |
| Maximum of Months | 28.127 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
| January | 19.420 |
| February | 20.868 |
| March | 21.567 |
| April | 24.112 |
| May | 26.413 |
| June | 27.683 |
| July | 28.127 |
| August | 27.974 |
| September | 27.493 |
| October | 26.347 |
| November | 23.587 |
| December | 20.295 |
| Annual Sum or Average | 24.507 |
| Minimum of Months | 19.420 |
| Maximum of Months | 28.127 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
| January | 19.420 |
| February | 20.868 |
| March | 21.567 |
| April | 24.112 |
| May | 26.413 |
| June | 27.683 |
| July | 28.127 |
| August | 27.974 |
| September | 27.493 |
| October | 26.347 |
| November | 23.587 |
| December | 20.295 |
| Annual Sum or Average | 24.507 |
| Minimum of Months | 19.420 |
| Maximum of Months | 28.127 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 1A
For: Environment
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
| January | 19.420 |
| February | 20.868 |
| March | 21.567 |
| April | 24.112 |
| May | 26.413 |
| June | 27.683 |
| July | 28.127 |
| August | 27.974 |
| September | 27.493 |
| October | 26.347 |
| November | 23.587 |
| December | 20.295 |
| Annual Sum or Average | 24.507 |
| Minimum of Months | 19.420 |
| Maximum of Months | 28.127 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_FL_MIAMI
For: Environment
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
| January | 19.420 |
| February | 20.868 |
| March | 21.567 |
| April | 24.112 |
| May | 26.413 |
| June | 27.683 |
| July | 28.127 |
| August | 27.974 |
| September | 27.493 |
| October | 26.347 |
| November | 23.587 |
| December | 20.295 |
| Annual Sum or Average | 24.507 |
| Minimum of Months | 19.420 |
| Maximum of Months | 28.127 |
Report: ZoneCoolingSummaryMonthly
For: G SW APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.214392E+10 | 2045.67 | 02-JAN-14:40 | 28.90 | 23.86 | 0.128701E+09 | 70.37 | 10-JAN-03:39 | 13.30 | 9.05 |
| February | 0.202492E+10 | 2045.44 | 20-FEB-17:10 | 26.42 | 17.81 | 0.113663E+09 | 70.37 | 06-FEB-05:49 | 26.42 | 17.81 |
| March | 0.214116E+10 | 1835.12 | 13-MAR-16:25 | 29.15 | 22.20 | 0.122801E+09 | 70.34 | 11-MAR-01:49 | 29.15 | 22.20 |
| April | 0.247154E+10 | 2035.35 | 15-APR-17:00 | 31.70 | 22.81 | 0.123951E+09 | 70.36 | 19-APR-04:10 | 15.00 | 11.82 |
| May | 0.292154E+10 | 2025.15 | 29-MAY-16:30 | 32.50 | 24.46 | 0.125734E+09 | 70.30 | 08-MAY-04:30 | 32.50 | 24.46 |
| June | 0.300470E+10 | 1922.75 | 14-JUN-17:13 | 29.80 | 23.59 | 0.120421E+09 | 70.30 | 14-JUN-05:00 | 29.80 | 23.59 |
| July | 0.341183E+10 | 2213.15 | 29-JUL-16:30 | 35.00 | 24.27 | 0.129275E+09 | 70.28 | 07-JUL-02:00 | 35.00 | 24.27 |
| August | 0.351168E+10 | 2181.81 | 20-AUG-16:30 | 30.60 | 24.86 | 0.123963E+09 | 70.29 | 14-AUG-02:00 | 30.60 | 24.86 |
| September | 0.359636E+10 | 2351.00 | 30-SEP-16:10 | 31.02 | 24.52 | 0.123963E+09 | 70.30 | 04-SEP-20:49 | 31.02 | 24.52 |
| October | 0.363694E+10 | 2335.65 | 25-OCT-16:03 | 28.22 | 22.40 | 0.127505E+09 | 70.30 | 19-OCT-03:49 | 28.22 | 22.40 |
| November | 0.293973E+10 | 2215.08 | 07-NOV-16:10 | 28.22 | 22.20 | 0.123766E+09 | 70.33 | 12-NOV-23:49 | 14.40 | 9.82 |
| December | 0.237664E+10 | 2199.21 | 10-DEC-15:10 | 28.80 | 22.65 | 0.128520E+09 | 70.37 | 20-DEC-04:30 | 12.75 | 11.21 |
| Annual Sum or Average | 0.341810E+11 | 0.149226E+10 | ||||||||
| Minimum of Months | 0.202492E+10 | 1835.12 | 26.42 | 17.81 | 0.113663E+09 | 70.28 | 12.75 | 9.05 | ||
| Maximum of Months | 0.363694E+10 | 2351.00 | 35.00 | 24.86 | 0.129275E+09 | 70.37 | 35.00 | 24.86 |
Report: ZoneCoolingSummaryMonthly
For: G NW APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.132026E+10 | 1213.83 | 03-JAN-16:10 | 26.42 | 20.44 | 0.126312E+09 | 70.38 | 09-JAN-23:10 | 14.40 | 10.80 |
| February | 0.137943E+10 | 1452.76 | 11-FEB-16:30 | 27.50 | 24.08 | 0.113421E+09 | 70.36 | 26-FEB-03:39 | 15.77 | 14.03 |
| March | 0.167034E+10 | 1532.35 | 27-MAR-16:25 | 26.95 | 22.12 | 0.126323E+09 | 70.37 | 21-MAR-22:40 | 26.95 | 22.12 |
| April | 0.221830E+10 | 1896.72 | 15-APR-17:00 | 31.70 | 22.81 | 0.124602E+09 | 70.31 | 19-APR-02:30 | 15.00 | 11.82 |
| May | 0.294105E+10 | 2047.08 | 29-MAY-17:10 | 31.60 | 24.40 | 0.128775E+09 | 70.30 | 08-MAY-04:30 | 31.60 | 24.40 |
| June | 0.311036E+10 | 2053.24 | 14-JUN-17:30 | 29.70 | 23.56 | 0.124621E+09 | 70.30 | 14-JUN-05:00 | 29.70 | 23.56 |
| July | 0.347552E+10 | 2173.83 | 27-JUL-17:12 | 33.67 | 25.23 | 0.128775E+09 | 70.28 | 07-JUL-02:00 | 33.67 | 25.23 |
| August | 0.343418E+10 | 2101.13 | 17-AUG-17:00 | 31.10 | 24.95 | 0.128775E+09 | 70.29 | 14-AUG-02:00 | 31.10 | 24.95 |
| September | 0.327856E+10 | 2049.49 | 17-SEP-16:30 | 31.10 | 24.77 | 0.124620E+09 | 70.30 | 04-SEP-20:49 | 31.10 | 24.77 |
| October | 0.302828E+10 | 1889.07 | 03-OCT-16:30 | 30.85 | 25.08 | 0.128775E+09 | 70.30 | 19-OCT-03:49 | 23.40 | 18.62 |
| November | 0.223579E+10 | 1529.11 | 03-NOV-16:04 | 28.22 | 24.50 | 0.124189E+09 | 70.32 | 12-NOV-02:09 | 15.50 | 10.90 |
| December | 0.158748E+10 | 1469.96 | 10-DEC-15:30 | 28.60 | 22.59 | 0.126610E+09 | 70.34 | 12-DEC-03:20 | 14.03 | 12.28 |
| Annual Sum or Average | 0.296796E+11 | 0.150580E+10 | ||||||||
| Minimum of Months | 0.132026E+10 | 1213.83 | 26.42 | 20.44 | 0.113421E+09 | 70.28 | 14.03 | 10.80 | ||
| Maximum of Months | 0.347552E+10 | 2173.83 | 33.67 | 25.23 | 0.128775E+09 | 70.38 | 33.67 | 25.23 |
Report: ZoneCoolingSummaryMonthly
For: OFFICE
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.145543E+10 | 6568.73 | 09-JAN-09:02 | 15.28 | 12.28 | 70068803.06 | 217.47 | 03-JAN-08:09 | 15.28 | 12.28 |
| February | 0.137720E+10 | 6581.93 | 22-FEB-09:02 | 17.85 | 12.79 | 66695765.00 | 207.59 | 17-FEB-08:09 | 17.85 | 12.79 |
| March | 0.153107E+10 | 6201.92 | 01-MAR-09:02 | 17.57 | 14.74 | 80444823.88 | 217.47 | 06-MAR-08:09 | 23.40 | 21.79 |
| April | 0.156446E+10 | 6631.31 | 18-APR-07:02 | 17.88 | 12.74 | 70563852.62 | 219.65 | 10-APR-07:10 | 17.88 | 12.74 |
| May | 0.193434E+10 | 5627.39 | 08-MAY-07:02 | 25.00 | 19.79 | 77749702.70 | 217.54 | 19-MAY-07:10 | 26.97 | 22.83 |
| June | 0.208495E+10 | 4435.67 | 12-JUN-08:62 | 28.48 | 24.42 | 77773401.38 | 217.47 | 19-JUN-07:10 | 25.28 | 22.81 |
| July | 0.211585E+10 | 4576.33 | 06-JUL-08:62 | 28.30 | 22.34 | 70711589.35 | 217.47 | 24-JUL-07:10 | 26.15 | 24.62 |
| August | 0.242440E+10 | 4515.83 | 28-AUG-08:62 | 23.72 | 21.70 | 81319814.27 | 217.49 | 21-AUG-07:10 | 23.72 | 21.70 |
| September | 0.226111E+10 | 4616.48 | 11-SEP-08:62 | 27.48 | 24.77 | 70712837.66 | 217.72 | 15-SEP-07:10 | 24.50 | 22.58 |
| October | 0.234067E+10 | 5920.75 | 18-OCT-07:02 | 25.18 | 18.80 | 74246851.24 | 218.23 | 19-OCT-07:10 | 23.77 | 19.55 |
| November | 0.192670E+10 | 6652.36 | 27-NOV-09:02 | 15.65 | 11.81 | 70624525.29 | 218.39 | 03-NOV-07:10 | 15.65 | 11.81 |
| December | 0.148774E+10 | 6698.23 | 12-DEC-09:02 | 13.07 | 9.28 | 70103602.33 | 217.47 | 01-DEC-08:09 | 13.07 | 9.28 |
| Annual Sum or Average | 0.225039E+11 | 0.881016E+09 | ||||||||
| Minimum of Months | 0.137720E+10 | 4435.67 | 13.07 | 9.28 | 66695765.00 | 207.59 | 13.07 | 9.28 | ||
| Maximum of Months | 0.242440E+10 | 6698.23 | 28.48 | 24.77 | 81319814.27 | 219.65 | 26.97 | 24.62 |
Report: ZoneCoolingSummaryMonthly
For: G NE APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.135409E+10 | 1139.81 | 01-JAN-13:00 | 27.20 | 21.55 | 0.126368E+09 | 70.36 | 21-JAN-22:10 | 17.12 | 13.26 |
| February | 0.138017E+10 | 1183.68 | 11-FEB-14:00 | 29.40 | 24.15 | 0.113443E+09 | 70.38 | 24-FEB-23:00 | 15.60 | 10.89 |
| March | 0.164755E+10 | 1299.28 | 13-MAR-17:00 | 28.90 | 21.99 | 0.126448E+09 | 70.37 | 21-MAR-22:49 | 17.88 | 14.24 |
| April | 0.220736E+10 | 1596.03 | 15-APR-17:00 | 31.70 | 22.81 | 0.124601E+09 | 70.37 | 19-APR-05:40 | 15.40 | 12.04 |
| May | 0.294183E+10 | 1795.11 | 22-MAY-16:03 | 32.62 | 23.73 | 0.128775E+09 | 70.30 | 08-MAY-04:30 | 32.62 | 23.73 |
| June | 0.318551E+10 | 1794.17 | 03-JUN-16:30 | 31.10 | 24.60 | 0.124621E+09 | 70.30 | 14-JUN-05:00 | 23.30 | 22.07 |
| July | 0.352008E+10 | 1974.67 | 29-JUL-16:30 | 35.00 | 24.27 | 0.128775E+09 | 70.28 | 07-JUL-02:00 | 35.00 | 24.27 |
| August | 0.343228E+10 | 1856.31 | 20-AUG-11:40 | 32.03 | 26.13 | 0.128775E+09 | 70.29 | 14-AUG-02:00 | 32.03 | 26.13 |
| September | 0.332890E+10 | 1858.39 | 18-SEP-16:03 | 31.60 | 25.51 | 0.124620E+09 | 70.30 | 04-SEP-20:49 | 31.60 | 25.51 |
| October | 0.304777E+10 | 1735.04 | 03-OCT-16:03 | 31.02 | 24.99 | 0.128775E+09 | 70.30 | 19-OCT-03:49 | 23.40 | 18.62 |
| November | 0.224390E+10 | 1439.35 | 03-NOV-16:04 | 28.22 | 24.50 | 0.124213E+09 | 70.35 | 26-NOV-23:30 | 12.50 | 9.12 |
| December | 0.153285E+10 | 1310.29 | 10-DEC-14:00 | 28.90 | 23.02 | 0.126525E+09 | 70.37 | 20-DEC-00:10 | 15.50 | 13.30 |
| Annual Sum or Average | 0.298223E+11 | 0.150594E+10 | ||||||||
| Minimum of Months | 0.135409E+10 | 1139.81 | 27.20 | 21.55 | 0.113443E+09 | 70.28 | 12.50 | 9.12 | ||
| Maximum of Months | 0.352008E+10 | 1974.67 | 35.00 | 26.13 | 0.128775E+09 | 70.38 | 35.00 | 26.13 |
Report: ZoneCoolingSummaryMonthly
For: G N1 APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.130509E+10 | 956.74 | 01-JAN-17:10 | 24.82 | 21.57 | 0.127671E+09 | 70.37 | 22-JAN-01:10 | 14.82 | 11.47 |
| February | 0.129176E+10 | 1026.01 | 11-FEB-17:10 | 27.02 | 23.97 | 0.114735E+09 | 70.36 | 05-FEB-22:49 | 27.02 | 23.97 |
| March | 0.150067E+10 | 1078.46 | 13-MAR-17:10 | 28.80 | 22.02 | 0.127483E+09 | 70.38 | 21-MAR-23:49 | 16.88 | 13.89 |
| April | 0.190069E+10 | 1270.05 | 15-APR-17:07 | 31.42 | 22.68 | 0.124612E+09 | 70.30 | 10-APR-21:49 | 31.42 | 22.68 |
| May | 0.247067E+10 | 1450.49 | 29-MAY-17:07 | 31.60 | 24.40 | 0.128775E+09 | 70.30 | 08-MAY-04:30 | 31.60 | 24.40 |
| June | 0.263740E+10 | 1445.83 | 29-JUN-17:17 | 30.40 | 24.80 | 0.124621E+09 | 70.30 | 14-JUN-05:00 | 30.40 | 24.80 |
| July | 0.287655E+10 | 1557.61 | 29-JUL-17:13 | 34.03 | 24.14 | 0.128774E+09 | 70.28 | 07-JUL-02:00 | 34.03 | 24.14 |
| August | 0.282644E+10 | 1461.88 | 02-AUG-17:30 | 30.55 | 24.65 | 0.128775E+09 | 70.29 | 14-AUG-02:00 | 22.80 | 22.32 |
| September | 0.271943E+10 | 1459.46 | 18-SEP-16:17 | 31.50 | 25.54 | 0.124620E+09 | 70.30 | 04-SEP-20:49 | 31.50 | 25.54 |
| October | 0.254725E+10 | 1374.11 | 03-OCT-16:03 | 31.02 | 24.99 | 0.128775E+09 | 70.30 | 19-OCT-03:49 | 23.40 | 18.62 |
| November | 0.198580E+10 | 1196.98 | 04-NOV-16:10 | 27.70 | 25.21 | 0.124481E+09 | 70.37 | 27-NOV-00:30 | 11.40 | 9.10 |
| December | 0.148854E+10 | 1083.28 | 10-DEC-17:10 | 27.02 | 22.46 | 0.127736E+09 | 70.38 | 13-DEC-00:00 | 11.70 | 9.89 |
| Annual Sum or Average | 0.255503E+11 | 0.151106E+10 | ||||||||
| Minimum of Months | 0.129176E+10 | 956.74 | 24.82 | 21.57 | 0.114735E+09 | 70.28 | 11.40 | 9.10 | ||
| Maximum of Months | 0.287655E+10 | 1557.61 | 34.03 | 25.54 | 0.128775E+09 | 70.38 | 34.03 | 25.54 |
Report: ZoneCoolingSummaryMonthly
For: G N2 APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.130817E+10 | 958.58 | 01-JAN-17:10 | 24.82 | 21.57 | 0.127675E+09 | 70.37 | 20-JAN-22:10 | 16.02 | 12.26 |
| February | 0.129284E+10 | 1020.72 | 11-FEB-17:10 | 27.02 | 23.97 | 0.114739E+09 | 70.38 | 05-FEB-22:49 | 27.02 | 23.97 |
| March | 0.150165E+10 | 1073.66 | 13-MAR-17:10 | 28.80 | 22.02 | 0.127495E+09 | 70.37 | 18-MAR-04:00 | 19.40 | 15.66 |
| April | 0.190048E+10 | 1265.61 | 15-APR-17:07 | 31.42 | 22.68 | 0.124612E+09 | 70.30 | 10-APR-21:49 | 31.42 | 22.68 |
| May | 0.247085E+10 | 1445.88 | 29-MAY-17:07 | 31.60 | 24.40 | 0.128775E+09 | 70.30 | 08-MAY-04:30 | 31.60 | 24.40 |
| June | 0.264079E+10 | 1441.68 | 29-JUN-17:17 | 30.40 | 24.80 | 0.124621E+09 | 70.30 | 14-JUN-05:00 | 30.40 | 24.80 |
| July | 0.287839E+10 | 1555.36 | 29-JUL-17:13 | 34.03 | 24.14 | 0.128774E+09 | 70.28 | 07-JUL-02:00 | 34.03 | 24.14 |
| August | 0.282651E+10 | 1458.79 | 02-AUG-17:30 | 30.55 | 24.65 | 0.128775E+09 | 70.29 | 14-AUG-02:00 | 22.80 | 22.32 |
| September | 0.272163E+10 | 1456.78 | 18-SEP-16:17 | 31.50 | 25.54 | 0.124620E+09 | 70.30 | 04-SEP-20:49 | 31.50 | 25.54 |
| October | 0.254823E+10 | 1372.49 | 03-OCT-16:03 | 31.02 | 24.99 | 0.128775E+09 | 70.30 | 19-OCT-03:49 | 23.40 | 18.62 |
| November | 0.198666E+10 | 1197.08 | 04-NOV-16:10 | 27.70 | 25.21 | 0.124481E+09 | 70.37 | 27-NOV-00:20 | 11.50 | 9.02 |
| December | 0.148645E+10 | 1080.06 | 10-DEC-17:10 | 27.02 | 22.46 | 0.127730E+09 | 70.37 | 20-DEC-02:00 | 13.30 | 11.39 |
| Annual Sum or Average | 0.255627E+11 | 0.151107E+10 | ||||||||
| Minimum of Months | 0.129284E+10 | 958.58 | 24.82 | 21.57 | 0.114739E+09 | 70.28 | 11.50 | 9.02 | ||
| Maximum of Months | 0.287839E+10 | 1555.36 | 34.03 | 25.54 | 0.128775E+09 | 70.38 | 34.03 | 25.54 |
Report: ZoneCoolingSummaryMonthly
For: G S1 APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.219885E+10 | 1795.14 | 02-JAN-14:30 | 28.90 | 24.11 | 0.129192E+09 | 70.36 | 31-JAN-02:00 | 13.30 | 10.59 |
| February | 0.198608E+10 | 1585.54 | 20-FEB-16:10 | 26.70 | 17.88 | 0.114518E+09 | 70.34 | 03-FEB-22:10 | 26.70 | 17.88 |
| March | 0.201022E+10 | 1425.72 | 01-MAR-15:10 | 24.50 | 16.04 | 0.123549E+09 | 70.36 | 11-MAR-05:10 | 13.30 | 10.89 |
| April | 0.216930E+10 | 1406.64 | 15-APR-17:00 | 31.70 | 22.81 | 0.123956E+09 | 70.31 | 02-APR-18:30 | 31.70 | 22.81 |
| May | 0.246261E+10 | 1420.88 | 29-MAY-16:40 | 32.23 | 24.43 | 0.125734E+09 | 70.30 | 08-MAY-04:30 | 32.23 | 24.43 |
| June | 0.254208E+10 | 1393.99 | 03-JUN-16:30 | 31.10 | 24.60 | 0.120421E+09 | 70.30 | 14-JUN-05:00 | 23.30 | 22.07 |
| July | 0.282497E+10 | 1587.58 | 29-JUL-17:05 | 34.22 | 24.14 | 0.129275E+09 | 70.28 | 07-JUL-02:00 | 34.22 | 24.14 |
| August | 0.291771E+10 | 1580.70 | 20-AUG-16:10 | 30.60 | 24.86 | 0.123963E+09 | 70.29 | 14-AUG-02:00 | 30.60 | 24.86 |
| September | 0.305517E+10 | 1756.44 | 24-SEP-13:30 | 31.10 | 24.05 | 0.123963E+09 | 70.30 | 04-SEP-20:49 | 31.10 | 24.05 |
| October | 0.318085E+10 | 1799.20 | 25-OCT-14:10 | 30.40 | 22.58 | 0.127505E+09 | 70.30 | 19-OCT-03:49 | 30.40 | 22.58 |
| November | 0.272215E+10 | 1821.30 | 22-NOV-12:40 | 27.60 | 22.86 | 0.123945E+09 | 70.34 | 13-NOV-02:00 | 27.60 | 22.86 |
| December | 0.233248E+10 | 1800.26 | 10-DEC-14:40 | 28.90 | 22.80 | 0.129105E+09 | 70.37 | 27-DEC-01:10 | 10.50 | 9.62 |
| Annual Sum or Average | 0.304025E+11 | 0.149513E+10 | ||||||||
| Minimum of Months | 0.198608E+10 | 1393.99 | 24.50 | 16.04 | 0.114518E+09 | 70.28 | 10.50 | 9.62 | ||
| Maximum of Months | 0.318085E+10 | 1821.30 | 34.22 | 24.86 | 0.129275E+09 | 70.37 | 34.22 | 24.86 |
Report: ZoneCoolingSummaryMonthly
For: G S2 APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.238668E+10 | 1969.55 | 02-JAN-14:30 | 28.90 | 24.11 | 0.129229E+09 | 70.34 | 31-JAN-05:10 | 12.70 | 10.49 |
| February | 0.213429E+10 | 1709.08 | 20-FEB-16:10 | 26.70 | 17.88 | 0.114585E+09 | 70.37 | 03-FEB-02:00 | 26.70 | 17.88 |
| March | 0.217516E+10 | 1482.30 | 01-MAR-15:10 | 24.50 | 16.04 | 0.123649E+09 | 70.37 | 17-MAR-02:09 | 14.40 | 9.82 |
| April | 0.237999E+10 | 1519.93 | 15-APR-17:00 | 31.70 | 22.81 | 0.123959E+09 | 70.31 | 02-APR-18:30 | 31.70 | 22.81 |
| May | 0.271444E+10 | 1551.15 | 29-MAY-16:40 | 32.23 | 24.43 | 0.125734E+09 | 70.30 | 08-MAY-04:30 | 32.23 | 24.43 |
| June | 0.281731E+10 | 1525.36 | 03-JUN-16:30 | 31.10 | 24.60 | 0.120421E+09 | 70.30 | 14-JUN-05:00 | 23.30 | 22.07 |
| July | 0.313272E+10 | 1722.09 | 29-JUL-17:05 | 34.22 | 24.14 | 0.129275E+09 | 70.28 | 07-JUL-02:00 | 34.22 | 24.14 |
| August | 0.321211E+10 | 1736.47 | 20-AUG-16:10 | 30.60 | 24.86 | 0.123963E+09 | 70.29 | 14-AUG-02:00 | 30.60 | 24.86 |
| September | 0.335725E+10 | 1922.10 | 24-SEP-13:30 | 31.10 | 24.05 | 0.123963E+09 | 70.30 | 04-SEP-20:49 | 31.10 | 24.05 |
| October | 0.348509E+10 | 1945.65 | 29-OCT-14:10 | 30.00 | 25.78 | 0.127505E+09 | 70.30 | 19-OCT-03:49 | 30.00 | 25.78 |
| November | 0.296015E+10 | 1908.93 | 22-NOV-12:40 | 27.60 | 22.86 | 0.123960E+09 | 70.32 | 13-NOV-03:49 | 27.60 | 22.86 |
| December | 0.251777E+10 | 1946.48 | 10-DEC-14:40 | 28.90 | 22.80 | 0.129164E+09 | 70.37 | 21-DEC-05:40 | 10.93 | 10.07 |
| Annual Sum or Average | 0.332730E+11 | 0.149541E+10 | ||||||||
| Minimum of Months | 0.213429E+10 | 1482.30 | 24.50 | 16.04 | 0.114585E+09 | 70.28 | 10.93 | 9.82 | ||
| Maximum of Months | 0.348509E+10 | 1969.55 | 34.22 | 25.78 | 0.129275E+09 | 70.37 | 34.22 | 25.78 |
Report: ZoneCoolingSummaryMonthly
For: M SW APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.216080E+10 | 2336.01 | 02-JAN-14:40 | 28.90 | 23.86 | 0.127971E+09 | 70.32 | 27-JAN-03:49 | 14.40 | 8.17 |
| February | 0.216719E+10 | 2428.98 | 20-FEB-16:20 | 26.70 | 17.88 | 0.113038E+09 | 70.32 | 06-FEB-02:20 | 26.70 | 17.88 |
| March | 0.247470E+10 | 2225.87 | 13-MAR-16:30 | 29.15 | 22.20 | 0.122662E+09 | 70.31 | 20-MAR-22:30 | 14.70 | 10.25 |
| April | 0.286871E+10 | 2439.09 | 15-APR-17:00 | 31.70 | 22.81 | 0.123949E+09 | 70.30 | 02-APR-18:30 | 31.70 | 22.81 |
| May | 0.328373E+10 | 2449.52 | 29-MAY-16:30 | 32.50 | 24.46 | 0.125734E+09 | 70.30 | 08-MAY-04:30 | 32.50 | 24.46 |
| June | 0.329753E+10 | 2266.11 | 14-JUN-17:13 | 29.80 | 23.59 | 0.120421E+09 | 70.29 | 14-JUN-05:00 | 29.80 | 23.59 |
| July | 0.354632E+10 | 2449.01 | 29-JUL-16:30 | 35.00 | 24.27 | 0.129275E+09 | 70.28 | 07-JUL-02:00 | 35.00 | 24.27 |
| August | 0.352503E+10 | 2370.37 | 16-AUG-16:03 | 31.60 | 25.03 | 0.123963E+09 | 70.29 | 14-AUG-02:00 | 31.60 | 25.03 |
| September | 0.353871E+10 | 2563.68 | 30-SEP-16:07 | 31.02 | 24.52 | 0.123963E+09 | 70.30 | 04-SEP-20:49 | 31.02 | 24.52 |
| October | 0.355002E+10 | 2550.12 | 25-OCT-16:03 | 28.22 | 22.40 | 0.127505E+09 | 70.30 | 19-OCT-03:49 | 28.22 | 22.40 |
| November | 0.285556E+10 | 2444.38 | 07-NOV-16:10 | 28.22 | 22.20 | 0.123306E+09 | 70.31 | 12-NOV-01:39 | 15.77 | 11.26 |
| December | 0.231214E+10 | 2454.19 | 10-DEC-15:00 | 28.90 | 22.68 | 0.127651E+09 | 70.31 | 28-DEC-00:40 | 15.77 | 14.24 |
| Annual Sum or Average | 0.355804E+11 | 0.148944E+10 | ||||||||
| Minimum of Months | 0.216080E+10 | 2225.87 | 26.70 | 17.88 | 0.113038E+09 | 70.28 | 14.40 | 8.17 | ||
| Maximum of Months | 0.355002E+10 | 2563.68 | 35.00 | 25.03 | 0.129275E+09 | 70.32 | 35.00 | 25.03 |
Report: ZoneCoolingSummaryMonthly
For: M NW APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.129581E+10 | 1305.48 | 03-JAN-16:10 | 26.42 | 20.44 | 0.125200E+09 | 70.31 | 21-JAN-21:19 | 17.60 | 13.68 |
| February | 0.148203E+10 | 1709.65 | 11-FEB-16:30 | 27.50 | 24.08 | 0.112508E+09 | 70.31 | 23-FEB-22:00 | 16.10 | 9.10 |
| March | 0.197379E+10 | 1900.65 | 13-MAR-16:40 | 29.07 | 22.13 | 0.126279E+09 | 70.30 | 01-MAR-02:20 | 29.07 | 22.13 |
| April | 0.259664E+10 | 2270.69 | 15-APR-17:00 | 31.70 | 22.81 | 0.124600E+09 | 70.32 | 19-APR-05:40 | 15.40 | 12.04 |
| May | 0.329687E+10 | 2461.92 | 29-MAY-16:40 | 32.23 | 24.43 | 0.128775E+09 | 70.30 | 08-MAY-04:30 | 32.23 | 24.43 |
| June | 0.339726E+10 | 2412.81 | 14-JUN-17:30 | 29.70 | 23.56 | 0.124621E+09 | 70.29 | 14-JUN-05:00 | 29.70 | 23.56 |
| July | 0.359945E+10 | 2403.12 | 27-JUL-16:30 | 34.70 | 25.03 | 0.128775E+09 | 70.28 | 07-JUL-02:00 | 34.70 | 25.03 |
| August | 0.343182E+10 | 2297.83 | 16-AUG-16:30 | 31.40 | 24.86 | 0.128775E+09 | 70.29 | 14-AUG-02:00 | 31.40 | 24.86 |
| September | 0.319508E+10 | 2221.88 | 17-SEP-16:30 | 31.10 | 24.77 | 0.124620E+09 | 70.30 | 04-SEP-20:49 | 31.10 | 24.77 |
| October | 0.290590E+10 | 2023.81 | 03-OCT-16:30 | 30.85 | 25.08 | 0.128775E+09 | 70.30 | 19-OCT-03:49 | 23.40 | 18.62 |
| November | 0.211504E+10 | 1601.49 | 03-NOV-16:04 | 28.22 | 24.50 | 0.123643E+09 | 70.30 | 01-NOV-20:49 | 28.22 | 24.50 |
| December | 0.149177E+10 | 1575.81 | 10-DEC-15:30 | 28.60 | 22.59 | 0.124992E+09 | 70.32 | 13-DEC-23:49 | 15.68 | 13.22 |
| Annual Sum or Average | 0.307815E+11 | 0.150156E+10 | ||||||||
| Minimum of Months | 0.129581E+10 | 1305.48 | 26.42 | 20.44 | 0.112508E+09 | 70.28 | 15.40 | 9.10 | ||
| Maximum of Months | 0.359945E+10 | 2461.92 | 34.70 | 25.08 | 0.128775E+09 | 70.32 | 34.70 | 25.03 |
Report: ZoneCoolingSummaryMonthly
For: M SE APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.220578E+10 | 2271.41 | 02-JAN-14:30 | 28.90 | 24.11 | 0.127948E+09 | 70.31 | 22-JAN-21:10 | 15.92 | 12.89 |
| February | 0.216837E+10 | 2120.77 | 11-FEB-14:30 | 28.85 | 24.07 | 0.113130E+09 | 70.32 | 05-FEB-22:10 | 28.85 | 24.07 |
| March | 0.245515E+10 | 1928.00 | 04-MAR-13:40 | 27.43 | 22.97 | 0.122647E+09 | 70.31 | 02-MAR-06:10 | 27.43 | 22.97 |
| April | 0.285507E+10 | 2042.73 | 15-APR-16:15 | 31.70 | 22.94 | 0.123945E+09 | 70.30 | 02-APR-18:30 | 31.70 | 22.94 |
| May | 0.328349E+10 | 2107.59 | 29-MAY-16:04 | 33.03 | 24.50 | 0.125734E+09 | 70.30 | 08-MAY-04:30 | 33.03 | 24.50 |
| June | 0.337426E+10 | 1997.24 | 03-JUN-16:07 | 31.10 | 24.60 | 0.120421E+09 | 70.29 | 14-JUN-05:00 | 23.30 | 22.07 |
| July | 0.359367E+10 | 2197.20 | 29-JUL-16:07 | 35.40 | 24.35 | 0.129275E+09 | 70.28 | 07-JUL-02:00 | 35.40 | 24.35 |
| August | 0.352097E+10 | 2133.79 | 20-AUG-12:00 | 32.20 | 26.10 | 0.123963E+09 | 70.29 | 14-AUG-02:00 | 32.20 | 26.10 |
| September | 0.359136E+10 | 2341.35 | 24-SEP-12:30 | 31.10 | 24.42 | 0.123963E+09 | 70.30 | 04-SEP-20:49 | 31.10 | 24.42 |
| October | 0.356965E+10 | 2344.42 | 25-OCT-13:00 | 30.00 | 22.19 | 0.127505E+09 | 70.30 | 19-OCT-03:49 | 30.00 | 22.19 |
| November | 0.286413E+10 | 2383.58 | 22-NOV-12:30 | 27.50 | 22.77 | 0.123369E+09 | 70.30 | 01-NOV-20:49 | 27.50 | 22.77 |
| December | 0.225298E+10 | 2268.08 | 09-DEC-12:30 | 27.20 | 22.50 | 0.127605E+09 | 70.32 | 13-DEC-00:00 | 11.70 | 9.89 |
| Annual Sum or Average | 0.357349E+11 | 0.148951E+10 | ||||||||
| Minimum of Months | 0.216837E+10 | 1928.00 | 27.20 | 22.19 | 0.113130E+09 | 70.28 | 11.70 | 9.89 | ||
| Maximum of Months | 0.359367E+10 | 2383.58 | 35.40 | 26.10 | 0.129275E+09 | 70.32 | 35.40 | 26.10 |
Report: ZoneCoolingSummaryMonthly
For: M NE APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.132736E+10 | 1212.20 | 07-JAN-13:00 | 28.30 | 22.51 | 0.125279E+09 | 70.32 | 09-JAN-22:10 | 14.90 | 10.38 |
| February | 0.148147E+10 | 1360.06 | 02-FEB-14:00 | 28.30 | 22.51 | 0.112510E+09 | 70.31 | 21-FEB-05:19 | 16.33 | 15.55 |
| March | 0.194650E+10 | 1593.30 | 13-MAR-17:00 | 28.90 | 21.99 | 0.126423E+09 | 70.31 | 17-MAR-21:10 | 19.32 | 14.27 |
| April | 0.258318E+10 | 1865.25 | 15-APR-16:50 | 31.70 | 22.84 | 0.124594E+09 | 70.30 | 10-APR-21:49 | 31.70 | 22.84 |
| May | 0.329669E+10 | 2107.27 | 29-MAY-16:20 | 32.77 | 24.48 | 0.128775E+09 | 70.30 | 08-MAY-04:30 | 32.77 | 24.48 |
| June | 0.347417E+10 | 2006.57 | 14-JUN-17:20 | 29.80 | 23.59 | 0.124621E+09 | 70.29 | 14-JUN-05:00 | 29.80 | 23.59 |
| July | 0.364688E+10 | 2122.90 | 29-JUL-16:03 | 35.40 | 24.35 | 0.128775E+09 | 70.28 | 07-JUL-02:00 | 35.40 | 24.35 |
| August | 0.342783E+10 | 1953.00 | 20-AUG-12:00 | 32.20 | 26.10 | 0.128775E+09 | 70.29 | 14-AUG-02:00 | 32.20 | 26.10 |
| September | 0.324751E+10 | 1944.95 | 18-SEP-16:03 | 31.60 | 25.51 | 0.124620E+09 | 70.30 | 04-SEP-20:49 | 31.60 | 25.51 |
| October | 0.292524E+10 | 1817.75 | 03-OCT-16:03 | 31.02 | 24.99 | 0.128775E+09 | 70.30 | 19-OCT-03:49 | 23.40 | 18.62 |
| November | 0.212078E+10 | 1482.85 | 03-NOV-16:04 | 28.22 | 24.50 | 0.123697E+09 | 70.30 | 01-NOV-20:49 | 28.22 | 24.50 |
| December | 0.143285E+10 | 1361.75 | 10-DEC-14:00 | 28.90 | 23.02 | 0.124834E+09 | 70.30 | 21-DEC-23:10 | 18.90 | 16.02 |
| Annual Sum or Average | 0.309105E+11 | 0.150168E+10 | ||||||||
| Minimum of Months | 0.132736E+10 | 1212.20 | 28.22 | 21.99 | 0.112510E+09 | 70.28 | 14.90 | 10.38 | ||
| Maximum of Months | 0.364688E+10 | 2122.90 | 35.40 | 26.10 | 0.128775E+09 | 70.32 | 35.40 | 26.10 |
Report: ZoneCoolingSummaryMonthly
For: M N1 APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.130891E+10 | 969.37 | 01-JAN-17:05 | 24.82 | 21.57 | 0.127283E+09 | 70.32 | 22-JAN-00:40 | 15.20 | 11.96 |
| February | 0.137368E+10 | 1125.38 | 11-FEB-17:10 | 27.02 | 23.97 | 0.114193E+09 | 70.32 | 22-FEB-02:39 | 13.87 | 10.93 |
| March | 0.171657E+10 | 1272.82 | 13-MAR-17:05 | 28.80 | 22.02 | 0.127497E+09 | 70.31 | 11-MAR-02:09 | 28.80 | 22.02 |
| April | 0.213961E+10 | 1424.06 | 15-APR-17:07 | 31.42 | 22.68 | 0.124613E+09 | 70.30 | 10-APR-21:49 | 31.42 | 22.68 |
| May | 0.267366E+10 | 1635.88 | 29-MAY-17:07 | 31.60 | 24.40 | 0.128775E+09 | 70.30 | 08-MAY-04:30 | 31.60 | 24.40 |
| June | 0.278549E+10 | 1592.66 | 14-JUN-17:30 | 29.70 | 23.56 | 0.124621E+09 | 70.29 | 14-JUN-05:00 | 29.70 | 23.56 |
| July | 0.290508E+10 | 1629.41 | 27-JUL-17:30 | 33.30 | 25.43 | 0.128775E+09 | 70.28 | 07-JUL-02:00 | 33.30 | 25.43 |
| August | 0.277325E+10 | 1495.27 | 02-AUG-17:30 | 30.55 | 24.65 | 0.128775E+09 | 70.29 | 14-AUG-02:00 | 22.80 | 22.32 |
| September | 0.262107E+10 | 1494.06 | 18-SEP-16:17 | 31.50 | 25.54 | 0.124620E+09 | 70.30 | 04-SEP-20:49 | 31.50 | 25.54 |
| October | 0.243260E+10 | 1401.83 | 03-OCT-16:03 | 31.02 | 24.99 | 0.128775E+09 | 70.30 | 19-OCT-03:49 | 23.40 | 18.62 |
| November | 0.189447E+10 | 1214.36 | 03-NOV-16:04 | 28.22 | 24.50 | 0.124251E+09 | 70.30 | 12-NOV-02:09 | 15.50 | 10.90 |
| December | 0.142722E+10 | 1082.02 | 10-DEC-17:10 | 27.02 | 22.46 | 0.127109E+09 | 70.32 | 19-DEC-22:10 | 16.02 | 12.32 |
| Annual Sum or Average | 0.260516E+11 | 0.150929E+10 | ||||||||
| Minimum of Months | 0.130891E+10 | 969.37 | 24.82 | 21.57 | 0.114193E+09 | 70.28 | 13.87 | 10.90 | ||
| Maximum of Months | 0.290508E+10 | 1635.88 | 33.30 | 25.54 | 0.128775E+09 | 70.32 | 33.30 | 25.54 |
Report: ZoneCoolingSummaryMonthly
For: M N2 APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.131223E+10 | 970.71 | 01-JAN-17:05 | 24.82 | 21.57 | 0.127292E+09 | 70.32 | 20-JAN-22:10 | 16.02 | 12.26 |
| February | 0.137490E+10 | 1118.93 | 11-FEB-17:10 | 27.02 | 23.97 | 0.114195E+09 | 70.30 | 22-FEB-02:39 | 13.87 | 10.93 |
| March | 0.171795E+10 | 1267.92 | 13-MAR-17:05 | 28.80 | 22.02 | 0.127512E+09 | 70.32 | 20-MAR-22:40 | 14.60 | 10.20 |
| April | 0.213943E+10 | 1419.30 | 15-APR-17:07 | 31.42 | 22.68 | 0.124613E+09 | 70.30 | 10-APR-21:49 | 31.42 | 22.68 |
| May | 0.267382E+10 | 1630.38 | 29-MAY-17:07 | 31.60 | 24.40 | 0.128775E+09 | 70.30 | 08-MAY-04:30 | 31.60 | 24.40 |
| June | 0.278843E+10 | 1588.12 | 14-JUN-17:30 | 29.70 | 23.56 | 0.124621E+09 | 70.29 | 14-JUN-05:00 | 29.70 | 23.56 |
| July | 0.290682E+10 | 1625.16 | 27-JUL-17:30 | 33.30 | 25.43 | 0.128775E+09 | 70.28 | 07-JUL-02:00 | 33.30 | 25.43 |
| August | 0.277327E+10 | 1491.26 | 02-AUG-17:30 | 30.55 | 24.65 | 0.128775E+09 | 70.29 | 14-AUG-02:00 | 22.80 | 22.32 |
| September | 0.262312E+10 | 1491.09 | 18-SEP-16:17 | 31.50 | 25.54 | 0.124620E+09 | 70.30 | 04-SEP-20:49 | 31.50 | 25.54 |
| October | 0.243348E+10 | 1400.40 | 03-OCT-16:03 | 31.02 | 24.99 | 0.128775E+09 | 70.30 | 19-OCT-03:49 | 23.40 | 18.62 |
| November | 0.189553E+10 | 1213.07 | 03-NOV-16:04 | 28.22 | 24.50 | 0.124253E+09 | 70.31 | 12-NOV-02:09 | 15.50 | 10.90 |
| December | 0.142522E+10 | 1078.34 | 10-DEC-17:10 | 27.02 | 22.46 | 0.127104E+09 | 70.31 | 14-DEC-04:10 | 15.10 | 15.10 |
| Annual Sum or Average | 0.260642E+11 | 0.150931E+10 | ||||||||
| Minimum of Months | 0.131223E+10 | 970.71 | 24.82 | 21.57 | 0.114195E+09 | 70.28 | 13.87 | 10.20 | ||
| Maximum of Months | 0.290682E+10 | 1630.38 | 33.30 | 25.54 | 0.128775E+09 | 70.32 | 33.30 | 25.54 |
Report: ZoneCoolingSummaryMonthly
For: M S1 APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.223456E+10 | 2001.94 | 02-JAN-14:30 | 28.90 | 24.11 | 0.129023E+09 | 70.32 | 26-JAN-01:39 | 12.20 | 8.51 |
| February | 0.209454E+10 | 1832.21 | 20-FEB-15:00 | 26.70 | 17.88 | 0.114270E+09 | 70.30 | 19-FEB-19:49 | 26.70 | 17.88 |
| March | 0.223955E+10 | 1657.23 | 01-MAR-14:40 | 24.03 | 15.98 | 0.123485E+09 | 70.30 | 30-MAR-22:49 | 23.40 | 19.66 |
| April | 0.241372E+10 | 1588.20 | 15-APR-16:30 | 31.70 | 22.91 | 0.123956E+09 | 70.30 | 02-APR-18:30 | 31.70 | 22.91 |
| May | 0.266075E+10 | 1615.93 | 29-MAY-16:20 | 32.77 | 24.48 | 0.125734E+09 | 70.30 | 08-MAY-04:30 | 32.77 | 24.48 |
| June | 0.268518E+10 | 1514.81 | 03-JUN-16:30 | 31.10 | 24.60 | 0.120421E+09 | 70.29 | 14-JUN-05:00 | 23.30 | 22.07 |
| July | 0.285155E+10 | 1662.52 | 29-JUL-16:03 | 35.40 | 24.35 | 0.129275E+09 | 70.28 | 07-JUL-02:00 | 35.40 | 24.35 |
| August | 0.286679E+10 | 1612.19 | 20-AUG-16:07 | 30.60 | 24.86 | 0.123963E+09 | 70.29 | 14-AUG-02:00 | 30.60 | 24.86 |
| September | 0.296688E+10 | 1844.47 | 30-SEP-14:00 | 31.10 | 24.59 | 0.123963E+09 | 70.30 | 04-SEP-20:49 | 31.10 | 24.59 |
| October | 0.308248E+10 | 1936.54 | 29-OCT-14:00 | 30.00 | 25.83 | 0.127505E+09 | 70.30 | 19-OCT-03:49 | 30.00 | 25.83 |
| November | 0.265287E+10 | 2001.31 | 22-NOV-12:30 | 27.50 | 22.77 | 0.123815E+09 | 70.30 | 12-NOV-04:40 | 27.50 | 22.77 |
| December | 0.230433E+10 | 1955.98 | 10-DEC-14:40 | 28.90 | 22.80 | 0.128765E+09 | 70.32 | 13-DEC-03:20 | 10.20 | 9.75 |
| Annual Sum or Average | 0.310532E+11 | 0.149418E+10 | ||||||||
| Minimum of Months | 0.209454E+10 | 1514.81 | 24.03 | 15.98 | 0.114270E+09 | 70.28 | 10.20 | 8.51 | ||
| Maximum of Months | 0.308248E+10 | 2001.94 | 35.40 | 25.83 | 0.129275E+09 | 70.32 | 35.40 | 25.83 |
Report: ZoneCoolingSummaryMonthly
For: M S2 APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.223700E+10 | 2005.23 | 02-JAN-14:30 | 28.90 | 24.11 | 0.129022E+09 | 70.32 | 22-JAN-02:49 | 13.40 | 10.38 |
| February | 0.209559E+10 | 1832.15 | 20-FEB-14:50 | 26.60 | 17.86 | 0.114272E+09 | 70.30 | 19-FEB-19:49 | 26.60 | 17.86 |
| March | 0.224073E+10 | 1661.10 | 01-MAR-14:40 | 24.03 | 15.98 | 0.123485E+09 | 70.30 | 11-MAR-03:00 | 13.90 | 11.45 |
| April | 0.241357E+10 | 1584.79 | 15-APR-16:30 | 31.70 | 22.91 | 0.123956E+09 | 70.30 | 02-APR-18:30 | 31.70 | 22.91 |
| May | 0.266092E+10 | 1611.98 | 29-MAY-16:20 | 32.77 | 24.48 | 0.125734E+09 | 70.30 | 08-MAY-04:30 | 32.77 | 24.48 |
| June | 0.268815E+10 | 1515.42 | 03-JUN-16:30 | 31.10 | 24.60 | 0.120421E+09 | 70.29 | 14-JUN-05:00 | 23.30 | 22.07 |
| July | 0.285332E+10 | 1660.91 | 29-JUL-16:03 | 35.40 | 24.35 | 0.129275E+09 | 70.28 | 07-JUL-02:00 | 35.40 | 24.35 |
| August | 0.286681E+10 | 1609.08 | 31-AUG-16:07 | 31.52 | 24.72 | 0.123963E+09 | 70.29 | 14-AUG-02:00 | 31.52 | 24.72 |
| September | 0.296889E+10 | 1847.23 | 30-SEP-14:00 | 31.10 | 24.59 | 0.123963E+09 | 70.30 | 04-SEP-20:49 | 31.10 | 24.59 |
| October | 0.308330E+10 | 1937.72 | 29-OCT-14:00 | 30.00 | 25.83 | 0.127505E+09 | 70.30 | 19-OCT-03:49 | 30.00 | 25.83 |
| November | 0.265368E+10 | 2007.42 | 22-NOV-12:30 | 27.50 | 22.77 | 0.123816E+09 | 70.31 | 12-NOV-04:40 | 27.50 | 22.77 |
| December | 0.230258E+10 | 1955.01 | 10-DEC-14:40 | 28.90 | 22.80 | 0.128762E+09 | 70.32 | 12-DEC-07:40 | 11.50 | 8.35 |
| Annual Sum or Average | 0.310646E+11 | 0.149417E+10 | ||||||||
| Minimum of Months | 0.209559E+10 | 1515.42 | 24.03 | 15.98 | 0.114272E+09 | 70.28 | 11.50 | 8.35 | ||
| Maximum of Months | 0.308330E+10 | 2007.42 | 35.40 | 25.83 | 0.129275E+09 | 70.32 | 35.40 | 25.83 |
Report: ZoneCoolingSummaryMonthly
For: T SW APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.184685E+10 | 3097.22 | 02-JAN-14:40 | 28.90 | 23.86 | 0.118797E+09 | 70.36 | 25-JAN-19:40 | 14.80 | 7.67 |
| February | 0.204391E+10 | 3187.87 | 11-FEB-15:00 | 28.30 | 23.97 | 0.107005E+09 | 70.36 | 21-FEB-23:30 | 16.40 | 13.47 |
| March | 0.241987E+10 | 2920.40 | 13-MAR-16:30 | 29.15 | 22.20 | 0.118176E+09 | 70.37 | 17-MAR-22:00 | 18.90 | 14.59 |
| April | 0.303503E+10 | 3324.68 | 15-APR-16:30 | 31.70 | 22.91 | 0.123391E+09 | 70.34 | 26-APR-05:00 | 20.60 | 19.80 |
| May | 0.369971E+10 | 3389.21 | 29-MAY-16:20 | 32.77 | 24.48 | 0.125734E+09 | 70.30 | 08-MAY-04:30 | 32.77 | 24.48 |
| June | 0.379797E+10 | 3084.64 | 14-JUN-17:13 | 29.80 | 23.59 | 0.120421E+09 | 70.30 | 14-JUN-05:00 | 29.80 | 23.59 |
| July | 0.412281E+10 | 3440.76 | 29-JUL-16:13 | 35.20 | 24.31 | 0.129275E+09 | 70.28 | 07-JUL-02:00 | 35.20 | 24.31 |
| August | 0.400584E+10 | 3268.01 | 31-AUG-15:30 | 31.95 | 24.87 | 0.123963E+09 | 70.29 | 14-AUG-02:00 | 31.95 | 24.87 |
| September | 0.399727E+10 | 3544.26 | 30-SEP-15:30 | 31.10 | 24.59 | 0.123963E+09 | 70.30 | 04-SEP-20:49 | 31.10 | 24.59 |
| October | 0.379852E+10 | 3376.19 | 25-OCT-15:20 | 29.03 | 22.22 | 0.127505E+09 | 70.30 | 19-OCT-03:49 | 29.03 | 22.22 |
| November | 0.285731E+10 | 3226.16 | 07-NOV-15:30 | 28.30 | 21.48 | 0.120345E+09 | 70.33 | 01-NOV-04:00 | 28.30 | 21.48 |
| December | 0.208375E+10 | 3188.54 | 10-DEC-15:00 | 28.90 | 22.68 | 0.120640E+09 | 70.36 | 12-DEC-19:30 | 15.85 | 11.16 |
| Annual Sum or Average | 0.377088E+11 | 0.145921E+10 | ||||||||
| Minimum of Months | 0.184685E+10 | 2920.40 | 28.30 | 21.48 | 0.107005E+09 | 70.28 | 14.80 | 7.67 | ||
| Maximum of Months | 0.412281E+10 | 3544.26 | 35.20 | 24.87 | 0.129275E+09 | 70.37 | 35.20 | 24.87 |
Report: ZoneCoolingSummaryMonthly
For: T NW APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.103273E+10 | 1701.68 | 02-JAN-15:10 | 28.35 | 22.91 | 0.113937E+09 | 70.36 | 27-JAN-23:10 | 19.32 | 15.37 |
| February | 0.135697E+10 | 2313.57 | 11-FEB-16:20 | 27.60 | 24.09 | 0.106402E+09 | 70.32 | 21-FEB-21:40 | 18.50 | 14.39 |
| March | 0.192115E+10 | 2549.77 | 13-MAR-16:30 | 29.15 | 22.20 | 0.121121E+09 | 70.35 | 03-MAR-01:30 | 29.15 | 22.20 |
| April | 0.273998E+10 | 3094.42 | 15-APR-16:40 | 31.70 | 22.88 | 0.124008E+09 | 70.32 | 26-APR-05:00 | 20.60 | 19.80 |
| May | 0.371825E+10 | 3414.95 | 29-MAY-16:30 | 32.50 | 24.46 | 0.128775E+09 | 70.30 | 08-MAY-04:30 | 32.50 | 24.46 |
| June | 0.390826E+10 | 3250.70 | 14-JUN-17:17 | 29.80 | 23.59 | 0.124621E+09 | 70.30 | 14-JUN-05:00 | 29.80 | 23.59 |
| July | 0.418173E+10 | 3354.09 | 27-JUL-16:17 | 34.80 | 25.11 | 0.128775E+09 | 70.28 | 07-JUL-02:00 | 34.80 | 25.11 |
| August | 0.390256E+10 | 3135.30 | 16-AUG-16:17 | 31.50 | 24.94 | 0.128775E+09 | 70.29 | 14-AUG-02:00 | 31.50 | 24.94 |
| September | 0.362042E+10 | 3024.91 | 17-SEP-16:20 | 31.10 | 24.83 | 0.124620E+09 | 70.30 | 04-SEP-20:49 | 31.10 | 24.83 |
| October | 0.310881E+10 | 2673.42 | 03-OCT-16:17 | 30.93 | 25.03 | 0.128775E+09 | 70.30 | 19-OCT-03:49 | 23.40 | 18.62 |
| November | 0.208827E+10 | 2112.31 | 02-NOV-16:10 | 28.22 | 22.48 | 0.120739E+09 | 70.31 | 14-NOV-21:00 | 18.30 | 14.31 |
| December | 0.130340E+10 | 2070.12 | 10-DEC-15:20 | 28.70 | 22.62 | 0.116186E+09 | 70.33 | 05-DEC-04:49 | 28.70 | 22.62 |
| Annual Sum or Average | 0.328825E+11 | 0.146673E+10 | ||||||||
| Minimum of Months | 0.103273E+10 | 1701.68 | 27.60 | 22.20 | 0.106402E+09 | 70.28 | 18.30 | 14.31 | ||
| Maximum of Months | 0.418173E+10 | 3414.95 | 34.80 | 25.11 | 0.128775E+09 | 70.36 | 34.80 | 25.11 |
Report: ZoneCoolingSummaryMonthly
For: T SE APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.187898E+10 | 2979.80 | 02-JAN-14:30 | 28.90 | 24.11 | 0.118659E+09 | 70.35 | 05-JAN-00:20 | 18.90 | 17.12 |
| February | 0.203253E+10 | 2941.99 | 11-FEB-14:30 | 28.85 | 24.07 | 0.107059E+09 | 70.35 | 27-FEB-00:49 | 17.20 | 14.26 |
| March | 0.237676E+10 | 2582.53 | 04-MAR-13:40 | 27.43 | 22.97 | 0.118072E+09 | 70.36 | 21-MAR-22:30 | 18.05 | 14.27 |
| April | 0.301299E+10 | 2775.63 | 15-APR-16:05 | 31.70 | 22.98 | 0.123374E+09 | 70.33 | 26-APR-05:00 | 20.60 | 19.80 |
| May | 0.369467E+10 | 2913.77 | 29-MAY-16:04 | 33.03 | 24.50 | 0.125734E+09 | 70.30 | 08-MAY-04:30 | 33.03 | 24.50 |
| June | 0.387377E+10 | 2682.79 | 03-JUN-16:07 | 31.10 | 24.60 | 0.120421E+09 | 70.30 | 14-JUN-05:00 | 23.30 | 22.07 |
| July | 0.417197E+10 | 3064.68 | 29-JUL-16:08 | 35.40 | 24.35 | 0.129275E+09 | 70.28 | 07-JUL-02:00 | 35.40 | 24.35 |
| August | 0.399654E+10 | 2985.50 | 23-AUG-13:00 | 33.90 | 25.44 | 0.123963E+09 | 70.29 | 14-AUG-02:00 | 33.90 | 25.44 |
| September | 0.405057E+10 | 3219.72 | 30-SEP-14:00 | 31.10 | 24.59 | 0.123962E+09 | 70.30 | 04-SEP-20:49 | 31.10 | 24.59 |
| October | 0.381694E+10 | 3192.05 | 25-OCT-13:00 | 30.00 | 22.19 | 0.127505E+09 | 70.30 | 19-OCT-03:49 | 30.00 | 22.19 |
| November | 0.285860E+10 | 3135.52 | 22-NOV-12:40 | 27.60 | 22.86 | 0.120459E+09 | 70.32 | 26-NOV-02:49 | 19.08 | 18.96 |
| December | 0.201345E+10 | 2977.74 | 09-DEC-12:30 | 27.20 | 22.50 | 0.120403E+09 | 70.37 | 28-DEC-19:19 | 19.80 | 14.51 |
| Annual Sum or Average | 0.377778E+11 | 0.145889E+10 | ||||||||
| Minimum of Months | 0.187898E+10 | 2582.53 | 27.20 | 22.19 | 0.107059E+09 | 70.28 | 17.20 | 14.26 | ||
| Maximum of Months | 0.417197E+10 | 3219.72 | 35.40 | 25.44 | 0.129275E+09 | 70.37 | 35.40 | 25.44 |
Report: ZoneCoolingSummaryMonthly
For: T NE APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.105227E+10 | 1554.52 | 02-JAN-15:00 | 28.90 | 23.37 | 0.113795E+09 | 70.35 | 19-JAN-02:49 | 19.08 | 16.08 |
| February | 0.133883E+10 | 1929.30 | 11-FEB-14:00 | 29.40 | 24.15 | 0.106308E+09 | 70.37 | 28-FEB-01:10 | 18.12 | 14.00 |
| March | 0.187696E+10 | 2099.25 | 13-MAR-16:30 | 29.15 | 22.20 | 0.120957E+09 | 70.35 | 23-MAR-03:49 | 21.10 | 16.88 |
| April | 0.271799E+10 | 2527.23 | 15-APR-16:20 | 31.70 | 22.94 | 0.123995E+09 | 70.31 | 26-APR-05:00 | 20.60 | 19.80 |
| May | 0.371347E+10 | 2913.36 | 29-MAY-16:15 | 32.77 | 24.48 | 0.128775E+09 | 70.30 | 08-MAY-04:30 | 32.77 | 24.48 |
| June | 0.398450E+10 | 2676.64 | 03-JUN-16:07 | 31.10 | 24.60 | 0.124621E+09 | 70.30 | 14-JUN-05:00 | 23.30 | 22.07 |
| July | 0.423111E+10 | 2952.09 | 29-JUL-16:03 | 35.40 | 24.35 | 0.128775E+09 | 70.28 | 07-JUL-02:00 | 35.40 | 24.35 |
| August | 0.389344E+10 | 2730.15 | 22-AUG-13:00 | 32.80 | 26.26 | 0.128775E+09 | 70.29 | 14-AUG-02:00 | 32.80 | 26.26 |
| September | 0.367338E+10 | 2568.84 | 18-SEP-16:01 | 31.60 | 25.51 | 0.124620E+09 | 70.30 | 04-SEP-20:49 | 31.60 | 25.51 |
| October | 0.312650E+10 | 2435.95 | 03-OCT-11:50 | 31.60 | 25.14 | 0.128775E+09 | 70.30 | 19-OCT-03:49 | 23.40 | 18.62 |
| November | 0.208307E+10 | 1967.34 | 03-NOV-13:30 | 29.40 | 24.30 | 0.120802E+09 | 70.36 | 14-NOV-23:10 | 18.30 | 14.06 |
| December | 0.124269E+10 | 1805.04 | 10-DEC-14:00 | 28.90 | 23.02 | 0.115725E+09 | 70.34 | 29-DEC-23:19 | 19.27 | 18.49 |
| Annual Sum or Average | 0.329342E+11 | 0.146592E+10 | ||||||||
| Minimum of Months | 0.105227E+10 | 1554.52 | 28.90 | 22.20 | 0.106308E+09 | 70.28 | 18.12 | 14.00 | ||
| Maximum of Months | 0.423111E+10 | 2952.09 | 35.40 | 26.26 | 0.128775E+09 | 70.37 | 35.40 | 26.26 |
Report: ZoneCoolingSummaryMonthly
For: T N1 APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.988994E+09 | 1219.68 | 02-JAN-15:00 | 28.90 | 23.37 | 0.117037E+09 | 70.35 | 29-JAN-03:39 | 19.40 | 18.28 |
| February | 0.119929E+10 | 1541.12 | 11-FEB-14:40 | 28.67 | 24.03 | 0.108329E+09 | 70.36 | 28-FEB-01:39 | 17.57 | 13.82 |
| March | 0.163825E+10 | 1712.85 | 13-MAR-16:40 | 29.07 | 22.13 | 0.122242E+09 | 70.36 | 10-MAR-22:49 | 29.07 | 22.13 |
| April | 0.225714E+10 | 2009.02 | 15-APR-16:30 | 31.70 | 22.91 | 0.124248E+09 | 70.36 | 03-APR-05:49 | 31.70 | 22.91 |
| May | 0.304597E+10 | 2315.90 | 29-MAY-16:30 | 32.50 | 24.46 | 0.128775E+09 | 70.30 | 08-MAY-04:30 | 32.50 | 24.46 |
| June | 0.324634E+10 | 2176.47 | 14-JUN-17:17 | 29.80 | 23.59 | 0.124621E+09 | 70.30 | 14-JUN-05:00 | 29.80 | 23.59 |
| July | 0.343322E+10 | 2337.02 | 29-JUL-16:13 | 35.20 | 24.31 | 0.128775E+09 | 70.28 | 07-JUL-02:00 | 35.20 | 24.31 |
| August | 0.319191E+10 | 2088.36 | 06-AUG-15:10 | 31.13 | 24.95 | 0.128775E+09 | 70.29 | 14-AUG-02:00 | 22.80 | 22.32 |
| September | 0.299951E+10 | 2046.00 | 18-SEP-16:03 | 31.60 | 25.51 | 0.124620E+09 | 70.30 | 04-SEP-20:49 | 31.60 | 25.51 |
| October | 0.260354E+10 | 1896.38 | 03-OCT-16:03 | 31.02 | 24.99 | 0.128775E+09 | 70.30 | 19-OCT-03:49 | 23.40 | 18.62 |
| November | 0.182627E+10 | 1557.94 | 03-NOV-16:10 | 28.22 | 24.50 | 0.121819E+09 | 70.31 | 25-NOV-06:40 | 19.40 | 19.40 |
| December | 0.118748E+10 | 1430.80 | 10-DEC-14:50 | 28.90 | 22.74 | 0.118403E+09 | 70.34 | 25-DEC-04:10 | 17.20 | 17.15 |
| Annual Sum or Average | 0.276179E+11 | 0.147642E+10 | ||||||||
| Minimum of Months | 0.988994E+09 | 1219.68 | 28.22 | 22.13 | 0.108329E+09 | 70.28 | 17.20 | 13.82 | ||
| Maximum of Months | 0.343322E+10 | 2337.02 | 35.20 | 25.51 | 0.128775E+09 | 70.36 | 35.20 | 25.51 |
Report: ZoneCoolingSummaryMonthly
For: T N2 APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.992347E+09 | 1222.39 | 02-JAN-15:00 | 28.90 | 23.37 | 0.117027E+09 | 70.36 | 12-JAN-00:20 | 17.60 | 15.32 |
| February | 0.120104E+10 | 1540.58 | 11-FEB-14:40 | 28.67 | 24.03 | 0.108311E+09 | 70.35 | 12-FEB-05:40 | 17.97 | 16.23 |
| March | 0.163876E+10 | 1703.69 | 13-MAR-16:40 | 29.07 | 22.13 | 0.122235E+09 | 70.37 | 10-MAR-22:49 | 29.07 | 22.13 |
| April | 0.225722E+10 | 2000.41 | 15-APR-16:20 | 31.70 | 22.94 | 0.124244E+09 | 70.33 | 03-APR-05:00 | 31.70 | 22.94 |
| May | 0.304622E+10 | 2305.69 | 29-MAY-16:20 | 32.77 | 24.48 | 0.128775E+09 | 70.30 | 08-MAY-04:30 | 32.77 | 24.48 |
| June | 0.324966E+10 | 2163.13 | 14-JUN-17:17 | 29.80 | 23.59 | 0.124621E+09 | 70.30 | 14-JUN-05:00 | 29.80 | 23.59 |
| July | 0.343540E+10 | 2330.28 | 29-JUL-16:13 | 35.20 | 24.31 | 0.128775E+09 | 70.28 | 07-JUL-02:00 | 35.20 | 24.31 |
| August | 0.319182E+10 | 2086.01 | 06-AUG-15:10 | 31.13 | 24.95 | 0.128775E+09 | 70.29 | 14-AUG-02:00 | 22.80 | 22.32 |
| September | 0.300197E+10 | 2039.40 | 18-SEP-16:03 | 31.60 | 25.51 | 0.124620E+09 | 70.30 | 04-SEP-20:49 | 31.60 | 25.51 |
| October | 0.260462E+10 | 1892.58 | 03-OCT-16:03 | 31.02 | 24.99 | 0.128775E+09 | 70.30 | 19-OCT-03:49 | 23.40 | 18.62 |
| November | 0.182744E+10 | 1556.69 | 03-NOV-14:10 | 29.22 | 24.44 | 0.121822E+09 | 70.30 | 25-NOV-06:40 | 19.40 | 19.40 |
| December | 0.118523E+10 | 1428.38 | 10-DEC-14:50 | 28.90 | 22.74 | 0.118354E+09 | 70.33 | 25-DEC-04:10 | 17.20 | 17.15 |
| Annual Sum or Average | 0.276317E+11 | 0.147633E+10 | ||||||||
| Minimum of Months | 0.992347E+09 | 1222.39 | 28.67 | 22.13 | 0.108311E+09 | 70.28 | 17.20 | 15.32 | ||
| Maximum of Months | 0.343540E+10 | 2330.28 | 35.20 | 25.51 | 0.128775E+09 | 70.37 | 35.20 | 25.51 |
Report: ZoneCoolingSummaryMonthly
For: T S1 APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.184254E+10 | 2658.43 | 02-JAN-14:30 | 28.90 | 24.11 | 0.122397E+09 | 70.36 | 24-JAN-20:49 | 12.30 | 7.35 |
| February | 0.190918E+10 | 2562.68 | 11-FEB-14:30 | 28.85 | 24.07 | 0.109376E+09 | 70.32 | 05-FEB-23:30 | 28.85 | 24.07 |
| March | 0.214172E+10 | 2109.43 | 04-MAR-13:50 | 27.62 | 23.01 | 0.119758E+09 | 70.37 | 14-MAR-22:00 | 16.10 | 11.06 |
| April | 0.255530E+10 | 2255.52 | 15-APR-16:05 | 31.70 | 22.98 | 0.123630E+09 | 70.35 | 02-APR-02:00 | 31.70 | 22.98 |
| May | 0.302746E+10 | 2308.67 | 29-MAY-16:04 | 33.03 | 24.50 | 0.125734E+09 | 70.30 | 08-MAY-04:30 | 33.03 | 24.50 |
| June | 0.313491E+10 | 2144.51 | 03-JUN-16:07 | 31.10 | 24.60 | 0.120421E+09 | 70.30 | 14-JUN-05:00 | 23.30 | 22.07 |
| July | 0.337369E+10 | 2445.34 | 29-JUL-16:03 | 35.40 | 24.35 | 0.129275E+09 | 70.28 | 07-JUL-02:00 | 35.40 | 24.35 |
| August | 0.329607E+10 | 2358.83 | 31-AUG-15:10 | 32.12 | 24.95 | 0.123963E+09 | 70.29 | 14-AUG-02:00 | 32.12 | 24.95 |
| September | 0.338010E+10 | 2695.88 | 30-SEP-14:00 | 31.10 | 24.59 | 0.123962E+09 | 70.30 | 04-SEP-20:49 | 31.10 | 24.59 |
| October | 0.330148E+10 | 2679.04 | 29-OCT-13:50 | 30.00 | 25.83 | 0.127505E+09 | 70.30 | 19-OCT-03:49 | 30.00 | 25.83 |
| November | 0.261634E+10 | 2663.55 | 22-NOV-12:40 | 27.60 | 22.86 | 0.121641E+09 | 70.34 | 11-NOV-02:00 | 27.60 | 22.86 |
| December | 0.201028E+10 | 2562.89 | 10-DEC-14:30 | 28.90 | 22.85 | 0.123237E+09 | 70.37 | 29-DEC-00:00 | 19.40 | 15.42 |
| Annual Sum or Average | 0.325891E+11 | 0.147090E+10 | ||||||||
| Minimum of Months | 0.184254E+10 | 2109.43 | 27.60 | 22.85 | 0.109376E+09 | 70.28 | 12.30 | 7.35 | ||
| Maximum of Months | 0.338010E+10 | 2695.88 | 35.40 | 25.83 | 0.129275E+09 | 70.37 | 35.40 | 25.83 |
Report: ZoneCoolingSummaryMonthly
For: T S2 APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.184686E+10 | 2662.74 | 02-JAN-14:30 | 28.90 | 24.11 | 0.122378E+09 | 70.36 | 08-JAN-20:49 | 15.78 | 13.01 |
| February | 0.191093E+10 | 2562.78 | 11-FEB-14:30 | 28.85 | 24.07 | 0.109363E+09 | 70.38 | 05-FEB-23:19 | 28.85 | 24.07 |
| March | 0.214330E+10 | 2114.67 | 04-MAR-13:50 | 27.62 | 23.01 | 0.119747E+09 | 70.36 | 17-MAR-23:49 | 18.90 | 14.80 |
| April | 0.255540E+10 | 2248.17 | 15-APR-16:05 | 31.70 | 22.98 | 0.123626E+09 | 70.33 | 02-APR-02:00 | 31.70 | 22.98 |
| May | 0.302774E+10 | 2299.90 | 29-MAY-16:04 | 33.03 | 24.50 | 0.125734E+09 | 70.30 | 08-MAY-04:30 | 33.03 | 24.50 |
| June | 0.313827E+10 | 2140.35 | 03-JUN-16:07 | 31.10 | 24.60 | 0.120421E+09 | 70.30 | 14-JUN-05:00 | 23.30 | 22.07 |
| July | 0.337590E+10 | 2439.23 | 29-JUL-16:03 | 35.40 | 24.35 | 0.129275E+09 | 70.28 | 07-JUL-02:00 | 35.40 | 24.35 |
| August | 0.329600E+10 | 2355.51 | 31-AUG-15:10 | 32.12 | 24.95 | 0.123963E+09 | 70.29 | 14-AUG-02:00 | 32.12 | 24.95 |
| September | 0.338254E+10 | 2698.67 | 30-SEP-14:00 | 31.10 | 24.59 | 0.123962E+09 | 70.30 | 04-SEP-20:49 | 31.10 | 24.59 |
| October | 0.330251E+10 | 2680.68 | 29-OCT-13:40 | 30.00 | 25.83 | 0.127505E+09 | 70.30 | 19-OCT-03:49 | 30.00 | 25.83 |
| November | 0.261750E+10 | 2674.72 | 22-NOV-12:40 | 27.60 | 22.86 | 0.121644E+09 | 70.34 | 11-NOV-02:00 | 27.60 | 22.86 |
| December | 0.200877E+10 | 2564.07 | 09-DEC-12:40 | 27.20 | 22.50 | 0.123219E+09 | 70.37 | 29-DEC-00:00 | 19.40 | 15.42 |
| Annual Sum or Average | 0.326057E+11 | 0.147084E+10 | ||||||||
| Minimum of Months | 0.184686E+10 | 2114.67 | 27.20 | 22.50 | 0.109363E+09 | 70.28 | 15.78 | 13.01 | ||
| Maximum of Months | 0.338254E+10 | 2698.67 | 35.40 | 25.83 | 0.129275E+09 | 70.38 | 35.40 | 25.83 |
Report: ZoneCoolingSummaryMonthly
For: T CORRIDOR
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 20.40 | 19.26 | 0.236392E+09 | 153.85 | 29-JAN-21:10 | 23.30 | 21.37 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 16.65 | 13.10 | 0.222549E+09 | 160.59 | 11-FEB-21:10 | 22.12 | 20.18 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 17.32 | 13.44 | 0.256515E+09 | 164.36 | 13-MAR-20:10 | 25.50 | 22.48 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 22.57 | 18.63 | 0.268855E+09 | 171.89 | 15-APR-20:10 | 26.52 | 21.98 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 22.05 | 20.01 | 0.289592E+09 | 174.30 | 29-MAY-20:10 | 28.22 | 24.58 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 26.68 | 24.42 | 0.287210E+09 | 175.05 | 03-JUN-20:10 | 29.40 | 24.88 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 26.83 | 23.72 | 0.298520E+09 | 179.66 | 29-JUL-20:10 | 28.40 | 23.25 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 28.60 | 25.82 | 0.295545E+09 | 175.05 | 02-AUG-20:10 | 28.98 | 24.80 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 27.05 | 24.00 | 0.285695E+09 | 174.85 | 09-SEP-20:10 | 28.53 | 24.49 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 27.93 | 23.96 | 0.285907E+09 | 168.93 | 03-OCT-20:10 | 27.80 | 25.31 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 22.40 | 21.03 | 0.258172E+09 | 163.67 | 03-NOV-20:10 | 26.20 | 24.48 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 24.10 | 21.22 | 0.243089E+09 | 159.31 | 09-DEC-21:10 | 24.32 | 22.47 |
| Annual Sum or Average | 0.00 | 0.322804E+10 | ||||||||
| Minimum of Months | 0.00 | 0.00 | 16.65 | 13.10 | 0.222549E+09 | 153.85 | 22.12 | 20.18 | ||
| Maximum of Months | 0.00 | 0.00 | 28.60 | 25.82 | 0.298520E+09 | 179.66 | 29.40 | 25.31 |
Report: ZoneCoolingSummaryMonthly
For: G CORRIDOR
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 20.40 | 19.26 | 0.252704E+09 | 166.97 | 01-JAN-22:49 | 22.38 | 20.71 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 16.65 | 13.10 | 0.234618E+09 | 163.30 | 11-FEB-22:49 | 21.20 | 19.31 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 17.32 | 13.44 | 0.265648E+09 | 166.45 | 13-MAR-17:10 | 28.80 | 22.02 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 22.57 | 18.63 | 0.279878E+09 | 196.36 | 15-APR-17:10 | 31.42 | 22.68 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 22.05 | 20.01 | 0.308532E+09 | 197.47 | 22-MAY-17:10 | 31.52 | 23.80 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 26.68 | 24.42 | 0.309719E+09 | 194.16 | 03-JUN-17:10 | 30.92 | 24.70 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 26.83 | 23.72 | 0.327834E+09 | 226.82 | 29-JUL-17:10 | 34.22 | 24.14 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 28.60 | 25.82 | 0.326101E+09 | 201.41 | 07-AUG-17:10 | 31.93 | 24.98 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 27.05 | 24.00 | 0.314344E+09 | 198.18 | 08-SEP-17:10 | 31.60 | 25.33 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 27.93 | 23.96 | 0.314675E+09 | 188.59 | 03-OCT-17:10 | 30.40 | 25.17 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 22.40 | 21.03 | 0.280073E+09 | 175.11 | 04-NOV-20:10 | 26.60 | 24.66 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 24.10 | 21.22 | 0.259997E+09 | 171.12 | 10-DEC-22:49 | 23.98 | 23.18 |
| Annual Sum or Average | 0.00 | 0.347412E+10 | ||||||||
| Minimum of Months | 0.00 | 0.00 | 16.65 | 13.10 | 0.234618E+09 | 163.30 | 21.20 | 19.31 | ||
| Maximum of Months | 0.00 | 0.00 | 28.60 | 25.82 | 0.327834E+09 | 226.82 | 34.22 | 25.33 |
Report: ZoneCoolingSummaryMonthly
For: M CORRIDOR
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 20.40 | 19.26 | 0.266866E+09 | 154.35 | 02-JAN-21:10 | 22.20 | 19.62 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 16.65 | 13.10 | 0.241954E+09 | 155.53 | 11-FEB-21:10 | 22.12 | 20.18 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 17.32 | 13.44 | 0.272510E+09 | 157.33 | 27-MAR-20:10 | 24.50 | 21.13 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 22.57 | 18.63 | 0.272234E+09 | 161.24 | 15-APR-20:10 | 26.52 | 21.98 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 22.05 | 20.01 | 0.285705E+09 | 161.40 | 20-MAY-20:10 | 26.02 | 21.57 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 26.68 | 24.42 | 0.279493E+09 | 162.91 | 29-JUN-20:10 | 28.90 | 25.09 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 26.83 | 23.72 | 0.290066E+09 | 164.17 | 29-JUL-20:10 | 28.40 | 23.25 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 28.60 | 25.82 | 0.288443E+09 | 163.26 | 19-AUG-20:10 | 28.90 | 24.82 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 27.05 | 24.00 | 0.279340E+09 | 162.59 | 18-SEP-20:10 | 28.80 | 24.60 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 27.93 | 23.96 | 0.285435E+09 | 160.48 | 07-OCT-20:10 | 27.70 | 23.73 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 22.40 | 21.03 | 0.268282E+09 | 157.36 | 03-NOV-20:10 | 26.20 | 24.48 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 24.10 | 21.22 | 0.267670E+09 | 156.63 | 09-DEC-21:10 | 24.32 | 22.47 |
| Annual Sum or Average | 0.00 | 0.329800E+10 | ||||||||
| Minimum of Months | 0.00 | 0.00 | 16.65 | 13.10 | 0.241954E+09 | 154.35 | 22.12 | 19.62 | ||
| Maximum of Months | 0.00 | 0.00 | 28.60 | 25.82 | 0.290066E+09 | 164.17 | 28.90 | 25.09 |
Report: ZoneHeatingSummaryMonthly
For: G SW APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 20.40 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 16.65 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 17.32 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 22.57 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 22.05 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 26.68 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 26.83 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 28.60 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 27.05 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 27.93 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 22.40 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 24.10 |
| Annual Sum or Average | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 16.65 | |
| Maximum of Months | 0.00 | 0.00 | 28.60 |
Report: ZoneHeatingSummaryMonthly
For: G NW APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 20.40 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 16.65 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 17.32 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 22.57 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 22.05 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 26.68 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 26.83 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 28.60 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 27.05 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 27.93 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 22.40 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 24.10 |
| Annual Sum or Average | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 16.65 | |
| Maximum of Months | 0.00 | 0.00 | 28.60 |
Report: ZoneHeatingSummaryMonthly
For: OFFICE
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.150561E+09 | 420.51 | 23-JAN-17:12 | 25.93 |
| February | 0.222748E+09 | 486.42 | 06-FEB-09:05 | 21.28 |
| March | 0.316597E+09 | 544.67 | 13-MAR-16:12 | 29.23 |
| April | 0.398704E+09 | 593.55 | 17-APR-16:13 | 31.50 |
| May | 0.510190E+09 | 624.44 | 22-MAY-16:13 | 32.43 |
| June | 0.518226E+09 | 601.94 | 09-JUN-16:13 | 31.10 |
| July | 0.463037E+09 | 734.99 | 28-JUL-16:13 | 34.80 |
| August | 0.488359E+09 | 622.77 | 07-AUG-16:13 | 32.20 |
| September | 0.374117E+09 | 612.81 | 08-SEP-16:13 | 32.03 |
| October | 0.362792E+09 | 554.62 | 03-OCT-16:13 | 30.93 |
| November | 0.320314E+09 | 525.25 | 29-NOV-08:05 | 25.10 |
| December | 0.216312E+09 | 474.79 | 01-DEC-08:05 | 23.48 |
| Annual Sum or Average | 0.434196E+10 | |||
| Minimum of Months | 0.150561E+09 | 420.51 | 21.28 | |
| Maximum of Months | 0.518226E+09 | 734.99 | 34.80 |
Report: ZoneHeatingSummaryMonthly
For: G NE APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 20.40 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 16.65 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 17.32 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 22.57 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 22.05 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 26.68 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 26.83 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 28.60 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 27.05 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 27.93 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 22.40 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 24.10 |
| Annual Sum or Average | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 16.65 | |
| Maximum of Months | 0.00 | 0.00 | 28.60 |
Report: ZoneHeatingSummaryMonthly
For: G N1 APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 20.40 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 16.65 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 17.32 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 22.57 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 22.05 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 26.68 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 26.83 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 28.60 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 27.05 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 27.93 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 22.40 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 24.10 |
| Annual Sum or Average | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 16.65 | |
| Maximum of Months | 0.00 | 0.00 | 28.60 |
Report: ZoneHeatingSummaryMonthly
For: G N2 APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 20.40 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 16.65 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 17.32 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 22.57 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 22.05 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 26.68 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 26.83 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 28.60 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 27.05 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 27.93 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 22.40 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 24.10 |
| Annual Sum or Average | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 16.65 | |
| Maximum of Months | 0.00 | 0.00 | 28.60 |
Report: ZoneHeatingSummaryMonthly
For: G S1 APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 20.40 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 16.65 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 17.32 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 22.57 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 22.05 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 26.68 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 26.83 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 28.60 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 27.05 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 27.93 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 22.40 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 24.10 |
| Annual Sum or Average | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 16.65 | |
| Maximum of Months | 0.00 | 0.00 | 28.60 |
Report: ZoneHeatingSummaryMonthly
For: G S2 APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 20.40 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 16.65 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 17.32 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 22.57 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 22.05 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 26.68 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 26.83 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 28.60 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 27.05 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 27.93 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 22.40 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 24.10 |
| Annual Sum or Average | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 16.65 | |
| Maximum of Months | 0.00 | 0.00 | 28.60 |
Report: ZoneHeatingSummaryMonthly
For: M SW APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 20.40 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 16.65 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 17.32 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 22.57 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 22.05 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 26.68 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 26.83 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 28.60 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 27.05 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 27.93 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 22.40 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 24.10 |
| Annual Sum or Average | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 16.65 | |
| Maximum of Months | 0.00 | 0.00 | 28.60 |
Report: ZoneHeatingSummaryMonthly
For: M NW APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 20.40 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 16.65 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 17.32 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 22.57 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 22.05 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 26.68 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 26.83 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 28.60 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 27.05 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 27.93 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 22.40 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 24.10 |
| Annual Sum or Average | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 16.65 | |
| Maximum of Months | 0.00 | 0.00 | 28.60 |
Report: ZoneHeatingSummaryMonthly
For: M SE APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 20.40 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 16.65 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 17.32 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 22.57 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 22.05 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 26.68 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 26.83 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 28.60 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 27.05 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 27.93 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 22.40 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 24.10 |
| Annual Sum or Average | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 16.65 | |
| Maximum of Months | 0.00 | 0.00 | 28.60 |
Report: ZoneHeatingSummaryMonthly
For: M NE APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 20.40 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 16.65 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 17.32 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 22.57 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 22.05 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 26.68 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 26.83 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 28.60 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 27.05 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 27.93 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 22.40 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 24.10 |
| Annual Sum or Average | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 16.65 | |
| Maximum of Months | 0.00 | 0.00 | 28.60 |
Report: ZoneHeatingSummaryMonthly
For: M N1 APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 20.40 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 16.65 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 17.32 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 22.57 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 22.05 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 26.68 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 26.83 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 28.60 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 27.05 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 27.93 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 22.40 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 24.10 |
| Annual Sum or Average | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 16.65 | |
| Maximum of Months | 0.00 | 0.00 | 28.60 |
Report: ZoneHeatingSummaryMonthly
For: M N2 APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 20.40 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 16.65 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 17.32 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 22.57 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 22.05 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 26.68 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 26.83 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 28.60 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 27.05 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 27.93 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 22.40 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 24.10 |
| Annual Sum or Average | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 16.65 | |
| Maximum of Months | 0.00 | 0.00 | 28.60 |
Report: ZoneHeatingSummaryMonthly
For: M S1 APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 20.40 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 16.65 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 17.32 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 22.57 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 22.05 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 26.68 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 26.83 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 28.60 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 27.05 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 27.93 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 22.40 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 24.10 |
| Annual Sum or Average | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 16.65 | |
| Maximum of Months | 0.00 | 0.00 | 28.60 |
Report: ZoneHeatingSummaryMonthly
For: M S2 APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 20.40 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 16.65 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 17.32 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 22.57 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 22.05 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 26.68 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 26.83 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 28.60 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 27.05 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 27.93 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 22.40 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 24.10 |
| Annual Sum or Average | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 16.65 | |
| Maximum of Months | 0.00 | 0.00 | 28.60 |
Report: ZoneHeatingSummaryMonthly
For: T SW APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 7181437.55 | 517.39 | 25-JAN-07:00 | 9.40 |
| February | 39652548.12 | 1209.56 | 04-FEB-07:00 | 5.00 |
| March | 19031569.87 | 885.61 | 16-MAR-06:00 | 6.70 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 22.57 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 22.05 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 26.68 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 26.83 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 28.60 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 27.05 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 27.93 |
| November | 3892849.29 | 349.82 | 13-NOV-06:00 | 12.20 |
| December | 22957552.62 | 759.39 | 15-DEC-06:00 | 7.80 |
| Annual Sum or Average | 92715957.46 | |||
| Minimum of Months | 0.00 | 0.00 | 5.00 | |
| Maximum of Months | 39652548.12 | 1209.56 | 28.60 |
Report: ZoneHeatingSummaryMonthly
For: T NW APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 24485664.27 | 700.76 | 25-JAN-07:00 | 9.40 |
| February | 64807814.67 | 1364.07 | 04-FEB-06:00 | 5.60 |
| March | 32692508.07 | 1015.27 | 16-MAR-06:00 | 6.70 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 22.57 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 22.05 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 26.68 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 26.83 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 28.60 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 27.05 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 27.93 |
| November | 9202281.18 | 425.57 | 13-NOV-06:00 | 12.20 |
| December | 49555494.59 | 894.25 | 15-DEC-06:00 | 7.80 |
| Annual Sum or Average | 0.180744E+09 | |||
| Minimum of Months | 0.00 | 0.00 | 5.60 | |
| Maximum of Months | 64807814.67 | 1364.07 | 28.60 |
Report: ZoneHeatingSummaryMonthly
For: T SE APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 6571616.78 | 534.16 | 25-JAN-07:00 | 9.40 |
| February | 37868308.88 | 1230.16 | 04-FEB-07:00 | 5.00 |
| March | 14992706.89 | 903.34 | 16-MAR-06:00 | 6.70 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 22.57 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 22.05 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 26.68 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 26.83 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 28.60 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 27.05 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 27.93 |
| November | 3341012.75 | 344.09 | 13-NOV-06:00 | 12.20 |
| December | 22628192.54 | 768.55 | 15-DEC-06:00 | 7.80 |
| Annual Sum or Average | 85401837.85 | |||
| Minimum of Months | 0.00 | 0.00 | 5.00 | |
| Maximum of Months | 37868308.88 | 1230.16 | 28.60 |
Report: ZoneHeatingSummaryMonthly
For: T NE APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 21127671.78 | 734.09 | 25-JAN-07:00 | 9.40 |
| February | 59623507.78 | 1387.84 | 04-FEB-06:00 | 5.60 |
| March | 25388540.00 | 1052.98 | 16-MAR-06:00 | 6.70 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 22.57 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 22.05 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 26.68 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 26.83 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 28.60 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 27.05 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 27.93 |
| November | 6985483.09 | 421.57 | 13-NOV-06:00 | 12.20 |
| December | 47890359.52 | 903.04 | 15-DEC-06:00 | 7.80 |
| Annual Sum or Average | 0.161016E+09 | |||
| Minimum of Months | 0.00 | 0.00 | 5.60 | |
| Maximum of Months | 59623507.78 | 1387.84 | 28.60 |
Report: ZoneHeatingSummaryMonthly
For: T N1 APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 5543813.60 | 287.42 | 25-JAN-07:00 | 9.40 |
| February | 24939609.47 | 730.70 | 04-FEB-06:00 | 5.60 |
| March | 8977458.14 | 486.68 | 16-MAR-06:00 | 6.70 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 22.57 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 22.05 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 26.68 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 26.83 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 28.60 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 27.05 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 27.93 |
| November | 40724.84 | 11.49 | 13-NOV-12:20 | 23.67 |
| December | 6886362.70 | 314.90 | 15-DEC-06:00 | 7.80 |
| Annual Sum or Average | 46387968.76 | |||
| Minimum of Months | 0.00 | 0.00 | 5.60 | |
| Maximum of Months | 24939609.47 | 730.70 | 28.60 |
Report: ZoneHeatingSummaryMonthly
For: T N2 APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 5593727.08 | 290.39 | 25-JAN-07:00 | 9.40 |
| February | 25006983.07 | 733.60 | 04-FEB-06:00 | 5.60 |
| March | 9032945.00 | 490.17 | 16-MAR-06:00 | 6.70 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 22.57 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 22.05 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 26.68 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 26.83 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 28.60 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 27.05 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 27.93 |
| November | 32075.67 | 9.79 | 13-NOV-12:20 | 23.67 |
| December | 7035244.50 | 316.68 | 15-DEC-06:00 | 7.80 |
| Annual Sum or Average | 46700975.31 | |||
| Minimum of Months | 0.00 | 0.00 | 5.60 | |
| Maximum of Months | 25006983.07 | 733.60 | 28.60 |
Report: ZoneHeatingSummaryMonthly
For: T S1 APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 47436.07 | 42.46 | 25-JAN-07:00 | 9.40 |
| February | 9848616.47 | 561.71 | 04-FEB-07:00 | 5.00 |
| March | 2245088.89 | 296.79 | 16-MAR-06:00 | 6.70 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 22.57 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 22.05 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 26.68 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 26.83 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 28.60 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 27.05 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 27.93 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 22.40 |
| December | 744074.07 | 135.91 | 15-DEC-06:00 | 7.80 |
| Annual Sum or Average | 12885215.49 | |||
| Minimum of Months | 0.00 | 0.00 | 5.00 | |
| Maximum of Months | 9848616.47 | 561.71 | 28.60 |
Report: ZoneHeatingSummaryMonthly
For: T S2 APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 52544.36 | 44.56 | 25-JAN-07:00 | 9.40 |
| February | 9924275.45 | 564.04 | 04-FEB-07:00 | 5.00 |
| March | 2253272.52 | 298.43 | 16-MAR-06:00 | 6.70 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 22.57 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 22.05 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 26.68 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 26.83 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 28.60 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 27.05 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 27.93 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 22.40 |
| December | 763123.79 | 137.46 | 15-DEC-06:00 | 7.80 |
| Annual Sum or Average | 12993216.12 | |||
| Minimum of Months | 0.00 | 0.00 | 5.00 | |
| Maximum of Months | 9924275.45 | 564.04 | 28.60 |
Report: ZoneHeatingSummaryMonthly
For: T CORRIDOR
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 20.40 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 16.65 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 17.32 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 22.57 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 22.05 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 26.68 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 26.83 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 28.60 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 27.05 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 27.93 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 22.40 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 24.10 |
| Annual Sum or Average | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 16.65 | |
| Maximum of Months | 0.00 | 0.00 | 28.60 |
Report: ZoneHeatingSummaryMonthly
For: G CORRIDOR
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 20.40 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 16.65 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 17.32 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 22.57 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 22.05 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 26.68 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 26.83 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 28.60 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 27.05 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 27.93 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 22.40 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 24.10 |
| Annual Sum or Average | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 16.65 | |
| Maximum of Months | 0.00 | 0.00 | 28.60 |
Report: ZoneHeatingSummaryMonthly
For: M CORRIDOR
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 20.40 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 16.65 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 17.32 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 22.57 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 22.05 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 26.68 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 26.83 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 28.60 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 27.05 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 27.93 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 22.40 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 24.10 |
| Annual Sum or Average | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 16.65 | |
| Maximum of Months | 0.00 | 0.00 | 28.60 |
Report: ZoneElectricSummaryMonthly
For: G SW APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: G NW APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: OFFICE
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.609777E+09 | 582.92 | 03-JAN-08:09 | 0.787690E+09 | 588.62 | 03-JAN-08:09 |
| February | 0.564682E+09 | 582.92 | 01-FEB-08:09 | 0.723971E+09 | 588.62 | 01-FEB-08:09 |
| March | 0.654405E+09 | 582.92 | 01-MAR-08:09 | 0.827804E+09 | 588.62 | 01-MAR-08:09 |
| April | 0.599704E+09 | 582.92 | 03-APR-07:10 | 0.770907E+09 | 588.62 | 03-APR-07:10 |
| May | 0.639529E+09 | 582.92 | 01-MAY-07:10 | 0.814432E+09 | 588.62 | 01-MAY-07:10 |
| June | 0.629456E+09 | 582.92 | 01-JUN-07:10 | 0.797650E+09 | 588.62 | 01-JUN-07:10 |
| July | 0.609777E+09 | 582.92 | 03-JUL-07:10 | 0.787690E+09 | 588.62 | 03-JUL-07:10 |
| August | 0.654405E+09 | 582.92 | 01-AUG-07:10 | 0.827804E+09 | 588.62 | 01-AUG-07:10 |
| September | 0.599704E+09 | 582.92 | 01-SEP-07:10 | 0.770907E+09 | 588.62 | 01-SEP-07:10 |
| October | 0.624653E+09 | 582.92 | 02-OCT-07:10 | 0.801061E+09 | 588.62 | 02-OCT-07:10 |
| November | 0.599704E+09 | 582.92 | 01-NOV-07:10 | 0.770907E+09 | 588.62 | 01-NOV-07:10 |
| December | 0.609777E+09 | 582.92 | 01-DEC-08:09 | 0.787690E+09 | 588.62 | 01-DEC-08:09 |
| Annual Sum or Average | 0.739557E+10 | 0.946851E+10 | ||||
| Minimum of Months | 0.564682E+09 | 582.92 | 0.723971E+09 | 588.62 | ||
| Maximum of Months | 0.654405E+09 | 582.92 | 0.827804E+09 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: G NE APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: G N1 APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: G N2 APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: G S1 APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: G S2 APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: M SW APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: M NW APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: M SE APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: M NE APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: M N1 APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: M N2 APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: M S1 APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: M S2 APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: T SW APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: T NW APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: T SE APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: T NE APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: T N1 APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: T N2 APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: T S1 APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: T S2 APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: T CORRIDOR
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
| January | 0.992689E+09 | 370.63 | 01-JAN-00:10 | 0.00 | 0.00 |
| February | 0.896622E+09 | 370.63 | 01-FEB-00:10 | 0.00 | 0.00 |
| March | 0.992689E+09 | 370.63 | 01-MAR-00:10 | 0.00 | 0.00 |
| April | 0.960667E+09 | 370.63 | 01-APR-00:10 | 0.00 | 0.00 |
| May | 0.992689E+09 | 370.63 | 01-MAY-00:10 | 0.00 | 0.00 |
| June | 0.960667E+09 | 370.63 | 01-JUN-00:10 | 0.00 | 0.00 |
| July | 0.992689E+09 | 370.63 | 01-JUL-00:10 | 0.00 | 0.00 |
| August | 0.992689E+09 | 370.63 | 01-AUG-00:10 | 0.00 | 0.00 |
| September | 0.960667E+09 | 370.63 | 01-SEP-00:10 | 0.00 | 0.00 |
| October | 0.992689E+09 | 370.63 | 01-OCT-00:10 | 0.00 | 0.00 |
| November | 0.960667E+09 | 370.63 | 01-NOV-00:10 | 0.00 | 0.00 |
| December | 0.992689E+09 | 370.63 | 01-DEC-00:10 | 0.00 | 0.00 |
| Annual Sum or Average | 0.116881E+11 | 0.00 | 0.00 | ||
| Minimum of Months | 0.896622E+09 | 370.63 | 0.00 | 0.00 | |
| Maximum of Months | 0.992689E+09 | 370.63 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: G CORRIDOR
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.992689E+09 | 370.63 | 01-JAN-00:10 | 0.599555E+10 | 4168.07 | 01-JAN-07:10 |
| February | 0.896622E+09 | 370.63 | 01-FEB-00:10 | 0.541534E+10 | 4168.07 | 01-FEB-07:10 |
| March | 0.992689E+09 | 370.63 | 01-MAR-00:10 | 0.599555E+10 | 4168.07 | 01-MAR-07:10 |
| April | 0.960667E+09 | 370.63 | 01-APR-00:10 | 0.580215E+10 | 4168.07 | 01-APR-06:10 |
| May | 0.992689E+09 | 370.63 | 01-MAY-00:10 | 0.599555E+10 | 4168.07 | 01-MAY-06:10 |
| June | 0.960667E+09 | 370.63 | 01-JUN-00:10 | 0.580215E+10 | 4168.07 | 01-JUN-06:10 |
| July | 0.992689E+09 | 370.63 | 01-JUL-00:10 | 0.599555E+10 | 4168.07 | 01-JUL-06:10 |
| August | 0.992689E+09 | 370.63 | 01-AUG-00:10 | 0.599555E+10 | 4168.07 | 01-AUG-06:10 |
| September | 0.960667E+09 | 370.63 | 01-SEP-00:10 | 0.580215E+10 | 4168.07 | 01-SEP-06:10 |
| October | 0.992689E+09 | 370.63 | 01-OCT-00:10 | 0.599555E+10 | 4168.07 | 01-OCT-06:10 |
| November | 0.960667E+09 | 370.63 | 01-NOV-00:10 | 0.580215E+10 | 4168.07 | 01-NOV-06:10 |
| December | 0.992689E+09 | 370.63 | 01-DEC-00:10 | 0.599555E+10 | 4168.07 | 01-DEC-07:10 |
| Annual Sum or Average | 0.116881E+11 | 0.705928E+11 | ||||
| Minimum of Months | 0.896622E+09 | 370.63 | 0.541534E+10 | 4168.07 | ||
| Maximum of Months | 0.992689E+09 | 370.63 | 0.599555E+10 | 4168.07 |
Report: ZoneElectricSummaryMonthly
For: M CORRIDOR
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
| January | 0.992689E+09 | 370.63 | 01-JAN-00:10 | 0.00 | 0.00 |
| February | 0.896622E+09 | 370.63 | 01-FEB-00:10 | 0.00 | 0.00 |
| March | 0.992689E+09 | 370.63 | 01-MAR-00:10 | 0.00 | 0.00 |
| April | 0.960667E+09 | 370.63 | 01-APR-00:10 | 0.00 | 0.00 |
| May | 0.992689E+09 | 370.63 | 01-MAY-00:10 | 0.00 | 0.00 |
| June | 0.960667E+09 | 370.63 | 01-JUN-00:10 | 0.00 | 0.00 |
| July | 0.992689E+09 | 370.63 | 01-JUL-00:10 | 0.00 | 0.00 |
| August | 0.992689E+09 | 370.63 | 01-AUG-00:10 | 0.00 | 0.00 |
| September | 0.960667E+09 | 370.63 | 01-SEP-00:10 | 0.00 | 0.00 |
| October | 0.992689E+09 | 370.63 | 01-OCT-00:10 | 0.00 | 0.00 |
| November | 0.960667E+09 | 370.63 | 01-NOV-00:10 | 0.00 | 0.00 |
| December | 0.992689E+09 | 370.63 | 01-DEC-00:10 | 0.00 | 0.00 |
| Annual Sum or Average | 0.116881E+11 | 0.00 | 0.00 | ||
| Minimum of Months | 0.896622E+09 | 370.63 | 0.00 | 0.00 | |
| Maximum of Months | 0.992689E+09 | 370.63 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: G SW APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11262545.99 | 0.140407E+09 |
| February | 0.389025E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 23338622.94 | 0.154026E+09 |
| March | 0.418950E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28109688.31 | 0.140973E+09 |
| April | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 56730994.28 | 36355312.49 |
| May | 0.424935E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.148511E+09 | 4501933.37 |
| June | 0.406980E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.156880E+09 | 212532.40 |
| July | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.141343E+09 | 745827.64 |
| August | 0.418950E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.165261E+09 | 1129036.16 |
| September | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.146010E+09 | 546032.66 |
| October | 0.430920E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111483E+09 | 3941505.53 |
| November | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 59321064.90 | 73754154.29 |
| December | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15666664.43 | 0.146033E+09 |
| Annual Sum or Average | 0.505732E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106392E+10 | 0.702627E+09 |
| Minimum of Months | 0.389025E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11262545.99 | 212532.40 |
| Maximum of Months | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.165261E+09 | 0.154026E+09 |
Report: SpaceGainsMonthly
For: G NW APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11262545.34 | 0.137260E+09 |
| February | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 23338634.29 | 0.149318E+09 |
| March | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28109684.05 | 0.137612E+09 |
| April | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 56730985.12 | 36348206.30 |
| May | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.148511E+09 | 4501934.62 |
| June | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.156880E+09 | 212532.83 |
| July | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.141343E+09 | 745828.69 |
| August | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.165261E+09 | 1129035.85 |
| September | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.146010E+09 | 546030.22 |
| October | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111483E+09 | 3941499.01 |
| November | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 59321046.05 | 73066574.10 |
| December | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15666658.63 | 0.143175E+09 |
| Annual Sum or Average | 0.512427E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106392E+10 | 0.687857E+09 |
| Minimum of Months | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11262545.34 | 212532.83 |
| Maximum of Months | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.165261E+09 | 0.149318E+09 |
Report: SpaceGainsMonthly
For: OFFICE
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.227408E+09 | 0.609777E+09 | 0.787690E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5235420.62 | 0.208879E+09 |
| February | 0.216037E+09 | 0.564682E+09 | 0.723971E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17568016.73 | 0.248843E+09 |
| March | 0.261519E+09 | 0.654405E+09 | 0.827804E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15855863.87 | 0.248524E+09 |
| April | 0.227408E+09 | 0.599704E+09 | 0.770907E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 29012741.12 | 0.134800E+09 |
| May | 0.250148E+09 | 0.639529E+09 | 0.814432E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 75195947.95 | 86629795.82 |
| June | 0.250148E+09 | 0.629456E+09 | 0.797650E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 67703423.00 | 35339066.11 |
| July | 0.227408E+09 | 0.609777E+09 | 0.787690E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 69670628.44 | 30455739.46 |
| August | 0.261519E+09 | 0.654405E+09 | 0.827804E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 81372088.31 | 30197859.66 |
| September | 0.227408E+09 | 0.599704E+09 | 0.770907E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 65155729.28 | 36051681.08 |
| October | 0.238778E+09 | 0.624653E+09 | 0.801061E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 52307178.29 | 70512378.88 |
| November | 0.227408E+09 | 0.599704E+09 | 0.770907E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 29092892.15 | 0.166593E+09 |
| December | 0.227408E+09 | 0.609777E+09 | 0.787690E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6359720.85 | 0.220114E+09 |
| Annual Sum or Average | 0.284259E+10 | 0.739557E+10 | 0.946851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.514530E+09 | 0.151694E+10 |
| Minimum of Months | 0.216037E+09 | 0.564682E+09 | 0.723971E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5235420.62 | 30197859.66 |
| Maximum of Months | 0.261519E+09 | 0.654405E+09 | 0.827804E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 81372088.31 | 0.248843E+09 |
Report: SpaceGainsMonthly
For: G NE APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11262549.59 | 0.138004E+09 |
| February | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 23338645.79 | 0.149685E+09 |
| March | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28109694.65 | 0.138804E+09 |
| April | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 56731000.30 | 36347446.31 |
| May | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.148511E+09 | 4501931.21 |
| June | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.156880E+09 | 212532.28 |
| July | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.141343E+09 | 745827.80 |
| August | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.165261E+09 | 1129034.76 |
| September | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.146010E+09 | 546029.64 |
| October | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111483E+09 | 3941497.28 |
| November | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 59321064.17 | 73245564.18 |
| December | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15666664.43 | 0.143382E+09 |
| Annual Sum or Average | 0.512427E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106392E+10 | 0.690545E+09 |
| Minimum of Months | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11262549.59 | 212532.28 |
| Maximum of Months | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.165261E+09 | 0.149685E+09 |
Report: SpaceGainsMonthly
For: G N1 APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6793288.16 | 84119711.04 |
| February | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14077289.04 | 92279071.34 |
| March | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16955064.02 | 84928232.52 |
| April | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34218711.38 | 21931924.24 |
| May | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 89578222.79 | 2715447.08 |
| June | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 94626186.39 | 128192.80 |
| July | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 85254338.92 | 449861.31 |
| August | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 99681075.05 | 681003.56 |
| September | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 88069278.68 | 329347.56 |
| October | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 67244011.05 | 2377406.59 |
| November | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 35780971.84 | 44551683.43 |
| December | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9449739.03 | 87742897.89 |
| Annual Sum or Average | 0.512427E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.641728E+09 | 0.422235E+09 |
| Minimum of Months | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6793288.16 | 128192.80 |
| Maximum of Months | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 99681075.05 | 92279071.34 |
Report: SpaceGainsMonthly
For: G N2 APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6793288.21 | 84133363.49 |
| February | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14077289.05 | 92295064.45 |
| March | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16955064.16 | 84957801.15 |
| April | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34218711.59 | 21931918.81 |
| May | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 89578223.33 | 2715447.01 |
| June | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 94626186.94 | 128192.80 |
| July | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 85254339.34 | 449861.30 |
| August | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 99681075.51 | 681003.54 |
| September | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 88069279.14 | 329347.56 |
| October | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 67244011.46 | 2377406.53 |
| November | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 35780972.10 | 44553320.45 |
| December | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9449739.12 | 87741334.25 |
| Annual Sum or Average | 0.512427E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.641728E+09 | 0.422294E+09 |
| Minimum of Months | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6793288.21 | 128192.80 |
| Maximum of Months | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 99681075.51 | 92295064.45 |
Report: SpaceGainsMonthly
For: G S1 APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6793288.89 | 85156148.39 |
| February | 0.389025E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14077285.20 | 94234612.48 |
| March | 0.418950E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16955065.24 | 86415479.22 |
| April | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34218714.78 | 21933815.19 |
| May | 0.424935E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 89578229.23 | 2715446.74 |
| June | 0.406980E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 94626188.96 | 128192.62 |
| July | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 85254341.68 | 449860.81 |
| August | 0.418950E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 99681082.02 | 681003.92 |
| September | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 88069292.35 | 329349.69 |
| October | 0.430920E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 67244026.41 | 2377411.41 |
| November | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 35780982.65 | 44717122.11 |
| December | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9449742.36 | 88793453.37 |
| Annual Sum or Average | 0.505732E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.641728E+09 | 0.427932E+09 |
| Minimum of Months | 0.389025E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6793288.89 | 128192.62 |
| Maximum of Months | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 99681082.02 | 94234612.48 |
Report: SpaceGainsMonthly
For: G S2 APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6793289.18 | 85186832.23 |
| February | 0.389025E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14077285.01 | 94342646.18 |
| March | 0.418950E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16955065.14 | 86617640.14 |
| April | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34218714.48 | 21936301.46 |
| May | 0.424935E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 89578230.17 | 2715450.00 |
| June | 0.406980E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 94626191.99 | 128193.24 |
| July | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 85254344.78 | 449863.76 |
| August | 0.418950E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 99681086.19 | 681005.42 |
| September | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 88069296.69 | 329354.19 |
| October | 0.430920E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 67244030.05 | 2377414.39 |
| November | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 35780984.36 | 44738808.00 |
| December | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9449742.95 | 88870683.02 |
| Annual Sum or Average | 0.505732E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.641728E+09 | 0.428374E+09 |
| Minimum of Months | 0.389025E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6793289.18 | 128193.24 |
| Maximum of Months | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 99681086.19 | 94342646.18 |
Report: SpaceGainsMonthly
For: M SW APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15962373.18 | 0.200995E+09 |
| February | 0.389025E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 33118214.05 | 0.220175E+09 |
| March | 0.418950E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 39878681.28 | 0.202812E+09 |
| April | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 80824917.38 | 52889682.17 |
| May | 0.424935E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.212109E+09 | 6641806.29 |
| June | 0.406980E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.224385E+09 | 338947.36 |
| July | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.202314E+09 | 1102968.96 |
| August | 0.418950E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.236518E+09 | 1660554.42 |
| September | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.208912E+09 | 830296.91 |
| October | 0.430920E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.159230E+09 | 5774620.40 |
| November | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 84519415.11 | 0.104962E+09 |
| December | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22249210.88 | 0.208340E+09 |
| Annual Sum or Average | 0.505732E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.152002E+10 | 0.100652E+10 |
| Minimum of Months | 0.389025E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15962373.18 | 338947.36 |
| Maximum of Months | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.236518E+09 | 0.220175E+09 |
Report: SpaceGainsMonthly
For: M NW APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15962374.26 | 0.194971E+09 |
| February | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 33118229.50 | 0.211166E+09 |
| March | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 39878673.62 | 0.198005E+09 |
| April | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 80824903.46 | 52878141.17 |
| May | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.212109E+09 | 6641807.58 |
| June | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.224385E+09 | 338947.84 |
| July | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.202314E+09 | 1102970.16 |
| August | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.236518E+09 | 1660553.14 |
| September | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.208912E+09 | 830293.39 |
| October | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.159230E+09 | 5774610.82 |
| November | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 84519395.04 | 0.103087E+09 |
| December | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22249205.30 | 0.201325E+09 |
| Annual Sum or Average | 0.512427E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.152002E+10 | 0.977780E+09 |
| Minimum of Months | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15962374.26 | 338947.84 |
| Maximum of Months | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.236518E+09 | 0.211166E+09 |
Report: SpaceGainsMonthly
For: M SE APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15962384.44 | 0.201358E+09 |
| February | 0.389025E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 33118245.46 | 0.220742E+09 |
| March | 0.418950E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 39878704.09 | 0.204014E+09 |
| April | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 80824947.81 | 52885267.62 |
| May | 0.424935E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.212109E+09 | 6641800.73 |
| June | 0.406980E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.224385E+09 | 338946.22 |
| July | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.202314E+09 | 1102967.34 |
| August | 0.418950E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.236518E+09 | 1660552.76 |
| September | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.208912E+09 | 830295.70 |
| October | 0.430920E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.159230E+09 | 5774618.09 |
| November | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 84519451.38 | 0.105248E+09 |
| December | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22249222.73 | 0.208533E+09 |
| Annual Sum or Average | 0.505732E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.152002E+10 | 0.100913E+10 |
| Minimum of Months | 0.389025E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15962384.44 | 338946.22 |
| Maximum of Months | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.236518E+09 | 0.220742E+09 |
Report: SpaceGainsMonthly
For: M NE APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15962382.68 | 0.196600E+09 |
| February | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 33118254.70 | 0.211765E+09 |
| March | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 39878695.92 | 0.200182E+09 |
| April | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 80824935.35 | 52869666.49 |
| May | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.212109E+09 | 6641801.09 |
| June | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.224385E+09 | 338946.47 |
| July | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.202314E+09 | 1102968.36 |
| August | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.236518E+09 | 1660551.30 |
| September | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.208912E+09 | 830292.02 |
| October | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.159230E+09 | 5774608.10 |
| November | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 84519428.51 | 0.103682E+09 |
| December | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22249216.48 | 0.201810E+09 |
| Annual Sum or Average | 0.512427E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.152002E+10 | 0.983258E+09 |
| Minimum of Months | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15962382.68 | 338946.47 |
| Maximum of Months | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.236518E+09 | 0.211765E+09 |
Report: SpaceGainsMonthly
For: M N1 APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9628108.99 | 0.120606E+09 |
| February | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19976103.43 | 0.131524E+09 |
| March | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24053828.22 | 0.122505E+09 |
| April | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 48751562.47 | 31909309.25 |
| May | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127939E+09 | 4006160.33 |
| June | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.135343E+09 | 204442.11 |
| July | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122031E+09 | 665277.96 |
| August | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.142662E+09 | 1001600.85 |
| September | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126010E+09 | 500807.50 |
| October | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 96043456.49 | 3483092.72 |
| November | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 50979987.93 | 63773099.41 |
| December | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13420168.31 | 0.125253E+09 |
| Annual Sum or Average | 0.512427E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.916838E+09 | 0.605431E+09 |
| Minimum of Months | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9628108.99 | 204442.11 |
| Maximum of Months | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.142662E+09 | 0.131524E+09 |
Report: SpaceGainsMonthly
For: M N2 APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9628109.06 | 0.120643E+09 |
| February | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19976103.60 | 0.131546E+09 |
