Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 09:14
Tabular Output Report in Format: HTML
Building: ApartmentMidRise
Environment: RUNPERIOD 1 ** Albuquerque Intl Sunport NM USA TMY3 WMO#=723650
Simulation Timestamp: 2023-10-16 09:14:27
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 09:14:27
Values gathered over 8760.00 hours| Total Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
| Total Site Energy | 1455.84 | 464.44 | 515.53 |
| Net Site Energy | 1455.84 | 464.44 | 515.53 |
| Total Source Energy | 4304.59 | 1373.25 | 1524.30 |
| Net Source Energy | 4304.59 | 1373.25 | 1524.30 |
| Site=>Source Conversion Factor | |
| Electricity | 3.167 |
| Natural Gas | 1.084 |
| District Cooling | 1.056 |
| District Heating | 3.613 |
| Steam | 1.200 |
| Gasoline | 1.050 |
| Diesel | 1.050 |
| Coal | 1.050 |
| Fuel Oil No 1 | 1.050 |
| Fuel Oil No 2 | 1.050 |
| Propane | 1.050 |
| Other Fuel 1 | 1.000 |
| Other Fuel 2 | 1.000 |
| Area [m2] | |
| Total Building Area | 3134.61 |
| Net Conditioned Building Area | 2823.98 |
| Unconditioned Building Area | 310.64 |
| Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
| Heating | 0.00 | 146.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Cooling | 151.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Lighting | 99.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Lighting | 50.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment | 458.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans | 106.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems | 442.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1875.32 |
| Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Total End Uses | 1308.91 | 146.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1875.32 |
| Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
| Heating | General | 0.00 | 146.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Cooling | General | 151.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Lighting | LightsWired | 94.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LightsPlugIn | 4.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Exterior Lighting | General | 50.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment | MiscPlug | 388.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| ElevatorLift | 65.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| ElevatorLightsFan | 5.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| General | 106.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems | Water Heater | 442.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1875.32 |
| Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
| Heating | Unassigned | 0.00 | 146.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Cooling | Unassigned | 151.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Lighting | GENERAL | 99.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Lighting | Unassigned | 50.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment | GENERAL | 458.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans | Unassigned | 106.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Pumps | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems | Unassigned | 442.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1875.32 |
| Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
| Lighting | 52.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| HVAC | 248.23 | 52.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.66 |
| Other | 162.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Total | 463.50 | 52.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.66 |
| Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
| Lighting | 47.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| HVAC | 223.63 | 46.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.60 |
| Other | 146.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Total | 417.57 | 46.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.60 |
| Electricity [GJ] | Percent Electricity [%] | |
| Fuel-Fired Power Generation | 0.000 | 0.00 |
| High Temperature Geothermal* | 0.000 | 0.00 |
| Photovoltaic Power | 0.000 | 0.00 |
| Wind Power | 0.000 | 0.00 |
| Power Conversion | 0.000 | 0.00 |
| Net Decrease in On-Site Storage | 0.000 | 0.00 |
| Total On-Site Electric Sources | 0.000 | 0.00 |
| Electricity Coming From Utility | 1308.913 | 100.00 |
| Surplus Electricity Going To Utility | 0.000 | 0.00 |
| Net Electricity From Utility | 1308.913 | 100.00 |
| Total On-Site and Utility Electric Sources | 1308.913 | 100.00 |
| Total Electricity End Uses | 1308.913 | 100.00 |
| Heat [GJ] | Percent Heat [%] | |
| Water-Side Heat Recovery | 0.00 | 0.00 |
| Air to Air Heat Recovery for Cooling | 0.00 | 50.54 |
| Air to Air Heat Recovery for Heating | 0.00 | 49.46 |
| High-Temperature Geothermal* | 0.00 | 0.00 |
| Solar Water Thermal | 0.00 | 0.00 |
| Solar Air Thermal | 0.00 | 0.00 |
| Total On-Site Thermal Sources | 0.00 | 100.00 |
| Water [m3] | Percent Water [%] | |
| Rainwater Collection | 0.00 | 0.00 |
| Condensate Collection | 0.00 | 0.00 |
| Groundwater Well | 0.00 | 0.00 |
| Total On Site Water Sources | 0.00 | 0.00 |
| - | - | - |
| Initial Storage | 0.00 | 0.00 |
| Final Storage | 0.00 | 0.00 |
| Change in Storage | 0.00 | 0.00 |
| - | - | - |
| Water Supplied by Utility | 1875.32 | 100.00 |
| - | - | - |
| Total On Site, Change in Storage, and Utility Water Sources | 1875.32 | 100.00 |
| Total Water End Uses | 1875.32 | 100.00 |
| Degrees [deltaC] | |
| Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
| Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
| Facility [Hours] | |
| Time Setpoint Not Met During Occupied Heating | 0.00 |
| Time Setpoint Not Met During Occupied Cooling | 0.00 |
| Time Not Comfortable Based on Simple ASHRAE 55-2004 | 8750.33 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2012
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME APARTMENTMIDRISE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4B
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NM_ALBUQUERQUE
| Environment |ZoneCoolingSummaryMonthly
| G SW APARTMENT | G NW APARTMENT | OFFICE | G NE APARTMENT | G N1 APARTMENT | G N2 APARTMENT | G S1 APARTMENT | G S2 APARTMENT | M SW APARTMENT | M NW APARTMENT | M SE APARTMENT | M NE APARTMENT | M N1 APARTMENT | M N2 APARTMENT | M S1 APARTMENT | M S2 APARTMENT | T SW APARTMENT | T NW APARTMENT | T SE APARTMENT | T NE APARTMENT | T N1 APARTMENT | T N2 APARTMENT | T S1 APARTMENT | T S2 APARTMENT | T CORRIDOR | G CORRIDOR | M CORRIDOR |ZoneHeatingSummaryMonthly
| G SW APARTMENT | G NW APARTMENT | OFFICE | G NE APARTMENT | G N1 APARTMENT | G N2 APARTMENT | G S1 APARTMENT | G S2 APARTMENT | M SW APARTMENT | M NW APARTMENT | M SE APARTMENT | M NE APARTMENT | M N1 APARTMENT | M N2 APARTMENT | M S1 APARTMENT | M S2 APARTMENT | T SW APARTMENT | T NW APARTMENT | T SE APARTMENT | T NE APARTMENT | T N1 APARTMENT | T N2 APARTMENT | T S1 APARTMENT | T S2 APARTMENT | T CORRIDOR | G CORRIDOR | M CORRIDOR |ZoneElectricSummaryMonthly
| G SW APARTMENT | G NW APARTMENT | OFFICE | G NE APARTMENT | G N1 APARTMENT | G N2 APARTMENT | G S1 APARTMENT | G S2 APARTMENT | M SW APARTMENT | M NW APARTMENT | M SE APARTMENT | M NE APARTMENT | M N1 APARTMENT | M N2 APARTMENT | M S1 APARTMENT | M S2 APARTMENT | T SW APARTMENT | T NW APARTMENT | T SE APARTMENT | T NE APARTMENT | T N1 APARTMENT | T N2 APARTMENT | T S1 APARTMENT | T S2 APARTMENT | T CORRIDOR | G CORRIDOR | M CORRIDOR |SpaceGainsMonthly
| G SW APARTMENT | G NW APARTMENT | OFFICE | G NE APARTMENT | G N1 APARTMENT | G N2 APARTMENT | G S1 APARTMENT | G S2 APARTMENT | M SW APARTMENT | M NW APARTMENT | M SE APARTMENT | M NE APARTMENT | M N1 APARTMENT | M N2 APARTMENT | M S1 APARTMENT | M S2 APARTMENT | T SW APARTMENT | T NW APARTMENT | T SE APARTMENT | T NE APARTMENT | T N1 APARTMENT | T N2 APARTMENT | T S1 APARTMENT | T S2 APARTMENT | T CORRIDOR | G CORRIDOR | M CORRIDOR |PeakSpaceGainsMonthly
| G SW APARTMENT | G NW APARTMENT | OFFICE | G NE APARTMENT | G N1 APARTMENT | G N2 APARTMENT | G S1 APARTMENT | G S2 APARTMENT | M SW APARTMENT | M NW APARTMENT | M SE APARTMENT | M NE APARTMENT | M N1 APARTMENT | M N2 APARTMENT | M S1 APARTMENT | M S2 APARTMENT | T SW APARTMENT | T NW APARTMENT | T SE APARTMENT | T NE APARTMENT | T N1 APARTMENT | T N2 APARTMENT | T S1 APARTMENT | T S2 APARTMENT | T CORRIDOR | G CORRIDOR | M CORRIDOR |SpaceGainComponentsAtCoolingPeakMonthly
| G SW APARTMENT | G NW APARTMENT | OFFICE | G NE APARTMENT | G N1 APARTMENT | G N2 APARTMENT | G S1 APARTMENT | G S2 APARTMENT | M SW APARTMENT | M NW APARTMENT | M SE APARTMENT | M NE APARTMENT | M N1 APARTMENT | M N2 APARTMENT | M S1 APARTMENT | M S2 APARTMENT | T SW APARTMENT | T NW APARTMENT | T SE APARTMENT | T NE APARTMENT | T N1 APARTMENT | T N2 APARTMENT | T S1 APARTMENT | T S2 APARTMENT | T CORRIDOR | G CORRIDOR | M CORRIDOR |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| G SW APARTMENT | G NW APARTMENT | OFFICE | G NE APARTMENT | G N1 APARTMENT | G N2 APARTMENT | G S1 APARTMENT | G S2 APARTMENT | M SW APARTMENT | M NW APARTMENT | M SE APARTMENT | M NE APARTMENT | M N1 APARTMENT | M N2 APARTMENT | M S1 APARTMENT | M S2 APARTMENT | T SW APARTMENT | T NW APARTMENT | T SE APARTMENT | T NE APARTMENT | T N1 APARTMENT | T N2 APARTMENT | T S1 APARTMENT | T S2 APARTMENT | T CORRIDOR | G CORRIDOR | M CORRIDOR |ComfortReportSimple55Monthly
| G SW APARTMENT | G NW APARTMENT | OFFICE | G NE APARTMENT | G N1 APARTMENT | G N2 APARTMENT | G S1 APARTMENT | G S2 APARTMENT | M SW APARTMENT | M NW APARTMENT | M SE APARTMENT | M NE APARTMENT | M N1 APARTMENT | M N2 APARTMENT | M S1 APARTMENT | M S2 APARTMENT | T SW APARTMENT | T NW APARTMENT | T SE APARTMENT | T NE APARTMENT | T N1 APARTMENT | T N2 APARTMENT | T S1 APARTMENT | T S2 APARTMENT | T CORRIDOR | G CORRIDOR | M CORRIDOR |OccupantComfortDataSummaryMonthly
| OCCUP_GSW | OCCUP_GNW | OCCUP_OFFICE | OCCUP_GNE | OCCUP_GN1 | OCCUP_GN2 | OCCUP_GS1 | OCCUP_GS2 | OCCUP_MSW | OCCUP_MNW | OCCUP_MSE | OCCUP_MNE | OCCUP_MN1 | OCCUP_MN2 | OCCUP_MS1 | OCCUP_MS2 | OCCUP_TSW | OCCUP_TNW | OCCUP_TSE | OCCUP_TNE | OCCUP_TN1 | OCCUP_TN2 | OCCUP_TS1 | OCCUP_TS2 | OCCUP_T CORRIDOR | OCCUP_G CORRIDOR | OCCUP_M CORRIDOR |DXReportMonthly
| SPLIT GSW COOLING COIL | SPLIT GNW COOLING COIL | SPLIT OFFICE COOLING COIL | SPLIT GNE COOLING COIL | SPLIT GN1 COOLING COIL | SPLIT GN2 COOLING COIL | SPLIT GS1 COOLING COIL | SPLIT GS2 COOLING COIL | SPLIT MSW COOLING COIL | SPLIT MNW COOLING COIL | SPLIT MSE COOLING COIL | SPLIT MNE COOLING COIL | SPLIT MN1 COOLING COIL | SPLIT MN2 COOLING COIL | SPLIT MS1 COOLING COIL | SPLIT MS2 COOLING COIL | SPLIT TSW COOLING COIL | SPLIT TNW COOLING COIL | SPLIT TSE COOLING COIL | SPLIT TNE COOLING COIL | SPLIT TN1 COOLING COIL | SPLIT TN2 COOLING COIL | SPLIT TS1 COOLING COIL | SPLIT TS2 COOLING COIL |WindowReportMonthly
| GWINDOW1 S SWA | GWINDOW1 W SWA | GWINDOW1 W NWA | GWINDOW1 N NWA | GWINDOW1 S SEA | GWINDOW1 E SEA | GWINDOW1 E NEA | GWINDOW1 N NEA | GWINDOW1 N N1A | GWINDOW1 N N2A | GWINDOW1 S S1A | GWINDOW1 S S2A | MWINDOW1 S SWA | MWINDOW1 W SWA | MWINDOW1 W NWA | MWINDOW1 N NWA | MWINDOW1 S SEA | MWINDOW1 E SEA | MWINDOW1 E NEA | MWINDOW1 N NEA | MWINDOW1 N N1A | MWINDOW1 N N2A | MWINDOW1 S S1A | MWINDOW1 S S2A | TWINDOW1 S SWA | TWINDOW1 W SWA | TWINDOW1 W NWA | TWINDOW1 N NWA | TWINDOW1 S SEA | TWINDOW1 E SEA | TWINDOW1 E NEA | TWINDOW1 N NEA | TWINDOW1 N N1A | TWINDOW1 N N2A | TWINDOW1 S S1A | TWINDOW1 S S2A | TWINDOW14 | ENTRANCE DOOR | MWINDOW14 |WindowEnergyReportMonthly
| GWINDOW1 S SWA | GWINDOW1 W SWA | GWINDOW1 W NWA | GWINDOW1 N NWA | GWINDOW1 S SEA | GWINDOW1 E SEA | GWINDOW1 E NEA | GWINDOW1 N NEA | GWINDOW1 N N1A | GWINDOW1 N N2A | GWINDOW1 S S1A | GWINDOW1 S S2A | MWINDOW1 S SWA | MWINDOW1 W SWA | MWINDOW1 W NWA | MWINDOW1 N NWA | MWINDOW1 S SEA | MWINDOW1 E SEA | MWINDOW1 E NEA | MWINDOW1 N NEA | MWINDOW1 N N1A | MWINDOW1 N N2A | MWINDOW1 S S1A | MWINDOW1 S S2A | TWINDOW1 S SWA | TWINDOW1 W SWA | TWINDOW1 W NWA | TWINDOW1 N NWA | TWINDOW1 S SEA | TWINDOW1 E SEA | TWINDOW1 E NEA | TWINDOW1 N NEA | TWINDOW1 N N1A | TWINDOW1 N N2A | TWINDOW1 S S1A | TWINDOW1 S S2A | TWINDOW14 | ENTRANCE DOOR | MWINDOW14 |WindowZoneSummaryMonthly
| G SW APARTMENT | G NW APARTMENT | OFFICE | G NE APARTMENT | G N1 APARTMENT | G N2 APARTMENT | G S1 APARTMENT | G S2 APARTMENT | M SW APARTMENT | M NW APARTMENT | M SE APARTMENT | M NE APARTMENT | M N1 APARTMENT | M N2 APARTMENT | M S1 APARTMENT | M S2 APARTMENT | T SW APARTMENT | T NW APARTMENT | T SE APARTMENT | T NE APARTMENT | T N1 APARTMENT | T N2 APARTMENT | T S1 APARTMENT | T S2 APARTMENT | T CORRIDOR | G CORRIDOR | M CORRIDOR |WindowEnergyZoneSummaryMonthly
| G SW APARTMENT | G NW APARTMENT | OFFICE | G NE APARTMENT | G N1 APARTMENT | G N2 APARTMENT | G S1 APARTMENT | G S2 APARTMENT | M SW APARTMENT | M NW APARTMENT | M SE APARTMENT | M NE APARTMENT | M N1 APARTMENT | M N2 APARTMENT | M S1 APARTMENT | M S2 APARTMENT | T SW APARTMENT | T NW APARTMENT | T SE APARTMENT | T NE APARTMENT | T N1 APARTMENT | T N2 APARTMENT | T S1 APARTMENT | T S2 APARTMENT | T CORRIDOR | G CORRIDOR | M CORRIDOR |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| G SW APARTMENT WATER HEATER | G NW APARTMENT WATER HEATER | G NE APARTMENT WATER HEATER | G N1 APARTMENT WATER HEATER | G N2 APARTMENT WATER HEATER | G S1 APARTMENT WATER HEATER | G S2 APARTMENT WATER HEATER | M SW APARTMENT WATER HEATER | M NW APARTMENT WATER HEATER | M SE APARTMENT WATER HEATER | M NE APARTMENT WATER HEATER | M N1 APARTMENT WATER HEATER | M N2 APARTMENT WATER HEATER | M S1 APARTMENT WATER HEATER | M S2 APARTMENT WATER HEATER | T SW APARTMENT WATER HEATER | T NW APARTMENT WATER HEATER | T SE APARTMENT WATER HEATER | T NE APARTMENT WATER HEATER | T N1 APARTMENT WATER HEATER | T N2 APARTMENT WATER HEATER | T S1 APARTMENT WATER HEATER | T S2 APARTMENT WATER HEATER |DaylightingReportMonthly
| Environment |CoilReportMonthly
| SPLIT GSW HEATING COIL | SPLIT GNW HEATING COIL | SPLIT OFFICE HEATING COIL | SPLIT GNE HEATING COIL | SPLIT GN1 HEATING COIL | SPLIT GN2 HEATING COIL | SPLIT GS1 HEATING COIL | SPLIT GS2 HEATING COIL | SPLIT MSW HEATING COIL | SPLIT MNW HEATING COIL | SPLIT MSE HEATING COIL | SPLIT MNE HEATING COIL | SPLIT MN1 HEATING COIL | SPLIT MN2 HEATING COIL | SPLIT MS1 HEATING COIL | SPLIT MS2 HEATING COIL | SPLIT TSW HEATING COIL | SPLIT TNW HEATING COIL | SPLIT TSE HEATING COIL | SPLIT TNE HEATING COIL | SPLIT TN1 HEATING COIL | SPLIT TN2 HEATING COIL | SPLIT TS1 HEATING COIL | SPLIT TS2 HEATING COIL | SPLIT GSW COOLING COIL | SPLIT GNW COOLING COIL | SPLIT OFFICE COOLING COIL | SPLIT GNE COOLING COIL | SPLIT GN1 COOLING COIL | SPLIT GN2 COOLING COIL | SPLIT GS1 COOLING COIL | SPLIT GS2 COOLING COIL | SPLIT MSW COOLING COIL | SPLIT MNW COOLING COIL | SPLIT MSE COOLING COIL | SPLIT MNE COOLING COIL | SPLIT MN1 COOLING COIL | SPLIT MN2 COOLING COIL | SPLIT MS1 COOLING COIL | SPLIT MS2 COOLING COIL | SPLIT TSW COOLING COIL | SPLIT TNW COOLING COIL | SPLIT TSE COOLING COIL | SPLIT TNE COOLING COIL | SPLIT TN1 COOLING COIL | SPLIT TN2 COOLING COIL | SPLIT TS1 COOLING COIL | SPLIT TS2 COOLING COIL |FanReportMonthly
| SPLIT GSW SUPPLY FAN | G SW APARTMENT ERV SUP FAN | G SW APARTMENT ERV EXH FAN | SPLIT GNW SUPPLY FAN | G NW APARTMENT ERV SUP FAN | G NW APARTMENT ERV EXH FAN | SPLIT OFFICE SUPPLY FAN | SPLIT GNE SUPPLY FAN | G NE APARTMENT ERV SUP FAN | G NE APARTMENT ERV EXH FAN | SPLIT GN1 SUPPLY FAN | G N1 APARTMENT ERV SUP FAN | G N1 APARTMENT ERV EXH FAN | SPLIT GN2 SUPPLY FAN | G N2 APARTMENT ERV SUP FAN | G N2 APARTMENT ERV EXH FAN | SPLIT GS1 SUPPLY FAN | G S1 APARTMENT ERV SUP FAN | G S1 APARTMENT ERV EXH FAN | SPLIT GS2 SUPPLY FAN | G S2 APARTMENT ERV SUP FAN | G S2 APARTMENT ERV EXH FAN | SPLIT MSW SUPPLY FAN | M SW APARTMENT ERV SUP FAN | M SW APARTMENT ERV EXH FAN | SPLIT MNW SUPPLY FAN | M NW APARTMENT ERV SUP FAN | M NW APARTMENT ERV EXH FAN | SPLIT MSE SUPPLY FAN | M SE APARTMENT ERV SUP FAN | M SE APARTMENT ERV EXH FAN | SPLIT MNE SUPPLY FAN | M NE APARTMENT ERV SUP FAN | M NE APARTMENT ERV EXH FAN | SPLIT MN1 SUPPLY FAN | M N1 APARTMENT ERV SUP FAN | M N1 APARTMENT ERV EXH FAN | SPLIT MN2 SUPPLY FAN | M N2 APARTMENT ERV SUP FAN | M N2 APARTMENT ERV EXH FAN | SPLIT MS1 SUPPLY FAN | M S1 APARTMENT ERV SUP FAN | M S1 APARTMENT ERV EXH FAN | SPLIT MS2 SUPPLY FAN | M S2 APARTMENT ERV SUP FAN | M S2 APARTMENT ERV EXH FAN | SPLIT TSW SUPPLY FAN | T SW APARTMENT ERV SUP FAN | T SW APARTMENT ERV EXH FAN | SPLIT TNW SUPPLY FAN | T NW APARTMENT ERV SUP FAN | T NW APARTMENT ERV EXH FAN | SPLIT TSE SUPPLY FAN | T SE APARTMENT ERV SUP FAN | T SE APARTMENT ERV EXH FAN | SPLIT TNE SUPPLY FAN | T NE APARTMENT ERV SUP FAN | T NE APARTMENT ERV EXH FAN | SPLIT TN1 SUPPLY FAN | T N1 APARTMENT ERV SUP FAN | T N1 APARTMENT ERV EXH FAN | SPLIT TN2 SUPPLY FAN | T N2 APARTMENT ERV SUP FAN | T N2 APARTMENT ERV EXH FAN | SPLIT TS1 SUPPLY FAN | T S1 APARTMENT ERV SUP FAN | T S1 APARTMENT ERV EXH FAN | SPLIT TS2 SUPPLY FAN | T S2 APARTMENT ERV SUP FAN | T S2 APARTMENT ERV EXH FAN |ZoneTemperatureOscillationReportMonthly
| G SW APARTMENT | G NW APARTMENT | OFFICE | G NE APARTMENT | G N1 APARTMENT | G N2 APARTMENT | G S1 APARTMENT | G S2 APARTMENT | M SW APARTMENT | M NW APARTMENT | M SE APARTMENT | M NE APARTMENT | M N1 APARTMENT | M N2 APARTMENT | M S1 APARTMENT | M S2 APARTMENT | T SW APARTMENT | T NW APARTMENT | T SE APARTMENT | T NE APARTMENT | T N1 APARTMENT | T N2 APARTMENT | T S1 APARTMENT | T S2 APARTMENT | T CORRIDOR | G CORRIDOR | M CORRIDOR |AirLoopSystemEnergyAndWaterUseMonthly
| SPLIT GSW | SPLIT GNW | SPLIT OFFICE | SPLIT GNE | SPLIT GN1 | SPLIT GN2 | SPLIT GS1 | SPLIT GS2 | SPLIT MSW | SPLIT MNW | SPLIT MSE | SPLIT MNE | SPLIT MN1 | SPLIT MN2 | SPLIT MS1 | SPLIT MS2 | SPLIT TSW | SPLIT TNW | SPLIT TSE | SPLIT TNE | SPLIT TN1 | SPLIT TN2 | SPLIT TS1 | SPLIT TS2 |AirLoopSystemComponentLoadsMonthly
| SPLIT GSW | SPLIT GNW | SPLIT OFFICE | SPLIT GNE | SPLIT GN1 | SPLIT GN2 | SPLIT GS1 | SPLIT GS2 | SPLIT MSW | SPLIT MNW | SPLIT MSE | SPLIT MNE | SPLIT MN1 | SPLIT MN2 | SPLIT MS1 | SPLIT MS2 | SPLIT TSW | SPLIT TNW | SPLIT TSE | SPLIT TNE | SPLIT TN1 | SPLIT TN2 | SPLIT TS1 | SPLIT TS2 |AirLoopSystemComponentEnergyUseMonthly
| SPLIT GSW | SPLIT GNW | SPLIT OFFICE | SPLIT GNE | SPLIT GN1 | SPLIT GN2 | SPLIT GS1 | SPLIT GS2 | SPLIT MSW | SPLIT MNW | SPLIT MSE | SPLIT MNE | SPLIT MN1 | SPLIT MN2 | SPLIT MS1 | SPLIT MS2 | SPLIT TSW | SPLIT TNW | SPLIT TSE | SPLIT TNE | SPLIT TN1 | SPLIT TN2 | SPLIT TS1 | SPLIT TS2 |MechanicalVentilationLoadsMonthly
| G SW APARTMENT | G NW APARTMENT | OFFICE | G NE APARTMENT | G N1 APARTMENT | G N2 APARTMENT | G S1 APARTMENT | G S2 APARTMENT | M SW APARTMENT | M NW APARTMENT | M SE APARTMENT | M NE APARTMENT | M N1 APARTMENT | M N2 APARTMENT | M S1 APARTMENT | M S2 APARTMENT | T SW APARTMENT | T NW APARTMENT | T SE APARTMENT | T NE APARTMENT | T N1 APARTMENT | T N2 APARTMENT | T S1 APARTMENT | T S2 APARTMENT |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 09:14:27
General| Value | |
| Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 09:14 |
| RunPeriod | RUNPERIOD 1 |
| Weather File | Albuquerque Intl Sunport NM USA TMY3 WMO#=723650 |
| Latitude [deg] | 35.04 |
| Longitude [deg] | -106.6 |
| Elevation [m] | 1619.00 |
| Time Zone | -7.0 |
| North Axis Angle [deg] | 0.00 |
| Rotation for Appendix G [deg] | 0.00 |
| Hours Simulated [hrs] | 8760.00 |
| Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
| Gross Wall Area [m2] | 1542.04 | 564.80 | 206.22 | 564.80 | 206.22 |
| Above Ground Wall Area [m2] | 1542.04 | 564.80 | 206.22 | 564.80 | 206.22 |
| Window Opening Area [m2] | 306.92 | 112.97 | 43.82 | 112.97 | 37.16 |
| Gross Window-Wall Ratio [%] | 19.90 | 20.00 | 21.25 | 20.00 | 18.02 |
| Above Ground Window-Wall Ratio [%] | 19.90 | 20.00 | 21.25 | 20.00 | 18.02 |
| Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
| Gross Wall Area [m2] | 1501.17 | 564.80 | 185.79 | 564.80 | 185.79 |
| Above Ground Wall Area [m2] | 1501.17 | 564.80 | 185.79 | 564.80 | 185.79 |
| Window Opening Area [m2] | 300.26 | 112.97 | 37.16 | 112.97 | 37.16 |
| Gross Window-Wall Ratio [%] | 20.00 | 20.00 | 20.00 | 20.00 | 20.00 |
| Above Ground Window-Wall Ratio [%] | 20.00 | 20.00 | 20.00 | 20.00 | 20.00 |
| Total | |
| Gross Roof Area [m2] | 783.65 |
| Skylight Area [m2] | 0.00 |
| Skylight-Roof Ratio [%] | 0.00 |
| Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
| G SW APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 0.00 | 11.71 | 11.71 | 8.6918 | 35.30 | 6.6700 |
| G NW APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 0.00 | 11.71 | 11.71 | 8.6918 | 35.30 | 6.6700 |
| OFFICE | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 0.00 | 11.71 | 11.71 | 9.7532 | 18.58 | 6.6700 |
| G NE APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 0.00 | 11.71 | 11.71 | 8.6918 | 35.30 | 6.6700 |
| G N1 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 0.00 | 7.06 | 7.06 | 8.6918 | 35.30 | 6.6700 |
| G N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 0.00 | 7.06 | 7.06 | 8.6918 | 35.30 | 6.6700 |
| G S1 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 0.00 | 7.06 | 7.06 | 8.6918 | 35.30 | 6.6700 |
| G S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 0.00 | 7.06 | 7.06 | 8.6918 | 35.30 | 6.6700 |
| M SW APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 58.52 | 0.00 | 11.71 | 11.71 | 8.6918 | 35.30 | 6.6700 |
| M NW APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 58.52 | 0.00 | 11.71 | 11.71 | 8.6918 | 35.30 | 6.6700 |
| M SE APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 58.52 | 0.00 | 11.71 | 11.71 | 8.6918 | 35.30 | 6.6700 |
| M NE APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 58.52 | 0.00 | 11.71 | 11.71 | 8.6918 | 35.30 | 6.6700 |
| M N1 APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 35.30 | 0.00 | 7.06 | 7.06 | 8.6918 | 35.30 | 6.6700 |
| M N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 35.30 | 0.00 | 7.06 | 7.06 | 8.6918 | 35.30 | 6.6700 |
| M S1 APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 35.30 | 0.00 | 7.06 | 7.06 | 8.6918 | 35.30 | 6.6700 |
| M S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 35.30 | 0.00 | 7.06 | 7.06 | 8.6918 | 35.30 | 6.6700 |
| T SW APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 0.00 | 11.71 | 11.71 | 8.6918 | 35.30 | 6.6700 |
| T NW APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 0.00 | 11.71 | 11.71 | 8.6918 | 35.30 | 6.6700 |
| T SE APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 0.00 | 11.71 | 11.71 | 8.6918 | 35.30 | 6.6700 |
| T NE APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 0.00 | 11.71 | 11.71 | 8.6918 | 35.30 | 6.6700 |
| T N1 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 0.00 | 7.06 | 7.06 | 8.6918 | 35.30 | 6.6700 |
| T N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 0.00 | 7.06 | 7.06 | 8.6918 | 35.30 | 6.6700 |
| T S1 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 0.00 | 7.06 | 7.06 | 8.6918 | 35.30 | 6.6700 |
| T S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 0.00 | 7.06 | 7.06 | 8.6918 | 35.30 | 6.6700 |
| T CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 0.00 | 1.11 | 1.11 | 4.7725 | 18.58 | 0.0000 |
| G CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 0.00 | 3.32 | 3.32 | 4.7725 | 18.58 | 105.2565 |
| M CORRIDOR | 77.66 | No | Yes | 236.69 | 2.00 | 10.22 | 0.00 | 1.11 | 1.11 | 4.7725 | 18.58 | 0.0000 |
| Total | 3134.61 | 9553.84 | 1542.04 | 0.00 | 306.92 | 306.92 | 8.3333 | 31.67 | 8.6167 | |||
| Conditioned Total | 2823.98 | 8607.06 | 1501.17 | 0.00 | 300.26 | 300.26 | 8.7250 | 34.33 | 6.6700 | |||
| Unconditioned Total | 310.64 | 946.78 | 40.87 | 0.00 | 6.66 | 6.66 | 4.7725 | 18.58 | 26.3141 | |||
| Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
| G SW APARTMENT | 88.25 | Yes | Yes | 1.00 | G SW APARTMENT | GENERAL | G SW APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| G NW APARTMENT | 88.25 | Yes | Yes | 1.00 | G NW APARTMENT | GENERAL | G NW APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| OFFICE | 88.25 | Yes | Yes | 1.00 | OFFICE | GENERAL | OFFICE | 9.7532 | 18.58 | 6.6700 | |
| G NE APARTMENT | 88.25 | Yes | Yes | 1.00 | G NE APARTMENT | GENERAL | G NE APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| G N1 APARTMENT | 88.25 | Yes | Yes | 1.00 | G N1 APARTMENT | GENERAL | G N1 APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| G N2 APARTMENT | 88.25 | Yes | Yes | 1.00 | G N2 APARTMENT | GENERAL | G N2 APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| G S1 APARTMENT | 88.25 | Yes | Yes | 1.00 | G S1 APARTMENT | GENERAL | G S1 APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| G S2 APARTMENT | 88.25 | Yes | Yes | 1.00 | G S2 APARTMENT | GENERAL | G S2 APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| M SW APARTMENT | 88.25 | Yes | Yes | 2.00 | M SW APARTMENT | GENERAL | M SW APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| M NW APARTMENT | 88.25 | Yes | Yes | 2.00 | M NW APARTMENT | GENERAL | M NW APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| M SE APARTMENT | 88.25 | Yes | Yes | 2.00 | M SE APARTMENT | GENERAL | M SE APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| M NE APARTMENT | 88.25 | Yes | Yes | 2.00 | M NE APARTMENT | GENERAL | M NE APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| M N1 APARTMENT | 88.25 | Yes | Yes | 2.00 | M N1 APARTMENT | GENERAL | M N1 APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| M N2 APARTMENT | 88.25 | Yes | Yes | 2.00 | M N2 APARTMENT | GENERAL | M N2 APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| M S1 APARTMENT | 88.25 | Yes | Yes | 2.00 | M S1 APARTMENT | GENERAL | M S1 APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| M S2 APARTMENT | 88.25 | Yes | Yes | 2.00 | M S2 APARTMENT | GENERAL | M S2 APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| T SW APARTMENT | 88.25 | Yes | Yes | 1.00 | T SW APARTMENT | GENERAL | T SW APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| T NW APARTMENT | 88.25 | Yes | Yes | 1.00 | T NW APARTMENT | GENERAL | T NW APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| T SE APARTMENT | 88.25 | Yes | Yes | 1.00 | T SE APARTMENT | GENERAL | T SE APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| T NE APARTMENT | 88.25 | Yes | Yes | 1.00 | T NE APARTMENT | GENERAL | T NE APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| T N1 APARTMENT | 88.25 | Yes | Yes | 1.00 | T N1 APARTMENT | GENERAL | T N1 APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| T N2 APARTMENT | 88.25 | Yes | Yes | 1.00 | T N2 APARTMENT | GENERAL | T N2 APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| T S1 APARTMENT | 88.25 | Yes | Yes | 1.00 | T S1 APARTMENT | GENERAL | T S1 APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| T S2 APARTMENT | 88.25 | Yes | Yes | 1.00 | T S2 APARTMENT | GENERAL | T S2 APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| T CORRIDOR | 77.66 | No | Yes | 1.00 | T CORRIDOR | GENERAL | T CORRIDOR | 4.7725 | 18.58 | 0.0000 | |
| G CORRIDOR | 77.66 | No | Yes | 1.00 | G CORRIDOR | GENERAL | G CORRIDOR | 4.7725 | 18.58 | 105.2565 | |
| M CORRIDOR | 77.66 | No | Yes | 2.00 | M CORRIDOR | GENERAL | M CORRIDOR | 4.7725 | 18.58 | 0.0000 | |
| Total | 3134.61 | 8.3333 | 15.84 | 8.6167 | |||||||
| Conditioned Total | 2823.98 | 8.7250 | 17.17 | 6.6700 | |||||||
| Unconditioned Total | 310.64 | 4.7725 | 9.29 | 26.3141 | |||||||
| Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
| Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
| GENERAL | 3134.61 | 2823.98 | 310.64 | 0.00 | 6.2575 | 41.91 | 7.1145 |
| Total | 3134.61 | 2823.98 | 310.64 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 09:14:27
End Uses| Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
| Time of Peak | 20-AUG-17:10 | 06-FEB-04:00 | - | - | - | - | - | - | - | - | - | - | 01-JAN-07:10 |
| Heating | 0.00 | 54300.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Cooling | 24370.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Lighting | 5231.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment | 22609.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans | 8736.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems | 29341.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Total End Uses | 90289.92 | 54300.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
| Heating | General | 0.00 | 54300.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Cooling | General | 24370.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Lighting | LightsWired | 4887.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LightsPlugIn | 344.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment | MiscPlug | 18441.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| ElevatorLift | 4006.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| ElevatorLightsFan | 162.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| General | 8736.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems | Water Heater | 29341.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 09:14:27
Values gathered over 8760.00 hours| Source Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
| Heating | 0.00 | 159.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Cooling | 478.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Lighting | 314.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Lighting | 158.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment | 1452.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans | 338.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems | 1402.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Total Source Energy End Use Components | 4145.33 | 159.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
| Heating | 0.00 | 56.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Cooling | 169.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Lighting | 111.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Lighting | 56.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment | 514.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans | 119.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems | 496.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Total Source Energy End Use Components | 1467.90 | 56.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
| Heating | 0.00 | 50.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Cooling | 152.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Lighting | 100.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Lighting | 50.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment | 463.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans | 107.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems | 447.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Total Source Energy End Use Components | 1322.44 | 50.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 09:14:27
ZoneHVAC:EnergyRecoveryVentilator| User-Specified Supply Air Flow Rate [m3/s] | User-Specified Exhaust Air Flow Rate [m3/s] | |
| G SW APARTMENT ERV | 0.025955 | 0.025955 |
| G NW APARTMENT ERV | 0.025955 | 0.025955 |
| G NE APARTMENT ERV | 0.025955 | 0.025955 |
| G N1 APARTMENT ERV | 0.025955 | 0.025955 |
| G N2 APARTMENT ERV | 0.025955 | 0.025955 |
| G S1 APARTMENT ERV | 0.025955 | 0.025955 |
| G S2 APARTMENT ERV | 0.025955 | 0.025955 |
| M SW APARTMENT ERV | 0.051909 | 0.051909 |
| M NW APARTMENT ERV | 0.051909 | 0.051909 |
| M SE APARTMENT ERV | 0.051909 | 0.051909 |
| M NE APARTMENT ERV | 0.051909 | 0.051909 |
| M N1 APARTMENT ERV | 0.051909 | 0.051909 |
| M N2 APARTMENT ERV | 0.051909 | 0.051909 |
| M S1 APARTMENT ERV | 0.051909 | 0.051909 |
| M S2 APARTMENT ERV | 0.051909 | 0.051909 |
| T SW APARTMENT ERV | 0.025955 | 0.025955 |
| T NW APARTMENT ERV | 0.025955 | 0.025955 |
| T SE APARTMENT ERV | 0.025955 | 0.025955 |
| T NE APARTMENT ERV | 0.025955 | 0.025955 |
| T N1 APARTMENT ERV | 0.025955 | 0.025955 |
| T N2 APARTMENT ERV | 0.025955 | 0.025955 |
| T S1 APARTMENT ERV | 0.025955 | 0.025955 |
| T S2 APARTMENT ERV | 0.025955 | 0.025955 |
| Design Size Maximum Flow Rate [m3/s] | |
| G SW APARTMENT ERV SUP FAN | 0.025955 |
| G SW APARTMENT ERV EXH FAN | 0.025955 |
| G NW APARTMENT ERV SUP FAN | 0.025955 |
| G NW APARTMENT ERV EXH FAN | 0.025955 |
| G NE APARTMENT ERV SUP FAN | 0.025955 |
| G NE APARTMENT ERV EXH FAN | 0.025955 |
| G N1 APARTMENT ERV SUP FAN | 0.025955 |
| G N1 APARTMENT ERV EXH FAN | 0.025955 |
| G N2 APARTMENT ERV SUP FAN | 0.025955 |
| G N2 APARTMENT ERV EXH FAN | 0.025955 |
| G S1 APARTMENT ERV SUP FAN | 0.025955 |
| G S1 APARTMENT ERV EXH FAN | 0.025955 |
| G S2 APARTMENT ERV SUP FAN | 0.025955 |
| G S2 APARTMENT ERV EXH FAN | 0.025955 |
| M SW APARTMENT ERV SUP FAN | 0.051909 |
| M SW APARTMENT ERV EXH FAN | 0.051909 |
| M NW APARTMENT ERV SUP FAN | 0.051909 |
| M NW APARTMENT ERV EXH FAN | 0.051909 |
| M SE APARTMENT ERV SUP FAN | 0.051909 |
| M SE APARTMENT ERV EXH FAN | 0.051909 |
| M NE APARTMENT ERV SUP FAN | 0.051909 |
| M NE APARTMENT ERV EXH FAN | 0.051909 |
| M N1 APARTMENT ERV SUP FAN | 0.051909 |
| M N1 APARTMENT ERV EXH FAN | 0.051909 |
| M N2 APARTMENT ERV SUP FAN | 0.051909 |
| M N2 APARTMENT ERV EXH FAN | 0.051909 |
| M S1 APARTMENT ERV SUP FAN | 0.051909 |
| M S1 APARTMENT ERV EXH FAN | 0.051909 |
| M S2 APARTMENT ERV SUP FAN | 0.051909 |
| M S2 APARTMENT ERV EXH FAN | 0.051909 |
| T SW APARTMENT ERV SUP FAN | 0.025955 |
| T SW APARTMENT ERV EXH FAN | 0.025955 |
| T NW APARTMENT ERV SUP FAN | 0.025955 |
| T NW APARTMENT ERV EXH FAN | 0.025955 |
| T SE APARTMENT ERV SUP FAN | 0.025955 |
| T SE APARTMENT ERV EXH FAN | 0.025955 |
| T NE APARTMENT ERV SUP FAN | 0.025955 |
| T NE APARTMENT ERV EXH FAN | 0.025955 |
| T N1 APARTMENT ERV SUP FAN | 0.025955 |
| T N1 APARTMENT ERV EXH FAN | 0.025955 |
| T N2 APARTMENT ERV SUP FAN | 0.025955 |
| T N2 APARTMENT ERV EXH FAN | 0.025955 |
| T S1 APARTMENT ERV SUP FAN | 0.025955 |
| T S1 APARTMENT ERV EXH FAN | 0.025955 |
| T S2 APARTMENT ERV SUP FAN | 0.025955 |
| T S2 APARTMENT ERV EXH FAN | 0.025955 |
| SPLIT GSW SUPPLY FAN | 0.415565 |
| SPLIT GNW SUPPLY FAN | 0.407833 |
| SPLIT OFFICE SUPPLY FAN | 0.470352 |
| SPLIT GNE SUPPLY FAN | 0.372356 |
| SPLIT GN1 SUPPLY FAN | 0.331984 |
| SPLIT GN2 SUPPLY FAN | 0.331287 |
| SPLIT GS1 SUPPLY FAN | 0.342157 |
| SPLIT GS2 SUPPLY FAN | 0.344592 |
| SPLIT MSW SUPPLY FAN | 1.00 |
| SPLIT MNW SUPPLY FAN | 0.993924 |
| SPLIT MSE SUPPLY FAN | 0.899288 |
| SPLIT MNE SUPPLY FAN | 0.890667 |
| SPLIT MN1 SUPPLY FAN | 0.791657 |
| SPLIT MN2 SUPPLY FAN | 0.789628 |
| SPLIT MS1 SUPPLY FAN | 0.804358 |
| SPLIT MS2 SUPPLY FAN | 0.802259 |
| SPLIT TSW SUPPLY FAN | 0.559358 |
| SPLIT TNW SUPPLY FAN | 0.564333 |
| SPLIT TSE SUPPLY FAN | 0.482752 |
| SPLIT TNE SUPPLY FAN | 0.487516 |
| SPLIT TN1 SUPPLY FAN | 0.452140 |
| SPLIT TN2 SUPPLY FAN | 0.449489 |
| SPLIT TS1 SUPPLY FAN | 0.448234 |
| SPLIT TS2 SUPPLY FAN | 0.445595 |
| Design Size Nominal Supply Air Flow Rate [m3/s] | |
| G SW APARTMENT OA HEAT EXCHANGER | 0.025955 |
| G NW APARTMENT OA HEAT EXCHANGER | 0.025955 |
| G NE APARTMENT OA HEAT EXCHANGER | 0.025955 |
| G N1 APARTMENT OA HEAT EXCHANGER | 0.025955 |
| G N2 APARTMENT OA HEAT EXCHANGER | 0.025955 |
| G S1 APARTMENT OA HEAT EXCHANGER | 0.025955 |
| G S2 APARTMENT OA HEAT EXCHANGER | 0.025955 |
| M SW APARTMENT OA HEAT EXCHANGER | 0.051909 |
| M NW APARTMENT OA HEAT EXCHANGER | 0.051909 |
| M SE APARTMENT OA HEAT EXCHANGER | 0.051909 |
| M NE APARTMENT OA HEAT EXCHANGER | 0.051909 |
| M N1 APARTMENT OA HEAT EXCHANGER | 0.051909 |
| M N2 APARTMENT OA HEAT EXCHANGER | 0.051909 |
| M S1 APARTMENT OA HEAT EXCHANGER | 0.051909 |
| M S2 APARTMENT OA HEAT EXCHANGER | 0.051909 |
| T SW APARTMENT OA HEAT EXCHANGER | 0.025955 |
| T NW APARTMENT OA HEAT EXCHANGER | 0.025955 |
| T SE APARTMENT OA HEAT EXCHANGER | 0.025955 |
| T NE APARTMENT OA HEAT EXCHANGER | 0.025955 |
| T N1 APARTMENT OA HEAT EXCHANGER | 0.025955 |
| T N2 APARTMENT OA HEAT EXCHANGER | 0.025955 |
| T S1 APARTMENT OA HEAT EXCHANGER | 0.025955 |
| T S2 APARTMENT OA HEAT EXCHANGER | 0.025955 |
| Design Size Maximum Air Flow Rate [m3/s] | |
| G SW APARTMENT DIRECT AIR | 0.415565 |
| G NW APARTMENT DIRECT AIR | 0.407833 |
| OFFICE DIRECT AIR | 0.470352 |
| G NE APARTMENT DIRECT AIR | 0.372356 |
| G N1 APARTMENT DIRECT AIR | 0.331984 |
| G N2 APARTMENT DIRECT AIR | 0.331287 |
| G S1 APARTMENT DIRECT AIR | 0.342157 |
| G S2 APARTMENT DIRECT AIR | 0.344592 |
| M SW APARTMENT DIRECT AIR | 1.00 |
| M NW APARTMENT DIRECT AIR | 0.993924 |
| M SE APARTMENT DIRECT AIR | 0.899288 |
| M NE APARTMENT DIRECT AIR | 0.890667 |
| M N1 APARTMENT DIRECT AIR | 0.791657 |
| M N2 APARTMENT DIRECT AIR | 0.789628 |
| M S1 APARTMENT DIRECT AIR | 0.804358 |
| M S2 APARTMENT DIRECT AIR | 0.802259 |
| T SW APARTMENT DIRECT AIR | 0.559358 |
| T NW APARTMENT DIRECT AIR | 0.564333 |
| T SE APARTMENT DIRECT AIR | 0.482752 |
| T NE APARTMENT DIRECT AIR | 0.487516 |
| T N1 APARTMENT DIRECT AIR | 0.452140 |
| T N2 APARTMENT DIRECT AIR | 0.449489 |
| T S1 APARTMENT DIRECT AIR | 0.448234 |
| T S2 APARTMENT DIRECT AIR | 0.445595 |
| Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
| SPLIT GSW | 0.415565 | 0.415565 | 0.415565 | 0.415565 | 0.415565 | 0.415565 | 1.00 | 1.00 | 0.415565 |
| SPLIT GNW | 0.407833 | 0.407833 | 0.407833 | 0.407833 | 0.407833 | 0.407833 | 1.00 | 1.000000 | 0.407833 |
| SPLIT OFFICE | 0.470352 | 0.470352 | 0.470352 | 0.470352 | 0.470352 | 0.470352 | 1.00 | 1.00 | 0.470352 |
| SPLIT GNE | 0.372356 | 0.372356 | 0.372356 | 0.372356 | 0.372356 | 0.372356 | 1.00 | 1.00 | 0.372356 |
| SPLIT GN1 | 0.331984 | 0.331984 | 0.331984 | 0.331984 | 0.331984 | 0.331984 | 1.00 | 1.000000 | 0.331984 |
| SPLIT GN2 | 0.331287 | 0.331287 | 0.331287 | 0.331287 | 0.331287 | 0.331287 | 1.00 | 1.000000 | 0.331287 |
| SPLIT GS1 | 0.342157 | 0.342157 | 0.342157 | 0.342157 | 0.342157 | 0.342157 | 1.00 | 1.00 | 0.342157 |
| SPLIT GS2 | 0.344592 | 0.344592 | 0.344592 | 0.344592 | 0.344592 | 0.344592 | 1.00 | 1.00 | 0.344592 |
| SPLIT MSW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| SPLIT MNW | 0.993924 | 0.993924 | 0.993924 | 0.993924 | 0.993924 | 0.993924 | 1.00 | 1.00 | 0.993924 |
| SPLIT MSE | 0.899288 | 0.899288 | 0.899288 | 0.899288 | 0.899288 | 0.899288 | 1.00 | 1.00 | 0.899288 |
| SPLIT MNE | 0.890667 | 0.890667 | 0.890667 | 0.890667 | 0.890667 | 0.890667 | 1.00 | 1.00 | 0.890667 |
| SPLIT MN1 | 0.791657 | 0.791657 | 0.791657 | 0.791657 | 0.791657 | 0.791657 | 1.00 | 1.00 | 0.791657 |
| SPLIT MN2 | 0.789628 | 0.789628 | 0.789628 | 0.789628 | 0.789628 | 0.789628 | 1.00 | 1.00 | 0.789628 |
| SPLIT MS1 | 0.804358 | 0.804358 | 0.804358 | 0.804358 | 0.804358 | 0.804358 | 1.00 | 1.00 | 0.804358 |
| SPLIT MS2 | 0.802259 | 0.802259 | 0.802259 | 0.802259 | 0.802259 | 0.802259 | 1.00 | 1.00 | 0.802259 |
| SPLIT TSW | 0.559358 | 0.559358 | 0.559358 | 0.559358 | 0.559358 | 0.559358 | 1.00 | 1.00 | 0.559358 |
| SPLIT TNW | 0.564333 | 0.564333 | 0.564333 | 0.564333 | 0.564333 | 0.564333 | 1.00 | 1.00 | 0.564333 |
| SPLIT TSE | 0.482752 | 0.482752 | 0.482752 | 0.482752 | 0.482752 | 0.482752 | 1.00 | 1.00 | 0.482752 |
| SPLIT TNE | 0.487516 | 0.487516 | 0.487516 | 0.487516 | 0.487516 | 0.487516 | 1.00 | 1.00 | 0.487516 |
| SPLIT TN1 | 0.452140 | 0.452140 | 0.452140 | 0.452140 | 0.452140 | 0.452140 | 1.00 | 1.00 | 0.452140 |
| SPLIT TN2 | 0.449489 | 0.449489 | 0.449489 | 0.449489 | 0.449489 | 0.449489 | 1.00 | 1.000000 | 0.449489 |
| SPLIT TS1 | 0.448234 | 0.448234 | 0.448234 | 0.448234 | 0.448234 | 0.448234 | 1.00 | 1.000000 | 0.448234 |
| SPLIT TS2 | 0.445595 | 0.445595 | 0.445595 | 0.445595 | 0.445595 | 0.445595 | 1.00 | 1.00 | 0.445595 |
| Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
| SPLIT GSW_OA_CONTROLLER | 0.415565 | 0.025955 |
| SPLIT GNW_OA_CONTROLLER | 0.407833 | 0.025955 |
| SPLIT OFFICE_OA_CONTROLLER | 0.470352 | 0.038106 |
| SPLIT GNE_OA_CONTROLLER | 0.372356 | 0.025955 |
| SPLIT GN1_OA_CONTROLLER | 0.331984 | 0.025955 |
| SPLIT GN2_OA_CONTROLLER | 0.331287 | 0.025955 |
| SPLIT GS1_OA_CONTROLLER | 0.342157 | 0.025955 |
| SPLIT GS2_OA_CONTROLLER | 0.344592 | 0.025955 |
| SPLIT MSW_OA_CONTROLLER | 1.00 | 0.051909 |
| SPLIT MNW_OA_CONTROLLER | 0.993924 | 0.051909 |
| SPLIT MSE_OA_CONTROLLER | 0.899288 | 0.051909 |
| SPLIT MNE_OA_CONTROLLER | 0.890667 | 0.051909 |
| SPLIT MN1_OA_CONTROLLER | 0.791657 | 0.051909 |
| SPLIT MN2_OA_CONTROLLER | 0.789628 | 0.051909 |
| SPLIT MS1_OA_CONTROLLER | 0.804358 | 0.051909 |
| SPLIT MS2_OA_CONTROLLER | 0.802259 | 0.051909 |
| SPLIT TSW_OA_CONTROLLER | 0.559358 | 0.025955 |
| SPLIT TNW_OA_CONTROLLER | 0.564333 | 0.025955 |
| SPLIT TSE_OA_CONTROLLER | 0.482752 | 0.025955 |
| SPLIT TNE_OA_CONTROLLER | 0.487516 | 0.025955 |
| SPLIT TN1_OA_CONTROLLER | 0.452140 | 0.025955 |
| SPLIT TN2_OA_CONTROLLER | 0.449489 | 0.025955 |
| SPLIT TS1_OA_CONTROLLER | 0.448234 | 0.025955 |
| SPLIT TS2_OA_CONTROLLER | 0.445595 | 0.025955 |
| Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | Design Size Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
| SPLIT GSW_UNITARY_PACKAGE_DX | 0.415565 | 0.415565 | 0.415565 | 0.415565 | 6879.08 | 8565.90 | 40.00 | 1.00 |
| SPLIT GNW_UNITARY_PACKAGE_DX | 0.407833 | 0.407833 | 0.407833 | 0.407833 | 6751.08 | 8420.39 | 40.00 | 1.00 |
| SPLIT OFFICE_UNITARY_PACKAGE_DX | 0.470352 | 0.470352 | 0.470352 | 0.470352 | 7785.99 | 9947.14 | 40.00 | 1.00 |
| SPLIT GNE_UNITARY_PACKAGE_DX | 0.372356 | 0.372356 | 0.372356 | 0.372356 | 6163.82 | 7753.08 | 40.00 | 1.00 |
| SPLIT GN1_UNITARY_PACKAGE_DX | 0.331984 | 0.331984 | 0.331984 | 0.331984 | 5495.52 | 6993.63 | 40.00 | 1.00 |
| SPLIT GN2_UNITARY_PACKAGE_DX | 0.331287 | 0.331287 | 0.331287 | 0.331287 | 5483.98 | 6980.51 | 40.00 | 1.00 |
| SPLIT GS1_UNITARY_PACKAGE_DX | 0.342157 | 0.342157 | 0.342157 | 0.342157 | 5663.92 | 7185.04 | 40.00 | 1.00 |
| SPLIT GS2_UNITARY_PACKAGE_DX | 0.344592 | 0.344592 | 0.344592 | 0.344592 | 5704.22 | 7230.83 | 40.00 | 1.00 |
| SPLIT MSW_UNITARY_PACKAGE_DX | 1.00 | 1.00 | 1.00 | 1.00 | 16602.94 | 20364.98 | 40.00 | 1.00 |
| SPLIT MNW_UNITARY_PACKAGE_DX | 0.993924 | 0.993924 | 0.993924 | 0.993924 | 16452.98 | 20194.24 | 40.00 | 1.00 |
| SPLIT MSE_UNITARY_PACKAGE_DX | 0.899288 | 0.899288 | 0.899288 | 0.899288 | 14886.41 | 18414.38 | 40.00 | 1.00 |
| SPLIT MNE_UNITARY_PACKAGE_DX | 0.890667 | 0.890667 | 0.890667 | 0.890667 | 14743.71 | 18251.93 | 40.00 | 1.00 |
| SPLIT MN1_UNITARY_PACKAGE_DX | 0.791657 | 0.791657 | 0.791657 | 0.791657 | 13104.73 | 16389.21 | 40.00 | 1.00 |
| SPLIT MN2_UNITARY_PACKAGE_DX | 0.789628 | 0.789628 | 0.789628 | 0.789628 | 13071.14 | 16351.05 | 40.00 | 1.00 |
| SPLIT MS1_UNITARY_PACKAGE_DX | 0.804358 | 0.804358 | 0.804358 | 0.804358 | 13314.99 | 16628.41 | 40.00 | 1.00 |
| SPLIT MS2_UNITARY_PACKAGE_DX | 0.802259 | 0.802259 | 0.802259 | 0.802259 | 13280.23 | 16588.91 | 40.00 | 1.00 |
| SPLIT TSW_UNITARY_PACKAGE_DX | 0.559358 | 0.559358 | 0.559358 | 0.559358 | 9259.35 | 11271.18 | 40.00 | 1.00 |
| SPLIT TNW_UNITARY_PACKAGE_DX | 0.564333 | 0.564333 | 0.564333 | 0.564333 | 9341.72 | 11364.59 | 40.00 | 1.00 |
| SPLIT TSE_UNITARY_PACKAGE_DX | 0.482752 | 0.482752 | 0.482752 | 0.482752 | 7991.26 | 9830.14 | 40.00 | 1.00 |
| SPLIT TNE_UNITARY_PACKAGE_DX | 0.487516 | 0.487516 | 0.487516 | 0.487516 | 8070.11 | 9919.59 | 40.00 | 1.00 |
| SPLIT TN1_UNITARY_PACKAGE_DX | 0.452140 | 0.452140 | 0.452140 | 0.452140 | 7484.52 | 9253.92 | 40.00 | 1.00 |
| SPLIT TN2_UNITARY_PACKAGE_DX | 0.449489 | 0.449489 | 0.449489 | 0.449489 | 7440.64 | 9204.05 | 40.00 | 1.00 |
| SPLIT TS1_UNITARY_PACKAGE_DX | 0.448234 | 0.448234 | 0.448234 | 0.448234 | 7419.87 | 9180.61 | 40.00 | 1.00 |
| SPLIT TS2_UNITARY_PACKAGE_DX | 0.445595 | 0.445595 | 0.445595 | 0.445595 | 7376.18 | 9130.96 | 40.00 | 1.00 |
| Design Size Rated Air Flow Rate [m3/s] | Design Size Gross Rated Total Cooling Capacity [W] | Design Size Gross Rated Sensible Heat Ratio | |
| SPLIT GSW COOLING COIL | 0.415565 | 6879.08 | 0.800655 |
| SPLIT GNW COOLING COIL | 0.407833 | 6751.08 | 0.800655 |
| SPLIT OFFICE COOLING COIL | 0.470352 | 7785.99 | 0.800655 |
| SPLIT GNE COOLING COIL | 0.372356 | 6163.82 | 0.800655 |
| SPLIT GN1 COOLING COIL | 0.331984 | 5495.52 | 0.800655 |
| SPLIT GN2 COOLING COIL | 0.331287 | 5483.98 | 0.800655 |
| SPLIT GS1 COOLING COIL | 0.342157 | 5663.92 | 0.800655 |
| SPLIT GS2 COOLING COIL | 0.344592 | 5704.22 | 0.800655 |
| SPLIT MSW COOLING COIL | 1.00 | 16602.94 | 0.800655 |
| SPLIT MNW COOLING COIL | 0.993924 | 16452.98 | 0.800655 |
| SPLIT MSE COOLING COIL | 0.899288 | 14886.41 | 0.800655 |
| SPLIT MNE COOLING COIL | 0.890667 | 14743.71 | 0.800655 |
| SPLIT MN1 COOLING COIL | 0.791657 | 13104.73 | 0.800655 |
| SPLIT MN2 COOLING COIL | 0.789628 | 13071.14 | 0.800655 |
| SPLIT MS1 COOLING COIL | 0.804358 | 13314.99 | 0.800655 |
| SPLIT MS2 COOLING COIL | 0.802259 | 13280.23 | 0.800655 |
| SPLIT TSW COOLING COIL | 0.559358 | 9259.35 | 0.800655 |
| SPLIT TNW COOLING COIL | 0.564333 | 9341.72 | 0.800655 |
| SPLIT TSE COOLING COIL | 0.482752 | 7991.26 | 0.800655 |
| SPLIT TNE COOLING COIL | 0.487516 | 8070.11 | 0.800655 |
| SPLIT TN1 COOLING COIL | 0.452140 | 7484.52 | 0.800655 |
| SPLIT TN2 COOLING COIL | 0.449489 | 7440.64 | 0.800655 |
| SPLIT TS1 COOLING COIL | 0.448234 | 7419.87 | 0.800655 |
| SPLIT TS2 COOLING COIL | 0.445595 | 7376.18 | 0.800655 |
| Design Size Nominal Capacity [W] | |
| SPLIT GSW HEATING COIL | 8565.90 |
| SPLIT GNW HEATING COIL | 8420.39 |
| SPLIT OFFICE HEATING COIL | 9947.14 |
| SPLIT GNE HEATING COIL | 7753.08 |
| SPLIT GN1 HEATING COIL | 6993.63 |
| SPLIT GN2 HEATING COIL | 6980.51 |
| SPLIT GS1 HEATING COIL | 7185.04 |
| SPLIT GS2 HEATING COIL | 7230.83 |
| SPLIT MSW HEATING COIL | 20364.98 |
| SPLIT MNW HEATING COIL | 20194.24 |
| SPLIT MSE HEATING COIL | 18414.38 |
| SPLIT MNE HEATING COIL | 18251.93 |
| SPLIT MN1 HEATING COIL | 16389.21 |
| SPLIT MN2 HEATING COIL | 16351.05 |
| SPLIT MS1 HEATING COIL | 16628.41 |
| SPLIT MS2 HEATING COIL | 16588.91 |
| SPLIT TSW HEATING COIL | 11271.18 |
| SPLIT TNW HEATING COIL | 11364.59 |
| SPLIT TSE HEATING COIL | 9830.14 |
| SPLIT TNE HEATING COIL | 9919.59 |
| SPLIT TN1 HEATING COIL | 9253.92 |
| SPLIT TN2 HEATING COIL | 9204.05 |
| SPLIT TS1 HEATING COIL | 9180.61 |
| SPLIT TS2 HEATING COIL | 9130.96 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 09:14:27
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other Surfaces| None |
| Possible Shadow Receivers | |
| G SWALL SWA | GWINDOW1 S SWA | |
| G WWALL SWA | GWINDOW1 W SWA | |
| G NWALL NWA | GWINDOW1 N NWA | |
| G WWALL NWA | GWINDOW1 W NWA | |
| G SWALL SEA | GWINDOW1 S SEA | |
| G EWALL SEA | GWINDOW1 E SEA | |
| G NWALL NEA | GWINDOW1 N NEA | |
| G EWALL NEA | GWINDOW1 E NEA | |
| G NWALL N1A | GWINDOW1 N N1A | |
| G NWALL N2A | GWINDOW1 N N2A | |
| G SWALL S1A | GWINDOW1 S S1A | |
| G SWALL S2A | GWINDOW1 S S2A | |
| M WWALL SWA | MWINDOW1 W SWA | |
| M SWALL SWA | MWINDOW1 S SWA | |
| M NWALL NWA | MWINDOW1 N NWA | |
| M WWALL NWA | MWINDOW1 W NWA | |
| M EWALL SEA | MWINDOW1 E SEA | |
| M SWALL SEA | MWINDOW1 S SEA | |
| M NWALL NEA | MWINDOW1 N NEA | |
| M EWALL NEA | MWINDOW1 E NEA | |
| M NWALL N1A | MWINDOW1 N N1A | |
| M NWALL N2A | MWINDOW1 N N2A | |
| M SWALL S1A | MWINDOW1 S S1A | |
| M SWALL S2A | MWINDOW1 S S2A | |
| T WWALL SWA | TWINDOW1 W SWA | |
| T SWALL SWA | TWINDOW1 S SWA | |
| T NWALL NWA | TWINDOW1 N NWA | |
| T WWALL NWA | TWINDOW1 W NWA | |
| T EWALL SEA | TWINDOW1 E SEA | |
| T SWALL SEA | TWINDOW1 S SEA | |
| T NWALL NEA | TWINDOW1 N NEA | |
| T EWALL NEA | TWINDOW1 E NEA | |
| T NWALL N1A | TWINDOW1 N N1A | |
| T NWALL N2A | TWINDOW1 N N2A | |
| T SWALL S1A | TWINDOW1 S S1A | |
| T SWALL S2A | TWINDOW1 S S2A | |
| T EWALL C | TWINDOW14 | |
| G EWALL C | ENTRANCE DOOR | |
| M EWALL C | MWINDOW14 | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 09:14:27
Time Not Meeting the Adaptive Comfort Models during Occupied Hours| ASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 09:14:27
Version| Version ID | |
| 1 | 22.1 |
| #TimeSteps | Minutes per TimeStep {minutes} | |
| 1 | 6 | 10 |
| Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
| 1 | 1 | 20 | 2 | 8 |
| Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
| 1 | Yes | Yes | No | No | Yes | No |
| Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
| 1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
| Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
| 1 | 0.556 | 0.556 |
| Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
| 1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
| Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
| 1 | 13.70 | 7.00 | 2.10 | 2.60 | 4.30 | 8.80 | 13.90 | 17.80 | 23.20 | 25.60 | 24.10 | 20.50 |
| Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
| 1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
| Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
| 1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
| Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
| 1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
| Normal | Daylighting {dimensionless} | |
| 1 | 1.000 | 1.000 |
| Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
| 1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
| Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
| 1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
| Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
| 1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
| Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
| 1 | Albuquerque Intl Sunport NM USA TMY3 WMO#=723650 | 35.04 | -106.62 | -7.00 | 1619.00 | 83328 | 0.9904 |
| Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
| 1 | Correlation | NA | 13.63 | 23.50 | NA |
| Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
| 1 | ApartmentMidRise | 0.000 | City | 4.00000E-002 | 0.40000 | FullExterior | 25 | 6 |
| Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
| 1 | TARP |
| Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
| 1 | TARP |
| Value {Anisotropic} | |
| 1 | Anisotropic |
| Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
| 1 | ThirdOrderBackwardDifference |
| Simulation {Yes/No} | Carbon Dioxide Concentration | |
| 1 | No | N/A |
| Simulation {Yes/No} | Generic Contaminant Concentration | |
| 1 | No | N/A |
| Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
| 1 | No | N/A | N/A | N/A |
| Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
| 1 | RegulaFalsi |
| Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
| 1 | 0.330 | 460.000 | 6.500000E-003 |
| Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
| 1 | LowerLeftCorner | Clockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
| Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
| 1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
| Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
| 1 | 0 | 0 | 0 |
| Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
| 1 | 27 | 243 | 39 |
| Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
| 1 | G SW APARTMENT | 0.0 | 0.00 | 0.00 | 0.00 | 5.79 | 3.81 | 1.52 | 1 | 1 | 1 | 0.00 | 11.58 | 0.00 | 7.62 | 0.00 | 3.05 | 3.05 | 268.97 | TARP | TARP | 88.25 | 58.52 | 46.82 | 11.71 | 6 | 2 | 0 | Yes |
| 2 | G NW APARTMENT | 0.0 | 0.00 | 9.30 | 0.00 | 5.79 | 13.11 | 1.52 | 1 | 1 | 1 | 0.00 | 11.58 | 9.30 | 16.92 | 0.00 | 3.05 | 3.05 | 268.97 | TARP | TARP | 88.25 | 58.52 | 46.82 | 11.71 | 6 | 2 | 0 | Yes |
| 3 | OFFICE | 0.0 | 34.75 | 0.00 | 0.00 | 40.54 | 3.81 | 1.52 | 1 | 1 | 1 | 34.75 | 46.33 | 0.00 | 7.62 | 0.00 | 3.05 | 3.05 | 268.97 | TARP | TARP | 88.25 | 58.52 | 46.82 | 11.71 | 6 | 2 | 0 | Yes |
| 4 | G NE APARTMENT | 0.0 | 34.75 | 9.30 | 0.00 | 40.54 | 13.11 | 1.52 | 1 | 1 | 1 | 34.75 | 46.33 | 9.30 | 16.92 | 0.00 | 3.05 | 3.05 | 268.97 | TARP | TARP | 88.25 | 58.52 | 46.82 | 11.71 | 6 | 2 | 0 | Yes |
| 5 | G N1 APARTMENT | 0.0 | 11.58 | 9.30 | 0.00 | 17.37 | 13.11 | 1.52 | 1 | 1 | 1 | 11.58 | 23.16 | 9.30 | 16.92 | 0.00 | 3.05 | 3.05 | 268.97 | TARP | TARP | 88.25 | 35.30 | 28.24 | 7.06 | 6 | 1 | 0 | Yes |
| 6 | G N2 APARTMENT | 0.0 | 23.16 | 9.30 | 0.00 | 28.95 | 13.11 | 1.52 | 1 | 1 | 1 | 23.16 | 34.75 | 9.30 | 16.92 | 0.00 | 3.05 | 3.05 | 268.97 | TARP | TARP | 88.25 | 35.30 | 28.24 | 7.06 | 6 | 1 | 0 | Yes |
| 7 | G S1 APARTMENT | 0.0 | 11.58 | 0.00 | 0.00 | 17.37 | 3.81 | 1.52 | 1 | 1 | 1 | 11.58 | 23.16 | 0.00 | 7.62 | 0.00 | 3.05 | 3.05 | 268.97 | TARP | TARP | 88.25 | 35.30 | 28.24 | 7.06 | 6 | 1 | 0 | Yes |
| 8 | G S2 APARTMENT | 0.0 | 23.16 | 0.00 | 0.00 | 28.95 | 3.81 | 1.52 | 1 | 1 | 1 | 23.16 | 34.75 | 0.00 | 7.62 | 0.00 | 3.05 | 3.05 | 268.97 | TARP | TARP | 88.25 | 35.30 | 28.24 | 7.06 | 6 | 1 | 0 | Yes |
| 9 | M SW APARTMENT | 0.0 | 0.00 | 0.00 | 3.05 | 5.79 | 3.81 | 4.57 | 1 | 1 | 2 | 0.00 | 11.58 | 0.00 | 7.62 | 3.05 | 6.10 | 3.05 | 268.97 | TARP | TARP | 88.25 | 58.52 | 46.82 | 11.71 | 6 | 2 | 0 | Yes |
| 10 | M NW APARTMENT | 0.0 | 0.00 | 9.30 | 3.05 | 5.79 | 13.11 | 4.57 | 1 | 1 | 2 | 0.00 | 11.58 | 9.30 | 16.92 | 3.05 | 6.10 | 3.05 | 268.97 | TARP | TARP | 88.25 | 58.52 | 46.82 | 11.71 | 6 | 2 | 0 | Yes |
| 11 | M SE APARTMENT | 0.0 | 34.75 | 0.00 | 3.05 | 40.54 | 3.81 | 4.57 | 1 | 1 | 2 | 34.75 | 46.33 | 0.00 | 7.62 | 3.05 | 6.10 | 3.05 | 268.97 | TARP | TARP | 88.25 | 58.52 | 46.82 | 11.71 | 6 | 2 | 0 | Yes |
| 12 | M NE APARTMENT | 0.0 | 34.75 | 9.30 | 3.05 | 40.54 | 13.11 | 4.57 | 1 | 1 | 2 | 34.75 | 46.33 | 9.30 | 16.92 | 3.05 | 6.10 | 3.05 | 268.97 | TARP | TARP | 88.25 | 58.52 | 46.82 | 11.71 | 6 | 2 | 0 | Yes |
| 13 | M N1 APARTMENT | 0.0 | 11.58 | 9.30 | 3.05 | 17.37 | 13.11 | 4.57 | 1 | 1 | 2 | 11.58 | 23.16 | 9.30 | 16.92 | 3.05 | 6.10 | 3.05 | 268.97 | TARP | TARP | 88.25 | 35.30 | 28.24 | 7.06 | 6 | 1 | 0 | Yes |
| 14 | M N2 APARTMENT | 0.0 | 23.16 | 9.30 | 3.05 | 28.95 | 13.11 | 4.57 | 1 | 1 | 2 | 23.16 | 34.75 | 9.30 | 16.92 | 3.05 | 6.10 | 3.05 | 268.97 | TARP | TARP | 88.25 | 35.30 | 28.24 | 7.06 | 6 | 1 | 0 | Yes |
| 15 | M S1 APARTMENT | 0.0 | 11.58 | 0.00 | 3.05 | 17.37 | 3.81 | 4.57 | 1 | 1 | 2 | 11.58 | 23.16 | 0.00 | 7.62 | 3.05 | 6.10 | 3.05 | 268.97 | TARP | TARP | 88.25 | 35.30 | 28.24 | 7.06 | 6 | 1 | 0 | Yes |
| 16 | M S2 APARTMENT | 0.0 | 23.16 | 0.00 | 3.05 | 28.95 | 3.81 | 4.57 | 1 | 1 | 2 | 23.16 | 34.75 | 0.00 | 7.62 | 3.05 | 6.10 | 3.05 | 268.97 | TARP | TARP | 88.25 | 35.30 | 28.24 | 7.06 | 6 | 1 | 0 | Yes |
| 17 | T SW APARTMENT | 0.0 | 0.00 | 0.00 | 9.14 | 5.79 | 3.81 | 10.67 | 1 | 1 | 1 | 0.00 | 11.58 | 0.00 | 7.62 | 9.14 | 12.19 | 3.05 | 268.97 | TARP | TARP | 88.25 | 58.52 | 46.82 | 11.71 | 6 | 2 | 0 | Yes |
| 18 | T NW APARTMENT | 0.0 | 0.00 | 9.30 | 9.14 | 5.79 | 13.11 | 10.67 | 1 | 1 | 1 | 0.00 | 11.58 | 9.30 | 16.92 | 9.14 | 12.19 | 3.05 | 268.97 | TARP | TARP | 88.25 | 58.52 | 46.82 | 11.71 | 6 | 2 | 0 | Yes |
| 19 | T SE APARTMENT | 0.0 | 34.75 | 0.00 | 9.14 | 40.54 | 3.81 | 10.67 | 1 | 1 | 1 | 34.75 | 46.33 | 0.00 | 7.62 | 9.14 | 12.19 | 3.05 | 268.97 | TARP | TARP | 88.25 | 58.52 | 46.82 | 11.71 | 6 | 2 | 0 | Yes |
| 20 | T NE APARTMENT | 0.0 | 34.75 | 9.30 | 9.14 | 40.54 | 13.11 | 10.67 | 1 | 1 | 1 | 34.75 | 46.33 | 9.30 | 16.92 | 9.14 | 12.19 | 3.05 | 268.97 | TARP | TARP | 88.25 | 58.52 | 46.82 | 11.71 | 6 | 2 | 0 | Yes |
| 21 | T N1 APARTMENT | 0.0 | 11.58 | 9.30 | 9.14 | 17.37 | 13.11 | 10.67 | 1 | 1 | 1 | 11.58 | 23.16 | 9.30 | 16.92 | 9.14 | 12.19 | 3.05 | 268.97 | TARP | TARP | 88.25 | 35.30 | 28.24 | 7.06 | 6 | 1 | 0 | Yes |
| 22 | T N2 APARTMENT | 0.0 | 23.16 | 9.30 | 9.14 | 28.95 | 13.11 | 10.67 | 1 | 1 | 1 | 23.16 | 34.75 | 9.30 | 16.92 | 9.14 | 12.19 | 3.05 | 268.97 | TARP | TARP | 88.25 | 35.30 | 28.24 | 7.06 | 6 | 1 | 0 | Yes |
| 23 | T S1 APARTMENT | 0.0 | 11.58 | 0.00 | 9.14 | 17.37 | 3.81 | 10.67 | 1 | 1 | 1 | 11.58 | 23.16 | 0.00 | 7.62 | 9.14 | 12.19 | 3.05 | 268.97 | TARP | TARP | 88.25 | 35.30 | 28.24 | 7.06 | 6 | 1 | 0 | Yes |
| 24 | T S2 APARTMENT | 0.0 | 23.16 | 0.00 | 9.14 | 28.95 | 3.81 | 10.67 | 1 | 1 | 1 | 23.16 | 34.75 | 0.00 | 7.62 | 9.14 | 12.19 | 3.05 | 268.97 | TARP | TARP | 88.25 | 35.30 | 28.24 | 7.06 | 6 | 1 | 0 | Yes |
| 25 | T CORRIDOR | 0.0 | 0.00 | 7.62 | 9.14 | 23.16 | 8.46 | 10.67 | 1 | 1 | 1 | 0.00 | 46.33 | 7.62 | 9.30 | 9.14 | 12.19 | 3.05 | 236.69 | TARP | TARP | 77.66 | 10.22 | 9.10 | 1.11 | 12 | 1 | 0 | Yes |
| 26 | G CORRIDOR | 0.0 | 0.00 | 7.62 | 0.00 | 23.16 | 8.46 | 1.52 | 1 | 1 | 1 | 0.00 | 46.33 | 7.62 | 9.30 | 0.00 | 3.05 | 3.05 | 236.69 | TARP | TARP | 77.66 | 10.22 | 6.90 | 3.32 | 12 | 1 | 0 | Yes |
| 27 | M CORRIDOR | 0.0 | 0.00 | 7.62 | 3.05 | 23.16 | 8.46 | 4.57 | 1 | 1 | 2 | 0.00 | 46.33 | 7.62 | 9.30 | 3.05 | 6.10 | 3.05 | 236.69 | TARP | TARP | 77.66 | 10.22 | 9.10 | 1.11 | 12 | 1 | 0 | Yes |
| Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
| 1 | G SW APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 2 | G NW APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 3 | OFFICE | 88.25 | 4.7 | 18.581 | 5.382E-002 | 9.753 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 16.423 | No |
| 4 | G NE APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 5 | G N1 APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 6 | G N2 APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 7 | G S1 APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 8 | G S2 APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 9 | M SW APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 10 | M NW APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 11 | M SE APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 12 | M NE APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 13 | M N1 APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 14 | M N2 APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 15 | M S1 APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 16 | M S2 APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 17 | T SW APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 18 | T NW APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 19 | T SE APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 20 | T NE APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 21 | T N1 APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 22 | T N2 APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 23 | T S1 APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 24 | T S2 APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 25 | T CORRIDOR | 77.66 | 4.2 | 18.579 | 5.382E-002 | 4.772 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 4.772 | No |
| 26 | G CORRIDOR | 77.66 | 4.2 | 18.579 | 5.382E-002 | 4.772 | 105.256 | 0.000 | 0.000 | 0.000 | 0.000 | 110.029 | No |
| 27 | M CORRIDOR | 77.66 | 4.2 | 18.579 | 5.382E-002 | 4.772 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 4.772 | No |
| Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | |
| 1 | OCCUP_GSW | OCC_APT_SCH_WORKING_FAMILY | G SW APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 3 |
| 2 | OCCUP_GNW | OCC_APT_SCH_STAY_HOME_FAMILY | G NW APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 1 | 3 |
| 3 | OCCUP_OFFICE | OCC_OFF_W_SB_SCH | OFFICE | 88.25 | 4.7 | 4.7 | 5.382E-002 | 18.581 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 5 |
| 4 | OCCUP_GNE | OCC_APT_SCH_STAY_HOME_FAMILY | G NE APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 1 | 3 |
| 5 | OCCUP_GN1 | OCC_APT_SCH_STAY_HOME_FAMILY | G N1 APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 1 | 3 |
| 6 | OCCUP_GN2 | OCC_APT_SCH_STAY_HOME_FAMILY | G N2 APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 1 | 3 |
| 7 | OCCUP_GS1 | OCC_APT_SCH_WORKING_FAMILY | G S1 APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 3 |
| 8 | OCCUP_GS2 | OCC_APT_SCH_WORKING_FAMILY | G S2 APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 3 |
| 9 | OCCUP_MSW | OCC_APT_SCH_WORKING_FAMILY | M SW APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 3 |
| 10 | OCCUP_MNW | OCC_APT_SCH_STAY_HOME_FAMILY | M NW APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 1 | 3 |
| 11 | OCCUP_MSE | OCC_APT_SCH_WORKING_FAMILY | M SE APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 3 |
| 12 | OCCUP_MNE | OCC_APT_SCH_STAY_HOME_FAMILY | M NE APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 1 | 3 |
| 13 | OCCUP_MN1 | OCC_APT_SCH_STAY_HOME_FAMILY | M N1 APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 1 | 3 |
| 14 | OCCUP_MN2 | OCC_APT_SCH_STAY_HOME_FAMILY | M N2 APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 1 | 3 |
| 15 | OCCUP_MS1 | OCC_APT_SCH_WORKING_FAMILY | M S1 APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 3 |
| 16 | OCCUP_MS2 | OCC_APT_SCH_WORKING_FAMILY | M S2 APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 3 |
| 17 | OCCUP_TSW | OCC_APT_SCH_WORKING_FAMILY | T SW APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 3 |
| 18 | OCCUP_TNW | OCC_APT_SCH_STAY_HOME_FAMILY | T NW APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 1 | 3 |
| 19 | OCCUP_TSE | OCC_APT_SCH_WORKING_FAMILY | T SE APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 3 |
| 20 | OCCUP_TNE | OCC_APT_SCH_STAY_HOME_FAMILY | T NE APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 1 | 3 |
| 21 | OCCUP_TN1 | OCC_APT_SCH_STAY_HOME_FAMILY | T N1 APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 1 | 3 |
| 22 | OCCUP_TN2 | OCC_APT_SCH_STAY_HOME_FAMILY | T N2 APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 1 | 3 |
| 23 | OCCUP_TS1 | OCC_APT_SCH_WORKING_FAMILY | T S1 APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 3 |
| 24 | OCCUP_TS2 | OCC_APT_SCH_WORKING_FAMILY | T S2 APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 3 |
| 25 | OCCUP_T CORRIDOR | OCC_APT_SCH_CORRIDOR | T CORRIDOR | 77.66 | 4.2 | 4.2 | 5.382E-002 | 18.579 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 1 | 4 |
| 26 | OCCUP_G CORRIDOR | OCC_APT_SCH_CORRIDOR | G CORRIDOR | 77.66 | 4.2 | 4.2 | 5.382E-002 | 18.579 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 1 | 4 |
| 27 | OCCUP_M CORRIDOR | OCC_APT_SCH_CORRIDOR | M CORRIDOR | 77.66 | 4.2 | 4.2 | 5.382E-002 | 18.579 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 1 | 4 |
| Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
| 1 | LIGHTING_HARDWIRED_GSW | LTG_SCH_APARTMENT_HARDWIRED | G SW APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 2 | LIGHTING_HARDWIRED_GNW | LTG_SCH_APARTMENT_HARDWIRED | G NW APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 3 | LIGHTING_HARDWIRED_OFFICE | LTG_SCH_OFFICE | OFFICE | 88.25 | 4.7 | 860.710 | 9.753 | 181.220 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 860.710 |
| 4 | LIGHTING_HARDWIRED_GNE | LTG_SCH_APARTMENT_HARDWIRED | G NE APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 5 | LIGHTING_HARDWIRED_GN1 | LTG_SCH_APARTMENT_HARDWIRED | G N1 APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 6 | LIGHTING_HARDWIRED_GN2 | LTG_SCH_APARTMENT_HARDWIRED | G N2 APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 7 | LIGHTING_HARDWIRED_GS1 | LTG_SCH_APARTMENT_HARDWIRED | G S1 APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 8 | LIGHTING_HARDWIRED_GS2 | LTG_SCH_APARTMENT_HARDWIRED | G S2 APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 9 | LIGHTING_HARDWIRED_MSW | LTG_SCH_APARTMENT_HARDWIRED | M SW APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 10 | LIGHTING_HARDWIRED_MNW | LTG_SCH_APARTMENT_HARDWIRED | M NW APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 11 | LIGHTING_HARDWIRED_MSE | LTG_SCH_APARTMENT_HARDWIRED | M SE APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 12 | LIGHTING_HARDWIRED_MNE | LTG_SCH_APARTMENT_HARDWIRED | M NE APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 13 | LIGHTING_HARDWIRED_MN1 | LTG_SCH_APARTMENT_HARDWIRED | M N1 APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 14 | LIGHTING_HARDWIRED_MN2 | LTG_SCH_APARTMENT_HARDWIRED | M N2 APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 15 | LIGHTING_HARDWIRED_MS1 | LTG_SCH_APARTMENT_HARDWIRED | M S1 APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 16 | LIGHTING_HARDWIRED_MS2 | LTG_SCH_APARTMENT_HARDWIRED | M S2 APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 17 | LIGHTING_HARDWIRED_TSW | LTG_SCH_APARTMENT_HARDWIRED | T SW APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 18 | LIGHTING_HARDWIRED_TNW | LTG_SCH_APARTMENT_HARDWIRED | T NW APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 19 | LIGHTING_HARDWIRED_TSE | LTG_SCH_APARTMENT_HARDWIRED | T SE APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 20 | LIGHTING_HARDWIRED_TNE | LTG_SCH_APARTMENT_HARDWIRED | T NE APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 21 | LIGHTING_HARDWIRED_TN1 | LTG_SCH_APARTMENT_HARDWIRED | T N1 APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 22 | LIGHTING_HARDWIRED_TN2 | LTG_SCH_APARTMENT_HARDWIRED | T N2 APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 23 | LIGHTING_HARDWIRED_TS1 | LTG_SCH_APARTMENT_HARDWIRED | T S1 APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 24 | LIGHTING_HARDWIRED_TS2 | LTG_SCH_APARTMENT_HARDWIRED | T S2 APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 25 | LIGHTING_HARDWIRED_GC | LTG_SCH_CORRIDOR | G CORRIDOR | 77.66 | 4.2 | 370.628 | 4.772 | 88.667 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 370.628 |
| 26 | LIGHTING_HARDWIRED_MC | LTG_SCH_CORRIDOR | M CORRIDOR | 77.66 | 4.2 | 370.628 | 4.772 | 88.667 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 370.628 |
| 27 | LIGHTING_HARDWIRED_TC | LTG_SCH_CORRIDOR | T CORRIDOR | 77.66 | 4.2 | 370.628 | 4.772 | 88.667 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 370.628 |
| 28 | LIGHTING_PLUGIN_GSW | LTG_SCH_APARTMENT_PLUGIN | G SW APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| 29 | LIGHTING_PLUGIN_GNW | LTG_SCH_APARTMENT_PLUGIN | G NW APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| 30 | LIGHTING_PLUGIN_GNE | LTG_SCH_APARTMENT_PLUGIN | G NE APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| 31 | LIGHTING_PLUGIN_GN1 | LTG_SCH_APARTMENT_PLUGIN | G N1 APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| 32 | LIGHTING_PLUGIN_GN2 | LTG_SCH_APARTMENT_PLUGIN | G N2 APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| 33 | LIGHTING_PLUGIN_GS1 | LTG_SCH_APARTMENT_PLUGIN | G S1 APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| 34 | LIGHTING_PLUGIN_GS2 | LTG_SCH_APARTMENT_PLUGIN | G S2 APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| 35 | LIGHTING_PLUGIN_MSW | LTG_SCH_APARTMENT_PLUGIN | M SW APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| 36 | LIGHTING_PLUGIN_MNW | LTG_SCH_APARTMENT_PLUGIN | M NW APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| 37 | LIGHTING_PLUGIN_MSE | LTG_SCH_APARTMENT_PLUGIN | M SE APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| 38 | LIGHTING_PLUGIN_MNE | LTG_SCH_APARTMENT_PLUGIN | M NE APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| 39 | LIGHTING_PLUGIN_MN1 | LTG_SCH_APARTMENT_PLUGIN | M N1 APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| 40 | LIGHTING_PLUGIN_MN2 | LTG_SCH_APARTMENT_PLUGIN | M N2 APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| 41 | LIGHTING_PLUGIN_MS1 | LTG_SCH_APARTMENT_PLUGIN | M S1 APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| 42 | LIGHTING_PLUGIN_MS2 | LTG_SCH_APARTMENT_PLUGIN | M S2 APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| 43 | LIGHTING_PLUGIN_TSW | LTG_SCH_APARTMENT_PLUGIN | T SW APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| 44 | LIGHTING_PLUGIN_TNW | LTG_SCH_APARTMENT_PLUGIN | T NW APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| 45 | LIGHTING_PLUGIN_TSE | LTG_SCH_APARTMENT_PLUGIN | T SE APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| 46 | LIGHTING_PLUGIN_TNE | LTG_SCH_APARTMENT_PLUGIN | T NE APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| 47 | LIGHTING_PLUGIN_TN1 | LTG_SCH_APARTMENT_PLUGIN | T N1 APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| 48 | LIGHTING_PLUGIN_TN2 | LTG_SCH_APARTMENT_PLUGIN | T N2 APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| 49 | LIGHTING_PLUGIN_TS1 | LTG_SCH_APARTMENT_PLUGIN | T S1 APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| 50 | LIGHTING_PLUGIN_TS2 | LTG_SCH_APARTMENT_PLUGIN | T S2 APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
| 1 | PLUG_GSW | EQP_APT_SCH | G SW APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 2 | PLUG_GNW | EQP_APT_SCH | G NW APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 3 | PLUG_OFFICE | EQP_OFF_SCH | OFFICE | 88.25 | 4.7 | 588.623 | 6.670 | 123.933 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 588.623 |
| 4 | PLUG_GNE | EQP_APT_SCH | G NE APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 5 | PLUG_GN1 | EQP_APT_SCH | G N1 APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 6 | PLUG_GN2 | EQP_APT_SCH | G N2 APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 7 | PLUG_GS1 | EQP_APT_SCH | G S1 APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 8 | PLUG_GS2 | EQP_APT_SCH | G S2 APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 9 | PLUG_MSW | EQP_APT_SCH | M SW APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 10 | PLUG_MNW | EQP_APT_SCH | M NW APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 11 | PLUG_MSE | EQP_APT_SCH | M SE APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 12 | PLUG_MNE | EQP_APT_SCH | M NE APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 13 | PLUG_MN1 | EQP_APT_SCH | M N1 APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 14 | PLUG_MN2 | EQP_APT_SCH | M N2 APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 15 | PLUG_MS1 | EQP_APT_SCH | M S1 APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 16 | PLUG_MS2 | EQP_APT_SCH | M S2 APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 17 | PLUG_TSW | EQP_APT_SCH | T SW APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 18 | PLUG_TNW | EQP_APT_SCH | T NW APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 19 | PLUG_TSE | EQP_APT_SCH | T SE APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 20 | PLUG_TNE | EQP_APT_SCH | T NE APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 21 | PLUG_TN1 | EQP_APT_SCH | T N1 APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 22 | PLUG_TN2 | EQP_APT_SCH | T N2 APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 23 | PLUG_TS1 | EQP_APT_SCH | T S1 APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 24 | PLUG_TS2 | EQP_APT_SCH | T S2 APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 25 | G CORRIDOR_ELEVATORS_EQUIP | BLDG_ELEVATORS | G CORRIDOR | 77.66 | 4.2 | 8012.150 | 103.170 | 1916.782 | 0.000 | 0.000 | 0.950 | 5.000E-002 | ElevatorLift | 961.458 | 4006.075 |
| 26 | ELEVATORS_LIGHTS_FAN | ELEV_LIGHT_FAN_SCH_24_7 | G CORRIDOR | 77.66 | 4.2 | 162.000 | 2.086 | 38.756 | 0.000 | 0.000 | 0.950 | 5.000E-002 | ElevatorLightsFan | 162.000 | 162.000 |
| Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
| 1 | PolygonClipping | Periodic | 20 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
| Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
| 1 | WaterHeater:Mixed | G SW APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.496 | 0.7729 |
| 2 | WaterHeater:Mixed | G NW APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.496 | 0.7729 |
| 3 | WaterHeater:Mixed | G NE APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.496 | 0.7729 |
| 4 | WaterHeater:Mixed | G N1 APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.496 | 0.7729 |
| 5 | WaterHeater:Mixed | G N2 APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.496 | 0.7729 |
| 6 | WaterHeater:Mixed | G S1 APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.496 | 0.7729 |
| 7 | WaterHeater:Mixed | G S2 APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.496 | 0.7729 |
| 8 | WaterHeater:Mixed | M SW APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.498 | 0.7911 |
| 9 | WaterHeater:Mixed | M NW APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.498 | 0.7911 |
| 10 | WaterHeater:Mixed | M SE APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.498 | 0.7911 |
| 11 | WaterHeater:Mixed | M NE APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.498 | 0.7911 |
| 12 | WaterHeater:Mixed | M N1 APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.498 | 0.7911 |
| 13 | WaterHeater:Mixed | M N2 APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.498 | 0.7911 |
| 14 | WaterHeater:Mixed | M S1 APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.498 | 0.7911 |
| 15 | WaterHeater:Mixed | M S2 APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.498 | 0.7911 |
| 16 | WaterHeater:Mixed | T SW APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.496 | 0.7729 |
| 17 | WaterHeater:Mixed | T NW APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.496 | 0.7729 |
| 18 | WaterHeater:Mixed | T SE APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.496 | 0.7729 |
| 19 | WaterHeater:Mixed | T NE APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.496 | 0.7729 |
| 20 | WaterHeater:Mixed | T N1 APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.496 | 0.7729 |
| 21 | WaterHeater:Mixed | T N2 APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.496 | 0.7729 |
| 22 | WaterHeater:Mixed | T S1 APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.496 | 0.7729 |
| 23 | WaterHeater:Mixed | T S2 APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.496 | 0.7729 |
| Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
| 1 | G SWALL SWA | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 2 | GWINDOW1 S SWA | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 3 | G WWALL SWA | 0 | 154.67 | 58.21 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 4 | GWINDOW1 W SWA | 0 | 154.67 | 58.21 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 5 | G NIWALL SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 6 | G EIWALL SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 7 | G GFLOOR SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 8 | G CEILIN SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 9 | G INTERNALMASS SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 10 | G NWALL NWA | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 11 | GWINDOW1 N NWA | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 12 | G WWALL NWA | 0 | 154.67 | 58.21 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 13 | GWINDOW1 W NWA | 0 | 154.67 | 58.21 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 14 | G SIWALL NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 15 | G EIWALL NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 16 | G GFLOOR NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 17 | G CEILIN NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 18 | G INTERNALMASS NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 19 | G SWALL SEA | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 20 | GWINDOW1 S SEA | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 21 | G EWALL SEA | 0 | 154.67 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 22 | GWINDOW1 E SEA | 0 | 154.67 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 23 | G NIWALL SEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 24 | iz-G EIWALL S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 25 | G GFLOOR SEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 26 | G CEILIN SEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 27 | G INTERNALMASS SEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 28 | G NWALL NEA | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 29 | GWINDOW1 N NEA | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 30 | G EWALL NEA | 0 | 154.67 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 31 | GWINDOW1 E NEA | 0 | 154.67 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 32 | G SIWALL NEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 33 | iz-G EIWALL N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 34 | G GFLOOR NEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 35 | G CEILIN NEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 36 | G INTERNALMASS NEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 37 | G NWALL N1A | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 3 | No | No |
| 38 | GWINDOW1 N N1A | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 2 | No | No |
| 39 | G SIWALL N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 40 | G EIWALL N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 41 | iz-G EIWALL NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 42 | G GFLOOR N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 43 | G CEILIN N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 44 | G INTERNALMASS N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 45 | G NWALL N2A | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 3 | No | No |
| 46 | GWINDOW1 N N2A | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 2 | No | No |
| 47 | G SIWALL N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 48 | G EIWALL N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 49 | iz-G EIWALL N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 50 | G GFLOOR N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 51 | G CEILIN N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 52 | G INTERNALMASS N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 53 | G SWALL S1A | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 3 | No | No |
| 54 | GWINDOW1 S S1A | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 2 | No | No |
| 55 | G NIWALL S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 56 | G EIWALL S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 57 | iz-G EIWALL SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 58 | G GFLOOR S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 59 | G CEILIN S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 60 | G INTERNALMASS S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 61 | G SWALL S2A | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 3 | No | No |
| 62 | GWINDOW1 S S2A | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 2 | No | No |
| 63 | G NIWALL S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 64 | G EIWALL S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 65 | iz-G EIWALL S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 66 | G GFLOOR S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 67 | G CEILIN S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 68 | G INTERNALMASS S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 69 | M WWALL SWA | 0 | 154.67 | 58.21 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 70 | MWINDOW1 W SWA | 0 | 154.67 | 58.21 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 71 | M SWALL SWA | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 72 | MWINDOW1 S SWA | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 73 | M NIWALL SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 74 | M EIWALL SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 75 | M GFLOOR SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 76 | M CEILIN SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 77 | M INTERNALMASS SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 78 | M NWALL NWA | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 79 | MWINDOW1 N NWA | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 80 | M WWALL NWA | 0 | 154.67 | 58.21 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 81 | MWINDOW1 W NWA | 0 | 154.67 | 58.21 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 82 | M SIWALL NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 83 | M EIWALL NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 84 | M GFLOOR NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 85 | M CEILIN NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 86 | M INTERNALMASS NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 87 | M EWALL SEA | 0 | 154.67 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 88 | MWINDOW1 E SEA | 0 | 154.67 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 89 | M SWALL SEA | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 90 | MWINDOW1 S SEA | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 91 | M NIWALL SEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 92 | iz-M EIWALL S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 93 | M GFLOOR SEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 94 | M CEILIN SEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 95 | M INTERNALMASS SEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 96 | M NWALL NEA | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 97 | MWINDOW1 N NEA | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 98 | M EWALL NEA | 0 | 154.67 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 99 | MWINDOW1 E NEA | 0 | 154.67 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 100 | M SIWALL NEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 101 | iz-M EIWALL N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 102 | M GFLOOR NEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 103 | M CEILIN NEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 104 | M INTERNALMASS NEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 105 | M NWALL N1A | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 3 | No | No |
| 106 | MWINDOW1 N N1A | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 2 | No | No |
| 107 | M SIWALL N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 108 | M EIWALL N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 109 | iz-M EIWALL NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 110 | M GFLOOR N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 111 | M CEILIN N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 112 | M INTERNALMASS N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 113 | M NWALL N2A | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 3 | No | No |
| 114 | MWINDOW1 N N2A | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 2 | No | No |
| 115 | M SIWALL N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 116 | M EIWALL N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 117 | iz-M EIWALL N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 118 | M GFLOOR N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 119 | M CEILIN N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 120 | M INTERNALMASS N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 121 | M SWALL S1A | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 3 | No | No |
| 122 | MWINDOW1 S S1A | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 2 | No | No |
| 123 | M NIWALL S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 124 | M EIWALL S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 125 | iz-M EIWALL SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 126 | M GFLOOR S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 127 | M CEILIN S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 128 | M INTERNALMASS S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 129 | M SWALL S2A | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 3 | No | No |
| 130 | MWINDOW1 S S2A | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 2 | No | No |
| 131 | M NIWALL S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 132 | M EIWALL S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 133 | iz-M EIWALL S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 134 | M GFLOOR S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 135 | M CEILIN S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 136 | M INTERNALMASS S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 137 | T WWALL SWA | 0 | 154.67 | 58.21 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 138 | TWINDOW1 W SWA | 0 | 154.67 | 58.21 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 139 | T SWALL SWA | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 140 | TWINDOW1 S SWA | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 141 | T NIWALL SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 142 | T EIWALL SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 143 | T GFLOOR SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 144 | T ROOF SWA | 0 | 783.65 | 155.90 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 145 | T INTERNALMASS SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 146 | T NWALL NWA | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 147 | TWINDOW1 N NWA | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 148 | T WWALL NWA | 0 | 154.67 | 58.21 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 149 | TWINDOW1 W NWA | 0 | 154.67 | 58.21 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 150 | T SIWALL NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 151 | T EIWALL NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 152 | T GFLOOR NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 153 | T ROOF NWA | 0 | 783.65 | 155.90 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 154 | T INTERNALMASS NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 155 | T EWALL SEA | 0 | 154.67 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 156 | TWINDOW1 E SEA | 0 | 154.67 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 157 | T SWALL SEA | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 158 | TWINDOW1 S SEA | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 159 | T NIWALL SEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 160 | iz-T EIWALL S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 161 | T GFLOOR SEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 162 | T ROOF SEA | 0 | 783.65 | 155.90 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 163 | T INTERNALMASS SEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 164 | T NWALL NEA | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 165 | TWINDOW1 N NEA | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 166 | T EWALL NEA | 0 | 154.67 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 167 | TWINDOW1 E NEA | 0 | 154.67 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 168 | T SIWALL NEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 169 | iz-T EIWALL N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 170 | T GFLOOR NEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 171 | T ROOF NEA | 0 | 783.65 | 155.90 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 172 | T INTERNALMASS NEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 173 | T NWALL N1A | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 3 | No | No |
| 174 | TWINDOW1 N N1A | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 2 | No | No |
| 175 | T SIWALL N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 176 | T EIWALL N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 177 | iz-T EIWALL NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 178 | T GFLOOR N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 179 | T ROOF N1A | 0 | 783.65 | 155.90 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 180 | T INTERNALMASS N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 181 | T NWALL N2A | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 3 | No | No |
| 182 | TWINDOW1 N N2A | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 2 | No | No |
| 183 | T SIWALL N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 184 | T EIWALL N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 185 | iz-T EIWALL N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 186 | T GFLOOR N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 187 | T ROOF N2A | 0 | 783.65 | 155.90 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 188 | T INTERNALMASS N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 189 | T SWALL S1A | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 3 | No | No |
| 190 | TWINDOW1 S S1A | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 2 | No | No |
| 191 | T NIWALL S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 192 | T EIWALL S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 193 | iz-T EIWALL SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 194 | T GFLOOR S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 195 | T ROOF S1A | 0 | 783.65 | 155.90 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 196 | T INTERNALMASS S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 197 | T SWALL S2A | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 3 | No | No |
| 198 | TWINDOW1 S S2A | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 2 | No | No |
| 199 | T NIWALL S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 200 | T EIWALL S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 201 | iz-T EIWALL S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 202 | T GFLOOR S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 203 | T ROOF S2A | 0 | 783.65 | 155.90 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 204 | T INTERNALMASS S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 205 | T WWALL C | 0 | 154.67 | 58.21 | 12.19 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 3 | No | No |
| 206 | T EWALL C | 0 | 154.67 | 123.02 | 12.19 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 3 | No | No |
| 207 | TWINDOW14 | 0 | 154.67 | 123.02 | 12.19 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 2 | No | No |
| 208 | iz-T NIWALL SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 209 | iz-T NIWALL S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 210 | iz-T NIWALL S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 211 | iz-T NIWALL SEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 212 | iz-T SIWALL NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 213 | iz-T SIWALL N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 214 | iz-T SIWALL N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 215 | iz-T SIWALL NEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 216 | T FLOOR C | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 217 | T ROOF C | 0 | 783.65 | 155.90 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 218 | G WWALL C | 0 | 154.67 | 58.21 | 12.19 | 0 | 3.05 | 3.35 | 3.24 | 0.32 | 4 | No | No |
| 219 | G EWALL C | 0 | 154.67 | 123.02 | 12.19 | 0 | 3.05 | 3.35 | 3.24 | 0.32 | 4 | No | No |
| 220 | ENTRANCE DOOR | 0 | 154.67 | 123.02 | 12.19 | 0 | 3.05 | 3.35 | 3.24 | 0.32 | 1 | No | No |
| 221 | iz-G NIWALL SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.32 | 0 | No | No |
| 222 | iz-G NIWALL S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.32 | 0 | No | No |
| 223 | iz-G NIWALL S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.32 | 0 | No | No |
| 224 | iz-G NIWALL SEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.32 | 0 | No | No |
| 225 | iz-G SIWALL NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.32 | 0 | No | No |
| 226 | iz-G SIWALL N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.32 | 0 | No | No |
| 227 | iz-G SIWALL N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.32 | 0 | No | No |
| 228 | iz-G SIWALL NEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.32 | 0 | No | No |
| 229 | G FLOOR C | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.32 | 0 | No | No |
| 230 | G CEILING C | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.32 | 0 | No | No |
| 231 | M WWALL C | 0 | 154.67 | 58.21 | 12.19 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 4 | No | No |
| 232 | M EWALL C | 0 | 154.67 | 123.02 | 12.19 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 3 | No | No |
| 233 | MWINDOW14 | 0 | 154.67 | 123.02 | 12.19 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 2 | No | No |
| 234 | iz-M NIWALL SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 235 | iz-M NIWALL S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 236 | iz-M NIWALL S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 237 | iz-M NIWALL SEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 238 | iz-M SIWALL NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 239 | iz-M SIWALL N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 240 | iz-M SIWALL N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 241 | iz-M SIWALL NEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 242 | M FLOOR C | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 243 | M CEILING C | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
| 1 | INFIL_GSW | INF_APT_SCH | G SW APARTMENT | 88.25 | 2.5 | 3.333E-002 | 3.777E-004 | 5.696E-004 | 0.446 | 0.000 | 0.000 | 0.224 | 0.000 |
| 2 | INFIL_GNW | INF_APT_SCH | G NW APARTMENT | 88.25 | 2.5 | 3.333E-002 | 3.777E-004 | 5.696E-004 | 0.446 | 0.000 | 0.000 | 0.224 | 0.000 |
| 3 | INFIL_OFFICE | INF_OFF_SCH | OFFICE | 88.25 | 4.7 | 3.333E-002 | 3.777E-004 | 5.696E-004 | 0.446 | 0.000 | 0.000 | 0.224 | 0.000 |
| 4 | INFIL_GNE | INF_APT_SCH | G NE APARTMENT | 88.25 | 2.5 | 3.333E-002 | 3.777E-004 | 5.696E-004 | 0.446 | 0.000 | 0.000 | 0.224 | 0.000 |
| 5 | INFIL_GN1 | INF_APT_SCH | G N1 APARTMENT | 88.25 | 2.5 | 2.011E-002 | 2.278E-004 | 5.696E-004 | 0.269 | 0.000 | 0.000 | 0.224 | 0.000 |
| 6 | INFIL_GN2 | INF_APT_SCH | G N2 APARTMENT | 88.25 | 2.5 | 2.011E-002 | 2.278E-004 | 5.696E-004 | 0.269 | 0.000 | 0.000 | 0.224 | 0.000 |
| 7 | INFIL_GS1 | INF_APT_SCH | G S1 APARTMENT | 88.25 | 2.5 | 2.011E-002 | 2.278E-004 | 5.696E-004 | 0.269 | 0.000 | 0.000 | 0.224 | 0.000 |
| 8 | INFIL_GS2 | INF_APT_SCH | G S2 APARTMENT | 88.25 | 2.5 | 2.011E-002 | 2.278E-004 | 5.696E-004 | 0.269 | 0.000 | 0.000 | 0.224 | 0.000 |
| 9 | INFIL_MSW | INF_APT_SCH | M SW APARTMENT | 88.25 | 2.5 | 3.333E-002 | 3.777E-004 | 5.696E-004 | 0.446 | 0.000 | 0.000 | 0.224 | 0.000 |
| 10 | INFIL_MNW | INF_APT_SCH | M NW APARTMENT | 88.25 | 2.5 | 3.333E-002 | 3.777E-004 | 5.696E-004 | 0.446 | 0.000 | 0.000 | 0.224 | 0.000 |
| 11 | INFIL_MSE | INF_APT_SCH | M SE APARTMENT | 88.25 | 2.5 | 3.333E-002 | 3.777E-004 | 5.696E-004 | 0.446 | 0.000 | 0.000 | 0.224 | 0.000 |
| 12 | INFIL_MNE | INF_APT_SCH | M NE APARTMENT | 88.25 | 2.5 | 3.333E-002 | 3.777E-004 | 5.696E-004 | 0.446 | 0.000 | 0.000 | 0.224 | 0.000 |
| 13 | INFIL_MN1 | INF_APT_SCH | M N1 APARTMENT | 88.25 | 2.5 | 2.011E-002 | 2.278E-004 | 5.696E-004 | 0.269 | 0.000 | 0.000 | 0.224 | 0.000 |
| 14 | INFIL_MN2 | INF_APT_SCH | M N2 APARTMENT | 88.25 | 2.5 | 2.011E-002 | 2.278E-004 | 5.696E-004 | 0.269 | 0.000 | 0.000 | 0.224 | 0.000 |
| 15 | INFIL_MS1 | INF_APT_SCH | M S1 APARTMENT | 88.25 | 2.5 | 2.011E-002 | 2.278E-004 | 5.696E-004 | 0.269 | 0.000 | 0.000 | 0.224 | 0.000 |
| 16 | INFIL_MS2 | INF_APT_SCH | M S2 APARTMENT | 88.25 | 2.5 | 2.011E-002 | 2.278E-004 | 5.696E-004 | 0.269 | 0.000 | 0.000 | 0.224 | 0.000 |
| 17 | INFIL_SW | INF_APT_SCH | T SW APARTMENT | 88.25 | 2.5 | 3.333E-002 | 3.777E-004 | 2.271E-004 | 0.446 | 0.000 | 0.000 | 0.224 | 0.000 |
| 18 | INFIL_NW | INF_APT_SCH | T NW APARTMENT | 88.25 | 2.5 | 3.333E-002 | 3.777E-004 | 2.271E-004 | 0.446 | 0.000 | 0.000 | 0.224 | 0.000 |
| 19 | INFIL_SE | INF_APT_SCH | T SE APARTMENT | 88.25 | 2.5 | 3.333E-002 | 3.777E-004 | 2.271E-004 | 0.446 | 0.000 | 0.000 | 0.224 | 0.000 |
| 20 | INFIL_NE | INF_APT_SCH | T NE APARTMENT | 88.25 | 2.5 | 3.333E-002 | 3.777E-004 | 2.271E-004 | 0.446 | 0.000 | 0.000 | 0.224 | 0.000 |
| 21 | INFIL_TN1 | INF_APT_SCH | T N1 APARTMENT | 88.25 | 2.5 | 2.011E-002 | 2.278E-004 | 1.627E-004 | 0.269 | 0.000 | 0.000 | 0.224 | 0.000 |
| 22 | INFIL_TN2 | INF_APT_SCH | T N2 APARTMENT | 88.25 | 2.5 | 2.011E-002 | 2.278E-004 | 1.627E-004 | 0.269 | 0.000 | 0.000 | 0.224 | 0.000 |
| 23 | INFIL_TS1 | INF_APT_SCH | T S1 APARTMENT | 88.25 | 2.5 | 2.011E-002 | 2.278E-004 | 1.627E-004 | 0.269 | 0.000 | 0.000 | 0.224 | 0.000 |
| 24 | INFIL_TS2 | INF_APT_SCH | T S2 APARTMENT | 88.25 | 2.5 | 2.011E-002 | 2.278E-004 | 1.627E-004 | 0.269 | 0.000 | 0.000 | 0.224 | 0.000 |
| 25 | INFIL_GC | INF_COR_SCH | G CORRIDOR | 77.66 | 4.2 | 5.820E-003 | 7.494E-005 | 5.696E-004 | 8.852E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
| 26 | DOOR_INFIL_GC | INFIL_DOOR_OPENING_SCH | G CORRIDOR | 77.66 | 4.2 | 0.521 | 6.703E-003 | 5.094E-002 | 7.917 | 1.000 | 0.000 | 0.000 | 0.000 |
| 27 | INFIL_MC | INF_COR_SCH | M CORRIDOR | 77.66 | 4.2 | 5.820E-003 | 7.494E-005 | 5.696E-004 | 8.852E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
| 28 | INFIL_TC | INF_COR_SCH | T CORRIDOR | 77.66 | 4.2 | 5.820E-003 | 7.494E-005 | 6.623E-005 | 8.852E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
| Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
| 1 | G SW APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | G SW APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 2 | G NW APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | G NW APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 3 | G NE APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | G NE APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 4 | G N1 APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | G N1 APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 5 | G N2 APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | G N2 APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 6 | G S1 APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | G S1 APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 7 | G S2 APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | G S2 APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 8 | M SW APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | M SW APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 9 | M NW APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | M NW APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 10 | M SE APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | M SE APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 11 | M NE APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | M NE APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 12 | M N1 APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | M N1 APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 13 | M N2 APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | M N2 APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 14 | M S1 APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | M S1 APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 15 | M S2 APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | M S2 APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 16 | T SW APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | T SW APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 17 | T NW APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | T NW APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 18 | T SE APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | T SE APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 19 | T NE APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | T NE APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 20 | T N1 APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | T N1 APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 21 | T N2 APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | T N2 APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 22 | T S1 APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | T S1 APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 23 | T S2 APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | T S2 APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| Simple | |
| 1 | Simple |
| Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
| 1 | G SW APARTMENT | Mixing/Well-Stirred |
| 2 | G NW APARTMENT | Mixing/Well-Stirred |
| 3 | OFFICE | Mixing/Well-Stirred |
| 4 | G NE APARTMENT | Mixing/Well-Stirred |
| 5 | G N1 APARTMENT | Mixing/Well-Stirred |
| 6 | G N2 APARTMENT | Mixing/Well-Stirred |
| 7 | G S1 APARTMENT | Mixing/Well-Stirred |
| 8 | G S2 APARTMENT | Mixing/Well-Stirred |
| 9 | M SW APARTMENT | Mixing/Well-Stirred |
| 10 | M NW APARTMENT | Mixing/Well-Stirred |
| 11 | M SE APARTMENT | Mixing/Well-Stirred |
| 12 | M NE APARTMENT | Mixing/Well-Stirred |
| 13 | M N1 APARTMENT | Mixing/Well-Stirred |
| 14 | M N2 APARTMENT | Mixing/Well-Stirred |
| 15 | M S1 APARTMENT | Mixing/Well-Stirred |
| 16 | M S2 APARTMENT | Mixing/Well-Stirred |
| 17 | T SW APARTMENT | Mixing/Well-Stirred |
| 18 | T NW APARTMENT | Mixing/Well-Stirred |
| 19 | T SE APARTMENT | Mixing/Well-Stirred |
| 20 | T NE APARTMENT | Mixing/Well-Stirred |
| 21 | T N1 APARTMENT | Mixing/Well-Stirred |
| 22 | T N2 APARTMENT | Mixing/Well-Stirred |
| 23 | T S1 APARTMENT | Mixing/Well-Stirred |
| 24 | T S2 APARTMENT | Mixing/Well-Stirred |
| 25 | T CORRIDOR | Mixing/Well-Stirred |
| 26 | G CORRIDOR | Mixing/Well-Stirred |
| 27 | M CORRIDOR | Mixing/Well-Stirred |
| No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
| 1 | NoMultizoneOrDistribution |
| Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
| 1 | 1.000 | 1.000 | 1.000 | 1.000 |
| Value | |
| 1 | 6 |
| Sizing Factor ID | Value | |
| 1 | Global | 1.2000 |
| 2 | Zone G SW APARTMENT | 1.2000 |
| 3 | Zone G NW APARTMENT | 1.2000 |
| 4 | Zone OFFICE | 1.2000 |
| 5 | Zone G NE APARTMENT | 1.2000 |
| 6 | Zone G N1 APARTMENT | 1.2000 |
| 7 | Zone G N2 APARTMENT | 1.2000 |
| 8 | Zone G S1 APARTMENT | 1.2000 |
| 9 | Zone G S2 APARTMENT | 1.2000 |
| 10 | Zone M SW APARTMENT | 1.2000 |
| 11 | Zone M NW APARTMENT | 1.2000 |
| 12 | Zone M SE APARTMENT | 1.2000 |
| 13 | Zone M NE APARTMENT | 1.2000 |
| 14 | Zone M N1 APARTMENT | 1.2000 |
| 15 | Zone M N2 APARTMENT | 1.2000 |
| 16 | Zone M S1 APARTMENT | 1.2000 |
| 17 | Zone M S2 APARTMENT | 1.2000 |
| 18 | Zone T SW APARTMENT | 1.2000 |
| 19 | Zone T NW APARTMENT | 1.2000 |
| 20 | Zone T SE APARTMENT | 1.2000 |
| 21 | Zone T NE APARTMENT | 1.2000 |
| 22 | Zone T N1 APARTMENT | 1.2000 |
| 23 | Zone T N2 APARTMENT | 1.2000 |
| 24 | Zone T S1 APARTMENT | 1.2000 |
| 25 | Zone T S2 APARTMENT | 1.2000 |
| Sizing Factor ID | Value | |
| 1 | Global | 1.2000 |
| 2 | Zone G SW APARTMENT | 1.2000 |
| 3 | Zone G NW APARTMENT | 1.2000 |
| 4 | Zone OFFICE | 1.2000 |
| 5 | Zone G NE APARTMENT | 1.2000 |
| 6 | Zone G N1 APARTMENT | 1.2000 |
| 7 | Zone G N2 APARTMENT | 1.2000 |
| 8 | Zone G S1 APARTMENT | 1.2000 |
| 9 | Zone G S2 APARTMENT | 1.2000 |
| 10 | Zone M SW APARTMENT | 1.2000 |
| 11 | Zone M NW APARTMENT | 1.2000 |
| 12 | Zone M SE APARTMENT | 1.2000 |
| 13 | Zone M NE APARTMENT | 1.2000 |
| 14 | Zone M N1 APARTMENT | 1.2000 |
| 15 | Zone M N2 APARTMENT | 1.2000 |
| 16 | Zone M S1 APARTMENT | 1.2000 |
| 17 | Zone M S2 APARTMENT | 1.2000 |
| 18 | Zone T SW APARTMENT | 1.2000 |
| 19 | Zone T NW APARTMENT | 1.2000 |
| 20 | Zone T SE APARTMENT | 1.2000 |
| 21 | Zone T NE APARTMENT | 1.2000 |
| 22 | Zone T N1 APARTMENT | 1.2000 |
| 23 | Zone T N2 APARTMENT | 1.2000 |
| 24 | Zone T S1 APARTMENT | 1.2000 |
| 25 | Zone T S2 APARTMENT | 1.2000 |
| Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
| 1 | G SW APARTMENT | Cooling | 4017.12011 | 4820.54413 | 0.34630 | 0.41557 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 29.83500 | 5.69125E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 2 | G SW APARTMENT | Heating | 1489.85360 | 1787.82432 | 7.80513E-002 | 9.36615E-002 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:50:00 | -7.90000 | 2.34317E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 3 | G NW APARTMENT | Cooling | 3943.83963 | 4732.60755 | 0.33986 | 0.40783 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 29.83500 | 5.69125E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 4 | G NW APARTMENT | Heating | 1376.66149 | 1651.99379 | 7.21219E-002 | 8.65463E-002 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | -7.90000 | 2.34317E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 5 | OFFICE | Cooling | 4485.36388 | 5382.43665 | 0.39196 | 0.47035 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 27.67500 | 5.68796E-003 | 88.24927 | 4.74953 | 3.81060E-002 | 0.00000 |
| 6 | OFFICE | Heating | 1930.75565 | 2316.90678 | 0.10115 | 0.12138 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 18:50:00 | -7.90000 | 2.34317E-003 | 88.24927 | 4.74953 | 3.81060E-002 | 0.00000 |
| 7 | G NE APARTMENT | Cooling | 3608.14037 | 4329.76844 | 0.31030 | 0.37236 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 29.83500 | 5.69125E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 8 | G NE APARTMENT | Heating | 1376.66147 | 1651.99376 | 7.21219E-002 | 8.65463E-002 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | -7.90000 | 2.34317E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 9 | G N1 APARTMENT | Cooling | 3224.84283 | 3869.81139 | 0.27665 | 0.33198 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 29.83500 | 5.69125E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 10 | G N1 APARTMENT | Heating | 797.79100 | 957.34920 | 4.17959E-002 | 5.01550E-002 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | -7.90000 | 2.34317E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 11 | G N2 APARTMENT | Cooling | 3218.21309 | 3861.85571 | 0.27607 | 0.33129 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 29.83500 | 5.69125E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 12 | G N2 APARTMENT | Heating | 797.79100 | 957.34920 | 4.17959E-002 | 5.01550E-002 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | -7.90000 | 2.34317E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 13 | G S1 APARTMENT | Cooling | 3322.17206 | 3986.60647 | 0.28513 | 0.34216 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 29.83500 | 5.69125E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 14 | G S1 APARTMENT | Heating | 912.32224 | 1094.78669 | 4.77956E-002 | 5.73548E-002 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:50:00 | -7.90000 | 2.34317E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 15 | G S2 APARTMENT | Cooling | 3345.21511 | 4014.25813 | 0.28716 | 0.34459 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 29.83500 | 5.69125E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 16 | G S2 APARTMENT | Heating | 920.85159 | 1105.02191 | 4.82425E-002 | 5.78910E-002 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:50:00 | -7.90000 | 2.34317E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 17 | M SW APARTMENT | Cooling | 9668.87617 | 11602.65140 | 0.83582 | 1.00298 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 29.83500 | 5.69125E-003 | 88.24927 | 2.50000 | 5.19091E-002 | 0.00000 |
| 18 | M SW APARTMENT | Heating | 2810.94341 | 3373.13209 | 0.14726 | 0.17671 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | -7.90000 | 2.34317E-003 | 88.24927 | 2.50000 | 5.19091E-002 | 0.00000 |
| 19 | M NW APARTMENT | Cooling | 9583.25200 | 11499.90240 | 0.82827 | 0.99392 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 29.83500 | 5.69125E-003 | 88.24927 | 2.50000 | 5.19091E-002 | 0.00000 |
| 20 | M NW APARTMENT | Heating | 2538.79226 | 3046.55071 | 0.13300 | 0.15960 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | -7.90000 | 2.34317E-003 | 88.24927 | 2.50000 | 5.19091E-002 | 0.00000 |
| 21 | M SE APARTMENT | Cooling | 8682.38300 | 10418.85960 | 0.74941 | 0.89929 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 29.83500 | 5.69125E-003 | 88.24927 | 2.50000 | 5.19091E-002 | 0.00000 |
| 22 | M SE APARTMENT | Heating | 2810.94336 | 3373.13203 | 0.14726 | 0.17671 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | -7.90000 | 2.34317E-003 | 88.24927 | 2.50000 | 5.19091E-002 | 0.00000 |
| 23 | M NE APARTMENT | Cooling | 8600.34076 | 10320.40892 | 0.74222 | 0.89067 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 29.83500 | 5.69125E-003 | 88.24927 | 2.50000 | 5.19091E-002 | 0.00000 |
| 24 | M NE APARTMENT | Heating | 2538.79221 | 3046.55066 | 0.13300 | 0.15960 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | -7.90000 | 2.34317E-003 | 88.24927 | 2.50000 | 5.19091E-002 | 0.00000 |
| 25 | M N1 APARTMENT | Cooling | 7660.37089 | 9192.44507 | 0.65971 | 0.79166 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 29.83500 | 5.69125E-003 | 88.24927 | 2.50000 | 5.19091E-002 | 0.00000 |
| 26 | M N1 APARTMENT | Heating | 1259.25129 | 1511.10155 | 6.59707E-002 | 7.91649E-002 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | -7.90000 | 2.34317E-003 | 88.24927 | 2.50000 | 5.19091E-002 | 0.00000 |
| 27 | M N2 APARTMENT | Cooling | 7641.15351 | 9169.38421 | 0.65802 | 0.78963 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 29.83500 | 5.69125E-003 | 88.24927 | 2.50000 | 5.19091E-002 | 0.00000 |
| 28 | M N2 APARTMENT | Heating | 1259.25129 | 1511.10155 | 6.59707E-002 | 7.91649E-002 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | -7.90000 | 2.34317E-003 | 88.24927 | 2.50000 | 5.19091E-002 | 0.00000 |
| 29 | M S1 APARTMENT | Cooling | 7780.71552 | 9336.85862 | 0.67030 | 0.80436 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 29.83500 | 5.69125E-003 | 88.24927 | 2.50000 | 5.19091E-002 | 0.00000 |
| 30 | M S1 APARTMENT | Heating | 1524.24545 | 1829.09455 | 7.98519E-002 | 9.58223E-002 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | -7.90000 | 2.34317E-003 | 88.24927 | 2.50000 | 5.19091E-002 | 0.00000 |
| 31 | M S2 APARTMENT | Cooling | 7760.81424 | 9312.97709 | 0.66855 | 0.80226 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 29.83500 | 5.69125E-003 | 88.24927 | 2.50000 | 5.19091E-002 | 0.00000 |
| 32 | M S2 APARTMENT | Heating | 1524.24545 | 1829.09454 | 7.98519E-002 | 9.58223E-002 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | -7.90000 | 2.34317E-003 | 88.24927 | 2.50000 | 5.19091E-002 | 0.00000 |
| 33 | T SW APARTMENT | Cooling | 5384.29111 | 6461.14934 | 0.46613 | 0.55936 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 29.83500 | 5.69125E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 34 | T SW APARTMENT | Heating | 2491.20733 | 2989.44880 | 0.13050 | 0.15660 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | -7.90000 | 2.34317E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 35 | T NW APARTMENT | Cooling | 5431.37148 | 6517.64578 | 0.47028 | 0.56433 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 29.83500 | 5.69125E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 36 | T NW APARTMENT | Heating | 2349.07945 | 2818.89535 | 0.12306 | 0.14767 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | -7.90000 | 2.34317E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 37 | T SE APARTMENT | Cooling | 4658.40068 | 5590.08081 | 0.40229 | 0.48275 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 29.83500 | 5.69125E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 38 | T SE APARTMENT | Heating | 2491.20730 | 2989.44876 | 0.13050 | 0.15660 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | -7.90000 | 2.34317E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 39 | T NE APARTMENT | Cooling | 4703.43104 | 5644.11725 | 0.40626 | 0.48752 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 29.83500 | 5.69125E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 40 | T NE APARTMENT | Heating | 2349.07943 | 2818.89531 | 0.12306 | 0.14767 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | -7.90000 | 2.34317E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 41 | T N1 APARTMENT | Cooling | 4368.72530 | 5242.47036 | 0.37678 | 0.45214 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 29.83500 | 5.69125E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 42 | T N1 APARTMENT | Heating | 1593.07127 | 1911.68552 | 8.34582E-002 | 0.10015 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | -7.90000 | 2.34317E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 43 | T N2 APARTMENT | Cooling | 4343.55937 | 5212.27125 | 0.37457 | 0.44949 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 29.83500 | 5.69125E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 44 | T N2 APARTMENT | Heating | 1593.07127 | 1911.68552 | 8.34582E-002 | 0.10015 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | -7.90000 | 2.34317E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 45 | T S1 APARTMENT | Cooling | 4331.83009 | 5198.19611 | 0.37353 | 0.44823 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 29.83500 | 5.69125E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 46 | T S1 APARTMENT | Heating | 1735.30056 | 2082.36067 | 9.09076E-002 | 0.10909 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | -7.90000 | 2.34317E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 47 | T S2 APARTMENT | Cooling | 4306.69761 | 5168.03713 | 0.37133 | 0.44560 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 29.83500 | 5.69125E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 48 | T S2 APARTMENT | Heating | 1735.30056 | 2082.36067 | 9.09076E-002 | 0.10909 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | -7.90000 | 2.34317E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
| 1 | SPLIT GSW | Cooling | Sensible | 4802.41 | 0.41557 | 0.41557 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 2 | SPLIT GSW | Heating | Sensible | 2510.86 | 9.36615E-002 | 9.36615E-002 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:50:00 |
| 3 | SPLIT GNW | Cooling | Sensible | 4715.45 | 0.40783 | 0.40783 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 4 | SPLIT GNW | Heating | Sensible | 2377.01 | 8.65463E-002 | 8.65463E-002 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 |
| 5 | SPLIT OFFICE | Cooling | Sensible | 5366.69 | 0.47035 | 0.47035 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 6 | SPLIT OFFICE | Heating | Sensible | 3382.94 | 0.12138 | 0.12138 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 18:50:00 |
| 7 | SPLIT GNE | Cooling | Sensible | 4316.44 | 0.37236 | 0.37236 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 8 | SPLIT GNE | Heating | Sensible | 2377.01 | 8.65463E-002 | 8.65463E-002 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 |
| 9 | SPLIT GN1 | Cooling | Sensible | 3861.44 | 0.33198 | 0.33198 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 10 | SPLIT GN1 | Heating | Sensible | 1692.49 | 5.01550E-002 | 5.01550E-002 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 |
| 11 | SPLIT GN2 | Cooling | Sensible | 3853.58 | 0.33129 | 0.33129 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 12 | SPLIT GN2 | Heating | Sensible | 1692.49 | 5.01550E-002 | 5.01550E-002 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 |
| 13 | SPLIT GS1 | Cooling | Sensible | 3976.54 | 0.34216 | 0.34216 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 14 | SPLIT GS1 | Heating | Sensible | 1827.92 | 5.73548E-002 | 5.73548E-002 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:50:00 |
| 15 | SPLIT GS2 | Cooling | Sensible | 4003.85 | 0.34459 | 0.34459 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 16 | SPLIT GS2 | Heating | Sensible | 1838.00 | 5.78910E-002 | 5.78910E-002 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:50:00 |
| 17 | SPLIT MSW | Cooling | Sensible | 11540.38 | 1.00298 | 1.00298 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 18 | SPLIT MSW | Heating | Sensible | 4822.11 | 0.17671 | 0.17671 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 |
| 19 | SPLIT MNW | Cooling | Sensible | 11438.78 | 0.99392 | 0.99392 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 20 | SPLIT MNW | Heating | Sensible | 4500.31 | 0.15960 | 0.15960 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 |
| 21 | SPLIT MSE | Cooling | Sensible | 10372.63 | 0.89929 | 0.89929 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 22 | SPLIT MSE | Heating | Sensible | 4822.11 | 0.17671 | 0.17671 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 |
| 23 | SPLIT MNE | Cooling | Sensible | 10275.59 | 0.89067 | 0.89067 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 24 | SPLIT MNE | Heating | Sensible | 4500.31 | 0.15960 | 0.15960 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 |
| 25 | SPLIT MN1 | Cooling | Sensible | 9161.01 | 0.79166 | 0.79166 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 26 | SPLIT MN1 | Heating | Sensible | 2987.24 | 7.91649E-002 | 7.91649E-002 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 |
| 27 | SPLIT MN2 | Cooling | Sensible | 9138.18 | 0.78963 | 0.78963 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 28 | SPLIT MN2 | Heating | Sensible | 2987.24 | 7.91649E-002 | 7.91649E-002 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 |
| 29 | SPLIT MS1 | Cooling | Sensible | 9303.86 | 0.80436 | 0.80436 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 30 | SPLIT MS1 | Heating | Sensible | 3300.59 | 9.58223E-002 | 9.58223E-002 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 |
| 31 | SPLIT MS2 | Cooling | Sensible | 9280.24 | 0.80226 | 0.80226 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 32 | SPLIT MS2 | Heating | Sensible | 3300.59 | 9.58223E-002 | 9.58223E-002 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 |
| 33 | SPLIT TSW | Cooling | Sensible | 6421.25 | 0.55936 | 0.55936 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 34 | SPLIT TSW | Heating | Sensible | 3694.95 | 0.15660 | 0.15660 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 |
| 35 | SPLIT TNW | Cooling | Sensible | 6477.16 | 0.56433 | 0.56433 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 36 | SPLIT TNW | Heating | Sensible | 3526.89 | 0.14767 | 0.14767 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 |
| 37 | SPLIT TSE | Cooling | Sensible | 5560.59 | 0.48275 | 0.48275 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 38 | SPLIT TSE | Heating | Sensible | 3694.95 | 0.15660 | 0.15660 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 |
| 39 | SPLIT TNE | Cooling | Sensible | 5614.09 | 0.48752 | 0.48752 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 40 | SPLIT TNE | Heating | Sensible | 3526.89 | 0.14767 | 0.14767 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 |
| 41 | SPLIT TN1 | Cooling | Sensible | 5216.83 | 0.45214 | 0.45214 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 42 | SPLIT TN1 | Heating | Sensible | 2632.91 | 0.10015 | 0.10015 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 |
| 43 | SPLIT TN2 | Cooling | Sensible | 5187.02 | 0.44949 | 0.44949 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 44 | SPLIT TN2 | Heating | Sensible | 2632.91 | 0.10015 | 0.10015 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 |
| 45 | SPLIT TS1 | Cooling | Sensible | 5172.98 | 0.44823 | 0.44823 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 46 | SPLIT TS1 | Heating | Sensible | 2801.09 | 0.10909 | 0.10909 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 |
| 47 | SPLIT TS2 | Cooling | Sensible | 5143.25 | 0.44560 | 0.44560 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 48 | SPLIT TS2 | Heating | Sensible | 2801.09 | 0.10909 | 0.10909 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 |
| Component Type | Component Name | Input Field Description | Value | |
| 1 | ZoneHVAC:EnergyRecoveryVentilator | G SW APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 2 | ZoneHVAC:EnergyRecoveryVentilator | G SW APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 2.59546E-002 |
| 3 | Fan:OnOff | G SW APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 4 | Fan:OnOff | G SW APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 5 | HeatExchanger:AirToAir:SensibleAndLatent | G SW APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 6 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | G SW APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.41557 |
| 7 | ZoneHVAC:EnergyRecoveryVentilator | G NW APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 8 | ZoneHVAC:EnergyRecoveryVentilator | G NW APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 2.59546E-002 |
| 9 | Fan:OnOff | G NW APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 10 | Fan:OnOff | G NW APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 11 | HeatExchanger:AirToAir:SensibleAndLatent | G NW APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 12 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | G NW APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.40783 |
| 13 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | OFFICE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.47035 |
| 14 | ZoneHVAC:EnergyRecoveryVentilator | G NE APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 15 | ZoneHVAC:EnergyRecoveryVentilator | G NE APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 2.59546E-002 |
| 16 | Fan:OnOff | G NE APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 17 | Fan:OnOff | G NE APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 18 | HeatExchanger:AirToAir:SensibleAndLatent | G NE APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 19 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | G NE APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.37236 |
| 20 | ZoneHVAC:EnergyRecoveryVentilator | G N1 APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 21 | ZoneHVAC:EnergyRecoveryVentilator | G N1 APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 2.59546E-002 |
| 22 | Fan:OnOff | G N1 APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 23 | Fan:OnOff | G N1 APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 24 | HeatExchanger:AirToAir:SensibleAndLatent | G N1 APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 25 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | G N1 APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.33198 |
| 26 | ZoneHVAC:EnergyRecoveryVentilator | G N2 APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 27 | ZoneHVAC:EnergyRecoveryVentilator | G N2 APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 2.59546E-002 |
| 28 | Fan:OnOff | G N2 APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 29 | Fan:OnOff | G N2 APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 30 | HeatExchanger:AirToAir:SensibleAndLatent | G N2 APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 31 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | G N2 APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.33129 |
| 32 | ZoneHVAC:EnergyRecoveryVentilator | G S1 APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 33 | ZoneHVAC:EnergyRecoveryVentilator | G S1 APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 2.59546E-002 |
| 34 | Fan:OnOff | G S1 APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 35 | Fan:OnOff | G S1 APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 36 | HeatExchanger:AirToAir:SensibleAndLatent | G S1 APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 37 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | G S1 APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.34216 |
| 38 | ZoneHVAC:EnergyRecoveryVentilator | G S2 APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 39 | ZoneHVAC:EnergyRecoveryVentilator | G S2 APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 2.59546E-002 |
| 40 | Fan:OnOff | G S2 APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 41 | Fan:OnOff | G S2 APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 42 | HeatExchanger:AirToAir:SensibleAndLatent | G S2 APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 43 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | G S2 APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.34459 |
| 44 | ZoneHVAC:EnergyRecoveryVentilator | M SW APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 5.19091E-002 |
| 45 | ZoneHVAC:EnergyRecoveryVentilator | M SW APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 5.19091E-002 |
| 46 | Fan:OnOff | M SW APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 5.19091E-002 |
| 47 | Fan:OnOff | M SW APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 5.19091E-002 |
| 48 | HeatExchanger:AirToAir:SensibleAndLatent | M SW APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 5.19091E-002 |
| 49 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | M SW APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.00298 |
| 50 | ZoneHVAC:EnergyRecoveryVentilator | M NW APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 5.19091E-002 |
| 51 | ZoneHVAC:EnergyRecoveryVentilator | M NW APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 5.19091E-002 |
| 52 | Fan:OnOff | M NW APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 5.19091E-002 |
| 53 | Fan:OnOff | M NW APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 5.19091E-002 |
| 54 | HeatExchanger:AirToAir:SensibleAndLatent | M NW APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 5.19091E-002 |
| 55 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | M NW APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.99392 |
| 56 | ZoneHVAC:EnergyRecoveryVentilator | M SE APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 5.19091E-002 |
| 57 | ZoneHVAC:EnergyRecoveryVentilator | M SE APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 5.19091E-002 |
| 58 | Fan:OnOff | M SE APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 5.19091E-002 |
| 59 | Fan:OnOff | M SE APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 5.19091E-002 |
| 60 | HeatExchanger:AirToAir:SensibleAndLatent | M SE APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 5.19091E-002 |
| 61 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | M SE APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.89929 |
| 62 | ZoneHVAC:EnergyRecoveryVentilator | M NE APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 5.19091E-002 |
| 63 | ZoneHVAC:EnergyRecoveryVentilator | M NE APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 5.19091E-002 |
| 64 | Fan:OnOff | M NE APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 5.19091E-002 |
| 65 | Fan:OnOff | M NE APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 5.19091E-002 |
| 66 | HeatExchanger:AirToAir:SensibleAndLatent | M NE APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 5.19091E-002 |
| 67 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | M NE APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.89067 |
| 68 | ZoneHVAC:EnergyRecoveryVentilator | M N1 APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 5.19091E-002 |
| 69 | ZoneHVAC:EnergyRecoveryVentilator | M N1 APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 5.19091E-002 |
| 70 | Fan:OnOff | M N1 APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 5.19091E-002 |
| 71 | Fan:OnOff | M N1 APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 5.19091E-002 |
| 72 | HeatExchanger:AirToAir:SensibleAndLatent | M N1 APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 5.19091E-002 |
| 73 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | M N1 APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.79166 |
| 74 | ZoneHVAC:EnergyRecoveryVentilator | M N2 APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 5.19091E-002 |
| 75 | ZoneHVAC:EnergyRecoveryVentilator | M N2 APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 5.19091E-002 |
| 76 | Fan:OnOff | M N2 APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 5.19091E-002 |
| 77 | Fan:OnOff | M N2 APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 5.19091E-002 |
| 78 | HeatExchanger:AirToAir:SensibleAndLatent | M N2 APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 5.19091E-002 |
| 79 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | M N2 APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.78963 |
| 80 | ZoneHVAC:EnergyRecoveryVentilator | M S1 APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 5.19091E-002 |
| 81 | ZoneHVAC:EnergyRecoveryVentilator | M S1 APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 5.19091E-002 |
| 82 | Fan:OnOff | M S1 APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 5.19091E-002 |
| 83 | Fan:OnOff | M S1 APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 5.19091E-002 |
| 84 | HeatExchanger:AirToAir:SensibleAndLatent | M S1 APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 5.19091E-002 |
| 85 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | M S1 APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.80436 |
| 86 | ZoneHVAC:EnergyRecoveryVentilator | M S2 APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 5.19091E-002 |
| 87 | ZoneHVAC:EnergyRecoveryVentilator | M S2 APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 5.19091E-002 |
| 88 | Fan:OnOff | M S2 APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 5.19091E-002 |
| 89 | Fan:OnOff | M S2 APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 5.19091E-002 |
| 90 | HeatExchanger:AirToAir:SensibleAndLatent | M S2 APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 5.19091E-002 |
| 91 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | M S2 APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.80226 |
| 92 | ZoneHVAC:EnergyRecoveryVentilator | T SW APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 93 | ZoneHVAC:EnergyRecoveryVentilator | T SW APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 2.59546E-002 |
| 94 | Fan:OnOff | T SW APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 95 | Fan:OnOff | T SW APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 96 | HeatExchanger:AirToAir:SensibleAndLatent | T SW APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 97 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | T SW APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.55936 |
| 98 | ZoneHVAC:EnergyRecoveryVentilator | T NW APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 99 | ZoneHVAC:EnergyRecoveryVentilator | T NW APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 2.59546E-002 |
| 100 | Fan:OnOff | T NW APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 101 | Fan:OnOff | T NW APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 102 | HeatExchanger:AirToAir:SensibleAndLatent | T NW APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 103 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | T NW APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.56433 |
| 104 | ZoneHVAC:EnergyRecoveryVentilator | T SE APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 105 | ZoneHVAC:EnergyRecoveryVentilator | T SE APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 2.59546E-002 |
| 106 | Fan:OnOff | T SE APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 107 | Fan:OnOff | T SE APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 108 | HeatExchanger:AirToAir:SensibleAndLatent | T SE APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 109 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | T SE APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.48275 |
| 110 | ZoneHVAC:EnergyRecoveryVentilator | T NE APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 111 | ZoneHVAC:EnergyRecoveryVentilator | T NE APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 2.59546E-002 |
| 112 | Fan:OnOff | T NE APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 113 | Fan:OnOff | T NE APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 114 | HeatExchanger:AirToAir:SensibleAndLatent | T NE APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 115 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | T NE APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.48752 |
| 116 | ZoneHVAC:EnergyRecoveryVentilator | T N1 APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 117 | ZoneHVAC:EnergyRecoveryVentilator | T N1 APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 2.59546E-002 |
| 118 | Fan:OnOff | T N1 APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 119 | Fan:OnOff | T N1 APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 120 | HeatExchanger:AirToAir:SensibleAndLatent | T N1 APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 121 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | T N1 APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.45214 |
| 122 | ZoneHVAC:EnergyRecoveryVentilator | T N2 APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 123 | ZoneHVAC:EnergyRecoveryVentilator | T N2 APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 2.59546E-002 |
| 124 | Fan:OnOff | T N2 APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 125 | Fan:OnOff | T N2 APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 126 | HeatExchanger:AirToAir:SensibleAndLatent | T N2 APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 127 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | T N2 APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.44949 |
| 128 | ZoneHVAC:EnergyRecoveryVentilator | T S1 APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 129 | ZoneHVAC:EnergyRecoveryVentilator | T S1 APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 2.59546E-002 |
| 130 | Fan:OnOff | T S1 APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 131 | Fan:OnOff | T S1 APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 132 | HeatExchanger:AirToAir:SensibleAndLatent | T S1 APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 133 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | T S1 APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.44823 |
| 134 | ZoneHVAC:EnergyRecoveryVentilator | T S2 APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 135 | ZoneHVAC:EnergyRecoveryVentilator | T S2 APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 2.59546E-002 |
| 136 | Fan:OnOff | T S2 APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 137 | Fan:OnOff | T S2 APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 138 | HeatExchanger:AirToAir:SensibleAndLatent | T S2 APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 139 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | T S2 APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.44560 |
| 140 | AirLoopHVAC | SPLIT GSW | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.41557 |
| 141 | AirLoopHVAC | SPLIT GSW | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.41557 |
| 142 | AirLoopHVAC | SPLIT GSW | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.41557 |
| 143 | AirLoopHVAC | SPLIT GSW | Adjusted Heating Design Air Flow Rate [m3/s] | 0.41557 |
| 144 | AirLoopHVAC | SPLIT GSW | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.41557 |
| 145 | AirLoopHVAC | SPLIT GSW | Adjusted Main Design Air Flow Rate [m3/s] | 0.41557 |
| 146 | AirLoopHVAC | SPLIT GSW | User Heating Air Flow Ratio [] | 1.00000 |
| 147 | AirLoopHVAC | SPLIT GSW | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 148 | AirLoopHVAC | SPLIT GNW | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.40783 |
| 149 | AirLoopHVAC | SPLIT GNW | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.40783 |
| 150 | AirLoopHVAC | SPLIT GNW | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.40783 |
| 151 | AirLoopHVAC | SPLIT GNW | Adjusted Heating Design Air Flow Rate [m3/s] | 0.40783 |
| 152 | AirLoopHVAC | SPLIT GNW | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.40783 |
| 153 | AirLoopHVAC | SPLIT GNW | Adjusted Main Design Air Flow Rate [m3/s] | 0.40783 |
| 154 | AirLoopHVAC | SPLIT GNW | User Heating Air Flow Ratio [] | 1.00000 |
| 155 | AirLoopHVAC | SPLIT GNW | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 156 | AirLoopHVAC | SPLIT OFFICE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.47035 |
| 157 | AirLoopHVAC | SPLIT OFFICE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.47035 |
| 158 | AirLoopHVAC | SPLIT OFFICE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.47035 |
| 159 | AirLoopHVAC | SPLIT OFFICE | Adjusted Heating Design Air Flow Rate [m3/s] | 0.47035 |
| 160 | AirLoopHVAC | SPLIT OFFICE | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.47035 |
| 161 | AirLoopHVAC | SPLIT OFFICE | Adjusted Main Design Air Flow Rate [m3/s] | 0.47035 |
| 162 | AirLoopHVAC | SPLIT OFFICE | User Heating Air Flow Ratio [] | 1.00000 |
| 163 | AirLoopHVAC | SPLIT OFFICE | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 164 | AirLoopHVAC | SPLIT GNE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.37236 |
| 165 | AirLoopHVAC | SPLIT GNE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.37236 |
| 166 | AirLoopHVAC | SPLIT GNE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.37236 |
| 167 | AirLoopHVAC | SPLIT GNE | Adjusted Heating Design Air Flow Rate [m3/s] | 0.37236 |
| 168 | AirLoopHVAC | SPLIT GNE | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.37236 |
| 169 | AirLoopHVAC | SPLIT GNE | Adjusted Main Design Air Flow Rate [m3/s] | 0.37236 |
| 170 | AirLoopHVAC | SPLIT GNE | User Heating Air Flow Ratio [] | 1.00000 |
| 171 | AirLoopHVAC | SPLIT GNE | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 172 | AirLoopHVAC | SPLIT GN1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.33198 |
| 173 | AirLoopHVAC | SPLIT GN1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.33198 |
| 174 | AirLoopHVAC | SPLIT GN1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.33198 |
| 175 | AirLoopHVAC | SPLIT GN1 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.33198 |
| 176 | AirLoopHVAC | SPLIT GN1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.33198 |
| 177 | AirLoopHVAC | SPLIT GN1 | Adjusted Main Design Air Flow Rate [m3/s] | 0.33198 |
| 178 | AirLoopHVAC | SPLIT GN1 | User Heating Air Flow Ratio [] | 1.00000 |
| 179 | AirLoopHVAC | SPLIT GN1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 180 | AirLoopHVAC | SPLIT GN2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.33129 |
| 181 | AirLoopHVAC | SPLIT GN2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.33129 |
| 182 | AirLoopHVAC | SPLIT GN2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.33129 |
| 183 | AirLoopHVAC | SPLIT GN2 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.33129 |
| 184 | AirLoopHVAC | SPLIT GN2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.33129 |
| 185 | AirLoopHVAC | SPLIT GN2 | Adjusted Main Design Air Flow Rate [m3/s] | 0.33129 |
| 186 | AirLoopHVAC | SPLIT GN2 | User Heating Air Flow Ratio [] | 1.00000 |
| 187 | AirLoopHVAC | SPLIT GN2 | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 188 | AirLoopHVAC | SPLIT GS1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.34216 |
| 189 | AirLoopHVAC | SPLIT GS1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.34216 |
| 190 | AirLoopHVAC | SPLIT GS1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.34216 |
| 191 | AirLoopHVAC | SPLIT GS1 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.34216 |
| 192 | AirLoopHVAC | SPLIT GS1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.34216 |
| 193 | AirLoopHVAC | SPLIT GS1 | Adjusted Main Design Air Flow Rate [m3/s] | 0.34216 |
| 194 | AirLoopHVAC | SPLIT GS1 | User Heating Air Flow Ratio [] | 1.00000 |
| 195 | AirLoopHVAC | SPLIT GS1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 196 | AirLoopHVAC | SPLIT GS2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.34459 |
| 197 | AirLoopHVAC | SPLIT GS2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.34459 |
| 198 | AirLoopHVAC | SPLIT GS2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.34459 |
| 199 | AirLoopHVAC | SPLIT GS2 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.34459 |
| 200 | AirLoopHVAC | SPLIT GS2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.34459 |
| 201 | AirLoopHVAC | SPLIT GS2 | Adjusted Main Design Air Flow Rate [m3/s] | 0.34459 |
| 202 | AirLoopHVAC | SPLIT GS2 | User Heating Air Flow Ratio [] | 1.00000 |
| 203 | AirLoopHVAC | SPLIT GS2 | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 204 | AirLoopHVAC | SPLIT MSW | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.00298 |
| 205 | AirLoopHVAC | SPLIT MSW | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.00298 |
| 206 | AirLoopHVAC | SPLIT MSW | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.00298 |
| 207 | AirLoopHVAC | SPLIT MSW | Adjusted Heating Design Air Flow Rate [m3/s] | 1.00298 |
| 208 | AirLoopHVAC | SPLIT MSW | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.00298 |
| 209 | AirLoopHVAC | SPLIT MSW | Adjusted Main Design Air Flow Rate [m3/s] | 1.00298 |
| 210 | AirLoopHVAC | SPLIT MSW | User Heating Air Flow Ratio [] | 1.00000 |
| 211 | AirLoopHVAC | SPLIT MSW | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 212 | AirLoopHVAC | SPLIT MNW | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.99392 |
| 213 | AirLoopHVAC | SPLIT MNW | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.99392 |
| 214 | AirLoopHVAC | SPLIT MNW | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.99392 |
| 215 | AirLoopHVAC | SPLIT MNW | Adjusted Heating Design Air Flow Rate [m3/s] | 0.99392 |
| 216 | AirLoopHVAC | SPLIT MNW | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.99392 |
| 217 | AirLoopHVAC | SPLIT MNW | Adjusted Main Design Air Flow Rate [m3/s] | 0.99392 |
| 218 | AirLoopHVAC | SPLIT MNW | User Heating Air Flow Ratio [] | 1.00000 |
| 219 | AirLoopHVAC | SPLIT MNW | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 220 | AirLoopHVAC | SPLIT MSE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.89929 |
| 221 | AirLoopHVAC | SPLIT MSE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.89929 |
| 222 | AirLoopHVAC | SPLIT MSE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.89929 |
| 223 | AirLoopHVAC | SPLIT MSE | Adjusted Heating Design Air Flow Rate [m3/s] | 0.89929 |
| 224 | AirLoopHVAC | SPLIT MSE | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.89929 |
| 225 | AirLoopHVAC | SPLIT MSE | Adjusted Main Design Air Flow Rate [m3/s] | 0.89929 |
| 226 | AirLoopHVAC | SPLIT MSE | User Heating Air Flow Ratio [] | 1.00000 |
| 227 | AirLoopHVAC | SPLIT MSE | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 228 | AirLoopHVAC | SPLIT MNE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.89067 |
| 229 | AirLoopHVAC | SPLIT MNE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.89067 |
| 230 | AirLoopHVAC | SPLIT MNE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.89067 |
| 231 | AirLoopHVAC | SPLIT MNE | Adjusted Heating Design Air Flow Rate [m3/s] | 0.89067 |
| 232 | AirLoopHVAC | SPLIT MNE | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.89067 |
| 233 | AirLoopHVAC | SPLIT MNE | Adjusted Main Design Air Flow Rate [m3/s] | 0.89067 |
| 234 | AirLoopHVAC | SPLIT MNE | User Heating Air Flow Ratio [] | 1.00000 |
| 235 | AirLoopHVAC | SPLIT MNE | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 236 | AirLoopHVAC | SPLIT MN1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.79166 |
| 237 | AirLoopHVAC | SPLIT MN1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.79166 |
| 238 | AirLoopHVAC | SPLIT MN1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.79166 |
| 239 | AirLoopHVAC | SPLIT MN1 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.79166 |
| 240 | AirLoopHVAC | SPLIT MN1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.79166 |
| 241 | AirLoopHVAC | SPLIT MN1 | Adjusted Main Design Air Flow Rate [m3/s] | 0.79166 |
| 242 | AirLoopHVAC | SPLIT MN1 | User Heating Air Flow Ratio [] | 1.00000 |
| 243 | AirLoopHVAC | SPLIT MN1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 244 | AirLoopHVAC | SPLIT MN2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.78963 |
| 245 | AirLoopHVAC | SPLIT MN2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.78963 |
| 246 | AirLoopHVAC | SPLIT MN2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.78963 |
| 247 | AirLoopHVAC | SPLIT MN2 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.78963 |
| 248 | AirLoopHVAC | SPLIT MN2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.78963 |
| 249 | AirLoopHVAC | SPLIT MN2 | Adjusted Main Design Air Flow Rate [m3/s] | 0.78963 |
| 250 | AirLoopHVAC | SPLIT MN2 | User Heating Air Flow Ratio [] | 1.00000 |
| 251 | AirLoopHVAC | SPLIT MN2 | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 252 | AirLoopHVAC | SPLIT MS1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.80436 |
| 253 | AirLoopHVAC | SPLIT MS1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.80436 |
| 254 | AirLoopHVAC | SPLIT MS1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.80436 |
| 255 | AirLoopHVAC | SPLIT MS1 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.80436 |
| 256 | AirLoopHVAC | SPLIT MS1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.80436 |
| 257 | AirLoopHVAC | SPLIT MS1 | Adjusted Main Design Air Flow Rate [m3/s] | 0.80436 |
| 258 | AirLoopHVAC | SPLIT MS1 | User Heating Air Flow Ratio [] | 1.00000 |
| 259 | AirLoopHVAC | SPLIT MS1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 260 | AirLoopHVAC | SPLIT MS2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.80226 |
| 261 | AirLoopHVAC | SPLIT MS2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.80226 |
| 262 | AirLoopHVAC | SPLIT MS2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.80226 |
| 263 | AirLoopHVAC | SPLIT MS2 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.80226 |
| 264 | AirLoopHVAC | SPLIT MS2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.80226 |
| 265 | AirLoopHVAC | SPLIT MS2 | Adjusted Main Design Air Flow Rate [m3/s] | 0.80226 |
| 266 | AirLoopHVAC | SPLIT MS2 | User Heating Air Flow Ratio [] | 1.00000 |
| 267 | AirLoopHVAC | SPLIT MS2 | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 268 | AirLoopHVAC | SPLIT TSW | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.55936 |
| 269 | AirLoopHVAC | SPLIT TSW | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.55936 |
| 270 | AirLoopHVAC | SPLIT TSW | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.55936 |
| 271 | AirLoopHVAC | SPLIT TSW | Adjusted Heating Design Air Flow Rate [m3/s] | 0.55936 |
| 272 | AirLoopHVAC | SPLIT TSW | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.55936 |
| 273 | AirLoopHVAC | SPLIT TSW | Adjusted Main Design Air Flow Rate [m3/s] | 0.55936 |
| 274 | AirLoopHVAC | SPLIT TSW | User Heating Air Flow Ratio [] | 1.00000 |
| 275 | AirLoopHVAC | SPLIT TSW | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 276 | AirLoopHVAC | SPLIT TNW | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.56433 |
| 277 | AirLoopHVAC | SPLIT TNW | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.56433 |
| 278 | AirLoopHVAC | SPLIT TNW | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.56433 |
| 279 | AirLoopHVAC | SPLIT TNW | Adjusted Heating Design Air Flow Rate [m3/s] | 0.56433 |
| 280 | AirLoopHVAC | SPLIT TNW | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.56433 |
| 281 | AirLoopHVAC | SPLIT TNW | Adjusted Main Design Air Flow Rate [m3/s] | 0.56433 |
| 282 | AirLoopHVAC | SPLIT TNW | User Heating Air Flow Ratio [] | 1.00000 |
| 283 | AirLoopHVAC | SPLIT TNW | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 284 | AirLoopHVAC | SPLIT TSE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.48275 |
| 285 | AirLoopHVAC | SPLIT TSE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.48275 |
| 286 | AirLoopHVAC | SPLIT TSE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.48275 |
| 287 | AirLoopHVAC | SPLIT TSE | Adjusted Heating Design Air Flow Rate [m3/s] | 0.48275 |
| 288 | AirLoopHVAC | SPLIT TSE | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.48275 |
| 289 | AirLoopHVAC | SPLIT TSE | Adjusted Main Design Air Flow Rate [m3/s] | 0.48275 |
| 290 | AirLoopHVAC | SPLIT TSE | User Heating Air Flow Ratio [] | 1.00000 |
| 291 | AirLoopHVAC | SPLIT TSE | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 292 | AirLoopHVAC | SPLIT TNE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.48752 |
| 293 | AirLoopHVAC | SPLIT TNE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.48752 |
| 294 | AirLoopHVAC | SPLIT TNE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.48752 |
| 295 | AirLoopHVAC | SPLIT TNE | Adjusted Heating Design Air Flow Rate [m3/s] | 0.48752 |
| 296 | AirLoopHVAC | SPLIT TNE | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.48752 |
| 297 | AirLoopHVAC | SPLIT TNE | Adjusted Main Design Air Flow Rate [m3/s] | 0.48752 |
| 298 | AirLoopHVAC | SPLIT TNE | User Heating Air Flow Ratio [] | 1.00000 |
| 299 | AirLoopHVAC | SPLIT TNE | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 300 | AirLoopHVAC | SPLIT TN1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.45214 |
| 301 | AirLoopHVAC | SPLIT TN1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.45214 |
| 302 | AirLoopHVAC | SPLIT TN1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.45214 |
| 303 | AirLoopHVAC | SPLIT TN1 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.45214 |
| 304 | AirLoopHVAC | SPLIT TN1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.45214 |
| 305 | AirLoopHVAC | SPLIT TN1 | Adjusted Main Design Air Flow Rate [m3/s] | 0.45214 |
| 306 | AirLoopHVAC | SPLIT TN1 | User Heating Air Flow Ratio [] | 1.00000 |
| 307 | AirLoopHVAC | SPLIT TN1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 308 | AirLoopHVAC | SPLIT TN2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.44949 |
| 309 | AirLoopHVAC | SPLIT TN2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.44949 |
| 310 | AirLoopHVAC | SPLIT TN2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.44949 |
| 311 | AirLoopHVAC | SPLIT TN2 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.44949 |
| 312 | AirLoopHVAC | SPLIT TN2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.44949 |
| 313 | AirLoopHVAC | SPLIT TN2 | Adjusted Main Design Air Flow Rate [m3/s] | 0.44949 |
| 314 | AirLoopHVAC | SPLIT TN2 | User Heating Air Flow Ratio [] | 1.00000 |
| 315 | AirLoopHVAC | SPLIT TN2 | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 316 | AirLoopHVAC | SPLIT TS1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.44823 |
| 317 | AirLoopHVAC | SPLIT TS1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.44823 |
| 318 | AirLoopHVAC | SPLIT TS1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.44823 |
| 319 | AirLoopHVAC | SPLIT TS1 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.44823 |
| 320 | AirLoopHVAC | SPLIT TS1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.44823 |
| 321 | AirLoopHVAC | SPLIT TS1 | Adjusted Main Design Air Flow Rate [m3/s] | 0.44823 |
| 322 | AirLoopHVAC | SPLIT TS1 | User Heating Air Flow Ratio [] | 1.00000 |
| 323 | AirLoopHVAC | SPLIT TS1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 324 | AirLoopHVAC | SPLIT TS2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.44560 |
| 325 | AirLoopHVAC | SPLIT TS2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.44560 |
| 326 | AirLoopHVAC | SPLIT TS2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.44560 |
| 327 | AirLoopHVAC | SPLIT TS2 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.44560 |
| 328 | AirLoopHVAC | SPLIT TS2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.44560 |
| 329 | AirLoopHVAC | SPLIT TS2 | Adjusted Main Design Air Flow Rate [m3/s] | 0.44560 |
| 330 | AirLoopHVAC | SPLIT TS2 | User Heating Air Flow Ratio [] | 1.00000 |
| 331 | AirLoopHVAC | SPLIT TS2 | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 332 | AirLoopHVAC | SPLIT GSW | Design Supply Air Flow Rate [m3/s] | 0.41557 |
| 333 | AirLoopHVAC | SPLIT GNW | Design Supply Air Flow Rate [m3/s] | 0.40783 |
| 334 | AirLoopHVAC | SPLIT OFFICE | Design Supply Air Flow Rate [m3/s] | 0.47035 |
| 335 | AirLoopHVAC | SPLIT GNE | Design Supply Air Flow Rate [m3/s] | 0.37236 |
| 336 | AirLoopHVAC | SPLIT GN1 | Design Supply Air Flow Rate [m3/s] | 0.33198 |
| 337 | AirLoopHVAC | SPLIT GN2 | Design Supply Air Flow Rate [m3/s] | 0.33129 |
| 338 | AirLoopHVAC | SPLIT GS1 | Design Supply Air Flow Rate [m3/s] | 0.34216 |
| 339 | AirLoopHVAC | SPLIT GS2 | Design Supply Air Flow Rate [m3/s] | 0.34459 |
| 340 | AirLoopHVAC | SPLIT MSW | Design Supply Air Flow Rate [m3/s] | 1.00298 |
| 341 | AirLoopHVAC | SPLIT MNW | Design Supply Air Flow Rate [m3/s] | 0.99392 |
| 342 | AirLoopHVAC | SPLIT MSE | Design Supply Air Flow Rate [m3/s] | 0.89929 |
| 343 | AirLoopHVAC | SPLIT MNE | Design Supply Air Flow Rate [m3/s] | 0.89067 |
| 344 | AirLoopHVAC | SPLIT MN1 | Design Supply Air Flow Rate [m3/s] | 0.79166 |
| 345 | AirLoopHVAC | SPLIT MN2 | Design Supply Air Flow Rate [m3/s] | 0.78963 |
| 346 | AirLoopHVAC | SPLIT MS1 | Design Supply Air Flow Rate [m3/s] | 0.80436 |
| 347 | AirLoopHVAC | SPLIT MS2 | Design Supply Air Flow Rate [m3/s] | 0.80226 |
| 348 | AirLoopHVAC | SPLIT TSW | Design Supply Air Flow Rate [m3/s] | 0.55936 |
| 349 | AirLoopHVAC | SPLIT TNW | Design Supply Air Flow Rate [m3/s] | 0.56433 |
| 350 | AirLoopHVAC | SPLIT TSE | Design Supply Air Flow Rate [m3/s] | 0.48275 |
| 351 | AirLoopHVAC | SPLIT TNE | Design Supply Air Flow Rate [m3/s] | 0.48752 |
| 352 | AirLoopHVAC | SPLIT TN1 | Design Supply Air Flow Rate [m3/s] | 0.45214 |
| 353 | AirLoopHVAC | SPLIT TN2 | Design Supply Air Flow Rate [m3/s] | 0.44949 |
| 354 | AirLoopHVAC | SPLIT TS1 | Design Supply Air Flow Rate [m3/s] | 0.44823 |
| 355 | AirLoopHVAC | SPLIT TS2 | Design Supply Air Flow Rate [m3/s] | 0.44560 |
| 356 | Controller:OutdoorAir | SPLIT GSW_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.41557 |
| 357 | Controller:OutdoorAir | SPLIT GSW_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.59546E-002 |
| 358 | AirLoopHVAC:UnitarySystem | SPLIT GSW_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.41557 |
| 359 | AirLoopHVAC:UnitarySystem | SPLIT GSW_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.41557 |
| 360 | AirLoopHVAC:UnitarySystem | SPLIT GSW_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.41557 |
| 361 | AirLoopHVAC:UnitarySystem | SPLIT GSW_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.41557 |
| 362 | AirLoopHVAC:UnitarySystem | SPLIT GSW_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 6879.08241 |
| 363 | AirLoopHVAC:UnitarySystem | SPLIT GSW_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 8565.90062 |
| 364 | AirLoopHVAC:UnitarySystem | SPLIT GSW_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 365 | AirLoopHVAC:UnitarySystem | SPLIT GSW_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 366 | Fan:OnOff | SPLIT GSW SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.41557 |
| 367 | Coil:Cooling:DX:SingleSpeed | SPLIT GSW COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.41557 |
| 368 | Coil:Cooling:DX:SingleSpeed | SPLIT GSW COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 6879.08241 |
| 369 | Coil:Cooling:DX:SingleSpeed | SPLIT GSW COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
| 370 | Coil:Heating:Fuel | SPLIT GSW HEATING COIL | Design Size Nominal Capacity [W] | 8565.90062 |
| 371 | Controller:OutdoorAir | SPLIT GNW_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.40783 |
| 372 | Controller:OutdoorAir | SPLIT GNW_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.59546E-002 |
| 373 | AirLoopHVAC:UnitarySystem | SPLIT GNW_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.40783 |
| 374 | AirLoopHVAC:UnitarySystem | SPLIT GNW_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.40783 |
| 375 | AirLoopHVAC:UnitarySystem | SPLIT GNW_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.40783 |
| 376 | AirLoopHVAC:UnitarySystem | SPLIT GNW_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.40783 |
| 377 | AirLoopHVAC:UnitarySystem | SPLIT GNW_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 6751.07785 |
| 378 | AirLoopHVAC:UnitarySystem | SPLIT GNW_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 8420.38610 |
| 379 | AirLoopHVAC:UnitarySystem | SPLIT GNW_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 380 | AirLoopHVAC:UnitarySystem | SPLIT GNW_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 381 | Fan:OnOff | SPLIT GNW SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.40783 |
| 382 | Coil:Cooling:DX:SingleSpeed | SPLIT GNW COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.40783 |
| 383 | Coil:Cooling:DX:SingleSpeed | SPLIT GNW COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 6751.07785 |
| 384 | Coil:Cooling:DX:SingleSpeed | SPLIT GNW COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
| 385 | Coil:Heating:Fuel | SPLIT GNW HEATING COIL | Design Size Nominal Capacity [W] | 8420.38610 |
| 386 | Controller:OutdoorAir | SPLIT OFFICE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.47035 |
| 387 | Controller:OutdoorAir | SPLIT OFFICE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 3.81060E-002 |
| 388 | AirLoopHVAC:UnitarySystem | SPLIT OFFICE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.47035 |
| 389 | AirLoopHVAC:UnitarySystem | SPLIT OFFICE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.47035 |
| 390 | AirLoopHVAC:UnitarySystem | SPLIT OFFICE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.47035 |
| 391 | AirLoopHVAC:UnitarySystem | SPLIT OFFICE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.47035 |
| 392 | AirLoopHVAC:UnitarySystem | SPLIT OFFICE_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 7785.99379 |
| 393 | AirLoopHVAC:UnitarySystem | SPLIT OFFICE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 9947.14494 |
| 394 | AirLoopHVAC:UnitarySystem | SPLIT OFFICE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 395 | AirLoopHVAC:UnitarySystem | SPLIT OFFICE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 396 | Fan:OnOff | SPLIT OFFICE SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.47035 |
| 397 | Coil:Cooling:DX:SingleSpeed | SPLIT OFFICE COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.47035 |
| 398 | Coil:Cooling:DX:SingleSpeed | SPLIT OFFICE COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 7785.99379 |
| 399 | Coil:Cooling:DX:SingleSpeed | SPLIT OFFICE COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
| 400 | Coil:Heating:Fuel | SPLIT OFFICE HEATING COIL | Design Size Nominal Capacity [W] | 9947.14494 |
| 401 | Controller:OutdoorAir | SPLIT GNE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.37236 |
| 402 | Controller:OutdoorAir | SPLIT GNE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.59546E-002 |
| 403 | AirLoopHVAC:UnitarySystem | SPLIT GNE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.37236 |
| 404 | AirLoopHVAC:UnitarySystem | SPLIT GNE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.37236 |
| 405 | AirLoopHVAC:UnitarySystem | SPLIT GNE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.37236 |
| 406 | AirLoopHVAC:UnitarySystem | SPLIT GNE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.37236 |
| 407 | AirLoopHVAC:UnitarySystem | SPLIT GNE_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 6163.81994 |
| 408 | AirLoopHVAC:UnitarySystem | SPLIT GNE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 7753.07986 |
| 409 | AirLoopHVAC:UnitarySystem | SPLIT GNE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 410 | AirLoopHVAC:UnitarySystem | SPLIT GNE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 411 | Fan:OnOff | SPLIT GNE SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.37236 |
| 412 | Coil:Cooling:DX:SingleSpeed | SPLIT GNE COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.37236 |
| 413 | Coil:Cooling:DX:SingleSpeed | SPLIT GNE COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 6163.81994 |
| 414 | Coil:Cooling:DX:SingleSpeed | SPLIT GNE COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
