Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 09:14
Tabular Output Report in Format: HTML
Building: ApartmentMidRise
Environment: RUNPERIOD 1 ** Fairbanks Intl Arpt AK USA TMY3 WMO#=702610
Simulation Timestamp: 2023-10-16 09:14:30
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 09:14:30
Values gathered over 8760.00 hours| Total Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
| Total Site Energy | 2533.14 | 808.12 | 897.01 |
| Net Site Energy | 2533.14 | 808.12 | 897.01 |
| Total Source Energy | 5487.36 | 1750.57 | 1943.13 |
| Net Source Energy | 5487.36 | 1750.57 | 1943.13 |
| Site=>Source Conversion Factor | |
| Electricity | 3.167 |
| Natural Gas | 1.084 |
| District Cooling | 1.056 |
| District Heating | 3.613 |
| Steam | 1.200 |
| Gasoline | 1.050 |
| Diesel | 1.050 |
| Coal | 1.050 |
| Fuel Oil No 1 | 1.050 |
| Fuel Oil No 2 | 1.050 |
| Propane | 1.050 |
| Other Fuel 1 | 1.000 |
| Other Fuel 2 | 1.000 |
| Area [m2] | |
| Total Building Area | 3134.61 |
| Net Conditioned Building Area | 2823.98 |
| Unconditioned Building Area | 310.64 |
| Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
| Heating | 0.00 | 1217.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Cooling | 45.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Lighting | 99.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Lighting | 49.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment | 458.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans | 105.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems | 557.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1875.32 |
| Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Total End Uses | 1316.10 | 1217.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1875.32 |
| Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
| Heating | General | 0.00 | 1217.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Cooling | General | 45.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Lighting | LightsWired | 94.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LightsPlugIn | 4.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Exterior Lighting | General | 49.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment | MiscPlug | 388.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| ElevatorLift | 65.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| ElevatorLightsFan | 5.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| General | 105.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems | Water Heater | 557.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1875.32 |
| Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
| Heating | Unassigned | 0.00 | 1217.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Cooling | Unassigned | 45.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Lighting | GENERAL | 99.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Lighting | Unassigned | 49.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment | GENERAL | 458.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans | Unassigned | 105.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Pumps | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems | Unassigned | 557.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1875.32 |
| Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
| Lighting | 52.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| HVAC | 250.92 | 430.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.66 |
| Other | 162.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Total | 466.04 | 430.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.66 |
| Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
| Lighting | 47.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| HVAC | 226.05 | 388.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.60 |
| Other | 146.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Total | 419.86 | 388.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.60 |
| Electricity [GJ] | Percent Electricity [%] | |
| Fuel-Fired Power Generation | 0.000 | 0.00 |
| High Temperature Geothermal* | 0.000 | 0.00 |
| Photovoltaic Power | 0.000 | 0.00 |
| Wind Power | 0.000 | 0.00 |
| Power Conversion | 0.000 | 0.00 |
| Net Decrease in On-Site Storage | 0.000 | 0.00 |
| Total On-Site Electric Sources | 0.000 | 0.00 |
| Electricity Coming From Utility | 1316.097 | 100.00 |
| Surplus Electricity Going To Utility | 0.000 | 0.00 |
| Net Electricity From Utility | 1316.097 | 100.00 |
| Total On-Site and Utility Electric Sources | 1316.097 | 100.00 |
| Total Electricity End Uses | 1316.097 | 100.00 |
| Heat [GJ] | Percent Heat [%] | |
| Water-Side Heat Recovery | 0.00 | 0.00 |
| Air to Air Heat Recovery for Cooling | 0.00 | 46.38 |
| Air to Air Heat Recovery for Heating | 0.00 | 53.62 |
| High-Temperature Geothermal* | 0.00 | 0.00 |
| Solar Water Thermal | 0.00 | 0.00 |
| Solar Air Thermal | 0.00 | 0.00 |
| Total On-Site Thermal Sources | 0.00 | 100.00 |
| Water [m3] | Percent Water [%] | |
| Rainwater Collection | 0.00 | 0.00 |
| Condensate Collection | 0.00 | 0.00 |
| Groundwater Well | 0.00 | 0.00 |
| Total On Site Water Sources | 0.00 | 0.00 |
| - | - | - |
| Initial Storage | 0.00 | 0.00 |
| Final Storage | 0.00 | 0.00 |
| Change in Storage | 0.00 | 0.00 |
| - | - | - |
| Water Supplied by Utility | 1875.32 | 100.00 |
| - | - | - |
| Total On Site, Change in Storage, and Utility Water Sources | 1875.32 | 100.00 |
| Total Water End Uses | 1875.32 | 100.00 |
| Degrees [deltaC] | |
| Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
| Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
| Facility [Hours] | |
| Time Setpoint Not Met During Occupied Heating | 0.00 |
| Time Setpoint Not Met During Occupied Cooling | 0.00 |
| Time Not Comfortable Based on Simple ASHRAE 55-2004 | 8760.00 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2012
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME APARTMENTMIDRISE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 8
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_AK_FAIRBANKS
| Environment |ZoneCoolingSummaryMonthly
| G SW APARTMENT | G NW APARTMENT | OFFICE | G NE APARTMENT | G N1 APARTMENT | G N2 APARTMENT | G S1 APARTMENT | G S2 APARTMENT | M SW APARTMENT | M NW APARTMENT | M SE APARTMENT | M NE APARTMENT | M N1 APARTMENT | M N2 APARTMENT | M S1 APARTMENT | M S2 APARTMENT | T SW APARTMENT | T NW APARTMENT | T SE APARTMENT | T NE APARTMENT | T N1 APARTMENT | T N2 APARTMENT | T S1 APARTMENT | T S2 APARTMENT | T CORRIDOR | G CORRIDOR | M CORRIDOR |ZoneHeatingSummaryMonthly
| G SW APARTMENT | G NW APARTMENT | OFFICE | G NE APARTMENT | G N1 APARTMENT | G N2 APARTMENT | G S1 APARTMENT | G S2 APARTMENT | M SW APARTMENT | M NW APARTMENT | M SE APARTMENT | M NE APARTMENT | M N1 APARTMENT | M N2 APARTMENT | M S1 APARTMENT | M S2 APARTMENT | T SW APARTMENT | T NW APARTMENT | T SE APARTMENT | T NE APARTMENT | T N1 APARTMENT | T N2 APARTMENT | T S1 APARTMENT | T S2 APARTMENT | T CORRIDOR | G CORRIDOR | M CORRIDOR |ZoneElectricSummaryMonthly
| G SW APARTMENT | G NW APARTMENT | OFFICE | G NE APARTMENT | G N1 APARTMENT | G N2 APARTMENT | G S1 APARTMENT | G S2 APARTMENT | M SW APARTMENT | M NW APARTMENT | M SE APARTMENT | M NE APARTMENT | M N1 APARTMENT | M N2 APARTMENT | M S1 APARTMENT | M S2 APARTMENT | T SW APARTMENT | T NW APARTMENT | T SE APARTMENT | T NE APARTMENT | T N1 APARTMENT | T N2 APARTMENT | T S1 APARTMENT | T S2 APARTMENT | T CORRIDOR | G CORRIDOR | M CORRIDOR |SpaceGainsMonthly
| G SW APARTMENT | G NW APARTMENT | OFFICE | G NE APARTMENT | G N1 APARTMENT | G N2 APARTMENT | G S1 APARTMENT | G S2 APARTMENT | M SW APARTMENT | M NW APARTMENT | M SE APARTMENT | M NE APARTMENT | M N1 APARTMENT | M N2 APARTMENT | M S1 APARTMENT | M S2 APARTMENT | T SW APARTMENT | T NW APARTMENT | T SE APARTMENT | T NE APARTMENT | T N1 APARTMENT | T N2 APARTMENT | T S1 APARTMENT | T S2 APARTMENT | T CORRIDOR | G CORRIDOR | M CORRIDOR |PeakSpaceGainsMonthly
| G SW APARTMENT | G NW APARTMENT | OFFICE | G NE APARTMENT | G N1 APARTMENT | G N2 APARTMENT | G S1 APARTMENT | G S2 APARTMENT | M SW APARTMENT | M NW APARTMENT | M SE APARTMENT | M NE APARTMENT | M N1 APARTMENT | M N2 APARTMENT | M S1 APARTMENT | M S2 APARTMENT | T SW APARTMENT | T NW APARTMENT | T SE APARTMENT | T NE APARTMENT | T N1 APARTMENT | T N2 APARTMENT | T S1 APARTMENT | T S2 APARTMENT | T CORRIDOR | G CORRIDOR | M CORRIDOR |SpaceGainComponentsAtCoolingPeakMonthly
| G SW APARTMENT | G NW APARTMENT | OFFICE | G NE APARTMENT | G N1 APARTMENT | G N2 APARTMENT | G S1 APARTMENT | G S2 APARTMENT | M SW APARTMENT | M NW APARTMENT | M SE APARTMENT | M NE APARTMENT | M N1 APARTMENT | M N2 APARTMENT | M S1 APARTMENT | M S2 APARTMENT | T SW APARTMENT | T NW APARTMENT | T SE APARTMENT | T NE APARTMENT | T N1 APARTMENT | T N2 APARTMENT | T S1 APARTMENT | T S2 APARTMENT | T CORRIDOR | G CORRIDOR | M CORRIDOR |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| G SW APARTMENT | G NW APARTMENT | OFFICE | G NE APARTMENT | G N1 APARTMENT | G N2 APARTMENT | G S1 APARTMENT | G S2 APARTMENT | M SW APARTMENT | M NW APARTMENT | M SE APARTMENT | M NE APARTMENT | M N1 APARTMENT | M N2 APARTMENT | M S1 APARTMENT | M S2 APARTMENT | T SW APARTMENT | T NW APARTMENT | T SE APARTMENT | T NE APARTMENT | T N1 APARTMENT | T N2 APARTMENT | T S1 APARTMENT | T S2 APARTMENT | T CORRIDOR | G CORRIDOR | M CORRIDOR |ComfortReportSimple55Monthly
| G SW APARTMENT | G NW APARTMENT | OFFICE | G NE APARTMENT | G N1 APARTMENT | G N2 APARTMENT | G S1 APARTMENT | G S2 APARTMENT | M SW APARTMENT | M NW APARTMENT | M SE APARTMENT | M NE APARTMENT | M N1 APARTMENT | M N2 APARTMENT | M S1 APARTMENT | M S2 APARTMENT | T SW APARTMENT | T NW APARTMENT | T SE APARTMENT | T NE APARTMENT | T N1 APARTMENT | T N2 APARTMENT | T S1 APARTMENT | T S2 APARTMENT | T CORRIDOR | G CORRIDOR | M CORRIDOR |OccupantComfortDataSummaryMonthly
| OCCUP_GSW | OCCUP_GNW | OCCUP_OFFICE | OCCUP_GNE | OCCUP_GN1 | OCCUP_GN2 | OCCUP_GS1 | OCCUP_GS2 | OCCUP_MSW | OCCUP_MNW | OCCUP_MSE | OCCUP_MNE | OCCUP_MN1 | OCCUP_MN2 | OCCUP_MS1 | OCCUP_MS2 | OCCUP_TSW | OCCUP_TNW | OCCUP_TSE | OCCUP_TNE | OCCUP_TN1 | OCCUP_TN2 | OCCUP_TS1 | OCCUP_TS2 | OCCUP_T CORRIDOR | OCCUP_G CORRIDOR | OCCUP_M CORRIDOR |DXReportMonthly
| SPLIT GSW COOLING COIL | SPLIT GNW COOLING COIL | SPLIT OFFICE COOLING COIL | SPLIT GNE COOLING COIL | SPLIT GN1 COOLING COIL | SPLIT GN2 COOLING COIL | SPLIT GS1 COOLING COIL | SPLIT GS2 COOLING COIL | SPLIT MSW COOLING COIL | SPLIT MNW COOLING COIL | SPLIT MSE COOLING COIL | SPLIT MNE COOLING COIL | SPLIT MN1 COOLING COIL | SPLIT MN2 COOLING COIL | SPLIT MS1 COOLING COIL | SPLIT MS2 COOLING COIL | SPLIT TSW COOLING COIL | SPLIT TNW COOLING COIL | SPLIT TSE COOLING COIL | SPLIT TNE COOLING COIL | SPLIT TN1 COOLING COIL | SPLIT TN2 COOLING COIL | SPLIT TS1 COOLING COIL | SPLIT TS2 COOLING COIL |WindowReportMonthly
| GWINDOW1 S SWA | GWINDOW1 W SWA | GWINDOW1 W NWA | GWINDOW1 N NWA | GWINDOW1 S SEA | GWINDOW1 E SEA | GWINDOW1 E NEA | GWINDOW1 N NEA | GWINDOW1 N N1A | GWINDOW1 N N2A | GWINDOW1 S S1A | GWINDOW1 S S2A | MWINDOW1 S SWA | MWINDOW1 W SWA | MWINDOW1 W NWA | MWINDOW1 N NWA | MWINDOW1 S SEA | MWINDOW1 E SEA | MWINDOW1 E NEA | MWINDOW1 N NEA | MWINDOW1 N N1A | MWINDOW1 N N2A | MWINDOW1 S S1A | MWINDOW1 S S2A | TWINDOW1 S SWA | TWINDOW1 W SWA | TWINDOW1 W NWA | TWINDOW1 N NWA | TWINDOW1 S SEA | TWINDOW1 E SEA | TWINDOW1 E NEA | TWINDOW1 N NEA | TWINDOW1 N N1A | TWINDOW1 N N2A | TWINDOW1 S S1A | TWINDOW1 S S2A | TWINDOW14 | ENTRANCE DOOR | MWINDOW14 |WindowEnergyReportMonthly
| GWINDOW1 S SWA | GWINDOW1 W SWA | GWINDOW1 W NWA | GWINDOW1 N NWA | GWINDOW1 S SEA | GWINDOW1 E SEA | GWINDOW1 E NEA | GWINDOW1 N NEA | GWINDOW1 N N1A | GWINDOW1 N N2A | GWINDOW1 S S1A | GWINDOW1 S S2A | MWINDOW1 S SWA | MWINDOW1 W SWA | MWINDOW1 W NWA | MWINDOW1 N NWA | MWINDOW1 S SEA | MWINDOW1 E SEA | MWINDOW1 E NEA | MWINDOW1 N NEA | MWINDOW1 N N1A | MWINDOW1 N N2A | MWINDOW1 S S1A | MWINDOW1 S S2A | TWINDOW1 S SWA | TWINDOW1 W SWA | TWINDOW1 W NWA | TWINDOW1 N NWA | TWINDOW1 S SEA | TWINDOW1 E SEA | TWINDOW1 E NEA | TWINDOW1 N NEA | TWINDOW1 N N1A | TWINDOW1 N N2A | TWINDOW1 S S1A | TWINDOW1 S S2A | TWINDOW14 | ENTRANCE DOOR | MWINDOW14 |WindowZoneSummaryMonthly
| G SW APARTMENT | G NW APARTMENT | OFFICE | G NE APARTMENT | G N1 APARTMENT | G N2 APARTMENT | G S1 APARTMENT | G S2 APARTMENT | M SW APARTMENT | M NW APARTMENT | M SE APARTMENT | M NE APARTMENT | M N1 APARTMENT | M N2 APARTMENT | M S1 APARTMENT | M S2 APARTMENT | T SW APARTMENT | T NW APARTMENT | T SE APARTMENT | T NE APARTMENT | T N1 APARTMENT | T N2 APARTMENT | T S1 APARTMENT | T S2 APARTMENT | T CORRIDOR | G CORRIDOR | M CORRIDOR |WindowEnergyZoneSummaryMonthly
| G SW APARTMENT | G NW APARTMENT | OFFICE | G NE APARTMENT | G N1 APARTMENT | G N2 APARTMENT | G S1 APARTMENT | G S2 APARTMENT | M SW APARTMENT | M NW APARTMENT | M SE APARTMENT | M NE APARTMENT | M N1 APARTMENT | M N2 APARTMENT | M S1 APARTMENT | M S2 APARTMENT | T SW APARTMENT | T NW APARTMENT | T SE APARTMENT | T NE APARTMENT | T N1 APARTMENT | T N2 APARTMENT | T S1 APARTMENT | T S2 APARTMENT | T CORRIDOR | G CORRIDOR | M CORRIDOR |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| G SW APARTMENT WATER HEATER | G NW APARTMENT WATER HEATER | G NE APARTMENT WATER HEATER | G N1 APARTMENT WATER HEATER | G N2 APARTMENT WATER HEATER | G S1 APARTMENT WATER HEATER | G S2 APARTMENT WATER HEATER | M SW APARTMENT WATER HEATER | M NW APARTMENT WATER HEATER | M SE APARTMENT WATER HEATER | M NE APARTMENT WATER HEATER | M N1 APARTMENT WATER HEATER | M N2 APARTMENT WATER HEATER | M S1 APARTMENT WATER HEATER | M S2 APARTMENT WATER HEATER | T SW APARTMENT WATER HEATER | T NW APARTMENT WATER HEATER | T SE APARTMENT WATER HEATER | T NE APARTMENT WATER HEATER | T N1 APARTMENT WATER HEATER | T N2 APARTMENT WATER HEATER | T S1 APARTMENT WATER HEATER | T S2 APARTMENT WATER HEATER |DaylightingReportMonthly
| Environment |CoilReportMonthly
| SPLIT GSW HEATING COIL | SPLIT GNW HEATING COIL | SPLIT OFFICE HEATING COIL | SPLIT GNE HEATING COIL | SPLIT GN1 HEATING COIL | SPLIT GN2 HEATING COIL | SPLIT GS1 HEATING COIL | SPLIT GS2 HEATING COIL | SPLIT MSW HEATING COIL | SPLIT MNW HEATING COIL | SPLIT MSE HEATING COIL | SPLIT MNE HEATING COIL | SPLIT MN1 HEATING COIL | SPLIT MN2 HEATING COIL | SPLIT MS1 HEATING COIL | SPLIT MS2 HEATING COIL | SPLIT TSW HEATING COIL | SPLIT TNW HEATING COIL | SPLIT TSE HEATING COIL | SPLIT TNE HEATING COIL | SPLIT TN1 HEATING COIL | SPLIT TN2 HEATING COIL | SPLIT TS1 HEATING COIL | SPLIT TS2 HEATING COIL | SPLIT GSW COOLING COIL | SPLIT GNW COOLING COIL | SPLIT OFFICE COOLING COIL | SPLIT GNE COOLING COIL | SPLIT GN1 COOLING COIL | SPLIT GN2 COOLING COIL | SPLIT GS1 COOLING COIL | SPLIT GS2 COOLING COIL | SPLIT MSW COOLING COIL | SPLIT MNW COOLING COIL | SPLIT MSE COOLING COIL | SPLIT MNE COOLING COIL | SPLIT MN1 COOLING COIL | SPLIT MN2 COOLING COIL | SPLIT MS1 COOLING COIL | SPLIT MS2 COOLING COIL | SPLIT TSW COOLING COIL | SPLIT TNW COOLING COIL | SPLIT TSE COOLING COIL | SPLIT TNE COOLING COIL | SPLIT TN1 COOLING COIL | SPLIT TN2 COOLING COIL | SPLIT TS1 COOLING COIL | SPLIT TS2 COOLING COIL |FanReportMonthly
| SPLIT GSW SUPPLY FAN | G SW APARTMENT ERV SUP FAN | G SW APARTMENT ERV EXH FAN | SPLIT GNW SUPPLY FAN | G NW APARTMENT ERV SUP FAN | G NW APARTMENT ERV EXH FAN | SPLIT OFFICE SUPPLY FAN | SPLIT GNE SUPPLY FAN | G NE APARTMENT ERV SUP FAN | G NE APARTMENT ERV EXH FAN | SPLIT GN1 SUPPLY FAN | G N1 APARTMENT ERV SUP FAN | G N1 APARTMENT ERV EXH FAN | SPLIT GN2 SUPPLY FAN | G N2 APARTMENT ERV SUP FAN | G N2 APARTMENT ERV EXH FAN | SPLIT GS1 SUPPLY FAN | G S1 APARTMENT ERV SUP FAN | G S1 APARTMENT ERV EXH FAN | SPLIT GS2 SUPPLY FAN | G S2 APARTMENT ERV SUP FAN | G S2 APARTMENT ERV EXH FAN | SPLIT MSW SUPPLY FAN | M SW APARTMENT ERV SUP FAN | M SW APARTMENT ERV EXH FAN | SPLIT MNW SUPPLY FAN | M NW APARTMENT ERV SUP FAN | M NW APARTMENT ERV EXH FAN | SPLIT MSE SUPPLY FAN | M SE APARTMENT ERV SUP FAN | M SE APARTMENT ERV EXH FAN | SPLIT MNE SUPPLY FAN | M NE APARTMENT ERV SUP FAN | M NE APARTMENT ERV EXH FAN | SPLIT MN1 SUPPLY FAN | M N1 APARTMENT ERV SUP FAN | M N1 APARTMENT ERV EXH FAN | SPLIT MN2 SUPPLY FAN | M N2 APARTMENT ERV SUP FAN | M N2 APARTMENT ERV EXH FAN | SPLIT MS1 SUPPLY FAN | M S1 APARTMENT ERV SUP FAN | M S1 APARTMENT ERV EXH FAN | SPLIT MS2 SUPPLY FAN | M S2 APARTMENT ERV SUP FAN | M S2 APARTMENT ERV EXH FAN | SPLIT TSW SUPPLY FAN | T SW APARTMENT ERV SUP FAN | T SW APARTMENT ERV EXH FAN | SPLIT TNW SUPPLY FAN | T NW APARTMENT ERV SUP FAN | T NW APARTMENT ERV EXH FAN | SPLIT TSE SUPPLY FAN | T SE APARTMENT ERV SUP FAN | T SE APARTMENT ERV EXH FAN | SPLIT TNE SUPPLY FAN | T NE APARTMENT ERV SUP FAN | T NE APARTMENT ERV EXH FAN | SPLIT TN1 SUPPLY FAN | T N1 APARTMENT ERV SUP FAN | T N1 APARTMENT ERV EXH FAN | SPLIT TN2 SUPPLY FAN | T N2 APARTMENT ERV SUP FAN | T N2 APARTMENT ERV EXH FAN | SPLIT TS1 SUPPLY FAN | T S1 APARTMENT ERV SUP FAN | T S1 APARTMENT ERV EXH FAN | SPLIT TS2 SUPPLY FAN | T S2 APARTMENT ERV SUP FAN | T S2 APARTMENT ERV EXH FAN |ZoneTemperatureOscillationReportMonthly
| G SW APARTMENT | G NW APARTMENT | OFFICE | G NE APARTMENT | G N1 APARTMENT | G N2 APARTMENT | G S1 APARTMENT | G S2 APARTMENT | M SW APARTMENT | M NW APARTMENT | M SE APARTMENT | M NE APARTMENT | M N1 APARTMENT | M N2 APARTMENT | M S1 APARTMENT | M S2 APARTMENT | T SW APARTMENT | T NW APARTMENT | T SE APARTMENT | T NE APARTMENT | T N1 APARTMENT | T N2 APARTMENT | T S1 APARTMENT | T S2 APARTMENT | T CORRIDOR | G CORRIDOR | M CORRIDOR |AirLoopSystemEnergyAndWaterUseMonthly
| SPLIT GSW | SPLIT GNW | SPLIT OFFICE | SPLIT GNE | SPLIT GN1 | SPLIT GN2 | SPLIT GS1 | SPLIT GS2 | SPLIT MSW | SPLIT MNW | SPLIT MSE | SPLIT MNE | SPLIT MN1 | SPLIT MN2 | SPLIT MS1 | SPLIT MS2 | SPLIT TSW | SPLIT TNW | SPLIT TSE | SPLIT TNE | SPLIT TN1 | SPLIT TN2 | SPLIT TS1 | SPLIT TS2 |AirLoopSystemComponentLoadsMonthly
| SPLIT GSW | SPLIT GNW | SPLIT OFFICE | SPLIT GNE | SPLIT GN1 | SPLIT GN2 | SPLIT GS1 | SPLIT GS2 | SPLIT MSW | SPLIT MNW | SPLIT MSE | SPLIT MNE | SPLIT MN1 | SPLIT MN2 | SPLIT MS1 | SPLIT MS2 | SPLIT TSW | SPLIT TNW | SPLIT TSE | SPLIT TNE | SPLIT TN1 | SPLIT TN2 | SPLIT TS1 | SPLIT TS2 |AirLoopSystemComponentEnergyUseMonthly
| SPLIT GSW | SPLIT GNW | SPLIT OFFICE | SPLIT GNE | SPLIT GN1 | SPLIT GN2 | SPLIT GS1 | SPLIT GS2 | SPLIT MSW | SPLIT MNW | SPLIT MSE | SPLIT MNE | SPLIT MN1 | SPLIT MN2 | SPLIT MS1 | SPLIT MS2 | SPLIT TSW | SPLIT TNW | SPLIT TSE | SPLIT TNE | SPLIT TN1 | SPLIT TN2 | SPLIT TS1 | SPLIT TS2 |MechanicalVentilationLoadsMonthly
| G SW APARTMENT | G NW APARTMENT | OFFICE | G NE APARTMENT | G N1 APARTMENT | G N2 APARTMENT | G S1 APARTMENT | G S2 APARTMENT | M SW APARTMENT | M NW APARTMENT | M SE APARTMENT | M NE APARTMENT | M N1 APARTMENT | M N2 APARTMENT | M S1 APARTMENT | M S2 APARTMENT | T SW APARTMENT | T NW APARTMENT | T SE APARTMENT | T NE APARTMENT | T N1 APARTMENT | T N2 APARTMENT | T S1 APARTMENT | T S2 APARTMENT |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 09:14:30
General| Value | |
| Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 09:14 |
| RunPeriod | RUNPERIOD 1 |
| Weather File | Fairbanks Intl Arpt AK USA TMY3 WMO#=702610 |
| Latitude [deg] | 64.82 |
| Longitude [deg] | -147.8 |
| Elevation [m] | 133.00 |
| Time Zone | -9.0 |
| North Axis Angle [deg] | 0.00 |
| Rotation for Appendix G [deg] | 0.00 |
| Hours Simulated [hrs] | 8760.00 |
| Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
| Gross Wall Area [m2] | 1542.04 | 564.80 | 206.22 | 564.80 | 206.22 |
| Above Ground Wall Area [m2] | 1542.04 | 564.80 | 206.22 | 564.80 | 206.22 |
| Window Opening Area [m2] | 306.92 | 112.97 | 43.82 | 112.97 | 37.16 |
| Gross Window-Wall Ratio [%] | 19.90 | 20.00 | 21.25 | 20.00 | 18.02 |
| Above Ground Window-Wall Ratio [%] | 19.90 | 20.00 | 21.25 | 20.00 | 18.02 |
| Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
| Gross Wall Area [m2] | 1501.17 | 564.80 | 185.79 | 564.80 | 185.79 |
| Above Ground Wall Area [m2] | 1501.17 | 564.80 | 185.79 | 564.80 | 185.79 |
| Window Opening Area [m2] | 300.26 | 112.97 | 37.16 | 112.97 | 37.16 |
| Gross Window-Wall Ratio [%] | 20.00 | 20.00 | 20.00 | 20.00 | 20.00 |
| Above Ground Window-Wall Ratio [%] | 20.00 | 20.00 | 20.00 | 20.00 | 20.00 |
| Total | |
| Gross Roof Area [m2] | 783.65 |
| Skylight Area [m2] | 0.00 |
| Skylight-Roof Ratio [%] | 0.00 |
| Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
| G SW APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 0.00 | 11.71 | 11.71 | 8.6918 | 35.30 | 6.6700 |
| G NW APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 0.00 | 11.71 | 11.71 | 8.6918 | 35.30 | 6.6700 |
| OFFICE | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 0.00 | 11.71 | 11.71 | 9.7532 | 18.58 | 6.6700 |
| G NE APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 0.00 | 11.71 | 11.71 | 8.6918 | 35.30 | 6.6700 |
| G N1 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 0.00 | 7.06 | 7.06 | 8.6918 | 35.30 | 6.6700 |
| G N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 0.00 | 7.06 | 7.06 | 8.6918 | 35.30 | 6.6700 |
| G S1 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 0.00 | 7.06 | 7.06 | 8.6918 | 35.30 | 6.6700 |
| G S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 0.00 | 7.06 | 7.06 | 8.6918 | 35.30 | 6.6700 |
| M SW APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 58.52 | 0.00 | 11.71 | 11.71 | 8.6918 | 35.30 | 6.6700 |
| M NW APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 58.52 | 0.00 | 11.71 | 11.71 | 8.6918 | 35.30 | 6.6700 |
| M SE APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 58.52 | 0.00 | 11.71 | 11.71 | 8.6918 | 35.30 | 6.6700 |
| M NE APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 58.52 | 0.00 | 11.71 | 11.71 | 8.6918 | 35.30 | 6.6700 |
| M N1 APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 35.30 | 0.00 | 7.06 | 7.06 | 8.6918 | 35.30 | 6.6700 |
| M N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 35.30 | 0.00 | 7.06 | 7.06 | 8.6918 | 35.30 | 6.6700 |
| M S1 APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 35.30 | 0.00 | 7.06 | 7.06 | 8.6918 | 35.30 | 6.6700 |
| M S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 35.30 | 0.00 | 7.06 | 7.06 | 8.6918 | 35.30 | 6.6700 |
| T SW APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 0.00 | 11.71 | 11.71 | 8.6918 | 35.30 | 6.6700 |
| T NW APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 0.00 | 11.71 | 11.71 | 8.6918 | 35.30 | 6.6700 |
| T SE APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 0.00 | 11.71 | 11.71 | 8.6918 | 35.30 | 6.6700 |
| T NE APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 0.00 | 11.71 | 11.71 | 8.6918 | 35.30 | 6.6700 |
| T N1 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 0.00 | 7.06 | 7.06 | 8.6918 | 35.30 | 6.6700 |
| T N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 0.00 | 7.06 | 7.06 | 8.6918 | 35.30 | 6.6700 |
| T S1 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 0.00 | 7.06 | 7.06 | 8.6918 | 35.30 | 6.6700 |
| T S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 0.00 | 7.06 | 7.06 | 8.6918 | 35.30 | 6.6700 |
| T CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 0.00 | 1.11 | 1.11 | 4.7725 | 18.58 | 0.0000 |
| G CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 0.00 | 3.32 | 3.32 | 4.7725 | 18.58 | 105.2565 |
| M CORRIDOR | 77.66 | No | Yes | 236.69 | 2.00 | 10.22 | 0.00 | 1.11 | 1.11 | 4.7725 | 18.58 | 0.0000 |
| Total | 3134.61 | 9553.84 | 1542.04 | 0.00 | 306.92 | 306.92 | 8.3333 | 31.67 | 8.6167 | |||
| Conditioned Total | 2823.98 | 8607.06 | 1501.17 | 0.00 | 300.26 | 300.26 | 8.7250 | 34.33 | 6.6700 | |||
| Unconditioned Total | 310.64 | 946.78 | 40.87 | 0.00 | 6.66 | 6.66 | 4.7725 | 18.58 | 26.3141 | |||
| Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
| G SW APARTMENT | 88.25 | Yes | Yes | 1.00 | G SW APARTMENT | GENERAL | G SW APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| G NW APARTMENT | 88.25 | Yes | Yes | 1.00 | G NW APARTMENT | GENERAL | G NW APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| OFFICE | 88.25 | Yes | Yes | 1.00 | OFFICE | GENERAL | OFFICE | 9.7532 | 18.58 | 6.6700 | |
| G NE APARTMENT | 88.25 | Yes | Yes | 1.00 | G NE APARTMENT | GENERAL | G NE APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| G N1 APARTMENT | 88.25 | Yes | Yes | 1.00 | G N1 APARTMENT | GENERAL | G N1 APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| G N2 APARTMENT | 88.25 | Yes | Yes | 1.00 | G N2 APARTMENT | GENERAL | G N2 APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| G S1 APARTMENT | 88.25 | Yes | Yes | 1.00 | G S1 APARTMENT | GENERAL | G S1 APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| G S2 APARTMENT | 88.25 | Yes | Yes | 1.00 | G S2 APARTMENT | GENERAL | G S2 APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| M SW APARTMENT | 88.25 | Yes | Yes | 2.00 | M SW APARTMENT | GENERAL | M SW APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| M NW APARTMENT | 88.25 | Yes | Yes | 2.00 | M NW APARTMENT | GENERAL | M NW APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| M SE APARTMENT | 88.25 | Yes | Yes | 2.00 | M SE APARTMENT | GENERAL | M SE APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| M NE APARTMENT | 88.25 | Yes | Yes | 2.00 | M NE APARTMENT | GENERAL | M NE APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| M N1 APARTMENT | 88.25 | Yes | Yes | 2.00 | M N1 APARTMENT | GENERAL | M N1 APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| M N2 APARTMENT | 88.25 | Yes | Yes | 2.00 | M N2 APARTMENT | GENERAL | M N2 APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| M S1 APARTMENT | 88.25 | Yes | Yes | 2.00 | M S1 APARTMENT | GENERAL | M S1 APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| M S2 APARTMENT | 88.25 | Yes | Yes | 2.00 | M S2 APARTMENT | GENERAL | M S2 APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| T SW APARTMENT | 88.25 | Yes | Yes | 1.00 | T SW APARTMENT | GENERAL | T SW APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| T NW APARTMENT | 88.25 | Yes | Yes | 1.00 | T NW APARTMENT | GENERAL | T NW APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| T SE APARTMENT | 88.25 | Yes | Yes | 1.00 | T SE APARTMENT | GENERAL | T SE APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| T NE APARTMENT | 88.25 | Yes | Yes | 1.00 | T NE APARTMENT | GENERAL | T NE APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| T N1 APARTMENT | 88.25 | Yes | Yes | 1.00 | T N1 APARTMENT | GENERAL | T N1 APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| T N2 APARTMENT | 88.25 | Yes | Yes | 1.00 | T N2 APARTMENT | GENERAL | T N2 APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| T S1 APARTMENT | 88.25 | Yes | Yes | 1.00 | T S1 APARTMENT | GENERAL | T S1 APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| T S2 APARTMENT | 88.25 | Yes | Yes | 1.00 | T S2 APARTMENT | GENERAL | T S2 APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| T CORRIDOR | 77.66 | No | Yes | 1.00 | T CORRIDOR | GENERAL | T CORRIDOR | 4.7725 | 18.58 | 0.0000 | |
| G CORRIDOR | 77.66 | No | Yes | 1.00 | G CORRIDOR | GENERAL | G CORRIDOR | 4.7725 | 18.58 | 105.2565 | |
| M CORRIDOR | 77.66 | No | Yes | 2.00 | M CORRIDOR | GENERAL | M CORRIDOR | 4.7725 | 18.58 | 0.0000 | |
| Total | 3134.61 | 8.3333 | 15.84 | 8.6167 | |||||||
| Conditioned Total | 2823.98 | 8.7250 | 17.17 | 6.6700 | |||||||
| Unconditioned Total | 310.64 | 4.7725 | 9.29 | 26.3141 | |||||||
| Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
| Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
| GENERAL | 3134.61 | 2823.98 | 310.64 | 0.00 | 6.2575 | 41.91 | 7.1145 |
| Total | 3134.61 | 2823.98 | 310.64 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 09:14:30
End Uses| Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
| Time of Peak | 21-JUN-17:19 | 12-JAN-03:00 | - | - | - | - | - | - | - | - | - | - | 01-JAN-07:10 |
| Heating | 0.00 | 151176.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Cooling | 15367.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Lighting | 5231.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment | 22609.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans | 6344.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems | 33316.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Total End Uses | 82869.64 | 151176.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
| Heating | General | 0.00 | 151176.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Cooling | General | 15367.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Lighting | LightsWired | 4887.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LightsPlugIn | 344.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment | MiscPlug | 18441.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| ElevatorLift | 4006.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| ElevatorLightsFan | 162.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| General | 6344.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems | Water Heater | 33316.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 09:14:30
Values gathered over 8760.00 hours| Source Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
| Heating | 0.00 | 1319.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Cooling | 143.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Lighting | 314.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Lighting | 157.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment | 1452.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans | 333.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems | 1766.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Total Source Energy End Use Components | 4168.08 | 1319.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
| Heating | 0.00 | 467.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Cooling | 50.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Lighting | 111.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Lighting | 55.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment | 514.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans | 118.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems | 625.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Total Source Energy End Use Components | 1475.96 | 467.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
| Heating | 0.00 | 420.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Cooling | 45.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Lighting | 100.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Lighting | 50.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment | 463.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans | 106.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems | 563.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Total Source Energy End Use Components | 1329.69 | 420.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 09:14:30
ZoneHVAC:EnergyRecoveryVentilator| User-Specified Supply Air Flow Rate [m3/s] | User-Specified Exhaust Air Flow Rate [m3/s] | |
| G SW APARTMENT ERV | 0.025955 | 0.025955 |
| G NW APARTMENT ERV | 0.025955 | 0.025955 |
| G NE APARTMENT ERV | 0.025955 | 0.025955 |
| G N1 APARTMENT ERV | 0.025955 | 0.025955 |
| G N2 APARTMENT ERV | 0.025955 | 0.025955 |
| G S1 APARTMENT ERV | 0.025955 | 0.025955 |
| G S2 APARTMENT ERV | 0.025955 | 0.025955 |
| M SW APARTMENT ERV | 0.051909 | 0.051909 |
| M NW APARTMENT ERV | 0.051909 | 0.051909 |
| M SE APARTMENT ERV | 0.051909 | 0.051909 |
| M NE APARTMENT ERV | 0.051909 | 0.051909 |
| M N1 APARTMENT ERV | 0.051909 | 0.051909 |
| M N2 APARTMENT ERV | 0.051909 | 0.051909 |
| M S1 APARTMENT ERV | 0.051909 | 0.051909 |
| M S2 APARTMENT ERV | 0.051909 | 0.051909 |
| T SW APARTMENT ERV | 0.025955 | 0.025955 |
| T NW APARTMENT ERV | 0.025955 | 0.025955 |
| T SE APARTMENT ERV | 0.025955 | 0.025955 |
| T NE APARTMENT ERV | 0.025955 | 0.025955 |
| T N1 APARTMENT ERV | 0.025955 | 0.025955 |
| T N2 APARTMENT ERV | 0.025955 | 0.025955 |
| T S1 APARTMENT ERV | 0.025955 | 0.025955 |
| T S2 APARTMENT ERV | 0.025955 | 0.025955 |
| Design Size Maximum Flow Rate [m3/s] | |
| G SW APARTMENT ERV SUP FAN | 0.025955 |
| G SW APARTMENT ERV EXH FAN | 0.025955 |
| G NW APARTMENT ERV SUP FAN | 0.025955 |
| G NW APARTMENT ERV EXH FAN | 0.025955 |
| G NE APARTMENT ERV SUP FAN | 0.025955 |
| G NE APARTMENT ERV EXH FAN | 0.025955 |
| G N1 APARTMENT ERV SUP FAN | 0.025955 |
| G N1 APARTMENT ERV EXH FAN | 0.025955 |
| G N2 APARTMENT ERV SUP FAN | 0.025955 |
| G N2 APARTMENT ERV EXH FAN | 0.025955 |
| G S1 APARTMENT ERV SUP FAN | 0.025955 |
| G S1 APARTMENT ERV EXH FAN | 0.025955 |
| G S2 APARTMENT ERV SUP FAN | 0.025955 |
| G S2 APARTMENT ERV EXH FAN | 0.025955 |
| M SW APARTMENT ERV SUP FAN | 0.051909 |
| M SW APARTMENT ERV EXH FAN | 0.051909 |
| M NW APARTMENT ERV SUP FAN | 0.051909 |
| M NW APARTMENT ERV EXH FAN | 0.051909 |
| M SE APARTMENT ERV SUP FAN | 0.051909 |
| M SE APARTMENT ERV EXH FAN | 0.051909 |
| M NE APARTMENT ERV SUP FAN | 0.051909 |
| M NE APARTMENT ERV EXH FAN | 0.051909 |
| M N1 APARTMENT ERV SUP FAN | 0.051909 |
| M N1 APARTMENT ERV EXH FAN | 0.051909 |
| M N2 APARTMENT ERV SUP FAN | 0.051909 |
| M N2 APARTMENT ERV EXH FAN | 0.051909 |
| M S1 APARTMENT ERV SUP FAN | 0.051909 |
| M S1 APARTMENT ERV EXH FAN | 0.051909 |
| M S2 APARTMENT ERV SUP FAN | 0.051909 |
| M S2 APARTMENT ERV EXH FAN | 0.051909 |
| T SW APARTMENT ERV SUP FAN | 0.025955 |
| T SW APARTMENT ERV EXH FAN | 0.025955 |
| T NW APARTMENT ERV SUP FAN | 0.025955 |
| T NW APARTMENT ERV EXH FAN | 0.025955 |
| T SE APARTMENT ERV SUP FAN | 0.025955 |
| T SE APARTMENT ERV EXH FAN | 0.025955 |
| T NE APARTMENT ERV SUP FAN | 0.025955 |
| T NE APARTMENT ERV EXH FAN | 0.025955 |
| T N1 APARTMENT ERV SUP FAN | 0.025955 |
| T N1 APARTMENT ERV EXH FAN | 0.025955 |
| T N2 APARTMENT ERV SUP FAN | 0.025955 |
| T N2 APARTMENT ERV EXH FAN | 0.025955 |
| T S1 APARTMENT ERV SUP FAN | 0.025955 |
| T S1 APARTMENT ERV EXH FAN | 0.025955 |
| T S2 APARTMENT ERV SUP FAN | 0.025955 |
| T S2 APARTMENT ERV EXH FAN | 0.025955 |
| SPLIT GSW SUPPLY FAN | 0.389736 |
| SPLIT GNW SUPPLY FAN | 0.319053 |
| SPLIT OFFICE SUPPLY FAN | 0.409760 |
| SPLIT GNE SUPPLY FAN | 0.280779 |
| SPLIT GN1 SUPPLY FAN | 0.250986 |
| SPLIT GN2 SUPPLY FAN | 0.250464 |
| SPLIT GS1 SUPPLY FAN | 0.326021 |
| SPLIT GS2 SUPPLY FAN | 0.327871 |
| SPLIT MSW SUPPLY FAN | 0.977770 |
| SPLIT MNW SUPPLY FAN | 0.838166 |
| SPLIT MSE SUPPLY FAN | 0.838672 |
| SPLIT MNE SUPPLY FAN | 0.703392 |
| SPLIT MN1 SUPPLY FAN | 0.627840 |
| SPLIT MN2 SUPPLY FAN | 0.626183 |
| SPLIT MS1 SUPPLY FAN | 0.775442 |
| SPLIT MS2 SUPPLY FAN | 0.773486 |
| SPLIT TSW SUPPLY FAN | 0.530308 |
| SPLIT TNW SUPPLY FAN | 0.464476 |
| SPLIT TSE SUPPLY FAN | 0.428758 |
| SPLIT TNE SUPPLY FAN | 0.364362 |
| SPLIT TN1 SUPPLY FAN | 0.342583 |
| SPLIT TN2 SUPPLY FAN | 0.339994 |
| SPLIT TS1 SUPPLY FAN | 0.410860 |
| SPLIT TS2 SUPPLY FAN | 0.408249 |
| Design Size Nominal Supply Air Flow Rate [m3/s] | |
| G SW APARTMENT OA HEAT EXCHANGER | 0.025955 |
| G NW APARTMENT OA HEAT EXCHANGER | 0.025955 |
| G NE APARTMENT OA HEAT EXCHANGER | 0.025955 |
| G N1 APARTMENT OA HEAT EXCHANGER | 0.025955 |
| G N2 APARTMENT OA HEAT EXCHANGER | 0.025955 |
| G S1 APARTMENT OA HEAT EXCHANGER | 0.025955 |
| G S2 APARTMENT OA HEAT EXCHANGER | 0.025955 |
| M SW APARTMENT OA HEAT EXCHANGER | 0.051909 |
| M NW APARTMENT OA HEAT EXCHANGER | 0.051909 |
| M SE APARTMENT OA HEAT EXCHANGER | 0.051909 |
| M NE APARTMENT OA HEAT EXCHANGER | 0.051909 |
| M N1 APARTMENT OA HEAT EXCHANGER | 0.051909 |
| M N2 APARTMENT OA HEAT EXCHANGER | 0.051909 |
| M S1 APARTMENT OA HEAT EXCHANGER | 0.051909 |
| M S2 APARTMENT OA HEAT EXCHANGER | 0.051909 |
| T SW APARTMENT OA HEAT EXCHANGER | 0.025955 |
| T NW APARTMENT OA HEAT EXCHANGER | 0.025955 |
| T SE APARTMENT OA HEAT EXCHANGER | 0.025955 |
| T NE APARTMENT OA HEAT EXCHANGER | 0.025955 |
| T N1 APARTMENT OA HEAT EXCHANGER | 0.025955 |
| T N2 APARTMENT OA HEAT EXCHANGER | 0.025955 |
| T S1 APARTMENT OA HEAT EXCHANGER | 0.025955 |
| T S2 APARTMENT OA HEAT EXCHANGER | 0.025955 |
| Design Size Maximum Air Flow Rate [m3/s] | |
| G SW APARTMENT DIRECT AIR | 0.389736 |
| G NW APARTMENT DIRECT AIR | 0.319053 |
| OFFICE DIRECT AIR | 0.409760 |
| G NE APARTMENT DIRECT AIR | 0.280779 |
| G N1 APARTMENT DIRECT AIR | 0.250986 |
| G N2 APARTMENT DIRECT AIR | 0.250464 |
| G S1 APARTMENT DIRECT AIR | 0.326021 |
| G S2 APARTMENT DIRECT AIR | 0.327871 |
| M SW APARTMENT DIRECT AIR | 0.977770 |
| M NW APARTMENT DIRECT AIR | 0.838166 |
| M SE APARTMENT DIRECT AIR | 0.838672 |
| M NE APARTMENT DIRECT AIR | 0.703392 |
| M N1 APARTMENT DIRECT AIR | 0.627840 |
| M N2 APARTMENT DIRECT AIR | 0.626183 |
| M S1 APARTMENT DIRECT AIR | 0.775442 |
| M S2 APARTMENT DIRECT AIR | 0.773486 |
| T SW APARTMENT DIRECT AIR | 0.530308 |
| T NW APARTMENT DIRECT AIR | 0.464476 |
| T SE APARTMENT DIRECT AIR | 0.428758 |
| T NE APARTMENT DIRECT AIR | 0.364362 |
| T N1 APARTMENT DIRECT AIR | 0.342583 |
| T N2 APARTMENT DIRECT AIR | 0.339994 |
| T S1 APARTMENT DIRECT AIR | 0.410860 |
| T S2 APARTMENT DIRECT AIR | 0.408249 |
| Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
| SPLIT GSW | 0.389736 | 0.389736 | 0.389736 | 0.389736 | 0.389736 | 0.389736 | 1.00 | 1.00 | 0.389736 |
| SPLIT GNW | 0.319053 | 0.319053 | 0.319053 | 0.319053 | 0.319053 | 0.319053 | 1.00 | 1.000000 | 0.319053 |
| SPLIT OFFICE | 0.409760 | 0.409760 | 0.409760 | 0.409760 | 0.409760 | 0.409760 | 1.00 | 1.00 | 0.409760 |
| SPLIT GNE | 0.280779 | 0.280779 | 0.280779 | 0.280779 | 0.280779 | 0.280779 | 1.00 | 1.00 | 0.280779 |
| SPLIT GN1 | 0.250986 | 0.250986 | 0.250986 | 0.250986 | 0.250986 | 0.250986 | 1.00 | 1.00 | 0.250986 |
| SPLIT GN2 | 0.250464 | 0.250464 | 0.250464 | 0.250464 | 0.250464 | 0.250464 | 1.00 | 1.00 | 0.250464 |
| SPLIT GS1 | 0.326021 | 0.326021 | 0.326021 | 0.326021 | 0.326021 | 0.326021 | 1.00 | 1.00 | 0.326021 |
| SPLIT GS2 | 0.327871 | 0.327871 | 0.327871 | 0.327871 | 0.327871 | 0.327871 | 1.00 | 1.00 | 0.327871 |
| SPLIT MSW | 0.977770 | 0.977770 | 0.977770 | 0.977770 | 0.977770 | 0.977770 | 1.00 | 1.00 | 0.977770 |
| SPLIT MNW | 0.838166 | 0.838166 | 0.838166 | 0.838166 | 0.838166 | 0.838166 | 1.00 | 1.00 | 0.838166 |
| SPLIT MSE | 0.838672 | 0.838672 | 0.838672 | 0.838672 | 0.838672 | 0.838672 | 1.00 | 1.00 | 0.838672 |
| SPLIT MNE | 0.703392 | 0.703392 | 0.703392 | 0.703392 | 0.703392 | 0.703392 | 1.00 | 1.00 | 0.703392 |
| SPLIT MN1 | 0.627840 | 0.627840 | 0.627840 | 0.627840 | 0.627840 | 0.627840 | 1.00 | 1.00 | 0.627840 |
| SPLIT MN2 | 0.626183 | 0.626183 | 0.626183 | 0.626183 | 0.626183 | 0.626183 | 1.00 | 1.00 | 0.626183 |
| SPLIT MS1 | 0.775442 | 0.775442 | 0.775442 | 0.775442 | 0.775442 | 0.775442 | 1.00 | 1.00 | 0.775442 |
| SPLIT MS2 | 0.773486 | 0.773486 | 0.773486 | 0.773486 | 0.773486 | 0.773486 | 1.00 | 1.00 | 0.773486 |
| SPLIT TSW | 0.530308 | 0.530308 | 0.530308 | 0.530308 | 0.530308 | 0.530308 | 1.00 | 1.00 | 0.530308 |
| SPLIT TNW | 0.464476 | 0.464476 | 0.464476 | 0.464476 | 0.464476 | 0.464476 | 1.00 | 1.000000 | 0.464476 |
| SPLIT TSE | 0.428758 | 0.428758 | 0.428758 | 0.428758 | 0.428758 | 0.428758 | 1.00 | 1.00 | 0.428758 |
| SPLIT TNE | 0.364362 | 0.364362 | 0.364362 | 0.364362 | 0.364362 | 0.364362 | 1.00 | 1.00 | 0.364362 |
| SPLIT TN1 | 0.342583 | 0.342583 | 0.342583 | 0.342583 | 0.342583 | 0.342583 | 1.00 | 1.00 | 0.342583 |
| SPLIT TN2 | 0.339994 | 0.339994 | 0.339994 | 0.339994 | 0.339994 | 0.339994 | 1.00 | 1.000000 | 0.339994 |
| SPLIT TS1 | 0.410860 | 0.410860 | 0.410860 | 0.410860 | 0.410860 | 0.410860 | 1.00 | 1.00 | 0.410860 |
| SPLIT TS2 | 0.408249 | 0.408249 | 0.408249 | 0.408249 | 0.408249 | 0.408249 | 1.00 | 1.00 | 0.408249 |
| Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
| SPLIT GSW_OA_CONTROLLER | 0.389736 | 0.025955 |
| SPLIT GNW_OA_CONTROLLER | 0.319053 | 0.025955 |
| SPLIT OFFICE_OA_CONTROLLER | 0.409760 | 0.038106 |
| SPLIT GNE_OA_CONTROLLER | 0.280779 | 0.025955 |
| SPLIT GN1_OA_CONTROLLER | 0.250986 | 0.025955 |
| SPLIT GN2_OA_CONTROLLER | 0.250464 | 0.025955 |
| SPLIT GS1_OA_CONTROLLER | 0.326021 | 0.025955 |
| SPLIT GS2_OA_CONTROLLER | 0.327871 | 0.025955 |
| SPLIT MSW_OA_CONTROLLER | 0.977770 | 0.051909 |
| SPLIT MNW_OA_CONTROLLER | 0.838166 | 0.051909 |
| SPLIT MSE_OA_CONTROLLER | 0.838672 | 0.051909 |
| SPLIT MNE_OA_CONTROLLER | 0.703392 | 0.051909 |
| SPLIT MN1_OA_CONTROLLER | 0.627840 | 0.051909 |
| SPLIT MN2_OA_CONTROLLER | 0.626183 | 0.051909 |
| SPLIT MS1_OA_CONTROLLER | 0.775442 | 0.051909 |
| SPLIT MS2_OA_CONTROLLER | 0.773486 | 0.051909 |
| SPLIT TSW_OA_CONTROLLER | 0.530308 | 0.025955 |
| SPLIT TNW_OA_CONTROLLER | 0.464476 | 0.025955 |
| SPLIT TSE_OA_CONTROLLER | 0.428758 | 0.025955 |
| SPLIT TNE_OA_CONTROLLER | 0.364362 | 0.025955 |
| SPLIT TN1_OA_CONTROLLER | 0.342583 | 0.025955 |
| SPLIT TN2_OA_CONTROLLER | 0.339994 | 0.025955 |
| SPLIT TS1_OA_CONTROLLER | 0.410860 | 0.025955 |
| SPLIT TS2_OA_CONTROLLER | 0.408249 | 0.025955 |
| Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | Design Size Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
| SPLIT GSW_UNITARY_PACKAGE_DX | 0.389736 | 0.389736 | 0.389736 | 0.389736 | 6451.51 | 10722.17 | 40.00 | 1.00 |
| SPLIT GNW_UNITARY_PACKAGE_DX | 0.319053 | 0.319053 | 0.319053 | 0.319053 | 5281.46 | 9130.81 | 40.00 | 1.00 |
| SPLIT OFFICE_UNITARY_PACKAGE_DX | 0.409760 | 0.409760 | 0.409760 | 0.409760 | 6782.98 | 12084.91 | 40.00 | 1.00 |
| SPLIT GNE_UNITARY_PACKAGE_DX | 0.280779 | 0.280779 | 0.280779 | 0.280779 | 4647.89 | 8269.12 | 40.00 | 1.00 |
| SPLIT GN1_UNITARY_PACKAGE_DX | 0.250986 | 0.250986 | 0.250986 | 0.250986 | 4154.71 | 7598.36 | 40.00 | 1.00 |
| SPLIT GN2_UNITARY_PACKAGE_DX | 0.250464 | 0.250464 | 0.250464 | 0.250464 | 4146.07 | 7586.61 | 40.00 | 1.00 |
| SPLIT GS1_UNITARY_PACKAGE_DX | 0.326021 | 0.326021 | 0.326021 | 0.326021 | 5396.80 | 9287.71 | 40.00 | 1.00 |
| SPLIT GS2_UNITARY_PACKAGE_DX | 0.327871 | 0.327871 | 0.327871 | 0.327871 | 5427.42 | 9329.35 | 40.00 | 1.00 |
| SPLIT MSW_UNITARY_PACKAGE_DX | 0.977770 | 0.977770 | 0.977770 | 0.977770 | 16185.57 | 25908.94 | 40.00 | 1.00 |
| SPLIT MNW_UNITARY_PACKAGE_DX | 0.838166 | 0.838166 | 0.838166 | 0.838166 | 13874.62 | 22765.58 | 40.00 | 1.00 |
| SPLIT MSE_UNITARY_PACKAGE_DX | 0.838672 | 0.838672 | 0.838672 | 0.838672 | 13882.99 | 22777.29 | 40.00 | 1.00 |
| SPLIT MNE_UNITARY_PACKAGE_DX | 0.703392 | 0.703392 | 0.703392 | 0.703392 | 11643.63 | 19731.36 | 40.00 | 1.00 |
| SPLIT MN1_UNITARY_PACKAGE_DX | 0.627840 | 0.627840 | 0.627840 | 0.627840 | 10392.98 | 18030.36 | 40.00 | 1.00 |
| SPLIT MN2_UNITARY_PACKAGE_DX | 0.626183 | 0.626183 | 0.626183 | 0.626183 | 10365.54 | 17993.04 | 40.00 | 1.00 |
| SPLIT MS1_UNITARY_PACKAGE_DX | 0.775442 | 0.775442 | 0.775442 | 0.775442 | 12836.31 | 21353.68 | 40.00 | 1.00 |
| SPLIT MS2_UNITARY_PACKAGE_DX | 0.773486 | 0.773486 | 0.773486 | 0.773486 | 12803.94 | 21309.64 | 40.00 | 1.00 |
| SPLIT TSW_UNITARY_PACKAGE_DX | 0.530308 | 0.530308 | 0.530308 | 0.530308 | 8778.48 | 13887.09 | 40.00 | 1.00 |
| SPLIT TNW_UNITARY_PACKAGE_DX | 0.464476 | 0.464476 | 0.464476 | 0.464476 | 7688.72 | 12404.78 | 40.00 | 1.00 |
| SPLIT TSE_UNITARY_PACKAGE_DX | 0.428758 | 0.428758 | 0.428758 | 0.428758 | 7097.47 | 11600.80 | 40.00 | 1.00 |
| SPLIT TNE_UNITARY_PACKAGE_DX | 0.364362 | 0.364362 | 0.364362 | 0.364362 | 6031.48 | 10150.85 | 40.00 | 1.00 |
| SPLIT TN1_UNITARY_PACKAGE_DX | 0.342583 | 0.342583 | 0.342583 | 0.342583 | 5670.97 | 9660.51 | 40.00 | 1.00 |
| SPLIT TN2_UNITARY_PACKAGE_DX | 0.339994 | 0.339994 | 0.339994 | 0.339994 | 5628.11 | 9602.22 | 40.00 | 1.00 |
| SPLIT TS1_UNITARY_PACKAGE_DX | 0.410860 | 0.410860 | 0.410860 | 0.410860 | 6801.20 | 11197.81 | 40.00 | 1.00 |
| SPLIT TS2_UNITARY_PACKAGE_DX | 0.408249 | 0.408249 | 0.408249 | 0.408249 | 6757.97 | 11139.02 | 40.00 | 1.00 |
| Design Size Rated Air Flow Rate [m3/s] | Design Size Gross Rated Total Cooling Capacity [W] | Design Size Gross Rated Sensible Heat Ratio | |
| SPLIT GSW COOLING COIL | 0.389736 | 6451.51 | 0.800655 |
| SPLIT GNW COOLING COIL | 0.319053 | 5281.46 | 0.800655 |
| SPLIT OFFICE COOLING COIL | 0.409760 | 6782.98 | 0.800655 |
| SPLIT GNE COOLING COIL | 0.280779 | 4647.89 | 0.800655 |
| SPLIT GN1 COOLING COIL | 0.250986 | 4154.71 | 0.800655 |
| SPLIT GN2 COOLING COIL | 0.250464 | 4146.07 | 0.800655 |
| SPLIT GS1 COOLING COIL | 0.326021 | 5396.80 | 0.800655 |
| SPLIT GS2 COOLING COIL | 0.327871 | 5427.42 | 0.800655 |
| SPLIT MSW COOLING COIL | 0.977770 | 16185.57 | 0.800655 |
| SPLIT MNW COOLING COIL | 0.838166 | 13874.62 | 0.800655 |
| SPLIT MSE COOLING COIL | 0.838672 | 13882.99 | 0.800655 |
| SPLIT MNE COOLING COIL | 0.703392 | 11643.63 | 0.800655 |
| SPLIT MN1 COOLING COIL | 0.627840 | 10392.98 | 0.800655 |
| SPLIT MN2 COOLING COIL | 0.626183 | 10365.54 | 0.800655 |
| SPLIT MS1 COOLING COIL | 0.775442 | 12836.31 | 0.800655 |
| SPLIT MS2 COOLING COIL | 0.773486 | 12803.94 | 0.800655 |
| SPLIT TSW COOLING COIL | 0.530308 | 8778.48 | 0.800655 |
| SPLIT TNW COOLING COIL | 0.464476 | 7688.72 | 0.800655 |
| SPLIT TSE COOLING COIL | 0.428758 | 7097.47 | 0.800655 |
| SPLIT TNE COOLING COIL | 0.364362 | 6031.48 | 0.800655 |
| SPLIT TN1 COOLING COIL | 0.342583 | 5670.97 | 0.800655 |
| SPLIT TN2 COOLING COIL | 0.339994 | 5628.11 | 0.800655 |
| SPLIT TS1 COOLING COIL | 0.410860 | 6801.20 | 0.800655 |
| SPLIT TS2 COOLING COIL | 0.408249 | 6757.97 | 0.800655 |
| Design Size Nominal Capacity [W] | |
| SPLIT GSW HEATING COIL | 10722.17 |
| SPLIT GNW HEATING COIL | 9130.81 |
| SPLIT OFFICE HEATING COIL | 12084.91 |
| SPLIT GNE HEATING COIL | 8269.12 |
| SPLIT GN1 HEATING COIL | 7598.36 |
| SPLIT GN2 HEATING COIL | 7586.61 |
| SPLIT GS1 HEATING COIL | 9287.71 |
| SPLIT GS2 HEATING COIL | 9329.35 |
| SPLIT MSW HEATING COIL | 25908.94 |
| SPLIT MNW HEATING COIL | 22765.58 |
| SPLIT MSE HEATING COIL | 22777.29 |
| SPLIT MNE HEATING COIL | 19731.36 |
| SPLIT MN1 HEATING COIL | 18030.36 |
| SPLIT MN2 HEATING COIL | 17993.04 |
| SPLIT MS1 HEATING COIL | 21353.68 |
| SPLIT MS2 HEATING COIL | 21309.64 |
| SPLIT TSW HEATING COIL | 13887.09 |
| SPLIT TNW HEATING COIL | 12404.78 |
| SPLIT TSE HEATING COIL | 11600.80 |
| SPLIT TNE HEATING COIL | 10150.85 |
| SPLIT TN1 HEATING COIL | 9660.51 |
| SPLIT TN2 HEATING COIL | 9602.22 |
| SPLIT TS1 HEATING COIL | 11197.81 |
| SPLIT TS2 HEATING COIL | 11139.02 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 09:14:30
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other Surfaces| None |
| Possible Shadow Receivers | |
| G SWALL SWA | GWINDOW1 S SWA | |
| G WWALL SWA | GWINDOW1 W SWA | |
| G NWALL NWA | GWINDOW1 N NWA | |
| G WWALL NWA | GWINDOW1 W NWA | |
| G SWALL SEA | GWINDOW1 S SEA | |
| G EWALL SEA | GWINDOW1 E SEA | |
| G NWALL NEA | GWINDOW1 N NEA | |
| G EWALL NEA | GWINDOW1 E NEA | |
| G NWALL N1A | GWINDOW1 N N1A | |
| G NWALL N2A | GWINDOW1 N N2A | |
| G SWALL S1A | GWINDOW1 S S1A | |
| G SWALL S2A | GWINDOW1 S S2A | |
| M WWALL SWA | MWINDOW1 W SWA | |
| M SWALL SWA | MWINDOW1 S SWA | |
| M NWALL NWA | MWINDOW1 N NWA | |
| M WWALL NWA | MWINDOW1 W NWA | |
| M EWALL SEA | MWINDOW1 E SEA | |
| M SWALL SEA | MWINDOW1 S SEA | |
| M NWALL NEA | MWINDOW1 N NEA | |
| M EWALL NEA | MWINDOW1 E NEA | |
| M NWALL N1A | MWINDOW1 N N1A | |
| M NWALL N2A | MWINDOW1 N N2A | |
| M SWALL S1A | MWINDOW1 S S1A | |
| M SWALL S2A | MWINDOW1 S S2A | |
| T WWALL SWA | TWINDOW1 W SWA | |
| T SWALL SWA | TWINDOW1 S SWA | |
| T NWALL NWA | TWINDOW1 N NWA | |
| T WWALL NWA | TWINDOW1 W NWA | |
| T EWALL SEA | TWINDOW1 E SEA | |
| T SWALL SEA | TWINDOW1 S SEA | |
| T NWALL NEA | TWINDOW1 N NEA | |
| T EWALL NEA | TWINDOW1 E NEA | |
| T NWALL N1A | TWINDOW1 N N1A | |
| T NWALL N2A | TWINDOW1 N N2A | |
| T SWALL S1A | TWINDOW1 S S1A | |
| T SWALL S2A | TWINDOW1 S S2A | |
| T EWALL C | TWINDOW14 | |
| G EWALL C | ENTRANCE DOOR | |
| M EWALL C | MWINDOW14 | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 09:14:30
Time Not Meeting the Adaptive Comfort Models during Occupied Hours| ASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 09:14:30
Version| Version ID | |
| 1 | 22.1 |
| #TimeSteps | Minutes per TimeStep {minutes} | |
| 1 | 6 | 10 |
| Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
| 1 | 1 | 20 | 2 | 8 |
| Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
| 1 | Yes | Yes | No | No | Yes | No |
| Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
| 1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
| Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
| 1 | 0.556 | 0.556 |
| Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
| 1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
| Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
| 1 | -3.10 | -17.70 | -19.30 | -17.60 | -15.40 | -10.30 | 0.70 | 10.60 | 16.00 | 16.90 | 14.20 | 6.70 |
| Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
| 1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
| Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
| 1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
| Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
| 1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
| Normal | Daylighting {dimensionless} | |
| 1 | 1.000 | 1.000 |
| Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
| 1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
| Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
| 1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
| Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
| 1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
| Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
| 1 | Fairbanks Intl Arpt AK USA TMY3 WMO#=702610 | 64.82 | -147.85 | -9.00 | 133.00 | 99737 | 1.1854 |
| Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
| 1 | Correlation | NA | -1.53 | 36.20 | NA |
| Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
| 1 | ApartmentMidRise | 0.000 | City | 4.00000E-002 | 0.40000 | FullExterior | 25 | 6 |
| Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
| 1 | TARP |
| Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
| 1 | TARP |
| Value {Anisotropic} | |
| 1 | Anisotropic |
| Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
| 1 | ThirdOrderBackwardDifference |
| Simulation {Yes/No} | Carbon Dioxide Concentration | |
| 1 | No | N/A |
| Simulation {Yes/No} | Generic Contaminant Concentration | |
| 1 | No | N/A |
| Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
| 1 | No | N/A | N/A | N/A |
| Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
| 1 | RegulaFalsi |
| Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
| 1 | 0.330 | 460.000 | 6.500000E-003 |
| Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
| 1 | LowerLeftCorner | Clockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
| Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
| 1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
| Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
| 1 | 0 | 0 | 0 |
| Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
| 1 | 27 | 243 | 39 |
| Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
| 1 | G SW APARTMENT | 0.0 | 0.00 | 0.00 | 0.00 | 5.79 | 3.81 | 1.52 | 1 | 1 | 1 | 0.00 | 11.58 | 0.00 | 7.62 | 0.00 | 3.05 | 3.05 | 268.97 | TARP | TARP | 88.25 | 58.52 | 46.82 | 11.71 | 6 | 2 | 0 | Yes |
| 2 | G NW APARTMENT | 0.0 | 0.00 | 9.30 | 0.00 | 5.79 | 13.11 | 1.52 | 1 | 1 | 1 | 0.00 | 11.58 | 9.30 | 16.92 | 0.00 | 3.05 | 3.05 | 268.97 | TARP | TARP | 88.25 | 58.52 | 46.82 | 11.71 | 6 | 2 | 0 | Yes |
| 3 | OFFICE | 0.0 | 34.75 | 0.00 | 0.00 | 40.54 | 3.81 | 1.52 | 1 | 1 | 1 | 34.75 | 46.33 | 0.00 | 7.62 | 0.00 | 3.05 | 3.05 | 268.97 | TARP | TARP | 88.25 | 58.52 | 46.82 | 11.71 | 6 | 2 | 0 | Yes |
| 4 | G NE APARTMENT | 0.0 | 34.75 | 9.30 | 0.00 | 40.54 | 13.11 | 1.52 | 1 | 1 | 1 | 34.75 | 46.33 | 9.30 | 16.92 | 0.00 | 3.05 | 3.05 | 268.97 | TARP | TARP | 88.25 | 58.52 | 46.82 | 11.71 | 6 | 2 | 0 | Yes |
| 5 | G N1 APARTMENT | 0.0 | 11.58 | 9.30 | 0.00 | 17.37 | 13.11 | 1.52 | 1 | 1 | 1 | 11.58 | 23.16 | 9.30 | 16.92 | 0.00 | 3.05 | 3.05 | 268.97 | TARP | TARP | 88.25 | 35.30 | 28.24 | 7.06 | 6 | 1 | 0 | Yes |
| 6 | G N2 APARTMENT | 0.0 | 23.16 | 9.30 | 0.00 | 28.95 | 13.11 | 1.52 | 1 | 1 | 1 | 23.16 | 34.75 | 9.30 | 16.92 | 0.00 | 3.05 | 3.05 | 268.97 | TARP | TARP | 88.25 | 35.30 | 28.24 | 7.06 | 6 | 1 | 0 | Yes |
| 7 | G S1 APARTMENT | 0.0 | 11.58 | 0.00 | 0.00 | 17.37 | 3.81 | 1.52 | 1 | 1 | 1 | 11.58 | 23.16 | 0.00 | 7.62 | 0.00 | 3.05 | 3.05 | 268.97 | TARP | TARP | 88.25 | 35.30 | 28.24 | 7.06 | 6 | 1 | 0 | Yes |
| 8 | G S2 APARTMENT | 0.0 | 23.16 | 0.00 | 0.00 | 28.95 | 3.81 | 1.52 | 1 | 1 | 1 | 23.16 | 34.75 | 0.00 | 7.62 | 0.00 | 3.05 | 3.05 | 268.97 | TARP | TARP | 88.25 | 35.30 | 28.24 | 7.06 | 6 | 1 | 0 | Yes |
| 9 | M SW APARTMENT | 0.0 | 0.00 | 0.00 | 3.05 | 5.79 | 3.81 | 4.57 | 1 | 1 | 2 | 0.00 | 11.58 | 0.00 | 7.62 | 3.05 | 6.10 | 3.05 | 268.97 | TARP | TARP | 88.25 | 58.52 | 46.82 | 11.71 | 6 | 2 | 0 | Yes |
| 10 | M NW APARTMENT | 0.0 | 0.00 | 9.30 | 3.05 | 5.79 | 13.11 | 4.57 | 1 | 1 | 2 | 0.00 | 11.58 | 9.30 | 16.92 | 3.05 | 6.10 | 3.05 | 268.97 | TARP | TARP | 88.25 | 58.52 | 46.82 | 11.71 | 6 | 2 | 0 | Yes |
| 11 | M SE APARTMENT | 0.0 | 34.75 | 0.00 | 3.05 | 40.54 | 3.81 | 4.57 | 1 | 1 | 2 | 34.75 | 46.33 | 0.00 | 7.62 | 3.05 | 6.10 | 3.05 | 268.97 | TARP | TARP | 88.25 | 58.52 | 46.82 | 11.71 | 6 | 2 | 0 | Yes |
| 12 | M NE APARTMENT | 0.0 | 34.75 | 9.30 | 3.05 | 40.54 | 13.11 | 4.57 | 1 | 1 | 2 | 34.75 | 46.33 | 9.30 | 16.92 | 3.05 | 6.10 | 3.05 | 268.97 | TARP | TARP | 88.25 | 58.52 | 46.82 | 11.71 | 6 | 2 | 0 | Yes |
| 13 | M N1 APARTMENT | 0.0 | 11.58 | 9.30 | 3.05 | 17.37 | 13.11 | 4.57 | 1 | 1 | 2 | 11.58 | 23.16 | 9.30 | 16.92 | 3.05 | 6.10 | 3.05 | 268.97 | TARP | TARP | 88.25 | 35.30 | 28.24 | 7.06 | 6 | 1 | 0 | Yes |
| 14 | M N2 APARTMENT | 0.0 | 23.16 | 9.30 | 3.05 | 28.95 | 13.11 | 4.57 | 1 | 1 | 2 | 23.16 | 34.75 | 9.30 | 16.92 | 3.05 | 6.10 | 3.05 | 268.97 | TARP | TARP | 88.25 | 35.30 | 28.24 | 7.06 | 6 | 1 | 0 | Yes |
| 15 | M S1 APARTMENT | 0.0 | 11.58 | 0.00 | 3.05 | 17.37 | 3.81 | 4.57 | 1 | 1 | 2 | 11.58 | 23.16 | 0.00 | 7.62 | 3.05 | 6.10 | 3.05 | 268.97 | TARP | TARP | 88.25 | 35.30 | 28.24 | 7.06 | 6 | 1 | 0 | Yes |
| 16 | M S2 APARTMENT | 0.0 | 23.16 | 0.00 | 3.05 | 28.95 | 3.81 | 4.57 | 1 | 1 | 2 | 23.16 | 34.75 | 0.00 | 7.62 | 3.05 | 6.10 | 3.05 | 268.97 | TARP | TARP | 88.25 | 35.30 | 28.24 | 7.06 | 6 | 1 | 0 | Yes |
| 17 | T SW APARTMENT | 0.0 | 0.00 | 0.00 | 9.14 | 5.79 | 3.81 | 10.67 | 1 | 1 | 1 | 0.00 | 11.58 | 0.00 | 7.62 | 9.14 | 12.19 | 3.05 | 268.97 | TARP | TARP | 88.25 | 58.52 | 46.82 | 11.71 | 6 | 2 | 0 | Yes |
| 18 | T NW APARTMENT | 0.0 | 0.00 | 9.30 | 9.14 | 5.79 | 13.11 | 10.67 | 1 | 1 | 1 | 0.00 | 11.58 | 9.30 | 16.92 | 9.14 | 12.19 | 3.05 | 268.97 | TARP | TARP | 88.25 | 58.52 | 46.82 | 11.71 | 6 | 2 | 0 | Yes |
| 19 | T SE APARTMENT | 0.0 | 34.75 | 0.00 | 9.14 | 40.54 | 3.81 | 10.67 | 1 | 1 | 1 | 34.75 | 46.33 | 0.00 | 7.62 | 9.14 | 12.19 | 3.05 | 268.97 | TARP | TARP | 88.25 | 58.52 | 46.82 | 11.71 | 6 | 2 | 0 | Yes |
| 20 | T NE APARTMENT | 0.0 | 34.75 | 9.30 | 9.14 | 40.54 | 13.11 | 10.67 | 1 | 1 | 1 | 34.75 | 46.33 | 9.30 | 16.92 | 9.14 | 12.19 | 3.05 | 268.97 | TARP | TARP | 88.25 | 58.52 | 46.82 | 11.71 | 6 | 2 | 0 | Yes |
| 21 | T N1 APARTMENT | 0.0 | 11.58 | 9.30 | 9.14 | 17.37 | 13.11 | 10.67 | 1 | 1 | 1 | 11.58 | 23.16 | 9.30 | 16.92 | 9.14 | 12.19 | 3.05 | 268.97 | TARP | TARP | 88.25 | 35.30 | 28.24 | 7.06 | 6 | 1 | 0 | Yes |
| 22 | T N2 APARTMENT | 0.0 | 23.16 | 9.30 | 9.14 | 28.95 | 13.11 | 10.67 | 1 | 1 | 1 | 23.16 | 34.75 | 9.30 | 16.92 | 9.14 | 12.19 | 3.05 | 268.97 | TARP | TARP | 88.25 | 35.30 | 28.24 | 7.06 | 6 | 1 | 0 | Yes |
| 23 | T S1 APARTMENT | 0.0 | 11.58 | 0.00 | 9.14 | 17.37 | 3.81 | 10.67 | 1 | 1 | 1 | 11.58 | 23.16 | 0.00 | 7.62 | 9.14 | 12.19 | 3.05 | 268.97 | TARP | TARP | 88.25 | 35.30 | 28.24 | 7.06 | 6 | 1 | 0 | Yes |
| 24 | T S2 APARTMENT | 0.0 | 23.16 | 0.00 | 9.14 | 28.95 | 3.81 | 10.67 | 1 | 1 | 1 | 23.16 | 34.75 | 0.00 | 7.62 | 9.14 | 12.19 | 3.05 | 268.97 | TARP | TARP | 88.25 | 35.30 | 28.24 | 7.06 | 6 | 1 | 0 | Yes |
| 25 | T CORRIDOR | 0.0 | 0.00 | 7.62 | 9.14 | 23.16 | 8.46 | 10.67 | 1 | 1 | 1 | 0.00 | 46.33 | 7.62 | 9.30 | 9.14 | 12.19 | 3.05 | 236.69 | TARP | TARP | 77.66 | 10.22 | 9.10 | 1.11 | 12 | 1 | 0 | Yes |
| 26 | G CORRIDOR | 0.0 | 0.00 | 7.62 | 0.00 | 23.16 | 8.46 | 1.52 | 1 | 1 | 1 | 0.00 | 46.33 | 7.62 | 9.30 | 0.00 | 3.05 | 3.05 | 236.69 | TARP | TARP | 77.66 | 10.22 | 6.90 | 3.32 | 12 | 1 | 0 | Yes |
| 27 | M CORRIDOR | 0.0 | 0.00 | 7.62 | 3.05 | 23.16 | 8.46 | 4.57 | 1 | 1 | 2 | 0.00 | 46.33 | 7.62 | 9.30 | 3.05 | 6.10 | 3.05 | 236.69 | TARP | TARP | 77.66 | 10.22 | 9.10 | 1.11 | 12 | 1 | 0 | Yes |
| Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
| 1 | G SW APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 2 | G NW APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 3 | OFFICE | 88.25 | 4.7 | 18.581 | 5.382E-002 | 9.753 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 16.423 | No |
| 4 | G NE APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 5 | G N1 APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 6 | G N2 APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 7 | G S1 APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 8 | G S2 APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 9 | M SW APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 10 | M NW APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 11 | M SE APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 12 | M NE APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 13 | M N1 APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 14 | M N2 APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 15 | M S1 APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 16 | M S2 APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 17 | T SW APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 18 | T NW APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 19 | T SE APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 20 | T NE APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 21 | T N1 APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 22 | T N2 APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 23 | T S1 APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 24 | T S2 APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 25 | T CORRIDOR | 77.66 | 4.2 | 18.579 | 5.382E-002 | 4.772 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 4.772 | No |