| March | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24053828.45 | 0.122566E+09 |
| April | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 48751562.81 | 31909236.38 |
| May | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127939E+09 | 4006160.22 |
| June | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.135343E+09 | 204442.11 |
| July | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122031E+09 | 665277.93 |
| August | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.142662E+09 | 1001600.82 |
| September | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126010E+09 | 500807.50 |
| October | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 96043457.12 | 3483092.63 |
| November | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 50979988.32 | 63783526.31 |
| December | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13420168.45 | 0.125261E+09 |
| Annual Sum or Average | 0.512427E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.916838E+09 | 0.605569E+09 |
| Minimum of Months | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9628109.06 | 204442.11 |
| Maximum of Months | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.142662E+09 | 0.131546E+09 |
Report: SpaceGainsMonthly
For: M S1 APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9628110.06 | 0.122621E+09 |
| February | 0.389025E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19976096.07 | 0.135511E+09 |
| March | 0.418950E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24053832.58 | 0.124655E+09 |
| April | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 48751570.40 | 31911111.07 |
| May | 0.424935E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127939E+09 | 4006159.17 |
| June | 0.406980E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.135343E+09 | 204441.72 |
| July | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122031E+09 | 665277.07 |
| August | 0.418950E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.142662E+09 | 1001601.52 |
| September | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126010E+09 | 500809.79 |
| October | 0.430920E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 96043478.78 | 3483098.69 |
| November | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 50980003.05 | 64348079.36 |
| December | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13420172.88 | 0.127523E+09 |
| Annual Sum or Average | 0.505732E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.916839E+09 | 0.616430E+09 |
| Minimum of Months | 0.389025E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9628110.06 | 204441.72 |
| Maximum of Months | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.142662E+09 | 0.135511E+09 |
Report: SpaceGainsMonthly
For: M S2 APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9628110.23 | 0.122621E+09 |
| February | 0.389025E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19976096.41 | 0.135517E+09 |
| March | 0.418950E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24053832.94 | 0.124664E+09 |
| April | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 48751570.83 | 31911056.38 |
| May | 0.424935E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127939E+09 | 4006159.06 |
| June | 0.406980E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.135343E+09 | 204441.71 |
| July | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122031E+09 | 665277.04 |
| August | 0.418950E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.142662E+09 | 1001601.48 |
| September | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126010E+09 | 500809.78 |
| October | 0.430920E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 96043479.49 | 3483098.60 |
| November | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 50980003.56 | 64350402.85 |
| December | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13420173.05 | 0.127519E+09 |
| Annual Sum or Average | 0.505732E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.916839E+09 | 0.616445E+09 |
| Minimum of Months | 0.389025E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9628110.23 | 204441.71 |
| Maximum of Months | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.142662E+09 | 0.135517E+09 |
Report: SpaceGainsMonthly
For: T SW APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20529127.24 | 0.244223E+09 |
| February | 0.389025E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 42706252.31 | 0.270159E+09 |
| March | 0.418950E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 51389796.44 | 0.248235E+09 |
| April | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105064E+09 | 70027664.72 |
| May | 0.424935E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.277105E+09 | 9242550.76 |
| June | 0.406980E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.294000E+09 | 537295.74 |
| July | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.265488E+09 | 1541417.64 |
| August | 0.418950E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.310288E+09 | 2297526.13 |
| September | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.273928E+09 | 1219791.30 |
| October | 0.430920E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.208036E+09 | 7931518.35 |
| November | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109877E+09 | 0.126737E+09 |
| December | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28733191.76 | 0.255315E+09 |
| Annual Sum or Average | 0.505732E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.198714E+10 | 0.123747E+10 |
| Minimum of Months | 0.389025E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 20529127.24 | 537295.74 |
| Maximum of Months | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.310288E+09 | 0.270159E+09 |
Report: SpaceGainsMonthly
For: T NW APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20566127.52 | 0.227359E+09 |
| February | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 42706271.26 | 0.255659E+09 |
| March | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 51389773.67 | 0.239089E+09 |
| April | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105064E+09 | 69904175.78 |
| May | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.277105E+09 | 9242553.31 |
| June | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.294000E+09 | 537296.55 |
| July | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.265488E+09 | 1541419.11 |
| August | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.310288E+09 | 2297523.90 |
| September | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.273928E+09 | 1219789.37 |
| October | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.208036E+09 | 7931508.66 |
| November | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109877E+09 | 0.121214E+09 |
| December | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28733177.35 | 0.237073E+09 |
| Annual Sum or Average | 0.512427E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.198718E+10 | 0.117307E+10 |
| Minimum of Months | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 20566127.52 | 537296.55 |
| Maximum of Months | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.310288E+09 | 0.255659E+09 |
Report: SpaceGainsMonthly
For: T SE APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20529151.81 | 0.246739E+09 |
| February | 0.389025E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 42706316.00 | 0.271197E+09 |
| March | 0.418950E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 51389847.78 | 0.251825E+09 |
| April | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105064E+09 | 70314890.61 |
| May | 0.424935E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.277105E+09 | 9242541.33 |
| June | 0.406980E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.294000E+09 | 537293.18 |
| July | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.265488E+09 | 1541414.49 |
| August | 0.418950E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.310288E+09 | 2297523.58 |
| September | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.273928E+09 | 1219788.41 |
| October | 0.430920E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.208036E+09 | 7931516.06 |
| November | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109877E+09 | 0.127733E+09 |
| December | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28733218.04 | 0.256621E+09 |
| Annual Sum or Average | 0.505732E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.198714E+10 | 0.124720E+10 |
| Minimum of Months | 0.389025E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 20529151.81 | 537293.18 |
| Maximum of Months | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.310288E+09 | 0.271197E+09 |
Report: SpaceGainsMonthly
For: T NE APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20529142.11 | 0.231181E+09 |
| February | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 42706313.08 | 0.256602E+09 |
| March | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 51389819.73 | 0.242143E+09 |
| April | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105064E+09 | 70207861.77 |
| May | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.277105E+09 | 9242543.18 |
| June | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.294000E+09 | 537293.78 |
| July | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.265488E+09 | 1541415.83 |
| August | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.310288E+09 | 2297521.31 |
| September | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.273928E+09 | 1219786.35 |
| October | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.208036E+09 | 7931506.18 |
| November | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109877E+09 | 0.122914E+09 |
| December | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28733199.31 | 0.237419E+09 |
| Annual Sum or Average | 0.512427E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.198714E+10 | 0.118324E+10 |
| Minimum of Months | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 20529142.11 | 537293.78 |
| Maximum of Months | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.310288E+09 | 0.256602E+09 |
Report: SpaceGainsMonthly
For: T N1 APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12387125.84 | 0.143065E+09 |
| February | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 25759378.47 | 0.158521E+09 |
| March | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30997041.66 | 0.147479E+09 |
| April | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 63371957.21 | 42623563.86 |
| May | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.167143E+09 | 5574864.62 |
| June | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.177333E+09 | 324080.42 |
| July | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160136E+09 | 929739.44 |
| August | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.187158E+09 | 1385806.31 |
| September | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.165226E+09 | 735745.68 |
| October | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125482E+09 | 4784083.26 |
| November | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 66274816.16 | 76735326.37 |
| December | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17331141.34 | 0.147606E+09 |
| Annual Sum or Average | 0.512427E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119860E+10 | 0.729764E+09 |
| Minimum of Months | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12387125.84 | 324080.42 |
| Maximum of Months | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.187158E+09 | 0.158521E+09 |
Report: SpaceGainsMonthly
For: T N2 APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12385830.31 | 0.143228E+09 |
| February | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 25759380.54 | 0.158531E+09 |
| March | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30997045.35 | 0.147605E+09 |
| April | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 63371962.27 | 42625405.68 |
| May | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.167143E+09 | 5574863.44 |
| June | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.177333E+09 | 324080.16 |
| July | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160136E+09 | 929739.17 |
| August | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.187158E+09 | 1385806.02 |
| September | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.165226E+09 | 735745.32 |
| October | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125482E+09 | 4784082.54 |
| November | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 66274821.54 | 76795606.38 |
| December | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17331143.27 | 0.147621E+09 |
| Annual Sum or Average | 0.512427E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119860E+10 | 0.730140E+09 |
| Minimum of Months | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12385830.31 | 324080.16 |
| Maximum of Months | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.187158E+09 | 0.158531E+09 |
Report: SpaceGainsMonthly
For: T S1 APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12382665.82 | 0.153476E+09 |
| February | 0.389025E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 25759367.45 | 0.168636E+09 |
| March | 0.418950E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30997055.56 | 0.154604E+09 |
| April | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 63371978.49 | 42680014.44 |
| May | 0.424935E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.167143E+09 | 5574862.46 |
| June | 0.406980E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.177333E+09 | 324079.78 |
| July | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160136E+09 | 929738.39 |
| August | 0.418950E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.187158E+09 | 1385807.43 |
| September | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.165226E+09 | 735746.76 |
| October | 0.430920E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125482E+09 | 4784088.76 |
| November | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 66274846.70 | 80079323.13 |
| December | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17331151.93 | 0.159347E+09 |
| Annual Sum or Average | 0.505732E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119860E+10 | 0.772557E+09 |
| Minimum of Months | 0.389025E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12382665.82 | 324079.78 |
| Maximum of Months | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.187158E+09 | 0.168636E+09 |
Report: SpaceGainsMonthly
For: T S2 APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12382666.40 | 0.153511E+09 |
| February | 0.389025E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 25759368.74 | 0.168640E+09 |
| March | 0.418950E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30997056.81 | 0.154692E+09 |
| April | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 63371980.11 | 42681358.20 |
| May | 0.424935E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.167143E+09 | 5574862.17 |
| June | 0.406980E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.177333E+09 | 324079.73 |
| July | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160136E+09 | 929738.28 |
| August | 0.418950E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.187158E+09 | 1385807.35 |
| September | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.165226E+09 | 735746.66 |
| October | 0.430920E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125482E+09 | 4784088.54 |
| November | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 66274848.43 | 80102663.07 |
| December | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17331152.58 | 0.159363E+09 |
| Annual Sum or Average | 0.505732E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119860E+10 | 0.772724E+09 |
| Minimum of Months | 0.389025E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12382666.40 | 324079.73 |
| Maximum of Months | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.187158E+09 | 0.168640E+09 |
Report: SpaceGainsMonthly
For: T CORRIDOR
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.727675E+09 | 0.992689E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 651467.26 | 54185368.95 |
| February | 0.657255E+09 | 0.896622E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1000833.71 | 65279863.25 |
| March | 0.727675E+09 | 0.992689E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1120134.79 | 66818036.70 |
| April | 0.704201E+09 | 0.960667E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4445534.30 | 29726985.48 |
| May | 0.727675E+09 | 0.992689E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17194361.21 | 10878301.24 |
| June | 0.704201E+09 | 0.960667E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21809950.82 | 2874152.43 |
| July | 0.727675E+09 | 0.992689E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22569979.72 | 2296955.71 |
| August | 0.727675E+09 | 0.992689E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25878865.07 | 2317059.08 |
| September | 0.704201E+09 | 0.960667E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22176180.84 | 3277227.34 |
| October | 0.727675E+09 | 0.992689E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13063821.04 | 6874955.15 |
| November | 0.704201E+09 | 0.960667E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3391972.47 | 32311451.45 |
| December | 0.727675E+09 | 0.992689E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 715511.06 | 56858784.57 |
| Annual Sum or Average | 0.856778E+10 | 0.116881E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.134019E+09 | 0.333699E+09 |
| Minimum of Months | 0.657255E+09 | 0.896622E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 651467.26 | 2296955.71 |
| Maximum of Months | 0.727675E+09 | 0.992689E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25878865.07 | 66818036.70 |
Report: SpaceGainsMonthly
For: G CORRIDOR
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.727675E+09 | 0.992689E+09 | 0.299778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4850416.16 | 0.122075E+10 |
| February | 0.657255E+09 | 0.896622E+09 | 0.270767E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9698595.78 | 0.829543E+09 |
| March | 0.727675E+09 | 0.992689E+09 | 0.299778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12929962.12 | 0.826041E+09 |
| April | 0.704201E+09 | 0.960667E+09 | 0.290107E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 71698624.61 | 0.425362E+09 |
| May | 0.727675E+09 | 0.992689E+09 | 0.299778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.200255E+09 | 0.166909E+09 |
| June | 0.704201E+09 | 0.960667E+09 | 0.290107E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.268059E+09 | 95928036.29 |
| July | 0.727675E+09 | 0.992689E+09 | 0.299778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.395172E+09 | 81589063.56 |
| August | 0.727675E+09 | 0.992689E+09 | 0.299778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.332473E+09 | 86741329.05 |
| September | 0.704201E+09 | 0.960667E+09 | 0.290107E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.284415E+09 | 0.135980E+09 |
| October | 0.727675E+09 | 0.992689E+09 | 0.299778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.151370E+09 | 0.199790E+09 |
| November | 0.704201E+09 | 0.960667E+09 | 0.290107E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 32050063.59 | 0.524834E+09 |
| December | 0.727675E+09 | 0.992689E+09 | 0.299778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5236303.29 | 0.105695E+10 |
| Annual Sum or Average | 0.856778E+10 | 0.116881E+11 | 0.352964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.176821E+10 | 0.565041E+10 |
| Minimum of Months | 0.657255E+09 | 0.896622E+09 | 0.270767E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4850416.16 | 81589063.56 |
| Maximum of Months | 0.727675E+09 | 0.992689E+09 | 0.299778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.395172E+09 | 0.122075E+10 |
Report: SpaceGainsMonthly
For: M CORRIDOR
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.727675E+09 | 0.992689E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 492785.86 | 47181836.88 |
| February | 0.657255E+09 | 0.896622E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1050705.33 | 56069849.09 |
| March | 0.727675E+09 | 0.992689E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1306546.88 | 56271114.62 |
| April | 0.704201E+09 | 0.960667E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4467844.95 | 22976344.12 |
| May | 0.727675E+09 | 0.992689E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16028493.81 | 7781212.93 |
| June | 0.704201E+09 | 0.960667E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19832190.92 | 1948289.57 |
| July | 0.727675E+09 | 0.992689E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20112281.42 | 1575419.60 |
| August | 0.727675E+09 | 0.992689E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22985273.62 | 1679982.42 |
| September | 0.704201E+09 | 0.960667E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20005769.71 | 2496698.04 |
| October | 0.727675E+09 | 0.992689E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11888407.70 | 5365748.48 |
| November | 0.704201E+09 | 0.960667E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3719386.67 | 28133531.57 |
| December | 0.727675E+09 | 0.992689E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 748268.95 | 49294855.49 |
| Annual Sum or Average | 0.856778E+10 | 0.116881E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122638E+09 | 0.280775E+09 |
| Minimum of Months | 0.657255E+09 | 0.896622E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 492785.86 | 1575419.60 |
| Maximum of Months | 0.727675E+09 | 0.992689E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22985273.62 | 56271114.62 |
Report: PeakSpaceGainsMonthly
For: G SW APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 127.12 | 07-JAN-13:00 | 350.48 | 24-JAN-09:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 153.39 | 02-FEB-14:00 | 445.15 | 04-FEB-05:00 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 173.55 | 13-MAR-17:00 | 427.91 | 16-MAR-02:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 194.68 | 15-APR-17:00 | 130.38 | 19-APR-03:00 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 335.46 | 22-MAY-15:00 | 79.31 | 10-MAY-15:00 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 236.70 | 16-JUN-13:00 | 14.33 | 05-JUN-14:10 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 258.30 | 30-JUL-16:00 | 21.59 | 02-JUL-16:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 239.45 | 22-AUG-13:00 | 36.74 | 12-AUG-09:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 223.29 | 20-SEP-14:00 | 18.27 | 05-SEP-06:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 238.22 | 03-OCT-13:00 | 46.92 | 31-OCT-06:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 136.21 | 22-NOV-13:00 | 398.83 | 11-NOV-09:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 153.06 | 10-DEC-15:00 | 416.63 | 15-DEC-06:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 127.12 | 14.33 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 335.46 | 445.15 |
Report: PeakSpaceGainsMonthly
For: G NW APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 127.12 | 07-JAN-13:00 | 333.07 | 24-JAN-09:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 153.39 | 02-FEB-14:00 | 431.90 | 04-FEB-05:00 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 173.55 | 13-MAR-17:00 | 415.45 | 16-MAR-02:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 194.68 | 15-APR-17:00 | 130.02 | 18-APR-24:00 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 335.46 | 22-MAY-15:00 | 79.31 | 10-MAY-15:00 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 236.70 | 16-JUN-13:00 | 14.33 | 05-JUN-14:10 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 258.30 | 30-JUL-16:00 | 21.59 | 02-JUL-16:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 239.45 | 22-AUG-13:00 | 36.74 | 12-AUG-09:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 223.29 | 20-SEP-14:00 | 18.27 | 05-SEP-06:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 238.22 | 03-OCT-13:00 | 46.92 | 31-OCT-06:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 136.21 | 22-NOV-13:00 | 393.58 | 11-NOV-09:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 153.06 | 10-DEC-15:00 | 402.21 | 15-DEC-06:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 127.12 | 14.33 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 335.46 | 431.90 |
Report: PeakSpaceGainsMonthly
For: OFFICE
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 451.21 | 03-JAN-08:09 | 582.92 | 03-JAN-08:09 | 588.62 | 03-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 97.12 | 06-JAN-14:00 | 403.26 | 24-JAN-09:00 |
| February | 451.21 | 01-FEB-08:09 | 582.92 | 01-FEB-08:09 | 588.62 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 153.39 | 02-FEB-14:00 | 465.13 | 03-FEB-09:00 |
| March | 451.21 | 01-MAR-08:09 | 582.92 | 01-MAR-08:09 | 588.62 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 127.31 | 13-MAR-16:00 | 456.46 | 16-MAR-02:00 |
| April | 451.21 | 03-APR-07:10 | 582.92 | 03-APR-07:10 | 588.62 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 160.62 | 17-APR-15:00 | 167.15 | 18-APR-07:00 |
| May | 451.21 | 01-MAY-07:10 | 582.92 | 01-MAY-07:10 | 588.62 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 335.38 | 22-MAY-15:00 | 166.38 | 07-MAY-19:00 |
| June | 451.21 | 01-JUN-07:10 | 582.92 | 01-JUN-07:10 | 588.62 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 236.70 | 16-JUN-13:00 | 154.30 | 18-JUN-20:00 |
| July | 451.21 | 03-JUL-07:10 | 582.92 | 03-JUL-07:10 | 588.62 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 234.17 | 27-JUL-16:00 | 124.16 | 02-JUL-15:30 |
| August | 451.21 | 01-AUG-07:10 | 582.92 | 01-AUG-07:10 | 588.62 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 239.42 | 22-AUG-13:00 | 180.17 | 14-AUG-03:00 |
| September | 451.21 | 01-SEP-07:10 | 582.92 | 01-SEP-07:10 | 588.62 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 223.26 | 20-SEP-14:00 | 131.78 | 02-SEP-12:00 |
| October | 451.21 | 02-OCT-07:10 | 582.92 | 02-OCT-07:10 | 588.62 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 238.18 | 03-OCT-13:00 | 153.09 | 16-OCT-05:00 |
| November | 451.21 | 01-NOV-07:10 | 582.92 | 01-NOV-07:10 | 588.62 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 136.15 | 22-NOV-13:00 | 478.40 | 11-NOV-09:00 |
| December | 451.21 | 01-DEC-08:09 | 582.92 | 01-DEC-08:09 | 588.62 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 69.99 | 07-DEC-11:00 | 439.89 | 15-DEC-06:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 451.21 | 582.92 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 69.99 | 124.16 | |||||
| Maximum of Months | 451.21 | 582.92 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 335.38 | 478.40 |
Report: PeakSpaceGainsMonthly
For: G NE APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 127.12 | 07-JAN-13:00 | 340.28 | 24-JAN-09:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 153.39 | 02-FEB-14:00 | 431.27 | 04-FEB-05:00 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 173.55 | 13-MAR-17:00 | 414.08 | 16-MAR-02:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 194.68 | 15-APR-17:00 | 130.02 | 18-APR-24:00 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 335.46 | 22-MAY-15:00 | 79.31 | 10-MAY-15:00 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 236.70 | 16-JUN-13:00 | 14.33 | 05-JUN-14:10 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 258.30 | 30-JUL-16:00 | 21.59 | 02-JUL-16:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 239.45 | 22-AUG-13:00 | 36.74 | 12-AUG-09:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 223.29 | 20-SEP-14:00 | 18.27 | 05-SEP-06:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 238.22 | 03-OCT-13:00 | 46.92 | 31-OCT-06:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 136.21 | 22-NOV-13:00 | 398.83 | 11-NOV-09:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 153.06 | 10-DEC-15:00 | 401.12 | 15-DEC-06:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 127.12 | 14.33 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 335.46 | 431.27 |
Report: PeakSpaceGainsMonthly
For: G N1 APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 76.68 | 07-JAN-13:00 | 209.11 | 24-JAN-09:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 92.52 | 02-FEB-14:00 | 274.09 | 04-FEB-05:00 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 104.68 | 13-MAR-17:00 | 260.26 | 16-MAR-02:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 117.42 | 15-APR-17:00 | 78.60 | 19-APR-03:00 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 202.34 | 22-MAY-15:00 | 47.84 | 10-MAY-15:00 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 142.77 | 16-JUN-13:00 | 8.64 | 05-JUN-14:10 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 155.80 | 30-JUL-16:00 | 13.02 | 02-JUL-16:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 144.43 | 22-AUG-13:00 | 22.16 | 12-AUG-09:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 134.69 | 20-SEP-14:00 | 11.02 | 05-SEP-06:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 143.69 | 03-OCT-13:00 | 28.30 | 31-OCT-06:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 82.16 | 22-NOV-13:00 | 240.56 | 11-NOV-09:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 92.32 | 10-DEC-15:00 | 252.45 | 15-DEC-06:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 76.68 | 8.64 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 202.34 | 274.09 |
Report: PeakSpaceGainsMonthly
For: G N2 APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 76.68 | 07-JAN-13:00 | 209.14 | 24-JAN-09:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 92.52 | 02-FEB-14:00 | 274.10 | 04-FEB-05:00 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 104.68 | 13-MAR-17:00 | 260.22 | 16-MAR-02:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 117.42 | 15-APR-17:00 | 78.60 | 19-APR-03:00 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 202.34 | 22-MAY-15:00 | 47.84 | 10-MAY-15:00 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 142.77 | 16-JUN-13:00 | 8.64 | 05-JUN-14:10 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 155.80 | 30-JUL-16:00 | 13.02 | 02-JUL-16:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 144.43 | 22-AUG-13:00 | 22.16 | 12-AUG-09:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 134.69 | 20-SEP-14:00 | 11.02 | 05-SEP-06:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 143.69 | 03-OCT-13:00 | 28.30 | 31-OCT-06:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 82.16 | 22-NOV-13:00 | 240.56 | 11-NOV-09:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 92.32 | 10-DEC-15:00 | 252.39 | 15-DEC-06:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 76.68 | 8.64 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 202.34 | 274.10 |
Report: PeakSpaceGainsMonthly
For: G S1 APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 76.68 | 07-JAN-13:00 | 217.68 | 24-JAN-09:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 92.52 | 02-FEB-14:00 | 281.85 | 04-FEB-05:00 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 104.68 | 13-MAR-17:00 | 267.95 | 16-MAR-02:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 117.42 | 15-APR-17:00 | 78.60 | 19-APR-03:00 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 202.34 | 22-MAY-15:00 | 47.84 | 10-MAY-15:00 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 142.77 | 16-JUN-13:00 | 8.64 | 05-JUN-14:10 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 155.80 | 30-JUL-16:00 | 13.02 | 02-JUL-16:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 144.43 | 22-AUG-13:00 | 22.16 | 12-AUG-09:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 134.69 | 20-SEP-14:00 | 11.02 | 05-SEP-06:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 143.69 | 03-OCT-13:00 | 28.30 | 31-OCT-06:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 82.16 | 22-NOV-13:00 | 240.56 | 11-NOV-09:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 92.32 | 10-DEC-15:00 | 261.40 | 15-DEC-06:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 76.68 | 8.64 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 202.34 | 281.85 |
Report: PeakSpaceGainsMonthly
For: G S2 APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 76.68 | 07-JAN-13:00 | 217.68 | 24-JAN-09:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 92.52 | 02-FEB-14:00 | 282.94 | 04-FEB-05:00 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 104.68 | 13-MAR-17:00 | 269.46 | 16-MAR-02:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 117.42 | 15-APR-17:00 | 78.60 | 19-APR-03:00 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 202.34 | 22-MAY-15:00 | 47.84 | 10-MAY-15:00 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 142.77 | 16-JUN-13:00 | 8.64 | 05-JUN-14:10 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 155.80 | 30-JUL-16:00 | 13.02 | 02-JUL-16:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 144.43 | 22-AUG-13:00 | 22.16 | 12-AUG-09:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 134.69 | 20-SEP-14:00 | 11.02 | 05-SEP-06:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 143.69 | 03-OCT-13:00 | 28.30 | 31-OCT-06:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 82.16 | 22-NOV-13:00 | 240.56 | 11-NOV-09:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 92.32 | 10-DEC-15:00 | 262.54 | 15-DEC-06:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 76.68 | 8.64 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 202.34 | 282.94 |
Report: PeakSpaceGainsMonthly
For: M SW APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 181.84 | 07-JAN-13:00 | 493.13 | 24-JAN-09:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 219.42 | 02-FEB-14:00 | 619.04 | 04-FEB-05:00 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 248.40 | 13-MAR-17:00 | 604.93 | 16-MAR-02:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 279.04 | 15-APR-17:00 | 187.32 | 18-APR-24:00 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 480.64 | 22-MAY-15:00 | 114.96 | 10-MAY-15:00 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 339.03 | 16-JUN-13:00 | 21.11 | 05-JUN-14:10 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 369.97 | 30-JUL-16:00 | 31.54 | 02-JUL-16:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 343.33 | 22-AUG-13:00 | 53.38 | 12-AUG-09:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 320.11 | 20-SEP-14:00 | 26.55 | 05-SEP-06:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 341.46 | 03-OCT-13:00 | 68.00 | 31-OCT-06:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 194.72 | 22-NOV-13:00 | 565.02 | 11-NOV-09:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 219.07 | 10-DEC-15:00 | 573.69 | 15-DEC-06:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 181.84 | 21.11 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 480.64 | 619.04 |
Report: PeakSpaceGainsMonthly
For: M NW APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 181.84 | 07-JAN-13:00 | 468.15 | 24-JAN-09:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 219.42 | 02-FEB-14:00 | 603.68 | 04-FEB-05:00 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 248.40 | 13-MAR-17:00 | 586.25 | 16-MAR-02:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 279.04 | 15-APR-17:00 | 187.32 | 18-APR-24:00 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 480.64 | 22-MAY-15:00 | 114.96 | 10-MAY-15:00 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 339.03 | 16-JUN-13:00 | 21.11 | 05-JUN-14:10 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 369.97 | 30-JUL-16:00 | 31.54 | 02-JUL-16:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 343.33 | 22-AUG-13:00 | 53.38 | 12-AUG-09:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 320.11 | 20-SEP-14:00 | 26.55 | 05-SEP-06:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 341.46 | 03-OCT-13:00 | 68.00 | 31-OCT-06:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 194.72 | 22-NOV-13:00 | 541.32 | 11-NOV-09:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 219.07 | 10-DEC-15:00 | 555.21 | 15-DEC-06:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 181.84 | 21.11 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 480.64 | 603.68 |
Report: PeakSpaceGainsMonthly
For: M SE APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 181.84 | 07-JAN-13:00 | 508.39 | 24-JAN-09:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 219.42 | 02-FEB-14:00 | 618.03 | 04-FEB-05:00 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 248.40 | 13-MAR-17:00 | 602.74 | 16-MAR-02:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 279.04 | 15-APR-17:00 | 187.32 | 18-APR-24:00 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 480.64 | 22-MAY-15:00 | 114.96 | 10-MAY-15:00 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 339.03 | 16-JUN-13:00 | 21.11 | 05-JUN-14:10 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 369.97 | 30-JUL-16:00 | 31.54 | 02-JUL-16:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 343.33 | 22-AUG-13:00 | 53.38 | 12-AUG-09:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 320.11 | 20-SEP-14:00 | 26.55 | 05-SEP-06:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 341.46 | 03-OCT-13:00 | 68.00 | 31-OCT-06:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 194.72 | 22-NOV-13:00 | 574.32 | 11-NOV-09:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 219.07 | 10-DEC-15:00 | 572.63 | 15-DEC-06:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 181.84 | 21.11 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 480.64 | 618.03 |
Report: PeakSpaceGainsMonthly
For: M NE APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 181.84 | 07-JAN-13:00 | 482.80 | 24-JAN-09:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 219.42 | 02-FEB-14:00 | 603.68 | 04-FEB-05:00 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 248.40 | 13-MAR-17:00 | 584.02 | 16-MAR-02:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 279.04 | 15-APR-17:00 | 187.32 | 18-APR-24:00 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 480.64 | 22-MAY-15:00 | 114.96 | 10-MAY-15:00 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 339.03 | 16-JUN-13:00 | 21.11 | 05-JUN-14:10 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 369.97 | 30-JUL-16:00 | 31.54 | 02-JUL-16:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 343.33 | 22-AUG-13:00 | 53.38 | 12-AUG-09:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 320.11 | 20-SEP-14:00 | 26.55 | 05-SEP-06:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 341.46 | 03-OCT-13:00 | 68.00 | 31-OCT-06:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 194.72 | 22-NOV-13:00 | 555.61 | 11-NOV-09:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 219.07 | 10-DEC-15:00 | 553.62 | 15-DEC-06:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 181.84 | 21.11 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 480.64 | 603.68 |
Report: PeakSpaceGainsMonthly
For: M N1 APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 109.68 | 07-JAN-13:00 | 298.44 | 24-JAN-09:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 132.35 | 02-FEB-14:00 | 385.10 | 04-FEB-05:00 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 149.83 | 13-MAR-17:00 | 370.42 | 16-MAR-02:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 168.31 | 15-APR-17:00 | 113.20 | 19-APR-03:00 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 289.91 | 22-MAY-15:00 | 69.34 | 10-MAY-15:00 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 204.49 | 16-JUN-13:00 | 12.73 | 05-JUN-14:10 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 223.16 | 30-JUL-16:00 | 19.03 | 02-JUL-16:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 207.09 | 22-AUG-13:00 | 32.20 | 12-AUG-09:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 193.08 | 20-SEP-14:00 | 16.01 | 05-SEP-06:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 205.96 | 03-OCT-13:00 | 41.02 | 31-OCT-06:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 117.45 | 22-NOV-13:00 | 343.32 | 11-NOV-09:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 132.14 | 10-DEC-15:00 | 355.09 | 15-DEC-06:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 109.68 | 12.73 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 289.91 | 385.10 |
Report: PeakSpaceGainsMonthly
For: M N2 APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 109.68 | 07-JAN-13:00 | 298.53 | 24-JAN-09:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 132.35 | 02-FEB-14:00 | 385.05 | 04-FEB-05:00 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 149.83 | 13-MAR-17:00 | 370.43 | 16-MAR-02:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 168.31 | 15-APR-17:00 | 113.20 | 19-APR-03:00 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 289.91 | 22-MAY-15:00 | 69.34 | 10-MAY-15:00 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 204.49 | 16-JUN-13:00 | 12.73 | 05-JUN-14:10 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 223.16 | 30-JUL-16:00 | 19.03 | 02-JUL-16:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 207.09 | 22-AUG-13:00 | 32.20 | 12-AUG-09:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 193.08 | 20-SEP-14:00 | 16.01 | 05-SEP-06:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 205.96 | 03-OCT-13:00 | 41.02 | 31-OCT-06:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 117.45 | 22-NOV-13:00 | 343.51 | 11-NOV-09:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 132.14 | 10-DEC-15:00 | 354.99 | 15-DEC-06:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 109.68 | 12.73 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 289.91 | 385.05 |
Report: PeakSpaceGainsMonthly
For: M S1 APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 109.68 | 07-JAN-13:00 | 313.33 | 24-JAN-09:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 132.35 | 02-FEB-14:00 | 397.77 | 04-FEB-05:00 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 149.83 | 13-MAR-17:00 | 381.78 | 16-MAR-02:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 168.31 | 15-APR-17:00 | 113.20 | 19-APR-03:00 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 289.91 | 22-MAY-15:00 | 69.34 | 10-MAY-15:00 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 204.49 | 16-JUN-13:00 | 12.73 | 05-JUN-14:10 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 223.16 | 30-JUL-16:00 | 19.03 | 02-JUL-16:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 207.09 | 22-AUG-13:00 | 32.20 | 12-AUG-09:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 193.08 | 20-SEP-14:00 | 16.01 | 05-SEP-06:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 205.96 | 03-OCT-13:00 | 41.02 | 31-OCT-06:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 117.45 | 22-NOV-13:00 | 346.42 | 11-NOV-09:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 132.14 | 10-DEC-15:00 | 365.82 | 15-DEC-06:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 109.68 | 12.73 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 289.91 | 397.77 |
Report: PeakSpaceGainsMonthly
For: M S2 APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 109.68 | 07-JAN-13:00 | 313.33 | 24-JAN-09:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 132.35 | 02-FEB-14:00 | 397.74 | 04-FEB-05:00 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 149.83 | 13-MAR-17:00 | 381.71 | 16-MAR-02:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 168.31 | 15-APR-17:00 | 113.20 | 19-APR-03:00 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 289.91 | 22-MAY-15:00 | 69.34 | 10-MAY-15:00 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 204.49 | 16-JUN-13:00 | 12.73 | 05-JUN-14:10 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 223.16 | 30-JUL-16:00 | 19.03 | 02-JUL-16:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 207.09 | 22-AUG-13:00 | 32.20 | 12-AUG-09:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 193.08 | 20-SEP-14:00 | 16.01 | 05-SEP-06:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 205.96 | 03-OCT-13:00 | 41.02 | 31-OCT-06:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 117.45 | 22-NOV-13:00 | 346.42 | 11-NOV-09:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 132.14 | 10-DEC-15:00 | 365.76 | 15-DEC-06:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 109.68 | 12.73 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 289.91 | 397.74 |
Report: PeakSpaceGainsMonthly
For: T SW APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 238.31 | 07-JAN-13:00 | 529.19 | 24-JAN-09:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 287.55 | 02-FEB-14:00 | 800.66 | 04-FEB-05:00 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 325.91 | 13-MAR-17:00 | 724.87 | 16-MAR-02:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 367.21 | 15-APR-17:00 | 233.94 | 18-APR-24:00 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 631.95 | 22-MAY-15:00 | 154.66 | 10-MAY-15:00 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 445.49 | 16-JUN-13:00 | 29.30 | 05-JUN-14:10 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 486.15 | 30-JUL-16:00 | 43.08 | 02-JUL-16:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 452.10 | 22-AUG-13:00 | 72.29 | 14-AUG-03:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 421.39 | 20-SEP-14:00 | 35.88 | 05-SEP-06:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 449.35 | 03-OCT-13:00 | 91.49 | 31-OCT-06:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 254.87 | 22-NOV-13:00 | 632.57 | 11-NOV-09:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 287.43 | 10-DEC-15:00 | 703.48 | 15-DEC-06:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 238.31 | 29.30 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 631.95 | 800.66 |
Report: PeakSpaceGainsMonthly
For: T NW APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 238.31 | 07-JAN-13:00 | 527.60 | 24-JAN-09:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 287.55 | 02-FEB-14:00 | 800.66 | 04-FEB-05:00 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 325.91 | 13-MAR-17:00 | 724.87 | 16-MAR-02:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 367.21 | 15-APR-17:00 | 231.80 | 18-APR-24:00 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 631.95 | 22-MAY-15:00 | 154.66 | 10-MAY-15:00 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 445.49 | 16-JUN-13:00 | 29.30 | 05-JUN-14:10 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 486.15 | 30-JUL-16:00 | 43.08 | 02-JUL-16:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 452.10 | 22-AUG-13:00 | 72.29 | 14-AUG-03:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 421.39 | 20-SEP-14:00 | 35.88 | 05-SEP-06:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 449.35 | 03-OCT-13:00 | 91.49 | 31-OCT-06:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 254.87 | 22-NOV-13:00 | 590.57 | 11-NOV-09:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 287.43 | 10-DEC-15:00 | 703.48 | 15-DEC-06:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 238.31 | 29.30 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 631.95 | 800.66 |
Report: PeakSpaceGainsMonthly
For: T SE APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 238.31 | 07-JAN-13:00 | 563.17 | 24-JAN-09:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 287.55 | 02-FEB-14:00 | 800.66 | 04-FEB-05:00 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 325.91 | 13-MAR-17:00 | 724.87 | 16-MAR-02:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 367.21 | 15-APR-17:00 | 247.82 | 18-APR-08:00 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 631.95 | 22-MAY-15:00 | 154.66 | 10-MAY-15:00 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 445.49 | 16-JUN-13:00 | 29.30 | 05-JUN-14:10 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 486.15 | 30-JUL-16:00 | 43.08 | 02-JUL-16:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 452.10 | 22-AUG-13:00 | 72.29 | 14-AUG-03:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 421.39 | 20-SEP-14:00 | 35.88 | 05-SEP-06:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 449.35 | 03-OCT-13:00 | 91.49 | 31-OCT-06:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 254.87 | 22-NOV-13:00 | 663.25 | 11-NOV-09:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 287.43 | 10-DEC-15:00 | 703.48 | 15-DEC-06:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 238.31 | 29.30 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 631.95 | 800.66 |
Report: PeakSpaceGainsMonthly
For: T NE APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 238.31 | 07-JAN-13:00 | 527.10 | 24-JAN-09:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 287.55 | 02-FEB-14:00 | 800.66 | 04-FEB-05:00 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 325.91 | 13-MAR-17:00 | 724.87 | 16-MAR-02:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 367.21 | 15-APR-17:00 | 247.87 | 18-APR-08:00 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 631.95 | 22-MAY-15:00 | 154.66 | 10-MAY-15:00 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 445.49 | 16-JUN-13:00 | 29.30 | 05-JUN-14:10 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 486.15 | 30-JUL-16:00 | 43.08 | 02-JUL-16:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 452.10 | 22-AUG-13:00 | 72.29 | 14-AUG-03:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 421.39 | 20-SEP-14:00 | 35.88 | 05-SEP-06:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 449.35 | 03-OCT-13:00 | 91.49 | 31-OCT-06:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 254.87 | 22-NOV-13:00 | 621.40 | 11-NOV-09:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 287.43 | 10-DEC-15:00 | 703.48 | 15-DEC-06:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 238.31 | 29.30 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 631.95 | 800.66 |
Report: PeakSpaceGainsMonthly
For: T N1 APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 143.75 | 07-JAN-13:00 | 326.82 | 24-JAN-09:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 173.44 | 02-FEB-14:00 | 482.94 | 04-FEB-05:00 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 196.58 | 13-MAR-17:00 | 437.22 | 16-MAR-02:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 221.49 | 15-APR-17:00 | 145.10 | 18-APR-24:00 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 381.18 | 22-MAY-15:00 | 93.29 | 10-MAY-15:00 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 268.71 | 16-JUN-13:00 | 17.67 | 05-JUN-14:10 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 293.24 | 30-JUL-16:00 | 25.98 | 02-JUL-16:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 272.70 | 22-AUG-13:00 | 43.60 | 14-AUG-03:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 254.17 | 20-SEP-14:00 | 21.64 | 05-SEP-06:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 271.04 | 03-OCT-13:00 | 55.18 | 31-OCT-06:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 153.73 | 22-NOV-13:00 | 395.53 | 11-NOV-09:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 173.37 | 10-DEC-15:00 | 424.32 | 15-DEC-06:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 143.75 | 17.67 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 381.18 | 482.94 |
Report: PeakSpaceGainsMonthly
For: T N2 APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 143.75 | 07-JAN-13:00 | 327.15 | 24-JAN-09:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 173.44 | 02-FEB-14:00 | 482.94 | 04-FEB-05:00 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 196.58 | 13-MAR-17:00 | 437.22 | 16-MAR-02:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 221.49 | 15-APR-17:00 | 144.91 | 18-APR-24:00 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 381.18 | 22-MAY-15:00 | 93.29 | 10-MAY-15:00 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 268.71 | 16-JUN-13:00 | 17.67 | 05-JUN-14:10 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 293.24 | 30-JUL-16:00 | 25.98 | 02-JUL-16:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 272.70 | 22-AUG-13:00 | 43.60 | 14-AUG-03:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 254.17 | 20-SEP-14:00 | 21.64 | 05-SEP-06:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 271.04 | 03-OCT-13:00 | 55.18 | 31-OCT-06:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 153.73 | 22-NOV-13:00 | 396.14 | 11-NOV-09:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 173.37 | 10-DEC-15:00 | 424.32 | 15-DEC-06:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 143.75 | 17.67 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 381.18 | 482.94 |
Report: PeakSpaceGainsMonthly
For: T S1 APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 143.75 | 07-JAN-13:00 | 352.55 | 24-JAN-09:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 173.44 | 02-FEB-14:00 | 482.94 | 04-FEB-05:00 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 196.58 | 13-MAR-17:00 | 437.22 | 16-MAR-02:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 221.49 | 15-APR-17:00 | 146.46 | 18-APR-24:00 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 381.18 | 22-MAY-15:00 | 93.29 | 10-MAY-15:00 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 268.71 | 16-JUN-13:00 | 17.67 | 05-JUN-14:10 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 293.24 | 30-JUL-16:00 | 25.98 | 02-JUL-16:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 272.70 | 22-AUG-13:00 | 43.60 | 14-AUG-03:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 254.17 | 20-SEP-14:00 | 21.64 | 05-SEP-06:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 271.04 | 03-OCT-13:00 | 55.18 | 31-OCT-06:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 153.73 | 22-NOV-13:00 | 422.55 | 11-NOV-09:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 173.37 | 10-DEC-15:00 | 424.32 | 15-DEC-06:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 143.75 | 17.67 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 381.18 | 482.94 |
Report: PeakSpaceGainsMonthly
For: T S2 APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 143.75 | 07-JAN-13:00 | 353.08 | 24-JAN-09:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 173.44 | 02-FEB-14:00 | 482.94 | 04-FEB-05:00 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 196.58 | 13-MAR-17:00 | 437.22 | 16-MAR-02:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 221.49 | 15-APR-17:00 | 146.28 | 18-APR-24:00 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 381.18 | 22-MAY-15:00 | 93.29 | 10-MAY-15:00 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 268.71 | 16-JUN-13:00 | 17.67 | 05-JUN-14:10 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 293.24 | 30-JUL-16:00 | 25.98 | 02-JUL-16:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 272.70 | 22-AUG-13:00 | 43.60 | 14-AUG-03:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 254.17 | 20-SEP-14:00 | 21.64 | 05-SEP-06:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 271.04 | 03-OCT-13:00 | 55.18 | 31-OCT-06:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 153.73 | 22-NOV-13:00 | 423.16 | 11-NOV-09:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 173.37 | 10-DEC-15:00 | 424.32 | 15-DEC-06:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 143.75 | 17.67 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 381.18 | 482.94 |
Report: PeakSpaceGainsMonthly
For: T CORRIDOR
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 397.10 | 01-JAN-00:10 | 370.63 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.17 | 07-JAN-13:00 | 107.06 | 24-JAN-09:00 |
| February | 397.10 | 01-FEB-00:10 | 370.63 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.79 | 02-FEB-14:00 | 136.75 | 04-FEB-05:00 |
| March | 397.10 | 01-MAR-00:10 | 370.63 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.38 | 13-MAR-17:00 | 135.48 | 16-MAR-02:00 |
| April | 397.10 | 01-APR-00:10 | 370.63 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.24 | 15-APR-17:00 | 50.16 | 18-APR-08:10 |
| May | 397.10 | 01-MAY-00:10 | 370.63 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.48 | 29-MAY-16:00 | 58.45 | 10-MAY-15:00 |
| June | 397.10 | 01-JUN-00:10 | 370.63 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.96 | 16-JUN-13:00 | 25.65 | 18-JUN-20:00 |
| July | 397.10 | 01-JUL-00:10 | 370.63 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.10 | 27-JUL-16:00 | 24.06 | 14-JUL-15:00 |
| August | 397.10 | 01-AUG-00:10 | 370.63 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.83 | 22-AUG-13:00 | 32.32 | 14-AUG-03:00 |
| September | 397.10 | 01-SEP-00:10 | 370.63 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.03 | 20-SEP-14:00 | 17.38 | 19-SEP-23:00 |
| October | 397.10 | 01-OCT-00:10 | 370.63 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.13 | 03-OCT-13:00 | 27.13 | 31-OCT-06:00 |
| November | 397.10 | 01-NOV-00:10 | 370.63 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.34 | 03-NOV-13:00 | 130.27 | 11-NOV-09:00 |
| December | 397.10 | 01-DEC-00:10 | 370.63 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.54 | 10-DEC-15:00 | 127.26 | 15-DEC-06:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
| Minimum of Months | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.34 | 17.38 | ||||
| Maximum of Months | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.48 | 136.75 |
Report: PeakSpaceGainsMonthly
For: G CORRIDOR
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 397.10 | 01-JAN-00:10 | 370.63 | 01-JAN-00:10 | 208.40 | 01-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 168.51 | 02-JAN-14:00 | 8302.93 | 25-JAN-07:01 |
| February | 397.10 | 01-FEB-00:10 | 370.63 | 01-FEB-00:10 | 208.40 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 224.15 | 11-FEB-14:00 | 10524.05 | 04-FEB-07:01 |
| March | 397.10 | 01-MAR-00:10 | 370.63 | 01-MAR-00:10 | 208.40 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1327.09 | 13-MAR-16:02 | 9911.27 | 16-MAR-06:01 |
| April | 397.10 | 01-APR-00:10 | 370.63 | 01-APR-00:10 | 208.40 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2209.34 | 17-APR-16:02 | 5946.02 | 02-APR-06:01 |
| May | 397.10 | 01-MAY-00:10 | 370.63 | 01-MAY-00:10 | 208.40 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2808.29 | 29-MAY-16:02 | 2692.59 | 07-MAY-06:02 |
| June | 397.10 | 01-JUN-00:10 | 370.63 | 01-JUN-00:10 | 208.40 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1931.72 | 10-JUN-16:03 | 1487.45 | 14-JUN-06:03 |
| July | 397.10 | 01-JUL-00:10 | 370.63 | 01-JUL-00:10 | 208.40 | 01-JUL-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3717.56 | 29-JUL-16:02 | 2071.59 | 02-JUL-16:03 |
| August | 397.10 | 01-AUG-00:10 | 370.63 | 01-AUG-00:10 | 208.40 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2459.67 | 07-AUG-16:02 | 1664.31 | 29-AUG-06:03 |
| September | 397.10 | 01-SEP-00:10 | 370.63 | 01-SEP-00:10 | 208.40 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2342.76 | 08-SEP-16:02 | 2138.11 | 05-SEP-06:03 |
| October | 397.10 | 01-OCT-00:10 | 370.63 | 01-OCT-00:10 | 208.40 | 01-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1790.77 | 03-OCT-16:02 | 2388.30 | 31-OCT-06:02 |
| November | 397.10 | 01-NOV-00:10 | 370.63 | 01-NOV-00:10 | 208.40 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 632.48 | 02-NOV-16:02 | 8246.74 | 27-NOV-07:01 |
| December | 397.10 | 01-DEC-00:10 | 370.63 | 01-DEC-00:10 | 208.40 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 158.49 | 10-DEC-14:00 | 9383.83 | 15-DEC-07:01 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 397.10 | 370.63 | 208.40 | 0.00 | 0.00 | 0.00 | 0.00 | 158.49 | 1487.45 | |||||
| Maximum of Months | 397.10 | 370.63 | 208.40 | 0.00 | 0.00 | 0.00 | 0.00 | 3717.56 | 10524.05 |
Report: PeakSpaceGainsMonthly
For: M CORRIDOR
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 397.10 | 01-JAN-00:10 | 370.63 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.29 | 07-JAN-13:00 | 98.26 | 24-JAN-09:00 |
| February | 397.10 | 01-FEB-00:10 | 370.63 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.85 | 02-FEB-14:00 | 125.54 | 04-FEB-05:00 |
| March | 397.10 | 01-MAR-00:10 | 370.63 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.69 | 13-MAR-17:00 | 121.99 | 16-MAR-02:00 |
| April | 397.10 | 01-APR-00:10 | 370.63 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.15 | 15-APR-17:00 | 43.04 | 18-APR-08:40 |
| May | 397.10 | 01-MAY-00:10 | 370.63 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.79 | 22-MAY-14:50 | 38.34 | 10-MAY-15:00 |
| June | 397.10 | 01-JUN-00:10 | 370.63 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.53 | 16-JUN-13:00 | 17.29 | 18-JUN-20:00 |
| July | 397.10 | 01-JUL-00:10 | 370.63 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.42 | 27-JUL-16:00 | 15.30 | 04-JUL-03:00 |
| August | 397.10 | 01-AUG-00:10 | 370.63 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.46 | 22-AUG-13:00 | 24.07 | 14-AUG-03:00 |
| September | 397.10 | 01-SEP-00:10 | 370.63 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.38 | 20-SEP-14:00 | 11.88 | 19-SEP-23:00 |
| October | 397.10 | 01-OCT-00:10 | 370.63 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.82 | 03-OCT-13:00 | 22.02 | 16-OCT-05:00 |
| November | 397.10 | 01-NOV-00:10 | 370.63 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.43 | 03-NOV-13:00 | 114.80 | 11-NOV-09:00 |
| December | 397.10 | 01-DEC-00:10 | 370.63 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.73 | 10-DEC-15:00 | 116.09 | 15-DEC-06:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
| Minimum of Months | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.29 | 11.88 | ||||
| Maximum of Months | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.79 | 125.54 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: G SW APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 2045.67 | 02-JAN-14:40 | 118.75 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 60.85 | 0.00 |
| February | 2045.44 | 20-FEB-17:10 | 237.50 | 86.80 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 41.91 | 0.00 |
| March | 1835.12 | 13-MAR-16:25 | 0.00 | 173.60 | 1177.25 | 0.00 | 0.00 | 0.00 | 0.00 | 151.89 | 0.00 |
| April | 2035.35 | 15-APR-17:00 | 237.50 | 86.80 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 194.68 | 0.00 |
| May | 2025.15 | 29-MAY-16:30 | 237.50 | 86.80 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 279.79 | 0.00 |
| June | 1922.75 | 14-JUN-17:13 | 712.50 | 351.55 | 1765.87 | 0.00 | 0.00 | 0.00 | 0.00 | 186.18 | 0.00 |
| July | 2213.15 | 29-JUL-16:30 | 237.50 | 86.80 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 147.86 | 0.00 |
| August | 2181.81 | 20-AUG-16:30 | 237.50 | 86.80 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 123.06 | 0.00 |
| September | 2351.00 | 30-SEP-16:10 | 712.50 | 260.40 | 1765.87 | 0.00 | 0.00 | 0.00 | 0.00 | 118.08 | 0.00 |
| October | 2335.65 | 25-OCT-16:03 | 0.00 | 520.80 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 87.57 | 0.00 |
| November | 2215.08 | 07-NOV-16:10 | 0.00 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 59.29 | 0.00 |
| December | 2199.21 | 10-DEC-15:10 | 0.00 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 142.36 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 1835.12 | 0.00 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 41.91 | 0.00 | |
| Maximum of Months | 2351.00 | 712.50 | 520.80 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 279.79 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: G NW APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 1213.83 | 03-JAN-16:10 | 71.25 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 31.35 | 0.00 |
| February | 1452.76 | 11-FEB-16:30 | 71.25 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 77.07 | 0.00 |
| March | 1532.35 | 27-MAR-16:25 | 247.00 | 173.60 | 1177.25 | 0.00 | 0.00 | 0.00 | 0.00 | 64.91 | 0.00 |
| April | 1896.72 | 15-APR-17:00 | 123.50 | 86.80 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 194.68 | 0.00 |
| May | 2047.08 | 29-MAY-17:10 | 619.87 | 351.55 | 1765.87 | 0.00 | 0.00 | 0.00 | 0.00 | 261.44 | 0.00 |
| June | 2053.24 | 14-JUN-17:30 | 413.25 | 234.36 | 1177.25 | 0.00 | 0.00 | 0.00 | 0.00 | 185.21 | 0.00 |
| July | 2173.83 | 27-JUL-17:12 | 826.50 | 468.73 | 2354.49 | 0.00 | 0.00 | 0.00 | 0.00 | 212.57 | 0.00 |
| August | 2101.13 | 17-AUG-17:00 | 123.50 | 86.80 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 194.59 | 0.00 |
| September | 2049.49 | 17-SEP-16:30 | 123.50 | 86.80 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 207.47 | 0.00 |
| October | 1889.07 | 03-OCT-16:30 | 123.50 | 86.80 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 186.62 | 0.00 |
| November | 1529.11 | 03-NOV-16:04 | 617.50 | 434.00 | 2943.11 | 0.00 | 0.00 | 0.00 | 0.00 | 97.31 | 0.00 |
| December | 1469.96 | 10-DEC-15:30 | 59.38 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 121.90 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 1213.83 | 59.38 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 31.35 | 0.00 | |
| Maximum of Months | 2173.83 | 826.50 | 468.73 | 2943.11 | 0.00 | 0.00 | 0.00 | 0.00 | 261.44 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: OFFICE
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 6568.73 | 09-JAN-09:02 | 2256.03 | 2914.58 | 2943.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 153.30 |
| February | 6581.93 | 22-FEB-09:02 | 2256.03 | 2914.58 | 2943.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82.56 |
| March | 6201.92 | 01-MAR-09:02 | 2256.03 | 2914.58 | 2943.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 158.29 |
| April | 6631.31 | 18-APR-07:02 | 2256.03 | 2914.58 | 2943.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 149.32 |
| May | 5627.39 | 08-MAY-07:02 | 2707.23 | 3497.50 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.84 |
| June | 4435.67 | 12-JUN-08:62 | 1804.82 | 2331.66 | 2354.49 | 0.00 | 0.00 | 0.00 | 0.00 | 35.14 | 0.00 |
| July | 4576.33 | 06-JUL-08:62 | 2256.03 | 2914.58 | 2943.11 | 0.00 | 0.00 | 0.00 | 0.00 | 17.60 | 0.00 |
| August | 4515.83 | 28-AUG-08:62 | 2256.03 | 2914.58 | 2943.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.21 |
| September | 4616.48 | 11-SEP-08:62 | 1804.82 | 2331.66 | 2354.49 | 0.00 | 0.00 | 0.00 | 0.00 | 17.02 | 0.00 |
| October | 5920.75 | 18-OCT-07:02 | 2707.23 | 3497.50 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.39 |
| November | 6652.36 | 27-NOV-09:02 | 2256.03 | 2914.58 | 2943.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 120.52 |
| December | 6698.23 | 12-DEC-09:02 | 2256.03 | 2914.58 | 2943.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 166.87 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 4435.67 | 1804.82 | 2331.66 | 2354.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 6698.23 | 2707.23 | 3497.50 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 35.14 | 166.87 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: G NE APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 1139.81 | 01-JAN-13:00 | 59.38 | 17.36 | 406.15 | 0.00 | 0.00 | 0.00 | 0.00 | 38.29 | 0.00 |
| February | 1183.68 | 11-FEB-14:00 | 59.38 | 17.36 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 95.35 | 0.00 |
| March | 1299.28 | 13-MAR-17:00 | 123.50 | 86.80 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 173.55 | 0.00 |
| April | 1596.03 | 15-APR-17:00 | 123.50 | 86.80 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 194.68 | 0.00 |
| May | 1795.11 | 22-MAY-16:03 | 741.00 | 520.80 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 260.74 | 0.00 |
| June | 1794.17 | 03-JUN-16:30 | 123.50 | 86.80 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 125.53 | 0.00 |
| July | 1974.67 | 29-JUL-16:30 | 123.50 | 86.80 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 147.86 | 0.00 |
| August | 1856.31 | 20-AUG-11:40 | 59.38 | 17.36 | 406.15 | 0.00 | 0.00 | 0.00 | 0.00 | 189.08 | 0.00 |
| September | 1858.39 | 18-SEP-16:03 | 864.50 | 607.59 | 4120.36 | 0.00 | 0.00 | 0.00 | 0.00 | 207.78 | 0.00 |
| October | 1735.04 | 03-OCT-16:03 | 741.00 | 520.80 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 199.89 | 0.00 |
| November | 1439.35 | 03-NOV-16:04 | 617.50 | 434.00 | 2943.11 | 0.00 | 0.00 | 0.00 | 0.00 | 97.31 | 0.00 |
| December | 1310.29 | 10-DEC-14:00 | 59.38 | 17.36 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 143.74 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 1139.81 | 59.38 | 17.36 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 38.29 | 0.00 | |
| Maximum of Months | 1974.67 | 864.50 | 607.59 | 4120.36 | 0.00 | 0.00 | 0.00 | 0.00 | 260.74 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: G N1 APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 956.74 | 01-JAN-17:10 | 247.00 | 173.60 | 1177.25 | 0.00 | 0.00 | 0.00 | 0.00 | 8.18 | 0.00 |
| February | 1026.01 | 11-FEB-17:10 | 123.50 | 86.80 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 40.73 | 0.00 |
| March | 1078.46 | 13-MAR-17:10 | 413.25 | 234.36 | 1177.25 | 0.00 | 0.00 | 0.00 | 0.00 | 97.80 | 0.00 |
| April | 1270.05 | 15-APR-17:07 | 619.87 | 351.55 | 1765.87 | 0.00 | 0.00 | 0.00 | 0.00 | 109.00 | 0.00 |
| May | 1450.49 | 29-MAY-17:07 | 619.87 | 351.55 | 1765.87 | 0.00 | 0.00 | 0.00 | 0.00 | 157.69 | 0.00 |
| June | 1445.83 | 29-JUN-17:17 | 619.87 | 351.55 | 1765.87 | 0.00 | 0.00 | 0.00 | 0.00 | 86.24 | 0.00 |
| July | 1557.61 | 29-JUL-17:13 | 619.87 | 351.55 | 1765.87 | 0.00 | 0.00 | 0.00 | 0.00 | 93.73 | 0.00 |
| August | 1461.88 | 02-AUG-17:30 | 413.25 | 234.36 | 1177.25 | 0.00 | 0.00 | 0.00 | 0.00 | 85.79 | 0.00 |
| September | 1459.46 | 18-SEP-16:17 | 370.50 | 260.40 | 1765.87 | 0.00 | 0.00 | 0.00 | 0.00 | 123.72 | 0.00 |
| October | 1374.11 | 03-OCT-16:03 | 741.00 | 520.80 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 120.57 | 0.00 |
| November | 1196.98 | 04-NOV-16:10 | 123.50 | 86.80 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 71.57 | 0.00 |
| December | 1083.28 | 10-DEC-17:10 | 123.50 | 86.80 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 40.23 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 956.74 | 123.50 | 86.80 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 8.18 | 0.00 | |
| Maximum of Months | 1557.61 | 741.00 | 520.80 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 157.69 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: G N2 APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 958.58 | 01-JAN-17:10 | 247.00 | 173.60 | 1177.25 | 0.00 | 0.00 | 0.00 | 0.00 | 8.18 | 0.00 |
| February | 1020.72 | 11-FEB-17:10 | 123.50 | 86.80 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 40.73 | 0.00 |
| March | 1073.66 | 13-MAR-17:10 | 413.25 | 234.36 | 1177.25 | 0.00 | 0.00 | 0.00 | 0.00 | 97.80 | 0.00 |
| April | 1265.61 | 15-APR-17:07 | 619.87 | 351.55 | 1765.87 | 0.00 | 0.00 | 0.00 | 0.00 | 109.00 | 0.00 |
| May | 1445.88 | 29-MAY-17:07 | 619.87 | 351.55 | 1765.87 | 0.00 | 0.00 | 0.00 | 0.00 | 157.69 | 0.00 |
| June | 1441.68 | 29-JUN-17:17 | 619.87 | 351.55 | 1765.87 | 0.00 | 0.00 | 0.00 | 0.00 | 86.24 | 0.00 |
| July | 1555.36 | 29-JUL-17:13 | 619.87 | 351.55 | 1765.87 | 0.00 | 0.00 | 0.00 | 0.00 | 93.73 | 0.00 |
| August | 1458.79 | 02-AUG-17:30 | 413.25 | 234.36 | 1177.25 | 0.00 | 0.00 | 0.00 | 0.00 | 85.79 | 0.00 |
| September | 1456.78 | 18-SEP-16:17 | 370.50 | 260.40 | 1765.87 | 0.00 | 0.00 | 0.00 | 0.00 | 123.72 | 0.00 |
| October | 1372.49 | 03-OCT-16:03 | 741.00 | 520.80 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 120.57 | 0.00 |
| November | 1197.08 | 04-NOV-16:10 | 123.50 | 86.80 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 71.57 | 0.00 |
| December | 1080.06 | 10-DEC-17:10 | 123.50 | 86.80 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 40.23 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 958.58 | 123.50 | 86.80 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 8.18 | 0.00 | |
| Maximum of Months | 1555.36 | 741.00 | 520.80 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 157.69 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: G S1 APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 1795.14 | 02-JAN-14:30 | 118.75 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 31.79 | 0.00 |
| February | 1585.54 | 20-FEB-16:10 | 237.50 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 37.07 | 0.00 |
| March | 1425.72 | 01-MAR-15:10 | 0.00 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 7.35 | 0.00 |
| April | 1406.64 | 15-APR-17:00 | 237.50 | 86.80 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 117.42 | 0.00 |
| May | 1420.88 | 29-MAY-16:40 | 237.50 | 86.80 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 167.04 | 0.00 |
| June | 1393.99 | 03-JUN-16:30 | 237.50 | 86.80 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 75.72 | 0.00 |
| July | 1587.58 | 29-JUL-17:05 | 950.00 | 468.73 | 2354.49 | 0.00 | 0.00 | 0.00 | 0.00 | 89.22 | 0.00 |
| August | 1580.70 | 20-AUG-16:10 | 712.50 | 260.40 | 1765.87 | 0.00 | 0.00 | 0.00 | 0.00 | 77.26 | 0.00 |
| September | 1756.44 | 24-SEP-13:30 | 118.75 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 88.77 | 0.00 |
| October | 1799.20 | 25-OCT-14:10 | 0.00 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 73.53 | 0.00 |
| November | 1821.30 | 22-NOV-12:40 | 0.00 | 17.36 | 406.15 | 0.00 | 0.00 | 0.00 | 0.00 | 76.51 | 0.00 |
| December | 1800.26 | 10-DEC-14:40 | 118.75 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 90.45 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 1393.99 | 0.00 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 7.35 | 0.00 | |
| Maximum of Months | 1821.30 | 950.00 | 468.73 | 2354.49 | 0.00 | 0.00 | 0.00 | 0.00 | 167.04 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: G S2 APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 1969.55 | 02-JAN-14:30 | 118.75 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 31.79 | 0.00 |
| February | 1709.08 | 20-FEB-16:10 | 237.50 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 37.07 | 0.00 |
| March | 1482.30 | 01-MAR-15:10 | 0.00 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 7.35 | 0.00 |
| April | 1519.93 | 15-APR-17:00 | 237.50 | 86.80 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 117.42 | 0.00 |
| May | 1551.15 | 29-MAY-16:40 | 237.50 | 86.80 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 167.04 | 0.00 |
| June | 1525.36 | 03-JUN-16:30 | 237.50 | 86.80 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 75.72 | 0.00 |
| July | 1722.09 | 29-JUL-17:05 | 950.00 | 468.73 | 2354.49 | 0.00 | 0.00 | 0.00 | 0.00 | 89.22 | 0.00 |
| August | 1736.47 | 20-AUG-16:10 | 712.50 | 260.40 | 1765.87 | 0.00 | 0.00 | 0.00 | 0.00 | 77.26 | 0.00 |
| September | 1922.10 | 24-SEP-13:30 | 118.75 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 88.77 | 0.00 |
| October | 1945.65 | 29-OCT-14:10 | 0.00 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 103.89 | 0.00 |
| November | 1908.93 | 22-NOV-12:40 | 0.00 | 17.36 | 406.15 | 0.00 | 0.00 | 0.00 | 0.00 | 76.51 | 0.00 |
| December | 1946.48 | 10-DEC-14:40 | 118.75 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 90.45 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 1482.30 | 0.00 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 7.35 | 0.00 | |
| Maximum of Months | 1969.55 | 950.00 | 468.73 | 2354.49 | 0.00 | 0.00 | 0.00 | 0.00 | 167.04 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: M SW APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 2336.01 | 02-JAN-14:40 | 118.75 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 87.10 | 0.00 |
| February | 2428.98 | 20-FEB-16:20 | 237.50 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 83.72 | 0.00 |
| March | 2225.87 | 13-MAR-16:30 | 0.00 | 173.60 | 1177.25 | 0.00 | 0.00 | 0.00 | 0.00 | 217.43 | 0.00 |
| April | 2439.09 | 15-APR-17:00 | 237.50 | 86.80 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 279.04 | 0.00 |
| May | 2449.52 | 29-MAY-16:30 | 237.50 | 86.80 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 401.14 | 0.00 |
| June | 2266.11 | 14-JUN-17:13 | 712.50 | 351.55 | 1765.87 | 0.00 | 0.00 | 0.00 | 0.00 | 266.64 | 0.00 |
| July | 2449.01 | 29-JUL-16:30 | 237.50 | 86.80 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 212.11 | 0.00 |
| August | 2370.37 | 16-AUG-16:03 | 0.00 | 520.80 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 291.15 | 0.00 |
| September | 2563.68 | 30-SEP-16:07 | 712.50 | 260.40 | 1765.87 | 0.00 | 0.00 | 0.00 | 0.00 | 169.20 | 0.00 |
| October | 2550.12 | 25-OCT-16:03 | 0.00 | 520.80 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 125.25 | 0.00 |
| November | 2444.38 | 07-NOV-16:10 | 0.00 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 84.81 | 0.00 |
| December | 2454.19 | 10-DEC-15:00 | 118.75 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 219.07 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 2225.87 | 0.00 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 83.72 | 0.00 | |
| Maximum of Months | 2563.68 | 712.50 | 520.80 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 401.14 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: M NW APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 1305.48 | 03-JAN-16:10 | 71.25 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 44.69 | 0.00 |
| February | 1709.65 | 11-FEB-16:30 | 71.25 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 110.13 | 0.00 |
| March | 1900.65 | 13-MAR-16:40 | 123.50 | 86.80 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 228.22 | 0.00 |
| April | 2270.69 | 15-APR-17:00 | 123.50 | 86.80 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 279.04 | 0.00 |
| May | 2461.92 | 29-MAY-16:40 | 123.50 | 86.80 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 397.02 | 0.00 |
| June | 2412.81 | 14-JUN-17:30 | 413.25 | 234.36 | 1177.25 | 0.00 | 0.00 | 0.00 | 0.00 | 265.23 | 0.00 |
| July | 2403.12 | 27-JUL-16:30 | 123.50 | 86.80 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 312.58 | 0.00 |
| August | 2297.83 | 16-AUG-16:30 | 123.50 | 86.80 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 270.20 | 0.00 |
| September | 2221.88 | 17-SEP-16:30 | 123.50 | 86.80 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 297.32 | 0.00 |
| October | 2023.81 | 03-OCT-16:30 | 123.50 | 86.80 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 267.40 | 0.00 |
| November | 1601.49 | 03-NOV-16:04 | 617.50 | 434.00 | 2943.11 | 0.00 | 0.00 | 0.00 | 0.00 | 139.19 | 0.00 |
| December | 1575.81 | 10-DEC-15:30 | 59.38 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 174.43 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 1305.48 | 59.38 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 44.69 | 0.00 | |
| Maximum of Months | 2461.92 | 617.50 | 434.00 | 2943.11 | 0.00 | 0.00 | 0.00 | 0.00 | 397.02 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: M SE APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 2271.41 | 02-JAN-14:30 | 118.75 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 75.43 | 0.00 |
| February | 2120.77 | 11-FEB-14:30 | 118.75 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 144.15 | 0.00 |
| March | 1928.00 | 04-MAR-13:40 | 118.75 | 17.36 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 176.11 | 0.00 |
| April | 2042.73 | 15-APR-16:15 | 475.00 | 173.60 | 1177.25 | 0.00 | 0.00 | 0.00 | 0.00 | 251.29 | 0.00 |
| May | 2107.59 | 29-MAY-16:04 | 1187.50 | 434.00 | 2943.11 | 0.00 | 0.00 | 0.00 | 0.00 | 407.78 | 0.00 |
| June | 1997.24 | 03-JUN-16:07 | 712.50 | 260.40 | 1765.87 | 0.00 | 0.00 | 0.00 | 0.00 | 194.08 | 0.00 |
| July | 2197.20 | 29-JUL-16:07 | 1425.00 | 520.80 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 219.55 | 0.00 |
| August | 2133.79 | 20-AUG-12:00 | 118.75 | 17.36 | 406.15 | 0.00 | 0.00 | 0.00 | 0.00 | 298.83 | 0.00 |
| September | 2341.35 | 24-SEP-12:30 | 118.75 | 17.36 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 220.82 | 0.00 |
| October | 2344.42 | 25-OCT-13:00 | 0.00 | 17.36 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 186.24 | 0.00 |
| November | 2383.58 | 22-NOV-12:30 | 0.00 | 17.36 | 406.15 | 0.00 | 0.00 | 0.00 | 0.00 | 174.70 | 0.00 |
| December | 2268.08 | 09-DEC-12:30 | 118.75 | 17.36 | 406.15 | 0.00 | 0.00 | 0.00 | 0.00 | 99.51 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 1928.00 | 0.00 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 75.43 | 0.00 | |
| Maximum of Months | 2383.58 | 1425.00 | 520.80 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 407.78 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: M NE APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 1212.20 | 07-JAN-13:00 | 59.38 | 17.36 | 406.15 | 0.00 | 0.00 | 0.00 | 0.00 | 181.84 | 0.00 |
| February | 1360.06 | 02-FEB-14:00 | 59.38 | 17.36 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 219.42 | 0.00 |
| March | 1593.30 | 13-MAR-17:00 | 123.50 | 86.80 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 248.40 | 0.00 |
| April | 1865.25 | 15-APR-16:50 | 123.50 | 86.80 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 272.11 | 0.00 |
| May | 2107.27 | 29-MAY-16:20 | 247.00 | 173.60 | 1177.25 | 0.00 | 0.00 | 0.00 | 0.00 | 404.73 | 0.00 |
| June | 2006.57 | 14-JUN-17:20 | 619.87 | 351.55 | 1765.87 | 0.00 | 0.00 | 0.00 | 0.00 | 266.64 | 0.00 |
| July | 2122.90 | 29-JUL-16:03 | 741.00 | 520.80 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 219.55 | 0.00 |
| August | 1953.00 | 20-AUG-12:00 | 59.38 | 17.36 | 406.15 | 0.00 | 0.00 | 0.00 | 0.00 | 298.83 | 0.00 |
| September | 1944.95 | 18-SEP-16:03 | 864.50 | 607.59 | 4120.36 | 0.00 | 0.00 | 0.00 | 0.00 | 297.82 | 0.00 |
| October | 1817.75 | 03-OCT-16:03 | 741.00 | 520.80 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 286.44 | 0.00 |
| November | 1482.85 | 03-NOV-16:04 | 617.50 | 434.00 | 2943.11 | 0.00 | 0.00 | 0.00 | 0.00 | 139.19 | 0.00 |
| December | 1361.75 | 10-DEC-14:00 | 59.38 | 17.36 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 205.73 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 1212.20 | 59.38 | 17.36 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 139.19 | 0.00 | |
| Maximum of Months | 2122.90 | 864.50 | 607.59 | 4120.36 | 0.00 | 0.00 | 0.00 | 0.00 | 404.73 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: M N1 APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 969.37 | 01-JAN-17:05 | 247.00 | 173.60 | 1177.25 | 0.00 | 0.00 | 0.00 | 0.00 | 11.47 | 0.00 |
| February | 1125.38 | 11-FEB-17:10 | 123.50 | 86.80 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 58.15 | 0.00 |
| March | 1272.82 | 13-MAR-17:05 | 413.25 | 234.36 | 1177.25 | 0.00 | 0.00 | 0.00 | 0.00 | 139.97 | 0.00 |
| April | 1424.06 | 15-APR-17:07 | 619.87 | 351.55 | 1765.87 | 0.00 | 0.00 | 0.00 | 0.00 | 156.22 | 0.00 |
| May | 1635.88 | 29-MAY-17:07 | 619.87 | 351.55 | 1765.87 | 0.00 | 0.00 | 0.00 | 0.00 | 226.02 | 0.00 |
| June | 1592.66 | 14-JUN-17:30 | 413.25 | 234.36 | 1177.25 | 0.00 | 0.00 | 0.00 | 0.00 | 159.98 | 0.00 |
| July | 1629.41 | 27-JUL-17:30 | 413.25 | 234.36 | 1177.25 | 0.00 | 0.00 | 0.00 | 0.00 | 187.18 | 0.00 |
| August | 1495.27 | 02-AUG-17:30 | 413.25 | 234.36 | 1177.25 | 0.00 | 0.00 | 0.00 | 0.00 | 122.91 | 0.00 |
| September | 1494.06 | 18-SEP-16:17 | 370.50 | 260.40 | 1765.87 | 0.00 | 0.00 | 0.00 | 0.00 | 177.33 | 0.00 |
| October | 1401.83 | 03-OCT-16:03 | 741.00 | 520.80 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 172.77 | 0.00 |
| November | 1214.36 | 03-NOV-16:04 | 617.50 | 434.00 | 2943.11 | 0.00 | 0.00 | 0.00 | 0.00 | 83.95 | 0.00 |
| December | 1082.02 | 10-DEC-17:10 | 123.50 | 86.80 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 57.43 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 969.37 | 123.50 | 86.80 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 11.47 | 0.00 | |
| Maximum of Months | 1635.88 | 741.00 | 520.80 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 226.02 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: M N2 APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 970.71 | 01-JAN-17:05 | 247.00 | 173.60 | 1177.25 | 0.00 | 0.00 | 0.00 | 0.00 | 11.47 | 0.00 |
| February | 1118.93 | 11-FEB-17:10 | 123.50 | 86.80 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 58.15 | 0.00 |
| March | 1267.92 | 13-MAR-17:05 | 413.25 | 234.36 | 1177.25 | 0.00 | 0.00 | 0.00 | 0.00 | 139.97 | 0.00 |
| April | 1419.30 | 15-APR-17:07 | 619.87 | 351.55 | 1765.87 | 0.00 | 0.00 | 0.00 | 0.00 | 156.22 | 0.00 |
| May | 1630.38 | 29-MAY-17:07 | 619.87 | 351.55 | 1765.87 | 0.00 | 0.00 | 0.00 | 0.00 | 226.02 | 0.00 |
| June | 1588.12 | 14-JUN-17:30 | 413.25 | 234.36 | 1177.25 | 0.00 | 0.00 | 0.00 | 0.00 | 159.98 | 0.00 |
| July | 1625.16 | 27-JUL-17:30 | 413.25 | 234.36 | 1177.25 | 0.00 | 0.00 | 0.00 | 0.00 | 187.18 | 0.00 |
| August | 1491.26 | 02-AUG-17:30 | 413.25 | 234.36 | 1177.25 | 0.00 | 0.00 | 0.00 | 0.00 | 122.91 | 0.00 |
| September | 1491.09 | 18-SEP-16:17 | 370.50 | 260.40 | 1765.87 | 0.00 | 0.00 | 0.00 | 0.00 | 177.33 | 0.00 |
| October | 1400.40 | 03-OCT-16:03 | 741.00 | 520.80 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 172.77 | 0.00 |
| November | 1213.07 | 03-NOV-16:04 | 617.50 | 434.00 | 2943.11 | 0.00 | 0.00 | 0.00 | 0.00 | 83.95 | 0.00 |
| December | 1078.34 | 10-DEC-17:10 | 123.50 | 86.80 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 57.43 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 970.71 | 123.50 | 86.80 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 11.47 | 0.00 | |
| Maximum of Months | 1630.38 | 741.00 | 520.80 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 226.02 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: M S1 APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 2001.94 | 02-JAN-14:30 | 118.75 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 45.50 | 0.00 |
| February | 1832.21 | 20-FEB-15:00 | 118.75 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 59.77 | 0.00 |
| March | 1657.23 | 01-MAR-14:40 | 0.00 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.26 | 0.00 |
| April | 1588.20 | 15-APR-16:30 | 237.50 | 86.80 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 155.76 | 0.00 |
| May | 1615.93 | 29-MAY-16:20 | 475.00 | 173.60 | 1177.25 | 0.00 | 0.00 | 0.00 | 0.00 | 244.12 | 0.00 |
| June | 1514.81 | 03-JUN-16:30 | 237.50 | 86.80 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 108.51 | 0.00 |
| July | 1662.52 | 29-JUL-16:03 | 1425.00 | 520.80 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 132.42 | 0.00 |
| August | 1612.19 | 20-AUG-16:07 | 712.50 | 260.40 | 1765.87 | 0.00 | 0.00 | 0.00 | 0.00 | 110.69 | 0.00 |
| September | 1844.47 | 30-SEP-14:00 | 118.75 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 121.22 | 0.00 |
| October | 1936.54 | 29-OCT-14:00 | 118.75 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 152.10 | 0.00 |
| November | 2001.31 | 22-NOV-12:30 | 0.00 | 17.36 | 406.15 | 0.00 | 0.00 | 0.00 | 0.00 | 105.37 | 0.00 |
| December | 1955.98 | 10-DEC-14:40 | 118.75 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 129.46 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 1514.81 | 0.00 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.26 | 0.00 | |
| Maximum of Months | 2001.94 | 1425.00 | 520.80 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 244.12 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: M S2 APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 2005.23 | 02-JAN-14:30 | 118.75 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 45.50 | 0.00 |
| February | 1832.15 | 20-FEB-14:50 | 118.75 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 56.84 | 0.00 |
| March | 1661.10 | 01-MAR-14:40 | 0.00 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.26 | 0.00 |
| April | 1584.79 | 15-APR-16:30 | 237.50 | 86.80 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 155.76 | 0.00 |
| May | 1611.98 | 29-MAY-16:20 | 475.00 | 173.60 | 1177.25 | 0.00 | 0.00 | 0.00 | 0.00 | 244.12 | 0.00 |
| June | 1515.42 | 03-JUN-16:30 | 237.50 | 86.80 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 108.51 | 0.00 |
| July | 1660.91 | 29-JUL-16:03 | 1425.00 | 520.80 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 132.42 | 0.00 |
| August | 1609.08 | 31-AUG-16:07 | 0.00 | 520.80 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 110.03 | 0.00 |
| September | 1847.23 | 30-SEP-14:00 | 118.75 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 121.22 | 0.00 |
| October | 1937.72 | 29-OCT-14:00 | 118.75 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 152.10 | 0.00 |
| November | 2007.42 | 22-NOV-12:30 | 0.00 | 17.36 | 406.15 | 0.00 | 0.00 | 0.00 | 0.00 | 105.37 | 0.00 |
| December | 1955.01 | 10-DEC-14:40 | 118.75 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 129.46 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 1515.42 | 0.00 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.26 | 0.00 | |
| Maximum of Months | 2007.42 | 1425.00 | 520.80 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 244.12 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: T SW APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 3097.22 | 02-JAN-14:40 | 118.75 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 114.28 | 0.00 |
| February | 3187.87 | 11-FEB-15:00 | 118.75 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 192.55 | 0.00 |
| March | 2920.40 | 13-MAR-16:30 | 0.00 | 173.60 | 1177.25 | 0.00 | 0.00 | 0.00 | 0.00 | 285.39 | 0.00 |
| April | 3324.68 | 15-APR-16:30 | 237.50 | 86.80 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 339.82 | 0.00 |
| May | 3389.21 | 29-MAY-16:20 | 475.00 | 173.60 | 1177.25 | 0.00 | 0.00 | 0.00 | 0.00 | 532.94 | 0.00 |
| June | 3084.64 | 14-JUN-17:13 | 712.50 | 351.55 | 1765.87 | 0.00 | 0.00 | 0.00 | 0.00 | 350.29 | 0.00 |
| July | 3440.76 | 29-JUL-16:13 | 712.50 | 260.40 | 1765.87 | 0.00 | 0.00 | 0.00 | 0.00 | 284.48 | 0.00 |
| August | 3268.01 | 31-AUG-15:30 | 0.00 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 233.75 | 0.00 |
| September | 3544.26 | 30-SEP-15:30 | 237.50 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 208.23 | 0.00 |
| October | 3376.19 | 25-OCT-15:20 | 0.00 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 166.94 | 0.00 |
| November | 3226.16 | 07-NOV-15:30 | 0.00 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 78.43 | 0.00 |
| December | 3188.54 | 10-DEC-15:00 | 118.75 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 287.43 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 2920.40 | 0.00 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 78.43 | 0.00 | |
| Maximum of Months | 3544.26 | 712.50 | 351.55 | 1765.87 | 0.00 | 0.00 | 0.00 | 0.00 | 532.94 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: T NW APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 1701.68 | 02-JAN-15:10 | 59.38 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 126.02 | 0.00 |
| February | 2313.57 | 11-FEB-16:20 | 71.25 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 148.16 | 0.00 |
| March | 2549.77 | 13-MAR-16:30 | 247.00 | 173.60 | 1177.25 | 0.00 | 0.00 | 0.00 | 0.00 | 285.39 | 0.00 |
| April | 3094.42 | 15-APR-16:40 | 123.50 | 86.80 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 348.95 | 0.00 |
| May | 3414.95 | 29-MAY-16:30 | 123.50 | 86.80 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 528.14 | 0.00 |
| June | 3250.70 | 14-JUN-17:17 | 619.87 | 351.55 | 1765.87 | 0.00 | 0.00 | 0.00 | 0.00 | 350.28 | 0.00 |
| July | 3354.09 | 27-JUL-16:17 | 370.50 | 260.40 | 1765.87 | 0.00 | 0.00 | 0.00 | 0.00 | 422.11 | 0.00 |
| August | 3135.30 | 16-AUG-16:17 | 370.50 | 260.40 | 1765.87 | 0.00 | 0.00 | 0.00 | 0.00 | 369.19 | 0.00 |
| September | 3024.91 | 17-SEP-16:20 | 247.00 | 173.60 | 1177.25 | 0.00 | 0.00 | 0.00 | 0.00 | 391.10 | 0.00 |
| October | 2673.42 | 03-OCT-16:17 | 370.50 | 260.40 | 1765.87 | 0.00 | 0.00 | 0.00 | 0.00 | 364.11 | 0.00 |
| November | 2112.31 | 02-NOV-16:10 | 741.00 | 520.80 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 129.36 | 0.00 |
| December | 2070.12 | 10-DEC-15:20 | 59.38 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 247.71 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 1701.68 | 59.38 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 126.02 | 0.00 | |
| Maximum of Months | 3414.95 | 741.00 | 520.80 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 528.14 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: T SE APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 2979.80 | 02-JAN-14:30 | 118.75 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 98.97 | 0.00 |
| February | 2941.99 | 11-FEB-14:30 | 118.75 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 189.11 | 0.00 |
| March | 2582.53 | 04-MAR-13:40 | 118.75 | 17.36 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 230.25 | 0.00 |
| April | 2775.63 | 15-APR-16:05 | 950.00 | 347.20 | 2354.49 | 0.00 | 0.00 | 0.00 | 0.00 | 321.56 | 0.00 |
| May | 2913.77 | 29-MAY-16:04 | 1187.50 | 434.00 | 2943.11 | 0.00 | 0.00 | 0.00 | 0.00 | 537.03 | 0.00 |
| June | 2682.79 | 03-JUN-16:07 | 712.50 | 260.40 | 1765.87 | 0.00 | 0.00 | 0.00 | 0.00 | 255.29 | 0.00 |
| July | 3064.68 | 29-JUL-16:08 | 1425.00 | 520.80 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 289.40 | 0.00 |
| August | 2985.50 | 23-AUG-13:00 | 0.00 | 17.36 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 402.13 | 0.00 |
| September | 3219.72 | 30-SEP-14:00 | 118.75 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 264.36 | 0.00 |
| October | 3192.05 | 25-OCT-13:00 | 0.00 | 17.36 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 244.72 | 0.00 |
| November | 3135.52 | 22-NOV-12:40 | 0.00 | 17.36 | 406.15 | 0.00 | 0.00 | 0.00 | 0.00 | 237.15 | 0.00 |
| December | 2977.74 | 09-DEC-12:30 | 118.75 | 17.36 | 406.15 | 0.00 | 0.00 | 0.00 | 0.00 | 129.99 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 2582.53 | 0.00 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 98.97 | 0.00 | |
| Maximum of Months | 3219.72 | 1425.00 | 520.80 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 537.03 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: T NE APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 1554.52 | 02-JAN-15:00 | 59.38 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 144.88 | 0.00 |
| February | 1929.30 | 11-FEB-14:00 | 59.38 | 17.36 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 179.26 | 0.00 |
| March | 2099.25 | 13-MAR-16:30 | 247.00 | 173.60 | 1177.25 | 0.00 | 0.00 | 0.00 | 0.00 | 285.39 | 0.00 |
| April | 2527.23 | 15-APR-16:20 | 247.00 | 173.60 | 1177.25 | 0.00 | 0.00 | 0.00 | 0.00 | 330.69 | 0.00 |
| May | 2913.36 | 29-MAY-16:15 | 247.00 | 173.60 | 1177.25 | 0.00 | 0.00 | 0.00 | 0.00 | 532.94 | 0.00 |
| June | 2676.64 | 03-JUN-16:07 | 370.50 | 260.40 | 1765.87 | 0.00 | 0.00 | 0.00 | 0.00 | 255.29 | 0.00 |
| July | 2952.09 | 29-JUL-16:03 | 741.00 | 520.80 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 289.40 | 0.00 |
| August | 2730.15 | 22-AUG-13:00 | 59.38 | 17.36 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 452.10 | 0.00 |
| September | 2568.84 | 18-SEP-16:01 | 864.50 | 607.59 | 4120.36 | 0.00 | 0.00 | 0.00 | 0.00 | 391.89 | 0.00 |
| October | 2435.95 | 03-OCT-11:50 | 59.38 | 17.36 | 406.15 | 0.00 | 0.00 | 0.00 | 0.00 | 417.06 | 0.00 |
| November | 1967.34 | 03-NOV-13:30 | 59.38 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 210.94 | 0.00 |
| December | 1805.04 | 10-DEC-14:00 | 59.38 | 17.36 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 269.93 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 1554.52 | 59.38 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 144.88 | 0.00 | |
| Maximum of Months | 2952.09 | 864.50 | 607.59 | 4120.36 | 0.00 | 0.00 | 0.00 | 0.00 | 532.94 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: T N1 APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 1219.68 | 02-JAN-15:00 | 59.38 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 87.39 | 0.00 |
| February | 1541.12 | 11-FEB-14:40 | 59.38 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 115.19 | 0.00 |
| March | 1712.85 | 13-MAR-16:40 | 123.50 | 86.80 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 180.66 | 0.00 |
| April | 2009.02 | 15-APR-16:30 | 123.50 | 86.80 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 204.97 | 0.00 |
| May | 2315.90 | 29-MAY-16:30 | 123.50 | 86.80 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 318.56 | 0.00 |
| June | 2176.47 | 14-JUN-17:17 | 619.87 | 351.55 | 1765.87 | 0.00 | 0.00 | 0.00 | 0.00 | 211.28 | 0.00 |
| July | 2337.02 | 29-JUL-16:13 | 370.50 | 260.40 | 1765.87 | 0.00 | 0.00 | 0.00 | 0.00 | 171.59 | 0.00 |
| August | 2088.36 | 06-AUG-15:10 | 71.25 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 206.46 | 0.00 |
| September | 2046.00 | 18-SEP-16:03 | 864.50 | 607.59 | 4120.36 | 0.00 | 0.00 | 0.00 | 0.00 | 236.38 | 0.00 |
| October | 1896.38 | 03-OCT-16:03 | 741.00 | 520.80 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 227.25 | 0.00 |
| November | 1557.94 | 03-NOV-16:10 | 617.50 | 434.00 | 2943.11 | 0.00 | 0.00 | 0.00 | 0.00 | 110.01 | 0.00 |
| December | 1430.80 | 10-DEC-14:50 | 59.38 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 171.61 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 1219.68 | 59.38 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 87.39 | 0.00 | |
| Maximum of Months | 2337.02 | 864.50 | 607.59 | 4120.36 | 0.00 | 0.00 | 0.00 | 0.00 | 318.56 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: T N2 APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 1222.39 | 02-JAN-15:00 | 59.38 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 87.39 | 0.00 |
| February | 1540.58 | 11-FEB-14:40 | 59.38 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 115.19 | 0.00 |
| March | 1703.69 | 13-MAR-16:40 | 123.50 | 86.80 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 180.66 | 0.00 |
| April | 2000.41 | 15-APR-16:20 | 247.00 | 173.60 | 1177.25 | 0.00 | 0.00 | 0.00 | 0.00 | 199.46 | 0.00 |
| May | 2305.69 | 29-MAY-16:20 | 247.00 | 173.60 | 1177.25 | 0.00 | 0.00 | 0.00 | 0.00 | 321.46 | 0.00 |
| June | 2163.13 | 14-JUN-17:17 | 619.87 | 351.55 | 1765.87 | 0.00 | 0.00 | 0.00 | 0.00 | 211.28 | 0.00 |
| July | 2330.28 | 29-JUL-16:13 | 370.50 | 260.40 | 1765.87 | 0.00 | 0.00 | 0.00 | 0.00 | 171.59 | 0.00 |
| August | 2086.01 | 06-AUG-15:10 | 71.25 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 206.46 | 0.00 |
| September | 2039.40 | 18-SEP-16:03 | 864.50 | 607.59 | 4120.36 | 0.00 | 0.00 | 0.00 | 0.00 | 236.38 | 0.00 |
| October | 1892.58 | 03-OCT-16:03 | 741.00 | 520.80 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 227.25 | 0.00 |
| November | 1556.69 | 03-NOV-14:10 | 59.38 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 119.17 | 0.00 |
| December | 1428.38 | 10-DEC-14:50 | 59.38 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 171.61 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 1222.39 | 59.38 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 87.39 | 0.00 | |
| Maximum of Months | 2330.28 | 864.50 | 607.59 | 4120.36 | 0.00 | 0.00 | 0.00 | 0.00 | 321.46 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: T S1 APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 2658.43 | 02-JAN-14:30 | 118.75 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 59.70 | 0.00 |
| February | 2562.68 | 11-FEB-14:30 | 118.75 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 114.07 | 0.00 |
| March | 2109.43 | 04-MAR-13:50 | 118.75 | 17.36 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 146.31 | 0.00 |
| April | 2255.52 | 15-APR-16:05 | 950.00 | 347.20 | 2354.49 | 0.00 | 0.00 | 0.00 | 0.00 | 193.95 | 0.00 |
| May | 2308.67 | 29-MAY-16:04 | 1187.50 | 434.00 | 2943.11 | 0.00 | 0.00 | 0.00 | 0.00 | 323.92 | 0.00 |
| June | 2144.51 | 03-JUN-16:07 | 712.50 | 260.40 | 1765.87 | 0.00 | 0.00 | 0.00 | 0.00 | 153.98 | 0.00 |
| July | 2445.34 | 29-JUL-16:03 | 1425.00 | 520.80 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 174.56 | 0.00 |
| August | 2358.83 | 31-AUG-15:10 | 0.00 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 143.94 | 0.00 |
| September | 2695.88 | 30-SEP-14:00 | 118.75 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 159.45 | 0.00 |
| October | 2679.04 | 29-OCT-13:50 | 118.75 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 195.57 | 0.00 |
| November | 2663.55 | 22-NOV-12:40 | 0.00 | 17.36 | 406.15 | 0.00 | 0.00 | 0.00 | 0.00 | 143.04 | 0.00 |
| December | 2562.89 | 10-DEC-14:30 | 118.75 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 168.09 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 2109.43 | 0.00 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 59.70 | 0.00 | |
| Maximum of Months | 2695.88 | 1425.00 | 520.80 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 323.92 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: T S2 APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 2662.74 | 02-JAN-14:30 | 118.75 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 59.70 | 0.00 |
| February | 2562.78 | 11-FEB-14:30 | 118.75 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 114.07 | 0.00 |
| March | 2114.67 | 04-MAR-13:50 | 118.75 | 17.36 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 146.31 | 0.00 |
| April | 2248.17 | 15-APR-16:05 | 950.00 | 347.20 | 2354.49 | 0.00 | 0.00 | 0.00 | 0.00 | 193.95 | 0.00 |