| 415 | Coil:Heating:Fuel | SPLIT GNE HEATING COIL | Design Size Nominal Capacity [W] | 7753.07986 |
| 416 | Controller:OutdoorAir | SPLIT GN1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.33198 |
| 417 | Controller:OutdoorAir | SPLIT GN1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.59546E-002 |
| 418 | AirLoopHVAC:UnitarySystem | SPLIT GN1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.33198 |
| 419 | AirLoopHVAC:UnitarySystem | SPLIT GN1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.33198 |
| 420 | AirLoopHVAC:UnitarySystem | SPLIT GN1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.33198 |
| 421 | AirLoopHVAC:UnitarySystem | SPLIT GN1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.33198 |
| 422 | AirLoopHVAC:UnitarySystem | SPLIT GN1_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 5495.51946 |
| 423 | AirLoopHVAC:UnitarySystem | SPLIT GN1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 6993.62911 |
| 424 | AirLoopHVAC:UnitarySystem | SPLIT GN1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 425 | AirLoopHVAC:UnitarySystem | SPLIT GN1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 426 | Fan:OnOff | SPLIT GN1 SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.33198 |
| 427 | Coil:Cooling:DX:SingleSpeed | SPLIT GN1 COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.33198 |
| 428 | Coil:Cooling:DX:SingleSpeed | SPLIT GN1 COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 5495.51946 |
| 429 | Coil:Cooling:DX:SingleSpeed | SPLIT GN1 COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
| 430 | Coil:Heating:Fuel | SPLIT GN1 HEATING COIL | Design Size Nominal Capacity [W] | 6993.62911 |
| 431 | Controller:OutdoorAir | SPLIT GN2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.33129 |
| 432 | Controller:OutdoorAir | SPLIT GN2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.59546E-002 |
| 433 | AirLoopHVAC:UnitarySystem | SPLIT GN2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.33129 |
| 434 | AirLoopHVAC:UnitarySystem | SPLIT GN2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.33129 |
| 435 | AirLoopHVAC:UnitarySystem | SPLIT GN2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.33129 |
| 436 | AirLoopHVAC:UnitarySystem | SPLIT GN2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.33129 |
| 437 | AirLoopHVAC:UnitarySystem | SPLIT GN2_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 5483.97767 |
| 438 | AirLoopHVAC:UnitarySystem | SPLIT GN2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 6980.51420 |
| 439 | AirLoopHVAC:UnitarySystem | SPLIT GN2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 440 | AirLoopHVAC:UnitarySystem | SPLIT GN2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 441 | Fan:OnOff | SPLIT GN2 SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.33129 |
| 442 | Coil:Cooling:DX:SingleSpeed | SPLIT GN2 COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.33129 |
| 443 | Coil:Cooling:DX:SingleSpeed | SPLIT GN2 COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 5483.97767 |
| 444 | Coil:Cooling:DX:SingleSpeed | SPLIT GN2 COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
| 445 | Coil:Heating:Fuel | SPLIT GN2 HEATING COIL | Design Size Nominal Capacity [W] | 6980.51420 |
| 446 | Controller:OutdoorAir | SPLIT GS1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.34216 |
| 447 | Controller:OutdoorAir | SPLIT GS1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.59546E-002 |
| 448 | AirLoopHVAC:UnitarySystem | SPLIT GS1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.34216 |
| 449 | AirLoopHVAC:UnitarySystem | SPLIT GS1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.34216 |
| 450 | AirLoopHVAC:UnitarySystem | SPLIT GS1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.34216 |
| 451 | AirLoopHVAC:UnitarySystem | SPLIT GS1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.34216 |
| 452 | AirLoopHVAC:UnitarySystem | SPLIT GS1_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 5663.91595 |
| 453 | AirLoopHVAC:UnitarySystem | SPLIT GS1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 7185.03530 |
| 454 | AirLoopHVAC:UnitarySystem | SPLIT GS1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 455 | AirLoopHVAC:UnitarySystem | SPLIT GS1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 456 | Fan:OnOff | SPLIT GS1 SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.34216 |
| 457 | Coil:Cooling:DX:SingleSpeed | SPLIT GS1 COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.34216 |
| 458 | Coil:Cooling:DX:SingleSpeed | SPLIT GS1 COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 5663.91595 |
| 459 | Coil:Cooling:DX:SingleSpeed | SPLIT GS1 COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
| 460 | Coil:Heating:Fuel | SPLIT GS1 HEATING COIL | Design Size Nominal Capacity [W] | 7185.03530 |
| 461 | Controller:OutdoorAir | SPLIT GS2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.34459 |
| 462 | Controller:OutdoorAir | SPLIT GS2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.59546E-002 |
| 463 | AirLoopHVAC:UnitarySystem | SPLIT GS2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.34459 |
| 464 | AirLoopHVAC:UnitarySystem | SPLIT GS2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.34459 |
| 465 | AirLoopHVAC:UnitarySystem | SPLIT GS2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.34459 |
| 466 | AirLoopHVAC:UnitarySystem | SPLIT GS2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.34459 |
| 467 | AirLoopHVAC:UnitarySystem | SPLIT GS2_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 5704.21556 |
| 468 | AirLoopHVAC:UnitarySystem | SPLIT GS2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 7230.82809 |
| 469 | AirLoopHVAC:UnitarySystem | SPLIT GS2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 470 | AirLoopHVAC:UnitarySystem | SPLIT GS2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 471 | Fan:OnOff | SPLIT GS2 SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.34459 |
| 472 | Coil:Cooling:DX:SingleSpeed | SPLIT GS2 COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.34459 |
| 473 | Coil:Cooling:DX:SingleSpeed | SPLIT GS2 COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 5704.21556 |
| 474 | Coil:Cooling:DX:SingleSpeed | SPLIT GS2 COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
| 475 | Coil:Heating:Fuel | SPLIT GS2 HEATING COIL | Design Size Nominal Capacity [W] | 7230.82809 |
| 476 | Controller:OutdoorAir | SPLIT MSW_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.00298 |
| 477 | Controller:OutdoorAir | SPLIT MSW_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 5.19091E-002 |
| 478 | AirLoopHVAC:UnitarySystem | SPLIT MSW_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.00298 |
| 479 | AirLoopHVAC:UnitarySystem | SPLIT MSW_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.00298 |
| 480 | AirLoopHVAC:UnitarySystem | SPLIT MSW_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.00298 |
| 481 | AirLoopHVAC:UnitarySystem | SPLIT MSW_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.00298 |
| 482 | AirLoopHVAC:UnitarySystem | SPLIT MSW_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 16602.93985 |
| 483 | AirLoopHVAC:UnitarySystem | SPLIT MSW_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 20364.97527 |
| 484 | AirLoopHVAC:UnitarySystem | SPLIT MSW_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 485 | AirLoopHVAC:UnitarySystem | SPLIT MSW_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 486 | Fan:OnOff | SPLIT MSW SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 1.00298 |
| 487 | Coil:Cooling:DX:SingleSpeed | SPLIT MSW COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 1.00298 |
| 488 | Coil:Cooling:DX:SingleSpeed | SPLIT MSW COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 16602.93985 |
| 489 | Coil:Cooling:DX:SingleSpeed | SPLIT MSW COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
| 490 | Coil:Heating:Fuel | SPLIT MSW HEATING COIL | Design Size Nominal Capacity [W] | 20364.97527 |
| 491 | Controller:OutdoorAir | SPLIT MNW_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.99392 |
| 492 | Controller:OutdoorAir | SPLIT MNW_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 5.19091E-002 |
| 493 | AirLoopHVAC:UnitarySystem | SPLIT MNW_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.99392 |
| 494 | AirLoopHVAC:UnitarySystem | SPLIT MNW_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.99392 |
| 495 | AirLoopHVAC:UnitarySystem | SPLIT MNW_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.99392 |
| 496 | AirLoopHVAC:UnitarySystem | SPLIT MNW_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.99392 |
| 497 | AirLoopHVAC:UnitarySystem | SPLIT MNW_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 16452.97617 |
| 498 | AirLoopHVAC:UnitarySystem | SPLIT MNW_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 20194.23804 |
| 499 | AirLoopHVAC:UnitarySystem | SPLIT MNW_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 500 | AirLoopHVAC:UnitarySystem | SPLIT MNW_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 501 | Fan:OnOff | SPLIT MNW SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.99392 |
| 502 | Coil:Cooling:DX:SingleSpeed | SPLIT MNW COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.99392 |
| 503 | Coil:Cooling:DX:SingleSpeed | SPLIT MNW COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 16452.97617 |
| 504 | Coil:Cooling:DX:SingleSpeed | SPLIT MNW COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
| 505 | Coil:Heating:Fuel | SPLIT MNW HEATING COIL | Design Size Nominal Capacity [W] | 20194.23804 |
| 506 | Controller:OutdoorAir | SPLIT MSE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.89929 |
| 507 | Controller:OutdoorAir | SPLIT MSE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 5.19091E-002 |
| 508 | AirLoopHVAC:UnitarySystem | SPLIT MSE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.89929 |
| 509 | AirLoopHVAC:UnitarySystem | SPLIT MSE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.89929 |
| 510 | AirLoopHVAC:UnitarySystem | SPLIT MSE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.89929 |
| 511 | AirLoopHVAC:UnitarySystem | SPLIT MSE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.89929 |
| 512 | AirLoopHVAC:UnitarySystem | SPLIT MSE_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 14886.40728 |
| 513 | AirLoopHVAC:UnitarySystem | SPLIT MSE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 18414.38211 |
| 514 | AirLoopHVAC:UnitarySystem | SPLIT MSE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 515 | AirLoopHVAC:UnitarySystem | SPLIT MSE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 516 | Fan:OnOff | SPLIT MSE SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.89929 |
| 517 | Coil:Cooling:DX:SingleSpeed | SPLIT MSE COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.89929 |
| 518 | Coil:Cooling:DX:SingleSpeed | SPLIT MSE COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 14886.40728 |
| 519 | Coil:Cooling:DX:SingleSpeed | SPLIT MSE COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
| 520 | Coil:Heating:Fuel | SPLIT MSE HEATING COIL | Design Size Nominal Capacity [W] | 18414.38211 |
| 521 | Controller:OutdoorAir | SPLIT MNE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.89067 |
| 522 | Controller:OutdoorAir | SPLIT MNE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 5.19091E-002 |
| 523 | AirLoopHVAC:UnitarySystem | SPLIT MNE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.89067 |
| 524 | AirLoopHVAC:UnitarySystem | SPLIT MNE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.89067 |
| 525 | AirLoopHVAC:UnitarySystem | SPLIT MNE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.89067 |
| 526 | AirLoopHVAC:UnitarySystem | SPLIT MNE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.89067 |
| 527 | AirLoopHVAC:UnitarySystem | SPLIT MNE_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 14743.70516 |
| 528 | AirLoopHVAC:UnitarySystem | SPLIT MNE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 18251.93223 |
| 529 | AirLoopHVAC:UnitarySystem | SPLIT MNE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 530 | AirLoopHVAC:UnitarySystem | SPLIT MNE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 531 | Fan:OnOff | SPLIT MNE SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.89067 |
| 532 | Coil:Cooling:DX:SingleSpeed | SPLIT MNE COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.89067 |
| 533 | Coil:Cooling:DX:SingleSpeed | SPLIT MNE COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 14743.70516 |
| 534 | Coil:Cooling:DX:SingleSpeed | SPLIT MNE COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
| 535 | Coil:Heating:Fuel | SPLIT MNE HEATING COIL | Design Size Nominal Capacity [W] | 18251.93223 |
| 536 | Controller:OutdoorAir | SPLIT MN1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.79166 |
| 537 | Controller:OutdoorAir | SPLIT MN1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 5.19091E-002 |
| 538 | AirLoopHVAC:UnitarySystem | SPLIT MN1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.79166 |
| 539 | AirLoopHVAC:UnitarySystem | SPLIT MN1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.79166 |
| 540 | AirLoopHVAC:UnitarySystem | SPLIT MN1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.79166 |
| 541 | AirLoopHVAC:UnitarySystem | SPLIT MN1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.79166 |
| 542 | AirLoopHVAC:UnitarySystem | SPLIT MN1_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 13104.72774 |
| 543 | AirLoopHVAC:UnitarySystem | SPLIT MN1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 16389.21096 |
| 544 | AirLoopHVAC:UnitarySystem | SPLIT MN1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 545 | AirLoopHVAC:UnitarySystem | SPLIT MN1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 546 | Fan:OnOff | SPLIT MN1 SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.79166 |
| 547 | Coil:Cooling:DX:SingleSpeed | SPLIT MN1 COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.79166 |
| 548 | Coil:Cooling:DX:SingleSpeed | SPLIT MN1 COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 13104.72774 |
| 549 | Coil:Cooling:DX:SingleSpeed | SPLIT MN1 COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
| 550 | Coil:Heating:Fuel | SPLIT MN1 HEATING COIL | Design Size Nominal Capacity [W] | 16389.21096 |
| 551 | Controller:OutdoorAir | SPLIT MN2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.78963 |
| 552 | Controller:OutdoorAir | SPLIT MN2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 5.19091E-002 |
| 553 | AirLoopHVAC:UnitarySystem | SPLIT MN2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.78963 |
| 554 | AirLoopHVAC:UnitarySystem | SPLIT MN2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.78963 |
| 555 | AirLoopHVAC:UnitarySystem | SPLIT MN2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.78963 |
| 556 | AirLoopHVAC:UnitarySystem | SPLIT MN2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.78963 |
| 557 | AirLoopHVAC:UnitarySystem | SPLIT MN2_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 13071.14025 |
| 558 | AirLoopHVAC:UnitarySystem | SPLIT MN2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 16351.04509 |
| 559 | AirLoopHVAC:UnitarySystem | SPLIT MN2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 560 | AirLoopHVAC:UnitarySystem | SPLIT MN2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 561 | Fan:OnOff | SPLIT MN2 SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.78963 |
| 562 | Coil:Cooling:DX:SingleSpeed | SPLIT MN2 COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.78963 |
| 563 | Coil:Cooling:DX:SingleSpeed | SPLIT MN2 COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 13071.14025 |
| 564 | Coil:Cooling:DX:SingleSpeed | SPLIT MN2 COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
| 565 | Coil:Heating:Fuel | SPLIT MN2 HEATING COIL | Design Size Nominal Capacity [W] | 16351.04509 |
| 566 | Controller:OutdoorAir | SPLIT MS1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.80436 |
| 567 | Controller:OutdoorAir | SPLIT MS1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 5.19091E-002 |
| 568 | AirLoopHVAC:UnitarySystem | SPLIT MS1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.80436 |
| 569 | AirLoopHVAC:UnitarySystem | SPLIT MS1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.80436 |
| 570 | AirLoopHVAC:UnitarySystem | SPLIT MS1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.80436 |
| 571 | AirLoopHVAC:UnitarySystem | SPLIT MS1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.80436 |
| 572 | AirLoopHVAC:UnitarySystem | SPLIT MS1_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 13314.98719 |
| 573 | AirLoopHVAC:UnitarySystem | SPLIT MS1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 16628.40728 |
| 574 | AirLoopHVAC:UnitarySystem | SPLIT MS1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 575 | AirLoopHVAC:UnitarySystem | SPLIT MS1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 576 | Fan:OnOff | SPLIT MS1 SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.80436 |
| 577 | Coil:Cooling:DX:SingleSpeed | SPLIT MS1 COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.80436 |
| 578 | Coil:Cooling:DX:SingleSpeed | SPLIT MS1 COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 13314.98719 |
| 579 | Coil:Cooling:DX:SingleSpeed | SPLIT MS1 COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
| 580 | Coil:Heating:Fuel | SPLIT MS1 HEATING COIL | Design Size Nominal Capacity [W] | 16628.40728 |
| 581 | Controller:OutdoorAir | SPLIT MS2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.80226 |
| 582 | Controller:OutdoorAir | SPLIT MS2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 5.19091E-002 |
| 583 | AirLoopHVAC:UnitarySystem | SPLIT MS2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.80226 |
| 584 | AirLoopHVAC:UnitarySystem | SPLIT MS2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.80226 |
| 585 | AirLoopHVAC:UnitarySystem | SPLIT MS2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.80226 |
| 586 | AirLoopHVAC:UnitarySystem | SPLIT MS2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.80226 |
| 587 | AirLoopHVAC:UnitarySystem | SPLIT MS2_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 13280.22899 |
| 588 | AirLoopHVAC:UnitarySystem | SPLIT MS2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 16588.91036 |
| 589 | AirLoopHVAC:UnitarySystem | SPLIT MS2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 590 | AirLoopHVAC:UnitarySystem | SPLIT MS2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 591 | Fan:OnOff | SPLIT MS2 SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.80226 |
| 592 | Coil:Cooling:DX:SingleSpeed | SPLIT MS2 COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.80226 |
| 593 | Coil:Cooling:DX:SingleSpeed | SPLIT MS2 COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 13280.22899 |
| 594 | Coil:Cooling:DX:SingleSpeed | SPLIT MS2 COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
| 595 | Coil:Heating:Fuel | SPLIT MS2 HEATING COIL | Design Size Nominal Capacity [W] | 16588.91036 |
| 596 | Controller:OutdoorAir | SPLIT TSW_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.55936 |
| 597 | Controller:OutdoorAir | SPLIT TSW_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.59546E-002 |
| 598 | AirLoopHVAC:UnitarySystem | SPLIT TSW_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.55936 |
| 599 | AirLoopHVAC:UnitarySystem | SPLIT TSW_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.55936 |
| 600 | AirLoopHVAC:UnitarySystem | SPLIT TSW_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.55936 |
| 601 | AirLoopHVAC:UnitarySystem | SPLIT TSW_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.55936 |
| 602 | AirLoopHVAC:UnitarySystem | SPLIT TSW_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 9259.35413 |
| 603 | AirLoopHVAC:UnitarySystem | SPLIT TSW_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 11271.18447 |
| 604 | AirLoopHVAC:UnitarySystem | SPLIT TSW_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 605 | AirLoopHVAC:UnitarySystem | SPLIT TSW_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 606 | Fan:OnOff | SPLIT TSW SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.55936 |
| 607 | Coil:Cooling:DX:SingleSpeed | SPLIT TSW COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.55936 |
| 608 | Coil:Cooling:DX:SingleSpeed | SPLIT TSW COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 9259.35413 |
| 609 | Coil:Cooling:DX:SingleSpeed | SPLIT TSW COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
| 610 | Coil:Heating:Fuel | SPLIT TSW HEATING COIL | Design Size Nominal Capacity [W] | 11271.18447 |
| 611 | Controller:OutdoorAir | SPLIT TNW_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.56433 |
| 612 | Controller:OutdoorAir | SPLIT TNW_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.59546E-002 |
| 613 | AirLoopHVAC:UnitarySystem | SPLIT TNW_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.56433 |
| 614 | AirLoopHVAC:UnitarySystem | SPLIT TNW_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.56433 |
| 615 | AirLoopHVAC:UnitarySystem | SPLIT TNW_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.56433 |
| 616 | AirLoopHVAC:UnitarySystem | SPLIT TNW_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.56433 |
| 617 | AirLoopHVAC:UnitarySystem | SPLIT TNW_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 9341.71958 |
| 618 | AirLoopHVAC:UnitarySystem | SPLIT TNW_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 11364.59319 |
| 619 | AirLoopHVAC:UnitarySystem | SPLIT TNW_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 620 | AirLoopHVAC:UnitarySystem | SPLIT TNW_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 621 | Fan:OnOff | SPLIT TNW SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.56433 |
| 622 | Coil:Cooling:DX:SingleSpeed | SPLIT TNW COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.56433 |
| 623 | Coil:Cooling:DX:SingleSpeed | SPLIT TNW COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 9341.71958 |
| 624 | Coil:Cooling:DX:SingleSpeed | SPLIT TNW COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
| 625 | Coil:Heating:Fuel | SPLIT TNW HEATING COIL | Design Size Nominal Capacity [W] | 11364.59319 |
| 626 | Controller:OutdoorAir | SPLIT TSE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.48275 |
| 627 | Controller:OutdoorAir | SPLIT TSE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.59546E-002 |
| 628 | AirLoopHVAC:UnitarySystem | SPLIT TSE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.48275 |
| 629 | AirLoopHVAC:UnitarySystem | SPLIT TSE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.48275 |
| 630 | AirLoopHVAC:UnitarySystem | SPLIT TSE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.48275 |
| 631 | AirLoopHVAC:UnitarySystem | SPLIT TSE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.48275 |
| 632 | AirLoopHVAC:UnitarySystem | SPLIT TSE_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 7991.25648 |
| 633 | AirLoopHVAC:UnitarySystem | SPLIT TSE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 9830.14475 |
| 634 | AirLoopHVAC:UnitarySystem | SPLIT TSE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 635 | AirLoopHVAC:UnitarySystem | SPLIT TSE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 636 | Fan:OnOff | SPLIT TSE SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.48275 |
| 637 | Coil:Cooling:DX:SingleSpeed | SPLIT TSE COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.48275 |
| 638 | Coil:Cooling:DX:SingleSpeed | SPLIT TSE COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 7991.25648 |
| 639 | Coil:Cooling:DX:SingleSpeed | SPLIT TSE COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
| 640 | Coil:Heating:Fuel | SPLIT TSE HEATING COIL | Design Size Nominal Capacity [W] | 9830.14475 |
| 641 | Controller:OutdoorAir | SPLIT TNE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.48752 |
| 642 | Controller:OutdoorAir | SPLIT TNE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.59546E-002 |
| 643 | AirLoopHVAC:UnitarySystem | SPLIT TNE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.48752 |
| 644 | AirLoopHVAC:UnitarySystem | SPLIT TNE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.48752 |
| 645 | AirLoopHVAC:UnitarySystem | SPLIT TNE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.48752 |
| 646 | AirLoopHVAC:UnitarySystem | SPLIT TNE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.48752 |
| 647 | AirLoopHVAC:UnitarySystem | SPLIT TNE_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 8070.11401 |
| 648 | AirLoopHVAC:UnitarySystem | SPLIT TNE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 9919.59422 |
| 649 | AirLoopHVAC:UnitarySystem | SPLIT TNE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 650 | AirLoopHVAC:UnitarySystem | SPLIT TNE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 651 | Fan:OnOff | SPLIT TNE SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.48752 |
| 652 | Coil:Cooling:DX:SingleSpeed | SPLIT TNE COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.48752 |
| 653 | Coil:Cooling:DX:SingleSpeed | SPLIT TNE COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 8070.11401 |
| 654 | Coil:Cooling:DX:SingleSpeed | SPLIT TNE COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
| 655 | Coil:Heating:Fuel | SPLIT TNE HEATING COIL | Design Size Nominal Capacity [W] | 9919.59422 |
| 656 | Controller:OutdoorAir | SPLIT TN1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.45214 |
| 657 | Controller:OutdoorAir | SPLIT TN1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.59546E-002 |
| 658 | AirLoopHVAC:UnitarySystem | SPLIT TN1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.45214 |
| 659 | AirLoopHVAC:UnitarySystem | SPLIT TN1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.45214 |
| 660 | AirLoopHVAC:UnitarySystem | SPLIT TN1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.45214 |
| 661 | AirLoopHVAC:UnitarySystem | SPLIT TN1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.45214 |
| 662 | AirLoopHVAC:UnitarySystem | SPLIT TN1_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 7484.51985 |
| 663 | AirLoopHVAC:UnitarySystem | SPLIT TN1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 9253.91764 |
| 664 | AirLoopHVAC:UnitarySystem | SPLIT TN1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 665 | AirLoopHVAC:UnitarySystem | SPLIT TN1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 666 | Fan:OnOff | SPLIT TN1 SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.45214 |
| 667 | Coil:Cooling:DX:SingleSpeed | SPLIT TN1 COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.45214 |
| 668 | Coil:Cooling:DX:SingleSpeed | SPLIT TN1 COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 7484.51985 |
| 669 | Coil:Cooling:DX:SingleSpeed | SPLIT TN1 COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
| 670 | Coil:Heating:Fuel | SPLIT TN1 HEATING COIL | Design Size Nominal Capacity [W] | 9253.91764 |
| 671 | Controller:OutdoorAir | SPLIT TN2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.44949 |
| 672 | Controller:OutdoorAir | SPLIT TN2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.59546E-002 |
| 673 | AirLoopHVAC:UnitarySystem | SPLIT TN2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.44949 |
| 674 | AirLoopHVAC:UnitarySystem | SPLIT TN2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.44949 |
| 675 | AirLoopHVAC:UnitarySystem | SPLIT TN2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.44949 |
| 676 | AirLoopHVAC:UnitarySystem | SPLIT TN2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.44949 |
| 677 | AirLoopHVAC:UnitarySystem | SPLIT TN2_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 7440.63903 |
| 678 | AirLoopHVAC:UnitarySystem | SPLIT TN2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 9204.05478 |
| 679 | AirLoopHVAC:UnitarySystem | SPLIT TN2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 680 | AirLoopHVAC:UnitarySystem | SPLIT TN2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 681 | Fan:OnOff | SPLIT TN2 SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.44949 |
| 682 | Coil:Cooling:DX:SingleSpeed | SPLIT TN2 COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.44949 |
| 683 | Coil:Cooling:DX:SingleSpeed | SPLIT TN2 COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 7440.63903 |
| 684 | Coil:Cooling:DX:SingleSpeed | SPLIT TN2 COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
| 685 | Coil:Heating:Fuel | SPLIT TN2 HEATING COIL | Design Size Nominal Capacity [W] | 9204.05478 |
| 686 | Controller:OutdoorAir | SPLIT TS1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.44823 |
| 687 | Controller:OutdoorAir | SPLIT TS1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.59546E-002 |
| 688 | AirLoopHVAC:UnitarySystem | SPLIT TS1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.44823 |
| 689 | AirLoopHVAC:UnitarySystem | SPLIT TS1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.44823 |
| 690 | AirLoopHVAC:UnitarySystem | SPLIT TS1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.44823 |
| 691 | AirLoopHVAC:UnitarySystem | SPLIT TS1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.44823 |
| 692 | AirLoopHVAC:UnitarySystem | SPLIT TS1_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 7419.86912 |
| 693 | AirLoopHVAC:UnitarySystem | SPLIT TS1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 9180.61021 |
| 694 | AirLoopHVAC:UnitarySystem | SPLIT TS1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 695 | AirLoopHVAC:UnitarySystem | SPLIT TS1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 696 | Fan:OnOff | SPLIT TS1 SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.44823 |
| 697 | Coil:Cooling:DX:SingleSpeed | SPLIT TS1 COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.44823 |
| 698 | Coil:Cooling:DX:SingleSpeed | SPLIT TS1 COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 7419.86912 |
| 699 | Coil:Cooling:DX:SingleSpeed | SPLIT TS1 COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
| 700 | Coil:Heating:Fuel | SPLIT TS1 HEATING COIL | Design Size Nominal Capacity [W] | 9180.61021 |
| 701 | Controller:OutdoorAir | SPLIT TS2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.44560 |
| 702 | Controller:OutdoorAir | SPLIT TS2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.59546E-002 |
| 703 | AirLoopHVAC:UnitarySystem | SPLIT TS2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.44560 |
| 704 | AirLoopHVAC:UnitarySystem | SPLIT TS2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.44560 |
| 705 | AirLoopHVAC:UnitarySystem | SPLIT TS2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.44560 |
| 706 | AirLoopHVAC:UnitarySystem | SPLIT TS2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.44560 |
| 707 | AirLoopHVAC:UnitarySystem | SPLIT TS2_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 7376.18046 |
| 708 | AirLoopHVAC:UnitarySystem | SPLIT TS2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 9130.96471 |
| 709 | AirLoopHVAC:UnitarySystem | SPLIT TS2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 710 | AirLoopHVAC:UnitarySystem | SPLIT TS2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 711 | Fan:OnOff | SPLIT TS2 SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.44560 |
| 712 | Coil:Cooling:DX:SingleSpeed | SPLIT TS2 COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.44560 |
| 713 | Coil:Cooling:DX:SingleSpeed | SPLIT TS2 COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 7376.18046 |
| 714 | Coil:Cooling:DX:SingleSpeed | SPLIT TS2 COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
| 715 | Coil:Heating:Fuel | SPLIT TS2 HEATING COIL | Design Size Nominal Capacity [W] | 9130.96471 |
| Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
| 1 | Coil:Cooling:DX:SingleSpeed | SPLIT GSW COOLING COIL | 6553.4 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 |
| 2 | Coil:Cooling:DX:SingleSpeed | SPLIT GNW COOLING COIL | 6431.5 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 |
| 3 | Coil:Cooling:DX:SingleSpeed | SPLIT OFFICE COOLING COIL | 7417.4 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 |
| 4 | Coil:Cooling:DX:SingleSpeed | SPLIT GNE COOLING COIL | 5872.0 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 |
| 5 | Coil:Cooling:DX:SingleSpeed | SPLIT GN1 COOLING COIL | 5235.3 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 |
| 6 | Coil:Cooling:DX:SingleSpeed | SPLIT GN2 COOLING COIL | 5224.4 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 |
| 7 | Coil:Cooling:DX:SingleSpeed | SPLIT GS1 COOLING COIL | 5395.8 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 |
| 8 | Coil:Cooling:DX:SingleSpeed | SPLIT GS2 COOLING COIL | 5434.2 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 |
| 9 | Coil:Cooling:DX:SingleSpeed | SPLIT MSW COOLING COIL | 15816.9 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 |
| 10 | Coil:Cooling:DX:SingleSpeed | SPLIT MNW COOLING COIL | 15674.1 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 |
| 11 | Coil:Cooling:DX:SingleSpeed | SPLIT MSE COOLING COIL | 14181.6 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 |
| 12 | Coil:Cooling:DX:SingleSpeed | SPLIT MNE COOLING COIL | 14045.7 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 |
| 13 | Coil:Cooling:DX:SingleSpeed | SPLIT MN1 COOLING COIL | 12484.3 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 |
| 14 | Coil:Cooling:DX:SingleSpeed | SPLIT MN2 COOLING COIL | 12452.3 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 |
| 15 | Coil:Cooling:DX:SingleSpeed | SPLIT MS1 COOLING COIL | 12684.6 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 |
| 16 | Coil:Cooling:DX:SingleSpeed | SPLIT MS2 COOLING COIL | 12651.5 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 |
| 17 | Coil:Cooling:DX:SingleSpeed | SPLIT TSW COOLING COIL | 8821.0 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 |
| 18 | Coil:Cooling:DX:SingleSpeed | SPLIT TNW COOLING COIL | 8899.5 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 |
| 19 | Coil:Cooling:DX:SingleSpeed | SPLIT TSE COOLING COIL | 7612.9 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 |
| 20 | Coil:Cooling:DX:SingleSpeed | SPLIT TNE COOLING COIL | 7688.1 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 |
| 21 | Coil:Cooling:DX:SingleSpeed | SPLIT TN1 COOLING COIL | 7130.2 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 |
| 22 | Coil:Cooling:DX:SingleSpeed | SPLIT TN2 COOLING COIL | 7088.4 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 |
| 23 | Coil:Cooling:DX:SingleSpeed | SPLIT TS1 COOLING COIL | 7068.6 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 |
| 24 | Coil:Cooling:DX:SingleSpeed | SPLIT TS2 COOLING COIL | 7027.0 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 |
| Zone Name | # Surfaces | |
| 1 | G SW APARTMENT | 9 |
| 2 | G NW APARTMENT | 9 |
| 3 | OFFICE | 9 |
| 4 | G NE APARTMENT | 9 |
| 5 | G N1 APARTMENT | 8 |
| 6 | G N2 APARTMENT | 8 |
| 7 | G S1 APARTMENT | 8 |
| 8 | G S2 APARTMENT | 8 |
| 9 | M SW APARTMENT | 9 |
| 10 | M NW APARTMENT | 9 |
| 11 | M SE APARTMENT | 9 |
| 12 | M NE APARTMENT | 9 |
| 13 | M N1 APARTMENT | 8 |
| 14 | M N2 APARTMENT | 8 |
| 15 | M S1 APARTMENT | 8 |
| 16 | M S2 APARTMENT | 8 |
| 17 | T SW APARTMENT | 9 |
| 18 | T NW APARTMENT | 9 |
| 19 | T SE APARTMENT | 9 |
| 20 | T NE APARTMENT | 9 |
| 21 | T N1 APARTMENT | 8 |
| 22 | T N2 APARTMENT | 8 |
| 23 | T S1 APARTMENT | 8 |
| 24 | T S2 APARTMENT | 8 |
| 25 | T CORRIDOR | 13 |
| 26 | G CORRIDOR | 13 |
| 27 | M CORRIDOR | 13 |
| Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
| 1 | G SWALL SWA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_GRD | 0.752 | 0.676 | 28.24 | 35.30 | 28.24 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 2 | GWINDOW1 S SWA | Window | G SWALL SWA | Window5 Detailed Fenestration | RESWINDOW_U_0.3972_SHGC_0.4 | N/A | 2.257 | No | 7.06 | 7.06 | 7.06 | 180.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 3 | G WWALL SWA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_GRD | 0.752 | 0.676 | 18.58 | 23.22 | 18.58 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 4 | GWINDOW1 W SWA | Window | G WWALL SWA | Window5 Detailed Fenestration | RESWINDOW_U_0.3972_SHGC_0.4 | N/A | 2.257 | No | 4.65 | 4.65 | 4.65 | 270.00 | 90.00 | 3.81 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 5 | G NIWALL SWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-G NIWALL SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 6 | G EIWALL SWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | iz-G EIWALL SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 7 | G GFLOOR SWA | Floor | CTF - ConductionTransferFunction | GGFLOORSWA_FFACTOR | 0.210 | 0.200 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 8 | G CEILIN SWA | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | G CEILIN SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 9 | G INTERNALMASS SWA | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 88.25 | 88.25 | 88.25 | 0.00 | 90.00 | 88.25 | 1.00 | 0.00 | G INTERNALMASS SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 10 | G NWALL NWA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_GRD | 0.752 | 0.676 | 28.24 | 35.30 | 28.24 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 11 | GWINDOW1 N NWA | Window | G NWALL NWA | Window5 Detailed Fenestration | RESWINDOW_U_0.3972_SHGC_0.4 | N/A | 2.257 | No | 7.06 | 7.06 | 7.06 | 0.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 12 | G WWALL NWA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_GRD | 0.752 | 0.676 | 18.58 | 23.22 | 18.58 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 13 | GWINDOW1 W NWA | Window | G WWALL NWA | Window5 Detailed Fenestration | RESWINDOW_U_0.3972_SHGC_0.4 | N/A | 2.257 | No | 4.65 | 4.65 | 4.65 | 270.00 | 90.00 | 3.81 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 14 | G SIWALL NWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-G SIWALL NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 15 | G EIWALL NWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | iz-G EIWALL NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 16 | G GFLOOR NWA | Floor | CTF - ConductionTransferFunction | GGFLOORNWA_FFACTOR | 0.210 | 0.200 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 17 | G CEILIN NWA | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | G CEILIN NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 18 | G INTERNALMASS NWA | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 88.25 | 88.25 | 88.25 | 0.00 | 90.00 | 88.25 | 1.00 | 0.00 | G INTERNALMASS NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 19 | G SWALL SEA | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.752 | 0.676 | 28.24 | 35.30 | 28.24 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 20 | GWINDOW1 S SEA | Window | G SWALL SEA | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3972_SHGC_0.4 | N/A | 2.257 | No | 7.06 | 7.06 | 7.06 | 180.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 21 | G EWALL SEA | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.752 | 0.676 | 18.58 | 23.22 | 18.58 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 22 | GWINDOW1 E SEA | Window | G EWALL SEA | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3972_SHGC_0.4 | N/A | 2.257 | No | 4.65 | 4.65 | 4.65 | 90.00 | 90.00 | 3.81 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 23 | G NIWALL SEA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-G NIWALL SEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 24 | iz-G EIWALL S2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | G EIWALL S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 25 | G GFLOOR SEA | Floor | CTF - ConductionTransferFunction | GGFLOORSEA_FFACTOR | 0.210 | 0.200 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 26 | G CEILIN SEA | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | G CEILIN SEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 27 | G INTERNALMASS SEA | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 88.25 | 88.25 | 88.25 | 0.00 | 90.00 | 88.25 | 1.00 | 0.00 | G INTERNALMASS SEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 28 | G NWALL NEA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_GRD | 0.752 | 0.676 | 28.24 | 35.30 | 28.24 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 29 | GWINDOW1 N NEA | Window | G NWALL NEA | Window5 Detailed Fenestration | RESWINDOW_U_0.3972_SHGC_0.4 | N/A | 2.257 | No | 7.06 | 7.06 | 7.06 | 0.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 30 | G EWALL NEA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_GRD | 0.752 | 0.676 | 18.58 | 23.22 | 18.58 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 31 | GWINDOW1 E NEA | Window | G EWALL NEA | Window5 Detailed Fenestration | RESWINDOW_U_0.3972_SHGC_0.4 | N/A | 2.257 | No | 4.65 | 4.65 | 4.65 | 90.00 | 90.00 | 3.81 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 32 | G SIWALL NEA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-G SIWALL NEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 33 | iz-G EIWALL N2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | G EIWALL N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 34 | G GFLOOR NEA | Floor | CTF - ConductionTransferFunction | GGFLOORNEA_FFACTOR | 0.210 | 0.200 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 35 | G CEILIN NEA | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | G CEILIN NEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 36 | G INTERNALMASS NEA | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 88.25 | 88.25 | 88.25 | 0.00 | 90.00 | 88.25 | 1.00 | 0.00 | G INTERNALMASS NEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 37 | G NWALL N1A | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_GRD | 0.752 | 0.676 | 28.24 | 35.30 | 28.24 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 38 | GWINDOW1 N N1A | Window | G NWALL N1A | Window5 Detailed Fenestration | RESWINDOW_U_0.3972_SHGC_0.4 | N/A | 2.257 | No | 7.06 | 7.06 | 7.06 | 0.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 39 | G SIWALL N1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-G SIWALL N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 40 | G EIWALL N1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | iz-G EIWALL N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 41 | iz-G EIWALL NWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | G EIWALL NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 42 | G GFLOOR N1A | Floor | CTF - ConductionTransferFunction | GGFLOORN1A_FFACTOR | 0.125 | 0.121 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 43 | G CEILIN N1A | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | G CEILIN N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 44 | G INTERNALMASS N1A | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 88.25 | 88.25 | 88.25 | 0.00 | 90.00 | 88.25 | 1.00 | 0.00 | G INTERNALMASS N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 45 | G NWALL N2A | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_GRD | 0.752 | 0.676 | 28.24 | 35.30 | 28.24 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 46 | GWINDOW1 N N2A | Window | G NWALL N2A | Window5 Detailed Fenestration | RESWINDOW_U_0.3972_SHGC_0.4 | N/A | 2.257 | No | 7.06 | 7.06 | 7.06 | 0.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 47 | G SIWALL N2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-G SIWALL N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 48 | G EIWALL N2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | iz-G EIWALL N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 49 | iz-G EIWALL N1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | G EIWALL N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 50 | G GFLOOR N2A | Floor | CTF - ConductionTransferFunction | GGFLOORN2A_FFACTOR | 0.125 | 0.121 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 51 | G CEILIN N2A | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | G CEILIN N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 52 | G INTERNALMASS N2A | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 88.25 | 88.25 | 88.25 | 0.00 | 90.00 | 88.25 | 1.00 | 0.00 | G INTERNALMASS N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 53 | G SWALL S1A | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_GRD | 0.752 | 0.676 | 28.24 | 35.30 | 28.24 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 54 | GWINDOW1 S S1A | Window | G SWALL S1A | Window5 Detailed Fenestration | RESWINDOW_U_0.3972_SHGC_0.4 | N/A | 2.257 | No | 7.06 | 7.06 | 7.06 | 180.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 55 | G NIWALL S1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-G NIWALL S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 56 | G EIWALL S1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | iz-G EIWALL S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 57 | iz-G EIWALL SWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | G EIWALL SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 58 | G GFLOOR S1A | Floor | CTF - ConductionTransferFunction | GGFLOORS1A_FFACTOR | 0.125 | 0.121 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 59 | G CEILIN S1A | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | G CEILIN S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 60 | G INTERNALMASS S1A | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 88.25 | 88.25 | 88.25 | 0.00 | 90.00 | 88.25 | 1.00 | 0.00 | G INTERNALMASS S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 61 | G SWALL S2A | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_GRD | 0.752 | 0.676 | 28.24 | 35.30 | 28.24 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 62 | GWINDOW1 S S2A | Window | G SWALL S2A | Window5 Detailed Fenestration | RESWINDOW_U_0.3972_SHGC_0.4 | N/A | 2.257 | No | 7.06 | 7.06 | 7.06 | 180.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 63 | G NIWALL S2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-G NIWALL S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 64 | G EIWALL S2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | iz-G EIWALL S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 65 | iz-G EIWALL S1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | G EIWALL S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 66 | G GFLOOR S2A | Floor | CTF - ConductionTransferFunction | GGFLOORS2A_FFACTOR | 0.125 | 0.121 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 67 | G CEILIN S2A | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | G CEILIN S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 68 | G INTERNALMASS S2A | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 88.25 | 88.25 | 88.25 | 0.00 | 90.00 | 88.25 | 1.00 | 0.00 | G INTERNALMASS S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 69 | M WWALL SWA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.761 | 0.683 | 18.58 | 23.22 | 18.58 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 70 | MWINDOW1 W SWA | Window | M WWALL SWA | Window5 Detailed Fenestration | RESWINDOW_U_0.3972_SHGC_0.4 | N/A | 2.257 | No | 4.65 | 4.65 | 4.65 | 270.00 | 90.00 | 3.81 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 71 | M SWALL SWA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.761 | 0.683 | 28.24 | 35.30 | 28.24 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 72 | MWINDOW1 S SWA | Window | M SWALL SWA | Window5 Detailed Fenestration | RESWINDOW_U_0.3972_SHGC_0.4 | N/A | 2.257 | No | 7.06 | 7.06 | 7.06 | 180.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 73 | M NIWALL SWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-M NIWALL SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 74 | M EIWALL SWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 90.00 | 90.00 | 3.05 | 7.62 | 0.00 | iz-M EIWALL SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 75 | M GFLOOR SWA | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | M GFLOOR SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 76 | M CEILIN SWA | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | M CEILIN SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 77 | M INTERNALMASS SWA | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 176.50 | 176.50 | 176.50 | 0.00 | 90.00 | 176.50 | 1.00 | 0.00 | M INTERNALMASS SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 78 | M NWALL NWA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.761 | 0.683 | 28.24 | 35.30 | 28.24 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 79 | MWINDOW1 N NWA | Window | M NWALL NWA | Window5 Detailed Fenestration | RESWINDOW_U_0.3972_SHGC_0.4 | N/A | 2.257 | No | 7.06 | 7.06 | 7.06 | 0.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 80 | M WWALL NWA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.761 | 0.683 | 18.58 | 23.22 | 18.58 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 81 | MWINDOW1 W NWA | Window | M WWALL NWA | Window5 Detailed Fenestration | RESWINDOW_U_0.3972_SHGC_0.4 | N/A | 2.257 | No | 4.65 | 4.65 | 4.65 | 270.00 | 90.00 | 3.81 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 82 | M SIWALL NWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-M SIWALL NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 83 | M EIWALL NWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | iz-M EIWALL NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 84 | M GFLOOR NWA | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | M GFLOOR NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 85 | M CEILIN NWA | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | M CEILIN NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 86 | M INTERNALMASS NWA | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 176.50 | 176.50 | 176.50 | 0.00 | 90.00 | 176.50 | 1.00 | 0.00 | M INTERNALMASS NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 87 | M EWALL SEA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.761 | 0.683 | 18.58 | 23.22 | 18.58 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 88 | MWINDOW1 E SEA | Window | M EWALL SEA | Window5 Detailed Fenestration | RESWINDOW_U_0.3972_SHGC_0.4 | N/A | 2.257 | No | 4.65 | 4.65 | 4.65 | 90.00 | 90.00 | 3.81 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 89 | M SWALL SEA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.761 | 0.683 | 28.24 | 35.30 | 28.24 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 90 | MWINDOW1 S SEA | Window | M SWALL SEA | Window5 Detailed Fenestration | RESWINDOW_U_0.3972_SHGC_0.4 | N/A | 2.257 | No | 7.06 | 7.06 | 7.06 | 180.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 91 | M NIWALL SEA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-M NIWALL SEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 92 | iz-M EIWALL S2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | M EIWALL S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 93 | M GFLOOR SEA | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | M GFLOOR SEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 94 | M CEILIN SEA | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | M CEILIN SEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 95 | M INTERNALMASS SEA | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 176.50 | 176.50 | 176.50 | 0.00 | 90.00 | 176.50 | 1.00 | 0.00 | M INTERNALMASS SEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 96 | M NWALL NEA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.761 | 0.683 | 28.24 | 35.30 | 28.24 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 97 | MWINDOW1 N NEA | Window | M NWALL NEA | Window5 Detailed Fenestration | RESWINDOW_U_0.3972_SHGC_0.4 | N/A | 2.257 | No | 7.06 | 7.06 | 7.06 | 0.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 98 | M EWALL NEA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.761 | 0.683 | 18.58 | 23.22 | 18.58 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 99 | MWINDOW1 E NEA | Window | M EWALL NEA | Window5 Detailed Fenestration | RESWINDOW_U_0.3972_SHGC_0.4 | N/A | 2.257 | No | 4.65 | 4.65 | 4.65 | 90.00 | 90.00 | 3.81 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 100 | M SIWALL NEA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-M SIWALL NEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 101 | iz-M EIWALL N2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | M EIWALL N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 102 | M GFLOOR NEA | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | M GFLOOR NEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 103 | M CEILIN NEA | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | M CEILIN NEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 104 | M INTERNALMASS NEA | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 176.50 | 176.50 | 176.50 | 0.00 | 90.00 | 176.50 | 1.00 | 0.00 | M INTERNALMASS NEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 105 | M NWALL N1A | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.761 | 0.683 | 28.24 | 35.30 | 28.24 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 106 | MWINDOW1 N N1A | Window | M NWALL N1A | Window5 Detailed Fenestration | RESWINDOW_U_0.3972_SHGC_0.4 | N/A | 2.257 | No | 7.06 | 7.06 | 7.06 | 0.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 107 | M SIWALL N1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-M SIWALL N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 108 | M EIWALL N1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | iz-M EIWALL N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 109 | iz-M EIWALL NWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | M EIWALL NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 110 | M GFLOOR N1A | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | M GFLOOR N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 111 | M CEILIN N1A | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | M CEILIN N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 112 | M INTERNALMASS N1A | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 176.50 | 176.50 | 176.50 | 0.00 | 90.00 | 176.50 | 1.00 | 0.00 | M INTERNALMASS N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 113 | M NWALL N2A | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.761 | 0.683 | 28.24 | 35.30 | 28.24 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 114 | MWINDOW1 N N2A | Window | M NWALL N2A | Window5 Detailed Fenestration | RESWINDOW_U_0.3972_SHGC_0.4 | N/A | 2.257 | No | 7.06 | 7.06 | 7.06 | 0.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 115 | M SIWALL N2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-M SIWALL N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 116 | M EIWALL N2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | iz-M EIWALL N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 117 | iz-M EIWALL N1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | M EIWALL N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 118 | M GFLOOR N2A | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | M GFLOOR N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 119 | M CEILIN N2A | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | M CEILIN N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 120 | M INTERNALMASS N2A | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 176.50 | 176.50 | 176.50 | 0.00 | 90.00 | 176.50 | 1.00 | 0.00 | M INTERNALMASS N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 121 | M SWALL S1A | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.761 | 0.683 | 28.24 | 35.30 | 28.24 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 122 | MWINDOW1 S S1A | Window | M SWALL S1A | Window5 Detailed Fenestration | RESWINDOW_U_0.3972_SHGC_0.4 | N/A | 2.257 | No | 7.06 | 7.06 | 7.06 | 180.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 123 | M NIWALL S1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-M NIWALL S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 124 | M EIWALL S1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | iz-M EIWALL S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 125 | iz-M EIWALL SWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 270.00 | 90.00 | 3.05 | 7.62 | 0.00 | M EIWALL SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 126 | M GFLOOR S1A | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | M GFLOOR S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 127 | M CEILIN S1A | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | M CEILIN S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 128 | M INTERNALMASS S1A | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 176.50 | 176.50 | 176.50 | 0.00 | 90.00 | 176.50 | 1.00 | 0.00 | M INTERNALMASS S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 129 | M SWALL S2A | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.761 | 0.683 | 28.24 | 35.30 | 28.24 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 130 | MWINDOW1 S S2A | Window | M SWALL S2A | Window5 Detailed Fenestration | RESWINDOW_U_0.3972_SHGC_0.4 | N/A | 2.257 | No | 7.06 | 7.06 | 7.06 | 180.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 131 | M NIWALL S2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-M NIWALL S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 132 | M EIWALL S2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | iz-M EIWALL S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 133 | iz-M EIWALL S1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | M EIWALL S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 134 | M GFLOOR S2A | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | M GFLOOR S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 135 | M CEILIN S2A | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | M CEILIN S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 136 | M INTERNALMASS S2A | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 176.50 | 176.50 | 176.50 | 0.00 | 90.00 | 176.50 | 1.00 | 0.00 | M INTERNALMASS S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 137 | T WWALL SWA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.098 | 0.943 | 18.58 | 23.22 | 18.58 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 138 | TWINDOW1 W SWA | Window | T WWALL SWA | Window5 Detailed Fenestration | RESWINDOW_U_0.3972_SHGC_0.4 | N/A | 2.257 | No | 4.65 | 4.65 | 4.65 | 270.00 | 90.00 | 3.81 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 139 | T SWALL SWA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.098 | 0.943 | 28.24 | 35.30 | 28.24 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 140 | TWINDOW1 S SWA | Window | T SWALL SWA | Window5 Detailed Fenestration | RESWINDOW_U_0.3972_SHGC_0.4 | N/A | 2.257 | No | 7.06 | 7.06 | 7.06 | 180.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 141 | T NIWALL SWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-T NIWALL SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 142 | T EIWALL SWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | iz-T EIWALL SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 143 | T GFLOOR SWA | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | T GFLOOR SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 144 | T ROOF SWA | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.228 | 0.219 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 145 | T INTERNALMASS SWA | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 88.25 | 88.25 | 88.25 | 0.00 | 90.00 | 88.25 | 1.00 | 0.00 | T INTERNALMASS SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 146 | T NWALL NWA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.098 | 0.943 | 28.24 | 35.30 | 28.24 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 147 | TWINDOW1 N NWA | Window | T NWALL NWA | Window5 Detailed Fenestration | RESWINDOW_U_0.3972_SHGC_0.4 | N/A | 2.257 | No | 7.06 | 7.06 | 7.06 | 0.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 148 | T WWALL NWA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.098 | 0.943 | 18.58 | 23.22 | 18.58 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 149 | TWINDOW1 W NWA | Window | T WWALL NWA | Window5 Detailed Fenestration | RESWINDOW_U_0.3972_SHGC_0.4 | N/A | 2.257 | No | 4.65 | 4.65 | 4.65 | 270.00 | 90.00 | 3.81 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 150 | T SIWALL NWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-T SIWALL NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 151 | T EIWALL NWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | iz-T EIWALL NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 152 | T GFLOOR NWA | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | T GFLOOR NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 153 | T ROOF NWA | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.228 | 0.219 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 154 | T INTERNALMASS NWA | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 88.25 | 88.25 | 88.25 | 0.00 | 90.00 | 88.25 | 1.00 | 0.00 | T INTERNALMASS NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 155 | T EWALL SEA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.098 | 0.943 | 18.58 | 23.22 | 18.58 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 156 | TWINDOW1 E SEA | Window | T EWALL SEA | Window5 Detailed Fenestration | RESWINDOW_U_0.3972_SHGC_0.4 | N/A | 2.257 | No | 4.65 | 4.65 | 4.65 | 90.00 | 90.00 | 3.81 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 157 | T SWALL SEA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.098 | 0.943 | 28.24 | 35.30 | 28.24 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 158 | TWINDOW1 S SEA | Window | T SWALL SEA | Window5 Detailed Fenestration | RESWINDOW_U_0.3972_SHGC_0.4 | N/A | 2.257 | No | 7.06 | 7.06 | 7.06 | 180.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 159 | T NIWALL SEA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-T NIWALL SEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 160 | iz-T EIWALL S2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | T EIWALL S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 161 | T GFLOOR SEA | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | T GFLOOR SEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 162 | T ROOF SEA | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.228 | 0.219 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 163 | T INTERNALMASS SEA | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 88.25 | 88.25 | 88.25 | 0.00 | 90.00 | 88.25 | 1.00 | 0.00 | T INTERNALMASS SEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 164 | T NWALL NEA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.098 | 0.943 | 28.24 | 35.30 | 28.24 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 165 | TWINDOW1 N NEA | Window | T NWALL NEA | Window5 Detailed Fenestration | RESWINDOW_U_0.3972_SHGC_0.4 | N/A | 2.257 | No | 7.06 | 7.06 | 7.06 | 0.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 166 | T EWALL NEA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.098 | 0.943 | 18.58 | 23.22 | 18.58 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 167 | TWINDOW1 E NEA | Window | T EWALL NEA | Window5 Detailed Fenestration | RESWINDOW_U_0.3972_SHGC_0.4 | N/A | 2.257 | No | 4.65 | 4.65 | 4.65 | 90.00 | 90.00 | 3.81 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 168 | T SIWALL NEA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-T SIWALL NEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 169 | iz-T EIWALL N2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | T EIWALL N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 170 | T GFLOOR NEA | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | T GFLOOR NEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 171 | T ROOF NEA | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.228 | 0.219 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 172 | T INTERNALMASS NEA | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 88.25 | 88.25 | 88.25 | 0.00 | 90.00 | 88.25 | 1.00 | 0.00 | T INTERNALMASS NEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 173 | T NWALL N1A | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.098 | 0.943 | 28.24 | 35.30 | 28.24 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 174 | TWINDOW1 N N1A | Window | T NWALL N1A | Window5 Detailed Fenestration | RESWINDOW_U_0.3972_SHGC_0.4 | N/A | 2.257 | No | 7.06 | 7.06 | 7.06 | 0.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 175 | T SIWALL N1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-T SIWALL N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 176 | T EIWALL N1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | iz-T EIWALL N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 177 | iz-T EIWALL NWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | T EIWALL NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 178 | T GFLOOR N1A | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | T GFLOOR N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 179 | T ROOF N1A | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.228 | 0.219 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 180 | T INTERNALMASS N1A | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 88.25 | 88.25 | 88.25 | 0.00 | 90.00 | 88.25 | 1.00 | 0.00 | T INTERNALMASS N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 181 | T NWALL N2A | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.098 | 0.943 | 28.24 | 35.30 | 28.24 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 182 | TWINDOW1 N N2A | Window | T NWALL N2A | Window5 Detailed Fenestration | RESWINDOW_U_0.3972_SHGC_0.4 | N/A | 2.257 | No | 7.06 | 7.06 | 7.06 | 0.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 183 | T SIWALL N2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-T SIWALL N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 184 | T EIWALL N2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | iz-T EIWALL N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 185 | iz-T EIWALL N1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | T EIWALL N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 186 | T GFLOOR N2A | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | T GFLOOR N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 187 | T ROOF N2A | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.228 | 0.219 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 188 | T INTERNALMASS N2A | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 88.25 | 88.25 | 88.25 | 0.00 | 90.00 | 88.25 | 1.00 | 0.00 | T INTERNALMASS N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 189 | T SWALL S1A | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.098 | 0.943 | 28.24 | 35.30 | 28.24 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 190 | TWINDOW1 S S1A | Window | T SWALL S1A | Window5 Detailed Fenestration | RESWINDOW_U_0.3972_SHGC_0.4 | N/A | 2.257 | No | 7.06 | 7.06 | 7.06 | 180.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 191 | T NIWALL S1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-T NIWALL S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 192 | T EIWALL S1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | iz-T EIWALL S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 193 | iz-T EIWALL SWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | T EIWALL SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 194 | T GFLOOR S1A | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | T GFLOOR S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 195 | T ROOF S1A | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.228 | 0.219 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 196 | T INTERNALMASS S1A | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 88.25 | 88.25 | 88.25 | 0.00 | 90.00 | 88.25 | 1.00 | 0.00 | T INTERNALMASS S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 197 | T SWALL S2A | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.098 | 0.943 | 28.24 | 35.30 | 28.24 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 198 | TWINDOW1 S S2A | Window | T SWALL S2A | Window5 Detailed Fenestration | RESWINDOW_U_0.3972_SHGC_0.4 | N/A | 2.257 | No | 7.06 | 7.06 | 7.06 | 180.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 199 | T NIWALL S2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-T NIWALL S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 200 | T EIWALL S2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | iz-T EIWALL S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 201 | iz-T EIWALL S1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | T EIWALL S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 202 | T GFLOOR S2A | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | T GFLOOR S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 203 | T ROOF S2A | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.228 | 0.219 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 204 | T INTERNALMASS S2A | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 88.25 | 88.25 | 88.25 | 0.00 | 90.00 | 88.25 | 1.00 | 0.00 | T INTERNALMASS S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 205 | T WWALL C | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.098 | 0.943 | 5.11 | 5.11 | 5.11 | 270.00 | 90.00 | 1.68 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 206 | T EWALL C | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.098 | 0.943 | 3.99 | 5.11 | 3.99 | 90.00 | 90.00 | 1.68 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 207 | TWINDOW14 | Window | T EWALL C | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3972_SHGC_0.4 | N/A | 2.257 | No | 1.11 | 1.11 | 1.11 | 90.00 | 90.00 | 0.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 208 | iz-T NIWALL SWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | T NIWALL SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 209 | iz-T NIWALL S1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | T NIWALL S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 210 | iz-T NIWALL S2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | T NIWALL S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 211 | iz-T NIWALL SEA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | T NIWALL SEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 212 | iz-T SIWALL NWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | T SIWALL NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 213 | iz-T SIWALL N1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | T SIWALL N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 214 | iz-T SIWALL N2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | T SIWALL N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 215 | iz-T SIWALL NEA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | T SIWALL NEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 216 | T FLOOR C | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 77.66 | 77.66 | 77.66 | 90.00 | 180.00 | 1.68 | 46.33 | 0.00 | T FLOOR C | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 217 | T ROOF C | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 77.66 | 77.66 | 77.66 | 180.00 | 0.00 | 46.33 | 1.68 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 218 | G WWALL C | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.752 | 0.676 | 5.11 | 5.11 | 5.11 | 270.00 | 90.00 | 1.68 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 219 | G EWALL C | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.752 | 0.676 | 1.79 | 5.11 | 1.79 | 90.00 | 90.00 | 1.68 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 220 | ENTRANCE DOOR | Window | G EWALL C | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3972_SHGC_0.4 | N/A | 2.257 | No | 3.32 | 3.32 | 3.32 | 90.00 | 90.00 | 1.57 | 2.11 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 221 | iz-G NIWALL SWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | G NIWALL SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 222 | iz-G NIWALL S1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | G NIWALL S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 223 | iz-G NIWALL S2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | G NIWALL S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 224 | iz-G NIWALL SEA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | G NIWALL SEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 225 | iz-G SIWALL NWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | G SIWALL NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 226 | iz-G SIWALL N1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | G SIWALL N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 227 | iz-G SIWALL N2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | G SIWALL N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 228 | iz-G SIWALL NEA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | G SIWALL NEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 229 | G FLOOR C | Floor | CTF - ConductionTransferFunction | GFLOORC_FFACTOR | 4.061E-002 | 4.021E-002 | 77.66 | 77.66 | 77.66 | 90.00 | 180.00 | 1.68 | 46.33 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 230 | G CEILING C | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 77.66 | 77.66 | 77.66 | 180.00 | 0.00 | 46.33 | 1.68 | 0.00 | G CEILING C | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 231 | M WWALL C | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.761 | 0.683 | 5.11 | 5.11 | 5.11 | 270.00 | 90.00 | 1.68 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 232 | M EWALL C | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.761 | 0.683 | 3.99 | 5.11 | 3.99 | 90.00 | 90.00 | 1.68 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 233 | MWINDOW14 | Window | M EWALL C | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3972_SHGC_0.4 | N/A | 2.257 | No | 1.11 | 1.11 | 1.11 | 90.00 | 90.00 | 0.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 234 | iz-M NIWALL SWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | M NIWALL SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 235 | iz-M NIWALL S1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | M NIWALL S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 236 | iz-M NIWALL S2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | M NIWALL S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 237 | iz-M NIWALL SEA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | M NIWALL SEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 238 | iz-M SIWALL NWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | M SIWALL NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 239 | iz-M SIWALL N1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | M SIWALL N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 240 | iz-M SIWALL N2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | M SIWALL N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 241 | iz-M SIWALL NEA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | M SIWALL NEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 242 | M FLOOR C | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 77.66 | 77.66 | 77.66 | 90.00 | 180.00 | 1.68 | 46.33 | 0.00 | M FLOOR C | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 243 | M CEILING C | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 77.66 | 77.66 | 77.66 | 180.00 | 0.00 | 46.33 | 1.68 | 0.00 | M CEILING C | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
| Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
| 1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | Yes | Yes | Yes | Clark and Allen |
| Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
| 1 | NEW YEAR'S DAY | Holiday | InputFile | 01/02 | 1Environment:Special Days |
| Daylight Saving Indicator | Source | Start Date | End Date | |
| 1 | Yes | InputFile | 03/12 | 11/05 |
| Style | Unit Conversion | |
| 1 | Commaandhtml | commaandhtml |
| Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
| 1 | G SW APARTMENT | RunPeriod: RUNPERIOD 1 | 3.7879831691E-002 | 3.8449158926E-002 | Pass | Pass | 3.0167880395E-002 | 6.7895078714E-002 | Pass | Pass |
| 2 | G NW APARTMENT | RunPeriod: RUNPERIOD 1 | 8.2973248475E-003 | 2.5799503014E-002 | Pass | Pass | 0.1841609123 | 0.4305964871 | Pass | Pass |
| 3 | OFFICE | RunPeriod: RUNPERIOD 1 | 5.6699268733E-002 | 4.5198141715E-002 | Pass | Pass | 0.1999016036 | 0.9871584553 | Pass | Pass |
| 4 | G NE APARTMENT | RunPeriod: RUNPERIOD 1 | 2.9292661206E-003 | 1.1353115716E-002 | Pass | Pass | 0.2856809947 | 0.8888261052 | Pass | Pass |
| 5 | G N1 APARTMENT | RunPeriod: RUNPERIOD 1 | 7.1210502547E-003 | 2.1184832309E-002 | Pass | Pass | 13.9254698437 | 164.1273335342 | Pass | Pass |
| 6 | G N2 APARTMENT | RunPeriod: RUNPERIOD 1 | 7.5947311458E-003 | 2.2054394638E-002 | Pass | Pass | 0.4319690954 | 2.9209274438 | Pass | Pass |
| 7 | G S1 APARTMENT | RunPeriod: RUNPERIOD 1 | 2.2865467386E-002 | 3.0484820840E-002 | Pass | Pass | 2.5085737482E-002 | 4.7992526621E-002 | Pass | Pass |
| 8 | G S2 APARTMENT | RunPeriod: RUNPERIOD 1 | 2.2773087893E-002 | 3.0588827571E-002 | Pass | Pass | 2.5162299116E-002 | 4.8288988496E-002 | Pass | Pass |
| 9 | M SW APARTMENT | RunPeriod: RUNPERIOD 1 | 3.3586617446E-002 | 4.1463805404E-002 | Pass | Pass | 2.9846936665E-002 | 4.0036987428E-002 | Pass | Pass |
| 10 | M NW APARTMENT | RunPeriod: RUNPERIOD 1 | 1.9449099364E-002 | 3.3641017168E-002 | Pass | Pass | 0.2024023660 | 0.5365979674 | Pass | Pass |
| 11 | M SE APARTMENT | RunPeriod: RUNPERIOD 1 | 3.4134561325E-002 | 4.9853110049E-002 | Pass | Pass | 2.7963426408E-002 | 4.3180064761E-002 | Pass | Pass |
| 12 | M NE APARTMENT | RunPeriod: RUNPERIOD 1 | 1.5697648758E-002 | 2.7999254736E-002 | Pass | Pass | 0.3716884603 | 2.4646016591 | Pass | Pass |
| 13 | M N1 APARTMENT | RunPeriod: RUNPERIOD 1 | 1.7652231648E-002 | 3.0606092549E-002 | Pass | Pass | 5.6649028510E-002 | 6.4359971949E-002 | Pass | Pass |
| 14 | M N2 APARTMENT | RunPeriod: RUNPERIOD 1 | 1.7696748114E-002 | 3.0452604195E-002 | Pass | Pass | 5.7857207867E-002 | 6.6789025800E-002 | Pass | Pass |
| 15 | M S1 APARTMENT | RunPeriod: RUNPERIOD 1 | 1.9610117533E-002 | 3.3408261081E-002 | Pass | Pass | 2.7227102061E-002 | 3.7654805953E-002 | Pass | Pass |
| 16 | M S2 APARTMENT | RunPeriod: RUNPERIOD 1 | 1.9645621883E-002 | 3.3482188585E-002 | Pass | Pass | 2.7247929231E-002 | 3.6511044643E-002 | Pass | Pass |
| 17 | T SW APARTMENT | RunPeriod: RUNPERIOD 1 | 4.0296560788E-002 | 7.7730937594E-002 | Pass | Pass | 0.1722156834 | 0.6954226136 | Pass | Pass |
| 18 | T NW APARTMENT | RunPeriod: RUNPERIOD 1 | 2.3320292738E-002 | 5.2389162728E-002 | Pass | Pass | 0.1444653681 | 0.3375213180 | Pass | Pass |
| 19 | T SE APARTMENT | RunPeriod: RUNPERIOD 1 | 4.0279765806E-002 | 7.4879746731E-002 | Pass | Pass | 0.1329480870 | 0.3364964422 | Pass | Pass |
| 20 | T NE APARTMENT | RunPeriod: RUNPERIOD 1 | 1.4747256058E-002 | 3.4540635477E-002 | Pass | Pass | 0.1503570584 | 0.4183132501 | Pass | Pass |
| 21 | T N1 APARTMENT | RunPeriod: RUNPERIOD 1 | 1.4430465306E-002 | 3.6237126902E-002 | Pass | Pass | 0.2603218613 | 1.5094290795 | Pass | Pass |
| 22 | T N2 APARTMENT | RunPeriod: RUNPERIOD 1 | 1.4449184545E-002 | 3.5825083636E-002 | Pass | Pass | 0.1904417347 | 0.7649268853 | Pass | Pass |
| 23 | T S1 APARTMENT | RunPeriod: RUNPERIOD 1 | 4.0278096200E-002 | 7.3681446134E-002 | Pass | Pass | 0.1774652112 | 0.7275862567 | Pass | Pass |
| 24 | T S2 APARTMENT | RunPeriod: RUNPERIOD 1 | 4.0278108818E-002 | 7.3650723249E-002 | Pass | Pass | 0.1878679546 | 0.8490303533 | Pass | Pass |
| 25 | T CORRIDOR | RunPeriod: RUNPERIOD 1 | 4.5394444510E-002 | 2.5897996897E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
| 26 | G CORRIDOR | RunPeriod: RUNPERIOD 1 | 0.2084239253 | 0.6604380670 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
| 27 | M CORRIDOR | RunPeriod: RUNPERIOD 1 | 1.2878154155E-002 | 7.4576076688E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 09:14:27
Heat Emission by Components| Envelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
| Heat Emissions [GJ] | 2360.00 | 103.22 | 0.00 | 13.51 | 747.59 | 3224.33 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 09:14:27
SizingPeriod:DesignDay| Maximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
| ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | -7.90 | 0.00 | -7.90 | Wetbulb [C] | 3.20 | 0.00 |
| ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 35.10 | 13.50 | 15.70 | Wetbulb [C] | 4.40 | 220.00 |
| Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
| Jan | 0.00 | 0 | |||
| Feb | 0.00 | 0 | |||
| Mar | 0.00 | 0 | |||
| Apr | 0.00 | 0 | |||
| May | 9.00 | 6 | |||
| Jun | 0.00 | 0 | |||
| Jul | 0.00 | 0 | |||
| Aug | 0.00 | 0 | |||
| Sep | 0.00 | 0 | |||
| Oct | 5.00 | 4 | |||
| Nov | 9.00 | 7 | |||
| Dec | 0.00 | 0 |
| Value | |
| None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 09:14:27
Opaque Exterior| Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
| G SWALL SWA | RES_EXT_WALL_GRD | 0.30 | 0.676 | 0.752 | 35.30 | 28.24 | 180.00 | 90.00 | S |
| G WWALL SWA | RES_EXT_WALL_GRD | 0.30 | 0.676 | 0.752 | 23.22 | 18.58 | 270.00 | 90.00 | W |
| G GFLOOR SWA | GGFLOORSWA_FFACTOR | 1.00 | 0.203 | 0.210 | 88.25 | 88.25 | 90.00 | 180.00 | |
| G NWALL NWA | RES_EXT_WALL_GRD | 0.30 | 0.676 | 0.752 | 35.30 | 28.24 | 0.00 | 90.00 | N |
| G WWALL NWA | RES_EXT_WALL_GRD | 0.30 | 0.676 | 0.752 | 23.22 | 18.58 | 270.00 | 90.00 | W |
| G GFLOOR NWA | GGFLOORNWA_FFACTOR | 1.00 | 0.203 | 0.210 | 88.25 | 88.25 | 90.00 | 180.00 | |
| G SWALL SEA | NONRES_EXT_WALL_GRD | 0.30 | 0.676 | 0.752 | 35.30 | 28.24 | 180.00 | 90.00 | S |
| G EWALL SEA | NONRES_EXT_WALL_GRD | 0.30 | 0.676 | 0.752 | 23.22 | 18.58 | 90.00 | 90.00 | E |
| G GFLOOR SEA | GGFLOORSEA_FFACTOR | 1.00 | 0.203 | 0.210 | 88.25 | 88.25 | 90.00 | 180.00 | |
| G NWALL NEA | RES_EXT_WALL_GRD | 0.30 | 0.676 | 0.752 | 35.30 | 28.24 | 0.00 | 90.00 | N |
| G EWALL NEA | RES_EXT_WALL_GRD | 0.30 | 0.676 | 0.752 | 23.22 | 18.58 | 90.00 | 90.00 | E |
| G GFLOOR NEA | GGFLOORNEA_FFACTOR | 1.00 | 0.203 | 0.210 | 88.25 | 88.25 | 90.00 | 180.00 | |
| G NWALL N1A | RES_EXT_WALL_GRD | 0.30 | 0.676 | 0.752 | 35.30 | 28.24 | 0.00 | 90.00 | N |
| G GFLOOR N1A | GGFLOORN1A_FFACTOR | 1.00 | 0.123 | 0.125 | 88.25 | 88.25 | 90.00 | 180.00 | |
| G NWALL N2A | RES_EXT_WALL_GRD | 0.30 | 0.676 | 0.752 | 35.30 | 28.24 | 0.00 | 90.00 | N |
| G GFLOOR N2A | GGFLOORN2A_FFACTOR | 1.00 | 0.123 | 0.125 | 88.25 | 88.25 | 90.00 | 180.00 | |
| G SWALL S1A | RES_EXT_WALL_GRD | 0.30 | 0.676 | 0.752 | 35.30 | 28.24 | 180.00 | 90.00 | S |
| G GFLOOR S1A | GGFLOORS1A_FFACTOR | 1.00 | 0.123 | 0.125 | 88.25 | 88.25 | 90.00 | 180.00 | |
| G SWALL S2A | RES_EXT_WALL_GRD | 0.30 | 0.676 | 0.752 | 35.30 | 28.24 | 180.00 | 90.00 | S |
| G GFLOOR S2A | GGFLOORS2A_FFACTOR | 1.00 | 0.123 | 0.125 | 88.25 | 88.25 | 90.00 | 180.00 | |
| M WWALL SWA | RES_EXT_WALL_MID | 0.30 | 0.683 | 0.761 | 46.45 | 37.16 | 270.00 | 90.00 | W |
| M SWALL SWA | RES_EXT_WALL_MID | 0.30 | 0.683 | 0.761 | 70.60 | 56.48 | 180.00 | 90.00 | S |
| M NWALL NWA | RES_EXT_WALL_MID | 0.30 | 0.683 | 0.761 | 70.60 | 56.48 | 0.00 | 90.00 | N |
| M WWALL NWA | RES_EXT_WALL_MID | 0.30 | 0.683 | 0.761 | 46.45 | 37.16 | 270.00 | 90.00 | W |
| M EWALL SEA | RES_EXT_WALL_MID | 0.30 | 0.683 | 0.761 | 46.45 | 37.16 | 90.00 | 90.00 | E |
| M SWALL SEA | RES_EXT_WALL_MID | 0.30 | 0.683 | 0.761 | 70.60 | 56.48 | 180.00 | 90.00 | S |
| M NWALL NEA | RES_EXT_WALL_MID | 0.30 | 0.683 | 0.761 | 70.60 | 56.48 | 0.00 | 90.00 | N |
| M EWALL NEA | RES_EXT_WALL_MID | 0.30 | 0.683 | 0.761 | 46.45 | 37.16 | 90.00 | 90.00 | E |
| M NWALL N1A | RES_EXT_WALL_MID | 0.30 | 0.683 | 0.761 | 70.60 | 56.48 | 0.00 | 90.00 | N |
| M NWALL N2A | RES_EXT_WALL_MID | 0.30 | 0.683 | 0.761 | 70.60 | 56.48 | 0.00 | 90.00 | N |
| M SWALL S1A | RES_EXT_WALL_MID | 0.30 | 0.683 | 0.761 | 70.60 | 56.48 | 180.00 | 90.00 | S |
| M SWALL S2A | RES_EXT_WALL_MID | 0.30 | 0.683 | 0.761 | 70.60 | 56.48 | 180.00 | 90.00 | S |
| T WWALL SWA | RES_EXT_WALL_TOP | 0.30 | 0.943 | 1.098 | 23.22 | 18.58 | 270.00 | 90.00 | W |
| T SWALL SWA | RES_EXT_WALL_TOP | 0.30 | 0.943 | 1.098 | 35.30 | 28.24 | 180.00 | 90.00 | S |
| T ROOF SWA | RES_ROOF | 0.30 | 0.221 | 0.228 | 88.25 | 88.25 | 180.00 | 0.00 | |
| T NWALL NWA | RES_EXT_WALL_TOP | 0.30 | 0.943 | 1.098 | 35.30 | 28.24 | 0.00 | 90.00 | N |
| T WWALL NWA | RES_EXT_WALL_TOP | 0.30 | 0.943 | 1.098 | 23.22 | 18.58 | 270.00 | 90.00 | W |
| T ROOF NWA | RES_ROOF | 0.30 | 0.221 | 0.228 | 88.25 | 88.25 | 180.00 | 0.00 | |
| T EWALL SEA | RES_EXT_WALL_TOP | 0.30 | 0.943 | 1.098 | 23.22 | 18.58 | 90.00 | 90.00 | E |
| T SWALL SEA | RES_EXT_WALL_TOP | 0.30 | 0.943 | 1.098 | 35.30 | 28.24 | 180.00 | 90.00 | S |
| T ROOF SEA | RES_ROOF | 0.30 | 0.221 | 0.228 | 88.25 | 88.25 | 180.00 | 0.00 | |
| T NWALL NEA | RES_EXT_WALL_TOP | 0.30 | 0.943 | 1.098 | 35.30 | 28.24 | 0.00 | 90.00 | N |
| T EWALL NEA | RES_EXT_WALL_TOP | 0.30 | 0.943 | 1.098 | 23.22 | 18.58 | 90.00 | 90.00 | E |
| T ROOF NEA | RES_ROOF | 0.30 | 0.221 | 0.228 | 88.25 | 88.25 | 180.00 | 0.00 | |
| T NWALL N1A | RES_EXT_WALL_TOP | 0.30 | 0.943 | 1.098 | 35.30 | 28.24 | 0.00 | 90.00 | N |
| T ROOF N1A | RES_ROOF | 0.30 | 0.221 | 0.228 | 88.25 | 88.25 | 180.00 | 0.00 | |
| T NWALL N2A | RES_EXT_WALL_TOP | 0.30 | 0.943 | 1.098 | 35.30 | 28.24 | 0.00 | 90.00 | N |
| T ROOF N2A | RES_ROOF | 0.30 | 0.221 | 0.228 | 88.25 | 88.25 | 180.00 | 0.00 | |
| T SWALL S1A | RES_EXT_WALL_TOP | 0.30 | 0.943 | 1.098 | 35.30 | 28.24 | 180.00 | 90.00 | S |
| T ROOF S1A | RES_ROOF | 0.30 | 0.221 | 0.228 | 88.25 | 88.25 | 180.00 | 0.00 | |
| T SWALL S2A | RES_EXT_WALL_TOP | 0.30 | 0.943 | 1.098 | 35.30 | 28.24 | 180.00 | 90.00 | S |
| T ROOF S2A | RES_ROOF | 0.30 | 0.221 | 0.228 | 88.25 | 88.25 | 180.00 | 0.00 | |
| T WWALL C | NONRES_EXT_WALL_TOP | 0.30 | 0.943 | 1.098 | 5.11 | 5.11 | 270.00 | 90.00 | W |
| T EWALL C | NONRES_EXT_WALL_TOP | 0.30 | 0.943 | 1.098 | 5.11 | 3.99 | 90.00 | 90.00 | E |
| T ROOF C | NONRES_ROOF | 0.30 | 0.221 | 0.228 | 77.66 | 77.66 | 180.00 | 0.00 | |
| G WWALL C | NONRES_EXT_WALL_GRD | 0.30 | 0.676 | 0.752 | 5.11 | 5.11 | 270.00 | 90.00 | W |
| G EWALL C | NONRES_EXT_WALL_GRD | 0.30 | 0.676 | 0.752 | 5.11 | 1.79 | 90.00 | 90.00 | E |
| G FLOOR C | GFLOORC_FFACTOR | 1.00 | 0.040 | 0.041 | 77.66 | 77.66 | 90.00 | 180.00 | |
| M WWALL C | NONRES_EXT_WALL_MID | 0.30 | 0.683 | 0.761 | 10.22 | 10.22 | 270.00 | 90.00 | W |
| M EWALL C | NONRES_EXT_WALL_MID | 0.30 | 0.683 | 0.761 | 10.22 | 7.99 | 90.00 | 90.00 | E |
| Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
| G NIWALL SWA | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 0.00 | 90.00 | N |
| G EIWALL SWA | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 90.00 | 90.00 | E |
| G CEILIN SWA | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 88.25 | 88.25 | 180.00 | 0.00 | |
| G SIWALL NWA | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 180.00 | 90.00 | S |
| G EIWALL NWA | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 90.00 | 90.00 | E |
| G CEILIN NWA | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 88.25 | 88.25 | 180.00 | 0.00 | |
| G NIWALL SEA | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 0.00 | 90.00 | N |
| iz-G EIWALL S2A | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 270.00 | 90.00 | W |
| G CEILIN SEA | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 88.25 | 88.25 | 180.00 | 0.00 | |
| G SIWALL NEA | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 180.00 | 90.00 | S |
| iz-G EIWALL N2A | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 270.00 | 90.00 | W |
| G CEILIN NEA | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 88.25 | 88.25 | 180.00 | 0.00 | |
| G SIWALL N1A | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 180.00 | 90.00 | S |
| G EIWALL N1A | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 90.00 | 90.00 | E |
| iz-G EIWALL NWA | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 270.00 | 90.00 | W |
| G CEILIN N1A | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 88.25 | 88.25 | 180.00 | 0.00 | |
| G SIWALL N2A | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 180.00 | 90.00 | S |
| G EIWALL N2A | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 90.00 | 90.00 | E |
| iz-G EIWALL N1A | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 270.00 | 90.00 | W |
| G CEILIN N2A | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 88.25 | 88.25 | 180.00 | 0.00 | |
| G NIWALL S1A | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 0.00 | 90.00 | N |
| G EIWALL S1A | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 90.00 | 90.00 | E |
| iz-G EIWALL SWA | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 270.00 | 90.00 | W |
| G CEILIN S1A | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 88.25 | 88.25 | 180.00 | 0.00 | |
| G NIWALL S2A | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 0.00 | 90.00 | N |
| G EIWALL S2A | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 90.00 | 90.00 | E |
| iz-G EIWALL S1A | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 270.00 | 90.00 | W |
| G CEILIN S2A | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 88.25 | 88.25 | 180.00 | 0.00 | |
| M NIWALL SWA | INT_WALL | 0.30 | 2.511 | 6.299 | 70.60 | 70.60 | 0.00 | 90.00 | N |
| M EIWALL SWA | INT_WALL | 0.30 | 2.511 | 6.299 | 46.45 | 46.45 | 90.00 | 90.00 | E |
| M GFLOOR SWA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 176.50 | 176.50 | 90.00 | 180.00 | |
| M CEILIN SWA | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 176.50 | 176.50 | 180.00 | 0.00 | |
| M SIWALL NWA | INT_WALL | 0.30 | 2.511 | 6.299 | 70.60 | 70.60 | 180.00 | 90.00 | S |
| M EIWALL NWA | INT_WALL | 0.30 | 2.511 | 6.299 | 46.45 | 46.45 | 90.00 | 90.00 | E |
| M GFLOOR NWA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 176.50 | 176.50 | 90.00 | 180.00 | |
| M CEILIN NWA | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 176.50 | 176.50 | 180.00 | 0.00 | |
| M NIWALL SEA | INT_WALL | 0.30 | 2.511 | 6.299 | 70.60 | 70.60 | 0.00 | 90.00 | N |
| iz-M EIWALL S2A | INT_WALL | 0.30 | 2.511 | 6.299 | 46.45 | 46.45 | 270.00 | 90.00 | W |
| M GFLOOR SEA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 176.50 | 176.50 | 90.00 | 180.00 | |
| M CEILIN SEA | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 176.50 | 176.50 | 180.00 | 0.00 | |
| M SIWALL NEA | INT_WALL | 0.30 | 2.511 | 6.299 | 70.60 | 70.60 | 180.00 | 90.00 | S |
| iz-M EIWALL N2A | INT_WALL | 0.30 | 2.511 | 6.299 | 46.45 | 46.45 | 270.00 | 90.00 | W |
| M GFLOOR NEA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 176.50 | 176.50 | 90.00 | 180.00 | |
| M CEILIN NEA | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 176.50 | 176.50 | 180.00 | 0.00 | |
| M SIWALL N1A | INT_WALL | 0.30 | 2.511 | 6.299 | 70.60 | 70.60 | 180.00 | 90.00 | S |
| M EIWALL N1A | INT_WALL | 0.30 | 2.511 | 6.299 | 46.45 | 46.45 | 90.00 | 90.00 | E |
| iz-M EIWALL NWA | INT_WALL | 0.30 | 2.511 | 6.299 | 46.45 | 46.45 | 270.00 | 90.00 | W |
| M GFLOOR N1A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 176.50 | 176.50 | 90.00 | 180.00 | |
| M CEILIN N1A | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 176.50 | 176.50 | 180.00 | 0.00 | |
| M SIWALL N2A | INT_WALL | 0.30 | 2.511 | 6.299 | 70.60 | 70.60 | 180.00 | 90.00 | S |
| M EIWALL N2A | INT_WALL | 0.30 | 2.511 | 6.299 | 46.45 | 46.45 | 90.00 | 90.00 | E |
| iz-M EIWALL N1A | INT_WALL | 0.30 | 2.511 | 6.299 | 46.45 | 46.45 | 270.00 | 90.00 | W |
| M GFLOOR N2A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 176.50 | 176.50 | 90.00 | 180.00 | |
| M CEILIN N2A | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 176.50 | 176.50 | 180.00 | 0.00 | |
| M NIWALL S1A | INT_WALL | 0.30 | 2.511 | 6.299 | 70.60 | 70.60 | 0.00 | 90.00 | N |
| M EIWALL S1A | INT_WALL | 0.30 | 2.511 | 6.299 | 46.45 | 46.45 | 90.00 | 90.00 | E |
| iz-M EIWALL SWA | INT_WALL | 0.30 | 2.511 | 6.299 | 46.45 | 46.45 | 270.00 | 90.00 | W |
| M GFLOOR S1A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 176.50 | 176.50 | 90.00 | 180.00 | |
| M CEILIN S1A | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 176.50 | 176.50 | 180.00 | 0.00 | |
| M NIWALL S2A | INT_WALL | 0.30 | 2.511 | 6.299 | 70.60 | 70.60 | 0.00 | 90.00 | N |
| M EIWALL S2A | INT_WALL | 0.30 | 2.511 | 6.299 | 46.45 | 46.45 | 90.00 | 90.00 | E |
| iz-M EIWALL S1A | INT_WALL | 0.30 | 2.511 | 6.299 | 46.45 | 46.45 | 270.00 | 90.00 | W |
| M GFLOOR S2A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 176.50 | 176.50 | 90.00 | 180.00 | |
| M CEILIN S2A | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 176.50 | 176.50 | 180.00 | 0.00 | |
| T NIWALL SWA | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 0.00 | 90.00 | N |
| T EIWALL SWA | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 90.00 | 90.00 | E |
| T GFLOOR SWA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 88.25 | 88.25 | 90.00 | 180.00 | |
| T SIWALL NWA | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 180.00 | 90.00 | S |
| T EIWALL NWA | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 90.00 | 90.00 | E |
| T GFLOOR NWA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 88.25 | 88.25 | 90.00 | 180.00 | |
| T NIWALL SEA | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 0.00 | 90.00 | N |
| iz-T EIWALL S2A | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 270.00 | 90.00 | W |
| T GFLOOR SEA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 88.25 | 88.25 | 90.00 | 180.00 | |
| T SIWALL NEA | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 180.00 | 90.00 | S |
| iz-T EIWALL N2A | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 270.00 | 90.00 | W |
| T GFLOOR NEA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 88.25 | 88.25 | 90.00 | 180.00 | |
| T SIWALL N1A | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 180.00 | 90.00 | S |
| T EIWALL N1A | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 90.00 | 90.00 | E |
| iz-T EIWALL NWA | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 270.00 | 90.00 | W |
| T GFLOOR N1A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 88.25 | 88.25 | 90.00 | 180.00 | |
| T SIWALL N2A | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 180.00 | 90.00 | S |
| T EIWALL N2A | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 90.00 | 90.00 | E |
| iz-T EIWALL N1A | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 270.00 | 90.00 | W |
| T GFLOOR N2A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 88.25 | 88.25 | 90.00 | 180.00 | |
| T NIWALL S1A | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 0.00 | 90.00 | N |
| T EIWALL S1A | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 90.00 | 90.00 | E |
| iz-T EIWALL SWA | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 270.00 | 90.00 | W |
| T GFLOOR S1A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 88.25 | 88.25 | 90.00 | 180.00 | |
| T NIWALL S2A | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 0.00 | 90.00 | N |
| T EIWALL S2A | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 90.00 | 90.00 | E |
| iz-T EIWALL S1A | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 270.00 | 90.00 | W |
| T GFLOOR S2A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 88.25 | 88.25 | 90.00 | 180.00 | |
| iz-T NIWALL SWA | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 180.00 | 90.00 | S |
| iz-T NIWALL S1A | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 180.00 | 90.00 | S |
| iz-T NIWALL S2A | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 180.00 | 90.00 | S |
| iz-T NIWALL SEA | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 180.00 | 90.00 | S |
| iz-T SIWALL NWA | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 0.00 | 90.00 | N |
| iz-T SIWALL N1A | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 0.00 | 90.00 | N |
| iz-T SIWALL N2A | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 0.00 | 90.00 | N |
| iz-T SIWALL NEA | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 0.00 | 90.00 | N |
| T FLOOR C | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 77.66 | 77.66 | 90.00 | 180.00 | |
| iz-G NIWALL SWA | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 180.00 | 90.00 | S |
| iz-G NIWALL S1A | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 180.00 | 90.00 | S |
| iz-G NIWALL S2A | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 180.00 | 90.00 | S |
| iz-G NIWALL SEA | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 180.00 | 90.00 | S |
| iz-G SIWALL NWA | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 0.00 | 90.00 | N |
| iz-G SIWALL N1A | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 0.00 | 90.00 | N |
| iz-G SIWALL N2A | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 0.00 | 90.00 | N |
| iz-G SIWALL NEA | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 0.00 | 90.00 | N |
| G CEILING C | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 77.66 | 77.66 | 180.00 | 0.00 | |
| iz-M NIWALL SWA | INT_WALL | 0.30 | 2.511 | 6.299 | 70.60 | 70.60 | 180.00 | 90.00 | S |
| iz-M NIWALL S1A | INT_WALL | 0.30 | 2.511 | 6.299 | 70.60 | 70.60 | 180.00 | 90.00 | S |
| iz-M NIWALL S2A | INT_WALL | 0.30 | 2.511 | 6.299 | 70.60 | 70.60 | 180.00 | 90.00 | S |
| iz-M NIWALL SEA | INT_WALL | 0.30 | 2.511 | 6.299 | 70.60 | 70.60 | 180.00 | 90.00 | S |
| iz-M SIWALL NWA | INT_WALL | 0.30 | 2.511 | 6.299 | 70.60 | 70.60 | 0.00 | 90.00 | N |
| iz-M SIWALL N1A | INT_WALL | 0.30 | 2.511 | 6.299 | 70.60 | 70.60 | 0.00 | 90.00 | N |
| iz-M SIWALL N2A | INT_WALL | 0.30 | 2.511 | 6.299 | 70.60 | 70.60 | 0.00 | 90.00 | N |
| iz-M SIWALL NEA | INT_WALL | 0.30 | 2.511 | 6.299 | 70.60 | 70.60 | 0.00 | 90.00 | N |
| M FLOOR C | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 155.32 | 155.32 | 90.00 | 180.00 | |
| M CEILING C | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 155.32 | 155.32 | 180.00 | 0.00 | |
| G INTERNALMASS SWA | INTERIORFURNISHINGS | 0.30 | 0.800 | 88.25 | 0.00 | 90.00 | N | ||
| G INTERNALMASS NWA | INTERIORFURNISHINGS | 0.30 | 0.800 | 88.25 | 0.00 | 90.00 | N | ||
| G INTERNALMASS SEA | INTERIORFURNISHINGS | 0.30 | 0.800 | 88.25 | 0.00 | 90.00 | N | ||
| G INTERNALMASS NEA | INTERIORFURNISHINGS | 0.30 | 0.800 | 88.25 | 0.00 | 90.00 | N | ||
| G INTERNALMASS N1A | INTERIORFURNISHINGS | 0.30 | 0.800 | 88.25 | 0.00 | 90.00 | N | ||
| G INTERNALMASS N2A | INTERIORFURNISHINGS | 0.30 | 0.800 | 88.25 | 0.00 | 90.00 | N | ||
| G INTERNALMASS S1A | INTERIORFURNISHINGS | 0.30 | 0.800 | 88.25 | 0.00 | 90.00 | N | ||
| G INTERNALMASS S2A | INTERIORFURNISHINGS | 0.30 | 0.800 | 88.25 | 0.00 | 90.00 | N | ||
| M INTERNALMASS SWA | INTERIORFURNISHINGS | 0.30 | 0.800 | 353.00 | 0.00 | 90.00 | N | ||
| M INTERNALMASS NWA | INTERIORFURNISHINGS | 0.30 | 0.800 | 353.00 | 0.00 | 90.00 | N | ||
| M INTERNALMASS SEA | INTERIORFURNISHINGS | 0.30 | 0.800 | 353.00 | 0.00 | 90.00 | N | ||
| M INTERNALMASS NEA | INTERIORFURNISHINGS | 0.30 | 0.800 | 353.00 | 0.00 | 90.00 | N | ||
| M INTERNALMASS N1A | INTERIORFURNISHINGS | 0.30 | 0.800 | 353.00 | 0.00 | 90.00 | N | ||
| M INTERNALMASS N2A | INTERIORFURNISHINGS | 0.30 | 0.800 | 353.00 | 0.00 | 90.00 | N | ||
| M INTERNALMASS S1A | INTERIORFURNISHINGS | 0.30 | 0.800 | 353.00 | 0.00 | 90.00 | N | ||
| M INTERNALMASS S2A | INTERIORFURNISHINGS | 0.30 | 0.800 | 353.00 | 0.00 | 90.00 | N | ||
| T INTERNALMASS SWA | INTERIORFURNISHINGS | 0.30 | 0.800 | 88.25 | 0.00 | 90.00 | N | ||
| T INTERNALMASS NWA | INTERIORFURNISHINGS | 0.30 | 0.800 | 88.25 | 0.00 | 90.00 | N | ||
| T INTERNALMASS SEA | INTERIORFURNISHINGS | 0.30 | 0.800 | 88.25 | 0.00 | 90.00 | N | ||
| T INTERNALMASS NEA | INTERIORFURNISHINGS | 0.30 | 0.800 | 88.25 | 0.00 | 90.00 | N | ||
| T INTERNALMASS N1A | INTERIORFURNISHINGS | 0.30 | 0.800 | 88.25 | 0.00 | 90.00 | N | ||
| T INTERNALMASS N2A | INTERIORFURNISHINGS | 0.30 | 0.800 | 88.25 | 0.00 | 90.00 | N | ||
| T INTERNALMASS S1A | INTERIORFURNISHINGS | 0.30 | 0.800 | 88.25 | 0.00 | 90.00 | N | ||
| T INTERNALMASS S2A | INTERIORFURNISHINGS | 0.30 | 0.800 | 88.25 | 0.00 | 90.00 | N |
| Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
| GWINDOW1 S SWA | RESWINDOW_U_0.3972_SHGC_0.4 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.257 | 0.401 | 0.402 | No | G SWALL SWA | 180.00 | 90.00 | S | |||||||
| GWINDOW1 W SWA | RESWINDOW_U_0.3972_SHGC_0.4 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 2.257 | 0.401 | 0.402 | No | G WWALL SWA | 270.00 | 90.00 | W | |||||||
| GWINDOW1 N NWA | RESWINDOW_U_0.3972_SHGC_0.4 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.257 | 0.401 | 0.402 | No | G NWALL NWA | 0.00 | 90.00 | N | |||||||
| GWINDOW1 W NWA | RESWINDOW_U_0.3972_SHGC_0.4 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 2.257 | 0.401 | 0.402 | No | G WWALL NWA | 270.00 | 90.00 | W | |||||||
| GWINDOW1 S SEA | NONRESWINDOW_U_0.3972_SHGC_0.4 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.257 | 0.401 | 0.402 | No | G SWALL SEA | 180.00 | 90.00 | S | |||||||
| GWINDOW1 E SEA | NONRESWINDOW_U_0.3972_SHGC_0.4 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 2.257 | 0.401 | 0.402 | No | G EWALL SEA | 90.00 | 90.00 | E | |||||||
| GWINDOW1 N NEA | RESWINDOW_U_0.3972_SHGC_0.4 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.257 | 0.401 | 0.402 | No | G NWALL NEA | 0.00 | 90.00 | N | |||||||
| GWINDOW1 E NEA | RESWINDOW_U_0.3972_SHGC_0.4 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 2.257 | 0.401 | 0.402 | No | G EWALL NEA | 90.00 | 90.00 | E | |||||||
| GWINDOW1 N N1A | RESWINDOW_U_0.3972_SHGC_0.4 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.257 | 0.401 | 0.402 | No | G NWALL N1A | 0.00 | 90.00 | N | |||||||
| GWINDOW1 N N2A | RESWINDOW_U_0.3972_SHGC_0.4 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.257 | 0.401 | 0.402 | No | G NWALL N2A | 0.00 | 90.00 | N | |||||||
| GWINDOW1 S S1A | RESWINDOW_U_0.3972_SHGC_0.4 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.257 | 0.401 | 0.402 | No | G SWALL S1A | 180.00 | 90.00 | S | |||||||
| GWINDOW1 S S2A | RESWINDOW_U_0.3972_SHGC_0.4 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.257 | 0.401 | 0.402 | No | G SWALL S2A | 180.00 | 90.00 | S | |||||||
| MWINDOW1 W SWA | RESWINDOW_U_0.3972_SHGC_0.4 | 4.65 | 0.00 | 0.00 | 4.65 | 9.29 | 2.257 | 0.401 | 0.402 | No | M WWALL SWA | 270.00 | 90.00 | W | |||||||
| MWINDOW1 S SWA | RESWINDOW_U_0.3972_SHGC_0.4 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 2.257 | 0.401 | 0.402 | No | M SWALL SWA | 180.00 | 90.00 | S | |||||||
| MWINDOW1 N NWA | RESWINDOW_U_0.3972_SHGC_0.4 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 2.257 | 0.401 | 0.402 | No | M NWALL NWA | 0.00 | 90.00 | N | |||||||
| MWINDOW1 W NWA | RESWINDOW_U_0.3972_SHGC_0.4 | 4.65 | 0.00 | 0.00 | 4.65 | 9.29 | 2.257 | 0.401 | 0.402 | No | M WWALL NWA | 270.00 | 90.00 | W | |||||||
| MWINDOW1 E SEA | RESWINDOW_U_0.3972_SHGC_0.4 | 4.65 | 0.00 | 0.00 | 4.65 | 9.29 | 2.257 | 0.401 | 0.402 | No | M EWALL SEA | 90.00 | 90.00 | E | |||||||
| MWINDOW1 S SEA | RESWINDOW_U_0.3972_SHGC_0.4 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 2.257 | 0.401 | 0.402 | No | M SWALL SEA | 180.00 | 90.00 | S | |||||||
| MWINDOW1 N NEA | RESWINDOW_U_0.3972_SHGC_0.4 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 2.257 | 0.401 | 0.402 | No | M NWALL NEA | 0.00 | 90.00 | N | |||||||
| MWINDOW1 E NEA | RESWINDOW_U_0.3972_SHGC_0.4 | 4.65 | 0.00 | 0.00 | 4.65 | 9.29 | 2.257 | 0.401 | 0.402 | No | M EWALL NEA | 90.00 | 90.00 | E | |||||||
| MWINDOW1 N N1A | RESWINDOW_U_0.3972_SHGC_0.4 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 2.257 | 0.401 | 0.402 | No | M NWALL N1A | 0.00 | 90.00 | N | |||||||
| MWINDOW1 N N2A | RESWINDOW_U_0.3972_SHGC_0.4 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 2.257 | 0.401 | 0.402 | No | M NWALL N2A | 0.00 | 90.00 | N | |||||||
| MWINDOW1 S S1A | RESWINDOW_U_0.3972_SHGC_0.4 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 2.257 | 0.401 | 0.402 | No | M SWALL S1A | 180.00 | 90.00 | S | |||||||
| MWINDOW1 S S2A | RESWINDOW_U_0.3972_SHGC_0.4 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 2.257 | 0.401 | 0.402 | No | M SWALL S2A | 180.00 | 90.00 | S | |||||||
| TWINDOW1 W SWA | RESWINDOW_U_0.3972_SHGC_0.4 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 2.257 | 0.401 | 0.402 | No | T WWALL SWA | 270.00 | 90.00 | W | |||||||
| TWINDOW1 S SWA | RESWINDOW_U_0.3972_SHGC_0.4 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.257 | 0.401 | 0.402 | No | T SWALL SWA | 180.00 | 90.00 | S | |||||||
| TWINDOW1 N NWA | RESWINDOW_U_0.3972_SHGC_0.4 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.257 | 0.401 | 0.402 | No | T NWALL NWA | 0.00 | 90.00 | N | |||||||
| TWINDOW1 W NWA | RESWINDOW_U_0.3972_SHGC_0.4 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 2.257 | 0.401 | 0.402 | No | T WWALL NWA | 270.00 | 90.00 | W | |||||||
| TWINDOW1 E SEA | RESWINDOW_U_0.3972_SHGC_0.4 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 2.257 | 0.401 | 0.402 | No | T EWALL SEA | 90.00 | 90.00 | E | |||||||
| TWINDOW1 S SEA | RESWINDOW_U_0.3972_SHGC_0.4 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.257 | 0.401 | 0.402 | No | T SWALL SEA | 180.00 | 90.00 | S | |||||||
| TWINDOW1 N NEA | RESWINDOW_U_0.3972_SHGC_0.4 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.257 | 0.401 | 0.402 | No | T NWALL NEA | 0.00 | 90.00 | N | |||||||
| TWINDOW1 E NEA | RESWINDOW_U_0.3972_SHGC_0.4 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 2.257 | 0.401 | 0.402 | No | T EWALL NEA | 90.00 | 90.00 | E | |||||||
| TWINDOW1 N N1A | RESWINDOW_U_0.3972_SHGC_0.4 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.257 | 0.401 | 0.402 | No | T NWALL N1A | 0.00 | 90.00 | N | |||||||
| TWINDOW1 N N2A | RESWINDOW_U_0.3972_SHGC_0.4 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.257 | 0.401 | 0.402 | No | T NWALL N2A | 0.00 | 90.00 | N | |||||||
| TWINDOW1 S S1A | RESWINDOW_U_0.3972_SHGC_0.4 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.257 | 0.401 | 0.402 | No | T SWALL S1A | 180.00 | 90.00 | S | |||||||
| TWINDOW1 S S2A | RESWINDOW_U_0.3972_SHGC_0.4 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.257 | 0.401 | 0.402 | No | T SWALL S2A | 180.00 | 90.00 | S | |||||||
| TWINDOW14 | NONRESWINDOW_U_0.3972_SHGC_0.4 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.257 | 0.401 | 0.402 | No | T EWALL C | 90.00 | 90.00 | E | |||||||
| ENTRANCE DOOR | NONRESWINDOW_U_0.3972_SHGC_0.4 | 3.32 | 0.00 | 0.00 | 3.32 | 3.32 | 2.257 | 0.401 | 0.402 | No | G EWALL C | 90.00 | 90.00 | E | |||||||
| MWINDOW14 | NONRESWINDOW_U_0.3972_SHGC_0.4 | 1.11 | 0.00 | 0.00 | 1.11 | 2.23 | 2.257 | 0.401 | 0.402 | No | M EWALL C | 90.00 | 90.00 | E | |||||||
| Total or Average | 306.92 | 2.257 | 0.401 | 0.402 | |||||||||||||||||
| North Total or Average | 112.97 | 2.257 | 0.401 | 0.402 | |||||||||||||||||
| Non-North Total or Average | 193.95 | 2.257 | 0.401 | 0.402 |
| Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
| None |
| Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
| Total or Average | 0.00 | - | - | - |
| Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
| None |
| Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
| None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 09:14:27
Sunlit Fraction| March 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
| GWINDOW1 S SWA | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| GWINDOW1 W SWA | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
| GWINDOW1 N NWA | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| GWINDOW1 W NWA | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
| GWINDOW1 S SEA | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| GWINDOW1 E SEA | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
| GWINDOW1 N NEA | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| GWINDOW1 E NEA | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
| GWINDOW1 N N1A | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| GWINDOW1 N N2A | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| GWINDOW1 S S1A | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| GWINDOW1 S S2A | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| MWINDOW1 W SWA | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
| MWINDOW1 S SWA | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| MWINDOW1 N NWA | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| MWINDOW1 W NWA | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
| MWINDOW1 E SEA | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
| MWINDOW1 S SEA | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| MWINDOW1 N NEA | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| MWINDOW1 E NEA | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
| MWINDOW1 N N1A | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| MWINDOW1 N N2A | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| MWINDOW1 S S1A | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| MWINDOW1 S S2A | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| TWINDOW1 W SWA | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
| TWINDOW1 S SWA | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| TWINDOW1 N NWA | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| TWINDOW1 W NWA | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
| TWINDOW1 E SEA | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
| TWINDOW1 S SEA | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| TWINDOW1 N NEA | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| TWINDOW1 E NEA | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
| TWINDOW1 N N1A | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| TWINDOW1 N N2A | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| TWINDOW1 S S1A | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| TWINDOW1 S S2A | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| TWINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
| ENTRANCE DOOR | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
| MWINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
| Name | Type | Shaded Construction | Control | Glare Control | |
| None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 09:14:27
Interior Lighting| Zone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
| LIGHTING_HARDWIRED_GSW | G SW APARTMENT | G SW APARTMENT | GENERAL | 7.8684 | 88.25 | 694.38 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.32 |
| LIGHTING_HARDWIRED_GNW | G NW APARTMENT | G NW APARTMENT | GENERAL | 7.8684 | 88.25 | 694.38 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.32 |
| LIGHTING_HARDWIRED_OFFICE | OFFICE | OFFICE | GENERAL | 9.7532 | 88.25 | 860.71 | LightsWired | LTG_SCH_OFFICE | 46.69 | 168.00 | 45.77 | 0.0000 | Y | 7.40 |
| LIGHTING_HARDWIRED_GNE | G NE APARTMENT | G NE APARTMENT | GENERAL | 7.8684 | 88.25 | 694.38 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.32 |
| LIGHTING_HARDWIRED_GN1 | G N1 APARTMENT | G N1 APARTMENT | GENERAL | 7.8684 | 88.25 | 694.38 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.32 |
| LIGHTING_HARDWIRED_GN2 | G N2 APARTMENT | G N2 APARTMENT | GENERAL | 7.8684 | 88.25 | 694.38 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.32 |
| LIGHTING_HARDWIRED_GS1 | G S1 APARTMENT | G S1 APARTMENT | GENERAL | 7.8684 | 88.25 | 694.38 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.32 |
| LIGHTING_HARDWIRED_GS2 | G S2 APARTMENT | G S2 APARTMENT | GENERAL | 7.8684 | 88.25 | 694.38 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.32 |
| LIGHTING_HARDWIRED_MSW | M SW APARTMENT | M SW APARTMENT | GENERAL | 7.8684 | 176.50 | 1388.76 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 2.63 |
| LIGHTING_HARDWIRED_MNW | M NW APARTMENT | M NW APARTMENT | GENERAL | 7.8684 | 176.50 | 1388.76 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 2.63 |
| LIGHTING_HARDWIRED_MSE | M SE APARTMENT | M SE APARTMENT | GENERAL | 7.8684 | 176.50 | 1388.76 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 2.63 |
| LIGHTING_HARDWIRED_MNE | M NE APARTMENT | M NE APARTMENT | GENERAL | 7.8684 | 176.50 | 1388.76 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 2.63 |
| LIGHTING_HARDWIRED_MN1 | M N1 APARTMENT | M N1 APARTMENT | GENERAL | 7.8684 | 176.50 | 1388.76 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 2.63 |
| LIGHTING_HARDWIRED_MN2 | M N2 APARTMENT | M N2 APARTMENT | GENERAL | 7.8684 | 176.50 | 1388.76 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 2.63 |
| LIGHTING_HARDWIRED_MS1 | M S1 APARTMENT | M S1 APARTMENT | GENERAL | 7.8684 | 176.50 | 1388.76 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 2.63 |
| LIGHTING_HARDWIRED_MS2 | M S2 APARTMENT | M S2 APARTMENT | GENERAL | 7.8684 | 176.50 | 1388.76 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 2.63 |
| LIGHTING_HARDWIRED_TSW | T SW APARTMENT | T SW APARTMENT | GENERAL | 7.8684 | 88.25 | 694.38 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.32 |
| LIGHTING_HARDWIRED_TNW | T NW APARTMENT | T NW APARTMENT | GENERAL | 7.8684 | 88.25 | 694.38 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.32 |
| LIGHTING_HARDWIRED_TSE | T SE APARTMENT | T SE APARTMENT | GENERAL | 7.8684 | 88.25 | 694.38 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.32 |
| LIGHTING_HARDWIRED_TNE | T NE APARTMENT | T NE APARTMENT | GENERAL | 7.8684 | 88.25 | 694.38 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.32 |
| LIGHTING_HARDWIRED_TN1 | T N1 APARTMENT | T N1 APARTMENT | GENERAL | 7.8684 | 88.25 | 694.38 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.32 |
| LIGHTING_HARDWIRED_TN2 | T N2 APARTMENT | T N2 APARTMENT | GENERAL | 7.8684 | 88.25 | 694.38 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.32 |
| LIGHTING_HARDWIRED_TS1 | T S1 APARTMENT | T S1 APARTMENT | GENERAL | 7.8684 | 88.25 | 694.38 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.32 |
| LIGHTING_HARDWIRED_TS2 | T S2 APARTMENT | T S2 APARTMENT | GENERAL | 7.8684 | 88.25 | 694.38 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.32 |
| LIGHTING_HARDWIRED_GC | G CORRIDOR | G CORRIDOR | GENERAL | 4.7725 | 77.66 | 370.63 | LightsWired | LTG_SCH_CORRIDOR | 168.00 | 168.00 | 168.00 | 0.0000 | N | 11.69 |
| LIGHTING_HARDWIRED_MC | M CORRIDOR | M CORRIDOR | GENERAL | 4.7725 | 155.32 | 741.26 | LightsWired | LTG_SCH_CORRIDOR | 168.00 | 168.00 | 168.00 | 0.0000 | N | 23.38 |
| LIGHTING_HARDWIRED_TC | T CORRIDOR | T CORRIDOR | GENERAL | 4.7725 | 77.66 | 370.63 | LightsWired | LTG_SCH_CORRIDOR | 168.00 | 168.00 | 168.00 | 0.0000 | N | 11.69 |
| LIGHTING_PLUGIN_GSW | G SW APARTMENT | G SW APARTMENT | GENERAL | 0.8234 | 88.25 | 72.67 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.14 |
| LIGHTING_PLUGIN_GNW | G NW APARTMENT | G NW APARTMENT | GENERAL | 0.8234 | 88.25 | 72.67 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.14 |
| LIGHTING_PLUGIN_GNE | G NE APARTMENT | G NE APARTMENT | GENERAL | 0.8234 | 88.25 | 72.67 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.14 |
| LIGHTING_PLUGIN_GN1 | G N1 APARTMENT | G N1 APARTMENT | GENERAL | 0.8234 | 88.25 | 72.67 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.14 |
| LIGHTING_PLUGIN_GN2 | G N2 APARTMENT | G N2 APARTMENT | GENERAL | 0.8234 | 88.25 | 72.67 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.14 |
| LIGHTING_PLUGIN_GS1 | G S1 APARTMENT | G S1 APARTMENT | GENERAL | 0.8234 | 88.25 | 72.67 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.14 |
| LIGHTING_PLUGIN_GS2 | G S2 APARTMENT | G S2 APARTMENT | GENERAL | 0.8234 | 88.25 | 72.67 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.14 |
| LIGHTING_PLUGIN_MSW | M SW APARTMENT | M SW APARTMENT | GENERAL | 0.8234 | 176.50 | 145.34 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.28 |
| LIGHTING_PLUGIN_MNW | M NW APARTMENT | M NW APARTMENT | GENERAL | 0.8234 | 176.50 | 145.34 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.28 |
| LIGHTING_PLUGIN_MSE | M SE APARTMENT | M SE APARTMENT | GENERAL | 0.8234 | 176.50 | 145.34 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.28 |
| LIGHTING_PLUGIN_MNE | M NE APARTMENT | M NE APARTMENT | GENERAL | 0.8234 | 176.50 | 145.34 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.28 |
| LIGHTING_PLUGIN_MN1 | M N1 APARTMENT | M N1 APARTMENT | GENERAL | 0.8234 | 176.50 | 145.34 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.28 |
| LIGHTING_PLUGIN_MN2 | M N2 APARTMENT | M N2 APARTMENT | GENERAL | 0.8234 | 176.50 | 145.34 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.28 |
| LIGHTING_PLUGIN_MS1 | M S1 APARTMENT | M S1 APARTMENT | GENERAL | 0.8234 | 176.50 | 145.34 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.28 |
| LIGHTING_PLUGIN_MS2 | M S2 APARTMENT | M S2 APARTMENT | GENERAL | 0.8234 | 176.50 | 145.34 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.28 |
| LIGHTING_PLUGIN_TSW | T SW APARTMENT | T SW APARTMENT | GENERAL | 0.8234 | 88.25 | 72.67 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.14 |
| LIGHTING_PLUGIN_TNW | T NW APARTMENT | T NW APARTMENT | GENERAL | 0.8234 | 88.25 | 72.67 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.14 |
| LIGHTING_PLUGIN_TSE | T SE APARTMENT | T SE APARTMENT | GENERAL | 0.8234 | 88.25 | 72.67 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.14 |
| LIGHTING_PLUGIN_TNE | T NE APARTMENT | T NE APARTMENT | GENERAL | 0.8234 | 88.25 | 72.67 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.14 |
| LIGHTING_PLUGIN_TN1 | T N1 APARTMENT | T N1 APARTMENT | GENERAL | 0.8234 | 88.25 | 72.67 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.14 |
| LIGHTING_PLUGIN_TN2 | T N2 APARTMENT | T N2 APARTMENT | GENERAL | 0.8234 | 88.25 | 72.67 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.14 |
| LIGHTING_PLUGIN_TS1 | T S1 APARTMENT | T S1 APARTMENT | GENERAL | 0.8234 | 88.25 | 72.67 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.14 |
| LIGHTING_PLUGIN_TS2 | T S2 APARTMENT | T S2 APARTMENT | GENERAL | 0.8234 | 88.25 | 72.67 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.14 |
| Interior Lighting Total | 4.4498 | 5870.34 | 26121.74 | 75.91 |
| Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
| None |
| Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
| FACADE LIGHTING | 3183.33 | AstronomicalClock | - | 83.71 | 83.71 | 50.02 | |
| Exterior Lighting Total | 3183.33 | 50.02 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 09:14:27
Central Plant| Type | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
| None |
| Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
| SPLIT GSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 6879.08 | 5507.77 | 1371.31 | 0.80 | 3.91 | |||
| SPLIT GNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 6751.08 | 5405.29 | 1345.79 | 0.80 | 3.91 | |||
| SPLIT OFFICE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7785.99 | 6233.90 | 1552.10 | 0.80 | 3.91 | |||
| SPLIT GNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 6163.82 | 4935.09 | 1228.73 | 0.80 | 3.91 | |||
| SPLIT GN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5495.52 | 4400.02 | 1095.50 | 0.80 | 3.91 | |||
| SPLIT GN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5483.98 | 4390.78 | 1093.20 | 0.80 | 3.91 | |||
| SPLIT GS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5663.92 | 4534.84 | 1129.07 | 0.80 | 3.91 | |||
| SPLIT GS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5704.22 | 4567.11 | 1137.11 | 0.80 | 3.91 | |||
| SPLIT MSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 16602.94 | 13293.23 | 3309.71 | 0.80 | 3.91 | |||
| SPLIT MNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 16452.98 | 13173.16 | 3279.81 | 0.80 | 3.91 | |||
| SPLIT MSE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 14886.41 | 11918.88 | 2967.53 | 0.80 | 3.91 | |||
| SPLIT MNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 14743.71 | 11804.63 | 2939.08 | 0.80 | 3.91 | |||
| SPLIT MN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 13104.73 | 10492.37 | 2612.36 | 0.80 | 3.91 | |||
| SPLIT MN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 13071.14 | 10465.48 | 2605.66 | 0.80 | 3.91 | |||
| SPLIT MS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 13314.99 | 10660.71 | 2654.27 | 0.80 | 3.91 | |||
| SPLIT MS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 13280.23 | 10632.89 | 2647.34 | 0.80 | 3.91 | |||
| SPLIT TSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 9259.35 | 7413.55 | 1845.80 | 0.80 | 3.91 | |||
| SPLIT TNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 9341.72 | 7479.50 | 1862.22 | 0.80 | 3.91 | |||
| SPLIT TSE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7991.26 | 6398.24 | 1593.01 | 0.80 | 3.91 | |||
| SPLIT TNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 8070.11 | 6461.38 | 1608.73 | 0.80 | 3.91 | |||
| SPLIT TN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7484.52 | 5992.52 | 1492.00 | 0.80 | 3.91 | |||
| SPLIT TN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7440.64 | 5957.39 | 1483.25 | 0.80 | 3.91 | |||
| SPLIT TS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7419.87 | 5940.76 | 1479.11 | 0.80 | 3.91 | |||
| SPLIT TS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7376.18 | 5905.78 | 1470.40 | 0.80 | 3.91 |
| DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
| SPLIT GSW COOLING COIL | 6553.4 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 | |
| SPLIT GNW COOLING COIL | 6431.5 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 | |
| SPLIT OFFICE COOLING COIL | 7417.4 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 | |
| SPLIT GNE COOLING COIL | 5872.0 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 | |
| SPLIT GN1 COOLING COIL | 5235.3 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 | |
| SPLIT GN2 COOLING COIL | 5224.4 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 | |
| SPLIT GS1 COOLING COIL | 5395.8 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 | |
| SPLIT GS2 COOLING COIL | 5434.2 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 | |
| SPLIT MSW COOLING COIL | 15816.9 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 | |
| SPLIT MNW COOLING COIL | 15674.1 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 | |
| SPLIT MSE COOLING COIL | 14181.6 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 | |
| SPLIT MNE COOLING COIL | 14045.7 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 | |
| SPLIT MN1 COOLING COIL | 12484.3 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 | |
| SPLIT MN2 COOLING COIL | 12452.3 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 | |
| SPLIT MS1 COOLING COIL | 12684.6 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 | |
| SPLIT MS2 COOLING COIL | 12651.5 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 | |
| SPLIT TSW COOLING COIL | 8821.0 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 | |
| SPLIT TNW COOLING COIL | 8899.5 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 | |
| SPLIT TSE COOLING COIL | 7612.9 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 | |
| SPLIT TNE COOLING COIL | 7688.1 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 | |
| SPLIT TN1 COOLING COIL | 7130.2 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 | |
| SPLIT TN2 COOLING COIL | 7088.4 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 | |
| SPLIT TS1 COOLING COIL | 7068.6 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 | |
| SPLIT TS2 COOLING COIL | 7027.0 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 |
| DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
| SPLIT GSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT GNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT OFFICE COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT GNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT GN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT GN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT GS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT GS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT MSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT MNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT MSE COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT MNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT MN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT MN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT MS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT MS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT TSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT TNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT TSE COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT TNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT TN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT TN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT TS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT TS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed |
| DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
| None |
| Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
| SPLIT GSW HEATING COIL | Coil:Heating:Fuel | 8565.90 | 0.80 | |
| SPLIT GNW HEATING COIL | Coil:Heating:Fuel | 8420.39 | 0.80 | |
| SPLIT OFFICE HEATING COIL | Coil:Heating:Fuel | 9947.14 | 0.80 | |
| SPLIT GNE HEATING COIL | Coil:Heating:Fuel | 7753.08 | 0.80 | |
| SPLIT GN1 HEATING COIL | Coil:Heating:Fuel | 6993.63 | 0.80 | |
| SPLIT GN2 HEATING COIL | Coil:Heating:Fuel | 6980.51 | 0.80 | |
| SPLIT GS1 HEATING COIL | Coil:Heating:Fuel | 7185.04 | 0.80 | |
| SPLIT GS2 HEATING COIL | Coil:Heating:Fuel | 7230.83 | 0.80 | |
| SPLIT MSW HEATING COIL | Coil:Heating:Fuel | 20364.98 | 0.80 | |
| SPLIT MNW HEATING COIL | Coil:Heating:Fuel | 20194.24 | 0.80 | |
| SPLIT MSE HEATING COIL | Coil:Heating:Fuel | 18414.38 | 0.80 | |
| SPLIT MNE HEATING COIL | Coil:Heating:Fuel | 18251.93 | 0.80 | |
| SPLIT MN1 HEATING COIL | Coil:Heating:Fuel | 16389.21 | 0.80 | |
| SPLIT MN2 HEATING COIL | Coil:Heating:Fuel | 16351.05 | 0.80 | |
| SPLIT MS1 HEATING COIL | Coil:Heating:Fuel | 16628.41 | 0.80 | |
| SPLIT MS2 HEATING COIL | Coil:Heating:Fuel | 16588.91 | 0.80 | |
| SPLIT TSW HEATING COIL | Coil:Heating:Fuel | 11271.18 | 0.80 | |
| SPLIT TNW HEATING COIL | Coil:Heating:Fuel | 11364.59 | 0.80 | |
| SPLIT TSE HEATING COIL | Coil:Heating:Fuel | 9830.14 | 0.80 | |
| SPLIT TNE HEATING COIL | Coil:Heating:Fuel | 9919.59 | 0.80 | |
| SPLIT TN1 HEATING COIL | Coil:Heating:Fuel | 9253.92 | 0.80 | |
| SPLIT TN2 HEATING COIL | Coil:Heating:Fuel | 9204.05 | 0.80 | |
| SPLIT TS1 HEATING COIL | Coil:Heating:Fuel | 9180.61 | 0.80 | |
| SPLIT TS2 HEATING COIL | Coil:Heating:Fuel | 9130.96 | 0.80 |
| Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
| G SW APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| G SW APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| G NW APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| G NW APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| G NE APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| G NE APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| G N1 APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| G N1 APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| G N2 APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| G N2 APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| G S1 APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| G S1 APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| G S2 APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| G S2 APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| M SW APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.05 | 40.01 | 770.84 | 1.00 | 4.13 | General | ||
| M SW APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.05 | 40.01 | 770.84 | 1.00 | 4.13 | General | ||
| M NW APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.05 | 40.01 | 770.84 | 1.00 | 4.13 | General | ||
| M NW APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.05 | 40.01 | 770.84 | 1.00 | 4.13 | General | ||
| M SE APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.05 | 40.01 | 770.84 | 1.00 | 4.13 | General | ||
| M SE APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.05 | 40.01 | 770.84 | 1.00 | 4.13 | General | ||
| M NE APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.05 | 40.01 | 770.84 | 1.00 | 4.13 | General | ||
| M NE APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.05 | 40.01 | 770.84 | 1.00 | 4.13 | General | ||
| M N1 APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.05 | 40.01 | 770.84 | 1.00 | 4.13 | General | ||
| M N1 APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.05 | 40.01 | 770.84 | 1.00 | 4.13 | General | ||
| M N2 APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.05 | 40.01 | 770.84 | 1.00 | 4.13 | General | ||
| M N2 APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.05 | 40.01 | 770.84 | 1.00 | 4.13 | General | ||
| M S1 APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.05 | 40.01 | 770.84 | 1.00 | 4.13 | General | ||
| M S1 APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.05 | 40.01 | 770.84 | 1.00 | 4.13 | General | ||
| M S2 APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.05 | 40.01 | 770.84 | 1.00 | 4.13 | General | ||
| M S2 APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.05 | 40.01 | 770.84 | 1.00 | 4.13 | General | ||
| T SW APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| T SW APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| T NW APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| T NW APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| T SE APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| T SE APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| T NE APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| T NE APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| T N1 APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| T N1 APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| T N2 APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| T N2 APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| T S1 APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| T S1 APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| T S2 APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| T S2 APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| SPLIT GSW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.42 | 465.48 | 1120.11 | 1.00 | 1.70 | General | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 |
| SPLIT GNW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.41 | 456.82 | 1120.11 | 1.00 | 1.71 | General | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 |
| SPLIT OFFICE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.47 | 526.84 | 1120.11 | 1.00 | 1.63 | General | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 |
| SPLIT GNE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.37 | 417.08 | 1120.11 | 1.00 | 1.76 | General | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 |
| SPLIT GN1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.33 | 371.86 | 1120.11 | 1.00 | 1.83 | General | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 |
| SPLIT GN2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.33 | 371.08 | 1120.11 | 1.00 | 1.83 | General | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 |
| SPLIT GS1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.34 | 383.25 | 1120.11 | 1.00 | 1.81 | General | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 |
| SPLIT GS2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.34 | 385.98 | 1120.11 | 1.00 | 1.80 | General | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 |
| SPLIT MSW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 1.00 | 1123.45 | 1120.11 | 1.00 | 1.37 | General | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 |
| SPLIT MNW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.99 | 1113.30 | 1120.11 | 1.00 | 1.37 | General | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 |
| SPLIT MSE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.90 | 1007.30 | 1120.11 | 1.00 | 1.40 | General | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 |
| SPLIT MNE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.89 | 997.64 | 1120.11 | 1.00 | 1.40 | General | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 |
| SPLIT MN1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.79 | 886.74 | 1120.11 | 1.00 | 1.44 | General | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 |
| SPLIT MN2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.79 | 884.47 | 1120.11 | 1.00 | 1.44 | General | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 |
| SPLIT MS1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.80 | 900.97 | 1120.11 | 1.00 | 1.43 | General | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 |
| SPLIT MS2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.80 | 898.62 | 1120.11 | 1.00 | 1.43 | General | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 |
| SPLIT TSW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.56 | 626.54 | 1120.11 | 1.00 | 1.56 | General | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 |
| SPLIT TNW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.56 | 632.11 | 1120.11 | 1.00 | 1.55 | General | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 |
| SPLIT TSE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.48 | 540.73 | 1120.11 | 1.00 | 1.62 | General | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 |
| SPLIT TNE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.49 | 546.07 | 1120.11 | 1.00 | 1.62 | General | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 |
| SPLIT TN1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.45 | 506.45 | 1120.11 | 1.00 | 1.65 | General | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 |
| SPLIT TN2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.45 | 503.48 | 1120.11 | 1.00 | 1.66 | General | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 |
| SPLIT TS1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.45 | 502.07 | 1120.11 | 1.00 | 1.66 | General | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 |
| SPLIT TS2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.45 | 499.11 | 1120.11 | 1.00 | 1.66 | General | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 |
| Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
| None |
| Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
| G SW APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.77 |
| G NW APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.77 |
| G NE APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.77 |
| G N1 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.77 |
| G N2 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.77 |
| G S1 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.77 |
| G S2 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.77 |
| M SW APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.79 |
| M NW APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.79 |
| M SE APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.79 |
| M NE APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.79 |
| M N1 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.79 |
| M N2 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.79 |
| M S1 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.79 |
| M S2 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.79 |
| T SW APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.77 |
| T NW APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.77 |
| T SE APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.77 |
| T NE APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.77 |
| T N1 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.77 |
| T N2 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.77 |
| T S1 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.77 |
| T S2 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.77 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 09:14:27
Zone Sensible Cooling| Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
| G SW APARTMENT | 4017.12 | 4820.54 | 54.62 | 0.346 | 0.416 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 24.00 | 24.00 | 0.00806 | 29.84 | 0.00569 | 0.026 | 0.00 |
| G NW APARTMENT | 3943.84 | 4732.61 | 53.63 | 0.340 | 0.408 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 24.00 | 24.00 | 0.00802 | 29.84 | 0.00569 | 0.026 | 0.00 |
| OFFICE | 4485.36 | 5382.44 | 60.99 | 0.392 | 0.470 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 23.90 | 23.90 | 0.00794 | 27.68 | 0.00569 | 0.038 | 0.00 |
| G NE APARTMENT | 3608.14 | 4329.77 | 49.06 | 0.310 | 0.372 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 24.00 | 24.00 | 0.00802 | 29.84 | 0.00569 | 0.026 | 0.00 |
| G N1 APARTMENT | 3224.84 | 3869.81 | 43.85 | 0.277 | 0.332 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 24.00 | 24.00 | 0.00806 | 29.84 | 0.00569 | 0.026 | 0.00 |
| G N2 APARTMENT | 3218.21 | 3861.86 | 43.76 | 0.276 | 0.331 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 24.00 | 24.00 | 0.00806 | 29.84 | 0.00569 | 0.026 | 0.00 |
| G S1 APARTMENT | 3322.17 | 3986.61 | 45.17 | 0.285 | 0.342 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 24.00 | 24.00 | 0.00814 | 29.84 | 0.00569 | 0.026 | 0.00 |
| G S2 APARTMENT | 3345.22 | 4014.26 | 45.49 | 0.287 | 0.345 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 24.00 | 24.00 | 0.00814 | 29.84 | 0.00569 | 0.026 | 0.00 |
| M SW APARTMENT | 9668.88 | 11602.65 | 131.48 | 0.836 | 1.003 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 24.00 | 24.00 | 0.00802 | 29.84 | 0.00569 | 0.052 | 0.00 |
| M NW APARTMENT | 9583.25 | 11499.90 | 130.31 | 0.828 | 0.994 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 24.00 | 24.00 | 0.00800 | 29.84 | 0.00569 | 0.052 | 0.00 |
| M SE APARTMENT | 8682.38 | 10418.86 | 118.06 | 0.749 | 0.899 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 24.00 | 24.00 | 0.00803 | 29.84 | 0.00569 | 0.052 | 0.00 |
| M NE APARTMENT | 8600.34 | 10320.41 | 116.95 | 0.742 | 0.891 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 24.00 | 24.00 | 0.00799 | 29.84 | 0.00569 | 0.052 | 0.00 |
| M N1 APARTMENT | 7660.37 | 9192.45 | 104.16 | 0.660 | 0.792 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 24.00 | 24.00 | 0.00803 | 29.84 | 0.00569 | 0.052 | 0.00 |
| M N2 APARTMENT | 7641.15 | 9169.38 | 103.90 | 0.658 | 0.790 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 24.00 | 24.00 | 0.00803 | 29.84 | 0.00569 | 0.052 | 0.00 |
| M S1 APARTMENT | 7780.72 | 9336.86 | 105.80 | 0.670 | 0.804 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 24.00 | 24.00 | 0.00808 | 29.84 | 0.00569 | 0.052 | 0.00 |
| M S2 APARTMENT | 7760.81 | 9312.98 | 105.53 | 0.669 | 0.802 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 24.00 | 24.00 | 0.00808 | 29.84 | 0.00569 | 0.052 | 0.00 |
| T SW APARTMENT | 5384.29 | 6461.15 | 73.21 | 0.466 | 0.559 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 24.00 | 24.00 | 0.00799 | 29.84 | 0.00569 | 0.026 | 0.00 |
| T NW APARTMENT | 5431.37 | 6517.65 | 73.85 | 0.470 | 0.564 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 24.00 | 24.00 | 0.00798 | 29.84 | 0.00569 | 0.026 | 0.00 |
| T SE APARTMENT | 4658.40 | 5590.08 | 63.34 | 0.402 | 0.483 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 24.00 | 24.00 | 0.00800 | 29.84 | 0.00569 | 0.026 | 0.00 |
| T NE APARTMENT | 4703.43 | 5644.12 | 63.96 | 0.406 | 0.488 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 24.00 | 24.00 | 0.00797 | 29.84 | 0.00569 | 0.026 | 0.00 |
| T N1 APARTMENT | 4368.73 | 5242.47 | 59.41 | 0.377 | 0.452 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 24.00 | 24.00 | 0.00801 | 29.84 | 0.00569 | 0.026 | 0.00 |
| T N2 APARTMENT | 4343.56 | 5212.27 | 59.06 | 0.375 | 0.449 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 24.00 | 24.00 | 0.00801 | 29.84 | 0.00569 | 0.026 | 0.00 |
| T S1 APARTMENT | 4331.83 | 5198.20 | 58.90 | 0.374 | 0.448 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 24.00 | 24.00 | 0.00804 | 29.84 | 0.00569 | 0.026 | 0.00 |
| T S2 APARTMENT | 4306.70 | 5168.04 | 58.56 | 0.371 | 0.446 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 24.00 | 24.00 | 0.00804 | 29.84 | 0.00569 | 0.026 | 0.00 |
| Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
| G SW APARTMENT | 1489.85 | 1787.82 | 20.26 | 0.078 | 0.094 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:50:00 | 21.10 | 21.10 | 0.00757 | -7.90 | 0.00234 | 0.026 | 0.00 |
| G NW APARTMENT | 1376.66 | 1651.99 | 18.72 | 0.072 | 0.087 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | 21.10 | 21.10 | 0.00768 | -7.90 | 0.00234 | 0.026 | 0.00 |
| OFFICE | 1930.76 | 2316.91 | 26.25 | 0.101 | 0.121 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 18:50:00 | 21.10 | 21.10 | 0.00766 | -7.90 | 0.00234 | 0.038 | 0.00 |
| G NE APARTMENT | 1376.66 | 1651.99 | 18.72 | 0.072 | 0.087 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | 21.10 | 21.10 | 0.00768 | -7.90 | 0.00234 | 0.026 | 0.00 |
| G N1 APARTMENT | 797.79 | 957.35 | 10.85 | 0.042 | 0.050 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | 21.10 | 21.10 | 0.00781 | -7.90 | 0.00234 | 0.026 | 0.00 |
| G N2 APARTMENT | 797.79 | 957.35 | 10.85 | 0.042 | 0.050 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | 21.10 | 21.10 | 0.00781 | -7.90 | 0.00234 | 0.026 | 0.00 |
| G S1 APARTMENT | 912.32 | 1094.79 | 12.41 | 0.048 | 0.057 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:50:00 | 21.10 | 21.10 | 0.00757 | -7.90 | 0.00234 | 0.026 | 0.00 |
| G S2 APARTMENT | 920.85 | 1105.02 | 12.52 | 0.048 | 0.058 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:50:00 | 21.10 | 21.10 | 0.00757 | -7.90 | 0.00234 | 0.026 | 0.00 |
| M SW APARTMENT | 2810.94 | 3373.13 | 38.22 | 0.147 | 0.177 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | 21.10 | 21.10 | 0.00738 | -7.90 | 0.00234 | 0.052 | 0.00 |
| M NW APARTMENT | 2538.79 | 3046.55 | 34.52 | 0.133 | 0.160 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | 21.10 | 21.10 | 0.00754 | -7.90 | 0.00234 | 0.052 | 0.00 |
| M SE APARTMENT | 2810.94 | 3373.13 | 38.22 | 0.147 | 0.177 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | 21.10 | 21.10 | 0.00738 | -7.90 | 0.00234 | 0.052 | 0.00 |
| M NE APARTMENT | 2538.79 | 3046.55 | 34.52 | 0.133 | 0.160 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | 21.10 | 21.10 | 0.00754 | -7.90 | 0.00234 | 0.052 | 0.00 |
| M N1 APARTMENT | 1259.25 | 1511.10 | 17.12 | 0.066 | 0.079 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | 21.10 | 21.10 | 0.00762 | -7.90 | 0.00234 | 0.052 | 0.00 |
| M N2 APARTMENT | 1259.25 | 1511.10 | 17.12 | 0.066 | 0.079 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | 21.10 | 21.10 | 0.00762 | -7.90 | 0.00234 | 0.052 | 0.00 |
| M S1 APARTMENT | 1524.25 | 1829.09 | 20.73 | 0.080 | 0.096 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | 21.10 | 21.10 | 0.00730 | -7.90 | 0.00234 | 0.052 | 0.00 |
| M S2 APARTMENT | 1524.25 | 1829.09 | 20.73 | 0.080 | 0.096 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | 21.10 | 21.10 | 0.00730 | -7.90 | 0.00234 | 0.052 | 0.00 |
| T SW APARTMENT | 2491.21 | 2989.45 | 33.88 | 0.131 | 0.157 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | 21.10 | 21.10 | 0.00752 | -7.90 | 0.00234 | 0.026 | 0.00 |
| T NW APARTMENT | 2349.08 | 2818.90 | 31.94 | 0.123 | 0.148 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | 21.10 | 21.10 | 0.00762 | -7.90 | 0.00234 | 0.026 | 0.00 |
| T SE APARTMENT | 2491.21 | 2989.45 | 33.88 | 0.131 | 0.157 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | 21.10 | 21.10 | 0.00752 | -7.90 | 0.00234 | 0.026 | 0.00 |
| T NE APARTMENT | 2349.08 | 2818.90 | 31.94 | 0.123 | 0.148 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | 21.10 | 21.10 | 0.00762 | -7.90 | 0.00234 | 0.026 | 0.00 |
| T N1 APARTMENT | 1593.07 | 1911.69 | 21.66 | 0.083 | 0.100 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | 21.10 | 21.10 | 0.00773 | -7.90 | 0.00234 | 0.026 | 0.00 |
| T N2 APARTMENT | 1593.07 | 1911.69 | 21.66 | 0.083 | 0.100 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | 21.10 | 21.10 | 0.00773 | -7.90 | 0.00234 | 0.026 | 0.00 |
| T S1 APARTMENT | 1735.30 | 2082.36 | 23.60 | 0.091 | 0.109 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | 21.10 | 21.10 | 0.00758 | -7.90 | 0.00234 | 0.026 | 0.00 |
| T S2 APARTMENT | 1735.30 | 2082.36 | 23.60 | 0.091 | 0.109 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | 21.10 | 21.10 | 0.00758 | -7.90 | 0.00234 | 0.026 | 0.00 |
| Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
| SPLIT GSW | 0.42 | 0.42 | 0.09 | 0.09 | 0.4156 | 0.4156 | 0.4156 | 1.0000 | 1.0000 |
| SPLIT GNW | 0.41 | 0.41 | 0.09 | 0.09 | 0.4078 | 0.4078 | 0.4078 | 1.0000 | 1.0000 |
| SPLIT OFFICE | 0.47 | 0.47 | 0.12 | 0.12 | 0.4704 | 0.4704 | 0.4704 | 1.0000 | 1.0000 |
| SPLIT GNE | 0.37 | 0.37 | 0.09 | 0.09 | 0.3724 | 0.3724 | 0.3724 | 1.0000 | 1.0000 |
| SPLIT GN1 | 0.33 | 0.33 | 0.05 | 0.05 | 0.3320 | 0.3320 | 0.3320 | 1.0000 | 1.0000 |
| SPLIT GN2 | 0.33 | 0.33 | 0.05 | 0.05 | 0.3313 | 0.3313 | 0.3313 | 1.0000 | 1.0000 |
| SPLIT GS1 | 0.34 | 0.34 | 0.06 | 0.06 | 0.3422 | 0.3422 | 0.3422 | 1.0000 | 1.0000 |
| SPLIT GS2 | 0.34 | 0.34 | 0.06 | 0.06 | 0.3446 | 0.3446 | 0.3446 | 1.0000 | 1.0000 |
| SPLIT MSW | 1.00 | 1.00 | 0.18 | 0.18 | 1.0030 | 1.0030 | 1.0030 | 1.0000 | 1.0000 |
| SPLIT MNW | 0.99 | 0.99 | 0.16 | 0.16 | 0.9939 | 0.9939 | 0.9939 | 1.0000 | 1.0000 |
| SPLIT MSE | 0.90 | 0.90 | 0.18 | 0.18 | 0.8993 | 0.8993 | 0.8993 | 1.0000 | 1.0000 |
| SPLIT MNE | 0.89 | 0.89 | 0.16 | 0.16 | 0.8907 | 0.8907 | 0.8907 | 1.0000 | 1.0000 |
| SPLIT MN1 | 0.79 | 0.79 | 0.08 | 0.08 | 0.7917 | 0.7917 | 0.7917 | 1.0000 | 1.0000 |
| SPLIT MN2 | 0.79 | 0.79 | 0.08 | 0.08 | 0.7896 | 0.7896 | 0.7896 | 1.0000 | 1.0000 |
| SPLIT MS1 | 0.80 | 0.80 | 0.10 | 0.10 | 0.8044 | 0.8044 | 0.8044 | 1.0000 | 1.0000 |
| SPLIT MS2 | 0.80 | 0.80 | 0.10 | 0.10 | 0.8023 | 0.8023 | 0.8023 | 1.0000 | 1.0000 |
| SPLIT TSW | 0.56 | 0.56 | 0.16 | 0.16 | 0.5594 | 0.5594 | 0.5594 | 1.0000 | 1.0000 |
| SPLIT TNW | 0.56 | 0.56 | 0.15 | 0.15 | 0.5643 | 0.5643 | 0.5643 | 1.0000 | 1.0000 |
| SPLIT TSE | 0.48 | 0.48 | 0.16 | 0.16 | 0.4828 | 0.4828 | 0.4828 | 1.0000 | 1.0000 |
| SPLIT TNE | 0.49 | 0.49 | 0.15 | 0.15 | 0.4875 | 0.4875 | 0.4875 | 1.0000 | 1.0000 |
| SPLIT TN1 | 0.45 | 0.45 | 0.10 | 0.10 | 0.4521 | 0.4521 | 0.4521 | 1.0000 | 1.0000 |
| SPLIT TN2 | 0.45 | 0.45 | 0.10 | 0.10 | 0.4495 | 0.4495 | 0.4495 | 1.0000 | 1.0000 |
| SPLIT TS1 | 0.45 | 0.45 | 0.11 | 0.11 | 0.4482 | 0.4482 | 0.4482 | 1.0000 | 1.0000 |
| SPLIT TS2 | 0.45 | 0.45 | 0.11 | 0.11 | 0.4456 | 0.4456 | 0.4456 | 1.0000 | 1.0000 |
| Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
| None |
| Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
| SPLIT GSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT GSW | 6879.082 | 5507.774 | 0.415565 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 6316.85 | 6316.85 | 0.415565 | 25.52 | 14.42 | 0.00791202 | 12.80 | 9.77 | 0.00791202 | 29.84 | 0.00569125 | 14.04 | 6.2456 | 24.00 | 0.00805996 | 35.7111 | 4017.12 | 0.00 | 6877.91 | 4996.58 |
| SPLIT GSW HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT GSW | 8565.901 | 8565.901 | -999.0 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:50:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:50:00 | 8565.90 | 8565.90 | 0.415565 | 19.29 | 11.64 | 0.00724023 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 6.2456 | 21.10 | 0.00756646 | 40.0140 | 1489.85 | 0.00 | -999.00 | -999.00 |
| SPLIT GNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT GNW | 6751.078 | 5405.286 | 0.407833 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 6194.59 | 6194.59 | 0.407833 | 25.53 | 14.39 | 0.00787271 | 12.80 | 9.73 | 0.00787271 | 29.84 | 0.00569125 | 14.04 | 6.3640 | 24.00 | 0.00802097 | 35.5401 | 3943.84 | 0.00 | 6749.93 | 4903.60 |
| SPLIT GNW HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT GNW | 8420.386 | 8420.386 | -999.0 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | 8420.39 | 8420.39 | 0.407833 | 19.25 | 11.72 | 0.00734409 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 6.3640 | 21.10 | 0.00768398 | 40.6279 | 1376.66 | 0.00 | -999.00 | -999.00 |
| SPLIT OFFICE COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT OFFICE | 7785.994 | 6233.897 | 0.470352 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 7238.37 | 7238.37 | 0.470352 | 25.37 | 14.24 | 0.00775931 | 12.80 | 9.62 | 0.00775931 | 27.68 | 0.00568796 | 13.29 | 8.1016 | 23.90 | 0.00794191 | 35.4053 | 4485.36 | 0.00 | 7784.67 | 5655.31 |
| SPLIT OFFICE HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT OFFICE | 9947.145 | 9947.145 | -999.0 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 18:50:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 18:50:00 | 9947.14 | 9947.14 | 0.470352 | 18.75 | 11.43 | 0.00723012 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 8.1016 | 21.10 | 0.00766094 | 40.5075 | 1930.76 | 0.00 | -999.00 | -999.00 |
| SPLIT GNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT GNE | 6163.820 | 4935.095 | 0.372356 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 5655.58 | 5655.58 | 0.372356 | 25.56 | 14.39 | 0.00785898 | 12.80 | 9.72 | 0.00785898 | 29.84 | 0.00569125 | 14.04 | 6.9704 | 24.00 | 0.00802140 | 35.5419 | 3608.14 | 0.00 | 6162.77 | 4477.05 |
| SPLIT GNE HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT GNE | 7753.080 | 7753.080 | -999.0 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | 7753.08 | 7753.08 | 0.372356 | 19.08 | 11.62 | 0.00731170 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 6.9704 | 21.10 | 0.00768398 | 40.6279 | 1376.66 | 0.00 | -999.00 | -999.00 |
| SPLIT GN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT GN1 | 5495.519 | 4400.017 | 0.331984 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 5045.84 | 5045.84 | 0.331984 | 25.60 | 14.41 | 0.00787591 | 12.80 | 9.74 | 0.00787591 | 29.83 | 0.00569125 | 14.04 | 7.8180 | 24.00 | 0.00806120 | 35.7163 | 3224.84 | 0.00 | 5494.58 | 3991.63 |
| SPLIT GN1 HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT GN1 | 6993.629 | 6993.629 | -999.0 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | 6993.63 | 6993.63 | 0.331984 | 18.83 | 11.60 | 0.00738372 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 7.8180 | 21.10 | 0.00781121 | 41.2914 | 797.79 | 0.00 | -999.00 | -999.00 |
| SPLIT GN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT GN2 | 5483.978 | 4390.776 | 0.331287 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 5035.24 | 5035.24 | 0.331287 | 25.60 | 14.41 | 0.00787566 | 12.80 | 9.74 | 0.00787566 | 29.84 | 0.00569125 | 14.04 | 7.8345 | 24.00 | 0.00806134 | 35.7170 | 3218.21 | 0.00 | 5483.04 | 3983.25 |
| SPLIT GN2 HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT GN2 | 6980.514 | 6980.514 | -999.0 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | 6980.51 | 6980.51 | 0.331287 | 18.83 | 11.60 | 0.00738282 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 7.8345 | 21.10 | 0.00781121 | 41.2914 | 797.79 | 0.00 | -999.00 | -999.00 |
| SPLIT GS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT GS1 | 5663.916 | 4534.844 | 0.342157 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 5208.29 | 5208.29 | 0.342157 | 25.59 | 14.47 | 0.00795290 | 12.80 | 9.81 | 0.00795290 | 29.84 | 0.00569125 | 14.04 | 7.5856 | 24.00 | 0.00813854 | 36.0553 | 3322.17 | 0.00 | 5662.95 | 4113.95 |
| SPLIT GS1 HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT GS1 | 7185.035 | 7185.035 | -999.0 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:50:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:50:00 | 7185.04 | 7185.04 | 0.342157 | 18.90 | 11.43 | 0.00716907 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 7.5856 | 21.10 | 0.00756519 | 40.0069 | 912.32 | 0.00 | -999.00 | -999.00 |
| SPLIT GS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT GS2 | 5704.216 | 4567.110 | 0.344592 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 5245.31 | 5245.31 | 0.344592 | 25.58 | 14.47 | 0.00795372 | 12.80 | 9.81 | 0.00795372 | 29.83 | 0.00569125 | 14.04 | 7.5320 | 24.00 | 0.00813801 | 36.0530 | 3345.22 | 0.00 | 5703.24 | 4143.22 |
| SPLIT GS2 HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT GS2 | 7230.828 | 7230.828 | -999.0 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:50:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:50:00 | 7230.83 | 7230.83 | 0.344592 | 18.92 | 11.44 | 0.00717535 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 7.5320 | 21.10 | 0.00756896 | 40.0265 | 920.85 | 0.00 | -999.00 | -999.00 |
| SPLIT MSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT MSW | 16602.940 | 13293.231 | 1.002984 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 15235.49 | 15235.49 | 1.002984 | 25.47 | 14.39 | 0.00789945 | 12.80 | 9.76 | 0.00789945 | 29.84 | 0.00569125 | 14.04 | 5.1755 | 24.00 | 0.00801997 | 35.5357 | 19337.75 | 0.00 | 16600.11 | 12059.44 |
| SPLIT MSW HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT MSW | 20364.975 | 20364.975 | -999.0 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | 20364.98 | 20364.98 | 1.002984 | 19.60 | 11.64 | 0.00711505 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 5.1755 | 21.10 | 0.00737550 | 39.0172 | 5621.89 | 0.00 | -999.00 | -999.00 |
| SPLIT MNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT MNW | 16452.976 | 13173.162 | 0.993924 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 15090.87 | 15090.87 | 0.993924 | 25.47 | 14.37 | 0.00787593 | 12.80 | 9.74 | 0.00787593 | 29.84 | 0.00569125 | 14.04 | 5.2226 | 24.00 | 0.00799632 | 35.4320 | 19166.50 | 0.00 | 16450.18 | 11950.51 |
| SPLIT MNW HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT MNW | 20194.238 | 20194.238 | -999.0 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | 20194.24 | 20194.24 | 0.993924 | 19.58 | 11.77 | 0.00726930 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 5.2226 | 21.10 | 0.00754075 | 39.8801 | 5077.58 | 0.00 | -999.00 | -999.00 |
| SPLIT MSE COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT MSE | 14886.407 | 11918.880 | 0.899288 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 13661.63 | 13661.63 | 0.899288 | 25.50 | 14.39 | 0.00789240 | 12.80 | 9.75 | 0.00789240 | 29.84 | 0.00569125 | 14.04 | 5.7722 | 24.00 | 0.00802724 | 35.5676 | 17364.77 | 0.00 | 14883.87 | 10812.64 |
| SPLIT MSE HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT MSE | 18414.382 | 18414.382 | -999.0 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | 18414.38 | 18414.38 | 0.899288 | 19.43 | 11.55 | 0.00708502 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 5.7722 | 21.10 | 0.00737550 | 39.0172 | 5621.89 | 0.00 | -999.00 | -999.00 |
| SPLIT MNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT MNE | 14743.705 | 11804.625 | 0.890667 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 13521.66 | 13521.66 | 0.890667 | 25.50 | 14.37 | 0.00785910 | 12.80 | 9.72 | 0.00785910 | 29.84 | 0.00569125 | 14.04 | 5.8281 | 24.00 | 0.00799327 | 35.4186 | 17200.68 | 0.00 | 14741.20 | 10708.99 |
| SPLIT MNE HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT MNE | 18251.932 | 18251.932 | -999.0 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | 18251.93 | 18251.93 | 0.890667 | 19.41 | 11.68 | 0.00723783 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 5.8281 | 21.10 | 0.00754075 | 39.8801 | 5077.58 | 0.00 | -999.00 | -999.00 |
| SPLIT MN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT MN1 | 13104.728 | 10492.369 | 0.791657 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 12026.54 | 12026.54 | 0.791657 | 25.54 | 14.39 | 0.00787685 | 12.80 | 9.74 | 0.00787685 | 29.84 | 0.00569125 | 14.04 | 6.5570 | 24.00 | 0.00803022 | 35.5806 | 15320.74 | 0.00 | 13102.50 | 9518.53 |
| SPLIT MN1 HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT MN1 | 16389.211 | 16389.211 | -999.0 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | 16389.21 | 16389.21 | 0.791657 | 19.20 | 11.63 | 0.00727245 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 6.5570 | 21.10 | 0.00761834 | 40.2845 | 2518.50 | 0.00 | -999.00 | -999.00 |
| SPLIT MN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT MN2 | 13071.140 | 10465.477 | 0.789628 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 11995.72 | 11995.72 | 0.789628 | 25.54 | 14.39 | 0.00787651 | 12.80 | 9.74 | 0.00787651 | 29.83 | 0.00569125 | 14.04 | 6.5739 | 24.00 | 0.00803028 | 35.5808 | 15282.31 | 0.00 | 13068.92 | 9494.14 |
| SPLIT MN2 HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT MN2 | 16351.045 | 16351.045 | -999.0 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | 16351.05 | 16351.05 | 0.789628 | 19.19 | 11.63 | 0.00727156 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 6.5739 | 21.10 | 0.00761834 | 40.2845 | 2518.50 | 0.00 | -999.00 | -999.00 |
| SPLIT MS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT MS1 | 13314.987 | 10660.715 | 0.804358 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 12231.74 | 12231.74 | 0.804358 | 25.53 | 14.43 | 0.00792748 | 12.80 | 9.79 | 0.00792748 | 29.83 | 0.00569125 | 14.04 | 6.4535 | 24.00 | 0.00808175 | 35.8065 | 15561.43 | 0.00 | 13312.72 | 9671.25 |
| SPLIT MS1 HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT MS1 | 16628.407 | 16628.407 | -999.0 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | 16628.41 | 16628.41 | 0.804358 | 19.23 | 11.38 | 0.00698280 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 6.4535 | 21.10 | 0.00730287 | 38.6366 | 3048.49 | 0.00 | -999.00 | -999.00 |
| SPLIT MS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT MS2 | 13280.229 | 10632.885 | 0.802259 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 12199.91 | 12199.90 | 0.802259 | 25.53 | 14.43 | 0.00792750 | 12.80 | 9.79 | 0.00792750 | 29.84 | 0.00569125 | 14.04 | 6.4704 | 24.00 | 0.00808220 | 35.8085 | 15521.63 | 0.00 | 13277.97 | 9646.01 |
| SPLIT MS2 HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT MS2 | 16588.910 | 16588.910 | -999.0 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | 16588.91 | 16588.91 | 0.802259 | 19.22 | 11.38 | 0.00698196 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 6.4704 | 21.10 | 0.00730287 | 38.6366 | 3048.49 | 0.00 | -999.00 | -999.00 |
| SPLIT TSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT TSW | 9259.354 | 7413.551 | 0.559358 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 8492.73 | 8492.73 | 0.559358 | 25.44 | 14.37 | 0.00788755 | 12.80 | 9.75 | 0.00788755 | 29.84 | 0.00569125 | 14.04 | 4.6401 | 24.00 | 0.00799442 | 35.4237 | 5384.29 | 0.00 | 9257.78 | 6725.47 |
| SPLIT TSW HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT TSW | 11271.184 | 11271.184 | -999.0 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | 11271.18 | 11271.18 | 0.559358 | 19.75 | 11.85 | 0.00728126 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 4.6401 | 21.10 | 0.00752154 | 39.7815 | 2491.21 | 0.00 | -999.00 | -999.00 |