| 26 | G CORRIDOR | 77.66 | 4.2 | 18.579 | 5.382E-002 | 4.772 | 105.256 | 0.000 | 0.000 | 0.000 | 0.000 | 110.029 | No |
| 27 | M CORRIDOR | 77.66 | 4.2 | 18.579 | 5.382E-002 | 4.772 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 4.772 | No |
| Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | |
| 1 | OCCUP_GSW | OCC_APT_SCH_WORKING_FAMILY | G SW APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 3 |
| 2 | OCCUP_GNW | OCC_APT_SCH_STAY_HOME_FAMILY | G NW APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 1 | 3 |
| 3 | OCCUP_OFFICE | OCC_OFF_W_SB_SCH | OFFICE | 88.25 | 4.7 | 4.7 | 5.382E-002 | 18.581 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 5 |
| 4 | OCCUP_GNE | OCC_APT_SCH_STAY_HOME_FAMILY | G NE APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 1 | 3 |
| 5 | OCCUP_GN1 | OCC_APT_SCH_STAY_HOME_FAMILY | G N1 APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 1 | 3 |
| 6 | OCCUP_GN2 | OCC_APT_SCH_STAY_HOME_FAMILY | G N2 APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 1 | 3 |
| 7 | OCCUP_GS1 | OCC_APT_SCH_WORKING_FAMILY | G S1 APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 3 |
| 8 | OCCUP_GS2 | OCC_APT_SCH_WORKING_FAMILY | G S2 APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 3 |
| 9 | OCCUP_MSW | OCC_APT_SCH_WORKING_FAMILY | M SW APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 3 |
| 10 | OCCUP_MNW | OCC_APT_SCH_STAY_HOME_FAMILY | M NW APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 1 | 3 |
| 11 | OCCUP_MSE | OCC_APT_SCH_WORKING_FAMILY | M SE APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 3 |
| 12 | OCCUP_MNE | OCC_APT_SCH_STAY_HOME_FAMILY | M NE APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 1 | 3 |
| 13 | OCCUP_MN1 | OCC_APT_SCH_STAY_HOME_FAMILY | M N1 APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 1 | 3 |
| 14 | OCCUP_MN2 | OCC_APT_SCH_STAY_HOME_FAMILY | M N2 APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 1 | 3 |
| 15 | OCCUP_MS1 | OCC_APT_SCH_WORKING_FAMILY | M S1 APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 3 |
| 16 | OCCUP_MS2 | OCC_APT_SCH_WORKING_FAMILY | M S2 APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 3 |
| 17 | OCCUP_TSW | OCC_APT_SCH_WORKING_FAMILY | T SW APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 3 |
| 18 | OCCUP_TNW | OCC_APT_SCH_STAY_HOME_FAMILY | T NW APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 1 | 3 |
| 19 | OCCUP_TSE | OCC_APT_SCH_WORKING_FAMILY | T SE APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 3 |
| 20 | OCCUP_TNE | OCC_APT_SCH_STAY_HOME_FAMILY | T NE APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 1 | 3 |
| 21 | OCCUP_TN1 | OCC_APT_SCH_STAY_HOME_FAMILY | T N1 APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 1 | 3 |
| 22 | OCCUP_TN2 | OCC_APT_SCH_STAY_HOME_FAMILY | T N2 APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 1 | 3 |
| 23 | OCCUP_TS1 | OCC_APT_SCH_WORKING_FAMILY | T S1 APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 3 |
| 24 | OCCUP_TS2 | OCC_APT_SCH_WORKING_FAMILY | T S2 APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 3 |
| 25 | OCCUP_T CORRIDOR | OCC_APT_SCH_CORRIDOR | T CORRIDOR | 77.66 | 4.2 | 4.2 | 5.382E-002 | 18.579 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 1 | 4 |
| 26 | OCCUP_G CORRIDOR | OCC_APT_SCH_CORRIDOR | G CORRIDOR | 77.66 | 4.2 | 4.2 | 5.382E-002 | 18.579 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 1 | 4 |
| 27 | OCCUP_M CORRIDOR | OCC_APT_SCH_CORRIDOR | M CORRIDOR | 77.66 | 4.2 | 4.2 | 5.382E-002 | 18.579 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 1 | 4 |
| Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
| 1 | LIGHTING_HARDWIRED_GSW | LTG_SCH_APARTMENT_HARDWIRED | G SW APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 2 | LIGHTING_HARDWIRED_GNW | LTG_SCH_APARTMENT_HARDWIRED | G NW APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 3 | LIGHTING_HARDWIRED_OFFICE | LTG_SCH_OFFICE | OFFICE | 88.25 | 4.7 | 860.710 | 9.753 | 181.220 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 860.710 |
| 4 | LIGHTING_HARDWIRED_GNE | LTG_SCH_APARTMENT_HARDWIRED | G NE APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 5 | LIGHTING_HARDWIRED_GN1 | LTG_SCH_APARTMENT_HARDWIRED | G N1 APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 6 | LIGHTING_HARDWIRED_GN2 | LTG_SCH_APARTMENT_HARDWIRED | G N2 APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 7 | LIGHTING_HARDWIRED_GS1 | LTG_SCH_APARTMENT_HARDWIRED | G S1 APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 8 | LIGHTING_HARDWIRED_GS2 | LTG_SCH_APARTMENT_HARDWIRED | G S2 APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 9 | LIGHTING_HARDWIRED_MSW | LTG_SCH_APARTMENT_HARDWIRED | M SW APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 10 | LIGHTING_HARDWIRED_MNW | LTG_SCH_APARTMENT_HARDWIRED | M NW APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 11 | LIGHTING_HARDWIRED_MSE | LTG_SCH_APARTMENT_HARDWIRED | M SE APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 12 | LIGHTING_HARDWIRED_MNE | LTG_SCH_APARTMENT_HARDWIRED | M NE APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 13 | LIGHTING_HARDWIRED_MN1 | LTG_SCH_APARTMENT_HARDWIRED | M N1 APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 14 | LIGHTING_HARDWIRED_MN2 | LTG_SCH_APARTMENT_HARDWIRED | M N2 APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 15 | LIGHTING_HARDWIRED_MS1 | LTG_SCH_APARTMENT_HARDWIRED | M S1 APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 16 | LIGHTING_HARDWIRED_MS2 | LTG_SCH_APARTMENT_HARDWIRED | M S2 APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 17 | LIGHTING_HARDWIRED_TSW | LTG_SCH_APARTMENT_HARDWIRED | T SW APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 18 | LIGHTING_HARDWIRED_TNW | LTG_SCH_APARTMENT_HARDWIRED | T NW APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 19 | LIGHTING_HARDWIRED_TSE | LTG_SCH_APARTMENT_HARDWIRED | T SE APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 20 | LIGHTING_HARDWIRED_TNE | LTG_SCH_APARTMENT_HARDWIRED | T NE APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 21 | LIGHTING_HARDWIRED_TN1 | LTG_SCH_APARTMENT_HARDWIRED | T N1 APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 22 | LIGHTING_HARDWIRED_TN2 | LTG_SCH_APARTMENT_HARDWIRED | T N2 APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 23 | LIGHTING_HARDWIRED_TS1 | LTG_SCH_APARTMENT_HARDWIRED | T S1 APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 24 | LIGHTING_HARDWIRED_TS2 | LTG_SCH_APARTMENT_HARDWIRED | T S2 APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 25 | LIGHTING_HARDWIRED_GC | LTG_SCH_CORRIDOR | G CORRIDOR | 77.66 | 4.2 | 370.628 | 4.772 | 88.667 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 370.628 |
| 26 | LIGHTING_HARDWIRED_MC | LTG_SCH_CORRIDOR | M CORRIDOR | 77.66 | 4.2 | 370.628 | 4.772 | 88.667 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 370.628 |
| 27 | LIGHTING_HARDWIRED_TC | LTG_SCH_CORRIDOR | T CORRIDOR | 77.66 | 4.2 | 370.628 | 4.772 | 88.667 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 370.628 |
| 28 | LIGHTING_PLUGIN_GSW | LTG_SCH_APARTMENT_PLUGIN | G SW APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| 29 | LIGHTING_PLUGIN_GNW | LTG_SCH_APARTMENT_PLUGIN | G NW APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| 30 | LIGHTING_PLUGIN_GNE | LTG_SCH_APARTMENT_PLUGIN | G NE APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| 31 | LIGHTING_PLUGIN_GN1 | LTG_SCH_APARTMENT_PLUGIN | G N1 APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| 32 | LIGHTING_PLUGIN_GN2 | LTG_SCH_APARTMENT_PLUGIN | G N2 APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| 33 | LIGHTING_PLUGIN_GS1 | LTG_SCH_APARTMENT_PLUGIN | G S1 APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| 34 | LIGHTING_PLUGIN_GS2 | LTG_SCH_APARTMENT_PLUGIN | G S2 APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| 35 | LIGHTING_PLUGIN_MSW | LTG_SCH_APARTMENT_PLUGIN | M SW APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| 36 | LIGHTING_PLUGIN_MNW | LTG_SCH_APARTMENT_PLUGIN | M NW APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| 37 | LIGHTING_PLUGIN_MSE | LTG_SCH_APARTMENT_PLUGIN | M SE APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| 38 | LIGHTING_PLUGIN_MNE | LTG_SCH_APARTMENT_PLUGIN | M NE APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| 39 | LIGHTING_PLUGIN_MN1 | LTG_SCH_APARTMENT_PLUGIN | M N1 APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| 40 | LIGHTING_PLUGIN_MN2 | LTG_SCH_APARTMENT_PLUGIN | M N2 APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| 41 | LIGHTING_PLUGIN_MS1 | LTG_SCH_APARTMENT_PLUGIN | M S1 APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| 42 | LIGHTING_PLUGIN_MS2 | LTG_SCH_APARTMENT_PLUGIN | M S2 APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| 43 | LIGHTING_PLUGIN_TSW | LTG_SCH_APARTMENT_PLUGIN | T SW APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| 44 | LIGHTING_PLUGIN_TNW | LTG_SCH_APARTMENT_PLUGIN | T NW APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| 45 | LIGHTING_PLUGIN_TSE | LTG_SCH_APARTMENT_PLUGIN | T SE APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| 46 | LIGHTING_PLUGIN_TNE | LTG_SCH_APARTMENT_PLUGIN | T NE APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| 47 | LIGHTING_PLUGIN_TN1 | LTG_SCH_APARTMENT_PLUGIN | T N1 APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| 48 | LIGHTING_PLUGIN_TN2 | LTG_SCH_APARTMENT_PLUGIN | T N2 APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| 49 | LIGHTING_PLUGIN_TS1 | LTG_SCH_APARTMENT_PLUGIN | T S1 APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| 50 | LIGHTING_PLUGIN_TS2 | LTG_SCH_APARTMENT_PLUGIN | T S2 APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
| 1 | PLUG_GSW | EQP_APT_SCH | G SW APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 2 | PLUG_GNW | EQP_APT_SCH | G NW APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 3 | PLUG_OFFICE | EQP_OFF_SCH | OFFICE | 88.25 | 4.7 | 588.623 | 6.670 | 123.933 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 588.623 |
| 4 | PLUG_GNE | EQP_APT_SCH | G NE APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 5 | PLUG_GN1 | EQP_APT_SCH | G N1 APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 6 | PLUG_GN2 | EQP_APT_SCH | G N2 APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 7 | PLUG_GS1 | EQP_APT_SCH | G S1 APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 8 | PLUG_GS2 | EQP_APT_SCH | G S2 APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 9 | PLUG_MSW | EQP_APT_SCH | M SW APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 10 | PLUG_MNW | EQP_APT_SCH | M NW APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 11 | PLUG_MSE | EQP_APT_SCH | M SE APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 12 | PLUG_MNE | EQP_APT_SCH | M NE APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 13 | PLUG_MN1 | EQP_APT_SCH | M N1 APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 14 | PLUG_MN2 | EQP_APT_SCH | M N2 APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 15 | PLUG_MS1 | EQP_APT_SCH | M S1 APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 16 | PLUG_MS2 | EQP_APT_SCH | M S2 APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 17 | PLUG_TSW | EQP_APT_SCH | T SW APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 18 | PLUG_TNW | EQP_APT_SCH | T NW APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 19 | PLUG_TSE | EQP_APT_SCH | T SE APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 20 | PLUG_TNE | EQP_APT_SCH | T NE APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 21 | PLUG_TN1 | EQP_APT_SCH | T N1 APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 22 | PLUG_TN2 | EQP_APT_SCH | T N2 APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 23 | PLUG_TS1 | EQP_APT_SCH | T S1 APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 24 | PLUG_TS2 | EQP_APT_SCH | T S2 APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 25 | G CORRIDOR_ELEVATORS_EQUIP | BLDG_ELEVATORS | G CORRIDOR | 77.66 | 4.2 | 8012.150 | 103.170 | 1916.782 | 0.000 | 0.000 | 0.950 | 5.000E-002 | ElevatorLift | 961.458 | 4006.075 |
| 26 | ELEVATORS_LIGHTS_FAN | ELEV_LIGHT_FAN_SCH_24_7 | G CORRIDOR | 77.66 | 4.2 | 162.000 | 2.086 | 38.756 | 0.000 | 0.000 | 0.950 | 5.000E-002 | ElevatorLightsFan | 162.000 | 162.000 |
| Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
| 1 | PolygonClipping | Periodic | 20 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
| Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
| 1 | WaterHeater:Mixed | G SW APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.496 | 0.7729 |
| 2 | WaterHeater:Mixed | G NW APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.496 | 0.7729 |
| 3 | WaterHeater:Mixed | G NE APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.496 | 0.7729 |
| 4 | WaterHeater:Mixed | G N1 APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.496 | 0.7729 |
| 5 | WaterHeater:Mixed | G N2 APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.496 | 0.7729 |
| 6 | WaterHeater:Mixed | G S1 APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.496 | 0.7729 |
| 7 | WaterHeater:Mixed | G S2 APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.496 | 0.7729 |
| 8 | WaterHeater:Mixed | M SW APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.498 | 0.7911 |
| 9 | WaterHeater:Mixed | M NW APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.498 | 0.7911 |
| 10 | WaterHeater:Mixed | M SE APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.498 | 0.7911 |
| 11 | WaterHeater:Mixed | M NE APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.498 | 0.7911 |
| 12 | WaterHeater:Mixed | M N1 APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.498 | 0.7911 |
| 13 | WaterHeater:Mixed | M N2 APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.498 | 0.7911 |
| 14 | WaterHeater:Mixed | M S1 APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.498 | 0.7911 |
| 15 | WaterHeater:Mixed | M S2 APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.498 | 0.7911 |
| 16 | WaterHeater:Mixed | T SW APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.496 | 0.7729 |
| 17 | WaterHeater:Mixed | T NW APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.496 | 0.7729 |
| 18 | WaterHeater:Mixed | T SE APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.496 | 0.7729 |
| 19 | WaterHeater:Mixed | T NE APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.496 | 0.7729 |
| 20 | WaterHeater:Mixed | T N1 APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.496 | 0.7729 |
| 21 | WaterHeater:Mixed | T N2 APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.496 | 0.7729 |
| 22 | WaterHeater:Mixed | T S1 APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.496 | 0.7729 |
| 23 | WaterHeater:Mixed | T S2 APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.496 | 0.7729 |
| Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
| 1 | G SWALL SWA | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 2 | GWINDOW1 S SWA | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 3 | G WWALL SWA | 0 | 154.67 | 58.21 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 4 | GWINDOW1 W SWA | 0 | 154.67 | 58.21 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 5 | G NIWALL SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 6 | G EIWALL SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 7 | G GFLOOR SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 8 | G CEILIN SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 9 | G INTERNALMASS SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 10 | G NWALL NWA | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 11 | GWINDOW1 N NWA | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 12 | G WWALL NWA | 0 | 154.67 | 58.21 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 13 | GWINDOW1 W NWA | 0 | 154.67 | 58.21 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 14 | G SIWALL NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 15 | G EIWALL NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 16 | G GFLOOR NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 17 | G CEILIN NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 18 | G INTERNALMASS NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 19 | G SWALL SEA | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 20 | GWINDOW1 S SEA | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 21 | G EWALL SEA | 0 | 154.67 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 22 | GWINDOW1 E SEA | 0 | 154.67 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 23 | G NIWALL SEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 24 | iz-G EIWALL S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 25 | G GFLOOR SEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 26 | G CEILIN SEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 27 | G INTERNALMASS SEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 28 | G NWALL NEA | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 29 | GWINDOW1 N NEA | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 30 | G EWALL NEA | 0 | 154.67 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 31 | GWINDOW1 E NEA | 0 | 154.67 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 32 | G SIWALL NEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 33 | iz-G EIWALL N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 34 | G GFLOOR NEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 35 | G CEILIN NEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 36 | G INTERNALMASS NEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 37 | G NWALL N1A | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 3 | No | No |
| 38 | GWINDOW1 N N1A | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 2 | No | No |
| 39 | G SIWALL N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 40 | G EIWALL N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 41 | iz-G EIWALL NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 42 | G GFLOOR N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 43 | G CEILIN N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 44 | G INTERNALMASS N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 45 | G NWALL N2A | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 3 | No | No |
| 46 | GWINDOW1 N N2A | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 2 | No | No |
| 47 | G SIWALL N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 48 | G EIWALL N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 49 | iz-G EIWALL N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 50 | G GFLOOR N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 51 | G CEILIN N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 52 | G INTERNALMASS N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 53 | G SWALL S1A | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 3 | No | No |
| 54 | GWINDOW1 S S1A | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 2 | No | No |
| 55 | G NIWALL S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 56 | G EIWALL S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 57 | iz-G EIWALL SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 58 | G GFLOOR S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 59 | G CEILIN S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 60 | G INTERNALMASS S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 61 | G SWALL S2A | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 3 | No | No |
| 62 | GWINDOW1 S S2A | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 2 | No | No |
| 63 | G NIWALL S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 64 | G EIWALL S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 65 | iz-G EIWALL S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 66 | G GFLOOR S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 67 | G CEILIN S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 68 | G INTERNALMASS S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 69 | M WWALL SWA | 0 | 154.67 | 58.21 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 70 | MWINDOW1 W SWA | 0 | 154.67 | 58.21 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 71 | M SWALL SWA | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 72 | MWINDOW1 S SWA | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 73 | M NIWALL SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 74 | M EIWALL SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 75 | M GFLOOR SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 76 | M CEILIN SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 77 | M INTERNALMASS SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 78 | M NWALL NWA | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 79 | MWINDOW1 N NWA | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 80 | M WWALL NWA | 0 | 154.67 | 58.21 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 81 | MWINDOW1 W NWA | 0 | 154.67 | 58.21 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 82 | M SIWALL NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 83 | M EIWALL NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 84 | M GFLOOR NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 85 | M CEILIN NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 86 | M INTERNALMASS NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 87 | M EWALL SEA | 0 | 154.67 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 88 | MWINDOW1 E SEA | 0 | 154.67 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 89 | M SWALL SEA | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 90 | MWINDOW1 S SEA | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 91 | M NIWALL SEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 92 | iz-M EIWALL S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 93 | M GFLOOR SEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 94 | M CEILIN SEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 95 | M INTERNALMASS SEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 96 | M NWALL NEA | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 97 | MWINDOW1 N NEA | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 98 | M EWALL NEA | 0 | 154.67 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 99 | MWINDOW1 E NEA | 0 | 154.67 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 100 | M SIWALL NEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 101 | iz-M EIWALL N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 102 | M GFLOOR NEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 103 | M CEILIN NEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 104 | M INTERNALMASS NEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 105 | M NWALL N1A | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 3 | No | No |
| 106 | MWINDOW1 N N1A | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 2 | No | No |
| 107 | M SIWALL N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 108 | M EIWALL N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 109 | iz-M EIWALL NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 110 | M GFLOOR N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 111 | M CEILIN N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 112 | M INTERNALMASS N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 113 | M NWALL N2A | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 3 | No | No |
| 114 | MWINDOW1 N N2A | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 2 | No | No |
| 115 | M SIWALL N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 116 | M EIWALL N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 117 | iz-M EIWALL N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 118 | M GFLOOR N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 119 | M CEILIN N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 120 | M INTERNALMASS N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 121 | M SWALL S1A | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 3 | No | No |
| 122 | MWINDOW1 S S1A | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 2 | No | No |
| 123 | M NIWALL S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 124 | M EIWALL S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 125 | iz-M EIWALL SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 126 | M GFLOOR S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 127 | M CEILIN S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 128 | M INTERNALMASS S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 129 | M SWALL S2A | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 3 | No | No |
| 130 | MWINDOW1 S S2A | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 2 | No | No |
| 131 | M NIWALL S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 132 | M EIWALL S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 133 | iz-M EIWALL S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 134 | M GFLOOR S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 135 | M CEILIN S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 136 | M INTERNALMASS S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 137 | T WWALL SWA | 0 | 154.67 | 58.21 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 138 | TWINDOW1 W SWA | 0 | 154.67 | 58.21 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 139 | T SWALL SWA | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 140 | TWINDOW1 S SWA | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 141 | T NIWALL SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 142 | T EIWALL SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 143 | T GFLOOR SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 144 | T ROOF SWA | 0 | 783.65 | 155.90 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 145 | T INTERNALMASS SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 146 | T NWALL NWA | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 147 | TWINDOW1 N NWA | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 148 | T WWALL NWA | 0 | 154.67 | 58.21 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 149 | TWINDOW1 W NWA | 0 | 154.67 | 58.21 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 150 | T SIWALL NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 151 | T EIWALL NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 152 | T GFLOOR NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 153 | T ROOF NWA | 0 | 783.65 | 155.90 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 154 | T INTERNALMASS NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 155 | T EWALL SEA | 0 | 154.67 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 156 | TWINDOW1 E SEA | 0 | 154.67 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 157 | T SWALL SEA | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 158 | TWINDOW1 S SEA | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 159 | T NIWALL SEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 160 | iz-T EIWALL S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 161 | T GFLOOR SEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 162 | T ROOF SEA | 0 | 783.65 | 155.90 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 163 | T INTERNALMASS SEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 164 | T NWALL NEA | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 165 | TWINDOW1 N NEA | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 166 | T EWALL NEA | 0 | 154.67 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 167 | TWINDOW1 E NEA | 0 | 154.67 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 168 | T SIWALL NEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 169 | iz-T EIWALL N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 170 | T GFLOOR NEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 171 | T ROOF NEA | 0 | 783.65 | 155.90 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 172 | T INTERNALMASS NEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 173 | T NWALL N1A | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 3 | No | No |
| 174 | TWINDOW1 N N1A | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 2 | No | No |
| 175 | T SIWALL N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 176 | T EIWALL N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 177 | iz-T EIWALL NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 178 | T GFLOOR N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 179 | T ROOF N1A | 0 | 783.65 | 155.90 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 180 | T INTERNALMASS N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 181 | T NWALL N2A | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 3 | No | No |
| 182 | TWINDOW1 N N2A | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 2 | No | No |
| 183 | T SIWALL N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 184 | T EIWALL N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 185 | iz-T EIWALL N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 186 | T GFLOOR N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 187 | T ROOF N2A | 0 | 783.65 | 155.90 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 188 | T INTERNALMASS N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 189 | T SWALL S1A | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 3 | No | No |
| 190 | TWINDOW1 S S1A | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 2 | No | No |
| 191 | T NIWALL S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 192 | T EIWALL S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 193 | iz-T EIWALL SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 194 | T GFLOOR S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 195 | T ROOF S1A | 0 | 783.65 | 155.90 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 196 | T INTERNALMASS S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 197 | T SWALL S2A | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 3 | No | No |
| 198 | TWINDOW1 S S2A | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 2 | No | No |
| 199 | T NIWALL S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 200 | T EIWALL S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 201 | iz-T EIWALL S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 202 | T GFLOOR S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 203 | T ROOF S2A | 0 | 783.65 | 155.90 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 204 | T INTERNALMASS S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 205 | T WWALL C | 0 | 154.67 | 58.21 | 12.19 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 3 | No | No |
| 206 | T EWALL C | 0 | 154.67 | 123.02 | 12.19 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 3 | No | No |
| 207 | TWINDOW14 | 0 | 154.67 | 123.02 | 12.19 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 2 | No | No |
| 208 | iz-T NIWALL SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 209 | iz-T NIWALL S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 210 | iz-T NIWALL S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 211 | iz-T NIWALL SEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 212 | iz-T SIWALL NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 213 | iz-T SIWALL N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 214 | iz-T SIWALL N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 215 | iz-T SIWALL NEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 216 | T FLOOR C | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 217 | T ROOF C | 0 | 783.65 | 155.90 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 218 | G WWALL C | 0 | 154.67 | 58.21 | 12.19 | 0 | 3.05 | 3.35 | 3.24 | 0.32 | 4 | No | No |
| 219 | G EWALL C | 0 | 154.67 | 123.02 | 12.19 | 0 | 3.05 | 3.35 | 3.24 | 0.32 | 4 | No | No |
| 220 | ENTRANCE DOOR | 0 | 154.67 | 123.02 | 12.19 | 0 | 3.05 | 3.35 | 3.24 | 0.32 | 1 | No | No |
| 221 | iz-G NIWALL SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.32 | 0 | No | No |
| 222 | iz-G NIWALL S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.32 | 0 | No | No |
| 223 | iz-G NIWALL S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.32 | 0 | No | No |
| 224 | iz-G NIWALL SEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.32 | 0 | No | No |
| 225 | iz-G SIWALL NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.32 | 0 | No | No |
| 226 | iz-G SIWALL N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.32 | 0 | No | No |
| 227 | iz-G SIWALL N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.32 | 0 | No | No |
| 228 | iz-G SIWALL NEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.32 | 0 | No | No |
| 229 | G FLOOR C | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.32 | 0 | No | No |
| 230 | G CEILING C | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.32 | 0 | No | No |
| 231 | M WWALL C | 0 | 154.67 | 58.21 | 12.19 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 4 | No | No |
| 232 | M EWALL C | 0 | 154.67 | 123.02 | 12.19 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 3 | No | No |
| 233 | MWINDOW14 | 0 | 154.67 | 123.02 | 12.19 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 2 | No | No |
| 234 | iz-M NIWALL SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 235 | iz-M NIWALL S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 236 | iz-M NIWALL S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 237 | iz-M NIWALL SEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 238 | iz-M SIWALL NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 239 | iz-M SIWALL N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 240 | iz-M SIWALL N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 241 | iz-M SIWALL NEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 242 | M FLOOR C | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 243 | M CEILING C | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
| 1 | INFIL_GSW | INF_APT_SCH | G SW APARTMENT | 88.25 | 2.5 | 3.333E-002 | 3.777E-004 | 5.696E-004 | 0.446 | 0.000 | 0.000 | 0.224 | 0.000 |
| 2 | INFIL_GNW | INF_APT_SCH | G NW APARTMENT | 88.25 | 2.5 | 3.333E-002 | 3.777E-004 | 5.696E-004 | 0.446 | 0.000 | 0.000 | 0.224 | 0.000 |
| 3 | INFIL_OFFICE | INF_OFF_SCH | OFFICE | 88.25 | 4.7 | 3.333E-002 | 3.777E-004 | 5.696E-004 | 0.446 | 0.000 | 0.000 | 0.224 | 0.000 |
| 4 | INFIL_GNE | INF_APT_SCH | G NE APARTMENT | 88.25 | 2.5 | 3.333E-002 | 3.777E-004 | 5.696E-004 | 0.446 | 0.000 | 0.000 | 0.224 | 0.000 |
| 5 | INFIL_GN1 | INF_APT_SCH | G N1 APARTMENT | 88.25 | 2.5 | 2.011E-002 | 2.278E-004 | 5.696E-004 | 0.269 | 0.000 | 0.000 | 0.224 | 0.000 |
| 6 | INFIL_GN2 | INF_APT_SCH | G N2 APARTMENT | 88.25 | 2.5 | 2.011E-002 | 2.278E-004 | 5.696E-004 | 0.269 | 0.000 | 0.000 | 0.224 | 0.000 |
| 7 | INFIL_GS1 | INF_APT_SCH | G S1 APARTMENT | 88.25 | 2.5 | 2.011E-002 | 2.278E-004 | 5.696E-004 | 0.269 | 0.000 | 0.000 | 0.224 | 0.000 |
| 8 | INFIL_GS2 | INF_APT_SCH | G S2 APARTMENT | 88.25 | 2.5 | 2.011E-002 | 2.278E-004 | 5.696E-004 | 0.269 | 0.000 | 0.000 | 0.224 | 0.000 |
| 9 | INFIL_MSW | INF_APT_SCH | M SW APARTMENT | 88.25 | 2.5 | 3.333E-002 | 3.777E-004 | 5.696E-004 | 0.446 | 0.000 | 0.000 | 0.224 | 0.000 |
| 10 | INFIL_MNW | INF_APT_SCH | M NW APARTMENT | 88.25 | 2.5 | 3.333E-002 | 3.777E-004 | 5.696E-004 | 0.446 | 0.000 | 0.000 | 0.224 | 0.000 |
| 11 | INFIL_MSE | INF_APT_SCH | M SE APARTMENT | 88.25 | 2.5 | 3.333E-002 | 3.777E-004 | 5.696E-004 | 0.446 | 0.000 | 0.000 | 0.224 | 0.000 |
| 12 | INFIL_MNE | INF_APT_SCH | M NE APARTMENT | 88.25 | 2.5 | 3.333E-002 | 3.777E-004 | 5.696E-004 | 0.446 | 0.000 | 0.000 | 0.224 | 0.000 |
| 13 | INFIL_MN1 | INF_APT_SCH | M N1 APARTMENT | 88.25 | 2.5 | 2.011E-002 | 2.278E-004 | 5.696E-004 | 0.269 | 0.000 | 0.000 | 0.224 | 0.000 |
| 14 | INFIL_MN2 | INF_APT_SCH | M N2 APARTMENT | 88.25 | 2.5 | 2.011E-002 | 2.278E-004 | 5.696E-004 | 0.269 | 0.000 | 0.000 | 0.224 | 0.000 |
| 15 | INFIL_MS1 | INF_APT_SCH | M S1 APARTMENT | 88.25 | 2.5 | 2.011E-002 | 2.278E-004 | 5.696E-004 | 0.269 | 0.000 | 0.000 | 0.224 | 0.000 |
| 16 | INFIL_MS2 | INF_APT_SCH | M S2 APARTMENT | 88.25 | 2.5 | 2.011E-002 | 2.278E-004 | 5.696E-004 | 0.269 | 0.000 | 0.000 | 0.224 | 0.000 |
| 17 | INFIL_SW | INF_APT_SCH | T SW APARTMENT | 88.25 | 2.5 | 3.333E-002 | 3.777E-004 | 2.271E-004 | 0.446 | 0.000 | 0.000 | 0.224 | 0.000 |
| 18 | INFIL_NW | INF_APT_SCH | T NW APARTMENT | 88.25 | 2.5 | 3.333E-002 | 3.777E-004 | 2.271E-004 | 0.446 | 0.000 | 0.000 | 0.224 | 0.000 |
| 19 | INFIL_SE | INF_APT_SCH | T SE APARTMENT | 88.25 | 2.5 | 3.333E-002 | 3.777E-004 | 2.271E-004 | 0.446 | 0.000 | 0.000 | 0.224 | 0.000 |
| 20 | INFIL_NE | INF_APT_SCH | T NE APARTMENT | 88.25 | 2.5 | 3.333E-002 | 3.777E-004 | 2.271E-004 | 0.446 | 0.000 | 0.000 | 0.224 | 0.000 |
| 21 | INFIL_TN1 | INF_APT_SCH | T N1 APARTMENT | 88.25 | 2.5 | 2.011E-002 | 2.278E-004 | 1.627E-004 | 0.269 | 0.000 | 0.000 | 0.224 | 0.000 |
| 22 | INFIL_TN2 | INF_APT_SCH | T N2 APARTMENT | 88.25 | 2.5 | 2.011E-002 | 2.278E-004 | 1.627E-004 | 0.269 | 0.000 | 0.000 | 0.224 | 0.000 |
| 23 | INFIL_TS1 | INF_APT_SCH | T S1 APARTMENT | 88.25 | 2.5 | 2.011E-002 | 2.278E-004 | 1.627E-004 | 0.269 | 0.000 | 0.000 | 0.224 | 0.000 |
| 24 | INFIL_TS2 | INF_APT_SCH | T S2 APARTMENT | 88.25 | 2.5 | 2.011E-002 | 2.278E-004 | 1.627E-004 | 0.269 | 0.000 | 0.000 | 0.224 | 0.000 |
| 25 | INFIL_GC | INF_COR_SCH | G CORRIDOR | 77.66 | 4.2 | 5.820E-003 | 7.494E-005 | 5.696E-004 | 8.852E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
| 26 | DOOR_INFIL_GC | INFIL_DOOR_OPENING_SCH | G CORRIDOR | 77.66 | 4.2 | 0.521 | 6.703E-003 | 5.094E-002 | 7.917 | 1.000 | 0.000 | 0.000 | 0.000 |
| 27 | INFIL_MC | INF_COR_SCH | M CORRIDOR | 77.66 | 4.2 | 5.820E-003 | 7.494E-005 | 5.696E-004 | 8.852E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
| 28 | INFIL_TC | INF_COR_SCH | T CORRIDOR | 77.66 | 4.2 | 5.820E-003 | 7.494E-005 | 6.623E-005 | 8.852E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
| Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
| 1 | G SW APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | G SW APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 2 | G NW APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | G NW APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 3 | G NE APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | G NE APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 4 | G N1 APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | G N1 APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 5 | G N2 APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | G N2 APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 6 | G S1 APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | G S1 APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 7 | G S2 APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | G S2 APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 8 | M SW APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | M SW APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 9 | M NW APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | M NW APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 10 | M SE APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | M SE APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 11 | M NE APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | M NE APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 12 | M N1 APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | M N1 APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 13 | M N2 APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | M N2 APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 14 | M S1 APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | M S1 APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 15 | M S2 APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | M S2 APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 16 | T SW APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | T SW APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 17 | T NW APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | T NW APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 18 | T SE APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | T SE APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 19 | T NE APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | T NE APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 20 | T N1 APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | T N1 APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 21 | T N2 APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | T N2 APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 22 | T S1 APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | T S1 APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 23 | T S2 APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | T S2 APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| Simple | |
| 1 | Simple |
| Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
| 1 | G SW APARTMENT | Mixing/Well-Stirred |
| 2 | G NW APARTMENT | Mixing/Well-Stirred |
| 3 | OFFICE | Mixing/Well-Stirred |
| 4 | G NE APARTMENT | Mixing/Well-Stirred |
| 5 | G N1 APARTMENT | Mixing/Well-Stirred |
| 6 | G N2 APARTMENT | Mixing/Well-Stirred |
| 7 | G S1 APARTMENT | Mixing/Well-Stirred |
| 8 | G S2 APARTMENT | Mixing/Well-Stirred |
| 9 | M SW APARTMENT | Mixing/Well-Stirred |
| 10 | M NW APARTMENT | Mixing/Well-Stirred |
| 11 | M SE APARTMENT | Mixing/Well-Stirred |
| 12 | M NE APARTMENT | Mixing/Well-Stirred |
| 13 | M N1 APARTMENT | Mixing/Well-Stirred |
| 14 | M N2 APARTMENT | Mixing/Well-Stirred |
| 15 | M S1 APARTMENT | Mixing/Well-Stirred |
| 16 | M S2 APARTMENT | Mixing/Well-Stirred |
| 17 | T SW APARTMENT | Mixing/Well-Stirred |
| 18 | T NW APARTMENT | Mixing/Well-Stirred |
| 19 | T SE APARTMENT | Mixing/Well-Stirred |
| 20 | T NE APARTMENT | Mixing/Well-Stirred |
| 21 | T N1 APARTMENT | Mixing/Well-Stirred |
| 22 | T N2 APARTMENT | Mixing/Well-Stirred |
| 23 | T S1 APARTMENT | Mixing/Well-Stirred |
| 24 | T S2 APARTMENT | Mixing/Well-Stirred |
| 25 | T CORRIDOR | Mixing/Well-Stirred |
| 26 | G CORRIDOR | Mixing/Well-Stirred |
| 27 | M CORRIDOR | Mixing/Well-Stirred |
| No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
| 1 | NoMultizoneOrDistribution |
| Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
| 1 | 1.000 | 1.000 | 1.000 | 1.000 |
| Value | |
| 1 | 6 |
| Sizing Factor ID | Value | |
| 1 | Global | 1.2000 |
| 2 | Zone G SW APARTMENT | 1.2000 |
| 3 | Zone G NW APARTMENT | 1.2000 |
| 4 | Zone OFFICE | 1.2000 |
| 5 | Zone G NE APARTMENT | 1.2000 |
| 6 | Zone G N1 APARTMENT | 1.2000 |
| 7 | Zone G N2 APARTMENT | 1.2000 |
| 8 | Zone G S1 APARTMENT | 1.2000 |
| 9 | Zone G S2 APARTMENT | 1.2000 |
| 10 | Zone M SW APARTMENT | 1.2000 |
| 11 | Zone M NW APARTMENT | 1.2000 |
| 12 | Zone M SE APARTMENT | 1.2000 |
| 13 | Zone M NE APARTMENT | 1.2000 |
| 14 | Zone M N1 APARTMENT | 1.2000 |
| 15 | Zone M N2 APARTMENT | 1.2000 |
| 16 | Zone M S1 APARTMENT | 1.2000 |
| 17 | Zone M S2 APARTMENT | 1.2000 |
| 18 | Zone T SW APARTMENT | 1.2000 |
| 19 | Zone T NW APARTMENT | 1.2000 |
| 20 | Zone T SE APARTMENT | 1.2000 |
| 21 | Zone T NE APARTMENT | 1.2000 |
| 22 | Zone T N1 APARTMENT | 1.2000 |
| 23 | Zone T N2 APARTMENT | 1.2000 |
| 24 | Zone T S1 APARTMENT | 1.2000 |
| 25 | Zone T S2 APARTMENT | 1.2000 |
| Sizing Factor ID | Value | |
| 1 | Global | 1.2000 |
| 2 | Zone G SW APARTMENT | 1.2000 |
| 3 | Zone G NW APARTMENT | 1.2000 |
| 4 | Zone OFFICE | 1.2000 |
| 5 | Zone G NE APARTMENT | 1.2000 |
| 6 | Zone G N1 APARTMENT | 1.2000 |
| 7 | Zone G N2 APARTMENT | 1.2000 |
| 8 | Zone G S1 APARTMENT | 1.2000 |
| 9 | Zone G S2 APARTMENT | 1.2000 |
| 10 | Zone M SW APARTMENT | 1.2000 |
| 11 | Zone M NW APARTMENT | 1.2000 |
| 12 | Zone M SE APARTMENT | 1.2000 |
| 13 | Zone M NE APARTMENT | 1.2000 |
| 14 | Zone M N1 APARTMENT | 1.2000 |
| 15 | Zone M N2 APARTMENT | 1.2000 |
| 16 | Zone M S1 APARTMENT | 1.2000 |
| 17 | Zone M S2 APARTMENT | 1.2000 |
| 18 | Zone T SW APARTMENT | 1.2000 |
| 19 | Zone T NW APARTMENT | 1.2000 |
| 20 | Zone T SE APARTMENT | 1.2000 |
| 21 | Zone T NE APARTMENT | 1.2000 |
| 22 | Zone T N1 APARTMENT | 1.2000 |
| 23 | Zone T N2 APARTMENT | 1.2000 |
| 24 | Zone T S1 APARTMENT | 1.2000 |
| 25 | Zone T S2 APARTMENT | 1.2000 |
| Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
| 1 | G SW APARTMENT | Cooling | 4515.54424 | 5418.65308 | 0.32478 | 0.38974 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 23.42200 | 7.00114E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 2 | G SW APARTMENT | Heating | 3328.09953 | 3993.71944 | 0.14567 | 0.17481 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:50:00 | -41.90000 | 6.45023E-005 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 3 | G NW APARTMENT | Cooling | 3714.03026 | 4456.83631 | 0.26588 | 0.31905 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 23.42200 | 7.00114E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 4 | G NW APARTMENT | Heating | 3208.83448 | 3850.60138 | 0.14045 | 0.16854 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:50:00 | -41.90000 | 6.45023E-005 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 5 | OFFICE | Cooling | 4686.52244 | 5623.82693 | 0.34147 | 0.40976 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 21.79000 | 6.99871E-003 | 88.24927 | 4.74953 | 3.81060E-002 | 0.00000 |
| 6 | OFFICE | Heating | 3836.38331 | 4603.65997 | 0.16792 | 0.20150 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 18:50:00 | -41.90000 | 6.45023E-005 | 88.24927 | 4.74953 | 3.81060E-002 | 0.00000 |
| 7 | G NE APARTMENT | Cooling | 3280.01322 | 3936.01586 | 0.23398 | 0.28078 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 23.42200 | 7.00114E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 8 | G NE APARTMENT | Heating | 3214.07425 | 3856.88910 | 0.14068 | 0.16882 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:50:00 | -41.90000 | 6.45023E-005 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 9 | G N1 APARTMENT | Cooling | 2941.56968 | 3529.88362 | 0.20915 | 0.25099 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 23.42200 | 7.00114E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 10 | G N1 APARTMENT | Heating | 2191.14759 | 2629.37711 | 9.59081E-002 | 0.11509 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:50:00 | -41.90000 | 6.45023E-005 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 11 | G N2 APARTMENT | Cooling | 2935.64276 | 3522.77131 | 0.20872 | 0.25046 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 23.42200 | 7.00114E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 12 | G N2 APARTMENT | Heating | 2191.28570 | 2629.54284 | 9.59141E-002 | 0.11510 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:50:00 | -41.90000 | 6.45023E-005 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 13 | G S1 APARTMENT | Cooling | 3794.34488 | 4553.21386 | 0.27168 | 0.32602 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 23.42200 | 7.00114E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 14 | G S1 APARTMENT | Heating | 2311.46847 | 2773.76216 | 0.10117 | 0.12141 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:50:00 | -41.90000 | 6.45023E-005 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 15 | G S2 APARTMENT | Cooling | 3815.24627 | 4578.29553 | 0.27323 | 0.32787 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 23.42200 | 7.00114E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 16 | G S2 APARTMENT | Heating | 2319.52358 | 2783.42830 | 0.10153 | 0.12183 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:50:00 | -41.90000 | 6.45023E-005 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 17 | M SW APARTMENT | Cooling | 11287.23381 | 13544.68057 | 0.81481 | 0.97777 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 23.42200 | 7.00114E-003 | 88.24927 | 2.50000 | 5.19091E-002 | 0.00000 |
| 18 | M SW APARTMENT | Heating | 4625.12379 | 5550.14854 | 0.20244 | 0.24293 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | -41.90000 | 6.45023E-005 | 88.24927 | 2.50000 | 5.19091E-002 | 0.00000 |
| 19 | M NW APARTMENT | Cooling | 9697.39993 | 11636.87992 | 0.69847 | 0.83817 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 23.42200 | 7.00114E-003 | 88.24927 | 2.50000 | 5.19091E-002 | 0.00000 |
| 20 | M NW APARTMENT | Heating | 4344.47376 | 5213.36851 | 0.19016 | 0.22819 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | -41.90000 | 6.45023E-005 | 88.24927 | 2.50000 | 5.19091E-002 | 0.00000 |
| 21 | M SE APARTMENT | Cooling | 9704.79541 | 11645.75449 | 0.69889 | 0.83867 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 23.42200 | 7.00114E-003 | 88.24927 | 2.50000 | 5.19091E-002 | 0.00000 |
| 22 | M SE APARTMENT | Heating | 4637.88790 | 5565.46548 | 0.20300 | 0.24360 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | -41.90000 | 6.45023E-005 | 88.24927 | 2.50000 | 5.19091E-002 | 0.00000 |
| 23 | M NE APARTMENT | Cooling | 8170.94621 | 9805.13545 | 0.58616 | 0.70339 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 23.42200 | 7.00114E-003 | 88.24927 | 2.50000 | 5.19091E-002 | 0.00000 |
| 24 | M NE APARTMENT | Heating | 4357.22250 | 5228.66700 | 0.19072 | 0.22886 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | -41.90000 | 6.45023E-005 | 88.24927 | 2.50000 | 5.19091E-002 | 0.00000 |
| 25 | M N1 APARTMENT | Cooling | 7312.51815 | 8775.02178 | 0.52320 | 0.62784 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 23.42200 | 7.00114E-003 | 88.24927 | 2.50000 | 5.19091E-002 | 0.00000 |
| 26 | M N1 APARTMENT | Heating | 2420.38530 | 2904.46236 | 0.10594 | 0.12713 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | -41.90000 | 6.45023E-005 | 88.24927 | 2.50000 | 5.19091E-002 | 0.00000 |
| 27 | M N2 APARTMENT | Cooling | 7293.67415 | 8752.40899 | 0.52182 | 0.62618 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 23.42200 | 7.00114E-003 | 88.24927 | 2.50000 | 5.19091E-002 | 0.00000 |
| 28 | M N2 APARTMENT | Heating | 2420.68730 | 2904.82475 | 0.10596 | 0.12715 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | -41.90000 | 6.45023E-005 | 88.24927 | 2.50000 | 5.19091E-002 | 0.00000 |
| 29 | M S1 APARTMENT | Cooling | 8986.74649 | 10784.09578 | 0.64620 | 0.77544 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 23.42200 | 7.00114E-003 | 88.24927 | 2.50000 | 5.19091E-002 | 0.00000 |
| 30 | M S1 APARTMENT | Heating | 2694.60697 | 3233.52837 | 0.11794 | 0.14153 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | -41.90000 | 6.45023E-005 | 88.24927 | 2.50000 | 5.19091E-002 | 0.00000 |
| 31 | M S2 APARTMENT | Cooling | 8964.58520 | 10757.50224 | 0.64457 | 0.77349 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 23.42200 | 7.00114E-003 | 88.24927 | 2.50000 | 5.19091E-002 | 0.00000 |
| 32 | M S2 APARTMENT | Heating | 2694.90665 | 3233.88798 | 0.11796 | 0.14155 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | -41.90000 | 6.45023E-005 | 88.24927 | 2.50000 | 5.19091E-002 | 0.00000 |
| 33 | T SW APARTMENT | Cooling | 6114.20503 | 7337.04603 | 0.44192 | 0.53031 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 23.42200 | 7.00114E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 34 | T SW APARTMENT | Heating | 3991.25184 | 4789.50221 | 0.17470 | 0.20964 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | -41.90000 | 6.45023E-005 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 35 | T NW APARTMENT | Cooling | 5368.31973 | 6441.98368 | 0.38706 | 0.46448 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 23.42200 | 7.00114E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 36 | T NW APARTMENT | Heating | 3845.60304 | 4614.72365 | 0.16832 | 0.20199 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | -41.90000 | 6.45023E-005 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 37 | T SE APARTMENT | Cooling | 4963.37362 | 5956.04835 | 0.35730 | 0.42876 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 23.42200 | 7.00114E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 38 | T SE APARTMENT | Heating | 4001.03008 | 4801.23610 | 0.17512 | 0.21015 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | -41.90000 | 6.45023E-005 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 39 | T NE APARTMENT | Cooling | 4230.29459 | 5076.35351 | 0.30363 | 0.36436 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 23.42200 | 7.00114E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 40 | T NE APARTMENT | Heating | 3855.38498 | 4626.46198 | 0.16875 | 0.20250 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | -41.90000 | 6.45023E-005 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 41 | T N1 APARTMENT | Cooling | 3983.39591 | 4780.07510 | 0.28549 | 0.34258 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 23.42200 | 7.00114E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 42 | T N1 APARTMENT | Heating | 2682.59311 | 3219.11173 | 0.11742 | 0.14090 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | -41.90000 | 6.45023E-005 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 43 | T N2 APARTMENT | Cooling | 3954.10145 | 4744.92174 | 0.28333 | 0.33999 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 23.42200 | 7.00114E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 44 | T N2 APARTMENT | Heating | 2682.83693 | 3219.40432 | 0.11743 | 0.14092 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | -41.90000 | 6.45023E-005 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 45 | T S1 APARTMENT | Cooling | 4759.25090 | 5711.10107 | 0.34238 | 0.41086 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 23.42200 | 7.00114E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 46 | T S1 APARTMENT | Heating | 2827.90418 | 3393.48501 | 0.12378 | 0.14853 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | -41.90000 | 6.45023E-005 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 47 | T S2 APARTMENT | Cooling | 4729.55304 | 5675.46365 | 0.34021 | 0.40825 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 23.42200 | 7.00114E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 48 | T S2 APARTMENT | Heating | 2828.14623 | 3393.77548 | 0.12379 | 0.14855 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | -41.90000 | 6.45023E-005 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
| 1 | SPLIT GSW | Cooling | Sensible | 5202.32 | 0.38974 | 0.38974 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 2 | SPLIT GSW | Heating | Sensible | 5883.32 | 0.17481 | 0.17481 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:50:00 |
| 3 | SPLIT GNW | Cooling | Sensible | 4250.40 | 0.31905 | 0.31905 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 4 | SPLIT GNW | Heating | Sensible | 5742.29 | 0.16854 | 0.16854 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:50:00 |
| 5 | SPLIT OFFICE | Cooling | Sensible | 5347.58 | 0.40976 | 0.40976 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 6 | SPLIT OFFICE | Heating | Sensible | 7396.29 | 0.20150 | 0.20150 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 18:50:00 |
| 7 | SPLIT GNE | Cooling | Sensible | 3735.01 | 0.28078 | 0.28078 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 8 | SPLIT GNE | Heating | Sensible | 5748.48 | 0.16882 | 0.16882 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:50:00 |
| 9 | SPLIT GN1 | Cooling | Sensible | 3332.52 | 0.25099 | 0.25099 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 10 | SPLIT GN1 | Heating | Sensible | 4538.85 | 0.11509 | 0.11509 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:50:00 |
| 11 | SPLIT GN2 | Cooling | Sensible | 3325.47 | 0.25046 | 0.25046 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 12 | SPLIT GN2 | Heating | Sensible | 4539.02 | 0.11510 | 0.11510 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:50:00 |
| 13 | SPLIT GS1 | Cooling | Sensible | 4345.22 | 0.32602 | 0.32602 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 14 | SPLIT GS1 | Heating | Sensible | 4681.13 | 0.12141 | 0.12141 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:50:00 |
| 15 | SPLIT GS2 | Cooling | Sensible | 4370.01 | 0.32787 | 0.32787 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 16 | SPLIT GS2 | Heating | Sensible | 4690.66 | 0.12183 | 0.12183 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:50:00 |
| 17 | SPLIT MSW | Cooling | Sensible | 13077.48 | 0.97777 | 0.97777 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 18 | SPLIT MSW | Heating | Sensible | 9364.84 | 0.24293 | 0.24293 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 |
| 19 | SPLIT MNW | Cooling | Sensible | 11195.40 | 0.83817 | 0.83817 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 20 | SPLIT MNW | Heating | Sensible | 9032.99 | 0.22819 | 0.22819 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 |
| 21 | SPLIT MSE | Cooling | Sensible | 11203.47 | 0.83867 | 0.83867 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 22 | SPLIT MSE | Heating | Sensible | 9379.93 | 0.24360 | 0.24360 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 |