| May | 2299.90 | 29-MAY-16:04 | 1187.50 | 434.00 | 2943.11 | 0.00 | 0.00 | 0.00 | 0.00 | 323.92 | 0.00 |
| June | 2140.35 | 03-JUN-16:07 | 712.50 | 260.40 | 1765.87 | 0.00 | 0.00 | 0.00 | 0.00 | 153.98 | 0.00 |
| July | 2439.23 | 29-JUL-16:03 | 1425.00 | 520.80 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 174.56 | 0.00 |
| August | 2355.51 | 31-AUG-15:10 | 0.00 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 143.94 | 0.00 |
| September | 2698.67 | 30-SEP-14:00 | 118.75 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 159.45 | 0.00 |
| October | 2680.68 | 29-OCT-13:40 | 118.75 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 191.28 | 0.00 |
| November | 2674.72 | 22-NOV-12:40 | 0.00 | 17.36 | 406.15 | 0.00 | 0.00 | 0.00 | 0.00 | 143.04 | 0.00 |
| December | 2564.07 | 09-DEC-12:40 | 118.75 | 17.36 | 406.15 | 0.00 | 0.00 | 0.00 | 0.00 | 73.55 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 2114.67 | 0.00 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 59.70 | 0.00 | |
| Maximum of Months | 2698.67 | 1425.00 | 520.80 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 323.92 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: T CORRIDOR
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 0.00 | 01-JAN-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 01-FEB-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.84 |
| March | 0.00 | 01-MAR-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.23 |
| April | 0.00 | 01-APR-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.71 |
| May | 0.00 | 01-MAY-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.72 |
| June | 0.00 | 01-JUN-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.80 | 0.00 |
| July | 0.00 | 01-JUL-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.20 | 0.00 |
| August | 0.00 | 01-AUG-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.69 | 0.00 |
| September | 0.00 | 01-SEP-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.31 | 0.00 |
| October | 0.00 | 01-OCT-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 0.00 |
| November | 0.00 | 01-NOV-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.22 |
| December | 0.00 | 01-DEC-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.78 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
| Minimum of Months | 0.00 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.69 | 41.84 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: G CORRIDOR
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 0.00 | 01-JAN-00:10 | 397.10 | 370.63 | 56.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 01-FEB-00:10 | 397.10 | 370.63 | 56.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.05 |
| March | 0.00 | 01-MAR-00:10 | 397.10 | 370.63 | 56.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.31 |
| April | 0.00 | 01-APR-00:10 | 397.10 | 370.63 | 56.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.70 |
| May | 0.00 | 01-MAY-00:10 | 397.10 | 370.63 | 56.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.77 |
| June | 0.00 | 01-JUN-00:10 | 397.10 | 370.63 | 56.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.20 |
| July | 0.00 | 01-JUL-00:10 | 397.10 | 370.63 | 56.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
| August | 0.00 | 01-AUG-00:10 | 397.10 | 370.63 | 56.17 | 0.00 | 0.00 | 0.00 | 0.00 | 2.74 | 0.00 |
| September | 0.00 | 01-SEP-00:10 | 397.10 | 370.63 | 56.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.21 | 0.00 |
| October | 0.00 | 01-OCT-00:10 | 397.10 | 370.63 | 56.17 | 0.00 | 0.00 | 0.00 | 0.00 | 1.36 | 0.00 |
| November | 0.00 | 01-NOV-00:10 | 397.10 | 370.63 | 56.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.81 |
| December | 0.00 | 01-DEC-00:10 | 397.10 | 370.63 | 56.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.64 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 0.00 | 397.10 | 370.63 | 56.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 397.10 | 370.63 | 56.17 | 0.00 | 0.00 | 0.00 | 0.00 | 2.74 | 27.05 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: M CORRIDOR
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 0.00 | 01-JAN-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 01-FEB-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.27 |
| March | 0.00 | 01-MAR-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.45 |
| April | 0.00 | 01-APR-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.24 |
| May | 0.00 | 01-MAY-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.13 |
| June | 0.00 | 01-JUN-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.54 | 0.00 |
| July | 0.00 | 01-JUL-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.01 | 0.00 |
| August | 0.00 | 01-AUG-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.26 | 0.00 |
| September | 0.00 | 01-SEP-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.88 | 0.00 |
| October | 0.00 | 01-OCT-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.01 | 0.00 |
| November | 0.00 | 01-NOV-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.95 |
| December | 0.00 | 01-DEC-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.22 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
| Minimum of Months | 0.00 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.26 | 39.27 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
| January | 0.107533E+12 | 86333.99 | 01-JAN-18:19 | 0.270721E+09 | 7099.66 | 25-JAN-06:00 |
| February | 0.101135E+12 | 76768.03 | 07-FEB-18:10 | 0.625810E+09 | 15306.27 | 04-FEB-06:00 |
| March | 0.114436E+12 | 81041.63 | 13-MAR-17:30 | 0.347235E+09 | 10640.57 | 16-MAR-05:00 |
| April | 0.118938E+12 | 84048.63 | 15-APR-16:40 | 0.00 | 0.00 | 01-APR-00:10 |
| May | 0.135043E+12 | 88293.22 | 29-MAY-17:30 | 0.00 | 0.00 | 01-MAY-00:10 |
| June | 0.137057E+12 | 89626.01 | 29-JUN-16:30 | 0.00 | 0.00 | 01-JUN-00:10 |
| July | 0.143141E+12 | 92145.00 | 27-JUL-17:40 | 0.00 | 0.00 | 01-JUL-00:10 |
| August | 0.143222E+12 | 90350.32 | 21-AUG-16:10 | 0.00 | 0.00 | 01-AUG-00:10 |
| September | 0.138348E+12 | 91926.13 | 18-SEP-17:00 | 0.00 | 0.00 | 01-SEP-00:10 |
| October | 0.137136E+12 | 91101.00 | 03-OCT-16:19 | 0.00 | 0.00 | 01-OCT-00:10 |
| November | 0.120989E+12 | 86483.78 | 03-NOV-17:49 | 92493998.54 | 3954.18 | 13-NOV-05:00 |
| December | 0.111462E+12 | 79034.92 | 09-DEC-17:00 | 0.517139E+09 | 8878.93 | 15-DEC-05:00 |
| Annual Sum or Average | 0.150844E+13 | 0.185340E+10 | ||||
| Minimum of Months | 0.101135E+12 | 76768.03 | 0.00 | 0.00 | ||
| Maximum of Months | 0.143222E+12 | 92145.00 | 0.625810E+09 | 15306.27 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| INTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [J] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
| January | 0.840929E+10 | 0.477881E+10 | 0.389380E+11 | 0.00 | 0.819473E+10 | 0.00 | 0.00 | 0.148647E+11 | 0.00 | 0.00 | 0.00 | 0.323473E+11 | 0.00 |
| February | 0.760941E+10 | 0.412369E+10 | 0.351823E+11 | 0.00 | 0.829515E+10 | 0.00 | 0.00 | 0.169017E+11 | 0.00 | 0.00 | 0.00 | 0.290226E+11 | 0.00 |
| March | 0.845392E+10 | 0.430514E+10 | 0.389781E+11 | 0.00 | 0.985303E+10 | 0.00 | 0.00 | 0.214177E+11 | 0.00 | 0.00 | 0.00 | 0.314284E+11 | 0.00 |
| April | 0.814762E+10 | 0.391168E+10 | 0.376905E+11 | 0.00 | 0.113977E+11 | 0.00 | 0.00 | 0.283695E+11 | 0.00 | 0.00 | 0.00 | 0.294210E+11 | 0.00 |
| May | 0.843904E+10 | 0.381236E+10 | 0.389647E+11 | 0.00 | 0.142850E+11 | 0.00 | 0.00 | 0.401988E+11 | 0.00 | 0.00 | 0.00 | 0.293430E+11 | 0.00 |
| June | 0.817737E+10 | 0.358507E+10 | 0.377173E+11 | 0.00 | 0.151041E+11 | 0.00 | 0.00 | 0.448473E+11 | 0.00 | 0.00 | 0.00 | 0.276257E+11 | 0.00 |
| July | 0.840929E+10 | 0.373787E+10 | 0.389380E+11 | 0.00 | 0.159110E+11 | 0.00 | 0.00 | 0.479395E+11 | 0.00 | 0.00 | 0.00 | 0.282051E+11 | 0.00 |
| August | 0.845392E+10 | 0.394033E+10 | 0.389781E+11 | 0.00 | 0.158213E+11 | 0.00 | 0.00 | 0.476017E+11 | 0.00 | 0.00 | 0.00 | 0.284270E+11 | 0.00 |
| September | 0.814762E+10 | 0.405875E+10 | 0.376905E+11 | 0.00 | 0.151514E+11 | 0.00 | 0.00 | 0.450967E+11 | 0.00 | 0.00 | 0.00 | 0.282028E+11 | 0.00 |
| October | 0.842417E+10 | 0.445794E+10 | 0.389514E+11 | 0.00 | 0.143888E+11 | 0.00 | 0.00 | 0.407434E+11 | 0.00 | 0.00 | 0.00 | 0.301706E+11 | 0.00 |
| November | 0.814762E+10 | 0.454962E+10 | 0.376905E+11 | 0.00 | 0.114677E+11 | 0.00 | 0.00 | 0.289113E+11 | 0.00 | 0.00 | 0.00 | 0.302223E+11 | 0.00 |
| December | 0.840929E+10 | 0.482847E+10 | 0.389380E+11 | 0.00 | 0.904365E+10 | 0.00 | 0.00 | 0.182116E+11 | 0.00 | 0.00 | 0.00 | 0.320309E+11 | 0.00 |
| Annual Sum or Average | 0.992286E+11 | 0.500897E+11 | 0.458657E+12 | 0.00 | 0.148914E+12 | 0.00 | 0.00 | 0.395104E+12 | 0.00 | 0.00 | 0.00 | 0.356447E+12 | 0.00 |
| Minimum of Months | 0.760941E+10 | 0.358507E+10 | 0.351823E+11 | 0.00 | 0.819473E+10 | 0.00 | 0.00 | 0.148647E+11 | 0.00 | 0.00 | 0.00 | 0.276257E+11 | 0.00 |
| Maximum of Months | 0.845392E+10 | 0.482847E+10 | 0.389781E+11 | 0.00 | 0.159110E+11 | 0.00 | 0.00 | 0.479395E+11 | 0.00 | 0.00 | 0.00 | 0.323473E+11 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| INTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
| January | 0.00 | 0.00 | 0.270721E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.625810E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.347235E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 92493998.54 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.517139E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.185340E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.625810E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| INTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
| January | 5904.43 | 01-JAN-19:10 | 3183.33 | 01-JAN-00:10 | 22709.69 | 03-JAN-17:10 | 0.00 | 6754.63 | 02-JAN-14:00 | 0.00 | 0.00 | 01-JAN-00:10 |
| February | 5904.43 | 01-FEB-19:10 | 3183.33 | 01-FEB-00:10 | 22709.69 | 01-FEB-17:10 | 0.00 | 7111.36 | 11-FEB-14:30 | 0.00 | 0.00 | 01-FEB-00:10 |
| March | 5904.43 | 01-MAR-19:10 | 3183.33 | 01-MAR-00:10 | 22709.69 | 01-MAR-17:10 | 0.00 | 7009.95 | 13-MAR-16:30 | 0.00 | 0.00 | 01-MAR-00:10 |
| April | 5904.43 | 01-APR-18:10 | 3183.33 | 01-APR-00:10 | 22709.69 | 03-APR-16:10 | 0.00 | 7604.86 | 15-APR-16:30 | 0.00 | 0.00 | 01-APR-00:10 |
| May | 5904.43 | 01-MAY-18:10 | 3183.33 | 01-MAY-00:10 | 22709.69 | 01-MAY-16:10 | 0.00 | 8436.83 | 29-MAY-16:10 | 0.00 | 0.00 | 01-MAY-00:10 |
| June | 5904.43 | 01-JUN-18:10 | 3183.33 | 01-JUN-00:10 | 22709.69 | 01-JUN-16:10 | 0.00 | 8079.07 | 08-JUN-16:10 | 0.00 | 0.00 | 01-JUN-00:10 |
| July | 5904.43 | 01-JUL-18:10 | 3183.33 | 01-JUL-00:10 | 22709.69 | 03-JUL-16:10 | 0.00 | 8544.64 | 27-JUL-16:10 | 0.00 | 0.00 | 01-JUL-00:10 |
| August | 5904.43 | 01-AUG-18:10 | 3183.33 | 01-AUG-00:10 | 22709.69 | 01-AUG-16:10 | 0.00 | 8258.27 | 16-AUG-16:10 | 0.00 | 0.00 | 01-AUG-00:10 |
| September | 5904.43 | 01-SEP-18:10 | 3183.33 | 01-SEP-00:10 | 22709.69 | 01-SEP-16:10 | 0.00 | 8434.59 | 18-SEP-16:10 | 0.00 | 0.00 | 01-SEP-00:10 |
| October | 5904.43 | 01-OCT-18:10 | 3183.33 | 01-OCT-00:10 | 22709.69 | 02-OCT-16:10 | 0.00 | 8237.03 | 29-OCT-14:09 | 0.00 | 0.00 | 01-OCT-00:10 |
| November | 5904.43 | 01-NOV-18:10 | 3183.33 | 01-NOV-00:10 | 22709.69 | 01-NOV-16:10 | 0.00 | 7205.57 | 03-NOV-13:30 | 0.00 | 0.00 | 01-NOV-00:10 |
| December | 5904.43 | 01-DEC-19:10 | 3183.33 | 01-DEC-00:10 | 22709.69 | 01-DEC-17:10 | 0.00 | 7237.43 | 10-DEC-14:39 | 0.00 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 5904.43 | 3183.33 | 22709.69 | 0.00 | 6754.63 | 0.00 | 0.00 | |||||
| Maximum of Months | 5904.43 | 3183.33 | 22709.69 | 0.00 | 8544.64 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| COOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY {Maximum} [W] | HEATRECOVERY:ELECTRICITY {TIMESTAMP} | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
| January | 21097.50 | 02-JAN-14:00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 37016.31 | 08-JAN-07:19 | 0.00 |
| February | 22437.30 | 11-FEB-13:00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 30985.58 | 11-FEB-07:00 | 0.00 |
| March | 22546.91 | 13-MAR-15:30 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 29987.94 | 19-MAR-05:19 | 0.00 |
| April | 25051.34 | 15-APR-16:30 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 28538.92 | 24-APR-06:10 | 0.00 |
| May | 29254.72 | 29-MAY-16:10 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 29264.12 | 31-MAY-06:19 | 0.00 |
| June | 27423.45 | 08-JUN-15:00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 29261.02 | 02-JUN-06:30 | 0.00 |
| July | 30617.47 | 27-JUL-15:00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 29220.21 | 10-JUL-06:10 | 0.00 |
| August | 29491.02 | 22-AUG-12:00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 30745.83 | 30-AUG-06:19 | 0.00 |
| September | 30349.50 | 20-SEP-13:00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 30012.65 | 22-SEP-06:00 | 0.00 |
| October | 28756.96 | 03-OCT-14:30 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 29375.98 | 27-OCT-06:49 | 0.00 |
| November | 24161.17 | 03-NOV-12:00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 29401.56 | 07-NOV-07:10 | 0.00 |
| December | 23087.43 | 10-DEC-14:30 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 30969.86 | 25-DEC-07:00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
| Minimum of Months | 21097.50 | 0.00 | 0.00 | 0.00 | 28538.92 | 0.00 | |||
| Maximum of Months | 30617.47 | 0.00 | 0.00 | 0.00 | 37016.31 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
| January | 86333.99 | 01-JAN-18:19 | 5231.74 | 22609.62 | 3183.33 | 0.00 | 5148.77 | 0.00 | 0.00 | 13405.26 | 0.00 |
| February | 76768.03 | 07-FEB-18:10 | 5231.74 | 22609.62 | 3183.33 | 0.00 | 4839.36 | 0.00 | 0.00 | 12156.78 | 0.00 |
| March | 81041.63 | 13-MAR-17:30 | 5231.74 | 22609.62 | 0.00 | 0.00 | 6663.15 | 0.00 | 0.00 | 20355.40 | 0.00 |
| April | 84048.63 | 15-APR-16:40 | 4289.87 | 22609.62 | 0.00 | 0.00 | 7604.36 | 0.00 | 0.00 | 25047.46 | 0.00 |
| May | 88293.22 | 29-MAY-17:30 | 5231.74 | 22609.62 | 0.00 | 0.00 | 8179.39 | 0.00 | 0.00 | 27652.43 | 0.00 |
| June | 89626.01 | 29-JUN-16:30 | 4289.87 | 22709.69 | 0.00 | 0.00 | 7869.29 | 0.00 | 0.00 | 26348.44 | 0.00 |
| July | 92145.00 | 27-JUL-17:40 | 5231.74 | 22609.62 | 0.00 | 0.00 | 8308.97 | 0.00 | 0.00 | 28417.75 | 0.00 |
| August | 90350.32 | 21-AUG-16:10 | 4289.87 | 22709.69 | 0.00 | 0.00 | 8022.49 | 0.00 | 0.00 | 27347.17 | 0.00 |
| September | 91926.13 | 18-SEP-17:00 | 5231.74 | 22609.62 | 0.00 | 0.00 | 8034.16 | 0.00 | 0.00 | 26947.51 | 0.00 |
| October | 91101.00 | 03-OCT-16:19 | 4289.87 | 22709.69 | 0.00 | 0.00 | 8023.46 | 0.00 | 0.00 | 27119.73 | 0.00 |
| November | 86483.78 | 03-NOV-17:49 | 5231.74 | 22609.62 | 3183.33 | 0.00 | 6528.39 | 0.00 | 0.00 | 19737.89 | 0.00 |
| December | 79034.92 | 09-DEC-17:00 | 4289.87 | 22609.62 | 3183.33 | 0.00 | 5755.30 | 0.00 | 0.00 | 15945.60 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
| Minimum of Months | 76768.03 | 4289.87 | 22609.62 | 0.00 | 0.00 | 4839.36 | 0.00 | 0.00 | 12156.78 | 0.00 | |
| Maximum of Months | 92145.00 | 5231.74 | 22709.69 | 3183.33 | 0.00 | 8308.97 | 0.00 | 0.00 | 28417.75 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| INTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | |
| January | 0.00 | 0.00 | 7099.66 | 25-JAN-06:00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 15306.27 | 04-FEB-06:00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 10640.57 | 16-MAR-05:00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 3954.18 | 13-NOV-05:00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 8878.93 | 15-DEC-05:00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 15306.27 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: G SW APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: G NW APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: OFFICE
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.61 | 0.17 | 24.61 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.17 | 24.61 | 0.17 | 24.61 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.61 | 0.17 | 24.61 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: G NE APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: G N1 APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: G N2 APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: G S1 APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: G S2 APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: M SW APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: M NW APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: M SE APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: M NE APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: M N1 APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: M N2 APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: M S1 APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: M S2 APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: T SW APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: T NW APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: T SE APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: T NE APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: T N1 APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: T N2 APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: T S1 APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: T S2 APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: T CORRIDOR
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: G CORRIDOR
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: M CORRIDOR
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: G SW APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 103.50 | 23.88 | 354.33 | 23.97 | 49.17 | 23.97 |
| February | 138.33 | 23.72 | 307.67 | 23.91 | 80.50 | 23.92 |
| March | 169.83 | 23.82 | 359.83 | 23.94 | 111.17 | 23.95 |
| April | 79.83 | 24.00 | 458.17 | 24.00 | 79.00 | 24.00 |
| May | 222.83 | 24.00 | 515.00 | 24.00 | 222.83 | 24.00 |
| June | 302.50 | 24.00 | 492.00 | 24.00 | 302.50 | 24.00 |
| July | 223.17 | 24.00 | 533.00 | 24.00 | 223.17 | 24.00 |
| August | 253.67 | 24.00 | 506.00 | 24.00 | 253.67 | 24.00 |
| September | 168.83 | 24.00 | 510.00 | 24.00 | 168.83 | 24.00 |
| October | 156.33 | 24.00 | 524.00 | 24.00 | 156.33 | 24.00 |
| November | 148.00 | 23.97 | 437.67 | 23.99 | 129.83 | 23.99 |
| December | 161.00 | 23.88 | 408.00 | 23.97 | 120.67 | 23.97 |
| Annual Sum or Average | 2127.83 | 23.95 | 5405.67 | 23.99 | 1897.67 | 23.99 |
| Minimum of Months | 79.83 | 23.72 | 307.67 | 23.91 | 49.17 | 23.92 |
| Maximum of Months | 302.50 | 24.00 | 533.00 | 24.00 | 302.50 | 24.00 |
Report: ComfortReportSimple55Monthly
For: G NW APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 273.50 | 23.70 | 369.67 | 23.87 | 102.50 | 23.89 |
| February | 267.17 | 23.63 | 390.00 | 23.85 | 141.33 | 23.87 |
| March | 318.83 | 23.71 | 470.67 | 23.88 | 179.17 | 23.90 |
| April | 103.83 | 24.00 | 642.00 | 24.00 | 102.33 | 24.00 |
| May | 262.17 | 24.00 | 744.00 | 24.00 | 262.17 | 24.00 |
| June | 357.83 | 24.00 | 720.00 | 24.00 | 357.83 | 24.00 |
| July | 274.50 | 24.00 | 744.00 | 24.00 | 274.50 | 24.00 |
| August | 350.50 | 24.00 | 744.00 | 24.00 | 350.50 | 24.00 |
| September | 289.17 | 24.00 | 720.00 | 24.00 | 289.17 | 24.00 |
| October | 283.00 | 24.00 | 744.00 | 24.00 | 283.00 | 24.00 |
| November | 273.33 | 23.95 | 605.00 | 23.98 | 241.17 | 23.99 |
| December | 310.33 | 23.78 | 471.67 | 23.91 | 201.83 | 23.93 |
| Annual Sum or Average | 3364.17 | 23.89 | 7365.00 | 23.97 | 2785.50 | 23.97 |
| Minimum of Months | 103.83 | 23.63 | 369.67 | 23.85 | 102.33 | 23.87 |
| Maximum of Months | 357.83 | 24.00 | 744.00 | 24.00 | 357.83 | 24.00 |
Report: ComfortReportSimple55Monthly
For: OFFICE
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 5.00 | 25.55 | 128.33 | 24.28 | 4.83 | 24.33 |
| February | 8.17 | 25.37 | 125.67 | 24.30 | 8.17 | 24.36 |
| March | 13.33 | 25.10 | 134.00 | 24.31 | 11.83 | 24.38 |
| April | 11.17 | 25.45 | 140.00 | 24.33 | 11.17 | 24.40 |
| May | 25.00 | 25.37 | 154.00 | 24.40 | 25.00 | 24.52 |
| June | 31.33 | 25.23 | 154.00 | 24.42 | 31.33 | 24.53 |
| July | 27.50 | 25.28 | 140.00 | 24.42 | 27.50 | 24.54 |
| August | 31.50 | 25.28 | 161.00 | 24.42 | 31.50 | 24.54 |
| September | 26.33 | 25.33 | 140.00 | 24.42 | 26.33 | 24.55 |
| October | 22.33 | 25.40 | 147.00 | 24.40 | 22.33 | 24.52 |
| November | 18.33 | 25.41 | 140.00 | 24.38 | 18.33 | 24.49 |
| December | 6.17 | 25.41 | 133.50 | 24.28 | 6.00 | 24.33 |
| Annual Sum or Average | 226.17 | 25.32 | 1697.50 | 24.37 | 224.33 | 24.47 |
| Minimum of Months | 5.00 | 25.10 | 125.67 | 24.28 | 4.83 | 24.33 |
| Maximum of Months | 31.50 | 25.55 | 161.00 | 24.42 | 31.50 | 24.55 |
Report: ComfortReportSimple55Monthly
For: G NE APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 250.67 | 23.71 | 375.83 | 23.88 | 91.17 | 23.90 |
| February | 259.50 | 23.63 | 388.33 | 23.85 | 137.00 | 23.88 |
| March | 307.83 | 23.75 | 471.33 | 23.90 | 173.33 | 23.92 |
| April | 100.83 | 24.00 | 643.83 | 24.00 | 99.67 | 24.00 |
| May | 258.83 | 24.00 | 744.00 | 24.00 | 258.83 | 24.00 |
| June | 302.50 | 24.00 | 720.00 | 24.00 | 302.50 | 24.00 |
| July | 238.17 | 24.00 | 744.00 | 24.00 | 238.17 | 24.00 |
| August | 316.83 | 24.00 | 744.00 | 24.00 | 316.83 | 24.00 |
| September | 238.67 | 24.00 | 720.00 | 24.00 | 238.67 | 24.00 |
| October | 262.50 | 24.00 | 744.00 | 24.00 | 262.50 | 24.00 |
| November | 261.33 | 23.95 | 604.00 | 23.99 | 231.50 | 23.99 |
| December | 311.67 | 23.78 | 468.83 | 23.91 | 203.83 | 23.93 |
| Annual Sum or Average | 3109.33 | 23.90 | 7368.17 | 23.97 | 2554.00 | 23.97 |
| Minimum of Months | 100.83 | 23.63 | 375.83 | 23.85 | 91.17 | 23.88 |
| Maximum of Months | 316.83 | 24.00 | 744.00 | 24.00 | 316.83 | 24.00 |
Report: ComfortReportSimple55Monthly
For: G N1 APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 202.67 | 23.82 | 371.83 | 23.94 | 78.83 | 23.94 |
| February | 231.00 | 23.76 | 385.83 | 23.91 | 115.50 | 23.92 |
| March | 274.00 | 23.82 | 456.17 | 23.93 | 160.33 | 23.94 |
| April | 86.50 | 24.00 | 637.17 | 24.00 | 86.50 | 24.00 |
| May | 247.17 | 24.00 | 744.00 | 24.00 | 247.17 | 24.00 |
| June | 365.17 | 24.00 | 720.00 | 24.00 | 365.17 | 24.00 |
| July | 299.00 | 24.00 | 744.00 | 24.00 | 299.00 | 24.00 |
| August | 394.33 | 24.00 | 744.00 | 24.00 | 394.33 | 24.00 |
| September | 314.67 | 24.00 | 720.00 | 24.00 | 314.67 | 24.00 |
| October | 284.50 | 24.00 | 744.00 | 24.00 | 284.50 | 24.00 |
| November | 256.33 | 23.98 | 598.83 | 23.99 | 231.50 | 24.00 |
| December | 270.67 | 23.88 | 480.33 | 23.96 | 192.17 | 23.96 |
| Annual Sum or Average | 3226.00 | 23.95 | 7346.17 | 23.98 | 2769.67 | 23.99 |
| Minimum of Months | 86.50 | 23.76 | 371.83 | 23.91 | 78.83 | 23.92 |
| Maximum of Months | 394.33 | 24.00 | 744.00 | 24.00 | 394.33 | 24.00 |
Report: ComfortReportSimple55Monthly
For: G N2 APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 200.17 | 23.82 | 372.17 | 23.94 | 78.33 | 23.95 |
| February | 230.83 | 23.76 | 386.00 | 23.91 | 115.17 | 23.92 |
| March | 272.67 | 23.82 | 456.17 | 23.93 | 159.50 | 23.95 |
| April | 86.83 | 24.00 | 636.50 | 24.00 | 86.83 | 24.00 |
| May | 247.50 | 24.00 | 744.00 | 24.00 | 247.50 | 24.00 |
| June | 362.67 | 24.00 | 720.00 | 24.00 | 362.67 | 24.00 |
| July | 297.83 | 24.00 | 744.00 | 24.00 | 297.83 | 24.00 |
| August | 393.83 | 24.00 | 744.00 | 24.00 | 393.83 | 24.00 |
| September | 313.67 | 24.00 | 720.00 | 24.00 | 313.67 | 24.00 |
| October | 284.50 | 24.00 | 744.00 | 24.00 | 284.50 | 24.00 |
| November | 257.33 | 23.98 | 598.83 | 23.99 | 232.33 | 24.00 |
| December | 271.50 | 23.88 | 479.83 | 23.96 | 192.33 | 23.96 |
| Annual Sum or Average | 3219.33 | 23.95 | 7345.50 | 23.98 | 2764.50 | 23.99 |
| Minimum of Months | 86.83 | 23.76 | 372.17 | 23.91 | 78.33 | 23.92 |
| Maximum of Months | 393.83 | 24.00 | 744.00 | 24.00 | 393.83 | 24.00 |
Report: ComfortReportSimple55Monthly
For: G S1 APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 67.00 | 23.97 | 364.67 | 24.00 | 31.50 | 24.00 |
| February | 102.83 | 23.84 | 301.83 | 23.96 | 59.00 | 23.97 |
| March | 138.50 | 23.92 | 357.17 | 23.98 | 92.33 | 23.98 |
| April | 62.83 | 24.00 | 456.83 | 24.00 | 62.83 | 24.00 |
| May | 208.17 | 24.00 | 515.00 | 24.00 | 208.17 | 24.00 |
| June | 305.00 | 24.00 | 492.00 | 24.00 | 305.00 | 24.00 |
| July | 238.00 | 24.00 | 533.00 | 24.00 | 238.00 | 24.00 |
| August | 279.50 | 24.00 | 506.00 | 24.00 | 279.50 | 24.00 |
| September | 176.33 | 24.00 | 510.00 | 24.00 | 176.33 | 24.00 |
| October | 140.83 | 24.00 | 524.00 | 24.00 | 140.83 | 24.00 |
| November | 118.00 | 24.00 | 441.50 | 24.00 | 111.17 | 24.00 |
| December | 96.00 | 23.97 | 417.00 | 23.99 | 81.17 | 23.99 |
| Annual Sum or Average | 1933.00 | 23.98 | 5419.00 | 24.00 | 1785.83 | 24.00 |
| Minimum of Months | 62.83 | 23.84 | 301.83 | 23.96 | 31.50 | 23.97 |
| Maximum of Months | 305.00 | 24.00 | 533.00 | 24.00 | 305.00 | 24.00 |
Report: ComfortReportSimple55Monthly
For: G S2 APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 55.00 | 23.98 | 374.17 | 24.00 | 23.00 | 24.00 |
| February | 76.17 | 23.81 | 321.17 | 23.96 | 37.17 | 23.97 |
| March | 121.50 | 23.93 | 364.17 | 23.98 | 80.00 | 23.98 |
| April | 39.33 | 24.00 | 461.50 | 24.00 | 39.33 | 24.00 |
| May | 150.17 | 24.00 | 515.00 | 24.00 | 150.17 | 24.00 |
| June | 236.17 | 24.00 | 492.00 | 24.00 | 236.17 | 24.00 |
| July | 165.83 | 24.00 | 533.00 | 24.00 | 165.83 | 24.00 |
| August | 189.83 | 24.00 | 506.00 | 24.00 | 189.83 | 24.00 |
| September | 90.83 | 24.00 | 510.00 | 24.00 | 90.83 | 24.00 |
| October | 89.00 | 24.00 | 524.00 | 24.00 | 89.00 | 24.00 |
| November | 89.67 | 24.00 | 449.50 | 24.00 | 85.33 | 24.00 |
| December | 66.83 | 23.97 | 424.00 | 24.00 | 55.33 | 24.00 |
| Annual Sum or Average | 1370.33 | 23.98 | 5474.50 | 24.00 | 1242.00 | 24.00 |
| Minimum of Months | 39.33 | 23.81 | 321.17 | 23.96 | 23.00 | 23.97 |
| Maximum of Months | 236.17 | 24.00 | 533.00 | 24.00 | 236.17 | 24.00 |
Report: ComfortReportSimple55Monthly
For: M SW APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 157.33 | 23.80 | 314.33 | 23.93 | 75.33 | 23.94 |
| February | 165.17 | 23.66 | 293.83 | 23.88 | 98.33 | 23.90 |
| March | 170.00 | 23.80 | 362.67 | 23.93 | 114.67 | 23.95 |
| April | 82.00 | 24.00 | 457.67 | 24.00 | 81.00 | 24.00 |
| May | 241.17 | 24.00 | 515.00 | 24.00 | 241.17 | 24.00 |
| June | 322.00 | 24.00 | 492.00 | 24.00 | 322.00 | 24.00 |
| July | 268.00 | 24.00 | 533.00 | 24.00 | 268.00 | 24.00 |
| August | 335.00 | 24.00 | 506.00 | 24.00 | 335.00 | 24.00 |
| September | 285.83 | 24.00 | 510.00 | 24.00 | 285.83 | 24.00 |
| October | 242.00 | 24.00 | 524.00 | 24.00 | 242.00 | 24.00 |
| November | 218.50 | 23.92 | 426.33 | 23.97 | 190.83 | 23.98 |
| December | 224.83 | 23.81 | 373.33 | 23.93 | 165.83 | 23.94 |
| Annual Sum or Average | 2711.83 | 23.93 | 5308.17 | 23.98 | 2420.00 | 23.98 |
| Minimum of Months | 82.00 | 23.66 | 293.83 | 23.88 | 75.33 | 23.90 |
| Maximum of Months | 335.00 | 24.00 | 533.00 | 24.00 | 335.00 | 24.00 |
Report: ComfortReportSimple55Monthly
For: M NW APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 333.17 | 23.61 | 355.83 | 23.81 | 125.00 | 23.84 |
| February | 284.67 | 23.53 | 385.33 | 23.80 | 152.33 | 23.84 |
| March | 301.00 | 23.67 | 488.50 | 23.88 | 174.50 | 23.90 |
| April | 104.67 | 24.00 | 641.83 | 24.00 | 103.17 | 24.00 |
| May | 291.50 | 24.00 | 744.00 | 24.00 | 291.50 | 24.00 |
| June | 403.17 | 24.00 | 720.00 | 24.00 | 403.17 | 24.00 |
| July | 345.50 | 24.00 | 744.00 | 24.00 | 345.50 | 24.00 |
| August | 467.50 | 24.00 | 744.00 | 24.00 | 467.50 | 24.00 |
| September | 408.00 | 24.00 | 720.00 | 24.00 | 408.00 | 24.00 |
| October | 375.67 | 24.00 | 744.00 | 24.00 | 375.67 | 24.00 |
| November | 372.83 | 23.91 | 593.50 | 23.97 | 321.33 | 23.97 |
| December | 392.67 | 23.66 | 457.00 | 23.84 | 233.67 | 23.87 |
| Annual Sum or Average | 4080.33 | 23.87 | 7338.00 | 23.95 | 3401.33 | 23.96 |
| Minimum of Months | 104.67 | 23.53 | 355.83 | 23.80 | 103.17 | 23.84 |
| Maximum of Months | 467.50 | 24.00 | 744.00 | 24.00 | 467.50 | 24.00 |
Report: ComfortReportSimple55Monthly
For: M SE APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 154.67 | 23.79 | 306.50 | 23.93 | 69.83 | 23.94 |
| February | 160.00 | 23.67 | 291.67 | 23.88 | 95.83 | 23.90 |
| March | 172.67 | 23.80 | 356.00 | 23.93 | 116.50 | 23.95 |
| April | 80.83 | 24.00 | 457.17 | 24.00 | 79.83 | 24.00 |
| May | 245.50 | 24.00 | 515.00 | 24.00 | 245.50 | 24.00 |
| June | 296.17 | 24.00 | 492.00 | 24.00 | 296.17 | 24.00 |
| July | 257.00 | 24.00 | 533.00 | 24.00 | 257.00 | 24.00 |
| August | 332.33 | 24.00 | 506.00 | 24.00 | 332.33 | 24.00 |
| September | 267.67 | 24.00 | 510.00 | 24.00 | 267.67 | 24.00 |
| October | 234.33 | 24.00 | 524.00 | 24.00 | 234.33 | 24.00 |
| November | 215.33 | 23.93 | 427.33 | 23.98 | 188.50 | 23.98 |
| December | 230.17 | 23.81 | 360.00 | 23.92 | 170.33 | 23.94 |
| Annual Sum or Average | 2646.67 | 23.93 | 5278.67 | 23.98 | 2353.83 | 23.98 |
| Minimum of Months | 80.83 | 23.67 | 291.67 | 23.88 | 69.83 | 23.90 |
| Maximum of Months | 332.33 | 24.00 | 533.00 | 24.00 | 332.33 | 24.00 |
Report: ComfortReportSimple55Monthly
For: M NE APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 313.00 | 23.64 | 363.00 | 23.83 | 118.83 | 23.86 |
| February | 277.33 | 23.54 | 381.67 | 23.80 | 147.67 | 23.84 |
| March | 286.17 | 23.72 | 482.17 | 23.90 | 170.17 | 23.92 |
| April | 101.50 | 24.00 | 644.33 | 24.00 | 100.50 | 24.00 |
| May | 284.33 | 24.00 | 744.00 | 24.00 | 284.33 | 24.00 |
| June | 345.83 | 24.00 | 720.00 | 24.00 | 345.83 | 24.00 |
| July | 307.83 | 24.00 | 744.00 | 24.00 | 307.83 | 24.00 |
| August | 445.17 | 24.00 | 744.00 | 24.00 | 445.17 | 24.00 |
| September | 371.50 | 24.00 | 720.00 | 24.00 | 371.50 | 24.00 |
| October | 360.67 | 24.00 | 744.00 | 24.00 | 360.67 | 24.00 |
| November | 358.00 | 23.92 | 592.67 | 23.97 | 310.33 | 23.98 |
| December | 399.67 | 23.67 | 452.33 | 23.84 | 231.33 | 23.87 |
| Annual Sum or Average | 3851.00 | 23.88 | 7332.17 | 23.96 | 3194.17 | 23.97 |
| Minimum of Months | 101.50 | 23.54 | 363.00 | 23.80 | 100.50 | 23.84 |
| Maximum of Months | 445.17 | 24.00 | 744.00 | 24.00 | 445.17 | 24.00 |
Report: ComfortReportSimple55Monthly
For: M N1 APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 248.50 | 23.79 | 360.50 | 23.92 | 97.83 | 23.93 |
| February | 247.00 | 23.69 | 377.67 | 23.87 | 122.83 | 23.90 |
| March | 261.83 | 23.81 | 468.83 | 23.93 | 158.67 | 23.94 |
| April | 90.33 | 24.00 | 633.17 | 24.00 | 90.33 | 24.00 |
| May | 267.50 | 24.00 | 744.00 | 24.00 | 267.50 | 24.00 |
| June | 403.17 | 24.00 | 720.00 | 24.00 | 403.17 | 24.00 |
| July | 363.67 | 24.00 | 744.00 | 24.00 | 363.67 | 24.00 |
| August | 498.83 | 24.00 | 744.00 | 24.00 | 498.83 | 24.00 |
| September | 414.67 | 24.00 | 720.00 | 24.00 | 414.67 | 24.00 |
| October | 373.83 | 24.00 | 744.00 | 24.00 | 373.83 | 24.00 |
| November | 339.33 | 23.96 | 589.67 | 23.99 | 300.67 | 23.99 |
| December | 332.67 | 23.83 | 459.33 | 23.93 | 215.83 | 23.94 |
| Annual Sum or Average | 3841.33 | 23.94 | 7305.17 | 23.98 | 3307.83 | 23.98 |
| Minimum of Months | 90.33 | 23.69 | 360.50 | 23.87 | 90.33 | 23.90 |
| Maximum of Months | 498.83 | 24.00 | 744.00 | 24.00 | 498.83 | 24.00 |
Report: ComfortReportSimple55Monthly
For: M N2 APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 247.17 | 23.80 | 360.50 | 23.92 | 97.33 | 23.93 |
| February | 246.33 | 23.69 | 378.33 | 23.87 | 122.33 | 23.90 |
| March | 260.50 | 23.81 | 469.17 | 23.93 | 158.00 | 23.94 |
| April | 90.33 | 24.00 | 633.00 | 24.00 | 90.33 | 24.00 |
| May | 267.67 | 24.00 | 744.00 | 24.00 | 267.67 | 24.00 |
| June | 402.50 | 24.00 | 720.00 | 24.00 | 402.50 | 24.00 |
| July | 363.33 | 24.00 | 744.00 | 24.00 | 363.33 | 24.00 |
| August | 497.83 | 24.00 | 744.00 | 24.00 | 497.83 | 24.00 |
| September | 413.33 | 24.00 | 720.00 | 24.00 | 413.33 | 24.00 |
| October | 372.83 | 24.00 | 744.00 | 24.00 | 372.83 | 24.00 |
| November | 339.33 | 23.96 | 589.50 | 23.99 | 300.33 | 23.99 |
| December | 332.83 | 23.83 | 459.00 | 23.93 | 216.33 | 23.94 |
| Annual Sum or Average | 3834.00 | 23.94 | 7305.50 | 23.98 | 3302.17 | 23.98 |
| Minimum of Months | 90.33 | 23.69 | 360.50 | 23.87 | 90.33 | 23.90 |
| Maximum of Months | 497.83 | 24.00 | 744.00 | 24.00 | 497.83 | 24.00 |
Report: ComfortReportSimple55Monthly
For: M S1 APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 98.83 | 23.94 | 316.33 | 23.99 | 50.50 | 23.99 |
| February | 126.00 | 23.82 | 291.17 | 23.95 | 74.33 | 23.95 |
| March | 145.00 | 23.91 | 353.67 | 23.97 | 98.67 | 23.98 |
| April | 67.83 | 24.00 | 455.50 | 24.00 | 67.83 | 24.00 |
| May | 227.33 | 24.00 | 515.00 | 24.00 | 227.33 | 24.00 |
| June | 329.17 | 24.00 | 492.00 | 24.00 | 329.17 | 24.00 |
| July | 283.33 | 24.00 | 533.00 | 24.00 | 283.33 | 24.00 |
| August | 359.50 | 24.00 | 506.00 | 24.00 | 359.50 | 24.00 |
| September | 279.33 | 24.00 | 510.00 | 24.00 | 279.33 | 24.00 |
| October | 222.67 | 24.00 | 524.00 | 24.00 | 222.67 | 24.00 |
| November | 176.67 | 23.98 | 427.17 | 23.99 | 157.00 | 23.99 |
| December | 159.33 | 23.92 | 388.50 | 23.98 | 123.00 | 23.98 |
| Annual Sum or Average | 2475.00 | 23.98 | 5312.33 | 23.99 | 2272.67 | 23.99 |
| Minimum of Months | 67.83 | 23.82 | 291.17 | 23.95 | 50.50 | 23.95 |
| Maximum of Months | 359.50 | 24.00 | 533.00 | 24.00 | 359.50 | 24.00 |
Report: ComfortReportSimple55Monthly
For: M S2 APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 98.83 | 23.94 | 316.33 | 23.99 | 50.50 | 23.99 |
| February | 126.00 | 23.82 | 291.33 | 23.95 | 74.33 | 23.95 |
| March | 145.33 | 23.91 | 353.00 | 23.97 | 98.83 | 23.98 |
| April | 68.00 | 24.00 | 455.50 | 24.00 | 68.00 | 24.00 |
| May | 227.83 | 24.00 | 515.00 | 24.00 | 227.83 | 24.00 |
| June | 328.33 | 24.00 | 492.00 | 24.00 | 328.33 | 24.00 |
| July | 283.50 | 24.00 | 533.00 | 24.00 | 283.50 | 24.00 |
| August | 359.50 | 24.00 | 506.00 | 24.00 | 359.50 | 24.00 |
| September | 278.83 | 24.00 | 510.00 | 24.00 | 278.83 | 24.00 |
| October | 221.83 | 24.00 | 524.00 | 24.00 | 221.83 | 24.00 |
| November | 176.50 | 23.98 | 427.33 | 23.99 | 157.00 | 23.99 |
| December | 159.33 | 23.92 | 388.00 | 23.98 | 123.00 | 23.98 |
| Annual Sum or Average | 2473.83 | 23.98 | 5311.50 | 23.99 | 2271.50 | 23.99 |
| Minimum of Months | 68.00 | 23.82 | 291.33 | 23.95 | 50.50 | 23.95 |
| Maximum of Months | 359.50 | 24.00 | 533.00 | 24.00 | 359.50 | 24.00 |
Report: ComfortReportSimple55Monthly
For: T SW APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 328.50 | 23.09 | 284.17 | 23.48 | 139.33 | 23.55 |
| February | 279.17 | 23.17 | 282.17 | 23.54 | 143.50 | 23.60 |
| March | 258.00 | 23.36 | 346.33 | 23.71 | 156.17 | 23.76 |
| April | 168.33 | 23.91 | 450.17 | 23.97 | 152.00 | 23.98 |
| May | 302.83 | 24.00 | 515.00 | 24.00 | 302.83 | 24.00 |
| June | 336.67 | 24.00 | 492.00 | 24.00 | 336.67 | 24.00 |
| July | 285.50 | 24.00 | 533.00 | 24.00 | 285.50 | 24.00 |
| August | 349.00 | 24.00 | 506.00 | 24.00 | 349.00 | 24.00 |
| September | 308.17 | 24.00 | 510.00 | 24.00 | 308.17 | 24.00 |
| October | 282.33 | 24.00 | 524.00 | 24.00 | 282.33 | 24.00 |
| November | 317.83 | 23.68 | 418.33 | 23.86 | 256.00 | 23.89 |
| December | 356.17 | 23.31 | 344.83 | 23.62 | 210.33 | 23.69 |
| Annual Sum or Average | 3572.50 | 23.70 | 5206.00 | 23.87 | 2921.83 | 23.90 |
| Minimum of Months | 168.33 | 23.09 | 282.17 | 23.48 | 139.33 | 23.55 |
| Maximum of Months | 356.17 | 24.00 | 533.00 | 24.00 | 349.00 | 24.00 |
Report: ComfortReportSimple55Monthly
For: T NW APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 510.33 | 22.89 | 343.50 | 23.29 | 194.17 | 23.39 |
| February | 393.83 | 23.08 | 400.17 | 23.48 | 200.00 | 23.53 |
| March | 382.17 | 23.20 | 503.33 | 23.63 | 214.50 | 23.68 |
| April | 208.00 | 23.90 | 641.67 | 23.98 | 185.17 | 23.98 |
| May | 357.17 | 24.00 | 744.00 | 24.00 | 357.17 | 24.00 |
| June | 407.33 | 24.00 | 720.00 | 24.00 | 407.33 | 24.00 |
| July | 350.50 | 24.00 | 744.00 | 24.00 | 350.50 | 24.00 |
| August | 459.00 | 24.00 | 744.00 | 24.00 | 459.00 | 24.00 |
| September | 409.83 | 24.00 | 720.00 | 24.00 | 409.83 | 24.00 |
| October | 397.17 | 24.00 | 744.00 | 24.00 | 397.17 | 24.00 |
| November | 444.17 | 23.68 | 586.17 | 23.86 | 361.50 | 23.89 |
| December | 537.00 | 23.11 | 445.17 | 23.47 | 272.50 | 23.56 |
| Annual Sum or Average | 4856.50 | 23.61 | 7336.00 | 23.83 | 3808.83 | 23.86 |
| Minimum of Months | 208.00 | 22.89 | 343.50 | 23.29 | 185.17 | 23.39 |
| Maximum of Months | 537.00 | 24.00 | 744.00 | 24.00 | 459.00 | 24.00 |
Report: ComfortReportSimple55Monthly
For: T SE APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 330.83 | 23.08 | 280.33 | 23.48 | 138.83 | 23.55 |
| February | 282.50 | 23.20 | 279.83 | 23.55 | 146.67 | 23.61 |
| March | 263.00 | 23.36 | 342.17 | 23.71 | 157.50 | 23.76 |
| April | 168.67 | 23.91 | 447.00 | 23.97 | 152.00 | 23.98 |
| May | 303.50 | 24.00 | 515.00 | 24.00 | 303.50 | 24.00 |
| June | 324.83 | 24.00 | 492.00 | 24.00 | 324.83 | 24.00 |
| July | 278.83 | 24.00 | 533.00 | 24.00 | 278.83 | 24.00 |
| August | 349.33 | 24.00 | 506.00 | 24.00 | 349.33 | 24.00 |
| September | 300.83 | 24.00 | 510.00 | 24.00 | 300.83 | 24.00 |
| October | 279.83 | 24.00 | 524.00 | 24.00 | 279.83 | 24.00 |
| November | 314.83 | 23.69 | 416.83 | 23.86 | 253.67 | 23.89 |
| December | 362.00 | 23.30 | 341.67 | 23.62 | 213.67 | 23.69 |
| Annual Sum or Average | 3559.00 | 23.70 | 5187.83 | 23.87 | 2899.50 | 23.90 |
| Minimum of Months | 168.67 | 23.08 | 279.83 | 23.48 | 138.83 | 23.55 |
| Maximum of Months | 362.00 | 24.00 | 533.00 | 24.00 | 349.33 | 24.00 |
Report: ComfortReportSimple55Monthly
For: T NE APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 500.50 | 22.92 | 347.67 | 23.32 | 188.00 | 23.42 |
| February | 388.83 | 23.09 | 403.33 | 23.50 | 196.50 | 23.56 |
| March | 376.33 | 23.24 | 493.83 | 23.65 | 210.83 | 23.70 |
| April | 198.67 | 23.90 | 641.00 | 23.98 | 178.00 | 23.98 |
| May | 345.83 | 24.00 | 744.00 | 24.00 | 345.83 | 24.00 |
| June | 372.17 | 24.00 | 720.00 | 24.00 | 372.17 | 24.00 |
| July | 322.17 | 24.00 | 744.00 | 24.00 | 322.17 | 24.00 |
| August | 442.83 | 24.00 | 744.00 | 24.00 | 442.83 | 24.00 |
| September | 378.33 | 24.00 | 720.00 | 24.00 | 378.33 | 24.00 |
| October | 388.33 | 24.00 | 744.00 | 24.00 | 388.33 | 24.00 |
| November | 432.83 | 23.69 | 583.33 | 23.86 | 351.33 | 23.89 |
| December | 540.33 | 23.10 | 445.83 | 23.47 | 272.00 | 23.55 |
| Annual Sum or Average | 4687.17 | 23.61 | 7331.00 | 23.84 | 3646.33 | 23.87 |
| Minimum of Months | 198.67 | 22.92 | 347.67 | 23.32 | 178.00 | 23.42 |
| Maximum of Months | 540.33 | 24.00 | 744.00 | 24.00 | 442.83 | 24.00 |
Report: ComfortReportSimple55Monthly
For: T N1 APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 481.83 | 23.07 | 345.50 | 23.43 | 176.33 | 23.51 |
| February | 370.17 | 23.20 | 379.67 | 23.57 | 176.67 | 23.62 |
| March | 358.67 | 23.26 | 478.83 | 23.67 | 189.83 | 23.72 |
| April | 174.00 | 23.93 | 634.50 | 23.98 | 153.33 | 23.99 |
| May | 329.50 | 24.00 | 744.00 | 24.00 | 329.50 | 24.00 |
| June | 378.83 | 24.00 | 720.00 | 24.00 | 378.83 | 24.00 |
| July | 340.67 | 24.00 | 744.00 | 24.00 | 340.67 | 24.00 |
| August | 459.00 | 24.00 | 744.00 | 24.00 | 459.00 | 24.00 |
| September | 391.83 | 24.00 | 720.00 | 24.00 | 391.83 | 24.00 |
| October | 385.33 | 24.00 | 744.00 | 24.00 | 385.33 | 24.00 |
| November | 414.17 | 23.75 | 578.67 | 23.89 | 339.00 | 23.92 |
| December | 522.17 | 23.24 | 441.17 | 23.57 | 261.50 | 23.65 |
| Annual Sum or Average | 4606.17 | 23.67 | 7274.33 | 23.87 | 3581.83 | 23.89 |
| Minimum of Months | 174.00 | 23.07 | 345.50 | 23.43 | 153.33 | 23.51 |
| Maximum of Months | 522.17 | 24.00 | 744.00 | 24.00 | 459.00 | 24.00 |
Report: ComfortReportSimple55Monthly
For: T N2 APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 481.50 | 23.07 | 346.50 | 23.43 | 176.83 | 23.51 |
| February | 370.00 | 23.20 | 379.83 | 23.57 | 177.33 | 23.62 |
| March | 359.50 | 23.27 | 478.83 | 23.67 | 190.83 | 23.72 |
| April | 175.67 | 23.93 | 634.67 | 23.98 | 155.33 | 23.99 |
| May | 332.33 | 24.00 | 744.00 | 24.00 | 332.33 | 24.00 |
| June | 380.67 | 24.00 | 720.00 | 24.00 | 380.67 | 24.00 |
| July | 342.00 | 24.00 | 744.00 | 24.00 | 342.00 | 24.00 |
| August | 460.67 | 24.00 | 744.00 | 24.00 | 460.67 | 24.00 |
| September | 393.67 | 24.00 | 720.00 | 24.00 | 393.67 | 24.00 |
| October | 387.33 | 24.00 | 744.00 | 24.00 | 387.33 | 24.00 |
| November | 415.33 | 23.75 | 579.00 | 23.89 | 340.50 | 23.92 |
| December | 523.50 | 23.24 | 441.50 | 23.57 | 262.83 | 23.65 |
| Annual Sum or Average | 4622.17 | 23.67 | 7276.33 | 23.87 | 3600.33 | 23.89 |
| Minimum of Months | 175.67 | 23.07 | 346.50 | 23.43 | 155.33 | 23.51 |
| Maximum of Months | 523.50 | 24.00 | 744.00 | 24.00 | 460.67 | 24.00 |
Report: ComfortReportSimple55Monthly
For: T S1 APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 282.17 | 23.32 | 284.67 | 23.66 | 115.17 | 23.71 |
| February | 241.83 | 23.34 | 277.33 | 23.67 | 122.17 | 23.71 |
| March | 232.17 | 23.49 | 340.17 | 23.79 | 135.33 | 23.83 |
| April | 137.83 | 23.93 | 449.83 | 23.98 | 123.33 | 23.99 |
| May | 283.50 | 24.00 | 515.00 | 24.00 | 283.50 | 24.00 |
| June | 318.83 | 24.00 | 492.00 | 24.00 | 318.83 | 24.00 |
| July | 283.67 | 24.00 | 533.00 | 24.00 | 283.67 | 24.00 |
| August | 349.33 | 24.00 | 506.00 | 24.00 | 349.33 | 24.00 |
| September | 294.50 | 24.00 | 510.00 | 24.00 | 294.50 | 24.00 |
| October | 270.33 | 24.00 | 524.00 | 24.00 | 270.33 | 24.00 |
| November | 275.50 | 23.77 | 424.83 | 23.91 | 227.17 | 23.93 |
| December | 312.83 | 23.46 | 345.83 | 23.73 | 195.33 | 23.79 |
| Annual Sum or Average | 3282.50 | 23.78 | 5202.67 | 23.91 | 2718.67 | 23.93 |
| Minimum of Months | 137.83 | 23.32 | 277.33 | 23.66 | 115.17 | 23.71 |
| Maximum of Months | 349.33 | 24.00 | 533.00 | 24.00 | 349.33 | 24.00 |
Report: ComfortReportSimple55Monthly
For: T S2 APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 282.33 | 23.31 | 284.00 | 23.66 | 115.17 | 23.71 |
| February | 242.00 | 23.34 | 277.50 | 23.67 | 122.17 | 23.71 |
| March | 232.67 | 23.49 | 340.17 | 23.79 | 135.83 | 23.83 |
| April | 138.00 | 23.93 | 450.00 | 23.98 | 123.67 | 23.99 |
| May | 284.50 | 24.00 | 515.00 | 24.00 | 284.50 | 24.00 |
| June | 317.33 | 24.00 | 492.00 | 24.00 | 317.33 | 24.00 |
| July | 283.50 | 24.00 | 533.00 | 24.00 | 283.50 | 24.00 |
| August | 350.17 | 24.00 | 506.00 | 24.00 | 350.17 | 24.00 |
| September | 294.33 | 24.00 | 510.00 | 24.00 | 294.33 | 24.00 |
| October | 270.00 | 24.00 | 524.00 | 24.00 | 270.00 | 24.00 |
| November | 275.50 | 23.77 | 424.83 | 23.91 | 227.33 | 23.93 |
| December | 313.33 | 23.45 | 345.67 | 23.73 | 195.67 | 23.79 |
| Annual Sum or Average | 3283.67 | 23.78 | 5202.17 | 23.91 | 2719.67 | 23.93 |
| Minimum of Months | 138.00 | 23.31 | 277.50 | 23.66 | 115.17 | 23.71 |
| Maximum of Months | 350.17 | 24.00 | 533.00 | 24.00 | 350.17 | 24.00 |
Report: ComfortReportSimple55Monthly
For: T CORRIDOR
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 726.67 | 24.67 | 703.17 | 24.71 | 694.33 | 24.73 |
| February | 645.67 | 24.99 | 604.17 | 25.12 | 589.67 | 25.16 |
| March | 706.17 | 25.26 | 679.17 | 25.35 | 652.50 | 25.39 |
| April | 720.00 | 25.91 | 720.00 | 25.91 | 720.00 | 25.91 |
| May | 744.00 | 26.25 | 744.00 | 26.25 | 744.00 | 26.25 |
| June | 720.00 | 26.43 | 720.00 | 26.43 | 720.00 | 26.43 |
| July | 744.00 | 26.50 | 744.00 | 26.50 | 744.00 | 26.50 |
| August | 744.00 | 26.40 | 744.00 | 26.40 | 744.00 | 26.40 |
| September | 720.00 | 26.39 | 720.00 | 26.39 | 720.00 | 26.39 |
| October | 744.00 | 26.15 | 744.00 | 26.15 | 744.00 | 26.15 |
| November | 703.33 | 25.62 | 688.17 | 25.66 | 679.67 | 25.68 |
| December | 725.50 | 24.88 | 707.33 | 24.92 | 695.83 | 24.93 |
| Annual Sum or Average | 8643.33 | 25.80 | 8518.00 | 25.83 | 8448.00 | 25.85 |
| Minimum of Months | 645.67 | 24.67 | 604.17 | 24.71 | 589.67 | 24.73 |
| Maximum of Months | 744.00 | 26.50 | 744.00 | 26.50 | 744.00 | 26.50 |
Report: ComfortReportSimple55Monthly
For: G CORRIDOR
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 457.83 | 25.15 | 588.67 | 25.33 | 372.17 | 25.44 |
| February | 412.67 | 25.29 | 582.33 | 25.48 | 356.50 | 25.54 |
| March | 513.17 | 25.56 | 641.67 | 25.67 | 452.17 | 25.74 |
| April | 580.50 | 26.28 | 715.50 | 26.24 | 577.83 | 26.26 |
| May | 740.17 | 26.78 | 744.00 | 26.78 | 740.17 | 26.78 |
| June | 720.00 | 27.08 | 720.00 | 27.08 | 720.00 | 27.08 |
| July | 744.00 | 27.33 | 744.00 | 27.33 | 744.00 | 27.33 |
| August | 744.00 | 27.25 | 744.00 | 27.25 | 744.00 | 27.25 |
| September | 720.00 | 27.21 | 720.00 | 27.21 | 720.00 | 27.21 |
| October | 716.17 | 26.94 | 744.00 | 26.93 | 716.17 | 26.93 |
| November | 592.33 | 26.35 | 697.67 | 26.30 | 583.67 | 26.34 |
| December | 487.67 | 25.44 | 640.17 | 25.52 | 437.00 | 25.60 |
| Annual Sum or Average | 7428.50 | 26.54 | 8282.00 | 26.52 | 7163.67 | 26.57 |
| Minimum of Months | 412.67 | 25.15 | 582.33 | 25.33 | 356.50 | 25.44 |
| Maximum of Months | 744.00 | 27.33 | 744.00 | 27.33 | 744.00 | 27.33 |
Report: ComfortReportSimple55Monthly
For: M CORRIDOR
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 744.00 | 25.55 | 744.00 | 25.55 | 744.00 | 25.55 |
| February | 619.83 | 25.68 | 663.00 | 25.64 | 619.83 | 25.65 |
| March | 703.33 | 25.74 | 744.00 | 25.72 | 703.33 | 25.73 |
| April | 720.00 | 25.96 | 720.00 | 25.96 | 720.00 | 25.96 |
| May | 744.00 | 26.09 | 744.00 | 26.09 | 744.00 | 26.09 |
| June | 720.00 | 26.17 | 720.00 | 26.17 | 720.00 | 26.17 |
| July | 744.00 | 26.21 | 744.00 | 26.21 | 744.00 | 26.21 |
| August | 744.00 | 26.16 | 744.00 | 26.16 | 744.00 | 26.16 |
| September | 720.00 | 26.17 | 720.00 | 26.17 | 720.00 | 26.17 |
| October | 744.00 | 26.08 | 744.00 | 26.08 | 744.00 | 26.08 |
| November | 706.50 | 25.86 | 720.00 | 25.86 | 706.50 | 25.86 |
| December | 744.00 | 25.57 | 744.00 | 25.57 | 744.00 | 25.57 |
| Annual Sum or Average | 8653.67 | 25.94 | 8751.00 | 25.94 | 8653.67 | 25.94 |
| Minimum of Months | 619.83 | 25.55 | 663.00 | 25.55 | 619.83 | 25.55 |
| Maximum of Months | 744.00 | 26.21 | 744.00 | 26.21 | 744.00 | 26.21 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_GSW
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 515.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 492.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 524.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 6145.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_GNW
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 8760.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_OFFICE
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 140.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 133.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 161.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 140.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 154.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 154.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 140.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 161.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 140.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 147.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 140.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 140.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 1750.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 133.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 161.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_GNE
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 8760.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_GN1
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 8760.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_GN2
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 8760.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_GS1
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 515.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 492.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 524.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 6145.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_GS2
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 515.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 492.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 524.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 6145.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_MSW
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 515.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 492.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 524.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 6145.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_MNW
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 8760.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_MSE
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 515.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 492.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 524.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 6145.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_MNE
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 8760.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_MN1
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 8760.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_MN2
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 8760.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_MS1
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 515.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 492.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 524.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 6145.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_MS2
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 515.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 492.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 524.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 6145.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_TSW
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 515.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 492.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 524.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 6145.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_TNW
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 8760.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_TSE
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 515.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 492.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 524.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 6145.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_TNE
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 8760.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_TN1
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 8760.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_TN2
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 8760.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_TS1
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 515.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 492.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 524.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 6145.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_TS2
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 515.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 492.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 524.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 6145.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_T CORRIDOR
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 8760.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_G CORRIDOR
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 8760.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_M CORRIDOR
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 8760.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: DXReportMonthly
For: SPLIT GSW COOLING COIL
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.243647E+10 | 0.602689E+09 | 662.58 | 0.196221E+10 | 0.474261E+09 | 0.00 | 0.49 | 02-JAN-15:00 | 0.00 | 05-JAN-06:05 | 3050.06 | 02-JAN-15:00 | 2406.62 | 02-JAN-14:40 | 816.30 | 07-JAN-11:20 | 777.72 | 02-JAN-15:00 | 0.00 | 01-JAN-00:10 |
| February | 0.249525E+10 | 0.617272E+09 | 600.70 | 0.199332E+10 | 0.501935E+09 | 0.00 | 0.50 | 11-FEB-16:30 | 0.00 | 02-FEB-21:40 | 3188.49 | 11-FEB-16:30 | 2336.27 | 11-FEB-16:20 | 855.19 | 11-FEB-16:30 | 785.69 | 11-FEB-16:20 | 0.00 | 01-FEB-00:10 |
| March | 0.286255E+10 | 0.703373E+09 | 651.25 | 0.216925E+10 | 0.693298E+09 | 0.00 | 0.46 | 13-MAR-16:25 | 0.00 | 01-MAR-08:25 | 2846.18 | 13-MAR-16:25 | 2193.10 | 13-MAR-16:25 | 904.88 | 14-MAR-10:10 | 731.15 | 13-MAR-16:25 | 0.00 | 01-MAR-00:10 |
| April | 0.357557E+10 | 0.891752E+09 | 716.81 | 0.275375E+10 | 0.821822E+09 | 0.00 | 0.51 | 15-APR-17:00 | 0.00 | 02-APR-06:50 | 3098.87 | 15-APR-16:50 | 2493.94 | 15-APR-17:00 | 889.30 | 01-APR-16:05 | 828.23 | 15-APR-17:00 | 0.00 | 01-APR-00:10 |
| May | 0.489736E+10 | 0.122815E+10 | 744.00 | 0.347783E+10 | 0.141953E+10 | 0.00 | 0.55 | 29-MAY-16:04 | 0.09 | 01-MAY-05:40 | 3377.78 | 29-MAY-16:30 | 2522.45 | 29-MAY-16:15 | 949.79 | 28-MAY-12:00 | 909.72 | 29-MAY-16:04 | 0.00 | 01-MAY-00:10 |
| June | 0.539080E+10 | 0.136203E+10 | 720.00 | 0.368450E+10 | 0.170631E+10 | 0.00 | 0.52 | 08-JUN-16:13 | 0.19 | 06-JUN-04:00 | 3319.40 | 08-JUN-16:13 | 2367.70 | 10-JUN-16:05 | 1040.85 | 08-JUN-16:02 | 853.55 | 08-JUN-16:13 | 0.00 | 01-JUN-00:10 |
| July | 0.594950E+10 | 0.151803E+10 | 744.00 | 0.417671E+10 | 0.177279E+10 | 0.00 | 0.57 | 27-JUL-16:02 | 0.19 | 15-JUL-03:00 | 3492.29 | 22-JUL-15:50 | 2800.65 | 29-JUL-16:30 | 1043.90 | 22-JUL-15:40 | 966.88 | 27-JUL-16:02 | 0.00 | 01-JUL-00:10 |
| August | 0.617017E+10 | 0.156242E+10 | 744.00 | 0.427429E+10 | 0.189588E+10 | 0.00 | 0.57 | 16-AUG-16:02 | 0.20 | 29-AUG-03:00 | 3609.44 | 16-AUG-16:02 | 2642.34 | 19-AUG-16:05 | 1095.24 | 13-AUG-16:03 | 942.49 | 16-AUG-16:02 | 0.00 | 01-AUG-00:10 |
| September | 0.605740E+10 | 0.152688E+10 | 720.00 | 0.430069E+10 | 0.175670E+10 | 0.00 | 0.60 | 17-SEP-16:10 | 0.20 | 05-SEP-06:00 | 3783.31 | 17-SEP-16:10 | 2814.39 | 30-SEP-16:10 | 1046.82 | 18-SEP-18:00 | 985.84 | 20-SEP-14:10 | 0.00 | 01-SEP-00:10 |
| October | 0.580316E+10 | 0.144633E+10 | 744.00 | 0.424168E+10 | 0.156148E+10 | 0.00 | 0.59 | 29-OCT-14:20 | 0.16 | 28-OCT-04:00 | 3801.29 | 29-OCT-14:20 | 2689.99 | 25-OCT-16:03 | 1158.86 | 29-OCT-14:10 | 957.99 | 29-OCT-14:20 | 0.00 | 01-OCT-00:10 |
| November | 0.435194E+10 | 0.107147E+10 | 697.51 | 0.322248E+10 | 0.112946E+10 | 0.00 | 0.51 | 10-NOV-14:30 | 0.00 | 11-NOV-06:03 | 3223.41 | 22-NOV-14:30 | 2555.27 | 07-NOV-16:10 | 1109.95 | 04-NOV-16:20 | 810.99 | 10-NOV-14:30 | 0.00 | 01-NOV-00:10 |
| December | 0.300292E+10 | 0.735302E+09 | 680.19 | 0.230178E+10 | 0.701134E+09 | 0.00 | 0.53 | 10-DEC-15:00 | 0.00 | 12-DEC-06:50 | 3340.58 | 10-DEC-15:00 | 2573.89 | 10-DEC-15:00 | 838.00 | 10-DEC-11:30 | 844.59 | 10-DEC-15:00 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.529931E+11 | 0.132657E+11 | 8425.03 | 0.385585E+11 | 0.144346E+11 | 0.00 | ||||||||||||||
| Minimum of Months | 0.243647E+10 | 0.602689E+09 | 600.70 | 0.196221E+10 | 0.474261E+09 | 0.00 | 0.46 | 0.00 | 2846.18 | 2193.10 | 816.30 | 731.15 | 0.00 | |||||||
| Maximum of Months | 0.617017E+10 | 0.156242E+10 | 744.00 | 0.430069E+10 | 0.189588E+10 | 0.00 | 0.60 | 0.20 | 3801.29 | 2814.39 | 1158.86 | 985.84 | 0.00 |
Report: DXReportMonthly
For: SPLIT GNW COOLING COIL
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.145351E+10 | 0.359355E+09 | 534.14 | 0.108440E+10 | 0.369112E+09 | 0.00 | 0.33 | 02-JAN-15:00 | 0.00 | 05-JAN-06:05 | 2010.91 | 02-JAN-15:00 | 1479.18 | 02-JAN-15:00 | 667.67 | 07-JAN-11:00 | 521.91 | 02-JAN-15:00 | 0.00 | 01-JAN-00:10 |
| February | 0.172075E+10 | 0.426441E+09 | 521.33 | 0.130644E+10 | 0.414313E+09 | 0.00 | 0.39 | 11-FEB-16:30 | 0.00 | 01-FEB-00:10 | 2505.12 | 11-FEB-16:30 | 1734.14 | 11-FEB-16:30 | 770.98 | 11-FEB-16:30 | 623.05 | 11-FEB-16:30 | 0.00 | 01-FEB-00:10 |
| March | 0.228660E+10 | 0.562099E+09 | 600.58 | 0.166864E+10 | 0.617958E+09 | 0.00 | 0.40 | 13-MAR-16:25 | 0.00 | 01-MAR-02:30 | 2505.17 | 13-MAR-16:25 | 1864.85 | 13-MAR-16:40 | 832.35 | 14-MAR-10:10 | 646.60 | 13-MAR-16:25 | 0.00 | 01-MAR-00:10 |
| April | 0.326584E+10 | 0.815876E+09 | 714.17 | 0.248263E+10 | 0.783209E+09 | 0.00 | 0.48 | 15-APR-17:00 | 0.00 | 02-APR-06:50 | 2919.62 | 15-APR-17:00 | 2346.07 | 15-APR-17:00 | 821.44 | 01-APR-16:05 | 784.00 | 15-APR-17:00 | 0.00 | 01-APR-00:10 |
| May | 0.492378E+10 | 0.123480E+10 | 744.00 | 0.350084E+10 | 0.142294E+10 | 0.00 | 0.54 | 29-MAY-16:30 | 0.08 | 01-MAY-05:05 | 3376.88 | 29-MAY-17:10 | 2536.79 | 29-MAY-16:30 | 941.70 | 28-MAY-15:10 | 905.18 | 29-MAY-16:04 | 0.00 | 01-MAY-00:10 |
| June | 0.552625E+10 | 0.139578E+10 | 720.00 | 0.380037E+10 | 0.172588E+10 | 0.00 | 0.54 | 08-JUN-16:30 | 0.20 | 06-JUN-04:00 | 3441.07 | 08-JUN-16:30 | 2463.42 | 09-JUN-17:30 | 1073.02 | 08-JUN-16:13 | 883.02 | 08-JUN-16:30 | 0.00 | 01-JUN-00:10 |
| July | 0.602802E+10 | 0.153786E+10 | 744.00 | 0.424747E+10 | 0.178055E+10 | 0.00 | 0.57 | 27-JUL-16:30 | 0.19 | 15-JUL-03:00 | 3501.24 | 27-JUL-16:30 | 2754.68 | 29-JUL-16:30 | 1025.35 | 22-JUL-15:30 | 972.26 | 27-JUL-16:02 | 0.00 | 01-JUL-00:10 |
| August | 0.607820E+10 | 0.154010E+10 | 744.00 | 0.419370E+10 | 0.188450E+10 | 0.00 | 0.56 | 16-AUG-16:02 | 0.20 | 29-AUG-03:00 | 3546.79 | 16-AUG-16:02 | 2558.40 | 16-AUG-16:30 | 1057.54 | 13-AUG-16:03 | 926.99 | 16-AUG-16:02 | 0.00 | 01-AUG-00:10 |
| September | 0.566893E+10 | 0.143184E+10 | 720.00 | 0.396207E+10 | 0.170686E+10 | 0.00 | 0.55 | 18-SEP-16:10 | 0.19 | 05-SEP-06:00 | 3478.29 | 18-SEP-16:10 | 2503.21 | 17-SEP-16:30 | 1027.90 | 18-SEP-18:00 | 910.45 | 18-SEP-16:10 | 0.00 | 01-SEP-00:10 |
| October | 0.506204E+10 | 0.126580E+10 | 744.00 | 0.359039E+10 | 0.147165E+10 | 0.00 | 0.52 | 03-OCT-16:13 | 0.15 | 28-OCT-04:00 | 3272.03 | 03-OCT-16:30 | 2324.41 | 03-OCT-16:30 | 1055.08 | 29-OCT-14:20 | 850.50 | 03-OCT-16:13 | 0.00 | 01-OCT-00:10 |
| November | 0.348945E+10 | 0.861900E+09 | 681.82 | 0.246808E+10 | 0.102137E+10 | 0.00 | 0.43 | 04-NOV-16:10 | 0.00 | 11-NOV-06:03 | 2802.26 | 04-NOV-16:10 | 1843.80 | 03-NOV-16:04 | 1039.09 | 04-NOV-16:20 | 687.73 | 04-NOV-16:10 | 0.00 | 01-NOV-00:10 |
| December | 0.203057E+10 | 0.497591E+09 | 583.48 | 0.145837E+10 | 0.572202E+09 | 0.00 | 0.39 | 10-DEC-15:10 | 0.00 | 12-DEC-03:10 | 2440.11 | 10-DEC-15:10 | 1786.17 | 10-DEC-15:20 | 728.52 | 25-DEC-16:10 | 626.53 | 10-DEC-15:00 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.475339E+11 | 0.119294E+11 | 8051.52 | 0.337634E+11 | 0.137705E+11 | 0.00 | ||||||||||||||
| Minimum of Months | 0.145351E+10 | 0.359355E+09 | 521.33 | 0.108440E+10 | 0.369112E+09 | 0.00 | 0.33 | 0.00 | 2010.91 | 1479.18 | 667.67 | 521.91 | 0.00 | |||||||
| Maximum of Months | 0.607820E+10 | 0.154010E+10 | 744.00 | 0.424747E+10 | 0.188450E+10 | 0.00 | 0.57 | 0.20 | 3546.79 | 2754.68 | 1073.02 | 972.26 | 0.00 |
Report: DXReportMonthly
For: SPLIT OFFICE COOLING COIL
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.182697E+10 | 0.440915E+09 | 202.94 | 0.158037E+10 | 0.246602E+09 | 0.00 | 1.00 | 03-JAN-08:62 | 0.00 | 01-JAN-00:10 | 7993.68 | 30-JAN-08:62 | 7080.00 | 10-JAN-09:02 | 2951.33 | 30-JAN-08:62 | 1620.99 | 13-JAN-09:02 | 0.00 | 01-JAN-00:10 |
| February | 0.188825E+10 | 0.455794E+09 | 182.70 | 0.158354E+10 | 0.304711E+09 | 0.00 | 1.00 | 01-FEB-09:02 | 0.00 | 01-FEB-00:10 | 7991.84 | 02-FEB-08:62 | 7105.82 | 22-FEB-09:02 | 3007.97 | 02-FEB-09:04 | 1621.21 | 17-FEB-09:04 | 0.00 | 01-FEB-00:10 |
| March | 0.218151E+10 | 0.523024E+09 | 211.43 | 0.177060E+10 | 0.410903E+09 | 0.00 | 1.00 | 01-MAR-09:02 | 0.00 | 01-MAR-00:10 | 8196.21 | 14-MAR-07:02 | 6685.41 | 01-MAR-09:02 | 3936.67 | 14-MAR-07:04 | 1615.77 | 14-MAR-08:04 | 0.00 | 01-MAR-00:10 |
| April | 0.237050E+10 | 0.575261E+09 | 217.92 | 0.192066E+10 | 0.449833E+09 | 0.00 | 1.00 | 03-APR-07:02 | 0.00 | 01-APR-00:10 | 8185.36 | 14-APR-07:02 | 7174.82 | 18-APR-07:02 | 3673.10 | 14-APR-07:03 | 1690.63 | 13-APR-08:62 | 0.00 | 01-APR-00:10 |
| May | 0.323944E+10 | 0.792026E+09 | 277.13 | 0.244525E+10 | 0.794194E+09 | 0.00 | 1.00 | 01-MAY-07:02 | 0.00 | 01-MAY-00:10 | 8202.20 | 31-MAY-07:02 | 6292.40 | 08-MAY-07:02 | 4060.66 | 31-MAY-07:05 | 1718.77 | 31-MAY-08:15 | 0.00 | 01-MAY-00:10 |
| June | 0.375500E+10 | 0.908101E+09 | 329.43 | 0.267680E+10 | 0.107820E+10 | 0.00 | 1.00 | 01-JUN-07:02 | 0.00 | 01-JUN-00:10 | 8222.94 | 22-JUN-07:02 | 5168.95 | 12-JUN-08:62 | 4370.74 | 07-JUN-07:05 | 1743.75 | 08-JUN-08:15 | 0.00 | 01-JUN-00:10 |
| July | 0.391253E+10 | 0.962411E+09 | 385.99 | 0.281785E+10 | 0.109469E+10 | 0.00 | 1.00 | 03-JUL-06:03 | 0.00 | 01-JUL-00:10 | 8222.70 | 24-JUL-06:03 | 5331.07 | 06-JUL-08:62 | 4214.95 | 26-JUL-07:05 | 1745.34 | 14-JUL-08:15 | 0.00 | 01-JUL-00:10 |
| August | 0.433019E+10 | 0.105508E+10 | 361.16 | 0.310967E+10 | 0.122052E+10 | 0.00 | 1.00 | 01-AUG-06:02 | 0.00 | 01-AUG-00:10 | 8222.07 | 10-AUG-07:02 | 5200.01 | 21-AUG-08:63 | 4166.18 | 04-AUG-07:05 | 1767.85 | 23-AUG-08:62 | 0.00 | 01-AUG-00:10 |
| September | 0.403738E+10 | 0.975978E+09 | 401.23 | 0.293867E+10 | 0.109871E+10 | 0.00 | 1.00 | 01-SEP-07:02 | 0.00 | 01-SEP-00:10 | 8223.13 | 28-SEP-07:02 | 5297.16 | 11-SEP-08:62 | 4135.60 | 22-SEP-07:05 | 1718.16 | 21-SEP-08:15 | 0.00 | 01-SEP-00:10 |
| October | 0.387776E+10 | 0.931776E+09 | 374.39 | 0.293659E+10 | 0.941172E+09 | 0.00 | 1.00 | 02-OCT-06:03 | 0.00 | 01-OCT-06:03 | 8220.97 | 05-OCT-07:02 | 6625.94 | 18-OCT-07:02 | 4550.45 | 04-OCT-06:03 | 1722.65 | 13-OCT-08:62 | 0.00 | 01-OCT-00:10 |
| November | 0.292655E+10 | 0.695001E+09 | 235.42 | 0.227602E+10 | 0.650531E+09 | 0.00 | 1.00 | 01-NOV-07:02 | 0.00 | 01-NOV-00:10 | 8222.70 | 10-NOV-08:62 | 7064.32 | 27-NOV-09:02 | 4304.14 | 30-NOV-08:05 | 1673.44 | 21-NOV-09:02 | 0.00 | 01-NOV-00:10 |
| December | 0.193211E+10 | 0.464308E+09 | 213.21 | 0.163624E+10 | 0.295870E+09 | 0.00 | 1.00 | 01-DEC-08:62 | 0.00 | 01-DEC-00:10 | 8132.00 | 08-DEC-08:62 | 7022.03 | 12-DEC-09:02 | 3464.14 | 08-DEC-08:03 | 1647.44 | 07-DEC-09:04 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.362782E+11 | 0.877968E+10 | 3392.98 | 0.276923E+11 | 0.858593E+10 | 0.00 | ||||||||||||||
| Minimum of Months | 0.182697E+10 | 0.440915E+09 | 182.70 | 0.158037E+10 | 0.246602E+09 | 0.00 | 1.00 | 0.00 | 7991.84 | 5168.95 | 2951.33 | 1615.77 | 0.00 | |||||||
| Maximum of Months | 0.433019E+10 | 0.105508E+10 | 401.23 | 0.310967E+10 | 0.122052E+10 | 0.00 | 1.00 | 0.00 | 8223.13 | 7174.82 | 4550.45 | 1767.85 | 0.00 |
Report: DXReportMonthly
For: SPLIT GNE COOLING COIL
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.150392E+10 | 0.371290E+09 | 542.78 | 0.111818E+10 | 0.385741E+09 | 0.00 | 0.34 | 07-JAN-13:00 | 0.00 | 05-JAN-06:05 | 1996.62 | 07-JAN-13:00 | 1425.95 | 02-JAN-15:00 | 704.65 | 07-JAN-11:00 | 509.35 | 07-JAN-13:00 | 0.00 | 01-JAN-00:10 |
| February | 0.173015E+10 | 0.428285E+09 | 524.76 | 0.130499E+10 | 0.425164E+09 | 0.00 | 0.37 | 11-FEB-14:00 | 0.00 | 01-FEB-00:10 | 2146.85 | 11-FEB-14:00 | 1504.36 | 11-FEB-14:00 | 717.90 | 11-FEB-17:10 | 555.75 | 11-FEB-14:00 | 0.00 | 01-FEB-00:10 |
| March | 0.226848E+10 | 0.556771E+09 | 600.72 | 0.163994E+10 | 0.628541E+09 | 0.00 | 0.38 | 13-MAR-16:12 | 0.00 | 01-MAR-02:20 | 2252.53 | 14-MAR-10:10 | 1608.39 | 13-MAR-16:50 | 910.00 | 14-MAR-10:00 | 570.84 | 13-MAR-16:02 | 0.00 | 01-MAR-00:10 |
| April | 0.326482E+10 | 0.814554E+09 | 714.01 | 0.246744E+10 | 0.797384E+09 | 0.00 | 0.45 | 15-APR-17:00 | 0.00 | 02-APR-06:50 | 2559.43 | 15-APR-16:50 | 2020.03 | 15-APR-17:00 | 735.01 | 01-APR-16:05 | 690.10 | 15-APR-17:00 | 0.00 | 01-APR-00:10 |
| May | 0.493715E+10 | 0.123552E+10 | 744.00 | 0.349596E+10 | 0.144119E+10 | 0.00 | 0.52 | 29-MAY-16:04 | 0.09 | 01-MAY-05:15 | 3070.35 | 22-MAY-15:30 | 2275.03 | 22-MAY-16:03 | 938.72 | 28-MAY-11:50 | 827.64 | 29-MAY-16:04 | 0.00 | 01-MAY-00:10 |
| June | 0.563139E+10 | 0.141770E+10 | 720.00 | 0.387435E+10 | 0.175704E+10 | 0.00 | 0.52 | 08-JUN-16:02 | 0.21 | 06-JUN-04:00 | 3148.48 | 08-JUN-16:02 | 2221.30 | 03-JUN-16:30 | 1022.71 | 08-JUN-16:02 | 808.70 | 08-JUN-16:02 | 0.00 | 01-JUN-00:10 |
| July | 0.609263E+10 | 0.154973E+10 | 744.00 | 0.428779E+10 | 0.180484E+10 | 0.00 | 0.57 | 27-JUL-16:10 | 0.21 | 15-JUL-03:00 | 3252.77 | 22-JUL-16:03 | 2551.73 | 29-JUL-16:05 | 999.03 | 13-JUL-13:20 | 905.77 | 27-JUL-16:10 | 0.00 | 01-JUL-00:10 |
| August | 0.608479E+10 | 0.153769E+10 | 744.00 | 0.418412E+10 | 0.190066E+10 | 0.00 | 0.56 | 20-AUG-12:00 | 0.20 | 29-AUG-03:00 | 3339.11 | 20-AUG-12:00 | 2336.20 | 23-AUG-13:00 | 1031.27 | 13-AUG-13:20 | 879.83 | 20-AUG-12:00 | 0.00 | 01-AUG-00:10 |
| September | 0.574241E+10 | 0.144569E+10 | 720.00 | 0.400918E+10 | 0.173324E+10 | 0.00 | 0.55 | 18-SEP-16:10 | 0.21 | 05-SEP-06:00 | 3268.22 | 18-SEP-16:10 | 2313.27 | 18-SEP-16:04 | 1019.86 | 18-SEP-18:00 | 855.05 | 18-SEP-16:10 | 0.00 | 01-SEP-00:10 |
| October | 0.509871E+10 | 0.127196E+10 | 744.00 | 0.360540E+10 | 0.149331E+10 | 0.00 | 0.52 | 03-OCT-11:00 | 0.16 | 28-OCT-04:00 | 3109.55 | 03-OCT-11:00 | 2160.58 | 03-OCT-16:03 | 1050.46 | 01-OCT-13:00 | 807.48 | 03-OCT-11:30 | 0.00 | 01-OCT-00:10 |
| November | 0.351159E+10 | 0.865485E+09 | 685.86 | 0.247278E+10 | 0.103881E+10 | 0.00 | 0.45 | 04-NOV-16:10 | 0.00 | 11-NOV-06:03 | 2744.20 | 04-NOV-16:10 | 1743.92 | 03-NOV-16:04 | 1022.39 | 04-NOV-16:20 | 672.02 | 04-NOV-16:10 | 0.00 | 01-NOV-00:10 |
| December | 0.196832E+10 | 0.481615E+09 | 574.42 | 0.139714E+10 | 0.571181E+09 | 0.00 | 0.39 | 10-DEC-14:00 | 0.00 | 12-DEC-03:10 | 2300.71 | 10-DEC-14:00 | 1623.78 | 10-DEC-14:00 | 738.50 | 24-DEC-10:40 | 589.41 | 10-DEC-14:00 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.478344E+11 | 0.119763E+11 | 8058.54 | 0.338573E+11 | 0.139771E+11 | 0.00 | ||||||||||||||
| Minimum of Months | 0.150392E+10 | 0.371290E+09 | 524.76 | 0.111818E+10 | 0.385741E+09 | 0.00 | 0.34 | 0.00 | 1996.62 | 1425.95 | 704.65 | 509.35 | 0.00 | |||||||
| Maximum of Months | 0.609263E+10 | 0.154973E+10 | 744.00 | 0.428779E+10 | 0.190066E+10 | 0.00 | 0.57 | 0.21 | 3339.11 | 2551.73 | 1050.46 | 905.77 | 0.00 |
Report: DXReportMonthly
For: SPLIT GN1 COOLING COIL
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.141941E+10 | 0.350609E+09 | 585.46 | 0.105993E+10 | 0.359479E+09 | 0.00 | 0.32 | 07-JAN-13:00 | 0.00 | 05-JAN-06:05 | 1677.76 | 07-JAN-13:00 | 1173.96 | 07-JAN-13:00 | 581.51 | 07-JAN-10:30 | 429.38 | 07-JAN-13:00 | 0.00 | 01-JAN-00:10 |
| February | 0.159473E+10 | 0.394709E+09 | 554.47 | 0.120370E+10 | 0.391028E+09 | 0.00 | 0.35 | 11-FEB-17:10 | 0.00 | 02-FEB-19:50 | 1874.27 | 11-FEB-17:10 | 1252.34 | 11-FEB-17:10 | 621.93 | 11-FEB-17:10 | 465.19 | 11-FEB-14:00 | 0.00 | 01-FEB-00:10 |
| March | 0.203617E+10 | 0.500157E+09 | 619.02 | 0.147616E+10 | 0.560007E+09 | 0.00 | 0.36 | 13-MAR-16:25 | 0.00 | 01-MAR-03:30 | 1874.81 | 13-MAR-16:25 | 1363.84 | 13-MAR-17:10 | 693.92 | 14-MAR-10:00 | 486.93 | 13-MAR-16:02 | 0.00 | 01-MAR-00:10 |
| April | 0.283739E+10 | 0.708069E+09 | 717.62 | 0.213530E+10 | 0.702086E+09 | 0.00 | 0.41 | 15-APR-17:00 | 0.00 | 02-APR-06:50 | 2118.56 | 15-APR-17:00 | 1662.95 | 15-APR-17:00 | 639.39 | 01-APR-16:05 | 574.02 | 15-APR-17:00 | 0.00 | 01-APR-00:10 |
| May | 0.423030E+10 | 0.105966E+10 | 744.00 | 0.298390E+10 | 0.124640E+10 | 0.00 | 0.48 | 29-MAY-16:04 | 0.11 | 01-MAY-05:05 | 2545.77 | 29-MAY-17:10 | 1876.06 | 29-MAY-16:20 | 801.30 | 28-MAY-15:10 | 689.84 | 29-MAY-16:04 | 0.00 | 01-MAY-00:10 |
| June | 0.481211E+10 | 0.121301E+10 | 720.00 | 0.327916E+10 | 0.153295E+10 | 0.00 | 0.48 | 08-JUN-16:40 | 0.23 | 06-JUN-04:00 | 2598.68 | 08-JUN-16:40 | 1821.96 | 29-JUN-17:17 | 849.02 | 08-JUN-16:13 | 671.78 | 08-JUN-16:40 | 0.00 | 01-JUN-00:10 |
| July | 0.518313E+10 | 0.131922E+10 | 744.00 | 0.359137E+10 | 0.159176E+10 | 0.00 | 0.52 | 27-JUL-16:30 | 0.22 | 15-JUL-03:00 | 2689.74 | 27-JUL-17:20 | 2068.67 | 29-JUL-16:05 | 860.99 | 25-JUL-16:02 | 748.66 | 27-JUL-16:08 | 0.00 | 01-JUL-00:10 |
| August | 0.518998E+10 | 0.131289E+10 | 744.00 | 0.352687E+10 | 0.166310E+10 | 0.00 | 0.49 | 21-AUG-16:01 | 0.22 | 29-AUG-03:00 | 2645.22 | 21-AUG-16:01 | 1850.69 | 19-AUG-16:05 | 846.00 | 13-AUG-16:03 | 701.10 | 21-AUG-16:01 | 0.00 | 01-AUG-00:10 |
| September | 0.485976E+10 | 0.122497E+10 | 720.00 | 0.334872E+10 | 0.151104E+10 | 0.00 | 0.50 | 18-SEP-16:10 | 0.22 | 05-SEP-06:00 | 2679.29 | 18-SEP-17:20 | 1878.70 | 18-SEP-16:03 | 844.03 | 22-SEP-18:00 | 702.85 | 18-SEP-16:10 | 0.00 | 01-SEP-00:10 |
| October | 0.436964E+10 | 0.109061E+10 | 744.00 | 0.306243E+10 | 0.130721E+10 | 0.00 | 0.47 | 03-OCT-16:03 | 0.17 | 28-OCT-04:00 | 2529.66 | 03-OCT-16:03 | 1768.68 | 03-OCT-16:03 | 868.15 | 01-OCT-12:50 | 662.59 | 03-OCT-16:03 | 0.00 | 01-OCT-00:10 |
| November | 0.310880E+10 | 0.766795E+09 | 696.95 | 0.219056E+10 | 0.918238E+09 | 0.00 | 0.42 | 04-NOV-16:10 | 0.00 | 11-NOV-06:03 | 2320.02 | 04-NOV-16:10 | 1471.28 | 03-NOV-16:04 | 852.81 | 04-NOV-16:20 | 570.97 | 04-NOV-16:10 | 0.00 | 01-NOV-00:10 |
| December | 0.187867E+10 | 0.460065E+09 | 640.06 | 0.134352E+10 | 0.535147E+09 | 0.00 | 0.36 | 10-DEC-14:00 | 0.00 | 12-DEC-07:00 | 1898.49 | 10-DEC-14:00 | 1342.86 | 10-DEC-15:10 | 643.98 | 25-DEC-22:00 | 488.55 | 10-DEC-14:00 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.415201E+11 | 0.104008E+11 | 8229.58 | 0.292016E+11 | 0.123185E+11 | 0.00 | ||||||||||||||
| Minimum of Months | 0.141941E+10 | 0.350609E+09 | 554.47 | 0.105993E+10 | 0.359479E+09 | 0.00 | 0.32 | 0.00 | 1677.76 | 1173.96 | 581.51 | 429.38 | 0.00 | |||||||
| Maximum of Months | 0.518998E+10 | 0.131922E+10 | 744.00 | 0.359137E+10 | 0.166310E+10 | 0.00 | 0.52 | 0.23 | 2689.74 | 2068.67 | 868.15 | 748.66 | 0.00 |
Report: DXReportMonthly
For: SPLIT GN2 COOLING COIL
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.142334E+10 | 0.351572E+09 | 586.60 | 0.106318E+10 | 0.360153E+09 | 0.00 | 0.32 | 07-JAN-13:00 | 0.00 | 05-JAN-06:05 | 1679.94 | 07-JAN-13:00 | 1175.78 | 07-JAN-13:00 | 582.07 | 07-JAN-10:30 | 429.91 | 07-JAN-13:00 | 0.00 | 01-JAN-00:10 |
| February | 0.159611E+10 | 0.395046E+09 | 555.16 | 0.120480E+10 | 0.391314E+09 | 0.00 | 0.35 | 11-FEB-17:10 | 0.00 | 02-FEB-19:50 | 1866.97 | 11-FEB-17:10 | 1246.58 | 11-FEB-17:10 | 620.39 | 11-FEB-17:10 | 465.28 | 11-FEB-14:00 | 0.00 | 01-FEB-00:10 |
| March | 0.203740E+10 | 0.500455E+09 | 619.83 | 0.147708E+10 | 0.560315E+09 | 0.00 | 0.36 | 13-MAR-16:25 | 0.00 | 01-MAR-03:30 | 1869.25 | 13-MAR-16:25 | 1358.61 | 13-MAR-17:10 | 695.23 | 14-MAR-10:00 | 485.74 | 13-MAR-16:02 | 0.00 | 01-MAR-00:10 |
| April | 0.283719E+10 | 0.708009E+09 | 717.62 | 0.213500E+10 | 0.702186E+09 | 0.00 | 0.41 | 15-APR-17:00 | 0.00 | 02-APR-06:50 | 2113.20 | 15-APR-17:00 | 1658.40 | 15-APR-17:00 | 637.85 | 01-APR-16:05 | 572.60 | 15-APR-17:00 | 0.00 | 01-APR-00:10 |
| May | 0.423059E+10 | 0.105969E+10 | 744.00 | 0.298397E+10 | 0.124662E+10 | 0.00 | 0.48 | 29-MAY-16:04 | 0.11 | 01-MAY-05:05 | 2539.86 | 29-MAY-17:10 | 1872.34 | 29-MAY-16:20 | 800.86 | 28-MAY-15:10 | 688.74 | 29-MAY-16:04 | 0.00 | 01-MAY-00:10 |
| June | 0.481649E+10 | 0.121402E+10 | 720.00 | 0.328267E+10 | 0.153382E+10 | 0.00 | 0.48 | 08-JUN-16:40 | 0.23 | 06-JUN-04:00 | 2596.15 | 08-JUN-16:40 | 1817.42 | 29-JUN-17:17 | 848.30 | 08-JUN-16:13 | 671.12 | 08-JUN-16:40 | 0.00 | 01-JUN-00:10 |
| July | 0.518549E+10 | 0.131974E+10 | 744.00 | 0.359320E+10 | 0.159229E+10 | 0.00 | 0.52 | 27-JUL-16:30 | 0.22 | 15-JUL-03:00 | 2685.77 | 27-JUL-17:20 | 2067.21 | 29-JUL-16:05 | 861.13 | 25-JUL-16:02 | 747.87 | 27-JUL-16:08 | 0.00 | 01-JUL-00:10 |
| August | 0.519012E+10 | 0.131286E+10 | 744.00 | 0.352681E+10 | 0.166332E+10 | 0.00 | 0.49 | 21-AUG-16:01 | 0.22 | 29-AUG-03:00 | 2641.54 | 21-AUG-16:01 | 1847.89 | 19-AUG-16:05 | 844.95 | 13-AUG-16:03 | 700.13 | 21-AUG-16:01 | 0.00 | 01-AUG-00:10 |
| September | 0.486262E+10 | 0.122560E+10 | 720.00 | 0.335095E+10 | 0.151167E+10 | 0.00 | 0.50 | 18-SEP-16:10 | 0.22 | 05-SEP-06:00 | 2675.43 | 18-SEP-17:20 | 1875.92 | 18-SEP-16:03 | 844.08 | 22-SEP-18:00 | 701.96 | 18-SEP-16:10 | 0.00 | 01-SEP-00:10 |
| October | 0.437100E+10 | 0.109090E+10 | 744.00 | 0.306337E+10 | 0.130764E+10 | 0.00 | 0.47 | 03-OCT-16:03 | 0.17 | 28-OCT-04:00 | 2527.45 | 03-OCT-16:03 | 1766.85 | 03-OCT-16:03 | 868.25 | 01-OCT-12:50 | 661.99 | 03-OCT-16:03 | 0.00 | 01-OCT-00:10 |
| November | 0.310995E+10 | 0.767048E+09 | 697.09 | 0.219140E+10 | 0.918552E+09 | 0.00 | 0.42 | 04-NOV-16:10 | 0.00 | 11-NOV-06:03 | 2319.99 | 04-NOV-16:10 | 1470.09 | 03-NOV-16:04 | 852.70 | 04-NOV-16:20 | 570.93 | 04-NOV-16:10 | 0.00 | 01-NOV-00:10 |
| December | 0.187599E+10 | 0.459399E+09 | 639.86 | 0.134122E+10 | 0.534775E+09 | 0.00 | 0.36 | 10-DEC-14:00 | 0.00 | 12-DEC-07:00 | 1898.48 | 10-DEC-14:00 | 1340.87 | 10-DEC-15:00 | 643.54 | 25-DEC-22:00 | 488.52 | 10-DEC-14:00 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.415363E+11 | 0.104043E+11 | 8232.16 | 0.292136E+11 | 0.123227E+11 | 0.00 | ||||||||||||||
| Minimum of Months | 0.142334E+10 | 0.351572E+09 | 555.16 | 0.106318E+10 | 0.360153E+09 | 0.00 | 0.32 | 0.00 | 1679.94 | 1175.78 | 582.07 | 429.91 | 0.00 | |||||||
| Maximum of Months | 0.519012E+10 | 0.131974E+10 | 744.00 | 0.359320E+10 | 0.166332E+10 | 0.00 | 0.52 | 0.23 | 2685.77 | 2067.21 | 868.25 | 747.87 | 0.00 |
Report: DXReportMonthly
For: SPLIT GS1 COOLING COIL
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.248744E+10 | 0.614715E+09 | 721.49 | 0.201563E+10 | 0.471811E+09 | 0.00 | 0.51 | 02-JAN-14:40 | 0.00 | 08-JAN-06:03 | 2669.21 | 02-JAN-14:40 | 2130.60 | 02-JAN-14:30 | 728.93 | 07-JAN-11:30 | 680.52 | 02-JAN-14:40 | 0.00 | 01-JAN-00:10 |
| February | 0.242680E+10 | 0.599977E+09 | 635.32 | 0.194438E+10 | 0.482418E+09 | 0.00 | 0.48 | 11-FEB-14:00 | 0.00 | 03-FEB-02:70 | 2562.20 | 11-FEB-14:00 | 1898.57 | 11-FEB-14:20 | 711.65 | 11-FEB-17:10 | 655.64 | 11-FEB-14:00 | 0.00 | 01-FEB-00:10 |
| March | 0.266150E+10 | 0.653989E+09 | 687.65 | 0.201920E+10 | 0.642301E+09 | 0.00 | 0.43 | 13-MAR-16:02 | 0.00 | 11-MAR-05:00 | 2244.16 | 13-MAR-16:02 | 1691.55 | 13-MAR-16:15 | 766.19 | 14-MAR-10:10 | 580.28 | 13-MAR-16:02 | 0.00 | 01-MAR-00:10 |
| April | 0.317139E+10 | 0.790206E+09 | 718.42 | 0.242246E+10 | 0.748928E+09 | 0.00 | 0.45 | 15-APR-16:50 | 0.00 | 19-APR-06:00 | 2364.61 | 01-APR-16:05 | 1813.78 | 15-APR-17:00 | 722.23 | 01-APR-16:05 | 621.21 | 15-APR-16:50 | 0.00 | 01-APR-00:10 |
| May | 0.422277E+10 | 0.105797E+10 | 744.00 | 0.297287E+10 | 0.124990E+10 | 0.00 | 0.49 | 29-MAY-16:04 | 0.12 | 01-MAY-05:10 | 2562.65 | 29-MAY-16:04 | 1880.91 | 29-MAY-16:04 | 813.76 | 28-MAY-12:00 | 696.78 | 29-MAY-16:04 | 0.00 | 01-MAY-00:10 |
| June | 0.469307E+10 | 0.118371E+10 | 720.00 | 0.317405E+10 | 0.151902E+10 | 0.00 | 0.47 | 03-JUN-16:03 | 0.22 | 14-JUN-06:00 | 2513.73 | 03-JUN-16:03 | 1789.07 | 03-JUN-16:30 | 819.63 | 08-JUN-16:02 | 660.16 | 03-JUN-16:03 | 0.00 | 01-JUN-00:10 |
| July | 0.512283E+10 | 0.130437E+10 | 744.00 | 0.353315E+10 | 0.158968E+10 | 0.00 | 0.52 | 29-JUL-16:03 | 0.22 | 15-JUL-03:00 | 2733.00 | 22-JUL-16:03 | 2125.45 | 29-JUL-16:03 | 857.82 | 22-JUL-16:03 | 750.39 | 29-JUL-16:03 | 0.00 | 01-JUL-00:10 |
| August | 0.530418E+10 | 0.134125E+10 | 744.00 | 0.362171E+10 | 0.168247E+10 | 0.00 | 0.53 | 20-AUG-12:00 | 0.22 | 29-AUG-03:00 | 2818.05 | 20-AUG-12:00 | 1977.18 | 19-AUG-16:05 | 885.87 | 13-AUG-16:03 | 745.34 | 20-AUG-12:00 | 0.00 | 01-AUG-00:10 |
| September | 0.527690E+10 | 0.132762E+10 | 720.00 | 0.370580E+10 | 0.157109E+10 | 0.00 | 0.57 | 20-SEP-14:10 | 0.23 | 05-SEP-06:00 | 3023.81 | 20-SEP-14:10 | 2189.24 | 20-SEP-14:10 | 870.17 | 18-SEP-18:30 | 798.55 | 20-SEP-14:00 | 0.00 | 01-SEP-00:10 |
| October | 0.514844E+10 | 0.128064E+10 | 744.00 | 0.373930E+10 | 0.140914E+10 | 0.00 | 0.58 | 29-OCT-14:10 | 0.19 | 28-OCT-04:00 | 3130.23 | 29-OCT-14:10 | 2185.95 | 29-OCT-14:10 | 944.28 | 29-OCT-14:10 | 792.23 | 29-OCT-14:10 | 0.00 | 01-OCT-00:10 |
| November | 0.401332E+10 | 0.986479E+09 | 714.50 | 0.297888E+10 | 0.103444E+10 | 0.00 | 0.52 | 22-NOV-12:50 | 0.00 | 12-NOV-09:50 | 2766.16 | 22-NOV-12:50 | 2120.07 | 22-NOV-12:50 | 923.95 | 04-NOV-16:20 | 690.28 | 10-NOV-14:00 | 0.00 | 01-NOV-00:10 |
| December | 0.291929E+10 | 0.714379E+09 | 710.41 | 0.224693E+10 | 0.672358E+09 | 0.00 | 0.53 | 10-DEC-14:30 | 0.00 | 15-DEC-01:20 | 2800.90 | 10-DEC-14:30 | 2141.65 | 10-DEC-14:40 | 761.50 | 25-DEC-22:00 | 709.15 | 10-DEC-14:30 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.474479E+11 | 0.118553E+11 | 8603.80 | 0.343744E+11 | 0.130735E+11 | 0.00 | ||||||||||||||
| Minimum of Months | 0.242680E+10 | 0.599977E+09 | 635.32 | 0.194438E+10 | 0.471811E+09 | 0.00 | 0.43 | 0.00 | 2244.16 | 1691.55 | 711.65 | 580.28 | 0.00 | |||||||
| Maximum of Months | 0.530418E+10 | 0.134125E+10 | 744.00 | 0.373930E+10 | 0.168247E+10 | 0.00 | 0.58 | 0.23 | 3130.23 | 2189.24 | 944.28 | 798.55 | 0.00 |
Report: DXReportMonthly
For: SPLIT GS2 COOLING COIL
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.271533E+10 | 0.670220E+09 | 729.58 | 0.221768E+10 | 0.497650E+09 | 0.00 | 0.54 | 02-JAN-14:40 | 0.00 | 08-JAN-06:50 | 2871.33 | 02-JAN-14:40 | 2316.93 | 02-JAN-14:30 | 741.64 | 07-JAN-11:30 | 729.02 | 02-JAN-14:40 | 0.00 | 01-JAN-00:10 |
| February | 0.260912E+10 | 0.644318E+09 | 640.08 | 0.210382E+10 | 0.505306E+09 | 0.00 | 0.50 | 11-FEB-14:00 | 0.00 | 03-FEB-02:40 | 2680.69 | 11-FEB-14:30 | 2006.94 | 11-FEB-14:20 | 726.48 | 11-FEB-17:10 | 684.43 | 11-FEB-14:00 | 0.00 | 01-FEB-00:10 |
| March | 0.286853E+10 | 0.704209E+09 | 696.17 | 0.219651E+10 | 0.672021E+09 | 0.00 | 0.44 | 13-MAR-16:02 | 0.00 | 11-MAR-09:40 | 2345.27 | 04-MAR-14:00 | 1755.03 | 13-MAR-16:06 | 780.88 | 14-MAR-10:10 | 597.38 | 13-MAR-16:02 | 0.00 | 01-MAR-00:10 |
| April | 0.343277E+10 | 0.853942E+09 | 718.83 | 0.264932E+10 | 0.783443E+09 | 0.00 | 0.47 | 15-APR-16:50 | 0.00 | 19-APR-06:00 | 2482.06 | 01-APR-16:05 | 1935.18 | 15-APR-17:00 | 736.33 | 01-APR-16:05 | 654.90 | 15-APR-16:50 | 0.00 | 01-APR-00:10 |
| May | 0.454284E+10 | 0.113622E+10 | 744.00 | 0.324406E+10 | 0.129878E+10 | 0.00 | 0.52 | 29-MAY-16:04 | 0.14 | 01-MAY-05:05 | 2717.32 | 29-MAY-16:04 | 2021.43 | 29-MAY-16:04 | 832.53 | 28-MAY-12:00 | 736.70 | 29-MAY-16:04 | 0.00 | 01-MAY-00:10 |
| June | 0.504155E+10 | 0.126947E+10 | 720.00 | 0.347014E+10 | 0.157141E+10 | 0.00 | 0.50 | 03-JUN-16:03 | 0.25 | 14-JUN-06:00 | 2668.52 | 03-JUN-16:03 | 1929.72 | 03-JUN-16:30 | 830.48 | 08-JUN-16:02 | 699.13 | 03-JUN-16:03 | 0.00 | 01-JUN-00:10 |
| July | 0.550511E+10 | 0.139873E+10 | 744.00 | 0.386385E+10 | 0.164127E+10 | 0.00 | 0.55 | 29-JUL-16:03 | 0.24 | 15-JUL-03:00 | 2890.16 | 22-JUL-16:03 | 2270.39 | 29-JUL-16:03 | 875.03 | 22-JUL-16:03 | 791.08 | 29-JUL-16:03 | 0.00 | 01-JUL-00:10 |
| August | 0.567200E+10 | 0.143154E+10 | 744.00 | 0.393809E+10 | 0.173391E+10 | 0.00 | 0.56 | 20-AUG-12:00 | 0.25 | 29-AUG-03:00 | 3007.07 | 20-AUG-12:00 | 2137.66 | 20-AUG-16:10 | 904.83 | 13-AUG-16:03 | 792.87 | 20-AUG-12:00 | 0.00 | 01-AUG-00:10 |
| September | 0.564876E+10 | 0.141801E+10 | 720.00 | 0.403012E+10 | 0.161865E+10 | 0.00 | 0.58 | 20-SEP-14:10 | 0.26 | 06-SEP-05:00 | 3124.01 | 20-SEP-14:10 | 2349.11 | 24-SEP-13:30 | 893.68 | 18-SEP-18:30 | 823.94 | 20-SEP-14:00 | 0.00 | 01-SEP-00:10 |
| October | 0.552102E+10 | 0.137032E+10 | 744.00 | 0.406592E+10 | 0.145510E+10 | 0.00 | 0.60 | 29-OCT-14:10 | 0.21 | 28-OCT-04:00 | 3311.75 | 29-OCT-14:10 | 2347.49 | 29-OCT-14:10 | 964.26 | 29-OCT-14:10 | 835.65 | 29-OCT-14:10 | 0.00 | 01-OCT-00:10 |
| November | 0.430588E+10 | 0.105679E+10 | 716.33 | 0.323471E+10 | 0.107117E+10 | 0.00 | 0.53 | 22-NOV-12:50 | 0.00 | 12-NOV-09:50 | 2865.78 | 22-NOV-12:50 | 2212.64 | 22-NOV-12:50 | 946.36 | 04-NOV-16:20 | 711.70 | 10-NOV-14:00 | 0.00 | 01-NOV-00:10 |
| December | 0.314680E+10 | 0.769252E+09 | 720.15 | 0.244613E+10 | 0.700668E+09 | 0.00 | 0.55 | 10-DEC-14:30 | 0.00 | 15-DEC-01:40 | 2970.07 | 10-DEC-14:30 | 2297.87 | 10-DEC-14:40 | 798.14 | 25-DEC-22:00 | 749.67 | 10-DEC-14:30 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.510097E+11 | 0.127230E+11 | 8637.15 | 0.374603E+11 | 0.135494E+11 | 0.00 | ||||||||||||||
| Minimum of Months | 0.260912E+10 | 0.644318E+09 | 640.08 | 0.210382E+10 | 0.497650E+09 | 0.00 | 0.44 | 0.00 | 2345.27 | 1755.03 | 726.48 | 597.38 | 0.00 | |||||||
| Maximum of Months | 0.567200E+10 | 0.143154E+10 | 744.00 | 0.406592E+10 | 0.173391E+10 | 0.00 | 0.60 | 0.26 | 3311.75 | 2349.11 | 964.26 | 835.65 | 0.00 |
Report: DXReportMonthly
For: SPLIT MSW COOLING COIL
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.494630E+10 | 0.122466E+10 | 623.58 | 0.397000E+10 | 0.976304E+09 | 0.00 | 0.48 | 02-JAN-15:00 | 0.00 | 05-JAN-06:05 | 6847.28 | 02-JAN-15:00 | 5444.27 | 02-JAN-14:40 | 1899.85 | 07-JAN-11:30 | 1747.92 | 02-JAN-15:00 | 0.00 | 01-JAN-00:10 |
| February | 0.541011E+10 | 0.133764E+10 | 579.55 | 0.430342E+10 | 0.110669E+10 | 0.00 | 0.52 | 11-FEB-16:20 | 0.00 | 01-FEB-00:10 | 7478.72 | 11-FEB-16:30 | 5481.99 | 11-FEB-16:20 | 2008.16 | 11-FEB-16:30 | 1840.50 | 11-FEB-16:20 | 0.00 | 01-FEB-00:10 |
| March | 0.668288E+10 | 0.164007E+10 | 649.49 | 0.506810E+10 | 0.161478E+10 | 0.00 | 0.48 | 13-MAR-16:25 | 0.00 | 01-MAR-03:30 | 6751.94 | 13-MAR-16:25 | 5233.64 | 13-MAR-16:30 | 2161.57 | 14-MAR-10:10 | 1730.49 | 13-MAR-16:25 | 0.00 | 01-MAR-00:10 |
| April | 0.825459E+10 | 0.205730E+10 | 716.50 | 0.637282E+10 | 0.188178E+10 | 0.00 | 0.52 | 15-APR-16:40 | 0.00 | 19-APR-02:40 | 7273.02 | 15-APR-16:40 | 5863.37 | 15-APR-17:00 | 2057.55 | 01-APR-16:05 | 1939.39 | 15-APR-16:40 | 0.00 | 01-APR-00:10 |
| May | 0.109726E+11 | 0.275170E+10 | 744.00 | 0.775457E+10 | 0.321807E+10 | 0.00 | 0.57 | 29-MAY-16:04 | 0.09 | 01-MAY-05:15 | 8002.23 | 29-MAY-16:20 | 5979.23 | 29-MAY-16:20 | 2200.34 | 28-MAY-12:00 | 2147.38 | 29-MAY-16:04 | 0.00 | 01-MAY-00:10 |
| June | 0.118040E+11 | 0.298599E+10 | 720.00 | 0.802011E+10 | 0.378386E+10 | 0.00 | 0.53 | 08-JUN-16:13 | 0.17 | 06-JUN-04:00 | 7674.59 | 08-JUN-16:13 | 5378.14 | 14-JUN-17:13 | 2456.09 | 08-JUN-16:02 | 1969.24 | 08-JUN-16:13 | 0.00 | 01-JUN-00:10 |
| July | 0.124758E+11 | 0.319397E+10 | 744.00 | 0.866258E+10 | 0.381324E+10 | 0.00 | 0.56 | 27-JUL-16:02 | 0.16 | 15-JUL-03:00 | 7819.80 | 22-JUL-15:40 | 6129.36 | 29-JUL-16:07 | 2412.66 | 22-JUL-15:40 | 2156.51 | 27-JUL-16:02 | 0.00 | 01-JUL-00:10 |
| August | 0.126663E+11 | 0.321839E+10 | 744.00 | 0.859972E+10 | 0.406656E+10 | 0.00 | 0.56 | 16-AUG-16:02 | 0.16 | 29-AUG-03:00 | 8015.21 | 16-AUG-16:02 | 5746.45 | 16-AUG-16:03 | 2521.82 | 13-AUG-16:03 | 2094.13 | 16-AUG-16:02 | 0.00 | 01-AUG-00:10 |
| September | 0.122345E+11 | 0.309755E+10 | 720.00 | 0.849827E+10 | 0.373624E+10 | 0.00 | 0.58 | 17-SEP-16:10 | 0.15 | 05-SEP-06:00 | 8375.08 | 17-SEP-16:10 | 6097.67 | 17-SEP-16:07 | 2417.14 | 19-SEP-14:20 | 2171.71 | 20-SEP-14:10 | 0.00 | 01-SEP-00:10 |
| October | 0.116087E+11 | 0.290539E+10 | 744.00 | 0.831438E+10 | 0.329432E+10 | 0.00 | 0.58 | 29-OCT-14:10 | 0.11 | 28-OCT-04:00 | 8502.73 | 29-OCT-14:10 | 5850.07 | 25-OCT-16:03 | 2704.73 | 29-OCT-14:10 | 2141.87 | 29-OCT-14:10 | 0.00 | 01-OCT-00:10 |
| November | 0.864685E+10 | 0.213421E+10 | 683.39 | 0.627876E+10 | 0.236809E+10 | 0.00 | 0.50 | 22-NOV-14:30 | 0.00 | 11-NOV-06:03 | 7225.31 | 22-NOV-14:30 | 5608.87 | 07-NOV-16:10 | 2540.86 | 04-NOV-16:20 | 1790.23 | 22-NOV-14:30 | 0.00 | 01-NOV-00:10 |
| December | 0.593033E+10 | 0.145284E+10 | 645.74 | 0.447786E+10 | 0.145247E+10 | 0.00 | 0.52 | 10-DEC-15:00 | 0.00 | 12-DEC-02:00 | 7495.55 | 10-DEC-15:00 | 5713.87 | 10-DEC-15:00 | 1915.49 | 25-DEC-14:30 | 1895.12 | 10-DEC-15:00 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.111633E+12 | 0.279997E+11 | 8314.25 | 0.803206E+11 | 0.313124E+11 | 0.00 | ||||||||||||||
| Minimum of Months | 0.494630E+10 | 0.122466E+10 | 579.55 | 0.397000E+10 | 0.976304E+09 | 0.00 | 0.48 | 0.00 | 6751.94 | 5233.64 | 1899.85 | 1730.49 | 0.00 | |||||||
| Maximum of Months | 0.126663E+11 | 0.321839E+10 | 744.00 | 0.866258E+10 | 0.406656E+10 | 0.00 | 0.58 | 0.17 | 8502.73 | 6129.36 | 2704.73 | 2171.71 | 0.00 |
Report: DXReportMonthly
For: SPLIT MNW COOLING COIL
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.288746E+10 | 0.714076E+09 | 507.46 | 0.212952E+10 | 0.757941E+09 | 0.00 | 0.31 | 02-JAN-15:00 | 0.00 | 05-JAN-05:00 | 4343.01 | 02-JAN-15:00 | 3162.32 | 02-JAN-15:00 | 1492.33 | 07-JAN-11:00 | 1128.67 | 02-JAN-15:00 | 0.00 | 01-JAN-00:10 |
| February | 0.377598E+10 | 0.935628E+09 | 510.54 | 0.285452E+10 | 0.921460E+09 | 0.00 | 0.40 | 11-FEB-16:30 | 0.00 | 01-FEB-00:10 | 5838.19 | 11-FEB-16:30 | 4032.43 | 11-FEB-16:30 | 1805.76 | 11-FEB-16:30 | 1449.72 | 11-FEB-16:20 | 0.00 | 01-FEB-00:10 |
| March | 0.546789E+10 | 0.134261E+10 | 604.67 | 0.400200E+10 | 0.146589E+10 | 0.00 | 0.42 | 13-MAR-16:25 | 0.00 | 01-MAR-02:70 | 6037.93 | 13-MAR-16:25 | 4538.02 | 13-MAR-16:30 | 1992.03 | 14-MAR-10:10 | 1554.88 | 13-MAR-16:25 | 0.00 | 01-MAR-00:10 |
| April | 0.759139E+10 | 0.189524E+10 | 713.87 | 0.579009E+10 | 0.180130E+10 | 0.00 | 0.49 | 15-APR-17:00 | 0.00 | 02-APR-06:50 | 6835.01 | 15-APR-17:00 | 5503.96 | 15-APR-17:00 | 1912.58 | 01-APR-16:05 | 1832.27 | 15-APR-17:00 | 0.00 | 01-APR-00:10 |
| May | 0.110067E+11 | 0.276081E+10 | 744.00 | 0.778663E+10 | 0.322005E+10 | 0.00 | 0.56 | 29-MAY-16:30 | 0.09 | 01-MAY-05:05 | 7983.91 | 29-MAY-16:30 | 5995.53 | 29-MAY-16:30 | 2163.08 | 28-MAY-15:10 | 2134.54 | 29-MAY-16:02 | 0.00 | 01-MAY-00:10 |
| June | 0.120599E+11 | 0.305036E+10 | 720.00 | 0.823900E+10 | 0.382089E+10 | 0.00 | 0.54 | 08-JUN-16:30 | 0.17 | 06-JUN-04:00 | 7949.69 | 08-JUN-16:30 | 5690.16 | 14-JUN-17:30 | 2528.40 | 08-JUN-16:13 | 2036.45 | 08-JUN-16:30 | 0.00 | 01-JUN-00:10 |
| July | 0.126069E+11 | 0.322774E+10 | 744.00 | 0.878112E+10 | 0.382581E+10 | 0.00 | 0.56 | 27-JUL-16:13 | 0.16 | 15-JUL-03:00 | 7778.65 | 27-JUL-16:13 | 6025.76 | 27-JUL-16:20 | 2373.64 | 22-JUL-15:30 | 2165.12 | 27-JUL-16:03 | 0.00 | 01-JUL-00:10 |
| August | 0.124388E+11 | 0.316274E+10 | 744.00 | 0.840388E+10 | 0.403492E+10 | 0.00 | 0.54 | 16-AUG-16:02 | 0.16 | 29-AUG-03:00 | 7871.19 | 16-AUG-16:02 | 5583.03 | 16-AUG-16:13 | 2444.33 | 13-AUG-15:30 | 2058.69 | 16-AUG-16:02 | 0.00 | 01-AUG-00:10 |
| September | 0.113784E+11 | 0.288586E+10 | 720.00 | 0.776356E+10 | 0.361484E+10 | 0.00 | 0.52 | 18-SEP-16:10 | 0.14 | 05-SEP-06:00 | 7562.81 | 18-SEP-16:10 | 5393.31 | 17-SEP-16:30 | 2338.69 | 18-SEP-18:00 | 1983.15 | 18-SEP-16:10 | 0.00 | 01-SEP-00:10 |
| October | 0.100129E+11 | 0.251266E+10 | 744.00 | 0.693250E+10 | 0.308045E+10 | 0.00 | 0.49 | 03-OCT-16:30 | 0.11 | 28-OCT-04:00 | 7134.29 | 03-OCT-16:30 | 4955.05 | 03-OCT-16:30 | 2437.89 | 29-OCT-14:20 | 1856.36 | 03-OCT-16:13 | 0.00 | 01-OCT-00:10 |
| November | 0.680300E+10 | 0.168345E+10 | 663.08 | 0.468981E+10 | 0.211320E+10 | 0.00 | 0.41 | 04-NOV-16:10 | 0.00 | 11-NOV-05:30 | 6011.01 | 04-NOV-16:10 | 3856.34 | 03-NOV-16:04 | 2376.29 | 04-NOV-16:20 | 1473.95 | 04-NOV-16:10 | 0.00 | 01-NOV-00:10 |
| December | 0.389676E+10 | 0.954731E+09 | 522.20 | 0.273016E+10 | 0.116660E+10 | 0.00 | 0.37 | 10-DEC-15:10 | 0.00 | 04-DEC-06:05 | 5302.78 | 10-DEC-15:10 | 3813.67 | 10-DEC-15:10 | 1647.20 | 25-DEC-16:10 | 1362.88 | 10-DEC-15:00 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.999261E+11 | 0.251259E+11 | 7937.83 | 0.701028E+11 | 0.298234E+11 | 0.00 | ||||||||||||||
| Minimum of Months | 0.288746E+10 | 0.714076E+09 | 507.46 | 0.212952E+10 | 0.757941E+09 | 0.00 | 0.31 | 0.00 | 4343.01 | 3162.32 | 1492.33 | 1128.67 | 0.00 | |||||||
| Maximum of Months | 0.126069E+11 | 0.322774E+10 | 744.00 | 0.878112E+10 | 0.403492E+10 | 0.00 | 0.56 | 0.17 | 7983.91 | 6025.76 | 2528.40 | 2165.12 | 0.00 |
Report: DXReportMonthly
For: SPLIT MSE COOLING COIL
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.507651E+10 | 0.125431E+10 | 633.72 | 0.405984E+10 | 0.101667E+10 | 0.00 | 0.50 | 02-JAN-14:40 | 0.00 | 05-JAN-06:05 | 6612.40 | 02-JAN-14:40 | 5291.45 | 02-JAN-14:30 | 1978.30 | 07-JAN-11:20 | 1686.82 | 02-JAN-14:40 | 0.00 | 01-JAN-00:10 |
| February | 0.543678E+10 | 0.134153E+10 | 582.77 | 0.429836E+10 | 0.113841E+10 | 0.00 | 0.51 | 11-FEB-14:00 | 0.00 | 01-FEB-00:10 | 6742.69 | 11-FEB-14:00 | 5005.11 | 11-FEB-14:00 | 1864.42 | 11-FEB-17:10 | 1718.73 | 11-FEB-14:00 | 0.00 | 01-FEB-00:10 |
| March | 0.666389E+10 | 0.163258E+10 | 664.32 | 0.501555E+10 | 0.164834E+10 | 0.00 | 0.47 | 04-MAR-14:00 | 0.00 | 01-MAR-03:20 | 6343.23 | 04-MAR-14:00 | 4534.60 | 13-MAR-16:20 | 2354.58 | 14-MAR-10:00 | 1573.62 | 04-MAR-14:00 | 0.00 | 01-MAR-00:10 |
| April | 0.825554E+10 | 0.205368E+10 | 715.03 | 0.633330E+10 | 0.192224E+10 | 0.00 | 0.49 | 15-APR-16:05 | 0.00 | 19-APR-02:20 | 6336.90 | 15-APR-16:03 | 5004.65 | 15-APR-16:15 | 1876.08 | 01-APR-16:05 | 1696.94 | 15-APR-16:05 | 0.00 | 01-APR-00:10 |
| May | 0.110042E+11 | 0.275267E+10 | 744.00 | 0.773940E+10 | 0.326481E+10 | 0.00 | 0.55 | 29-MAY-16:06 | 0.10 | 01-MAY-05:15 | 7180.69 | 29-MAY-16:10 | 5262.28 | 29-MAY-16:04 | 2234.90 | 28-MAY-12:00 | 1934.36 | 29-MAY-16:10 | 0.00 | 01-MAY-00:10 |
| June | 0.120267E+11 | 0.303153E+10 | 720.00 | 0.816863E+10 | 0.385811E+10 | 0.00 | 0.51 | 03-JUN-16:03 | 0.19 | 06-JUN-04:00 | 6878.84 | 08-JUN-16:02 | 4889.45 | 03-JUN-16:03 | 2311.71 | 08-JUN-16:02 | 1776.71 | 03-JUN-16:03 | 0.00 | 01-JUN-00:10 |
| July | 0.126185E+11 | 0.322028E+10 | 744.00 | 0.874663E+10 | 0.387189E+10 | 0.00 | 0.55 | 27-JUL-16:05 | 0.17 | 15-JUL-03:00 | 7369.42 | 30-JUL-16:05 | 5595.35 | 29-JUL-16:07 | 2301.88 | 22-JUL-15:40 | 1975.15 | 27-JUL-16:05 | 0.00 | 01-JUL-00:10 |
| August | 0.126779E+11 | 0.321201E+10 | 744.00 | 0.857307E+10 | 0.410483E+10 | 0.00 | 0.57 | 20-AUG-12:00 | 0.17 | 29-AUG-03:00 | 7667.68 | 20-AUG-12:00 | 5296.53 | 23-AUG-13:00 | 2503.92 | 13-AUG-13:20 | 2013.43 | 20-AUG-12:00 | 0.00 | 01-AUG-00:10 |
| September | 0.123933E+11 | 0.312588E+10 | 720.00 | 0.859409E+10 | 0.379921E+10 | 0.00 | 0.60 | 20-SEP-14:00 | 0.16 | 05-SEP-06:00 | 7985.54 | 20-SEP-14:00 | 5656.76 | 20-SEP-14:00 | 2369.28 | 18-SEP-18:00 | 2095.52 | 20-SEP-14:00 | 0.00 | 01-SEP-00:10 |
| October | 0.116870E+11 | 0.291600E+10 | 744.00 | 0.834055E+10 | 0.334645E+10 | 0.00 | 0.60 | 29-OCT-14:00 | 0.12 | 28-OCT-04:00 | 8189.11 | 29-OCT-14:00 | 5571.27 | 29-OCT-14:00 | 2634.38 | 29-OCT-14:10 | 2058.22 | 29-OCT-14:00 | 0.00 | 01-OCT-00:10 |
| November | 0.869749E+10 | 0.214027E+10 | 685.56 | 0.628537E+10 | 0.241211E+10 | 0.00 | 0.54 | 22-NOV-12:40 | 0.00 | 11-NOV-06:03 | 7272.88 | 22-NOV-12:30 | 5454.22 | 22-NOV-12:30 | 2487.11 | 04-NOV-16:20 | 1790.59 | 22-NOV-12:40 | 0.00 | 01-NOV-00:10 |
| December | 0.580494E+10 | 0.141969E+10 | 649.91 | 0.434278E+10 | 0.146216E+10 | 0.00 | 0.53 | 10-DEC-14:30 | 0.00 | 12-DEC-02:00 | 7043.84 | 10-DEC-14:30 | 5264.28 | 10-DEC-14:30 | 2009.55 | 10-DEC-09:30 | 1777.81 | 10-DEC-14:30 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.112343E+12 | 0.281004E+11 | 8347.31 | 0.804976E+11 | 0.318452E+11 | 0.00 | ||||||||||||||
| Minimum of Months | 0.507651E+10 | 0.125431E+10 | 582.77 | 0.405984E+10 | 0.101667E+10 | 0.00 | 0.47 | 0.00 | 6336.90 | 4534.60 | 1864.42 | 1573.62 | 0.00 | |||||||
| Maximum of Months | 0.126779E+11 | 0.322028E+10 | 744.00 | 0.874663E+10 | 0.410483E+10 | 0.00 | 0.60 | 0.19 | 8189.11 | 5656.76 | 2634.38 | 2095.52 | 0.00 |
Report: DXReportMonthly
For: SPLIT MNE COOLING COIL
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.298176E+10 | 0.736258E+09 | 514.26 | 0.219055E+10 | 0.791216E+09 | 0.00 | 0.33 | 07-JAN-13:00 | 0.00 | 05-JAN-06:05 | 4341.24 | 07-JAN-13:00 | 2998.60 | 07-JAN-13:00 | 1589.32 | 07-JAN-11:00 | 1107.59 | 07-JAN-13:00 | 0.00 | 01-JAN-00:10 |
| February | 0.379096E+10 | 0.938058E+09 | 514.53 | 0.284736E+10 | 0.943601E+09 | 0.00 | 0.36 | 11-FEB-14:00 | 0.00 | 01-FEB-00:10 | 4855.59 | 11-FEB-14:00 | 3392.63 | 11-FEB-14:00 | 1642.76 | 11-FEB-17:10 | 1256.22 | 11-FEB-14:00 | 0.00 | 01-FEB-00:10 |
| March | 0.542164E+10 | 0.132876E+10 | 607.92 | 0.393234E+10 | 0.148930E+10 | 0.00 | 0.40 | 13-MAR-16:12 | 0.00 | 01-MAR-02:00 | 5425.61 | 14-MAR-10:10 | 3856.13 | 13-MAR-16:50 | 2194.74 | 14-MAR-10:00 | 1353.36 | 13-MAR-16:12 | 0.00 | 01-MAR-00:10 |
| April | 0.758425E+10 | 0.189026E+10 | 714.00 | 0.575204E+10 | 0.183222E+10 | 0.00 | 0.45 | 15-APR-16:30 | 0.00 | 02-APR-06:50 | 5872.87 | 15-APR-16:30 | 4625.31 | 15-APR-16:50 | 1687.25 | 01-APR-16:05 | 1581.27 | 15-APR-16:30 | 0.00 | 01-APR-00:10 |
| May | 0.110296E+11 | 0.275946E+10 | 744.00 | 0.777177E+10 | 0.325784E+10 | 0.00 | 0.54 | 29-MAY-16:10 | 0.09 | 01-MAY-05:05 | 7200.47 | 22-MAY-15:30 | 5251.80 | 29-MAY-16:02 | 2174.17 | 28-MAY-12:00 | 1920.63 | 29-MAY-16:10 | 0.00 | 01-MAY-00:10 |
| June | 0.122737E+11 | 0.309296E+10 | 720.00 | 0.838782E+10 | 0.388585E+10 | 0.00 | 0.52 | 08-JUN-16:02 | 0.19 | 06-JUN-04:00 | 7109.13 | 08-JUN-16:02 | 4895.38 | 03-JUN-16:20 | 2379.92 | 08-JUN-16:02 | 1823.11 | 08-JUN-16:02 | 0.00 | 01-JUN-00:10 |
| July | 0.127416E+11 | 0.325162E+10 | 744.00 | 0.886552E+10 | 0.387603E+10 | 0.00 | 0.55 | 27-JUL-16:10 | 0.17 | 15-JUL-03:00 | 7125.28 | 30-JUL-16:05 | 5437.15 | 29-JUL-16:03 | 2282.36 | 13-JUL-13:20 | 1982.27 | 27-JUL-16:10 | 0.00 | 01-JUL-00:10 |
| August | 0.124428E+11 | 0.315475E+10 | 744.00 | 0.837814E+10 | 0.406467E+10 | 0.00 | 0.53 | 20-AUG-12:00 | 0.17 | 29-AUG-03:00 | 7166.91 | 20-AUG-12:00 | 4911.48 | 22-AUG-13:00 | 2401.57 | 13-AUG-13:20 | 1891.92 | 20-AUG-12:00 | 0.00 | 01-AUG-00:10 |
| September | 0.115320E+11 | 0.291463E+10 | 720.00 | 0.786095E+10 | 0.367104E+10 | 0.00 | 0.52 | 18-SEP-16:10 | 0.16 | 05-SEP-06:00 | 6998.60 | 18-SEP-16:10 | 4827.27 | 18-SEP-16:03 | 2308.71 | 18-SEP-18:00 | 1834.08 | 18-SEP-16:10 | 0.00 | 01-SEP-00:10 |
| October | 0.100858E+11 | 0.252466E+10 | 744.00 | 0.696116E+10 | 0.312461E+10 | 0.00 | 0.49 | 03-OCT-11:00 | 0.12 | 28-OCT-04:00 | 6730.12 | 03-OCT-11:00 | 4512.82 | 03-OCT-16:03 | 2361.60 | 03-OCT-10:20 | 1745.89 | 03-OCT-11:00 | 0.00 | 01-OCT-00:10 |
| November | 0.684266E+10 | 0.168902E+10 | 666.39 | 0.469305E+10 | 0.214961E+10 | 0.00 | 0.42 | 04-NOV-16:10 | 0.00 | 11-NOV-05:30 | 5840.96 | 04-NOV-16:10 | 3592.65 | 03-NOV-16:04 | 2315.82 | 04-NOV-16:10 | 1428.84 | 04-NOV-16:10 | 0.00 | 01-NOV-00:10 |
| December | 0.375743E+10 | 0.918933E+09 | 509.35 | 0.259789E+10 | 0.115955E+10 | 0.00 | 0.37 | 10-DEC-14:00 | 0.00 | 04-DEC-06:05 | 4881.58 | 10-DEC-14:00 | 3367.56 | 10-DEC-14:00 | 1623.64 | 24-DEC-10:40 | 1251.57 | 10-DEC-14:00 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.100484E+12 | 0.251994E+11 | 7942.45 | 0.702386E+11 | 0.302455E+11 | 0.00 | ||||||||||||||
| Minimum of Months | 0.298176E+10 | 0.736258E+09 | 509.35 | 0.219055E+10 | 0.791216E+09 | 0.00 | 0.33 | 0.00 | 4341.24 | 2998.60 | 1589.32 | 1107.59 | 0.00 | |||||||
| Maximum of Months | 0.127416E+11 | 0.325162E+10 | 744.00 | 0.886552E+10 | 0.406467E+10 | 0.00 | 0.55 | 0.19 | 7200.47 | 5437.15 | 2401.57 | 1982.27 | 0.00 |
Report: DXReportMonthly
For: SPLIT MN1 COOLING COIL
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.288000E+10 | 0.711774E+09 | 568.01 | 0.213517E+10 | 0.744832E+09 | 0.00 | 0.30 | 07-JAN-13:00 | 0.00 | 05-JAN-06:05 | 3564.45 | 07-JAN-13:00 | 2467.93 | 07-JAN-13:00 | 1274.89 | 07-JAN-10:30 | 913.10 | 07-JAN-13:00 | 0.00 | 01-JAN-00:10 |
| February | 0.345135E+10 | 0.854136E+09 | 547.95 | 0.259434E+10 | 0.857007E+09 | 0.00 | 0.34 | 11-FEB-17:10 | 0.00 | 01-FEB-00:10 | 4101.15 | 11-FEB-17:10 | 2726.13 | 11-FEB-17:10 | 1375.02 | 11-FEB-17:10 | 1019.39 | 11-FEB-14:00 | 0.00 | 01-FEB-00:10 |
| March | 0.470946E+10 | 0.115617E+10 | 627.72 | 0.342553E+10 | 0.128393E+10 | 0.00 | 0.36 | 13-MAR-16:12 | 0.00 | 01-MAR-03:20 | 4299.07 | 13-MAR-16:12 | 3154.09 | 13-MAR-16:50 | 1599.12 | 14-MAR-10:10 | 1115.94 | 13-MAR-16:12 | 0.00 | 01-MAR-00:10 |
| April | 0.635198E+10 | 0.158504E+10 | 718.17 | 0.479335E+10 | 0.155864E+10 | 0.00 | 0.40 | 15-APR-17:00 | 0.00 | 02-APR-06:50 | 4674.83 | 15-APR-17:00 | 3668.76 | 15-APR-17:00 | 1418.08 | 01-APR-16:05 | 1267.53 | 15-APR-17:00 | 0.00 | 01-APR-00:10 |
| May | 0.914220E+10 | 0.229197E+10 | 744.00 | 0.641942E+10 | 0.272278E+10 | 0.00 | 0.48 | 29-MAY-16:04 | 0.12 | 01-MAY-05:05 | 5681.26 | 29-MAY-17:10 | 4186.81 | 29-MAY-16:20 | 1800.75 | 24-MAY-17:05 | 1542.74 | 29-MAY-16:04 | 0.00 | 01-MAY-00:10 |
| June | 0.101757E+11 | 0.257045E+10 | 720.00 | 0.689316E+10 | 0.328255E+10 | 0.00 | 0.47 | 08-JUN-16:13 | 0.20 | 06-JUN-04:00 | 5672.93 | 08-JUN-16:13 | 3913.71 | 29-JUN-17:17 | 1898.72 | 08-JUN-16:13 | 1466.85 | 08-JUN-16:13 | 0.00 | 01-JUN-00:10 |
| July | 0.105834E+11 | 0.270414E+10 | 744.00 | 0.725970E+10 | 0.332369E+10 | 0.00 | 0.49 | 27-JUL-16:13 | 0.19 | 15-JUL-03:00 | 5675.67 | 27-JUL-18:00 | 4291.10 | 29-JUL-16:03 | 1857.27 | 25-JUL-16:02 | 1592.48 | 27-JUL-16:03 | 0.00 | 01-JUL-00:10 |
| August | 0.104199E+11 | 0.264579E+10 | 744.00 | 0.695621E+10 | 0.346367E+10 | 0.00 | 0.46 | 16-AUG-16:02 | 0.18 | 29-AUG-03:00 | 5534.20 | 16-AUG-16:02 | 3812.40 | 16-AUG-16:03 | 1862.01 | 13-AUG-16:03 | 1462.85 | 16-AUG-16:02 | 0.00 | 01-AUG-00:10 |
| September | 0.962371E+10 | 0.243589E+10 | 720.00 | 0.650103E+10 | 0.312268E+10 | 0.00 | 0.46 | 18-SEP-16:10 | 0.18 | 05-SEP-06:00 | 5573.07 | 18-SEP-16:20 | 3843.67 | 18-SEP-16:03 | 1842.78 | 18-SEP-18:00 | 1472.35 | 18-SEP-16:10 | 0.00 | 01-SEP-00:10 |
| October | 0.857230E+10 | 0.214706E+10 | 744.00 | 0.589070E+10 | 0.268160E+10 | 0.00 | 0.44 | 03-OCT-16:03 | 0.14 | 28-OCT-04:00 | 5273.48 | 03-OCT-16:03 | 3608.24 | 03-OCT-16:03 | 1877.39 | 01-OCT-12:50 | 1384.85 | 03-OCT-16:03 | 0.00 | 01-OCT-00:10 |
| November | 0.607417E+10 | 0.150105E+10 | 680.88 | 0.419461E+10 | 0.187956E+10 | 0.00 | 0.39 | 04-NOV-16:10 | 0.00 | 11-NOV-06:03 | 4844.13 | 04-NOV-16:10 | 3005.95 | 03-NOV-16:04 | 1870.19 | 04-NOV-16:20 | 1192.78 | 04-NOV-16:10 | 0.00 | 01-NOV-00:10 |
| December | 0.365767E+10 | 0.895680E+09 | 597.53 | 0.256547E+10 | 0.109221E+10 | 0.00 | 0.33 | 10-DEC-14:00 | 0.00 | 12-DEC-03:10 | 3939.16 | 10-DEC-14:00 | 2736.13 | 10-DEC-15:00 | 1385.74 | 25-DEC-22:00 | 1015.32 | 10-DEC-14:00 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.856418E+11 | 0.214991E+11 | 8156.26 | 0.596287E+11 | 0.260131E+11 | 0.00 | ||||||||||||||
| Minimum of Months | 0.288000E+10 | 0.711774E+09 | 547.95 | 0.213517E+10 | 0.744832E+09 | 0.00 | 0.30 | 0.00 | 3564.45 | 2467.93 | 1274.89 | 913.10 | 0.00 | |||||||
| Maximum of Months | 0.105834E+11 | 0.270414E+10 | 744.00 | 0.725970E+10 | 0.346367E+10 | 0.00 | 0.49 | 0.20 | 5681.26 | 4291.10 | 1898.72 | 1592.48 | 0.00 |
Report: DXReportMonthly
For: SPLIT MN2 COOLING COIL
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.288817E+10 | 0.713799E+09 | 568.96 | 0.214207E+10 | 0.746101E+09 | 0.00 | 0.30 | 07-JAN-13:00 | 0.00 | 05-JAN-06:05 | 3569.06 | 07-JAN-13:00 | 2471.69 | 07-JAN-13:00 | 1276.13 | 07-JAN-10:30 | 914.21 | 07-JAN-13:00 | 0.00 | 01-JAN-00:10 |
| February | 0.345433E+10 | 0.854869E+09 | 548.40 | 0.259680E+10 | 0.857529E+09 | 0.00 | 0.34 | 11-FEB-17:10 | 0.00 | 01-FEB-00:10 | 4083.30 | 11-FEB-17:10 | 2720.22 | 11-FEB-14:00 | 1371.22 | 11-FEB-17:10 | 1019.78 | 11-FEB-14:00 | 0.00 | 01-FEB-00:10 |
| March | 0.471263E+10 | 0.115695E+10 | 628.76 | 0.342814E+10 | 0.128449E+10 | 0.00 | 0.36 | 13-MAR-16:12 | 0.00 | 01-MAR-03:20 | 4289.21 | 13-MAR-16:12 | 3144.01 | 13-MAR-16:50 | 1602.95 | 14-MAR-10:10 | 1113.42 | 13-MAR-16:12 | 0.00 | 01-MAR-00:10 |
| April | 0.635171E+10 | 0.158494E+10 | 718.17 | 0.479279E+10 | 0.155891E+10 | 0.00 | 0.40 | 15-APR-17:00 | 0.00 | 02-APR-06:50 | 4663.33 | 15-APR-17:00 | 3659.06 | 15-APR-17:00 | 1414.22 | 01-APR-16:05 | 1264.49 | 15-APR-17:00 | 0.00 | 01-APR-00:10 |
| May | 0.914277E+10 | 0.229204E+10 | 744.00 | 0.641951E+10 | 0.272326E+10 | 0.00 | 0.48 | 29-MAY-16:04 | 0.12 | 01-MAY-05:05 | 5667.12 | 29-MAY-17:10 | 4178.12 | 29-MAY-16:20 | 1800.64 | 24-MAY-17:05 | 1540.18 | 29-MAY-16:04 | 0.00 | 01-MAY-00:10 |
| June | 0.101834E+11 | 0.257221E+10 | 720.00 | 0.689920E+10 | 0.328422E+10 | 0.00 | 0.47 | 08-JUN-16:13 | 0.20 | 06-JUN-04:00 | 5666.46 | 08-JUN-16:13 | 3902.77 | 29-JUN-17:17 | 1896.64 | 08-JUN-16:13 | 1465.16 | 08-JUN-16:13 | 0.00 | 01-JUN-00:10 |
| July | 0.105879E+11 | 0.270515E+10 | 744.00 | 0.726315E+10 | 0.332480E+10 | 0.00 | 0.49 | 27-JUL-16:13 | 0.19 | 15-JUL-03:00 | 5665.02 | 27-JUL-18:00 | 4287.49 | 29-JUL-16:03 | 1857.47 | 25-JUL-16:02 | 1590.39 | 27-JUL-16:03 | 0.00 | 01-JUL-00:10 |
| August | 0.104200E+11 | 0.264570E+10 | 744.00 | 0.695595E+10 | 0.346409E+10 | 0.00 | 0.46 | 16-AUG-16:02 | 0.18 | 29-AUG-03:00 | 5524.46 | 16-AUG-16:02 | 3804.96 | 16-AUG-16:03 | 1859.42 | 13-AUG-16:03 | 1460.30 | 16-AUG-16:02 | 0.00 | 01-AUG-00:10 |
| September | 0.962919E+10 | 0.243712E+10 | 720.00 | 0.650517E+10 | 0.312402E+10 | 0.00 | 0.46 | 18-SEP-16:10 | 0.18 | 05-SEP-06:00 | 5564.87 | 18-SEP-16:20 | 3837.58 | 18-SEP-16:03 | 1841.78 | 18-SEP-18:00 | 1470.34 | 18-SEP-16:10 | 0.00 | 01-SEP-00:10 |
| October | 0.857482E+10 | 0.214761E+10 | 744.00 | 0.589236E+10 | 0.268246E+10 | 0.00 | 0.44 | 03-OCT-16:03 | 0.14 | 28-OCT-04:00 | 5269.39 | 03-OCT-16:03 | 3604.98 | 03-OCT-16:03 | 1877.44 | 01-OCT-12:50 | 1383.72 | 03-OCT-16:03 | 0.00 | 01-OCT-00:10 |
| November | 0.607698E+10 | 0.150169E+10 | 681.07 | 0.419670E+10 | 0.188027E+10 | 0.00 | 0.39 | 04-NOV-16:10 | 0.00 | 11-NOV-06:03 | 4844.10 | 04-NOV-16:10 | 3003.01 | 03-NOV-16:04 | 1869.90 | 04-NOV-16:20 | 1192.70 | 04-NOV-16:10 | 0.00 | 01-NOV-00:10 |