| SPLIT TNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT TNW | 9341.720 | 7479.497 | 0.564333 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 8565.79 | 8565.79 | 0.564333 | 25.44 | 14.36 | 0.00787439 | 12.80 | 9.73 | 0.00787439 | 29.84 | 0.00569125 | 14.04 | 4.5992 | 24.00 | 0.00797963 | 35.3589 | 5431.37 | 0.00 | 9340.13 | 6785.30 |
| SPLIT TNW HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT TNW | 11364.593 | 11364.593 | -999.0 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | 11364.59 | 11364.59 | 0.564333 | 19.77 | 11.94 | 0.00737759 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 4.5992 | 21.10 | 0.00762030 | 40.2966 | 2349.08 | 0.00 | -999.00 | -999.00 |
| SPLIT TSE COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT TSE | 7991.256 | 6398.242 | 0.482752 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 7329.69 | 7329.69 | 0.482752 | 25.48 | 14.37 | 0.00787198 | 12.80 | 9.73 | 0.00787198 | 29.84 | 0.00569125 | 14.04 | 5.3764 | 24.00 | 0.00799589 | 35.4302 | 4658.40 | 0.00 | 7989.90 | 5804.40 |
| SPLIT TSE HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT TSE | 9830.145 | 9830.145 | -999.0 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | 9830.14 | 9830.14 | 0.482752 | 19.54 | 11.73 | 0.00724313 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 5.3764 | 21.10 | 0.00752154 | 39.7815 | 2491.21 | 0.00 | -999.00 | -999.00 |
| SPLIT TNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT TNE | 8070.114 | 6461.379 | 0.487516 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 7398.99 | 7398.99 | 0.487516 | 25.48 | 14.35 | 0.00785336 | 12.80 | 9.71 | 0.00785336 | 29.84 | 0.00569125 | 14.04 | 5.3238 | 24.00 | 0.00797494 | 35.3383 | 4703.43 | 0.00 | 8068.74 | 5861.67 |
| SPLIT TNE HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT TNE | 9919.594 | 9919.594 | -999.0 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | 9919.59 | 9919.59 | 0.487516 | 19.56 | 11.83 | 0.00733935 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 5.3238 | 21.10 | 0.00762030 | 40.2966 | 2349.08 | 0.00 | -999.00 | -999.00 |
| SPLIT TN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT TN1 | 7484.520 | 5992.520 | 0.452140 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 6867.05 | 6867.05 | 0.452140 | 25.50 | 14.38 | 0.00787897 | 12.80 | 9.74 | 0.00787897 | 29.84 | 0.00569125 | 14.04 | 5.7404 | 24.00 | 0.00801221 | 35.5017 | 4368.73 | 0.00 | 7483.25 | 5436.33 |
| SPLIT TN1 HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT TN1 | 9253.918 | 9253.918 | -999.0 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | 9253.92 | 9253.92 | 0.452140 | 19.43 | 11.86 | 0.00742318 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 5.7404 | 21.10 | 0.00773255 | 40.8816 | 1593.07 | 0.00 | -999.00 | -999.00 |
| SPLIT TN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT TN2 | 7440.639 | 5957.387 | 0.449489 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 6826.78 | 6826.78 | 0.449489 | 25.50 | 14.38 | 0.00787822 | 12.80 | 9.74 | 0.00787822 | 29.84 | 0.00569125 | 14.04 | 5.7742 | 24.00 | 0.00801224 | 35.5018 | 4343.56 | 0.00 | 7439.37 | 5404.46 |
| SPLIT TN2 HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT TN2 | 9204.055 | 9204.055 | -999.0 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | 9204.05 | 9204.05 | 0.449489 | 19.42 | 11.85 | 0.00742136 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 5.7742 | 21.10 | 0.00773255 | 40.8816 | 1593.07 | 0.00 | -999.00 | -999.00 |
| SPLIT TS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT TS1 | 7419.869 | 5940.757 | 0.448234 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 6811.27 | 6811.27 | 0.448234 | 25.51 | 14.40 | 0.00790299 | 12.80 | 9.76 | 0.00790299 | 29.84 | 0.00569125 | 14.04 | 5.7904 | 24.00 | 0.00803893 | 35.6189 | 4331.83 | 0.00 | 7418.61 | 5389.37 |
| SPLIT TS1 HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT TS1 | 9180.610 | 9180.610 | -999.0 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | 9180.61 | 9180.61 | 0.448234 | 19.42 | 11.72 | 0.00727721 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 5.7904 | 21.10 | 0.00758048 | 40.0881 | 1735.30 | 0.00 | -999.00 | -999.00 |
| SPLIT TS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT TS2 | 7376.180 | 5905.778 | 0.445595 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 6771.20 | 6771.20 | 0.445595 | 25.51 | 14.40 | 0.00790258 | 12.80 | 9.76 | 0.00790258 | 29.84 | 0.00569125 | 14.04 | 5.8247 | 24.00 | 0.00803935 | 35.6207 | 4306.70 | 0.00 | 7374.93 | 5357.64 |
| SPLIT TS2 HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT TS2 | 9130.965 | 9130.965 | -999.0 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | 9130.96 | 9130.96 | 0.445595 | 19.41 | 11.72 | 0.00727542 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 5.8247 | 21.10 | 0.00758048 | 40.0881 | 1735.30 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 09:14:27
Coils| Coil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
| SPLIT GSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT GSW | G SW APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 6879.082 | 5507.774 | 0.415565 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.5481 | 1004.8586 | 0.9904 | SPLIT GSW SUPPLY FAN | Fan:OnOff | 0.415565 | 0.41157964 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | Sensible | 6316.85 | 6316.85 | 0.9183 | 0.41157964 | 0.415565 | 25.52 | 14.42 | 0.00791202 | 45807.5 | 12.80 | 9.77 | 0.00791202 | 32837.7 | -999.0 | -999.00 | -999.00 | -999.00 | 465.478 | 5851.38 | 29.84 | 0.00569125 | 14.04 | 0.02595455 | 6.2456 | 24.05 | 0.00805996 | 24.00 | 0.00805996 | 35.7111 | 4017.12 | 0.00 | 6877.91 | 4996.58 | 0.39532535 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.30 | 13.50 | 0.00931878 | 37924.3 | |
| SPLIT GSW HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT GSW | G SW APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 8565.901 | 8565.901 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | SPLIT GSW SUPPLY FAN | Fan:OnOff | 0.415565 | 0.41157964 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:50:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:50:00 | Sensible | 8565.90 | 8565.90 | 1.0000 | 0.41157964 | 0.415565 | 19.29 | 11.64 | 0.00724023 | 37748.7 | 40.00 | 18.92 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8565.90 | -7.90 | 0.00234317 | -7.90 | 0.02595455 | 6.2456 | 21.10 | 0.00756646 | 21.10 | 0.00756646 | 40.0140 | 1489.85 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT GNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT GNW | G NW APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 6751.078 | 5405.286 | 0.407833 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.4750 | 1004.8586 | 0.9904 | SPLIT GNW SUPPLY FAN | Fan:OnOff | 0.407833 | 0.40392105 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | Sensible | 6194.59 | 6194.59 | 0.9176 | 0.40392105 | 0.407833 | 25.53 | 14.39 | 0.00787271 | 45713.4 | 12.80 | 9.73 | 0.00787271 | 32738.5 | -999.0 | -999.00 | -999.00 | -999.00 | 456.817 | 5737.77 | 29.84 | 0.00569125 | 14.04 | 0.02595455 | 6.3640 | 24.05 | 0.00802097 | 24.00 | 0.00802097 | 35.5401 | 3943.84 | 0.00 | 6749.93 | 4903.60 | 0.38796922 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.30 | 13.50 | 0.00931878 | 37924.3 | |
| SPLIT GNW HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT GNW | G NW APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 8420.386 | 8420.386 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | SPLIT GNW SUPPLY FAN | Fan:OnOff | 0.407833 | 0.40392105 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | Sensible | 8420.39 | 8420.39 | 1.0000 | 0.40392105 | 0.407833 | 19.25 | 11.72 | 0.00734409 | 37977.4 | 40.00 | 18.92 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8420.39 | -7.90 | 0.00234317 | -7.90 | 0.02595455 | 6.3640 | 21.10 | 0.00768398 | 21.10 | 0.00768398 | 40.6279 | 1376.66 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT OFFICE COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT OFFICE | OFFICE | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 7785.994 | 6233.897 | 0.470352 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.2642 | 1004.8586 | 0.9904 | SPLIT OFFICE SUPPLY FAN | Fan:OnOff | 0.470352 | 0.46584069 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | Sensible | 7238.37 | 7238.37 | 0.9297 | 0.46584069 | 0.470352 | 25.37 | 14.24 | 0.00775931 | 45268.7 | 12.80 | 9.62 | 0.00775931 | 32452.1 | -999.0 | -999.00 | -999.00 | -999.00 | 526.845 | 6711.53 | 27.68 | 0.00568796 | 13.29 | 0.03810604 | 8.1016 | 23.96 | 0.00794191 | 23.90 | 0.00794191 | 35.4053 | 4485.36 | 0.00 | 7784.67 | 5655.31 | 0.44744350 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.30 | 13.50 | 0.00931878 | 37924.3 | |
| SPLIT OFFICE HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT OFFICE | OFFICE | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 9947.145 | 9947.145 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | SPLIT OFFICE SUPPLY FAN | Fan:OnOff | 0.470352 | 0.46584069 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 18:50:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 18:50:00 | Sensible | 9947.14 | 9947.14 | 1.0000 | 0.46584069 | 0.470352 | 18.75 | 11.43 | 0.00723012 | 37175.0 | 40.00 | 18.92 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9947.14 | -7.90 | 0.00234317 | -7.90 | 0.03810604 | 8.1016 | 21.10 | 0.00766094 | 21.10 | 0.00766094 | 40.5075 | 1930.76 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT GNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT GNE | G NE APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 6163.820 | 4935.095 | 0.372356 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.4494 | 1004.8586 | 0.9904 | SPLIT GNE SUPPLY FAN | Fan:OnOff | 0.372356 | 0.36878505 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | Sensible | 5655.58 | 5655.58 | 0.9175 | 0.36878505 | 0.372356 | 25.56 | 14.39 | 0.00785898 | 45709.2 | 12.80 | 9.72 | 0.00785898 | 32703.8 | -999.0 | -999.00 | -999.00 | -999.00 | 417.079 | 5238.50 | 29.84 | 0.00569125 | 14.04 | 0.02595455 | 6.9704 | 24.04 | 0.00802140 | 24.00 | 0.00802140 | 35.5419 | 3608.14 | 0.00 | 6162.77 | 4477.05 | 0.35422083 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.30 | 13.50 | 0.00931878 | 37924.3 | |
| SPLIT GNE HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT GNE | G NE APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 7753.080 | 7753.080 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | SPLIT GNE SUPPLY FAN | Fan:OnOff | 0.372356 | 0.36878505 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | Sensible | 7753.08 | 7753.08 | 1.0000 | 0.36878505 | 0.372356 | 19.08 | 11.62 | 0.00731170 | 37716.1 | 40.00 | 18.92 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 7753.08 | -7.90 | 0.00234317 | -7.90 | 0.02595455 | 6.9704 | 21.10 | 0.00768398 | 21.10 | 0.00768398 | 40.6279 | 1376.66 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT GN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT GN1 | G N1 APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 5495.519 | 4400.017 | 0.331984 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.4809 | 1004.8586 | 0.9904 | SPLIT GN1 SUPPLY FAN | Fan:OnOff | 0.331984 | 0.32880023 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | Sensible | 5045.84 | 5045.84 | 0.9182 | 0.32880023 | 0.331984 | 25.60 | 14.41 | 0.00787591 | 45792.4 | 12.80 | 9.74 | 0.00787591 | 32746.5 | -999.0 | -999.00 | -999.00 | -999.00 | 371.858 | 4673.98 | 29.83 | 0.00569125 | 14.04 | 0.02595455 | 7.8180 | 24.03 | 0.00806120 | 24.00 | 0.00806120 | 35.7163 | 3224.84 | 0.00 | 5494.58 | 3991.63 | 0.31581511 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.30 | 13.50 | 0.00931878 | 37924.3 | |
| SPLIT GN1 HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT GN1 | G N1 APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 6993.629 | 6993.629 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | SPLIT GN1 SUPPLY FAN | Fan:OnOff | 0.331984 | 0.32880023 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | Sensible | 6993.63 | 6993.63 | 1.0000 | 0.32880023 | 0.331984 | 18.83 | 11.60 | 0.00738372 | 37648.6 | 40.00 | 18.92 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 6993.63 | -7.90 | 0.00234317 | -7.90 | 0.02595455 | 7.8180 | 21.10 | 0.00781121 | 21.10 | 0.00781121 | 41.2914 | 797.79 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT GN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT GN2 | G N2 APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 5483.978 | 4390.776 | 0.331287 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.4805 | 1004.8586 | 0.9904 | SPLIT GN2 SUPPLY FAN | Fan:OnOff | 0.331287 | 0.32810968 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | Sensible | 5035.24 | 5035.24 | 0.9182 | 0.32810968 | 0.331287 | 25.60 | 14.41 | 0.00787566 | 45792.6 | 12.80 | 9.74 | 0.00787566 | 32745.9 | -999.0 | -999.00 | -999.00 | -999.00 | 371.077 | 4664.17 | 29.84 | 0.00569125 | 14.04 | 0.02595455 | 7.8345 | 24.03 | 0.00806134 | 24.00 | 0.00806134 | 35.7170 | 3218.21 | 0.00 | 5483.04 | 3983.25 | 0.31515183 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.30 | 13.50 | 0.00931878 | 37924.3 | |
| SPLIT GN2 HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT GN2 | G N2 APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 6980.514 | 6980.514 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | SPLIT GN2 SUPPLY FAN | Fan:OnOff | 0.331287 | 0.32810968 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | Sensible | 6980.51 | 6980.51 | 1.0000 | 0.32810968 | 0.331287 | 18.83 | 11.60 | 0.00738282 | 37641.4 | 40.00 | 18.92 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 6980.51 | -7.90 | 0.00234317 | -7.90 | 0.02595455 | 7.8345 | 21.10 | 0.00781121 | 21.10 | 0.00781121 | 41.2914 | 797.79 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT GS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT GS1 | G S1 APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 5663.916 | 4534.844 | 0.342157 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.6240 | 1004.8586 | 0.9904 | SPLIT GS1 SUPPLY FAN | Fan:OnOff | 0.342157 | 0.33887550 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | Sensible | 5208.29 | 5208.29 | 0.9196 | 0.33887550 | 0.342157 | 25.59 | 14.47 | 0.00795290 | 45978.8 | 12.80 | 9.81 | 0.00795290 | 32940.9 | -999.0 | -999.00 | -999.00 | -999.00 | 383.253 | 4825.04 | 29.84 | 0.00569125 | 14.04 | 0.02595455 | 7.5856 | 24.04 | 0.00813854 | 24.00 | 0.00813854 | 36.0553 | 3322.17 | 0.00 | 5662.95 | 4113.95 | 0.32549248 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.30 | 13.50 | 0.00931878 | 37924.3 | |
| SPLIT GS1 HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT GS1 | G S1 APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 7185.035 | 7185.035 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | SPLIT GS1 SUPPLY FAN | Fan:OnOff | 0.342157 | 0.33887550 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:50:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:50:00 | Sensible | 7185.04 | 7185.04 | 1.0000 | 0.33887550 | 0.342157 | 18.90 | 11.43 | 0.00716907 | 37172.7 | 40.00 | 18.92 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 7185.04 | -7.90 | 0.00234317 | -7.90 | 0.02595455 | 7.5856 | 21.10 | 0.00756519 | 21.10 | 0.00756519 | 40.0069 | 912.32 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT GS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT GS2 | G S2 APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 5704.216 | 4567.110 | 0.344592 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.6256 | 1004.8586 | 0.9904 | SPLIT GS2 SUPPLY FAN | Fan:OnOff | 0.344592 | 0.34128665 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | Sensible | 5245.31 | 5245.31 | 0.9195 | 0.34128665 | 0.344592 | 25.58 | 14.47 | 0.00795372 | 45978.0 | 12.80 | 9.81 | 0.00795372 | 32943.0 | -999.0 | -999.00 | -999.00 | -999.00 | 385.980 | 4859.33 | 29.83 | 0.00569125 | 14.04 | 0.02595455 | 7.5320 | 24.04 | 0.00813801 | 24.00 | 0.00813801 | 36.0530 | 3345.22 | 0.00 | 5703.24 | 4143.22 | 0.32780840 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.30 | 13.50 | 0.00931878 | 37924.3 | |
| SPLIT GS2 HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT GS2 | G S2 APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 7230.828 | 7230.828 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | SPLIT GS2 SUPPLY FAN | Fan:OnOff | 0.344592 | 0.34128665 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:50:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:50:00 | Sensible | 7230.83 | 7230.83 | 1.0000 | 0.34128665 | 0.344592 | 18.92 | 11.44 | 0.00717535 | 37204.5 | 40.00 | 18.92 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 7230.83 | -7.90 | 0.00234317 | -7.90 | 0.02595455 | 7.5320 | 21.10 | 0.00756896 | 21.10 | 0.00756896 | 40.0265 | 920.85 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT MSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT MSW | M SW APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 16602.940 | 13293.231 | 1.002984 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.5247 | 1004.8586 | 0.9904 | SPLIT MSW SUPPLY FAN | Fan:OnOff | 1.002984 | 0.99336387 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | Sensible | 15235.49 | 15235.49 | 0.9176 | 0.99336387 | 1.002984 | 25.47 | 14.39 | 0.00789945 | 45723.9 | 12.80 | 9.76 | 0.00789945 | 32806.0 | -999.0 | -999.00 | -999.00 | -999.00 | 1123.450 | 14112.04 | 29.84 | 0.00569125 | 14.04 | 0.05190911 | 5.1755 | 24.06 | 0.00801997 | 24.00 | 0.00801997 | 35.5357 | 19337.75 | 0.00 | 16600.11 | 12059.44 | 0.95413351 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.30 | 13.50 | 0.00931878 | 37924.3 | |
| SPLIT MSW HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT MSW | M SW APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 20364.975 | 20364.975 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | SPLIT MSW SUPPLY FAN | Fan:OnOff | 1.002984 | 0.99336387 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | Sensible | 20364.98 | 20364.98 | 1.0000 | 0.99336387 | 1.002984 | 19.60 | 11.64 | 0.00711505 | 37746.5 | 40.00 | 18.92 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 20364.98 | -7.90 | 0.00234317 | -7.90 | 0.05190911 | 5.1755 | 21.10 | 0.00737550 | 21.10 | 0.00737550 | 39.0172 | 5621.89 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT MNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT MNW | M NW APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 16452.976 | 13173.162 | 0.993924 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.4810 | 1004.8586 | 0.9904 | SPLIT MNW SUPPLY FAN | Fan:OnOff | 0.993924 | 0.98439146 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | Sensible | 15090.87 | 15090.87 | 0.9172 | 0.98439146 | 0.993924 | 25.47 | 14.37 | 0.00787593 | 45666.8 | 12.80 | 9.74 | 0.00787593 | 32746.6 | -999.0 | -999.00 | -999.00 | -999.00 | 1113.303 | 13977.57 | 29.84 | 0.00569125 | 14.04 | 0.05190911 | 5.2226 | 24.06 | 0.00799632 | 24.00 | 0.00799632 | 35.4320 | 19166.50 | 0.00 | 16450.18 | 11950.51 | 0.94551544 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.30 | 13.50 | 0.00931878 | 37924.3 | |
| SPLIT MNW HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT MNW | M NW APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 20194.238 | 20194.238 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | SPLIT MNW SUPPLY FAN | Fan:OnOff | 0.993924 | 0.98439146 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | Sensible | 20194.24 | 20194.24 | 1.0000 | 0.98439146 | 0.993924 | 19.58 | 11.77 | 0.00726930 | 38124.3 | 40.00 | 18.92 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 20194.24 | -7.90 | 0.00234317 | -7.90 | 0.05190911 | 5.2226 | 21.10 | 0.00754075 | 21.10 | 0.00754075 | 39.8801 | 5077.58 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT MSE COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT MSE | M SE APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 14886.407 | 11918.880 | 0.899288 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.5116 | 1004.8586 | 0.9904 | SPLIT MSE SUPPLY FAN | Fan:OnOff | 0.899288 | 0.89066270 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | Sensible | 13661.63 | 13661.63 | 0.9177 | 0.89066270 | 0.899288 | 25.50 | 14.39 | 0.00789240 | 45734.9 | 12.80 | 9.75 | 0.00789240 | 32788.2 | -999.0 | -999.00 | -999.00 | -999.00 | 1007.299 | 12654.33 | 29.84 | 0.00569125 | 14.04 | 0.05190911 | 5.7722 | 24.06 | 0.00802724 | 24.00 | 0.00802724 | 35.5676 | 17364.77 | 0.00 | 14883.87 | 10812.64 | 0.85548826 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.30 | 13.50 | 0.00931878 | 37924.3 | |
| SPLIT MSE HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT MSE | M SE APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 18414.382 | 18414.382 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | SPLIT MSE SUPPLY FAN | Fan:OnOff | 0.899288 | 0.89066270 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | Sensible | 18414.38 | 18414.38 | 1.0000 | 0.89066270 | 0.899288 | 19.43 | 11.55 | 0.00708502 | 37494.1 | 40.00 | 18.92 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 18414.38 | -7.90 | 0.00234317 | -7.90 | 0.05190911 | 5.7722 | 21.10 | 0.00737550 | 21.10 | 0.00737550 | 39.0172 | 5621.89 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT MNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT MNE | M NE APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 14743.705 | 11804.625 | 0.890667 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.4497 | 1004.8586 | 0.9904 | SPLIT MNE SUPPLY FAN | Fan:OnOff | 0.890667 | 0.88212475 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | Sensible | 13521.66 | 13521.66 | 0.9171 | 0.88212475 | 0.890667 | 25.50 | 14.37 | 0.00785910 | 45652.9 | 12.80 | 9.72 | 0.00785910 | 32704.1 | -999.0 | -999.00 | -999.00 | -999.00 | 997.643 | 12524.02 | 29.84 | 0.00569125 | 14.04 | 0.05190911 | 5.8281 | 24.06 | 0.00799327 | 24.00 | 0.00799327 | 35.4186 | 17200.68 | 0.00 | 14741.20 | 10708.99 | 0.84728749 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.30 | 13.50 | 0.00931878 | 37924.3 | |
| SPLIT MNE HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT MNE | M NE APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 18251.932 | 18251.932 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | SPLIT MNE SUPPLY FAN | Fan:OnOff | 0.890667 | 0.88212475 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | Sensible | 18251.93 | 18251.93 | 1.0000 | 0.88212475 | 0.890667 | 19.41 | 11.68 | 0.00723783 | 37865.6 | 40.00 | 18.92 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 18251.93 | -7.90 | 0.00234317 | -7.90 | 0.05190911 | 5.8281 | 21.10 | 0.00754075 | 21.10 | 0.00754075 | 39.8801 | 5077.58 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT MN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT MN1 | M N1 APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 13104.728 | 10492.369 | 0.791657 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.4827 | 1004.8586 | 0.9904 | SPLIT MN1 SUPPLY FAN | Fan:OnOff | 0.791657 | 0.78406374 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | Sensible | 12026.54 | 12026.54 | 0.9177 | 0.78406374 | 0.791657 | 25.54 | 14.39 | 0.00787685 | 45733.9 | 12.80 | 9.74 | 0.00787685 | 32748.9 | -999.0 | -999.00 | -999.00 | -999.00 | 886.741 | 11139.80 | 29.84 | 0.00569125 | 14.04 | 0.05190911 | 6.5570 | 24.05 | 0.00803022 | 24.00 | 0.00803022 | 35.5806 | 15320.74 | 0.00 | 13102.50 | 9518.53 | 0.75309915 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.30 | 13.50 | 0.00931878 | 37924.3 | |
| SPLIT MN1 HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT MN1 | M N1 APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 16389.211 | 16389.211 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | SPLIT MN1 SUPPLY FAN | Fan:OnOff | 0.791657 | 0.78406374 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | Sensible | 16389.21 | 16389.21 | 1.0000 | 0.78406374 | 0.791657 | 19.20 | 11.63 | 0.00727245 | 37738.6 | 40.00 | 18.92 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 16389.21 | -7.90 | 0.00234317 | -7.90 | 0.05190911 | 6.5570 | 21.10 | 0.00761834 | 21.10 | 0.00761834 | 40.2845 | 2518.50 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT MN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT MN2 | M N2 APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 13071.140 | 10465.477 | 0.789628 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.4820 | 1004.8586 | 0.9904 | SPLIT MN2 SUPPLY FAN | Fan:OnOff | 0.789628 | 0.78205418 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | Sensible | 11995.72 | 11995.72 | 0.9177 | 0.78205418 | 0.789628 | 25.54 | 14.39 | 0.00787651 | 45733.9 | 12.80 | 9.74 | 0.00787651 | 32748.1 | -999.0 | -999.00 | -999.00 | -999.00 | 884.468 | 11111.25 | 29.83 | 0.00569125 | 14.04 | 0.05190911 | 6.5739 | 24.05 | 0.00803028 | 24.00 | 0.00803028 | 35.5808 | 15282.31 | 0.00 | 13068.92 | 9494.14 | 0.75116895 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.30 | 13.50 | 0.00931878 | 37924.3 | |
| SPLIT MN2 HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT MN2 | M N2 APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 16351.045 | 16351.045 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | SPLIT MN2 SUPPLY FAN | Fan:OnOff | 0.789628 | 0.78205418 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | Sensible | 16351.05 | 16351.05 | 1.0000 | 0.78205418 | 0.789628 | 19.19 | 11.63 | 0.00727156 | 37731.3 | 40.00 | 18.92 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 16351.05 | -7.90 | 0.00234317 | -7.90 | 0.05190911 | 6.5739 | 21.10 | 0.00761834 | 21.10 | 0.00761834 | 40.2845 | 2518.50 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT MS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT MS1 | M S1 APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 13314.987 | 10660.715 | 0.804358 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.5768 | 1004.8586 | 0.9904 | SPLIT MS1 SUPPLY FAN | Fan:OnOff | 0.804358 | 0.79664369 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | Sensible | 12231.74 | 12231.74 | 0.9186 | 0.79664369 | 0.804358 | 25.53 | 14.43 | 0.00792748 | 45857.6 | 12.80 | 9.79 | 0.00792748 | 32876.7 | -999.0 | -999.00 | -999.00 | -999.00 | 900.968 | 11330.78 | 29.83 | 0.00569125 | 14.04 | 0.05190911 | 6.4535 | 24.05 | 0.00808175 | 24.00 | 0.00808175 | 35.8065 | 15561.43 | 0.00 | 13312.72 | 9671.25 | 0.76518229 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.30 | 13.50 | 0.00931878 | 37924.3 | |
| SPLIT MS1 HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT MS1 | M S1 APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 16628.407 | 16628.407 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | SPLIT MS1 SUPPLY FAN | Fan:OnOff | 0.804358 | 0.79664369 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | Sensible | 16628.41 | 16628.41 | 1.0000 | 0.79664369 | 0.804358 | 19.23 | 11.38 | 0.00698280 | 37034.1 | 40.00 | 18.92 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 16628.41 | -7.90 | 0.00234317 | -7.90 | 0.05190911 | 6.4535 | 21.10 | 0.00730287 | 21.10 | 0.00730287 | 38.6366 | 3048.49 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT MS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT MS2 | M S2 APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 13280.229 | 10632.885 | 0.802259 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.5768 | 1004.8586 | 0.9904 | SPLIT MS2 SUPPLY FAN | Fan:OnOff | 0.802259 | 0.79456409 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | Sensible | 12199.91 | 12199.90 | 0.9187 | 0.79456409 | 0.802259 | 25.53 | 14.43 | 0.00792750 | 45858.5 | 12.80 | 9.79 | 0.00792750 | 32876.8 | -999.0 | -999.00 | -999.00 | -999.00 | 898.616 | 11301.29 | 29.84 | 0.00569125 | 14.04 | 0.05190911 | 6.4704 | 24.05 | 0.00808220 | 24.00 | 0.00808220 | 35.8085 | 15521.63 | 0.00 | 13277.97 | 9646.01 | 0.76318481 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.30 | 13.50 | 0.00931878 | 37924.3 | |
| SPLIT MS2 HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT MS2 | M S2 APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 16588.910 | 16588.910 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | SPLIT MS2 SUPPLY FAN | Fan:OnOff | 0.802259 | 0.79456409 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | Sensible | 16588.91 | 16588.91 | 1.0000 | 0.79456409 | 0.802259 | 19.22 | 11.38 | 0.00698196 | 37026.9 | 40.00 | 18.92 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 16588.91 | -7.90 | 0.00234317 | -7.90 | 0.05190911 | 6.4704 | 21.10 | 0.00730287 | 21.10 | 0.00730287 | 38.6366 | 3048.49 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT TSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT TSW | T SW APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 9259.354 | 7413.551 | 0.559358 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.5026 | 1004.8586 | 0.9904 | SPLIT TSW SUPPLY FAN | Fan:OnOff | 0.559358 | 0.55399273 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | Sensible | 8492.73 | 8492.73 | 0.9172 | 0.55399273 | 0.559358 | 25.44 | 14.37 | 0.00788755 | 45666.6 | 12.80 | 9.75 | 0.00788755 | 32775.9 | -999.0 | -999.00 | -999.00 | -999.00 | 626.541 | 7866.19 | 29.84 | 0.00569125 | 14.04 | 0.02595455 | 4.6401 | 24.07 | 0.00799442 | 24.00 | 0.00799442 | 35.4237 | 5384.29 | 0.00 | 9257.78 | 6725.47 | 0.53211420 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.30 | 13.50 | 0.00931878 | 37924.3 | |
| SPLIT TSW HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT TSW | T SW APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 11271.184 | 11271.184 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | SPLIT TSW SUPPLY FAN | Fan:OnOff | 0.559358 | 0.55399273 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | Sensible | 11271.18 | 11271.18 | 1.0000 | 0.55399273 | 0.559358 | 19.75 | 11.85 | 0.00728126 | 38326.0 | 40.00 | 18.92 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 11271.18 | -7.90 | 0.00234317 | -7.90 | 0.02595455 | 4.6401 | 21.10 | 0.00752154 | 21.10 | 0.00752154 | 39.7815 | 2491.21 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT TNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT TNW | T NW APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 9341.720 | 7479.497 | 0.564333 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.4781 | 1004.8586 | 0.9904 | SPLIT TNW SUPPLY FAN | Fan:OnOff | 0.564333 | 0.55892070 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | Sensible | 8565.79 | 8565.79 | 0.9169 | 0.55892070 | 0.564333 | 25.44 | 14.36 | 0.00787439 | 45630.9 | 12.80 | 9.73 | 0.00787439 | 32742.7 | -999.0 | -999.00 | -999.00 | -999.00 | 632.114 | 7933.67 | 29.84 | 0.00569125 | 14.04 | 0.02595455 | 4.5992 | 24.07 | 0.00797963 | 24.00 | 0.00797963 | 35.3589 | 5431.37 | 0.00 | 9340.13 | 6785.30 | 0.53684756 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.30 | 13.50 | 0.00931878 | 37924.3 | |
| SPLIT TNW HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT TNW | T NW APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 11364.593 | 11364.593 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | SPLIT TNW SUPPLY FAN | Fan:OnOff | 0.564333 | 0.55892070 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | Sensible | 11364.59 | 11364.59 | 1.0000 | 0.55892070 | 0.564333 | 19.77 | 11.94 | 0.00737759 | 38582.9 | 40.00 | 18.92 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 11364.59 | -7.90 | 0.00234317 | -7.90 | 0.02595455 | 4.5992 | 21.10 | 0.00762030 | 21.10 | 0.00762030 | 40.2966 | 2349.08 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT TSE COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT TSE | T SE APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 7991.256 | 6398.242 | 0.482752 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.4736 | 1004.8586 | 0.9904 | SPLIT TSE SUPPLY FAN | Fan:OnOff | 0.482752 | 0.47812168 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | Sensible | 7329.69 | 7329.69 | 0.9172 | 0.47812168 | 0.482752 | 25.48 | 14.37 | 0.00787198 | 45666.8 | 12.80 | 9.73 | 0.00787198 | 32736.6 | -999.0 | -999.00 | -999.00 | -999.00 | 540.734 | 6788.96 | 29.84 | 0.00569125 | 14.04 | 0.02595455 | 5.3764 | 24.06 | 0.00799589 | 24.00 | 0.00799589 | 35.4302 | 4658.40 | 0.00 | 7989.90 | 5804.40 | 0.45923949 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.30 | 13.50 | 0.00931878 | 37924.3 | |
| SPLIT TSE HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT TSE | T SE APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 9830.145 | 9830.145 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | SPLIT TSE SUPPLY FAN | Fan:OnOff | 0.482752 | 0.47812168 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | Sensible | 9830.14 | 9830.14 | 1.0000 | 0.47812168 | 0.482752 | 19.54 | 11.73 | 0.00724313 | 38011.8 | 40.00 | 18.92 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9830.14 | -7.90 | 0.00234317 | -7.90 | 0.02595455 | 5.3764 | 21.10 | 0.00752154 | 21.10 | 0.00752154 | 39.7815 | 2491.21 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT TNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT TNE | T NE APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 8070.114 | 6461.379 | 0.487516 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.4390 | 1004.8586 | 0.9904 | SPLIT TNE SUPPLY FAN | Fan:OnOff | 0.487516 | 0.48283977 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | Sensible | 7398.99 | 7398.99 | 0.9168 | 0.48283977 | 0.487516 | 25.48 | 14.35 | 0.00785336 | 45616.5 | 12.80 | 9.71 | 0.00785336 | 32689.6 | -999.0 | -999.00 | -999.00 | -999.00 | 546.070 | 6852.92 | 29.84 | 0.00569125 | 14.04 | 0.02595455 | 5.3238 | 24.06 | 0.00797494 | 24.00 | 0.00797494 | 35.3383 | 4703.43 | 0.00 | 8068.74 | 5861.67 | 0.46377125 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.30 | 13.50 | 0.00931878 | 37924.3 | |
| SPLIT TNE HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT TNE | T NE APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 9919.594 | 9919.594 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | SPLIT TNE SUPPLY FAN | Fan:OnOff | 0.487516 | 0.48283977 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | Sensible | 9919.59 | 9919.59 | 1.0000 | 0.48283977 | 0.487516 | 19.56 | 11.83 | 0.00733935 | 38271.8 | 40.00 | 18.92 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9919.59 | -7.90 | 0.00234317 | -7.90 | 0.02595455 | 5.3238 | 21.10 | 0.00762030 | 21.10 | 0.00762030 | 40.2966 | 2349.08 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT TN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT TN1 | T N1 APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 7484.520 | 5992.520 | 0.452140 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.4866 | 1004.8586 | 0.9904 | SPLIT TN1 SUPPLY FAN | Fan:OnOff | 0.452140 | 0.44780332 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | Sensible | 6867.05 | 6867.05 | 0.9175 | 0.44780332 | 0.452140 | 25.50 | 14.38 | 0.00787897 | 45704.6 | 12.80 | 9.74 | 0.00787897 | 32754.3 | -999.0 | -999.00 | -999.00 | -999.00 | 506.445 | 6360.60 | 29.84 | 0.00569125 | 14.04 | 0.02595455 | 5.7404 | 24.06 | 0.00801221 | 24.00 | 0.00801221 | 35.5017 | 4368.73 | 0.00 | 7483.25 | 5436.33 | 0.43011848 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.30 | 13.50 | 0.00931878 | 37924.3 | |
| SPLIT TN1 HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT TN1 | T N1 APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 9253.918 | 9253.918 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | SPLIT TN1 SUPPLY FAN | Fan:OnOff | 0.452140 | 0.44780332 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | Sensible | 9253.92 | 9253.92 | 1.0000 | 0.44780332 | 0.452140 | 19.43 | 11.86 | 0.00742318 | 38362.0 | 40.00 | 18.92 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9253.92 | -7.90 | 0.00234317 | -7.90 | 0.02595455 | 5.7404 | 21.10 | 0.00773255 | 21.10 | 0.00773255 | 40.8816 | 1593.07 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT TN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT TN2 | T N2 APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 7440.639 | 5957.387 | 0.449489 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.4852 | 1004.8586 | 0.9904 | SPLIT TN2 SUPPLY FAN | Fan:OnOff | 0.449489 | 0.44517791 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | Sensible | 6826.78 | 6826.78 | 0.9175 | 0.44517791 | 0.449489 | 25.50 | 14.38 | 0.00787822 | 45704.5 | 12.80 | 9.74 | 0.00787822 | 32752.4 | -999.0 | -999.00 | -999.00 | -999.00 | 503.476 | 6323.31 | 29.84 | 0.00569125 | 14.04 | 0.02595455 | 5.7742 | 24.06 | 0.00801224 | 24.00 | 0.00801224 | 35.5018 | 4343.56 | 0.00 | 7439.37 | 5404.46 | 0.42759675 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.30 | 13.50 | 0.00931878 | 37924.3 | |
| SPLIT TN2 HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT TN2 | T N2 APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 9204.055 | 9204.055 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | SPLIT TN2 SUPPLY FAN | Fan:OnOff | 0.449489 | 0.44517791 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | Sensible | 9204.05 | 9204.05 | 1.0000 | 0.44517791 | 0.449489 | 19.42 | 11.85 | 0.00742136 | 38347.3 | 40.00 | 18.92 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9204.05 | -7.90 | 0.00234317 | -7.90 | 0.02595455 | 5.7742 | 21.10 | 0.00773255 | 21.10 | 0.00773255 | 40.8816 | 1593.07 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT TS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT TS1 | T S1 APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 7419.869 | 5940.757 | 0.448234 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.5313 | 1004.8586 | 0.9904 | SPLIT TS1 SUPPLY FAN | Fan:OnOff | 0.448234 | 0.44393523 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | Sensible | 6811.27 | 6811.27 | 0.9180 | 0.44393523 | 0.448234 | 25.51 | 14.40 | 0.00790299 | 45768.6 | 12.80 | 9.76 | 0.00790299 | 32814.9 | -999.0 | -999.00 | -999.00 | -999.00 | 502.071 | 6309.20 | 29.84 | 0.00569125 | 14.04 | 0.02595455 | 5.7904 | 24.06 | 0.00803893 | 24.00 | 0.00803893 | 35.6189 | 4331.83 | 0.00 | 7418.61 | 5389.37 | 0.42640315 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.30 | 13.50 | 0.00931878 | 37924.3 | |
| SPLIT TS1 HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT TS1 | T S1 APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 9180.610 | 9180.610 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | SPLIT TS1 SUPPLY FAN | Fan:OnOff | 0.448234 | 0.44393523 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | Sensible | 9180.61 | 9180.61 | 1.0000 | 0.44393523 | 0.448234 | 19.42 | 11.72 | 0.00727721 | 37976.5 | 40.00 | 18.92 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9180.61 | -7.90 | 0.00234317 | -7.90 | 0.02595455 | 5.7904 | 21.10 | 0.00758048 | 21.10 | 0.00758048 | 40.0881 | 1735.30 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT TS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT TS2 | T S2 APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 7376.180 | 5905.778 | 0.445595 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.5305 | 1004.8586 | 0.9904 | SPLIT TS2 SUPPLY FAN | Fan:OnOff | 0.445595 | 0.44132131 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | Sensible | 6771.20 | 6771.20 | 0.9180 | 0.44132131 | 0.445595 | 25.51 | 14.40 | 0.00790258 | 45769.2 | 12.80 | 9.76 | 0.00790258 | 32813.9 | -999.0 | -999.00 | -999.00 | -999.00 | 499.115 | 6272.09 | 29.84 | 0.00569125 | 14.04 | 0.02595455 | 5.8247 | 24.06 | 0.00803935 | 24.00 | 0.00803935 | 35.6207 | 4306.70 | 0.00 | 7374.93 | 5357.64 | 0.42389246 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.30 | 13.50 | 0.00931878 | 37924.3 | |
| SPLIT TS2 HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT TS2 | T S2 APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 9130.965 | 9130.965 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | SPLIT TS2 SUPPLY FAN | Fan:OnOff | 0.445595 | 0.44132131 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | Sensible | 9130.96 | 9130.96 | 1.0000 | 0.44132131 | 0.445595 | 19.41 | 11.72 | 0.00727542 | 37961.8 | 40.00 | 18.92 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9130.96 | -7.90 | 0.00234317 | -7.90 | 0.02595455 | 5.8247 | 21.10 | 0.00758048 | 21.10 | 0.00758048 | 40.0881 | 1735.30 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 09:14:27
Economizer| High Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
| None |
| Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
| None |
| Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
| G SW APARTMENT | 1902.83 | 3767.50 | 509.67 |
| G NW APARTMENT | 4597.17 | 5586.00 | 2791.00 |
| OFFICE | 829.50 | 746.33 | 68.83 |
| G NE APARTMENT | 4629.17 | 5503.17 | 2731.17 |
| G N1 APARTMENT | 3933.83 | 5604.50 | 2444.33 |
| G N2 APARTMENT | 3938.50 | 5592.33 | 2441.50 |
| G S1 APARTMENT | 1377.17 | 3695.17 | 124.17 |
| G S2 APARTMENT | 1575.50 | 3577.17 | 125.00 |
| M SW APARTMENT | 1482.83 | 3531.83 | 167.17 |
| M NW APARTMENT | 3349.00 | 5323.33 | 1557.50 |
| M SE APARTMENT | 1497.50 | 3547.67 | 165.00 |
| M NE APARTMENT | 3476.83 | 5284.67 | 1579.33 |
| M N1 APARTMENT | 2407.00 | 5464.83 | 1035.00 |
| M N2 APARTMENT | 2420.33 | 5462.50 | 1040.67 |
| M S1 APARTMENT | 1139.00 | 3576.83 | 32.33 |
| M S2 APARTMENT | 1139.83 | 3573.67 | 31.33 |
| T SW APARTMENT | 2845.50 | 3889.17 | 1630.00 |
| T NW APARTMENT | 4879.50 | 5701.00 | 2951.00 |
| T SE APARTMENT | 2838.17 | 3885.83 | 1620.83 |
| T NE APARTMENT | 4934.50 | 5612.17 | 2923.33 |
| T N1 APARTMENT | 4591.33 | 5715.33 | 2834.50 |
| T N2 APARTMENT | 4595.17 | 5710.33 | 2833.83 |
| T S1 APARTMENT | 2339.50 | 3855.00 | 1219.67 |
| T S2 APARTMENT | 2342.83 | 3851.83 | 1222.67 |
| T CORRIDOR | 7305.17 | 8574.67 | 7181.50 |
| G CORRIDOR | 5506.33 | 6126.67 | 3296.00 |
| M CORRIDOR | 8668.83 | 8742.17 | 8658.17 |
| Facility | 8759.83 | 8760.00 | 8750.33 |
| During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
| G SW APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| G NW APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| OFFICE | 0.00 | 0.00 | 0.00 | 0.00 |
| G NE APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| G N1 APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| G N2 APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| G S1 APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| G S2 APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| M SW APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| M NW APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| M SE APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| M NE APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| M N1 APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| M N2 APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| M S1 APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| M S2 APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| T SW APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| T NW APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| T SE APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| T NE APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| T N1 APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| T N2 APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| T S1 APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| T S2 APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| T CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
| G CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
| M CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
| Facility | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 09:14:27
Average Outdoor Air During Occupied Hours| Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
| G SW APARTMENT | 2.40 | 2.50 | 268.97 | 0.351 | 0.094 | 0.000 | 0.051 |
| G NW APARTMENT | 1.71 | 2.50 | 268.97 | 0.351 | 0.097 | 0.000 | 0.061 |
| OFFICE | 4.75 | 4.75 | 268.97 | 0.517 | 0.099 | 0.000 | 0.000 |
| G NE APARTMENT | 1.71 | 2.50 | 268.97 | 0.351 | 0.097 | 0.000 | 0.061 |
| G N1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.351 | 0.058 | 0.000 | 0.061 |
| G N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.351 | 0.058 | 0.000 | 0.061 |
| G S1 APARTMENT | 2.40 | 2.50 | 268.97 | 0.352 | 0.057 | 0.000 | 0.051 |
| G S2 APARTMENT | 2.40 | 2.50 | 268.97 | 0.352 | 0.057 | 0.000 | 0.051 |
| M SW APARTMENT | 2.40 | 2.50 | 268.97 | 0.352 | 0.135 | 0.000 | 0.063 |
| M NW APARTMENT | 1.71 | 2.50 | 268.97 | 0.351 | 0.139 | 0.000 | 0.075 |
| M SE APARTMENT | 2.40 | 2.50 | 268.97 | 0.352 | 0.135 | 0.000 | 0.063 |
| M NE APARTMENT | 1.71 | 2.50 | 268.97 | 0.351 | 0.139 | 0.000 | 0.075 |
| M N1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.351 | 0.084 | 0.000 | 0.075 |
| M N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.351 | 0.084 | 0.000 | 0.075 |
| M S1 APARTMENT | 2.40 | 2.50 | 268.97 | 0.352 | 0.082 | 0.000 | 0.063 |
| M S2 APARTMENT | 2.40 | 2.50 | 268.97 | 0.352 | 0.082 | 0.000 | 0.063 |
| T SW APARTMENT | 2.40 | 2.50 | 268.97 | 0.351 | 0.179 | 0.000 | 0.073 |
| T NW APARTMENT | 1.71 | 2.50 | 268.97 | 0.351 | 0.183 | 0.000 | 0.088 |
| T SE APARTMENT | 2.40 | 2.50 | 268.97 | 0.351 | 0.179 | 0.000 | 0.073 |
| T NE APARTMENT | 1.71 | 2.50 | 268.97 | 0.351 | 0.183 | 0.000 | 0.089 |
| T N1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.351 | 0.111 | 0.000 | 0.088 |
| T N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.351 | 0.111 | 0.000 | 0.088 |
| T S1 APARTMENT | 2.40 | 2.50 | 268.97 | 0.351 | 0.108 | 0.000 | 0.073 |
| T S2 APARTMENT | 2.40 | 2.50 | 268.97 | 0.351 | 0.108 | 0.000 | 0.073 |
| Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
| G SW APARTMENT | 2.40 | 2.50 | 268.97 | 0.342 | 0.000 | 0.000 | 0.000 |
| G NW APARTMENT | 1.71 | 2.50 | 268.97 | 0.341 | 0.000 | 0.000 | 0.000 |
| OFFICE | 4.75 | 4.75 | 268.97 | 0.500 | 0.000 | 0.000 | 0.000 |
| G NE APARTMENT | 1.71 | 2.50 | 268.97 | 0.341 | 0.000 | 0.000 | 0.000 |
| G N1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.341 | 0.000 | 0.000 | 0.000 |
| G N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.341 | 0.000 | 0.000 | 0.000 |
| G S1 APARTMENT | 2.40 | 2.50 | 268.97 | 0.342 | 0.000 | 0.000 | 0.000 |
| G S2 APARTMENT | 2.40 | 2.50 | 268.97 | 0.342 | 0.000 | 0.000 | 0.000 |
| M SW APARTMENT | 2.40 | 2.50 | 268.97 | 0.342 | 0.000 | 0.000 | 0.000 |
| M NW APARTMENT | 1.71 | 2.50 | 268.97 | 0.341 | 0.000 | 0.000 | 0.000 |
| M SE APARTMENT | 2.40 | 2.50 | 268.97 | 0.342 | 0.000 | 0.000 | 0.000 |
| M NE APARTMENT | 1.71 | 2.50 | 268.97 | 0.341 | 0.000 | 0.000 | 0.000 |
| M N1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.341 | 0.000 | 0.000 | 0.000 |
| M N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.341 | 0.000 | 0.000 | 0.000 |
| M S1 APARTMENT | 2.40 | 2.50 | 268.97 | 0.342 | 0.000 | 0.000 | 0.000 |
| M S2 APARTMENT | 2.40 | 2.50 | 268.97 | 0.342 | 0.000 | 0.000 | 0.000 |
| T SW APARTMENT | 2.40 | 2.50 | 268.97 | 0.342 | 0.000 | 0.000 | 0.000 |
| T NW APARTMENT | 1.71 | 2.50 | 268.97 | 0.341 | 0.000 | 0.000 | 0.000 |
| T SE APARTMENT | 2.40 | 2.50 | 268.97 | 0.342 | 0.000 | 0.000 | 0.000 |
| T NE APARTMENT | 1.71 | 2.50 | 268.97 | 0.341 | 0.000 | 0.000 | 0.000 |
| T N1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.341 | 0.000 | 0.000 | 0.000 |
| T N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.341 | 0.000 | 0.000 | 0.000 |
| T S1 APARTMENT | 2.40 | 2.50 | 268.97 | 0.342 | 0.000 | 0.000 | 0.000 |
| T S2 APARTMENT | 2.40 | 2.50 | 268.97 | 0.342 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 09:14:27
Mechanical Ventilation Parameters by Zone| AirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
| G SW APARTMENT | SPLIT GSW | 2.40 | 2.50 | 268.97 | 88.25 | 0.0260 | 0.026 |
| G NW APARTMENT | SPLIT GNW | 1.71 | 2.50 | 268.97 | 88.25 | 0.0260 | 0.026 |
| OFFICE | SPLIT OFFICE | 4.75 | 4.75 | 268.97 | 88.25 | 0.0381 | 0.038 |
| G NE APARTMENT | SPLIT GNE | 1.71 | 2.50 | 268.97 | 88.25 | 0.0260 | 0.026 |
| G N1 APARTMENT | SPLIT GN1 | 1.71 | 2.50 | 268.97 | 88.25 | 0.0260 | 0.026 |
| G N2 APARTMENT | SPLIT GN2 | 1.71 | 2.50 | 268.97 | 88.25 | 0.0260 | 0.026 |
| G S1 APARTMENT | SPLIT GS1 | 2.40 | 2.50 | 268.97 | 88.25 | 0.0260 | 0.026 |
| G S2 APARTMENT | SPLIT GS2 | 2.40 | 2.50 | 268.97 | 88.25 | 0.0260 | 0.026 |
| M SW APARTMENT | SPLIT MSW | 2.40 | 2.50 | 268.97 | 88.25 | 0.0519 | 0.052 |
| M NW APARTMENT | SPLIT MNW | 1.71 | 2.50 | 268.97 | 88.25 | 0.0519 | 0.052 |
| M SE APARTMENT | SPLIT MSE | 2.40 | 2.50 | 268.97 | 88.25 | 0.0519 | 0.052 |
| M NE APARTMENT | SPLIT MNE | 1.71 | 2.50 | 268.97 | 88.25 | 0.0519 | 0.052 |
| M N1 APARTMENT | SPLIT MN1 | 1.71 | 2.50 | 268.97 | 88.25 | 0.0519 | 0.052 |
| M N2 APARTMENT | SPLIT MN2 | 1.71 | 2.50 | 268.97 | 88.25 | 0.0519 | 0.052 |
| M S1 APARTMENT | SPLIT MS1 | 2.40 | 2.50 | 268.97 | 88.25 | 0.0519 | 0.052 |
| M S2 APARTMENT | SPLIT MS2 | 2.40 | 2.50 | 268.97 | 88.25 | 0.0519 | 0.052 |
| T SW APARTMENT | SPLIT TSW | 2.40 | 2.50 | 268.97 | 88.25 | 0.0260 | 0.026 |
| T NW APARTMENT | SPLIT TNW | 1.71 | 2.50 | 268.97 | 88.25 | 0.0260 | 0.026 |
| T SE APARTMENT | SPLIT TSE | 2.40 | 2.50 | 268.97 | 88.25 | 0.0260 | 0.026 |
| T NE APARTMENT | SPLIT TNE | 1.71 | 2.50 | 268.97 | 88.25 | 0.0260 | 0.026 |
| T N1 APARTMENT | SPLIT TN1 | 1.71 | 2.50 | 268.97 | 88.25 | 0.0260 | 0.026 |
| T N2 APARTMENT | SPLIT TN2 | 1.71 | 2.50 | 268.97 | 88.25 | 0.0260 | 0.026 |
| T S1 APARTMENT | SPLIT TS1 | 2.40 | 2.50 | 268.97 | 88.25 | 0.0260 | 0.026 |
| T S2 APARTMENT | SPLIT TS2 | 2.40 | 2.50 | 268.97 | 88.25 | 0.0260 | 0.026 |
| Total Facility | 68.19 | 82.25 | 8607.06 | 2823.98 | 0.8427 | 1.258 |
| Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
| G SW APARTMENT | 818502.78 | 146917.16 | 965419.94 | 224889.49 | 1190309.43 | 818502.78 | 0.00 | 7279.00 | 1481.00 | 2615.00 |
| G NW APARTMENT | 818502.78 | 140783.82 | 959286.60 | 224889.49 | 1184176.08 | 818502.78 | 0.00 | 7279.00 | 1481.00 | 0.00 |
| OFFICE | 1201711.97 | 0.00 | 1201711.97 | 224889.49 | 1426601.46 | 1201711.97 | 0.00 | 8760.00 | 0.00 | 7010.00 |
| G NE APARTMENT | 818502.78 | 141201.37 | 959704.15 | 224889.49 | 1184593.63 | 818502.78 | 0.00 | 7279.00 | 1481.00 | 0.00 |
| G N1 APARTMENT | 818502.78 | 140744.26 | 959247.04 | 135647.63 | 1094894.67 | 818502.78 | 0.00 | 7279.00 | 1481.00 | 0.00 |
| G N2 APARTMENT | 818502.78 | 140796.66 | 959299.44 | 135647.63 | 1094947.07 | 818502.78 | 0.00 | 7279.00 | 1481.00 | 0.00 |
| G S1 APARTMENT | 818502.78 | 147242.56 | 965745.34 | 135647.63 | 1101392.97 | 818502.78 | 0.00 | 7279.00 | 1481.00 | 2615.00 |
| G S2 APARTMENT | 818502.78 | 147342.68 | 965845.45 | 135647.63 | 1101493.08 | 818502.78 | 0.00 | 7279.00 | 1481.00 | 2615.00 |
| M SW APARTMENT | 1637005.55 | 181130.40 | 1818135.95 | 323183.46 | 2141319.41 | 1637005.55 | 0.00 | 7251.83 | 1508.17 | 2615.00 |
| M NW APARTMENT | 1637005.55 | 174827.71 | 1811833.26 | 323183.46 | 2135016.72 | 1637005.55 | 0.00 | 7251.83 | 1508.17 | 0.00 |
| M SE APARTMENT | 1637005.55 | 181149.99 | 1818155.55 | 323183.46 | 2141339.01 | 1637005.55 | 0.00 | 7251.83 | 1508.17 | 2615.00 |
| M NE APARTMENT | 1637005.55 | 174969.84 | 1811975.39 | 323183.46 | 2135158.85 | 1637005.55 | 0.00 | 7251.83 | 1508.17 | 0.00 |
| M N1 APARTMENT | 1637005.55 | 174685.37 | 1811690.93 | 194936.06 | 2006626.98 | 1637005.55 | 0.00 | 7251.83 | 1508.17 | 0.00 |
| M N2 APARTMENT | 1637005.55 | 174717.82 | 1811723.38 | 194936.06 | 2006659.44 | 1637005.55 | 0.00 | 7251.83 | 1508.17 | 0.00 |
| M S1 APARTMENT | 1637005.55 | 181162.20 | 1818167.75 | 194936.06 | 2013103.81 | 1637005.55 | 0.00 | 7251.83 | 1508.17 | 2615.00 |
| M S2 APARTMENT | 1637005.55 | 181162.84 | 1818168.40 | 194936.06 | 2013104.46 | 1637005.55 | 0.00 | 7251.83 | 1508.17 | 2615.00 |
| T SW APARTMENT | 818502.78 | 212827.51 | 1031330.29 | 427505.17 | 1458835.46 | 818502.78 | 0.00 | 7278.00 | 1482.00 | 2615.00 |
| T NW APARTMENT | 818502.78 | 204515.16 | 1023017.94 | 427505.17 | 1450523.12 | 818502.78 | 0.00 | 7278.00 | 1482.00 | 0.00 |
| T SE APARTMENT | 818502.78 | 213214.99 | 1031717.76 | 427505.17 | 1459222.94 | 818502.78 | 0.00 | 7278.00 | 1482.00 | 2615.00 |
| T NE APARTMENT | 818502.78 | 205369.04 | 1023871.82 | 427505.17 | 1451377.00 | 818502.78 | 0.00 | 7278.00 | 1482.00 | 0.00 |
| T N1 APARTMENT | 818502.78 | 204640.55 | 1023143.33 | 257860.27 | 1281003.60 | 818502.78 | 0.00 | 7278.00 | 1482.00 | 0.00 |
| T N2 APARTMENT | 818502.78 | 204737.74 | 1023240.52 | 257860.27 | 1281100.79 | 818502.78 | 0.00 | 7278.00 | 1482.00 | 0.00 |
| T S1 APARTMENT | 818502.78 | 213161.61 | 1031664.38 | 257860.27 | 1289524.65 | 818502.78 | 0.00 | 7278.00 | 1482.00 | 2615.00 |
| T S2 APARTMENT | 818502.78 | 213183.92 | 1031686.70 | 257860.27 | 1289546.96 | 818502.78 | 0.00 | 7278.00 | 1482.00 | 2615.00 |
| Total Facility | 39671342.50 | 5524291.37 | 45195633.87 | 8328566.38 | 53524200.26 | 39671342.50 | 0.00 | 8760.00 | 1511.50 | 8760.00 |
| Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
| G SW APARTMENT | 0.0260 | 0.0037 | 0.0297 | 0.0069 | 0.0366 | 0.0260 | 0.00 | 5302.00 | 843.00 |
| G NW APARTMENT | 0.0260 | 0.0045 | 0.0304 | 0.0071 | 0.0375 | 0.0260 | 0.00 | 7279.00 | 1481.00 |
| OFFICE | 0.0381 | 0.0000 | 0.0381 | 0.0073 | 0.0454 | 0.0381 | 0.00 | 1750.00 | 0.00 |
| G NE APARTMENT | 0.0260 | 0.0045 | 0.0304 | 0.0071 | 0.0376 | 0.0260 | 0.00 | 7279.00 | 1481.00 |
| G N1 APARTMENT | 0.0260 | 0.0045 | 0.0304 | 0.0043 | 0.0347 | 0.0260 | 0.00 | 7279.00 | 1481.00 |
| G N2 APARTMENT | 0.0260 | 0.0045 | 0.0304 | 0.0043 | 0.0347 | 0.0260 | 0.00 | 7279.00 | 1481.00 |
| G S1 APARTMENT | 0.0260 | 0.0038 | 0.0297 | 0.0042 | 0.0339 | 0.0260 | 0.00 | 5302.00 | 843.00 |
| G S2 APARTMENT | 0.0260 | 0.0038 | 0.0297 | 0.0042 | 0.0339 | 0.0260 | 0.00 | 5302.00 | 843.00 |
| M SW APARTMENT | 0.0519 | 0.0046 | 0.0565 | 0.0100 | 0.0665 | 0.0519 | 0.00 | 5285.83 | 859.17 |
| M NW APARTMENT | 0.0519 | 0.0055 | 0.0575 | 0.0102 | 0.0677 | 0.0519 | 0.00 | 7251.83 | 1508.17 |
| M SE APARTMENT | 0.0519 | 0.0046 | 0.0565 | 0.0100 | 0.0665 | 0.0519 | 0.00 | 5285.83 | 859.17 |
| M NE APARTMENT | 0.0519 | 0.0055 | 0.0575 | 0.0102 | 0.0677 | 0.0519 | 0.00 | 7251.83 | 1508.17 |
| M N1 APARTMENT | 0.0519 | 0.0055 | 0.0574 | 0.0062 | 0.0636 | 0.0519 | 0.00 | 7251.83 | 1508.17 |
| M N2 APARTMENT | 0.0519 | 0.0055 | 0.0574 | 0.0062 | 0.0636 | 0.0519 | 0.00 | 7251.83 | 1508.17 |
| M S1 APARTMENT | 0.0519 | 0.0046 | 0.0565 | 0.0060 | 0.0625 | 0.0519 | 0.00 | 5285.83 | 859.17 |
| M S2 APARTMENT | 0.0519 | 0.0046 | 0.0565 | 0.0060 | 0.0625 | 0.0519 | 0.00 | 5285.83 | 859.17 |
| T SW APARTMENT | 0.0260 | 0.0054 | 0.0313 | 0.0132 | 0.0445 | 0.0260 | 0.00 | 5300.50 | 844.50 |
| T NW APARTMENT | 0.0260 | 0.0065 | 0.0324 | 0.0136 | 0.0460 | 0.0260 | 0.00 | 7278.00 | 1482.00 |
| T SE APARTMENT | 0.0260 | 0.0054 | 0.0313 | 0.0132 | 0.0445 | 0.0260 | 0.00 | 5300.50 | 844.50 |
| T NE APARTMENT | 0.0260 | 0.0065 | 0.0325 | 0.0136 | 0.0460 | 0.0260 | 0.00 | 7278.00 | 1482.00 |
| T N1 APARTMENT | 0.0260 | 0.0065 | 0.0324 | 0.0082 | 0.0406 | 0.0260 | 0.00 | 7278.00 | 1482.00 |
| T N2 APARTMENT | 0.0260 | 0.0065 | 0.0324 | 0.0082 | 0.0406 | 0.0260 | 0.00 | 7278.00 | 1482.00 |
| T S1 APARTMENT | 0.0260 | 0.0054 | 0.0313 | 0.0080 | 0.0393 | 0.0260 | 0.00 | 5300.50 | 844.50 |
| T S2 APARTMENT | 0.0260 | 0.0054 | 0.0313 | 0.0080 | 0.0393 | 0.0260 | 0.00 | 5300.50 | 844.50 |
| Total Facility | 1.2580 | 0.1578 | 1.4158 | 0.2609 | 1.6767 | 1.2580 | 0.00 | 8760.00 | 1511.50 |
| Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
| SPLIT GSW | 0.00 | 146917.16 | 146917.16 | 818502.78 | 7959.33 | 38.17 | 762.50 | 638.00 |
| SPLIT GNW | 0.00 | 140783.82 | 140783.82 | 818502.78 | 8027.33 | 41.58 | 691.08 | 0.00 |
| SPLIT OFFICE | 1178771.02 | 0.00 | 1178771.02 | 1201711.97 | 8760.00 | 0.00 | 0.00 | 7010.00 |
| SPLIT GNE | 0.00 | 141201.37 | 141201.37 | 818502.78 | 8021.50 | 38.48 | 700.02 | 0.00 |
| SPLIT GN1 | 0.00 | 140744.26 | 140744.26 | 818502.78 | 8029.33 | 40.00 | 690.67 | 0.00 |
| SPLIT GN2 | 0.00 | 140796.66 | 140796.66 | 818502.78 | 8028.17 | 40.00 | 691.83 | 0.00 |
| SPLIT GS1 | 0.00 | 147242.56 | 147242.56 | 818502.78 | 7953.83 | 38.00 | 768.17 | 638.00 |
| SPLIT GS2 | 0.00 | 147342.68 | 147342.68 | 818502.78 | 7953.67 | 37.00 | 769.33 | 638.00 |
| SPLIT MSW | 0.00 | 181130.40 | 181130.40 | 1637005.55 | 8591.50 | 7.00 | 161.50 | 649.00 |
| SPLIT MNW | 0.00 | 174827.71 | 174827.71 | 1637005.55 | 8619.50 | 9.83 | 130.67 | 0.00 |
| SPLIT MSE | 0.00 | 181149.99 | 181149.99 | 1637005.55 | 8591.33 | 7.00 | 161.67 | 649.00 |
| SPLIT MNE | 0.00 | 174969.84 | 174969.84 | 1637005.55 | 8618.67 | 10.00 | 131.33 | 0.00 |
| SPLIT MN1 | 0.00 | 174685.37 | 174685.37 | 1637005.55 | 8619.33 | 9.33 | 131.33 | 0.00 |
| SPLIT MN2 | 0.00 | 174717.82 | 174717.82 | 1637005.55 | 8619.33 | 9.33 | 131.33 | 0.00 |
| SPLIT MS1 | 0.00 | 181162.20 | 181162.20 | 1637005.55 | 8591.33 | 7.17 | 161.50 | 649.00 |
| SPLIT MS2 | 0.00 | 181162.84 | 181162.84 | 1637005.55 | 8591.33 | 7.17 | 161.50 | 649.00 |
| SPLIT TSW | 0.00 | 212827.51 | 212827.51 | 818502.78 | 7599.96 | 24.54 | 1135.50 | 637.50 |
| SPLIT TNW | 0.00 | 204515.16 | 204515.16 | 818502.78 | 7637.73 | 28.48 | 1093.79 | 0.00 |
| SPLIT TSE | 0.00 | 213214.99 | 213214.99 | 818502.78 | 7596.60 | 24.90 | 1138.50 | 637.50 |
| SPLIT TNE | 0.00 | 205369.04 | 205369.04 | 818502.78 | 7624.55 | 28.79 | 1106.67 | 0.00 |
| SPLIT TN1 | 0.00 | 204640.55 | 204640.55 | 818502.78 | 7633.93 | 28.61 | 1097.46 | 0.00 |
| SPLIT TN2 | 0.00 | 204737.74 | 204737.74 | 818502.78 | 7632.35 | 28.65 | 1099.00 | 0.00 |
| SPLIT TS1 | 0.00 | 213161.61 | 213161.61 | 818502.78 | 7597.08 | 24.75 | 1138.17 | 637.50 |
| SPLIT TS2 | 0.00 | 213183.92 | 213183.92 | 818502.78 | 7597.08 | 24.58 | 1138.33 | 637.50 |
| Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
| SPLIT GSW | 0.0000 | 0.0037 | 0.0037 | 0.0260 | 5687.50 | 22.17 | 435.33 |
| SPLIT GNW | 0.0000 | 0.0045 | 0.0045 | 0.0260 | 8027.33 | 41.58 | 691.08 |
| SPLIT OFFICE | 0.0374 | 0.0000 | 0.0374 | 0.0381 | 1750.00 | 0.00 | 0.00 |
| SPLIT GNE | 0.0000 | 0.0045 | 0.0045 | 0.0260 | 8021.50 | 38.48 | 700.02 |
| SPLIT GN1 | 0.0000 | 0.0045 | 0.0045 | 0.0260 | 8029.33 | 40.00 | 690.67 |
| SPLIT GN2 | 0.0000 | 0.0045 | 0.0045 | 0.0260 | 8028.17 | 40.00 | 691.83 |
| SPLIT GS1 | 0.0000 | 0.0038 | 0.0038 | 0.0260 | 5685.83 | 22.50 | 436.67 |
| SPLIT GS2 | 0.0000 | 0.0038 | 0.0038 | 0.0260 | 5685.83 | 22.33 | 436.83 |
| SPLIT MSW | 0.0000 | 0.0046 | 0.0046 | 0.0519 | 6067.50 | 3.83 | 73.67 |
| SPLIT MNW | 0.0000 | 0.0055 | 0.0055 | 0.0519 | 8619.50 | 9.83 | 130.67 |
| SPLIT MSE | 0.0000 | 0.0046 | 0.0046 | 0.0519 | 6067.33 | 4.00 | 73.67 |
| SPLIT MNE | 0.0000 | 0.0055 | 0.0055 | 0.0519 | 8618.67 | 10.00 | 131.33 |
| SPLIT MN1 | 0.0000 | 0.0055 | 0.0055 | 0.0519 | 8619.33 | 9.33 | 131.33 |
| SPLIT MN2 | 0.0000 | 0.0055 | 0.0055 | 0.0519 | 8619.33 | 9.33 | 131.33 |
| SPLIT MS1 | 0.0000 | 0.0046 | 0.0046 | 0.0519 | 6067.33 | 4.00 | 73.67 |
| SPLIT MS2 | 0.0000 | 0.0046 | 0.0046 | 0.0519 | 6067.33 | 4.00 | 73.67 |
| SPLIT TSW | 0.0000 | 0.0054 | 0.0054 | 0.0260 | 5468.00 | 13.50 | 663.50 |
| SPLIT TNW | 0.0000 | 0.0065 | 0.0065 | 0.0260 | 7637.73 | 28.48 | 1093.79 |
| SPLIT TSE | 0.0000 | 0.0054 | 0.0054 | 0.0260 | 5466.43 | 13.74 | 664.83 |
| SPLIT TNE | 0.0000 | 0.0065 | 0.0065 | 0.0260 | 7624.55 | 28.79 | 1106.67 |
| SPLIT TN1 | 0.0000 | 0.0065 | 0.0065 | 0.0260 | 7633.93 | 28.61 | 1097.46 |
| SPLIT TN2 | 0.0000 | 0.0065 | 0.0065 | 0.0260 | 7632.35 | 28.65 | 1099.00 |
| SPLIT TS1 | 0.0000 | 0.0054 | 0.0054 | 0.0260 | 5467.00 | 12.83 | 665.17 |
| SPLIT TS2 | 0.0000 | 0.0054 | 0.0054 | 0.0260 | 5467.00 | 12.83 | 665.17 |
| No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
| SPLIT GSW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT GNW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT OFFICE | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT GNE | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT GN1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT GN2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT GS1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT GS2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT MSW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT MNW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT MSE | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT MNE | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT MN1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT MN2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT MS1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT MS2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT TSW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT TNW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT TSE | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT TNE | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT TN1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT TN2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT TS1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT TS2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
| SPLIT GSW | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT GNW | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT OFFICE | 0.0374 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT GNE | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT GN1 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT GN2 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT GS1 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT GS2 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT MSW | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT MNW | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT MSE | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT MNE | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT MN1 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT MN2 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT MS1 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT MS2 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT TSW | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT TNW | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT TSE | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT TNE | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT TN1 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT TN2 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT TS1 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT TS2 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 09:14:27
Surfaces by Class| Total | Outdoors | |
| Wall | 126 | 42 |
| Floor | 27 | 9 |
| Roof | 27 | 9 |
| Internal Mass | 24 | 0 |
| Building Detached Shading | 0 | 0 |
| Fixed Detached Shading | 0 | 0 |
| Window | 39 | 39 |
| Door | 0 | 0 |
| Glass Door | 0 | 0 |
| Shading | 0 | 0 |
| Overhang | 0 | 0 |
| Fin | 0 | 0 |
| Tubular Daylighting Device Dome | 0 | 0 |
| Tubular Daylighting Device Diffuser | 0 | 0 |
| Count | |
| HVAC Air Loops | 24 |
| Conditioned Zones | 24 |
| Unconditioned Zones | 3 |
| Supply Plenums | 0 |
| Return Plenums | 0 |
| Count | |
| IDF Objects | 1536 |
| Defaulted Fields | 1816 |
| Fields with Defaults | 5921 |
| Autosized Fields | 617 |
| Autosizable Fields | 759 |
| Autocalculated Fields | 331 |
| Autocalculatable Fields | 508 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 09:14:27
Annual and Peak Values - Electricity| Electricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
| Electricity:Facility | 1308.91 | 17020.55 | 18-APR-02:30 | 90289.92 | 20-AUG-17:10 |
| Electricity:Building | 557.89 | 10119.94 | 01-JAN-03:10 | 27841.36 | 01-JAN-18:10 |
| Electricity:Zone:G SW APARTMENT | 13.67 | 232.36 | 01-JAN-03:10 | 705.80 | 01-JAN-18:10 |
| Electricity:SpaceType:GENERAL | 557.89 | 10119.94 | 01-JAN-03:10 | 27841.36 | 01-JAN-18:10 |
| InteriorLights:Electricity | 99.23 | 1868.27 | 01-JAN-00:10 | 5904.43 | 01-JAN-19:10 |
| InteriorLights:Electricity:Zone:G SW APARTMENT | 1.45 | 8.68 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 |
| InteriorLights:Electricity:SpaceType:GENERAL | 99.23 | 1868.27 | 01-JAN-00:10 | 5904.43 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity | 94.96 | 1842.77 | 01-JAN-00:10 | 5496.56 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:G SW APARTMENT | 1.32 | 7.86 | 01-JAN-00:10 | 125.72 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 94.96 | 1842.77 | 01-JAN-00:10 | 5496.56 | 01-JAN-19:10 |
| Electricity:Zone:G NW APARTMENT | 13.67 | 232.36 | 01-JAN-03:10 | 705.80 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:G NW APARTMENT | 1.45 | 8.68 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:G NW APARTMENT | 1.32 | 7.86 | 01-JAN-00:10 | 125.72 | 01-JAN-19:10 |
| Electricity:Zone:OFFICE | 16.86 | 310.83 | 01-JAN-00:10 | 1171.54 | 03-JAN-08:10 |
| InteriorLights:Electricity:Zone:OFFICE | 7.40 | 116.58 | 01-JAN-00:10 | 582.92 | 03-JAN-08:10 |
| LightsWired:InteriorLights:Electricity:Zone:OFFICE | 7.40 | 116.58 | 01-JAN-00:10 | 582.92 | 03-JAN-08:10 |
| Electricity:Zone:G NE APARTMENT | 13.67 | 232.36 | 01-JAN-03:10 | 705.80 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:G NE APARTMENT | 1.45 | 8.68 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:G NE APARTMENT | 1.32 | 7.86 | 01-JAN-00:10 | 125.72 | 01-JAN-19:10 |
| Electricity:Zone:G N1 APARTMENT | 13.67 | 232.36 | 01-JAN-03:10 | 705.80 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:G N1 APARTMENT | 1.45 | 8.68 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:G N1 APARTMENT | 1.32 | 7.86 | 01-JAN-00:10 | 125.72 | 01-JAN-19:10 |
| Electricity:Zone:G N2 APARTMENT | 13.67 | 232.36 | 01-JAN-03:10 | 705.80 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:G N2 APARTMENT | 1.45 | 8.68 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:G N2 APARTMENT | 1.32 | 7.86 | 01-JAN-00:10 | 125.72 | 01-JAN-19:10 |
| Electricity:Zone:G S1 APARTMENT | 13.67 | 232.36 | 01-JAN-03:10 | 705.80 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:G S1 APARTMENT | 1.45 | 8.68 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:G S1 APARTMENT | 1.32 | 7.86 | 01-JAN-00:10 | 125.72 | 01-JAN-19:10 |
| Electricity:Zone:G S2 APARTMENT | 13.67 | 232.36 | 01-JAN-03:10 | 705.80 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:G S2 APARTMENT | 1.45 | 8.68 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:G S2 APARTMENT | 1.32 | 7.86 | 01-JAN-00:10 | 125.72 | 01-JAN-19:10 |
| Electricity:Zone:M SW APARTMENT | 27.33 | 464.72 | 01-JAN-03:10 | 1411.61 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:M SW APARTMENT | 2.91 | 17.37 | 01-JAN-00:10 | 277.76 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:M SW APARTMENT | 2.63 | 15.72 | 01-JAN-00:10 | 251.45 | 01-JAN-19:10 |
| Electricity:Zone:M NW APARTMENT | 27.33 | 464.72 | 01-JAN-03:10 | 1411.61 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:M NW APARTMENT | 2.91 | 17.37 | 01-JAN-00:10 | 277.76 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:M NW APARTMENT | 2.63 | 15.72 | 01-JAN-00:10 | 251.45 | 01-JAN-19:10 |
| Electricity:Zone:M SE APARTMENT | 27.33 | 464.72 | 01-JAN-03:10 | 1411.61 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:M SE APARTMENT | 2.91 | 17.37 | 01-JAN-00:10 | 277.76 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:M SE APARTMENT | 2.63 | 15.72 | 01-JAN-00:10 | 251.45 | 01-JAN-19:10 |
| Electricity:Zone:M NE APARTMENT | 27.33 | 464.72 | 01-JAN-03:10 | 1411.61 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:M NE APARTMENT | 2.91 | 17.37 | 01-JAN-00:10 | 277.76 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:M NE APARTMENT | 2.63 | 15.72 | 01-JAN-00:10 | 251.45 | 01-JAN-19:10 |
| Electricity:Zone:M N1 APARTMENT | 27.33 | 464.72 | 01-JAN-03:10 | 1411.61 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:M N1 APARTMENT | 2.91 | 17.37 | 01-JAN-00:10 | 277.76 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:M N1 APARTMENT | 2.63 | 15.72 | 01-JAN-00:10 | 251.45 | 01-JAN-19:10 |
| Electricity:Zone:M N2 APARTMENT | 27.33 | 464.72 | 01-JAN-03:10 | 1411.61 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:M N2 APARTMENT | 2.91 | 17.37 | 01-JAN-00:10 | 277.76 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:M N2 APARTMENT | 2.63 | 15.72 | 01-JAN-00:10 | 251.45 | 01-JAN-19:10 |
| Electricity:Zone:M S1 APARTMENT | 27.33 | 464.72 | 01-JAN-03:10 | 1411.61 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:M S1 APARTMENT | 2.91 | 17.37 | 01-JAN-00:10 | 277.76 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:M S1 APARTMENT | 2.63 | 15.72 | 01-JAN-00:10 | 251.45 | 01-JAN-19:10 |
| Electricity:Zone:M S2 APARTMENT | 27.33 | 464.72 | 01-JAN-03:10 | 1411.61 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:M S2 APARTMENT | 2.91 | 17.37 | 01-JAN-00:10 | 277.76 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:M S2 APARTMENT | 2.63 | 15.72 | 01-JAN-00:10 | 251.45 | 01-JAN-19:10 |
| Electricity:Zone:T SW APARTMENT | 13.67 | 232.36 | 01-JAN-03:10 | 705.80 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:T SW APARTMENT | 1.45 | 8.68 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:T SW APARTMENT | 1.32 | 7.86 | 01-JAN-00:10 | 125.72 | 01-JAN-19:10 |
| Electricity:Zone:T NW APARTMENT | 13.67 | 232.36 | 01-JAN-03:10 | 705.80 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:T NW APARTMENT | 1.45 | 8.68 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:T NW APARTMENT | 1.32 | 7.86 | 01-JAN-00:10 | 125.72 | 01-JAN-19:10 |
| Electricity:Zone:T SE APARTMENT | 13.67 | 232.36 | 01-JAN-03:10 | 705.80 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:T SE APARTMENT | 1.45 | 8.68 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:T SE APARTMENT | 1.32 | 7.86 | 01-JAN-00:10 | 125.72 | 01-JAN-19:10 |
| Electricity:Zone:T NE APARTMENT | 13.67 | 232.36 | 01-JAN-03:10 | 705.80 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:T NE APARTMENT | 1.45 | 8.68 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:T NE APARTMENT | 1.32 | 7.86 | 01-JAN-00:10 | 125.72 | 01-JAN-19:10 |
| Electricity:Zone:T N1 APARTMENT | 13.67 | 232.36 | 01-JAN-03:10 | 705.80 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:T N1 APARTMENT | 1.45 | 8.68 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:T N1 APARTMENT | 1.32 | 7.86 | 01-JAN-00:10 | 125.72 | 01-JAN-19:10 |
| Electricity:Zone:T N2 APARTMENT | 13.67 | 232.36 | 01-JAN-03:10 | 705.80 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:T N2 APARTMENT | 1.45 | 8.68 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:T N2 APARTMENT | 1.32 | 7.86 | 01-JAN-00:10 | 125.72 | 01-JAN-19:10 |
| Electricity:Zone:T S1 APARTMENT | 13.67 | 232.36 | 01-JAN-03:10 | 705.80 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:T S1 APARTMENT | 1.45 | 8.68 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:T S1 APARTMENT | 1.32 | 7.86 | 01-JAN-00:10 | 125.72 | 01-JAN-19:10 |
| Electricity:Zone:T S2 APARTMENT | 13.67 | 232.36 | 01-JAN-03:10 | 705.80 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:T S2 APARTMENT | 1.45 | 8.68 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:T S2 APARTMENT | 1.32 | 7.86 | 01-JAN-00:10 | 125.72 | 01-JAN-19:10 |
| Electricity:Zone:G CORRIDOR | 82.28 | 1494.09 | 01-JAN-00:10 | 4538.70 | 01-JAN-07:10 |
| InteriorLights:Electricity:Zone:G CORRIDOR | 11.69 | 370.63 | 01-JAN-00:10 | 370.63 | 01-JAN-00:10 |
| LightsWired:InteriorLights:Electricity:Zone:G CORRIDOR | 11.69 | 370.63 | 01-JAN-00:10 | 370.63 | 01-JAN-00:10 |
| Electricity:Zone:M CORRIDOR | 23.38 | 741.26 | 01-JAN-00:10 | 741.26 | 01-JAN-00:10 |
| InteriorLights:Electricity:Zone:M CORRIDOR | 23.38 | 741.26 | 01-JAN-00:10 | 741.26 | 01-JAN-00:10 |
| LightsWired:InteriorLights:Electricity:Zone:M CORRIDOR | 23.38 | 741.26 | 01-JAN-00:10 | 741.26 | 01-JAN-00:10 |
| Electricity:Zone:T CORRIDOR | 11.69 | 370.63 | 01-JAN-00:10 | 370.63 | 01-JAN-00:10 |
| InteriorLights:Electricity:Zone:T CORRIDOR | 11.69 | 370.63 | 01-JAN-00:10 | 370.63 | 01-JAN-00:10 |
| LightsWired:InteriorLights:Electricity:Zone:T CORRIDOR | 11.69 | 370.63 | 01-JAN-00:10 | 370.63 | 01-JAN-00:10 |
| LightsPlugIn:InteriorLights:Electricity | 4.27 | 25.50 | 01-JAN-00:10 | 407.87 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:G SW APARTMENT | 0.14 | 0.82 | 01-JAN-00:10 | 13.16 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:SpaceType:GENERAL | 4.27 | 25.50 | 01-JAN-00:10 | 407.87 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:G NW APARTMENT | 0.14 | 0.82 | 01-JAN-00:10 | 13.16 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:G NE APARTMENT | 0.14 | 0.82 | 01-JAN-00:10 | 13.16 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:G N1 APARTMENT | 0.14 | 0.82 | 01-JAN-00:10 | 13.16 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:G N2 APARTMENT | 0.14 | 0.82 | 01-JAN-00:10 | 13.16 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:G S1 APARTMENT | 0.14 | 0.82 | 01-JAN-00:10 | 13.16 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:G S2 APARTMENT | 0.14 | 0.82 | 01-JAN-00:10 | 13.16 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:M SW APARTMENT | 0.28 | 1.65 | 01-JAN-00:10 | 26.31 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:M NW APARTMENT | 0.28 | 1.65 | 01-JAN-00:10 | 26.31 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:M SE APARTMENT | 0.28 | 1.65 | 01-JAN-00:10 | 26.31 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:M NE APARTMENT | 0.28 | 1.65 | 01-JAN-00:10 | 26.31 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:M N1 APARTMENT | 0.28 | 1.65 | 01-JAN-00:10 | 26.31 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:M N2 APARTMENT | 0.28 | 1.65 | 01-JAN-00:10 | 26.31 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:M S1 APARTMENT | 0.28 | 1.65 | 01-JAN-00:10 | 26.31 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:M S2 APARTMENT | 0.28 | 1.65 | 01-JAN-00:10 | 26.31 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:T SW APARTMENT | 0.14 | 0.82 | 01-JAN-00:10 | 13.16 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:T NW APARTMENT | 0.14 | 0.82 | 01-JAN-00:10 | 13.16 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:T SE APARTMENT | 0.14 | 0.82 | 01-JAN-00:10 | 13.16 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:T NE APARTMENT | 0.14 | 0.82 | 01-JAN-00:10 | 13.16 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:T N1 APARTMENT | 0.14 | 0.82 | 01-JAN-00:10 | 13.16 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:T N2 APARTMENT | 0.14 | 0.82 | 01-JAN-00:10 | 13.16 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:T S1 APARTMENT | 0.14 | 0.82 | 01-JAN-00:10 | 13.16 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:T S2 APARTMENT | 0.14 | 0.82 | 01-JAN-00:10 | 13.16 | 01-JAN-19:10 |
| InteriorEquipment:Electricity | 458.66 | 8251.68 | 01-JAN-03:10 | 22709.69 | 03-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:G SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:SpaceType:GENERAL | 458.66 | 8251.68 | 01-JAN-03:10 | 22709.69 | 03-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity | 388.06 | 7128.22 | 01-JAN-03:10 | 18541.61 | 03-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:G SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 388.06 | 7128.22 | 01-JAN-03:10 | 18541.61 | 03-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:G NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:G NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:OFFICE | 9.47 | 194.25 | 01-JAN-00:10 | 588.62 | 03-JAN-08:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:OFFICE | 9.47 | 194.25 | 01-JAN-00:10 | 588.62 | 03-JAN-08:10 |
| InteriorEquipment:Electricity:Zone:G NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:G NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:G N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:G N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:G N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:G N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:G S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:G S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:G S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:G S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:M SW APARTMENT | 24.43 | 447.35 | 01-JAN-03:10 | 1177.25 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:M SW APARTMENT | 24.43 | 447.35 | 01-JAN-03:10 | 1177.25 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:M NW APARTMENT | 24.43 | 447.35 | 01-JAN-03:10 | 1177.25 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:M NW APARTMENT | 24.43 | 447.35 | 01-JAN-03:10 | 1177.25 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:M SE APARTMENT | 24.43 | 447.35 | 01-JAN-03:10 | 1177.25 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:M SE APARTMENT | 24.43 | 447.35 | 01-JAN-03:10 | 1177.25 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:M NE APARTMENT | 24.43 | 447.35 | 01-JAN-03:10 | 1177.25 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:M NE APARTMENT | 24.43 | 447.35 | 01-JAN-03:10 | 1177.25 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:M N1 APARTMENT | 24.43 | 447.35 | 01-JAN-03:10 | 1177.25 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:M N1 APARTMENT | 24.43 | 447.35 | 01-JAN-03:10 | 1177.25 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:M N2 APARTMENT | 24.43 | 447.35 | 01-JAN-03:10 | 1177.25 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:M N2 APARTMENT | 24.43 | 447.35 | 01-JAN-03:10 | 1177.25 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:M S1 APARTMENT | 24.43 | 447.35 | 01-JAN-03:10 | 1177.25 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:M S1 APARTMENT | 24.43 | 447.35 | 01-JAN-03:10 | 1177.25 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:M S2 APARTMENT | 24.43 | 447.35 | 01-JAN-03:10 | 1177.25 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:M S2 APARTMENT | 24.43 | 447.35 | 01-JAN-03:10 | 1177.25 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:T SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:T SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:T NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:T NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:T SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:T SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:T NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:T NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:T N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:T N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:T N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:T N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:T S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:T S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:T S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:T S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:G CORRIDOR | 70.59 | 1123.46 | 01-JAN-00:10 | 4168.07 | 01-JAN-07:10 |
| ElevatorLift:InteriorEquipment:Electricity | 65.48 | 961.46 | 01-JAN-00:10 | 4006.07 | 01-JAN-07:10 |
| ElevatorLift:InteriorEquipment:Electricity:Zone:G CORRIDOR | 65.48 | 961.46 | 01-JAN-00:10 | 4006.07 | 01-JAN-07:10 |
| ElevatorLift:InteriorEquipment:Electricity:SpaceType:GENERAL | 65.48 | 961.46 | 01-JAN-00:10 | 4006.07 | 01-JAN-07:10 |
| ElevatorLightsFan:InteriorEquipment:Electricity | 5.11 | 162.00 | 01-JAN-00:10 | 162.00 | 01-JAN-00:10 |
| ElevatorLightsFan:InteriorEquipment:Electricity:Zone:G CORRIDOR | 5.11 | 162.00 | 01-JAN-00:10 | 162.00 | 01-JAN-00:10 |
| ElevatorLightsFan:InteriorEquipment:Electricity:SpaceType:GENERAL | 5.11 | 162.00 | 01-JAN-00:10 | 162.00 | 01-JAN-00:10 |
| Fans:Electricity | 106.86 | 1767.27 | 03-MAY-16:10 | 9639.30 | 28-JUN-16:20 |
| Fans:Electricity:Zone:G SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:G SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:G NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:G NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:G NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:G NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:G N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:G N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:G N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:G N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:G S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:G S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:G S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:G S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:M SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:M SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:M NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:M NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:M SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:M SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:M NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:M NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:M N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:M N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:M N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:M N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:M S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:M S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:M S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:M S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:T SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:T SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:T NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:T NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:T SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:T SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:T NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:T NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:T N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:T N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:T N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:T N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:T S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:T S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:T S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:T S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| ElectricityPurchased:Facility | 1308.91 | 17020.55 | 18-APR-02:30 | 90289.92 | 20-AUG-17:10 |
| ElectricityPurchased:Plant | 1308.91 | 17020.55 | 18-APR-02:30 | 90289.92 | 20-AUG-17:10 |
| Cogeneration:ElectricityPurchased | 1308.91 | 17020.55 | 18-APR-02:30 | 90289.92 | 20-AUG-17:10 |
| General:Cogeneration:ElectricityPurchased | 1308.91 | 17020.55 | 18-APR-02:30 | 90289.92 | 20-AUG-17:10 |
| ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| ElectricityNet:Facility | 1308.91 | 17020.55 | 18-APR-02:30 | 90289.92 | 20-AUG-17:10 |
| ElectricityNet:Plant | 1308.91 | 17020.55 | 18-APR-02:30 | 90289.92 | 20-AUG-17:10 |
| Cogeneration:ElectricityNet | 1308.91 | 17020.55 | 18-APR-02:30 | 90289.92 | 20-AUG-17:10 |
| General:Cogeneration:ElectricityNet | 1308.91 | 17020.55 | 18-APR-02:30 | 90289.92 | 20-AUG-17:10 |
| Electricity:HVAC | 258.09 | 1767.27 | 03-MAY-16:10 | 36582.37 | 28-JUN-16:30 |
| HeatRecovery:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:HeatRecovery:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:Fans:Electricity | 106.86 | 1767.27 | 03-MAY-16:10 | 9639.30 | 28-JUN-16:20 |
| Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Cooling:Electricity | 151.23 | 0.00 | 01-JAN-00:10 | 27057.48 | 28-JUN-16:00 |
| General:Cooling:Electricity | 151.23 | 0.00 | 01-JAN-00:10 | 27057.48 | 28-JUN-16:00 |
| ExteriorLights:Electricity | 50.02 | 0.00 | 01-JAN-07:20 | 3183.33 | 01-JAN-00:10 |
| General:ExteriorLights:Electricity | 50.02 | 0.00 | 01-JAN-07:20 | 3183.33 | 01-JAN-00:10 |
| Electricity:Plant | 442.92 | 1950.00 | 01-JAN-00:10 | 37737.59 | 08-JAN-07:50 |
| WaterSystems:Electricity | 442.92 | 1950.00 | 01-JAN-00:10 | 37737.59 | 08-JAN-07:50 |
| Water Heater:WaterSystems:Electricity | 442.92 | 1950.00 | 01-JAN-00:10 | 37737.59 | 08-JAN-07:50 |
| Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
| NaturalGas:Facility | 146.93 | 0.00 | 01-JAN-13:30 | 54300.33 | 06-FEB-05:00 |
| NaturalGas:HVAC | 146.93 | 0.00 | 01-JAN-13:30 | 54300.33 | 06-FEB-05:00 |
| Heating:NaturalGas | 146.93 | 0.00 | 01-JAN-13:30 | 54300.33 | 06-FEB-05:00 |
| General:Heating:NaturalGas | 146.93 | 0.00 | 01-JAN-13:30 | 54300.33 | 06-FEB-05:00 |
| Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
| None |
| Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
| Water:Facility | 1875.32 | 0.00 | 01-JAN-02:10 | 0.00 | 01-JAN-07:10 |
| Water:Plant | 1875.32 | 0.00 | 01-JAN-02:10 | 0.00 | 01-JAN-07:10 |
| WaterSystems:Water | 1875.32 | 0.00 | 01-JAN-02:10 | 0.00 | 01-JAN-07:10 |
| Water Heater:WaterSystems:Water | 1875.32 | 0.00 | 01-JAN-02:10 | 0.00 | 01-JAN-07:10 |
| MainsWater:Facility | 1875.32 | 0.00 | 01-JAN-02:10 | 0.00 | 01-JAN-07:10 |
| MainsWater:Plant | 1875.32 | 0.00 | 01-JAN-02:10 | 0.00 | 01-JAN-07:10 |
| WaterSystems:MainsWater | 1875.32 | 0.00 | 01-JAN-02:10 | 0.00 | 01-JAN-07:10 |
| Water Heater:WaterSystems:MainsWater | 1875.32 | 0.00 | 01-JAN-02:10 | 0.00 | 01-JAN-07:10 |
| Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
| Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
| CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
| Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
| None |
| Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
| None |
| Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
| EnergyTransfer:Facility | 1368.44 | 4083.25 | 20-MAR-12:40 | 157088.48 | 29-JUN-15:10 |
| EnergyTransfer:Building | 683.93 | 3748.77 | 28-MAR-12:00 | 68646.48 | 04-JUL-17:00 |
| EnergyTransfer:Zone:G SW APARTMENT | 20.52 | 0.00 | 29-MAR-06:00 | 2467.86 | 21-SEP-16:10 |
| Heating:EnergyTransfer | 48.03 | 0.00 | 01-JAN-17:50 | 26152.91 | 06-FEB-05:00 |
| Heating:EnergyTransfer:Zone:G SW APARTMENT | 0.36 | 0.00 | 01-JAN-00:10 | 728.87 | 18-JAN-01:50 |
| General:Heating:EnergyTransfer | 48.03 | 0.00 | 01-JAN-17:50 | 26152.91 | 06-FEB-05:00 |
| General:Heating:EnergyTransfer:Zone:G SW APARTMENT | 0.36 | 0.00 | 01-JAN-00:10 | 728.87 | 18-JAN-01:50 |
| Cooling:EnergyTransfer | 635.90 | 22.26 | 19-JAN-09:00 | 68646.48 | 04-JUL-17:00 |
| Cooling:EnergyTransfer:Zone:G SW APARTMENT | 20.15 | 0.00 | 08-JAN-05:00 | 2467.86 | 21-SEP-16:10 |
| General:Cooling:EnergyTransfer | 635.90 | 22.26 | 19-JAN-09:00 | 68646.48 | 04-JUL-17:00 |
| General:Cooling:EnergyTransfer:Zone:G SW APARTMENT | 20.15 | 0.00 | 08-JAN-05:00 | 2467.86 | 21-SEP-16:10 |
| EnergyTransfer:Zone:G NW APARTMENT | 16.13 | 0.01 | 28-JAN-18:50 | 2261.72 | 04-JUL-17:30 |
| Heating:EnergyTransfer:Zone:G NW APARTMENT | 2.46 | 0.00 | 01-JAN-12:10 | 1135.09 | 06-FEB-05:00 |
| General:Heating:EnergyTransfer:Zone:G NW APARTMENT | 2.46 | 0.00 | 01-JAN-12:10 | 1135.09 | 06-FEB-05:00 |
| Cooling:EnergyTransfer:Zone:G NW APARTMENT | 13.68 | 0.00 | 01-JAN-00:10 | 2261.72 | 04-JUL-17:30 |
| General:Cooling:EnergyTransfer:Zone:G NW APARTMENT | 13.68 | 0.00 | 01-JAN-00:10 | 2261.72 | 04-JUL-17:30 |
| EnergyTransfer:Zone:OFFICE | 17.46 | 0.00 | 14-OCT-19:40 | 4383.37 | 21-AUG-08:10 |
| Heating:EnergyTransfer:Zone:OFFICE | 2.54 | 0.00 | 01-JAN-00:10 | 1638.63 | 06-FEB-08:10 |
| General:Heating:EnergyTransfer:Zone:OFFICE | 2.54 | 0.00 | 01-JAN-00:10 | 1638.63 | 06-FEB-08:10 |
| Cooling:EnergyTransfer:Zone:OFFICE | 14.91 | 0.00 | 01-JAN-12:30 | 4383.37 | 21-AUG-08:10 |
| General:Cooling:EnergyTransfer:Zone:OFFICE | 14.91 | 0.00 | 01-JAN-12:30 | 4383.37 | 21-AUG-08:10 |
| EnergyTransfer:Zone:G NE APARTMENT | 16.69 | 0.01 | 17-DEC-20:00 | 1845.24 | 04-JUL-17:10 |
| Heating:EnergyTransfer:Zone:G NE APARTMENT | 2.37 | 0.00 | 01-JAN-09:20 | 1144.30 | 06-FEB-05:00 |
| General:Heating:EnergyTransfer:Zone:G NE APARTMENT | 2.37 | 0.00 | 01-JAN-09:20 | 1144.30 | 06-FEB-05:00 |
| Cooling:EnergyTransfer:Zone:G NE APARTMENT | 14.32 | 0.00 | 01-JAN-00:10 | 1845.24 | 04-JUL-17:10 |
| General:Cooling:EnergyTransfer:Zone:G NE APARTMENT | 14.32 | 0.00 | 01-JAN-00:10 | 1845.24 | 04-JUL-17:10 |
| EnergyTransfer:Zone:G N1 APARTMENT | 13.01 | 0.01 | 07-FEB-19:00 | 1429.83 | 04-JUL-17:40 |
| Heating:EnergyTransfer:Zone:G N1 APARTMENT | 0.68 | 0.00 | 01-JAN-07:20 | 586.36 | 06-FEB-05:00 |
| General:Heating:EnergyTransfer:Zone:G N1 APARTMENT | 0.68 | 0.00 | 01-JAN-07:20 | 586.36 | 06-FEB-05:00 |
| Cooling:EnergyTransfer:Zone:G N1 APARTMENT | 12.33 | 0.00 | 01-JAN-00:10 | 1429.83 | 04-JUL-17:40 |
| General:Cooling:EnergyTransfer:Zone:G N1 APARTMENT | 12.33 | 0.00 | 01-JAN-00:10 | 1429.83 | 04-JUL-17:40 |
| EnergyTransfer:Zone:G N2 APARTMENT | 13.06 | 0.00 | 27-NOV-05:20 | 1423.25 | 04-JUL-17:40 |
| Heating:EnergyTransfer:Zone:G N2 APARTMENT | 0.68 | 0.00 | 01-JAN-08:50 | 586.74 | 06-FEB-05:00 |
| General:Heating:EnergyTransfer:Zone:G N2 APARTMENT | 0.68 | 0.00 | 01-JAN-08:50 | 586.74 | 06-FEB-05:00 |
| Cooling:EnergyTransfer:Zone:G N2 APARTMENT | 12.37 | 0.00 | 01-JAN-00:10 | 1423.25 | 04-JUL-17:40 |
| General:Cooling:EnergyTransfer:Zone:G N2 APARTMENT | 12.37 | 0.00 | 01-JAN-00:10 | 1423.25 | 04-JUL-17:40 |
| EnergyTransfer:Zone:G S1 APARTMENT | 19.94 | 0.05 | 17-JAN-03:40 | 1836.64 | 21-SEP-15:10 |
| Heating:EnergyTransfer:Zone:G S1 APARTMENT | 0.02 | 0.00 | 01-JAN-00:10 | 232.32 | 18-JAN-01:50 |
| General:Heating:EnergyTransfer:Zone:G S1 APARTMENT | 0.02 | 0.00 | 01-JAN-00:10 | 232.32 | 18-JAN-01:50 |
| Cooling:EnergyTransfer:Zone:G S1 APARTMENT | 19.92 | 0.00 | 17-JAN-03:50 | 1836.64 | 21-SEP-15:10 |
| General:Cooling:EnergyTransfer:Zone:G S1 APARTMENT | 19.92 | 0.00 | 17-JAN-03:50 | 1836.64 | 21-SEP-15:10 |
| EnergyTransfer:Zone:G S2 APARTMENT | 21.45 | 0.10 | 04-FEB-05:10 | 1956.15 | 03-SEP-13:30 |
| Heating:EnergyTransfer:Zone:G S2 APARTMENT | 0.03 | 0.00 | 01-JAN-00:10 | 269.29 | 18-JAN-02:00 |
| General:Heating:EnergyTransfer:Zone:G S2 APARTMENT | 0.03 | 0.00 | 01-JAN-00:10 | 269.29 | 18-JAN-02:00 |
| Cooling:EnergyTransfer:Zone:G S2 APARTMENT | 21.42 | 0.00 | 17-JAN-02:40 | 1956.15 | 03-SEP-13:30 |
| General:Cooling:EnergyTransfer:Zone:G S2 APARTMENT | 21.42 | 0.00 | 17-JAN-02:40 | 1956.15 | 03-SEP-13:30 |
| EnergyTransfer:Zone:M SW APARTMENT | 53.11 | 0.04 | 17-JAN-12:30 | 5909.72 | 20-SEP-16:20 |
| Heating:EnergyTransfer:Zone:M SW APARTMENT | 0.30 | 0.00 | 01-JAN-00:10 | 1560.98 | 18-JAN-01:10 |
| General:Heating:EnergyTransfer:Zone:M SW APARTMENT | 0.30 | 0.00 | 01-JAN-00:10 | 1560.98 | 18-JAN-01:10 |
| Cooling:EnergyTransfer:Zone:M SW APARTMENT | 52.81 | 0.00 | 12-JAN-05:50 | 5909.72 | 20-SEP-16:20 |
| General:Cooling:EnergyTransfer:Zone:M SW APARTMENT | 52.81 | 0.00 | 12-JAN-05:50 | 5909.72 | 20-SEP-16:20 |
| EnergyTransfer:Zone:M NW APARTMENT | 38.92 | 0.01 | 20-DEC-11:50 | 5671.27 | 04-JUL-17:30 |
| Heating:EnergyTransfer:Zone:M NW APARTMENT | 2.46 | 0.00 | 01-JAN-00:10 | 2163.05 | 14-DEC-04:00 |
| General:Heating:EnergyTransfer:Zone:M NW APARTMENT | 2.46 | 0.00 | 01-JAN-00:10 | 2163.05 | 14-DEC-04:00 |
| Cooling:EnergyTransfer:Zone:M NW APARTMENT | 36.46 | 0.00 | 01-JAN-01:10 | 5671.27 | 04-JUL-17:30 |
| General:Cooling:EnergyTransfer:Zone:M NW APARTMENT | 36.46 | 0.00 | 01-JAN-01:10 | 5671.27 | 04-JUL-17:30 |
| EnergyTransfer:Zone:M SE APARTMENT | 54.73 | 0.33 | 01-FEB-00:50 | 5225.36 | 03-SEP-13:30 |
| Heating:EnergyTransfer:Zone:M SE APARTMENT | 0.32 | 0.00 | 01-JAN-00:10 | 1579.18 | 18-JAN-01:10 |
| General:Heating:EnergyTransfer:Zone:M SE APARTMENT | 0.32 | 0.00 | 01-JAN-00:10 | 1579.18 | 18-JAN-01:10 |
| Cooling:EnergyTransfer:Zone:M SE APARTMENT | 54.41 | 0.00 | 12-JAN-06:00 | 5225.36 | 03-SEP-13:30 |
| General:Cooling:EnergyTransfer:Zone:M SE APARTMENT | 54.41 | 0.00 | 12-JAN-06:00 | 5225.36 | 03-SEP-13:30 |
| EnergyTransfer:Zone:M NE APARTMENT | 40.43 | 0.04 | 22-FEB-22:50 | 4393.80 | 29-JUN-15:10 |
| Heating:EnergyTransfer:Zone:M NE APARTMENT | 2.39 | 0.00 | 01-JAN-07:50 | 2214.92 | 14-DEC-04:00 |
| General:Heating:EnergyTransfer:Zone:M NE APARTMENT | 2.39 | 0.00 | 01-JAN-07:50 | 2214.92 | 14-DEC-04:00 |
| Cooling:EnergyTransfer:Zone:M NE APARTMENT | 38.04 | 0.00 | 01-JAN-00:10 | 4393.80 | 29-JUN-15:10 |
| General:Cooling:EnergyTransfer:Zone:M NE APARTMENT | 38.04 | 0.00 | 01-JAN-00:10 | 4393.80 | 29-JUN-15:10 |
| EnergyTransfer:Zone:M N1 APARTMENT | 32.67 | 0.08 | 17-DEC-02:20 | 3267.41 | 04-JUL-18:00 |
| Heating:EnergyTransfer:Zone:M N1 APARTMENT | 0.28 | 0.00 | 01-JAN-00:10 | 969.60 | 14-DEC-04:00 |
| General:Heating:EnergyTransfer:Zone:M N1 APARTMENT | 0.28 | 0.00 | 01-JAN-00:10 | 969.60 | 14-DEC-04:00 |
| Cooling:EnergyTransfer:Zone:M N1 APARTMENT | 32.38 | 0.00 | 07-JAN-02:30 | 3267.41 | 04-JUL-18:00 |
| General:Cooling:EnergyTransfer:Zone:M N1 APARTMENT | 32.38 | 0.00 | 07-JAN-02:30 | 3267.41 | 04-JUL-18:00 |
| EnergyTransfer:Zone:M N2 APARTMENT | 32.75 | 0.10 | 15-JAN-00:30 | 3246.11 | 16-JUN-18:00 |
| Heating:EnergyTransfer:Zone:M N2 APARTMENT | 0.29 | 0.00 | 01-JAN-00:10 | 970.87 | 14-DEC-04:00 |
| General:Heating:EnergyTransfer:Zone:M N2 APARTMENT | 0.29 | 0.00 | 01-JAN-00:10 | 970.87 | 14-DEC-04:00 |
| Cooling:EnergyTransfer:Zone:M N2 APARTMENT | 32.46 | 0.00 | 07-JAN-02:30 | 3246.11 | 16-JUN-18:00 |
| General:Cooling:EnergyTransfer:Zone:M N2 APARTMENT | 32.46 | 0.00 | 07-JAN-02:30 | 3246.11 | 16-JUN-18:00 |
| EnergyTransfer:Zone:M S1 APARTMENT | 49.68 | 0.85 | 17-JAN-23:50 | 4259.33 | 21-SEP-14:10 |
| Heating:EnergyTransfer:Zone:M S1 APARTMENT | 0.01 | 0.00 | 01-JAN-00:10 | 413.53 | 18-JAN-02:00 |
| General:Heating:EnergyTransfer:Zone:M S1 APARTMENT | 0.01 | 0.00 | 01-JAN-00:10 | 413.53 | 18-JAN-02:00 |
| Cooling:EnergyTransfer:Zone:M S1 APARTMENT | 49.68 | 0.00 | 17-JAN-23:50 | 4259.33 | 21-SEP-14:10 |
| General:Cooling:EnergyTransfer:Zone:M S1 APARTMENT | 49.68 | 0.00 | 17-JAN-23:50 | 4259.33 | 21-SEP-14:10 |
| EnergyTransfer:Zone:M S2 APARTMENT | 49.81 | 1.21 | 09-DEC-04:40 | 4265.37 | 21-SEP-14:10 |
| Heating:EnergyTransfer:Zone:M S2 APARTMENT | 0.01 | 0.00 | 01-JAN-00:10 | 414.04 | 18-JAN-02:00 |
| General:Heating:EnergyTransfer:Zone:M S2 APARTMENT | 0.01 | 0.00 | 01-JAN-00:10 | 414.04 | 18-JAN-02:00 |
| Cooling:EnergyTransfer:Zone:M S2 APARTMENT | 49.80 | 0.00 | 17-JAN-23:50 | 4265.37 | 21-SEP-14:10 |
| General:Cooling:EnergyTransfer:Zone:M S2 APARTMENT | 49.80 | 0.00 | 17-JAN-23:50 | 4265.37 | 21-SEP-14:10 |
| EnergyTransfer:Zone:T SW APARTMENT | 29.21 | 0.01 | 01-APR-01:00 | 4120.30 | 20-AUG-16:10 |
| Heating:EnergyTransfer:Zone:T SW APARTMENT | 4.13 | 0.00 | 01-JAN-08:50 | 2034.77 | 06-FEB-05:00 |
| General:Heating:EnergyTransfer:Zone:T SW APARTMENT | 4.13 | 0.00 | 01-JAN-08:50 | 2034.77 | 06-FEB-05:00 |
| Cooling:EnergyTransfer:Zone:T SW APARTMENT | 25.07 | 0.00 | 01-JAN-00:10 | 4120.30 | 20-AUG-16:10 |
| General:Cooling:EnergyTransfer:Zone:T SW APARTMENT | 25.07 | 0.00 | 01-JAN-00:10 | 4120.30 | 20-AUG-16:10 |
| EnergyTransfer:Zone:T NW APARTMENT | 24.90 | 0.00 | 23-OCT-08:50 | 3907.60 | 28-JUN-16:30 |
| Heating:EnergyTransfer:Zone:T NW APARTMENT | 7.12 | 0.00 | 01-JAN-12:30 | 2181.11 | 14-DEC-04:00 |
| General:Heating:EnergyTransfer:Zone:T NW APARTMENT | 7.12 | 0.00 | 01-JAN-12:30 | 2181.11 | 14-DEC-04:00 |
| Cooling:EnergyTransfer:Zone:T NW APARTMENT | 17.78 | 0.00 | 01-JAN-00:10 | 3907.60 | 28-JUN-16:30 |
| General:Cooling:EnergyTransfer:Zone:T NW APARTMENT | 17.78 | 0.00 | 01-JAN-00:10 | 3907.60 | 28-JUN-16:30 |
| EnergyTransfer:Zone:T SE APARTMENT | 29.77 | 0.17 | 01-FEB-20:00 | 3713.67 | 03-SEP-13:30 |
| Heating:EnergyTransfer:Zone:T SE APARTMENT | 4.06 | 0.00 | 01-JAN-08:20 | 2041.98 | 06-FEB-05:00 |
| General:Heating:EnergyTransfer:Zone:T SE APARTMENT | 4.06 | 0.00 | 01-JAN-08:20 | 2041.98 | 06-FEB-05:00 |
| Cooling:EnergyTransfer:Zone:T SE APARTMENT | 25.71 | 0.00 | 01-JAN-00:10 | 3713.67 | 03-SEP-13:30 |
| General:Cooling:EnergyTransfer:Zone:T SE APARTMENT | 25.71 | 0.00 | 01-JAN-00:10 | 3713.67 | 03-SEP-13:30 |
| EnergyTransfer:Zone:T NE APARTMENT | 25.20 | 0.00 | 24-JAN-20:00 | 3140.22 | 29-JUN-15:10 |
| Heating:EnergyTransfer:Zone:T NE APARTMENT | 6.86 | 0.00 | 01-JAN-10:10 | 2210.17 | 14-DEC-04:00 |
| General:Heating:EnergyTransfer:Zone:T NE APARTMENT | 6.86 | 0.00 | 01-JAN-10:10 | 2210.17 | 14-DEC-04:00 |
| Cooling:EnergyTransfer:Zone:T NE APARTMENT | 18.35 | 0.00 | 01-JAN-00:10 | 3140.22 | 29-JUN-15:10 |
| General:Cooling:EnergyTransfer:Zone:T NE APARTMENT | 18.35 | 0.00 | 01-JAN-00:10 | 3140.22 | 29-JUN-15:10 |
| EnergyTransfer:Zone:T N1 APARTMENT | 18.29 | 0.01 | 30-JAN-21:10 | 2390.97 | 29-JUN-15:10 |
| Heating:EnergyTransfer:Zone:T N1 APARTMENT | 3.75 | 0.00 | 01-JAN-11:10 | 1387.68 | 06-FEB-05:00 |
| General:Heating:EnergyTransfer:Zone:T N1 APARTMENT | 3.75 | 0.00 | 01-JAN-11:10 | 1387.68 | 06-FEB-05:00 |
| Cooling:EnergyTransfer:Zone:T N1 APARTMENT | 14.54 | 0.00 | 01-JAN-00:10 | 2390.97 | 29-JUN-15:10 |
| General:Cooling:EnergyTransfer:Zone:T N1 APARTMENT | 14.54 | 0.00 | 01-JAN-00:10 | 2390.97 | 29-JUN-15:10 |
| EnergyTransfer:Zone:T N2 APARTMENT | 18.35 | 0.00 | 22-FEB-13:50 | 2389.70 | 29-JUN-15:10 |
| Heating:EnergyTransfer:Zone:T N2 APARTMENT | 3.76 | 0.00 | 01-JAN-11:00 | 1388.25 | 06-FEB-05:00 |
| General:Heating:EnergyTransfer:Zone:T N2 APARTMENT | 3.76 | 0.00 | 01-JAN-11:00 | 1388.25 | 06-FEB-05:00 |
| Cooling:EnergyTransfer:Zone:T N2 APARTMENT | 14.59 | 0.00 | 01-JAN-00:10 | 2389.70 | 29-JUN-15:10 |
| General:Cooling:EnergyTransfer:Zone:T N2 APARTMENT | 14.59 | 0.00 | 01-JAN-00:10 | 2389.70 | 29-JUN-15:10 |
| EnergyTransfer:Zone:T S1 APARTMENT | 23.88 | 0.03 | 06-NOV-03:20 | 3067.40 | 03-SEP-13:30 |
| Heating:EnergyTransfer:Zone:T S1 APARTMENT | 1.56 | 0.00 | 01-JAN-00:10 | 1227.83 | 06-FEB-05:00 |
| General:Heating:EnergyTransfer:Zone:T S1 APARTMENT | 1.56 | 0.00 | 01-JAN-00:10 | 1227.83 | 06-FEB-05:00 |
| Cooling:EnergyTransfer:Zone:T S1 APARTMENT | 22.32 | 0.00 | 01-JAN-02:10 | 3067.40 | 03-SEP-13:30 |
| General:Cooling:EnergyTransfer:Zone:T S1 APARTMENT | 22.32 | 0.00 | 01-JAN-02:10 | 3067.40 | 03-SEP-13:30 |
| EnergyTransfer:Zone:T S2 APARTMENT | 23.98 | 0.03 | 04-NOV-10:10 | 3078.75 | 03-SEP-13:30 |
| Heating:EnergyTransfer:Zone:T S2 APARTMENT | 1.57 | 0.00 | 01-JAN-00:10 | 1227.84 | 06-FEB-05:00 |
| General:Heating:EnergyTransfer:Zone:T S2 APARTMENT | 1.57 | 0.00 | 01-JAN-00:10 | 1227.84 | 06-FEB-05:00 |
| Cooling:EnergyTransfer:Zone:T S2 APARTMENT | 22.41 | 0.00 | 01-JAN-02:10 | 3078.75 | 03-SEP-13:30 |
| General:Cooling:EnergyTransfer:Zone:T S2 APARTMENT | 22.41 | 0.00 | 01-JAN-02:10 | 3078.75 | 03-SEP-13:30 |
| EnergyTransfer:Zone:T CORRIDOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Heating:EnergyTransfer:Zone:T CORRIDOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:Heating:EnergyTransfer:Zone:T CORRIDOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Cooling:EnergyTransfer:Zone:T CORRIDOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:Cooling:EnergyTransfer:Zone:T CORRIDOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| EnergyTransfer:Zone:G CORRIDOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Heating:EnergyTransfer:Zone:G CORRIDOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:Heating:EnergyTransfer:Zone:G CORRIDOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Cooling:EnergyTransfer:Zone:G CORRIDOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:Cooling:EnergyTransfer:Zone:G CORRIDOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| EnergyTransfer:Zone:M CORRIDOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Heating:EnergyTransfer:Zone:M CORRIDOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:Heating:EnergyTransfer:Zone:M CORRIDOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Cooling:EnergyTransfer:Zone:M CORRIDOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:Cooling:EnergyTransfer:Zone:M CORRIDOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| EnergyTransfer:HVAC | 684.51 | 0.00 | 22-MAR-13:10 | 88506.84 | 29-JUN-15:10 |
| HeatRecoveryForHeating:EnergyTransfer | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 21-MAY-20:10 |
| HeatRecoveryForCooling:EnergyTransfer | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 21-MAY-18:20 |
| HeatingCoils:EnergyTransfer | 117.54 | 0.00 | 01-JAN-13:30 | 43440.26 | 06-FEB-05:00 |
| CoolingCoils:EnergyTransfer | 566.97 | 0.00 | 01-JAN-00:10 | 88506.84 | 29-JUN-15:10 |
| PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 09:14:27
Annual Building Sensible Heat Gain Components| HVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
| G SW APARTMENT | 0.729 | -7.817 | 2.149 | -14.850 | 0.000 | 0.000 | 3.772 | 1.454 | 12.213 | 17.416 | 0.000 | 0.183 | 0.001 | 0.000 | -5.457 | 0.000 | -2.802 | -6.989 |
| G NW APARTMENT | 0.729 | -7.445 | 6.929 | -11.433 | 0.000 | 0.000 | 3.896 | 1.454 | 12.213 | 8.780 | 0.000 | 0.183 | 0.000 | 0.000 | -5.399 | 0.000 | -2.632 | -7.275 |
| OFFICE | 0.000 | 0.000 | 2.544 | -14.913 | 0.000 | 0.000 | 2.024 | 7.396 | 9.469 | 17.555 | 0.000 | 0.102 | 0.001 | 0.000 | -5.856 | 0.000 | -2.429 | -15.890 |
| G NE APARTMENT | 0.729 | -7.460 | 6.821 | -12.036 | 0.000 | 0.000 | 3.895 | 1.454 | 12.213 | 9.149 | 0.000 | 0.183 | 0.000 | 0.000 | -5.171 | 0.000 | -2.645 | -7.132 |
| G N1 APARTMENT | 0.730 | -7.480 | 4.526 | -9.424 | 0.000 | 0.000 | 3.887 | 1.454 | 12.213 | 2.881 | 0.000 | 0.110 | 0.000 | 0.000 | -3.360 | 0.000 | -1.833 | -3.704 |
| G N2 APARTMENT | 0.730 | -7.482 | 4.527 | -9.464 | 0.000 | 0.000 | 3.887 | 1.454 | 12.213 | 2.879 | 0.000 | 0.110 | 0.000 | 0.000 | -3.361 | 0.000 | -1.834 | -3.658 |
| G S1 APARTMENT | 0.729 | -7.996 | 0.649 | -13.278 | 0.000 | 0.000 | 3.726 | 1.454 | 12.213 | 11.614 | 0.000 | 0.110 | 0.001 | 0.000 | -3.357 | 0.000 | -1.996 | -3.868 |
| G S2 APARTMENT | 0.729 | -8.014 | 0.676 | -14.781 | 0.000 | 0.000 | 3.722 | 1.454 | 12.213 | 11.600 | 0.000 | 0.110 | 0.000 | 0.000 | -3.373 | 0.000 | -2.002 | -2.334 |
| M SW APARTMENT | 1.457 | -16.106 | 1.999 | -39.858 | 0.000 | 0.000 | 7.428 | 2.908 | 24.426 | 34.432 | 0.000 | 0.522 | 2.069 | 0.000 | -11.319 | 0.000 | -7.958 | -0.000 |
| M NW APARTMENT | 1.457 | -15.241 | 9.123 | -29.338 | 0.000 | 0.000 | 7.707 | 2.908 | 24.426 | 17.237 | 0.000 | 0.522 | 0.000 | 0.000 | -11.241 | 0.000 | -7.537 | -0.024 |
| M SE APARTMENT | 1.457 | -16.145 | 2.025 | -41.430 | 0.000 | 0.000 | 7.427 | 2.908 | 24.426 | 35.375 | 0.000 | 0.522 | 2.473 | 0.000 | -11.061 | 0.000 | -7.976 | -0.001 |
| M NE APARTMENT | 1.457 | -15.269 | 8.981 | -30.814 | 0.000 | 0.000 | 7.708 | 2.908 | 24.426 | 17.955 | 0.000 | 0.522 | 0.436 | 0.000 | -10.753 | 0.000 | -7.558 | -0.001 |
| M N1 APARTMENT | 1.458 | -15.352 | 4.906 | -23.111 | 0.000 | 0.000 | 7.678 | 2.908 | 24.426 | 5.614 | 0.000 | 0.315 | 3.340 | 0.000 | -7.004 | 0.000 | -5.178 | -0.000 |
| M N2 APARTMENT | 1.458 | -15.356 | 4.920 | -23.195 | 0.000 | 0.000 | 7.677 | 2.908 | 24.426 | 5.611 | 0.000 | 0.315 | 3.422 | 0.000 | -7.005 | 0.000 | -5.182 | -0.000 |
| M S1 APARTMENT | 1.457 | -16.489 | 0.376 | -35.011 | 0.000 | 0.000 | 7.322 | 2.908 | 24.426 | 23.011 | 0.000 | 0.315 | 4.179 | 0.000 | -6.955 | 0.000 | -5.540 | -0.000 |
| M S2 APARTMENT | 1.457 | -16.490 | 0.377 | -35.135 | 0.000 | 0.000 | 7.322 | 2.908 | 24.426 | 23.009 | 0.000 | 0.315 | 4.305 | 0.000 | -6.955 | 0.000 | -5.540 | -0.000 |
| T SW APARTMENT | 0.729 | -7.698 | 7.755 | -21.724 | 0.000 | 0.000 | 3.816 | 1.454 | 12.213 | 17.159 | 0.000 | 0.342 | 0.000 | 0.000 | -5.271 | 0.000 | -4.920 | -3.855 |
| T NW APARTMENT | 0.729 | -7.424 | 12.060 | -16.023 | 0.000 | 0.000 | 3.908 | 1.454 | 12.213 | 8.585 | 0.000 | 0.342 | 0.000 | 0.000 | -5.326 | 0.000 | -4.719 | -5.798 |
| T SE APARTMENT | 0.729 | -7.734 | 7.551 | -22.195 | 0.000 | 0.000 | 3.816 | 1.454 | 12.213 | 17.624 | 0.000 | 0.342 | 0.000 | 0.000 | -5.150 | 0.000 | -4.951 | -3.697 |
| T NE APARTMENT | 0.729 | -7.442 | 11.756 | -16.533 | 0.000 | 0.000 | 3.910 | 1.454 | 12.213 | 8.953 | 0.000 | 0.342 | 0.000 | 0.000 | -5.097 | 0.000 | -4.751 | -5.535 |
| T N1 APARTMENT | 0.729 | -7.443 | 8.432 | -12.499 | 0.000 | 0.000 | 3.900 | 1.454 | 12.213 | 2.806 | 0.000 | 0.207 | 0.000 | 0.000 | -3.324 | 0.000 | -3.185 | -3.291 |
| T N2 APARTMENT | 0.729 | -7.446 | 8.441 | -12.552 | 0.000 | 0.000 | 3.900 | 1.454 | 12.213 | 2.803 | 0.000 | 0.207 | 0.000 | 0.000 | -3.322 | 0.000 | -3.189 | -3.238 |
| T S1 APARTMENT | 0.729 | -7.803 | 4.436 | -18.116 | 0.000 | 0.000 | 3.789 | 1.454 | 12.213 | 11.496 | 0.000 | 0.207 | 0.000 | 0.000 | -3.233 | 0.000 | -3.371 | -1.801 |
| T S2 APARTMENT | 0.729 | -7.804 | 4.443 | -18.204 | 0.000 | 0.000 | 3.789 | 1.454 | 12.213 | 11.493 | 0.000 | 0.207 | 0.001 | 0.000 | -3.232 | 0.000 | -3.372 | -1.716 |
| T CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 6.080 | 11.688 | 0.000 | 1.508 | 0.000 | 0.027 | 0.000 | 0.000 | -0.542 | 0.000 | -0.743 | -18.018 |
| G CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 6.150 | 11.688 | 3.530 | 4.527 | 0.000 | 1.042 | 0.000 | 0.000 | -1.586 | 0.000 | -21.757 | -3.594 |
| M CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 11.412 | 23.376 | 0.000 | 2.980 | 0.000 | 0.050 | 0.000 | 0.000 | -1.171 | 0.000 | -1.232 | -35.415 |
| Total Facility | 22.594 | -240.937 | 126.402 | -495.917 | 0.000 | 0.000 | 143.550 | 99.229 | 391.594 | 334.052 | 0.000 | 7.756 | 20.227 | 0.000 | -144.882 | 0.000 | -126.832 | -136.834 |
| Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
| G SW APARTMENT | 21-SEP-16:01 | 0.00 | 176.71 | 0.00 | -2644.75 | 0.00 | 0.00 | 0.00 | 86.80 | 588.62 | 2113.32 | 0.00 | 28.05 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -348.76 |
| G NW APARTMENT | 04-JUL-17:30 | 0.00 | 306.69 | 0.00 | -2568.36 | 0.00 | 0.00 | 145.49 | 117.18 | 588.62 | 2037.69 | 0.00 | 146.21 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -773.52 |
| OFFICE | 10-OCT-07:01 | 0.00 | 0.00 | 0.00 | -7151.95 | 0.00 | 0.00 | 236.06 | 582.92 | 588.62 | 1326.45 | 0.00 | 0.00 | 4474.31 | 0.00 | -0.00 | 0.00 | -56.41 | 0.00 |
| G NE APARTMENT | 04-JUL-17:10 | 0.00 | 325.79 | 0.00 | -2172.18 | 0.00 | 0.00 | 145.49 | 117.18 | 588.62 | 667.38 | 0.00 | 169.64 | 158.07 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| G N1 APARTMENT | 04-JUL-17:40 | 0.00 | 297.21 | 0.00 | -1726.96 | 0.00 | 0.00 | 145.49 | 117.18 | 588.62 | 543.07 | 0.00 | 81.49 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -46.10 |
| G N2 APARTMENT | 04-JUL-17:40 | 0.00 | 297.21 | 0.00 | -1720.39 | 0.00 | 0.00 | 145.49 | 117.18 | 588.62 | 543.13 | 0.00 | 81.49 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -52.73 |
| G S1 APARTMENT | 21-SEP-15:10 | 0.00 | 176.74 | 0.00 | -2013.32 | 0.00 | 0.00 | 0.00 | 60.76 | 470.90 | 1113.08 | 0.00 | 13.78 | 178.07 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| G S2 APARTMENT | 03-SEP-13:30 | 0.00 | 228.53 | 0.00 | -2184.62 | 0.00 | 0.00 | 83.61 | 17.36 | 382.60 | 1664.19 | 0.00 | 29.90 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -221.57 |
| M SW APARTMENT | 20-SEP-16:17 | 0.00 | 363.65 | 0.00 | -6273.50 | 0.00 | 0.00 | 0.00 | 173.60 | 1177.25 | 4272.57 | 0.00 | 84.47 | 201.96 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| M NW APARTMENT | 04-JUL-17:30 | 0.00 | 613.21 | 0.00 | -6284.35 | 0.00 | 0.00 | 290.97 | 234.36 | 1177.25 | 4066.57 | 0.00 | 419.46 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -517.47 |
| M SE APARTMENT | 03-SEP-13:30 | 0.00 | 457.00 | 0.00 | -5682.26 | 0.00 | 0.00 | 167.23 | 34.72 | 765.21 | 3975.11 | 0.00 | 142.11 | 140.89 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| M NE APARTMENT | 29-JUN-15:10 | 0.00 | 742.35 | 0.00 | -5135.29 | 0.00 | 0.00 | 100.34 | 121.52 | 941.80 | 1822.35 | 0.00 | 429.80 | 977.15 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| M N1 APARTMENT | 04-JUL-18:00 | 0.00 | 556.00 | 0.00 | -3823.23 | 0.00 | 0.00 | 290.97 | 234.36 | 1177.25 | 1122.88 | 0.00 | 197.51 | 244.26 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| M N2 APARTMENT | 16-JUN-18:00 | 0.00 | 409.94 | 0.00 | -3656.20 | 0.00 | 0.00 | 290.97 | 234.36 | 1177.25 | 1199.33 | 0.00 | 163.21 | 181.14 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| M S1 APARTMENT | 21-SEP-14:10 | 0.00 | 379.64 | 0.00 | -4638.88 | 0.00 | 0.00 | 0.00 | 60.77 | 800.53 | 3077.10 | 0.00 | 49.23 | 271.62 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| M S2 APARTMENT | 21-SEP-14:10 | 0.00 | 379.64 | 0.00 | -4644.91 | 0.00 | 0.00 | 0.00 | 60.77 | 800.53 | 3077.03 | 0.00 | 49.23 | 277.72 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| T SW APARTMENT | 20-AUG-16:08 | 0.00 | 305.47 | 0.00 | -4426.66 | 0.00 | 0.00 | 167.23 | 86.80 | 588.62 | 1934.88 | 0.00 | 125.27 | 1218.40 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| T NW APARTMENT | 28-JUN-16:30 | 0.00 | 393.49 | 0.00 | -4300.86 | 0.00 | 0.00 | 86.96 | 86.80 | 588.62 | 2101.51 | 0.00 | 143.16 | 900.33 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| T SE APARTMENT | 03-SEP-13:30 | 0.00 | 228.48 | 0.00 | -3942.10 | 0.00 | 0.00 | 83.61 | 17.36 | 382.60 | 1958.92 | 0.00 | 93.52 | 1177.60 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| T NE APARTMENT | 29-JUN-15:10 | 0.00 | 371.16 | 0.00 | -3510.77 | 0.00 | 0.00 | 50.17 | 60.76 | 470.90 | 890.38 | 0.00 | 283.43 | 1383.98 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| T N1 APARTMENT | 29-JUN-15:10 | 0.00 | 371.26 | 0.00 | -2761.79 | 0.00 | 0.00 | 50.17 | 60.76 | 470.90 | 543.35 | 0.00 | 170.95 | 1094.40 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| T N2 APARTMENT | 29-JUN-15:10 | 0.00 | 371.26 | 0.00 | -2760.51 | 0.00 | 0.00 | 50.17 | 60.76 | 470.90 | 543.36 | 0.00 | 170.95 | 1093.11 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| T S1 APARTMENT | 03-SEP-13:30 | 0.00 | 228.49 | 0.00 | -3295.83 | 0.00 | 0.00 | 83.61 | 17.36 | 382.60 | 1645.77 | 0.00 | 56.41 | 881.59 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| T S2 APARTMENT | 03-SEP-13:30 | 0.00 | 228.49 | 0.00 | -3307.17 | 0.00 | 0.00 | 83.61 | 17.36 | 382.60 | 1645.64 | 0.00 | 56.41 | 893.06 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| T CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| G CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Total Facility | 04-JUL-17:00 | 0.00 | 10397.59 | 0.00 | -79040.41 | 0.00 | 0.00 | 4316.04 | 4289.87 | 18649.95 | 26625.49 | 0.00 | 9286.84 | 5474.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
| G SW APARTMENT | 18-JAN-01:50 | -585.56 | 0.00 | 1314.40 | 0.00 | 0.00 | 0.00 | 194.99 | 8.68 | 241.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -528.50 | 0.00 | -406.99 | -238.36 |
| G NW APARTMENT | 06-FEB-05:00 | -641.27 | 0.00 | 1776.35 | 0.00 | 0.00 | 0.00 | 194.99 | 26.04 | 223.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -587.92 | 0.00 | -357.85 | -634.03 |
| OFFICE | 07-FEB-08:61 | 0.00 | 0.00 | 9185.16 | 0.00 | 0.00 | 0.00 | 408.42 | 582.92 | 588.62 | 1750.67 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -106.99 | -12408.79 |
| G NE APARTMENT | 06-FEB-05:00 | -641.27 | 0.00 | 1785.56 | 0.00 | 0.00 | 0.00 | 194.99 | 26.04 | 223.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -587.68 | 0.00 | -357.85 | -643.47 |
| G N1 APARTMENT | 06-FEB-05:00 | -641.36 | 0.00 | 1227.71 | 0.00 | 0.00 | 0.00 | 194.99 | 26.04 | 223.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -359.79 | 0.00 | -215.85 | -455.43 |
| G N2 APARTMENT | 06-FEB-05:00 | -641.36 | 0.00 | 1228.09 | 0.00 | 0.00 | 0.00 | 194.99 | 26.04 | 223.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -359.78 | 0.00 | -215.85 | -455.81 |
| G S1 APARTMENT | 18-JAN-01:50 | -585.65 | 0.00 | 817.97 | 0.00 | 0.00 | 0.00 | 194.99 | 8.68 | 241.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -329.07 | 0.00 | -245.49 | -102.76 |
| G S2 APARTMENT | 18-JAN-02:00 | -585.63 | 0.00 | 854.91 | 0.00 | 0.00 | 0.00 | 194.99 | 8.68 | 241.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -327.81 | 0.00 | -243.18 | -143.30 |
| M SW APARTMENT | 18-JAN-01:10 | -1171.18 | 0.00 | 2732.05 | 0.00 | 0.00 | 0.00 | 389.98 | 17.37 | 482.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1086.90 | 0.00 | -1214.69 | -149.30 |
| M NW APARTMENT | 14-DEC-04:00 | -1110.95 | 0.00 | 3273.70 | 0.00 | 0.00 | 0.00 | 389.98 | 17.37 | 447.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1088.63 | 0.00 | -1831.94 | -96.89 |
| M SE APARTMENT | 18-JAN-01:10 | -1171.18 | 0.00 | 2750.25 | 0.00 | 0.00 | 0.00 | 389.98 | 17.37 | 482.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1100.56 | 0.00 | -1214.69 | -153.85 |
| M NE APARTMENT | 14-DEC-04:00 | -1110.95 | 0.00 | 3325.57 | 0.00 | 0.00 | 0.00 | 389.98 | 17.37 | 447.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1073.99 | 0.00 | -1831.94 | -163.39 |
| M N1 APARTMENT | 14-DEC-04:00 | -1111.22 | 0.00 | 2080.71 | 0.00 | 0.00 | 0.00 | 389.98 | 17.37 | 447.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -663.80 | 0.00 | -1104.98 | -55.41 |
| M N2 APARTMENT | 14-DEC-04:00 | -1111.22 | 0.00 | 2081.97 | 0.00 | 0.00 | 0.00 | 389.98 | 17.37 | 447.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -663.73 | 0.00 | -1104.98 | -56.74 |
| M S1 APARTMENT | 18-JAN-02:00 | -1171.12 | 0.00 | 1584.63 | 0.00 | 0.00 | 0.00 | 389.98 | 17.37 | 482.67 | 0.00 | 0.00 | 0.00 | 66.63 | 0.00 | -670.62 | 0.00 | -699.55 | 0.00 |
| M S2 APARTMENT | 18-JAN-02:00 | -1171.12 | 0.00 | 1585.14 | 0.00 | 0.00 | 0.00 | 389.98 | 17.37 | 482.67 | 0.00 | 0.00 | 0.00 | 66.12 | 0.00 | -670.62 | 0.00 | -699.55 | 0.00 |
| T SW APARTMENT | 06-FEB-05:00 | -641.13 | 0.00 | 2675.88 | 0.00 | 0.00 | 0.00 | 194.99 | 26.04 | 223.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -577.94 | 0.00 | -681.86 | -1219.66 |
| T NW APARTMENT | 14-DEC-04:00 | -555.41 | 0.00 | 2736.21 | 0.00 | 0.00 | 0.00 | 194.99 | 8.68 | 223.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -526.21 | 0.00 | -1213.81 | -868.13 |
| T SE APARTMENT | 06-FEB-05:00 | -641.13 | 0.00 | 2683.10 | 0.00 | 0.00 | 0.00 | 194.99 | 26.04 | 223.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -577.78 | 0.00 | -681.86 | -1227.04 |
| T NE APARTMENT | 14-DEC-04:00 | -555.41 | 0.00 | 2765.26 | 0.00 | 0.00 | 0.00 | 194.99 | 8.68 | 223.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -519.16 | 0.00 | -1213.81 | -904.23 |
| T N1 APARTMENT | 06-FEB-05:00 | -641.24 | 0.00 | 2028.91 | 0.00 | 0.00 | 0.00 | 194.99 | 26.04 | 223.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -358.32 | 0.00 | -411.28 | -1062.78 |
| T N2 APARTMENT | 06-FEB-05:00 | -641.24 | 0.00 | 2029.48 | 0.00 | 0.00 | 0.00 | 194.99 | 26.04 | 223.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -358.31 | 0.00 | -411.28 | -1063.35 |
| T S1 APARTMENT | 06-FEB-05:00 | -641.24 | 0.00 | 1869.06 | 0.00 | 0.00 | 0.00 | 194.99 | 26.04 | 223.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -350.59 | 0.00 | -411.28 | -910.66 |
| T S2 APARTMENT | 06-FEB-05:00 | -641.24 | 0.00 | 1869.07 | 0.00 | 0.00 | 0.00 | 194.99 | 26.04 | 223.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -350.59 | 0.00 | -411.28 | -910.67 |
| T CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| G CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Total Facility | 17-JAN-08:61 | -19350.03 | 0.00 | 51240.89 | 0.00 | 0.00 | 0.00 | 2169.67 | 2872.71 | 12840.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -11019.85 | 0.00 | -17513.74 | -21239.90 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 09:14:27
System Ventilation Requirements for Cooling| Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
| SPLIT GSW | 0.4156 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.4156 | 0.0625 | 1.0000 | Not calculated | 0.0260 | 0.0625 | ||
| SPLIT GNW | 0.4078 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.4078 | 0.0636 | 1.0000 | Not calculated | 0.0260 | 0.0636 | ||
| SPLIT OFFICE | 0.4704 | 0.0000 | 4.7495 | 1.0000 | Calculated from schedules | 0.0381 | 0.4704 | 0.0810 | 1.0000 | Not calculated | 0.0381 | 0.0810 | ||
| SPLIT GNE | 0.3724 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.3724 | 0.0697 | 1.0000 | Not calculated | 0.0260 | 0.0697 | ||
| SPLIT GN1 | 0.3320 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.3320 | 0.0782 | 1.0000 | Not calculated | 0.0260 | 0.0782 | ||
| SPLIT GN2 | 0.3313 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.3313 | 0.0783 | 1.0000 | Not calculated | 0.0260 | 0.0783 | ||
| SPLIT GS1 | 0.3422 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.3422 | 0.0759 | 1.0000 | Not calculated | 0.0260 | 0.0759 | ||
| SPLIT GS2 | 0.3446 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.3446 | 0.0753 | 1.0000 | Not calculated | 0.0260 | 0.0753 | ||
| SPLIT MSW | 1.0030 | 0.0000 | 5.0000 | 1.0000 | Calculated from schedules | 0.0519 | 1.0030 | 0.0518 | 1.0000 | Not calculated | 0.0519 | 0.0518 | ||
| SPLIT MNW | 0.9939 | 0.0000 | 5.0000 | 1.0000 | Calculated from schedules | 0.0519 | 0.9939 | 0.0522 | 1.0000 | Not calculated | 0.0519 | 0.0522 | ||
| SPLIT MSE | 0.8993 | 0.0000 | 5.0000 | 1.0000 | Calculated from schedules | 0.0519 | 0.8993 | 0.0577 | 1.0000 | Not calculated | 0.0519 | 0.0577 | ||
| SPLIT MNE | 0.8907 | 0.0000 | 5.0000 | 1.0000 | Calculated from schedules | 0.0519 | 0.8907 | 0.0583 | 1.0000 | Not calculated | 0.0519 | 0.0583 | ||
| SPLIT MN1 | 0.7917 | 0.0000 | 5.0000 | 1.0000 | Calculated from schedules | 0.0519 | 0.7917 | 0.0656 | 1.0000 | Not calculated | 0.0519 | 0.0656 | ||
| SPLIT MN2 | 0.7896 | 0.0000 | 5.0000 | 1.0000 | Calculated from schedules | 0.0519 | 0.7896 | 0.0657 | 1.0000 | Not calculated | 0.0519 | 0.0657 | ||
| SPLIT MS1 | 0.8044 | 0.0000 | 5.0000 | 1.0000 | Calculated from schedules | 0.0519 | 0.8044 | 0.0645 | 1.0000 | Not calculated | 0.0519 | 0.0645 | ||
| SPLIT MS2 | 0.8023 | 0.0000 | 5.0000 | 1.0000 | Calculated from schedules | 0.0519 | 0.8023 | 0.0647 | 1.0000 | Not calculated | 0.0519 | 0.0647 | ||
| SPLIT TSW | 0.5594 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.5594 | 0.0464 | 1.0000 | Not calculated | 0.0260 | 0.0464 | ||
| SPLIT TNW | 0.5643 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.5643 | 0.0460 | 1.0000 | Not calculated | 0.0260 | 0.0460 | ||
| SPLIT TSE | 0.4828 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.4828 | 0.0538 | 1.0000 | Not calculated | 0.0260 | 0.0538 | ||
| SPLIT TNE | 0.4875 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.4875 | 0.0532 | 1.0000 | Not calculated | 0.0260 | 0.0532 | ||
| SPLIT TN1 | 0.4521 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.4521 | 0.0574 | 1.0000 | Not calculated | 0.0260 | 0.0574 | ||
| SPLIT TN2 | 0.4495 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.4495 | 0.0577 | 1.0000 | Not calculated | 0.0260 | 0.0577 | ||
| SPLIT TS1 | 0.4482 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.4482 | 0.0579 | 1.0000 | Not calculated | 0.0260 | 0.0579 | ||
| SPLIT TS2 | 0.4456 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.4456 | 0.0582 | 1.0000 | Not calculated | 0.0260 | 0.0582 |
| Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
| SPLIT GSW | 0.4156 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.4156 | 1.0000 | 1.0000 | Not calculated | 0.0260 | 0.0625 | ||
| SPLIT GNW | 0.4078 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.4078 | 1.0000 | 1.0000 | Not calculated | 0.0260 | 0.0636 | ||
| SPLIT OFFICE | 0.4704 | 0.0000 | 4.7495 | 1.0000 | Calculated from schedules | 0.0381 | 0.4704 | 1.0000 | 1.0000 | Not calculated | 0.0381 | 0.0810 | ||
| SPLIT GNE | 0.3724 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.3724 | 1.0000 | 1.0000 | Not calculated | 0.0260 | 0.0697 | ||
| SPLIT GN1 | 0.3320 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.3320 | 1.0000 | 1.0000 | Not calculated | 0.0260 | 0.0782 | ||
| SPLIT GN2 | 0.3313 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.3313 | 1.0000 | 1.0000 | Not calculated | 0.0260 | 0.0783 | ||
| SPLIT GS1 | 0.3422 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.3422 | 1.0000 | 1.0000 | Not calculated | 0.0260 | 0.0759 | ||
| SPLIT GS2 | 0.3446 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.3446 | 1.0000 | 1.0000 | Not calculated | 0.0260 | 0.0753 | ||
| SPLIT MSW | 1.0030 | 0.0000 | 5.0000 | 1.0000 | Calculated from schedules | 0.0519 | 1.0030 | 1.0000 | 1.0000 | Not calculated | 0.0519 | 0.0518 | ||
| SPLIT MNW | 0.9939 | 0.0000 | 5.0000 | 1.0000 | Calculated from schedules | 0.0519 | 0.9939 | 1.0000 | 1.0000 | Not calculated | 0.0519 | 0.0522 | ||
| SPLIT MSE | 0.8993 | 0.0000 | 5.0000 | 1.0000 | Calculated from schedules | 0.0519 | 0.8993 | 1.0000 | 1.0000 | Not calculated | 0.0519 | 0.0577 | ||
| SPLIT MNE | 0.8907 | 0.0000 | 5.0000 | 1.0000 | Calculated from schedules | 0.0519 | 0.8907 | 1.0000 | 1.0000 | Not calculated | 0.0519 | 0.0583 | ||
| SPLIT MN1 | 0.7917 | 0.0000 | 5.0000 | 1.0000 | Calculated from schedules | 0.0519 | 0.7917 | 1.0000 | 1.0000 | Not calculated | 0.0519 | 0.0656 | ||
| SPLIT MN2 | 0.7896 | 0.0000 | 5.0000 | 1.0000 | Calculated from schedules | 0.0519 | 0.7896 | 1.0000 | 1.0000 | Not calculated | 0.0519 | 0.0657 | ||
| SPLIT MS1 | 0.8044 | 0.0000 | 5.0000 | 1.0000 | Calculated from schedules | 0.0519 | 0.8044 | 1.0000 | 1.0000 | Not calculated | 0.0519 | 0.0645 | ||
| SPLIT MS2 | 0.8023 | 0.0000 | 5.0000 | 1.0000 | Calculated from schedules | 0.0519 | 0.8023 | 1.0000 | 1.0000 | Not calculated | 0.0519 | 0.0647 | ||
| SPLIT TSW | 0.5594 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.5594 | 1.0000 | 1.0000 | Not calculated | 0.0260 | 0.0464 | ||
| SPLIT TNW | 0.5643 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.5643 | 1.0000 | 1.0000 | Not calculated | 0.0260 | 0.0460 | ||
| SPLIT TSE | 0.4828 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.4828 | 1.0000 | 1.0000 | Not calculated | 0.0260 | 0.0538 | ||
| SPLIT TNE | 0.4875 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.4875 | 1.0000 | 1.0000 | Not calculated | 0.0260 | 0.0532 | ||
| SPLIT TN1 | 0.4521 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.4521 | 1.0000 | 1.0000 | Not calculated | 0.0260 | 0.0574 | ||
| SPLIT TN2 | 0.4495 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.4495 | 1.0000 | 1.0000 | Not calculated | 0.0260 | 0.0577 | ||
| SPLIT TS1 | 0.4482 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.4482 | 1.0000 | 1.0000 | Not calculated | 0.0260 | 0.0579 | ||
| SPLIT TS2 | 0.4456 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.4456 | 1.0000 | 1.0000 | Not calculated | 0.0260 | 0.0582 |
| AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
| G SW APARTMENT | SPLIT GSW | 0.000000 | 2.5000 | 0.000294 | 88.25 | 0.0260 | 1.0000 | 0.0260 | 1.000 | 0.0260 |
| G NW APARTMENT | SPLIT GNW | 0.000000 | 2.5000 | 0.000294 | 88.25 | 0.0260 | 1.0000 | 0.0260 | 1.000 | 0.0260 |
| OFFICE | SPLIT OFFICE | 0.000000 | 4.7495 | 0.000432 | 88.25 | 0.0381 | 1.0000 | 0.0381 | 1.000 | 0.0381 |
| G NE APARTMENT | SPLIT GNE | 0.000000 | 2.5000 | 0.000294 | 88.25 | 0.0260 | 1.0000 | 0.0260 | 1.000 | 0.0260 |
| G N1 APARTMENT | SPLIT GN1 | 0.000000 | 2.5000 | 0.000294 | 88.25 | 0.0260 | 1.0000 | 0.0260 | 1.000 | 0.0260 |
| G N2 APARTMENT | SPLIT GN2 | 0.000000 | 2.5000 | 0.000294 | 88.25 | 0.0260 | 1.0000 | 0.0260 | 1.000 | 0.0260 |
| G S1 APARTMENT | SPLIT GS1 | 0.000000 | 2.5000 | 0.000294 | 88.25 | 0.0260 | 1.0000 | 0.0260 | 1.000 | 0.0260 |
| G S2 APARTMENT | SPLIT GS2 | 0.000000 | 2.5000 | 0.000294 | 88.25 | 0.0260 | 1.0000 | 0.0260 | 1.000 | 0.0260 |
| M SW APARTMENT | SPLIT MSW | 0.000000 | 5.0000 | 0.000294 | 176.50 | 0.0519 | 1.0000 | 0.0519 | 1.000 | 0.0519 |
| M NW APARTMENT | SPLIT MNW | 0.000000 | 5.0000 | 0.000294 | 176.50 | 0.0519 | 1.0000 | 0.0519 | 1.000 | 0.0519 |
| M SE APARTMENT | SPLIT MSE | 0.000000 | 5.0000 | 0.000294 | 176.50 | 0.0519 | 1.0000 | 0.0519 | 1.000 | 0.0519 |
| M NE APARTMENT | SPLIT MNE | 0.000000 | 5.0000 | 0.000294 | 176.50 | 0.0519 | 1.0000 | 0.0519 | 1.000 | 0.0519 |
| M N1 APARTMENT | SPLIT MN1 | 0.000000 | 5.0000 | 0.000294 | 176.50 | 0.0519 | 1.0000 | 0.0519 | 1.000 | 0.0519 |
| M N2 APARTMENT | SPLIT MN2 | 0.000000 | 5.0000 | 0.000294 | 176.50 | 0.0519 | 1.0000 | 0.0519 | 1.000 | 0.0519 |
| M S1 APARTMENT | SPLIT MS1 | 0.000000 | 5.0000 | 0.000294 | 176.50 | 0.0519 | 1.0000 | 0.0519 | 1.000 | 0.0519 |
| M S2 APARTMENT | SPLIT MS2 | 0.000000 | 5.0000 | 0.000294 | 176.50 | 0.0519 | 1.0000 | 0.0519 | 1.000 | 0.0519 |
| T SW APARTMENT | SPLIT TSW | 0.000000 | 2.5000 | 0.000294 | 88.25 | 0.0260 | 1.0000 | 0.0260 | 1.000 | 0.0260 |
| T NW APARTMENT | SPLIT TNW | 0.000000 | 2.5000 | 0.000294 | 88.25 | 0.0260 | 1.0000 | 0.0260 | 1.000 | 0.0260 |
| T SE APARTMENT | SPLIT TSE | 0.000000 | 2.5000 | 0.000294 | 88.25 | 0.0260 | 1.0000 | 0.0260 | 1.000 | 0.0260 |
| T NE APARTMENT | SPLIT TNE | 0.000000 | 2.5000 | 0.000294 | 88.25 | 0.0260 | 1.0000 | 0.0260 | 1.000 | 0.0260 |
| T N1 APARTMENT | SPLIT TN1 | 0.000000 | 2.5000 | 0.000294 | 88.25 | 0.0260 | 1.0000 | 0.0260 | 1.000 | 0.0260 |
| T N2 APARTMENT | SPLIT TN2 | 0.000000 | 2.5000 | 0.000294 | 88.25 | 0.0260 | 1.0000 | 0.0260 | 1.000 | 0.0260 |
| T S1 APARTMENT | SPLIT TS1 | 0.000000 | 2.5000 | 0.000294 | 88.25 | 0.0260 | 1.0000 | 0.0260 | 1.000 | 0.0260 |
| T S2 APARTMENT | SPLIT TS2 | 0.000000 | 2.5000 | 0.000294 | 88.25 | 0.0260 | 1.0000 | 0.0260 | 1.000 | 0.0260 |
| People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
| SPLIT GSW | 0.000000 | 2.50 | 0.000294 | 88.2493 | 0.0260 | 0.0260 | 0.0260 |
| SPLIT GNW | 0.000000 | 2.50 | 0.000294 | 88.2493 | 0.0260 | 0.0260 | 0.0260 |
| SPLIT OFFICE | 0.000000 | 4.75 | 0.000432 | 88.2493 | 0.0381 | 0.0381 | 0.0381 |
| SPLIT GNE | 0.000000 | 2.50 | 0.000294 | 88.2493 | 0.0260 | 0.0260 | 0.0260 |
| SPLIT GN1 | 0.000000 | 2.50 | 0.000294 | 88.2493 | 0.0260 | 0.0260 | 0.0260 |
| SPLIT GN2 | 0.000000 | 2.50 | 0.000294 | 88.2493 | 0.0260 | 0.0260 | 0.0260 |
| SPLIT GS1 | 0.000000 | 2.50 | 0.000294 | 88.2493 | 0.0260 | 0.0260 | 0.0260 |
| SPLIT GS2 | 0.000000 | 2.50 | 0.000294 | 88.2493 | 0.0260 | 0.0260 | 0.0260 |
| SPLIT MSW | 0.000000 | 5.00 | 0.000294 | 176.4985 | 0.0519 | 0.0519 | 0.0519 |
| SPLIT MNW | 0.000000 | 5.00 | 0.000294 | 176.4985 | 0.0519 | 0.0519 | 0.0519 |
| SPLIT MSE | 0.000000 | 5.00 | 0.000294 | 176.4985 | 0.0519 | 0.0519 | 0.0519 |
| SPLIT MNE | 0.000000 | 5.00 | 0.000294 | 176.4985 | 0.0519 | 0.0519 | 0.0519 |
| SPLIT MN1 | 0.000000 | 5.00 | 0.000294 | 176.4985 | 0.0519 | 0.0519 | 0.0519 |
| SPLIT MN2 | 0.000000 | 5.00 | 0.000294 | 176.4985 | 0.0519 | 0.0519 | 0.0519 |
| SPLIT MS1 | 0.000000 | 5.00 | 0.000294 | 176.4985 | 0.0519 | 0.0519 | 0.0519 |
| SPLIT MS2 | 0.000000 | 5.00 | 0.000294 | 176.4985 | 0.0519 | 0.0519 | 0.0519 |
| SPLIT TSW | 0.000000 | 2.50 | 0.000294 | 88.2493 | 0.0260 | 0.0260 | 0.0260 |
| SPLIT TNW | 0.000000 | 2.50 | 0.000294 | 88.2493 | 0.0260 | 0.0260 | 0.0260 |
| SPLIT TSE | 0.000000 | 2.50 | 0.000294 | 88.2493 | 0.0260 | 0.0260 | 0.0260 |
| SPLIT TNE | 0.000000 | 2.50 | 0.000294 | 88.2493 | 0.0260 | 0.0260 | 0.0260 |
| SPLIT TN1 | 0.000000 | 2.50 | 0.000294 | 88.2493 | 0.0260 | 0.0260 | 0.0260 |
| SPLIT TN2 | 0.000000 | 2.50 | 0.000294 | 88.2493 | 0.0260 | 0.0260 | 0.0260 |
| SPLIT TS1 | 0.000000 | 2.50 | 0.000294 | 88.2493 | 0.0260 | 0.0260 | 0.0260 |
| SPLIT TS2 | 0.000000 | 2.50 | 0.000294 | 88.2493 | 0.0260 | 0.0260 | 0.0260 |
| AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
| G SW APARTMENT | SPLIT GSW | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4156 | 0.4156 | 0.4156 | No | 0.0260 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| G NW APARTMENT | SPLIT GNW | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4078 | 0.4078 | 0.4078 | No | 0.0260 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| OFFICE | SPLIT OFFICE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4704 | 0.4704 | 0.4704 | No | 0.0381 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| G NE APARTMENT | SPLIT GNE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.3724 | 0.3724 | 0.3724 | No | 0.0260 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| G N1 APARTMENT | SPLIT GN1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.3320 | 0.3320 | 0.3320 | No | 0.0260 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| G N2 APARTMENT | SPLIT GN2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.3313 | 0.3313 | 0.3313 | No | 0.0260 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| G S1 APARTMENT | SPLIT GS1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.3422 | 0.3422 | 0.3422 | No | 0.0260 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| G S2 APARTMENT | SPLIT GS2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.3446 | 0.3446 | 0.3446 | No | 0.0260 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| M SW APARTMENT | SPLIT MSW | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0030 | 1.0030 | 1.0030 | No | 0.0519 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| M NW APARTMENT | SPLIT MNW | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9939 | 0.9939 | 0.9939 | No | 0.0519 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| M SE APARTMENT | SPLIT MSE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8993 | 0.8993 | 0.8993 | No | 0.0519 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| M NE APARTMENT | SPLIT MNE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8907 | 0.8907 | 0.8907 | No | 0.0519 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| M N1 APARTMENT | SPLIT MN1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.7917 | 0.7917 | 0.7917 | No | 0.0519 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| M N2 APARTMENT | SPLIT MN2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.7896 | 0.7896 | 0.7896 | No | 0.0519 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| M S1 APARTMENT | SPLIT MS1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8044 | 0.8044 | 0.8044 | No | 0.0519 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| M S2 APARTMENT | SPLIT MS2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8023 | 0.8023 | 0.8023 | No | 0.0519 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| T SW APARTMENT | SPLIT TSW | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.5594 | 0.5594 | 0.5594 | No | 0.0260 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| T NW APARTMENT | SPLIT TNW | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.5643 | 0.5643 | 0.5643 | No | 0.0260 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| T SE APARTMENT | SPLIT TSE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4828 | 0.4828 | 0.4828 | No | 0.0260 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| T NE APARTMENT | SPLIT TNE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4875 | 0.4875 | 0.4875 | No | 0.0260 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| T N1 APARTMENT | SPLIT TN1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4521 | 0.4521 | 0.4521 | No | 0.0260 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| T N2 APARTMENT | SPLIT TN2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4495 | 0.4495 | 0.4495 | No | 0.0260 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| T S1 APARTMENT | SPLIT TS1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4482 | 0.4482 | 0.4482 | No | 0.0260 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| T S2 APARTMENT | SPLIT TS2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4456 | 0.4456 | 0.4456 | No | 0.0260 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
| SPLIT GSW | 0.4156 | 0.4156 | 0.4156 | 0.4156 | 0.0260 | 1.0000 |
| SPLIT GNW | 0.4078 | 0.4078 | 0.4078 | 0.4078 | 0.0260 | 1.0000 |
| SPLIT OFFICE | 0.4704 | 0.4704 | 0.4704 | 0.4704 | 0.0381 | 1.0000 |
| SPLIT GNE | 0.3724 | 0.3724 | 0.3724 | 0.3724 | 0.0260 | 1.0000 |
| SPLIT GN1 | 0.3320 | 0.3320 | 0.3320 | 0.3320 | 0.0260 | 1.0000 |
| SPLIT GN2 | 0.3313 | 0.3313 | 0.3313 | 0.3313 | 0.0260 | 1.0000 |
| SPLIT GS1 | 0.3422 | 0.3422 | 0.3422 | 0.3422 | 0.0260 | 1.0000 |
| SPLIT GS2 | 0.3446 | 0.3446 | 0.3446 | 0.3446 | 0.0260 | 1.0000 |
| SPLIT MSW | 1.0030 | 1.0030 | 1.0030 | 1.0030 | 0.0519 | 1.0000 |
| SPLIT MNW | 0.9939 | 0.9939 | 0.9939 | 0.9939 | 0.0519 | 1.0000 |
| SPLIT MSE | 0.8993 | 0.8993 | 0.8993 | 0.8993 | 0.0519 | 1.0000 |
| SPLIT MNE | 0.8907 | 0.8907 | 0.8907 | 0.8907 | 0.0519 | 1.0000 |
| SPLIT MN1 | 0.7917 | 0.7917 | 0.7917 | 0.7917 | 0.0519 | 1.0000 |
| SPLIT MN2 | 0.7896 | 0.7896 | 0.7896 | 0.7896 | 0.0519 | 1.0000 |
| SPLIT MS1 | 0.8044 | 0.8044 | 0.8044 | 0.8044 | 0.0519 | 1.0000 |
| SPLIT MS2 | 0.8023 | 0.8023 | 0.8023 | 0.8023 | 0.0519 | 1.0000 |
| SPLIT TSW | 0.5594 | 0.5594 | 0.5594 | 0.5594 | 0.0260 | 1.0000 |
| SPLIT TNW | 0.5643 | 0.5643 | 0.5643 | 0.5643 | 0.0260 | 1.0000 |
| SPLIT TSE | 0.4828 | 0.4828 | 0.4828 | 0.4828 | 0.0260 | 1.0000 |
| SPLIT TNE | 0.4875 | 0.4875 | 0.4875 | 0.4875 | 0.0260 | 1.0000 |
| SPLIT TN1 | 0.4521 | 0.4521 | 0.4521 | 0.4521 | 0.0260 | 1.0000 |
| SPLIT TN2 | 0.4495 | 0.4495 | 0.4495 | 0.4495 | 0.0260 | 1.0000 |
| SPLIT TS1 | 0.4482 | 0.4482 | 0.4482 | 0.4482 | 0.0260 | 1.0000 |
| SPLIT TS2 | 0.4456 | 0.4456 | 0.4456 | 0.4456 | 0.0260 | 1.0000 |
| AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
| G SW APARTMENT | SPLIT GSW | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4156 | 0.4156 | 0.4156 | No | 0.0260 | 0.2771 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| G NW APARTMENT | SPLIT GNW | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4078 | 0.4078 | 0.4078 | No | 0.0260 | 0.2999 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| OFFICE | SPLIT OFFICE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4704 | 0.4704 | 0.4704 | No | 0.0381 | 0.3139 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| G NE APARTMENT | SPLIT GNE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.3724 | 0.3724 | 0.3724 | No | 0.0260 | 0.2999 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| G N1 APARTMENT | SPLIT GN1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.3320 | 0.3320 | 0.3320 | No | 0.0260 | 0.5175 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| G N2 APARTMENT | SPLIT GN2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.3313 | 0.3313 | 0.3313 | No | 0.0260 | 0.5175 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| G S1 APARTMENT | SPLIT GS1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.3422 | 0.3422 | 0.3422 | No | 0.0260 | 0.4525 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| G S2 APARTMENT | SPLIT GS2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.3446 | 0.3446 | 0.3446 | No | 0.0260 | 0.4483 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| M SW APARTMENT | SPLIT MSW | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0030 | 1.0030 | 1.0030 | No | 0.0519 | 0.2938 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| M NW APARTMENT | SPLIT MNW | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9939 | 0.9939 | 0.9939 | No | 0.0519 | 0.3252 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| M SE APARTMENT | SPLIT MSE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8993 | 0.8993 | 0.8993 | No | 0.0519 | 0.2938 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| M NE APARTMENT | SPLIT MNE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8907 | 0.8907 | 0.8907 | No | 0.0519 | 0.3252 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| M N1 APARTMENT | SPLIT MN1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.7917 | 0.7917 | 0.7917 | No | 0.0519 | 0.6557 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| M N2 APARTMENT | SPLIT MN2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.7896 | 0.7896 | 0.7896 | No | 0.0519 | 0.6557 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| M S1 APARTMENT | SPLIT MS1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8044 | 0.8044 | 0.8044 | No | 0.0519 | 0.5417 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| M S2 APARTMENT | SPLIT MS2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8023 | 0.8023 | 0.8023 | No | 0.0519 | 0.5417 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| T SW APARTMENT | SPLIT TSW | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.5594 | 0.5594 | 0.5594 | No | 0.0260 | 0.1657 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| T NW APARTMENT | SPLIT TNW | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.5643 | 0.5643 | 0.5643 | No | 0.0260 | 0.1758 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| T SE APARTMENT | SPLIT TSE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4828 | 0.4828 | 0.4828 | No | 0.0260 | 0.1657 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| T NE APARTMENT | SPLIT TNE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4875 | 0.4875 | 0.4875 | No | 0.0260 | 0.1758 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| T N1 APARTMENT | SPLIT TN1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4521 | 0.4521 | 0.4521 | No | 0.0260 | 0.2592 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| T N2 APARTMENT | SPLIT TN2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4495 | 0.4495 | 0.4495 | No | 0.0260 | 0.2592 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| T S1 APARTMENT | SPLIT TS1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4482 | 0.4482 | 0.4482 | No | 0.0260 | 0.2379 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| T S2 APARTMENT | SPLIT TS2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4456 | 0.4456 | 0.4456 | No | 0.0260 | 0.2379 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
| SPLIT GSW | 0.4156 | 0.4156 | 0.4156 | 0.4156 | 0.0260 | 1.0000 |
| SPLIT GNW | 0.4078 | 0.4078 | 0.4078 | 0.4078 | 0.0260 | 1.0000 |
| SPLIT OFFICE | 0.4704 | 0.4704 | 0.4704 | 0.4704 | 0.0381 | 1.0000 |
| SPLIT GNE | 0.3724 | 0.3724 | 0.3724 | 0.3724 | 0.0260 | 1.0000 |
| SPLIT GN1 | 0.3320 | 0.3320 | 0.3320 | 0.3320 | 0.0260 | 1.0000 |
| SPLIT GN2 | 0.3313 | 0.3313 | 0.3313 | 0.3313 | 0.0260 | 1.0000 |
| SPLIT GS1 | 0.3422 | 0.3422 | 0.3422 | 0.3422 | 0.0260 | 1.0000 |
| SPLIT GS2 | 0.3446 | 0.3446 | 0.3446 | 0.3446 | 0.0260 | 1.0000 |
| SPLIT MSW | 1.0030 | 1.0030 | 1.0030 | 1.0030 | 0.0519 | 1.0000 |
| SPLIT MNW | 0.9939 | 0.9939 | 0.9939 | 0.9939 | 0.0519 | 1.0000 |
| SPLIT MSE | 0.8993 | 0.8993 | 0.8993 | 0.8993 | 0.0519 | 1.0000 |
| SPLIT MNE | 0.8907 | 0.8907 | 0.8907 | 0.8907 | 0.0519 | 1.0000 |
| SPLIT MN1 | 0.7917 | 0.7917 | 0.7917 | 0.7917 | 0.0519 | 1.0000 |
| SPLIT MN2 | 0.7896 | 0.7896 | 0.7896 | 0.7896 | 0.0519 | 1.0000 |
| SPLIT MS1 | 0.8044 | 0.8044 | 0.8044 | 0.8044 | 0.0519 | 1.0000 |
| SPLIT MS2 | 0.8023 | 0.8023 | 0.8023 | 0.8023 | 0.0519 | 1.0000 |
| SPLIT TSW | 0.5594 | 0.5594 | 0.5594 | 0.5594 | 0.0260 | 1.0000 |
| SPLIT TNW | 0.5643 | 0.5643 | 0.5643 | 0.5643 | 0.0260 | 1.0000 |
| SPLIT TSE | 0.4828 | 0.4828 | 0.4828 | 0.4828 | 0.0260 | 1.0000 |
| SPLIT TNE | 0.4875 | 0.4875 | 0.4875 | 0.4875 | 0.0260 | 1.0000 |
| SPLIT TN1 | 0.4521 | 0.4521 | 0.4521 | 0.4521 | 0.0260 | 1.0000 |
| SPLIT TN2 | 0.4495 | 0.4495 | 0.4495 | 0.4495 | 0.0260 | 1.0000 |
| SPLIT TS1 | 0.4482 | 0.4482 | 0.4482 | 0.4482 | 0.0260 | 1.0000 |
| SPLIT TS2 | 0.4456 | 0.4456 | 0.4456 | 0.4456 | 0.0260 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 09:14:27
Sec1.1A-General Information| Data | |
| Weather File | RUNPERIOD 1 ** Albuquerque Intl Sunport NM USA TMY3 WMO#=723650 |
| Total gross floor area [m2] | 3134.61 |
| Principal Heating Source | Natural Gas |
| Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
| G SW APARTMENT | 88.25 | 88.25 | 0.00 | 117.85 |
| G NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
| OFFICE | 88.25 | 88.25 | 0.00 | 33.56 |
| G NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
| G N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
| G N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
| G S1 APARTMENT | 88.25 | 88.25 | 0.00 | 117.85 |
| G S2 APARTMENT | 88.25 | 88.25 | 0.00 | 117.85 |
| M SW APARTMENT | 88.25 | 88.25 | 0.00 | 117.85 |
| M NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
| M SE APARTMENT | 88.25 | 88.25 | 0.00 | 117.85 |
| M NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
| M N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
| M N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
| M S1 APARTMENT | 88.25 | 88.25 | 0.00 | 117.85 |
| M S2 APARTMENT | 88.25 | 88.25 | 0.00 | 117.85 |
| T SW APARTMENT | 88.25 | 88.25 | 0.00 | 117.85 |
| T NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
| T SE APARTMENT | 88.25 | 88.25 | 0.00 | 117.85 |
| T NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
| T N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
| T N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
| T S1 APARTMENT | 88.25 | 88.25 | 0.00 | 117.85 |
| T S2 APARTMENT | 88.25 | 88.25 | 0.00 | 117.85 |
| T CORRIDOR | 77.66 | 0.00 | 77.66 | 168.00 |
| G CORRIDOR | 77.66 | 0.00 | 77.66 | 168.00 |
| M CORRIDOR | 77.66 | 0.00 | 77.66 | 168.00 |
| Totals | 3134.61 | 2823.98 | 310.64 |
| Data | |
| Number of hours heating loads not met | 0.00 |
| Number of hours cooling loads not met | 0.00 |
| Number of hours not met | 0.00 |
| Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
| None |
| Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
| Heating -- General | 0.00 | 0.00 | 146.93 | 54300.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Cooling -- General | 151.23 | 27057.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Lighting -- LightsWired | 94.96 | 5496.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Lighting -- LightsPlugIn | 4.27 | 407.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Lighting -- General | 50.02 | 3183.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment -- MiscPlug | 388.06 | 18541.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment -- ElevatorLift | 65.48 | 4006.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment -- ElevatorLightsFan | 5.11 | 162.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans -- Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans -- General | 106.86 | 9639.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Recovery -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems -- Water Heater | 442.92 | 37737.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Process Subtotal [GJ] | Total Energy Use [GJ] | |
| Electricity | 458.66 | 1308.91 |
| Natural Gas | 0.00 | 146.93 |
| Additional | 0.00 | 0.00 |
| Total | 458.66 | 1455.84 |
| Process Subtotal [$] | Total Energy Cost [$] | |
| Electricity | 0.00 | |
| Natural Gas | 0.00 | |
| Additional | 0.00 | |
| Total | 0.00 |
| Rated Capacity [kW] | Annual Energy Generated [GJ] | |
| Photovoltaic | 0.00 | 0.00 |
| Wind | 0.00 | 0.00 |
| Electricty [MJ/m2] | |
| Interior Lighting (All) | 31.66 |
| Space Heating | 0.00 |
| Space Cooling | 48.25 |
| Fans (All) | 34.09 |
| Service Water Heating | 141.30 |
| Receptacle Equipment | 146.32 |
| Miscellaneous (All) | 417.57 |
| Subtotal | 417.57 |
| Natural Gas [MJ/m2] | |
| Space Heating | 46.87 |
| Service Water Heating | 0.00 |
| Miscellaneous (All) | 46.87 |
| Subtotal | 46.87 |
| Additional [MJ/m2] | |
| Subtotal | 0.00 |
| Miscellaneous | 0.00 |
| Percent [%] | |
| Interior Lighting (All) | 6.82 |
| Space Heating | 10.09 |
| Space Cooling | 10.39 |
| Fans (All) | 7.34 |
| Service Water Heating | 30.42 |
| Receptacle Equipment | 31.50 |
| Miscellaneous | 3.44 |
| Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
| OCC_APT_SCH_STAY_HOME_FAMILY | 5993. | 8760. |
| OCC_APT_SCH_CORRIDOR | 5993. | 8760. |
| OCC_APT_SCH_WORKING_FAMILY | 5845. | 6055. |
| OCC_OFF_SCH | 2210. | 2340. |
| OCC_OFF_W_SB_SCH | 1820. | 1820. |
| LTG_SCH_OFFICE | 2435. | 8760. |
| LTG_SCH_CORRIDOR | 8760. | 8760. |
| LTG_SCH_APARTMENT_HARDWIRED | 527. | 8760. |
| LTG_SCH_APARTMENT_PLUGIN | 527. | 8760. |
| EQP_APT_SCH | 5763. | 8760. |
| EQP_OFF_SCH | 4531. | 8760. |
| INF_APT_SCH | 8760. | 8760. |
| INF_OFF_SCH | 8760. | 8760. |
| INF_COR_SCH | 8760. | 8760. |
| INFIL_DOOR_OPENING_SCH | 1466. | 5840. |
| ALL OFF | 0. | 0. |
| ALL ON | 8760. | 8760. |
| ALWAYS_ON | 8760. | 8760. |
| ALLON_EXCEPT_DD | 8760. | 8760. |
| EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
| FAN_OFF_W_SB_SCH | 8240. | 8240. |
| APT_DHW_SCH | 4592. | 8760. |
| EXTERIOR_LTG_SCH | 4380. | 4380. |
| BLDG_ELEVATORS | 2270. | 8760. |
| ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
| ELEV_LIGHT_FAN_SCH_ADD_DF | 2154. | 8760. |
| SLIDING_DOORS_VENTILATION_AVAILABILITY_SCH | 5840. | 5840. |
| First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
| HTGSETP_APT_SCH | APTHEATINGSETPOINT | January | 21.10 | 365 | 21.10 | 365 |
| HTGSETP_DESIGN_OFF_SCH | OFFHEATINGSETPOINT | January | 21.10 | 365 | 21.10 | 365 |
| CLGSETP_APT_SCH | APTCOOLINGSETPOINT | July | 24.00 | 365 | 24.00 | 365 |
| CLGSETP_DESIGN_OFF_SCH | OFFCOOLINGSETPOINT | July | 23.90 | 365 | 23.90 | 365 |
| S HTGSETP_APT_SCH | S APARTMENT DUAL SP CONTROL | January | 21.10 | 365 | 21.10 | 365 |
| S CLGSETP_APT_SCH | S APARTMENT DUAL SP CONTROL | July | 24.00 | 365 | 24.00 | 365 |
| N HTGSETP_APT_SCH | N APARTMENT DUAL SP CONTROL | January | 21.10 | 365 | 21.10 | 365 |
| N CLGSETP_APT_SCH | N APARTMENT DUAL SP CONTROL | July | 24.00 | 365 | 24.00 | 365 |
| HTGSETP_OFF_SCH_YES_OPTIMUM | OFFICE DUAL SP CONTROL | January | 21.10 | 365 | 15.60 | 365 |
| CLGSETP_OFF_SCH_YES_OPTIMUM | OFFICE DUAL SP CONTROL | July | 24.00 | 365 | 29.40 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 09:14:27
Heat Index Hours| Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
| G SW APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| G NW APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| OFFICE | 6856.67 | 1903.33 | 0.00 | 0.00 | 0.00 |
| G NE APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| G N1 APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| G N2 APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| G S1 APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| G S2 APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M SW APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M NW APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M SE APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M NE APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M N1 APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M N2 APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M S1 APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M S2 APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T SW APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T NW APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T SE APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T NE APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T N1 APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T N2 APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T S1 APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T S2 APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T CORRIDOR | 6431.83 | 2303.83 | 24.33 | 0.00 | 0.00 |
| G CORRIDOR | 7647.00 | 1113.00 | 0.00 | 0.00 | 0.00 |
| M CORRIDOR | 5007.17 | 3752.83 | 0.00 | 0.00 | 0.00 |
| Min | 5007.17 | 0.00 | 0.00 | 0.00 | 0.00 |
| Max | 8760.00 | 3752.83 | 24.33 | 0.00 | 0.00 |
| Average | 8423.06 | 336.04 | 0.90 | 0.00 | 0.00 |
| Sum | 227422.67 | 9073.00 | 24.33 | 0.00 | 0.00 |
| Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
| G SW APARTMENT | 11830.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| G NW APARTMENT | 10585.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| OFFICE | 7000.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| G NE APARTMENT | 10585.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| G N1 APARTMENT | 10585.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| G N2 APARTMENT | 10585.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| G S1 APARTMENT | 11830.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| G S2 APARTMENT | 11830.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M SW APARTMENT | 11830.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M NW APARTMENT | 10585.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M SE APARTMENT | 11830.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M NE APARTMENT | 10585.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M N1 APARTMENT | 10585.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M N2 APARTMENT | 10585.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M S1 APARTMENT | 11830.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M S2 APARTMENT | 11830.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T SW APARTMENT | 11830.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T NW APARTMENT | 10585.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T SE APARTMENT | 11830.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T NE APARTMENT | 10585.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T N1 APARTMENT | 10585.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T N2 APARTMENT | 10585.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T S1 APARTMENT | 11830.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T S2 APARTMENT | 11830.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T CORRIDOR | 17431.00 | 5493.83 | 70.17 | 0.00 | 0.00 |
| G CORRIDOR | 20057.17 | 2937.83 | 0.00 | 0.00 | 0.00 |
| M CORRIDOR | 13284.17 | 9710.83 | 0.00 | 0.00 | 0.00 |
| Min | 7000.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Max | 20057.17 | 9710.83 | 70.17 | 0.00 | 0.00 |
| Average | 11663.79 | 671.94 | 2.60 | 0.00 | 0.00 |
| Sum | 314922.33 | 18142.50 | 70.17 | 0.00 | 0.00 |
| Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
| G SW APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| G NW APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| OFFICE | 7583.67 | 1176.33 | 0.00 | 0.00 | 0.00 |
| G NE APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| G N1 APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| G N2 APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| G S1 APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| G S2 APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M SW APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M NW APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M SE APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M NE APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M N1 APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M N2 APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M S1 APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M S2 APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T SW APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T NW APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T SE APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T NE APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T N1 APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T N2 APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T S1 APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T S2 APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T CORRIDOR | 3840.00 | 4831.50 | 88.50 | 0.00 | 0.00 |
| G CORRIDOR | 7412.83 | 1347.17 | 0.00 | 0.00 | 0.00 |
| M CORRIDOR | 626.50 | 7910.00 | 223.50 | 0.00 | 0.00 |
| Min | 626.50 | 0.00 | 0.00 | 0.00 | 0.00 |
| Max | 8760.00 | 7910.00 | 223.50 | 0.00 | 0.00 |
| Average | 8183.07 | 565.37 | 11.56 | 0.00 | 0.00 |
| Sum | 220943.00 | 15265.00 | 312.00 | 0.00 | 0.00 |
| Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
| G SW APARTMENT | 11830.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| G NW APARTMENT | 10585.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| OFFICE | 6998.00 | 2.00 | 0.00 | 0.00 | 0.00 |
| G NE APARTMENT | 10585.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| G N1 APARTMENT | 10585.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| G N2 APARTMENT | 10585.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| G S1 APARTMENT | 11830.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| G S2 APARTMENT | 11830.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M SW APARTMENT | 11830.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M NW APARTMENT | 10585.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M SE APARTMENT | 11830.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M NE APARTMENT | 10585.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M N1 APARTMENT | 10585.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M N2 APARTMENT | 10585.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M S1 APARTMENT | 11830.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M S2 APARTMENT | 11830.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T SW APARTMENT | 11830.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T NW APARTMENT | 10585.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T SE APARTMENT | 11830.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T NE APARTMENT | 10585.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T N1 APARTMENT | 10585.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T N2 APARTMENT | 10585.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T S1 APARTMENT | 11830.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T S2 APARTMENT | 11830.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T CORRIDOR | 10146.83 | 12588.50 | 259.67 | 0.00 | 0.00 |
| G CORRIDOR | 18716.17 | 4278.83 | 0.00 | 0.00 | 0.00 |
| M CORRIDOR | 1663.50 | 20785.50 | 546.00 | 0.00 | 0.00 |
| Min | 1663.50 | 0.00 | 0.00 | 0.00 | 0.00 |
| Max | 18716.17 | 20785.50 | 546.00 | 0.00 | 0.00 |
| Average | 10913.87 | 1394.62 | 29.84 | 0.00 | 0.00 |
| Sum | 294674.50 | 37654.83 | 805.67 | 0.00 | 0.00 |
| SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
| None |
| SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
| None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 09:14:27
CO2 Level Hours| Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
| None |
| Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
| None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 09:14:27
Illuminance Level Hours| A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
| None |
| A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
| None |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
| January | 2.601 |
| February | 4.285 |
| March | 8.765 |
| April | 13.905 |
| May | 17.822 |
| June | 23.208 |
| July | 25.626 |
| August | 24.075 |
| September | 20.490 |
| October | 13.707 |
| November | 6.961 |
| December | 2.072 |
| Annual Sum or Average | 13.676 |
| Minimum of Months | 2.072 |
| Maximum of Months | 25.626 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Environment
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
| January | 2.601 |
| February | 4.285 |
| March | 8.765 |
| April | 13.905 |
| May | 17.822 |
| June | 23.208 |
| July | 25.626 |
| August | 24.075 |
| September | 20.490 |
| October | 13.707 |
| November | 6.961 |
| December | 2.072 |
| Annual Sum or Average | 13.676 |
| Minimum of Months | 2.072 |
| Maximum of Months | 25.626 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2012
For: Environment
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
| January | 2.601 |
| February | 4.285 |
| March | 8.765 |
| April | 13.905 |
| May | 17.822 |
| June | 23.208 |
| July | 25.626 |
| August | 24.075 |
| September | 20.490 |
| October | 13.707 |
| November | 6.961 |
| December | 2.072 |
| Annual Sum or Average | 13.676 |
| Minimum of Months | 2.072 |
| Maximum of Months | 25.626 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
| January | 2.601 |
| February | 4.285 |
| March | 8.765 |
| April | 13.905 |
| May | 17.822 |
| June | 23.208 |
| July | 25.626 |
| August | 24.075 |
| September | 20.490 |
| October | 13.707 |
| November | 6.961 |
| December | 2.072 |
| Annual Sum or Average | 13.676 |
| Minimum of Months | 2.072 |
| Maximum of Months | 25.626 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME APARTMENTMIDRISE
For: Environment
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
| January | 2.601 |
| February | 4.285 |
| March | 8.765 |
| April | 13.905 |
| May | 17.822 |
| June | 23.208 |
| July | 25.626 |
| August | 24.075 |
| September | 20.490 |
| October | 13.707 |
| November | 6.961 |
| December | 2.072 |
| Annual Sum or Average | 13.676 |
| Minimum of Months | 2.072 |
| Maximum of Months | 25.626 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
| January | 2.601 |
| February | 4.285 |
| March | 8.765 |
| April | 13.905 |
| May | 17.822 |
| June | 23.208 |
| July | 25.626 |
| August | 24.075 |
| September | 20.490 |
| October | 13.707 |
| November | 6.961 |
| December | 2.072 |
| Annual Sum or Average | 13.676 |
| Minimum of Months | 2.072 |
| Maximum of Months | 25.626 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
| January | 2.601 |
| February | 4.285 |
| March | 8.765 |
| April | 13.905 |
| May | 17.822 |
| June | 23.208 |
| July | 25.626 |
| August | 24.075 |
| September | 20.490 |
| October | 13.707 |
| November | 6.961 |
| December | 2.072 |
| Annual Sum or Average | 13.676 |
| Minimum of Months | 2.072 |
| Maximum of Months | 25.626 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4B
For: Environment
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
| January | 2.601 |
| February | 4.285 |
| March | 8.765 |
| April | 13.905 |
| May | 17.822 |
| June | 23.208 |
| July | 25.626 |
| August | 24.075 |
| September | 20.490 |
| October | 13.707 |
| November | 6.961 |
| December | 2.072 |
| Annual Sum or Average | 13.676 |
| Minimum of Months | 2.072 |
| Maximum of Months | 25.626 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NM_ALBUQUERQUE
For: Environment
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
| January | 2.601 |
| February | 4.285 |
| March | 8.765 |
| April | 13.905 |
| May | 17.822 |
| June | 23.208 |
| July | 25.626 |
| August | 24.075 |
| September | 20.490 |
| October | 13.707 |
| November | 6.961 |
| December | 2.072 |
| Annual Sum or Average | 13.676 |
| Minimum of Months | 2.072 |
| Maximum of Months | 25.626 |
Report: ZoneCoolingSummaryMonthly
For: G SW APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.717427E+09 | 819.73 | 02-JAN-15:30 | 14.40 | 5.68 | 85068402.62 | 70.27 | 01-JAN-16:19 | 14.40 | 5.68 |
| February | 0.592681E+09 | 881.37 | 14-FEB-16:10 | 22.02 | 7.76 | 76633781.13 | 70.32 | 14-FEB-18:30 | 15.00 | 4.81 |
| March | 0.631490E+09 | 718.04 | 12-MAR-16:30 | 20.00 | 6.24 | 85906516.01 | 70.37 | 08-MAR-18:49 | 20.00 | 6.24 |
| April | 0.946040E+09 | 1272.87 | 13-APR-16:30 | 25.85 | 10.20 | 0.107147E+09 | 70.40 | 27-APR-01:10 | 16.55 | 6.57 |
| May | 0.130384E+10 | 1630.60 | 20-MAY-17:20 | 26.70 | 10.75 | 0.119157E+09 | 70.39 | 23-MAY-02:00 | 16.10 | 10.66 |
| June | 0.219592E+10 | 2099.86 | 28-JUN-16:30 | 38.35 | 14.13 | 0.119637E+09 | 70.39 | 01-JUN-02:00 | 38.35 | 14.13 |
| July | 0.299255E+10 | 2314.86 | 21-JUL-17:20 | 37.23 | 14.75 | 0.129276E+09 | 70.33 | 19-JUL-00:30 | 37.23 | 14.75 |
| August | 0.315828E+10 | 2414.66 | 20-AUG-17:05 | 34.40 | 15.58 | 0.123963E+09 | 70.32 | 06-AUG-23:49 | 34.40 | 15.58 |
| September | 0.294843E+10 | 2468.03 | 21-SEP-16:01 | 30.00 | 14.17 | 0.123963E+09 | 70.33 | 09-SEP-05:00 | 30.00 | 14.17 |
| October | 0.238190E+10 | 2312.06 | 06-OCT-16:05 | 27.62 | 12.31 | 0.122745E+09 | 70.39 | 08-OCT-01:39 | 11.30 | 5.31 |