| 23 | SPLIT MNE | Cooling | Sensible | 9382.33 | 0.70339 | 0.70339 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 24 | SPLIT MNE | Heating | Sensible | 9048.06 | 0.22886 | 0.22886 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 |
| 25 | SPLIT MN1 | Cooling | Sensible | 8363.81 | 0.62784 | 0.62784 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 26 | SPLIT MN1 | Heating | Sensible | 6757.72 | 0.12713 | 0.12713 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 |
| 27 | SPLIT MN2 | Cooling | Sensible | 8341.49 | 0.62618 | 0.62618 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 28 | SPLIT MN2 | Heating | Sensible | 6758.07 | 0.12715 | 0.12715 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 |
| 29 | SPLIT MS1 | Cooling | Sensible | 10351.93 | 0.77544 | 0.77544 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 30 | SPLIT MS1 | Heating | Sensible | 7081.97 | 0.14153 | 0.14153 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 |
| 31 | SPLIT MS2 | Cooling | Sensible | 10325.62 | 0.77349 | 0.77349 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 32 | SPLIT MS2 | Heating | Sensible | 7082.32 | 0.14155 | 0.14155 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 |
| 33 | SPLIT TSW | Cooling | Sensible | 7096.46 | 0.53031 | 0.53031 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 34 | SPLIT TSW | Heating | Sensible | 6667.50 | 0.20964 | 0.20964 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 |
| 35 | SPLIT TNW | Cooling | Sensible | 6211.48 | 0.46448 | 0.46448 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 36 | SPLIT TNW | Heating | Sensible | 6495.28 | 0.20199 | 0.20199 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 |
| 37 | SPLIT TSE | Cooling | Sensible | 5731.18 | 0.42876 | 0.42876 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 38 | SPLIT TSE | Heating | Sensible | 6679.07 | 0.21015 | 0.21015 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 |
| 39 | SPLIT TNE | Cooling | Sensible | 4863.38 | 0.36436 | 0.36436 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 40 | SPLIT TNE | Heating | Sensible | 6506.85 | 0.20250 | 0.20250 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 |
| 41 | SPLIT TN1 | Cooling | Sensible | 4570.26 | 0.34258 | 0.34258 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 42 | SPLIT TN1 | Heating | Sensible | 5120.00 | 0.14090 | 0.14090 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 |
| 43 | SPLIT TN2 | Cooling | Sensible | 4535.46 | 0.33999 | 0.33999 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 44 | SPLIT TN2 | Heating | Sensible | 5120.29 | 0.14092 | 0.14092 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 |
| 45 | SPLIT TS1 | Cooling | Sensible | 5489.84 | 0.41086 | 0.41086 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 46 | SPLIT TS1 | Heating | Sensible | 5291.82 | 0.14853 | 0.14853 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 |
| 47 | SPLIT TS2 | Cooling | Sensible | 5454.68 | 0.40825 | 0.40825 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 48 | SPLIT TS2 | Heating | Sensible | 5292.11 | 0.14855 | 0.14855 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 |
| Component Type | Component Name | Input Field Description | Value | |
| 1 | ZoneHVAC:EnergyRecoveryVentilator | G SW APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 2 | ZoneHVAC:EnergyRecoveryVentilator | G SW APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 2.59546E-002 |
| 3 | Fan:OnOff | G SW APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 4 | Fan:OnOff | G SW APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 5 | HeatExchanger:AirToAir:SensibleAndLatent | G SW APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 6 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | G SW APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.38974 |
| 7 | ZoneHVAC:EnergyRecoveryVentilator | G NW APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 8 | ZoneHVAC:EnergyRecoveryVentilator | G NW APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 2.59546E-002 |
| 9 | Fan:OnOff | G NW APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 10 | Fan:OnOff | G NW APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 11 | HeatExchanger:AirToAir:SensibleAndLatent | G NW APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 12 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | G NW APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.31905 |
| 13 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | OFFICE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.40976 |
| 14 | ZoneHVAC:EnergyRecoveryVentilator | G NE APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 15 | ZoneHVAC:EnergyRecoveryVentilator | G NE APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 2.59546E-002 |
| 16 | Fan:OnOff | G NE APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 17 | Fan:OnOff | G NE APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 18 | HeatExchanger:AirToAir:SensibleAndLatent | G NE APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 19 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | G NE APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.28078 |
| 20 | ZoneHVAC:EnergyRecoveryVentilator | G N1 APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 21 | ZoneHVAC:EnergyRecoveryVentilator | G N1 APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 2.59546E-002 |
| 22 | Fan:OnOff | G N1 APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 23 | Fan:OnOff | G N1 APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 24 | HeatExchanger:AirToAir:SensibleAndLatent | G N1 APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 25 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | G N1 APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.25099 |
| 26 | ZoneHVAC:EnergyRecoveryVentilator | G N2 APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 27 | ZoneHVAC:EnergyRecoveryVentilator | G N2 APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 2.59546E-002 |
| 28 | Fan:OnOff | G N2 APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 29 | Fan:OnOff | G N2 APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 30 | HeatExchanger:AirToAir:SensibleAndLatent | G N2 APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 31 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | G N2 APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.25046 |
| 32 | ZoneHVAC:EnergyRecoveryVentilator | G S1 APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 33 | ZoneHVAC:EnergyRecoveryVentilator | G S1 APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 2.59546E-002 |
| 34 | Fan:OnOff | G S1 APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 35 | Fan:OnOff | G S1 APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 36 | HeatExchanger:AirToAir:SensibleAndLatent | G S1 APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 37 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | G S1 APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.32602 |
| 38 | ZoneHVAC:EnergyRecoveryVentilator | G S2 APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 39 | ZoneHVAC:EnergyRecoveryVentilator | G S2 APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 2.59546E-002 |
| 40 | Fan:OnOff | G S2 APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 41 | Fan:OnOff | G S2 APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 42 | HeatExchanger:AirToAir:SensibleAndLatent | G S2 APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 43 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | G S2 APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.32787 |
| 44 | ZoneHVAC:EnergyRecoveryVentilator | M SW APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 5.19091E-002 |
| 45 | ZoneHVAC:EnergyRecoveryVentilator | M SW APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 5.19091E-002 |
| 46 | Fan:OnOff | M SW APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 5.19091E-002 |
| 47 | Fan:OnOff | M SW APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 5.19091E-002 |
| 48 | HeatExchanger:AirToAir:SensibleAndLatent | M SW APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 5.19091E-002 |
| 49 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | M SW APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.97777 |
| 50 | ZoneHVAC:EnergyRecoveryVentilator | M NW APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 5.19091E-002 |
| 51 | ZoneHVAC:EnergyRecoveryVentilator | M NW APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 5.19091E-002 |
| 52 | Fan:OnOff | M NW APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 5.19091E-002 |
| 53 | Fan:OnOff | M NW APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 5.19091E-002 |
| 54 | HeatExchanger:AirToAir:SensibleAndLatent | M NW APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 5.19091E-002 |
| 55 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | M NW APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.83817 |
| 56 | ZoneHVAC:EnergyRecoveryVentilator | M SE APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 5.19091E-002 |
| 57 | ZoneHVAC:EnergyRecoveryVentilator | M SE APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 5.19091E-002 |
| 58 | Fan:OnOff | M SE APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 5.19091E-002 |
| 59 | Fan:OnOff | M SE APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 5.19091E-002 |
| 60 | HeatExchanger:AirToAir:SensibleAndLatent | M SE APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 5.19091E-002 |
| 61 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | M SE APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.83867 |
| 62 | ZoneHVAC:EnergyRecoveryVentilator | M NE APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 5.19091E-002 |
| 63 | ZoneHVAC:EnergyRecoveryVentilator | M NE APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 5.19091E-002 |
| 64 | Fan:OnOff | M NE APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 5.19091E-002 |
| 65 | Fan:OnOff | M NE APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 5.19091E-002 |
| 66 | HeatExchanger:AirToAir:SensibleAndLatent | M NE APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 5.19091E-002 |
| 67 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | M NE APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.70339 |
| 68 | ZoneHVAC:EnergyRecoveryVentilator | M N1 APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 5.19091E-002 |
| 69 | ZoneHVAC:EnergyRecoveryVentilator | M N1 APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 5.19091E-002 |
| 70 | Fan:OnOff | M N1 APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 5.19091E-002 |
| 71 | Fan:OnOff | M N1 APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 5.19091E-002 |
| 72 | HeatExchanger:AirToAir:SensibleAndLatent | M N1 APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 5.19091E-002 |
| 73 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | M N1 APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.62784 |
| 74 | ZoneHVAC:EnergyRecoveryVentilator | M N2 APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 5.19091E-002 |
| 75 | ZoneHVAC:EnergyRecoveryVentilator | M N2 APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 5.19091E-002 |
| 76 | Fan:OnOff | M N2 APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 5.19091E-002 |
| 77 | Fan:OnOff | M N2 APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 5.19091E-002 |
| 78 | HeatExchanger:AirToAir:SensibleAndLatent | M N2 APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 5.19091E-002 |
| 79 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | M N2 APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.62618 |
| 80 | ZoneHVAC:EnergyRecoveryVentilator | M S1 APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 5.19091E-002 |
| 81 | ZoneHVAC:EnergyRecoveryVentilator | M S1 APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 5.19091E-002 |
| 82 | Fan:OnOff | M S1 APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 5.19091E-002 |
| 83 | Fan:OnOff | M S1 APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 5.19091E-002 |
| 84 | HeatExchanger:AirToAir:SensibleAndLatent | M S1 APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 5.19091E-002 |
| 85 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | M S1 APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.77544 |
| 86 | ZoneHVAC:EnergyRecoveryVentilator | M S2 APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 5.19091E-002 |
| 87 | ZoneHVAC:EnergyRecoveryVentilator | M S2 APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 5.19091E-002 |
| 88 | Fan:OnOff | M S2 APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 5.19091E-002 |
| 89 | Fan:OnOff | M S2 APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 5.19091E-002 |
| 90 | HeatExchanger:AirToAir:SensibleAndLatent | M S2 APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 5.19091E-002 |
| 91 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | M S2 APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.77349 |
| 92 | ZoneHVAC:EnergyRecoveryVentilator | T SW APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 93 | ZoneHVAC:EnergyRecoveryVentilator | T SW APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 2.59546E-002 |
| 94 | Fan:OnOff | T SW APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 95 | Fan:OnOff | T SW APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 96 | HeatExchanger:AirToAir:SensibleAndLatent | T SW APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 97 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | T SW APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.53031 |
| 98 | ZoneHVAC:EnergyRecoveryVentilator | T NW APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 99 | ZoneHVAC:EnergyRecoveryVentilator | T NW APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 2.59546E-002 |
| 100 | Fan:OnOff | T NW APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 101 | Fan:OnOff | T NW APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 102 | HeatExchanger:AirToAir:SensibleAndLatent | T NW APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 103 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | T NW APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.46448 |
| 104 | ZoneHVAC:EnergyRecoveryVentilator | T SE APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 105 | ZoneHVAC:EnergyRecoveryVentilator | T SE APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 2.59546E-002 |
| 106 | Fan:OnOff | T SE APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 107 | Fan:OnOff | T SE APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 108 | HeatExchanger:AirToAir:SensibleAndLatent | T SE APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 109 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | T SE APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.42876 |
| 110 | ZoneHVAC:EnergyRecoveryVentilator | T NE APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 111 | ZoneHVAC:EnergyRecoveryVentilator | T NE APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 2.59546E-002 |
| 112 | Fan:OnOff | T NE APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 113 | Fan:OnOff | T NE APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 114 | HeatExchanger:AirToAir:SensibleAndLatent | T NE APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 115 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | T NE APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.36436 |
| 116 | ZoneHVAC:EnergyRecoveryVentilator | T N1 APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 117 | ZoneHVAC:EnergyRecoveryVentilator | T N1 APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 2.59546E-002 |
| 118 | Fan:OnOff | T N1 APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 119 | Fan:OnOff | T N1 APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 120 | HeatExchanger:AirToAir:SensibleAndLatent | T N1 APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 121 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | T N1 APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.34258 |
| 122 | ZoneHVAC:EnergyRecoveryVentilator | T N2 APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 123 | ZoneHVAC:EnergyRecoveryVentilator | T N2 APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 2.59546E-002 |
| 124 | Fan:OnOff | T N2 APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 125 | Fan:OnOff | T N2 APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 126 | HeatExchanger:AirToAir:SensibleAndLatent | T N2 APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 127 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | T N2 APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.33999 |
| 128 | ZoneHVAC:EnergyRecoveryVentilator | T S1 APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 129 | ZoneHVAC:EnergyRecoveryVentilator | T S1 APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 2.59546E-002 |
| 130 | Fan:OnOff | T S1 APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 131 | Fan:OnOff | T S1 APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 132 | HeatExchanger:AirToAir:SensibleAndLatent | T S1 APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 133 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | T S1 APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.41086 |
| 134 | ZoneHVAC:EnergyRecoveryVentilator | T S2 APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 135 | ZoneHVAC:EnergyRecoveryVentilator | T S2 APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 2.59546E-002 |
| 136 | Fan:OnOff | T S2 APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 137 | Fan:OnOff | T S2 APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 138 | HeatExchanger:AirToAir:SensibleAndLatent | T S2 APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 139 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | T S2 APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.40825 |
| 140 | AirLoopHVAC | SPLIT GSW | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.38974 |
| 141 | AirLoopHVAC | SPLIT GSW | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.38974 |
| 142 | AirLoopHVAC | SPLIT GSW | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.38974 |
| 143 | AirLoopHVAC | SPLIT GSW | Adjusted Heating Design Air Flow Rate [m3/s] | 0.38974 |
| 144 | AirLoopHVAC | SPLIT GSW | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.38974 |
| 145 | AirLoopHVAC | SPLIT GSW | Adjusted Main Design Air Flow Rate [m3/s] | 0.38974 |
| 146 | AirLoopHVAC | SPLIT GSW | User Heating Air Flow Ratio [] | 1.00000 |
| 147 | AirLoopHVAC | SPLIT GSW | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 148 | AirLoopHVAC | SPLIT GNW | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.31905 |
| 149 | AirLoopHVAC | SPLIT GNW | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.31905 |
| 150 | AirLoopHVAC | SPLIT GNW | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.31905 |
| 151 | AirLoopHVAC | SPLIT GNW | Adjusted Heating Design Air Flow Rate [m3/s] | 0.31905 |
| 152 | AirLoopHVAC | SPLIT GNW | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.31905 |
| 153 | AirLoopHVAC | SPLIT GNW | Adjusted Main Design Air Flow Rate [m3/s] | 0.31905 |
| 154 | AirLoopHVAC | SPLIT GNW | User Heating Air Flow Ratio [] | 1.00000 |
| 155 | AirLoopHVAC | SPLIT GNW | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 156 | AirLoopHVAC | SPLIT OFFICE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.40976 |
| 157 | AirLoopHVAC | SPLIT OFFICE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.40976 |
| 158 | AirLoopHVAC | SPLIT OFFICE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.40976 |
| 159 | AirLoopHVAC | SPLIT OFFICE | Adjusted Heating Design Air Flow Rate [m3/s] | 0.40976 |
| 160 | AirLoopHVAC | SPLIT OFFICE | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.40976 |
| 161 | AirLoopHVAC | SPLIT OFFICE | Adjusted Main Design Air Flow Rate [m3/s] | 0.40976 |
| 162 | AirLoopHVAC | SPLIT OFFICE | User Heating Air Flow Ratio [] | 1.00000 |
| 163 | AirLoopHVAC | SPLIT OFFICE | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 164 | AirLoopHVAC | SPLIT GNE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.28078 |
| 165 | AirLoopHVAC | SPLIT GNE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.28078 |
| 166 | AirLoopHVAC | SPLIT GNE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.28078 |
| 167 | AirLoopHVAC | SPLIT GNE | Adjusted Heating Design Air Flow Rate [m3/s] | 0.28078 |
| 168 | AirLoopHVAC | SPLIT GNE | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.28078 |
| 169 | AirLoopHVAC | SPLIT GNE | Adjusted Main Design Air Flow Rate [m3/s] | 0.28078 |
| 170 | AirLoopHVAC | SPLIT GNE | User Heating Air Flow Ratio [] | 1.00000 |
| 171 | AirLoopHVAC | SPLIT GNE | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 172 | AirLoopHVAC | SPLIT GN1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.25099 |
| 173 | AirLoopHVAC | SPLIT GN1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.25099 |
| 174 | AirLoopHVAC | SPLIT GN1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.25099 |
| 175 | AirLoopHVAC | SPLIT GN1 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.25099 |
| 176 | AirLoopHVAC | SPLIT GN1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.25099 |
| 177 | AirLoopHVAC | SPLIT GN1 | Adjusted Main Design Air Flow Rate [m3/s] | 0.25099 |
| 178 | AirLoopHVAC | SPLIT GN1 | User Heating Air Flow Ratio [] | 1.00000 |
| 179 | AirLoopHVAC | SPLIT GN1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 180 | AirLoopHVAC | SPLIT GN2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.25046 |
| 181 | AirLoopHVAC | SPLIT GN2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.25046 |
| 182 | AirLoopHVAC | SPLIT GN2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.25046 |
| 183 | AirLoopHVAC | SPLIT GN2 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.25046 |
| 184 | AirLoopHVAC | SPLIT GN2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.25046 |
| 185 | AirLoopHVAC | SPLIT GN2 | Adjusted Main Design Air Flow Rate [m3/s] | 0.25046 |
| 186 | AirLoopHVAC | SPLIT GN2 | User Heating Air Flow Ratio [] | 1.00000 |
| 187 | AirLoopHVAC | SPLIT GN2 | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 188 | AirLoopHVAC | SPLIT GS1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.32602 |
| 189 | AirLoopHVAC | SPLIT GS1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.32602 |
| 190 | AirLoopHVAC | SPLIT GS1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.32602 |
| 191 | AirLoopHVAC | SPLIT GS1 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.32602 |
| 192 | AirLoopHVAC | SPLIT GS1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.32602 |
| 193 | AirLoopHVAC | SPLIT GS1 | Adjusted Main Design Air Flow Rate [m3/s] | 0.32602 |
| 194 | AirLoopHVAC | SPLIT GS1 | User Heating Air Flow Ratio [] | 1.00000 |
| 195 | AirLoopHVAC | SPLIT GS1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 196 | AirLoopHVAC | SPLIT GS2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.32787 |
| 197 | AirLoopHVAC | SPLIT GS2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.32787 |
| 198 | AirLoopHVAC | SPLIT GS2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.32787 |
| 199 | AirLoopHVAC | SPLIT GS2 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.32787 |
| 200 | AirLoopHVAC | SPLIT GS2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.32787 |
| 201 | AirLoopHVAC | SPLIT GS2 | Adjusted Main Design Air Flow Rate [m3/s] | 0.32787 |
| 202 | AirLoopHVAC | SPLIT GS2 | User Heating Air Flow Ratio [] | 1.00000 |
| 203 | AirLoopHVAC | SPLIT GS2 | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 204 | AirLoopHVAC | SPLIT MSW | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.97777 |
| 205 | AirLoopHVAC | SPLIT MSW | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.97777 |
| 206 | AirLoopHVAC | SPLIT MSW | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.97777 |
| 207 | AirLoopHVAC | SPLIT MSW | Adjusted Heating Design Air Flow Rate [m3/s] | 0.97777 |
| 208 | AirLoopHVAC | SPLIT MSW | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.97777 |
| 209 | AirLoopHVAC | SPLIT MSW | Adjusted Main Design Air Flow Rate [m3/s] | 0.97777 |
| 210 | AirLoopHVAC | SPLIT MSW | User Heating Air Flow Ratio [] | 1.00000 |
| 211 | AirLoopHVAC | SPLIT MSW | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 212 | AirLoopHVAC | SPLIT MNW | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.83817 |
| 213 | AirLoopHVAC | SPLIT MNW | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.83817 |
| 214 | AirLoopHVAC | SPLIT MNW | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.83817 |
| 215 | AirLoopHVAC | SPLIT MNW | Adjusted Heating Design Air Flow Rate [m3/s] | 0.83817 |
| 216 | AirLoopHVAC | SPLIT MNW | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.83817 |
| 217 | AirLoopHVAC | SPLIT MNW | Adjusted Main Design Air Flow Rate [m3/s] | 0.83817 |
| 218 | AirLoopHVAC | SPLIT MNW | User Heating Air Flow Ratio [] | 1.00000 |
| 219 | AirLoopHVAC | SPLIT MNW | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 220 | AirLoopHVAC | SPLIT MSE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.83867 |
| 221 | AirLoopHVAC | SPLIT MSE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.83867 |
| 222 | AirLoopHVAC | SPLIT MSE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.83867 |
| 223 | AirLoopHVAC | SPLIT MSE | Adjusted Heating Design Air Flow Rate [m3/s] | 0.83867 |
| 224 | AirLoopHVAC | SPLIT MSE | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.83867 |
| 225 | AirLoopHVAC | SPLIT MSE | Adjusted Main Design Air Flow Rate [m3/s] | 0.83867 |
| 226 | AirLoopHVAC | SPLIT MSE | User Heating Air Flow Ratio [] | 1.00000 |
| 227 | AirLoopHVAC | SPLIT MSE | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 228 | AirLoopHVAC | SPLIT MNE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.70339 |
| 229 | AirLoopHVAC | SPLIT MNE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.70339 |
| 230 | AirLoopHVAC | SPLIT MNE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.70339 |
| 231 | AirLoopHVAC | SPLIT MNE | Adjusted Heating Design Air Flow Rate [m3/s] | 0.70339 |
| 232 | AirLoopHVAC | SPLIT MNE | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.70339 |
| 233 | AirLoopHVAC | SPLIT MNE | Adjusted Main Design Air Flow Rate [m3/s] | 0.70339 |
| 234 | AirLoopHVAC | SPLIT MNE | User Heating Air Flow Ratio [] | 1.00000 |
| 235 | AirLoopHVAC | SPLIT MNE | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 236 | AirLoopHVAC | SPLIT MN1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.62784 |
| 237 | AirLoopHVAC | SPLIT MN1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.62784 |
| 238 | AirLoopHVAC | SPLIT MN1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.62784 |
| 239 | AirLoopHVAC | SPLIT MN1 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.62784 |
| 240 | AirLoopHVAC | SPLIT MN1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.62784 |
| 241 | AirLoopHVAC | SPLIT MN1 | Adjusted Main Design Air Flow Rate [m3/s] | 0.62784 |
| 242 | AirLoopHVAC | SPLIT MN1 | User Heating Air Flow Ratio [] | 1.00000 |
| 243 | AirLoopHVAC | SPLIT MN1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 244 | AirLoopHVAC | SPLIT MN2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.62618 |
| 245 | AirLoopHVAC | SPLIT MN2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.62618 |
| 246 | AirLoopHVAC | SPLIT MN2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.62618 |
| 247 | AirLoopHVAC | SPLIT MN2 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.62618 |
| 248 | AirLoopHVAC | SPLIT MN2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.62618 |
| 249 | AirLoopHVAC | SPLIT MN2 | Adjusted Main Design Air Flow Rate [m3/s] | 0.62618 |
| 250 | AirLoopHVAC | SPLIT MN2 | User Heating Air Flow Ratio [] | 1.00000 |
| 251 | AirLoopHVAC | SPLIT MN2 | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 252 | AirLoopHVAC | SPLIT MS1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.77544 |
| 253 | AirLoopHVAC | SPLIT MS1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.77544 |
| 254 | AirLoopHVAC | SPLIT MS1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.77544 |
| 255 | AirLoopHVAC | SPLIT MS1 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.77544 |
| 256 | AirLoopHVAC | SPLIT MS1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.77544 |
| 257 | AirLoopHVAC | SPLIT MS1 | Adjusted Main Design Air Flow Rate [m3/s] | 0.77544 |
| 258 | AirLoopHVAC | SPLIT MS1 | User Heating Air Flow Ratio [] | 1.00000 |
| 259 | AirLoopHVAC | SPLIT MS1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 260 | AirLoopHVAC | SPLIT MS2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.77349 |
| 261 | AirLoopHVAC | SPLIT MS2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.77349 |
| 262 | AirLoopHVAC | SPLIT MS2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.77349 |
| 263 | AirLoopHVAC | SPLIT MS2 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.77349 |
| 264 | AirLoopHVAC | SPLIT MS2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.77349 |
| 265 | AirLoopHVAC | SPLIT MS2 | Adjusted Main Design Air Flow Rate [m3/s] | 0.77349 |
| 266 | AirLoopHVAC | SPLIT MS2 | User Heating Air Flow Ratio [] | 1.00000 |
| 267 | AirLoopHVAC | SPLIT MS2 | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 268 | AirLoopHVAC | SPLIT TSW | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.53031 |
| 269 | AirLoopHVAC | SPLIT TSW | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.53031 |
| 270 | AirLoopHVAC | SPLIT TSW | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.53031 |
| 271 | AirLoopHVAC | SPLIT TSW | Adjusted Heating Design Air Flow Rate [m3/s] | 0.53031 |
| 272 | AirLoopHVAC | SPLIT TSW | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.53031 |
| 273 | AirLoopHVAC | SPLIT TSW | Adjusted Main Design Air Flow Rate [m3/s] | 0.53031 |
| 274 | AirLoopHVAC | SPLIT TSW | User Heating Air Flow Ratio [] | 1.00000 |
| 275 | AirLoopHVAC | SPLIT TSW | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 276 | AirLoopHVAC | SPLIT TNW | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.46448 |
| 277 | AirLoopHVAC | SPLIT TNW | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.46448 |
| 278 | AirLoopHVAC | SPLIT TNW | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.46448 |
| 279 | AirLoopHVAC | SPLIT TNW | Adjusted Heating Design Air Flow Rate [m3/s] | 0.46448 |
| 280 | AirLoopHVAC | SPLIT TNW | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.46448 |
| 281 | AirLoopHVAC | SPLIT TNW | Adjusted Main Design Air Flow Rate [m3/s] | 0.46448 |
| 282 | AirLoopHVAC | SPLIT TNW | User Heating Air Flow Ratio [] | 1.00000 |
| 283 | AirLoopHVAC | SPLIT TNW | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 284 | AirLoopHVAC | SPLIT TSE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.42876 |
| 285 | AirLoopHVAC | SPLIT TSE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.42876 |
| 286 | AirLoopHVAC | SPLIT TSE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.42876 |
| 287 | AirLoopHVAC | SPLIT TSE | Adjusted Heating Design Air Flow Rate [m3/s] | 0.42876 |
| 288 | AirLoopHVAC | SPLIT TSE | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.42876 |
| 289 | AirLoopHVAC | SPLIT TSE | Adjusted Main Design Air Flow Rate [m3/s] | 0.42876 |
| 290 | AirLoopHVAC | SPLIT TSE | User Heating Air Flow Ratio [] | 1.00000 |
| 291 | AirLoopHVAC | SPLIT TSE | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 292 | AirLoopHVAC | SPLIT TNE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.36436 |
| 293 | AirLoopHVAC | SPLIT TNE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.36436 |
| 294 | AirLoopHVAC | SPLIT TNE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.36436 |
| 295 | AirLoopHVAC | SPLIT TNE | Adjusted Heating Design Air Flow Rate [m3/s] | 0.36436 |
| 296 | AirLoopHVAC | SPLIT TNE | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.36436 |
| 297 | AirLoopHVAC | SPLIT TNE | Adjusted Main Design Air Flow Rate [m3/s] | 0.36436 |
| 298 | AirLoopHVAC | SPLIT TNE | User Heating Air Flow Ratio [] | 1.00000 |
| 299 | AirLoopHVAC | SPLIT TNE | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 300 | AirLoopHVAC | SPLIT TN1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.34258 |
| 301 | AirLoopHVAC | SPLIT TN1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.34258 |
| 302 | AirLoopHVAC | SPLIT TN1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.34258 |
| 303 | AirLoopHVAC | SPLIT TN1 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.34258 |
| 304 | AirLoopHVAC | SPLIT TN1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.34258 |
| 305 | AirLoopHVAC | SPLIT TN1 | Adjusted Main Design Air Flow Rate [m3/s] | 0.34258 |
| 306 | AirLoopHVAC | SPLIT TN1 | User Heating Air Flow Ratio [] | 1.00000 |
| 307 | AirLoopHVAC | SPLIT TN1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 308 | AirLoopHVAC | SPLIT TN2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.33999 |
| 309 | AirLoopHVAC | SPLIT TN2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.33999 |
| 310 | AirLoopHVAC | SPLIT TN2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.33999 |
| 311 | AirLoopHVAC | SPLIT TN2 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.33999 |
| 312 | AirLoopHVAC | SPLIT TN2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.33999 |
| 313 | AirLoopHVAC | SPLIT TN2 | Adjusted Main Design Air Flow Rate [m3/s] | 0.33999 |
| 314 | AirLoopHVAC | SPLIT TN2 | User Heating Air Flow Ratio [] | 1.00000 |
| 315 | AirLoopHVAC | SPLIT TN2 | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 316 | AirLoopHVAC | SPLIT TS1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.41086 |
| 317 | AirLoopHVAC | SPLIT TS1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.41086 |
| 318 | AirLoopHVAC | SPLIT TS1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.41086 |
| 319 | AirLoopHVAC | SPLIT TS1 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.41086 |
| 320 | AirLoopHVAC | SPLIT TS1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.41086 |
| 321 | AirLoopHVAC | SPLIT TS1 | Adjusted Main Design Air Flow Rate [m3/s] | 0.41086 |
| 322 | AirLoopHVAC | SPLIT TS1 | User Heating Air Flow Ratio [] | 1.00000 |
| 323 | AirLoopHVAC | SPLIT TS1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 324 | AirLoopHVAC | SPLIT TS2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.40825 |
| 325 | AirLoopHVAC | SPLIT TS2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.40825 |
| 326 | AirLoopHVAC | SPLIT TS2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.40825 |
| 327 | AirLoopHVAC | SPLIT TS2 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.40825 |
| 328 | AirLoopHVAC | SPLIT TS2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.40825 |
| 329 | AirLoopHVAC | SPLIT TS2 | Adjusted Main Design Air Flow Rate [m3/s] | 0.40825 |
| 330 | AirLoopHVAC | SPLIT TS2 | User Heating Air Flow Ratio [] | 1.00000 |
| 331 | AirLoopHVAC | SPLIT TS2 | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 332 | AirLoopHVAC | SPLIT GSW | Design Supply Air Flow Rate [m3/s] | 0.38974 |
| 333 | AirLoopHVAC | SPLIT GNW | Design Supply Air Flow Rate [m3/s] | 0.31905 |
| 334 | AirLoopHVAC | SPLIT OFFICE | Design Supply Air Flow Rate [m3/s] | 0.40976 |
| 335 | AirLoopHVAC | SPLIT GNE | Design Supply Air Flow Rate [m3/s] | 0.28078 |
| 336 | AirLoopHVAC | SPLIT GN1 | Design Supply Air Flow Rate [m3/s] | 0.25099 |
| 337 | AirLoopHVAC | SPLIT GN2 | Design Supply Air Flow Rate [m3/s] | 0.25046 |
| 338 | AirLoopHVAC | SPLIT GS1 | Design Supply Air Flow Rate [m3/s] | 0.32602 |
| 339 | AirLoopHVAC | SPLIT GS2 | Design Supply Air Flow Rate [m3/s] | 0.32787 |
| 340 | AirLoopHVAC | SPLIT MSW | Design Supply Air Flow Rate [m3/s] | 0.97777 |
| 341 | AirLoopHVAC | SPLIT MNW | Design Supply Air Flow Rate [m3/s] | 0.83817 |
| 342 | AirLoopHVAC | SPLIT MSE | Design Supply Air Flow Rate [m3/s] | 0.83867 |
| 343 | AirLoopHVAC | SPLIT MNE | Design Supply Air Flow Rate [m3/s] | 0.70339 |
| 344 | AirLoopHVAC | SPLIT MN1 | Design Supply Air Flow Rate [m3/s] | 0.62784 |
| 345 | AirLoopHVAC | SPLIT MN2 | Design Supply Air Flow Rate [m3/s] | 0.62618 |
| 346 | AirLoopHVAC | SPLIT MS1 | Design Supply Air Flow Rate [m3/s] | 0.77544 |
| 347 | AirLoopHVAC | SPLIT MS2 | Design Supply Air Flow Rate [m3/s] | 0.77349 |
| 348 | AirLoopHVAC | SPLIT TSW | Design Supply Air Flow Rate [m3/s] | 0.53031 |
| 349 | AirLoopHVAC | SPLIT TNW | Design Supply Air Flow Rate [m3/s] | 0.46448 |
| 350 | AirLoopHVAC | SPLIT TSE | Design Supply Air Flow Rate [m3/s] | 0.42876 |
| 351 | AirLoopHVAC | SPLIT TNE | Design Supply Air Flow Rate [m3/s] | 0.36436 |
| 352 | AirLoopHVAC | SPLIT TN1 | Design Supply Air Flow Rate [m3/s] | 0.34258 |
| 353 | AirLoopHVAC | SPLIT TN2 | Design Supply Air Flow Rate [m3/s] | 0.33999 |
| 354 | AirLoopHVAC | SPLIT TS1 | Design Supply Air Flow Rate [m3/s] | 0.41086 |
| 355 | AirLoopHVAC | SPLIT TS2 | Design Supply Air Flow Rate [m3/s] | 0.40825 |
| 356 | Controller:OutdoorAir | SPLIT GSW_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.38974 |
| 357 | Controller:OutdoorAir | SPLIT GSW_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.59546E-002 |
| 358 | AirLoopHVAC:UnitarySystem | SPLIT GSW_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.38974 |
| 359 | AirLoopHVAC:UnitarySystem | SPLIT GSW_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.38974 |
| 360 | AirLoopHVAC:UnitarySystem | SPLIT GSW_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.38974 |
| 361 | AirLoopHVAC:UnitarySystem | SPLIT GSW_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.38974 |
| 362 | AirLoopHVAC:UnitarySystem | SPLIT GSW_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 6451.50978 |
| 363 | AirLoopHVAC:UnitarySystem | SPLIT GSW_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 10722.17388 |
| 364 | AirLoopHVAC:UnitarySystem | SPLIT GSW_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 365 | AirLoopHVAC:UnitarySystem | SPLIT GSW_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 366 | Fan:OnOff | SPLIT GSW SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.38974 |
| 367 | Coil:Cooling:DX:SingleSpeed | SPLIT GSW COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.38974 |
| 368 | Coil:Cooling:DX:SingleSpeed | SPLIT GSW COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 6451.50978 |
| 369 | Coil:Cooling:DX:SingleSpeed | SPLIT GSW COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
| 370 | Coil:Heating:Fuel | SPLIT GSW HEATING COIL | Design Size Nominal Capacity [W] | 10722.17388 |
| 371 | Controller:OutdoorAir | SPLIT GNW_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.31905 |
| 372 | Controller:OutdoorAir | SPLIT GNW_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.59546E-002 |
| 373 | AirLoopHVAC:UnitarySystem | SPLIT GNW_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.31905 |
| 374 | AirLoopHVAC:UnitarySystem | SPLIT GNW_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.31905 |
| 375 | AirLoopHVAC:UnitarySystem | SPLIT GNW_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.31905 |
| 376 | AirLoopHVAC:UnitarySystem | SPLIT GNW_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.31905 |
| 377 | AirLoopHVAC:UnitarySystem | SPLIT GNW_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 5281.46389 |
| 378 | AirLoopHVAC:UnitarySystem | SPLIT GNW_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 9130.80909 |
| 379 | AirLoopHVAC:UnitarySystem | SPLIT GNW_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 380 | AirLoopHVAC:UnitarySystem | SPLIT GNW_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 381 | Fan:OnOff | SPLIT GNW SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.31905 |
| 382 | Coil:Cooling:DX:SingleSpeed | SPLIT GNW COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.31905 |
| 383 | Coil:Cooling:DX:SingleSpeed | SPLIT GNW COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 5281.46389 |
| 384 | Coil:Cooling:DX:SingleSpeed | SPLIT GNW COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
| 385 | Coil:Heating:Fuel | SPLIT GNW HEATING COIL | Design Size Nominal Capacity [W] | 9130.80909 |
| 386 | Controller:OutdoorAir | SPLIT OFFICE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.40976 |
| 387 | Controller:OutdoorAir | SPLIT OFFICE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 3.81060E-002 |
| 388 | AirLoopHVAC:UnitarySystem | SPLIT OFFICE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.40976 |
| 389 | AirLoopHVAC:UnitarySystem | SPLIT OFFICE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.40976 |
| 390 | AirLoopHVAC:UnitarySystem | SPLIT OFFICE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.40976 |
| 391 | AirLoopHVAC:UnitarySystem | SPLIT OFFICE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.40976 |
| 392 | AirLoopHVAC:UnitarySystem | SPLIT OFFICE_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 6782.98109 |
| 393 | AirLoopHVAC:UnitarySystem | SPLIT OFFICE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 12084.90592 |
| 394 | AirLoopHVAC:UnitarySystem | SPLIT OFFICE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 395 | AirLoopHVAC:UnitarySystem | SPLIT OFFICE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 396 | Fan:OnOff | SPLIT OFFICE SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.40976 |
| 397 | Coil:Cooling:DX:SingleSpeed | SPLIT OFFICE COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.40976 |
| 398 | Coil:Cooling:DX:SingleSpeed | SPLIT OFFICE COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 6782.98109 |
| 399 | Coil:Cooling:DX:SingleSpeed | SPLIT OFFICE COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
| 400 | Coil:Heating:Fuel | SPLIT OFFICE HEATING COIL | Design Size Nominal Capacity [W] | 12084.90592 |
| 401 | Controller:OutdoorAir | SPLIT GNE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.28078 |
| 402 | Controller:OutdoorAir | SPLIT GNE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.59546E-002 |
| 403 | AirLoopHVAC:UnitarySystem | SPLIT GNE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.28078 |
| 404 | AirLoopHVAC:UnitarySystem | SPLIT GNE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.28078 |
| 405 | AirLoopHVAC:UnitarySystem | SPLIT GNE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.28078 |
| 406 | AirLoopHVAC:UnitarySystem | SPLIT GNE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.28078 |
| 407 | AirLoopHVAC:UnitarySystem | SPLIT GNE_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 4647.89151 |
| 408 | AirLoopHVAC:UnitarySystem | SPLIT GNE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 8269.12148 |
| 409 | AirLoopHVAC:UnitarySystem | SPLIT GNE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 410 | AirLoopHVAC:UnitarySystem | SPLIT GNE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 411 | Fan:OnOff | SPLIT GNE SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.28078 |
| 412 | Coil:Cooling:DX:SingleSpeed | SPLIT GNE COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.28078 |
| 413 | Coil:Cooling:DX:SingleSpeed | SPLIT GNE COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 4647.89151 |
| 414 | Coil:Cooling:DX:SingleSpeed | SPLIT GNE COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
| 415 | Coil:Heating:Fuel | SPLIT GNE HEATING COIL | Design Size Nominal Capacity [W] | 8269.12148 |
| 416 | Controller:OutdoorAir | SPLIT GN1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.25099 |
| 417 | Controller:OutdoorAir | SPLIT GN1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.59546E-002 |
| 418 | AirLoopHVAC:UnitarySystem | SPLIT GN1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.25099 |
| 419 | AirLoopHVAC:UnitarySystem | SPLIT GN1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.25099 |
| 420 | AirLoopHVAC:UnitarySystem | SPLIT GN1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.25099 |
| 421 | AirLoopHVAC:UnitarySystem | SPLIT GN1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.25099 |
| 422 | AirLoopHVAC:UnitarySystem | SPLIT GN1_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 4154.70728 |
| 423 | AirLoopHVAC:UnitarySystem | SPLIT GN1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 7598.35832 |
| 424 | AirLoopHVAC:UnitarySystem | SPLIT GN1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 425 | AirLoopHVAC:UnitarySystem | SPLIT GN1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 426 | Fan:OnOff | SPLIT GN1 SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.25099 |
| 427 | Coil:Cooling:DX:SingleSpeed | SPLIT GN1 COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.25099 |
| 428 | Coil:Cooling:DX:SingleSpeed | SPLIT GN1 COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 4154.70728 |
| 429 | Coil:Cooling:DX:SingleSpeed | SPLIT GN1 COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
| 430 | Coil:Heating:Fuel | SPLIT GN1 HEATING COIL | Design Size Nominal Capacity [W] | 7598.35832 |
| 431 | Controller:OutdoorAir | SPLIT GN2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.25046 |
| 432 | Controller:OutdoorAir | SPLIT GN2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.59546E-002 |
| 433 | AirLoopHVAC:UnitarySystem | SPLIT GN2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.25046 |
| 434 | AirLoopHVAC:UnitarySystem | SPLIT GN2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.25046 |
| 435 | AirLoopHVAC:UnitarySystem | SPLIT GN2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.25046 |
| 436 | AirLoopHVAC:UnitarySystem | SPLIT GN2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.25046 |
| 437 | AirLoopHVAC:UnitarySystem | SPLIT GN2_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 4146.07045 |
| 438 | AirLoopHVAC:UnitarySystem | SPLIT GN2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 7586.61186 |
| 439 | AirLoopHVAC:UnitarySystem | SPLIT GN2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 440 | AirLoopHVAC:UnitarySystem | SPLIT GN2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 441 | Fan:OnOff | SPLIT GN2 SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.25046 |
| 442 | Coil:Cooling:DX:SingleSpeed | SPLIT GN2 COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.25046 |
| 443 | Coil:Cooling:DX:SingleSpeed | SPLIT GN2 COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 4146.07045 |
| 444 | Coil:Cooling:DX:SingleSpeed | SPLIT GN2 COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
| 445 | Coil:Heating:Fuel | SPLIT GN2 HEATING COIL | Design Size Nominal Capacity [W] | 7586.61186 |
| 446 | Controller:OutdoorAir | SPLIT GS1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.32602 |
| 447 | Controller:OutdoorAir | SPLIT GS1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.59546E-002 |
| 448 | AirLoopHVAC:UnitarySystem | SPLIT GS1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.32602 |
| 449 | AirLoopHVAC:UnitarySystem | SPLIT GS1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.32602 |
| 450 | AirLoopHVAC:UnitarySystem | SPLIT GS1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.32602 |
| 451 | AirLoopHVAC:UnitarySystem | SPLIT GS1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.32602 |
| 452 | AirLoopHVAC:UnitarySystem | SPLIT GS1_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 5396.80469 |
| 453 | AirLoopHVAC:UnitarySystem | SPLIT GS1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 9287.71069 |
| 454 | AirLoopHVAC:UnitarySystem | SPLIT GS1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 455 | AirLoopHVAC:UnitarySystem | SPLIT GS1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 456 | Fan:OnOff | SPLIT GS1 SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.32602 |
| 457 | Coil:Cooling:DX:SingleSpeed | SPLIT GS1 COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.32602 |
| 458 | Coil:Cooling:DX:SingleSpeed | SPLIT GS1 COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 5396.80469 |
| 459 | Coil:Cooling:DX:SingleSpeed | SPLIT GS1 COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
| 460 | Coil:Heating:Fuel | SPLIT GS1 HEATING COIL | Design Size Nominal Capacity [W] | 9287.71069 |
| 461 | Controller:OutdoorAir | SPLIT GS2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.32787 |
| 462 | Controller:OutdoorAir | SPLIT GS2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.59546E-002 |
| 463 | AirLoopHVAC:UnitarySystem | SPLIT GS2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.32787 |
| 464 | AirLoopHVAC:UnitarySystem | SPLIT GS2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.32787 |
| 465 | AirLoopHVAC:UnitarySystem | SPLIT GS2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.32787 |
| 466 | AirLoopHVAC:UnitarySystem | SPLIT GS2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.32787 |
| 467 | AirLoopHVAC:UnitarySystem | SPLIT GS2_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 5427.42262 |
| 468 | AirLoopHVAC:UnitarySystem | SPLIT GS2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 9329.35268 |
| 469 | AirLoopHVAC:UnitarySystem | SPLIT GS2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 470 | AirLoopHVAC:UnitarySystem | SPLIT GS2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 471 | Fan:OnOff | SPLIT GS2 SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.32787 |
| 472 | Coil:Cooling:DX:SingleSpeed | SPLIT GS2 COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.32787 |
| 473 | Coil:Cooling:DX:SingleSpeed | SPLIT GS2 COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 5427.42262 |
| 474 | Coil:Cooling:DX:SingleSpeed | SPLIT GS2 COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
| 475 | Coil:Heating:Fuel | SPLIT GS2 HEATING COIL | Design Size Nominal Capacity [W] | 9329.35268 |
| 476 | Controller:OutdoorAir | SPLIT MSW_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.97777 |
| 477 | Controller:OutdoorAir | SPLIT MSW_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 5.19091E-002 |
| 478 | AirLoopHVAC:UnitarySystem | SPLIT MSW_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.97777 |
| 479 | AirLoopHVAC:UnitarySystem | SPLIT MSW_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.97777 |
| 480 | AirLoopHVAC:UnitarySystem | SPLIT MSW_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.97777 |
| 481 | AirLoopHVAC:UnitarySystem | SPLIT MSW_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.97777 |
| 482 | AirLoopHVAC:UnitarySystem | SPLIT MSW_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 16185.57247 |
| 483 | AirLoopHVAC:UnitarySystem | SPLIT MSW_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 25908.93758 |
| 484 | AirLoopHVAC:UnitarySystem | SPLIT MSW_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 485 | AirLoopHVAC:UnitarySystem | SPLIT MSW_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 486 | Fan:OnOff | SPLIT MSW SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.97777 |
| 487 | Coil:Cooling:DX:SingleSpeed | SPLIT MSW COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.97777 |
| 488 | Coil:Cooling:DX:SingleSpeed | SPLIT MSW COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 16185.57247 |
| 489 | Coil:Cooling:DX:SingleSpeed | SPLIT MSW COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
| 490 | Coil:Heating:Fuel | SPLIT MSW HEATING COIL | Design Size Nominal Capacity [W] | 25908.93758 |
| 491 | Controller:OutdoorAir | SPLIT MNW_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.83817 |
| 492 | Controller:OutdoorAir | SPLIT MNW_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 5.19091E-002 |
| 493 | AirLoopHVAC:UnitarySystem | SPLIT MNW_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.83817 |
| 494 | AirLoopHVAC:UnitarySystem | SPLIT MNW_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.83817 |
| 495 | AirLoopHVAC:UnitarySystem | SPLIT MNW_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.83817 |
| 496 | AirLoopHVAC:UnitarySystem | SPLIT MNW_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.83817 |
| 497 | AirLoopHVAC:UnitarySystem | SPLIT MNW_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 13874.61592 |
| 498 | AirLoopHVAC:UnitarySystem | SPLIT MNW_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 22765.57932 |
| 499 | AirLoopHVAC:UnitarySystem | SPLIT MNW_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 500 | AirLoopHVAC:UnitarySystem | SPLIT MNW_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 501 | Fan:OnOff | SPLIT MNW SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.83817 |
| 502 | Coil:Cooling:DX:SingleSpeed | SPLIT MNW COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.83817 |
| 503 | Coil:Cooling:DX:SingleSpeed | SPLIT MNW COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 13874.61592 |
| 504 | Coil:Cooling:DX:SingleSpeed | SPLIT MNW COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
| 505 | Coil:Heating:Fuel | SPLIT MNW HEATING COIL | Design Size Nominal Capacity [W] | 22765.57932 |
| 506 | Controller:OutdoorAir | SPLIT MSE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.83867 |
| 507 | Controller:OutdoorAir | SPLIT MSE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 5.19091E-002 |
| 508 | AirLoopHVAC:UnitarySystem | SPLIT MSE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.83867 |
| 509 | AirLoopHVAC:UnitarySystem | SPLIT MSE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.83867 |
| 510 | AirLoopHVAC:UnitarySystem | SPLIT MSE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.83867 |
| 511 | AirLoopHVAC:UnitarySystem | SPLIT MSE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.83867 |
| 512 | AirLoopHVAC:UnitarySystem | SPLIT MSE_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 13882.99486 |
| 513 | AirLoopHVAC:UnitarySystem | SPLIT MSE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 22777.28629 |
| 514 | AirLoopHVAC:UnitarySystem | SPLIT MSE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 515 | AirLoopHVAC:UnitarySystem | SPLIT MSE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 516 | Fan:OnOff | SPLIT MSE SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.83867 |
| 517 | Coil:Cooling:DX:SingleSpeed | SPLIT MSE COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.83867 |
| 518 | Coil:Cooling:DX:SingleSpeed | SPLIT MSE COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 13882.99486 |
| 519 | Coil:Cooling:DX:SingleSpeed | SPLIT MSE COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
| 520 | Coil:Heating:Fuel | SPLIT MSE HEATING COIL | Design Size Nominal Capacity [W] | 22777.28629 |
| 521 | Controller:OutdoorAir | SPLIT MNE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.70339 |
| 522 | Controller:OutdoorAir | SPLIT MNE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 5.19091E-002 |
| 523 | AirLoopHVAC:UnitarySystem | SPLIT MNE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.70339 |
| 524 | AirLoopHVAC:UnitarySystem | SPLIT MNE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.70339 |
| 525 | AirLoopHVAC:UnitarySystem | SPLIT MNE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.70339 |
| 526 | AirLoopHVAC:UnitarySystem | SPLIT MNE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.70339 |
| 527 | AirLoopHVAC:UnitarySystem | SPLIT MNE_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 11643.63330 |
| 528 | AirLoopHVAC:UnitarySystem | SPLIT MNE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 19731.35516 |
| 529 | AirLoopHVAC:UnitarySystem | SPLIT MNE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 530 | AirLoopHVAC:UnitarySystem | SPLIT MNE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 531 | Fan:OnOff | SPLIT MNE SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.70339 |
| 532 | Coil:Cooling:DX:SingleSpeed | SPLIT MNE COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.70339 |
| 533 | Coil:Cooling:DX:SingleSpeed | SPLIT MNE COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 11643.63330 |
| 534 | Coil:Cooling:DX:SingleSpeed | SPLIT MNE COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
| 535 | Coil:Heating:Fuel | SPLIT MNE HEATING COIL | Design Size Nominal Capacity [W] | 19731.35516 |
| 536 | Controller:OutdoorAir | SPLIT MN1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.62784 |
| 537 | Controller:OutdoorAir | SPLIT MN1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 5.19091E-002 |
| 538 | AirLoopHVAC:UnitarySystem | SPLIT MN1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.62784 |
| 539 | AirLoopHVAC:UnitarySystem | SPLIT MN1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.62784 |
| 540 | AirLoopHVAC:UnitarySystem | SPLIT MN1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.62784 |
| 541 | AirLoopHVAC:UnitarySystem | SPLIT MN1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.62784 |
| 542 | AirLoopHVAC:UnitarySystem | SPLIT MN1_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 10392.98014 |
| 543 | AirLoopHVAC:UnitarySystem | SPLIT MN1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 18030.35713 |
| 544 | AirLoopHVAC:UnitarySystem | SPLIT MN1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 545 | AirLoopHVAC:UnitarySystem | SPLIT MN1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 546 | Fan:OnOff | SPLIT MN1 SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.62784 |
| 547 | Coil:Cooling:DX:SingleSpeed | SPLIT MN1 COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.62784 |
| 548 | Coil:Cooling:DX:SingleSpeed | SPLIT MN1 COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 10392.98014 |