| December | 0.365230E+10 | 0.894346E+09 | 597.19 | 0.256102E+10 | 0.109127E+10 | 0.00 | 0.33 | 10-DEC-14:00 | 0.00 | 12-DEC-03:10 | 3939.99 | 10-DEC-14:00 | 2732.58 | 10-DEC-15:00 | 1384.47 | 25-DEC-22:00 | 1015.48 | 10-DEC-14:00 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.856743E+11 | 0.215064E+11 | 8158.55 | 0.596529E+11 | 0.260214E+11 | 0.00 | ||||||||||||||
| Minimum of Months | 0.288817E+10 | 0.713799E+09 | 548.40 | 0.214207E+10 | 0.746101E+09 | 0.00 | 0.30 | 0.00 | 3569.06 | 2471.69 | 1276.13 | 914.21 | 0.00 | |||||||
| Maximum of Months | 0.105879E+11 | 0.270515E+10 | 744.00 | 0.726315E+10 | 0.346409E+10 | 0.00 | 0.49 | 0.20 | 5667.12 | 4287.49 | 1896.64 | 1590.39 | 0.00 |
Report: DXReportMonthly
For: SPLIT MS1 COOLING COIL
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.507582E+10 | 0.125563E+10 | 702.94 | 0.411339E+10 | 0.962431E+09 | 0.00 | 0.50 | 02-JAN-14:40 | 0.00 | 05-JAN-06:05 | 5863.35 | 02-JAN-14:40 | 4710.77 | 02-JAN-14:30 | 1658.94 | 07-JAN-11:30 | 1496.76 | 02-JAN-14:40 | 0.00 | 01-JAN-00:10 |
| February | 0.516884E+10 | 0.127744E+10 | 626.22 | 0.412962E+10 | 0.103922E+10 | 0.00 | 0.49 | 11-FEB-14:00 | 0.00 | 03-FEB-00:50 | 5793.26 | 11-FEB-14:30 | 4322.51 | 11-FEB-14:30 | 1569.00 | 11-FEB-17:10 | 1480.37 | 11-FEB-14:00 | 0.00 | 01-FEB-00:10 |
| March | 0.597662E+10 | 0.146754E+10 | 686.61 | 0.454071E+10 | 0.143591E+10 | 0.00 | 0.43 | 13-MAR-16:02 | 0.00 | 11-MAR-04:00 | 5127.94 | 04-MAR-14:00 | 3833.60 | 13-MAR-16:15 | 1761.31 | 14-MAR-10:00 | 1306.14 | 13-MAR-16:02 | 0.00 | 01-MAR-00:10 |
| April | 0.702358E+10 | 0.174993E+10 | 718.58 | 0.537942E+10 | 0.164416E+10 | 0.00 | 0.44 | 15-APR-16:30 | 0.00 | 19-APR-06:00 | 5303.73 | 01-APR-16:05 | 4024.55 | 15-APR-16:30 | 1594.70 | 01-APR-16:05 | 1377.75 | 15-APR-16:30 | 0.00 | 01-APR-00:10 |
| May | 0.910908E+10 | 0.228346E+10 | 744.00 | 0.638686E+10 | 0.272223E+10 | 0.00 | 0.49 | 29-MAY-16:04 | 0.12 | 01-MAY-05:05 | 5722.09 | 29-MAY-16:04 | 4193.55 | 29-MAY-16:04 | 1804.34 | 28-MAY-12:00 | 1555.05 | 29-MAY-16:04 | 0.00 | 01-MAY-00:10 |
| June | 0.991695E+10 | 0.250569E+10 | 720.00 | 0.667196E+10 | 0.324499E+10 | 0.00 | 0.46 | 03-JUN-16:03 | 0.20 | 06-JUN-04:00 | 5427.98 | 08-JUN-16:02 | 3846.29 | 03-JUN-16:30 | 1831.09 | 18-JUN-20:40 | 1426.99 | 03-JUN-16:03 | 0.00 | 01-JUN-00:10 |
| July | 0.104499E+11 | 0.267023E+10 | 744.00 | 0.713916E+10 | 0.331075E+10 | 0.00 | 0.49 | 29-JUL-16:03 | 0.19 | 15-JUL-03:00 | 5811.64 | 22-JUL-16:03 | 4445.21 | 29-JUL-16:03 | 1871.20 | 22-JUL-16:03 | 1584.18 | 27-JUL-16:02 | 0.00 | 01-JUL-00:10 |
| August | 0.106498E+11 | 0.270275E+10 | 744.00 | 0.715146E+10 | 0.349831E+10 | 0.00 | 0.49 | 20-AUG-12:00 | 0.19 | 29-AUG-03:00 | 5901.70 | 20-AUG-12:00 | 4099.69 | 31-AUG-15:10 | 1945.68 | 13-AUG-16:03 | 1565.13 | 20-AUG-12:00 | 0.00 | 01-AUG-00:10 |
| September | 0.104877E+11 | 0.265038E+10 | 720.00 | 0.723866E+10 | 0.324906E+10 | 0.00 | 0.54 | 20-SEP-14:00 | 0.18 | 05-SEP-06:00 | 6437.74 | 20-SEP-14:00 | 4586.25 | 20-SEP-14:10 | 1896.45 | 18-SEP-18:20 | 1704.65 | 20-SEP-14:00 | 0.00 | 01-SEP-00:10 |
| October | 0.101819E+11 | 0.254352E+10 | 744.00 | 0.728233E+10 | 0.289955E+10 | 0.00 | 0.56 | 29-OCT-14:00 | 0.15 | 28-OCT-04:00 | 6785.78 | 29-OCT-14:10 | 4689.74 | 29-OCT-14:00 | 2106.49 | 29-OCT-14:10 | 1718.80 | 29-OCT-14:10 | 0.00 | 01-OCT-00:10 |
| November | 0.794921E+10 | 0.195896E+10 | 699.61 | 0.582032E+10 | 0.212889E+10 | 0.00 | 0.51 | 22-NOV-12:30 | 0.00 | 11-NOV-06:03 | 6089.64 | 22-NOV-12:30 | 4625.90 | 22-NOV-12:30 | 2025.94 | 04-NOV-16:20 | 1508.07 | 22-NOV-12:40 | 0.00 | 01-NOV-00:10 |
| December | 0.582361E+10 | 0.142626E+10 | 691.65 | 0.444238E+10 | 0.138123E+10 | 0.00 | 0.51 | 10-DEC-14:30 | 0.00 | 12-DEC-04:00 | 6091.73 | 10-DEC-14:30 | 4627.06 | 10-DEC-14:40 | 1658.74 | 25-DEC-22:00 | 1543.71 | 10-DEC-14:30 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.978130E+11 | 0.244918E+11 | 8541.61 | 0.702962E+11 | 0.275167E+11 | 0.00 | ||||||||||||||
| Minimum of Months | 0.507582E+10 | 0.125563E+10 | 626.22 | 0.411339E+10 | 0.962431E+09 | 0.00 | 0.43 | 0.00 | 5127.94 | 3833.60 | 1569.00 | 1306.14 | 0.00 | |||||||
| Maximum of Months | 0.106498E+11 | 0.270275E+10 | 744.00 | 0.728233E+10 | 0.349831E+10 | 0.00 | 0.56 | 0.20 | 6785.78 | 4710.77 | 2106.49 | 1718.80 | 0.00 |
Report: DXReportMonthly
For: SPLIT MS2 COOLING COIL
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.508180E+10 | 0.125703E+10 | 702.57 | 0.411848E+10 | 0.963313E+09 | 0.00 | 0.50 | 02-JAN-14:40 | 0.00 | 05-JAN-06:05 | 5869.17 | 02-JAN-14:40 | 4717.56 | 02-JAN-14:30 | 1660.22 | 07-JAN-11:30 | 1498.03 | 02-JAN-14:40 | 0.00 | 01-JAN-00:10 |
| February | 0.517135E+10 | 0.127800E+10 | 626.34 | 0.413170E+10 | 0.103965E+10 | 0.00 | 0.49 | 11-FEB-14:00 | 0.00 | 03-FEB-00:50 | 5791.65 | 11-FEB-14:30 | 4321.59 | 11-FEB-14:20 | 1566.26 | 11-FEB-17:10 | 1480.62 | 11-FEB-14:00 | 0.00 | 01-FEB-00:10 |
| March | 0.597930E+10 | 0.146817E+10 | 687.21 | 0.454304E+10 | 0.143626E+10 | 0.00 | 0.43 | 13-MAR-16:02 | 0.00 | 11-MAR-03:50 | 5134.17 | 04-MAR-14:00 | 3825.67 | 13-MAR-16:15 | 1764.96 | 14-MAR-10:00 | 1303.94 | 13-MAR-16:02 | 0.00 | 01-MAR-00:10 |
| April | 0.702339E+10 | 0.174983E+10 | 718.58 | 0.537889E+10 | 0.164450E+10 | 0.00 | 0.44 | 15-APR-16:30 | 0.00 | 19-APR-06:00 | 5290.35 | 01-APR-16:05 | 4017.02 | 15-APR-16:30 | 1591.74 | 01-APR-16:05 | 1375.32 | 15-APR-16:30 | 0.00 | 01-APR-00:10 |
| May | 0.910969E+10 | 0.228353E+10 | 744.00 | 0.638695E+10 | 0.272274E+10 | 0.00 | 0.49 | 29-MAY-16:04 | 0.12 | 01-MAY-05:05 | 5712.56 | 29-MAY-16:04 | 4185.70 | 29-MAY-16:04 | 1805.31 | 28-MAY-12:00 | 1552.48 | 29-MAY-16:04 | 0.00 | 01-MAY-00:10 |
| June | 0.992481E+10 | 0.250749E+10 | 720.00 | 0.667805E+10 | 0.324676E+10 | 0.00 | 0.46 | 03-JUN-16:03 | 0.20 | 06-JUN-04:00 | 5425.15 | 03-JUN-16:03 | 3847.36 | 03-JUN-16:30 | 1830.72 | 18-JUN-20:40 | 1427.11 | 03-JUN-16:03 | 0.00 | 01-JUN-00:10 |
| July | 0.104545E+11 | 0.267126E+10 | 744.00 | 0.714261E+10 | 0.331190E+10 | 0.00 | 0.49 | 29-JUL-16:03 | 0.19 | 15-JUL-03:00 | 5805.92 | 22-JUL-16:03 | 4441.53 | 29-JUL-16:03 | 1869.57 | 22-JUL-16:03 | 1582.12 | 27-JUL-16:02 | 0.00 | 01-JUL-00:10 |
| August | 0.106499E+11 | 0.270265E+10 | 744.00 | 0.715117E+10 | 0.349875E+10 | 0.00 | 0.50 | 20-AUG-12:00 | 0.19 | 29-AUG-03:00 | 5913.28 | 20-AUG-12:00 | 4098.82 | 31-AUG-15:10 | 1943.18 | 13-AUG-16:03 | 1567.91 | 20-AUG-12:00 | 0.00 | 01-AUG-00:10 |
| September | 0.104930E+11 | 0.265151E+10 | 720.00 | 0.724266E+10 | 0.325033E+10 | 0.00 | 0.54 | 20-SEP-14:00 | 0.19 | 05-SEP-06:00 | 6440.30 | 20-SEP-14:00 | 4588.20 | 20-SEP-14:10 | 1895.72 | 18-SEP-18:20 | 1705.13 | 20-SEP-14:00 | 0.00 | 01-SEP-00:10 |
| October | 0.101841E+11 | 0.254392E+10 | 744.00 | 0.728377E+10 | 0.290034E+10 | 0.00 | 0.56 | 29-OCT-14:00 | 0.15 | 28-OCT-04:00 | 6786.81 | 29-OCT-14:10 | 4691.99 | 29-OCT-14:00 | 2106.08 | 29-OCT-14:10 | 1718.95 | 29-OCT-14:00 | 0.00 | 01-OCT-00:10 |
| November | 0.795131E+10 | 0.195935E+10 | 699.61 | 0.582180E+10 | 0.212951E+10 | 0.00 | 0.51 | 22-NOV-12:30 | 0.00 | 11-NOV-06:03 | 6103.73 | 22-NOV-12:30 | 4638.74 | 22-NOV-12:30 | 2025.68 | 04-NOV-16:20 | 1511.11 | 22-NOV-12:40 | 0.00 | 01-NOV-00:10 |
| December | 0.581936E+10 | 0.142517E+10 | 691.19 | 0.443847E+10 | 0.138090E+10 | 0.00 | 0.51 | 10-DEC-14:30 | 0.00 | 12-DEC-04:00 | 6089.82 | 10-DEC-14:30 | 4624.74 | 10-DEC-14:40 | 1657.63 | 25-DEC-22:00 | 1543.11 | 10-DEC-14:30 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.978425E+11 | 0.244979E+11 | 8541.50 | 0.703176E+11 | 0.275249E+11 | 0.00 | ||||||||||||||
| Minimum of Months | 0.508180E+10 | 0.125703E+10 | 626.34 | 0.411848E+10 | 0.963313E+09 | 0.00 | 0.43 | 0.00 | 5134.17 | 3825.67 | 1566.26 | 1303.94 | 0.00 | |||||||
| Maximum of Months | 0.106499E+11 | 0.270265E+10 | 744.00 | 0.728377E+10 | 0.349875E+10 | 0.00 | 0.56 | 0.20 | 6786.81 | 4717.56 | 2106.08 | 1718.95 | 0.00 |
Report: DXReportMonthly
For: SPLIT TSW COOLING COIL
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.213127E+10 | 0.526675E+09 | 455.65 | 0.170224E+10 | 0.429033E+09 | 0.00 | 0.55 | 02-JAN-15:00 | 0.00 | 01-JAN-05:20 | 4378.78 | 02-JAN-15:00 | 3540.03 | 02-JAN-14:40 | 1139.96 | 07-JAN-11:30 | 1108.54 | 02-JAN-15:00 | 0.00 | 01-JAN-00:10 |
| February | 0.259960E+10 | 0.641934E+09 | 468.67 | 0.207600E+10 | 0.523605E+09 | 0.00 | 0.59 | 11-FEB-16:20 | 0.00 | 01-FEB-00:10 | 4794.63 | 11-FEB-16:20 | 3628.28 | 11-FEB-15:00 | 1199.83 | 11-FEB-16:30 | 1177.93 | 11-FEB-15:00 | 0.00 | 01-FEB-00:10 |
| March | 0.333712E+10 | 0.817601E+09 | 587.53 | 0.252717E+10 | 0.809950E+09 | 0.00 | 0.54 | 13-MAR-16:25 | 0.00 | 01-MAR-00:20 | 4262.64 | 13-MAR-16:25 | 3364.62 | 13-MAR-16:30 | 1319.28 | 14-MAR-10:10 | 1084.46 | 13-MAR-16:25 | 0.00 | 01-MAR-00:10 |
| April | 0.434081E+10 | 0.108203E+10 | 691.83 | 0.336768E+10 | 0.973128E+09 | 0.00 | 0.60 | 15-APR-16:30 | 0.00 | 02-APR-02:00 | 4729.40 | 15-APR-16:30 | 3883.63 | 15-APR-16:30 | 1233.14 | 01-APR-15:40 | 1247.27 | 15-APR-16:30 | 0.00 | 01-APR-00:10 |
| May | 0.609319E+10 | 0.152885E+10 | 744.00 | 0.432973E+10 | 0.176345E+10 | 0.00 | 0.66 | 29-MAY-16:04 | 0.02 | 01-MAY-05:40 | 5238.86 | 29-MAY-16:20 | 4006.63 | 29-MAY-16:04 | 1344.67 | 28-MAY-12:00 | 1388.93 | 29-MAY-16:04 | 0.00 | 01-MAY-00:10 |
| June | 0.664999E+10 | 0.168227E+10 | 720.00 | 0.455542E+10 | 0.209457E+10 | 0.00 | 0.61 | 08-JUN-16:02 | 0.11 | 06-JUN-04:00 | 4966.94 | 08-JUN-16:02 | 3590.22 | 10-JUN-16:05 | 1489.22 | 08-JUN-16:02 | 1262.12 | 08-JUN-16:02 | 0.00 | 01-JUN-00:10 |
| July | 0.704621E+10 | 0.180585E+10 | 744.00 | 0.495689E+10 | 0.208932E+10 | 0.00 | 0.65 | 27-JUL-16:10 | 0.09 | 15-JUL-03:00 | 5086.59 | 22-JUL-15:40 | 4136.48 | 29-JUL-16:03 | 1459.60 | 22-JUL-15:30 | 1399.51 | 27-JUL-16:10 | 0.00 | 01-JUL-00:10 |
| August | 0.705599E+10 | 0.179331E+10 | 744.00 | 0.482384E+10 | 0.223214E+10 | 0.00 | 0.64 | 16-AUG-16:02 | 0.10 | 29-AUG-06:00 | 5176.66 | 16-AUG-16:02 | 3836.49 | 31-AUG-15:30 | 1572.27 | 13-AUG-13:30 | 1338.39 | 16-AUG-16:02 | 0.00 | 01-AUG-00:10 |
| September | 0.678332E+10 | 0.171858E+10 | 720.00 | 0.474763E+10 | 0.203569E+10 | 0.00 | 0.67 | 20-SEP-14:10 | 0.08 | 05-SEP-06:00 | 5400.27 | 17-SEP-16:10 | 4102.87 | 30-SEP-15:30 | 1469.00 | 19-SEP-14:20 | 1399.35 | 20-SEP-14:10 | 0.00 | 01-SEP-00:10 |
| October | 0.617146E+10 | 0.154641E+10 | 744.00 | 0.442767E+10 | 0.174379E+10 | 0.00 | 0.66 | 29-OCT-14:10 | 0.04 | 28-OCT-04:00 | 5492.47 | 29-OCT-14:10 | 3842.28 | 25-OCT-15:10 | 1650.23 | 29-OCT-14:10 | 1368.59 | 29-OCT-14:10 | 0.00 | 01-OCT-00:10 |
| November | 0.437008E+10 | 0.107858E+10 | 625.37 | 0.316307E+10 | 0.120701E+10 | 0.00 | 0.57 | 10-NOV-14:30 | 0.00 | 01-NOV-04:50 | 4569.94 | 22-NOV-14:30 | 3641.03 | 07-NOV-15:30 | 1494.88 | 04-NOV-16:20 | 1139.78 | 10-NOV-14:30 | 0.00 | 01-NOV-00:10 |
| December | 0.275504E+10 | 0.672931E+09 | 493.43 | 0.206173E+10 | 0.693305E+09 | 0.00 | 0.59 | 10-DEC-15:00 | 0.00 | 03-DEC-06:05 | 4717.85 | 10-DEC-15:00 | 3648.24 | 10-DEC-15:00 | 1161.24 | 10-DEC-12:30 | 1182.86 | 10-DEC-15:00 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.593341E+11 | 0.148950E+11 | 7738.48 | 0.427391E+11 | 0.165950E+11 | 0.00 | ||||||||||||||
| Minimum of Months | 0.213127E+10 | 0.526675E+09 | 455.65 | 0.170224E+10 | 0.429033E+09 | 0.00 | 0.54 | 0.00 | 4262.64 | 3364.62 | 1139.96 | 1084.46 | 0.00 | |||||||
| Maximum of Months | 0.705599E+10 | 0.180585E+10 | 744.00 | 0.495689E+10 | 0.223214E+10 | 0.00 | 0.67 | 0.11 | 5492.47 | 4136.48 | 1650.23 | 1399.51 | 0.00 |
Report: DXReportMonthly
For: SPLIT TNW COOLING COIL
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.120449E+10 | 0.297942E+09 | 359.43 | 0.877236E+09 | 0.327250E+09 | 0.00 | 0.35 | 02-JAN-15:00 | 0.00 | 01-JAN-03:10 | 2762.94 | 02-JAN-15:00 | 2046.20 | 02-JAN-15:00 | 881.25 | 07-JAN-11:20 | 715.15 | 02-JAN-15:00 | 0.00 | 01-JAN-00:10 |
| February | 0.179903E+10 | 0.446227E+09 | 423.92 | 0.136216E+10 | 0.436868E+09 | 0.00 | 0.46 | 11-FEB-16:20 | 0.00 | 01-FEB-00:10 | 3762.52 | 11-FEB-16:20 | 2673.75 | 11-FEB-16:20 | 1088.76 | 11-FEB-16:20 | 930.98 | 11-FEB-16:20 | 0.00 | 01-FEB-00:10 |
| March | 0.275224E+10 | 0.675592E+09 | 551.33 | 0.201151E+10 | 0.740729E+09 | 0.00 | 0.48 | 13-MAR-16:25 | 0.00 | 01-MAR-00:10 | 3861.64 | 13-MAR-16:25 | 2971.52 | 13-MAR-16:25 | 1209.74 | 14-MAR-10:10 | 988.43 | 13-MAR-16:25 | 0.00 | 01-MAR-00:10 |
| April | 0.398480E+10 | 0.996161E+09 | 690.47 | 0.305264E+10 | 0.932158E+09 | 0.00 | 0.56 | 15-APR-16:40 | 0.00 | 02-APR-01:50 | 4444.69 | 15-APR-16:40 | 3639.11 | 15-APR-16:40 | 1135.98 | 01-APR-15:40 | 1179.93 | 15-APR-16:40 | 0.00 | 01-APR-00:10 |
| May | 0.611829E+10 | 0.153627E+10 | 744.00 | 0.435252E+10 | 0.176577E+10 | 0.00 | 0.65 | 29-MAY-16:30 | 0.02 | 01-MAY-05:40 | 5243.84 | 29-MAY-16:30 | 4026.37 | 29-MAY-16:30 | 1338.85 | 22-MAY-15:30 | 1385.75 | 29-MAY-16:20 | 0.00 | 01-MAY-00:10 |
| June | 0.679097E+10 | 0.171845E+10 | 720.00 | 0.467714E+10 | 0.211383E+10 | 0.00 | 0.62 | 08-JUN-16:13 | 0.11 | 06-JUN-04:00 | 5123.90 | 08-JUN-16:13 | 3752.33 | 14-JUN-17:17 | 1526.61 | 08-JUN-16:02 | 1300.72 | 08-JUN-16:13 | 0.00 | 01-JUN-00:10 |
| July | 0.711956E+10 | 0.182573E+10 | 744.00 | 0.502345E+10 | 0.209611E+10 | 0.00 | 0.64 | 27-JUL-16:10 | 0.09 | 15-JUL-03:00 | 5077.94 | 27-JUL-16:10 | 4039.47 | 27-JUL-16:08 | 1433.85 | 22-JUL-15:30 | 1399.67 | 27-JUL-16:10 | 0.00 | 01-JUL-00:10 |
| August | 0.693289E+10 | 0.176457E+10 | 744.00 | 0.471635E+10 | 0.221654E+10 | 0.00 | 0.62 | 16-AUG-16:02 | 0.10 | 29-AUG-06:00 | 5076.09 | 16-AUG-16:02 | 3698.34 | 16-AUG-16:03 | 1515.34 | 13-AUG-13:30 | 1315.64 | 16-AUG-16:02 | 0.00 | 01-AUG-00:10 |
| September | 0.632140E+10 | 0.160634E+10 | 720.00 | 0.434614E+10 | 0.197527E+10 | 0.00 | 0.59 | 17-SEP-16:15 | 0.07 | 05-SEP-06:00 | 4874.66 | 17-SEP-16:15 | 3564.69 | 17-SEP-16:20 | 1398.02 | 19-SEP-14:20 | 1258.34 | 17-SEP-16:15 | 0.00 | 01-SEP-00:10 |
| October | 0.532488E+10 | 0.133979E+10 | 744.00 | 0.368915E+10 | 0.163573E+10 | 0.00 | 0.55 | 03-OCT-16:17 | 0.04 | 28-OCT-04:00 | 4491.33 | 03-OCT-16:17 | 3184.90 | 03-OCT-16:17 | 1504.21 | 29-OCT-14:20 | 1163.73 | 03-OCT-14:40 | 0.00 | 01-OCT-00:10 |
| November | 0.342357E+10 | 0.848625E+09 | 603.08 | 0.234623E+10 | 0.107734E+10 | 0.00 | 0.43 | 03-NOV-16:10 | 0.00 | 01-NOV-04:50 | 3578.11 | 04-NOV-16:20 | 2471.22 | 03-NOV-14:20 | 1409.55 | 04-NOV-16:20 | 893.04 | 03-NOV-14:10 | 0.00 | 01-NOV-00:10 |
| December | 0.182309E+10 | 0.446726E+09 | 414.53 | 0.126428E+10 | 0.558807E+09 | 0.00 | 0.42 | 10-DEC-15:00 | 0.00 | 03-DEC-04:00 | 3352.92 | 10-DEC-15:00 | 2447.04 | 10-DEC-15:10 | 976.66 | 25-DEC-16:10 | 857.59 | 10-DEC-15:00 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.535952E+11 | 0.135024E+11 | 7458.76 | 0.377188E+11 | 0.158764E+11 | 0.00 | ||||||||||||||
| Minimum of Months | 0.120449E+10 | 0.297942E+09 | 359.43 | 0.877236E+09 | 0.327250E+09 | 0.00 | 0.35 | 0.00 | 2762.94 | 2046.20 | 881.25 | 715.15 | 0.00 | |||||||
| Maximum of Months | 0.711956E+10 | 0.182573E+10 | 744.00 | 0.502345E+10 | 0.221654E+10 | 0.00 | 0.65 | 0.11 | 5243.84 | 4039.47 | 1526.61 | 1399.67 | 0.00 |
Report: DXReportMonthly
For: SPLIT TSE COOLING COIL
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.217888E+10 | 0.536528E+09 | 463.32 | 0.172997E+10 | 0.448907E+09 | 0.00 | 0.58 | 02-JAN-14:40 | 0.00 | 01-JAN-05:00 | 4183.56 | 02-JAN-14:40 | 3403.75 | 02-JAN-14:30 | 1189.33 | 07-JAN-11:30 | 1056.18 | 02-JAN-14:40 | 0.00 | 01-JAN-00:10 |
| February | 0.259871E+10 | 0.639632E+09 | 472.67 | 0.205797E+10 | 0.540737E+09 | 0.00 | 0.61 | 11-FEB-14:00 | 0.00 | 01-FEB-00:10 | 4424.28 | 11-FEB-14:30 | 3379.39 | 11-FEB-14:00 | 1128.20 | 11-FEB-12:20 | 1113.38 | 11-FEB-14:00 | 0.00 | 01-FEB-00:10 |
| March | 0.329686E+10 | 0.805197E+09 | 592.42 | 0.246744E+10 | 0.829418E+09 | 0.00 | 0.56 | 04-MAR-14:00 | 0.00 | 01-MAR-00:10 | 4097.46 | 04-MAR-13:50 | 2952.38 | 04-MAR-13:50 | 1459.36 | 14-MAR-10:00 | 1004.44 | 04-MAR-14:00 | 0.00 | 01-MAR-00:10 |
| April | 0.433442E+10 | 0.107697E+10 | 694.50 | 0.333704E+10 | 0.997385E+09 | 0.00 | 0.58 | 15-APR-16:03 | 0.00 | 02-APR-01:50 | 4085.91 | 15-APR-16:03 | 3288.28 | 15-APR-16:05 | 1128.03 | 01-APR-15:40 | 1081.16 | 15-APR-16:03 | 0.00 | 01-APR-00:10 |
| May | 0.610743E+10 | 0.152608E+10 | 744.00 | 0.431409E+10 | 0.179334E+10 | 0.00 | 0.65 | 29-MAY-16:10 | 0.02 | 01-MAY-05:40 | 4670.46 | 29-MAY-16:10 | 3497.67 | 29-MAY-16:04 | 1379.92 | 28-MAY-11:30 | 1240.38 | 29-MAY-16:10 | 0.00 | 01-MAY-00:10 |
| June | 0.676334E+10 | 0.170173E+10 | 720.00 | 0.462517E+10 | 0.213817E+10 | 0.00 | 0.59 | 25-JUN-14:00 | 0.12 | 06-JUN-04:00 | 4361.32 | 08-JUN-16:02 | 3180.55 | 03-JUN-16:07 | 1399.50 | 19-JUN-14:00 | 1119.93 | 25-JUN-14:00 | 0.00 | 01-JUN-00:10 |
| July | 0.712170E+10 | 0.181583E+10 | 744.00 | 0.499700E+10 | 0.212471E+10 | 0.00 | 0.65 | 27-JUL-16:10 | 0.11 | 15-JUL-03:00 | 4655.25 | 22-JUL-15:40 | 3726.49 | 29-JUL-16:08 | 1393.53 | 30-JUL-16:20 | 1265.99 | 27-JUL-16:10 | 0.00 | 01-JUL-00:10 |
| August | 0.705682E+10 | 0.178503E+10 | 744.00 | 0.480121E+10 | 0.225561E+10 | 0.00 | 0.67 | 20-AUG-12:00 | 0.11 | 29-AUG-06:00 | 4979.64 | 20-AUG-12:00 | 3596.29 | 23-AUG-13:00 | 1561.71 | 13-AUG-13:30 | 1288.96 | 20-AUG-12:00 | 0.00 | 01-AUG-00:10 |
| September | 0.686634E+10 | 0.172947E+10 | 720.00 | 0.479272E+10 | 0.207362E+10 | 0.00 | 0.70 | 20-SEP-14:00 | 0.08 | 05-SEP-06:00 | 5191.42 | 20-SEP-14:00 | 3770.06 | 20-SEP-14:00 | 1434.31 | 20-SEP-13:30 | 1341.71 | 20-SEP-14:00 | 0.00 | 01-SEP-00:10 |
| October | 0.621222E+10 | 0.154911E+10 | 744.00 | 0.443674E+10 | 0.177547E+10 | 0.00 | 0.70 | 29-OCT-14:00 | 0.05 | 28-OCT-04:00 | 5274.77 | 29-OCT-14:00 | 3719.15 | 14-OCT-13:30 | 1606.42 | 29-OCT-14:10 | 1307.16 | 29-OCT-14:00 | 0.00 | 01-OCT-00:10 |
| November | 0.438950E+10 | 0.107826E+10 | 630.12 | 0.315594E+10 | 0.123356E+10 | 0.00 | 0.63 | 22-NOV-12:40 | 0.00 | 01-NOV-04:50 | 4668.92 | 22-NOV-12:40 | 3538.20 | 22-NOV-12:40 | 1460.47 | 29-NOV-13:20 | 1135.44 | 22-NOV-12:50 | 0.00 | 01-NOV-00:10 |
| December | 0.267833E+10 | 0.652146E+09 | 491.71 | 0.198065E+10 | 0.697681E+09 | 0.00 | 0.61 | 10-DEC-14:00 | 0.00 | 03-DEC-04:40 | 4440.76 | 10-DEC-14:00 | 3358.16 | 10-DEC-14:30 | 1194.09 | 10-DEC-09:30 | 1107.44 | 10-DEC-14:00 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.596046E+11 | 0.148960E+11 | 7760.73 | 0.426959E+11 | 0.169086E+11 | 0.00 | ||||||||||||||
| Minimum of Months | 0.217888E+10 | 0.536528E+09 | 463.32 | 0.172997E+10 | 0.448907E+09 | 0.00 | 0.56 | 0.00 | 4085.91 | 2952.38 | 1128.03 | 1004.44 | 0.00 | |||||||
| Maximum of Months | 0.712170E+10 | 0.181583E+10 | 744.00 | 0.499700E+10 | 0.225561E+10 | 0.00 | 0.70 | 0.12 | 5274.77 | 3770.06 | 1606.42 | 1341.71 | 0.00 |
Report: DXReportMonthly
For: SPLIT TNE COOLING COIL
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.123216E+10 | 0.304028E+09 | 364.43 | 0.889473E+09 | 0.342686E+09 | 0.00 | 0.36 | 07-JAN-13:00 | 0.00 | 01-JAN-03:10 | 2651.08 | 07-JAN-13:00 | 1885.30 | 02-JAN-15:00 | 945.37 | 07-JAN-11:10 | 673.38 | 07-JAN-13:00 | 0.00 | 01-JAN-00:10 |
| February | 0.178563E+10 | 0.441987E+09 | 430.67 | 0.133721E+10 | 0.448429E+09 | 0.00 | 0.44 | 11-FEB-14:00 | 0.00 | 01-FEB-00:10 | 3208.89 | 11-FEB-14:00 | 2312.39 | 11-FEB-14:00 | 966.80 | 11-FEB-16:10 | 823.87 | 11-FEB-14:00 | 0.00 | 01-FEB-00:10 |
| March | 0.270337E+10 | 0.661673E+09 | 553.53 | 0.194890E+10 | 0.754478E+09 | 0.00 | 0.45 | 04-MAR-14:00 | 0.00 | 01-MAR-00:10 | 3390.42 | 04-MAR-14:00 | 2481.63 | 13-MAR-16:30 | 1358.65 | 14-MAR-10:00 | 849.19 | 13-MAR-16:12 | 0.00 | 01-MAR-00:10 |
| April | 0.397530E+10 | 0.991120E+09 | 693.50 | 0.302292E+10 | 0.952381E+09 | 0.00 | 0.53 | 15-APR-16:20 | 0.00 | 02-APR-01:30 | 3774.04 | 15-APR-16:20 | 3024.36 | 15-APR-16:20 | 1035.70 | 12-APR-10:30 | 1006.16 | 15-APR-16:20 | 0.00 | 01-APR-00:10 |
| May | 0.612887E+10 | 0.153270E+10 | 744.00 | 0.433741E+10 | 0.179146E+10 | 0.00 | 0.63 | 29-MAY-16:10 | 0.02 | 01-MAY-05:40 | 4655.22 | 22-MAY-15:30 | 3498.37 | 29-MAY-16:04 | 1346.28 | 28-MAY-11:30 | 1236.23 | 29-MAY-16:10 | 0.00 | 01-MAY-00:10 |
| June | 0.690022E+10 | 0.173664E+10 | 720.00 | 0.474744E+10 | 0.215278E+10 | 0.00 | 0.60 | 08-JUN-16:02 | 0.12 | 06-JUN-04:00 | 4501.16 | 08-JUN-16:02 | 3175.21 | 03-JUN-16:07 | 1434.07 | 08-JUN-16:02 | 1143.43 | 08-JUN-16:02 | 0.00 | 01-JUN-00:10 |
| July | 0.719155E+10 | 0.183487E+10 | 744.00 | 0.506407E+10 | 0.212748E+10 | 0.00 | 0.64 | 27-JUL-16:10 | 0.10 | 15-JUL-03:00 | 4591.15 | 27-JUL-16:10 | 3607.79 | 29-JUL-16:03 | 1398.30 | 13-JUL-13:20 | 1264.96 | 27-JUL-16:10 | 0.00 | 01-JUL-00:10 |
| August | 0.693070E+10 | 0.175615E+10 | 744.00 | 0.469460E+10 | 0.223611E+10 | 0.00 | 0.62 | 20-AUG-12:00 | 0.11 | 29-AUG-06:00 | 4674.34 | 20-AUG-12:00 | 3326.40 | 23-AUG-13:00 | 1503.62 | 13-AUG-13:30 | 1224.44 | 22-AUG-13:00 | 0.00 | 01-AUG-00:10 |
| September | 0.640291E+10 | 0.161866E+10 | 720.00 | 0.439245E+10 | 0.201046E+10 | 0.00 | 0.59 | 18-SEP-16:10 | 0.08 | 05-SEP-06:00 | 4394.31 | 18-SEP-16:10 | 3087.78 | 18-SEP-16:10 | 1359.23 | 18-SEP-18:00 | 1146.00 | 20-SEP-14:00 | 0.00 | 01-SEP-00:10 |
| October | 0.536427E+10 | 0.134474E+10 | 744.00 | 0.369974E+10 | 0.166453E+10 | 0.00 | 0.58 | 03-OCT-11:30 | 0.04 | 20-OCT-05:10 | 4321.44 | 03-OCT-11:30 | 2948.65 | 03-OCT-11:50 | 1448.37 | 03-OCT-10:30 | 1116.89 | 03-OCT-11:40 | 0.00 | 01-OCT-00:10 |
| November | 0.343222E+10 | 0.847629E+09 | 609.07 | 0.233320E+10 | 0.109903E+10 | 0.00 | 0.46 | 04-NOV-12:00 | 0.00 | 01-NOV-04:40 | 3459.55 | 04-NOV-12:00 | 2357.34 | 03-NOV-13:30 | 1369.38 | 04-NOV-16:20 | 855.98 | 04-NOV-12:00 | 0.00 | 01-NOV-00:10 |
| December | 0.174930E+10 | 0.427600E+09 | 405.66 | 0.119384E+10 | 0.555457E+09 | 0.00 | 0.42 | 10-DEC-14:00 | 0.00 | 03-DEC-03:20 | 3086.14 | 10-DEC-14:00 | 2164.16 | 10-DEC-14:00 | 965.71 | 24-DEC-10:50 | 786.21 | 10-DEC-14:00 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.537965E+11 | 0.134978E+11 | 7472.84 | 0.376612E+11 | 0.161353E+11 | 0.00 | ||||||||||||||
| Minimum of Months | 0.123216E+10 | 0.304028E+09 | 364.43 | 0.889473E+09 | 0.342686E+09 | 0.00 | 0.36 | 0.00 | 2651.08 | 1885.30 | 945.37 | 673.38 | 0.00 | |||||||
| Maximum of Months | 0.719155E+10 | 0.183487E+10 | 744.00 | 0.506407E+10 | 0.223611E+10 | 0.00 | 0.64 | 0.12 | 4674.34 | 3607.79 | 1503.62 | 1264.96 | 0.00 |
Report: DXReportMonthly
For: SPLIT TN1 COOLING COIL
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.109920E+10 | 0.271197E+09 | 385.53 | 0.790870E+09 | 0.308333E+09 | 0.00 | 0.32 | 07-JAN-13:00 | 0.00 | 01-JAN-06:05 | 2127.72 | 07-JAN-13:00 | 1524.83 | 02-JAN-15:00 | 733.49 | 07-JAN-11:20 | 543.69 | 07-JAN-13:00 | 0.00 | 01-JAN-00:10 |
| February | 0.156435E+10 | 0.387405E+09 | 458.17 | 0.116801E+10 | 0.396342E+09 | 0.00 | 0.39 | 11-FEB-14:00 | 0.00 | 01-FEB-00:10 | 2601.30 | 11-FEB-14:00 | 1875.14 | 11-FEB-14:00 | 782.20 | 11-FEB-17:10 | 672.04 | 11-FEB-14:00 | 0.00 | 01-FEB-00:10 |
| March | 0.231457E+10 | 0.568054E+09 | 562.75 | 0.167441E+10 | 0.640161E+09 | 0.00 | 0.41 | 13-MAR-16:12 | 0.00 | 01-MAR-00:10 | 2733.11 | 13-MAR-16:12 | 2063.78 | 13-MAR-16:25 | 964.39 | 14-MAR-10:10 | 706.12 | 13-MAR-16:12 | 0.00 | 01-MAR-00:10 |
| April | 0.332516E+10 | 0.831519E+09 | 696.64 | 0.252732E+10 | 0.797840E+09 | 0.00 | 0.47 | 15-APR-16:15 | 0.00 | 02-APR-02:20 | 3063.45 | 15-APR-16:15 | 2468.53 | 15-APR-16:30 | 825.99 | 01-APR-16:05 | 823.39 | 15-APR-16:15 | 0.00 | 01-APR-00:10 |
| May | 0.508726E+10 | 0.127769E+10 | 744.00 | 0.361711E+10 | 0.147015E+10 | 0.00 | 0.56 | 29-MAY-16:04 | 0.04 | 01-MAY-05:40 | 3730.42 | 29-MAY-16:20 | 2845.78 | 29-MAY-16:04 | 1049.60 | 28-MAY-11:40 | 1003.61 | 29-MAY-16:04 | 0.00 | 01-MAY-00:10 |
| June | 0.573391E+10 | 0.144997E+10 | 720.00 | 0.395065E+10 | 0.178326E+10 | 0.00 | 0.54 | 08-JUN-16:02 | 0.14 | 06-JUN-04:00 | 3653.91 | 08-JUN-16:02 | 2597.30 | 03-JUN-16:20 | 1118.31 | 08-JUN-16:02 | 938.09 | 08-JUN-16:02 | 0.00 | 01-JUN-00:10 |
| July | 0.599733E+10 | 0.153570E+10 | 744.00 | 0.420546E+10 | 0.179186E+10 | 0.00 | 0.57 | 27-JUL-16:10 | 0.12 | 15-JUL-03:00 | 3712.23 | 27-JUL-16:10 | 2946.34 | 29-JUL-16:03 | 1089.74 | 13-JUL-13:20 | 1033.47 | 27-JUL-16:10 | 0.00 | 01-JUL-00:10 |
| August | 0.580524E+10 | 0.147677E+10 | 744.00 | 0.393698E+10 | 0.186827E+10 | 0.00 | 0.53 | 16-AUG-16:02 | 0.13 | 29-AUG-06:00 | 3576.96 | 15-AUG-15:10 | 2558.92 | 23-AUG-15:10 | 1130.57 | 13-AUG-13:30 | 948.70 | 22-AUG-13:00 | 0.00 | 01-AUG-00:10 |
| September | 0.534116E+10 | 0.135544E+10 | 720.00 | 0.366508E+10 | 0.167608E+10 | 0.00 | 0.53 | 18-SEP-16:10 | 0.10 | 05-SEP-06:00 | 3534.51 | 18-SEP-16:10 | 2522.35 | 18-SEP-16:04 | 1057.43 | 18-SEP-18:00 | 927.70 | 18-SEP-16:10 | 0.00 | 01-SEP-00:10 |
| October | 0.453475E+10 | 0.113967E+10 | 744.00 | 0.313503E+10 | 0.139972E+10 | 0.00 | 0.50 | 03-OCT-15:10 | 0.06 | 20-OCT-05:10 | 3337.92 | 03-OCT-15:10 | 2343.39 | 03-OCT-15:10 | 1102.73 | 29-OCT-14:20 | 879.18 | 03-OCT-15:10 | 0.00 | 01-OCT-00:10 |
| November | 0.297872E+10 | 0.737500E+09 | 627.31 | 0.204168E+10 | 0.937043E+09 | 0.00 | 0.41 | 04-NOV-16:10 | 0.00 | 01-NOV-05:05 | 2846.60 | 04-NOV-16:10 | 1907.02 | 03-NOV-14:10 | 1074.80 | 04-NOV-16:20 | 699.59 | 04-NOV-16:10 | 0.00 | 01-NOV-00:10 |
| December | 0.160488E+10 | 0.392675E+09 | 431.72 | 0.110351E+10 | 0.501370E+09 | 0.00 | 0.37 | 10-DEC-14:00 | 0.00 | 03-DEC-06:05 | 2477.23 | 10-DEC-14:00 | 1756.60 | 10-DEC-14:50 | 778.13 | 24-DEC-11:00 | 635.80 | 10-DEC-14:00 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.453865E+11 | 0.114236E+11 | 7578.11 | 0.318161E+11 | 0.135704E+11 | 0.00 | ||||||||||||||
| Minimum of Months | 0.109920E+10 | 0.271197E+09 | 385.53 | 0.790870E+09 | 0.308333E+09 | 0.00 | 0.32 | 0.00 | 2127.72 | 1524.83 | 733.49 | 543.69 | 0.00 | |||||||
| Maximum of Months | 0.599733E+10 | 0.153570E+10 | 744.00 | 0.420546E+10 | 0.186827E+10 | 0.00 | 0.57 | 0.14 | 3730.42 | 2946.34 | 1130.57 | 1033.47 | 0.00 |
Report: DXReportMonthly
For: SPLIT TN2 COOLING COIL
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.110230E+10 | 0.271941E+09 | 386.81 | 0.794140E+09 | 0.308158E+09 | 0.00 | 0.32 | 07-JAN-13:00 | 0.00 | 01-JAN-06:05 | 2131.06 | 07-JAN-13:00 | 1527.46 | 02-JAN-15:00 | 733.78 | 07-JAN-11:20 | 544.42 | 07-JAN-13:00 | 0.00 | 01-JAN-00:10 |
| February | 0.156509E+10 | 0.387561E+09 | 458.50 | 0.116972E+10 | 0.395361E+09 | 0.00 | 0.39 | 11-FEB-14:00 | 0.00 | 01-FEB-00:10 | 2602.98 | 11-FEB-14:00 | 1878.34 | 11-FEB-14:00 | 777.41 | 11-FEB-17:10 | 672.31 | 11-FEB-14:00 | 0.00 | 01-FEB-00:10 |
| March | 0.231284E+10 | 0.567560E+09 | 563.50 | 0.167430E+10 | 0.638543E+09 | 0.00 | 0.41 | 13-MAR-16:12 | 0.00 | 01-MAR-00:10 | 2721.37 | 13-MAR-16:12 | 2054.44 | 13-MAR-16:25 | 967.54 | 14-MAR-10:10 | 703.05 | 13-MAR-16:12 | 0.00 | 01-MAR-00:10 |
| April | 0.332267E+10 | 0.830785E+09 | 696.47 | 0.252703E+10 | 0.795644E+09 | 0.00 | 0.47 | 15-APR-16:15 | 0.00 | 02-APR-02:20 | 3051.05 | 15-APR-16:15 | 2458.98 | 15-APR-16:20 | 821.13 | 01-APR-16:05 | 820.03 | 15-APR-16:15 | 0.00 | 01-APR-00:10 |
| May | 0.508442E+10 | 0.127674E+10 | 744.00 | 0.361683E+10 | 0.146758E+10 | 0.00 | 0.56 | 29-MAY-16:04 | 0.04 | 01-MAY-05:40 | 3716.20 | 29-MAY-16:20 | 2835.95 | 29-MAY-16:04 | 1049.53 | 28-MAY-11:40 | 999.99 | 29-MAY-16:04 | 0.00 | 01-MAY-00:10 |
| June | 0.573516E+10 | 0.144992E+10 | 720.00 | 0.395364E+10 | 0.178152E+10 | 0.00 | 0.54 | 08-JUN-16:02 | 0.14 | 06-JUN-04:00 | 3641.58 | 08-JUN-16:02 | 2592.06 | 03-JUN-16:20 | 1114.62 | 08-JUN-16:02 | 934.81 | 08-JUN-16:02 | 0.00 | 01-JUN-00:10 |
| July | 0.599704E+10 | 0.153527E+10 | 744.00 | 0.420720E+10 | 0.178984E+10 | 0.00 | 0.57 | 27-JUL-16:10 | 0.12 | 15-JUL-03:00 | 3700.93 | 27-JUL-16:10 | 2939.45 | 29-JUL-16:03 | 1088.51 | 13-JUL-13:20 | 1030.20 | 27-JUL-16:10 | 0.00 | 01-JUL-00:10 |
| August | 0.580212E+10 | 0.147566E+10 | 744.00 | 0.393629E+10 | 0.186583E+10 | 0.00 | 0.53 | 22-AUG-13:00 | 0.13 | 29-AUG-06:00 | 3573.13 | 15-AUG-15:10 | 2559.93 | 19-AUG-14:10 | 1129.69 | 13-AUG-13:30 | 950.62 | 22-AUG-13:00 | 0.00 | 01-AUG-00:10 |
| September | 0.534156E+10 | 0.135522E+10 | 720.00 | 0.366718E+10 | 0.167438E+10 | 0.00 | 0.53 | 18-SEP-16:10 | 0.10 | 05-SEP-06:00 | 3524.17 | 18-SEP-16:10 | 2514.88 | 18-SEP-16:04 | 1054.98 | 18-SEP-18:00 | 924.85 | 18-SEP-16:10 | 0.00 | 01-SEP-00:10 |
| October | 0.453352E+10 | 0.113915E+10 | 744.00 | 0.313573E+10 | 0.139779E+10 | 0.00 | 0.50 | 03-OCT-15:10 | 0.06 | 20-OCT-05:10 | 3333.06 | 03-OCT-15:10 | 2341.20 | 03-OCT-15:10 | 1100.23 | 29-OCT-14:20 | 877.72 | 03-OCT-15:10 | 0.00 | 01-OCT-00:10 |
| November | 0.297823E+10 | 0.737250E+09 | 627.81 | 0.204255E+10 | 0.935684E+09 | 0.00 | 0.42 | 04-NOV-16:10 | 0.00 | 01-NOV-05:05 | 2844.48 | 04-NOV-16:10 | 1906.97 | 03-NOV-14:10 | 1073.13 | 04-NOV-16:20 | 698.90 | 04-NOV-16:10 | 0.00 | 01-NOV-00:10 |
| December | 0.160094E+10 | 0.391661E+09 | 431.72 | 0.110119E+10 | 0.499750E+09 | 0.00 | 0.37 | 10-DEC-14:00 | 0.00 | 03-DEC-06:05 | 2476.92 | 10-DEC-14:00 | 1754.22 | 10-DEC-14:00 | 778.79 | 24-DEC-11:00 | 635.59 | 10-DEC-14:00 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.453759E+11 | 0.114187E+11 | 7580.81 | 0.318258E+11 | 0.135501E+11 | 0.00 | ||||||||||||||
| Minimum of Months | 0.110230E+10 | 0.271941E+09 | 386.81 | 0.794140E+09 | 0.308158E+09 | 0.00 | 0.32 | 0.00 | 2131.06 | 1527.46 | 733.78 | 544.42 | 0.00 | |||||||
| Maximum of Months | 0.599704E+10 | 0.153527E+10 | 744.00 | 0.420720E+10 | 0.186583E+10 | 0.00 | 0.57 | 0.14 | 3716.20 | 2939.45 | 1129.69 | 1030.20 | 0.00 |
Report: DXReportMonthly
For: SPLIT TS1 COOLING COIL
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.208095E+10 | 0.513141E+09 | 511.13 | 0.166748E+10 | 0.413470E+09 | 0.00 | 0.57 | 02-JAN-14:40 | 0.00 | 01-JAN-06:05 | 3728.76 | 02-JAN-14:40 | 3061.14 | 02-JAN-14:30 | 978.92 | 07-JAN-11:30 | 942.74 | 02-JAN-14:40 | 0.00 | 01-JAN-00:10 |
| February | 0.238742E+10 | 0.588687E+09 | 505.46 | 0.190375E+10 | 0.483675E+09 | 0.00 | 0.58 | 11-FEB-14:30 | 0.00 | 01-FEB-00:10 | 3829.58 | 11-FEB-14:30 | 2966.37 | 11-FEB-14:30 | 943.87 | 19-FEB-11:50 | 963.67 | 11-FEB-14:00 | 0.00 | 01-FEB-00:10 |
| March | 0.290731E+10 | 0.712357E+09 | 607.35 | 0.219716E+10 | 0.710154E+09 | 0.00 | 0.50 | 04-MAR-14:00 | 0.00 | 01-MAR-01:00 | 3322.13 | 04-MAR-14:00 | 2461.62 | 13-MAR-16:15 | 1066.68 | 14-MAR-10:10 | 823.24 | 04-MAR-14:00 | 0.00 | 01-MAR-00:10 |
| April | 0.368440E+10 | 0.918546E+09 | 698.67 | 0.284549E+10 | 0.838909E+09 | 0.00 | 0.53 | 15-APR-16:03 | 0.00 | 02-APR-02:50 | 3406.98 | 01-APR-16:05 | 2731.10 | 15-APR-16:05 | 919.62 | 01-APR-16:05 | 898.03 | 15-APR-16:03 | 0.00 | 01-APR-00:10 |
| May | 0.506213E+10 | 0.127040E+10 | 744.00 | 0.359409E+10 | 0.146804E+10 | 0.00 | 0.58 | 29-MAY-16:06 | 0.05 | 01-MAY-05:40 | 3751.53 | 29-MAY-16:10 | 2846.57 | 29-MAY-16:04 | 1081.67 | 28-MAY-11:40 | 1007.86 | 29-MAY-16:06 | 0.00 | 01-MAY-00:10 |
| June | 0.559140E+10 | 0.141349E+10 | 720.00 | 0.382737E+10 | 0.176403E+10 | 0.00 | 0.54 | 03-JUN-16:03 | 0.14 | 06-JUN-04:00 | 3513.56 | 08-JUN-16:02 | 2602.59 | 03-JUN-16:07 | 1078.96 | 08-JUN-16:02 | 914.35 | 03-JUN-16:03 | 0.00 | 01-JUN-00:10 |
| July | 0.592268E+10 | 0.151564E+10 | 744.00 | 0.413788E+10 | 0.178480E+10 | 0.00 | 0.59 | 29-JUL-16:03 | 0.12 | 15-JUL-03:00 | 3756.48 | 22-JUL-15:50 | 3064.69 | 29-JUL-16:03 | 1096.68 | 22-JUL-15:40 | 1036.19 | 29-JUL-16:02 | 0.00 | 01-JUL-00:10 |
| August | 0.592892E+10 | 0.150592E+10 | 744.00 | 0.404506E+10 | 0.188387E+10 | 0.00 | 0.59 | 20-AUG-12:40 | 0.13 | 29-AUG-03:00 | 3875.41 | 20-AUG-12:30 | 2858.69 | 31-AUG-15:10 | 1184.44 | 13-AUG-13:30 | 1017.24 | 20-AUG-12:30 | 0.00 | 01-AUG-00:10 |
| September | 0.580553E+10 | 0.146856E+10 | 720.00 | 0.407005E+10 | 0.173548E+10 | 0.00 | 0.64 | 20-SEP-14:00 | 0.11 | 05-SEP-06:00 | 4236.94 | 20-SEP-14:00 | 3187.57 | 30-SEP-14:00 | 1120.45 | 20-SEP-13:30 | 1107.53 | 20-SEP-14:00 | 0.00 | 01-SEP-00:10 |
| October | 0.538657E+10 | 0.134761E+10 | 744.00 | 0.388161E+10 | 0.150497E+10 | 0.00 | 0.65 | 29-OCT-14:00 | 0.07 | 28-OCT-04:00 | 4388.95 | 29-OCT-14:00 | 3146.06 | 29-OCT-13:50 | 1250.80 | 29-OCT-14:10 | 1099.24 | 29-OCT-14:00 | 0.00 | 01-OCT-00:10 |
| November | 0.394542E+10 | 0.972147E+09 | 653.08 | 0.288199E+10 | 0.106342E+10 | 0.00 | 0.59 | 22-NOV-12:50 | 0.00 | 01-NOV-05:05 | 3912.69 | 22-NOV-12:50 | 3032.13 | 22-NOV-12:50 | 1154.37 | 04-NOV-16:20 | 960.67 | 22-NOV-12:50 | 0.00 | 01-NOV-00:10 |
| December | 0.258019E+10 | 0.629405E+09 | 543.47 | 0.194175E+10 | 0.638437E+09 | 0.00 | 0.58 | 10-DEC-14:30 | 0.00 | 04-DEC-03:40 | 3820.97 | 10-DEC-14:30 | 2968.43 | 10-DEC-14:30 | 983.39 | 31-DEC-13:40 | 959.77 | 10-DEC-14:30 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.512829E+11 | 0.128559E+11 | 7935.16 | 0.369937E+11 | 0.142892E+11 | 0.00 | ||||||||||||||
| Minimum of Months | 0.208095E+10 | 0.513141E+09 | 505.46 | 0.166748E+10 | 0.413470E+09 | 0.00 | 0.50 | 0.00 | 3322.13 | 2461.62 | 919.62 | 823.24 | 0.00 | |||||||
| Maximum of Months | 0.592892E+10 | 0.151564E+10 | 744.00 | 0.413788E+10 | 0.188387E+10 | 0.00 | 0.65 | 0.14 | 4388.95 | 3187.57 | 1250.80 | 1107.53 | 0.00 |
Report: DXReportMonthly
For: SPLIT TS2 COOLING COIL
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.208613E+10 | 0.514344E+09 | 511.22 | 0.167201E+10 | 0.414114E+09 | 0.00 | 0.57 | 02-JAN-14:40 | 0.00 | 01-JAN-06:05 | 3731.65 | 02-JAN-14:40 | 3065.43 | 02-JAN-14:30 | 980.22 | 07-JAN-11:30 | 943.18 | 02-JAN-14:40 | 0.00 | 01-JAN-00:10 |
| February | 0.238960E+10 | 0.589140E+09 | 505.29 | 0.190551E+10 | 0.484092E+09 | 0.00 | 0.58 | 11-FEB-14:30 | 0.00 | 01-FEB-00:10 | 3828.88 | 11-FEB-14:30 | 2966.16 | 11-FEB-14:30 | 945.56 | 19-FEB-11:50 | 964.08 | 11-FEB-14:00 | 0.00 | 01-FEB-00:10 |
| March | 0.290898E+10 | 0.712698E+09 | 607.15 | 0.219850E+10 | 0.710481E+09 | 0.00 | 0.50 | 04-MAR-14:00 | 0.00 | 01-MAR-01:00 | 3327.16 | 04-MAR-14:00 | 2453.89 | 13-MAR-16:06 | 1070.97 | 14-MAR-10:10 | 824.24 | 04-MAR-14:00 | 0.00 | 01-MAR-00:10 |
| April | 0.368461E+10 | 0.918492E+09 | 698.67 | 0.284535E+10 | 0.839257E+09 | 0.00 | 0.53 | 15-APR-16:03 | 0.00 | 02-APR-02:50 | 3391.79 | 01-APR-16:05 | 2722.94 | 15-APR-16:05 | 916.96 | 01-APR-16:05 | 895.48 | 15-APR-16:03 | 0.00 | 01-APR-00:10 |
| May | 0.506266E+10 | 0.127037E+10 | 744.00 | 0.359406E+10 | 0.146861E+10 | 0.00 | 0.58 | 29-MAY-16:10 | 0.05 | 01-MAY-05:40 | 3740.58 | 29-MAY-16:10 | 2836.87 | 29-MAY-16:04 | 1083.12 | 28-MAY-11:40 | 1004.85 | 29-MAY-16:10 | 0.00 | 01-MAY-00:10 |
| June | 0.559590E+10 | 0.141436E+10 | 720.00 | 0.383061E+10 | 0.176530E+10 | 0.00 | 0.54 | 03-JUN-16:03 | 0.14 | 06-JUN-04:00 | 3503.05 | 08-JUN-16:02 | 2597.85 | 03-JUN-16:07 | 1076.84 | 08-JUN-16:02 | 912.74 | 03-JUN-16:03 | 0.00 | 01-JUN-00:10 |
| July | 0.592557E+10 | 0.151612E+10 | 744.00 | 0.413985E+10 | 0.178572E+10 | 0.00 | 0.59 | 29-JUL-16:03 | 0.12 | 15-JUL-03:00 | 3749.65 | 22-JUL-15:50 | 3057.85 | 29-JUL-16:03 | 1095.15 | 22-JUL-15:40 | 1033.97 | 29-JUL-16:03 | 0.00 | 01-JUL-00:10 |
| August | 0.592890E+10 | 0.150567E+10 | 744.00 | 0.404456E+10 | 0.188434E+10 | 0.00 | 0.59 | 20-AUG-12:40 | 0.13 | 29-AUG-03:00 | 3885.83 | 20-AUG-12:30 | 2854.83 | 31-AUG-15:10 | 1185.03 | 13-AUG-13:30 | 1019.52 | 20-AUG-12:30 | 0.00 | 01-AUG-00:10 |
| September | 0.580875E+10 | 0.146907E+10 | 720.00 | 0.407226E+10 | 0.173648E+10 | 0.00 | 0.64 | 20-SEP-14:00 | 0.11 | 05-SEP-06:00 | 4238.88 | 20-SEP-14:00 | 3190.19 | 30-SEP-14:00 | 1120.49 | 20-SEP-13:30 | 1107.67 | 20-SEP-14:00 | 0.00 | 01-SEP-00:10 |
| October | 0.538801E+10 | 0.134773E+10 | 744.00 | 0.388234E+10 | 0.150567E+10 | 0.00 | 0.65 | 29-OCT-14:00 | 0.07 | 28-OCT-04:00 | 4388.83 | 29-OCT-14:00 | 3147.26 | 29-OCT-13:50 | 1250.23 | 29-OCT-14:10 | 1098.88 | 29-OCT-14:00 | 0.00 | 01-OCT-00:10 |
| November | 0.394698E+10 | 0.972358E+09 | 653.25 | 0.288294E+10 | 0.106404E+10 | 0.00 | 0.59 | 22-NOV-12:50 | 0.00 | 01-NOV-05:05 | 3924.57 | 22-NOV-12:40 | 3042.97 | 22-NOV-12:50 | 1154.07 | 04-NOV-16:20 | 963.09 | 22-NOV-12:50 | 0.00 | 01-NOV-00:10 |
| December | 0.257837E+10 | 0.628889E+09 | 543.25 | 0.194007E+10 | 0.638303E+09 | 0.00 | 0.58 | 10-DEC-14:30 | 0.00 | 04-DEC-03:30 | 3819.18 | 10-DEC-14:30 | 2966.97 | 10-DEC-14:30 | 983.92 | 31-DEC-13:40 | 959.10 | 10-DEC-14:30 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.513045E+11 | 0.128593E+11 | 7934.83 | 0.370080E+11 | 0.142964E+11 | 0.00 | ||||||||||||||
| Minimum of Months | 0.208613E+10 | 0.514344E+09 | 505.29 | 0.167201E+10 | 0.414114E+09 | 0.00 | 0.50 | 0.00 | 3327.16 | 2453.89 | 916.96 | 824.24 | 0.00 | |||||||
| Maximum of Months | 0.592890E+10 | 0.151612E+10 | 744.00 | 0.413985E+10 | 0.188434E+10 | 0.00 | 0.65 | 0.14 | 4388.83 | 3190.19 | 1250.23 | 1107.67 | 0.00 |
Report: WindowReportMonthly
For: GWINDOW1 S SWA
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 167.09 | 108.10 | 58.99 | 261.52 | 79.25 | 0.00 | 0.00 | 0.00 |
| February | 152.47 | 88.29 | 64.18 | 252.49 | 64.77 | 0.00 | 0.00 | 0.00 |
| March | 114.21 | 46.73 | 67.48 | 191.72 | 52.21 | 0.00 | 0.00 | 0.00 |
| April | 84.40 | 18.81 | 65.59 | 157.83 | 32.76 | 0.00 | 0.00 | 0.00 |
| May | 64.21 | 1.86 | 62.35 | 132.41 | 12.60 | 0.00 | 0.00 | 0.00 |
| June | 60.79 | 0.17 | 60.63 | 136.69 | 4.33 | 0.00 | 0.00 | 0.00 |
| July | 65.18 | 0.72 | 64.46 | 151.96 | 7.02 | 0.00 | 0.00 | 0.00 |
| August | 73.48 | 5.90 | 67.59 | 161.88 | 4.56 | 0.00 | 0.00 | 0.00 |
| September | 95.46 | 24.11 | 71.35 | 209.09 | 10.50 | 0.00 | 0.00 | 0.00 |
| October | 130.20 | 61.23 | 68.98 | 250.68 | 18.14 | 0.00 | 0.00 | 0.00 |
| November | 148.61 | 83.27 | 65.34 | 256.66 | 38.54 | 0.00 | 0.00 | 0.00 |
| December | 161.82 | 101.89 | 59.92 | 259.28 | 68.67 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 109.61 | 44.88 | 64.73 | 201.56 | 32.64 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 60.79 | 0.17 | 58.99 | 132.41 | 4.33 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 167.09 | 108.10 | 71.35 | 261.52 | 79.25 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: GWINDOW1 W SWA
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 51.23 | 22.20 | 29.03 | 71.15 | 56.44 | 0.00 | 0.00 | 0.00 |
| February | 63.95 | 29.04 | 34.91 | 100.06 | 45.52 | 0.00 | 0.00 | 0.00 |
| March | 79.60 | 36.41 | 43.18 | 126.48 | 36.07 | 0.00 | 0.00 | 0.00 |
| April | 87.18 | 40.27 | 46.91 | 152.36 | 21.33 | 0.00 | 0.00 | 0.00 |
| May | 79.83 | 30.82 | 49.01 | 153.47 | 8.60 | 0.00 | 0.00 | 0.00 |
| June | 67.60 | 18.99 | 48.61 | 140.07 | 2.87 | 0.00 | 0.00 | 0.00 |
| July | 75.49 | 23.40 | 52.09 | 159.22 | 4.48 | 0.00 | 0.00 | 0.00 |
| August | 75.26 | 24.48 | 50.77 | 151.20 | 2.94 | 0.00 | 0.00 | 0.00 |
| September | 64.17 | 18.94 | 45.23 | 133.30 | 6.75 | 0.00 | 0.00 | 0.00 |
| October | 63.82 | 24.88 | 38.93 | 120.30 | 12.13 | 0.00 | 0.00 | 0.00 |
| November | 52.59 | 19.24 | 33.35 | 88.99 | 27.13 | 0.00 | 0.00 | 0.00 |
| December | 52.86 | 23.69 | 29.17 | 78.67 | 47.58 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 67.83 | 26.02 | 41.80 | 123.06 | 22.56 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 51.23 | 18.94 | 29.03 | 71.15 | 2.87 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 87.18 | 40.27 | 52.09 | 159.22 | 56.44 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: GWINDOW1 W NWA
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 51.23 | 22.20 | 29.03 | 73.37 | 53.86 | 0.00 | 0.00 | 0.00 |
| February | 63.95 | 29.04 | 34.91 | 102.18 | 43.42 | 0.00 | 0.00 | 0.00 |
| March | 79.60 | 36.41 | 43.18 | 128.02 | 34.65 | 0.00 | 0.00 | 0.00 |
| April | 87.18 | 40.27 | 46.91 | 153.03 | 20.95 | 0.00 | 0.00 | 0.00 |
| May | 79.83 | 30.82 | 49.01 | 153.45 | 8.65 | 0.00 | 0.00 | 0.00 |
| June | 67.60 | 18.99 | 48.61 | 139.74 | 2.94 | 0.00 | 0.00 | 0.00 |
| July | 75.49 | 23.40 | 52.09 | 159.03 | 4.54 | 0.00 | 0.00 | 0.00 |
| August | 75.26 | 24.48 | 50.77 | 151.46 | 2.91 | 0.00 | 0.00 | 0.00 |
| September | 64.17 | 18.94 | 45.23 | 134.28 | 6.57 | 0.00 | 0.00 | 0.00 |
| October | 63.82 | 24.88 | 38.93 | 121.75 | 11.28 | 0.00 | 0.00 | 0.00 |
| November | 52.59 | 19.24 | 33.35 | 90.70 | 25.79 | 0.00 | 0.00 | 0.00 |
| December | 52.86 | 23.69 | 29.17 | 80.57 | 45.24 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 67.83 | 26.02 | 41.80 | 124.08 | 21.64 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 51.23 | 18.94 | 29.03 | 73.37 | 2.91 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 87.18 | 40.27 | 52.09 | 159.03 | 53.86 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: GWINDOW1 N NWA
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 35.81 | 0.00 | 35.81 | 36.94 | 84.35 | 0.00 | 0.00 | 0.00 |
| February | 42.39 | 0.00 | 42.39 | 56.51 | 67.18 | 0.00 | 0.00 | 0.00 |
| March | 50.57 | 0.00 | 50.57 | 69.02 | 53.73 | 0.00 | 0.00 | 0.00 |
| April | 56.78 | 0.32 | 56.46 | 96.16 | 31.64 | 0.00 | 0.00 | 0.00 |
| May | 64.45 | 2.59 | 61.85 | 131.76 | 12.91 | 0.00 | 0.00 | 0.00 |
| June | 68.99 | 4.83 | 64.16 | 153.90 | 4.21 | 0.00 | 0.00 | 0.00 |
| July | 69.77 | 3.24 | 66.53 | 161.45 | 6.95 | 0.00 | 0.00 | 0.00 |
| August | 62.08 | 0.70 | 61.38 | 135.92 | 4.37 | 0.00 | 0.00 | 0.00 |
| September | 54.93 | 0.01 | 54.91 | 126.12 | 10.02 | 0.00 | 0.00 | 0.00 |
| October | 45.99 | 0.00 | 45.99 | 92.06 | 17.06 | 0.00 | 0.00 | 0.00 |
| November | 39.99 | 0.00 | 39.99 | 64.29 | 39.43 | 0.00 | 0.00 | 0.00 |
| December | 35.42 | 0.00 | 35.42 | 41.77 | 70.94 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 52.31 | 0.98 | 51.34 | 97.35 | 33.42 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 35.42 | 0.00 | 35.42 | 36.94 | 4.21 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 69.77 | 4.83 | 66.53 | 161.45 | 84.35 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: GWINDOW1 S SEA
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 167.09 | 108.10 | 58.99 | 251.96 | 99.60 | 0.00 | 0.00 | 0.00 |
| February | 152.47 | 88.29 | 64.18 | 243.61 | 82.42 | 0.00 | 0.00 | 0.00 |
| March | 114.21 | 46.73 | 67.48 | 182.61 | 69.83 | 0.00 | 0.00 | 0.00 |
| April | 84.40 | 18.81 | 65.59 | 144.78 | 54.06 | 0.00 | 0.00 | 0.00 |
| May | 64.21 | 1.86 | 62.35 | 115.52 | 34.25 | 0.00 | 0.00 | 0.00 |
| June | 60.79 | 0.17 | 60.63 | 112.66 | 22.36 | 0.00 | 0.00 | 0.00 |
| July | 65.18 | 0.72 | 64.46 | 128.05 | 28.90 | 0.00 | 0.00 | 0.00 |
| August | 73.48 | 5.90 | 67.59 | 139.78 | 26.70 | 0.00 | 0.00 | 0.00 |
| September | 95.46 | 24.11 | 71.35 | 184.71 | 32.21 | 0.00 | 0.00 | 0.00 |
| October | 130.20 | 61.23 | 68.98 | 233.46 | 46.55 | 0.00 | 0.00 | 0.00 |
| November | 148.61 | 83.27 | 65.34 | 243.79 | 63.03 | 0.00 | 0.00 | 0.00 |
| December | 161.82 | 101.89 | 59.92 | 250.00 | 88.99 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 109.61 | 44.88 | 64.73 | 185.59 | 53.96 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 60.79 | 0.17 | 58.99 | 112.66 | 22.36 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 167.09 | 108.10 | 71.35 | 251.96 | 99.60 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: GWINDOW1 E SEA
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 56.89 | 27.34 | 29.55 | 73.26 | 67.10 | 0.00 | 0.00 | 0.00 |
| February | 65.65 | 30.39 | 35.26 | 93.78 | 54.34 | 0.00 | 0.00 | 0.00 |
| March | 80.06 | 37.78 | 42.28 | 117.08 | 44.47 | 0.00 | 0.00 | 0.00 |
| April | 87.31 | 39.08 | 48.23 | 142.01 | 34.25 | 0.00 | 0.00 | 0.00 |
| May | 82.33 | 32.88 | 49.45 | 144.73 | 21.52 | 0.00 | 0.00 | 0.00 |
| June | 81.06 | 31.14 | 49.92 | 146.70 | 13.47 | 0.00 | 0.00 | 0.00 |
| July | 83.44 | 30.19 | 53.25 | 156.61 | 18.28 | 0.00 | 0.00 | 0.00 |
| August | 76.12 | 25.43 | 50.69 | 137.59 | 16.86 | 0.00 | 0.00 | 0.00 |
| September | 73.37 | 26.47 | 46.90 | 132.70 | 20.25 | 0.00 | 0.00 | 0.00 |
| October | 67.61 | 29.08 | 38.52 | 115.12 | 30.28 | 0.00 | 0.00 | 0.00 |
| November | 54.91 | 21.90 | 33.01 | 82.77 | 41.45 | 0.00 | 0.00 | 0.00 |
| December | 44.42 | 15.72 | 28.70 | 57.00 | 60.07 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 71.11 | 28.93 | 42.18 | 116.70 | 35.12 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 44.42 | 15.72 | 28.70 | 57.00 | 13.47 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 87.31 | 39.08 | 53.25 | 156.61 | 67.10 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: GWINDOW1 E NEA
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 56.89 | 27.34 | 29.55 | 80.85 | 50.70 | 0.00 | 0.00 | 0.00 |
| February | 65.65 | 30.39 | 35.26 | 101.35 | 40.24 | 0.00 | 0.00 | 0.00 |
| March | 80.06 | 37.78 | 42.28 | 124.74 | 31.58 | 0.00 | 0.00 | 0.00 |
| April | 87.31 | 39.08 | 48.23 | 151.88 | 20.07 | 0.00 | 0.00 | 0.00 |
| May | 82.33 | 32.88 | 49.45 | 156.72 | 7.85 | 0.00 | 0.00 | 0.00 |
| June | 81.06 | 31.14 | 49.92 | 163.51 | 2.69 | 0.00 | 0.00 | 0.00 |
| July | 83.44 | 30.19 | 53.25 | 173.15 | 4.56 | 0.00 | 0.00 | 0.00 |
| August | 76.12 | 25.43 | 50.69 | 153.27 | 2.76 | 0.00 | 0.00 | 0.00 |
| September | 73.37 | 26.47 | 46.90 | 150.66 | 6.52 | 0.00 | 0.00 | 0.00 |
| October | 67.61 | 29.08 | 38.52 | 127.92 | 10.63 | 0.00 | 0.00 | 0.00 |
| November | 54.91 | 21.90 | 33.01 | 92.65 | 23.67 | 0.00 | 0.00 | 0.00 |
| December | 44.42 | 15.72 | 28.70 | 64.39 | 43.63 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 71.11 | 28.93 | 42.18 | 128.52 | 20.32 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 44.42 | 15.72 | 28.70 | 64.39 | 2.69 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 87.31 | 39.08 | 53.25 | 173.15 | 50.70 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: GWINDOW1 N NEA
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 35.81 | 0.00 | 35.81 | 36.42 | 84.39 | 0.00 | 0.00 | 0.00 |
| February | 42.39 | 0.00 | 42.39 | 56.08 | 66.96 | 0.00 | 0.00 | 0.00 |
| March | 50.57 | 0.00 | 50.57 | 68.53 | 53.53 | 0.00 | 0.00 | 0.00 |
| April | 56.78 | 0.32 | 56.46 | 95.80 | 31.21 | 0.00 | 0.00 | 0.00 |
| May | 64.45 | 2.59 | 61.85 | 131.52 | 12.65 | 0.00 | 0.00 | 0.00 |
| June | 68.99 | 4.83 | 64.16 | 153.48 | 4.24 | 0.00 | 0.00 | 0.00 |
| July | 69.77 | 3.24 | 66.53 | 161.16 | 6.89 | 0.00 | 0.00 | 0.00 |
| August | 62.08 | 0.70 | 61.38 | 135.88 | 4.29 | 0.00 | 0.00 | 0.00 |
| September | 54.93 | 0.01 | 54.91 | 125.84 | 10.02 | 0.00 | 0.00 | 0.00 |
| October | 45.99 | 0.00 | 45.99 | 91.79 | 16.89 | 0.00 | 0.00 | 0.00 |
| November | 39.99 | 0.00 | 39.99 | 64.02 | 39.30 | 0.00 | 0.00 | 0.00 |
| December | 35.42 | 0.00 | 35.42 | 41.66 | 70.50 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 52.31 | 0.98 | 51.34 | 97.04 | 33.26 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 35.42 | 0.00 | 35.42 | 36.42 | 4.24 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 69.77 | 4.83 | 66.53 | 161.16 | 84.39 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: GWINDOW1 N N1A
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 35.81 | 0.00 | 35.81 | 36.95 | 85.25 | 0.00 | 0.00 | 0.00 |
| February | 42.39 | 0.00 | 42.39 | 56.76 | 67.85 | 0.00 | 0.00 | 0.00 |
| March | 50.57 | 0.00 | 50.57 | 69.48 | 54.03 | 0.00 | 0.00 | 0.00 |
| April | 56.78 | 0.32 | 56.46 | 97.35 | 30.93 | 0.00 | 0.00 | 0.00 |
| May | 64.45 | 2.59 | 61.85 | 133.40 | 12.16 | 0.00 | 0.00 | 0.00 |
| June | 68.99 | 4.83 | 64.16 | 156.02 | 3.94 | 0.00 | 0.00 | 0.00 |
| July | 69.77 | 3.24 | 66.53 | 163.89 | 6.37 | 0.00 | 0.00 | 0.00 |
| August | 62.08 | 0.70 | 61.38 | 138.60 | 3.88 | 0.00 | 0.00 | 0.00 |
| September | 54.93 | 0.01 | 54.91 | 128.60 | 9.50 | 0.00 | 0.00 | 0.00 |
| October | 45.99 | 0.00 | 45.99 | 93.74 | 16.05 | 0.00 | 0.00 | 0.00 |
| November | 39.99 | 0.00 | 39.99 | 65.21 | 38.99 | 0.00 | 0.00 | 0.00 |
| December | 35.42 | 0.00 | 35.42 | 42.06 | 71.39 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 52.31 | 0.98 | 51.34 | 98.70 | 33.21 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 35.42 | 0.00 | 35.42 | 36.95 | 3.88 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 69.77 | 4.83 | 66.53 | 163.89 | 85.25 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: GWINDOW1 N N2A
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 35.81 | 0.00 | 35.81 | 36.92 | 85.26 | 0.00 | 0.00 | 0.00 |
| February | 42.39 | 0.00 | 42.39 | 56.74 | 67.85 | 0.00 | 0.00 | 0.00 |
| March | 50.57 | 0.00 | 50.57 | 69.45 | 54.03 | 0.00 | 0.00 | 0.00 |
| April | 56.78 | 0.32 | 56.46 | 97.34 | 30.91 | 0.00 | 0.00 | 0.00 |
| May | 64.45 | 2.59 | 61.85 | 133.39 | 12.15 | 0.00 | 0.00 | 0.00 |
| June | 68.99 | 4.83 | 64.16 | 156.01 | 3.95 | 0.00 | 0.00 | 0.00 |
| July | 69.77 | 3.24 | 66.53 | 163.88 | 6.37 | 0.00 | 0.00 | 0.00 |
| August | 62.08 | 0.70 | 61.38 | 138.60 | 3.88 | 0.00 | 0.00 | 0.00 |
| September | 54.93 | 0.01 | 54.91 | 128.59 | 9.50 | 0.00 | 0.00 | 0.00 |
| October | 45.99 | 0.00 | 45.99 | 93.73 | 16.04 | 0.00 | 0.00 | 0.00 |
| November | 39.99 | 0.00 | 39.99 | 65.20 | 38.98 | 0.00 | 0.00 | 0.00 |
| December | 35.42 | 0.00 | 35.42 | 42.06 | 71.37 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 52.31 | 0.98 | 51.34 | 98.69 | 33.21 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 35.42 | 0.00 | 35.42 | 36.92 | 3.88 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 69.77 | 4.83 | 66.53 | 163.88 | 85.26 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: GWINDOW1 S S1A
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 167.09 | 108.10 | 58.99 | 261.46 | 79.80 | 0.00 | 0.00 | 0.00 |
| February | 152.47 | 88.29 | 64.18 | 252.62 | 65.22 | 0.00 | 0.00 | 0.00 |
| March | 114.21 | 46.73 | 67.48 | 192.05 | 52.39 | 0.00 | 0.00 | 0.00 |
| April | 84.40 | 18.81 | 65.59 | 158.90 | 32.10 | 0.00 | 0.00 | 0.00 |
| May | 64.21 | 1.86 | 62.35 | 134.11 | 11.92 | 0.00 | 0.00 | 0.00 |
| June | 60.79 | 0.17 | 60.63 | 138.83 | 4.07 | 0.00 | 0.00 | 0.00 |
| July | 65.18 | 0.72 | 64.46 | 154.41 | 6.48 | 0.00 | 0.00 | 0.00 |
| August | 73.48 | 5.90 | 67.59 | 164.50 | 4.09 | 0.00 | 0.00 | 0.00 |
| September | 95.46 | 24.11 | 71.35 | 211.39 | 10.02 | 0.00 | 0.00 | 0.00 |
| October | 130.20 | 61.23 | 68.98 | 252.17 | 17.29 | 0.00 | 0.00 | 0.00 |
| November | 148.61 | 83.27 | 65.34 | 257.42 | 38.18 | 0.00 | 0.00 | 0.00 |
| December | 161.82 | 101.89 | 59.92 | 259.50 | 68.96 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 109.61 | 44.88 | 64.73 | 202.83 | 32.40 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 60.79 | 0.17 | 58.99 | 134.11 | 4.07 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 167.09 | 108.10 | 71.35 | 261.46 | 79.80 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: GWINDOW1 S S2A
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 167.09 | 108.10 | 58.99 | 260.97 | 80.55 | 0.00 | 0.00 | 0.00 |
| February | 152.47 | 88.29 | 64.18 | 252.14 | 65.87 | 0.00 | 0.00 | 0.00 |
| March | 114.21 | 46.73 | 67.48 | 191.51 | 53.09 | 0.00 | 0.00 | 0.00 |
| April | 84.40 | 18.81 | 65.59 | 158.23 | 32.90 | 0.00 | 0.00 | 0.00 |
| May | 64.21 | 1.86 | 62.35 | 133.17 | 12.65 | 0.00 | 0.00 | 0.00 |
| June | 60.79 | 0.17 | 60.63 | 137.47 | 4.50 | 0.00 | 0.00 | 0.00 |
| July | 65.18 | 0.72 | 64.46 | 153.10 | 7.05 | 0.00 | 0.00 | 0.00 |
| August | 73.48 | 5.90 | 67.59 | 163.11 | 4.55 | 0.00 | 0.00 | 0.00 |
| September | 95.46 | 24.11 | 71.35 | 210.11 | 10.59 | 0.00 | 0.00 | 0.00 |
| October | 130.20 | 61.23 | 68.98 | 251.23 | 18.21 | 0.00 | 0.00 | 0.00 |
| November | 148.61 | 83.27 | 65.34 | 256.73 | 39.02 | 0.00 | 0.00 | 0.00 |
| December | 161.82 | 101.89 | 59.92 | 259.04 | 69.72 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 109.61 | 44.88 | 64.73 | 201.95 | 33.08 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 60.79 | 0.17 | 58.99 | 133.17 | 4.50 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 167.09 | 108.10 | 71.35 | 260.97 | 80.55 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MWINDOW1 S SWA
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 167.09 | 108.10 | 58.99 | 260.72 | 78.15 | 0.00 | 0.00 | 0.00 |
| February | 152.47 | 88.29 | 64.18 | 251.31 | 64.18 | 0.00 | 0.00 | 0.00 |
| March | 114.21 | 46.73 | 67.48 | 190.14 | 52.39 | 0.00 | 0.00 | 0.00 |
| April | 84.40 | 18.81 | 65.59 | 156.80 | 32.75 | 0.00 | 0.00 | 0.00 |
| May | 64.21 | 1.86 | 62.35 | 132.41 | 12.06 | 0.00 | 0.00 | 0.00 |
| June | 60.79 | 0.17 | 60.63 | 137.53 | 3.98 | 0.00 | 0.00 | 0.00 |
| July | 65.18 | 0.72 | 64.46 | 153.47 | 6.22 | 0.00 | 0.00 | 0.00 |
| August | 73.48 | 5.90 | 67.59 | 164.20 | 3.78 | 0.00 | 0.00 | 0.00 |
| September | 95.46 | 24.11 | 71.35 | 211.09 | 9.35 | 0.00 | 0.00 | 0.00 |
| October | 130.20 | 61.23 | 68.98 | 251.63 | 16.04 | 0.00 | 0.00 | 0.00 |
| November | 148.61 | 83.27 | 65.34 | 256.81 | 36.61 | 0.00 | 0.00 | 0.00 |
| December | 161.82 | 101.89 | 59.92 | 258.71 | 67.10 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 109.61 | 44.88 | 64.73 | 201.79 | 31.74 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 60.79 | 0.17 | 58.99 | 132.41 | 3.78 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 167.09 | 108.10 | 71.35 | 260.72 | 78.15 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MWINDOW1 W SWA
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 51.23 | 22.20 | 29.03 | 71.00 | 55.77 | 0.00 | 0.00 | 0.00 |
| February | 63.95 | 29.04 | 34.91 | 99.68 | 45.19 | 0.00 | 0.00 | 0.00 |
| March | 79.60 | 36.41 | 43.18 | 125.55 | 36.28 | 0.00 | 0.00 | 0.00 |
| April | 87.18 | 40.27 | 46.91 | 151.60 | 21.38 | 0.00 | 0.00 | 0.00 |
| May | 79.83 | 30.82 | 49.01 | 153.15 | 8.31 | 0.00 | 0.00 | 0.00 |
| June | 67.60 | 18.99 | 48.61 | 140.31 | 2.65 | 0.00 | 0.00 | 0.00 |
| July | 75.49 | 23.40 | 52.09 | 159.92 | 3.94 | 0.00 | 0.00 | 0.00 |
| August | 75.26 | 24.48 | 50.77 | 152.46 | 2.43 | 0.00 | 0.00 | 0.00 |
| September | 64.17 | 18.94 | 45.23 | 134.65 | 5.98 | 0.00 | 0.00 | 0.00 |
| October | 63.82 | 24.88 | 38.93 | 121.16 | 10.70 | 0.00 | 0.00 | 0.00 |
| November | 52.59 | 19.24 | 33.35 | 89.41 | 25.82 | 0.00 | 0.00 | 0.00 |
| December | 52.86 | 23.69 | 29.17 | 78.66 | 46.57 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 67.83 | 26.02 | 41.80 | 123.26 | 21.98 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 51.23 | 18.94 | 29.03 | 71.00 | 2.43 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 87.18 | 40.27 | 52.09 | 159.92 | 55.77 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MWINDOW1 W NWA
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 51.23 | 22.20 | 29.03 | 73.26 | 53.44 | 0.00 | 0.00 | 0.00 |
| February | 63.95 | 29.04 | 34.91 | 101.79 | 43.28 | 0.00 | 0.00 | 0.00 |
| March | 79.60 | 36.41 | 43.18 | 126.96 | 35.15 | 0.00 | 0.00 | 0.00 |
| April | 87.18 | 40.27 | 46.91 | 152.20 | 21.10 | 0.00 | 0.00 | 0.00 |
| May | 79.83 | 30.82 | 49.01 | 153.14 | 8.33 | 0.00 | 0.00 | 0.00 |
| June | 67.60 | 18.99 | 48.61 | 140.05 | 2.68 | 0.00 | 0.00 | 0.00 |
| July | 75.49 | 23.40 | 52.09 | 159.78 | 3.97 | 0.00 | 0.00 | 0.00 |
| August | 75.26 | 24.48 | 50.77 | 152.72 | 2.39 | 0.00 | 0.00 | 0.00 |
| September | 64.17 | 18.94 | 45.23 | 135.56 | 5.85 | 0.00 | 0.00 | 0.00 |
| October | 63.82 | 24.88 | 38.93 | 122.55 | 10.08 | 0.00 | 0.00 | 0.00 |
| November | 52.59 | 19.24 | 33.35 | 91.10 | 24.70 | 0.00 | 0.00 | 0.00 |
| December | 52.86 | 23.69 | 29.17 | 80.67 | 44.30 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 67.83 | 26.02 | 41.80 | 124.27 | 21.18 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 51.23 | 18.94 | 29.03 | 73.26 | 2.39 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 87.18 | 40.27 | 52.09 | 159.78 | 53.44 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MWINDOW1 N NWA
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 35.81 | 0.00 | 35.81 | 37.19 | 83.57 | 0.00 | 0.00 | 0.00 |
| February | 42.39 | 0.00 | 42.39 | 56.44 | 66.84 | 0.00 | 0.00 | 0.00 |
| March | 50.57 | 0.00 | 50.57 | 68.11 | 54.43 | 0.00 | 0.00 | 0.00 |
| April | 56.78 | 0.32 | 56.46 | 95.48 | 31.80 | 0.00 | 0.00 | 0.00 |
| May | 64.45 | 2.59 | 61.85 | 131.74 | 12.41 | 0.00 | 0.00 | 0.00 |
| June | 68.99 | 4.83 | 64.16 | 154.62 | 3.83 | 0.00 | 0.00 | 0.00 |
| July | 69.77 | 3.24 | 66.53 | 162.93 | 6.08 | 0.00 | 0.00 | 0.00 |
| August | 62.08 | 0.70 | 61.38 | 138.33 | 3.58 | 0.00 | 0.00 | 0.00 |
| September | 54.93 | 0.01 | 54.91 | 128.58 | 8.91 | 0.00 | 0.00 | 0.00 |
| October | 45.99 | 0.00 | 45.99 | 93.75 | 15.13 | 0.00 | 0.00 | 0.00 |
| November | 39.99 | 0.00 | 39.99 | 65.31 | 37.65 | 0.00 | 0.00 | 0.00 |
| December | 35.42 | 0.00 | 35.42 | 42.33 | 69.35 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 52.31 | 0.98 | 51.34 | 98.10 | 32.65 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 35.42 | 0.00 | 35.42 | 37.19 | 3.58 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 69.77 | 4.83 | 66.53 | 162.93 | 83.57 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MWINDOW1 S SEA
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 167.09 | 108.10 | 58.99 | 260.23 | 77.97 | 0.00 | 0.00 | 0.00 |
| February | 152.47 | 88.29 | 64.18 | 250.88 | 63.89 | 0.00 | 0.00 | 0.00 |
| March | 114.21 | 46.73 | 67.48 | 189.58 | 52.01 | 0.00 | 0.00 | 0.00 |
| April | 84.40 | 18.81 | 65.59 | 156.41 | 32.28 | 0.00 | 0.00 | 0.00 |
| May | 64.21 | 1.86 | 62.35 | 132.19 | 11.82 | 0.00 | 0.00 | 0.00 |
| June | 60.79 | 0.17 | 60.63 | 137.17 | 3.98 | 0.00 | 0.00 | 0.00 |
| July | 65.18 | 0.72 | 64.46 | 153.21 | 6.15 | 0.00 | 0.00 | 0.00 |
| August | 73.48 | 5.90 | 67.59 | 164.17 | 3.71 | 0.00 | 0.00 | 0.00 |
| September | 95.46 | 24.11 | 71.35 | 210.84 | 9.33 | 0.00 | 0.00 | 0.00 |
| October | 130.20 | 61.23 | 68.98 | 251.37 | 15.86 | 0.00 | 0.00 | 0.00 |
| November | 148.61 | 83.27 | 65.34 | 256.53 | 36.43 | 0.00 | 0.00 | 0.00 |
| December | 161.82 | 101.89 | 59.92 | 258.60 | 66.73 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 109.61 | 44.88 | 64.73 | 201.49 | 31.54 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 60.79 | 0.17 | 58.99 | 132.19 | 3.71 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 167.09 | 108.10 | 71.35 | 260.23 | 77.97 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MWINDOW1 E SEA
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 56.89 | 27.34 | 29.55 | 78.55 | 52.46 | 0.00 | 0.00 | 0.00 |
| February | 65.65 | 30.39 | 35.26 | 98.71 | 41.92 | 0.00 | 0.00 | 0.00 |
| March | 80.06 | 37.78 | 42.28 | 122.09 | 33.00 | 0.00 | 0.00 | 0.00 |
| April | 87.31 | 39.08 | 48.23 | 150.29 | 20.46 | 0.00 | 0.00 | 0.00 |
| May | 82.33 | 32.88 | 49.45 | 156.36 | 7.47 | 0.00 | 0.00 | 0.00 |
| June | 81.06 | 31.14 | 49.92 | 164.09 | 2.40 | 0.00 | 0.00 | 0.00 |
| July | 83.44 | 30.19 | 53.25 | 174.06 | 4.00 | 0.00 | 0.00 | 0.00 |
| August | 76.12 | 25.43 | 50.69 | 154.42 | 2.31 | 0.00 | 0.00 | 0.00 |
| September | 73.37 | 26.47 | 46.90 | 151.08 | 5.97 | 0.00 | 0.00 | 0.00 |
| October | 67.61 | 29.08 | 38.52 | 127.32 | 10.04 | 0.00 | 0.00 | 0.00 |
| November | 54.91 | 21.90 | 33.01 | 91.36 | 23.66 | 0.00 | 0.00 | 0.00 |
| December | 44.42 | 15.72 | 28.70 | 62.60 | 45.01 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 71.11 | 28.93 | 42.18 | 127.69 | 20.63 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 44.42 | 15.72 | 28.70 | 62.60 | 2.31 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 87.31 | 39.08 | 53.25 | 174.06 | 52.46 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MWINDOW1 E NEA
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 56.89 | 27.34 | 29.55 | 80.72 | 50.24 | 0.00 | 0.00 | 0.00 |
| February | 65.65 | 30.39 | 35.26 | 100.88 | 40.02 | 0.00 | 0.00 | 0.00 |
| March | 80.06 | 37.78 | 42.28 | 123.52 | 31.96 | 0.00 | 0.00 | 0.00 |
| April | 87.31 | 39.08 | 48.23 | 150.90 | 20.15 | 0.00 | 0.00 | 0.00 |
| May | 82.33 | 32.88 | 49.45 | 156.35 | 7.49 | 0.00 | 0.00 | 0.00 |
| June | 81.06 | 31.14 | 49.92 | 163.82 | 2.42 | 0.00 | 0.00 | 0.00 |
| July | 83.44 | 30.19 | 53.25 | 173.92 | 4.02 | 0.00 | 0.00 | 0.00 |
| August | 76.12 | 25.43 | 50.69 | 154.69 | 2.28 | 0.00 | 0.00 | 0.00 |
| September | 73.37 | 26.47 | 46.90 | 152.02 | 5.84 | 0.00 | 0.00 | 0.00 |
| October | 67.61 | 29.08 | 38.52 | 128.79 | 9.45 | 0.00 | 0.00 | 0.00 |
| November | 54.91 | 21.90 | 33.01 | 93.13 | 22.62 | 0.00 | 0.00 | 0.00 |
| December | 44.42 | 15.72 | 28.70 | 64.60 | 42.67 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 71.11 | 28.93 | 42.18 | 128.71 | 19.85 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 44.42 | 15.72 | 28.70 | 64.60 | 2.28 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 87.31 | 39.08 | 53.25 | 173.92 | 50.24 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MWINDOW1 N NEA
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 35.81 | 0.00 | 35.81 | 36.57 | 83.59 | 0.00 | 0.00 | 0.00 |
| February | 42.39 | 0.00 | 42.39 | 55.96 | 66.58 | 0.00 | 0.00 | 0.00 |
| March | 50.57 | 0.00 | 50.57 | 67.55 | 54.26 | 0.00 | 0.00 | 0.00 |
| April | 56.78 | 0.32 | 56.46 | 95.10 | 31.35 | 0.00 | 0.00 | 0.00 |
| May | 64.45 | 2.59 | 61.85 | 131.49 | 12.15 | 0.00 | 0.00 | 0.00 |
| June | 68.99 | 4.83 | 64.16 | 154.26 | 3.83 | 0.00 | 0.00 | 0.00 |
| July | 69.77 | 3.24 | 66.53 | 162.66 | 6.01 | 0.00 | 0.00 | 0.00 |
| August | 62.08 | 0.70 | 61.38 | 138.31 | 3.52 | 0.00 | 0.00 | 0.00 |
| September | 54.93 | 0.01 | 54.91 | 128.30 | 8.88 | 0.00 | 0.00 | 0.00 |
| October | 45.99 | 0.00 | 45.99 | 93.48 | 14.94 | 0.00 | 0.00 | 0.00 |
| November | 39.99 | 0.00 | 39.99 | 65.01 | 37.53 | 0.00 | 0.00 | 0.00 |
| December | 35.42 | 0.00 | 35.42 | 42.16 | 68.90 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 52.31 | 0.98 | 51.34 | 97.77 | 32.48 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 35.42 | 0.00 | 35.42 | 36.57 | 3.52 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 69.77 | 4.83 | 66.53 | 162.66 | 83.59 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MWINDOW1 N N1A
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 35.81 | 0.00 | 35.81 | 36.99 | 85.09 | 0.00 | 0.00 | 0.00 |
| February | 42.39 | 0.00 | 42.39 | 56.65 | 67.79 | 0.00 | 0.00 | 0.00 |
| March | 50.57 | 0.00 | 50.57 | 68.74 | 54.65 | 0.00 | 0.00 | 0.00 |
| April | 56.78 | 0.32 | 56.46 | 96.90 | 30.95 | 0.00 | 0.00 | 0.00 |
| May | 64.45 | 2.59 | 61.85 | 133.54 | 11.64 | 0.00 | 0.00 | 0.00 |
| June | 68.99 | 4.83 | 64.16 | 156.87 | 3.56 | 0.00 | 0.00 | 0.00 |
| July | 69.77 | 3.24 | 66.53 | 165.31 | 5.64 | 0.00 | 0.00 | 0.00 |
| August | 62.08 | 0.70 | 61.38 | 140.76 | 3.29 | 0.00 | 0.00 | 0.00 |
| September | 54.93 | 0.01 | 54.91 | 130.69 | 8.59 | 0.00 | 0.00 | 0.00 |
| October | 45.99 | 0.00 | 45.99 | 95.23 | 14.52 | 0.00 | 0.00 | 0.00 |
| November | 39.99 | 0.00 | 39.99 | 65.99 | 37.75 | 0.00 | 0.00 | 0.00 |
| December | 35.42 | 0.00 | 35.42 | 42.31 | 70.72 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 52.31 | 0.98 | 51.34 | 99.37 | 32.70 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 35.42 | 0.00 | 35.42 | 36.99 | 3.29 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 69.77 | 4.83 | 66.53 | 165.31 | 85.09 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MWINDOW1 N N2A
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 35.81 | 0.00 | 35.81 | 36.96 | 85.11 | 0.00 | 0.00 | 0.00 |
| February | 42.39 | 0.00 | 42.39 | 56.62 | 67.78 | 0.00 | 0.00 | 0.00 |
| March | 50.57 | 0.00 | 50.57 | 68.70 | 54.66 | 0.00 | 0.00 | 0.00 |
| April | 56.78 | 0.32 | 56.46 | 96.89 | 30.94 | 0.00 | 0.00 | 0.00 |
| May | 64.45 | 2.59 | 61.85 | 133.53 | 11.63 | 0.00 | 0.00 | 0.00 |
| June | 68.99 | 4.83 | 64.16 | 156.86 | 3.57 | 0.00 | 0.00 | 0.00 |
| July | 69.77 | 3.24 | 66.53 | 165.30 | 5.64 | 0.00 | 0.00 | 0.00 |
| August | 62.08 | 0.70 | 61.38 | 140.76 | 3.29 | 0.00 | 0.00 | 0.00 |
| September | 54.93 | 0.01 | 54.91 | 130.68 | 8.59 | 0.00 | 0.00 | 0.00 |
| October | 45.99 | 0.00 | 45.99 | 95.22 | 14.51 | 0.00 | 0.00 | 0.00 |
| November | 39.99 | 0.00 | 39.99 | 65.98 | 37.75 | 0.00 | 0.00 | 0.00 |
| December | 35.42 | 0.00 | 35.42 | 42.31 | 70.70 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 52.31 | 0.98 | 51.34 | 99.35 | 32.70 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 35.42 | 0.00 | 35.42 | 36.96 | 3.29 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 69.77 | 4.83 | 66.53 | 165.30 | 85.11 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MWINDOW1 S S1A
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 167.09 | 108.10 | 58.99 | 260.54 | 78.98 | 0.00 | 0.00 | 0.00 |
| February | 152.47 | 88.29 | 64.18 | 251.45 | 64.74 | 0.00 | 0.00 | 0.00 |
| March | 114.21 | 46.73 | 67.48 | 190.68 | 52.40 | 0.00 | 0.00 | 0.00 |
| April | 84.40 | 18.81 | 65.59 | 158.14 | 31.90 | 0.00 | 0.00 | 0.00 |
| May | 64.21 | 1.86 | 62.35 | 134.34 | 11.33 | 0.00 | 0.00 | 0.00 |
| June | 60.79 | 0.17 | 60.63 | 139.87 | 3.71 | 0.00 | 0.00 | 0.00 |
| July | 65.18 | 0.72 | 64.46 | 155.90 | 5.78 | 0.00 | 0.00 | 0.00 |
| August | 73.48 | 5.90 | 67.59 | 166.63 | 3.48 | 0.00 | 0.00 | 0.00 |
| September | 95.46 | 24.11 | 71.35 | 213.12 | 9.06 | 0.00 | 0.00 | 0.00 |
| October | 130.20 | 61.23 | 68.98 | 252.97 | 15.51 | 0.00 | 0.00 | 0.00 |
| November | 148.61 | 83.27 | 65.34 | 257.37 | 36.60 | 0.00 | 0.00 | 0.00 |
| December | 161.82 | 101.89 | 59.92 | 258.74 | 67.82 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 109.61 | 44.88 | 64.73 | 203.04 | 31.63 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 60.79 | 0.17 | 58.99 | 134.34 | 3.48 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 167.09 | 108.10 | 71.35 | 260.54 | 78.98 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MWINDOW1 S S2A
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 167.09 | 108.10 | 58.99 | 260.52 | 78.98 | 0.00 | 0.00 | 0.00 |
| February | 152.47 | 88.29 | 64.18 | 251.43 | 64.73 | 0.00 | 0.00 | 0.00 |
| March | 114.21 | 46.73 | 67.48 | 190.66 | 52.39 | 0.00 | 0.00 | 0.00 |
| April | 84.40 | 18.81 | 65.59 | 158.13 | 31.89 | 0.00 | 0.00 | 0.00 |
| May | 64.21 | 1.86 | 62.35 | 134.33 | 11.32 | 0.00 | 0.00 | 0.00 |
| June | 60.79 | 0.17 | 60.63 | 139.85 | 3.71 | 0.00 | 0.00 | 0.00 |
| July | 65.18 | 0.72 | 64.46 | 155.89 | 5.78 | 0.00 | 0.00 | 0.00 |
| August | 73.48 | 5.90 | 67.59 | 166.63 | 3.47 | 0.00 | 0.00 | 0.00 |
| September | 95.46 | 24.11 | 71.35 | 213.11 | 9.06 | 0.00 | 0.00 | 0.00 |
| October | 130.20 | 61.23 | 68.98 | 252.96 | 15.51 | 0.00 | 0.00 | 0.00 |
| November | 148.61 | 83.27 | 65.34 | 257.36 | 36.60 | 0.00 | 0.00 | 0.00 |
| December | 161.82 | 101.89 | 59.92 | 258.74 | 67.81 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 109.61 | 44.88 | 64.73 | 203.03 | 31.62 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 60.79 | 0.17 | 58.99 | 134.33 | 3.47 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 167.09 | 108.10 | 71.35 | 260.52 | 78.98 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: TWINDOW1 S SWA
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 167.09 | 108.10 | 58.99 | 260.93 | 71.09 | 0.00 | 0.00 | 0.00 |
| February | 152.47 | 88.29 | 64.18 | 249.75 | 59.13 | 0.00 | 0.00 | 0.00 |
| March | 114.21 | 46.73 | 67.48 | 188.08 | 48.47 | 0.00 | 0.00 | 0.00 |
| April | 84.40 | 18.81 | 65.59 | 152.77 | 31.68 | 0.00 | 0.00 | 0.00 |
| May | 64.21 | 1.86 | 62.35 | 127.68 | 11.83 | 0.00 | 0.00 | 0.00 |
| June | 60.79 | 0.17 | 60.63 | 132.38 | 3.85 | 0.00 | 0.00 | 0.00 |
| July | 65.18 | 0.72 | 64.46 | 147.97 | 6.04 | 0.00 | 0.00 | 0.00 |
| August | 73.48 | 5.90 | 67.59 | 159.20 | 3.72 | 0.00 | 0.00 | 0.00 |
| September | 95.46 | 24.11 | 71.35 | 205.77 | 8.96 | 0.00 | 0.00 | 0.00 |
| October | 130.20 | 61.23 | 68.98 | 247.18 | 15.39 | 0.00 | 0.00 | 0.00 |
| November | 148.61 | 83.27 | 65.34 | 254.05 | 34.05 | 0.00 | 0.00 | 0.00 |
| December | 161.82 | 101.89 | 59.92 | 257.76 | 61.22 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 109.61 | 44.88 | 64.73 | 198.34 | 29.49 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 60.79 | 0.17 | 58.99 | 127.68 | 3.72 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 167.09 | 108.10 | 71.35 | 260.93 | 71.09 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: TWINDOW1 W SWA
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 51.23 | 22.20 | 29.03 | 70.12 | 49.90 | 0.00 | 0.00 | 0.00 |
| February | 63.95 | 29.04 | 34.91 | 98.15 | 41.14 | 0.00 | 0.00 | 0.00 |
| March | 79.60 | 36.41 | 43.18 | 123.68 | 33.03 | 0.00 | 0.00 | 0.00 |
| April | 87.18 | 40.27 | 46.91 | 148.84 | 20.52 | 0.00 | 0.00 | 0.00 |
| May | 79.83 | 30.82 | 49.01 | 149.98 | 8.16 | 0.00 | 0.00 | 0.00 |
| June | 67.60 | 18.99 | 48.61 | 136.85 | 2.56 | 0.00 | 0.00 | 0.00 |
| July | 75.49 | 23.40 | 52.09 | 156.19 | 3.80 | 0.00 | 0.00 | 0.00 |
| August | 75.26 | 24.48 | 50.77 | 149.13 | 2.37 | 0.00 | 0.00 | 0.00 |
| September | 64.17 | 18.94 | 45.23 | 131.17 | 5.68 | 0.00 | 0.00 | 0.00 |
| October | 63.82 | 24.88 | 38.93 | 118.33 | 10.22 | 0.00 | 0.00 | 0.00 |
| November | 52.59 | 19.24 | 33.35 | 87.46 | 23.77 | 0.00 | 0.00 | 0.00 |
| December | 52.86 | 23.69 | 29.17 | 77.54 | 42.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 67.83 | 26.02 | 41.80 | 120.74 | 20.17 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 51.23 | 18.94 | 29.03 | 70.12 | 2.37 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 87.18 | 40.27 | 52.09 | 156.19 | 49.90 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: TWINDOW1 W NWA
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 51.23 | 22.20 | 29.03 | 74.19 | 47.11 | 0.00 | 0.00 | 0.00 |
| February | 63.95 | 29.04 | 34.91 | 101.41 | 39.29 | 0.00 | 0.00 | 0.00 |
| March | 79.60 | 36.41 | 43.18 | 125.90 | 31.93 | 0.00 | 0.00 | 0.00 |
| April | 87.18 | 40.27 | 46.91 | 149.71 | 20.29 | 0.00 | 0.00 | 0.00 |
| May | 79.83 | 30.82 | 49.01 | 149.95 | 8.20 | 0.00 | 0.00 | 0.00 |
| June | 67.60 | 18.99 | 48.61 | 136.50 | 2.59 | 0.00 | 0.00 | 0.00 |
| July | 75.49 | 23.40 | 52.09 | 156.00 | 3.82 | 0.00 | 0.00 | 0.00 |
| August | 75.26 | 24.48 | 50.77 | 149.47 | 2.35 | 0.00 | 0.00 | 0.00 |
| September | 64.17 | 18.94 | 45.23 | 132.36 | 5.60 | 0.00 | 0.00 | 0.00 |
| October | 63.82 | 24.88 | 38.93 | 120.27 | 9.71 | 0.00 | 0.00 | 0.00 |
| November | 52.59 | 19.24 | 33.35 | 90.06 | 22.67 | 0.00 | 0.00 | 0.00 |
| December | 52.86 | 23.69 | 29.17 | 81.02 | 39.31 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 67.83 | 26.02 | 41.80 | 122.35 | 19.32 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 51.23 | 18.94 | 29.03 | 74.19 | 2.35 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 87.18 | 40.27 | 52.09 | 156.00 | 47.11 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: TWINDOW1 N NWA
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 35.81 | 0.00 | 35.81 | 38.69 | 73.94 | 0.00 | 0.00 | 0.00 |
| February | 42.39 | 0.00 | 42.39 | 56.13 | 60.90 | 0.00 | 0.00 | 0.00 |
| March | 50.57 | 0.00 | 50.57 | 66.92 | 49.77 | 0.00 | 0.00 | 0.00 |
| April | 56.78 | 0.32 | 56.46 | 92.07 | 30.80 | 0.00 | 0.00 | 0.00 |
| May | 64.45 | 2.59 | 61.85 | 127.23 | 12.32 | 0.00 | 0.00 | 0.00 |
| June | 68.99 | 4.83 | 64.16 | 149.39 | 3.72 | 0.00 | 0.00 | 0.00 |
| July | 69.77 | 3.24 | 66.53 | 157.43 | 5.91 | 0.00 | 0.00 | 0.00 |
| August | 62.08 | 0.70 | 61.38 | 133.61 | 3.52 | 0.00 | 0.00 | 0.00 |
| September | 54.93 | 0.01 | 54.91 | 123.90 | 8.56 | 0.00 | 0.00 | 0.00 |
| October | 45.99 | 0.00 | 45.99 | 90.49 | 14.60 | 0.00 | 0.00 | 0.00 |
| November | 39.99 | 0.00 | 39.99 | 63.90 | 34.62 | 0.00 | 0.00 | 0.00 |
| December | 35.42 | 0.00 | 35.42 | 42.98 | 61.75 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 52.31 | 0.98 | 51.34 | 95.42 | 29.90 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 35.42 | 0.00 | 35.42 | 38.69 | 3.52 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 69.77 | 4.83 | 66.53 | 157.43 | 73.94 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: TWINDOW1 S SEA
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 167.09 | 108.10 | 58.99 | 259.78 | 70.62 | 0.00 | 0.00 | 0.00 |
| February | 152.47 | 88.29 | 64.18 | 248.86 | 58.50 | 0.00 | 0.00 | 0.00 |
| March | 114.21 | 46.73 | 67.48 | 186.90 | 47.69 | 0.00 | 0.00 | 0.00 |
| April | 84.40 | 18.81 | 65.59 | 152.06 | 30.87 | 0.00 | 0.00 | 0.00 |
| May | 64.21 | 1.86 | 62.35 | 127.31 | 11.41 | 0.00 | 0.00 | 0.00 |
| June | 60.79 | 0.17 | 60.63 | 131.91 | 3.82 | 0.00 | 0.00 | 0.00 |
| July | 65.18 | 0.72 | 64.46 | 147.62 | 5.92 | 0.00 | 0.00 | 0.00 |
| August | 73.48 | 5.90 | 67.59 | 159.17 | 3.61 | 0.00 | 0.00 | 0.00 |
| September | 95.46 | 24.11 | 71.35 | 205.42 | 8.89 | 0.00 | 0.00 | 0.00 |
| October | 130.20 | 61.23 | 68.98 | 246.79 | 15.07 | 0.00 | 0.00 | 0.00 |
| November | 148.61 | 83.27 | 65.34 | 253.54 | 33.71 | 0.00 | 0.00 | 0.00 |
| December | 161.82 | 101.89 | 59.92 | 257.37 | 60.61 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 109.61 | 44.88 | 64.73 | 197.78 | 29.09 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 60.79 | 0.17 | 58.99 | 127.31 | 3.61 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 167.09 | 108.10 | 71.35 | 259.78 | 70.62 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: TWINDOW1 E SEA
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 56.89 | 27.34 | 29.55 | 78.68 | 47.88 | 0.00 | 0.00 | 0.00 |
| February | 65.65 | 30.39 | 35.26 | 97.73 | 38.63 | 0.00 | 0.00 | 0.00 |
| March | 80.06 | 37.78 | 42.28 | 120.68 | 30.53 | 0.00 | 0.00 | 0.00 |
| April | 87.31 | 39.08 | 48.23 | 147.33 | 19.62 | 0.00 | 0.00 | 0.00 |
| May | 82.33 | 32.88 | 49.45 | 152.91 | 7.22 | 0.00 | 0.00 | 0.00 |
| June | 81.06 | 31.14 | 49.92 | 160.38 | 2.30 | 0.00 | 0.00 | 0.00 |
| July | 83.44 | 30.19 | 53.25 | 170.18 | 3.85 | 0.00 | 0.00 | 0.00 |
| August | 76.12 | 25.43 | 50.69 | 150.97 | 2.23 | 0.00 | 0.00 | 0.00 |
| September | 73.37 | 26.47 | 46.90 | 147.43 | 5.70 | 0.00 | 0.00 | 0.00 |
| October | 67.61 | 29.08 | 38.52 | 124.33 | 9.51 | 0.00 | 0.00 | 0.00 |
| November | 54.91 | 21.90 | 33.01 | 89.57 | 21.95 | 0.00 | 0.00 | 0.00 |
| December | 44.42 | 15.72 | 28.70 | 62.12 | 41.12 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 71.11 | 28.93 | 42.18 | 125.30 | 19.13 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 44.42 | 15.72 | 28.70 | 62.12 | 2.23 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 87.31 | 39.08 | 53.25 | 170.18 | 47.88 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: TWINDOW1 E NEA
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 56.89 | 27.34 | 29.55 | 82.30 | 44.77 | 0.00 | 0.00 | 0.00 |
| February | 65.65 | 30.39 | 35.26 | 100.88 | 36.60 | 0.00 | 0.00 | 0.00 |
| March | 80.06 | 37.78 | 42.28 | 122.85 | 29.29 | 0.00 | 0.00 | 0.00 |
| April | 87.31 | 39.08 | 48.23 | 148.20 | 19.35 | 0.00 | 0.00 | 0.00 |
| May | 82.33 | 32.88 | 49.45 | 152.87 | 7.26 | 0.00 | 0.00 | 0.00 |
| June | 81.06 | 31.14 | 49.92 | 160.01 | 2.32 | 0.00 | 0.00 | 0.00 |
| July | 83.44 | 30.19 | 53.25 | 169.98 | 3.88 | 0.00 | 0.00 | 0.00 |
| August | 76.12 | 25.43 | 50.69 | 151.33 | 2.21 | 0.00 | 0.00 | 0.00 |
| September | 73.37 | 26.47 | 46.90 | 148.67 | 5.62 | 0.00 | 0.00 | 0.00 |
| October | 67.61 | 29.08 | 38.52 | 126.34 | 9.03 | 0.00 | 0.00 | 0.00 |
| November | 54.91 | 21.90 | 33.01 | 92.20 | 20.87 | 0.00 | 0.00 | 0.00 |
| December | 44.42 | 15.72 | 28.70 | 65.33 | 37.94 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 71.11 | 28.93 | 42.18 | 126.85 | 18.18 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 44.42 | 15.72 | 28.70 | 65.33 | 2.21 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 87.31 | 39.08 | 53.25 | 169.98 | 44.77 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: TWINDOW1 N NEA
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 35.81 | 0.00 | 35.81 | 37.27 | 73.40 | 0.00 | 0.00 | 0.00 |
| February | 42.39 | 0.00 | 42.39 | 55.09 | 60.20 | 0.00 | 0.00 | 0.00 |
| March | 50.57 | 0.00 | 50.57 | 65.78 | 48.98 | 0.00 | 0.00 | 0.00 |
| April | 56.78 | 0.32 | 56.46 | 91.37 | 30.01 | 0.00 | 0.00 | 0.00 |
| May | 64.45 | 2.59 | 61.85 | 126.84 | 11.88 | 0.00 | 0.00 | 0.00 |
| June | 68.99 | 4.83 | 64.16 | 148.93 | 3.68 | 0.00 | 0.00 | 0.00 |
| July | 69.77 | 3.24 | 66.53 | 157.07 | 5.79 | 0.00 | 0.00 | 0.00 |
| August | 62.08 | 0.70 | 61.38 | 133.59 | 3.42 | 0.00 | 0.00 | 0.00 |
| September | 54.93 | 0.01 | 54.91 | 123.53 | 8.50 | 0.00 | 0.00 | 0.00 |
| October | 45.99 | 0.00 | 45.99 | 90.05 | 14.26 | 0.00 | 0.00 | 0.00 |
| November | 39.99 | 0.00 | 39.99 | 63.30 | 34.31 | 0.00 | 0.00 | 0.00 |
| December | 35.42 | 0.00 | 35.42 | 42.48 | 60.75 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 52.31 | 0.98 | 51.34 | 94.80 | 29.46 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 35.42 | 0.00 | 35.42 | 37.27 | 3.42 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 69.77 | 4.83 | 66.53 | 157.07 | 73.40 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: TWINDOW1 N N1A
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 35.81 | 0.00 | 35.81 | 38.54 | 75.99 | 0.00 | 0.00 | 0.00 |
| February | 42.39 | 0.00 | 42.39 | 56.76 | 61.99 | 0.00 | 0.00 | 0.00 |
| March | 50.57 | 0.00 | 50.57 | 68.04 | 49.97 | 0.00 | 0.00 | 0.00 |
| April | 56.78 | 0.32 | 56.46 | 93.95 | 30.25 | 0.00 | 0.00 | 0.00 |
| May | 64.45 | 2.59 | 61.85 | 129.59 | 11.70 | 0.00 | 0.00 | 0.00 |
| June | 68.99 | 4.83 | 64.16 | 152.17 | 3.56 | 0.00 | 0.00 | 0.00 |
| July | 69.77 | 3.24 | 66.53 | 160.41 | 5.62 | 0.00 | 0.00 | 0.00 |
| August | 62.08 | 0.70 | 61.38 | 136.57 | 3.32 | 0.00 | 0.00 | 0.00 |
| September | 54.93 | 0.01 | 54.91 | 126.57 | 8.41 | 0.00 | 0.00 | 0.00 |
| October | 45.99 | 0.00 | 45.99 | 92.43 | 14.16 | 0.00 | 0.00 | 0.00 |
| November | 39.99 | 0.00 | 39.99 | 64.87 | 35.10 | 0.00 | 0.00 | 0.00 |
| December | 35.42 | 0.00 | 35.42 | 43.24 | 63.06 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 52.31 | 0.98 | 51.34 | 97.12 | 30.12 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 35.42 | 0.00 | 35.42 | 38.54 | 3.32 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 69.77 | 4.83 | 66.53 | 160.41 | 75.99 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: TWINDOW1 N N2A
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 35.81 | 0.00 | 35.81 | 38.45 | 75.97 | 0.00 | 0.00 | 0.00 |
| February | 42.39 | 0.00 | 42.39 | 56.69 | 61.95 | 0.00 | 0.00 | 0.00 |
| March | 50.57 | 0.00 | 50.57 | 67.95 | 49.92 | 0.00 | 0.00 | 0.00 |
| April | 56.78 | 0.32 | 56.46 | 93.91 | 30.21 | 0.00 | 0.00 | 0.00 |
| May | 64.45 | 2.59 | 61.85 | 129.57 | 11.68 | 0.00 | 0.00 | 0.00 |
| June | 68.99 | 4.83 | 64.16 | 152.15 | 3.55 | 0.00 | 0.00 | 0.00 |
| July | 69.77 | 3.24 | 66.53 | 160.40 | 5.61 | 0.00 | 0.00 | 0.00 |
| August | 62.08 | 0.70 | 61.38 | 136.56 | 3.32 | 0.00 | 0.00 | 0.00 |
| September | 54.93 | 0.01 | 54.91 | 126.55 | 8.41 | 0.00 | 0.00 | 0.00 |
| October | 45.99 | 0.00 | 45.99 | 92.41 | 14.15 | 0.00 | 0.00 | 0.00 |
| November | 39.99 | 0.00 | 39.99 | 64.84 | 35.09 | 0.00 | 0.00 | 0.00 |
| December | 35.42 | 0.00 | 35.42 | 43.21 | 62.99 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 52.31 | 0.98 | 51.34 | 97.08 | 30.10 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 35.42 | 0.00 | 35.42 | 38.45 | 3.32 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 69.77 | 4.83 | 66.53 | 160.40 | 75.97 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: TWINDOW1 S S1A
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 167.09 | 108.10 | 58.99 | 260.33 | 73.32 | 0.00 | 0.00 | 0.00 |
| February | 152.47 | 88.29 | 64.18 | 249.97 | 60.46 | 0.00 | 0.00 | 0.00 |
| March | 114.21 | 46.73 | 67.48 | 188.87 | 48.98 | 0.00 | 0.00 | 0.00 |
| April | 84.40 | 18.81 | 65.59 | 154.55 | 31.12 | 0.00 | 0.00 | 0.00 |
| May | 64.21 | 1.86 | 62.35 | 130.20 | 11.25 | 0.00 | 0.00 | 0.00 |
| June | 60.79 | 0.17 | 60.63 | 135.28 | 3.70 | 0.00 | 0.00 | 0.00 |
| July | 65.18 | 0.72 | 64.46 | 151.03 | 5.75 | 0.00 | 0.00 | 0.00 |
| August | 73.48 | 5.90 | 67.59 | 162.18 | 3.52 | 0.00 | 0.00 | 0.00 |
| September | 95.46 | 24.11 | 71.35 | 208.32 | 8.82 | 0.00 | 0.00 | 0.00 |
| October | 130.20 | 61.23 | 68.98 | 248.96 | 15.03 | 0.00 | 0.00 | 0.00 |
| November | 148.61 | 83.27 | 65.34 | 254.76 | 34.55 | 0.00 | 0.00 | 0.00 |
| December | 161.82 | 101.89 | 59.92 | 257.72 | 62.90 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 109.61 | 44.88 | 64.73 | 199.90 | 29.81 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 60.79 | 0.17 | 58.99 | 130.20 | 3.52 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 167.09 | 108.10 | 71.35 | 260.33 | 73.32 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: TWINDOW1 S S2A
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 167.09 | 108.10 | 58.99 | 260.28 | 73.29 | 0.00 | 0.00 | 0.00 |
| February | 152.47 | 88.29 | 64.18 | 249.92 | 60.42 | 0.00 | 0.00 | 0.00 |
| March | 114.21 | 46.73 | 67.48 | 188.80 | 48.94 | 0.00 | 0.00 | 0.00 |
| April | 84.40 | 18.81 | 65.59 | 154.51 | 31.08 | 0.00 | 0.00 | 0.00 |
| May | 64.21 | 1.86 | 62.35 | 130.18 | 11.23 | 0.00 | 0.00 | 0.00 |
| June | 60.79 | 0.17 | 60.63 | 135.25 | 3.69 | 0.00 | 0.00 | 0.00 |
| July | 65.18 | 0.72 | 64.46 | 151.01 | 5.75 | 0.00 | 0.00 | 0.00 |
| August | 73.48 | 5.90 | 67.59 | 162.18 | 3.51 | 0.00 | 0.00 | 0.00 |
| September | 95.46 | 24.11 | 71.35 | 208.31 | 8.82 | 0.00 | 0.00 | 0.00 |
| October | 130.20 | 61.23 | 68.98 | 248.94 | 15.01 | 0.00 | 0.00 | 0.00 |
| November | 148.61 | 83.27 | 65.34 | 254.73 | 34.54 | 0.00 | 0.00 | 0.00 |
| December | 161.82 | 101.89 | 59.92 | 257.69 | 62.87 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 109.61 | 44.88 | 64.73 | 199.87 | 29.79 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 60.79 | 0.17 | 58.99 | 130.18 | 3.51 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 167.09 | 108.10 | 71.35 | 260.28 | 73.29 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: TWINDOW14
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 13.65 | 6.56 | 7.09 | 18.50 | 13.36 | 291.33 | 0.00 | 0.00 |
| February | 15.75 | 7.29 | 8.46 | 22.67 | 11.13 | 122.50 | 0.00 | 0.00 |
| March | 19.21 | 9.07 | 10.15 | 27.79 | 9.14 | 139.17 | 0.00 | 0.00 |
| April | 20.95 | 9.38 | 11.57 | 33.65 | 6.54 | 187.00 | 0.00 | 0.00 |
| May | 19.76 | 7.89 | 11.87 | 34.42 | 3.31 | 228.67 | 0.00 | 0.00 |
| June | 19.45 | 7.47 | 11.98 | 35.37 | 1.42 | 164.50 | 0.00 | 0.00 |
| July | 20.02 | 7.24 | 12.78 | 38.09 | 2.10 | 238.33 | 0.00 | 0.00 |
| August | 18.26 | 6.10 | 12.16 | 33.37 | 1.58 | 205.83 | 0.00 | 0.00 |
| September | 17.61 | 6.35 | 11.25 | 32.70 | 2.37 | 200.33 | 0.00 | 0.00 |
| October | 16.22 | 6.98 | 9.24 | 28.24 | 3.94 | 283.50 | 0.00 | 0.00 |
| November | 13.18 | 5.25 | 7.92 | 20.39 | 7.02 | 229.67 | 0.00 | 0.00 |
| December | 10.66 | 3.77 | 6.89 | 14.38 | 11.80 | 281.00 | 0.00 | 0.00 |
| Annual Sum or Average | 17.06 | 6.94 | 10.12 | 28.32 | 6.12 | 2571.83 | 0.00 | 0.00 |
| Minimum of Months | 10.66 | 3.77 | 6.89 | 14.38 | 1.42 | 122.50 | 0.00 | 0.00 |
| Maximum of Months | 20.95 | 9.38 | 12.78 | 38.09 | 13.36 | 291.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ENTRANCE DOOR
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 40.66 | 19.53 | 21.12 | 53.70 | 42.72 | 39.67 | 0.00 | 0.00 |
| February | 46.91 | 21.72 | 25.20 | 66.95 | 35.34 | 14.33 | 0.00 | 0.00 |
| March | 57.21 | 27.00 | 30.21 | 82.86 | 28.80 | 33.17 | 0.00 | 0.00 |
| April | 62.40 | 27.93 | 34.47 | 100.36 | 20.96 | 34.50 | 0.00 | 0.00 |
| May | 58.84 | 23.50 | 35.34 | 101.70 | 11.67 | 77.67 | 0.00 | 0.00 |
| June | 57.93 | 22.26 | 35.67 | 103.45 | 5.78 | 112.67 | 0.00 | 0.00 |
| July | 59.63 | 21.57 | 38.06 | 110.95 | 8.51 | 130.17 | 0.00 | 0.00 |
| August | 54.40 | 18.17 | 36.22 | 96.59 | 7.15 | 127.17 | 0.00 | 0.00 |
| September | 52.43 | 18.92 | 33.51 | 94.74 | 9.38 | 122.67 | 0.00 | 0.00 |
| October | 48.31 | 20.78 | 27.53 | 82.13 | 15.08 | 108.83 | 0.00 | 0.00 |
| November | 39.24 | 15.65 | 23.59 | 59.50 | 24.03 | 90.83 | 0.00 | 0.00 |
| December | 31.74 | 11.23 | 20.51 | 41.63 | 38.02 | 59.50 | 0.00 | 0.00 |
| Annual Sum or Average | 50.82 | 20.68 | 30.14 | 82.94 | 20.56 | 951.17 | 0.00 | 0.00 |
| Minimum of Months | 31.74 | 11.23 | 20.51 | 41.63 | 5.78 | 14.33 | 0.00 | 0.00 |
| Maximum of Months | 62.40 | 27.93 | 38.06 | 110.95 | 42.72 | 130.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MWINDOW14
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 13.65 | 6.56 | 7.09 | 17.68 | 14.75 | 402.50 | 0.00 | 0.00 |
| February | 15.75 | 7.29 | 8.46 | 22.19 | 12.08 | 212.17 | 0.00 | 0.00 |
| March | 19.21 | 9.07 | 10.15 | 27.45 | 9.84 | 217.83 | 0.00 | 0.00 |
| April | 20.95 | 9.38 | 11.57 | 33.94 | 6.74 | 260.67 | 0.00 | 0.00 |
| May | 19.76 | 7.89 | 11.87 | 35.03 | 3.29 | 268.17 | 0.00 | 0.00 |
| June | 19.45 | 7.47 | 11.98 | 36.20 | 1.39 | 163.17 | 0.00 | 0.00 |
| July | 20.02 | 7.24 | 12.78 | 38.93 | 2.04 | 227.00 | 0.00 | 0.00 |
| August | 18.26 | 6.10 | 12.16 | 34.10 | 1.53 | 205.83 | 0.00 | 0.00 |
| September | 17.61 | 6.35 | 11.25 | 33.48 | 2.40 | 202.17 | 0.00 | 0.00 |
| October | 16.22 | 6.98 | 9.24 | 28.62 | 4.02 | 315.67 | 0.00 | 0.00 |
| November | 13.18 | 5.25 | 7.92 | 20.32 | 7.49 | 281.00 | 0.00 | 0.00 |
| December | 10.66 | 3.77 | 6.89 | 13.87 | 13.02 | 384.17 | 0.00 | 0.00 |
| Annual Sum or Average | 17.06 | 6.94 | 10.12 | 28.51 | 6.53 | 3140.33 | 0.00 | 0.00 |
| Minimum of Months | 10.66 | 3.77 | 6.89 | 13.87 | 1.39 | 163.17 | 0.00 | 0.00 |
| Maximum of Months | 20.95 | 9.38 | 12.78 | 38.93 | 14.75 | 402.50 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: GWINDOW1 S SWA
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.447539E+09 | 0.289548E+09 | 0.157992E+09 | 0.700443E+09 | 0.212254E+09 |
| February | 0.368860E+09 | 0.213589E+09 | 0.155271E+09 | 0.610822E+09 | 0.156697E+09 |
| March | 0.305895E+09 | 0.125166E+09 | 0.180729E+09 | 0.513495E+09 | 0.139835E+09 |
| April | 0.218759E+09 | 48762672.05 | 0.169997E+09 | 0.409092E+09 | 84902950.82 |
| May | 0.171985E+09 | 4985512.72 | 0.166999E+09 | 0.354658E+09 | 33759099.26 |
| June | 0.157580E+09 | 438652.82 | 0.157142E+09 | 0.354297E+09 | 11210892.16 |
| July | 0.174576E+09 | 1932094.98 | 0.172644E+09 | 0.407004E+09 | 18806240.68 |
| August | 0.196815E+09 | 15792809.78 | 0.181022E+09 | 0.433592E+09 | 12216279.23 |
| September | 0.247423E+09 | 62495235.59 | 0.184928E+09 | 0.541957E+09 | 27204013.33 |
| October | 0.348736E+09 | 0.163993E+09 | 0.184743E+09 | 0.671434E+09 | 48587953.45 |
| November | 0.385200E+09 | 0.215831E+09 | 0.169369E+09 | 0.665260E+09 | 99896268.72 |
| December | 0.433407E+09 | 0.272909E+09 | 0.160498E+09 | 0.694456E+09 | 0.183918E+09 |
| Annual Sum or Average | 0.345677E+10 | 0.141544E+10 | 0.204133E+10 | 0.635651E+10 | 0.102929E+10 |
| Minimum of Months | 0.157580E+09 | 438652.82 | 0.155271E+09 | 0.354297E+09 | 11210892.16 |
| Maximum of Months | 0.447539E+09 | 0.289548E+09 | 0.184928E+09 | 0.700443E+09 | 0.212254E+09 |
Report: WindowEnergyReportMonthly
For: GWINDOW1 W SWA
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.137216E+09 | 59462026.64 | 77754226.73 | 0.190569E+09 | 0.151179E+09 |
| February | 0.154698E+09 | 70244097.88 | 84453894.02 | 0.242056E+09 | 0.110133E+09 |
| March | 0.213188E+09 | 97527639.98 | 0.115660E+09 | 0.338757E+09 | 96598781.87 |
| April | 0.225961E+09 | 0.104374E+09 | 0.121587E+09 | 0.394923E+09 | 55295058.55 |
| May | 0.213812E+09 | 82544160.59 | 0.131268E+09 | 0.411055E+09 | 23034433.62 |
| June | 0.175217E+09 | 49233297.07 | 0.125984E+09 | 0.363067E+09 | 7451693.71 |
| July | 0.202190E+09 | 62668635.49 | 0.139522E+09 | 0.426468E+09 | 12007886.98 |
| August | 0.201575E+09 | 65580447.78 | 0.135994E+09 | 0.404982E+09 | 7884397.24 |
| September | 0.166336E+09 | 49094784.96 | 0.117241E+09 | 0.345505E+09 | 17507721.82 |
| October | 0.170925E+09 | 66648864.77 | 0.104276E+09 | 0.322213E+09 | 32480521.90 |
| November | 0.136319E+09 | 49872369.86 | 86446752.73 | 0.230665E+09 | 70312393.66 |
| December | 0.141581E+09 | 63440405.52 | 78140754.64 | 0.210717E+09 | 0.127425E+09 |
| Annual Sum or Average | 0.213902E+10 | 0.820691E+09 | 0.131833E+10 | 0.388098E+10 | 0.711310E+09 |
| Minimum of Months | 0.136319E+09 | 49094784.96 | 77754226.73 | 0.190569E+09 | 7451693.71 |
| Maximum of Months | 0.225961E+09 | 0.104374E+09 | 0.139522E+09 | 0.426468E+09 | 0.151179E+09 |
Report: WindowEnergyReportMonthly
For: GWINDOW1 W NWA
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.137216E+09 | 59462026.64 | 77754226.73 | 0.196521E+09 | 0.144252E+09 |
| February | 0.154698E+09 | 70244097.88 | 84453894.02 | 0.247184E+09 | 0.105039E+09 |
| March | 0.213188E+09 | 97527639.98 | 0.115660E+09 | 0.342885E+09 | 92819740.31 |
| April | 0.225961E+09 | 0.104374E+09 | 0.121587E+09 | 0.396654E+09 | 54293628.17 |
| May | 0.213812E+09 | 82544160.59 | 0.131268E+09 | 0.410996E+09 | 23159080.22 |
| June | 0.175217E+09 | 49233297.07 | 0.125984E+09 | 0.362211E+09 | 7617073.33 |
| July | 0.202190E+09 | 62668635.49 | 0.139522E+09 | 0.425955E+09 | 12161165.52 |
| August | 0.201575E+09 | 65580447.78 | 0.135994E+09 | 0.405676E+09 | 7788450.93 |
| September | 0.166336E+09 | 49094784.96 | 0.117241E+09 | 0.348042E+09 | 17041065.70 |
| October | 0.170925E+09 | 66648864.77 | 0.104276E+09 | 0.326098E+09 | 30217301.44 |
| November | 0.136319E+09 | 49872369.86 | 86446752.73 | 0.235107E+09 | 66836540.29 |
| December | 0.141581E+09 | 63440405.52 | 78140754.64 | 0.215801E+09 | 0.121173E+09 |
| Annual Sum or Average | 0.213902E+10 | 0.820691E+09 | 0.131833E+10 | 0.391313E+10 | 0.682398E+09 |
| Minimum of Months | 0.136319E+09 | 49094784.96 | 77754226.73 | 0.196521E+09 | 7617073.33 |
| Maximum of Months | 0.225961E+09 | 0.104374E+09 | 0.139522E+09 | 0.425955E+09 | 0.144252E+09 |
Report: WindowEnergyReportMonthly
For: GWINDOW1 N NWA
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 95922893.25 | 0.00 | 95922893.25 | 98950833.54 | 0.225934E+09 |
| February | 0.102552E+09 | 0.00 | 0.102552E+09 | 0.136720E+09 | 0.162518E+09 |
| March | 0.135455E+09 | 8987.58 | 0.135446E+09 | 0.184855E+09 | 0.143899E+09 |
| April | 0.147170E+09 | 822185.82 | 0.146348E+09 | 0.249245E+09 | 82017414.59 |
| May | 0.172610E+09 | 6939233.84 | 0.165670E+09 | 0.352915E+09 | 34566943.17 |
| June | 0.178820E+09 | 12506596.35 | 0.166314E+09 | 0.398903E+09 | 10915340.69 |
| July | 0.186873E+09 | 8688044.55 | 0.178185E+09 | 0.432434E+09 | 18606591.99 |
| August | 0.166270E+09 | 1873332.33 | 0.164397E+09 | 0.364061E+09 | 11692360.05 |
| September | 0.142367E+09 | 28547.29 | 0.142339E+09 | 0.326908E+09 | 25974052.69 |
| October | 0.123193E+09 | 0.00 | 0.123193E+09 | 0.246586E+09 | 45701337.66 |
| November | 0.103661E+09 | 0.00 | 0.103661E+09 | 0.166636E+09 | 0.102204E+09 |
| December | 94879756.67 | 0.00 | 94879756.67 | 0.111884E+09 | 0.189997E+09 |
| Annual Sum or Average | 0.164977E+10 | 30866927.75 | 0.161891E+10 | 0.307010E+10 | 0.105403E+10 |
| Minimum of Months | 94879756.67 | 0.00 | 94879756.67 | 98950833.54 | 10915340.69 |
| Maximum of Months | 0.186873E+09 | 12506596.35 | 0.178185E+09 | 0.432434E+09 | 0.225934E+09 |
Report: WindowEnergyReportMonthly
For: GWINDOW1 S SEA
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.447539E+09 | 0.289548E+09 | 0.157992E+09 | 0.674849E+09 | 0.266756E+09 |
| February | 0.368860E+09 | 0.213589E+09 | 0.155271E+09 | 0.589342E+09 | 0.199384E+09 |
| March | 0.305895E+09 | 0.125166E+09 | 0.180729E+09 | 0.489095E+09 | 0.187029E+09 |
| April | 0.218759E+09 | 48762672.05 | 0.169997E+09 | 0.375262E+09 | 0.140126E+09 |
| May | 0.171985E+09 | 4985512.72 | 0.166999E+09 | 0.309402E+09 | 91734375.73 |
| June | 0.157580E+09 | 438652.82 | 0.157142E+09 | 0.292026E+09 | 57959318.44 |
| July | 0.174576E+09 | 1932094.98 | 0.172644E+09 | 0.342972E+09 | 77396283.82 |
| August | 0.196815E+09 | 15792809.78 | 0.181022E+09 | 0.374380E+09 | 71511415.07 |
| September | 0.247423E+09 | 62495235.59 | 0.184928E+09 | 0.478759E+09 | 83497771.10 |
| October | 0.348736E+09 | 0.163993E+09 | 0.184743E+09 | 0.625295E+09 | 0.124680E+09 |
| November | 0.385200E+09 | 0.215831E+09 | 0.169369E+09 | 0.631916E+09 | 0.163374E+09 |
| December | 0.433407E+09 | 0.272909E+09 | 0.160498E+09 | 0.669599E+09 | 0.238355E+09 |
| Annual Sum or Average | 0.345677E+10 | 0.141544E+10 | 0.204133E+10 | 0.585290E+10 | 0.170180E+10 |
| Minimum of Months | 0.157580E+09 | 438652.82 | 0.155271E+09 | 0.292026E+09 | 57959318.44 |
| Maximum of Months | 0.447539E+09 | 0.289548E+09 | 0.184928E+09 | 0.674849E+09 | 0.266756E+09 |
Report: WindowEnergyReportMonthly
For: GWINDOW1 E SEA
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.152373E+09 | 73214687.62 | 79157903.76 | 0.196233E+09 | 0.179731E+09 |
| February | 0.158810E+09 | 73517497.32 | 85292300.99 | 0.226867E+09 | 0.131469E+09 |
| March | 0.214432E+09 | 0.101192E+09 | 0.113241E+09 | 0.313600E+09 | 0.119117E+09 |
| April | 0.226316E+09 | 0.101302E+09 | 0.125013E+09 | 0.368088E+09 | 88769944.16 |
| May | 0.220522E+09 | 88072297.16 | 0.132449E+09 | 0.387650E+09 | 57647885.67 |
| June | 0.210113E+09 | 80722048.01 | 0.129391E+09 | 0.380247E+09 | 34923357.58 |
| July | 0.223483E+09 | 80852891.11 | 0.142630E+09 | 0.419466E+09 | 48966224.71 |
| August | 0.203875E+09 | 68111557.53 | 0.135764E+09 | 0.368515E+09 | 45145717.55 |
| September | 0.190174E+09 | 68618181.15 | 0.121556E+09 | 0.343946E+09 | 52491353.66 |
| October | 0.181073E+09 | 77895027.35 | 0.103178E+09 | 0.308331E+09 | 81099522.47 |
| November | 0.142321E+09 | 56755460.23 | 85565885.21 | 0.214534E+09 | 0.107430E+09 |
| December | 0.118964E+09 | 42102991.35 | 76860568.64 | 0.152662E+09 | 0.160883E+09 |
| Annual Sum or Average | 0.224246E+10 | 0.912357E+09 | 0.133010E+10 | 0.368014E+10 | 0.110767E+10 |
| Minimum of Months | 0.118964E+09 | 42102991.35 | 76860568.64 | 0.152662E+09 | 34923357.58 |
| Maximum of Months | 0.226316E+09 | 0.101302E+09 | 0.142630E+09 | 0.419466E+09 | 0.179731E+09 |
Report: WindowEnergyReportMonthly
For: GWINDOW1 E NEA
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.152373E+09 | 73214687.62 | 79157903.76 | 0.216540E+09 | 0.135787E+09 |
| February | 0.158810E+09 | 73517497.32 | 85292300.99 | 0.245177E+09 | 97354405.58 |
| March | 0.214432E+09 | 0.101192E+09 | 0.113241E+09 | 0.334101E+09 | 84577034.71 |
| April | 0.226316E+09 | 0.101302E+09 | 0.125013E+09 | 0.393686E+09 | 52021841.24 |
| May | 0.220522E+09 | 88072297.16 | 0.132449E+09 | 0.419751E+09 | 21029743.11 |
| June | 0.210113E+09 | 80722048.01 | 0.129391E+09 | 0.423808E+09 | 6966281.45 |
| July | 0.223483E+09 | 80852891.11 | 0.142630E+09 | 0.463752E+09 | 12202524.76 |
| August | 0.203875E+09 | 68111557.53 | 0.135764E+09 | 0.410505E+09 | 7388093.68 |
| September | 0.190174E+09 | 68618181.15 | 0.121556E+09 | 0.390507E+09 | 16900355.86 |
| October | 0.181073E+09 | 77895027.35 | 0.103178E+09 | 0.342619E+09 | 28467929.83 |
| November | 0.142321E+09 | 56755460.23 | 85565885.21 | 0.240161E+09 | 61362313.08 |
| December | 0.118964E+09 | 42102991.35 | 76860568.64 | 0.172451E+09 | 0.116849E+09 |
| Annual Sum or Average | 0.224246E+10 | 0.912357E+09 | 0.133010E+10 | 0.405306E+10 | 0.640907E+09 |
| Minimum of Months | 0.118964E+09 | 42102991.35 | 76860568.64 | 0.172451E+09 | 6966281.45 |
| Maximum of Months | 0.226316E+09 | 0.101302E+09 | 0.142630E+09 | 0.463752E+09 | 0.135787E+09 |
Report: WindowEnergyReportMonthly
For: GWINDOW1 N NEA
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 95922893.25 | 0.00 | 95922893.25 | 97550315.54 | 0.226025E+09 |
| February | 0.102552E+09 | 0.00 | 0.102552E+09 | 0.135676E+09 | 0.161994E+09 |
| March | 0.135455E+09 | 8987.58 | 0.135446E+09 | 0.183543E+09 | 0.143365E+09 |
| April | 0.147170E+09 | 822185.82 | 0.146348E+09 | 0.248326E+09 | 80889741.77 |
| May | 0.172610E+09 | 6939233.84 | 0.165670E+09 | 0.352273E+09 | 33888041.12 |
| June | 0.178820E+09 | 12506596.35 | 0.166314E+09 | 0.397826E+09 | 10981502.02 |
| July | 0.186873E+09 | 8688044.55 | 0.178185E+09 | 0.431664E+09 | 18453973.21 |
| August | 0.166270E+09 | 1873332.33 | 0.164397E+09 | 0.363950E+09 | 11496646.99 |
| September | 0.142367E+09 | 28547.29 | 0.142339E+09 | 0.326165E+09 | 25971914.92 |
| October | 0.123193E+09 | 0.00 | 0.123193E+09 | 0.245856E+09 | 45249644.50 |
| November | 0.103661E+09 | 0.00 | 0.103661E+09 | 0.165948E+09 | 0.101855E+09 |
| December | 94879756.67 | 0.00 | 94879756.67 | 0.111595E+09 | 0.188824E+09 |
| Annual Sum or Average | 0.164977E+10 | 30866927.75 | 0.161891E+10 | 0.306037E+10 | 0.104899E+10 |
| Minimum of Months | 94879756.67 | 0.00 | 94879756.67 | 97550315.54 | 10981502.02 |
| Maximum of Months | 0.186873E+09 | 12506596.35 | 0.178185E+09 | 0.431664E+09 | 0.226025E+09 |
Report: WindowEnergyReportMonthly
For: GWINDOW1 N N1A
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 95922893.25 | 0.00 | 95922893.25 | 98961155.64 | 0.228336E+09 |
| February | 0.102552E+09 | 0.00 | 0.102552E+09 | 0.137309E+09 | 0.164153E+09 |
| March | 0.135455E+09 | 8987.58 | 0.135446E+09 | 0.186096E+09 | 0.144716E+09 |
| April | 0.147170E+09 | 822185.82 | 0.146348E+09 | 0.252338E+09 | 80166843.30 |
| May | 0.172610E+09 | 6939233.84 | 0.165670E+09 | 0.357296E+09 | 32564688.79 |
| June | 0.178820E+09 | 12506596.35 | 0.166314E+09 | 0.404415E+09 | 10221571.69 |
| July | 0.186873E+09 | 8688044.55 | 0.178185E+09 | 0.438966E+09 | 17052170.17 |
| August | 0.166270E+09 | 1873332.33 | 0.164397E+09 | 0.371223E+09 | 10387090.47 |
| September | 0.142367E+09 | 28547.29 | 0.142339E+09 | 0.333342E+09 | 24630467.82 |
| October | 0.123193E+09 | 0.00 | 0.123193E+09 | 0.251085E+09 | 42976319.68 |
| November | 0.103661E+09 | 0.00 | 0.103661E+09 | 0.169015E+09 | 0.101056E+09 |
| December | 94879756.67 | 0.00 | 94879756.67 | 0.112650E+09 | 0.191204E+09 |
| Annual Sum or Average | 0.164977E+10 | 30866927.75 | 0.161891E+10 | 0.311269E+10 | 0.104746E+10 |
| Minimum of Months | 94879756.67 | 0.00 | 94879756.67 | 98961155.64 | 10221571.69 |
| Maximum of Months | 0.186873E+09 | 12506596.35 | 0.178185E+09 | 0.438966E+09 | 0.228336E+09 |
Report: WindowEnergyReportMonthly
For: GWINDOW1 N N2A
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 95922893.25 | 0.00 | 95922893.25 | 98899355.90 | 0.228368E+09 |
| February | 0.102552E+09 | 0.00 | 0.102552E+09 | 0.137261E+09 | 0.164152E+09 |
| March | 0.135455E+09 | 8987.58 | 0.135446E+09 | 0.186024E+09 | 0.144725E+09 |
| April | 0.147170E+09 | 822185.82 | 0.146348E+09 | 0.252307E+09 | 80131031.20 |
| May | 0.172610E+09 | 6939233.84 | 0.165670E+09 | 0.357274E+09 | 32544238.89 |
| June | 0.178820E+09 | 12506596.35 | 0.166314E+09 | 0.404366E+09 | 10228741.97 |
| July | 0.186873E+09 | 8688044.55 | 0.178185E+09 | 0.438936E+09 | 17050876.93 |
| August | 0.166270E+09 | 1873332.33 | 0.164397E+09 | 0.371218E+09 | 10382024.22 |
| September | 0.142367E+09 | 28547.29 | 0.142339E+09 | 0.333311E+09 | 24634877.26 |
| October | 0.123193E+09 | 0.00 | 0.123193E+09 | 0.251058E+09 | 42966087.01 |
| November | 0.103661E+09 | 0.00 | 0.103661E+09 | 0.168988E+09 | 0.101048E+09 |
| December | 94879756.67 | 0.00 | 94879756.67 | 0.112645E+09 | 0.191150E+09 |
| Annual Sum or Average | 0.164977E+10 | 30866927.75 | 0.161891E+10 | 0.311229E+10 | 0.104738E+10 |
| Minimum of Months | 94879756.67 | 0.00 | 94879756.67 | 98899355.90 | 10228741.97 |
| Maximum of Months | 0.186873E+09 | 12506596.35 | 0.178185E+09 | 0.438936E+09 | 0.228368E+09 |
Report: WindowEnergyReportMonthly
For: GWINDOW1 S S1A
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.447539E+09 | 0.289548E+09 | 0.157992E+09 | 0.700299E+09 | 0.213744E+09 |
| February | 0.368860E+09 | 0.213589E+09 | 0.155271E+09 | 0.611141E+09 | 0.157787E+09 |
| March | 0.305895E+09 | 0.125166E+09 | 0.180729E+09 | 0.514393E+09 | 0.140329E+09 |
| April | 0.218759E+09 | 48762672.05 | 0.169997E+09 | 0.411880E+09 | 83205132.93 |
| May | 0.171985E+09 | 4985512.72 | 0.166999E+09 | 0.359205E+09 | 31922266.00 |
| June | 0.157580E+09 | 438652.82 | 0.157142E+09 | 0.359852E+09 | 10546151.75 |
| July | 0.174576E+09 | 1932094.98 | 0.172644E+09 | 0.413570E+09 | 17343976.34 |
| August | 0.196815E+09 | 15792809.78 | 0.181022E+09 | 0.440608E+09 | 10958288.19 |
| September | 0.247423E+09 | 62495235.59 | 0.184928E+09 | 0.547929E+09 | 25972621.10 |
| October | 0.348736E+09 | 0.163993E+09 | 0.184743E+09 | 0.675424E+09 | 46304788.63 |
| November | 0.385200E+09 | 0.215831E+09 | 0.169369E+09 | 0.667241E+09 | 98962860.64 |
| December | 0.433407E+09 | 0.272909E+09 | 0.160498E+09 | 0.695050E+09 | 0.184711E+09 |
| Annual Sum or Average | 0.345677E+10 | 0.141544E+10 | 0.204133E+10 | 0.639659E+10 | 0.102179E+10 |
| Minimum of Months | 0.157580E+09 | 438652.82 | 0.155271E+09 | 0.359205E+09 | 10546151.75 |
| Maximum of Months | 0.447539E+09 | 0.289548E+09 | 0.184928E+09 | 0.700299E+09 | 0.213744E+09 |
Report: WindowEnergyReportMonthly
For: GWINDOW1 S S2A
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.447539E+09 | 0.289548E+09 | 0.157992E+09 | 0.698992E+09 | 0.215756E+09 |
| February | 0.368860E+09 | 0.213589E+09 | 0.155271E+09 | 0.609975E+09 | 0.159361E+09 |
| March | 0.305895E+09 | 0.125166E+09 | 0.180729E+09 | 0.512929E+09 | 0.142201E+09 |
| April | 0.218759E+09 | 48762672.05 | 0.169997E+09 | 0.410126E+09 | 85266258.36 |
| May | 0.171985E+09 | 4985512.72 | 0.166999E+09 | 0.356682E+09 | 33869998.12 |
| June | 0.157580E+09 | 438652.82 | 0.157142E+09 | 0.356310E+09 | 11673721.89 |
| July | 0.174576E+09 | 1932094.98 | 0.172644E+09 | 0.410067E+09 | 18873470.18 |
| August | 0.196815E+09 | 15792809.78 | 0.181022E+09 | 0.436870E+09 | 12197308.69 |
| September | 0.247423E+09 | 62495235.59 | 0.184928E+09 | 0.544597E+09 | 27458168.86 |
| October | 0.348736E+09 | 0.163993E+09 | 0.184743E+09 | 0.672906E+09 | 48766807.86 |
| November | 0.385200E+09 | 0.215831E+09 | 0.169369E+09 | 0.665451E+09 | 0.101137E+09 |
| December | 0.433407E+09 | 0.272909E+09 | 0.160498E+09 | 0.693803E+09 | 0.186738E+09 |
| Annual Sum or Average | 0.345677E+10 | 0.141544E+10 | 0.204133E+10 | 0.636871E+10 | 0.104330E+10 |
| Minimum of Months | 0.157580E+09 | 438652.82 | 0.155271E+09 | 0.356310E+09 | 11673721.89 |
| Maximum of Months | 0.447539E+09 | 0.289548E+09 | 0.184928E+09 | 0.698992E+09 | 0.215756E+09 |
Report: WindowEnergyReportMonthly
For: MWINDOW1 S SWA
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.447539E+09 | 0.289548E+09 | 0.157992E+09 | 0.698299E+09 | 0.209315E+09 |
| February | 0.368860E+09 | 0.213589E+09 | 0.155271E+09 | 0.607974E+09 | 0.155259E+09 |
| March | 0.305895E+09 | 0.125166E+09 | 0.180729E+09 | 0.509274E+09 | 0.140322E+09 |