| November | 0.138092E+10 | 1541.85 | 01-NOV-15:10 | 12.43 | 7.32 | 0.105700E+09 | 70.38 | 01-NOV-04:49 | 12.43 | 7.32 |
| December | 0.904574E+09 | 825.65 | 31-DEC-15:30 | 10.55 | 1.85 | 86308202.12 | 70.39 | 31-DEC-18:10 | 7.93 | 0.57 |
| Annual Sum or Average | 0.201541E+11 | 0.128551E+10 | ||||||||
| Minimum of Months | 0.592681E+09 | 718.04 | 10.55 | 1.85 | 76633781.13 | 70.27 | 7.93 | 0.57 | ||
| Maximum of Months | 0.315828E+10 | 2468.03 | 38.35 | 15.58 | 0.129276E+09 | 70.40 | 38.35 | 15.58 |
Report: ZoneCoolingSummaryMonthly
For: G NW APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 62680543.50 | 307.91 | 02-JAN-17:35 | 8.50 | 2.91 | 77952604.53 | 42.51 | 15-JAN-22:49 | 1.70 | -1.8 |
| February | 77646414.19 | 304.45 | 15-FEB-19:00 | 9.40 | 2.21 | 70845025.27 | 47.08 | 15-FEB-18:10 | 9.40 | 2.21 |
| March | 0.172770E+09 | 351.34 | 29-MAR-19:20 | 6.83 | 1.61 | 80223672.23 | 51.16 | 08-MAR-21:10 | 6.83 | 1.61 |
| April | 0.566979E+09 | 899.46 | 29-APR-17:30 | 24.45 | 9.24 | 97984153.08 | 70.40 | 30-APR-22:40 | 15.77 | 4.40 |
| May | 0.111189E+10 | 1503.85 | 19-MAY-17:20 | 29.80 | 11.90 | 0.120490E+09 | 70.39 | 07-MAY-20:10 | 29.80 | 11.90 |
| June | 0.222308E+10 | 2139.76 | 26-JUN-17:12 | 33.90 | 15.36 | 0.123849E+09 | 70.37 | 12-JUN-05:00 | 33.90 | 15.36 |
| July | 0.285681E+10 | 2261.72 | 04-JUL-17:30 | 35.00 | 14.25 | 0.128775E+09 | 70.33 | 19-JUL-00:30 | 23.05 | 12.37 |
| August | 0.272193E+10 | 2107.96 | 20-AUG-17:30 | 34.40 | 15.47 | 0.128775E+09 | 70.32 | 31-AUG-21:49 | 23.40 | 14.17 |
| September | 0.204269E+10 | 1800.48 | 02-SEP-17:10 | 30.92 | 15.53 | 0.124619E+09 | 70.36 | 09-SEP-03:00 | 12.20 | 10.82 |
| October | 0.123301E+10 | 1506.89 | 06-OCT-16:30 | 27.25 | 12.33 | 0.115912E+09 | 70.38 | 20-OCT-00:49 | 13.40 | 8.43 |
| November | 0.524495E+09 | 513.37 | 04-NOV-07:00 | 0.60 | 0.02 | 80627928.71 | 63.92 | 02-NOV-20:10 | 0.60 | 0.02 |
| December | 82632377.93 | 380.54 | 02-DEC-18:50 | 5.65 | -0.8 | 77979558.03 | 42.94 | 01-DEC-21:10 | 5.65 | -0.8 |
| Annual Sum or Average | 0.136766E+11 | 0.122803E+10 | ||||||||
| Minimum of Months | 62680543.50 | 304.45 | 0.60 | -0.8 | 70845025.27 | 42.51 | 0.60 | -1.8 | ||
| Maximum of Months | 0.285681E+10 | 2261.72 | 35.00 | 15.53 | 0.128775E+09 | 70.40 | 33.90 | 15.36 |
Report: ZoneCoolingSummaryMonthly
For: OFFICE
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.602556E+09 | 1087.52 | 03-JAN-14:00 | 15.00 | 5.83 | 53860431.58 | 135.88 | 23-JAN-15:20 | 15.60 | 4.85 |
| February | 0.469333E+09 | 1210.43 | 15-FEB-15:20 | 17.20 | 6.61 | 51726786.51 | 136.01 | 15-FEB-09:09 | 17.20 | 6.61 |
| March | 0.403054E+09 | 1183.24 | 13-MAR-14:30 | 21.15 | 7.30 | 71204270.30 | 136.89 | 09-MAR-09:09 | 21.15 | 7.30 |
| April | 0.718191E+09 | 5696.88 | 28-APR-08:62 | 16.97 | 7.11 | 68047436.04 | 171.21 | 28-APR-07:10 | 16.97 | 7.11 |
| May | 0.107115E+10 | 6758.74 | 22-MAY-07:02 | 19.60 | 12.50 | 76771099.17 | 207.78 | 22-MAY-07:10 | 19.60 | 12.50 |
| June | 0.174250E+10 | 6878.93 | 30-JUN-07:02 | 22.07 | 14.71 | 77608673.55 | 223.03 | 22-JUN-07:10 | 22.07 | 14.71 |
| July | 0.207915E+10 | 6904.08 | 03-JUL-07:02 | 21.97 | 14.22 | 70696864.47 | 217.86 | 07-JUL-07:10 | 22.35 | 15.77 |
| August | 0.239195E+10 | 6902.36 | 16-AUG-07:02 | 20.47 | 14.39 | 81266029.43 | 217.56 | 03-AUG-07:10 | 20.47 | 14.39 |
| September | 0.201242E+10 | 7148.83 | 18-SEP-07:01 | 13.68 | 11.37 | 70612520.21 | 217.94 | 11-SEP-07:10 | 13.68 | 11.37 |
| October | 0.169927E+10 | 7151.75 | 10-OCT-07:01 | 14.45 | 11.44 | 72845215.98 | 217.47 | 02-OCT-07:10 | 14.45 | 11.44 |
| November | 0.103228E+10 | 5940.37 | 01-NOV-08:62 | 8.17 | 5.63 | 67605398.86 | 166.81 | 01-NOV-07:30 | 8.17 | 5.63 |
| December | 0.691403E+09 | 810.62 | 29-DEC-15:30 | 11.40 | 3.91 | 56785053.21 | 136.63 | 01-DEC-09:09 | 11.40 | 3.91 |
| Annual Sum or Average | 0.149133E+11 | 0.819030E+09 | ||||||||
| Minimum of Months | 0.403054E+09 | 810.62 | 8.17 | 3.91 | 51726786.51 | 135.88 | 8.17 | 3.91 | ||
| Maximum of Months | 0.239195E+10 | 7151.75 | 22.07 | 14.71 | 81266029.43 | 223.03 | 22.35 | 15.77 |
Report: ZoneCoolingSummaryMonthly
For: G NE APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 42650806.83 | 262.28 | 03-JAN-17:25 | 10.25 | 3.66 | 77903892.87 | 42.51 | 15-JAN-22:49 | 1.70 | -1.8 |
| February | 63167184.71 | 291.35 | 15-FEB-19:00 | 9.40 | 2.21 | 70625331.33 | 43.11 | 14-FEB-18:00 | 9.40 | 2.21 |
| March | 0.210207E+09 | 336.43 | 17-MAR-17:35 | 7.43 | 4.03 | 79837495.12 | 50.72 | 26-MAR-20:10 | 12.20 | 3.73 |
| April | 0.624787E+09 | 854.78 | 29-APR-16:10 | 25.50 | 9.93 | 99033323.43 | 70.41 | 26-APR-22:49 | 25.50 | 9.93 |
| May | 0.121129E+10 | 1205.62 | 19-MAY-17:30 | 29.70 | 11.76 | 0.121540E+09 | 70.40 | 12-MAY-23:30 | 29.70 | 11.76 |
| June | 0.235507E+10 | 1800.43 | 29-JUN-15:10 | 37.43 | 15.90 | 0.123995E+09 | 70.35 | 11-JUN-01:00 | 37.43 | 15.90 |
| July | 0.302931E+10 | 1846.40 | 04-JUL-17:10 | 35.73 | 14.63 | 0.128775E+09 | 70.33 | 19-JUL-00:30 | 23.05 | 12.37 |
| August | 0.284934E+10 | 1737.82 | 20-AUG-17:10 | 34.40 | 15.58 | 0.128775E+09 | 70.32 | 31-AUG-21:49 | 23.40 | 14.17 |
| September | 0.209227E+10 | 1529.03 | 03-SEP-15:10 | 30.13 | 16.11 | 0.124613E+09 | 70.38 | 27-SEP-05:10 | 11.60 | 6.66 |
| October | 0.124178E+10 | 1279.93 | 01-OCT-16:10 | 28.35 | 13.47 | 0.115943E+09 | 70.36 | 19-OCT-23:40 | 14.07 | 8.58 |
| November | 0.547074E+09 | 494.92 | 04-NOV-06:35 | 1.33 | 0.44 | 80029399.14 | 61.39 | 02-NOV-21:10 | 1.33 | 0.44 |
| December | 50585901.50 | 326.02 | 02-DEC-11:30 | 7.75 | 1.68 | 77924745.95 | 42.51 | 20-DEC-22:49 | -1.0 | -3.5 |
| Annual Sum or Average | 0.143175E+11 | 0.122900E+10 | ||||||||
| Minimum of Months | 42650806.83 | 262.28 | 1.33 | 0.44 | 70625331.33 | 42.51 | -1.0 | -3.5 | ||
| Maximum of Months | 0.302931E+10 | 1846.40 | 37.43 | 16.11 | 0.128775E+09 | 70.41 | 37.43 | 15.90 |
Report: ZoneCoolingSummaryMonthly
For: G N1 APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.132874E+09 | 331.66 | 03-JAN-18:12 | 7.57 | 2.15 | 77936700.78 | 42.51 | 26-JAN-06:49 | -5.9 | -8.4 |
| February | 0.138367E+09 | 325.80 | 15-FEB-21:00 | 7.80 | 3.08 | 70754108.11 | 45.29 | 14-FEB-21:10 | 7.80 | 3.08 |
| March | 0.320296E+09 | 382.55 | 17-MAR-19:10 | 5.63 | 3.49 | 80223417.47 | 51.84 | 16-MAR-20:10 | 5.63 | 3.49 |
| April | 0.581487E+09 | 608.20 | 29-APR-16:30 | 25.30 | 9.72 | 0.100245E+09 | 70.41 | 14-APR-23:10 | 25.30 | 9.72 |
| May | 0.102246E+10 | 975.26 | 19-MAY-18:00 | 29.40 | 11.33 | 0.123323E+09 | 70.40 | 02-MAY-20:40 | 29.40 | 11.33 |
| June | 0.184993E+10 | 1394.68 | 28-JUN-17:50 | 34.97 | 16.29 | 0.124405E+09 | 70.38 | 09-JUN-23:30 | 34.97 | 16.29 |
| July | 0.235461E+10 | 1429.83 | 04-JUL-17:40 | 34.63 | 14.06 | 0.128775E+09 | 70.33 | 19-JUL-00:30 | 23.05 | 12.37 |
| August | 0.221392E+10 | 1333.66 | 20-AUG-17:17 | 34.40 | 15.52 | 0.128775E+09 | 70.33 | 31-AUG-21:49 | 23.40 | 14.17 |
| September | 0.170357E+10 | 1143.73 | 03-SEP-16:40 | 27.40 | 15.86 | 0.124621E+09 | 70.30 | 02-SEP-21:40 | 27.40 | 15.86 |
| October | 0.113305E+10 | 1010.26 | 01-OCT-16:10 | 28.35 | 13.47 | 0.118001E+09 | 70.38 | 08-OCT-01:39 | 11.30 | 5.31 |
| November | 0.706944E+09 | 525.76 | 04-NOV-07:00 | 0.60 | 0.02 | 82178004.87 | 64.30 | 02-NOV-20:10 | 0.60 | 0.02 |
| December | 0.172137E+09 | 407.30 | 02-DEC-19:20 | 4.63 | -1.4 | 78019378.17 | 45.91 | 01-DEC-21:10 | 4.63 | -1.4 |
| Annual Sum or Average | 0.123296E+11 | 0.123726E+10 | ||||||||
| Minimum of Months | 0.132874E+09 | 325.80 | 0.60 | -1.4 | 70754108.11 | 42.51 | -5.9 | -8.4 | ||
| Maximum of Months | 0.235461E+10 | 1429.83 | 34.97 | 16.29 | 0.128775E+09 | 70.41 | 34.97 | 16.29 |
Report: ZoneCoolingSummaryMonthly
For: G N2 APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.133013E+09 | 324.16 | 02-JAN-17:45 | 7.85 | 2.57 | 77935736.03 | 42.51 | 26-JAN-06:49 | -5.9 | -8.4 |
| February | 0.136859E+09 | 325.31 | 15-FEB-21:00 | 7.80 | 3.08 | 70745167.64 | 45.21 | 14-FEB-21:10 | 7.80 | 3.08 |
| March | 0.322974E+09 | 383.11 | 17-MAR-19:10 | 5.63 | 3.49 | 80238670.30 | 51.94 | 16-MAR-20:10 | 5.63 | 3.49 |
| April | 0.588301E+09 | 622.02 | 29-APR-16:10 | 25.50 | 9.93 | 0.100474E+09 | 70.40 | 30-APR-00:30 | 15.85 | 5.60 |
| May | 0.103264E+10 | 972.34 | 19-MAY-18:00 | 29.40 | 11.33 | 0.123485E+09 | 70.40 | 10-MAY-23:19 | 29.40 | 11.33 |
| June | 0.185753E+10 | 1390.38 | 28-JUN-17:50 | 34.97 | 16.29 | 0.124414E+09 | 70.38 | 03-JUN-03:30 | 34.97 | 16.29 |
| July | 0.236295E+10 | 1423.25 | 04-JUL-17:40 | 34.63 | 14.06 | 0.128775E+09 | 70.33 | 19-JUL-00:30 | 23.05 | 12.37 |
| August | 0.221997E+10 | 1330.15 | 20-AUG-17:17 | 34.40 | 15.52 | 0.128775E+09 | 70.33 | 31-AUG-21:49 | 23.40 | 14.17 |
| September | 0.170630E+10 | 1146.82 | 03-SEP-16:30 | 27.50 | 15.86 | 0.124621E+09 | 70.30 | 02-SEP-21:40 | 27.50 | 15.86 |
| October | 0.113490E+10 | 1009.27 | 01-OCT-16:20 | 27.80 | 13.65 | 0.118043E+09 | 70.39 | 17-OCT-23:10 | 12.62 | 4.68 |
| November | 0.706800E+09 | 525.47 | 04-NOV-07:00 | 0.60 | 0.02 | 82164521.12 | 64.28 | 02-NOV-20:10 | 0.60 | 0.02 |
| December | 0.171012E+09 | 403.09 | 02-DEC-19:10 | 4.82 | -1.3 | 78016538.93 | 45.84 | 01-DEC-21:10 | 4.82 | -1.3 |
| Annual Sum or Average | 0.123732E+11 | 0.123769E+10 | ||||||||
| Minimum of Months | 0.133013E+09 | 324.16 | 0.60 | -1.3 | 70745167.64 | 42.51 | -5.9 | -8.4 | ||
| Maximum of Months | 0.236295E+10 | 1423.25 | 34.97 | 16.29 | 0.128775E+09 | 70.40 | 34.97 | 16.29 |
Report: ZoneCoolingSummaryMonthly
For: G S1 APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.110333E+10 | 1001.74 | 02-JAN-14:30 | 14.15 | 5.57 | 91837347.33 | 70.36 | 15-JAN-16:10 | 11.42 | 3.23 |
| February | 0.912432E+09 | 793.16 | 14-FEB-15:10 | 21.78 | 7.45 | 81222964.94 | 70.40 | 14-FEB-20:40 | 10.37 | 3.21 |
| March | 0.861055E+09 | 644.11 | 13-MAR-14:30 | 21.15 | 7.30 | 92719221.33 | 70.40 | 13-MAR-19:10 | 16.52 | 5.65 |
| April | 0.954731E+09 | 967.78 | 29-APR-16:10 | 25.50 | 9.93 | 0.112624E+09 | 70.40 | 02-APR-18:10 | 25.50 | 9.93 |
| May | 0.123257E+10 | 1064.23 | 19-MAY-17:20 | 29.80 | 11.90 | 0.121960E+09 | 70.41 | 03-MAY-18:00 | 29.80 | 11.90 |
| June | 0.183223E+10 | 1367.23 | 29-JUN-15:10 | 37.43 | 15.90 | 0.120192E+09 | 70.39 | 11-JUN-02:39 | 37.43 | 15.90 |
| July | 0.250496E+10 | 1541.70 | 22-JUL-16:05 | 36.05 | 15.98 | 0.129276E+09 | 70.33 | 19-JUL-00:30 | 36.05 | 15.98 |
| August | 0.266801E+10 | 1655.29 | 20-AUG-16:07 | 34.90 | 15.92 | 0.123963E+09 | 70.32 | 16-AUG-22:49 | 34.90 | 15.92 |
| September | 0.263497E+10 | 1836.64 | 21-SEP-15:10 | 30.00 | 14.18 | 0.123963E+09 | 70.32 | 12-SEP-19:49 | 30.00 | 14.18 |
| October | 0.234225E+10 | 1757.84 | 01-OCT-15:10 | 28.40 | 12.95 | 0.124823E+09 | 70.38 | 12-OCT-22:00 | 5.60 | -0.8 |
| November | 0.157662E+10 | 1471.63 | 01-NOV-13:00 | 13.30 | 7.71 | 0.114340E+09 | 70.38 | 08-NOV-03:00 | 12.20 | 4.49 |
| December | 0.129511E+10 | 908.09 | 31-DEC-15:10 | 10.92 | 2.09 | 93914217.22 | 70.36 | 24-DEC-16:30 | 10.92 | 2.09 |
| Annual Sum or Average | 0.199183E+11 | 0.133084E+10 | ||||||||
| Minimum of Months | 0.861055E+09 | 644.11 | 10.92 | 2.09 | 81222964.94 | 70.32 | 5.60 | -0.8 | ||
| Maximum of Months | 0.266801E+10 | 1836.64 | 37.43 | 15.98 | 0.129276E+09 | 70.41 | 37.43 | 15.98 |
Report: ZoneCoolingSummaryMonthly
For: G S2 APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.109417E+10 | 1013.80 | 02-JAN-14:30 | 14.15 | 5.57 | 91865481.37 | 70.35 | 15-JAN-16:19 | 11.13 | 3.10 |
| February | 0.903809E+09 | 813.64 | 14-FEB-15:10 | 21.78 | 7.45 | 81254249.59 | 70.34 | 14-FEB-20:49 | 10.18 | 3.16 |
| March | 0.884574E+09 | 688.40 | 13-MAR-14:30 | 21.15 | 7.30 | 93828553.92 | 70.40 | 18-MAR-17:40 | 11.50 | 3.03 |
| April | 0.102414E+10 | 1060.37 | 29-APR-16:10 | 25.50 | 9.93 | 0.113970E+09 | 70.41 | 09-APR-20:10 | 25.50 | 9.93 |
| May | 0.136995E+10 | 1154.68 | 14-MAY-16:30 | 28.30 | 10.87 | 0.122722E+09 | 70.40 | 11-MAY-02:00 | 28.30 | 10.87 |
| June | 0.204806E+10 | 1450.86 | 29-JUN-15:10 | 37.43 | 15.90 | 0.120283E+09 | 70.38 | 08-JUN-23:10 | 37.43 | 15.90 |
| July | 0.280698E+10 | 1678.67 | 22-JUL-16:05 | 36.05 | 15.98 | 0.129276E+09 | 70.33 | 19-JUL-00:30 | 36.05 | 15.98 |
| August | 0.295591E+10 | 1815.54 | 20-AUG-16:07 | 34.90 | 15.92 | 0.123963E+09 | 70.32 | 16-AUG-22:49 | 34.90 | 15.92 |
| September | 0.288721E+10 | 1956.15 | 03-SEP-13:30 | 31.95 | 16.76 | 0.123963E+09 | 70.32 | 12-SEP-19:49 | 23.40 | 12.91 |
| October | 0.252393E+10 | 1912.78 | 01-OCT-14:10 | 28.30 | 13.52 | 0.125164E+09 | 70.40 | 26-OCT-18:19 | 8.87 | 2.06 |
| November | 0.162376E+10 | 1529.66 | 01-NOV-13:00 | 13.30 | 7.71 | 0.114967E+09 | 70.39 | 09-NOV-01:00 | 11.70 | 6.71 |
| December | 0.129966E+10 | 928.30 | 31-DEC-15:10 | 10.92 | 2.09 | 94092721.51 | 70.36 | 01-DEC-18:00 | 10.92 | 2.09 |
| Annual Sum or Average | 0.214222E+11 | 0.133535E+10 | ||||||||
| Minimum of Months | 0.884574E+09 | 688.40 | 10.92 | 2.09 | 81254249.59 | 70.32 | 8.87 | 2.06 | ||
| Maximum of Months | 0.295591E+10 | 1956.15 | 37.43 | 16.76 | 0.129276E+09 | 70.41 | 37.43 | 15.98 |
Report: ZoneCoolingSummaryMonthly
For: M SW APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.119090E+10 | 1715.95 | 02-JAN-15:20 | 14.40 | 5.68 | 92779071.34 | 70.29 | 24-JAN-18:10 | 10.13 | 1.50 |
| February | 0.118074E+10 | 2098.75 | 14-FEB-15:30 | 21.95 | 7.62 | 86487242.35 | 70.32 | 09-FEB-19:10 | 21.95 | 7.62 |
| March | 0.137610E+10 | 1984.79 | 12-MAR-16:03 | 19.60 | 6.14 | 0.104174E+09 | 70.33 | 27-MAR-20:49 | 10.28 | 3.25 |
| April | 0.194405E+10 | 2328.34 | 13-APR-16:27 | 25.85 | 10.20 | 0.119297E+09 | 70.32 | 15-APR-20:00 | 7.80 | 2.27 |
| May | 0.221504E+10 | 2419.05 | 19-MAY-16:25 | 30.00 | 12.36 | 0.123814E+09 | 70.33 | 12-MAY-03:39 | 30.00 | 12.36 |
| June | 0.294460E+10 | 2740.76 | 26-JUN-17:05 | 33.90 | 15.52 | 0.120148E+09 | 70.32 | 14-JUN-22:30 | 33.90 | 15.52 |
| July | 0.353798E+10 | 2872.48 | 04-JUL-17:00 | 36.10 | 14.82 | 0.129276E+09 | 70.32 | 19-JUL-00:30 | 23.05 | 12.37 |
| August | 0.354620E+10 | 2885.04 | 20-AUG-17:00 | 34.40 | 15.63 | 0.123963E+09 | 70.32 | 06-AUG-23:49 | 34.40 | 15.63 |
| September | 0.312900E+10 | 2955.15 | 20-SEP-16:17 | 30.20 | 12.24 | 0.123958E+09 | 70.32 | 12-SEP-19:49 | 30.20 | 12.24 |
| October | 0.252864E+10 | 2720.11 | 05-OCT-16:03 | 26.70 | 11.77 | 0.121651E+09 | 70.33 | 12-OCT-21:10 | 7.02 | 0.37 |
| November | 0.160170E+10 | 2078.17 | 20-NOV-15:30 | 15.00 | 5.06 | 0.105236E+09 | 70.32 | 21-NOV-20:49 | 8.68 | 2.83 |
| December | 0.120949E+10 | 1767.27 | 31-DEC-15:30 | 10.55 | 1.85 | 92455054.70 | 70.30 | 30-DEC-18:00 | 10.55 | 1.85 |
| Annual Sum or Average | 0.264044E+11 | 0.134324E+10 | ||||||||
| Minimum of Months | 0.118074E+10 | 1715.95 | 10.55 | 1.85 | 86487242.35 | 70.29 | 7.02 | 0.37 | ||
| Maximum of Months | 0.354620E+10 | 2955.15 | 36.10 | 15.63 | 0.129276E+09 | 70.33 | 34.40 | 15.63 |
Report: ZoneCoolingSummaryMonthly
For: M NW APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.231672E+09 | 478.01 | 03-JAN-21:30 | 1.95 | -1.2 | 78691498.01 | 44.67 | 03-JAN-21:10 | 1.95 | -1.2 |
| February | 0.340650E+09 | 509.48 | 14-FEB-02:20 | 0.77 | -2.7 | 73829609.57 | 60.38 | 15-FEB-18:10 | 12.23 | 3.61 |
| March | 0.720262E+09 | 559.94 | 30-MAR-02:00 | -1.1 | -2.4 | 92512413.55 | 68.69 | 08-MAR-21:10 | -1.1 | -2.4 |
| April | 0.132830E+10 | 1915.64 | 13-APR-16:27 | 25.85 | 10.20 | 0.116444E+09 | 70.33 | 28-APR-03:39 | 11.87 | 3.94 |
| May | 0.198107E+10 | 2271.25 | 19-MAY-16:50 | 30.00 | 12.24 | 0.126504E+09 | 70.32 | 03-MAY-03:30 | 30.00 | 12.24 |
| June | 0.296815E+10 | 2801.16 | 26-JUN-17:17 | 33.90 | 15.36 | 0.124359E+09 | 70.32 | 14-JUN-22:30 | 33.90 | 15.36 |
| July | 0.338281E+10 | 2835.63 | 04-JUL-17:30 | 35.00 | 14.25 | 0.128775E+09 | 70.32 | 19-JUL-00:30 | 23.05 | 12.37 |
| August | 0.307264E+10 | 2535.56 | 20-AUG-17:30 | 34.40 | 15.47 | 0.128775E+09 | 70.32 | 06-AUG-23:49 | 34.40 | 15.47 |
| September | 0.216996E+10 | 2160.90 | 02-SEP-16:40 | 31.10 | 15.74 | 0.124589E+09 | 70.30 | 23-SEP-20:19 | 16.10 | 13.87 |
| October | 0.125109E+10 | 1803.62 | 06-OCT-16:30 | 27.25 | 12.33 | 0.115237E+09 | 70.33 | 15-OCT-20:10 | 16.93 | 6.79 |
| November | 0.583297E+09 | 514.40 | 04-NOV-07:00 | 0.60 | 0.02 | 82750446.36 | 68.31 | 02-NOV-21:10 | 0.60 | 0.02 |
| December | 0.198499E+09 | 434.13 | 02-DEC-20:30 | 3.60 | -2.0 | 78286531.76 | 45.85 | 01-DEC-21:10 | 3.60 | -2.0 |
| Annual Sum or Average | 0.182284E+11 | 0.127075E+10 | ||||||||
| Minimum of Months | 0.198499E+09 | 434.13 | -1.1 | -2.7 | 73829609.57 | 44.67 | -1.1 | -2.4 | ||
| Maximum of Months | 0.338281E+10 | 2835.63 | 35.00 | 15.74 | 0.128775E+09 | 70.33 | 34.40 | 15.47 |
Report: ZoneCoolingSummaryMonthly
For: M SE APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.118537E+10 | 1531.24 | 02-JAN-14:00 | 13.90 | 5.47 | 92966749.31 | 70.29 | 14-JAN-17:30 | 7.20 | 0.47 |
| February | 0.115171E+10 | 1784.77 | 14-FEB-14:40 | 21.33 | 7.23 | 85922064.36 | 70.32 | 12-FEB-20:40 | 21.33 | 7.23 |
| March | 0.141487E+10 | 1731.11 | 08-MAR-14:00 | 22.80 | 9.68 | 0.104792E+09 | 70.32 | 06-MAR-19:40 | 22.80 | 9.68 |
| April | 0.208339E+10 | 1970.09 | 28-APR-13:00 | 24.40 | 9.84 | 0.119634E+09 | 70.32 | 02-APR-07:10 | 24.40 | 9.84 |
| May | 0.235260E+10 | 1928.71 | 19-MAY-12:30 | 28.35 | 12.80 | 0.124140E+09 | 70.32 | 22-MAY-19:49 | 23.40 | 11.72 |
| June | 0.309324E+10 | 2287.50 | 29-JUN-15:10 | 37.43 | 15.90 | 0.120201E+09 | 70.32 | 08-JUN-22:30 | 37.43 | 15.90 |
| July | 0.372017E+10 | 2419.23 | 22-JUL-14:00 | 37.80 | 17.92 | 0.129276E+09 | 70.32 | 19-JUL-00:30 | 37.80 | 17.92 |
| August | 0.368381E+10 | 2376.60 | 17-AUG-13:30 | 33.35 | 17.85 | 0.123963E+09 | 70.32 | 16-AUG-22:49 | 33.35 | 17.85 |
| September | 0.318531E+10 | 2612.68 | 03-SEP-13:30 | 31.95 | 16.76 | 0.123953E+09 | 70.32 | 12-SEP-19:49 | 23.40 | 12.91 |
| October | 0.255501E+10 | 2418.33 | 01-OCT-13:30 | 27.75 | 13.90 | 0.121591E+09 | 70.32 | 17-OCT-01:10 | 8.58 | 3.52 |
| November | 0.159794E+10 | 1901.88 | 01-NOV-12:50 | 13.30 | 7.71 | 0.105262E+09 | 70.32 | 21-NOV-19:10 | 10.10 | 3.47 |
| December | 0.118370E+10 | 1489.68 | 31-DEC-14:20 | 10.37 | 1.81 | 92230090.86 | 70.30 | 30-DEC-18:10 | 10.37 | 1.81 |
| Annual Sum or Average | 0.272071E+11 | 0.134393E+10 | ||||||||
| Minimum of Months | 0.115171E+10 | 1489.68 | 10.37 | 1.81 | 85922064.36 | 70.29 | 7.20 | 0.47 | ||
| Maximum of Months | 0.372017E+10 | 2612.68 | 37.80 | 17.92 | 0.129276E+09 | 70.32 | 37.80 | 17.92 |
Report: ZoneCoolingSummaryMonthly
For: M NE APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.248680E+09 | 445.25 | 03-JAN-21:10 | 3.25 | -0.5 | 78324913.71 | 43.38 | 03-JAN-21:10 | 3.25 | -0.5 |
| February | 0.326575E+09 | 500.73 | 14-FEB-07:20 | 1.10 | -2.3 | 73115202.96 | 55.97 | 14-FEB-22:10 | 10.60 | 3.54 |
| March | 0.746768E+09 | 557.48 | 12-MAR-07:00 | -1.1 | -4.4 | 92916943.35 | 68.50 | 26-MAR-20:10 | 12.20 | 3.73 |
| April | 0.143121E+10 | 1467.29 | 29-APR-16:10 | 25.50 | 9.93 | 0.117304E+09 | 70.33 | 24-APR-23:30 | 25.50 | 9.93 |
| May | 0.211337E+10 | 1717.65 | 19-MAY-17:20 | 29.80 | 11.90 | 0.126944E+09 | 70.32 | 13-MAY-04:49 | 29.80 | 11.90 |
| June | 0.311803E+10 | 2196.90 | 29-JUN-15:10 | 37.43 | 15.90 | 0.124405E+09 | 70.32 | 17-JUN-21:49 | 37.43 | 15.90 |
| July | 0.356497E+10 | 2148.98 | 04-JUL-17:04 | 35.73 | 14.63 | 0.128775E+09 | 70.32 | 19-JUL-00:30 | 23.05 | 12.37 |
| August | 0.320940E+10 | 1941.12 | 02-AUG-17:10 | 32.85 | 15.85 | 0.128775E+09 | 70.32 | 16-AUG-22:49 | 23.40 | 13.80 |
| September | 0.222476E+10 | 1675.07 | 03-SEP-14:30 | 31.70 | 16.46 | 0.124559E+09 | 70.32 | 25-SEP-03:39 | 13.13 | 10.33 |
| October | 0.125727E+10 | 1369.94 | 01-OCT-16:10 | 28.35 | 13.47 | 0.115242E+09 | 70.32 | 10-OCT-02:30 | 15.00 | 11.15 |
| November | 0.608153E+09 | 485.12 | 04-NOV-06:25 | 1.70 | 0.65 | 81957189.75 | 64.62 | 02-NOV-21:10 | 1.70 | 0.65 |
| December | 0.168884E+09 | 398.69 | 02-DEC-19:00 | 5.00 | -1.2 | 78045777.53 | 44.72 | 01-DEC-21:10 | 5.00 | -1.2 |
| Annual Sum or Average | 0.190181E+11 | 0.127036E+10 | ||||||||
| Minimum of Months | 0.168884E+09 | 398.69 | -1.1 | -4.4 | 73115202.96 | 43.38 | 1.70 | -1.2 | ||
| Maximum of Months | 0.356497E+10 | 2196.90 | 37.43 | 16.46 | 0.128775E+09 | 70.33 | 37.43 | 15.90 |
Report: ZoneCoolingSummaryMonthly
For: M N1 APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.464498E+09 | 530.27 | 03-JAN-22:00 | 0.00 | -2.3 | 78842490.06 | 46.38 | 03-JAN-21:10 | 0.00 | -2.3 |
| February | 0.548874E+09 | 558.68 | 14-FEB-03:00 | -1.1 | -3.8 | 74124665.04 | 57.06 | 14-FEB-22:10 | 10.60 | 3.54 |
| March | 0.832399E+09 | 596.18 | 30-MAR-06:00 | -2.2 | -3.1 | 96423067.39 | 68.95 | 27-MAR-20:10 | -2.2 | -3.1 |
| April | 0.114418E+10 | 1080.77 | 29-APR-16:20 | 25.40 | 9.82 | 0.119012E+09 | 70.33 | 09-APR-20:49 | 25.40 | 9.82 |
| May | 0.165946E+10 | 1343.29 | 31-MAY-18:00 | 27.20 | 10.19 | 0.127641E+09 | 70.32 | 26-MAY-04:10 | 27.20 | 10.19 |
| June | 0.232325E+10 | 1629.48 | 16-JUN-18:00 | 31.10 | 13.39 | 0.124562E+09 | 70.32 | 17-JUN-21:49 | 23.40 | 8.37 |
| July | 0.264885E+10 | 1633.71 | 04-JUL-18:00 | 33.90 | 13.69 | 0.128775E+09 | 70.32 | 19-JUL-00:30 | 23.05 | 12.37 |
| August | 0.240465E+10 | 1462.25 | 01-AUG-17:10 | 32.93 | 15.29 | 0.128775E+09 | 70.32 | 16-AUG-22:49 | 23.40 | 13.80 |
| September | 0.178175E+10 | 1220.19 | 03-SEP-16:50 | 27.30 | 15.86 | 0.124619E+09 | 70.29 | 02-SEP-21:40 | 27.30 | 15.86 |
| October | 0.115591E+10 | 1067.11 | 01-OCT-16:10 | 28.35 | 13.47 | 0.118246E+09 | 70.33 | 19-OCT-01:30 | 11.40 | 4.46 |
| November | 0.809513E+09 | 534.33 | 04-NOV-07:00 | 0.60 | 0.02 | 85979956.35 | 69.25 | 02-NOV-21:10 | 0.60 | 0.02 |
| December | 0.418056E+09 | 483.98 | 30-DEC-21:20 | 1.67 | -3.1 | 78415076.19 | 49.79 | 01-DEC-21:10 | 1.67 | -3.1 |
| Annual Sum or Average | 0.161914E+11 | 0.128542E+10 | ||||||||
| Minimum of Months | 0.418056E+09 | 483.98 | -2.2 | -3.8 | 74124665.04 | 46.38 | -2.2 | -3.1 | ||
| Maximum of Months | 0.264885E+10 | 1633.71 | 33.90 | 15.86 | 0.128775E+09 | 70.33 | 27.30 | 15.86 |
Report: ZoneCoolingSummaryMonthly
For: M N2 APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.463145E+09 | 530.13 | 03-JAN-22:00 | 0.00 | -2.3 | 78828678.77 | 46.33 | 03-JAN-21:10 | 0.00 | -2.3 |
| February | 0.545823E+09 | 558.45 | 14-FEB-03:00 | -1.1 | -3.8 | 74075302.68 | 57.06 | 14-FEB-22:10 | 10.60 | 3.54 |
| March | 0.834105E+09 | 596.13 | 30-MAR-06:00 | -2.2 | -3.1 | 96687773.38 | 69.13 | 27-MAR-20:10 | -2.2 | -3.1 |
| April | 0.115469E+10 | 1087.03 | 29-APR-16:20 | 25.40 | 9.82 | 0.119146E+09 | 70.33 | 09-APR-21:10 | 25.40 | 9.82 |
| May | 0.166783E+10 | 1335.74 | 19-MAY-18:00 | 29.40 | 11.33 | 0.127694E+09 | 70.33 | 04-MAY-20:10 | 29.40 | 11.33 |
| June | 0.232951E+10 | 1623.05 | 16-JUN-18:00 | 31.10 | 13.39 | 0.124564E+09 | 70.32 | 17-JUN-21:49 | 23.40 | 8.37 |
| July | 0.265600E+10 | 1622.75 | 04-JUL-18:00 | 33.90 | 13.69 | 0.128775E+09 | 70.32 | 19-JUL-00:30 | 23.05 | 12.37 |
| August | 0.241006E+10 | 1454.86 | 07-AUG-18:00 | 30.00 | 16.48 | 0.128775E+09 | 70.32 | 16-AUG-22:49 | 23.40 | 13.80 |
| September | 0.178435E+10 | 1223.83 | 03-SEP-16:40 | 27.40 | 15.86 | 0.124619E+09 | 70.29 | 02-SEP-21:40 | 27.40 | 15.86 |
| October | 0.115908E+10 | 1064.49 | 01-OCT-16:20 | 27.80 | 13.65 | 0.118274E+09 | 70.32 | 08-OCT-00:49 | 11.97 | 6.31 |
| November | 0.808921E+09 | 533.77 | 04-NOV-07:00 | 0.60 | 0.02 | 85951199.25 | 69.15 | 02-NOV-21:10 | 0.60 | 0.02 |
| December | 0.416523E+09 | 478.15 | 30-DEC-21:10 | 1.93 | -3.0 | 78397704.96 | 49.70 | 01-DEC-21:10 | 1.93 | -3.0 |
| Annual Sum or Average | 0.162300E+11 | 0.128579E+10 | ||||||||
| Minimum of Months | 0.416523E+09 | 478.15 | -2.2 | -3.8 | 74075302.68 | 46.33 | -2.2 | -3.1 | ||
| Maximum of Months | 0.265600E+10 | 1623.05 | 33.90 | 16.48 | 0.128775E+09 | 70.33 | 29.40 | 15.86 |
Report: ZoneCoolingSummaryMonthly
For: M S1 APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.154563E+10 | 1738.94 | 02-JAN-14:00 | 13.90 | 5.47 | 0.103172E+09 | 70.33 | 24-JAN-20:10 | 5.95 | -1.0 |
| February | 0.144285E+10 | 1751.90 | 14-FEB-14:40 | 21.33 | 7.23 | 94496720.14 | 70.33 | 10-FEB-21:40 | 21.33 | 7.23 |
| March | 0.146855E+10 | 1565.91 | 08-MAR-14:00 | 22.80 | 9.68 | 0.112395E+09 | 70.32 | 20-MAR-17:40 | 9.80 | 5.68 |
| April | 0.179186E+10 | 1480.28 | 26-APR-14:10 | 25.60 | 10.05 | 0.121638E+09 | 70.33 | 17-APR-04:49 | 25.60 | 10.05 |
| May | 0.189794E+10 | 1453.89 | 14-MAY-16:30 | 28.30 | 10.87 | 0.124843E+09 | 70.32 | 22-MAY-19:49 | 23.40 | 11.72 |
| June | 0.229919E+10 | 1613.20 | 29-JUN-15:10 | 37.43 | 15.90 | 0.120347E+09 | 70.32 | 17-JUN-21:49 | 37.43 | 15.90 |
| July | 0.280411E+10 | 1740.32 | 22-JUL-14:00 | 37.80 | 17.92 | 0.129276E+09 | 70.32 | 19-JUL-00:30 | 37.80 | 17.92 |
| August | 0.287911E+10 | 1820.33 | 20-AUG-16:03 | 34.90 | 15.92 | 0.123963E+09 | 70.32 | 16-AUG-22:49 | 34.90 | 15.92 |
| September | 0.274699E+10 | 2129.67 | 21-SEP-14:10 | 30.50 | 14.49 | 0.123963E+09 | 70.32 | 12-SEP-19:49 | 30.50 | 14.49 |
| October | 0.248537E+10 | 2068.29 | 18-OCT-14:30 | 22.50 | 9.43 | 0.124385E+09 | 70.33 | 18-OCT-05:00 | 22.50 | 9.43 |
| November | 0.185444E+10 | 1933.59 | 20-NOV-14:00 | 14.40 | 4.74 | 0.114345E+09 | 70.32 | 06-NOV-23:30 | 14.40 | 4.74 |
| December | 0.162191E+10 | 1746.06 | 31-DEC-14:30 | 10.55 | 1.91 | 0.103318E+09 | 70.30 | 13-DEC-18:00 | 10.55 | 1.91 |
| Annual Sum or Average | 0.248379E+11 | 0.139614E+10 | ||||||||
| Minimum of Months | 0.144285E+10 | 1453.89 | 10.55 | 1.91 | 94496720.14 | 70.30 | 5.95 | -1.0 | ||
| Maximum of Months | 0.287911E+10 | 2129.67 | 37.80 | 17.92 | 0.129276E+09 | 70.33 | 37.80 | 17.92 |
Report: ZoneCoolingSummaryMonthly
For: M S2 APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.154818E+10 | 1745.48 | 02-JAN-14:00 | 13.90 | 5.47 | 0.103193E+09 | 70.32 | 05-JAN-20:10 | 5.92 | 0.22 |
| February | 0.144381E+10 | 1756.96 | 14-FEB-14:40 | 21.33 | 7.23 | 94400319.50 | 70.33 | 28-FEB-20:00 | 5.00 | 0.85 |
| March | 0.147741E+10 | 1575.24 | 08-MAR-14:00 | 22.80 | 9.68 | 0.112469E+09 | 70.33 | 20-MAR-17:40 | 9.80 | 5.68 |
| April | 0.180167E+10 | 1489.18 | 28-APR-13:30 | 24.40 | 10.06 | 0.121649E+09 | 70.32 | 21-APR-03:30 | 24.40 | 10.06 |
| May | 0.190671E+10 | 1449.67 | 14-MAY-16:10 | 28.30 | 10.98 | 0.124868E+09 | 70.33 | 08-MAY-04:00 | 28.30 | 10.98 |
| June | 0.230563E+10 | 1614.92 | 29-JUN-15:10 | 37.43 | 15.90 | 0.120349E+09 | 70.32 | 17-JUN-21:49 | 37.43 | 15.90 |
| July | 0.281129E+10 | 1746.02 | 22-JUL-14:00 | 37.80 | 17.92 | 0.129276E+09 | 70.32 | 19-JUL-00:30 | 37.80 | 17.92 |
| August | 0.288444E+10 | 1816.38 | 20-AUG-16:03 | 34.90 | 15.92 | 0.123963E+09 | 70.32 | 16-AUG-22:49 | 34.90 | 15.92 |
| September | 0.274947E+10 | 2132.68 | 21-SEP-14:10 | 30.50 | 14.49 | 0.123963E+09 | 70.32 | 12-SEP-19:49 | 30.50 | 14.49 |
| October | 0.248819E+10 | 2069.25 | 18-OCT-14:20 | 22.40 | 9.40 | 0.124383E+09 | 70.33 | 21-OCT-03:49 | 9.32 | 6.84 |
| November | 0.185808E+10 | 1937.47 | 20-NOV-14:00 | 14.40 | 4.74 | 0.114336E+09 | 70.33 | 13-NOV-21:00 | 14.40 | 4.74 |
| December | 0.162458E+10 | 1752.16 | 31-DEC-14:30 | 10.55 | 1.91 | 0.103290E+09 | 70.32 | 01-DEC-19:00 | 10.55 | 1.91 |
| Annual Sum or Average | 0.248995E+11 | 0.139614E+10 | ||||||||
| Minimum of Months | 0.144381E+10 | 1449.67 | 10.55 | 1.91 | 94400319.50 | 70.32 | 5.00 | 0.22 | ||
| Maximum of Months | 0.288444E+10 | 2132.68 | 37.80 | 17.92 | 0.129276E+09 | 70.33 | 37.80 | 17.92 |
Report: ZoneCoolingSummaryMonthly
For: T SW APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.766377E+09 | 2261.53 | 23-JAN-15:30 | 15.60 | 4.85 | 85069010.73 | 70.29 | 01-JAN-18:30 | 15.60 | 4.85 |
| February | 0.861948E+09 | 2756.61 | 14-FEB-15:30 | 21.95 | 7.62 | 78488205.92 | 70.33 | 20-FEB-18:10 | 8.12 | 2.80 |
| March | 0.100805E+10 | 2588.70 | 12-MAR-16:03 | 19.60 | 6.14 | 89106254.22 | 70.37 | 13-MAR-20:00 | 11.70 | 3.39 |
| April | 0.171332E+10 | 3092.35 | 13-APR-16:03 | 25.68 | 10.12 | 0.103773E+09 | 70.38 | 13-APR-23:49 | 14.08 | 4.42 |
| May | 0.219564E+10 | 3368.11 | 19-MAY-16:30 | 30.00 | 12.36 | 0.114148E+09 | 70.37 | 22-MAY-04:30 | 17.25 | 12.03 |
| June | 0.328107E+10 | 3960.22 | 28-JUN-16:30 | 38.35 | 14.13 | 0.116851E+09 | 70.39 | 21-JUN-02:30 | 38.35 | 14.13 |
| July | 0.407192E+10 | 4030.82 | 22-JUL-15:30 | 37.50 | 16.28 | 0.129175E+09 | 70.33 | 08-JUL-01:39 | 37.50 | 16.28 |
| August | 0.396299E+10 | 4121.27 | 20-AUG-16:08 | 34.90 | 15.92 | 0.123635E+09 | 70.38 | 24-AUG-05:10 | 16.70 | 13.83 |
| September | 0.317018E+10 | 3916.55 | 21-SEP-15:20 | 30.00 | 14.18 | 0.120596E+09 | 70.37 | 13-SEP-03:09 | 30.00 | 14.18 |
| October | 0.219923E+10 | 3635.13 | 05-OCT-15:20 | 26.70 | 12.21 | 0.108221E+09 | 70.36 | 01-OCT-02:20 | 26.70 | 12.21 |
| November | 0.108574E+10 | 2420.43 | 20-NOV-15:20 | 15.00 | 5.04 | 87124834.44 | 70.37 | 23-NOV-19:19 | 11.50 | 3.78 |
| December | 0.756870E+09 | 2364.65 | 31-DEC-15:30 | 10.55 | 1.85 | 84895559.51 | 70.40 | 29-DEC-19:10 | 10.55 | 1.85 |
| Annual Sum or Average | 0.250733E+11 | 0.124108E+10 | ||||||||
| Minimum of Months | 0.756870E+09 | 2261.53 | 10.55 | 1.85 | 78488205.92 | 70.29 | 8.12 | 1.85 | ||
| Maximum of Months | 0.407192E+10 | 4121.27 | 38.35 | 16.28 | 0.129175E+09 | 70.40 | 38.35 | 16.28 |
Report: ZoneCoolingSummaryMonthly
For: T NW APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.100061E+09 | 428.88 | 13-JAN-17:33 | 3.87 | -0.5 | 78617781.41 | 45.12 | 23-JAN-18:10 | 8.77 | 1.10 |
| February | 0.175746E+09 | 743.69 | 14-FEB-16:30 | 21.65 | 7.55 | 73281315.63 | 61.14 | 14-FEB-18:40 | 14.43 | 4.62 |
| March | 0.355394E+09 | 1051.44 | 08-MAR-16:30 | 22.50 | 8.65 | 87511753.06 | 70.17 | 08-MAR-21:10 | 13.62 | 5.13 |
| April | 0.112961E+10 | 2587.45 | 13-APR-16:27 | 25.85 | 10.20 | 0.102127E+09 | 70.35 | 12-APR-23:19 | 25.85 | 10.20 |
| May | 0.194618E+10 | 3186.62 | 19-MAY-16:40 | 30.00 | 12.30 | 0.116676E+09 | 70.37 | 20-MAY-02:00 | 16.10 | 5.15 |
| June | 0.329554E+10 | 3907.60 | 28-JUN-16:30 | 38.35 | 14.13 | 0.121351E+09 | 70.38 | 11-JUN-00:30 | 38.35 | 14.13 |
| July | 0.389991E+10 | 3891.59 | 04-JUL-17:20 | 35.37 | 14.44 | 0.128683E+09 | 70.35 | 08-JUL-01:39 | 16.70 | 15.02 |
| August | 0.344784E+10 | 3553.28 | 20-AUG-17:05 | 34.40 | 15.58 | 0.128400E+09 | 70.37 | 25-AUG-02:49 | 16.10 | 13.69 |
| September | 0.218078E+10 | 3030.19 | 02-SEP-16:30 | 31.10 | 15.79 | 0.120318E+09 | 70.39 | 14-SEP-02:00 | 16.70 | 11.16 |
| October | 0.953759E+09 | 2382.62 | 06-OCT-16:13 | 27.43 | 12.32 | 0.102971E+09 | 70.38 | 01-OCT-01:39 | 27.43 | 12.32 |
| November | 0.215537E+09 | 365.74 | 20-NOV-20:50 | 6.33 | 1.01 | 78527984.60 | 61.39 | 02-NOV-20:10 | 6.33 | 1.01 |
| December | 78844024.43 | 375.28 | 30-DEC-17:35 | 6.07 | -0.9 | 78092933.36 | 42.51 | 04-DEC-22:00 | 6.07 | -0.9 |
| Annual Sum or Average | 0.177792E+11 | 0.121656E+10 | ||||||||
| Minimum of Months | 78844024.43 | 365.74 | 3.87 | -0.9 | 73281315.63 | 42.51 | 6.07 | -0.9 | ||
| Maximum of Months | 0.389991E+10 | 3907.60 | 38.35 | 15.79 | 0.128683E+09 | 70.39 | 38.35 | 15.02 |
Report: ZoneCoolingSummaryMonthly
For: T SE APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.750980E+09 | 1911.30 | 23-JAN-14:20 | 14.80 | 4.45 | 84946780.31 | 70.27 | 02-JAN-16:10 | 14.80 | 4.45 |
| February | 0.822050E+09 | 2322.71 | 14-FEB-14:30 | 21.15 | 7.16 | 78038295.06 | 70.39 | 10-FEB-18:00 | 21.15 | 7.16 |
| March | 0.102212E+10 | 2315.20 | 08-MAR-14:00 | 22.80 | 9.68 | 88921603.18 | 70.36 | 11-MAR-19:30 | 8.35 | 0.65 |
| April | 0.180706E+10 | 2676.46 | 28-APR-13:00 | 24.40 | 9.84 | 0.104385E+09 | 70.39 | 03-APR-19:30 | 24.40 | 9.84 |
| May | 0.229359E+10 | 2755.89 | 19-MAY-12:50 | 28.72 | 12.76 | 0.114595E+09 | 70.38 | 07-MAY-23:19 | 28.72 | 12.76 |
| June | 0.342230E+10 | 3315.72 | 29-JUN-14:40 | 37.43 | 15.77 | 0.117182E+09 | 70.38 | 02-JUN-23:40 | 37.43 | 15.77 |
| July | 0.426337E+10 | 3549.74 | 22-JUL-14:00 | 37.80 | 17.92 | 0.129204E+09 | 70.36 | 08-JUL-01:00 | 37.80 | 17.92 |
| August | 0.410524E+10 | 3415.34 | 17-AUG-13:30 | 33.35 | 17.85 | 0.123686E+09 | 70.37 | 31-AUG-06:49 | 16.97 | 12.72 |
| September | 0.322027E+10 | 3713.67 | 03-SEP-13:30 | 31.95 | 16.76 | 0.120686E+09 | 70.38 | 20-SEP-01:19 | 15.53 | 8.86 |
| October | 0.220423E+10 | 3317.52 | 01-OCT-13:30 | 27.75 | 13.90 | 0.108401E+09 | 70.39 | 07-OCT-02:00 | 17.20 | 11.01 |
| November | 0.106916E+10 | 2069.18 | 20-NOV-13:50 | 14.22 | 4.64 | 86692278.52 | 70.38 | 07-NOV-19:19 | 14.22 | 4.64 |
| December | 0.729199E+09 | 1939.61 | 31-DEC-14:30 | 10.55 | 1.91 | 84556659.65 | 70.31 | 24-DEC-17:40 | 10.55 | 1.91 |
| Annual Sum or Average | 0.257096E+11 | 0.124129E+10 | ||||||||
| Minimum of Months | 0.729199E+09 | 1911.30 | 10.55 | 1.91 | 78038295.06 | 70.27 | 8.35 | 0.65 | ||
| Maximum of Months | 0.426337E+10 | 3713.67 | 37.80 | 17.92 | 0.129204E+09 | 70.39 | 37.80 | 17.92 |
Report: ZoneCoolingSummaryMonthly
For: T NE APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 82759838.22 | 319.56 | 23-JAN-18:12 | 8.13 | 0.77 | 78082356.78 | 42.51 | 15-JAN-22:49 | 8.13 | 0.77 |
| February | 0.148900E+09 | 362.71 | 28-FEB-19:30 | 6.40 | 1.45 | 72350316.76 | 58.45 | 14-FEB-18:49 | 6.40 | 1.45 |
| March | 0.353682E+09 | 632.64 | 26-MAR-15:10 | 20.60 | 7.74 | 86728062.21 | 69.07 | 26-MAR-20:10 | 12.20 | 3.73 |
| April | 0.119512E+10 | 1799.36 | 28-APR-15:10 | 25.00 | 10.42 | 0.102684E+09 | 70.36 | 25-APR-22:00 | 25.00 | 10.42 |
| May | 0.204660E+10 | 2291.05 | 19-MAY-16:15 | 30.00 | 12.41 | 0.117142E+09 | 70.38 | 11-MAY-22:19 | 30.00 | 12.41 |
| June | 0.344315E+10 | 3140.22 | 29-JUN-15:10 | 37.43 | 15.90 | 0.121555E+09 | 70.38 | 14-JUN-02:39 | 37.43 | 15.90 |
| July | 0.409243E+10 | 2986.46 | 22-JUL-15:10 | 38.03 | 16.57 | 0.128701E+09 | 70.33 | 19-JUL-00:30 | 38.03 | 16.57 |
| August | 0.358954E+10 | 2708.47 | 20-AUG-16:07 | 34.90 | 15.92 | 0.128441E+09 | 70.39 | 31-AUG-02:20 | 16.10 | 11.81 |
| September | 0.222046E+10 | 2458.28 | 03-SEP-14:10 | 32.43 | 16.67 | 0.120391E+09 | 70.38 | 28-SEP-00:00 | 17.20 | 8.58 |
| October | 0.924524E+09 | 1783.96 | 01-OCT-15:10 | 28.40 | 12.95 | 0.102656E+09 | 70.38 | 02-OCT-05:10 | 17.12 | 12.75 |
| November | 0.215552E+09 | 378.37 | 07-NOV-09:30 | 5.80 | 1.45 | 77342128.89 | 53.90 | 01-NOV-00:10 | 5.80 | 1.45 |
| December | 32657380.92 | 311.89 | 30-DEC-12:00 | 8.30 | 1.54 | 77901039.80 | 42.51 | 04-DEC-22:00 | 8.30 | 1.54 |
| Annual Sum or Average | 0.183454E+11 | 0.121397E+10 | ||||||||
| Minimum of Months | 32657380.92 | 311.89 | 5.80 | 0.77 | 72350316.76 | 42.51 | 5.80 | 0.77 | ||
| Maximum of Months | 0.409243E+10 | 3140.22 | 38.03 | 16.67 | 0.128701E+09 | 70.39 | 38.03 | 16.57 |
Report: ZoneCoolingSummaryMonthly
For: T N1 APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.106748E+09 | 370.06 | 02-JAN-18:12 | 6.10 | 1.60 | 78140603.73 | 42.51 | 15-JAN-22:49 | 1.70 | -1.8 |
| February | 0.171059E+09 | 412.38 | 11-FEB-21:10 | 4.45 | 0.04 | 72619774.59 | 58.39 | 14-FEB-18:49 | 13.87 | 4.41 |
| March | 0.363586E+09 | 444.37 | 17-MAR-20:00 | 3.30 | 2.28 | 86890475.73 | 68.88 | 26-MAR-20:10 | 12.20 | 3.73 |
| April | 0.915074E+09 | 1392.02 | 27-APR-16:27 | 24.15 | 9.44 | 0.104127E+09 | 70.37 | 29-APR-01:19 | 15.20 | 4.83 |
| May | 0.158480E+10 | 1860.56 | 19-MAY-17:10 | 29.90 | 12.04 | 0.119402E+09 | 70.40 | 19-MAY-04:40 | 29.90 | 12.04 |
| June | 0.261208E+10 | 2390.97 | 29-JUN-15:10 | 37.43 | 15.90 | 0.122723E+09 | 70.38 | 21-JUN-03:30 | 37.43 | 15.90 |
| July | 0.314208E+10 | 2335.05 | 04-JUL-17:04 | 35.73 | 14.63 | 0.128757E+09 | 70.33 | 19-JUL-00:30 | 23.05 | 12.37 |
| August | 0.276390E+10 | 2159.37 | 20-AUG-16:20 | 34.80 | 15.86 | 0.128662E+09 | 70.36 | 30-AUG-03:49 | 16.02 | 14.36 |
| September | 0.175381E+10 | 1846.73 | 03-SEP-14:10 | 32.43 | 16.67 | 0.122310E+09 | 70.39 | 21-SEP-01:10 | 15.50 | 7.62 |
| October | 0.805313E+09 | 1458.88 | 01-OCT-16:10 | 28.35 | 13.47 | 0.104526E+09 | 70.40 | 16-OCT-20:19 | 12.93 | 5.48 |
| November | 0.258617E+09 | 365.12 | 20-NOV-20:50 | 6.33 | 1.01 | 77938678.64 | 59.08 | 02-NOV-20:10 | 6.33 | 1.01 |
| December | 58394807.46 | 313.68 | 02-DEC-18:01 | 8.25 | 1.04 | 77926038.24 | 42.51 | 20-DEC-22:49 | -1.0 | -3.5 |
| Annual Sum or Average | 0.145355E+11 | 0.122402E+10 | ||||||||
| Minimum of Months | 58394807.46 | 313.68 | 3.30 | 0.04 | 72619774.59 | 42.51 | -1.0 | -3.5 | ||
| Maximum of Months | 0.314208E+10 | 2390.97 | 37.43 | 16.67 | 0.128757E+09 | 70.40 | 37.43 | 15.90 |
Report: ZoneCoolingSummaryMonthly
For: T N2 APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.105473E+09 | 365.41 | 23-JAN-18:50 | 6.23 | -0.7 | 78126207.90 | 42.51 | 15-JAN-22:49 | 6.23 | -0.7 |
| February | 0.169537E+09 | 398.59 | 11-FEB-21:00 | 5.00 | 0.35 | 72564177.16 | 58.23 | 14-FEB-18:49 | 13.87 | 4.41 |
| March | 0.366285E+09 | 445.86 | 17-MAR-20:00 | 3.30 | 2.28 | 86893234.24 | 69.00 | 26-MAR-20:10 | 12.20 | 3.73 |
| April | 0.926264E+09 | 1393.97 | 28-APR-16:08 | 25.00 | 10.41 | 0.104229E+09 | 70.38 | 29-APR-01:19 | 15.20 | 4.83 |
| May | 0.159574E+10 | 1838.05 | 19-MAY-17:20 | 29.80 | 11.90 | 0.119434E+09 | 70.40 | 19-MAY-04:40 | 29.80 | 11.90 |
| June | 0.262102E+10 | 2389.70 | 29-JUN-15:10 | 37.43 | 15.90 | 0.122727E+09 | 70.38 | 11-JUN-00:00 | 37.43 | 15.90 |
| July | 0.315086E+10 | 2313.48 | 04-JUL-17:10 | 35.73 | 14.63 | 0.128757E+09 | 70.33 | 08-JUL-04:00 | 16.70 | 14.90 |
| August | 0.277116E+10 | 2144.15 | 20-AUG-16:20 | 34.80 | 15.86 | 0.128661E+09 | 70.36 | 30-AUG-03:49 | 16.02 | 14.36 |
| September | 0.175971E+10 | 1851.76 | 03-SEP-14:10 | 32.43 | 16.67 | 0.122288E+09 | 70.38 | 08-SEP-00:30 | 16.10 | 11.64 |
| October | 0.809393E+09 | 1450.04 | 01-OCT-16:10 | 28.35 | 13.47 | 0.104536E+09 | 70.38 | 11-OCT-02:09 | 18.22 | 13.75 |
| November | 0.257301E+09 | 364.32 | 23-NOV-21:00 | 6.70 | 1.32 | 77865499.03 | 58.15 | 02-NOV-20:10 | 6.70 | 1.32 |
| December | 56872260.58 | 297.13 | 02-DEC-12:20 | 8.87 | 2.26 | 77920837.89 | 42.51 | 20-DEC-22:49 | -1.0 | -3.5 |
| Annual Sum or Average | 0.145896E+11 | 0.122400E+10 | ||||||||
| Minimum of Months | 56872260.58 | 297.13 | 3.30 | -0.7 | 72564177.16 | 42.51 | -1.0 | -3.5 | ||
| Maximum of Months | 0.315086E+10 | 2389.70 | 37.43 | 16.67 | 0.128757E+09 | 70.40 | 37.43 | 15.90 |
Report: ZoneCoolingSummaryMonthly
For: T S1 APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.891037E+09 | 1915.97 | 02-JAN-14:30 | 14.15 | 5.57 | 87279767.61 | 70.38 | 09-JAN-18:00 | 6.10 | 0.21 |
| February | 0.926395E+09 | 2147.21 | 14-FEB-14:50 | 21.52 | 7.30 | 80646934.28 | 70.38 | 14-FEB-21:10 | 10.10 | 3.17 |
| March | 0.101970E+10 | 2004.09 | 08-MAR-14:00 | 22.80 | 9.68 | 91701878.40 | 70.38 | 25-MAR-21:10 | 11.02 | 3.04 |
| April | 0.149859E+10 | 2124.51 | 26-APR-14:10 | 25.60 | 10.05 | 0.107256E+09 | 70.40 | 06-APR-18:00 | 25.60 | 10.05 |
| May | 0.182902E+10 | 2128.25 | 19-MAY-14:10 | 29.08 | 12.74 | 0.117050E+09 | 70.40 | 25-MAY-22:30 | 13.60 | 10.19 |
| June | 0.259464E+10 | 2544.83 | 29-JUN-15:10 | 37.43 | 15.90 | 0.118259E+09 | 70.39 | 19-JUN-03:20 | 37.43 | 15.90 |
| July | 0.331452E+10 | 2774.65 | 22-JUL-14:00 | 37.80 | 17.92 | 0.129255E+09 | 70.33 | 19-JUL-00:30 | 37.80 | 17.92 |
| August | 0.328288E+10 | 2771.12 | 20-AUG-15:20 | 35.00 | 15.76 | 0.123871E+09 | 70.36 | 29-AUG-02:00 | 16.10 | 12.92 |
| September | 0.276182E+10 | 3067.40 | 03-SEP-13:30 | 31.95 | 16.76 | 0.122478E+09 | 70.38 | 16-SEP-01:39 | 14.07 | 11.30 |
| October | 0.207666E+10 | 2884.29 | 01-OCT-13:40 | 27.93 | 13.82 | 0.112060E+09 | 70.39 | 23-OCT-21:40 | 12.07 | 6.35 |
| November | 0.121214E+10 | 2073.63 | 20-NOV-14:00 | 14.40 | 4.74 | 90949426.11 | 70.39 | 07-NOV-20:49 | 14.40 | 4.74 |
| December | 0.911061E+09 | 2013.08 | 31-DEC-14:40 | 10.73 | 2.01 | 87403675.05 | 70.36 | 10-DEC-16:49 | 10.73 | 2.01 |
| Annual Sum or Average | 0.223185E+11 | 0.126821E+10 | ||||||||
| Minimum of Months | 0.891037E+09 | 1915.97 | 10.73 | 2.01 | 80646934.28 | 70.33 | 6.10 | 0.21 | ||
| Maximum of Months | 0.331452E+10 | 3067.40 | 37.80 | 17.92 | 0.129255E+09 | 70.40 | 37.80 | 17.92 |
Report: ZoneCoolingSummaryMonthly
For: T S2 APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.895161E+09 | 1924.03 | 02-JAN-14:30 | 14.15 | 5.57 | 87244064.46 | 70.39 | 03-JAN-18:00 | 6.10 | 1.24 |
| February | 0.929749E+09 | 2155.57 | 14-FEB-14:50 | 21.52 | 7.30 | 80578093.20 | 70.39 | 26-FEB-16:10 | 12.62 | 4.44 |
| March | 0.102837E+10 | 2023.77 | 08-MAR-14:00 | 22.80 | 9.68 | 91679157.44 | 70.39 | 27-MAR-19:40 | 12.80 | 4.52 |
| April | 0.151291E+10 | 2140.59 | 28-APR-13:40 | 24.40 | 10.14 | 0.107285E+09 | 70.39 | 15-APR-01:39 | 24.40 | 10.14 |
| May | 0.184069E+10 | 2139.33 | 19-MAY-13:30 | 28.90 | 12.73 | 0.117065E+09 | 70.39 | 19-MAY-04:49 | 28.90 | 12.73 |
| June | 0.260422E+10 | 2545.52 | 29-JUN-14:40 | 37.43 | 15.77 | 0.118263E+09 | 70.39 | 17-JUN-04:19 | 37.43 | 15.77 |
| July | 0.332344E+10 | 2783.77 | 22-JUL-14:00 | 37.80 | 17.92 | 0.129256E+09 | 70.33 | 19-JUL-00:30 | 37.80 | 17.92 |
| August | 0.329016E+10 | 2765.43 | 20-AUG-15:20 | 35.00 | 15.76 | 0.123870E+09 | 70.38 | 29-AUG-05:49 | 15.60 | 13.17 |
| September | 0.276689E+10 | 3078.75 | 03-SEP-13:30 | 31.95 | 16.76 | 0.122465E+09 | 70.39 | 21-SEP-03:09 | 14.40 | 7.35 |
| October | 0.208332E+10 | 2894.88 | 01-OCT-13:40 | 27.93 | 13.82 | 0.112027E+09 | 70.39 | 23-OCT-21:00 | 11.70 | 6.25 |
| November | 0.121762E+10 | 2090.48 | 01-NOV-13:00 | 13.30 | 7.71 | 90887817.67 | 70.37 | 18-NOV-19:49 | 8.48 | 1.13 |
| December | 0.914956E+09 | 2020.07 | 31-DEC-14:40 | 10.73 | 2.01 | 87345587.60 | 70.36 | 10-DEC-16:49 | 10.73 | 2.01 |
| Annual Sum or Average | 0.224075E+11 | 0.126796E+10 | ||||||||
| Minimum of Months | 0.895161E+09 | 1924.03 | 10.73 | 2.01 | 80578093.20 | 70.33 | 6.10 | 1.13 | ||
| Maximum of Months | 0.332344E+10 | 3078.75 | 37.80 | 17.92 | 0.129256E+09 | 70.39 | 37.80 | 17.92 |
Report: ZoneCoolingSummaryMonthly
For: T CORRIDOR
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 2.30 | -1.2 | 0.128140E+09 | 96.06 | 23-JAN-18:10 | 8.77 | 1.10 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | -3.2 | -5.2 | 0.127870E+09 | 120.55 | 14-FEB-21:10 | 10.10 | 3.17 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 2.47 | -0.8 | 0.168808E+09 | 134.18 | 26-MAR-20:10 | 12.20 | 3.73 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 7.00 | 2.84 | 0.212328E+09 | 156.73 | 13-APR-20:10 | 19.68 | 7.16 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 14.45 | 4.92 | 0.246773E+09 | 169.57 | 19-MAY-20:10 | 25.22 | 9.14 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 | 8.96 | 0.270174E+09 | 182.24 | 28-JUN-20:10 | 29.82 | 16.20 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 | 14.90 | 0.294098E+09 | 184.47 | 21-JUL-20:10 | 30.50 | 12.95 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 20.95 | 16.86 | 0.289765E+09 | 180.24 | 20-AUG-20:10 | 29.32 | 14.89 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 21.88 | 14.47 | 0.259917E+09 | 170.06 | 02-SEP-20:10 | 24.63 | 13.78 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 17.33 | 10.88 | 0.214290E+09 | 159.04 | 01-OCT-20:10 | 20.92 | 12.39 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 12.83 | 5.34 | 0.148982E+09 | 120.10 | 02-NOV-20:10 | 12.80 | 4.49 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 5.13 | 1.84 | 0.126317E+09 | 93.56 | 31-DEC-21:10 | 5.68 | -1.0 |
| Annual Sum or Average | 0.00 | 0.248746E+10 | ||||||||
| Minimum of Months | 0.00 | 0.00 | -3.2 | -5.2 | 0.126317E+09 | 93.56 | 5.68 | -1.0 | ||
| Maximum of Months | 0.00 | 0.00 | 21.95 | 16.86 | 0.294098E+09 | 184.47 | 30.50 | 16.20 |
Report: ZoneCoolingSummaryMonthly
For: G CORRIDOR
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 2.30 | -1.2 | 0.100708E+09 | 90.84 | 01-JAN-23:19 | 4.07 | 0.05 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | -3.2 | -5.2 | 96637965.57 | 99.57 | 14-FEB-23:10 | 10.50 | 3.53 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 2.47 | -0.8 | 0.133828E+09 | 104.99 | 13-MAR-21:49 | 12.62 | 3.92 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 7.00 | 2.84 | 0.187772E+09 | 149.11 | 29-APR-21:49 | 17.30 | 6.22 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 14.45 | 4.92 | 0.241504E+09 | 172.03 | 19-MAY-17:10 | 29.90 | 12.04 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 | 8.96 | 0.283927E+09 | 244.12 | 28-JUN-17:10 | 37.23 | 14.64 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 | 14.90 | 0.315000E+09 | 244.06 | 21-JUL-17:10 | 37.52 | 14.82 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 20.95 | 16.86 | 0.306563E+09 | 220.16 | 20-AUG-17:10 | 34.40 | 15.58 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 21.88 | 14.47 | 0.272878E+09 | 188.45 | 02-SEP-17:10 | 30.92 | 15.53 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 17.33 | 10.88 | 0.227963E+09 | 168.88 | 01-OCT-21:49 | 20.00 | 12.09 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 12.83 | 5.34 | 0.147278E+09 | 130.01 | 01-NOV-04:40 | 8.17 | 5.81 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 5.13 | 1.84 | 0.103358E+09 | 97.33 | 01-DEC-22:49 | 7.15 | 1.50 |
| Annual Sum or Average | 0.00 | 0.241742E+10 | ||||||||
| Minimum of Months | 0.00 | 0.00 | -3.2 | -5.2 | 96637965.57 | 90.84 | 4.07 | 0.05 | ||
| Maximum of Months | 0.00 | 0.00 | 21.95 | 16.86 | 0.315000E+09 | 244.12 | 37.52 | 15.58 |
Report: ZoneCoolingSummaryMonthly
For: M CORRIDOR
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 2.30 | -1.2 | 0.180385E+09 | 116.23 | 03-JAN-21:10 | 3.25 | -0.5 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | -3.2 | -5.2 | 0.171018E+09 | 128.81 | 15-FEB-21:10 | 7.62 | 2.97 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 2.47 | -0.8 | 0.217411E+09 | 136.03 | 26-MAR-20:10 | 12.20 | 3.73 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 7.00 | 2.84 | 0.253043E+09 | 156.76 | 29-APR-20:10 | 19.63 | 7.40 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 14.45 | 4.92 | 0.272987E+09 | 160.50 | 19-MAY-20:10 | 25.22 | 9.14 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 | 8.96 | 0.276456E+09 | 166.50 | 28-JUN-20:10 | 29.82 | 16.20 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 | 14.90 | 0.290500E+09 | 167.59 | 21-JUL-20:10 | 30.50 | 12.95 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 20.95 | 16.86 | 0.288953E+09 | 166.12 | 20-AUG-20:10 | 29.32 | 14.89 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 21.88 | 14.47 | 0.272497E+09 | 161.85 | 02-SEP-20:10 | 24.63 | 13.78 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 17.33 | 10.88 | 0.255970E+09 | 157.83 | 01-OCT-20:10 | 20.92 | 12.39 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 12.83 | 5.34 | 0.203485E+09 | 138.64 | 02-NOV-21:10 | 12.33 | 5.44 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 5.13 | 1.84 | 0.179211E+09 | 113.14 | 31-DEC-22:10 | 5.92 | -0.5 |
| Annual Sum or Average | 0.00 | 0.286192E+10 | ||||||||
| Minimum of Months | 0.00 | 0.00 | -3.2 | -5.2 | 0.171018E+09 | 113.14 | 3.25 | -0.5 | ||
| Maximum of Months | 0.00 | 0.00 | 21.95 | 16.86 | 0.290500E+09 | 167.59 | 30.50 | 16.20 |
Report: ZoneHeatingSummaryMonthly
For: G SW APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.154155E+09 | 728.87 | 18-JAN-01:50 | -2.2 |
| February | 0.120169E+09 | 708.56 | 06-FEB-05:00 | -4.4 |
| March | 48486357.44 | 586.41 | 04-MAR-06:00 | -1.7 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 7.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 14.45 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 20.95 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 21.88 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 17.33 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 12.83 |
| December | 41098416.64 | 451.76 | 09-DEC-05:00 | -5.6 |
| Annual Sum or Average | 0.363908E+09 | |||
| Minimum of Months | 0.00 | 0.00 | -5.6 | |
| Maximum of Months | 0.154155E+09 | 728.87 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: G NW APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.809574E+09 | 980.99 | 17-JAN-08:18 | -3.5 |
| February | 0.679504E+09 | 1135.09 | 06-FEB-05:00 | -4.4 |
| March | 0.280536E+09 | 765.04 | 04-MAR-06:00 | -1.7 |
| April | 9681225.06 | 266.60 | 08-APR-02:70 | 3.30 |
| May | 41625.52 | 12.53 | 07-MAY-14:40 | 23.70 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 20.95 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 21.88 |
| October | 9404.97 | 8.20 | 31-OCT-14:40 | 23.53 |
| November | 47332676.30 | 430.77 | 26-NOV-06:00 | 0.60 |
| December | 0.630298E+09 | 933.86 | 14-DEC-04:00 | -1.1 |
| Annual Sum or Average | 0.245698E+10 | |||
| Minimum of Months | 0.00 | 0.00 | -4.4 | |
| Maximum of Months | 0.809574E+09 | 1135.09 | 23.70 |
Report: ZoneHeatingSummaryMonthly
For: OFFICE
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 54339340.17 | 9169.94 | 19-JAN-08:61 | -2.7 |
| February | 40774667.26 | 9185.12 | 07-FEB-08:61 | -1.4 |
| March | 0.100735E+09 | 354.76 | 26-MAR-16:00 | 20.60 |
| April | 0.232227E+09 | 505.18 | 13-APR-16:12 | 25.77 |
| May | 0.365276E+09 | 631.39 | 19-MAY-16:12 | 30.00 |
| June | 0.460562E+09 | 857.24 | 28-JUN-16:13 | 38.53 |
| July | 0.478126E+09 | 828.45 | 21-JUL-17:12 | 37.23 |
| August | 0.399640E+09 | 719.68 | 01-AUG-16:13 | 34.43 |
| September | 0.275227E+09 | 562.62 | 20-SEP-16:13 | 30.20 |
| October | 0.121305E+09 | 488.70 | 11-OCT-07:04 | 18.07 |
| November | 11550780.05 | 401.47 | 09-NOV-09:05 | 14.60 |
| December | 3768682.05 | 4611.20 | 22-DEC-08:61 | -6.0 |
| Annual Sum or Average | 0.254353E+10 | |||
| Minimum of Months | 3768682.05 | 354.76 | -6.0 | |
| Maximum of Months | 0.478126E+09 | 9185.12 | 38.53 |
Report: ZoneHeatingSummaryMonthly
For: G NE APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.785187E+09 | 984.89 | 17-JAN-08:18 | -3.5 |
| February | 0.682046E+09 | 1144.30 | 06-FEB-05:00 | -4.4 |
| March | 0.245005E+09 | 762.97 | 04-MAR-06:00 | -1.7 |
| April | 11139093.69 | 285.80 | 08-APR-02:70 | 3.30 |
| May | 1160.34 | 1.93 | 07-MAY-14:00 | 23.30 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 20.95 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 21.88 |
| October | 16753.58 | 12.72 | 31-OCT-14:50 | 23.72 |
| November | 44667914.23 | 433.02 | 26-NOV-06:00 | 0.60 |
| December | 0.603172E+09 | 956.09 | 14-DEC-04:00 | -1.1 |
| Annual Sum or Average | 0.237124E+10 | |||
| Minimum of Months | 0.00 | 0.00 | -4.4 | |
| Maximum of Months | 0.785187E+09 | 1144.30 | 23.72 |
Report: ZoneHeatingSummaryMonthly
For: G N1 APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.252034E+09 | 463.25 | 17-JAN-08:18 | -3.5 |
| February | 0.225637E+09 | 586.36 | 06-FEB-05:00 | -4.4 |
| March | 41318597.09 | 337.19 | 05-MAR-04:00 | -1.1 |
| April | 1508721.53 | 65.81 | 01-APR-15:00 | 24.40 |
| May | 108247.24 | 23.65 | 07-MAY-15:30 | 24.15 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 20.95 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 21.88 |
| October | 99047.89 | 24.14 | 31-OCT-15:00 | 23.90 |
| November | 1514500.67 | 105.56 | 28-NOV-05:00 | -1.1 |
| December | 0.159574E+09 | 459.03 | 14-DEC-04:00 | -1.1 |
| Annual Sum or Average | 0.681794E+09 | |||
| Minimum of Months | 0.00 | 0.00 | -4.4 | |
| Maximum of Months | 0.252034E+09 | 586.36 | 24.40 |
Report: ZoneHeatingSummaryMonthly
For: G N2 APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.252783E+09 | 463.53 | 17-JAN-08:18 | -3.5 |
| February | 0.226735E+09 | 586.74 | 06-FEB-05:00 | -4.4 |
| March | 41044008.75 | 337.62 | 05-MAR-04:00 | -1.1 |
| April | 1451396.46 | 65.49 | 01-APR-15:00 | 24.40 |
| May | 70983.43 | 20.52 | 07-MAY-15:10 | 23.98 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 20.95 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 21.88 |
| October | 94980.54 | 23.64 | 31-OCT-15:00 | 23.90 |
| November | 1511536.65 | 107.34 | 28-NOV-05:00 | -1.1 |
| December | 0.159860E+09 | 459.01 | 14-DEC-04:00 | -1.1 |
| Annual Sum or Average | 0.683551E+09 | |||
| Minimum of Months | 0.00 | 0.00 | -4.4 | |
| Maximum of Months | 0.252783E+09 | 586.74 | 24.40 |
Report: ZoneHeatingSummaryMonthly
For: G S1 APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 16120785.58 | 232.32 | 18-JAN-01:50 | -2.2 |
| February | 3561061.80 | 193.54 | 06-FEB-05:00 | -4.4 |
| March | 1966650.64 | 123.40 | 04-MAR-05:00 | -1.1 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 7.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 14.45 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 20.95 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 21.88 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 17.33 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 12.83 |
| December | 246976.91 | 58.07 | 09-DEC-05:00 | -5.6 |
| Annual Sum or Average | 21895474.93 | |||
| Minimum of Months | 0.00 | 0.00 | -5.6 | |
| Maximum of Months | 16120785.58 | 232.32 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: G S2 APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 24909648.96 | 269.29 | 18-JAN-02:00 | -2.2 |
| February | 6006771.82 | 255.39 | 06-FEB-05:00 | -4.4 |
| March | 1623857.97 | 113.26 | 04-MAR-05:00 | -1.1 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 7.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 14.45 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 20.95 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 21.88 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 17.33 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 12.83 |
| December | 251626.59 | 58.17 | 09-DEC-05:00 | -5.6 |
| Annual Sum or Average | 32791905.34 | |||
| Minimum of Months | 0.00 | 0.00 | -5.6 | |
| Maximum of Months | 24909648.96 | 269.29 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: M SW APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 83481240.36 | 780.49 | 18-JAN-01:10 | -2.2 |
| February | 27515829.55 | 633.06 | 06-FEB-05:00 | -4.4 |
| March | 3646474.80 | 269.52 | 04-MAR-06:00 | -1.7 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 7.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 14.45 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 20.95 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 21.88 |
| October | 645310.84 | 115.99 | 26-OCT-04:00 | -2.8 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 12.83 |
| December | 35006425.28 | 559.07 | 22-DEC-07:00 | -6.1 |
| Annual Sum or Average | 0.150295E+09 | |||
| Minimum of Months | 0.00 | 0.00 | -6.1 | |
| Maximum of Months | 83481240.36 | 780.49 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: M NW APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.426767E+09 | 913.57 | 18-JAN-01:10 | -2.2 |
| February | 0.255810E+09 | 951.76 | 06-FEB-05:00 | -4.4 |
| March | 24228722.49 | 463.30 | 04-MAR-06:00 | -1.7 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 7.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 14.45 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 20.95 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 21.88 |
| October | 4727280.07 | 236.06 | 26-OCT-04:00 | -2.8 |
| November | 57925460.20 | 637.01 | 26-NOV-06:00 | 0.60 |
| December | 0.459809E+09 | 1081.52 | 14-DEC-04:00 | -1.1 |
| Annual Sum or Average | 0.122927E+10 | |||
| Minimum of Months | 0.00 | 0.00 | -4.4 | |
| Maximum of Months | 0.459809E+09 | 1081.52 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: M SE APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 92401685.37 | 789.59 | 18-JAN-01:10 | -2.2 |
| February | 29805875.74 | 635.19 | 06-FEB-05:00 | -4.4 |
| March | 2687848.03 | 245.21 | 04-MAR-06:00 | -1.7 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 7.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 14.45 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 20.95 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 21.88 |
| October | 688982.50 | 120.12 | 26-OCT-04:00 | -2.8 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 12.83 |
| December | 34664442.19 | 539.38 | 22-DEC-07:00 | -6.1 |
| Annual Sum or Average | 0.160249E+09 | |||
| Minimum of Months | 0.00 | 0.00 | -6.1 | |
| Maximum of Months | 92401685.37 | 789.59 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: M NE APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.429133E+09 | 929.55 | 18-JAN-01:10 | -2.2 |
| February | 0.254780E+09 | 961.73 | 06-FEB-05:00 | -4.4 |
| March | 21419640.53 | 462.89 | 04-MAR-06:00 | -1.7 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 7.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 14.45 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 20.95 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 21.88 |
| October | 3668560.87 | 228.57 | 26-OCT-04:00 | -2.8 |
| November | 56809139.15 | 648.65 | 26-NOV-06:00 | 0.60 |
| December | 0.429947E+09 | 1107.46 | 14-DEC-04:00 | -1.1 |
| Annual Sum or Average | 0.119576E+10 | |||
| Minimum of Months | 0.00 | 0.00 | -4.4 | |
| Maximum of Months | 0.429947E+09 | 1107.46 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: M N1 APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 46837804.45 | 356.80 | 17-JAN-04:00 | -3.3 |
| February | 42331413.43 | 379.44 | 06-FEB-05:00 | -4.4 |
| March | 199237.54 | 44.33 | 05-MAR-05:00 | -1.7 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 7.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 14.45 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 20.95 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 21.88 |
| October | 16896.00 | 12.59 | 31-OCT-14:50 | 23.72 |
| November | 1841539.30 | 126.76 | 28-NOV-05:00 | -1.1 |
| December | 50590005.79 | 484.80 | 14-DEC-04:00 | -1.1 |
| Annual Sum or Average | 0.141817E+09 | |||
| Minimum of Months | 0.00 | 0.00 | -4.4 | |
| Maximum of Months | 50590005.79 | 484.80 | 23.72 |
Report: ZoneHeatingSummaryMonthly
For: M N2 APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 47794908.05 | 358.02 | 17-JAN-04:00 | -3.3 |
| February | 42523924.97 | 379.77 | 06-FEB-05:00 | -4.4 |
| March | 215576.13 | 47.06 | 05-MAR-05:00 | -1.7 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 7.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 14.45 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 20.95 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 21.88 |
| October | 7826.77 | 8.08 | 31-OCT-14:40 | 23.53 |
| November | 1871193.30 | 126.95 | 28-NOV-05:00 | -1.1 |
| December | 50990609.01 | 485.43 | 14-DEC-04:00 | -1.1 |
| Annual Sum or Average | 0.143404E+09 | |||
| Minimum of Months | 0.00 | 0.00 | -4.4 | |
| Maximum of Months | 50990609.01 | 485.43 | 23.53 |
Report: ZoneHeatingSummaryMonthly
For: M S1 APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 4299640.86 | 206.77 | 18-JAN-02:00 | -2.2 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | -3.2 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 2.47 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 7.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 14.45 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 20.95 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 21.88 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 17.33 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 12.83 |
| December | 62806.12 | 28.86 | 09-DEC-05:00 | -5.6 |
| Annual Sum or Average | 4362446.98 | |||
| Minimum of Months | 0.00 | 0.00 | -5.6 | |
| Maximum of Months | 4299640.86 | 206.77 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: M S2 APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 4349750.52 | 207.02 | 18-JAN-02:00 | -2.2 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | -3.2 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 2.47 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 7.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 14.45 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 20.95 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 21.88 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 17.33 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 12.83 |
| December | 63181.20 | 28.78 | 09-DEC-05:00 | -5.6 |
| Annual Sum or Average | 4412931.72 | |||
| Minimum of Months | 0.00 | 0.00 | -5.6 | |
| Maximum of Months | 4349750.52 | 207.02 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: T SW APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.116277E+10 | 1962.37 | 17-JAN-04:00 | -3.3 |
| February | 0.810362E+09 | 2034.77 | 06-FEB-05:00 | -4.4 |
| March | 0.410785E+09 | 1511.96 | 04-MAR-06:00 | -1.7 |
| April | 67704743.78 | 738.09 | 08-APR-05:00 | 2.80 |
| May | 25830887.82 | 609.58 | 05-MAY-05:00 | 5.60 |
| June | 635843.69 | 137.46 | 09-JUN-03:50 | 7.98 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 20.95 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 21.88 |
| October | 0.142366E+09 | 1342.04 | 26-OCT-04:00 | -2.8 |
| November | 0.423140E+09 | 1477.90 | 26-NOV-06:50 | 0.10 |
| December | 0.109043E+10 | 1911.78 | 22-DEC-07:00 | -6.1 |
| Annual Sum or Average | 0.413402E+10 | |||
| Minimum of Months | 0.00 | 0.00 | -6.1 | |
| Maximum of Months | 0.116277E+10 | 2034.77 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: T NW APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.189552E+10 | 2061.07 | 17-JAN-04:00 | -3.3 |
| February | 0.133960E+10 | 2171.89 | 06-FEB-05:00 | -4.4 |
| March | 0.630834E+09 | 1569.79 | 04-MAR-06:00 | -1.7 |
| April | 0.104768E+09 | 856.71 | 08-APR-05:00 | 2.80 |
| May | 26737697.42 | 639.24 | 05-MAY-05:00 | 5.60 |
| June | 365837.80 | 176.49 | 09-JUN-03:50 | 7.98 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 20.95 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 21.88 |
| October | 0.243141E+09 | 1358.77 | 26-OCT-04:00 | -2.8 |
| November | 0.892126E+09 | 1748.84 | 26-NOV-06:00 | 0.60 |
| December | 0.198707E+10 | 2181.11 | 14-DEC-04:00 | -1.1 |
| Annual Sum or Average | 0.712016E+10 | |||
| Minimum of Months | 0.00 | 0.00 | -4.4 | |
| Maximum of Months | 0.198707E+10 | 2181.11 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: T SE APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.115384E+10 | 1978.88 | 17-JAN-04:00 | -3.3 |
| February | 0.805413E+09 | 2041.98 | 06-FEB-05:00 | -4.4 |
| March | 0.380105E+09 | 1520.34 | 04-MAR-06:00 | -1.7 |
| April | 60584306.93 | 771.92 | 08-APR-05:00 | 2.80 |
| May | 15880876.57 | 548.52 | 05-MAY-05:00 | 5.60 |
| June | 136287.22 | 93.76 | 09-JUN-03:50 | 7.98 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 20.95 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 21.88 |
| October | 0.139060E+09 | 1348.69 | 26-OCT-04:00 | -2.8 |
| November | 0.418682E+09 | 1498.06 | 26-NOV-06:50 | 0.10 |
| December | 0.108506E+10 | 1900.91 | 22-DEC-07:00 | -6.1 |
| Annual Sum or Average | 0.405876E+10 | |||
| Minimum of Months | 0.00 | 0.00 | -6.1 | |
| Maximum of Months | 0.115384E+10 | 2041.98 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: T NE APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.184753E+10 | 2078.86 | 17-JAN-04:00 | -3.3 |
| February | 0.131199E+10 | 2180.80 | 06-FEB-05:00 | -4.4 |
| March | 0.574131E+09 | 1578.69 | 04-MAR-06:00 | -1.7 |
| April | 96338127.10 | 912.83 | 08-APR-05:00 | 2.80 |
| May | 18409586.07 | 575.14 | 05-MAY-05:00 | 5.60 |
| June | 198390.04 | 126.01 | 09-JUN-03:50 | 7.98 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 20.95 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 21.88 |
| October | 0.224954E+09 | 1363.99 | 26-OCT-04:00 | -2.8 |
| November | 0.849698E+09 | 1767.68 | 26-NOV-06:00 | 0.60 |
| December | 0.193188E+10 | 2210.17 | 14-DEC-04:00 | -1.1 |
| Annual Sum or Average | 0.685513E+10 | |||
| Minimum of Months | 0.00 | 0.00 | -4.4 | |
| Maximum of Months | 0.193188E+10 | 2210.17 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: T N1 APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.107229E+10 | 1277.96 | 17-JAN-04:00 | -3.3 |
| February | 0.727344E+09 | 1387.68 | 06-FEB-05:00 | -4.4 |
| March | 0.255636E+09 | 940.12 | 04-MAR-06:00 | -1.7 |
| April | 25722963.50 | 445.98 | 08-APR-05:00 | 2.80 |
| May | 3291937.20 | 228.21 | 05-MAY-05:00 | 5.60 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 20.95 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 21.88 |
| October | 0.102831E+09 | 837.92 | 26-OCT-04:00 | -2.8 |
| November | 0.430987E+09 | 1030.46 | 26-NOV-06:00 | 0.60 |
| December | 0.113617E+10 | 1331.06 | 14-DEC-04:00 | -1.1 |
| Annual Sum or Average | 0.375428E+10 | |||
| Minimum of Months | 0.00 | 0.00 | -4.4 | |
| Maximum of Months | 0.113617E+10 | 1387.68 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: T N2 APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.107470E+10 | 1278.87 | 17-JAN-04:00 | -3.3 |
| February | 0.730151E+09 | 1388.25 | 06-FEB-05:00 | -4.4 |
| March | 0.255363E+09 | 941.14 | 04-MAR-06:00 | -1.7 |
| April | 25517185.22 | 448.59 | 08-APR-05:00 | 2.80 |
| May | 2973742.55 | 215.24 | 05-MAY-05:00 | 5.60 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 20.95 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 21.88 |
| October | 0.103358E+09 | 838.93 | 26-OCT-04:00 | -2.8 |
| November | 0.432590E+09 | 1030.35 | 26-NOV-06:00 | 0.60 |
| December | 0.113724E+10 | 1334.34 | 14-DEC-04:00 | -1.1 |
| Annual Sum or Average | 0.376190E+10 | |||
| Minimum of Months | 0.00 | 0.00 | -4.4 | |
| Maximum of Months | 0.113724E+10 | 1388.25 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: T S1 APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.498750E+09 | 1176.42 | 18-JAN-02:00 | -2.2 |
| February | 0.322521E+09 | 1227.83 | 06-FEB-05:00 | -4.4 |
| March | 0.110069E+09 | 872.74 | 04-MAR-06:00 | -1.7 |
| April | 8460443.88 | 294.95 | 08-APR-05:00 | 2.80 |
| May | 2478492.04 | 194.79 | 05-MAY-05:00 | 5.60 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 20.95 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 21.88 |
| October | 51026886.14 | 817.67 | 26-OCT-04:00 | -2.8 |
| November | 0.117803E+09 | 731.65 | 26-NOV-06:00 | 0.60 |
| December | 0.452904E+09 | 1174.19 | 22-DEC-07:00 | -6.1 |
| Annual Sum or Average | 0.156401E+10 | |||
| Minimum of Months | 0.00 | 0.00 | -6.1 | |
| Maximum of Months | 0.498750E+09 | 1227.83 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: T S2 APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.500768E+09 | 1177.07 | 18-JAN-02:00 | -2.2 |
| February | 0.324714E+09 | 1227.84 | 06-FEB-05:00 | -4.4 |
| March | 0.110304E+09 | 873.76 | 04-MAR-06:00 | -1.7 |
| April | 8212813.89 | 296.78 | 08-APR-05:00 | 2.80 |
| May | 2136982.25 | 181.40 | 05-MAY-05:00 | 5.60 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 20.95 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 21.88 |
| October | 51196630.15 | 817.90 | 26-OCT-04:00 | -2.8 |
| November | 0.118610E+09 | 733.17 | 26-NOV-06:00 | 0.60 |
| December | 0.454720E+09 | 1172.97 | 22-DEC-07:00 | -6.1 |
| Annual Sum or Average | 0.157066E+10 | |||
| Minimum of Months | 0.00 | 0.00 | -6.1 | |
| Maximum of Months | 0.500768E+09 | 1227.84 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: T CORRIDOR
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 2.30 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | -3.2 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 2.47 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 7.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 14.45 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 20.95 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 21.88 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 17.33 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 12.83 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 5.13 |
| Annual Sum or Average | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | -3.2 | |
| Maximum of Months | 0.00 | 0.00 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: G CORRIDOR
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 2.30 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | -3.2 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 2.47 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 7.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 14.45 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 20.95 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 21.88 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 17.33 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 12.83 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 5.13 |
| Annual Sum or Average | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | -3.2 | |
| Maximum of Months | 0.00 | 0.00 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: M CORRIDOR
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 2.30 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | -3.2 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 2.47 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 7.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 14.45 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 20.95 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 21.88 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 17.33 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 12.83 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 5.13 |
| Annual Sum or Average | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | -3.2 | |
| Maximum of Months | 0.00 | 0.00 | 21.95 |
Report: ZoneElectricSummaryMonthly
For: G SW APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: G NW APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: OFFICE
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.609777E+09 | 582.92 | 03-JAN-08:09 | 0.787690E+09 | 588.62 | 03-JAN-08:09 |
| February | 0.564682E+09 | 582.92 | 01-FEB-08:09 | 0.723971E+09 | 588.62 | 01-FEB-08:09 |
| March | 0.654405E+09 | 582.92 | 01-MAR-08:09 | 0.827804E+09 | 588.62 | 01-MAR-08:09 |
| April | 0.599704E+09 | 582.92 | 03-APR-07:10 | 0.770907E+09 | 588.62 | 03-APR-07:10 |
| May | 0.639529E+09 | 582.92 | 01-MAY-07:10 | 0.814432E+09 | 588.62 | 01-MAY-07:10 |
| June | 0.629456E+09 | 582.92 | 01-JUN-07:10 | 0.797650E+09 | 588.62 | 01-JUN-07:10 |
| July | 0.609777E+09 | 582.92 | 03-JUL-07:10 | 0.787690E+09 | 588.62 | 03-JUL-07:10 |
| August | 0.654405E+09 | 582.92 | 01-AUG-07:10 | 0.827804E+09 | 588.62 | 01-AUG-07:10 |
| September | 0.599704E+09 | 582.92 | 01-SEP-07:10 | 0.770907E+09 | 588.62 | 01-SEP-07:10 |
| October | 0.624653E+09 | 582.92 | 02-OCT-07:10 | 0.801061E+09 | 588.62 | 02-OCT-07:10 |
| November | 0.599704E+09 | 582.92 | 01-NOV-07:10 | 0.770907E+09 | 588.62 | 01-NOV-07:10 |
| December | 0.609777E+09 | 582.92 | 01-DEC-08:09 | 0.787690E+09 | 588.62 | 01-DEC-08:09 |
| Annual Sum or Average | 0.739557E+10 | 0.946851E+10 | ||||
| Minimum of Months | 0.564682E+09 | 582.92 | 0.723971E+09 | 588.62 | ||
| Maximum of Months | 0.654405E+09 | 582.92 | 0.827804E+09 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: G NE APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: G N1 APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: G N2 APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: G S1 APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: G S2 APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: M SW APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: M NW APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: M SE APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: M NE APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: M N1 APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: M N2 APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: M S1 APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: M S2 APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: T SW APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: T NW APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: T SE APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: T NE APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: T N1 APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: T N2 APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: T S1 APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: T S2 APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: T CORRIDOR
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
| January | 0.992689E+09 | 370.63 | 01-JAN-00:10 | 0.00 | 0.00 |
| February | 0.896622E+09 | 370.63 | 01-FEB-00:10 | 0.00 | 0.00 |
| March | 0.992689E+09 | 370.63 | 01-MAR-00:10 | 0.00 | 0.00 |
| April | 0.960667E+09 | 370.63 | 01-APR-00:10 | 0.00 | 0.00 |
| May | 0.992689E+09 | 370.63 | 01-MAY-00:10 | 0.00 | 0.00 |
| June | 0.960667E+09 | 370.63 | 01-JUN-00:10 | 0.00 | 0.00 |
| July | 0.992689E+09 | 370.63 | 01-JUL-00:10 | 0.00 | 0.00 |
| August | 0.992689E+09 | 370.63 | 01-AUG-00:10 | 0.00 | 0.00 |
| September | 0.960667E+09 | 370.63 | 01-SEP-00:10 | 0.00 | 0.00 |
| October | 0.992689E+09 | 370.63 | 01-OCT-00:10 | 0.00 | 0.00 |
| November | 0.960667E+09 | 370.63 | 01-NOV-00:10 | 0.00 | 0.00 |
| December | 0.992689E+09 | 370.63 | 01-DEC-00:10 | 0.00 | 0.00 |
| Annual Sum or Average | 0.116881E+11 | 0.00 | 0.00 | ||
| Minimum of Months | 0.896622E+09 | 370.63 | 0.00 | 0.00 | |
| Maximum of Months | 0.992689E+09 | 370.63 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: G CORRIDOR
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.992689E+09 | 370.63 | 01-JAN-00:10 | 0.599555E+10 | 4168.07 | 01-JAN-07:10 |
| February | 0.896622E+09 | 370.63 | 01-FEB-00:10 | 0.541534E+10 | 4168.07 | 01-FEB-07:10 |
| March | 0.992689E+09 | 370.63 | 01-MAR-00:10 | 0.599555E+10 | 4168.07 | 01-MAR-07:10 |
| April | 0.960667E+09 | 370.63 | 01-APR-00:10 | 0.580215E+10 | 4168.07 | 01-APR-06:10 |
| May | 0.992689E+09 | 370.63 | 01-MAY-00:10 | 0.599555E+10 | 4168.07 | 01-MAY-06:10 |
| June | 0.960667E+09 | 370.63 | 01-JUN-00:10 | 0.580215E+10 | 4168.07 | 01-JUN-06:10 |
| July | 0.992689E+09 | 370.63 | 01-JUL-00:10 | 0.599555E+10 | 4168.07 | 01-JUL-06:10 |
| August | 0.992689E+09 | 370.63 | 01-AUG-00:10 | 0.599555E+10 | 4168.07 | 01-AUG-06:10 |
| September | 0.960667E+09 | 370.63 | 01-SEP-00:10 | 0.580215E+10 | 4168.07 | 01-SEP-06:10 |
| October | 0.992689E+09 | 370.63 | 01-OCT-00:10 | 0.599555E+10 | 4168.07 | 01-OCT-06:10 |
| November | 0.960667E+09 | 370.63 | 01-NOV-00:10 | 0.580215E+10 | 4168.07 | 01-NOV-06:10 |
| December | 0.992689E+09 | 370.63 | 01-DEC-00:10 | 0.599555E+10 | 4168.07 | 01-DEC-07:10 |
| Annual Sum or Average | 0.116881E+11 | 0.705928E+11 | ||||
| Minimum of Months | 0.896622E+09 | 370.63 | 0.541534E+10 | 4168.07 | ||
| Maximum of Months | 0.992689E+09 | 370.63 | 0.599555E+10 | 4168.07 |
Report: ZoneElectricSummaryMonthly
For: M CORRIDOR
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
| January | 0.992689E+09 | 370.63 | 01-JAN-00:10 | 0.00 | 0.00 |
| February | 0.896622E+09 | 370.63 | 01-FEB-00:10 | 0.00 | 0.00 |
| March | 0.992689E+09 | 370.63 | 01-MAR-00:10 | 0.00 | 0.00 |
| April | 0.960667E+09 | 370.63 | 01-APR-00:10 | 0.00 | 0.00 |
| May | 0.992689E+09 | 370.63 | 01-MAY-00:10 | 0.00 | 0.00 |
| June | 0.960667E+09 | 370.63 | 01-JUN-00:10 | 0.00 | 0.00 |
| July | 0.992689E+09 | 370.63 | 01-JUL-00:10 | 0.00 | 0.00 |
| August | 0.992689E+09 | 370.63 | 01-AUG-00:10 | 0.00 | 0.00 |
| September | 0.960667E+09 | 370.63 | 01-SEP-00:10 | 0.00 | 0.00 |
| October | 0.992689E+09 | 370.63 | 01-OCT-00:10 | 0.00 | 0.00 |
| November | 0.960667E+09 | 370.63 | 01-NOV-00:10 | 0.00 | 0.00 |
| December | 0.992689E+09 | 370.63 | 01-DEC-00:10 | 0.00 | 0.00 |
| Annual Sum or Average | 0.116881E+11 | 0.00 | 0.00 | ||
| Minimum of Months | 0.896622E+09 | 370.63 | 0.00 | 0.00 | |
| Maximum of Months | 0.992689E+09 | 370.63 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: G SW APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.315989E+09 |
| February | 0.389025E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.302070E+09 |
| March | 0.418950E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.291301E+09 |
| April | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1397478.17 | 0.185042E+09 |
| May | 0.424935E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11395514.77 | 0.137390E+09 |
| June | 0.406980E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 50628447.14 | 60506926.71 |
| July | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 64069779.83 | 21405266.20 |
| August | 0.418950E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 38409199.36 | 35704560.24 |
| September | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13365485.96 | 65049065.49 |
| October | 0.430920E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3335152.33 | 0.159610E+09 |
| November | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.265414E+09 |
| December | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.290248E+09 |
| Annual Sum or Average | 0.505732E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.182601E+09 | 0.212973E+10 |
| Minimum of Months | 0.389025E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21405266.20 |
| Maximum of Months | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 64069779.83 | 0.315989E+09 |
Report: SpaceGainsMonthly
For: G NW APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.305637E+09 |
| February | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.291639E+09 |
| March | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6770.30 | 0.274945E+09 |
| April | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1462684.87 | 0.171582E+09 |
| May | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11395541.73 | 0.135014E+09 |
| June | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 50628459.09 | 60546056.94 |
| July | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 64069789.70 | 21405265.12 |
| August | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 38409204.96 | 35704549.51 |
| September | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13365487.84 | 65043157.07 |
| October | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3335155.74 | 0.153315E+09 |
| November | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.238094E+09 |
| December | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.279579E+09 |
| Annual Sum or Average | 0.512427E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.182673E+09 | 0.203250E+10 |
| Minimum of Months | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21405265.12 |
| Maximum of Months | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 64069789.70 | 0.305637E+09 |
Report: SpaceGainsMonthly
For: OFFICE
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.227408E+09 | 0.609777E+09 | 0.787690E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.310724E+09 |
| February | 0.216037E+09 | 0.564682E+09 | 0.723971E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.299493E+09 |
| March | 0.261519E+09 | 0.654405E+09 | 0.827804E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.312301E+09 |
| April | 0.227408E+09 | 0.599704E+09 | 0.770907E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 677923.41 | 0.215695E+09 |
| May | 0.250148E+09 | 0.639529E+09 | 0.814432E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5029535.19 | 0.174325E+09 |
| June | 0.250148E+09 | 0.629456E+09 | 0.797650E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 29268695.07 | 94239438.22 |
| July | 0.227408E+09 | 0.609777E+09 | 0.787690E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 35653719.31 | 63628818.26 |
| August | 0.261519E+09 | 0.654405E+09 | 0.827804E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 21623991.03 | 84718897.14 |
| September | 0.227408E+09 | 0.599704E+09 | 0.770907E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7593499.68 | 0.109097E+09 |
| October | 0.238778E+09 | 0.624653E+09 | 0.801061E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2471463.15 | 0.195528E+09 |
| November | 0.227408E+09 | 0.599704E+09 | 0.770907E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.277630E+09 |
| December | 0.227408E+09 | 0.609777E+09 | 0.787690E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.291580E+09 |
| Annual Sum or Average | 0.284259E+10 | 0.739557E+10 | 0.946851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102319E+09 | 0.242896E+10 |
| Minimum of Months | 0.216037E+09 | 0.564682E+09 | 0.723971E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63628818.26 |
| Maximum of Months | 0.261519E+09 | 0.654405E+09 | 0.827804E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 35653719.31 | 0.312301E+09 |
Report: SpaceGainsMonthly
For: G NE APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.305531E+09 |
| February | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.291363E+09 |
| March | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9529.98 | 0.274619E+09 |
| April | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1491622.60 | 0.174085E+09 |
| May | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11395564.22 | 0.137416E+09 |
| June | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 50628491.97 | 60844257.58 |
| July | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 64069812.86 | 21405262.45 |
| August | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 38409223.17 | 35704553.67 |
| September | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13365492.58 | 65039443.73 |
| October | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3335159.49 | 0.153704E+09 |
| November | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.237674E+09 |
| December | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.279488E+09 |
| Annual Sum or Average | 0.512427E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.182705E+09 | 0.203687E+10 |
| Minimum of Months | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21405262.45 |
| Maximum of Months | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 64069812.86 | 0.305531E+09 |
Report: SpaceGainsMonthly
For: G N1 APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.184327E+09 |
| February | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.175839E+09 |
| March | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15837.55 | 0.165991E+09 |
| April | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 942110.54 | 0.105151E+09 |
| May | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6873950.63 | 83619320.82 |
| June | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30537851.81 | 36938562.50 |
| July | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 38645298.45 | 12911105.07 |
| August | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23167481.05 | 21536064.62 |
| September | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8061743.05 | 39235525.32 |
| October | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2012631.46 | 93594807.55 |
| November | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.144719E+09 |
| December | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.168682E+09 |
| Annual Sum or Average | 0.512427E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110257E+09 | 0.123255E+10 |
| Minimum of Months | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12911105.07 |
| Maximum of Months | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 38645298.45 | 0.184327E+09 |
Report: SpaceGainsMonthly
For: G N2 APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.184326E+09 |
| February | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1.07 | 0.175832E+09 |
| March | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15645.40 | 0.166025E+09 |
| April | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 939906.79 | 0.105349E+09 |
| May | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6873610.88 | 83779449.12 |
| June | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30537852.16 | 36948057.71 |
| July | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 38645298.69 | 12911105.11 |
| August | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23167478.24 | 21536064.62 |
| September | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8061743.07 | 39235514.51 |
| October | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2012468.25 | 93629855.53 |
| November | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.144732E+09 |
| December | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.168679E+09 |
| Annual Sum or Average | 0.512427E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110254E+09 | 0.123298E+10 |
| Minimum of Months | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12911105.11 |
| Maximum of Months | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 38645298.69 | 0.184326E+09 |
Report: SpaceGainsMonthly
For: G S1 APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.194609E+09 |
| February | 0.389025E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.185827E+09 |
| March | 0.418950E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.182158E+09 |
| April | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 842939.09 | 0.115081E+09 |
| May | 0.424935E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6873521.00 | 85072768.10 |
| June | 0.406980E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30537841.58 | 36919694.13 |
| July | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 38645289.70 | 12911106.16 |
| August | 0.418950E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23167475.74 | 21536071.39 |
| September | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8061738.92 | 39236971.34 |
| October | 0.430920E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2011685.39 | 97190629.08 |
| November | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.164401E+09 |
| December | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.179512E+09 |
| Annual Sum or Average | 0.505732E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110140E+09 | 0.131446E+10 |
| Minimum of Months | 0.389025E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12911106.16 |
| Maximum of Months | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 38645289.70 | 0.194609E+09 |
Report: SpaceGainsMonthly
For: G S2 APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.194650E+09 |
| February | 0.389025E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.185905E+09 |
| March | 0.418950E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.183323E+09 |
| April | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 842937.04 | 0.115971E+09 |
| May | 0.424935E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6873516.66 | 85702572.51 |
| June | 0.406980E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30537841.27 | 36997929.21 |
| July | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 38645292.56 | 12911110.84 |
| August | 0.418950E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23167476.24 | 21536077.52 |
| September | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8061739.69 | 39236979.58 |
| October | 0.430920E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2011685.61 | 97335688.42 |
| November | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.164716E+09 |
| December | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.179629E+09 |
| Annual Sum or Average | 0.505732E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110140E+09 | 0.131791E+10 |
| Minimum of Months | 0.389025E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12911110.84 |
| Maximum of Months | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 38645292.56 | 0.194650E+09 |
Report: SpaceGainsMonthly
For: M SW APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.465488E+09 |
| February | 0.389025E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.452702E+09 |
| March | 0.418950E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.456751E+09 |
| April | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1961589.45 | 0.283226E+09 |
| May | 0.424935E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16243287.17 | 0.205772E+09 |
| June | 0.406980E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 72489715.86 | 88168586.56 |
| July | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 91745313.93 | 30973476.62 |
| August | 0.418950E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 54952282.99 | 51605493.01 |
| September | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19076421.16 | 93795178.95 |
| October | 0.430920E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4743053.16 | 0.228247E+09 |
| November | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.380556E+09 |
| December | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.426425E+09 |
| Annual Sum or Average | 0.505732E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.261212E+09 | 0.316371E+10 |
| Minimum of Months | 0.389025E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30973476.62 |
| Maximum of Months | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 91745313.93 | 0.465488E+09 |
Report: SpaceGainsMonthly
For: M NW APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.441581E+09 |
| February | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.425403E+09 |
| March | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.423187E+09 |
| April | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1961602.57 | 0.277303E+09 |
| May | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16243300.92 | 0.204905E+09 |
| June | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 72489730.87 | 88241889.47 |
| July | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 91745323.81 | 30973476.94 |
| August | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 54952294.27 | 51605480.44 |
| September | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19076424.98 | 93766455.42 |
| October | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4743058.83 | 0.219391E+09 |
| November | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.345834E+09 |
| December | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.402818E+09 |
| Annual Sum or Average | 0.512427E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.261212E+09 | 0.300501E+10 |
| Minimum of Months | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30973476.94 |
| Maximum of Months | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 91745323.81 | 0.441581E+09 |
Report: SpaceGainsMonthly
For: M SE APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.466307E+09 |
| February | 0.389025E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.451948E+09 |
| March | 0.418950E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.459631E+09 |
| April | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1961611.77 | 0.284181E+09 |
| May | 0.424935E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16243334.88 | 0.207631E+09 |
| June | 0.406980E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 72489791.60 | 88363613.80 |
| July | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 91745356.86 | 30973471.38 |
| August | 0.418950E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 54952317.01 | 51605486.29 |
| September | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19076449.47 | 93792162.50 |
| October | 0.430920E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4743061.99 | 0.228467E+09 |
| November | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.381397E+09 |
| December | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.426997E+09 |
| Annual Sum or Average | 0.505732E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.261212E+09 | 0.317129E+10 |
| Minimum of Months | 0.389025E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30973471.38 |
| Maximum of Months | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 91745356.86 | 0.466307E+09 |
Report: SpaceGainsMonthly
For: M NE APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.440750E+09 |
| February | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.424123E+09 |
| March | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.426474E+09 |
| April | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1961625.28 | 0.280218E+09 |
| May | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16243341.62 | 0.207306E+09 |
| June | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 72489799.79 | 88377691.23 |
| July | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 91745362.54 | 30973471.20 |
| August | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 54952323.32 | 51605476.05 |
| September | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19076446.58 | 93742987.92 |
| October | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4743066.61 | 0.220066E+09 |
| November | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.345231E+09 |
| December | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.402341E+09 |
| Annual Sum or Average | 0.512427E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.261212E+09 | 0.301121E+10 |
| Minimum of Months | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30973471.20 |
| Maximum of Months | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 91745362.54 | 0.440750E+09 |
Report: SpaceGainsMonthly
For: M N1 APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.266445E+09 |
| February | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.256793E+09 |
| March | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.260576E+09 |
| April | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1183220.39 | 0.169628E+09 |
| May | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9797613.57 | 0.125182E+09 |
| June | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 43724045.96 | 53448518.20 |
| July | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 55338496.29 | 18682401.69 |
| August | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33145868.78 | 31127094.27 |
| September | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11506450.99 | 56579803.30 |
| October | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2860904.62 | 0.134783E+09 |
| November | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.211663E+09 |
| December | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.243033E+09 |
| Annual Sum or Average | 0.512427E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.157557E+09 | 0.182794E+10 |
| Minimum of Months | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18682401.69 |
| Maximum of Months | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 55338496.29 | 0.266445E+09 |
Report: SpaceGainsMonthly
For: M N2 APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.266439E+09 |
| February | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.256755E+09 |
| March | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.260988E+09 |
| April | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1183220.29 | 0.169807E+09 |
| May | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9797613.79 | 0.125294E+09 |
| June | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 43724046.89 | 53450757.11 |
| July | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 55338496.77 | 18682401.60 |
| August | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33145869.01 | 31127094.21 |
| September | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11506451.08 | 56579745.09 |
| October | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2860903.63 | 0.134832E+09 |
| November | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.211688E+09 |
| December | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.243019E+09 |
| Annual Sum or Average | 0.512427E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.157557E+09 | 0.182866E+10 |
| Minimum of Months | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18682401.60 |
| Maximum of Months | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 55338496.77 | 0.266439E+09 |
Report: SpaceGainsMonthly
For: M S1 APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.288562E+09 |
| February | 0.389025E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.280471E+09 |
| March | 0.418950E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.284535E+09 |
| April | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1183205.96 | 0.172603E+09 |
| May | 0.424935E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9797598.98 | 0.125552E+09 |
| June | 0.406980E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 43724039.07 | 53420819.77 |
| July | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 55338488.97 | 18682401.98 |
| August | 0.418950E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33145856.34 | 31127102.07 |
| September | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11506442.93 | 56584931.24 |
| October | 0.430920E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2860899.44 | 0.139584E+09 |
| November | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.236230E+09 |
| December | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.265309E+09 |
| Annual Sum or Average | 0.505732E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.157557E+09 | 0.195266E+10 |
| Minimum of Months | 0.389025E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18682401.98 |
| Maximum of Months | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 55338488.97 | 0.288562E+09 |
Report: SpaceGainsMonthly
For: M S2 APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.288592E+09 |
| February | 0.389025E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.280413E+09 |
| March | 0.418950E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.284642E+09 |
| April | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1183206.21 | 0.172618E+09 |
| May | 0.424935E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9797599.54 | 0.125602E+09 |
| June | 0.406980E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 43724039.71 | 53425342.60 |
| July | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 55338489.44 | 18682401.91 |
| August | 0.418950E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33145861.64 | 31127101.96 |
| September | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11506443.29 | 56584895.84 |
| October | 0.430920E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2860899.63 | 0.139586E+09 |
| November | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.236238E+09 |
| December | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.265306E+09 |
| Annual Sum or Average | 0.505732E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.157557E+09 | 0.195282E+10 |
| Minimum of Months | 0.389025E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18682401.91 |
| Maximum of Months | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 55338489.44 | 0.288592E+09 |
Report: SpaceGainsMonthly
For: T SW APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.605587E+09 |
| February | 0.389025E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.587101E+09 |
| March | 0.418950E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.570630E+09 |
| April | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2472385.52 | 0.349731E+09 |
| May | 0.424935E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21136861.27 | 0.252760E+09 |
| June | 0.406980E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 95182715.76 | 0.110560E+09 |
| July | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120494E+09 | 41440218.58 |
| August | 0.418950E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 72045128.25 | 68662374.97 |
| September | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24889032.29 | 0.120959E+09 |
| October | 0.430920E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6142601.41 | 0.282392E+09 |
| November | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.474262E+09 |
| December | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.554139E+09 |
| Annual Sum or Average | 0.505732E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.342363E+09 | 0.401822E+10 |
| Minimum of Months | 0.389025E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41440218.58 |
| Maximum of Months | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120494E+09 | 0.605587E+09 |
Report: SpaceGainsMonthly
For: T NW APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.585408E+09 |
| February | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.562847E+09 |
| March | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.549177E+09 |
| April | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2472382.56 | 0.340237E+09 |
| May | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21136853.17 | 0.251333E+09 |
| June | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 95182695.19 | 0.111175E+09 |
| July | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120494E+09 | 41446337.58 |
| August | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 72045097.74 | 68625624.94 |
| September | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24889003.70 | 0.119530E+09 |
| October | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6142598.50 | 0.269125E+09 |
| November | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.448568E+09 |
| December | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.533453E+09 |
| Annual Sum or Average | 0.512427E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.342362E+09 | 0.388092E+10 |
| Minimum of Months | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41446337.58 |
| Maximum of Months | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120494E+09 | 0.585408E+09 |
Report: SpaceGainsMonthly
For: T SE APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.605800E+09 |
| February | 0.389025E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.586595E+09 |
| March | 0.418950E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.573691E+09 |
| April | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2472429.88 | 0.354129E+09 |
| May | 0.424935E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21136987.61 | 0.257920E+09 |
| June | 0.406980E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 95182886.35 | 0.112033E+09 |
| July | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120494E+09 | 41464436.90 |
| August | 0.418950E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 72045205.55 | 68779797.36 |
| September | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24889096.01 | 0.121228E+09 |
| October | 0.430920E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6142619.24 | 0.283309E+09 |
| November | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.475615E+09 |
| December | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.554743E+09 |
| Annual Sum or Average | 0.505732E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.342363E+09 | 0.403531E+10 |
| Minimum of Months | 0.389025E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41464436.90 |
| Maximum of Months | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120494E+09 | 0.605800E+09 |
Report: SpaceGainsMonthly
For: T NE APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.583494E+09 |
| February | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.560838E+09 |
| March | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.550061E+09 |
| April | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2472427.00 | 0.346053E+09 |
| May | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21136944.26 | 0.256375E+09 |
| June | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 95182857.31 | 0.112434E+09 |
| July | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120494E+09 | 41462744.83 |
| August | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 72045165.31 | 68726471.41 |
| September | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24889042.30 | 0.120020E+09 |
| October | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6142613.05 | 0.270263E+09 |
| November | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.446780E+09 |
| December | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.532889E+09 |
| Annual Sum or Average | 0.512427E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.342363E+09 | 0.388940E+10 |
| Minimum of Months | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41462744.83 |
| Maximum of Months | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120494E+09 | 0.583494E+09 |
Report: SpaceGainsMonthly
For: T N1 APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.352055E+09 |
| February | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.338361E+09 |
| March | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.329928E+09 |
| April | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1491324.33 | 0.207507E+09 |
| May | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12749300.09 | 0.154782E+09 |
| June | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 57411889.43 | 68745116.31 |
| July | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 72678898.47 | 25040441.82 |
| August | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 43455839.22 | 41562305.75 |
| September | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15012462.93 | 73678201.13 |
| October | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3705078.01 | 0.163956E+09 |
| November | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.269748E+09 |
| December | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.321485E+09 |
| Annual Sum or Average | 0.512427E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.206505E+09 | 0.234685E+10 |
| Minimum of Months | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25040441.82 |
| Maximum of Months | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 72678898.47 | 0.352055E+09 |
Report: SpaceGainsMonthly
For: T N2 APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.352034E+09 |
| February | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.338323E+09 |
| March | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.330149E+09 |
| April | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1491324.74 | 0.207949E+09 |
| May | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12749304.05 | 0.155044E+09 |
| June | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 57411890.07 | 68789650.72 |
| July | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 72678900.57 | 25040544.25 |
| August | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 43455840.72 | 41562219.52 |
| September | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15012464.27 | 73676245.25 |
| October | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3705078.22 | 0.164069E+09 |
| November | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.269757E+09 |
| December | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.321475E+09 |
| Annual Sum or Average | 0.512427E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.206505E+09 | 0.234787E+10 |
| Minimum of Months | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25040544.25 |
| Maximum of Months | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 72678900.57 | 0.352034E+09 |
Report: SpaceGainsMonthly
For: T S1 APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.367945E+09 |
| February | 0.389025E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.357442E+09 |
| March | 0.418950E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.348814E+09 |
| April | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1491314.97 | 0.215221E+09 |
| May | 0.424935E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12749302.27 | 0.156147E+09 |
| June | 0.406980E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 57411905.76 | 68367055.61 |
| July | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 72678905.93 | 25039292.91 |
| August | 0.418950E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 43455841.19 | 41576443.88 |
| September | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15012476.60 | 74362794.78 |
| October | 0.430920E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3705075.38 | 0.174256E+09 |
| November | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.290660E+09 |
| December | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.337396E+09 |
| Annual Sum or Average | 0.505732E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.206505E+09 | 0.245723E+10 |
| Minimum of Months | 0.389025E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25039292.91 |
| Maximum of Months | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 72678905.93 | 0.367945E+09 |
Report: SpaceGainsMonthly
For: T S2 APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.367942E+09 |
| February | 0.389025E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.357405E+09 |
| March | 0.418950E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.348953E+09 |
| April | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1491316.11 | 0.215417E+09 |
| May | 0.424935E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12749304.86 | 0.156377E+09 |
| June | 0.406980E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 57411909.47 | 68414036.68 |
| July | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 72678908.02 | 25039474.02 |
| August | 0.418950E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 43455848.05 | 41576888.84 |
| September | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15012472.49 | 74357618.00 |
| October | 0.430920E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3705075.90 | 0.174252E+09 |
| November | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.290685E+09 |
| December | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.337395E+09 |
| Annual Sum or Average | 0.505732E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.206505E+09 | 0.245781E+10 |
| Minimum of Months | 0.389025E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25039474.02 |
| Maximum of Months | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 72678908.02 | 0.367942E+09 |
Report: SpaceGainsMonthly
For: T CORRIDOR
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.727675E+09 | 0.992689E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101843E+09 |
| February | 0.657255E+09 | 0.896622E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99982881.37 |
| March | 0.727675E+09 | 0.992689E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101933E+09 |
| April | 0.704201E+09 | 0.960667E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69199840.31 |
| May | 0.727675E+09 | 0.992689E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 892951.80 | 53308722.94 |
| June | 0.704201E+09 | 0.960667E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8643555.71 | 25895018.19 |
| July | 0.727675E+09 | 0.992689E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10784855.90 | 13069763.43 |
| August | 0.727675E+09 | 0.992689E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5441129.39 | 19620480.17 |
| September | 0.704201E+09 | 0.960667E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1218867.97 | 28298289.22 |
| October | 0.727675E+09 | 0.992689E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97013.25 | 54290189.98 |
| November | 0.704201E+09 | 0.960667E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82623814.52 |
| December | 0.727675E+09 | 0.992689E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92962539.92 |
| Annual Sum or Average | 0.856778E+10 | 0.116881E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27078374.02 | 0.743028E+09 |
| Minimum of Months | 0.657255E+09 | 0.896622E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13069763.43 |
| Maximum of Months | 0.727675E+09 | 0.992689E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10784855.90 | 0.101933E+09 |
Report: SpaceGainsMonthly
For: G CORRIDOR
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.727675E+09 | 0.992689E+09 | 0.299778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.338263E+10 |
| February | 0.657255E+09 | 0.896622E+09 | 0.270767E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.271148E+10 |
| March | 0.727675E+09 | 0.992689E+09 | 0.299778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.224299E+10 |
| April | 0.704201E+09 | 0.960667E+09 | 0.290107E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2191487.83 | 0.160913E+10 |
| May | 0.727675E+09 | 0.992689E+09 | 0.299778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 35016746.37 | 0.119135E+10 |
| June | 0.704201E+09 | 0.960667E+09 | 0.290107E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.321940E+09 | 0.583239E+09 |
| July | 0.727675E+09 | 0.992689E+09 | 0.299778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.381220E+09 | 0.367367E+09 |
| August | 0.727675E+09 | 0.992689E+09 | 0.299778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.243406E+09 | 0.529782E+09 |
| September | 0.704201E+09 | 0.960667E+09 | 0.290107E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 55414066.52 | 0.868906E+09 |
| October | 0.727675E+09 | 0.992689E+09 | 0.299778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2849747.61 | 0.193278E+10 |
| November | 0.704201E+09 | 0.960667E+09 | 0.290107E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.279120E+10 |
| December | 0.727675E+09 | 0.992689E+09 | 0.299778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.354659E+10 |
| Annual Sum or Average | 0.856778E+10 | 0.116881E+11 | 0.352964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104204E+10 | 0.217574E+11 |
| Minimum of Months | 0.657255E+09 | 0.896622E+09 | 0.270767E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.367367E+09 |
| Maximum of Months | 0.727675E+09 | 0.992689E+09 | 0.299778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.381220E+09 | 0.354659E+10 |
Report: SpaceGainsMonthly
For: M CORRIDOR
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.727675E+09 | 0.992689E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84225713.54 |
| February | 0.657255E+09 | 0.896622E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82039605.50 |
| March | 0.727675E+09 | 0.992689E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85668104.99 |
| April | 0.704201E+09 | 0.960667E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58077803.27 |
| May | 0.727675E+09 | 0.992689E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 947967.84 | 44546307.84 |
| June | 0.704201E+09 | 0.960667E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7656254.60 | 20952251.38 |
| July | 0.727675E+09 | 0.992689E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9757307.63 | 9981289.25 |
| August | 0.727675E+09 | 0.992689E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5155565.68 | 15063423.68 |
| September | 0.704201E+09 | 0.960667E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1256770.61 | 22498924.44 |
| October | 0.727675E+09 | 0.992689E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 138321.56 | 46062324.28 |
| November | 0.704201E+09 | 0.960667E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69858523.24 |
| December | 0.727675E+09 | 0.992689E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76887674.11 |
| Annual Sum or Average | 0.856778E+10 | 0.116881E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24912187.91 | 0.615862E+09 |
| Minimum of Months | 0.657255E+09 | 0.896622E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9981289.25 |
| Maximum of Months | 0.727675E+09 | 0.992689E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9757307.63 | 85668104.99 |
Report: PeakSpaceGainsMonthly
For: G SW APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 598.24 | 16-JAN-18:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 467.91 | 05-FEB-01:00 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 443.54 | 14-MAR-07:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.86 | 29-APR-16:00 | 454.32 | 15-APR-12:00 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 97.28 | 19-MAY-15:00 | 309.88 | 05-MAY-08:30 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 182.65 | 17-JUN-16:00 | 194.02 | 10-JUN-01:30 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 194.80 | 04-JUL-15:00 | 81.60 | 15-JUL-19:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 118.46 | 04-AUG-18:00 | 101.83 | 25-AUG-20:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 76.92 | 03-SEP-15:00 | 137.23 | 18-SEP-01:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 79.91 | 11-OCT-13:00 | 433.21 | 24-OCT-17:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 454.76 | 26-NOV-06:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 636.81 | 14-DEC-04:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81.60 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 194.80 | 636.81 |
Report: PeakSpaceGainsMonthly
For: G NW APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 598.24 | 16-JAN-18:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 467.91 | 05-FEB-01:00 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.61 | 08-MAR-14:00 | 443.54 | 14-MAR-07:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.86 | 29-APR-16:00 | 435.65 | 15-APR-12:00 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 97.28 | 19-MAY-15:00 | 308.24 | 05-MAY-08:00 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 182.65 | 17-JUN-16:00 | 194.37 | 10-JUN-01:30 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 194.80 | 04-JUL-15:00 | 81.60 | 15-JUL-19:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 118.46 | 04-AUG-18:00 | 101.83 | 25-AUG-20:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 76.92 | 03-SEP-15:00 | 137.23 | 18-SEP-01:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 79.91 | 11-OCT-13:00 | 416.62 | 24-OCT-17:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 448.13 | 26-NOV-06:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 636.81 | 14-DEC-04:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81.60 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 194.80 | 636.81 |
Report: PeakSpaceGainsMonthly
For: OFFICE
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 451.21 | 03-JAN-08:09 | 582.92 | 03-JAN-08:09 | 588.62 | 03-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 552.54 | 16-JAN-18:00 |
| February | 451.21 | 01-FEB-08:09 | 582.92 | 01-FEB-08:09 | 588.62 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 424.92 | 05-FEB-01:00 |
| March | 451.21 | 01-MAR-08:09 | 582.92 | 01-MAR-08:09 | 588.62 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 469.37 | 14-MAR-07:00 |
| April | 451.21 | 03-APR-07:10 | 582.92 | 03-APR-07:10 | 588.62 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 30.52 | 26-APR-15:00 | 507.51 | 15-APR-12:00 |
| May | 451.21 | 01-MAY-07:10 | 582.92 | 01-MAY-07:10 | 588.62 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 97.28 | 19-MAY-15:00 | 377.84 | 05-MAY-08:50 |
| June | 451.21 | 01-JUN-07:10 | 582.92 | 01-JUN-07:10 | 588.62 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 167.09 | 26-JUN-16:00 | 224.06 | 10-JUN-01:00 |
| July | 451.21 | 03-JUL-07:10 | 582.92 | 03-JUL-07:10 | 588.62 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 146.84 | 19-JUL-16:00 | 156.65 | 15-JUL-19:00 |
| August | 451.21 | 01-AUG-07:10 | 582.92 | 01-AUG-07:10 | 588.62 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 110.21 | 02-AUG-13:00 | 175.60 | 22-AUG-21:00 |
| September | 451.21 | 01-SEP-07:10 | 582.92 | 01-SEP-07:10 | 588.62 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 61.79 | 22-SEP-14:00 | 206.24 | 17-SEP-20:00 |
| October | 451.21 | 02-OCT-07:10 | 582.92 | 02-OCT-07:10 | 588.62 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 79.89 | 11-OCT-13:00 | 456.94 | 24-OCT-17:00 |
| November | 451.21 | 01-NOV-07:10 | 582.92 | 01-NOV-07:10 | 588.62 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 473.93 | 03-NOV-24:00 |
| December | 451.21 | 01-DEC-08:09 | 582.92 | 01-DEC-08:09 | 588.62 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 616.42 | 14-DEC-04:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 451.21 | 582.92 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 156.65 | |||||
| Maximum of Months | 451.21 | 582.92 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 167.09 | 616.42 |
Report: PeakSpaceGainsMonthly
For: G NE APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 598.24 | 16-JAN-18:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 467.91 | 05-FEB-01:00 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.98 | 08-MAR-14:00 | 443.54 | 14-MAR-07:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.86 | 29-APR-16:00 | 447.05 | 15-APR-12:00 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 97.28 | 19-MAY-15:00 | 332.63 | 05-MAY-08:50 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 182.65 | 17-JUN-16:00 | 194.30 | 10-JUN-01:30 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 194.80 | 04-JUL-15:00 | 81.60 | 15-JUL-19:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 118.46 | 04-AUG-18:00 | 101.83 | 25-AUG-20:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 76.92 | 03-SEP-15:00 | 137.23 | 18-SEP-01:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 79.91 | 11-OCT-13:00 | 419.23 | 24-OCT-17:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 448.13 | 26-NOV-06:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 636.81 | 14-DEC-04:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81.60 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 194.80 | 636.81 |
Report: PeakSpaceGainsMonthly
For: G N1 APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 360.84 | 16-JAN-18:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 282.23 | 05-FEB-01:00 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.75 | 08-MAR-14:00 | 267.53 | 14-MAR-07:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.22 | 29-APR-16:00 | 273.07 | 15-APR-12:00 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 58.68 | 19-MAY-15:00 | 199.15 | 05-MAY-08:30 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 110.17 | 17-JUN-16:00 | 120.76 | 10-JUN-01:40 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 117.50 | 04-JUL-15:00 | 49.22 | 15-JUL-19:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 71.45 | 04-AUG-18:00 | 61.42 | 25-AUG-20:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 46.40 | 03-SEP-15:00 | 82.77 | 18-SEP-01:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 48.20 | 11-OCT-13:00 | 259.41 | 24-OCT-17:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 270.30 | 26-NOV-06:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 384.11 | 14-DEC-04:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.22 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 117.50 | 384.11 |
Report: PeakSpaceGainsMonthly
For: G N2 APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 360.84 | 16-JAN-18:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14-FEB-16:00 | 282.23 | 05-FEB-01:00 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.71 | 08-MAR-16:00 | 267.53 | 14-MAR-07:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.22 | 29-APR-16:00 | 273.73 | 15-APR-12:00 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 58.68 | 19-MAY-15:00 | 200.06 | 05-MAY-08:30 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 110.17 | 17-JUN-16:00 | 120.83 | 10-JUN-01:30 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 117.50 | 04-JUL-15:00 | 49.22 | 15-JUL-19:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 71.45 | 04-AUG-18:00 | 61.42 | 25-AUG-20:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 46.40 | 03-SEP-15:00 | 82.77 | 18-SEP-01:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 48.20 | 11-OCT-13:00 | 259.67 | 24-OCT-17:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 270.30 | 26-NOV-06:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 384.11 | 14-DEC-04:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.22 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 117.50 | 384.11 |
Report: PeakSpaceGainsMonthly
For: G S1 APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 360.84 | 16-JAN-18:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 282.23 | 05-FEB-01:00 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 284.79 | 14-MAR-07:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.22 | 29-APR-16:00 | 285.68 | 15-APR-12:00 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 58.68 | 19-MAY-15:00 | 201.77 | 05-MAY-08:50 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 110.17 | 17-JUN-16:00 | 120.56 | 10-JUN-01:40 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 117.50 | 04-JUL-15:00 | 49.22 | 15-JUL-19:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 71.45 | 04-AUG-18:00 | 61.42 | 25-AUG-20:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 46.40 | 03-SEP-15:00 | 82.77 | 18-SEP-01:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 48.20 | 11-OCT-13:00 | 268.48 | 24-OCT-17:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 287.74 | 26-NOV-06:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 384.11 | 14-DEC-04:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.22 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 117.50 | 384.11 |
Report: PeakSpaceGainsMonthly
For: G S2 APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 360.84 | 16-JAN-18:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 282.23 | 05-FEB-01:00 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 286.25 | 14-MAR-07:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.22 | 29-APR-16:00 | 287.99 | 15-APR-12:00 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 58.68 | 19-MAY-15:00 | 205.00 | 05-MAY-09:00 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 110.17 | 17-JUN-16:00 | 121.78 | 10-JUN-01:30 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 117.50 | 04-JUL-15:00 | 49.22 | 15-JUL-19:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 71.45 | 04-AUG-18:00 | 61.42 | 25-AUG-20:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 46.40 | 03-SEP-15:00 | 82.77 | 18-SEP-01:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 48.20 | 11-OCT-13:00 | 269.73 | 24-OCT-17:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 288.39 | 26-NOV-06:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 384.11 | 14-DEC-04:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.22 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 117.50 | 384.11 |
Report: PeakSpaceGainsMonthly
For: M SW APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 860.47 | 16-JAN-18:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 672.99 | 05-FEB-01:00 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 673.02 | 14-MAR-07:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 45.21 | 29-APR-16:00 | 681.30 | 15-APR-12:00 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 139.34 | 19-MAY-15:00 | 477.71 | 05-MAY-08:50 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 261.95 | 17-JUN-16:00 | 290.60 | 10-JUN-01:00 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 279.47 | 04-JUL-15:00 | 117.73 | 15-JUL-19:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 169.72 | 04-AUG-18:00 | 146.76 | 25-AUG-20:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 110.21 | 03-SEP-15:00 | 197.67 | 18-SEP-01:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 113.99 | 11-OCT-13:00 | 614.54 | 24-OCT-17:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 646.42 | 03-NOV-21:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 915.97 | 14-DEC-04:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 117.73 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 279.47 | 915.97 |
Report: PeakSpaceGainsMonthly
For: M NW APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 860.47 | 16-JAN-18:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 672.99 | 05-FEB-01:00 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 638.19 | 14-MAR-07:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 45.21 | 29-APR-16:00 | 670.45 | 15-APR-12:00 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 139.34 | 19-MAY-15:00 | 476.87 | 05-MAY-08:20 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 261.95 | 17-JUN-16:00 | 291.29 | 10-JUN-01:00 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 279.47 | 04-JUL-15:00 | 117.73 | 15-JUL-19:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 169.72 | 04-AUG-18:00 | 146.76 | 25-AUG-20:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 110.21 | 03-SEP-15:00 | 197.67 | 18-SEP-01:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 113.99 | 11-OCT-13:00 | 592.97 | 24-OCT-17:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 644.62 | 26-NOV-06:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 915.97 | 14-DEC-04:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 117.73 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 279.47 | 915.97 |
Report: PeakSpaceGainsMonthly
For: M SE APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 860.47 | 16-JAN-18:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 672.99 | 05-FEB-01:00 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 679.16 | 14-MAR-07:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 45.21 | 29-APR-16:00 | 694.03 | 15-APR-12:00 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 139.34 | 19-MAY-15:00 | 528.34 | 05-MAY-09:00 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 261.95 | 17-JUN-16:00 | 287.73 | 10-JUN-01:00 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 279.47 | 04-JUL-15:00 | 117.73 | 15-JUL-19:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 169.72 | 04-AUG-18:00 | 146.76 | 25-AUG-20:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 110.21 | 03-SEP-15:00 | 197.67 | 18-SEP-01:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 113.99 | 11-OCT-13:00 | 614.44 | 24-OCT-17:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 644.62 | 26-NOV-06:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 915.97 | 14-DEC-04:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 117.73 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 279.47 | 915.97 |
Report: PeakSpaceGainsMonthly
For: M NE APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 860.47 | 16-JAN-18:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 672.99 | 05-FEB-01:00 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 639.22 | 14-MAR-07:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 45.22 | 29-APR-16:00 | 684.50 | 15-APR-12:00 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 139.34 | 19-MAY-15:00 | 527.18 | 05-MAY-09:00 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 261.95 | 17-JUN-16:00 | 288.28 | 10-JUN-01:00 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 279.47 | 04-JUL-15:00 | 117.73 | 15-JUL-19:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 169.72 | 04-AUG-18:00 | 146.76 | 25-AUG-20:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 110.21 | 03-SEP-15:00 | 197.67 | 18-SEP-01:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 113.99 | 11-OCT-13:00 | 596.93 | 24-OCT-17:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 644.62 | 26-NOV-06:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 915.97 | 14-DEC-04:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 117.73 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 279.47 | 915.97 |
Report: PeakSpaceGainsMonthly
For: M N1 APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 519.01 | 16-JAN-18:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 405.93 | 05-FEB-01:00 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 398.06 | 14-MAR-07:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.27 | 29-APR-16:00 | 416.04 | 15-APR-12:00 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 84.05 | 19-MAY-15:00 | 307.02 | 05-MAY-08:40 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 158.00 | 17-JUN-16:00 | 178.08 | 10-JUN-01:50 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 168.57 | 04-JUL-15:00 | 71.01 | 15-JUL-19:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 102.37 | 04-AUG-18:00 | 88.52 | 25-AUG-20:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 66.47 | 03-SEP-15:00 | 119.23 | 18-SEP-01:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 68.76 | 11-OCT-13:00 | 373.40 | 24-OCT-17:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 388.82 | 26-NOV-06:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 552.49 | 14-DEC-04:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.01 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 168.57 | 552.49 |
Report: PeakSpaceGainsMonthly
For: M N2 APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 519.01 | 16-JAN-18:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 405.93 | 05-FEB-01:00 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 398.83 | 14-MAR-07:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.27 | 29-APR-16:00 | 416.51 | 15-APR-12:00 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 84.05 | 19-MAY-15:00 | 308.55 | 05-MAY-08:50 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 158.00 | 17-JUN-16:00 | 178.08 | 10-JUN-01:50 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 168.57 | 04-JUL-15:00 | 71.01 | 15-JUL-19:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 102.37 | 04-AUG-18:00 | 88.52 | 25-AUG-20:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 66.47 | 03-SEP-15:00 | 119.23 | 18-SEP-01:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 68.76 | 11-OCT-13:00 | 373.91 | 24-OCT-17:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 388.82 | 26-NOV-06:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 552.49 | 14-DEC-04:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.01 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 168.57 | 552.49 |
Report: PeakSpaceGainsMonthly
For: M S1 APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 534.81 | 16-JAN-18:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 414.30 | 05-FEB-01:00 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 428.19 | 14-MAR-07:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.27 | 29-APR-16:00 | 421.44 | 15-APR-12:00 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 84.05 | 19-MAY-15:00 | 307.69 | 05-MAY-09:00 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 158.00 | 17-JUN-16:00 | 177.89 | 10-JUN-01:40 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 168.57 | 04-JUL-15:00 | 71.01 | 15-JUL-19:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 102.37 | 04-AUG-18:00 | 88.52 | 25-AUG-20:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 66.47 | 03-SEP-15:00 | 119.23 | 18-SEP-01:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 68.76 | 11-OCT-13:00 | 384.01 | 24-OCT-17:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 406.77 | 26-NOV-06:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 564.47 | 14-DEC-04:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.01 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 168.57 | 564.47 |
Report: PeakSpaceGainsMonthly
For: M S2 APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 534.83 | 16-JAN-18:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 414.30 | 05-FEB-01:00 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 428.37 | 14-MAR-07:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.27 | 29-APR-16:00 | 421.62 | 15-APR-12:00 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 84.05 | 19-MAY-15:00 | 309.19 | 05-MAY-09:00 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 158.00 | 17-JUN-16:00 | 177.88 | 10-JUN-01:40 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 168.57 | 04-JUL-15:00 | 71.01 | 15-JUL-19:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 102.37 | 04-AUG-18:00 | 88.52 | 25-AUG-20:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 66.47 | 03-SEP-15:00 | 119.23 | 18-SEP-01:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 68.76 | 11-OCT-13:00 | 384.05 | 24-OCT-17:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 406.79 | 26-NOV-06:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 564.48 | 14-DEC-04:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.01 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 168.57 | 564.48 |
Report: PeakSpaceGainsMonthly
For: T SW APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 1140.21 | 16-JAN-18:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 891.75 | 05-FEB-01:00 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 846.27 | 14-MAR-07:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 58.31 | 29-APR-16:00 | 842.96 | 15-APR-12:00 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 183.10 | 19-MAY-15:00 | 588.57 | 05-MAY-08:00 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 345.11 | 17-JUN-16:00 | 344.43 | 01-JUN-18:00 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 368.41 | 04-JUL-15:00 | 156.93 | 15-JUL-19:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 223.15 | 04-AUG-18:00 | 195.26 | 25-AUG-20:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 144.90 | 03-SEP-15:00 | 259.42 | 07-SEP-22:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 148.56 | 11-OCT-13:00 | 746.28 | 24-OCT-17:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 854.35 | 26-NOV-06:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1213.81 | 14-DEC-04:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 156.93 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 368.41 | 1213.81 |
Report: PeakSpaceGainsMonthly
For: T NW APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 1140.21 | 16-JAN-18:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 891.75 | 05-FEB-01:00 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 846.27 | 14-MAR-07:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 58.31 | 29-APR-16:00 | 822.67 | 15-APR-12:00 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 183.10 | 19-MAY-15:00 | 588.57 | 05-MAY-08:00 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 345.11 | 17-JUN-16:00 | 344.43 | 01-JUN-18:00 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 368.41 | 04-JUL-15:00 | 156.93 | 15-JUL-19:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 223.15 | 04-AUG-18:00 | 195.26 | 25-AUG-20:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 144.90 | 03-SEP-15:00 | 259.42 | 07-SEP-22:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 148.56 | 11-OCT-13:00 | 746.28 | 24-OCT-17:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 854.35 | 26-NOV-06:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1213.81 | 14-DEC-04:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 156.93 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 368.41 | 1213.81 |
Report: PeakSpaceGainsMonthly
For: T SE APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 1140.21 | 16-JAN-18:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 891.75 | 05-FEB-01:00 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 846.27 | 14-MAR-07:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 58.31 | 29-APR-16:00 | 875.65 | 15-APR-12:00 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 183.10 | 19-MAY-15:00 | 610.75 | 05-MAY-09:00 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 345.11 | 17-JUN-16:00 | 344.43 | 01-JUN-18:00 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 368.41 | 04-JUL-15:00 | 156.93 | 15-JUL-19:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 223.15 | 04-AUG-18:00 | 195.26 | 25-AUG-20:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 144.90 | 03-SEP-15:00 | 259.42 | 07-SEP-22:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 148.56 | 11-OCT-13:00 | 746.28 | 24-OCT-17:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 854.35 | 26-NOV-06:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1213.81 | 14-DEC-04:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 156.93 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 368.41 | 1213.81 |
Report: PeakSpaceGainsMonthly
For: T NE APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 1140.21 | 16-JAN-18:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 891.75 | 05-FEB-01:00 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 846.27 | 14-MAR-07:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 58.31 | 29-APR-16:00 | 859.77 | 15-APR-12:00 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 183.10 | 19-MAY-15:00 | 610.09 | 05-MAY-09:00 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 345.11 | 17-JUN-16:00 | 344.43 | 01-JUN-18:00 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 368.41 | 04-JUL-15:00 | 156.93 | 15-JUL-19:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 223.15 | 04-AUG-18:00 | 195.26 | 25-AUG-20:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 144.90 | 03-SEP-15:00 | 259.42 | 07-SEP-22:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 148.56 | 11-OCT-13:00 | 746.28 | 24-OCT-17:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 854.35 | 26-NOV-06:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1213.81 | 14-DEC-04:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 156.93 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 368.41 | 1213.81 |
Report: PeakSpaceGainsMonthly
For: T N1 APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 687.74 | 16-JAN-18:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 537.88 | 05-FEB-01:00 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 510.45 | 14-MAR-07:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 35.17 | 29-APR-16:00 | 526.05 | 15-APR-12:00 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 110.44 | 19-MAY-15:00 | 355.01 | 05-MAY-08:00 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 208.16 | 17-JUN-16:00 | 214.70 | 10-JUN-01:00 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 222.21 | 04-JUL-15:00 | 94.66 | 15-JUL-19:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 134.60 | 04-AUG-18:00 | 117.77 | 25-AUG-20:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 87.40 | 03-SEP-15:00 | 156.48 | 07-SEP-22:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 89.61 | 11-OCT-13:00 | 450.14 | 24-OCT-17:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 515.32 | 26-NOV-06:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 732.14 | 14-DEC-04:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94.66 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 222.21 | 732.14 |
Report: PeakSpaceGainsMonthly
For: T N2 APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 687.74 | 16-JAN-18:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 537.88 | 05-FEB-01:00 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 510.45 | 14-MAR-07:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 35.17 | 29-APR-16:00 | 528.20 | 15-APR-12:00 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 110.44 | 19-MAY-15:00 | 355.01 | 05-MAY-08:00 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 208.16 | 17-JUN-16:00 | 214.55 | 10-JUN-01:00 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 222.21 | 04-JUL-15:00 | 94.66 | 15-JUL-19:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 134.60 | 04-AUG-18:00 | 117.77 | 25-AUG-20:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 87.40 | 03-SEP-15:00 | 156.48 | 07-SEP-22:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 89.61 | 11-OCT-13:00 | 450.14 | 24-OCT-17:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 515.32 | 26-NOV-06:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 732.14 | 14-DEC-04:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94.66 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 222.21 | 732.14 |
Report: PeakSpaceGainsMonthly
For: T S1 APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 687.74 | 16-JAN-18:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 537.88 | 05-FEB-01:00 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 510.45 | 14-MAR-07:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 35.17 | 29-APR-16:00 | 537.52 | 15-APR-12:00 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 110.44 | 19-MAY-15:00 | 355.01 | 05-MAY-08:00 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 208.16 | 17-JUN-16:00 | 213.36 | 10-JUN-01:00 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 222.21 | 04-JUL-15:00 | 94.66 | 15-JUL-19:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 134.60 | 04-AUG-18:00 | 117.77 | 25-AUG-20:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 87.40 | 03-SEP-15:00 | 158.61 | 18-SEP-01:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 89.61 | 11-OCT-13:00 | 450.18 | 24-OCT-17:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 515.32 | 26-NOV-06:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 732.14 | 14-DEC-04:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94.66 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 222.21 | 732.14 |
Report: PeakSpaceGainsMonthly
For: T S2 APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 687.74 | 16-JAN-18:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 537.88 | 05-FEB-01:00 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 510.45 | 14-MAR-07:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 35.17 | 29-APR-16:00 | 539.20 | 15-APR-12:00 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 110.44 | 19-MAY-15:00 | 355.01 | 05-MAY-08:00 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 208.16 | 17-JUN-16:00 | 213.11 | 10-JUN-01:00 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 222.21 | 04-JUL-15:00 | 94.66 | 15-JUL-19:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 134.60 | 04-AUG-18:00 | 117.77 | 25-AUG-20:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 87.40 | 03-SEP-15:00 | 158.57 | 18-SEP-01:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 89.61 | 11-OCT-13:00 | 450.28 | 24-OCT-17:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 515.32 | 26-NOV-06:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 732.14 | 14-DEC-04:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94.66 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 222.21 | 732.14 |
Report: PeakSpaceGainsMonthly
For: T CORRIDOR
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 397.10 | 01-JAN-00:10 | 370.63 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 192.60 | 16-JAN-18:00 |
| February | 397.10 | 01-FEB-00:10 | 370.63 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 150.43 | 05-FEB-01:00 |
| March | 397.10 | 01-MAR-00:10 | 370.63 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 150.78 | 14-MAR-07:00 |
| April | 397.10 | 01-APR-00:10 | 370.63 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 167.22 | 15-APR-12:00 |
| May | 397.10 | 01-MAY-00:10 | 370.63 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.61 | 22-MAY-13:00 | 106.47 | 05-MAY-08:40 |
| June | 397.10 | 01-JUN-00:10 | 370.63 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.52 | 17-JUN-16:00 | 69.83 | 10-JUN-01:00 |
| July | 397.10 | 01-JUL-00:10 | 370.63 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.06 | 04-JUL-15:00 | 41.52 | 15-JUL-19:00 |
| August | 397.10 | 01-AUG-00:10 | 370.63 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.80 | 02-AUG-13:00 | 46.39 | 25-AUG-20:00 |
| September | 397.10 | 01-SEP-00:10 | 370.63 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.63 | 03-SEP-14:40 | 54.16 | 07-SEP-22:00 |
| October | 397.10 | 01-OCT-00:10 | 370.63 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.58 | 11-OCT-13:00 | 136.48 | 24-OCT-17:00 |
| November | 397.10 | 01-NOV-00:10 | 370.63 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 143.39 | 03-NOV-21:00 |
| December | 397.10 | 01-DEC-00:10 | 370.63 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 202.71 | 14-DEC-04:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
| Minimum of Months | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.52 | ||||
| Maximum of Months | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.06 | 202.71 |
Report: PeakSpaceGainsMonthly
For: G CORRIDOR
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 397.10 | 01-JAN-00:10 | 370.63 | 01-JAN-00:10 | 208.40 | 01-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 13545.93 | 21-JAN-07:01 |
| February | 397.10 | 01-FEB-00:10 | 370.63 | 01-FEB-00:10 | 208.40 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 13164.59 | 05-FEB-07:01 |
| March | 397.10 | 01-MAR-00:10 | 370.63 | 01-MAR-00:10 | 208.40 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 11666.88 | 05-MAR-07:01 |
| April | 397.10 | 01-APR-00:10 | 370.63 | 01-APR-00:10 | 208.40 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 304.71 | 01-APR-16:10 | 9696.85 | 06-APR-06:01 |
| May | 397.10 | 01-MAY-00:10 | 370.63 | 01-MAY-00:10 | 208.40 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1421.00 | 19-MAY-16:02 | 8339.64 | 04-MAY-06:01 |
| June | 397.10 | 01-JUN-00:10 | 370.63 | 01-JUN-00:10 | 208.40 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4646.11 | 28-JUN-16:01 | 7265.07 | 09-JUN-06:01 |
| July | 397.10 | 01-JUL-00:10 | 370.63 | 01-JUL-00:10 | 208.40 | 01-JUL-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4008.46 | 21-JUL-16:01 | 3603.48 | 08-JUL-06:01 |
| August | 397.10 | 01-AUG-00:10 | 370.63 | 01-AUG-00:10 | 208.40 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3097.41 | 01-AUG-16:01 | 5553.71 | 31-AUG-06:01 |
| September | 397.10 | 01-SEP-00:10 | 370.63 | 01-SEP-00:10 | 208.40 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1499.46 | 02-SEP-16:03 | 6624.41 | 20-SEP-06:01 |
| October | 397.10 | 01-OCT-00:10 | 370.63 | 01-OCT-00:10 | 208.40 | 01-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 399.46 | 01-OCT-16:10 | 11522.28 | 25-OCT-06:01 |
| November | 397.10 | 01-NOV-00:10 | 370.63 | 01-NOV-00:10 | 208.40 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 12729.57 | 27-NOV-07:01 |
| December | 397.10 | 01-DEC-00:10 | 370.63 | 01-DEC-00:10 | 208.40 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 14190.99 | 15-DEC-07:01 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 397.10 | 370.63 | 208.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3603.48 | |||||
| Maximum of Months | 397.10 | 370.63 | 208.40 | 0.00 | 0.00 | 0.00 | 0.00 | 4646.11 | 14190.99 |
Report: PeakSpaceGainsMonthly
For: M CORRIDOR
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 397.10 | 01-JAN-00:10 | 370.63 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 158.66 | 16-JAN-18:00 |
| February | 397.10 | 01-FEB-00:10 | 370.63 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 123.97 | 05-FEB-01:00 |
| March | 397.10 | 01-MAR-00:10 | 370.63 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 130.45 | 14-MAR-07:00 |
| April | 397.10 | 01-APR-00:10 | 370.63 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 133.12 | 15-APR-12:00 |
| May | 397.10 | 01-MAY-00:10 | 370.63 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.15 | 19-MAY-15:00 | 98.98 | 05-MAY-09:00 |
| June | 397.10 | 01-JUN-00:10 | 370.63 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.17 | 17-JUN-16:00 | 58.31 | 10-JUN-01:00 |
| July | 397.10 | 01-JUL-00:10 | 370.63 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.00 | 04-JUL-15:00 | 29.57 | 15-JUL-19:00 |
| August | 397.10 | 01-AUG-00:10 | 370.63 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.11 | 02-AUG-13:00 | 33.72 | 25-AUG-20:00 |
| September | 397.10 | 01-SEP-00:10 | 370.63 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.99 | 03-SEP-14:50 | 42.70 | 07-SEP-22:00 |
| October | 397.10 | 01-OCT-00:10 | 370.63 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.56 | 01-OCT-16:00 | 116.96 | 24-OCT-17:00 |
| November | 397.10 | 01-NOV-00:10 | 370.63 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 122.70 | 03-NOV-24:00 |
| December | 397.10 | 01-DEC-00:10 | 370.63 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 169.60 | 14-DEC-04:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
| Minimum of Months | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.57 | ||||
| Maximum of Months | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.00 | 169.60 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: G SW APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 819.73 | 02-JAN-15:30 | 0.00 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.03 |
| February | 881.37 | 14-FEB-16:10 | 0.00 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.47 |
| March | 718.04 | 12-MAR-16:30 | 237.50 | 86.80 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.04 |
| April | 1272.87 | 13-APR-16:30 | 0.00 | 260.40 | 1765.87 | 0.00 | 0.00 | 0.00 | 0.00 | 17.00 | 0.00 |
| May | 1630.60 | 20-MAY-17:20 | 237.50 | 117.18 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 17.10 | 0.00 |
| June | 2099.86 | 28-JUN-16:30 | 0.00 | 86.80 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 75.62 | 0.00 |
| July | 2314.86 | 21-JUL-17:20 | 1187.50 | 585.91 | 2943.11 | 0.00 | 0.00 | 0.00 | 0.00 | 69.84 | 0.00 |
| August | 2414.66 | 20-AUG-17:05 | 950.00 | 468.73 | 2354.49 | 0.00 | 0.00 | 0.00 | 0.00 | 94.39 | 0.00 |
| September | 2468.03 | 21-SEP-16:01 | 0.00 | 607.59 | 4120.36 | 0.00 | 0.00 | 0.00 | 0.00 | 28.05 | 0.00 |
| October | 2312.06 | 06-OCT-16:05 | 0.00 | 520.80 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 31.70 | 0.00 |
| November | 1541.85 | 01-NOV-15:10 | 0.00 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 263.71 |
| December | 825.65 | 31-DEC-15:30 | 0.00 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 718.04 | 0.00 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 2468.03 | 1187.50 | 607.59 | 4120.36 | 0.00 | 0.00 | 0.00 | 0.00 | 94.39 | 263.71 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: G NW APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 307.91 | 02-JAN-17:35 | 247.00 | 173.60 | 1177.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.72 |
| February | 304.45 | 15-FEB-19:00 | 206.62 | 117.18 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.33 |
| March | 351.34 | 29-MAR-19:20 | 206.62 | 138.88 | 523.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.77 |
| April | 899.46 | 29-APR-17:30 | 206.62 | 117.18 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 7.13 | 0.00 |
| May | 1503.85 | 19-MAY-17:20 | 413.25 | 234.36 | 1177.25 | 0.00 | 0.00 | 0.00 | 0.00 | 86.48 | 0.00 |
| June | 2139.76 | 26-JUN-17:12 | 826.50 | 468.73 | 2354.49 | 0.00 | 0.00 | 0.00 | 0.00 | 135.31 | 0.00 |
| July | 2261.72 | 04-JUL-17:30 | 206.62 | 117.18 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 146.21 | 0.00 |
| August | 2107.96 | 20-AUG-17:30 | 206.62 | 117.18 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 78.85 | 0.00 |
| September | 1800.48 | 02-SEP-17:10 | 619.87 | 351.55 | 1765.87 | 0.00 | 0.00 | 0.00 | 0.00 | 37.12 | 0.00 |
| October | 1506.89 | 06-OCT-16:30 | 123.50 | 86.80 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 26.43 | 0.00 |
| November | 513.37 | 04-NOV-07:00 | 201.88 | 56.42 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82.88 |
| December | 380.54 | 02-DEC-18:50 | 206.62 | 117.18 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99.63 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 304.45 | 123.50 | 56.42 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 2261.72 | 826.50 | 468.73 | 2354.49 | 0.00 | 0.00 | 0.00 | 0.00 | 146.21 | 99.63 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: OFFICE
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 1087.52 | 03-JAN-14:00 | 451.21 | 582.92 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.87 |
| February | 1210.43 | 15-FEB-15:20 | 451.21 | 582.92 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.07 |
| March | 1183.24 | 13-MAR-14:30 | 451.21 | 582.92 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.95 |
| April | 5696.88 | 28-APR-08:62 | 1804.82 | 2331.66 | 2354.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 6758.74 | 22-MAY-07:02 | 2256.03 | 2914.58 | 2943.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.69 |
| June | 6878.93 | 30-JUN-07:02 | 2707.23 | 3497.50 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.59 |
| July | 6904.08 | 03-JUL-07:02 | 2707.23 | 3497.50 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.87 |
| August | 6902.36 | 16-AUG-07:02 | 2707.23 | 3497.50 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.10 |
| September | 7148.83 | 18-SEP-07:01 | 3158.44 | 4080.41 | 4120.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.12 |
| October | 7151.75 | 10-OCT-07:01 | 3158.44 | 4080.41 | 4120.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.41 |
| November | 5940.37 | 01-NOV-08:62 | 1804.82 | 2331.66 | 2354.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 106.03 |
| December | 810.62 | 29-DEC-15:30 | 451.21 | 582.92 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.45 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 810.62 | 451.21 | 582.92 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 7151.75 | 3158.44 | 4080.41 | 4120.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 106.03 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: G NE APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 262.28 | 03-JAN-17:25 | 247.00 | 173.60 | 1177.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.96 |
| February | 291.35 | 15-FEB-19:00 | 206.62 | 117.18 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.41 |
| March | 336.43 | 17-MAR-17:35 | 413.25 | 234.36 | 1177.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 185.03 |
| April | 854.78 | 29-APR-16:10 | 123.50 | 86.80 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 29.18 | 0.00 |
| May | 1205.62 | 19-MAY-17:30 | 206.62 | 117.18 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 84.13 | 0.00 |
| June | 1800.43 | 29-JUN-15:10 | 71.25 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 149.76 | 0.00 |
| July | 1846.40 | 04-JUL-17:10 | 1033.12 | 585.91 | 2943.11 | 0.00 | 0.00 | 0.00 | 0.00 | 169.64 | 0.00 |
| August | 1737.82 | 20-AUG-17:10 | 826.50 | 468.73 | 2354.49 | 0.00 | 0.00 | 0.00 | 0.00 | 94.39 | 0.00 |
| September | 1529.03 | 03-SEP-15:10 | 71.25 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 71.59 | 0.00 |
| October | 1279.93 | 01-OCT-16:10 | 123.50 | 86.80 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 35.94 | 0.00 |
| November | 494.92 | 04-NOV-06:35 | 403.75 | 112.83 | 765.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86.14 |
| December | 326.02 | 02-DEC-11:30 | 59.38 | 17.36 | 412.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 262.28 | 59.38 | 17.36 | 412.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 1846.40 | 1033.12 | 585.91 | 2943.11 | 0.00 | 0.00 | 0.00 | 0.00 | 169.64 | 185.03 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: G N1 APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 331.66 | 03-JAN-18:12 | 1033.12 | 585.91 | 2943.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.75 |
| February | 325.80 | 15-FEB-21:00 | 206.62 | 138.88 | 523.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 155.14 |
| March | 382.55 | 17-MAR-19:10 | 206.62 | 138.88 | 523.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96.81 |
| April | 608.20 | 29-APR-16:30 | 123.50 | 86.80 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 14.54 | 0.00 |
| May | 975.26 | 19-MAY-18:00 | 206.62 | 117.18 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 46.59 | 0.00 |
| June | 1394.68 | 28-JUN-17:50 | 206.62 | 117.18 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 74.16 | 0.00 |
| July | 1429.83 | 04-JUL-17:40 | 206.62 | 117.18 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 81.49 | 0.00 |
| August | 1333.66 | 20-AUG-17:17 | 619.87 | 351.55 | 1765.87 | 0.00 | 0.00 | 0.00 | 0.00 | 52.25 | 0.00 |
| September | 1143.73 | 03-SEP-16:40 | 123.50 | 86.80 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 36.42 | 0.00 |
| October | 1010.26 | 01-OCT-16:10 | 123.50 | 86.80 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 21.68 | 0.00 |
| November | 525.76 | 04-NOV-07:00 | 201.88 | 56.42 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.14 |