| 549 | Coil:Cooling:DX:SingleSpeed | SPLIT MN1 COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
| 550 | Coil:Heating:Fuel | SPLIT MN1 HEATING COIL | Design Size Nominal Capacity [W] | 18030.35713 |
| 551 | Controller:OutdoorAir | SPLIT MN2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.62618 |
| 552 | Controller:OutdoorAir | SPLIT MN2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 5.19091E-002 |
| 553 | AirLoopHVAC:UnitarySystem | SPLIT MN2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.62618 |
| 554 | AirLoopHVAC:UnitarySystem | SPLIT MN2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.62618 |
| 555 | AirLoopHVAC:UnitarySystem | SPLIT MN2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.62618 |
| 556 | AirLoopHVAC:UnitarySystem | SPLIT MN2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.62618 |
| 557 | AirLoopHVAC:UnitarySystem | SPLIT MN2_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 10365.54477 |
| 558 | AirLoopHVAC:UnitarySystem | SPLIT MN2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 17993.04413 |
| 559 | AirLoopHVAC:UnitarySystem | SPLIT MN2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 560 | AirLoopHVAC:UnitarySystem | SPLIT MN2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 561 | Fan:OnOff | SPLIT MN2 SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.62618 |
| 562 | Coil:Cooling:DX:SingleSpeed | SPLIT MN2 COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.62618 |
| 563 | Coil:Cooling:DX:SingleSpeed | SPLIT MN2 COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 10365.54477 |
| 564 | Coil:Cooling:DX:SingleSpeed | SPLIT MN2 COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
| 565 | Coil:Heating:Fuel | SPLIT MN2 HEATING COIL | Design Size Nominal Capacity [W] | 17993.04413 |
| 566 | Controller:OutdoorAir | SPLIT MS1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.77544 |
| 567 | Controller:OutdoorAir | SPLIT MS1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 5.19091E-002 |
| 568 | AirLoopHVAC:UnitarySystem | SPLIT MS1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.77544 |
| 569 | AirLoopHVAC:UnitarySystem | SPLIT MS1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.77544 |
| 570 | AirLoopHVAC:UnitarySystem | SPLIT MS1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.77544 |
| 571 | AirLoopHVAC:UnitarySystem | SPLIT MS1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.77544 |
| 572 | AirLoopHVAC:UnitarySystem | SPLIT MS1_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 12836.31392 |
| 573 | AirLoopHVAC:UnitarySystem | SPLIT MS1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 21353.67765 |
| 574 | AirLoopHVAC:UnitarySystem | SPLIT MS1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 575 | AirLoopHVAC:UnitarySystem | SPLIT MS1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 576 | Fan:OnOff | SPLIT MS1 SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.77544 |
| 577 | Coil:Cooling:DX:SingleSpeed | SPLIT MS1 COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.77544 |
| 578 | Coil:Cooling:DX:SingleSpeed | SPLIT MS1 COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 12836.31392 |
| 579 | Coil:Cooling:DX:SingleSpeed | SPLIT MS1 COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
| 580 | Coil:Heating:Fuel | SPLIT MS1 HEATING COIL | Design Size Nominal Capacity [W] | 21353.67765 |
| 581 | Controller:OutdoorAir | SPLIT MS2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.77349 |
| 582 | Controller:OutdoorAir | SPLIT MS2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 5.19091E-002 |
| 583 | AirLoopHVAC:UnitarySystem | SPLIT MS2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.77349 |
| 584 | AirLoopHVAC:UnitarySystem | SPLIT MS2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.77349 |
| 585 | AirLoopHVAC:UnitarySystem | SPLIT MS2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.77349 |
| 586 | AirLoopHVAC:UnitarySystem | SPLIT MS2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.77349 |
| 587 | AirLoopHVAC:UnitarySystem | SPLIT MS2_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 12803.93681 |
| 588 | AirLoopHVAC:UnitarySystem | SPLIT MS2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 21309.64288 |
| 589 | AirLoopHVAC:UnitarySystem | SPLIT MS2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 590 | AirLoopHVAC:UnitarySystem | SPLIT MS2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 591 | Fan:OnOff | SPLIT MS2 SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.77349 |
| 592 | Coil:Cooling:DX:SingleSpeed | SPLIT MS2 COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.77349 |
| 593 | Coil:Cooling:DX:SingleSpeed | SPLIT MS2 COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 12803.93681 |
| 594 | Coil:Cooling:DX:SingleSpeed | SPLIT MS2 COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
| 595 | Coil:Heating:Fuel | SPLIT MS2 HEATING COIL | Design Size Nominal Capacity [W] | 21309.64288 |
| 596 | Controller:OutdoorAir | SPLIT TSW_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.53031 |
| 597 | Controller:OutdoorAir | SPLIT TSW_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.59546E-002 |
| 598 | AirLoopHVAC:UnitarySystem | SPLIT TSW_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.53031 |
| 599 | AirLoopHVAC:UnitarySystem | SPLIT TSW_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.53031 |
| 600 | AirLoopHVAC:UnitarySystem | SPLIT TSW_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.53031 |
| 601 | AirLoopHVAC:UnitarySystem | SPLIT TSW_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.53031 |
| 602 | AirLoopHVAC:UnitarySystem | SPLIT TSW_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 8778.48188 |
| 603 | AirLoopHVAC:UnitarySystem | SPLIT TSW_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 13887.09426 |
| 604 | AirLoopHVAC:UnitarySystem | SPLIT TSW_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 605 | AirLoopHVAC:UnitarySystem | SPLIT TSW_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 606 | Fan:OnOff | SPLIT TSW SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.53031 |
| 607 | Coil:Cooling:DX:SingleSpeed | SPLIT TSW COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.53031 |
| 608 | Coil:Cooling:DX:SingleSpeed | SPLIT TSW COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 8778.48188 |
| 609 | Coil:Cooling:DX:SingleSpeed | SPLIT TSW COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
| 610 | Coil:Heating:Fuel | SPLIT TSW HEATING COIL | Design Size Nominal Capacity [W] | 13887.09426 |
| 611 | Controller:OutdoorAir | SPLIT TNW_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.46448 |
| 612 | Controller:OutdoorAir | SPLIT TNW_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.59546E-002 |
| 613 | AirLoopHVAC:UnitarySystem | SPLIT TNW_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.46448 |
| 614 | AirLoopHVAC:UnitarySystem | SPLIT TNW_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.46448 |
| 615 | AirLoopHVAC:UnitarySystem | SPLIT TNW_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.46448 |
| 616 | AirLoopHVAC:UnitarySystem | SPLIT TNW_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.46448 |
| 617 | AirLoopHVAC:UnitarySystem | SPLIT TNW_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 7688.72458 |
| 618 | AirLoopHVAC:UnitarySystem | SPLIT TNW_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 12404.77695 |
| 619 | AirLoopHVAC:UnitarySystem | SPLIT TNW_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 620 | AirLoopHVAC:UnitarySystem | SPLIT TNW_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 621 | Fan:OnOff | SPLIT TNW SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.46448 |
| 622 | Coil:Cooling:DX:SingleSpeed | SPLIT TNW COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.46448 |
| 623 | Coil:Cooling:DX:SingleSpeed | SPLIT TNW COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 7688.72458 |
| 624 | Coil:Cooling:DX:SingleSpeed | SPLIT TNW COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
| 625 | Coil:Heating:Fuel | SPLIT TNW HEATING COIL | Design Size Nominal Capacity [W] | 12404.77695 |
| 626 | Controller:OutdoorAir | SPLIT TSE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.42876 |
| 627 | Controller:OutdoorAir | SPLIT TSE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.59546E-002 |
| 628 | AirLoopHVAC:UnitarySystem | SPLIT TSE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.42876 |
| 629 | AirLoopHVAC:UnitarySystem | SPLIT TSE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.42876 |
| 630 | AirLoopHVAC:UnitarySystem | SPLIT TSE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.42876 |
| 631 | AirLoopHVAC:UnitarySystem | SPLIT TSE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.42876 |
| 632 | AirLoopHVAC:UnitarySystem | SPLIT TSE_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 7097.46560 |
| 633 | AirLoopHVAC:UnitarySystem | SPLIT TSE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 11600.79848 |
| 634 | AirLoopHVAC:UnitarySystem | SPLIT TSE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 635 | AirLoopHVAC:UnitarySystem | SPLIT TSE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 636 | Fan:OnOff | SPLIT TSE SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.42876 |
| 637 | Coil:Cooling:DX:SingleSpeed | SPLIT TSE COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.42876 |
| 638 | Coil:Cooling:DX:SingleSpeed | SPLIT TSE COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 7097.46560 |
| 639 | Coil:Cooling:DX:SingleSpeed | SPLIT TSE COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
| 640 | Coil:Heating:Fuel | SPLIT TSE HEATING COIL | Design Size Nominal Capacity [W] | 11600.79848 |
| 641 | Controller:OutdoorAir | SPLIT TNE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.36436 |
| 642 | Controller:OutdoorAir | SPLIT TNE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.59546E-002 |
| 643 | AirLoopHVAC:UnitarySystem | SPLIT TNE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.36436 |
| 644 | AirLoopHVAC:UnitarySystem | SPLIT TNE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.36436 |
| 645 | AirLoopHVAC:UnitarySystem | SPLIT TNE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.36436 |
| 646 | AirLoopHVAC:UnitarySystem | SPLIT TNE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.36436 |
| 647 | AirLoopHVAC:UnitarySystem | SPLIT TNE_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 6031.48204 |
| 648 | AirLoopHVAC:UnitarySystem | SPLIT TNE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 10150.85476 |
| 649 | AirLoopHVAC:UnitarySystem | SPLIT TNE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 650 | AirLoopHVAC:UnitarySystem | SPLIT TNE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 651 | Fan:OnOff | SPLIT TNE SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.36436 |
| 652 | Coil:Cooling:DX:SingleSpeed | SPLIT TNE COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.36436 |
| 653 | Coil:Cooling:DX:SingleSpeed | SPLIT TNE COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 6031.48204 |
| 654 | Coil:Cooling:DX:SingleSpeed | SPLIT TNE COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
| 655 | Coil:Heating:Fuel | SPLIT TNE HEATING COIL | Design Size Nominal Capacity [W] | 10150.85476 |
| 656 | Controller:OutdoorAir | SPLIT TN1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.34258 |
| 657 | Controller:OutdoorAir | SPLIT TN1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.59546E-002 |
| 658 | AirLoopHVAC:UnitarySystem | SPLIT TN1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.34258 |
| 659 | AirLoopHVAC:UnitarySystem | SPLIT TN1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.34258 |
| 660 | AirLoopHVAC:UnitarySystem | SPLIT TN1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.34258 |
| 661 | AirLoopHVAC:UnitarySystem | SPLIT TN1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.34258 |
| 662 | AirLoopHVAC:UnitarySystem | SPLIT TN1_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 5670.97310 |
| 663 | AirLoopHVAC:UnitarySystem | SPLIT TN1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 9660.50761 |
| 664 | AirLoopHVAC:UnitarySystem | SPLIT TN1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 665 | AirLoopHVAC:UnitarySystem | SPLIT TN1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 666 | Fan:OnOff | SPLIT TN1 SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.34258 |
| 667 | Coil:Cooling:DX:SingleSpeed | SPLIT TN1 COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.34258 |
| 668 | Coil:Cooling:DX:SingleSpeed | SPLIT TN1 COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 5670.97310 |
| 669 | Coil:Cooling:DX:SingleSpeed | SPLIT TN1 COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
| 670 | Coil:Heating:Fuel | SPLIT TN1 HEATING COIL | Design Size Nominal Capacity [W] | 9660.50761 |
| 671 | Controller:OutdoorAir | SPLIT TN2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.33999 |
| 672 | Controller:OutdoorAir | SPLIT TN2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.59546E-002 |
| 673 | AirLoopHVAC:UnitarySystem | SPLIT TN2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.33999 |
| 674 | AirLoopHVAC:UnitarySystem | SPLIT TN2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.33999 |
| 675 | AirLoopHVAC:UnitarySystem | SPLIT TN2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.33999 |
| 676 | AirLoopHVAC:UnitarySystem | SPLIT TN2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.33999 |
| 677 | AirLoopHVAC:UnitarySystem | SPLIT TN2_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 5628.11356 |
| 678 | AirLoopHVAC:UnitarySystem | SPLIT TN2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 9602.21710 |
| 679 | AirLoopHVAC:UnitarySystem | SPLIT TN2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 680 | AirLoopHVAC:UnitarySystem | SPLIT TN2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 681 | Fan:OnOff | SPLIT TN2 SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.33999 |
| 682 | Coil:Cooling:DX:SingleSpeed | SPLIT TN2 COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.33999 |
| 683 | Coil:Cooling:DX:SingleSpeed | SPLIT TN2 COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 5628.11356 |
| 684 | Coil:Cooling:DX:SingleSpeed | SPLIT TN2 COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
| 685 | Coil:Heating:Fuel | SPLIT TN2 HEATING COIL | Design Size Nominal Capacity [W] | 9602.21710 |
| 686 | Controller:OutdoorAir | SPLIT TS1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.41086 |
| 687 | Controller:OutdoorAir | SPLIT TS1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.59546E-002 |
| 688 | AirLoopHVAC:UnitarySystem | SPLIT TS1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.41086 |
| 689 | AirLoopHVAC:UnitarySystem | SPLIT TS1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.41086 |
| 690 | AirLoopHVAC:UnitarySystem | SPLIT TS1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.41086 |
| 691 | AirLoopHVAC:UnitarySystem | SPLIT TS1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.41086 |
| 692 | AirLoopHVAC:UnitarySystem | SPLIT TS1_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 6801.19544 |
| 693 | AirLoopHVAC:UnitarySystem | SPLIT TS1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 11197.80937 |
| 694 | AirLoopHVAC:UnitarySystem | SPLIT TS1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 695 | AirLoopHVAC:UnitarySystem | SPLIT TS1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 696 | Fan:OnOff | SPLIT TS1 SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.41086 |
| 697 | Coil:Cooling:DX:SingleSpeed | SPLIT TS1 COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.41086 |
| 698 | Coil:Cooling:DX:SingleSpeed | SPLIT TS1 COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 6801.19544 |
| 699 | Coil:Cooling:DX:SingleSpeed | SPLIT TS1 COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
| 700 | Coil:Heating:Fuel | SPLIT TS1 HEATING COIL | Design Size Nominal Capacity [W] | 11197.80937 |
| 701 | Controller:OutdoorAir | SPLIT TS2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.40825 |
| 702 | Controller:OutdoorAir | SPLIT TS2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.59546E-002 |
| 703 | AirLoopHVAC:UnitarySystem | SPLIT TS2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.40825 |
| 704 | AirLoopHVAC:UnitarySystem | SPLIT TS2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.40825 |
| 705 | AirLoopHVAC:UnitarySystem | SPLIT TS2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.40825 |
| 706 | AirLoopHVAC:UnitarySystem | SPLIT TS2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.40825 |
| 707 | AirLoopHVAC:UnitarySystem | SPLIT TS2_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 6757.97336 |
| 708 | AirLoopHVAC:UnitarySystem | SPLIT TS2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 11139.02469 |
| 709 | AirLoopHVAC:UnitarySystem | SPLIT TS2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 710 | AirLoopHVAC:UnitarySystem | SPLIT TS2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 711 | Fan:OnOff | SPLIT TS2 SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.40825 |
| 712 | Coil:Cooling:DX:SingleSpeed | SPLIT TS2 COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.40825 |
| 713 | Coil:Cooling:DX:SingleSpeed | SPLIT TS2 COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 6757.97336 |
| 714 | Coil:Cooling:DX:SingleSpeed | SPLIT TS2 COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
| 715 | Coil:Heating:Fuel | SPLIT TS2 HEATING COIL | Design Size Nominal Capacity [W] | 11139.02469 |
| Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
| 1 | Coil:Cooling:DX:SingleSpeed | SPLIT GSW COOLING COIL | 6146.1 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 |
| 2 | Coil:Cooling:DX:SingleSpeed | SPLIT GNW COOLING COIL | 5031.4 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 |
| 3 | Coil:Cooling:DX:SingleSpeed | SPLIT OFFICE COOLING COIL | 6461.9 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 |
| 4 | Coil:Cooling:DX:SingleSpeed | SPLIT GNE COOLING COIL | 4427.8 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 |
| 5 | Coil:Cooling:DX:SingleSpeed | SPLIT GN1 COOLING COIL | 3958.0 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 |
| 6 | Coil:Cooling:DX:SingleSpeed | SPLIT GN2 COOLING COIL | 3949.8 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 |
| 7 | Coil:Cooling:DX:SingleSpeed | SPLIT GS1 COOLING COIL | 5141.3 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 |
| 8 | Coil:Cooling:DX:SingleSpeed | SPLIT GS2 COOLING COIL | 5170.5 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 |
| 9 | Coil:Cooling:DX:SingleSpeed | SPLIT MSW COOLING COIL | 15419.3 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 |
| 10 | Coil:Cooling:DX:SingleSpeed | SPLIT MNW COOLING COIL | 13217.8 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 |
| 11 | Coil:Cooling:DX:SingleSpeed | SPLIT MSE COOLING COIL | 13225.7 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 |
| 12 | Coil:Cooling:DX:SingleSpeed | SPLIT MNE COOLING COIL | 11092.4 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 |
| 13 | Coil:Cooling:DX:SingleSpeed | SPLIT MN1 COOLING COIL | 9901.0 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 |
| 14 | Coil:Cooling:DX:SingleSpeed | SPLIT MN2 COOLING COIL | 9874.8 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 |
| 15 | Coil:Cooling:DX:SingleSpeed | SPLIT MS1 COOLING COIL | 12228.6 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 |
| 16 | Coil:Cooling:DX:SingleSpeed | SPLIT MS2 COOLING COIL | 12197.8 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 |
| 17 | Coil:Cooling:DX:SingleSpeed | SPLIT TSW COOLING COIL | 8362.9 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 |
| 18 | Coil:Cooling:DX:SingleSpeed | SPLIT TNW COOLING COIL | 7324.7 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 |
| 19 | Coil:Cooling:DX:SingleSpeed | SPLIT TSE COOLING COIL | 6761.5 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 |
| 20 | Coil:Cooling:DX:SingleSpeed | SPLIT TNE COOLING COIL | 5745.9 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 |
| 21 | Coil:Cooling:DX:SingleSpeed | SPLIT TN1 COOLING COIL | 5402.5 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 |
| 22 | Coil:Cooling:DX:SingleSpeed | SPLIT TN2 COOLING COIL | 5361.7 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 |
| 23 | Coil:Cooling:DX:SingleSpeed | SPLIT TS1 COOLING COIL | 6479.2 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 |
| 24 | Coil:Cooling:DX:SingleSpeed | SPLIT TS2 COOLING COIL | 6438.0 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 |
| Zone Name | # Surfaces | |
| 1 | G SW APARTMENT | 9 |
| 2 | G NW APARTMENT | 9 |
| 3 | OFFICE | 9 |
| 4 | G NE APARTMENT | 9 |
| 5 | G N1 APARTMENT | 8 |
| 6 | G N2 APARTMENT | 8 |
| 7 | G S1 APARTMENT | 8 |
| 8 | G S2 APARTMENT | 8 |
| 9 | M SW APARTMENT | 9 |
| 10 | M NW APARTMENT | 9 |
| 11 | M SE APARTMENT | 9 |
| 12 | M NE APARTMENT | 9 |
| 13 | M N1 APARTMENT | 8 |
| 14 | M N2 APARTMENT | 8 |
| 15 | M S1 APARTMENT | 8 |
| 16 | M S2 APARTMENT | 8 |
| 17 | T SW APARTMENT | 9 |
| 18 | T NW APARTMENT | 9 |
| 19 | T SE APARTMENT | 9 |
| 20 | T NE APARTMENT | 9 |
| 21 | T N1 APARTMENT | 8 |
| 22 | T N2 APARTMENT | 8 |
| 23 | T S1 APARTMENT | 8 |
| 24 | T S2 APARTMENT | 8 |
| 25 | T CORRIDOR | 13 |
| 26 | G CORRIDOR | 13 |
| 27 | M CORRIDOR | 13 |
| Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
| 1 | G SWALL SWA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_GRD | 0.621 | 0.568 | 28.24 | 35.30 | 28.24 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 2 | GWINDOW1 S SWA | Window | G SWALL SWA | Window5 Detailed Fenestration | RESWINDOW_U_0.3097_SHGC_0.45 | N/A | 1.759 | No | 7.06 | 7.06 | 7.06 | 180.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 3 | G WWALL SWA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_GRD | 0.621 | 0.568 | 18.58 | 23.22 | 18.58 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 4 | GWINDOW1 W SWA | Window | G WWALL SWA | Window5 Detailed Fenestration | RESWINDOW_U_0.3097_SHGC_0.45 | N/A | 1.759 | No | 4.65 | 4.65 | 4.65 | 270.00 | 90.00 | 3.81 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 5 | G NIWALL SWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-G NIWALL SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 6 | G EIWALL SWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | iz-G EIWALL SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 7 | G GFLOOR SWA | Floor | CTF - ConductionTransferFunction | GGFLOORSWA_FFACTOR | 0.154 | 0.149 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 8 | G CEILIN SWA | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | G CEILIN SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 9 | G INTERNALMASS SWA | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 88.25 | 88.25 | 88.25 | 0.00 | 90.00 | 88.25 | 1.00 | 0.00 | G INTERNALMASS SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 10 | G NWALL NWA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_GRD | 0.621 | 0.568 | 28.24 | 35.30 | 28.24 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 11 | GWINDOW1 N NWA | Window | G NWALL NWA | Window5 Detailed Fenestration | RESWINDOW_U_0.3097_SHGC_0.45 | N/A | 1.759 | No | 7.06 | 7.06 | 7.06 | 0.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 12 | G WWALL NWA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_GRD | 0.621 | 0.568 | 18.58 | 23.22 | 18.58 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 13 | GWINDOW1 W NWA | Window | G WWALL NWA | Window5 Detailed Fenestration | RESWINDOW_U_0.3097_SHGC_0.45 | N/A | 1.759 | No | 4.65 | 4.65 | 4.65 | 270.00 | 90.00 | 3.81 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 14 | G SIWALL NWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-G SIWALL NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 15 | G EIWALL NWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | iz-G EIWALL NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 16 | G GFLOOR NWA | Floor | CTF - ConductionTransferFunction | GGFLOORNWA_FFACTOR | 0.154 | 0.149 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 17 | G CEILIN NWA | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | G CEILIN NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 18 | G INTERNALMASS NWA | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 88.25 | 88.25 | 88.25 | 0.00 | 90.00 | 88.25 | 1.00 | 0.00 | G INTERNALMASS NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 19 | G SWALL SEA | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.621 | 0.568 | 28.24 | 35.30 | 28.24 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 20 | GWINDOW1 S SEA | Window | G SWALL SEA | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3097_SHGC_0.45 | N/A | 1.759 | No | 7.06 | 7.06 | 7.06 | 180.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 21 | G EWALL SEA | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.621 | 0.568 | 18.58 | 23.22 | 18.58 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 22 | GWINDOW1 E SEA | Window | G EWALL SEA | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3097_SHGC_0.45 | N/A | 1.759 | No | 4.65 | 4.65 | 4.65 | 90.00 | 90.00 | 3.81 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 23 | G NIWALL SEA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-G NIWALL SEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 24 | iz-G EIWALL S2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | G EIWALL S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 25 | G GFLOOR SEA | Floor | CTF - ConductionTransferFunction | GGFLOORSEA_FFACTOR | 0.154 | 0.149 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 26 | G CEILIN SEA | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | G CEILIN SEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 27 | G INTERNALMASS SEA | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 88.25 | 88.25 | 88.25 | 0.00 | 90.00 | 88.25 | 1.00 | 0.00 | G INTERNALMASS SEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 28 | G NWALL NEA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_GRD | 0.621 | 0.568 | 28.24 | 35.30 | 28.24 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 29 | GWINDOW1 N NEA | Window | G NWALL NEA | Window5 Detailed Fenestration | RESWINDOW_U_0.3097_SHGC_0.45 | N/A | 1.759 | No | 7.06 | 7.06 | 7.06 | 0.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 30 | G EWALL NEA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_GRD | 0.621 | 0.568 | 18.58 | 23.22 | 18.58 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 31 | GWINDOW1 E NEA | Window | G EWALL NEA | Window5 Detailed Fenestration | RESWINDOW_U_0.3097_SHGC_0.45 | N/A | 1.759 | No | 4.65 | 4.65 | 4.65 | 90.00 | 90.00 | 3.81 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 32 | G SIWALL NEA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-G SIWALL NEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 33 | iz-G EIWALL N2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | G EIWALL N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 34 | G GFLOOR NEA | Floor | CTF - ConductionTransferFunction | GGFLOORNEA_FFACTOR | 0.154 | 0.149 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 35 | G CEILIN NEA | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | G CEILIN NEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 36 | G INTERNALMASS NEA | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 88.25 | 88.25 | 88.25 | 0.00 | 90.00 | 88.25 | 1.00 | 0.00 | G INTERNALMASS NEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 37 | G NWALL N1A | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_GRD | 0.621 | 0.568 | 28.24 | 35.30 | 28.24 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 38 | GWINDOW1 N N1A | Window | G NWALL N1A | Window5 Detailed Fenestration | RESWINDOW_U_0.3097_SHGC_0.45 | N/A | 1.759 | No | 7.06 | 7.06 | 7.06 | 0.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 39 | G SIWALL N1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-G SIWALL N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 40 | G EIWALL N1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | iz-G EIWALL N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 41 | iz-G EIWALL NWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | G EIWALL NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 42 | G GFLOOR N1A | Floor | CTF - ConductionTransferFunction | GGFLOORN1A_FFACTOR | 9.217E-002 | 9.015E-002 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 43 | G CEILIN N1A | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | G CEILIN N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 44 | G INTERNALMASS N1A | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 88.25 | 88.25 | 88.25 | 0.00 | 90.00 | 88.25 | 1.00 | 0.00 | G INTERNALMASS N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 45 | G NWALL N2A | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_GRD | 0.621 | 0.568 | 28.24 | 35.30 | 28.24 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 46 | GWINDOW1 N N2A | Window | G NWALL N2A | Window5 Detailed Fenestration | RESWINDOW_U_0.3097_SHGC_0.45 | N/A | 1.759 | No | 7.06 | 7.06 | 7.06 | 0.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 47 | G SIWALL N2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-G SIWALL N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 48 | G EIWALL N2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | iz-G EIWALL N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 49 | iz-G EIWALL N1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | G EIWALL N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 50 | G GFLOOR N2A | Floor | CTF - ConductionTransferFunction | GGFLOORN2A_FFACTOR | 9.217E-002 | 9.015E-002 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 51 | G CEILIN N2A | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | G CEILIN N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 52 | G INTERNALMASS N2A | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 88.25 | 88.25 | 88.25 | 0.00 | 90.00 | 88.25 | 1.00 | 0.00 | G INTERNALMASS N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 53 | G SWALL S1A | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_GRD | 0.621 | 0.568 | 28.24 | 35.30 | 28.24 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 54 | GWINDOW1 S S1A | Window | G SWALL S1A | Window5 Detailed Fenestration | RESWINDOW_U_0.3097_SHGC_0.45 | N/A | 1.759 | No | 7.06 | 7.06 | 7.06 | 180.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 55 | G NIWALL S1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-G NIWALL S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 56 | G EIWALL S1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | iz-G EIWALL S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 57 | iz-G EIWALL SWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | G EIWALL SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 58 | G GFLOOR S1A | Floor | CTF - ConductionTransferFunction | GGFLOORS1A_FFACTOR | 9.217E-002 | 9.015E-002 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 59 | G CEILIN S1A | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | G CEILIN S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 60 | G INTERNALMASS S1A | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 88.25 | 88.25 | 88.25 | 0.00 | 90.00 | 88.25 | 1.00 | 0.00 | G INTERNALMASS S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 61 | G SWALL S2A | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_GRD | 0.621 | 0.568 | 28.24 | 35.30 | 28.24 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 62 | GWINDOW1 S S2A | Window | G SWALL S2A | Window5 Detailed Fenestration | RESWINDOW_U_0.3097_SHGC_0.45 | N/A | 1.759 | No | 7.06 | 7.06 | 7.06 | 180.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 63 | G NIWALL S2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-G NIWALL S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 64 | G EIWALL S2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | iz-G EIWALL S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 65 | iz-G EIWALL S1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | G EIWALL S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 66 | G GFLOOR S2A | Floor | CTF - ConductionTransferFunction | GGFLOORS2A_FFACTOR | 9.217E-002 | 9.015E-002 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 67 | G CEILIN S2A | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | G CEILIN S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 68 | G INTERNALMASS S2A | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 88.25 | 88.25 | 88.25 | 0.00 | 90.00 | 88.25 | 1.00 | 0.00 | G INTERNALMASS S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 69 | M WWALL SWA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.629 | 0.575 | 18.58 | 23.22 | 18.58 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 70 | MWINDOW1 W SWA | Window | M WWALL SWA | Window5 Detailed Fenestration | RESWINDOW_U_0.3097_SHGC_0.45 | N/A | 1.759 | No | 4.65 | 4.65 | 4.65 | 270.00 | 90.00 | 3.81 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 71 | M SWALL SWA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.629 | 0.575 | 28.24 | 35.30 | 28.24 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 72 | MWINDOW1 S SWA | Window | M SWALL SWA | Window5 Detailed Fenestration | RESWINDOW_U_0.3097_SHGC_0.45 | N/A | 1.759 | No | 7.06 | 7.06 | 7.06 | 180.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 73 | M NIWALL SWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-M NIWALL SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 74 | M EIWALL SWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 90.00 | 90.00 | 3.05 | 7.62 | 0.00 | iz-M EIWALL SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 75 | M GFLOOR SWA | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | M GFLOOR SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 76 | M CEILIN SWA | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | M CEILIN SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 77 | M INTERNALMASS SWA | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 176.50 | 176.50 | 176.50 | 0.00 | 90.00 | 176.50 | 1.00 | 0.00 | M INTERNALMASS SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 78 | M NWALL NWA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.629 | 0.575 | 28.24 | 35.30 | 28.24 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 79 | MWINDOW1 N NWA | Window | M NWALL NWA | Window5 Detailed Fenestration | RESWINDOW_U_0.3097_SHGC_0.45 | N/A | 1.759 | No | 7.06 | 7.06 | 7.06 | 0.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 80 | M WWALL NWA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.629 | 0.575 | 18.58 | 23.22 | 18.58 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 81 | MWINDOW1 W NWA | Window | M WWALL NWA | Window5 Detailed Fenestration | RESWINDOW_U_0.3097_SHGC_0.45 | N/A | 1.759 | No | 4.65 | 4.65 | 4.65 | 270.00 | 90.00 | 3.81 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 82 | M SIWALL NWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-M SIWALL NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 83 | M EIWALL NWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | iz-M EIWALL NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 84 | M GFLOOR NWA | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | M GFLOOR NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 85 | M CEILIN NWA | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | M CEILIN NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 86 | M INTERNALMASS NWA | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 176.50 | 176.50 | 176.50 | 0.00 | 90.00 | 176.50 | 1.00 | 0.00 | M INTERNALMASS NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 87 | M EWALL SEA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.629 | 0.575 | 18.58 | 23.22 | 18.58 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 88 | MWINDOW1 E SEA | Window | M EWALL SEA | Window5 Detailed Fenestration | RESWINDOW_U_0.3097_SHGC_0.45 | N/A | 1.759 | No | 4.65 | 4.65 | 4.65 | 90.00 | 90.00 | 3.81 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 89 | M SWALL SEA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.629 | 0.575 | 28.24 | 35.30 | 28.24 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 90 | MWINDOW1 S SEA | Window | M SWALL SEA | Window5 Detailed Fenestration | RESWINDOW_U_0.3097_SHGC_0.45 | N/A | 1.759 | No | 7.06 | 7.06 | 7.06 | 180.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 91 | M NIWALL SEA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-M NIWALL SEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 92 | iz-M EIWALL S2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | M EIWALL S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 93 | M GFLOOR SEA | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | M GFLOOR SEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 94 | M CEILIN SEA | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | M CEILIN SEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 95 | M INTERNALMASS SEA | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 176.50 | 176.50 | 176.50 | 0.00 | 90.00 | 176.50 | 1.00 | 0.00 | M INTERNALMASS SEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 96 | M NWALL NEA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.629 | 0.575 | 28.24 | 35.30 | 28.24 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 97 | MWINDOW1 N NEA | Window | M NWALL NEA | Window5 Detailed Fenestration | RESWINDOW_U_0.3097_SHGC_0.45 | N/A | 1.759 | No | 7.06 | 7.06 | 7.06 | 0.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 98 | M EWALL NEA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.629 | 0.575 | 18.58 | 23.22 | 18.58 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 99 | MWINDOW1 E NEA | Window | M EWALL NEA | Window5 Detailed Fenestration | RESWINDOW_U_0.3097_SHGC_0.45 | N/A | 1.759 | No | 4.65 | 4.65 | 4.65 | 90.00 | 90.00 | 3.81 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 100 | M SIWALL NEA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-M SIWALL NEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 101 | iz-M EIWALL N2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | M EIWALL N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 102 | M GFLOOR NEA | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | M GFLOOR NEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 103 | M CEILIN NEA | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | M CEILIN NEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 104 | M INTERNALMASS NEA | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 176.50 | 176.50 | 176.50 | 0.00 | 90.00 | 176.50 | 1.00 | 0.00 | M INTERNALMASS NEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 105 | M NWALL N1A | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.629 | 0.575 | 28.24 | 35.30 | 28.24 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 106 | MWINDOW1 N N1A | Window | M NWALL N1A | Window5 Detailed Fenestration | RESWINDOW_U_0.3097_SHGC_0.45 | N/A | 1.759 | No | 7.06 | 7.06 | 7.06 | 0.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 107 | M SIWALL N1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-M SIWALL N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 108 | M EIWALL N1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | iz-M EIWALL N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 109 | iz-M EIWALL NWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | M EIWALL NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 110 | M GFLOOR N1A | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | M GFLOOR N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 111 | M CEILIN N1A | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | M CEILIN N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 112 | M INTERNALMASS N1A | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 176.50 | 176.50 | 176.50 | 0.00 | 90.00 | 176.50 | 1.00 | 0.00 | M INTERNALMASS N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 113 | M NWALL N2A | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.629 | 0.575 | 28.24 | 35.30 | 28.24 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 114 | MWINDOW1 N N2A | Window | M NWALL N2A | Window5 Detailed Fenestration | RESWINDOW_U_0.3097_SHGC_0.45 | N/A | 1.759 | No | 7.06 | 7.06 | 7.06 | 0.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 115 | M SIWALL N2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-M SIWALL N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 116 | M EIWALL N2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | iz-M EIWALL N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 117 | iz-M EIWALL N1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | M EIWALL N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 118 | M GFLOOR N2A | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | M GFLOOR N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 119 | M CEILIN N2A | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | M CEILIN N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 120 | M INTERNALMASS N2A | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 176.50 | 176.50 | 176.50 | 0.00 | 90.00 | 176.50 | 1.00 | 0.00 | M INTERNALMASS N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 121 | M SWALL S1A | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.629 | 0.575 | 28.24 | 35.30 | 28.24 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 122 | MWINDOW1 S S1A | Window | M SWALL S1A | Window5 Detailed Fenestration | RESWINDOW_U_0.3097_SHGC_0.45 | N/A | 1.759 | No | 7.06 | 7.06 | 7.06 | 180.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 123 | M NIWALL S1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-M NIWALL S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 124 | M EIWALL S1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | iz-M EIWALL S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 125 | iz-M EIWALL SWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 270.00 | 90.00 | 3.05 | 7.62 | 0.00 | M EIWALL SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 126 | M GFLOOR S1A | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | M GFLOOR S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 127 | M CEILIN S1A | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | M CEILIN S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 128 | M INTERNALMASS S1A | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 176.50 | 176.50 | 176.50 | 0.00 | 90.00 | 176.50 | 1.00 | 0.00 | M INTERNALMASS S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 129 | M SWALL S2A | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.629 | 0.575 | 28.24 | 35.30 | 28.24 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 130 | MWINDOW1 S S2A | Window | M SWALL S2A | Window5 Detailed Fenestration | RESWINDOW_U_0.3097_SHGC_0.45 | N/A | 1.759 | No | 7.06 | 7.06 | 7.06 | 180.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 131 | M NIWALL S2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-M NIWALL S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 132 | M EIWALL S2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | iz-M EIWALL S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 133 | iz-M EIWALL S1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | M EIWALL S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 134 | M GFLOOR S2A | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | M GFLOOR S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 135 | M CEILIN S2A | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | M CEILIN S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 136 | M INTERNALMASS S2A | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 176.50 | 176.50 | 176.50 | 0.00 | 90.00 | 176.50 | 1.00 | 0.00 | M INTERNALMASS S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 137 | T WWALL SWA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 0.955 | 0.835 | 18.58 | 23.22 | 18.58 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 138 | TWINDOW1 W SWA | Window | T WWALL SWA | Window5 Detailed Fenestration | RESWINDOW_U_0.3097_SHGC_0.45 | N/A | 1.759 | No | 4.65 | 4.65 | 4.65 | 270.00 | 90.00 | 3.81 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 139 | T SWALL SWA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 0.955 | 0.835 | 28.24 | 35.30 | 28.24 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 140 | TWINDOW1 S SWA | Window | T SWALL SWA | Window5 Detailed Fenestration | RESWINDOW_U_0.3097_SHGC_0.45 | N/A | 1.759 | No | 7.06 | 7.06 | 7.06 | 180.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 141 | T NIWALL SWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-T NIWALL SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 142 | T EIWALL SWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | iz-T EIWALL SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 143 | T GFLOOR SWA | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | T GFLOOR SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 144 | T ROOF SWA | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.163 | 0.158 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 145 | T INTERNALMASS SWA | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 88.25 | 88.25 | 88.25 | 0.00 | 90.00 | 88.25 | 1.00 | 0.00 | T INTERNALMASS SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 146 | T NWALL NWA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 0.955 | 0.835 | 28.24 | 35.30 | 28.24 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 147 | TWINDOW1 N NWA | Window | T NWALL NWA | Window5 Detailed Fenestration | RESWINDOW_U_0.3097_SHGC_0.45 | N/A | 1.759 | No | 7.06 | 7.06 | 7.06 | 0.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 148 | T WWALL NWA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 0.955 | 0.835 | 18.58 | 23.22 | 18.58 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 149 | TWINDOW1 W NWA | Window | T WWALL NWA | Window5 Detailed Fenestration | RESWINDOW_U_0.3097_SHGC_0.45 | N/A | 1.759 | No | 4.65 | 4.65 | 4.65 | 270.00 | 90.00 | 3.81 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 150 | T SIWALL NWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-T SIWALL NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 151 | T EIWALL NWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | iz-T EIWALL NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 152 | T GFLOOR NWA | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | T GFLOOR NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 153 | T ROOF NWA | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.163 | 0.158 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 154 | T INTERNALMASS NWA | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 88.25 | 88.25 | 88.25 | 0.00 | 90.00 | 88.25 | 1.00 | 0.00 | T INTERNALMASS NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 155 | T EWALL SEA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 0.955 | 0.835 | 18.58 | 23.22 | 18.58 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 156 | TWINDOW1 E SEA | Window | T EWALL SEA | Window5 Detailed Fenestration | RESWINDOW_U_0.3097_SHGC_0.45 | N/A | 1.759 | No | 4.65 | 4.65 | 4.65 | 90.00 | 90.00 | 3.81 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 157 | T SWALL SEA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 0.955 | 0.835 | 28.24 | 35.30 | 28.24 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 158 | TWINDOW1 S SEA | Window | T SWALL SEA | Window5 Detailed Fenestration | RESWINDOW_U_0.3097_SHGC_0.45 | N/A | 1.759 | No | 7.06 | 7.06 | 7.06 | 180.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 159 | T NIWALL SEA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-T NIWALL SEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 160 | iz-T EIWALL S2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | T EIWALL S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 161 | T GFLOOR SEA | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | T GFLOOR SEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 162 | T ROOF SEA | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.163 | 0.158 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 163 | T INTERNALMASS SEA | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 88.25 | 88.25 | 88.25 | 0.00 | 90.00 | 88.25 | 1.00 | 0.00 | T INTERNALMASS SEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 164 | T NWALL NEA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 0.955 | 0.835 | 28.24 | 35.30 | 28.24 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 165 | TWINDOW1 N NEA | Window | T NWALL NEA | Window5 Detailed Fenestration | RESWINDOW_U_0.3097_SHGC_0.45 | N/A | 1.759 | No | 7.06 | 7.06 | 7.06 | 0.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 166 | T EWALL NEA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 0.955 | 0.835 | 18.58 | 23.22 | 18.58 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 167 | TWINDOW1 E NEA | Window | T EWALL NEA | Window5 Detailed Fenestration | RESWINDOW_U_0.3097_SHGC_0.45 | N/A | 1.759 | No | 4.65 | 4.65 | 4.65 | 90.00 | 90.00 | 3.81 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 168 | T SIWALL NEA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-T SIWALL NEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 169 | iz-T EIWALL N2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | T EIWALL N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 170 | T GFLOOR NEA | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | T GFLOOR NEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 171 | T ROOF NEA | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.163 | 0.158 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 172 | T INTERNALMASS NEA | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 88.25 | 88.25 | 88.25 | 0.00 | 90.00 | 88.25 | 1.00 | 0.00 | T INTERNALMASS NEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 173 | T NWALL N1A | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 0.955 | 0.835 | 28.24 | 35.30 | 28.24 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 174 | TWINDOW1 N N1A | Window | T NWALL N1A | Window5 Detailed Fenestration | RESWINDOW_U_0.3097_SHGC_0.45 | N/A | 1.759 | No | 7.06 | 7.06 | 7.06 | 0.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 175 | T SIWALL N1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-T SIWALL N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 176 | T EIWALL N1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | iz-T EIWALL N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 177 | iz-T EIWALL NWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | T EIWALL NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 178 | T GFLOOR N1A | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | T GFLOOR N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 179 | T ROOF N1A | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.163 | 0.158 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 180 | T INTERNALMASS N1A | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 88.25 | 88.25 | 88.25 | 0.00 | 90.00 | 88.25 | 1.00 | 0.00 | T INTERNALMASS N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 181 | T NWALL N2A | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 0.955 | 0.835 | 28.24 | 35.30 | 28.24 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 182 | TWINDOW1 N N2A | Window | T NWALL N2A | Window5 Detailed Fenestration | RESWINDOW_U_0.3097_SHGC_0.45 | N/A | 1.759 | No | 7.06 | 7.06 | 7.06 | 0.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 183 | T SIWALL N2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-T SIWALL N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 184 | T EIWALL N2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | iz-T EIWALL N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 185 | iz-T EIWALL N1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | T EIWALL N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 186 | T GFLOOR N2A | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | T GFLOOR N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 187 | T ROOF N2A | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.163 | 0.158 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 188 | T INTERNALMASS N2A | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 88.25 | 88.25 | 88.25 | 0.00 | 90.00 | 88.25 | 1.00 | 0.00 | T INTERNALMASS N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 189 | T SWALL S1A | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 0.955 | 0.835 | 28.24 | 35.30 | 28.24 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 190 | TWINDOW1 S S1A | Window | T SWALL S1A | Window5 Detailed Fenestration | RESWINDOW_U_0.3097_SHGC_0.45 | N/A | 1.759 | No | 7.06 | 7.06 | 7.06 | 180.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 191 | T NIWALL S1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-T NIWALL S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 192 | T EIWALL S1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | iz-T EIWALL S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 193 | iz-T EIWALL SWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | T EIWALL SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 194 | T GFLOOR S1A | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | T GFLOOR S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 195 | T ROOF S1A | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.163 | 0.158 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 196 | T INTERNALMASS S1A | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 88.25 | 88.25 | 88.25 | 0.00 | 90.00 | 88.25 | 1.00 | 0.00 | T INTERNALMASS S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 197 | T SWALL S2A | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 0.955 | 0.835 | 28.24 | 35.30 | 28.24 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 198 | TWINDOW1 S S2A | Window | T SWALL S2A | Window5 Detailed Fenestration | RESWINDOW_U_0.3097_SHGC_0.45 | N/A | 1.759 | No | 7.06 | 7.06 | 7.06 | 180.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 199 | T NIWALL S2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-T NIWALL S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 200 | T EIWALL S2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | iz-T EIWALL S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 201 | iz-T EIWALL S1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | T EIWALL S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 202 | T GFLOOR S2A | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | T GFLOOR S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 203 | T ROOF S2A | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.163 | 0.158 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 204 | T INTERNALMASS S2A | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 88.25 | 88.25 | 88.25 | 0.00 | 90.00 | 88.25 | 1.00 | 0.00 | T INTERNALMASS S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 205 | T WWALL C | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.955 | 0.835 | 5.11 | 5.11 | 5.11 | 270.00 | 90.00 | 1.68 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 206 | T EWALL C | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.955 | 0.835 | 3.99 | 5.11 | 3.99 | 90.00 | 90.00 | 1.68 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 207 | TWINDOW14 | Window | T EWALL C | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3097_SHGC_0.45 | N/A | 1.759 | No | 1.11 | 1.11 | 1.11 | 90.00 | 90.00 | 0.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 208 | iz-T NIWALL SWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | T NIWALL SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 209 | iz-T NIWALL S1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | T NIWALL S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 210 | iz-T NIWALL S2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | T NIWALL S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 211 | iz-T NIWALL SEA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | T NIWALL SEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 212 | iz-T SIWALL NWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | T SIWALL NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 213 | iz-T SIWALL N1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | T SIWALL N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 214 | iz-T SIWALL N2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | T SIWALL N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 215 | iz-T SIWALL NEA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | T SIWALL NEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 216 | T FLOOR C | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 77.66 | 77.66 | 77.66 | 90.00 | 180.00 | 1.68 | 46.33 | 0.00 | T FLOOR C | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 217 | T ROOF C | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.163 | 0.158 | 77.66 | 77.66 | 77.66 | 180.00 | 0.00 | 46.33 | 1.68 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 218 | G WWALL C | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.621 | 0.568 | 5.11 | 5.11 | 5.11 | 270.00 | 90.00 | 1.68 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 219 | G EWALL C | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.621 | 0.568 | 1.79 | 5.11 | 1.79 | 90.00 | 90.00 | 1.68 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 220 | ENTRANCE DOOR | Window | G EWALL C | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3097_SHGC_0.45 | N/A | 1.759 | No | 3.32 | 3.32 | 3.32 | 90.00 | 90.00 | 1.57 | 2.11 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 221 | iz-G NIWALL SWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | G NIWALL SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 222 | iz-G NIWALL S1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | G NIWALL S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 223 | iz-G NIWALL S2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | G NIWALL S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 224 | iz-G NIWALL SEA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | G NIWALL SEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 225 | iz-G SIWALL NWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | G SIWALL NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 226 | iz-G SIWALL N1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | G SIWALL N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 227 | iz-G SIWALL N2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | G SIWALL N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 228 | iz-G SIWALL NEA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | G SIWALL NEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 229 | G FLOOR C | Floor | CTF - ConductionTransferFunction | GFLOORC_FFACTOR | 3.003E-002 | 2.981E-002 | 77.66 | 77.66 | 77.66 | 90.00 | 180.00 | 1.68 | 46.33 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 230 | G CEILING C | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 77.66 | 77.66 | 77.66 | 180.00 | 0.00 | 46.33 | 1.68 | 0.00 | G CEILING C | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 231 | M WWALL C | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.629 | 0.575 | 5.11 | 5.11 | 5.11 | 270.00 | 90.00 | 1.68 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 232 | M EWALL C | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.629 | 0.575 | 3.99 | 5.11 | 3.99 | 90.00 | 90.00 | 1.68 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 233 | MWINDOW14 | Window | M EWALL C | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3097_SHGC_0.45 | N/A | 1.759 | No | 1.11 | 1.11 | 1.11 | 90.00 | 90.00 | 0.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 234 | iz-M NIWALL SWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | M NIWALL SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 235 | iz-M NIWALL S1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | M NIWALL S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 236 | iz-M NIWALL S2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | M NIWALL S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 237 | iz-M NIWALL SEA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | M NIWALL SEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 238 | iz-M SIWALL NWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | M SIWALL NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 239 | iz-M SIWALL N1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | M SIWALL N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 240 | iz-M SIWALL N2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | M SIWALL N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 241 | iz-M SIWALL NEA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | M SIWALL NEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 242 | M FLOOR C | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 77.66 | 77.66 | 77.66 | 90.00 | 180.00 | 1.68 | 46.33 | 0.00 | M FLOOR C | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 243 | M CEILING C | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 77.66 | 77.66 | 77.66 | 180.00 | 0.00 | 46.33 | 1.68 | 0.00 | M CEILING C | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
| Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
| 1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | Yes | Yes | Yes | Clark and Allen |
| Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
| 1 | NEW YEAR'S DAY | Holiday | InputFile | 01/02 | 1Environment:Special Days |
| Daylight Saving Indicator | Source | Start Date | End Date | |
| 1 | Yes | InputFile | 03/12 | 11/05 |
| Style | Unit Conversion | |
| 1 | Commaandhtml | commaandhtml |
| Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
| 1 | G SW APARTMENT | RunPeriod: RUNPERIOD 1 | 2.4074034808E-007 | 9.3596129770E-007 | Pass | Pass | 1.0135236544E-002 | 7.6755733975E-003 | Pass | Pass |
| 2 | G NW APARTMENT | RunPeriod: RUNPERIOD 1 | 4.0365694883E-007 | 1.4984575981E-006 | Pass | Pass | 9.6247468790E-003 | 7.4255635851E-003 | Pass | Pass |
| 3 | OFFICE | RunPeriod: RUNPERIOD 1 | 9.4039888629E-008 | 3.3871713696E-007 | Pass | Pass | 1.2944753504E-002 | 1.0053830038E-002 | Pass | Pass |
| 4 | G NE APARTMENT | RunPeriod: RUNPERIOD 1 | 4.0572263665E-007 | 1.5060127608E-006 | Pass | Pass | 9.7102656922E-003 | 7.4542784078E-003 | Pass | Pass |
| 5 | G N1 APARTMENT | RunPeriod: RUNPERIOD 1 | 2.4502995208E-007 | 9.3046111295E-007 | Pass | Pass | 1.1851738073E-002 | 1.1064681576E-002 | Pass | Pass |
| 6 | G N2 APARTMENT | RunPeriod: RUNPERIOD 1 | 2.4505647849E-007 | 9.3056246236E-007 | Pass | Pass | 1.1850133886E-002 | 1.1064826474E-002 | Pass | Pass |
| 7 | G S1 APARTMENT | RunPeriod: RUNPERIOD 1 | 1.4116009102E-007 | 5.6307226729E-007 | Pass | Pass | 1.2862699581E-002 | 1.1760113931E-002 | Pass | Pass |
| 8 | G S2 APARTMENT | RunPeriod: RUNPERIOD 1 | 1.6727343774E-007 | 6.6989523376E-007 | Pass | Pass | 1.0638517690E-002 | 9.7053203220E-003 | Pass | Pass |
| 9 | M SW APARTMENT | RunPeriod: RUNPERIOD 1 | 1.7052560581E-007 | 6.3972721968E-007 | Pass | Pass | 1.8346691041E-002 | 1.5503519853E-002 | Pass | Pass |
| 10 | M NW APARTMENT | RunPeriod: RUNPERIOD 1 | 2.8506290363E-007 | 1.0388927106E-006 | Pass | Pass | 1.7151756341E-002 | 1.4717333287E-002 | Pass | Pass |
| 11 | M SE APARTMENT | RunPeriod: RUNPERIOD 1 | 1.7164966991E-007 | 6.4391126154E-007 | Pass | Pass | 1.8547998788E-002 | 1.5662127006E-002 | Pass | Pass |
| 12 | M NE APARTMENT | RunPeriod: RUNPERIOD 1 | 2.8697390049E-007 | 1.0458870563E-006 | Pass | Pass | 1.7245919684E-002 | 1.4793469901E-002 | Pass | Pass |
| 13 | M N1 APARTMENT | RunPeriod: RUNPERIOD 1 | 1.2271875437E-007 | 4.6035214134E-007 | Pass | Pass | 2.6957411144E-002 | 2.5340223136E-002 | Pass | Pass |
| 14 | M N2 APARTMENT | RunPeriod: RUNPERIOD 1 | 1.2274456301E-007 | 4.6045157051E-007 | Pass | Pass | 2.6951292591E-002 | 2.5336611972E-002 | Pass | Pass |
| 15 | M S1 APARTMENT | RunPeriod: RUNPERIOD 1 | 6.5966983777E-008 | 2.4570080637E-007 | Pass | Pass | 3.1524955197E-002 | 2.9973422865E-002 | Pass | Pass |
| 16 | M S2 APARTMENT | RunPeriod: RUNPERIOD 1 | 6.5982333992E-008 | 2.4575896037E-007 | Pass | Pass | 3.1518760677E-002 | 2.9967294077E-002 | Pass | Pass |
| 17 | T SW APARTMENT | RunPeriod: RUNPERIOD 1 | 3.2848512416E-007 | 1.2378643307E-006 | Pass | Pass | 1.1851057255E-002 | 9.5185029325E-003 | Pass | Pass |
| 18 | T NW APARTMENT | RunPeriod: RUNPERIOD 1 | 5.3192516305E-007 | 1.9229973560E-006 | Pass | Pass | 1.1300035716E-002 | 9.3188623872E-003 | Pass | Pass |
| 19 | T SE APARTMENT | RunPeriod: RUNPERIOD 1 | 3.3119665146E-007 | 1.2481181959E-006 | Pass | Pass | 1.1990375303E-002 | 9.5950141347E-003 | Pass | Pass |
| 20 | T NE APARTMENT | RunPeriod: RUNPERIOD 1 | 5.3651819039E-007 | 1.9397547383E-006 | Pass | Pass | 1.1356102976E-002 | 9.3601699543E-003 | Pass | Pass |
| 21 | T N1 APARTMENT | RunPeriod: RUNPERIOD 1 | 3.3293996681E-007 | 1.2311720413E-006 | Pass | Pass | 1.1542279628E-002 | 9.9062033275E-003 | Pass | Pass |
| 22 | T N2 APARTMENT | RunPeriod: RUNPERIOD 1 | 3.3303171445E-007 | 1.2315123900E-006 | Pass | Pass | 1.1540142284E-002 | 9.9052262853E-003 | Pass | Pass |
| 23 | T S1 APARTMENT | RunPeriod: RUNPERIOD 1 | 1.9738420962E-007 | 7.5128984612E-007 | Pass | Pass | 1.2497391444E-002 | 1.0626086844E-002 | Pass | Pass |
| 24 | T S2 APARTMENT | RunPeriod: RUNPERIOD 1 | 1.9743593977E-007 | 7.5148263394E-007 | Pass | Pass | 1.2495919475E-002 | 1.0624992319E-002 | Pass | Pass |
| 25 | T CORRIDOR | RunPeriod: RUNPERIOD 1 | 8.7510333298E-003 | 5.8117791346E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
| 26 | G CORRIDOR | RunPeriod: RUNPERIOD 1 | 0.3244550745 | 1.1253387704 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
| 27 | M CORRIDOR | RunPeriod: RUNPERIOD 1 | 7.9841770764E-003 | 5.7884211061E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 09:14:30
Heat Emission by Components| Envelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
| Heat Emissions [GJ] | 1329.87 | 179.69 | 0.00 | 32.06 | 466.33 | 2007.95 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 09:14:30
SizingPeriod:DesignDay| Maximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
| FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | -41.90 | 0.00 | -41.90 | Wetbulb [C] | 0.30 | 20.00 |
| FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 27.40 | 10.20 | 16.10 | Wetbulb [C] | 3.10 | 180.00 |
| Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
| Jan | 0.00 | 0 | |||
| Feb | 0.00 | 0 | |||
| Mar | 0.00 | 0 | |||
| Apr | 0.00 | 0 | |||
| May | 0.00 | 0 | |||
| Jun | 0.00 | 0 | |||
| Jul | 0.00 | 0 | |||
| Aug | 0.00 | 0 | |||
| Sep | 0.00 | 0 | |||
| Oct | 0.00 | 0 | |||
| Nov | 0.00 | 0 | |||
| Dec | 0.00 | 0 |
| Value | |
| None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 09:14:30
Opaque Exterior| Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
| G SWALL SWA | RES_EXT_WALL_GRD | 0.30 | 0.568 | 0.621 | 35.30 | 28.24 | 180.00 | 90.00 | S |
| G WWALL SWA | RES_EXT_WALL_GRD | 0.30 | 0.568 | 0.621 | 23.22 | 18.58 | 270.00 | 90.00 | W |
| G GFLOOR SWA | GGFLOORSWA_FFACTOR | 1.00 | 0.150 | 0.154 | 88.25 | 88.25 | 90.00 | 180.00 | |
| G NWALL NWA | RES_EXT_WALL_GRD | 0.30 | 0.568 | 0.621 | 35.30 | 28.24 | 0.00 | 90.00 | N |
| G WWALL NWA | RES_EXT_WALL_GRD | 0.30 | 0.568 | 0.621 | 23.22 | 18.58 | 270.00 | 90.00 | W |
| G GFLOOR NWA | GGFLOORNWA_FFACTOR | 1.00 | 0.150 | 0.154 | 88.25 | 88.25 | 90.00 | 180.00 | |
| G SWALL SEA | NONRES_EXT_WALL_GRD | 0.30 | 0.568 | 0.621 | 35.30 | 28.24 | 180.00 | 90.00 | S |
| G EWALL SEA | NONRES_EXT_WALL_GRD | 0.30 | 0.568 | 0.621 | 23.22 | 18.58 | 90.00 | 90.00 | E |
| G GFLOOR SEA | GGFLOORSEA_FFACTOR | 1.00 | 0.150 | 0.154 | 88.25 | 88.25 | 90.00 | 180.00 | |
| G NWALL NEA | RES_EXT_WALL_GRD | 0.30 | 0.568 | 0.621 | 35.30 | 28.24 | 0.00 | 90.00 | N |
| G EWALL NEA | RES_EXT_WALL_GRD | 0.30 | 0.568 | 0.621 | 23.22 | 18.58 | 90.00 | 90.00 | E |
| G GFLOOR NEA | GGFLOORNEA_FFACTOR | 1.00 | 0.150 | 0.154 | 88.25 | 88.25 | 90.00 | 180.00 | |
| G NWALL N1A | RES_EXT_WALL_GRD | 0.30 | 0.568 | 0.621 | 35.30 | 28.24 | 0.00 | 90.00 | N |
| G GFLOOR N1A | GGFLOORN1A_FFACTOR | 1.00 | 0.091 | 0.092 | 88.25 | 88.25 | 90.00 | 180.00 | |
| G NWALL N2A | RES_EXT_WALL_GRD | 0.30 | 0.568 | 0.621 | 35.30 | 28.24 | 0.00 | 90.00 | N |
| G GFLOOR N2A | GGFLOORN2A_FFACTOR | 1.00 | 0.091 | 0.092 | 88.25 | 88.25 | 90.00 | 180.00 | |
| G SWALL S1A | RES_EXT_WALL_GRD | 0.30 | 0.568 | 0.621 | 35.30 | 28.24 | 180.00 | 90.00 | S |
| G GFLOOR S1A | GGFLOORS1A_FFACTOR | 1.00 | 0.091 | 0.092 | 88.25 | 88.25 | 90.00 | 180.00 | |
| G SWALL S2A | RES_EXT_WALL_GRD | 0.30 | 0.568 | 0.621 | 35.30 | 28.24 | 180.00 | 90.00 | S |
| G GFLOOR S2A | GGFLOORS2A_FFACTOR | 1.00 | 0.091 | 0.092 | 88.25 | 88.25 | 90.00 | 180.00 | |
| M WWALL SWA | RES_EXT_WALL_MID | 0.30 | 0.575 | 0.629 | 46.45 | 37.16 | 270.00 | 90.00 | W |
| M SWALL SWA | RES_EXT_WALL_MID | 0.30 | 0.575 | 0.629 | 70.60 | 56.48 | 180.00 | 90.00 | S |
| M NWALL NWA | RES_EXT_WALL_MID | 0.30 | 0.575 | 0.629 | 70.60 | 56.48 | 0.00 | 90.00 | N |
| M WWALL NWA | RES_EXT_WALL_MID | 0.30 | 0.575 | 0.629 | 46.45 | 37.16 | 270.00 | 90.00 | W |
| M EWALL SEA | RES_EXT_WALL_MID | 0.30 | 0.575 | 0.629 | 46.45 | 37.16 | 90.00 | 90.00 | E |
| M SWALL SEA | RES_EXT_WALL_MID | 0.30 | 0.575 | 0.629 | 70.60 | 56.48 | 180.00 | 90.00 | S |
| M NWALL NEA | RES_EXT_WALL_MID | 0.30 | 0.575 | 0.629 | 70.60 | 56.48 | 0.00 | 90.00 | N |
| M EWALL NEA | RES_EXT_WALL_MID | 0.30 | 0.575 | 0.629 | 46.45 | 37.16 | 90.00 | 90.00 | E |
| M NWALL N1A | RES_EXT_WALL_MID | 0.30 | 0.575 | 0.629 | 70.60 | 56.48 | 0.00 | 90.00 | N |
| M NWALL N2A | RES_EXT_WALL_MID | 0.30 | 0.575 | 0.629 | 70.60 | 56.48 | 0.00 | 90.00 | N |
| M SWALL S1A | RES_EXT_WALL_MID | 0.30 | 0.575 | 0.629 | 70.60 | 56.48 | 180.00 | 90.00 | S |
| M SWALL S2A | RES_EXT_WALL_MID | 0.30 | 0.575 | 0.629 | 70.60 | 56.48 | 180.00 | 90.00 | S |
| T WWALL SWA | RES_EXT_WALL_TOP | 0.30 | 0.835 | 0.955 | 23.22 | 18.58 | 270.00 | 90.00 | W |
| T SWALL SWA | RES_EXT_WALL_TOP | 0.30 | 0.835 | 0.955 | 35.30 | 28.24 | 180.00 | 90.00 | S |
| T ROOF SWA | RES_ROOF | 0.30 | 0.159 | 0.163 | 88.25 | 88.25 | 180.00 | 0.00 | |
| T NWALL NWA | RES_EXT_WALL_TOP | 0.30 | 0.835 | 0.955 | 35.30 | 28.24 | 0.00 | 90.00 | N |
| T WWALL NWA | RES_EXT_WALL_TOP | 0.30 | 0.835 | 0.955 | 23.22 | 18.58 | 270.00 | 90.00 | W |
| T ROOF NWA | RES_ROOF | 0.30 | 0.159 | 0.163 | 88.25 | 88.25 | 180.00 | 0.00 | |
| T EWALL SEA | RES_EXT_WALL_TOP | 0.30 | 0.835 | 0.955 | 23.22 | 18.58 | 90.00 | 90.00 | E |
| T SWALL SEA | RES_EXT_WALL_TOP | 0.30 | 0.835 | 0.955 | 35.30 | 28.24 | 180.00 | 90.00 | S |
| T ROOF SEA | RES_ROOF | 0.30 | 0.159 | 0.163 | 88.25 | 88.25 | 180.00 | 0.00 | |
| T NWALL NEA | RES_EXT_WALL_TOP | 0.30 | 0.835 | 0.955 | 35.30 | 28.24 | 0.00 | 90.00 | N |
| T EWALL NEA | RES_EXT_WALL_TOP | 0.30 | 0.835 | 0.955 | 23.22 | 18.58 | 90.00 | 90.00 | E |
| T ROOF NEA | RES_ROOF | 0.30 | 0.159 | 0.163 | 88.25 | 88.25 | 180.00 | 0.00 | |
| T NWALL N1A | RES_EXT_WALL_TOP | 0.30 | 0.835 | 0.955 | 35.30 | 28.24 | 0.00 | 90.00 | N |
| T ROOF N1A | RES_ROOF | 0.30 | 0.159 | 0.163 | 88.25 | 88.25 | 180.00 | 0.00 | |
| T NWALL N2A | RES_EXT_WALL_TOP | 0.30 | 0.835 | 0.955 | 35.30 | 28.24 | 0.00 | 90.00 | N |
| T ROOF N2A | RES_ROOF | 0.30 | 0.159 | 0.163 | 88.25 | 88.25 | 180.00 | 0.00 | |
| T SWALL S1A | RES_EXT_WALL_TOP | 0.30 | 0.835 | 0.955 | 35.30 | 28.24 | 180.00 | 90.00 | S |
| T ROOF S1A | RES_ROOF | 0.30 | 0.159 | 0.163 | 88.25 | 88.25 | 180.00 | 0.00 | |
| T SWALL S2A | RES_EXT_WALL_TOP | 0.30 | 0.835 | 0.955 | 35.30 | 28.24 | 180.00 | 90.00 | S |
| T ROOF S2A | RES_ROOF | 0.30 | 0.159 | 0.163 | 88.25 | 88.25 | 180.00 | 0.00 | |
| T WWALL C | NONRES_EXT_WALL_TOP | 0.30 | 0.835 | 0.955 | 5.11 | 5.11 | 270.00 | 90.00 | W |
| T EWALL C | NONRES_EXT_WALL_TOP | 0.30 | 0.835 | 0.955 | 5.11 | 3.99 | 90.00 | 90.00 | E |
| T ROOF C | NONRES_ROOF | 0.30 | 0.159 | 0.163 | 77.66 | 77.66 | 180.00 | 0.00 | |
| G WWALL C | NONRES_EXT_WALL_GRD | 0.30 | 0.568 | 0.621 | 5.11 | 5.11 | 270.00 | 90.00 | W |
| G EWALL C | NONRES_EXT_WALL_GRD | 0.30 | 0.568 | 0.621 | 5.11 | 1.79 | 90.00 | 90.00 | E |
| G FLOOR C | GFLOORC_FFACTOR | 1.00 | 0.030 | 0.030 | 77.66 | 77.66 | 90.00 | 180.00 | |
| M WWALL C | NONRES_EXT_WALL_MID | 0.30 | 0.575 | 0.629 | 10.22 | 10.22 | 270.00 | 90.00 | W |
| M EWALL C | NONRES_EXT_WALL_MID | 0.30 | 0.575 | 0.629 | 10.22 | 7.99 | 90.00 | 90.00 | E |
| Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
| G NIWALL SWA | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 0.00 | 90.00 | N |
| G EIWALL SWA | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 90.00 | 90.00 | E |
| G CEILIN SWA | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 88.25 | 88.25 | 180.00 | 0.00 | |
| G SIWALL NWA | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 180.00 | 90.00 | S |
| G EIWALL NWA | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 90.00 | 90.00 | E |
| G CEILIN NWA | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 88.25 | 88.25 | 180.00 | 0.00 | |
| G NIWALL SEA | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 0.00 | 90.00 | N |
| iz-G EIWALL S2A | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 270.00 | 90.00 | W |
| G CEILIN SEA | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 88.25 | 88.25 | 180.00 | 0.00 | |
| G SIWALL NEA | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 180.00 | 90.00 | S |
| iz-G EIWALL N2A | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 270.00 | 90.00 | W |
| G CEILIN NEA | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 88.25 | 88.25 | 180.00 | 0.00 | |
| G SIWALL N1A | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 180.00 | 90.00 | S |
| G EIWALL N1A | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 90.00 | 90.00 | E |
| iz-G EIWALL NWA | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 270.00 | 90.00 | W |
| G CEILIN N1A | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 88.25 | 88.25 | 180.00 | 0.00 | |
| G SIWALL N2A | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 180.00 | 90.00 | S |
| G EIWALL N2A | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 90.00 | 90.00 | E |
| iz-G EIWALL N1A | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 270.00 | 90.00 | W |
| G CEILIN N2A | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 88.25 | 88.25 | 180.00 | 0.00 | |
| G NIWALL S1A | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 0.00 | 90.00 | N |
| G EIWALL S1A | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 90.00 | 90.00 | E |
| iz-G EIWALL SWA | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 270.00 | 90.00 | W |
| G CEILIN S1A | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 88.25 | 88.25 | 180.00 | 0.00 | |
| G NIWALL S2A | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 0.00 | 90.00 | N |
| G EIWALL S2A | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 90.00 | 90.00 | E |
| iz-G EIWALL S1A | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 270.00 | 90.00 | W |
| G CEILIN S2A | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 88.25 | 88.25 | 180.00 | 0.00 | |
| M NIWALL SWA | INT_WALL | 0.30 | 2.511 | 6.299 | 70.60 | 70.60 | 0.00 | 90.00 | N |
| M EIWALL SWA | INT_WALL | 0.30 | 2.511 | 6.299 | 46.45 | 46.45 | 90.00 | 90.00 | E |
| M GFLOOR SWA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 176.50 | 176.50 | 90.00 | 180.00 | |
| M CEILIN SWA | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 176.50 | 176.50 | 180.00 | 0.00 | |
| M SIWALL NWA | INT_WALL | 0.30 | 2.511 | 6.299 | 70.60 | 70.60 | 180.00 | 90.00 | S |
| M EIWALL NWA | INT_WALL | 0.30 | 2.511 | 6.299 | 46.45 | 46.45 | 90.00 | 90.00 | E |
| M GFLOOR NWA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 176.50 | 176.50 | 90.00 | 180.00 | |
| M CEILIN NWA | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 176.50 | 176.50 | 180.00 | 0.00 | |
| M NIWALL SEA | INT_WALL | 0.30 | 2.511 | 6.299 | 70.60 | 70.60 | 0.00 | 90.00 | N |
| iz-M EIWALL S2A | INT_WALL | 0.30 | 2.511 | 6.299 | 46.45 | 46.45 | 270.00 | 90.00 | W |
| M GFLOOR SEA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 176.50 | 176.50 | 90.00 | 180.00 | |
| M CEILIN SEA | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 176.50 | 176.50 | 180.00 | 0.00 | |
| M SIWALL NEA | INT_WALL | 0.30 | 2.511 | 6.299 | 70.60 | 70.60 | 180.00 | 90.00 | S |
| iz-M EIWALL N2A | INT_WALL | 0.30 | 2.511 | 6.299 | 46.45 | 46.45 | 270.00 | 90.00 | W |
| M GFLOOR NEA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 176.50 | 176.50 | 90.00 | 180.00 | |
| M CEILIN NEA | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 176.50 | 176.50 | 180.00 | 0.00 | |
| M SIWALL N1A | INT_WALL | 0.30 | 2.511 | 6.299 | 70.60 | 70.60 | 180.00 | 90.00 | S |
| M EIWALL N1A | INT_WALL | 0.30 | 2.511 | 6.299 | 46.45 | 46.45 | 90.00 | 90.00 | E |
| iz-M EIWALL NWA | INT_WALL | 0.30 | 2.511 | 6.299 | 46.45 | 46.45 | 270.00 | 90.00 | W |
| M GFLOOR N1A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 176.50 | 176.50 | 90.00 | 180.00 | |
| M CEILIN N1A | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 176.50 | 176.50 | 180.00 | 0.00 | |
| M SIWALL N2A | INT_WALL | 0.30 | 2.511 | 6.299 | 70.60 | 70.60 | 180.00 | 90.00 | S |
| M EIWALL N2A | INT_WALL | 0.30 | 2.511 | 6.299 | 46.45 | 46.45 | 90.00 | 90.00 | E |
| iz-M EIWALL N1A | INT_WALL | 0.30 | 2.511 | 6.299 | 46.45 | 46.45 | 270.00 | 90.00 | W |
| M GFLOOR N2A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 176.50 | 176.50 | 90.00 | 180.00 | |
| M CEILIN N2A | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 176.50 | 176.50 | 180.00 | 0.00 | |
| M NIWALL S1A | INT_WALL | 0.30 | 2.511 | 6.299 | 70.60 | 70.60 | 0.00 | 90.00 | N |
| M EIWALL S1A | INT_WALL | 0.30 | 2.511 | 6.299 | 46.45 | 46.45 | 90.00 | 90.00 | E |
| iz-M EIWALL SWA | INT_WALL | 0.30 | 2.511 | 6.299 | 46.45 | 46.45 | 270.00 | 90.00 | W |
| M GFLOOR S1A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 176.50 | 176.50 | 90.00 | 180.00 | |
| M CEILIN S1A | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 176.50 | 176.50 | 180.00 | 0.00 | |
| M NIWALL S2A | INT_WALL | 0.30 | 2.511 | 6.299 | 70.60 | 70.60 | 0.00 | 90.00 | N |
| M EIWALL S2A | INT_WALL | 0.30 | 2.511 | 6.299 | 46.45 | 46.45 | 90.00 | 90.00 | E |
| iz-M EIWALL S1A | INT_WALL | 0.30 | 2.511 | 6.299 | 46.45 | 46.45 | 270.00 | 90.00 | W |
| M GFLOOR S2A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 176.50 | 176.50 | 90.00 | 180.00 | |
| M CEILIN S2A | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 176.50 | 176.50 | 180.00 | 0.00 | |
| T NIWALL SWA | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 0.00 | 90.00 | N |
| T EIWALL SWA | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 90.00 | 90.00 | E |
| T GFLOOR SWA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 88.25 | 88.25 | 90.00 | 180.00 | |
| T SIWALL NWA | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 180.00 | 90.00 | S |
| T EIWALL NWA | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 90.00 | 90.00 | E |
| T GFLOOR NWA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 88.25 | 88.25 | 90.00 | 180.00 | |
| T NIWALL SEA | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 0.00 | 90.00 | N |
| iz-T EIWALL S2A | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 270.00 | 90.00 | W |
| T GFLOOR SEA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 88.25 | 88.25 | 90.00 | 180.00 | |
| T SIWALL NEA | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 180.00 | 90.00 | S |
| iz-T EIWALL N2A | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 270.00 | 90.00 | W |
| T GFLOOR NEA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 88.25 | 88.25 | 90.00 | 180.00 | |
| T SIWALL N1A | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 180.00 | 90.00 | S |
| T EIWALL N1A | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 90.00 | 90.00 | E |
| iz-T EIWALL NWA | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 270.00 | 90.00 | W |
| T GFLOOR N1A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 88.25 | 88.25 | 90.00 | 180.00 | |
| T SIWALL N2A | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 180.00 | 90.00 | S |
| T EIWALL N2A | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 90.00 | 90.00 | E |
| iz-T EIWALL N1A | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 270.00 | 90.00 | W |
| T GFLOOR N2A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 88.25 | 88.25 | 90.00 | 180.00 | |
| T NIWALL S1A | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 0.00 | 90.00 | N |
| T EIWALL S1A | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 90.00 | 90.00 | E |
| iz-T EIWALL SWA | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 270.00 | 90.00 | W |
| T GFLOOR S1A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 88.25 | 88.25 | 90.00 | 180.00 | |
| T NIWALL S2A | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 0.00 | 90.00 | N |
| T EIWALL S2A | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 90.00 | 90.00 | E |
| iz-T EIWALL S1A | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 270.00 | 90.00 | W |
| T GFLOOR S2A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 88.25 | 88.25 | 90.00 | 180.00 | |
| iz-T NIWALL SWA | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 180.00 | 90.00 | S |
| iz-T NIWALL S1A | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 180.00 | 90.00 | S |
| iz-T NIWALL S2A | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 180.00 | 90.00 | S |
| iz-T NIWALL SEA | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 180.00 | 90.00 | S |
| iz-T SIWALL NWA | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 0.00 | 90.00 | N |
| iz-T SIWALL N1A | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 0.00 | 90.00 | N |
| iz-T SIWALL N2A | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 0.00 | 90.00 | N |
| iz-T SIWALL NEA | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 0.00 | 90.00 | N |
| T FLOOR C | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 77.66 | 77.66 | 90.00 | 180.00 | |
| iz-G NIWALL SWA | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 180.00 | 90.00 | S |
| iz-G NIWALL S1A | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 180.00 | 90.00 | S |
| iz-G NIWALL S2A | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 180.00 | 90.00 | S |
| iz-G NIWALL SEA | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 180.00 | 90.00 | S |
| iz-G SIWALL NWA | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 0.00 | 90.00 | N |
| iz-G SIWALL N1A | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 0.00 | 90.00 | N |
| iz-G SIWALL N2A | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 0.00 | 90.00 | N |
| iz-G SIWALL NEA | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 0.00 | 90.00 | N |
| G CEILING C | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 77.66 | 77.66 | 180.00 | 0.00 | |
| iz-M NIWALL SWA | INT_WALL | 0.30 | 2.511 | 6.299 | 70.60 | 70.60 | 180.00 | 90.00 | S |
| iz-M NIWALL S1A | INT_WALL | 0.30 | 2.511 | 6.299 | 70.60 | 70.60 | 180.00 | 90.00 | S |
| iz-M NIWALL S2A | INT_WALL | 0.30 | 2.511 | 6.299 | 70.60 | 70.60 | 180.00 | 90.00 | S |
| iz-M NIWALL SEA | INT_WALL | 0.30 | 2.511 | 6.299 | 70.60 | 70.60 | 180.00 | 90.00 | S |
| iz-M SIWALL NWA | INT_WALL | 0.30 | 2.511 | 6.299 | 70.60 | 70.60 | 0.00 | 90.00 | N |
| iz-M SIWALL N1A | INT_WALL | 0.30 | 2.511 | 6.299 | 70.60 | 70.60 | 0.00 | 90.00 | N |
| iz-M SIWALL N2A | INT_WALL | 0.30 | 2.511 | 6.299 | 70.60 | 70.60 | 0.00 | 90.00 | N |
| iz-M SIWALL NEA | INT_WALL | 0.30 | 2.511 | 6.299 | 70.60 | 70.60 | 0.00 | 90.00 | N |
| M FLOOR C | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 155.32 | 155.32 | 90.00 | 180.00 | |
| M CEILING C | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 155.32 | 155.32 | 180.00 | 0.00 | |
| G INTERNALMASS SWA | INTERIORFURNISHINGS | 0.30 | 0.800 | 88.25 | 0.00 | 90.00 | N | ||
| G INTERNALMASS NWA | INTERIORFURNISHINGS | 0.30 | 0.800 | 88.25 | 0.00 | 90.00 | N | ||
| G INTERNALMASS SEA | INTERIORFURNISHINGS | 0.30 | 0.800 | 88.25 | 0.00 | 90.00 | N | ||
| G INTERNALMASS NEA | INTERIORFURNISHINGS | 0.30 | 0.800 | 88.25 | 0.00 | 90.00 | N | ||
| G INTERNALMASS N1A | INTERIORFURNISHINGS | 0.30 | 0.800 | 88.25 | 0.00 | 90.00 | N | ||
| G INTERNALMASS N2A | INTERIORFURNISHINGS | 0.30 | 0.800 | 88.25 | 0.00 | 90.00 | N | ||
| G INTERNALMASS S1A | INTERIORFURNISHINGS | 0.30 | 0.800 | 88.25 | 0.00 | 90.00 | N | ||
| G INTERNALMASS S2A | INTERIORFURNISHINGS | 0.30 | 0.800 | 88.25 | 0.00 | 90.00 | N | ||
| M INTERNALMASS SWA | INTERIORFURNISHINGS | 0.30 | 0.800 | 353.00 | 0.00 | 90.00 | N | ||
| M INTERNALMASS NWA | INTERIORFURNISHINGS | 0.30 | 0.800 | 353.00 | 0.00 | 90.00 | N | ||
| M INTERNALMASS SEA | INTERIORFURNISHINGS | 0.30 | 0.800 | 353.00 | 0.00 | 90.00 | N | ||
| M INTERNALMASS NEA | INTERIORFURNISHINGS | 0.30 | 0.800 | 353.00 | 0.00 | 90.00 | N | ||
| M INTERNALMASS N1A | INTERIORFURNISHINGS | 0.30 | 0.800 | 353.00 | 0.00 | 90.00 | N | ||
| M INTERNALMASS N2A | INTERIORFURNISHINGS | 0.30 | 0.800 | 353.00 | 0.00 | 90.00 | N | ||
| M INTERNALMASS S1A | INTERIORFURNISHINGS | 0.30 | 0.800 | 353.00 | 0.00 | 90.00 | N | ||
| M INTERNALMASS S2A | INTERIORFURNISHINGS | 0.30 | 0.800 | 353.00 | 0.00 | 90.00 | N | ||
| T INTERNALMASS SWA | INTERIORFURNISHINGS | 0.30 | 0.800 | 88.25 | 0.00 | 90.00 | N | ||
| T INTERNALMASS NWA | INTERIORFURNISHINGS | 0.30 | 0.800 | 88.25 | 0.00 | 90.00 | N | ||
| T INTERNALMASS SEA | INTERIORFURNISHINGS | 0.30 | 0.800 | 88.25 | 0.00 | 90.00 | N | ||
| T INTERNALMASS NEA | INTERIORFURNISHINGS | 0.30 | 0.800 | 88.25 | 0.00 | 90.00 | N | ||
| T INTERNALMASS N1A | INTERIORFURNISHINGS | 0.30 | 0.800 | 88.25 | 0.00 | 90.00 | N | ||
| T INTERNALMASS N2A | INTERIORFURNISHINGS | 0.30 | 0.800 | 88.25 | 0.00 | 90.00 | N | ||
| T INTERNALMASS S1A | INTERIORFURNISHINGS | 0.30 | 0.800 | 88.25 | 0.00 | 90.00 | N | ||
| T INTERNALMASS S2A | INTERIORFURNISHINGS | 0.30 | 0.800 | 88.25 | 0.00 | 90.00 | N |
| Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
| GWINDOW1 S SWA | RESWINDOW_U_0.3097_SHGC_0.45 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 1.759 | 0.451 | 0.452 | No | G SWALL SWA | 180.00 | 90.00 | S | |||||||
| GWINDOW1 W SWA | RESWINDOW_U_0.3097_SHGC_0.45 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 1.759 | 0.451 | 0.452 | No | G WWALL SWA | 270.00 | 90.00 | W | |||||||
| GWINDOW1 N NWA | RESWINDOW_U_0.3097_SHGC_0.45 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 1.759 | 0.451 | 0.452 | No | G NWALL NWA | 0.00 | 90.00 | N | |||||||
| GWINDOW1 W NWA | RESWINDOW_U_0.3097_SHGC_0.45 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 1.759 | 0.451 | 0.452 | No | G WWALL NWA | 270.00 | 90.00 | W | |||||||
| GWINDOW1 S SEA | NONRESWINDOW_U_0.3097_SHGC_0.45 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 1.759 | 0.451 | 0.452 | No | G SWALL SEA | 180.00 | 90.00 | S | |||||||
| GWINDOW1 E SEA | NONRESWINDOW_U_0.3097_SHGC_0.45 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 1.759 | 0.451 | 0.452 | No | G EWALL SEA | 90.00 | 90.00 | E | |||||||
| GWINDOW1 N NEA | RESWINDOW_U_0.3097_SHGC_0.45 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 1.759 | 0.451 | 0.452 | No | G NWALL NEA | 0.00 | 90.00 | N | |||||||
| GWINDOW1 E NEA | RESWINDOW_U_0.3097_SHGC_0.45 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 1.759 | 0.451 | 0.452 | No | G EWALL NEA | 90.00 | 90.00 | E | |||||||
| GWINDOW1 N N1A | RESWINDOW_U_0.3097_SHGC_0.45 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 1.759 | 0.451 | 0.452 | No | G NWALL N1A | 0.00 | 90.00 | N | |||||||
| GWINDOW1 N N2A | RESWINDOW_U_0.3097_SHGC_0.45 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 1.759 | 0.451 | 0.452 | No | G NWALL N2A | 0.00 | 90.00 | N | |||||||
| GWINDOW1 S S1A | RESWINDOW_U_0.3097_SHGC_0.45 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 1.759 | 0.451 | 0.452 | No | G SWALL S1A | 180.00 | 90.00 | S | |||||||
| GWINDOW1 S S2A | RESWINDOW_U_0.3097_SHGC_0.45 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 1.759 | 0.451 | 0.452 | No | G SWALL S2A | 180.00 | 90.00 | S | |||||||
| MWINDOW1 W SWA | RESWINDOW_U_0.3097_SHGC_0.45 | 4.65 | 0.00 | 0.00 | 4.65 | 9.29 | 1.759 | 0.451 | 0.452 | No | M WWALL SWA | 270.00 | 90.00 | W | |||||||
| MWINDOW1 S SWA | RESWINDOW_U_0.3097_SHGC_0.45 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 1.759 | 0.451 | 0.452 | No | M SWALL SWA | 180.00 | 90.00 | S | |||||||
| MWINDOW1 N NWA | RESWINDOW_U_0.3097_SHGC_0.45 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 1.759 | 0.451 | 0.452 | No | M NWALL NWA | 0.00 | 90.00 | N | |||||||
| MWINDOW1 W NWA | RESWINDOW_U_0.3097_SHGC_0.45 | 4.65 | 0.00 | 0.00 | 4.65 | 9.29 | 1.759 | 0.451 | 0.452 | No | M WWALL NWA | 270.00 | 90.00 | W | |||||||
| MWINDOW1 E SEA | RESWINDOW_U_0.3097_SHGC_0.45 | 4.65 | 0.00 | 0.00 | 4.65 | 9.29 | 1.759 | 0.451 | 0.452 | No | M EWALL SEA | 90.00 | 90.00 | E | |||||||
| MWINDOW1 S SEA | RESWINDOW_U_0.3097_SHGC_0.45 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 1.759 | 0.451 | 0.452 | No | M SWALL SEA | 180.00 | 90.00 | S | |||||||
| MWINDOW1 N NEA | RESWINDOW_U_0.3097_SHGC_0.45 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 1.759 | 0.451 | 0.452 | No | M NWALL NEA | 0.00 | 90.00 | N | |||||||
| MWINDOW1 E NEA | RESWINDOW_U_0.3097_SHGC_0.45 | 4.65 | 0.00 | 0.00 | 4.65 | 9.29 | 1.759 | 0.451 | 0.452 | No | M EWALL NEA | 90.00 | 90.00 | E | |||||||
| MWINDOW1 N N1A | RESWINDOW_U_0.3097_SHGC_0.45 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 1.759 | 0.451 | 0.452 | No | M NWALL N1A | 0.00 | 90.00 | N | |||||||
| MWINDOW1 N N2A | RESWINDOW_U_0.3097_SHGC_0.45 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 1.759 | 0.451 | 0.452 | No | M NWALL N2A | 0.00 | 90.00 | N | |||||||
| MWINDOW1 S S1A | RESWINDOW_U_0.3097_SHGC_0.45 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 1.759 | 0.451 | 0.452 | No | M SWALL S1A | 180.00 | 90.00 | S | |||||||
| MWINDOW1 S S2A | RESWINDOW_U_0.3097_SHGC_0.45 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 1.759 | 0.451 | 0.452 | No | M SWALL S2A | 180.00 | 90.00 | S | |||||||
| TWINDOW1 W SWA | RESWINDOW_U_0.3097_SHGC_0.45 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 1.759 | 0.451 | 0.452 | No | T WWALL SWA | 270.00 | 90.00 | W | |||||||
| TWINDOW1 S SWA | RESWINDOW_U_0.3097_SHGC_0.45 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 1.759 | 0.451 | 0.452 | No | T SWALL SWA | 180.00 | 90.00 | S | |||||||
| TWINDOW1 N NWA | RESWINDOW_U_0.3097_SHGC_0.45 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 1.759 | 0.451 | 0.452 | No | T NWALL NWA | 0.00 | 90.00 | N | |||||||
| TWINDOW1 W NWA | RESWINDOW_U_0.3097_SHGC_0.45 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 1.759 | 0.451 | 0.452 | No | T WWALL NWA | 270.00 | 90.00 | W | |||||||
| TWINDOW1 E SEA | RESWINDOW_U_0.3097_SHGC_0.45 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 1.759 | 0.451 | 0.452 | No | T EWALL SEA | 90.00 | 90.00 | E | |||||||
| TWINDOW1 S SEA | RESWINDOW_U_0.3097_SHGC_0.45 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 1.759 | 0.451 | 0.452 | No | T SWALL SEA | 180.00 | 90.00 | S | |||||||
| TWINDOW1 N NEA | RESWINDOW_U_0.3097_SHGC_0.45 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 1.759 | 0.451 | 0.452 | No | T NWALL NEA | 0.00 | 90.00 | N | |||||||
| TWINDOW1 E NEA | RESWINDOW_U_0.3097_SHGC_0.45 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 1.759 | 0.451 | 0.452 | No | T EWALL NEA | 90.00 | 90.00 | E | |||||||
| TWINDOW1 N N1A | RESWINDOW_U_0.3097_SHGC_0.45 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 1.759 | 0.451 | 0.452 | No | T NWALL N1A | 0.00 | 90.00 | N | |||||||
| TWINDOW1 N N2A | RESWINDOW_U_0.3097_SHGC_0.45 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 1.759 | 0.451 | 0.452 | No | T NWALL N2A | 0.00 | 90.00 | N | |||||||
| TWINDOW1 S S1A | RESWINDOW_U_0.3097_SHGC_0.45 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 1.759 | 0.451 | 0.452 | No | T SWALL S1A | 180.00 | 90.00 | S | |||||||
| TWINDOW1 S S2A | RESWINDOW_U_0.3097_SHGC_0.45 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 1.759 | 0.451 | 0.452 | No | T SWALL S2A | 180.00 | 90.00 | S | |||||||
| TWINDOW14 | NONRESWINDOW_U_0.3097_SHGC_0.45 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 1.759 | 0.451 | 0.452 | No | T EWALL C | 90.00 | 90.00 | E | |||||||
| ENTRANCE DOOR | NONRESWINDOW_U_0.3097_SHGC_0.45 | 3.32 | 0.00 | 0.00 | 3.32 | 3.32 | 1.759 | 0.451 | 0.452 | No | G EWALL C | 90.00 | 90.00 | E | |||||||
| MWINDOW14 | NONRESWINDOW_U_0.3097_SHGC_0.45 | 1.11 | 0.00 | 0.00 | 1.11 | 2.23 | 1.759 | 0.451 | 0.452 | No | M EWALL C | 90.00 | 90.00 | E | |||||||
| Total or Average | 306.92 | 1.759 | 0.451 | 0.452 | |||||||||||||||||
| North Total or Average | 112.97 | 1.759 | 0.451 | 0.452 | |||||||||||||||||
| Non-North Total or Average | 193.95 | 1.759 | 0.451 | 0.452 |
| Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
| None |
| Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
| Total or Average | 0.00 | - | - | - |
| Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
| None |
| Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
| None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 09:14:30
Sunlit Fraction| March 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
| GWINDOW1 S SWA | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
| GWINDOW1 W SWA | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
| GWINDOW1 N NWA | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| GWINDOW1 W NWA | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
| GWINDOW1 S SEA | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
| GWINDOW1 E SEA | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 |
| GWINDOW1 N NEA | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| GWINDOW1 E NEA | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 |
| GWINDOW1 N N1A | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| GWINDOW1 N N2A | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| GWINDOW1 S S1A | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
| GWINDOW1 S S2A | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
| MWINDOW1 W SWA | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
| MWINDOW1 S SWA | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
| MWINDOW1 N NWA | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| MWINDOW1 W NWA | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
| MWINDOW1 E SEA | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 |
| MWINDOW1 S SEA | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
| MWINDOW1 N NEA | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| MWINDOW1 E NEA | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 |
| MWINDOW1 N N1A | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| MWINDOW1 N N2A | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| MWINDOW1 S S1A | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
| MWINDOW1 S S2A | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
| TWINDOW1 W SWA | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
| TWINDOW1 S SWA | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
| TWINDOW1 N NWA | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| TWINDOW1 W NWA | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
| TWINDOW1 E SEA | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 |
| TWINDOW1 S SEA | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
| TWINDOW1 N NEA | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| TWINDOW1 E NEA | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 |
| TWINDOW1 N N1A | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| TWINDOW1 N N2A | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| TWINDOW1 S S1A | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
| TWINDOW1 S S2A | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
| TWINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 |
| ENTRANCE DOOR | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 |
| MWINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 |
| Name | Type | Shaded Construction | Control | Glare Control | |
| None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 09:14:30
Interior Lighting| Zone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
| LIGHTING_HARDWIRED_GSW | G SW APARTMENT | G SW APARTMENT | GENERAL | 7.8684 | 88.25 | 694.38 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.32 |
| LIGHTING_HARDWIRED_GNW | G NW APARTMENT | G NW APARTMENT | GENERAL | 7.8684 | 88.25 | 694.38 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.32 |
| LIGHTING_HARDWIRED_OFFICE | OFFICE | OFFICE | GENERAL | 9.7532 | 88.25 | 860.71 | LightsWired | LTG_SCH_OFFICE | 46.69 | 168.00 | 45.77 | 0.0000 | Y | 7.40 |
| LIGHTING_HARDWIRED_GNE | G NE APARTMENT | G NE APARTMENT | GENERAL | 7.8684 | 88.25 | 694.38 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.32 |
| LIGHTING_HARDWIRED_GN1 | G N1 APARTMENT | G N1 APARTMENT | GENERAL | 7.8684 | 88.25 | 694.38 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.32 |
| LIGHTING_HARDWIRED_GN2 | G N2 APARTMENT | G N2 APARTMENT | GENERAL | 7.8684 | 88.25 | 694.38 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.32 |
| LIGHTING_HARDWIRED_GS1 | G S1 APARTMENT | G S1 APARTMENT | GENERAL | 7.8684 | 88.25 | 694.38 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.32 |
| LIGHTING_HARDWIRED_GS2 | G S2 APARTMENT | G S2 APARTMENT | GENERAL | 7.8684 | 88.25 | 694.38 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.32 |
| LIGHTING_HARDWIRED_MSW | M SW APARTMENT | M SW APARTMENT | GENERAL | 7.8684 | 176.50 | 1388.76 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 2.63 |
| LIGHTING_HARDWIRED_MNW | M NW APARTMENT | M NW APARTMENT | GENERAL | 7.8684 | 176.50 | 1388.76 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 2.63 |
| LIGHTING_HARDWIRED_MSE | M SE APARTMENT | M SE APARTMENT | GENERAL | 7.8684 | 176.50 | 1388.76 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 2.63 |
| LIGHTING_HARDWIRED_MNE | M NE APARTMENT | M NE APARTMENT | GENERAL | 7.8684 | 176.50 | 1388.76 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 2.63 |
| LIGHTING_HARDWIRED_MN1 | M N1 APARTMENT | M N1 APARTMENT | GENERAL | 7.8684 | 176.50 | 1388.76 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 2.63 |
| LIGHTING_HARDWIRED_MN2 | M N2 APARTMENT | M N2 APARTMENT | GENERAL | 7.8684 | 176.50 | 1388.76 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 2.63 |
| LIGHTING_HARDWIRED_MS1 | M S1 APARTMENT | M S1 APARTMENT | GENERAL | 7.8684 | 176.50 | 1388.76 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 2.63 |
| LIGHTING_HARDWIRED_MS2 | M S2 APARTMENT | M S2 APARTMENT | GENERAL | 7.8684 | 176.50 | 1388.76 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 2.63 |
| LIGHTING_HARDWIRED_TSW | T SW APARTMENT | T SW APARTMENT | GENERAL | 7.8684 | 88.25 | 694.38 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.32 |
| LIGHTING_HARDWIRED_TNW | T NW APARTMENT | T NW APARTMENT | GENERAL | 7.8684 | 88.25 | 694.38 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.32 |
| LIGHTING_HARDWIRED_TSE | T SE APARTMENT | T SE APARTMENT | GENERAL | 7.8684 | 88.25 | 694.38 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.32 |
| LIGHTING_HARDWIRED_TNE | T NE APARTMENT | T NE APARTMENT | GENERAL | 7.8684 | 88.25 | 694.38 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.32 |
| LIGHTING_HARDWIRED_TN1 | T N1 APARTMENT | T N1 APARTMENT | GENERAL | 7.8684 | 88.25 | 694.38 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.32 |
| LIGHTING_HARDWIRED_TN2 | T N2 APARTMENT | T N2 APARTMENT | GENERAL | 7.8684 | 88.25 | 694.38 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.32 |
| LIGHTING_HARDWIRED_TS1 | T S1 APARTMENT | T S1 APARTMENT | GENERAL | 7.8684 | 88.25 | 694.38 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.32 |
| LIGHTING_HARDWIRED_TS2 | T S2 APARTMENT | T S2 APARTMENT | GENERAL | 7.8684 | 88.25 | 694.38 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.32 |
| LIGHTING_HARDWIRED_GC | G CORRIDOR | G CORRIDOR | GENERAL | 4.7725 | 77.66 | 370.63 | LightsWired | LTG_SCH_CORRIDOR | 168.00 | 168.00 | 168.00 | 0.0000 | N | 11.69 |
| LIGHTING_HARDWIRED_MC | M CORRIDOR | M CORRIDOR | GENERAL | 4.7725 | 155.32 | 741.26 | LightsWired | LTG_SCH_CORRIDOR | 168.00 | 168.00 | 168.00 | 0.0000 | N | 23.38 |
| LIGHTING_HARDWIRED_TC | T CORRIDOR | T CORRIDOR | GENERAL | 4.7725 | 77.66 | 370.63 | LightsWired | LTG_SCH_CORRIDOR | 168.00 | 168.00 | 168.00 | 0.0000 | N | 11.69 |
| LIGHTING_PLUGIN_GSW | G SW APARTMENT | G SW APARTMENT | GENERAL | 0.8234 | 88.25 | 72.67 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.14 |
| LIGHTING_PLUGIN_GNW | G NW APARTMENT | G NW APARTMENT | GENERAL | 0.8234 | 88.25 | 72.67 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.14 |
| LIGHTING_PLUGIN_GNE | G NE APARTMENT | G NE APARTMENT | GENERAL | 0.8234 | 88.25 | 72.67 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.14 |
| LIGHTING_PLUGIN_GN1 | G N1 APARTMENT | G N1 APARTMENT | GENERAL | 0.8234 | 88.25 | 72.67 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.14 |
| LIGHTING_PLUGIN_GN2 | G N2 APARTMENT | G N2 APARTMENT | GENERAL | 0.8234 | 88.25 | 72.67 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.14 |
| LIGHTING_PLUGIN_GS1 | G S1 APARTMENT | G S1 APARTMENT | GENERAL | 0.8234 | 88.25 | 72.67 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.14 |
| LIGHTING_PLUGIN_GS2 | G S2 APARTMENT | G S2 APARTMENT | GENERAL | 0.8234 | 88.25 | 72.67 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.14 |
| LIGHTING_PLUGIN_MSW | M SW APARTMENT | M SW APARTMENT | GENERAL | 0.8234 | 176.50 | 145.34 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.28 |
| LIGHTING_PLUGIN_MNW | M NW APARTMENT | M NW APARTMENT | GENERAL | 0.8234 | 176.50 | 145.34 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.28 |
| LIGHTING_PLUGIN_MSE | M SE APARTMENT | M SE APARTMENT | GENERAL | 0.8234 | 176.50 | 145.34 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.28 |
| LIGHTING_PLUGIN_MNE | M NE APARTMENT | M NE APARTMENT | GENERAL | 0.8234 | 176.50 | 145.34 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.28 |
| LIGHTING_PLUGIN_MN1 | M N1 APARTMENT | M N1 APARTMENT | GENERAL | 0.8234 | 176.50 | 145.34 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.28 |
| LIGHTING_PLUGIN_MN2 | M N2 APARTMENT | M N2 APARTMENT | GENERAL | 0.8234 | 176.50 | 145.34 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.28 |
| LIGHTING_PLUGIN_MS1 | M S1 APARTMENT | M S1 APARTMENT | GENERAL | 0.8234 | 176.50 | 145.34 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.28 |
| LIGHTING_PLUGIN_MS2 | M S2 APARTMENT | M S2 APARTMENT | GENERAL | 0.8234 | 176.50 | 145.34 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.28 |
| LIGHTING_PLUGIN_TSW | T SW APARTMENT | T SW APARTMENT | GENERAL | 0.8234 | 88.25 | 72.67 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.14 |
| LIGHTING_PLUGIN_TNW | T NW APARTMENT | T NW APARTMENT | GENERAL | 0.8234 | 88.25 | 72.67 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.14 |
| LIGHTING_PLUGIN_TSE | T SE APARTMENT | T SE APARTMENT | GENERAL | 0.8234 | 88.25 | 72.67 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.14 |
| LIGHTING_PLUGIN_TNE | T NE APARTMENT | T NE APARTMENT | GENERAL | 0.8234 | 88.25 | 72.67 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.14 |
| LIGHTING_PLUGIN_TN1 | T N1 APARTMENT | T N1 APARTMENT | GENERAL | 0.8234 | 88.25 | 72.67 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.14 |
| LIGHTING_PLUGIN_TN2 | T N2 APARTMENT | T N2 APARTMENT | GENERAL | 0.8234 | 88.25 | 72.67 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.14 |
| LIGHTING_PLUGIN_TS1 | T S1 APARTMENT | T S1 APARTMENT | GENERAL | 0.8234 | 88.25 | 72.67 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.14 |
| LIGHTING_PLUGIN_TS2 | T S2 APARTMENT | T S2 APARTMENT | GENERAL | 0.8234 | 88.25 | 72.67 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.14 |
| Interior Lighting Total | 4.4498 | 5870.34 | 26121.74 | 75.91 |
| Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
| None |
| Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
| FACADE LIGHTING | 3183.33 | AstronomicalClock | - | 83.06 | 83.06 | 49.63 | |
| Exterior Lighting Total | 3183.33 | 49.63 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 09:14:30
Central Plant| Type | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
| None |
| Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
| SPLIT GSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 6451.51 | 5165.44 | 1286.07 | 0.80 | 3.91 | |||
| SPLIT GNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5281.46 | 4228.63 | 1052.83 | 0.80 | 3.91 | |||
| SPLIT OFFICE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 6782.98 | 5430.83 | 1352.15 | 0.80 | 3.91 | |||
| SPLIT GNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 4647.89 | 3721.36 | 926.53 | 0.80 | 3.91 | |||
| SPLIT GN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 4154.71 | 3326.49 | 828.22 | 0.80 | 3.91 | |||
| SPLIT GN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 4146.07 | 3319.57 | 826.50 | 0.80 | 3.91 | |||
| SPLIT GS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5396.80 | 4320.98 | 1075.82 | 0.80 | 3.91 | |||
| SPLIT GS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5427.42 | 4345.49 | 1081.93 | 0.80 | 3.91 | |||
| SPLIT MSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 16185.57 | 12959.06 | 3226.51 | 0.80 | 3.91 | |||
| SPLIT MNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 13874.62 | 11108.78 | 2765.83 | 0.80 | 3.91 | |||
| SPLIT MSE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 13882.99 | 11115.49 | 2767.50 | 0.80 | 3.91 | |||
| SPLIT MNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 11643.63 | 9322.54 | 2321.10 | 0.80 | 3.91 | |||
| SPLIT MN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10392.98 | 8321.19 | 2071.79 | 0.80 | 3.91 | |||
| SPLIT MN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10365.54 | 8299.23 | 2066.32 | 0.80 | 3.91 | |||
| SPLIT MS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 12836.31 | 10277.46 | 2558.85 | 0.80 | 3.91 | |||
| SPLIT MS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 12803.94 | 10251.54 | 2552.40 | 0.80 | 3.91 | |||
| SPLIT TSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 8778.48 | 7028.54 | 1749.94 | 0.80 | 3.91 | |||
| SPLIT TNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7688.72 | 6156.02 | 1532.71 | 0.80 | 3.91 | |||
| SPLIT TSE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7097.47 | 5682.62 | 1414.84 | 0.80 | 3.91 | |||
| SPLIT TNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 6031.48 | 4829.14 | 1202.34 | 0.80 | 3.91 | |||
| SPLIT TN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5670.97 | 4540.49 | 1130.48 | 0.80 | 3.91 | |||
| SPLIT TN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5628.11 | 4506.18 | 1121.93 | 0.80 | 3.91 | |||
| SPLIT TS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 6801.20 | 5445.41 | 1355.78 | 0.80 | 3.91 | |||
| SPLIT TS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 6757.97 | 5410.81 | 1347.17 | 0.80 | 3.91 |
| DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
| SPLIT GSW COOLING COIL | 6146.1 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 | |
| SPLIT GNW COOLING COIL | 5031.4 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 | |
| SPLIT OFFICE COOLING COIL | 6461.9 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 | |
| SPLIT GNE COOLING COIL | 4427.8 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 | |
| SPLIT GN1 COOLING COIL | 3958.0 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 | |
| SPLIT GN2 COOLING COIL | 3949.8 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 | |
| SPLIT GS1 COOLING COIL | 5141.3 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 | |
| SPLIT GS2 COOLING COIL | 5170.5 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 | |
| SPLIT MSW COOLING COIL | 15419.3 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 | |
| SPLIT MNW COOLING COIL | 13217.8 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 | |
| SPLIT MSE COOLING COIL | 13225.7 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 | |
| SPLIT MNE COOLING COIL | 11092.4 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 | |
| SPLIT MN1 COOLING COIL | 9901.0 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 | |
| SPLIT MN2 COOLING COIL | 9874.8 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 | |
| SPLIT MS1 COOLING COIL | 12228.6 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 | |
| SPLIT MS2 COOLING COIL | 12197.8 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 | |
| SPLIT TSW COOLING COIL | 8362.9 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 | |
| SPLIT TNW COOLING COIL | 7324.7 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 | |
| SPLIT TSE COOLING COIL | 6761.5 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 | |
| SPLIT TNE COOLING COIL | 5745.9 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 | |
| SPLIT TN1 COOLING COIL | 5402.5 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 | |
| SPLIT TN2 COOLING COIL | 5361.7 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 | |
| SPLIT TS1 COOLING COIL | 6479.2 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 | |
| SPLIT TS2 COOLING COIL | 6438.0 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 |
| DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
| SPLIT GSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT GNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT OFFICE COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT GNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT GN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT GN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT GS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT GS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT MSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT MNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT MSE COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT MNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT MN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT MN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT MS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT MS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT TSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT TNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT TSE COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT TNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT TN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT TN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT TS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT TS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed |
| DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
| None |
| Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
| SPLIT GSW HEATING COIL | Coil:Heating:Fuel | 10722.17 | 0.80 | |
| SPLIT GNW HEATING COIL | Coil:Heating:Fuel | 9130.81 | 0.80 | |
| SPLIT OFFICE HEATING COIL | Coil:Heating:Fuel | 12084.91 | 0.80 | |
| SPLIT GNE HEATING COIL | Coil:Heating:Fuel | 8269.12 | 0.80 | |
| SPLIT GN1 HEATING COIL | Coil:Heating:Fuel | 7598.36 | 0.80 | |
| SPLIT GN2 HEATING COIL | Coil:Heating:Fuel | 7586.61 | 0.80 | |
| SPLIT GS1 HEATING COIL | Coil:Heating:Fuel | 9287.71 | 0.80 | |
| SPLIT GS2 HEATING COIL | Coil:Heating:Fuel | 9329.35 | 0.80 | |
| SPLIT MSW HEATING COIL | Coil:Heating:Fuel | 25908.94 | 0.80 | |
| SPLIT MNW HEATING COIL | Coil:Heating:Fuel | 22765.58 | 0.80 | |
| SPLIT MSE HEATING COIL | Coil:Heating:Fuel | 22777.29 | 0.80 | |
| SPLIT MNE HEATING COIL | Coil:Heating:Fuel | 19731.36 | 0.80 | |
| SPLIT MN1 HEATING COIL | Coil:Heating:Fuel | 18030.36 | 0.80 | |
| SPLIT MN2 HEATING COIL | Coil:Heating:Fuel | 17993.04 | 0.80 | |
| SPLIT MS1 HEATING COIL | Coil:Heating:Fuel | 21353.68 | 0.80 | |
| SPLIT MS2 HEATING COIL | Coil:Heating:Fuel | 21309.64 | 0.80 | |
| SPLIT TSW HEATING COIL | Coil:Heating:Fuel | 13887.09 | 0.80 | |
| SPLIT TNW HEATING COIL | Coil:Heating:Fuel | 12404.78 | 0.80 | |
| SPLIT TSE HEATING COIL | Coil:Heating:Fuel | 11600.80 | 0.80 | |
| SPLIT TNE HEATING COIL | Coil:Heating:Fuel | 10150.85 | 0.80 | |
| SPLIT TN1 HEATING COIL | Coil:Heating:Fuel | 9660.51 | 0.80 | |
| SPLIT TN2 HEATING COIL | Coil:Heating:Fuel | 9602.22 | 0.80 | |
| SPLIT TS1 HEATING COIL | Coil:Heating:Fuel | 11197.81 | 0.80 | |
| SPLIT TS2 HEATING COIL | Coil:Heating:Fuel | 11139.02 | 0.80 |
| Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
| G SW APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| G SW APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| G NW APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| G NW APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| G NE APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| G NE APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| G N1 APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| G N1 APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| G N2 APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| G N2 APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| G S1 APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| G S1 APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| G S2 APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| G S2 APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| M SW APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.05 | 40.01 | 770.84 | 1.00 | 4.13 | General | ||
| M SW APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.05 | 40.01 | 770.84 | 1.00 | 4.13 | General | ||
| M NW APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.05 | 40.01 | 770.84 | 1.00 | 4.13 | General | ||
| M NW APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.05 | 40.01 | 770.84 | 1.00 | 4.13 | General | ||
| M SE APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.05 | 40.01 | 770.84 | 1.00 | 4.13 | General | ||
| M SE APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.05 | 40.01 | 770.84 | 1.00 | 4.13 | General | ||
| M NE APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.05 | 40.01 | 770.84 | 1.00 | 4.13 | General | ||
| M NE APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.05 | 40.01 | 770.84 | 1.00 | 4.13 | General | ||
| M N1 APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.05 | 40.01 | 770.84 | 1.00 | 4.13 | General | ||
| M N1 APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.05 | 40.01 | 770.84 | 1.00 | 4.13 | General | ||
| M N2 APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.05 | 40.01 | 770.84 | 1.00 | 4.13 | General | ||
| M N2 APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.05 | 40.01 | 770.84 | 1.00 | 4.13 | General | ||
| M S1 APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.05 | 40.01 | 770.84 | 1.00 | 4.13 | General | ||
| M S1 APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.05 | 40.01 | 770.84 | 1.00 | 4.13 | General | ||
| M S2 APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.05 | 40.01 | 770.84 | 1.00 | 4.13 | General | ||