| April | 0.218759E+09 | 48762672.05 | 0.169997E+09 | 0.406424E+09 | 84886750.25 |
| May | 0.171985E+09 | 4985512.72 | 0.166999E+09 | 0.354659E+09 | 32308535.63 |
| June | 0.157580E+09 | 438652.82 | 0.157142E+09 | 0.356487E+09 | 10307756.13 |
| July | 0.174576E+09 | 1932094.98 | 0.172644E+09 | 0.411056E+09 | 16656569.23 |
| August | 0.196815E+09 | 15792809.78 | 0.181022E+09 | 0.439806E+09 | 10124116.24 |
| September | 0.247423E+09 | 62495235.59 | 0.184928E+09 | 0.547157E+09 | 24231169.35 |
| October | 0.348736E+09 | 0.163993E+09 | 0.184743E+09 | 0.673955E+09 | 42967171.09 |
| November | 0.385200E+09 | 0.215831E+09 | 0.169369E+09 | 0.665644E+09 | 94900417.86 |
| December | 0.433407E+09 | 0.272909E+09 | 0.160498E+09 | 0.692933E+09 | 0.179716E+09 |
| Annual Sum or Average | 0.345677E+10 | 0.141544E+10 | 0.204133E+10 | 0.636367E+10 | 0.100099E+10 |
| Minimum of Months | 0.157580E+09 | 438652.82 | 0.155271E+09 | 0.354659E+09 | 10124116.24 |
| Maximum of Months | 0.447539E+09 | 0.289548E+09 | 0.184928E+09 | 0.698299E+09 | 0.209315E+09 |
Report: WindowEnergyReportMonthly
For: MWINDOW1 W SWA
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.137216E+09 | 59462026.64 | 77754226.73 | 0.190153E+09 | 0.149369E+09 |
| February | 0.154698E+09 | 70244097.88 | 84453894.02 | 0.241138E+09 | 0.109317E+09 |
| March | 0.213188E+09 | 97527639.98 | 0.115660E+09 | 0.336283E+09 | 97162875.98 |
| April | 0.225961E+09 | 0.104374E+09 | 0.121587E+09 | 0.392953E+09 | 55423730.33 |
| May | 0.213812E+09 | 82544160.59 | 0.131268E+09 | 0.410189E+09 | 22250843.03 |
| June | 0.175217E+09 | 49233297.07 | 0.125984E+09 | 0.363696E+09 | 6865779.24 |
| July | 0.202190E+09 | 62668635.49 | 0.139522E+09 | 0.428329E+09 | 10545685.34 |
| August | 0.201575E+09 | 65580447.78 | 0.135994E+09 | 0.408346E+09 | 6495849.71 |
| September | 0.166336E+09 | 49094784.96 | 0.117241E+09 | 0.349018E+09 | 15498407.79 |
| October | 0.170925E+09 | 66648864.77 | 0.104276E+09 | 0.324508E+09 | 28664272.48 |
| November | 0.136319E+09 | 49872369.86 | 86446752.73 | 0.231758E+09 | 66913065.21 |
| December | 0.141581E+09 | 63440405.52 | 78140754.64 | 0.210682E+09 | 0.124741E+09 |
| Annual Sum or Average | 0.213902E+10 | 0.820691E+09 | 0.131833E+10 | 0.388705E+10 | 0.693248E+09 |
| Minimum of Months | 0.136319E+09 | 49094784.96 | 77754226.73 | 0.190153E+09 | 6495849.71 |
| Maximum of Months | 0.225961E+09 | 0.104374E+09 | 0.139522E+09 | 0.428329E+09 | 0.149369E+09 |
Report: WindowEnergyReportMonthly
For: MWINDOW1 W NWA
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.137216E+09 | 59462026.64 | 77754226.73 | 0.196227E+09 | 0.143129E+09 |
| February | 0.154698E+09 | 70244097.88 | 84453894.02 | 0.246248E+09 | 0.104701E+09 |
| March | 0.213188E+09 | 97527639.98 | 0.115660E+09 | 0.340049E+09 | 94139980.18 |
| April | 0.225961E+09 | 0.104374E+09 | 0.121587E+09 | 0.394491E+09 | 54685888.28 |
| May | 0.213812E+09 | 82544160.59 | 0.131268E+09 | 0.410165E+09 | 22318179.61 |
| June | 0.175217E+09 | 49233297.07 | 0.125984E+09 | 0.363017E+09 | 6956146.52 |
| July | 0.202190E+09 | 62668635.49 | 0.139522E+09 | 0.427946E+09 | 10620049.17 |
| August | 0.201575E+09 | 65580447.78 | 0.135994E+09 | 0.409042E+09 | 6411731.03 |
| September | 0.166336E+09 | 49094784.96 | 0.117241E+09 | 0.351371E+09 | 15163678.80 |
| October | 0.170925E+09 | 66648864.77 | 0.104276E+09 | 0.328227E+09 | 27007265.57 |
| November | 0.136319E+09 | 49872369.86 | 86446752.73 | 0.236143E+09 | 64028345.45 |
| December | 0.141581E+09 | 63440405.52 | 78140754.64 | 0.216073E+09 | 0.118652E+09 |
| Annual Sum or Average | 0.213902E+10 | 0.820691E+09 | 0.131833E+10 | 0.391900E+10 | 0.667813E+09 |
| Minimum of Months | 0.136319E+09 | 49094784.96 | 77754226.73 | 0.196227E+09 | 6411731.03 |
| Maximum of Months | 0.225961E+09 | 0.104374E+09 | 0.139522E+09 | 0.427946E+09 | 0.143129E+09 |
Report: WindowEnergyReportMonthly
For: MWINDOW1 N NWA
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 95922893.25 | 0.00 | 95922893.25 | 99601369.30 | 0.223836E+09 |
| February | 0.102552E+09 | 0.00 | 0.102552E+09 | 0.136543E+09 | 0.161696E+09 |
| March | 0.135455E+09 | 8987.58 | 0.135446E+09 | 0.182435E+09 | 0.145798E+09 |
| April | 0.147170E+09 | 822185.82 | 0.146348E+09 | 0.247476E+09 | 82435670.35 |
| May | 0.172610E+09 | 6939233.84 | 0.165670E+09 | 0.352845E+09 | 33252102.97 |
| June | 0.178820E+09 | 12506596.35 | 0.166314E+09 | 0.400775E+09 | 9925919.72 |
| July | 0.186873E+09 | 8688044.55 | 0.178185E+09 | 0.436387E+09 | 16291201.64 |
| August | 0.166270E+09 | 1873332.33 | 0.164397E+09 | 0.370515E+09 | 9595960.07 |
| September | 0.142367E+09 | 28547.29 | 0.142339E+09 | 0.333267E+09 | 23081975.56 |
| October | 0.123193E+09 | 0.00 | 0.123193E+09 | 0.251106E+09 | 40520442.90 |
| November | 0.103661E+09 | 0.00 | 0.103661E+09 | 0.169283E+09 | 97591566.02 |
| December | 94879756.67 | 0.00 | 94879756.67 | 0.113387E+09 | 0.185750E+09 |
| Annual Sum or Average | 0.164977E+10 | 30866927.75 | 0.161891E+10 | 0.309362E+10 | 0.102977E+10 |
| Minimum of Months | 94879756.67 | 0.00 | 94879756.67 | 99601369.30 | 9595960.07 |
| Maximum of Months | 0.186873E+09 | 12506596.35 | 0.178185E+09 | 0.436387E+09 | 0.223836E+09 |
Report: WindowEnergyReportMonthly
For: MWINDOW1 S SEA
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.447539E+09 | 0.289548E+09 | 0.157992E+09 | 0.696996E+09 | 0.208847E+09 |
| February | 0.368860E+09 | 0.213589E+09 | 0.155271E+09 | 0.606927E+09 | 0.154568E+09 |
| March | 0.305895E+09 | 0.125166E+09 | 0.180729E+09 | 0.507770E+09 | 0.139304E+09 |
| April | 0.218759E+09 | 48762672.05 | 0.169997E+09 | 0.405413E+09 | 83665251.57 |
| May | 0.171985E+09 | 4985512.72 | 0.166999E+09 | 0.354057E+09 | 31645437.77 |
| June | 0.157580E+09 | 438652.82 | 0.157142E+09 | 0.355535E+09 | 10324626.80 |
| July | 0.174576E+09 | 1932094.98 | 0.172644E+09 | 0.410350E+09 | 16477396.61 |
| August | 0.196815E+09 | 15792809.78 | 0.181022E+09 | 0.439721E+09 | 9939592.93 |
| September | 0.247423E+09 | 62495235.59 | 0.184928E+09 | 0.546485E+09 | 24173142.03 |
| October | 0.348736E+09 | 0.163993E+09 | 0.184743E+09 | 0.673282E+09 | 42471858.58 |
| November | 0.385200E+09 | 0.215831E+09 | 0.169369E+09 | 0.664938E+09 | 94436804.09 |
| December | 0.433407E+09 | 0.272909E+09 | 0.160498E+09 | 0.692641E+09 | 0.178742E+09 |
| Annual Sum or Average | 0.345677E+10 | 0.141544E+10 | 0.204133E+10 | 0.635411E+10 | 0.994595E+09 |
| Minimum of Months | 0.157580E+09 | 438652.82 | 0.155271E+09 | 0.354057E+09 | 9939592.93 |
| Maximum of Months | 0.447539E+09 | 0.289548E+09 | 0.184928E+09 | 0.696996E+09 | 0.208847E+09 |
Report: WindowEnergyReportMonthly
For: MWINDOW1 E SEA
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.152373E+09 | 73214687.62 | 79157903.76 | 0.210391E+09 | 0.140503E+09 |
| February | 0.158810E+09 | 73517497.32 | 85292300.99 | 0.238803E+09 | 0.101405E+09 |
| March | 0.214432E+09 | 0.101192E+09 | 0.113241E+09 | 0.327018E+09 | 88379081.57 |
| April | 0.226316E+09 | 0.101302E+09 | 0.125013E+09 | 0.389561E+09 | 53025504.03 |
| May | 0.220522E+09 | 88072297.16 | 0.132449E+09 | 0.418797E+09 | 19999662.11 |
| June | 0.210113E+09 | 80722048.01 | 0.129391E+09 | 0.425328E+09 | 6212600.09 |
| July | 0.223483E+09 | 80852891.11 | 0.142630E+09 | 0.466212E+09 | 10704218.19 |
| August | 0.203875E+09 | 68111557.53 | 0.135764E+09 | 0.413590E+09 | 6189091.12 |
| September | 0.190174E+09 | 68618181.15 | 0.121556E+09 | 0.391597E+09 | 15463534.73 |
| October | 0.181073E+09 | 77895027.35 | 0.103178E+09 | 0.341017E+09 | 26881591.53 |
| November | 0.142321E+09 | 56755460.23 | 85565885.21 | 0.236812E+09 | 61324312.49 |
| December | 0.118964E+09 | 42102991.35 | 76860568.64 | 0.167673E+09 | 0.120548E+09 |
| Annual Sum or Average | 0.224246E+10 | 0.912357E+09 | 0.133010E+10 | 0.402680E+10 | 0.650636E+09 |
| Minimum of Months | 0.118964E+09 | 42102991.35 | 76860568.64 | 0.167673E+09 | 6189091.12 |
| Maximum of Months | 0.226316E+09 | 0.101302E+09 | 0.142630E+09 | 0.466212E+09 | 0.140503E+09 |
Report: WindowEnergyReportMonthly
For: MWINDOW1 E NEA
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.152373E+09 | 73214687.62 | 79157903.76 | 0.216208E+09 | 0.134570E+09 |
| February | 0.158810E+09 | 73517497.32 | 85292300.99 | 0.244042E+09 | 96818567.75 |
| March | 0.214432E+09 | 0.101192E+09 | 0.113241E+09 | 0.330837E+09 | 85604529.07 |
| April | 0.226316E+09 | 0.101302E+09 | 0.125013E+09 | 0.391133E+09 | 52230309.13 |
| May | 0.220522E+09 | 88072297.16 | 0.132449E+09 | 0.418756E+09 | 20048424.36 |
| June | 0.210113E+09 | 80722048.01 | 0.129391E+09 | 0.424620E+09 | 6283783.40 |
| July | 0.223483E+09 | 80852891.11 | 0.142630E+09 | 0.465818E+09 | 10770101.84 |
| August | 0.203875E+09 | 68111557.53 | 0.135764E+09 | 0.414322E+09 | 6112485.70 |
| September | 0.190174E+09 | 68618181.15 | 0.121556E+09 | 0.394040E+09 | 15149374.71 |
| October | 0.181073E+09 | 77895027.35 | 0.103178E+09 | 0.344946E+09 | 25323858.04 |
| November | 0.142321E+09 | 56755460.23 | 85565885.21 | 0.241394E+09 | 58635620.02 |
| December | 0.118964E+09 | 42102991.35 | 76860568.64 | 0.173027E+09 | 0.114294E+09 |
| Annual Sum or Average | 0.224246E+10 | 0.912357E+09 | 0.133010E+10 | 0.405914E+10 | 0.625841E+09 |
| Minimum of Months | 0.118964E+09 | 42102991.35 | 76860568.64 | 0.173027E+09 | 6112485.70 |
| Maximum of Months | 0.226316E+09 | 0.101302E+09 | 0.142630E+09 | 0.465818E+09 | 0.134570E+09 |
Report: WindowEnergyReportMonthly
For: MWINDOW1 N NEA
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 95922893.25 | 0.00 | 95922893.25 | 97953041.24 | 0.223893E+09 |
| February | 0.102552E+09 | 0.00 | 0.102552E+09 | 0.135377E+09 | 0.161067E+09 |
| March | 0.135455E+09 | 8987.58 | 0.135446E+09 | 0.180923E+09 | 0.145317E+09 |
| April | 0.147170E+09 | 822185.82 | 0.146348E+09 | 0.246498E+09 | 81248051.46 |
| May | 0.172610E+09 | 6939233.84 | 0.165670E+09 | 0.352178E+09 | 32532964.23 |
| June | 0.178820E+09 | 12506596.35 | 0.166314E+09 | 0.399841E+09 | 9922372.45 |
| July | 0.186873E+09 | 8688044.55 | 0.178185E+09 | 0.435668E+09 | 16108089.51 |
| August | 0.166270E+09 | 1873332.33 | 0.164397E+09 | 0.370453E+09 | 9425589.44 |
| September | 0.142367E+09 | 28547.29 | 0.142339E+09 | 0.332561E+09 | 23024823.98 |
| October | 0.123193E+09 | 0.00 | 0.123193E+09 | 0.250385E+09 | 40027447.43 |
| November | 0.103661E+09 | 0.00 | 0.103661E+09 | 0.168500E+09 | 97266669.82 |
| December | 94879756.67 | 0.00 | 94879756.67 | 0.112930E+09 | 0.184543E+09 |
| Annual Sum or Average | 0.164977E+10 | 30866927.75 | 0.161891E+10 | 0.308327E+10 | 0.102438E+10 |
| Minimum of Months | 94879756.67 | 0.00 | 94879756.67 | 97953041.24 | 9425589.44 |
| Maximum of Months | 0.186873E+09 | 12506596.35 | 0.178185E+09 | 0.435668E+09 | 0.223893E+09 |
Report: WindowEnergyReportMonthly
For: MWINDOW1 N N1A
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 95922893.25 | 0.00 | 95922893.25 | 99070215.23 | 0.227910E+09 |
| February | 0.102552E+09 | 0.00 | 0.102552E+09 | 0.137039E+09 | 0.163987E+09 |
| March | 0.135455E+09 | 8987.58 | 0.135446E+09 | 0.184103E+09 | 0.146388E+09 |
| April | 0.147170E+09 | 822185.82 | 0.146348E+09 | 0.251178E+09 | 80228078.95 |
| May | 0.172610E+09 | 6939233.84 | 0.165670E+09 | 0.357674E+09 | 31185231.90 |
| June | 0.178820E+09 | 12506596.35 | 0.166314E+09 | 0.406610E+09 | 9239761.82 |
| July | 0.186873E+09 | 8688044.55 | 0.178185E+09 | 0.442754E+09 | 15115209.00 |
| August | 0.166270E+09 | 1873332.33 | 0.164397E+09 | 0.377007E+09 | 8810292.16 |
| September | 0.142367E+09 | 28547.29 | 0.142339E+09 | 0.338757E+09 | 22271347.62 |
| October | 0.123193E+09 | 0.00 | 0.123193E+09 | 0.255056E+09 | 38883249.53 |
| November | 0.103661E+09 | 0.00 | 0.103661E+09 | 0.171048E+09 | 97846205.63 |
| December | 94879756.67 | 0.00 | 94879756.67 | 0.113336E+09 | 0.189405E+09 |
| Annual Sum or Average | 0.164977E+10 | 30866927.75 | 0.161891E+10 | 0.313363E+10 | 0.103127E+10 |
| Minimum of Months | 94879756.67 | 0.00 | 94879756.67 | 99070215.23 | 8810292.16 |
| Maximum of Months | 0.186873E+09 | 12506596.35 | 0.178185E+09 | 0.442754E+09 | 0.227910E+09 |
Report: WindowEnergyReportMonthly
For: MWINDOW1 N N2A
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 95922893.25 | 0.00 | 95922893.25 | 98995186.13 | 0.227946E+09 |
| February | 0.102552E+09 | 0.00 | 0.102552E+09 | 0.136986E+09 | 0.163978E+09 |
| March | 0.135455E+09 | 8987.58 | 0.135446E+09 | 0.184018E+09 | 0.146401E+09 |
| April | 0.147170E+09 | 822185.82 | 0.146348E+09 | 0.251145E+09 | 80190121.93 |
| May | 0.172610E+09 | 6939233.84 | 0.165670E+09 | 0.357652E+09 | 31162730.49 |
| June | 0.178820E+09 | 12506596.35 | 0.166314E+09 | 0.406574E+09 | 9242798.63 |
| July | 0.186873E+09 | 8688044.55 | 0.178185E+09 | 0.442727E+09 | 15111366.58 |
| August | 0.166270E+09 | 1873332.33 | 0.164397E+09 | 0.377003E+09 | 8805036.77 |
| September | 0.142367E+09 | 28547.29 | 0.142339E+09 | 0.338729E+09 | 22272432.00 |
| October | 0.123193E+09 | 0.00 | 0.123193E+09 | 0.255030E+09 | 38869291.32 |
| November | 0.103661E+09 | 0.00 | 0.103661E+09 | 0.171015E+09 | 97840391.93 |
| December | 94879756.67 | 0.00 | 94879756.67 | 0.113320E+09 | 0.189357E+09 |
| Annual Sum or Average | 0.164977E+10 | 30866927.75 | 0.161891E+10 | 0.313319E+10 | 0.103118E+10 |
| Minimum of Months | 94879756.67 | 0.00 | 94879756.67 | 98995186.13 | 8805036.77 |
| Maximum of Months | 0.186873E+09 | 12506596.35 | 0.178185E+09 | 0.442727E+09 | 0.227946E+09 |
Report: WindowEnergyReportMonthly
For: MWINDOW1 S S1A
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.447539E+09 | 0.289548E+09 | 0.157992E+09 | 0.697827E+09 | 0.211544E+09 |
| February | 0.368860E+09 | 0.213589E+09 | 0.155271E+09 | 0.608297E+09 | 0.156613E+09 |
| March | 0.305895E+09 | 0.125166E+09 | 0.180729E+09 | 0.510728E+09 | 0.140357E+09 |
| April | 0.218759E+09 | 48762672.05 | 0.169997E+09 | 0.409907E+09 | 82686240.87 |
| May | 0.171985E+09 | 4985512.72 | 0.166999E+09 | 0.359823E+09 | 30345097.52 |
| June | 0.157580E+09 | 438652.82 | 0.157142E+09 | 0.362538E+09 | 9624240.44 |
| July | 0.174576E+09 | 1932094.98 | 0.172644E+09 | 0.417561E+09 | 15472642.13 |
| August | 0.196815E+09 | 15792809.78 | 0.181022E+09 | 0.446301E+09 | 9310816.58 |
| September | 0.247423E+09 | 62495235.59 | 0.184928E+09 | 0.552400E+09 | 23474743.44 |
| October | 0.348736E+09 | 0.163993E+09 | 0.184743E+09 | 0.677554E+09 | 41542554.79 |
| November | 0.385200E+09 | 0.215831E+09 | 0.169369E+09 | 0.667111E+09 | 94878745.83 |
| December | 0.433407E+09 | 0.272909E+09 | 0.160498E+09 | 0.693011E+09 | 0.181649E+09 |
| Annual Sum or Average | 0.345677E+10 | 0.141544E+10 | 0.204133E+10 | 0.640306E+10 | 0.997498E+09 |
| Minimum of Months | 0.157580E+09 | 438652.82 | 0.155271E+09 | 0.359823E+09 | 9310816.58 |
| Maximum of Months | 0.447539E+09 | 0.289548E+09 | 0.184928E+09 | 0.697827E+09 | 0.211544E+09 |
Report: WindowEnergyReportMonthly
For: MWINDOW1 S S2A
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.447539E+09 | 0.289548E+09 | 0.157992E+09 | 0.697788E+09 | 0.211537E+09 |
| February | 0.368860E+09 | 0.213589E+09 | 0.155271E+09 | 0.608262E+09 | 0.156597E+09 |
| March | 0.305895E+09 | 0.125166E+09 | 0.180729E+09 | 0.510674E+09 | 0.140329E+09 |
| April | 0.218759E+09 | 48762672.05 | 0.169997E+09 | 0.409874E+09 | 82648159.69 |
| May | 0.171985E+09 | 4985512.72 | 0.166999E+09 | 0.359802E+09 | 30323109.71 |
| June | 0.157580E+09 | 438652.82 | 0.157142E+09 | 0.362501E+09 | 9627739.53 |
| July | 0.174576E+09 | 1932094.98 | 0.172644E+09 | 0.417535E+09 | 15468878.74 |
| August | 0.196815E+09 | 15792809.78 | 0.181022E+09 | 0.446298E+09 | 9305425.37 |
| September | 0.247423E+09 | 62495235.59 | 0.184928E+09 | 0.552375E+09 | 23475627.39 |
| October | 0.348736E+09 | 0.163993E+09 | 0.184743E+09 | 0.677532E+09 | 41529149.29 |
| November | 0.385200E+09 | 0.215831E+09 | 0.169369E+09 | 0.667089E+09 | 94866716.82 |
| December | 0.433407E+09 | 0.272909E+09 | 0.160498E+09 | 0.693004E+09 | 0.181612E+09 |
| Annual Sum or Average | 0.345677E+10 | 0.141544E+10 | 0.204133E+10 | 0.640273E+10 | 0.997320E+09 |
| Minimum of Months | 0.157580E+09 | 438652.82 | 0.155271E+09 | 0.359802E+09 | 9305425.37 |
| Maximum of Months | 0.447539E+09 | 0.289548E+09 | 0.184928E+09 | 0.697788E+09 | 0.211537E+09 |
Report: WindowEnergyReportMonthly
For: TWINDOW1 S SWA
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.447539E+09 | 0.289548E+09 | 0.157992E+09 | 0.698877E+09 | 0.190411E+09 |
| February | 0.368860E+09 | 0.213589E+09 | 0.155271E+09 | 0.604206E+09 | 0.143055E+09 |
| March | 0.305895E+09 | 0.125166E+09 | 0.180729E+09 | 0.503753E+09 | 0.129812E+09 |
| April | 0.218759E+09 | 48762672.05 | 0.169997E+09 | 0.395981E+09 | 82115255.90 |
| May | 0.171985E+09 | 4985512.72 | 0.166999E+09 | 0.341988E+09 | 31675555.12 |
| June | 0.157580E+09 | 438652.82 | 0.157142E+09 | 0.343127E+09 | 9977856.02 |
| July | 0.174576E+09 | 1932094.98 | 0.172644E+09 | 0.396325E+09 | 16185773.73 |
| August | 0.196815E+09 | 15792809.78 | 0.181022E+09 | 0.426413E+09 | 9975509.13 |
| September | 0.247423E+09 | 62495235.59 | 0.184928E+09 | 0.533346E+09 | 23226916.94 |
| October | 0.348736E+09 | 0.163993E+09 | 0.184743E+09 | 0.662052E+09 | 41216681.79 |
| November | 0.385200E+09 | 0.215831E+09 | 0.169369E+09 | 0.658497E+09 | 88250840.84 |
| December | 0.433407E+09 | 0.272909E+09 | 0.160498E+09 | 0.690389E+09 | 0.163976E+09 |
| Annual Sum or Average | 0.345677E+10 | 0.141544E+10 | 0.204133E+10 | 0.625495E+10 | 0.929878E+09 |
| Minimum of Months | 0.157580E+09 | 438652.82 | 0.155271E+09 | 0.341988E+09 | 9975509.13 |
| Maximum of Months | 0.447539E+09 | 0.289548E+09 | 0.184928E+09 | 0.698877E+09 | 0.190411E+09 |
Report: WindowEnergyReportMonthly
For: TWINDOW1 W SWA
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.137216E+09 | 59462026.64 | 77754226.73 | 0.187801E+09 | 0.133653E+09 |
| February | 0.154698E+09 | 70244097.88 | 84453894.02 | 0.237451E+09 | 99517723.81 |
| March | 0.213188E+09 | 97527639.98 | 0.115660E+09 | 0.331276E+09 | 88476695.89 |
| April | 0.225961E+09 | 0.104374E+09 | 0.121587E+09 | 0.385782E+09 | 53182744.58 |
| May | 0.213812E+09 | 82544160.59 | 0.131268E+09 | 0.401709E+09 | 21851875.12 |
| June | 0.175217E+09 | 49233297.07 | 0.125984E+09 | 0.354717E+09 | 6639540.77 |
| July | 0.202190E+09 | 62668635.49 | 0.139522E+09 | 0.418348E+09 | 10165914.10 |
| August | 0.201575E+09 | 65580447.78 | 0.135994E+09 | 0.399436E+09 | 6348054.21 |
| September | 0.166336E+09 | 49094784.96 | 0.117241E+09 | 0.339984E+09 | 14735022.52 |
| October | 0.170925E+09 | 66648864.77 | 0.104276E+09 | 0.316923E+09 | 27361274.41 |
| November | 0.136319E+09 | 49872369.86 | 86446752.73 | 0.226686E+09 | 61605097.50 |
| December | 0.141581E+09 | 63440405.52 | 78140754.64 | 0.207688E+09 | 0.112493E+09 |
| Annual Sum or Average | 0.213902E+10 | 0.820691E+09 | 0.131833E+10 | 0.380780E+10 | 0.636030E+09 |
| Minimum of Months | 0.136319E+09 | 49094784.96 | 77754226.73 | 0.187801E+09 | 6348054.21 |
| Maximum of Months | 0.225961E+09 | 0.104374E+09 | 0.139522E+09 | 0.418348E+09 | 0.133653E+09 |
Report: WindowEnergyReportMonthly
For: TWINDOW1 W NWA
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.137216E+09 | 59462026.64 | 77754226.73 | 0.198715E+09 | 0.126167E+09 |
| February | 0.154698E+09 | 70244097.88 | 84453894.02 | 0.245326E+09 | 95039602.87 |
| March | 0.213188E+09 | 97527639.98 | 0.115660E+09 | 0.337223E+09 | 85530285.76 |
| April | 0.225961E+09 | 0.104374E+09 | 0.121587E+09 | 0.388038E+09 | 52587308.51 |
| May | 0.213812E+09 | 82544160.59 | 0.131268E+09 | 0.401638E+09 | 21972701.02 |
| June | 0.175217E+09 | 49233297.07 | 0.125984E+09 | 0.353796E+09 | 6710525.82 |
| July | 0.202190E+09 | 62668635.49 | 0.139522E+09 | 0.417819E+09 | 10241036.53 |
| August | 0.201575E+09 | 65580447.78 | 0.135994E+09 | 0.400332E+09 | 6291008.31 |
| September | 0.166336E+09 | 49094784.96 | 0.117241E+09 | 0.343069E+09 | 14518376.35 |
| October | 0.170925E+09 | 66648864.77 | 0.104276E+09 | 0.322125E+09 | 26018316.94 |
| November | 0.136319E+09 | 49872369.86 | 86446752.73 | 0.233424E+09 | 58768941.71 |
| December | 0.141581E+09 | 63440405.52 | 78140754.64 | 0.217008E+09 | 0.105282E+09 |
| Annual Sum or Average | 0.213902E+10 | 0.820691E+09 | 0.131833E+10 | 0.385851E+10 | 0.609127E+09 |
| Minimum of Months | 0.136319E+09 | 49094784.96 | 77754226.73 | 0.198715E+09 | 6291008.31 |
| Maximum of Months | 0.225961E+09 | 0.104374E+09 | 0.139522E+09 | 0.417819E+09 | 0.126167E+09 |
Report: WindowEnergyReportMonthly
For: TWINDOW1 N NWA
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 95922893.25 | 0.00 | 95922893.25 | 0.103627E+09 | 0.198029E+09 |
| February | 0.102552E+09 | 0.00 | 0.102552E+09 | 0.135799E+09 | 0.147341E+09 |
| March | 0.135455E+09 | 8987.58 | 0.135446E+09 | 0.179237E+09 | 0.133297E+09 |
| April | 0.147170E+09 | 822185.82 | 0.146348E+09 | 0.238636E+09 | 79833313.37 |
| May | 0.172610E+09 | 6939233.84 | 0.165670E+09 | 0.340777E+09 | 32986497.23 |
| June | 0.178820E+09 | 12506596.35 | 0.166314E+09 | 0.387214E+09 | 9640063.10 |
| July | 0.186873E+09 | 8688044.55 | 0.178185E+09 | 0.421673E+09 | 15829044.01 |
| August | 0.166270E+09 | 1873332.33 | 0.164397E+09 | 0.357861E+09 | 9428983.24 |
| September | 0.142367E+09 | 28547.29 | 0.142339E+09 | 0.321150E+09 | 22197495.44 |
| October | 0.123193E+09 | 0.00 | 0.123193E+09 | 0.242370E+09 | 39110745.56 |
| November | 0.103661E+09 | 0.00 | 0.103661E+09 | 0.165619E+09 | 89734403.38 |
| December | 94879756.67 | 0.00 | 94879756.67 | 0.115119E+09 | 0.165379E+09 |
| Annual Sum or Average | 0.164977E+10 | 30866927.75 | 0.161891E+10 | 0.300908E+10 | 0.942806E+09 |
| Minimum of Months | 94879756.67 | 0.00 | 94879756.67 | 0.103627E+09 | 9428983.24 |
| Maximum of Months | 0.186873E+09 | 12506596.35 | 0.178185E+09 | 0.421673E+09 | 0.198029E+09 |
Report: WindowEnergyReportMonthly
For: TWINDOW1 S SEA
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.447539E+09 | 0.289548E+09 | 0.157992E+09 | 0.695786E+09 | 0.189150E+09 |
| February | 0.368860E+09 | 0.213589E+09 | 0.155271E+09 | 0.602036E+09 | 0.141513E+09 |
| March | 0.305895E+09 | 0.125166E+09 | 0.180729E+09 | 0.500594E+09 | 0.127736E+09 |
| April | 0.218759E+09 | 48762672.05 | 0.169997E+09 | 0.394127E+09 | 80009073.65 |
| May | 0.171985E+09 | 4985512.72 | 0.166999E+09 | 0.340999E+09 | 30569194.43 |
| June | 0.157580E+09 | 438652.82 | 0.157142E+09 | 0.341922E+09 | 9906084.87 |
| July | 0.174576E+09 | 1932094.98 | 0.172644E+09 | 0.395376E+09 | 15861122.86 |
| August | 0.196815E+09 | 15792809.78 | 0.181022E+09 | 0.426312E+09 | 9679955.06 |
| September | 0.247423E+09 | 62495235.59 | 0.184928E+09 | 0.532438E+09 | 23046046.39 |
| October | 0.348736E+09 | 0.163993E+09 | 0.184743E+09 | 0.661001E+09 | 40350549.72 |
| November | 0.385200E+09 | 0.215831E+09 | 0.169369E+09 | 0.657174E+09 | 87380332.71 |
| December | 0.433407E+09 | 0.272909E+09 | 0.160498E+09 | 0.689329E+09 | 0.162332E+09 |
| Annual Sum or Average | 0.345677E+10 | 0.141544E+10 | 0.204133E+10 | 0.623709E+10 | 0.917534E+09 |
| Minimum of Months | 0.157580E+09 | 438652.82 | 0.155271E+09 | 0.340999E+09 | 9679955.06 |
| Maximum of Months | 0.447539E+09 | 0.289548E+09 | 0.184928E+09 | 0.695786E+09 | 0.189150E+09 |
Report: WindowEnergyReportMonthly
For: TWINDOW1 E SEA
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.152373E+09 | 73214687.62 | 79157903.76 | 0.210743E+09 | 0.128239E+09 |
| February | 0.158810E+09 | 73517497.32 | 85292300.99 | 0.236438E+09 | 93457271.92 |
| March | 0.214432E+09 | 0.101192E+09 | 0.113241E+09 | 0.323224E+09 | 81779272.27 |
| April | 0.226316E+09 | 0.101302E+09 | 0.125013E+09 | 0.381867E+09 | 50850565.70 |
| May | 0.220522E+09 | 88072297.16 | 0.132449E+09 | 0.409542E+09 | 19347432.94 |
| June | 0.210113E+09 | 80722048.01 | 0.129391E+09 | 0.415702E+09 | 5955919.26 |
| July | 0.223483E+09 | 80852891.11 | 0.142630E+09 | 0.455807E+09 | 10319591.14 |
| August | 0.203875E+09 | 68111557.53 | 0.135764E+09 | 0.404371E+09 | 5983572.54 |
| September | 0.190174E+09 | 68618181.15 | 0.121556E+09 | 0.382140E+09 | 14765558.08 |
| October | 0.181073E+09 | 77895027.35 | 0.103178E+09 | 0.332998E+09 | 25469691.74 |
| November | 0.142321E+09 | 56755460.23 | 85565885.21 | 0.232173E+09 | 56887381.86 |
| December | 0.118964E+09 | 42102991.35 | 76860568.64 | 0.166379E+09 | 0.110141E+09 |
| Annual Sum or Average | 0.224246E+10 | 0.912357E+09 | 0.133010E+10 | 0.395138E+10 | 0.603196E+09 |
| Minimum of Months | 0.118964E+09 | 42102991.35 | 76860568.64 | 0.166379E+09 | 5955919.26 |
| Maximum of Months | 0.226316E+09 | 0.101302E+09 | 0.142630E+09 | 0.455807E+09 | 0.128239E+09 |
Report: WindowEnergyReportMonthly
For: TWINDOW1 E NEA
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.152373E+09 | 73214687.62 | 79157903.76 | 0.220442E+09 | 0.119915E+09 |
| February | 0.158810E+09 | 73517497.32 | 85292300.99 | 0.244039E+09 | 88551967.36 |
| March | 0.214432E+09 | 0.101192E+09 | 0.113241E+09 | 0.329054E+09 | 78437394.62 |
| April | 0.226316E+09 | 0.101302E+09 | 0.125013E+09 | 0.384144E+09 | 50158577.20 |
| May | 0.220522E+09 | 88072297.16 | 0.132449E+09 | 0.409459E+09 | 19445824.98 |
| June | 0.210113E+09 | 80722048.01 | 0.129391E+09 | 0.414757E+09 | 6009384.74 |
| July | 0.223483E+09 | 80852891.11 | 0.142630E+09 | 0.455271E+09 | 10387188.41 |
| August | 0.203875E+09 | 68111557.53 | 0.135764E+09 | 0.405319E+09 | 5931833.46 |
| September | 0.190174E+09 | 68618181.15 | 0.121556E+09 | 0.385343E+09 | 14561904.01 |
| October | 0.181073E+09 | 77895027.35 | 0.103178E+09 | 0.338402E+09 | 24174330.54 |
| November | 0.142321E+09 | 56755460.23 | 85565885.21 | 0.238973E+09 | 54098692.19 |
| December | 0.118964E+09 | 42102991.35 | 76860568.64 | 0.174993E+09 | 0.101624E+09 |
| Annual Sum or Average | 0.224246E+10 | 0.912357E+09 | 0.133010E+10 | 0.400020E+10 | 0.573296E+09 |
| Minimum of Months | 0.118964E+09 | 42102991.35 | 76860568.64 | 0.174993E+09 | 5931833.46 |
| Maximum of Months | 0.226316E+09 | 0.101302E+09 | 0.142630E+09 | 0.455271E+09 | 0.119915E+09 |
Report: WindowEnergyReportMonthly
For: TWINDOW1 N NEA
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 95922893.25 | 0.00 | 95922893.25 | 99832277.16 | 0.196586E+09 |
| February | 0.102552E+09 | 0.00 | 0.102552E+09 | 0.133271E+09 | 0.145645E+09 |
| March | 0.135455E+09 | 8987.58 | 0.135446E+09 | 0.176196E+09 | 0.131182E+09 |
| April | 0.147170E+09 | 822185.82 | 0.146348E+09 | 0.236831E+09 | 77790860.40 |
| May | 0.172610E+09 | 6939233.84 | 0.165670E+09 | 0.339728E+09 | 31824738.04 |
| June | 0.178820E+09 | 12506596.35 | 0.166314E+09 | 0.386035E+09 | 9537465.70 |
| July | 0.186873E+09 | 8688044.55 | 0.178185E+09 | 0.420692E+09 | 15496920.95 |
| August | 0.166270E+09 | 1873332.33 | 0.164397E+09 | 0.357804E+09 | 9149667.37 |
| September | 0.142367E+09 | 28547.29 | 0.142339E+09 | 0.320194E+09 | 22020685.95 |
| October | 0.123193E+09 | 0.00 | 0.123193E+09 | 0.241198E+09 | 38205860.64 |
| November | 0.103661E+09 | 0.00 | 0.103661E+09 | 0.164068E+09 | 88923149.71 |
| December | 94879756.67 | 0.00 | 94879756.67 | 0.113778E+09 | 0.162714E+09 |
| Annual Sum or Average | 0.164977E+10 | 30866927.75 | 0.161891E+10 | 0.298963E+10 | 0.929077E+09 |
| Minimum of Months | 94879756.67 | 0.00 | 94879756.67 | 99832277.16 | 9149667.37 |
| Maximum of Months | 0.186873E+09 | 12506596.35 | 0.178185E+09 | 0.420692E+09 | 0.196586E+09 |
Report: WindowEnergyReportMonthly
For: TWINDOW1 N N1A
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 95922893.25 | 0.00 | 95922893.25 | 0.103234E+09 | 0.203529E+09 |
| February | 0.102552E+09 | 0.00 | 0.102552E+09 | 0.137307E+09 | 0.149976E+09 |
| March | 0.135455E+09 | 8987.58 | 0.135446E+09 | 0.182239E+09 | 0.133829E+09 |
| April | 0.147170E+09 | 822185.82 | 0.146348E+09 | 0.243517E+09 | 78416826.46 |
| May | 0.172610E+09 | 6939233.84 | 0.165670E+09 | 0.347097E+09 | 31337654.90 |
| June | 0.178820E+09 | 12506596.35 | 0.166314E+09 | 0.394427E+09 | 9218730.46 |
| July | 0.186873E+09 | 8688044.55 | 0.178185E+09 | 0.429655E+09 | 15039870.70 |
| August | 0.166270E+09 | 1873332.33 | 0.164397E+09 | 0.365776E+09 | 8898295.79 |
| September | 0.142367E+09 | 28547.29 | 0.142339E+09 | 0.328073E+09 | 21809363.21 |
| October | 0.123193E+09 | 0.00 | 0.123193E+09 | 0.247571E+09 | 37935907.11 |
| November | 0.103661E+09 | 0.00 | 0.103661E+09 | 0.168154E+09 | 90991032.26 |
| December | 94879756.67 | 0.00 | 94879756.67 | 0.115827E+09 | 0.168901E+09 |
| Annual Sum or Average | 0.164977E+10 | 30866927.75 | 0.161891E+10 | 0.306288E+10 | 0.949883E+09 |
| Minimum of Months | 94879756.67 | 0.00 | 94879756.67 | 0.103234E+09 | 8898295.79 |
| Maximum of Months | 0.186873E+09 | 12506596.35 | 0.178185E+09 | 0.429655E+09 | 0.203529E+09 |
Report: WindowEnergyReportMonthly
For: TWINDOW1 N N2A
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 95922893.25 | 0.00 | 95922893.25 | 0.102976E+09 | 0.203471E+09 |
| February | 0.102552E+09 | 0.00 | 0.102552E+09 | 0.137133E+09 | 0.149866E+09 |
| March | 0.135455E+09 | 8987.58 | 0.135446E+09 | 0.182001E+09 | 0.133707E+09 |
| April | 0.147170E+09 | 822185.82 | 0.146348E+09 | 0.243421E+09 | 78306946.04 |
| May | 0.172610E+09 | 6939233.84 | 0.165670E+09 | 0.347042E+09 | 31277196.89 |
| June | 0.178820E+09 | 12506596.35 | 0.166314E+09 | 0.394375E+09 | 9214142.60 |
| July | 0.186873E+09 | 8688044.55 | 0.178185E+09 | 0.429612E+09 | 15023057.38 |
| August | 0.166270E+09 | 1873332.33 | 0.164397E+09 | 0.365771E+09 | 8883428.38 |
| September | 0.142367E+09 | 28547.29 | 0.142339E+09 | 0.328029E+09 | 21800637.59 |
| October | 0.123193E+09 | 0.00 | 0.123193E+09 | 0.247513E+09 | 37889356.38 |
| November | 0.103661E+09 | 0.00 | 0.103661E+09 | 0.168054E+09 | 90952472.87 |
| December | 94879756.67 | 0.00 | 94879756.67 | 0.115738E+09 | 0.168712E+09 |
| Annual Sum or Average | 0.164977E+10 | 30866927.75 | 0.161891E+10 | 0.306167E+10 | 0.949103E+09 |
| Minimum of Months | 94879756.67 | 0.00 | 94879756.67 | 0.102976E+09 | 8883428.38 |
| Maximum of Months | 0.186873E+09 | 12506596.35 | 0.178185E+09 | 0.429612E+09 | 0.203471E+09 |
Report: WindowEnergyReportMonthly
For: TWINDOW1 S S1A
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.447539E+09 | 0.289548E+09 | 0.157992E+09 | 0.697274E+09 | 0.196376E+09 |
| February | 0.368860E+09 | 0.213589E+09 | 0.155271E+09 | 0.604726E+09 | 0.146256E+09 |
| March | 0.305895E+09 | 0.125166E+09 | 0.180729E+09 | 0.505869E+09 | 0.131179E+09 |
| April | 0.218759E+09 | 48762672.05 | 0.169997E+09 | 0.400586E+09 | 80662366.72 |
| May | 0.171985E+09 | 4985512.72 | 0.166999E+09 | 0.348733E+09 | 30123272.29 |
| June | 0.157580E+09 | 438652.82 | 0.157142E+09 | 0.350634E+09 | 9579540.40 |
| July | 0.174576E+09 | 1932094.98 | 0.172644E+09 | 0.404517E+09 | 15409047.43 |
| August | 0.196815E+09 | 15792809.78 | 0.181022E+09 | 0.434382E+09 | 9417588.09 |
| September | 0.247423E+09 | 62495235.59 | 0.184928E+09 | 0.539978E+09 | 22866830.62 |
| October | 0.348736E+09 | 0.163993E+09 | 0.184743E+09 | 0.666811E+09 | 40247957.52 |
| November | 0.385200E+09 | 0.215831E+09 | 0.169369E+09 | 0.660340E+09 | 89560757.42 |
| December | 0.433407E+09 | 0.272909E+09 | 0.160498E+09 | 0.690269E+09 | 0.168476E+09 |
| Annual Sum or Average | 0.345677E+10 | 0.141544E+10 | 0.204133E+10 | 0.630412E+10 | 0.940155E+09 |
| Minimum of Months | 0.157580E+09 | 438652.82 | 0.155271E+09 | 0.348733E+09 | 9417588.09 |
| Maximum of Months | 0.447539E+09 | 0.289548E+09 | 0.184928E+09 | 0.697274E+09 | 0.196376E+09 |
Report: WindowEnergyReportMonthly
For: TWINDOW1 S S2A
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.447539E+09 | 0.289548E+09 | 0.157992E+09 | 0.697122E+09 | 0.196305E+09 |
| February | 0.368860E+09 | 0.213589E+09 | 0.155271E+09 | 0.604612E+09 | 0.146166E+09 |
| March | 0.305895E+09 | 0.125166E+09 | 0.180729E+09 | 0.505673E+09 | 0.131072E+09 |
| April | 0.218759E+09 | 48762672.05 | 0.169997E+09 | 0.400491E+09 | 80552346.69 |
| May | 0.171985E+09 | 4985512.72 | 0.166999E+09 | 0.348683E+09 | 30066243.27 |
| June | 0.157580E+09 | 438652.82 | 0.157142E+09 | 0.350580E+09 | 9575636.54 |
| July | 0.174576E+09 | 1932094.98 | 0.172644E+09 | 0.404473E+09 | 15391915.13 |
| August | 0.196815E+09 | 15792809.78 | 0.181022E+09 | 0.434375E+09 | 9401896.32 |
| September | 0.247423E+09 | 62495235.59 | 0.184928E+09 | 0.539938E+09 | 22858084.87 |
| October | 0.348736E+09 | 0.163993E+09 | 0.184743E+09 | 0.666763E+09 | 40205496.31 |
| November | 0.385200E+09 | 0.215831E+09 | 0.169369E+09 | 0.660272E+09 | 89519068.22 |
| December | 0.433407E+09 | 0.272909E+09 | 0.160498E+09 | 0.690206E+09 | 0.168379E+09 |
| Annual Sum or Average | 0.345677E+10 | 0.141544E+10 | 0.204133E+10 | 0.630319E+10 | 0.939492E+09 |
| Minimum of Months | 0.157580E+09 | 438652.82 | 0.155271E+09 | 0.348683E+09 | 9401896.32 |
| Maximum of Months | 0.447539E+09 | 0.289548E+09 | 0.184928E+09 | 0.697122E+09 | 0.196305E+09 |
Report: WindowEnergyReportMonthly
For: TWINDOW14
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 36562423.52 | 17568162.31 | 18994261.21 | 49555269.00 | 35778971.23 |
| February | 38107057.52 | 17640822.73 | 20466234.79 | 54854647.83 | 26933233.70 |
| March | 51453936.11 | 24281312.48 | 27172623.64 | 74427284.05 | 24487404.44 |
| April | 54305359.94 | 24307919.67 | 29997440.27 | 87219194.77 | 16953247.54 |
| May | 52915052.50 | 21133306.19 | 31781746.30 | 92190673.53 | 8871048.25 |
| June | 50417375.43 | 19369583.99 | 31047791.44 | 91667758.58 | 3690681.22 |
| July | 53625545.36 | 19400980.32 | 34224565.03 | 0.102008E+09 | 5629276.68 |
| August | 48920698.37 | 16343645.47 | 32577052.90 | 89367938.12 | 4229597.34 |
| September | 45633079.38 | 16465211.87 | 29167867.51 | 84767104.33 | 6153556.19 |
| October | 43449306.57 | 18691228.88 | 24758077.70 | 75627049.55 | 10541668.23 |
| November | 34150586.14 | 13618703.70 | 20531882.44 | 52858901.49 | 18199285.06 |
| December | 28545790.45 | 10102784.15 | 18443006.30 | 38505192.55 | 31595082.78 |
| Annual Sum or Average | 0.538086E+09 | 0.218924E+09 | 0.319163E+09 | 0.893049E+09 | 0.193063E+09 |
| Minimum of Months | 28545790.45 | 10102784.15 | 18443006.30 | 38505192.55 | 3690681.22 |
| Maximum of Months | 54305359.94 | 24307919.67 | 34224565.03 | 0.102008E+09 | 35778971.23 |
Report: WindowEnergyReportMonthly
For: ENTRANCE DOOR
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.108892E+09 | 52322359.42 | 56569636.87 | 0.143830E+09 | 0.114431E+09 |
| February | 0.113492E+09 | 52538760.24 | 60953540.52 | 0.161974E+09 | 85504563.81 |
| March | 0.153243E+09 | 72315791.28 | 80926835.46 | 0.221938E+09 | 77141347.17 |
| April | 0.161735E+09 | 72395034.13 | 89339842.40 | 0.260146E+09 | 54326390.61 |
| May | 0.157594E+09 | 62940245.14 | 94653949.81 | 0.272388E+09 | 31265836.30 |
| June | 0.150155E+09 | 57687441.50 | 92468049.56 | 0.268133E+09 | 14985089.49 |
| July | 0.159710E+09 | 57780947.60 | 0.101929E+09 | 0.297165E+09 | 22793867.89 |
| August | 0.145698E+09 | 48675443.54 | 97022570.76 | 0.258706E+09 | 19143982.49 |
| September | 0.135907E+09 | 49037498.53 | 86869168.25 | 0.245560E+09 | 24311554.60 |
| October | 0.129403E+09 | 55667131.16 | 73735716.76 | 0.219976E+09 | 40377029.85 |
| November | 0.101709E+09 | 40559888.82 | 61149055.55 | 0.154232E+09 | 62293627.16 |
| December | 85016467.95 | 30088605.41 | 54927862.54 | 0.111495E+09 | 0.101823E+09 |
| Annual Sum or Average | 0.160255E+10 | 0.652009E+09 | 0.950546E+09 | 0.261554E+10 | 0.648397E+09 |
| Minimum of Months | 85016467.95 | 30088605.41 | 54927862.54 | 0.111495E+09 | 14985089.49 |
| Maximum of Months | 0.161735E+09 | 72395034.13 | 0.101929E+09 | 0.297165E+09 | 0.114431E+09 |
Report: WindowEnergyReportMonthly
For: MWINDOW14
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 36562423.52 | 17568162.31 | 18994261.21 | 47366474.18 | 39510105.51 |
| February | 38107057.52 | 17640822.73 | 20466234.79 | 53670868.49 | 29221630.98 |
| March | 51453936.11 | 24281312.48 | 27172623.64 | 73523780.73 | 26351544.74 |
| April | 54305359.94 | 24307919.67 | 29997440.27 | 87962275.86 | 17472961.73 |
| May | 52915052.50 | 21133306.19 | 31781746.30 | 93830394.45 | 8813303.95 |
| June | 50417375.43 | 19369583.99 | 31047791.44 | 93839004.68 | 3610633.00 |
| July | 53625545.36 | 19400980.32 | 34224565.03 | 0.104277E+09 | 5461744.08 |
| August | 48920698.37 | 16343645.47 | 32577052.90 | 91342203.42 | 4099171.57 |
| September | 45633079.38 | 16465211.87 | 29167867.51 | 86771153.22 | 6222370.99 |
| October | 43449306.57 | 18691228.88 | 24758077.70 | 76645408.93 | 10757682.17 |
| November | 34150586.14 | 13618703.70 | 20531882.44 | 52659049.62 | 19413419.58 |
| December | 28545790.45 | 10102784.15 | 18443006.30 | 37151285.99 | 34864155.65 |
| Annual Sum or Average | 0.538086E+09 | 0.218924E+09 | 0.319163E+09 | 0.899039E+09 | 0.205799E+09 |
| Minimum of Months | 28545790.45 | 10102784.15 | 18443006.30 | 37151285.99 | 3610633.00 |
| Maximum of Months | 54305359.94 | 24307919.67 | 34224565.03 | 0.104277E+09 | 39510105.51 |
Report: WindowZoneSummaryMonthly
For: G SW APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 329.75 | 132.77 | 218.32 | 130.31 | 88.02 | 0.00 | 0.00 |
| February | 351.00 | 108.76 | 216.42 | 117.33 | 99.09 | 0.00 | 0.00 |
| March | 316.71 | 86.79 | 193.80 | 83.14 | 110.66 | 0.00 | 0.00 |
| April | 309.71 | 53.61 | 171.57 | 59.08 | 112.49 | 0.00 | 0.00 |
| May | 285.86 | 21.18 | 144.04 | 32.68 | 111.36 | 0.00 | 0.00 |
| June | 276.75 | 7.19 | 128.39 | 19.16 | 109.23 | 0.00 | 0.00 |
| July | 311.17 | 11.49 | 140.67 | 24.12 | 116.55 | 0.00 | 0.00 |
| August | 313.06 | 7.48 | 148.74 | 30.38 | 118.36 | 0.00 | 0.00 |
| September | 342.37 | 17.24 | 159.63 | 43.05 | 116.58 | 0.00 | 0.00 |
| October | 370.84 | 30.12 | 194.02 | 86.11 | 107.91 | 0.00 | 0.00 |
| November | 344.67 | 64.69 | 201.20 | 102.51 | 98.69 | 0.00 | 0.00 |
| December | 336.58 | 114.87 | 214.68 | 125.58 | 89.10 | 0.00 | 0.00 |
| Annual Sum or Average | 323.88 | 54.45 | 177.44 | 70.91 | 106.53 | 0.00 | 0.00 |
| Minimum of Months | 276.75 | 7.19 | 128.39 | 19.16 | 88.02 | 0.00 | 0.00 |
| Maximum of Months | 370.84 | 132.77 | 218.32 | 130.31 | 118.36 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: G NW APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 108.44 | 136.33 | 87.04 | 22.20 | 64.84 | 0.00 | 0.00 |
| February | 157.96 | 109.87 | 106.34 | 29.04 | 77.30 | 0.00 | 0.00 |
| March | 196.07 | 87.41 | 130.17 | 36.42 | 93.75 | 0.00 | 0.00 |
| April | 248.92 | 52.32 | 143.95 | 40.58 | 103.37 | 0.00 | 0.00 |
| May | 285.05 | 21.39 | 144.27 | 33.41 | 110.86 | 0.00 | 0.00 |
| June | 293.52 | 7.03 | 136.59 | 23.82 | 112.77 | 0.00 | 0.00 |
| July | 320.42 | 11.42 | 145.26 | 26.64 | 118.62 | 0.00 | 0.00 |
| August | 287.37 | 7.25 | 137.34 | 25.18 | 112.15 | 0.00 | 0.00 |
| September | 260.39 | 16.59 | 119.10 | 18.95 | 100.15 | 0.00 | 0.00 |
| October | 213.79 | 28.32 | 109.81 | 24.88 | 84.93 | 0.00 | 0.00 |
| November | 154.79 | 65.01 | 92.59 | 19.24 | 73.34 | 0.00 | 0.00 |
| December | 120.90 | 114.74 | 88.28 | 23.69 | 64.60 | 0.00 | 0.00 |
| Annual Sum or Average | 220.94 | 54.57 | 120.14 | 27.00 | 93.14 | 0.00 | 0.00 |
| Minimum of Months | 108.44 | 7.03 | 87.04 | 18.95 | 64.60 | 0.00 | 0.00 |
| Maximum of Months | 320.42 | 136.33 | 145.26 | 40.58 | 118.62 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: OFFICE
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 323.28 | 164.76 | 223.98 | 135.44 | 88.54 | 0.00 | 0.00 |
| February | 335.82 | 135.19 | 218.12 | 118.68 | 99.44 | 0.00 | 0.00 |
| March | 296.88 | 111.49 | 194.27 | 84.51 | 109.76 | 0.00 | 0.00 |
| April | 285.14 | 86.66 | 171.71 | 57.90 | 113.82 | 0.00 | 0.00 |
| May | 259.00 | 54.52 | 146.55 | 34.74 | 111.80 | 0.00 | 0.00 |
| June | 257.96 | 34.43 | 141.86 | 31.31 | 110.54 | 0.00 | 0.00 |
| July | 283.74 | 46.25 | 148.62 | 30.91 | 117.71 | 0.00 | 0.00 |
| August | 276.80 | 42.99 | 149.60 | 31.33 | 118.27 | 0.00 | 0.00 |
| September | 316.40 | 51.47 | 168.83 | 50.58 | 118.24 | 0.00 | 0.00 |
| October | 348.04 | 76.29 | 197.81 | 90.31 | 107.50 | 0.00 | 0.00 |
| November | 325.86 | 103.77 | 203.52 | 105.16 | 98.35 | 0.00 | 0.00 |
| December | 305.64 | 147.70 | 206.23 | 117.61 | 88.62 | 0.00 | 0.00 |
| Annual Sum or Average | 300.98 | 87.78 | 180.72 | 73.81 | 106.91 | 0.00 | 0.00 |
| Minimum of Months | 257.96 | 34.43 | 141.86 | 30.91 | 88.54 | 0.00 | 0.00 |
| Maximum of Months | 348.04 | 164.76 | 223.98 | 135.44 | 118.27 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: G NE APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 111.96 | 129.77 | 92.70 | 27.34 | 65.37 | 0.00 | 0.00 |
| February | 153.31 | 103.09 | 108.04 | 30.39 | 77.65 | 0.00 | 0.00 |
| March | 188.84 | 80.68 | 130.63 | 37.78 | 92.85 | 0.00 | 0.00 |
| April | 247.26 | 50.84 | 144.09 | 39.40 | 104.69 | 0.00 | 0.00 |
| May | 288.20 | 20.47 | 146.78 | 35.47 | 111.31 | 0.00 | 0.00 |
| June | 316.98 | 6.91 | 150.05 | 35.97 | 114.08 | 0.00 | 0.00 |
| July | 334.30 | 11.43 | 153.21 | 33.43 | 119.78 | 0.00 | 0.00 |
| August | 289.12 | 7.02 | 138.20 | 26.13 | 112.07 | 0.00 | 0.00 |
| September | 276.34 | 16.39 | 128.30 | 26.48 | 101.81 | 0.00 | 0.00 |
| October | 219.27 | 27.08 | 113.60 | 29.08 | 84.52 | 0.00 | 0.00 |
| November | 154.56 | 60.86 | 94.90 | 21.90 | 73.00 | 0.00 | 0.00 |
| December | 103.97 | 112.04 | 79.84 | 15.72 | 64.12 | 0.00 | 0.00 |
| Annual Sum or Average | 223.98 | 52.00 | 123.42 | 29.91 | 93.51 | 0.00 | 0.00 |
| Minimum of Months | 103.97 | 6.91 | 79.84 | 15.72 | 64.12 | 0.00 | 0.00 |
| Maximum of Months | 334.30 | 129.77 | 153.21 | 39.40 | 119.78 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: G N1 APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 36.95 | 85.25 | 35.81 | 0.00 | 35.81 | 0.00 | 0.00 |
| February | 56.76 | 67.85 | 42.39 | 0.00 | 42.39 | 0.00 | 0.00 |
| March | 69.48 | 54.03 | 50.57 | 0.00 | 50.57 | 0.00 | 0.00 |
| April | 97.35 | 30.93 | 56.78 | 0.32 | 56.46 | 0.00 | 0.00 |
| May | 133.40 | 12.16 | 64.45 | 2.59 | 61.85 | 0.00 | 0.00 |
| June | 156.02 | 3.94 | 68.99 | 4.83 | 64.16 | 0.00 | 0.00 |
| July | 163.89 | 6.37 | 69.77 | 3.24 | 66.53 | 0.00 | 0.00 |
| August | 138.60 | 3.88 | 62.08 | 0.70 | 61.38 | 0.00 | 0.00 |
| September | 128.60 | 9.50 | 54.93 | 0.01 | 54.91 | 0.00 | 0.00 |
| October | 93.74 | 16.05 | 45.99 | 0.00 | 45.99 | 0.00 | 0.00 |
| November | 65.21 | 38.99 | 39.99 | 0.00 | 39.99 | 0.00 | 0.00 |
| December | 42.06 | 71.39 | 35.42 | 0.00 | 35.42 | 0.00 | 0.00 |
| Annual Sum or Average | 98.70 | 33.21 | 52.31 | 0.98 | 51.34 | 0.00 | 0.00 |
| Minimum of Months | 36.95 | 3.88 | 35.42 | 0.00 | 35.42 | 0.00 | 0.00 |
| Maximum of Months | 163.89 | 85.25 | 69.77 | 4.83 | 66.53 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: G N2 APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 36.92 | 85.26 | 35.81 | 0.00 | 35.81 | 0.00 | 0.00 |
| February | 56.74 | 67.85 | 42.39 | 0.00 | 42.39 | 0.00 | 0.00 |
| March | 69.45 | 54.03 | 50.57 | 0.00 | 50.57 | 0.00 | 0.00 |
| April | 97.34 | 30.91 | 56.78 | 0.32 | 56.46 | 0.00 | 0.00 |
| May | 133.39 | 12.15 | 64.45 | 2.59 | 61.85 | 0.00 | 0.00 |
| June | 156.01 | 3.95 | 68.99 | 4.83 | 64.16 | 0.00 | 0.00 |
| July | 163.88 | 6.37 | 69.77 | 3.24 | 66.53 | 0.00 | 0.00 |
| August | 138.60 | 3.88 | 62.08 | 0.70 | 61.38 | 0.00 | 0.00 |
| September | 128.59 | 9.50 | 54.93 | 0.01 | 54.91 | 0.00 | 0.00 |
| October | 93.73 | 16.04 | 45.99 | 0.00 | 45.99 | 0.00 | 0.00 |
| November | 65.20 | 38.98 | 39.99 | 0.00 | 39.99 | 0.00 | 0.00 |
| December | 42.06 | 71.37 | 35.42 | 0.00 | 35.42 | 0.00 | 0.00 |
| Annual Sum or Average | 98.69 | 33.21 | 52.31 | 0.98 | 51.34 | 0.00 | 0.00 |
| Minimum of Months | 36.92 | 3.88 | 35.42 | 0.00 | 35.42 | 0.00 | 0.00 |
| Maximum of Months | 163.88 | 85.26 | 69.77 | 4.83 | 66.53 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: G S1 APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 261.46 | 79.80 | 167.09 | 108.10 | 58.99 | 0.00 | 0.00 |
| February | 252.62 | 65.22 | 152.47 | 88.29 | 64.18 | 0.00 | 0.00 |
| March | 192.05 | 52.39 | 114.21 | 46.73 | 67.48 | 0.00 | 0.00 |
| April | 158.90 | 32.10 | 84.40 | 18.81 | 65.59 | 0.00 | 0.00 |
| May | 134.11 | 11.92 | 64.21 | 1.86 | 62.35 | 0.00 | 0.00 |
| June | 138.83 | 4.07 | 60.79 | 0.17 | 60.63 | 0.00 | 0.00 |
| July | 154.41 | 6.48 | 65.18 | 0.72 | 64.46 | 0.00 | 0.00 |
| August | 164.50 | 4.09 | 73.48 | 5.90 | 67.59 | 0.00 | 0.00 |
| September | 211.39 | 10.02 | 95.46 | 24.11 | 71.35 | 0.00 | 0.00 |
| October | 252.17 | 17.29 | 130.20 | 61.23 | 68.98 | 0.00 | 0.00 |
| November | 257.42 | 38.18 | 148.61 | 83.27 | 65.34 | 0.00 | 0.00 |
| December | 259.50 | 68.96 | 161.82 | 101.89 | 59.92 | 0.00 | 0.00 |
| Annual Sum or Average | 202.83 | 32.40 | 109.61 | 44.88 | 64.73 | 0.00 | 0.00 |
| Minimum of Months | 134.11 | 4.07 | 60.79 | 0.17 | 58.99 | 0.00 | 0.00 |
| Maximum of Months | 261.46 | 79.80 | 167.09 | 108.10 | 71.35 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: G S2 APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 260.97 | 80.55 | 167.09 | 108.10 | 58.99 | 0.00 | 0.00 |
| February | 252.14 | 65.87 | 152.47 | 88.29 | 64.18 | 0.00 | 0.00 |
| March | 191.51 | 53.09 | 114.21 | 46.73 | 67.48 | 0.00 | 0.00 |
| April | 158.23 | 32.90 | 84.40 | 18.81 | 65.59 | 0.00 | 0.00 |
| May | 133.17 | 12.65 | 64.21 | 1.86 | 62.35 | 0.00 | 0.00 |
| June | 137.47 | 4.50 | 60.79 | 0.17 | 60.63 | 0.00 | 0.00 |
| July | 153.10 | 7.05 | 65.18 | 0.72 | 64.46 | 0.00 | 0.00 |
| August | 163.11 | 4.55 | 73.48 | 5.90 | 67.59 | 0.00 | 0.00 |
| September | 210.11 | 10.59 | 95.46 | 24.11 | 71.35 | 0.00 | 0.00 |
| October | 251.23 | 18.21 | 130.20 | 61.23 | 68.98 | 0.00 | 0.00 |
| November | 256.73 | 39.02 | 148.61 | 83.27 | 65.34 | 0.00 | 0.00 |
| December | 259.04 | 69.72 | 161.82 | 101.89 | 59.92 | 0.00 | 0.00 |
| Annual Sum or Average | 201.95 | 33.08 | 109.61 | 44.88 | 64.73 | 0.00 | 0.00 |
| Minimum of Months | 133.17 | 4.50 | 60.79 | 0.17 | 58.99 | 0.00 | 0.00 |
| Maximum of Months | 260.97 | 80.55 | 167.09 | 108.10 | 71.35 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: M SW APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 328.82 | 131.03 | 218.32 | 130.31 | 88.02 | 0.00 | 0.00 |
| February | 349.46 | 107.84 | 216.42 | 117.33 | 99.09 | 0.00 | 0.00 |
| March | 314.17 | 87.14 | 193.80 | 83.14 | 110.66 | 0.00 | 0.00 |
| April | 307.90 | 53.63 | 171.57 | 59.08 | 112.49 | 0.00 | 0.00 |
| May | 285.53 | 20.34 | 144.04 | 32.68 | 111.36 | 0.00 | 0.00 |
| June | 277.83 | 6.61 | 128.39 | 19.16 | 109.23 | 0.00 | 0.00 |
| July | 313.38 | 10.14 | 140.67 | 24.12 | 116.55 | 0.00 | 0.00 |
| August | 316.65 | 6.19 | 148.74 | 30.38 | 118.36 | 0.00 | 0.00 |
| September | 345.74 | 15.32 | 159.63 | 43.05 | 116.58 | 0.00 | 0.00 |
| October | 372.66 | 26.62 | 194.02 | 86.11 | 107.91 | 0.00 | 0.00 |
| November | 345.28 | 61.49 | 201.20 | 102.51 | 98.69 | 0.00 | 0.00 |
| December | 336.04 | 112.34 | 214.68 | 125.58 | 89.10 | 0.00 | 0.00 |
| Annual Sum or Average | 324.31 | 52.98 | 177.44 | 70.91 | 106.53 | 0.00 | 0.00 |
| Minimum of Months | 277.83 | 6.19 | 128.39 | 19.16 | 88.02 | 0.00 | 0.00 |
| Maximum of Months | 372.66 | 131.03 | 218.32 | 130.31 | 118.36 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: M NW APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 108.60 | 135.16 | 87.04 | 22.20 | 64.84 | 0.00 | 0.00 |
| February | 157.52 | 109.41 | 106.34 | 29.04 | 77.30 | 0.00 | 0.00 |
| March | 194.05 | 88.56 | 130.17 | 36.42 | 93.75 | 0.00 | 0.00 |
| April | 247.39 | 52.62 | 143.95 | 40.58 | 103.37 | 0.00 | 0.00 |
| May | 284.72 | 20.59 | 144.27 | 33.41 | 110.86 | 0.00 | 0.00 |
| June | 294.56 | 6.40 | 136.59 | 23.82 | 112.77 | 0.00 | 0.00 |
| July | 322.65 | 9.99 | 145.26 | 26.64 | 118.62 | 0.00 | 0.00 |
| August | 291.03 | 5.96 | 137.34 | 25.18 | 112.15 | 0.00 | 0.00 |
| September | 264.13 | 14.75 | 119.10 | 18.95 | 100.15 | 0.00 | 0.00 |
| October | 216.27 | 25.19 | 109.81 | 24.88 | 84.93 | 0.00 | 0.00 |
| November | 156.22 | 62.16 | 92.59 | 19.24 | 73.34 | 0.00 | 0.00 |
| December | 121.61 | 112.25 | 88.28 | 23.69 | 64.60 | 0.00 | 0.00 |
| Annual Sum or Average | 221.88 | 53.34 | 120.14 | 27.00 | 93.14 | 0.00 | 0.00 |
| Minimum of Months | 108.60 | 5.96 | 87.04 | 18.95 | 64.60 | 0.00 | 0.00 |
| Maximum of Months | 322.65 | 135.16 | 145.26 | 40.58 | 118.62 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: M SE APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 337.30 | 128.95 | 223.98 | 135.44 | 88.54 | 0.00 | 0.00 |
| February | 348.51 | 104.73 | 218.12 | 118.68 | 99.44 | 0.00 | 0.00 |
| March | 309.56 | 82.89 | 194.27 | 84.51 | 109.76 | 0.00 | 0.00 |
| April | 305.94 | 51.98 | 171.71 | 57.90 | 113.82 | 0.00 | 0.00 |
| May | 288.19 | 18.93 | 146.55 | 34.74 | 111.80 | 0.00 | 0.00 |
| June | 301.08 | 6.20 | 141.86 | 31.31 | 110.54 | 0.00 | 0.00 |
| July | 327.19 | 10.06 | 148.62 | 30.91 | 117.71 | 0.00 | 0.00 |
| August | 318.55 | 5.99 | 149.60 | 31.33 | 118.27 | 0.00 | 0.00 |
| September | 361.77 | 15.14 | 168.83 | 50.58 | 118.24 | 0.00 | 0.00 |
| October | 378.60 | 25.80 | 197.81 | 90.31 | 107.50 | 0.00 | 0.00 |
| November | 347.59 | 59.79 | 203.52 | 105.16 | 98.35 | 0.00 | 0.00 |
| December | 320.22 | 110.76 | 206.23 | 117.61 | 88.62 | 0.00 | 0.00 |
| Annual Sum or Average | 328.54 | 51.53 | 180.72 | 73.81 | 106.91 | 0.00 | 0.00 |
| Minimum of Months | 288.19 | 5.99 | 141.86 | 30.91 | 88.54 | 0.00 | 0.00 |
| Maximum of Months | 378.60 | 128.95 | 223.98 | 135.44 | 118.27 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: M NE APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 112.04 | 128.58 | 92.70 | 27.34 | 65.37 | 0.00 | 0.00 |
| February | 152.74 | 102.50 | 108.04 | 30.39 | 77.65 | 0.00 | 0.00 |
| March | 186.53 | 81.68 | 130.63 | 37.78 | 92.85 | 0.00 | 0.00 |
| April | 245.55 | 51.05 | 144.09 | 39.40 | 104.69 | 0.00 | 0.00 |
| May | 287.79 | 19.58 | 146.78 | 35.47 | 111.31 | 0.00 | 0.00 |
| June | 318.06 | 6.24 | 150.05 | 35.97 | 114.08 | 0.00 | 0.00 |
| July | 336.57 | 10.02 | 153.21 | 33.43 | 119.78 | 0.00 | 0.00 |
| August | 292.98 | 5.78 | 138.20 | 26.13 | 112.07 | 0.00 | 0.00 |
| September | 280.20 | 14.61 | 128.30 | 26.48 | 101.81 | 0.00 | 0.00 |
| October | 221.88 | 24.01 | 113.60 | 29.08 | 84.52 | 0.00 | 0.00 |
| November | 156.10 | 58.11 | 94.90 | 21.90 | 73.00 | 0.00 | 0.00 |
| December | 104.77 | 109.58 | 79.84 | 15.72 | 64.12 | 0.00 | 0.00 |
| Annual Sum or Average | 224.91 | 50.76 | 123.42 | 29.91 | 93.51 | 0.00 | 0.00 |
| Minimum of Months | 104.77 | 5.78 | 79.84 | 15.72 | 64.12 | 0.00 | 0.00 |
| Maximum of Months | 336.57 | 128.58 | 153.21 | 39.40 | 119.78 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: M N1 APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 36.99 | 85.09 | 35.81 | 0.00 | 35.81 | 0.00 | 0.00 |
| February | 56.65 | 67.79 | 42.39 | 0.00 | 42.39 | 0.00 | 0.00 |
| March | 68.74 | 54.65 | 50.57 | 0.00 | 50.57 | 0.00 | 0.00 |
| April | 96.90 | 30.95 | 56.78 | 0.32 | 56.46 | 0.00 | 0.00 |
| May | 133.54 | 11.64 | 64.45 | 2.59 | 61.85 | 0.00 | 0.00 |
| June | 156.87 | 3.56 | 68.99 | 4.83 | 64.16 | 0.00 | 0.00 |
| July | 165.31 | 5.64 | 69.77 | 3.24 | 66.53 | 0.00 | 0.00 |
| August | 140.76 | 3.29 | 62.08 | 0.70 | 61.38 | 0.00 | 0.00 |
| September | 130.69 | 8.59 | 54.93 | 0.01 | 54.91 | 0.00 | 0.00 |
| October | 95.23 | 14.52 | 45.99 | 0.00 | 45.99 | 0.00 | 0.00 |
| November | 65.99 | 37.75 | 39.99 | 0.00 | 39.99 | 0.00 | 0.00 |
| December | 42.31 | 70.72 | 35.42 | 0.00 | 35.42 | 0.00 | 0.00 |
| Annual Sum or Average | 99.37 | 32.70 | 52.31 | 0.98 | 51.34 | 0.00 | 0.00 |
| Minimum of Months | 36.99 | 3.29 | 35.42 | 0.00 | 35.42 | 0.00 | 0.00 |
| Maximum of Months | 165.31 | 85.09 | 69.77 | 4.83 | 66.53 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: M N2 APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 36.96 | 85.11 | 35.81 | 0.00 | 35.81 | 0.00 | 0.00 |
| February | 56.62 | 67.78 | 42.39 | 0.00 | 42.39 | 0.00 | 0.00 |
| March | 68.70 | 54.66 | 50.57 | 0.00 | 50.57 | 0.00 | 0.00 |
| April | 96.89 | 30.94 | 56.78 | 0.32 | 56.46 | 0.00 | 0.00 |
| May | 133.53 | 11.63 | 64.45 | 2.59 | 61.85 | 0.00 | 0.00 |
| June | 156.86 | 3.57 | 68.99 | 4.83 | 64.16 | 0.00 | 0.00 |
| July | 165.30 | 5.64 | 69.77 | 3.24 | 66.53 | 0.00 | 0.00 |
| August | 140.76 | 3.29 | 62.08 | 0.70 | 61.38 | 0.00 | 0.00 |
| September | 130.68 | 8.59 | 54.93 | 0.01 | 54.91 | 0.00 | 0.00 |
| October | 95.22 | 14.51 | 45.99 | 0.00 | 45.99 | 0.00 | 0.00 |
| November | 65.98 | 37.75 | 39.99 | 0.00 | 39.99 | 0.00 | 0.00 |
| December | 42.31 | 70.70 | 35.42 | 0.00 | 35.42 | 0.00 | 0.00 |
| Annual Sum or Average | 99.35 | 32.70 | 52.31 | 0.98 | 51.34 | 0.00 | 0.00 |
| Minimum of Months | 36.96 | 3.29 | 35.42 | 0.00 | 35.42 | 0.00 | 0.00 |
| Maximum of Months | 165.30 | 85.11 | 69.77 | 4.83 | 66.53 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: M S1 APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 260.54 | 78.98 | 167.09 | 108.10 | 58.99 | 0.00 | 0.00 |
| February | 251.45 | 64.74 | 152.47 | 88.29 | 64.18 | 0.00 | 0.00 |
| March | 190.68 | 52.40 | 114.21 | 46.73 | 67.48 | 0.00 | 0.00 |
| April | 158.14 | 31.90 | 84.40 | 18.81 | 65.59 | 0.00 | 0.00 |
| May | 134.34 | 11.33 | 64.21 | 1.86 | 62.35 | 0.00 | 0.00 |
| June | 139.87 | 3.71 | 60.79 | 0.17 | 60.63 | 0.00 | 0.00 |
| July | 155.90 | 5.78 | 65.18 | 0.72 | 64.46 | 0.00 | 0.00 |
| August | 166.63 | 3.48 | 73.48 | 5.90 | 67.59 | 0.00 | 0.00 |
| September | 213.12 | 9.06 | 95.46 | 24.11 | 71.35 | 0.00 | 0.00 |
| October | 252.97 | 15.51 | 130.20 | 61.23 | 68.98 | 0.00 | 0.00 |
| November | 257.37 | 36.60 | 148.61 | 83.27 | 65.34 | 0.00 | 0.00 |
| December | 258.74 | 67.82 | 161.82 | 101.89 | 59.92 | 0.00 | 0.00 |
| Annual Sum or Average | 203.04 | 31.63 | 109.61 | 44.88 | 64.73 | 0.00 | 0.00 |
| Minimum of Months | 134.34 | 3.48 | 60.79 | 0.17 | 58.99 | 0.00 | 0.00 |
| Maximum of Months | 260.54 | 78.98 | 167.09 | 108.10 | 71.35 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: M S2 APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 260.52 | 78.98 | 167.09 | 108.10 | 58.99 | 0.00 | 0.00 |
| February | 251.43 | 64.73 | 152.47 | 88.29 | 64.18 | 0.00 | 0.00 |
| March | 190.66 | 52.39 | 114.21 | 46.73 | 67.48 | 0.00 | 0.00 |
| April | 158.13 | 31.89 | 84.40 | 18.81 | 65.59 | 0.00 | 0.00 |
| May | 134.33 | 11.32 | 64.21 | 1.86 | 62.35 | 0.00 | 0.00 |
| June | 139.85 | 3.71 | 60.79 | 0.17 | 60.63 | 0.00 | 0.00 |
| July | 155.89 | 5.78 | 65.18 | 0.72 | 64.46 | 0.00 | 0.00 |
| August | 166.63 | 3.47 | 73.48 | 5.90 | 67.59 | 0.00 | 0.00 |
| September | 213.11 | 9.06 | 95.46 | 24.11 | 71.35 | 0.00 | 0.00 |
| October | 252.96 | 15.51 | 130.20 | 61.23 | 68.98 | 0.00 | 0.00 |
| November | 257.36 | 36.60 | 148.61 | 83.27 | 65.34 | 0.00 | 0.00 |
| December | 258.74 | 67.81 | 161.82 | 101.89 | 59.92 | 0.00 | 0.00 |
| Annual Sum or Average | 203.03 | 31.62 | 109.61 | 44.88 | 64.73 | 0.00 | 0.00 |
| Minimum of Months | 134.33 | 3.47 | 60.79 | 0.17 | 58.99 | 0.00 | 0.00 |
| Maximum of Months | 260.52 | 78.98 | 167.09 | 108.10 | 71.35 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: T SW APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 328.86 | 118.81 | 218.32 | 130.31 | 88.02 | 0.00 | 0.00 |
| February | 346.67 | 99.03 | 216.42 | 117.33 | 99.09 | 0.00 | 0.00 |
| March | 310.41 | 80.14 | 193.80 | 83.14 | 110.66 | 0.00 | 0.00 |
| April | 300.95 | 51.54 | 171.57 | 59.08 | 112.49 | 0.00 | 0.00 |
| May | 277.62 | 19.94 | 144.04 | 32.68 | 111.36 | 0.00 | 0.00 |
| June | 269.21 | 6.39 | 128.39 | 19.16 | 109.23 | 0.00 | 0.00 |
| July | 304.15 | 9.82 | 140.67 | 24.12 | 116.55 | 0.00 | 0.00 |
| August | 308.31 | 6.07 | 148.74 | 30.38 | 118.36 | 0.00 | 0.00 |
| September | 336.92 | 14.63 | 159.63 | 43.05 | 116.58 | 0.00 | 0.00 |
| October | 365.40 | 25.50 | 194.02 | 86.11 | 107.91 | 0.00 | 0.00 |
| November | 340.73 | 57.04 | 201.20 | 102.51 | 98.69 | 0.00 | 0.00 |
| December | 334.41 | 102.33 | 214.68 | 125.58 | 89.10 | 0.00 | 0.00 |
| Annual Sum or Average | 318.48 | 49.04 | 177.44 | 70.91 | 106.53 | 0.00 | 0.00 |
| Minimum of Months | 269.21 | 6.07 | 128.39 | 19.16 | 88.02 | 0.00 | 0.00 |
| Maximum of Months | 365.40 | 118.81 | 218.32 | 130.31 | 118.36 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: T NW APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 111.13 | 119.29 | 87.04 | 22.20 | 64.84 | 0.00 | 0.00 |
| February | 156.77 | 99.41 | 106.34 | 29.04 | 77.30 | 0.00 | 0.00 |
| March | 191.69 | 80.56 | 130.17 | 36.42 | 93.75 | 0.00 | 0.00 |
| April | 241.40 | 50.71 | 143.95 | 40.58 | 103.37 | 0.00 | 0.00 |
| May | 277.05 | 20.38 | 144.27 | 33.41 | 110.86 | 0.00 | 0.00 |
| June | 285.79 | 6.21 | 136.59 | 23.82 | 112.77 | 0.00 | 0.00 |
| July | 313.38 | 9.69 | 145.26 | 26.64 | 118.62 | 0.00 | 0.00 |
| August | 283.06 | 5.85 | 137.34 | 25.18 | 112.15 | 0.00 | 0.00 |
| September | 256.24 | 14.15 | 119.10 | 18.95 | 100.15 | 0.00 | 0.00 |
| October | 210.72 | 24.28 | 109.81 | 24.88 | 84.93 | 0.00 | 0.00 |
| November | 153.74 | 57.08 | 92.59 | 19.24 | 73.34 | 0.00 | 0.00 |
| December | 122.66 | 99.71 | 88.28 | 23.69 | 64.60 | 0.00 | 0.00 |
| Annual Sum or Average | 217.27 | 48.71 | 120.14 | 27.00 | 93.14 | 0.00 | 0.00 |
| Minimum of Months | 111.13 | 5.85 | 87.04 | 18.95 | 64.60 | 0.00 | 0.00 |
| Maximum of Months | 313.38 | 119.29 | 145.26 | 40.58 | 118.62 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: T SE APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 336.98 | 117.02 | 223.98 | 135.44 | 88.54 | 0.00 | 0.00 |
| February | 345.68 | 96.21 | 218.12 | 118.68 | 99.44 | 0.00 | 0.00 |
| March | 305.86 | 76.51 | 194.27 | 84.51 | 109.76 | 0.00 | 0.00 |
| April | 298.76 | 49.87 | 171.71 | 57.90 | 113.82 | 0.00 | 0.00 |
| May | 279.91 | 18.33 | 146.55 | 34.74 | 111.80 | 0.00 | 0.00 |
| June | 292.14 | 5.97 | 141.86 | 31.31 | 110.54 | 0.00 | 0.00 |
| July | 317.73 | 9.71 | 148.62 | 30.91 | 117.71 | 0.00 | 0.00 |
| August | 310.11 | 5.81 | 149.60 | 31.33 | 118.27 | 0.00 | 0.00 |
| September | 352.72 | 14.46 | 168.83 | 50.58 | 118.24 | 0.00 | 0.00 |
| October | 371.03 | 24.49 | 197.81 | 90.31 | 107.50 | 0.00 | 0.00 |
| November | 342.84 | 55.38 | 203.52 | 105.16 | 98.35 | 0.00 | 0.00 |
| December | 318.45 | 100.69 | 206.23 | 117.61 | 88.62 | 0.00 | 0.00 |
| Annual Sum or Average | 322.51 | 47.65 | 180.72 | 73.81 | 106.91 | 0.00 | 0.00 |
| Minimum of Months | 279.91 | 5.81 | 141.86 | 30.91 | 88.54 | 0.00 | 0.00 |
| Maximum of Months | 371.03 | 117.02 | 223.98 | 135.44 | 118.27 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: T NE APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 115.69 | 114.28 | 92.70 | 27.34 | 65.37 | 0.00 | 0.00 |
| February | 152.71 | 93.55 | 108.04 | 30.39 | 77.65 | 0.00 | 0.00 |
| March | 185.18 | 74.80 | 130.63 | 37.78 | 92.85 | 0.00 | 0.00 |
| April | 239.23 | 49.02 | 144.09 | 39.40 | 104.69 | 0.00 | 0.00 |
| May | 279.67 | 19.10 | 146.78 | 35.47 | 111.31 | 0.00 | 0.00 |
| June | 308.93 | 5.98 | 150.05 | 35.97 | 114.08 | 0.00 | 0.00 |
| July | 327.03 | 9.65 | 153.21 | 33.43 | 119.78 | 0.00 | 0.00 |
| August | 284.89 | 5.61 | 138.20 | 26.13 | 112.07 | 0.00 | 0.00 |
| September | 272.10 | 14.01 | 128.30 | 26.48 | 101.81 | 0.00 | 0.00 |
| October | 216.06 | 22.95 | 113.60 | 29.08 | 84.52 | 0.00 | 0.00 |
| November | 153.81 | 53.49 | 94.90 | 21.90 | 73.00 | 0.00 | 0.00 |
| December | 106.46 | 97.34 | 79.84 | 15.72 | 64.12 | 0.00 | 0.00 |
| Annual Sum or Average | 220.45 | 46.44 | 123.42 | 29.91 | 93.51 | 0.00 | 0.00 |
| Minimum of Months | 106.46 | 5.61 | 79.84 | 15.72 | 64.12 | 0.00 | 0.00 |
| Maximum of Months | 327.03 | 114.28 | 153.21 | 39.40 | 119.78 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: T N1 APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 38.54 | 75.99 | 35.81 | 0.00 | 35.81 | 0.00 | 0.00 |
| February | 56.76 | 61.99 | 42.39 | 0.00 | 42.39 | 0.00 | 0.00 |
| March | 68.04 | 49.97 | 50.57 | 0.00 | 50.57 | 0.00 | 0.00 |
| April | 93.95 | 30.25 | 56.78 | 0.32 | 56.46 | 0.00 | 0.00 |
| May | 129.59 | 11.70 | 64.45 | 2.59 | 61.85 | 0.00 | 0.00 |
| June | 152.17 | 3.56 | 68.99 | 4.83 | 64.16 | 0.00 | 0.00 |
| July | 160.41 | 5.62 | 69.77 | 3.24 | 66.53 | 0.00 | 0.00 |
| August | 136.57 | 3.32 | 62.08 | 0.70 | 61.38 | 0.00 | 0.00 |
| September | 126.57 | 8.41 | 54.93 | 0.01 | 54.91 | 0.00 | 0.00 |
| October | 92.43 | 14.16 | 45.99 | 0.00 | 45.99 | 0.00 | 0.00 |
| November | 64.87 | 35.10 | 39.99 | 0.00 | 39.99 | 0.00 | 0.00 |
| December | 43.24 | 63.06 | 35.42 | 0.00 | 35.42 | 0.00 | 0.00 |
| Annual Sum or Average | 97.12 | 30.12 | 52.31 | 0.98 | 51.34 | 0.00 | 0.00 |
| Minimum of Months | 38.54 | 3.32 | 35.42 | 0.00 | 35.42 | 0.00 | 0.00 |
| Maximum of Months | 160.41 | 75.99 | 69.77 | 4.83 | 66.53 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: T N2 APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 38.45 | 75.97 | 35.81 | 0.00 | 35.81 | 0.00 | 0.00 |
| February | 56.69 | 61.95 | 42.39 | 0.00 | 42.39 | 0.00 | 0.00 |
| March | 67.95 | 49.92 | 50.57 | 0.00 | 50.57 | 0.00 | 0.00 |
| April | 93.91 | 30.21 | 56.78 | 0.32 | 56.46 | 0.00 | 0.00 |
| May | 129.57 | 11.68 | 64.45 | 2.59 | 61.85 | 0.00 | 0.00 |
| June | 152.15 | 3.55 | 68.99 | 4.83 | 64.16 | 0.00 | 0.00 |
| July | 160.40 | 5.61 | 69.77 | 3.24 | 66.53 | 0.00 | 0.00 |
| August | 136.56 | 3.32 | 62.08 | 0.70 | 61.38 | 0.00 | 0.00 |
| September | 126.55 | 8.41 | 54.93 | 0.01 | 54.91 | 0.00 | 0.00 |
| October | 92.41 | 14.15 | 45.99 | 0.00 | 45.99 | 0.00 | 0.00 |
| November | 64.84 | 35.09 | 39.99 | 0.00 | 39.99 | 0.00 | 0.00 |
| December | 43.21 | 62.99 | 35.42 | 0.00 | 35.42 | 0.00 | 0.00 |
| Annual Sum or Average | 97.08 | 30.10 | 52.31 | 0.98 | 51.34 | 0.00 | 0.00 |
| Minimum of Months | 38.45 | 3.32 | 35.42 | 0.00 | 35.42 | 0.00 | 0.00 |
| Maximum of Months | 160.40 | 75.97 | 69.77 | 4.83 | 66.53 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: T S1 APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 260.33 | 73.32 | 167.09 | 108.10 | 58.99 | 0.00 | 0.00 |
| February | 249.97 | 60.46 | 152.47 | 88.29 | 64.18 | 0.00 | 0.00 |
| March | 188.87 | 48.98 | 114.21 | 46.73 | 67.48 | 0.00 | 0.00 |
| April | 154.55 | 31.12 | 84.40 | 18.81 | 65.59 | 0.00 | 0.00 |
| May | 130.20 | 11.25 | 64.21 | 1.86 | 62.35 | 0.00 | 0.00 |
| June | 135.28 | 3.70 | 60.79 | 0.17 | 60.63 | 0.00 | 0.00 |
| July | 151.03 | 5.75 | 65.18 | 0.72 | 64.46 | 0.00 | 0.00 |
| August | 162.18 | 3.52 | 73.48 | 5.90 | 67.59 | 0.00 | 0.00 |
| September | 208.32 | 8.82 | 95.46 | 24.11 | 71.35 | 0.00 | 0.00 |
| October | 248.96 | 15.03 | 130.20 | 61.23 | 68.98 | 0.00 | 0.00 |
| November | 254.76 | 34.55 | 148.61 | 83.27 | 65.34 | 0.00 | 0.00 |
| December | 257.72 | 62.90 | 161.82 | 101.89 | 59.92 | 0.00 | 0.00 |
| Annual Sum or Average | 199.90 | 29.81 | 109.61 | 44.88 | 64.73 | 0.00 | 0.00 |
| Minimum of Months | 130.20 | 3.52 | 60.79 | 0.17 | 58.99 | 0.00 | 0.00 |
| Maximum of Months | 260.33 | 73.32 | 167.09 | 108.10 | 71.35 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: T S2 APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 260.28 | 73.29 | 167.09 | 108.10 | 58.99 | 0.00 | 0.00 |
| February | 249.92 | 60.42 | 152.47 | 88.29 | 64.18 | 0.00 | 0.00 |
| March | 188.80 | 48.94 | 114.21 | 46.73 | 67.48 | 0.00 | 0.00 |
| April | 154.51 | 31.08 | 84.40 | 18.81 | 65.59 | 0.00 | 0.00 |
| May | 130.18 | 11.23 | 64.21 | 1.86 | 62.35 | 0.00 | 0.00 |
| June | 135.25 | 3.69 | 60.79 | 0.17 | 60.63 | 0.00 | 0.00 |
| July | 151.01 | 5.75 | 65.18 | 0.72 | 64.46 | 0.00 | 0.00 |
| August | 162.18 | 3.51 | 73.48 | 5.90 | 67.59 | 0.00 | 0.00 |
| September | 208.31 | 8.82 | 95.46 | 24.11 | 71.35 | 0.00 | 0.00 |
| October | 248.94 | 15.01 | 130.20 | 61.23 | 68.98 | 0.00 | 0.00 |
| November | 254.73 | 34.54 | 148.61 | 83.27 | 65.34 | 0.00 | 0.00 |
| December | 257.69 | 62.87 | 161.82 | 101.89 | 59.92 | 0.00 | 0.00 |
| Annual Sum or Average | 199.87 | 29.79 | 109.61 | 44.88 | 64.73 | 0.00 | 0.00 |
| Minimum of Months | 130.18 | 3.51 | 60.79 | 0.17 | 58.99 | 0.00 | 0.00 |
| Maximum of Months | 260.28 | 73.29 | 167.09 | 108.10 | 71.35 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: T CORRIDOR
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 18.50 | 13.36 | 13.65 | 6.56 | 7.09 | 0.00 | 0.00 |
| February | 22.67 | 11.13 | 15.75 | 7.29 | 8.46 | 0.00 | 0.00 |
| March | 27.79 | 9.14 | 19.21 | 9.07 | 10.15 | 0.00 | 0.00 |
| April | 33.65 | 6.54 | 20.95 | 9.38 | 11.57 | 0.00 | 0.00 |
| May | 34.42 | 3.31 | 19.76 | 7.89 | 11.87 | 0.00 | 0.00 |
| June | 35.37 | 1.42 | 19.45 | 7.47 | 11.98 | 0.00 | 0.00 |
| July | 38.09 | 2.10 | 20.02 | 7.24 | 12.78 | 0.00 | 0.00 |
| August | 33.37 | 1.58 | 18.26 | 6.10 | 12.16 | 0.00 | 0.00 |
| September | 32.70 | 2.37 | 17.61 | 6.35 | 11.25 | 0.00 | 0.00 |
| October | 28.24 | 3.94 | 16.22 | 6.98 | 9.24 | 0.00 | 0.00 |
| November | 20.39 | 7.02 | 13.18 | 5.25 | 7.92 | 0.00 | 0.00 |
| December | 14.38 | 11.80 | 10.66 | 3.77 | 6.89 | 0.00 | 0.00 |
| Annual Sum or Average | 28.32 | 6.12 | 17.06 | 6.94 | 10.12 | 0.00 | 0.00 |
| Minimum of Months | 14.38 | 1.42 | 10.66 | 3.77 | 6.89 | 0.00 | 0.00 |
| Maximum of Months | 38.09 | 13.36 | 20.95 | 9.38 | 12.78 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: G CORRIDOR
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 53.70 | 42.72 | 40.66 | 19.53 | 21.12 | 0.00 | 0.00 |
| February | 66.95 | 35.34 | 46.91 | 21.72 | 25.20 | 0.00 | 0.00 |
| March | 82.86 | 28.80 | 57.21 | 27.00 | 30.21 | 0.00 | 0.00 |
| April | 100.36 | 20.96 | 62.40 | 27.93 | 34.47 | 0.00 | 0.00 |
| May | 101.70 | 11.67 | 58.84 | 23.50 | 35.34 | 0.00 | 0.00 |
| June | 103.45 | 5.78 | 57.93 | 22.26 | 35.67 | 0.00 | 0.00 |
| July | 110.95 | 8.51 | 59.63 | 21.57 | 38.06 | 0.00 | 0.00 |
| August | 96.59 | 7.15 | 54.40 | 18.17 | 36.22 | 0.00 | 0.00 |
| September | 94.74 | 9.38 | 52.43 | 18.92 | 33.51 | 0.00 | 0.00 |
| October | 82.13 | 15.08 | 48.31 | 20.78 | 27.53 | 0.00 | 0.00 |
| November | 59.50 | 24.03 | 39.24 | 15.65 | 23.59 | 0.00 | 0.00 |
| December | 41.63 | 38.02 | 31.74 | 11.23 | 20.51 | 0.00 | 0.00 |
| Annual Sum or Average | 82.94 | 20.56 | 50.82 | 20.68 | 30.14 | 0.00 | 0.00 |
| Minimum of Months | 41.63 | 5.78 | 31.74 | 11.23 | 20.51 | 0.00 | 0.00 |
| Maximum of Months | 110.95 | 42.72 | 62.40 | 27.93 | 38.06 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: M CORRIDOR
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 17.68 | 14.75 | 13.65 | 6.56 | 7.09 | 0.00 | 0.00 |
| February | 22.19 | 12.08 | 15.75 | 7.29 | 8.46 | 0.00 | 0.00 |
| March | 27.45 | 9.84 | 19.21 | 9.07 | 10.15 | 0.00 | 0.00 |
| April | 33.94 | 6.74 | 20.95 | 9.38 | 11.57 | 0.00 | 0.00 |
| May | 35.03 | 3.29 | 19.76 | 7.89 | 11.87 | 0.00 | 0.00 |
| June | 36.20 | 1.39 | 19.45 | 7.47 | 11.98 | 0.00 | 0.00 |
| July | 38.93 | 2.04 | 20.02 | 7.24 | 12.78 | 0.00 | 0.00 |
| August | 34.10 | 1.53 | 18.26 | 6.10 | 12.16 | 0.00 | 0.00 |
| September | 33.48 | 2.40 | 17.61 | 6.35 | 11.25 | 0.00 | 0.00 |
| October | 28.62 | 4.02 | 16.22 | 6.98 | 9.24 | 0.00 | 0.00 |
| November | 20.32 | 7.49 | 13.18 | 5.25 | 7.92 | 0.00 | 0.00 |
| December | 13.87 | 13.02 | 10.66 | 3.77 | 6.89 | 0.00 | 0.00 |
| Annual Sum or Average | 28.51 | 6.53 | 17.06 | 6.94 | 10.12 | 0.00 | 0.00 |
| Minimum of Months | 13.87 | 1.39 | 10.66 | 3.77 | 6.89 | 0.00 | 0.00 |
| Maximum of Months | 38.93 | 14.75 | 20.95 | 9.38 | 12.78 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: G SW APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.883195E+09 | 0.355616E+09 | 0.584756E+09 | 0.349010E+09 | 0.235746E+09 | 0.00 | 0.00 |
| February | 0.849151E+09 | 0.263103E+09 | 0.523558E+09 | 0.283833E+09 | 0.239725E+09 | 0.00 | 0.00 |
| March | 0.848266E+09 | 0.232447E+09 | 0.519083E+09 | 0.222694E+09 | 0.296389E+09 | 0.00 | 0.00 |
| April | 0.802762E+09 | 0.138944E+09 | 0.444720E+09 | 0.153137E+09 | 0.291583E+09 | 0.00 | 0.00 |
| May | 0.765646E+09 | 56726188.31 | 0.385797E+09 | 87529673.31 | 0.298268E+09 | 0.00 | 0.00 |
| June | 0.717332E+09 | 18629715.82 | 0.332798E+09 | 49671949.89 | 0.283126E+09 | 0.00 | 0.00 |
| July | 0.833443E+09 | 30784911.28 | 0.376766E+09 | 64600730.47 | 0.312165E+09 | 0.00 | 0.00 |
| August | 0.838508E+09 | 20035129.31 | 0.398389E+09 | 81373257.56 | 0.317016E+09 | 0.00 | 0.00 |
| September | 0.887436E+09 | 44685231.84 | 0.413759E+09 | 0.111590E+09 | 0.302169E+09 | 0.00 | 0.00 |
| October | 0.993262E+09 | 80683216.49 | 0.519661E+09 | 0.230642E+09 | 0.289019E+09 | 0.00 | 0.00 |
| November | 0.893388E+09 | 0.167672E+09 | 0.521519E+09 | 0.265703E+09 | 0.255816E+09 | 0.00 | 0.00 |
| December | 0.901496E+09 | 0.307667E+09 | 0.574988E+09 | 0.336350E+09 | 0.238639E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.102139E+11 | 0.171699E+10 | 0.559579E+10 | 0.223613E+10 | 0.335966E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.717332E+09 | 18629715.82 | 0.332798E+09 | 49671949.89 | 0.235746E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.993262E+09 | 0.355616E+09 | 0.584756E+09 | 0.349010E+09 | 0.317016E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: G NW APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.290441E+09 | 0.365155E+09 | 0.233139E+09 | 59462026.64 | 0.173677E+09 | 0.00 | 0.00 |
| February | 0.382148E+09 | 0.265800E+09 | 0.257250E+09 | 70244097.88 | 0.187006E+09 | 0.00 | 0.00 |
| March | 0.525150E+09 | 0.234128E+09 | 0.348643E+09 | 97536627.56 | 0.251107E+09 | 0.00 | 0.00 |
| April | 0.645198E+09 | 0.135610E+09 | 0.373131E+09 | 0.105196E+09 | 0.267935E+09 | 0.00 | 0.00 |
| May | 0.763480E+09 | 57294882.47 | 0.386422E+09 | 89483394.43 | 0.296939E+09 | 0.00 | 0.00 |
| June | 0.760801E+09 | 18220296.28 | 0.354038E+09 | 61739893.42 | 0.292298E+09 | 0.00 | 0.00 |
| July | 0.858220E+09 | 30598736.45 | 0.389063E+09 | 71356680.04 | 0.317706E+09 | 0.00 | 0.00 |
| August | 0.769680E+09 | 19423326.79 | 0.367845E+09 | 67453780.11 | 0.300391E+09 | 0.00 | 0.00 |
| September | 0.674924E+09 | 42989615.55 | 0.308703E+09 | 49123332.24 | 0.259580E+09 | 0.00 | 0.00 |
| October | 0.572622E+09 | 75855956.55 | 0.294118E+09 | 66648864.77 | 0.227469E+09 | 0.00 | 0.00 |
| November | 0.401203E+09 | 0.168501E+09 | 0.239980E+09 | 49872369.86 | 0.190108E+09 | 0.00 | 0.00 |
| December | 0.323825E+09 | 0.307310E+09 | 0.236461E+09 | 63440405.52 | 0.173021E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.696769E+10 | 0.172089E+10 | 0.378879E+10 | 0.851558E+09 | 0.293724E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.290441E+09 | 18220296.28 | 0.233139E+09 | 49123332.24 | 0.173021E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.858220E+09 | 0.365155E+09 | 0.389063E+09 | 0.105196E+09 | 0.317706E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: OFFICE
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.865881E+09 | 0.441287E+09 | 0.599912E+09 | 0.362763E+09 | 0.237149E+09 | 0.00 | 0.00 |
| February | 0.812418E+09 | 0.327062E+09 | 0.527670E+09 | 0.287106E+09 | 0.240564E+09 | 0.00 | 0.00 |
| March | 0.795157E+09 | 0.298609E+09 | 0.520327E+09 | 0.226357E+09 | 0.293970E+09 | 0.00 | 0.00 |
| April | 0.739072E+09 | 0.224618E+09 | 0.445075E+09 | 0.150065E+09 | 0.295010E+09 | 0.00 | 0.00 |
| May | 0.693698E+09 | 0.146028E+09 | 0.392507E+09 | 93057809.88 | 0.299449E+09 | 0.00 | 0.00 |
| June | 0.668642E+09 | 89252392.45 | 0.367693E+09 | 81160700.83 | 0.286532E+09 | 0.00 | 0.00 |
| July | 0.759961E+09 | 0.123886E+09 | 0.398058E+09 | 82784986.09 | 0.315273E+09 | 0.00 | 0.00 |
| August | 0.741389E+09 | 0.115151E+09 | 0.400690E+09 | 83904367.31 | 0.316785E+09 | 0.00 | 0.00 |
| September | 0.820115E+09 | 0.133399E+09 | 0.437597E+09 | 0.131113E+09 | 0.306484E+09 | 0.00 | 0.00 |
| October | 0.932178E+09 | 0.204331E+09 | 0.529809E+09 | 0.241888E+09 | 0.287921E+09 | 0.00 | 0.00 |
| November | 0.844626E+09 | 0.268980E+09 | 0.527521E+09 | 0.272586E+09 | 0.254935E+09 | 0.00 | 0.00 |
| December | 0.818632E+09 | 0.395609E+09 | 0.552371E+09 | 0.315012E+09 | 0.237358E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.949177E+10 | 0.276821E+10 | 0.569923E+10 | 0.232780E+10 | 0.337143E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.668642E+09 | 89252392.45 | 0.367693E+09 | 81160700.83 | 0.237149E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.932178E+09 | 0.441287E+09 | 0.599912E+09 | 0.362763E+09 | 0.316785E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: G NE APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.299863E+09 | 0.347584E+09 | 0.248295E+09 | 73214687.62 | 0.175081E+09 | 0.00 | 0.00 |
| February | 0.370896E+09 | 0.249391E+09 | 0.261362E+09 | 73517497.32 | 0.187845E+09 | 0.00 | 0.00 |
| March | 0.505786E+09 | 0.216084E+09 | 0.349888E+09 | 0.101200E+09 | 0.248687E+09 | 0.00 | 0.00 |
| April | 0.640889E+09 | 0.131789E+09 | 0.373486E+09 | 0.102125E+09 | 0.271361E+09 | 0.00 | 0.00 |
| May | 0.771922E+09 | 54815241.04 | 0.393131E+09 | 95011531.00 | 0.298120E+09 | 0.00 | 0.00 |
| June | 0.821608E+09 | 17922174.64 | 0.388933E+09 | 93228644.36 | 0.295704E+09 | 0.00 | 0.00 |
| July | 0.895386E+09 | 30627389.16 | 0.410355E+09 | 89540935.66 | 0.320814E+09 | 0.00 | 0.00 |
| August | 0.774379E+09 | 18809426.53 | 0.370145E+09 | 69984889.86 | 0.300161E+09 | 0.00 | 0.00 |
| September | 0.716270E+09 | 42470982.08 | 0.332541E+09 | 68646728.43 | 0.263895E+09 | 0.00 | 0.00 |
| October | 0.587297E+09 | 72539152.00 | 0.304266E+09 | 77895027.35 | 0.226371E+09 | 0.00 | 0.00 |
| November | 0.400629E+09 | 0.157738E+09 | 0.245983E+09 | 56755460.23 | 0.189227E+09 | 0.00 | 0.00 |
| December | 0.278462E+09 | 0.300089E+09 | 0.213843E+09 | 42102991.35 | 0.171740E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.706339E+10 | 0.163986E+10 | 0.389223E+10 | 0.943223E+09 | 0.294901E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.278462E+09 | 17922174.64 | 0.213843E+09 | 42102991.35 | 0.171740E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.895386E+09 | 0.347584E+09 | 0.410355E+09 | 0.102125E+09 | 0.320814E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: G N1 APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 98961155.64 | 0.228336E+09 | 95922893.25 | 0.00 | 95922893.25 | 0.00 | 0.00 |
| February | 0.137309E+09 | 0.164153E+09 | 0.102552E+09 | 0.00 | 0.102552E+09 | 0.00 | 0.00 |
| March | 0.186096E+09 | 0.144716E+09 | 0.135455E+09 | 8987.58 | 0.135446E+09 | 0.00 | 0.00 |
| April | 0.252338E+09 | 80166843.30 | 0.147170E+09 | 822185.82 | 0.146348E+09 | 0.00 | 0.00 |
| May | 0.357296E+09 | 32564688.79 | 0.172610E+09 | 6939233.84 | 0.165670E+09 | 0.00 | 0.00 |
| June | 0.404415E+09 | 10221571.69 | 0.178820E+09 | 12506596.35 | 0.166314E+09 | 0.00 | 0.00 |
| July | 0.438966E+09 | 17052170.17 | 0.186873E+09 | 8688044.55 | 0.178185E+09 | 0.00 | 0.00 |
| August | 0.371223E+09 | 10387090.47 | 0.166270E+09 | 1873332.33 | 0.164397E+09 | 0.00 | 0.00 |
| September | 0.333342E+09 | 24630467.82 | 0.142367E+09 | 28547.29 | 0.142339E+09 | 0.00 | 0.00 |
| October | 0.251085E+09 | 42976319.68 | 0.123193E+09 | 0.00 | 0.123193E+09 | 0.00 | 0.00 |
| November | 0.169015E+09 | 0.101056E+09 | 0.103661E+09 | 0.00 | 0.103661E+09 | 0.00 | 0.00 |
| December | 0.112650E+09 | 0.191204E+09 | 94879756.67 | 0.00 | 94879756.67 | 0.00 | 0.00 |
| Annual Sum or Average | 0.311269E+10 | 0.104746E+10 | 0.164977E+10 | 30866927.75 | 0.161891E+10 | 0.00 | 0.00 |
| Minimum of Months | 98961155.64 | 10221571.69 | 94879756.67 | 0.00 | 94879756.67 | 0.00 | 0.00 |
| Maximum of Months | 0.438966E+09 | 0.228336E+09 | 0.186873E+09 | 12506596.35 | 0.178185E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: G N2 APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 98899355.90 | 0.228368E+09 | 95922893.25 | 0.00 | 95922893.25 | 0.00 | 0.00 |
| February | 0.137261E+09 | 0.164152E+09 | 0.102552E+09 | 0.00 | 0.102552E+09 | 0.00 | 0.00 |
| March | 0.186024E+09 | 0.144725E+09 | 0.135455E+09 | 8987.58 | 0.135446E+09 | 0.00 | 0.00 |
| April | 0.252307E+09 | 80131031.20 | 0.147170E+09 | 822185.82 | 0.146348E+09 | 0.00 | 0.00 |
| May | 0.357274E+09 | 32544238.89 | 0.172610E+09 | 6939233.84 | 0.165670E+09 | 0.00 | 0.00 |
| June | 0.404366E+09 | 10228741.97 | 0.178820E+09 | 12506596.35 | 0.166314E+09 | 0.00 | 0.00 |
| July | 0.438936E+09 | 17050876.93 | 0.186873E+09 | 8688044.55 | 0.178185E+09 | 0.00 | 0.00 |
| August | 0.371218E+09 | 10382024.22 | 0.166270E+09 | 1873332.33 | 0.164397E+09 | 0.00 | 0.00 |
| September | 0.333311E+09 | 24634877.26 | 0.142367E+09 | 28547.29 | 0.142339E+09 | 0.00 | 0.00 |
| October | 0.251058E+09 | 42966087.01 | 0.123193E+09 | 0.00 | 0.123193E+09 | 0.00 | 0.00 |
| November | 0.168988E+09 | 0.101048E+09 | 0.103661E+09 | 0.00 | 0.103661E+09 | 0.00 | 0.00 |
| December | 0.112645E+09 | 0.191150E+09 | 94879756.67 | 0.00 | 94879756.67 | 0.00 | 0.00 |
| Annual Sum or Average | 0.311229E+10 | 0.104738E+10 | 0.164977E+10 | 30866927.75 | 0.161891E+10 | 0.00 | 0.00 |
| Minimum of Months | 98899355.90 | 10228741.97 | 94879756.67 | 0.00 | 94879756.67 | 0.00 | 0.00 |
| Maximum of Months | 0.438936E+09 | 0.228368E+09 | 0.186873E+09 | 12506596.35 | 0.178185E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: G S1 APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.700299E+09 | 0.213744E+09 | 0.447539E+09 | 0.289548E+09 | 0.157992E+09 | 0.00 | 0.00 |
| February | 0.611141E+09 | 0.157787E+09 | 0.368860E+09 | 0.213589E+09 | 0.155271E+09 | 0.00 | 0.00 |
| March | 0.514393E+09 | 0.140329E+09 | 0.305895E+09 | 0.125166E+09 | 0.180729E+09 | 0.00 | 0.00 |
| April | 0.411880E+09 | 83205132.93 | 0.218759E+09 | 48762672.05 | 0.169997E+09 | 0.00 | 0.00 |
| May | 0.359205E+09 | 31922266.00 | 0.171985E+09 | 4985512.72 | 0.166999E+09 | 0.00 | 0.00 |
| June | 0.359852E+09 | 10546151.75 | 0.157580E+09 | 438652.82 | 0.157142E+09 | 0.00 | 0.00 |
| July | 0.413570E+09 | 17343976.34 | 0.174576E+09 | 1932094.98 | 0.172644E+09 | 0.00 | 0.00 |
| August | 0.440608E+09 | 10958288.19 | 0.196815E+09 | 15792809.78 | 0.181022E+09 | 0.00 | 0.00 |
| September | 0.547929E+09 | 25972621.10 | 0.247423E+09 | 62495235.59 | 0.184928E+09 | 0.00 | 0.00 |
| October | 0.675424E+09 | 46304788.63 | 0.348736E+09 | 0.163993E+09 | 0.184743E+09 | 0.00 | 0.00 |
| November | 0.667241E+09 | 98962860.64 | 0.385200E+09 | 0.215831E+09 | 0.169369E+09 | 0.00 | 0.00 |
| December | 0.695050E+09 | 0.184711E+09 | 0.433407E+09 | 0.272909E+09 | 0.160498E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.639659E+10 | 0.102179E+10 | 0.345677E+10 | 0.141544E+10 | 0.204133E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.359205E+09 | 10546151.75 | 0.157580E+09 | 438652.82 | 0.155271E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.700299E+09 | 0.213744E+09 | 0.447539E+09 | 0.289548E+09 | 0.184928E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: G S2 APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.698992E+09 | 0.215756E+09 | 0.447539E+09 | 0.289548E+09 | 0.157992E+09 | 0.00 | 0.00 |
| February | 0.609975E+09 | 0.159361E+09 | 0.368860E+09 | 0.213589E+09 | 0.155271E+09 | 0.00 | 0.00 |
| March | 0.512929E+09 | 0.142201E+09 | 0.305895E+09 | 0.125166E+09 | 0.180729E+09 | 0.00 | 0.00 |
| April | 0.410126E+09 | 85266258.36 | 0.218759E+09 | 48762672.05 | 0.169997E+09 | 0.00 | 0.00 |
| May | 0.356682E+09 | 33869998.12 | 0.171985E+09 | 4985512.72 | 0.166999E+09 | 0.00 | 0.00 |
| June | 0.356310E+09 | 11673721.89 | 0.157580E+09 | 438652.82 | 0.157142E+09 | 0.00 | 0.00 |
| July | 0.410067E+09 | 18873470.18 | 0.174576E+09 | 1932094.98 | 0.172644E+09 | 0.00 | 0.00 |
| August | 0.436870E+09 | 12197308.69 | 0.196815E+09 | 15792809.78 | 0.181022E+09 | 0.00 | 0.00 |
| September | 0.544597E+09 | 27458168.86 | 0.247423E+09 | 62495235.59 | 0.184928E+09 | 0.00 | 0.00 |
| October | 0.672906E+09 | 48766807.86 | 0.348736E+09 | 0.163993E+09 | 0.184743E+09 | 0.00 | 0.00 |
| November | 0.665451E+09 | 0.101137E+09 | 0.385200E+09 | 0.215831E+09 | 0.169369E+09 | 0.00 | 0.00 |
| December | 0.693803E+09 | 0.186738E+09 | 0.433407E+09 | 0.272909E+09 | 0.160498E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.636871E+10 | 0.104330E+10 | 0.345677E+10 | 0.141544E+10 | 0.204133E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.356310E+09 | 11673721.89 | 0.157580E+09 | 438652.82 | 0.155271E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.698992E+09 | 0.215756E+09 | 0.447539E+09 | 0.289548E+09 | 0.184928E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: M SW APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.880713E+09 | 0.350945E+09 | 0.584756E+09 | 0.349010E+09 | 0.235746E+09 | 0.00 | 0.00 |
| February | 0.845418E+09 | 0.260883E+09 | 0.523558E+09 | 0.283833E+09 | 0.239725E+09 | 0.00 | 0.00 |
| March | 0.841479E+09 | 0.233407E+09 | 0.519083E+09 | 0.222694E+09 | 0.296389E+09 | 0.00 | 0.00 |
| April | 0.798068E+09 | 0.139002E+09 | 0.444720E+09 | 0.153137E+09 | 0.291583E+09 | 0.00 | 0.00 |
| May | 0.764755E+09 | 54466733.47 | 0.385797E+09 | 87529673.31 | 0.298268E+09 | 0.00 | 0.00 |
| June | 0.720139E+09 | 17129802.14 | 0.332798E+09 | 49671949.89 | 0.283126E+09 | 0.00 | 0.00 |
| July | 0.839352E+09 | 27170252.41 | 0.376766E+09 | 64600730.47 | 0.312165E+09 | 0.00 | 0.00 |
| August | 0.848102E+09 | 16569580.43 | 0.398389E+09 | 81373257.56 | 0.317016E+09 | 0.00 | 0.00 |
| September | 0.896149E+09 | 39703518.61 | 0.413759E+09 | 0.111590E+09 | 0.302169E+09 | 0.00 | 0.00 |
| October | 0.998129E+09 | 71298405.90 | 0.519661E+09 | 0.230642E+09 | 0.289019E+09 | 0.00 | 0.00 |
| November | 0.894964E+09 | 0.159375E+09 | 0.521519E+09 | 0.265703E+09 | 0.255816E+09 | 0.00 | 0.00 |
| December | 0.900059E+09 | 0.300900E+09 | 0.574988E+09 | 0.336350E+09 | 0.238639E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.102273E+11 | 0.167085E+10 | 0.559579E+10 | 0.223613E+10 | 0.335966E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.720139E+09 | 16569580.43 | 0.332798E+09 | 49671949.89 | 0.235746E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.998129E+09 | 0.350945E+09 | 0.584756E+09 | 0.349010E+09 | 0.317016E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: M NW APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.290880E+09 | 0.362016E+09 | 0.233139E+09 | 59462026.64 | 0.173677E+09 | 0.00 | 0.00 |
| February | 0.381070E+09 | 0.264675E+09 | 0.257250E+09 | 70244097.88 | 0.187006E+09 | 0.00 | 0.00 |
| March | 0.519744E+09 | 0.237197E+09 | 0.348643E+09 | 97536627.56 | 0.251107E+09 | 0.00 | 0.00 |
| April | 0.641226E+09 | 0.136381E+09 | 0.373131E+09 | 0.105196E+09 | 0.267935E+09 | 0.00 | 0.00 |
| May | 0.762585E+09 | 55145079.14 | 0.386422E+09 | 89483394.43 | 0.296939E+09 | 0.00 | 0.00 |
| June | 0.763509E+09 | 16598886.03 | 0.354038E+09 | 61739893.42 | 0.292298E+09 | 0.00 | 0.00 |
| July | 0.864190E+09 | 26768048.94 | 0.389063E+09 | 71356680.04 | 0.317706E+09 | 0.00 | 0.00 |
| August | 0.779500E+09 | 15950605.09 | 0.367845E+09 | 67453780.11 | 0.300391E+09 | 0.00 | 0.00 |
| September | 0.684617E+09 | 38223929.05 | 0.308703E+09 | 49123332.24 | 0.259580E+09 | 0.00 | 0.00 |
| October | 0.579266E+09 | 67461288.27 | 0.294118E+09 | 66648864.77 | 0.227469E+09 | 0.00 | 0.00 |
| November | 0.404921E+09 | 0.161116E+09 | 0.239980E+09 | 49872369.86 | 0.190108E+09 | 0.00 | 0.00 |
| December | 0.325714E+09 | 0.300656E+09 | 0.236461E+09 | 63440405.52 | 0.173021E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.699722E+10 | 0.168219E+10 | 0.378879E+10 | 0.851558E+09 | 0.293724E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.290880E+09 | 15950605.09 | 0.233139E+09 | 49123332.24 | 0.173021E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.864190E+09 | 0.362016E+09 | 0.389063E+09 | 0.105196E+09 | 0.317706E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: M SE APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.903421E+09 | 0.345383E+09 | 0.599912E+09 | 0.362763E+09 | 0.237149E+09 | 0.00 | 0.00 |
| February | 0.843112E+09 | 0.253355E+09 | 0.527670E+09 | 0.287106E+09 | 0.240564E+09 | 0.00 | 0.00 |
| March | 0.829118E+09 | 0.222012E+09 | 0.520327E+09 | 0.226357E+09 | 0.293970E+09 | 0.00 | 0.00 |
| April | 0.793004E+09 | 0.134720E+09 | 0.445075E+09 | 0.150065E+09 | 0.295010E+09 | 0.00 | 0.00 |
| May | 0.771900E+09 | 50691624.51 | 0.392507E+09 | 93057809.88 | 0.299449E+09 | 0.00 | 0.00 |
| June | 0.780398E+09 | 16072519.52 | 0.367693E+09 | 81160700.83 | 0.286532E+09 | 0.00 | 0.00 |
| July | 0.876335E+09 | 26955118.15 | 0.398058E+09 | 82784986.09 | 0.315273E+09 | 0.00 | 0.00 |
| August | 0.853217E+09 | 16034544.10 | 0.400690E+09 | 83904367.31 | 0.316785E+09 | 0.00 | 0.00 |
| September | 0.937696E+09 | 39251600.87 | 0.437597E+09 | 0.131113E+09 | 0.306484E+09 | 0.00 | 0.00 |
| October | 0.101404E+10 | 69098422.51 | 0.529809E+09 | 0.241888E+09 | 0.287921E+09 | 0.00 | 0.00 |
| November | 0.900958E+09 | 0.154970E+09 | 0.527521E+09 | 0.272586E+09 | 0.254935E+09 | 0.00 | 0.00 |
| December | 0.857682E+09 | 0.296659E+09 | 0.552371E+09 | 0.315012E+09 | 0.237358E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.103609E+11 | 0.162520E+10 | 0.569923E+10 | 0.232780E+10 | 0.337143E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.771900E+09 | 16034544.10 | 0.367693E+09 | 81160700.83 | 0.237149E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.101404E+10 | 0.345383E+09 | 0.599912E+09 | 0.362763E+09 | 0.316785E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: M NE APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.300082E+09 | 0.344384E+09 | 0.248295E+09 | 73214687.62 | 0.175081E+09 | 0.00 | 0.00 |
| February | 0.369499E+09 | 0.247966E+09 | 0.261362E+09 | 73517497.32 | 0.187845E+09 | 0.00 | 0.00 |
| March | 0.499610E+09 | 0.218772E+09 | 0.349888E+09 | 0.101200E+09 | 0.248687E+09 | 0.00 | 0.00 |
| April | 0.636473E+09 | 0.132321E+09 | 0.373486E+09 | 0.102125E+09 | 0.271361E+09 | 0.00 | 0.00 |
| May | 0.770804E+09 | 52451230.95 | 0.393131E+09 | 95011531.00 | 0.298120E+09 | 0.00 | 0.00 |
| June | 0.824422E+09 | 16167415.94 | 0.388933E+09 | 93228644.36 | 0.295704E+09 | 0.00 | 0.00 |
| July | 0.901457E+09 | 26849699.60 | 0.410355E+09 | 89540935.66 | 0.320814E+09 | 0.00 | 0.00 |
| August | 0.784720E+09 | 15482863.91 | 0.370145E+09 | 69984889.86 | 0.300161E+09 | 0.00 | 0.00 |
| September | 0.726287E+09 | 37859454.70 | 0.332541E+09 | 68646728.43 | 0.263895E+09 | 0.00 | 0.00 |
| October | 0.594275E+09 | 64295438.44 | 0.304266E+09 | 77895027.35 | 0.226371E+09 | 0.00 | 0.00 |
| November | 0.404619E+09 | 0.150628E+09 | 0.245983E+09 | 56755460.23 | 0.189227E+09 | 0.00 | 0.00 |
| December | 0.280627E+09 | 0.293506E+09 | 0.213843E+09 | 42102991.35 | 0.171740E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.709287E+10 | 0.160068E+10 | 0.389223E+10 | 0.943223E+09 | 0.294901E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.280627E+09 | 15482863.91 | 0.213843E+09 | 42102991.35 | 0.171740E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.901457E+09 | 0.344384E+09 | 0.410355E+09 | 0.102125E+09 | 0.320814E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: M N1 APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 99070215.23 | 0.227910E+09 | 95922893.25 | 0.00 | 95922893.25 | 0.00 | 0.00 |
| February | 0.137039E+09 | 0.163987E+09 | 0.102552E+09 | 0.00 | 0.102552E+09 | 0.00 | 0.00 |
| March | 0.184103E+09 | 0.146388E+09 | 0.135455E+09 | 8987.58 | 0.135446E+09 | 0.00 | 0.00 |
| April | 0.251178E+09 | 80228078.95 | 0.147170E+09 | 822185.82 | 0.146348E+09 | 0.00 | 0.00 |
| May | 0.357674E+09 | 31185231.90 | 0.172610E+09 | 6939233.84 | 0.165670E+09 | 0.00 | 0.00 |
| June | 0.406610E+09 | 9239761.82 | 0.178820E+09 | 12506596.35 | 0.166314E+09 | 0.00 | 0.00 |
| July | 0.442754E+09 | 15115209.00 | 0.186873E+09 | 8688044.55 | 0.178185E+09 | 0.00 | 0.00 |
| August | 0.377007E+09 | 8810292.16 | 0.166270E+09 | 1873332.33 | 0.164397E+09 | 0.00 | 0.00 |
| September | 0.338757E+09 | 22271347.62 | 0.142367E+09 | 28547.29 | 0.142339E+09 | 0.00 | 0.00 |
| October | 0.255056E+09 | 38883249.53 | 0.123193E+09 | 0.00 | 0.123193E+09 | 0.00 | 0.00 |
| November | 0.171048E+09 | 97846205.63 | 0.103661E+09 | 0.00 | 0.103661E+09 | 0.00 | 0.00 |
| December | 0.113336E+09 | 0.189405E+09 | 94879756.67 | 0.00 | 94879756.67 | 0.00 | 0.00 |
| Annual Sum or Average | 0.313363E+10 | 0.103127E+10 | 0.164977E+10 | 30866927.75 | 0.161891E+10 | 0.00 | 0.00 |
| Minimum of Months | 99070215.23 | 8810292.16 | 94879756.67 | 0.00 | 94879756.67 | 0.00 | 0.00 |
| Maximum of Months | 0.442754E+09 | 0.227910E+09 | 0.186873E+09 | 12506596.35 | 0.178185E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: M N2 APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 98995186.13 | 0.227946E+09 | 95922893.25 | 0.00 | 95922893.25 | 0.00 | 0.00 |
| February | 0.136986E+09 | 0.163978E+09 | 0.102552E+09 | 0.00 | 0.102552E+09 | 0.00 | 0.00 |
| March | 0.184018E+09 | 0.146401E+09 | 0.135455E+09 | 8987.58 | 0.135446E+09 | 0.00 | 0.00 |
| April | 0.251145E+09 | 80190121.93 | 0.147170E+09 | 822185.82 | 0.146348E+09 | 0.00 | 0.00 |
| May | 0.357652E+09 | 31162730.49 | 0.172610E+09 | 6939233.84 | 0.165670E+09 | 0.00 | 0.00 |
| June | 0.406574E+09 | 9242798.63 | 0.178820E+09 | 12506596.35 | 0.166314E+09 | 0.00 | 0.00 |
| July | 0.442727E+09 | 15111366.58 | 0.186873E+09 | 8688044.55 | 0.178185E+09 | 0.00 | 0.00 |
| August | 0.377003E+09 | 8805036.77 | 0.166270E+09 | 1873332.33 | 0.164397E+09 | 0.00 | 0.00 |
| September | 0.338729E+09 | 22272432.00 | 0.142367E+09 | 28547.29 | 0.142339E+09 | 0.00 | 0.00 |
| October | 0.255030E+09 | 38869291.32 | 0.123193E+09 | 0.00 | 0.123193E+09 | 0.00 | 0.00 |
| November | 0.171015E+09 | 97840391.93 | 0.103661E+09 | 0.00 | 0.103661E+09 | 0.00 | 0.00 |
| December | 0.113320E+09 | 0.189357E+09 | 94879756.67 | 0.00 | 94879756.67 | 0.00 | 0.00 |
| Annual Sum or Average | 0.313319E+10 | 0.103118E+10 | 0.164977E+10 | 30866927.75 | 0.161891E+10 | 0.00 | 0.00 |
| Minimum of Months | 98995186.13 | 8805036.77 | 94879756.67 | 0.00 | 94879756.67 | 0.00 | 0.00 |
| Maximum of Months | 0.442727E+09 | 0.227946E+09 | 0.186873E+09 | 12506596.35 | 0.178185E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: M S1 APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.697827E+09 | 0.211544E+09 | 0.447539E+09 | 0.289548E+09 | 0.157992E+09 | 0.00 | 0.00 |
| February | 0.608297E+09 | 0.156613E+09 | 0.368860E+09 | 0.213589E+09 | 0.155271E+09 | 0.00 | 0.00 |
| March | 0.510728E+09 | 0.140357E+09 | 0.305895E+09 | 0.125166E+09 | 0.180729E+09 | 0.00 | 0.00 |
| April | 0.409907E+09 | 82686240.87 | 0.218759E+09 | 48762672.05 | 0.169997E+09 | 0.00 | 0.00 |
| May | 0.359823E+09 | 30345097.52 | 0.171985E+09 | 4985512.72 | 0.166999E+09 | 0.00 | 0.00 |
| June | 0.362538E+09 | 9624240.44 | 0.157580E+09 | 438652.82 | 0.157142E+09 | 0.00 | 0.00 |
| July | 0.417561E+09 | 15472642.13 | 0.174576E+09 | 1932094.98 | 0.172644E+09 | 0.00 | 0.00 |
| August | 0.446301E+09 | 9310816.58 | 0.196815E+09 | 15792809.78 | 0.181022E+09 | 0.00 | 0.00 |
| September | 0.552400E+09 | 23474743.44 | 0.247423E+09 | 62495235.59 | 0.184928E+09 | 0.00 | 0.00 |
| October | 0.677554E+09 | 41542554.79 | 0.348736E+09 | 0.163993E+09 | 0.184743E+09 | 0.00 | 0.00 |
| November | 0.667111E+09 | 94878745.83 | 0.385200E+09 | 0.215831E+09 | 0.169369E+09 | 0.00 | 0.00 |
| December | 0.693011E+09 | 0.181649E+09 | 0.433407E+09 | 0.272909E+09 | 0.160498E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.640306E+10 | 0.997498E+09 | 0.345677E+10 | 0.141544E+10 | 0.204133E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.359823E+09 | 9310816.58 | 0.157580E+09 | 438652.82 | 0.155271E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.697827E+09 | 0.211544E+09 | 0.447539E+09 | 0.289548E+09 | 0.184928E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: M S2 APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.697788E+09 | 0.211537E+09 | 0.447539E+09 | 0.289548E+09 | 0.157992E+09 | 0.00 | 0.00 |
| February | 0.608262E+09 | 0.156597E+09 | 0.368860E+09 | 0.213589E+09 | 0.155271E+09 | 0.00 | 0.00 |
| March | 0.510674E+09 | 0.140329E+09 | 0.305895E+09 | 0.125166E+09 | 0.180729E+09 | 0.00 | 0.00 |
| April | 0.409874E+09 | 82648159.69 | 0.218759E+09 | 48762672.05 | 0.169997E+09 | 0.00 | 0.00 |
| May | 0.359802E+09 | 30323109.71 | 0.171985E+09 | 4985512.72 | 0.166999E+09 | 0.00 | 0.00 |
| June | 0.362501E+09 | 9627739.53 | 0.157580E+09 | 438652.82 | 0.157142E+09 | 0.00 | 0.00 |
| July | 0.417535E+09 | 15468878.74 | 0.174576E+09 | 1932094.98 | 0.172644E+09 | 0.00 | 0.00 |
| August | 0.446298E+09 | 9305425.37 | 0.196815E+09 | 15792809.78 | 0.181022E+09 | 0.00 | 0.00 |
| September | 0.552375E+09 | 23475627.39 | 0.247423E+09 | 62495235.59 | 0.184928E+09 | 0.00 | 0.00 |
| October | 0.677532E+09 | 41529149.29 | 0.348736E+09 | 0.163993E+09 | 0.184743E+09 | 0.00 | 0.00 |
| November | 0.667089E+09 | 94866716.82 | 0.385200E+09 | 0.215831E+09 | 0.169369E+09 | 0.00 | 0.00 |
| December | 0.693004E+09 | 0.181612E+09 | 0.433407E+09 | 0.272909E+09 | 0.160498E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.640273E+10 | 0.997320E+09 | 0.345677E+10 | 0.141544E+10 | 0.204133E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.359802E+09 | 9305425.37 | 0.157580E+09 | 438652.82 | 0.155271E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.697788E+09 | 0.211537E+09 | 0.447539E+09 | 0.289548E+09 | 0.184928E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: T SW APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.880822E+09 | 0.318208E+09 | 0.584756E+09 | 0.349010E+09 | 0.235746E+09 | 0.00 | 0.00 |
| February | 0.838659E+09 | 0.239575E+09 | 0.523558E+09 | 0.283833E+09 | 0.239725E+09 | 0.00 | 0.00 |
| March | 0.831400E+09 | 0.214660E+09 | 0.519083E+09 | 0.222694E+09 | 0.296389E+09 | 0.00 | 0.00 |
| April | 0.780057E+09 | 0.133592E+09 | 0.444720E+09 | 0.153137E+09 | 0.291583E+09 | 0.00 | 0.00 |
| May | 0.743584E+09 | 53414232.50 | 0.385797E+09 | 87529673.31 | 0.298268E+09 | 0.00 | 0.00 |
| June | 0.697783E+09 | 16556297.30 | 0.332798E+09 | 49671949.89 | 0.283126E+09 | 0.00 | 0.00 |
| July | 0.814623E+09 | 26301899.40 | 0.376766E+09 | 64600730.47 | 0.312165E+09 | 0.00 | 0.00 |
| August | 0.825780E+09 | 16254896.96 | 0.398389E+09 | 81373257.56 | 0.317016E+09 | 0.00 | 0.00 |
| September | 0.873289E+09 | 37921307.54 | 0.413759E+09 | 0.111590E+09 | 0.302169E+09 | 0.00 | 0.00 |
| October | 0.978688E+09 | 68291503.51 | 0.519661E+09 | 0.230642E+09 | 0.289019E+09 | 0.00 | 0.00 |
| November | 0.883166E+09 | 0.147839E+09 | 0.521519E+09 | 0.265703E+09 | 0.255816E+09 | 0.00 | 0.00 |
| December | 0.895677E+09 | 0.274069E+09 | 0.574988E+09 | 0.336350E+09 | 0.238639E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.100435E+11 | 0.154668E+10 | 0.559579E+10 | 0.223613E+10 | 0.335966E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.697783E+09 | 16254896.96 | 0.332798E+09 | 49671949.89 | 0.235746E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.978688E+09 | 0.318208E+09 | 0.584756E+09 | 0.349010E+09 | 0.317016E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: T NW APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.297654E+09 | 0.319507E+09 | 0.233139E+09 | 59462026.64 | 0.173677E+09 | 0.00 | 0.00 |
| February | 0.379246E+09 | 0.240503E+09 | 0.257250E+09 | 70244097.88 | 0.187006E+09 | 0.00 | 0.00 |
| March | 0.513416E+09 | 0.215783E+09 | 0.348643E+09 | 97536627.56 | 0.251107E+09 | 0.00 | 0.00 |
| April | 0.625699E+09 | 0.131446E+09 | 0.373131E+09 | 0.105196E+09 | 0.267935E+09 | 0.00 | 0.00 |
| May | 0.742046E+09 | 54589745.51 | 0.386422E+09 | 89483394.43 | 0.296939E+09 | 0.00 | 0.00 |
| June | 0.740760E+09 | 16100629.30 | 0.354038E+09 | 61739893.42 | 0.292298E+09 | 0.00 | 0.00 |
| July | 0.839370E+09 | 25947203.74 | 0.389063E+09 | 71356680.04 | 0.317706E+09 | 0.00 | 0.00 |
| August | 0.758141E+09 | 15668261.43 | 0.367845E+09 | 67453780.11 | 0.300391E+09 | 0.00 | 0.00 |
| September | 0.664179E+09 | 36676464.86 | 0.308703E+09 | 49123332.24 | 0.259580E+09 | 0.00 | 0.00 |
| October | 0.564388E+09 | 65022890.74 | 0.294118E+09 | 66648864.77 | 0.227469E+09 | 0.00 | 0.00 |
| November | 0.398497E+09 | 0.147958E+09 | 0.239980E+09 | 49872369.86 | 0.190108E+09 | 0.00 | 0.00 |
| December | 0.328537E+09 | 0.267071E+09 | 0.236461E+09 | 63440405.52 | 0.173021E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.685193E+10 | 0.153627E+10 | 0.378879E+10 | 0.851558E+09 | 0.293724E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.297654E+09 | 15668261.43 | 0.233139E+09 | 49123332.24 | 0.173021E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.839370E+09 | 0.319507E+09 | 0.389063E+09 | 0.105196E+09 | 0.317706E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: T SE APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.902573E+09 | 0.313432E+09 | 0.599912E+09 | 0.362763E+09 | 0.237149E+09 | 0.00 | 0.00 |
| February | 0.836266E+09 | 0.232761E+09 | 0.527670E+09 | 0.287106E+09 | 0.240564E+09 | 0.00 | 0.00 |
| March | 0.819225E+09 | 0.204922E+09 | 0.520327E+09 | 0.226357E+09 | 0.293970E+09 | 0.00 | 0.00 |
| April | 0.774397E+09 | 0.129263E+09 | 0.445075E+09 | 0.150065E+09 | 0.295010E+09 | 0.00 | 0.00 |
| May | 0.749717E+09 | 49092692.35 | 0.392507E+09 | 93057809.88 | 0.299449E+09 | 0.00 | 0.00 |
| June | 0.757226E+09 | 15463945.25 | 0.367693E+09 | 81160700.83 | 0.286532E+09 | 0.00 | 0.00 |
| July | 0.851003E+09 | 26000834.09 | 0.398058E+09 | 82784986.09 | 0.315273E+09 | 0.00 | 0.00 |
| August | 0.830587E+09 | 15567865.40 | 0.400690E+09 | 83904367.31 | 0.316785E+09 | 0.00 | 0.00 |
| September | 0.914258E+09 | 37492567.23 | 0.437597E+09 | 0.131113E+09 | 0.306484E+09 | 0.00 | 0.00 |
| October | 0.993768E+09 | 65589998.36 | 0.529809E+09 | 0.241888E+09 | 0.287921E+09 | 0.00 | 0.00 |
| November | 0.888631E+09 | 0.143551E+09 | 0.527521E+09 | 0.272586E+09 | 0.254935E+09 | 0.00 | 0.00 |
| December | 0.852925E+09 | 0.269691E+09 | 0.552371E+09 | 0.315012E+09 | 0.237358E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.101706E+11 | 0.150283E+10 | 0.569923E+10 | 0.232780E+10 | 0.337143E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.749717E+09 | 15463945.25 | 0.367693E+09 | 81160700.83 | 0.237149E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.993768E+09 | 0.313432E+09 | 0.599912E+09 | 0.362763E+09 | 0.316785E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: T NE APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.309872E+09 | 0.306100E+09 | 0.248295E+09 | 73214687.62 | 0.175081E+09 | 0.00 | 0.00 |
| February | 0.369432E+09 | 0.226320E+09 | 0.261362E+09 | 73517497.32 | 0.187845E+09 | 0.00 | 0.00 |
| March | 0.495979E+09 | 0.200348E+09 | 0.349888E+09 | 0.101200E+09 | 0.248687E+09 | 0.00 | 0.00 |
| April | 0.620094E+09 | 0.127067E+09 | 0.373486E+09 | 0.102125E+09 | 0.271361E+09 | 0.00 | 0.00 |
| May | 0.749075E+09 | 51158623.91 | 0.393131E+09 | 95011531.00 | 0.298120E+09 | 0.00 | 0.00 |
| June | 0.800747E+09 | 15502399.87 | 0.388933E+09 | 93228644.36 | 0.295704E+09 | 0.00 | 0.00 |
| July | 0.875929E+09 | 25849703.77 | 0.410355E+09 | 89540935.66 | 0.320814E+09 | 0.00 | 0.00 |
| August | 0.763061E+09 | 15019029.92 | 0.370145E+09 | 69984889.86 | 0.300161E+09 | 0.00 | 0.00 |
| September | 0.705276E+09 | 36321266.48 | 0.332541E+09 | 68646728.43 | 0.263895E+09 | 0.00 | 0.00 |
| October | 0.578688E+09 | 61467716.46 | 0.304266E+09 | 77895027.35 | 0.226371E+09 | 0.00 | 0.00 |
| November | 0.398670E+09 | 0.138652E+09 | 0.245983E+09 | 56755460.23 | 0.189227E+09 | 0.00 | 0.00 |
| December | 0.285146E+09 | 0.260713E+09 | 0.213843E+09 | 42102991.35 | 0.171740E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.695197E+10 | 0.146452E+10 | 0.389223E+10 | 0.943223E+09 | 0.294901E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.285146E+09 | 15019029.92 | 0.213843E+09 | 42102991.35 | 0.171740E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.875929E+09 | 0.306100E+09 | 0.410355E+09 | 0.102125E+09 | 0.320814E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: T N1 APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.103234E+09 | 0.203529E+09 | 95922893.25 | 0.00 | 95922893.25 | 0.00 | 0.00 |
| February | 0.137307E+09 | 0.149976E+09 | 0.102552E+09 | 0.00 | 0.102552E+09 | 0.00 | 0.00 |
| March | 0.182239E+09 | 0.133829E+09 | 0.135455E+09 | 8987.58 | 0.135446E+09 | 0.00 | 0.00 |
| April | 0.243517E+09 | 78416826.46 | 0.147170E+09 | 822185.82 | 0.146348E+09 | 0.00 | 0.00 |
| May | 0.347097E+09 | 31337654.90 | 0.172610E+09 | 6939233.84 | 0.165670E+09 | 0.00 | 0.00 |
| June | 0.394427E+09 | 9218730.46 | 0.178820E+09 | 12506596.35 | 0.166314E+09 | 0.00 | 0.00 |
| July | 0.429655E+09 | 15039870.70 | 0.186873E+09 | 8688044.55 | 0.178185E+09 | 0.00 | 0.00 |
| August | 0.365776E+09 | 8898295.79 | 0.166270E+09 | 1873332.33 | 0.164397E+09 | 0.00 | 0.00 |
| September | 0.328073E+09 | 21809363.21 | 0.142367E+09 | 28547.29 | 0.142339E+09 | 0.00 | 0.00 |
| October | 0.247571E+09 | 37935907.11 | 0.123193E+09 | 0.00 | 0.123193E+09 | 0.00 | 0.00 |
| November | 0.168154E+09 | 90991032.26 | 0.103661E+09 | 0.00 | 0.103661E+09 | 0.00 | 0.00 |
| December | 0.115827E+09 | 0.168901E+09 | 94879756.67 | 0.00 | 94879756.67 | 0.00 | 0.00 |
| Annual Sum or Average | 0.306288E+10 | 0.949883E+09 | 0.164977E+10 | 30866927.75 | 0.161891E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.103234E+09 | 8898295.79 | 94879756.67 | 0.00 | 94879756.67 | 0.00 | 0.00 |
| Maximum of Months | 0.429655E+09 | 0.203529E+09 | 0.186873E+09 | 12506596.35 | 0.178185E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: T N2 APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.102976E+09 | 0.203471E+09 | 95922893.25 | 0.00 | 95922893.25 | 0.00 | 0.00 |
| February | 0.137133E+09 | 0.149866E+09 | 0.102552E+09 | 0.00 | 0.102552E+09 | 0.00 | 0.00 |
| March | 0.182001E+09 | 0.133707E+09 | 0.135455E+09 | 8987.58 | 0.135446E+09 | 0.00 | 0.00 |
| April | 0.243421E+09 | 78306946.04 | 0.147170E+09 | 822185.82 | 0.146348E+09 | 0.00 | 0.00 |
| May | 0.347042E+09 | 31277196.89 | 0.172610E+09 | 6939233.84 | 0.165670E+09 | 0.00 | 0.00 |
| June | 0.394375E+09 | 9214142.60 | 0.178820E+09 | 12506596.35 | 0.166314E+09 | 0.00 | 0.00 |