| December | 407.30 | 02-DEC-19:20 | 206.62 | 138.88 | 547.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.54 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 325.80 | 123.50 | 56.42 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 1429.83 | 1033.12 | 585.91 | 2943.11 | 0.00 | 0.00 | 0.00 | 0.00 | 81.49 | 155.14 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: G N2 APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 324.16 | 02-JAN-17:45 | 247.00 | 173.60 | 1177.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.44 |
| February | 325.31 | 15-FEB-21:00 | 206.62 | 138.88 | 523.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 154.92 |
| March | 383.11 | 17-MAR-19:10 | 206.62 | 138.88 | 523.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96.94 |
| April | 622.02 | 29-APR-16:10 | 123.50 | 86.80 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 17.60 | 0.00 |
| May | 972.34 | 19-MAY-18:00 | 206.62 | 117.18 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 46.59 | 0.00 |
| June | 1390.38 | 28-JUN-17:50 | 206.62 | 117.18 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 74.16 | 0.00 |
| July | 1423.25 | 04-JUL-17:40 | 206.62 | 117.18 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 81.49 | 0.00 |
| August | 1330.15 | 20-AUG-17:17 | 619.87 | 351.55 | 1765.87 | 0.00 | 0.00 | 0.00 | 0.00 | 52.25 | 0.00 |
| September | 1146.82 | 03-SEP-16:30 | 123.50 | 86.80 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 34.33 | 0.00 |
| October | 1009.27 | 01-OCT-16:20 | 123.50 | 86.80 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 21.39 | 0.00 |
| November | 525.47 | 04-NOV-07:00 | 201.88 | 56.42 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.12 |
| December | 403.09 | 02-DEC-19:10 | 206.62 | 138.88 | 547.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.26 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 324.16 | 123.50 | 56.42 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 1423.25 | 619.87 | 351.55 | 1765.87 | 0.00 | 0.00 | 0.00 | 0.00 | 81.49 | 154.92 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: G S1 APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 1001.74 | 02-JAN-14:30 | 118.75 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.52 |
| February | 793.16 | 14-FEB-15:10 | 0.00 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.98 |
| March | 644.11 | 13-MAR-14:30 | 0.00 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.04 |
| April | 967.78 | 29-APR-16:10 | 237.50 | 86.80 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 17.60 | 0.00 |
| May | 1064.23 | 19-MAY-17:20 | 475.00 | 234.36 | 1177.25 | 0.00 | 0.00 | 0.00 | 0.00 | 52.16 | 0.00 |
| June | 1367.23 | 29-JUN-15:10 | 0.00 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 90.33 | 0.00 |
| July | 1541.70 | 22-JUL-16:05 | 1425.00 | 520.80 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 68.69 | 0.00 |
| August | 1655.29 | 20-AUG-16:07 | 1425.00 | 520.80 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 39.97 | 0.00 |
| September | 1836.64 | 21-SEP-15:10 | 0.00 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 13.78 | 0.00 |
| October | 1757.84 | 01-OCT-15:10 | 237.50 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 9.02 | 0.00 |
| November | 1471.63 | 01-NOV-13:00 | 0.00 | 17.36 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 123.14 |
| December | 908.09 | 31-DEC-15:10 | 0.00 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 644.11 | 0.00 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 1836.64 | 1425.00 | 520.80 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 90.33 | 123.14 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: G S2 APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 1013.80 | 02-JAN-14:30 | 118.75 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.52 |
| February | 813.64 | 14-FEB-15:10 | 0.00 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.98 |
| March | 688.40 | 13-MAR-14:30 | 0.00 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.04 |
| April | 1060.37 | 29-APR-16:10 | 237.50 | 86.80 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 17.60 | 0.00 |
| May | 1154.68 | 14-MAY-16:30 | 237.50 | 86.80 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 40.72 | 0.00 |
| June | 1450.86 | 29-JUN-15:10 | 0.00 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 90.33 | 0.00 |
| July | 1678.67 | 22-JUL-16:05 | 1425.00 | 520.80 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 68.69 | 0.00 |
| August | 1815.54 | 20-AUG-16:07 | 1425.00 | 520.80 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 39.97 | 0.00 |
| September | 1956.15 | 03-SEP-13:30 | 118.75 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 29.90 | 0.00 |
| October | 1912.78 | 01-OCT-14:10 | 0.00 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 6.84 | 0.00 |
| November | 1529.66 | 01-NOV-13:00 | 0.00 | 17.36 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 123.14 |
| December | 928.30 | 31-DEC-15:10 | 0.00 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 688.40 | 0.00 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 1956.15 | 1425.00 | 520.80 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 90.33 | 123.14 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: M SW APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 1715.95 | 02-JAN-15:20 | 0.00 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.04 |
| February | 2098.75 | 14-FEB-15:30 | 0.00 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.06 |
| March | 1984.79 | 12-MAR-16:03 | 712.50 | 260.40 | 1765.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.87 |
| April | 2328.34 | 13-APR-16:27 | 0.00 | 260.40 | 1765.87 | 0.00 | 0.00 | 0.00 | 0.00 | 24.17 | 0.00 |
| May | 2419.05 | 19-MAY-16:25 | 0.00 | 173.60 | 1177.25 | 0.00 | 0.00 | 0.00 | 0.00 | 126.81 | 0.00 |
| June | 2740.76 | 26-JUN-17:05 | 950.00 | 468.73 | 2354.49 | 0.00 | 0.00 | 0.00 | 0.00 | 217.41 | 0.00 |
| July | 2872.48 | 04-JUL-17:00 | 237.50 | 86.80 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 261.08 | 0.00 |
| August | 2885.04 | 20-AUG-17:00 | 237.50 | 86.80 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 146.52 | 0.00 |
| September | 2955.15 | 20-SEP-16:17 | 0.00 | 260.40 | 1765.87 | 0.00 | 0.00 | 0.00 | 0.00 | 42.24 | 0.00 |
| October | 2720.11 | 05-OCT-16:03 | 0.00 | 520.80 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 17.61 | 0.00 |
| November | 2078.17 | 20-NOV-15:30 | 0.00 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.42 |
| December | 1767.27 | 31-DEC-15:30 | 0.00 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 1715.95 | 0.00 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 2955.15 | 950.00 | 520.80 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 261.08 | 62.04 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: M NW APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 478.01 | 03-JAN-21:30 | 237.50 | 95.48 | 500.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.94 |
| February | 509.48 | 14-FEB-02:20 | 237.50 | 8.68 | 229.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 105.60 |
| March | 559.94 | 30-MAR-02:00 | 237.50 | 8.68 | 229.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 192.88 |
| April | 1915.64 | 13-APR-16:27 | 370.50 | 260.40 | 1765.87 | 0.00 | 0.00 | 0.00 | 0.00 | 24.17 | 0.00 |
| May | 2271.25 | 19-MAY-16:50 | 123.50 | 86.80 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 129.43 | 0.00 |
| June | 2801.16 | 26-JUN-17:17 | 826.50 | 468.73 | 2354.49 | 0.00 | 0.00 | 0.00 | 0.00 | 194.06 | 0.00 |
| July | 2835.63 | 04-JUL-17:30 | 206.62 | 117.18 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 209.73 | 0.00 |
| August | 2535.56 | 20-AUG-17:30 | 206.62 | 117.18 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 113.10 | 0.00 |
| September | 2160.90 | 02-SEP-16:40 | 123.50 | 86.80 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 57.53 | 0.00 |
| October | 1803.62 | 06-OCT-16:30 | 123.50 | 86.80 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 37.75 | 0.00 |
| November | 514.40 | 04-NOV-07:00 | 201.88 | 56.42 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 119.46 |
| December | 434.13 | 02-DEC-20:30 | 206.62 | 138.88 | 523.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 183.40 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 434.13 | 123.50 | 8.68 | 229.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 2835.63 | 826.50 | 468.73 | 2354.49 | 0.00 | 0.00 | 0.00 | 0.00 | 209.73 | 192.88 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: M SE APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 1531.24 | 02-JAN-14:00 | 118.75 | 17.36 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 1784.77 | 14-FEB-14:40 | 0.00 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.34 |
| March | 1731.11 | 08-MAR-14:00 | 0.00 | 17.36 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.18 |
| April | 1970.09 | 28-APR-13:00 | 0.00 | 17.36 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 5.54 | 0.00 |
| May | 1928.71 | 19-MAY-12:30 | 0.00 | 17.36 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 90.22 | 0.00 |
| June | 2287.50 | 29-JUN-15:10 | 0.00 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 214.90 | 0.00 |
| July | 2419.23 | 22-JUL-14:00 | 118.75 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 208.85 | 0.00 |
| August | 2376.60 | 17-AUG-13:30 | 0.00 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 120.80 | 0.00 |
| September | 2612.68 | 03-SEP-13:30 | 118.75 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 71.05 | 0.00 |
| October | 2418.33 | 01-OCT-13:30 | 118.75 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 14.17 | 0.00 |
| November | 1901.88 | 01-NOV-12:50 | 0.00 | 17.36 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 296.31 |
| December | 1489.68 | 31-DEC-14:20 | 118.75 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 1489.68 | 0.00 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 2612.68 | 118.75 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 214.90 | 296.31 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: M NE APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 445.25 | 03-JAN-21:10 | 237.50 | 95.48 | 500.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.33 |
| February | 500.73 | 14-FEB-07:20 | 807.50 | 225.67 | 1530.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.78 |
| March | 557.48 | 12-MAR-07:00 | 201.88 | 56.42 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 130.78 |
| April | 1467.29 | 29-APR-16:10 | 123.50 | 86.80 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 41.38 | 0.00 |
| May | 1717.65 | 19-MAY-17:20 | 413.25 | 234.36 | 1177.25 | 0.00 | 0.00 | 0.00 | 0.00 | 123.86 | 0.00 |
| June | 2196.90 | 29-JUN-15:10 | 71.25 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 214.90 | 0.00 |
| July | 2148.98 | 04-JUL-17:04 | 1033.12 | 585.91 | 2943.11 | 0.00 | 0.00 | 0.00 | 0.00 | 243.37 | 0.00 |
| August | 1941.12 | 02-AUG-17:10 | 826.50 | 468.73 | 2354.49 | 0.00 | 0.00 | 0.00 | 0.00 | 149.12 | 0.00 |
| September | 1675.07 | 03-SEP-14:30 | 59.38 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 98.52 | 0.00 |
| October | 1369.94 | 01-OCT-16:10 | 123.50 | 86.80 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 51.41 | 0.00 |
| November | 485.12 | 04-NOV-06:25 | 403.75 | 112.83 | 765.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 125.89 |
| December | 398.69 | 02-DEC-19:00 | 206.62 | 117.18 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 157.40 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 398.69 | 59.38 | 30.38 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 2196.90 | 1033.12 | 585.91 | 2943.11 | 0.00 | 0.00 | 0.00 | 0.00 | 243.37 | 157.40 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: M N1 APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 530.27 | 03-JAN-22:00 | 237.50 | 95.48 | 500.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.13 |
| February | 558.68 | 14-FEB-03:00 | 237.50 | 8.68 | 229.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97.61 |
| March | 596.18 | 30-MAR-06:00 | 237.50 | 60.76 | 317.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 144.27 |
| April | 1080.77 | 29-APR-16:20 | 123.50 | 86.80 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 22.73 | 0.00 |
| May | 1343.29 | 31-MAY-18:00 | 206.62 | 117.18 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 50.00 | 0.00 |
| June | 1629.48 | 16-JUN-18:00 | 206.62 | 117.18 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 81.61 | 0.00 |
| July | 1633.71 | 04-JUL-18:00 | 206.62 | 117.18 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 98.75 | 0.00 |
| August | 1462.25 | 01-AUG-17:10 | 826.50 | 468.73 | 2354.49 | 0.00 | 0.00 | 0.00 | 0.00 | 83.74 | 0.00 |
| September | 1220.19 | 03-SEP-16:50 | 123.50 | 86.80 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 54.76 | 0.00 |
| October | 1067.11 | 01-OCT-16:10 | 123.50 | 86.80 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 31.01 | 0.00 |
| November | 534.33 | 04-NOV-07:00 | 201.88 | 56.42 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74.72 |
| December | 483.98 | 30-DEC-21:20 | 237.50 | 95.48 | 500.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.23 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 483.98 | 123.50 | 8.68 | 229.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 1633.71 | 826.50 | 468.73 | 2354.49 | 0.00 | 0.00 | 0.00 | 0.00 | 98.75 | 144.27 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: M N2 APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 530.13 | 03-JAN-22:00 | 237.50 | 95.48 | 500.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.11 |
| February | 558.45 | 14-FEB-03:00 | 237.50 | 8.68 | 229.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97.57 |
| March | 596.13 | 30-MAR-06:00 | 237.50 | 60.76 | 317.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 144.26 |
| April | 1087.03 | 29-APR-16:20 | 123.50 | 86.80 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 22.73 | 0.00 |
| May | 1335.74 | 19-MAY-18:00 | 206.62 | 117.18 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 66.70 | 0.00 |
| June | 1623.05 | 16-JUN-18:00 | 206.62 | 117.18 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 81.61 | 0.00 |
| July | 1622.75 | 04-JUL-18:00 | 206.62 | 117.18 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 98.75 | 0.00 |
| August | 1454.86 | 07-AUG-18:00 | 206.62 | 117.18 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 65.06 | 0.00 |
| September | 1223.83 | 03-SEP-16:40 | 123.50 | 86.80 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 52.03 | 0.00 |
| October | 1064.49 | 01-OCT-16:20 | 123.50 | 86.80 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 30.58 | 0.00 |
| November | 533.77 | 04-NOV-07:00 | 201.88 | 56.42 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74.65 |
| December | 478.15 | 30-DEC-21:10 | 237.50 | 95.48 | 500.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.02 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 478.15 | 123.50 | 8.68 | 229.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 1623.05 | 237.50 | 117.18 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 98.75 | 144.26 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: M S1 APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 1738.94 | 02-JAN-14:00 | 118.75 | 17.36 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 1751.90 | 14-FEB-14:40 | 0.00 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.87 |
| March | 1565.91 | 08-MAR-14:00 | 0.00 | 17.36 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.74 |
| April | 1480.28 | 26-APR-14:10 | 0.00 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 23.10 | 0.00 |
| May | 1453.89 | 14-MAY-16:30 | 237.50 | 86.80 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 58.24 | 0.00 |
| June | 1613.20 | 29-JUN-15:10 | 0.00 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 129.62 | 0.00 |
| July | 1740.32 | 22-JUL-14:00 | 118.75 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 125.97 | 0.00 |
| August | 1820.33 | 20-AUG-16:03 | 1425.00 | 520.80 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 57.33 | 0.00 |
| September | 2129.67 | 21-SEP-14:10 | 0.00 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 24.62 | 0.00 |
| October | 2068.29 | 18-OCT-14:30 | 0.00 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.24 |
| November | 1933.59 | 20-NOV-14:00 | 0.00 | 17.36 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.31 |
| December | 1746.06 | 31-DEC-14:30 | 118.75 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 1453.89 | 0.00 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 2129.67 | 1425.00 | 520.80 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 129.62 | 23.31 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: M S2 APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 1745.48 | 02-JAN-14:00 | 118.75 | 17.36 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 1756.96 | 14-FEB-14:40 | 0.00 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.87 |
| March | 1575.24 | 08-MAR-14:00 | 0.00 | 17.36 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.74 |
| April | 1489.18 | 28-APR-13:30 | 0.00 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 3.34 | 0.00 |
| May | 1449.67 | 14-MAY-16:10 | 475.00 | 173.60 | 1177.25 | 0.00 | 0.00 | 0.00 | 0.00 | 54.92 | 0.00 |
| June | 1614.92 | 29-JUN-15:10 | 0.00 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 129.62 | 0.00 |
| July | 1746.02 | 22-JUL-14:00 | 118.75 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 125.97 | 0.00 |
| August | 1816.38 | 20-AUG-16:03 | 1425.00 | 520.80 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 57.33 | 0.00 |
| September | 2132.68 | 21-SEP-14:10 | 0.00 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 24.62 | 0.00 |
| October | 2069.25 | 18-OCT-14:20 | 0.00 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.03 |
| November | 1937.47 | 20-NOV-14:00 | 0.00 | 17.36 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.31 |
| December | 1752.16 | 31-DEC-14:30 | 118.75 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 1449.67 | 0.00 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 2132.68 | 1425.00 | 520.80 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 129.62 | 23.31 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: T SW APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 2261.53 | 23-JAN-15:30 | 0.00 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.59 |
| February | 2756.61 | 14-FEB-15:30 | 0.00 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.69 |
| March | 2588.70 | 12-MAR-16:03 | 712.50 | 260.40 | 1765.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.20 |
| April | 3092.35 | 13-APR-16:03 | 0.00 | 347.20 | 2354.49 | 0.00 | 0.00 | 0.00 | 0.00 | 28.45 | 0.00 |
| May | 3368.11 | 19-MAY-16:30 | 0.00 | 173.60 | 1177.25 | 0.00 | 0.00 | 0.00 | 0.00 | 166.63 | 0.00 |
| June | 3960.22 | 28-JUN-16:30 | 0.00 | 86.80 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 143.16 | 0.00 |
| July | 4030.82 | 22-JUL-15:30 | 237.50 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 225.83 | 0.00 |
| August | 4121.27 | 20-AUG-16:08 | 1425.00 | 520.80 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 125.27 | 0.00 |
| September | 3916.55 | 21-SEP-15:20 | 0.00 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 44.62 | 0.00 |
| October | 3635.13 | 05-OCT-15:20 | 0.00 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 7.65 | 0.00 |
| November | 2420.43 | 20-NOV-15:20 | 0.00 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.88 |
| December | 2364.65 | 31-DEC-15:30 | 0.00 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 2261.53 | 0.00 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 4121.27 | 1425.00 | 520.80 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 225.83 | 76.59 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: T NW APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 428.88 | 13-JAN-17:33 | 370.50 | 260.40 | 1765.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 195.10 |
| February | 743.69 | 14-FEB-16:30 | 71.25 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.10 |
| March | 1051.44 | 08-MAR-16:30 | 71.25 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.85 |
| April | 2587.45 | 13-APR-16:27 | 370.50 | 260.40 | 1765.87 | 0.00 | 0.00 | 0.00 | 0.00 | 31.27 | 0.00 |
| May | 3186.62 | 19-MAY-16:40 | 123.50 | 86.80 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 168.35 | 0.00 |
| June | 3907.60 | 28-JUN-16:30 | 123.50 | 86.80 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 143.16 | 0.00 |
| July | 3891.59 | 04-JUL-17:20 | 619.87 | 351.55 | 1765.87 | 0.00 | 0.00 | 0.00 | 0.00 | 298.24 | 0.00 |
| August | 3553.28 | 20-AUG-17:05 | 826.50 | 468.73 | 2354.49 | 0.00 | 0.00 | 0.00 | 0.00 | 178.40 | 0.00 |
| September | 3030.19 | 02-SEP-16:30 | 123.50 | 86.80 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 77.62 | 0.00 |
| October | 2382.62 | 06-OCT-16:13 | 370.50 | 260.40 | 1765.87 | 0.00 | 0.00 | 0.00 | 0.00 | 54.19 | 0.00 |
| November | 365.74 | 20-NOV-20:50 | 206.62 | 138.88 | 523.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81.35 |
| December | 375.28 | 30-DEC-17:35 | 247.00 | 173.60 | 1177.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 152.62 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 365.74 | 71.25 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 3907.60 | 826.50 | 468.73 | 2354.49 | 0.00 | 0.00 | 0.00 | 0.00 | 298.24 | 195.10 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: T SE APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 1911.30 | 23-JAN-14:20 | 0.00 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.22 |
| February | 2322.71 | 14-FEB-14:30 | 0.00 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.06 |
| March | 2315.20 | 08-MAR-14:00 | 0.00 | 17.36 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.27 |
| April | 2676.46 | 28-APR-13:00 | 0.00 | 17.36 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 6.56 | 0.00 |
| May | 2755.89 | 19-MAY-12:50 | 0.00 | 17.36 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 117.32 | 0.00 |
| June | 3315.72 | 29-JUN-14:40 | 0.00 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 276.24 | 0.00 |
| July | 3549.74 | 22-JUL-14:00 | 118.75 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 275.47 | 0.00 |
| August | 3415.34 | 17-AUG-13:30 | 0.00 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 159.11 | 0.00 |
| September | 3713.67 | 03-SEP-13:30 | 118.75 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 93.52 | 0.00 |
| October | 3317.52 | 01-OCT-13:30 | 118.75 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 18.55 | 0.00 |
| November | 2069.18 | 20-NOV-13:50 | 0.00 | 17.36 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.35 |
| December | 1939.61 | 31-DEC-14:30 | 118.75 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 1911.30 | 0.00 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 3713.67 | 118.75 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 276.24 | 52.35 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: T NE APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 319.56 | 23-JAN-18:12 | 826.50 | 468.73 | 2354.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 145.73 |
| February | 362.71 | 28-FEB-19:30 | 206.62 | 138.88 | 547.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 150.74 |
| March | 632.64 | 26-MAR-15:10 | 71.25 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.67 |
| April | 1799.36 | 28-APR-15:10 | 71.25 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 23.36 | 0.00 |
| May | 2291.05 | 19-MAY-16:15 | 494.00 | 347.20 | 2354.49 | 0.00 | 0.00 | 0.00 | 0.00 | 164.90 | 0.00 |
| June | 3140.22 | 29-JUN-15:10 | 71.25 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 283.43 | 0.00 |
| July | 2986.46 | 22-JUL-15:10 | 71.25 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 234.40 | 0.00 |
| August | 2708.47 | 20-AUG-16:07 | 741.00 | 520.80 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 125.27 | 0.00 |
| September | 2458.28 | 03-SEP-14:10 | 59.38 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 113.30 | 0.00 |
| October | 1783.96 | 01-OCT-15:10 | 71.25 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 28.03 | 0.00 |
| November | 378.37 | 07-NOV-09:30 | 118.75 | 34.72 | 788.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.85 |
| December | 311.89 | 30-DEC-12:00 | 59.38 | 17.36 | 412.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 311.89 | 59.38 | 17.36 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 3140.22 | 826.50 | 520.80 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 283.43 | 150.74 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: T N1 APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 370.06 | 02-JAN-18:12 | 1033.12 | 585.91 | 2943.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96.22 |
| February | 412.38 | 11-FEB-21:10 | 237.50 | 95.48 | 500.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.85 |
| March | 444.37 | 17-MAR-20:00 | 206.62 | 138.88 | 523.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 178.98 |
| April | 1392.02 | 27-APR-16:27 | 370.50 | 260.40 | 1765.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.90 | 0.00 |
| May | 1860.56 | 19-MAY-17:10 | 413.25 | 234.36 | 1177.25 | 0.00 | 0.00 | 0.00 | 0.00 | 100.86 | 0.00 |
| June | 2390.97 | 29-JUN-15:10 | 71.25 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 170.95 | 0.00 |
| July | 2335.05 | 04-JUL-17:04 | 1033.12 | 585.91 | 2943.11 | 0.00 | 0.00 | 0.00 | 0.00 | 193.52 | 0.00 |
| August | 2159.37 | 20-AUG-16:20 | 247.00 | 173.60 | 1177.25 | 0.00 | 0.00 | 0.00 | 0.00 | 84.07 | 0.00 |
| September | 1846.73 | 03-SEP-14:10 | 59.38 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 68.34 | 0.00 |
| October | 1458.88 | 01-OCT-16:10 | 123.50 | 86.80 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 40.64 | 0.00 |
| November | 365.12 | 20-NOV-20:50 | 206.62 | 138.88 | 523.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.99 |
| December | 313.68 | 02-DEC-18:01 | 1446.38 | 820.27 | 4120.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.51 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 313.68 | 59.38 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 2390.97 | 1446.38 | 820.27 | 4120.36 | 0.00 | 0.00 | 0.00 | 0.00 | 193.52 | 178.98 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: T N2 APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 365.41 | 23-JAN-18:50 | 206.62 | 117.18 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 100.39 |
| February | 398.59 | 11-FEB-21:00 | 206.62 | 138.88 | 523.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 445.86 | 17-MAR-20:00 | 206.62 | 138.88 | 523.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 179.55 |
| April | 1393.97 | 28-APR-16:08 | 494.00 | 347.20 | 2354.49 | 0.00 | 0.00 | 0.00 | 0.00 | 14.86 | 0.00 |
| May | 1838.05 | 19-MAY-17:20 | 413.25 | 234.36 | 1177.25 | 0.00 | 0.00 | 0.00 | 0.00 | 98.14 | 0.00 |
| June | 2389.70 | 29-JUN-15:10 | 71.25 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 170.95 | 0.00 |
| July | 2313.48 | 04-JUL-17:10 | 1033.12 | 585.91 | 2943.11 | 0.00 | 0.00 | 0.00 | 0.00 | 193.52 | 0.00 |
| August | 2144.15 | 20-AUG-16:20 | 247.00 | 173.60 | 1177.25 | 0.00 | 0.00 | 0.00 | 0.00 | 84.07 | 0.00 |
| September | 1851.76 | 03-SEP-14:10 | 59.38 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 68.34 | 0.00 |
| October | 1450.04 | 01-OCT-16:10 | 123.50 | 86.80 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 40.64 | 0.00 |
| November | 364.32 | 23-NOV-21:00 | 206.62 | 138.88 | 523.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.43 |
| December | 297.13 | 02-DEC-12:20 | 59.38 | 17.36 | 406.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.15 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 297.13 | 59.38 | 17.36 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 2389.70 | 1033.12 | 585.91 | 2943.11 | 0.00 | 0.00 | 0.00 | 0.00 | 193.52 | 179.55 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: T S1 APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 1915.97 | 02-JAN-14:30 | 118.75 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.02 |
| February | 2147.21 | 14-FEB-14:50 | 0.00 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.81 |
| March | 2004.09 | 08-MAR-14:00 | 0.00 | 17.36 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.21 |
| April | 2124.51 | 26-APR-14:10 | 0.00 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 29.80 | 0.00 |
| May | 2128.25 | 19-MAY-14:10 | 0.00 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 59.33 | 0.00 |
| June | 2544.83 | 29-JUN-15:10 | 0.00 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 170.95 | 0.00 |
| July | 2774.65 | 22-JUL-14:00 | 118.75 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 166.16 | 0.00 |
| August | 2771.12 | 20-AUG-15:20 | 237.50 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 52.54 | 0.00 |
| September | 3067.40 | 03-SEP-13:30 | 118.75 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 56.41 | 0.00 |
| October | 2884.29 | 01-OCT-13:40 | 118.75 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 11.73 | 0.00 |
| November | 2073.63 | 20-NOV-14:00 | 0.00 | 17.36 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.96 |
| December | 2013.08 | 31-DEC-14:40 | 118.75 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 1915.97 | 0.00 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 3067.40 | 237.50 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 170.95 | 30.96 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: T S2 APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 1924.03 | 02-JAN-14:30 | 118.75 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.02 |
| February | 2155.57 | 14-FEB-14:50 | 0.00 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.81 |
| March | 2023.77 | 08-MAR-14:00 | 0.00 | 17.36 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.21 |
| April | 2140.59 | 28-APR-13:40 | 0.00 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 3.96 | 0.00 |
| May | 2139.33 | 19-MAY-13:30 | 0.00 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 60.32 | 0.00 |
| June | 2545.52 | 29-JUN-14:40 | 0.00 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 166.62 | 0.00 |
| July | 2783.77 | 22-JUL-14:00 | 118.75 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 166.16 | 0.00 |
| August | 2765.43 | 20-AUG-15:20 | 237.50 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 52.54 | 0.00 |
| September | 3078.75 | 03-SEP-13:30 | 118.75 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 56.41 | 0.00 |
| October | 2894.88 | 01-OCT-13:40 | 118.75 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 11.73 | 0.00 |
| November | 2090.48 | 01-NOV-13:00 | 0.00 | 17.36 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 235.39 |
| December | 2020.07 | 31-DEC-14:40 | 118.75 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 1924.03 | 0.00 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 3078.75 | 237.50 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 166.62 | 235.39 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: T CORRIDOR
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 0.00 | 01-JAN-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.27 |
| February | 0.00 | 01-FEB-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.32 |
| March | 0.00 | 01-MAR-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.42 |
| April | 0.00 | 01-APR-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.96 |
| May | 0.00 | 01-MAY-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.79 |
| June | 0.00 | 01-JUN-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.32 |
| July | 0.00 | 01-JUL-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.19 |
| August | 0.00 | 01-AUG-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.41 |
| September | 0.00 | 01-SEP-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.27 |
| October | 0.00 | 01-OCT-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.74 |
| November | 0.00 | 01-NOV-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.89 |
| December | 0.00 | 01-DEC-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.92 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
| Minimum of Months | 0.00 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.41 | |
| Maximum of Months | 0.00 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.32 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: G CORRIDOR
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 0.00 | 01-JAN-00:10 | 397.10 | 370.63 | 56.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.26 |
| February | 0.00 | 01-FEB-00:10 | 397.10 | 370.63 | 56.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.12 |
| March | 0.00 | 01-MAR-00:10 | 397.10 | 370.63 | 56.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.42 |
| April | 0.00 | 01-APR-00:10 | 397.10 | 370.63 | 56.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.04 |
| May | 0.00 | 01-MAY-00:10 | 397.10 | 370.63 | 56.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.11 |
| June | 0.00 | 01-JUN-00:10 | 397.10 | 370.63 | 56.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.86 |
| July | 0.00 | 01-JUL-00:10 | 397.10 | 370.63 | 56.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.17 |
| August | 0.00 | 01-AUG-00:10 | 397.10 | 370.63 | 56.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.64 |
| September | 0.00 | 01-SEP-00:10 | 397.10 | 370.63 | 56.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.26 |
| October | 0.00 | 01-OCT-00:10 | 397.10 | 370.63 | 56.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.02 |
| November | 0.00 | 01-NOV-00:10 | 397.10 | 370.63 | 56.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.65 |
| December | 0.00 | 01-DEC-00:10 | 397.10 | 370.63 | 56.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.52 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 0.00 | 397.10 | 370.63 | 56.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.64 | |
| Maximum of Months | 0.00 | 397.10 | 370.63 | 56.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.12 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: M CORRIDOR
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 0.00 | 01-JAN-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.66 |
| February | 0.00 | 01-FEB-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.82 |
| March | 0.00 | 01-MAR-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.77 |
| April | 0.00 | 01-APR-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.12 |
| May | 0.00 | 01-MAY-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.18 |
| June | 0.00 | 01-JUN-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.50 |
| July | 0.00 | 01-JUL-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.76 |
| August | 0.00 | 01-AUG-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.35 |
| September | 0.00 | 01-SEP-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.51 |
| October | 0.00 | 01-OCT-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.85 |
| November | 0.00 | 01-NOV-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.38 |
| December | 0.00 | 01-DEC-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.92 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
| Minimum of Months | 0.00 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.35 | |
| Maximum of Months | 0.00 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.82 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
| January | 0.101882E+12 | 70413.83 | 01-JAN-17:00 | 0.428613E+11 | 52224.04 | 17-JAN-08:09 |
| February | 0.920235E+11 | 68288.55 | 14-FEB-18:19 | 0.303360E+11 | 54300.33 | 06-FEB-04:00 |
| March | 0.100445E+12 | 68572.50 | 25-MAR-17:19 | 0.126679E+11 | 37248.05 | 04-MAR-05:00 |
| April | 0.101654E+12 | 72280.95 | 26-APR-17:40 | 0.191923E+10 | 13055.05 | 08-APR-04:00 |
| May | 0.110076E+12 | 82585.42 | 19-MAY-17:10 | 0.414344E+09 | 7442.40 | 05-MAY-04:00 |
| June | 0.120457E+12 | 87096.40 | 23-JUN-17:30 | 15790127.61 | 2178.61 | 09-JUN-03:49 |
| July | 0.133453E+12 | 89115.25 | 21-JUL-17:40 | 0.00 | 0.00 | 01-JUL-00:10 |
| August | 0.129552E+12 | 90289.92 | 20-AUG-17:10 | 0.00 | 0.00 | 01-AUG-00:10 |
| September | 0.115548E+12 | 86025.00 | 02-SEP-17:10 | 0.00 | 0.00 | 01-SEP-00:10 |
| October | 0.107089E+12 | 78703.69 | 05-OCT-17:10 | 0.340293E+10 | 26166.11 | 26-OCT-03:00 |
| November | 0.963881E+11 | 63614.73 | 02-NOV-17:30 | 0.136011E+11 | 30282.42 | 27-NOV-05:00 |
| December | 0.100345E+12 | 64286.97 | 14-DEC-18:40 | 0.417083E+11 | 49745.18 | 22-DEC-06:00 |
| Annual Sum or Average | 0.130891E+13 | 0.146927E+12 | ||||
| Minimum of Months | 0.920235E+11 | 63614.73 | 0.00 | 0.00 | ||
| Maximum of Months | 0.133453E+12 | 90289.92 | 0.428613E+11 | 54300.33 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| INTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [J] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
| January | 0.840929E+10 | 0.498509E+10 | 0.389380E+11 | 0.00 | 0.693085E+10 | 0.00 | 0.00 | 0.106294E+10 | 0.00 | 0.00 | 0.00 | 0.415556E+11 | 0.00 |
| February | 0.760941E+10 | 0.424593E+10 | 0.351823E+11 | 0.00 | 0.598621E+10 | 0.00 | 0.00 | 0.125035E+10 | 0.00 | 0.00 | 0.00 | 0.377493E+11 | 0.00 |
| March | 0.845392E+10 | 0.432997E+10 | 0.389781E+11 | 0.00 | 0.585699E+10 | 0.00 | 0.00 | 0.187307E+10 | 0.00 | 0.00 | 0.00 | 0.409530E+11 | 0.00 |
| April | 0.814762E+10 | 0.381045E+10 | 0.376905E+11 | 0.00 | 0.688252E+10 | 0.00 | 0.00 | 0.721522E+10 | 0.00 | 0.00 | 0.00 | 0.379078E+11 | 0.00 |
| May | 0.843904E+10 | 0.361372E+10 | 0.389647E+11 | 0.00 | 0.878010E+10 | 0.00 | 0.00 | 0.132458E+11 | 0.00 | 0.00 | 0.00 | 0.370323E+11 | 0.00 |
| June | 0.817737E+10 | 0.332531E+10 | 0.377173E+11 | 0.00 | 0.120479E+11 | 0.00 | 0.00 | 0.252744E+11 | 0.00 | 0.00 | 0.00 | 0.339150E+11 | 0.00 |
| July | 0.840929E+10 | 0.352586E+10 | 0.389380E+11 | 0.00 | 0.146450E+11 | 0.00 | 0.00 | 0.341791E+11 | 0.00 | 0.00 | 0.00 | 0.337557E+11 | 0.00 |
| August | 0.845392E+10 | 0.379135E+10 | 0.389781E+11 | 0.00 | 0.137866E+11 | 0.00 | 0.00 | 0.310704E+11 | 0.00 | 0.00 | 0.00 | 0.334715E+11 | 0.00 |
| September | 0.814762E+10 | 0.403010E+10 | 0.376905E+11 | 0.00 | 0.109680E+11 | 0.00 | 0.00 | 0.215146E+11 | 0.00 | 0.00 | 0.00 | 0.331970E+11 | 0.00 |
| October | 0.842417E+10 | 0.454962E+10 | 0.389514E+11 | 0.00 | 0.816124E+10 | 0.00 | 0.00 | 0.109454E+11 | 0.00 | 0.00 | 0.00 | 0.360571E+11 | 0.00 |
| November | 0.814762E+10 | 0.473489E+10 | 0.376905E+11 | 0.00 | 0.599774E+10 | 0.00 | 0.00 | 0.277637E+10 | 0.00 | 0.00 | 0.00 | 0.370409E+11 | 0.00 |
| December | 0.840929E+10 | 0.507677E+10 | 0.389380E+11 | 0.00 | 0.681247E+10 | 0.00 | 0.00 | 0.825126E+09 | 0.00 | 0.00 | 0.00 | 0.402837E+11 | 0.00 |
| Annual Sum or Average | 0.992286E+11 | 0.500190E+11 | 0.458657E+12 | 0.00 | 0.106856E+12 | 0.00 | 0.00 | 0.151233E+12 | 0.00 | 0.00 | 0.00 | 0.442919E+12 | 0.00 |
| Minimum of Months | 0.760941E+10 | 0.332531E+10 | 0.351823E+11 | 0.00 | 0.585699E+10 | 0.00 | 0.00 | 0.825126E+09 | 0.00 | 0.00 | 0.00 | 0.331970E+11 | 0.00 |
| Maximum of Months | 0.845392E+10 | 0.507677E+10 | 0.389781E+11 | 0.00 | 0.146450E+11 | 0.00 | 0.00 | 0.341791E+11 | 0.00 | 0.00 | 0.00 | 0.415556E+11 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| INTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
| January | 0.00 | 0.00 | 0.428613E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.303360E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.126679E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.191923E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.414344E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 15790127.61 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.340293E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.136011E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.417083E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.146927E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.428613E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| INTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
| January | 5904.43 | 01-JAN-19:10 | 3183.33 | 01-JAN-00:10 | 22709.69 | 03-JAN-17:10 | 0.00 | 4034.93 | 18-JAN-01:30 | 0.00 | 0.00 | 01-JAN-00:10 |
| February | 5904.43 | 01-FEB-19:10 | 3183.33 | 01-FEB-00:10 | 22709.69 | 01-FEB-17:10 | 0.00 | 4140.13 | 06-FEB-04:00 | 0.00 | 0.00 | 01-FEB-00:10 |
| March | 5904.43 | 01-MAR-19:10 | 3183.33 | 01-MAR-00:10 | 22709.69 | 01-MAR-17:10 | 0.00 | 3949.23 | 08-MAR-16:10 | 0.00 | 0.00 | 01-MAR-00:10 |
| April | 5904.43 | 01-APR-18:10 | 3183.33 | 01-APR-00:10 | 22709.69 | 03-APR-16:10 | 0.00 | 6007.73 | 13-APR-16:30 | 0.00 | 0.00 | 01-APR-00:10 |
| May | 5904.43 | 01-MAY-18:10 | 3183.33 | 01-MAY-00:10 | 22709.69 | 01-MAY-16:10 | 0.00 | 7299.08 | 19-MAY-16:30 | 0.00 | 0.00 | 01-MAY-00:10 |
| June | 5904.43 | 01-JUN-18:10 | 3183.33 | 01-JUN-00:10 | 22709.69 | 01-JUN-16:10 | 0.00 | 9639.30 | 28-JUN-16:19 | 0.00 | 0.00 | 01-JUN-00:10 |
| July | 5904.43 | 01-JUL-18:10 | 3183.33 | 01-JUL-00:10 | 22709.69 | 03-JUL-16:10 | 0.00 | 9417.33 | 21-JUL-16:00 | 0.00 | 0.00 | 01-JUL-00:10 |
| August | 5904.43 | 01-AUG-18:10 | 3183.33 | 01-AUG-00:10 | 22709.69 | 01-AUG-16:10 | 0.00 | 8834.87 | 20-AUG-16:10 | 0.00 | 0.00 | 01-AUG-00:10 |
| September | 5904.43 | 01-SEP-18:10 | 3183.33 | 01-SEP-00:10 | 22709.69 | 01-SEP-16:10 | 0.00 | 8041.63 | 03-SEP-13:50 | 0.00 | 0.00 | 01-SEP-00:10 |
| October | 5904.43 | 01-OCT-18:10 | 3183.33 | 01-OCT-00:10 | 22709.69 | 02-OCT-16:10 | 0.00 | 7172.19 | 01-OCT-15:30 | 0.00 | 0.00 | 01-OCT-00:10 |
| November | 5904.43 | 01-NOV-18:10 | 3183.33 | 01-NOV-00:10 | 22709.69 | 01-NOV-16:10 | 0.00 | 3956.87 | 20-NOV-14:30 | 0.00 | 0.00 | 01-NOV-00:10 |
| December | 5904.43 | 01-DEC-19:10 | 3183.33 | 01-DEC-00:10 | 22709.69 | 01-DEC-17:10 | 0.00 | 3942.64 | 22-DEC-06:00 | 0.00 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 5904.43 | 3183.33 | 22709.69 | 0.00 | 3942.64 | 0.00 | 0.00 | |||||
| Maximum of Months | 5904.43 | 3183.33 | 22709.69 | 0.00 | 9639.30 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| COOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY {Maximum} [W] | HEATRECOVERY:ELECTRICITY {TIMESTAMP} | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
| January | 5930.46 | 03-JAN-14:39 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 37737.59 | 08-JAN-07:49 | 0.00 |
| February | 7803.53 | 14-FEB-15:09 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 35657.81 | 13-FEB-08:00 | 0.00 |
| March | 7232.86 | 08-MAR-16:10 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 36225.81 | 02-MAR-07:40 | 0.00 |
| April | 13591.98 | 13-APR-16:30 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 31585.11 | 10-APR-06:30 | 0.00 |
| May | 18444.55 | 19-MAY-16:40 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 32781.36 | 04-MAY-05:40 | 0.00 |
| June | 27057.48 | 28-JUN-15:00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 30233.66 | 24-JUN-06:10 | 0.00 |
| July | 26863.92 | 22-JUL-15:09 | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 32570.98 | 25-JUL-07:49 | 0.00 |
| August | 24848.29 | 20-AUG-16:10 | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 32868.99 | 31-AUG-06:40 | 0.00 |
| September | 22060.47 | 03-SEP-13:50 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 32681.44 | 08-SEP-05:40 | 0.00 |
| October | 18174.61 | 01-OCT-15:30 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 31544.65 | 20-OCT-06:49 | 0.00 |
| November | 7437.65 | 20-NOV-14:30 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 30547.82 | 20-NOV-08:00 | 0.00 |
| December | 5496.76 | 31-DEC-14:00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 32238.79 | 29-DEC-07:49 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
| Minimum of Months | 5496.76 | 0.00 | 0.00 | 0.00 | 30233.66 | 0.00 | |||
| Maximum of Months | 27057.48 | 0.00 | 0.00 | 0.00 | 37737.59 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
| January | 70413.83 | 01-JAN-17:00 | 4289.87 | 22609.62 | 3183.33 | 0.00 | 2223.30 | 0.00 | 0.00 | 1298.63 | 0.00 |
| February | 68288.55 | 14-FEB-18:19 | 5231.74 | 22609.62 | 3183.33 | 0.00 | 2844.67 | 0.00 | 0.00 | 3397.94 | 0.00 |
| March | 68572.50 | 25-MAR-17:19 | 5231.74 | 22609.62 | 0.00 | 0.00 | 2936.73 | 0.00 | 0.00 | 3688.27 | 0.00 |
| April | 72280.95 | 26-APR-17:40 | 5231.74 | 22609.62 | 0.00 | 0.00 | 5590.63 | 0.00 | 0.00 | 12144.18 | 0.00 |
| May | 82585.42 | 19-MAY-17:10 | 5231.74 | 22609.62 | 0.00 | 0.00 | 7283.44 | 0.00 | 0.00 | 18104.93 | 0.00 |
| June | 87096.40 | 23-JUN-17:30 | 5231.74 | 22609.62 | 0.00 | 0.00 | 8667.52 | 0.00 | 0.00 | 23007.42 | 0.00 |
| July | 89115.25 | 21-JUL-17:40 | 5231.74 | 22609.62 | 0.00 | 0.00 | 9209.69 | 0.00 | 0.00 | 25421.96 | 0.00 |
| August | 90289.92 | 20-AUG-17:10 | 5231.74 | 22609.62 | 0.00 | 0.00 | 8736.77 | 0.00 | 0.00 | 24370.53 | 0.00 |
| September | 86025.00 | 02-SEP-17:10 | 5231.74 | 22609.62 | 0.00 | 0.00 | 7522.85 | 0.00 | 0.00 | 19800.76 | 0.00 |
| October | 78703.69 | 05-OCT-17:10 | 5231.74 | 22609.62 | 0.00 | 0.00 | 6411.74 | 0.00 | 0.00 | 15003.47 | 0.00 |
| November | 63614.73 | 02-NOV-17:30 | 5231.74 | 22609.62 | 3183.33 | 0.00 | 3075.61 | 0.00 | 0.00 | 4166.29 | 0.00 |
| December | 64286.97 | 14-DEC-18:40 | 5231.74 | 22609.62 | 3183.33 | 0.00 | 2417.42 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
| Minimum of Months | 63614.73 | 4289.87 | 22609.62 | 0.00 | 0.00 | 2223.30 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 90289.92 | 5231.74 | 22609.62 | 3183.33 | 0.00 | 9209.69 | 0.00 | 0.00 | 25421.96 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| INTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | |
| January | 0.00 | 0.00 | 52224.04 | 17-JAN-08:09 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 54300.33 | 06-FEB-04:00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 37248.05 | 04-MAR-05:00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 13055.05 | 08-APR-04:00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 7442.40 | 05-MAY-04:00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 2178.61 | 09-JUN-03:49 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 26166.11 | 26-OCT-03:00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 30282.42 | 27-NOV-05:00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 49745.18 | 22-DEC-06:00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 54300.33 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: G SW APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: G NW APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: OFFICE
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: G NE APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: G N1 APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: G N2 APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: G S1 APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: G S2 APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: M SW APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: M NW APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: M SE APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: M NE APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: M N1 APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: M N2 APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: M S1 APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: M S2 APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: T SW APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: T NW APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: T SE APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: T NE APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: T N1 APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: T N2 APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: T S1 APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: T S2 APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: T CORRIDOR
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: G CORRIDOR
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: M CORRIDOR
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: G SW APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 533.00 | 21.54 | 153.33 | 21.45 | 153.33 | 21.38 |
| February | 473.00 | 21.59 | 123.67 | 21.49 | 123.67 | 21.42 |
| March | 506.00 | 21.78 | 65.50 | 21.71 | 65.50 | 21.64 |
| April | 508.00 | 23.04 | 2.83 | 23.03 | 2.83 | 23.02 |
| May | 363.83 | 23.50 | 1.00 | 23.50 | 0.00 | 23.50 |
| June | 89.00 | 23.80 | 84.17 | 23.90 | 0.00 | 23.90 |
| July | 25.50 | 24.00 | 475.17 | 24.00 | 25.50 | 24.00 |
| August | 7.67 | 24.00 | 470.67 | 24.00 | 7.67 | 24.00 |
| September | 0.00 | 0.00 | 318.83 | 24.00 | 0.00 | 24.00 |
| October | 238.67 | 23.44 | 76.50 | 23.57 | 0.00 | 23.57 |
| November | 489.83 | 22.93 | 0.00 | 22.93 | 0.00 | 22.93 |
| December | 533.00 | 21.62 | 131.17 | 21.52 | 131.17 | 21.45 |
| Annual Sum or Average | 3767.50 | 22.36 | 1902.83 | 22.67 | 509.67 | 22.55 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 21.45 | 0.00 | 21.38 |
| Maximum of Months | 533.00 | 24.00 | 475.17 | 24.00 | 153.33 | 24.00 |
Report: ComfortReportSimple55Monthly
For: G NW APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 744.00 | 21.11 | 729.00 | 21.10 | 729.00 | 21.10 |
| February | 672.00 | 21.15 | 582.50 | 21.13 | 582.50 | 21.12 |
| March | 744.00 | 21.27 | 441.83 | 21.21 | 441.83 | 21.18 |
| April | 720.00 | 22.52 | 90.17 | 22.36 | 90.17 | 22.24 |
| May | 562.67 | 23.45 | 2.67 | 23.46 | 0.00 | 23.46 |
| June | 106.50 | 23.80 | 133.17 | 23.91 | 0.00 | 23.91 |
| July | 26.50 | 24.00 | 689.33 | 24.00 | 26.50 | 24.00 |
| August | 15.00 | 24.00 | 669.67 | 24.00 | 15.00 | 24.00 |
| September | 16.67 | 24.00 | 297.50 | 24.00 | 1.33 | 24.00 |
| October | 514.67 | 23.01 | 61.00 | 23.09 | 4.33 | 23.08 |
| November | 720.00 | 21.49 | 184.00 | 21.41 | 184.00 | 21.36 |
| December | 744.00 | 21.11 | 716.33 | 21.11 | 716.33 | 21.10 |
| Annual Sum or Average | 5586.00 | 21.86 | 4597.17 | 22.04 | 2791.00 | 21.85 |
| Minimum of Months | 15.00 | 21.11 | 2.67 | 21.10 | 0.00 | 21.10 |
| Maximum of Months | 744.00 | 24.00 | 729.00 | 24.00 | 729.00 | 24.00 |
Report: ComfortReportSimple55Monthly
For: OFFICE
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 140.00 | 22.61 | 32.83 | 22.28 | 32.83 | 22.05 |
| February | 130.00 | 22.65 | 17.50 | 22.41 | 17.50 | 22.23 |
| March | 156.50 | 23.46 | 2.00 | 23.43 | 2.00 | 23.40 |
| April | 71.33 | 23.98 | 1.33 | 24.01 | 0.00 | 24.01 |
| May | 20.67 | 23.98 | 71.83 | 24.22 | 0.00 | 24.22 |
| June | 0.00 | 0.00 | 146.33 | 24.24 | 0.00 | 24.24 |
| July | 0.67 | 25.80 | 140.00 | 24.24 | 0.67 | 24.25 |
| August | 3.33 | 25.66 | 161.00 | 24.27 | 3.33 | 24.29 |
| September | 0.50 | 25.67 | 140.00 | 24.24 | 0.50 | 24.24 |
| October | 18.67 | 23.76 | 92.50 | 24.18 | 0.00 | 24.18 |
| November | 64.67 | 23.93 | 12.17 | 24.00 | 0.00 | 24.00 |
| December | 140.00 | 22.94 | 12.00 | 22.76 | 12.00 | 22.62 |
| Annual Sum or Average | 746.33 | 23.19 | 829.50 | 23.61 | 68.83 | 23.50 |
| Minimum of Months | 0.00 | 0.00 | 1.33 | 22.28 | 0.00 | 22.05 |
| Maximum of Months | 156.50 | 25.80 | 161.00 | 24.27 | 32.83 | 24.29 |
Report: ComfortReportSimple55Monthly
For: G NE APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 744.00 | 21.10 | 737.67 | 21.10 | 737.67 | 21.10 |
| February | 672.00 | 21.13 | 605.83 | 21.12 | 605.83 | 21.11 |
| March | 744.00 | 21.27 | 396.33 | 21.21 | 396.33 | 21.18 |
| April | 720.00 | 22.67 | 68.17 | 22.53 | 68.17 | 22.42 |
| May | 506.67 | 23.52 | 18.67 | 23.54 | 0.00 | 23.54 |
| June | 93.67 | 23.85 | 180.17 | 23.95 | 0.00 | 23.95 |
| July | 18.33 | 24.00 | 680.00 | 24.00 | 18.33 | 24.00 |
| August | 11.17 | 24.00 | 665.67 | 24.00 | 11.17 | 24.00 |
| September | 21.33 | 24.00 | 325.83 | 24.00 | 0.00 | 24.00 |
| October | 508.00 | 23.05 | 57.17 | 23.15 | 0.00 | 23.15 |
| November | 720.00 | 21.46 | 169.17 | 21.39 | 169.17 | 21.35 |
| December | 744.00 | 21.10 | 724.50 | 21.10 | 724.50 | 21.10 |
| Annual Sum or Average | 5503.17 | 21.86 | 4629.17 | 22.06 | 2731.17 | 21.87 |
| Minimum of Months | 11.17 | 21.10 | 18.67 | 21.10 | 0.00 | 21.10 |
| Maximum of Months | 744.00 | 24.00 | 737.67 | 24.00 | 737.67 | 24.00 |
Report: ComfortReportSimple55Monthly
For: G N1 APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 744.00 | 21.11 | 719.33 | 21.10 | 719.33 | 21.10 |
| February | 672.00 | 21.14 | 521.00 | 21.12 | 521.00 | 21.12 |
| March | 744.00 | 21.27 | 304.67 | 21.23 | 304.67 | 21.20 |
| April | 720.00 | 22.66 | 46.67 | 22.56 | 46.67 | 22.48 |
| May | 542.17 | 23.63 | 9.50 | 23.64 | 0.00 | 23.64 |
| June | 134.67 | 23.96 | 86.83 | 23.98 | 0.00 | 23.98 |
| July | 21.17 | 24.00 | 629.67 | 24.00 | 21.17 | 24.00 |
| August | 14.83 | 24.00 | 556.67 | 24.00 | 14.83 | 24.00 |
| September | 31.83 | 24.00 | 206.83 | 24.00 | 0.00 | 24.00 |
| October | 515.83 | 23.18 | 36.00 | 23.23 | 0.00 | 23.23 |
| November | 720.00 | 21.57 | 127.67 | 21.50 | 127.67 | 21.45 |
| December | 744.00 | 21.11 | 689.00 | 21.11 | 689.00 | 21.10 |
| Annual Sum or Average | 5604.50 | 21.93 | 3933.83 | 22.05 | 2444.33 | 21.87 |
| Minimum of Months | 14.83 | 21.11 | 9.50 | 21.10 | 0.00 | 21.10 |
| Maximum of Months | 744.00 | 24.00 | 719.33 | 24.00 | 719.33 | 24.00 |
Report: ComfortReportSimple55Monthly
For: G N2 APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 744.00 | 21.11 | 719.67 | 21.10 | 719.67 | 21.10 |
| February | 672.00 | 21.14 | 522.17 | 21.12 | 522.17 | 21.12 |
| March | 744.00 | 21.28 | 300.83 | 21.23 | 300.83 | 21.20 |
| April | 720.00 | 22.67 | 44.83 | 22.58 | 44.83 | 22.50 |
| May | 532.67 | 23.64 | 10.00 | 23.64 | 0.00 | 23.64 |
| June | 133.17 | 23.97 | 88.67 | 23.98 | 0.00 | 23.98 |
| July | 20.67 | 24.00 | 630.67 | 24.00 | 20.67 | 24.00 |
| August | 14.50 | 24.00 | 559.67 | 24.00 | 14.50 | 24.00 |
| September | 31.67 | 24.00 | 206.83 | 24.00 | 0.00 | 24.00 |
| October | 515.67 | 23.18 | 36.33 | 23.24 | 0.00 | 23.24 |
| November | 720.00 | 21.57 | 128.17 | 21.50 | 128.17 | 21.45 |
| December | 744.00 | 21.11 | 690.67 | 21.11 | 690.67 | 21.10 |
| Annual Sum or Average | 5592.33 | 21.93 | 3938.50 | 22.05 | 2441.50 | 21.87 |
| Minimum of Months | 14.50 | 21.11 | 10.00 | 21.10 | 0.00 | 21.10 |
| Maximum of Months | 744.00 | 24.00 | 719.67 | 24.00 | 719.67 | 24.00 |
Report: ComfortReportSimple55Monthly
For: G S1 APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 532.67 | 21.95 | 52.00 | 21.87 | 52.00 | 21.81 |
| February | 473.00 | 21.90 | 24.67 | 21.86 | 24.67 | 21.83 |
| March | 506.00 | 22.21 | 11.67 | 22.18 | 11.67 | 22.16 |
| April | 508.83 | 23.36 | 0.00 | 23.36 | 0.00 | 23.36 |
| May | 353.67 | 23.70 | 3.67 | 23.71 | 0.00 | 23.71 |
| June | 100.83 | 23.95 | 59.33 | 23.97 | 0.00 | 23.97 |
| July | 18.67 | 24.00 | 449.50 | 24.00 | 18.67 | 24.00 |
| August | 7.33 | 24.00 | 414.00 | 24.00 | 7.33 | 24.00 |
| September | 0.00 | 0.00 | 283.50 | 24.00 | 0.00 | 24.00 |
| October | 196.50 | 23.62 | 69.00 | 23.72 | 0.00 | 23.72 |
| November | 464.67 | 23.42 | 0.00 | 23.42 | 0.00 | 23.42 |
| December | 533.00 | 22.07 | 9.83 | 22.05 | 9.83 | 22.03 |
| Annual Sum or Average | 3695.17 | 22.70 | 1377.17 | 23.00 | 124.17 | 22.97 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 21.86 | 0.00 | 21.81 |
| Maximum of Months | 533.00 | 24.00 | 449.50 | 24.00 | 52.00 | 24.00 |
Report: ComfortReportSimple55Monthly
For: G S2 APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 532.33 | 21.94 | 62.50 | 21.86 | 62.50 | 21.78 |
| February | 473.00 | 21.91 | 31.00 | 21.86 | 31.00 | 21.81 |
| March | 506.00 | 22.27 | 11.50 | 22.25 | 11.50 | 22.22 |
| April | 497.50 | 23.43 | 0.00 | 23.43 | 0.00 | 23.43 |
| May | 311.00 | 23.73 | 8.33 | 23.74 | 0.00 | 23.74 |
| June | 82.67 | 23.96 | 76.83 | 23.98 | 0.00 | 23.98 |
| July | 6.33 | 24.00 | 476.33 | 24.00 | 6.33 | 24.00 |
| August | 3.17 | 24.00 | 463.00 | 24.00 | 3.17 | 24.00 |
| September | 0.00 | 0.00 | 345.67 | 24.00 | 0.00 | 24.00 |
| October | 170.83 | 23.62 | 89.83 | 23.75 | 0.00 | 23.75 |
| November | 461.33 | 23.46 | 0.00 | 23.46 | 0.00 | 23.46 |
| December | 533.00 | 22.08 | 10.50 | 22.06 | 10.50 | 22.04 |
| Annual Sum or Average | 3577.17 | 22.69 | 1575.50 | 23.03 | 125.00 | 22.99 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 21.86 | 0.00 | 21.78 |
| Maximum of Months | 533.00 | 24.00 | 476.33 | 24.00 | 62.50 | 24.00 |
Report: ComfortReportSimple55Monthly
For: M SW APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 528.17 | 21.98 | 54.50 | 21.90 | 54.50 | 21.83 |
| February | 468.50 | 22.23 | 25.33 | 22.17 | 25.33 | 22.12 |
| March | 496.00 | 22.86 | 3.83 | 22.85 | 3.83 | 22.83 |
| April | 427.17 | 23.69 | 0.00 | 23.69 | 0.00 | 23.69 |
| May | 244.33 | 23.79 | 28.50 | 23.81 | 0.00 | 23.81 |
| June | 52.50 | 23.87 | 110.33 | 23.96 | 0.00 | 23.96 |
| July | 15.83 | 24.00 | 465.00 | 24.00 | 15.83 | 24.00 |
| August | 7.50 | 24.00 | 432.17 | 24.00 | 7.50 | 24.00 |
| September | 5.67 | 24.00 | 253.00 | 24.00 | 0.00 | 24.00 |
| October | 264.17 | 23.37 | 52.00 | 23.46 | 2.00 | 23.44 |
| November | 491.33 | 22.91 | 0.00 | 22.91 | 0.00 | 22.91 |
| December | 530.67 | 21.97 | 58.17 | 21.88 | 58.17 | 21.81 |
| Annual Sum or Average | 3531.83 | 22.74 | 1482.83 | 23.03 | 167.17 | 22.98 |
| Minimum of Months | 5.67 | 21.97 | 0.00 | 21.88 | 0.00 | 21.81 |
| Maximum of Months | 530.67 | 24.00 | 465.00 | 24.00 | 58.17 | 24.00 |
Report: ComfortReportSimple55Monthly
For: M NW APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 744.00 | 21.19 | 516.00 | 21.15 | 516.00 | 21.14 |
| February | 672.00 | 21.39 | 234.50 | 21.31 | 234.50 | 21.27 |
| March | 744.00 | 22.04 | 29.00 | 22.01 | 29.00 | 21.97 |
| April | 665.17 | 23.54 | 0.00 | 23.54 | 0.00 | 23.54 |
| May | 370.00 | 23.78 | 28.83 | 23.79 | 0.00 | 23.79 |
| June | 58.33 | 23.88 | 193.33 | 23.97 | 0.00 | 23.97 |
| July | 17.83 | 24.00 | 678.00 | 24.00 | 17.83 | 24.00 |
| August | 10.17 | 24.00 | 626.67 | 24.00 | 10.17 | 24.00 |
| September | 42.00 | 23.99 | 254.33 | 24.00 | 2.33 | 24.00 |
| October | 535.83 | 22.99 | 54.50 | 23.02 | 13.83 | 22.97 |
| November | 720.00 | 21.63 | 123.00 | 21.55 | 123.00 | 21.49 |
| December | 744.00 | 21.14 | 610.83 | 21.12 | 610.83 | 21.12 |
| Annual Sum or Average | 5323.33 | 22.11 | 3349.00 | 22.33 | 1557.50 | 22.15 |
| Minimum of Months | 10.17 | 21.14 | 0.00 | 21.12 | 0.00 | 21.12 |
| Maximum of Months | 744.00 | 24.00 | 678.00 | 24.00 | 610.83 | 24.00 |
Report: ComfortReportSimple55Monthly
For: M SE APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 527.17 | 22.00 | 60.17 | 21.91 | 60.17 | 21.83 |
| February | 468.50 | 22.20 | 26.83 | 22.14 | 26.83 | 22.08 |
| March | 492.83 | 22.90 | 2.33 | 22.89 | 2.33 | 22.88 |
| April | 428.33 | 23.72 | 0.00 | 23.72 | 0.00 | 23.72 |
| May | 261.50 | 23.84 | 48.17 | 23.86 | 0.00 | 23.86 |
| June | 61.00 | 23.92 | 112.33 | 23.97 | 0.00 | 23.97 |
| July | 9.00 | 24.00 | 464.50 | 24.00 | 9.00 | 24.00 |
| August | 5.17 | 24.00 | 423.00 | 24.00 | 5.17 | 24.00 |
| September | 7.00 | 24.00 | 249.33 | 24.00 | 0.00 | 24.00 |
| October | 264.50 | 23.37 | 51.00 | 23.46 | 1.67 | 23.44 |
| November | 489.67 | 22.91 | 0.00 | 22.91 | 0.00 | 22.91 |
| December | 533.00 | 21.97 | 59.83 | 21.88 | 59.83 | 21.81 |
| Annual Sum or Average | 3547.67 | 22.76 | 1497.50 | 23.04 | 165.00 | 22.99 |
| Minimum of Months | 5.17 | 21.97 | 0.00 | 21.88 | 0.00 | 21.81 |
| Maximum of Months | 533.00 | 24.00 | 464.50 | 24.00 | 60.17 | 24.00 |
Report: ComfortReportSimple55Monthly
For: M NE APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 744.00 | 21.15 | 521.17 | 21.13 | 521.17 | 21.12 |
| February | 672.00 | 21.35 | 241.50 | 21.28 | 241.50 | 21.25 |
| March | 744.00 | 22.16 | 25.00 | 22.12 | 25.00 | 22.09 |
| April | 649.17 | 23.65 | 0.00 | 23.65 | 0.00 | 23.65 |
| May | 370.17 | 23.86 | 63.50 | 23.88 | 0.00 | 23.88 |
| June | 55.17 | 23.91 | 239.33 | 23.98 | 0.00 | 23.98 |
| July | 10.17 | 24.00 | 667.67 | 24.00 | 10.17 | 24.00 |
| August | 9.50 | 24.00 | 623.83 | 24.00 | 9.50 | 24.00 |
| September | 43.50 | 23.99 | 278.67 | 24.00 | 0.00 | 24.00 |
| October | 523.00 | 23.03 | 52.50 | 23.08 | 8.33 | 23.05 |
| November | 720.00 | 21.60 | 118.83 | 21.53 | 118.83 | 21.48 |
| December | 744.00 | 21.12 | 644.83 | 21.11 | 644.83 | 21.11 |
| Annual Sum or Average | 5284.67 | 22.12 | 3476.83 | 22.35 | 1579.33 | 22.17 |
| Minimum of Months | 9.50 | 21.12 | 0.00 | 21.11 | 0.00 | 21.11 |
| Maximum of Months | 744.00 | 24.00 | 667.67 | 24.00 | 644.83 | 24.00 |
Report: ComfortReportSimple55Monthly
For: M N1 APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 744.00 | 21.19 | 310.00 | 21.16 | 310.00 | 21.15 |
| February | 672.00 | 21.40 | 158.33 | 21.34 | 158.33 | 21.30 |
| March | 744.00 | 22.27 | 5.67 | 22.26 | 5.67 | 22.25 |
| April | 705.33 | 23.71 | 0.00 | 23.71 | 0.00 | 23.71 |
| May | 444.83 | 23.91 | 28.33 | 23.92 | 0.00 | 23.92 |
| June | 95.67 | 23.99 | 101.17 | 23.99 | 0.00 | 23.99 |
| July | 12.83 | 24.00 | 596.50 | 24.00 | 12.83 | 24.00 |
| August | 9.50 | 24.00 | 480.67 | 24.00 | 9.50 | 24.00 |
| September | 45.17 | 24.00 | 165.00 | 24.00 | 1.00 | 24.00 |
| October | 527.50 | 23.21 | 23.67 | 23.24 | 0.00 | 23.24 |
| November | 720.00 | 21.81 | 40.50 | 21.77 | 40.50 | 21.74 |
| December | 744.00 | 21.14 | 497.17 | 21.12 | 497.17 | 21.12 |
| Annual Sum or Average | 5464.83 | 22.26 | 2407.00 | 22.42 | 1035.00 | 22.28 |
| Minimum of Months | 9.50 | 21.14 | 0.00 | 21.12 | 0.00 | 21.12 |
| Maximum of Months | 744.00 | 24.00 | 596.50 | 24.00 | 497.17 | 24.00 |
Report: ComfortReportSimple55Monthly
For: M N2 APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 744.00 | 21.19 | 312.00 | 21.16 | 312.00 | 21.15 |
| February | 672.00 | 21.39 | 160.33 | 21.34 | 160.33 | 21.30 |
| March | 744.00 | 22.29 | 5.50 | 22.28 | 5.50 | 22.27 |
| April | 705.33 | 23.72 | 0.00 | 23.72 | 0.00 | 23.72 |
| May | 444.83 | 23.92 | 28.83 | 23.92 | 0.00 | 23.92 |
| June | 94.00 | 23.99 | 103.33 | 23.99 | 0.00 | 23.99 |
| July | 12.83 | 24.00 | 599.50 | 24.00 | 12.83 | 24.00 |
| August | 9.17 | 24.00 | 482.17 | 24.00 | 9.17 | 24.00 |
| September | 45.33 | 24.00 | 164.83 | 24.00 | 1.00 | 24.00 |
| October | 527.00 | 23.21 | 24.00 | 23.25 | 0.00 | 23.25 |
| November | 720.00 | 21.81 | 39.67 | 21.77 | 39.67 | 21.74 |
| December | 744.00 | 21.14 | 500.17 | 21.12 | 500.17 | 21.12 |
| Annual Sum or Average | 5462.50 | 22.27 | 2420.33 | 22.42 | 1040.67 | 22.28 |
| Minimum of Months | 9.17 | 21.14 | 0.00 | 21.12 | 0.00 | 21.12 |
| Maximum of Months | 744.00 | 24.00 | 599.50 | 24.00 | 500.17 | 24.00 |
Report: ComfortReportSimple55Monthly
For: M S1 APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 523.33 | 22.57 | 7.33 | 22.55 | 7.33 | 22.53 |
| February | 465.17 | 22.73 | 1.17 | 22.73 | 1.17 | 22.72 |
| March | 500.83 | 23.35 | 0.00 | 23.35 | 0.00 | 23.35 |
| April | 478.67 | 23.87 | 0.00 | 23.87 | 0.00 | 23.87 |
| May | 281.00 | 23.92 | 23.33 | 23.92 | 0.00 | 23.92 |
| June | 73.67 | 23.98 | 64.00 | 23.99 | 0.00 | 23.99 |
| July | 13.50 | 24.00 | 422.17 | 24.00 | 13.50 | 24.00 |
| August | 7.50 | 24.00 | 358.83 | 24.00 | 7.50 | 24.00 |
| September | 0.00 | 0.00 | 219.50 | 24.00 | 0.00 | 24.00 |
| October | 244.83 | 23.64 | 39.83 | 23.69 | 0.00 | 23.69 |
| November | 464.50 | 23.42 | 0.00 | 23.42 | 0.00 | 23.42 |
| December | 523.83 | 22.57 | 2.83 | 22.56 | 2.83 | 22.56 |
| Annual Sum or Average | 3576.83 | 23.20 | 1139.00 | 23.39 | 32.33 | 23.38 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 22.55 | 0.00 | 22.53 |
| Maximum of Months | 523.83 | 24.00 | 422.17 | 24.00 | 13.50 | 24.00 |
Report: ComfortReportSimple55Monthly
For: M S2 APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 523.33 | 22.57 | 7.33 | 22.55 | 7.33 | 22.53 |
| February | 465.17 | 22.73 | 1.17 | 22.72 | 1.17 | 22.72 |
| March | 500.17 | 23.36 | 0.00 | 23.36 | 0.00 | 23.36 |
| April | 477.83 | 23.87 | 0.00 | 23.87 | 0.00 | 23.87 |
| May | 281.17 | 23.92 | 25.17 | 23.93 | 0.00 | 23.93 |
| June | 74.17 | 23.98 | 64.17 | 23.99 | 0.00 | 23.99 |
| July | 12.67 | 24.00 | 421.83 | 24.00 | 12.67 | 24.00 |
| August | 7.33 | 24.00 | 358.00 | 24.00 | 7.33 | 24.00 |
| September | 0.00 | 0.00 | 219.67 | 24.00 | 0.00 | 24.00 |
| October | 244.00 | 23.64 | 39.67 | 23.69 | 0.00 | 23.69 |
| November | 464.17 | 23.42 | 0.00 | 23.42 | 0.00 | 23.42 |
| December | 523.67 | 22.57 | 2.83 | 22.56 | 2.83 | 22.56 |
| Annual Sum or Average | 3573.67 | 23.20 | 1139.83 | 23.39 | 31.33 | 23.38 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 22.55 | 0.00 | 22.53 |
| Maximum of Months | 523.67 | 24.00 | 421.83 | 24.00 | 12.67 | 24.00 |
Report: ComfortReportSimple55Monthly
For: T SW APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 507.67 | 21.44 | 361.00 | 21.30 | 361.00 | 21.24 |
| February | 447.50 | 21.60 | 261.00 | 21.41 | 261.00 | 21.33 |
| March | 466.83 | 21.81 | 184.17 | 21.61 | 184.17 | 21.50 |
| April | 420.17 | 22.59 | 66.50 | 22.39 | 66.00 | 22.24 |
| May | 326.17 | 22.99 | 74.67 | 23.05 | 17.83 | 22.96 |
| June | 142.33 | 23.31 | 158.17 | 23.67 | 0.00 | 23.67 |
| July | 49.50 | 23.95 | 446.17 | 23.99 | 49.50 | 23.99 |
| August | 34.83 | 23.88 | 378.33 | 23.98 | 29.67 | 23.98 |
| September | 142.67 | 23.38 | 208.83 | 23.74 | 9.67 | 23.73 |
| October | 356.50 | 22.44 | 119.33 | 22.44 | 63.83 | 22.28 |
| November | 480.83 | 21.75 | 216.33 | 21.55 | 216.33 | 21.44 |
| December | 514.17 | 21.46 | 371.00 | 21.31 | 371.00 | 21.25 |
| Annual Sum or Average | 3889.17 | 22.08 | 2845.50 | 22.23 | 1630.00 | 22.04 |
| Minimum of Months | 34.83 | 21.44 | 66.50 | 21.30 | 0.00 | 21.24 |
| Maximum of Months | 514.17 | 23.95 | 446.17 | 23.99 | 371.00 | 23.99 |
Report: ComfortReportSimple55Monthly
For: T NW APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 744.00 | 21.19 | 647.33 | 21.15 | 647.33 | 21.13 |
| February | 672.00 | 21.37 | 474.67 | 21.26 | 474.67 | 21.21 |
| March | 740.83 | 21.75 | 318.83 | 21.56 | 318.83 | 21.45 |
| April | 611.17 | 22.57 | 102.67 | 22.36 | 102.67 | 22.20 |
| May | 426.33 | 22.97 | 102.33 | 23.04 | 23.33 | 22.96 |
| June | 149.83 | 23.31 | 318.50 | 23.78 | 0.00 | 23.78 |
| July | 51.67 | 23.96 | 660.00 | 23.99 | 51.67 | 23.99 |
| August | 43.83 | 23.85 | 601.67 | 23.99 | 35.83 | 23.98 |
| September | 213.50 | 23.33 | 308.67 | 23.71 | 15.50 | 23.71 |
| October | 584.00 | 22.23 | 199.00 | 22.18 | 135.33 | 22.02 |
| November | 719.83 | 21.38 | 453.67 | 21.27 | 453.67 | 21.22 |
| December | 744.00 | 21.13 | 692.17 | 21.11 | 692.17 | 21.11 |
| Annual Sum or Average | 5701.00 | 21.87 | 4879.50 | 22.07 | 2951.00 | 21.88 |
| Minimum of Months | 43.83 | 21.13 | 102.33 | 21.11 | 0.00 | 21.11 |
| Maximum of Months | 744.00 | 23.96 | 692.17 | 23.99 | 692.17 | 23.99 |
Report: ComfortReportSimple55Monthly
For: T SE APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 505.00 | 21.43 | 363.50 | 21.29 | 363.50 | 21.23 |
| February | 447.50 | 21.58 | 265.50 | 21.40 | 265.50 | 21.32 |
| March | 471.00 | 21.83 | 179.50 | 21.63 | 179.50 | 21.51 |
| April | 420.33 | 22.66 | 62.83 | 22.47 | 60.50 | 22.32 |
| May | 330.00 | 23.05 | 73.33 | 23.11 | 14.50 | 23.04 |
| June | 138.50 | 23.36 | 150.83 | 23.69 | 0.00 | 23.69 |
| July | 42.83 | 23.96 | 445.67 | 23.99 | 42.83 | 23.99 |
| August | 34.00 | 23.87 | 384.33 | 23.98 | 27.50 | 23.98 |
| September | 143.33 | 23.41 | 202.83 | 23.74 | 10.17 | 23.74 |
| October | 359.00 | 22.47 | 117.50 | 22.45 | 64.50 | 22.29 |
| November | 479.33 | 21.72 | 215.50 | 21.53 | 215.50 | 21.43 |
| December | 515.00 | 21.46 | 376.83 | 21.31 | 376.83 | 21.24 |
| Annual Sum or Average | 3885.83 | 22.09 | 2838.17 | 22.23 | 1620.83 | 22.04 |
| Minimum of Months | 34.00 | 21.43 | 62.83 | 21.29 | 0.00 | 21.23 |
| Maximum of Months | 515.00 | 23.96 | 445.67 | 23.99 | 376.83 | 23.99 |
Report: ComfortReportSimple55Monthly
For: T NE APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 744.00 | 21.13 | 675.17 | 21.11 | 675.17 | 21.11 |
| February | 672.00 | 21.31 | 474.83 | 21.23 | 474.83 | 21.19 |
| March | 744.00 | 21.82 | 285.50 | 21.62 | 285.50 | 21.51 |
| April | 589.17 | 22.73 | 83.17 | 22.53 | 83.17 | 22.37 |
| May | 389.67 | 23.04 | 115.67 | 23.17 | 16.67 | 23.10 |
| June | 134.33 | 23.35 | 344.17 | 23.82 | 0.00 | 23.82 |
| July | 47.67 | 23.97 | 658.67 | 24.00 | 47.67 | 23.99 |
| August | 40.33 | 23.85 | 610.83 | 23.99 | 33.00 | 23.98 |
| September | 189.83 | 23.35 | 327.83 | 23.75 | 14.50 | 23.75 |
| October | 597.17 | 22.37 | 188.17 | 22.31 | 122.33 | 22.15 |
| November | 720.00 | 21.31 | 443.50 | 21.23 | 443.50 | 21.19 |
| December | 744.00 | 21.10 | 727.00 | 21.10 | 727.00 | 21.10 |
| Annual Sum or Average | 5612.17 | 21.87 | 4934.50 | 22.09 | 2923.33 | 21.89 |
| Minimum of Months | 40.33 | 21.10 | 83.17 | 21.10 | 0.00 | 21.10 |
| Maximum of Months | 744.00 | 23.97 | 727.00 | 24.00 | 727.00 | 23.99 |
Report: ComfortReportSimple55Monthly
For: T N1 APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 744.00 | 21.13 | 679.50 | 21.12 | 679.50 | 21.11 |
| February | 672.00 | 21.30 | 464.17 | 21.22 | 464.17 | 21.19 |
| March | 744.00 | 21.73 | 242.67 | 21.57 | 242.67 | 21.48 |
| April | 663.17 | 22.81 | 71.67 | 22.64 | 71.67 | 22.50 |
| May | 438.00 | 23.23 | 61.83 | 23.24 | 13.50 | 23.19 |
| June | 135.33 | 23.57 | 246.83 | 23.85 | 0.00 | 23.85 |
| July | 45.00 | 23.99 | 646.83 | 24.00 | 45.00 | 24.00 |
| August | 35.17 | 23.96 | 595.83 | 24.00 | 33.00 | 23.99 |
| September | 176.33 | 23.58 | 270.50 | 23.83 | 13.33 | 23.83 |
| October | 598.33 | 22.37 | 156.67 | 22.26 | 116.83 | 22.10 |
| November | 720.00 | 21.31 | 428.17 | 21.23 | 428.17 | 21.20 |
| December | 744.00 | 21.10 | 726.67 | 21.10 | 726.67 | 21.10 |
| Annual Sum or Average | 5715.33 | 21.91 | 4591.33 | 22.07 | 2834.50 | 21.88 |
| Minimum of Months | 35.17 | 21.10 | 61.83 | 21.10 | 0.00 | 21.10 |
| Maximum of Months | 744.00 | 23.99 | 726.67 | 24.00 | 726.67 | 24.00 |
Report: ComfortReportSimple55Monthly
For: T N2 APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 744.00 | 21.13 | 680.00 | 21.12 | 680.00 | 21.11 |
| February | 672.00 | 21.30 | 465.33 | 21.22 | 465.33 | 21.19 |
| March | 744.00 | 21.73 | 241.00 | 21.58 | 241.00 | 21.49 |
| April | 661.33 | 22.82 | 70.67 | 22.66 | 70.67 | 22.52 |
| May | 435.33 | 23.23 | 63.83 | 23.26 | 12.83 | 23.20 |
| June | 134.33 | 23.57 | 248.83 | 23.85 | 0.00 | 23.85 |
| July | 45.00 | 23.99 | 646.67 | 24.00 | 45.00 | 24.00 |
| August | 35.17 | 23.96 | 595.67 | 24.00 | 33.00 | 23.99 |
| September | 176.33 | 23.58 | 270.67 | 23.83 | 13.33 | 23.83 |
| October | 598.83 | 22.38 | 156.67 | 22.27 | 116.83 | 22.11 |
| November | 720.00 | 21.31 | 429.33 | 21.23 | 429.33 | 21.20 |
| December | 744.00 | 21.10 | 726.50 | 21.10 | 726.50 | 21.10 |
| Annual Sum or Average | 5710.33 | 21.91 | 4595.17 | 22.07 | 2833.83 | 21.88 |
| Minimum of Months | 35.17 | 21.10 | 63.83 | 21.10 | 0.00 | 21.10 |
| Maximum of Months | 744.00 | 23.99 | 726.50 | 24.00 | 726.50 | 24.00 |
Report: ComfortReportSimple55Monthly
For: T S1 APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 505.17 | 21.56 | 300.00 | 21.39 | 300.00 | 21.31 |
| February | 448.33 | 21.75 | 197.83 | 21.55 | 197.83 | 21.45 |
| March | 479.50 | 22.04 | 108.33 | 21.86 | 108.33 | 21.74 |
| April | 444.00 | 22.91 | 34.17 | 22.78 | 34.17 | 22.67 |
| May | 334.17 | 23.26 | 47.50 | 23.28 | 9.67 | 23.23 |
| June | 136.17 | 23.57 | 108.00 | 23.76 | 0.00 | 23.76 |
| July | 42.00 | 23.99 | 432.50 | 24.00 | 42.00 | 24.00 |
| August | 27.00 | 23.98 | 370.33 | 24.00 | 26.50 | 24.00 |
| September | 110.17 | 23.66 | 204.50 | 23.88 | 7.50 | 23.87 |
| October | 340.17 | 22.70 | 83.83 | 22.67 | 41.17 | 22.53 |
| November | 477.00 | 21.97 | 139.33 | 21.78 | 139.33 | 21.65 |
| December | 511.33 | 21.60 | 313.17 | 21.41 | 313.17 | 21.32 |
| Annual Sum or Average | 3855.00 | 22.28 | 2339.50 | 22.39 | 1219.67 | 22.21 |
| Minimum of Months | 27.00 | 21.56 | 34.17 | 21.39 | 0.00 | 21.31 |
| Maximum of Months | 511.33 | 23.99 | 432.50 | 24.00 | 313.17 | 24.00 |
Report: ComfortReportSimple55Monthly
For: T S2 APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 504.83 | 21.56 | 301.00 | 21.39 | 301.00 | 21.31 |
| February | 448.33 | 21.75 | 199.17 | 21.55 | 199.17 | 21.44 |
| March | 479.33 | 22.03 | 108.17 | 21.86 | 108.17 | 21.74 |
| April | 442.17 | 22.91 | 33.17 | 22.78 | 33.17 | 22.67 |
| May | 334.67 | 23.27 | 47.83 | 23.29 | 9.17 | 23.24 |
| June | 135.83 | 23.57 | 108.33 | 23.76 | 0.00 | 23.76 |
| July | 41.83 | 23.99 | 432.00 | 24.00 | 41.83 | 24.00 |
| August | 27.00 | 23.98 | 370.33 | 24.00 | 26.50 | 24.00 |
| September | 111.17 | 23.66 | 204.17 | 23.87 | 7.50 | 23.87 |
| October | 339.33 | 22.69 | 83.83 | 22.67 | 41.33 | 22.53 |
| November | 476.67 | 21.97 | 140.33 | 21.77 | 140.33 | 21.65 |
| December | 510.67 | 21.59 | 314.50 | 21.41 | 314.50 | 21.32 |
| Annual Sum or Average | 3851.83 | 22.27 | 2342.83 | 22.39 | 1222.67 | 22.21 |
| Minimum of Months | 27.00 | 21.56 | 33.17 | 21.39 | 0.00 | 21.31 |
| Maximum of Months | 510.67 | 23.99 | 432.00 | 24.00 | 314.50 | 24.00 |
Report: ComfortReportSimple55Monthly
For: T CORRIDOR
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 744.00 | 21.13 | 559.83 | 21.10 | 559.83 | 21.09 |
| February | 662.50 | 21.57 | 382.67 | 21.59 | 380.33 | 21.60 |
| March | 690.50 | 22.35 | 449.17 | 22.51 | 416.83 | 22.53 |
| April | 625.17 | 24.02 | 597.83 | 24.22 | 519.00 | 24.26 |
| May | 721.67 | 25.00 | 670.00 | 25.10 | 659.83 | 25.14 |
| June | 720.00 | 25.98 | 720.00 | 25.98 | 720.00 | 25.98 |
| July | 744.00 | 26.41 | 744.00 | 26.41 | 744.00 | 26.41 |
| August | 744.00 | 26.28 | 744.00 | 26.28 | 744.00 | 26.28 |
| September | 720.00 | 25.67 | 720.00 | 25.67 | 720.00 | 25.67 |
| October | 738.83 | 23.93 | 713.00 | 23.96 | 713.00 | 23.97 |
| November | 720.00 | 22.07 | 552.17 | 22.12 | 552.17 | 22.13 |
| December | 744.00 | 21.07 | 452.50 | 21.03 | 452.50 | 21.01 |
| Annual Sum or Average | 8574.67 | 23.81 | 7305.17 | 24.00 | 7181.50 | 24.07 |
| Minimum of Months | 625.17 | 21.07 | 382.67 | 21.03 | 380.33 | 21.01 |
| Maximum of Months | 744.00 | 26.41 | 744.00 | 26.41 | 744.00 | 26.41 |
Report: ComfortReportSimple55Monthly
For: G CORRIDOR
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 744.00 | 19.43 | 542.33 | 19.11 | 542.33 | 18.98 |
| February | 672.00 | 19.76 | 440.83 | 19.39 | 440.83 | 19.23 |
| March | 744.00 | 20.95 | 218.33 | 20.51 | 218.33 | 20.23 |
| April | 585.00 | 22.64 | 70.33 | 22.54 | 35.50 | 22.31 |
| May | 255.00 | 23.20 | 398.00 | 24.61 | 50.33 | 24.60 |
| June | 177.67 | 26.41 | 675.83 | 26.49 | 160.00 | 26.56 |
| July | 531.67 | 27.03 | 744.00 | 26.99 | 531.67 | 27.00 |
| August | 415.83 | 26.82 | 739.67 | 26.75 | 414.17 | 26.77 |
| September | 195.33 | 25.58 | 690.33 | 25.99 | 175.33 | 26.00 |
| October | 357.50 | 22.79 | 331.67 | 23.97 | 74.67 | 23.92 |
| November | 704.67 | 21.47 | 106.83 | 21.05 | 104.67 | 20.72 |
| December | 744.00 | 19.50 | 548.17 | 19.19 | 548.17 | 19.06 |
| Annual Sum or Average | 6126.67 | 22.11 | 5506.33 | 22.87 | 3296.00 | 22.70 |
| Minimum of Months | 177.67 | 19.43 | 70.33 | 19.11 | 35.50 | 18.98 |
| Maximum of Months | 744.00 | 27.03 | 744.00 | 26.99 | 548.17 | 27.00 |
Report: ComfortReportSimple55Monthly
For: M CORRIDOR
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 744.00 | 22.89 | 698.17 | 22.92 | 698.17 | 22.93 |
| February | 672.00 | 23.19 | 649.67 | 23.20 | 649.67 | 23.20 |
| March | 734.00 | 24.07 | 737.50 | 24.07 | 734.00 | 24.07 |
| April | 720.00 | 25.41 | 720.00 | 25.41 | 720.00 | 25.41 |
| May | 736.83 | 25.75 | 744.00 | 25.74 | 736.83 | 25.74 |
| June | 720.00 | 26.10 | 720.00 | 26.10 | 720.00 | 26.10 |
| July | 744.00 | 26.24 | 744.00 | 26.24 | 744.00 | 26.24 |
| August | 744.00 | 26.19 | 744.00 | 26.19 | 744.00 | 26.19 |
| September | 720.00 | 25.99 | 720.00 | 25.99 | 720.00 | 25.99 |
| October | 744.00 | 25.23 | 744.00 | 25.23 | 744.00 | 25.23 |
| November | 719.33 | 23.87 | 715.00 | 23.87 | 715.00 | 23.87 |
| December | 744.00 | 22.86 | 732.50 | 22.86 | 732.50 | 22.86 |
| Annual Sum or Average | 8742.17 | 24.82 | 8668.83 | 24.84 | 8658.17 | 24.84 |
| Minimum of Months | 672.00 | 22.86 | 649.67 | 22.86 | 649.67 | 22.86 |
| Maximum of Months | 744.00 | 26.24 | 744.00 | 26.24 | 744.00 | 26.24 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_GSW
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 515.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 492.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 524.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 6145.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_GNW
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 8760.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_OFFICE
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 140.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 133.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 161.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 140.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 154.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 154.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 140.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 161.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 140.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 147.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 140.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 140.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 1750.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 133.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 161.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_GNE
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 8760.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_GN1
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 8760.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_GN2
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 8760.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_GS1
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 515.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 492.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 524.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 6145.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_GS2
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 515.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 492.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 524.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 6145.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_MSW
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 515.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 492.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 524.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 6145.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_MNW
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 8760.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_MSE
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 515.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 492.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 524.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 6145.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_MNE
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 8760.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_MN1
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 8760.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_MN2
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 8760.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_MS1
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 515.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 492.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 524.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 6145.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_MS2
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 515.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 492.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 524.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 6145.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_TSW
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 515.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 492.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 524.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 6145.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_TNW
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 8760.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_TSE
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 515.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 492.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 524.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 6145.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_TNE
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 8760.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_TN1
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 8760.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_TN2
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 8760.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_TS1
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 515.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 492.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 524.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 6145.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_TS2
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 515.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 492.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 524.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 6145.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_T CORRIDOR
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 8760.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_G CORRIDOR
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 8760.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_M CORRIDOR
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 8760.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: DXReportMonthly
For: SPLIT GSW COOLING COIL
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 23256309.86 | 6217462.13 | 20.00 | 23256309.86 | 0.00 | 0.00 | 0.12 | 02-JAN-15:30 | 0.00 | 01-JAN-00:10 | 644.38 | 02-JAN-15:30 | 644.38 | 02-JAN-15:30 | 0.00 | 02-JAN-16:00 | 171.23 | 02-JAN-15:30 | 0.00 | 01-JAN-00:10 |
| February | 36962247.48 | 9852443.06 | 28.81 | 36962247.48 | 0.00 | 0.00 | 0.17 | 14-FEB-16:10 | 0.00 | 01-FEB-00:10 | 927.49 | 14-FEB-16:10 | 927.49 | 14-FEB-16:10 | 0.00 | 14-FEB-16:10 | 244.58 | 14-FEB-16:10 | 0.00 | 01-FEB-00:10 |
| March | 40626917.80 | 10867841.47 | 37.50 | 40626917.80 | -0.0 | 0.00 | 0.13 | 12-MAR-16:30 | 0.00 | 01-MAR-00:10 | 692.61 | 12-MAR-16:30 | 692.61 | 12-MAR-16:30 | 0.00 | 08-MAR-17:05 | 183.80 | 12-MAR-16:30 | 0.00 | 01-MAR-00:10 |
| April | 0.417879E+09 | 0.111104E+09 | 224.56 | 0.417879E+09 | -0.0 | 0.00 | 0.26 | 13-APR-16:30 | 0.00 | 01-APR-00:10 | 1462.91 | 13-APR-16:30 | 1462.91 | 13-APR-16:30 | 0.00 | 13-APR-17:00 | 390.60 | 13-APR-16:30 | 0.00 | 01-APR-00:10 |
| May | 0.103982E+10 | 0.278279E+09 | 425.77 | 0.103552E+10 | 4302460.67 | 0.00 | 0.36 | 19-MAY-16:40 | 0.00 | 01-MAY-00:10 | 1964.12 | 19-MAY-16:40 | 1964.12 | 19-MAY-16:40 | 58.57 | 28-MAY-11:40 | 548.14 | 19-MAY-16:40 | 0.00 | 01-MAY-00:10 |
| June | 0.243497E+10 | 0.672683E+09 | 646.66 | 0.239918E+10 | 35787820.76 | 0.00 | 0.54 | 28-JUN-16:30 | 0.00 | 01-JUN-02:50 | 2744.65 | 28-JUN-16:30 | 2744.65 | 28-JUN-16:30 | 210.15 | 24-JUN-10:00 | 843.44 | 28-JUN-16:30 | 0.00 | 01-JUN-00:10 |
| July | 0.377509E+10 | 0.102098E+10 | 744.00 | 0.345980E+10 | 0.315289E+09 | 0.00 | 0.56 | 21-JUL-17:10 | 0.03 | 02-JUL-05:10 | 2943.24 | 21-JUL-17:05 | 2943.24 | 21-JUL-17:05 | 453.21 | 01-JUL-14:00 | 888.57 | 21-JUL-17:00 | 0.00 | 01-JUL-00:10 |
| August | 0.380211E+10 | 0.100966E+10 | 744.00 | 0.351637E+10 | 0.285735E+09 | 0.00 | 0.53 | 20-AUG-17:10 | 0.02 | 29-AUG-06:00 | 2953.06 | 20-AUG-17:05 | 2953.06 | 20-AUG-17:05 | 427.45 | 26-AUG-10:50 | 850.22 | 20-AUG-17:05 | 0.00 | 01-AUG-00:10 |
| September | 0.315312E+10 | 0.821970E+09 | 718.83 | 0.301190E+10 | 0.141213E+09 | 0.00 | 0.51 | 20-SEP-16:30 | 0.00 | 08-SEP-09:00 | 2883.23 | 20-SEP-16:30 | 2883.23 | 20-SEP-16:30 | 403.04 | 05-SEP-13:00 | 786.83 | 20-SEP-16:30 | 0.00 | 01-SEP-00:10 |
| October | 0.192447E+10 | 0.500698E+09 | 560.58 | 0.189447E+10 | 30003042.99 | 0.00 | 0.46 | 06-OCT-16:10 | 0.00 | 08-OCT-01:30 | 2640.34 | 06-OCT-16:05 | 2640.34 | 06-OCT-16:05 | 297.16 | 11-OCT-11:00 | 698.31 | 06-OCT-16:05 | 0.00 | 01-OCT-00:10 |
| November | 0.372502E+09 | 98658564.71 | 220.61 | 0.372502E+09 | -0.0 | 0.00 | 0.24 | 01-NOV-15:10 | 0.00 | 01-NOV-04:40 | 1372.22 | 01-NOV-15:10 | 1372.22 | 01-NOV-15:10 | 0.00 | 02-NOV-16:03 | 356.24 | 01-NOV-15:10 | 0.00 | 01-NOV-00:10 |
| December | 14522908.03 | 3892665.38 | 17.85 | 14522908.03 | 0.00 | 0.00 | 0.10 | 31-DEC-15:30 | 0.00 | 01-DEC-00:10 | 542.59 | 31-DEC-15:30 | 542.59 | 31-DEC-15:30 | 0.00 | 02-DEC-15:50 | 144.58 | 31-DEC-15:30 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.170353E+11 | 0.454486E+10 | 4389.16 | 0.162230E+11 | 0.812330E+09 | 0.00 | ||||||||||||||
| Minimum of Months | 14522908.03 | 3892665.38 | 17.85 | 14522908.03 | -0.0 | 0.00 | 0.10 | 0.00 | 542.59 | 542.59 | 0.00 | 144.58 | 0.00 | |||||||
| Maximum of Months | 0.380211E+10 | 0.102098E+10 | 744.00 | 0.351637E+10 | 0.315289E+09 | 0.00 | 0.56 | 0.03 | 2953.06 | 2953.06 | 453.21 | 888.57 | 0.00 |
Report: DXReportMonthly
For: SPLIT GNW COOLING COIL
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
| April | 0.146817E+09 | 39374868.49 | 105.86 | 0.146817E+09 | 0.00 | 0.00 | 0.19 | 29-APR-17:10 | 0.00 | 01-APR-00:10 | 1016.17 | 29-APR-17:30 | 1016.17 | 29-APR-17:30 | 0.00 | 26-APR-16:30 | 270.48 | 29-APR-17:10 | 0.00 | 01-APR-00:10 |
| May | 0.837322E+09 | 0.224910E+09 | 391.04 | 0.833811E+09 | 3510591.78 | 0.00 | 0.34 | 19-MAY-17:05 | 0.00 | 01-MAY-00:10 | 1833.49 | 19-MAY-17:05 | 1833.49 | 19-MAY-17:05 | 56.61 | 23-MAY-16:20 | 512.26 | 19-MAY-17:05 | 0.00 | 01-MAY-00:10 |
| June | 0.246335E+10 | 0.679066E+09 | 646.75 | 0.242828E+10 | 35069260.72 | 0.00 | 0.55 | 28-JUN-16:40 | 0.00 | 01-JUN-02:40 | 2738.00 | 28-JUN-16:50 | 2738.00 | 28-JUN-16:50 | 189.81 | 24-JUN-08:50 | 838.15 | 28-JUN-16:30 | 0.00 | 01-JUN-00:10 |
| July | 0.362139E+10 | 0.979388E+09 | 744.00 | 0.331189E+10 | 0.309501E+09 | 0.00 | 0.55 | 21-JUL-17:10 | 0.02 | 08-JUL-05:05 | 2854.17 | 21-JUL-17:14 | 2854.17 | 21-JUL-17:14 | 423.62 | 01-JUL-14:00 | 859.95 | 21-JUL-17:10 | 0.00 | 01-JUL-00:10 |
| August | 0.330582E+10 | 0.881404E+09 | 744.00 | 0.304167E+10 | 0.264148E+09 | 0.00 | 0.48 | 20-AUG-17:30 | 0.01 | 28-AUG-06:00 | 2620.98 | 20-AUG-17:30 | 2620.98 | 20-AUG-17:30 | 396.11 | 23-AUG-16:25 | 760.72 | 20-AUG-17:30 | 0.00 | 01-AUG-00:10 |
| September | 0.213819E+10 | 0.563333E+09 | 714.43 | 0.202694E+10 | 0.111248E+09 | 0.00 | 0.39 | 02-SEP-17:00 | 0.00 | 08-SEP-09:00 | 2180.12 | 02-SEP-17:10 | 2180.12 | 02-SEP-17:10 | 332.77 | 05-SEP-13:00 | 608.43 | 02-SEP-17:00 | 0.00 | 01-SEP-00:10 |
| October | 0.731773E+09 | 0.192759E+09 | 341.92 | 0.711512E+09 | 20261595.67 | 0.00 | 0.32 | 06-OCT-16:20 | 0.00 | 03-OCT-05:03 | 1758.22 | 06-OCT-16:17 | 1758.22 | 06-OCT-16:17 | 191.46 | 11-OCT-11:00 | 477.05 | 01-OCT-16:10 | 0.00 | 01-OCT-00:10 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.132447E+11 | 0.356023E+10 | 3688.00 | 0.125009E+11 | 0.743738E+09 | 0.00 | ||||||||||||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Maximum of Months | 0.362139E+10 | 0.979388E+09 | 744.00 | 0.331189E+10 | 0.309501E+09 | 0.00 | 0.55 | 0.02 | 2854.17 | 2854.17 | 423.62 | 859.95 | 0.00 |
Report: DXReportMonthly
For: SPLIT OFFICE COOLING COIL
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.108453E+09 | 28860571.00 | 63.75 | 0.108453E+09 | 0.00 | 0.00 | 0.20 | 03-JAN-14:00 | 0.00 | 01-JAN-00:10 | 1270.93 | 03-JAN-14:00 | 1270.93 | 03-JAN-14:00 | 0.00 | 05-JAN-10:30 | 333.39 | 03-JAN-14:00 | 0.00 | 01-JAN-00:10 |
| February | 0.122849E+09 | 32389173.15 | 44.92 | 0.122849E+09 | -0.0 | 0.00 | 0.25 | 14-FEB-15:30 | 0.00 | 01-FEB-00:10 | 1618.82 | 14-FEB-15:30 | 1618.82 | 14-FEB-15:30 | 0.00 | 17-FEB-13:30 | 421.17 | 14-FEB-15:30 | 0.00 | 01-FEB-00:10 |
| March | 0.287375E+09 | 76026710.85 | 116.33 | 0.287375E+09 | -0.0 | 0.00 | 0.25 | 13-MAR-14:30 | 0.00 | 01-MAR-00:10 | 1601.43 | 13-MAR-14:30 | 1601.43 | 13-MAR-14:30 | 0.00 | 27-MAR-12:40 | 416.82 | 13-MAR-14:30 | 0.00 | 01-MAR-00:10 |
| April | 0.804133E+09 | 0.209446E+09 | 166.96 | 0.804133E+09 | 0.00 | 0.00 | 0.92 | 28-APR-08:62 | 0.00 | 01-APR-00:10 | 6559.74 | 28-APR-08:62 | 6559.74 | 28-APR-08:62 | 0.00 | 11-APR-11:30 | 1528.89 | 28-APR-08:62 | 0.00 | 01-APR-00:10 |
| May | 0.133676E+10 | 0.345322E+09 | 198.19 | 0.132133E+10 | 15424319.13 | 0.00 | 1.00 | 15-MAY-07:02 | 0.00 | 01-MAY-00:10 | 7702.66 | 22-MAY-07:02 | 7702.66 | 22-MAY-07:02 | 689.26 | 24-MAY-08:62 | 1718.51 | 22-MAY-07:02 | 0.00 | 01-MAY-00:10 |
| June | 0.233864E+10 | 0.628510E+09 | 271.13 | 0.230291E+10 | 35734558.72 | 0.00 | 1.00 | 07-JUN-07:02 | 0.00 | 01-JUN-00:10 | 7793.87 | 05-JUN-08:62 | 7787.33 | 30-JUN-07:02 | 1153.09 | 05-JUN-08:62 | 1837.85 | 29-JUN-08:62 | 0.00 | 01-JUN-00:10 |
| July | 0.297753E+10 | 0.788067E+09 | 362.77 | 0.280976E+10 | 0.167769E+09 | 0.00 | 1.00 | 03-JUL-07:02 | 0.00 | 01-JUL-00:10 | 8155.97 | 17-JUL-07:02 | 7780.49 | 03-JUL-07:02 | 1634.82 | 17-JUL-08:62 | 1793.71 | 21-JUL-08:62 | 0.00 | 01-JUL-00:10 |
| August | 0.327584E+10 | 0.842458E+09 | 361.27 | 0.306967E+10 | 0.206162E+09 | 0.00 | 1.00 | 01-AUG-07:02 | 0.00 | 01-AUG-00:10 | 8230.87 | 14-AUG-07:02 | 7783.61 | 18-AUG-07:02 | 1812.43 | 14-AUG-07:02 | 1767.90 | 17-AUG-08:62 | 0.00 | 01-AUG-00:10 |
| September | 0.253521E+10 | 0.638293E+09 | 267.46 | 0.244665E+10 | 88564372.79 | 0.00 | 1.00 | 01-SEP-07:02 | 0.00 | 01-SEP-00:10 | 8118.26 | 06-SEP-07:02 | 7691.02 | 15-SEP-07:02 | 1731.99 | 06-SEP-08:62 | 1746.71 | 06-SEP-07:02 | 0.00 | 01-SEP-00:10 |
| October | 0.177243E+10 | 0.445434E+09 | 204.61 | 0.174349E+10 | 28939988.05 | 0.00 | 1.00 | 02-OCT-07:02 | 0.00 | 01-OCT-00:10 | 7930.89 | 11-OCT-07:02 | 7705.47 | 10-OCT-07:01 | 1153.80 | 11-OCT-08:62 | 1736.91 | 11-OCT-07:02 | 0.00 | 01-OCT-00:10 |
| November | 0.717153E+09 | 0.186940E+09 | 159.92 | 0.717153E+09 | 0.00 | 0.00 | 0.90 | 01-NOV-08:62 | 0.00 | 01-NOV-00:10 | 6469.37 | 01-NOV-08:62 | 6469.37 | 01-NOV-08:62 | 0.00 | 09-NOV-10:50 | 1505.52 | 01-NOV-08:62 | 0.00 | 01-NOV-00:10 |
| December | 77381728.15 | 20666418.51 | 57.00 | 77381728.15 | -0.0 | 0.00 | 0.14 | 01-DEC-15:30 | 0.00 | 01-DEC-00:10 | 872.44 | 01-DEC-15:30 | 872.44 | 01-DEC-15:30 | 0.00 | 01-DEC-15:20 | 231.04 | 01-DEC-15:30 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.163538E+11 | 0.424241E+10 | 2274.31 | 0.158112E+11 | 0.542594E+09 | 0.00 | ||||||||||||||
| Minimum of Months | 77381728.15 | 20666418.51 | 44.92 | 77381728.15 | -0.0 | 0.00 | 0.14 | 0.00 | 872.44 | 872.44 | 0.00 | 231.04 | 0.00 | |||||||
| Maximum of Months | 0.327584E+10 | 0.842458E+09 | 362.77 | 0.306967E+10 | 0.206162E+09 | 0.00 | 1.00 | 0.00 | 8230.87 | 7787.33 | 1812.43 | 1837.85 | 0.00 |
Report: DXReportMonthly
For: SPLIT GNE COOLING COIL
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
| April | 0.180144E+09 | 48214525.28 | 133.72 | 0.180144E+09 | -0.0 | 0.00 | 0.20 | 29-APR-16:10 | 0.00 | 01-APR-00:10 | 997.59 | 29-APR-16:10 | 997.59 | 29-APR-16:10 | 0.00 | 28-APR-14:10 | 267.58 | 29-APR-16:10 | 0.00 | 01-APR-00:10 |
| May | 0.942676E+09 | 0.251903E+09 | 440.59 | 0.934966E+09 | 7709738.24 | 0.00 | 0.31 | 19-MAY-17:05 | 0.00 | 01-MAY-00:10 | 1505.14 | 19-MAY-17:20 | 1505.14 | 19-MAY-17:20 | 88.37 | 29-MAY-07:45 | 422.56 | 19-MAY-17:05 | 0.00 | 01-MAY-00:10 |
| June | 0.261039E+10 | 0.714420E+09 | 665.23 | 0.257036E+10 | 40027682.42 | 0.00 | 0.51 | 28-JUN-16:30 | 0.00 | 01-JUN-02:30 | 2379.98 | 29-JUN-15:10 | 2379.98 | 29-JUN-15:10 | 239.12 | 24-JUN-08:50 | 722.60 | 29-JUN-15:10 | 0.00 | 01-JUN-00:10 |
| July | 0.382804E+10 | 0.102710E+10 | 744.00 | 0.349867E+10 | 0.329362E+09 | 0.00 | 0.51 | 21-JUL-17:00 | 0.04 | 08-JUL-05:05 | 2383.92 | 04-JUL-17:00 | 2383.92 | 04-JUL-17:00 | 427.72 | 01-JUL-14:10 | 724.76 | 21-JUL-17:00 | 0.00 | 01-JUL-00:10 |
| August | 0.345952E+10 | 0.916243E+09 | 743.83 | 0.317965E+10 | 0.279861E+09 | 0.00 | 0.45 | 20-AUG-17:10 | 0.00 | 29-AUG-05:40 | 2217.84 | 20-AUG-17:10 | 2217.84 | 20-AUG-17:10 | 405.23 | 26-AUG-10:40 | 647.13 | 20-AUG-17:10 | 0.00 | 01-AUG-00:10 |
| September | 0.219634E+10 | 0.576479E+09 | 710.57 | 0.208062E+10 | 0.115723E+09 | 0.00 | 0.38 | 03-SEP-14:10 | 0.00 | 08-SEP-09:00 | 1923.20 | 03-SEP-14:10 | 1904.88 | 03-SEP-14:10 | 326.13 | 05-SEP-13:00 | 549.09 | 03-SEP-14:00 | 0.00 | 01-SEP-00:10 |
| October | 0.732531E+09 | 0.192574E+09 | 363.29 | 0.710396E+09 | 22134964.81 | 0.00 | 0.31 | 01-OCT-16:10 | 0.00 | 03-OCT-05:03 | 1540.98 | 01-OCT-16:10 | 1540.98 | 01-OCT-16:10 | 218.98 | 11-OCT-11:00 | 420.90 | 01-OCT-16:10 | 0.00 | 01-OCT-00:10 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.139496E+11 | 0.372693E+10 | 3801.23 | 0.131548E+11 | 0.794818E+09 | 0.00 | ||||||||||||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | -0.0 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Maximum of Months | 0.382804E+10 | 0.102710E+10 | 744.00 | 0.349867E+10 | 0.329362E+09 | 0.00 | 0.51 | 0.04 | 2383.92 | 2383.92 | 427.72 | 724.76 | 0.00 |
Report: DXReportMonthly
For: SPLIT GN1 COOLING COIL
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
| April | 98752837.40 | 26530038.51 | 100.50 | 98752837.40 | 0.00 | 0.00 | 0.17 | 29-APR-16:10 | 0.00 | 01-APR-00:10 | 727.11 | 29-APR-16:10 | 727.11 | 29-APR-16:10 | 0.00 | 27-APR-15:50 | 196.11 | 29-APR-16:10 | 0.00 | 01-APR-00:10 |
| May | 0.730986E+09 | 0.195995E+09 | 448.52 | 0.724528E+09 | 6457302.47 | 0.00 | 0.29 | 19-MAY-17:50 | 0.00 | 01-MAY-00:10 | 1243.52 | 19-MAY-17:50 | 1243.52 | 19-MAY-17:50 | 69.45 | 23-MAY-17:10 | 348.99 | 19-MAY-17:30 | 0.00 | 01-MAY-00:10 |
| June | 0.205603E+10 | 0.565185E+09 | 680.02 | 0.201908E+10 | 36950210.50 | 0.00 | 0.47 | 28-JUN-17:00 | 0.00 | 01-JUN-06:35 | 1912.35 | 28-JUN-17:05 | 1912.35 | 28-JUN-17:05 | 170.90 | 24-JUN-08:50 | 586.04 | 28-JUN-16:50 | 0.00 | 01-JUN-00:10 |
| July | 0.305224E+10 | 0.821574E+09 | 744.00 | 0.276330E+10 | 0.288941E+09 | 0.00 | 0.46 | 21-JUL-17:10 | 0.05 | 08-JUL-05:05 | 1923.21 | 21-JUL-17:14 | 1923.21 | 21-JUL-17:14 | 375.51 | 01-JUL-14:10 | 588.88 | 21-JUL-17:05 | 0.00 | 01-JUL-00:10 |
| August | 0.272922E+10 | 0.725670E+09 | 744.00 | 0.248741E+10 | 0.241812E+09 | 0.00 | 0.41 | 20-AUG-17:30 | 0.02 | 29-AUG-06:00 | 1777.32 | 20-AUG-17:17 | 1777.32 | 20-AUG-17:17 | 308.67 | 26-AUG-11:30 | 522.11 | 20-AUG-17:30 | 0.00 | 01-AUG-00:10 |
| September | 0.176113E+10 | 0.463555E+09 | 718.75 | 0.165741E+10 | 0.103716E+09 | 0.00 | 0.32 | 03-SEP-14:10 | 0.00 | 08-SEP-09:00 | 1451.14 | 04-SEP-16:10 | 1432.59 | 02-SEP-17:07 | 284.07 | 05-SEP-13:00 | 413.68 | 03-SEP-14:10 | 0.00 | 01-SEP-00:10 |
| October | 0.576977E+09 | 0.152035E+09 | 358.20 | 0.557747E+09 | 19229573.09 | 0.00 | 0.28 | 01-OCT-16:10 | 0.00 | 03-OCT-05:03 | 1247.47 | 01-OCT-16:10 | 1247.47 | 01-OCT-16:10 | 171.51 | 11-OCT-11:00 | 342.15 | 01-OCT-16:10 | 0.00 | 01-OCT-00:10 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.110053E+11 | 0.295054E+10 | 3793.99 | 0.103082E+11 | 0.697106E+09 | 0.00 | ||||||||||||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Maximum of Months | 0.305224E+10 | 0.821574E+09 | 744.00 | 0.276330E+10 | 0.288941E+09 | 0.00 | 0.47 | 0.05 | 1923.21 | 1923.21 | 375.51 | 588.88 | 0.00 |
Report: DXReportMonthly
For: SPLIT GN2 COOLING COIL
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
| April | 0.104344E+09 | 28021670.07 | 105.17 | 0.104344E+09 | 0.00 | 0.00 | 0.17 | 29-APR-16:10 | 0.00 | 01-APR-00:10 | 743.81 | 29-APR-16:10 | 743.81 | 29-APR-16:10 | 0.00 | 29-APR-17:20 | 200.49 | 29-APR-16:10 | 0.00 | 01-APR-00:10 |
| May | 0.741731E+09 | 0.198806E+09 | 454.49 | 0.734924E+09 | 6806985.73 | 0.00 | 0.29 | 19-MAY-17:30 | 0.00 | 01-MAY-00:10 | 1239.90 | 19-MAY-17:50 | 1239.90 | 19-MAY-17:50 | 70.36 | 23-MAY-17:10 | 348.16 | 19-MAY-17:30 | 0.00 | 01-MAY-00:10 |
| June | 0.206448E+10 | 0.567367E+09 | 681.06 | 0.202730E+10 | 37182269.33 | 0.00 | 0.47 | 28-JUN-17:00 | 0.00 | 01-JUN-06:35 | 1907.01 | 28-JUN-17:10 | 1907.01 | 28-JUN-17:10 | 172.14 | 24-JUN-08:50 | 584.48 | 28-JUN-17:00 | 0.00 | 01-JUN-00:10 |
| July | 0.306216E+10 | 0.824050E+09 | 744.00 | 0.277237E+10 | 0.289794E+09 | 0.00 | 0.46 | 21-JUL-17:10 | 0.05 | 08-JUL-05:10 | 1917.22 | 21-JUL-17:14 | 1917.22 | 21-JUL-17:14 | 376.47 | 01-JUL-14:10 | 587.12 | 21-JUL-17:10 | 0.00 | 01-JUL-00:10 |
| August | 0.273635E+10 | 0.727437E+09 | 744.00 | 0.249398E+10 | 0.242369E+09 | 0.00 | 0.41 | 20-AUG-17:20 | 0.02 | 29-AUG-06:00 | 1773.49 | 20-AUG-17:17 | 1773.49 | 20-AUG-17:17 | 310.72 | 26-AUG-11:30 | 520.99 | 20-AUG-17:17 | 0.00 | 01-AUG-00:10 |
| September | 0.176424E+10 | 0.464327E+09 | 718.71 | 0.166038E+10 | 0.103860E+09 | 0.00 | 0.32 | 03-SEP-14:10 | 0.00 | 08-SEP-09:00 | 1448.18 | 04-SEP-16:10 | 1427.31 | 02-SEP-17:10 | 284.74 | 05-SEP-13:00 | 414.40 | 03-SEP-14:10 | 0.00 | 01-SEP-00:10 |
| October | 0.578564E+09 | 0.152441E+09 | 358.92 | 0.559264E+09 | 19300396.63 | 0.00 | 0.28 | 01-OCT-16:10 | 0.00 | 03-OCT-05:03 | 1245.45 | 01-OCT-16:10 | 1245.45 | 01-OCT-16:10 | 172.24 | 11-OCT-11:00 | 341.59 | 01-OCT-16:10 | 0.00 | 01-OCT-00:10 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.110519E+11 | 0.296245E+10 | 3806.34 | 0.103526E+11 | 0.699312E+09 | 0.00 | ||||||||||||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Maximum of Months | 0.306216E+10 | 0.824050E+09 | 744.00 | 0.277237E+10 | 0.289794E+09 | 0.00 | 0.47 | 0.05 | 1917.22 | 1917.22 | 376.47 | 587.12 | 0.00 |
Report: DXReportMonthly
For: SPLIT GS1 COOLING COIL
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 56844506.47 | 15102717.22 | 49.25 | 56844506.47 | -0.0 | 0.00 | 0.18 | 01-JAN-13:50 | 0.00 | 01-JAN-00:10 | 838.25 | 01-JAN-13:50 | 838.25 | 01-JAN-13:50 | 0.00 | 02-JAN-15:10 | 220.51 | 01-JAN-13:50 | 0.00 | 01-JAN-00:10 |
| February | 45902899.31 | 12225271.00 | 43.37 | 45902899.31 | -0.0 | 0.00 | 0.18 | 14-FEB-15:10 | 0.00 | 01-FEB-00:10 | 824.48 | 14-FEB-15:10 | 824.48 | 14-FEB-15:10 | 0.00 | 15-FEB-12:40 | 216.98 | 14-FEB-15:10 | 0.00 | 01-FEB-00:10 |
| March | 49623095.50 | 13276835.11 | 63.90 | 49623095.50 | -0.0 | 0.00 | 0.14 | 13-MAR-14:30 | 0.00 | 01-MAR-00:10 | 644.28 | 13-MAR-14:30 | 644.28 | 13-MAR-14:30 | 0.00 | 13-MAR-14:20 | 170.56 | 13-MAR-14:30 | 0.00 | 01-MAR-00:10 |
| April | 0.395880E+09 | 0.105242E+09 | 269.80 | 0.395880E+09 | 0.00 | 0.00 | 0.24 | 29-APR-16:10 | 0.00 | 01-APR-00:10 | 1120.29 | 29-APR-16:10 | 1120.29 | 29-APR-16:10 | 0.00 | 29-APR-14:50 | 298.50 | 29-APR-16:10 | 0.00 | 01-APR-00:10 |
| May | 0.954260E+09 | 0.254922E+09 | 499.37 | 0.946656E+09 | 7604133.30 | 0.00 | 0.30 | 19-MAY-17:10 | 0.00 | 01-MAY-02:00 | 1352.37 | 19-MAY-16:20 | 1352.37 | 19-MAY-16:20 | 64.96 | 23-MAY-17:10 | 380.64 | 19-MAY-16:20 | 0.00 | 01-MAY-00:10 |
| June | 0.203811E+10 | 0.561627E+09 | 677.69 | 0.200024E+10 | 37872313.31 | 0.00 | 0.46 | 28-JUN-16:10 | 0.00 | 01-JUN-06:35 | 1907.11 | 29-JUN-15:10 | 1907.11 | 29-JUN-15:10 | 188.49 | 24-JUN-10:00 | 594.59 | 28-JUN-16:01 | 0.00 | 01-JUN-00:10 |
| July | 0.322375E+10 | 0.867935E+09 | 744.00 | 0.292723E+10 | 0.296522E+09 | 0.00 | 0.48 | 22-JUL-15:10 | 0.06 | 08-JUL-05:05 | 2099.28 | 22-JUL-15:10 | 2099.28 | 22-JUL-15:10 | 403.45 | 01-JUL-14:10 | 644.29 | 22-JUL-15:10 | 0.00 | 01-JUL-00:10 |
| August | 0.324852E+10 | 0.859873E+09 | 744.00 | 0.298160E+10 | 0.266920E+09 | 0.00 | 0.47 | 20-AUG-16:10 | 0.03 | 29-AUG-06:00 | 2141.49 | 20-AUG-16:07 | 2141.49 | 20-AUG-16:07 | 402.43 | 26-AUG-10:50 | 626.83 | 20-AUG-16:07 | 0.00 | 01-AUG-00:10 |
| September | 0.280680E+10 | 0.729819E+09 | 720.00 | 0.267034E+10 | 0.136455E+09 | 0.00 | 0.47 | 03-SEP-13:40 | 0.00 | 08-SEP-09:00 | 2250.41 | 03-SEP-13:30 | 2204.73 | 21-SEP-14:10 | 364.97 | 05-SEP-13:00 | 628.25 | 03-SEP-13:40 | 0.00 | 01-SEP-00:10 |
| October | 0.186801E+10 | 0.485409E+09 | 618.97 | 0.183834E+10 | 29674380.74 | 0.00 | 0.43 | 01-OCT-15:20 | 0.00 | 12-OCT-22:50 | 2059.13 | 01-OCT-15:20 | 2059.13 | 01-OCT-15:20 | 279.08 | 11-OCT-11:00 | 551.45 | 01-OCT-15:20 | 0.00 | 01-OCT-00:10 |
| November | 0.553703E+09 | 0.146227E+09 | 330.85 | 0.553703E+09 | 0.00 | 0.00 | 0.28 | 01-NOV-13:00 | 0.00 | 02-NOV-05:50 | 1319.47 | 01-NOV-13:00 | 1319.47 | 01-NOV-13:00 | 0.00 | 02-NOV-13:10 | 340.32 | 01-NOV-13:00 | 0.00 | 01-NOV-00:10 |
| December | 41314847.77 | 11045248.38 | 48.61 | 41314847.77 | -0.0 | 0.00 | 0.14 | 31-DEC-15:00 | 0.00 | 01-DEC-00:10 | 644.33 | 31-DEC-15:00 | 644.33 | 31-DEC-15:00 | 0.00 | 30-DEC-13:50 | 170.58 | 31-DEC-15:00 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.152827E+11 | 0.406270E+10 | 4809.82 | 0.145077E+11 | 0.775048E+09 | 0.00 | ||||||||||||||
| Minimum of Months | 41314847.77 | 11045248.38 | 43.37 | 41314847.77 | -0.0 | 0.00 | 0.14 | 0.00 | 644.28 | 644.28 | 0.00 | 170.56 | 0.00 | |||||||
| Maximum of Months | 0.324852E+10 | 0.867935E+09 | 744.00 | 0.298160E+10 | 0.296522E+09 | 0.00 | 0.48 | 0.06 | 2250.41 | 2204.73 | 403.45 | 644.29 | 0.00 |
Report: DXReportMonthly
For: SPLIT GS2 COOLING COIL
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 60091147.23 | 15963624.34 | 50.58 | 60091147.23 | 0.00 | 0.00 | 0.18 | 01-JAN-13:50 | 0.00 | 01-JAN-00:10 | 852.55 | 01-JAN-13:50 | 852.55 | 01-JAN-13:50 | 0.00 | 02-JAN-13:10 | 224.21 | 01-JAN-13:50 | 0.00 | 01-JAN-00:10 |
| February | 48198045.39 | 12832316.57 | 45.26 | 48198045.39 | 0.00 | 0.00 | 0.18 | 14-FEB-15:10 | 0.00 | 01-FEB-00:10 | 846.79 | 14-FEB-15:10 | 846.79 | 14-FEB-15:10 | 0.00 | 14-FEB-15:20 | 222.73 | 14-FEB-15:10 | 0.00 | 01-FEB-00:10 |
| March | 61112247.45 | 16343715.23 | 74.00 | 61112247.45 | -0.0 | 0.00 | 0.15 | 13-MAR-14:30 | 0.00 | 01-MAR-00:10 | 692.54 | 13-MAR-14:30 | 692.54 | 13-MAR-14:30 | 0.00 | 08-MAR-14:10 | 183.08 | 13-MAR-14:30 | 0.00 | 01-MAR-00:10 |
| April | 0.466220E+09 | 0.123776E+09 | 305.63 | 0.466220E+09 | 0.00 | 0.00 | 0.26 | 29-APR-16:10 | 0.00 | 01-APR-00:10 | 1220.97 | 29-APR-16:10 | 1220.97 | 29-APR-16:10 | 0.00 | 13-APR-14:50 | 324.35 | 29-APR-16:10 | 0.00 | 01-APR-00:10 |
| May | 0.110406E+10 | 0.294067E+09 | 541.93 | 0.109344E+10 | 10617725.62 | 0.00 | 0.31 | 19-MAY-17:10 | 0.00 | 01-MAY-03:00 | 1413.95 | 19-MAY-17:10 | 1413.95 | 19-MAY-17:10 | 98.96 | 24-MAY-19:10 | 396.92 | 19-MAY-17:10 | 0.00 | 01-MAY-00:10 |
| June | 0.227794E+10 | 0.624641E+09 | 695.03 | 0.223504E+10 | 42902409.20 | 0.00 | 0.48 | 28-JUN-16:10 | 0.00 | 01-JUN-06:35 | 1998.33 | 29-JUN-15:10 | 1998.33 | 29-JUN-15:10 | 199.72 | 24-JUN-10:00 | 619.80 | 28-JUN-16:04 | 0.00 | 01-JUN-00:10 |
| July | 0.357531E+10 | 0.957968E+09 | 744.00 | 0.325618E+10 | 0.319133E+09 | 0.00 | 0.51 | 22-JUL-15:10 | 0.08 | 08-JUL-05:05 | 2252.44 | 22-JUL-15:10 | 2252.44 | 22-JUL-15:10 | 431.37 | 01-JUL-14:10 | 688.07 | 22-JUL-15:10 | 0.00 | 01-JUL-00:10 |
| August | 0.358117E+10 | 0.944059E+09 | 744.00 | 0.329488E+10 | 0.286283E+09 | 0.00 | 0.50 | 20-AUG-16:10 | 0.05 | 29-AUG-06:00 | 2315.41 | 20-AUG-16:07 | 2315.41 | 20-AUG-16:07 | 421.77 | 26-AUG-10:50 | 674.23 | 20-AUG-16:07 | 0.00 | 01-AUG-00:10 |
| September | 0.309292E+10 | 0.801659E+09 | 720.00 | 0.294463E+10 | 0.148291E+09 | 0.00 | 0.51 | 03-SEP-13:40 | 0.02 | 08-SEP-09:00 | 2427.74 | 03-SEP-13:30 | 2379.46 | 03-SEP-13:40 | 376.84 | 05-SEP-13:00 | 674.45 | 03-SEP-13:40 | 0.00 | 01-SEP-00:10 |
| October | 0.206683E+10 | 0.535984E+09 | 630.82 | 0.203462E+10 | 32203793.53 | 0.00 | 0.46 | 01-OCT-15:20 | 0.00 | 12-OCT-23:10 | 2224.70 | 01-OCT-15:10 | 2224.70 | 01-OCT-15:10 | 290.80 | 11-OCT-11:00 | 592.91 | 01-OCT-15:20 | 0.00 | 01-OCT-00:10 |
| November | 0.602913E+09 | 0.159113E+09 | 346.63 | 0.602913E+09 | -0.0 | 0.00 | 0.29 | 01-NOV-13:00 | 0.00 | 02-NOV-07:01 | 1382.43 | 01-NOV-13:00 | 1382.43 | 01-NOV-13:00 | 0.00 | 01-NOV-10:20 | 355.96 | 01-NOV-13:00 | 0.00 | 01-NOV-00:10 |
| December | 46030460.12 | 12300068.83 | 51.30 | 46030460.12 | -0.0 | 0.00 | 0.14 | 31-DEC-15:00 | 0.00 | 01-DEC-00:10 | 665.92 | 31-DEC-15:00 | 665.92 | 31-DEC-15:00 | 0.00 | 02-DEC-14:20 | 176.19 | 31-DEC-15:00 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.169828E+11 | 0.449871E+10 | 4949.18 | 0.161434E+11 | 0.839431E+09 | 0.00 | ||||||||||||||
| Minimum of Months | 46030460.12 | 12300068.83 | 45.26 | 46030460.12 | -0.0 | 0.00 | 0.14 | 0.00 | 665.92 | 665.92 | 0.00 | 176.19 | 0.00 | |||||||
| Maximum of Months | 0.358117E+10 | 0.957968E+09 | 744.00 | 0.329488E+10 | 0.319133E+09 | 0.00 | 0.51 | 0.08 | 2427.74 | 2379.46 | 431.37 | 688.07 | 0.00 |
Report: DXReportMonthly
For: SPLIT MSW COOLING COIL
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.439766E+09 | 0.116683E+09 | 104.42 | 0.439766E+09 | -0.0 | 0.00 | 0.24 | 02-JAN-15:20 | 0.00 | 01-JAN-00:10 | 3240.55 | 02-JAN-15:20 | 3240.55 | 02-JAN-15:20 | 0.00 | 02-JAN-13:40 | 845.07 | 02-JAN-15:20 | 0.00 | 01-JAN-00:10 |
| February | 0.620788E+09 | 0.163698E+09 | 117.25 | 0.620788E+09 | -0.0 | 0.00 | 0.33 | 14-FEB-16:10 | 0.00 | 01-FEB-00:10 | 4498.68 | 14-FEB-16:10 | 4498.68 | 14-FEB-16:10 | 0.00 | 15-FEB-15:40 | 1157.10 | 14-FEB-16:10 | 0.00 | 01-FEB-00:10 |
| March | 0.100177E+10 | 0.264722E+09 | 207.93 | 0.100177E+10 | 0.00 | 0.00 | 0.30 | 12-MAR-16:03 | 0.00 | 01-MAR-00:10 | 4118.74 | 12-MAR-16:03 | 4118.74 | 12-MAR-16:03 | 0.00 | 08-MAR-15:40 | 1063.77 | 12-MAR-16:03 | 0.00 | 01-MAR-00:10 |
| April | 0.290161E+10 | 0.763749E+09 | 481.63 | 0.290161E+10 | -0.0 | 0.00 | 0.38 | 13-APR-16:27 | 0.00 | 01-APR-00:10 | 5220.09 | 13-APR-16:27 | 5220.09 | 13-APR-16:27 | 0.00 | 11-APR-16:35 | 1368.03 | 13-APR-16:27 | 0.00 | 01-APR-00:10 |
| May | 0.405397E+10 | 0.107424E+10 | 615.71 | 0.402296E+10 | 31014924.41 | 0.00 | 0.42 | 19-MAY-16:30 | 0.00 | 01-MAY-02:40 | 5667.18 | 19-MAY-16:25 | 5667.18 | 19-MAY-16:25 | 221.50 | 23-MAY-16:17 | 1565.08 | 19-MAY-16:25 | 0.00 | 01-MAY-00:10 |
| June | 0.653005E+10 | 0.179406E+10 | 688.94 | 0.642907E+10 | 0.100982E+09 | 0.00 | 0.56 | 28-JUN-16:30 | 0.00 | 01-JUN-06:35 | 6860.97 | 28-JUN-16:30 | 6860.97 | 28-JUN-16:30 | 494.36 | 24-JUN-10:00 | 2102.33 | 28-JUN-16:30 | 0.00 | 01-JUN-00:10 |
| July | 0.882114E+10 | 0.239059E+10 | 744.00 | 0.811323E+10 | 0.707912E+09 | 0.00 | 0.56 | 21-JUL-17:10 | 0.02 | 08-JUL-05:10 | 7049.99 | 21-JUL-17:03 | 7049.99 | 21-JUL-17:03 | 1109.07 | 01-JUL-14:00 | 2129.64 | 21-JUL-17:00 | 0.00 | 01-JUL-00:10 |
| August | 0.849636E+10 | 0.226487E+10 | 744.00 | 0.788139E+10 | 0.614975E+09 | 0.00 | 0.52 | 20-AUG-16:02 | 0.01 | 29-AUG-06:00 | 6933.72 | 20-AUG-17:00 | 6933.72 | 20-AUG-17:00 | 975.73 | 26-AUG-10:50 | 2010.80 | 20-AUG-16:02 | 0.00 | 01-AUG-00:10 |
| September | 0.670345E+10 | 0.175380E+10 | 713.83 | 0.641818E+10 | 0.285274E+09 | 0.00 | 0.50 | 20-SEP-16:30 | 0.00 | 08-SEP-09:00 | 6835.94 | 20-SEP-16:17 | 6835.94 | 20-SEP-16:17 | 945.77 | 05-SEP-13:10 | 1866.34 | 20-SEP-16:30 | 0.00 | 01-SEP-00:10 |
| October | 0.419852E+10 | 0.109339E+10 | 528.03 | 0.414122E+10 | 57292263.32 | 0.00 | 0.44 | 06-OCT-16:10 | 0.00 | 03-OCT-05:03 | 6147.87 | 06-OCT-16:03 | 6147.87 | 06-OCT-16:03 | 682.29 | 11-OCT-11:10 | 1630.10 | 06-OCT-16:05 | 0.00 | 01-OCT-00:10 |
| November | 0.125251E+10 | 0.330331E+09 | 247.20 | 0.125251E+10 | -0.0 | 0.00 | 0.30 | 20-NOV-15:30 | 0.00 | 01-NOV-03:50 | 4062.22 | 20-NOV-15:30 | 4062.22 | 20-NOV-15:30 | 0.00 | 01-NOV-16:02 | 1049.82 | 20-NOV-15:30 | 0.00 | 01-NOV-00:10 |
| December | 0.310538E+09 | 82566007.64 | 89.63 | 0.310538E+09 | 0.00 | 0.00 | 0.23 | 31-DEC-15:30 | 0.00 | 01-DEC-00:10 | 3136.32 | 31-DEC-15:30 | 3136.32 | 31-DEC-15:30 | 0.00 | 02-DEC-14:20 | 818.84 | 31-DEC-15:30 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.453305E+11 | 0.120927E+11 | 5282.56 | 0.435330E+11 | 0.179745E+10 | 0.00 | ||||||||||||||
| Minimum of Months | 0.310538E+09 | 82566007.64 | 89.63 | 0.310538E+09 | -0.0 | 0.00 | 0.23 | 0.00 | 3136.32 | 3136.32 | 0.00 | 818.84 | 0.00 | |||||||
| Maximum of Months | 0.882114E+10 | 0.239059E+10 | 744.00 | 0.811323E+10 | 0.707912E+09 | 0.00 | 0.56 | 0.02 | 7049.99 | 7049.99 | 1109.07 | 2129.64 | 0.00 |
Report: DXReportMonthly
For: SPLIT MNW COOLING COIL
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| February | 410189.37 | 110603.67 | 0.78 | 410189.37 | 0.00 | 0.00 | 0.03 | 15-FEB-17:20 | 0.00 | 01-FEB-00:10 | 441.82 | 15-FEB-17:20 | 441.82 | 15-FEB-17:20 | 0.00 | 15-FEB-17:17 | 118.89 | 15-FEB-17:20 | 0.00 | 01-FEB-00:10 |
| March | 14360440.49 | 3863040.90 | 11.28 | 14360440.49 | -0.0 | 0.00 | 0.06 | 08-MAR-16:30 | 0.00 | 01-MAR-00:10 | 792.61 | 08-MAR-16:30 | 792.61 | 08-MAR-16:30 | 0.00 | 26-MAR-15:30 | 212.42 | 08-MAR-16:30 | 0.00 | 01-MAR-00:10 |
| April | 0.159134E+10 | 0.421767E+09 | 360.03 | 0.159134E+10 | 0.00 | 0.00 | 0.32 | 13-APR-16:27 | 0.00 | 01-APR-00:10 | 4324.78 | 13-APR-16:27 | 4324.78 | 13-APR-16:27 | 0.00 | 13-APR-17:30 | 1144.10 | 13-APR-16:27 | 0.00 | 01-APR-00:10 |
| May | 0.354624E+10 | 0.942491E+09 | 600.20 | 0.351644E+10 | 29804203.02 | 0.00 | 0.41 | 19-MAY-17:00 | 0.00 | 01-MAY-01:40 | 5345.74 | 19-MAY-16:50 | 5345.74 | 19-MAY-16:50 | 266.31 | 24-MAY-19:10 | 1480.85 | 19-MAY-17:00 | 0.00 | 01-MAY-00:10 |
| June | 0.657953E+10 | 0.180488E+10 | 688.94 | 0.647956E+10 | 99972752.72 | 0.00 | 0.56 | 28-JUN-16:30 | 0.00 | 01-JUN-06:35 | 6815.17 | 28-JUN-16:30 | 6815.17 | 28-JUN-16:30 | 464.12 | 24-JUN-08:50 | 2087.85 | 28-JUN-16:30 | 0.00 | 01-JUN-00:10 |
| July | 0.847255E+10 | 0.229634E+10 | 744.00 | 0.777539E+10 | 0.697157E+09 | 0.00 | 0.54 | 21-JUL-17:10 | 0.01 | 08-JUL-05:05 | 6895.78 | 04-JUL-17:10 | 6895.78 | 04-JUL-17:10 | 1034.33 | 01-JUL-14:00 | 2067.14 | 21-JUL-17:08 | 0.00 | 01-JUL-00:10 |
| August | 0.742526E+10 | 0.198698E+10 | 744.00 | 0.685132E+10 | 0.573940E+09 | 0.00 | 0.47 | 20-AUG-17:30 | 0.01 | 28-AUG-06:00 | 6177.52 | 20-AUG-17:30 | 6177.52 | 20-AUG-17:30 | 944.05 | 23-AUG-16:25 | 1797.39 | 20-AUG-17:30 | 0.00 | 01-AUG-00:10 |
| September | 0.455782E+10 | 0.120518E+10 | 699.54 | 0.433243E+10 | 0.225392E+09 | 0.00 | 0.38 | 02-SEP-16:40 | 0.00 | 08-SEP-09:00 | 5156.91 | 02-SEP-16:40 | 5156.91 | 02-SEP-16:40 | 754.86 | 05-SEP-13:10 | 1443.04 | 02-SEP-16:40 | 0.00 | 01-SEP-00:10 |
| October | 0.154673E+10 | 0.408544E+09 | 325.45 | 0.150795E+10 | 38776926.96 | 0.00 | 0.31 | 06-OCT-16:17 | 0.00 | 03-OCT-05:03 | 4170.57 | 06-OCT-16:17 | 4170.57 | 06-OCT-16:17 | 410.92 | 11-OCT-11:10 | 1127.22 | 06-OCT-16:10 | 0.00 | 01-OCT-00:10 |
| November | 1218110.92 | 327215.43 | 2.62 | 1218110.92 | 0.00 | 0.00 | 0.03 | 02-NOV-17:40 | 0.00 | 01-NOV-00:10 | 424.65 | 02-NOV-17:40 | 424.65 | 02-NOV-17:40 | 0.00 | 03-NOV-16:01 | 113.51 | 02-NOV-17:40 | 0.00 | 01-NOV-00:10 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.337355E+11 | 0.907049E+10 | 4176.85 | 0.320704E+11 | 0.166504E+10 | 0.00 | ||||||||||||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | -0.0 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Maximum of Months | 0.847255E+10 | 0.229634E+10 | 744.00 | 0.777539E+10 | 0.697157E+09 | 0.00 | 0.56 | 0.01 | 6895.78 | 6895.78 | 1034.33 | 2087.85 | 0.00 |
Report: DXReportMonthly
For: SPLIT MSE COOLING COIL
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.418317E+09 | 0.111036E+09 | 109.88 | 0.418317E+09 | -0.0 | 0.00 | 0.23 | 02-JAN-14:00 | 0.00 | 01-JAN-00:10 | 2809.78 | 02-JAN-14:00 | 2809.78 | 02-JAN-14:00 | 0.00 | 02-JAN-12:20 | 733.60 | 02-JAN-14:00 | 0.00 | 01-JAN-00:10 |
| February | 0.576138E+09 | 0.152102E+09 | 121.25 | 0.576138E+09 | 0.00 | 0.00 | 0.31 | 14-FEB-14:50 | 0.00 | 01-FEB-00:10 | 3786.87 | 14-FEB-14:50 | 3786.87 | 14-FEB-14:50 | 0.00 | 10-FEB-13:40 | 976.94 | 14-FEB-14:50 | 0.00 | 01-FEB-00:10 |
| March | 0.106533E+10 | 0.281412E+09 | 229.12 | 0.106533E+10 | 0.00 | 0.00 | 0.30 | 08-MAR-14:00 | 0.00 | 01-MAR-00:10 | 3746.40 | 08-MAR-14:00 | 3746.40 | 08-MAR-14:00 | 0.00 | 07-MAR-15:30 | 966.98 | 08-MAR-14:00 | 0.00 | 01-MAR-00:10 |
| April | 0.319975E+10 | 0.840709E+09 | 528.56 | 0.319975E+10 | -0.0 | 0.00 | 0.35 | 28-APR-13:00 | 0.00 | 01-APR-00:10 | 4355.85 | 28-APR-13:00 | 4355.85 | 28-APR-13:00 | 0.00 | 13-APR-18:10 | 1123.70 | 28-APR-13:00 | 0.00 | 01-APR-00:10 |
| May | 0.436119E+10 | 0.115023E+10 | 644.44 | 0.431744E+10 | 43753359.54 | 0.00 | 0.38 | 19-MAY-15:10 | 0.00 | 01-MAY-02:40 | 4517.42 | 19-MAY-13:00 | 4517.42 | 19-MAY-13:00 | 327.64 | 29-MAY-07:45 | 1251.36 | 19-MAY-15:10 | 0.00 | 01-MAY-00:10 |
| June | 0.686186E+10 | 0.187006E+10 | 695.50 | 0.674917E+10 | 0.112692E+09 | 0.00 | 0.51 | 29-JUN-15:10 | 0.00 | 01-JUN-06:35 | 5828.26 | 29-JUN-15:10 | 5828.26 | 29-JUN-15:10 | 646.30 | 24-JUN-08:50 | 1768.07 | 29-JUN-15:10 | 0.00 | 01-JUN-00:10 |
| July | 0.925803E+10 | 0.248620E+10 | 744.00 | 0.850657E+10 | 0.751459E+09 | 0.00 | 0.52 | 22-JUL-14:00 | 0.03 | 08-JUL-05:05 | 6128.46 | 22-JUL-14:00 | 6128.46 | 22-JUL-14:00 | 1095.66 | 01-JUL-14:00 | 1858.81 | 22-JUL-14:00 | 0.00 | 01-JUL-00:10 |
| August | 0.883044E+10 | 0.233493E+10 | 744.00 | 0.817819E+10 | 0.652248E+09 | 0.00 | 0.48 | 20-AUG-15:20 | 0.01 | 29-AUG-05:40 | 5918.14 | 17-AUG-13:30 | 5789.92 | 20-AUG-15:20 | 1090.48 | 26-AUG-10:40 | 1693.26 | 20-AUG-15:20 | 0.00 | 01-AUG-00:10 |
| September | 0.683483E+10 | 0.177829E+10 | 711.55 | 0.653862E+10 | 0.296210E+09 | 0.00 | 0.50 | 03-SEP-13:30 | 0.00 | 08-SEP-09:00 | 6285.15 | 03-SEP-13:30 | 6187.28 | 03-SEP-13:30 | 912.36 | 05-SEP-13:00 | 1744.22 | 03-SEP-13:30 | 0.00 | 01-SEP-00:10 |
| October | 0.425362E+10 | 0.110449E+10 | 533.99 | 0.419199E+10 | 61639124.97 | 0.00 | 0.44 | 01-OCT-13:50 | 0.00 | 03-OCT-05:03 | 5564.88 | 10-OCT-12:30 | 5512.37 | 01-OCT-13:40 | 743.59 | 11-OCT-11:10 | 1464.67 | 01-OCT-14:00 | 0.00 | 01-OCT-00:10 |
| November | 0.124102E+10 | 0.327200E+09 | 260.61 | 0.124102E+10 | -0.0 | 0.00 | 0.29 | 01-NOV-12:50 | 0.00 | 01-NOV-03:30 | 3575.31 | 01-NOV-12:50 | 3575.31 | 01-NOV-12:50 | 0.00 | 06-NOV-11:10 | 921.14 | 01-NOV-12:50 | 0.00 | 01-NOV-00:10 |
| December | 0.249956E+09 | 66511049.80 | 83.24 | 0.249956E+09 | -0.0 | 0.00 | 0.21 | 31-DEC-14:30 | 0.00 | 01-DEC-00:10 | 2531.66 | 31-DEC-14:30 | 2531.66 | 31-DEC-14:30 | 0.00 | 24-DEC-14:30 | 663.26 | 31-DEC-14:30 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.471505E+11 | 0.125032E+11 | 5406.13 | 0.452325E+11 | 0.191800E+10 | 0.00 | ||||||||||||||
| Minimum of Months | 0.249956E+09 | 66511049.80 | 83.24 | 0.249956E+09 | -0.0 | 0.00 | 0.21 | 0.00 | 2531.66 | 2531.66 | 0.00 | 663.26 | 0.00 | |||||||
| Maximum of Months | 0.925803E+10 | 0.248620E+10 | 744.00 | 0.850657E+10 | 0.751459E+09 | 0.00 | 0.52 | 0.03 | 6285.15 | 6187.28 | 1095.66 | 1858.81 | 0.00 |
Report: DXReportMonthly
For: SPLIT MNE COOLING COIL
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
| March | 5314280.21 | 1433386.68 | 9.17 | 5314280.21 | 0.00 | 0.00 | 0.03 | 26-MAR-17:00 | 0.00 | 01-MAR-00:10 | 322.66 | 26-MAR-17:00 | 322.66 | 26-MAR-17:00 | 0.00 | 26-MAR-16:20 | 86.90 | 26-MAR-17:00 | 0.00 | 01-MAR-00:10 |
| April | 0.179987E+10 | 0.476611E+09 | 410.95 | 0.179987E+10 | 0.00 | 0.00 | 0.28 | 29-APR-16:10 | 0.00 | 01-APR-00:10 | 3328.94 | 29-APR-16:10 | 3328.94 | 29-APR-16:10 | 0.00 | 25-APR-16:00 | 882.42 | 29-APR-16:10 | 0.00 | 01-APR-00:10 |
| May | 0.384044E+10 | 0.101597E+10 | 622.31 | 0.379818E+10 | 42258706.66 | 0.00 | 0.35 | 19-MAY-17:05 | 0.00 | 01-MAY-01:40 | 4128.15 | 19-MAY-17:20 | 4128.15 | 19-MAY-17:20 | 318.15 | 29-MAY-07:35 | 1151.16 | 19-MAY-17:05 | 0.00 | 01-MAY-00:10 |
| June | 0.691367E+10 | 0.188119E+10 | 696.72 | 0.680246E+10 | 0.111212E+09 | 0.00 | 0.50 | 28-JUN-16:10 | 0.00 | 01-JUN-06:35 | 5629.89 | 29-JUN-15:10 | 5629.89 | 29-JUN-15:10 | 613.02 | 24-JUN-08:50 | 1710.90 | 29-JUN-15:10 | 0.00 | 01-JUN-00:10 |
| July | 0.890977E+10 | 0.239309E+10 | 744.00 | 0.816901E+10 | 0.740766E+09 | 0.00 | 0.48 | 04-JUL-17:00 | 0.03 | 08-JUL-05:10 | 5440.59 | 04-JUL-17:00 | 5440.59 | 04-JUL-17:00 | 1021.12 | 01-JUL-14:00 | 1640.74 | 22-JUL-15:10 | 0.00 | 01-JUL-00:10 |
| August | 0.776240E+10 | 0.206097E+10 | 744.00 | 0.714752E+10 | 0.614876E+09 | 0.00 | 0.41 | 20-AUG-17:10 | 0.00 | 29-AUG-05:40 | 4916.60 | 17-AUG-10:30 | 4844.89 | 20-AUG-16:40 | 947.20 | 14-AUG-07:35 | 1428.06 | 20-AUG-16:20 | 0.00 | 01-AUG-00:10 |
| September | 0.469012E+10 | 0.123482E+10 | 697.74 | 0.445150E+10 | 0.238625E+09 | 0.00 | 0.35 | 03-SEP-14:10 | 0.00 | 08-SEP-09:00 | 4185.27 | 03-SEP-14:10 | 4149.48 | 03-SEP-14:10 | 724.79 | 05-SEP-13:00 | 1200.25 | 03-SEP-14:00 | 0.00 | 01-SEP-00:10 |
| October | 0.154084E+10 | 0.406352E+09 | 359.16 | 0.149678E+10 | 44058142.57 | 0.00 | 0.27 | 01-OCT-16:10 | 0.00 | 03-OCT-05:03 | 3279.81 | 01-OCT-16:10 | 3279.81 | 01-OCT-16:10 | 487.40 | 11-OCT-11:00 | 900.49 | 01-OCT-16:10 | 0.00 | 01-OCT-00:10 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.354624E+11 | 0.947043E+10 | 4284.04 | 0.336706E+11 | 0.179180E+10 | 0.00 | ||||||||||||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Maximum of Months | 0.890977E+10 | 0.239309E+10 | 744.00 | 0.816901E+10 | 0.740766E+09 | 0.00 | 0.50 | 0.03 | 5629.89 | 5629.89 | 1021.12 | 1710.90 | 0.00 |
Report: DXReportMonthly
For: SPLIT MN1 COOLING COIL
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
| March | 596907.90 | 160938.09 | 1.00 | 596907.90 | -0.0 | 0.00 | 0.03 | 27-MAR-18:50 | 0.00 | 01-MAR-00:10 | 290.31 | 27-MAR-18:50 | 290.31 | 27-MAR-18:50 | 0.00 | 27-MAR-19:30 | 78.19 | 27-MAR-18:50 | 0.00 | 01-MAR-00:10 |
| April | 0.116873E+10 | 0.311004E+09 | 384.23 | 0.116873E+10 | 0.00 | 0.00 | 0.23 | 29-APR-16:10 | 0.00 | 01-APR-00:10 | 2481.72 | 29-APR-16:10 | 2481.72 | 29-APR-16:10 | 0.00 | 12-APR-18:20 | 662.28 | 29-APR-16:10 | 0.00 | 01-APR-00:10 |
| May | 0.284167E+10 | 0.756104E+09 | 636.36 | 0.280665E+10 | 35017616.60 | 0.00 | 0.32 | 19-MAY-18:00 | 0.00 | 01-MAY-03:00 | 3285.94 | 19-MAY-18:00 | 3285.94 | 19-MAY-18:00 | 294.49 | 24-MAY-19:10 | 915.74 | 19-MAY-17:50 | 0.00 | 01-MAY-00:10 |
| June | 0.516785E+10 | 0.141585E+10 | 707.71 | 0.507099E+10 | 96854700.67 | 0.00 | 0.44 | 28-JUN-16:40 | 0.00 | 01-JUN-06:35 | 4266.03 | 28-JUN-17:03 | 4266.03 | 28-JUN-17:03 | 405.51 | 24-JUN-08:50 | 1316.99 | 28-JUN-16:17 | 0.00 | 01-JUN-00:10 |
| July | 0.680267E+10 | 0.183600E+10 | 744.00 | 0.617209E+10 | 0.630582E+09 | 0.00 | 0.42 | 04-JUL-17:04 | 0.04 | 08-JUL-05:10 | 4242.08 | 04-JUL-17:04 | 4242.08 | 04-JUL-17:04 | 871.97 | 01-JUL-14:10 | 1280.05 | 21-JUL-17:03 | 0.00 | 01-JUL-00:10 |
| August | 0.591033E+10 | 0.157713E+10 | 744.00 | 0.539371E+10 | 0.516621E+09 | 0.00 | 0.37 | 20-AUG-17:30 | 0.02 | 29-AUG-06:00 | 3779.86 | 20-AUG-17:30 | 3779.86 | 20-AUG-17:30 | 687.06 | 26-AUG-11:40 | 1117.90 | 20-AUG-17:30 | 0.00 | 01-AUG-00:10 |
| September | 0.369910E+10 | 0.977030E+09 | 717.43 | 0.348643E+10 | 0.212674E+09 | 0.00 | 0.29 | 03-SEP-14:10 | 0.00 | 08-SEP-09:00 | 3073.32 | 04-SEP-16:20 | 3041.76 | 02-SEP-17:10 | 617.94 | 05-SEP-13:00 | 881.22 | 03-SEP-14:10 | 0.00 | 01-SEP-00:10 |
| October | 0.121664E+10 | 0.321619E+09 | 361.05 | 0.117831E+10 | 38334953.69 | 0.00 | 0.25 | 01-OCT-16:10 | 0.00 | 03-OCT-05:03 | 2620.17 | 01-OCT-16:10 | 2620.17 | 01-OCT-16:10 | 372.77 | 11-OCT-11:10 | 722.29 | 01-OCT-16:10 | 0.00 | 01-OCT-00:10 |
| November | 260045.61 | 69759.37 | 1.33 | 260045.61 | 0.00 | 0.00 | 0.02 | 02-NOV-17:50 | 0.00 | 01-NOV-00:10 | 159.89 | 02-NOV-17:50 | 159.89 | 02-NOV-17:50 | 0.00 | 02-NOV-17:50 | 42.85 | 02-NOV-17:50 | 0.00 | 01-NOV-00:10 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.268078E+11 | 0.719496E+10 | 4297.11 | 0.252778E+11 | 0.153008E+10 | 0.00 | ||||||||||||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | -0.0 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Maximum of Months | 0.680267E+10 | 0.183600E+10 | 744.00 | 0.617209E+10 | 0.630582E+09 | 0.00 | 0.44 | 0.04 | 4266.03 | 4266.03 | 871.97 | 1316.99 | 0.00 |
Report: DXReportMonthly
For: SPLIT MN2 COOLING COIL
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
| March | 659977.91 | 177904.73 | 1.00 | 659977.91 | 0.00 | 0.00 | 0.03 | 27-MAR-18:40 | 0.00 | 01-MAR-00:10 | 287.61 | 27-MAR-18:40 | 287.61 | 27-MAR-18:40 | 0.00 | 27-MAR-19:00 | 77.46 | 27-MAR-18:40 | 0.00 | 01-MAR-00:10 |
| April | 0.119019E+10 | 0.316683E+09 | 389.56 | 0.119019E+10 | 0.00 | 0.00 | 0.24 | 29-APR-16:10 | 0.00 | 01-APR-00:10 | 2496.40 | 29-APR-16:10 | 2496.40 | 29-APR-16:10 | 0.00 | 13-APR-17:20 | 666.00 | 29-APR-16:10 | 0.00 | 01-APR-00:10 |
| May | 0.285982E+10 | 0.760801E+09 | 639.40 | 0.282433E+10 | 35499050.41 | 0.00 | 0.31 | 19-MAY-18:00 | 0.00 | 01-MAY-03:00 | 3271.28 | 19-MAY-18:00 | 3271.28 | 19-MAY-18:00 | 293.87 | 24-MAY-19:10 | 911.38 | 19-MAY-17:50 | 0.00 | 01-MAY-00:10 |
| June | 0.518176E+10 | 0.141940E+10 | 708.21 | 0.508458E+10 | 97187777.39 | 0.00 | 0.44 | 28-JUN-16:30 | 0.00 | 01-JUN-06:35 | 4249.54 | 28-JUN-17:10 | 4249.54 | 28-JUN-17:10 | 408.75 | 24-JUN-08:50 | 1313.70 | 28-JUN-16:30 | 0.00 | 01-JUN-00:10 |
| July | 0.681961E+10 | 0.184020E+10 | 744.00 | 0.618762E+10 | 0.631989E+09 | 0.00 | 0.42 | 04-JUL-17:08 | 0.04 | 08-JUL-05:05 | 4225.74 | 04-JUL-17:08 | 4225.74 | 04-JUL-17:08 | 873.67 | 01-JUL-14:10 | 1274.79 | 21-JUL-17:07 | 0.00 | 01-JUL-00:10 |
| August | 0.592314E+10 | 0.158029E+10 | 744.00 | 0.540546E+10 | 0.517686E+09 | 0.00 | 0.37 | 20-AUG-17:30 | 0.02 | 29-AUG-06:00 | 3762.11 | 20-AUG-17:17 | 3762.11 | 20-AUG-17:17 | 691.42 | 26-AUG-11:40 | 1112.71 | 20-AUG-17:17 | 0.00 | 01-AUG-00:10 |
| September | 0.370500E+10 | 0.978497E+09 | 717.42 | 0.349207E+10 | 0.212933E+09 | 0.00 | 0.29 | 03-SEP-14:10 | 0.00 | 08-SEP-09:00 | 3062.81 | 04-SEP-16:10 | 3023.02 | 02-SEP-17:03 | 618.23 | 05-SEP-13:00 | 883.74 | 03-SEP-14:10 | 0.00 | 01-SEP-00:10 |
| October | 0.122255E+10 | 0.323166E+09 | 362.51 | 0.118405E+10 | 38499991.35 | 0.00 | 0.25 | 01-OCT-16:10 | 0.00 | 03-OCT-05:03 | 2614.00 | 01-OCT-16:10 | 2614.00 | 01-OCT-16:10 | 375.44 | 11-OCT-11:10 | 720.58 | 01-OCT-16:10 | 0.00 | 01-OCT-00:10 |
| November | 216817.68 | 58173.46 | 1.17 | 216817.68 | -0.0 | 0.00 | 0.01 | 02-NOV-17:50 | 0.00 | 01-NOV-00:10 | 130.08 | 02-NOV-17:50 | 130.08 | 02-NOV-17:50 | 0.00 | 02-NOV-18:20 | 34.88 | 02-NOV-17:50 | 0.00 | 01-NOV-00:10 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.269030E+11 | 0.721927E+10 | 4307.26 | 0.253692E+11 | 0.153379E+10 | 0.00 | ||||||||||||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | -0.0 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Maximum of Months | 0.681961E+10 | 0.184020E+10 | 744.00 | 0.618762E+10 | 0.631989E+09 | 0.00 | 0.44 | 0.04 | 4249.54 | 4249.54 | 873.67 | 1313.70 | 0.00 |
Report: DXReportMonthly
For: SPLIT MS1 COOLING COIL
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.693595E+09 | 0.183094E+09 | 161.97 | 0.693595E+09 | 0.00 | 0.00 | 0.30 | 01-JAN-13:50 | 0.00 | 01-JAN-00:10 | 3274.99 | 01-JAN-13:50 | 3274.99 | 01-JAN-13:50 | 0.00 | 02-JAN-14:10 | 846.18 | 01-JAN-13:50 | 0.00 | 01-JAN-00:10 |
| February | 0.750997E+09 | 0.197830E+09 | 173.52 | 0.750997E+09 | 0.00 | 0.00 | 0.34 | 14-FEB-15:00 | 0.00 | 01-FEB-00:10 | 3723.17 | 14-FEB-15:00 | 3723.17 | 14-FEB-15:00 | 0.00 | 15-FEB-14:50 | 956.13 | 14-FEB-15:00 | 0.00 | 01-FEB-00:10 |
| March | 0.108700E+10 | 0.287316E+09 | 285.71 | 0.108700E+10 | 0.00 | 0.00 | 0.31 | 08-MAR-14:00 | 0.00 | 01-MAR-00:10 | 3386.40 | 08-MAR-14:00 | 3386.40 | 08-MAR-14:00 | 0.00 | 08-MAR-14:40 | 873.64 | 08-MAR-14:00 | 0.00 | 01-MAR-00:10 |
| April | 0.255374E+10 | 0.673974E+09 | 559.66 | 0.255374E+10 | -0.0 | 0.00 | 0.31 | 26-APR-14:10 | 0.00 | 01-APR-00:10 | 3361.64 | 26-APR-14:10 | 3361.64 | 26-APR-14:10 | 0.00 | 27-APR-12:20 | 887.95 | 26-APR-14:10 | 0.00 | 01-APR-00:10 |
| May | 0.336022E+10 | 0.891313E+09 | 667.75 | 0.332404E+10 | 36179342.55 | 0.00 | 0.33 | 19-MAY-16:20 | 0.00 | 01-MAY-23:10 | 3484.36 | 19-MAY-16:04 | 3484.36 | 19-MAY-16:04 | 214.20 | 24-MAY-19:10 | 976.53 | 19-MAY-16:20 | 0.00 | 01-MAY-00:10 |
| June | 0.511724E+10 | 0.140480E+10 | 705.96 | 0.501928E+10 | 97954298.00 | 0.00 | 0.45 | 28-JUN-16:10 | 0.00 | 01-JUN-06:35 | 4354.88 | 29-JUN-15:10 | 4354.88 | 29-JUN-15:10 | 430.52 | 24-JUN-10:00 | 1346.50 | 28-JUN-16:04 | 0.00 | 01-JUN-00:10 |
| July | 0.715353E+10 | 0.193123E+10 | 744.00 | 0.651037E+10 | 0.643162E+09 | 0.00 | 0.45 | 22-JUL-15:10 | 0.05 | 08-JUL-05:05 | 4650.70 | 22-JUL-15:10 | 4650.70 | 22-JUL-15:10 | 942.84 | 01-JUL-14:00 | 1433.32 | 22-JUL-15:10 | 0.00 | 01-JUL-00:10 |
| August | 0.698925E+10 | 0.185745E+10 | 744.00 | 0.642619E+10 | 0.563066E+09 | 0.00 | 0.44 | 20-AUG-16:05 | 0.03 | 29-AUG-06:00 | 4645.84 | 20-AUG-16:03 | 4645.84 | 20-AUG-16:03 | 910.58 | 26-AUG-11:30 | 1367.34 | 20-AUG-16:03 | 0.00 | 01-AUG-00:10 |
| September | 0.586216E+10 | 0.152991E+10 | 718.83 | 0.558595E+10 | 0.276210E+09 | 0.00 | 0.46 | 21-SEP-14:10 | 0.00 | 08-SEP-09:00 | 5075.62 | 03-SEP-13:30 | 5054.74 | 21-SEP-14:10 | 834.45 | 05-SEP-13:00 | 1418.55 | 03-SEP-13:30 | 0.00 | 01-SEP-00:10 |
| October | 0.404996E+10 | 0.105330E+10 | 597.61 | 0.399225E+10 | 57716520.37 | 0.00 | 0.42 | 01-OCT-14:00 | 0.00 | 03-OCT-05:03 | 4729.26 | 10-OCT-12:30 | 4686.83 | 01-OCT-14:00 | 643.13 | 11-OCT-11:10 | 1251.89 | 01-OCT-14:00 | 0.00 | 01-OCT-00:10 |
| November | 0.171268E+10 | 0.450076E+09 | 354.83 | 0.171268E+10 | 0.00 | 0.00 | 0.34 | 20-NOV-14:00 | 0.00 | 01-NOV-05:50 | 3711.25 | 20-NOV-14:00 | 3711.25 | 20-NOV-14:00 | 0.00 | 01-NOV-10:40 | 953.22 | 20-NOV-14:00 | 0.00 | 01-NOV-00:10 |
| December | 0.590065E+09 | 0.156208E+09 | 164.35 | 0.590065E+09 | 0.00 | 0.00 | 0.28 | 31-DEC-14:40 | 0.00 | 01-DEC-00:10 | 3088.63 | 31-DEC-14:40 | 3088.63 | 31-DEC-14:40 | 0.00 | 30-DEC-13:00 | 800.06 | 31-DEC-14:40 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.399205E+11 | 0.106165E+11 | 5878.19 | 0.382462E+11 | 0.167429E+10 | 0.00 | ||||||||||||||
| Minimum of Months | 0.590065E+09 | 0.156208E+09 | 161.97 | 0.590065E+09 | -0.0 | 0.00 | 0.28 | 0.00 | 3088.63 | 3088.63 | 0.00 | 800.06 | 0.00 | |||||||
| Maximum of Months | 0.715353E+10 | 0.193123E+10 | 744.00 | 0.651037E+10 | 0.643162E+09 | 0.00 | 0.46 | 0.05 | 5075.62 | 5054.74 | 942.84 | 1433.32 | 0.00 |
Report: DXReportMonthly
For: SPLIT MS2 COOLING COIL
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.700972E+09 | 0.185004E+09 | 162.56 | 0.700972E+09 | 0.00 | 0.00 | 0.30 | 01-JAN-13:50 | 0.00 | 01-JAN-00:10 | 3290.49 | 01-JAN-13:50 | 3290.49 | 01-JAN-13:50 | 0.00 | 01-JAN-15:50 | 849.90 | 01-JAN-13:50 | 0.00 | 01-JAN-00:10 |
| February | 0.753678E+09 | 0.198504E+09 | 172.73 | 0.753678E+09 | -0.0 | 0.00 | 0.34 | 14-FEB-15:00 | 0.00 | 01-FEB-00:10 | 3729.87 | 14-FEB-15:00 | 3729.87 | 14-FEB-15:00 | 0.00 | 09-FEB-16:10 | 957.64 | 14-FEB-15:00 | 0.00 | 01-FEB-00:10 |
| March | 0.110532E+10 | 0.292099E+09 | 287.99 | 0.110532E+10 | 0.00 | 0.00 | 0.31 | 08-MAR-14:00 | 0.00 | 01-MAR-00:10 | 3406.59 | 08-MAR-14:00 | 3406.59 | 08-MAR-14:00 | 0.00 | 07-MAR-14:20 | 878.50 | 08-MAR-14:00 | 0.00 | 01-MAR-00:10 |
| April | 0.257499E+10 | 0.679470E+09 | 560.31 | 0.257499E+10 | -0.0 | 0.00 | 0.31 | 26-APR-14:10 | 0.00 | 01-APR-00:10 | 3378.35 | 26-APR-14:10 | 3378.35 | 26-APR-14:10 | 0.00 | 13-APR-18:20 | 892.05 | 26-APR-14:10 | 0.00 | 01-APR-00:10 |
| May | 0.337958E+10 | 0.896283E+09 | 669.34 | 0.334291E+10 | 36673256.92 | 0.00 | 0.33 | 19-MAY-16:20 | 0.00 | 01-MAY-23:10 | 3477.70 | 19-MAY-16:04 | 3477.70 | 19-MAY-16:04 | 213.66 | 24-MAY-19:10 | 974.49 | 19-MAY-16:04 | 0.00 | 01-MAY-00:10 |
| June | 0.513154E+10 | 0.140844E+10 | 706.29 | 0.503326E+10 | 98289494.55 | 0.00 | 0.45 | 28-JUN-16:10 | 0.00 | 01-JUN-06:35 | 4358.58 | 29-JUN-15:10 | 4358.58 | 29-JUN-15:10 | 432.90 | 24-JUN-10:00 | 1343.60 | 28-JUN-16:04 | 0.00 | 01-JUN-00:10 |
| July | 0.717048E+10 | 0.193539E+10 | 744.00 | 0.652596E+10 | 0.644527E+09 | 0.00 | 0.45 | 22-JUL-15:10 | 0.05 | 08-JUL-05:05 | 4661.08 | 22-JUL-14:10 | 4661.08 | 22-JUL-14:10 | 943.66 | 01-JUL-14:00 | 1432.98 | 22-JUL-15:10 | 0.00 | 01-JUL-00:10 |
| August | 0.700169E+10 | 0.186040E+10 | 744.00 | 0.643774E+10 | 0.563952E+09 | 0.00 | 0.44 | 20-AUG-16:05 | 0.03 | 29-AUG-06:00 | 4637.19 | 20-AUG-16:03 | 4637.19 | 20-AUG-16:03 | 913.34 | 26-AUG-11:30 | 1364.72 | 20-AUG-16:03 | 0.00 | 01-AUG-00:10 |
| September | 0.586766E+10 | 0.153110E+10 | 718.83 | 0.559128E+10 | 0.276383E+09 | 0.00 | 0.46 | 21-SEP-14:10 | 0.00 | 08-SEP-09:00 | 5090.49 | 03-SEP-13:30 | 5061.19 | 21-SEP-14:10 | 834.71 | 05-SEP-13:00 | 1422.18 | 03-SEP-13:30 | 0.00 | 01-SEP-00:10 |
| October | 0.405612E+10 | 0.105475E+10 | 597.58 | 0.399831E+10 | 57811264.48 | 0.00 | 0.42 | 01-OCT-14:00 | 0.00 | 03-OCT-05:03 | 4747.49 | 10-OCT-12:30 | 4698.33 | 01-OCT-14:00 | 644.98 | 11-OCT-11:10 | 1254.57 | 01-OCT-14:00 | 0.00 | 01-OCT-00:10 |
| November | 0.172057E+10 | 0.452081E+09 | 354.50 | 0.172057E+10 | -0.0 | 0.00 | 0.34 | 20-NOV-14:00 | 0.00 | 01-NOV-05:50 | 3719.63 | 20-NOV-14:00 | 3719.63 | 20-NOV-14:00 | 0.00 | 01-NOV-12:20 | 955.14 | 20-NOV-14:00 | 0.00 | 01-NOV-00:10 |
| December | 0.595581E+09 | 0.157643E+09 | 164.77 | 0.595581E+09 | 0.00 | 0.00 | 0.28 | 31-DEC-14:30 | 0.00 | 01-DEC-00:10 | 3100.89 | 31-DEC-14:30 | 3100.89 | 31-DEC-14:30 | 0.00 | 02-DEC-13:50 | 803.01 | 31-DEC-14:30 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.400582E+11 | 0.106512E+11 | 5882.89 | 0.383806E+11 | 0.167764E+10 | 0.00 | ||||||||||||||
| Minimum of Months | 0.595581E+09 | 0.157643E+09 | 162.56 | 0.595581E+09 | -0.0 | 0.00 | 0.28 | 0.00 | 3100.89 | 3100.89 | 0.00 | 803.01 | 0.00 | |||||||
| Maximum of Months | 0.717048E+10 | 0.193539E+10 | 744.00 | 0.652596E+10 | 0.644527E+09 | 0.00 | 0.46 | 0.05 | 5090.49 | 5061.19 | 943.66 | 1432.98 | 0.00 |
Report: DXReportMonthly
For: SPLIT TSW COOLING COIL
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.388252E+09 | 0.102270E+09 | 108.42 | 0.388252E+09 | 0.00 | 0.00 | 0.29 | 23-JAN-15:30 | 0.00 | 01-JAN-00:10 | 2247.96 | 23-JAN-15:30 | 2247.96 | 23-JAN-15:30 | 0.00 | 03-JAN-16:10 | 581.16 | 23-JAN-15:30 | 0.00 | 01-JAN-00:10 |
| February | 0.484620E+09 | 0.126977E+09 | 124.88 | 0.484620E+09 | -0.0 | 0.00 | 0.38 | 14-FEB-15:30 | 0.00 | 01-FEB-00:10 | 2962.97 | 14-FEB-15:30 | 2962.97 | 14-FEB-15:30 | 0.00 | 09-FEB-15:30 | 755.40 | 14-FEB-15:30 | 0.00 | 01-FEB-00:10 |
| March | 0.635228E+09 | 0.166531E+09 | 165.71 | 0.635228E+09 | -0.0 | 0.00 | 0.35 | 12-MAR-16:03 | 0.00 | 01-MAR-00:10 | 2715.19 | 12-MAR-16:03 | 2715.19 | 12-MAR-16:03 | 0.00 | 08-MAR-17:05 | 695.57 | 12-MAR-16:03 | 0.00 | 01-MAR-00:10 |
| April | 0.140368E+10 | 0.366856E+09 | 309.28 | 0.140368E+10 | 0.00 | 0.00 | 0.44 | 13-APR-16:14 | 0.00 | 01-APR-00:10 | 3435.68 | 13-APR-16:14 | 3435.68 | 13-APR-16:14 | 0.00 | 14-APR-16:00 | 890.22 | 13-APR-16:14 | 0.00 | 01-APR-00:10 |
| May | 0.207754E+10 | 0.548103E+09 | 409.21 | 0.207084E+10 | 6697195.26 | 0.00 | 0.51 | 19-MAY-16:30 | 0.00 | 01-MAY-00:10 | 3865.02 | 19-MAY-16:30 | 3865.02 | 19-MAY-16:30 | 122.81 | 23-MAY-15:20 | 1052.57 | 19-MAY-16:30 | 0.00 | 01-MAY-00:10 |
| June | 0.363593E+10 | 0.100136E+10 | 576.46 | 0.359540E+10 | 40527092.13 | 0.00 | 0.68 | 28-JUN-16:30 | 0.00 | 01-JUN-01:40 | 4781.26 | 28-JUN-16:30 | 4781.26 | 28-JUN-16:30 | 297.53 | 24-JUN-10:00 | 1435.11 | 28-JUN-16:30 | 0.00 | 01-JUN-00:10 |
| July | 0.497478E+10 | 0.135296E+10 | 730.17 | 0.463572E+10 | 0.339063E+09 | 0.00 | 0.66 | 21-JUL-17:00 | 0.00 | 02-JUL-02:50 | 4811.48 | 22-JUL-15:30 | 4811.48 | 22-JUL-15:30 | 690.92 | 01-JUL-14:00 | 1424.64 | 22-JUL-15:30 | 0.00 | 01-JUL-00:10 |
| August | 0.467279E+10 | 0.124737E+10 | 701.31 | 0.439146E+10 | 0.281333E+09 | 0.00 | 0.63 | 20-AUG-16:10 | 0.00 | 03-AUG-05:05 | 4823.29 | 20-AUG-16:08 | 4823.29 | 20-AUG-16:08 | 616.61 | 26-AUG-10:50 | 1375.22 | 20-AUG-16:10 | 0.00 | 01-AUG-00:10 |
| September | 0.337662E+10 | 0.880630E+09 | 536.25 | 0.326102E+10 | 0.115596E+09 | 0.00 | 0.58 | 20-SEP-15:20 | 0.00 | 02-SEP-03:40 | 4451.93 | 21-SEP-15:20 | 4451.93 | 21-SEP-15:20 | 602.86 | 05-SEP-13:10 | 1201.52 | 03-SEP-13:50 | 0.00 | 01-SEP-00:10 |
| October | 0.194958E+10 | 0.504850E+09 | 361.25 | 0.192828E+10 | 21298612.00 | 0.00 | 0.51 | 01-OCT-15:30 | 0.00 | 01-OCT-02:70 | 4048.67 | 01-OCT-15:20 | 4048.67 | 01-OCT-15:20 | 383.56 | 11-OCT-11:10 | 1070.88 | 01-OCT-15:30 | 0.00 | 01-OCT-00:10 |
| November | 0.610270E+09 | 0.160304E+09 | 166.37 | 0.610270E+09 | 0.00 | 0.00 | 0.31 | 20-NOV-15:20 | 0.00 | 01-NOV-00:10 | 2403.35 | 20-NOV-15:20 | 2403.35 | 20-NOV-15:20 | 0.00 | 07-NOV-15:40 | 619.44 | 20-NOV-15:20 | 0.00 | 01-NOV-00:10 |
| December | 0.300416E+09 | 79498152.11 | 107.44 | 0.300416E+09 | 0.00 | 0.00 | 0.29 | 31-DEC-15:30 | 0.00 | 01-DEC-00:10 | 2217.64 | 31-DEC-15:30 | 2217.64 | 31-DEC-15:30 | 0.00 | 27-DEC-14:40 | 573.66 | 31-DEC-15:30 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.245097E+11 | 0.653770E+10 | 4296.74 | 0.237052E+11 | 0.804515E+09 | 0.00 | ||||||||||||||
| Minimum of Months | 0.300416E+09 | 79498152.11 | 107.44 | 0.300416E+09 | -0.0 | 0.00 | 0.29 | 0.00 | 2217.64 | 2217.64 | 0.00 | 573.66 | 0.00 | |||||||
| Maximum of Months | 0.497478E+10 | 0.135296E+10 | 730.17 | 0.463572E+10 | 0.339063E+09 | 0.00 | 0.68 | 0.00 | 4823.29 | 4823.29 | 690.92 | 1435.11 | 0.00 |
Report: DXReportMonthly
For: SPLIT TNW COOLING COIL
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| February | 17159779.36 | 4596467.15 | 14.44 | 17159779.36 | 0.00 | 0.00 | 0.10 | 14-FEB-16:30 | 0.00 | 01-FEB-00:10 | 767.56 | 14-FEB-16:30 | 767.56 | 14-FEB-16:30 | 0.00 | 13-FEB-15:50 | 204.40 | 14-FEB-16:30 | 0.00 | 01-FEB-00:10 |
| March | 79258556.87 | 21164748.00 | 50.41 | 79258556.87 | -0.0 | 0.00 | 0.15 | 08-MAR-16:30 | 0.00 | 01-MAR-00:10 | 1126.95 | 08-MAR-16:30 | 1126.95 | 08-MAR-16:30 | 0.00 | 08-MAR-16:20 | 297.96 | 08-MAR-16:30 | 0.00 | 01-MAR-00:10 |
| April | 0.817478E+09 | 0.215572E+09 | 240.13 | 0.817478E+09 | 0.00 | 0.00 | 0.37 | 13-APR-16:27 | 0.00 | 01-APR-00:10 | 2892.51 | 13-APR-16:27 | 2892.51 | 13-APR-16:27 | 0.00 | 13-APR-15:20 | 758.70 | 13-APR-16:27 | 0.00 | 01-APR-00:10 |
| May | 0.180965E+10 | 0.479790E+09 | 396.38 | 0.180358E+10 | 6070240.61 | 0.00 | 0.48 | 19-MAY-16:40 | 0.00 | 01-MAY-00:10 | 3668.33 | 19-MAY-16:40 | 3668.33 | 19-MAY-16:40 | 128.10 | 23-MAY-15:10 | 1003.41 | 19-MAY-16:40 | 0.00 | 01-MAY-00:10 |
| June | 0.364953E+10 | 0.100480E+10 | 588.02 | 0.360914E+10 | 40385185.31 | 0.00 | 0.67 | 28-JUN-16:30 | 0.00 | 01-JUN-01:40 | 4723.53 | 28-JUN-16:30 | 4723.53 | 28-JUN-16:30 | 266.22 | 24-JUN-09:00 | 1420.84 | 28-JUN-16:30 | 0.00 | 01-JUN-00:10 |
| July | 0.478632E+10 | 0.130372E+10 | 730.36 | 0.444943E+10 | 0.336895E+09 | 0.00 | 0.64 | 21-JUL-17:10 | 0.00 | 02-JUL-02:40 | 4629.70 | 21-JUL-17:05 | 4629.70 | 21-JUL-17:05 | 642.42 | 01-JUL-13:50 | 1381.68 | 21-JUL-17:00 | 0.00 | 01-JUL-00:10 |
| August | 0.409764E+10 | 0.110079E+10 | 696.00 | 0.383280E+10 | 0.264842E+09 | 0.00 | 0.55 | 20-AUG-16:20 | 0.00 | 02-AUG-05:20 | 4198.69 | 20-AUG-16:15 | 4198.69 | 20-AUG-16:15 | 564.47 | 23-AUG-16:25 | 1211.41 | 20-AUG-16:15 | 0.00 | 01-AUG-00:10 |
| September | 0.228169E+10 | 0.604192E+09 | 501.59 | 0.219109E+10 | 90604994.72 | 0.00 | 0.45 | 02-SEP-16:30 | 0.00 | 01-SEP-07:00 | 3521.94 | 02-SEP-16:30 | 3521.94 | 02-SEP-16:30 | 494.61 | 05-SEP-13:10 | 974.36 | 02-SEP-16:30 | 0.00 | 01-SEP-00:10 |
| October | 0.714901E+09 | 0.188741E+09 | 209.83 | 0.700671E+09 | 14230668.57 | 0.00 | 0.35 | 06-OCT-16:10 | 0.00 | 01-OCT-01:30 | 2719.64 | 06-OCT-16:02 | 2719.64 | 06-OCT-16:02 | 227.26 | 02-OCT-18:00 | 731.36 | 06-OCT-16:05 | 0.00 | 01-OCT-00:10 |
| November | 579007.60 | 155719.74 | 2.36 | 579007.60 | 0.00 | 0.00 | 0.02 | 02-NOV-17:40 | 0.00 | 01-NOV-00:10 | 167.18 | 02-NOV-17:40 | 167.18 | 02-NOV-17:40 | 0.00 | 02-NOV-16:40 | 44.76 | 02-NOV-17:40 | 0.00 | 01-NOV-00:10 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.182542E+11 | 0.492353E+10 | 3429.54 | 0.175012E+11 | 0.753029E+09 | 0.00 | ||||||||||||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | -0.0 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Maximum of Months | 0.478632E+10 | 0.130372E+10 | 730.36 | 0.444943E+10 | 0.336895E+09 | 0.00 | 0.67 | 0.00 | 4723.53 | 4723.53 | 642.42 | 1420.84 | 0.00 |
Report: DXReportMonthly
For: SPLIT TSE COOLING COIL
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.357545E+09 | 94236649.89 | 114.88 | 0.357545E+09 | 0.00 | 0.00 | 0.28 | 23-JAN-14:20 | 0.00 | 01-JAN-00:10 | 1844.21 | 23-JAN-14:20 | 1844.21 | 23-JAN-14:20 | 0.00 | 01-JAN-16:00 | 477.82 | 23-JAN-14:20 | 0.00 | 01-JAN-00:10 |
| February | 0.426214E+09 | 0.111719E+09 | 126.09 | 0.426214E+09 | 0.00 | 0.00 | 0.37 | 14-FEB-14:40 | 0.00 | 01-FEB-00:10 | 2473.69 | 14-FEB-14:40 | 2473.69 | 14-FEB-14:40 | 0.00 | 09-FEB-15:30 | 631.84 | 14-FEB-14:40 | 0.00 | 01-FEB-00:10 |
| March | 0.615310E+09 | 0.161395E+09 | 180.75 | 0.615310E+09 | 0.00 | 0.00 | 0.38 | 08-MAR-14:00 | 0.00 | 01-MAR-00:10 | 2506.87 | 08-MAR-14:00 | 2506.87 | 08-MAR-14:00 | 0.00 | 08-MAR-14:10 | 639.84 | 08-MAR-14:00 | 0.00 | 01-MAR-00:10 |
| April | 0.147187E+10 | 0.383701E+09 | 345.95 | 0.147187E+10 | -0.0 | 0.00 | 0.44 | 28-APR-13:00 | 0.00 | 01-APR-00:10 | 2943.43 | 28-APR-13:00 | 2943.43 | 28-APR-13:00 | 0.00 | 26-APR-15:20 | 749.09 | 28-APR-13:00 | 0.00 | 01-APR-00:10 |
| May | 0.217276E+10 | 0.569636E+09 | 446.44 | 0.216098E+10 | 11774385.31 | 0.00 | 0.48 | 19-MAY-13:00 | 0.00 | 01-MAY-00:10 | 3161.57 | 19-MAY-13:00 | 3161.57 | 19-MAY-13:00 | 176.58 | 28-MAY-08:50 | 849.47 | 19-MAY-13:00 | 0.00 | 01-MAY-00:10 |
| June | 0.378973E+10 | 0.103235E+10 | 595.39 | 0.374250E+10 | 47237470.43 | 0.00 | 0.64 | 29-JUN-15:00 | 0.00 | 01-JUN-01:20 | 4031.29 | 29-JUN-14:40 | 4031.29 | 29-JUN-14:40 | 392.70 | 24-JUN-08:50 | 1199.60 | 29-JUN-15:00 | 0.00 | 01-JUN-00:10 |
| July | 0.520626E+10 | 0.139807E+10 | 732.02 | 0.484097E+10 | 0.365293E+09 | 0.00 | 0.67 | 22-JUL-14:00 | 0.00 | 02-JUL-02:50 | 4291.83 | 22-JUL-14:00 | 4291.83 | 22-JUL-14:00 | 675.17 | 01-JUL-14:00 | 1271.46 | 22-JUL-14:00 | 0.00 | 01-JUL-00:10 |
| August | 0.484965E+10 | 0.127964E+10 | 707.57 | 0.454361E+10 | 0.306039E+09 | 0.00 | 0.61 | 20-AUG-15:20 | 0.00 | 02-AUG-05:05 | 4087.17 | 17-AUG-13:30 | 4006.62 | 17-AUG-13:30 | 680.47 | 26-AUG-10:20 | 1142.65 | 20-AUG-15:20 | 0.00 | 01-AUG-00:10 |
| September | 0.343504E+10 | 0.888401E+09 | 549.33 | 0.331262E+10 | 0.122419E+09 | 0.00 | 0.63 | 03-SEP-13:30 | 0.00 | 02-SEP-03:30 | 4333.92 | 03-SEP-13:30 | 4283.68 | 03-SEP-13:30 | 581.58 | 05-SEP-13:00 | 1177.82 | 03-SEP-13:30 | 0.00 | 01-SEP-00:10 |
| October | 0.194467E+10 | 0.501563E+09 | 378.18 | 0.192071E+10 | 23962155.32 | 0.00 | 0.54 | 01-OCT-13:50 | 0.00 | 01-OCT-02:70 | 3728.00 | 01-OCT-13:40 | 3728.00 | 01-OCT-13:40 | 433.85 | 11-OCT-11:10 | 972.32 | 01-OCT-13:50 | 0.00 | 01-OCT-00:10 |
| November | 0.572822E+09 | 0.150395E+09 | 175.76 | 0.572822E+09 | 0.00 | 0.00 | 0.30 | 24-NOV-14:00 | 0.00 | 01-NOV-00:10 | 2007.17 | 24-NOV-14:00 | 2007.17 | 24-NOV-14:00 | 0.00 | 23-NOV-11:50 | 518.11 | 24-NOV-14:00 | 0.00 | 01-NOV-00:10 |
| December | 0.242019E+09 | 64134196.99 | 108.92 | 0.242019E+09 | -0.0 | 0.00 | 0.27 | 31-DEC-14:40 | 0.00 | 01-DEC-00:10 | 1755.78 | 31-DEC-14:40 | 1755.78 | 31-DEC-14:40 | 0.00 | 27-DEC-14:40 | 455.83 | 31-DEC-14:40 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.250839E+11 | 0.663524E+10 | 4461.29 | 0.242072E+11 | 0.876725E+09 | 0.00 | ||||||||||||||
| Minimum of Months | 0.242019E+09 | 64134196.99 | 108.92 | 0.242019E+09 | -0.0 | 0.00 | 0.27 | 0.00 | 1755.78 | 1755.78 | 0.00 | 455.83 | 0.00 | |||||||
| Maximum of Months | 0.520626E+10 | 0.139807E+10 | 732.02 | 0.484097E+10 | 0.365293E+09 | 0.00 | 0.67 | 0.00 | 4333.92 | 4291.83 | 680.47 | 1271.46 | 0.00 |
Report: DXReportMonthly
For: SPLIT TNE COOLING COIL
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| February | 2849735.20 | 767569.97 | 5.39 | 2849735.20 | -0.0 | 0.00 | 0.04 | 14-FEB-16:10 | 0.00 | 01-FEB-00:10 | 255.72 | 14-FEB-16:10 | 255.72 | 14-FEB-16:10 | 0.00 | 13-FEB-16:20 | 68.75 | 14-FEB-16:10 | 0.00 | 01-FEB-00:10 |
| March | 31195230.90 | 8360975.94 | 33.17 | 31195230.90 | -0.0 | 0.00 | 0.10 | 08-MAR-16:10 | 0.00 | 01-MAR-00:10 | 654.23 | 08-MAR-16:10 | 654.23 | 08-MAR-16:10 | 0.00 | 08-MAR-15:30 | 174.26 | 08-MAR-16:10 | 0.00 | 01-MAR-00:10 |
| April | 0.842579E+09 | 0.222132E+09 | 274.67 | 0.842579E+09 | 0.00 | 0.00 | 0.30 | 28-APR-15:10 | 0.00 | 01-APR-00:10 | 2011.09 | 28-APR-15:10 | 2011.09 | 28-APR-15:10 | 0.00 | 27-APR-14:30 | 527.19 | 28-APR-15:10 | 0.00 | 01-APR-00:10 |
| May | 0.190703E+10 | 0.502913E+09 | 434.14 | 0.189570E+10 | 11334008.68 | 0.00 | 0.41 | 19-MAY-16:30 | 0.00 | 01-MAY-00:10 | 2693.85 | 19-MAY-16:15 | 2693.85 | 19-MAY-16:15 | 167.78 | 29-MAY-07:45 | 744.86 | 19-MAY-16:30 | 0.00 | 01-MAY-00:10 |
| June | 0.381147E+10 | 0.103812E+10 | 602.93 | 0.376452E+10 | 46950216.16 | 0.00 | 0.61 | 28-JUN-16:10 | 0.00 | 01-JUN-01:20 | 3842.47 | 29-JUN-15:10 | 3842.47 | 29-JUN-15:10 | 375.81 | 24-JUN-08:50 | 1149.96 | 29-JUN-15:00 | 0.00 | 01-JUN-00:10 |
| July | 0.501904E+10 | 0.135040E+10 | 732.35 | 0.465625E+10 | 0.362787E+09 | 0.00 | 0.58 | 22-JUL-15:10 | 0.00 | 02-JUL-02:40 | 3691.82 | 22-JUL-15:10 | 3691.82 | 22-JUL-15:10 | 625.49 | 01-JUL-13:50 | 1114.58 | 22-JUL-15:10 | 0.00 | 01-JUL-00:10 |
| August | 0.427709E+10 | 0.113664E+10 | 701.06 | 0.398545E+10 | 0.291648E+09 | 0.00 | 0.51 | 20-AUG-16:10 | 0.00 | 02-AUG-05:05 | 3290.72 | 20-AUG-16:07 | 3290.72 | 20-AUG-16:07 | 582.78 | 26-AUG-10:30 | 958.26 | 20-AUG-16:07 | 0.00 | 01-AUG-00:10 |
| September | 0.233008E+10 | 0.613505E+09 | 520.55 | 0.223190E+10 | 98181332.63 | 0.00 | 0.44 | 03-SEP-14:00 | 0.00 | 02-SEP-03:20 | 2957.79 | 03-SEP-14:10 | 2943.09 | 03-SEP-14:00 | 477.05 | 05-SEP-13:00 | 839.68 | 03-SEP-14:00 | 0.00 | 01-SEP-00:10 |
| October | 0.655801E+09 | 0.172718E+09 | 226.70 | 0.638867E+09 | 16933156.64 | 0.00 | 0.32 | 01-OCT-15:20 | 0.00 | 01-OCT-01:30 | 2093.71 | 02-OCT-14:10 | 2092.26 | 01-OCT-15:20 | 271.47 | 11-OCT-11:10 | 571.21 | 01-OCT-15:20 | 0.00 | 01-OCT-00:10 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.188771E+11 | 0.504555E+10 | 3530.95 | 0.180493E+11 | 0.827834E+09 | 0.00 | ||||||||||||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | -0.0 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Maximum of Months | 0.501904E+10 | 0.135040E+10 | 732.35 | 0.465625E+10 | 0.362787E+09 | 0.00 | 0.61 | 0.00 | 3842.47 | 3842.47 | 625.49 | 1149.96 | 0.00 |
Report: DXReportMonthly
For: SPLIT TN1 COOLING COIL
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| February | 203237.61 | 54880.13 | 1.00 | 203237.61 | 0.00 | 0.00 | 0.01 | 14-FEB-16:10 | 0.00 | 01-FEB-00:10 | 84.45 | 14-FEB-16:10 | 84.45 | 14-FEB-16:10 | 0.00 | 14-FEB-16:20 | 22.79 | 14-FEB-16:10 | 0.00 | 01-FEB-00:10 |
| March | 9395014.32 | 2526480.71 | 16.08 | 9395014.32 | -0.0 | 0.00 | 0.06 | 08-MAR-16:10 | 0.00 | 01-MAR-00:10 | 377.96 | 08-MAR-16:10 | 377.96 | 08-MAR-16:10 | 0.00 | 08-MAR-16:00 | 101.25 | 08-MAR-16:10 | 0.00 | 01-MAR-00:10 |
| April | 0.519840E+09 | 0.137828E+09 | 217.17 | 0.519840E+09 | 0.00 | 0.00 | 0.26 | 13-APR-16:27 | 0.00 | 01-APR-00:10 | 1586.49 | 13-APR-16:27 | 1586.49 | 13-APR-16:27 | 0.00 | 27-APR-16:14 | 423.65 | 13-APR-16:27 | 0.00 | 01-APR-00:10 |
| May | 0.138637E+10 | 0.368693E+09 | 425.19 | 0.137862E+10 | 7757242.19 | 0.00 | 0.37 | 19-MAY-17:10 | 0.00 | 01-MAY-00:10 | 2222.49 | 19-MAY-17:10 | 2222.49 | 19-MAY-17:10 | 111.09 | 24-MAY-19:05 | 617.99 | 19-MAY-17:10 | 0.00 | 01-MAY-00:10 |
| June | 0.289528E+10 | 0.797433E+09 | 618.33 | 0.285591E+10 | 39372932.22 | 0.00 | 0.55 | 28-JUN-16:20 | 0.00 | 01-JUN-02:20 | 3027.39 | 28-JUN-16:30 | 3027.39 | 28-JUN-16:30 | 240.89 | 24-JUN-09:00 | 931.27 | 28-JUN-16:17 | 0.00 | 01-JUN-00:10 |
| July | 0.393649E+10 | 0.106847E+10 | 739.61 | 0.362259E+10 | 0.313904E+09 | 0.00 | 0.51 | 21-JUL-17:00 | 0.00 | 02-JUL-05:05 | 2943.55 | 22-JUL-15:10 | 2943.55 | 22-JUL-15:10 | 548.39 | 01-JUL-14:00 | 899.61 | 22-JUL-15:10 | 0.00 | 01-JUL-00:10 |
| August | 0.333473E+10 | 0.893988E+09 | 717.62 | 0.308695E+10 | 0.247778E+09 | 0.00 | 0.45 | 20-AUG-16:10 | 0.00 | 03-AUG-05:15 | 2690.80 | 20-AUG-16:05 | 2690.80 | 20-AUG-16:05 | 453.90 | 26-AUG-11:40 | 790.59 | 20-AUG-16:05 | 0.00 | 01-AUG-00:10 |
| September | 0.180402E+10 | 0.478043E+09 | 536.38 | 0.171925E+10 | 84771847.19 | 0.00 | 0.37 | 03-SEP-14:10 | 0.00 | 02-SEP-04:00 | 2297.34 | 03-SEP-14:10 | 2277.49 | 03-SEP-14:10 | 420.64 | 05-SEP-13:00 | 657.18 | 03-SEP-14:00 | 0.00 | 01-SEP-00:10 |
| October | 0.481543E+09 | 0.127419E+09 | 209.89 | 0.467613E+09 | 13930043.00 | 0.00 | 0.28 | 01-OCT-16:10 | 0.00 | 01-OCT-02:50 | 1736.55 | 01-OCT-16:10 | 1736.55 | 01-OCT-16:10 | 198.42 | 11-OCT-11:20 | 475.87 | 01-OCT-16:10 | 0.00 | 01-OCT-00:10 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.143679E+11 | 0.387446E+10 | 3481.27 | 0.136604E+11 | 0.707515E+09 | 0.00 | ||||||||||||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | -0.0 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Maximum of Months | 0.393649E+10 | 0.106847E+10 | 739.61 | 0.362259E+10 | 0.313904E+09 | 0.00 | 0.55 | 0.00 | 3027.39 | 3027.39 | 548.39 | 931.27 | 0.00 |
Report: DXReportMonthly
For: SPLIT TN2 COOLING COIL
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| February | 240302.32 | 64885.85 | 1.17 | 240302.32 | 0.00 | 0.00 | 0.02 | 14-FEB-16:10 | 0.00 | 01-FEB-00:10 | 90.54 | 14-FEB-16:10 | 90.54 | 14-FEB-16:10 | 0.00 | 14-FEB-16:10 | 24.43 | 14-FEB-16:10 | 0.00 | 01-FEB-00:10 |
| March | 10047102.47 | 2701378.01 | 16.33 | 10047102.47 | 0.00 | 0.00 | 0.06 | 08-MAR-16:10 | 0.00 | 01-MAR-00:10 | 383.21 | 08-MAR-16:10 | 383.21 | 08-MAR-16:10 | 0.00 | 08-MAR-16:30 | 102.64 | 08-MAR-16:10 | 0.00 | 01-MAR-00:10 |
| April | 0.529695E+09 | 0.140408E+09 | 221.92 | 0.529695E+09 | 0.00 | 0.00 | 0.26 | 13-APR-16:14 | 0.00 | 01-APR-00:10 | 1570.80 | 13-APR-16:14 | 1570.80 | 13-APR-16:14 | 0.00 | 29-APR-16:10 | 419.19 | 13-APR-16:27 | 0.00 | 01-APR-00:10 |
| May | 0.139747E+10 | 0.371503E+09 | 426.48 | 0.138940E+10 | 8067628.78 | 0.00 | 0.37 | 19-MAY-17:05 | 0.00 | 01-MAY-00:10 | 2197.78 | 19-MAY-17:05 | 2197.78 | 19-MAY-17:05 | 111.76 | 23-MAY-15:20 | 611.56 | 19-MAY-16:40 | 0.00 | 01-MAY-00:10 |
| June | 0.290512E+10 | 0.799789E+09 | 618.35 | 0.286549E+10 | 39632598.25 | 0.00 | 0.55 | 28-JUN-16:20 | 0.00 | 01-JUN-02:20 | 3024.54 | 29-JUN-15:10 | 3024.54 | 29-JUN-15:10 | 244.46 | 24-JUN-09:00 | 925.34 | 28-JUN-16:13 | 0.00 | 01-JUN-00:10 |
| July | 0.394682E+10 | 0.107082E+10 | 739.69 | 0.363205E+10 | 0.314771E+09 | 0.00 | 0.51 | 21-JUL-17:00 | 0.00 | 02-JUL-05:05 | 2937.84 | 22-JUL-15:10 | 2937.84 | 22-JUL-15:10 | 547.87 | 01-JUL-14:00 | 897.60 | 22-JUL-15:10 | 0.00 | 01-JUL-00:10 |
| August | 0.334344E+10 | 0.895969E+09 | 717.40 | 0.309480E+10 | 0.248641E+09 | 0.00 | 0.45 | 20-AUG-16:10 | 0.00 | 03-AUG-05:15 | 2675.60 | 20-AUG-16:07 | 2675.60 | 20-AUG-16:07 | 457.14 | 26-AUG-11:40 | 786.12 | 20-AUG-16:07 | 0.00 | 01-AUG-00:10 |
| September | 0.181074E+10 | 0.479691E+09 | 537.25 | 0.172565E+10 | 85099024.11 | 0.00 | 0.38 | 03-SEP-14:00 | 0.00 | 02-SEP-04:00 | 2302.49 | 03-SEP-14:10 | 2282.87 | 03-SEP-14:10 | 421.71 | 05-SEP-13:00 | 658.80 | 03-SEP-14:00 | 0.00 | 01-SEP-00:10 |
| October | 0.484907E+09 | 0.128280E+09 | 211.33 | 0.470846E+09 | 14060854.93 | 0.00 | 0.28 | 01-OCT-16:10 | 0.00 | 01-OCT-03:00 | 1726.91 | 01-OCT-16:10 | 1726.91 | 01-OCT-16:10 | 201.90 | 11-OCT-11:20 | 473.22 | 01-OCT-16:10 | 0.00 | 01-OCT-00:10 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.144285E+11 | 0.388923E+10 | 3489.92 | 0.137182E+11 | 0.710271E+09 | 0.00 | ||||||||||||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Maximum of Months | 0.394682E+10 | 0.107082E+10 | 739.69 | 0.363205E+10 | 0.314771E+09 | 0.00 | 0.55 | 0.00 | 3024.54 | 3024.54 | 547.87 | 925.34 | 0.00 |
Report: DXReportMonthly
For: SPLIT TS1 COOLING COIL
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.386577E+09 | 0.101612E+09 | 122.89 | 0.386577E+09 | 0.00 | 0.00 | 0.30 | 23-JAN-14:40 | 0.00 | 01-JAN-00:10 | 1835.58 | 23-JAN-14:40 | 1835.58 | 23-JAN-14:40 | 0.00 | 01-JAN-13:10 | 474.15 | 23-JAN-14:40 | 0.00 | 01-JAN-00:10 |
| February | 0.429926E+09 | 0.112738E+09 | 142.02 | 0.429926E+09 | -0.0 | 0.00 | 0.37 | 14-FEB-15:00 | 0.00 | 01-FEB-00:10 | 2290.60 | 14-FEB-15:00 | 2290.60 | 14-FEB-15:00 | 0.00 | 13-FEB-13:10 | 585.17 | 14-FEB-15:00 | 0.00 | 01-FEB-00:10 |
| March | 0.495425E+09 | 0.130252E+09 | 176.25 | 0.495425E+09 | -0.0 | 0.00 | 0.35 | 08-MAR-14:00 | 0.00 | 01-MAR-00:10 | 2169.09 | 08-MAR-14:00 | 2169.09 | 08-MAR-14:00 | 0.00 | 08-MAR-14:30 | 555.76 | 08-MAR-14:00 | 0.00 | 01-MAR-00:10 |
| April | 0.108598E+10 | 0.284661E+09 | 326.58 | 0.108598E+10 | -0.0 | 0.00 | 0.39 | 26-APR-14:10 | 0.00 | 01-APR-00:10 | 2380.45 | 26-APR-14:10 | 2380.45 | 26-APR-14:10 | 0.00 | 13-APR-16:14 | 621.00 | 26-APR-14:10 | 0.00 | 01-APR-00:10 |
| May | 0.164698E+10 | 0.435302E+09 | 437.30 | 0.163876E+10 | 8223852.52 | 0.00 | 0.42 | 19-MAY-15:10 | 0.00 | 01-MAY-00:10 | 2510.10 | 19-MAY-15:10 | 2510.10 | 19-MAY-15:10 | 113.40 | 28-MAY-10:20 | 692.98 | 19-MAY-15:10 | 0.00 | 01-MAY-00:10 |
| June | 0.287743E+10 | 0.792902E+09 | 604.27 | 0.283791E+10 | 39514031.86 | 0.00 | 0.57 | 28-JUN-16:10 | 0.00 | 01-JUN-02:20 | 3193.51 | 29-JUN-15:10 | 3193.51 | 29-JUN-15:10 | 264.72 | 24-JUN-10:00 | 964.64 | 29-JUN-15:00 | 0.00 | 01-JUN-00:10 |
| July | 0.412601E+10 | 0.111815E+10 | 738.76 | 0.380940E+10 | 0.316611E+09 | 0.00 | 0.58 | 22-JUL-14:10 | 0.00 | 02-JUL-05:05 | 3449.71 | 22-JUL-14:00 | 3449.71 | 22-JUL-14:00 | 597.62 | 01-JUL-14:00 | 1036.40 | 22-JUL-14:10 | 0.00 | 01-JUL-00:10 |
| August | 0.391612E+10 | 0.104222E+10 | 721.82 | 0.364997E+10 | 0.266148E+09 | 0.00 | 0.56 | 20-AUG-15:30 | 0.00 | 03-AUG-05:40 | 3358.31 | 20-AUG-15:20 | 3358.31 | 20-AUG-15:20 | 578.38 | 26-AUG-10:50 | 970.59 | 20-AUG-15:20 | 0.00 | 01-AUG-00:10 |
| September | 0.292303E+10 | 0.760484E+09 | 582.59 | 0.281036E+10 | 0.112664E+09 | 0.00 | 0.58 | 03-SEP-13:30 | 0.00 | 02-SEP-06:01 | 3636.42 | 03-SEP-13:30 | 3584.75 | 03-SEP-13:30 | 540.68 | 05-SEP-13:00 | 998.16 | 03-SEP-13:40 | 0.00 | 01-SEP-00:10 |
| October | 0.173385E+10 | 0.448580E+09 | 399.70 | 0.171192E+10 | 21929219.28 | 0.00 | 0.51 | 01-OCT-14:00 | 0.00 | 01-OCT-04:00 | 3268.61 | 01-OCT-13:50 | 3268.61 | 01-OCT-13:50 | 367.33 | 11-OCT-11:10 | 859.20 | 01-OCT-14:00 | 0.00 | 01-OCT-00:10 |
| November | 0.596578E+09 | 0.156395E+09 | 191.27 | 0.596578E+09 | -0.0 | 0.00 | 0.33 | 20-NOV-14:00 | 0.00 | 01-NOV-00:10 | 2008.37 | 20-NOV-14:00 | 2008.37 | 20-NOV-14:00 | 0.00 | 22-NOV-13:30 | 516.60 | 20-NOV-14:00 | 0.00 | 01-NOV-00:10 |
| December | 0.320841E+09 | 84736395.80 | 130.13 | 0.320841E+09 | 0.00 | 0.00 | 0.30 | 31-DEC-14:50 | 0.00 | 01-DEC-00:10 | 1843.27 | 31-DEC-14:50 | 1843.27 | 31-DEC-14:50 | 0.00 | 02-DEC-15:40 | 476.04 | 31-DEC-14:50 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.205388E+11 | 0.546804E+10 | 4573.59 | 0.197737E+11 | 0.765090E+09 | 0.00 | ||||||||||||||
| Minimum of Months | 0.320841E+09 | 84736395.80 | 122.89 | 0.320841E+09 | -0.0 | 0.00 | 0.30 | 0.00 | 1835.58 | 1835.58 | 0.00 | 474.15 | 0.00 | |||||||
| Maximum of Months | 0.412601E+10 | 0.111815E+10 | 738.76 | 0.380940E+10 | 0.316611E+09 | 0.00 | 0.58 | 0.00 | 3636.42 | 3584.75 | 597.62 | 1036.40 | 0.00 |
Report: DXReportMonthly
For: SPLIT TS2 COOLING COIL
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.391494E+09 | 0.102865E+09 | 123.22 | 0.391494E+09 | -0.0 | 0.00 | 0.30 | 23-JAN-14:40 | 0.00 | 01-JAN-00:10 | 1846.00 | 23-JAN-14:40 | 1846.00 | 23-JAN-14:40 | 0.00 | 08-JAN-13:50 | 476.59 | 23-JAN-14:40 | 0.00 | 01-JAN-00:10 |
| February | 0.434452E+09 | 0.113890E+09 | 142.58 | 0.434452E+09 | 0.00 | 0.00 | 0.37 | 14-FEB-14:50 | 0.00 | 01-FEB-00:10 | 2297.16 | 14-FEB-14:50 | 2297.16 | 14-FEB-14:50 | 0.00 | 18-FEB-14:30 | 586.56 | 14-FEB-14:50 | 0.00 | 01-FEB-00:10 |
| March | 0.503941E+09 | 0.132441E+09 | 176.99 | 0.503941E+09 | 0.00 | 0.00 | 0.36 | 08-MAR-14:00 | 0.00 | 01-MAR-00:10 | 2190.35 | 08-MAR-14:00 | 2190.35 | 08-MAR-14:00 | 0.00 | 08-MAR-16:00 | 560.74 | 08-MAR-14:00 | 0.00 | 01-MAR-00:10 |
| April | 0.110060E+10 | 0.288385E+09 | 329.72 | 0.110060E+10 | 0.00 | 0.00 | 0.39 | 26-APR-14:10 | 0.00 | 01-APR-00:10 | 2395.04 | 26-APR-14:10 | 2395.04 | 26-APR-14:10 | 0.00 | 26-APR-12:20 | 624.36 | 26-APR-14:10 | 0.00 | 01-APR-00:10 |
| May | 0.165891E+10 | 0.438254E+09 | 440.66 | 0.165039E+10 | 8520312.83 | 0.00 | 0.42 | 19-MAY-15:10 | 0.00 | 01-MAY-00:10 | 2507.56 | 19-MAY-15:10 | 2507.56 | 19-MAY-15:10 | 115.90 | 28-MAY-10:10 | 692.06 | 19-MAY-15:10 | 0.00 | 01-MAY-00:10 |
| June | 0.288794E+10 | 0.795406E+09 | 604.69 | 0.284816E+10 | 39783497.32 | 0.00 | 0.57 | 28-JUN-16:10 | 0.00 | 01-JUN-02:20 | 3192.90 | 29-JUN-14:40 | 3192.90 | 29-JUN-14:40 | 267.05 | 24-JUN-10:00 | 963.94 | 29-JUN-15:00 | 0.00 | 01-JUN-00:10 |
| July | 0.413649E+10 | 0.112047E+10 | 738.76 | 0.381901E+10 | 0.317482E+09 | 0.00 | 0.59 | 22-JUL-14:10 | 0.00 | 02-JUL-05:05 | 3459.44 | 22-JUL-14:00 | 3459.44 | 22-JUL-14:00 | 597.55 | 01-JUL-14:00 | 1037.99 | 22-JUL-14:10 | 0.00 | 01-JUL-00:10 |
| August | 0.392467E+10 | 0.104401E+10 | 721.29 | 0.365779E+10 | 0.266879E+09 | 0.00 | 0.56 | 20-AUG-15:20 | 0.00 | 03-AUG-05:40 | 3352.01 | 20-AUG-15:20 | 3352.01 | 20-AUG-15:20 | 581.65 | 26-AUG-10:50 | 968.45 | 20-AUG-15:20 | 0.00 | 01-AUG-00:10 |
| September | 0.292867E+10 | 0.761618E+09 | 582.57 | 0.281580E+10 | 0.112874E+09 | 0.00 | 0.58 | 03-SEP-13:30 | 0.00 | 02-SEP-06:01 | 3648.25 | 03-SEP-13:30 | 3596.82 | 03-SEP-13:30 | 540.81 | 05-SEP-13:00 | 1000.28 | 03-SEP-13:40 | 0.00 | 01-SEP-00:10 |
| October | 0.174132E+10 | 0.450345E+09 | 400.44 | 0.171930E+10 | 22025380.70 | 0.00 | 0.52 | 01-OCT-14:00 | 0.00 | 01-OCT-04:00 | 3277.95 | 01-OCT-13:50 | 3277.95 | 01-OCT-13:50 | 369.84 | 11-OCT-11:10 | 860.60 | 01-OCT-14:00 | 0.00 | 01-OCT-00:10 |
| November | 0.603084E+09 | 0.158044E+09 | 192.56 | 0.603084E+09 | -0.0 | 0.00 | 0.33 | 20-NOV-14:00 | 0.00 | 01-NOV-00:10 | 2018.93 | 20-NOV-14:00 | 2018.93 | 20-NOV-14:00 | 0.00 | 01-NOV-11:40 | 519.03 | 20-NOV-14:00 | 0.00 | 01-NOV-00:10 |
| December | 0.325432E+09 | 85924463.84 | 130.98 | 0.325432E+09 | 0.00 | 0.00 | 0.30 | 31-DEC-14:50 | 0.00 | 01-DEC-00:10 | 1847.31 | 31-DEC-14:50 | 1847.31 | 31-DEC-14:50 | 0.00 | 27-DEC-15:50 | 476.91 | 31-DEC-14:50 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.206370E+11 | 0.549165E+10 | 4584.48 | 0.198694E+11 | 0.767564E+09 | 0.00 | ||||||||||||||
| Minimum of Months | 0.325432E+09 | 85924463.84 | 123.22 | 0.325432E+09 | -0.0 | 0.00 | 0.30 | 0.00 | 1846.00 | 1846.00 | 0.00 | 476.59 | 0.00 | |||||||
| Maximum of Months | 0.413649E+10 | 0.112047E+10 | 738.76 | 0.381901E+10 | 0.317482E+09 | 0.00 | 0.59 | 0.00 | 3648.25 | 3596.82 | 597.55 | 1037.99 | 0.00 |
Report: WindowReportMonthly
For: GWINDOW1 S SWA
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 410.12 | 318.01 | 92.11 | 472.06 | 181.36 | 0.00 | 0.00 | 0.00 |
| February | 410.02 | 300.58 | 109.44 | 484.59 | 164.43 | 0.00 | 0.00 | 0.00 |
| March | 295.14 | 176.75 | 118.39 | 358.86 | 129.06 | 0.00 | 0.00 | 0.00 |
| April | 239.51 | 101.83 | 137.68 | 300.77 | 93.69 | 0.00 | 0.00 | 0.00 |
| May | 156.65 | 35.15 | 121.49 | 198.17 | 69.14 | 0.00 | 0.00 | 0.00 |
| June | 131.80 | 16.29 | 115.51 | 193.86 | 45.00 | 0.00 | 0.00 | 0.00 |
| July | 147.19 | 24.69 | 122.50 | 234.75 | 27.67 | 0.00 | 0.00 | 0.00 |
| August | 198.24 | 62.93 | 135.31 | 299.87 | 33.70 | 0.00 | 0.00 | 0.00 |
| September | 283.34 | 160.69 | 122.65 | 396.56 | 62.10 | 0.00 | 0.00 | 0.00 |
| October | 376.78 | 276.83 | 99.95 | 476.45 | 108.60 | 0.00 | 0.00 | 0.00 |
| November | 425.60 | 327.36 | 98.24 | 499.77 | 153.24 | 0.00 | 0.00 | 0.00 |
| December | 450.43 | 371.55 | 78.88 | 520.81 | 187.41 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 293.04 | 180.40 | 112.64 | 369.01 | 104.30 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 131.80 | 16.29 | 78.88 | 193.86 | 27.67 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 450.43 | 371.55 | 137.68 | 520.81 | 187.41 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: GWINDOW1 W SWA
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 105.42 | 60.07 | 45.35 | 99.26 | 130.42 | 0.00 | 0.00 | 0.00 |
| February | 135.35 | 78.04 | 57.32 | 138.57 | 115.79 | 0.00 | 0.00 | 0.00 |
| March | 151.79 | 80.82 | 70.98 | 167.18 | 87.35 | 0.00 | 0.00 | 0.00 |
| April | 193.39 | 102.78 | 90.61 | 227.23 | 60.27 | 0.00 | 0.00 | 0.00 |
| May | 184.31 | 95.23 | 89.08 | 229.03 | 44.60 | 0.00 | 0.00 | 0.00 |
| June | 196.47 | 109.49 | 86.99 | 272.25 | 29.62 | 0.00 | 0.00 | 0.00 |
| July | 177.53 | 86.89 | 90.64 | 257.17 | 18.15 | 0.00 | 0.00 | 0.00 |
| August | 181.20 | 83.66 | 97.54 | 252.56 | 22.11 | 0.00 | 0.00 | 0.00 |
| September | 164.41 | 86.78 | 77.63 | 215.41 | 41.09 | 0.00 | 0.00 | 0.00 |
| October | 149.77 | 93.04 | 56.74 | 173.94 | 76.70 | 0.00 | 0.00 | 0.00 |
| November | 117.49 | 69.04 | 48.45 | 114.80 | 109.03 | 0.00 | 0.00 | 0.00 |
| December | 101.63 | 63.68 | 37.95 | 93.17 | 135.70 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 154.92 | 84.09 | 70.83 | 186.88 | 72.35 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 101.63 | 60.07 | 37.95 | 93.17 | 18.15 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 196.47 | 109.49 | 97.54 | 272.25 | 135.70 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: GWINDOW1 W NWA
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 105.42 | 60.07 | 45.35 | 104.06 | 123.18 | 0.00 | 0.00 | 0.00 |
| February | 135.35 | 78.04 | 57.32 | 143.69 | 109.26 | 0.00 | 0.00 | 0.00 |
| March | 151.79 | 80.82 | 70.98 | 172.15 | 82.26 | 0.00 | 0.00 | 0.00 |
| April | 193.39 | 102.78 | 90.61 | 231.38 | 56.58 | 0.00 | 0.00 | 0.00 |
| May | 184.31 | 95.23 | 89.08 | 230.03 | 43.93 | 0.00 | 0.00 | 0.00 |
| June | 196.47 | 109.49 | 86.99 | 272.22 | 29.72 | 0.00 | 0.00 | 0.00 |
| July | 177.53 | 86.89 | 90.64 | 257.46 | 18.05 | 0.00 | 0.00 | 0.00 |
| August | 181.20 | 83.66 | 97.54 | 253.53 | 21.68 | 0.00 | 0.00 | 0.00 |
| September | 164.41 | 86.78 | 77.63 | 217.30 | 39.87 | 0.00 | 0.00 | 0.00 |
| October | 149.77 | 93.04 | 56.74 | 177.64 | 72.13 | 0.00 | 0.00 | 0.00 |
| November | 117.49 | 69.04 | 48.45 | 121.61 | 96.65 | 0.00 | 0.00 | 0.00 |
| December | 101.63 | 63.68 | 37.95 | 97.58 | 127.10 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 154.92 | 84.09 | 70.83 | 190.04 | 68.17 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 101.63 | 60.07 | 37.95 | 97.58 | 18.05 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 196.47 | 109.49 | 97.54 | 272.22 | 127.10 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: GWINDOW1 N NWA
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 56.16 | 0.00 | 56.16 | 15.87 | 194.32 | 0.00 | 0.00 | 0.00 |
| February | 70.19 | 0.00 | 70.19 | 32.19 | 171.06 | 0.00 | 0.00 | 0.00 |
| March | 88.56 | 0.01 | 88.56 | 66.48 | 127.44 | 0.00 | 0.00 | 0.00 |
| April | 112.57 | 1.18 | 111.39 | 100.66 | 85.05 | 0.00 | 0.00 | 0.00 |
| May | 122.40 | 8.09 | 114.30 | 131.22 | 64.06 | 0.00 | 0.00 | 0.00 |
| June | 138.81 | 22.80 | 116.01 | 195.39 | 41.99 | 0.00 | 0.00 | 0.00 |
| July | 127.08 | 10.32 | 116.76 | 193.38 | 26.37 | 0.00 | 0.00 | 0.00 |
| August | 118.60 | 3.09 | 115.50 | 164.33 | 31.64 | 0.00 | 0.00 | 0.00 |
| September | 94.55 | 0.06 | 94.49 | 111.00 | 60.85 | 0.00 | 0.00 | 0.00 |
| October | 70.49 | 0.00 | 70.49 | 51.47 | 112.10 | 0.00 | 0.00 | 0.00 |
| November | 59.87 | 0.00 | 59.87 | 21.79 | 153.51 | 0.00 | 0.00 | 0.00 |