| M S2 APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.05 | 40.01 | 770.84 | 1.00 | 4.13 | General | ||
| T SW APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| T SW APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| T NW APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| T NW APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| T SE APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| T SE APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| T NE APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| T NE APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| T N1 APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| T N1 APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| T N2 APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| T N2 APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| T S1 APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| T S1 APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| T S2 APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| T S2 APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| SPLIT GSW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.39 | 436.55 | 1120.11 | 1.00 | 1.73 | General | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 |
| SPLIT GNW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.32 | 357.37 | 1120.11 | 1.00 | 1.85 | General | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 |
| SPLIT OFFICE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.41 | 458.98 | 1120.11 | 1.00 | 1.70 | General | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 12:20:00 |
| SPLIT GNE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.28 | 314.50 | 1120.11 | 1.00 | 1.94 | General | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 |
| SPLIT GN1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.25 | 281.13 | 1120.11 | 1.00 | 2.03 | General | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 |
| SPLIT GN2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.25 | 280.55 | 1120.11 | 1.00 | 2.04 | General | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 |
| SPLIT GS1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.33 | 365.18 | 1120.11 | 1.00 | 1.84 | General | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 |
| SPLIT GS2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.33 | 367.25 | 1120.11 | 1.00 | 1.84 | General | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 |
| SPLIT MSW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.98 | 1095.21 | 1120.11 | 1.00 | 1.38 | General | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 |
| SPLIT MNW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.84 | 938.84 | 1120.11 | 1.00 | 1.42 | General | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 |
| SPLIT MSE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.84 | 939.40 | 1120.11 | 1.00 | 1.42 | General | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 |
| SPLIT MNE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.70 | 787.87 | 1120.11 | 1.00 | 1.47 | General | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 |
| SPLIT MN1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.63 | 703.25 | 1120.11 | 1.00 | 1.51 | General | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 |
| SPLIT MN2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.63 | 701.39 | 1120.11 | 1.00 | 1.51 | General | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 |
| SPLIT MS1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.78 | 868.58 | 1120.11 | 1.00 | 1.44 | General | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 |
| SPLIT MS2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.77 | 866.39 | 1120.11 | 1.00 | 1.44 | General | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 |
| SPLIT TSW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.53 | 594.00 | 1120.11 | 1.00 | 1.58 | General | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 |
| SPLIT TNW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.46 | 520.26 | 1120.11 | 1.00 | 1.64 | General | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 |
| SPLIT TSE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.43 | 480.26 | 1120.11 | 1.00 | 1.68 | General | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 |
| SPLIT TNE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.36 | 408.12 | 1120.11 | 1.00 | 1.77 | General | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 |
| SPLIT TN1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.34 | 383.73 | 1120.11 | 1.00 | 1.81 | General | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 |
| SPLIT TN2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.34 | 380.83 | 1120.11 | 1.00 | 1.81 | General | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 |
| SPLIT TS1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.41 | 460.21 | 1120.11 | 1.00 | 1.70 | General | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 |
| SPLIT TS2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.41 | 457.28 | 1120.11 | 1.00 | 1.71 | General | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 |
| Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
| None |
| Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
| G SW APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.77 |
| G NW APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.77 |
| G NE APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.77 |
| G N1 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.77 |
| G N2 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.77 |
| G S1 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.77 |
| G S2 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.77 |
| M SW APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.79 |
| M NW APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.79 |
| M SE APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.79 |
| M NE APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.79 |
| M N1 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.79 |
| M N2 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.79 |
| M S1 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.79 |
| M S2 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.79 |
| T SW APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.77 |
| T NW APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.77 |
| T SE APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.77 |
| T NE APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.77 |
| T N1 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.77 |
| T N2 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.77 |
| T S1 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.77 |
| T S2 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.77 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 09:14:30
Zone Sensible Cooling| Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
| G SW APARTMENT | 4515.54 | 5418.65 | 61.40 | 0.325 | 0.390 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 24.00 | 24.00 | 0.00807 | 23.42 | 0.00700 | 0.026 | 0.00 |
| G NW APARTMENT | 3714.03 | 4456.84 | 50.50 | 0.266 | 0.319 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 24.00 | 24.00 | 0.00806 | 23.42 | 0.00700 | 0.026 | 0.00 |
| OFFICE | 4686.52 | 5623.83 | 63.73 | 0.341 | 0.410 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 23.90 | 23.90 | 0.00798 | 21.79 | 0.00700 | 0.038 | 0.00 |
| G NE APARTMENT | 3280.01 | 3936.02 | 44.60 | 0.234 | 0.281 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 24.00 | 24.00 | 0.00808 | 23.42 | 0.00700 | 0.026 | 0.00 |
| G N1 APARTMENT | 2941.57 | 3529.88 | 40.00 | 0.209 | 0.251 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 24.00 | 24.00 | 0.00811 | 23.42 | 0.00700 | 0.026 | 0.00 |
| G N2 APARTMENT | 2935.64 | 3522.77 | 39.92 | 0.209 | 0.250 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 24.00 | 24.00 | 0.00811 | 23.42 | 0.00700 | 0.026 | 0.00 |
| G S1 APARTMENT | 3794.34 | 4553.21 | 51.59 | 0.272 | 0.326 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 24.00 | 24.00 | 0.00811 | 23.42 | 0.00700 | 0.026 | 0.00 |
| G S2 APARTMENT | 3815.25 | 4578.30 | 51.88 | 0.273 | 0.328 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 24.00 | 24.00 | 0.00811 | 23.42 | 0.00700 | 0.026 | 0.00 |
| M SW APARTMENT | 11287.23 | 13544.68 | 153.48 | 0.815 | 0.978 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 24.00 | 24.00 | 0.00804 | 23.42 | 0.00700 | 0.052 | 0.00 |
| M NW APARTMENT | 9697.40 | 11636.88 | 131.86 | 0.698 | 0.838 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 24.00 | 24.00 | 0.00804 | 23.42 | 0.00700 | 0.052 | 0.00 |
| M SE APARTMENT | 9704.80 | 11645.75 | 131.96 | 0.699 | 0.839 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 24.00 | 24.00 | 0.00805 | 23.42 | 0.00700 | 0.052 | 0.00 |
| M NE APARTMENT | 8170.95 | 9805.14 | 111.11 | 0.586 | 0.703 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 24.00 | 24.00 | 0.00805 | 23.42 | 0.00700 | 0.052 | 0.00 |
| M N1 APARTMENT | 7312.52 | 8775.02 | 99.43 | 0.523 | 0.628 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 24.00 | 24.00 | 0.00807 | 23.42 | 0.00700 | 0.052 | 0.00 |
| M N2 APARTMENT | 7293.67 | 8752.41 | 99.18 | 0.522 | 0.626 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 24.00 | 24.00 | 0.00807 | 23.42 | 0.00700 | 0.052 | 0.00 |
| M S1 APARTMENT | 8986.75 | 10784.10 | 122.20 | 0.646 | 0.775 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 24.00 | 24.00 | 0.00807 | 23.42 | 0.00700 | 0.052 | 0.00 |
| M S2 APARTMENT | 8964.59 | 10757.50 | 121.90 | 0.645 | 0.773 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 24.00 | 24.00 | 0.00807 | 23.42 | 0.00700 | 0.052 | 0.00 |
| T SW APARTMENT | 6114.21 | 7337.05 | 83.14 | 0.442 | 0.530 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 24.00 | 24.00 | 0.00803 | 23.42 | 0.00700 | 0.026 | 0.00 |
| T NW APARTMENT | 5368.32 | 6441.98 | 73.00 | 0.387 | 0.464 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 24.00 | 24.00 | 0.00803 | 23.42 | 0.00700 | 0.026 | 0.00 |
| T SE APARTMENT | 4963.37 | 5956.05 | 67.49 | 0.357 | 0.429 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 24.00 | 24.00 | 0.00804 | 23.42 | 0.00700 | 0.026 | 0.00 |
| T NE APARTMENT | 4230.29 | 5076.35 | 57.52 | 0.304 | 0.364 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 24.00 | 24.00 | 0.00803 | 23.42 | 0.00700 | 0.026 | 0.00 |
| T N1 APARTMENT | 3983.40 | 4780.08 | 54.17 | 0.285 | 0.343 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 24.00 | 24.00 | 0.00805 | 23.42 | 0.00700 | 0.026 | 0.00 |
| T N2 APARTMENT | 3954.10 | 4744.92 | 53.77 | 0.283 | 0.340 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 24.00 | 24.00 | 0.00806 | 23.42 | 0.00700 | 0.026 | 0.00 |
| T S1 APARTMENT | 4759.25 | 5711.10 | 64.72 | 0.342 | 0.411 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 24.00 | 24.00 | 0.00806 | 23.42 | 0.00700 | 0.026 | 0.00 |
| T S2 APARTMENT | 4729.55 | 5675.46 | 64.31 | 0.340 | 0.408 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 24.00 | 24.00 | 0.00806 | 23.42 | 0.00700 | 0.026 | 0.00 |
| Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
| G SW APARTMENT | 3328.10 | 3993.72 | 45.25 | 0.146 | 0.175 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:50:00 | 21.10 | 21.10 | 0.00796 | -41.90 | 0.00006 | 0.026 | 0.00 |
| G NW APARTMENT | 3208.83 | 3850.60 | 43.63 | 0.140 | 0.169 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:50:00 | 21.10 | 21.10 | 0.00803 | -41.90 | 0.00006 | 0.026 | 0.00 |
| OFFICE | 3836.38 | 4603.66 | 52.17 | 0.168 | 0.202 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 18:50:00 | 21.10 | 21.10 | 0.00797 | -41.90 | 0.00006 | 0.038 | 0.00 |
| G NE APARTMENT | 3214.07 | 3856.89 | 43.70 | 0.141 | 0.169 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:50:00 | 21.10 | 21.10 | 0.00803 | -41.90 | 0.00006 | 0.026 | 0.00 |
| G N1 APARTMENT | 2191.15 | 2629.38 | 29.79 | 0.096 | 0.115 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:50:00 | 21.10 | 21.10 | 0.00808 | -41.90 | 0.00006 | 0.026 | 0.00 |
| G N2 APARTMENT | 2191.29 | 2629.54 | 29.80 | 0.096 | 0.115 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:50:00 | 21.10 | 21.10 | 0.00808 | -41.90 | 0.00006 | 0.026 | 0.00 |
| G S1 APARTMENT | 2311.47 | 2773.76 | 31.43 | 0.101 | 0.121 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:50:00 | 21.10 | 21.10 | 0.00797 | -41.90 | 0.00006 | 0.026 | 0.00 |
| G S2 APARTMENT | 2319.52 | 2783.43 | 31.54 | 0.102 | 0.122 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:50:00 | 21.10 | 21.10 | 0.00797 | -41.90 | 0.00006 | 0.026 | 0.00 |
| M SW APARTMENT | 4625.12 | 5550.15 | 62.89 | 0.202 | 0.243 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 21.10 | 21.10 | 0.00792 | -41.90 | 0.00006 | 0.052 | 0.00 |
| M NW APARTMENT | 4344.47 | 5213.37 | 59.08 | 0.190 | 0.228 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 21.10 | 21.10 | 0.00807 | -41.90 | 0.00006 | 0.052 | 0.00 |
| M SE APARTMENT | 4637.89 | 5565.47 | 63.07 | 0.203 | 0.244 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 21.10 | 21.10 | 0.00792 | -41.90 | 0.00006 | 0.052 | 0.00 |
| M NE APARTMENT | 4357.22 | 5228.67 | 59.25 | 0.191 | 0.229 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 21.10 | 21.10 | 0.00807 | -41.90 | 0.00006 | 0.052 | 0.00 |
| M N1 APARTMENT | 2420.39 | 2904.46 | 32.91 | 0.106 | 0.127 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 21.10 | 21.10 | 0.00818 | -41.90 | 0.00006 | 0.052 | 0.00 |
| M N2 APARTMENT | 2420.69 | 2904.82 | 32.92 | 0.106 | 0.127 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 21.10 | 21.10 | 0.00818 | -41.90 | 0.00006 | 0.052 | 0.00 |
| M S1 APARTMENT | 2694.61 | 3233.53 | 36.64 | 0.118 | 0.142 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 21.10 | 21.10 | 0.00792 | -41.90 | 0.00006 | 0.052 | 0.00 |
| M S2 APARTMENT | 2694.91 | 3233.89 | 36.64 | 0.118 | 0.142 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 21.10 | 21.10 | 0.00792 | -41.90 | 0.00006 | 0.052 | 0.00 |
| T SW APARTMENT | 3991.25 | 4789.50 | 54.27 | 0.175 | 0.210 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 21.10 | 21.10 | 0.00794 | -41.90 | 0.00006 | 0.026 | 0.00 |
| T NW APARTMENT | 3845.60 | 4614.72 | 52.29 | 0.168 | 0.202 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 21.10 | 21.10 | 0.00802 | -41.90 | 0.00006 | 0.026 | 0.00 |
| T SE APARTMENT | 4001.03 | 4801.24 | 54.41 | 0.175 | 0.210 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 21.10 | 21.10 | 0.00794 | -41.90 | 0.00006 | 0.026 | 0.00 |
| T NE APARTMENT | 3855.38 | 4626.46 | 52.42 | 0.169 | 0.203 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 21.10 | 21.10 | 0.00802 | -41.90 | 0.00006 | 0.026 | 0.00 |
| T N1 APARTMENT | 2682.59 | 3219.11 | 36.48 | 0.117 | 0.141 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 21.10 | 21.10 | 0.00807 | -41.90 | 0.00006 | 0.026 | 0.00 |
| T N2 APARTMENT | 2682.84 | 3219.40 | 36.48 | 0.117 | 0.141 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 21.10 | 21.10 | 0.00807 | -41.90 | 0.00006 | 0.026 | 0.00 |
| T S1 APARTMENT | 2827.90 | 3393.49 | 38.45 | 0.124 | 0.149 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 21.10 | 21.10 | 0.00795 | -41.90 | 0.00006 | 0.026 | 0.00 |
| T S2 APARTMENT | 2828.15 | 3393.78 | 38.46 | 0.124 | 0.149 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 21.10 | 21.10 | 0.00795 | -41.90 | 0.00006 | 0.026 | 0.00 |
| Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
| SPLIT GSW | 0.39 | 0.39 | 0.17 | 0.17 | 0.3897 | 0.3897 | 0.3897 | 1.0000 | 1.0000 |
| SPLIT GNW | 0.32 | 0.32 | 0.17 | 0.17 | 0.3191 | 0.3191 | 0.3191 | 1.0000 | 1.0000 |
| SPLIT OFFICE | 0.41 | 0.41 | 0.20 | 0.20 | 0.4098 | 0.4098 | 0.4098 | 1.0000 | 1.0000 |
| SPLIT GNE | 0.28 | 0.28 | 0.17 | 0.17 | 0.2808 | 0.2808 | 0.2808 | 1.0000 | 1.0000 |
| SPLIT GN1 | 0.25 | 0.25 | 0.12 | 0.12 | 0.2510 | 0.2510 | 0.2510 | 1.0000 | 1.0000 |
| SPLIT GN2 | 0.25 | 0.25 | 0.12 | 0.12 | 0.2505 | 0.2505 | 0.2505 | 1.0000 | 1.0000 |
| SPLIT GS1 | 0.33 | 0.33 | 0.12 | 0.12 | 0.3260 | 0.3260 | 0.3260 | 1.0000 | 1.0000 |
| SPLIT GS2 | 0.33 | 0.33 | 0.12 | 0.12 | 0.3279 | 0.3279 | 0.3279 | 1.0000 | 1.0000 |
| SPLIT MSW | 0.98 | 0.98 | 0.24 | 0.24 | 0.9778 | 0.9778 | 0.9778 | 1.0000 | 1.0000 |
| SPLIT MNW | 0.84 | 0.84 | 0.23 | 0.23 | 0.8382 | 0.8382 | 0.8382 | 1.0000 | 1.0000 |
| SPLIT MSE | 0.84 | 0.84 | 0.24 | 0.24 | 0.8387 | 0.8387 | 0.8387 | 1.0000 | 1.0000 |
| SPLIT MNE | 0.70 | 0.70 | 0.23 | 0.23 | 0.7034 | 0.7034 | 0.7034 | 1.0000 | 1.0000 |
| SPLIT MN1 | 0.63 | 0.63 | 0.13 | 0.13 | 0.6278 | 0.6278 | 0.6278 | 1.0000 | 1.0000 |
| SPLIT MN2 | 0.63 | 0.63 | 0.13 | 0.13 | 0.6262 | 0.6262 | 0.6262 | 1.0000 | 1.0000 |
| SPLIT MS1 | 0.78 | 0.78 | 0.14 | 0.14 | 0.7754 | 0.7754 | 0.7754 | 1.0000 | 1.0000 |
| SPLIT MS2 | 0.77 | 0.77 | 0.14 | 0.14 | 0.7735 | 0.7735 | 0.7735 | 1.0000 | 1.0000 |
| SPLIT TSW | 0.53 | 0.53 | 0.21 | 0.21 | 0.5303 | 0.5303 | 0.5303 | 1.0000 | 1.0000 |
| SPLIT TNW | 0.46 | 0.46 | 0.20 | 0.20 | 0.4645 | 0.4645 | 0.4645 | 1.0000 | 1.0000 |
| SPLIT TSE | 0.43 | 0.43 | 0.21 | 0.21 | 0.4288 | 0.4288 | 0.4288 | 1.0000 | 1.0000 |
| SPLIT TNE | 0.36 | 0.36 | 0.20 | 0.20 | 0.3644 | 0.3644 | 0.3644 | 1.0000 | 1.0000 |
| SPLIT TN1 | 0.34 | 0.34 | 0.14 | 0.14 | 0.3426 | 0.3426 | 0.3426 | 1.0000 | 1.0000 |
| SPLIT TN2 | 0.34 | 0.34 | 0.14 | 0.14 | 0.3400 | 0.3400 | 0.3400 | 1.0000 | 1.0000 |
| SPLIT TS1 | 0.41 | 0.41 | 0.15 | 0.15 | 0.4109 | 0.4109 | 0.4109 | 1.0000 | 1.0000 |
| SPLIT TS2 | 0.41 | 0.41 | 0.15 | 0.15 | 0.4082 | 0.4082 | 0.4082 | 1.0000 | 1.0000 |
| Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
| None |
| Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
| SPLIT GSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT GSW | 6451.510 | 5165.435 | 0.389736 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 6383.11 | 6383.11 | 0.389736 | 24.93 | 16.13 | 0.00799681 | 12.80 | 11.45 | 0.00799681 | 23.42 | 0.00700114 | 14.70 | 6.6595 | 24.00 | 0.00806785 | 42.7847 | 4515.54 | 0.00 | 6450.41 | 5117.72 |
| SPLIT GSW HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT GSW | 10722.174 | 10722.174 | -999.0 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:50:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:50:00 | 10722.17 | 10722.17 | 0.389736 | 16.90 | 12.58 | 0.00743573 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 6.6595 | 21.10 | 0.00796164 | 50.3618 | 3328.10 | 0.00 | -999.00 | -999.00 |
| SPLIT GNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT GNW | 5281.464 | 4228.632 | 0.319053 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 5222.84 | 5222.84 | 0.319053 | 24.91 | 16.10 | 0.00797762 | 12.80 | 11.43 | 0.00797762 | 23.42 | 0.00700114 | 14.70 | 8.1349 | 24.00 | 0.00806409 | 42.7647 | 3714.03 | 0.00 | 5280.57 | 4189.57 |
| SPLIT GNW HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT GNW | 9130.809 | 9130.809 | -999.0 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:50:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:50:00 | 9130.81 | 9130.81 | 0.319053 | 15.98 | 12.15 | 0.00737950 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 8.1349 | 21.10 | 0.00802726 | 50.7713 | 3208.83 | 0.00 | -999.00 | -999.00 |
| SPLIT OFFICE COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT OFFICE | 6782.981 | 5430.829 | 0.409760 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 12:20:00 | 6685.81 | 6685.81 | 0.409760 | 24.68 | 15.94 | 0.00788832 | 12.80 | 11.34 | 0.00788832 | 21.79 | 0.00699871 | 14.08 | 9.2996 | 23.90 | 0.00798451 | 42.6025 | 4562.49 | 0.00 | 6781.83 | 5380.66 |
| SPLIT OFFICE HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT OFFICE | 12084.906 | 12084.906 | -999.0 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 18:50:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 18:50:00 | 12084.91 | 12084.91 | 0.409760 | 15.24 | 11.70 | 0.00723226 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 9.2996 | 21.10 | 0.00796718 | 50.3964 | 3836.38 | 0.00 | -999.00 | -999.00 |
| SPLIT GNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT GNE | 4647.892 | 3721.359 | 0.280779 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 4595.61 | 4595.61 | 0.280779 | 24.89 | 16.09 | 0.00797597 | 12.80 | 11.43 | 0.00797597 | 23.42 | 0.00700114 | 14.70 | 9.2438 | 24.00 | 0.00807526 | 42.8232 | 3280.01 | 0.00 | 4647.10 | 3686.98 |
| SPLIT GNE HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT GNE | 8269.121 | 8269.121 | -999.0 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:50:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:50:00 | 8269.12 | 8269.12 | 0.280779 | 15.28 | 11.77 | 0.00729113 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 9.2438 | 21.10 | 0.00802718 | 50.7707 | 3214.07 | 0.00 | -999.00 | -999.00 |
| SPLIT GN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT GN1 | 4154.707 | 3326.488 | 0.250986 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 4108.60 | 4108.60 | 0.250986 | 24.87 | 16.10 | 0.00799299 | 12.80 | 11.45 | 0.00799299 | 23.42 | 0.00700114 | 14.70 | 10.3410 | 24.00 | 0.00810739 | 42.9917 | 2941.57 | 0.00 | 4154.00 | 3295.76 |
| SPLIT GN1 HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT GN1 | 7598.358 | 7598.358 | -999.0 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:50:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:50:00 | 7598.36 | 7598.36 | 0.250986 | 14.59 | 11.44 | 0.00725005 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 10.3410 | 21.10 | 0.00807882 | 51.0930 | 2191.15 | 0.00 | -999.00 | -999.00 |
| SPLIT GN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT GN2 | 4146.070 | 3319.573 | 0.250464 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 4100.04 | 4100.04 | 0.250464 | 24.87 | 16.10 | 0.00799290 | 12.80 | 11.45 | 0.00799290 | 23.42 | 0.00700114 | 14.70 | 10.3626 | 24.00 | 0.00810756 | 42.9925 | 2935.64 | 0.00 | 4145.36 | 3288.91 |
| SPLIT GN2 HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT GN2 | 7586.612 | 7586.612 | -999.0 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:50:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:50:00 | 7586.61 | 7586.61 | 0.250464 | 14.57 | 11.43 | 0.00724832 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 10.3626 | 21.10 | 0.00807881 | 51.0929 | 2191.29 | 0.00 | -999.00 | -999.00 |
| SPLIT GS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT GS1 | 5396.805 | 4320.980 | 0.326021 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 5340.98 | 5323.94 | 0.326021 | 24.92 | 16.14 | 0.00801852 | 12.80 | 11.46 | 0.00800000 | 23.42 | 0.00700114 | 14.70 | 7.9610 | 24.00 | 0.00810652 | 42.9874 | 3794.34 | 0.00 | 5395.89 | 4281.07 |
| SPLIT GS1 HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT GS1 | 9287.711 | 9287.711 | -999.0 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:50:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:50:00 | 9287.71 | 9287.71 | 0.326021 | 16.08 | 12.15 | 0.00733646 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 7.9610 | 21.10 | 0.00796546 | 50.3856 | 2311.47 | 0.00 | -999.00 | -999.00 |
| SPLIT GS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT GS2 | 5427.423 | 4345.494 | 0.327871 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 5371.27 | 5354.30 | 0.327871 | 24.92 | 16.14 | 0.00801835 | 12.80 | 11.46 | 0.00800000 | 23.42 | 0.00700114 | 14.70 | 7.9161 | 24.00 | 0.00810579 | 42.9836 | 3815.25 | 0.00 | 5426.50 | 4305.36 |
| SPLIT GS2 HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT GS2 | 9329.353 | 9329.353 | -999.0 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:50:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:50:00 | 9329.35 | 9329.35 | 0.327871 | 16.11 | 12.16 | 0.00734013 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 7.9161 | 21.10 | 0.00796559 | 50.3864 | 2319.52 | 0.00 | -999.00 | -999.00 |
| SPLIT MSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT MSW | 16185.572 | 12959.064 | 0.977770 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 16013.53 | 16013.53 | 0.977770 | 24.95 | 16.13 | 0.00798611 | 12.80 | 11.44 | 0.00798611 | 23.42 | 0.00700114 | 14.70 | 5.3089 | 24.00 | 0.00804133 | 42.6456 | 22574.47 | 0.00 | 16182.82 | 12839.36 |
| SPLIT MSW HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT MSW | 25908.938 | 25908.938 | -999.0 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 25908.94 | 25908.94 | 0.977770 | 17.76 | 12.99 | 0.00750632 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 5.3089 | 21.10 | 0.00792355 | 50.1243 | 9250.25 | 0.00 | -999.00 | -999.00 |
| SPLIT MNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT MNW | 13874.616 | 11108.784 | 0.838166 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 13722.64 | 13722.64 | 0.838166 | 24.94 | 16.11 | 0.00797379 | 12.80 | 11.43 | 0.00797379 | 23.42 | 0.00700114 | 14.70 | 6.1932 | 24.00 | 0.00803801 | 42.6280 | 19394.80 | 0.00 | 13872.25 | 11006.17 |
| SPLIT MNW HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT MNW | 22765.579 | 22765.579 | -999.0 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 22765.58 | 22765.58 | 0.838166 | 17.20 | 12.83 | 0.00757023 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 6.1932 | 21.10 | 0.00806577 | 51.0114 | 8688.95 | 0.00 | -999.00 | -999.00 |
| SPLIT MSE COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT MSE | 13882.995 | 11115.493 | 0.838672 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 13734.38 | 13734.38 | 0.838672 | 24.94 | 16.12 | 0.00798743 | 12.80 | 11.44 | 0.00798743 | 23.42 | 0.00700114 | 14.70 | 6.1894 | 24.00 | 0.00805250 | 42.7041 | 19409.59 | 0.00 | 13880.63 | 11012.82 |
| SPLIT MSE HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT MSE | 22777.286 | 22777.286 | -999.0 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 22777.29 | 22777.29 | 0.838672 | 17.20 | 12.70 | 0.00743732 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 6.1894 | 21.10 | 0.00792376 | 50.1256 | 9275.78 | 0.00 | -999.00 | -999.00 |
| SPLIT MNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT MNE | 11643.633 | 9322.536 | 0.703392 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 11513.94 | 11513.94 | 0.703392 | 24.92 | 16.10 | 0.00796958 | 12.80 | 11.43 | 0.00796958 | 23.42 | 0.00700114 | 14.70 | 7.3798 | 24.00 | 0.00804674 | 42.6737 | 16341.89 | 0.00 | 11641.65 | 9236.42 |
| SPLIT MNE HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT MNE | 19731.355 | 19731.355 | -999.0 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 19731.36 | 19731.36 | 0.703392 | 16.45 | 12.43 | 0.00747511 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 7.3798 | 21.10 | 0.00806557 | 51.0102 | 8714.44 | 0.00 | -999.00 | -999.00 |
| SPLIT MN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT MN1 | 10392.980 | 8321.194 | 0.627840 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 10278.58 | 10278.58 | 0.627840 | 24.91 | 16.11 | 0.00798297 | 12.80 | 11.44 | 0.00798297 | 23.42 | 0.00700114 | 14.70 | 8.2679 | 24.00 | 0.00807146 | 42.8034 | 14625.04 | 0.00 | 10391.21 | 8244.33 |
| SPLIT MN1 HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT MN1 | 18030.357 | 18030.357 | -999.0 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 18030.36 | 18030.36 | 0.627840 | 15.89 | 12.24 | 0.00750575 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 8.2679 | 21.10 | 0.00817643 | 51.7019 | 4840.77 | 0.00 | -999.00 | -999.00 |
| SPLIT MN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT MN2 | 10365.545 | 8299.228 | 0.626183 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 10251.41 | 10251.41 | 0.626183 | 24.91 | 16.11 | 0.00798292 | 12.80 | 11.44 | 0.00798292 | 23.42 | 0.00700114 | 14.70 | 8.2898 | 24.00 | 0.00807167 | 42.8044 | 14587.35 | 0.00 | 10363.78 | 8222.57 |
| SPLIT MN2 HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT MN2 | 17993.044 | 17993.044 | -999.0 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 17993.04 | 17993.04 | 0.626183 | 15.88 | 12.23 | 0.00750395 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 8.2898 | 21.10 | 0.00817641 | 51.7018 | 4841.37 | 0.00 | -999.00 | -999.00 |
| SPLIT MS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT MS1 | 12836.314 | 10277.462 | 0.775442 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 12701.23 | 12699.39 | 0.775442 | 24.93 | 16.13 | 0.00800084 | 12.80 | 11.46 | 0.00800000 | 23.42 | 0.00700114 | 14.70 | 6.6941 | 24.00 | 0.00807256 | 42.8094 | 17973.49 | 0.00 | 12834.13 | 10182.53 |
| SPLIT MS1 HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT MS1 | 21353.678 | 21353.678 | -999.0 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 21353.68 | 21353.68 | 0.775442 | 16.88 | 12.53 | 0.00739457 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 6.6941 | 21.10 | 0.00792046 | 50.1048 | 5389.21 | 0.00 | -999.00 | -999.00 |
| SPLIT MS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT MS2 | 12803.937 | 10251.539 | 0.773486 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 12669.20 | 12667.15 | 0.773486 | 24.93 | 16.13 | 0.00800094 | 12.80 | 11.46 | 0.00800000 | 23.42 | 0.00700114 | 14.70 | 6.7111 | 24.00 | 0.00807286 | 42.8109 | 17929.17 | 0.00 | 12801.76 | 10156.85 |
| SPLIT MS2 HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT MS2 | 21309.643 | 21309.643 | -999.0 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 21309.64 | 21309.64 | 0.773486 | 16.87 | 12.52 | 0.00739325 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 6.7111 | 21.10 | 0.00792047 | 50.1048 | 5389.81 | 0.00 | -999.00 | -999.00 |
| SPLIT TSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT TSW | 8778.482 | 7028.538 | 0.530308 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 8684.72 | 8684.72 | 0.530308 | 24.96 | 16.12 | 0.00798076 | 12.80 | 11.44 | 0.00798076 | 23.42 | 0.00700114 | 14.70 | 4.8942 | 24.00 | 0.00803117 | 42.5922 | 6114.21 | 0.00 | 8776.99 | 6963.61 |
| SPLIT TSW HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT TSW | 13887.094 | 13887.094 | -999.0 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 13887.09 | 13887.09 | 0.530308 | 18.02 | 13.14 | 0.00755582 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 4.8942 | 21.10 | 0.00794133 | 50.2355 | 3991.25 | 0.00 | -999.00 | -999.00 |
| SPLIT TNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT TNW | 7688.725 | 6156.018 | 0.464476 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 7604.69 | 7604.69 | 0.464476 | 24.95 | 16.11 | 0.00796960 | 12.80 | 11.43 | 0.00796960 | 23.42 | 0.00700114 | 14.70 | 5.5879 | 24.00 | 0.00802692 | 42.5699 | 5368.32 | 0.00 | 7687.42 | 6099.15 |
| SPLIT TNW HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT TNW | 12404.777 | 12404.777 | -999.0 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 12404.78 | 12404.78 | 0.464476 | 17.58 | 12.99 | 0.00757769 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 5.5879 | 21.10 | 0.00802236 | 50.7405 | 3845.60 | 0.00 | -999.00 | -999.00 |
| SPLIT TSE COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT TSE | 7097.466 | 5682.623 | 0.428758 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 7020.77 | 7020.77 | 0.428758 | 24.95 | 16.12 | 0.00797879 | 12.80 | 11.43 | 0.00797879 | 23.42 | 0.00700114 | 14.70 | 6.0534 | 24.00 | 0.00804179 | 42.6479 | 4963.37 | 0.00 | 7096.26 | 5630.13 |
| SPLIT TSE HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT TSE | 11600.798 | 11600.798 | -999.0 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 11600.80 | 11600.80 | 0.428758 | 17.29 | 12.76 | 0.00746465 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 6.0534 | 21.10 | 0.00794147 | 50.2364 | 4001.03 | 0.00 | -999.00 | -999.00 |
| SPLIT TNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT TNE | 6031.482 | 4829.138 | 0.364362 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 5963.75 | 5963.75 | 0.364362 | 24.93 | 16.10 | 0.00796131 | 12.80 | 11.42 | 0.00796131 | 23.42 | 0.00700114 | 14.70 | 7.1233 | 24.00 | 0.00803495 | 42.6119 | 4230.29 | 0.00 | 6030.46 | 4784.53 |
| SPLIT TNE HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT TNE | 10150.855 | 10150.855 | -999.0 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 10150.85 | 10150.85 | 0.364362 | 16.61 | 12.48 | 0.00745545 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 7.1233 | 21.10 | 0.00802231 | 50.7402 | 3855.38 | 0.00 | -999.00 | -999.00 |
| SPLIT TN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT TN1 | 5670.973 | 4540.494 | 0.342583 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 5608.42 | 5608.42 | 0.342583 | 24.93 | 16.11 | 0.00797513 | 12.80 | 11.43 | 0.00797513 | 23.42 | 0.00700114 | 14.70 | 7.5761 | 24.00 | 0.00805497 | 42.7169 | 3983.40 | 0.00 | 5670.01 | 4498.55 |
| SPLIT TN1 HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT TN1 | 9660.508 | 9660.508 | -999.0 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 9660.51 | 9660.51 | 0.342583 | 16.33 | 12.37 | 0.00746052 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 7.5761 | 21.10 | 0.00806678 | 51.0176 | 2682.59 | 0.00 | -999.00 | -999.00 |
| SPLIT TN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT TN2 | 5628.114 | 4506.179 | 0.339994 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 5565.99 | 5565.99 | 0.339994 | 24.93 | 16.10 | 0.00797497 | 12.80 | 11.43 | 0.00797497 | 23.42 | 0.00700114 | 14.70 | 7.6338 | 24.00 | 0.00805545 | 42.7194 | 3954.10 | 0.00 | 5627.16 | 4464.56 |
| SPLIT TN2 HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT TN2 | 9602.217 | 9602.217 | -999.0 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 9602.22 | 9602.22 | 0.339994 | 16.29 | 12.35 | 0.00745590 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 7.6338 | 21.10 | 0.00806678 | 51.0175 | 2682.84 | 0.00 | -999.00 | -999.00 |
| SPLIT TS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT TS1 | 6801.195 | 5445.413 | 0.410860 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 6729.06 | 6729.06 | 0.410860 | 24.94 | 16.13 | 0.00799190 | 12.80 | 11.45 | 0.00799190 | 23.42 | 0.00700114 | 14.70 | 6.3171 | 24.00 | 0.00805871 | 42.7367 | 4759.25 | 0.00 | 6800.04 | 5395.11 |
| SPLIT TS1 HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT TS1 | 11197.809 | 11197.809 | -999.0 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 11197.81 | 11197.81 | 0.410860 | 17.12 | 12.68 | 0.00745184 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 6.3171 | 21.10 | 0.00794998 | 50.2892 | 2827.90 | 0.00 | -999.00 | -999.00 |
| SPLIT TS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT TS2 | 6757.973 | 5410.807 | 0.408249 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 6686.27 | 6686.27 | 0.408249 | 24.94 | 16.13 | 0.00799198 | 12.80 | 11.45 | 0.00799198 | 23.42 | 0.00700114 | 14.70 | 6.3575 | 24.00 | 0.00805925 | 42.7395 | 4729.55 | 0.00 | 6756.82 | 5360.83 |
| SPLIT TS2 HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT TS2 | 11139.025 | 11139.025 | -999.0 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 11139.02 | 11139.02 | 0.408249 | 17.09 | 12.67 | 0.00744866 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 6.3575 | 21.10 | 0.00794998 | 50.2893 | 2828.15 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 09:14:30
Coils| Coil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
| SPLIT GSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT GSW | G SW APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 6451.510 | 5165.435 | 0.389736 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7057 | 1004.8586 | 1.1854 | SPLIT GSW SUPPLY FAN | Fan:OnOff | 0.389736 | 0.46200802 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | Sensible | 6383.11 | 6383.11 | 0.9894 | 0.46200802 | 0.389736 | 24.93 | 16.13 | 0.00799681 | 45423.3 | 12.80 | 11.45 | 0.00799681 | 33051.8 | -999.0 | -999.00 | -999.00 | -999.00 | 436.546 | 5946.56 | 23.42 | 0.00700114 | 14.70 | 0.02595455 | 6.6595 | 24.05 | 0.00806785 | 24.00 | 0.00806785 | 42.7847 | 4515.54 | 0.00 | 6450.41 | 5117.72 | 0.44376220 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 15.40 | 14.57 | 0.01000719 | 40786.6 | |
| SPLIT GSW HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT GSW | G SW APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 10722.174 | 10722.174 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | SPLIT GSW SUPPLY FAN | Fan:OnOff | 0.389736 | 0.46200802 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:50:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:50:00 | Sensible | 10722.17 | 10722.17 | 1.0000 | 0.46200802 | 0.389736 | 16.90 | 12.58 | 0.00743573 | 35816.2 | 40.00 | 21.00 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10722.17 | -41.90 | 0.00006450 | -41.90 | 0.02595455 | 6.6595 | 21.10 | 0.00796164 | 21.10 | 0.00796164 | 50.3618 | 3328.10 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT GNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT GNW | G NW APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 5281.464 | 4228.632 | 0.319053 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.6700 | 1004.8586 | 1.1854 | SPLIT GNW SUPPLY FAN | Fan:OnOff | 0.319053 | 0.37821824 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | Sensible | 5222.84 | 5222.84 | 0.9889 | 0.37821824 | 0.319053 | 24.91 | 16.10 | 0.00797762 | 45351.8 | 12.80 | 11.43 | 0.00797762 | 33003.3 | -999.0 | -999.00 | -999.00 | -999.00 | 357.374 | 4865.47 | 23.42 | 0.00700114 | 14.70 | 0.02595455 | 8.1349 | 24.03 | 0.00806409 | 24.00 | 0.00806409 | 42.7647 | 3714.03 | 0.00 | 5280.57 | 4189.57 | 0.36328148 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 15.40 | 14.57 | 0.01000719 | 40786.6 | |
| SPLIT GNW HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT GNW | G NW APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 9130.809 | 9130.809 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | SPLIT GNW SUPPLY FAN | Fan:OnOff | 0.319053 | 0.37821824 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:50:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:50:00 | Sensible | 9130.81 | 9130.81 | 1.0000 | 0.37821824 | 0.319053 | 15.98 | 12.15 | 0.00737950 | 34727.3 | 40.00 | 21.00 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9130.81 | -41.90 | 0.00006450 | -41.90 | 0.02595455 | 8.1349 | 21.10 | 0.00802726 | 21.10 | 0.00802726 | 50.7713 | 3208.83 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT OFFICE COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT OFFICE | OFFICE | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 6782.981 | 5430.829 | 0.409760 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.5040 | 1004.8586 | 1.1854 | SPLIT OFFICE SUPPLY FAN | Fan:OnOff | 0.409760 | 0.48574547 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 12:20:00 | Sensible | 6685.81 | 6685.81 | 0.9857 | 0.48574547 | 0.409760 | 24.68 | 15.94 | 0.00788832 | 44892.2 | 12.80 | 11.34 | 0.00788832 | 32777.9 | -999.0 | -999.00 | -999.00 | -999.00 | 458.975 | 6226.84 | 21.79 | 0.00699871 | 14.08 | 0.03810604 | 9.2996 | 23.96 | 0.00797954 | 23.90 | 0.00798451 | 42.6025 | 4562.49 | 0.00 | 6781.83 | 5380.66 | 0.46656220 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 15.40 | 14.57 | 0.01000719 | 40786.6 | |
| SPLIT OFFICE HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT OFFICE | OFFICE | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 12084.906 | 12084.906 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | SPLIT OFFICE SUPPLY FAN | Fan:OnOff | 0.409760 | 0.48574547 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 18:50:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 18:50:00 | Sensible | 12084.91 | 12084.91 | 1.0000 | 0.48574547 | 0.409760 | 15.24 | 11.70 | 0.00723226 | 33607.3 | 40.00 | 21.00 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 12084.91 | -41.90 | 0.00006450 | -41.90 | 0.03810604 | 9.2996 | 21.10 | 0.00796718 | 21.10 | 0.00796718 | 50.3964 | 3836.38 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT GNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT GNE | G NE APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 4647.892 | 3721.359 | 0.280779 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.6669 | 1004.8586 | 1.1854 | SPLIT GNE SUPPLY FAN | Fan:OnOff | 0.280779 | 0.33284661 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | Sensible | 4595.61 | 4595.61 | 0.9888 | 0.33284661 | 0.280779 | 24.89 | 16.09 | 0.00797597 | 45330.8 | 12.80 | 11.43 | 0.00797597 | 32999.2 | -999.0 | -999.00 | -999.00 | -999.00 | 314.503 | 4281.11 | 23.42 | 0.00700114 | 14.70 | 0.02595455 | 9.2438 | 24.02 | 0.00807526 | 24.00 | 0.00807526 | 42.8232 | 3280.01 | 0.00 | 4647.10 | 3686.98 | 0.31970168 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 15.40 | 14.57 | 0.01000719 | 40786.6 | |
| SPLIT GNE HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT GNE | G NE APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 8269.121 | 8269.121 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | SPLIT GNE SUPPLY FAN | Fan:OnOff | 0.280779 | 0.33284661 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:50:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:50:00 | Sensible | 8269.12 | 8269.12 | 1.0000 | 0.33284661 | 0.280779 | 15.28 | 11.77 | 0.00729113 | 33792.2 | 40.00 | 21.00 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8269.12 | -41.90 | 0.00006450 | -41.90 | 0.02595455 | 9.2438 | 21.10 | 0.00802718 | 21.10 | 0.00802718 | 50.7707 | 3214.07 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT GN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT GN1 | G N1 APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 4154.707 | 3326.488 | 0.250986 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.6986 | 1004.8586 | 1.1854 | SPLIT GN1 SUPPLY FAN | Fan:OnOff | 0.250986 | 0.29752851 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | Sensible | 4108.60 | 4108.60 | 0.9889 | 0.29752851 | 0.250986 | 24.87 | 16.10 | 0.00799299 | 45353.1 | 12.80 | 11.45 | 0.00799299 | 33042.1 | -999.0 | -999.00 | -999.00 | -999.00 | 281.131 | 3827.47 | 23.42 | 0.00700114 | 14.70 | 0.02595455 | 10.3410 | 24.01 | 0.00810739 | 24.00 | 0.00810739 | 42.9917 | 2941.57 | 0.00 | 4154.00 | 3295.76 | 0.28577838 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 15.40 | 14.57 | 0.01000719 | 40786.6 | |
| SPLIT GN1 HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT GN1 | G N1 APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 7598.358 | 7598.358 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | SPLIT GN1 SUPPLY FAN | Fan:OnOff | 0.250986 | 0.29752851 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:50:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:50:00 | Sensible | 7598.36 | 7598.36 | 1.0000 | 0.29752851 | 0.250986 | 14.59 | 11.44 | 0.00725005 | 32984.3 | 40.00 | 21.00 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 7598.36 | -41.90 | 0.00006450 | -41.90 | 0.02595455 | 10.3410 | 21.10 | 0.00807882 | 21.10 | 0.00807882 | 51.0930 | 2191.15 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT GN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT GN2 | G N2 APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 4146.070 | 3319.573 | 0.250464 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.6984 | 1004.8586 | 1.1854 | SPLIT GN2 SUPPLY FAN | Fan:OnOff | 0.250464 | 0.29691001 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | Sensible | 4100.04 | 4100.04 | 0.9889 | 0.29691001 | 0.250464 | 24.87 | 16.10 | 0.00799290 | 45352.5 | 12.80 | 11.45 | 0.00799290 | 33041.9 | -999.0 | -999.00 | -999.00 | -999.00 | 280.547 | 3819.49 | 23.42 | 0.00700114 | 14.70 | 0.02595455 | 10.3626 | 24.01 | 0.00810756 | 24.00 | 0.00810756 | 42.9925 | 2935.64 | 0.00 | 4145.36 | 3288.91 | 0.28518430 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 15.40 | 14.57 | 0.01000719 | 40786.6 | |
| SPLIT GN2 HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT GN2 | G N2 APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 7586.612 | 7586.612 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | SPLIT GN2 SUPPLY FAN | Fan:OnOff | 0.250464 | 0.29691001 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:50:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:50:00 | Sensible | 7586.61 | 7586.61 | 1.0000 | 0.29691001 | 0.250464 | 14.57 | 11.43 | 0.00724832 | 32966.1 | 40.00 | 21.00 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 7586.61 | -41.90 | 0.00006450 | -41.90 | 0.02595455 | 10.3626 | 21.10 | 0.00807881 | 21.10 | 0.00807881 | 51.0929 | 2191.29 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT GS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT GS1 | G S1 APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 5396.805 | 4320.980 | 0.326021 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7460 | 1004.8586 | 1.1854 | SPLIT GS1 SUPPLY FAN | Fan:OnOff | 0.326021 | 0.38647807 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | Sensible | 5340.98 | 5323.94 | 0.9897 | 0.38647807 | 0.326021 | 24.92 | 16.14 | 0.00801852 | 45461.2 | 12.80 | 11.46 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 365.179 | 4975.80 | 23.42 | 0.00700114 | 14.70 | 0.02595455 | 7.9610 | 24.04 | 0.00810652 | 24.00 | 0.00810652 | 42.9874 | 3794.34 | 0.00 | 5395.89 | 4281.07 | 0.37121511 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 15.40 | 14.57 | 0.01000719 | 40786.6 | |
| SPLIT GS1 HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT GS1 | G S1 APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 9287.711 | 9287.711 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | SPLIT GS1 SUPPLY FAN | Fan:OnOff | 0.326021 | 0.38647807 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:50:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:50:00 | Sensible | 9287.71 | 9287.71 | 1.0000 | 0.38647807 | 0.326021 | 16.08 | 12.15 | 0.00733646 | 34729.8 | 40.00 | 21.00 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9287.71 | -41.90 | 0.00006450 | -41.90 | 0.02595455 | 7.9610 | 21.10 | 0.00796546 | 21.10 | 0.00796546 | 50.3856 | 2311.47 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT GS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT GS2 | G S2 APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 5427.423 | 4345.494 | 0.327871 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7457 | 1004.8586 | 1.1854 | SPLIT GS2 SUPPLY FAN | Fan:OnOff | 0.327871 | 0.38867069 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | Sensible | 5371.27 | 5354.30 | 0.9897 | 0.38867069 | 0.327871 | 24.92 | 16.14 | 0.00801835 | 45461.1 | 12.80 | 11.46 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 367.250 | 5004.02 | 23.42 | 0.00700114 | 14.70 | 0.02595455 | 7.9161 | 24.04 | 0.00810579 | 24.00 | 0.00810579 | 42.9836 | 3815.25 | 0.00 | 5426.50 | 4305.36 | 0.37332114 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 15.40 | 14.57 | 0.01000719 | 40786.6 | |
| SPLIT GS2 HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT GS2 | G S2 APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 9329.353 | 9329.353 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | SPLIT GS2 SUPPLY FAN | Fan:OnOff | 0.327871 | 0.38867069 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:50:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:50:00 | Sensible | 9329.35 | 9329.35 | 1.0000 | 0.38867069 | 0.327871 | 16.11 | 12.16 | 0.00734013 | 34767.9 | 40.00 | 21.00 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9329.35 | -41.90 | 0.00006450 | -41.90 | 0.02595455 | 7.9161 | 21.10 | 0.00796559 | 21.10 | 0.00796559 | 50.3864 | 2319.52 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT MSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT MSW | M SW APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 16185.572 | 12959.064 | 0.977770 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.6858 | 1004.8586 | 1.1854 | SPLIT MSW SUPPLY FAN | Fan:OnOff | 0.977770 | 1.15908749 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | Sensible | 16013.53 | 16013.53 | 0.9894 | 1.15908749 | 0.977770 | 24.95 | 16.13 | 0.00798611 | 45418.7 | 12.80 | 11.44 | 0.00798611 | 33024.8 | -999.0 | -999.00 | -999.00 | -999.00 | 1095.208 | 14918.32 | 23.42 | 0.00700114 | 14.70 | 0.05190911 | 5.3089 | 24.06 | 0.00804133 | 24.00 | 0.00804133 | 42.6456 | 22574.47 | 0.00 | 16182.82 | 12839.36 | 1.11331230 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 15.40 | 14.57 | 0.01000719 | 40786.6 | |
| SPLIT MSW HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT MSW | M SW APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 25908.938 | 25908.938 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | SPLIT MSW SUPPLY FAN | Fan:OnOff | 0.977770 | 1.15908749 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | Sensible | 25908.94 | 25908.94 | 1.0000 | 1.15908749 | 0.977770 | 17.76 | 12.99 | 0.00750632 | 36861.8 | 40.00 | 21.00 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 25908.94 | -41.90 | 0.00006450 | -41.90 | 0.05190911 | 5.3089 | 21.10 | 0.00792355 | 21.10 | 0.00792355 | 50.1243 | 9250.25 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT MNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT MNW | M NW APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 13874.616 | 11108.784 | 0.838166 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.6629 | 1004.8586 | 1.1854 | SPLIT MNW SUPPLY FAN | Fan:OnOff | 0.838166 | 0.99359438 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | Sensible | 13722.64 | 13722.64 | 0.9890 | 0.99359438 | 0.838166 | 24.94 | 16.11 | 0.00797379 | 45372.1 | 12.80 | 11.43 | 0.00797379 | 32993.7 | -999.0 | -999.00 | -999.00 | -999.00 | 938.836 | 12783.81 | 23.42 | 0.00700114 | 14.70 | 0.05190911 | 6.1932 | 24.05 | 0.00803801 | 24.00 | 0.00803801 | 42.6280 | 19394.80 | 0.00 | 13872.25 | 11006.17 | 0.95435491 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 15.40 | 14.57 | 0.01000719 | 40786.6 | |
| SPLIT MNW HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT MNW | M NW APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 22765.579 | 22765.579 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | SPLIT MNW SUPPLY FAN | Fan:OnOff | 0.838166 | 0.99359438 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | Sensible | 22765.58 | 22765.58 | 1.0000 | 0.99359438 | 0.838166 | 17.20 | 12.83 | 0.00757023 | 36456.4 | 40.00 | 21.00 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 22765.58 | -41.90 | 0.00006450 | -41.90 | 0.05190911 | 6.1932 | 21.10 | 0.00806577 | 21.10 | 0.00806577 | 51.0114 | 8688.95 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT MSE COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT MSE | M SE APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 13882.995 | 11115.493 | 0.838672 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.6882 | 1004.8586 | 1.1854 | SPLIT MSE SUPPLY FAN | Fan:OnOff | 0.838672 | 0.99419441 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | Sensible | 13734.38 | 13734.38 | 0.9893 | 0.99419441 | 0.838672 | 24.94 | 16.12 | 0.00798743 | 45408.2 | 12.80 | 11.44 | 0.00798743 | 33028.1 | -999.0 | -999.00 | -999.00 | -999.00 | 939.403 | 12794.98 | 23.42 | 0.00700114 | 14.70 | 0.05190911 | 6.1894 | 24.05 | 0.00805250 | 24.00 | 0.00805250 | 42.7041 | 19409.59 | 0.00 | 13880.63 | 11012.82 | 0.95493125 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 15.40 | 14.57 | 0.01000719 | 40786.6 | |
| SPLIT MSE HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT MSE | M SE APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 22777.286 | 22777.286 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | SPLIT MSE SUPPLY FAN | Fan:OnOff | 0.838672 | 0.99419441 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | Sensible | 22777.29 | 22777.29 | 1.0000 | 0.99419441 | 0.838672 | 17.20 | 12.70 | 0.00743732 | 36121.8 | 40.00 | 21.00 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 22777.29 | -41.90 | 0.00006450 | -41.90 | 0.05190911 | 6.1894 | 21.10 | 0.00792376 | 21.10 | 0.00792376 | 50.1256 | 9275.78 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT MNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT MNE | M NE APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 11643.633 | 9322.536 | 0.703392 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.6550 | 1004.8586 | 1.1854 | SPLIT MNE SUPPLY FAN | Fan:OnOff | 0.703392 | 0.83382838 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | Sensible | 11513.94 | 11513.94 | 0.9889 | 0.83382838 | 0.703392 | 24.92 | 16.10 | 0.00796958 | 45345.7 | 12.80 | 11.43 | 0.00796958 | 32983.0 | -999.0 | -999.00 | -999.00 | -999.00 | 787.875 | 10726.06 | 23.42 | 0.00700114 | 14.70 | 0.05190911 | 7.3798 | 24.04 | 0.00804674 | 24.00 | 0.00804674 | 42.6737 | 16341.89 | 0.00 | 11641.65 | 9236.42 | 0.80089846 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 15.40 | 14.57 | 0.01000719 | 40786.6 | |
| SPLIT MNE HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT MNE | M NE APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 19731.355 | 19731.355 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | SPLIT MNE SUPPLY FAN | Fan:OnOff | 0.703392 | 0.83382838 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | Sensible | 19731.36 | 19731.36 | 1.0000 | 0.83382838 | 0.703392 | 16.45 | 12.43 | 0.00747511 | 35453.9 | 40.00 | 21.00 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 19731.36 | -41.90 | 0.00006450 | -41.90 | 0.05190911 | 7.3798 | 21.10 | 0.00806557 | 21.10 | 0.00806557 | 51.0102 | 8714.44 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT MN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT MN1 | M N1 APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 10392.980 | 8321.194 | 0.627840 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.6799 | 1004.8586 | 1.1854 | SPLIT MN1 SUPPLY FAN | Fan:OnOff | 0.627840 | 0.74426612 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | Sensible | 10278.58 | 10278.58 | 0.9890 | 0.74426612 | 0.627840 | 24.91 | 16.11 | 0.00798297 | 45365.1 | 12.80 | 11.44 | 0.00798297 | 33016.8 | -999.0 | -999.00 | -999.00 | -999.00 | 703.249 | 9575.33 | 23.42 | 0.00700114 | 14.70 | 0.05190911 | 8.2679 | 24.03 | 0.00807146 | 24.00 | 0.00807146 | 42.8034 | 14625.04 | 0.00 | 10391.21 | 8244.33 | 0.71487324 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 15.40 | 14.57 | 0.01000719 | 40786.6 | |
| SPLIT MN1 HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT MN1 | M N1 APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 18030.357 | 18030.357 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | SPLIT MN1 SUPPLY FAN | Fan:OnOff | 0.627840 | 0.74426612 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | Sensible | 18030.36 | 18030.36 | 1.0000 | 0.74426612 | 0.627840 | 15.89 | 12.24 | 0.00750575 | 34961.5 | 40.00 | 21.00 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 18030.36 | -41.90 | 0.00006450 | -41.90 | 0.05190911 | 8.2679 | 21.10 | 0.00817643 | 21.10 | 0.00817643 | 51.7019 | 4840.77 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT MN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT MN2 | M N2 APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 10365.545 | 8299.228 | 0.626183 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.6799 | 1004.8586 | 1.1854 | SPLIT MN2 SUPPLY FAN | Fan:OnOff | 0.626183 | 0.74230141 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | Sensible | 10251.41 | 10251.41 | 0.9890 | 0.74230141 | 0.626183 | 24.91 | 16.11 | 0.00798292 | 45364.7 | 12.80 | 11.44 | 0.00798292 | 33016.7 | -999.0 | -999.00 | -999.00 | -999.00 | 701.392 | 9550.02 | 23.42 | 0.00700114 | 14.70 | 0.05190911 | 8.2898 | 24.03 | 0.00807167 | 24.00 | 0.00807167 | 42.8044 | 14587.35 | 0.00 | 10363.78 | 8222.57 | 0.71298612 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 15.40 | 14.57 | 0.01000719 | 40786.6 | |
| SPLIT MN2 HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT MN2 | M N2 APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 17993.044 | 17993.044 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | SPLIT MN2 SUPPLY FAN | Fan:OnOff | 0.626183 | 0.74230141 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | Sensible | 17993.04 | 17993.04 | 1.0000 | 0.74230141 | 0.626183 | 15.88 | 12.23 | 0.00750395 | 34942.9 | 40.00 | 21.00 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 17993.04 | -41.90 | 0.00006450 | -41.90 | 0.05190911 | 8.2898 | 21.10 | 0.00817641 | 21.10 | 0.00817641 | 51.7018 | 4841.37 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT MS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT MS1 | M S1 APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 12836.314 | 10277.462 | 0.775442 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7132 | 1004.8586 | 1.1854 | SPLIT MS1 SUPPLY FAN | Fan:OnOff | 0.775442 | 0.91923909 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | Sensible | 12701.23 | 12699.39 | 0.9895 | 0.91923909 | 0.775442 | 24.93 | 16.13 | 0.00800084 | 45434.7 | 12.80 | 11.46 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 868.578 | 11832.65 | 23.42 | 0.00700114 | 14.70 | 0.05190911 | 6.6941 | 24.05 | 0.00807256 | 24.00 | 0.00807256 | 42.8094 | 17973.49 | 0.00 | 12834.13 | 10182.53 | 0.88293609 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 15.40 | 14.57 | 0.01000719 | 40786.6 | |