| July | 0.429612E+09 | 15023057.38 | 0.186873E+09 | 8688044.55 | 0.178185E+09 | 0.00 | 0.00 |
| August | 0.365771E+09 | 8883428.38 | 0.166270E+09 | 1873332.33 | 0.164397E+09 | 0.00 | 0.00 |
| September | 0.328029E+09 | 21800637.59 | 0.142367E+09 | 28547.29 | 0.142339E+09 | 0.00 | 0.00 |
| October | 0.247513E+09 | 37889356.38 | 0.123193E+09 | 0.00 | 0.123193E+09 | 0.00 | 0.00 |
| November | 0.168054E+09 | 90952472.87 | 0.103661E+09 | 0.00 | 0.103661E+09 | 0.00 | 0.00 |
| December | 0.115738E+09 | 0.168712E+09 | 94879756.67 | 0.00 | 94879756.67 | 0.00 | 0.00 |
| Annual Sum or Average | 0.306167E+10 | 0.949103E+09 | 0.164977E+10 | 30866927.75 | 0.161891E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.102976E+09 | 8883428.38 | 94879756.67 | 0.00 | 94879756.67 | 0.00 | 0.00 |
| Maximum of Months | 0.429612E+09 | 0.203471E+09 | 0.186873E+09 | 12506596.35 | 0.178185E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: T S1 APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.697274E+09 | 0.196376E+09 | 0.447539E+09 | 0.289548E+09 | 0.157992E+09 | 0.00 | 0.00 |
| February | 0.604726E+09 | 0.146256E+09 | 0.368860E+09 | 0.213589E+09 | 0.155271E+09 | 0.00 | 0.00 |
| March | 0.505869E+09 | 0.131179E+09 | 0.305895E+09 | 0.125166E+09 | 0.180729E+09 | 0.00 | 0.00 |
| April | 0.400586E+09 | 80662366.72 | 0.218759E+09 | 48762672.05 | 0.169997E+09 | 0.00 | 0.00 |
| May | 0.348733E+09 | 30123272.29 | 0.171985E+09 | 4985512.72 | 0.166999E+09 | 0.00 | 0.00 |
| June | 0.350634E+09 | 9579540.40 | 0.157580E+09 | 438652.82 | 0.157142E+09 | 0.00 | 0.00 |
| July | 0.404517E+09 | 15409047.43 | 0.174576E+09 | 1932094.98 | 0.172644E+09 | 0.00 | 0.00 |
| August | 0.434382E+09 | 9417588.09 | 0.196815E+09 | 15792809.78 | 0.181022E+09 | 0.00 | 0.00 |
| September | 0.539978E+09 | 22866830.62 | 0.247423E+09 | 62495235.59 | 0.184928E+09 | 0.00 | 0.00 |
| October | 0.666811E+09 | 40247957.52 | 0.348736E+09 | 0.163993E+09 | 0.184743E+09 | 0.00 | 0.00 |
| November | 0.660340E+09 | 89560757.42 | 0.385200E+09 | 0.215831E+09 | 0.169369E+09 | 0.00 | 0.00 |
| December | 0.690269E+09 | 0.168476E+09 | 0.433407E+09 | 0.272909E+09 | 0.160498E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.630412E+10 | 0.940155E+09 | 0.345677E+10 | 0.141544E+10 | 0.204133E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.348733E+09 | 9417588.09 | 0.157580E+09 | 438652.82 | 0.155271E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.697274E+09 | 0.196376E+09 | 0.447539E+09 | 0.289548E+09 | 0.184928E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: T S2 APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.697122E+09 | 0.196305E+09 | 0.447539E+09 | 0.289548E+09 | 0.157992E+09 | 0.00 | 0.00 |
| February | 0.604612E+09 | 0.146166E+09 | 0.368860E+09 | 0.213589E+09 | 0.155271E+09 | 0.00 | 0.00 |
| March | 0.505673E+09 | 0.131072E+09 | 0.305895E+09 | 0.125166E+09 | 0.180729E+09 | 0.00 | 0.00 |
| April | 0.400491E+09 | 80552346.69 | 0.218759E+09 | 48762672.05 | 0.169997E+09 | 0.00 | 0.00 |
| May | 0.348683E+09 | 30066243.27 | 0.171985E+09 | 4985512.72 | 0.166999E+09 | 0.00 | 0.00 |
| June | 0.350580E+09 | 9575636.54 | 0.157580E+09 | 438652.82 | 0.157142E+09 | 0.00 | 0.00 |
| July | 0.404473E+09 | 15391915.13 | 0.174576E+09 | 1932094.98 | 0.172644E+09 | 0.00 | 0.00 |
| August | 0.434375E+09 | 9401896.32 | 0.196815E+09 | 15792809.78 | 0.181022E+09 | 0.00 | 0.00 |
| September | 0.539938E+09 | 22858084.87 | 0.247423E+09 | 62495235.59 | 0.184928E+09 | 0.00 | 0.00 |
| October | 0.666763E+09 | 40205496.31 | 0.348736E+09 | 0.163993E+09 | 0.184743E+09 | 0.00 | 0.00 |
| November | 0.660272E+09 | 89519068.22 | 0.385200E+09 | 0.215831E+09 | 0.169369E+09 | 0.00 | 0.00 |
| December | 0.690206E+09 | 0.168379E+09 | 0.433407E+09 | 0.272909E+09 | 0.160498E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.630319E+10 | 0.939492E+09 | 0.345677E+10 | 0.141544E+10 | 0.204133E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.348683E+09 | 9401896.32 | 0.157580E+09 | 438652.82 | 0.155271E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.697122E+09 | 0.196305E+09 | 0.447539E+09 | 0.289548E+09 | 0.184928E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: T CORRIDOR
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 49555269.00 | 35778971.23 | 36562423.52 | 17568162.31 | 18994261.21 | 0.00 | 0.00 |
| February | 54854647.83 | 26933233.70 | 38107057.52 | 17640822.73 | 20466234.79 | 0.00 | 0.00 |
| March | 74427284.05 | 24487404.44 | 51453936.11 | 24281312.48 | 27172623.64 | 0.00 | 0.00 |
| April | 87219194.77 | 16953247.54 | 54305359.94 | 24307919.67 | 29997440.27 | 0.00 | 0.00 |
| May | 92190673.53 | 8871048.25 | 52915052.50 | 21133306.19 | 31781746.30 | 0.00 | 0.00 |
| June | 91667758.58 | 3690681.22 | 50417375.43 | 19369583.99 | 31047791.44 | 0.00 | 0.00 |
| July | 0.102008E+09 | 5629276.68 | 53625545.36 | 19400980.32 | 34224565.03 | 0.00 | 0.00 |
| August | 89367938.12 | 4229597.34 | 48920698.37 | 16343645.47 | 32577052.90 | 0.00 | 0.00 |
| September | 84767104.33 | 6153556.19 | 45633079.38 | 16465211.87 | 29167867.51 | 0.00 | 0.00 |
| October | 75627049.55 | 10541668.23 | 43449306.57 | 18691228.88 | 24758077.70 | 0.00 | 0.00 |
| November | 52858901.49 | 18199285.06 | 34150586.14 | 13618703.70 | 20531882.44 | 0.00 | 0.00 |
| December | 38505192.55 | 31595082.78 | 28545790.45 | 10102784.15 | 18443006.30 | 0.00 | 0.00 |
| Annual Sum or Average | 0.893049E+09 | 0.193063E+09 | 0.538086E+09 | 0.218924E+09 | 0.319163E+09 | 0.00 | 0.00 |
| Minimum of Months | 38505192.55 | 3690681.22 | 28545790.45 | 10102784.15 | 18443006.30 | 0.00 | 0.00 |
| Maximum of Months | 0.102008E+09 | 35778971.23 | 54305359.94 | 24307919.67 | 34224565.03 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: G CORRIDOR
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.143830E+09 | 0.114431E+09 | 0.108892E+09 | 52322359.42 | 56569636.87 | 0.00 | 0.00 |
| February | 0.161974E+09 | 85504563.81 | 0.113492E+09 | 52538760.24 | 60953540.52 | 0.00 | 0.00 |
| March | 0.221938E+09 | 77141347.17 | 0.153243E+09 | 72315791.28 | 80926835.46 | 0.00 | 0.00 |
| April | 0.260146E+09 | 54326390.61 | 0.161735E+09 | 72395034.13 | 89339842.40 | 0.00 | 0.00 |
| May | 0.272388E+09 | 31265836.30 | 0.157594E+09 | 62940245.14 | 94653949.81 | 0.00 | 0.00 |
| June | 0.268133E+09 | 14985089.49 | 0.150155E+09 | 57687441.50 | 92468049.56 | 0.00 | 0.00 |
| July | 0.297165E+09 | 22793867.89 | 0.159710E+09 | 57780947.60 | 0.101929E+09 | 0.00 | 0.00 |
| August | 0.258706E+09 | 19143982.49 | 0.145698E+09 | 48675443.54 | 97022570.76 | 0.00 | 0.00 |
| September | 0.245560E+09 | 24311554.60 | 0.135907E+09 | 49037498.53 | 86869168.25 | 0.00 | 0.00 |
| October | 0.219976E+09 | 40377029.85 | 0.129403E+09 | 55667131.16 | 73735716.76 | 0.00 | 0.00 |
| November | 0.154232E+09 | 62293627.16 | 0.101709E+09 | 40559888.82 | 61149055.55 | 0.00 | 0.00 |
| December | 0.111495E+09 | 0.101823E+09 | 85016467.95 | 30088605.41 | 54927862.54 | 0.00 | 0.00 |
| Annual Sum or Average | 0.261554E+10 | 0.648397E+09 | 0.160255E+10 | 0.652009E+09 | 0.950546E+09 | 0.00 | 0.00 |
| Minimum of Months | 0.111495E+09 | 14985089.49 | 85016467.95 | 30088605.41 | 54927862.54 | 0.00 | 0.00 |
| Maximum of Months | 0.297165E+09 | 0.114431E+09 | 0.161735E+09 | 72395034.13 | 0.101929E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: M CORRIDOR
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 47366474.18 | 39510105.51 | 36562423.52 | 17568162.31 | 18994261.21 | 0.00 | 0.00 |
| February | 53670868.49 | 29221630.98 | 38107057.52 | 17640822.73 | 20466234.79 | 0.00 | 0.00 |
| March | 73523780.73 | 26351544.74 | 51453936.11 | 24281312.48 | 27172623.64 | 0.00 | 0.00 |
| April | 87962275.86 | 17472961.73 | 54305359.94 | 24307919.67 | 29997440.27 | 0.00 | 0.00 |
| May | 93830394.45 | 8813303.95 | 52915052.50 | 21133306.19 | 31781746.30 | 0.00 | 0.00 |
| June | 93839004.68 | 3610633.00 | 50417375.43 | 19369583.99 | 31047791.44 | 0.00 | 0.00 |
| July | 0.104277E+09 | 5461744.08 | 53625545.36 | 19400980.32 | 34224565.03 | 0.00 | 0.00 |
| August | 91342203.42 | 4099171.57 | 48920698.37 | 16343645.47 | 32577052.90 | 0.00 | 0.00 |
| September | 86771153.22 | 6222370.99 | 45633079.38 | 16465211.87 | 29167867.51 | 0.00 | 0.00 |
| October | 76645408.93 | 10757682.17 | 43449306.57 | 18691228.88 | 24758077.70 | 0.00 | 0.00 |
| November | 52659049.62 | 19413419.58 | 34150586.14 | 13618703.70 | 20531882.44 | 0.00 | 0.00 |
| December | 37151285.99 | 34864155.65 | 28545790.45 | 10102784.15 | 18443006.30 | 0.00 | 0.00 |
| Annual Sum or Average | 0.899039E+09 | 0.205799E+09 | 0.538086E+09 | 0.218924E+09 | 0.319163E+09 | 0.00 | 0.00 |
| Minimum of Months | 37151285.99 | 3610633.00 | 28545790.45 | 10102784.15 | 18443006.30 | 0.00 | 0.00 |
| Maximum of Months | 0.104277E+09 | 39510105.51 | 54305359.94 | 24307919.67 | 34224565.03 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
| January | 19.42 | 15.96 | 13.59 | 3.30 | 9.49 | 57.21 | 169.93 | 0.03 |
| February | 20.87 | 16.70 | 13.89 | 5.53 | 11.19 | 68.99 | 182.59 | 0.00 |
| March | 21.57 | 17.63 | 15.09 | 5.59 | 12.13 | 85.97 | 199.13 | 0.00 |
| April | 24.11 | 19.68 | 17.40 | 4.69 | 15.31 | 97.05 | 212.67 | 0.01 |
| May | 26.41 | 22.40 | 20.67 | 5.05 | 18.50 | 110.67 | 177.92 | 0.00 |
| June | 27.68 | 24.06 | 22.67 | 3.87 | 20.33 | 120.35 | 147.07 | 0.00 |
| July | 28.13 | 24.25 | 22.77 | 2.86 | 20.30 | 124.71 | 163.26 | 0.00 |
| August | 27.97 | 24.38 | 23.03 | 3.45 | 20.36 | 120.27 | 145.14 | 0.08 |
| September | 27.49 | 23.91 | 22.56 | 3.39 | 20.13 | 107.67 | 134.94 | 0.00 |
| October | 26.35 | 22.68 | 21.10 | 3.72 | 17.49 | 81.44 | 160.40 | 0.04 |
| November | 23.59 | 20.24 | 18.46 | 4.39 | 14.74 | 70.67 | 140.11 | 0.00 |
| December | 20.30 | 17.47 | 15.75 | 3.70 | 12.21 | 59.50 | 147.31 | 0.00 |
| Annual Sum or Average | 24.51 | 20.80 | 18.94 | 4.12 | 16.04 | 92.16 | 164.97 | 0.01 |
| Minimum of Months | 19.42 | 15.96 | 13.59 | 2.86 | 9.49 | 57.21 | 134.94 | 0.00 |
| Maximum of Months | 28.13 | 24.38 | 23.03 | 5.59 | 20.36 | 124.71 | 212.67 | 0.08 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
| January | 28.90 | 02-JAN-14:20 | 24.35 | 22.57 | 2.37 | 19.46 | 142.33 | 666.50 |
| February | 29.40 | 11-FEB-13:00 | 24.15 | 22.20 | 4.60 | 20.75 | 178.50 | 682.00 |
| March | 29.40 | 13-MAR-15:00 | 22.41 | 19.40 | 6.20 | 21.27 | 178.00 | 499.00 |
| April | 32.20 | 17-APR-14:00 | 19.76 | 12.80 | 5.20 | 21.27 | 367.00 | 219.50 |
| May | 34.40 | 22-MAY-12:00 | 23.24 | 18.30 | 5.70 | 25.99 | 382.50 | 457.50 |
| June | 32.20 | 11-JUN-12:00 | 23.83 | 20.60 | 3.60 | 23.15 | 181.50 | 762.50 |
| July | 35.60 | 29-JUL-15:00 | 24.39 | 20.00 | 3.60 | 25.66 | 281.50 | 374.50 |
| August | 33.90 | 23-AUG-12:00 | 25.44 | 22.20 | 5.70 | 24.50 | 261.50 | 640.00 |
| September | 32.20 | 08-SEP-14:00 | 23.42 | 20.00 | 2.10 | 21.61 | 221.50 | 576.00 |
| October | 32.20 | 09-OCT-10:00 | 23.83 | 20.60 | 3.10 | 25.16 | 286.50 | 457.50 |
| November | 30.00 | 17-NOV-14:00 | 22.20 | 18.90 | 4.10 | 19.35 | 178.50 | 412.50 |
| December | 28.90 | 10-DEC-14:20 | 22.91 | 20.40 | 7.87 | 19.82 | 162.67 | 585.17 |
| Annual Sum or Average | ||||||||
| Minimum of Months | 28.90 | 19.76 | 12.80 | 2.10 | 19.35 | 142.33 | 219.50 | |
| Maximum of Months | 35.60 | 25.44 | 22.57 | 7.87 | 25.99 | 382.50 | 762.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
| January | 9.40 | 25-JAN-04:00 | 4.59 | -1.7 | 3.10 | -7.3 | 0.00 | 0.00 |
| February | 5.00 | 04-FEB-06:00 | 1.99 | -2.8 | 5.70 | -11.9 | 0.00 | 0.00 |
| March | 6.70 | 16-MAR-04:00 | 4.49 | 1.70 | 4.60 | -9.2 | 0.00 | 0.00 |
| April | 14.40 | 02-APR-05:49 | 13.38 | 12.70 | 1.60 | 0.69 | 0.00 | 0.00 |
| May | 20.60 | 01-MAY-04:00 | 19.45 | 18.90 | 1.00 | 7.95 | 0.00 | 0.00 |
| June | 22.80 | 05-JUN-14:00 | 20.57 | 19.40 | 2.10 | 18.46 | 245.00 | 55.00 |
| July | 22.80 | 02-JUL-15:00 | 21.59 | 21.10 | 4.60 | 20.92 | 155.00 | 8.50 |
| August | 22.20 | 12-AUG-06:00 | 21.85 | 21.70 | 2.60 | 20.40 | 65.50 | 0.00 |
| September | 22.20 | 05-SEP-05:00 | 21.37 | 21.10 | 2.60 | 13.54 | 0.00 | 0.00 |
| October | 21.10 | 28-OCT-02:00 | 20.29 | 20.00 | 2.60 | 8.54 | 0.00 | 0.00 |
| November | 10.00 | 27-NOV-02:00 | 8.82 | 7.80 | 3.10 | -4.6 | 0.00 | 0.00 |
| December | 7.80 | 15-DEC-05:40 | 5.61 | 3.13 | 6.37 | -7.8 | 0.00 | 0.00 |
| Annual Sum or Average | ||||||||
| Minimum of Months | 5.00 | 1.99 | -2.8 | 1.00 | -11.9 | 0.00 | 0.00 | |
| Maximum of Months | 22.80 | 21.85 | 21.70 | 6.37 | 20.92 | 245.00 | 55.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| SITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
| January | 24.83 | 02-JAN-13:00 | 28.90 | 23.30 | 1.50 | 19.87 | 151.00 | 613.50 |
| February | 24.15 | 11-FEB-13:00 | 29.40 | 22.20 | 4.60 | 20.75 | 178.50 | 682.00 |
| March | 23.83 | 14-MAR-09:00 | 26.70 | 22.80 | 11.30 | 19.52 | 243.50 | 478.00 |
| April | 24.58 | 01-APR-15:00 | 28.30 | 23.30 | 3.60 | 16.30 | 93.50 | 759.50 |
| May | 26.05 | 28-MAY-14:00 | 28.90 | 25.00 | 5.20 | 25.66 | 289.00 | 98.50 |
| June | 26.06 | 28-JUN-11:00 | 28.90 | 25.00 | 1.50 | 22.98 | 404.50 | 373.50 |
| July | 26.39 | 12-JUL-10:00 | 30.60 | 25.00 | 4.60 | 23.82 | 287.50 | 574.00 |
| August | 26.46 | 21-AUG-15:00 | 32.20 | 24.40 | 3.60 | 24.50 | 205.50 | 366.00 |
| September | 26.31 | 22-SEP-16:00 | 30.00 | 25.00 | 6.20 | 28.91 | 54.00 | 21.00 |
| October | 26.52 | 01-OCT-11:00 | 29.40 | 25.60 | 6.20 | 28.43 | 283.50 | 0.00 |
| November | 25.31 | 04-NOV-13:00 | 27.80 | 24.40 | 2.10 | 26.48 | 199.00 | 3.00 |
| December | 24.31 | 24-DEC-14:00 | 27.20 | 23.30 | 2.10 | 23.66 | 201.50 | 114.50 |
| Annual Sum or Average | ||||||||
| Minimum of Months | 23.83 | 26.70 | 22.20 | 1.50 | 16.30 | 54.00 | 0.00 | |
| Maximum of Months | 26.52 | 32.20 | 25.60 | 11.30 | 28.91 | 404.50 | 759.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| SITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
| January | 23.30 | 02-JAN-13:00 | 28.90 | 24.83 | 1.50 | 19.87 | 151.00 | 613.50 |
| February | 22.80 | 11-FEB-16:19 | 27.60 | 24.09 | 5.70 | 18.94 | 101.33 | 565.33 |
| March | 22.80 | 14-MAR-09:20 | 25.57 | 23.60 | 9.63 | 22.18 | 176.17 | 527.17 |
| April | 23.30 | 01-APR-14:00 | 27.80 | 24.57 | 5.70 | 15.76 | 108.00 | 831.00 |
| May | 25.00 | 28-MAY-12:00 | 27.80 | 25.74 | 6.70 | 22.98 | 249.50 | 244.50 |
| June | 25.00 | 06-JUN-18:00 | 27.20 | 25.59 | 3.60 | 23.99 | 17.50 | 0.00 |
| July | 25.00 | 12-JUL-03:00 | 27.20 | 25.59 | 1.50 | 19.70 | 0.00 | 0.00 |
| August | 25.60 | 21-AUG-11:00 | 28.90 | 26.35 | 2.60 | 23.15 | 567.00 | 173.50 |
| September | 25.00 | 22-SEP-00:00 | 27.80 | 25.31 | 3.60 | 20.92 | 0.00 | 0.00 |
| October | 25.60 | 01-OCT-11:00 | 29.40 | 26.52 | 6.20 | 28.43 | 283.50 | 0.00 |
| November | 24.40 | 05-NOV-01:19 | 26.10 | 24.93 | 2.03 | 16.37 | 0.00 | 0.00 |
| December | 23.90 | 24-DEC-08:00 | 23.90 | 23.90 | 2.60 | 17.75 | 168.50 | 167.00 |
| Annual Sum or Average | ||||||||
| Minimum of Months | 22.80 | 23.90 | 23.60 | 1.50 | 15.76 | 0.00 | 0.00 | |
| Maximum of Months | 25.60 | 29.40 | 26.52 | 9.63 | 28.43 | 567.00 | 831.00 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| SITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
| January | 18.00 | 13.00 | 16.00 | 24.73 | 28.77 | 0.00 |
| February | 18.00 | 13.00 | 16.00 | 25.06 | 35.04 | 0.00 |
| March | 18.00 | 13.00 | 16.00 | 26.11 | 42.49 | 0.00 |
| April | 18.00 | 13.00 | 16.00 | 27.63 | 49.05 | 0.00 |
| May | 18.00 | 13.00 | 16.00 | 29.20 | 48.15 | 0.00 |
| June | 18.00 | 13.00 | 16.00 | 30.41 | 45.99 | 0.00 |
| July | 18.00 | 13.00 | 16.00 | 30.92 | 49.88 | 0.00 |
| August | 18.00 | 13.00 | 16.00 | 30.58 | 45.60 | 0.00 |
| September | 18.00 | 13.00 | 16.00 | 29.50 | 40.49 | 0.00 |
| October | 18.00 | 13.00 | 16.00 | 27.97 | 35.89 | 0.00 |
| November | 18.00 | 13.00 | 16.00 | 26.40 | 29.31 | 0.00 |
| December | 18.00 | 13.00 | 16.00 | 25.21 | 26.63 | 0.00 |
| Annual Sum or Average | 18.00 | 13.00 | 16.00 | 27.83 | 39.80 | 0.00 |
| Minimum of Months | 18.00 | 13.00 | 16.00 | 24.73 | 26.63 | 0.00 |
| Maximum of Months | 18.00 | 13.00 | 16.00 | 30.92 | 49.88 | 0.00 |
Report: WaterHeaterReportMonthly
For: G SW APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.918973E+09 | -746367402.8 | 0.00 | 0.00 | 744.00 | 0.00 | -172605106.1 | 59.44 | 0.00 | 0.00 |
| February | 0.823709E+09 | -667627412.6 | 0.00 | 0.00 | 672.00 | 0.00 | -156081709.3 | 59.44 | 0.00 | 0.00 |
| March | 0.889558E+09 | -716754180.5 | 0.00 | 0.00 | 744.00 | 0.00 | -172803426.8 | 59.44 | 0.00 | 0.00 |
| April | 0.828866E+09 | -661942651.9 | 0.00 | 0.00 | 720.00 | 0.00 | -166923360.3 | 59.44 | 0.00 | 0.00 |
| May | 0.822598E+09 | -650110079.0 | 0.00 | 0.00 | 744.00 | 0.00 | -172488331.4 | 59.44 | 0.00 | 0.00 |
| June | 0.770957E+09 | -604041642.8 | 0.00 | 0.00 | 720.00 | 0.00 | -166915293.0 | 59.44 | 0.00 | 0.00 |
| July | 0.785745E+09 | -613263046.8 | 0.00 | 0.00 | 744.00 | 0.00 | -172482359.1 | 59.44 | 0.00 | 0.00 |
| August | 0.792964E+09 | -620473863.3 | 0.00 | 0.00 | 744.00 | 0.00 | -172490620.5 | 59.44 | 0.00 | 0.00 |
| September | 0.789824E+09 | -622908760.6 | 0.00 | 0.00 | 720.00 | 0.00 | -166915661.2 | 59.44 | 0.00 | 0.00 |
| October | 0.849110E+09 | -676628077.0 | 0.00 | 0.00 | 744.00 | 0.00 | -172481659.7 | 59.44 | 0.00 | 0.00 |
| November | 0.854462E+09 | -687501975.9 | 0.00 | 0.00 | 720.00 | 0.00 | -166959775.5 | 59.44 | 0.00 | 0.00 |
| December | 0.908573E+09 | -735937372.5 | 0.00 | 0.00 | 744.00 | 0.00 | -172635787.3 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.100353E+11 | -0.800356E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.203178E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.770957E+09 | -746367402.8 | 0.00 | 0.00 | 672.00 | 0.00 | -172803426.8 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.918973E+09 | -604041642.8 | 0.00 | 0.00 | 744.00 | 0.00 | -156081709.3 | 59.44 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: G NW APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.919455E+09 | -746369829.7 | 0.00 | 0.00 | 744.00 | 0.00 | -173084984.3 | 59.44 | 0.00 | 0.00 |
| February | 0.824114E+09 | -667627024.9 | 0.00 | 0.00 | 672.00 | 0.00 | -156487037.8 | 59.44 | 0.00 | 0.00 |
| March | 0.889880E+09 | -716760707.3 | 0.00 | 0.00 | 744.00 | 0.00 | -173118998.7 | 59.44 | 0.00 | 0.00 |
| April | 0.828869E+09 | -661943299.2 | 0.00 | 0.00 | 720.00 | 0.00 | -166925656.4 | 59.44 | 0.00 | 0.00 |
| May | 0.822599E+09 | -650113593.4 | 0.00 | 0.00 | 744.00 | 0.00 | -172485193.8 | 59.44 | 0.00 | 0.00 |
| June | 0.770952E+09 | -604030085.8 | 0.00 | 0.00 | 720.00 | 0.00 | -166922005.5 | 59.44 | 0.00 | 0.00 |
| July | 0.785743E+09 | -613261992.3 | 0.00 | 0.00 | 744.00 | 0.00 | -172481322.8 | 59.44 | 0.00 | 0.00 |
| August | 0.792968E+09 | -620479079.7 | 0.00 | 0.00 | 744.00 | 0.00 | -172489256.6 | 59.44 | 0.00 | 0.00 |
| September | 0.789824E+09 | -622906209.1 | 0.00 | 0.00 | 720.00 | 0.00 | -166917978.5 | 59.44 | 0.00 | 0.00 |
| October | 0.849110E+09 | -676624105.6 | 0.00 | 0.00 | 744.00 | 0.00 | -172485510.7 | 59.44 | 0.00 | 0.00 |
| November | 0.854521E+09 | -687503644.2 | 0.00 | 0.00 | 720.00 | 0.00 | -167017262.3 | 59.44 | 0.00 | 0.00 |
| December | 0.908918E+09 | -735930365.3 | 0.00 | 0.00 | 744.00 | 0.00 | -172987632.3 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.100370E+11 | -0.800355E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.203340E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.770952E+09 | -746369829.7 | 0.00 | 0.00 | 672.00 | 0.00 | -173118998.7 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.919455E+09 | -604030085.8 | 0.00 | 0.00 | 744.00 | 0.00 | -156487037.8 | 59.44 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: G NE APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.919380E+09 | -746369051.3 | 0.00 | 0.00 | 744.00 | 0.00 | -173011042.2 | 59.44 | 0.00 | 0.00 |
| February | 0.824081E+09 | -667633461.1 | 0.00 | 0.00 | 672.00 | 0.00 | -156447765.2 | 59.44 | 0.00 | 0.00 |
| March | 0.889777E+09 | -716760786.0 | 0.00 | 0.00 | 744.00 | 0.00 | -173015845.8 | 59.44 | 0.00 | 0.00 |
| April | 0.828869E+09 | -661949690.6 | 0.00 | 0.00 | 720.00 | 0.00 | -166918961.9 | 59.44 | 0.00 | 0.00 |
| May | 0.822599E+09 | -650118623.4 | 0.00 | 0.00 | 744.00 | 0.00 | -172480501.3 | 59.44 | 0.00 | 0.00 |
| June | 0.770952E+09 | -604036398.1 | 0.00 | 0.00 | 720.00 | 0.00 | -166915765.0 | 59.44 | 0.00 | 0.00 |
| July | 0.785749E+09 | -613264553.1 | 0.00 | 0.00 | 744.00 | 0.00 | -172484389.2 | 59.44 | 0.00 | 0.00 |
| August | 0.792963E+09 | -620486223.2 | 0.00 | 0.00 | 744.00 | 0.00 | -172477183.5 | 59.44 | 0.00 | 0.00 |
| September | 0.789829E+09 | -622909679.8 | 0.00 | 0.00 | 720.00 | 0.00 | -166919106.6 | 59.44 | 0.00 | 0.00 |
| October | 0.849108E+09 | -676624446.9 | 0.00 | 0.00 | 744.00 | 0.00 | -172484031.4 | 59.44 | 0.00 | 0.00 |
| November | 0.854508E+09 | -687513417.3 | 0.00 | 0.00 | 720.00 | 0.00 | -166994771.3 | 59.44 | 0.00 | 0.00 |
| December | 0.908909E+09 | -735920177.0 | 0.00 | 0.00 | 744.00 | 0.00 | -172988900.4 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.100367E+11 | -0.800359E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.203314E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.770952E+09 | -746369051.3 | 0.00 | 0.00 | 672.00 | 0.00 | -173015845.8 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.919380E+09 | -604036398.1 | 0.00 | 0.00 | 744.00 | 0.00 | -156447765.2 | 59.44 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: G N1 APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.919125E+09 | -746368193.1 | 0.00 | 0.00 | 744.00 | 0.00 | -172756697.1 | 59.44 | 0.00 | 0.00 |
| February | 0.823806E+09 | -667635505.7 | 0.00 | 0.00 | 672.00 | 0.00 | -156170507.1 | 59.44 | 0.00 | 0.00 |
| March | 0.889582E+09 | -716761315.6 | 0.00 | 0.00 | 744.00 | 0.00 | -172820556.5 | 59.44 | 0.00 | 0.00 |
| April | 0.828866E+09 | -661949652.1 | 0.00 | 0.00 | 720.00 | 0.00 | -166916757.0 | 59.44 | 0.00 | 0.00 |
| May | 0.822599E+09 | -650118570.9 | 0.00 | 0.00 | 744.00 | 0.00 | -172480566.3 | 59.44 | 0.00 | 0.00 |
| June | 0.770952E+09 | -604036416.6 | 0.00 | 0.00 | 720.00 | 0.00 | -166915757.5 | 59.44 | 0.00 | 0.00 |
| July | 0.785749E+09 | -613264550.9 | 0.00 | 0.00 | 744.00 | 0.00 | -172484392.4 | 59.44 | 0.00 | 0.00 |
| August | 0.792963E+09 | -620486219.3 | 0.00 | 0.00 | 744.00 | 0.00 | -172477187.9 | 59.44 | 0.00 | 0.00 |
| September | 0.789829E+09 | -622909680.6 | 0.00 | 0.00 | 720.00 | 0.00 | -166919110.1 | 59.44 | 0.00 | 0.00 |
| October | 0.849108E+09 | -676624447.2 | 0.00 | 0.00 | 744.00 | 0.00 | -172484035.3 | 59.44 | 0.00 | 0.00 |
| November | 0.854455E+09 | -687511954.8 | 0.00 | 0.00 | 720.00 | 0.00 | -166942882.4 | 59.44 | 0.00 | 0.00 |
| December | 0.908650E+09 | -735922510.6 | 0.00 | 0.00 | 744.00 | 0.00 | -172727333.1 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.100357E+11 | -0.800359E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.203210E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.770952E+09 | -746368193.1 | 0.00 | 0.00 | 672.00 | 0.00 | -172820556.5 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.919125E+09 | -604036416.6 | 0.00 | 0.00 | 744.00 | 0.00 | -156170507.1 | 59.44 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: G N2 APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.919122E+09 | -746368182.5 | 0.00 | 0.00 | 744.00 | 0.00 | -172754108.6 | 59.44 | 0.00 | 0.00 |
| February | 0.823804E+09 | -667634852.9 | 0.00 | 0.00 | 672.00 | 0.00 | -156169089.2 | 59.44 | 0.00 | 0.00 |
| March | 0.889577E+09 | -716761076.0 | 0.00 | 0.00 | 744.00 | 0.00 | -172815902.0 | 59.44 | 0.00 | 0.00 |
| April | 0.828866E+09 | -661949640.5 | 0.00 | 0.00 | 720.00 | 0.00 | -166916820.9 | 59.44 | 0.00 | 0.00 |
| May | 0.822599E+09 | -650118544.2 | 0.00 | 0.00 | 744.00 | 0.00 | -172480606.3 | 59.44 | 0.00 | 0.00 |
| June | 0.770952E+09 | -604036435.8 | 0.00 | 0.00 | 720.00 | 0.00 | -166915745.6 | 59.44 | 0.00 | 0.00 |
| July | 0.785749E+09 | -613264548.6 | 0.00 | 0.00 | 744.00 | 0.00 | -172484392.4 | 59.44 | 0.00 | 0.00 |
| August | 0.792963E+09 | -620486214.7 | 0.00 | 0.00 | 744.00 | 0.00 | -172477190.1 | 59.44 | 0.00 | 0.00 |
| September | 0.789829E+09 | -622909681.8 | 0.00 | 0.00 | 720.00 | 0.00 | -166919110.1 | 59.44 | 0.00 | 0.00 |
| October | 0.849108E+09 | -676624447.8 | 0.00 | 0.00 | 744.00 | 0.00 | -172484034.7 | 59.44 | 0.00 | 0.00 |
| November | 0.854455E+09 | -687511960.9 | 0.00 | 0.00 | 720.00 | 0.00 | -166942758.7 | 59.44 | 0.00 | 0.00 |
| December | 0.908651E+09 | -735922496.9 | 0.00 | 0.00 | 744.00 | 0.00 | -172728085.1 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.100357E+11 | -0.800359E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.203209E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.770952E+09 | -746368182.5 | 0.00 | 0.00 | 672.00 | 0.00 | -172815902.0 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.919122E+09 | -604036435.8 | 0.00 | 0.00 | 744.00 | 0.00 | -156169089.2 | 59.44 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: G S1 APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.918870E+09 | -746369527.1 | 0.00 | 0.00 | 744.00 | 0.00 | -172500864.9 | 59.44 | 0.00 | 0.00 |
| February | 0.823535E+09 | -667634137.8 | 0.00 | 0.00 | 672.00 | 0.00 | -155901168.2 | 59.44 | 0.00 | 0.00 |
| March | 0.889352E+09 | -716756470.5 | 0.00 | 0.00 | 744.00 | 0.00 | -172595269.6 | 59.44 | 0.00 | 0.00 |
| April | 0.828867E+09 | -661939983.6 | 0.00 | 0.00 | 720.00 | 0.00 | -166926640.8 | 59.44 | 0.00 | 0.00 |
| May | 0.822598E+09 | -650109960.1 | 0.00 | 0.00 | 744.00 | 0.00 | -172488222.0 | 59.44 | 0.00 | 0.00 |
| June | 0.770954E+09 | -604033484.1 | 0.00 | 0.00 | 720.00 | 0.00 | -166920157.0 | 59.44 | 0.00 | 0.00 |
| July | 0.785744E+09 | -613262453.9 | 0.00 | 0.00 | 744.00 | 0.00 | -172481192.9 | 59.44 | 0.00 | 0.00 |
| August | 0.792968E+09 | -620476562.4 | 0.00 | 0.00 | 744.00 | 0.00 | -172490965.8 | 59.44 | 0.00 | 0.00 |
| September | 0.789824E+09 | -622907585.1 | 0.00 | 0.00 | 720.00 | 0.00 | -166916734.4 | 59.44 | 0.00 | 0.00 |
| October | 0.849109E+09 | -676626726.9 | 0.00 | 0.00 | 744.00 | 0.00 | -172482703.4 | 59.44 | 0.00 | 0.00 |
| November | 0.854430E+09 | -687503118.5 | 0.00 | 0.00 | 720.00 | 0.00 | -166927320.8 | 59.44 | 0.00 | 0.00 |
| December | 0.908447E+09 | -735930090.0 | 0.00 | 0.00 | 744.00 | 0.00 | -172517147.6 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.100347E+11 | -0.800355E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.203115E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.770954E+09 | -746369527.1 | 0.00 | 0.00 | 672.00 | 0.00 | -172595269.6 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.918870E+09 | -604033484.1 | 0.00 | 0.00 | 744.00 | 0.00 | -155901168.2 | 59.44 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: G S2 APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.918864E+09 | -746369556.6 | 0.00 | 0.00 | 744.00 | 0.00 | -172493973.2 | 59.44 | 0.00 | 0.00 |
| February | 0.823522E+09 | -667634499.0 | 0.00 | 0.00 | 672.00 | 0.00 | -155887246.6 | 59.44 | 0.00 | 0.00 |
| March | 0.889324E+09 | -716757377.9 | 0.00 | 0.00 | 744.00 | 0.00 | -172566446.6 | 59.44 | 0.00 | 0.00 |
| April | 0.828865E+09 | -661939773.2 | 0.00 | 0.00 | 720.00 | 0.00 | -166925675.8 | 59.44 | 0.00 | 0.00 |
| May | 0.822598E+09 | -650110045.7 | 0.00 | 0.00 | 744.00 | 0.00 | -172488103.1 | 59.44 | 0.00 | 0.00 |
| June | 0.770954E+09 | -604033364.3 | 0.00 | 0.00 | 720.00 | 0.00 | -166920257.5 | 59.44 | 0.00 | 0.00 |
| July | 0.785744E+09 | -613262453.6 | 0.00 | 0.00 | 744.00 | 0.00 | -172481187.6 | 59.44 | 0.00 | 0.00 |
| August | 0.792968E+09 | -620476565.6 | 0.00 | 0.00 | 744.00 | 0.00 | -172490967.2 | 59.44 | 0.00 | 0.00 |
| September | 0.789824E+09 | -622907582.7 | 0.00 | 0.00 | 720.00 | 0.00 | -166916735.6 | 59.44 | 0.00 | 0.00 |
| October | 0.849109E+09 | -676626723.3 | 0.00 | 0.00 | 744.00 | 0.00 | -172482707.7 | 59.44 | 0.00 | 0.00 |
| November | 0.854428E+09 | -687503185.3 | 0.00 | 0.00 | 720.00 | 0.00 | -166924686.7 | 59.44 | 0.00 | 0.00 |
| December | 0.908434E+09 | -735929648.8 | 0.00 | 0.00 | 744.00 | 0.00 | -172504798.3 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.100346E+11 | -0.800355E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.203108E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.770954E+09 | -746369556.6 | 0.00 | 0.00 | 672.00 | 0.00 | -172566446.6 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.918864E+09 | -604033364.3 | 0.00 | 0.00 | 744.00 | 0.00 | -155887246.6 | 59.44 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: M SW APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.166550E+10 | -0.149274E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172759930.9 | 59.44 | 0.00 | 0.00 |
| February | 0.149148E+10 | -0.133527E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -156206322.9 | 59.44 | 0.00 | 0.00 |
| March | 0.160636E+10 | -0.143352E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172842198.4 | 59.44 | 0.00 | 0.00 |
| April | 0.149082E+10 | -0.132389E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -166924493.5 | 59.44 | 0.00 | 0.00 |
| May | 0.147272E+10 | -0.130023E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172484748.8 | 59.44 | 0.00 | 0.00 |
| June | 0.137499E+10 | -0.120807E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -166917687.5 | 59.44 | 0.00 | 0.00 |
| July | 0.139901E+10 | -0.122653E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172484871.5 | 59.44 | 0.00 | 0.00 |
| August | 0.141345E+10 | -0.124097E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172484723.2 | 59.44 | 0.00 | 0.00 |
| September | 0.141273E+10 | -0.124582E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -166917575.5 | 59.44 | 0.00 | 0.00 |
| October | 0.152574E+10 | -0.135325E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172484811.6 | 59.44 | 0.00 | 0.00 |
| November | 0.154205E+10 | -0.137502E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -167036917.8 | 59.44 | 0.00 | 0.00 |
| December | 0.164470E+10 | -0.147186E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172836366.9 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.180395E+11 | -0.160072E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.203238E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.137499E+10 | -0.149274E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -172842198.4 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.166550E+10 | -0.120807E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -156206322.9 | 59.44 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: M NW APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.166612E+10 | -0.149274E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -173378334.7 | 59.44 | 0.00 | 0.00 |
| February | 0.149200E+10 | -0.133527E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -156727854.1 | 59.44 | 0.00 | 0.00 |
| March | 0.160667E+10 | -0.143352E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -173153960.4 | 59.44 | 0.00 | 0.00 |
| April | 0.149082E+10 | -0.132389E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -166924714.6 | 59.44 | 0.00 | 0.00 |
| May | 0.147272E+10 | -0.130024E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172482061.5 | 59.44 | 0.00 | 0.00 |
| June | 0.137499E+10 | -0.120807E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -166918680.6 | 59.44 | 0.00 | 0.00 |
| July | 0.139901E+10 | -0.122653E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172483401.4 | 59.44 | 0.00 | 0.00 |
| August | 0.141345E+10 | -0.124097E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172484741.3 | 59.44 | 0.00 | 0.00 |
| September | 0.141273E+10 | -0.124582E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -166916377.7 | 59.44 | 0.00 | 0.00 |
| October | 0.152574E+10 | -0.135325E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172485366.8 | 59.44 | 0.00 | 0.00 |
| November | 0.154216E+10 | -0.137502E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -167146831.4 | 59.44 | 0.00 | 0.00 |
| December | 0.164527E+10 | -0.147186E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -173407299.7 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.180417E+11 | -0.160072E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.203451E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.137499E+10 | -0.149274E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -173407299.7 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.166612E+10 | -0.120807E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -156727854.1 | 59.44 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: M SE APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.166548E+10 | -0.149274E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172737133.0 | 59.44 | 0.00 | 0.00 |
| February | 0.149145E+10 | -0.133527E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -156178076.5 | 59.44 | 0.00 | 0.00 |
| March | 0.160629E+10 | -0.143352E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172771809.4 | 59.44 | 0.00 | 0.00 |
| April | 0.149082E+10 | -0.132389E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -166923859.5 | 59.44 | 0.00 | 0.00 |
| May | 0.147272E+10 | -0.130023E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172484857.4 | 59.44 | 0.00 | 0.00 |
| June | 0.137499E+10 | -0.120807E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -166917702.3 | 59.44 | 0.00 | 0.00 |
| July | 0.139901E+10 | -0.122653E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172484870.2 | 59.44 | 0.00 | 0.00 |
| August | 0.141345E+10 | -0.124097E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172484728.2 | 59.44 | 0.00 | 0.00 |
| September | 0.141273E+10 | -0.124582E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -166917579.6 | 59.44 | 0.00 | 0.00 |
| October | 0.152574E+10 | -0.135325E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172484814.4 | 59.44 | 0.00 | 0.00 |
| November | 0.154204E+10 | -0.137502E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -167024046.1 | 59.44 | 0.00 | 0.00 |
| December | 0.164469E+10 | -0.147186E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172827652.4 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.180394E+11 | -0.160072E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.203224E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.137499E+10 | -0.149274E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -172827652.4 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.166548E+10 | -0.120807E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -156178076.5 | 59.44 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: M NE APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.166601E+10 | -0.149274E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -173267846.4 | 59.44 | 0.00 | 0.00 |
| February | 0.149196E+10 | -0.133527E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -156690059.9 | 59.44 | 0.00 | 0.00 |
| March | 0.160654E+10 | -0.143352E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -173025125.6 | 59.44 | 0.00 | 0.00 |
| April | 0.149082E+10 | -0.132389E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -166926933.4 | 59.44 | 0.00 | 0.00 |
| May | 0.147271E+10 | -0.130023E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172482363.9 | 59.44 | 0.00 | 0.00 |
| June | 0.137499E+10 | -0.120807E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -166918708.3 | 59.44 | 0.00 | 0.00 |
| July | 0.139901E+10 | -0.122653E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172483957.9 | 59.44 | 0.00 | 0.00 |
| August | 0.141345E+10 | -0.124097E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172485081.4 | 59.44 | 0.00 | 0.00 |
| September | 0.141273E+10 | -0.124582E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -166916423.2 | 59.44 | 0.00 | 0.00 |
| October | 0.152574E+10 | -0.135325E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172485171.4 | 59.44 | 0.00 | 0.00 |
| November | 0.154213E+10 | -0.137502E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -167119332.2 | 59.44 | 0.00 | 0.00 |
| December | 0.164526E+10 | -0.147186E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -173396256.8 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.180414E+11 | -0.160072E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.203420E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.137499E+10 | -0.149274E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -173396256.8 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.166601E+10 | -0.120807E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -156690059.9 | 59.44 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: M N1 APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.166560E+10 | -0.149274E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172860513.9 | 59.44 | 0.00 | 0.00 |
| February | 0.149160E+10 | -0.133527E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -156323455.3 | 59.44 | 0.00 | 0.00 |
| March | 0.160635E+10 | -0.143352E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172830094.3 | 59.44 | 0.00 | 0.00 |
| April | 0.149082E+10 | -0.132389E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -166923369.1 | 59.44 | 0.00 | 0.00 |
| May | 0.147271E+10 | -0.130023E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172483277.2 | 59.44 | 0.00 | 0.00 |
| June | 0.137499E+10 | -0.120807E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -166917955.3 | 59.44 | 0.00 | 0.00 |
| July | 0.139901E+10 | -0.122653E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172484198.1 | 59.44 | 0.00 | 0.00 |
| August | 0.141345E+10 | -0.124097E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172485100.8 | 59.44 | 0.00 | 0.00 |
| September | 0.141273E+10 | -0.124582E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -166916428.0 | 59.44 | 0.00 | 0.00 |
| October | 0.152574E+10 | -0.135325E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172485171.2 | 59.44 | 0.00 | 0.00 |
| November | 0.154202E+10 | -0.137502E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -167002977.9 | 59.44 | 0.00 | 0.00 |
| December | 0.164475E+10 | -0.147186E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172887985.3 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.180398E+11 | -0.160072E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.203260E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.137499E+10 | -0.149274E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -172887985.3 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.166560E+10 | -0.120807E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -156323455.3 | 59.44 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: M N2 APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.166560E+10 | -0.149274E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172855715.0 | 59.44 | 0.00 | 0.00 |
| February | 0.149159E+10 | -0.133527E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -156321688.5 | 59.44 | 0.00 | 0.00 |
| March | 0.160634E+10 | -0.143352E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172822582.6 | 59.44 | 0.00 | 0.00 |
| April | 0.149082E+10 | -0.132389E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -166923042.8 | 59.44 | 0.00 | 0.00 |
| May | 0.147271E+10 | -0.130023E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172483344.0 | 59.44 | 0.00 | 0.00 |
| June | 0.137499E+10 | -0.120807E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -166917924.9 | 59.44 | 0.00 | 0.00 |
| July | 0.139901E+10 | -0.122653E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172484207.5 | 59.44 | 0.00 | 0.00 |
| August | 0.141345E+10 | -0.124097E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172485101.2 | 59.44 | 0.00 | 0.00 |
| September | 0.141273E+10 | -0.124582E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -166916428.2 | 59.44 | 0.00 | 0.00 |
| October | 0.152574E+10 | -0.135325E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172485171.2 | 59.44 | 0.00 | 0.00 |
| November | 0.154202E+10 | -0.137502E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -167002269.3 | 59.44 | 0.00 | 0.00 |
| December | 0.164475E+10 | -0.147186E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172887938.6 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.180398E+11 | -0.160072E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.203259E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.137499E+10 | -0.149274E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -172887938.6 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.166560E+10 | -0.120807E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -156321688.5 | 59.44 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: M S1 APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.166528E+10 | -0.149274E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172533700.8 | 59.44 | 0.00 | 0.00 |
| February | 0.149122E+10 | -0.133527E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -155950030.5 | 59.44 | 0.00 | 0.00 |
| March | 0.160613E+10 | -0.143352E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172609122.1 | 59.44 | 0.00 | 0.00 |
| April | 0.149082E+10 | -0.132389E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -166923011.2 | 59.44 | 0.00 | 0.00 |
| May | 0.147271E+10 | -0.130023E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172483074.9 | 59.44 | 0.00 | 0.00 |
| June | 0.137499E+10 | -0.120807E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -166918177.4 | 59.44 | 0.00 | 0.00 |
| July | 0.139901E+10 | -0.122653E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172484156.5 | 59.44 | 0.00 | 0.00 |
| August | 0.141345E+10 | -0.124097E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172485101.4 | 59.44 | 0.00 | 0.00 |
| September | 0.141273E+10 | -0.124582E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -166916429.8 | 59.44 | 0.00 | 0.00 |
| October | 0.152574E+10 | -0.135325E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172485172.7 | 59.44 | 0.00 | 0.00 |
| November | 0.154196E+10 | -0.137501E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -166945733.5 | 59.44 | 0.00 | 0.00 |
| December | 0.164445E+10 | -0.147186E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172592607.8 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.180385E+11 | -0.160072E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.203133E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.137499E+10 | -0.149274E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -172609122.1 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.166528E+10 | -0.120807E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -155950030.5 | 59.44 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: M S2 APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.166528E+10 | -0.149274E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172533750.6 | 59.44 | 0.00 | 0.00 |
| February | 0.149122E+10 | -0.133527E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -155949555.4 | 59.44 | 0.00 | 0.00 |
| March | 0.160613E+10 | -0.143352E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172607956.1 | 59.44 | 0.00 | 0.00 |
| April | 0.149082E+10 | -0.132389E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -166923055.3 | 59.44 | 0.00 | 0.00 |
| May | 0.147271E+10 | -0.130023E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172483131.3 | 59.44 | 0.00 | 0.00 |
| June | 0.137499E+10 | -0.120807E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -166918064.8 | 59.44 | 0.00 | 0.00 |
| July | 0.139901E+10 | -0.122653E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172484172.3 | 59.44 | 0.00 | 0.00 |
| August | 0.141345E+10 | -0.124097E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172485101.9 | 59.44 | 0.00 | 0.00 |
| September | 0.141273E+10 | -0.124582E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -166916430.0 | 59.44 | 0.00 | 0.00 |
| October | 0.152574E+10 | -0.135325E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172485172.7 | 59.44 | 0.00 | 0.00 |
| November | 0.154196E+10 | -0.137501E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -166945620.7 | 59.44 | 0.00 | 0.00 |
| December | 0.164445E+10 | -0.147186E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172593076.7 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.180385E+11 | -0.160072E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.203133E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.137499E+10 | -0.149274E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -172607956.1 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.166528E+10 | -0.120807E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -155949555.4 | 59.44 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: T SW APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.921266E+09 | -746370904.0 | 0.00 | 0.00 | 744.00 | 0.00 | -174894634.8 | 59.44 | 0.00 | 0.00 |
| February | 0.825137E+09 | -667636048.6 | 0.00 | 0.00 | 672.00 | 0.00 | -157500892.2 | 59.44 | 0.00 | 0.00 |
| March | 0.890789E+09 | -716760725.0 | 0.00 | 0.00 | 744.00 | 0.00 | -174028577.4 | 59.44 | 0.00 | 0.00 |
| April | 0.828996E+09 | -661940359.6 | 0.00 | 0.00 | 720.00 | 0.00 | -167055775.9 | 59.44 | 0.00 | 0.00 |
| May | 0.822598E+09 | -650109934.7 | 0.00 | 0.00 | 744.00 | 0.00 | -172488277.0 | 59.44 | 0.00 | 0.00 |
| June | 0.770954E+09 | -604033901.8 | 0.00 | 0.00 | 720.00 | 0.00 | -166919839.4 | 59.44 | 0.00 | 0.00 |
| July | 0.785744E+09 | -613262454.0 | 0.00 | 0.00 | 744.00 | 0.00 | -172481184.6 | 59.44 | 0.00 | 0.00 |
| August | 0.792968E+09 | -620476559.1 | 0.00 | 0.00 | 744.00 | 0.00 | -172490949.3 | 59.44 | 0.00 | 0.00 |
| September | 0.789824E+09 | -622907587.0 | 0.00 | 0.00 | 720.00 | 0.00 | -166916726.0 | 59.44 | 0.00 | 0.00 |
| October | 0.849109E+09 | -676626728.9 | 0.00 | 0.00 | 744.00 | 0.00 | -172482692.6 | 59.44 | 0.00 | 0.00 |
| November | 0.855146E+09 | -687507289.6 | 0.00 | 0.00 | 720.00 | 0.00 | -167638389.0 | 59.44 | 0.00 | 0.00 |
| December | 0.910436E+09 | -735925803.0 | 0.00 | 0.00 | 744.00 | 0.00 | -174509951.9 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.100430E+11 | -0.800356E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.203941E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.770954E+09 | -746370904.0 | 0.00 | 0.00 | 672.00 | 0.00 | -174894634.8 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.921266E+09 | -604033901.8 | 0.00 | 0.00 | 744.00 | 0.00 | -157500892.2 | 59.44 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: T NW APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.922576E+09 | -746367426.4 | 0.00 | 0.00 | 744.00 | 0.00 | -176208943.8 | 59.44 | 0.00 | 0.00 |
| February | 0.825821E+09 | -667631691.3 | 0.00 | 0.00 | 672.00 | 0.00 | -158188888.8 | 59.44 | 0.00 | 0.00 |
| March | 0.891258E+09 | -716757233.8 | 0.00 | 0.00 | 744.00 | 0.00 | -174500575.8 | 59.44 | 0.00 | 0.00 |
| April | 0.829009E+09 | -661948988.9 | 0.00 | 0.00 | 720.00 | 0.00 | -167060304.0 | 59.44 | 0.00 | 0.00 |
| May | 0.822599E+09 | -650118270.0 | 0.00 | 0.00 | 744.00 | 0.00 | -172480879.6 | 59.44 | 0.00 | 0.00 |
| June | 0.770952E+09 | -604036958.5 | 0.00 | 0.00 | 720.00 | 0.00 | -166915426.8 | 59.44 | 0.00 | 0.00 |
| July | 0.785749E+09 | -613264491.6 | 0.00 | 0.00 | 744.00 | 0.00 | -172484375.5 | 59.44 | 0.00 | 0.00 |
| August | 0.792963E+09 | -620486061.7 | 0.00 | 0.00 | 744.00 | 0.00 | -172477241.8 | 59.44 | 0.00 | 0.00 |
| September | 0.789829E+09 | -622909718.8 | 0.00 | 0.00 | 720.00 | 0.00 | -166919097.5 | 59.44 | 0.00 | 0.00 |
| October | 0.849108E+09 | -676624464.4 | 0.00 | 0.00 | 744.00 | 0.00 | -172484004.5 | 59.44 | 0.00 | 0.00 |
| November | 0.855366E+09 | -687497706.2 | 0.00 | 0.00 | 720.00 | 0.00 | -167868625.6 | 59.44 | 0.00 | 0.00 |
| December | 0.911568E+09 | -735935145.5 | 0.00 | 0.00 | 744.00 | 0.00 | -175632801.8 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.100468E+11 | -0.800358E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.204322E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.770952E+09 | -746367426.4 | 0.00 | 0.00 | 672.00 | 0.00 | -176208943.8 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.922576E+09 | -604036958.5 | 0.00 | 0.00 | 744.00 | 0.00 | -158188888.8 | 59.44 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: T SE APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.921147E+09 | -746371602.2 | 0.00 | 0.00 | 744.00 | 0.00 | -174775785.2 | 59.44 | 0.00 | 0.00 |
| February | 0.825075E+09 | -667628866.2 | 0.00 | 0.00 | 672.00 | 0.00 | -157446527.1 | 59.44 | 0.00 | 0.00 |
| March | 0.890643E+09 | -716757241.2 | 0.00 | 0.00 | 744.00 | 0.00 | -173886138.6 | 59.44 | 0.00 | 0.00 |
| April | 0.828986E+09 | -661946042.0 | 0.00 | 0.00 | 720.00 | 0.00 | -167039646.8 | 59.44 | 0.00 | 0.00 |
| May | 0.822599E+09 | -650117211.6 | 0.00 | 0.00 | 744.00 | 0.00 | -172481889.3 | 59.44 | 0.00 | 0.00 |
| June | 0.770955E+09 | -604041873.8 | 0.00 | 0.00 | 720.00 | 0.00 | -166913310.7 | 59.44 | 0.00 | 0.00 |
| July | 0.785748E+09 | -613264503.5 | 0.00 | 0.00 | 744.00 | 0.00 | -172483257.9 | 59.44 | 0.00 | 0.00 |
| August | 0.792964E+09 | -620482658.2 | 0.00 | 0.00 | 744.00 | 0.00 | -172481037.4 | 59.44 | 0.00 | 0.00 |
| September | 0.789829E+09 | -622913642.8 | 0.00 | 0.00 | 720.00 | 0.00 | -166915174.3 | 59.44 | 0.00 | 0.00 |
| October | 0.849109E+09 | -676625570.8 | 0.00 | 0.00 | 744.00 | 0.00 | -172483253.3 | 59.44 | 0.00 | 0.00 |
| November | 0.855108E+09 | -687503635.8 | 0.00 | 0.00 | 720.00 | 0.00 | -167604255.5 | 59.44 | 0.00 | 0.00 |
| December | 0.910396E+09 | -735935030.3 | 0.00 | 0.00 | 744.00 | 0.00 | -174461234.8 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.100426E+11 | -0.800359E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.203897E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.770955E+09 | -746371602.2 | 0.00 | 0.00 | 672.00 | 0.00 | -174775785.2 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.921147E+09 | -604041873.8 | 0.00 | 0.00 | 744.00 | 0.00 | -157446527.1 | 59.44 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: T NE APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.922408E+09 | -746369263.8 | 0.00 | 0.00 | 744.00 | 0.00 | -176038878.4 | 59.44 | 0.00 | 0.00 |
| February | 0.825744E+09 | -667622752.6 | 0.00 | 0.00 | 672.00 | 0.00 | -158121168.1 | 59.44 | 0.00 | 0.00 |
| March | 0.891132E+09 | -716750374.6 | 0.00 | 0.00 | 744.00 | 0.00 | -174381881.0 | 59.44 | 0.00 | 0.00 |
| April | 0.828995E+09 | -661940722.5 | 0.00 | 0.00 | 720.00 | 0.00 | -167054595.2 | 59.44 | 0.00 | 0.00 |
| May | 0.822598E+09 | -650110073.4 | 0.00 | 0.00 | 744.00 | 0.00 | -172488297.7 | 59.44 | 0.00 | 0.00 |
| June | 0.770957E+09 | -604041644.1 | 0.00 | 0.00 | 720.00 | 0.00 | -166915290.3 | 59.44 | 0.00 | 0.00 |
| July | 0.785745E+09 | -613263045.0 | 0.00 | 0.00 | 744.00 | 0.00 | -172482361.4 | 59.44 | 0.00 | 0.00 |
| August | 0.792964E+09 | -620473862.7 | 0.00 | 0.00 | 744.00 | 0.00 | -172490613.3 | 59.44 | 0.00 | 0.00 |
| September | 0.789824E+09 | -622908767.3 | 0.00 | 0.00 | 720.00 | 0.00 | -166915663.2 | 59.44 | 0.00 | 0.00 |
| October | 0.849110E+09 | -676628087.1 | 0.00 | 0.00 | 744.00 | 0.00 | -172481663.3 | 59.44 | 0.00 | 0.00 |
| November | 0.855314E+09 | -687513748.5 | 0.00 | 0.00 | 720.00 | 0.00 | -167800386.4 | 59.44 | 0.00 | 0.00 |
| December | 0.911602E+09 | -735923925.5 | 0.00 | 0.00 | 744.00 | 0.00 | -175678076.4 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.100464E+11 | -0.800355E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.204285E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.770957E+09 | -746369263.8 | 0.00 | 0.00 | 672.00 | 0.00 | -176038878.4 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.922408E+09 | -604041644.1 | 0.00 | 0.00 | 744.00 | 0.00 | -158121168.1 | 59.44 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: T N1 APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.921809E+09 | -746370632.4 | 0.00 | 0.00 | 744.00 | 0.00 | -175438086.3 | 59.44 | 0.00 | 0.00 |
| February | 0.825389E+09 | -667633726.9 | 0.00 | 0.00 | 672.00 | 0.00 | -157755531.2 | 59.44 | 0.00 | 0.00 |
| March | 0.890983E+09 | -716759074.0 | 0.00 | 0.00 | 744.00 | 0.00 | -174224127.9 | 59.44 | 0.00 | 0.00 |
| April | 0.828951E+09 | -661940654.2 | 0.00 | 0.00 | 720.00 | 0.00 | -167010321.1 | 59.44 | 0.00 | 0.00 |
| May | 0.822598E+09 | -650109998.2 | 0.00 | 0.00 | 744.00 | 0.00 | -172488143.8 | 59.44 | 0.00 | 0.00 |
| June | 0.770954E+09 | -604033387.7 | 0.00 | 0.00 | 720.00 | 0.00 | -166920229.1 | 59.44 | 0.00 | 0.00 |
| July | 0.785744E+09 | -613262453.7 | 0.00 | 0.00 | 744.00 | 0.00 | -172481182.7 | 59.44 | 0.00 | 0.00 |
| August | 0.792968E+09 | -620476564.9 | 0.00 | 0.00 | 744.00 | 0.00 | -172490956.3 | 59.44 | 0.00 | 0.00 |
| September | 0.789824E+09 | -622907582.8 | 0.00 | 0.00 | 720.00 | 0.00 | -166916733.1 | 59.44 | 0.00 | 0.00 |
| October | 0.849109E+09 | -676626723.2 | 0.00 | 0.00 | 744.00 | 0.00 | -172482704.3 | 59.44 | 0.00 | 0.00 |
| November | 0.855113E+09 | -687504277.7 | 0.00 | 0.00 | 720.00 | 0.00 | -167608775.1 | 59.44 | 0.00 | 0.00 |
| December | 0.911045E+09 | -735928079.7 | 0.00 | 0.00 | 744.00 | 0.00 | -175116729.2 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.100445E+11 | -0.800355E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.204093E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.770954E+09 | -746370632.4 | 0.00 | 0.00 | 672.00 | 0.00 | -175438086.3 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.921809E+09 | -604033387.7 | 0.00 | 0.00 | 744.00 | 0.00 | -157755531.2 | 59.44 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: T N2 APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.921798E+09 | -746370440.8 | 0.00 | 0.00 | 744.00 | 0.00 | -175427823.3 | 59.44 | 0.00 | 0.00 |
| February | 0.825389E+09 | -667633286.2 | 0.00 | 0.00 | 672.00 | 0.00 | -157755410.0 | 59.44 | 0.00 | 0.00 |
| March | 0.890975E+09 | -716759592.6 | 0.00 | 0.00 | 744.00 | 0.00 | -174215056.9 | 59.44 | 0.00 | 0.00 |
| April | 0.828951E+09 | -661940683.3 | 0.00 | 0.00 | 720.00 | 0.00 | -167010554.6 | 59.44 | 0.00 | 0.00 |
| May | 0.822598E+09 | -650110036.5 | 0.00 | 0.00 | 744.00 | 0.00 | -172488106.6 | 59.44 | 0.00 | 0.00 |
| June | 0.770954E+09 | -604033367.9 | 0.00 | 0.00 | 720.00 | 0.00 | -166920246.0 | 59.44 | 0.00 | 0.00 |
| July | 0.785744E+09 | -613262453.6 | 0.00 | 0.00 | 744.00 | 0.00 | -172481182.5 | 59.44 | 0.00 | 0.00 |
| August | 0.792968E+09 | -620476565.7 | 0.00 | 0.00 | 744.00 | 0.00 | -172490957.6 | 59.44 | 0.00 | 0.00 |
| September | 0.789824E+09 | -622907582.3 | 0.00 | 0.00 | 720.00 | 0.00 | -166916734.6 | 59.44 | 0.00 | 0.00 |
| October | 0.849109E+09 | -676626722.4 | 0.00 | 0.00 | 744.00 | 0.00 | -172482706.1 | 59.44 | 0.00 | 0.00 |
| November | 0.855110E+09 | -687504136.4 | 0.00 | 0.00 | 720.00 | 0.00 | -167605965.2 | 59.44 | 0.00 | 0.00 |
| December | 0.911050E+09 | -735928720.4 | 0.00 | 0.00 | 744.00 | 0.00 | -175121654.6 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.100445E+11 | -0.800355E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.204092E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.770954E+09 | -746370440.8 | 0.00 | 0.00 | 672.00 | 0.00 | -175427823.3 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.921798E+09 | -604033367.9 | 0.00 | 0.00 | 744.00 | 0.00 | -157755410.0 | 59.44 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: T S1 APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.920410E+09 | -746370814.5 | 0.00 | 0.00 | 744.00 | 0.00 | -174038963.1 | 59.44 | 0.00 | 0.00 |
| February | 0.824620E+09 | -667627029.5 | 0.00 | 0.00 | 672.00 | 0.00 | -156992534.9 | 59.44 | 0.00 | 0.00 |
| March | 0.890378E+09 | -716755019.4 | 0.00 | 0.00 | 744.00 | 0.00 | -173622950.4 | 59.44 | 0.00 | 0.00 |
| April | 0.828942E+09 | -661939347.6 | 0.00 | 0.00 | 720.00 | 0.00 | -167002497.2 | 59.44 | 0.00 | 0.00 |
| May | 0.822598E+09 | -650110175.8 | 0.00 | 0.00 | 744.00 | 0.00 | -172488236.2 | 59.44 | 0.00 | 0.00 |
| June | 0.770954E+09 | -604035878.6 | 0.00 | 0.00 | 720.00 | 0.00 | -166918575.5 | 59.44 | 0.00 | 0.00 |
| July | 0.785744E+09 | -613262453.6 | 0.00 | 0.00 | 744.00 | 0.00 | -172481244.9 | 59.44 | 0.00 | 0.00 |
| August | 0.792967E+09 | -620476488.6 | 0.00 | 0.00 | 744.00 | 0.00 | -172490937.1 | 59.44 | 0.00 | 0.00 |
| September | 0.789824E+09 | -622907624.7 | 0.00 | 0.00 | 720.00 | 0.00 | -166916690.5 | 59.44 | 0.00 | 0.00 |
| October | 0.849109E+09 | -676626793.0 | 0.00 | 0.00 | 744.00 | 0.00 | -172482608.9 | 59.44 | 0.00 | 0.00 |
| November | 0.854881E+09 | -687496867.3 | 0.00 | 0.00 | 720.00 | 0.00 | -167383709.5 | 59.44 | 0.00 | 0.00 |
| December | 0.909804E+09 | -735934552.0 | 0.00 | 0.00 | 744.00 | 0.00 | -173869321.1 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.100402E+11 | -0.800354E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.203669E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.770954E+09 | -746370814.5 | 0.00 | 0.00 | 672.00 | 0.00 | -174038963.1 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.920410E+09 | -604035878.6 | 0.00 | 0.00 | 744.00 | 0.00 | -156992534.9 | 59.44 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: T S2 APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.920410E+09 | -746370824.4 | 0.00 | 0.00 | 744.00 | 0.00 | -174038779.0 | 59.44 | 0.00 | 0.00 |
| February | 0.824620E+09 | -667627000.9 | 0.00 | 0.00 | 672.00 | 0.00 | -156993151.9 | 59.44 | 0.00 | 0.00 |
| March | 0.890372E+09 | -716755246.3 | 0.00 | 0.00 | 744.00 | 0.00 | -173616927.0 | 59.44 | 0.00 | 0.00 |
| April | 0.828942E+09 | -661939369.1 | 0.00 | 0.00 | 720.00 | 0.00 | -167002775.0 | 59.44 | 0.00 | 0.00 |
| May | 0.822598E+09 | -650110174.0 | 0.00 | 0.00 | 744.00 | 0.00 | -172488246.3 | 59.44 | 0.00 | 0.00 |
| June | 0.770954E+09 | -604035761.4 | 0.00 | 0.00 | 720.00 | 0.00 | -166918655.1 | 59.44 | 0.00 | 0.00 |
| July | 0.785744E+09 | -613262453.7 | 0.00 | 0.00 | 744.00 | 0.00 | -172481242.7 | 59.44 | 0.00 | 0.00 |
| August | 0.792967E+09 | -620476494.5 | 0.00 | 0.00 | 744.00 | 0.00 | -172490938.9 | 59.44 | 0.00 | 0.00 |
| September | 0.789824E+09 | -622907623.0 | 0.00 | 0.00 | 720.00 | 0.00 | -166916693.0 | 59.44 | 0.00 | 0.00 |
| October | 0.849109E+09 | -676626789.7 | 0.00 | 0.00 | 744.00 | 0.00 | -172482613.8 | 59.44 | 0.00 | 0.00 |
| November | 0.854880E+09 | -687496838.5 | 0.00 | 0.00 | 720.00 | 0.00 | -167382695.7 | 59.44 | 0.00 | 0.00 |
| December | 0.909805E+09 | -735934594.1 | 0.00 | 0.00 | 744.00 | 0.00 | -173870285.4 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.100402E+11 | -0.800354E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.203668E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.770954E+09 | -746370824.4 | 0.00 | 0.00 | 672.00 | 0.00 | -174038779.0 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.920410E+09 | -604035761.4 | 0.00 | 0.00 | 744.00 | 0.00 | -156993151.9 | 59.44 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
| January | 287.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 304.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 362.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 357.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 389.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 388.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 403.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 348.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 349.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 323.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 314.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 282.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 4111.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 282.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 403.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT GSW HEATING COIL
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT GNW HEATING COIL
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT OFFICE HEATING COIL
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT GNE HEATING COIL
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT GN1 HEATING COIL
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT GN2 HEATING COIL
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT GS1 HEATING COIL
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT GS2 HEATING COIL
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT MSW HEATING COIL
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT MNW HEATING COIL
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 5746062.46 | 527.58 | 04-FEB-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 5746062.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 5746062.46 | 527.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT MSE HEATING COIL
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT MNE HEATING COIL
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 5366617.47 | 577.07 | 04-FEB-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 5366617.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 5366617.47 | 577.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT MN1 HEATING COIL
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT MN2 HEATING COIL
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT MS1 HEATING COIL
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT MS2 HEATING COIL
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT TSW HEATING COIL
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 22188977.73 | 827.73 | 25-JAN-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 68295155.34 | 1621.11 | 04-FEB-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 45382420.80 | 1261.46 | 16-MAR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 12667171.30 | 583.94 | 13-NOV-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 56232346.64 | 1107.94 | 15-DEC-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.204766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 68295155.34 | 1621.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT TNW HEATING COIL
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 62726023.68 | 1002.79 | 25-JAN-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.102960E+09 | 1766.62 | 04-FEB-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 68632953.97 | 1385.21 | 16-MAR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 22458596.71 | 656.25 | 13-NOV-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.101188E+09 | 1236.67 | 15-DEC-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.357966E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.102960E+09 | 1766.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT TSE HEATING COIL
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 20379345.27 | 843.93 | 25-JAN-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 65899668.13 | 1641.14 | 04-FEB-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 36360774.21 | 1278.68 | 16-MAR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 11469334.21 | 578.60 | 13-NOV-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 55653145.01 | 1116.94 | 15-DEC-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.189762E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 65899668.13 | 1641.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT TNE HEATING COIL
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 55779400.00 | 1034.83 | 25-JAN-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 96465935.30 | 1786.62 | 04-FEB-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 53758666.43 | 1421.52 | 16-MAR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 19076815.71 | 652.56 | 13-NOV-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 97035558.82 | 1245.32 | 15-DEC-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.322116E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 97035558.82 | 1786.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT TN1 HEATING COIL
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 23422848.33 | 608.38 | 25-JAN-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 51784445.39 | 1157.09 | 04-FEB-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 24576133.28 | 880.83 | 16-MAR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 3640578.46 | 226.75 | 13-NOV-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 39517613.05 | 683.73 | 15-DEC-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.142942E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 51784445.39 | 1157.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT TN2 HEATING COIL
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 23436571.52 | 611.21 | 25-JAN-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 51865598.72 | 1159.64 | 04-FEB-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 24425531.91 | 884.17 | 16-MAR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 3600784.36 | 225.21 | 13-NOV-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 39835233.26 | 685.44 | 15-DEC-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.143164E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 51865598.72 | 1159.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT TS1 HEATING COIL
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 4307304.97 | 374.41 | 25-JAN-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 26082351.33 | 1002.96 | 04-FEB-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 12347505.63 | 699.50 | 16-MAR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 546514.79 | 120.71 | 13-NOV-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 12071330.54 | 512.81 | 15-DEC-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 55355007.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 26082351.33 | 1002.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT TS2 HEATING COIL
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 4336491.89 | 376.43 | 25-JAN-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 26181656.43 | 1005.19 | 04-FEB-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 12303776.71 | 701.07 | 16-MAR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 535403.29 | 119.30 | 13-NOV-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 12177486.73 | 514.29 | 15-DEC-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 55534815.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 26181656.43 | 1005.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT GSW COOLING COIL
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.243647E+10 | 0.196221E+10 | 3050.06 | 02-JAN-15:00 | 2405.95 | 0.00 |
| February | 0.00 | 0.00 | 0.249525E+10 | 0.199332E+10 | 3188.49 | 11-FEB-16:30 | 2333.31 | 0.00 |
| March | 0.00 | 0.00 | 0.286255E+10 | 0.216925E+10 | 2846.18 | 13-MAR-16:25 | 2193.10 | 0.00 |
| April | 0.00 | 0.00 | 0.357557E+10 | 0.275375E+10 | 3098.87 | 15-APR-16:50 | 2490.42 | 0.00 |
| May | 0.00 | 0.00 | 0.489736E+10 | 0.347783E+10 | 3377.78 | 29-MAY-16:30 | 2522.22 | 0.00 |
| June | 0.00 | 0.00 | 0.539080E+10 | 0.368450E+10 | 3319.40 | 08-JUN-16:13 | 2281.96 | 0.00 |
| July | 0.00 | 0.00 | 0.594950E+10 | 0.417671E+10 | 3492.29 | 22-JUL-15:50 | 2451.42 | 0.00 |
| August | 0.00 | 0.00 | 0.617017E+10 | 0.427429E+10 | 3609.44 | 16-AUG-16:02 | 2631.18 | 0.00 |
| September | 0.00 | 0.00 | 0.605740E+10 | 0.430069E+10 | 3783.31 | 17-SEP-16:10 | 2799.74 | 0.00 |
| October | 0.00 | 0.00 | 0.580316E+10 | 0.424168E+10 | 3801.29 | 29-OCT-14:20 | 2644.23 | 0.00 |
| November | 0.00 | 0.00 | 0.435194E+10 | 0.322248E+10 | 3223.41 | 22-NOV-14:30 | 2412.18 | 0.00 |
| December | 0.00 | 0.00 | 0.300292E+10 | 0.230178E+10 | 3340.58 | 10-DEC-15:00 | 2573.89 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.529931E+11 | 0.385585E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.243647E+10 | 0.196221E+10 | 2846.18 | 2193.10 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.617017E+10 | 0.430069E+10 | 3801.29 | 2799.74 | 0.00 |
Report: CoilReportMonthly
For: SPLIT GNW COOLING COIL
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.145351E+10 | 0.108440E+10 | 2010.91 | 02-JAN-15:00 | 1479.18 | 0.00 |
| February | 0.00 | 0.00 | 0.172075E+10 | 0.130644E+10 | 2505.12 | 11-FEB-16:30 | 1734.14 | 0.00 |
| March | 0.00 | 0.00 | 0.228660E+10 | 0.166864E+10 | 2505.17 | 13-MAR-16:25 | 1862.35 | 0.00 |
| April | 0.00 | 0.00 | 0.326584E+10 | 0.248263E+10 | 2919.62 | 15-APR-17:00 | 2346.07 | 0.00 |
| May | 0.00 | 0.00 | 0.492378E+10 | 0.350084E+10 | 3376.88 | 29-MAY-17:10 | 2515.37 | 0.00 |
| June | 0.00 | 0.00 | 0.552625E+10 | 0.380037E+10 | 3441.07 | 08-JUN-16:30 | 2373.09 | 0.00 |
| July | 0.00 | 0.00 | 0.602802E+10 | 0.424747E+10 | 3501.24 | 27-JUL-16:30 | 2732.86 | 0.00 |
| August | 0.00 | 0.00 | 0.607820E+10 | 0.419370E+10 | 3546.79 | 16-AUG-16:02 | 2555.00 | 0.00 |
| September | 0.00 | 0.00 | 0.566893E+10 | 0.396207E+10 | 3478.29 | 18-SEP-16:10 | 2499.97 | 0.00 |
| October | 0.00 | 0.00 | 0.506204E+10 | 0.359039E+10 | 3272.03 | 03-OCT-16:30 | 2324.41 | 0.00 |
| November | 0.00 | 0.00 | 0.348945E+10 | 0.246808E+10 | 2802.26 | 04-NOV-16:10 | 1767.22 | 0.00 |
| December | 0.00 | 0.00 | 0.203057E+10 | 0.145837E+10 | 2440.11 | 10-DEC-15:10 | 1785.89 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.475339E+11 | 0.337634E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.145351E+10 | 0.108440E+10 | 2010.91 | 1479.18 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.607820E+10 | 0.424747E+10 | 3546.79 | 2732.86 | 0.00 |
Report: CoilReportMonthly
For: SPLIT OFFICE COOLING COIL
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.182697E+10 | 0.158037E+10 | 7993.68 | 30-JAN-08:62 | 5042.34 | 0.00 |
| February | 0.00 | 0.00 | 0.188825E+10 | 0.158354E+10 | 7991.84 | 02-FEB-08:62 | 4992.32 | 0.00 |
| March | 0.00 | 0.00 | 0.218151E+10 | 0.177060E+10 | 8196.21 | 14-MAR-07:02 | 4336.93 | 0.00 |
| April | 0.00 | 0.00 | 0.237050E+10 | 0.192066E+10 | 8185.36 | 14-APR-07:02 | 4590.88 | 0.00 |
| May | 0.00 | 0.00 | 0.323944E+10 | 0.244525E+10 | 8202.20 | 31-MAY-07:02 | 4315.52 | 0.00 |
| June | 0.00 | 0.00 | 0.375500E+10 | 0.267680E+10 | 8222.94 | 22-JUN-07:02 | 4120.34 | 0.00 |
| July | 0.00 | 0.00 | 0.391253E+10 | 0.281785E+10 | 8222.70 | 24-JUL-06:03 | 4497.40 | 0.00 |
| August | 0.00 | 0.00 | 0.433019E+10 | 0.310967E+10 | 8222.07 | 10-AUG-07:02 | 4256.82 | 0.00 |
| September | 0.00 | 0.00 | 0.403738E+10 | 0.293867E+10 | 8223.13 | 28-SEP-07:02 | 4295.59 | 0.00 |
| October | 0.00 | 0.00 | 0.387776E+10 | 0.293659E+10 | 8220.97 | 05-OCT-07:02 | 4429.59 | 0.00 |
| November | 0.00 | 0.00 | 0.292655E+10 | 0.227602E+10 | 8222.70 | 10-NOV-08:62 | 4455.77 | 0.00 |
| December | 0.00 | 0.00 | 0.193211E+10 | 0.163624E+10 | 8132.00 | 08-DEC-08:62 | 4753.63 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.362782E+11 | 0.276923E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.182697E+10 | 0.158037E+10 | 7991.84 | 4120.34 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.433019E+10 | 0.310967E+10 | 8223.13 | 5042.34 | 0.00 |
Report: CoilReportMonthly
For: SPLIT GNE COOLING COIL
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.150392E+10 | 0.111818E+10 | 1996.62 | 07-JAN-13:00 | 1397.70 | 0.00 |
| February | 0.00 | 0.00 | 0.173015E+10 | 0.130499E+10 | 2146.85 | 11-FEB-14:00 | 1504.36 | 0.00 |
| March | 0.00 | 0.00 | 0.226848E+10 | 0.163994E+10 | 2252.53 | 14-MAR-10:10 | 1346.32 | 0.00 |
| April | 0.00 | 0.00 | 0.326482E+10 | 0.246744E+10 | 2559.43 | 15-APR-16:50 | 2018.68 | 0.00 |
| May | 0.00 | 0.00 | 0.493715E+10 | 0.349596E+10 | 3070.35 | 22-MAY-15:30 | 2223.88 | 0.00 |
| June | 0.00 | 0.00 | 0.563139E+10 | 0.387435E+10 | 3148.48 | 08-JUN-16:02 | 2125.77 | 0.00 |
| July | 0.00 | 0.00 | 0.609263E+10 | 0.428779E+10 | 3252.77 | 22-JUL-16:03 | 2271.58 | 0.00 |
| August | 0.00 | 0.00 | 0.608479E+10 | 0.418412E+10 | 3339.11 | 20-AUG-12:00 | 2334.50 | 0.00 |
| September | 0.00 | 0.00 | 0.574241E+10 | 0.400918E+10 | 3268.22 | 18-SEP-16:10 | 2313.12 | 0.00 |
| October | 0.00 | 0.00 | 0.509871E+10 | 0.360540E+10 | 3109.55 | 03-OCT-11:00 | 2090.35 | 0.00 |
| November | 0.00 | 0.00 | 0.351159E+10 | 0.247278E+10 | 2744.20 | 04-NOV-16:10 | 1723.71 | 0.00 |
| December | 0.00 | 0.00 | 0.196832E+10 | 0.139714E+10 | 2300.71 | 10-DEC-14:00 | 1623.78 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.478344E+11 | 0.338573E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.150392E+10 | 0.111818E+10 | 1996.62 | 1346.32 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.609263E+10 | 0.428779E+10 | 3339.11 | 2334.50 | 0.00 |
Report: CoilReportMonthly
For: SPLIT GN1 COOLING COIL
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.141941E+10 | 0.105993E+10 | 1677.76 | 07-JAN-13:00 | 1173.96 | 0.00 |
| February | 0.00 | 0.00 | 0.159473E+10 | 0.120370E+10 | 1874.27 | 11-FEB-17:10 | 1252.34 | 0.00 |
| March | 0.00 | 0.00 | 0.203617E+10 | 0.147616E+10 | 1874.81 | 13-MAR-16:25 | 1359.16 | 0.00 |
| April | 0.00 | 0.00 | 0.283739E+10 | 0.213530E+10 | 2118.56 | 15-APR-17:00 | 1662.95 | 0.00 |
| May | 0.00 | 0.00 | 0.423030E+10 | 0.298390E+10 | 2545.77 | 29-MAY-17:10 | 1866.58 | 0.00 |
| June | 0.00 | 0.00 | 0.481211E+10 | 0.327916E+10 | 2598.68 | 08-JUN-16:40 | 1753.19 | 0.00 |
| July | 0.00 | 0.00 | 0.518313E+10 | 0.359137E+10 | 2689.74 | 27-JUL-17:20 | 2044.09 | 0.00 |
| August | 0.00 | 0.00 | 0.518998E+10 | 0.352687E+10 | 2645.22 | 21-AUG-16:01 | 1848.97 | 0.00 |
| September | 0.00 | 0.00 | 0.485976E+10 | 0.334872E+10 | 2679.29 | 18-SEP-17:20 | 1856.18 | 0.00 |
| October | 0.00 | 0.00 | 0.436964E+10 | 0.306243E+10 | 2529.66 | 03-OCT-16:03 | 1768.68 | 0.00 |
| November | 0.00 | 0.00 | 0.310880E+10 | 0.219056E+10 | 2320.02 | 04-NOV-16:10 | 1468.73 | 0.00 |
| December | 0.00 | 0.00 | 0.187867E+10 | 0.134352E+10 | 1898.49 | 10-DEC-14:00 | 1336.30 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.415201E+11 | 0.292016E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.141941E+10 | 0.105993E+10 | 1677.76 | 1173.96 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.518998E+10 | 0.359137E+10 | 2689.74 | 2044.09 | 0.00 |
Report: CoilReportMonthly
For: SPLIT GN2 COOLING COIL
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.142334E+10 | 0.106318E+10 | 1679.94 | 07-JAN-13:00 | 1175.78 | 0.00 |
| February | 0.00 | 0.00 | 0.159611E+10 | 0.120480E+10 | 1866.97 | 11-FEB-17:10 | 1246.58 | 0.00 |
| March | 0.00 | 0.00 | 0.203740E+10 | 0.147708E+10 | 1869.25 | 13-MAR-16:25 | 1354.69 | 0.00 |
| April | 0.00 | 0.00 | 0.283719E+10 | 0.213500E+10 | 2113.20 | 15-APR-17:00 | 1658.40 | 0.00 |
| May | 0.00 | 0.00 | 0.423059E+10 | 0.298397E+10 | 2539.86 | 29-MAY-17:10 | 1861.56 | 0.00 |
| June | 0.00 | 0.00 | 0.481649E+10 | 0.328267E+10 | 2596.15 | 08-JUN-16:40 | 1751.52 | 0.00 |
| July | 0.00 | 0.00 | 0.518549E+10 | 0.359320E+10 | 2685.77 | 27-JUL-17:20 | 2040.57 | 0.00 |
| August | 0.00 | 0.00 | 0.519012E+10 | 0.352681E+10 | 2641.54 | 21-AUG-16:01 | 1846.05 | 0.00 |
| September | 0.00 | 0.00 | 0.486262E+10 | 0.335095E+10 | 2675.43 | 18-SEP-17:20 | 1852.87 | 0.00 |
| October | 0.00 | 0.00 | 0.437100E+10 | 0.306337E+10 | 2527.45 | 03-OCT-16:03 | 1766.85 | 0.00 |
| November | 0.00 | 0.00 | 0.310995E+10 | 0.219140E+10 | 2319.99 | 04-NOV-16:10 | 1468.75 | 0.00 |
| December | 0.00 | 0.00 | 0.187599E+10 | 0.134122E+10 | 1898.48 | 10-DEC-14:00 | 1336.41 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.415363E+11 | 0.292136E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.142334E+10 | 0.106318E+10 | 1679.94 | 1175.78 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.519012E+10 | 0.359320E+10 | 2685.77 | 2040.57 | 0.00 |
Report: CoilReportMonthly
For: SPLIT GS1 COOLING COIL
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.248744E+10 | 0.201563E+10 | 2669.21 | 02-JAN-14:40 | 2122.83 | 0.00 |
| February | 0.00 | 0.00 | 0.242680E+10 | 0.194438E+10 | 2562.20 | 11-FEB-14:00 | 1897.72 | 0.00 |
| March | 0.00 | 0.00 | 0.266150E+10 | 0.201920E+10 | 2244.16 | 13-MAR-16:02 | 1691.23 | 0.00 |
| April | 0.00 | 0.00 | 0.317139E+10 | 0.242246E+10 | 2364.61 | 01-APR-16:05 | 1642.39 | 0.00 |
| May | 0.00 | 0.00 | 0.422277E+10 | 0.297287E+10 | 2562.65 | 29-MAY-16:04 | 1880.91 | 0.00 |
| June | 0.00 | 0.00 | 0.469307E+10 | 0.317405E+10 | 2513.73 | 03-JUN-16:03 | 1783.98 | 0.00 |
| July | 0.00 | 0.00 | 0.512283E+10 | 0.353315E+10 | 2733.00 | 22-JUL-16:03 | 1875.18 | 0.00 |
| August | 0.00 | 0.00 | 0.530418E+10 | 0.362171E+10 | 2818.05 | 20-AUG-12:00 | 1938.98 | 0.00 |
| September | 0.00 | 0.00 | 0.527690E+10 | 0.370580E+10 | 3023.81 | 20-SEP-14:10 | 2189.24 | 0.00 |
| October | 0.00 | 0.00 | 0.514844E+10 | 0.373930E+10 | 3130.23 | 29-OCT-14:10 | 2185.95 | 0.00 |
| November | 0.00 | 0.00 | 0.401332E+10 | 0.297888E+10 | 2766.16 | 22-NOV-12:50 | 2120.07 | 0.00 |
| December | 0.00 | 0.00 | 0.291929E+10 | 0.224693E+10 | 2800.90 | 10-DEC-14:30 | 2140.80 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.474479E+11 | 0.343744E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.242680E+10 | 0.194438E+10 | 2244.16 | 1642.39 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.530418E+10 | 0.373930E+10 | 3130.23 | 2189.24 | 0.00 |
Report: CoilReportMonthly
For: SPLIT GS2 COOLING COIL
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.271533E+10 | 0.221768E+10 | 2871.33 | 02-JAN-14:40 | 2308.91 | 0.00 |
| February | 0.00 | 0.00 | 0.260912E+10 | 0.210382E+10 | 2680.69 | 11-FEB-14:30 | 2006.73 | 0.00 |
| March | 0.00 | 0.00 | 0.286853E+10 | 0.219651E+10 | 2345.27 | 04-MAR-14:00 | 1699.70 | 0.00 |
| April | 0.00 | 0.00 | 0.343277E+10 | 0.264932E+10 | 2482.06 | 01-APR-16:05 | 1745.74 | 0.00 |
| May | 0.00 | 0.00 | 0.454284E+10 | 0.324406E+10 | 2717.32 | 29-MAY-16:04 | 2021.43 | 0.00 |
| June | 0.00 | 0.00 | 0.504155E+10 | 0.347014E+10 | 2668.52 | 03-JUN-16:03 | 1924.65 | 0.00 |
| July | 0.00 | 0.00 | 0.550511E+10 | 0.386385E+10 | 2890.16 | 22-JUL-16:03 | 2015.13 | 0.00 |
| August | 0.00 | 0.00 | 0.567200E+10 | 0.393809E+10 | 3007.07 | 20-AUG-12:00 | 2108.81 | 0.00 |
| September | 0.00 | 0.00 | 0.564876E+10 | 0.403012E+10 | 3124.01 | 20-SEP-14:10 | 2281.68 | 0.00 |
| October | 0.00 | 0.00 | 0.552102E+10 | 0.406592E+10 | 3311.75 | 29-OCT-14:10 | 2347.49 | 0.00 |
| November | 0.00 | 0.00 | 0.430588E+10 | 0.323471E+10 | 2865.78 | 22-NOV-12:50 | 2212.64 | 0.00 |
| December | 0.00 | 0.00 | 0.314680E+10 | 0.244613E+10 | 2970.07 | 10-DEC-14:30 | 2297.02 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.510097E+11 | 0.374603E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.260912E+10 | 0.210382E+10 | 2345.27 | 1699.70 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.567200E+10 | 0.406592E+10 | 3311.75 | 2347.49 | 0.00 |
Report: CoilReportMonthly
For: SPLIT MSW COOLING COIL
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.494630E+10 | 0.397000E+10 | 6847.28 | 02-JAN-15:00 | 5408.97 | 0.00 |
| February | 0.00 | 0.00 | 0.541011E+10 | 0.430342E+10 | 7478.72 | 11-FEB-16:30 | 5470.56 | 0.00 |
| March | 0.00 | 0.00 | 0.668288E+10 | 0.506810E+10 | 6751.94 | 13-MAR-16:25 | 5233.34 | 0.00 |
| April | 0.00 | 0.00 | 0.825459E+10 | 0.637282E+10 | 7273.02 | 15-APR-16:40 | 5855.42 | 0.00 |
| May | 0.00 | 0.00 | 0.109726E+11 | 0.775457E+10 | 8002.23 | 29-MAY-16:20 | 5979.23 | 0.00 |
| June | 0.00 | 0.00 | 0.118040E+11 | 0.802011E+10 | 7674.59 | 08-JUN-16:13 | 5227.55 | 0.00 |
| July | 0.00 | 0.00 | 0.124758E+11 | 0.866258E+10 | 7819.80 | 22-JUL-15:40 | 5407.14 | 0.00 |
| August | 0.00 | 0.00 | 0.126663E+11 | 0.859972E+10 | 8015.21 | 16-AUG-16:02 | 5745.82 | 0.00 |
| September | 0.00 | 0.00 | 0.122345E+11 | 0.849827E+10 | 8375.08 | 17-SEP-16:10 | 6097.14 | 0.00 |
| October | 0.00 | 0.00 | 0.116087E+11 | 0.831438E+10 | 8502.73 | 29-OCT-14:10 | 5797.99 | 0.00 |
| November | 0.00 | 0.00 | 0.864685E+10 | 0.627876E+10 | 7225.31 | 22-NOV-14:30 | 5309.40 | 0.00 |
| December | 0.00 | 0.00 | 0.593033E+10 | 0.447786E+10 | 7495.55 | 10-DEC-15:00 | 5713.87 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.111633E+12 | 0.803206E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.494630E+10 | 0.397000E+10 | 6751.94 | 5227.55 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.126663E+11 | 0.866258E+10 | 8502.73 | 6097.14 | 0.00 |
Report: CoilReportMonthly
For: SPLIT MNW COOLING COIL
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.288746E+10 | 0.212952E+10 | 4343.01 | 02-JAN-15:00 | 3162.32 | 0.00 |
| February | 0.00 | 0.00 | 0.377598E+10 | 0.285452E+10 | 5838.19 | 11-FEB-16:30 | 4032.43 | 0.00 |
| March | 0.00 | 0.00 | 0.546789E+10 | 0.400200E+10 | 6037.93 | 13-MAR-16:25 | 4537.83 | 0.00 |
| April | 0.00 | 0.00 | 0.759139E+10 | 0.579009E+10 | 6835.01 | 15-APR-17:00 | 5503.96 | 0.00 |
| May | 0.00 | 0.00 | 0.110067E+11 | 0.778663E+10 | 7983.91 | 29-MAY-16:30 | 5995.53 | 0.00 |
| June | 0.00 | 0.00 | 0.120599E+11 | 0.823900E+10 | 7949.69 | 08-JUN-16:30 | 5442.49 | 0.00 |
| July | 0.00 | 0.00 | 0.126069E+11 | 0.878112E+10 | 7778.65 | 27-JUL-16:13 | 6025.61 | 0.00 |
| August | 0.00 | 0.00 | 0.124388E+11 | 0.840388E+10 | 7871.19 | 16-AUG-16:02 | 5575.97 | 0.00 |
| September | 0.00 | 0.00 | 0.113784E+11 | 0.776356E+10 | 7562.81 | 18-SEP-16:10 | 5317.52 | 0.00 |
| October | 0.00 | 0.00 | 0.100129E+11 | 0.693250E+10 | 7134.29 | 03-OCT-16:30 | 4955.05 | 0.00 |
| November | 0.00 | 0.00 | 0.680300E+10 | 0.468981E+10 | 6011.01 | 04-NOV-16:10 | 3645.10 | 0.00 |
| December | 0.00 | 0.00 | 0.389676E+10 | 0.273016E+10 | 5302.78 | 10-DEC-15:10 | 3813.67 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.999261E+11 | 0.701028E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.288746E+10 | 0.212952E+10 | 4343.01 | 3162.32 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.126069E+11 | 0.878112E+10 | 7983.91 | 6025.61 | 0.00 |
Report: CoilReportMonthly
For: SPLIT MSE COOLING COIL
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.507651E+10 | 0.405984E+10 | 6612.40 | 02-JAN-14:40 | 5270.25 | 0.00 |
| February | 0.00 | 0.00 | 0.543678E+10 | 0.429836E+10 | 6742.69 | 11-FEB-14:00 | 5005.11 | 0.00 |
| March | 0.00 | 0.00 | 0.666389E+10 | 0.501555E+10 | 6343.23 | 04-MAR-14:00 | 4501.36 | 0.00 |
| April | 0.00 | 0.00 | 0.825554E+10 | 0.633330E+10 | 6336.90 | 15-APR-16:03 | 5003.76 | 0.00 |
| May | 0.00 | 0.00 | 0.110042E+11 | 0.773940E+10 | 7180.69 | 29-MAY-16:10 | 5261.09 | 0.00 |
| June | 0.00 | 0.00 | 0.120267E+11 | 0.816863E+10 | 6878.84 | 08-JUN-16:02 | 4567.13 | 0.00 |
| July | 0.00 | 0.00 | 0.126185E+11 | 0.874663E+10 | 7369.42 | 30-JUL-16:05 | 5099.85 | 0.00 |
| August | 0.00 | 0.00 | 0.126779E+11 | 0.857307E+10 | 7667.68 | 20-AUG-12:00 | 5277.99 | 0.00 |
| September | 0.00 | 0.00 | 0.123933E+11 | 0.859409E+10 | 7985.54 | 20-SEP-14:00 | 5656.76 | 0.00 |
| October | 0.00 | 0.00 | 0.116870E+11 | 0.834055E+10 | 8189.11 | 29-OCT-14:00 | 5571.27 | 0.00 |
| November | 0.00 | 0.00 | 0.869749E+10 | 0.628537E+10 | 7272.88 | 22-NOV-12:30 | 5454.22 | 0.00 |
| December | 0.00 | 0.00 | 0.580494E+10 | 0.434278E+10 | 7043.84 | 10-DEC-14:30 | 5264.28 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.112343E+12 | 0.804976E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.507651E+10 | 0.405984E+10 | 6336.90 | 4501.36 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.126779E+11 | 0.874663E+10 | 8189.11 | 5656.76 | 0.00 |
Report: CoilReportMonthly
For: SPLIT MNE COOLING COIL
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.298176E+10 | 0.219055E+10 | 4341.24 | 07-JAN-13:00 | 2998.60 | 0.00 |
| February | 0.00 | 0.00 | 0.379096E+10 | 0.284736E+10 | 4855.59 | 11-FEB-14:00 | 3392.63 | 0.00 |
| March | 0.00 | 0.00 | 0.542164E+10 | 0.393234E+10 | 5425.61 | 14-MAR-10:10 | 3245.66 | 0.00 |
| April | 0.00 | 0.00 | 0.758425E+10 | 0.575204E+10 | 5872.87 | 15-APR-16:30 | 4623.57 | 0.00 |
| May | 0.00 | 0.00 | 0.110296E+11 | 0.777177E+10 | 7200.47 | 22-MAY-15:30 | 5122.55 | 0.00 |
| June | 0.00 | 0.00 | 0.122737E+11 | 0.838782E+10 | 7109.13 | 08-JUN-16:02 | 4729.21 | 0.00 |
| July | 0.00 | 0.00 | 0.127416E+11 | 0.886552E+10 | 7125.28 | 30-JUL-16:05 | 4943.29 | 0.00 |
| August | 0.00 | 0.00 | 0.124428E+11 | 0.837814E+10 | 7166.91 | 20-AUG-12:00 | 4891.87 | 0.00 |
| September | 0.00 | 0.00 | 0.115320E+11 | 0.786095E+10 | 6998.60 | 18-SEP-16:10 | 4826.40 | 0.00 |
| October | 0.00 | 0.00 | 0.100858E+11 | 0.696116E+10 | 6730.12 | 03-OCT-11:00 | 4405.22 | 0.00 |
| November | 0.00 | 0.00 | 0.684266E+10 | 0.469305E+10 | 5840.96 | 04-NOV-16:10 | 3525.14 | 0.00 |
| December | 0.00 | 0.00 | 0.375743E+10 | 0.259789E+10 | 4881.58 | 10-DEC-14:00 | 3367.56 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.100484E+12 | 0.702386E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.298176E+10 | 0.219055E+10 | 4341.24 | 2998.60 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.127416E+11 | 0.886552E+10 | 7200.47 | 5122.55 | 0.00 |
Report: CoilReportMonthly
For: SPLIT MN1 COOLING COIL
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.288000E+10 | 0.213517E+10 | 3564.45 | 07-JAN-13:00 | 2467.93 | 0.00 |
| February | 0.00 | 0.00 | 0.345135E+10 | 0.259434E+10 | 4101.15 | 11-FEB-17:10 | 2726.13 | 0.00 |
| March | 0.00 | 0.00 | 0.470946E+10 | 0.342553E+10 | 4299.07 | 13-MAR-16:12 | 3133.69 | 0.00 |
| April | 0.00 | 0.00 | 0.635198E+10 | 0.479335E+10 | 4674.83 | 15-APR-17:00 | 3668.76 | 0.00 |
| May | 0.00 | 0.00 | 0.914220E+10 | 0.641942E+10 | 5681.26 | 29-MAY-17:10 | 4141.49 | 0.00 |
| June | 0.00 | 0.00 | 0.101757E+11 | 0.689316E+10 | 5672.93 | 08-JUN-16:13 | 3774.21 | 0.00 |
| July | 0.00 | 0.00 | 0.105834E+11 | 0.725970E+10 | 5675.67 | 27-JUL-18:00 | 4146.69 | 0.00 |
| August | 0.00 | 0.00 | 0.104199E+11 | 0.695621E+10 | 5534.20 | 16-AUG-16:02 | 3811.71 | 0.00 |
| September | 0.00 | 0.00 | 0.962371E+10 | 0.650103E+10 | 5573.07 | 18-SEP-16:20 | 3840.50 | 0.00 |
| October | 0.00 | 0.00 | 0.857230E+10 | 0.589070E+10 | 5273.48 | 03-OCT-16:03 | 3608.24 | 0.00 |
| November | 0.00 | 0.00 | 0.607417E+10 | 0.419461E+10 | 4844.13 | 04-NOV-16:10 | 2976.64 | 0.00 |
| December | 0.00 | 0.00 | 0.365767E+10 | 0.256547E+10 | 3939.16 | 10-DEC-14:00 | 2721.59 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.856418E+11 | 0.596287E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.288000E+10 | 0.213517E+10 | 3564.45 | 2467.93 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.105834E+11 | 0.725970E+10 | 5681.26 | 4146.69 | 0.00 |
Report: CoilReportMonthly
For: SPLIT MN2 COOLING COIL
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.288817E+10 | 0.214207E+10 | 3569.06 | 07-JAN-13:00 | 2471.69 | 0.00 |
| February | 0.00 | 0.00 | 0.345433E+10 | 0.259680E+10 | 4083.30 | 11-FEB-17:10 | 2712.07 | 0.00 |
| March | 0.00 | 0.00 | 0.471263E+10 | 0.342814E+10 | 4289.21 | 13-MAR-16:12 | 3125.92 | 0.00 |
| April | 0.00 | 0.00 | 0.635171E+10 | 0.479279E+10 | 4663.33 | 15-APR-17:00 | 3659.06 | 0.00 |
| May | 0.00 | 0.00 | 0.914277E+10 | 0.641951E+10 | 5667.12 | 29-MAY-17:10 | 4129.49 | 0.00 |
| June | 0.00 | 0.00 | 0.101834E+11 | 0.689920E+10 | 5666.46 | 08-JUN-16:13 | 3769.83 | 0.00 |
| July | 0.00 | 0.00 | 0.105879E+11 | 0.726315E+10 | 5665.02 | 27-JUL-18:00 | 4137.42 | 0.00 |
| August | 0.00 | 0.00 | 0.104200E+11 | 0.695595E+10 | 5524.46 | 16-AUG-16:02 | 3804.26 | 0.00 |
| September | 0.00 | 0.00 | 0.962919E+10 | 0.650517E+10 | 5564.87 | 18-SEP-16:20 | 3833.93 | 0.00 |
| October | 0.00 | 0.00 | 0.857482E+10 | 0.589236E+10 | 5269.39 | 03-OCT-16:03 | 3604.98 | 0.00 |
| November | 0.00 | 0.00 | 0.607698E+10 | 0.419670E+10 | 4844.10 | 04-NOV-16:10 | 2976.74 | 0.00 |
| December | 0.00 | 0.00 | 0.365230E+10 | 0.256102E+10 | 3939.99 | 10-DEC-14:00 | 2722.57 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.856743E+11 | 0.596529E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.288817E+10 | 0.214207E+10 | 3569.06 | 2471.69 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.105879E+11 | 0.726315E+10 | 5667.12 | 4137.42 | 0.00 |
Report: CoilReportMonthly
For: SPLIT MS1 COOLING COIL
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.507582E+10 | 0.411339E+10 | 5863.35 | 02-JAN-14:40 | 4685.95 | 0.00 |
| February | 0.00 | 0.00 | 0.516884E+10 | 0.412962E+10 | 5793.26 | 11-FEB-14:30 | 4322.51 | 0.00 |
| March | 0.00 | 0.00 | 0.597662E+10 | 0.454071E+10 | 5127.94 | 04-MAR-14:00 | 3679.19 | 0.00 |
| April | 0.00 | 0.00 | 0.702358E+10 | 0.537942E+10 | 5303.73 | 01-APR-16:05 | 3709.02 | 0.00 |
| May | 0.00 | 0.00 | 0.910908E+10 | 0.638686E+10 | 5722.09 | 29-MAY-16:04 | 4193.55 | 0.00 |
| June | 0.00 | 0.00 | 0.991695E+10 | 0.667196E+10 | 5427.98 | 08-JUN-16:02 | 3602.89 | 0.00 |
| July | 0.00 | 0.00 | 0.104499E+11 | 0.713916E+10 | 5811.64 | 22-JUL-16:03 | 3940.44 | 0.00 |
| August | 0.00 | 0.00 | 0.106498E+11 | 0.715146E+10 | 5901.70 | 20-AUG-12:00 | 3982.01 | 0.00 |
| September | 0.00 | 0.00 | 0.104877E+11 | 0.723866E+10 | 6437.74 | 20-SEP-14:00 | 4579.61 | 0.00 |
| October | 0.00 | 0.00 | 0.101819E+11 | 0.728233E+10 | 6785.78 | 29-OCT-14:10 | 4679.29 | 0.00 |
| November | 0.00 | 0.00 | 0.794921E+10 | 0.582032E+10 | 6089.64 | 22-NOV-12:30 | 4625.90 | 0.00 |
| December | 0.00 | 0.00 | 0.582361E+10 | 0.444238E+10 | 6091.73 | 10-DEC-14:30 | 4625.09 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.978130E+11 | 0.702962E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.507582E+10 | 0.411339E+10 | 5127.94 | 3602.89 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.106498E+11 | 0.728233E+10 | 6785.78 | 4685.95 | 0.00 |
Report: CoilReportMonthly
For: SPLIT MS2 COOLING COIL
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.508180E+10 | 0.411848E+10 | 5869.17 | 02-JAN-14:40 | 4691.67 | 0.00 |
| February | 0.00 | 0.00 | 0.517135E+10 | 0.413170E+10 | 5791.65 | 11-FEB-14:30 | 4321.56 | 0.00 |
| March | 0.00 | 0.00 | 0.597930E+10 | 0.454304E+10 | 5134.17 | 04-MAR-14:00 | 3684.81 | 0.00 |
| April | 0.00 | 0.00 | 0.702339E+10 | 0.537889E+10 | 5290.35 | 01-APR-16:05 | 3698.61 | 0.00 |
| May | 0.00 | 0.00 | 0.910969E+10 | 0.638695E+10 | 5712.56 | 29-MAY-16:04 | 4185.70 | 0.00 |
| June | 0.00 | 0.00 | 0.992481E+10 | 0.667805E+10 | 5425.15 | 03-JUN-16:03 | 3841.76 | 0.00 |
| July | 0.00 | 0.00 | 0.104545E+11 | 0.714261E+10 | 5805.92 | 22-JUL-16:03 | 3936.35 | 0.00 |
| August | 0.00 | 0.00 | 0.106499E+11 | 0.715117E+10 | 5913.28 | 20-AUG-12:00 | 3992.16 | 0.00 |
| September | 0.00 | 0.00 | 0.104930E+11 | 0.724266E+10 | 6440.30 | 20-SEP-14:00 | 4582.50 | 0.00 |
| October | 0.00 | 0.00 | 0.101841E+11 | 0.728377E+10 | 6786.81 | 29-OCT-14:10 | 4680.73 | 0.00 |
| November | 0.00 | 0.00 | 0.795131E+10 | 0.582180E+10 | 6103.73 | 22-NOV-12:30 | 4638.74 | 0.00 |
| December | 0.00 | 0.00 | 0.581936E+10 | 0.443847E+10 | 6089.82 | 10-DEC-14:30 | 4623.64 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.978425E+11 | 0.703176E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.508180E+10 | 0.411848E+10 | 5134.17 | 3684.81 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.106499E+11 | 0.728377E+10 | 6786.81 | 4691.67 | 0.00 |
Report: CoilReportMonthly
For: SPLIT TSW COOLING COIL
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.213127E+10 | 0.170224E+10 | 4378.78 | 02-JAN-15:00 | 3530.66 | 0.00 |
| February | 0.00 | 0.00 | 0.259960E+10 | 0.207600E+10 | 4794.63 | 11-FEB-16:20 | 3601.57 | 0.00 |
| March | 0.00 | 0.00 | 0.333712E+10 | 0.252717E+10 | 4262.64 | 13-MAR-16:25 | 3364.59 | 0.00 |
| April | 0.00 | 0.00 | 0.434081E+10 | 0.336768E+10 | 4729.40 | 15-APR-16:30 | 3883.63 | 0.00 |
| May | 0.00 | 0.00 | 0.609319E+10 | 0.432973E+10 | 5238.86 | 29-MAY-16:20 | 4006.59 | 0.00 |
| June | 0.00 | 0.00 | 0.664999E+10 | 0.455542E+10 | 4966.94 | 08-JUN-16:02 | 3477.72 | 0.00 |
| July | 0.00 | 0.00 | 0.704621E+10 | 0.495689E+10 | 5086.59 | 22-JUL-15:40 | 3628.61 | 0.00 |
| August | 0.00 | 0.00 | 0.705599E+10 | 0.482384E+10 | 5176.66 | 16-AUG-16:02 | 3812.32 | 0.00 |
| September | 0.00 | 0.00 | 0.678332E+10 | 0.474763E+10 | 5400.27 | 17-SEP-16:10 | 4022.76 | 0.00 |
| October | 0.00 | 0.00 | 0.617146E+10 | 0.442767E+10 | 5492.47 | 29-OCT-14:10 | 3842.24 | 0.00 |
| November | 0.00 | 0.00 | 0.437008E+10 | 0.316307E+10 | 4569.94 | 22-NOV-14:30 | 3398.75 | 0.00 |
| December | 0.00 | 0.00 | 0.275504E+10 | 0.206173E+10 | 4717.85 | 10-DEC-15:00 | 3648.24 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.593341E+11 | 0.427391E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.213127E+10 | 0.170224E+10 | 4262.64 | 3364.59 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.705599E+10 | 0.495689E+10 | 5492.47 | 4022.76 | 0.00 |
Report: CoilReportMonthly
For: SPLIT TNW COOLING COIL
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.120449E+10 | 0.877236E+09 | 2762.94 | 02-JAN-15:00 | 2046.20 | 0.00 |
| February | 0.00 | 0.00 | 0.179903E+10 | 0.136216E+10 | 3762.52 | 11-FEB-16:20 | 2673.75 | 0.00 |
| March | 0.00 | 0.00 | 0.275224E+10 | 0.201151E+10 | 3861.64 | 13-MAR-16:25 | 2971.52 | 0.00 |
| April | 0.00 | 0.00 | 0.398480E+10 | 0.305264E+10 | 4444.69 | 15-APR-16:40 | 3639.11 | 0.00 |
| May | 0.00 | 0.00 | 0.611829E+10 | 0.435252E+10 | 5243.84 | 29-MAY-16:30 | 4026.37 | 0.00 |
| June | 0.00 | 0.00 | 0.679097E+10 | 0.467714E+10 | 5123.90 | 08-JUN-16:13 | 3598.87 | 0.00 |
| July | 0.00 | 0.00 | 0.711956E+10 | 0.502345E+10 | 5077.94 | 27-JUL-16:10 | 4039.46 | 0.00 |
| August | 0.00 | 0.00 | 0.693289E+10 | 0.471635E+10 | 5076.09 | 16-AUG-16:02 | 3698.29 | 0.00 |
| September | 0.00 | 0.00 | 0.632140E+10 | 0.434614E+10 | 4874.66 | 17-SEP-16:15 | 3564.61 | 0.00 |
| October | 0.00 | 0.00 | 0.532488E+10 | 0.368915E+10 | 4491.33 | 03-OCT-16:17 | 3184.90 | 0.00 |
| November | 0.00 | 0.00 | 0.342357E+10 | 0.234623E+10 | 3578.11 | 04-NOV-16:20 | 2168.56 | 0.00 |
| December | 0.00 | 0.00 | 0.182309E+10 | 0.126428E+10 | 3352.92 | 10-DEC-15:00 | 2438.75 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.535952E+11 | 0.377188E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.120449E+10 | 0.877236E+09 | 2762.94 | 2046.20 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.711956E+10 | 0.502345E+10 | 5243.84 | 4039.46 | 0.00 |
Report: CoilReportMonthly
For: SPLIT TSE COOLING COIL
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.217888E+10 | 0.172997E+10 | 4183.56 | 02-JAN-14:40 | 3395.68 | 0.00 |
| February | 0.00 | 0.00 | 0.259871E+10 | 0.205797E+10 | 4424.28 | 11-FEB-14:30 | 3373.63 | 0.00 |
| March | 0.00 | 0.00 | 0.329686E+10 | 0.246744E+10 | 4097.46 | 04-MAR-13:50 | 2952.38 | 0.00 |
| April | 0.00 | 0.00 | 0.433442E+10 | 0.333704E+10 | 4085.91 | 15-APR-16:03 | 3288.09 | 0.00 |
| May | 0.00 | 0.00 | 0.610743E+10 | 0.431409E+10 | 4670.46 | 29-MAY-16:10 | 3497.50 | 0.00 |
| June | 0.00 | 0.00 | 0.676334E+10 | 0.462517E+10 | 4361.32 | 08-JUN-16:02 | 2965.41 | 0.00 |
| July | 0.00 | 0.00 | 0.712170E+10 | 0.499700E+10 | 4655.25 | 22-JUL-15:40 | 3264.15 | 0.00 |
| August | 0.00 | 0.00 | 0.705682E+10 | 0.480121E+10 | 4979.64 | 20-AUG-12:00 | 3513.50 | 0.00 |
| September | 0.00 | 0.00 | 0.686634E+10 | 0.479272E+10 | 5191.42 | 20-SEP-14:00 | 3770.06 | 0.00 |
| October | 0.00 | 0.00 | 0.621222E+10 | 0.443674E+10 | 5274.77 | 29-OCT-14:00 | 3674.50 | 0.00 |
| November | 0.00 | 0.00 | 0.438950E+10 | 0.315594E+10 | 4668.92 | 22-NOV-12:40 | 3538.20 | 0.00 |
| December | 0.00 | 0.00 | 0.267833E+10 | 0.198065E+10 | 4440.76 | 10-DEC-14:00 | 3335.54 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.596046E+11 | 0.426959E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.217888E+10 | 0.172997E+10 | 4085.91 | 2952.38 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.712170E+10 | 0.499700E+10 | 5274.77 | 3770.06 | 0.00 |
Report: CoilReportMonthly
For: SPLIT TNE COOLING COIL
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.123216E+10 | 0.889473E+09 | 2651.08 | 07-JAN-13:00 | 1846.27 | 0.00 |
| February | 0.00 | 0.00 | 0.178563E+10 | 0.133721E+10 | 3208.89 | 11-FEB-14:00 | 2312.39 | 0.00 |
| March | 0.00 | 0.00 | 0.270337E+10 | 0.194890E+10 | 3390.42 | 04-MAR-14:00 | 2358.24 | 0.00 |
| April | 0.00 | 0.00 | 0.397530E+10 | 0.302292E+10 | 3774.04 | 15-APR-16:20 | 3024.36 | 0.00 |
| May | 0.00 | 0.00 | 0.612887E+10 | 0.433741E+10 | 4655.22 | 22-MAY-15:30 | 3340.39 | 0.00 |
| June | 0.00 | 0.00 | 0.690022E+10 | 0.474744E+10 | 4501.16 | 08-JUN-16:02 | 3067.09 | 0.00 |
| July | 0.00 | 0.00 | 0.719155E+10 | 0.506407E+10 | 4591.15 | 27-JUL-16:10 | 3584.54 | 0.00 |
| August | 0.00 | 0.00 | 0.693070E+10 | 0.469460E+10 | 4674.34 | 20-AUG-12:00 | 3270.83 | 0.00 |
| September | 0.00 | 0.00 | 0.640291E+10 | 0.439245E+10 | 4394.31 | 18-SEP-16:10 | 3087.78 | 0.00 |
| October | 0.00 | 0.00 | 0.536427E+10 | 0.369974E+10 | 4321.44 | 03-OCT-11:30 | 2934.54 | 0.00 |
| November | 0.00 | 0.00 | 0.343222E+10 | 0.233320E+10 | 3459.55 | 04-NOV-12:00 | 2196.29 | 0.00 |
| December | 0.00 | 0.00 | 0.174930E+10 | 0.119384E+10 | 3086.14 | 10-DEC-14:00 | 2164.16 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.537965E+11 | 0.376612E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.123216E+10 | 0.889473E+09 | 2651.08 | 1846.27 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.719155E+10 | 0.506407E+10 | 4674.34 | 3584.54 | 0.00 |
Report: CoilReportMonthly
For: SPLIT TN1 COOLING COIL
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.109920E+10 | 0.790870E+09 | 2127.72 | 07-JAN-13:00 | 1489.63 | 0.00 |
| February | 0.00 | 0.00 | 0.156435E+10 | 0.116801E+10 | 2601.30 | 11-FEB-14:00 | 1875.14 | 0.00 |
| March | 0.00 | 0.00 | 0.231457E+10 | 0.167441E+10 | 2733.11 | 13-MAR-16:12 | 2058.53 | 0.00 |
| April | 0.00 | 0.00 | 0.332516E+10 | 0.252732E+10 | 3063.45 | 15-APR-16:15 | 2468.03 | 0.00 |
| May | 0.00 | 0.00 | 0.508726E+10 | 0.361711E+10 | 3730.42 | 29-MAY-16:20 | 2845.75 | 0.00 |
| June | 0.00 | 0.00 | 0.573391E+10 | 0.395065E+10 | 3653.91 | 08-JUN-16:02 | 2535.60 | 0.00 |
| July | 0.00 | 0.00 | 0.599733E+10 | 0.420546E+10 | 3712.23 | 27-JUL-16:10 | 2913.30 | 0.00 |
| August | 0.00 | 0.00 | 0.580524E+10 | 0.393698E+10 | 3576.96 | 15-AUG-15:10 | 2495.15 | 0.00 |
| September | 0.00 | 0.00 | 0.534116E+10 | 0.366508E+10 | 3534.51 | 18-SEP-16:10 | 2522.26 | 0.00 |
| October | 0.00 | 0.00 | 0.453475E+10 | 0.313503E+10 | 3337.92 | 03-OCT-15:10 | 2343.39 | 0.00 |
| November | 0.00 | 0.00 | 0.297872E+10 | 0.204168E+10 | 2846.60 | 04-NOV-16:10 | 1776.54 | 0.00 |
| December | 0.00 | 0.00 | 0.160488E+10 | 0.110351E+10 | 2477.23 | 10-DEC-14:00 | 1752.90 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.453865E+11 | 0.318161E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.109920E+10 | 0.790870E+09 | 2127.72 | 1489.63 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.599733E+10 | 0.420546E+10 | 3730.42 | 2913.30 | 0.00 |
Report: CoilReportMonthly
For: SPLIT TN2 COOLING COIL
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.110230E+10 | 0.794140E+09 | 2131.06 | 07-JAN-13:00 | 1493.58 | 0.00 |
| February | 0.00 | 0.00 | 0.156509E+10 | 0.116972E+10 | 2602.98 | 11-FEB-14:00 | 1878.34 | 0.00 |
| March | 0.00 | 0.00 | 0.231284E+10 | 0.167430E+10 | 2721.37 | 13-MAR-16:12 | 2050.26 | 0.00 |
| April | 0.00 | 0.00 | 0.332267E+10 | 0.252703E+10 | 3051.05 | 15-APR-16:15 | 2458.84 | 0.00 |
| May | 0.00 | 0.00 | 0.508442E+10 | 0.361683E+10 | 3716.20 | 29-MAY-16:20 | 2834.98 | 0.00 |
| June | 0.00 | 0.00 | 0.573516E+10 | 0.395364E+10 | 3641.58 | 08-JUN-16:02 | 2526.96 | 0.00 |
| July | 0.00 | 0.00 | 0.599704E+10 | 0.420720E+10 | 3700.93 | 27-JUL-16:10 | 2904.62 | 0.00 |
| August | 0.00 | 0.00 | 0.580212E+10 | 0.393629E+10 | 3573.13 | 15-AUG-15:10 | 2493.78 | 0.00 |
| September | 0.00 | 0.00 | 0.534156E+10 | 0.366718E+10 | 3524.17 | 18-SEP-16:10 | 2514.80 | 0.00 |
| October | 0.00 | 0.00 | 0.453352E+10 | 0.313573E+10 | 3333.06 | 03-OCT-15:10 | 2341.20 | 0.00 |
| November | 0.00 | 0.00 | 0.297823E+10 | 0.204255E+10 | 2844.48 | 04-NOV-16:10 | 1775.93 | 0.00 |
| December | 0.00 | 0.00 | 0.160094E+10 | 0.110119E+10 | 2476.92 | 10-DEC-14:00 | 1754.22 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.453759E+11 | 0.318258E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.110230E+10 | 0.794140E+09 | 2131.06 | 1493.58 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.599704E+10 | 0.420720E+10 | 3716.20 | 2904.62 | 0.00 |
Report: CoilReportMonthly
For: SPLIT TS1 COOLING COIL
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.208095E+10 | 0.166748E+10 | 3728.76 | 02-JAN-14:40 | 3052.78 | 0.00 |
| February | 0.00 | 0.00 | 0.238742E+10 | 0.190375E+10 | 3829.58 | 11-FEB-14:30 | 2966.37 | 0.00 |
| March | 0.00 | 0.00 | 0.290731E+10 | 0.219716E+10 | 3322.13 | 04-MAR-14:00 | 2446.63 | 0.00 |
| April | 0.00 | 0.00 | 0.368440E+10 | 0.284549E+10 | 3406.98 | 01-APR-16:05 | 2487.37 | 0.00 |
| May | 0.00 | 0.00 | 0.506213E+10 | 0.359409E+10 | 3751.53 | 29-MAY-16:10 | 2846.25 | 0.00 |
| June | 0.00 | 0.00 | 0.559140E+10 | 0.382737E+10 | 3513.56 | 08-JUN-16:02 | 2434.60 | 0.00 |
| July | 0.00 | 0.00 | 0.592268E+10 | 0.413788E+10 | 3756.48 | 22-JUL-15:50 | 2661.04 | 0.00 |
| August | 0.00 | 0.00 | 0.592892E+10 | 0.404506E+10 | 3875.41 | 20-AUG-12:30 | 2741.53 | 0.00 |
| September | 0.00 | 0.00 | 0.580553E+10 | 0.407005E+10 | 4236.94 | 20-SEP-14:00 | 3129.68 | 0.00 |
| October | 0.00 | 0.00 | 0.538657E+10 | 0.388161E+10 | 4388.95 | 29-OCT-14:00 | 3143.08 | 0.00 |
| November | 0.00 | 0.00 | 0.394542E+10 | 0.288199E+10 | 3912.69 | 22-NOV-12:50 | 3032.13 | 0.00 |
| December | 0.00 | 0.00 | 0.258019E+10 | 0.194175E+10 | 3820.97 | 10-DEC-14:30 | 2968.43 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.512829E+11 | 0.369937E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.208095E+10 | 0.166748E+10 | 3322.13 | 2434.60 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.592892E+10 | 0.413788E+10 | 4388.95 | 3143.08 | 0.00 |
Report: CoilReportMonthly
For: SPLIT TS2 COOLING COIL