| December | 47.80 | 0.00 | 47.80 | 5.53 | 204.16 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 92.34 | 3.80 | 88.53 | 91.08 | 105.74 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 47.80 | 0.00 | 47.80 | 5.53 | 26.37 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 138.81 | 22.80 | 116.76 | 195.39 | 204.16 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: GWINDOW1 S SEA
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 410.12 | 318.01 | 92.11 | 472.77 | 179.49 | 0.00 | 0.00 | 0.00 |
| February | 410.02 | 300.58 | 109.44 | 485.21 | 163.30 | 0.00 | 0.00 | 0.00 |
| March | 295.14 | 176.75 | 118.39 | 355.12 | 134.82 | 0.00 | 0.00 | 0.00 |
| April | 239.51 | 101.83 | 137.68 | 294.70 | 103.18 | 0.00 | 0.00 | 0.00 |
| May | 156.65 | 35.15 | 121.49 | 189.72 | 81.63 | 0.00 | 0.00 | 0.00 |
| June | 131.80 | 16.29 | 115.51 | 181.61 | 60.25 | 0.00 | 0.00 | 0.00 |
| July | 147.19 | 24.69 | 122.50 | 218.15 | 46.89 | 0.00 | 0.00 | 0.00 |
| August | 198.24 | 62.93 | 135.31 | 286.36 | 53.42 | 0.00 | 0.00 | 0.00 |
| September | 283.34 | 160.69 | 122.65 | 385.67 | 82.54 | 0.00 | 0.00 | 0.00 |
| October | 376.78 | 276.83 | 99.95 | 468.94 | 124.40 | 0.00 | 0.00 | 0.00 |
| November | 425.60 | 327.36 | 98.24 | 497.55 | 159.55 | 0.00 | 0.00 | 0.00 |
| December | 450.43 | 371.55 | 78.88 | 520.44 | 188.61 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 293.04 | 180.40 | 112.64 | 362.27 | 114.59 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 131.80 | 16.29 | 78.88 | 181.61 | 46.89 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 450.43 | 371.55 | 137.68 | 520.44 | 188.61 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: GWINDOW1 E SEA
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 103.21 | 58.09 | 45.12 | 90.14 | 122.65 | 0.00 | 0.00 | 0.00 |
| February | 123.18 | 65.96 | 57.22 | 118.59 | 109.89 | 0.00 | 0.00 | 0.00 |
| March | 164.71 | 93.76 | 70.94 | 178.35 | 86.04 | 0.00 | 0.00 | 0.00 |
| April | 224.10 | 127.72 | 96.38 | 263.19 | 63.21 | 0.00 | 0.00 | 0.00 |
| May | 213.71 | 121.73 | 91.98 | 262.59 | 50.74 | 0.00 | 0.00 | 0.00 |
| June | 230.63 | 142.13 | 88.50 | 307.51 | 36.30 | 0.00 | 0.00 | 0.00 |
| July | 213.62 | 122.28 | 91.33 | 293.97 | 29.14 | 0.00 | 0.00 | 0.00 |
| August | 210.67 | 115.98 | 94.69 | 281.31 | 32.89 | 0.00 | 0.00 | 0.00 |
| September | 175.55 | 98.09 | 77.46 | 220.27 | 51.96 | 0.00 | 0.00 | 0.00 |
| October | 153.47 | 97.54 | 55.94 | 169.72 | 82.44 | 0.00 | 0.00 | 0.00 |
| November | 119.37 | 70.10 | 49.26 | 112.44 | 110.24 | 0.00 | 0.00 | 0.00 |
| December | 97.03 | 59.16 | 37.87 | 84.10 | 133.49 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 169.28 | 97.84 | 71.44 | 198.87 | 75.58 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 97.03 | 58.09 | 37.87 | 84.10 | 29.14 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 230.63 | 142.13 | 96.38 | 307.51 | 133.49 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: GWINDOW1 E NEA
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 103.21 | 58.09 | 45.12 | 93.89 | 116.14 | 0.00 | 0.00 | 0.00 |
| February | 123.18 | 65.96 | 57.22 | 122.78 | 103.45 | 0.00 | 0.00 | 0.00 |
| March | 164.71 | 93.76 | 70.94 | 185.02 | 76.98 | 0.00 | 0.00 | 0.00 |
| April | 224.10 | 127.72 | 96.38 | 270.47 | 54.11 | 0.00 | 0.00 | 0.00 |
| May | 213.71 | 121.73 | 91.98 | 268.56 | 42.57 | 0.00 | 0.00 | 0.00 |
| June | 230.63 | 142.13 | 88.50 | 316.04 | 27.28 | 0.00 | 0.00 | 0.00 |
| July | 213.62 | 122.28 | 91.33 | 305.61 | 17.13 | 0.00 | 0.00 | 0.00 |
| August | 210.67 | 115.98 | 94.69 | 291.86 | 20.40 | 0.00 | 0.00 | 0.00 |
| September | 175.55 | 98.09 | 77.46 | 229.63 | 37.80 | 0.00 | 0.00 | 0.00 |
| October | 153.47 | 97.54 | 55.94 | 177.82 | 67.31 | 0.00 | 0.00 | 0.00 |
| November | 119.37 | 70.10 | 49.26 | 120.16 | 92.96 | 0.00 | 0.00 | 0.00 |
| December | 97.03 | 59.16 | 37.87 | 87.33 | 122.59 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 169.28 | 97.84 | 71.44 | 206.14 | 64.71 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 97.03 | 58.09 | 37.87 | 87.33 | 17.13 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 230.63 | 142.13 | 96.38 | 316.04 | 122.59 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: GWINDOW1 N NEA
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 56.16 | 0.00 | 56.16 | 15.65 | 194.02 | 0.00 | 0.00 | 0.00 |
| February | 70.19 | 0.00 | 70.19 | 31.99 | 170.39 | 0.00 | 0.00 | 0.00 |
| March | 88.56 | 0.01 | 88.56 | 65.74 | 127.25 | 0.00 | 0.00 | 0.00 |
| April | 112.57 | 1.18 | 111.39 | 98.45 | 85.26 | 0.00 | 0.00 | 0.00 |
| May | 122.40 | 8.09 | 114.30 | 129.44 | 64.29 | 0.00 | 0.00 | 0.00 |
| June | 138.81 | 22.80 | 116.01 | 194.29 | 41.86 | 0.00 | 0.00 | 0.00 |
| July | 127.08 | 10.32 | 116.76 | 192.45 | 26.36 | 0.00 | 0.00 | 0.00 |
| August | 118.60 | 3.09 | 115.50 | 163.51 | 31.50 | 0.00 | 0.00 | 0.00 |
| September | 94.55 | 0.06 | 94.49 | 110.43 | 60.61 | 0.00 | 0.00 | 0.00 |
| October | 70.49 | 0.00 | 70.49 | 50.72 | 111.96 | 0.00 | 0.00 | 0.00 |
| November | 59.87 | 0.00 | 59.87 | 21.31 | 152.91 | 0.00 | 0.00 | 0.00 |
| December | 47.80 | 0.00 | 47.80 | 5.38 | 203.83 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 92.34 | 3.80 | 88.53 | 90.25 | 105.55 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 47.80 | 0.00 | 47.80 | 5.38 | 26.36 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 138.81 | 22.80 | 116.76 | 194.29 | 203.83 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: GWINDOW1 N N1A
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 56.16 | 0.00 | 56.16 | 15.39 | 196.63 | 0.00 | 0.00 | 0.00 |
| February | 70.19 | 0.00 | 70.19 | 31.73 | 172.98 | 0.00 | 0.00 | 0.00 |
| March | 88.56 | 0.01 | 88.56 | 65.96 | 129.06 | 0.00 | 0.00 | 0.00 |
| April | 112.57 | 1.18 | 111.39 | 100.27 | 86.11 | 0.00 | 0.00 | 0.00 |
| May | 122.40 | 8.09 | 114.30 | 130.83 | 64.96 | 0.00 | 0.00 | 0.00 |
| June | 138.81 | 22.80 | 116.01 | 196.62 | 41.68 | 0.00 | 0.00 | 0.00 |
| July | 127.08 | 10.32 | 116.76 | 195.12 | 25.73 | 0.00 | 0.00 | 0.00 |
| August | 118.60 | 3.09 | 115.50 | 166.04 | 30.81 | 0.00 | 0.00 | 0.00 |
| September | 94.55 | 0.06 | 94.49 | 112.19 | 60.10 | 0.00 | 0.00 | 0.00 |
| October | 70.49 | 0.00 | 70.49 | 51.65 | 112.89 | 0.00 | 0.00 | 0.00 |
| November | 59.87 | 0.00 | 59.87 | 21.39 | 155.03 | 0.00 | 0.00 | 0.00 |
| December | 47.80 | 0.00 | 47.80 | 5.27 | 206.36 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 92.34 | 3.80 | 88.53 | 91.34 | 106.55 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 47.80 | 0.00 | 47.80 | 5.27 | 25.73 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 138.81 | 22.80 | 116.76 | 196.62 | 206.36 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: GWINDOW1 N N2A
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 56.16 | 0.00 | 56.16 | 15.38 | 196.61 | 0.00 | 0.00 | 0.00 |
| February | 70.19 | 0.00 | 70.19 | 31.73 | 172.94 | 0.00 | 0.00 | 0.00 |
| March | 88.56 | 0.01 | 88.56 | 65.91 | 129.07 | 0.00 | 0.00 | 0.00 |
| April | 112.57 | 1.18 | 111.39 | 100.09 | 86.21 | 0.00 | 0.00 | 0.00 |
| May | 122.40 | 8.09 | 114.30 | 130.69 | 65.04 | 0.00 | 0.00 | 0.00 |
| June | 138.81 | 22.80 | 116.01 | 196.57 | 41.69 | 0.00 | 0.00 | 0.00 |
| July | 127.08 | 10.32 | 116.76 | 195.09 | 25.74 | 0.00 | 0.00 | 0.00 |
| August | 118.60 | 3.09 | 115.50 | 166.01 | 30.81 | 0.00 | 0.00 | 0.00 |
| September | 94.55 | 0.06 | 94.49 | 112.17 | 60.09 | 0.00 | 0.00 | 0.00 |
| October | 70.49 | 0.00 | 70.49 | 51.61 | 112.92 | 0.00 | 0.00 | 0.00 |
| November | 59.87 | 0.00 | 59.87 | 21.37 | 155.01 | 0.00 | 0.00 | 0.00 |
| December | 47.80 | 0.00 | 47.80 | 5.27 | 206.34 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 92.34 | 3.80 | 88.53 | 91.29 | 106.56 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 47.80 | 0.00 | 47.80 | 5.27 | 25.74 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 138.81 | 22.80 | 116.76 | 196.57 | 206.34 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: GWINDOW1 S S1A
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 410.12 | 318.01 | 92.11 | 469.29 | 186.47 | 0.00 | 0.00 | 0.00 |
| February | 410.02 | 300.58 | 109.44 | 482.21 | 168.79 | 0.00 | 0.00 | 0.00 |
| March | 295.14 | 176.75 | 118.39 | 356.31 | 133.51 | 0.00 | 0.00 | 0.00 |
| April | 239.51 | 101.83 | 137.68 | 299.40 | 96.17 | 0.00 | 0.00 | 0.00 |
| May | 156.65 | 35.15 | 121.49 | 197.82 | 70.27 | 0.00 | 0.00 | 0.00 |
| June | 131.80 | 16.29 | 115.51 | 195.15 | 44.74 | 0.00 | 0.00 | 0.00 |
| July | 147.19 | 24.69 | 122.50 | 236.41 | 27.06 | 0.00 | 0.00 | 0.00 |
| August | 198.24 | 62.93 | 135.31 | 301.44 | 32.94 | 0.00 | 0.00 | 0.00 |
| September | 283.34 | 160.69 | 122.65 | 397.55 | 61.52 | 0.00 | 0.00 | 0.00 |
| October | 376.78 | 276.83 | 99.95 | 476.31 | 109.58 | 0.00 | 0.00 | 0.00 |
| November | 425.60 | 327.36 | 98.24 | 497.68 | 157.44 | 0.00 | 0.00 | 0.00 |
| December | 450.43 | 371.55 | 78.88 | 518.18 | 192.83 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 293.04 | 180.40 | 112.64 | 368.29 | 106.45 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 131.80 | 16.29 | 78.88 | 195.15 | 27.06 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 450.43 | 371.55 | 137.68 | 518.18 | 192.83 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: GWINDOW1 S S2A
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 410.12 | 318.01 | 92.11 | 469.29 | 186.39 | 0.00 | 0.00 | 0.00 |
| February | 410.02 | 300.58 | 109.44 | 482.20 | 168.75 | 0.00 | 0.00 | 0.00 |
| March | 295.14 | 176.75 | 118.39 | 355.80 | 134.17 | 0.00 | 0.00 | 0.00 |
| April | 239.51 | 101.83 | 137.68 | 298.71 | 97.00 | 0.00 | 0.00 | 0.00 |
| May | 156.65 | 35.15 | 121.49 | 197.14 | 71.00 | 0.00 | 0.00 | 0.00 |
| June | 131.80 | 16.29 | 115.51 | 194.45 | 45.35 | 0.00 | 0.00 | 0.00 |
| July | 147.19 | 24.69 | 122.50 | 235.57 | 27.77 | 0.00 | 0.00 | 0.00 |
| August | 198.24 | 62.93 | 135.31 | 300.71 | 33.65 | 0.00 | 0.00 | 0.00 |
| September | 283.34 | 160.69 | 122.65 | 397.00 | 62.24 | 0.00 | 0.00 | 0.00 |
| October | 376.78 | 276.83 | 99.95 | 475.85 | 110.26 | 0.00 | 0.00 | 0.00 |
| November | 425.60 | 327.36 | 98.24 | 497.40 | 157.85 | 0.00 | 0.00 | 0.00 |
| December | 450.43 | 371.55 | 78.88 | 518.07 | 192.95 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 293.04 | 180.40 | 112.64 | 367.82 | 106.96 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 131.80 | 16.29 | 78.88 | 194.45 | 27.77 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 450.43 | 371.55 | 137.68 | 518.07 | 192.95 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MWINDOW1 S SWA
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 410.12 | 318.01 | 92.11 | 466.22 | 188.44 | 0.00 | 0.00 | 0.00 |
| February | 410.02 | 300.58 | 109.44 | 477.04 | 173.86 | 0.00 | 0.00 | 0.00 |
| March | 295.14 | 176.75 | 118.39 | 349.29 | 142.08 | 0.00 | 0.00 | 0.00 |
| April | 239.51 | 101.83 | 137.68 | 293.33 | 102.18 | 0.00 | 0.00 | 0.00 |
| May | 156.65 | 35.15 | 121.49 | 193.83 | 73.29 | 0.00 | 0.00 | 0.00 |
| June | 131.80 | 16.29 | 115.51 | 192.30 | 46.15 | 0.00 | 0.00 | 0.00 |
| July | 147.19 | 24.69 | 122.50 | 234.16 | 27.64 | 0.00 | 0.00 | 0.00 |
| August | 198.24 | 62.93 | 135.31 | 299.34 | 33.29 | 0.00 | 0.00 | 0.00 |
| September | 283.34 | 160.69 | 122.65 | 395.84 | 61.29 | 0.00 | 0.00 | 0.00 |
| October | 376.78 | 276.83 | 99.95 | 475.43 | 107.72 | 0.00 | 0.00 | 0.00 |
| November | 425.60 | 327.36 | 98.24 | 497.65 | 153.86 | 0.00 | 0.00 | 0.00 |
| December | 450.43 | 371.55 | 78.88 | 516.03 | 192.74 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 293.04 | 180.40 | 112.64 | 365.19 | 108.20 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 131.80 | 16.29 | 78.88 | 192.30 | 27.64 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 450.43 | 371.55 | 137.68 | 516.03 | 192.74 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MWINDOW1 W SWA
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 105.42 | 60.07 | 45.35 | 96.60 | 135.99 | 0.00 | 0.00 | 0.00 |
| February | 135.35 | 78.04 | 57.32 | 134.53 | 122.88 | 0.00 | 0.00 | 0.00 |
| March | 151.79 | 80.82 | 70.98 | 161.26 | 96.29 | 0.00 | 0.00 | 0.00 |
| April | 193.39 | 102.78 | 90.61 | 222.10 | 65.72 | 0.00 | 0.00 | 0.00 |
| May | 184.31 | 95.23 | 89.08 | 225.77 | 47.24 | 0.00 | 0.00 | 0.00 |
| June | 196.47 | 109.49 | 86.99 | 270.90 | 30.41 | 0.00 | 0.00 | 0.00 |
| July | 177.53 | 86.89 | 90.64 | 256.58 | 18.15 | 0.00 | 0.00 | 0.00 |
| August | 181.20 | 83.66 | 97.54 | 252.18 | 21.88 | 0.00 | 0.00 | 0.00 |
| September | 164.41 | 86.78 | 77.63 | 215.14 | 40.60 | 0.00 | 0.00 | 0.00 |
| October | 149.77 | 93.04 | 56.74 | 173.50 | 76.16 | 0.00 | 0.00 | 0.00 |
| November | 117.49 | 69.04 | 48.45 | 113.85 | 109.67 | 0.00 | 0.00 | 0.00 |
| December | 101.63 | 63.68 | 37.95 | 91.23 | 140.19 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 154.92 | 84.09 | 70.83 | 184.65 | 75.19 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 101.63 | 60.07 | 37.95 | 91.23 | 18.15 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 196.47 | 109.49 | 97.54 | 270.90 | 140.19 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MWINDOW1 W NWA
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 105.42 | 60.07 | 45.35 | 102.01 | 127.50 | 0.00 | 0.00 | 0.00 |
| February | 135.35 | 78.04 | 57.32 | 140.50 | 114.95 | 0.00 | 0.00 | 0.00 |
| March | 151.79 | 80.82 | 70.98 | 166.51 | 90.05 | 0.00 | 0.00 | 0.00 |
| April | 193.39 | 102.78 | 90.61 | 224.38 | 64.07 | 0.00 | 0.00 | 0.00 |
| May | 184.31 | 95.23 | 89.08 | 226.37 | 47.01 | 0.00 | 0.00 | 0.00 |
| June | 196.47 | 109.49 | 86.99 | 270.89 | 30.50 | 0.00 | 0.00 | 0.00 |
| July | 177.53 | 86.89 | 90.64 | 256.86 | 18.08 | 0.00 | 0.00 | 0.00 |
| August | 181.20 | 83.66 | 97.54 | 253.07 | 21.58 | 0.00 | 0.00 | 0.00 |
| September | 164.41 | 86.78 | 77.63 | 216.87 | 39.74 | 0.00 | 0.00 | 0.00 |
| October | 149.77 | 93.04 | 56.74 | 177.19 | 72.21 | 0.00 | 0.00 | 0.00 |
| November | 117.49 | 69.04 | 48.45 | 120.40 | 98.63 | 0.00 | 0.00 | 0.00 |
| December | 101.63 | 63.68 | 37.95 | 96.37 | 130.26 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 154.92 | 84.09 | 70.83 | 187.78 | 71.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 101.63 | 60.07 | 37.95 | 96.37 | 18.08 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 196.47 | 109.49 | 97.54 | 270.89 | 130.26 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MWINDOW1 N NWA
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 56.16 | 0.00 | 56.16 | 14.10 | 201.59 | 0.00 | 0.00 | 0.00 |
| February | 70.19 | 0.00 | 70.19 | 28.83 | 180.43 | 0.00 | 0.00 | 0.00 |
| March | 88.56 | 0.01 | 88.56 | 59.62 | 140.05 | 0.00 | 0.00 | 0.00 |
| April | 112.57 | 1.18 | 111.39 | 91.22 | 96.65 | 0.00 | 0.00 | 0.00 |
| May | 122.40 | 8.09 | 114.30 | 125.94 | 68.36 | 0.00 | 0.00 | 0.00 |
| June | 138.81 | 22.80 | 116.01 | 193.65 | 43.02 | 0.00 | 0.00 | 0.00 |
| July | 127.08 | 10.32 | 116.76 | 192.96 | 26.38 | 0.00 | 0.00 | 0.00 |
| August | 118.60 | 3.09 | 115.50 | 164.17 | 31.44 | 0.00 | 0.00 | 0.00 |
| September | 94.55 | 0.06 | 94.49 | 110.97 | 60.59 | 0.00 | 0.00 | 0.00 |
| October | 70.49 | 0.00 | 70.49 | 51.44 | 112.14 | 0.00 | 0.00 | 0.00 |
| November | 59.87 | 0.00 | 59.87 | 20.81 | 156.83 | 0.00 | 0.00 | 0.00 |
| December | 47.80 | 0.00 | 47.80 | 4.87 | 209.61 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 92.34 | 3.80 | 88.53 | 88.53 | 110.25 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 47.80 | 0.00 | 47.80 | 4.87 | 26.38 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 138.81 | 22.80 | 116.76 | 193.65 | 209.61 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MWINDOW1 S SEA
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 410.12 | 318.01 | 92.11 | 465.34 | 188.05 | 0.00 | 0.00 | 0.00 |
| February | 410.02 | 300.58 | 109.44 | 476.28 | 172.95 | 0.00 | 0.00 | 0.00 |
| March | 295.14 | 176.75 | 118.39 | 347.75 | 142.00 | 0.00 | 0.00 | 0.00 |
| April | 239.51 | 101.83 | 137.68 | 291.98 | 102.00 | 0.00 | 0.00 | 0.00 |
| May | 156.65 | 35.15 | 121.49 | 192.63 | 73.18 | 0.00 | 0.00 | 0.00 |
| June | 131.80 | 16.29 | 115.51 | 191.38 | 45.95 | 0.00 | 0.00 | 0.00 |
| July | 147.19 | 24.69 | 122.50 | 233.33 | 27.52 | 0.00 | 0.00 | 0.00 |
| August | 198.24 | 62.93 | 135.31 | 298.60 | 33.09 | 0.00 | 0.00 | 0.00 |
| September | 283.34 | 160.69 | 122.65 | 395.30 | 60.97 | 0.00 | 0.00 | 0.00 |
| October | 376.78 | 276.83 | 99.95 | 474.71 | 107.30 | 0.00 | 0.00 | 0.00 |
| November | 425.60 | 327.36 | 98.24 | 496.76 | 153.41 | 0.00 | 0.00 | 0.00 |
| December | 450.43 | 371.55 | 78.88 | 515.12 | 192.19 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 293.04 | 180.40 | 112.64 | 364.25 | 107.88 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 131.80 | 16.29 | 78.88 | 191.38 | 27.52 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 450.43 | 371.55 | 137.68 | 515.12 | 192.19 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MWINDOW1 E SEA
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 103.21 | 58.09 | 45.12 | 86.53 | 129.27 | 0.00 | 0.00 | 0.00 |
| February | 123.18 | 65.96 | 57.22 | 113.74 | 117.02 | 0.00 | 0.00 | 0.00 |
| March | 164.71 | 93.76 | 70.94 | 173.51 | 90.65 | 0.00 | 0.00 | 0.00 |
| April | 224.10 | 127.72 | 96.38 | 261.29 | 62.34 | 0.00 | 0.00 | 0.00 |
| May | 213.71 | 121.73 | 91.98 | 264.58 | 45.44 | 0.00 | 0.00 | 0.00 |
| June | 230.63 | 142.13 | 88.50 | 314.63 | 27.79 | 0.00 | 0.00 | 0.00 |
| July | 213.62 | 122.28 | 91.33 | 304.75 | 17.13 | 0.00 | 0.00 | 0.00 |
| August | 210.67 | 115.98 | 94.69 | 290.46 | 20.51 | 0.00 | 0.00 | 0.00 |
| September | 175.55 | 98.09 | 77.46 | 227.49 | 38.47 | 0.00 | 0.00 | 0.00 |
| October | 153.47 | 97.54 | 55.94 | 173.60 | 71.02 | 0.00 | 0.00 | 0.00 |
| November | 119.37 | 70.10 | 49.26 | 112.27 | 106.31 | 0.00 | 0.00 | 0.00 |
| December | 97.03 | 59.16 | 37.87 | 82.13 | 137.17 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 169.28 | 97.84 | 71.44 | 200.81 | 71.70 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 97.03 | 58.09 | 37.87 | 82.13 | 17.13 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 230.63 | 142.13 | 96.38 | 314.63 | 137.17 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MWINDOW1 E NEA
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 103.21 | 58.09 | 45.12 | 91.75 | 120.10 | 0.00 | 0.00 | 0.00 |
| February | 123.18 | 65.96 | 57.22 | 119.50 | 108.69 | 0.00 | 0.00 | 0.00 |
| March | 164.71 | 93.76 | 70.94 | 178.74 | 84.63 | 0.00 | 0.00 | 0.00 |
| April | 224.10 | 127.72 | 96.38 | 263.24 | 60.92 | 0.00 | 0.00 | 0.00 |
| May | 213.71 | 121.73 | 91.98 | 265.11 | 45.22 | 0.00 | 0.00 | 0.00 |
| June | 230.63 | 142.13 | 88.50 | 314.62 | 27.84 | 0.00 | 0.00 | 0.00 |
| July | 213.62 | 122.28 | 91.33 | 305.03 | 17.05 | 0.00 | 0.00 | 0.00 |
| August | 210.67 | 115.98 | 94.69 | 291.35 | 20.21 | 0.00 | 0.00 | 0.00 |
| September | 175.55 | 98.09 | 77.46 | 229.23 | 37.61 | 0.00 | 0.00 | 0.00 |
| October | 153.47 | 97.54 | 55.94 | 177.31 | 67.31 | 0.00 | 0.00 | 0.00 |
| November | 119.37 | 70.10 | 49.26 | 118.81 | 94.79 | 0.00 | 0.00 | 0.00 |
| December | 97.03 | 59.16 | 37.87 | 86.08 | 125.61 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 169.28 | 97.84 | 71.44 | 203.78 | 67.29 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 97.03 | 58.09 | 37.87 | 86.08 | 17.05 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 230.63 | 142.13 | 96.38 | 314.62 | 125.61 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MWINDOW1 N NEA
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 56.16 | 0.00 | 56.16 | 13.83 | 200.97 | 0.00 | 0.00 | 0.00 |
| February | 70.19 | 0.00 | 70.19 | 28.43 | 179.43 | 0.00 | 0.00 | 0.00 |
| March | 88.56 | 0.01 | 88.56 | 58.00 | 140.14 | 0.00 | 0.00 | 0.00 |
| April | 112.57 | 1.18 | 111.39 | 89.24 | 96.76 | 0.00 | 0.00 | 0.00 |
| May | 122.40 | 8.09 | 114.30 | 124.53 | 68.22 | 0.00 | 0.00 | 0.00 |
| June | 138.81 | 22.80 | 116.01 | 192.64 | 42.74 | 0.00 | 0.00 | 0.00 |
| July | 127.08 | 10.32 | 116.76 | 192.09 | 26.24 | 0.00 | 0.00 | 0.00 |
| August | 118.60 | 3.09 | 115.50 | 163.36 | 31.21 | 0.00 | 0.00 | 0.00 |
| September | 94.55 | 0.06 | 94.49 | 110.38 | 60.30 | 0.00 | 0.00 | 0.00 |
| October | 70.49 | 0.00 | 70.49 | 50.52 | 111.95 | 0.00 | 0.00 | 0.00 |
| November | 59.87 | 0.00 | 59.87 | 20.14 | 156.01 | 0.00 | 0.00 | 0.00 |
| December | 47.80 | 0.00 | 47.80 | 4.69 | 209.13 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 92.34 | 3.80 | 88.53 | 87.63 | 109.92 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 47.80 | 0.00 | 47.80 | 4.69 | 26.24 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 138.81 | 22.80 | 116.76 | 192.64 | 209.13 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MWINDOW1 N N1A
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 56.16 | 0.00 | 56.16 | 13.69 | 203.59 | 0.00 | 0.00 | 0.00 |
| February | 70.19 | 0.00 | 70.19 | 28.64 | 181.75 | 0.00 | 0.00 | 0.00 |
| March | 88.56 | 0.01 | 88.56 | 58.99 | 142.22 | 0.00 | 0.00 | 0.00 |
| April | 112.57 | 1.18 | 111.39 | 91.44 | 97.37 | 0.00 | 0.00 | 0.00 |
| May | 122.40 | 8.09 | 114.30 | 126.76 | 68.30 | 0.00 | 0.00 | 0.00 |
| June | 138.81 | 22.80 | 116.01 | 195.49 | 42.36 | 0.00 | 0.00 | 0.00 |
| July | 127.08 | 10.32 | 116.76 | 195.02 | 25.64 | 0.00 | 0.00 | 0.00 |
| August | 118.60 | 3.09 | 115.50 | 166.05 | 30.64 | 0.00 | 0.00 | 0.00 |
| September | 94.55 | 0.06 | 94.49 | 112.18 | 60.01 | 0.00 | 0.00 | 0.00 |
| October | 70.49 | 0.00 | 70.49 | 51.42 | 113.55 | 0.00 | 0.00 | 0.00 |
| November | 59.87 | 0.00 | 59.87 | 20.11 | 159.29 | 0.00 | 0.00 | 0.00 |
| December | 47.80 | 0.00 | 47.80 | 4.59 | 212.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 92.34 | 3.80 | 88.53 | 89.02 | 111.05 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 47.80 | 0.00 | 47.80 | 4.59 | 25.64 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 138.81 | 22.80 | 116.76 | 195.49 | 212.00 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MWINDOW1 N N2A
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 56.16 | 0.00 | 56.16 | 13.67 | 203.55 | 0.00 | 0.00 | 0.00 |
| February | 70.19 | 0.00 | 70.19 | 28.62 | 181.69 | 0.00 | 0.00 | 0.00 |
| March | 88.56 | 0.01 | 88.56 | 58.85 | 142.36 | 0.00 | 0.00 | 0.00 |
| April | 112.57 | 1.18 | 111.39 | 91.31 | 97.44 | 0.00 | 0.00 | 0.00 |
| May | 122.40 | 8.09 | 114.30 | 126.68 | 68.32 | 0.00 | 0.00 | 0.00 |
| June | 138.81 | 22.80 | 116.01 | 195.45 | 42.35 | 0.00 | 0.00 | 0.00 |
| July | 127.08 | 10.32 | 116.76 | 194.99 | 25.64 | 0.00 | 0.00 | 0.00 |
| August | 118.60 | 3.09 | 115.50 | 166.02 | 30.63 | 0.00 | 0.00 | 0.00 |
| September | 94.55 | 0.06 | 94.49 | 112.16 | 60.00 | 0.00 | 0.00 | 0.00 |
| October | 70.49 | 0.00 | 70.49 | 51.37 | 113.57 | 0.00 | 0.00 | 0.00 |
| November | 59.87 | 0.00 | 59.87 | 20.08 | 159.25 | 0.00 | 0.00 | 0.00 |
| December | 47.80 | 0.00 | 47.80 | 4.58 | 211.97 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 92.34 | 3.80 | 88.53 | 88.97 | 111.06 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 47.80 | 0.00 | 47.80 | 4.58 | 25.64 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 138.81 | 22.80 | 116.76 | 195.45 | 211.97 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MWINDOW1 S S1A
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 410.12 | 318.01 | 92.11 | 463.40 | 194.30 | 0.00 | 0.00 | 0.00 |
| February | 410.02 | 300.58 | 109.44 | 474.72 | 178.87 | 0.00 | 0.00 | 0.00 |
| March | 295.14 | 176.75 | 118.39 | 347.47 | 146.04 | 0.00 | 0.00 | 0.00 |
| April | 239.51 | 101.83 | 137.68 | 293.57 | 102.84 | 0.00 | 0.00 | 0.00 |
| May | 156.65 | 35.15 | 121.49 | 194.65 | 73.23 | 0.00 | 0.00 | 0.00 |
| June | 131.80 | 16.29 | 115.51 | 194.18 | 45.47 | 0.00 | 0.00 | 0.00 |
| July | 147.19 | 24.69 | 122.50 | 236.17 | 26.89 | 0.00 | 0.00 | 0.00 |
| August | 198.24 | 62.93 | 135.31 | 301.11 | 32.52 | 0.00 | 0.00 | 0.00 |
| September | 283.34 | 160.69 | 122.65 | 396.90 | 60.81 | 0.00 | 0.00 | 0.00 |
| October | 376.78 | 276.83 | 99.95 | 475.24 | 109.06 | 0.00 | 0.00 | 0.00 |
| November | 425.60 | 327.36 | 98.24 | 495.60 | 158.28 | 0.00 | 0.00 | 0.00 |
| December | 450.43 | 371.55 | 78.88 | 513.18 | 199.27 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 293.04 | 180.40 | 112.64 | 364.84 | 110.28 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 131.80 | 16.29 | 78.88 | 194.18 | 26.89 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 450.43 | 371.55 | 137.68 | 513.18 | 199.27 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MWINDOW1 S S2A
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 410.12 | 318.01 | 92.11 | 463.36 | 194.30 | 0.00 | 0.00 | 0.00 |
| February | 410.02 | 300.58 | 109.44 | 474.70 | 178.80 | 0.00 | 0.00 | 0.00 |
| March | 295.14 | 176.75 | 118.39 | 347.39 | 146.08 | 0.00 | 0.00 | 0.00 |
| April | 239.51 | 101.83 | 137.68 | 293.51 | 102.84 | 0.00 | 0.00 | 0.00 |
| May | 156.65 | 35.15 | 121.49 | 194.60 | 73.24 | 0.00 | 0.00 | 0.00 |
| June | 131.80 | 16.29 | 115.51 | 194.15 | 45.46 | 0.00 | 0.00 | 0.00 |
| July | 147.19 | 24.69 | 122.50 | 236.14 | 26.89 | 0.00 | 0.00 | 0.00 |
| August | 198.24 | 62.93 | 135.31 | 301.09 | 32.51 | 0.00 | 0.00 | 0.00 |
| September | 283.34 | 160.69 | 122.65 | 396.89 | 60.80 | 0.00 | 0.00 | 0.00 |
| October | 376.78 | 276.83 | 99.95 | 475.22 | 109.05 | 0.00 | 0.00 | 0.00 |
| November | 425.60 | 327.36 | 98.24 | 495.57 | 158.27 | 0.00 | 0.00 | 0.00 |
| December | 450.43 | 371.55 | 78.88 | 513.14 | 199.24 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 293.04 | 180.40 | 112.64 | 364.81 | 110.27 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 131.80 | 16.29 | 78.88 | 194.15 | 26.89 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 450.43 | 371.55 | 137.68 | 513.14 | 199.24 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: TWINDOW1 S SWA
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 410.12 | 318.01 | 92.11 | 466.78 | 177.97 | 0.00 | 0.00 | 0.00 |
| February | 410.02 | 300.58 | 109.44 | 476.76 | 163.68 | 0.00 | 0.00 | 0.00 |
| March | 295.14 | 176.75 | 118.39 | 350.82 | 130.52 | 0.00 | 0.00 | 0.00 |
| April | 239.51 | 101.83 | 137.68 | 294.10 | 92.95 | 0.00 | 0.00 | 0.00 |
| May | 156.65 | 35.15 | 121.49 | 193.25 | 67.74 | 0.00 | 0.00 | 0.00 |
| June | 131.80 | 16.29 | 115.51 | 188.94 | 43.76 | 0.00 | 0.00 | 0.00 |
| July | 147.19 | 24.69 | 122.50 | 229.45 | 26.91 | 0.00 | 0.00 | 0.00 |
| August | 198.24 | 62.93 | 135.31 | 294.77 | 32.32 | 0.00 | 0.00 | 0.00 |
| September | 283.34 | 160.69 | 122.65 | 392.67 | 58.36 | 0.00 | 0.00 | 0.00 |
| October | 376.78 | 276.83 | 99.95 | 475.88 | 99.05 | 0.00 | 0.00 | 0.00 |
| November | 425.60 | 327.36 | 98.24 | 499.87 | 140.09 | 0.00 | 0.00 | 0.00 |
| December | 450.43 | 371.55 | 78.88 | 516.08 | 181.79 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 293.04 | 180.40 | 112.64 | 364.26 | 100.94 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 131.80 | 16.29 | 78.88 | 188.94 | 26.91 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 450.43 | 371.55 | 137.68 | 516.08 | 181.79 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: TWINDOW1 W SWA
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 105.42 | 60.07 | 45.35 | 95.87 | 127.88 | 0.00 | 0.00 | 0.00 |
| February | 135.35 | 78.04 | 57.32 | 133.38 | 115.17 | 0.00 | 0.00 | 0.00 |
| March | 151.79 | 80.82 | 70.98 | 161.48 | 87.86 | 0.00 | 0.00 | 0.00 |
| April | 193.39 | 102.78 | 90.61 | 222.30 | 59.37 | 0.00 | 0.00 | 0.00 |
| May | 184.31 | 95.23 | 89.08 | 225.24 | 43.49 | 0.00 | 0.00 | 0.00 |
| June | 196.47 | 109.49 | 86.99 | 268.56 | 28.79 | 0.00 | 0.00 | 0.00 |
| July | 177.53 | 86.89 | 90.64 | 253.36 | 17.63 | 0.00 | 0.00 | 0.00 |
| August | 181.20 | 83.66 | 97.54 | 249.14 | 21.20 | 0.00 | 0.00 | 0.00 |
| September | 164.41 | 86.78 | 77.63 | 212.94 | 38.47 | 0.00 | 0.00 | 0.00 |
| October | 149.77 | 93.04 | 56.74 | 172.61 | 69.18 | 0.00 | 0.00 | 0.00 |
| November | 117.49 | 69.04 | 48.45 | 113.72 | 98.93 | 0.00 | 0.00 | 0.00 |
| December | 101.63 | 63.68 | 37.95 | 90.12 | 131.80 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 154.92 | 84.09 | 70.83 | 183.41 | 69.76 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 101.63 | 60.07 | 37.95 | 90.12 | 17.63 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 196.47 | 109.49 | 97.54 | 268.56 | 131.80 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: TWINDOW1 W NWA
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 105.42 | 60.07 | 45.35 | 102.18 | 122.60 | 0.00 | 0.00 | 0.00 |
| February | 135.35 | 78.04 | 57.32 | 140.21 | 110.43 | 0.00 | 0.00 | 0.00 |
| March | 151.79 | 80.82 | 70.98 | 166.46 | 85.07 | 0.00 | 0.00 | 0.00 |
| April | 193.39 | 102.78 | 90.61 | 225.43 | 58.16 | 0.00 | 0.00 | 0.00 |
| May | 184.31 | 95.23 | 89.08 | 226.05 | 43.33 | 0.00 | 0.00 | 0.00 |
| June | 196.47 | 109.49 | 86.99 | 268.46 | 28.97 | 0.00 | 0.00 | 0.00 |
| July | 177.53 | 86.89 | 90.64 | 253.73 | 17.62 | 0.00 | 0.00 | 0.00 |
| August | 181.20 | 83.66 | 97.54 | 250.36 | 20.99 | 0.00 | 0.00 | 0.00 |
| September | 164.41 | 86.78 | 77.63 | 215.62 | 37.59 | 0.00 | 0.00 | 0.00 |
| October | 149.77 | 93.04 | 56.74 | 178.15 | 65.88 | 0.00 | 0.00 | 0.00 |
| November | 117.49 | 69.04 | 48.45 | 121.07 | 92.84 | 0.00 | 0.00 | 0.00 |
| December | 101.63 | 63.68 | 37.95 | 96.54 | 125.03 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 154.92 | 84.09 | 70.83 | 187.18 | 67.16 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 101.63 | 60.07 | 37.95 | 96.54 | 17.62 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 196.47 | 109.49 | 97.54 | 268.46 | 125.03 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: TWINDOW1 N NWA
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 56.16 | 0.00 | 56.16 | 14.77 | 194.55 | 0.00 | 0.00 | 0.00 |
| February | 70.19 | 0.00 | 70.19 | 29.06 | 174.13 | 0.00 | 0.00 | 0.00 |
| March | 88.56 | 0.01 | 88.56 | 60.22 | 132.96 | 0.00 | 0.00 | 0.00 |
| April | 112.57 | 1.18 | 111.39 | 93.53 | 88.16 | 0.00 | 0.00 | 0.00 |
| May | 122.40 | 8.09 | 114.30 | 126.46 | 63.55 | 0.00 | 0.00 | 0.00 |
| June | 138.81 | 22.80 | 116.01 | 190.72 | 41.29 | 0.00 | 0.00 | 0.00 |
| July | 127.08 | 10.32 | 116.76 | 188.58 | 25.83 | 0.00 | 0.00 | 0.00 |
| August | 118.60 | 3.09 | 115.50 | 160.43 | 30.75 | 0.00 | 0.00 | 0.00 |
| September | 94.55 | 0.06 | 94.49 | 109.36 | 57.45 | 0.00 | 0.00 | 0.00 |
| October | 70.49 | 0.00 | 70.49 | 53.20 | 102.73 | 0.00 | 0.00 | 0.00 |
| November | 59.87 | 0.00 | 59.87 | 22.18 | 148.37 | 0.00 | 0.00 | 0.00 |
| December | 47.80 | 0.00 | 47.80 | 5.27 | 201.88 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 92.34 | 3.80 | 88.53 | 88.12 | 104.80 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 47.80 | 0.00 | 47.80 | 5.27 | 25.83 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 138.81 | 22.80 | 116.76 | 190.72 | 201.88 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: TWINDOW1 S SEA
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 410.12 | 318.01 | 92.11 | 465.61 | 177.09 | 0.00 | 0.00 | 0.00 |
| February | 410.02 | 300.58 | 109.44 | 475.44 | 162.50 | 0.00 | 0.00 | 0.00 |
| March | 295.14 | 176.75 | 118.39 | 348.49 | 129.70 | 0.00 | 0.00 | 0.00 |
| April | 239.51 | 101.83 | 137.68 | 290.88 | 92.19 | 0.00 | 0.00 | 0.00 |
| May | 156.65 | 35.15 | 121.49 | 190.66 | 67.09 | 0.00 | 0.00 | 0.00 |
| June | 131.80 | 16.29 | 115.51 | 187.27 | 43.32 | 0.00 | 0.00 | 0.00 |
| July | 147.19 | 24.69 | 122.50 | 228.25 | 26.62 | 0.00 | 0.00 | 0.00 |
| August | 198.24 | 62.93 | 135.31 | 293.62 | 31.93 | 0.00 | 0.00 | 0.00 |
| September | 283.34 | 160.69 | 122.65 | 391.55 | 57.73 | 0.00 | 0.00 | 0.00 |
| October | 376.78 | 276.83 | 99.95 | 474.22 | 98.19 | 0.00 | 0.00 | 0.00 |
| November | 425.60 | 327.36 | 98.24 | 498.24 | 139.10 | 0.00 | 0.00 | 0.00 |
| December | 450.43 | 371.55 | 78.88 | 514.79 | 180.77 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 293.04 | 180.40 | 112.64 | 362.56 | 100.20 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 131.80 | 16.29 | 78.88 | 187.27 | 26.62 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 450.43 | 371.55 | 137.68 | 514.79 | 180.77 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: TWINDOW1 E SEA
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 103.21 | 58.09 | 45.12 | 87.51 | 122.57 | 0.00 | 0.00 | 0.00 |
| February | 123.18 | 65.96 | 57.22 | 113.88 | 110.62 | 0.00 | 0.00 | 0.00 |
| March | 164.71 | 93.76 | 70.94 | 174.71 | 83.08 | 0.00 | 0.00 | 0.00 |
| April | 224.10 | 127.72 | 96.38 | 261.81 | 56.98 | 0.00 | 0.00 | 0.00 |
| May | 213.71 | 121.73 | 91.98 | 263.92 | 42.02 | 0.00 | 0.00 | 0.00 |
| June | 230.63 | 142.13 | 88.50 | 312.16 | 26.40 | 0.00 | 0.00 | 0.00 |
| July | 213.62 | 122.28 | 91.33 | 301.43 | 16.59 | 0.00 | 0.00 | 0.00 |
| August | 210.67 | 115.98 | 94.69 | 287.28 | 19.85 | 0.00 | 0.00 | 0.00 |
| September | 175.55 | 98.09 | 77.46 | 225.38 | 36.57 | 0.00 | 0.00 | 0.00 |
| October | 153.47 | 97.54 | 55.94 | 173.69 | 65.32 | 0.00 | 0.00 | 0.00 |
| November | 119.37 | 70.10 | 49.26 | 113.71 | 97.21 | 0.00 | 0.00 | 0.00 |
| December | 97.03 | 59.16 | 37.87 | 82.93 | 130.52 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 169.28 | 97.84 | 71.44 | 200.26 | 67.10 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 97.03 | 58.09 | 37.87 | 82.93 | 16.59 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 230.63 | 142.13 | 96.38 | 312.16 | 130.52 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: TWINDOW1 E NEA
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 103.21 | 58.09 | 45.12 | 92.74 | 115.75 | 0.00 | 0.00 | 0.00 |
| February | 123.18 | 65.96 | 57.22 | 119.95 | 104.61 | 0.00 | 0.00 | 0.00 |
| March | 164.71 | 93.76 | 70.94 | 179.38 | 79.82 | 0.00 | 0.00 | 0.00 |
| April | 224.10 | 127.72 | 96.38 | 264.46 | 55.64 | 0.00 | 0.00 | 0.00 |
| May | 213.71 | 121.73 | 91.98 | 264.69 | 41.83 | 0.00 | 0.00 | 0.00 |
| June | 230.63 | 142.13 | 88.50 | 312.08 | 26.51 | 0.00 | 0.00 | 0.00 |
| July | 213.62 | 122.28 | 91.33 | 301.81 | 16.56 | 0.00 | 0.00 | 0.00 |
| August | 210.67 | 115.98 | 94.69 | 288.49 | 19.63 | 0.00 | 0.00 | 0.00 |
| September | 175.55 | 98.09 | 77.46 | 227.94 | 35.67 | 0.00 | 0.00 | 0.00 |
| October | 153.47 | 97.54 | 55.94 | 178.71 | 61.67 | 0.00 | 0.00 | 0.00 |
| November | 119.37 | 70.10 | 49.26 | 120.10 | 89.29 | 0.00 | 0.00 | 0.00 |
| December | 97.03 | 59.16 | 37.87 | 86.91 | 120.90 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 169.28 | 97.84 | 71.44 | 203.48 | 63.79 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 97.03 | 58.09 | 37.87 | 86.91 | 16.56 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 230.63 | 142.13 | 96.38 | 312.08 | 120.90 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: TWINDOW1 N NEA
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 56.16 | 0.00 | 56.16 | 14.28 | 193.50 | 0.00 | 0.00 | 0.00 |
| February | 70.19 | 0.00 | 70.19 | 28.27 | 172.59 | 0.00 | 0.00 | 0.00 |
| March | 88.56 | 0.01 | 88.56 | 57.94 | 131.90 | 0.00 | 0.00 | 0.00 |
| April | 112.57 | 1.18 | 111.39 | 89.65 | 87.30 | 0.00 | 0.00 | 0.00 |
| May | 122.40 | 8.09 | 114.30 | 123.82 | 62.91 | 0.00 | 0.00 | 0.00 |
| June | 138.81 | 22.80 | 116.01 | 188.96 | 40.72 | 0.00 | 0.00 | 0.00 |
| July | 127.08 | 10.32 | 116.76 | 187.34 | 25.51 | 0.00 | 0.00 | 0.00 |
| August | 118.60 | 3.09 | 115.50 | 159.18 | 30.30 | 0.00 | 0.00 | 0.00 |
| September | 94.55 | 0.06 | 94.49 | 108.03 | 56.87 | 0.00 | 0.00 | 0.00 |
| October | 70.49 | 0.00 | 70.49 | 51.04 | 101.76 | 0.00 | 0.00 | 0.00 |
| November | 59.87 | 0.00 | 59.87 | 21.15 | 146.75 | 0.00 | 0.00 | 0.00 |
| December | 47.80 | 0.00 | 47.80 | 4.94 | 201.18 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 92.34 | 3.80 | 88.53 | 86.52 | 103.95 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 47.80 | 0.00 | 47.80 | 4.94 | 25.51 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 138.81 | 22.80 | 116.76 | 188.96 | 201.18 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: TWINDOW1 N N1A
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 56.16 | 0.00 | 56.16 | 14.56 | 196.10 | 0.00 | 0.00 | 0.00 |
| February | 70.19 | 0.00 | 70.19 | 29.21 | 175.06 | 0.00 | 0.00 | 0.00 |
| March | 88.56 | 0.01 | 88.56 | 60.76 | 133.50 | 0.00 | 0.00 | 0.00 |
| April | 112.57 | 1.18 | 111.39 | 94.20 | 88.77 | 0.00 | 0.00 | 0.00 |
| May | 122.40 | 8.09 | 114.30 | 127.35 | 64.21 | 0.00 | 0.00 | 0.00 |
| June | 138.81 | 22.80 | 116.01 | 192.77 | 41.20 | 0.00 | 0.00 | 0.00 |
| July | 127.08 | 10.32 | 116.76 | 191.15 | 25.40 | 0.00 | 0.00 | 0.00 |
| August | 118.60 | 3.09 | 115.50 | 162.73 | 30.30 | 0.00 | 0.00 | 0.00 |
| September | 94.55 | 0.06 | 94.49 | 110.66 | 57.85 | 0.00 | 0.00 | 0.00 |
| October | 70.49 | 0.00 | 70.49 | 53.63 | 103.46 | 0.00 | 0.00 | 0.00 |
| November | 59.87 | 0.00 | 59.87 | 22.08 | 148.92 | 0.00 | 0.00 | 0.00 |
| December | 47.80 | 0.00 | 47.80 | 5.07 | 203.88 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 92.34 | 3.80 | 88.53 | 88.99 | 105.39 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 47.80 | 0.00 | 47.80 | 5.07 | 25.40 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 138.81 | 22.80 | 116.76 | 192.77 | 203.88 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: TWINDOW1 N N2A
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 56.16 | 0.00 | 56.16 | 14.52 | 196.03 | 0.00 | 0.00 | 0.00 |
| February | 70.19 | 0.00 | 70.19 | 29.14 | 174.94 | 0.00 | 0.00 | 0.00 |
| March | 88.56 | 0.01 | 88.56 | 60.55 | 133.45 | 0.00 | 0.00 | 0.00 |
| April | 112.57 | 1.18 | 111.39 | 93.87 | 88.76 | 0.00 | 0.00 | 0.00 |
| May | 122.40 | 8.09 | 114.30 | 127.16 | 64.19 | 0.00 | 0.00 | 0.00 |
| June | 138.81 | 22.80 | 116.01 | 192.68 | 41.17 | 0.00 | 0.00 | 0.00 |
| July | 127.08 | 10.32 | 116.76 | 191.10 | 25.39 | 0.00 | 0.00 | 0.00 |
| August | 118.60 | 3.09 | 115.50 | 162.67 | 30.28 | 0.00 | 0.00 | 0.00 |
| September | 94.55 | 0.06 | 94.49 | 110.58 | 57.81 | 0.00 | 0.00 | 0.00 |
| October | 70.49 | 0.00 | 70.49 | 53.44 | 103.41 | 0.00 | 0.00 | 0.00 |
| November | 59.87 | 0.00 | 59.87 | 22.00 | 148.80 | 0.00 | 0.00 | 0.00 |
| December | 47.80 | 0.00 | 47.80 | 5.05 | 203.83 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 92.34 | 3.80 | 88.53 | 88.87 | 105.34 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 47.80 | 0.00 | 47.80 | 5.05 | 25.39 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 138.81 | 22.80 | 116.76 | 192.68 | 203.83 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: TWINDOW1 S S1A
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 410.12 | 318.01 | 92.11 | 465.45 | 181.27 | 0.00 | 0.00 | 0.00 |
| February | 410.02 | 300.58 | 109.44 | 475.79 | 166.64 | 0.00 | 0.00 | 0.00 |
| March | 295.14 | 176.75 | 118.39 | 350.38 | 132.83 | 0.00 | 0.00 | 0.00 |
| April | 239.51 | 101.83 | 137.68 | 294.30 | 94.29 | 0.00 | 0.00 | 0.00 |
| May | 156.65 | 35.15 | 121.49 | 194.01 | 68.50 | 0.00 | 0.00 | 0.00 |
| June | 131.80 | 16.29 | 115.51 | 191.19 | 43.77 | 0.00 | 0.00 | 0.00 |
| July | 147.19 | 24.69 | 122.50 | 232.01 | 26.50 | 0.00 | 0.00 | 0.00 |
| August | 198.24 | 62.93 | 135.31 | 297.00 | 31.93 | 0.00 | 0.00 | 0.00 |
| September | 283.34 | 160.69 | 122.65 | 393.78 | 58.76 | 0.00 | 0.00 | 0.00 |
| October | 376.78 | 276.83 | 99.95 | 475.61 | 100.97 | 0.00 | 0.00 | 0.00 |
| November | 425.60 | 327.36 | 98.24 | 498.71 | 143.37 | 0.00 | 0.00 | 0.00 |
| December | 450.43 | 371.55 | 78.88 | 514.55 | 185.38 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 293.04 | 180.40 | 112.64 | 364.55 | 102.52 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 131.80 | 16.29 | 78.88 | 191.19 | 26.50 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 450.43 | 371.55 | 137.68 | 514.55 | 185.38 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: TWINDOW1 S S2A
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 410.12 | 318.01 | 92.11 | 465.38 | 181.21 | 0.00 | 0.00 | 0.00 |
| February | 410.02 | 300.58 | 109.44 | 475.70 | 166.54 | 0.00 | 0.00 | 0.00 |
| March | 295.14 | 176.75 | 118.39 | 350.22 | 132.78 | 0.00 | 0.00 | 0.00 |
| April | 239.51 | 101.83 | 137.68 | 294.07 | 94.25 | 0.00 | 0.00 | 0.00 |
| May | 156.65 | 35.15 | 121.49 | 193.84 | 68.47 | 0.00 | 0.00 | 0.00 |
| June | 131.80 | 16.29 | 115.51 | 191.09 | 43.74 | 0.00 | 0.00 | 0.00 |
| July | 147.19 | 24.69 | 122.50 | 231.96 | 26.49 | 0.00 | 0.00 | 0.00 |
| August | 198.24 | 62.93 | 135.31 | 296.95 | 31.91 | 0.00 | 0.00 | 0.00 |
| September | 283.34 | 160.69 | 122.65 | 393.72 | 58.73 | 0.00 | 0.00 | 0.00 |
| October | 376.78 | 276.83 | 99.95 | 475.52 | 100.92 | 0.00 | 0.00 | 0.00 |
| November | 425.60 | 327.36 | 98.24 | 498.61 | 143.30 | 0.00 | 0.00 | 0.00 |
| December | 450.43 | 371.55 | 78.88 | 514.46 | 185.31 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 293.04 | 180.40 | 112.64 | 364.45 | 102.47 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 131.80 | 16.29 | 78.88 | 191.09 | 26.49 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 450.43 | 371.55 | 137.68 | 514.46 | 185.31 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: TWINDOW14
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 24.76 | 13.94 | 10.83 | 21.54 | 30.00 | 205.33 | 0.00 | 0.00 |
| February | 29.56 | 15.83 | 13.73 | 27.99 | 27.40 | 99.00 | 0.00 | 0.00 |
| March | 39.52 | 22.50 | 17.02 | 42.32 | 21.25 | 77.17 | 0.00 | 0.00 |
| April | 53.77 | 30.65 | 23.13 | 62.68 | 15.07 | 61.17 | 0.00 | 0.00 |
| May | 51.28 | 29.21 | 22.07 | 62.57 | 11.53 | 109.67 | 0.00 | 0.00 |
| June | 55.34 | 34.10 | 21.24 | 73.54 | 7.63 | 157.50 | 0.00 | 0.00 |
| July | 51.26 | 29.34 | 21.92 | 70.83 | 5.23 | 223.17 | 0.00 | 0.00 |
| August | 50.55 | 27.83 | 22.72 | 67.64 | 6.08 | 233.33 | 0.00 | 0.00 |
| September | 42.12 | 23.54 | 18.59 | 53.45 | 10.26 | 274.17 | 0.00 | 0.00 |
| October | 36.83 | 23.40 | 13.42 | 41.95 | 16.97 | 268.17 | 0.00 | 0.00 |
| November | 28.64 | 16.82 | 11.82 | 27.88 | 24.08 | 185.67 | 0.00 | 0.00 |
| December | 23.28 | 14.20 | 9.09 | 20.31 | 31.49 | 227.17 | 0.00 | 0.00 |
| Annual Sum or Average | 40.62 | 23.48 | 17.14 | 47.81 | 17.20 | 2121.50 | 0.00 | 0.00 |
| Minimum of Months | 23.28 | 13.94 | 9.09 | 20.31 | 5.23 | 61.17 | 0.00 | 0.00 |
| Maximum of Months | 55.34 | 34.10 | 23.13 | 73.54 | 31.49 | 274.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ENTRANCE DOOR
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 73.76 | 41.51 | 32.24 | 66.88 | 84.46 | 0.00 | 0.00 | 0.00 |
| February | 88.03 | 47.14 | 40.89 | 86.96 | 76.16 | 0.00 | 0.00 | 0.00 |
| March | 117.71 | 67.01 | 50.70 | 129.80 | 59.15 | 0.00 | 0.00 | 0.00 |
| April | 160.15 | 91.27 | 68.88 | 189.95 | 43.06 | 0.00 | 0.00 | 0.00 |
| May | 152.73 | 86.99 | 65.74 | 187.77 | 34.49 | 0.00 | 0.00 | 0.00 |
| June | 164.82 | 101.57 | 63.25 | 218.52 | 23.81 | 0.00 | 0.00 | 0.00 |
| July | 152.66 | 87.39 | 65.27 | 209.91 | 17.20 | 0.00 | 0.00 | 0.00 |
| August | 150.55 | 82.88 | 67.67 | 200.97 | 19.68 | 0.00 | 0.00 | 0.00 |
| September | 125.45 | 70.10 | 55.36 | 158.82 | 32.40 | 0.00 | 0.00 | 0.00 |
| October | 109.68 | 69.70 | 39.97 | 124.08 | 53.16 | 0.00 | 0.00 | 0.00 |
| November | 85.30 | 50.10 | 35.20 | 83.73 | 72.18 | 0.00 | 0.00 | 0.00 |
| December | 69.34 | 42.28 | 27.07 | 62.39 | 89.27 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 120.97 | 69.92 | 51.05 | 143.56 | 50.29 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 69.34 | 41.51 | 27.07 | 62.39 | 17.20 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 164.82 | 101.57 | 68.88 | 218.52 | 89.27 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MWINDOW14
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 24.76 | 13.94 | 10.83 | 20.50 | 32.47 | 535.50 | 0.00 | 0.00 |
| February | 29.56 | 15.83 | 13.73 | 27.04 | 29.56 | 353.67 | 0.00 | 0.00 |
| March | 39.52 | 22.50 | 17.02 | 41.12 | 23.18 | 296.50 | 0.00 | 0.00 |
| April | 53.77 | 30.65 | 23.13 | 61.50 | 16.41 | 216.83 | 0.00 | 0.00 |
| May | 51.28 | 29.21 | 22.07 | 61.98 | 12.35 | 245.33 | 0.00 | 0.00 |
| June | 55.34 | 34.10 | 21.24 | 73.68 | 7.91 | 245.00 | 0.00 | 0.00 |
| July | 51.26 | 29.34 | 21.92 | 71.35 | 5.28 | 280.83 | 0.00 | 0.00 |
| August | 50.55 | 27.83 | 22.72 | 68.03 | 6.16 | 303.50 | 0.00 | 0.00 |
| September | 42.12 | 23.54 | 18.59 | 53.35 | 10.69 | 354.83 | 0.00 | 0.00 |
| October | 36.83 | 23.40 | 13.42 | 40.98 | 18.59 | 436.17 | 0.00 | 0.00 |
| November | 28.64 | 16.82 | 11.82 | 26.76 | 26.60 | 484.17 | 0.00 | 0.00 |
| December | 23.28 | 14.20 | 9.09 | 19.52 | 34.25 | 585.00 | 0.00 | 0.00 |
| Annual Sum or Average | 40.62 | 23.48 | 17.14 | 47.24 | 18.56 | 4337.33 | 0.00 | 0.00 |
| Minimum of Months | 23.28 | 13.94 | 9.09 | 19.52 | 5.28 | 216.83 | 0.00 | 0.00 |
| Maximum of Months | 55.34 | 34.10 | 23.13 | 73.68 | 34.25 | 585.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: GWINDOW1 S SWA
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.109847E+10 | 0.851769E+09 | 0.246697E+09 | 0.126438E+10 | 0.485753E+09 |
| February | 0.991919E+09 | 0.727165E+09 | 0.264754E+09 | 0.117231E+10 | 0.397786E+09 |
| March | 0.790507E+09 | 0.473407E+09 | 0.317100E+09 | 0.961159E+09 | 0.345681E+09 |
| April | 0.620807E+09 | 0.263938E+09 | 0.356868E+09 | 0.779601E+09 | 0.242839E+09 |
| May | 0.419565E+09 | 94158394.50 | 0.325407E+09 | 0.530767E+09 | 0.185193E+09 |
| June | 0.341622E+09 | 42228752.46 | 0.299393E+09 | 0.502483E+09 | 0.116647E+09 |
| July | 0.394246E+09 | 66136923.55 | 0.328110E+09 | 0.628742E+09 | 74119313.31 |
| August | 0.530966E+09 | 0.168559E+09 | 0.362407E+09 | 0.803179E+09 | 90255305.88 |
| September | 0.734405E+09 | 0.416509E+09 | 0.317897E+09 | 0.102788E+10 | 0.160974E+09 |
| October | 0.100916E+10 | 0.741462E+09 | 0.267698E+09 | 0.127612E+10 | 0.290867E+09 |
| November | 0.110314E+10 | 0.848511E+09 | 0.254632E+09 | 0.129541E+10 | 0.397190E+09 |
| December | 0.120643E+10 | 0.995151E+09 | 0.211279E+09 | 0.139493E+10 | 0.501954E+09 |
| Annual Sum or Average | 0.924124E+10 | 0.568900E+10 | 0.355224E+10 | 0.116370E+11 | 0.328926E+10 |
| Minimum of Months | 0.341622E+09 | 42228752.46 | 0.211279E+09 | 0.502483E+09 | 74119313.31 |
| Maximum of Months | 0.120643E+10 | 0.995151E+09 | 0.362407E+09 | 0.139493E+10 | 0.501954E+09 |
Report: WindowEnergyReportMonthly
For: GWINDOW1 W SWA
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.282364E+09 | 0.160904E+09 | 0.121459E+09 | 0.265863E+09 | 0.349306E+09 |
| February | 0.327447E+09 | 0.188785E+09 | 0.138662E+09 | 0.335233E+09 | 0.280116E+09 |
| March | 0.406560E+09 | 0.216460E+09 | 0.190100E+09 | 0.447783E+09 | 0.233957E+09 |
| April | 0.501256E+09 | 0.266408E+09 | 0.234849E+09 | 0.588989E+09 | 0.156208E+09 |
| May | 0.493658E+09 | 0.255067E+09 | 0.238591E+09 | 0.613444E+09 | 0.119469E+09 |
| June | 0.509262E+09 | 0.283791E+09 | 0.225471E+09 | 0.705665E+09 | 76773316.40 |
| July | 0.475499E+09 | 0.232720E+09 | 0.242779E+09 | 0.688791E+09 | 48600328.50 |
| August | 0.485326E+09 | 0.224083E+09 | 0.261244E+09 | 0.676457E+09 | 59222514.70 |
| September | 0.426150E+09 | 0.224946E+09 | 0.201204E+09 | 0.558343E+09 | 0.106504E+09 |
| October | 0.401151E+09 | 0.249187E+09 | 0.151964E+09 | 0.465893E+09 | 0.205427E+09 |
| November | 0.304531E+09 | 0.178941E+09 | 0.125591E+09 | 0.297565E+09 | 0.282597E+09 |
| December | 0.272210E+09 | 0.170554E+09 | 0.101655E+09 | 0.249540E+09 | 0.363461E+09 |
| Annual Sum or Average | 0.488541E+10 | 0.265184E+10 | 0.223357E+10 | 0.589357E+10 | 0.228164E+10 |
| Minimum of Months | 0.272210E+09 | 0.160904E+09 | 0.101655E+09 | 0.249540E+09 | 48600328.50 |
| Maximum of Months | 0.509262E+09 | 0.283791E+09 | 0.261244E+09 | 0.705665E+09 | 0.363461E+09 |
Report: WindowEnergyReportMonthly
For: GWINDOW1 W NWA
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.282364E+09 | 0.160904E+09 | 0.121459E+09 | 0.278720E+09 | 0.329923E+09 |
| February | 0.327447E+09 | 0.188785E+09 | 0.138662E+09 | 0.347621E+09 | 0.264319E+09 |
| March | 0.406560E+09 | 0.216460E+09 | 0.190100E+09 | 0.461087E+09 | 0.220317E+09 |
| April | 0.501256E+09 | 0.266408E+09 | 0.234849E+09 | 0.599740E+09 | 0.146649E+09 |
| May | 0.493658E+09 | 0.255067E+09 | 0.238591E+09 | 0.616126E+09 | 0.117659E+09 |
| June | 0.509262E+09 | 0.283791E+09 | 0.225471E+09 | 0.705593E+09 | 77025878.71 |
| July | 0.475499E+09 | 0.232720E+09 | 0.242779E+09 | 0.689589E+09 | 48333887.57 |
| August | 0.485326E+09 | 0.224083E+09 | 0.261244E+09 | 0.679065E+09 | 58059808.90 |
| September | 0.426150E+09 | 0.224946E+09 | 0.201204E+09 | 0.563230E+09 | 0.103340E+09 |
| October | 0.401151E+09 | 0.249187E+09 | 0.151964E+09 | 0.475802E+09 | 0.193188E+09 |
| November | 0.304531E+09 | 0.178941E+09 | 0.125591E+09 | 0.315208E+09 | 0.250529E+09 |
| December | 0.272210E+09 | 0.170554E+09 | 0.101655E+09 | 0.261365E+09 | 0.340417E+09 |
| Annual Sum or Average | 0.488541E+10 | 0.265184E+10 | 0.223357E+10 | 0.599314E+10 | 0.214976E+10 |
| Minimum of Months | 0.272210E+09 | 0.160904E+09 | 0.101655E+09 | 0.261365E+09 | 48333887.57 |
| Maximum of Months | 0.509262E+09 | 0.283791E+09 | 0.261244E+09 | 0.705593E+09 | 0.340417E+09 |
Report: WindowEnergyReportMonthly
For: GWINDOW1 N NWA
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.150424E+09 | 0.00 | 0.150424E+09 | 42513010.36 | 0.520469E+09 |
| February | 0.169811E+09 | 0.00 | 0.169811E+09 | 77863156.18 | 0.413823E+09 |
| March | 0.237211E+09 | 23134.55 | 0.237188E+09 | 0.178070E+09 | 0.341325E+09 |
| April | 0.291771E+09 | 3046518.65 | 0.288725E+09 | 0.260902E+09 | 0.220453E+09 |
| May | 0.327828E+09 | 21674088.24 | 0.306154E+09 | 0.351462E+09 | 0.171584E+09 |
| June | 0.359800E+09 | 59092131.21 | 0.300708E+09 | 0.506446E+09 | 0.108846E+09 |
| July | 0.340370E+09 | 27644461.40 | 0.312725E+09 | 0.517940E+09 | 70641314.59 |
| August | 0.317651E+09 | 8286352.67 | 0.309364E+09 | 0.440142E+09 | 84735982.25 |
| September | 0.245065E+09 | 147417.50 | 0.244917E+09 | 0.287699E+09 | 0.157727E+09 |
| October | 0.188808E+09 | 0.00 | 0.188808E+09 | 0.137849E+09 | 0.300239E+09 |
| November | 0.155171E+09 | 0.00 | 0.155171E+09 | 56481643.65 | 0.397909E+09 |
| December | 0.128034E+09 | 0.00 | 0.128034E+09 | 14804299.43 | 0.546821E+09 |
| Annual Sum or Average | 0.291194E+10 | 0.119914E+09 | 0.279203E+10 | 0.287217E+10 | 0.333457E+10 |
| Minimum of Months | 0.128034E+09 | 0.00 | 0.128034E+09 | 14804299.43 | 70641314.59 |
| Maximum of Months | 0.359800E+09 | 59092131.21 | 0.312725E+09 | 0.517940E+09 | 0.546821E+09 |
Report: WindowEnergyReportMonthly
For: GWINDOW1 S SEA
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.109847E+10 | 0.851769E+09 | 0.246697E+09 | 0.126627E+10 | 0.480758E+09 |
| February | 0.991919E+09 | 0.727165E+09 | 0.264754E+09 | 0.117382E+10 | 0.395057E+09 |
| March | 0.790507E+09 | 0.473407E+09 | 0.317100E+09 | 0.951148E+09 | 0.361095E+09 |
| April | 0.620807E+09 | 0.263938E+09 | 0.356868E+09 | 0.763857E+09 | 0.267438E+09 |
| May | 0.419565E+09 | 94158394.50 | 0.325407E+09 | 0.508135E+09 | 0.218638E+09 |
| June | 0.341622E+09 | 42228752.46 | 0.299393E+09 | 0.470722E+09 | 0.156170E+09 |
| July | 0.394246E+09 | 66136923.55 | 0.328110E+09 | 0.584289E+09 | 0.125596E+09 |
| August | 0.530966E+09 | 0.168559E+09 | 0.362407E+09 | 0.766980E+09 | 0.143067E+09 |
| September | 0.734405E+09 | 0.416509E+09 | 0.317897E+09 | 0.999649E+09 | 0.213944E+09 |
| October | 0.100916E+10 | 0.741462E+09 | 0.267698E+09 | 0.125600E+10 | 0.333198E+09 |
| November | 0.110314E+10 | 0.848511E+09 | 0.254632E+09 | 0.128965E+10 | 0.413566E+09 |
| December | 0.120643E+10 | 0.995151E+09 | 0.211279E+09 | 0.139396E+10 | 0.505184E+09 |
| Annual Sum or Average | 0.924124E+10 | 0.568900E+10 | 0.355224E+10 | 0.114245E+11 | 0.361371E+10 |
| Minimum of Months | 0.341622E+09 | 42228752.46 | 0.211279E+09 | 0.470722E+09 | 0.125596E+09 |
| Maximum of Months | 0.120643E+10 | 0.995151E+09 | 0.362407E+09 | 0.139396E+10 | 0.505184E+09 |
Report: WindowEnergyReportMonthly
For: GWINDOW1 E SEA
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.276425E+09 | 0.155583E+09 | 0.120842E+09 | 0.241436E+09 | 0.328510E+09 |
| February | 0.297990E+09 | 0.159564E+09 | 0.138426E+09 | 0.286882E+09 | 0.265847E+09 |
| March | 0.441148E+09 | 0.251139E+09 | 0.190009E+09 | 0.477690E+09 | 0.230457E+09 |
| April | 0.580860E+09 | 0.331044E+09 | 0.249816E+09 | 0.682197E+09 | 0.163841E+09 |
| May | 0.572412E+09 | 0.326040E+09 | 0.246372E+09 | 0.703315E+09 | 0.135897E+09 |
| June | 0.597784E+09 | 0.368388E+09 | 0.229395E+09 | 0.797075E+09 | 94097170.44 |
| July | 0.572156E+09 | 0.327528E+09 | 0.244628E+09 | 0.787365E+09 | 78048128.61 |
| August | 0.564262E+09 | 0.310638E+09 | 0.253624E+09 | 0.753471E+09 | 88086751.62 |
| September | 0.455020E+09 | 0.254243E+09 | 0.200777E+09 | 0.570931E+09 | 0.134675E+09 |
| October | 0.411065E+09 | 0.261244E+09 | 0.149821E+09 | 0.454585E+09 | 0.220799E+09 |
| November | 0.309395E+09 | 0.181709E+09 | 0.127686E+09 | 0.291437E+09 | 0.285736E+09 |
| December | 0.259895E+09 | 0.158458E+09 | 0.101437E+09 | 0.225248E+09 | 0.357534E+09 |
| Annual Sum or Average | 0.533841E+10 | 0.308558E+10 | 0.225283E+10 | 0.627163E+10 | 0.238353E+10 |
| Minimum of Months | 0.259895E+09 | 0.155583E+09 | 0.101437E+09 | 0.225248E+09 | 78048128.61 |
| Maximum of Months | 0.597784E+09 | 0.368388E+09 | 0.253624E+09 | 0.797075E+09 | 0.357534E+09 |
Report: WindowEnergyReportMonthly
For: GWINDOW1 E NEA
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.276425E+09 | 0.155583E+09 | 0.120842E+09 | 0.251470E+09 | 0.311057E+09 |
| February | 0.297990E+09 | 0.159564E+09 | 0.138426E+09 | 0.297025E+09 | 0.250265E+09 |
| March | 0.441148E+09 | 0.251139E+09 | 0.190009E+09 | 0.495545E+09 | 0.206192E+09 |
| April | 0.580860E+09 | 0.331044E+09 | 0.249816E+09 | 0.701047E+09 | 0.140264E+09 |
| May | 0.572412E+09 | 0.326040E+09 | 0.246372E+09 | 0.719300E+09 | 0.114009E+09 |
| June | 0.597784E+09 | 0.368388E+09 | 0.229395E+09 | 0.819178E+09 | 70698401.49 |
| July | 0.572156E+09 | 0.327528E+09 | 0.244628E+09 | 0.818554E+09 | 45871995.49 |
| August | 0.564262E+09 | 0.310638E+09 | 0.253624E+09 | 0.781717E+09 | 54636175.36 |
| September | 0.455020E+09 | 0.254243E+09 | 0.200777E+09 | 0.595199E+09 | 97980102.20 |
| October | 0.411065E+09 | 0.261244E+09 | 0.149821E+09 | 0.476277E+09 | 0.180288E+09 |
| November | 0.309395E+09 | 0.181709E+09 | 0.127686E+09 | 0.311462E+09 | 0.240956E+09 |
| December | 0.259895E+09 | 0.158458E+09 | 0.101437E+09 | 0.233903E+09 | 0.328356E+09 |
| Annual Sum or Average | 0.533841E+10 | 0.308558E+10 | 0.225283E+10 | 0.650068E+10 | 0.204057E+10 |
| Minimum of Months | 0.259895E+09 | 0.155583E+09 | 0.101437E+09 | 0.233903E+09 | 45871995.49 |
| Maximum of Months | 0.597784E+09 | 0.368388E+09 | 0.253624E+09 | 0.819178E+09 | 0.328356E+09 |
Report: WindowEnergyReportMonthly
For: GWINDOW1 N NEA
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.150424E+09 | 0.00 | 0.150424E+09 | 41909011.23 | 0.519673E+09 |
| February | 0.169811E+09 | 0.00 | 0.169811E+09 | 77380750.38 | 0.412204E+09 |
| March | 0.237211E+09 | 23134.55 | 0.237188E+09 | 0.176074E+09 | 0.340814E+09 |
| April | 0.291771E+09 | 3046518.65 | 0.288725E+09 | 0.255175E+09 | 0.220993E+09 |
| May | 0.327828E+09 | 21674088.24 | 0.306154E+09 | 0.346701E+09 | 0.172198E+09 |
| June | 0.359800E+09 | 59092131.21 | 0.300708E+09 | 0.503603E+09 | 0.108506E+09 |
| July | 0.340370E+09 | 27644461.40 | 0.312725E+09 | 0.515464E+09 | 70592800.06 |
| August | 0.317651E+09 | 8286352.67 | 0.309364E+09 | 0.437937E+09 | 84375495.94 |
| September | 0.245065E+09 | 147417.50 | 0.244917E+09 | 0.286242E+09 | 0.157111E+09 |
| October | 0.188808E+09 | 0.00 | 0.188808E+09 | 0.135856E+09 | 0.299864E+09 |
| November | 0.155171E+09 | 0.00 | 0.155171E+09 | 55230252.60 | 0.396335E+09 |
| December | 0.128034E+09 | 0.00 | 0.128034E+09 | 14411806.27 | 0.545929E+09 |
| Annual Sum or Average | 0.291194E+10 | 0.119914E+09 | 0.279203E+10 | 0.284598E+10 | 0.332860E+10 |
| Minimum of Months | 0.128034E+09 | 0.00 | 0.128034E+09 | 14411806.27 | 70592800.06 |
| Maximum of Months | 0.359800E+09 | 59092131.21 | 0.312725E+09 | 0.515464E+09 | 0.545929E+09 |
Report: WindowEnergyReportMonthly
For: GWINDOW1 N N1A
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.150424E+09 | 0.00 | 0.150424E+09 | 41208385.36 | 0.526654E+09 |
| February | 0.169811E+09 | 0.00 | 0.169811E+09 | 76771700.51 | 0.418470E+09 |
| March | 0.237211E+09 | 23134.55 | 0.237188E+09 | 0.176658E+09 | 0.345670E+09 |
| April | 0.291771E+09 | 3046518.65 | 0.288725E+09 | 0.259897E+09 | 0.223192E+09 |
| May | 0.327828E+09 | 21674088.24 | 0.306154E+09 | 0.350404E+09 | 0.174000E+09 |
| June | 0.359800E+09 | 59092131.21 | 0.300708E+09 | 0.509637E+09 | 0.108035E+09 |
| July | 0.340370E+09 | 27644461.40 | 0.312725E+09 | 0.522615E+09 | 68923349.66 |
| August | 0.317651E+09 | 8286352.67 | 0.309364E+09 | 0.444722E+09 | 82522104.97 |
| September | 0.245065E+09 | 147417.50 | 0.244917E+09 | 0.290793E+09 | 0.155771E+09 |
| October | 0.188808E+09 | 0.00 | 0.188808E+09 | 0.138343E+09 | 0.302376E+09 |
| November | 0.155171E+09 | 0.00 | 0.155171E+09 | 55449901.78 | 0.401850E+09 |
| December | 0.128034E+09 | 0.00 | 0.128034E+09 | 14121407.43 | 0.552721E+09 |
| Annual Sum or Average | 0.291194E+10 | 0.119914E+09 | 0.279203E+10 | 0.288062E+10 | 0.336018E+10 |
| Minimum of Months | 0.128034E+09 | 0.00 | 0.128034E+09 | 14121407.43 | 68923349.66 |
| Maximum of Months | 0.359800E+09 | 59092131.21 | 0.312725E+09 | 0.522615E+09 | 0.552721E+09 |
Report: WindowEnergyReportMonthly
For: GWINDOW1 N N2A
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.150424E+09 | 0.00 | 0.150424E+09 | 41181817.25 | 0.526611E+09 |
| February | 0.169811E+09 | 0.00 | 0.169811E+09 | 76757635.65 | 0.418367E+09 |
| March | 0.237211E+09 | 23134.55 | 0.237188E+09 | 0.176527E+09 | 0.345703E+09 |
| April | 0.291771E+09 | 3046518.65 | 0.288725E+09 | 0.259424E+09 | 0.223462E+09 |
| May | 0.327828E+09 | 21674088.24 | 0.306154E+09 | 0.350033E+09 | 0.174206E+09 |
| June | 0.359800E+09 | 59092131.21 | 0.300708E+09 | 0.509516E+09 | 0.108054E+09 |
| July | 0.340370E+09 | 27644461.40 | 0.312725E+09 | 0.522517E+09 | 68944316.42 |
| August | 0.317651E+09 | 8286352.67 | 0.309364E+09 | 0.444640E+09 | 82526025.40 |
| September | 0.245065E+09 | 147417.50 | 0.244917E+09 | 0.290737E+09 | 0.155757E+09 |
| October | 0.188808E+09 | 0.00 | 0.188808E+09 | 0.138226E+09 | 0.302434E+09 |
| November | 0.155171E+09 | 0.00 | 0.155171E+09 | 55379876.04 | 0.401793E+09 |
| December | 0.128034E+09 | 0.00 | 0.128034E+09 | 14107513.99 | 0.552660E+09 |
| Annual Sum or Average | 0.291194E+10 | 0.119914E+09 | 0.279203E+10 | 0.287905E+10 | 0.336052E+10 |
| Minimum of Months | 0.128034E+09 | 0.00 | 0.128034E+09 | 14107513.99 | 68944316.42 |
| Maximum of Months | 0.359800E+09 | 59092131.21 | 0.312725E+09 | 0.522517E+09 | 0.552660E+09 |
Report: WindowEnergyReportMonthly
For: GWINDOW1 S S1A
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.109847E+10 | 0.851769E+09 | 0.246697E+09 | 0.125694E+10 | 0.499454E+09 |
| February | 0.991919E+09 | 0.727165E+09 | 0.264754E+09 | 0.116657E+10 | 0.408332E+09 |
| March | 0.790507E+09 | 0.473407E+09 | 0.317100E+09 | 0.954352E+09 | 0.357585E+09 |
| April | 0.620807E+09 | 0.263938E+09 | 0.356868E+09 | 0.776048E+09 | 0.249262E+09 |
| May | 0.419565E+09 | 94158394.50 | 0.325407E+09 | 0.529845E+09 | 0.188200E+09 |
| June | 0.341622E+09 | 42228752.46 | 0.299393E+09 | 0.505819E+09 | 0.115978E+09 |
| July | 0.394246E+09 | 66136923.55 | 0.328110E+09 | 0.633204E+09 | 72479168.49 |
| August | 0.530966E+09 | 0.168559E+09 | 0.362407E+09 | 0.807368E+09 | 88229867.93 |
| September | 0.734405E+09 | 0.416509E+09 | 0.317897E+09 | 0.103045E+10 | 0.159466E+09 |
| October | 0.100916E+10 | 0.741462E+09 | 0.267698E+09 | 0.127576E+10 | 0.293504E+09 |
| November | 0.110314E+10 | 0.848511E+09 | 0.254632E+09 | 0.128998E+10 | 0.408093E+09 |
| December | 0.120643E+10 | 0.995151E+09 | 0.211279E+09 | 0.138790E+10 | 0.516487E+09 |
| Annual Sum or Average | 0.924124E+10 | 0.568900E+10 | 0.355224E+10 | 0.116142E+11 | 0.335707E+10 |
| Minimum of Months | 0.341622E+09 | 42228752.46 | 0.211279E+09 | 0.505819E+09 | 72479168.49 |
| Maximum of Months | 0.120643E+10 | 0.995151E+09 | 0.362407E+09 | 0.138790E+10 | 0.516487E+09 |
Report: WindowEnergyReportMonthly
For: GWINDOW1 S S2A
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.109847E+10 | 0.851769E+09 | 0.246697E+09 | 0.125694E+10 | 0.499223E+09 |
| February | 0.991919E+09 | 0.727165E+09 | 0.264754E+09 | 0.116654E+10 | 0.408234E+09 |
| March | 0.790507E+09 | 0.473407E+09 | 0.317100E+09 | 0.952976E+09 | 0.359369E+09 |
| April | 0.620807E+09 | 0.263938E+09 | 0.356868E+09 | 0.774259E+09 | 0.251412E+09 |
| May | 0.419565E+09 | 94158394.50 | 0.325407E+09 | 0.528021E+09 | 0.190165E+09 |
| June | 0.341622E+09 | 42228752.46 | 0.299393E+09 | 0.504025E+09 | 0.117547E+09 |
| July | 0.394246E+09 | 66136923.55 | 0.328110E+09 | 0.630960E+09 | 74371617.00 |
| August | 0.530966E+09 | 0.168559E+09 | 0.362407E+09 | 0.805415E+09 | 90125434.54 |
| September | 0.734405E+09 | 0.416509E+09 | 0.317897E+09 | 0.102902E+10 | 0.161326E+09 |
| October | 0.100916E+10 | 0.741462E+09 | 0.267698E+09 | 0.127453E+10 | 0.295327E+09 |
| November | 0.110314E+10 | 0.848511E+09 | 0.254632E+09 | 0.128927E+10 | 0.409160E+09 |
| December | 0.120643E+10 | 0.995151E+09 | 0.211279E+09 | 0.138761E+10 | 0.516798E+09 |
| Annual Sum or Average | 0.924124E+10 | 0.568900E+10 | 0.355224E+10 | 0.115996E+11 | 0.337306E+10 |
| Minimum of Months | 0.341622E+09 | 42228752.46 | 0.211279E+09 | 0.504025E+09 | 74371617.00 |
| Maximum of Months | 0.120643E+10 | 0.995151E+09 | 0.362407E+09 | 0.138761E+10 | 0.516798E+09 |
Report: WindowEnergyReportMonthly
For: MWINDOW1 S SWA
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.109847E+10 | 0.851769E+09 | 0.246697E+09 | 0.124873E+10 | 0.504725E+09 |
| February | 0.991919E+09 | 0.727165E+09 | 0.264754E+09 | 0.115406E+10 | 0.420601E+09 |
| March | 0.790507E+09 | 0.473407E+09 | 0.317100E+09 | 0.935548E+09 | 0.380548E+09 |
| April | 0.620807E+09 | 0.263938E+09 | 0.356868E+09 | 0.760306E+09 | 0.264852E+09 |
| May | 0.419565E+09 | 94158394.50 | 0.325407E+09 | 0.519158E+09 | 0.196291E+09 |
| June | 0.341622E+09 | 42228752.46 | 0.299393E+09 | 0.498437E+09 | 0.119610E+09 |
| July | 0.394246E+09 | 66136923.55 | 0.328110E+09 | 0.627164E+09 | 74031524.80 |
| August | 0.530966E+09 | 0.168559E+09 | 0.362407E+09 | 0.801751E+09 | 89155289.84 |
| September | 0.734405E+09 | 0.416509E+09 | 0.317897E+09 | 0.102602E+10 | 0.158873E+09 |
| October | 0.100916E+10 | 0.741462E+09 | 0.267698E+09 | 0.127340E+10 | 0.288505E+09 |
| November | 0.110314E+10 | 0.848511E+09 | 0.254632E+09 | 0.128992E+10 | 0.398817E+09 |
| December | 0.120643E+10 | 0.995151E+09 | 0.211279E+09 | 0.138214E+10 | 0.516247E+09 |
| Annual Sum or Average | 0.924124E+10 | 0.568900E+10 | 0.355224E+10 | 0.115166E+11 | 0.341226E+10 |
| Minimum of Months | 0.341622E+09 | 42228752.46 | 0.211279E+09 | 0.498437E+09 | 74031524.80 |
| Maximum of Months | 0.120643E+10 | 0.995151E+09 | 0.362407E+09 | 0.138214E+10 | 0.516247E+09 |
Report: WindowEnergyReportMonthly
For: MWINDOW1 W SWA
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.282364E+09 | 0.160904E+09 | 0.121459E+09 | 0.258735E+09 | 0.364223E+09 |
| February | 0.327447E+09 | 0.188785E+09 | 0.138662E+09 | 0.325459E+09 | 0.297267E+09 |
| March | 0.406560E+09 | 0.216460E+09 | 0.190100E+09 | 0.431925E+09 | 0.257904E+09 |
| April | 0.501256E+09 | 0.266408E+09 | 0.234849E+09 | 0.575681E+09 | 0.170358E+09 |
| May | 0.493658E+09 | 0.255067E+09 | 0.238591E+09 | 0.604711E+09 | 0.126516E+09 |
| June | 0.509262E+09 | 0.283791E+09 | 0.225471E+09 | 0.702180E+09 | 78829042.07 |
| July | 0.475499E+09 | 0.232720E+09 | 0.242779E+09 | 0.687237E+09 | 48618248.24 |
| August | 0.485326E+09 | 0.224083E+09 | 0.261244E+09 | 0.675451E+09 | 58606426.53 |
| September | 0.426150E+09 | 0.224946E+09 | 0.201204E+09 | 0.557631E+09 | 0.105242E+09 |
| October | 0.401151E+09 | 0.249187E+09 | 0.151964E+09 | 0.464695E+09 | 0.203999E+09 |
| November | 0.304531E+09 | 0.178941E+09 | 0.125591E+09 | 0.295107E+09 | 0.284274E+09 |
| December | 0.272210E+09 | 0.170554E+09 | 0.101655E+09 | 0.244349E+09 | 0.375496E+09 |
| Annual Sum or Average | 0.488541E+10 | 0.265184E+10 | 0.223357E+10 | 0.582316E+10 | 0.237133E+10 |
| Minimum of Months | 0.272210E+09 | 0.160904E+09 | 0.101655E+09 | 0.244349E+09 | 48618248.24 |
| Maximum of Months | 0.509262E+09 | 0.283791E+09 | 0.261244E+09 | 0.702180E+09 | 0.375496E+09 |
Report: WindowEnergyReportMonthly
For: MWINDOW1 W NWA
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.282364E+09 | 0.160904E+09 | 0.121459E+09 | 0.273219E+09 | 0.341485E+09 |
| February | 0.327447E+09 | 0.188785E+09 | 0.138662E+09 | 0.339899E+09 | 0.278081E+09 |
| March | 0.406560E+09 | 0.216460E+09 | 0.190100E+09 | 0.445969E+09 | 0.241198E+09 |
| April | 0.501256E+09 | 0.266408E+09 | 0.234849E+09 | 0.581589E+09 | 0.166063E+09 |
| May | 0.493658E+09 | 0.255067E+09 | 0.238591E+09 | 0.606303E+09 | 0.125901E+09 |
| June | 0.509262E+09 | 0.283791E+09 | 0.225471E+09 | 0.702150E+09 | 79054680.31 |
| July | 0.475499E+09 | 0.232720E+09 | 0.242779E+09 | 0.687980E+09 | 48429920.48 |
| August | 0.485326E+09 | 0.224083E+09 | 0.261244E+09 | 0.677813E+09 | 57796741.83 |
| September | 0.426150E+09 | 0.224946E+09 | 0.201204E+09 | 0.562140E+09 | 0.103009E+09 |
| October | 0.401151E+09 | 0.249187E+09 | 0.151964E+09 | 0.474576E+09 | 0.193412E+09 |
| November | 0.304531E+09 | 0.178941E+09 | 0.125591E+09 | 0.312074E+09 | 0.255642E+09 |
| December | 0.272210E+09 | 0.170554E+09 | 0.101655E+09 | 0.258107E+09 | 0.348881E+09 |
| Annual Sum or Average | 0.488541E+10 | 0.265184E+10 | 0.223357E+10 | 0.592182E+10 | 0.223895E+10 |
| Minimum of Months | 0.272210E+09 | 0.160904E+09 | 0.101655E+09 | 0.258107E+09 | 48429920.48 |
| Maximum of Months | 0.509262E+09 | 0.283791E+09 | 0.261244E+09 | 0.702150E+09 | 0.348881E+09 |
Report: WindowEnergyReportMonthly
For: MWINDOW1 N NWA
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.150424E+09 | 0.00 | 0.150424E+09 | 37764785.44 | 0.539949E+09 |
| February | 0.169811E+09 | 0.00 | 0.169811E+09 | 69747991.59 | 0.436493E+09 |
| March | 0.237211E+09 | 23134.55 | 0.237188E+09 | 0.159694E+09 | 0.375108E+09 |
| April | 0.291771E+09 | 3046518.65 | 0.288725E+09 | 0.236445E+09 | 0.250524E+09 |
| May | 0.327828E+09 | 21674088.24 | 0.306154E+09 | 0.337329E+09 | 0.183091E+09 |
| June | 0.359800E+09 | 59092131.21 | 0.300708E+09 | 0.501943E+09 | 0.111504E+09 |
| July | 0.340370E+09 | 27644461.40 | 0.312725E+09 | 0.516821E+09 | 70657870.61 |
| August | 0.317651E+09 | 8286352.67 | 0.309364E+09 | 0.439705E+09 | 84208107.61 |
| September | 0.245065E+09 | 147417.50 | 0.244917E+09 | 0.287625E+09 | 0.157038E+09 |
| October | 0.188808E+09 | 0.00 | 0.188808E+09 | 0.137778E+09 | 0.300351E+09 |
| November | 0.155171E+09 | 0.00 | 0.155171E+09 | 53927088.89 | 0.406496E+09 |
| December | 0.128034E+09 | 0.00 | 0.128034E+09 | 13038792.90 | 0.561430E+09 |
| Annual Sum or Average | 0.291194E+10 | 0.119914E+09 | 0.279203E+10 | 0.279182E+10 | 0.347685E+10 |
| Minimum of Months | 0.128034E+09 | 0.00 | 0.128034E+09 | 13038792.90 | 70657870.61 |
| Maximum of Months | 0.359800E+09 | 59092131.21 | 0.312725E+09 | 0.516821E+09 | 0.561430E+09 |
Report: WindowEnergyReportMonthly
For: MWINDOW1 S SEA
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.109847E+10 | 0.851769E+09 | 0.246697E+09 | 0.124636E+10 | 0.503683E+09 |
| February | 0.991919E+09 | 0.727165E+09 | 0.264754E+09 | 0.115223E+10 | 0.418408E+09 |
| March | 0.790507E+09 | 0.473407E+09 | 0.317100E+09 | 0.931422E+09 | 0.380341E+09 |
| April | 0.620807E+09 | 0.263938E+09 | 0.356868E+09 | 0.756814E+09 | 0.264382E+09 |
| May | 0.419565E+09 | 94158394.50 | 0.325407E+09 | 0.515947E+09 | 0.195993E+09 |
| June | 0.341622E+09 | 42228752.46 | 0.299393E+09 | 0.496058E+09 | 0.119091E+09 |
| July | 0.394246E+09 | 66136923.55 | 0.328110E+09 | 0.624964E+09 | 73720198.54 |
| August | 0.530966E+09 | 0.168559E+09 | 0.362407E+09 | 0.799772E+09 | 88620342.65 |
| September | 0.734405E+09 | 0.416509E+09 | 0.317897E+09 | 0.102462E+10 | 0.158044E+09 |
| October | 0.100916E+10 | 0.741462E+09 | 0.267698E+09 | 0.127148E+10 | 0.287387E+09 |
| November | 0.110314E+10 | 0.848511E+09 | 0.254632E+09 | 0.128760E+10 | 0.397641E+09 |
| December | 0.120643E+10 | 0.995151E+09 | 0.211279E+09 | 0.137971E+10 | 0.514770E+09 |
| Annual Sum or Average | 0.924124E+10 | 0.568900E+10 | 0.355224E+10 | 0.114870E+11 | 0.340208E+10 |
| Minimum of Months | 0.341622E+09 | 42228752.46 | 0.211279E+09 | 0.496058E+09 | 73720198.54 |
| Maximum of Months | 0.120643E+10 | 0.995151E+09 | 0.362407E+09 | 0.137971E+10 | 0.514770E+09 |
Report: WindowEnergyReportMonthly
For: MWINDOW1 E SEA
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.276425E+09 | 0.155583E+09 | 0.120842E+09 | 0.231769E+09 | 0.346230E+09 |
| February | 0.297990E+09 | 0.159564E+09 | 0.138426E+09 | 0.275149E+09 | 0.283084E+09 |
| March | 0.441148E+09 | 0.251139E+09 | 0.190009E+09 | 0.464732E+09 | 0.242794E+09 |
| April | 0.580860E+09 | 0.331044E+09 | 0.249816E+09 | 0.677263E+09 | 0.161584E+09 |
| May | 0.572412E+09 | 0.326040E+09 | 0.246372E+09 | 0.708656E+09 | 0.121699E+09 |
| June | 0.597784E+09 | 0.368388E+09 | 0.229395E+09 | 0.815527E+09 | 72040754.80 |
| July | 0.572156E+09 | 0.327528E+09 | 0.244628E+09 | 0.816244E+09 | 45880004.85 |
| August | 0.564262E+09 | 0.310638E+09 | 0.253624E+09 | 0.777980E+09 | 54935503.39 |
| September | 0.455020E+09 | 0.254243E+09 | 0.200777E+09 | 0.589647E+09 | 99715447.01 |
| October | 0.411065E+09 | 0.261244E+09 | 0.149821E+09 | 0.464960E+09 | 0.190223E+09 |
| November | 0.309395E+09 | 0.181709E+09 | 0.127686E+09 | 0.290993E+09 | 0.275546E+09 |
| December | 0.259895E+09 | 0.158458E+09 | 0.101437E+09 | 0.219974E+09 | 0.367393E+09 |
| Annual Sum or Average | 0.533841E+10 | 0.308558E+10 | 0.225283E+10 | 0.633290E+10 | 0.226112E+10 |
| Minimum of Months | 0.259895E+09 | 0.155583E+09 | 0.101437E+09 | 0.219974E+09 | 45880004.85 |
| Maximum of Months | 0.597784E+09 | 0.368388E+09 | 0.253624E+09 | 0.816244E+09 | 0.367393E+09 |
Report: WindowEnergyReportMonthly
For: MWINDOW1 E NEA
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.276425E+09 | 0.155583E+09 | 0.120842E+09 | 0.245749E+09 | 0.321673E+09 |
| February | 0.297990E+09 | 0.159564E+09 | 0.138426E+09 | 0.289087E+09 | 0.262934E+09 |
| March | 0.441148E+09 | 0.251139E+09 | 0.190009E+09 | 0.478748E+09 | 0.226660E+09 |
| April | 0.580860E+09 | 0.331044E+09 | 0.249816E+09 | 0.682316E+09 | 0.157895E+09 |
| May | 0.572412E+09 | 0.326040E+09 | 0.246372E+09 | 0.710073E+09 | 0.121131E+09 |
| June | 0.597784E+09 | 0.368388E+09 | 0.229395E+09 | 0.815484E+09 | 72168683.71 |
| July | 0.572156E+09 | 0.327528E+09 | 0.244628E+09 | 0.816992E+09 | 45672733.97 |
| August | 0.564262E+09 | 0.310638E+09 | 0.253624E+09 | 0.780351E+09 | 54128223.84 |
| September | 0.455020E+09 | 0.254243E+09 | 0.200777E+09 | 0.594153E+09 | 97485480.55 |
| October | 0.411065E+09 | 0.261244E+09 | 0.149821E+09 | 0.474904E+09 | 0.180280E+09 |
| November | 0.309395E+09 | 0.181709E+09 | 0.127686E+09 | 0.307955E+09 | 0.245704E+09 |
| December | 0.259895E+09 | 0.158458E+09 | 0.101437E+09 | 0.230559E+09 | 0.336426E+09 |
| Annual Sum or Average | 0.533841E+10 | 0.308558E+10 | 0.225283E+10 | 0.642637E+10 | 0.212216E+10 |
| Minimum of Months | 0.259895E+09 | 0.155583E+09 | 0.101437E+09 | 0.230559E+09 | 45672733.97 |
| Maximum of Months | 0.597784E+09 | 0.368388E+09 | 0.253624E+09 | 0.816992E+09 | 0.336426E+09 |
Report: WindowEnergyReportMonthly
For: MWINDOW1 N NEA
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.150424E+09 | 0.00 | 0.150424E+09 | 37029967.60 | 0.538283E+09 |
| February | 0.169811E+09 | 0.00 | 0.169811E+09 | 68787198.06 | 0.434074E+09 |
| March | 0.237211E+09 | 23134.55 | 0.237188E+09 | 0.155359E+09 | 0.375346E+09 |
| April | 0.291771E+09 | 3046518.65 | 0.288725E+09 | 0.231322E+09 | 0.250814E+09 |
| May | 0.327828E+09 | 21674088.24 | 0.306154E+09 | 0.333541E+09 | 0.182733E+09 |
| June | 0.359800E+09 | 59092131.21 | 0.300708E+09 | 0.499323E+09 | 0.110778E+09 |
| July | 0.340370E+09 | 27644461.40 | 0.312725E+09 | 0.514493E+09 | 70286031.30 |
| August | 0.317651E+09 | 8286352.67 | 0.309364E+09 | 0.437535E+09 | 83596026.03 |
| September | 0.245065E+09 | 147417.50 | 0.244917E+09 | 0.286116E+09 | 0.156290E+09 |
| October | 0.188808E+09 | 0.00 | 0.188808E+09 | 0.135315E+09 | 0.299843E+09 |
| November | 0.155171E+09 | 0.00 | 0.155171E+09 | 52214689.67 | 0.404376E+09 |
| December | 0.128034E+09 | 0.00 | 0.128034E+09 | 12559785.79 | 0.560134E+09 |
| Annual Sum or Average | 0.291194E+10 | 0.119914E+09 | 0.279203E+10 | 0.276360E+10 | 0.346655E+10 |
| Minimum of Months | 0.128034E+09 | 0.00 | 0.128034E+09 | 12559785.79 | 70286031.30 |
| Maximum of Months | 0.359800E+09 | 59092131.21 | 0.312725E+09 | 0.514493E+09 | 0.560134E+09 |
Report: WindowEnergyReportMonthly
For: MWINDOW1 N N1A
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.150424E+09 | 0.00 | 0.150424E+09 | 36654557.36 | 0.545293E+09 |
| February | 0.169811E+09 | 0.00 | 0.169811E+09 | 69283248.69 | 0.439700E+09 |
| March | 0.237211E+09 | 23134.55 | 0.237188E+09 | 0.158011E+09 | 0.380933E+09 |
| April | 0.291771E+09 | 3046518.65 | 0.288725E+09 | 0.237019E+09 | 0.252377E+09 |
| May | 0.327828E+09 | 21674088.24 | 0.306154E+09 | 0.339515E+09 | 0.182945E+09 |
| June | 0.359800E+09 | 59092131.21 | 0.300708E+09 | 0.506701E+09 | 0.109785E+09 |
| July | 0.340370E+09 | 27644461.40 | 0.312725E+09 | 0.522333E+09 | 68676034.51 |
| August | 0.317651E+09 | 8286352.67 | 0.309364E+09 | 0.444736E+09 | 82057913.40 |
| September | 0.245065E+09 | 147417.50 | 0.244917E+09 | 0.290779E+09 | 0.155550E+09 |
| October | 0.188808E+09 | 0.00 | 0.188808E+09 | 0.137736E+09 | 0.304144E+09 |
| November | 0.155171E+09 | 0.00 | 0.155171E+09 | 52137346.64 | 0.412871E+09 |
| December | 0.128034E+09 | 0.00 | 0.128034E+09 | 12296932.24 | 0.567812E+09 |
| Annual Sum or Average | 0.291194E+10 | 0.119914E+09 | 0.279203E+10 | 0.280720E+10 | 0.350214E+10 |
| Minimum of Months | 0.128034E+09 | 0.00 | 0.128034E+09 | 12296932.24 | 68676034.51 |
| Maximum of Months | 0.359800E+09 | 59092131.21 | 0.312725E+09 | 0.522333E+09 | 0.567812E+09 |
Report: WindowEnergyReportMonthly
For: MWINDOW1 N N2A
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.150424E+09 | 0.00 | 0.150424E+09 | 36612307.63 | 0.545194E+09 |
| February | 0.169811E+09 | 0.00 | 0.169811E+09 | 69233886.81 | 0.439535E+09 |
| March | 0.237211E+09 | 23134.55 | 0.237188E+09 | 0.157617E+09 | 0.381287E+09 |
| April | 0.291771E+09 | 3046518.65 | 0.288725E+09 | 0.236675E+09 | 0.252554E+09 |
| May | 0.327828E+09 | 21674088.24 | 0.306154E+09 | 0.339310E+09 | 0.182999E+09 |
| June | 0.359800E+09 | 59092131.21 | 0.300708E+09 | 0.506612E+09 | 0.109772E+09 |
| July | 0.340370E+09 | 27644461.40 | 0.312725E+09 | 0.522254E+09 | 68675886.44 |
| August | 0.317651E+09 | 8286352.67 | 0.309364E+09 | 0.444664E+09 | 82046077.31 |
| September | 0.245065E+09 | 147417.50 | 0.244917E+09 | 0.290722E+09 | 0.155526E+09 |
| October | 0.188808E+09 | 0.00 | 0.188808E+09 | 0.137591E+09 | 0.304180E+09 |
| November | 0.155171E+09 | 0.00 | 0.155171E+09 | 52034610.21 | 0.412780E+09 |
| December | 0.128034E+09 | 0.00 | 0.128034E+09 | 12276635.31 | 0.567732E+09 |
| Annual Sum or Average | 0.291194E+10 | 0.119914E+09 | 0.279203E+10 | 0.280560E+10 | 0.350228E+10 |
| Minimum of Months | 0.128034E+09 | 0.00 | 0.128034E+09 | 12276635.31 | 68675886.44 |
| Maximum of Months | 0.359800E+09 | 59092131.21 | 0.312725E+09 | 0.522254E+09 | 0.567732E+09 |
Report: WindowEnergyReportMonthly
For: MWINDOW1 S S1A
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.109847E+10 | 0.851769E+09 | 0.246697E+09 | 0.124117E+10 | 0.520406E+09 |
| February | 0.991919E+09 | 0.727165E+09 | 0.264754E+09 | 0.114844E+10 | 0.432731E+09 |
| March | 0.790507E+09 | 0.473407E+09 | 0.317100E+09 | 0.930662E+09 | 0.391158E+09 |
| April | 0.620807E+09 | 0.263938E+09 | 0.356868E+09 | 0.760930E+09 | 0.266563E+09 |
| May | 0.419565E+09 | 94158394.50 | 0.325407E+09 | 0.521358E+09 | 0.196129E+09 |
| June | 0.341622E+09 | 42228752.46 | 0.299393E+09 | 0.503319E+09 | 0.117849E+09 |
| July | 0.394246E+09 | 66136923.55 | 0.328110E+09 | 0.632562E+09 | 72030509.90 |
| August | 0.530966E+09 | 0.168559E+09 | 0.362407E+09 | 0.806501E+09 | 87091990.23 |
| September | 0.734405E+09 | 0.416509E+09 | 0.317897E+09 | 0.102878E+10 | 0.157630E+09 |
| October | 0.100916E+10 | 0.741462E+09 | 0.267698E+09 | 0.127288E+10 | 0.292101E+09 |
| November | 0.110314E+10 | 0.848511E+09 | 0.254632E+09 | 0.128460E+10 | 0.410251E+09 |
| December | 0.120643E+10 | 0.995151E+09 | 0.211279E+09 | 0.137450E+10 | 0.533718E+09 |
| Annual Sum or Average | 0.924124E+10 | 0.568900E+10 | 0.355224E+10 | 0.115057E+11 | 0.347766E+10 |
| Minimum of Months | 0.341622E+09 | 42228752.46 | 0.211279E+09 | 0.503319E+09 | 72030509.90 |
| Maximum of Months | 0.120643E+10 | 0.995151E+09 | 0.362407E+09 | 0.137450E+10 | 0.533718E+09 |
Report: WindowEnergyReportMonthly
For: MWINDOW1 S S2A
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.109847E+10 | 0.851769E+09 | 0.246697E+09 | 0.124106E+10 | 0.520411E+09 |
| February | 0.991919E+09 | 0.727165E+09 | 0.264754E+09 | 0.114840E+10 | 0.432563E+09 |
| March | 0.790507E+09 | 0.473407E+09 | 0.317100E+09 | 0.930455E+09 | 0.391256E+09 |
| April | 0.620807E+09 | 0.263938E+09 | 0.356868E+09 | 0.760787E+09 | 0.266571E+09 |
| May | 0.419565E+09 | 94158394.50 | 0.325407E+09 | 0.521219E+09 | 0.196159E+09 |
| June | 0.341622E+09 | 42228752.46 | 0.299393E+09 | 0.503229E+09 | 0.117838E+09 |
| July | 0.394246E+09 | 66136923.55 | 0.328110E+09 | 0.632485E+09 | 72029734.64 |
| August | 0.530966E+09 | 0.168559E+09 | 0.362407E+09 | 0.806435E+09 | 87079251.38 |
| September | 0.734405E+09 | 0.416509E+09 | 0.317897E+09 | 0.102873E+10 | 0.157604E+09 |
| October | 0.100916E+10 | 0.741462E+09 | 0.267698E+09 | 0.127282E+10 | 0.292076E+09 |
| November | 0.110314E+10 | 0.848511E+09 | 0.254632E+09 | 0.128452E+10 | 0.410223E+09 |
| December | 0.120643E+10 | 0.995151E+09 | 0.211279E+09 | 0.137441E+10 | 0.533657E+09 |
| Annual Sum or Average | 0.924124E+10 | 0.568900E+10 | 0.355224E+10 | 0.115045E+11 | 0.347747E+10 |
| Minimum of Months | 0.341622E+09 | 42228752.46 | 0.211279E+09 | 0.503229E+09 | 72029734.64 |
| Maximum of Months | 0.120643E+10 | 0.995151E+09 | 0.362407E+09 | 0.137441E+10 | 0.533657E+09 |
Report: WindowEnergyReportMonthly
For: TWINDOW1 S SWA
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.109847E+10 | 0.851769E+09 | 0.246697E+09 | 0.125021E+10 | 0.476676E+09 |
| February | 0.991919E+09 | 0.727165E+09 | 0.264754E+09 | 0.115337E+10 | 0.395967E+09 |
| March | 0.790507E+09 | 0.473407E+09 | 0.317100E+09 | 0.939629E+09 | 0.349584E+09 |
| April | 0.620807E+09 | 0.263938E+09 | 0.356868E+09 | 0.762305E+09 | 0.240937E+09 |
| May | 0.419565E+09 | 94158394.50 | 0.325407E+09 | 0.517600E+09 | 0.181446E+09 |
| June | 0.341622E+09 | 42228752.46 | 0.299393E+09 | 0.489742E+09 | 0.113437E+09 |
| July | 0.394246E+09 | 66136923.55 | 0.328110E+09 | 0.614561E+09 | 72067520.26 |
| August | 0.530966E+09 | 0.168559E+09 | 0.362407E+09 | 0.789502E+09 | 86561672.90 |
| September | 0.734405E+09 | 0.416509E+09 | 0.317897E+09 | 0.101779E+10 | 0.151280E+09 |
| October | 0.100916E+10 | 0.741462E+09 | 0.267698E+09 | 0.127460E+10 | 0.265293E+09 |
| November | 0.110314E+10 | 0.848511E+09 | 0.254632E+09 | 0.129567E+10 | 0.363119E+09 |
| December | 0.120643E+10 | 0.995151E+09 | 0.211279E+09 | 0.138228E+10 | 0.486894E+09 |
| Annual Sum or Average | 0.924124E+10 | 0.568900E+10 | 0.355224E+10 | 0.114873E+11 | 0.318326E+10 |
| Minimum of Months | 0.341622E+09 | 42228752.46 | 0.211279E+09 | 0.489742E+09 | 72067520.26 |
| Maximum of Months | 0.120643E+10 | 0.995151E+09 | 0.362407E+09 | 0.138228E+10 | 0.486894E+09 |
Report: WindowEnergyReportMonthly
For: TWINDOW1 W SWA
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.282364E+09 | 0.160904E+09 | 0.121459E+09 | 0.256768E+09 | 0.342503E+09 |
| February | 0.327447E+09 | 0.188785E+09 | 0.138662E+09 | 0.322678E+09 | 0.278627E+09 |
| March | 0.406560E+09 | 0.216460E+09 | 0.190100E+09 | 0.432509E+09 | 0.235332E+09 |
| April | 0.501256E+09 | 0.266408E+09 | 0.234849E+09 | 0.576212E+09 | 0.153875E+09 |
| May | 0.493658E+09 | 0.255067E+09 | 0.238591E+09 | 0.603288E+09 | 0.116476E+09 |
| June | 0.509262E+09 | 0.283791E+09 | 0.225471E+09 | 0.696112E+09 | 74628326.47 |
| July | 0.475499E+09 | 0.232720E+09 | 0.242779E+09 | 0.678607E+09 | 47231651.17 |
| August | 0.485326E+09 | 0.224083E+09 | 0.261244E+09 | 0.667287E+09 | 56781173.13 |
| September | 0.426150E+09 | 0.224946E+09 | 0.201204E+09 | 0.551930E+09 | 99724574.47 |
| October | 0.401151E+09 | 0.249187E+09 | 0.151964E+09 | 0.462315E+09 | 0.185295E+09 |
| November | 0.304531E+09 | 0.178941E+09 | 0.125591E+09 | 0.294774E+09 | 0.256421E+09 |
| December | 0.272210E+09 | 0.170554E+09 | 0.101655E+09 | 0.241389E+09 | 0.353015E+09 |
| Annual Sum or Average | 0.488541E+10 | 0.265184E+10 | 0.223357E+10 | 0.578387E+10 | 0.219991E+10 |
| Minimum of Months | 0.272210E+09 | 0.160904E+09 | 0.101655E+09 | 0.241389E+09 | 47231651.17 |
| Maximum of Months | 0.509262E+09 | 0.283791E+09 | 0.261244E+09 | 0.696112E+09 | 0.353015E+09 |
Report: WindowEnergyReportMonthly
For: TWINDOW1 W NWA
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.282364E+09 | 0.160904E+09 | 0.121459E+09 | 0.273668E+09 | 0.328384E+09 |
| February | 0.327447E+09 | 0.188785E+09 | 0.138662E+09 | 0.339188E+09 | 0.267149E+09 |
| March | 0.406560E+09 | 0.216460E+09 | 0.190100E+09 | 0.445849E+09 | 0.227853E+09 |
| April | 0.501256E+09 | 0.266408E+09 | 0.234849E+09 | 0.584306E+09 | 0.150748E+09 |
| May | 0.493658E+09 | 0.255067E+09 | 0.238591E+09 | 0.605439E+09 | 0.116067E+09 |
| June | 0.509262E+09 | 0.283791E+09 | 0.225471E+09 | 0.695858E+09 | 75084065.64 |
| July | 0.475499E+09 | 0.232720E+09 | 0.242779E+09 | 0.679596E+09 | 47191378.53 |
| August | 0.485326E+09 | 0.224083E+09 | 0.261244E+09 | 0.670568E+09 | 56225884.47 |
| September | 0.426150E+09 | 0.224946E+09 | 0.201204E+09 | 0.558879E+09 | 97444250.70 |
| October | 0.401151E+09 | 0.249187E+09 | 0.151964E+09 | 0.477151E+09 | 0.176453E+09 |
| November | 0.304531E+09 | 0.178941E+09 | 0.125591E+09 | 0.313802E+09 | 0.240636E+09 |
| December | 0.272210E+09 | 0.170554E+09 | 0.101655E+09 | 0.258576E+09 | 0.334875E+09 |
| Annual Sum or Average | 0.488541E+10 | 0.265184E+10 | 0.223357E+10 | 0.590288E+10 | 0.211811E+10 |
| Minimum of Months | 0.272210E+09 | 0.160904E+09 | 0.101655E+09 | 0.258576E+09 | 47191378.53 |
| Maximum of Months | 0.509262E+09 | 0.283791E+09 | 0.261244E+09 | 0.695858E+09 | 0.334875E+09 |
Report: WindowEnergyReportMonthly
For: TWINDOW1 N NWA
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.150424E+09 | 0.00 | 0.150424E+09 | 39566405.16 | 0.521070E+09 |
| February | 0.169811E+09 | 0.00 | 0.169811E+09 | 70303101.07 | 0.421253E+09 |
| March | 0.237211E+09 | 23134.55 | 0.237188E+09 | 0.161286E+09 | 0.356131E+09 |
| April | 0.291771E+09 | 3046518.65 | 0.288725E+09 | 0.242440E+09 | 0.228502E+09 |
| May | 0.327828E+09 | 21674088.24 | 0.306154E+09 | 0.338705E+09 | 0.170221E+09 |
| June | 0.359800E+09 | 59092131.21 | 0.300708E+09 | 0.494339E+09 | 0.107014E+09 |
| July | 0.340370E+09 | 27644461.40 | 0.312725E+09 | 0.505103E+09 | 69179456.89 |
| August | 0.317651E+09 | 8286352.67 | 0.309364E+09 | 0.429694E+09 | 82348729.65 |
| September | 0.245065E+09 | 147417.50 | 0.244917E+09 | 0.283448E+09 | 0.148909E+09 |
| October | 0.188808E+09 | 0.00 | 0.188808E+09 | 0.142494E+09 | 0.275144E+09 |
| November | 0.155171E+09 | 0.00 | 0.155171E+09 | 57497668.01 | 0.384587E+09 |
| December | 0.128034E+09 | 0.00 | 0.128034E+09 | 14119686.33 | 0.540718E+09 |
| Annual Sum or Average | 0.291194E+10 | 0.119914E+09 | 0.279203E+10 | 0.277900E+10 | 0.330508E+10 |
| Minimum of Months | 0.128034E+09 | 0.00 | 0.128034E+09 | 14119686.33 | 69179456.89 |
| Maximum of Months | 0.359800E+09 | 59092131.21 | 0.312725E+09 | 0.505103E+09 | 0.540718E+09 |
Report: WindowEnergyReportMonthly
For: TWINDOW1 S SEA
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.109847E+10 | 0.851769E+09 | 0.246697E+09 | 0.124710E+10 | 0.474320E+09 |
| February | 0.991919E+09 | 0.727165E+09 | 0.264754E+09 | 0.115018E+10 | 0.393125E+09 |
| March | 0.790507E+09 | 0.473407E+09 | 0.317100E+09 | 0.933408E+09 | 0.347376E+09 |
| April | 0.620807E+09 | 0.263938E+09 | 0.356868E+09 | 0.753973E+09 | 0.238959E+09 |
| May | 0.419565E+09 | 94158394.50 | 0.325407E+09 | 0.510670E+09 | 0.179691E+09 |
| June | 0.341622E+09 | 42228752.46 | 0.299393E+09 | 0.485406E+09 | 0.112272E+09 |
| July | 0.394246E+09 | 66136923.55 | 0.328110E+09 | 0.611339E+09 | 71302091.77 |
| August | 0.530966E+09 | 0.168559E+09 | 0.362407E+09 | 0.786420E+09 | 85527130.63 |
| September | 0.734405E+09 | 0.416509E+09 | 0.317897E+09 | 0.101491E+10 | 0.149645E+09 |
| October | 0.100916E+10 | 0.741462E+09 | 0.267698E+09 | 0.127015E+10 | 0.262982E+09 |
| November | 0.110314E+10 | 0.848511E+09 | 0.254632E+09 | 0.129144E+10 | 0.360535E+09 |
| December | 0.120643E+10 | 0.995151E+09 | 0.211279E+09 | 0.137880E+10 | 0.484172E+09 |
| Annual Sum or Average | 0.924124E+10 | 0.568900E+10 | 0.355224E+10 | 0.114338E+11 | 0.315991E+10 |
| Minimum of Months | 0.341622E+09 | 42228752.46 | 0.211279E+09 | 0.485406E+09 | 71302091.77 |
| Maximum of Months | 0.120643E+10 | 0.995151E+09 | 0.362407E+09 | 0.137880E+10 | 0.484172E+09 |
Report: WindowEnergyReportMonthly
For: TWINDOW1 E SEA
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.276425E+09 | 0.155583E+09 | 0.120842E+09 | 0.234385E+09 | 0.328293E+09 |
| February | 0.297990E+09 | 0.159564E+09 | 0.138426E+09 | 0.275491E+09 | 0.267607E+09 |
| March | 0.441148E+09 | 0.251139E+09 | 0.190009E+09 | 0.467947E+09 | 0.222518E+09 |
| April | 0.580860E+09 | 0.331044E+09 | 0.249816E+09 | 0.678616E+09 | 0.147690E+09 |
| May | 0.572412E+09 | 0.326040E+09 | 0.246372E+09 | 0.706875E+09 | 0.112554E+09 |
| June | 0.597784E+09 | 0.368388E+09 | 0.229395E+09 | 0.809114E+09 | 68429494.40 |
| July | 0.572156E+09 | 0.327528E+09 | 0.244628E+09 | 0.807338E+09 | 44442069.81 |
| August | 0.564262E+09 | 0.310638E+09 | 0.253624E+09 | 0.769440E+09 | 53177547.04 |
| September | 0.455020E+09 | 0.254243E+09 | 0.200777E+09 | 0.584197E+09 | 94778447.64 |
| October | 0.411065E+09 | 0.261244E+09 | 0.149821E+09 | 0.465221E+09 | 0.174951E+09 |
| November | 0.309395E+09 | 0.181709E+09 | 0.127686E+09 | 0.294734E+09 | 0.251961E+09 |
| December | 0.259895E+09 | 0.158458E+09 | 0.101437E+09 | 0.222118E+09 | 0.349591E+09 |
| Annual Sum or Average | 0.533841E+10 | 0.308558E+10 | 0.225283E+10 | 0.631548E+10 | 0.211599E+10 |
| Minimum of Months | 0.259895E+09 | 0.155583E+09 | 0.101437E+09 | 0.222118E+09 | 44442069.81 |
| Maximum of Months | 0.597784E+09 | 0.368388E+09 | 0.253624E+09 | 0.809114E+09 | 0.349591E+09 |
Report: WindowEnergyReportMonthly
For: TWINDOW1 E NEA
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.276425E+09 | 0.155583E+09 | 0.120842E+09 | 0.248383E+09 | 0.310014E+09 |
| February | 0.297990E+09 | 0.159564E+09 | 0.138426E+09 | 0.290191E+09 | 0.253067E+09 |
| March | 0.441148E+09 | 0.251139E+09 | 0.190009E+09 | 0.480448E+09 | 0.213783E+09 |
| April | 0.580860E+09 | 0.331044E+09 | 0.249816E+09 | 0.685480E+09 | 0.144222E+09 |
| May | 0.572412E+09 | 0.326040E+09 | 0.246372E+09 | 0.708938E+09 | 0.112034E+09 |
| June | 0.597784E+09 | 0.368388E+09 | 0.229395E+09 | 0.808912E+09 | 68711474.14 |
| July | 0.572156E+09 | 0.327528E+09 | 0.244628E+09 | 0.808358E+09 | 44362123.47 |
| August | 0.564262E+09 | 0.310638E+09 | 0.253624E+09 | 0.772704E+09 | 52584211.49 |
| September | 0.455020E+09 | 0.254243E+09 | 0.200777E+09 | 0.590833E+09 | 92467168.81 |
| October | 0.411065E+09 | 0.261244E+09 | 0.149821E+09 | 0.478656E+09 | 0.165172E+09 |
| November | 0.309395E+09 | 0.181709E+09 | 0.127686E+09 | 0.311310E+09 | 0.231438E+09 |
| December | 0.259895E+09 | 0.158458E+09 | 0.101437E+09 | 0.232793E+09 | 0.323812E+09 |
| Annual Sum or Average | 0.533841E+10 | 0.308558E+10 | 0.225283E+10 | 0.641701E+10 | 0.201167E+10 |
| Minimum of Months | 0.259895E+09 | 0.155583E+09 | 0.101437E+09 | 0.232793E+09 | 44362123.47 |
| Maximum of Months | 0.597784E+09 | 0.368388E+09 | 0.253624E+09 | 0.808912E+09 | 0.323812E+09 |
Report: WindowEnergyReportMonthly
For: TWINDOW1 N NEA
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.150424E+09 | 0.00 | 0.150424E+09 | 38249382.74 | 0.518279E+09 |
| February | 0.169811E+09 | 0.00 | 0.169811E+09 | 68398398.31 | 0.417535E+09 |
| March | 0.237211E+09 | 23134.55 | 0.237188E+09 | 0.155193E+09 | 0.353287E+09 |
| April | 0.291771E+09 | 3046518.65 | 0.288725E+09 | 0.232370E+09 | 0.226281E+09 |
| May | 0.327828E+09 | 21674088.24 | 0.306154E+09 | 0.331632E+09 | 0.168487E+09 |
| June | 0.359800E+09 | 59092131.21 | 0.300708E+09 | 0.489773E+09 | 0.105551E+09 |
| July | 0.340370E+09 | 27644461.40 | 0.312725E+09 | 0.501758E+09 | 68337999.79 |
| August | 0.317651E+09 | 8286352.67 | 0.309364E+09 | 0.426335E+09 | 81158969.56 |
| September | 0.245065E+09 | 147417.50 | 0.244917E+09 | 0.280008E+09 | 0.147401E+09 |
| October | 0.188808E+09 | 0.00 | 0.188808E+09 | 0.136703E+09 | 0.272547E+09 |
| November | 0.155171E+09 | 0.00 | 0.155171E+09 | 54809541.27 | 0.380381E+09 |
| December | 0.128034E+09 | 0.00 | 0.128034E+09 | 13236541.33 | 0.538847E+09 |
| Annual Sum or Average | 0.291194E+10 | 0.119914E+09 | 0.279203E+10 | 0.272847E+10 | 0.327809E+10 |
| Minimum of Months | 0.128034E+09 | 0.00 | 0.128034E+09 | 13236541.33 | 68337999.79 |
| Maximum of Months | 0.359800E+09 | 59092131.21 | 0.312725E+09 | 0.501758E+09 | 0.538847E+09 |
Report: WindowEnergyReportMonthly
For: TWINDOW1 N N1A
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.150424E+09 | 0.00 | 0.150424E+09 | 38992472.47 | 0.525243E+09 |
| February | 0.169811E+09 | 0.00 | 0.169811E+09 | 70665693.65 | 0.423497E+09 |
| March | 0.237211E+09 | 23134.55 | 0.237188E+09 | 0.162749E+09 | 0.357569E+09 |
| April | 0.291771E+09 | 3046518.65 | 0.288725E+09 | 0.244166E+09 | 0.230104E+09 |
| May | 0.327828E+09 | 21674088.24 | 0.306154E+09 | 0.341084E+09 | 0.171990E+09 |
| June | 0.359800E+09 | 59092131.21 | 0.300708E+09 | 0.499653E+09 | 0.106791E+09 |
| July | 0.340370E+09 | 27644461.40 | 0.312725E+09 | 0.511987E+09 | 68035280.72 |
| August | 0.317651E+09 | 8286352.67 | 0.309364E+09 | 0.435849E+09 | 81154889.20 |
| September | 0.245065E+09 | 147417.50 | 0.244917E+09 | 0.286821E+09 | 0.149948E+09 |
| October | 0.188808E+09 | 0.00 | 0.188808E+09 | 0.143640E+09 | 0.277114E+09 |
| November | 0.155171E+09 | 0.00 | 0.155171E+09 | 57242152.48 | 0.386010E+09 |
| December | 0.128034E+09 | 0.00 | 0.128034E+09 | 13587032.82 | 0.546076E+09 |
| Annual Sum or Average | 0.291194E+10 | 0.119914E+09 | 0.279203E+10 | 0.280644E+10 | 0.332353E+10 |
| Minimum of Months | 0.128034E+09 | 0.00 | 0.128034E+09 | 13587032.82 | 68035280.72 |
| Maximum of Months | 0.359800E+09 | 59092131.21 | 0.312725E+09 | 0.511987E+09 | 0.546076E+09 |
Report: WindowEnergyReportMonthly
For: TWINDOW1 N N2A
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.150424E+09 | 0.00 | 0.150424E+09 | 38882113.89 | 0.525049E+09 |
| February | 0.169811E+09 | 0.00 | 0.169811E+09 | 70485060.90 | 0.423204E+09 |
| March | 0.237211E+09 | 23134.55 | 0.237188E+09 | 0.162182E+09 | 0.357422E+09 |
| April | 0.291771E+09 | 3046518.65 | 0.288725E+09 | 0.243299E+09 | 0.230072E+09 |
| May | 0.327828E+09 | 21674088.24 | 0.306154E+09 | 0.340592E+09 | 0.171935E+09 |
| June | 0.359800E+09 | 59092131.21 | 0.300708E+09 | 0.499417E+09 | 0.106722E+09 |
| July | 0.340370E+09 | 27644461.40 | 0.312725E+09 | 0.511841E+09 | 67994405.44 |
| August | 0.317651E+09 | 8286352.67 | 0.309364E+09 | 0.435697E+09 | 81092399.87 |
| September | 0.245065E+09 | 147417.50 | 0.244917E+09 | 0.286614E+09 | 0.149837E+09 |
| October | 0.188808E+09 | 0.00 | 0.188808E+09 | 0.143131E+09 | 0.276983E+09 |
| November | 0.155171E+09 | 0.00 | 0.155171E+09 | 57016981.45 | 0.385687E+09 |
| December | 0.128034E+09 | 0.00 | 0.128034E+09 | 13527099.37 | 0.545950E+09 |
| Annual Sum or Average | 0.291194E+10 | 0.119914E+09 | 0.279203E+10 | 0.280269E+10 | 0.332195E+10 |
| Minimum of Months | 0.128034E+09 | 0.00 | 0.128034E+09 | 13527099.37 | 67994405.44 |
| Maximum of Months | 0.359800E+09 | 59092131.21 | 0.312725E+09 | 0.511841E+09 | 0.545950E+09 |
Report: WindowEnergyReportMonthly
For: TWINDOW1 S S1A
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.109847E+10 | 0.851769E+09 | 0.246697E+09 | 0.124667E+10 | 0.485515E+09 |
| February | 0.991919E+09 | 0.727165E+09 | 0.264754E+09 | 0.115103E+10 | 0.403129E+09 |
| March | 0.790507E+09 | 0.473407E+09 | 0.317100E+09 | 0.938456E+09 | 0.355763E+09 |
| April | 0.620807E+09 | 0.263938E+09 | 0.356868E+09 | 0.762828E+09 | 0.244400E+09 |
| May | 0.419565E+09 | 94158394.50 | 0.325407E+09 | 0.519648E+09 | 0.183464E+09 |
| June | 0.341622E+09 | 42228752.46 | 0.299393E+09 | 0.495557E+09 | 0.113450E+09 |
| July | 0.394246E+09 | 66136923.55 | 0.328110E+09 | 0.621424E+09 | 70979423.36 |
| August | 0.530966E+09 | 0.168559E+09 | 0.362407E+09 | 0.795487E+09 | 85530809.39 |
| September | 0.734405E+09 | 0.416509E+09 | 0.317897E+09 | 0.102067E+10 | 0.152319E+09 |
| October | 0.100916E+10 | 0.741462E+09 | 0.267698E+09 | 0.127388E+10 | 0.270446E+09 |
| November | 0.110314E+10 | 0.848511E+09 | 0.254632E+09 | 0.129266E+10 | 0.371616E+09 |
| December | 0.120643E+10 | 0.995151E+09 | 0.211279E+09 | 0.137818E+10 | 0.496525E+09 |
| Annual Sum or Average | 0.924124E+10 | 0.568900E+10 | 0.355224E+10 | 0.114965E+11 | 0.323314E+10 |
| Minimum of Months | 0.341622E+09 | 42228752.46 | 0.211279E+09 | 0.495557E+09 | 70979423.36 |
| Maximum of Months | 0.120643E+10 | 0.995151E+09 | 0.362407E+09 | 0.137818E+10 | 0.496525E+09 |
Report: WindowEnergyReportMonthly
For: TWINDOW1 S S2A
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.109847E+10 | 0.851769E+09 | 0.246697E+09 | 0.124646E+10 | 0.485343E+09 |
| February | 0.991919E+09 | 0.727165E+09 | 0.264754E+09 | 0.115080E+10 | 0.402899E+09 |
| March | 0.790507E+09 | 0.473407E+09 | 0.317100E+09 | 0.938025E+09 | 0.355646E+09 |
| April | 0.620807E+09 | 0.263938E+09 | 0.356868E+09 | 0.762238E+09 | 0.244303E+09 |
| May | 0.419565E+09 | 94158394.50 | 0.325407E+09 | 0.519186E+09 | 0.183401E+09 |
| June | 0.341622E+09 | 42228752.46 | 0.299393E+09 | 0.495305E+09 | 0.113373E+09 |
| July | 0.394246E+09 | 66136923.55 | 0.328110E+09 | 0.621280E+09 | 70937588.92 |
| August | 0.530966E+09 | 0.168559E+09 | 0.362407E+09 | 0.795346E+09 | 85469802.40 |
| September | 0.734405E+09 | 0.416509E+09 | 0.317897E+09 | 0.102053E+10 | 0.152219E+09 |
| October | 0.100916E+10 | 0.741462E+09 | 0.267698E+09 | 0.127364E+10 | 0.270303E+09 |
| November | 0.110314E+10 | 0.848511E+09 | 0.254632E+09 | 0.129239E+10 | 0.371433E+09 |
| December | 0.120643E+10 | 0.995151E+09 | 0.211279E+09 | 0.137794E+10 | 0.496324E+09 |
| Annual Sum or Average | 0.924124E+10 | 0.568900E+10 | 0.355224E+10 | 0.114932E+11 | 0.323165E+10 |
| Minimum of Months | 0.341622E+09 | 42228752.46 | 0.211279E+09 | 0.495305E+09 | 70937588.92 |
| Maximum of Months | 0.120643E+10 | 0.995151E+09 | 0.362407E+09 | 0.137794E+10 | 0.496324E+09 |
Report: WindowEnergyReportMonthly
For: TWINDOW14
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 66329402.61 | 37332787.17 | 28996615.44 | 57694561.94 | 80347079.60 |
| February | 71503839.62 | 38288004.02 | 33215835.60 | 67713585.15 | 66295135.28 |
| March | 0.105855E+09 | 60261746.15 | 45593479.26 | 0.113351E+09 | 56913744.00 |
| April | 0.139380E+09 | 79435428.98 | 59944391.99 | 0.162470E+09 | 39049084.06 |
| May | 0.137353E+09 | 78234694.40 | 59118013.30 | 0.167582E+09 | 30888729.57 |
| June | 0.143441E+09 | 88396280.40 | 55044310.28 | 0.190607E+09 | 19783281.08 |
| July | 0.137291E+09 | 78591685.32 | 58699578.46 | 0.189713E+09 | 14001180.84 |
| August | 0.135397E+09 | 74538963.50 | 60858075.37 | 0.181164E+09 | 16272681.13 |
| September | 0.109184E+09 | 61006740.84 | 48177174.02 | 0.138532E+09 | 26581356.42 |
| October | 98636709.67 | 62686582.10 | 35950127.57 | 0.112346E+09 | 45459274.12 |
| November | 74240706.78 | 43601933.51 | 30638773.27 | 72272465.46 | 62419665.19 |
| December | 62362933.65 | 38022662.65 | 24340271.01 | 54388117.20 | 84330346.77 |
| Annual Sum or Average | 0.128097E+10 | 0.740398E+09 | 0.540577E+09 | 0.150783E+10 | 0.542342E+09 |
| Minimum of Months | 62362933.65 | 37332787.17 | 24340271.01 | 54388117.20 | 14001180.84 |
| Maximum of Months | 0.143441E+09 | 88396280.40 | 60858075.37 | 0.190607E+09 | 84330346.77 |
Report: WindowEnergyReportMonthly
For: ENTRANCE DOOR
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.197545E+09 | 0.111186E+09 | 86359136.96 | 0.179120E+09 | 0.226216E+09 |
| February | 0.212956E+09 | 0.114031E+09 | 98925024.62 | 0.210367E+09 | 0.184239E+09 |
| March | 0.315263E+09 | 0.179474E+09 | 0.135789E+09 | 0.347650E+09 | 0.158436E+09 |
| April | 0.415108E+09 | 0.236578E+09 | 0.178529E+09 | 0.492344E+09 | 0.111606E+09 |
| May | 0.409071E+09 | 0.233002E+09 | 0.176068E+09 | 0.502918E+09 | 92375687.09 |
| June | 0.427202E+09 | 0.263266E+09 | 0.163936E+09 | 0.566406E+09 | 61715258.68 |
| July | 0.408888E+09 | 0.234066E+09 | 0.174822E+09 | 0.562231E+09 | 46080933.23 |
| August | 0.403246E+09 | 0.221996E+09 | 0.181250E+09 | 0.538278E+09 | 52718356.80 |
| September | 0.325177E+09 | 0.181693E+09 | 0.143484E+09 | 0.411660E+09 | 83974478.25 |
| October | 0.293765E+09 | 0.186696E+09 | 0.107068E+09 | 0.332329E+09 | 0.142374E+09 |
| November | 0.221107E+09 | 0.129857E+09 | 91249891.67 | 0.217016E+09 | 0.187102E+09 |
| December | 0.185732E+09 | 0.113241E+09 | 72491384.46 | 0.167107E+09 | 0.239092E+09 |
| Annual Sum or Average | 0.381506E+10 | 0.220509E+10 | 0.160997E+10 | 0.452742E+10 | 0.158593E+10 |
| Minimum of Months | 0.185732E+09 | 0.111186E+09 | 72491384.46 | 0.167107E+09 | 46080933.23 |
| Maximum of Months | 0.427202E+09 | 0.263266E+09 | 0.181250E+09 | 0.566406E+09 | 0.239092E+09 |
Report: WindowEnergyReportMonthly
For: MWINDOW14
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 66329402.61 | 37332787.17 | 28996615.44 | 54918697.75 | 86954783.96 |
| February | 71503839.62 | 38288004.02 | 33215835.60 | 65422479.12 | 71502714.14 |
| March | 0.105855E+09 | 60261746.15 | 45593479.26 | 0.110124E+09 | 62075703.91 |
| April | 0.139380E+09 | 79435428.98 | 59944391.99 | 0.159412E+09 | 42541578.57 |
| May | 0.137353E+09 | 78234694.40 | 59118013.30 | 0.166011E+09 | 33076877.41 |
| June | 0.143441E+09 | 88396280.40 | 55044310.28 | 0.190969E+09 | 20492078.64 |
| July | 0.137291E+09 | 78591685.32 | 58699578.46 | 0.191092E+09 | 14132246.82 |
| August | 0.135397E+09 | 74538963.50 | 60858075.37 | 0.182206E+09 | 16485667.12 |
| September | 0.109184E+09 | 61006740.84 | 48177174.02 | 0.138278E+09 | 27703123.23 |
| October | 98636709.67 | 62686582.10 | 35950127.57 | 0.109761E+09 | 49790745.95 |
| November | 74240706.78 | 43601933.51 | 30638773.27 | 69352835.39 | 68946320.95 |
| December | 62362933.65 | 38022662.65 | 24340271.01 | 52273124.54 | 91748093.64 |
| Annual Sum or Average | 0.128097E+10 | 0.740398E+09 | 0.540577E+09 | 0.148982E+10 | 0.585450E+09 |
| Minimum of Months | 62362933.65 | 37332787.17 | 24340271.01 | 52273124.54 | 14132246.82 |
| Maximum of Months | 0.143441E+09 | 88396280.40 | 60858075.37 | 0.191092E+09 | 91748093.64 |
Report: WindowZoneSummaryMonthly
For: G SW APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 562.48 | 302.93 | 515.54 | 378.09 | 137.45 | 0.00 | 0.00 |
| February | 617.57 | 274.62 | 545.37 | 378.62 | 166.76 | 0.00 | 0.00 |
| March | 522.84 | 213.22 | 446.93 | 257.57 | 189.37 | 0.00 | 0.00 |
| April | 526.07 | 152.02 | 432.89 | 204.61 | 228.29 | 0.00 | 0.00 |
| May | 425.96 | 112.51 | 340.96 | 130.39 | 210.57 | 0.00 | 0.00 |
| June | 466.01 | 74.53 | 328.27 | 125.78 | 202.49 | 0.00 | 0.00 |
| July | 491.90 | 45.81 | 324.73 | 111.58 | 213.15 | 0.00 | 0.00 |
| August | 552.40 | 55.77 | 379.44 | 146.60 | 232.84 | 0.00 | 0.00 |
| September | 611.56 | 102.79 | 447.75 | 247.47 | 200.27 | 0.00 | 0.00 |
| October | 646.48 | 181.38 | 526.55 | 369.87 | 156.68 | 0.00 | 0.00 |
| November | 607.41 | 255.10 | 543.08 | 396.39 | 146.69 | 0.00 | 0.00 |
| December | 602.92 | 312.06 | 552.06 | 435.22 | 116.84 | 0.00 | 0.00 |
| Annual Sum or Average | 552.27 | 173.03 | 447.95 | 264.49 | 183.47 | 0.00 | 0.00 |
| Minimum of Months | 425.96 | 45.81 | 324.73 | 111.58 | 116.84 | 0.00 | 0.00 |
| Maximum of Months | 646.48 | 312.06 | 552.06 | 435.22 | 232.84 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: G NW APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 115.02 | 312.59 | 161.58 | 60.07 | 101.51 | 0.00 | 0.00 |
| February | 172.00 | 276.44 | 205.55 | 78.04 | 127.51 | 0.00 | 0.00 |
| March | 236.75 | 207.81 | 240.36 | 80.83 | 159.53 | 0.00 | 0.00 |
| April | 330.75 | 140.34 | 305.95 | 103.96 | 202.00 | 0.00 | 0.00 |
| May | 360.10 | 106.84 | 306.71 | 103.32 | 203.38 | 0.00 | 0.00 |
| June | 465.56 | 69.66 | 335.29 | 132.29 | 203.00 | 0.00 | 0.00 |
| July | 450.28 | 43.86 | 304.61 | 97.21 | 207.40 | 0.00 | 0.00 |
| August | 417.27 | 52.72 | 299.80 | 86.76 | 213.04 | 0.00 | 0.00 |
| September | 328.16 | 100.59 | 258.96 | 86.84 | 172.11 | 0.00 | 0.00 |
| October | 227.22 | 182.33 | 220.27 | 93.04 | 127.23 | 0.00 | 0.00 |
| November | 138.46 | 245.23 | 177.35 | 69.04 | 108.32 | 0.00 | 0.00 |
| December | 93.88 | 322.03 | 149.43 | 63.68 | 85.76 | 0.00 | 0.00 |
| Annual Sum or Average | 278.41 | 171.20 | 247.25 | 87.89 | 159.36 | 0.00 | 0.00 |
| Minimum of Months | 93.88 | 43.86 | 149.43 | 60.07 | 85.76 | 0.00 | 0.00 |
| Maximum of Months | 465.56 | 322.03 | 335.29 | 132.29 | 213.04 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: OFFICE
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 558.65 | 297.88 | 513.33 | 376.10 | 137.22 | 0.00 | 0.00 |
| February | 600.50 | 269.90 | 533.20 | 366.54 | 166.66 | 0.00 | 0.00 |
| March | 528.76 | 216.15 | 459.85 | 270.51 | 189.33 | 0.00 | 0.00 |
| April | 551.08 | 159.58 | 463.61 | 229.55 | 234.06 | 0.00 | 0.00 |
| May | 448.35 | 128.41 | 370.36 | 156.88 | 213.48 | 0.00 | 0.00 |
| June | 484.29 | 91.73 | 362.42 | 158.42 | 204.01 | 0.00 | 0.00 |
| July | 509.95 | 73.87 | 360.81 | 146.98 | 213.84 | 0.00 | 0.00 |
| August | 564.46 | 83.09 | 408.91 | 178.91 | 230.00 | 0.00 | 0.00 |
| September | 602.45 | 131.02 | 458.88 | 258.78 | 200.11 | 0.00 | 0.00 |
| October | 635.24 | 203.43 | 530.25 | 374.37 | 155.88 | 0.00 | 0.00 |
| November | 605.13 | 264.94 | 544.96 | 397.46 | 147.50 | 0.00 | 0.00 |
| December | 596.02 | 313.58 | 547.46 | 430.71 | 116.75 | 0.00 | 0.00 |
| Annual Sum or Average | 556.68 | 185.71 | 462.32 | 278.24 | 184.08 | 0.00 | 0.00 |
| Minimum of Months | 448.35 | 73.87 | 360.81 | 146.98 | 116.75 | 0.00 | 0.00 |
| Maximum of Months | 635.24 | 313.58 | 547.46 | 430.71 | 234.06 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: G NE APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 95.53 | 296.15 | 159.37 | 58.09 | 101.28 | 0.00 | 0.00 |
| February | 144.50 | 263.57 | 193.37 | 65.96 | 127.41 | 0.00 | 0.00 |
| March | 242.01 | 195.48 | 253.27 | 93.77 | 159.50 | 0.00 | 0.00 |
| April | 365.48 | 135.94 | 336.66 | 128.89 | 207.77 | 0.00 | 0.00 |
| May | 397.03 | 105.89 | 336.11 | 129.82 | 206.29 | 0.00 | 0.00 |
| June | 510.23 | 69.04 | 369.44 | 164.92 | 204.52 | 0.00 | 0.00 |
| July | 498.01 | 43.43 | 340.70 | 132.61 | 208.09 | 0.00 | 0.00 |
| August | 455.06 | 51.59 | 329.27 | 119.07 | 210.20 | 0.00 | 0.00 |
| September | 337.14 | 95.49 | 270.09 | 98.14 | 171.95 | 0.00 | 0.00 |
| October | 219.55 | 170.27 | 223.97 | 97.54 | 126.43 | 0.00 | 0.00 |
| November | 131.23 | 235.62 | 179.23 | 70.10 | 109.13 | 0.00 | 0.00 |
| December | 77.32 | 311.03 | 144.84 | 59.16 | 85.67 | 0.00 | 0.00 |
| Annual Sum or Average | 290.10 | 163.98 | 261.62 | 101.65 | 159.97 | 0.00 | 0.00 |
| Minimum of Months | 77.32 | 43.43 | 144.84 | 58.09 | 85.67 | 0.00 | 0.00 |
| Maximum of Months | 510.23 | 311.03 | 369.44 | 164.92 | 210.20 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: G N1 APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 15.39 | 196.63 | 56.16 | 0.00 | 56.16 | 0.00 | 0.00 |
| February | 31.73 | 172.98 | 70.19 | 0.00 | 70.19 | 0.00 | 0.00 |
| March | 65.96 | 129.06 | 88.56 | 0.01 | 88.56 | 0.00 | 0.00 |
| April | 100.27 | 86.11 | 112.57 | 1.18 | 111.39 | 0.00 | 0.00 |
| May | 130.83 | 64.96 | 122.40 | 8.09 | 114.30 | 0.00 | 0.00 |
| June | 196.62 | 41.68 | 138.81 | 22.80 | 116.01 | 0.00 | 0.00 |
| July | 195.12 | 25.73 | 127.08 | 10.32 | 116.76 | 0.00 | 0.00 |
| August | 166.04 | 30.81 | 118.60 | 3.09 | 115.50 | 0.00 | 0.00 |
| September | 112.19 | 60.10 | 94.55 | 0.06 | 94.49 | 0.00 | 0.00 |
| October | 51.65 | 112.89 | 70.49 | 0.00 | 70.49 | 0.00 | 0.00 |
| November | 21.39 | 155.03 | 59.87 | 0.00 | 59.87 | 0.00 | 0.00 |
| December | 5.27 | 206.36 | 47.80 | 0.00 | 47.80 | 0.00 | 0.00 |
| Annual Sum or Average | 91.34 | 106.55 | 92.34 | 3.80 | 88.53 | 0.00 | 0.00 |
| Minimum of Months | 5.27 | 25.73 | 47.80 | 0.00 | 47.80 | 0.00 | 0.00 |
| Maximum of Months | 196.62 | 206.36 | 138.81 | 22.80 | 116.76 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: G N2 APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 15.38 | 196.61 | 56.16 | 0.00 | 56.16 | 0.00 | 0.00 |
| February | 31.73 | 172.94 | 70.19 | 0.00 | 70.19 | 0.00 | 0.00 |
| March | 65.91 | 129.07 | 88.56 | 0.01 | 88.56 | 0.00 | 0.00 |
| April | 100.09 | 86.21 | 112.57 | 1.18 | 111.39 | 0.00 | 0.00 |
| May | 130.69 | 65.04 | 122.40 | 8.09 | 114.30 | 0.00 | 0.00 |
| June | 196.57 | 41.69 | 138.81 | 22.80 | 116.01 | 0.00 | 0.00 |
| July | 195.09 | 25.74 | 127.08 | 10.32 | 116.76 | 0.00 | 0.00 |
| August | 166.01 | 30.81 | 118.60 | 3.09 | 115.50 | 0.00 | 0.00 |
| September | 112.17 | 60.09 | 94.55 | 0.06 | 94.49 | 0.00 | 0.00 |
| October | 51.61 | 112.92 | 70.49 | 0.00 | 70.49 | 0.00 | 0.00 |
| November | 21.37 | 155.01 | 59.87 | 0.00 | 59.87 | 0.00 | 0.00 |
| December | 5.27 | 206.34 | 47.80 | 0.00 | 47.80 | 0.00 | 0.00 |
| Annual Sum or Average | 91.29 | 106.56 | 92.34 | 3.80 | 88.53 | 0.00 | 0.00 |
| Minimum of Months | 5.27 | 25.74 | 47.80 | 0.00 | 47.80 | 0.00 | 0.00 |
| Maximum of Months | 196.57 | 206.34 | 138.81 | 22.80 | 116.76 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: G S1 APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 469.29 | 186.47 | 410.12 | 318.01 | 92.11 | 0.00 | 0.00 |
| February | 482.21 | 168.79 | 410.02 | 300.58 | 109.44 | 0.00 | 0.00 |
| March | 356.31 | 133.51 | 295.14 | 176.75 | 118.39 | 0.00 | 0.00 |
| April | 299.40 | 96.17 | 239.51 | 101.83 | 137.68 | 0.00 | 0.00 |
| May | 197.82 | 70.27 | 156.65 | 35.15 | 121.49 | 0.00 | 0.00 |
| June | 195.15 | 44.74 | 131.80 | 16.29 | 115.51 | 0.00 | 0.00 |
| July | 236.41 | 27.06 | 147.19 | 24.69 | 122.50 | 0.00 | 0.00 |
| August | 301.44 | 32.94 | 198.24 | 62.93 | 135.31 | 0.00 | 0.00 |
| September | 397.55 | 61.52 | 283.34 | 160.69 | 122.65 | 0.00 | 0.00 |
| October | 476.31 | 109.58 | 376.78 | 276.83 | 99.95 | 0.00 | 0.00 |
| November | 497.68 | 157.44 | 425.60 | 327.36 | 98.24 | 0.00 | 0.00 |
| December | 518.18 | 192.83 | 450.43 | 371.55 | 78.88 | 0.00 | 0.00 |
| Annual Sum or Average | 368.29 | 106.45 | 293.04 | 180.40 | 112.64 | 0.00 | 0.00 |
| Minimum of Months | 195.15 | 27.06 | 131.80 | 16.29 | 78.88 | 0.00 | 0.00 |
| Maximum of Months | 518.18 | 192.83 | 450.43 | 371.55 | 137.68 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: G S2 APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 469.29 | 186.39 | 410.12 | 318.01 | 92.11 | 0.00 | 0.00 |
| February | 482.20 | 168.75 | 410.02 | 300.58 | 109.44 | 0.00 | 0.00 |
| March | 355.80 | 134.17 | 295.14 | 176.75 | 118.39 | 0.00 | 0.00 |
| April | 298.71 | 97.00 | 239.51 | 101.83 | 137.68 | 0.00 | 0.00 |
| May | 197.14 | 71.00 | 156.65 | 35.15 | 121.49 | 0.00 | 0.00 |
| June | 194.45 | 45.35 | 131.80 | 16.29 | 115.51 | 0.00 | 0.00 |
| July | 235.57 | 27.77 | 147.19 | 24.69 | 122.50 | 0.00 | 0.00 |
| August | 300.71 | 33.65 | 198.24 | 62.93 | 135.31 | 0.00 | 0.00 |
| September | 397.00 | 62.24 | 283.34 | 160.69 | 122.65 | 0.00 | 0.00 |
| October | 475.85 | 110.26 | 376.78 | 276.83 | 99.95 | 0.00 | 0.00 |
| November | 497.40 | 157.85 | 425.60 | 327.36 | 98.24 | 0.00 | 0.00 |
| December | 518.07 | 192.95 | 450.43 | 371.55 | 78.88 | 0.00 | 0.00 |
| Annual Sum or Average | 367.82 | 106.96 | 293.04 | 180.40 | 112.64 | 0.00 | 0.00 |
| Minimum of Months | 194.45 | 27.77 | 131.80 | 16.29 | 78.88 | 0.00 | 0.00 |
| Maximum of Months | 518.07 | 192.95 | 450.43 | 371.55 | 137.68 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: M SW APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 553.24 | 314.85 | 515.54 | 378.09 | 137.45 | 0.00 | 0.00 |
| February | 605.33 | 290.50 | 545.37 | 378.62 | 166.76 | 0.00 | 0.00 |
| March | 506.64 | 234.45 | 446.93 | 257.57 | 189.37 | 0.00 | 0.00 |
| April | 513.12 | 165.60 | 432.89 | 204.61 | 228.29 | 0.00 | 0.00 |
| May | 418.12 | 119.04 | 340.96 | 130.39 | 210.57 | 0.00 | 0.00 |
| June | 463.09 | 76.45 | 328.27 | 125.78 | 202.49 | 0.00 | 0.00 |
| July | 490.72 | 45.78 | 324.73 | 111.58 | 213.15 | 0.00 | 0.00 |
| August | 551.49 | 55.13 | 379.44 | 146.60 | 232.84 | 0.00 | 0.00 |
| September | 610.58 | 101.50 | 447.75 | 247.47 | 200.27 | 0.00 | 0.00 |
| October | 645.02 | 179.97 | 526.55 | 369.87 | 156.68 | 0.00 | 0.00 |
| November | 604.18 | 256.21 | 543.08 | 396.39 | 146.69 | 0.00 | 0.00 |
| December | 595.36 | 321.04 | 552.06 | 435.22 | 116.84 | 0.00 | 0.00 |
| Annual Sum or Average | 545.91 | 179.46 | 447.95 | 264.49 | 183.47 | 0.00 | 0.00 |
| Minimum of Months | 418.12 | 45.78 | 324.73 | 111.58 | 116.84 | 0.00 | 0.00 |
| Maximum of Months | 645.02 | 321.04 | 552.06 | 435.22 | 232.84 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: M NW APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 110.52 | 323.50 | 161.58 | 60.07 | 101.51 | 0.00 | 0.00 |
| February | 164.72 | 290.76 | 205.55 | 78.04 | 127.51 | 0.00 | 0.00 |
| March | 223.54 | 227.51 | 240.36 | 80.83 | 159.53 | 0.00 | 0.00 |
| April | 313.96 | 159.08 | 305.95 | 103.96 | 202.00 | 0.00 | 0.00 |
| May | 351.00 | 114.06 | 306.71 | 103.32 | 203.38 | 0.00 | 0.00 |
| June | 462.42 | 71.39 | 335.29 | 132.29 | 203.00 | 0.00 | 0.00 |
| July | 449.26 | 43.90 | 304.61 | 97.21 | 207.40 | 0.00 | 0.00 |
| August | 416.64 | 52.42 | 299.80 | 86.76 | 213.04 | 0.00 | 0.00 |
| September | 327.70 | 100.19 | 258.96 | 86.84 | 172.11 | 0.00 | 0.00 |
| October | 226.68 | 182.41 | 220.27 | 93.04 | 127.23 | 0.00 | 0.00 |
| November | 135.93 | 250.18 | 177.35 | 69.04 | 108.32 | 0.00 | 0.00 |
| December | 91.35 | 329.99 | 149.43 | 63.68 | 85.76 | 0.00 | 0.00 |
| Annual Sum or Average | 273.29 | 178.23 | 247.25 | 87.89 | 159.36 | 0.00 | 0.00 |
| Minimum of Months | 91.35 | 43.90 | 149.43 | 60.07 | 85.76 | 0.00 | 0.00 |
| Maximum of Months | 462.42 | 329.99 | 335.29 | 132.29 | 213.04 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: M SE APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 546.77 | 312.22 | 513.33 | 376.10 | 137.22 | 0.00 | 0.00 |
| February | 586.02 | 285.97 | 533.20 | 366.54 | 166.66 | 0.00 | 0.00 |
| March | 516.10 | 227.49 | 459.85 | 270.51 | 189.33 | 0.00 | 0.00 |
| April | 546.26 | 157.33 | 463.61 | 229.55 | 234.06 | 0.00 | 0.00 |
| May | 453.54 | 114.94 | 370.36 | 156.88 | 213.48 | 0.00 | 0.00 |
| June | 502.47 | 70.20 | 362.42 | 158.42 | 204.01 | 0.00 | 0.00 |
| July | 537.05 | 43.62 | 360.81 | 146.98 | 213.84 | 0.00 | 0.00 |
| August | 587.35 | 51.88 | 408.91 | 178.91 | 230.00 | 0.00 | 0.00 |
| September | 620.47 | 97.12 | 458.88 | 258.78 | 200.11 | 0.00 | 0.00 |
| October | 645.72 | 175.73 | 530.25 | 374.37 | 155.88 | 0.00 | 0.00 |
| November | 604.22 | 254.92 | 544.96 | 397.46 | 147.50 | 0.00 | 0.00 |
| December | 587.75 | 319.86 | 547.46 | 430.71 | 116.75 | 0.00 | 0.00 |
| Annual Sum or Average | 560.86 | 175.37 | 462.32 | 278.24 | 184.08 | 0.00 | 0.00 |
| Minimum of Months | 453.54 | 43.62 | 360.81 | 146.98 | 116.75 | 0.00 | 0.00 |
| Maximum of Months | 645.72 | 319.86 | 547.46 | 430.71 | 234.06 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: M NE APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 90.78 | 306.27 | 159.37 | 58.09 | 101.28 | 0.00 | 0.00 |
| February | 136.76 | 276.95 | 193.37 | 65.96 | 127.41 | 0.00 | 0.00 |
| March | 226.90 | 214.92 | 253.27 | 93.77 | 159.50 | 0.00 | 0.00 |
| April | 347.77 | 152.96 | 336.66 | 128.89 | 207.77 | 0.00 | 0.00 |
| May | 388.52 | 112.33 | 336.11 | 129.82 | 206.29 | 0.00 | 0.00 |
| June | 507.14 | 70.47 | 369.44 | 164.92 | 204.52 | 0.00 | 0.00 |
| July | 497.07 | 43.24 | 340.70 | 132.61 | 208.09 | 0.00 | 0.00 |
| August | 454.39 | 51.11 | 329.27 | 119.07 | 210.20 | 0.00 | 0.00 |
| September | 336.67 | 94.97 | 270.09 | 98.14 | 171.95 | 0.00 | 0.00 |
| October | 218.75 | 170.17 | 223.97 | 97.54 | 126.43 | 0.00 | 0.00 |
| November | 128.29 | 240.14 | 179.23 | 70.10 | 109.13 | 0.00 | 0.00 |
| December | 74.61 | 318.57 | 144.84 | 59.16 | 85.67 | 0.00 | 0.00 |
| Annual Sum or Average | 284.68 | 170.48 | 261.62 | 101.65 | 159.97 | 0.00 | 0.00 |
| Minimum of Months | 74.61 | 43.24 | 144.84 | 58.09 | 85.67 | 0.00 | 0.00 |
| Maximum of Months | 507.14 | 318.57 | 369.44 | 164.92 | 210.20 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: M N1 APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 13.69 | 203.59 | 56.16 | 0.00 | 56.16 | 0.00 | 0.00 |
| February | 28.64 | 181.75 | 70.19 | 0.00 | 70.19 | 0.00 | 0.00 |
| March | 58.99 | 142.22 | 88.56 | 0.01 | 88.56 | 0.00 | 0.00 |
| April | 91.44 | 97.37 | 112.57 | 1.18 | 111.39 | 0.00 | 0.00 |
| May | 126.76 | 68.30 | 122.40 | 8.09 | 114.30 | 0.00 | 0.00 |
| June | 195.49 | 42.36 | 138.81 | 22.80 | 116.01 | 0.00 | 0.00 |
| July | 195.02 | 25.64 | 127.08 | 10.32 | 116.76 | 0.00 | 0.00 |
| August | 166.05 | 30.64 | 118.60 | 3.09 | 115.50 | 0.00 | 0.00 |
| September | 112.18 | 60.01 | 94.55 | 0.06 | 94.49 | 0.00 | 0.00 |
| October | 51.42 | 113.55 | 70.49 | 0.00 | 70.49 | 0.00 | 0.00 |
| November | 20.11 | 159.29 | 59.87 | 0.00 | 59.87 | 0.00 | 0.00 |
| December | 4.59 | 212.00 | 47.80 | 0.00 | 47.80 | 0.00 | 0.00 |
| Annual Sum or Average | 89.02 | 111.05 | 92.34 | 3.80 | 88.53 | 0.00 | 0.00 |
| Minimum of Months | 4.59 | 25.64 | 47.80 | 0.00 | 47.80 | 0.00 | 0.00 |
| Maximum of Months | 195.49 | 212.00 | 138.81 | 22.80 | 116.76 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: M N2 APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 13.67 | 203.55 | 56.16 | 0.00 | 56.16 | 0.00 | 0.00 |
| February | 28.62 | 181.69 | 70.19 | 0.00 | 70.19 | 0.00 | 0.00 |
| March | 58.85 | 142.36 | 88.56 | 0.01 | 88.56 | 0.00 | 0.00 |
| April | 91.31 | 97.44 | 112.57 | 1.18 | 111.39 | 0.00 | 0.00 |
| May | 126.68 | 68.32 | 122.40 | 8.09 | 114.30 | 0.00 | 0.00 |
| June | 195.45 | 42.35 | 138.81 | 22.80 | 116.01 | 0.00 | 0.00 |
| July | 194.99 | 25.64 | 127.08 | 10.32 | 116.76 | 0.00 | 0.00 |
| August | 166.02 | 30.63 | 118.60 | 3.09 | 115.50 | 0.00 | 0.00 |
| September | 112.16 | 60.00 | 94.55 | 0.06 | 94.49 | 0.00 | 0.00 |
| October | 51.37 | 113.57 | 70.49 | 0.00 | 70.49 | 0.00 | 0.00 |
| November | 20.08 | 159.25 | 59.87 | 0.00 | 59.87 | 0.00 | 0.00 |
| December | 4.58 | 211.97 | 47.80 | 0.00 | 47.80 | 0.00 | 0.00 |
| Annual Sum or Average | 88.97 | 111.06 | 92.34 | 3.80 | 88.53 | 0.00 | 0.00 |
| Minimum of Months | 4.58 | 25.64 | 47.80 | 0.00 | 47.80 | 0.00 | 0.00 |
| Maximum of Months | 195.45 | 211.97 | 138.81 | 22.80 | 116.76 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: M S1 APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 463.40 | 194.30 | 410.12 | 318.01 | 92.11 | 0.00 | 0.00 |
| February | 474.72 | 178.87 | 410.02 | 300.58 | 109.44 | 0.00 | 0.00 |
| March | 347.47 | 146.04 | 295.14 | 176.75 | 118.39 | 0.00 | 0.00 |
| April | 293.57 | 102.84 | 239.51 | 101.83 | 137.68 | 0.00 | 0.00 |
| May | 194.65 | 73.23 | 156.65 | 35.15 | 121.49 | 0.00 | 0.00 |
| June | 194.18 | 45.47 | 131.80 | 16.29 | 115.51 | 0.00 | 0.00 |
| July | 236.17 | 26.89 | 147.19 | 24.69 | 122.50 | 0.00 | 0.00 |
| August | 301.11 | 32.52 | 198.24 | 62.93 | 135.31 | 0.00 | 0.00 |
| September | 396.90 | 60.81 | 283.34 | 160.69 | 122.65 | 0.00 | 0.00 |
| October | 475.24 | 109.06 | 376.78 | 276.83 | 99.95 | 0.00 | 0.00 |
| November | 495.60 | 158.28 | 425.60 | 327.36 | 98.24 | 0.00 | 0.00 |
| December | 513.18 | 199.27 | 450.43 | 371.55 | 78.88 | 0.00 | 0.00 |
| Annual Sum or Average | 364.84 | 110.28 | 293.04 | 180.40 | 112.64 | 0.00 | 0.00 |
| Minimum of Months | 194.18 | 26.89 | 131.80 | 16.29 | 78.88 | 0.00 | 0.00 |
| Maximum of Months | 513.18 | 199.27 | 450.43 | 371.55 | 137.68 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: M S2 APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 463.36 | 194.30 | 410.12 | 318.01 | 92.11 | 0.00 | 0.00 |
| February | 474.70 | 178.80 | 410.02 | 300.58 | 109.44 | 0.00 | 0.00 |
| March | 347.39 | 146.08 | 295.14 | 176.75 | 118.39 | 0.00 | 0.00 |
| April | 293.51 | 102.84 | 239.51 | 101.83 | 137.68 | 0.00 | 0.00 |
| May | 194.60 | 73.24 | 156.65 | 35.15 | 121.49 | 0.00 | 0.00 |
| June | 194.15 | 45.46 | 131.80 | 16.29 | 115.51 | 0.00 | 0.00 |
| July | 236.14 | 26.89 | 147.19 | 24.69 | 122.50 | 0.00 | 0.00 |
| August | 301.09 | 32.51 | 198.24 | 62.93 | 135.31 | 0.00 | 0.00 |
| September | 396.89 | 60.80 | 283.34 | 160.69 | 122.65 | 0.00 | 0.00 |
| October | 475.22 | 109.05 | 376.78 | 276.83 | 99.95 | 0.00 | 0.00 |
| November | 495.57 | 158.27 | 425.60 | 327.36 | 98.24 | 0.00 | 0.00 |
| December | 513.14 | 199.24 | 450.43 | 371.55 | 78.88 | 0.00 | 0.00 |
| Annual Sum or Average | 364.81 | 110.27 | 293.04 | 180.40 | 112.64 | 0.00 | 0.00 |
| Minimum of Months | 194.15 | 26.89 | 131.80 | 16.29 | 78.88 | 0.00 | 0.00 |
| Maximum of Months | 513.14 | 199.24 | 450.43 | 371.55 | 137.68 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: T SW APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 553.88 | 297.09 | 515.54 | 378.09 | 137.45 | 0.00 | 0.00 |
| February | 604.43 | 273.14 | 545.37 | 378.62 | 166.76 | 0.00 | 0.00 |
| March | 508.74 | 214.83 | 446.93 | 257.57 | 189.37 | 0.00 | 0.00 |
| April | 514.02 | 149.93 | 432.89 | 204.61 | 228.29 | 0.00 | 0.00 |
| May | 416.98 | 109.72 | 340.96 | 130.39 | 210.57 | 0.00 | 0.00 |
| June | 457.37 | 72.42 | 328.27 | 125.78 | 202.49 | 0.00 | 0.00 |
| July | 482.79 | 44.52 | 324.73 | 111.58 | 213.15 | 0.00 | 0.00 |
| August | 543.85 | 53.47 | 379.44 | 146.60 | 232.84 | 0.00 | 0.00 |
| September | 605.21 | 96.45 | 447.75 | 247.47 | 200.27 | 0.00 | 0.00 |
| October | 645.35 | 165.09 | 526.55 | 369.87 | 156.68 | 0.00 | 0.00 |
| November | 607.58 | 233.00 | 543.08 | 396.39 | 146.69 | 0.00 | 0.00 |
| December | 595.21 | 302.59 | 552.06 | 435.22 | 116.84 | 0.00 | 0.00 |
| Annual Sum or Average | 544.11 | 167.15 | 447.95 | 264.49 | 183.47 | 0.00 | 0.00 |
| Minimum of Months | 416.98 | 44.52 | 324.73 | 111.58 | 116.84 | 0.00 | 0.00 |
| Maximum of Months | 645.35 | 302.59 | 552.06 | 435.22 | 232.84 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: T NW APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 111.17 | 311.37 | 161.58 | 60.07 | 101.51 | 0.00 | 0.00 |
| February | 164.31 | 279.60 | 205.55 | 78.04 | 127.51 | 0.00 | 0.00 |
| March | 223.73 | 215.09 | 240.36 | 80.83 | 159.53 | 0.00 | 0.00 |
| April | 317.13 | 144.48 | 305.95 | 103.96 | 202.00 | 0.00 | 0.00 |
| May | 351.44 | 105.83 | 306.71 | 103.32 | 203.38 | 0.00 | 0.00 |
| June | 457.34 | 68.41 | 335.29 | 132.29 | 203.00 | 0.00 | 0.00 |
| July | 441.82 | 42.95 | 304.61 | 97.21 | 207.40 | 0.00 | 0.00 |
| August | 410.23 | 51.18 | 299.80 | 86.76 | 213.04 | 0.00 | 0.00 |
| September | 324.79 | 94.86 | 258.96 | 86.84 | 172.11 | 0.00 | 0.00 |
| October | 229.29 | 166.55 | 220.27 | 93.04 | 127.23 | 0.00 | 0.00 |
| November | 137.77 | 235.73 | 177.35 | 69.04 | 108.32 | 0.00 | 0.00 |
| December | 91.94 | 317.03 | 149.43 | 63.68 | 85.76 | 0.00 | 0.00 |
| Annual Sum or Average | 272.22 | 168.89 | 247.25 | 87.89 | 159.36 | 0.00 | 0.00 |
| Minimum of Months | 91.94 | 42.95 | 149.43 | 60.07 | 85.76 | 0.00 | 0.00 |
| Maximum of Months | 457.34 | 317.03 | 335.29 | 132.29 | 213.04 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: T SE APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 547.59 | 294.13 | 513.33 | 376.10 | 137.22 | 0.00 | 0.00 |
| February | 585.10 | 268.91 | 533.20 | 366.54 | 166.66 | 0.00 | 0.00 |
| March | 518.57 | 208.14 | 459.85 | 270.51 | 189.33 | 0.00 | 0.00 |
| April | 547.21 | 143.68 | 463.61 | 229.55 | 234.06 | 0.00 | 0.00 |
| May | 451.69 | 106.22 | 370.36 | 156.88 | 213.48 | 0.00 | 0.00 |
| June | 496.41 | 66.70 | 362.42 | 158.42 | 204.01 | 0.00 | 0.00 |
| July | 528.75 | 42.29 | 360.81 | 146.98 | 213.84 | 0.00 | 0.00 |
| August | 579.37 | 50.27 | 408.91 | 178.91 | 230.00 | 0.00 | 0.00 |
| September | 615.00 | 92.36 | 458.88 | 258.78 | 200.11 | 0.00 | 0.00 |
| October | 645.66 | 161.25 | 530.25 | 374.37 | 155.88 | 0.00 | 0.00 |
| November | 606.91 | 231.26 | 544.96 | 397.46 | 147.50 | 0.00 | 0.00 |
| December | 587.37 | 300.95 | 547.46 | 430.71 | 116.75 | 0.00 | 0.00 |
| Annual Sum or Average | 558.84 | 163.32 | 462.32 | 278.24 | 184.08 | 0.00 | 0.00 |
| Minimum of Months | 451.69 | 42.29 | 360.81 | 146.98 | 116.75 | 0.00 | 0.00 |
| Maximum of Months | 645.66 | 300.95 | 547.46 | 430.71 | 234.06 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: T NE APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 92.87 | 295.10 | 159.37 | 58.09 | 101.28 | 0.00 | 0.00 |
| February | 137.68 | 266.65 | 193.37 | 65.96 | 127.41 | 0.00 | 0.00 |
| March | 228.32 | 202.72 | 253.27 | 93.77 | 159.50 | 0.00 | 0.00 |
| April | 350.80 | 139.63 | 336.66 | 128.89 | 207.77 | 0.00 | 0.00 |
| May | 387.53 | 103.76 | 336.11 | 129.82 | 206.29 | 0.00 | 0.00 |
| June | 500.93 | 67.12 | 369.44 | 164.92 | 204.52 | 0.00 | 0.00 |
| July | 489.10 | 42.03 | 340.70 | 132.61 | 208.09 | 0.00 | 0.00 |
| August | 447.43 | 49.69 | 329.27 | 119.07 | 210.20 | 0.00 | 0.00 |
| September | 333.60 | 90.17 | 270.09 | 98.14 | 171.95 | 0.00 | 0.00 |
| October | 222.24 | 155.92 | 223.97 | 97.54 | 126.43 | 0.00 | 0.00 |
| November | 131.42 | 226.21 | 179.23 | 70.10 | 109.13 | 0.00 | 0.00 |
| December | 76.44 | 306.66 | 144.84 | 59.16 | 85.67 | 0.00 | 0.00 |
| Annual Sum or Average | 283.89 | 161.62 | 261.62 | 101.65 | 159.97 | 0.00 | 0.00 |
| Minimum of Months | 76.44 | 42.03 | 144.84 | 58.09 | 85.67 | 0.00 | 0.00 |
| Maximum of Months | 500.93 | 306.66 | 369.44 | 164.92 | 210.20 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: T N1 APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 14.56 | 196.10 | 56.16 | 0.00 | 56.16 | 0.00 | 0.00 |
| February | 29.21 | 175.06 | 70.19 | 0.00 | 70.19 | 0.00 | 0.00 |
| March | 60.76 | 133.50 | 88.56 | 0.01 | 88.56 | 0.00 | 0.00 |
| April | 94.20 | 88.77 | 112.57 | 1.18 | 111.39 | 0.00 | 0.00 |
| May | 127.35 | 64.21 | 122.40 | 8.09 | 114.30 | 0.00 | 0.00 |
| June | 192.77 | 41.20 | 138.81 | 22.80 | 116.01 | 0.00 | 0.00 |
| July | 191.15 | 25.40 | 127.08 | 10.32 | 116.76 | 0.00 | 0.00 |
| August | 162.73 | 30.30 | 118.60 | 3.09 | 115.50 | 0.00 | 0.00 |
| September | 110.66 | 57.85 | 94.55 | 0.06 | 94.49 | 0.00 | 0.00 |
| October | 53.63 | 103.46 | 70.49 | 0.00 | 70.49 | 0.00 | 0.00 |
| November | 22.08 | 148.92 | 59.87 | 0.00 | 59.87 | 0.00 | 0.00 |
| December | 5.07 | 203.88 | 47.80 | 0.00 | 47.80 | 0.00 | 0.00 |
| Annual Sum or Average | 88.99 | 105.39 | 92.34 | 3.80 | 88.53 | 0.00 | 0.00 |
| Minimum of Months | 5.07 | 25.40 | 47.80 | 0.00 | 47.80 | 0.00 | 0.00 |
| Maximum of Months | 192.77 | 203.88 | 138.81 | 22.80 | 116.76 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: T N2 APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 14.52 | 196.03 | 56.16 | 0.00 | 56.16 | 0.00 | 0.00 |
| February | 29.14 | 174.94 | 70.19 | 0.00 | 70.19 | 0.00 | 0.00 |
| March | 60.55 | 133.45 | 88.56 | 0.01 | 88.56 | 0.00 | 0.00 |
| April | 93.87 | 88.76 | 112.57 | 1.18 | 111.39 | 0.00 | 0.00 |
| May | 127.16 | 64.19 | 122.40 | 8.09 | 114.30 | 0.00 | 0.00 |
| June | 192.68 | 41.17 | 138.81 | 22.80 | 116.01 | 0.00 | 0.00 |
| July | 191.10 | 25.39 | 127.08 | 10.32 | 116.76 | 0.00 | 0.00 |
| August | 162.67 | 30.28 | 118.60 | 3.09 | 115.50 | 0.00 | 0.00 |
| September | 110.58 | 57.81 | 94.55 | 0.06 | 94.49 | 0.00 | 0.00 |
| October | 53.44 | 103.41 | 70.49 | 0.00 | 70.49 | 0.00 | 0.00 |
| November | 22.00 | 148.80 | 59.87 | 0.00 | 59.87 | 0.00 | 0.00 |
| December | 5.05 | 203.83 | 47.80 | 0.00 | 47.80 | 0.00 | 0.00 |
| Annual Sum or Average | 88.87 | 105.34 | 92.34 | 3.80 | 88.53 | 0.00 | 0.00 |
| Minimum of Months | 5.05 | 25.39 | 47.80 | 0.00 | 47.80 | 0.00 | 0.00 |
| Maximum of Months | 192.68 | 203.83 | 138.81 | 22.80 | 116.76 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: T S1 APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 465.45 | 181.27 | 410.12 | 318.01 | 92.11 | 0.00 | 0.00 |
| February | 475.79 | 166.64 | 410.02 | 300.58 | 109.44 | 0.00 | 0.00 |
| March | 350.38 | 132.83 | 295.14 | 176.75 | 118.39 | 0.00 | 0.00 |
| April | 294.30 | 94.29 | 239.51 | 101.83 | 137.68 | 0.00 | 0.00 |
| May | 194.01 | 68.50 | 156.65 | 35.15 | 121.49 | 0.00 | 0.00 |
| June | 191.19 | 43.77 | 131.80 | 16.29 | 115.51 | 0.00 | 0.00 |
| July | 232.01 | 26.50 | 147.19 | 24.69 | 122.50 | 0.00 | 0.00 |
| August | 297.00 | 31.93 | 198.24 | 62.93 | 135.31 | 0.00 | 0.00 |
| September | 393.78 | 58.76 | 283.34 | 160.69 | 122.65 | 0.00 | 0.00 |
| October | 475.61 | 100.97 | 376.78 | 276.83 | 99.95 | 0.00 | 0.00 |
| November | 498.71 | 143.37 | 425.60 | 327.36 | 98.24 | 0.00 | 0.00 |
| December | 514.55 | 185.38 | 450.43 | 371.55 | 78.88 | 0.00 | 0.00 |
| Annual Sum or Average | 364.55 | 102.52 | 293.04 | 180.40 | 112.64 | 0.00 | 0.00 |
| Minimum of Months | 191.19 | 26.50 | 131.80 | 16.29 | 78.88 | 0.00 | 0.00 |
| Maximum of Months | 514.55 | 185.38 | 450.43 | 371.55 | 137.68 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: T S2 APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 465.38 | 181.21 | 410.12 | 318.01 | 92.11 | 0.00 | 0.00 |
| February | 475.70 | 166.54 | 410.02 | 300.58 | 109.44 | 0.00 | 0.00 |
| March | 350.22 | 132.78 | 295.14 | 176.75 | 118.39 | 0.00 | 0.00 |
| April | 294.07 | 94.25 | 239.51 | 101.83 | 137.68 | 0.00 | 0.00 |
| May | 193.84 | 68.47 | 156.65 | 35.15 | 121.49 | 0.00 | 0.00 |
| June | 191.09 | 43.74 | 131.80 | 16.29 | 115.51 | 0.00 | 0.00 |
| July | 231.96 | 26.49 | 147.19 | 24.69 | 122.50 | 0.00 | 0.00 |
| August | 296.95 | 31.91 | 198.24 | 62.93 | 135.31 | 0.00 | 0.00 |
| September | 393.72 | 58.73 | 283.34 | 160.69 | 122.65 | 0.00 | 0.00 |
| October | 475.52 | 100.92 | 376.78 | 276.83 | 99.95 | 0.00 | 0.00 |
| November | 498.61 | 143.30 | 425.60 | 327.36 | 98.24 | 0.00 | 0.00 |
| December | 514.46 | 185.31 | 450.43 | 371.55 | 78.88 | 0.00 | 0.00 |
| Annual Sum or Average | 364.45 | 102.47 | 293.04 | 180.40 | 112.64 | 0.00 | 0.00 |
| Minimum of Months | 191.09 | 26.49 | 131.80 | 16.29 | 78.88 | 0.00 | 0.00 |
| Maximum of Months | 514.46 | 185.31 | 450.43 | 371.55 | 137.68 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: T CORRIDOR
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 21.54 | 30.00 | 24.76 | 13.94 | 10.83 | 0.00 | 0.00 |
| February | 27.99 | 27.40 | 29.56 | 15.83 | 13.73 | 0.00 | 0.00 |
| March | 42.32 | 21.25 | 39.52 | 22.50 | 17.02 | 0.00 | 0.00 |
| April | 62.68 | 15.07 | 53.77 | 30.65 | 23.13 | 0.00 | 0.00 |
| May | 62.57 | 11.53 | 51.28 | 29.21 | 22.07 | 0.00 | 0.00 |
| June | 73.54 | 7.63 | 55.34 | 34.10 | 21.24 | 0.00 | 0.00 |
| July | 70.83 | 5.23 | 51.26 | 29.34 | 21.92 | 0.00 | 0.00 |
| August | 67.64 | 6.08 | 50.55 | 27.83 | 22.72 | 0.00 | 0.00 |
| September | 53.45 | 10.26 | 42.12 | 23.54 | 18.59 | 0.00 | 0.00 |
| October | 41.95 | 16.97 | 36.83 | 23.40 | 13.42 | 0.00 | 0.00 |
| November | 27.88 | 24.08 | 28.64 | 16.82 | 11.82 | 0.00 | 0.00 |
| December | 20.31 | 31.49 | 23.28 | 14.20 | 9.09 | 0.00 | 0.00 |
| Annual Sum or Average | 47.81 | 17.20 | 40.62 | 23.48 | 17.14 | 0.00 | 0.00 |
| Minimum of Months | 20.31 | 5.23 | 23.28 | 13.94 | 9.09 | 0.00 | 0.00 |
| Maximum of Months | 73.54 | 31.49 | 55.34 | 34.10 | 23.13 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: G CORRIDOR
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 66.88 | 84.46 | 73.76 | 41.51 | 32.24 | 0.00 | 0.00 |
| February | 86.96 | 76.16 | 88.03 | 47.14 | 40.89 | 0.00 | 0.00 |
| March | 129.80 | 59.15 | 117.71 | 67.01 | 50.70 | 0.00 | 0.00 |
| April | 189.95 | 43.06 | 160.15 | 91.27 | 68.88 | 0.00 | 0.00 |
| May | 187.77 | 34.49 | 152.73 | 86.99 | 65.74 | 0.00 | 0.00 |
| June | 218.52 | 23.81 | 164.82 | 101.57 | 63.25 | 0.00 | 0.00 |
| July | 209.91 | 17.20 | 152.66 | 87.39 | 65.27 | 0.00 | 0.00 |
| August | 200.97 | 19.68 | 150.55 | 82.88 | 67.67 | 0.00 | 0.00 |
| September | 158.82 | 32.40 | 125.45 | 70.10 | 55.36 | 0.00 | 0.00 |
| October | 124.08 | 53.16 | 109.68 | 69.70 | 39.97 | 0.00 | 0.00 |
| November | 83.73 | 72.18 | 85.30 | 50.10 | 35.20 | 0.00 | 0.00 |
| December | 62.39 | 89.27 | 69.34 | 42.28 | 27.07 | 0.00 | 0.00 |
| Annual Sum or Average | 143.56 | 50.29 | 120.97 | 69.92 | 51.05 | 0.00 | 0.00 |
| Minimum of Months | 62.39 | 17.20 | 69.34 | 41.51 | 27.07 | 0.00 | 0.00 |
| Maximum of Months | 218.52 | 89.27 | 164.82 | 101.57 | 68.88 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: M CORRIDOR
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 20.50 | 32.47 | 24.76 | 13.94 | 10.83 | 0.00 | 0.00 |
| February | 27.04 | 29.56 | 29.56 | 15.83 | 13.73 | 0.00 | 0.00 |
| March | 41.12 | 23.18 | 39.52 | 22.50 | 17.02 | 0.00 | 0.00 |
| April | 61.50 | 16.41 | 53.77 | 30.65 | 23.13 | 0.00 | 0.00 |
| May | 61.98 | 12.35 | 51.28 | 29.21 | 22.07 | 0.00 | 0.00 |
| June | 73.68 | 7.91 | 55.34 | 34.10 | 21.24 | 0.00 | 0.00 |
| July | 71.35 | 5.28 | 51.26 | 29.34 | 21.92 | 0.00 | 0.00 |
| August | 68.03 | 6.16 | 50.55 | 27.83 | 22.72 | 0.00 | 0.00 |
| September | 53.35 | 10.69 | 42.12 | 23.54 | 18.59 | 0.00 | 0.00 |
| October | 40.98 | 18.59 | 36.83 | 23.40 | 13.42 | 0.00 | 0.00 |
| November | 26.76 | 26.60 | 28.64 | 16.82 | 11.82 | 0.00 | 0.00 |
| December | 19.52 | 34.25 | 23.28 | 14.20 | 9.09 | 0.00 | 0.00 |
| Annual Sum or Average | 47.24 | 18.56 | 40.62 | 23.48 | 17.14 | 0.00 | 0.00 |
| Minimum of Months | 19.52 | 5.28 | 23.28 | 13.94 | 9.09 | 0.00 | 0.00 |
| Maximum of Months | 73.68 | 34.25 | 55.34 | 34.10 | 23.13 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: G SW APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.150654E+10 | 0.811361E+09 | 0.138083E+10 | 0.101267E+10 | 0.368156E+09 | 0.00 | 0.00 |
| February | 0.149402E+10 | 0.664372E+09 | 0.131937E+10 | 0.915950E+09 | 0.403416E+09 | 0.00 | 0.00 |
| March | 0.140038E+10 | 0.571076E+09 | 0.119707E+10 | 0.689867E+09 | 0.507200E+09 | 0.00 | 0.00 |
| April | 0.136358E+10 | 0.394036E+09 | 0.112206E+10 | 0.530346E+09 | 0.591717E+09 | 0.00 | 0.00 |
| May | 0.114090E+10 | 0.301350E+09 | 0.913223E+09 | 0.349225E+09 | 0.563998E+09 | 0.00 | 0.00 |
| June | 0.120791E+10 | 0.193180E+09 | 0.850884E+09 | 0.326020E+09 | 0.524864E+09 | 0.00 | 0.00 |
| July | 0.131750E+10 | 0.122684E+09 | 0.869746E+09 | 0.298857E+09 | 0.570889E+09 | 0.00 | 0.00 |
| August | 0.147954E+10 | 0.149386E+09 | 0.101629E+10 | 0.392641E+09 | 0.623651E+09 | 0.00 | 0.00 |
| September | 0.158517E+10 | 0.266428E+09 | 0.116056E+10 | 0.641455E+09 | 0.519101E+09 | 0.00 | 0.00 |
| October | 0.173154E+10 | 0.485818E+09 | 0.141031E+10 | 0.990649E+09 | 0.419662E+09 | 0.00 | 0.00 |
| November | 0.157442E+10 | 0.661226E+09 | 0.140767E+10 | 0.102745E+10 | 0.380223E+09 | 0.00 | 0.00 |
| December | 0.161486E+10 | 0.835811E+09 | 0.147864E+10 | 0.116571E+10 | 0.312934E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.174164E+11 | 0.545673E+10 | 0.141267E+11 | 0.834084E+10 | 0.578581E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.114090E+10 | 0.122684E+09 | 0.850884E+09 | 0.298857E+09 | 0.312934E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.173154E+10 | 0.835811E+09 | 0.147864E+10 | 0.116571E+10 | 0.623651E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: G NW APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.308081E+09 | 0.837240E+09 | 0.432788E+09 | 0.160904E+09 | 0.271884E+09 | 0.00 | 0.00 |
| February | 0.416107E+09 | 0.668765E+09 | 0.497258E+09 | 0.188785E+09 | 0.308473E+09 | 0.00 | 0.00 |
| March | 0.634116E+09 | 0.556602E+09 | 0.643771E+09 | 0.216483E+09 | 0.427288E+09 | 0.00 | 0.00 |
| April | 0.857302E+09 | 0.363762E+09 | 0.793027E+09 | 0.269454E+09 | 0.523573E+09 | 0.00 | 0.00 |
| May | 0.964498E+09 | 0.286154E+09 | 0.821486E+09 | 0.276741E+09 | 0.544745E+09 | 0.00 | 0.00 |
| June | 0.120673E+10 | 0.180567E+09 | 0.869062E+09 | 0.342883E+09 | 0.526179E+09 | 0.00 | 0.00 |
| July | 0.120603E+10 | 0.117475E+09 | 0.815869E+09 | 0.260364E+09 | 0.555505E+09 | 0.00 | 0.00 |
| August | 0.111760E+10 | 0.141192E+09 | 0.802977E+09 | 0.232369E+09 | 0.570608E+09 | 0.00 | 0.00 |
| September | 0.850581E+09 | 0.260719E+09 | 0.671215E+09 | 0.225093E+09 | 0.446121E+09 | 0.00 | 0.00 |
| October | 0.608580E+09 | 0.488358E+09 | 0.589959E+09 | 0.249187E+09 | 0.340772E+09 | 0.00 | 0.00 |
| November | 0.358886E+09 | 0.635633E+09 | 0.459702E+09 | 0.178941E+09 | 0.280761E+09 | 0.00 | 0.00 |
| December | 0.251453E+09 | 0.862521E+09 | 0.400243E+09 | 0.170554E+09 | 0.229689E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.877997E+10 | 0.539899E+10 | 0.779736E+10 | 0.277176E+10 | 0.502560E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.251453E+09 | 0.117475E+09 | 0.400243E+09 | 0.160904E+09 | 0.229689E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.120673E+10 | 0.862521E+09 | 0.869062E+09 | 0.342883E+09 | 0.570608E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: OFFICE
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.149628E+10 | 0.797841E+09 | 0.137489E+10 | 0.100735E+10 | 0.367539E+09 | 0.00 | 0.00 |
| February | 0.145273E+10 | 0.652934E+09 | 0.128991E+10 | 0.886729E+09 | 0.403180E+09 | 0.00 | 0.00 |
| March | 0.141623E+10 | 0.578945E+09 | 0.123166E+10 | 0.724546E+09 | 0.507109E+09 | 0.00 | 0.00 |
| April | 0.142840E+10 | 0.413630E+09 | 0.120167E+10 | 0.594983E+09 | 0.606685E+09 | 0.00 | 0.00 |
| May | 0.120085E+10 | 0.343935E+09 | 0.991978E+09 | 0.420199E+09 | 0.571779E+09 | 0.00 | 0.00 |
| June | 0.125528E+10 | 0.237751E+09 | 0.939405E+09 | 0.410617E+09 | 0.528788E+09 | 0.00 | 0.00 |
| July | 0.136586E+10 | 0.197850E+09 | 0.966403E+09 | 0.393665E+09 | 0.572738E+09 | 0.00 | 0.00 |
| August | 0.151185E+10 | 0.222556E+09 | 0.109523E+10 | 0.479197E+09 | 0.616031E+09 | 0.00 | 0.00 |
| September | 0.156156E+10 | 0.339600E+09 | 0.118943E+10 | 0.670752E+09 | 0.518673E+09 | 0.00 | 0.00 |
| October | 0.170144E+10 | 0.544855E+09 | 0.142022E+10 | 0.100271E+10 | 0.417518E+09 | 0.00 | 0.00 |
| November | 0.156850E+10 | 0.686716E+09 | 0.141254E+10 | 0.103022E+10 | 0.382318E+09 | 0.00 | 0.00 |
| December | 0.159637E+10 | 0.839881E+09 | 0.146633E+10 | 0.115361E+10 | 0.312716E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.175554E+11 | 0.585650E+10 | 0.145796E+11 | 0.877458E+10 | 0.580507E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.120085E+10 | 0.197850E+09 | 0.939405E+09 | 0.393665E+09 | 0.312716E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.170144E+10 | 0.839881E+09 | 0.146633E+10 | 0.115361E+10 | 0.616031E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: G NE APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.255860E+09 | 0.793210E+09 | 0.426850E+09 | 0.155583E+09 | 0.271267E+09 | 0.00 | 0.00 |
| February | 0.349565E+09 | 0.637628E+09 | 0.467801E+09 | 0.159564E+09 | 0.308237E+09 | 0.00 | 0.00 |
| March | 0.648193E+09 | 0.523580E+09 | 0.678359E+09 | 0.251162E+09 | 0.427197E+09 | 0.00 | 0.00 |
| April | 0.947332E+09 | 0.352367E+09 | 0.872631E+09 | 0.334091E+09 | 0.538541E+09 | 0.00 | 0.00 |
| May | 0.106341E+10 | 0.283620E+09 | 0.900240E+09 | 0.347714E+09 | 0.552526E+09 | 0.00 | 0.00 |
| June | 0.132252E+10 | 0.178945E+09 | 0.957583E+09 | 0.427480E+09 | 0.530103E+09 | 0.00 | 0.00 |
| July | 0.133388E+10 | 0.116328E+09 | 0.912526E+09 | 0.355172E+09 | 0.557354E+09 | 0.00 | 0.00 |
| August | 0.121883E+10 | 0.138191E+09 | 0.881913E+09 | 0.318925E+09 | 0.562988E+09 | 0.00 | 0.00 |
| September | 0.873856E+09 | 0.247506E+09 | 0.700085E+09 | 0.254391E+09 | 0.445694E+09 | 0.00 | 0.00 |
| October | 0.588033E+09 | 0.456052E+09 | 0.599873E+09 | 0.261244E+09 | 0.338629E+09 | 0.00 | 0.00 |
| November | 0.340139E+09 | 0.610738E+09 | 0.464566E+09 | 0.181709E+09 | 0.282857E+09 | 0.00 | 0.00 |
| December | 0.207090E+09 | 0.833061E+09 | 0.387929E+09 | 0.158458E+09 | 0.229471E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.914872E+10 | 0.517123E+10 | 0.825036E+10 | 0.320549E+10 | 0.504486E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.207090E+09 | 0.116328E+09 | 0.387929E+09 | 0.155583E+09 | 0.229471E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.133388E+10 | 0.833061E+09 | 0.957583E+09 | 0.427480E+09 | 0.562988E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: G N1 APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 41208385.36 | 0.526654E+09 | 0.150424E+09 | 0.00 | 0.150424E+09 | 0.00 | 0.00 |
| February | 76771700.51 | 0.418470E+09 | 0.169811E+09 | 0.00 | 0.169811E+09 | 0.00 | 0.00 |
| March | 0.176658E+09 | 0.345670E+09 | 0.237211E+09 | 23134.55 | 0.237188E+09 | 0.00 | 0.00 |
| April | 0.259897E+09 | 0.223192E+09 | 0.291771E+09 | 3046518.65 | 0.288725E+09 | 0.00 | 0.00 |
| May | 0.350404E+09 | 0.174000E+09 | 0.327828E+09 | 21674088.24 | 0.306154E+09 | 0.00 | 0.00 |
| June | 0.509637E+09 | 0.108035E+09 | 0.359800E+09 | 59092131.21 | 0.300708E+09 | 0.00 | 0.00 |
| July | 0.522615E+09 | 68923349.66 | 0.340370E+09 | 27644461.40 | 0.312725E+09 | 0.00 | 0.00 |
| August | 0.444722E+09 | 82522104.97 | 0.317651E+09 | 8286352.67 | 0.309364E+09 | 0.00 | 0.00 |
| September | 0.290793E+09 | 0.155771E+09 | 0.245065E+09 | 147417.50 | 0.244917E+09 | 0.00 | 0.00 |
| October | 0.138343E+09 | 0.302376E+09 | 0.188808E+09 | 0.00 | 0.188808E+09 | 0.00 | 0.00 |
| November | 55449901.78 | 0.401850E+09 | 0.155171E+09 | 0.00 | 0.155171E+09 | 0.00 | 0.00 |
| December | 14121407.43 | 0.552721E+09 | 0.128034E+09 | 0.00 | 0.128034E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.288062E+10 | 0.336018E+10 | 0.291194E+10 | 0.119914E+09 | 0.279203E+10 | 0.00 | 0.00 |
| Minimum of Months | 14121407.43 | 68923349.66 | 0.128034E+09 | 0.00 | 0.128034E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.522615E+09 | 0.552721E+09 | 0.359800E+09 | 59092131.21 | 0.312725E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: G N2 APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 41181817.25 | 0.526611E+09 | 0.150424E+09 | 0.00 | 0.150424E+09 | 0.00 | 0.00 |
| February | 76757635.65 | 0.418367E+09 | 0.169811E+09 | 0.00 | 0.169811E+09 | 0.00 | 0.00 |
| March | 0.176527E+09 | 0.345703E+09 | 0.237211E+09 | 23134.55 | 0.237188E+09 | 0.00 | 0.00 |
| April | 0.259424E+09 | 0.223462E+09 | 0.291771E+09 | 3046518.65 | 0.288725E+09 | 0.00 | 0.00 |
| May | 0.350033E+09 | 0.174206E+09 | 0.327828E+09 | 21674088.24 | 0.306154E+09 | 0.00 | 0.00 |
| June | 0.509516E+09 | 0.108054E+09 | 0.359800E+09 | 59092131.21 | 0.300708E+09 | 0.00 | 0.00 |
| July | 0.522517E+09 | 68944316.42 | 0.340370E+09 | 27644461.40 | 0.312725E+09 | 0.00 | 0.00 |
| August | 0.444640E+09 | 82526025.40 | 0.317651E+09 | 8286352.67 | 0.309364E+09 | 0.00 | 0.00 |
| September | 0.290737E+09 | 0.155757E+09 | 0.245065E+09 | 147417.50 | 0.244917E+09 | 0.00 | 0.00 |
| October | 0.138226E+09 | 0.302434E+09 | 0.188808E+09 | 0.00 | 0.188808E+09 | 0.00 | 0.00 |
| November | 55379876.04 | 0.401793E+09 | 0.155171E+09 | 0.00 | 0.155171E+09 | 0.00 | 0.00 |
| December | 14107513.99 | 0.552660E+09 | 0.128034E+09 | 0.00 | 0.128034E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.287905E+10 | 0.336052E+10 | 0.291194E+10 | 0.119914E+09 | 0.279203E+10 | 0.00 | 0.00 |
| Minimum of Months | 14107513.99 | 68944316.42 | 0.128034E+09 | 0.00 | 0.128034E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.522517E+09 | 0.552660E+09 | 0.359800E+09 | 59092131.21 | 0.312725E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: G S1 APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.125694E+10 | 0.499454E+09 | 0.109847E+10 | 0.851769E+09 | 0.246697E+09 | 0.00 | 0.00 |
| February | 0.116657E+10 | 0.408332E+09 | 0.991919E+09 | 0.727165E+09 | 0.264754E+09 | 0.00 | 0.00 |
| March | 0.954352E+09 | 0.357585E+09 | 0.790507E+09 | 0.473407E+09 | 0.317100E+09 | 0.00 | 0.00 |
| April | 0.776048E+09 | 0.249262E+09 | 0.620807E+09 | 0.263938E+09 | 0.356868E+09 | 0.00 | 0.00 |
| May | 0.529845E+09 | 0.188200E+09 | 0.419565E+09 | 94158394.50 | 0.325407E+09 | 0.00 | 0.00 |
| June | 0.505819E+09 | 0.115978E+09 | 0.341622E+09 | 42228752.46 | 0.299393E+09 | 0.00 | 0.00 |
| July | 0.633204E+09 | 72479168.49 | 0.394246E+09 | 66136923.55 | 0.328110E+09 | 0.00 | 0.00 |
| August | 0.807368E+09 | 88229867.93 | 0.530966E+09 | 0.168559E+09 | 0.362407E+09 | 0.00 | 0.00 |
| September | 0.103045E+10 | 0.159466E+09 | 0.734405E+09 | 0.416509E+09 | 0.317897E+09 | 0.00 | 0.00 |
| October | 0.127576E+10 | 0.293504E+09 | 0.100916E+10 | 0.741462E+09 | 0.267698E+09 | 0.00 | 0.00 |
| November | 0.128998E+10 | 0.408093E+09 | 0.110314E+10 | 0.848511E+09 | 0.254632E+09 | 0.00 | 0.00 |
| December | 0.138790E+10 | 0.516487E+09 | 0.120643E+10 | 0.995151E+09 | 0.211279E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.116142E+11 | 0.335707E+10 | 0.924124E+10 | 0.568900E+10 | 0.355224E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.505819E+09 | 72479168.49 | 0.341622E+09 | 42228752.46 | 0.211279E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.138790E+10 | 0.516487E+09 | 0.120643E+10 | 0.995151E+09 | 0.362407E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: G S2 APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.125694E+10 | 0.499223E+09 | 0.109847E+10 | 0.851769E+09 | 0.246697E+09 | 0.00 | 0.00 |
| February | 0.116654E+10 | 0.408234E+09 | 0.991919E+09 | 0.727165E+09 | 0.264754E+09 | 0.00 | 0.00 |
| March | 0.952976E+09 | 0.359369E+09 | 0.790507E+09 | 0.473407E+09 | 0.317100E+09 | 0.00 | 0.00 |
| April | 0.774259E+09 | 0.251412E+09 | 0.620807E+09 | 0.263938E+09 | 0.356868E+09 | 0.00 | 0.00 |
| May | 0.528021E+09 | 0.190165E+09 | 0.419565E+09 | 94158394.50 | 0.325407E+09 | 0.00 | 0.00 |
| June | 0.504025E+09 | 0.117547E+09 | 0.341622E+09 | 42228752.46 | 0.299393E+09 | 0.00 | 0.00 |
| July | 0.630960E+09 | 74371617.00 | 0.394246E+09 | 66136923.55 | 0.328110E+09 | 0.00 | 0.00 |
| August | 0.805415E+09 | 90125434.54 | 0.530966E+09 | 0.168559E+09 | 0.362407E+09 | 0.00 | 0.00 |
| September | 0.102902E+10 | 0.161326E+09 | 0.734405E+09 | 0.416509E+09 | 0.317897E+09 | 0.00 | 0.00 |
| October | 0.127453E+10 | 0.295327E+09 | 0.100916E+10 | 0.741462E+09 | 0.267698E+09 | 0.00 | 0.00 |
| November | 0.128927E+10 | 0.409160E+09 | 0.110314E+10 | 0.848511E+09 | 0.254632E+09 | 0.00 | 0.00 |
| December | 0.138761E+10 | 0.516798E+09 | 0.120643E+10 | 0.995151E+09 | 0.211279E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.115996E+11 | 0.337306E+10 | 0.924124E+10 | 0.568900E+10 | 0.355224E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.504025E+09 | 74371617.00 | 0.341622E+09 | 42228752.46 | 0.211279E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.138761E+10 | 0.516798E+09 | 0.120643E+10 | 0.995151E+09 | 0.362407E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: M SW APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.148180E+10 | 0.843284E+09 | 0.138083E+10 | 0.101267E+10 | 0.368156E+09 | 0.00 | 0.00 |
| February | 0.146442E+10 | 0.702774E+09 | 0.131937E+10 | 0.915950E+09 | 0.403416E+09 | 0.00 | 0.00 |
| March | 0.135698E+10 | 0.627962E+09 | 0.119707E+10 | 0.689867E+09 | 0.507200E+09 | 0.00 | 0.00 |
| April | 0.133001E+10 | 0.429236E+09 | 0.112206E+10 | 0.530346E+09 | 0.591717E+09 | 0.00 | 0.00 |
| May | 0.111990E+10 | 0.318834E+09 | 0.913223E+09 | 0.349225E+09 | 0.563998E+09 | 0.00 | 0.00 |
| June | 0.120033E+10 | 0.198153E+09 | 0.850884E+09 | 0.326020E+09 | 0.524864E+09 | 0.00 | 0.00 |
| July | 0.131436E+10 | 0.122606E+09 | 0.869746E+09 | 0.298857E+09 | 0.570889E+09 | 0.00 | 0.00 |
| August | 0.147711E+10 | 0.147667E+09 | 0.101629E+10 | 0.392641E+09 | 0.623651E+09 | 0.00 | 0.00 |
| September | 0.158262E+10 | 0.263084E+09 | 0.116056E+10 | 0.641455E+09 | 0.519101E+09 | 0.00 | 0.00 |
| October | 0.172762E+10 | 0.482029E+09 | 0.141031E+10 | 0.990649E+09 | 0.419662E+09 | 0.00 | 0.00 |
| November | 0.156603E+10 | 0.664096E+09 | 0.140767E+10 | 0.102745E+10 | 0.380223E+09 | 0.00 | 0.00 |
| December | 0.159462E+10 | 0.859875E+09 | 0.147864E+10 | 0.116571E+10 | 0.312934E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.172158E+11 | 0.565960E+10 | 0.141267E+11 | 0.834084E+10 | 0.578581E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.111990E+10 | 0.122606E+09 | 0.850884E+09 | 0.298857E+09 | 0.312934E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.172762E+10 | 0.859875E+09 | 0.147864E+10 | 0.116571E+10 | 0.623651E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: M NW APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.296010E+09 | 0.866460E+09 | 0.432788E+09 | 0.160904E+09 | 0.271884E+09 | 0.00 | 0.00 |
| February | 0.398490E+09 | 0.703417E+09 | 0.497258E+09 | 0.188785E+09 | 0.308473E+09 | 0.00 | 0.00 |
| March | 0.598720E+09 | 0.609363E+09 | 0.643771E+09 | 0.216483E+09 | 0.427288E+09 | 0.00 | 0.00 |
| April | 0.813795E+09 | 0.412348E+09 | 0.793027E+09 | 0.269454E+09 | 0.523573E+09 | 0.00 | 0.00 |
| May | 0.940129E+09 | 0.305491E+09 | 0.821486E+09 | 0.276741E+09 | 0.544745E+09 | 0.00 | 0.00 |
| June | 0.119859E+10 | 0.185054E+09 | 0.869062E+09 | 0.342883E+09 | 0.526179E+09 | 0.00 | 0.00 |
| July | 0.120329E+10 | 0.117580E+09 | 0.815869E+09 | 0.260364E+09 | 0.555505E+09 | 0.00 | 0.00 |
| August | 0.111592E+10 | 0.140410E+09 | 0.802977E+09 | 0.232369E+09 | 0.570608E+09 | 0.00 | 0.00 |
| September | 0.849411E+09 | 0.259693E+09 | 0.671215E+09 | 0.225093E+09 | 0.446121E+09 | 0.00 | 0.00 |
| October | 0.607147E+09 | 0.488556E+09 | 0.589959E+09 | 0.249187E+09 | 0.340772E+09 | 0.00 | 0.00 |
| November | 0.352325E+09 | 0.648462E+09 | 0.459702E+09 | 0.178941E+09 | 0.280761E+09 | 0.00 | 0.00 |
| December | 0.244679E+09 | 0.883845E+09 | 0.400243E+09 | 0.170554E+09 | 0.229689E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.861851E+10 | 0.562068E+10 | 0.779736E+10 | 0.277176E+10 | 0.502560E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.244679E+09 | 0.117580E+09 | 0.400243E+09 | 0.160904E+09 | 0.229689E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.120329E+10 | 0.883845E+09 | 0.869062E+09 | 0.342883E+09 | 0.570608E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: M SE APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.146447E+10 | 0.836256E+09 | 0.137489E+10 | 0.100735E+10 | 0.367539E+09 | 0.00 | 0.00 |
| February | 0.141770E+10 | 0.691819E+09 | 0.128991E+10 | 0.886729E+09 | 0.403180E+09 | 0.00 | 0.00 |
| March | 0.138232E+10 | 0.609300E+09 | 0.123166E+10 | 0.724546E+09 | 0.507109E+09 | 0.00 | 0.00 |
| April | 0.141591E+10 | 0.407798E+09 | 0.120167E+10 | 0.594983E+09 | 0.606685E+09 | 0.00 | 0.00 |
| May | 0.121477E+10 | 0.307854E+09 | 0.991978E+09 | 0.420199E+09 | 0.571779E+09 | 0.00 | 0.00 |
| June | 0.130241E+10 | 0.181952E+09 | 0.939405E+09 | 0.410617E+09 | 0.528788E+09 | 0.00 | 0.00 |
| July | 0.143843E+10 | 0.116824E+09 | 0.966403E+09 | 0.393665E+09 | 0.572738E+09 | 0.00 | 0.00 |
| August | 0.157315E+10 | 0.138954E+09 | 0.109523E+10 | 0.479197E+09 | 0.616031E+09 | 0.00 | 0.00 |
| September | 0.160825E+10 | 0.251742E+09 | 0.118943E+10 | 0.670752E+09 | 0.518673E+09 | 0.00 | 0.00 |
| October | 0.172950E+10 | 0.470675E+09 | 0.142022E+10 | 0.100271E+10 | 0.417518E+09 | 0.00 | 0.00 |
| November | 0.156615E+10 | 0.660744E+09 | 0.141254E+10 | 0.103022E+10 | 0.382318E+09 | 0.00 | 0.00 |
| December | 0.157423E+10 | 0.856707E+09 | 0.146633E+10 | 0.115361E+10 | 0.312716E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.176873E+11 | 0.553062E+10 | 0.145796E+11 | 0.877458E+10 | 0.580507E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.121477E+10 | 0.116824E+09 | 0.939405E+09 | 0.393665E+09 | 0.312716E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.172950E+10 | 0.856707E+09 | 0.146633E+10 | 0.115361E+10 | 0.616031E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: M NE APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.243137E+09 | 0.820314E+09 | 0.426850E+09 | 0.155583E+09 | 0.271267E+09 | 0.00 | 0.00 |
| February | 0.330852E+09 | 0.669986E+09 | 0.467801E+09 | 0.159564E+09 | 0.308237E+09 | 0.00 | 0.00 |
| March | 0.607734E+09 | 0.575634E+09 | 0.678359E+09 | 0.251162E+09 | 0.427197E+09 | 0.00 | 0.00 |
| April | 0.901414E+09 | 0.396485E+09 | 0.872631E+09 | 0.334091E+09 | 0.538541E+09 | 0.00 | 0.00 |
| May | 0.104061E+10 | 0.300854E+09 | 0.900240E+09 | 0.347714E+09 | 0.552526E+09 | 0.00 | 0.00 |
| June | 0.131452E+10 | 0.182656E+09 | 0.957583E+09 | 0.427480E+09 | 0.530103E+09 | 0.00 | 0.00 |
| July | 0.133134E+10 | 0.115818E+09 | 0.912526E+09 | 0.355172E+09 | 0.557354E+09 | 0.00 | 0.00 |
| August | 0.121705E+10 | 0.136888E+09 | 0.881913E+09 | 0.318925E+09 | 0.562988E+09 | 0.00 | 0.00 |
| September | 0.872659E+09 | 0.246166E+09 | 0.700085E+09 | 0.254391E+09 | 0.445694E+09 | 0.00 | 0.00 |
| October | 0.585889E+09 | 0.455793E+09 | 0.599873E+09 | 0.261244E+09 | 0.338629E+09 | 0.00 | 0.00 |
| November | 0.332539E+09 | 0.622449E+09 | 0.464566E+09 | 0.181709E+09 | 0.282857E+09 | 0.00 | 0.00 |
| December | 0.199824E+09 | 0.853264E+09 | 0.387929E+09 | 0.158458E+09 | 0.229471E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.897756E+10 | 0.537631E+10 | 0.825036E+10 | 0.320549E+10 | 0.504486E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.199824E+09 | 0.115818E+09 | 0.387929E+09 | 0.155583E+09 | 0.229471E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.133134E+10 | 0.853264E+09 | 0.957583E+09 | 0.427480E+09 | 0.562988E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: M N1 APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 36654557.36 | 0.545293E+09 | 0.150424E+09 | 0.00 | 0.150424E+09 | 0.00 | 0.00 |
| February | 69283248.69 | 0.439700E+09 | 0.169811E+09 | 0.00 | 0.169811E+09 | 0.00 | 0.00 |
| March | 0.158011E+09 | 0.380933E+09 | 0.237211E+09 | 23134.55 | 0.237188E+09 | 0.00 | 0.00 |
| April | 0.237019E+09 | 0.252377E+09 | 0.291771E+09 | 3046518.65 | 0.288725E+09 | 0.00 | 0.00 |
| May | 0.339515E+09 | 0.182945E+09 | 0.327828E+09 | 21674088.24 | 0.306154E+09 | 0.00 | 0.00 |
| June | 0.506701E+09 | 0.109785E+09 | 0.359800E+09 | 59092131.21 | 0.300708E+09 | 0.00 | 0.00 |
| July | 0.522333E+09 | 68676034.51 | 0.340370E+09 | 27644461.40 | 0.312725E+09 | 0.00 | 0.00 |
| August | 0.444736E+09 | 82057913.40 | 0.317651E+09 | 8286352.67 | 0.309364E+09 | 0.00 | 0.00 |
| September | 0.290779E+09 | 0.155550E+09 | 0.245065E+09 | 147417.50 | 0.244917E+09 | 0.00 | 0.00 |
| October | 0.137736E+09 | 0.304144E+09 | 0.188808E+09 | 0.00 | 0.188808E+09 | 0.00 | 0.00 |
| November | 52137346.64 | 0.412871E+09 | 0.155171E+09 | 0.00 | 0.155171E+09 | 0.00 | 0.00 |
| December | 12296932.24 | 0.567812E+09 | 0.128034E+09 | 0.00 | 0.128034E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.280720E+10 | 0.350214E+10 | 0.291194E+10 | 0.119914E+09 | 0.279203E+10 | 0.00 | 0.00 |
| Minimum of Months | 12296932.24 | 68676034.51 | 0.128034E+09 | 0.00 | 0.128034E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.522333E+09 | 0.567812E+09 | 0.359800E+09 | 59092131.21 | 0.312725E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: M N2 APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 36612307.63 | 0.545194E+09 | 0.150424E+09 | 0.00 | 0.150424E+09 | 0.00 | 0.00 |
| February | 69233886.81 | 0.439535E+09 | 0.169811E+09 | 0.00 | 0.169811E+09 | 0.00 | 0.00 |
| March | 0.157617E+09 | 0.381287E+09 | 0.237211E+09 | 23134.55 | 0.237188E+09 | 0.00 | 0.00 |
| April | 0.236675E+09 | 0.252554E+09 | 0.291771E+09 | 3046518.65 | 0.288725E+09 | 0.00 | 0.00 |
| May | 0.339310E+09 | 0.182999E+09 | 0.327828E+09 | 21674088.24 | 0.306154E+09 | 0.00 | 0.00 |
| June | 0.506612E+09 | 0.109772E+09 | 0.359800E+09 | 59092131.21 | 0.300708E+09 | 0.00 | 0.00 |
| July | 0.522254E+09 | 68675886.44 | 0.340370E+09 | 27644461.40 | 0.312725E+09 | 0.00 | 0.00 |
| August | 0.444664E+09 | 82046077.31 | 0.317651E+09 | 8286352.67 | 0.309364E+09 | 0.00 | 0.00 |
| September | 0.290722E+09 | 0.155526E+09 | 0.245065E+09 | 147417.50 | 0.244917E+09 | 0.00 | 0.00 |
| October | 0.137591E+09 | 0.304180E+09 | 0.188808E+09 | 0.00 | 0.188808E+09 | 0.00 | 0.00 |
| November | 52034610.21 | 0.412780E+09 | 0.155171E+09 | 0.00 | 0.155171E+09 | 0.00 | 0.00 |
| December | 12276635.31 | 0.567732E+09 | 0.128034E+09 | 0.00 | 0.128034E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.280560E+10 | 0.350228E+10 | 0.291194E+10 | 0.119914E+09 | 0.279203E+10 | 0.00 | 0.00 |
| Minimum of Months | 12276635.31 | 68675886.44 | 0.128034E+09 | 0.00 | 0.128034E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.522254E+09 | 0.567732E+09 | 0.359800E+09 | 59092131.21 | 0.312725E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: M S1 APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.124117E+10 | 0.520406E+09 | 0.109847E+10 | 0.851769E+09 | 0.246697E+09 | 0.00 | 0.00 |
| February | 0.114844E+10 | 0.432731E+09 | 0.991919E+09 | 0.727165E+09 | 0.264754E+09 | 0.00 | 0.00 |
| March | 0.930662E+09 | 0.391158E+09 | 0.790507E+09 | 0.473407E+09 | 0.317100E+09 | 0.00 | 0.00 |
| April | 0.760930E+09 | 0.266563E+09 | 0.620807E+09 | 0.263938E+09 | 0.356868E+09 | 0.00 | 0.00 |
| May | 0.521358E+09 | 0.196129E+09 | 0.419565E+09 | 94158394.50 | 0.325407E+09 | 0.00 | 0.00 |
| June | 0.503319E+09 | 0.117849E+09 | 0.341622E+09 | 42228752.46 | 0.299393E+09 | 0.00 | 0.00 |
| July | 0.632562E+09 | 72030509.90 | 0.394246E+09 | 66136923.55 | 0.328110E+09 | 0.00 | 0.00 |
| August | 0.806501E+09 | 87091990.23 | 0.530966E+09 | 0.168559E+09 | 0.362407E+09 | 0.00 | 0.00 |
| September | 0.102878E+10 | 0.157630E+09 | 0.734405E+09 | 0.416509E+09 | 0.317897E+09 | 0.00 | 0.00 |
| October | 0.127288E+10 | 0.292101E+09 | 0.100916E+10 | 0.741462E+09 | 0.267698E+09 | 0.00 | 0.00 |
| November | 0.128460E+10 | 0.410251E+09 | 0.110314E+10 | 0.848511E+09 | 0.254632E+09 | 0.00 | 0.00 |
| December | 0.137450E+10 | 0.533718E+09 | 0.120643E+10 | 0.995151E+09 | 0.211279E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.115057E+11 | 0.347766E+10 | 0.924124E+10 | 0.568900E+10 | 0.355224E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.503319E+09 | 72030509.90 | 0.341622E+09 | 42228752.46 | 0.211279E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.137450E+10 | 0.533718E+09 | 0.120643E+10 | 0.995151E+09 | 0.362407E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: M S2 APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.124106E+10 | 0.520411E+09 | 0.109847E+10 | 0.851769E+09 | 0.246697E+09 | 0.00 | 0.00 |
| February | 0.114840E+10 | 0.432563E+09 | 0.991919E+09 | 0.727165E+09 | 0.264754E+09 | 0.00 | 0.00 |
| March | 0.930455E+09 | 0.391256E+09 | 0.790507E+09 | 0.473407E+09 | 0.317100E+09 | 0.00 | 0.00 |
| April | 0.760787E+09 | 0.266571E+09 | 0.620807E+09 | 0.263938E+09 | 0.356868E+09 | 0.00 | 0.00 |
| May | 0.521219E+09 | 0.196159E+09 | 0.419565E+09 | 94158394.50 | 0.325407E+09 | 0.00 | 0.00 |
| June | 0.503229E+09 | 0.117838E+09 | 0.341622E+09 | 42228752.46 | 0.299393E+09 | 0.00 | 0.00 |
| July | 0.632485E+09 | 72029734.64 | 0.394246E+09 | 66136923.55 | 0.328110E+09 | 0.00 | 0.00 |
| August | 0.806435E+09 | 87079251.38 | 0.530966E+09 | 0.168559E+09 | 0.362407E+09 | 0.00 | 0.00 |
| September | 0.102873E+10 | 0.157604E+09 | 0.734405E+09 | 0.416509E+09 | 0.317897E+09 | 0.00 | 0.00 |
| October | 0.127282E+10 | 0.292076E+09 | 0.100916E+10 | 0.741462E+09 | 0.267698E+09 | 0.00 | 0.00 |
| November | 0.128452E+10 | 0.410223E+09 | 0.110314E+10 | 0.848511E+09 | 0.254632E+09 | 0.00 | 0.00 |
| December | 0.137441E+10 | 0.533657E+09 | 0.120643E+10 | 0.995151E+09 | 0.211279E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.115045E+11 | 0.347747E+10 | 0.924124E+10 | 0.568900E+10 | 0.355224E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.503229E+09 | 72029734.64 | 0.341622E+09 | 42228752.46 | 0.211279E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.137441E+10 | 0.533657E+09 | 0.120643E+10 | 0.995151E+09 | 0.362407E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: T SW APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.148352E+10 | 0.795715E+09 | 0.138083E+10 | 0.101267E+10 | 0.368156E+09 | 0.00 | 0.00 |
| February | 0.146224E+10 | 0.660788E+09 | 0.131937E+10 | 0.915950E+09 | 0.403416E+09 | 0.00 | 0.00 |
| March | 0.136262E+10 | 0.575397E+09 | 0.119707E+10 | 0.689867E+09 | 0.507200E+09 | 0.00 | 0.00 |
| April | 0.133233E+10 | 0.388627E+09 | 0.112206E+10 | 0.530346E+09 | 0.591717E+09 | 0.00 | 0.00 |
| May | 0.111684E+10 | 0.293872E+09 | 0.913223E+09 | 0.349225E+09 | 0.563998E+09 | 0.00 | 0.00 |
| June | 0.118550E+10 | 0.187712E+09 | 0.850884E+09 | 0.326020E+09 | 0.524864E+09 | 0.00 | 0.00 |
| July | 0.129312E+10 | 0.119248E+09 | 0.869746E+09 | 0.298857E+09 | 0.570889E+09 | 0.00 | 0.00 |
| August | 0.145666E+10 | 0.143211E+09 | 0.101629E+10 | 0.392641E+09 | 0.623651E+09 | 0.00 | 0.00 |
| September | 0.156872E+10 | 0.249997E+09 | 0.116056E+10 | 0.641455E+09 | 0.519101E+09 | 0.00 | 0.00 |
| October | 0.172850E+10 | 0.442177E+09 | 0.141031E+10 | 0.990649E+09 | 0.419662E+09 | 0.00 | 0.00 |
| November | 0.157484E+10 | 0.603939E+09 | 0.140767E+10 | 0.102745E+10 | 0.380223E+09 | 0.00 | 0.00 |
| December | 0.159421E+10 | 0.810453E+09 | 0.147864E+10 | 0.116571E+10 | 0.312934E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.171591E+11 | 0.527114E+10 | 0.141267E+11 | 0.834084E+10 | 0.578581E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.111684E+10 | 0.119248E+09 | 0.850884E+09 | 0.298857E+09 | 0.312934E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.172850E+10 | 0.810453E+09 | 0.147864E+10 | 0.116571E+10 | 0.623651E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: T NW APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.297751E+09 | 0.833970E+09 | 0.432788E+09 | 0.160904E+09 | 0.271884E+09 | 0.00 | 0.00 |
| February | 0.397498E+09 | 0.676409E+09 | 0.497258E+09 | 0.188785E+09 | 0.308473E+09 | 0.00 | 0.00 |
| March | 0.599239E+09 | 0.576086E+09 | 0.643771E+09 | 0.216483E+09 | 0.427288E+09 | 0.00 | 0.00 |
| April | 0.822002E+09 | 0.374505E+09 | 0.793027E+09 | 0.269454E+09 | 0.523573E+09 | 0.00 | 0.00 |
| May | 0.941307E+09 | 0.283450E+09 | 0.821486E+09 | 0.276741E+09 | 0.544745E+09 | 0.00 | 0.00 |
| June | 0.118542E+10 | 0.177325E+09 | 0.869062E+09 | 0.342883E+09 | 0.526179E+09 | 0.00 | 0.00 |
| July | 0.118337E+10 | 0.115044E+09 | 0.815869E+09 | 0.260364E+09 | 0.555505E+09 | 0.00 | 0.00 |
| August | 0.109877E+10 | 0.137086E+09 | 0.802977E+09 | 0.232369E+09 | 0.570608E+09 | 0.00 | 0.00 |
| September | 0.841863E+09 | 0.245888E+09 | 0.671215E+09 | 0.225093E+09 | 0.446121E+09 | 0.00 | 0.00 |
| October | 0.614128E+09 | 0.446079E+09 | 0.589959E+09 | 0.249187E+09 | 0.340772E+09 | 0.00 | 0.00 |
| November | 0.357090E+09 | 0.611013E+09 | 0.459702E+09 | 0.178941E+09 | 0.280761E+09 | 0.00 | 0.00 |
| December | 0.246245E+09 | 0.849142E+09 | 0.400243E+09 | 0.170554E+09 | 0.229689E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.858469E+10 | 0.532600E+10 | 0.779736E+10 | 0.277176E+10 | 0.502560E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.246245E+09 | 0.115044E+09 | 0.400243E+09 | 0.160904E+09 | 0.229689E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.118542E+10 | 0.849142E+09 | 0.869062E+09 | 0.342883E+09 | 0.570608E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: T SE APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.146666E+10 | 0.787795E+09 | 0.137489E+10 | 0.100735E+10 | 0.367539E+09 | 0.00 | 0.00 |