| SPLIT MS1 HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT MS1 | M S1 APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 21353.678 | 21353.678 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | SPLIT MS1 SUPPLY FAN | Fan:OnOff | 0.775442 | 0.91923909 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | Sensible | 21353.68 | 21353.68 | 1.0000 | 0.91923909 | 0.775442 | 16.88 | 12.53 | 0.00739457 | 35689.8 | 40.00 | 21.00 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 21353.68 | -41.90 | 0.00006450 | -41.90 | 0.05190911 | 6.6941 | 21.10 | 0.00792046 | 21.10 | 0.00792046 | 50.1048 | 5389.21 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT MS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT MS2 | M S2 APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 12803.937 | 10251.539 | 0.773486 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7133 | 1004.8586 | 1.1854 | SPLIT MS2 SUPPLY FAN | Fan:OnOff | 0.773486 | 0.91692049 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | Sensible | 12669.20 | 12667.15 | 0.9895 | 0.91692049 | 0.773486 | 24.93 | 16.13 | 0.00800094 | 45434.7 | 12.80 | 11.46 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 866.388 | 11802.81 | 23.42 | 0.00700114 | 14.70 | 0.05190911 | 6.7111 | 24.05 | 0.00807286 | 24.00 | 0.00807286 | 42.8109 | 17929.17 | 0.00 | 12801.76 | 10156.85 | 0.88070906 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 15.40 | 14.57 | 0.01000719 | 40786.6 | |
| SPLIT MS2 HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT MS2 | M S2 APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 21309.643 | 21309.643 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | SPLIT MS2 SUPPLY FAN | Fan:OnOff | 0.773486 | 0.91692049 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | Sensible | 21309.64 | 21309.64 | 1.0000 | 0.91692049 | 0.773486 | 16.87 | 12.52 | 0.00739325 | 35675.5 | 40.00 | 21.00 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 21309.64 | -41.90 | 0.00006450 | -41.90 | 0.05190911 | 6.7111 | 21.10 | 0.00792047 | 21.10 | 0.00792047 | 50.1048 | 5389.81 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT TSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT TSW | T SW APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 8778.482 | 7028.538 | 0.530308 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.6758 | 1004.8586 | 1.1854 | SPLIT TSW SUPPLY FAN | Fan:OnOff | 0.530308 | 0.62864805 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | Sensible | 8684.72 | 8684.72 | 0.9893 | 0.62864805 | 0.530308 | 24.96 | 16.12 | 0.00798076 | 45411.0 | 12.80 | 11.44 | 0.00798076 | 33011.2 | -999.0 | -999.00 | -999.00 | -999.00 | 594.002 | 8090.72 | 23.42 | 0.00700114 | 14.70 | 0.02595455 | 4.8942 | 24.07 | 0.00803117 | 24.00 | 0.00803117 | 42.5922 | 6114.21 | 0.00 | 8776.99 | 6963.61 | 0.60382120 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 15.40 | 14.57 | 0.01000719 | 40786.6 | |
| SPLIT TSW HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT TSW | T SW APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 13887.094 | 13887.094 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | SPLIT TSW SUPPLY FAN | Fan:OnOff | 0.530308 | 0.62864805 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | Sensible | 13887.09 | 13887.09 | 1.0000 | 0.62864805 | 0.530308 | 18.02 | 13.14 | 0.00755582 | 37253.3 | 40.00 | 21.00 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 13887.09 | -41.90 | 0.00006450 | -41.90 | 0.02595455 | 4.8942 | 21.10 | 0.00794133 | 21.10 | 0.00794133 | 50.2355 | 3991.25 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT TNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT TNW | T NW APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 7688.725 | 6156.018 | 0.464476 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.6551 | 1004.8586 | 1.1854 | SPLIT TNW SUPPLY FAN | Fan:OnOff | 0.464476 | 0.55060793 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | Sensible | 7604.69 | 7604.69 | 0.9891 | 0.55060793 | 0.464476 | 24.95 | 16.11 | 0.00796960 | 45375.2 | 12.80 | 11.43 | 0.00796960 | 32983.1 | -999.0 | -999.00 | -999.00 | -999.00 | 520.263 | 7084.43 | 23.42 | 0.00700114 | 14.70 | 0.02595455 | 5.5879 | 24.06 | 0.00802692 | 24.00 | 0.00802692 | 42.5699 | 5368.32 | 0.00 | 7687.42 | 6099.15 | 0.52886308 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 15.40 | 14.57 | 0.01000719 | 40786.6 | |
| SPLIT TNW HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT TNW | T NW APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 12404.777 | 12404.777 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | SPLIT TNW SUPPLY FAN | Fan:OnOff | 0.464476 | 0.55060793 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | Sensible | 12404.78 | 12404.78 | 1.0000 | 0.55060793 | 0.464476 | 17.58 | 12.99 | 0.00757769 | 36863.8 | 40.00 | 21.00 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 12404.78 | -41.90 | 0.00006450 | -41.90 | 0.02595455 | 5.5879 | 21.10 | 0.00802236 | 21.10 | 0.00802236 | 50.7405 | 3845.60 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT TSE COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT TSE | T SE APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 7097.466 | 5682.623 | 0.428758 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.6722 | 1004.8586 | 1.1854 | SPLIT TSE SUPPLY FAN | Fan:OnOff | 0.428758 | 0.50826646 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | Sensible | 7020.77 | 7020.77 | 0.9892 | 0.50826646 | 0.428758 | 24.95 | 16.12 | 0.00797879 | 45393.4 | 12.80 | 11.43 | 0.00797879 | 33006.3 | -999.0 | -999.00 | -999.00 | -999.00 | 480.255 | 6540.52 | 23.42 | 0.00700114 | 14.70 | 0.02595455 | 6.0534 | 24.06 | 0.00804179 | 24.00 | 0.00804179 | 42.6479 | 4963.37 | 0.00 | 7096.26 | 5630.13 | 0.48819378 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 15.40 | 14.57 | 0.01000719 | 40786.6 | |
| SPLIT TSE HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT TSE | T SE APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 11600.798 | 11600.798 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | SPLIT TSE SUPPLY FAN | Fan:OnOff | 0.428758 | 0.50826646 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | Sensible | 11600.80 | 11600.80 | 1.0000 | 0.50826646 | 0.428758 | 17.29 | 12.76 | 0.00746465 | 36278.3 | 40.00 | 21.00 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 11600.80 | -41.90 | 0.00006450 | -41.90 | 0.02595455 | 6.0534 | 21.10 | 0.00794147 | 21.10 | 0.00794147 | 50.2364 | 4001.03 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT TNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT TNE | T NE APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 6031.482 | 4829.138 | 0.364362 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.6397 | 1004.8586 | 1.1854 | SPLIT TNE SUPPLY FAN | Fan:OnOff | 0.364362 | 0.43192883 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | Sensible | 5963.75 | 5963.75 | 0.9888 | 0.43192883 | 0.364362 | 24.93 | 16.10 | 0.00796131 | 45332.3 | 12.80 | 11.42 | 0.00796131 | 32962.2 | -999.0 | -999.00 | -999.00 | -999.00 | 408.125 | 5555.63 | 23.42 | 0.00700114 | 14.70 | 0.02595455 | 7.1233 | 24.05 | 0.00803495 | 24.00 | 0.00803495 | 42.6119 | 4230.29 | 0.00 | 6030.46 | 4784.53 | 0.41487091 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 15.40 | 14.57 | 0.01000719 | 40786.6 | |
| SPLIT TNE HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT TNE | T NE APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 10150.855 | 10150.855 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | SPLIT TNE SUPPLY FAN | Fan:OnOff | 0.364362 | 0.43192883 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | Sensible | 10150.85 | 10150.85 | 1.0000 | 0.43192883 | 0.364362 | 16.61 | 12.48 | 0.00745545 | 35568.7 | 40.00 | 21.00 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10150.85 | -41.90 | 0.00006450 | -41.90 | 0.02595455 | 7.1233 | 21.10 | 0.00802231 | 21.10 | 0.00802231 | 50.7402 | 3855.38 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT TN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT TN1 | T N1 APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 5670.973 | 4540.494 | 0.342583 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.6654 | 1004.8586 | 1.1854 | SPLIT TN1 SUPPLY FAN | Fan:OnOff | 0.342583 | 0.40611192 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | Sensible | 5608.42 | 5608.42 | 0.9890 | 0.40611192 | 0.342583 | 24.93 | 16.11 | 0.00797513 | 45361.5 | 12.80 | 11.43 | 0.00797513 | 32997.0 | -999.0 | -999.00 | -999.00 | -999.00 | 383.730 | 5224.69 | 23.42 | 0.00700114 | 14.70 | 0.02595455 | 7.5761 | 24.05 | 0.00805497 | 24.00 | 0.00805497 | 42.7169 | 3983.40 | 0.00 | 5670.01 | 4498.55 | 0.39007357 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 15.40 | 14.57 | 0.01000719 | 40786.6 | |
| SPLIT TN1 HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT TN1 | T N1 APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 9660.508 | 9660.508 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | SPLIT TN1 SUPPLY FAN | Fan:OnOff | 0.342583 | 0.40611192 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | Sensible | 9660.51 | 9660.51 | 1.0000 | 0.40611192 | 0.342583 | 16.33 | 12.37 | 0.00746052 | 35291.0 | 40.00 | 21.00 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9660.51 | -41.90 | 0.00006450 | -41.90 | 0.02595455 | 7.5761 | 21.10 | 0.00806678 | 21.10 | 0.00806678 | 51.0176 | 2682.59 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT TN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT TN2 | T N2 APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 5628.114 | 4506.179 | 0.339994 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.6651 | 1004.8586 | 1.1854 | SPLIT TN2 SUPPLY FAN | Fan:OnOff | 0.339994 | 0.40304265 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | Sensible | 5565.99 | 5565.99 | 0.9890 | 0.40304265 | 0.339994 | 24.93 | 16.10 | 0.00797497 | 45360.4 | 12.80 | 11.43 | 0.00797497 | 32996.6 | -999.0 | -999.00 | -999.00 | -999.00 | 380.830 | 5185.16 | 23.42 | 0.00700114 | 14.70 | 0.02595455 | 7.6338 | 24.05 | 0.00805545 | 24.00 | 0.00805545 | 42.7194 | 3954.10 | 0.00 | 5627.16 | 4464.56 | 0.38712551 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 15.40 | 14.57 | 0.01000719 | 40786.6 | |
| SPLIT TN2 HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT TN2 | T N2 APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 9602.217 | 9602.217 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | SPLIT TN2 SUPPLY FAN | Fan:OnOff | 0.339994 | 0.40304265 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | Sensible | 9602.22 | 9602.22 | 1.0000 | 0.40304265 | 0.339994 | 16.29 | 12.35 | 0.00745590 | 35242.3 | 40.00 | 21.00 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9602.22 | -41.90 | 0.00006450 | -41.90 | 0.02595455 | 7.6338 | 21.10 | 0.00806678 | 21.10 | 0.00806678 | 51.0175 | 2682.84 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT TS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT TS1 | T S1 APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 6801.195 | 5445.413 | 0.410860 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.6965 | 1004.8586 | 1.1854 | SPLIT TS1 SUPPLY FAN | Fan:OnOff | 0.410860 | 0.48704985 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | Sensible | 6729.06 | 6729.06 | 0.9894 | 0.48704985 | 0.410860 | 24.94 | 16.13 | 0.00799190 | 45422.3 | 12.80 | 11.45 | 0.00799190 | 33039.4 | -999.0 | -999.00 | -999.00 | -999.00 | 460.208 | 6268.85 | 23.42 | 0.00700114 | 14.70 | 0.02595455 | 6.3171 | 24.06 | 0.00805871 | 24.00 | 0.00805871 | 42.7367 | 4759.25 | 0.00 | 6800.04 | 5395.11 | 0.46781506 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 15.40 | 14.57 | 0.01000719 | 40786.6 | |
| SPLIT TS1 HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT TS1 | T S1 APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 11197.809 | 11197.809 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | SPLIT TS1 SUPPLY FAN | Fan:OnOff | 0.410860 | 0.48704985 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | Sensible | 11197.81 | 11197.81 | 1.0000 | 0.48704985 | 0.410860 | 17.12 | 12.68 | 0.00745184 | 36076.7 | 40.00 | 21.00 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 11197.81 | -41.90 | 0.00006450 | -41.90 | 0.02595455 | 6.3171 | 21.10 | 0.00794998 | 21.10 | 0.00794998 | 50.2892 | 2827.90 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT TS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT TS2 | T S2 APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 6757.973 | 5410.807 | 0.408249 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.6967 | 1004.8586 | 1.1854 | SPLIT TS2 SUPPLY FAN | Fan:OnOff | 0.408249 | 0.48395461 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | Sensible | 6686.27 | 6686.27 | 0.9894 | 0.48395461 | 0.408249 | 24.94 | 16.13 | 0.00799198 | 45421.9 | 12.80 | 11.45 | 0.00799198 | 33039.6 | -999.0 | -999.00 | -999.00 | -999.00 | 457.283 | 6228.99 | 23.42 | 0.00700114 | 14.70 | 0.02595455 | 6.3575 | 24.06 | 0.00805925 | 24.00 | 0.00805925 | 42.7395 | 4729.55 | 0.00 | 6756.82 | 5360.83 | 0.46484206 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 15.40 | 14.57 | 0.01000719 | 40786.6 | |
| SPLIT TS2 HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT TS2 | T S2 APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 11139.025 | 11139.025 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | SPLIT TS2 SUPPLY FAN | Fan:OnOff | 0.408249 | 0.48395461 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | Sensible | 11139.02 | 11139.02 | 1.0000 | 0.48395461 | 0.408249 | 17.09 | 12.67 | 0.00744866 | 36042.7 | 40.00 | 21.00 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 11139.02 | -41.90 | 0.00006450 | -41.90 | 0.02595455 | 6.3575 | 21.10 | 0.00794998 | 21.10 | 0.00794998 | 50.2893 | 2828.15 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 09:14:30
Economizer| High Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
| None |
| Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
| None |
| Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
| G SW APARTMENT | 3623.17 | 5078.17 | 3403.00 |
| G NW APARTMENT | 5474.17 | 7634.33 | 5397.17 |
| OFFICE | 1316.50 | 1241.33 | 955.50 |
| G NE APARTMENT | 5502.33 | 7450.00 | 5315.00 |
| G N1 APARTMENT | 5295.17 | 7490.33 | 5221.50 |
| G N2 APARTMENT | 5288.00 | 7469.67 | 5209.33 |
| G S1 APARTMENT | 3396.00 | 4878.33 | 3188.33 |
| G S2 APARTMENT | 3504.50 | 4805.00 | 3238.83 |
| M SW APARTMENT | 3342.67 | 4567.67 | 2967.00 |
| M NW APARTMENT | 4987.67 | 6801.33 | 4686.67 |
| M SE APARTMENT | 3318.17 | 4527.17 | 2943.17 |
| M NE APARTMENT | 5032.00 | 6708.50 | 4645.17 |
| M N1 APARTMENT | 4638.67 | 6794.17 | 4458.83 |
| M N2 APARTMENT | 4637.17 | 6791.33 | 4454.33 |
| M S1 APARTMENT | 2978.50 | 4493.67 | 2723.67 |
| M S2 APARTMENT | 2978.33 | 4487.83 | 2721.83 |
| T SW APARTMENT | 3865.83 | 5039.17 | 3458.50 |
| T NW APARTMENT | 5700.50 | 7306.33 | 5234.83 |
| T SE APARTMENT | 3841.00 | 5031.33 | 3444.00 |
| T NE APARTMENT | 5768.17 | 7188.33 | 5165.50 |
| T N1 APARTMENT | 5427.17 | 7266.50 | 5116.00 |
| T N2 APARTMENT | 5425.33 | 7258.50 | 5108.33 |
| T S1 APARTMENT | 3609.00 | 4996.33 | 3284.50 |
| T S2 APARTMENT | 3609.33 | 4996.00 | 3284.50 |
| T CORRIDOR | 7806.17 | 8694.50 | 7762.33 |
| G CORRIDOR | 6609.00 | 7351.50 | 5577.00 |
| M CORRIDOR | 8278.33 | 8755.50 | 8278.33 |
| Facility | 8760.00 | 8760.00 | 8760.00 |
| During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
| G SW APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| G NW APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| OFFICE | 0.00 | 0.00 | 0.00 | 0.00 |
| G NE APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| G N1 APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| G N2 APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| G S1 APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| G S2 APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| M SW APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| M NW APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| M SE APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| M NE APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| M N1 APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| M N2 APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| M S1 APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| M S2 APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| T SW APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| T NW APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| T SE APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| T NE APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| T N1 APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| T N2 APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| T S1 APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| T S2 APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| T CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
| G CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
| M CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
| Facility | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 09:14:30
Average Outdoor Air During Occupied Hours| Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
| G SW APARTMENT | 2.41 | 2.50 | 268.97 | 0.353 | 0.064 | 0.000 | 0.030 |
| G NW APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.064 | 0.000 | 0.040 |
| OFFICE | 4.75 | 4.75 | 268.97 | 0.519 | 0.060 | 0.000 | 0.000 |
| G NE APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.064 | 0.000 | 0.040 |
| G N1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.038 | 0.000 | 0.040 |
| G N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.038 | 0.000 | 0.040 |
| G S1 APARTMENT | 2.41 | 2.50 | 268.97 | 0.353 | 0.038 | 0.000 | 0.030 |
| G S2 APARTMENT | 2.41 | 2.50 | 268.97 | 0.353 | 0.038 | 0.000 | 0.030 |
| M SW APARTMENT | 2.41 | 2.50 | 268.97 | 0.354 | 0.092 | 0.000 | 0.034 |
| M NW APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.091 | 0.000 | 0.047 |
| M SE APARTMENT | 2.41 | 2.50 | 268.97 | 0.354 | 0.092 | 0.000 | 0.034 |
| M NE APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.091 | 0.000 | 0.047 |
| M N1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.055 | 0.000 | 0.047 |
| M N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.055 | 0.000 | 0.047 |
| M S1 APARTMENT | 2.41 | 2.50 | 268.97 | 0.354 | 0.055 | 0.000 | 0.034 |
| M S2 APARTMENT | 2.41 | 2.50 | 268.97 | 0.354 | 0.055 | 0.000 | 0.034 |
| T SW APARTMENT | 2.41 | 2.50 | 268.97 | 0.353 | 0.121 | 0.000 | 0.038 |
| T NW APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.121 | 0.000 | 0.053 |
| T SE APARTMENT | 2.41 | 2.50 | 268.97 | 0.353 | 0.121 | 0.000 | 0.038 |
| T NE APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.121 | 0.000 | 0.053 |
| T N1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.073 | 0.000 | 0.053 |
| T N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.073 | 0.000 | 0.053 |
| T S1 APARTMENT | 2.41 | 2.50 | 268.97 | 0.353 | 0.073 | 0.000 | 0.038 |
| T S2 APARTMENT | 2.41 | 2.50 | 268.97 | 0.353 | 0.073 | 0.000 | 0.038 |
| Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
| G SW APARTMENT | 2.41 | 2.50 | 268.97 | 0.342 | 0.000 | 0.000 | 0.000 |
| G NW APARTMENT | 1.71 | 2.50 | 268.97 | 0.342 | 0.000 | 0.000 | 0.000 |
| OFFICE | 4.75 | 4.75 | 268.97 | 0.498 | 0.000 | 0.000 | 0.000 |
| G NE APARTMENT | 1.71 | 2.50 | 268.97 | 0.342 | 0.000 | 0.000 | 0.000 |
| G N1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.342 | 0.000 | 0.000 | 0.000 |
| G N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.342 | 0.000 | 0.000 | 0.000 |
| G S1 APARTMENT | 2.41 | 2.50 | 268.97 | 0.342 | 0.000 | 0.000 | 0.000 |
| G S2 APARTMENT | 2.41 | 2.50 | 268.97 | 0.342 | 0.000 | 0.000 | 0.000 |
| M SW APARTMENT | 2.41 | 2.50 | 268.97 | 0.342 | 0.000 | 0.000 | 0.000 |
| M NW APARTMENT | 1.71 | 2.50 | 268.97 | 0.342 | 0.000 | 0.000 | 0.000 |
| M SE APARTMENT | 2.41 | 2.50 | 268.97 | 0.342 | 0.000 | 0.000 | 0.000 |
| M NE APARTMENT | 1.71 | 2.50 | 268.97 | 0.342 | 0.000 | 0.000 | 0.000 |
| M N1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.342 | 0.000 | 0.000 | 0.000 |
| M N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.342 | 0.000 | 0.000 | 0.000 |
| M S1 APARTMENT | 2.41 | 2.50 | 268.97 | 0.342 | 0.000 | 0.000 | 0.000 |
| M S2 APARTMENT | 2.41 | 2.50 | 268.97 | 0.342 | 0.000 | 0.000 | 0.000 |
| T SW APARTMENT | 2.41 | 2.50 | 268.97 | 0.342 | 0.000 | 0.000 | 0.000 |
| T NW APARTMENT | 1.71 | 2.50 | 268.97 | 0.342 | 0.000 | 0.000 | 0.000 |
| T SE APARTMENT | 2.41 | 2.50 | 268.97 | 0.342 | 0.000 | 0.000 | 0.000 |
| T NE APARTMENT | 1.71 | 2.50 | 268.97 | 0.342 | 0.000 | 0.000 | 0.000 |
| T N1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.342 | 0.000 | 0.000 | 0.000 |
| T N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.342 | 0.000 | 0.000 | 0.000 |
| T S1 APARTMENT | 2.41 | 2.50 | 268.97 | 0.342 | 0.000 | 0.000 | 0.000 |
| T S2 APARTMENT | 2.41 | 2.50 | 268.97 | 0.342 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 09:14:30
Mechanical Ventilation Parameters by Zone| AirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
| G SW APARTMENT | SPLIT GSW | 2.41 | 2.50 | 268.97 | 88.25 | 0.0260 | 0.026 |
| G NW APARTMENT | SPLIT GNW | 1.71 | 2.50 | 268.97 | 88.25 | 0.0260 | 0.026 |
| OFFICE | SPLIT OFFICE | 4.75 | 4.75 | 268.97 | 88.25 | 0.0381 | 0.038 |
| G NE APARTMENT | SPLIT GNE | 1.71 | 2.50 | 268.97 | 88.25 | 0.0260 | 0.026 |
| G N1 APARTMENT | SPLIT GN1 | 1.71 | 2.50 | 268.97 | 88.25 | 0.0260 | 0.026 |
| G N2 APARTMENT | SPLIT GN2 | 1.71 | 2.50 | 268.97 | 88.25 | 0.0260 | 0.026 |
| G S1 APARTMENT | SPLIT GS1 | 2.41 | 2.50 | 268.97 | 88.25 | 0.0260 | 0.026 |
| G S2 APARTMENT | SPLIT GS2 | 2.41 | 2.50 | 268.97 | 88.25 | 0.0260 | 0.026 |
| M SW APARTMENT | SPLIT MSW | 2.41 | 2.50 | 268.97 | 88.25 | 0.0519 | 0.052 |
| M NW APARTMENT | SPLIT MNW | 1.71 | 2.50 | 268.97 | 88.25 | 0.0519 | 0.052 |
| M SE APARTMENT | SPLIT MSE | 2.41 | 2.50 | 268.97 | 88.25 | 0.0519 | 0.052 |
| M NE APARTMENT | SPLIT MNE | 1.71 | 2.50 | 268.97 | 88.25 | 0.0519 | 0.052 |
| M N1 APARTMENT | SPLIT MN1 | 1.71 | 2.50 | 268.97 | 88.25 | 0.0519 | 0.052 |
| M N2 APARTMENT | SPLIT MN2 | 1.71 | 2.50 | 268.97 | 88.25 | 0.0519 | 0.052 |
| M S1 APARTMENT | SPLIT MS1 | 2.41 | 2.50 | 268.97 | 88.25 | 0.0519 | 0.052 |
| M S2 APARTMENT | SPLIT MS2 | 2.41 | 2.50 | 268.97 | 88.25 | 0.0519 | 0.052 |
| T SW APARTMENT | SPLIT TSW | 2.41 | 2.50 | 268.97 | 88.25 | 0.0260 | 0.026 |
| T NW APARTMENT | SPLIT TNW | 1.71 | 2.50 | 268.97 | 88.25 | 0.0260 | 0.026 |
| T SE APARTMENT | SPLIT TSE | 2.41 | 2.50 | 268.97 | 88.25 | 0.0260 | 0.026 |
| T NE APARTMENT | SPLIT TNE | 1.71 | 2.50 | 268.97 | 88.25 | 0.0260 | 0.026 |
| T N1 APARTMENT | SPLIT TN1 | 1.71 | 2.50 | 268.97 | 88.25 | 0.0260 | 0.026 |
| T N2 APARTMENT | SPLIT TN2 | 1.71 | 2.50 | 268.97 | 88.25 | 0.0260 | 0.026 |
| T S1 APARTMENT | SPLIT TS1 | 2.41 | 2.50 | 268.97 | 88.25 | 0.0260 | 0.026 |
| T S2 APARTMENT | SPLIT TS2 | 2.41 | 2.50 | 268.97 | 88.25 | 0.0260 | 0.026 |
| Total Facility | 68.21 | 82.25 | 8607.06 | 2823.98 | 0.8427 | 1.258 |
| Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
| G SW APARTMENT | 818502.78 | 92207.47 | 910710.25 | 147026.72 | 1057736.96 | 818502.78 | 0.00 | 7796.83 | 963.17 | 2615.00 |
| G NW APARTMENT | 818502.78 | 91238.43 | 909741.20 | 147026.72 | 1056767.92 | 818502.78 | 0.00 | 7796.83 | 963.17 | 0.00 |
| OFFICE | 1201711.97 | 0.00 | 1201711.97 | 147026.72 | 1348738.69 | 1201711.97 | 0.00 | 8760.00 | 0.00 | 7010.00 |
| G NE APARTMENT | 818502.78 | 91993.24 | 910496.02 | 147026.72 | 1057522.74 | 818502.78 | 0.00 | 7796.83 | 963.17 | 0.00 |
| G N1 APARTMENT | 818502.78 | 91392.71 | 909895.49 | 88682.78 | 998578.27 | 818502.78 | 0.00 | 7796.83 | 963.17 | 0.00 |
| G N2 APARTMENT | 818502.78 | 91490.06 | 909992.84 | 88682.78 | 998675.62 | 818502.78 | 0.00 | 7796.83 | 963.17 | 0.00 |
| G S1 APARTMENT | 818502.78 | 92382.03 | 910884.81 | 88682.78 | 999567.59 | 818502.78 | 0.00 | 7796.83 | 963.17 | 2615.00 |
| G S2 APARTMENT | 818502.78 | 92427.23 | 910930.01 | 88682.78 | 999612.79 | 818502.78 | 0.00 | 7796.83 | 963.17 | 2615.00 |
| M SW APARTMENT | 1637005.55 | 107473.30 | 1744478.85 | 211289.32 | 1955768.17 | 1637005.55 | 0.00 | 7783.33 | 976.67 | 2615.00 |
| M NW APARTMENT | 1637005.55 | 108953.12 | 1745958.67 | 211289.32 | 1957248.00 | 1637005.55 | 0.00 | 7783.33 | 976.67 | 0.00 |
| M SE APARTMENT | 1637005.55 | 107473.34 | 1744478.90 | 211289.32 | 1955768.22 | 1637005.55 | 0.00 | 7783.33 | 976.67 | 2615.00 |
| M NE APARTMENT | 1637005.55 | 109003.88 | 1746009.43 | 211289.32 | 1957298.76 | 1637005.55 | 0.00 | 7783.33 | 976.67 | 0.00 |
| M N1 APARTMENT | 1637005.55 | 108945.25 | 1745950.81 | 127444.36 | 1873395.16 | 1637005.55 | 0.00 | 7783.33 | 976.67 | 0.00 |
| M N2 APARTMENT | 1637005.55 | 108963.25 | 1745968.80 | 127444.36 | 1873413.16 | 1637005.55 | 0.00 | 7783.33 | 976.67 | 0.00 |
| M S1 APARTMENT | 1637005.55 | 107475.11 | 1744480.67 | 127444.36 | 1871925.02 | 1637005.55 | 0.00 | 7783.33 | 976.67 | 2615.00 |
| M S2 APARTMENT | 1637005.55 | 107475.13 | 1744480.69 | 127444.36 | 1871925.04 | 1637005.55 | 0.00 | 7783.33 | 976.67 | 2615.00 |
| T SW APARTMENT | 818502.78 | 119700.65 | 938203.43 | 279493.98 | 1217697.40 | 818502.78 | 0.00 | 7816.50 | 943.50 | 2615.00 |
| T NW APARTMENT | 818502.78 | 121531.90 | 940034.68 | 279493.98 | 1219528.65 | 818502.78 | 0.00 | 7816.50 | 943.50 | 0.00 |
| T SE APARTMENT | 818502.78 | 119758.83 | 938261.61 | 279493.98 | 1217755.59 | 818502.78 | 0.00 | 7816.50 | 943.50 | 2615.00 |
| T NE APARTMENT | 818502.78 | 121735.01 | 940237.79 | 279493.98 | 1219731.76 | 818502.78 | 0.00 | 7816.50 | 943.50 | 0.00 |
| T N1 APARTMENT | 818502.78 | 121525.63 | 940028.40 | 168583.67 | 1108612.07 | 818502.78 | 0.00 | 7816.50 | 943.50 | 0.00 |
| T N2 APARTMENT | 818502.78 | 121570.44 | 940073.22 | 168583.67 | 1108656.89 | 818502.78 | 0.00 | 7816.50 | 943.50 | 0.00 |
| T S1 APARTMENT | 818502.78 | 119748.87 | 938251.65 | 168583.67 | 1106835.32 | 818502.78 | 0.00 | 7816.50 | 943.50 | 2615.00 |
| T S2 APARTMENT | 818502.78 | 119754.64 | 938257.42 | 168583.67 | 1106841.09 | 818502.78 | 0.00 | 7816.50 | 943.50 | 2615.00 |
| Total Facility | 39671342.50 | 3339981.91 | 43011324.41 | 5445018.02 | 48456342.43 | 39671342.50 | 0.00 | 8760.00 | 979.17 | 8760.00 |
| Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
| G SW APARTMENT | 0.0260 | 0.0022 | 0.0281 | 0.0047 | 0.0328 | 0.0260 | 0.00 | 5653.17 | 491.83 |
| G NW APARTMENT | 0.0260 | 0.0029 | 0.0288 | 0.0047 | 0.0335 | 0.0260 | 0.00 | 7796.83 | 963.17 |
| OFFICE | 0.0381 | 0.0000 | 0.0381 | 0.0044 | 0.0425 | 0.0381 | 0.00 | 1750.00 | 0.00 |
| G NE APARTMENT | 0.0260 | 0.0029 | 0.0289 | 0.0047 | 0.0335 | 0.0260 | 0.00 | 7796.83 | 963.17 |
| G N1 APARTMENT | 0.0260 | 0.0029 | 0.0289 | 0.0028 | 0.0317 | 0.0260 | 0.00 | 7796.83 | 963.17 |
| G N2 APARTMENT | 0.0260 | 0.0029 | 0.0289 | 0.0028 | 0.0317 | 0.0260 | 0.00 | 7796.83 | 963.17 |
| G S1 APARTMENT | 0.0260 | 0.0022 | 0.0281 | 0.0028 | 0.0309 | 0.0260 | 0.00 | 5653.17 | 491.83 |
| G S2 APARTMENT | 0.0260 | 0.0022 | 0.0281 | 0.0028 | 0.0309 | 0.0260 | 0.00 | 5653.17 | 491.83 |
| M SW APARTMENT | 0.0519 | 0.0025 | 0.0544 | 0.0067 | 0.0611 | 0.0519 | 0.00 | 5648.67 | 496.33 |
| M NW APARTMENT | 0.0519 | 0.0035 | 0.0554 | 0.0067 | 0.0621 | 0.0519 | 0.00 | 7783.33 | 976.67 |
| M SE APARTMENT | 0.0519 | 0.0025 | 0.0544 | 0.0067 | 0.0611 | 0.0519 | 0.00 | 5648.67 | 496.33 |
| M NE APARTMENT | 0.0519 | 0.0035 | 0.0554 | 0.0067 | 0.0621 | 0.0519 | 0.00 | 7783.33 | 976.67 |
| M N1 APARTMENT | 0.0519 | 0.0035 | 0.0554 | 0.0040 | 0.0594 | 0.0519 | 0.00 | 7783.33 | 976.67 |
| M N2 APARTMENT | 0.0519 | 0.0035 | 0.0554 | 0.0040 | 0.0594 | 0.0519 | 0.00 | 7783.33 | 976.67 |
| M S1 APARTMENT | 0.0519 | 0.0025 | 0.0544 | 0.0041 | 0.0585 | 0.0519 | 0.00 | 5648.67 | 496.33 |
| M S2 APARTMENT | 0.0519 | 0.0025 | 0.0544 | 0.0041 | 0.0585 | 0.0519 | 0.00 | 5648.67 | 496.33 |
| T SW APARTMENT | 0.0260 | 0.0028 | 0.0287 | 0.0089 | 0.0376 | 0.0260 | 0.00 | 5666.83 | 478.17 |
| T NW APARTMENT | 0.0260 | 0.0039 | 0.0298 | 0.0089 | 0.0387 | 0.0260 | 0.00 | 7816.50 | 943.50 |
| T SE APARTMENT | 0.0260 | 0.0028 | 0.0287 | 0.0089 | 0.0376 | 0.0260 | 0.00 | 5666.83 | 478.17 |
| T NE APARTMENT | 0.0260 | 0.0039 | 0.0298 | 0.0089 | 0.0387 | 0.0260 | 0.00 | 7816.50 | 943.50 |
| T N1 APARTMENT | 0.0260 | 0.0039 | 0.0298 | 0.0053 | 0.0352 | 0.0260 | 0.00 | 7816.50 | 943.50 |
| T N2 APARTMENT | 0.0260 | 0.0039 | 0.0298 | 0.0053 | 0.0352 | 0.0260 | 0.00 | 7816.50 | 943.50 |
| T S1 APARTMENT | 0.0260 | 0.0028 | 0.0287 | 0.0054 | 0.0341 | 0.0260 | 0.00 | 5666.83 | 478.17 |
| T S2 APARTMENT | 0.0260 | 0.0028 | 0.0287 | 0.0054 | 0.0341 | 0.0260 | 0.00 | 5666.83 | 478.17 |
| Total Facility | 1.2580 | 0.0923 | 1.3503 | 0.1727 | 1.5230 | 1.2580 | 0.00 | 8760.00 | 979.17 |
| Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
| SPLIT GSW | 0.00 | 92207.47 | 92207.47 | 818502.78 | 8192.83 | 28.83 | 538.33 | 471.33 |
| SPLIT GNW | 0.00 | 91238.43 | 91238.43 | 818502.78 | 8215.00 | 34.17 | 510.83 | 0.00 |
| SPLIT OFFICE | 1688725.36 | 0.00 | 1688725.36 | 1201711.97 | 0.00 | 0.00 | 8760.00 | 7010.00 |
| SPLIT GNE | 0.00 | 91993.24 | 91993.24 | 818502.78 | 8197.67 | 33.17 | 529.17 | 0.00 |
| SPLIT GN1 | 0.00 | 91392.71 | 91392.71 | 818502.78 | 8210.44 | 34.22 | 515.33 | 0.00 |
| SPLIT GN2 | 0.00 | 91490.06 | 91490.06 | 818502.78 | 8208.00 | 34.83 | 517.17 | 0.00 |
| SPLIT GS1 | 0.00 | 92382.03 | 92382.03 | 818502.78 | 8193.33 | 27.17 | 539.50 | 471.33 |
| SPLIT GS2 | 0.00 | 92427.23 | 92427.23 | 818502.78 | 8193.33 | 27.17 | 539.50 | 471.33 |
| SPLIT MSW | 0.00 | 107473.30 | 107473.30 | 1637005.55 | 8739.50 | 4.33 | 16.17 | 480.33 |
| SPLIT MNW | 0.00 | 108953.12 | 108953.12 | 1637005.55 | 8728.83 | 4.33 | 26.83 | 0.00 |
| SPLIT MSE | 0.00 | 107473.34 | 107473.34 | 1637005.55 | 8739.50 | 4.33 | 16.17 | 480.33 |
| SPLIT MNE | 0.00 | 109003.88 | 109003.88 | 1637005.55 | 8728.83 | 4.33 | 26.83 | 0.00 |
| SPLIT MN1 | 0.00 | 108945.25 | 108945.25 | 1637005.55 | 8728.83 | 4.33 | 26.83 | 0.00 |
| SPLIT MN2 | 0.00 | 108963.25 | 108963.25 | 1637005.55 | 8728.83 | 4.33 | 26.83 | 0.00 |
| SPLIT MS1 | 0.00 | 107475.11 | 107475.11 | 1637005.55 | 8739.50 | 4.33 | 16.17 | 480.33 |
| SPLIT MS2 | 0.00 | 107475.13 | 107475.13 | 1637005.55 | 8739.50 | 4.33 | 16.17 | 480.33 |
| SPLIT TSW | 0.00 | 119700.65 | 119700.65 | 818502.78 | 7984.67 | 13.50 | 761.83 | 465.33 |
| SPLIT TNW | 0.00 | 121531.90 | 121531.90 | 818502.78 | 7993.83 | 14.33 | 751.83 | 0.00 |
| SPLIT TSE | 0.00 | 119758.83 | 119758.83 | 818502.78 | 7984.67 | 13.50 | 761.83 | 465.33 |
| SPLIT TNE | 0.00 | 121735.01 | 121735.01 | 818502.78 | 7991.83 | 14.33 | 753.83 | 0.00 |
| SPLIT TN1 | 0.00 | 121525.63 | 121525.63 | 818502.78 | 7993.50 | 15.00 | 751.50 | 0.00 |
| SPLIT TN2 | 0.00 | 121570.44 | 121570.44 | 818502.78 | 7993.33 | 14.33 | 752.33 | 0.00 |
| SPLIT TS1 | 0.00 | 119748.87 | 119748.87 | 818502.78 | 7984.67 | 13.50 | 761.83 | 465.33 |
| SPLIT TS2 | 0.00 | 119754.64 | 119754.64 | 818502.78 | 7984.67 | 13.50 | 761.83 | 465.33 |
| Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
| SPLIT GSW | 0.0000 | 0.0022 | 0.0022 | 0.0260 | 5834.50 | 13.50 | 297.00 |
| SPLIT GNW | 0.0000 | 0.0029 | 0.0029 | 0.0260 | 8215.00 | 34.17 | 510.83 |
| SPLIT OFFICE | 0.0535 | 0.0000 | 0.0535 | 0.0381 | 0.00 | 0.00 | 1750.00 |
| SPLIT GNE | 0.0000 | 0.0029 | 0.0029 | 0.0260 | 8197.67 | 33.17 | 529.17 |
| SPLIT GN1 | 0.0000 | 0.0029 | 0.0029 | 0.0260 | 8210.44 | 34.22 | 515.33 |
| SPLIT GN2 | 0.0000 | 0.0029 | 0.0029 | 0.0260 | 8208.00 | 34.83 | 517.17 |
| SPLIT GS1 | 0.0000 | 0.0022 | 0.0022 | 0.0260 | 5835.50 | 12.17 | 297.33 |
| SPLIT GS2 | 0.0000 | 0.0022 | 0.0022 | 0.0260 | 5835.50 | 12.17 | 297.33 |
| SPLIT MSW | 0.0000 | 0.0025 | 0.0025 | 0.0519 | 6134.50 | 3.00 | 7.50 |
| SPLIT MNW | 0.0000 | 0.0035 | 0.0035 | 0.0519 | 8728.83 | 4.33 | 26.83 |
| SPLIT MSE | 0.0000 | 0.0025 | 0.0025 | 0.0519 | 6134.50 | 3.00 | 7.50 |
| SPLIT MNE | 0.0000 | 0.0035 | 0.0035 | 0.0519 | 8728.83 | 4.33 | 26.83 |
| SPLIT MN1 | 0.0000 | 0.0035 | 0.0035 | 0.0519 | 8728.83 | 4.33 | 26.83 |
| SPLIT MN2 | 0.0000 | 0.0035 | 0.0035 | 0.0519 | 8728.83 | 4.33 | 26.83 |
| SPLIT MS1 | 0.0000 | 0.0025 | 0.0025 | 0.0519 | 6134.50 | 3.00 | 7.50 |
| SPLIT MS2 | 0.0000 | 0.0025 | 0.0025 | 0.0519 | 6134.50 | 3.00 | 7.50 |
| SPLIT TSW | 0.0000 | 0.0028 | 0.0028 | 0.0260 | 5745.50 | 6.50 | 393.00 |
| SPLIT TNW | 0.0000 | 0.0039 | 0.0039 | 0.0260 | 7993.83 | 14.33 | 751.83 |
| SPLIT TSE | 0.0000 | 0.0028 | 0.0028 | 0.0260 | 5745.50 | 6.50 | 393.00 |
| SPLIT TNE | 0.0000 | 0.0039 | 0.0039 | 0.0260 | 7991.83 | 14.33 | 753.83 |
| SPLIT TN1 | 0.0000 | 0.0039 | 0.0039 | 0.0260 | 7993.50 | 15.00 | 751.50 |
| SPLIT TN2 | 0.0000 | 0.0039 | 0.0039 | 0.0260 | 7993.33 | 14.33 | 752.33 |
| SPLIT TS1 | 0.0000 | 0.0028 | 0.0028 | 0.0260 | 5745.50 | 6.50 | 393.00 |
| SPLIT TS2 | 0.0000 | 0.0028 | 0.0028 | 0.0260 | 5745.50 | 6.50 | 393.00 |
| No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
| SPLIT GSW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT GNW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT OFFICE | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT GNE | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT GN1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT GN2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT GS1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT GS2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT MSW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT MNW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT MSE | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT MNE | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT MN1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT MN2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT MS1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT MS2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT TSW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT TNW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT TSE | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT TNE | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT TN1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT TN2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT TS1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT TS2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
| SPLIT GSW | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT GNW | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT OFFICE | 0.0535 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT GNE | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT GN1 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT GN2 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT GS1 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT GS2 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT MSW | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT MNW | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT MSE | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT MNE | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT MN1 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT MN2 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT MS1 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT MS2 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT TSW | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT TNW | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT TSE | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT TNE | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT TN1 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT TN2 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT TS1 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT TS2 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 09:14:30
Surfaces by Class| Total | Outdoors | |
| Wall | 126 | 42 |
| Floor | 27 | 9 |
| Roof | 27 | 9 |
| Internal Mass | 24 | 0 |
| Building Detached Shading | 0 | 0 |
| Fixed Detached Shading | 0 | 0 |
| Window | 39 | 39 |
| Door | 0 | 0 |
| Glass Door | 0 | 0 |
| Shading | 0 | 0 |
| Overhang | 0 | 0 |
| Fin | 0 | 0 |
| Tubular Daylighting Device Dome | 0 | 0 |
| Tubular Daylighting Device Diffuser | 0 | 0 |
| Count | |
| HVAC Air Loops | 24 |
| Conditioned Zones | 24 |
| Unconditioned Zones | 3 |
| Supply Plenums | 0 |
| Return Plenums | 0 |
| Count | |
| IDF Objects | 1536 |
| Defaulted Fields | 1816 |
| Fields with Defaults | 5921 |
| Autosized Fields | 617 |
| Autosizable Fields | 759 |
| Autocalculated Fields | 331 |
| Autocalculatable Fields | 508 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 09:14:30
Annual and Peak Values - Electricity| Electricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
| Electricity:Facility | 1316.10 | 13849.57 | 03-JUL-02:40 | 82869.64 | 21-JUN-17:20 |
| Electricity:Building | 557.89 | 10119.94 | 01-JAN-03:10 | 27841.36 | 01-JAN-18:10 |
| Electricity:Zone:G SW APARTMENT | 13.67 | 232.36 | 01-JAN-03:10 | 705.80 | 01-JAN-18:10 |
| Electricity:SpaceType:GENERAL | 557.89 | 10119.94 | 01-JAN-03:10 | 27841.36 | 01-JAN-18:10 |
| InteriorLights:Electricity | 99.23 | 1868.27 | 01-JAN-00:10 | 5904.43 | 01-JAN-19:10 |
| InteriorLights:Electricity:Zone:G SW APARTMENT | 1.45 | 8.68 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 |
| InteriorLights:Electricity:SpaceType:GENERAL | 99.23 | 1868.27 | 01-JAN-00:10 | 5904.43 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity | 94.96 | 1842.77 | 01-JAN-00:10 | 5496.56 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:G SW APARTMENT | 1.32 | 7.86 | 01-JAN-00:10 | 125.72 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 94.96 | 1842.77 | 01-JAN-00:10 | 5496.56 | 01-JAN-19:10 |
| Electricity:Zone:G NW APARTMENT | 13.67 | 232.36 | 01-JAN-03:10 | 705.80 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:G NW APARTMENT | 1.45 | 8.68 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:G NW APARTMENT | 1.32 | 7.86 | 01-JAN-00:10 | 125.72 | 01-JAN-19:10 |
| Electricity:Zone:OFFICE | 16.86 | 310.83 | 01-JAN-00:10 | 1171.54 | 03-JAN-08:10 |
| InteriorLights:Electricity:Zone:OFFICE | 7.40 | 116.58 | 01-JAN-00:10 | 582.92 | 03-JAN-08:10 |
| LightsWired:InteriorLights:Electricity:Zone:OFFICE | 7.40 | 116.58 | 01-JAN-00:10 | 582.92 | 03-JAN-08:10 |
| Electricity:Zone:G NE APARTMENT | 13.67 | 232.36 | 01-JAN-03:10 | 705.80 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:G NE APARTMENT | 1.45 | 8.68 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:G NE APARTMENT | 1.32 | 7.86 | 01-JAN-00:10 | 125.72 | 01-JAN-19:10 |
| Electricity:Zone:G N1 APARTMENT | 13.67 | 232.36 | 01-JAN-03:10 | 705.80 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:G N1 APARTMENT | 1.45 | 8.68 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:G N1 APARTMENT | 1.32 | 7.86 | 01-JAN-00:10 | 125.72 | 01-JAN-19:10 |
| Electricity:Zone:G N2 APARTMENT | 13.67 | 232.36 | 01-JAN-03:10 | 705.80 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:G N2 APARTMENT | 1.45 | 8.68 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:G N2 APARTMENT | 1.32 | 7.86 | 01-JAN-00:10 | 125.72 | 01-JAN-19:10 |
| Electricity:Zone:G S1 APARTMENT | 13.67 | 232.36 | 01-JAN-03:10 | 705.80 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:G S1 APARTMENT | 1.45 | 8.68 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:G S1 APARTMENT | 1.32 | 7.86 | 01-JAN-00:10 | 125.72 | 01-JAN-19:10 |
| Electricity:Zone:G S2 APARTMENT | 13.67 | 232.36 | 01-JAN-03:10 | 705.80 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:G S2 APARTMENT | 1.45 | 8.68 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:G S2 APARTMENT | 1.32 | 7.86 | 01-JAN-00:10 | 125.72 | 01-JAN-19:10 |
| Electricity:Zone:M SW APARTMENT | 27.33 | 464.72 | 01-JAN-03:10 | 1411.61 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:M SW APARTMENT | 2.91 | 17.37 | 01-JAN-00:10 | 277.76 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:M SW APARTMENT | 2.63 | 15.72 | 01-JAN-00:10 | 251.45 | 01-JAN-19:10 |
| Electricity:Zone:M NW APARTMENT | 27.33 | 464.72 | 01-JAN-03:10 | 1411.61 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:M NW APARTMENT | 2.91 | 17.37 | 01-JAN-00:10 | 277.76 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:M NW APARTMENT | 2.63 | 15.72 | 01-JAN-00:10 | 251.45 | 01-JAN-19:10 |
| Electricity:Zone:M SE APARTMENT | 27.33 | 464.72 | 01-JAN-03:10 | 1411.61 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:M SE APARTMENT | 2.91 | 17.37 | 01-JAN-00:10 | 277.76 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:M SE APARTMENT | 2.63 | 15.72 | 01-JAN-00:10 | 251.45 | 01-JAN-19:10 |
| Electricity:Zone:M NE APARTMENT | 27.33 | 464.72 | 01-JAN-03:10 | 1411.61 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:M NE APARTMENT | 2.91 | 17.37 | 01-JAN-00:10 | 277.76 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:M NE APARTMENT | 2.63 | 15.72 | 01-JAN-00:10 | 251.45 | 01-JAN-19:10 |
| Electricity:Zone:M N1 APARTMENT | 27.33 | 464.72 | 01-JAN-03:10 | 1411.61 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:M N1 APARTMENT | 2.91 | 17.37 | 01-JAN-00:10 | 277.76 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:M N1 APARTMENT | 2.63 | 15.72 | 01-JAN-00:10 | 251.45 | 01-JAN-19:10 |
| Electricity:Zone:M N2 APARTMENT | 27.33 | 464.72 | 01-JAN-03:10 | 1411.61 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:M N2 APARTMENT | 2.91 | 17.37 | 01-JAN-00:10 | 277.76 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:M N2 APARTMENT | 2.63 | 15.72 | 01-JAN-00:10 | 251.45 | 01-JAN-19:10 |
| Electricity:Zone:M S1 APARTMENT | 27.33 | 464.72 | 01-JAN-03:10 | 1411.61 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:M S1 APARTMENT | 2.91 | 17.37 | 01-JAN-00:10 | 277.76 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:M S1 APARTMENT | 2.63 | 15.72 | 01-JAN-00:10 | 251.45 | 01-JAN-19:10 |
| Electricity:Zone:M S2 APARTMENT | 27.33 | 464.72 | 01-JAN-03:10 | 1411.61 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:M S2 APARTMENT | 2.91 | 17.37 | 01-JAN-00:10 | 277.76 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:M S2 APARTMENT | 2.63 | 15.72 | 01-JAN-00:10 | 251.45 | 01-JAN-19:10 |
| Electricity:Zone:T SW APARTMENT | 13.67 | 232.36 | 01-JAN-03:10 | 705.80 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:T SW APARTMENT | 1.45 | 8.68 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:T SW APARTMENT | 1.32 | 7.86 | 01-JAN-00:10 | 125.72 | 01-JAN-19:10 |
| Electricity:Zone:T NW APARTMENT | 13.67 | 232.36 | 01-JAN-03:10 | 705.80 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:T NW APARTMENT | 1.45 | 8.68 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:T NW APARTMENT | 1.32 | 7.86 | 01-JAN-00:10 | 125.72 | 01-JAN-19:10 |
| Electricity:Zone:T SE APARTMENT | 13.67 | 232.36 | 01-JAN-03:10 | 705.80 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:T SE APARTMENT | 1.45 | 8.68 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:T SE APARTMENT | 1.32 | 7.86 | 01-JAN-00:10 | 125.72 | 01-JAN-19:10 |
| Electricity:Zone:T NE APARTMENT | 13.67 | 232.36 | 01-JAN-03:10 | 705.80 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:T NE APARTMENT | 1.45 | 8.68 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:T NE APARTMENT | 1.32 | 7.86 | 01-JAN-00:10 | 125.72 | 01-JAN-19:10 |
| Electricity:Zone:T N1 APARTMENT | 13.67 | 232.36 | 01-JAN-03:10 | 705.80 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:T N1 APARTMENT | 1.45 | 8.68 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:T N1 APARTMENT | 1.32 | 7.86 | 01-JAN-00:10 | 125.72 | 01-JAN-19:10 |
| Electricity:Zone:T N2 APARTMENT | 13.67 | 232.36 | 01-JAN-03:10 | 705.80 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:T N2 APARTMENT | 1.45 | 8.68 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:T N2 APARTMENT | 1.32 | 7.86 | 01-JAN-00:10 | 125.72 | 01-JAN-19:10 |
| Electricity:Zone:T S1 APARTMENT | 13.67 | 232.36 | 01-JAN-03:10 | 705.80 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:T S1 APARTMENT | 1.45 | 8.68 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:T S1 APARTMENT | 1.32 | 7.86 | 01-JAN-00:10 | 125.72 | 01-JAN-19:10 |
| Electricity:Zone:T S2 APARTMENT | 13.67 | 232.36 | 01-JAN-03:10 | 705.80 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:T S2 APARTMENT | 1.45 | 8.68 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:T S2 APARTMENT | 1.32 | 7.86 | 01-JAN-00:10 | 125.72 | 01-JAN-19:10 |
| Electricity:Zone:G CORRIDOR | 82.28 | 1494.09 | 01-JAN-00:10 | 4538.70 | 01-JAN-07:10 |
| InteriorLights:Electricity:Zone:G CORRIDOR | 11.69 | 370.63 | 01-JAN-00:10 | 370.63 | 01-JAN-00:10 |
| LightsWired:InteriorLights:Electricity:Zone:G CORRIDOR | 11.69 | 370.63 | 01-JAN-00:10 | 370.63 | 01-JAN-00:10 |
| Electricity:Zone:M CORRIDOR | 23.38 | 741.26 | 01-JAN-00:10 | 741.26 | 01-JAN-00:10 |
| InteriorLights:Electricity:Zone:M CORRIDOR | 23.38 | 741.26 | 01-JAN-00:10 | 741.26 | 01-JAN-00:10 |
| LightsWired:InteriorLights:Electricity:Zone:M CORRIDOR | 23.38 | 741.26 | 01-JAN-00:10 | 741.26 | 01-JAN-00:10 |
| Electricity:Zone:T CORRIDOR | 11.69 | 370.63 | 01-JAN-00:10 | 370.63 | 01-JAN-00:10 |
| InteriorLights:Electricity:Zone:T CORRIDOR | 11.69 | 370.63 | 01-JAN-00:10 | 370.63 | 01-JAN-00:10 |
| LightsWired:InteriorLights:Electricity:Zone:T CORRIDOR | 11.69 | 370.63 | 01-JAN-00:10 | 370.63 | 01-JAN-00:10 |
| LightsPlugIn:InteriorLights:Electricity | 4.27 | 25.50 | 01-JAN-00:10 | 407.87 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:G SW APARTMENT | 0.14 | 0.82 | 01-JAN-00:10 | 13.16 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:SpaceType:GENERAL | 4.27 | 25.50 | 01-JAN-00:10 | 407.87 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:G NW APARTMENT | 0.14 | 0.82 | 01-JAN-00:10 | 13.16 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:G NE APARTMENT | 0.14 | 0.82 | 01-JAN-00:10 | 13.16 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:G N1 APARTMENT | 0.14 | 0.82 | 01-JAN-00:10 | 13.16 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:G N2 APARTMENT | 0.14 | 0.82 | 01-JAN-00:10 | 13.16 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:G S1 APARTMENT | 0.14 | 0.82 | 01-JAN-00:10 | 13.16 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:G S2 APARTMENT | 0.14 | 0.82 | 01-JAN-00:10 | 13.16 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:M SW APARTMENT | 0.28 | 1.65 | 01-JAN-00:10 | 26.31 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:M NW APARTMENT | 0.28 | 1.65 | 01-JAN-00:10 | 26.31 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:M SE APARTMENT | 0.28 | 1.65 | 01-JAN-00:10 | 26.31 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:M NE APARTMENT | 0.28 | 1.65 | 01-JAN-00:10 | 26.31 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:M N1 APARTMENT | 0.28 | 1.65 | 01-JAN-00:10 | 26.31 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:M N2 APARTMENT | 0.28 | 1.65 | 01-JAN-00:10 | 26.31 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:M S1 APARTMENT | 0.28 | 1.65 | 01-JAN-00:10 | 26.31 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:M S2 APARTMENT | 0.28 | 1.65 | 01-JAN-00:10 | 26.31 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:T SW APARTMENT | 0.14 | 0.82 | 01-JAN-00:10 | 13.16 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:T NW APARTMENT | 0.14 | 0.82 | 01-JAN-00:10 | 13.16 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:T SE APARTMENT | 0.14 | 0.82 | 01-JAN-00:10 | 13.16 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:T NE APARTMENT | 0.14 | 0.82 | 01-JAN-00:10 | 13.16 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:T N1 APARTMENT | 0.14 | 0.82 | 01-JAN-00:10 | 13.16 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:T N2 APARTMENT | 0.14 | 0.82 | 01-JAN-00:10 | 13.16 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:T S1 APARTMENT | 0.14 | 0.82 | 01-JAN-00:10 | 13.16 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:T S2 APARTMENT | 0.14 | 0.82 | 01-JAN-00:10 | 13.16 | 01-JAN-19:10 |
| InteriorEquipment:Electricity | 458.66 | 8251.68 | 01-JAN-03:10 | 22709.69 | 03-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:G SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:SpaceType:GENERAL | 458.66 | 8251.68 | 01-JAN-03:10 | 22709.69 | 03-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity | 388.06 | 7128.22 | 01-JAN-03:10 | 18541.61 | 03-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:G SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 388.06 | 7128.22 | 01-JAN-03:10 | 18541.61 | 03-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:G NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:G NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:OFFICE | 9.47 | 194.25 | 01-JAN-00:10 | 588.62 | 03-JAN-08:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:OFFICE | 9.47 | 194.25 | 01-JAN-00:10 | 588.62 | 03-JAN-08:10 |
| InteriorEquipment:Electricity:Zone:G NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:G NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:G N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:G N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:G N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:G N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:G S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:G S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:G S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:G S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:M SW APARTMENT | 24.43 | 447.35 | 01-JAN-03:10 | 1177.25 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:M SW APARTMENT | 24.43 | 447.35 | 01-JAN-03:10 | 1177.25 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:M NW APARTMENT | 24.43 | 447.35 | 01-JAN-03:10 | 1177.25 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:M NW APARTMENT | 24.43 | 447.35 | 01-JAN-03:10 | 1177.25 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:M SE APARTMENT | 24.43 | 447.35 | 01-JAN-03:10 | 1177.25 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:M SE APARTMENT | 24.43 | 447.35 | 01-JAN-03:10 | 1177.25 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:M NE APARTMENT | 24.43 | 447.35 | 01-JAN-03:10 | 1177.25 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:M NE APARTMENT | 24.43 | 447.35 | 01-JAN-03:10 | 1177.25 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:M N1 APARTMENT | 24.43 | 447.35 | 01-JAN-03:10 | 1177.25 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:M N1 APARTMENT | 24.43 | 447.35 | 01-JAN-03:10 | 1177.25 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:M N2 APARTMENT | 24.43 | 447.35 | 01-JAN-03:10 | 1177.25 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:M N2 APARTMENT | 24.43 | 447.35 | 01-JAN-03:10 | 1177.25 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:M S1 APARTMENT | 24.43 | 447.35 | 01-JAN-03:10 | 1177.25 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:M S1 APARTMENT | 24.43 | 447.35 | 01-JAN-03:10 | 1177.25 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:M S2 APARTMENT | 24.43 | 447.35 | 01-JAN-03:10 | 1177.25 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:M S2 APARTMENT | 24.43 | 447.35 | 01-JAN-03:10 | 1177.25 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:T SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:T SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:T NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:T NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:T SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:T SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:T NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:T NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:T N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:T N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:T N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:T N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:T S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:T S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:T S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:T S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:G CORRIDOR | 70.59 | 1123.46 | 01-JAN-00:10 | 4168.07 | 01-JAN-07:10 |
| ElevatorLift:InteriorEquipment:Electricity | 65.48 | 961.46 | 01-JAN-00:10 | 4006.07 | 01-JAN-07:10 |
| ElevatorLift:InteriorEquipment:Electricity:Zone:G CORRIDOR | 65.48 | 961.46 | 01-JAN-00:10 | 4006.07 | 01-JAN-07:10 |
| ElevatorLift:InteriorEquipment:Electricity:SpaceType:GENERAL | 65.48 | 961.46 | 01-JAN-00:10 | 4006.07 | 01-JAN-07:10 |
| ElevatorLightsFan:InteriorEquipment:Electricity | 5.11 | 162.00 | 01-JAN-00:10 | 162.00 | 01-JAN-00:10 |
| ElevatorLightsFan:InteriorEquipment:Electricity:Zone:G CORRIDOR | 5.11 | 162.00 | 01-JAN-00:10 | 162.00 | 01-JAN-00:10 |
| ElevatorLightsFan:InteriorEquipment:Electricity:SpaceType:GENERAL | 5.11 | 162.00 | 01-JAN-00:10 | 162.00 | 01-JAN-00:10 |
| Fans:Electricity | 105.31 | 1699.40 | 13-MAY-04:10 | 7344.40 | 29-JUL-16:10 |
| Fans:Electricity:Zone:G SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:G SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:G NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:G NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:G NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:G NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:G N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:G N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:G N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:G N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:G S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:G S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:G S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:G S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:M SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:M SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:M NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:M NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:M SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:M SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:M NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:M NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:M N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:M N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:M N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:M N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:M S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:M S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:M S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:M S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:T SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:T SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:T NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:T NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:T SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:T SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:T NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:T NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:T N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:T N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:T N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:T N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:T S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:T S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:T S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:T S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| ElectricityPurchased:Facility | 1316.10 | 13849.57 | 03-JUL-02:40 | 82869.64 | 21-JUN-17:20 |
| ElectricityPurchased:Plant | 1316.10 | 13849.57 | 03-JUL-02:40 | 82869.64 | 21-JUN-17:20 |
| Cogeneration:ElectricityPurchased | 1316.10 | 13849.57 | 03-JUL-02:40 | 82869.64 | 21-JUN-17:20 |
| General:Cogeneration:ElectricityPurchased | 1316.10 | 13849.57 | 03-JUL-02:40 | 82869.64 | 21-JUN-17:20 |
| ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| ElectricityNet:Facility | 1316.10 | 13849.57 | 03-JUL-02:40 | 82869.64 | 21-JUN-17:20 |
| ElectricityNet:Plant | 1316.10 | 13849.57 | 03-JUL-02:40 | 82869.64 | 21-JUN-17:20 |
| Cogeneration:ElectricityNet | 1316.10 | 13849.57 | 03-JUL-02:40 | 82869.64 | 21-JUN-17:20 |
| General:Cogeneration:ElectricityNet | 1316.10 | 13849.57 | 03-JUL-02:40 | 82869.64 | 21-JUN-17:20 |
| Electricity:HVAC | 150.70 | 1699.40 | 13-MAY-04:10 | 27069.39 | 29-JUL-16:10 |
| HeatRecovery:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:HeatRecovery:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:Fans:Electricity | 105.31 | 1699.40 | 13-MAY-04:10 | 7344.40 | 29-JUL-16:10 |
| Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Cooling:Electricity | 45.39 | 0.00 | 01-JAN-00:10 | 19724.99 | 29-JUL-16:10 |
| General:Cooling:Electricity | 45.39 | 0.00 | 01-JAN-00:10 | 19724.99 | 29-JUL-16:10 |
| ExteriorLights:Electricity | 49.63 | 0.00 | 01-JAN-11:20 | 3183.33 | 01-JAN-00:10 |
| General:ExteriorLights:Electricity | 49.63 | 0.00 | 01-JAN-11:20 | 3183.33 | 01-JAN-00:10 |
| Electricity:Plant | 557.88 | 1950.00 | 01-JAN-00:10 | 50200.01 | 09-MAR-07:50 |
| WaterSystems:Electricity | 557.88 | 1950.00 | 01-JAN-00:10 | 50200.01 | 09-MAR-07:50 |
| Water Heater:WaterSystems:Electricity | 557.88 | 1950.00 | 01-JAN-00:10 | 50200.01 | 09-MAR-07:50 |
| Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
| NaturalGas:Facility | 1217.05 | 0.00 | 21-APR-15:10 | 151176.37 | 12-JAN-04:00 |
| NaturalGas:HVAC | 1217.05 | 0.00 | 21-APR-15:10 | 151176.37 | 12-JAN-04:00 |
| Heating:NaturalGas | 1217.05 | 0.00 | 21-APR-15:10 | 151176.37 | 12-JAN-04:00 |
| General:Heating:NaturalGas | 1217.05 | 0.00 | 21-APR-15:10 | 151176.37 | 12-JAN-04:00 |
| Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
| None |
| Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
| Water:Facility | 1875.32 | 0.00 | 01-JAN-02:10 | 0.00 | 01-JAN-07:10 |
| Water:Plant | 1875.32 | 0.00 | 01-JAN-02:10 | 0.00 | 01-JAN-07:10 |
| WaterSystems:Water | 1875.32 | 0.00 | 01-JAN-02:10 | 0.00 | 01-JAN-07:10 |
| Water Heater:WaterSystems:Water | 1875.32 | 0.00 | 01-JAN-02:10 | 0.00 | 01-JAN-07:10 |
| MainsWater:Facility | 1875.32 | 0.00 | 01-JAN-02:10 | 0.00 | 01-JAN-07:10 |