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.208613E+10 | 0.167201E+10 | 3731.65 | 02-JAN-14:40 | 3055.84 | 0.00 |
| February | 0.00 | 0.00 | 0.238960E+10 | 0.190551E+10 | 3828.88 | 11-FEB-14:30 | 2966.16 | 0.00 |
| March | 0.00 | 0.00 | 0.290898E+10 | 0.219850E+10 | 3327.16 | 04-MAR-14:00 | 2451.26 | 0.00 |
| April | 0.00 | 0.00 | 0.368461E+10 | 0.284535E+10 | 3391.79 | 01-APR-16:05 | 2474.83 | 0.00 |
| May | 0.00 | 0.00 | 0.506266E+10 | 0.359406E+10 | 3740.58 | 29-MAY-16:10 | 2836.56 | 0.00 |
| June | 0.00 | 0.00 | 0.559590E+10 | 0.383061E+10 | 3503.05 | 08-JUN-16:02 | 2426.21 | 0.00 |
| July | 0.00 | 0.00 | 0.592557E+10 | 0.413985E+10 | 3749.65 | 22-JUL-15:50 | 2655.85 | 0.00 |
| August | 0.00 | 0.00 | 0.592890E+10 | 0.404456E+10 | 3885.83 | 20-AUG-12:30 | 2751.14 | 0.00 |
| September | 0.00 | 0.00 | 0.580875E+10 | 0.407226E+10 | 4238.88 | 20-SEP-14:00 | 3131.99 | 0.00 |
| October | 0.00 | 0.00 | 0.538801E+10 | 0.388234E+10 | 4388.83 | 29-OCT-14:00 | 3143.38 | 0.00 |
| November | 0.00 | 0.00 | 0.394698E+10 | 0.288294E+10 | 3924.57 | 22-NOV-12:40 | 3042.17 | 0.00 |
| December | 0.00 | 0.00 | 0.257837E+10 | 0.194007E+10 | 3819.18 | 10-DEC-14:30 | 2966.97 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.513045E+11 | 0.370080E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.208613E+10 | 0.167201E+10 | 3327.16 | 2426.21 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.592890E+10 | 0.413985E+10 | 4388.83 | 3143.38 | 0.00 |
Report: FanReportMonthly
For: SPLIT GSW SUPPLY FAN
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.157513E+09 | 0.93 | 191.42 | 02-JAN-15:00 | 0.99 |
| February | 0.160814E+09 | 0.93 | 195.68 | 11-FEB-16:30 | 0.99 |
| March | 0.182600E+09 | 0.91 | 179.19 | 13-MAR-16:25 | 1.00 |
| April | 0.228698E+09 | 1.03 | 198.10 | 15-APR-17:00 | 0.99 |
| May | 0.307964E+09 | 1.02 | 212.88 | 29-MAY-16:04 | 0.98 |
| June | 0.336167E+09 | 1.01 | 203.73 | 08-JUN-16:13 | 0.98 |
| July | 0.372335E+09 | 1.01 | 223.37 | 27-JUL-16:02 | 0.98 |
| August | 0.383960E+09 | 1.01 | 223.31 | 16-AUG-16:02 | 0.98 |
| September | 0.377708E+09 | 1.01 | 233.29 | 17-SEP-16:10 | 0.97 |
| October | 0.363619E+09 | 1.01 | 230.59 | 29-OCT-14:20 | 0.97 |
| November | 0.273909E+09 | 0.99 | 199.15 | 10-NOV-14:30 | 0.99 |
| December | 0.191182E+09 | 0.95 | 207.63 | 10-DEC-15:00 | 0.98 |
| Annual Sum or Average | 0.333647E+10 | 0.98 | |||
| Minimum of Months | 0.157513E+09 | 0.91 | 179.19 | 0.97 | |
| Maximum of Months | 0.383960E+09 | 1.03 | 233.29 | 1.00 |
Report: FanReportMonthly
For: G SW APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.63 | 20.01 | 01-JAN-00:10 | 0.62 |
| February | 48400714.57 | 0.63 | 20.01 | 01-FEB-00:10 | 0.63 |
| March | 53586505.42 | 0.62 | 20.01 | 01-MAR-00:10 | 0.63 |
| April | 51857908.47 | 0.62 | 20.01 | 01-APR-00:10 | 0.62 |
| May | 53586505.42 | 0.62 | 20.01 | 01-MAY-00:10 | 0.62 |
| June | 51857908.47 | 0.62 | 20.01 | 01-JUN-00:10 | 0.62 |
| July | 53586505.42 | 0.62 | 20.01 | 01-JUL-00:10 | 0.62 |
| August | 53586505.42 | 0.62 | 20.01 | 01-AUG-00:10 | 0.62 |
| September | 51857908.47 | 0.62 | 20.01 | 01-SEP-00:10 | 0.62 |
| October | 53586505.42 | 0.62 | 20.01 | 01-OCT-00:10 | 0.62 |
| November | 51857908.47 | 0.62 | 20.01 | 01-NOV-00:10 | 0.62 |
| December | 53586505.42 | 0.62 | 20.01 | 01-DEC-00:10 | 0.62 |
| Annual Sum or Average | 0.630938E+09 | 0.62 | |||
| Minimum of Months | 48400714.57 | 0.62 | 20.01 | 0.62 | |
| Maximum of Months | 53586505.42 | 0.63 | 20.01 | 0.63 |
Report: FanReportMonthly
For: G SW APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.63 | 20.01 | 01-JAN-00:10 | 0.63 |
| February | 48400714.57 | 0.63 | 20.01 | 01-FEB-00:10 | 0.63 |
| March | 53586505.42 | 0.63 | 20.01 | 01-MAR-00:10 | 0.63 |
| April | 51857908.47 | 0.63 | 20.01 | 01-APR-00:10 | 0.63 |
| May | 53586505.42 | 0.62 | 20.01 | 01-MAY-00:10 | 0.62 |
| June | 51857908.47 | 0.62 | 20.01 | 01-JUN-00:10 | 0.62 |
| July | 53586505.42 | 0.62 | 20.01 | 01-JUL-00:10 | 0.62 |
| August | 53586505.42 | 0.62 | 20.01 | 01-AUG-00:10 | 0.62 |
| September | 51857908.47 | 0.62 | 20.01 | 01-SEP-00:10 | 0.62 |
| October | 53586505.42 | 0.62 | 20.01 | 01-OCT-00:10 | 0.63 |
| November | 51857908.47 | 0.63 | 20.01 | 01-NOV-00:10 | 0.62 |
| December | 53586505.42 | 0.63 | 20.01 | 01-DEC-00:10 | 0.62 |
| Annual Sum or Average | 0.630938E+09 | 0.63 | |||
| Minimum of Months | 48400714.57 | 0.62 | 20.01 | 0.62 | |
| Maximum of Months | 53586505.42 | 0.63 | 20.01 | 0.63 |
Report: FanReportMonthly
For: SPLIT GNW SUPPLY FAN
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 93990015.67 | 0.75 | 128.49 | 02-JAN-15:00 | 1.02 |
| February | 0.111417E+09 | 0.81 | 155.70 | 11-FEB-16:30 | 1.00 |
| March | 0.146425E+09 | 0.84 | 158.92 | 13-MAR-16:25 | 1.00 |
| April | 0.210326E+09 | 1.03 | 188.53 | 15-APR-17:00 | 0.99 |
| May | 0.311432E+09 | 1.02 | 213.73 | 29-MAY-16:30 | 0.98 |
| June | 0.346562E+09 | 1.01 | 212.00 | 08-JUN-16:30 | 0.98 |
| July | 0.379462E+09 | 1.01 | 225.91 | 27-JUL-16:30 | 0.98 |
| August | 0.380602E+09 | 1.01 | 220.64 | 16-AUG-16:02 | 0.98 |
| September | 0.356102E+09 | 1.01 | 216.68 | 18-SEP-16:10 | 0.98 |
| October | 0.319746E+09 | 1.02 | 203.91 | 03-OCT-16:13 | 0.98 |
| November | 0.221092E+09 | 0.98 | 170.85 | 04-NOV-16:10 | 1.00 |
| December | 0.129638E+09 | 0.82 | 154.37 | 10-DEC-15:10 | 1.01 |
| Annual Sum or Average | 0.300679E+10 | 0.94 | |||
| Minimum of Months | 93990015.67 | 0.75 | 128.49 | 0.98 | |
| Maximum of Months | 0.380602E+09 | 1.03 | 225.91 | 1.02 |
Report: FanReportMonthly
For: G NW APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.63 | 20.01 | 01-JAN-00:10 | 0.62 |
| February | 48400714.57 | 0.63 | 20.01 | 01-FEB-00:10 | 0.63 |
| March | 53586505.42 | 0.62 | 20.01 | 01-MAR-00:10 | 0.63 |
| April | 51857908.47 | 0.62 | 20.01 | 01-APR-00:10 | 0.62 |
| May | 53586505.42 | 0.62 | 20.01 | 01-MAY-00:10 | 0.62 |
| June | 51857908.47 | 0.62 | 20.01 | 01-JUN-00:10 | 0.62 |
| July | 53586505.42 | 0.62 | 20.01 | 01-JUL-00:10 | 0.62 |
| August | 53586505.42 | 0.62 | 20.01 | 01-AUG-00:10 | 0.62 |
| September | 51857908.47 | 0.62 | 20.01 | 01-SEP-00:10 | 0.62 |
| October | 53586505.42 | 0.62 | 20.01 | 01-OCT-00:10 | 0.62 |
| November | 51857908.47 | 0.62 | 20.01 | 01-NOV-00:10 | 0.62 |
| December | 53586505.42 | 0.62 | 20.01 | 01-DEC-00:10 | 0.62 |
| Annual Sum or Average | 0.630938E+09 | 0.62 | |||
| Minimum of Months | 48400714.57 | 0.62 | 20.01 | 0.62 | |
| Maximum of Months | 53586505.42 | 0.63 | 20.01 | 0.63 |
Report: FanReportMonthly
For: G NW APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.63 | 20.01 | 01-JAN-00:10 | 0.62 |
| February | 48400714.57 | 0.63 | 20.01 | 01-FEB-00:10 | 0.63 |
| March | 53586505.42 | 0.63 | 20.01 | 01-MAR-00:10 | 0.63 |
| April | 51857908.47 | 0.63 | 20.01 | 01-APR-00:10 | 0.63 |
| May | 53586505.42 | 0.62 | 20.01 | 01-MAY-00:10 | 0.62 |
| June | 51857908.47 | 0.62 | 20.01 | 01-JUN-00:10 | 0.62 |
| July | 53586505.42 | 0.62 | 20.01 | 01-JUL-00:10 | 0.62 |
| August | 53586505.42 | 0.62 | 20.01 | 01-AUG-00:10 | 0.62 |
| September | 51857908.47 | 0.62 | 20.01 | 01-SEP-00:10 | 0.62 |
| October | 53586505.42 | 0.62 | 20.01 | 01-OCT-00:10 | 0.62 |
| November | 51857908.47 | 0.63 | 20.01 | 01-NOV-00:10 | 0.62 |
| December | 53586505.42 | 0.63 | 20.01 | 01-DEC-00:10 | 0.62 |
| Annual Sum or Average | 0.630938E+09 | 0.63 | |||
| Minimum of Months | 48400714.57 | 0.62 | 20.01 | 0.62 | |
| Maximum of Months | 53586505.42 | 0.63 | 20.01 | 0.63 |
Report: FanReportMonthly
For: SPLIT OFFICE SUPPLY FAN
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.112019E+10 | 0.91 | 418.23 | 01-JAN-00:10 | 0.90 |
| February | 0.101178E+10 | 0.91 | 418.23 | 01-FEB-00:10 | 0.91 |
| March | 0.112019E+10 | 0.91 | 418.23 | 01-MAR-00:10 | 0.91 |
| April | 0.108405E+10 | 0.91 | 418.23 | 01-APR-00:10 | 0.91 |
| May | 0.112019E+10 | 0.90 | 418.23 | 01-MAY-00:10 | 0.90 |
| June | 0.108405E+10 | 0.90 | 418.23 | 01-JUN-00:10 | 0.90 |
| July | 0.112019E+10 | 0.90 | 418.23 | 01-JUL-00:10 | 0.90 |
| August | 0.112019E+10 | 0.90 | 418.23 | 01-AUG-00:10 | 0.90 |
| September | 0.108405E+10 | 0.90 | 418.23 | 01-SEP-00:10 | 0.90 |
| October | 0.112019E+10 | 0.90 | 418.23 | 01-OCT-00:10 | 0.90 |
| November | 0.108405E+10 | 0.91 | 418.23 | 01-NOV-00:10 | 0.90 |
| December | 0.112019E+10 | 0.91 | 418.23 | 01-DEC-00:10 | 0.90 |
| Annual Sum or Average | 0.131893E+11 | 0.91 | |||
| Minimum of Months | 0.101178E+10 | 0.90 | 418.23 | 0.90 | |
| Maximum of Months | 0.112019E+10 | 0.91 | 418.23 | 0.91 |
Report: FanReportMonthly
For: SPLIT GNE SUPPLY FAN
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 95397017.89 | 0.76 | 123.84 | 07-JAN-13:00 | 1.01 |
| February | 0.109942E+09 | 0.82 | 133.19 | 11-FEB-14:00 | 1.01 |
| March | 0.142465E+09 | 0.84 | 137.44 | 13-MAR-16:12 | 1.01 |
| April | 0.206301E+09 | 1.03 | 162.84 | 15-APR-17:00 | 1.00 |
| May | 0.306126E+09 | 1.02 | 191.29 | 29-MAY-16:04 | 0.98 |
| June | 0.345963E+09 | 1.01 | 190.54 | 08-JUN-16:02 | 0.98 |
| July | 0.375735E+09 | 1.01 | 206.43 | 27-JUL-16:10 | 0.98 |
| August | 0.373326E+09 | 1.01 | 203.91 | 20-AUG-12:00 | 0.98 |
| September | 0.353375E+09 | 1.01 | 199.77 | 18-SEP-16:10 | 0.98 |
| October | 0.315663E+09 | 1.02 | 188.79 | 03-OCT-11:00 | 0.98 |
| November | 0.218165E+09 | 0.98 | 164.01 | 04-NOV-16:10 | 0.99 |
| December | 0.123222E+09 | 0.80 | 142.32 | 10-DEC-14:00 | 1.01 |
| Annual Sum or Average | 0.296568E+10 | 0.94 | |||
| Minimum of Months | 95397017.89 | 0.76 | 123.84 | 0.98 | |
| Maximum of Months | 0.375735E+09 | 1.03 | 206.43 | 1.01 |
Report: FanReportMonthly
For: G NE APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.63 | 20.01 | 01-JAN-00:10 | 0.62 |
| February | 48400714.57 | 0.63 | 20.01 | 01-FEB-00:10 | 0.63 |
| March | 53586505.42 | 0.62 | 20.01 | 01-MAR-00:10 | 0.63 |
| April | 51857908.47 | 0.62 | 20.01 | 01-APR-00:10 | 0.62 |
| May | 53586505.42 | 0.62 | 20.01 | 01-MAY-00:10 | 0.62 |
| June | 51857908.47 | 0.62 | 20.01 | 01-JUN-00:10 | 0.62 |
| July | 53586505.42 | 0.62 | 20.01 | 01-JUL-00:10 | 0.62 |
| August | 53586505.42 | 0.62 | 20.01 | 01-AUG-00:10 | 0.62 |
| September | 51857908.47 | 0.62 | 20.01 | 01-SEP-00:10 | 0.62 |
| October | 53586505.42 | 0.62 | 20.01 | 01-OCT-00:10 | 0.62 |
| November | 51857908.47 | 0.62 | 20.01 | 01-NOV-00:10 | 0.62 |
| December | 53586505.42 | 0.62 | 20.01 | 01-DEC-00:10 | 0.62 |
| Annual Sum or Average | 0.630938E+09 | 0.62 | |||
| Minimum of Months | 48400714.57 | 0.62 | 20.01 | 0.62 | |
| Maximum of Months | 53586505.42 | 0.63 | 20.01 | 0.63 |
Report: FanReportMonthly
For: G NE APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.63 | 20.01 | 01-JAN-00:10 | 0.62 |
| February | 48400714.57 | 0.63 | 20.01 | 01-FEB-00:10 | 0.63 |
| March | 53586505.42 | 0.63 | 20.01 | 01-MAR-00:10 | 0.63 |
| April | 51857908.47 | 0.63 | 20.01 | 01-APR-00:10 | 0.63 |
| May | 53586505.42 | 0.62 | 20.01 | 01-MAY-00:10 | 0.62 |
| June | 51857908.47 | 0.62 | 20.01 | 01-JUN-00:10 | 0.62 |
| July | 53586505.42 | 0.62 | 20.01 | 01-JUL-00:10 | 0.62 |
| August | 53586505.42 | 0.62 | 20.01 | 01-AUG-00:10 | 0.62 |
| September | 51857908.47 | 0.62 | 20.01 | 01-SEP-00:10 | 0.62 |
| October | 53586505.42 | 0.62 | 20.01 | 01-OCT-00:10 | 0.62 |
| November | 51857908.47 | 0.63 | 20.01 | 01-NOV-00:10 | 0.62 |
| December | 53586505.42 | 0.63 | 20.01 | 01-DEC-00:10 | 0.62 |
| Annual Sum or Average | 0.630938E+09 | 0.63 | |||
| Minimum of Months | 48400714.57 | 0.62 | 20.01 | 0.62 | |
| Maximum of Months | 53586505.42 | 0.63 | 20.01 | 0.63 |
Report: FanReportMonthly
For: SPLIT GN1 SUPPLY FAN
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 90408733.74 | 0.83 | 104.64 | 07-JAN-13:00 | 1.02 |
| February | 0.101665E+09 | 0.86 | 114.79 | 11-FEB-17:10 | 1.01 |
| March | 0.128420E+09 | 0.87 | 117.56 | 13-MAR-16:25 | 1.01 |
| April | 0.179987E+09 | 1.03 | 135.67 | 15-APR-17:00 | 1.00 |
| May | 0.263535E+09 | 1.02 | 159.78 | 29-MAY-16:04 | 0.99 |
| June | 0.296855E+09 | 1.01 | 158.65 | 08-JUN-16:40 | 0.99 |
| July | 0.320740E+09 | 1.01 | 170.88 | 27-JUL-16:30 | 0.99 |
| August | 0.319718E+09 | 1.01 | 163.40 | 21-AUG-16:01 | 0.99 |
| September | 0.300285E+09 | 1.01 | 164.52 | 18-SEP-16:10 | 0.99 |
| October | 0.271512E+09 | 1.02 | 156.16 | 03-OCT-16:03 | 0.99 |
| November | 0.193950E+09 | 1.00 | 139.73 | 04-NOV-16:10 | 1.00 |
| December | 0.118174E+09 | 0.90 | 118.23 | 10-DEC-14:00 | 1.01 |
| Annual Sum or Average | 0.258525E+10 | 0.96 | |||
| Minimum of Months | 90408733.74 | 0.83 | 104.64 | 0.99 | |
| Maximum of Months | 0.320740E+09 | 1.03 | 170.88 | 1.02 |
Report: FanReportMonthly
For: G N1 APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.63 | 20.01 | 01-JAN-00:10 | 0.62 |
| February | 48400714.57 | 0.63 | 20.01 | 01-FEB-00:10 | 0.63 |
| March | 53586505.42 | 0.62 | 20.01 | 01-MAR-00:10 | 0.63 |
| April | 51857908.47 | 0.62 | 20.01 | 01-APR-00:10 | 0.62 |
| May | 53586505.42 | 0.62 | 20.01 | 01-MAY-00:10 | 0.62 |
| June | 51857908.47 | 0.62 | 20.01 | 01-JUN-00:10 | 0.62 |
| July | 53586505.42 | 0.62 | 20.01 | 01-JUL-00:10 | 0.62 |
| August | 53586505.42 | 0.62 | 20.01 | 01-AUG-00:10 | 0.62 |
| September | 51857908.47 | 0.62 | 20.01 | 01-SEP-00:10 | 0.62 |
| October | 53586505.42 | 0.62 | 20.01 | 01-OCT-00:10 | 0.62 |
| November | 51857908.47 | 0.62 | 20.01 | 01-NOV-00:10 | 0.62 |
| December | 53586505.42 | 0.62 | 20.01 | 01-DEC-00:10 | 0.62 |
| Annual Sum or Average | 0.630938E+09 | 0.62 | |||
| Minimum of Months | 48400714.57 | 0.62 | 20.01 | 0.62 | |
| Maximum of Months | 53586505.42 | 0.63 | 20.01 | 0.63 |
Report: FanReportMonthly
For: G N1 APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.63 | 20.01 | 01-JAN-00:10 | 0.62 |
| February | 48400714.57 | 0.63 | 20.01 | 01-FEB-00:10 | 0.63 |
| March | 53586505.42 | 0.63 | 20.01 | 01-MAR-00:10 | 0.63 |
| April | 51857908.47 | 0.63 | 20.01 | 01-APR-00:10 | 0.63 |
| May | 53586505.42 | 0.62 | 20.01 | 01-MAY-00:10 | 0.62 |
| June | 51857908.47 | 0.62 | 20.01 | 01-JUN-00:10 | 0.62 |
| July | 53586505.42 | 0.62 | 20.01 | 01-JUL-00:10 | 0.62 |
| August | 53586505.42 | 0.62 | 20.01 | 01-AUG-00:10 | 0.62 |
| September | 51857908.47 | 0.62 | 20.01 | 01-SEP-00:10 | 0.62 |
| October | 53586505.42 | 0.62 | 20.01 | 01-OCT-00:10 | 0.62 |
| November | 51857908.47 | 0.63 | 20.01 | 01-NOV-00:10 | 0.62 |
| December | 53586505.42 | 0.63 | 20.01 | 01-DEC-00:10 | 0.62 |
| Annual Sum or Average | 0.630938E+09 | 0.63 | |||
| Minimum of Months | 48400714.57 | 0.62 | 20.01 | 0.62 | |
| Maximum of Months | 53586505.42 | 0.63 | 20.01 | 0.63 |
Report: FanReportMonthly
For: SPLIT GN2 SUPPLY FAN
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 90623244.61 | 0.83 | 104.73 | 07-JAN-13:00 | 1.02 |
| February | 0.101712E+09 | 0.86 | 114.30 | 11-FEB-17:10 | 1.01 |
| March | 0.128447E+09 | 0.87 | 117.18 | 13-MAR-16:25 | 1.01 |
| April | 0.179900E+09 | 1.03 | 135.28 | 15-APR-17:00 | 1.00 |
| May | 0.263439E+09 | 1.02 | 159.46 | 29-MAY-16:04 | 0.99 |
| June | 0.296990E+09 | 1.01 | 158.43 | 08-JUN-16:40 | 0.99 |
| July | 0.320741E+09 | 1.01 | 170.60 | 27-JUL-16:30 | 0.99 |
| August | 0.319584E+09 | 1.01 | 163.11 | 21-AUG-16:01 | 0.99 |
| September | 0.300326E+09 | 1.01 | 164.24 | 18-SEP-16:10 | 0.99 |
| October | 0.271477E+09 | 1.02 | 155.96 | 03-OCT-16:03 | 0.99 |
| November | 0.193940E+09 | 1.00 | 139.66 | 04-NOV-16:10 | 1.00 |
| December | 0.117955E+09 | 0.90 | 118.18 | 10-DEC-14:00 | 1.01 |
| Annual Sum or Average | 0.258513E+10 | 0.96 | |||
| Minimum of Months | 90623244.61 | 0.83 | 104.73 | 0.99 | |
| Maximum of Months | 0.320741E+09 | 1.03 | 170.60 | 1.02 |
Report: FanReportMonthly
For: G N2 APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.63 | 20.01 | 01-JAN-00:10 | 0.62 |
| February | 48400714.57 | 0.63 | 20.01 | 01-FEB-00:10 | 0.63 |
| March | 53586505.42 | 0.62 | 20.01 | 01-MAR-00:10 | 0.63 |
| April | 51857908.47 | 0.62 | 20.01 | 01-APR-00:10 | 0.62 |
| May | 53586505.42 | 0.62 | 20.01 | 01-MAY-00:10 | 0.62 |
| June | 51857908.47 | 0.62 | 20.01 | 01-JUN-00:10 | 0.62 |
| July | 53586505.42 | 0.62 | 20.01 | 01-JUL-00:10 | 0.62 |
| August | 53586505.42 | 0.62 | 20.01 | 01-AUG-00:10 | 0.62 |
| September | 51857908.47 | 0.62 | 20.01 | 01-SEP-00:10 | 0.62 |
| October | 53586505.42 | 0.62 | 20.01 | 01-OCT-00:10 | 0.62 |
| November | 51857908.47 | 0.62 | 20.01 | 01-NOV-00:10 | 0.62 |
| December | 53586505.42 | 0.62 | 20.01 | 01-DEC-00:10 | 0.62 |
| Annual Sum or Average | 0.630938E+09 | 0.62 | |||
| Minimum of Months | 48400714.57 | 0.62 | 20.01 | 0.62 | |
| Maximum of Months | 53586505.42 | 0.63 | 20.01 | 0.63 |
Report: FanReportMonthly
For: G N2 APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.63 | 20.01 | 01-JAN-00:10 | 0.62 |
| February | 48400714.57 | 0.63 | 20.01 | 01-FEB-00:10 | 0.63 |
| March | 53586505.42 | 0.63 | 20.01 | 01-MAR-00:10 | 0.63 |
| April | 51857908.47 | 0.63 | 20.01 | 01-APR-00:10 | 0.63 |
| May | 53586505.42 | 0.62 | 20.01 | 01-MAY-00:10 | 0.62 |
| June | 51857908.47 | 0.62 | 20.01 | 01-JUN-00:10 | 0.62 |
| July | 53586505.42 | 0.62 | 20.01 | 01-JUL-00:10 | 0.62 |
| August | 53586505.42 | 0.62 | 20.01 | 01-AUG-00:10 | 0.62 |
| September | 51857908.47 | 0.62 | 20.01 | 01-SEP-00:10 | 0.62 |
| October | 53586505.42 | 0.62 | 20.01 | 01-OCT-00:10 | 0.62 |
| November | 51857908.47 | 0.63 | 20.01 | 01-NOV-00:10 | 0.62 |
| December | 53586505.42 | 0.63 | 20.01 | 01-DEC-00:10 | 0.62 |
| Annual Sum or Average | 0.630938E+09 | 0.63 | |||
| Minimum of Months | 48400714.57 | 0.62 | 20.01 | 0.62 | |
| Maximum of Months | 53586505.42 | 0.63 | 20.01 | 0.63 |
Report: FanReportMonthly
For: SPLIT GS1 SUPPLY FAN
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.157879E+09 | 1.01 | 164.60 | 02-JAN-14:40 | 0.99 |
| February | 0.153617E+09 | 0.98 | 156.71 | 11-FEB-14:00 | 0.99 |
| March | 0.166827E+09 | 0.96 | 139.12 | 13-MAR-16:02 | 1.00 |
| April | 0.199125E+09 | 1.03 | 145.58 | 15-APR-16:50 | 1.00 |
| May | 0.260681E+09 | 1.02 | 159.82 | 29-MAY-16:04 | 0.99 |
| June | 0.286949E+09 | 1.01 | 154.14 | 03-JUN-16:03 | 0.99 |
| July | 0.314141E+09 | 1.01 | 170.15 | 29-JUL-16:03 | 0.99 |
| August | 0.323675E+09 | 1.01 | 171.35 | 20-AUG-12:00 | 0.98 |
| September | 0.322593E+09 | 1.01 | 184.54 | 20-SEP-14:10 | 0.98 |
| October | 0.316240E+09 | 1.01 | 187.27 | 29-OCT-14:10 | 0.98 |
| November | 0.247843E+09 | 1.01 | 168.11 | 22-NOV-12:50 | 0.99 |
| December | 0.182527E+09 | 0.99 | 171.08 | 10-DEC-14:30 | 0.99 |
| Annual Sum or Average | 0.293210E+10 | 1.00 | |||
| Minimum of Months | 0.153617E+09 | 0.96 | 139.12 | 0.98 | |
| Maximum of Months | 0.323675E+09 | 1.03 | 187.27 | 1.00 |
Report: FanReportMonthly
For: G S1 APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.63 | 20.01 | 01-JAN-00:10 | 0.62 |
| February | 48400714.57 | 0.63 | 20.01 | 01-FEB-00:10 | 0.63 |
| March | 53586505.42 | 0.62 | 20.01 | 01-MAR-00:10 | 0.63 |
| April | 51857908.47 | 0.62 | 20.01 | 01-APR-00:10 | 0.62 |
| May | 53586505.42 | 0.62 | 20.01 | 01-MAY-00:10 | 0.62 |
| June | 51857908.47 | 0.62 | 20.01 | 01-JUN-00:10 | 0.62 |
| July | 53586505.42 | 0.62 | 20.01 | 01-JUL-00:10 | 0.62 |
| August | 53586505.42 | 0.62 | 20.01 | 01-AUG-00:10 | 0.62 |
| September | 51857908.47 | 0.62 | 20.01 | 01-SEP-00:10 | 0.62 |
| October | 53586505.42 | 0.62 | 20.01 | 01-OCT-00:10 | 0.62 |
| November | 51857908.47 | 0.62 | 20.01 | 01-NOV-00:10 | 0.62 |
| December | 53586505.42 | 0.62 | 20.01 | 01-DEC-00:10 | 0.62 |
| Annual Sum or Average | 0.630938E+09 | 0.62 | |||
| Minimum of Months | 48400714.57 | 0.62 | 20.01 | 0.62 | |
| Maximum of Months | 53586505.42 | 0.63 | 20.01 | 0.63 |
Report: FanReportMonthly
For: G S1 APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.63 | 20.01 | 01-JAN-00:10 | 0.63 |
| February | 48400714.57 | 0.63 | 20.01 | 01-FEB-00:10 | 0.63 |
| March | 53586505.42 | 0.63 | 20.01 | 01-MAR-00:10 | 0.63 |
| April | 51857908.47 | 0.63 | 20.01 | 01-APR-00:10 | 0.63 |
| May | 53586505.42 | 0.62 | 20.01 | 01-MAY-00:10 | 0.62 |
| June | 51857908.47 | 0.62 | 20.01 | 01-JUN-00:10 | 0.62 |
| July | 53586505.42 | 0.62 | 20.01 | 01-JUL-00:10 | 0.62 |
| August | 53586505.42 | 0.62 | 20.01 | 01-AUG-00:10 | 0.62 |
| September | 51857908.47 | 0.62 | 20.01 | 01-SEP-00:10 | 0.62 |
| October | 53586505.42 | 0.62 | 20.01 | 01-OCT-00:10 | 0.62 |
| November | 51857908.47 | 0.63 | 20.01 | 01-NOV-00:10 | 0.62 |
| December | 53586505.42 | 0.63 | 20.01 | 01-DEC-00:10 | 0.62 |
| Annual Sum or Average | 0.630938E+09 | 0.63 | |||
| Minimum of Months | 48400714.57 | 0.62 | 20.01 | 0.62 | |
| Maximum of Months | 53586505.42 | 0.63 | 20.01 | 0.63 |
Report: FanReportMonthly
For: SPLIT GS2 SUPPLY FAN
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.172465E+09 | 1.02 | 176.75 | 02-JAN-14:40 | 0.98 |
| February | 0.165288E+09 | 0.99 | 163.95 | 11-FEB-14:00 | 0.99 |
| March | 0.179997E+09 | 0.97 | 143.51 | 13-MAR-16:02 | 1.00 |
| April | 0.215686E+09 | 1.03 | 153.85 | 15-APR-16:50 | 0.99 |
| May | 0.280647E+09 | 1.02 | 169.46 | 29-MAY-16:04 | 0.99 |
| June | 0.308537E+09 | 1.01 | 163.69 | 03-JUN-16:03 | 0.99 |
| July | 0.337828E+09 | 1.01 | 179.89 | 29-JUL-16:03 | 0.98 |
| August | 0.346387E+09 | 1.00 | 182.84 | 20-AUG-12:00 | 0.98 |
| September | 0.345498E+09 | 1.00 | 190.78 | 20-SEP-14:10 | 0.97 |
| October | 0.339224E+09 | 1.01 | 198.03 | 29-OCT-14:10 | 0.97 |
| November | 0.266131E+09 | 1.01 | 174.24 | 22-NOV-12:50 | 0.98 |
| December | 0.196935E+09 | 1.00 | 181.29 | 10-DEC-14:30 | 0.98 |
| Annual Sum or Average | 0.315462E+10 | 1.01 | |||
| Minimum of Months | 0.165288E+09 | 0.97 | 143.51 | 0.97 | |
| Maximum of Months | 0.346387E+09 | 1.03 | 198.03 | 1.00 |
Report: FanReportMonthly
For: G S2 APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.63 | 20.01 | 01-JAN-00:10 | 0.62 |
| February | 48400714.57 | 0.63 | 20.01 | 01-FEB-00:10 | 0.63 |
| March | 53586505.42 | 0.62 | 20.01 | 01-MAR-00:10 | 0.63 |
| April | 51857908.47 | 0.62 | 20.01 | 01-APR-00:10 | 0.62 |
| May | 53586505.42 | 0.62 | 20.01 | 01-MAY-00:10 | 0.62 |
| June | 51857908.47 | 0.62 | 20.01 | 01-JUN-00:10 | 0.62 |
| July | 53586505.42 | 0.62 | 20.01 | 01-JUL-00:10 | 0.62 |
| August | 53586505.42 | 0.62 | 20.01 | 01-AUG-00:10 | 0.62 |
| September | 51857908.47 | 0.62 | 20.01 | 01-SEP-00:10 | 0.62 |
| October | 53586505.42 | 0.62 | 20.01 | 01-OCT-00:10 | 0.62 |
| November | 51857908.47 | 0.62 | 20.01 | 01-NOV-00:10 | 0.62 |
| December | 53586505.42 | 0.62 | 20.01 | 01-DEC-00:10 | 0.62 |
| Annual Sum or Average | 0.630938E+09 | 0.62 | |||
| Minimum of Months | 48400714.57 | 0.62 | 20.01 | 0.62 | |
| Maximum of Months | 53586505.42 | 0.63 | 20.01 | 0.63 |
Report: FanReportMonthly
For: G S2 APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.63 | 20.01 | 01-JAN-00:10 | 0.63 |
| February | 48400714.57 | 0.63 | 20.01 | 01-FEB-00:10 | 0.63 |
| March | 53586505.42 | 0.63 | 20.01 | 01-MAR-00:10 | 0.63 |
| April | 51857908.47 | 0.63 | 20.01 | 01-APR-00:10 | 0.63 |
| May | 53586505.42 | 0.62 | 20.01 | 01-MAY-00:10 | 0.62 |
| June | 51857908.47 | 0.62 | 20.01 | 01-JUN-00:10 | 0.62 |
| July | 53586505.42 | 0.62 | 20.01 | 01-JUL-00:10 | 0.62 |
| August | 53586505.42 | 0.62 | 20.01 | 01-AUG-00:10 | 0.62 |
| September | 51857908.47 | 0.62 | 20.01 | 01-SEP-00:10 | 0.62 |
| October | 53586505.42 | 0.63 | 20.01 | 01-OCT-00:10 | 0.63 |
| November | 51857908.47 | 0.63 | 20.01 | 01-NOV-00:10 | 0.62 |
| December | 53586505.42 | 0.63 | 20.01 | 01-DEC-00:10 | 0.62 |
| Annual Sum or Average | 0.630938E+09 | 0.63 | |||
| Minimum of Months | 48400714.57 | 0.62 | 20.01 | 0.62 | |
| Maximum of Months | 53586505.42 | 0.63 | 20.01 | 0.63 |
Report: FanReportMonthly
For: SPLIT MSW SUPPLY FAN
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.321557E+09 | 0.88 | 432.47 | 02-JAN-15:00 | 0.99 |
| February | 0.350074E+09 | 0.90 | 460.47 | 11-FEB-16:20 | 0.99 |
| March | 0.428023E+09 | 0.91 | 426.52 | 13-MAR-16:25 | 0.99 |
| April | 0.530384E+09 | 1.03 | 466.28 | 15-APR-16:40 | 0.99 |
| May | 0.693243E+09 | 1.02 | 505.09 | 29-MAY-16:04 | 0.98 |
| June | 0.740338E+09 | 1.02 | 472.16 | 08-JUN-16:13 | 0.98 |
| July | 0.786354E+09 | 1.01 | 500.26 | 27-JUL-16:02 | 0.98 |
| August | 0.793473E+09 | 1.01 | 498.00 | 16-AUG-16:02 | 0.98 |
| September | 0.768343E+09 | 1.01 | 518.86 | 17-SEP-16:10 | 0.97 |
| October | 0.732588E+09 | 1.02 | 517.54 | 29-OCT-14:10 | 0.97 |
| November | 0.547349E+09 | 0.98 | 446.83 | 22-NOV-14:30 | 0.99 |
| December | 0.379243E+09 | 0.90 | 467.91 | 10-DEC-15:00 | 0.98 |
| Annual Sum or Average | 0.707097E+10 | 0.97 | |||
| Minimum of Months | 0.321557E+09 | 0.88 | 426.52 | 0.97 | |
| Maximum of Months | 0.793473E+09 | 1.03 | 518.86 | 0.99 |
Report: FanReportMonthly
For: M SW APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.107173E+09 | 0.63 | 40.01 | 01-JAN-00:10 | 0.62 |
| February | 96801429.15 | 0.63 | 40.01 | 01-FEB-00:10 | 0.63 |
| March | 0.107173E+09 | 0.62 | 40.01 | 01-MAR-00:10 | 0.63 |
| April | 0.103716E+09 | 0.62 | 40.01 | 01-APR-00:10 | 0.62 |
| May | 0.107173E+09 | 0.62 | 40.01 | 01-MAY-00:10 | 0.62 |
| June | 0.103716E+09 | 0.62 | 40.01 | 01-JUN-00:10 | 0.62 |
| July | 0.107173E+09 | 0.62 | 40.01 | 01-JUL-00:10 | 0.62 |
| August | 0.107173E+09 | 0.62 | 40.01 | 01-AUG-00:10 | 0.62 |
| September | 0.103716E+09 | 0.62 | 40.01 | 01-SEP-00:10 | 0.62 |
| October | 0.107173E+09 | 0.62 | 40.01 | 01-OCT-00:10 | 0.62 |
| November | 0.103716E+09 | 0.62 | 40.01 | 01-NOV-00:10 | 0.62 |
| December | 0.107173E+09 | 0.62 | 40.01 | 01-DEC-00:10 | 0.62 |
| Annual Sum or Average | 0.126188E+10 | 0.62 | |||
| Minimum of Months | 96801429.15 | 0.62 | 40.01 | 0.62 | |
| Maximum of Months | 0.107173E+09 | 0.63 | 40.01 | 0.63 |
Report: FanReportMonthly
For: M SW APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.107173E+09 | 0.63 | 40.01 | 01-JAN-00:10 | 0.63 |
| February | 96801429.15 | 0.63 | 40.01 | 01-FEB-00:10 | 0.63 |
| March | 0.107173E+09 | 0.63 | 40.01 | 01-MAR-00:10 | 0.63 |
| April | 0.103716E+09 | 0.63 | 40.01 | 01-APR-00:10 | 0.63 |
| May | 0.107173E+09 | 0.62 | 40.01 | 01-MAY-00:10 | 0.62 |
| June | 0.103716E+09 | 0.62 | 40.01 | 01-JUN-00:10 | 0.62 |
| July | 0.107173E+09 | 0.62 | 40.01 | 01-JUL-00:10 | 0.62 |
| August | 0.107173E+09 | 0.62 | 40.01 | 01-AUG-00:10 | 0.62 |
| September | 0.103716E+09 | 0.62 | 40.01 | 01-SEP-00:10 | 0.62 |
| October | 0.107173E+09 | 0.62 | 40.01 | 01-OCT-00:10 | 0.62 |
| November | 0.103716E+09 | 0.63 | 40.01 | 01-NOV-00:10 | 0.62 |
| December | 0.107173E+09 | 0.63 | 40.01 | 01-DEC-00:10 | 0.62 |
| Annual Sum or Average | 0.126188E+10 | 0.63 | |||
| Minimum of Months | 96801429.15 | 0.62 | 40.01 | 0.62 | |
| Maximum of Months | 0.107173E+09 | 0.63 | 40.01 | 0.63 |
Report: FanReportMonthly
For: SPLIT MNW SUPPLY FAN
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.187393E+09 | 0.72 | 278.87 | 02-JAN-15:00 | 1.02 |
| February | 0.245668E+09 | 0.80 | 363.82 | 11-FEB-16:30 | 1.00 |
| March | 0.351342E+09 | 0.85 | 384.11 | 13-MAR-16:25 | 1.00 |
| April | 0.490788E+09 | 1.03 | 442.58 | 15-APR-17:00 | 0.99 |
| May | 0.698949E+09 | 1.02 | 506.39 | 29-MAY-16:30 | 0.98 |
| June | 0.760122E+09 | 1.01 | 490.79 | 08-JUN-16:30 | 0.98 |
| July | 0.798694E+09 | 1.01 | 504.68 | 27-JUL-16:13 | 0.98 |
| August | 0.783446E+09 | 1.01 | 491.39 | 16-AUG-16:02 | 0.98 |
| September | 0.719108E+09 | 1.02 | 473.10 | 18-SEP-16:10 | 0.98 |
| October | 0.636136E+09 | 1.02 | 446.18 | 03-OCT-16:30 | 0.99 |
| November | 0.432785E+09 | 0.95 | 367.34 | 04-NOV-16:10 | 1.00 |
| December | 0.249420E+09 | 0.73 | 336.78 | 10-DEC-15:10 | 1.01 |
| Annual Sum or Average | 0.635385E+10 | 0.93 | |||
| Minimum of Months | 0.187393E+09 | 0.72 | 278.87 | 0.98 | |
| Maximum of Months | 0.798694E+09 | 1.03 | 506.39 | 1.02 |
Report: FanReportMonthly
For: M NW APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.107173E+09 | 0.63 | 40.01 | 01-JAN-00:10 | 0.62 |
| February | 96801429.15 | 0.63 | 40.01 | 01-FEB-00:10 | 0.63 |
| March | 0.107173E+09 | 0.62 | 40.01 | 01-MAR-00:10 | 0.63 |
| April | 0.103716E+09 | 0.62 | 40.01 | 01-APR-00:10 | 0.62 |
| May | 0.107173E+09 | 0.62 | 40.01 | 01-MAY-00:10 | 0.62 |
| June | 0.103716E+09 | 0.62 | 40.01 | 01-JUN-00:10 | 0.62 |
| July | 0.107173E+09 | 0.62 | 40.01 | 01-JUL-00:10 | 0.62 |
| August | 0.107173E+09 | 0.62 | 40.01 | 01-AUG-00:10 | 0.62 |
| September | 0.103716E+09 | 0.62 | 40.01 | 01-SEP-00:10 | 0.62 |
| October | 0.107173E+09 | 0.62 | 40.01 | 01-OCT-00:10 | 0.62 |
| November | 0.103716E+09 | 0.62 | 40.01 | 01-NOV-00:10 | 0.62 |
| December | 0.107173E+09 | 0.62 | 40.01 | 01-DEC-00:10 | 0.62 |
| Annual Sum or Average | 0.126188E+10 | 0.62 | |||
| Minimum of Months | 96801429.15 | 0.62 | 40.01 | 0.62 | |
| Maximum of Months | 0.107173E+09 | 0.63 | 40.01 | 0.63 |
Report: FanReportMonthly
For: M NW APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.107173E+09 | 0.63 | 40.01 | 01-JAN-00:10 | 0.62 |
| February | 96801429.15 | 0.63 | 40.01 | 01-FEB-00:10 | 0.63 |
| March | 0.107173E+09 | 0.63 | 40.01 | 01-MAR-00:10 | 0.63 |
| April | 0.103716E+09 | 0.63 | 40.01 | 01-APR-00:10 | 0.63 |
| May | 0.107173E+09 | 0.62 | 40.01 | 01-MAY-00:10 | 0.62 |
| June | 0.103716E+09 | 0.62 | 40.01 | 01-JUN-00:10 | 0.62 |
| July | 0.107173E+09 | 0.62 | 40.01 | 01-JUL-00:10 | 0.62 |
| August | 0.107173E+09 | 0.62 | 40.01 | 01-AUG-00:10 | 0.62 |
| September | 0.103716E+09 | 0.62 | 40.01 | 01-SEP-00:10 | 0.62 |
| October | 0.107173E+09 | 0.62 | 40.01 | 01-OCT-00:10 | 0.62 |
| November | 0.103716E+09 | 0.62 | 40.01 | 01-NOV-00:10 | 0.62 |
| December | 0.107173E+09 | 0.63 | 40.01 | 01-DEC-00:10 | 0.62 |
| Annual Sum or Average | 0.126188E+10 | 0.62 | |||
| Minimum of Months | 96801429.15 | 0.62 | 40.01 | 0.62 | |
| Maximum of Months | 0.107173E+09 | 0.63 | 40.01 | 0.63 |
Report: FanReportMonthly
For: SPLIT MSE SUPPLY FAN
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.322726E+09 | 0.89 | 409.52 | 02-JAN-14:40 | 0.99 |
| February | 0.344065E+09 | 0.90 | 412.35 | 11-FEB-14:00 | 0.99 |
| March | 0.417503E+09 | 0.92 | 384.19 | 04-MAR-14:00 | 0.99 |
| April | 0.518785E+09 | 1.02 | 399.26 | 15-APR-16:05 | 0.99 |
| May | 0.679448E+09 | 1.02 | 445.21 | 29-MAY-16:06 | 0.98 |
| June | 0.736760E+09 | 1.01 | 416.80 | 03-JUN-16:03 | 0.99 |
| July | 0.776934E+09 | 1.01 | 448.47 | 27-JUL-16:05 | 0.98 |
| August | 0.775865E+09 | 1.01 | 464.56 | 20-AUG-12:00 | 0.98 |
| September | 0.760081E+09 | 1.01 | 484.91 | 20-SEP-14:00 | 0.97 |
| October | 0.720476E+09 | 1.01 | 487.41 | 29-OCT-14:00 | 0.97 |
| November | 0.538001E+09 | 0.98 | 439.69 | 22-NOV-12:40 | 0.98 |
| December | 0.363033E+09 | 0.91 | 429.69 | 10-DEC-14:30 | 0.98 |
| Annual Sum or Average | 0.695368E+10 | 0.97 | |||
| Minimum of Months | 0.322726E+09 | 0.89 | 384.19 | 0.97 | |
| Maximum of Months | 0.776934E+09 | 1.02 | 487.41 | 0.99 |
Report: FanReportMonthly
For: M SE APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.107173E+09 | 0.63 | 40.01 | 01-JAN-00:10 | 0.62 |
| February | 96801429.15 | 0.63 | 40.01 | 01-FEB-00:10 | 0.63 |
| March | 0.107173E+09 | 0.62 | 40.01 | 01-MAR-00:10 | 0.63 |
| April | 0.103716E+09 | 0.62 | 40.01 | 01-APR-00:10 | 0.62 |
| May | 0.107173E+09 | 0.62 | 40.01 | 01-MAY-00:10 | 0.62 |
| June | 0.103716E+09 | 0.62 | 40.01 | 01-JUN-00:10 | 0.62 |
| July | 0.107173E+09 | 0.62 | 40.01 | 01-JUL-00:10 | 0.62 |
| August | 0.107173E+09 | 0.62 | 40.01 | 01-AUG-00:10 | 0.62 |
| September | 0.103716E+09 | 0.62 | 40.01 | 01-SEP-00:10 | 0.62 |
| October | 0.107173E+09 | 0.62 | 40.01 | 01-OCT-00:10 | 0.62 |
| November | 0.103716E+09 | 0.62 | 40.01 | 01-NOV-00:10 | 0.62 |
| December | 0.107173E+09 | 0.62 | 40.01 | 01-DEC-00:10 | 0.62 |
| Annual Sum or Average | 0.126188E+10 | 0.62 | |||
| Minimum of Months | 96801429.15 | 0.62 | 40.01 | 0.62 | |
| Maximum of Months | 0.107173E+09 | 0.63 | 40.01 | 0.63 |
Report: FanReportMonthly
For: M SE APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.107173E+09 | 0.63 | 40.01 | 01-JAN-00:10 | 0.63 |
| February | 96801429.15 | 0.63 | 40.01 | 01-FEB-00:10 | 0.63 |
| March | 0.107173E+09 | 0.63 | 40.01 | 01-MAR-00:10 | 0.63 |
| April | 0.103716E+09 | 0.63 | 40.01 | 01-APR-00:10 | 0.63 |
| May | 0.107173E+09 | 0.62 | 40.01 | 01-MAY-00:10 | 0.62 |
| June | 0.103716E+09 | 0.62 | 40.01 | 01-JUN-00:10 | 0.62 |
| July | 0.107173E+09 | 0.62 | 40.01 | 01-JUL-00:10 | 0.62 |
| August | 0.107173E+09 | 0.62 | 40.01 | 01-AUG-00:10 | 0.62 |
| September | 0.103716E+09 | 0.62 | 40.01 | 01-SEP-00:10 | 0.62 |
| October | 0.107173E+09 | 0.62 | 40.01 | 01-OCT-00:10 | 0.62 |
| November | 0.103716E+09 | 0.63 | 40.01 | 01-NOV-00:10 | 0.62 |
| December | 0.107173E+09 | 0.63 | 40.01 | 01-DEC-00:10 | 0.62 |
| Annual Sum or Average | 0.126188E+10 | 0.63 | |||
| Minimum of Months | 96801429.15 | 0.62 | 40.01 | 0.62 | |
| Maximum of Months | 0.107173E+09 | 0.63 | 40.01 | 0.63 |
Report: FanReportMonthly
For: SPLIT MNE SUPPLY FAN
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.189506E+09 | 0.73 | 269.83 | 07-JAN-13:00 | 1.01 |
| February | 0.241626E+09 | 0.81 | 301.84 | 11-FEB-14:00 | 1.01 |
| March | 0.341054E+09 | 0.85 | 327.16 | 13-MAR-16:12 | 1.00 |
| April | 0.480172E+09 | 1.02 | 374.00 | 15-APR-16:30 | 1.00 |
| May | 0.685248E+09 | 1.02 | 444.89 | 29-MAY-16:10 | 0.98 |
| June | 0.756359E+09 | 1.01 | 430.30 | 08-JUN-16:02 | 0.98 |
| July | 0.789364E+09 | 1.01 | 452.30 | 27-JUL-16:10 | 0.98 |
| August | 0.766505E+09 | 1.01 | 438.73 | 20-AUG-12:00 | 0.98 |
| September | 0.712744E+09 | 1.01 | 428.72 | 18-SEP-16:10 | 0.98 |
| October | 0.626971E+09 | 1.02 | 409.16 | 03-OCT-11:00 | 0.99 |
| November | 0.426066E+09 | 0.96 | 349.28 | 04-NOV-16:10 | 1.00 |
| December | 0.235382E+09 | 0.71 | 302.62 | 10-DEC-14:00 | 1.01 |
| Annual Sum or Average | 0.625100E+10 | 0.93 | |||
| Minimum of Months | 0.189506E+09 | 0.71 | 269.83 | 0.98 | |
| Maximum of Months | 0.789364E+09 | 1.02 | 452.30 | 1.01 |
Report: FanReportMonthly
For: M NE APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.107173E+09 | 0.63 | 40.01 | 01-JAN-00:10 | 0.62 |
| February | 96801429.15 | 0.63 | 40.01 | 01-FEB-00:10 | 0.63 |
| March | 0.107173E+09 | 0.62 | 40.01 | 01-MAR-00:10 | 0.63 |
| April | 0.103716E+09 | 0.62 | 40.01 | 01-APR-00:10 | 0.62 |
| May | 0.107173E+09 | 0.62 | 40.01 | 01-MAY-00:10 | 0.62 |
| June | 0.103716E+09 | 0.62 | 40.01 | 01-JUN-00:10 | 0.62 |
| July | 0.107173E+09 | 0.62 | 40.01 | 01-JUL-00:10 | 0.62 |
| August | 0.107173E+09 | 0.62 | 40.01 | 01-AUG-00:10 | 0.62 |
| September | 0.103716E+09 | 0.62 | 40.01 | 01-SEP-00:10 | 0.62 |
| October | 0.107173E+09 | 0.62 | 40.01 | 01-OCT-00:10 | 0.62 |
| November | 0.103716E+09 | 0.62 | 40.01 | 01-NOV-00:10 | 0.62 |
| December | 0.107173E+09 | 0.62 | 40.01 | 01-DEC-00:10 | 0.62 |
| Annual Sum or Average | 0.126188E+10 | 0.62 | |||
| Minimum of Months | 96801429.15 | 0.62 | 40.01 | 0.62 | |
| Maximum of Months | 0.107173E+09 | 0.63 | 40.01 | 0.63 |
Report: FanReportMonthly
For: M NE APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.107173E+09 | 0.63 | 40.01 | 01-JAN-00:10 | 0.62 |
| February | 96801429.15 | 0.63 | 40.01 | 01-FEB-00:10 | 0.63 |
| March | 0.107173E+09 | 0.63 | 40.01 | 01-MAR-00:10 | 0.63 |
| April | 0.103716E+09 | 0.63 | 40.01 | 01-APR-00:10 | 0.63 |
| May | 0.107173E+09 | 0.62 | 40.01 | 01-MAY-00:10 | 0.62 |
| June | 0.103716E+09 | 0.62 | 40.01 | 01-JUN-00:10 | 0.62 |
| July | 0.107173E+09 | 0.62 | 40.01 | 01-JUL-00:10 | 0.62 |
| August | 0.107173E+09 | 0.62 | 40.01 | 01-AUG-00:10 | 0.62 |
| September | 0.103716E+09 | 0.62 | 40.01 | 01-SEP-00:10 | 0.62 |
| October | 0.107173E+09 | 0.62 | 40.01 | 01-OCT-00:10 | 0.62 |
| November | 0.103716E+09 | 0.62 | 40.01 | 01-NOV-00:10 | 0.62 |
| December | 0.107173E+09 | 0.63 | 40.01 | 01-DEC-00:10 | 0.62 |
| Annual Sum or Average | 0.126188E+10 | 0.62 | |||
| Minimum of Months | 96801429.15 | 0.62 | 40.01 | 0.62 | |
| Maximum of Months | 0.107173E+09 | 0.63 | 40.01 | 0.63 |
Report: FanReportMonthly
For: SPLIT MN1 SUPPLY FAN
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.184895E+09 | 0.80 | 224.14 | 07-JAN-13:00 | 1.02 |
| February | 0.221680E+09 | 0.85 | 253.18 | 11-FEB-17:10 | 1.01 |
| March | 0.299290E+09 | 0.88 | 271.65 | 13-MAR-16:12 | 1.01 |
| April | 0.406171E+09 | 1.03 | 301.87 | 15-APR-17:00 | 1.00 |
| May | 0.574294E+09 | 1.02 | 359.97 | 29-MAY-16:04 | 0.99 |
| June | 0.633664E+09 | 1.01 | 348.78 | 08-JUN-16:13 | 0.99 |
| July | 0.661878E+09 | 1.01 | 365.79 | 27-JUL-16:13 | 0.99 |
| August | 0.648417E+09 | 1.01 | 344.39 | 16-AUG-16:02 | 0.99 |
| September | 0.600772E+09 | 1.02 | 346.70 | 18-SEP-16:10 | 0.99 |
| October | 0.537938E+09 | 1.02 | 328.37 | 03-OCT-16:03 | 1.00 |
| November | 0.382087E+09 | 0.98 | 293.92 | 04-NOV-16:10 | 1.00 |
| December | 0.231642E+09 | 0.84 | 247.35 | 10-DEC-14:00 | 1.01 |
| Annual Sum or Average | 0.538273E+10 | 0.96 | |||
| Minimum of Months | 0.184895E+09 | 0.80 | 224.14 | 0.99 | |
| Maximum of Months | 0.661878E+09 | 1.03 | 365.79 | 1.02 |
Report: FanReportMonthly
For: M N1 APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.107173E+09 | 0.63 | 40.01 | 01-JAN-00:10 | 0.62 |
| February | 96801429.15 | 0.63 | 40.01 | 01-FEB-00:10 | 0.63 |
| March | 0.107173E+09 | 0.62 | 40.01 | 01-MAR-00:10 | 0.63 |
| April | 0.103716E+09 | 0.62 | 40.01 | 01-APR-00:10 | 0.62 |
| May | 0.107173E+09 | 0.62 | 40.01 | 01-MAY-00:10 | 0.62 |
| June | 0.103716E+09 | 0.62 | 40.01 | 01-JUN-00:10 | 0.62 |
| July | 0.107173E+09 | 0.62 | 40.01 | 01-JUL-00:10 | 0.62 |
| August | 0.107173E+09 | 0.62 | 40.01 | 01-AUG-00:10 | 0.62 |
| September | 0.103716E+09 | 0.62 | 40.01 | 01-SEP-00:10 | 0.62 |
| October | 0.107173E+09 | 0.62 | 40.01 | 01-OCT-00:10 | 0.62 |
| November | 0.103716E+09 | 0.62 | 40.01 | 01-NOV-00:10 | 0.62 |
| December | 0.107173E+09 | 0.62 | 40.01 | 01-DEC-00:10 | 0.62 |
| Annual Sum or Average | 0.126188E+10 | 0.62 | |||
| Minimum of Months | 96801429.15 | 0.62 | 40.01 | 0.62 | |
| Maximum of Months | 0.107173E+09 | 0.63 | 40.01 | 0.63 |
Report: FanReportMonthly
For: M N1 APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.107173E+09 | 0.63 | 40.01 | 01-JAN-00:10 | 0.62 |
| February | 96801429.15 | 0.63 | 40.01 | 01-FEB-00:10 | 0.63 |
| March | 0.107173E+09 | 0.63 | 40.01 | 01-MAR-00:10 | 0.63 |
| April | 0.103716E+09 | 0.63 | 40.01 | 01-APR-00:10 | 0.63 |
| May | 0.107173E+09 | 0.62 | 40.01 | 01-MAY-00:10 | 0.62 |
| June | 0.103716E+09 | 0.62 | 40.01 | 01-JUN-00:10 | 0.62 |
| July | 0.107173E+09 | 0.62 | 40.01 | 01-JUL-00:10 | 0.62 |
| August | 0.107173E+09 | 0.62 | 40.01 | 01-AUG-00:10 | 0.62 |
| September | 0.103716E+09 | 0.62 | 40.01 | 01-SEP-00:10 | 0.62 |
| October | 0.107173E+09 | 0.62 | 40.01 | 01-OCT-00:10 | 0.62 |
| November | 0.103716E+09 | 0.62 | 40.01 | 01-NOV-00:10 | 0.62 |
| December | 0.107173E+09 | 0.63 | 40.01 | 01-DEC-00:10 | 0.62 |
| Annual Sum or Average | 0.126188E+10 | 0.62 | |||
| Minimum of Months | 96801429.15 | 0.62 | 40.01 | 0.62 | |
| Maximum of Months | 0.107173E+09 | 0.63 | 40.01 | 0.63 |
Report: FanReportMonthly
For: SPLIT MN2 SUPPLY FAN
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.185350E+09 | 0.80 | 224.32 | 07-JAN-13:00 | 1.02 |
| February | 0.221781E+09 | 0.85 | 251.99 | 11-FEB-17:10 | 1.01 |
| March | 0.299373E+09 | 0.88 | 270.93 | 13-MAR-16:12 | 1.01 |
| April | 0.405976E+09 | 1.03 | 301.03 | 15-APR-17:00 | 1.00 |
| May | 0.574069E+09 | 1.02 | 359.22 | 29-MAY-16:04 | 0.99 |
| June | 0.633846E+09 | 1.01 | 348.24 | 08-JUN-16:13 | 0.99 |
| July | 0.661854E+09 | 1.01 | 365.11 | 27-JUL-16:13 | 0.99 |
| August | 0.648127E+09 | 1.01 | 343.65 | 16-AUG-16:02 | 0.99 |
| September | 0.600835E+09 | 1.02 | 346.09 | 18-SEP-16:10 | 0.99 |
| October | 0.537852E+09 | 1.02 | 327.96 | 03-OCT-16:03 | 1.00 |
| November | 0.382098E+09 | 0.98 | 293.78 | 04-NOV-16:10 | 1.00 |
| December | 0.231198E+09 | 0.84 | 247.29 | 10-DEC-14:00 | 1.01 |
| Annual Sum or Average | 0.538236E+10 | 0.96 | |||
| Minimum of Months | 0.185350E+09 | 0.80 | 224.32 | 0.99 | |
| Maximum of Months | 0.661854E+09 | 1.03 | 365.11 | 1.02 |
Report: FanReportMonthly
For: M N2 APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.107173E+09 | 0.63 | 40.01 | 01-JAN-00:10 | 0.62 |
| February | 96801429.15 | 0.63 | 40.01 | 01-FEB-00:10 | 0.63 |
| March | 0.107173E+09 | 0.62 | 40.01 | 01-MAR-00:10 | 0.63 |
| April | 0.103716E+09 | 0.62 | 40.01 | 01-APR-00:10 | 0.62 |
| May | 0.107173E+09 | 0.62 | 40.01 | 01-MAY-00:10 | 0.62 |
| June | 0.103716E+09 | 0.62 | 40.01 | 01-JUN-00:10 | 0.62 |
| July | 0.107173E+09 | 0.62 | 40.01 | 01-JUL-00:10 | 0.62 |
| August | 0.107173E+09 | 0.62 | 40.01 | 01-AUG-00:10 | 0.62 |
| September | 0.103716E+09 | 0.62 | 40.01 | 01-SEP-00:10 | 0.62 |
| October | 0.107173E+09 | 0.62 | 40.01 | 01-OCT-00:10 | 0.62 |
| November | 0.103716E+09 | 0.62 | 40.01 | 01-NOV-00:10 | 0.62 |
| December | 0.107173E+09 | 0.62 | 40.01 | 01-DEC-00:10 | 0.62 |
| Annual Sum or Average | 0.126188E+10 | 0.62 | |||
| Minimum of Months | 96801429.15 | 0.62 | 40.01 | 0.62 | |
| Maximum of Months | 0.107173E+09 | 0.63 | 40.01 | 0.63 |
Report: FanReportMonthly
For: M N2 APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.107173E+09 | 0.63 | 40.01 | 01-JAN-00:10 | 0.62 |
| February | 96801429.15 | 0.63 | 40.01 | 01-FEB-00:10 | 0.63 |
| March | 0.107173E+09 | 0.63 | 40.01 | 01-MAR-00:10 | 0.63 |
| April | 0.103716E+09 | 0.63 | 40.01 | 01-APR-00:10 | 0.63 |
| May | 0.107173E+09 | 0.62 | 40.01 | 01-MAY-00:10 | 0.62 |
| June | 0.103716E+09 | 0.62 | 40.01 | 01-JUN-00:10 | 0.62 |
| July | 0.107173E+09 | 0.62 | 40.01 | 01-JUL-00:10 | 0.62 |
| August | 0.107173E+09 | 0.62 | 40.01 | 01-AUG-00:10 | 0.62 |
| September | 0.103716E+09 | 0.62 | 40.01 | 01-SEP-00:10 | 0.62 |
| October | 0.107173E+09 | 0.62 | 40.01 | 01-OCT-00:10 | 0.62 |
| November | 0.103716E+09 | 0.62 | 40.01 | 01-NOV-00:10 | 0.62 |
| December | 0.107173E+09 | 0.63 | 40.01 | 01-DEC-00:10 | 0.62 |
| Annual Sum or Average | 0.126188E+10 | 0.62 | |||
| Minimum of Months | 96801429.15 | 0.62 | 40.01 | 0.62 | |
| Maximum of Months | 0.107173E+09 | 0.63 | 40.01 | 0.63 |
Report: FanReportMonthly
For: SPLIT MS1 SUPPLY FAN
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.325426E+09 | 0.99 | 365.46 | 02-JAN-14:40 | 0.99 |
| February | 0.329969E+09 | 0.97 | 357.26 | 11-FEB-14:00 | 0.99 |
| March | 0.377901E+09 | 0.96 | 316.15 | 13-MAR-16:02 | 1.00 |
| April | 0.445097E+09 | 1.03 | 325.79 | 15-APR-16:30 | 1.00 |
| May | 0.567687E+09 | 1.02 | 359.83 | 29-MAY-16:04 | 0.99 |
| June | 0.612771E+09 | 1.01 | 336.15 | 03-JUN-16:03 | 0.99 |
| July | 0.648346E+09 | 1.01 | 361.31 | 29-JUL-16:03 | 0.99 |
| August | 0.657307E+09 | 1.01 | 362.49 | 20-AUG-12:00 | 0.99 |
| September | 0.648745E+09 | 1.01 | 396.76 | 20-SEP-14:00 | 0.98 |
| October | 0.632815E+09 | 1.02 | 409.70 | 29-OCT-14:00 | 0.98 |
| November | 0.496030E+09 | 1.00 | 372.83 | 22-NOV-12:30 | 0.99 |
| December | 0.367548E+09 | 0.96 | 375.62 | 10-DEC-14:30 | 0.99 |
| Annual Sum or Average | 0.610964E+10 | 1.00 | |||
| Minimum of Months | 0.325426E+09 | 0.96 | 316.15 | 0.98 | |
| Maximum of Months | 0.657307E+09 | 1.03 | 409.70 | 1.00 |
Report: FanReportMonthly
For: M S1 APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.107173E+09 | 0.63 | 40.01 | 01-JAN-00:10 | 0.62 |
| February | 96801429.15 | 0.63 | 40.01 | 01-FEB-00:10 | 0.63 |
| March | 0.107173E+09 | 0.62 | 40.01 | 01-MAR-00:10 | 0.63 |
| April | 0.103716E+09 | 0.62 | 40.01 | 01-APR-00:10 | 0.62 |
| May | 0.107173E+09 | 0.62 | 40.01 | 01-MAY-00:10 | 0.62 |
| June | 0.103716E+09 | 0.62 | 40.01 | 01-JUN-00:10 | 0.62 |
| July | 0.107173E+09 | 0.62 | 40.01 | 01-JUL-00:10 | 0.62 |
| August | 0.107173E+09 | 0.62 | 40.01 | 01-AUG-00:10 | 0.62 |
| September | 0.103716E+09 | 0.62 | 40.01 | 01-SEP-00:10 | 0.62 |
| October | 0.107173E+09 | 0.62 | 40.01 | 01-OCT-00:10 | 0.62 |
| November | 0.103716E+09 | 0.62 | 40.01 | 01-NOV-00:10 | 0.62 |
| December | 0.107173E+09 | 0.62 | 40.01 | 01-DEC-00:10 | 0.62 |
| Annual Sum or Average | 0.126188E+10 | 0.62 | |||
| Minimum of Months | 96801429.15 | 0.62 | 40.01 | 0.62 | |
| Maximum of Months | 0.107173E+09 | 0.63 | 40.01 | 0.63 |
Report: FanReportMonthly
For: M S1 APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.107173E+09 | 0.63 | 40.01 | 01-JAN-00:10 | 0.63 |
| February | 96801429.15 | 0.63 | 40.01 | 01-FEB-00:10 | 0.63 |
| March | 0.107173E+09 | 0.63 | 40.01 | 01-MAR-00:10 | 0.63 |
| April | 0.103716E+09 | 0.63 | 40.01 | 01-APR-00:10 | 0.63 |
| May | 0.107173E+09 | 0.62 | 40.01 | 01-MAY-00:10 | 0.62 |
| June | 0.103716E+09 | 0.62 | 40.01 | 01-JUN-00:10 | 0.62 |
| July | 0.107173E+09 | 0.62 | 40.01 | 01-JUL-00:10 | 0.62 |
| August | 0.107173E+09 | 0.62 | 40.01 | 01-AUG-00:10 | 0.62 |
| September | 0.103716E+09 | 0.62 | 40.01 | 01-SEP-00:10 | 0.62 |
| October | 0.107173E+09 | 0.62 | 40.01 | 01-OCT-00:10 | 0.62 |
| November | 0.103716E+09 | 0.63 | 40.01 | 01-NOV-00:10 | 0.62 |
| December | 0.107173E+09 | 0.63 | 40.01 | 01-DEC-00:10 | 0.62 |
| Annual Sum or Average | 0.126188E+10 | 0.63 | |||
| Minimum of Months | 96801429.15 | 0.62 | 40.01 | 0.62 | |
| Maximum of Months | 0.107173E+09 | 0.63 | 40.01 | 0.63 |
Report: FanReportMonthly
For: SPLIT MS2 SUPPLY FAN
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.325648E+09 | 0.99 | 365.62 | 02-JAN-14:40 | 0.99 |
| February | 0.329972E+09 | 0.97 | 357.17 | 11-FEB-14:00 | 0.99 |
| March | 0.377902E+09 | 0.96 | 315.47 | 13-MAR-16:02 | 1.00 |
| April | 0.444870E+09 | 1.03 | 325.08 | 15-APR-16:30 | 1.00 |
| May | 0.567446E+09 | 1.02 | 359.07 | 29-MAY-16:04 | 0.99 |
| June | 0.612946E+09 | 1.01 | 336.04 | 03-JUN-16:03 | 0.99 |
| July | 0.648305E+09 | 1.01 | 360.85 | 29-JUL-16:03 | 0.99 |
| August | 0.656986E+09 | 1.01 | 363.00 | 20-AUG-12:00 | 0.99 |
| September | 0.648737E+09 | 1.01 | 396.71 | 20-SEP-14:00 | 0.98 |
| October | 0.632631E+09 | 1.02 | 409.60 | 29-OCT-14:00 | 0.98 |
| November | 0.495914E+09 | 1.00 | 373.46 | 22-NOV-12:30 | 0.99 |
| December | 0.367103E+09 | 0.96 | 375.31 | 10-DEC-14:30 | 0.99 |
| Annual Sum or Average | 0.610846E+10 | 1.00 | |||
| Minimum of Months | 0.325648E+09 | 0.96 | 315.47 | 0.98 | |
| Maximum of Months | 0.656986E+09 | 1.03 | 409.60 | 1.00 |
Report: FanReportMonthly
For: M S2 APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.107173E+09 | 0.63 | 40.01 | 01-JAN-00:10 | 0.62 |
| February | 96801429.15 | 0.63 | 40.01 | 01-FEB-00:10 | 0.63 |
| March | 0.107173E+09 | 0.62 | 40.01 | 01-MAR-00:10 | 0.63 |
| April | 0.103716E+09 | 0.62 | 40.01 | 01-APR-00:10 | 0.62 |
| May | 0.107173E+09 | 0.62 | 40.01 | 01-MAY-00:10 | 0.62 |
| June | 0.103716E+09 | 0.62 | 40.01 | 01-JUN-00:10 | 0.62 |
| July | 0.107173E+09 | 0.62 | 40.01 | 01-JUL-00:10 | 0.62 |
| August | 0.107173E+09 | 0.62 | 40.01 | 01-AUG-00:10 | 0.62 |
| September | 0.103716E+09 | 0.62 | 40.01 | 01-SEP-00:10 | 0.62 |
| October | 0.107173E+09 | 0.62 | 40.01 | 01-OCT-00:10 | 0.62 |
| November | 0.103716E+09 | 0.62 | 40.01 | 01-NOV-00:10 | 0.62 |
| December | 0.107173E+09 | 0.62 | 40.01 | 01-DEC-00:10 | 0.62 |
| Annual Sum or Average | 0.126188E+10 | 0.62 | |||
| Minimum of Months | 96801429.15 | 0.62 | 40.01 | 0.62 | |
| Maximum of Months | 0.107173E+09 | 0.63 | 40.01 | 0.63 |
Report: FanReportMonthly
For: M S2 APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.107173E+09 | 0.63 | 40.01 | 01-JAN-00:10 | 0.63 |
| February | 96801429.15 | 0.63 | 40.01 | 01-FEB-00:10 | 0.63 |
| March | 0.107173E+09 | 0.63 | 40.01 | 01-MAR-00:10 | 0.63 |
| April | 0.103716E+09 | 0.63 | 40.01 | 01-APR-00:10 | 0.63 |
| May | 0.107173E+09 | 0.62 | 40.01 | 01-MAY-00:10 | 0.62 |
| June | 0.103716E+09 | 0.62 | 40.01 | 01-JUN-00:10 | 0.62 |
| July | 0.107173E+09 | 0.62 | 40.01 | 01-JUL-00:10 | 0.62 |
| August | 0.107173E+09 | 0.62 | 40.01 | 01-AUG-00:10 | 0.62 |
| September | 0.103716E+09 | 0.62 | 40.01 | 01-SEP-00:10 | 0.62 |
| October | 0.107173E+09 | 0.62 | 40.01 | 01-OCT-00:10 | 0.62 |
| November | 0.103716E+09 | 0.63 | 40.01 | 01-NOV-00:10 | 0.62 |
| December | 0.107173E+09 | 0.63 | 40.01 | 01-DEC-00:10 | 0.62 |
| Annual Sum or Average | 0.126188E+10 | 0.63 | |||
| Minimum of Months | 96801429.15 | 0.62 | 40.01 | 0.62 | |
| Maximum of Months | 0.107173E+09 | 0.63 | 40.01 | 0.63 |
Report: FanReportMonthly
For: SPLIT TSW SUPPLY FAN
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.139014E+09 | 0.66 | 275.01 | 02-JAN-15:00 | 0.98 |
| February | 0.170914E+09 | 0.76 | 293.47 | 11-FEB-16:20 | 0.97 |
| March | 0.215152E+09 | 0.86 | 267.94 | 13-MAR-16:25 | 0.98 |
| April | 0.278163E+09 | 0.99 | 300.84 | 15-APR-16:30 | 0.97 |
| May | 0.384292E+09 | 1.02 | 327.87 | 29-MAY-16:04 | 0.96 |
| June | 0.416716E+09 | 1.01 | 303.50 | 08-JUN-16:02 | 0.97 |
| July | 0.443839E+09 | 1.01 | 326.14 | 27-JUL-16:10 | 0.96 |
| August | 0.441435E+09 | 1.01 | 319.35 | 16-AUG-16:02 | 0.97 |
| September | 0.425407E+09 | 1.01 | 331.84 | 20-SEP-14:10 | 0.96 |
| October | 0.388884E+09 | 1.02 | 331.57 | 29-OCT-14:10 | 0.96 |
| November | 0.276457E+09 | 0.91 | 282.09 | 10-NOV-14:30 | 0.98 |
| December | 0.177893E+09 | 0.73 | 292.65 | 10-DEC-15:00 | 0.98 |
| Annual Sum or Average | 0.375817E+10 | 0.92 | |||
| Minimum of Months | 0.139014E+09 | 0.66 | 267.94 | 0.96 | |
| Maximum of Months | 0.443839E+09 | 1.02 | 331.84 | 0.98 |
Report: FanReportMonthly
For: T SW APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.63 | 20.01 | 01-JAN-00:10 | 0.62 |
| February | 48400714.57 | 0.63 | 20.01 | 01-FEB-00:10 | 0.63 |
| March | 53586505.42 | 0.62 | 20.01 | 01-MAR-00:10 | 0.63 |
| April | 51857908.47 | 0.62 | 20.01 | 01-APR-00:10 | 0.62 |
| May | 53586505.42 | 0.62 | 20.01 | 01-MAY-00:10 | 0.62 |
| June | 51857908.47 | 0.62 | 20.01 | 01-JUN-00:10 | 0.62 |
| July | 53586505.42 | 0.62 | 20.01 | 01-JUL-00:10 | 0.62 |
| August | 53586505.42 | 0.62 | 20.01 | 01-AUG-00:10 | 0.62 |
| September | 51857908.47 | 0.62 | 20.01 | 01-SEP-00:10 | 0.62 |
| October | 53586505.42 | 0.62 | 20.01 | 01-OCT-00:10 | 0.62 |
| November | 51857908.47 | 0.62 | 20.01 | 01-NOV-00:10 | 0.62 |
| December | 53586505.42 | 0.62 | 20.01 | 01-DEC-00:10 | 0.62 |
| Annual Sum or Average | 0.630938E+09 | 0.62 | |||
| Minimum of Months | 48400714.57 | 0.62 | 20.01 | 0.62 | |
| Maximum of Months | 53586505.42 | 0.63 | 20.01 | 0.63 |
Report: FanReportMonthly
For: T SW APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.63 | 20.01 | 01-JAN-00:10 | 0.62 |
| February | 48400714.57 | 0.63 | 20.01 | 01-FEB-00:10 | 0.63 |
| March | 53586505.42 | 0.63 | 20.01 | 01-MAR-00:10 | 0.63 |
| April | 51857908.47 | 0.63 | 20.01 | 01-APR-00:10 | 0.63 |
| May | 53586505.42 | 0.62 | 20.01 | 01-MAY-00:10 | 0.62 |
| June | 51857908.47 | 0.62 | 20.01 | 01-JUN-00:10 | 0.62 |
| July | 53586505.42 | 0.62 | 20.01 | 01-JUL-00:10 | 0.62 |
| August | 53586505.42 | 0.62 | 20.01 | 01-AUG-00:10 | 0.62 |
| September | 51857908.47 | 0.62 | 20.01 | 01-SEP-00:10 | 0.62 |
| October | 53586505.42 | 0.62 | 20.01 | 01-OCT-00:10 | 0.62 |
| November | 51857908.47 | 0.62 | 20.01 | 01-NOV-00:10 | 0.62 |
| December | 53586505.42 | 0.63 | 20.01 | 01-DEC-00:10 | 0.62 |
| Annual Sum or Average | 0.630938E+09 | 0.62 | |||
| Minimum of Months | 48400714.57 | 0.62 | 20.01 | 0.62 | |
| Maximum of Months | 53586505.42 | 0.63 | 20.01 | 0.63 |
Report: FanReportMonthly
For: SPLIT TNW SUPPLY FAN
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 80989477.86 | 0.58 | 177.25 | 02-JAN-15:00 | 1.01 |
| February | 0.121774E+09 | 0.72 | 234.11 | 11-FEB-16:20 | 0.99 |
| March | 0.179913E+09 | 0.82 | 245.11 | 13-MAR-16:25 | 0.99 |
| April | 0.257492E+09 | 0.99 | 286.12 | 15-APR-16:40 | 0.98 |
| May | 0.388490E+09 | 1.02 | 330.12 | 29-MAY-16:30 | 0.97 |
| June | 0.428312E+09 | 1.01 | 314.69 | 08-JUN-16:13 | 0.97 |
| July | 0.451502E+09 | 1.01 | 327.80 | 27-JUL-16:10 | 0.97 |
| August | 0.436901E+09 | 1.02 | 315.43 | 16-AUG-16:02 | 0.97 |
| September | 0.399870E+09 | 1.02 | 303.62 | 17-SEP-16:15 | 0.97 |
| October | 0.338661E+09 | 1.03 | 280.17 | 03-OCT-16:17 | 0.98 |
| November | 0.218806E+09 | 0.89 | 220.49 | 03-NOV-16:10 | 1.00 |
| December | 0.121321E+09 | 0.65 | 212.44 | 10-DEC-15:00 | 1.00 |
| Annual Sum or Average | 0.342403E+10 | 0.90 | |||
| Minimum of Months | 80989477.86 | 0.58 | 177.25 | 0.97 | |
| Maximum of Months | 0.451502E+09 | 1.03 | 330.12 | 1.01 |
Report: FanReportMonthly
For: T NW APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.63 | 20.01 | 01-JAN-00:10 | 0.62 |
| February | 48400714.57 | 0.63 | 20.01 | 01-FEB-00:10 | 0.63 |
| March | 53586505.42 | 0.62 | 20.01 | 01-MAR-00:10 | 0.63 |
| April | 51857908.47 | 0.62 | 20.01 | 01-APR-00:10 | 0.62 |
| May | 53586505.42 | 0.62 | 20.01 | 01-MAY-00:10 | 0.62 |
| June | 51857908.47 | 0.62 | 20.01 | 01-JUN-00:10 | 0.62 |
| July | 53586505.42 | 0.62 | 20.01 | 01-JUL-00:10 | 0.62 |
| August | 53586505.42 | 0.62 | 20.01 | 01-AUG-00:10 | 0.62 |
| September | 51857908.47 | 0.62 | 20.01 | 01-SEP-00:10 | 0.62 |
| October | 53586505.42 | 0.62 | 20.01 | 01-OCT-00:10 | 0.62 |
| November | 51857908.47 | 0.62 | 20.01 | 01-NOV-00:10 | 0.62 |
| December | 53586505.42 | 0.62 | 20.01 | 01-DEC-00:10 | 0.62 |
| Annual Sum or Average | 0.630938E+09 | 0.62 | |||
| Minimum of Months | 48400714.57 | 0.62 | 20.01 | 0.62 | |
| Maximum of Months | 53586505.42 | 0.63 | 20.01 | 0.63 |
Report: FanReportMonthly
For: T NW APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.63 | 20.01 | 01-JAN-00:10 | 0.62 |
| February | 48400714.57 | 0.63 | 20.01 | 01-FEB-00:10 | 0.63 |
| March | 53586505.42 | 0.63 | 20.01 | 01-MAR-00:10 | 0.63 |
| April | 51857908.47 | 0.63 | 20.01 | 01-APR-00:10 | 0.63 |
| May | 53586505.42 | 0.62 | 20.01 | 01-MAY-00:10 | 0.62 |
| June | 51857908.47 | 0.62 | 20.01 | 01-JUN-00:10 | 0.62 |
| July | 53586505.42 | 0.62 | 20.01 | 01-JUL-00:10 | 0.62 |
| August | 53586505.42 | 0.62 | 20.01 | 01-AUG-00:10 | 0.62 |
| September | 51857908.47 | 0.62 | 20.01 | 01-SEP-00:10 | 0.62 |
| October | 53586505.42 | 0.62 | 20.01 | 01-OCT-00:10 | 0.62 |
| November | 51857908.47 | 0.62 | 20.01 | 01-NOV-00:10 | 0.62 |
| December | 53586505.42 | 0.63 | 20.01 | 01-DEC-00:10 | 0.62 |
| Annual Sum or Average | 0.630938E+09 | 0.62 | |||
| Minimum of Months | 48400714.57 | 0.62 | 20.01 | 0.62 | |
| Maximum of Months | 53586505.42 | 0.63 | 20.01 | 0.63 |
Report: FanReportMonthly
For: SPLIT TSE SUPPLY FAN
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.138085E+09 | 0.67 | 256.01 | 02-JAN-14:40 | 0.98 |
| February | 0.166142E+09 | 0.77 | 266.88 | 11-FEB-14:00 | 0.97 |
| March | 0.206358E+09 | 0.85 | 244.64 | 04-MAR-14:00 | 0.98 |
| April | 0.270143E+09 | 0.99 | 254.12 | 15-APR-16:03 | 0.98 |
| May | 0.374267E+09 | 1.02 | 285.26 | 29-MAY-16:10 | 0.96 |
| June | 0.411493E+09 | 1.01 | 261.65 | 25-JUN-14:00 | 0.97 |
| July | 0.435547E+09 | 1.01 | 287.51 | 27-JUL-16:10 | 0.96 |
| August | 0.428706E+09 | 1.01 | 297.12 | 20-AUG-12:00 | 0.96 |
| September | 0.417953E+09 | 1.01 | 310.23 | 20-SEP-14:00 | 0.96 |
| October | 0.380144E+09 | 1.02 | 309.06 | 29-OCT-14:00 | 0.95 |
| November | 0.269725E+09 | 0.91 | 277.90 | 22-NOV-12:40 | 0.97 |
| December | 0.168251E+09 | 0.73 | 266.90 | 10-DEC-14:00 | 0.97 |
| Annual Sum or Average | 0.366681E+10 | 0.92 | |||
| Minimum of Months | 0.138085E+09 | 0.67 | 244.64 | 0.95 | |
| Maximum of Months | 0.435547E+09 | 1.02 | 310.23 | 0.98 |
Report: FanReportMonthly
For: T SE APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.63 | 20.01 | 01-JAN-00:10 | 0.62 |
| February | 48400714.57 | 0.63 | 20.01 | 01-FEB-00:10 | 0.63 |
| March | 53586505.42 | 0.62 | 20.01 | 01-MAR-00:10 | 0.63 |
| April | 51857908.47 | 0.62 | 20.01 | 01-APR-00:10 | 0.62 |
| May | 53586505.42 | 0.62 | 20.01 | 01-MAY-00:10 | 0.62 |
| June | 51857908.47 | 0.62 | 20.01 | 01-JUN-00:10 | 0.62 |
| July | 53586505.42 | 0.62 | 20.01 | 01-JUL-00:10 | 0.62 |
| August | 53586505.42 | 0.62 | 20.01 | 01-AUG-00:10 | 0.62 |
| September | 51857908.47 | 0.62 | 20.01 | 01-SEP-00:10 | 0.62 |
| October | 53586505.42 | 0.62 | 20.01 | 01-OCT-00:10 | 0.62 |
| November | 51857908.47 | 0.62 | 20.01 | 01-NOV-00:10 | 0.62 |
| December | 53586505.42 | 0.62 | 20.01 | 01-DEC-00:10 | 0.62 |
| Annual Sum or Average | 0.630938E+09 | 0.62 | |||
| Minimum of Months | 48400714.57 | 0.62 | 20.01 | 0.62 | |
| Maximum of Months | 53586505.42 | 0.63 | 20.01 | 0.63 |
Report: FanReportMonthly
For: T SE APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.63 | 20.01 | 01-JAN-00:10 | 0.62 |
| February | 48400714.57 | 0.63 | 20.01 | 01-FEB-00:10 | 0.63 |
| March | 53586505.42 | 0.63 | 20.01 | 01-MAR-00:10 | 0.63 |
| April | 51857908.47 | 0.63 | 20.01 | 01-APR-00:10 | 0.63 |
| May | 53586505.42 | 0.62 | 20.01 | 01-MAY-00:10 | 0.62 |
| June | 51857908.47 | 0.62 | 20.01 | 01-JUN-00:10 | 0.62 |
| July | 53586505.42 | 0.62 | 20.01 | 01-JUL-00:10 | 0.62 |
| August | 53586505.42 | 0.62 | 20.01 | 01-AUG-00:10 | 0.62 |
| September | 51857908.47 | 0.62 | 20.01 | 01-SEP-00:10 | 0.62 |
| October | 53586505.42 | 0.62 | 20.01 | 01-OCT-00:10 | 0.62 |
| November | 51857908.47 | 0.62 | 20.01 | 01-NOV-00:10 | 0.62 |
| December | 53586505.42 | 0.63 | 20.01 | 01-DEC-00:10 | 0.62 |
| Annual Sum or Average | 0.630938E+09 | 0.62 | |||
| Minimum of Months | 48400714.57 | 0.62 | 20.01 | 0.62 | |
| Maximum of Months | 53586505.42 | 0.63 | 20.01 | 0.63 |
Report: FanReportMonthly
For: SPLIT TNE SUPPLY FAN
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 80375217.32 | 0.57 | 163.80 | 07-JAN-13:00 | 1.01 |
| February | 0.117660E+09 | 0.72 | 197.99 | 11-FEB-14:00 | 1.00 |
| March | 0.171540E+09 | 0.81 | 205.91 | 04-MAR-14:00 | 0.99 |
| April | 0.250304E+09 | 1.00 | 238.02 | 15-APR-16:20 | 0.99 |
| May | 0.378691E+09 | 1.02 | 286.51 | 29-MAY-16:10 | 0.97 |
| June | 0.423128E+09 | 1.01 | 269.82 | 08-JUN-16:02 | 0.97 |
| July | 0.443451E+09 | 1.01 | 289.06 | 27-JUL-16:10 | 0.97 |
| August | 0.424819E+09 | 1.01 | 282.66 | 20-AUG-12:00 | 0.97 |
| September | 0.393917E+09 | 1.01 | 266.61 | 18-SEP-16:10 | 0.97 |
| October | 0.332109E+09 | 1.02 | 261.00 | 03-OCT-11:30 | 0.97 |
| November | 0.213462E+09 | 0.89 | 207.39 | 04-NOV-12:00 | 0.99 |
| December | 0.113486E+09 | 0.63 | 189.93 | 10-DEC-14:00 | 1.00 |
| Annual Sum or Average | 0.334294E+10 | 0.89 | |||
| Minimum of Months | 80375217.32 | 0.57 | 163.80 | 0.97 | |
| Maximum of Months | 0.443451E+09 | 1.02 | 289.06 | 1.01 |
Report: FanReportMonthly
For: T NE APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.63 | 20.01 | 01-JAN-00:10 | 0.62 |
| February | 48400714.57 | 0.63 | 20.01 | 01-FEB-00:10 | 0.63 |
| March | 53586505.42 | 0.62 | 20.01 | 01-MAR-00:10 | 0.63 |
| April | 51857908.47 | 0.62 | 20.01 | 01-APR-00:10 | 0.62 |
| May | 53586505.42 | 0.62 | 20.01 | 01-MAY-00:10 | 0.62 |
| June | 51857908.47 | 0.62 | 20.01 | 01-JUN-00:10 | 0.62 |
| July | 53586505.42 | 0.62 | 20.01 | 01-JUL-00:10 | 0.62 |
| August | 53586505.42 | 0.62 | 20.01 | 01-AUG-00:10 | 0.62 |
| September | 51857908.47 | 0.62 | 20.01 | 01-SEP-00:10 | 0.62 |
| October | 53586505.42 | 0.62 | 20.01 | 01-OCT-00:10 | 0.62 |
| November | 51857908.47 | 0.62 | 20.01 | 01-NOV-00:10 | 0.62 |
| December | 53586505.42 | 0.62 | 20.01 | 01-DEC-00:10 | 0.62 |
| Annual Sum or Average | 0.630938E+09 | 0.62 | |||
| Minimum of Months | 48400714.57 | 0.62 | 20.01 | 0.62 | |
| Maximum of Months | 53586505.42 | 0.63 | 20.01 | 0.63 |
Report: FanReportMonthly
For: T NE APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.63 | 20.01 | 01-JAN-00:10 | 0.62 |
| February | 48400714.57 | 0.63 | 20.01 | 01-FEB-00:10 | 0.63 |
| March | 53586505.42 | 0.63 | 20.01 | 01-MAR-00:10 | 0.63 |
| April | 51857908.47 | 0.63 | 20.01 | 01-APR-00:10 | 0.63 |
| May | 53586505.42 | 0.62 | 20.01 | 01-MAY-00:10 | 0.62 |
| June | 51857908.47 | 0.62 | 20.01 | 01-JUN-00:10 | 0.62 |
| July | 53586505.42 | 0.62 | 20.01 | 01-JUL-00:10 | 0.62 |
| August | 53586505.42 | 0.62 | 20.01 | 01-AUG-00:10 | 0.62 |
| September | 51857908.47 | 0.62 | 20.01 | 01-SEP-00:10 | 0.62 |
| October | 53586505.42 | 0.62 | 20.01 | 01-OCT-00:10 | 0.62 |
| November | 51857908.47 | 0.62 | 20.01 | 01-NOV-00:10 | 0.62 |
| December | 53586505.42 | 0.63 | 20.01 | 01-DEC-00:10 | 0.62 |
| Annual Sum or Average | 0.630938E+09 | 0.62 | |||
| Minimum of Months | 48400714.57 | 0.62 | 20.01 | 0.62 | |
| Maximum of Months | 53586505.42 | 0.63 | 20.01 | 0.63 |
Report: FanReportMonthly
For: SPLIT TN1 SUPPLY FAN
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 72040959.00 | 0.57 | 135.12 | 07-JAN-13:00 | 1.02 |
| February | 0.103831E+09 | 0.75 | 164.93 | 11-FEB-14:00 | 1.01 |
| March | 0.149535E+09 | 0.81 | 174.33 | 13-MAR-16:12 | 1.00 |
| April | 0.214832E+09 | 1.00 | 198.94 | 15-APR-16:15 | 0.99 |
| May | 0.323064E+09 | 1.02 | 237.78 | 29-MAY-16:04 | 0.98 |
| June | 0.361210E+09 | 1.01 | 226.35 | 08-JUN-16:02 | 0.98 |
| July | 0.379561E+09 | 1.01 | 241.17 | 27-JUL-16:10 | 0.98 |
| August | 0.365494E+09 | 1.01 | 223.58 | 16-AUG-16:02 | 0.98 |
| September | 0.337418E+09 | 1.02 | 221.64 | 18-SEP-16:10 | 0.98 |
| October | 0.288028E+09 | 1.03 | 209.88 | 03-OCT-15:10 | 0.99 |
| November | 0.189364E+09 | 0.91 | 174.54 | 04-NOV-16:10 | 1.00 |
| December | 0.104217E+09 | 0.65 | 156.95 | 10-DEC-14:00 | 1.01 |
| Annual Sum or Average | 0.288860E+10 | 0.90 | |||
| Minimum of Months | 72040959.00 | 0.57 | 135.12 | 0.98 | |
| Maximum of Months | 0.379561E+09 | 1.03 | 241.17 | 1.02 |
Report: FanReportMonthly
For: T N1 APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.63 | 20.01 | 01-JAN-00:10 | 0.62 |
| February | 48400714.57 | 0.63 | 20.01 | 01-FEB-00:10 | 0.63 |
| March | 53586505.42 | 0.62 | 20.01 | 01-MAR-00:10 | 0.63 |
| April | 51857908.47 | 0.62 | 20.01 | 01-APR-00:10 | 0.62 |
| May | 53586505.42 | 0.62 | 20.01 | 01-MAY-00:10 | 0.62 |
| June | 51857908.47 | 0.62 | 20.01 | 01-JUN-00:10 | 0.62 |
| July | 53586505.42 | 0.62 | 20.01 | 01-JUL-00:10 | 0.62 |
| August | 53586505.42 | 0.62 | 20.01 | 01-AUG-00:10 | 0.62 |
| September | 51857908.47 | 0.62 | 20.01 | 01-SEP-00:10 | 0.62 |
| October | 53586505.42 | 0.62 | 20.01 | 01-OCT-00:10 | 0.62 |
| November | 51857908.47 | 0.62 | 20.01 | 01-NOV-00:10 | 0.62 |
| December | 53586505.42 | 0.62 | 20.01 | 01-DEC-00:10 | 0.62 |
| Annual Sum or Average | 0.630938E+09 | 0.62 | |||
| Minimum of Months | 48400714.57 | 0.62 | 20.01 | 0.62 | |
| Maximum of Months | 53586505.42 | 0.63 | 20.01 | 0.63 |
Report: FanReportMonthly
For: T N1 APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.63 | 20.01 | 01-JAN-00:10 | 0.62 |
| February | 48400714.57 | 0.63 | 20.01 | 01-FEB-00:10 | 0.63 |
| March | 53586505.42 | 0.63 | 20.01 | 01-MAR-00:10 | 0.63 |
| April | 51857908.47 | 0.63 | 20.01 | 01-APR-00:10 | 0.63 |
| May | 53586505.42 | 0.62 | 20.01 | 01-MAY-00:10 | 0.62 |
| June | 51857908.47 | 0.62 | 20.01 | 01-JUN-00:10 | 0.62 |
| July | 53586505.42 | 0.62 | 20.01 | 01-JUL-00:10 | 0.62 |
| August | 53586505.42 | 0.62 | 20.01 | 01-AUG-00:10 | 0.62 |
| September | 51857908.47 | 0.62 | 20.01 | 01-SEP-00:10 | 0.62 |
| October | 53586505.42 | 0.62 | 20.01 | 01-OCT-00:10 | 0.62 |
| November | 51857908.47 | 0.62 | 20.01 | 01-NOV-00:10 | 0.62 |
| December | 53586505.42 | 0.63 | 20.01 | 01-DEC-00:10 | 0.62 |
| Annual Sum or Average | 0.630938E+09 | 0.62 | |||
| Minimum of Months | 48400714.57 | 0.62 | 20.01 | 0.62 | |
| Maximum of Months | 53586505.42 | 0.63 | 20.01 | 0.63 |
Report: FanReportMonthly
For: SPLIT TN2 SUPPLY FAN
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 72175747.96 | 0.57 | 135.19 | 07-JAN-13:00 | 1.02 |
| February | 0.103787E+09 | 0.75 | 164.86 | 11-FEB-14:00 | 1.00 |
| March | 0.149269E+09 | 0.81 | 173.41 | 13-MAR-16:12 | 1.00 |
| April | 0.214447E+09 | 1.00 | 197.94 | 15-APR-16:15 | 0.99 |
| May | 0.322530E+09 | 1.02 | 236.69 | 29-MAY-16:04 | 0.98 |
| June | 0.360880E+09 | 1.01 | 225.35 | 08-JUN-16:02 | 0.98 |
| July | 0.379109E+09 | 1.01 | 240.16 | 27-JUL-16:10 | 0.98 |
| August | 0.364889E+09 | 1.01 | 223.83 | 22-AUG-13:00 | 0.98 |
| September | 0.337064E+09 | 1.02 | 220.75 | 18-SEP-16:10 | 0.98 |
| October | 0.287639E+09 | 1.03 | 209.35 | 03-OCT-15:10 | 0.99 |
| November | 0.189136E+09 | 0.91 | 174.22 | 04-NOV-16:10 | 1.00 |
| December | 0.103876E+09 | 0.65 | 156.76 | 10-DEC-14:00 | 1.01 |
| Annual Sum or Average | 0.288480E+10 | 0.90 | |||
| Minimum of Months | 72175747.96 | 0.57 | 135.19 | 0.98 | |
| Maximum of Months | 0.379109E+09 | 1.03 | 240.16 | 1.02 |
Report: FanReportMonthly
For: T N2 APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.63 | 20.01 | 01-JAN-00:10 | 0.62 |
| February | 48400714.57 | 0.63 | 20.01 | 01-FEB-00:10 | 0.63 |
| March | 53586505.42 | 0.62 | 20.01 | 01-MAR-00:10 | 0.63 |
| April | 51857908.47 | 0.62 | 20.01 | 01-APR-00:10 | 0.62 |
| May | 53586505.42 | 0.62 | 20.01 | 01-MAY-00:10 | 0.62 |
| June | 51857908.47 | 0.62 | 20.01 | 01-JUN-00:10 | 0.62 |
| July | 53586505.42 | 0.62 | 20.01 | 01-JUL-00:10 | 0.62 |
| August | 53586505.42 | 0.62 | 20.01 | 01-AUG-00:10 | 0.62 |
| September | 51857908.47 | 0.62 | 20.01 | 01-SEP-00:10 | 0.62 |
| October | 53586505.42 | 0.62 | 20.01 | 01-OCT-00:10 | 0.62 |
| November | 51857908.47 | 0.62 | 20.01 | 01-NOV-00:10 | 0.62 |
| December | 53586505.42 | 0.62 | 20.01 | 01-DEC-00:10 | 0.62 |
| Annual Sum or Average | 0.630938E+09 | 0.62 | |||
| Minimum of Months | 48400714.57 | 0.62 | 20.01 | 0.62 | |
| Maximum of Months | 53586505.42 | 0.63 | 20.01 | 0.63 |
Report: FanReportMonthly
For: T N2 APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.63 | 20.01 | 01-JAN-00:10 | 0.62 |
| February | 48400714.57 | 0.63 | 20.01 | 01-FEB-00:10 | 0.63 |
| March | 53586505.42 | 0.63 | 20.01 | 01-MAR-00:10 | 0.63 |
| April | 51857908.47 | 0.63 | 20.01 | 01-APR-00:10 | 0.63 |
| May | 53586505.42 | 0.62 | 20.01 | 01-MAY-00:10 | 0.62 |
| June | 51857908.47 | 0.62 | 20.01 | 01-JUN-00:10 | 0.62 |
| July | 53586505.42 | 0.62 | 20.01 | 01-JUL-00:10 | 0.62 |
| August | 53586505.42 | 0.62 | 20.01 | 01-AUG-00:10 | 0.62 |
| September | 51857908.47 | 0.62 | 20.01 | 01-SEP-00:10 | 0.62 |
| October | 53586505.42 | 0.62 | 20.01 | 01-OCT-00:10 | 0.62 |
| November | 51857908.47 | 0.62 | 20.01 | 01-NOV-00:10 | 0.62 |
| December | 53586505.42 | 0.63 | 20.01 | 01-DEC-00:10 | 0.62 |
| Annual Sum or Average | 0.630938E+09 | 0.62 | |||
| Minimum of Months | 48400714.57 | 0.62 | 20.01 | 0.62 | |
| Maximum of Months | 53586505.42 | 0.63 | 20.01 | 0.63 |
Report: FanReportMonthly
For: SPLIT TS1 SUPPLY FAN
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.134261E+09 | 0.72 | 233.31 | 02-JAN-14:40 | 0.98 |
| February | 0.154571E+09 | 0.80 | 236.53 | 11-FEB-14:30 | 0.98 |
| March | 0.185609E+09 | 0.86 | 204.88 | 04-MAR-14:00 | 0.99 |
| April | 0.235518E+09 | 1.00 | 215.46 | 15-APR-16:03 | 0.99 |
| May | 0.318609E+09 | 1.02 | 236.75 | 29-MAY-16:06 | 0.98 |
| June | 0.349206E+09 | 1.01 | 218.76 | 03-JUN-16:03 | 0.98 |
| July | 0.371493E+09 | 1.01 | 240.87 | 29-JUL-16:03 | 0.98 |
| August | 0.369754E+09 | 1.01 | 239.33 | 20-AUG-12:40 | 0.97 |
| September | 0.362731E+09 | 1.01 | 261.66 | 20-SEP-14:00 | 0.97 |
| October | 0.338105E+09 | 1.02 | 265.73 | 29-OCT-14:00 | 0.96 |
| November | 0.248144E+09 | 0.93 | 240.17 | 22-NOV-12:50 | 0.98 |
| December | 0.164064E+09 | 0.78 | 236.63 | 10-DEC-14:30 | 0.98 |
| Annual Sum or Average | 0.323207E+10 | 0.93 | |||
| Minimum of Months | 0.134261E+09 | 0.72 | 204.88 | 0.96 | |
| Maximum of Months | 0.371493E+09 | 1.02 | 265.73 | 0.99 |
Report: FanReportMonthly
For: T S1 APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.63 | 20.01 | 01-JAN-00:10 | 0.62 |
| February | 48400714.57 | 0.63 | 20.01 | 01-FEB-00:10 | 0.63 |
| March | 53586505.42 | 0.62 | 20.01 | 01-MAR-00:10 | 0.63 |
| April | 51857908.47 | 0.62 | 20.01 | 01-APR-00:10 | 0.62 |
| May | 53586505.42 | 0.62 | 20.01 | 01-MAY-00:10 | 0.62 |
| June | 51857908.47 | 0.62 | 20.01 | 01-JUN-00:10 | 0.62 |
| July | 53586505.42 | 0.62 | 20.01 | 01-JUL-00:10 | 0.62 |
| August | 53586505.42 | 0.62 | 20.01 | 01-AUG-00:10 | 0.62 |
| September | 51857908.47 | 0.62 | 20.01 | 01-SEP-00:10 | 0.62 |
| October | 53586505.42 | 0.62 | 20.01 | 01-OCT-00:10 | 0.62 |
| November | 51857908.47 | 0.62 | 20.01 | 01-NOV-00:10 | 0.62 |
| December | 53586505.42 | 0.62 | 20.01 | 01-DEC-00:10 | 0.62 |
| Annual Sum or Average | 0.630938E+09 | 0.62 | |||
| Minimum of Months | 48400714.57 | 0.62 | 20.01 | 0.62 | |
| Maximum of Months | 53586505.42 | 0.63 | 20.01 | 0.63 |
Report: FanReportMonthly
For: T S1 APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.63 | 20.01 | 01-JAN-00:10 | 0.62 |
| February | 48400714.57 | 0.63 | 20.01 | 01-FEB-00:10 | 0.63 |
| March | 53586505.42 | 0.63 | 20.01 | 01-MAR-00:10 | 0.63 |
| April | 51857908.47 | 0.63 | 20.01 | 01-APR-00:10 | 0.63 |
| May | 53586505.42 | 0.62 | 20.01 | 01-MAY-00:10 | 0.62 |
| June | 51857908.47 | 0.62 | 20.01 | 01-JUN-00:10 | 0.62 |
| July | 53586505.42 | 0.62 | 20.01 | 01-JUL-00:10 | 0.62 |
| August | 53586505.42 | 0.62 | 20.01 | 01-AUG-00:10 | 0.62 |
| September | 51857908.47 | 0.62 | 20.01 | 01-SEP-00:10 | 0.62 |
| October | 53586505.42 | 0.62 | 20.01 | 01-OCT-00:10 | 0.62 |
| November | 51857908.47 | 0.63 | 20.01 | 01-NOV-00:10 | 0.62 |
| December | 53586505.42 | 0.63 | 20.01 | 01-DEC-00:10 | 0.62 |
| Annual Sum or Average | 0.630938E+09 | 0.62 | |||
| Minimum of Months | 48400714.57 | 0.62 | 20.01 | 0.62 | |
| Maximum of Months | 53586505.42 | 0.63 | 20.01 | 0.63 |
Report: FanReportMonthly
For: SPLIT TS2 SUPPLY FAN
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.134458E+09 | 0.72 | 233.21 | 02-JAN-14:40 | 0.98 |
| February | 0.154555E+09 | 0.80 | 236.23 | 11-FEB-14:30 | 0.98 |
| March | 0.185530E+09 | 0.86 | 204.95 | 04-MAR-14:00 | 0.99 |
| April | 0.235285E+09 | 1.00 | 214.65 | 15-APR-16:03 | 0.99 |
| May | 0.318303E+09 | 1.02 | 235.82 | 29-MAY-16:10 | 0.98 |
| June | 0.349108E+09 | 1.01 | 218.17 | 03-JUN-16:03 | 0.98 |
| July | 0.371269E+09 | 1.01 | 240.14 | 29-JUL-16:03 | 0.98 |
| August | 0.369351E+09 | 1.01 | 239.64 | 20-AUG-12:40 | 0.97 |
| September | 0.362531E+09 | 1.01 | 261.47 | 20-SEP-14:00 | 0.97 |
| October | 0.337823E+09 | 1.02 | 265.41 | 29-OCT-14:00 | 0.96 |
| November | 0.247975E+09 | 0.93 | 240.57 | 22-NOV-12:50 | 0.97 |
| December | 0.163785E+09 | 0.78 | 236.26 | 10-DEC-14:30 | 0.98 |
| Annual Sum or Average | 0.322997E+10 | 0.93 | |||
| Minimum of Months | 0.134458E+09 | 0.72 | 204.95 | 0.96 | |
| Maximum of Months | 0.371269E+09 | 1.02 | 265.41 | 0.99 |
Report: FanReportMonthly
For: T S2 APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.63 | 20.01 | 01-JAN-00:10 | 0.62 |
| February | 48400714.57 | 0.63 | 20.01 | 01-FEB-00:10 | 0.63 |
| March | 53586505.42 | 0.62 | 20.01 | 01-MAR-00:10 | 0.63 |
| April | 51857908.47 | 0.62 | 20.01 | 01-APR-00:10 | 0.62 |
| May | 53586505.42 | 0.62 | 20.01 | 01-MAY-00:10 | 0.62 |
| June | 51857908.47 | 0.62 | 20.01 | 01-JUN-00:10 | 0.62 |
| July | 53586505.42 | 0.62 | 20.01 | 01-JUL-00:10 | 0.62 |
| August | 53586505.42 | 0.62 | 20.01 | 01-AUG-00:10 | 0.62 |
| September | 51857908.47 | 0.62 | 20.01 | 01-SEP-00:10 | 0.62 |
| October | 53586505.42 | 0.62 | 20.01 | 01-OCT-00:10 | 0.62 |
| November | 51857908.47 | 0.62 | 20.01 | 01-NOV-00:10 | 0.62 |
| December | 53586505.42 | 0.62 | 20.01 | 01-DEC-00:10 | 0.62 |
| Annual Sum or Average | 0.630938E+09 | 0.62 | |||
| Minimum of Months | 48400714.57 | 0.62 | 20.01 | 0.62 | |
| Maximum of Months | 53586505.42 | 0.63 | 20.01 | 0.63 |
Report: FanReportMonthly
For: T S2 APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.63 | 20.01 | 01-JAN-00:10 | 0.62 |
| February | 48400714.57 | 0.63 | 20.01 | 01-FEB-00:10 | 0.63 |
| March | 53586505.42 | 0.63 | 20.01 | 01-MAR-00:10 | 0.63 |
| April | 51857908.47 | 0.63 | 20.01 | 01-APR-00:10 | 0.63 |
| May | 53586505.42 | 0.62 | 20.01 | 01-MAY-00:10 | 0.62 |
| June | 51857908.47 | 0.62 | 20.01 | 01-JUN-00:10 | 0.62 |
| July | 53586505.42 | 0.62 | 20.01 | 01-JUL-00:10 | 0.62 |
| August | 53586505.42 | 0.62 | 20.01 | 01-AUG-00:10 | 0.62 |
| September | 51857908.47 | 0.62 | 20.01 | 01-SEP-00:10 | 0.62 |
| October | 53586505.42 | 0.62 | 20.01 | 01-OCT-00:10 | 0.62 |
| November | 51857908.47 | 0.63 | 20.01 | 01-NOV-00:10 | 0.62 |
| December | 53586505.42 | 0.63 | 20.01 | 01-DEC-00:10 | 0.62 |
| Annual Sum or Average | 0.630938E+09 | 0.62 | |||
| Minimum of Months | 48400714.57 | 0.62 | 20.01 | 0.62 | |
| Maximum of Months | 53586505.42 | 0.63 | 20.01 | 0.63 |
Report: ZoneTemperatureOscillationReportMonthly
For: G SW APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: G NW APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: OFFICE
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: G NE APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: G N1 APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: G N2 APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: G S1 APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: G S2 APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: M SW APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: M NW APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: M SE APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: M NE APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: M N1 APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: M N2 APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: M S1 APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: M S2 APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: T SW APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: T NW APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: T SE APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: T NE APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: T N1 APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: T N2 APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: T S1 APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: T S2 APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: T CORRIDOR
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: G CORRIDOR
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: M CORRIDOR
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT GSW
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.760201E+09 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.778086E+09 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.885973E+09 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.112045E+10 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.153611E+10 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.169819E+10 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.189036E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.194638E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.190459E+10 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.180995E+10 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.134537E+10 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.926484E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.166021E+11 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.760201E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.194638E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT GNW
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.453345E+09 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.537858E+09 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.708524E+09 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.102620E+10 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.154623E+10 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.174234E+10 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.191732E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.192070E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.178794E+10 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.158554E+10 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.108299E+10 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.627229E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.149362E+11 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.453345E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.192070E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT OFFICE
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.156110E+10 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.146758E+10 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.164321E+10 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.165931E+10 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.191221E+10 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.199215E+10 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.208260E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.217527E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.206003E+10 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.205196E+10 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.177905E+10 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.158449E+10 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.219690E+11 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.146758E+10 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.217527E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT GNE
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.466687E+09 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.538227E+09 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.699236E+09 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.102086E+10 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.154165E+10 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.176366E+10 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.192547E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.191102E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.179907E+10 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.158762E+10 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.108365E+10 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.604838E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.149420E+11 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.466687E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.192547E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT GN1
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.441017E+09 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.496373E+09 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.628578E+09 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.888056E+09 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.132319E+10 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.150987E+10 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.163996E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.163261E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.152525E+10 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.136212E+10 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.960744E+09 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.578239E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.129860E+11 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.441017E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.163996E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT GN2
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.442195E+09 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.496758E+09 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.628902E+09 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.887909E+09 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.132313E+10 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.151101E+10 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.164048E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.163244E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.152593E+10 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.136238E+10 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.960988E+09 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.577355E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.129895E+11 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.442195E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.164048E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT GS1
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.772594E+09 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.753594E+09 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.820815E+09 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.989331E+09 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.131865E+10 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.147065E+10 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.161851E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.166493E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.165021E+10 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.159688E+10 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.123432E+10 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.896905E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.147874E+11 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.753594E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.166493E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT GS2
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.842685E+09 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.809606E+09 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.884206E+09 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.106963E+10 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.141687E+10 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.157801E+10 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.173656E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.177792E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.176350E+10 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.170954E+10 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.132292E+10 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.966187E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.158776E+11 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.809606E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.177792E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT MSW
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.154621E+10 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.168772E+10 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.206810E+10 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.258769E+10 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.344494E+10 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.372633E+10 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.398032E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.401186E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.386589E+10 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.363798E+10 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.268156E+10 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.183208E+10 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.350707E+11 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.154621E+10 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.401186E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT MNW
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.901469E+09 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.118130E+10 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.169395E+10 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.238603E+10 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.345976E+10 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.381048E+10 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.402643E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.394618E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.360496E+10 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.314879E+10 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.211623E+10 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.120415E+10 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.314797E+11 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.901469E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.402643E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT MSE
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.157704E+10 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.168559E+10 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.205009E+10 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.257246E+10 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.343212E+10 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.376829E+10 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.399721E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.398787E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.388596E+10 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.363648E+10 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.267828E+10 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.178272E+10 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.350541E+11 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.157704E+10 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.399721E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT MNE
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.925763E+09 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.117968E+10 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.166981E+10 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.237043E+10 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.344470E+10 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.384932E+10 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.404099E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.392126E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.362737E+10 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.315163E+10 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.211509E+10 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.115431E+10 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.314504E+11 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.925763E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.404099E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT MN1
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.896669E+09 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.107582E+10 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.145546E+10 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.199121E+10 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.286626E+10 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.320411E+10 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.336602E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.329420E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.303666E+10 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.268500E+10 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.188314E+10 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.112732E+10 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.268819E+11 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.896669E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.336602E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT MN2
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.899150E+09 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.107665E+10 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.145632E+10 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.199092E+10 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.286611E+10 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.320605E+10 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.336701E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.329383E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.303795E+10 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.268546E+10 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.188379E+10 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.112554E+10 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.268888E+11 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.899150E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.336701E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT MS1
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.158106E+10 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.160741E+10 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.184544E+10 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.219503E+10 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.285114E+10 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.311846E+10 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.331857E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.336006E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.329913E+10 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.317633E+10 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.245499E+10 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.179381E+10 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.306014E+11 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.158106E+10 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.336006E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT MS2
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.158268E+10 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.160797E+10 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.184608E+10 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.219470E+10 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.285098E+10 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.312044E+10 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.331956E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.335964E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.330024E+10 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.317655E+10 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.245527E+10 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.179228E+10 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.306064E+11 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.158268E+10 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.335964E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT TSW
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.665689E+09 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.812849E+09 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.103275E+10 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.136019E+10 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.191314E+10 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.209899E+10 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.224969E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.223475E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.214399E+10 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.193529E+10 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.135504E+10 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.850824E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.186532E+11 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.665689E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.224969E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT TNW
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.378932E+09 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.568001E+09 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.855505E+09 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.125365E+10 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.192476E+10 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.214677E+10 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.227724E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.220147E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.200621E+10 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.167846E+10 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.106743E+10 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.568047E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.169265E+11 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.378932E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.227724E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT TSE
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.674612E+09 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.805775E+09 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.101156E+10 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.134711E+10 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.190035E+10 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.211322E+10 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.225138E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.221374E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.214742E+10 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.192925E+10 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.134798E+10 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.820397E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.185628E+11 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.674612E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.225138E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT TNE
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.384403E+09 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.559647E+09 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.833213E+09 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.124142E+10 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.191139E+10 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.215977E+10 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.227832E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.218097E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.201258E+10 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.167685E+10 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.106109E+10 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.541085E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.168407E+11 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.384403E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.227832E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT TN1
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.343238E+09 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.491236E+09 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.717589E+09 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.104635E+10 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.160075E+10 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.181118E+10 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.191526E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.184226E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.169286E+10 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.142770E+10 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.926864E+09 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.496892E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.143122E+11 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.343238E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.191526E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT TN2
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.344117E+09 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.491348E+09 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.716829E+09 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.104523E+10 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.159927E+10 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.181079E+10 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.191438E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.184055E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.169228E+10 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.142679E+10 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.926386E+09 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.495537E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.143035E+11 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.344117E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.191438E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT TS1
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.647402E+09 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.743258E+09 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.897966E+09 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.115406E+10 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.158901E+10 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.176269E+10 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.188713E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.187568E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.183129E+10 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.168572E+10 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.122029E+10 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.793469E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.160880E+11 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.647402E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.188713E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT TS2
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.648802E+09 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.743694E+09 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.898228E+09 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.115378E+10 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.158867E+10 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.176347E+10 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.188739E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.187503E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.183160E+10 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.168556E+10 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.122033E+10 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.792674E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.160892E+11 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.648802E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.188739E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT GSW
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 0.157513E+09 | 0.243647E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.160814E+09 | 0.249525E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.182600E+09 | 0.286255E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.228698E+09 | 0.357557E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.307964E+09 | 0.489736E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.336167E+09 | 0.539080E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.372335E+09 | 0.594950E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.383960E+09 | 0.617017E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.377708E+09 | 0.605740E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.363619E+09 | 0.580316E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.273909E+09 | 0.435194E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.191182E+09 | 0.300292E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.333647E+10 | 0.529931E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 0.157513E+09 | 0.243647E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.383960E+09 | 0.617017E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT GNW
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 93990015.67 | 0.145351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.111417E+09 | 0.172075E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.146425E+09 | 0.228660E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.210326E+09 | 0.326584E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.311432E+09 | 0.492378E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.346562E+09 | 0.552625E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.379462E+09 | 0.602802E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.380602E+09 | 0.607820E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.356102E+09 | 0.566893E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.319746E+09 | 0.506204E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.221092E+09 | 0.348945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.129638E+09 | 0.203057E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.300679E+10 | 0.475339E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 93990015.67 | 0.145351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.380602E+09 | 0.607820E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT OFFICE
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 0.112019E+10 | 0.182697E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.101178E+10 | 0.188825E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.112019E+10 | 0.218151E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.108405E+10 | 0.237050E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.112019E+10 | 0.323944E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.108405E+10 | 0.375500E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.112019E+10 | 0.391253E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.112019E+10 | 0.433019E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.108405E+10 | 0.403738E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.112019E+10 | 0.387776E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.108405E+10 | 0.292655E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.112019E+10 | 0.193211E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.131893E+11 | 0.362782E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 0.101178E+10 | 0.182697E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.112019E+10 | 0.433019E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT GNE