| February | 0.141548E+10 | 0.650546E+09 | 0.128991E+10 | 0.886729E+09 | 0.403180E+09 | 0.00 | 0.00 |
| March | 0.138894E+10 | 0.557474E+09 | 0.123166E+10 | 0.724546E+09 | 0.507109E+09 | 0.00 | 0.00 |
| April | 0.141837E+10 | 0.372427E+09 | 0.120167E+10 | 0.594983E+09 | 0.606685E+09 | 0.00 | 0.00 |
| May | 0.120981E+10 | 0.284510E+09 | 0.991978E+09 | 0.420199E+09 | 0.571779E+09 | 0.00 | 0.00 |
| June | 0.128670E+10 | 0.172883E+09 | 0.939405E+09 | 0.410617E+09 | 0.528788E+09 | 0.00 | 0.00 |
| July | 0.141622E+10 | 0.113282E+09 | 0.966403E+09 | 0.393665E+09 | 0.572738E+09 | 0.00 | 0.00 |
| August | 0.155179E+10 | 0.134635E+09 | 0.109523E+10 | 0.479197E+09 | 0.616031E+09 | 0.00 | 0.00 |
| September | 0.159408E+10 | 0.239396E+09 | 0.118943E+10 | 0.670752E+09 | 0.518673E+09 | 0.00 | 0.00 |
| October | 0.172934E+10 | 0.431900E+09 | 0.142022E+10 | 0.100271E+10 | 0.417518E+09 | 0.00 | 0.00 |
| November | 0.157310E+10 | 0.599422E+09 | 0.141254E+10 | 0.103022E+10 | 0.382318E+09 | 0.00 | 0.00 |
| December | 0.157321E+10 | 0.806053E+09 | 0.146633E+10 | 0.115361E+10 | 0.312716E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.176237E+11 | 0.515033E+10 | 0.145796E+11 | 0.877458E+10 | 0.580507E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.120981E+10 | 0.113282E+09 | 0.939405E+09 | 0.393665E+09 | 0.312716E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.172934E+10 | 0.806053E+09 | 0.146633E+10 | 0.115361E+10 | 0.616031E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: T NE APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.248748E+09 | 0.790409E+09 | 0.426850E+09 | 0.155583E+09 | 0.271267E+09 | 0.00 | 0.00 |
| February | 0.333067E+09 | 0.645080E+09 | 0.467801E+09 | 0.159564E+09 | 0.308237E+09 | 0.00 | 0.00 |
| March | 0.611536E+09 | 0.542964E+09 | 0.678359E+09 | 0.251162E+09 | 0.427197E+09 | 0.00 | 0.00 |
| April | 0.909267E+09 | 0.361919E+09 | 0.872631E+09 | 0.334091E+09 | 0.538541E+09 | 0.00 | 0.00 |
| May | 0.103796E+10 | 0.277914E+09 | 0.900240E+09 | 0.347714E+09 | 0.552526E+09 | 0.00 | 0.00 |
| June | 0.129840E+10 | 0.173977E+09 | 0.957583E+09 | 0.427480E+09 | 0.530103E+09 | 0.00 | 0.00 |
| July | 0.130999E+10 | 0.112577E+09 | 0.912526E+09 | 0.355172E+09 | 0.557354E+09 | 0.00 | 0.00 |
| August | 0.119840E+10 | 0.133101E+09 | 0.881913E+09 | 0.318925E+09 | 0.562988E+09 | 0.00 | 0.00 |
| September | 0.864690E+09 | 0.233718E+09 | 0.700085E+09 | 0.254391E+09 | 0.445694E+09 | 0.00 | 0.00 |
| October | 0.595256E+09 | 0.417615E+09 | 0.599873E+09 | 0.261244E+09 | 0.338629E+09 | 0.00 | 0.00 |
| November | 0.340632E+09 | 0.586331E+09 | 0.464566E+09 | 0.181709E+09 | 0.282857E+09 | 0.00 | 0.00 |
| December | 0.204731E+09 | 0.821362E+09 | 0.387929E+09 | 0.158458E+09 | 0.229471E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.895268E+10 | 0.509697E+10 | 0.825036E+10 | 0.320549E+10 | 0.504486E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.204731E+09 | 0.112577E+09 | 0.387929E+09 | 0.155583E+09 | 0.229471E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.130999E+10 | 0.821362E+09 | 0.957583E+09 | 0.427480E+09 | 0.562988E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: T N1 APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 38992472.47 | 0.525243E+09 | 0.150424E+09 | 0.00 | 0.150424E+09 | 0.00 | 0.00 |
| February | 70665693.65 | 0.423497E+09 | 0.169811E+09 | 0.00 | 0.169811E+09 | 0.00 | 0.00 |
| March | 0.162749E+09 | 0.357569E+09 | 0.237211E+09 | 23134.55 | 0.237188E+09 | 0.00 | 0.00 |
| April | 0.244166E+09 | 0.230104E+09 | 0.291771E+09 | 3046518.65 | 0.288725E+09 | 0.00 | 0.00 |
| May | 0.341084E+09 | 0.171990E+09 | 0.327828E+09 | 21674088.24 | 0.306154E+09 | 0.00 | 0.00 |
| June | 0.499653E+09 | 0.106791E+09 | 0.359800E+09 | 59092131.21 | 0.300708E+09 | 0.00 | 0.00 |
| July | 0.511987E+09 | 68035280.72 | 0.340370E+09 | 27644461.40 | 0.312725E+09 | 0.00 | 0.00 |
| August | 0.435849E+09 | 81154889.20 | 0.317651E+09 | 8286352.67 | 0.309364E+09 | 0.00 | 0.00 |
| September | 0.286821E+09 | 0.149948E+09 | 0.245065E+09 | 147417.50 | 0.244917E+09 | 0.00 | 0.00 |
| October | 0.143640E+09 | 0.277114E+09 | 0.188808E+09 | 0.00 | 0.188808E+09 | 0.00 | 0.00 |
| November | 57242152.48 | 0.386010E+09 | 0.155171E+09 | 0.00 | 0.155171E+09 | 0.00 | 0.00 |
| December | 13587032.82 | 0.546076E+09 | 0.128034E+09 | 0.00 | 0.128034E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.280644E+10 | 0.332353E+10 | 0.291194E+10 | 0.119914E+09 | 0.279203E+10 | 0.00 | 0.00 |
| Minimum of Months | 13587032.82 | 68035280.72 | 0.128034E+09 | 0.00 | 0.128034E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.511987E+09 | 0.546076E+09 | 0.359800E+09 | 59092131.21 | 0.312725E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: T N2 APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 38882113.89 | 0.525049E+09 | 0.150424E+09 | 0.00 | 0.150424E+09 | 0.00 | 0.00 |
| February | 70485060.90 | 0.423204E+09 | 0.169811E+09 | 0.00 | 0.169811E+09 | 0.00 | 0.00 |
| March | 0.162182E+09 | 0.357422E+09 | 0.237211E+09 | 23134.55 | 0.237188E+09 | 0.00 | 0.00 |
| April | 0.243299E+09 | 0.230072E+09 | 0.291771E+09 | 3046518.65 | 0.288725E+09 | 0.00 | 0.00 |
| May | 0.340592E+09 | 0.171935E+09 | 0.327828E+09 | 21674088.24 | 0.306154E+09 | 0.00 | 0.00 |
| June | 0.499417E+09 | 0.106722E+09 | 0.359800E+09 | 59092131.21 | 0.300708E+09 | 0.00 | 0.00 |
| July | 0.511841E+09 | 67994405.44 | 0.340370E+09 | 27644461.40 | 0.312725E+09 | 0.00 | 0.00 |
| August | 0.435697E+09 | 81092399.87 | 0.317651E+09 | 8286352.67 | 0.309364E+09 | 0.00 | 0.00 |
| September | 0.286614E+09 | 0.149837E+09 | 0.245065E+09 | 147417.50 | 0.244917E+09 | 0.00 | 0.00 |
| October | 0.143131E+09 | 0.276983E+09 | 0.188808E+09 | 0.00 | 0.188808E+09 | 0.00 | 0.00 |
| November | 57016981.45 | 0.385687E+09 | 0.155171E+09 | 0.00 | 0.155171E+09 | 0.00 | 0.00 |
| December | 13527099.37 | 0.545950E+09 | 0.128034E+09 | 0.00 | 0.128034E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.280269E+10 | 0.332195E+10 | 0.291194E+10 | 0.119914E+09 | 0.279203E+10 | 0.00 | 0.00 |
| Minimum of Months | 13527099.37 | 67994405.44 | 0.128034E+09 | 0.00 | 0.128034E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.511841E+09 | 0.545950E+09 | 0.359800E+09 | 59092131.21 | 0.312725E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: T S1 APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.124667E+10 | 0.485515E+09 | 0.109847E+10 | 0.851769E+09 | 0.246697E+09 | 0.00 | 0.00 |
| February | 0.115103E+10 | 0.403129E+09 | 0.991919E+09 | 0.727165E+09 | 0.264754E+09 | 0.00 | 0.00 |
| March | 0.938456E+09 | 0.355763E+09 | 0.790507E+09 | 0.473407E+09 | 0.317100E+09 | 0.00 | 0.00 |
| April | 0.762828E+09 | 0.244400E+09 | 0.620807E+09 | 0.263938E+09 | 0.356868E+09 | 0.00 | 0.00 |
| May | 0.519648E+09 | 0.183464E+09 | 0.419565E+09 | 94158394.50 | 0.325407E+09 | 0.00 | 0.00 |
| June | 0.495557E+09 | 0.113450E+09 | 0.341622E+09 | 42228752.46 | 0.299393E+09 | 0.00 | 0.00 |
| July | 0.621424E+09 | 70979423.36 | 0.394246E+09 | 66136923.55 | 0.328110E+09 | 0.00 | 0.00 |
| August | 0.795487E+09 | 85530809.39 | 0.530966E+09 | 0.168559E+09 | 0.362407E+09 | 0.00 | 0.00 |
| September | 0.102067E+10 | 0.152319E+09 | 0.734405E+09 | 0.416509E+09 | 0.317897E+09 | 0.00 | 0.00 |
| October | 0.127388E+10 | 0.270446E+09 | 0.100916E+10 | 0.741462E+09 | 0.267698E+09 | 0.00 | 0.00 |
| November | 0.129266E+10 | 0.371616E+09 | 0.110314E+10 | 0.848511E+09 | 0.254632E+09 | 0.00 | 0.00 |
| December | 0.137818E+10 | 0.496525E+09 | 0.120643E+10 | 0.995151E+09 | 0.211279E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.114965E+11 | 0.323314E+10 | 0.924124E+10 | 0.568900E+10 | 0.355224E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.495557E+09 | 70979423.36 | 0.341622E+09 | 42228752.46 | 0.211279E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.137818E+10 | 0.496525E+09 | 0.120643E+10 | 0.995151E+09 | 0.362407E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: T S2 APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.124646E+10 | 0.485343E+09 | 0.109847E+10 | 0.851769E+09 | 0.246697E+09 | 0.00 | 0.00 |
| February | 0.115080E+10 | 0.402899E+09 | 0.991919E+09 | 0.727165E+09 | 0.264754E+09 | 0.00 | 0.00 |
| March | 0.938025E+09 | 0.355646E+09 | 0.790507E+09 | 0.473407E+09 | 0.317100E+09 | 0.00 | 0.00 |
| April | 0.762238E+09 | 0.244303E+09 | 0.620807E+09 | 0.263938E+09 | 0.356868E+09 | 0.00 | 0.00 |
| May | 0.519186E+09 | 0.183401E+09 | 0.419565E+09 | 94158394.50 | 0.325407E+09 | 0.00 | 0.00 |
| June | 0.495305E+09 | 0.113373E+09 | 0.341622E+09 | 42228752.46 | 0.299393E+09 | 0.00 | 0.00 |
| July | 0.621280E+09 | 70937588.92 | 0.394246E+09 | 66136923.55 | 0.328110E+09 | 0.00 | 0.00 |
| August | 0.795346E+09 | 85469802.40 | 0.530966E+09 | 0.168559E+09 | 0.362407E+09 | 0.00 | 0.00 |
| September | 0.102053E+10 | 0.152219E+09 | 0.734405E+09 | 0.416509E+09 | 0.317897E+09 | 0.00 | 0.00 |
| October | 0.127364E+10 | 0.270303E+09 | 0.100916E+10 | 0.741462E+09 | 0.267698E+09 | 0.00 | 0.00 |
| November | 0.129239E+10 | 0.371433E+09 | 0.110314E+10 | 0.848511E+09 | 0.254632E+09 | 0.00 | 0.00 |
| December | 0.137794E+10 | 0.496324E+09 | 0.120643E+10 | 0.995151E+09 | 0.211279E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.114932E+11 | 0.323165E+10 | 0.924124E+10 | 0.568900E+10 | 0.355224E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.495305E+09 | 70937588.92 | 0.341622E+09 | 42228752.46 | 0.211279E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.137794E+10 | 0.496324E+09 | 0.120643E+10 | 0.995151E+09 | 0.362407E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: T CORRIDOR
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 57694561.94 | 80347079.60 | 66329402.61 | 37332787.17 | 28996615.44 | 0.00 | 0.00 |
| February | 67713585.15 | 66295135.28 | 71503839.62 | 38288004.02 | 33215835.60 | 0.00 | 0.00 |
| March | 0.113351E+09 | 56913744.00 | 0.105855E+09 | 60261746.15 | 45593479.26 | 0.00 | 0.00 |
| April | 0.162470E+09 | 39049084.06 | 0.139380E+09 | 79435428.98 | 59944391.99 | 0.00 | 0.00 |
| May | 0.167582E+09 | 30888729.57 | 0.137353E+09 | 78234694.40 | 59118013.30 | 0.00 | 0.00 |
| June | 0.190607E+09 | 19783281.08 | 0.143441E+09 | 88396280.40 | 55044310.28 | 0.00 | 0.00 |
| July | 0.189713E+09 | 14001180.84 | 0.137291E+09 | 78591685.32 | 58699578.46 | 0.00 | 0.00 |
| August | 0.181164E+09 | 16272681.13 | 0.135397E+09 | 74538963.50 | 60858075.37 | 0.00 | 0.00 |
| September | 0.138532E+09 | 26581356.42 | 0.109184E+09 | 61006740.84 | 48177174.02 | 0.00 | 0.00 |
| October | 0.112346E+09 | 45459274.12 | 98636709.67 | 62686582.10 | 35950127.57 | 0.00 | 0.00 |
| November | 72272465.46 | 62419665.19 | 74240706.78 | 43601933.51 | 30638773.27 | 0.00 | 0.00 |
| December | 54388117.20 | 84330346.77 | 62362933.65 | 38022662.65 | 24340271.01 | 0.00 | 0.00 |
| Annual Sum or Average | 0.150783E+10 | 0.542342E+09 | 0.128097E+10 | 0.740398E+09 | 0.540577E+09 | 0.00 | 0.00 |
| Minimum of Months | 54388117.20 | 14001180.84 | 62362933.65 | 37332787.17 | 24340271.01 | 0.00 | 0.00 |
| Maximum of Months | 0.190607E+09 | 84330346.77 | 0.143441E+09 | 88396280.40 | 60858075.37 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: G CORRIDOR
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.179120E+09 | 0.226216E+09 | 0.197545E+09 | 0.111186E+09 | 86359136.96 | 0.00 | 0.00 |
| February | 0.210367E+09 | 0.184239E+09 | 0.212956E+09 | 0.114031E+09 | 98925024.62 | 0.00 | 0.00 |
| March | 0.347650E+09 | 0.158436E+09 | 0.315263E+09 | 0.179474E+09 | 0.135789E+09 | 0.00 | 0.00 |
| April | 0.492344E+09 | 0.111606E+09 | 0.415108E+09 | 0.236578E+09 | 0.178529E+09 | 0.00 | 0.00 |
| May | 0.502918E+09 | 92375687.09 | 0.409071E+09 | 0.233002E+09 | 0.176068E+09 | 0.00 | 0.00 |
| June | 0.566406E+09 | 61715258.68 | 0.427202E+09 | 0.263266E+09 | 0.163936E+09 | 0.00 | 0.00 |
| July | 0.562231E+09 | 46080933.23 | 0.408888E+09 | 0.234066E+09 | 0.174822E+09 | 0.00 | 0.00 |
| August | 0.538278E+09 | 52718356.80 | 0.403246E+09 | 0.221996E+09 | 0.181250E+09 | 0.00 | 0.00 |
| September | 0.411660E+09 | 83974478.25 | 0.325177E+09 | 0.181693E+09 | 0.143484E+09 | 0.00 | 0.00 |
| October | 0.332329E+09 | 0.142374E+09 | 0.293765E+09 | 0.186696E+09 | 0.107068E+09 | 0.00 | 0.00 |
| November | 0.217016E+09 | 0.187102E+09 | 0.221107E+09 | 0.129857E+09 | 91249891.67 | 0.00 | 0.00 |
| December | 0.167107E+09 | 0.239092E+09 | 0.185732E+09 | 0.113241E+09 | 72491384.46 | 0.00 | 0.00 |
| Annual Sum or Average | 0.452742E+10 | 0.158593E+10 | 0.381506E+10 | 0.220509E+10 | 0.160997E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.167107E+09 | 46080933.23 | 0.185732E+09 | 0.111186E+09 | 72491384.46 | 0.00 | 0.00 |
| Maximum of Months | 0.566406E+09 | 0.239092E+09 | 0.427202E+09 | 0.263266E+09 | 0.181250E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: M CORRIDOR
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 54918697.75 | 86954783.96 | 66329402.61 | 37332787.17 | 28996615.44 | 0.00 | 0.00 |
| February | 65422479.12 | 71502714.14 | 71503839.62 | 38288004.02 | 33215835.60 | 0.00 | 0.00 |
| March | 0.110124E+09 | 62075703.91 | 0.105855E+09 | 60261746.15 | 45593479.26 | 0.00 | 0.00 |
| April | 0.159412E+09 | 42541578.57 | 0.139380E+09 | 79435428.98 | 59944391.99 | 0.00 | 0.00 |
| May | 0.166011E+09 | 33076877.41 | 0.137353E+09 | 78234694.40 | 59118013.30 | 0.00 | 0.00 |
| June | 0.190969E+09 | 20492078.64 | 0.143441E+09 | 88396280.40 | 55044310.28 | 0.00 | 0.00 |
| July | 0.191092E+09 | 14132246.82 | 0.137291E+09 | 78591685.32 | 58699578.46 | 0.00 | 0.00 |
| August | 0.182206E+09 | 16485667.12 | 0.135397E+09 | 74538963.50 | 60858075.37 | 0.00 | 0.00 |
| September | 0.138278E+09 | 27703123.23 | 0.109184E+09 | 61006740.84 | 48177174.02 | 0.00 | 0.00 |
| October | 0.109761E+09 | 49790745.95 | 98636709.67 | 62686582.10 | 35950127.57 | 0.00 | 0.00 |
| November | 69352835.39 | 68946320.95 | 74240706.78 | 43601933.51 | 30638773.27 | 0.00 | 0.00 |
| December | 52273124.54 | 91748093.64 | 62362933.65 | 38022662.65 | 24340271.01 | 0.00 | 0.00 |
| Annual Sum or Average | 0.148982E+10 | 0.585450E+09 | 0.128097E+10 | 0.740398E+09 | 0.540577E+09 | 0.00 | 0.00 |
| Minimum of Months | 52273124.54 | 14132246.82 | 62362933.65 | 37332787.17 | 24340271.01 | 0.00 | 0.00 |
| Maximum of Months | 0.191092E+09 | 91748093.64 | 0.143441E+09 | 88396280.40 | 60858075.37 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
| January | 2.60 | -1.3 | -7.5 | 3.29 | -12.5 | 38.91 | 220.14 | 0.00 |
| February | 4.28 | 0.13 | -5.8 | 3.80 | -10.7 | 48.21 | 247.44 | 0.00 |
| March | 8.76 | 2.64 | -5.5 | 4.72 | -6.0 | 66.36 | 249.43 | 0.00 |
| April | 13.90 | 4.70 | -6.4 | 4.61 | -1.8 | 81.54 | 308.98 | 0.00 |
| May | 17.82 | 8.42 | -1.1 | 4.68 | 3.61 | 77.67 | 310.50 | 0.00 |
| June | 23.21 | 12.42 | 4.15 | 4.28 | 9.16 | 70.88 | 348.57 | 0.00 |
| July | 25.63 | 16.13 | 10.74 | 4.00 | 14.07 | 80.74 | 308.61 | 0.00 |
| August | 24.08 | 15.39 | 10.38 | 3.96 | 13.00 | 86.20 | 290.42 | 0.00 |
| September | 20.49 | 12.87 | 7.70 | 3.48 | 8.22 | 67.00 | 274.65 | 0.00 |
| October | 13.71 | 6.72 | -0.1 | 3.54 | -0.8 | 42.11 | 283.53 | 0.00 |
| November | 6.96 | 1.72 | -4.9 | 3.43 | -7.6 | 39.44 | 239.51 | 0.01 |
| December | 2.07 | -2.2 | -8.9 | 2.95 | -13.5 | 27.44 | 240.96 | 0.00 |
| Annual Sum or Average | 13.68 | 6.50 | -0.6 | 3.90 | -0.3 | 60.60 | 276.96 | 0.00 |
| Minimum of Months | 2.07 | -2.2 | -8.9 | 2.95 | -13.5 | 27.44 | 220.14 | 0.00 |
| Maximum of Months | 25.63 | 16.13 | 10.74 | 4.72 | 14.07 | 86.20 | 348.57 | 0.01 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
| January | 16.10 | 01-JAN-14:00 | 5.83 | -6.7 | 5.20 | -2.3 | 27.00 | 880.00 |
| February | 22.20 | 14-FEB-15:00 | 7.86 | -10.0 | 4.60 | 4.72 | 61.50 | 778.50 |
| March | 22.80 | 08-MAR-13:00 | 9.68 | -2.8 | 3.60 | 4.92 | 122.50 | 851.50 |
| April | 26.10 | 13-APR-16:00 | 10.32 | -4.4 | 5.20 | 7.55 | 95.00 | 507.00 |
| May | 30.00 | 19-MAY-15:20 | 12.71 | -1.5 | 8.93 | 13.35 | 108.33 | 887.00 |
| June | 38.90 | 28-JUN-15:00 | 14.16 | -8.9 | 3.10 | 20.75 | 70.00 | 888.00 |
| July | 38.30 | 22-JUL-14:00 | 16.71 | 3.30 | 5.20 | 24.16 | 99.00 | 907.50 |
| August | 35.00 | 01-AUG-14:00 | 16.30 | 4.40 | 2.60 | 19.52 | 113.00 | 840.50 |
| September | 32.80 | 03-SEP-13:00 | 16.76 | 7.80 | 3.60 | 21.78 | 263.50 | 532.50 |
| October | 28.90 | 01-OCT-15:00 | 13.26 | 1.70 | 4.10 | 15.94 | 85.00 | 435.00 |
| November | 19.40 | 09-NOV-13:00 | 9.81 | 1.70 | 10.80 | 8.35 | 157.50 | 0.00 |
| December | 13.30 | 24-DEC-14:00 | 4.02 | -8.3 | 8.20 | -2.5 | 40.50 | 792.50 |
| Annual Sum or Average | ||||||||
| Minimum of Months | 13.30 | 4.02 | -10.0 | 2.60 | -2.5 | 27.00 | 0.00 | |
| Maximum of Months | 38.90 | 16.76 | 7.80 | 10.80 | 24.16 | 263.50 | 907.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
| January | -8.3 | 20-JAN-01:00 | -8.3 | -8.3 | 2.10 | -25.6 | 0.00 | 0.00 |
| February | -6.7 | 04-FEB-06:10 | -8.2 | -11.7 | 5.10 | -25.0 | 0.00 | 0.00 |
| March | -3.9 | 05-MAR-06:00 | -5.7 | -9.4 | 1.50 | -21.6 | 17.00 | 434.50 |
| April | 1.70 | 06-APR-05:00 | -2.4 | -8.3 | 2.60 | -12.9 | 28.00 | 215.00 |
| May | 4.40 | 07-MAY-04:00 | -1.0 | -8.3 | 1.50 | -13.7 | 0.00 | 0.00 |
| June | 7.80 | 09-JUN-04:40 | 5.54 | 3.30 | 4.83 | -7.8 | 0.00 | 0.00 |
| July | 16.10 | 08-JUL-02:00 | 14.67 | 13.90 | 0.00 | 4.72 | 0.00 | 0.00 |
| August | 12.80 | 31-AUG-05:00 | 10.77 | 9.40 | 3.10 | -1.7 | 24.50 | 228.50 |
| September | 10.60 | 09-SEP-05:00 | 9.95 | 9.40 | 2.10 | -2.5 | 15.50 | 177.00 |
| October | -2.8 | 26-OCT-04:10 | -4.1 | -6.1 | 2.42 | -17.7 | 0.00 | 0.00 |
| November | -4.4 | 27-NOV-05:00 | -6.9 | -11.7 | 2.60 | -22.7 | 0.00 | 0.00 |
| December | -9.4 | 15-DEC-04:00 | -12.1 | -21.7 | 0.00 | -29.7 | 0.00 | 0.00 |
| Annual Sum or Average | ||||||||
| Minimum of Months | -9.4 | -12.1 | -21.7 | 0.00 | -29.7 | 0.00 | 0.00 | |
| Maximum of Months | 16.10 | 14.67 | 13.90 | 5.10 | 4.72 | 28.00 | 434.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| SITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
| January | 6.84 | 05-JAN-13:00 | 16.10 | -2.8 | 3.10 | -0.1 | 62.00 | 873.00 |
| February | 7.86 | 14-FEB-15:00 | 22.20 | -10.0 | 4.60 | 4.72 | 61.50 | 778.50 |
| March | 9.68 | 08-MAR-13:00 | 22.80 | -2.8 | 3.60 | 4.92 | 122.50 | 851.50 |
| April | 10.95 | 14-APR-15:00 | 24.40 | -0.6 | 8.20 | 17.21 | 237.00 | 154.00 |
| May | 15.08 | 22-MAY-12:30 | 28.60 | 6.40 | 5.15 | 16.76 | 167.00 | 0.00 |
| June | 18.19 | 24-JUN-13:00 | 31.70 | 11.70 | 2.60 | 19.17 | 130.00 | 891.50 |
| July | 19.21 | 31-JUL-14:00 | 32.80 | 12.80 | 6.20 | 22.98 | 264.50 | 624.50 |
| August | 19.18 | 26-AUG-12:00 | 27.80 | 15.60 | 3.60 | 17.03 | 289.00 | 426.50 |
| September | 18.19 | 05-SEP-12:00 | 23.90 | 15.60 | 3.10 | 13.35 | 196.50 | 796.00 |
| October | 16.16 | 11-OCT-10:00 | 23.90 | 12.20 | 13.40 | 13.73 | 219.50 | 450.00 |
| November | 9.81 | 09-NOV-13:00 | 19.40 | 1.70 | 10.80 | 8.35 | 157.50 | 0.00 |
| December | 4.92 | 01-DEC-15:00 | 12.80 | -3.9 | 2.10 | 1.58 | 50.00 | 276.00 |
| Annual Sum or Average | ||||||||
| Minimum of Months | 4.92 | 12.80 | -10.0 | 2.10 | -0.1 | 50.00 | 0.00 | |
| Maximum of Months | 19.21 | 32.80 | 15.60 | 13.40 | 22.98 | 289.00 | 891.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| SITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
| January | -0.6 | 28-JAN-17:00 | 6.10 | 3.01 | 4.60 | -5.0 | 0.00 | 0.00 |
| February | 2.20 | 17-FEB-10:00 | 7.20 | 4.72 | 3.10 | -4.1 | 212.50 | 561.00 |
| March | 5.60 | 28-MAR-17:10 | 8.80 | 7.05 | 4.60 | 3.37 | 35.00 | 0.67 |
| April | 7.20 | 15-APR-06:00 | 13.30 | 9.79 | 7.20 | 6.35 | 116.00 | 422.00 |
| May | 13.90 | 24-MAY-14:00 | 16.70 | 14.90 | 4.60 | 11.07 | 128.00 | 0.00 |
| June | 13.30 | 30-JUN-13:00 | 26.70 | 17.72 | 6.70 | 20.75 | 170.00 | 126.50 |
| July | 17.80 | 01-JUL-13:00 | 22.20 | 19.05 | 3.60 | 13.91 | 361.00 | 125.00 |
| August | 17.20 | 26-AUG-09:00 | 21.70 | 18.59 | 2.60 | 11.65 | 243.50 | 681.50 |
| September | 15.60 | 05-SEP-11:00 | 22.20 | 17.61 | 3.10 | 12.79 | 231.00 | 705.00 |
| October | 13.90 | 02-OCT-16:00 | 20.60 | 16.04 | 6.20 | 13.54 | 38.50 | 65.00 |
| November | 6.10 | 09-NOV-21:00 | 8.90 | 7.38 | 11.80 | 3.69 | 0.00 | 0.00 |
| December | 1.10 | 25-DEC-08:00 | 2.20 | 1.65 | 2.10 | -4.1 | 54.00 | 0.00 |
| Annual Sum or Average | ||||||||
| Minimum of Months | -0.6 | 2.20 | 1.65 | 2.10 | -5.0 | 0.00 | 0.00 | |
| Maximum of Months | 17.80 | 26.70 | 19.05 | 11.80 | 20.75 | 361.00 | 705.00 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| SITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
| January | 18.00 | 13.00 | 16.00 | 11.28 | 25.87 | 0.00 |
| February | 18.00 | 13.00 | 16.00 | 10.91 | 34.17 | 0.00 |
| March | 18.00 | 13.00 | 16.00 | 12.10 | 41.92 | 0.00 |
| April | 18.00 | 13.00 | 16.00 | 14.59 | 56.24 | 0.00 |
| May | 18.00 | 13.00 | 16.00 | 17.73 | 59.47 | 0.00 |
| June | 18.00 | 13.00 | 16.00 | 20.66 | 62.98 | 0.00 |
| July | 18.00 | 13.00 | 16.00 | 22.59 | 61.22 | 0.00 |
| August | 18.00 | 13.00 | 16.00 | 23.01 | 57.83 | 0.00 |
| September | 18.00 | 13.00 | 16.00 | 21.78 | 48.11 | 0.00 |
| October | 18.00 | 13.00 | 16.00 | 19.25 | 37.89 | 0.00 |
| November | 18.00 | 13.00 | 16.00 | 16.11 | 28.37 | 0.00 |
| December | 18.00 | 13.00 | 16.00 | 13.20 | 24.17 | 0.00 |
| Annual Sum or Average | 18.00 | 13.00 | 16.00 | 16.97 | 44.90 | 0.00 |
| Minimum of Months | 18.00 | 13.00 | 16.00 | 10.91 | 24.17 | 0.00 |
| Maximum of Months | 18.00 | 13.00 | 16.00 | 23.01 | 62.98 | 0.00 |
Report: WaterHeaterReportMonthly
For: G SW APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.121916E+10 | -0.103559E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -183572792.1 | 59.44 | 0.00 | 0.00 |
| February | 0.110812E+10 | -942479403.2 | 0.00 | 0.00 | 672.00 | 0.00 | -165639839.7 | 59.44 | 0.00 | 0.00 |
| March | 0.120042E+10 | -0.101799E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -182422766.6 | 59.44 | 0.00 | 0.00 |
| April | 0.110411E+10 | -933252232.9 | 0.00 | 0.00 | 720.00 | 0.00 | -170857749.2 | 59.44 | 0.00 | 0.00 |
| May | 0.107097E+10 | -896902081.5 | 0.00 | 0.00 | 744.00 | 0.00 | -174071214.8 | 59.44 | 0.00 | 0.00 |
| June | 0.974021E+09 | -806924173.3 | 0.00 | 0.00 | 720.00 | 0.00 | -167096431.4 | 59.44 | 0.00 | 0.00 |
| July | 0.964719E+09 | -792235683.6 | 0.00 | 0.00 | 744.00 | 0.00 | -172483541.9 | 59.44 | 0.00 | 0.00 |
| August | 0.955800E+09 | -783317335.3 | 0.00 | 0.00 | 744.00 | 0.00 | -172483002.6 | 59.44 | 0.00 | 0.00 |
| September | 0.950532E+09 | -783606821.1 | 0.00 | 0.00 | 720.00 | 0.00 | -166925288.4 | 59.44 | 0.00 | 0.00 |
| October | 0.103782E+10 | -864153827.0 | 0.00 | 0.00 | 744.00 | 0.00 | -173661212.1 | 59.44 | 0.00 | 0.00 |
| November | 0.107245E+10 | -901673627.5 | 0.00 | 0.00 | 720.00 | 0.00 | -170776450.8 | 59.44 | 0.00 | 0.00 |
| December | 0.117748E+10 | -994308788.8 | 0.00 | 0.00 | 744.00 | 0.00 | -183167637.7 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.128356E+11 | -0.107524E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.208316E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.950532E+09 | -0.103559E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -183572792.1 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.121916E+10 | -783317335.3 | 0.00 | 0.00 | 744.00 | 0.00 | -165639839.7 | 59.44 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: G NW APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.122215E+10 | -0.103558E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186569057.2 | 59.44 | 0.00 | 0.00 |
| February | 0.111080E+10 | -942479608.1 | 0.00 | 0.00 | 672.00 | 0.00 | -168325346.6 | 59.44 | 0.00 | 0.00 |
| March | 0.120377E+10 | -0.101799E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -185782116.7 | 59.44 | 0.00 | 0.00 |
| April | 0.110713E+10 | -933253361.3 | 0.00 | 0.00 | 720.00 | 0.00 | -173878975.5 | 59.44 | 0.00 | 0.00 |
| May | 0.107143E+10 | -896902502.5 | 0.00 | 0.00 | 744.00 | 0.00 | -174523694.1 | 59.44 | 0.00 | 0.00 |
| June | 0.974014E+09 | -806925147.5 | 0.00 | 0.00 | 720.00 | 0.00 | -167088578.6 | 59.44 | 0.00 | 0.00 |
| July | 0.964716E+09 | -792225716.7 | 0.00 | 0.00 | 744.00 | 0.00 | -172490179.5 | 59.44 | 0.00 | 0.00 |
| August | 0.955801E+09 | -783311915.5 | 0.00 | 0.00 | 744.00 | 0.00 | -172488843.3 | 59.44 | 0.00 | 0.00 |
| September | 0.950535E+09 | -783604281.0 | 0.00 | 0.00 | 720.00 | 0.00 | -166930567.5 | 59.44 | 0.00 | 0.00 |
| October | 0.103998E+10 | -864151535.9 | 0.00 | 0.00 | 744.00 | 0.00 | -175825162.9 | 59.44 | 0.00 | 0.00 |
| November | 0.108042E+10 | -901675949.4 | 0.00 | 0.00 | 720.00 | 0.00 | -178745420.9 | 59.44 | 0.00 | 0.00 |
| December | 0.118086E+10 | -994307053.7 | 0.00 | 0.00 | 744.00 | 0.00 | -186556984.1 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.128616E+11 | -0.107524E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.210920E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.950535E+09 | -0.103558E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -186569057.2 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.122215E+10 | -783311915.5 | 0.00 | 0.00 | 744.00 | 0.00 | -166930567.5 | 59.44 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: G NE APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.122218E+10 | -0.103558E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186597742.3 | 59.44 | 0.00 | 0.00 |
| February | 0.111089E+10 | -942477378.6 | 0.00 | 0.00 | 672.00 | 0.00 | -168411540.9 | 59.44 | 0.00 | 0.00 |
| March | 0.120378E+10 | -0.101799E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -185790844.4 | 59.44 | 0.00 | 0.00 |
| April | 0.110644E+10 | -933248748.1 | 0.00 | 0.00 | 720.00 | 0.00 | -173189911.2 | 59.44 | 0.00 | 0.00 |
| May | 0.107100E+10 | -896903469.3 | 0.00 | 0.00 | 744.00 | 0.00 | -174092555.5 | 59.44 | 0.00 | 0.00 |
| June | 0.973965E+09 | -806924087.4 | 0.00 | 0.00 | 720.00 | 0.00 | -167040707.7 | 59.44 | 0.00 | 0.00 |
| July | 0.964716E+09 | -792227080.6 | 0.00 | 0.00 | 744.00 | 0.00 | -172489363.0 | 59.44 | 0.00 | 0.00 |
| August | 0.955801E+09 | -783312031.3 | 0.00 | 0.00 | 744.00 | 0.00 | -172488619.0 | 59.44 | 0.00 | 0.00 |
| September | 0.950536E+09 | -783604010.8 | 0.00 | 0.00 | 720.00 | 0.00 | -166931794.5 | 59.44 | 0.00 | 0.00 |
| October | 0.103979E+10 | -864152986.5 | 0.00 | 0.00 | 744.00 | 0.00 | -175638863.2 | 59.44 | 0.00 | 0.00 |
| November | 0.108054E+10 | -901675090.8 | 0.00 | 0.00 | 720.00 | 0.00 | -178865888.7 | 59.44 | 0.00 | 0.00 |
| December | 0.118089E+10 | -994306711.9 | 0.00 | 0.00 | 744.00 | 0.00 | -186585235.7 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.128605E+11 | -0.107524E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.210812E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.950536E+09 | -0.103558E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -186597742.3 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.122218E+10 | -783312031.3 | 0.00 | 0.00 | 744.00 | 0.00 | -166931794.5 | 59.44 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: G N1 APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.122216E+10 | -0.103558E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186578999.0 | 59.44 | 0.00 | 0.00 |
| February | 0.111086E+10 | -942477927.0 | 0.00 | 0.00 | 672.00 | 0.00 | -168379559.2 | 59.44 | 0.00 | 0.00 |
| March | 0.120375E+10 | -0.101799E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -185762437.1 | 59.44 | 0.00 | 0.00 |
| April | 0.110651E+10 | -933248681.9 | 0.00 | 0.00 | 720.00 | 0.00 | -173258019.1 | 59.44 | 0.00 | 0.00 |
| May | 0.107072E+10 | -896902737.8 | 0.00 | 0.00 | 744.00 | 0.00 | -173818074.7 | 59.44 | 0.00 | 0.00 |
| June | 0.973891E+09 | -806927544.8 | 0.00 | 0.00 | 720.00 | 0.00 | -166963799.0 | 59.44 | 0.00 | 0.00 |
| July | 0.964721E+09 | -792237702.1 | 0.00 | 0.00 | 744.00 | 0.00 | -172483781.5 | 59.44 | 0.00 | 0.00 |
| August | 0.955799E+09 | -783312291.6 | 0.00 | 0.00 | 744.00 | 0.00 | -172487162.0 | 59.44 | 0.00 | 0.00 |
| September | 0.950532E+09 | -783610344.8 | 0.00 | 0.00 | 720.00 | 0.00 | -166921992.6 | 59.44 | 0.00 | 0.00 |
| October | 0.103941E+10 | -864152493.3 | 0.00 | 0.00 | 744.00 | 0.00 | -175261257.1 | 59.44 | 0.00 | 0.00 |
| November | 0.108002E+10 | -901671531.9 | 0.00 | 0.00 | 720.00 | 0.00 | -178350824.0 | 59.44 | 0.00 | 0.00 |
| December | 0.118086E+10 | -994308992.9 | 0.00 | 0.00 | 744.00 | 0.00 | -186551679.5 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.128592E+11 | -0.107524E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.210682E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.950532E+09 | -0.103558E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -186578999.0 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.122216E+10 | -783312291.6 | 0.00 | 0.00 | 744.00 | 0.00 | -166921992.6 | 59.44 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: G N2 APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.122216E+10 | -0.103558E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186579384.8 | 59.44 | 0.00 | 0.00 |
| February | 0.111086E+10 | -942477906.7 | 0.00 | 0.00 | 672.00 | 0.00 | -168381975.3 | 59.44 | 0.00 | 0.00 |
| March | 0.120374E+10 | -0.101799E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -185750934.4 | 59.44 | 0.00 | 0.00 |
| April | 0.110643E+10 | -933249180.3 | 0.00 | 0.00 | 720.00 | 0.00 | -173179823.7 | 59.44 | 0.00 | 0.00 |
| May | 0.107067E+10 | -896903745.4 | 0.00 | 0.00 | 744.00 | 0.00 | -173768121.8 | 59.44 | 0.00 | 0.00 |
| June | 0.973890E+09 | -806930506.4 | 0.00 | 0.00 | 720.00 | 0.00 | -166959251.4 | 59.44 | 0.00 | 0.00 |
| July | 0.964717E+09 | -792230414.8 | 0.00 | 0.00 | 744.00 | 0.00 | -172486818.0 | 59.44 | 0.00 | 0.00 |
| August | 0.955799E+09 | -783311974.7 | 0.00 | 0.00 | 744.00 | 0.00 | -172487507.6 | 59.44 | 0.00 | 0.00 |
| September | 0.950534E+09 | -783604660.2 | 0.00 | 0.00 | 720.00 | 0.00 | -166929748.0 | 59.44 | 0.00 | 0.00 |
| October | 0.103939E+10 | -864154875.5 | 0.00 | 0.00 | 744.00 | 0.00 | -175237673.4 | 59.44 | 0.00 | 0.00 |
| November | 0.108002E+10 | -901678022.7 | 0.00 | 0.00 | 720.00 | 0.00 | -178346948.1 | 59.44 | 0.00 | 0.00 |
| December | 0.118086E+10 | -994306852.5 | 0.00 | 0.00 | 744.00 | 0.00 | -186551401.8 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.128591E+11 | -0.107524E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.210666E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.950534E+09 | -0.103558E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -186579384.8 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.122216E+10 | -783311974.7 | 0.00 | 0.00 | 744.00 | 0.00 | -166929748.0 | 59.44 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: G S1 APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.121720E+10 | -0.103558E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -181612673.8 | 59.44 | 0.00 | 0.00 |
| February | 0.110665E+10 | -942479120.6 | 0.00 | 0.00 | 672.00 | 0.00 | -164173650.1 | 59.44 | 0.00 | 0.00 |
| March | 0.119835E+10 | -0.101799E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -180363384.3 | 59.44 | 0.00 | 0.00 |
| April | 0.110270E+10 | -933253476.7 | 0.00 | 0.00 | 720.00 | 0.00 | -169442599.3 | 59.44 | 0.00 | 0.00 |
| May | 0.107026E+10 | -896902579.7 | 0.00 | 0.00 | 744.00 | 0.00 | -173358570.9 | 59.44 | 0.00 | 0.00 |
| June | 0.973897E+09 | -806927963.7 | 0.00 | 0.00 | 720.00 | 0.00 | -166969296.4 | 59.44 | 0.00 | 0.00 |
| July | 0.964716E+09 | -792226542.6 | 0.00 | 0.00 | 744.00 | 0.00 | -172489846.4 | 59.44 | 0.00 | 0.00 |
| August | 0.955801E+09 | -783311727.6 | 0.00 | 0.00 | 744.00 | 0.00 | -172488813.8 | 59.44 | 0.00 | 0.00 |
| September | 0.950534E+09 | -783604404.8 | 0.00 | 0.00 | 720.00 | 0.00 | -166929438.3 | 59.44 | 0.00 | 0.00 |
| October | 0.103729E+10 | -864152855.4 | 0.00 | 0.00 | 744.00 | 0.00 | -173136145.6 | 59.44 | 0.00 | 0.00 |
| November | 0.107051E+10 | -901675117.9 | 0.00 | 0.00 | 720.00 | 0.00 | -168835199.4 | 59.44 | 0.00 | 0.00 |
| December | 0.117525E+10 | -994308098.8 | 0.00 | 0.00 | 744.00 | 0.00 | -180940041.1 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.128232E+11 | -0.107524E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.207074E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.950534E+09 | -0.103558E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -181612673.8 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.121720E+10 | -783311727.6 | 0.00 | 0.00 | 744.00 | 0.00 | -164173650.1 | 59.44 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: G S2 APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.121718E+10 | -0.103558E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -181592949.2 | 59.44 | 0.00 | 0.00 |
| February | 0.110663E+10 | -942479027.8 | 0.00 | 0.00 | 672.00 | 0.00 | -164153686.2 | 59.44 | 0.00 | 0.00 |
| March | 0.119800E+10 | -0.101799E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -180010616.5 | 59.44 | 0.00 | 0.00 |
| April | 0.110235E+10 | -933251672.3 | 0.00 | 0.00 | 720.00 | 0.00 | -169099296.7 | 59.44 | 0.00 | 0.00 |
| May | 0.107007E+10 | -896900351.6 | 0.00 | 0.00 | 744.00 | 0.00 | -173166598.0 | 59.44 | 0.00 | 0.00 |
| June | 0.973877E+09 | -806924394.4 | 0.00 | 0.00 | 720.00 | 0.00 | -166952956.1 | 59.44 | 0.00 | 0.00 |
| July | 0.964716E+09 | -792225345.3 | 0.00 | 0.00 | 744.00 | 0.00 | -172490253.3 | 59.44 | 0.00 | 0.00 |
| August | 0.955801E+09 | -783312027.9 | 0.00 | 0.00 | 744.00 | 0.00 | -172488906.8 | 59.44 | 0.00 | 0.00 |
| September | 0.950534E+09 | -783604171.3 | 0.00 | 0.00 | 720.00 | 0.00 | -166929481.6 | 59.44 | 0.00 | 0.00 |
| October | 0.103720E+10 | -864153227.1 | 0.00 | 0.00 | 744.00 | 0.00 | -173050810.6 | 59.44 | 0.00 | 0.00 |
| November | 0.107037E+10 | -901674121.0 | 0.00 | 0.00 | 720.00 | 0.00 | -168697275.5 | 59.44 | 0.00 | 0.00 |
| December | 0.117517E+10 | -994306632.4 | 0.00 | 0.00 | 744.00 | 0.00 | -180867931.7 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.128219E+11 | -0.107524E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.206950E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.950534E+09 | -0.103558E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -181592949.2 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.121718E+10 | -783312027.9 | 0.00 | 0.00 | 744.00 | 0.00 | -164153686.2 | 59.44 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: M SW APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.225242E+10 | -0.207117E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -181252725.7 | 59.44 | 0.00 | 0.00 |
| February | 0.204757E+10 | -0.188496E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -162608752.7 | 59.44 | 0.00 | 0.00 |
| March | 0.221316E+10 | -0.203599E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -177169190.9 | 59.44 | 0.00 | 0.00 |
| April | 0.203441E+10 | -0.186651E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -167901179.1 | 59.44 | 0.00 | 0.00 |
| May | 0.196675E+10 | -0.179381E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172941633.7 | 59.44 | 0.00 | 0.00 |
| June | 0.178084E+10 | -0.161386E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -166984170.0 | 59.44 | 0.00 | 0.00 |
| July | 0.175696E+10 | -0.158447E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172488557.9 | 59.44 | 0.00 | 0.00 |
| August | 0.173912E+10 | -0.156663E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172484787.1 | 59.44 | 0.00 | 0.00 |
| September | 0.173415E+10 | -0.156722E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -166928897.5 | 59.44 | 0.00 | 0.00 |
| October | 0.190224E+10 | -0.172831E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -173931749.4 | 59.44 | 0.00 | 0.00 |
| November | 0.197420E+10 | -0.180335E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -170846503.8 | 59.44 | 0.00 | 0.00 |
| December | 0.216976E+10 | -0.198861E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -181141951.4 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.235716E+11 | -0.215049E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.206668E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.173415E+10 | -0.207117E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -181252725.7 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.225242E+10 | -0.156663E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -162608752.7 | 59.44 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: M NW APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.225736E+10 | -0.207117E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186195051.1 | 59.44 | 0.00 | 0.00 |
| February | 0.205225E+10 | -0.188496E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -167286534.8 | 59.44 | 0.00 | 0.00 |
| March | 0.221801E+10 | -0.203599E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -182019058.0 | 59.44 | 0.00 | 0.00 |
| April | 0.203544E+10 | -0.186651E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -168934155.3 | 59.44 | 0.00 | 0.00 |
| May | 0.196685E+10 | -0.179381E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -173040946.7 | 59.44 | 0.00 | 0.00 |
| June | 0.178083E+10 | -0.161386E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -166974604.2 | 59.44 | 0.00 | 0.00 |
| July | 0.175696E+10 | -0.158447E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172484344.4 | 59.44 | 0.00 | 0.00 |
| August | 0.173912E+10 | -0.156663E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172486557.6 | 59.44 | 0.00 | 0.00 |
| September | 0.173416E+10 | -0.156723E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -166929299.7 | 59.44 | 0.00 | 0.00 |
| October | 0.190434E+10 | -0.172831E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -176028484.7 | 59.44 | 0.00 | 0.00 |
| November | 0.198145E+10 | -0.180335E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -178100759.6 | 59.44 | 0.00 | 0.00 |
| December | 0.217503E+10 | -0.198862E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186409055.0 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.236018E+11 | -0.215049E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.209689E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.173416E+10 | -0.207117E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -186409055.0 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.225736E+10 | -0.156663E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -166929299.7 | 59.44 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: M SE APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.225220E+10 | -0.207117E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -181037192.3 | 59.44 | 0.00 | 0.00 |
| February | 0.204756E+10 | -0.188496E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -162597848.0 | 59.44 | 0.00 | 0.00 |
| March | 0.221272E+10 | -0.203599E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -176727517.3 | 59.44 | 0.00 | 0.00 |
| April | 0.203423E+10 | -0.186651E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -167725509.4 | 59.44 | 0.00 | 0.00 |
| May | 0.196660E+10 | -0.179381E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172792848.9 | 59.44 | 0.00 | 0.00 |
| June | 0.178082E+10 | -0.161386E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -166960083.1 | 59.44 | 0.00 | 0.00 |
| July | 0.175696E+10 | -0.158447E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172485516.5 | 59.44 | 0.00 | 0.00 |
| August | 0.173912E+10 | -0.156663E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172485595.1 | 59.44 | 0.00 | 0.00 |
| September | 0.173415E+10 | -0.156723E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -166923354.2 | 59.44 | 0.00 | 0.00 |
| October | 0.190218E+10 | -0.172831E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -173866287.6 | 59.44 | 0.00 | 0.00 |
| November | 0.197404E+10 | -0.180336E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -170686396.3 | 59.44 | 0.00 | 0.00 |
| December | 0.216958E+10 | -0.198862E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -180960196.9 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.235702E+11 | -0.215049E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.206525E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.173415E+10 | -0.207117E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -181037192.3 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.225220E+10 | -0.156663E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -162597848.0 | 59.44 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: M NE APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.225752E+10 | -0.207117E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186352667.0 | 59.44 | 0.00 | 0.00 |
| February | 0.205240E+10 | -0.188496E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -167438690.9 | 59.44 | 0.00 | 0.00 |
| March | 0.221743E+10 | -0.203599E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -181439227.8 | 59.44 | 0.00 | 0.00 |
| April | 0.203493E+10 | -0.186651E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -168414587.7 | 59.44 | 0.00 | 0.00 |
| May | 0.196665E+10 | -0.179381E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172837542.2 | 59.44 | 0.00 | 0.00 |
| June | 0.178082E+10 | -0.161386E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -166959706.0 | 59.44 | 0.00 | 0.00 |
| July | 0.175696E+10 | -0.158447E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172486520.7 | 59.44 | 0.00 | 0.00 |
| August | 0.173912E+10 | -0.156663E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172483957.4 | 59.44 | 0.00 | 0.00 |
| September | 0.173416E+10 | -0.156723E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -166937100.6 | 59.44 | 0.00 | 0.00 |
| October | 0.190410E+10 | -0.172831E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -175788167.6 | 59.44 | 0.00 | 0.00 |
| November | 0.198156E+10 | -0.180336E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -178201838.0 | 59.44 | 0.00 | 0.00 |
| December | 0.217514E+10 | -0.198862E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186524673.7 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.236008E+11 | -0.215049E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.209586E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.173416E+10 | -0.207117E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -186524673.7 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.225752E+10 | -0.156663E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -166937100.6 | 59.44 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: M N1 APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.225735E+10 | -0.207117E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186178623.2 | 59.44 | 0.00 | 0.00 |
| February | 0.205220E+10 | -0.188496E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -167241700.2 | 59.44 | 0.00 | 0.00 |
| March | 0.221690E+10 | -0.203599E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -180902900.4 | 59.44 | 0.00 | 0.00 |
| April | 0.203477E+10 | -0.186651E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -168259824.1 | 59.44 | 0.00 | 0.00 |
| May | 0.196656E+10 | -0.179381E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172752209.9 | 59.44 | 0.00 | 0.00 |
| June | 0.178079E+10 | -0.161386E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -166934110.7 | 59.44 | 0.00 | 0.00 |
| July | 0.175696E+10 | -0.158447E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172488787.5 | 59.44 | 0.00 | 0.00 |
| August | 0.173912E+10 | -0.156663E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172484835.6 | 59.44 | 0.00 | 0.00 |
| September | 0.173415E+10 | -0.156722E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -166927384.0 | 59.44 | 0.00 | 0.00 |
| October | 0.190353E+10 | -0.172831E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -175215665.9 | 59.44 | 0.00 | 0.00 |
| November | 0.198060E+10 | -0.180335E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -177248405.1 | 59.44 | 0.00 | 0.00 |
| December | 0.217503E+10 | -0.198862E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186407247.6 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.235980E+11 | -0.215049E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.209304E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.173415E+10 | -0.207117E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -186407247.6 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.225735E+10 | -0.156663E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -166927384.0 | 59.44 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: M N2 APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.225735E+10 | -0.207117E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186180369.2 | 59.44 | 0.00 | 0.00 |
| February | 0.205221E+10 | -0.188496E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -167250473.9 | 59.44 | 0.00 | 0.00 |
| March | 0.221680E+10 | -0.203599E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -180809312.7 | 59.44 | 0.00 | 0.00 |
| April | 0.203472E+10 | -0.186651E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -168214297.7 | 59.44 | 0.00 | 0.00 |
| May | 0.196655E+10 | -0.179381E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172739278.6 | 59.44 | 0.00 | 0.00 |
| June | 0.178079E+10 | -0.161386E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -166931695.2 | 59.44 | 0.00 | 0.00 |
| July | 0.175696E+10 | -0.158447E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172486058.6 | 59.44 | 0.00 | 0.00 |
| August | 0.173912E+10 | -0.156663E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172485540.5 | 59.44 | 0.00 | 0.00 |
| September | 0.173415E+10 | -0.156723E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -166920952.7 | 59.44 | 0.00 | 0.00 |
| October | 0.190351E+10 | -0.172831E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -175199406.9 | 59.44 | 0.00 | 0.00 |
| November | 0.198060E+10 | -0.180335E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -177245702.7 | 59.44 | 0.00 | 0.00 |
| December | 0.217503E+10 | -0.198862E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186412463.3 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.235978E+11 | -0.215049E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.209288E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.173415E+10 | -0.207117E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -186412463.3 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.225735E+10 | -0.156663E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -166920952.7 | 59.44 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: M S1 APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.224979E+10 | -0.207117E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -178618124.4 | 59.44 | 0.00 | 0.00 |
| February | 0.204541E+10 | -0.188496E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -160453450.7 | 59.44 | 0.00 | 0.00 |
| March | 0.221102E+10 | -0.203599E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -175029314.4 | 59.44 | 0.00 | 0.00 |
| April | 0.203389E+10 | -0.186651E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -167383265.3 | 59.44 | 0.00 | 0.00 |
| May | 0.196650E+10 | -0.179381E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172687072.7 | 59.44 | 0.00 | 0.00 |
| June | 0.178079E+10 | -0.161386E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -166936569.8 | 59.44 | 0.00 | 0.00 |
| July | 0.175696E+10 | -0.158447E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172485895.5 | 59.44 | 0.00 | 0.00 |
| August | 0.173912E+10 | -0.156663E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172485513.3 | 59.44 | 0.00 | 0.00 |
| September | 0.173415E+10 | -0.156723E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -166920079.1 | 59.44 | 0.00 | 0.00 |
| October | 0.190156E+10 | -0.172831E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -173244002.6 | 59.44 | 0.00 | 0.00 |
| November | 0.197217E+10 | -0.180335E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -168820106.5 | 59.44 | 0.00 | 0.00 |
| December | 0.216690E+10 | -0.198862E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -178273866.2 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.235582E+11 | -0.215049E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.205334E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.173415E+10 | -0.207117E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -178618124.4 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.224979E+10 | -0.156663E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -160453450.7 | 59.44 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: M S2 APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.224978E+10 | -0.207117E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -178608191.0 | 59.44 | 0.00 | 0.00 |
| February | 0.204543E+10 | -0.188496E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -160470984.5 | 59.44 | 0.00 | 0.00 |
| March | 0.221099E+10 | -0.203599E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -175005349.0 | 59.44 | 0.00 | 0.00 |
| April | 0.203389E+10 | -0.186651E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -167378726.6 | 59.44 | 0.00 | 0.00 |
| May | 0.196649E+10 | -0.179381E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172679367.6 | 59.44 | 0.00 | 0.00 |
| June | 0.178079E+10 | -0.161386E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -166935764.7 | 59.44 | 0.00 | 0.00 |
| July | 0.175696E+10 | -0.158447E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172485895.4 | 59.44 | 0.00 | 0.00 |
| August | 0.173912E+10 | -0.156663E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172485514.5 | 59.44 | 0.00 | 0.00 |
| September | 0.173415E+10 | -0.156723E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -166920085.3 | 59.44 | 0.00 | 0.00 |
| October | 0.190155E+10 | -0.172831E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -173242788.4 | 59.44 | 0.00 | 0.00 |
| November | 0.197217E+10 | -0.180335E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -168819190.3 | 59.44 | 0.00 | 0.00 |
| December | 0.216690E+10 | -0.198862E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -178274358.5 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.235582E+11 | -0.215049E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.205331E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.173415E+10 | -0.207117E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -178608191.0 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.224978E+10 | -0.156663E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -160470984.5 | 59.44 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: T SW APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.121874E+10 | -0.103558E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -183155560.7 | 59.44 | 0.00 | 0.00 |
| February | 0.110700E+10 | -942476703.6 | 0.00 | 0.00 | 672.00 | 0.00 | -164520088.8 | 59.44 | 0.00 | 0.00 |
| March | 0.119916E+10 | -0.101799E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -181162086.6 | 59.44 | 0.00 | 0.00 |
| April | 0.110486E+10 | -933253582.4 | 0.00 | 0.00 | 720.00 | 0.00 | -171605208.8 | 59.44 | 0.00 | 0.00 |
| May | 0.107217E+10 | -896906840.2 | 0.00 | 0.00 | 744.00 | 0.00 | -175259327.3 | 59.44 | 0.00 | 0.00 |
| June | 0.974623E+09 | -806928002.1 | 0.00 | 0.00 | 720.00 | 0.00 | -167695214.6 | 59.44 | 0.00 | 0.00 |
| July | 0.964737E+09 | -792233831.3 | 0.00 | 0.00 | 744.00 | 0.00 | -172502952.6 | 59.44 | 0.00 | 0.00 |
| August | 0.955868E+09 | -783313817.6 | 0.00 | 0.00 | 744.00 | 0.00 | -172554151.5 | 59.44 | 0.00 | 0.00 |
| September | 0.951242E+09 | -783609416.5 | 0.00 | 0.00 | 720.00 | 0.00 | -167632953.9 | 59.44 | 0.00 | 0.00 |
| October | 0.104122E+10 | -864155441.5 | 0.00 | 0.00 | 744.00 | 0.00 | -177069295.8 | 59.44 | 0.00 | 0.00 |
| November | 0.107694E+10 | -901674585.5 | 0.00 | 0.00 | 720.00 | 0.00 | -175260610.5 | 59.44 | 0.00 | 0.00 |
| December | 0.117725E+10 | -994309543.1 | 0.00 | 0.00 | 744.00 | 0.00 | -182936839.9 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.128438E+11 | -0.107524E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.209135E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.951242E+09 | -0.103558E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -183155560.7 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.121874E+10 | -783313817.6 | 0.00 | 0.00 | 744.00 | 0.00 | -164520088.8 | 59.44 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: T NW APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.122178E+10 | -0.103558E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186194815.7 | 59.44 | 0.00 | 0.00 |
| February | 0.110984E+10 | -942474719.9 | 0.00 | 0.00 | 672.00 | 0.00 | -167365699.0 | 59.44 | 0.00 | 0.00 |
| March | 0.120137E+10 | -0.101799E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -183378226.9 | 59.44 | 0.00 | 0.00 |
| April | 0.110590E+10 | -933253651.0 | 0.00 | 0.00 | 720.00 | 0.00 | -172644130.5 | 59.44 | 0.00 | 0.00 |
| May | 0.107226E+10 | -896906806.8 | 0.00 | 0.00 | 744.00 | 0.00 | -175356508.4 | 59.44 | 0.00 | 0.00 |
| June | 0.974543E+09 | -806928954.5 | 0.00 | 0.00 | 720.00 | 0.00 | -167613825.5 | 59.44 | 0.00 | 0.00 |
| July | 0.964736E+09 | -792235675.3 | 0.00 | 0.00 | 744.00 | 0.00 | -172500724.1 | 59.44 | 0.00 | 0.00 |
| August | 0.955877E+09 | -783317383.7 | 0.00 | 0.00 | 744.00 | 0.00 | -172560054.2 | 59.44 | 0.00 | 0.00 |
| September | 0.951507E+09 | -783605358.4 | 0.00 | 0.00 | 720.00 | 0.00 | -167901504.2 | 59.44 | 0.00 | 0.00 |
| October | 0.104342E+10 | -864150556.8 | 0.00 | 0.00 | 744.00 | 0.00 | -179269414.5 | 59.44 | 0.00 | 0.00 |
| November | 0.108094E+10 | -901675337.8 | 0.00 | 0.00 | 720.00 | 0.00 | -179261366.3 | 59.44 | 0.00 | 0.00 |
| December | 0.118079E+10 | -994307589.1 | 0.00 | 0.00 | 744.00 | 0.00 | -186479260.8 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.128630E+11 | -0.107524E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.211053E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.951507E+09 | -0.103558E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -186479260.8 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.122178E+10 | -783317383.7 | 0.00 | 0.00 | 744.00 | 0.00 | -167365699.0 | 59.44 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: T SE APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.121863E+10 | -0.103558E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -183049021.6 | 59.44 | 0.00 | 0.00 |
| February | 0.110689E+10 | -942478832.1 | 0.00 | 0.00 | 672.00 | 0.00 | -164408438.4 | 59.44 | 0.00 | 0.00 |
| March | 0.119876E+10 | -0.101799E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -180769202.0 | 59.44 | 0.00 | 0.00 |
| April | 0.110423E+10 | -933252814.8 | 0.00 | 0.00 | 720.00 | 0.00 | -170972353.6 | 59.44 | 0.00 | 0.00 |
| May | 0.107172E+10 | -896902712.0 | 0.00 | 0.00 | 744.00 | 0.00 | -174819849.5 | 59.44 | 0.00 | 0.00 |
| June | 0.974479E+09 | -806925068.7 | 0.00 | 0.00 | 720.00 | 0.00 | -167554153.9 | 59.44 | 0.00 | 0.00 |
| July | 0.964730E+09 | -792230230.8 | 0.00 | 0.00 | 744.00 | 0.00 | -172500099.7 | 59.44 | 0.00 | 0.00 |
| August | 0.955851E+09 | -783311670.5 | 0.00 | 0.00 | 744.00 | 0.00 | -172539387.8 | 59.44 | 0.00 | 0.00 |
| September | 0.951164E+09 | -783610600.8 | 0.00 | 0.00 | 720.00 | 0.00 | -167553112.2 | 59.44 | 0.00 | 0.00 |
| October | 0.104097E+10 | -864153703.8 | 0.00 | 0.00 | 744.00 | 0.00 | -176820826.0 | 59.44 | 0.00 | 0.00 |
| November | 0.107670E+10 | -901672025.3 | 0.00 | 0.00 | 720.00 | 0.00 | -175029268.5 | 59.44 | 0.00 | 0.00 |
| December | 0.117710E+10 | -994306956.2 | 0.00 | 0.00 | 744.00 | 0.00 | -182793753.0 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.128412E+11 | -0.107524E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.208881E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.951164E+09 | -0.103558E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -183049021.6 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.121863E+10 | -783311670.5 | 0.00 | 0.00 | 744.00 | 0.00 | -164408438.4 | 59.44 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: T NE APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.122205E+10 | -0.103558E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186472441.1 | 59.44 | 0.00 | 0.00 |
| February | 0.111008E+10 | -942477822.9 | 0.00 | 0.00 | 672.00 | 0.00 | -167602599.1 | 59.44 | 0.00 | 0.00 |
| March | 0.120107E+10 | -0.101799E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -183082604.4 | 59.44 | 0.00 | 0.00 |
| April | 0.110504E+10 | -933251758.5 | 0.00 | 0.00 | 720.00 | 0.00 | -171791709.3 | 59.44 | 0.00 | 0.00 |
| May | 0.107183E+10 | -896899651.5 | 0.00 | 0.00 | 744.00 | 0.00 | -174934737.4 | 59.44 | 0.00 | 0.00 |
| June | 0.974435E+09 | -806922666.0 | 0.00 | 0.00 | 720.00 | 0.00 | -167512698.3 | 59.44 | 0.00 | 0.00 |
| July | 0.964729E+09 | -792225759.3 | 0.00 | 0.00 | 744.00 | 0.00 | -172503477.8 | 59.44 | 0.00 | 0.00 |
| August | 0.955863E+09 | -783311339.0 | 0.00 | 0.00 | 744.00 | 0.00 | -172551453.1 | 59.44 | 0.00 | 0.00 |
| September | 0.951375E+09 | -783611300.6 | 0.00 | 0.00 | 720.00 | 0.00 | -167763345.2 | 59.44 | 0.00 | 0.00 |
| October | 0.104299E+10 | -864150947.5 | 0.00 | 0.00 | 744.00 | 0.00 | -178840533.1 | 59.44 | 0.00 | 0.00 |
| November | 0.108128E+10 | -901675086.6 | 0.00 | 0.00 | 720.00 | 0.00 | -179606633.3 | 59.44 | 0.00 | 0.00 |
| December | 0.118090E+10 | -994308066.4 | 0.00 | 0.00 | 744.00 | 0.00 | -186596206.3 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.128617E+11 | -0.107524E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.210926E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.951375E+09 | -0.103558E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -186596206.3 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.122205E+10 | -783311339.0 | 0.00 | 0.00 | 744.00 | 0.00 | -167512698.3 | 59.44 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: T N1 APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.122204E+10 | -0.103558E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186459103.8 | 59.44 | 0.00 | 0.00 |
| February | 0.111013E+10 | -942478009.6 | 0.00 | 0.00 | 672.00 | 0.00 | -167647185.4 | 59.44 | 0.00 | 0.00 |
| March | 0.120155E+10 | -0.101799E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -183559549.3 | 59.44 | 0.00 | 0.00 |
| April | 0.110534E+10 | -933255074.8 | 0.00 | 0.00 | 720.00 | 0.00 | -172089834.2 | 59.44 | 0.00 | 0.00 |
| May | 0.107161E+10 | -896900102.0 | 0.00 | 0.00 | 744.00 | 0.00 | -174714889.3 | 59.44 | 0.00 | 0.00 |
| June | 0.974244E+09 | -806930357.6 | 0.00 | 0.00 | 720.00 | 0.00 | -167314065.4 | 59.44 | 0.00 | 0.00 |
| July | 0.964725E+09 | -792237726.3 | 0.00 | 0.00 | 744.00 | 0.00 | -172486902.0 | 59.44 | 0.00 | 0.00 |
| August | 0.955823E+09 | -783312405.6 | 0.00 | 0.00 | 744.00 | 0.00 | -172510665.5 | 59.44 | 0.00 | 0.00 |
| September | 0.951052E+09 | -783606853.2 | 0.00 | 0.00 | 720.00 | 0.00 | -167445093.2 | 59.44 | 0.00 | 0.00 |
| October | 0.104302E+10 | -864153383.6 | 0.00 | 0.00 | 744.00 | 0.00 | -178869042.6 | 59.44 | 0.00 | 0.00 |
| November | 0.108126E+10 | -901675831.5 | 0.00 | 0.00 | 720.00 | 0.00 | -179582245.1 | 59.44 | 0.00 | 0.00 |
| December | 0.118089E+10 | -994308484.0 | 0.00 | 0.00 | 744.00 | 0.00 | -186583028.6 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.128617E+11 | -0.107524E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.210926E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.951052E+09 | -0.103558E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -186583028.6 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.122204E+10 | -783312405.6 | 0.00 | 0.00 | 744.00 | 0.00 | -167314065.4 | 59.44 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: T N2 APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.122204E+10 | -0.103558E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186463121.7 | 59.44 | 0.00 | 0.00 |
| February | 0.111013E+10 | -942478020.2 | 0.00 | 0.00 | 672.00 | 0.00 | -167653746.8 | 59.44 | 0.00 | 0.00 |
| March | 0.120151E+10 | -0.101799E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -183515445.8 | 59.44 | 0.00 | 0.00 |
| April | 0.110526E+10 | -933253942.0 | 0.00 | 0.00 | 720.00 | 0.00 | -172007449.0 | 59.44 | 0.00 | 0.00 |
| May | 0.107158E+10 | -896904227.0 | 0.00 | 0.00 | 744.00 | 0.00 | -174678898.6 | 59.44 | 0.00 | 0.00 |
| June | 0.974242E+09 | -806920766.3 | 0.00 | 0.00 | 720.00 | 0.00 | -167321313.4 | 59.44 | 0.00 | 0.00 |
| July | 0.964720E+09 | -792227382.2 | 0.00 | 0.00 | 744.00 | 0.00 | -172492473.0 | 59.44 | 0.00 | 0.00 |
| August | 0.955824E+09 | -783311892.5 | 0.00 | 0.00 | 744.00 | 0.00 | -172512167.0 | 59.44 | 0.00 | 0.00 |
| September | 0.951057E+09 | -783612794.8 | 0.00 | 0.00 | 720.00 | 0.00 | -167443931.8 | 59.44 | 0.00 | 0.00 |
| October | 0.104298E+10 | -864151124.3 | 0.00 | 0.00 | 744.00 | 0.00 | -178832789.2 | 59.44 | 0.00 | 0.00 |
| November | 0.108126E+10 | -901672457.0 | 0.00 | 0.00 | 720.00 | 0.00 | -179590948.8 | 59.44 | 0.00 | 0.00 |
| December | 0.118089E+10 | -994308607.4 | 0.00 | 0.00 | 744.00 | 0.00 | -186584468.9 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.128615E+11 | -0.107524E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.210910E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.951057E+09 | -0.103558E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -186584468.9 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.122204E+10 | -783311892.5 | 0.00 | 0.00 | 744.00 | 0.00 | -167321313.4 | 59.44 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: T S1 APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.121807E+10 | -0.103558E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -182488146.4 | 59.44 | 0.00 | 0.00 |
| February | 0.110632E+10 | -942476752.4 | 0.00 | 0.00 | 672.00 | 0.00 | -163839880.7 | 59.44 | 0.00 | 0.00 |
| March | 0.119839E+10 | -0.101799E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -180395058.6 | 59.44 | 0.00 | 0.00 |
| April | 0.110397E+10 | -933252235.3 | 0.00 | 0.00 | 720.00 | 0.00 | -170720692.8 | 59.44 | 0.00 | 0.00 |
| May | 0.107145E+10 | -896905164.2 | 0.00 | 0.00 | 744.00 | 0.00 | -174542974.8 | 59.44 | 0.00 | 0.00 |
| June | 0.974320E+09 | -806930459.6 | 0.00 | 0.00 | 720.00 | 0.00 | -167389090.8 | 59.44 | 0.00 | 0.00 |
| July | 0.964721E+09 | -792229507.2 | 0.00 | 0.00 | 744.00 | 0.00 | -172491420.9 | 59.44 | 0.00 | 0.00 |
| August | 0.955819E+09 | -783311887.6 | 0.00 | 0.00 | 744.00 | 0.00 | -172506951.8 | 59.44 | 0.00 | 0.00 |
| September | 0.950842E+09 | -783609315.6 | 0.00 | 0.00 | 720.00 | 0.00 | -167232269.2 | 59.44 | 0.00 | 0.00 |
| October | 0.104028E+10 | -864151879.7 | 0.00 | 0.00 | 744.00 | 0.00 | -176131484.9 | 59.44 | 0.00 | 0.00 |
| November | 0.107591E+10 | -901676984.6 | 0.00 | 0.00 | 720.00 | 0.00 | -174228334.8 | 59.44 | 0.00 | 0.00 |
| December | 0.117644E+10 | -994307589.6 | 0.00 | 0.00 | 744.00 | 0.00 | -182132089.8 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.128365E+11 | -0.107524E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.208410E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.950842E+09 | -0.103558E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -182488146.4 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.121807E+10 | -783311887.6 | 0.00 | 0.00 | 744.00 | 0.00 | -163839880.7 | 59.44 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: T S2 APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.121807E+10 | -0.103558E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -182487817.4 | 59.44 | 0.00 | 0.00 |
| February | 0.110632E+10 | -942476751.7 | 0.00 | 0.00 | 672.00 | 0.00 | -163842229.8 | 59.44 | 0.00 | 0.00 |
| March | 0.119836E+10 | -0.101799E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -180372316.3 | 59.44 | 0.00 | 0.00 |
| April | 0.110394E+10 | -933252262.6 | 0.00 | 0.00 | 720.00 | 0.00 | -170683912.5 | 59.44 | 0.00 | 0.00 |
| May | 0.107142E+10 | -896904317.9 | 0.00 | 0.00 | 744.00 | 0.00 | -174516808.2 | 59.44 | 0.00 | 0.00 |
| June | 0.974313E+09 | -806920624.4 | 0.00 | 0.00 | 720.00 | 0.00 | -167392008.0 | 59.44 | 0.00 | 0.00 |
| July | 0.964720E+09 | -792226228.4 | 0.00 | 0.00 | 744.00 | 0.00 | -172493694.3 | 59.44 | 0.00 | 0.00 |
| August | 0.955820E+09 | -783311957.3 | 0.00 | 0.00 | 744.00 | 0.00 | -172508203.5 | 59.44 | 0.00 | 0.00 |
| September | 0.950842E+09 | -783606655.6 | 0.00 | 0.00 | 720.00 | 0.00 | -167235300.1 | 59.44 | 0.00 | 0.00 |
| October | 0.104028E+10 | -864151981.2 | 0.00 | 0.00 | 744.00 | 0.00 | -176130062.4 | 59.44 | 0.00 | 0.00 |
| November | 0.107590E+10 | -901677661.8 | 0.00 | 0.00 | 720.00 | 0.00 | -174225805.4 | 59.44 | 0.00 | 0.00 |
| December | 0.117644E+10 | -994307591.9 | 0.00 | 0.00 | 744.00 | 0.00 | -182131269.9 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.128364E+11 | -0.107524E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.208402E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.950842E+09 | -0.103558E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -182487817.4 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.121807E+10 | -783311957.3 | 0.00 | 0.00 | 744.00 | 0.00 | -163842229.8 | 59.44 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
| January | 301.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 282.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 351.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 381.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 378.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 412.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 395.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 408.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 359.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 329.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 284.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 265.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 4149.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 265.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 412.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT GSW HEATING COIL
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.697049E+09 | 1300.73 | 19-JAN-02:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.580317E+09 | 1280.26 | 06-FEB-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.302943E+09 | 1098.61 | 04-MAR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 8097874.05 | 289.29 | 08-APR-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 3922950.92 | 280.58 | 26-OCT-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 1524567.68 | 198.65 | 12-NOV-06:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.444200E+09 | 1067.50 | 09-DEC-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.203805E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.697049E+09 | 1300.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT GNW HEATING COIL
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.187890E+10 | 1522.48 | 17-JAN-08:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.153113E+10 | 1684.96 | 06-FEB-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.879849E+09 | 1268.15 | 04-MAR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.100218E+09 | 672.84 | 08-APR-02:70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 471401.22 | 55.42 | 06-MAY-05:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 33928347.62 | 552.83 | 27-OCT-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.426817E+09 | 912.26 | 28-NOV-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.172406E+10 | 1422.48 | 22-DEC-08:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.657537E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.187890E+10 | 1684.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT OFFICE HEATING COIL
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 71297111.60 | 9947.14 | 17-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 14114013.60 | 9947.14 | 06-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 30777.35 | 512.96 | 06-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 1939722.87 | 5340.27 | 22-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 87381625.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 71297111.60 | 9947.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT GNE HEATING COIL
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.187517E+10 | 1552.49 | 20-JAN-02:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.154688E+10 | 1694.42 | 06-FEB-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.811199E+09 | 1266.73 | 04-MAR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 85094853.07 | 691.35 | 08-APR-02:70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 27107618.10 | 501.89 | 26-OCT-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.401342E+09 | 934.10 | 28-NOV-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.172909E+10 | 1434.57 | 14-DEC-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.647587E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.187517E+10 | 1694.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT GN1 HEATING COIL
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.128470E+10 | 1094.52 | 20-JAN-02:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.104322E+10 | 1165.97 | 05-FEB-08:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.511902E+09 | 861.27 | 05-MAR-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 45543936.89 | 432.17 | 08-APR-02:70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 2698317.38 | 234.34 | 27-OCT-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.215935E+09 | 628.79 | 28-NOV-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.119403E+10 | 992.91 | 23-DEC-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.429803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.128470E+10 | 1165.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT GN2 HEATING COIL
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.128529E+10 | 1098.13 | 20-JAN-02:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.104568E+10 | 1166.47 | 05-FEB-08:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.509259E+09 | 861.67 | 05-MAR-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 44945199.75 | 430.73 | 08-APR-02:70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 2512750.02 | 228.97 | 27-OCT-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.216092E+09 | 630.48 | 28-NOV-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.119537E+10 | 993.94 | 23-DEC-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.429914E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.128529E+10 | 1166.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT GS1 HEATING COIL
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.256196E+09 | 870.30 | 19-JAN-02:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.194388E+09 | 792.63 | 06-FEB-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 76996532.45 | 656.78 | 04-MAR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 88649370.86 | 694.79 | 09-DEC-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.616230E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.256196E+09 | 870.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT GS2 HEATING COIL
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.276318E+09 | 919.75 | 19-JAN-02:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.207165E+09 | 851.31 | 06-FEB-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 69119161.23 | 649.82 | 04-MAR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 89389369.27 | 694.86 | 09-DEC-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.641992E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.276318E+09 | 919.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT MSW HEATING COIL
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.765783E+09 | 2589.39 | 18-JAN-01:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.426761E+09 | 2415.24 | 06-FEB-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 50925799.17 | 1594.72 | 04-MAR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 29931206.51 | 1359.51 | 26-OCT-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 23524808.02 | 772.55 | 12-NOV-06:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.597344E+09 | 2359.74 | 22-DEC-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.189427E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.765783E+09 | 2589.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT MNW HEATING COIL
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.271893E+10 | 2868.39 | 17-JAN-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.178604E+10 | 3019.43 | 06-FEB-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.344221E+09 | 1962.10 | 04-MAR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.110541E+09 | 1587.15 | 26-OCT-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.780094E+09 | 2178.58 | 26-NOV-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.290639E+10 | 3103.08 | 14-DEC-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.864621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.290639E+10 | 3103.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT MSE HEATING COIL
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.780559E+09 | 2607.80 | 18-JAN-01:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.447629E+09 | 2420.36 | 06-FEB-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 42852527.45 | 1549.32 | 04-MAR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 26586134.14 | 1367.94 | 26-OCT-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 24859036.18 | 887.54 | 12-NOV-06:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.597922E+09 | 2323.44 | 22-DEC-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.192041E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.780559E+09 | 2607.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT MNE HEATING COIL
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.268796E+10 | 2912.62 | 17-JAN-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.180693E+10 | 3039.70 | 06-FEB-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.296377E+09 | 1962.18 | 04-MAR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 93307500.03 | 1573.66 | 26-OCT-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.727125E+09 | 2201.62 | 26-NOV-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.290406E+10 | 3153.64 | 14-DEC-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.851576E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.290406E+10 | 3153.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT MN1 HEATING COIL
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.155949E+10 | 1841.04 | 17-JAN-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.988582E+09 | 1936.68 | 06-FEB-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.104603E+09 | 1169.44 | 05-MAR-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 17349805.29 | 597.05 | 27-OCT-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.267599E+09 | 1296.62 | 28-NOV-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.171636E+10 | 1974.14 | 14-DEC-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.465398E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.171636E+10 | 1974.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT MN2 HEATING COIL
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.156384E+10 | 1843.39 | 17-JAN-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.994501E+09 | 1937.33 | 06-FEB-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.104009E+09 | 1174.63 | 05-MAR-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 16766428.31 | 595.75 | 27-OCT-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.268806E+09 | 1296.99 | 28-NOV-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.171992E+10 | 1975.37 | 14-DEC-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.466785E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.171992E+10 | 1975.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT MS1 HEATING COIL
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.235743E+09 | 1555.00 | 19-JAN-02:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 49755515.48 | 1114.01 | 06-FEB-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 1195972.85 | 216.29 | 04-MAR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 69896128.92 | 1332.98 | 09-DEC-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.356590E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.235743E+09 | 1555.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT MS2 HEATING COIL
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.237688E+09 | 1558.42 | 19-JAN-02:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 49807909.64 | 1112.14 | 06-FEB-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 998676.18 | 195.74 | 04-MAR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 69607096.89 | 1332.85 | 09-DEC-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.358101E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.237688E+09 | 1558.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT TSW HEATING COIL
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.192780E+10 | 2440.10 | 17-JAN-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.138244E+10 | 2534.99 | 06-FEB-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.822851E+09 | 1974.00 | 04-MAR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.192543E+09 | 1130.83 | 08-APR-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 65210708.65 | 940.54 | 05-MAY-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 4517497.84 | 439.46 | 09-JUN-03:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.296040E+09 | 1840.95 | 26-OCT-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.827673E+09 | 1897.56 | 26-NOV-06:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.182883E+10 | 2460.83 | 22-DEC-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.734790E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.192780E+10 | 2534.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT TNW HEATING COIL
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.287486E+10 | 2533.52 | 17-JAN-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.208936E+10 | 2664.80 | 06-FEB-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.113705E+10 | 2028.73 | 04-MAR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.257095E+09 | 1243.16 | 08-APR-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 68053012.17 | 968.60 | 05-MAY-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 3518148.27 | 476.94 | 09-JUN-03:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.472803E+09 | 1856.74 | 26-OCT-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.151284E+10 | 2141.97 | 26-NOV-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.301166E+10 | 2592.41 | 14-DEC-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.114272E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.301166E+10 | 2664.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT TSE HEATING COIL
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.190972E+10 | 2457.10 | 17-JAN-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.136694E+10 | 2543.22 | 06-FEB-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.768742E+09 | 1983.03 | 04-MAR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.165085E+09 | 1163.52 | 08-APR-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 48009620.51 | 883.18 | 05-MAY-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 2333262.60 | 397.80 | 09-JUN-03:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.285412E+09 | 1848.27 | 26-OCT-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.810164E+09 | 1917.71 | 26-NOV-06:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.180216E+10 | 2451.88 | 22-DEC-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.715857E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.190972E+10 | 2543.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT TNE HEATING COIL
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.284345E+10 | 2551.75 | 17-JAN-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.207420E+10 | 2674.69 | 06-FEB-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.104782E+10 | 2038.26 | 04-MAR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.220253E+09 | 1297.03 | 08-APR-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 51515786.54 | 908.38 | 05-MAY-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 2263193.39 | 428.69 | 09-JUN-03:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.435401E+09 | 1862.69 | 26-OCT-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.146799E+10 | 2160.99 | 26-NOV-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.300313E+10 | 2621.35 | 14-DEC-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.111460E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.300313E+10 | 2674.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT TN1 HEATING COIL
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.208685E+10 | 1793.29 | 17-JAN-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.149639E+10 | 1923.65 | 06-FEB-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.710715E+09 | 1433.55 | 04-MAR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.133717E+09 | 854.86 | 08-APR-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 26594873.93 | 579.76 | 05-MAY-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.283533E+09 | 1364.54 | 26-OCT-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.103105E+10 | 1544.59 | 27-NOV-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.222552E+10 | 1868.97 | 15-DEC-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.799437E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.222552E+10 | 1923.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT TN2 HEATING COIL
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.209034E+10 | 1794.20 | 17-JAN-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.150048E+10 | 1924.23 | 06-FEB-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.709076E+09 | 1434.55 | 04-MAR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.132602E+09 | 857.37 | 08-APR-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 25741059.12 | 567.48 | 05-MAY-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.283509E+09 | 1365.53 | 26-OCT-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.103373E+10 | 1545.09 | 27-NOV-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.222800E+10 | 1870.70 | 15-DEC-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.800347E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.222800E+10 | 1924.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT TS1 HEATING COIL
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.118941E+10 | 1700.38 | 19-JAN-02:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.821644E+09 | 1772.16 | 06-FEB-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.415946E+09 | 1369.71 | 04-MAR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 75385973.54 | 711.70 | 08-APR-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 23366687.70 | 548.10 | 05-MAY-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.150335E+09 | 1345.39 | 26-OCT-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.421235E+09 | 1250.94 | 27-NOV-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.110852E+10 | 1763.68 | 22-DEC-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.420584E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.118941E+10 | 1772.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT TS2 HEATING COIL
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.119173E+10 | 1703.52 | 19-JAN-02:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.824476E+09 | 1772.21 | 06-FEB-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.415674E+09 | 1370.71 | 04-MAR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 74805303.25 | 713.46 | 08-APR-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 22511985.90 | 535.41 | 05-MAY-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.150661E+09 | 1345.64 | 26-OCT-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.422503E+09 | 1253.78 | 27-NOV-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.111058E+10 | 1762.56 | 22-DEC-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.421295E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.119173E+10 | 1772.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT GSW COOLING COIL
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 23256309.86 | 23256309.86 | 644.38 | 02-JAN-15:30 | 644.38 | 0.00 |
| February | 0.00 | 0.00 | 36962247.48 | 36962247.48 | 927.49 | 14-FEB-16:10 | 927.49 | 0.00 |
| March | 0.00 | 0.00 | 40626917.80 | 40626917.80 | 692.61 | 12-MAR-16:30 | 692.61 | 0.00 |
| April | 0.00 | 0.00 | 0.417879E+09 | 0.417879E+09 | 1462.91 | 13-APR-16:30 | 1462.91 | 0.00 |
| May | 0.00 | 0.00 | 0.103982E+10 | 0.103552E+10 | 1964.12 | 19-MAY-16:40 | 1964.12 | 0.00 |
| June | 0.00 | 0.00 | 0.243497E+10 | 0.239918E+10 | 2744.65 | 28-JUN-16:30 | 2744.65 | 0.00 |
| July | 0.00 | 0.00 | 0.377509E+10 | 0.345980E+10 | 2943.24 | 21-JUL-17:05 | 2943.24 | 0.00 |
| August | 0.00 | 0.00 | 0.380211E+10 | 0.351637E+10 | 2953.06 | 20-AUG-17:05 | 2953.06 | 0.00 |
| September | 0.00 | 0.00 | 0.315312E+10 | 0.301190E+10 | 2883.23 | 20-SEP-16:30 | 2883.23 | 0.00 |
| October | 0.00 | 0.00 | 0.192447E+10 | 0.189447E+10 | 2640.34 | 06-OCT-16:05 | 2640.34 | 0.00 |
| November | 0.00 | 0.00 | 0.372502E+09 | 0.372502E+09 | 1372.22 | 01-NOV-15:10 | 1372.22 | 0.00 |
| December | 0.00 | 0.00 | 14522908.03 | 14522908.03 | 542.59 | 31-DEC-15:30 | 542.59 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.170353E+11 | 0.162230E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 14522908.03 | 14522908.03 | 542.59 | 542.59 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.380211E+10 | 0.351637E+10 | 2953.06 | 2953.06 | 0.00 |
Report: CoilReportMonthly
For: SPLIT GNW COOLING COIL
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.146817E+09 | 0.146817E+09 | 1016.17 | 29-APR-17:30 | 1016.17 | 0.00 |
| May | 0.00 | 0.00 | 0.837322E+09 | 0.833811E+09 | 1833.49 | 19-MAY-17:05 | 1833.49 | 0.00 |
| June | 0.00 | 0.00 | 0.246335E+10 | 0.242828E+10 | 2738.00 | 28-JUN-16:50 | 2738.00 | 0.00 |
| July | 0.00 | 0.00 | 0.362139E+10 | 0.331189E+10 | 2854.17 | 21-JUL-17:14 | 2854.17 | 0.00 |
| August | 0.00 | 0.00 | 0.330582E+10 | 0.304167E+10 | 2620.98 | 20-AUG-17:30 | 2620.98 | 0.00 |
| September | 0.00 | 0.00 | 0.213819E+10 | 0.202694E+10 | 2180.12 | 02-SEP-17:10 | 2180.12 | 0.00 |
| October | 0.00 | 0.00 | 0.731773E+09 | 0.711512E+09 | 1758.22 | 06-OCT-16:17 | 1758.22 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.132447E+11 | 0.125009E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.362139E+10 | 0.331189E+10 | 2854.17 | 2854.17 | 0.00 |
Report: CoilReportMonthly
For: SPLIT OFFICE COOLING COIL
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.108453E+09 | 0.108453E+09 | 1270.93 | 03-JAN-14:00 | 1270.93 | 0.00 |
| February | 0.00 | 0.00 | 0.122849E+09 | 0.122849E+09 | 1618.82 | 14-FEB-15:30 | 1618.82 | 0.00 |
| March | 0.00 | 0.00 | 0.287375E+09 | 0.287375E+09 | 1601.43 | 13-MAR-14:30 | 1601.43 | 0.00 |
| April | 0.00 | 0.00 | 0.804133E+09 | 0.804133E+09 | 6559.74 | 28-APR-08:62 | 6559.74 | 0.00 |
| May | 0.00 | 0.00 | 0.133676E+10 | 0.132133E+10 | 7702.66 | 22-MAY-07:02 | 7702.66 | 0.00 |
| June | 0.00 | 0.00 | 0.233864E+10 | 0.230291E+10 | 7793.87 | 05-JUN-08:62 | 6640.77 | 0.00 |
| July | 0.00 | 0.00 | 0.297753E+10 | 0.280976E+10 | 8155.97 | 17-JUL-07:02 | 6622.30 | 0.00 |
| August | 0.00 | 0.00 | 0.327584E+10 | 0.306967E+10 | 8230.87 | 14-AUG-07:02 | 6418.44 | 0.00 |
| September | 0.00 | 0.00 | 0.253521E+10 | 0.244665E+10 | 8118.26 | 06-SEP-07:02 | 6561.65 | 0.00 |
| October | 0.00 | 0.00 | 0.177243E+10 | 0.174349E+10 | 7930.89 | 11-OCT-07:02 | 7140.81 | 0.00 |
| November | 0.00 | 0.00 | 0.717153E+09 | 0.717153E+09 | 6469.37 | 01-NOV-08:62 | 6469.37 | 0.00 |
| December | 0.00 | 0.00 | 77381728.15 | 77381728.15 | 872.44 | 01-DEC-15:30 | 872.44 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.163538E+11 | 0.158112E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 77381728.15 | 77381728.15 | 872.44 | 872.44 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.327584E+10 | 0.306967E+10 | 8230.87 | 7702.66 | 0.00 |
Report: CoilReportMonthly
For: SPLIT GNE COOLING COIL
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.180144E+09 | 0.180144E+09 | 997.59 | 29-APR-16:10 | 997.59 | 0.00 |
| May | 0.00 | 0.00 | 0.942676E+09 | 0.934966E+09 | 1505.14 | 19-MAY-17:20 | 1505.14 | 0.00 |
| June | 0.00 | 0.00 | 0.261039E+10 | 0.257036E+10 | 2379.98 | 29-JUN-15:10 | 2379.98 | 0.00 |
| July | 0.00 | 0.00 | 0.382804E+10 | 0.349867E+10 | 2383.92 | 04-JUL-17:00 | 2383.92 | 0.00 |
| August | 0.00 | 0.00 | 0.345952E+10 | 0.317965E+10 | 2217.84 | 20-AUG-17:10 | 2217.84 | 0.00 |
| September | 0.00 | 0.00 | 0.219634E+10 | 0.208062E+10 | 1923.20 | 03-SEP-14:10 | 1904.88 | 0.00 |
| October | 0.00 | 0.00 | 0.732531E+09 | 0.710396E+09 | 1540.98 | 01-OCT-16:10 | 1540.98 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.139496E+11 | 0.131548E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.382804E+10 | 0.349867E+10 | 2383.92 | 2383.92 | 0.00 |
Report: CoilReportMonthly
For: SPLIT GN1 COOLING COIL
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 98752837.40 | 98752837.40 | 727.11 | 29-APR-16:10 | 727.11 | 0.00 |
| May | 0.00 | 0.00 | 0.730986E+09 | 0.724528E+09 | 1243.52 | 19-MAY-17:50 | 1243.52 | 0.00 |
| June | 0.00 | 0.00 | 0.205603E+10 | 0.201908E+10 | 1912.35 | 28-JUN-17:05 | 1912.35 | 0.00 |
| July | 0.00 | 0.00 | 0.305224E+10 | 0.276330E+10 | 1923.21 | 21-JUL-17:14 | 1923.21 | 0.00 |
| August | 0.00 | 0.00 | 0.272922E+10 | 0.248741E+10 | 1777.32 | 20-AUG-17:17 | 1777.32 | 0.00 |
| September | 0.00 | 0.00 | 0.176113E+10 | 0.165741E+10 | 1451.14 | 04-SEP-16:10 | 1310.49 | 0.00 |
| October | 0.00 | 0.00 | 0.576977E+09 | 0.557747E+09 | 1247.47 | 01-OCT-16:10 | 1247.47 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.110053E+11 | 0.103082E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.305224E+10 | 0.276330E+10 | 1923.21 | 1923.21 | 0.00 |
Report: CoilReportMonthly
For: SPLIT GN2 COOLING COIL
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.104344E+09 | 0.104344E+09 | 743.81 | 29-APR-16:10 | 743.81 | 0.00 |
| May | 0.00 | 0.00 | 0.741731E+09 | 0.734924E+09 | 1239.90 | 19-MAY-17:50 | 1239.90 | 0.00 |
| June | 0.00 | 0.00 | 0.206448E+10 | 0.202730E+10 | 1907.01 | 28-JUN-17:10 | 1907.01 | 0.00 |
| July | 0.00 | 0.00 | 0.306216E+10 | 0.277237E+10 | 1917.22 | 21-JUL-17:14 | 1917.22 | 0.00 |
| August | 0.00 | 0.00 | 0.273635E+10 | 0.249398E+10 | 1773.49 | 20-AUG-17:17 | 1773.49 | 0.00 |
| September | 0.00 | 0.00 | 0.176424E+10 | 0.166038E+10 | 1448.18 | 04-SEP-16:10 | 1307.92 | 0.00 |
| October | 0.00 | 0.00 | 0.578564E+09 | 0.559264E+09 | 1245.45 | 01-OCT-16:10 | 1245.45 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.110519E+11 | 0.103526E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.306216E+10 | 0.277237E+10 | 1917.22 | 1917.22 | 0.00 |
Report: CoilReportMonthly
For: SPLIT GS1 COOLING COIL
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 56844506.47 | 56844506.47 | 838.25 | 01-JAN-13:50 | 838.25 | 0.00 |
| February | 0.00 | 0.00 | 45902899.31 | 45902899.31 | 824.48 | 14-FEB-15:10 | 824.48 | 0.00 |
| March | 0.00 | 0.00 | 49623095.50 | 49623095.50 | 644.28 | 13-MAR-14:30 | 644.28 | 0.00 |
| April | 0.00 | 0.00 | 0.395880E+09 | 0.395880E+09 | 1120.29 | 29-APR-16:10 | 1120.29 | 0.00 |
| May | 0.00 | 0.00 | 0.954260E+09 | 0.946656E+09 | 1352.37 | 19-MAY-16:20 | 1352.37 | 0.00 |
| June | 0.00 | 0.00 | 0.203811E+10 | 0.200024E+10 | 1907.11 | 29-JUN-15:10 | 1907.11 | 0.00 |
| July | 0.00 | 0.00 | 0.322375E+10 | 0.292723E+10 | 2099.28 | 22-JUL-15:10 | 2099.28 | 0.00 |
| August | 0.00 | 0.00 | 0.324852E+10 | 0.298160E+10 | 2141.49 | 20-AUG-16:07 | 2141.49 | 0.00 |
| September | 0.00 | 0.00 | 0.280680E+10 | 0.267034E+10 | 2250.41 | 03-SEP-13:30 | 2201.70 | 0.00 |
| October | 0.00 | 0.00 | 0.186801E+10 | 0.183834E+10 | 2059.13 | 01-OCT-15:20 | 2059.13 | 0.00 |
| November | 0.00 | 0.00 | 0.553703E+09 | 0.553703E+09 | 1319.47 | 01-NOV-13:00 | 1319.47 | 0.00 |
| December | 0.00 | 0.00 | 41314847.77 | 41314847.77 | 644.33 | 31-DEC-15:00 | 644.33 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.152827E+11 | 0.145077E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 41314847.77 | 41314847.77 | 644.28 | 644.28 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.324852E+10 | 0.298160E+10 | 2250.41 | 2201.70 | 0.00 |
Report: CoilReportMonthly
For: SPLIT GS2 COOLING COIL
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 60091147.23 | 60091147.23 | 852.55 | 01-JAN-13:50 | 852.55 | 0.00 |
| February | 0.00 | 0.00 | 48198045.39 | 48198045.39 | 846.79 | 14-FEB-15:10 | 846.79 | 0.00 |
| March | 0.00 | 0.00 | 61112247.45 | 61112247.45 | 692.54 | 13-MAR-14:30 | 692.54 | 0.00 |
| April | 0.00 | 0.00 | 0.466220E+09 | 0.466220E+09 | 1220.97 | 29-APR-16:10 | 1220.97 | 0.00 |
| May | 0.00 | 0.00 | 0.110406E+10 | 0.109344E+10 | 1413.95 | 19-MAY-17:10 | 1413.95 | 0.00 |
| June | 0.00 | 0.00 | 0.227794E+10 | 0.223504E+10 | 1998.33 | 29-JUN-15:10 | 1998.33 | 0.00 |
| July | 0.00 | 0.00 | 0.357531E+10 | 0.325618E+10 | 2252.44 | 22-JUL-15:10 | 2252.44 | 0.00 |
| August | 0.00 | 0.00 | 0.358117E+10 | 0.329488E+10 | 2315.41 | 20-AUG-16:07 | 2315.41 | 0.00 |
| September | 0.00 | 0.00 | 0.309292E+10 | 0.294463E+10 | 2427.74 | 03-SEP-13:30 | 2379.24 | 0.00 |
| October | 0.00 | 0.00 | 0.206683E+10 | 0.203462E+10 | 2224.70 | 01-OCT-15:10 | 2224.70 | 0.00 |
| November | 0.00 | 0.00 | 0.602913E+09 | 0.602913E+09 | 1382.43 | 01-NOV-13:00 | 1382.43 | 0.00 |
| December | 0.00 | 0.00 | 46030460.12 | 46030460.12 | 665.92 | 31-DEC-15:00 | 665.92 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.169828E+11 | 0.161434E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 46030460.12 | 46030460.12 | 665.92 | 665.92 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.358117E+10 | 0.329488E+10 | 2427.74 | 2379.24 | 0.00 |
Report: CoilReportMonthly
For: SPLIT MSW COOLING COIL
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.439766E+09 | 0.439766E+09 | 3240.55 | 02-JAN-15:20 | 3240.55 | 0.00 |
| February | 0.00 | 0.00 | 0.620788E+09 | 0.620788E+09 | 4498.68 | 14-FEB-16:10 | 4498.68 | 0.00 |
| March | 0.00 | 0.00 | 0.100177E+10 | 0.100177E+10 | 4118.74 | 12-MAR-16:03 | 4118.74 | 0.00 |
| April | 0.00 | 0.00 | 0.290161E+10 | 0.290161E+10 | 5220.09 | 13-APR-16:27 | 5220.09 | 0.00 |
| May | 0.00 | 0.00 | 0.405397E+10 | 0.402296E+10 | 5667.18 | 19-MAY-16:25 | 5667.18 | 0.00 |
| June | 0.00 | 0.00 | 0.653005E+10 | 0.642907E+10 | 6860.97 | 28-JUN-16:30 | 6860.97 | 0.00 |
| July | 0.00 | 0.00 | 0.882114E+10 | 0.811323E+10 | 7049.99 | 21-JUL-17:03 | 7049.99 | 0.00 |
| August | 0.00 | 0.00 | 0.849636E+10 | 0.788139E+10 | 6933.72 | 20-AUG-17:00 | 6933.72 | 0.00 |
| September | 0.00 | 0.00 | 0.670345E+10 | 0.641818E+10 | 6835.94 | 20-SEP-16:17 | 6835.94 | 0.00 |
| October | 0.00 | 0.00 | 0.419852E+10 | 0.414122E+10 | 6147.87 | 06-OCT-16:03 | 6147.87 | 0.00 |
| November | 0.00 | 0.00 | 0.125251E+10 | 0.125251E+10 | 4062.22 | 20-NOV-15:30 | 4062.22 | 0.00 |
| December | 0.00 | 0.00 | 0.310538E+09 | 0.310538E+09 | 3136.32 | 31-DEC-15:30 | 3136.32 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.453305E+11 | 0.435330E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.310538E+09 | 0.310538E+09 | 3136.32 | 3136.32 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.882114E+10 | 0.811323E+10 | 7049.99 | 7049.99 | 0.00 |
Report: CoilReportMonthly
For: SPLIT MNW COOLING COIL
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 410189.37 | 410189.37 | 441.82 | 15-FEB-17:20 | 441.82 | 0.00 |
| March | 0.00 | 0.00 | 14360440.49 | 14360440.49 | 792.61 | 08-MAR-16:30 | 792.61 | 0.00 |
| April | 0.00 | 0.00 | 0.159134E+10 | 0.159134E+10 | 4324.78 | 13-APR-16:27 | 4324.78 | 0.00 |
| May | 0.00 | 0.00 | 0.354624E+10 | 0.351644E+10 | 5345.74 | 19-MAY-16:50 | 5345.74 | 0.00 |
| June | 0.00 | 0.00 | 0.657953E+10 | 0.647956E+10 | 6815.17 | 28-JUN-16:30 | 6815.17 | 0.00 |
| July | 0.00 | 0.00 | 0.847255E+10 | 0.777539E+10 | 6895.78 | 04-JUL-17:10 | 6895.78 | 0.00 |
| August | 0.00 | 0.00 | 0.742526E+10 | 0.685132E+10 | 6177.52 | 20-AUG-17:30 | 6177.52 | 0.00 |
| September | 0.00 | 0.00 | 0.455782E+10 | 0.433243E+10 | 5156.91 | 02-SEP-16:40 | 5156.91 | 0.00 |
| October | 0.00 | 0.00 | 0.154673E+10 | 0.150795E+10 | 4170.57 | 06-OCT-16:17 | 4170.57 | 0.00 |
| November | 0.00 | 0.00 | 1218110.92 | 1218110.92 | 424.65 | 02-NOV-17:40 | 424.65 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.337355E+11 | 0.320704E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.847255E+10 | 0.777539E+10 | 6895.78 | 6895.78 | 0.00 |
Report: CoilReportMonthly
For: SPLIT MSE COOLING COIL
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.418317E+09 | 0.418317E+09 | 2809.78 | 02-JAN-14:00 | 2809.78 | 0.00 |
| February | 0.00 | 0.00 | 0.576138E+09 | 0.576138E+09 | 3786.87 | 14-FEB-14:50 | 3786.87 | 0.00 |
| March | 0.00 | 0.00 | 0.106533E+10 | 0.106533E+10 | 3746.40 | 08-MAR-14:00 | 3746.40 | 0.00 |
| April | 0.00 | 0.00 | 0.319975E+10 | 0.319975E+10 | 4355.85 | 28-APR-13:00 | 4355.85 | 0.00 |
| May | 0.00 | 0.00 | 0.436119E+10 | 0.431744E+10 | 4517.42 | 19-MAY-13:00 | 4517.42 | 0.00 |
| June | 0.00 | 0.00 | 0.686186E+10 | 0.674917E+10 | 5828.26 | 29-JUN-15:10 | 5828.26 | 0.00 |
| July | 0.00 | 0.00 | 0.925803E+10 | 0.850657E+10 | 6128.46 | 22-JUL-14:00 | 6128.46 | 0.00 |
| August | 0.00 | 0.00 | 0.883044E+10 | 0.817819E+10 | 5918.14 | 17-AUG-13:30 | 5764.18 | 0.00 |
| September | 0.00 | 0.00 | 0.683483E+10 | 0.653862E+10 | 6285.15 | 03-SEP-13:30 | 6187.28 | 0.00 |
| October | 0.00 | 0.00 | 0.425362E+10 | 0.419199E+10 | 5564.88 | 10-OCT-12:30 | 5384.86 | 0.00 |
| November | 0.00 | 0.00 | 0.124102E+10 | 0.124102E+10 | 3575.31 | 01-NOV-12:50 | 3575.31 | 0.00 |
| December | 0.00 | 0.00 | 0.249956E+09 | 0.249956E+09 | 2531.66 | 31-DEC-14:30 | 2531.66 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.471505E+11 | 0.452325E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.249956E+09 | 0.249956E+09 | 2531.66 | 2531.66 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.925803E+10 | 0.850657E+10 | 6285.15 | 6187.28 | 0.00 |
Report: CoilReportMonthly
For: SPLIT MNE COOLING COIL
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 5314280.21 | 5314280.21 | 322.66 | 26-MAR-17:00 | 322.66 | 0.00 |
| April | 0.00 | 0.00 | 0.179987E+10 | 0.179987E+10 | 3328.94 | 29-APR-16:10 | 3328.94 | 0.00 |
| May | 0.00 | 0.00 | 0.384044E+10 | 0.379818E+10 | 4128.15 | 19-MAY-17:20 | 4128.15 | 0.00 |
| June | 0.00 | 0.00 | 0.691367E+10 | 0.680246E+10 | 5629.89 | 29-JUN-15:10 | 5629.89 | 0.00 |
| July | 0.00 | 0.00 | 0.890977E+10 | 0.816901E+10 | 5440.59 | 04-JUL-17:00 | 5440.59 | 0.00 |
| August | 0.00 | 0.00 | 0.776240E+10 | 0.714752E+10 | 4916.60 | 17-AUG-10:30 | 4488.91 | 0.00 |
| September | 0.00 | 0.00 | 0.469012E+10 | 0.445150E+10 | 4185.27 | 03-SEP-14:10 | 4149.48 | 0.00 |
| October | 0.00 | 0.00 | 0.154084E+10 | 0.149678E+10 | 3279.81 | 01-OCT-16:10 | 3279.81 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.354624E+11 | 0.336706E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.890977E+10 | 0.816901E+10 | 5629.89 | 5629.89 | 0.00 |
Report: CoilReportMonthly
For: SPLIT MN1 COOLING COIL
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 596907.90 | 596907.90 | 290.31 | 27-MAR-18:50 | 290.31 | 0.00 |
| April | 0.00 | 0.00 | 0.116873E+10 | 0.116873E+10 | 2481.72 | 29-APR-16:10 | 2481.72 | 0.00 |
| May | 0.00 | 0.00 | 0.284167E+10 | 0.280665E+10 | 3285.94 | 19-MAY-18:00 | 3285.94 | 0.00 |
| June | 0.00 | 0.00 | 0.516785E+10 | 0.507099E+10 | 4266.03 | 28-JUN-17:03 | 4266.03 | 0.00 |
| July | 0.00 | 0.00 | 0.680267E+10 | 0.617209E+10 | 4242.08 | 04-JUL-17:04 | 4242.08 | 0.00 |
| August | 0.00 | 0.00 | 0.591033E+10 | 0.539371E+10 | 3779.86 | 20-AUG-17:30 | 3779.86 | 0.00 |
| September | 0.00 | 0.00 | 0.369910E+10 | 0.348643E+10 | 3073.32 | 04-SEP-16:20 | 2782.55 | 0.00 |
| October | 0.00 | 0.00 | 0.121664E+10 | 0.117831E+10 | 2620.17 | 01-OCT-16:10 | 2620.17 | 0.00 |
| November | 0.00 | 0.00 | 260045.61 | 260045.61 | 159.89 | 02-NOV-17:50 | 159.89 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.268078E+11 | 0.252778E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.680267E+10 | 0.617209E+10 | 4266.03 | 4266.03 | 0.00 |
Report: CoilReportMonthly
For: SPLIT MN2 COOLING COIL
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 659977.91 | 659977.91 | 287.61 | 27-MAR-18:40 | 287.61 | 0.00 |
| April | 0.00 | 0.00 | 0.119019E+10 | 0.119019E+10 | 2496.40 | 29-APR-16:10 | 2496.40 | 0.00 |
| May | 0.00 | 0.00 | 0.285982E+10 | 0.282433E+10 | 3271.28 | 19-MAY-18:00 | 3271.28 | 0.00 |
| June | 0.00 | 0.00 | 0.518176E+10 | 0.508458E+10 | 4249.54 | 28-JUN-17:10 | 4249.54 | 0.00 |
| July | 0.00 | 0.00 | 0.681961E+10 | 0.618762E+10 | 4225.74 | 04-JUL-17:08 | 4225.74 | 0.00 |
| August | 0.00 | 0.00 | 0.592314E+10 | 0.540546E+10 | 3762.11 | 20-AUG-17:17 | 3762.11 | 0.00 |
| September | 0.00 | 0.00 | 0.370500E+10 | 0.349207E+10 | 3062.81 | 04-SEP-16:10 | 2765.91 | 0.00 |
| October | 0.00 | 0.00 | 0.122255E+10 | 0.118405E+10 | 2614.00 | 01-OCT-16:10 | 2614.00 | 0.00 |
| November | 0.00 | 0.00 | 216817.68 | 216817.68 | 130.08 | 02-NOV-17:50 | 130.08 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.269030E+11 | 0.253692E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.681961E+10 | 0.618762E+10 | 4249.54 | 4249.54 | 0.00 |
Report: CoilReportMonthly
For: SPLIT MS1 COOLING COIL
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.693595E+09 | 0.693595E+09 | 3274.99 | 01-JAN-13:50 | 3274.99 | 0.00 |
| February | 0.00 | 0.00 | 0.750997E+09 | 0.750997E+09 | 3723.17 | 14-FEB-15:00 | 3723.17 | 0.00 |
| March | 0.00 | 0.00 | 0.108700E+10 | 0.108700E+10 | 3386.40 | 08-MAR-14:00 | 3386.40 | 0.00 |
| April | 0.00 | 0.00 | 0.255374E+10 | 0.255374E+10 | 3361.64 | 26-APR-14:10 | 3361.64 | 0.00 |
| May | 0.00 | 0.00 | 0.336022E+10 | 0.332404E+10 | 3484.36 | 19-MAY-16:04 | 3484.36 | 0.00 |
| June | 0.00 | 0.00 | 0.511724E+10 | 0.501928E+10 | 4354.88 | 29-JUN-15:10 | 4354.88 | 0.00 |
| July | 0.00 | 0.00 | 0.715353E+10 | 0.651037E+10 | 4650.70 | 22-JUL-15:10 | 4650.70 | 0.00 |
| August | 0.00 | 0.00 | 0.698925E+10 | 0.642619E+10 | 4645.84 | 20-AUG-16:03 | 4645.84 | 0.00 |
| September | 0.00 | 0.00 | 0.586216E+10 | 0.558595E+10 | 5075.62 | 03-SEP-13:30 | 4976.08 | 0.00 |
| October | 0.00 | 0.00 | 0.404996E+10 | 0.399225E+10 | 4729.26 | 10-OCT-12:30 | 4559.17 | 0.00 |
| November | 0.00 | 0.00 | 0.171268E+10 | 0.171268E+10 | 3711.25 | 20-NOV-14:00 | 3711.25 | 0.00 |
| December | 0.00 | 0.00 | 0.590065E+09 | 0.590065E+09 | 3088.63 | 31-DEC-14:40 | 3088.63 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.399205E+11 | 0.382462E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.590065E+09 | 0.590065E+09 | 3088.63 | 3088.63 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.715353E+10 | 0.651037E+10 | 5075.62 | 4976.08 | 0.00 |
Report: CoilReportMonthly
For: SPLIT MS2 COOLING COIL
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.700972E+09 | 0.700972E+09 | 3290.49 | 01-JAN-13:50 | 3290.49 | 0.00 |
| February | 0.00 | 0.00 | 0.753678E+09 | 0.753678E+09 | 3729.87 | 14-FEB-15:00 | 3729.87 | 0.00 |
| March | 0.00 | 0.00 | 0.110532E+10 | 0.110532E+10 | 3406.59 | 08-MAR-14:00 | 3406.59 | 0.00 |
| April | 0.00 | 0.00 | 0.257499E+10 | 0.257499E+10 | 3378.35 | 26-APR-14:10 | 3378.35 | 0.00 |
| May | 0.00 | 0.00 | 0.337958E+10 | 0.334291E+10 | 3477.70 | 19-MAY-16:04 | 3477.70 | 0.00 |
| June | 0.00 | 0.00 | 0.513154E+10 | 0.503326E+10 | 4358.58 | 29-JUN-15:10 | 4358.58 | 0.00 |
| July | 0.00 | 0.00 | 0.717048E+10 | 0.652596E+10 | 4661.08 | 22-JUL-14:10 | 4661.08 | 0.00 |
| August | 0.00 | 0.00 | 0.700169E+10 | 0.643774E+10 | 4637.19 | 20-AUG-16:03 | 4637.19 | 0.00 |
| September | 0.00 | 0.00 | 0.586766E+10 | 0.559128E+10 | 5090.49 | 03-SEP-13:30 | 4991.16 | 0.00 |
| October | 0.00 | 0.00 | 0.405612E+10 | 0.399831E+10 | 4747.49 | 10-OCT-12:30 | 4577.49 | 0.00 |
| November | 0.00 | 0.00 | 0.172057E+10 | 0.172057E+10 | 3719.63 | 20-NOV-14:00 | 3719.63 | 0.00 |
| December | 0.00 | 0.00 | 0.595581E+09 | 0.595581E+09 | 3100.89 | 31-DEC-14:30 | 3100.89 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.400582E+11 | 0.383806E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.595581E+09 | 0.595581E+09 | 3100.89 | 3100.89 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.717048E+10 | 0.652596E+10 | 5090.49 | 4991.16 | 0.00 |
Report: CoilReportMonthly
For: SPLIT TSW COOLING COIL
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.388252E+09 | 0.388252E+09 | 2247.96 | 23-JAN-15:30 | 2247.96 | 0.00 |
| February | 0.00 | 0.00 | 0.484620E+09 | 0.484620E+09 | 2962.97 | 14-FEB-15:30 | 2962.97 | 0.00 |
| March | 0.00 | 0.00 | 0.635228E+09 | 0.635228E+09 | 2715.19 | 12-MAR-16:03 | 2715.19 | 0.00 |
| April | 0.00 | 0.00 | 0.140368E+10 | 0.140368E+10 | 3435.68 | 13-APR-16:14 | 3435.68 | 0.00 |
| May | 0.00 | 0.00 | 0.207754E+10 | 0.207084E+10 | 3865.02 | 19-MAY-16:30 | 3865.02 | 0.00 |
| June | 0.00 | 0.00 | 0.363593E+10 | 0.359540E+10 | 4781.26 | 28-JUN-16:30 | 4781.26 | 0.00 |
| July | 0.00 | 0.00 | 0.497478E+10 | 0.463572E+10 | 4811.48 | 22-JUL-15:30 | 4811.48 | 0.00 |
| August | 0.00 | 0.00 | 0.467279E+10 | 0.439146E+10 | 4823.29 | 20-AUG-16:08 | 4823.29 | 0.00 |
| September | 0.00 | 0.00 | 0.337662E+10 | 0.326102E+10 | 4451.93 | 21-SEP-15:20 | 4451.93 | 0.00 |
| October | 0.00 | 0.00 | 0.194958E+10 | 0.192828E+10 | 4048.67 | 01-OCT-15:20 | 4048.67 | 0.00 |
| November | 0.00 | 0.00 | 0.610270E+09 | 0.610270E+09 | 2403.35 | 20-NOV-15:20 | 2403.35 | 0.00 |
| December | 0.00 | 0.00 | 0.300416E+09 | 0.300416E+09 | 2217.64 | 31-DEC-15:30 | 2217.64 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.245097E+11 | 0.237052E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.300416E+09 | 0.300416E+09 | 2217.64 | 2217.64 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.497478E+10 | 0.463572E+10 | 4823.29 | 4823.29 | 0.00 |
Report: CoilReportMonthly
For: SPLIT TNW COOLING COIL
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 17159779.36 | 17159779.36 | 767.56 | 14-FEB-16:30 | 767.56 | 0.00 |
| March | 0.00 | 0.00 | 79258556.87 | 79258556.87 | 1126.95 | 08-MAR-16:30 | 1126.95 | 0.00 |
| April | 0.00 | 0.00 | 0.817478E+09 | 0.817478E+09 | 2892.51 | 13-APR-16:27 | 2892.51 | 0.00 |
| May | 0.00 | 0.00 | 0.180965E+10 | 0.180358E+10 | 3668.33 | 19-MAY-16:40 | 3668.33 | 0.00 |
| June | 0.00 | 0.00 | 0.364953E+10 | 0.360914E+10 | 4723.53 | 28-JUN-16:30 | 4723.53 | 0.00 |
| July | 0.00 | 0.00 | 0.478632E+10 | 0.444943E+10 | 4629.70 | 21-JUL-17:05 | 4629.70 | 0.00 |
| August | 0.00 | 0.00 | 0.409764E+10 | 0.383280E+10 | 4198.69 | 20-AUG-16:15 | 4198.69 | 0.00 |
| September | 0.00 | 0.00 | 0.228169E+10 | 0.219109E+10 | 3521.94 | 02-SEP-16:30 | 3521.94 | 0.00 |
| October | 0.00 | 0.00 | 0.714901E+09 | 0.700671E+09 | 2719.64 | 06-OCT-16:02 | 2719.64 | 0.00 |
| November | 0.00 | 0.00 | 579007.60 | 579007.60 | 167.18 | 02-NOV-17:40 | 167.18 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.182542E+11 | 0.175012E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.478632E+10 | 0.444943E+10 | 4723.53 | 4723.53 | 0.00 |
Report: CoilReportMonthly
For: SPLIT TSE COOLING COIL
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.357545E+09 | 0.357545E+09 | 1844.21 | 23-JAN-14:20 | 1844.21 | 0.00 |
| February | 0.00 | 0.00 | 0.426214E+09 | 0.426214E+09 | 2473.69 | 14-FEB-14:40 | 2473.69 | 0.00 |
| March | 0.00 | 0.00 | 0.615310E+09 | 0.615310E+09 | 2506.87 | 08-MAR-14:00 | 2506.87 | 0.00 |
| April | 0.00 | 0.00 | 0.147187E+10 | 0.147187E+10 | 2943.43 | 28-APR-13:00 | 2943.43 | 0.00 |
| May | 0.00 | 0.00 | 0.217276E+10 | 0.216098E+10 | 3161.57 | 19-MAY-13:00 | 3161.57 | 0.00 |
| June | 0.00 | 0.00 | 0.378973E+10 | 0.374250E+10 | 4031.29 | 29-JUN-14:40 | 4031.29 | 0.00 |
| July | 0.00 | 0.00 | 0.520626E+10 | 0.484097E+10 | 4291.83 | 22-JUL-14:00 | 4291.83 | 0.00 |
| August | 0.00 | 0.00 | 0.484965E+10 | 0.454361E+10 | 4087.17 | 17-AUG-13:30 | 4006.62 | 0.00 |
| September | 0.00 | 0.00 | 0.343504E+10 | 0.331262E+10 | 4333.92 | 03-SEP-13:30 | 4283.68 | 0.00 |
| October | 0.00 | 0.00 | 0.194467E+10 | 0.192071E+10 | 3728.00 | 01-OCT-13:40 | 3728.00 | 0.00 |
| November | 0.00 | 0.00 | 0.572822E+09 | 0.572822E+09 | 2007.17 | 24-NOV-14:00 | 2007.17 | 0.00 |
| December | 0.00 | 0.00 | 0.242019E+09 | 0.242019E+09 | 1755.78 | 31-DEC-14:40 | 1755.78 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.250839E+11 | 0.242072E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.242019E+09 | 0.242019E+09 | 1755.78 | 1755.78 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.520626E+10 | 0.484097E+10 | 4333.92 | 4291.83 | 0.00 |
Report: CoilReportMonthly
For: SPLIT TNE COOLING COIL
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 2849735.20 | 2849735.20 | 255.72 | 14-FEB-16:10 | 255.72 | 0.00 |
| March | 0.00 | 0.00 | 31195230.90 | 31195230.90 | 654.23 | 08-MAR-16:10 | 654.23 | 0.00 |
| April | 0.00 | 0.00 | 0.842579E+09 | 0.842579E+09 | 2011.09 | 28-APR-15:10 | 2011.09 | 0.00 |
| May | 0.00 | 0.00 | 0.190703E+10 | 0.189570E+10 | 2693.85 | 19-MAY-16:15 | 2693.85 | 0.00 |
| June | 0.00 | 0.00 | 0.381147E+10 | 0.376452E+10 | 3842.47 | 29-JUN-15:10 | 3842.47 | 0.00 |
| July | 0.00 | 0.00 | 0.501904E+10 | 0.465625E+10 | 3691.82 | 22-JUL-15:10 | 3691.82 | 0.00 |
| August | 0.00 | 0.00 | 0.427709E+10 | 0.398545E+10 | 3290.72 | 20-AUG-16:07 | 3290.72 | 0.00 |
| September | 0.00 | 0.00 | 0.233008E+10 | 0.223190E+10 | 2957.79 | 03-SEP-14:10 | 2941.26 | 0.00 |
| October | 0.00 | 0.00 | 0.655801E+09 | 0.638867E+09 | 2093.71 | 02-OCT-14:10 | 2034.49 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.188771E+11 | 0.180493E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.501904E+10 | 0.465625E+10 | 3842.47 | 3842.47 | 0.00 |
Report: CoilReportMonthly
For: SPLIT TN1 COOLING COIL
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 203237.61 | 203237.61 | 84.45 | 14-FEB-16:10 | 84.45 | 0.00 |
| March | 0.00 | 0.00 | 9395014.32 | 9395014.32 | 377.96 | 08-MAR-16:10 | 377.96 | 0.00 |
| April | 0.00 | 0.00 | 0.519840E+09 | 0.519840E+09 | 1586.49 | 13-APR-16:27 | 1586.49 | 0.00 |
| May | 0.00 | 0.00 | 0.138637E+10 | 0.137862E+10 | 2222.49 | 19-MAY-17:10 | 2222.49 | 0.00 |
| June | 0.00 | 0.00 | 0.289528E+10 | 0.285591E+10 | 3027.39 | 28-JUN-16:30 | 3027.39 | 0.00 |
| July | 0.00 | 0.00 | 0.393649E+10 | 0.362259E+10 | 2943.55 | 22-JUL-15:10 | 2943.55 | 0.00 |
| August | 0.00 | 0.00 | 0.333473E+10 | 0.308695E+10 | 2690.80 | 20-AUG-16:05 | 2690.80 | 0.00 |
| September | 0.00 | 0.00 | 0.180402E+10 | 0.171925E+10 | 2297.34 | 03-SEP-14:10 | 2277.49 | 0.00 |
| October | 0.00 | 0.00 | 0.481543E+09 | 0.467613E+09 | 1736.55 | 01-OCT-16:10 | 1736.55 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.143679E+11 | 0.136604E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.393649E+10 | 0.362259E+10 | 3027.39 | 3027.39 | 0.00 |
Report: CoilReportMonthly
For: SPLIT TN2 COOLING COIL
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 240302.32 | 240302.32 | 90.54 | 14-FEB-16:10 | 90.54 | 0.00 |
| March | 0.00 | 0.00 | 10047102.47 | 10047102.47 | 383.21 | 08-MAR-16:10 | 383.21 | 0.00 |
| April | 0.00 | 0.00 | 0.529695E+09 | 0.529695E+09 | 1570.80 | 13-APR-16:14 | 1570.80 | 0.00 |
| May | 0.00 | 0.00 | 0.139747E+10 | 0.138940E+10 | 2197.78 | 19-MAY-17:05 | 2197.78 | 0.00 |
| June | 0.00 | 0.00 | 0.290512E+10 | 0.286549E+10 | 3024.54 | 29-JUN-15:10 | 3024.54 | 0.00 |
| July | 0.00 | 0.00 | 0.394682E+10 | 0.363205E+10 | 2937.84 | 22-JUL-15:10 | 2937.84 | 0.00 |
| August | 0.00 | 0.00 | 0.334344E+10 | 0.309480E+10 | 2675.60 | 20-AUG-16:07 | 2675.60 | 0.00 |
| September | 0.00 | 0.00 | 0.181074E+10 | 0.172565E+10 | 2302.49 | 03-SEP-14:10 | 2282.87 | 0.00 |
| October | 0.00 | 0.00 | 0.484907E+09 | 0.470846E+09 | 1726.91 | 01-OCT-16:10 | 1726.91 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.144285E+11 | 0.137182E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.394682E+10 | 0.363205E+10 | 3024.54 | 3024.54 | 0.00 |
Report: CoilReportMonthly
For: SPLIT TS1 COOLING COIL
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.386577E+09 | 0.386577E+09 | 1835.58 | 23-JAN-14:40 | 1835.58 | 0.00 |
| February | 0.00 | 0.00 | 0.429926E+09 | 0.429926E+09 | 2290.60 | 14-FEB-15:00 | 2290.60 | 0.00 |
| March | 0.00 | 0.00 | 0.495425E+09 | 0.495425E+09 | 2169.09 | 08-MAR-14:00 | 2169.09 | 0.00 |
| April | 0.00 | 0.00 | 0.108598E+10 | 0.108598E+10 | 2380.45 | 26-APR-14:10 | 2380.45 | 0.00 |
| May | 0.00 | 0.00 | 0.164698E+10 | 0.163876E+10 | 2510.10 | 19-MAY-15:10 | 2510.10 | 0.00 |
| June | 0.00 | 0.00 | 0.287743E+10 | 0.283791E+10 | 3193.51 | 29-JUN-15:10 | 3193.51 | 0.00 |
| July | 0.00 | 0.00 | 0.412601E+10 | 0.380940E+10 | 3449.71 | 22-JUL-14:00 | 3449.71 | 0.00 |
| August | 0.00 | 0.00 | 0.391612E+10 | 0.364997E+10 | 3358.31 | 20-AUG-15:20 | 3358.31 | 0.00 |
| September | 0.00 | 0.00 | 0.292303E+10 | 0.281036E+10 | 3636.42 | 03-SEP-13:30 | 3584.75 | 0.00 |
| October | 0.00 | 0.00 | 0.173385E+10 | 0.171192E+10 | 3268.61 | 01-OCT-13:50 | 3268.61 | 0.00 |
| November | 0.00 | 0.00 | 0.596578E+09 | 0.596578E+09 | 2008.37 | 20-NOV-14:00 | 2008.37 | 0.00 |
| December | 0.00 | 0.00 | 0.320841E+09 | 0.320841E+09 | 1843.27 | 31-DEC-14:50 | 1843.27 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.205388E+11 | 0.197737E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.320841E+09 | 0.320841E+09 | 1835.58 | 1835.58 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.412601E+10 | 0.380940E+10 | 3636.42 | 3584.75 | 0.00 |
Report: CoilReportMonthly
For: SPLIT TS2 COOLING COIL
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.391494E+09 | 0.391494E+09 | 1846.00 | 23-JAN-14:40 | 1846.00 | 0.00 |
| February | 0.00 | 0.00 | 0.434452E+09 | 0.434452E+09 | 2297.16 | 14-FEB-14:50 | 2297.16 | 0.00 |
| March | 0.00 | 0.00 | 0.503941E+09 | 0.503941E+09 | 2190.35 | 08-MAR-14:00 | 2190.35 | 0.00 |
| April | 0.00 | 0.00 | 0.110060E+10 | 0.110060E+10 | 2395.04 | 26-APR-14:10 | 2395.04 | 0.00 |
| May | 0.00 | 0.00 | 0.165891E+10 | 0.165039E+10 | 2507.56 | 19-MAY-15:10 | 2507.56 | 0.00 |
| June | 0.00 | 0.00 | 0.288794E+10 | 0.284816E+10 | 3192.90 | 29-JUN-14:40 | 3192.90 | 0.00 |
| July | 0.00 | 0.00 | 0.413649E+10 | 0.381901E+10 | 3459.44 | 22-JUL-14:00 | 3459.44 | 0.00 |
| August | 0.00 | 0.00 | 0.392467E+10 | 0.365779E+10 | 3352.01 | 20-AUG-15:20 | 3352.01 | 0.00 |
| September | 0.00 | 0.00 | 0.292867E+10 | 0.281580E+10 | 3648.25 | 03-SEP-13:30 | 3596.82 | 0.00 |
| October | 0.00 | 0.00 | 0.174132E+10 | 0.171930E+10 | 3277.95 | 01-OCT-13:50 | 3277.95 | 0.00 |
| November | 0.00 | 0.00 | 0.603084E+09 | 0.603084E+09 | 2018.93 | 20-NOV-14:00 | 2018.93 | 0.00 |
| December | 0.00 | 0.00 | 0.325432E+09 | 0.325432E+09 | 1847.31 | 31-DEC-14:50 | 1847.31 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.206370E+11 | 0.198694E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.325432E+09 | 0.325432E+09 | 1846.00 | 1846.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.413649E+10 | 0.381901E+10 | 3648.25 | 3596.82 | 0.00 |
Report: FanReportMonthly
For: SPLIT GSW SUPPLY FAN
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 39849596.97 | 0.59 | 70.68 | 19-JAN-02:00 | 1.12 |
| February | 34658859.93 | 0.60 | 77.55 | 14-FEB-16:10 | 1.29 |
| March | 19908112.50 | 0.43 | 59.70 | 04-MAR-06:00 | 1.12 |
| April | 35577186.02 | 0.43 | 122.02 | 13-APR-16:30 | 1.27 |
| May | 86832592.08 | 0.74 | 166.92 | 19-MAY-16:40 | 1.24 |
| June | 0.203574E+09 | 1.14 | 251.45 | 28-JUN-16:30 | 1.21 |
| July | 0.303086E+09 | 1.25 | 260.26 | 21-JUL-17:10 | 1.20 |
| August | 0.302660E+09 | 1.25 | 246.17 | 20-AUG-17:10 | 1.20 |
| September | 0.251857E+09 | 1.26 | 237.09 | 20-SEP-16:30 | 1.21 |
| October | 0.156797E+09 | 0.97 | 213.91 | 06-OCT-16:10 | 1.22 |
| November | 31313486.28 | 0.40 | 112.26 | 01-NOV-15:10 | 1.26 |
| December | 25372441.15 | 0.50 | 58.01 | 09-DEC-05:00 | 1.12 |
| Annual Sum or Average | 0.149149E+10 | 0.80 | |||
| Minimum of Months | 19908112.50 | 0.40 | 58.01 | 1.12 | |
| Maximum of Months | 0.303086E+09 | 1.26 | 260.26 | 1.29 |
Report: FanReportMonthly
For: G SW APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.77 | 20.01 | 01-JAN-00:10 | 0.77 |
| February | 48400714.57 | 0.77 | 20.01 | 01-FEB-00:10 | 0.77 |
| March | 53586505.42 | 0.77 | 20.01 | 01-MAR-00:10 | 0.77 |
| April | 51857908.47 | 0.77 | 20.01 | 01-APR-00:10 | 0.77 |
| May | 53586505.42 | 0.77 | 20.01 | 01-MAY-00:10 | 0.77 |
| June | 51857908.47 | 0.77 | 20.01 | 01-JUN-00:10 | 0.77 |
| July | 53586505.42 | 0.76 | 20.01 | 01-JUL-00:10 | 0.76 |
| August | 53586505.42 | 0.76 | 20.01 | 01-AUG-00:10 | 0.76 |
| September | 51857908.47 | 0.76 | 20.01 | 01-SEP-00:10 | 0.76 |
| October | 53586505.42 | 0.77 | 20.01 | 01-OCT-00:10 | 0.76 |
| November | 51857908.47 | 0.77 | 20.01 | 01-NOV-00:10 | 0.77 |
| December | 53586505.42 | 0.77 | 20.01 | 01-DEC-00:10 | 0.77 |
| Annual Sum or Average | 0.630938E+09 | 0.77 | |||
| Minimum of Months | 48400714.57 | 0.76 | 20.01 | 0.76 | |
| Maximum of Months | 53586505.42 | 0.77 | 20.01 | 0.77 |
Report: FanReportMonthly
For: G SW APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.77 | 20.01 | 01-JAN-00:10 | 0.77 |
| February | 48400714.57 | 0.77 | 20.01 | 01-FEB-00:10 | 0.77 |
| March | 53586505.42 | 0.77 | 20.01 | 01-MAR-00:10 | 0.77 |
| April | 51857908.47 | 0.77 | 20.01 | 01-APR-00:10 | 0.77 |
| May | 53586505.42 | 0.77 | 20.01 | 01-MAY-00:10 | 0.77 |
| June | 51857908.47 | 0.76 | 20.01 | 01-JUN-00:10 | 0.77 |
| July | 53586505.42 | 0.76 | 20.01 | 01-JUL-00:10 | 0.76 |
| August | 53586505.42 | 0.76 | 20.01 | 01-AUG-00:10 | 0.76 |
| September | 51857908.47 | 0.76 | 20.01 | 01-SEP-00:10 | 0.76 |
| October | 53586505.42 | 0.77 | 20.01 | 01-OCT-00:10 | 0.77 |
| November | 51857908.47 | 0.77 | 20.01 | 01-NOV-00:10 | 0.77 |
| December | 53586505.42 | 0.77 | 20.01 | 01-DEC-00:10 | 0.77 |
| Annual Sum or Average | 0.630938E+09 | 0.77 | |||
| Minimum of Months | 48400714.57 | 0.76 | 20.01 | 0.76 | |
| Maximum of Months | 53586505.42 | 0.77 | 20.01 | 0.77 |
Report: FanReportMonthly
For: SPLIT GNW SUPPLY FAN
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.101932E+09 | 1.07 | 82.60 | 17-JAN-08:10 | 1.12 |
| February | 83065830.49 | 1.00 | 91.41 | 06-FEB-05:00 | 1.12 |
| March | 47732916.99 | 0.80 | 68.80 | 04-MAR-06:00 | 1.12 |
| April | 17872592.17 | 0.36 | 85.15 | 29-APR-17:10 | 1.28 |
| May | 70131855.82 | 0.68 | 156.00 | 19-MAY-17:05 | 1.25 |
| June | 0.205598E+09 | 1.14 | 249.18 | 28-JUN-16:40 | 1.21 |
| July | 0.290837E+09 | 1.26 | 251.38 | 21-JUL-17:10 | 1.20 |
| August | 0.264064E+09 | 1.26 | 220.88 | 20-AUG-17:30 | 1.21 |
| September | 0.172345E+09 | 1.27 | 178.34 | 02-SEP-17:00 | 1.23 |
| October | 61679562.93 | 0.65 | 145.29 | 06-OCT-16:20 | 1.25 |
| November | 23155381.32 | 0.54 | 49.49 | 28-NOV-05:00 | 1.12 |
| December | 93532284.06 | 1.08 | 77.17 | 22-DEC-08:13 | 1.12 |
| Annual Sum or Average | 0.143195E+10 | 0.92 | |||
| Minimum of Months | 17872592.17 | 0.36 | 49.49 | 1.12 | |
| Maximum of Months | 0.290837E+09 | 1.27 | 251.38 | 1.28 |
Report: FanReportMonthly
For: G NW APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.77 | 20.01 | 01-JAN-00:10 | 0.77 |
| February | 48400714.57 | 0.77 | 20.01 | 01-FEB-00:10 | 0.77 |
| March | 53586505.42 | 0.77 | 20.01 | 01-MAR-00:10 | 0.77 |
| April | 51857908.47 | 0.77 | 20.01 | 01-APR-00:10 | 0.77 |
| May | 53586505.42 | 0.77 | 20.01 | 01-MAY-00:10 | 0.77 |
| June | 51857908.47 | 0.77 | 20.01 | 01-JUN-00:10 | 0.77 |
| July | 53586505.42 | 0.76 | 20.01 | 01-JUL-00:10 | 0.76 |
| August | 53586505.42 | 0.76 | 20.01 | 01-AUG-00:10 | 0.76 |
| September | 51857908.47 | 0.76 | 20.01 | 01-SEP-00:10 | 0.76 |
| October | 53586505.42 | 0.77 | 20.01 | 01-OCT-00:10 | 0.76 |
| November | 51857908.47 | 0.77 | 20.01 | 01-NOV-00:10 | 0.77 |
| December | 53586505.42 | 0.77 | 20.01 | 01-DEC-00:10 | 0.77 |
| Annual Sum or Average | 0.630938E+09 | 0.77 | |||
| Minimum of Months | 48400714.57 | 0.76 | 20.01 | 0.76 | |
| Maximum of Months | 53586505.42 | 0.77 | 20.01 | 0.77 |
Report: FanReportMonthly
For: G NW APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.77 | 20.01 | 01-JAN-00:10 | 0.77 |
| February | 48400714.57 | 0.77 | 20.01 | 01-FEB-00:10 | 0.77 |
| March | 53586505.42 | 0.77 | 20.01 | 01-MAR-00:10 | 0.77 |
| April | 51857908.47 | 0.77 | 20.01 | 01-APR-00:10 | 0.77 |
| May | 53586505.42 | 0.77 | 20.01 | 01-MAY-00:10 | 0.77 |
| June | 51857908.47 | 0.76 | 20.01 | 01-JUN-00:10 | 0.77 |
| July | 53586505.42 | 0.76 | 20.01 | 01-JUL-00:10 | 0.76 |
| August | 53586505.42 | 0.76 | 20.01 | 01-AUG-00:10 | 0.76 |
| September | 51857908.47 | 0.76 | 20.01 | 01-SEP-00:10 | 0.76 |
| October | 53586505.42 | 0.77 | 20.01 | 01-OCT-00:10 | 0.77 |
| November | 51857908.47 | 0.77 | 20.01 | 01-NOV-00:10 | 0.77 |
| December | 53586505.42 | 0.77 | 20.01 | 01-DEC-00:10 | 0.77 |
| Annual Sum or Average | 0.630938E+09 | 0.77 | |||
| Minimum of Months | 48400714.57 | 0.76 | 20.01 | 0.76 | |
| Maximum of Months | 53586505.42 | 0.77 | 20.01 | 0.77 |
Report: FanReportMonthly
For: SPLIT OFFICE SUPPLY FAN
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.141110E+10 | 1.12 | 526.84 | 01-JAN-00:10 | 1.12 |
| February | 0.127454E+10 | 1.12 | 526.84 | 01-FEB-00:10 | 1.12 |
| March | 0.141110E+10 | 1.12 | 526.84 | 01-MAR-00:10 | 1.12 |
| April | 0.136558E+10 | 1.12 | 526.84 | 01-APR-00:10 | 1.12 |
| May | 0.141110E+10 | 1.12 | 526.84 | 01-MAY-00:10 | 1.12 |
| June | 0.136558E+10 | 1.11 | 526.84 | 01-JUN-00:10 | 1.12 |
| July | 0.141110E+10 | 1.11 | 526.84 | 01-JUL-00:10 | 1.11 |
| August | 0.141110E+10 | 1.11 | 526.84 | 01-AUG-00:10 | 1.10 |
| September | 0.136558E+10 | 1.11 | 526.84 | 01-SEP-00:10 | 1.11 |
| October | 0.141110E+10 | 1.12 | 526.84 | 01-OCT-00:10 | 1.11 |
| November | 0.136558E+10 | 1.12 | 526.84 | 01-NOV-00:10 | 1.12 |
| December | 0.141110E+10 | 1.12 | 526.84 | 01-DEC-00:10 | 1.12 |
| Annual Sum or Average | 0.166146E+11 | 1.11 | |||
| Minimum of Months | 0.127454E+10 | 1.11 | 526.84 | 1.10 | |
| Maximum of Months | 0.141110E+10 | 1.12 | 526.84 | 1.12 |
Report: FanReportMonthly
For: SPLIT GNE SUPPLY FAN
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.100875E+09 | 1.10 | 83.52 | 20-JAN-02:00 | 1.12 |
| February | 83214820.83 | 1.03 | 91.15 | 06-FEB-05:00 | 1.12 |
| March | 43638685.18 | 0.75 | 68.14 | 04-MAR-06:00 | 1.12 |
| April | 19817993.66 | 0.37 | 83.81 | 29-APR-16:10 | 1.28 |
| May | 78517837.25 | 0.76 | 128.68 | 19-MAY-17:05 | 1.25 |
| June | 0.216453E+09 | 1.17 | 213.64 | 28-JUN-16:30 | 1.21 |
| July | 0.305361E+09 | 1.25 | 211.42 | 21-JUL-17:00 | 1.21 |
| August | 0.274813E+09 | 1.25 | 187.87 | 20-AUG-17:10 | 1.22 |
| September | 0.176472E+09 | 1.26 | 158.71 | 03-SEP-14:10 | 1.23 |
| October | 61214486.32 | 0.68 | 127.34 | 01-OCT-16:10 | 1.25 |
| November | 21590301.31 | 0.51 | 50.25 | 28-NOV-05:00 | 1.12 |
| December | 93016727.13 | 1.09 | 77.17 | 14-DEC-04:00 | 1.12 |
| Annual Sum or Average | 0.147499E+10 | 0.93 | |||
| Minimum of Months | 19817993.66 | 0.37 | 50.25 | 1.12 | |
| Maximum of Months | 0.305361E+09 | 1.26 | 213.64 | 1.28 |
Report: FanReportMonthly
For: G NE APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.77 | 20.01 | 01-JAN-00:10 | 0.77 |
| February | 48400714.57 | 0.77 | 20.01 | 01-FEB-00:10 | 0.77 |
| March | 53586505.42 | 0.77 | 20.01 | 01-MAR-00:10 | 0.77 |
| April | 51857908.47 | 0.77 | 20.01 | 01-APR-00:10 | 0.77 |
| May | 53586505.42 | 0.77 | 20.01 | 01-MAY-00:10 | 0.77 |
| June | 51857908.47 | 0.77 | 20.01 | 01-JUN-00:10 | 0.77 |
| July | 53586505.42 | 0.76 | 20.01 | 01-JUL-00:10 | 0.76 |
| August | 53586505.42 | 0.76 | 20.01 | 01-AUG-00:10 | 0.76 |
| September | 51857908.47 | 0.76 | 20.01 | 01-SEP-00:10 | 0.76 |
| October | 53586505.42 | 0.77 | 20.01 | 01-OCT-00:10 | 0.76 |
| November | 51857908.47 | 0.77 | 20.01 | 01-NOV-00:10 | 0.77 |
| December | 53586505.42 | 0.77 | 20.01 | 01-DEC-00:10 | 0.77 |
| Annual Sum or Average | 0.630938E+09 | 0.77 | |||
| Minimum of Months | 48400714.57 | 0.76 | 20.01 | 0.76 | |
| Maximum of Months | 53586505.42 | 0.77 | 20.01 | 0.77 |
Report: FanReportMonthly
For: G NE APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.77 | 20.01 | 01-JAN-00:10 | 0.77 |
| February | 48400714.57 | 0.77 | 20.01 | 01-FEB-00:10 | 0.77 |
| March | 53586505.42 | 0.77 | 20.01 | 01-MAR-00:10 | 0.77 |
| April | 51857908.47 | 0.77 | 20.01 | 01-APR-00:10 | 0.77 |
| May | 53586505.42 | 0.77 | 20.01 | 01-MAY-00:10 | 0.77 |
| June | 51857908.47 | 0.76 | 20.01 | 01-JUN-00:10 | 0.77 |
| July | 53586505.42 | 0.76 | 20.01 | 01-JUL-00:10 | 0.76 |
| August | 53586505.42 | 0.76 | 20.01 | 01-AUG-00:10 | 0.76 |
| September | 51857908.47 | 0.76 | 20.01 | 01-SEP-00:10 | 0.76 |
| October | 53586505.42 | 0.77 | 20.01 | 01-OCT-00:10 | 0.77 |
| November | 51857908.47 | 0.77 | 20.01 | 01-NOV-00:10 | 0.77 |
| December | 53586505.42 | 0.77 | 20.01 | 01-DEC-00:10 | 0.77 |
| Annual Sum or Average | 0.630938E+09 | 0.77 | |||
| Minimum of Months | 48400714.57 | 0.76 | 20.01 | 0.76 | |
| Maximum of Months | 53586505.42 | 0.77 | 20.01 | 0.77 |
Report: FanReportMonthly
For: SPLIT GN1 SUPPLY FAN
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 68308894.67 | 1.07 | 58.20 | 20-JAN-02:00 | 1.12 |
| February | 55469032.65 | 0.98 | 62.00 | 05-FEB-08:13 | 1.12 |
| March | 27218360.43 | 0.70 | 45.79 | 05-MAR-05:00 | 1.12 |
| April | 10801691.33 | 0.29 | 61.42 | 29-APR-16:10 | 1.28 |
| May | 61062424.81 | 0.78 | 106.31 | 19-MAY-17:50 | 1.26 |
| June | 0.171287E+09 | 1.20 | 174.45 | 28-JUN-17:00 | 1.22 |
| July | 0.244210E+09 | 1.25 | 171.98 | 21-JUL-17:10 | 1.22 |
| August | 0.217554E+09 | 1.26 | 151.52 | 20-AUG-17:30 | 1.23 |
| September | 0.141856E+09 | 1.27 | 119.58 | 03-SEP-14:10 | 1.24 |
| October | 47288833.09 | 0.63 | 103.49 | 01-OCT-16:10 | 1.25 |
| November | 11481457.93 | 0.40 | 33.43 | 28-NOV-05:00 | 1.12 |
| December | 63487704.96 | 1.08 | 52.79 | 23-DEC-05:00 | 1.12 |
| Annual Sum or Average | 0.112003E+10 | 0.91 | |||
| Minimum of Months | 10801691.33 | 0.29 | 33.43 | 1.12 | |
| Maximum of Months | 0.244210E+09 | 1.27 | 174.45 | 1.28 |
Report: FanReportMonthly
For: G N1 APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.77 | 20.01 | 01-JAN-00:10 | 0.77 |
| February | 48400714.57 | 0.77 | 20.01 | 01-FEB-00:10 | 0.77 |
| March | 53586505.42 | 0.77 | 20.01 | 01-MAR-00:10 | 0.77 |
| April | 51857908.47 | 0.77 | 20.01 | 01-APR-00:10 | 0.77 |
| May | 53586505.42 | 0.77 | 20.01 | 01-MAY-00:10 | 0.77 |
| June | 51857908.47 | 0.77 | 20.01 | 01-JUN-00:10 | 0.77 |
| July | 53586505.42 | 0.76 | 20.01 | 01-JUL-00:10 | 0.76 |
| August | 53586505.42 | 0.76 | 20.01 | 01-AUG-00:10 | 0.76 |
| September | 51857908.47 | 0.76 | 20.01 | 01-SEP-00:10 | 0.76 |
| October | 53586505.42 | 0.77 | 20.01 | 01-OCT-00:10 | 0.76 |
| November | 51857908.47 | 0.77 | 20.01 | 01-NOV-00:10 | 0.77 |
| December | 53586505.42 | 0.77 | 20.01 | 01-DEC-00:10 | 0.77 |
| Annual Sum or Average | 0.630938E+09 | 0.77 | |||
| Minimum of Months | 48400714.57 | 0.76 | 20.01 | 0.76 | |
| Maximum of Months | 53586505.42 | 0.77 | 20.01 | 0.77 |
Report: FanReportMonthly
For: G N1 APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.77 | 20.01 | 01-JAN-00:10 | 0.77 |
| February | 48400714.57 | 0.77 | 20.01 | 01-FEB-00:10 | 0.77 |
| March | 53586505.42 | 0.77 | 20.01 | 01-MAR-00:10 | 0.77 |
| April | 51857908.47 | 0.77 | 20.01 | 01-APR-00:10 | 0.77 |
| May | 53586505.42 | 0.77 | 20.01 | 01-MAY-00:10 | 0.77 |
| June | 51857908.47 | 0.76 | 20.01 | 01-JUN-00:10 | 0.77 |
| July | 53586505.42 | 0.76 | 20.01 | 01-JUL-00:10 | 0.76 |
| August | 53586505.42 | 0.76 | 20.01 | 01-AUG-00:10 | 0.76 |
| September | 51857908.47 | 0.76 | 20.01 | 01-SEP-00:10 | 0.76 |
| October | 53586505.42 | 0.77 | 20.01 | 01-OCT-00:10 | 0.77 |
| November | 51857908.47 | 0.77 | 20.01 | 01-NOV-00:10 | 0.77 |
| December | 53586505.42 | 0.77 | 20.01 | 01-DEC-00:10 | 0.77 |
| Annual Sum or Average | 0.630938E+09 | 0.77 | |||
| Minimum of Months | 48400714.57 | 0.76 | 20.01 | 0.76 | |
| Maximum of Months | 53586505.42 | 0.77 | 20.01 | 0.77 |
Report: FanReportMonthly
For: SPLIT GN2 SUPPLY FAN
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 68324724.62 | 1.07 | 58.38 | 20-JAN-02:00 | 1.12 |
| February | 55587061.34 | 0.98 | 62.01 | 05-FEB-08:13 | 1.12 |
| March | 27071704.79 | 0.69 | 45.81 | 05-MAR-05:00 | 1.12 |
| April | 11241127.67 | 0.30 | 62.79 | 29-APR-16:10 | 1.28 |
| May | 61937213.12 | 0.79 | 106.05 | 19-MAY-17:30 | 1.26 |
| June | 0.171953E+09 | 1.20 | 174.03 | 28-JUN-17:00 | 1.22 |
| July | 0.244952E+09 | 1.25 | 171.49 | 21-JUL-17:10 | 1.22 |
| August | 0.218088E+09 | 1.26 | 151.16 | 20-AUG-17:20 | 1.23 |
| September | 0.142093E+09 | 1.27 | 119.79 | 03-SEP-14:10 | 1.24 |
| October | 47404771.11 | 0.63 | 103.32 | 01-OCT-16:10 | 1.25 |
| November | 11487259.69 | 0.40 | 33.52 | 28-NOV-05:00 | 1.12 |
| December | 63544640.11 | 1.08 | 52.84 | 23-DEC-05:00 | 1.12 |
| Annual Sum or Average | 0.112368E+10 | 0.91 | |||
| Minimum of Months | 11241127.67 | 0.30 | 33.52 | 1.12 | |
| Maximum of Months | 0.244952E+09 | 1.27 | 174.03 | 1.28 |
Report: FanReportMonthly
For: G N2 APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.77 | 20.01 | 01-JAN-00:10 | 0.77 |
| February | 48400714.57 | 0.77 | 20.01 | 01-FEB-00:10 | 0.77 |
| March | 53586505.42 | 0.77 | 20.01 | 01-MAR-00:10 | 0.77 |
| April | 51857908.47 | 0.77 | 20.01 | 01-APR-00:10 | 0.77 |
| May | 53586505.42 | 0.77 | 20.01 | 01-MAY-00:10 | 0.77 |
| June | 51857908.47 | 0.77 | 20.01 | 01-JUN-00:10 | 0.77 |
| July | 53586505.42 | 0.76 | 20.01 | 01-JUL-00:10 | 0.76 |
| August | 53586505.42 | 0.76 | 20.01 | 01-AUG-00:10 | 0.76 |
| September | 51857908.47 | 0.76 | 20.01 | 01-SEP-00:10 | 0.76 |
| October | 53586505.42 | 0.77 | 20.01 | 01-OCT-00:10 | 0.76 |
| November | 51857908.47 | 0.77 | 20.01 | 01-NOV-00:10 | 0.77 |
| December | 53586505.42 | 0.77 | 20.01 | 01-DEC-00:10 | 0.77 |
| Annual Sum or Average | 0.630938E+09 | 0.77 | |||
| Minimum of Months | 48400714.57 | 0.76 | 20.01 | 0.76 | |
| Maximum of Months | 53586505.42 | 0.77 | 20.01 | 0.77 |
Report: FanReportMonthly
For: G N2 APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.77 | 20.01 | 01-JAN-00:10 | 0.77 |
| February | 48400714.57 | 0.77 | 20.01 | 01-FEB-00:10 | 0.77 |
| March | 53586505.42 | 0.77 | 20.01 | 01-MAR-00:10 | 0.77 |
| April | 51857908.47 | 0.77 | 20.01 | 01-APR-00:10 | 0.77 |
| May | 53586505.42 | 0.77 | 20.01 | 01-MAY-00:10 | 0.77 |
| June | 51857908.47 | 0.76 | 20.01 | 01-JUN-00:10 | 0.77 |
| July | 53586505.42 | 0.76 | 20.01 | 01-JUL-00:10 | 0.76 |
| August | 53586505.42 | 0.76 | 20.01 | 01-AUG-00:10 | 0.76 |
| September | 51857908.47 | 0.76 | 20.01 | 01-SEP-00:10 | 0.76 |
| October | 53586505.42 | 0.77 | 20.01 | 01-OCT-00:10 | 0.77 |
| November | 51857908.47 | 0.77 | 20.01 | 01-NOV-00:10 | 0.77 |
| December | 53586505.42 | 0.77 | 20.01 | 01-DEC-00:10 | 0.77 |
| Annual Sum or Average | 0.630938E+09 | 0.77 | |||
| Minimum of Months | 48400714.57 | 0.76 | 20.01 | 0.76 | |
| Maximum of Months | 53586505.42 | 0.77 | 20.01 | 0.77 |
Report: FanReportMonthly
For: SPLIT GS1 SUPPLY FAN
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 18454281.90 | 0.38 | 69.92 | 01-JAN-13:50 | 1.28 |
| February | 14245074.31 | 0.37 | 68.80 | 14-FEB-15:10 | 1.28 |
| March | 8316502.41 | 0.25 | 54.08 | 13-MAR-14:30 | 1.29 |
| April | 33293191.33 | 0.49 | 93.49 | 29-APR-16:10 | 1.27 |
| May | 79536759.11 | 0.86 | 115.84 | 19-MAY-17:10 | 1.25 |
| June | 0.170116E+09 | 1.20 | 177.00 | 28-JUN-16:10 | 1.22 |
| July | 0.257887E+09 | 1.25 | 183.13 | 22-JUL-15:10 | 1.21 |
| August | 0.257937E+09 | 1.25 | 180.72 | 20-AUG-16:10 | 1.21 |
| September | 0.223706E+09 | 1.26 | 181.72 | 03-SEP-13:40 | 1.21 |
| October | 0.151900E+09 | 1.06 | 166.05 | 01-OCT-15:20 | 1.22 |
| November | 46296054.21 | 0.60 | 107.15 | 01-NOV-13:00 | 1.26 |
| December | 8230769.18 | 0.27 | 54.09 | 31-DEC-15:00 | 1.29 |
| Annual Sum or Average | 0.126992E+10 | 0.77 | |||
| Minimum of Months | 8230769.18 | 0.25 | 54.08 | 1.21 | |
| Maximum of Months | 0.257937E+09 | 1.26 | 183.13 | 1.29 |
Report: FanReportMonthly
For: G S1 APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.77 | 20.01 | 01-JAN-00:10 | 0.77 |
| February | 48400714.57 | 0.77 | 20.01 | 01-FEB-00:10 | 0.77 |
| March | 53586505.42 | 0.77 | 20.01 | 01-MAR-00:10 | 0.77 |
| April | 51857908.47 | 0.77 | 20.01 | 01-APR-00:10 | 0.77 |
| May | 53586505.42 | 0.77 | 20.01 | 01-MAY-00:10 | 0.77 |
| June | 51857908.47 | 0.77 | 20.01 | 01-JUN-00:10 | 0.77 |
| July | 53586505.42 | 0.76 | 20.01 | 01-JUL-00:10 | 0.76 |
| August | 53586505.42 | 0.76 | 20.01 | 01-AUG-00:10 | 0.76 |
| September | 51857908.47 | 0.76 | 20.01 | 01-SEP-00:10 | 0.76 |
| October | 53586505.42 | 0.77 | 20.01 | 01-OCT-00:10 | 0.76 |
| November | 51857908.47 | 0.77 | 20.01 | 01-NOV-00:10 | 0.77 |
| December | 53586505.42 | 0.77 | 20.01 | 01-DEC-00:10 | 0.77 |
| Annual Sum or Average | 0.630938E+09 | 0.77 | |||
| Minimum of Months | 48400714.57 | 0.76 | 20.01 | 0.76 | |
| Maximum of Months | 53586505.42 | 0.77 | 20.01 | 0.77 |
Report: FanReportMonthly
For: G S1 APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.77 | 20.01 | 01-JAN-00:10 | 0.77 |
| February | 48400714.57 | 0.77 | 20.01 | 01-FEB-00:10 | 0.77 |
| March | 53586505.42 | 0.77 | 20.01 | 01-MAR-00:10 | 0.77 |
| April | 51857908.47 | 0.77 | 20.01 | 01-APR-00:10 | 0.77 |
| May | 53586505.42 | 0.77 | 20.01 | 01-MAY-00:10 | 0.77 |
| June | 51857908.47 | 0.76 | 20.01 | 01-JUN-00:10 | 0.77 |
| July | 53586505.42 | 0.76 | 20.01 | 01-JUL-00:10 | 0.76 |
| August | 53586505.42 | 0.76 | 20.01 | 01-AUG-00:10 | 0.76 |
| September | 51857908.47 | 0.76 | 20.01 | 01-SEP-00:10 | 0.76 |
| October | 53586505.42 | 0.77 | 20.01 | 01-OCT-00:10 | 0.77 |
| November | 51857908.47 | 0.77 | 20.01 | 01-NOV-00:10 | 0.77 |
| December | 53586505.42 | 0.77 | 20.01 | 01-DEC-00:10 | 0.77 |
| Annual Sum or Average | 0.630938E+09 | 0.77 | |||
| Minimum of Months | 48400714.57 | 0.76 | 20.01 | 0.76 | |
| Maximum of Months | 53586505.42 | 0.77 | 20.01 | 0.77 |
Report: FanReportMonthly
For: SPLIT GS2 SUPPLY FAN
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 19811452.96 | 0.39 | 71.09 | 01-JAN-13:50 | 1.28 |
| February | 15127246.21 | 0.39 | 70.62 | 14-FEB-15:10 | 1.28 |
| March | 8871310.44 | 0.26 | 58.05 | 13-MAR-14:30 | 1.29 |
| April | 39162336.75 | 0.55 | 101.58 | 29-APR-16:10 | 1.26 |
| May | 91767439.21 | 0.94 | 120.96 | 19-MAY-17:10 | 1.25 |
| June | 0.189423E+09 | 1.22 | 184.47 | 28-JUN-16:10 | 1.22 |
| July | 0.285048E+09 | 1.25 | 195.57 | 22-JUL-15:10 | 1.21 |
| August | 0.283514E+09 | 1.25 | 194.39 | 20-AUG-16:10 | 1.21 |
| September | 0.245861E+09 | 1.26 | 195.17 | 03-SEP-13:40 | 1.21 |
| October | 0.167753E+09 | 1.08 | 178.53 | 01-OCT-15:20 | 1.22 |
| November | 50374363.54 | 0.62 | 112.08 | 01-NOV-13:00 | 1.25 |
| December | 8671627.78 | 0.27 | 55.87 | 31-DEC-15:00 | 1.29 |
| Annual Sum or Average | 0.140538E+10 | 0.79 | |||
| Minimum of Months | 8671627.78 | 0.26 | 55.87 | 1.21 | |
| Maximum of Months | 0.285048E+09 | 1.26 | 195.57 | 1.29 |
Report: FanReportMonthly
For: G S2 APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.77 | 20.01 | 01-JAN-00:10 | 0.77 |
| February | 48400714.57 | 0.77 | 20.01 | 01-FEB-00:10 | 0.77 |
| March | 53586505.42 | 0.77 | 20.01 | 01-MAR-00:10 | 0.77 |
| April | 51857908.47 | 0.77 | 20.01 | 01-APR-00:10 | 0.77 |
| May | 53586505.42 | 0.77 | 20.01 | 01-MAY-00:10 | 0.77 |
| June | 51857908.47 | 0.77 | 20.01 | 01-JUN-00:10 | 0.77 |
| July | 53586505.42 | 0.76 | 20.01 | 01-JUL-00:10 | 0.76 |
| August | 53586505.42 | 0.76 | 20.01 | 01-AUG-00:10 | 0.76 |
| September | 51857908.47 | 0.76 | 20.01 | 01-SEP-00:10 | 0.76 |
| October | 53586505.42 | 0.77 | 20.01 | 01-OCT-00:10 | 0.76 |
| November | 51857908.47 | 0.77 | 20.01 | 01-NOV-00:10 | 0.77 |
| December | 53586505.42 | 0.77 | 20.01 | 01-DEC-00:10 | 0.77 |
| Annual Sum or Average | 0.630938E+09 | 0.77 | |||
| Minimum of Months | 48400714.57 | 0.76 | 20.01 | 0.76 | |
| Maximum of Months | 53586505.42 | 0.77 | 20.01 | 0.77 |
Report: FanReportMonthly
For: G S2 APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.77 | 20.01 | 01-JAN-00:10 | 0.77 |
| February | 48400714.57 | 0.77 | 20.01 | 01-FEB-00:10 | 0.77 |
| March | 53586505.42 | 0.77 | 20.01 | 01-MAR-00:10 | 0.77 |
| April | 51857908.47 | 0.77 | 20.01 | 01-APR-00:10 | 0.77 |
| May | 53586505.42 | 0.77 | 20.01 | 01-MAY-00:10 | 0.77 |
| June | 51857908.47 | 0.76 | 20.01 | 01-JUN-00:10 | 0.77 |
| July | 53586505.42 | 0.76 | 20.01 | 01-JUL-00:10 | 0.76 |
| August | 53586505.42 | 0.76 | 20.01 | 01-AUG-00:10 | 0.76 |
| September | 51857908.47 | 0.76 | 20.01 | 01-SEP-00:10 | 0.76 |
| October | 53586505.42 | 0.77 | 20.01 | 01-OCT-00:10 | 0.77 |
| November | 51857908.47 | 0.77 | 20.01 | 01-NOV-00:10 | 0.77 |
| December | 53586505.42 | 0.77 | 20.01 | 01-DEC-00:10 | 0.77 |
| Annual Sum or Average | 0.630938E+09 | 0.77 | |||
| Minimum of Months | 48400714.57 | 0.76 | 20.01 | 0.76 | |
| Maximum of Months | 53586505.42 | 0.77 | 20.01 | 0.77 |
Report: FanReportMonthly
For: SPLIT MSW SUPPLY FAN
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 79242304.72 | 0.51 | 267.95 | 02-JAN-15:20 | 1.27 |
| February | 75446918.95 | 0.46 | 366.89 | 14-FEB-16:10 | 1.25 |
| March | 86743204.16 | 0.39 | 337.30 | 12-MAR-16:03 | 1.26 |
| April | 0.241801E+09 | 0.86 | 427.38 | 13-APR-16:27 | 1.24 |
| May | 0.335771E+09 | 1.06 | 476.58 | 19-MAY-16:30 | 1.23 |
| June | 0.543993E+09 | 1.21 | 627.05 | 28-JUN-16:30 | 1.20 |
| July | 0.709763E+09 | 1.26 | 624.25 | 21-JUL-17:10 | 1.20 |
| August | 0.678575E+09 | 1.26 | 579.89 | 20-AUG-16:02 | 1.21 |
| September | 0.536941E+09 | 1.26 | 562.42 | 20-SEP-16:30 | 1.21 |
| October | 0.343792E+09 | 0.93 | 499.49 | 06-OCT-16:10 | 1.22 |
| November | 0.105913E+09 | 0.48 | 332.87 | 20-NOV-15:30 | 1.26 |
| December | 59132553.82 | 0.46 | 259.63 | 31-DEC-15:30 | 1.27 |
| Annual Sum or Average | 0.379711E+10 | 0.85 | |||
| Minimum of Months | 59132553.82 | 0.39 | 259.63 | 1.20 | |
| Maximum of Months | 0.709763E+09 | 1.26 | 627.05 | 1.27 |
Report: FanReportMonthly
For: M SW APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.107173E+09 | 0.77 | 40.01 | 01-JAN-00:10 | 0.77 |
| February | 96801429.15 | 0.77 | 40.01 | 01-FEB-00:10 | 0.77 |
| March | 0.107173E+09 | 0.77 | 40.01 | 01-MAR-00:10 | 0.77 |
| April | 0.103716E+09 | 0.77 | 40.01 | 01-APR-00:10 | 0.77 |
| May | 0.107173E+09 | 0.77 | 40.01 | 01-MAY-00:10 | 0.77 |
| June | 0.103716E+09 | 0.77 | 40.01 | 01-JUN-00:10 | 0.77 |
| July | 0.107173E+09 | 0.76 | 40.01 | 01-JUL-00:10 | 0.76 |
| August | 0.107173E+09 | 0.76 | 40.01 | 01-AUG-00:10 | 0.76 |
| September | 0.103716E+09 | 0.76 | 40.01 | 01-SEP-00:10 | 0.76 |
| October | 0.107173E+09 | 0.77 | 40.01 | 01-OCT-00:10 | 0.76 |
| November | 0.103716E+09 | 0.77 | 40.01 | 01-NOV-00:10 | 0.77 |
| December | 0.107173E+09 | 0.77 | 40.01 | 01-DEC-00:10 | 0.77 |
| Annual Sum or Average | 0.126188E+10 | 0.77 | |||
| Minimum of Months | 96801429.15 | 0.76 | 40.01 | 0.76 | |
| Maximum of Months | 0.107173E+09 | 0.77 | 40.01 | 0.77 |
Report: FanReportMonthly
For: M SW APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.107173E+09 | 0.77 | 40.01 | 01-JAN-00:10 | 0.77 |
| February | 96801429.15 | 0.77 | 40.01 | 01-FEB-00:10 | 0.77 |
| March | 0.107173E+09 | 0.77 | 40.01 | 01-MAR-00:10 | 0.77 |
| April | 0.103716E+09 | 0.77 | 40.01 | 01-APR-00:10 | 0.77 |
| May | 0.107173E+09 | 0.77 | 40.01 | 01-MAY-00:10 | 0.77 |
| June | 0.103716E+09 | 0.76 | 40.01 | 01-JUN-00:10 | 0.77 |
| July | 0.107173E+09 | 0.76 | 40.01 | 01-JUL-00:10 | 0.76 |
| August | 0.107173E+09 | 0.76 | 40.01 | 01-AUG-00:10 | 0.76 |
| September | 0.103716E+09 | 0.76 | 40.01 | 01-SEP-00:10 | 0.76 |
| October | 0.107173E+09 | 0.77 | 40.01 | 01-OCT-00:10 | 0.77 |
| November | 0.103716E+09 | 0.77 | 40.01 | 01-NOV-00:10 | 0.77 |
| December | 0.107173E+09 | 0.77 | 40.01 | 01-DEC-00:10 | 0.77 |
| Annual Sum or Average | 0.126188E+10 | 0.77 | |||
| Minimum of Months | 96801429.15 | 0.76 | 40.01 | 0.76 | |
| Maximum of Months | 0.107173E+09 | 0.77 | 40.01 | 0.77 |
Report: FanReportMonthly
For: SPLIT MNW SUPPLY FAN
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.149894E+09 | 0.92 | 158.13 | 17-JAN-04:00 | 1.12 |
| February | 98499022.57 | 0.74 | 166.46 | 06-FEB-05:00 | 1.12 |
| March | 20201678.82 | 0.25 | 108.17 | 04-MAR-06:00 | 1.12 |
| April | 0.133456E+09 | 0.65 | 357.42 | 13-APR-16:27 | 1.25 |
| May | 0.294419E+09 | 1.04 | 450.96 | 19-MAY-17:00 | 1.23 |
| June | 0.547531E+09 | 1.21 | 621.03 | 28-JUN-16:30 | 1.20 |
| July | 0.682128E+09 | 1.26 | 604.86 | 21-JUL-17:10 | 1.20 |
| August | 0.595151E+09 | 1.26 | 522.14 | 20-AUG-17:30 | 1.22 |
| September | 0.368529E+09 | 1.24 | 422.84 | 02-SEP-16:40 | 1.23 |
| October | 0.132972E+09 | 0.65 | 345.17 | 06-OCT-16:17 | 1.25 |
| November | 43109424.82 | 0.47 | 120.10 | 26-NOV-06:00 | 1.12 |
| December | 0.160228E+09 | 0.99 | 171.07 | 14-DEC-04:00 | 1.12 |
| Annual Sum or Average | 0.322612E+10 | 0.89 | |||
| Minimum of Months | 20201678.82 | 0.25 | 108.17 | 1.12 | |
| Maximum of Months | 0.682128E+09 | 1.26 | 621.03 | 1.25 |
Report: FanReportMonthly
For: M NW APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.107173E+09 | 0.77 | 40.01 | 01-JAN-00:10 | 0.77 |
| February | 96801429.15 | 0.77 | 40.01 | 01-FEB-00:10 | 0.77 |
| March | 0.107173E+09 | 0.77 | 40.01 | 01-MAR-00:10 | 0.77 |
| April | 0.103716E+09 | 0.77 | 40.01 | 01-APR-00:10 | 0.77 |
| May | 0.107173E+09 | 0.77 | 40.01 | 01-MAY-00:10 | 0.77 |
| June | 0.103716E+09 | 0.77 | 40.01 | 01-JUN-00:10 | 0.77 |
| July | 0.107173E+09 | 0.76 | 40.01 | 01-JUL-00:10 | 0.76 |
| August | 0.107173E+09 | 0.76 | 40.01 | 01-AUG-00:10 | 0.76 |
| September | 0.103716E+09 | 0.76 | 40.01 | 01-SEP-00:10 | 0.76 |
| October | 0.107173E+09 | 0.77 | 40.01 | 01-OCT-00:10 | 0.76 |
| November | 0.103716E+09 | 0.77 | 40.01 | 01-NOV-00:10 | 0.77 |
| December | 0.107173E+09 | 0.77 | 40.01 | 01-DEC-00:10 | 0.77 |
| Annual Sum or Average | 0.126188E+10 | 0.77 | |||
| Minimum of Months | 96801429.15 | 0.76 | 40.01 | 0.76 | |
| Maximum of Months | 0.107173E+09 | 0.77 | 40.01 | 0.77 |
Report: FanReportMonthly
For: M NW APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.107173E+09 | 0.77 | 40.01 | 01-JAN-00:10 | 0.77 |
| February | 96801429.15 | 0.77 | 40.01 | 01-FEB-00:10 | 0.77 |
| March | 0.107173E+09 | 0.77 | 40.01 | 01-MAR-00:10 | 0.77 |
| April | 0.103716E+09 | 0.77 | 40.01 | 01-APR-00:10 | 0.77 |
| May | 0.107173E+09 | 0.77 | 40.01 | 01-MAY-00:10 | 0.77 |
| June | 0.103716E+09 | 0.76 | 40.01 | 01-JUN-00:10 | 0.77 |
| July | 0.107173E+09 | 0.76 | 40.01 | 01-JUL-00:10 | 0.76 |
| August | 0.107173E+09 | 0.76 | 40.01 | 01-AUG-00:10 | 0.76 |
| September | 0.103716E+09 | 0.76 | 40.01 | 01-SEP-00:10 | 0.76 |
| October | 0.107173E+09 | 0.77 | 40.01 | 01-OCT-00:10 | 0.77 |
| November | 0.103716E+09 | 0.77 | 40.01 | 01-NOV-00:10 | 0.77 |
| December | 0.107173E+09 | 0.77 | 40.01 | 01-DEC-00:10 | 0.77 |
| Annual Sum or Average | 0.126188E+10 | 0.77 | |||
| Minimum of Months | 96801429.15 | 0.76 | 40.01 | 0.76 | |
| Maximum of Months | 0.107173E+09 | 0.77 | 40.01 | 0.77 |
Report: FanReportMonthly
For: SPLIT MSE SUPPLY FAN
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 77904665.70 | 0.51 | 232.61 | 02-JAN-14:00 | 1.27 |
| February | 72713234.77 | 0.47 | 309.76 | 14-FEB-14:50 | 1.26 |
| March | 91564650.81 | 0.43 | 306.60 | 08-MAR-14:00 | 1.25 |
| April | 0.266223E+09 | 0.95 | 354.86 | 28-APR-13:00 | 1.25 |
| May | 0.359558E+09 | 1.11 | 379.62 | 19-MAY-15:10 | 1.24 |
| June | 0.567561E+09 | 1.22 | 510.95 | 29-JUN-15:10 | 1.21 |
| July | 0.739248E+09 | 1.25 | 526.32 | 22-JUL-14:00 | 1.20 |
| August | 0.700600E+09 | 1.25 | 486.77 | 20-AUG-15:20 | 1.21 |
| September | 0.544867E+09 | 1.25 | 505.96 | 03-SEP-13:30 | 1.21 |
| October | 0.347079E+09 | 0.93 | 439.67 | 01-OCT-13:50 | 1.22 |
| November | 0.104984E+09 | 0.50 | 290.13 | 01-NOV-12:50 | 1.25 |
| December | 53796384.77 | 0.45 | 210.30 | 31-DEC-14:30 | 1.28 |
| Annual Sum or Average | 0.392610E+10 | 0.86 | |||
| Minimum of Months | 53796384.77 | 0.43 | 210.30 | 1.20 | |
| Maximum of Months | 0.739248E+09 | 1.25 | 526.32 | 1.28 |
Report: FanReportMonthly
For: M SE APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.107173E+09 | 0.77 | 40.01 | 01-JAN-00:10 | 0.77 |
| February | 96801429.15 | 0.77 | 40.01 | 01-FEB-00:10 | 0.77 |
| March | 0.107173E+09 | 0.77 | 40.01 | 01-MAR-00:10 | 0.77 |
| April | 0.103716E+09 | 0.77 | 40.01 | 01-APR-00:10 | 0.77 |
| May | 0.107173E+09 | 0.77 | 40.01 | 01-MAY-00:10 | 0.77 |
| June | 0.103716E+09 | 0.77 | 40.01 | 01-JUN-00:10 | 0.77 |
| July | 0.107173E+09 | 0.76 | 40.01 | 01-JUL-00:10 | 0.76 |
| August | 0.107173E+09 | 0.76 | 40.01 | 01-AUG-00:10 | 0.76 |
| September | 0.103716E+09 | 0.76 | 40.01 | 01-SEP-00:10 | 0.76 |
| October | 0.107173E+09 | 0.77 | 40.01 | 01-OCT-00:10 | 0.76 |
| November | 0.103716E+09 | 0.77 | 40.01 | 01-NOV-00:10 | 0.77 |
| December | 0.107173E+09 | 0.77 | 40.01 | 01-DEC-00:10 | 0.77 |
| Annual Sum or Average | 0.126188E+10 | 0.77 | |||
| Minimum of Months | 96801429.15 | 0.76 | 40.01 | 0.76 | |
| Maximum of Months | 0.107173E+09 | 0.77 | 40.01 | 0.77 |
Report: FanReportMonthly
For: M SE APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.107173E+09 | 0.77 | 40.01 | 01-JAN-00:10 | 0.77 |
| February | 96801429.15 | 0.77 | 40.01 | 01-FEB-00:10 | 0.77 |
| March | 0.107173E+09 | 0.77 | 40.01 | 01-MAR-00:10 | 0.77 |
| April | 0.103716E+09 | 0.77 | 40.01 | 01-APR-00:10 | 0.77 |
| May | 0.107173E+09 | 0.77 | 40.01 | 01-MAY-00:10 | 0.77 |
| June | 0.103716E+09 | 0.76 | 40.01 | 01-JUN-00:10 | 0.77 |
| July | 0.107173E+09 | 0.76 | 40.01 | 01-JUL-00:10 | 0.76 |
| August | 0.107173E+09 | 0.76 | 40.01 | 01-AUG-00:10 | 0.76 |
| September | 0.103716E+09 | 0.76 | 40.01 | 01-SEP-00:10 | 0.76 |
| October | 0.107173E+09 | 0.77 | 40.01 | 01-OCT-00:10 | 0.77 |
| November | 0.103716E+09 | 0.77 | 40.01 | 01-NOV-00:10 | 0.77 |
| December | 0.107173E+09 | 0.77 | 40.01 | 01-DEC-00:10 | 0.77 |
| Annual Sum or Average | 0.126188E+10 | 0.77 | |||
| Minimum of Months | 96801429.15 | 0.76 | 40.01 | 0.76 | |
| Maximum of Months | 0.107173E+09 | 0.77 | 40.01 | 0.77 |
Report: FanReportMonthly
For: SPLIT MNE SUPPLY FAN
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.146923E+09 | 0.92 | 159.20 | 17-JAN-04:00 | 1.12 |
| February | 98766011.31 | 0.75 | 166.15 | 06-FEB-05:00 | 1.12 |
| March | 16654316.01 | 0.20 | 107.25 | 04-MAR-06:00 | 1.12 |
| April | 0.150865E+09 | 0.74 | 276.37 | 29-APR-16:10 | 1.26 |
| May | 0.317400E+09 | 1.07 | 350.86 | 19-MAY-17:05 | 1.24 |
| June | 0.571218E+09 | 1.22 | 499.52 | 28-JUN-16:10 | 1.22 |
| July | 0.711945E+09 | 1.25 | 482.08 | 04-JUL-17:00 | 1.22 |
| August | 0.618311E+09 | 1.26 | 412.85 | 20-AUG-17:10 | 1.23 |
| September | 0.377980E+09 | 1.24 | 347.24 | 03-SEP-14:10 | 1.24 |
| October | 0.131257E+09 | 0.70 | 272.51 | 01-OCT-16:10 | 1.26 |
| November | 39744381.76 | 0.43 | 120.34 | 26-NOV-06:00 | 1.12 |
| December | 0.158735E+09 | 1.05 | 172.38 | 14-DEC-04:00 | 1.12 |
| Annual Sum or Average | 0.333980E+10 | 0.90 | |||
| Minimum of Months | 16654316.01 | 0.20 | 107.25 | 1.12 | |
| Maximum of Months | 0.711945E+09 | 1.26 | 499.52 | 1.26 |
Report: FanReportMonthly
For: M NE APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.107173E+09 | 0.77 | 40.01 | 01-JAN-00:10 | 0.77 |
| February | 96801429.15 | 0.77 | 40.01 | 01-FEB-00:10 | 0.77 |
| March | 0.107173E+09 | 0.77 | 40.01 | 01-MAR-00:10 | 0.77 |
| April | 0.103716E+09 | 0.77 | 40.01 | 01-APR-00:10 | 0.77 |
| May | 0.107173E+09 | 0.77 | 40.01 | 01-MAY-00:10 | 0.77 |
| June | 0.103716E+09 | 0.77 | 40.01 | 01-JUN-00:10 | 0.77 |
| July | 0.107173E+09 | 0.76 | 40.01 | 01-JUL-00:10 | 0.76 |
| August | 0.107173E+09 | 0.76 | 40.01 | 01-AUG-00:10 | 0.76 |
| September | 0.103716E+09 | 0.76 | 40.01 | 01-SEP-00:10 | 0.76 |
| October | 0.107173E+09 | 0.77 | 40.01 | 01-OCT-00:10 | 0.76 |
| November | 0.103716E+09 | 0.77 | 40.01 | 01-NOV-00:10 | 0.77 |
| December | 0.107173E+09 | 0.77 | 40.01 | 01-DEC-00:10 | 0.77 |
| Annual Sum or Average | 0.126188E+10 | 0.77 | |||
| Minimum of Months | 96801429.15 | 0.76 | 40.01 | 0.76 | |
| Maximum of Months | 0.107173E+09 | 0.77 | 40.01 | 0.77 |
Report: FanReportMonthly
For: M NE APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.107173E+09 | 0.77 | 40.01 | 01-JAN-00:10 | 0.77 |
| February | 96801429.15 | 0.77 | 40.01 | 01-FEB-00:10 | 0.77 |
| March | 0.107173E+09 | 0.77 | 40.01 | 01-MAR-00:10 | 0.77 |
| April | 0.103716E+09 | 0.77 | 40.01 | 01-APR-00:10 | 0.77 |
| May | 0.107173E+09 | 0.77 | 40.01 | 01-MAY-00:10 | 0.77 |
| June | 0.103716E+09 | 0.76 | 40.01 | 01-JUN-00:10 | 0.77 |
| July | 0.107173E+09 | 0.76 | 40.01 | 01-JUL-00:10 | 0.76 |
| August | 0.107173E+09 | 0.76 | 40.01 | 01-AUG-00:10 | 0.76 |
| September | 0.103716E+09 | 0.76 | 40.01 | 01-SEP-00:10 | 0.76 |
| October | 0.107173E+09 | 0.77 | 40.01 | 01-OCT-00:10 | 0.77 |
| November | 0.103716E+09 | 0.77 | 40.01 | 01-NOV-00:10 | 0.77 |
| December | 0.107173E+09 | 0.77 | 40.01 | 01-DEC-00:10 | 0.77 |
| Annual Sum or Average | 0.126188E+10 | 0.77 | |||
| Minimum of Months | 96801429.15 | 0.76 | 40.01 | 0.76 | |
| Maximum of Months | 0.107173E+09 | 0.77 | 40.01 | 0.77 |
Report: FanReportMonthly
For: SPLIT MN1 SUPPLY FAN
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 84376243.50 | 0.82 | 99.61 | 17-JAN-04:00 | 1.12 |
| February | 53487408.50 | 0.62 | 104.78 | 06-FEB-05:00 | 1.12 |
| March | 5710580.68 | 0.09 | 63.27 | 05-MAR-05:00 | 1.12 |
| April | 98415379.59 | 0.69 | 207.42 | 29-APR-16:10 | 1.27 |
| May | 0.236113E+09 | 1.10 | 279.71 | 19-MAY-18:00 | 1.25 |
| June | 0.429939E+09 | 1.25 | 391.50 | 28-JUN-16:40 | 1.23 |
| July | 0.545995E+09 | 1.26 | 376.86 | 04-JUL-17:04 | 1.23 |
| August | 0.472870E+09 | 1.26 | 324.55 | 20-AUG-17:30 | 1.24 |
| September | 0.298979E+09 | 1.27 | 254.74 | 03-SEP-14:10 | 1.25 |
| October | 0.100737E+09 | 0.65 | 218.51 | 01-OCT-16:10 | 1.26 |
| November | 14500373.66 | 0.28 | 70.15 | 28-NOV-05:00 | 1.12 |
| December | 92864108.89 | 0.97 | 106.81 | 14-DEC-04:00 | 1.12 |
| Annual Sum or Average | 0.243399E+10 | 0.86 | |||
| Minimum of Months | 5710580.68 | 0.09 | 63.27 | 1.12 | |
| Maximum of Months | 0.545995E+09 | 1.27 | 391.50 | 1.27 |
Report: FanReportMonthly
For: M N1 APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.107173E+09 | 0.77 | 40.01 | 01-JAN-00:10 | 0.77 |
| February | 96801429.15 | 0.77 | 40.01 | 01-FEB-00:10 | 0.77 |
| March | 0.107173E+09 | 0.77 | 40.01 | 01-MAR-00:10 | 0.77 |
| April | 0.103716E+09 | 0.77 | 40.01 | 01-APR-00:10 | 0.77 |
| May | 0.107173E+09 | 0.77 | 40.01 | 01-MAY-00:10 | 0.77 |
| June | 0.103716E+09 | 0.77 | 40.01 | 01-JUN-00:10 | 0.77 |
| July | 0.107173E+09 | 0.76 | 40.01 | 01-JUL-00:10 | 0.76 |
| August | 0.107173E+09 | 0.76 | 40.01 | 01-AUG-00:10 | 0.76 |
| September | 0.103716E+09 | 0.76 | 40.01 | 01-SEP-00:10 | 0.76 |
| October | 0.107173E+09 | 0.77 | 40.01 | 01-OCT-00:10 | 0.76 |
| November | 0.103716E+09 | 0.77 | 40.01 | 01-NOV-00:10 | 0.77 |
| December | 0.107173E+09 | 0.77 | 40.01 | 01-DEC-00:10 | 0.77 |
| Annual Sum or Average | 0.126188E+10 | 0.77 | |||
| Minimum of Months | 96801429.15 | 0.76 | 40.01 | 0.76 | |
| Maximum of Months | 0.107173E+09 | 0.77 | 40.01 | 0.77 |
Report: FanReportMonthly
For: M N1 APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.107173E+09 | 0.77 | 40.01 | 01-JAN-00:10 | 0.77 |
| February | 96801429.15 | 0.77 | 40.01 | 01-FEB-00:10 | 0.77 |
| March | 0.107173E+09 | 0.77 | 40.01 | 01-MAR-00:10 | 0.77 |
| April | 0.103716E+09 | 0.77 | 40.01 | 01-APR-00:10 | 0.77 |
| May | 0.107173E+09 | 0.77 | 40.01 | 01-MAY-00:10 | 0.77 |
| June | 0.103716E+09 | 0.76 | 40.01 | 01-JUN-00:10 | 0.77 |
| July | 0.107173E+09 | 0.76 | 40.01 | 01-JUL-00:10 | 0.76 |
| August | 0.107173E+09 | 0.76 | 40.01 | 01-AUG-00:10 | 0.76 |
| September | 0.103716E+09 | 0.76 | 40.01 | 01-SEP-00:10 | 0.76 |
| October | 0.107173E+09 | 0.77 | 40.01 | 01-OCT-00:10 | 0.77 |
| November | 0.103716E+09 | 0.77 | 40.01 | 01-NOV-00:10 | 0.77 |
| December | 0.107173E+09 | 0.77 | 40.01 | 01-DEC-00:10 | 0.77 |
| Annual Sum or Average | 0.126188E+10 | 0.77 | |||
| Minimum of Months | 96801429.15 | 0.76 | 40.01 | 0.76 | |
| Maximum of Months | 0.107173E+09 | 0.77 | 40.01 | 0.77 |
Report: FanReportMonthly
For: SPLIT MN2 SUPPLY FAN
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 84591867.98 | 0.82 | 99.71 | 17-JAN-04:00 | 1.12 |
| February | 53794989.71 | 0.63 | 104.79 | 06-FEB-05:00 | 1.12 |
| March | 5682517.68 | 0.09 | 63.54 | 05-MAR-05:00 | 1.12 |
| April | 0.100215E+09 | 0.70 | 208.59 | 29-APR-16:10 | 1.27 |
| May | 0.237580E+09 | 1.11 | 278.48 | 19-MAY-18:00 | 1.25 |
| June | 0.431014E+09 | 1.25 | 390.43 | 28-JUN-16:30 | 1.23 |
| July | 0.547251E+09 | 1.26 | 375.49 | 04-JUL-17:08 | 1.23 |
| August | 0.473823E+09 | 1.26 | 322.94 | 20-AUG-17:30 | 1.24 |
| September | 0.299427E+09 | 1.27 | 255.48 | 03-SEP-14:10 | 1.25 |
| October | 0.101189E+09 | 0.66 | 218.00 | 01-OCT-16:10 | 1.26 |
| November | 14558658.52 | 0.28 | 70.16 | 28-NOV-05:00 | 1.12 |
| December | 93034922.41 | 0.97 | 106.85 | 14-DEC-04:00 | 1.12 |
| Annual Sum or Average | 0.244216E+10 | 0.86 | |||
| Minimum of Months | 5682517.68 | 0.09 | 63.54 | 1.12 | |
| Maximum of Months | 0.547251E+09 | 1.27 | 390.43 | 1.27 |
Report: FanReportMonthly
For: M N2 APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.107173E+09 | 0.77 | 40.01 | 01-JAN-00:10 | 0.77 |
| February | 96801429.15 | 0.77 | 40.01 | 01-FEB-00:10 | 0.77 |
| March | 0.107173E+09 | 0.77 | 40.01 | 01-MAR-00:10 | 0.77 |
| April | 0.103716E+09 | 0.77 | 40.01 | 01-APR-00:10 | 0.77 |
| May | 0.107173E+09 | 0.77 | 40.01 | 01-MAY-00:10 | 0.77 |
| June | 0.103716E+09 | 0.77 | 40.01 | 01-JUN-00:10 | 0.77 |
| July | 0.107173E+09 | 0.76 | 40.01 | 01-JUL-00:10 | 0.76 |
| August | 0.107173E+09 | 0.76 | 40.01 | 01-AUG-00:10 | 0.76 |
| September | 0.103716E+09 | 0.76 | 40.01 | 01-SEP-00:10 | 0.76 |
| October | 0.107173E+09 | 0.77 | 40.01 | 01-OCT-00:10 | 0.76 |
| November | 0.103716E+09 | 0.77 | 40.01 | 01-NOV-00:10 | 0.77 |
| December | 0.107173E+09 | 0.77 | 40.01 | 01-DEC-00:10 | 0.77 |
| Annual Sum or Average | 0.126188E+10 | 0.77 | |||
| Minimum of Months | 96801429.15 | 0.76 | 40.01 | 0.76 | |
| Maximum of Months | 0.107173E+09 | 0.77 | 40.01 | 0.77 |
Report: FanReportMonthly
For: M N2 APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.107173E+09 | 0.77 | 40.01 | 01-JAN-00:10 | 0.77 |
| February | 96801429.15 | 0.77 | 40.01 | 01-FEB-00:10 | 0.77 |
| March | 0.107173E+09 | 0.77 | 40.01 | 01-MAR-00:10 | 0.77 |
| April | 0.103716E+09 | 0.77 | 40.01 | 01-APR-00:10 | 0.77 |
| May | 0.107173E+09 | 0.77 | 40.01 | 01-MAY-00:10 | 0.77 |
| June | 0.103716E+09 | 0.76 | 40.01 | 01-JUN-00:10 | 0.77 |
| July | 0.107173E+09 | 0.76 | 40.01 | 01-JUL-00:10 | 0.76 |
| August | 0.107173E+09 | 0.76 | 40.01 | 01-AUG-00:10 | 0.76 |
| September | 0.103716E+09 | 0.76 | 40.01 | 01-SEP-00:10 | 0.76 |
| October | 0.107173E+09 | 0.77 | 40.01 | 01-OCT-00:10 | 0.77 |
| November | 0.103716E+09 | 0.77 | 40.01 | 01-NOV-00:10 | 0.77 |
| December | 0.107173E+09 | 0.77 | 40.01 | 01-DEC-00:10 | 0.77 |
| Annual Sum or Average | 0.126188E+10 | 0.77 | |||
| Minimum of Months | 96801429.15 | 0.76 | 40.01 | 0.76 | |
| Maximum of Months | 0.107173E+09 | 0.77 | 40.01 | 0.77 |
Report: FanReportMonthly
For: SPLIT MS1 SUPPLY FAN
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 70827515.13 | 0.42 | 268.30 | 01-JAN-13:50 | 1.26 |
| February | 65421832.62 | 0.39 | 303.17 | 14-FEB-15:00 | 1.25 |
| March | 91158216.26 | 0.50 | 277.01 | 08-MAR-14:00 | 1.25 |
| April | 0.213414E+09 | 1.01 | 277.90 | 26-APR-14:10 | 1.26 |
| May | 0.278565E+09 | 1.15 | 297.03 | 19-MAY-16:20 | 1.25 |
| June | 0.426296E+09 | 1.25 | 400.95 | 28-JUN-16:10 | 1.23 |
| July | 0.573912E+09 | 1.26 | 407.57 | 22-JUL-15:10 | 1.22 |
| August | 0.556988E+09 | 1.26 | 394.23 | 20-AUG-16:05 | 1.22 |
| September | 0.468689E+09 | 1.26 | 415.75 | 21-SEP-14:10 | 1.22 |
| October | 0.329829E+09 | 1.03 | 375.70 | 01-OCT-14:00 | 1.22 |
| November | 0.142550E+09 | 0.64 | 302.24 | 20-NOV-14:00 | 1.25 |
| December | 53316663.04 | 0.35 | 253.68 | 31-DEC-14:40 | 1.26 |
| Annual Sum or Average | 0.327097E+10 | 0.88 | |||
| Minimum of Months | 53316663.04 | 0.35 | 253.68 | 1.22 | |
| Maximum of Months | 0.573912E+09 | 1.26 | 415.75 | 1.26 |
Report: FanReportMonthly
For: M S1 APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.107173E+09 | 0.77 | 40.01 | 01-JAN-00:10 | 0.77 |
| February | 96801429.15 | 0.77 | 40.01 | 01-FEB-00:10 | 0.77 |
| March | 0.107173E+09 | 0.77 | 40.01 | 01-MAR-00:10 | 0.77 |
| April | 0.103716E+09 | 0.77 | 40.01 | 01-APR-00:10 | 0.77 |
| May | 0.107173E+09 | 0.77 | 40.01 | 01-MAY-00:10 | 0.77 |
| June | 0.103716E+09 | 0.77 | 40.01 | 01-JUN-00:10 | 0.77 |
| July | 0.107173E+09 | 0.76 | 40.01 | 01-JUL-00:10 | 0.76 |
| August | 0.107173E+09 | 0.76 | 40.01 | 01-AUG-00:10 | 0.76 |
| September | 0.103716E+09 | 0.76 | 40.01 | 01-SEP-00:10 | 0.76 |
| October | 0.107173E+09 | 0.77 | 40.01 | 01-OCT-00:10 | 0.76 |
| November | 0.103716E+09 | 0.77 | 40.01 | 01-NOV-00:10 | 0.77 |
| December | 0.107173E+09 | 0.77 | 40.01 | 01-DEC-00:10 | 0.77 |
| Annual Sum or Average | 0.126188E+10 | 0.77 | |||
| Minimum of Months | 96801429.15 | 0.76 | 40.01 | 0.76 | |
| Maximum of Months | 0.107173E+09 | 0.77 | 40.01 | 0.77 |
Report: FanReportMonthly
For: M S1 APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.107173E+09 | 0.77 | 40.01 | 01-JAN-00:10 | 0.77 |
| February | 96801429.15 | 0.77 | 40.01 | 01-FEB-00:10 | 0.77 |
| March | 0.107173E+09 | 0.77 | 40.01 | 01-MAR-00:10 | 0.77 |
| April | 0.103716E+09 | 0.77 | 40.01 | 01-APR-00:10 | 0.77 |
| May | 0.107173E+09 | 0.77 | 40.01 | 01-MAY-00:10 | 0.77 |
| June | 0.103716E+09 | 0.76 | 40.01 | 01-JUN-00:10 | 0.77 |
| July | 0.107173E+09 | 0.76 | 40.01 | 01-JUL-00:10 | 0.76 |
| August | 0.107173E+09 | 0.76 | 40.01 | 01-AUG-00:10 | 0.76 |
| September | 0.103716E+09 | 0.76 | 40.01 | 01-SEP-00:10 | 0.76 |
| October | 0.107173E+09 | 0.77 | 40.01 | 01-OCT-00:10 | 0.77 |
| November | 0.103716E+09 | 0.77 | 40.01 | 01-NOV-00:10 | 0.77 |
| December | 0.107173E+09 | 0.77 | 40.01 | 01-DEC-00:10 | 0.77 |
| Annual Sum or Average | 0.126188E+10 | 0.77 | |||
| Minimum of Months | 96801429.15 | 0.76 | 40.01 | 0.76 | |
| Maximum of Months | 0.107173E+09 | 0.77 | 40.01 | 0.77 |
Report: FanReportMonthly
For: SPLIT MS2 SUPPLY FAN
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 71535625.96 | 0.42 | 269.48 | 01-JAN-13:50 | 1.26 |
| February | 65637568.93 | 0.39 | 303.64 | 14-FEB-15:00 | 1.25 |
| March | 92663829.95 | 0.51 | 278.55 | 08-MAR-14:00 | 1.25 |
| April | 0.215156E+09 | 1.01 | 279.18 | 26-APR-14:10 | 1.25 |
| May | 0.280119E+09 | 1.16 | 296.31 | 19-MAY-16:20 | 1.25 |
| June | 0.427400E+09 | 1.25 | 400.08 | 28-JUN-16:10 | 1.23 |
| July | 0.575155E+09 | 1.26 | 407.48 | 22-JUL-15:10 | 1.22 |
| August | 0.557880E+09 | 1.26 | 393.48 | 20-AUG-16:05 | 1.22 |
| September | 0.469054E+09 | 1.26 | 416.17 | 21-SEP-14:10 | 1.22 |
| October | 0.330283E+09 | 1.03 | 376.50 | 01-OCT-14:00 | 1.22 |
| November | 0.143185E+09 | 0.64 | 302.85 | 20-NOV-14:00 | 1.25 |
| December | 53755378.98 | 0.35 | 254.61 | 31-DEC-14:30 | 1.26 |
| Annual Sum or Average | 0.328182E+10 | 0.88 | |||
| Minimum of Months | 53755378.98 | 0.35 | 254.61 | 1.22 | |
| Maximum of Months | 0.575155E+09 | 1.26 | 416.17 | 1.26 |
Report: FanReportMonthly
For: M S2 APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.107173E+09 | 0.77 | 40.01 | 01-JAN-00:10 | 0.77 |
| February | 96801429.15 | 0.77 | 40.01 | 01-FEB-00:10 | 0.77 |
| March | 0.107173E+09 | 0.77 | 40.01 | 01-MAR-00:10 | 0.77 |
| April | 0.103716E+09 | 0.77 | 40.01 | 01-APR-00:10 | 0.77 |
| May | 0.107173E+09 | 0.77 | 40.01 | 01-MAY-00:10 | 0.77 |
| June | 0.103716E+09 | 0.77 | 40.01 | 01-JUN-00:10 | 0.77 |
| July | 0.107173E+09 | 0.76 | 40.01 | 01-JUL-00:10 | 0.76 |
| August | 0.107173E+09 | 0.76 | 40.01 | 01-AUG-00:10 | 0.76 |
| September | 0.103716E+09 | 0.76 | 40.01 | 01-SEP-00:10 | 0.76 |
| October | 0.107173E+09 | 0.77 | 40.01 | 01-OCT-00:10 | 0.76 |
| November | 0.103716E+09 | 0.77 | 40.01 | 01-NOV-00:10 | 0.77 |
| December | 0.107173E+09 | 0.77 | 40.01 | 01-DEC-00:10 | 0.77 |
| Annual Sum or Average | 0.126188E+10 | 0.77 | |||
| Minimum of Months | 96801429.15 | 0.76 | 40.01 | 0.76 | |
| Maximum of Months | 0.107173E+09 | 0.77 | 40.01 | 0.77 |
Report: FanReportMonthly
For: M S2 APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.107173E+09 | 0.77 | 40.01 | 01-JAN-00:10 | 0.77 |
| February | 96801429.15 | 0.77 | 40.01 | 01-FEB-00:10 | 0.77 |
| March | 0.107173E+09 | 0.77 | 40.01 | 01-MAR-00:10 | 0.77 |
| April | 0.103716E+09 | 0.77 | 40.01 | 01-APR-00:10 | 0.77 |
| May | 0.107173E+09 | 0.77 | 40.01 | 01-MAY-00:10 | 0.77 |
| June | 0.103716E+09 | 0.76 | 40.01 | 01-JUN-00:10 | 0.77 |
| July | 0.107173E+09 | 0.76 | 40.01 | 01-JUL-00:10 | 0.76 |
| August | 0.107173E+09 | 0.76 | 40.01 | 01-AUG-00:10 | 0.76 |
| September | 0.103716E+09 | 0.76 | 40.01 | 01-SEP-00:10 | 0.76 |
| October | 0.107173E+09 | 0.77 | 40.01 | 01-OCT-00:10 | 0.77 |
| November | 0.103716E+09 | 0.77 | 40.01 | 01-NOV-00:10 | 0.77 |
| December | 0.107173E+09 | 0.77 | 40.01 | 01-DEC-00:10 | 0.77 |
| Annual Sum or Average | 0.126188E+10 | 0.77 | |||
| Minimum of Months | 96801429.15 | 0.76 | 40.01 | 0.76 | |
| Maximum of Months | 0.107173E+09 | 0.77 | 40.01 | 0.77 |
Report: FanReportMonthly
For: SPLIT TSW SUPPLY FAN
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.139589E+09 | 0.89 | 184.27 | 23-JAN-15:30 | 1.26 |
| February | 0.117108E+09 | 0.85 | 239.52 | 14-FEB-15:30 | 1.24 |
| March | 98542139.74 | 0.77 | 220.55 | 12-MAR-16:03 | 1.25 |
| April | 0.126809E+09 | 0.73 | 278.27 | 13-APR-16:14 | 1.23 |
| May | 0.174723E+09 | 0.76 | 320.64 | 19-MAY-16:30 | 1.21 |
| June | 0.302367E+09 | 1.02 | 427.66 | 28-JUN-16:30 | 1.18 |
| July | 0.399734E+09 | 1.23 | 415.11 | 21-JUL-17:00 | 1.18 |
| August | 0.372122E+09 | 1.18 | 396.60 | 20-AUG-16:10 | 1.18 |
| September | 0.268782E+09 | 0.94 | 360.38 | 20-SEP-15:20 | 1.20 |
| October | 0.174289E+09 | 0.81 | 322.38 | 01-OCT-15:30 | 1.21 |
| November | 96790200.17 | 0.78 | 196.41 | 20-NOV-15:20 | 1.26 |
| December | 0.126868E+09 | 0.88 | 181.89 | 31-DEC-15:30 | 1.26 |
| Annual Sum or Average | 0.239772E+10 | 0.91 | |||
| Minimum of Months | 96790200.17 | 0.73 | 181.89 | 1.18 | |
| Maximum of Months | 0.399734E+09 | 1.23 | 427.66 | 1.26 |
Report: FanReportMonthly
For: T SW APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.77 | 20.01 | 01-JAN-00:10 | 0.77 |
| February | 48400714.57 | 0.77 | 20.01 | 01-FEB-00:10 | 0.77 |
| March | 53586505.42 | 0.77 | 20.01 | 01-MAR-00:10 | 0.77 |
| April | 51857908.47 | 0.77 | 20.01 | 01-APR-00:10 | 0.77 |
| May | 53586505.42 | 0.77 | 20.01 | 01-MAY-00:10 | 0.77 |
| June | 51857908.47 | 0.77 | 20.01 | 01-JUN-00:10 | 0.77 |
| July | 53586505.42 | 0.76 | 20.01 | 01-JUL-00:10 | 0.76 |
| August | 53586505.42 | 0.76 | 20.01 | 01-AUG-00:10 | 0.76 |
| September | 51857908.47 | 0.76 | 20.01 | 01-SEP-00:10 | 0.76 |
| October | 53586505.42 | 0.77 | 20.01 | 01-OCT-00:10 | 0.76 |
| November | 51857908.47 | 0.77 | 20.01 | 01-NOV-00:10 | 0.77 |
| December | 53586505.42 | 0.77 | 20.01 | 01-DEC-00:10 | 0.77 |
| Annual Sum or Average | 0.630938E+09 | 0.77 | |||
| Minimum of Months | 48400714.57 | 0.76 | 20.01 | 0.76 | |
| Maximum of Months | 53586505.42 | 0.77 | 20.01 | 0.77 |
Report: FanReportMonthly
For: T SW APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.77 | 20.01 | 01-JAN-00:10 | 0.77 |
| February | 48400714.57 | 0.77 | 20.01 | 01-FEB-00:10 | 0.77 |
| March | 53586505.42 | 0.77 | 20.01 | 01-MAR-00:10 | 0.77 |
| April | 51857908.47 | 0.77 | 20.01 | 01-APR-00:10 | 0.77 |
| May | 53586505.42 | 0.77 | 20.01 | 01-MAY-00:10 | 0.77 |
| June | 51857908.47 | 0.76 | 20.01 | 01-JUN-00:10 | 0.77 |
| July | 53586505.42 | 0.76 | 20.01 | 01-JUL-00:10 | 0.76 |
| August | 53586505.42 | 0.76 | 20.01 | 01-AUG-00:10 | 0.76 |
| September | 51857908.47 | 0.76 | 20.01 | 01-SEP-00:10 | 0.76 |
| October | 53586505.42 | 0.77 | 20.01 | 01-OCT-00:10 | 0.77 |
| November | 51857908.47 | 0.77 | 20.01 | 01-NOV-00:10 | 0.77 |
| December | 53586505.42 | 0.77 | 20.01 | 01-DEC-00:10 | 0.77 |
| Annual Sum or Average | 0.630938E+09 | 0.77 | |||
| Minimum of Months | 48400714.57 | 0.76 | 20.01 | 0.76 | |
| Maximum of Months | 53586505.42 | 0.77 | 20.01 | 0.77 |
Report: FanReportMonthly
For: SPLIT TNW SUPPLY FAN
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.159903E+09 | 0.98 | 140.92 | 17-JAN-04:00 | 1.12 |
| February | 0.117671E+09 | 0.90 | 148.22 | 06-FEB-05:00 | 1.12 |
| March | 69954909.76 | 0.72 | 112.84 | 04-MAR-06:00 | 1.12 |
| April | 82484670.38 | 0.65 | 237.02 | 13-APR-16:27 | 1.24 |
| May | 0.153472E+09 | 0.75 | 305.43 | 19-MAY-16:40 | 1.22 |
| June | 0.303512E+09 | 1.04 | 422.42 | 28-JUN-16:30 | 1.18 |
| July | 0.385446E+09 | 1.23 | 403.55 | 21-JUL-17:10 | 1.19 |
| August | 0.328288E+09 | 1.18 | 350.07 | 20-AUG-16:20 | 1.20 |
| September | 0.184139E+09 | 0.89 | 285.63 | 02-SEP-16:30 | 1.22 |
| October | 84803367.83 | 0.67 | 223.93 | 06-OCT-16:10 | 1.24 |
| November | 84195343.92 | 0.81 | 119.14 | 26-NOV-06:00 | 1.12 |
| December | 0.167512E+09 | 1.05 | 144.19 | 14-DEC-04:00 | 1.12 |
| Annual Sum or Average | 0.212138E+10 | 0.91 | |||
| Minimum of Months | 69954909.76 | 0.65 | 112.84 | 1.12 | |
| Maximum of Months | 0.385446E+09 | 1.23 | 422.42 | 1.24 |
Report: FanReportMonthly
For: T NW APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.77 | 20.01 | 01-JAN-00:10 | 0.77 |
| February | 48400714.57 | 0.77 | 20.01 | 01-FEB-00:10 | 0.77 |
| March | 53586505.42 | 0.77 | 20.01 | 01-MAR-00:10 | 0.77 |
| April | 51857908.47 | 0.77 | 20.01 | 01-APR-00:10 | 0.77 |
| May | 53586505.42 | 0.77 | 20.01 | 01-MAY-00:10 | 0.77 |
| June | 51857908.47 | 0.77 | 20.01 | 01-JUN-00:10 | 0.77 |
| July | 53586505.42 | 0.76 | 20.01 | 01-JUL-00:10 | 0.76 |
| August | 53586505.42 | 0.76 | 20.01 | 01-AUG-00:10 | 0.76 |
| September | 51857908.47 | 0.76 | 20.01 | 01-SEP-00:10 | 0.76 |
| October | 53586505.42 | 0.77 | 20.01 | 01-OCT-00:10 | 0.76 |
| November | 51857908.47 | 0.77 | 20.01 | 01-NOV-00:10 | 0.77 |
| December | 53586505.42 | 0.77 | 20.01 | 01-DEC-00:10 | 0.77 |
| Annual Sum or Average | 0.630938E+09 | 0.77 | |||
| Minimum of Months | 48400714.57 | 0.76 | 20.01 | 0.76 | |
| Maximum of Months | 53586505.42 | 0.77 | 20.01 | 0.77 |
Report: FanReportMonthly
For: T NW APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.77 | 20.01 | 01-JAN-00:10 | 0.77 |
| February | 48400714.57 | 0.77 | 20.01 | 01-FEB-00:10 | 0.77 |
| March | 53586505.42 | 0.77 | 20.01 | 01-MAR-00:10 | 0.77 |
| April | 51857908.47 | 0.77 | 20.01 | 01-APR-00:10 | 0.77 |
| May | 53586505.42 | 0.77 | 20.01 | 01-MAY-00:10 | 0.77 |
| June | 51857908.47 | 0.76 | 20.01 | 01-JUN-00:10 | 0.77 |
| July | 53586505.42 | 0.76 | 20.01 | 01-JUL-00:10 | 0.76 |
| August | 53586505.42 | 0.76 | 20.01 | 01-AUG-00:10 | 0.76 |
| September | 51857908.47 | 0.76 | 20.01 | 01-SEP-00:10 | 0.76 |
| October | 53586505.42 | 0.77 | 20.01 | 01-OCT-00:10 | 0.77 |
| November | 51857908.47 | 0.77 | 20.01 | 01-NOV-00:10 | 0.77 |
| December | 53586505.42 | 0.77 | 20.01 | 01-DEC-00:10 | 0.77 |
| Annual Sum or Average | 0.630938E+09 | 0.77 | |||
| Minimum of Months | 48400714.57 | 0.76 | 20.01 | 0.76 | |
| Maximum of Months | 53586505.42 | 0.77 | 20.01 | 0.77 |
Report: FanReportMonthly
For: SPLIT TSE SUPPLY FAN
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.134930E+09 | 0.90 | 151.50 | 23-JAN-14:20 | 1.26 |
| February | 0.110615E+09 | 0.84 | 200.34 | 14-FEB-14:40 | 1.25 |
| March | 93458329.12 | 0.77 | 202.88 | 08-MAR-14:00 | 1.24 |
| April | 0.130556E+09 | 0.76 | 236.56 | 28-APR-13:00 | 1.23 |
| May | 0.180521E+09 | 0.81 | 257.93 | 19-MAY-13:00 | 1.22 |
| June | 0.312009E+09 | 1.04 | 345.91 | 29-JUN-15:00 | 1.18 |
| July | 0.413929E+09 | 1.23 | 360.27 | 22-JUL-14:00 | 1.17 |
| August | 0.382562E+09 | 1.19 | 328.57 | 20-AUG-15:20 | 1.19 |
| September | 0.271478E+09 | 0.96 | 342.07 | 03-SEP-13:30 | 1.18 |
| October | 0.172512E+09 | 0.82 | 292.33 | 01-OCT-13:50 | 1.20 |
| November | 92210937.88 | 0.79 | 164.28 | 24-NOV-14:00 | 1.26 |
| December | 0.119468E+09 | 0.86 | 144.53 | 31-DEC-14:40 | 1.27 |
| Annual Sum or Average | 0.241425E+10 | 0.91 | |||
| Minimum of Months | 92210937.88 | 0.76 | 144.53 | 1.17 | |
| Maximum of Months | 0.413929E+09 | 1.23 | 360.27 | 1.27 |
Report: FanReportMonthly
For: T SE APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.77 | 20.01 | 01-JAN-00:10 | 0.77 |
| February | 48400714.57 | 0.77 | 20.01 | 01-FEB-00:10 | 0.77 |
| March | 53586505.42 | 0.77 | 20.01 | 01-MAR-00:10 | 0.77 |
| April | 51857908.47 | 0.77 | 20.01 | 01-APR-00:10 | 0.77 |
| May | 53586505.42 | 0.77 | 20.01 | 01-MAY-00:10 | 0.77 |
| June | 51857908.47 | 0.77 | 20.01 | 01-JUN-00:10 | 0.77 |
| July | 53586505.42 | 0.76 | 20.01 | 01-JUL-00:10 | 0.76 |
| August | 53586505.42 | 0.76 | 20.01 | 01-AUG-00:10 | 0.76 |
| September | 51857908.47 | 0.76 | 20.01 | 01-SEP-00:10 | 0.76 |
| October | 53586505.42 | 0.77 | 20.01 | 01-OCT-00:10 | 0.76 |
| November | 51857908.47 | 0.77 | 20.01 | 01-NOV-00:10 | 0.77 |
| December | 53586505.42 | 0.77 | 20.01 | 01-DEC-00:10 | 0.77 |
| Annual Sum or Average | 0.630938E+09 | 0.77 | |||
| Minimum of Months | 48400714.57 | 0.76 | 20.01 | 0.76 | |
| Maximum of Months | 53586505.42 | 0.77 | 20.01 | 0.77 |
Report: FanReportMonthly
For: T SE APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.77 | 20.01 | 01-JAN-00:10 | 0.77 |
| February | 48400714.57 | 0.77 | 20.01 | 01-FEB-00:10 | 0.77 |
| March | 53586505.42 | 0.77 | 20.01 | 01-MAR-00:10 | 0.77 |
| April | 51857908.47 | 0.77 | 20.01 | 01-APR-00:10 | 0.77 |
| May | 53586505.42 | 0.77 | 20.01 | 01-MAY-00:10 | 0.77 |
| June | 51857908.47 | 0.76 | 20.01 | 01-JUN-00:10 | 0.77 |
| July | 53586505.42 | 0.76 | 20.01 | 01-JUL-00:10 | 0.76 |
| August | 53586505.42 | 0.76 | 20.01 | 01-AUG-00:10 | 0.76 |
| September | 51857908.47 | 0.76 | 20.01 | 01-SEP-00:10 | 0.76 |
| October | 53586505.42 | 0.77 | 20.01 | 01-OCT-00:10 | 0.77 |
| November | 51857908.47 | 0.77 | 20.01 | 01-NOV-00:10 | 0.77 |
| December | 53586505.42 | 0.77 | 20.01 | 01-DEC-00:10 | 0.77 |
| Annual Sum or Average | 0.630938E+09 | 0.77 | |||
| Minimum of Months | 48400714.57 | 0.76 | 20.01 | 0.76 | |
| Maximum of Months | 53586505.42 | 0.77 | 20.01 | 0.77 |
Report: FanReportMonthly
For: SPLIT TNE SUPPLY FAN
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.156531E+09 | 1.02 | 140.47 | 17-JAN-04:00 | 1.12 |
| February | 0.114427E+09 | 0.89 | 147.24 | 06-FEB-05:00 | 1.12 |
| March | 60333304.25 | 0.64 | 112.21 | 04-MAR-06:00 | 1.12 |
| April | 82416471.41 | 0.66 | 165.72 | 28-APR-15:10 | 1.26 |
| May | 0.159792E+09 | 0.79 | 226.62 | 19-MAY-16:30 | 1.23 |
| June | 0.313953E+09 | 1.06 | 331.69 | 28-JUN-16:10 | 1.19 |
| July | 0.400104E+09 | 1.23 | 317.79 | 22-JUL-15:10 | 1.19 |
| August | 0.339770E+09 | 1.18 | 276.97 | 20-AUG-16:10 | 1.21 |
| September | 0.187245E+09 | 0.92 | 242.68 | 03-SEP-14:00 | 1.22 |
| October | 77428529.66 | 0.67 | 172.21 | 01-OCT-15:20 | 1.25 |
| November | 80812365.58 | 0.80 | 118.96 | 26-NOV-06:00 | 1.12 |
| December | 0.165321E+09 | 1.10 | 144.30 | 14-DEC-04:00 | 1.12 |
| Annual Sum or Average | 0.213813E+10 | 0.91 | |||
| Minimum of Months | 60333304.25 | 0.64 | 112.21 | 1.12 | |
| Maximum of Months | 0.400104E+09 | 1.23 | 331.69 | 1.26 |
Report: FanReportMonthly
For: T NE APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.77 | 20.01 | 01-JAN-00:10 | 0.77 |
| February | 48400714.57 | 0.77 | 20.01 | 01-FEB-00:10 | 0.77 |
| March | 53586505.42 | 0.77 | 20.01 | 01-MAR-00:10 | 0.77 |
| April | 51857908.47 | 0.77 | 20.01 | 01-APR-00:10 | 0.77 |
| May | 53586505.42 | 0.77 | 20.01 | 01-MAY-00:10 | 0.77 |
| June | 51857908.47 | 0.77 | 20.01 | 01-JUN-00:10 | 0.77 |
| July | 53586505.42 | 0.76 | 20.01 | 01-JUL-00:10 | 0.76 |
| August | 53586505.42 | 0.76 | 20.01 | 01-AUG-00:10 | 0.76 |
| September | 51857908.47 | 0.76 | 20.01 | 01-SEP-00:10 | 0.76 |
| October | 53586505.42 | 0.77 | 20.01 | 01-OCT-00:10 | 0.76 |
| November | 51857908.47 | 0.77 | 20.01 | 01-NOV-00:10 | 0.77 |
| December | 53586505.42 | 0.77 | 20.01 | 01-DEC-00:10 | 0.77 |
| Annual Sum or Average | 0.630938E+09 | 0.77 | |||
| Minimum of Months | 48400714.57 | 0.76 | 20.01 | 0.76 | |
| Maximum of Months | 53586505.42 | 0.77 | 20.01 | 0.77 |
Report: FanReportMonthly
For: T NE APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.77 | 20.01 | 01-JAN-00:10 | 0.77 |
| February | 48400714.57 | 0.77 | 20.01 | 01-FEB-00:10 | 0.77 |
| March | 53586505.42 | 0.77 | 20.01 | 01-MAR-00:10 | 0.77 |
| April | 51857908.47 | 0.77 | 20.01 | 01-APR-00:10 | 0.77 |
| May | 53586505.42 | 0.77 | 20.01 | 01-MAY-00:10 | 0.77 |
| June | 51857908.47 | 0.76 | 20.01 | 01-JUN-00:10 | 0.77 |
| July | 53586505.42 | 0.76 | 20.01 | 01-JUL-00:10 | 0.76 |
| August | 53586505.42 | 0.76 | 20.01 | 01-AUG-00:10 | 0.76 |
| September | 51857908.47 | 0.76 | 20.01 | 01-SEP-00:10 | 0.76 |
| October | 53586505.42 | 0.77 | 20.01 | 01-OCT-00:10 | 0.77 |
| November | 51857908.47 | 0.77 | 20.01 | 01-NOV-00:10 | 0.77 |
| December | 53586505.42 | 0.77 | 20.01 | 01-DEC-00:10 | 0.77 |
| Annual Sum or Average | 0.630938E+09 | 0.77 | |||
| Minimum of Months | 48400714.57 | 0.76 | 20.01 | 0.76 | |
| Maximum of Months | 53586505.42 | 0.77 | 20.01 | 0.77 |
Report: FanReportMonthly
For: SPLIT TN1 SUPPLY FAN
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.114209E+09 | 1.01 | 98.14 | 17-JAN-04:00 | 1.12 |
| February | 81911344.77 | 0.87 | 105.28 | 06-FEB-05:00 | 1.12 |
| March | 39696846.20 | 0.58 | 78.45 | 04-MAR-06:00 | 1.12 |
| April | 50909733.68 | 0.55 | 132.35 | 13-APR-16:27 | 1.27 |
| May | 0.116431E+09 | 0.77 | 188.22 | 19-MAY-17:10 | 1.24 |
| June | 0.240889E+09 | 1.09 | 276.37 | 28-JUN-16:20 | 1.21 |
| July | 0.316342E+09 | 1.25 | 258.29 | 21-JUL-17:00 | 1.21 |
| August | 0.266951E+09 | 1.22 | 228.33 | 20-AUG-16:10 | 1.22 |
| September | 0.145772E+09 | 0.95 | 189.81 | 03-SEP-14:10 | 1.23 |
| October | 54887943.71 | 0.60 | 143.95 | 01-OCT-16:10 | 1.25 |
| November | 56426938.03 | 0.77 | 84.53 | 27-NOV-06:00 | 1.12 |
| December | 0.121798E+09 | 1.09 | 102.28 | 15-DEC-07:00 | 1.12 |
| Annual Sum or Average | 0.160622E+10 | 0.90 | |||
| Minimum of Months | 39696846.20 | 0.55 | 78.45 | 1.12 | |
| Maximum of Months | 0.316342E+09 | 1.25 | 276.37 | 1.27 |
Report: FanReportMonthly
For: T N1 APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.77 | 20.01 | 01-JAN-00:10 | 0.77 |
| February | 48400714.57 | 0.77 | 20.01 | 01-FEB-00:10 | 0.77 |
| March | 53586505.42 | 0.77 | 20.01 | 01-MAR-00:10 | 0.77 |
| April | 51857908.47 | 0.77 | 20.01 | 01-APR-00:10 | 0.77 |
| May | 53586505.42 | 0.77 | 20.01 | 01-MAY-00:10 | 0.77 |
| June | 51857908.47 | 0.77 | 20.01 | 01-JUN-00:10 | 0.77 |
| July | 53586505.42 | 0.76 | 20.01 | 01-JUL-00:10 | 0.76 |
| August | 53586505.42 | 0.76 | 20.01 | 01-AUG-00:10 | 0.76 |
| September | 51857908.47 | 0.76 | 20.01 | 01-SEP-00:10 | 0.76 |
| October | 53586505.42 | 0.77 | 20.01 | 01-OCT-00:10 | 0.76 |
| November | 51857908.47 | 0.77 | 20.01 | 01-NOV-00:10 | 0.77 |
| December | 53586505.42 | 0.77 | 20.01 | 01-DEC-00:10 | 0.77 |
| Annual Sum or Average | 0.630938E+09 | 0.77 | |||
| Minimum of Months | 48400714.57 | 0.76 | 20.01 | 0.76 | |
| Maximum of Months | 53586505.42 | 0.77 | 20.01 | 0.77 |
Report: FanReportMonthly
For: T N1 APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.77 | 20.01 | 01-JAN-00:10 | 0.77 |
| February | 48400714.57 | 0.77 | 20.01 | 01-FEB-00:10 | 0.77 |
| March | 53586505.42 | 0.77 | 20.01 | 01-MAR-00:10 | 0.77 |
| April | 51857908.47 | 0.77 | 20.01 | 01-APR-00:10 | 0.77 |
| May | 53586505.42 | 0.77 | 20.01 | 01-MAY-00:10 | 0.77 |
| June | 51857908.47 | 0.76 | 20.01 | 01-JUN-00:10 | 0.77 |
| July | 53586505.42 | 0.76 | 20.01 | 01-JUL-00:10 | 0.76 |
| August | 53586505.42 | 0.76 | 20.01 | 01-AUG-00:10 | 0.76 |
| September | 51857908.47 | 0.76 | 20.01 | 01-SEP-00:10 | 0.76 |
| October | 53586505.42 | 0.77 | 20.01 | 01-OCT-00:10 | 0.77 |
| November | 51857908.47 | 0.77 | 20.01 | 01-NOV-00:10 | 0.77 |
| December | 53586505.42 | 0.77 | 20.01 | 01-DEC-00:10 | 0.77 |
| Annual Sum or Average | 0.630938E+09 | 0.77 | |||
| Minimum of Months | 48400714.57 | 0.76 | 20.01 | 0.76 | |
| Maximum of Months | 53586505.42 | 0.77 | 20.01 | 0.77 |
Report: FanReportMonthly
For: SPLIT TN2 SUPPLY FAN
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.114345E+09 | 1.01 | 98.15 | 17-JAN-04:00 | 1.12 |
| February | 82099123.80 | 0.87 | 105.26 | 06-FEB-05:00 | 1.12 |
| March | 39644125.44 | 0.58 | 78.47 | 04-MAR-06:00 | 1.12 |
| April | 51662802.01 | 0.56 | 130.99 | 13-APR-16:14 | 1.27 |
| May | 0.117261E+09 | 0.78 | 186.17 | 19-MAY-17:05 | 1.24 |
| June | 0.241605E+09 | 1.09 | 274.58 | 28-JUN-16:20 | 1.21 |
| July | 0.317046E+09 | 1.25 | 256.23 | 21-JUL-17:00 | 1.21 |
| August | 0.267555E+09 | 1.22 | 227.05 | 20-AUG-16:10 | 1.22 |
| September | 0.146278E+09 | 0.95 | 190.23 | 03-SEP-14:00 | 1.23 |
| October | 55147492.71 | 0.60 | 143.15 | 01-OCT-16:10 | 1.25 |
| November | 56546400.80 | 0.78 | 84.52 | 27-NOV-06:00 | 1.12 |
| December | 0.121875E+09 | 1.09 | 102.33 | 15-DEC-07:00 | 1.12 |
| Annual Sum or Average | 0.161107E+10 | 0.90 | |||
| Minimum of Months | 39644125.44 | 0.56 | 78.47 | 1.12 | |
| Maximum of Months | 0.317046E+09 | 1.25 | 274.58 | 1.27 |
Report: FanReportMonthly
For: T N2 APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.77 | 20.01 | 01-JAN-00:10 | 0.77 |
| February | 48400714.57 | 0.77 | 20.01 | 01-FEB-00:10 | 0.77 |
| March | 53586505.42 | 0.77 | 20.01 | 01-MAR-00:10 | 0.77 |
| April | 51857908.47 | 0.77 | 20.01 | 01-APR-00:10 | 0.77 |
| May | 53586505.42 | 0.77 | 20.01 | 01-MAY-00:10 | 0.77 |
| June | 51857908.47 | 0.77 | 20.01 | 01-JUN-00:10 | 0.77 |
| July | 53586505.42 | 0.76 | 20.01 | 01-JUL-00:10 | 0.76 |
| August | 53586505.42 | 0.76 | 20.01 | 01-AUG-00:10 | 0.76 |
| September | 51857908.47 | 0.76 | 20.01 | 01-SEP-00:10 | 0.76 |
| October | 53586505.42 | 0.77 | 20.01 | 01-OCT-00:10 | 0.76 |
| November | 51857908.47 | 0.77 | 20.01 | 01-NOV-00:10 | 0.77 |
| December | 53586505.42 | 0.77 | 20.01 | 01-DEC-00:10 | 0.77 |
| Annual Sum or Average | 0.630938E+09 | 0.77 | |||
| Minimum of Months | 48400714.57 | 0.76 | 20.01 | 0.76 | |
| Maximum of Months | 53586505.42 | 0.77 | 20.01 | 0.77 |
Report: FanReportMonthly
For: T N2 APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.77 | 20.01 | 01-JAN-00:10 | 0.77 |
| February | 48400714.57 | 0.77 | 20.01 | 01-FEB-00:10 | 0.77 |
| March | 53586505.42 | 0.77 | 20.01 | 01-MAR-00:10 | 0.77 |
| April | 51857908.47 | 0.77 | 20.01 | 01-APR-00:10 | 0.77 |
| May | 53586505.42 | 0.77 | 20.01 | 01-MAY-00:10 | 0.77 |
| June | 51857908.47 | 0.76 | 20.01 | 01-JUN-00:10 | 0.77 |
| July | 53586505.42 | 0.76 | 20.01 | 01-JUL-00:10 | 0.76 |
| August | 53586505.42 | 0.76 | 20.01 | 01-AUG-00:10 | 0.76 |
| September | 51857908.47 | 0.76 | 20.01 | 01-SEP-00:10 | 0.76 |
| October | 53586505.42 | 0.77 | 20.01 | 01-OCT-00:10 | 0.77 |
| November | 51857908.47 | 0.77 | 20.01 | 01-NOV-00:10 | 0.77 |
| December | 53586505.42 | 0.77 | 20.01 | 01-DEC-00:10 | 0.77 |
| Annual Sum or Average | 0.630938E+09 | 0.77 | |||
| Minimum of Months | 48400714.57 | 0.76 | 20.01 | 0.76 | |
| Maximum of Months | 53586505.42 | 0.77 | 20.01 | 0.77 |
Report: FanReportMonthly
For: SPLIT TS1 SUPPLY FAN
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 97265284.61 | 0.83 | 150.34 | 23-JAN-14:40 | 1.26 |
| February | 80680280.89 | 0.79 | 185.54 | 14-FEB-15:00 | 1.25 |
| March | 64045149.37 | 0.69 | 176.22 | 08-MAR-14:00 | 1.24 |
| April | 94223752.92 | 0.70 | 194.35 | 26-APR-14:10 | 1.24 |
| May | 0.137127E+09 | 0.79 | 210.12 | 19-MAY-15:10 | 1.23 |
| June | 0.239324E+09 | 1.06 | 285.97 | 28-JUN-16:10 | 1.20 |
| July | 0.330752E+09 | 1.24 | 293.40 | 22-JUL-14:10 | 1.19 |
| August | 0.311271E+09 | 1.22 | 278.96 | 20-AUG-15:30 | 1.20 |
| September | 0.232258E+09 | 1.02 | 289.41 | 03-SEP-13:30 | 1.19 |
| October | 0.148479E+09 | 0.80 | 257.90 | 01-OCT-14:00 | 1.21 |
| November | 72580231.15 | 0.71 | 163.80 | 20-NOV-14:00 | 1.25 |
| December | 87490707.59 | 0.83 | 150.94 | 31-DEC-14:50 | 1.26 |
| Annual Sum or Average | 0.189550E+10 | 0.89 | |||
| Minimum of Months | 64045149.37 | 0.69 | 150.34 | 1.19 | |
| Maximum of Months | 0.330752E+09 | 1.24 | 293.40 | 1.26 |
Report: FanReportMonthly
For: T S1 APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.77 | 20.01 | 01-JAN-00:10 | 0.77 |
| February | 48400714.57 | 0.77 | 20.01 | 01-FEB-00:10 | 0.77 |
| March | 53586505.42 | 0.77 | 20.01 | 01-MAR-00:10 | 0.77 |
| April | 51857908.47 | 0.77 | 20.01 | 01-APR-00:10 | 0.77 |
| May | 53586505.42 | 0.77 | 20.01 | 01-MAY-00:10 | 0.77 |
| June | 51857908.47 | 0.77 | 20.01 | 01-JUN-00:10 | 0.77 |
| July | 53586505.42 | 0.76 | 20.01 | 01-JUL-00:10 | 0.76 |
| August | 53586505.42 | 0.76 | 20.01 | 01-AUG-00:10 | 0.76 |
| September | 51857908.47 | 0.76 | 20.01 | 01-SEP-00:10 | 0.76 |
| October | 53586505.42 | 0.77 | 20.01 | 01-OCT-00:10 | 0.76 |
| November | 51857908.47 | 0.77 | 20.01 | 01-NOV-00:10 | 0.77 |
| December | 53586505.42 | 0.77 | 20.01 | 01-DEC-00:10 | 0.77 |
| Annual Sum or Average | 0.630938E+09 | 0.77 | |||
| Minimum of Months | 48400714.57 | 0.76 | 20.01 | 0.76 | |
| Maximum of Months | 53586505.42 | 0.77 | 20.01 | 0.77 |
Report: FanReportMonthly
For: T S1 APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.77 | 20.01 | 01-JAN-00:10 | 0.77 |
| February | 48400714.57 | 0.77 | 20.01 | 01-FEB-00:10 | 0.77 |
| March | 53586505.42 | 0.77 | 20.01 | 01-MAR-00:10 | 0.77 |
| April | 51857908.47 | 0.77 | 20.01 | 01-APR-00:10 | 0.77 |
| May | 53586505.42 | 0.77 | 20.01 | 01-MAY-00:10 | 0.77 |
| June | 51857908.47 | 0.76 | 20.01 | 01-JUN-00:10 | 0.77 |
| July | 53586505.42 | 0.76 | 20.01 | 01-JUL-00:10 | 0.76 |
| August | 53586505.42 | 0.76 | 20.01 | 01-AUG-00:10 | 0.76 |
| September | 51857908.47 | 0.76 | 20.01 | 01-SEP-00:10 | 0.76 |
| October | 53586505.42 | 0.77 | 20.01 | 01-OCT-00:10 | 0.77 |
| November | 51857908.47 | 0.77 | 20.01 | 01-NOV-00:10 | 0.77 |
| December | 53586505.42 | 0.77 | 20.01 | 01-DEC-00:10 | 0.77 |
| Annual Sum or Average | 0.630938E+09 | 0.77 | |||
| Minimum of Months | 48400714.57 | 0.76 | 20.01 | 0.76 | |
| Maximum of Months | 53586505.42 | 0.77 | 20.01 | 0.77 |
Report: FanReportMonthly
For: SPLIT TS2 SUPPLY FAN
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 97758156.34 | 0.83 | 151.11 | 23-JAN-14:40 | 1.26 |
| February | 81178662.19 | 0.79 | 185.98 | 14-FEB-14:50 | 1.25 |
| March | 64713334.70 | 0.69 | 177.80 | 08-MAR-14:00 | 1.24 |
| April | 95370641.71 | 0.70 | 195.41 | 26-APR-14:10 | 1.24 |
| May | 0.138003E+09 | 0.79 | 209.84 | 19-MAY-15:10 | 1.23 |
| June | 0.240086E+09 | 1.06 | 284.28 | 28-JUN-16:10 | 1.20 |
| July | 0.331446E+09 | 1.24 | 293.85 | 22-JUL-14:10 | 1.19 |
| August | 0.311818E+09 | 1.22 | 278.33 | 20-AUG-15:20 | 1.20 |
| September | 0.232610E+09 | 1.02 | 290.13 | 03-SEP-13:30 | 1.19 |
| October | 0.149048E+09 | 0.80 | 258.32 | 01-OCT-14:00 | 1.20 |
| November | 73161302.78 | 0.71 | 164.57 | 20-NOV-14:00 | 1.25 |
| December | 87950997.30 | 0.83 | 151.22 | 31-DEC-14:50 | 1.26 |
| Annual Sum or Average | 0.190315E+10 | 0.89 | |||
| Minimum of Months | 64713334.70 | 0.69 | 151.11 | 1.19 | |
| Maximum of Months | 0.331446E+09 | 1.24 | 293.85 | 1.26 |
Report: FanReportMonthly
For: T S2 APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.77 | 20.01 | 01-JAN-00:10 | 0.77 |
| February | 48400714.57 | 0.77 | 20.01 | 01-FEB-00:10 | 0.77 |
| March | 53586505.42 | 0.77 | 20.01 | 01-MAR-00:10 | 0.77 |
| April | 51857908.47 | 0.77 | 20.01 | 01-APR-00:10 | 0.77 |
| May | 53586505.42 | 0.77 | 20.01 | 01-MAY-00:10 | 0.77 |
| June | 51857908.47 | 0.77 | 20.01 | 01-JUN-00:10 | 0.77 |
| July | 53586505.42 | 0.76 | 20.01 | 01-JUL-00:10 | 0.76 |
| August | 53586505.42 | 0.76 | 20.01 | 01-AUG-00:10 | 0.76 |
| September | 51857908.47 | 0.76 | 20.01 | 01-SEP-00:10 | 0.76 |
| October | 53586505.42 | 0.77 | 20.01 | 01-OCT-00:10 | 0.76 |
| November | 51857908.47 | 0.77 | 20.01 | 01-NOV-00:10 | 0.77 |
| December | 53586505.42 | 0.77 | 20.01 | 01-DEC-00:10 | 0.77 |
| Annual Sum or Average | 0.630938E+09 | 0.77 | |||
| Minimum of Months | 48400714.57 | 0.76 | 20.01 | 0.76 | |
| Maximum of Months | 53586505.42 | 0.77 | 20.01 | 0.77 |
Report: FanReportMonthly
For: T S2 APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.77 | 20.01 | 01-JAN-00:10 | 0.77 |
| February | 48400714.57 | 0.77 | 20.01 | 01-FEB-00:10 | 0.77 |
| March | 53586505.42 | 0.77 | 20.01 | 01-MAR-00:10 | 0.77 |
| April | 51857908.47 | 0.77 | 20.01 | 01-APR-00:10 | 0.77 |
| May | 53586505.42 | 0.77 | 20.01 | 01-MAY-00:10 | 0.77 |
| June | 51857908.47 | 0.76 | 20.01 | 01-JUN-00:10 | 0.77 |
| July | 53586505.42 | 0.76 | 20.01 | 01-JUL-00:10 | 0.76 |
| August | 53586505.42 | 0.76 | 20.01 | 01-AUG-00:10 | 0.76 |
| September | 51857908.47 | 0.76 | 20.01 | 01-SEP-00:10 | 0.76 |
| October | 53586505.42 | 0.77 | 20.01 | 01-OCT-00:10 | 0.77 |
| November | 51857908.47 | 0.77 | 20.01 | 01-NOV-00:10 | 0.77 |
| December | 53586505.42 | 0.77 | 20.01 | 01-DEC-00:10 | 0.77 |
| Annual Sum or Average | 0.630938E+09 | 0.77 | |||
| Minimum of Months | 48400714.57 | 0.76 | 20.01 | 0.76 | |
| Maximum of Months | 53586505.42 | 0.77 | 20.01 | 0.77 |
Report: ZoneTemperatureOscillationReportMonthly
For: G SW APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: G NW APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: OFFICE
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: G NE APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: G N1 APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: G N2 APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: G S1 APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: G S2 APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: M SW APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: M NW APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: M SE APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: M NE APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: M N1 APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: M N2 APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: M S1 APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: M S2 APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: T SW APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: T NW APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: T SE APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: T NE APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: T N1 APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: T N2 APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: T S1 APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: T S2 APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: T CORRIDOR
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: G CORRIDOR
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: M CORRIDOR
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT GSW
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 46067059.10 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 44511302.98 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 30775953.97 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.146681E+09 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.365112E+09 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.876257E+09 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.132407E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.131232E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.107383E+10 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.657495E+09 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.129972E+09 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 29265106.52 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.603635E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 29265106.52 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.132407E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT GNW
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.101932E+09 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 83065830.49 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 47732916.99 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 57247460.66 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.295042E+09 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.884663E+09 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.127022E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.114547E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.735678E+09 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.254438E+09 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 23155381.32 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 93532284.06 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.499218E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 23155381.32 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.127022E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT OFFICE
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.143996E+10 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.130693E+10 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.148713E+10 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.157503E+10 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.175642E+10 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.199409E+10 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.219917E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.225356E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.200387E+10 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.185653E+10 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.155252E+10 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.143177E+10 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.208570E+11 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.130693E+10 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.225356E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT GNE
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.100875E+09 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 83214820.83 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 43638685.18 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 68032518.94 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.330421E+09 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.930872E+09 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.133246E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.119106E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.752951E+09 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.253789E+09 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 21590301.31 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 93016727.13 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.520192E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 21590301.31 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.133246E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT GN1
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 68308894.67 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 55469032.65 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 27218360.43 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 37331729.84 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.257057E+09 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.736472E+09 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.106578E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.943223E+09 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.605412E+09 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.199324E+09 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 11481457.93 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 63487704.96 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.407057E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 11481457.93 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.106578E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT GN2
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 68324724.62 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 55587061.34 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 27071704.79 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 39262797.75 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.260743E+09 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.739320E+09 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.106900E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.945525E+09 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.606420E+09 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.199846E+09 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 11487259.69 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 63544640.11 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.408613E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 11487259.69 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.106900E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT GS1
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 33556999.12 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 26470345.31 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 21593337.52 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.138535E+09 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.334459E+09 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.731743E+09 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.112582E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.111781E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.953525E+09 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.637308E+09 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.192523E+09 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 19276017.55 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.533262E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 19276017.55 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.112582E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT GS2
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 35775077.29 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 27959562.79 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 25215025.67 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.162939E+09 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.385835E+09 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.814063E+09 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.124302E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.122757E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.104752E+10 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.703737E+09 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.209488E+09 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 20971696.60 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.590409E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 20971696.60 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.124302E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT MSW
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.195925E+09 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.239144E+09 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.351465E+09 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.100555E+10 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.141001E+10 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.233806E+10 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.310035E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.294345E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.229074E+10 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.143719E+10 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.436244E+09 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.141699E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.158898E+11 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.141699E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.310035E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT MNW
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.149894E+09 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 98609626.24 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 24064719.72 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.555223E+09 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.123691E+10 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.235242E+10 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.297847E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.258213E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.157371E+10 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.541516E+09 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 43436640.24 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.160228E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.122966E+11 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 24064719.72 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.297847E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT MSE
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.188941E+09 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.224815E+09 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.372976E+09 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.110693E+10 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.150978E+10 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.243762E+10 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.322545E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.303553E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.232316E+10 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.145157E+10 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.432183E+09 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.120307E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.164293E+11 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.120307E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.322545E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT MNE
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.146923E+09 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 98766011.31 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 18087702.69 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.627476E+09 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.133337E+10 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.245241E+10 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.310503E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.267928E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.161280E+10 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.537609E+09 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 39744381.76 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.158735E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.128102E+11 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 18087702.69 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.310503E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT MN1
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 84376243.50 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 53487408.50 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 5871518.78 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.409419E+09 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.992217E+09 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.184579E+10 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.238199E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.205000E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.127601E+10 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.422357E+09 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 14570133.03 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 92864108.89 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.962895E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 5871518.78 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.238199E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT MN2
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 84591867.98 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 53794989.71 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 5860422.41 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.416897E+09 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.998381E+09 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.185042E+10 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.238745E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.205411E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.127792E+10 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.424355E+09 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 14616831.99 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 93034922.41 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.966143E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 5860422.41 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.238745E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT MS1
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.253921E+09 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.263252E+09 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.378474E+09 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.887388E+09 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.116988E+10 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.183109E+10 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.250514E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.241443E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.199860E+10 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.138313E+10 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.592626E+09 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.209524E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.138875E+11 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.209524E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.250514E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT MS2
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.256540E+09 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.264141E+09 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.384763E+09 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.894626E+09 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.117640E+10 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.183584E+10 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.251054E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.241827E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.200015E+10 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.138503E+10 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.595266E+09 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.211399E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.139330E+11 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.211399E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.251054E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT TSW
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.241859E+09 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.244084E+09 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.265073E+09 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.493665E+09 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.722826E+09 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.130372E+10 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.175269E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.161949E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.114941E+10 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.679139E+09 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.257094E+09 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.206366E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.893542E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.206366E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.175269E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT TNW
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.159903E+09 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.122267E+09 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 91119657.76 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.298057E+09 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.633262E+09 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.130831E+10 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.168916E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.142908E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.788331E+09 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.273544E+09 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 84351063.66 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.167512E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.704491E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 84351063.66 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.168916E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT TSE
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.229166E+09 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.222335E+09 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.254854E+09 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.514257E+09 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.750157E+09 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.134436E+10 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.181200E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.166220E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.115988E+10 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.674076E+09 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.242606E+09 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.183603E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.904949E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.183603E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.181200E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT TNE
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.156531E+09 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.115195E+09 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 68694280.19 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.304548E+09 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.662706E+09 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.135207E+10 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.175050E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.147641E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.800750E+09 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.250147E+09 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 80812365.58 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.165321E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.718369E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 68694280.19 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.175050E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT TN1
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.114209E+09 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 81966224.90 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 42223326.92 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.188738E+09 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.485123E+09 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.103832E+10 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.138481E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.116094E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.623815E+09 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.182307E+09 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 56426938.03 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.121798E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.548068E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 42223326.92 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.138481E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT TN2
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.114345E+09 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 82164009.65 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 42345503.45 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.192071E+09 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.488764E+09 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.104139E+10 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.138786E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.116352E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.625970E+09 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.183428E+09 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 56546400.80 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.121875E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.550029E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 42345503.45 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.138786E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT TS1
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.198877E+09 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.193419E+09 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.194297E+09 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.378885E+09 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.572429E+09 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.103223E+10 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.144891E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.135350E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.992742E+09 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.597059E+09 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.228975E+09 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.172227E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.736354E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.172227E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.144891E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT TS2
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.200623E+09 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.195069E+09 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.197154E+09 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.383755E+09 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.576257E+09 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.103549E+10 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.145191E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.135583E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.994228E+09 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.599393E+09 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.231205E+09 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.173875E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.739480E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.173875E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.145191E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT GSW
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 39849596.97 | 23256309.86 | 0.697049E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 34658859.93 | 36962247.48 | 0.580317E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 19908112.50 | 40626917.80 | 0.302943E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 35577186.02 | 0.417879E+09 | 8097874.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 86832592.08 | 0.103982E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.203574E+09 | 0.243497E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.303086E+09 | 0.377509E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.302660E+09 | 0.380211E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.251857E+09 | 0.315312E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.156797E+09 | 0.192447E+10 | 3922950.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 31313486.28 | 0.372502E+09 | 1524567.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 25372441.15 | 14522908.03 | 0.444200E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.149149E+10 | 0.170353E+11 | 0.203805E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 19908112.50 | 14522908.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.303086E+09 | 0.380211E+10 | 0.697049E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT GNW
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 0.101932E+09 | 0.00 | 0.187890E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 83065830.49 | 0.00 | 0.153113E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 47732916.99 | 0.00 | 0.879849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 17872592.17 | 0.146817E+09 | 0.100218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 70131855.82 | 0.837322E+09 | 471401.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.205598E+09 | 0.246335E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.290837E+09 | 0.362139E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.264064E+09 | 0.330582E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.172345E+09 | 0.213819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 61679562.93 | 0.731773E+09 | 33928347.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 23155381.32 | 0.00 | 0.426817E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 93532284.06 | 0.00 | 0.172406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.143195E+10 | 0.132447E+11 | 0.657537E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 17872592.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.290837E+09 | 0.362139E+10 | 0.187890E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT OFFICE
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 0.141110E+10 | 0.108453E+09 | 71297111.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.127454E+10 | 0.122849E+09 | 14114013.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.141110E+10 | 0.287375E+09 | 30777.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.136558E+10 | 0.804133E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.141110E+10 | 0.133676E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.136558E+10 | 0.233864E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.141110E+10 | 0.297753E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.141110E+10 | 0.327584E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.136558E+10 | 0.253521E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.141110E+10 | 0.177243E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.136558E+10 | 0.717153E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.141110E+10 | 77381728.15 | 1939722.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.166146E+11 | 0.163538E+11 | 87381625.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 0.127454E+10 | 77381728.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.141110E+10 | 0.327584E+10 | 71297111.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT GNE
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 0.100875E+09 | 0.00 | 0.187517E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 83214820.83 | 0.00 | 0.154688E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 43638685.18 | 0.00 | 0.811199E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 19817993.66 | 0.180144E+09 | 85094853.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 78517837.25 | 0.942676E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.216453E+09 | 0.261039E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.305361E+09 | 0.382804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.274813E+09 | 0.345952E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.176472E+09 | 0.219634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 61214486.32 | 0.732531E+09 | 27107618.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 21590301.31 | 0.00 | 0.401342E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 93016727.13 | 0.00 | 0.172909E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.147499E+10 | 0.139496E+11 | 0.647587E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 19817993.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.305361E+09 | 0.382804E+10 | 0.187517E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT GN1
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 68308894.67 | 0.00 | 0.128470E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 55469032.65 | 0.00 | 0.104322E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 27218360.43 | 0.00 | 0.511902E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 10801691.33 | 98752837.40 | 45543936.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 61062424.81 | 0.730986E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.171287E+09 | 0.205603E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.244210E+09 | 0.305224E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.217554E+09 | 0.272922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.141856E+09 | 0.176113E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 47288833.09 | 0.576977E+09 | 2698317.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 11481457.93 | 0.00 | 0.215935E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 63487704.96 | 0.00 | 0.119403E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.112003E+10 | 0.110053E+11 | 0.429803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 10801691.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.244210E+09 | 0.305224E+10 | 0.128470E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT GN2
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 68324724.62 | 0.00 | 0.128529E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 55587061.34 | 0.00 | 0.104568E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 27071704.79 | 0.00 | 0.509259E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 11241127.67 | 0.104344E+09 | 44945199.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 61937213.12 | 0.741731E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.171953E+09 | 0.206448E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.244952E+09 | 0.306216E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.218088E+09 | 0.273635E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.142093E+09 | 0.176424E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 47404771.11 | 0.578564E+09 | 2512750.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 11487259.69 | 0.00 | 0.216092E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 63544640.11 | 0.00 | 0.119537E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.112368E+10 | 0.110519E+11 | 0.429914E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 11241127.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.244952E+09 | 0.306216E+10 | 0.128529E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT GS1
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 18454281.90 | 56844506.47 | 0.256196E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 14245074.31 | 45902899.31 | 0.194388E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 8316502.41 | 49623095.50 | 76996532.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 33293191.33 | 0.395880E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 79536759.11 | 0.954260E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.170116E+09 | 0.203811E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.257887E+09 | 0.322375E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.257937E+09 | 0.324852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.223706E+09 | 0.280680E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.151900E+09 | 0.186801E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 46296054.21 | 0.553703E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 8230769.18 | 41314847.77 | 88649370.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.126992E+10 | 0.152827E+11 | 0.616230E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 8230769.18 | 41314847.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.257937E+09 | 0.324852E+10 | 0.256196E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT GS2
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 19811452.96 | 60091147.23 | 0.276318E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 15127246.21 | 48198045.39 | 0.207165E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 8871310.44 | 61112247.45 | 69119161.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 39162336.75 | 0.466220E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 91767439.21 | 0.110406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.189423E+09 | 0.227794E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.285048E+09 | 0.357531E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.283514E+09 | 0.358117E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.245861E+09 | 0.309292E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.167753E+09 | 0.206683E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 50374363.54 | 0.602913E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 8671627.78 | 46030460.12 | 89389369.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.140538E+10 | 0.169828E+11 | 0.641992E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 8671627.78 | 46030460.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.285048E+09 | 0.358117E+10 | 0.276318E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT MSW
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 79242304.72 | 0.439766E+09 | 0.765783E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 75446918.95 | 0.620788E+09 | 0.426761E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 86743204.16 | 0.100177E+10 | 50925799.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.241801E+09 | 0.290161E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.335771E+09 | 0.405397E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.543993E+09 | 0.653005E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.709763E+09 | 0.882114E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.678575E+09 | 0.849636E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.536941E+09 | 0.670345E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.343792E+09 | 0.419852E+10 | 29931206.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.105913E+09 | 0.125251E+10 | 23524808.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 59132553.82 | 0.310538E+09 | 0.597344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.379711E+10 | 0.453305E+11 | 0.189427E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 59132553.82 | 0.310538E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.709763E+09 | 0.882114E+10 | 0.765783E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT MNW
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 0.149894E+09 | 0.00 | 0.271893E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 98499022.57 | 410189.37 | 0.178604E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 20201678.82 | 14360440.49 | 0.344221E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.133456E+09 | 0.159134E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.294419E+09 | 0.354624E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.547531E+09 | 0.657953E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.682128E+09 | 0.847255E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.595151E+09 | 0.742526E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.368529E+09 | 0.455782E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.132972E+09 | 0.154673E+10 | 0.110541E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 43109424.82 | 1218110.92 | 0.780094E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.160228E+09 | 0.00 | 0.290639E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.322612E+10 | 0.337355E+11 | 0.864621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 20201678.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.682128E+09 | 0.847255E+10 | 0.290639E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT MSE
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 77904665.70 | 0.418317E+09 | 0.780559E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 72713234.77 | 0.576138E+09 | 0.447629E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 91564650.81 | 0.106533E+10 | 42852527.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.266223E+09 | 0.319975E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.359558E+09 | 0.436119E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.567561E+09 | 0.686186E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.739248E+09 | 0.925803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.700600E+09 | 0.883044E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.544867E+09 | 0.683483E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.347079E+09 | 0.425362E+10 | 26586134.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.104984E+09 | 0.124102E+10 | 24859036.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 53796384.77 | 0.249956E+09 | 0.597922E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.392610E+10 | 0.471505E+11 | 0.192041E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 53796384.77 | 0.249956E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.739248E+09 | 0.925803E+10 | 0.780559E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT MNE
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 0.146923E+09 | 0.00 | 0.268796E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 98766011.31 | 0.00 | 0.180693E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 16654316.01 | 5314280.21 | 0.296377E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.150865E+09 | 0.179987E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.317400E+09 | 0.384044E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.571218E+09 | 0.691367E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.711945E+09 | 0.890977E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.618311E+09 | 0.776240E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.377980E+09 | 0.469012E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.131257E+09 | 0.154084E+10 | 93307500.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 39744381.76 | 0.00 | 0.727125E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.158735E+09 | 0.00 | 0.290406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.333980E+10 | 0.354624E+11 | 0.851576E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 16654316.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.711945E+09 | 0.890977E+10 | 0.290406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT MN1
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 84376243.50 | 0.00 | 0.155949E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 53487408.50 | 0.00 | 0.988582E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 5710580.68 | 596907.90 | 0.104603E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 98415379.59 | 0.116873E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.236113E+09 | 0.284167E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.429939E+09 | 0.516785E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.545995E+09 | 0.680267E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.472870E+09 | 0.591033E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.298979E+09 | 0.369910E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.100737E+09 | 0.121664E+10 | 17349805.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 14500373.66 | 260045.61 | 0.267599E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 92864108.89 | 0.00 | 0.171636E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.243399E+10 | 0.268078E+11 | 0.465398E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 5710580.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.545995E+09 | 0.680267E+10 | 0.171636E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT MN2
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 84591867.98 | 0.00 | 0.156384E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 53794989.71 | 0.00 | 0.994501E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 5682517.68 | 659977.91 | 0.104009E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.100215E+09 | 0.119019E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.237580E+09 | 0.285982E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.431014E+09 | 0.518176E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.547251E+09 | 0.681961E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.473823E+09 | 0.592314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.299427E+09 | 0.370500E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.101189E+09 | 0.122255E+10 | 16766428.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 14558658.52 | 216817.68 | 0.268806E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 93034922.41 | 0.00 | 0.171992E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.244216E+10 | 0.269030E+11 | 0.466785E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 5682517.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.547251E+09 | 0.681961E+10 | 0.171992E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT MS1
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 70827515.13 | 0.693595E+09 | 0.235743E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 65421832.62 | 0.750997E+09 | 49755515.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 91158216.26 | 0.108700E+10 | 1195972.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.213414E+09 | 0.255374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.278565E+09 | 0.336022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.426296E+09 | 0.511724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.573912E+09 | 0.715353E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.556988E+09 | 0.698925E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.468689E+09 | 0.586216E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.329829E+09 | 0.404996E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.142550E+09 | 0.171268E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 53316663.04 | 0.590065E+09 | 69896128.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.327097E+10 | 0.399205E+11 | 0.356590E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 53316663.04 | 0.590065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.573912E+09 | 0.715353E+10 | 0.235743E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT MS2
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 71535625.96 | 0.700972E+09 | 0.237688E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 65637568.93 | 0.753678E+09 | 49807909.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 92663829.95 | 0.110532E+10 | 998676.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.215156E+09 | 0.257499E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.280119E+09 | 0.337958E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.427400E+09 | 0.513154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.575155E+09 | 0.717048E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.557880E+09 | 0.700169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.469054E+09 | 0.586766E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.330283E+09 | 0.405612E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.143185E+09 | 0.172057E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 53755378.98 | 0.595581E+09 | 69607096.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.328182E+10 | 0.400582E+11 | 0.358101E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 53755378.98 | 0.595581E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.575155E+09 | 0.717048E+10 | 0.237688E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT TSW
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 0.139589E+09 | 0.388252E+09 | 0.192780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.117108E+09 | 0.484620E+09 | 0.138244E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 98542139.74 | 0.635228E+09 | 0.822851E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.126809E+09 | 0.140368E+10 | 0.192543E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.174723E+09 | 0.207754E+10 | 65210708.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.302367E+09 | 0.363593E+10 | 4517497.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.399734E+09 | 0.497478E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.372122E+09 | 0.467279E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.268782E+09 | 0.337662E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.174289E+09 | 0.194958E+10 | 0.296040E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 96790200.17 | 0.610270E+09 | 0.827673E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.126868E+09 | 0.300416E+09 | 0.182883E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.239772E+10 | 0.245097E+11 | 0.734790E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 96790200.17 | 0.300416E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.399734E+09 | 0.497478E+10 | 0.192780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT TNW
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 0.159903E+09 | 0.00 | 0.287486E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.117671E+09 | 17159779.36 | 0.208936E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 69954909.76 | 79258556.87 | 0.113705E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 82484670.38 | 0.817478E+09 | 0.257095E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.153472E+09 | 0.180965E+10 | 68053012.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.303512E+09 | 0.364953E+10 | 3518148.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.385446E+09 | 0.478632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.328288E+09 | 0.409764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.184139E+09 | 0.228169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 84803367.83 | 0.714901E+09 | 0.472803E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 84195343.92 | 579007.60 | 0.151284E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.167512E+09 | 0.00 | 0.301166E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.212138E+10 | 0.182542E+11 | 0.114272E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 69954909.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.385446E+09 | 0.478632E+10 | 0.301166E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT TSE
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 0.134930E+09 | 0.357545E+09 | 0.190972E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.110615E+09 | 0.426214E+09 | 0.136694E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 93458329.12 | 0.615310E+09 | 0.768742E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.130556E+09 | 0.147187E+10 | 0.165085E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.180521E+09 | 0.217276E+10 | 48009620.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.312009E+09 | 0.378973E+10 | 2333262.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.413929E+09 | 0.520626E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.382562E+09 | 0.484965E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.271478E+09 | 0.343504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.172512E+09 | 0.194467E+10 | 0.285412E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 92210937.88 | 0.572822E+09 | 0.810164E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.119468E+09 | 0.242019E+09 | 0.180216E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.241425E+10 | 0.250839E+11 | 0.715857E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 92210937.88 | 0.242019E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.413929E+09 | 0.520626E+10 | 0.190972E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT TNE
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 0.156531E+09 | 0.00 | 0.284345E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.114427E+09 | 2849735.20 | 0.207420E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 60333304.25 | 31195230.90 | 0.104782E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 82416471.41 | 0.842579E+09 | 0.220253E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.159792E+09 | 0.190703E+10 | 51515786.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.313953E+09 | 0.381147E+10 | 2263193.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.400104E+09 | 0.501904E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.339770E+09 | 0.427709E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.187245E+09 | 0.233008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 77428529.66 | 0.655801E+09 | 0.435401E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 80812365.58 | 0.00 | 0.146799E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.165321E+09 | 0.00 | 0.300313E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.213813E+10 | 0.188771E+11 | 0.111460E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 60333304.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.400104E+09 | 0.501904E+10 | 0.300313E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT TN1
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 0.114209E+09 | 0.00 | 0.208685E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 81911344.77 | 203237.61 | 0.149639E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 39696846.20 | 9395014.32 | 0.710715E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 50909733.68 | 0.519840E+09 | 0.133717E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.116431E+09 | 0.138637E+10 | 26594873.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.240889E+09 | 0.289528E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.316342E+09 | 0.393649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.266951E+09 | 0.333473E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.145772E+09 | 0.180402E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 54887943.71 | 0.481543E+09 | 0.283533E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 56426938.03 | 0.00 | 0.103105E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.121798E+09 | 0.00 | 0.222552E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.160622E+10 | 0.143679E+11 | 0.799437E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 39696846.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.316342E+09 | 0.393649E+10 | 0.222552E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT TN2
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 0.114345E+09 | 0.00 | 0.209034E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 82099123.80 | 240302.32 | 0.150048E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 39644125.44 | 10047102.47 | 0.709076E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 51662802.01 | 0.529695E+09 | 0.132602E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.117261E+09 | 0.139747E+10 | 25741059.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.241605E+09 | 0.290512E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.317046E+09 | 0.394682E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.267555E+09 | 0.334344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.146278E+09 | 0.181074E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 55147492.71 | 0.484907E+09 | 0.283509E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 56546400.80 | 0.00 | 0.103373E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.121875E+09 | 0.00 | 0.222800E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.161107E+10 | 0.144285E+11 | 0.800347E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 39644125.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.317046E+09 | 0.394682E+10 | 0.222800E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT TS1
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 97265284.61 | 0.386577E+09 | 0.118941E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 80680280.89 | 0.429926E+09 | 0.821644E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 64045149.37 | 0.495425E+09 | 0.415946E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 94223752.92 | 0.108598E+10 | 75385973.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.137127E+09 | 0.164698E+10 | 23366687.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.239324E+09 | 0.287743E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.330752E+09 | 0.412601E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.311271E+09 | 0.391612E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.232258E+09 | 0.292303E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.148479E+09 | 0.173385E+10 | 0.150335E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 72580231.15 | 0.596578E+09 | 0.421235E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 87490707.59 | 0.320841E+09 | 0.110852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.189550E+10 | 0.205388E+11 | 0.420584E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 64045149.37 | 0.320841E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.330752E+09 | 0.412601E+10 | 0.118941E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT TS2
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 97758156.34 | 0.391494E+09 | 0.119173E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 81178662.19 | 0.434452E+09 | 0.824476E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 64713334.70 | 0.503941E+09 | 0.415674E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 95370641.71 | 0.110060E+10 | 74805303.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.138003E+09 | 0.165891E+10 | 22511985.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.240086E+09 | 0.288794E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.331446E+09 | 0.413649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.311818E+09 | 0.392467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.232610E+09 | 0.292867E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.149048E+09 | 0.174132E+10 | 0.150661E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 73161302.78 | 0.603084E+09 | 0.422503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 87950997.30 | 0.325432E+09 | 0.111058E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.190315E+10 | 0.206370E+11 | 0.421295E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 64713334.70 | 0.325432E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.331446E+09 | 0.413649E+10 | 0.119173E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT GSW
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 39849596.97 | 0.00 | 0.00 | 0.00 | 6217462.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 34658859.93 | 0.00 | 0.00 | 0.00 | 9852443.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 19908112.50 | 0.00 | 0.00 | 0.00 | 10867841.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 35577186.02 | 0.00 | 0.00 | 0.00 | 0.111104E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 86832592.08 | 0.00 | 0.00 | 0.00 | 0.278279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.203574E+09 | 0.00 | 0.00 | 0.00 | 0.672683E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.303086E+09 | 0.00 | 0.00 | 0.00 | 0.102098E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.302660E+09 | 0.00 | 0.00 | 0.00 | 0.100966E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.251857E+09 | 0.00 | 0.00 | 0.00 | 0.821970E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.156797E+09 | 0.00 | 0.00 | 0.00 | 0.500698E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 31313486.28 | 0.00 | 0.00 | 0.00 | 98658564.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 25372441.15 | 0.00 | 0.00 | 0.00 | 3892665.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.149149E+10 | 0.00 | 0.00 | 0.00 | 0.454486E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 19908112.50 | 0.00 | 0.00 | 0.00 | 3892665.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.303086E+09 | 0.00 | 0.00 | 0.00 | 0.102098E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT GNW
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 0.101932E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 83065830.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 47732916.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 17872592.17 | 0.00 | 0.00 | 0.00 | 39374868.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 70131855.82 | 0.00 | 0.00 | 0.00 | 0.224910E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.205598E+09 | 0.00 | 0.00 | 0.00 | 0.679066E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.290837E+09 | 0.00 | 0.00 | 0.00 | 0.979388E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.264064E+09 | 0.00 | 0.00 | 0.00 | 0.881404E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.172345E+09 | 0.00 | 0.00 | 0.00 | 0.563333E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 61679562.93 | 0.00 | 0.00 | 0.00 | 0.192759E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 23155381.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 93532284.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.143195E+10 | 0.00 | 0.00 | 0.00 | 0.356023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 17872592.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.290837E+09 | 0.00 | 0.00 | 0.00 | 0.979388E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT OFFICE
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 0.141110E+10 | 0.00 | 0.00 | 0.00 | 28860571.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.127454E+10 | 0.00 | 0.00 | 0.00 | 32389173.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.141110E+10 | 0.00 | 0.00 | 0.00 | 76026710.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.136558E+10 | 0.00 | 0.00 | 0.00 | 0.209446E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.141110E+10 | 0.00 | 0.00 | 0.00 | 0.345322E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.136558E+10 | 0.00 | 0.00 | 0.00 | 0.628510E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.141110E+10 | 0.00 | 0.00 | 0.00 | 0.788067E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.141110E+10 | 0.00 | 0.00 | 0.00 | 0.842458E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.136558E+10 | 0.00 | 0.00 | 0.00 | 0.638293E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.141110E+10 | 0.00 | 0.00 | 0.00 | 0.445434E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.136558E+10 | 0.00 | 0.00 | 0.00 | 0.186940E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.141110E+10 | 0.00 | 0.00 | 0.00 | 20666418.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.166146E+11 | 0.00 | 0.00 | 0.00 | 0.424241E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 0.127454E+10 | 0.00 | 0.00 | 0.00 | 20666418.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.141110E+10 | 0.00 | 0.00 | 0.00 | 0.842458E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT GNE
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 0.100875E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 83214820.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 43638685.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 19817993.66 | 0.00 | 0.00 | 0.00 | 48214525.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 78517837.25 | 0.00 | 0.00 | 0.00 | 0.251903E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.216453E+09 | 0.00 | 0.00 | 0.00 | 0.714420E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.305361E+09 | 0.00 | 0.00 | 0.00 | 0.102710E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.274813E+09 | 0.00 | 0.00 | 0.00 | 0.916243E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.176472E+09 | 0.00 | 0.00 | 0.00 | 0.576479E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 61214486.32 | 0.00 | 0.00 | 0.00 | 0.192574E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 21590301.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 93016727.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.147499E+10 | 0.00 | 0.00 | 0.00 | 0.372693E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 19817993.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.305361E+09 | 0.00 | 0.00 | 0.00 | 0.102710E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT GN1
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 68308894.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 55469032.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 27218360.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 10801691.33 | 0.00 | 0.00 | 0.00 | 26530038.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 61062424.81 | 0.00 | 0.00 | 0.00 | 0.195995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.171287E+09 | 0.00 | 0.00 | 0.00 | 0.565185E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.244210E+09 | 0.00 | 0.00 | 0.00 | 0.821574E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.217554E+09 | 0.00 | 0.00 | 0.00 | 0.725670E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.141856E+09 | 0.00 | 0.00 | 0.00 | 0.463555E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 47288833.09 | 0.00 | 0.00 | 0.00 | 0.152035E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 11481457.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 63487704.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.112003E+10 | 0.00 | 0.00 | 0.00 | 0.295054E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 10801691.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.244210E+09 | 0.00 | 0.00 | 0.00 | 0.821574E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT GN2
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 68324724.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 55587061.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 27071704.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 11241127.67 | 0.00 | 0.00 | 0.00 | 28021670.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 61937213.12 | 0.00 | 0.00 | 0.00 | 0.198806E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.171953E+09 | 0.00 | 0.00 | 0.00 | 0.567367E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.244952E+09 | 0.00 | 0.00 | 0.00 | 0.824050E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.218088E+09 | 0.00 | 0.00 | 0.00 | 0.727437E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.142093E+09 | 0.00 | 0.00 | 0.00 | 0.464327E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 47404771.11 | 0.00 | 0.00 | 0.00 | 0.152441E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 11487259.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 63544640.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.112368E+10 | 0.00 | 0.00 | 0.00 | 0.296245E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 11241127.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.244952E+09 | 0.00 | 0.00 | 0.00 | 0.824050E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT GS1
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 18454281.90 | 0.00 | 0.00 | 0.00 | 15102717.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 14245074.31 | 0.00 | 0.00 | 0.00 | 12225271.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 8316502.41 | 0.00 | 0.00 | 0.00 | 13276835.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 33293191.33 | 0.00 | 0.00 | 0.00 | 0.105242E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 79536759.11 | 0.00 | 0.00 | 0.00 | 0.254922E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.170116E+09 | 0.00 | 0.00 | 0.00 | 0.561627E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.257887E+09 | 0.00 | 0.00 | 0.00 | 0.867935E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.257937E+09 | 0.00 | 0.00 | 0.00 | 0.859873E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.223706E+09 | 0.00 | 0.00 | 0.00 | 0.729819E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.151900E+09 | 0.00 | 0.00 | 0.00 | 0.485409E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 46296054.21 | 0.00 | 0.00 | 0.00 | 0.146227E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 8230769.18 | 0.00 | 0.00 | 0.00 | 11045248.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.126992E+10 | 0.00 | 0.00 | 0.00 | 0.406270E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 8230769.18 | 0.00 | 0.00 | 0.00 | 11045248.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.257937E+09 | 0.00 | 0.00 | 0.00 | 0.867935E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT GS2
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 19811452.96 | 0.00 | 0.00 | 0.00 | 15963624.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 15127246.21 | 0.00 | 0.00 | 0.00 | 12832316.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 8871310.44 | 0.00 | 0.00 | 0.00 | 16343715.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 39162336.75 | 0.00 | 0.00 | 0.00 | 0.123776E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 91767439.21 | 0.00 | 0.00 | 0.00 | 0.294067E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.189423E+09 | 0.00 | 0.00 | 0.00 | 0.624641E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.285048E+09 | 0.00 | 0.00 | 0.00 | 0.957968E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.283514E+09 | 0.00 | 0.00 | 0.00 | 0.944059E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.245861E+09 | 0.00 | 0.00 | 0.00 | 0.801659E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.167753E+09 | 0.00 | 0.00 | 0.00 | 0.535984E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 50374363.54 | 0.00 | 0.00 | 0.00 | 0.159113E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 8671627.78 | 0.00 | 0.00 | 0.00 | 12300068.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.140538E+10 | 0.00 | 0.00 | 0.00 | 0.449871E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 8671627.78 | 0.00 | 0.00 | 0.00 | 12300068.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.285048E+09 | 0.00 | 0.00 | 0.00 | 0.957968E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT MSW
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 79242304.72 | 0.00 | 0.00 | 0.00 | 0.116683E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 75446918.95 | 0.00 | 0.00 | 0.00 | 0.163698E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 86743204.16 | 0.00 | 0.00 | 0.00 | 0.264722E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.241801E+09 | 0.00 | 0.00 | 0.00 | 0.763749E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.335771E+09 | 0.00 | 0.00 | 0.00 | 0.107424E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.543993E+09 | 0.00 | 0.00 | 0.00 | 0.179406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.709763E+09 | 0.00 | 0.00 | 0.00 | 0.239059E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.678575E+09 | 0.00 | 0.00 | 0.00 | 0.226487E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.536941E+09 | 0.00 | 0.00 | 0.00 | 0.175380E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.343792E+09 | 0.00 | 0.00 | 0.00 | 0.109339E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.105913E+09 | 0.00 | 0.00 | 0.00 | 0.330331E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 59132553.82 | 0.00 | 0.00 | 0.00 | 82566007.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.379711E+10 | 0.00 | 0.00 | 0.00 | 0.120927E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 59132553.82 | 0.00 | 0.00 | 0.00 | 82566007.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.709763E+09 | 0.00 | 0.00 | 0.00 | 0.239059E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT MNW
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 0.149894E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 98499022.57 | 0.00 | 0.00 | 0.00 | 110603.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 20201678.82 | 0.00 | 0.00 | 0.00 | 3863040.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.133456E+09 | 0.00 | 0.00 | 0.00 | 0.421767E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.294419E+09 | 0.00 | 0.00 | 0.00 | 0.942491E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.547531E+09 | 0.00 | 0.00 | 0.00 | 0.180488E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.682128E+09 | 0.00 | 0.00 | 0.00 | 0.229634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.595151E+09 | 0.00 | 0.00 | 0.00 | 0.198698E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.368529E+09 | 0.00 | 0.00 | 0.00 | 0.120518E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.132972E+09 | 0.00 | 0.00 | 0.00 | 0.408544E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 43109424.82 | 0.00 | 0.00 | 0.00 | 327215.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.160228E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.322612E+10 | 0.00 | 0.00 | 0.00 | 0.907049E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 20201678.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.682128E+09 | 0.00 | 0.00 | 0.00 | 0.229634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT MSE
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 77904665.70 | 0.00 | 0.00 | 0.00 | 0.111036E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 72713234.77 | 0.00 | 0.00 | 0.00 | 0.152102E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 91564650.81 | 0.00 | 0.00 | 0.00 | 0.281412E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.266223E+09 | 0.00 | 0.00 | 0.00 | 0.840709E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.359558E+09 | 0.00 | 0.00 | 0.00 | 0.115023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.567561E+09 | 0.00 | 0.00 | 0.00 | 0.187006E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.739248E+09 | 0.00 | 0.00 | 0.00 | 0.248620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.700600E+09 | 0.00 | 0.00 | 0.00 | 0.233493E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.544867E+09 | 0.00 | 0.00 | 0.00 | 0.177829E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.347079E+09 | 0.00 | 0.00 | 0.00 | 0.110449E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.104984E+09 | 0.00 | 0.00 | 0.00 | 0.327200E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 53796384.77 | 0.00 | 0.00 | 0.00 | 66511049.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.392610E+10 | 0.00 | 0.00 | 0.00 | 0.125032E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 53796384.77 | 0.00 | 0.00 | 0.00 | 66511049.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.739248E+09 | 0.00 | 0.00 | 0.00 | 0.248620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT MNE
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 0.146923E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 98766011.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 16654316.01 | 0.00 | 0.00 | 0.00 | 1433386.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.150865E+09 | 0.00 | 0.00 | 0.00 | 0.476611E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.317400E+09 | 0.00 | 0.00 | 0.00 | 0.101597E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.571218E+09 | 0.00 | 0.00 | 0.00 | 0.188119E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.711945E+09 | 0.00 | 0.00 | 0.00 | 0.239309E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.618311E+09 | 0.00 | 0.00 | 0.00 | 0.206097E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.377980E+09 | 0.00 | 0.00 | 0.00 | 0.123482E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.131257E+09 | 0.00 | 0.00 | 0.00 | 0.406352E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 39744381.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.158735E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.333980E+10 | 0.00 | 0.00 | 0.00 | 0.947043E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 16654316.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.711945E+09 | 0.00 | 0.00 | 0.00 | 0.239309E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT MN1
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 84376243.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 53487408.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 5710580.68 | 0.00 | 0.00 | 0.00 | 160938.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 98415379.59 | 0.00 | 0.00 | 0.00 | 0.311004E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.236113E+09 | 0.00 | 0.00 | 0.00 | 0.756104E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.429939E+09 | 0.00 | 0.00 | 0.00 | 0.141585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.545995E+09 | 0.00 | 0.00 | 0.00 | 0.183600E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.472870E+09 | 0.00 | 0.00 | 0.00 | 0.157713E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.298979E+09 | 0.00 | 0.00 | 0.00 | 0.977030E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.100737E+09 | 0.00 | 0.00 | 0.00 | 0.321619E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 14500373.66 | 0.00 | 0.00 | 0.00 | 69759.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 92864108.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.243399E+10 | 0.00 | 0.00 | 0.00 | 0.719496E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 5710580.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.545995E+09 | 0.00 | 0.00 | 0.00 | 0.183600E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT MN2
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 84591867.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 53794989.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 5682517.68 | 0.00 | 0.00 | 0.00 | 177904.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.100215E+09 | 0.00 | 0.00 | 0.00 | 0.316683E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.237580E+09 | 0.00 | 0.00 | 0.00 | 0.760801E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.431014E+09 | 0.00 | 0.00 | 0.00 | 0.141940E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.547251E+09 | 0.00 | 0.00 | 0.00 | 0.184020E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.473823E+09 | 0.00 | 0.00 | 0.00 | 0.158029E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.299427E+09 | 0.00 | 0.00 | 0.00 | 0.978497E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.101189E+09 | 0.00 | 0.00 | 0.00 | 0.323166E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 14558658.52 | 0.00 | 0.00 | 0.00 | 58173.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 93034922.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.244216E+10 | 0.00 | 0.00 | 0.00 | 0.721927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 5682517.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.547251E+09 | 0.00 | 0.00 | 0.00 | 0.184020E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT MS1
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 70827515.13 | 0.00 | 0.00 | 0.00 | 0.183094E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 65421832.62 | 0.00 | 0.00 | 0.00 | 0.197830E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 91158216.26 | 0.00 | 0.00 | 0.00 | 0.287316E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.213414E+09 | 0.00 | 0.00 | 0.00 | 0.673974E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.278565E+09 | 0.00 | 0.00 | 0.00 | 0.891313E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.426296E+09 | 0.00 | 0.00 | 0.00 | 0.140480E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.573912E+09 | 0.00 | 0.00 | 0.00 | 0.193123E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.556988E+09 | 0.00 | 0.00 | 0.00 | 0.185745E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.468689E+09 | 0.00 | 0.00 | 0.00 | 0.152991E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.329829E+09 | 0.00 | 0.00 | 0.00 | 0.105330E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.142550E+09 | 0.00 | 0.00 | 0.00 | 0.450076E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 53316663.04 | 0.00 | 0.00 | 0.00 | 0.156208E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.327097E+10 | 0.00 | 0.00 | 0.00 | 0.106165E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 53316663.04 | 0.00 | 0.00 | 0.00 | 0.156208E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.573912E+09 | 0.00 | 0.00 | 0.00 | 0.193123E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT MS2
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 71535625.96 | 0.00 | 0.00 | 0.00 | 0.185004E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 65637568.93 | 0.00 | 0.00 | 0.00 | 0.198504E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 92663829.95 | 0.00 | 0.00 | 0.00 | 0.292099E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.215156E+09 | 0.00 | 0.00 | 0.00 | 0.679470E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.280119E+09 | 0.00 | 0.00 | 0.00 | 0.896283E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.427400E+09 | 0.00 | 0.00 | 0.00 | 0.140844E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.575155E+09 | 0.00 | 0.00 | 0.00 | 0.193539E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.557880E+09 | 0.00 | 0.00 | 0.00 | 0.186040E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.469054E+09 | 0.00 | 0.00 | 0.00 | 0.153110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.330283E+09 | 0.00 | 0.00 | 0.00 | 0.105475E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.143185E+09 | 0.00 | 0.00 | 0.00 | 0.452081E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 53755378.98 | 0.00 | 0.00 | 0.00 | 0.157643E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.328182E+10 | 0.00 | 0.00 | 0.00 | 0.106512E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 53755378.98 | 0.00 | 0.00 | 0.00 | 0.157643E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.575155E+09 | 0.00 | 0.00 | 0.00 | 0.193539E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT TSW
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 0.139589E+09 | 0.00 | 0.00 | 0.00 | 0.102270E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.117108E+09 | 0.00 | 0.00 | 0.00 | 0.126977E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 98542139.74 | 0.00 | 0.00 | 0.00 | 0.166531E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.126809E+09 | 0.00 | 0.00 | 0.00 | 0.366856E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.174723E+09 | 0.00 | 0.00 | 0.00 | 0.548103E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.302367E+09 | 0.00 | 0.00 | 0.00 | 0.100136E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.399734E+09 | 0.00 | 0.00 | 0.00 | 0.135296E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.372122E+09 | 0.00 | 0.00 | 0.00 | 0.124737E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.268782E+09 | 0.00 | 0.00 | 0.00 | 0.880630E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.174289E+09 | 0.00 | 0.00 | 0.00 | 0.504850E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 96790200.17 | 0.00 | 0.00 | 0.00 | 0.160304E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.126868E+09 | 0.00 | 0.00 | 0.00 | 79498152.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.239772E+10 | 0.00 | 0.00 | 0.00 | 0.653770E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 96790200.17 | 0.00 | 0.00 | 0.00 | 79498152.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.399734E+09 | 0.00 | 0.00 | 0.00 | 0.135296E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT TNW
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 0.159903E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.117671E+09 | 0.00 | 0.00 | 0.00 | 4596467.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 69954909.76 | 0.00 | 0.00 | 0.00 | 21164748.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 82484670.38 | 0.00 | 0.00 | 0.00 | 0.215572E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.153472E+09 | 0.00 | 0.00 | 0.00 | 0.479790E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.303512E+09 | 0.00 | 0.00 | 0.00 | 0.100480E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.385446E+09 | 0.00 | 0.00 | 0.00 | 0.130372E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.328288E+09 | 0.00 | 0.00 | 0.00 | 0.110079E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.184139E+09 | 0.00 | 0.00 | 0.00 | 0.604192E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 84803367.83 | 0.00 | 0.00 | 0.00 | 0.188741E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 84195343.92 | 0.00 | 0.00 | 0.00 | 155719.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.167512E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.212138E+10 | 0.00 | 0.00 | 0.00 | 0.492353E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 69954909.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.385446E+09 | 0.00 | 0.00 | 0.00 | 0.130372E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT TSE
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 0.134930E+09 | 0.00 | 0.00 | 0.00 | 94236649.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.110615E+09 | 0.00 | 0.00 | 0.00 | 0.111719E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 93458329.12 | 0.00 | 0.00 | 0.00 | 0.161395E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.130556E+09 | 0.00 | 0.00 | 0.00 | 0.383701E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.180521E+09 | 0.00 | 0.00 | 0.00 | 0.569636E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.312009E+09 | 0.00 | 0.00 | 0.00 | 0.103235E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.413929E+09 | 0.00 | 0.00 | 0.00 | 0.139807E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.382562E+09 | 0.00 | 0.00 | 0.00 | 0.127964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.271478E+09 | 0.00 | 0.00 | 0.00 | 0.888401E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.172512E+09 | 0.00 | 0.00 | 0.00 | 0.501563E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 92210937.88 | 0.00 | 0.00 | 0.00 | 0.150395E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.119468E+09 | 0.00 | 0.00 | 0.00 | 64134196.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.241425E+10 | 0.00 | 0.00 | 0.00 | 0.663524E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 92210937.88 | 0.00 | 0.00 | 0.00 | 64134196.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.413929E+09 | 0.00 | 0.00 | 0.00 | 0.139807E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT TNE
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 0.156531E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.114427E+09 | 0.00 | 0.00 | 0.00 | 767569.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 60333304.25 | 0.00 | 0.00 | 0.00 | 8360975.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 82416471.41 | 0.00 | 0.00 | 0.00 | 0.222132E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.159792E+09 | 0.00 | 0.00 | 0.00 | 0.502913E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.313953E+09 | 0.00 | 0.00 | 0.00 | 0.103812E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.400104E+09 | 0.00 | 0.00 | 0.00 | 0.135040E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.339770E+09 | 0.00 | 0.00 | 0.00 | 0.113664E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.187245E+09 | 0.00 | 0.00 | 0.00 | 0.613505E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 77428529.66 | 0.00 | 0.00 | 0.00 | 0.172718E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 80812365.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.165321E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.213813E+10 | 0.00 | 0.00 | 0.00 | 0.504555E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 60333304.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.400104E+09 | 0.00 | 0.00 | 0.00 | 0.135040E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT TN1
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 0.114209E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 81911344.77 | 0.00 | 0.00 | 0.00 | 54880.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 39696846.20 | 0.00 | 0.00 | 0.00 | 2526480.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 50909733.68 | 0.00 | 0.00 | 0.00 | 0.137828E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.116431E+09 | 0.00 | 0.00 | 0.00 | 0.368693E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.240889E+09 | 0.00 | 0.00 | 0.00 | 0.797433E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.316342E+09 | 0.00 | 0.00 | 0.00 | 0.106847E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.266951E+09 | 0.00 | 0.00 | 0.00 | 0.893988E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.145772E+09 | 0.00 | 0.00 | 0.00 | 0.478043E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 54887943.71 | 0.00 | 0.00 | 0.00 | 0.127419E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 56426938.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.121798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.160622E+10 | 0.00 | 0.00 | 0.00 | 0.387446E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 39696846.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.316342E+09 | 0.00 | 0.00 | 0.00 | 0.106847E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT TN2
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 0.114345E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 82099123.80 | 0.00 | 0.00 | 0.00 | 64885.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 39644125.44 | 0.00 | 0.00 | 0.00 | 2701378.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 51662802.01 | 0.00 | 0.00 | 0.00 | 0.140408E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.117261E+09 | 0.00 | 0.00 | 0.00 | 0.371503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.241605E+09 | 0.00 | 0.00 | 0.00 | 0.799789E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.317046E+09 | 0.00 | 0.00 | 0.00 | 0.107082E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.267555E+09 | 0.00 | 0.00 | 0.00 | 0.895969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.146278E+09 | 0.00 | 0.00 | 0.00 | 0.479691E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 55147492.71 | 0.00 | 0.00 | 0.00 | 0.128280E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 56546400.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.121875E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.161107E+10 | 0.00 | 0.00 | 0.00 | 0.388923E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 39644125.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.317046E+09 | 0.00 | 0.00 | 0.00 | 0.107082E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT TS1
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 97265284.61 | 0.00 | 0.00 | 0.00 | 0.101612E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 80680280.89 | 0.00 | 0.00 | 0.00 | 0.112738E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 64045149.37 | 0.00 | 0.00 | 0.00 | 0.130252E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 94223752.92 | 0.00 | 0.00 | 0.00 | 0.284661E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.137127E+09 | 0.00 | 0.00 | 0.00 | 0.435302E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.239324E+09 | 0.00 | 0.00 | 0.00 | 0.792902E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.330752E+09 | 0.00 | 0.00 | 0.00 | 0.111815E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.311271E+09 | 0.00 | 0.00 | 0.00 | 0.104222E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.232258E+09 | 0.00 | 0.00 | 0.00 | 0.760484E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.148479E+09 | 0.00 | 0.00 | 0.00 | 0.448580E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 72580231.15 | 0.00 | 0.00 | 0.00 | 0.156395E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 87490707.59 | 0.00 | 0.00 | 0.00 | 84736395.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.189550E+10 | 0.00 | 0.00 | 0.00 | 0.546804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 64045149.37 | 0.00 | 0.00 | 0.00 | 84736395.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.330752E+09 | 0.00 | 0.00 | 0.00 | 0.111815E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT TS2
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 97758156.34 | 0.00 | 0.00 | 0.00 | 0.102865E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 81178662.19 | 0.00 | 0.00 | 0.00 | 0.113890E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 64713334.70 | 0.00 | 0.00 | 0.00 | 0.132441E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 95370641.71 | 0.00 | 0.00 | 0.00 | 0.288385E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.138003E+09 | 0.00 | 0.00 | 0.00 | 0.438254E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.240086E+09 | 0.00 | 0.00 | 0.00 | 0.795406E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.331446E+09 | 0.00 | 0.00 | 0.00 | 0.112047E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.311818E+09 | 0.00 | 0.00 | 0.00 | 0.104401E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.232610E+09 | 0.00 | 0.00 | 0.00 | 0.761618E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.149048E+09 | 0.00 | 0.00 | 0.00 | 0.450345E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 73161302.78 | 0.00 | 0.00 | 0.00 | 0.158044E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 87950997.30 | 0.00 | 0.00 | 0.00 | 85924463.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.190315E+10 | 0.00 | 0.00 | 0.00 | 0.549165E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 64713334.70 | 0.00 | 0.00 | 0.00 | 85924463.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.331446E+09 | 0.00 | 0.00 | 0.00 | 0.112047E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: G SW APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.943855E+09 | 0.00 | 0.00 | 102262.50 | 0.00 | 0.366764E+09 | 34240537.94 | 0.00 | 0.35 |
| February | 0.746928E+09 | 0.00 | 0.00 | 126538.88 | 0.00 | 0.331582E+09 | 29525587.65 | 0.00 | 0.35 |
| March | 0.746957E+09 | 0.00 | 0.00 | 119090.84 | 0.00 | 0.152272E+09 | 25875588.15 | 0.00 | 0.35 |
| April | 0.536354E+09 | 5199919.94 | 0.00 | 598264.05 | 0.00 | 0.00 | 0.110753E+09 | 0.00 | 0.35 |
| May | 0.274344E+09 | 23771372.72 | 0.00 | 1078926.18 | 0.00 | 0.00 | 0.183043E+09 | 0.00 | 0.35 |
| June | 53345503.88 | 0.158138E+09 | 0.00 | 1357358.34 | 0.00 | 0.00 | 0.168324E+09 | 0.00 | 0.35 |
| July | 0.00 | 0.324919E+09 | 0.00 | 819815.55 | 0.00 | 0.00 | 32186340.31 | 0.00 | 0.35 |
| August | 0.00 | 0.229691E+09 | 0.00 | 1461861.26 | 0.00 | 0.00 | 72166999.75 | 0.00 | 0.35 |
| September | 0.00 | 69440252.58 | 0.00 | 3070276.47 | 0.00 | 0.00 | 0.255941E+09 | 0.00 | 0.35 |
| October | 0.240674E+09 | 10480305.50 | 0.00 | 3651016.93 | 0.00 | 0.00 | 0.487309E+09 | 0.00 | 0.35 |
| November | 0.771044E+09 | 0.00 | 0.00 | 1392766.40 | 0.00 | 0.00 | 0.352454E+09 | 0.00 | 0.35 |
| December | 0.116201E+10 | 0.00 | 0.00 | 95429.68 | 0.00 | 0.178192E+09 | 49505630.36 | 0.00 | 0.35 |
| Annual Sum or Average | 0.547551E+10 | 0.821639E+09 | 0.00 | 13873607.08 | 0.00 | 0.102881E+10 | 0.180132E+10 | 0.00 | 0.35 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 95429.68 | 0.00 | 0.00 | 25875588.15 | 0.00 | 0.35 |
| Maximum of Months | 0.116201E+10 | 0.324919E+09 | 0.00 | 3651016.93 | 0.00 | 0.366764E+09 | 0.487309E+09 | 0.00 | 0.35 |
Report: MechanicalVentilationLoadsMonthly
For: G NW APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.148963E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114739E+10 | 0.00 | 0.00 | 0.35 |
| February | 0.157430E+09 | 0.00 | 0.00 | 0.00 | 9645.50 | 0.907424E+09 | 0.00 | 0.00 | 0.35 |
| March | 0.296460E+09 | 0.00 | 0.00 | 0.00 | 4076.64 | 0.575842E+09 | 0.00 | 0.00 | 0.35 |
| April | 0.526747E+09 | 3718554.09 | 0.00 | 162950.10 | 733401.61 | 42463503.61 | 28410741.24 | 0.00 | 0.35 |
| May | 0.300741E+09 | 22514143.60 | 0.00 | 850681.29 | 109278.62 | 0.00 | 0.149720E+09 | 0.00 | 0.35 |
| June | 52638812.93 | 0.154290E+09 | 0.00 | 1426939.39 | 0.00 | 0.00 | 0.169025E+09 | 0.00 | 0.35 |
| July | 0.00 | 0.321972E+09 | 0.00 | 822584.12 | 0.00 | 0.00 | 33029177.72 | 0.00 | 0.35 |
| August | 0.00 | 0.217418E+09 | 0.00 | 1352421.25 | 0.00 | 0.00 | 77611597.21 | 0.00 | 0.35 |
| September | 391331.93 | 61398755.06 | 0.00 | 2259070.32 | 0.00 | 0.00 | 0.267625E+09 | 0.00 | 0.35 |
| October | 0.471317E+09 | 8461883.22 | 0.00 | 1282866.34 | 0.00 | 0.00 | 0.225396E+09 | 0.00 | 0.35 |
| November | 0.785196E+09 | 0.00 | 0.00 | 207.96 | 0.00 | 0.204123E+09 | 447828.91 | 0.00 | 0.35 |
| December | 0.231256E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110378E+10 | 0.00 | 0.00 | 0.35 |
| Annual Sum or Average | 0.297114E+10 | 0.789774E+09 | 0.00 | 8157720.77 | 856402.36 | 0.398102E+10 | 0.951266E+09 | 0.00 | 0.35 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
| Maximum of Months | 0.785196E+09 | 0.321972E+09 | 0.00 | 2259070.32 | 733401.61 | 0.114739E+10 | 0.267625E+09 | 0.00 | 0.35 |
Report: MechanicalVentilationLoadsMonthly
For: OFFICE
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.177117E+10 | 0.00 | 0.00 | 157633.25 | 0.00 | 80034385.06 | 0.119824E+09 | 0.00 | 0.51 |
| February | 0.155581E+10 | 0.00 | 0.00 | 164578.64 | 0.00 | 10312532.97 | 71825293.61 | 0.00 | 0.51 |
| March | 0.132779E+10 | 0.00 | 0.00 | 354008.80 | 0.00 | 40287.35 | 0.157916E+09 | 0.00 | 0.52 |
| April | 0.913365E+09 | 128257.78 | 0.00 | 1132778.53 | 3439.86 | 0.00 | 0.194258E+09 | 0.00 | 0.52 |
| May | 0.693172E+09 | 3407243.46 | 0.00 | 1766562.75 | 369248.30 | 0.00 | 0.154514E+09 | 0.00 | 0.52 |
| June | 0.428940E+09 | 77978733.05 | 0.00 | 1313361.62 | 20340444.92 | 0.00 | 44107951.70 | 0.00 | 0.52 |
| July | 0.314246E+09 | 0.196224E+09 | 0.00 | 636312.56 | 23068074.35 | 0.00 | 16052056.04 | 0.00 | 0.53 |
| August | 0.363736E+09 | 0.159204E+09 | 0.00 | 1158151.86 | 9218777.95 | 0.00 | 33146773.62 | 0.00 | 0.53 |
| September | 0.627996E+09 | 42473181.51 | 0.00 | 1990052.07 | 457545.09 | 0.00 | 58053847.09 | 0.00 | 0.52 |
| October | 0.105799E+10 | 7457358.79 | 0.00 | 2528148.12 | 72065.62 | 0.00 | 0.236441E+09 | 0.00 | 0.52 |
| November | 0.140501E+10 | 0.00 | 0.00 | 1248177.91 | 0.00 | 0.00 | 0.324158E+09 | 0.00 | 0.51 |
| December | 0.190904E+10 | 0.00 | 0.00 | 165014.71 | 0.00 | 750622.70 | 0.165899E+09 | 0.00 | 0.51 |
| Annual Sum or Average | 0.123683E+11 | 0.486873E+09 | 0.00 | 12614780.84 | 53529596.09 | 91137828.07 | 0.157620E+10 | 0.00 | 0.52 |
| Minimum of Months | 0.314246E+09 | 0.00 | 0.00 | 157633.25 | 0.00 | 0.00 | 16052056.04 | 0.00 | 0.51 |
| Maximum of Months | 0.190904E+10 | 0.196224E+09 | 0.00 | 2528148.12 | 23068074.35 | 80034385.06 | 0.324158E+09 | 0.00 | 0.53 |
Report: MechanicalVentilationLoadsMonthly
For: G NE APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.154553E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114132E+10 | 0.00 | 0.00 | 0.35 |
| February | 0.150982E+09 | 0.00 | 0.00 | 0.00 | 30642.00 | 0.912486E+09 | 0.00 | 0.00 | 0.35 |
| March | 0.351197E+09 | 0.00 | 0.00 | 0.00 | 1835.28 | 0.520624E+09 | 0.00 | 0.00 | 0.35 |
| April | 0.522965E+09 | 3706827.22 | 0.00 | 247779.25 | 686682.39 | 38528595.51 | 46438742.27 | 0.00 | 0.35 |
| May | 0.259675E+09 | 22494239.63 | 0.00 | 1177258.16 | 46710.48 | 0.00 | 0.195402E+09 | 0.00 | 0.35 |
| June | 42949982.38 | 0.155222E+09 | 0.00 | 1669634.18 | 0.00 | 0.00 | 0.178063E+09 | 0.00 | 0.35 |
| July | 0.00 | 0.333137E+09 | 0.00 | 857072.57 | 0.00 | 0.00 | 31030160.58 | 0.00 | 0.35 |
| August | 0.00 | 0.225832E+09 | 0.00 | 1466351.59 | 0.00 | 0.00 | 76591524.83 | 0.00 | 0.35 |
| September | 531254.24 | 63358341.30 | 0.00 | 2391005.34 | 0.00 | 0.00 | 0.266992E+09 | 0.00 | 0.35 |
| October | 0.457933E+09 | 8931102.43 | 0.00 | 1289604.58 | 0.00 | 0.00 | 0.240989E+09 | 0.00 | 0.35 |
| November | 0.798646E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.188831E+09 | 0.00 | 0.00 | 0.35 |
| December | 0.187613E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114691E+10 | 0.00 | 0.00 | 0.35 |
| Annual Sum or Average | 0.292705E+10 | 0.812681E+09 | 0.00 | 9098705.66 | 765870.16 | 0.394870E+10 | 0.103551E+10 | 0.00 | 0.35 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
| Maximum of Months | 0.798646E+09 | 0.333137E+09 | 0.00 | 2391005.34 | 686682.39 | 0.114691E+10 | 0.266992E+09 | 0.00 | 0.35 |
Report: MechanicalVentilationLoadsMonthly
For: G N1 APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.389956E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.911270E+09 | 0.00 | 0.00 | 0.35 |
| February | 0.379673E+09 | 0.00 | 0.00 | 0.00 | 36734.11 | 0.689282E+09 | 0.00 | 0.00 | 0.35 |
| March | 0.661202E+09 | 0.00 | 0.00 | 0.00 | 8243.17 | 0.216529E+09 | 0.00 | 0.00 | 0.35 |
| April | 0.576784E+09 | 3455708.59 | 0.00 | 127233.73 | 1163707.27 | 2824397.12 | 34037498.67 | 0.00 | 0.35 |
| May | 0.238667E+09 | 21432139.01 | 0.00 | 1010765.28 | 191637.48 | 0.00 | 0.227201E+09 | 0.00 | 0.35 |
| June | 19155290.56 | 0.151522E+09 | 0.00 | 1473381.37 | 0.00 | 0.00 | 0.205144E+09 | 0.00 | 0.35 |
| July | 0.00 | 0.315392E+09 | 0.00 | 803252.07 | 0.00 | 0.00 | 32394029.46 | 0.00 | 0.35 |
| August | 0.00 | 0.209451E+09 | 0.00 | 1325769.68 | 0.00 | 0.00 | 79537384.97 | 0.00 | 0.35 |
| September | 0.00 | 58655112.94 | 0.00 | 2117263.43 | 0.00 | 0.00 | 0.270881E+09 | 0.00 | 0.35 |
| October | 0.430681E+09 | 7996753.22 | 0.00 | 1164936.41 | 0.00 | 0.00 | 0.281062E+09 | 0.00 | 0.35 |
| November | 0.977272E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 24599204.05 | 0.00 | 0.00 | 0.35 |
| December | 0.571963E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.767684E+09 | 0.00 | 0.00 | 0.35 |
| Annual Sum or Average | 0.424535E+10 | 0.767905E+09 | 0.00 | 8022601.96 | 1400322.03 | 0.261219E+10 | 0.113026E+10 | 0.00 | 0.35 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
| Maximum of Months | 0.977272E+09 | 0.315392E+09 | 0.00 | 2117263.43 | 1163707.27 | 0.911270E+09 | 0.281062E+09 | 0.00 | 0.35 |
Report: MechanicalVentilationLoadsMonthly
For: G N2 APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.391686E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.909532E+09 | 0.00 | 0.00 | 0.35 |
| February | 0.376368E+09 | 0.00 | 0.00 | 0.00 | 36918.44 | 0.692542E+09 | 0.00 | 0.00 | 0.35 |
| March | 0.664586E+09 | 0.00 | 0.00 | 0.00 | 7720.06 | 0.213314E+09 | 0.00 | 0.00 | 0.35 |
| April | 0.574913E+09 | 3454820.97 | 0.00 | 136234.67 | 1141507.36 | 2534942.90 | 37447267.93 | 0.00 | 0.35 |
| May | 0.234982E+09 | 21467595.37 | 0.00 | 1035844.37 | 145032.28 | 0.00 | 0.231473E+09 | 0.00 | 0.35 |
| June | 18022777.02 | 0.151548E+09 | 0.00 | 1483498.97 | 0.00 | 0.00 | 0.206213E+09 | 0.00 | 0.35 |
| July | 0.00 | 0.315864E+09 | 0.00 | 804343.33 | 0.00 | 0.00 | 32246034.58 | 0.00 | 0.35 |
| August | 0.00 | 0.209771E+09 | 0.00 | 1327866.18 | 0.00 | 0.00 | 79479446.90 | 0.00 | 0.35 |
| September | 0.00 | 58732619.66 | 0.00 | 2119313.79 | 0.00 | 0.00 | 0.270874E+09 | 0.00 | 0.35 |
| October | 0.429192E+09 | 8015495.11 | 0.00 | 1166995.62 | 0.00 | 0.00 | 0.282830E+09 | 0.00 | 0.35 |
| November | 0.977284E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 24599184.92 | 0.00 | 0.00 | 0.35 |
| December | 0.570840E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.768788E+09 | 0.00 | 0.00 | 0.35 |
| Annual Sum or Average | 0.423787E+10 | 0.768853E+09 | 0.00 | 8074096.94 | 1331178.13 | 0.261131E+10 | 0.114056E+10 | 0.00 | 0.35 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
| Maximum of Months | 0.977284E+09 | 0.315864E+09 | 0.00 | 2119313.79 | 1141507.36 | 0.909532E+09 | 0.282830E+09 | 0.00 | 0.35 |
Report: MechanicalVentilationLoadsMonthly
For: G S1 APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.117430E+10 | 0.00 | 0.00 | 278003.29 | 0.00 | 0.108605E+09 | 0.101201E+09 | 0.00 | 0.35 |
| February | 0.104952E+10 | 0.00 | 0.00 | 176347.39 | 0.00 | 29737684.38 | 58715948.61 | 0.00 | 0.35 |
| March | 0.888267E+09 | 0.00 | 0.00 | 187878.27 | 0.00 | 15041938.00 | 62130999.23 | 0.00 | 0.35 |
| April | 0.480354E+09 | 5134668.36 | 0.00 | 719259.74 | 0.00 | 0.00 | 0.196738E+09 | 0.00 | 0.35 |
| May | 0.199029E+09 | 22854860.17 | 0.00 | 1292094.26 | 0.00 | 0.00 | 0.273427E+09 | 0.00 | 0.35 |
| June | 21202791.22 | 0.155612E+09 | 0.00 | 1407092.14 | 0.00 | 0.00 | 0.202987E+09 | 0.00 | 0.35 |
| July | 0.00 | 0.319603E+09 | 0.00 | 803860.66 | 0.00 | 0.00 | 31142017.66 | 0.00 | 0.35 |
| August | 0.00 | 0.224249E+09 | 0.00 | 1429308.07 | 0.00 | 0.00 | 72804171.70 | 0.00 | 0.35 |
| September | 0.00 | 67918733.92 | 0.00 | 2992702.94 | 0.00 | 0.00 | 0.256760E+09 | 0.00 | 0.35 |
| October | 0.170772E+09 | 10334713.09 | 0.00 | 3900735.13 | 0.00 | 0.00 | 0.571088E+09 | 0.00 | 0.35 |
| November | 0.597572E+09 | 0.00 | 0.00 | 2183972.82 | 0.00 | 0.00 | 0.567224E+09 | 0.00 | 0.35 |
| December | 0.131522E+10 | 0.00 | 0.00 | 261913.05 | 0.00 | 5205836.95 | 0.112533E+09 | 0.00 | 0.35 |
| Annual Sum or Average | 0.589624E+10 | 0.805708E+09 | 0.00 | 15633167.75 | 0.00 | 0.158591E+09 | 0.250675E+10 | 0.00 | 0.35 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 176347.39 | 0.00 | 0.00 | 31142017.66 | 0.00 | 0.35 |
| Maximum of Months | 0.131522E+10 | 0.319603E+09 | 0.00 | 3900735.13 | 0.00 | 0.108605E+09 | 0.571088E+09 | 0.00 | 0.35 |
Report: MechanicalVentilationLoadsMonthly
For: G S2 APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.114768E+10 | 0.00 | 0.00 | 290407.06 | 0.00 | 0.134353E+09 | 0.102368E+09 | 0.00 | 0.35 |
| February | 0.103770E+10 | 0.00 | 0.00 | 183142.53 | 0.00 | 41200633.83 | 59391496.84 | 0.00 | 0.35 |
| March | 0.888444E+09 | 0.00 | 0.00 | 221345.59 | 0.00 | 13140473.60 | 69769705.79 | 0.00 | 0.35 |
| April | 0.447702E+09 | 5129062.41 | 0.00 | 903780.96 | 0.00 | 0.00 | 0.235228E+09 | 0.00 | 0.35 |
| May | 0.161650E+09 | 22865202.63 | 0.00 | 1585946.43 | 0.00 | 0.00 | 0.311921E+09 | 0.00 | 0.35 |
| June | 13534826.26 | 0.156324E+09 | 0.00 | 1646136.83 | 0.00 | 0.00 | 0.208005E+09 | 0.00 | 0.35 |
| July | 0.00 | 0.330770E+09 | 0.00 | 831743.46 | 0.00 | 0.00 | 25724133.00 | 0.00 | 0.35 |
| August | 0.00 | 0.231213E+09 | 0.00 | 1575030.75 | 0.00 | 0.00 | 66171878.37 | 0.00 | 0.35 |
| September | 0.00 | 69476125.89 | 0.00 | 3324969.91 | 0.00 | 0.00 | 0.250134E+09 | 0.00 | 0.35 |
| October | 0.158913E+09 | 10546295.81 | 0.00 | 4289764.09 | 0.00 | 0.00 | 0.582694E+09 | 0.00 | 0.35 |
| November | 0.571905E+09 | 0.00 | 0.00 | 2337718.94 | 0.00 | 0.00 | 0.595301E+09 | 0.00 | 0.35 |
| December | 0.130562E+10 | 0.00 | 0.00 | 279815.49 | 0.00 | 5205807.88 | 0.123289E+09 | 0.00 | 0.35 |
| Annual Sum or Average | 0.573315E+10 | 0.826324E+09 | 0.00 | 17469802.04 | 0.00 | 0.193900E+09 | 0.263000E+10 | 0.00 | 0.35 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 183142.53 | 0.00 | 0.00 | 25724133.00 | 0.00 | 0.35 |
| Maximum of Months | 0.130562E+10 | 0.330770E+09 | 0.00 | 4289764.09 | 0.00 | 0.134353E+09 | 0.595301E+09 | 0.00 | 0.35 |
Report: MechanicalVentilationLoadsMonthly
For: M SW APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.205874E+10 | 0.00 | 0.00 | 1528982.87 | 0.00 | 0.386866E+09 | 0.311125E+09 | 0.00 | 0.35 |
| February | 0.177753E+10 | 0.00 | 0.00 | 1877926.65 | 0.00 | 0.196039E+09 | 0.333389E+09 | 0.00 | 0.35 |
| March | 0.153838E+10 | 0.00 | 0.00 | 2648068.89 | 0.00 | 25290720.63 | 0.449961E+09 | 0.00 | 0.35 |
| April | 0.552006E+09 | 10472157.05 | 0.00 | 5419708.22 | 0.00 | 0.00 | 0.827118E+09 | 0.00 | 0.35 |
| May | 0.243235E+09 | 49454679.53 | 0.00 | 5217236.89 | 0.00 | 0.00 | 0.683213E+09 | 0.00 | 0.35 |
| June | 45268038.77 | 0.322744E+09 | 0.00 | 3978546.85 | 0.00 | 0.00 | 0.381339E+09 | 0.00 | 0.35 |
| July | 0.00 | 0.665929E+09 | 0.00 | 1757546.96 | 0.00 | 0.00 | 57993859.46 | 0.00 | 0.35 |
| August | 0.00 | 0.463927E+09 | 0.00 | 3046831.28 | 0.00 | 0.00 | 0.144209E+09 | 0.00 | 0.35 |
| September | 2097488.77 | 0.140420E+09 | 0.00 | 5870283.40 | 0.00 | 0.00 | 0.515231E+09 | 0.00 | 0.35 |
| October | 0.579449E+09 | 21049746.97 | 0.00 | 7369364.43 | 0.00 | 14222145.87 | 0.846005E+09 | 0.00 | 0.35 |
| November | 0.146115E+10 | 0.00 | 0.00 | 3949198.86 | 0.00 | 0.00 | 0.770565E+09 | 0.00 | 0.35 |
| December | 0.222004E+10 | 0.00 | 0.00 | 1242421.29 | 0.00 | 0.247912E+09 | 0.368399E+09 | 0.00 | 0.35 |
| Annual Sum or Average | 0.104779E+11 | 0.167400E+10 | 0.00 | 43906116.59 | 0.00 | 0.870329E+09 | 0.568855E+10 | 0.00 | 0.35 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 1242421.29 | 0.00 | 0.00 | 57993859.46 | 0.00 | 0.35 |
| Maximum of Months | 0.222004E+10 | 0.665929E+09 | 0.00 | 7369364.43 | 0.00 | 0.386866E+09 | 0.846005E+09 | 0.00 | 0.35 |
Report: MechanicalVentilationLoadsMonthly
For: M NW APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.848844E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.174641E+10 | 0.00 | 0.00 | 0.35 |
| February | 0.106516E+10 | 0.00 | 0.00 | 6506.77 | 0.00 | 0.108592E+10 | 3701956.82 | 0.00 | 0.35 |
| March | 0.170134E+10 | 0.00 | 0.00 | 51638.45 | 0.00 | 0.136373E+09 | 20126365.73 | 0.00 | 0.35 |
| April | 0.825461E+09 | 8465300.49 | 0.00 | 2971593.58 | 0.00 | 0.00 | 0.521116E+09 | 0.00 | 0.35 |
| May | 0.269567E+09 | 47481588.52 | 0.00 | 4705085.22 | 0.00 | 0.00 | 0.655050E+09 | 0.00 | 0.35 |
| June | 42688905.42 | 0.315626E+09 | 0.00 | 4180980.97 | 0.00 | 0.00 | 0.383620E+09 | 0.00 | 0.35 |
| July | 0.00 | 0.660847E+09 | 0.00 | 1767265.90 | 0.00 | 0.00 | 59140669.81 | 0.00 | 0.35 |
| August | 0.00 | 0.441051E+09 | 0.00 | 2877221.66 | 0.00 | 0.00 | 0.152058E+09 | 0.00 | 0.35 |
| September | 4089308.46 | 0.124411E+09 | 0.00 | 4400775.73 | 0.00 | 0.00 | 0.532525E+09 | 0.00 | 0.35 |
| October | 0.926820E+09 | 17200988.29 | 0.00 | 2531385.66 | 0.00 | 57092584.00 | 0.394092E+09 | 0.00 | 0.35 |
| November | 0.160601E+10 | 0.00 | 0.00 | 25109.23 | 0.00 | 0.373667E+09 | 12135299.83 | 0.00 | 0.35 |
| December | 0.794473E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.187178E+10 | 0.00 | 0.00 | 0.35 |
| Annual Sum or Average | 0.808445E+10 | 0.161508E+10 | 0.00 | 23517563.18 | 0.00 | 0.527125E+10 | 0.273357E+10 | 0.00 | 0.35 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
| Maximum of Months | 0.170134E+10 | 0.660847E+09 | 0.00 | 4705085.22 | 0.00 | 0.187178E+10 | 0.655050E+09 | 0.00 | 0.35 |
Report: MechanicalVentilationLoadsMonthly
For: M SE APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.203561E+10 | 0.00 | 0.00 | 1420724.69 | 0.00 | 0.383614E+09 | 0.344068E+09 | 0.00 | 0.35 |
| February | 0.174745E+10 | 0.00 | 0.00 | 1698951.57 | 0.00 | 0.223861E+09 | 0.335361E+09 | 0.00 | 0.35 |
| March | 0.147172E+10 | 0.00 | 0.00 | 2773144.03 | 0.00 | 20516948.34 | 0.535173E+09 | 0.00 | 0.35 |
| April | 0.471174E+09 | 10362219.33 | 0.00 | 6314665.96 | 0.00 | 0.00 | 0.913459E+09 | 0.00 | 0.35 |
| May | 0.184316E+09 | 49175052.43 | 0.00 | 6331413.58 | 0.00 | 0.00 | 0.741135E+09 | 0.00 | 0.35 |
| June | 34849159.43 | 0.324690E+09 | 0.00 | 4649350.62 | 0.00 | 0.00 | 0.389909E+09 | 0.00 | 0.35 |
| July | 0.00 | 0.689562E+09 | 0.00 | 1827860.47 | 0.00 | 0.00 | 55960721.36 | 0.00 | 0.35 |
| August | 0.00 | 0.481290E+09 | 0.00 | 3316683.17 | 0.00 | 0.00 | 0.142467E+09 | 0.00 | 0.35 |
| September | 1686270.56 | 0.143953E+09 | 0.00 | 6298787.69 | 0.00 | 0.00 | 0.514123E+09 | 0.00 | 0.35 |
| October | 0.549878E+09 | 21791355.05 | 0.00 | 7605991.48 | 0.00 | 14222021.61 | 0.876715E+09 | 0.00 | 0.35 |
| November | 0.140478E+10 | 0.00 | 0.00 | 3964856.23 | 0.00 | 0.00 | 0.831771E+09 | 0.00 | 0.35 |
| December | 0.219228E+10 | 0.00 | 0.00 | 1073061.90 | 0.00 | 0.262079E+09 | 0.386915E+09 | 0.00 | 0.35 |
| Annual Sum or Average | 0.100937E+11 | 0.172082E+10 | 0.00 | 47275491.40 | 0.00 | 0.904294E+09 | 0.606706E+10 | 0.00 | 0.35 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 1073061.90 | 0.00 | 0.00 | 55960721.36 | 0.00 | 0.35 |
| Maximum of Months | 0.219228E+10 | 0.689562E+09 | 0.00 | 7605991.48 | 0.00 | 0.383614E+09 | 0.913459E+09 | 0.00 | 0.35 |
Report: MechanicalVentilationLoadsMonthly
For: M NE APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.923169E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.166697E+10 | 0.00 | 0.00 | 0.35 |
| February | 0.108268E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106660E+10 | 0.00 | 0.00 | 0.35 |
| March | 0.173850E+10 | 0.00 | 0.00 | 25446.68 | 0.00 | 0.122673E+09 | 13397602.84 | 0.00 | 0.35 |
| April | 0.701016E+09 | 8380847.06 | 0.00 | 3690643.02 | 0.00 | 0.00 | 0.661169E+09 | 0.00 | 0.35 |
| May | 0.203547E+09 | 47309424.60 | 0.00 | 5773963.55 | 0.00 | 0.00 | 0.721654E+09 | 0.00 | 0.35 |
| June | 33347873.83 | 0.317733E+09 | 0.00 | 4889562.89 | 0.00 | 0.00 | 0.390998E+09 | 0.00 | 0.35 |
| July | 0.00 | 0.684640E+09 | 0.00 | 1835799.56 | 0.00 | 0.00 | 57177346.58 | 0.00 | 0.35 |
| August | 0.00 | 0.460696E+09 | 0.00 | 3180031.02 | 0.00 | 0.00 | 0.150186E+09 | 0.00 | 0.35 |
| September | 5399079.76 | 0.128950E+09 | 0.00 | 4848993.97 | 0.00 | 0.00 | 0.529180E+09 | 0.00 | 0.35 |
| October | 0.898687E+09 | 18252246.02 | 0.00 | 2631604.77 | 0.00 | 40776076.59 | 0.444097E+09 | 0.00 | 0.35 |
| November | 0.163812E+10 | 0.00 | 0.00 | 21.03 | 0.00 | 0.348289E+09 | 1062222.87 | 0.00 | 0.35 |
| December | 0.934739E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.172774E+10 | 0.00 | 0.00 | 0.35 |
| Annual Sum or Average | 0.815921E+10 | 0.166596E+10 | 0.00 | 26876066.48 | 0.00 | 0.497305E+10 | 0.296892E+10 | 0.00 | 0.35 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
| Maximum of Months | 0.173850E+10 | 0.684640E+09 | 0.00 | 5773963.55 | 0.00 | 0.172774E+10 | 0.721654E+09 | 0.00 | 0.35 |
Report: MechanicalVentilationLoadsMonthly
For: M N1 APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.202540E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.583119E+09 | 0.00 | 0.00 | 0.35 |
| February | 0.177096E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.397819E+09 | 0.00 | 0.00 | 0.35 |
| March | 0.189842E+10 | 0.00 | 0.00 | 5177.56 | 0.00 | 7124612.34 | 4112606.95 | 0.00 | 0.35 |
| April | 0.709579E+09 | 8113415.09 | 0.00 | 2687732.55 | 0.00 | 0.00 | 0.674486E+09 | 0.00 | 0.35 |
| May | 0.188943E+09 | 45076399.42 | 0.00 | 4605934.96 | 0.00 | 0.00 | 0.753661E+09 | 0.00 | 0.35 |
| June | 11427346.74 | 0.308722E+09 | 0.00 | 3951613.56 | 0.00 | 0.00 | 0.420935E+09 | 0.00 | 0.35 |
| July | 0.00 | 0.643198E+09 | 0.00 | 1703455.57 | 0.00 | 0.00 | 59634552.82 | 0.00 | 0.35 |
| August | 0.00 | 0.423605E+09 | 0.00 | 2796212.09 | 0.00 | 0.00 | 0.155319E+09 | 0.00 | 0.35 |
| September | 955873.14 | 0.118341E+09 | 0.00 | 4304561.39 | 0.00 | 0.00 | 0.538519E+09 | 0.00 | 0.35 |
| October | 0.879612E+09 | 16306373.09 | 0.00 | 2372576.04 | 0.00 | 0.00 | 0.537560E+09 | 0.00 | 0.35 |
| November | 0.197918E+10 | 0.00 | 0.00 | 7268.75 | 0.00 | 45464090.14 | 9509025.99 | 0.00 | 0.35 |
| December | 0.192082E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.757033E+09 | 0.00 | 0.00 | 0.35 |
| Annual Sum or Average | 0.113853E+11 | 0.156336E+10 | 0.00 | 22434532.46 | 0.00 | 0.179056E+10 | 0.315374E+10 | 0.00 | 0.35 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
| Maximum of Months | 0.202540E+10 | 0.643198E+09 | 0.00 | 4605934.96 | 0.00 | 0.757033E+09 | 0.753661E+09 | 0.00 | 0.35 |
Report: MechanicalVentilationLoadsMonthly
For: M N2 APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.201658E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.591862E+09 | 0.00 | 0.00 | 0.35 |
| February | 0.177312E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.395315E+09 | 0.00 | 0.00 | 0.35 |
| March | 0.190050E+10 | 0.00 | 0.00 | 5652.40 | 0.00 | 7124518.87 | 5072975.24 | 0.00 | 0.35 |
| April | 0.696525E+09 | 8111429.27 | 0.00 | 2752119.49 | 0.00 | 0.00 | 0.689052E+09 | 0.00 | 0.35 |
| May | 0.180497E+09 | 45068472.34 | 0.00 | 4651120.47 | 0.00 | 0.00 | 0.762426E+09 | 0.00 | 0.35 |
| June | 11430265.55 | 0.308763E+09 | 0.00 | 3965578.51 | 0.00 | 0.00 | 0.420855E+09 | 0.00 | 0.35 |
| July | 0.00 | 0.643999E+09 | 0.00 | 1703197.92 | 0.00 | 0.00 | 59495185.81 | 0.00 | 0.35 |
| August | 0.00 | 0.424257E+09 | 0.00 | 2801909.00 | 0.00 | 0.00 | 0.155317E+09 | 0.00 | 0.35 |
| September | 955861.19 | 0.118515E+09 | 0.00 | 4307572.50 | 0.00 | 0.00 | 0.538571E+09 | 0.00 | 0.35 |
| October | 0.876993E+09 | 16348070.38 | 0.00 | 2382124.40 | 0.00 | 0.00 | 0.540666E+09 | 0.00 | 0.35 |
| November | 0.197806E+10 | 0.00 | 0.00 | 6944.30 | 0.00 | 46809247.69 | 9305152.04 | 0.00 | 0.35 |
| December | 0.191798E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.759706E+09 | 0.00 | 0.00 | 0.35 |
| Annual Sum or Average | 0.113527E+11 | 0.156506E+10 | 0.00 | 22576218.99 | 0.00 | 0.180082E+10 | 0.318076E+10 | 0.00 | 0.35 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
| Maximum of Months | 0.201658E+10 | 0.643999E+09 | 0.00 | 4651120.47 | 0.00 | 0.759706E+09 | 0.762426E+09 | 0.00 | 0.35 |
Report: MechanicalVentilationLoadsMonthly
For: M S1 APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.219930E+10 | 0.00 | 0.00 | 2523418.84 | 0.00 | 62824400.50 | 0.600917E+09 | 0.00 | 0.35 |
| February | 0.181685E+10 | 0.00 | 0.00 | 2459168.01 | 0.00 | 0.00 | 0.578317E+09 | 0.00 | 0.35 |
| March | 0.133411E+10 | 0.00 | 0.00 | 3232523.55 | 0.00 | 0.00 | 0.769075E+09 | 0.00 | 0.35 |
| April | 0.367179E+09 | 10315654.83 | 0.00 | 5517804.16 | 0.00 | 0.00 | 0.104520E+10 | 0.00 | 0.35 |
| May | 0.149045E+09 | 47292232.46 | 0.00 | 5185665.12 | 0.00 | 0.00 | 0.794183E+09 | 0.00 | 0.35 |
| June | 16909093.62 | 0.316441E+09 | 0.00 | 3741633.53 | 0.00 | 0.00 | 0.415770E+09 | 0.00 | 0.35 |
| July | 0.00 | 0.650130E+09 | 0.00 | 1682549.92 | 0.00 | 0.00 | 58207191.51 | 0.00 | 0.35 |
| August | 0.00 | 0.451551E+09 | 0.00 | 2939433.99 | 0.00 | 0.00 | 0.145880E+09 | 0.00 | 0.35 |
| September | 353356.49 | 0.137048E+09 | 0.00 | 5825701.31 | 0.00 | 0.00 | 0.516780E+09 | 0.00 | 0.35 |
| October | 0.369356E+09 | 20782828.52 | 0.00 | 7956225.70 | 0.00 | 0.00 | 0.110487E+10 | 0.00 | 0.35 |
| November | 0.111746E+10 | 0.00 | 0.00 | 5672350.70 | 0.00 | 0.00 | 0.120221E+10 | 0.00 | 0.35 |
| December | 0.219967E+10 | 0.00 | 0.00 | 2472056.64 | 0.00 | 6879774.76 | 0.741921E+09 | 0.00 | 0.35 |
| Annual Sum or Average | 0.957023E+10 | 0.163356E+10 | 0.00 | 49208531.48 | 0.00 | 69704175.26 | 0.797333E+10 | 0.00 | 0.35 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 1682549.92 | 0.00 | 0.00 | 58207191.51 | 0.00 | 0.35 |
| Maximum of Months | 0.219967E+10 | 0.650130E+09 | 0.00 | 7956225.70 | 0.00 | 62824400.50 | 0.120221E+10 | 0.00 | 0.35 |
Report: MechanicalVentilationLoadsMonthly
For: M S2 APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.219780E+10 | 0.00 | 0.00 | 2537101.65 | 0.00 | 63717414.45 | 0.601843E+09 | 0.00 | 0.35 |
| February | 0.181656E+10 | 0.00 | 0.00 | 2457692.03 | 0.00 | 0.00 | 0.577955E+09 | 0.00 | 0.35 |
| March | 0.132706E+10 | 0.00 | 0.00 | 3275247.95 | 0.00 | 0.00 | 0.776927E+09 | 0.00 | 0.35 |
| April | 0.364818E+09 | 10312652.81 | 0.00 | 5560434.35 | 0.00 | 0.00 | 0.104770E+10 | 0.00 | 0.35 |
| May | 0.146024E+09 | 47280861.70 | 0.00 | 5223947.65 | 0.00 | 0.00 | 0.797194E+09 | 0.00 | 0.35 |
| June | 16688397.53 | 0.316475E+09 | 0.00 | 3756295.14 | 0.00 | 0.00 | 0.415925E+09 | 0.00 | 0.35 |
| July | 0.00 | 0.650904E+09 | 0.00 | 1682882.09 | 0.00 | 0.00 | 58078592.80 | 0.00 | 0.35 |
| August | 0.00 | 0.452065E+09 | 0.00 | 2944908.19 | 0.00 | 0.00 | 0.145874E+09 | 0.00 | 0.35 |
| September | 353388.25 | 0.137161E+09 | 0.00 | 5830009.24 | 0.00 | 0.00 | 0.516833E+09 | 0.00 | 0.35 |
| October | 0.368702E+09 | 20805773.35 | 0.00 | 7960732.44 | 0.00 | 0.00 | 0.110556E+10 | 0.00 | 0.35 |
| November | 0.111580E+10 | 0.00 | 0.00 | 5686384.11 | 0.00 | 0.00 | 0.120389E+10 | 0.00 | 0.35 |
| December | 0.219965E+10 | 0.00 | 0.00 | 2482558.38 | 0.00 | 6879773.17 | 0.741879E+09 | 0.00 | 0.35 |
| Annual Sum or Average | 0.955346E+10 | 0.163500E+10 | 0.00 | 49398193.22 | 0.00 | 70597187.63 | 0.798966E+10 | 0.00 | 0.35 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 1682882.09 | 0.00 | 0.00 | 58078592.80 | 0.00 | 0.35 |
| Maximum of Months | 0.219965E+10 | 0.650904E+09 | 0.00 | 7960732.44 | 0.00 | 63717414.45 | 0.120389E+10 | 0.00 | 0.35 |
Report: MechanicalVentilationLoadsMonthly
For: T SW APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.347348E+09 | 0.00 | 0.00 | 1061473.14 | 0.00 | 0.850360E+09 | 0.142914E+09 | 0.00 | 0.35 |
| February | 0.332968E+09 | 0.00 | 0.00 | 1293953.53 | 0.00 | 0.626144E+09 | 0.156733E+09 | 0.00 | 0.35 |
| March | 0.359451E+09 | 0.00 | 0.00 | 1470586.85 | 0.00 | 0.429976E+09 | 0.145127E+09 | 0.00 | 0.35 |
| April | 0.341413E+09 | 5324029.59 | 0.00 | 2014515.90 | 0.00 | 0.116294E+09 | 0.163652E+09 | 0.00 | 0.35 |
| May | 0.256905E+09 | 25244218.26 | 0.00 | 1725649.46 | 52089.21 | 35196529.79 | 0.133247E+09 | 0.00 | 0.35 |
| June | 97508119.53 | 0.161964E+09 | 0.00 | 1255117.84 | 0.00 | 3670193.45 | 0.105639E+09 | 0.00 | 0.35 |
| July | 5061434.24 | 0.329272E+09 | 0.00 | 636062.03 | 0.00 | 0.00 | 43664827.50 | 0.00 | 0.35 |
| August | 22060611.60 | 0.231266E+09 | 0.00 | 962981.97 | 0.00 | 0.00 | 74612940.87 | 0.00 | 0.35 |
| September | 0.133022E+09 | 71595075.20 | 0.00 | 1648720.98 | 0.00 | 0.00 | 0.135237E+09 | 0.00 | 0.35 |
| October | 0.317130E+09 | 10603935.74 | 0.00 | 2774541.53 | 0.00 | 0.148496E+09 | 0.201556E+09 | 0.00 | 0.35 |
| November | 0.397662E+09 | 0.00 | 0.00 | 1604432.22 | 0.00 | 0.418998E+09 | 0.218617E+09 | 0.00 | 0.35 |
| December | 0.377055E+09 | 0.00 | 0.00 | 873746.59 | 0.00 | 0.817342E+09 | 0.188191E+09 | 0.00 | 0.35 |
| Annual Sum or Average | 0.298758E+10 | 0.835270E+09 | 0.00 | 17321782.03 | 52089.21 | 0.344648E+10 | 0.170919E+10 | 0.00 | 0.35 |
| Minimum of Months | 5061434.24 | 0.00 | 0.00 | 636062.03 | 0.00 | 0.00 | 43664827.50 | 0.00 | 0.35 |
| Maximum of Months | 0.397662E+09 | 0.329272E+09 | 0.00 | 2774541.53 | 52089.21 | 0.850360E+09 | 0.218617E+09 | 0.00 | 0.35 |
Report: MechanicalVentilationLoadsMonthly
For: T NW APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.147012E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114642E+10 | 0.00 | 0.00 | 0.35 |
| February | 0.208519E+09 | 0.00 | 0.00 | 66386.47 | 0.00 | 0.852149E+09 | 11013620.71 | 0.00 | 0.35 |
| March | 0.306749E+09 | 0.00 | 0.00 | 235195.36 | 0.00 | 0.553248E+09 | 41185284.37 | 0.00 | 0.35 |
| April | 0.352722E+09 | 4410656.12 | 0.00 | 1094803.89 | 0.00 | 0.149258E+09 | 0.103818E+09 | 0.00 | 0.35 |
| May | 0.261053E+09 | 24427872.50 | 0.00 | 1488638.73 | 62706.51 | 37894162.83 | 0.125192E+09 | 0.00 | 0.35 |
| June | 94266205.18 | 0.158832E+09 | 0.00 | 1366310.91 | 0.00 | 2295553.13 | 0.111040E+09 | 0.00 | 0.35 |
| July | 4879726.32 | 0.328434E+09 | 0.00 | 662115.61 | 0.00 | 0.00 | 43760411.19 | 0.00 | 0.35 |
| August | 24565364.21 | 0.222080E+09 | 0.00 | 927864.25 | 0.00 | 0.00 | 74163330.00 | 0.00 | 0.35 |
| September | 0.151981E+09 | 64023935.92 | 0.00 | 1193629.63 | 0.00 | 0.00 | 0.116729E+09 | 0.00 | 0.35 |
| October | 0.326356E+09 | 8719936.74 | 0.00 | 836576.07 | 0.00 | 0.232703E+09 | 74904667.53 | 0.00 | 0.35 |
| November | 0.278203E+09 | 0.00 | 0.00 | 8274.99 | 0.00 | 0.689550E+09 | 4650745.86 | 0.00 | 0.35 |
| December | 0.133612E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119464E+10 | 0.00 | 0.00 | 0.35 |
| Annual Sum or Average | 0.228992E+10 | 0.810928E+09 | 0.00 | 7879795.91 | 62706.51 | 0.485816E+10 | 0.706456E+09 | 0.00 | 0.35 |
| Minimum of Months | 4879726.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
| Maximum of Months | 0.352722E+09 | 0.328434E+09 | 0.00 | 1488638.73 | 62706.51 | 0.119464E+10 | 0.125192E+09 | 0.00 | 0.35 |
Report: MechanicalVentilationLoadsMonthly
For: T SE APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.359940E+09 | 0.00 | 0.00 | 913800.80 | 0.00 | 0.832941E+09 | 0.149292E+09 | 0.00 | 0.35 |
| February | 0.341947E+09 | 0.00 | 0.00 | 1077018.14 | 0.00 | 0.608916E+09 | 0.166440E+09 | 0.00 | 0.35 |
| March | 0.376924E+09 | 0.00 | 0.00 | 1342463.49 | 0.00 | 0.399317E+09 | 0.164034E+09 | 0.00 | 0.35 |
| April | 0.335933E+09 | 5254413.34 | 0.00 | 2185615.86 | 0.00 | 95668644.68 | 0.199172E+09 | 0.00 | 0.35 |
| May | 0.242680E+09 | 25072093.62 | 0.00 | 2105625.08 | 54919.80 | 27458836.36 | 0.159875E+09 | 0.00 | 0.35 |
| June | 96482366.87 | 0.163133E+09 | 0.00 | 1590739.26 | 0.00 | 1012550.21 | 0.110439E+09 | 0.00 | 0.35 |
| July | 4111864.47 | 0.342234E+09 | 0.00 | 714965.31 | 0.00 | 0.00 | 43816985.76 | 0.00 | 0.35 |
| August | 17390997.32 | 0.241393E+09 | 0.00 | 1161792.05 | 0.00 | 0.00 | 78396940.48 | 0.00 | 0.35 |
| September | 0.125682E+09 | 73752681.16 | 0.00 | 1850071.38 | 0.00 | 0.00 | 0.142804E+09 | 0.00 | 0.35 |
| October | 0.309015E+09 | 11037786.28 | 0.00 | 2716410.02 | 0.00 | 0.141263E+09 | 0.220378E+09 | 0.00 | 0.35 |
| November | 0.393810E+09 | 0.00 | 0.00 | 1455913.45 | 0.00 | 0.406770E+09 | 0.237889E+09 | 0.00 | 0.35 |
| December | 0.393890E+09 | 0.00 | 0.00 | 727376.49 | 0.00 | 0.793263E+09 | 0.197288E+09 | 0.00 | 0.35 |
| Annual Sum or Average | 0.299781E+10 | 0.861876E+09 | 0.00 | 17841791.31 | 54919.80 | 0.330661E+10 | 0.186982E+10 | 0.00 | 0.35 |
| Minimum of Months | 4111864.47 | 0.00 | 0.00 | 714965.31 | 0.00 | 0.00 | 43816985.76 | 0.00 | 0.35 |
| Maximum of Months | 0.393890E+09 | 0.342234E+09 | 0.00 | 2716410.02 | 54919.80 | 0.832941E+09 | 0.237889E+09 | 0.00 | 0.35 |
Report: MechanicalVentilationLoadsMonthly
For: T NE APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.148437E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114061E+10 | 0.00 | 0.00 | 0.35 |
| February | 0.203280E+09 | 0.00 | 0.00 | 7184.05 | 0.00 | 0.862712E+09 | 1566632.03 | 0.00 | 0.35 |
| March | 0.379356E+09 | 0.00 | 0.00 | 82367.07 | 0.00 | 0.506288E+09 | 19116107.92 | 0.00 | 0.35 |
| April | 0.364556E+09 | 4358240.88 | 0.00 | 1198149.65 | 0.00 | 0.120608E+09 | 0.132950E+09 | 0.00 | 0.35 |
| May | 0.247340E+09 | 24313708.17 | 0.00 | 1888126.26 | 64971.93 | 30879170.88 | 0.150168E+09 | 0.00 | 0.35 |
| June | 89401844.78 | 0.160101E+09 | 0.00 | 1745379.23 | 0.00 | 1531011.84 | 0.117205E+09 | 0.00 | 0.35 |
| July | 4207236.82 | 0.341303E+09 | 0.00 | 731489.77 | 0.00 | 0.00 | 43809151.01 | 0.00 | 0.35 |
| August | 20134188.39 | 0.233337E+09 | 0.00 | 1136082.93 | 0.00 | 0.00 | 77592734.14 | 0.00 | 0.35 |
| September | 0.144499E+09 | 66797633.60 | 0.00 | 1372056.39 | 0.00 | 0.00 | 0.125134E+09 | 0.00 | 0.35 |
| October | 0.341273E+09 | 9347656.47 | 0.00 | 716702.90 | 0.00 | 0.212436E+09 | 85522962.80 | 0.00 | 0.35 |
| November | 0.299341E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.667038E+09 | 0.00 | 0.00 | 0.35 |
| December | 87504209.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123882E+10 | 0.00 | 0.00 | 0.35 |
| Annual Sum or Average | 0.232933E+10 | 0.839559E+09 | 0.00 | 8877538.25 | 64971.93 | 0.478092E+10 | 0.753064E+09 | 0.00 | 0.35 |
| Minimum of Months | 4207236.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
| Maximum of Months | 0.379356E+09 | 0.341303E+09 | 0.00 | 1888126.26 | 64971.93 | 0.123882E+10 | 0.150168E+09 | 0.00 | 0.35 |
Report: MechanicalVentilationLoadsMonthly
For: T N1 APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.203098E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109334E+10 | 0.00 | 0.00 | 0.35 |
| February | 0.270953E+09 | 0.00 | 0.00 | 1165.87 | 0.00 | 0.802479E+09 | 578355.48 | 0.00 | 0.35 |
| March | 0.473057E+09 | 0.00 | 0.00 | 30613.79 | 0.00 | 0.422058E+09 | 10501879.71 | 0.00 | 0.35 |
| April | 0.451374E+09 | 4212454.17 | 0.00 | 685316.36 | 0.00 | 77720492.88 | 93306634.11 | 0.00 | 0.35 |
| May | 0.267136E+09 | 23017923.85 | 0.00 | 1311206.54 | 52570.95 | 14337743.34 | 0.159339E+09 | 0.00 | 0.35 |
| June | 74509913.09 | 0.155424E+09 | 0.00 | 1343559.07 | 0.00 | 0.00 | 0.141023E+09 | 0.00 | 0.35 |
| July | 1011690.95 | 0.324938E+09 | 0.00 | 688170.07 | 0.00 | 0.00 | 43215278.64 | 0.00 | 0.35 |
| August | 9404396.17 | 0.217253E+09 | 0.00 | 1008845.13 | 0.00 | 0.00 | 86683393.86 | 0.00 | 0.35 |
| September | 0.125329E+09 | 61534795.20 | 0.00 | 1183855.37 | 0.00 | 0.00 | 0.153460E+09 | 0.00 | 0.35 |
| October | 0.394115E+09 | 8296470.27 | 0.00 | 547447.10 | 0.00 | 0.170898E+09 | 81839467.22 | 0.00 | 0.35 |
| November | 0.393217E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.581029E+09 | 0.00 | 0.00 | 0.35 |
| December | 0.155518E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.117768E+10 | 0.00 | 0.00 | 0.35 |
| Annual Sum or Average | 0.281872E+10 | 0.794676E+09 | 0.00 | 6800179.29 | 52570.95 | 0.433954E+10 | 0.769946E+09 | 0.00 | 0.35 |
| Minimum of Months | 1011690.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
| Maximum of Months | 0.473057E+09 | 0.324938E+09 | 0.00 | 1343559.07 | 52570.95 | 0.117768E+10 | 0.159339E+09 | 0.00 | 0.35 |
Report: MechanicalVentilationLoadsMonthly
For: T N2 APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.202341E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109402E+10 | 0.00 | 0.00 | 0.35 |
| February | 0.271092E+09 | 0.00 | 0.00 | 1152.54 | 0.00 | 0.802226E+09 | 542525.81 | 0.00 | 0.35 |
| March | 0.475580E+09 | 0.00 | 0.00 | 32046.23 | 0.00 | 0.420191E+09 | 10438729.66 | 0.00 | 0.35 |
| April | 0.448555E+09 | 4210571.54 | 0.00 | 703215.30 | 0.00 | 77780538.35 | 97276698.65 | 0.00 | 0.35 |
| May | 0.266949E+09 | 23009920.06 | 0.00 | 1331338.10 | 52457.93 | 13620279.29 | 0.160589E+09 | 0.00 | 0.35 |
| June | 74269509.37 | 0.155459E+09 | 0.00 | 1353696.46 | 0.00 | 0.00 | 0.141303E+09 | 0.00 | 0.35 |
| July | 1010519.01 | 0.325454E+09 | 0.00 | 689649.98 | 0.00 | 0.00 | 43211352.35 | 0.00 | 0.35 |
| August | 9411173.25 | 0.217759E+09 | 0.00 | 1013631.07 | 0.00 | 0.00 | 86732131.11 | 0.00 | 0.35 |
| September | 0.125345E+09 | 61702229.33 | 0.00 | 1186867.55 | 0.00 | 0.00 | 0.153444E+09 | 0.00 | 0.35 |
| October | 0.393861E+09 | 8339975.97 | 0.00 | 550123.57 | 0.00 | 0.170895E+09 | 82617172.69 | 0.00 | 0.35 |
| November | 0.393000E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.581052E+09 | 0.00 | 0.00 | 0.35 |
| December | 0.154121E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.117903E+10 | 0.00 | 0.00 | 0.35 |
| Annual Sum or Average | 0.281554E+10 | 0.795935E+09 | 0.00 | 6861720.80 | 52457.93 | 0.433882E+10 | 0.776154E+09 | 0.00 | 0.35 |
| Minimum of Months | 1010519.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
| Maximum of Months | 0.475580E+09 | 0.325454E+09 | 0.00 | 1353696.46 | 52457.93 | 0.117903E+10 | 0.160589E+09 | 0.00 | 0.35 |
Report: MechanicalVentilationLoadsMonthly
For: T S1 APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.494039E+09 | 0.00 | 0.00 | 1095950.57 | 0.00 | 0.695674E+09 | 0.169947E+09 | 0.00 | 0.35 |
| February | 0.459410E+09 | 0.00 | 0.00 | 1184435.51 | 0.00 | 0.483313E+09 | 0.191786E+09 | 0.00 | 0.35 |
| March | 0.552317E+09 | 0.00 | 0.00 | 1175782.06 | 0.00 | 0.235244E+09 | 0.167660E+09 | 0.00 | 0.35 |
| April | 0.419540E+09 | 5229400.91 | 0.00 | 1623195.21 | 0.00 | 29443615.43 | 0.195050E+09 | 0.00 | 0.35 |
| May | 0.262757E+09 | 23967675.24 | 0.00 | 1546040.93 | 41624.50 | 9756087.32 | 0.170636E+09 | 0.00 | 0.35 |
| June | 82205849.88 | 0.158867E+09 | 0.00 | 1215241.33 | 0.00 | 0.00 | 0.132660E+09 | 0.00 | 0.35 |
| July | 1303251.78 | 0.326330E+09 | 0.00 | 664224.23 | 0.00 | 0.00 | 42968869.45 | 0.00 | 0.35 |
| August | 8117554.44 | 0.228375E+09 | 0.00 | 1043891.85 | 0.00 | 0.00 | 85226458.24 | 0.00 | 0.35 |
| September | 89477699.84 | 70391660.06 | 0.00 | 1709865.69 | 0.00 | 0.00 | 0.186228E+09 | 0.00 | 0.35 |
| October | 0.348964E+09 | 10519943.18 | 0.00 | 2580318.80 | 0.00 | 86100975.20 | 0.254386E+09 | 0.00 | 0.35 |
| November | 0.536763E+09 | 0.00 | 0.00 | 1630394.60 | 0.00 | 0.257107E+09 | 0.266875E+09 | 0.00 | 0.35 |
| December | 0.506323E+09 | 0.00 | 0.00 | 999028.52 | 0.00 | 0.658330E+09 | 0.238390E+09 | 0.00 | 0.35 |
| Annual Sum or Average | 0.376122E+10 | 0.823681E+09 | 0.00 | 16468369.28 | 41624.50 | 0.245497E+10 | 0.210181E+10 | 0.00 | 0.35 |
| Minimum of Months | 1303251.78 | 0.00 | 0.00 | 664224.23 | 0.00 | 0.00 | 42968869.45 | 0.00 | 0.35 |
| Maximum of Months | 0.552317E+09 | 0.326330E+09 | 0.00 | 2580318.80 | 41624.50 | 0.695674E+09 | 0.266875E+09 | 0.00 | 0.35 |
Report: MechanicalVentilationLoadsMonthly
For: T S2 APARTMENT
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.494345E+09 | 0.00 | 0.00 | 1099200.73 | 0.00 | 0.695133E+09 | 0.170161E+09 | 0.00 | 0.35 |
| February | 0.456822E+09 | 0.00 | 0.00 | 1187560.29 | 0.00 | 0.483925E+09 | 0.193683E+09 | 0.00 | 0.35 |
| March | 0.551716E+09 | 0.00 | 0.00 | 1189398.43 | 0.00 | 0.234504E+09 | 0.169313E+09 | 0.00 | 0.35 |
| April | 0.417838E+09 | 5226132.11 | 0.00 | 1647933.91 | 0.00 | 29180034.81 | 0.197540E+09 | 0.00 | 0.35 |
| May | 0.261555E+09 | 23956230.76 | 0.00 | 1567024.81 | 41703.55 | 9299997.80 | 0.172589E+09 | 0.00 | 0.35 |
| June | 81920849.20 | 0.158898E+09 | 0.00 | 1224763.54 | 0.00 | 0.00 | 0.132999E+09 | 0.00 | 0.35 |
| July | 1152467.91 | 0.326843E+09 | 0.00 | 666450.95 | 0.00 | 0.00 | 43109898.24 | 0.00 | 0.35 |
| August | 8119202.14 | 0.228790E+09 | 0.00 | 1047339.83 | 0.00 | 0.00 | 85286835.61 | 0.00 | 0.35 |
| September | 89055378.56 | 70499045.05 | 0.00 | 1712228.43 | 0.00 | 0.00 | 0.186664E+09 | 0.00 | 0.35 |
| October | 0.349177E+09 | 10541373.72 | 0.00 | 2589192.99 | 0.00 | 86098652.15 | 0.254171E+09 | 0.00 | 0.35 |
| November | 0.534075E+09 | 0.00 | 0.00 | 1637619.55 | 0.00 | 0.258111E+09 | 0.268543E+09 | 0.00 | 0.35 |
| December | 0.502954E+09 | 0.00 | 0.00 | 1004242.42 | 0.00 | 0.658926E+09 | 0.241127E+09 | 0.00 | 0.35 |
| Annual Sum or Average | 0.374873E+10 | 0.824754E+09 | 0.00 | 16572955.87 | 41703.55 | 0.245518E+10 | 0.211519E+10 | 0.00 | 0.35 |
| Minimum of Months | 1152467.91 | 0.00 | 0.00 | 666450.95 | 0.00 | 0.00 | 43109898.24 | 0.00 | 0.35 |
| Maximum of Months | 0.551716E+09 | 0.326843E+09 | 0.00 | 2589192.99 | 41703.55 | 0.695133E+09 | 0.268543E+09 | 0.00 | 0.35 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 09:14:27
Custom Monthly Report| SITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
| January | 0.148114E+12 | 0.132893E+11 | 0.00 | 0.197072E+10 | 0.136589E+11 |
| February | 0.168013E+12 | 0.124817E+11 | 0.00 | 0.163811E+10 | 0.120691E+11 |
| March | 0.203832E+12 | 0.138446E+11 | 0.00 | 0.148610E+10 | 0.115055E+11 |
| April | 0.237278E+12 | 0.114920E+11 | 0.00 | 0.110862E+10 | 0.349652E+11 |
| May | 0.243702E+12 | 0.926220E+10 | 0.00 | 0.845676E+09 | 0.633162E+11 |
| June | 0.225082E+12 | 0.353448E+10 | 0.00 | 0.376042E+09 | 0.117497E+12 |
| July | 0.231832E+12 | -0.110749E+10 | 0.00 | 0.111642E+09 | 0.160835E+12 |
| August | 0.233767E+12 | 0.127272E+10 | 0.00 | 0.229618E+09 | 0.147964E+12 |
| September | 0.199446E+12 | 0.542521E+10 | 0.00 | 0.645110E+09 | 0.103773E+12 |
| October | 0.176027E+12 | 0.996410E+10 | 0.00 | 0.128943E+10 | 0.536692E+11 |
| November | 0.151110E+12 | 0.112679E+11 | 0.00 | 0.173042E+10 | 0.160547E+11 |
| December | 0.141801E+12 | 0.124955E+11 | 0.00 | 0.207585E+10 | 0.122809E+11 |
| Annual Sum or Average | 0.236000E+13 | 0.103222E+12 | 0.00 | 0.135073E+11 | 0.747588E+12 |
| Minimum of Months | 0.141801E+12 | -0.110749E+10 | 0.00 | 0.111642E+09 | 0.115055E+11 |
| Maximum of Months | 0.243702E+12 | 0.138446E+11 | 0.00 | 0.207585E+10 | 0.160835E+12 |