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 95397017.89 | 0.150392E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.109942E+09 | 0.173015E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.142465E+09 | 0.226848E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.206301E+09 | 0.326482E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.306126E+09 | 0.493715E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.345963E+09 | 0.563139E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.375735E+09 | 0.609263E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.373326E+09 | 0.608479E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.353375E+09 | 0.574241E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.315663E+09 | 0.509871E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.218165E+09 | 0.351159E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.123222E+09 | 0.196832E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.296568E+10 | 0.478344E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 95397017.89 | 0.150392E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.375735E+09 | 0.609263E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT GN1
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 90408733.74 | 0.141941E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.101665E+09 | 0.159473E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.128420E+09 | 0.203617E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.179987E+09 | 0.283739E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.263535E+09 | 0.423030E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.296855E+09 | 0.481211E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.320740E+09 | 0.518313E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.319718E+09 | 0.518998E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.300285E+09 | 0.485976E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.271512E+09 | 0.436964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.193950E+09 | 0.310880E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.118174E+09 | 0.187867E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.258525E+10 | 0.415201E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 90408733.74 | 0.141941E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.320740E+09 | 0.518998E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT GN2
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 90623244.61 | 0.142334E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.101712E+09 | 0.159611E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.128447E+09 | 0.203740E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.179900E+09 | 0.283719E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.263439E+09 | 0.423059E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.296990E+09 | 0.481649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.320741E+09 | 0.518549E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.319584E+09 | 0.519012E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.300326E+09 | 0.486262E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.271477E+09 | 0.437100E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.193940E+09 | 0.310995E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.117955E+09 | 0.187599E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.258513E+10 | 0.415363E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 90623244.61 | 0.142334E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.320741E+09 | 0.519012E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT GS1
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 0.157879E+09 | 0.248744E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.153617E+09 | 0.242680E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.166827E+09 | 0.266150E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.199125E+09 | 0.317139E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.260681E+09 | 0.422277E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.286949E+09 | 0.469307E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.314141E+09 | 0.512283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.323675E+09 | 0.530418E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.322593E+09 | 0.527690E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.316240E+09 | 0.514844E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.247843E+09 | 0.401332E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.182527E+09 | 0.291929E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.293210E+10 | 0.474479E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 0.153617E+09 | 0.242680E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.323675E+09 | 0.530418E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT GS2
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 0.172465E+09 | 0.271533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.165288E+09 | 0.260912E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.179997E+09 | 0.286853E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.215686E+09 | 0.343277E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.280647E+09 | 0.454284E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.308537E+09 | 0.504155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.337828E+09 | 0.550511E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.346387E+09 | 0.567200E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.345498E+09 | 0.564876E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.339224E+09 | 0.552102E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.266131E+09 | 0.430588E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.196935E+09 | 0.314680E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.315462E+10 | 0.510097E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 0.165288E+09 | 0.260912E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.346387E+09 | 0.567200E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT MSW
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 0.321557E+09 | 0.494630E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.350074E+09 | 0.541011E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.428023E+09 | 0.668288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.530384E+09 | 0.825459E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.693243E+09 | 0.109726E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.740338E+09 | 0.118040E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.786354E+09 | 0.124758E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.793473E+09 | 0.126663E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.768343E+09 | 0.122345E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.732588E+09 | 0.116087E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.547349E+09 | 0.864685E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.379243E+09 | 0.593033E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.707097E+10 | 0.111633E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 0.321557E+09 | 0.494630E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.793473E+09 | 0.126663E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT MNW
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 0.187393E+09 | 0.288746E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.245668E+09 | 0.377598E+10 | 5746062.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.351342E+09 | 0.546789E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.490788E+09 | 0.759139E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.698949E+09 | 0.110067E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.760122E+09 | 0.120599E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.798694E+09 | 0.126069E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.783446E+09 | 0.124388E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.719108E+09 | 0.113784E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.636136E+09 | 0.100129E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.432785E+09 | 0.680300E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.249420E+09 | 0.389676E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.635385E+10 | 0.999261E+11 | 5746062.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 0.187393E+09 | 0.288746E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.798694E+09 | 0.126069E+11 | 5746062.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT MSE
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 0.322726E+09 | 0.507651E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.344065E+09 | 0.543678E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.417503E+09 | 0.666389E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.518785E+09 | 0.825554E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.679448E+09 | 0.110042E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.736760E+09 | 0.120267E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.776934E+09 | 0.126185E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.775865E+09 | 0.126779E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.760081E+09 | 0.123933E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.720476E+09 | 0.116870E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.538001E+09 | 0.869749E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.363033E+09 | 0.580494E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.695368E+10 | 0.112343E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 0.322726E+09 | 0.507651E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.776934E+09 | 0.126779E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT MNE
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 0.189506E+09 | 0.298176E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.241626E+09 | 0.379096E+10 | 5366617.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.341054E+09 | 0.542164E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.480172E+09 | 0.758425E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.685248E+09 | 0.110296E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.756359E+09 | 0.122737E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.789364E+09 | 0.127416E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.766505E+09 | 0.124428E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.712744E+09 | 0.115320E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.626971E+09 | 0.100858E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.426066E+09 | 0.684266E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.235382E+09 | 0.375743E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.625100E+10 | 0.100484E+12 | 5366617.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 0.189506E+09 | 0.298176E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.789364E+09 | 0.127416E+11 | 5366617.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT MN1
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 0.184895E+09 | 0.288000E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.221680E+09 | 0.345135E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.299290E+09 | 0.470946E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.406171E+09 | 0.635198E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.574294E+09 | 0.914220E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.633664E+09 | 0.101757E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.661878E+09 | 0.105834E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.648417E+09 | 0.104199E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.600772E+09 | 0.962371E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.537938E+09 | 0.857230E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.382087E+09 | 0.607417E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.231642E+09 | 0.365767E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.538273E+10 | 0.856418E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 0.184895E+09 | 0.288000E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.661878E+09 | 0.105834E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT MN2
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 0.185350E+09 | 0.288817E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.221781E+09 | 0.345433E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.299373E+09 | 0.471263E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.405976E+09 | 0.635171E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.574069E+09 | 0.914277E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.633846E+09 | 0.101834E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.661854E+09 | 0.105879E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.648127E+09 | 0.104200E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.600835E+09 | 0.962919E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.537852E+09 | 0.857482E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.382098E+09 | 0.607698E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.231198E+09 | 0.365230E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.538236E+10 | 0.856743E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 0.185350E+09 | 0.288817E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.661854E+09 | 0.105879E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT MS1
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 0.325426E+09 | 0.507582E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.329969E+09 | 0.516884E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.377901E+09 | 0.597662E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.445097E+09 | 0.702358E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.567687E+09 | 0.910908E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.612771E+09 | 0.991695E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.648346E+09 | 0.104499E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.657307E+09 | 0.106498E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.648745E+09 | 0.104877E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.632815E+09 | 0.101819E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.496030E+09 | 0.794921E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.367548E+09 | 0.582361E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.610964E+10 | 0.978130E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 0.325426E+09 | 0.507582E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.657307E+09 | 0.106498E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT MS2
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 0.325648E+09 | 0.508180E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.329972E+09 | 0.517135E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.377902E+09 | 0.597930E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.444870E+09 | 0.702339E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.567446E+09 | 0.910969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.612946E+09 | 0.992481E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.648305E+09 | 0.104545E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.656986E+09 | 0.106499E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.648737E+09 | 0.104930E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.632631E+09 | 0.101841E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.495914E+09 | 0.795131E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.367103E+09 | 0.581936E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.610846E+10 | 0.978425E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 0.325648E+09 | 0.508180E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.656986E+09 | 0.106499E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT TSW
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 0.139014E+09 | 0.213127E+10 | 22188977.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.170914E+09 | 0.259960E+10 | 68295155.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.215152E+09 | 0.333712E+10 | 45382420.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.278163E+09 | 0.434081E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.384292E+09 | 0.609319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.416716E+09 | 0.664999E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.443839E+09 | 0.704621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.441435E+09 | 0.705599E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.425407E+09 | 0.678332E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.388884E+09 | 0.617146E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.276457E+09 | 0.437008E+10 | 12667171.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.177893E+09 | 0.275504E+10 | 56232346.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.375817E+10 | 0.593341E+11 | 0.204766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 0.139014E+09 | 0.213127E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.443839E+09 | 0.705599E+10 | 68295155.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT TNW
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 80989477.86 | 0.120449E+10 | 62726023.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.121774E+09 | 0.179903E+10 | 0.102960E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.179913E+09 | 0.275224E+10 | 68632953.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.257492E+09 | 0.398480E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.388490E+09 | 0.611829E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.428312E+09 | 0.679097E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.451502E+09 | 0.711956E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.436901E+09 | 0.693289E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.399870E+09 | 0.632140E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.338661E+09 | 0.532488E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.218806E+09 | 0.342357E+10 | 22458596.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.121321E+09 | 0.182309E+10 | 0.101188E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.342403E+10 | 0.535952E+11 | 0.357966E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 80989477.86 | 0.120449E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.451502E+09 | 0.711956E+10 | 0.102960E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT TSE
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 0.138085E+09 | 0.217888E+10 | 20379345.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.166142E+09 | 0.259871E+10 | 65899668.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.206358E+09 | 0.329686E+10 | 36360774.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.270143E+09 | 0.433442E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.374267E+09 | 0.610743E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.411493E+09 | 0.676334E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.435547E+09 | 0.712170E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.428706E+09 | 0.705682E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.417953E+09 | 0.686634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.380144E+09 | 0.621222E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.269725E+09 | 0.438950E+10 | 11469334.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.168251E+09 | 0.267833E+10 | 55653145.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.366681E+10 | 0.596046E+11 | 0.189762E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 0.138085E+09 | 0.217888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.435547E+09 | 0.712170E+10 | 65899668.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT TNE
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 80375217.32 | 0.123216E+10 | 55779400.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.117660E+09 | 0.178563E+10 | 96465935.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.171540E+09 | 0.270337E+10 | 53758666.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.250304E+09 | 0.397530E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.378691E+09 | 0.612887E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.423128E+09 | 0.690022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.443451E+09 | 0.719155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.424819E+09 | 0.693070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.393917E+09 | 0.640291E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.332109E+09 | 0.536427E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.213462E+09 | 0.343222E+10 | 19076815.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.113486E+09 | 0.174930E+10 | 97035558.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.334294E+10 | 0.537965E+11 | 0.322116E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 80375217.32 | 0.123216E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.443451E+09 | 0.719155E+10 | 97035558.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT TN1
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 72040959.00 | 0.109920E+10 | 23422848.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.103831E+09 | 0.156435E+10 | 51784445.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.149535E+09 | 0.231457E+10 | 24576133.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.214832E+09 | 0.332516E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.323064E+09 | 0.508726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.361210E+09 | 0.573391E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.379561E+09 | 0.599733E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.365494E+09 | 0.580524E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.337418E+09 | 0.534116E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.288028E+09 | 0.453475E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.189364E+09 | 0.297872E+10 | 3640578.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.104217E+09 | 0.160488E+10 | 39517613.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.288860E+10 | 0.453865E+11 | 0.142942E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 72040959.00 | 0.109920E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.379561E+09 | 0.599733E+10 | 51784445.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT TN2
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 72175747.96 | 0.110230E+10 | 23436571.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.103787E+09 | 0.156509E+10 | 51865598.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.149269E+09 | 0.231284E+10 | 24425531.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.214447E+09 | 0.332267E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.322530E+09 | 0.508442E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.360880E+09 | 0.573516E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.379109E+09 | 0.599704E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.364889E+09 | 0.580212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.337064E+09 | 0.534156E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.287639E+09 | 0.453352E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.189136E+09 | 0.297823E+10 | 3600784.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.103876E+09 | 0.160094E+10 | 39835233.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.288480E+10 | 0.453759E+11 | 0.143164E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 72175747.96 | 0.110230E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.379109E+09 | 0.599704E+10 | 51865598.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT TS1
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 0.134261E+09 | 0.208095E+10 | 4307304.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.154571E+09 | 0.238742E+10 | 26082351.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.185609E+09 | 0.290731E+10 | 12347505.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.235518E+09 | 0.368440E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.318609E+09 | 0.506213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.349206E+09 | 0.559140E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.371493E+09 | 0.592268E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.369754E+09 | 0.592892E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.362731E+09 | 0.580553E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.338105E+09 | 0.538657E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.248144E+09 | 0.394542E+10 | 546514.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.164064E+09 | 0.258019E+10 | 12071330.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.323207E+10 | 0.512829E+11 | 55355007.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 0.134261E+09 | 0.208095E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.371493E+09 | 0.592892E+10 | 26082351.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT TS2
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 0.134458E+09 | 0.208613E+10 | 4336491.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.154555E+09 | 0.238960E+10 | 26181656.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.185530E+09 | 0.290898E+10 | 12303776.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.235285E+09 | 0.368461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.318303E+09 | 0.506266E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.349108E+09 | 0.559590E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.371269E+09 | 0.592557E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.369351E+09 | 0.592890E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.362531E+09 | 0.580875E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.337823E+09 | 0.538801E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.247975E+09 | 0.394698E+10 | 535403.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.163785E+09 | 0.257837E+10 | 12177486.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.322997E+10 | 0.513045E+11 | 55534815.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 0.134458E+09 | 0.208613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.371269E+09 | 0.592890E+10 | 26181656.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT GSW
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 0.157513E+09 | 0.00 | 0.00 | 0.00 | 0.602689E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.160814E+09 | 0.00 | 0.00 | 0.00 | 0.617272E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.182600E+09 | 0.00 | 0.00 | 0.00 | 0.703373E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.228698E+09 | 0.00 | 0.00 | 0.00 | 0.891752E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.307964E+09 | 0.00 | 0.00 | 0.00 | 0.122815E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.336167E+09 | 0.00 | 0.00 | 0.00 | 0.136203E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.372335E+09 | 0.00 | 0.00 | 0.00 | 0.151803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.383960E+09 | 0.00 | 0.00 | 0.00 | 0.156242E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.377708E+09 | 0.00 | 0.00 | 0.00 | 0.152688E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.363619E+09 | 0.00 | 0.00 | 0.00 | 0.144633E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.273909E+09 | 0.00 | 0.00 | 0.00 | 0.107147E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.191182E+09 | 0.00 | 0.00 | 0.00 | 0.735302E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.333647E+10 | 0.00 | 0.00 | 0.00 | 0.132657E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 0.157513E+09 | 0.00 | 0.00 | 0.00 | 0.602689E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.383960E+09 | 0.00 | 0.00 | 0.00 | 0.156242E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT GNW
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 93990015.67 | 0.00 | 0.00 | 0.00 | 0.359355E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.111417E+09 | 0.00 | 0.00 | 0.00 | 0.426441E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.146425E+09 | 0.00 | 0.00 | 0.00 | 0.562099E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.210326E+09 | 0.00 | 0.00 | 0.00 | 0.815876E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.311432E+09 | 0.00 | 0.00 | 0.00 | 0.123480E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.346562E+09 | 0.00 | 0.00 | 0.00 | 0.139578E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.379462E+09 | 0.00 | 0.00 | 0.00 | 0.153786E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.380602E+09 | 0.00 | 0.00 | 0.00 | 0.154010E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.356102E+09 | 0.00 | 0.00 | 0.00 | 0.143184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.319746E+09 | 0.00 | 0.00 | 0.00 | 0.126580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.221092E+09 | 0.00 | 0.00 | 0.00 | 0.861900E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.129638E+09 | 0.00 | 0.00 | 0.00 | 0.497591E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.300679E+10 | 0.00 | 0.00 | 0.00 | 0.119294E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 93990015.67 | 0.00 | 0.00 | 0.00 | 0.359355E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.380602E+09 | 0.00 | 0.00 | 0.00 | 0.154010E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT OFFICE
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 0.112019E+10 | 0.00 | 0.00 | 0.00 | 0.440915E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.101178E+10 | 0.00 | 0.00 | 0.00 | 0.455794E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.112019E+10 | 0.00 | 0.00 | 0.00 | 0.523024E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.108405E+10 | 0.00 | 0.00 | 0.00 | 0.575261E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.112019E+10 | 0.00 | 0.00 | 0.00 | 0.792026E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.108405E+10 | 0.00 | 0.00 | 0.00 | 0.908101E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.112019E+10 | 0.00 | 0.00 | 0.00 | 0.962411E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.112019E+10 | 0.00 | 0.00 | 0.00 | 0.105508E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.108405E+10 | 0.00 | 0.00 | 0.00 | 0.975978E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.112019E+10 | 0.00 | 0.00 | 0.00 | 0.931776E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.108405E+10 | 0.00 | 0.00 | 0.00 | 0.695001E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.112019E+10 | 0.00 | 0.00 | 0.00 | 0.464308E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.131893E+11 | 0.00 | 0.00 | 0.00 | 0.877968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 0.101178E+10 | 0.00 | 0.00 | 0.00 | 0.440915E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.112019E+10 | 0.00 | 0.00 | 0.00 | 0.105508E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT GNE
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 95397017.89 | 0.00 | 0.00 | 0.00 | 0.371290E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.109942E+09 | 0.00 | 0.00 | 0.00 | 0.428285E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.142465E+09 | 0.00 | 0.00 | 0.00 | 0.556771E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.206301E+09 | 0.00 | 0.00 | 0.00 | 0.814554E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.306126E+09 | 0.00 | 0.00 | 0.00 | 0.123552E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.345963E+09 | 0.00 | 0.00 | 0.00 | 0.141770E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.375735E+09 | 0.00 | 0.00 | 0.00 | 0.154973E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.373326E+09 | 0.00 | 0.00 | 0.00 | 0.153769E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.353375E+09 | 0.00 | 0.00 | 0.00 | 0.144569E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.315663E+09 | 0.00 | 0.00 | 0.00 | 0.127196E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.218165E+09 | 0.00 | 0.00 | 0.00 | 0.865485E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.123222E+09 | 0.00 | 0.00 | 0.00 | 0.481615E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.296568E+10 | 0.00 | 0.00 | 0.00 | 0.119763E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 95397017.89 | 0.00 | 0.00 | 0.00 | 0.371290E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.375735E+09 | 0.00 | 0.00 | 0.00 | 0.154973E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT GN1
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 90408733.74 | 0.00 | 0.00 | 0.00 | 0.350609E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.101665E+09 | 0.00 | 0.00 | 0.00 | 0.394709E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.128420E+09 | 0.00 | 0.00 | 0.00 | 0.500157E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.179987E+09 | 0.00 | 0.00 | 0.00 | 0.708069E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.263535E+09 | 0.00 | 0.00 | 0.00 | 0.105966E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.296855E+09 | 0.00 | 0.00 | 0.00 | 0.121301E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.320740E+09 | 0.00 | 0.00 | 0.00 | 0.131922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.319718E+09 | 0.00 | 0.00 | 0.00 | 0.131289E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.300285E+09 | 0.00 | 0.00 | 0.00 | 0.122497E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.271512E+09 | 0.00 | 0.00 | 0.00 | 0.109061E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.193950E+09 | 0.00 | 0.00 | 0.00 | 0.766795E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.118174E+09 | 0.00 | 0.00 | 0.00 | 0.460065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.258525E+10 | 0.00 | 0.00 | 0.00 | 0.104008E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 90408733.74 | 0.00 | 0.00 | 0.00 | 0.350609E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.320740E+09 | 0.00 | 0.00 | 0.00 | 0.131922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT GN2
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 90623244.61 | 0.00 | 0.00 | 0.00 | 0.351572E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.101712E+09 | 0.00 | 0.00 | 0.00 | 0.395046E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.128447E+09 | 0.00 | 0.00 | 0.00 | 0.500455E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.179900E+09 | 0.00 | 0.00 | 0.00 | 0.708009E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.263439E+09 | 0.00 | 0.00 | 0.00 | 0.105969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.296990E+09 | 0.00 | 0.00 | 0.00 | 0.121402E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.320741E+09 | 0.00 | 0.00 | 0.00 | 0.131974E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.319584E+09 | 0.00 | 0.00 | 0.00 | 0.131286E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.300326E+09 | 0.00 | 0.00 | 0.00 | 0.122560E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.271477E+09 | 0.00 | 0.00 | 0.00 | 0.109090E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.193940E+09 | 0.00 | 0.00 | 0.00 | 0.767048E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.117955E+09 | 0.00 | 0.00 | 0.00 | 0.459399E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.258513E+10 | 0.00 | 0.00 | 0.00 | 0.104043E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 90623244.61 | 0.00 | 0.00 | 0.00 | 0.351572E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.320741E+09 | 0.00 | 0.00 | 0.00 | 0.131974E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT GS1
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 0.157879E+09 | 0.00 | 0.00 | 0.00 | 0.614715E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.153617E+09 | 0.00 | 0.00 | 0.00 | 0.599977E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.166827E+09 | 0.00 | 0.00 | 0.00 | 0.653989E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.199125E+09 | 0.00 | 0.00 | 0.00 | 0.790206E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.260681E+09 | 0.00 | 0.00 | 0.00 | 0.105797E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.286949E+09 | 0.00 | 0.00 | 0.00 | 0.118371E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.314141E+09 | 0.00 | 0.00 | 0.00 | 0.130437E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.323675E+09 | 0.00 | 0.00 | 0.00 | 0.134125E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.322593E+09 | 0.00 | 0.00 | 0.00 | 0.132762E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.316240E+09 | 0.00 | 0.00 | 0.00 | 0.128064E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.247843E+09 | 0.00 | 0.00 | 0.00 | 0.986479E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.182527E+09 | 0.00 | 0.00 | 0.00 | 0.714379E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.293210E+10 | 0.00 | 0.00 | 0.00 | 0.118553E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 0.153617E+09 | 0.00 | 0.00 | 0.00 | 0.599977E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.323675E+09 | 0.00 | 0.00 | 0.00 | 0.134125E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT GS2
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 0.172465E+09 | 0.00 | 0.00 | 0.00 | 0.670220E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.165288E+09 | 0.00 | 0.00 | 0.00 | 0.644318E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.179997E+09 | 0.00 | 0.00 | 0.00 | 0.704209E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.215686E+09 | 0.00 | 0.00 | 0.00 | 0.853942E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.280647E+09 | 0.00 | 0.00 | 0.00 | 0.113622E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.308537E+09 | 0.00 | 0.00 | 0.00 | 0.126947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.337828E+09 | 0.00 | 0.00 | 0.00 | 0.139873E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.346387E+09 | 0.00 | 0.00 | 0.00 | 0.143154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.345498E+09 | 0.00 | 0.00 | 0.00 | 0.141801E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.339224E+09 | 0.00 | 0.00 | 0.00 | 0.137032E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.266131E+09 | 0.00 | 0.00 | 0.00 | 0.105679E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.196935E+09 | 0.00 | 0.00 | 0.00 | 0.769252E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.315462E+10 | 0.00 | 0.00 | 0.00 | 0.127230E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 0.165288E+09 | 0.00 | 0.00 | 0.00 | 0.644318E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.346387E+09 | 0.00 | 0.00 | 0.00 | 0.143154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT MSW
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 0.321557E+09 | 0.00 | 0.00 | 0.00 | 0.122466E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.350074E+09 | 0.00 | 0.00 | 0.00 | 0.133764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.428023E+09 | 0.00 | 0.00 | 0.00 | 0.164007E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.530384E+09 | 0.00 | 0.00 | 0.00 | 0.205730E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.693243E+09 | 0.00 | 0.00 | 0.00 | 0.275170E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.740338E+09 | 0.00 | 0.00 | 0.00 | 0.298599E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.786354E+09 | 0.00 | 0.00 | 0.00 | 0.319397E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.793473E+09 | 0.00 | 0.00 | 0.00 | 0.321839E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.768343E+09 | 0.00 | 0.00 | 0.00 | 0.309755E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.732588E+09 | 0.00 | 0.00 | 0.00 | 0.290539E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.547349E+09 | 0.00 | 0.00 | 0.00 | 0.213421E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.379243E+09 | 0.00 | 0.00 | 0.00 | 0.145284E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.707097E+10 | 0.00 | 0.00 | 0.00 | 0.279997E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 0.321557E+09 | 0.00 | 0.00 | 0.00 | 0.122466E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.793473E+09 | 0.00 | 0.00 | 0.00 | 0.321839E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT MNW
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 0.187393E+09 | 0.00 | 0.00 | 0.00 | 0.714076E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.245668E+09 | 0.00 | 0.00 | 0.00 | 0.935628E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.351342E+09 | 0.00 | 0.00 | 0.00 | 0.134261E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.490788E+09 | 0.00 | 0.00 | 0.00 | 0.189524E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.698949E+09 | 0.00 | 0.00 | 0.00 | 0.276081E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.760122E+09 | 0.00 | 0.00 | 0.00 | 0.305036E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.798694E+09 | 0.00 | 0.00 | 0.00 | 0.322774E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.783446E+09 | 0.00 | 0.00 | 0.00 | 0.316274E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.719108E+09 | 0.00 | 0.00 | 0.00 | 0.288586E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.636136E+09 | 0.00 | 0.00 | 0.00 | 0.251266E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.432785E+09 | 0.00 | 0.00 | 0.00 | 0.168345E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.249420E+09 | 0.00 | 0.00 | 0.00 | 0.954731E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.635385E+10 | 0.00 | 0.00 | 0.00 | 0.251259E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 0.187393E+09 | 0.00 | 0.00 | 0.00 | 0.714076E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.798694E+09 | 0.00 | 0.00 | 0.00 | 0.322774E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT MSE
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 0.322726E+09 | 0.00 | 0.00 | 0.00 | 0.125431E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.344065E+09 | 0.00 | 0.00 | 0.00 | 0.134153E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.417503E+09 | 0.00 | 0.00 | 0.00 | 0.163258E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.518785E+09 | 0.00 | 0.00 | 0.00 | 0.205368E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.679448E+09 | 0.00 | 0.00 | 0.00 | 0.275267E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.736760E+09 | 0.00 | 0.00 | 0.00 | 0.303153E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.776934E+09 | 0.00 | 0.00 | 0.00 | 0.322028E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.775865E+09 | 0.00 | 0.00 | 0.00 | 0.321201E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.760081E+09 | 0.00 | 0.00 | 0.00 | 0.312588E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.720476E+09 | 0.00 | 0.00 | 0.00 | 0.291600E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.538001E+09 | 0.00 | 0.00 | 0.00 | 0.214027E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.363033E+09 | 0.00 | 0.00 | 0.00 | 0.141969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.695368E+10 | 0.00 | 0.00 | 0.00 | 0.281004E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 0.322726E+09 | 0.00 | 0.00 | 0.00 | 0.125431E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.776934E+09 | 0.00 | 0.00 | 0.00 | 0.322028E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT MNE
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 0.189506E+09 | 0.00 | 0.00 | 0.00 | 0.736258E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.241626E+09 | 0.00 | 0.00 | 0.00 | 0.938058E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.341054E+09 | 0.00 | 0.00 | 0.00 | 0.132876E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.480172E+09 | 0.00 | 0.00 | 0.00 | 0.189026E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.685248E+09 | 0.00 | 0.00 | 0.00 | 0.275946E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.756359E+09 | 0.00 | 0.00 | 0.00 | 0.309296E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.789364E+09 | 0.00 | 0.00 | 0.00 | 0.325162E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.766505E+09 | 0.00 | 0.00 | 0.00 | 0.315475E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.712744E+09 | 0.00 | 0.00 | 0.00 | 0.291463E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.626971E+09 | 0.00 | 0.00 | 0.00 | 0.252466E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.426066E+09 | 0.00 | 0.00 | 0.00 | 0.168902E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.235382E+09 | 0.00 | 0.00 | 0.00 | 0.918933E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.625100E+10 | 0.00 | 0.00 | 0.00 | 0.251994E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 0.189506E+09 | 0.00 | 0.00 | 0.00 | 0.736258E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.789364E+09 | 0.00 | 0.00 | 0.00 | 0.325162E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT MN1
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 0.184895E+09 | 0.00 | 0.00 | 0.00 | 0.711774E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.221680E+09 | 0.00 | 0.00 | 0.00 | 0.854136E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.299290E+09 | 0.00 | 0.00 | 0.00 | 0.115617E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.406171E+09 | 0.00 | 0.00 | 0.00 | 0.158504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.574294E+09 | 0.00 | 0.00 | 0.00 | 0.229197E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.633664E+09 | 0.00 | 0.00 | 0.00 | 0.257045E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.661878E+09 | 0.00 | 0.00 | 0.00 | 0.270414E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.648417E+09 | 0.00 | 0.00 | 0.00 | 0.264579E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.600772E+09 | 0.00 | 0.00 | 0.00 | 0.243589E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.537938E+09 | 0.00 | 0.00 | 0.00 | 0.214706E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.382087E+09 | 0.00 | 0.00 | 0.00 | 0.150105E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.231642E+09 | 0.00 | 0.00 | 0.00 | 0.895680E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.538273E+10 | 0.00 | 0.00 | 0.00 | 0.214991E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 0.184895E+09 | 0.00 | 0.00 | 0.00 | 0.711774E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.661878E+09 | 0.00 | 0.00 | 0.00 | 0.270414E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT MN2
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 0.185350E+09 | 0.00 | 0.00 | 0.00 | 0.713799E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.221781E+09 | 0.00 | 0.00 | 0.00 | 0.854869E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.299373E+09 | 0.00 | 0.00 | 0.00 | 0.115695E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.405976E+09 | 0.00 | 0.00 | 0.00 | 0.158494E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.574069E+09 | 0.00 | 0.00 | 0.00 | 0.229204E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.633846E+09 | 0.00 | 0.00 | 0.00 | 0.257221E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.661854E+09 | 0.00 | 0.00 | 0.00 | 0.270515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.648127E+09 | 0.00 | 0.00 | 0.00 | 0.264570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.600835E+09 | 0.00 | 0.00 | 0.00 | 0.243712E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.537852E+09 | 0.00 | 0.00 | 0.00 | 0.214761E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.382098E+09 | 0.00 | 0.00 | 0.00 | 0.150169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.231198E+09 | 0.00 | 0.00 | 0.00 | 0.894346E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.538236E+10 | 0.00 | 0.00 | 0.00 | 0.215064E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 0.185350E+09 | 0.00 | 0.00 | 0.00 | 0.713799E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.661854E+09 | 0.00 | 0.00 | 0.00 | 0.270515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT MS1
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 0.325426E+09 | 0.00 | 0.00 | 0.00 | 0.125563E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.329969E+09 | 0.00 | 0.00 | 0.00 | 0.127744E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.377901E+09 | 0.00 | 0.00 | 0.00 | 0.146754E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.445097E+09 | 0.00 | 0.00 | 0.00 | 0.174993E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.567687E+09 | 0.00 | 0.00 | 0.00 | 0.228346E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.612771E+09 | 0.00 | 0.00 | 0.00 | 0.250569E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.648346E+09 | 0.00 | 0.00 | 0.00 | 0.267023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.657307E+09 | 0.00 | 0.00 | 0.00 | 0.270275E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.648745E+09 | 0.00 | 0.00 | 0.00 | 0.265038E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.632815E+09 | 0.00 | 0.00 | 0.00 | 0.254352E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.496030E+09 | 0.00 | 0.00 | 0.00 | 0.195896E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.367548E+09 | 0.00 | 0.00 | 0.00 | 0.142626E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.610964E+10 | 0.00 | 0.00 | 0.00 | 0.244918E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 0.325426E+09 | 0.00 | 0.00 | 0.00 | 0.125563E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.657307E+09 | 0.00 | 0.00 | 0.00 | 0.270275E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT MS2
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 0.325648E+09 | 0.00 | 0.00 | 0.00 | 0.125703E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.329972E+09 | 0.00 | 0.00 | 0.00 | 0.127800E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.377902E+09 | 0.00 | 0.00 | 0.00 | 0.146817E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.444870E+09 | 0.00 | 0.00 | 0.00 | 0.174983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.567446E+09 | 0.00 | 0.00 | 0.00 | 0.228353E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.612946E+09 | 0.00 | 0.00 | 0.00 | 0.250749E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.648305E+09 | 0.00 | 0.00 | 0.00 | 0.267126E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.656986E+09 | 0.00 | 0.00 | 0.00 | 0.270265E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.648737E+09 | 0.00 | 0.00 | 0.00 | 0.265151E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.632631E+09 | 0.00 | 0.00 | 0.00 | 0.254392E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.495914E+09 | 0.00 | 0.00 | 0.00 | 0.195935E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.367103E+09 | 0.00 | 0.00 | 0.00 | 0.142517E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.610846E+10 | 0.00 | 0.00 | 0.00 | 0.244979E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 0.325648E+09 | 0.00 | 0.00 | 0.00 | 0.125703E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.656986E+09 | 0.00 | 0.00 | 0.00 | 0.270265E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT TSW
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 0.139014E+09 | 0.00 | 0.00 | 0.00 | 0.526675E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.170914E+09 | 0.00 | 0.00 | 0.00 | 0.641934E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.215152E+09 | 0.00 | 0.00 | 0.00 | 0.817601E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.278163E+09 | 0.00 | 0.00 | 0.00 | 0.108203E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.384292E+09 | 0.00 | 0.00 | 0.00 | 0.152885E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.416716E+09 | 0.00 | 0.00 | 0.00 | 0.168227E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.443839E+09 | 0.00 | 0.00 | 0.00 | 0.180585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.441435E+09 | 0.00 | 0.00 | 0.00 | 0.179331E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.425407E+09 | 0.00 | 0.00 | 0.00 | 0.171858E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.388884E+09 | 0.00 | 0.00 | 0.00 | 0.154641E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.276457E+09 | 0.00 | 0.00 | 0.00 | 0.107858E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.177893E+09 | 0.00 | 0.00 | 0.00 | 0.672931E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.375817E+10 | 0.00 | 0.00 | 0.00 | 0.148950E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 0.139014E+09 | 0.00 | 0.00 | 0.00 | 0.526675E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.443839E+09 | 0.00 | 0.00 | 0.00 | 0.180585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT TNW
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 80989477.86 | 0.00 | 0.00 | 0.00 | 0.297942E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.121774E+09 | 0.00 | 0.00 | 0.00 | 0.446227E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.179913E+09 | 0.00 | 0.00 | 0.00 | 0.675592E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.257492E+09 | 0.00 | 0.00 | 0.00 | 0.996161E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.388490E+09 | 0.00 | 0.00 | 0.00 | 0.153627E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.428312E+09 | 0.00 | 0.00 | 0.00 | 0.171845E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.451502E+09 | 0.00 | 0.00 | 0.00 | 0.182573E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.436901E+09 | 0.00 | 0.00 | 0.00 | 0.176457E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.399870E+09 | 0.00 | 0.00 | 0.00 | 0.160634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.338661E+09 | 0.00 | 0.00 | 0.00 | 0.133979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.218806E+09 | 0.00 | 0.00 | 0.00 | 0.848625E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.121321E+09 | 0.00 | 0.00 | 0.00 | 0.446726E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.342403E+10 | 0.00 | 0.00 | 0.00 | 0.135024E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 80989477.86 | 0.00 | 0.00 | 0.00 | 0.297942E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.451502E+09 | 0.00 | 0.00 | 0.00 | 0.182573E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT TSE
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 0.138085E+09 | 0.00 | 0.00 | 0.00 | 0.536528E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.166142E+09 | 0.00 | 0.00 | 0.00 | 0.639632E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.206358E+09 | 0.00 | 0.00 | 0.00 | 0.805197E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.270143E+09 | 0.00 | 0.00 | 0.00 | 0.107697E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.374267E+09 | 0.00 | 0.00 | 0.00 | 0.152608E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.411493E+09 | 0.00 | 0.00 | 0.00 | 0.170173E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.435547E+09 | 0.00 | 0.00 | 0.00 | 0.181583E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.428706E+09 | 0.00 | 0.00 | 0.00 | 0.178503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.417953E+09 | 0.00 | 0.00 | 0.00 | 0.172947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.380144E+09 | 0.00 | 0.00 | 0.00 | 0.154911E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.269725E+09 | 0.00 | 0.00 | 0.00 | 0.107826E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.168251E+09 | 0.00 | 0.00 | 0.00 | 0.652146E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.366681E+10 | 0.00 | 0.00 | 0.00 | 0.148960E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 0.138085E+09 | 0.00 | 0.00 | 0.00 | 0.536528E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.435547E+09 | 0.00 | 0.00 | 0.00 | 0.181583E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT TNE
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 80375217.32 | 0.00 | 0.00 | 0.00 | 0.304028E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.117660E+09 | 0.00 | 0.00 | 0.00 | 0.441987E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.171540E+09 | 0.00 | 0.00 | 0.00 | 0.661673E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.250304E+09 | 0.00 | 0.00 | 0.00 | 0.991120E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.378691E+09 | 0.00 | 0.00 | 0.00 | 0.153270E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.423128E+09 | 0.00 | 0.00 | 0.00 | 0.173664E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.443451E+09 | 0.00 | 0.00 | 0.00 | 0.183487E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.424819E+09 | 0.00 | 0.00 | 0.00 | 0.175615E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.393917E+09 | 0.00 | 0.00 | 0.00 | 0.161866E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.332109E+09 | 0.00 | 0.00 | 0.00 | 0.134474E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.213462E+09 | 0.00 | 0.00 | 0.00 | 0.847629E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.113486E+09 | 0.00 | 0.00 | 0.00 | 0.427600E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.334294E+10 | 0.00 | 0.00 | 0.00 | 0.134978E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 80375217.32 | 0.00 | 0.00 | 0.00 | 0.304028E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.443451E+09 | 0.00 | 0.00 | 0.00 | 0.183487E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT TN1
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 72040959.00 | 0.00 | 0.00 | 0.00 | 0.271197E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.103831E+09 | 0.00 | 0.00 | 0.00 | 0.387405E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.149535E+09 | 0.00 | 0.00 | 0.00 | 0.568054E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.214832E+09 | 0.00 | 0.00 | 0.00 | 0.831519E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.323064E+09 | 0.00 | 0.00 | 0.00 | 0.127769E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.361210E+09 | 0.00 | 0.00 | 0.00 | 0.144997E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.379561E+09 | 0.00 | 0.00 | 0.00 | 0.153570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.365494E+09 | 0.00 | 0.00 | 0.00 | 0.147677E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.337418E+09 | 0.00 | 0.00 | 0.00 | 0.135544E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.288028E+09 | 0.00 | 0.00 | 0.00 | 0.113967E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.189364E+09 | 0.00 | 0.00 | 0.00 | 0.737500E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.104217E+09 | 0.00 | 0.00 | 0.00 | 0.392675E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.288860E+10 | 0.00 | 0.00 | 0.00 | 0.114236E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 72040959.00 | 0.00 | 0.00 | 0.00 | 0.271197E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.379561E+09 | 0.00 | 0.00 | 0.00 | 0.153570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT TN2
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 72175747.96 | 0.00 | 0.00 | 0.00 | 0.271941E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.103787E+09 | 0.00 | 0.00 | 0.00 | 0.387561E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.149269E+09 | 0.00 | 0.00 | 0.00 | 0.567560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.214447E+09 | 0.00 | 0.00 | 0.00 | 0.830785E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.322530E+09 | 0.00 | 0.00 | 0.00 | 0.127674E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.360880E+09 | 0.00 | 0.00 | 0.00 | 0.144992E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.379109E+09 | 0.00 | 0.00 | 0.00 | 0.153527E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.364889E+09 | 0.00 | 0.00 | 0.00 | 0.147566E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.337064E+09 | 0.00 | 0.00 | 0.00 | 0.135522E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.287639E+09 | 0.00 | 0.00 | 0.00 | 0.113915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.189136E+09 | 0.00 | 0.00 | 0.00 | 0.737250E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.103876E+09 | 0.00 | 0.00 | 0.00 | 0.391661E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.288480E+10 | 0.00 | 0.00 | 0.00 | 0.114187E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 72175747.96 | 0.00 | 0.00 | 0.00 | 0.271941E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.379109E+09 | 0.00 | 0.00 | 0.00 | 0.153527E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT TS1
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 0.134261E+09 | 0.00 | 0.00 | 0.00 | 0.513141E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.154571E+09 | 0.00 | 0.00 | 0.00 | 0.588687E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.185609E+09 | 0.00 | 0.00 | 0.00 | 0.712357E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.235518E+09 | 0.00 | 0.00 | 0.00 | 0.918546E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.318609E+09 | 0.00 | 0.00 | 0.00 | 0.127040E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.349206E+09 | 0.00 | 0.00 | 0.00 | 0.141349E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.371493E+09 | 0.00 | 0.00 | 0.00 | 0.151564E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.369754E+09 | 0.00 | 0.00 | 0.00 | 0.150592E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.362731E+09 | 0.00 | 0.00 | 0.00 | 0.146856E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.338105E+09 | 0.00 | 0.00 | 0.00 | 0.134761E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.248144E+09 | 0.00 | 0.00 | 0.00 | 0.972147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.164064E+09 | 0.00 | 0.00 | 0.00 | 0.629405E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.323207E+10 | 0.00 | 0.00 | 0.00 | 0.128559E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 0.134261E+09 | 0.00 | 0.00 | 0.00 | 0.513141E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.371493E+09 | 0.00 | 0.00 | 0.00 | 0.151564E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT TS2
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 0.134458E+09 | 0.00 | 0.00 | 0.00 | 0.514344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.154555E+09 | 0.00 | 0.00 | 0.00 | 0.589140E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.185530E+09 | 0.00 | 0.00 | 0.00 | 0.712698E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.235285E+09 | 0.00 | 0.00 | 0.00 | 0.918492E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.318303E+09 | 0.00 | 0.00 | 0.00 | 0.127037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.349108E+09 | 0.00 | 0.00 | 0.00 | 0.141436E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.371269E+09 | 0.00 | 0.00 | 0.00 | 0.151612E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.369351E+09 | 0.00 | 0.00 | 0.00 | 0.150567E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.362531E+09 | 0.00 | 0.00 | 0.00 | 0.146907E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.337823E+09 | 0.00 | 0.00 | 0.00 | 0.134773E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.247975E+09 | 0.00 | 0.00 | 0.00 | 0.972358E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.163785E+09 | 0.00 | 0.00 | 0.00 | 0.628889E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.322997E+10 | 0.00 | 0.00 | 0.00 | 0.128593E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 0.134458E+09 | 0.00 | 0.00 | 0.00 | 0.514344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.371269E+09 | 0.00 | 0.00 | 0.00 | 0.151612E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: G SW APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 53795113.84 | 0.206211E+09 | 0.00 | 1775544.55 | 0.00 | 0.00 | 0.284834E+09 | 0.00 | 0.36 |
| February | 64719606.56 | 0.212238E+09 | 0.00 | 1052536.74 | 0.00 | 0.00 | 0.146000E+09 | 0.00 | 0.35 |
| March | 96099507.81 | 0.349471E+09 | 0.00 | 745166.57 | 0.00 | 0.00 | 97273135.17 | 0.00 | 0.35 |
| April | 1477884.15 | 0.521840E+09 | 0.00 | 382720.06 | 0.00 | 0.00 | 33487820.76 | 0.00 | 0.36 |
| May | 0.00 | 0.105965E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| June | 0.00 | 0.145496E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| July | 0.00 | 0.162593E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| August | 0.00 | 0.164004E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| September | 0.00 | 0.149937E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| October | 0.00 | 0.124376E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| November | 12591934.21 | 0.749244E+09 | 0.00 | 571298.81 | 0.00 | 0.00 | 71320162.63 | 0.00 | 0.36 |
| December | 62097208.61 | 0.358245E+09 | 0.00 | 1454174.25 | 0.00 | 0.00 | 0.200997E+09 | 0.00 | 0.36 |
| Annual Sum or Average | 0.290781E+09 | 0.109210E+11 | 0.00 | 5981440.98 | 0.00 | 0.00 | 0.833913E+09 | 0.00 | 0.36 |
| Minimum of Months | 0.00 | 0.206211E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
| Maximum of Months | 96099507.81 | 0.164004E+10 | 0.00 | 1775544.55 | 0.00 | 0.00 | 0.284834E+09 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: G NW APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.184518E+09 | 0.166548E+09 | 0.00 | 837966.35 | 64716.55 | 0.00 | 0.167737E+09 | 0.00 | 0.36 |
| February | 0.123739E+09 | 0.180358E+09 | 0.00 | 565084.74 | 275991.20 | 0.00 | 93284050.59 | 0.00 | 0.35 |
| March | 0.132619E+09 | 0.317332E+09 | 0.00 | 417648.17 | 255421.08 | 0.00 | 61863887.53 | 0.00 | 0.35 |
| April | 1729685.38 | 0.498903E+09 | 0.00 | 355549.40 | 0.00 | 0.00 | 34736442.94 | 0.00 | 0.36 |
| May | 0.00 | 0.106045E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| June | 0.00 | 0.146549E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| July | 0.00 | 0.163202E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| August | 0.00 | 0.162971E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| September | 0.00 | 0.146489E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| October | 0.00 | 0.118227E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| November | 32955425.72 | 0.685451E+09 | 0.00 | 371632.14 | 0.00 | 0.00 | 53448961.04 | 0.00 | 0.36 |
| December | 0.134238E+09 | 0.309673E+09 | 0.00 | 712770.35 | 0.00 | 0.00 | 0.145465E+09 | 0.00 | 0.36 |
| Annual Sum or Average | 0.609799E+09 | 0.105931E+11 | 0.00 | 3260651.16 | 596128.83 | 0.00 | 0.556535E+09 | 0.00 | 0.36 |
| Minimum of Months | 0.00 | 0.166548E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
| Maximum of Months | 0.184518E+09 | 0.163202E+10 | 0.00 | 837966.35 | 275991.20 | 0.00 | 0.167737E+09 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: OFFICE
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.736453E+09 | 0.113111E+09 | 0.00 | 1263725.32 | 6653283.96 | 0.00 | 0.102023E+09 | 0.00 | 0.53 |
| February | 0.537335E+09 | 0.140354E+09 | 0.00 | 850441.90 | 7194562.17 | 0.00 | 38184771.27 | 0.00 | 0.52 |
| March | 0.483723E+09 | 0.194290E+09 | 0.00 | 871705.25 | 14150464.61 | 0.00 | 64150195.58 | 0.00 | 0.53 |
| April | 0.345771E+09 | 0.277900E+09 | 0.00 | 617649.10 | 33721812.34 | 0.00 | 14005177.46 | 0.00 | 0.53 |
| May | 0.201118E+09 | 0.527402E+09 | 0.00 | 185328.87 | 84182082.34 | 0.00 | 2789618.27 | 0.00 | 0.53 |
| June | 95561402.10 | 0.712095E+09 | 0.00 | 121472.38 | 0.169032E+09 | 0.00 | 2153666.25 | 0.00 | 0.53 |
| July | 0.106952E+09 | 0.801230E+09 | 0.00 | 83861.52 | 0.162756E+09 | 0.00 | 1193841.35 | 0.00 | 0.53 |
| August | 95126065.45 | 0.851340E+09 | 0.00 | 116346.72 | 0.164111E+09 | 0.00 | 1918539.74 | 0.00 | 0.53 |
| September | 0.119806E+09 | 0.750121E+09 | 0.00 | 156310.05 | 0.124762E+09 | 0.00 | 7438719.09 | 0.00 | 0.53 |
| October | 0.179942E+09 | 0.599715E+09 | 0.00 | 311336.72 | 79769295.56 | 0.00 | 9420635.63 | 0.00 | 0.53 |
| November | 0.420178E+09 | 0.395479E+09 | 0.00 | 529852.88 | 55831615.32 | 0.00 | 16708190.73 | 0.00 | 0.53 |
| December | 0.629866E+09 | 0.131581E+09 | 0.00 | 1320623.78 | 12600228.62 | 0.00 | 96183646.75 | 0.00 | 0.53 |
| Annual Sum or Average | 0.395183E+10 | 0.549462E+10 | 0.00 | 6428654.48 | 0.914764E+09 | 0.00 | 0.356170E+09 | 0.00 | 0.53 |
| Minimum of Months | 95126065.45 | 0.113111E+09 | 0.00 | 83861.52 | 6653283.96 | 0.00 | 1193841.35 | 0.00 | 0.52 |
| Maximum of Months | 0.736453E+09 | 0.851340E+09 | 0.00 | 1320623.78 | 0.169032E+09 | 0.00 | 0.102023E+09 | 0.00 | 0.53 |
Report: MechanicalVentilationLoadsMonthly
For: G NE APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.172296E+09 | 0.174011E+09 | 0.00 | 824989.07 | 0.00 | 0.00 | 0.178976E+09 | 0.00 | 0.36 |
| February | 0.123194E+09 | 0.184285E+09 | 0.00 | 586243.66 | 175405.35 | 0.00 | 93307518.61 | 0.00 | 0.35 |
| March | 0.130564E+09 | 0.322115E+09 | 0.00 | 394730.81 | 0.00 | 0.00 | 65460705.25 | 0.00 | 0.35 |
| April | 1498914.84 | 0.506208E+09 | 0.00 | 354391.13 | 0.00 | 0.00 | 34812323.40 | 0.00 | 0.36 |
| May | 0.00 | 0.107079E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| June | 0.00 | 0.148653E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| July | 0.00 | 0.164920E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| August | 0.00 | 0.164084E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| September | 0.00 | 0.148323E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| October | 0.00 | 0.119650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| November | 31569307.45 | 0.693804E+09 | 0.00 | 391927.96 | 0.00 | 0.00 | 54195718.08 | 0.00 | 0.36 |
| December | 0.133052E+09 | 0.309809E+09 | 0.00 | 673532.87 | 0.00 | 0.00 | 0.147738E+09 | 0.00 | 0.36 |
| Annual Sum or Average | 0.592174E+09 | 0.107173E+11 | 0.00 | 3225815.50 | 175405.35 | 0.00 | 0.574490E+09 | 0.00 | 0.36 |
| Minimum of Months | 0.00 | 0.174011E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
| Maximum of Months | 0.172296E+09 | 0.164920E+10 | 0.00 | 824989.07 | 175405.35 | 0.00 | 0.178976E+09 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: G N1 APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 98184043.04 | 0.174041E+09 | 0.00 | 999918.63 | 0.00 | 0.00 | 0.256214E+09 | 0.00 | 0.36 |
| February | 91627809.00 | 0.189643E+09 | 0.00 | 635291.44 | 205005.05 | 0.00 | 0.127780E+09 | 0.00 | 0.35 |
| March | 0.106140E+09 | 0.328770E+09 | 0.00 | 458615.87 | 58822.74 | 0.00 | 95147069.23 | 0.00 | 0.35 |
| April | 1272748.93 | 0.502120E+09 | 0.00 | 343367.79 | 0.00 | 0.00 | 35113632.69 | 0.00 | 0.36 |
| May | 0.00 | 0.106990E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| June | 0.00 | 0.146630E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| July | 0.00 | 0.161428E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| August | 0.00 | 0.161390E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| September | 0.00 | 0.145240E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| October | 0.00 | 0.117704E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| November | 17557438.61 | 0.690545E+09 | 0.00 | 424768.47 | 0.00 | 0.00 | 69690276.47 | 0.00 | 0.36 |
| December | 84845616.17 | 0.311738E+09 | 0.00 | 878148.53 | 0.00 | 0.00 | 0.194820E+09 | 0.00 | 0.36 |
| Annual Sum or Average | 0.399627E+09 | 0.105907E+11 | 0.00 | 3740110.72 | 263827.79 | 0.00 | 0.778765E+09 | 0.00 | 0.36 |
| Minimum of Months | 0.00 | 0.174041E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
| Maximum of Months | 0.106140E+09 | 0.161428E+10 | 0.00 | 999918.63 | 205005.05 | 0.00 | 0.256214E+09 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: G N2 APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 98014942.98 | 0.174364E+09 | 0.00 | 1003047.91 | 0.00 | 0.00 | 0.256297E+09 | 0.00 | 0.36 |
| February | 91526833.01 | 0.189772E+09 | 0.00 | 636180.44 | 200200.41 | 0.00 | 0.127872E+09 | 0.00 | 0.35 |
| March | 0.105800E+09 | 0.328897E+09 | 0.00 | 459000.23 | 57539.80 | 0.00 | 95531668.74 | 0.00 | 0.35 |
| April | 1272734.09 | 0.502161E+09 | 0.00 | 343500.82 | 0.00 | 0.00 | 35123785.92 | 0.00 | 0.36 |
| May | 0.00 | 0.107004E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| June | 0.00 | 0.146698E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| July | 0.00 | 0.161469E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| August | 0.00 | 0.161407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| September | 0.00 | 0.145290E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| October | 0.00 | 0.117736E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| November | 17559050.81 | 0.690718E+09 | 0.00 | 425759.13 | 0.00 | 0.00 | 69670884.57 | 0.00 | 0.36 |
| December | 84753089.24 | 0.311587E+09 | 0.00 | 876383.81 | 0.00 | 0.00 | 0.194996E+09 | 0.00 | 0.36 |
| Annual Sum or Average | 0.398927E+09 | 0.105935E+11 | 0.00 | 3743872.33 | 257740.22 | 0.00 | 0.779491E+09 | 0.00 | 0.36 |
| Minimum of Months | 0.00 | 0.174364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
| Maximum of Months | 0.105800E+09 | 0.161469E+10 | 0.00 | 1003047.91 | 200200.41 | 0.00 | 0.256297E+09 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: G S1 APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 5390071.10 | 0.221176E+09 | 0.00 | 2083824.68 | 0.00 | 0.00 | 0.327407E+09 | 0.00 | 0.36 |
| February | 41140487.35 | 0.229808E+09 | 0.00 | 1201552.99 | 0.00 | 0.00 | 0.168208E+09 | 0.00 | 0.35 |
| March | 48048933.62 | 0.369211E+09 | 0.00 | 858353.85 | 0.00 | 0.00 | 0.148145E+09 | 0.00 | 0.35 |
| April | 520458.11 | 0.533889E+09 | 0.00 | 368260.18 | 0.00 | 0.00 | 33781470.31 | 0.00 | 0.36 |
| May | 0.00 | 0.107408E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| June | 0.00 | 0.145889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| July | 0.00 | 0.161236E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| August | 0.00 | 0.163213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| September | 0.00 | 0.149992E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| October | 0.00 | 0.125646E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| November | 650592.55 | 0.769538E+09 | 0.00 | 652761.66 | 0.00 | 0.00 | 82941733.86 | 0.00 | 0.36 |
| December | 14869786.72 | 0.370389E+09 | 0.00 | 1715473.09 | 0.00 | 0.00 | 0.241749E+09 | 0.00 | 0.36 |
| Annual Sum or Average | 0.110620E+09 | 0.110279E+11 | 0.00 | 6880226.46 | 0.00 | 0.00 | 0.100223E+10 | 0.00 | 0.36 |
| Minimum of Months | 0.00 | 0.221176E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
| Maximum of Months | 48048933.62 | 0.163213E+10 | 0.00 | 2083824.68 | 0.00 | 0.00 | 0.327407E+09 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: G S2 APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 2331444.14 | 0.232995E+09 | 0.00 | 2262096.57 | 0.00 | 0.00 | 0.325091E+09 | 0.00 | 0.35 |
| February | 37868978.02 | 0.239468E+09 | 0.00 | 1299158.42 | 0.00 | 0.00 | 0.168431E+09 | 0.00 | 0.35 |
| March | 35712237.57 | 0.385459E+09 | 0.00 | 934346.90 | 0.00 | 0.00 | 0.159055E+09 | 0.00 | 0.35 |
| April | 167436.12 | 0.556276E+09 | 0.00 | 411361.56 | 0.00 | 0.00 | 32713655.75 | 0.00 | 0.36 |
| May | 0.00 | 0.110994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| June | 0.00 | 0.150090E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| July | 0.00 | 0.165572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| August | 0.00 | 0.167387E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| September | 0.00 | 0.153895E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| October | 0.00 | 0.129271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| November | 0.00 | 0.793918E+09 | 0.00 | 712600.64 | 0.00 | 0.00 | 81930008.49 | 0.00 | 0.36 |
| December | 11687952.18 | 0.384428E+09 | 0.00 | 1855528.61 | 0.00 | 0.00 | 0.240328E+09 | 0.00 | 0.36 |
| Annual Sum or Average | 87768048.03 | 0.113646E+11 | 0.00 | 7475092.69 | 0.00 | 0.00 | 0.100755E+10 | 0.00 | 0.36 |
| Minimum of Months | 0.00 | 0.232995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
| Maximum of Months | 37868978.02 | 0.167387E+10 | 0.00 | 2262096.57 | 0.00 | 0.00 | 0.325091E+09 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: M SW APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.221525E+09 | 0.380844E+09 | 0.00 | 3401580.71 | 0.00 | 0.00 | 0.459920E+09 | 0.00 | 0.36 |
| February | 0.167596E+09 | 0.398624E+09 | 0.00 | 2026724.21 | 0.00 | 0.00 | 0.252366E+09 | 0.00 | 0.35 |
| March | 0.187322E+09 | 0.684567E+09 | 0.00 | 1684206.31 | 0.00 | 0.00 | 0.190927E+09 | 0.00 | 0.35 |
| April | 2816231.35 | 0.104270E+10 | 0.00 | 816739.54 | 0.00 | 0.00 | 65494550.93 | 0.00 | 0.36 |
| May | 0.00 | 0.208530E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| June | 0.00 | 0.287211E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| July | 0.00 | 0.318255E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| August | 0.00 | 0.316722E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| September | 0.00 | 0.287213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| October | 0.00 | 0.235665E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| November | 71927399.34 | 0.140232E+10 | 0.00 | 958929.98 | 0.00 | 0.00 | 98691669.33 | 0.00 | 0.36 |
| December | 0.197759E+09 | 0.667387E+09 | 0.00 | 2451606.10 | 0.00 | 0.00 | 0.337904E+09 | 0.00 | 0.36 |
| Annual Sum or Average | 0.848945E+09 | 0.211124E+11 | 0.00 | 11339786.85 | 0.00 | 0.00 | 0.140530E+10 | 0.00 | 0.36 |
| Minimum of Months | 0.00 | 0.380844E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
| Maximum of Months | 0.221525E+09 | 0.318255E+10 | 0.00 | 3401580.71 | 0.00 | 0.00 | 0.459920E+09 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: M NW APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.423877E+09 | 0.309138E+09 | 0.00 | 1518786.71 | 315572.17 | 0.00 | 0.274511E+09 | 0.00 | 0.36 |
| February | 0.264714E+09 | 0.342234E+09 | 0.00 | 1121289.76 | 638410.96 | 0.00 | 0.157957E+09 | 0.00 | 0.35 |
| March | 0.254184E+09 | 0.634295E+09 | 0.00 | 967367.08 | 447806.25 | 0.00 | 0.124110E+09 | 0.00 | 0.35 |
| April | 2930822.17 | 0.100128E+10 | 0.00 | 764740.76 | 0.00 | 0.00 | 67708100.62 | 0.00 | 0.36 |
| May | 0.00 | 0.208504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| June | 0.00 | 0.288875E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| July | 0.00 | 0.319135E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| August | 0.00 | 0.314341E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| September | 0.00 | 0.279853E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| October | 0.00 | 0.222880E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| November | 98108462.33 | 0.127469E+10 | 0.00 | 609941.10 | 268929.13 | 0.00 | 77439830.42 | 0.00 | 0.36 |
| December | 0.355337E+09 | 0.572063E+09 | 0.00 | 1046282.55 | 0.00 | 0.00 | 0.198792E+09 | 0.00 | 0.36 |
| Annual Sum or Average | 0.139915E+10 | 0.204696E+11 | 0.00 | 6028407.96 | 1670718.51 | 0.00 | 0.900519E+09 | 0.00 | 0.36 |
| Minimum of Months | 0.00 | 0.309138E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
| Maximum of Months | 0.423877E+09 | 0.319135E+10 | 0.00 | 1518786.71 | 638410.96 | 0.00 | 0.274511E+09 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: M SE APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.205799E+09 | 0.395231E+09 | 0.00 | 3404297.52 | 0.00 | 0.00 | 0.471685E+09 | 0.00 | 0.36 |
| February | 0.159098E+09 | 0.407661E+09 | 0.00 | 2139588.24 | 0.00 | 0.00 | 0.259267E+09 | 0.00 | 0.35 |
| March | 0.162569E+09 | 0.695657E+09 | 0.00 | 1722517.95 | 0.00 | 0.00 | 0.217066E+09 | 0.00 | 0.35 |
| April | 2485667.07 | 0.106101E+10 | 0.00 | 813225.75 | 0.00 | 0.00 | 65224831.99 | 0.00 | 0.36 |
| May | 0.00 | 0.210823E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| June | 0.00 | 0.291594E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| July | 0.00 | 0.321953E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| August | 0.00 | 0.319046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| September | 0.00 | 0.291082E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| October | 0.00 | 0.238653E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| November | 65145204.98 | 0.142036E+10 | 0.00 | 1021293.67 | 0.00 | 0.00 | 0.104155E+09 | 0.00 | 0.36 |
| December | 0.192921E+09 | 0.671053E+09 | 0.00 | 2406288.92 | 0.00 | 0.00 | 0.343159E+09 | 0.00 | 0.36 |
| Annual Sum or Average | 0.788019E+09 | 0.213825E+11 | 0.00 | 11507212.04 | 0.00 | 0.00 | 0.146056E+10 | 0.00 | 0.36 |
| Minimum of Months | 0.00 | 0.395231E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
| Maximum of Months | 0.205799E+09 | 0.321953E+10 | 0.00 | 3404297.52 | 0.00 | 0.00 | 0.471685E+09 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: M NE APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.421332E+09 | 0.322748E+09 | 0.00 | 1475265.22 | 0.00 | 0.00 | 0.277500E+09 | 0.00 | 0.36 |
| February | 0.257722E+09 | 0.348573E+09 | 0.00 | 1186644.75 | 391621.68 | 0.00 | 0.164474E+09 | 0.00 | 0.35 |
| March | 0.250225E+09 | 0.642317E+09 | 0.00 | 941745.30 | 0.00 | 0.00 | 0.132090E+09 | 0.00 | 0.35 |
| April | 2810428.00 | 0.101520E+10 | 0.00 | 769444.63 | 0.00 | 0.00 | 67646670.88 | 0.00 | 0.36 |
| May | 0.00 | 0.210329E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| June | 0.00 | 0.292704E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| July | 0.00 | 0.322278E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| August | 0.00 | 0.316141E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| September | 0.00 | 0.283296E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| October | 0.00 | 0.225394E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| November | 97327907.25 | 0.128864E+10 | 0.00 | 640547.36 | 0.00 | 0.00 | 77690672.63 | 0.00 | 0.36 |
| December | 0.379724E+09 | 0.570599E+09 | 0.00 | 951950.21 | 76050.02 | 0.00 | 0.177357E+09 | 0.00 | 0.36 |
| Annual Sum or Average | 0.140914E+10 | 0.206895E+11 | 0.00 | 5965597.47 | 467671.69 | 0.00 | 0.896759E+09 | 0.00 | 0.36 |
| Minimum of Months | 0.00 | 0.322748E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
| Maximum of Months | 0.421332E+09 | 0.322278E+10 | 0.00 | 1475265.22 | 391621.68 | 0.00 | 0.277500E+09 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: M N1 APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.279368E+09 | 0.330411E+09 | 0.00 | 1885749.62 | 0.00 | 0.00 | 0.425649E+09 | 0.00 | 0.36 |
| February | 0.202253E+09 | 0.361881E+09 | 0.00 | 1309798.44 | 446437.85 | 0.00 | 0.226995E+09 | 0.00 | 0.35 |
| March | 0.202239E+09 | 0.655967E+09 | 0.00 | 1041764.25 | 297238.51 | 0.00 | 0.191105E+09 | 0.00 | 0.35 |
| April | 1691399.55 | 0.100465E+10 | 0.00 | 731012.35 | 0.00 | 0.00 | 69238346.51 | 0.00 | 0.36 |
| May | 0.00 | 0.210584E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| June | 0.00 | 0.289195E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| July | 0.00 | 0.316435E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| August | 0.00 | 0.312850E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| September | 0.00 | 0.279614E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| October | 0.00 | 0.224435E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| November | 64934087.82 | 0.130614E+10 | 0.00 | 698146.62 | 0.00 | 0.00 | 0.111464E+09 | 0.00 | 0.36 |
| December | 0.229877E+09 | 0.588321E+09 | 0.00 | 1444895.61 | 0.00 | 0.00 | 0.330154E+09 | 0.00 | 0.36 |
| Annual Sum or Average | 0.980362E+09 | 0.205785E+11 | 0.00 | 7111366.91 | 743676.35 | 0.00 | 0.135460E+10 | 0.00 | 0.36 |
| Minimum of Months | 0.00 | 0.330411E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
| Maximum of Months | 0.279368E+09 | 0.316435E+10 | 0.00 | 1885749.62 | 446437.85 | 0.00 | 0.425649E+09 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: M N2 APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.277804E+09 | 0.330956E+09 | 0.00 | 1893976.54 | 0.00 | 0.00 | 0.427163E+09 | 0.00 | 0.36 |
| February | 0.203028E+09 | 0.362099E+09 | 0.00 | 1311654.39 | 437661.78 | 0.00 | 0.226240E+09 | 0.00 | 0.35 |
| March | 0.201639E+09 | 0.656214E+09 | 0.00 | 1045495.84 | 217276.12 | 0.00 | 0.191855E+09 | 0.00 | 0.35 |
| April | 1691193.42 | 0.100478E+10 | 0.00 | 731467.99 | 0.00 | 0.00 | 69261986.61 | 0.00 | 0.36 |
| May | 0.00 | 0.210608E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| June | 0.00 | 0.289313E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| July | 0.00 | 0.316512E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| August | 0.00 | 0.312877E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| September | 0.00 | 0.279709E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| October | 0.00 | 0.224493E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| November | 64665772.98 | 0.130646E+10 | 0.00 | 700731.65 | 0.00 | 0.00 | 0.111723E+09 | 0.00 | 0.36 |
| December | 0.228687E+09 | 0.588044E+09 | 0.00 | 1443548.44 | 0.00 | 0.00 | 0.331633E+09 | 0.00 | 0.36 |
| Annual Sum or Average | 0.977515E+09 | 0.205837E+11 | 0.00 | 7126874.85 | 654937.90 | 0.00 | 0.135788E+10 | 0.00 | 0.36 |
| Minimum of Months | 0.00 | 0.330956E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
| Maximum of Months | 0.277804E+09 | 0.316512E+10 | 0.00 | 1893976.54 | 437661.78 | 0.00 | 0.427163E+09 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: M S1 APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 53140949.82 | 0.412534E+09 | 0.00 | 4163156.62 | 0.00 | 0.00 | 0.619712E+09 | 0.00 | 0.36 |
| February | 0.100280E+09 | 0.429952E+09 | 0.00 | 2409591.55 | 0.00 | 0.00 | 0.318236E+09 | 0.00 | 0.35 |
| March | 0.106668E+09 | 0.717386E+09 | 0.00 | 1904333.22 | 0.00 | 0.00 | 0.280059E+09 | 0.00 | 0.35 |
| April | 825912.90 | 0.105722E+10 | 0.00 | 779300.39 | 0.00 | 0.00 | 67111278.89 | 0.00 | 0.36 |
| May | 0.00 | 0.210731E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| June | 0.00 | 0.287228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| July | 0.00 | 0.315431E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| August | 0.00 | 0.315904E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| September | 0.00 | 0.288707E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| October | 0.00 | 0.239848E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| November | 22180033.72 | 0.145669E+10 | 0.00 | 1151650.40 | 0.00 | 0.00 | 0.147982E+09 | 0.00 | 0.36 |
| December | 95916128.91 | 0.698809E+09 | 0.00 | 3126031.25 | 0.00 | 0.00 | 0.427457E+09 | 0.00 | 0.36 |
| Annual Sum or Average | 0.379012E+09 | 0.213511E+11 | 0.00 | 13534063.44 | 0.00 | 0.00 | 0.186056E+10 | 0.00 | 0.36 |
| Minimum of Months | 0.00 | 0.412534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
| Maximum of Months | 0.106668E+09 | 0.315904E+10 | 0.00 | 4163156.62 | 0.00 | 0.00 | 0.619712E+09 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: M S2 APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 53079351.70 | 0.412927E+09 | 0.00 | 4164258.99 | 0.00 | 0.00 | 0.619678E+09 | 0.00 | 0.36 |
| February | 0.100386E+09 | 0.430122E+09 | 0.00 | 2411780.85 | 0.00 | 0.00 | 0.318128E+09 | 0.00 | 0.35 |
| March | 0.104853E+09 | 0.717520E+09 | 0.00 | 1909330.87 | 0.00 | 0.00 | 0.281893E+09 | 0.00 | 0.35 |
| April | 825844.36 | 0.105737E+10 | 0.00 | 779286.96 | 0.00 | 0.00 | 67122534.50 | 0.00 | 0.36 |
| May | 0.00 | 0.210756E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| June | 0.00 | 0.287352E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| July | 0.00 | 0.315511E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| August | 0.00 | 0.315933E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| September | 0.00 | 0.288797E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| October | 0.00 | 0.239900E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| November | 22066301.55 | 0.145697E+10 | 0.00 | 1153410.44 | 0.00 | 0.00 | 0.148074E+09 | 0.00 | 0.36 |
| December | 96405038.04 | 0.698658E+09 | 0.00 | 3122883.81 | 0.00 | 0.00 | 0.427030E+09 | 0.00 | 0.36 |
| Annual Sum or Average | 0.377616E+09 | 0.213561E+11 | 0.00 | 13540951.92 | 0.00 | 0.00 | 0.186193E+10 | 0.00 | 0.36 |
| Minimum of Months | 0.00 | 0.412927E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
| Maximum of Months | 0.104853E+09 | 0.315933E+10 | 0.00 | 4164258.99 | 0.00 | 0.00 | 0.619678E+09 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: T SW APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.220902E+09 | 0.166376E+09 | 0.00 | 1077834.27 | 306577.27 | 12372044.75 | 97457871.80 | 0.00 | 0.35 |
| February | 0.127416E+09 | 0.179588E+09 | 0.00 | 567244.73 | 0.00 | 30297440.67 | 47253505.21 | 0.00 | 0.35 |
| March | 0.103405E+09 | 0.306807E+09 | 0.00 | 585802.45 | 141091.02 | 24477603.94 | 46823518.59 | 0.00 | 0.35 |
| April | 16452786.23 | 0.484502E+09 | 0.00 | 336360.82 | 39759.26 | 0.00 | 22229713.46 | 0.00 | 0.36 |
| May | 0.00 | 0.100486E+10 | 0.00 | 9083.47 | 0.00 | 0.00 | 501990.79 | 0.00 | 0.36 |
| June | 0.00 | 0.141868E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| July | 0.00 | 0.157606E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| August | 0.00 | 0.155735E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| September | 0.00 | 0.140290E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| October | 0.00 | 0.112016E+10 | 0.00 | 2068.56 | 0.00 | 0.00 | 8044.68 | 0.00 | 0.36 |
| November | 58137015.51 | 0.653498E+09 | 0.00 | 324754.80 | 262421.97 | 6724221.95 | 24362446.16 | 0.00 | 0.36 |
| December | 0.157315E+09 | 0.301635E+09 | 0.00 | 677441.79 | 0.00 | 29423057.09 | 73392805.31 | 0.00 | 0.35 |
| Annual Sum or Average | 0.683627E+09 | 0.101724E+11 | 0.00 | 3580590.89 | 749849.51 | 0.103294E+09 | 0.312030E+09 | 0.00 | 0.36 |
| Minimum of Months | 0.00 | 0.166376E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
| Maximum of Months | 0.220902E+09 | 0.157606E+10 | 0.00 | 1077834.27 | 306577.27 | 30297440.67 | 97457871.80 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: T NW APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.250112E+09 | 0.134796E+09 | 0.00 | 374217.09 | 2454452.02 | 26173728.89 | 43894600.31 | 0.00 | 0.35 |
| February | 0.126065E+09 | 0.155356E+09 | 0.00 | 317344.78 | 806323.26 | 40033812.43 | 32156204.43 | 0.00 | 0.35 |
| March | 0.102735E+09 | 0.286661E+09 | 0.00 | 322115.73 | 370444.33 | 37114590.55 | 29897212.73 | 0.00 | 0.35 |
| April | 17082919.62 | 0.466717E+09 | 0.00 | 316237.40 | 182414.47 | 0.00 | 22729719.23 | 0.00 | 0.36 |
| May | 0.00 | 0.100558E+10 | 0.00 | 9987.52 | 0.00 | 0.00 | 520183.06 | 0.00 | 0.36 |
| June | 0.00 | 0.142633E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| July | 0.00 | 0.158027E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| August | 0.00 | 0.154714E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| September | 0.00 | 0.137135E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| October | 0.00 | 0.106429E+10 | 0.00 | 3749.22 | 0.00 | 0.00 | 22056.16 | 0.00 | 0.36 |
| November | 57394687.81 | 0.597708E+09 | 0.00 | 192244.77 | 973901.57 | 12480734.16 | 20114572.35 | 0.00 | 0.36 |
| December | 0.168154E+09 | 0.259215E+09 | 0.00 | 242806.45 | 125135.21 | 50057434.32 | 32224950.06 | 0.00 | 0.35 |
| Annual Sum or Average | 0.721543E+09 | 0.989540E+10 | 0.00 | 1778702.96 | 4912670.85 | 0.165860E+09 | 0.181559E+09 | 0.00 | 0.36 |
| Minimum of Months | 0.00 | 0.134796E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
| Maximum of Months | 0.250112E+09 | 0.158027E+10 | 0.00 | 374217.09 | 2454452.02 | 50057434.32 | 43894600.31 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: T SE APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.221164E+09 | 0.173344E+09 | 0.00 | 1027354.91 | 170326.15 | 11612413.90 | 98561174.61 | 0.00 | 0.35 |
| February | 0.129788E+09 | 0.184132E+09 | 0.00 | 574249.59 | 0.00 | 29530410.35 | 46050241.42 | 0.00 | 0.35 |
| March | 0.110520E+09 | 0.312474E+09 | 0.00 | 543343.48 | 0.00 | 17802439.84 | 48761853.26 | 0.00 | 0.35 |
| April | 15856029.77 | 0.494463E+09 | 0.00 | 336301.58 | 0.00 | 0.00 | 23046446.32 | 0.00 | 0.36 |
| May | 0.00 | 0.101772E+10 | 0.00 | 10795.36 | 0.00 | 0.00 | 525494.84 | 0.00 | 0.36 |
| June | 0.00 | 0.144124E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| July | 0.00 | 0.159596E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| August | 0.00 | 0.156998E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| September | 0.00 | 0.142353E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| October | 0.00 | 0.113599E+10 | 0.00 | 968.36 | 0.00 | 0.00 | 4850.01 | 0.00 | 0.36 |
| November | 57602375.07 | 0.663003E+09 | 0.00 | 355714.49 | 90615.19 | 6056753.25 | 25422257.37 | 0.00 | 0.36 |
| December | 0.160486E+09 | 0.303944E+09 | 0.00 | 626783.04 | 0.00 | 29165657.63 | 72009031.34 | 0.00 | 0.35 |
| Annual Sum or Average | 0.695416E+09 | 0.103158E+11 | 0.00 | 3475510.81 | 260941.34 | 94167674.97 | 0.314381E+09 | 0.00 | 0.36 |
| Minimum of Months | 0.00 | 0.173344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
| Maximum of Months | 0.221164E+09 | 0.159596E+10 | 0.00 | 1027354.91 | 170326.15 | 29530410.35 | 98561174.61 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: T NE APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.255689E+09 | 0.142384E+09 | 0.00 | 315974.69 | 997744.26 | 24118371.86 | 42270690.43 | 0.00 | 0.35 |
| February | 0.127284E+09 | 0.158883E+09 | 0.00 | 322298.16 | 211929.73 | 39443640.06 | 32192687.89 | 0.00 | 0.35 |
| March | 0.117675E+09 | 0.290999E+09 | 0.00 | 284910.50 | 148255.82 | 26470005.95 | 27854240.06 | 0.00 | 0.35 |
| April | 16342114.19 | 0.475347E+09 | 0.00 | 325530.70 | 0.00 | 0.00 | 23961064.53 | 0.00 | 0.36 |
| May | 0.00 | 0.101654E+10 | 0.00 | 11653.08 | 0.00 | 0.00 | 553401.10 | 0.00 | 0.36 |
| June | 0.00 | 0.144644E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| July | 0.00 | 0.159780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| August | 0.00 | 0.155766E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| September | 0.00 | 0.139046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| October | 0.00 | 0.107868E+10 | 0.00 | 2680.24 | 0.00 | 0.00 | 14394.73 | 0.00 | 0.36 |
| November | 56956246.62 | 0.606085E+09 | 0.00 | 203073.75 | 444744.37 | 11637339.65 | 22041251.98 | 0.00 | 0.36 |
| December | 0.171512E+09 | 0.259625E+09 | 0.00 | 216179.63 | 74879.63 | 47529795.11 | 32350936.70 | 0.00 | 0.35 |
| Annual Sum or Average | 0.745458E+09 | 0.100209E+11 | 0.00 | 1682300.75 | 1877553.81 | 0.149199E+09 | 0.181239E+09 | 0.00 | 0.36 |
| Minimum of Months | 0.00 | 0.142384E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
| Maximum of Months | 0.255689E+09 | 0.159780E+10 | 0.00 | 325530.70 | 997744.26 | 47529795.11 | 42270690.43 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: T N1 APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.252278E+09 | 0.142473E+09 | 0.00 | 365869.44 | 2113686.39 | 16964333.00 | 63233914.42 | 0.00 | 0.35 |
| February | 0.132018E+09 | 0.163428E+09 | 0.00 | 347243.54 | 579004.94 | 28658771.62 | 43045610.11 | 0.00 | 0.35 |
| March | 0.127514E+09 | 0.301360E+09 | 0.00 | 278462.25 | 365983.09 | 13985694.67 | 34855794.36 | 0.00 | 0.35 |
| April | 14739351.76 | 0.476152E+09 | 0.00 | 290556.85 | 107052.09 | 0.00 | 24615925.53 | 0.00 | 0.36 |
| May | 0.00 | 0.103104E+10 | 0.00 | 8663.44 | 0.00 | 0.00 | 176789.46 | 0.00 | 0.36 |
| June | 0.00 | 0.144407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| July | 0.00 | 0.158528E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| August | 0.00 | 0.155690E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| September | 0.00 | 0.138672E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| October | 0.00 | 0.108582E+10 | 0.00 | 518.84 | 0.00 | 0.00 | 4374.13 | 0.00 | 0.36 |
| November | 63686609.71 | 0.618049E+09 | 0.00 | 204683.66 | 904024.50 | 0.00 | 27635191.64 | 0.00 | 0.36 |
| December | 0.194475E+09 | 0.268470E+09 | 0.00 | 271612.02 | 204383.63 | 22717647.88 | 41728646.93 | 0.00 | 0.35 |
| Annual Sum or Average | 0.784711E+09 | 0.100598E+11 | 0.00 | 1767610.03 | 4274134.64 | 82326447.17 | 0.235296E+09 | 0.00 | 0.36 |
| Minimum of Months | 0.00 | 0.142473E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
| Maximum of Months | 0.252278E+09 | 0.158528E+10 | 0.00 | 365869.44 | 2113686.39 | 28658771.62 | 63233914.42 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: T N2 APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.252036E+09 | 0.142512E+09 | 0.00 | 368065.69 | 2036452.57 | 17048601.17 | 63605642.24 | 0.00 | 0.35 |
| February | 0.132171E+09 | 0.163132E+09 | 0.00 | 348437.26 | 558380.38 | 28658241.22 | 43000583.78 | 0.00 | 0.35 |
| March | 0.128090E+09 | 0.300679E+09 | 0.00 | 278756.47 | 353335.76 | 13785426.91 | 34704548.14 | 0.00 | 0.35 |
| April | 14787749.20 | 0.475122E+09 | 0.00 | 291452.06 | 56264.61 | 0.00 | 24699849.21 | 0.00 | 0.36 |
| May | 0.00 | 0.102953E+10 | 0.00 | 8819.18 | 0.00 | 0.00 | 182537.61 | 0.00 | 0.36 |
| June | 0.00 | 0.144292E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| July | 0.00 | 0.158379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| August | 0.00 | 0.155524E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| September | 0.00 | 0.138553E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| October | 0.00 | 0.108452E+10 | 0.00 | 517.18 | 0.00 | 0.00 | 4725.87 | 0.00 | 0.36 |
| November | 63722272.01 | 0.617240E+09 | 0.00 | 205909.73 | 884080.12 | 0.00 | 27725023.91 | 0.00 | 0.36 |
| December | 0.194643E+09 | 0.267853E+09 | 0.00 | 269391.21 | 179856.27 | 22559558.17 | 41854334.95 | 0.00 | 0.35 |
| Annual Sum or Average | 0.785451E+09 | 0.100481E+11 | 0.00 | 1771348.79 | 4068369.71 | 82051827.46 | 0.235777E+09 | 0.00 | 0.36 |
| Minimum of Months | 0.00 | 0.142512E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
| Maximum of Months | 0.252036E+09 | 0.158379E+10 | 0.00 | 368065.69 | 2036452.57 | 28658241.22 | 63605642.24 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: T S1 APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.204712E+09 | 0.179627E+09 | 0.00 | 1157982.15 | 178349.58 | 900731.57 | 0.136056E+09 | 0.00 | 0.35 |
| February | 0.134221E+09 | 0.193212E+09 | 0.00 | 631915.91 | 0.00 | 13623308.82 | 62512788.81 | 0.00 | 0.35 |
| March | 0.117679E+09 | 0.326415E+09 | 0.00 | 556888.77 | 33294.80 | 8212931.37 | 57002997.37 | 0.00 | 0.35 |
| April | 14025739.79 | 0.498265E+09 | 0.00 | 311790.25 | 0.00 | 0.00 | 23960745.10 | 0.00 | 0.36 |
| May | 0.00 | 0.103043E+10 | 0.00 | 8331.77 | 0.00 | 0.00 | 161193.13 | 0.00 | 0.36 |
| June | 0.00 | 0.143500E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| July | 0.00 | 0.158032E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| August | 0.00 | 0.156955E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| September | 0.00 | 0.142491E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| October | 0.00 | 0.115241E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| November | 52856624.48 | 0.684492E+09 | 0.00 | 369304.46 | 148872.12 | 0.00 | 37222800.29 | 0.00 | 0.36 |
| December | 0.153714E+09 | 0.318632E+09 | 0.00 | 792854.06 | 0.00 | 5492527.85 | 0.108559E+09 | 0.00 | 0.35 |
| Annual Sum or Average | 0.677208E+09 | 0.103933E+11 | 0.00 | 3829067.38 | 360516.49 | 28229499.62 | 0.425475E+09 | 0.00 | 0.36 |
| Minimum of Months | 0.00 | 0.179627E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
| Maximum of Months | 0.204712E+09 | 0.158032E+10 | 0.00 | 1157982.15 | 178349.58 | 13623308.82 | 0.136056E+09 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: T S2 APARTMENT
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.205042E+09 | 0.179897E+09 | 0.00 | 1159570.55 | 179918.89 | 900705.85 | 0.135683E+09 | 0.00 | 0.35 |
| February | 0.134567E+09 | 0.193370E+09 | 0.00 | 632718.54 | 0.00 | 13623181.99 | 62146132.20 | 0.00 | 0.35 |
| March | 0.117948E+09 | 0.326536E+09 | 0.00 | 558787.70 | 30921.79 | 7975754.89 | 57074635.30 | 0.00 | 0.35 |
| April | 14179477.78 | 0.498445E+09 | 0.00 | 311762.19 | 0.00 | 0.00 | 23833521.33 | 0.00 | 0.36 |
| May | 0.00 | 0.103069E+10 | 0.00 | 8315.80 | 0.00 | 0.00 | 163949.82 | 0.00 | 0.36 |
| June | 0.00 | 0.143578E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| July | 0.00 | 0.158089E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| August | 0.00 | 0.156981E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| September | 0.00 | 0.142555E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| October | 0.00 | 0.115281E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| November | 53102004.49 | 0.684743E+09 | 0.00 | 369614.76 | 146544.18 | 0.00 | 36997689.60 | 0.00 | 0.36 |
| December | 0.154015E+09 | 0.318624E+09 | 0.00 | 792072.34 | 0.00 | 5492449.51 | 0.108332E+09 | 0.00 | 0.35 |
| Annual Sum or Average | 0.678852E+09 | 0.103971E+11 | 0.00 | 3832841.88 | 357384.86 | 27992092.24 | 0.424231E+09 | 0.00 | 0.36 |
| Minimum of Months | 0.00 | 0.179897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
| Maximum of Months | 0.205042E+09 | 0.158089E+10 | 0.00 | 1159570.55 | 179918.89 | 13623181.99 | 0.135683E+09 | 0.00 | 0.36 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 09:14:58
Custom Monthly Report| SITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
| January | 0.106227E+12 | 0.598004E+10 | 0.00 | 0.719667E+09 | 0.750983E+11 |
| February | 0.108921E+12 | 0.294776E+10 | 0.00 | 0.428822E+09 | 0.854372E+11 |
| March | 0.140288E+12 | 0.255660E+09 | 0.00 | 0.340304E+09 | 0.108837E+12 |
| April | 0.144858E+12 | -0.572699E+10 | 0.00 | 48772235.50 | 0.142214E+12 |
| May | 0.134869E+12 | -0.164849E+11 | 0.00 | -407490828.8 | 0.200684E+12 |
| June | 0.121127E+12 | -0.173484E+11 | 0.00 | -783290694.2 | 0.222640E+12 |
| July | 0.131157E+12 | -0.151628E+11 | 0.00 | -855757051.6 | 0.235759E+12 |
| August | 0.147052E+12 | -0.180851E+11 | 0.00 | -918289643.5 | 0.235428E+12 |
| September | 0.115445E+12 | -0.159834E+11 | 0.00 | -747481683.6 | 0.223694E+12 |
| October | 0.119664E+12 | -0.132282E+11 | 0.00 | -489810431.8 | 0.203818E+12 |
| November | 0.932806E+11 | -0.554356E+10 | 0.00 | -13894310.6 | 0.146254E+12 |
| December | 0.104414E+12 | 0.389887E+10 | 0.00 | 0.583189E+09 | 0.927822E+11 |
| Annual Sum or Average | 0.146730E+13 | -0.944810E+11 | 0.00 | -0.209526E+10 | 0.197265E+13 |
| Minimum of Months | 0.932806E+11 | -0.180851E+11 | 0.00 | -918289643.5 | 0.750983E+11 |
| Maximum of Months | 0.147052E+12 | 0.598004E+10 | 0.00 | 0.719667E+09 | 0.235759E+12 |