| MainsWater:Plant | 1875.32 | 0.00 | 01-JAN-02:10 | 0.00 | 01-JAN-07:10 |
| WaterSystems:MainsWater | 1875.32 | 0.00 | 01-JAN-02:10 | 0.00 | 01-JAN-07:10 |
| Water Heater:WaterSystems:MainsWater | 1875.32 | 0.00 | 01-JAN-02:10 | 0.00 | 01-JAN-07:10 |
| Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
| Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
| CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
| Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
| None |
| Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
| None |
| Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
| EnergyTransfer:Facility | 1912.44 | 6060.77 | 19-SEP-16:10 | 200313.03 | 29-JAN-00:10 |
| EnergyTransfer:Building | 761.27 | 5205.63 | 27-SEP-13:30 | 80031.28 | 29-JAN-00:10 |
| EnergyTransfer:Zone:G SW APARTMENT | 26.87 | 0.03 | 06-OCT-01:40 | 2767.01 | 29-JAN-00:10 |
| Heating:EnergyTransfer | 450.88 | 0.00 | 19-APR-14:40 | 80031.28 | 29-JAN-00:10 |
| Heating:EnergyTransfer:Zone:G SW APARTMENT | 19.51 | 0.00 | 20-MAR-12:30 | 2767.01 | 29-JAN-00:10 |
| General:Heating:EnergyTransfer | 450.88 | 0.00 | 19-APR-14:40 | 80031.28 | 29-JAN-00:10 |
| General:Heating:EnergyTransfer:Zone:G SW APARTMENT | 19.51 | 0.00 | 20-MAR-12:30 | 2767.01 | 29-JAN-00:10 |
| Cooling:EnergyTransfer | 310.40 | 0.00 | 01-JAN-00:10 | 59725.22 | 12-JUL-15:20 |
| Cooling:EnergyTransfer:Zone:G SW APARTMENT | 7.36 | 0.00 | 01-JAN-00:10 | 2113.54 | 11-AUG-16:10 |
| General:Cooling:EnergyTransfer | 310.40 | 0.00 | 01-JAN-00:10 | 59725.22 | 12-JUL-15:20 |
| General:Cooling:EnergyTransfer:Zone:G SW APARTMENT | 7.36 | 0.00 | 01-JAN-00:10 | 2113.54 | 11-AUG-16:10 |
| EnergyTransfer:Zone:G NW APARTMENT | 28.30 | 0.04 | 07-OCT-17:40 | 2933.25 | 29-JAN-00:10 |
| Heating:EnergyTransfer:Zone:G NW APARTMENT | 23.72 | 0.00 | 11-APR-16:10 | 2933.25 | 29-JAN-00:10 |
| General:Heating:EnergyTransfer:Zone:G NW APARTMENT | 23.72 | 0.00 | 11-APR-16:10 | 2933.25 | 29-JAN-00:10 |
| Cooling:EnergyTransfer:Zone:G NW APARTMENT | 4.58 | 0.00 | 01-JAN-00:10 | 1481.44 | 11-JUL-19:00 |
| General:Cooling:EnergyTransfer:Zone:G NW APARTMENT | 4.58 | 0.00 | 01-JAN-00:10 | 1481.44 | 11-JUL-19:00 |
| EnergyTransfer:Zone:OFFICE | 21.11 | 0.06 | 08-MAY-19:10 | 5562.94 | 30-JAN-09:10 |
| Heating:EnergyTransfer:Zone:OFFICE | 12.59 | 0.00 | 04-JAN-18:10 | 5562.94 | 30-JAN-09:10 |
| General:Heating:EnergyTransfer:Zone:OFFICE | 12.59 | 0.00 | 04-JAN-18:10 | 5562.94 | 30-JAN-09:10 |
| Cooling:EnergyTransfer:Zone:OFFICE | 8.52 | 0.00 | 01-JAN-00:10 | 3680.93 | 24-JUL-08:10 |
| General:Cooling:EnergyTransfer:Zone:OFFICE | 8.52 | 0.00 | 01-JAN-00:10 | 3680.93 | 24-JUL-08:10 |
| EnergyTransfer:Zone:G NE APARTMENT | 28.48 | 0.01 | 02-OCT-14:00 | 2938.68 | 29-JAN-00:10 |
| Heating:EnergyTransfer:Zone:G NE APARTMENT | 23.19 | 0.00 | 17-APR-15:20 | 2938.68 | 29-JAN-00:10 |
| General:Heating:EnergyTransfer:Zone:G NE APARTMENT | 23.19 | 0.00 | 17-APR-15:20 | 2938.68 | 29-JAN-00:10 |
| Cooling:EnergyTransfer:Zone:G NE APARTMENT | 5.29 | 0.00 | 01-JAN-00:10 | 1353.44 | 11-JUL-10:30 |
| General:Cooling:EnergyTransfer:Zone:G NE APARTMENT | 5.29 | 0.00 | 01-JAN-00:10 | 1353.44 | 11-JUL-10:30 |
| EnergyTransfer:Zone:G N1 APARTMENT | 18.64 | 0.06 | 22-APR-22:50 | 1820.01 | 27-FEB-08:20 |
| Heating:EnergyTransfer:Zone:G N1 APARTMENT | 13.67 | 0.00 | 06-APR-19:00 | 1820.01 | 27-FEB-08:20 |
| General:Heating:EnergyTransfer:Zone:G N1 APARTMENT | 13.67 | 0.00 | 06-APR-19:00 | 1820.01 | 27-FEB-08:20 |
| Cooling:EnergyTransfer:Zone:G N1 APARTMENT | 4.97 | 0.00 | 01-JAN-00:10 | 1015.26 | 11-JUL-20:00 |
| General:Cooling:EnergyTransfer:Zone:G N1 APARTMENT | 4.97 | 0.00 | 01-JAN-00:10 | 1015.26 | 11-JUL-20:00 |
| EnergyTransfer:Zone:G N2 APARTMENT | 18.68 | 0.00 | 27-MAY-04:30 | 1820.19 | 27-FEB-08:20 |
| Heating:EnergyTransfer:Zone:G N2 APARTMENT | 13.65 | 0.00 | 06-APR-19:00 | 1820.19 | 27-FEB-08:20 |
| General:Heating:EnergyTransfer:Zone:G N2 APARTMENT | 13.65 | 0.00 | 06-APR-19:00 | 1820.19 | 27-FEB-08:20 |
| Cooling:EnergyTransfer:Zone:G N2 APARTMENT | 5.03 | 0.00 | 01-JAN-00:10 | 1013.93 | 11-JUL-20:00 |
| General:Cooling:EnergyTransfer:Zone:G N2 APARTMENT | 5.03 | 0.00 | 01-JAN-00:10 | 1013.93 | 11-JUL-20:00 |
| EnergyTransfer:Zone:G S1 APARTMENT | 18.44 | 0.00 | 09-OCT-24:00 | 1748.13 | 12-JAN-08:20 |
| Heating:EnergyTransfer:Zone:G S1 APARTMENT | 10.14 | 0.00 | 09-FEB-12:40 | 1748.13 | 12-JAN-08:20 |
| General:Heating:EnergyTransfer:Zone:G S1 APARTMENT | 10.14 | 0.00 | 09-FEB-12:40 | 1748.13 | 12-JAN-08:20 |
| Cooling:EnergyTransfer:Zone:G S1 APARTMENT | 8.31 | 0.00 | 01-JAN-00:10 | 1741.48 | 11-AUG-16:10 |
| General:Cooling:EnergyTransfer:Zone:G S1 APARTMENT | 8.31 | 0.00 | 01-JAN-00:10 | 1741.48 | 11-AUG-16:10 |
| EnergyTransfer:Zone:G S2 APARTMENT | 20.64 | 0.01 | 09-FEB-14:50 | 1883.14 | 12-JAN-08:20 |
| Heating:EnergyTransfer:Zone:G S2 APARTMENT | 11.93 | 0.00 | 09-FEB-13:30 | 1883.14 | 12-JAN-08:20 |
| General:Heating:EnergyTransfer:Zone:G S2 APARTMENT | 11.93 | 0.00 | 09-FEB-13:30 | 1883.14 | 12-JAN-08:20 |
| Cooling:EnergyTransfer:Zone:G S2 APARTMENT | 8.70 | 0.00 | 01-JAN-00:10 | 1851.28 | 23-JUL-15:10 |
| General:Cooling:EnergyTransfer:Zone:G S2 APARTMENT | 8.70 | 0.00 | 01-JAN-00:10 | 1851.28 | 23-JUL-15:10 |
| EnergyTransfer:Zone:M SW APARTMENT | 49.14 | 0.11 | 05-MAR-13:30 | 5690.30 | 10-AUG-16:20 |
| Heating:EnergyTransfer:Zone:M SW APARTMENT | 22.39 | 0.00 | 09-FEB-11:20 | 5280.07 | 29-JAN-00:10 |
| General:Heating:EnergyTransfer:Zone:M SW APARTMENT | 22.39 | 0.00 | 09-FEB-11:20 | 5280.07 | 29-JAN-00:10 |
| Cooling:EnergyTransfer:Zone:M SW APARTMENT | 26.75 | 0.00 | 01-JAN-00:10 | 5690.30 | 10-AUG-16:20 |
| General:Cooling:EnergyTransfer:Zone:M SW APARTMENT | 26.75 | 0.00 | 01-JAN-00:10 | 5690.30 | 10-AUG-16:20 |
| EnergyTransfer:Zone:M NW APARTMENT | 46.28 | 0.01 | 26-SEP-09:40 | 5618.11 | 29-JAN-00:10 |
| Heating:EnergyTransfer:Zone:M NW APARTMENT | 28.52 | 0.00 | 18-MAR-11:00 | 5618.11 | 29-JAN-00:10 |
| General:Heating:EnergyTransfer:Zone:M NW APARTMENT | 28.52 | 0.00 | 18-MAR-11:00 | 5618.11 | 29-JAN-00:10 |
| Cooling:EnergyTransfer:Zone:M NW APARTMENT | 17.77 | 0.00 | 01-JAN-00:10 | 4285.16 | 11-JUL-18:00 |
| General:Cooling:EnergyTransfer:Zone:M NW APARTMENT | 17.77 | 0.00 | 01-JAN-00:10 | 4285.16 | 11-JUL-18:00 |
| EnergyTransfer:Zone:M SE APARTMENT | 51.12 | 0.03 | 23-MAR-06:50 | 5682.18 | 22-JUL-11:30 |
| Heating:EnergyTransfer:Zone:M SE APARTMENT | 21.85 | 0.00 | 23-JAN-13:00 | 5298.32 | 29-JAN-00:10 |
| General:Heating:EnergyTransfer:Zone:M SE APARTMENT | 21.85 | 0.00 | 23-JAN-13:00 | 5298.32 | 29-JAN-00:10 |
| Cooling:EnergyTransfer:Zone:M SE APARTMENT | 29.26 | 0.00 | 01-JAN-00:10 | 5682.18 | 22-JUL-11:30 |
| General:Cooling:EnergyTransfer:Zone:M SE APARTMENT | 29.26 | 0.00 | 01-JAN-00:10 | 5682.18 | 22-JUL-11:30 |
| EnergyTransfer:Zone:M NE APARTMENT | 47.43 | 0.02 | 27-SEP-08:50 | 5636.91 | 29-JAN-00:10 |
| Heating:EnergyTransfer:Zone:M NE APARTMENT | 27.63 | 0.00 | 18-MAR-08:50 | 5636.91 | 29-JAN-00:10 |
| General:Heating:EnergyTransfer:Zone:M NE APARTMENT | 27.63 | 0.00 | 18-MAR-08:50 | 5636.91 | 29-JAN-00:10 |
| Cooling:EnergyTransfer:Zone:M NE APARTMENT | 19.79 | 0.00 | 01-JAN-00:10 | 3946.94 | 11-JUL-09:50 |
| General:Cooling:EnergyTransfer:Zone:M NE APARTMENT | 19.79 | 0.00 | 01-JAN-00:10 | 3946.94 | 11-JUL-09:50 |
| EnergyTransfer:Zone:M N1 APARTMENT | 28.56 | 0.03 | 24-MAR-09:40 | 3038.87 | 29-JAN-00:10 |
| Heating:EnergyTransfer:Zone:M N1 APARTMENT | 11.12 | 0.00 | 19-JAN-18:50 | 3038.87 | 29-JAN-00:10 |
| General:Heating:EnergyTransfer:Zone:M N1 APARTMENT | 11.12 | 0.00 | 19-JAN-18:50 | 3038.87 | 29-JAN-00:10 |
| Cooling:EnergyTransfer:Zone:M N1 APARTMENT | 17.45 | 0.00 | 01-JAN-00:10 | 2659.86 | 11-JUL-20:00 |
| General:Cooling:EnergyTransfer:Zone:M N1 APARTMENT | 17.45 | 0.00 | 01-JAN-00:10 | 2659.86 | 11-JUL-20:00 |
| EnergyTransfer:Zone:M N2 APARTMENT | 28.64 | 0.00 | 17-APR-02:10 | 3038.88 | 29-JAN-00:10 |
| Heating:EnergyTransfer:Zone:M N2 APARTMENT | 11.09 | 0.00 | 19-JAN-18:50 | 3038.88 | 29-JAN-00:10 |
| General:Heating:EnergyTransfer:Zone:M N2 APARTMENT | 11.09 | 0.00 | 19-JAN-18:50 | 3038.88 | 29-JAN-00:10 |
| Cooling:EnergyTransfer:Zone:M N2 APARTMENT | 17.56 | 0.00 | 01-JAN-00:10 | 2649.17 | 11-JUL-20:00 |
| General:Cooling:EnergyTransfer:Zone:M N2 APARTMENT | 17.56 | 0.00 | 01-JAN-00:10 | 2649.17 | 11-JUL-20:00 |
| EnergyTransfer:Zone:M S1 APARTMENT | 35.74 | 0.01 | 20-OCT-05:40 | 4576.71 | 23-JUL-13:40 |
| Heating:EnergyTransfer:Zone:M S1 APARTMENT | 7.25 | 0.00 | 16-JAN-12:30 | 2702.90 | 29-JAN-00:10 |
| General:Heating:EnergyTransfer:Zone:M S1 APARTMENT | 7.25 | 0.00 | 16-JAN-12:30 | 2702.90 | 29-JAN-00:10 |
| Cooling:EnergyTransfer:Zone:M S1 APARTMENT | 28.49 | 0.00 | 01-JAN-00:10 | 4576.71 | 23-JUL-13:40 |
| General:Cooling:EnergyTransfer:Zone:M S1 APARTMENT | 28.49 | 0.00 | 01-JAN-00:10 | 4576.71 | 23-JUL-13:40 |
| EnergyTransfer:Zone:M S2 APARTMENT | 35.88 | 0.05 | 29-MAR-02:30 | 4606.42 | 23-JUL-13:40 |
| Heating:EnergyTransfer:Zone:M S2 APARTMENT | 7.24 | 0.00 | 16-JAN-12:30 | 2702.84 | 29-JAN-00:10 |
| General:Heating:EnergyTransfer:Zone:M S2 APARTMENT | 7.24 | 0.00 | 16-JAN-12:30 | 2702.84 | 29-JAN-00:10 |
| Cooling:EnergyTransfer:Zone:M S2 APARTMENT | 28.65 | 0.00 | 01-JAN-00:10 | 4606.42 | 23-JUL-13:40 |
| General:Cooling:EnergyTransfer:Zone:M S2 APARTMENT | 28.65 | 0.00 | 01-JAN-00:10 | 4606.42 | 23-JUL-13:40 |
| EnergyTransfer:Zone:T SW APARTMENT | 37.96 | 0.08 | 19-SEP-04:30 | 4456.69 | 29-JAN-00:10 |
| Heating:EnergyTransfer:Zone:T SW APARTMENT | 27.00 | 0.00 | 09-FEB-11:50 | 4456.69 | 29-JAN-00:10 |
| General:Heating:EnergyTransfer:Zone:T SW APARTMENT | 27.00 | 0.00 | 09-FEB-11:50 | 4456.69 | 29-JAN-00:10 |
| Cooling:EnergyTransfer:Zone:T SW APARTMENT | 10.95 | 0.00 | 01-JAN-00:10 | 3632.29 | 29-JUL-15:30 |
| General:Cooling:EnergyTransfer:Zone:T SW APARTMENT | 10.95 | 0.00 | 01-JAN-00:10 | 3632.29 | 29-JUL-15:30 |
| EnergyTransfer:Zone:T NW APARTMENT | 37.96 | 0.08 | 05-SEP-12:50 | 4584.37 | 29-JAN-00:10 |
| Heating:EnergyTransfer:Zone:T NW APARTMENT | 31.11 | 0.00 | 18-MAR-16:10 | 4584.37 | 29-JAN-00:10 |
| General:Heating:EnergyTransfer:Zone:T NW APARTMENT | 31.11 | 0.00 | 18-MAR-16:10 | 4584.37 | 29-JAN-00:10 |
| Cooling:EnergyTransfer:Zone:T NW APARTMENT | 6.85 | 0.00 | 01-JAN-00:10 | 2722.19 | 11-JUL-17:50 |
| General:Cooling:EnergyTransfer:Zone:T NW APARTMENT | 6.85 | 0.00 | 01-JAN-00:10 | 2722.19 | 11-JUL-17:50 |
| EnergyTransfer:Zone:T SE APARTMENT | 38.49 | 0.07 | 06-SEP-06:40 | 4474.87 | 29-JAN-00:10 |
| Heating:EnergyTransfer:Zone:T SE APARTMENT | 26.53 | 0.00 | 09-FEB-11:30 | 4474.87 | 29-JAN-00:10 |
| General:Heating:EnergyTransfer:Zone:T SE APARTMENT | 26.53 | 0.00 | 09-FEB-11:30 | 4474.87 | 29-JAN-00:10 |
| Cooling:EnergyTransfer:Zone:T SE APARTMENT | 11.96 | 0.00 | 01-JAN-00:10 | 3629.94 | 23-JUL-13:30 |
| General:Cooling:EnergyTransfer:Zone:T SE APARTMENT | 11.96 | 0.00 | 01-JAN-00:10 | 3629.94 | 23-JUL-13:30 |
| EnergyTransfer:Zone:T NE APARTMENT | 38.17 | 0.12 | 05-MAY-02:20 | 4602.44 | 29-JAN-00:10 |
| Heating:EnergyTransfer:Zone:T NE APARTMENT | 30.48 | 0.00 | 18-MAR-16:10 | 4602.44 | 29-JAN-00:10 |
| General:Heating:EnergyTransfer:Zone:T NE APARTMENT | 30.48 | 0.00 | 18-MAR-16:10 | 4602.44 | 29-JAN-00:10 |
| Cooling:EnergyTransfer:Zone:T NE APARTMENT | 7.69 | 0.00 | 01-JAN-00:10 | 2351.26 | 11-JUL-10:10 |
| General:Cooling:EnergyTransfer:Zone:T NE APARTMENT | 7.69 | 0.00 | 01-JAN-00:10 | 2351.26 | 11-JUL-10:10 |
| EnergyTransfer:Zone:T N1 APARTMENT | 25.66 | 0.02 | 05-SEP-06:30 | 2925.56 | 29-JAN-00:10 |
| Heating:EnergyTransfer:Zone:T N1 APARTMENT | 19.35 | 0.00 | 18-MAR-12:20 | 2925.56 | 29-JAN-00:10 |
| General:Heating:EnergyTransfer:Zone:T N1 APARTMENT | 19.35 | 0.00 | 18-MAR-12:20 | 2925.56 | 29-JAN-00:10 |
| Cooling:EnergyTransfer:Zone:T N1 APARTMENT | 6.30 | 0.00 | 01-JAN-00:10 | 1607.59 | 11-JUL-17:30 |
| General:Cooling:EnergyTransfer:Zone:T N1 APARTMENT | 6.30 | 0.00 | 01-JAN-00:10 | 1607.59 | 11-JUL-17:30 |
| EnergyTransfer:Zone:T N2 APARTMENT | 25.69 | 0.05 | 21-SEP-21:40 | 2926.00 | 29-JAN-00:10 |
| Heating:EnergyTransfer:Zone:T N2 APARTMENT | 19.33 | 0.00 | 18-MAR-12:20 | 2926.00 | 29-JAN-00:10 |
| General:Heating:EnergyTransfer:Zone:T N2 APARTMENT | 19.33 | 0.00 | 18-MAR-12:20 | 2926.00 | 29-JAN-00:10 |
| Cooling:EnergyTransfer:Zone:T N2 APARTMENT | 6.37 | 0.00 | 01-JAN-00:10 | 1596.39 | 11-JUL-17:20 |
| General:Cooling:EnergyTransfer:Zone:T N2 APARTMENT | 6.37 | 0.00 | 01-JAN-00:10 | 1596.39 | 11-JUL-17:20 |
| EnergyTransfer:Zone:T S1 APARTMENT | 26.66 | 0.19 | 11-APR-08:50 | 3065.87 | 23-JUL-13:50 |
| Heating:EnergyTransfer:Zone:T S1 APARTMENT | 15.81 | 0.00 | 09-FEB-11:20 | 2791.75 | 29-JAN-00:10 |
| General:Heating:EnergyTransfer:Zone:T S1 APARTMENT | 15.81 | 0.00 | 09-FEB-11:20 | 2791.75 | 29-JAN-00:10 |
| Cooling:EnergyTransfer:Zone:T S1 APARTMENT | 10.84 | 0.00 | 01-JAN-00:10 | 3065.87 | 23-JUL-13:50 |
| General:Cooling:EnergyTransfer:Zone:T S1 APARTMENT | 10.84 | 0.00 | 01-JAN-00:10 | 3065.87 | 23-JUL-13:50 |
| EnergyTransfer:Zone:T S2 APARTMENT | 26.73 | 0.13 | 21-MAR-13:30 | 3086.30 | 23-JUL-13:50 |
| Heating:EnergyTransfer:Zone:T S2 APARTMENT | 15.80 | 0.00 | 09-FEB-11:20 | 2792.19 | 29-JAN-00:10 |
| General:Heating:EnergyTransfer:Zone:T S2 APARTMENT | 15.80 | 0.00 | 09-FEB-11:20 | 2792.19 | 29-JAN-00:10 |
| Cooling:EnergyTransfer:Zone:T S2 APARTMENT | 10.93 | 0.00 | 01-JAN-00:10 | 3086.30 | 23-JUL-13:50 |
| General:Cooling:EnergyTransfer:Zone:T S2 APARTMENT | 10.93 | 0.00 | 01-JAN-00:10 | 3086.30 | 23-JUL-13:50 |
| EnergyTransfer:Zone:T CORRIDOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Heating:EnergyTransfer:Zone:T CORRIDOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:Heating:EnergyTransfer:Zone:T CORRIDOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Cooling:EnergyTransfer:Zone:T CORRIDOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:Cooling:EnergyTransfer:Zone:T CORRIDOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| EnergyTransfer:Zone:G CORRIDOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Heating:EnergyTransfer:Zone:G CORRIDOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:Heating:EnergyTransfer:Zone:G CORRIDOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Cooling:EnergyTransfer:Zone:G CORRIDOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:Cooling:EnergyTransfer:Zone:G CORRIDOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| EnergyTransfer:Zone:M CORRIDOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Heating:EnergyTransfer:Zone:M CORRIDOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:Heating:EnergyTransfer:Zone:M CORRIDOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Cooling:EnergyTransfer:Zone:M CORRIDOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:Cooling:EnergyTransfer:Zone:M CORRIDOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| EnergyTransfer:HVAC | 1151.17 | 0.00 | 13-MAY-04:10 | 120941.10 | 12-JAN-04:00 |
| HeatRecoveryForHeating:EnergyTransfer | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 15-AUG-22:10 |
| HeatRecoveryForCooling:EnergyTransfer | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 14-JUL-08:10 |
| HeatingCoils:EnergyTransfer | 973.64 | 0.00 | 21-APR-15:10 | 120941.10 | 12-JAN-04:00 |
| CoolingCoils:EnergyTransfer | 177.53 | 0.00 | 01-JAN-00:10 | 73586.76 | 29-JUL-16:10 |
| PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 09:14:30
Annual Building Sensible Heat Gain Components| HVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
| G SW APARTMENT | 0.026 | -22.356 | 37.793 | -3.308 | 0.000 | 0.000 | 3.973 | 1.454 | 12.213 | 10.880 | 0.000 | 0.004 | 0.000 | 0.000 | -9.542 | 0.000 | -4.046 | -27.092 |
| G NW APARTMENT | 0.026 | -22.145 | 42.949 | -1.693 | 0.000 | 0.000 | 4.064 | 1.454 | 12.213 | 4.771 | 0.000 | 0.004 | 0.000 | 0.000 | -10.196 | 0.000 | -3.952 | -27.495 |
| OFFICE | 0.000 | 0.000 | 12.589 | -8.522 | 0.000 | 0.000 | 2.203 | 7.396 | 9.469 | 12.179 | 0.000 | 0.002 | 0.000 | 0.000 | -8.760 | 0.000 | -3.271 | -23.283 |
| G NE APARTMENT | 0.026 | -22.197 | 42.234 | -2.165 | 0.000 | 0.000 | 4.057 | 1.454 | 12.213 | 5.931 | 0.000 | 0.004 | 0.000 | 0.000 | -9.995 | 0.000 | -3.982 | -27.581 |
| G N1 APARTMENT | 0.026 | -22.196 | 32.460 | -1.594 | 0.000 | 0.000 | 4.054 | 1.454 | 12.213 | 1.933 | 0.000 | 0.003 | 0.000 | 0.000 | -6.376 | 0.000 | -2.616 | -19.362 |
| G N2 APARTMENT | 0.026 | -22.203 | 32.421 | -1.629 | 0.000 | 0.000 | 4.053 | 1.454 | 12.213 | 1.931 | 0.000 | 0.003 | 0.000 | 0.000 | -6.377 | 0.000 | -2.620 | -19.272 |
| G S1 APARTMENT | 0.026 | -22.450 | 27.677 | -3.426 | 0.000 | 0.000 | 3.954 | 1.454 | 12.213 | 8.234 | 0.000 | 0.003 | 0.000 | 0.000 | -5.824 | 0.000 | -2.698 | -19.163 |
| G S2 APARTMENT | 0.026 | -22.463 | 29.580 | -3.910 | 0.000 | 0.000 | 3.951 | 1.454 | 12.213 | 8.232 | 0.000 | 0.003 | 0.000 | 0.000 | -5.813 | 0.000 | -2.701 | -20.572 |
| M SW APARTMENT | 0.052 | -45.201 | 56.018 | -15.232 | 0.000 | 0.000 | 7.845 | 2.908 | 24.426 | 21.345 | 0.000 | 0.012 | 0.000 | 0.000 | -19.759 | 0.000 | -11.466 | -20.948 |
| M NW APARTMENT | 0.052 | -44.843 | 64.638 | -9.098 | 0.000 | 0.000 | 8.012 | 2.908 | 24.426 | 9.131 | 0.000 | 0.012 | 0.000 | 0.000 | -21.141 | 0.000 | -11.356 | -22.741 |
| M SE APARTMENT | 0.052 | -45.246 | 55.043 | -17.260 | 0.000 | 0.000 | 7.841 | 2.908 | 24.426 | 23.869 | 0.000 | 0.012 | 0.000 | 0.000 | -19.528 | 0.000 | -11.477 | -20.641 |
| M NE APARTMENT | 0.052 | -44.911 | 63.559 | -10.862 | 0.000 | 0.000 | 8.004 | 2.908 | 24.426 | 11.449 | 0.000 | 0.012 | 0.000 | 0.000 | -20.717 | 0.000 | -11.377 | -22.543 |
| M N1 APARTMENT | 0.052 | -44.939 | 46.148 | -7.592 | 0.000 | 0.000 | 7.993 | 2.908 | 24.426 | 3.667 | 0.000 | 0.007 | 0.000 | 0.000 | -13.188 | 0.000 | -7.419 | -12.063 |
| M N2 APARTMENT | 0.052 | -44.950 | 46.102 | -7.677 | 0.000 | 0.000 | 7.990 | 2.908 | 24.426 | 3.664 | 0.000 | 0.007 | 0.000 | 0.000 | -13.191 | 0.000 | -7.422 | -11.909 |
| M S1 APARTMENT | 0.052 | -45.364 | 38.048 | -13.981 | 0.000 | 0.000 | 7.811 | 2.908 | 24.426 | 16.253 | 0.000 | 0.007 | 0.000 | 0.000 | -12.024 | 0.000 | -7.502 | -10.635 |
| M S2 APARTMENT | 0.052 | -45.369 | 38.003 | -14.097 | 0.000 | 0.000 | 7.811 | 2.908 | 24.426 | 16.250 | 0.000 | 0.007 | 0.000 | 0.000 | -12.025 | 0.000 | -7.502 | -10.465 |
| T SW APARTMENT | 0.026 | -22.342 | 45.348 | -6.985 | 0.000 | 0.000 | 3.982 | 1.454 | 12.213 | 10.707 | 0.000 | 0.008 | 0.000 | 0.000 | -9.533 | 0.000 | -7.324 | -27.554 |
| T NW APARTMENT | 0.026 | -22.217 | 50.317 | -3.871 | 0.000 | 0.000 | 4.051 | 1.454 | 12.213 | 4.622 | 0.000 | 0.008 | 0.000 | 0.000 | -10.251 | 0.000 | -7.260 | -29.093 |
| T SE APARTMENT | 0.026 | -22.384 | 44.682 | -7.755 | 0.000 | 0.000 | 3.979 | 1.454 | 12.213 | 11.976 | 0.000 | 0.008 | 0.000 | 0.000 | -9.439 | 0.000 | -7.338 | -27.422 |
| T NE APARTMENT | 0.026 | -22.258 | 49.567 | -4.553 | 0.000 | 0.000 | 4.049 | 1.454 | 12.213 | 5.776 | 0.000 | 0.008 | 0.000 | 0.000 | -10.043 | 0.000 | -7.282 | -28.956 |
| T N1 APARTMENT | 0.026 | -22.256 | 38.274 | -2.998 | 0.000 | 0.000 | 4.043 | 1.454 | 12.213 | 1.868 | 0.000 | 0.005 | 0.000 | 0.000 | -6.413 | 0.000 | -4.683 | -21.532 |
| T N2 APARTMENT | 0.026 | -22.261 | 38.241 | -3.046 | 0.000 | 0.000 | 4.042 | 1.454 | 12.213 | 1.865 | 0.000 | 0.005 | 0.000 | 0.000 | -6.413 | 0.000 | -4.687 | -21.439 |
| T S1 APARTMENT | 0.026 | -22.422 | 33.418 | -6.053 | 0.000 | 0.000 | 3.965 | 1.454 | 12.213 | 8.151 | 0.000 | 0.005 | 0.000 | 0.000 | -5.819 | 0.000 | -4.737 | -20.202 |
| T S2 APARTMENT | 0.026 | -22.425 | 33.394 | -6.130 | 0.000 | 0.000 | 3.965 | 1.454 | 12.213 | 8.148 | 0.000 | 0.005 | 0.000 | 0.000 | -5.818 | 0.000 | -4.738 | -20.094 |
| T CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 6.782 | 11.688 | 0.000 | 0.983 | 0.000 | 0.000 | 0.000 | 0.000 | -0.972 | 0.000 | -1.151 | -17.330 |
| G CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 7.342 | 11.688 | 3.530 | 3.020 | 0.000 | 0.011 | 34.375 | 0.000 | -2.566 | 0.000 | -57.399 | -0.000 |
| M CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 12.654 | 23.376 | 0.000 | 1.936 | 0.000 | 0.000 | 0.000 | 0.000 | -2.057 | 0.000 | -1.847 | -34.062 |
| Total Facility | 0.813 | -695.398 | 998.504 | -163.439 | 0.000 | 0.000 | 152.470 | 99.229 | 391.594 | 218.770 | 0.000 | 0.166 | 34.375 | 0.000 | -263.780 | 0.000 | -209.853 | -563.451 |
| Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
| G SW APARTMENT | 11-AUG-16:06 | 0.00 | 70.00 | 0.00 | -2183.99 | 0.00 | 0.00 | 0.00 | 86.80 | 588.62 | 2272.44 | 0.00 | 20.80 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -854.67 |
| G NW APARTMENT | 11-JUL-19:00 | 0.00 | 70.17 | 0.00 | -1551.54 | 0.00 | 0.00 | 145.49 | 138.88 | 547.42 | 1401.45 | 0.00 | 25.86 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -777.73 |
| OFFICE | 13-JUL-07:01 | 0.00 | 0.00 | 0.00 | -6537.79 | 0.00 | 0.00 | 262.11 | 582.92 | 588.62 | 1137.86 | 0.00 | 0.00 | 3966.28 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| G NE APARTMENT | 11-JUL-10:30 | 0.00 | -19.21 | 0.00 | -1334.26 | 0.00 | 0.00 | 41.81 | 17.36 | 412.04 | 1395.72 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -26.03 | -487.42 |
| G N1 APARTMENT | 11-JUL-20:00 | 0.00 | 16.91 | 0.00 | -1032.12 | 0.00 | 0.00 | 145.49 | 138.88 | 523.87 | 481.22 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -0.79 | -273.46 |
| G N2 APARTMENT | 11-JUL-20:00 | 0.00 | 16.91 | 0.00 | -1030.80 | 0.00 | 0.00 | 145.49 | 138.88 | 523.87 | 481.21 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -0.79 | -274.78 |
| G S1 APARTMENT | 11-AUG-16:10 | 0.00 | 70.00 | 0.00 | -1812.41 | 0.00 | 0.00 | 0.00 | 86.80 | 588.62 | 1127.16 | 0.00 | 12.55 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -72.72 |
| G S2 APARTMENT | 23-JUL-15:10 | 0.00 | 70.17 | 0.00 | -1921.46 | 0.00 | 0.00 | 167.23 | 60.76 | 470.90 | 1437.09 | 0.00 | 4.89 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -289.57 |
| M SW APARTMENT | 10-AUG-16:20 | 0.00 | -24.42 | 0.00 | -5667.06 | 0.00 | 0.00 | 0.00 | 173.60 | 1177.25 | 5082.44 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -86.52 | -655.27 |
| M NW APARTMENT | 11-JUL-18:00 | 0.00 | 171.72 | 0.00 | -4456.60 | 0.00 | 0.00 | 290.97 | 234.36 | 1177.25 | 3179.58 | 0.00 | 71.43 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -668.71 |
| M SE APARTMENT | 22-JUL-11:30 | 0.00 | 137.26 | 0.00 | -5819.01 | 0.00 | 0.00 | 167.23 | 34.72 | 812.30 | 5701.49 | 0.00 | 23.85 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -1057.84 |
| M NE APARTMENT | 11-JUL-09:50 | 0.00 | -84.40 | 0.00 | -3862.61 | 0.00 | 0.00 | 83.61 | 34.72 | 812.30 | 3209.48 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -94.31 | -98.79 |
| M N1 APARTMENT | 11-JUL-20:00 | 0.00 | 33.82 | 0.00 | -2693.34 | 0.00 | 0.00 | 290.97 | 277.76 | 1047.75 | 955.74 | 0.00 | 0.00 | 101.56 | 0.00 | -0.00 | 0.00 | -14.26 | 0.00 |
| M N2 APARTMENT | 11-JUL-20:00 | 0.00 | 33.82 | 0.00 | -2682.66 | 0.00 | 0.00 | 290.97 | 277.76 | 1047.75 | 955.80 | 0.00 | 0.00 | 90.82 | 0.00 | -0.00 | 0.00 | -14.26 | 0.00 |
| M S1 APARTMENT | 23-JUL-13:40 | 0.00 | 102.76 | 0.00 | -4679.28 | 0.00 | 0.00 | 167.23 | 34.72 | 765.21 | 4501.57 | 0.00 | 7.51 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -899.71 |
| M S2 APARTMENT | 23-JUL-13:40 | 0.00 | 102.76 | 0.00 | -4708.98 | 0.00 | 0.00 | 167.23 | 34.72 | 765.21 | 4501.37 | 0.00 | 7.51 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -869.80 |
| T SW APARTMENT | 29-JUL-15:30 | 0.00 | 198.78 | 0.00 | -3831.30 | 0.00 | 0.00 | 167.23 | 60.76 | 470.90 | 2540.07 | 0.00 | 98.10 | 295.46 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| T NW APARTMENT | 11-JUL-17:50 | 0.00 | 85.86 | 0.00 | -2807.87 | 0.00 | 0.00 | 145.49 | 117.18 | 588.62 | 1623.94 | 0.00 | 46.34 | 200.44 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| T SE APARTMENT | 23-JUL-13:30 | 0.00 | 51.37 | 0.00 | -3681.19 | 0.00 | 0.00 | 83.61 | 17.36 | 382.60 | 2452.29 | 0.00 | 7.90 | 686.06 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| T NE APARTMENT | 11-JUL-10:10 | 0.00 | -30.71 | 0.00 | -2320.60 | 0.00 | 0.00 | 41.81 | 17.36 | 412.04 | 1488.47 | 0.00 | 0.00 | 437.04 | 0.00 | -0.00 | 0.00 | -45.40 | 0.00 |
| T N1 APARTMENT | 11-JUL-17:30 | 0.00 | 85.87 | 0.00 | -1693.56 | 0.00 | 0.00 | 145.49 | 117.18 | 588.62 | 243.06 | 0.00 | 27.95 | 485.38 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| T N2 APARTMENT | 11-JUL-17:17 | 0.00 | 85.87 | 0.00 | -1682.47 | 0.00 | 0.00 | 145.49 | 117.18 | 588.62 | 250.66 | 0.00 | 27.95 | 466.69 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| T S1 APARTMENT | 23-JUL-13:50 | 0.00 | 51.37 | 0.00 | -3117.16 | 0.00 | 0.00 | 83.61 | 17.36 | 382.60 | 2165.24 | 0.00 | 4.76 | 412.21 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| T S2 APARTMENT | 23-JUL-13:50 | 0.00 | 51.37 | 0.00 | -3137.59 | 0.00 | 0.00 | 83.61 | 17.36 | 382.60 | 2165.08 | 0.00 | 4.76 | 432.80 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| T CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| G CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Total Facility | 12-JUL-15:20 | 0.00 | 1201.34 | 0.00 | -60926.65 | 0.00 | 0.00 | 1398.58 | 3948.92 | 15334.78 | 36774.06 | 0.00 | 230.65 | 2215.54 | 0.00 | 0.00 | 0.00 | -177.22 | 0.00 |
| Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
| G SW APARTMENT | 29-JAN-00:10 | -1406.58 | 0.00 | 4173.57 | 0.00 | 0.00 | 0.00 | 194.99 | 8.68 | 264.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -815.52 | 0.00 | -1115.26 | -1304.76 |
| G NW APARTMENT | 29-JAN-00:10 | -1406.53 | 0.00 | 4339.78 | 0.00 | 0.00 | 0.00 | 194.99 | 8.68 | 264.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -826.88 | 0.00 | -1115.26 | -1459.65 |
| OFFICE | 17-APR-07:01 | 0.00 | 0.00 | 11275.86 | 0.00 | 0.00 | 0.00 | 418.55 | 582.92 | 588.62 | 66.34 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -127.32 | -12804.96 |
| G NE APARTMENT | 29-JAN-00:10 | -1406.53 | 0.00 | 4345.21 | 0.00 | 0.00 | 0.00 | 194.99 | 8.68 | 264.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -836.15 | 0.00 | -1115.26 | -1455.81 |
| G N1 APARTMENT | 27-FEB-08:19 | -1692.54 | 0.00 | 3513.06 | 0.00 | 0.00 | 0.00 | 76.05 | 26.04 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -529.88 | 0.00 | -86.85 | -1694.37 |
| G N2 APARTMENT | 27-FEB-08:19 | -1692.54 | 0.00 | 3513.25 | 0.00 | 0.00 | 0.00 | 76.05 | 26.04 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -529.88 | 0.00 | -86.85 | -1694.55 |
| G S1 APARTMENT | 12-JAN-08:19 | -1813.11 | 0.00 | 3561.74 | 0.00 | 0.00 | 0.00 | 0.00 | 26.04 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -599.90 | 0.00 | 0.00 | -1563.27 |
| G S2 APARTMENT | 12-JAN-08:19 | -1813.11 | 0.00 | 3696.75 | 0.00 | 0.00 | 0.00 | 0.00 | 26.04 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -598.85 | 0.00 | 0.00 | -1699.32 |
| M SW APARTMENT | 29-JAN-00:10 | -2812.89 | 0.00 | 8092.93 | 0.00 | 0.00 | 0.00 | 389.98 | 17.37 | 529.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1670.61 | 0.00 | -3206.85 | -1339.69 |
| M NW APARTMENT | 29-JAN-00:10 | -2812.83 | 0.00 | 8430.92 | 0.00 | 0.00 | 0.00 | 389.98 | 17.37 | 529.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1696.69 | 0.00 | -3206.85 | -1651.66 |
| M SE APARTMENT | 29-JAN-00:10 | -2812.89 | 0.00 | 8111.17 | 0.00 | 0.00 | 0.00 | 389.98 | 17.37 | 529.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1691.21 | 0.00 | -3206.85 | -1337.33 |
| M NE APARTMENT | 29-JAN-00:10 | -2812.83 | 0.00 | 8449.72 | 0.00 | 0.00 | 0.00 | 389.98 | 17.37 | 529.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1717.22 | 0.00 | -3206.85 | -1649.93 |
| M N1 APARTMENT | 29-JAN-00:10 | -2813.15 | 0.00 | 5852.01 | 0.00 | 0.00 | 0.00 | 389.98 | 17.37 | 529.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1045.05 | 0.00 | -1934.29 | -996.62 |
| M N2 APARTMENT | 29-JAN-00:10 | -2813.15 | 0.00 | 5852.03 | 0.00 | 0.00 | 0.00 | 389.98 | 17.37 | 529.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1045.05 | 0.00 | -1934.29 | -996.64 |
| M S1 APARTMENT | 29-JAN-00:10 | -2813.24 | 0.00 | 5516.13 | 0.00 | 0.00 | 0.00 | 389.98 | 17.37 | 529.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1017.51 | 0.00 | -1934.29 | -688.20 |
| M S2 APARTMENT | 29-JAN-00:10 | -2813.24 | 0.00 | 5516.07 | 0.00 | 0.00 | 0.00 | 389.98 | 17.37 | 529.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1017.51 | 0.00 | -1934.29 | -688.14 |
| T SW APARTMENT | 29-JAN-00:10 | -1406.35 | 0.00 | 5863.01 | 0.00 | 0.00 | 0.00 | 194.99 | 8.68 | 264.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -819.10 | 0.00 | -2122.87 | -1983.24 |
| T NW APARTMENT | 29-JAN-00:10 | -1406.32 | 0.00 | 5990.67 | 0.00 | 0.00 | 0.00 | 194.99 | 8.68 | 264.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -833.40 | 0.00 | -2122.87 | -2096.63 |
| T SE APARTMENT | 29-JAN-00:10 | -1406.35 | 0.00 | 5881.19 | 0.00 | 0.00 | 0.00 | 194.99 | 8.68 | 264.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -829.68 | 0.00 | -2122.87 | -1990.85 |
| T NE APARTMENT | 29-JAN-00:10 | -1406.32 | 0.00 | 6008.75 | 0.00 | 0.00 | 0.00 | 194.99 | 8.68 | 264.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -843.95 | 0.00 | -2122.87 | -2104.15 |
| T N1 APARTMENT | 29-JAN-00:10 | -1406.49 | 0.00 | 4332.04 | 0.00 | 0.00 | 0.00 | 194.99 | 8.68 | 264.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -515.08 | 0.00 | -1280.46 | -1598.57 |
| T N2 APARTMENT | 29-JAN-00:10 | -1406.49 | 0.00 | 4332.48 | 0.00 | 0.00 | 0.00 | 194.99 | 8.68 | 264.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -515.08 | 0.00 | -1280.46 | -1599.01 |
| T S1 APARTMENT | 29-JAN-00:10 | -1406.53 | 0.00 | 4198.27 | 0.00 | 0.00 | 0.00 | 194.99 | 8.68 | 264.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -500.04 | 0.00 | -1280.46 | -1479.79 |
| T S2 APARTMENT | 29-JAN-00:10 | -1406.53 | 0.00 | 4198.70 | 0.00 | 0.00 | 0.00 | 194.99 | 8.68 | 264.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -500.04 | 0.00 | -1280.46 | -1480.23 |
| T CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| G CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Total Facility | 29-JAN-00:10 | -43602.07 | 0.00 | 123632.98 | 0.00 | 0.00 | 0.00 | 7482.25 | 1868.27 | 8461.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -21962.56 | 0.00 | -42260.23 | -33620.34 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 09:14:30
System Ventilation Requirements for Cooling| Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
| SPLIT GSW | 0.3897 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.3897 | 0.0666 | 1.0000 | Not calculated | 0.0260 | 0.0666 | ||
| SPLIT GNW | 0.3191 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.3191 | 0.0813 | 1.0000 | Not calculated | 0.0260 | 0.0813 | ||
| SPLIT OFFICE | 0.4098 | 0.0000 | 4.7495 | 1.0000 | Calculated from schedules | 0.0381 | 0.4098 | 0.0930 | 1.0000 | Not calculated | 0.0381 | 0.0930 | ||
| SPLIT GNE | 0.2808 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.2808 | 0.0924 | 1.0000 | Not calculated | 0.0260 | 0.0924 | ||
| SPLIT GN1 | 0.2510 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.2510 | 0.1034 | 1.0000 | Not calculated | 0.0260 | 0.1034 | ||
| SPLIT GN2 | 0.2505 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.2505 | 0.1036 | 1.0000 | Not calculated | 0.0260 | 0.1036 | ||
| SPLIT GS1 | 0.3260 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.3260 | 0.0796 | 1.0000 | Not calculated | 0.0260 | 0.0796 | ||
| SPLIT GS2 | 0.3279 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.3279 | 0.0792 | 1.0000 | Not calculated | 0.0260 | 0.0792 | ||
| SPLIT MSW | 0.9778 | 0.0000 | 5.0000 | 1.0000 | Calculated from schedules | 0.0519 | 0.9778 | 0.0531 | 1.0000 | Not calculated | 0.0519 | 0.0531 | ||
| SPLIT MNW | 0.8382 | 0.0000 | 5.0000 | 1.0000 | Calculated from schedules | 0.0519 | 0.8382 | 0.0619 | 1.0000 | Not calculated | 0.0519 | 0.0619 | ||
| SPLIT MSE | 0.8387 | 0.0000 | 5.0000 | 1.0000 | Calculated from schedules | 0.0519 | 0.8387 | 0.0619 | 1.0000 | Not calculated | 0.0519 | 0.0619 | ||
| SPLIT MNE | 0.7034 | 0.0000 | 5.0000 | 1.0000 | Calculated from schedules | 0.0519 | 0.7034 | 0.0738 | 1.0000 | Not calculated | 0.0519 | 0.0738 | ||
| SPLIT MN1 | 0.6278 | 0.0000 | 5.0000 | 1.0000 | Calculated from schedules | 0.0519 | 0.6278 | 0.0827 | 1.0000 | Not calculated | 0.0519 | 0.0827 | ||
| SPLIT MN2 | 0.6262 | 0.0000 | 5.0000 | 1.0000 | Calculated from schedules | 0.0519 | 0.6262 | 0.0829 | 1.0000 | Not calculated | 0.0519 | 0.0829 | ||
| SPLIT MS1 | 0.7754 | 0.0000 | 5.0000 | 1.0000 | Calculated from schedules | 0.0519 | 0.7754 | 0.0669 | 1.0000 | Not calculated | 0.0519 | 0.0669 | ||
| SPLIT MS2 | 0.7735 | 0.0000 | 5.0000 | 1.0000 | Calculated from schedules | 0.0519 | 0.7735 | 0.0671 | 1.0000 | Not calculated | 0.0519 | 0.0671 | ||
| SPLIT TSW | 0.5303 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.5303 | 0.0489 | 1.0000 | Not calculated | 0.0260 | 0.0489 | ||
| SPLIT TNW | 0.4645 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.4645 | 0.0559 | 1.0000 | Not calculated | 0.0260 | 0.0559 | ||
| SPLIT TSE | 0.4288 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.4288 | 0.0605 | 1.0000 | Not calculated | 0.0260 | 0.0605 | ||
| SPLIT TNE | 0.3644 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.3644 | 0.0712 | 1.0000 | Not calculated | 0.0260 | 0.0712 | ||
| SPLIT TN1 | 0.3426 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.3426 | 0.0758 | 1.0000 | Not calculated | 0.0260 | 0.0758 | ||
| SPLIT TN2 | 0.3400 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.3400 | 0.0763 | 1.0000 | Not calculated | 0.0260 | 0.0763 | ||
| SPLIT TS1 | 0.4109 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.4109 | 0.0632 | 1.0000 | Not calculated | 0.0260 | 0.0632 | ||
| SPLIT TS2 | 0.4082 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.4082 | 0.0636 | 1.0000 | Not calculated | 0.0260 | 0.0636 |
| Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
| SPLIT GSW | 0.3897 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.3897 | 1.0000 | 1.0000 | Not calculated | 0.0260 | 0.0666 | ||
| SPLIT GNW | 0.3191 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.3191 | 1.0000 | 1.0000 | Not calculated | 0.0260 | 0.0813 | ||
| SPLIT OFFICE | 0.4098 | 0.0000 | 4.7495 | 1.0000 | Calculated from schedules | 0.0381 | 0.4098 | 1.0000 | 1.0000 | Not calculated | 0.0381 | 0.0930 | ||
| SPLIT GNE | 0.2808 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.2808 | 1.0000 | 1.0000 | Not calculated | 0.0260 | 0.0924 | ||
| SPLIT GN1 | 0.2510 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.2510 | 1.0000 | 1.0000 | Not calculated | 0.0260 | 0.1034 | ||
| SPLIT GN2 | 0.2505 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.2505 | 1.0000 | 1.0000 | Not calculated | 0.0260 | 0.1036 | ||
| SPLIT GS1 | 0.3260 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.3260 | 1.0000 | 1.0000 | Not calculated | 0.0260 | 0.0796 | ||
| SPLIT GS2 | 0.3279 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.3279 | 1.0000 | 1.0000 | Not calculated | 0.0260 | 0.0792 | ||
| SPLIT MSW | 0.9778 | 0.0000 | 5.0000 | 1.0000 | Calculated from schedules | 0.0519 | 0.9778 | 1.0000 | 1.0000 | Not calculated | 0.0519 | 0.0531 | ||
| SPLIT MNW | 0.8382 | 0.0000 | 5.0000 | 1.0000 | Calculated from schedules | 0.0519 | 0.8382 | 1.0000 | 1.0000 | Not calculated | 0.0519 | 0.0619 | ||
| SPLIT MSE | 0.8387 | 0.0000 | 5.0000 | 1.0000 | Calculated from schedules | 0.0519 | 0.8387 | 1.0000 | 1.0000 | Not calculated | 0.0519 | 0.0619 | ||
| SPLIT MNE | 0.7034 | 0.0000 | 5.0000 | 1.0000 | Calculated from schedules | 0.0519 | 0.7034 | 1.0000 | 1.0000 | Not calculated | 0.0519 | 0.0738 | ||
| SPLIT MN1 | 0.6278 | 0.0000 | 5.0000 | 1.0000 | Calculated from schedules | 0.0519 | 0.6278 | 1.0000 | 1.0000 | Not calculated | 0.0519 | 0.0827 | ||
| SPLIT MN2 | 0.6262 | 0.0000 | 5.0000 | 1.0000 | Calculated from schedules | 0.0519 | 0.6262 | 1.0000 | 1.0000 | Not calculated | 0.0519 | 0.0829 | ||
| SPLIT MS1 | 0.7754 | 0.0000 | 5.0000 | 1.0000 | Calculated from schedules | 0.0519 | 0.7754 | 1.0000 | 1.0000 | Not calculated | 0.0519 | 0.0669 | ||
| SPLIT MS2 | 0.7735 | 0.0000 | 5.0000 | 1.0000 | Calculated from schedules | 0.0519 | 0.7735 | 1.0000 | 1.0000 | Not calculated | 0.0519 | 0.0671 | ||
| SPLIT TSW | 0.5303 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.5303 | 1.0000 | 1.0000 | Not calculated | 0.0260 | 0.0489 | ||
| SPLIT TNW | 0.4645 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.4645 | 1.0000 | 1.0000 | Not calculated | 0.0260 | 0.0559 | ||
| SPLIT TSE | 0.4288 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.4288 | 1.0000 | 1.0000 | Not calculated | 0.0260 | 0.0605 | ||
| SPLIT TNE | 0.3644 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.3644 | 1.0000 | 1.0000 | Not calculated | 0.0260 | 0.0712 | ||
| SPLIT TN1 | 0.3426 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.3426 | 1.0000 | 1.0000 | Not calculated | 0.0260 | 0.0758 | ||
| SPLIT TN2 | 0.3400 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.3400 | 1.0000 | 1.0000 | Not calculated | 0.0260 | 0.0763 | ||
| SPLIT TS1 | 0.4109 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.4109 | 1.0000 | 1.0000 | Not calculated | 0.0260 | 0.0632 | ||
| SPLIT TS2 | 0.4082 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.4082 | 1.0000 | 1.0000 | Not calculated | 0.0260 | 0.0636 |
| AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
| G SW APARTMENT | SPLIT GSW | 0.000000 | 2.5000 | 0.000294 | 88.25 | 0.0260 | 1.0000 | 0.0260 | 1.000 | 0.0260 |
| G NW APARTMENT | SPLIT GNW | 0.000000 | 2.5000 | 0.000294 | 88.25 | 0.0260 | 1.0000 | 0.0260 | 1.000 | 0.0260 |
| OFFICE | SPLIT OFFICE | 0.000000 | 4.7495 | 0.000432 | 88.25 | 0.0381 | 1.0000 | 0.0381 | 1.000 | 0.0381 |
| G NE APARTMENT | SPLIT GNE | 0.000000 | 2.5000 | 0.000294 | 88.25 | 0.0260 | 1.0000 | 0.0260 | 1.000 | 0.0260 |
| G N1 APARTMENT | SPLIT GN1 | 0.000000 | 2.5000 | 0.000294 | 88.25 | 0.0260 | 1.0000 | 0.0260 | 1.000 | 0.0260 |
| G N2 APARTMENT | SPLIT GN2 | 0.000000 | 2.5000 | 0.000294 | 88.25 | 0.0260 | 1.0000 | 0.0260 | 1.000 | 0.0260 |
| G S1 APARTMENT | SPLIT GS1 | 0.000000 | 2.5000 | 0.000294 | 88.25 | 0.0260 | 1.0000 | 0.0260 | 1.000 | 0.0260 |
| G S2 APARTMENT | SPLIT GS2 | 0.000000 | 2.5000 | 0.000294 | 88.25 | 0.0260 | 1.0000 | 0.0260 | 1.000 | 0.0260 |
| M SW APARTMENT | SPLIT MSW | 0.000000 | 5.0000 | 0.000294 | 176.50 | 0.0519 | 1.0000 | 0.0519 | 1.000 | 0.0519 |
| M NW APARTMENT | SPLIT MNW | 0.000000 | 5.0000 | 0.000294 | 176.50 | 0.0519 | 1.0000 | 0.0519 | 1.000 | 0.0519 |
| M SE APARTMENT | SPLIT MSE | 0.000000 | 5.0000 | 0.000294 | 176.50 | 0.0519 | 1.0000 | 0.0519 | 1.000 | 0.0519 |
| M NE APARTMENT | SPLIT MNE | 0.000000 | 5.0000 | 0.000294 | 176.50 | 0.0519 | 1.0000 | 0.0519 | 1.000 | 0.0519 |
| M N1 APARTMENT | SPLIT MN1 | 0.000000 | 5.0000 | 0.000294 | 176.50 | 0.0519 | 1.0000 | 0.0519 | 1.000 | 0.0519 |
| M N2 APARTMENT | SPLIT MN2 | 0.000000 | 5.0000 | 0.000294 | 176.50 | 0.0519 | 1.0000 | 0.0519 | 1.000 | 0.0519 |
| M S1 APARTMENT | SPLIT MS1 | 0.000000 | 5.0000 | 0.000294 | 176.50 | 0.0519 | 1.0000 | 0.0519 | 1.000 | 0.0519 |
| M S2 APARTMENT | SPLIT MS2 | 0.000000 | 5.0000 | 0.000294 | 176.50 | 0.0519 | 1.0000 | 0.0519 | 1.000 | 0.0519 |
| T SW APARTMENT | SPLIT TSW | 0.000000 | 2.5000 | 0.000294 | 88.25 | 0.0260 | 1.0000 | 0.0260 | 1.000 | 0.0260 |
| T NW APARTMENT | SPLIT TNW | 0.000000 | 2.5000 | 0.000294 | 88.25 | 0.0260 | 1.0000 | 0.0260 | 1.000 | 0.0260 |
| T SE APARTMENT | SPLIT TSE | 0.000000 | 2.5000 | 0.000294 | 88.25 | 0.0260 | 1.0000 | 0.0260 | 1.000 | 0.0260 |
| T NE APARTMENT | SPLIT TNE | 0.000000 | 2.5000 | 0.000294 | 88.25 | 0.0260 | 1.0000 | 0.0260 | 1.000 | 0.0260 |
| T N1 APARTMENT | SPLIT TN1 | 0.000000 | 2.5000 | 0.000294 | 88.25 | 0.0260 | 1.0000 | 0.0260 | 1.000 | 0.0260 |
| T N2 APARTMENT | SPLIT TN2 | 0.000000 | 2.5000 | 0.000294 | 88.25 | 0.0260 | 1.0000 | 0.0260 | 1.000 | 0.0260 |
| T S1 APARTMENT | SPLIT TS1 | 0.000000 | 2.5000 | 0.000294 | 88.25 | 0.0260 | 1.0000 | 0.0260 | 1.000 | 0.0260 |
| T S2 APARTMENT | SPLIT TS2 | 0.000000 | 2.5000 | 0.000294 | 88.25 | 0.0260 | 1.0000 | 0.0260 | 1.000 | 0.0260 |
| People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
| SPLIT GSW | 0.000000 | 2.50 | 0.000294 | 88.2493 | 0.0260 | 0.0260 | 0.0260 |
| SPLIT GNW | 0.000000 | 2.50 | 0.000294 | 88.2493 | 0.0260 | 0.0260 | 0.0260 |
| SPLIT OFFICE | 0.000000 | 4.75 | 0.000432 | 88.2493 | 0.0381 | 0.0381 | 0.0381 |
| SPLIT GNE | 0.000000 | 2.50 | 0.000294 | 88.2493 | 0.0260 | 0.0260 | 0.0260 |
| SPLIT GN1 | 0.000000 | 2.50 | 0.000294 | 88.2493 | 0.0260 | 0.0260 | 0.0260 |
| SPLIT GN2 | 0.000000 | 2.50 | 0.000294 | 88.2493 | 0.0260 | 0.0260 | 0.0260 |
| SPLIT GS1 | 0.000000 | 2.50 | 0.000294 | 88.2493 | 0.0260 | 0.0260 | 0.0260 |
| SPLIT GS2 | 0.000000 | 2.50 | 0.000294 | 88.2493 | 0.0260 | 0.0260 | 0.0260 |
| SPLIT MSW | 0.000000 | 5.00 | 0.000294 | 176.4985 | 0.0519 | 0.0519 | 0.0519 |
| SPLIT MNW | 0.000000 | 5.00 | 0.000294 | 176.4985 | 0.0519 | 0.0519 | 0.0519 |
| SPLIT MSE | 0.000000 | 5.00 | 0.000294 | 176.4985 | 0.0519 | 0.0519 | 0.0519 |
| SPLIT MNE | 0.000000 | 5.00 | 0.000294 | 176.4985 | 0.0519 | 0.0519 | 0.0519 |
| SPLIT MN1 | 0.000000 | 5.00 | 0.000294 | 176.4985 | 0.0519 | 0.0519 | 0.0519 |
| SPLIT MN2 | 0.000000 | 5.00 | 0.000294 | 176.4985 | 0.0519 | 0.0519 | 0.0519 |
| SPLIT MS1 | 0.000000 | 5.00 | 0.000294 | 176.4985 | 0.0519 | 0.0519 | 0.0519 |
| SPLIT MS2 | 0.000000 | 5.00 | 0.000294 | 176.4985 | 0.0519 | 0.0519 | 0.0519 |
| SPLIT TSW | 0.000000 | 2.50 | 0.000294 | 88.2493 | 0.0260 | 0.0260 | 0.0260 |
| SPLIT TNW | 0.000000 | 2.50 | 0.000294 | 88.2493 | 0.0260 | 0.0260 | 0.0260 |
| SPLIT TSE | 0.000000 | 2.50 | 0.000294 | 88.2493 | 0.0260 | 0.0260 | 0.0260 |
| SPLIT TNE | 0.000000 | 2.50 | 0.000294 | 88.2493 | 0.0260 | 0.0260 | 0.0260 |
| SPLIT TN1 | 0.000000 | 2.50 | 0.000294 | 88.2493 | 0.0260 | 0.0260 | 0.0260 |
| SPLIT TN2 | 0.000000 | 2.50 | 0.000294 | 88.2493 | 0.0260 | 0.0260 | 0.0260 |
| SPLIT TS1 | 0.000000 | 2.50 | 0.000294 | 88.2493 | 0.0260 | 0.0260 | 0.0260 |
| SPLIT TS2 | 0.000000 | 2.50 | 0.000294 | 88.2493 | 0.0260 | 0.0260 | 0.0260 |
| AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
| G SW APARTMENT | SPLIT GSW | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.3897 | 0.3897 | 0.3897 | No | 0.0260 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| G NW APARTMENT | SPLIT GNW | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.3191 | 0.3191 | 0.3191 | No | 0.0260 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| OFFICE | SPLIT OFFICE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4098 | 0.4098 | 0.4098 | No | 0.0381 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| G NE APARTMENT | SPLIT GNE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.2808 | 0.2808 | 0.2808 | No | 0.0260 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| G N1 APARTMENT | SPLIT GN1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.2510 | 0.2510 | 0.2510 | No | 0.0260 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| G N2 APARTMENT | SPLIT GN2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.2505 | 0.2505 | 0.2505 | No | 0.0260 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| G S1 APARTMENT | SPLIT GS1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.3260 | 0.3260 | 0.3260 | No | 0.0260 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| G S2 APARTMENT | SPLIT GS2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.3279 | 0.3279 | 0.3279 | No | 0.0260 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| M SW APARTMENT | SPLIT MSW | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9778 | 0.9778 | 0.9778 | No | 0.0519 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| M NW APARTMENT | SPLIT MNW | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8382 | 0.8382 | 0.8382 | No | 0.0519 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| M SE APARTMENT | SPLIT MSE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8387 | 0.8387 | 0.8387 | No | 0.0519 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| M NE APARTMENT | SPLIT MNE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.7034 | 0.7034 | 0.7034 | No | 0.0519 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| M N1 APARTMENT | SPLIT MN1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.6278 | 0.6278 | 0.6278 | No | 0.0519 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| M N2 APARTMENT | SPLIT MN2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.6262 | 0.6262 | 0.6262 | No | 0.0519 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| M S1 APARTMENT | SPLIT MS1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.7754 | 0.7754 | 0.7754 | No | 0.0519 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| M S2 APARTMENT | SPLIT MS2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.7735 | 0.7735 | 0.7735 | No | 0.0519 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| T SW APARTMENT | SPLIT TSW | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.5303 | 0.5303 | 0.5303 | No | 0.0260 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| T NW APARTMENT | SPLIT TNW | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4645 | 0.4645 | 0.4645 | No | 0.0260 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| T SE APARTMENT | SPLIT TSE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4288 | 0.4288 | 0.4288 | No | 0.0260 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| T NE APARTMENT | SPLIT TNE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.3644 | 0.3644 | 0.3644 | No | 0.0260 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| T N1 APARTMENT | SPLIT TN1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.3426 | 0.3426 | 0.3426 | No | 0.0260 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| T N2 APARTMENT | SPLIT TN2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.3400 | 0.3400 | 0.3400 | No | 0.0260 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| T S1 APARTMENT | SPLIT TS1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4109 | 0.4109 | 0.4109 | No | 0.0260 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| T S2 APARTMENT | SPLIT TS2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4082 | 0.4082 | 0.4082 | No | 0.0260 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
| SPLIT GSW | 0.3897 | 0.3897 | 0.3897 | 0.3897 | 0.0260 | 1.0000 |
| SPLIT GNW | 0.3191 | 0.3191 | 0.3191 | 0.3191 | 0.0260 | 1.0000 |
| SPLIT OFFICE | 0.4098 | 0.4098 | 0.4098 | 0.4098 | 0.0381 | 1.0000 |
| SPLIT GNE | 0.2808 | 0.2808 | 0.2808 | 0.2808 | 0.0260 | 1.0000 |
| SPLIT GN1 | 0.2510 | 0.2510 | 0.2510 | 0.2510 | 0.0260 | 1.0000 |
| SPLIT GN2 | 0.2505 | 0.2505 | 0.2505 | 0.2505 | 0.0260 | 1.0000 |
| SPLIT GS1 | 0.3260 | 0.3260 | 0.3260 | 0.3260 | 0.0260 | 1.0000 |
| SPLIT GS2 | 0.3279 | 0.3279 | 0.3279 | 0.3279 | 0.0260 | 1.0000 |
| SPLIT MSW | 0.9778 | 0.9778 | 0.9778 | 0.9778 | 0.0519 | 1.0000 |
| SPLIT MNW | 0.8382 | 0.8382 | 0.8382 | 0.8382 | 0.0519 | 1.0000 |
| SPLIT MSE | 0.8387 | 0.8387 | 0.8387 | 0.8387 | 0.0519 | 1.0000 |
| SPLIT MNE | 0.7034 | 0.7034 | 0.7034 | 0.7034 | 0.0519 | 1.0000 |
| SPLIT MN1 | 0.6278 | 0.6278 | 0.6278 | 0.6278 | 0.0519 | 1.0000 |
| SPLIT MN2 | 0.6262 | 0.6262 | 0.6262 | 0.6262 | 0.0519 | 1.0000 |
| SPLIT MS1 | 0.7754 | 0.7754 | 0.7754 | 0.7754 | 0.0519 | 1.0000 |
| SPLIT MS2 | 0.7735 | 0.7735 | 0.7735 | 0.7735 | 0.0519 | 1.0000 |
| SPLIT TSW | 0.5303 | 0.5303 | 0.5303 | 0.5303 | 0.0260 | 1.0000 |
| SPLIT TNW | 0.4645 | 0.4645 | 0.4645 | 0.4645 | 0.0260 | 1.0000 |
| SPLIT TSE | 0.4288 | 0.4288 | 0.4288 | 0.4288 | 0.0260 | 1.0000 |
| SPLIT TNE | 0.3644 | 0.3644 | 0.3644 | 0.3644 | 0.0260 | 1.0000 |
| SPLIT TN1 | 0.3426 | 0.3426 | 0.3426 | 0.3426 | 0.0260 | 1.0000 |
| SPLIT TN2 | 0.3400 | 0.3400 | 0.3400 | 0.3400 | 0.0260 | 1.0000 |
| SPLIT TS1 | 0.4109 | 0.4109 | 0.4109 | 0.4109 | 0.0260 | 1.0000 |
| SPLIT TS2 | 0.4082 | 0.4082 | 0.4082 | 0.4082 | 0.0260 | 1.0000 |
| AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
| G SW APARTMENT | SPLIT GSW | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.3897 | 0.3897 | 0.3897 | No | 0.0260 | 0.1485 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| G NW APARTMENT | SPLIT GNW | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.3191 | 0.3191 | 0.3191 | No | 0.0260 | 0.1540 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| OFFICE | SPLIT OFFICE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4098 | 0.4098 | 0.4098 | No | 0.0381 | 0.1891 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| G NE APARTMENT | SPLIT GNE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.2808 | 0.2808 | 0.2808 | No | 0.0260 | 0.1537 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| G N1 APARTMENT | SPLIT GN1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.2510 | 0.2510 | 0.2510 | No | 0.0260 | 0.2255 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| G N2 APARTMENT | SPLIT GN2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.2505 | 0.2505 | 0.2505 | No | 0.0260 | 0.2255 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| G S1 APARTMENT | SPLIT GS1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.3260 | 0.3260 | 0.3260 | No | 0.0260 | 0.2138 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| G S2 APARTMENT | SPLIT GS2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.3279 | 0.3279 | 0.3279 | No | 0.0260 | 0.2130 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| M SW APARTMENT | SPLIT MSW | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9778 | 0.9778 | 0.9778 | No | 0.0519 | 0.2137 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| M NW APARTMENT | SPLIT MNW | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8382 | 0.8382 | 0.8382 | No | 0.0519 | 0.2275 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| M SE APARTMENT | SPLIT MSE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8387 | 0.8387 | 0.8387 | No | 0.0519 | 0.2131 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| M NE APARTMENT | SPLIT MNE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.7034 | 0.7034 | 0.7034 | No | 0.0519 | 0.2268 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| M N1 APARTMENT | SPLIT MN1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.6278 | 0.6278 | 0.6278 | No | 0.0519 | 0.4083 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| M N2 APARTMENT | SPLIT MN2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.6262 | 0.6262 | 0.6262 | No | 0.0519 | 0.4083 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| M S1 APARTMENT | SPLIT MS1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.7754 | 0.7754 | 0.7754 | No | 0.0519 | 0.3668 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| M S2 APARTMENT | SPLIT MS2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.7735 | 0.7735 | 0.7735 | No | 0.0519 | 0.3667 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| T SW APARTMENT | SPLIT TSW | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.5303 | 0.5303 | 0.5303 | No | 0.0260 | 0.1238 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| T NW APARTMENT | SPLIT TNW | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4645 | 0.4645 | 0.4645 | No | 0.0260 | 0.1285 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| T SE APARTMENT | SPLIT TSE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4288 | 0.4288 | 0.4288 | No | 0.0260 | 0.1235 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| T NE APARTMENT | SPLIT TNE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.3644 | 0.3644 | 0.3644 | No | 0.0260 | 0.1282 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| T N1 APARTMENT | SPLIT TN1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.3426 | 0.3426 | 0.3426 | No | 0.0260 | 0.1842 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| T N2 APARTMENT | SPLIT TN2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.3400 | 0.3400 | 0.3400 | No | 0.0260 | 0.1842 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| T S1 APARTMENT | SPLIT TS1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4109 | 0.4109 | 0.4109 | No | 0.0260 | 0.1747 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| T S2 APARTMENT | SPLIT TS2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4082 | 0.4082 | 0.4082 | No | 0.0260 | 0.1747 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
| SPLIT GSW | 0.3897 | 0.3897 | 0.3897 | 0.3897 | 0.0260 | 1.0000 |
| SPLIT GNW | 0.3191 | 0.3191 | 0.3191 | 0.3191 | 0.0260 | 1.0000 |
| SPLIT OFFICE | 0.4098 | 0.4098 | 0.4098 | 0.4098 | 0.0381 | 1.0000 |
| SPLIT GNE | 0.2808 | 0.2808 | 0.2808 | 0.2808 | 0.0260 | 1.0000 |
| SPLIT GN1 | 0.2510 | 0.2510 | 0.2510 | 0.2510 | 0.0260 | 1.0000 |
| SPLIT GN2 | 0.2505 | 0.2505 | 0.2505 | 0.2505 | 0.0260 | 1.0000 |
| SPLIT GS1 | 0.3260 | 0.3260 | 0.3260 | 0.3260 | 0.0260 | 1.0000 |
| SPLIT GS2 | 0.3279 | 0.3279 | 0.3279 | 0.3279 | 0.0260 | 1.0000 |
| SPLIT MSW | 0.9778 | 0.9778 | 0.9778 | 0.9778 | 0.0519 | 1.0000 |
| SPLIT MNW | 0.8382 | 0.8382 | 0.8382 | 0.8382 | 0.0519 | 1.0000 |
| SPLIT MSE | 0.8387 | 0.8387 | 0.8387 | 0.8387 | 0.0519 | 1.0000 |
| SPLIT MNE | 0.7034 | 0.7034 | 0.7034 | 0.7034 | 0.0519 | 1.0000 |
| SPLIT MN1 | 0.6278 | 0.6278 | 0.6278 | 0.6278 | 0.0519 | 1.0000 |
| SPLIT MN2 | 0.6262 | 0.6262 | 0.6262 | 0.6262 | 0.0519 | 1.0000 |
| SPLIT MS1 | 0.7754 | 0.7754 | 0.7754 | 0.7754 | 0.0519 | 1.0000 |
| SPLIT MS2 | 0.7735 | 0.7735 | 0.7735 | 0.7735 | 0.0519 | 1.0000 |
| SPLIT TSW | 0.5303 | 0.5303 | 0.5303 | 0.5303 | 0.0260 | 1.0000 |
| SPLIT TNW | 0.4645 | 0.4645 | 0.4645 | 0.4645 | 0.0260 | 1.0000 |
| SPLIT TSE | 0.4288 | 0.4288 | 0.4288 | 0.4288 | 0.0260 | 1.0000 |
| SPLIT TNE | 0.3644 | 0.3644 | 0.3644 | 0.3644 | 0.0260 | 1.0000 |
| SPLIT TN1 | 0.3426 | 0.3426 | 0.3426 | 0.3426 | 0.0260 | 1.0000 |
| SPLIT TN2 | 0.3400 | 0.3400 | 0.3400 | 0.3400 | 0.0260 | 1.0000 |
| SPLIT TS1 | 0.4109 | 0.4109 | 0.4109 | 0.4109 | 0.0260 | 1.0000 |
| SPLIT TS2 | 0.4082 | 0.4082 | 0.4082 | 0.4082 | 0.0260 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 09:14:30
Sec1.1A-General Information| Data | |
| Weather File | RUNPERIOD 1 ** Fairbanks Intl Arpt AK USA TMY3 WMO#=702610 |
| Total gross floor area [m2] | 3134.61 |
| Principal Heating Source | Natural Gas |
| Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
| G SW APARTMENT | 88.25 | 88.25 | 0.00 | 117.85 |
| G NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
| OFFICE | 88.25 | 88.25 | 0.00 | 33.56 |
| G NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
| G N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
| G N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
| G S1 APARTMENT | 88.25 | 88.25 | 0.00 | 117.85 |
| G S2 APARTMENT | 88.25 | 88.25 | 0.00 | 117.85 |
| M SW APARTMENT | 88.25 | 88.25 | 0.00 | 117.85 |
| M NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
| M SE APARTMENT | 88.25 | 88.25 | 0.00 | 117.85 |
| M NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
| M N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
| M N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
| M S1 APARTMENT | 88.25 | 88.25 | 0.00 | 117.85 |
| M S2 APARTMENT | 88.25 | 88.25 | 0.00 | 117.85 |
| T SW APARTMENT | 88.25 | 88.25 | 0.00 | 117.85 |
| T NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
| T SE APARTMENT | 88.25 | 88.25 | 0.00 | 117.85 |
| T NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
| T N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
| T N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
| T S1 APARTMENT | 88.25 | 88.25 | 0.00 | 117.85 |
| T S2 APARTMENT | 88.25 | 88.25 | 0.00 | 117.85 |
| T CORRIDOR | 77.66 | 0.00 | 77.66 | 168.00 |
| G CORRIDOR | 77.66 | 0.00 | 77.66 | 168.00 |
| M CORRIDOR | 77.66 | 0.00 | 77.66 | 168.00 |
| Totals | 3134.61 | 2823.98 | 310.64 |
| Data | |
| Number of hours heating loads not met | 0.00 |
| Number of hours cooling loads not met | 0.00 |
| Number of hours not met | 0.00 |
| Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
| None |
| Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
| Heating -- General | 0.00 | 0.00 | 1217.05 | 151176.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Cooling -- General | 45.39 | 19724.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Lighting -- LightsWired | 94.96 | 5496.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Lighting -- LightsPlugIn | 4.27 | 407.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Lighting -- General | 49.63 | 3183.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment -- MiscPlug | 388.06 | 18541.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment -- ElevatorLift | 65.48 | 4006.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment -- ElevatorLightsFan | 5.11 | 162.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans -- Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans -- General | 105.31 | 7344.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Recovery -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems -- Water Heater | 557.88 | 50200.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Process Subtotal [GJ] | Total Energy Use [GJ] | |
| Electricity | 458.66 | 1316.10 |
| Natural Gas | 0.00 | 1217.05 |
| Additional | 0.00 | 0.00 |
| Total | 458.66 | 2533.14 |
| Process Subtotal [$] | Total Energy Cost [$] | |
| Electricity | 0.00 | |
| Natural Gas | 0.00 | |
| Additional | 0.00 | |
| Total | 0.00 |
| Rated Capacity [kW] | Annual Energy Generated [GJ] | |
| Photovoltaic | 0.00 | 0.00 |
| Wind | 0.00 | 0.00 |
| Electricty [MJ/m2] | |
| Interior Lighting (All) | 31.66 |
| Space Heating | 0.00 |
| Space Cooling | 14.48 |
| Fans (All) | 33.60 |
| Service Water Heating | 177.97 |
| Receptacle Equipment | 146.32 |
| Miscellaneous (All) | 419.86 |
| Subtotal | 419.86 |
| Natural Gas [MJ/m2] | |
| Space Heating | 388.26 |
| Service Water Heating | 0.00 |
| Miscellaneous (All) | 388.26 |
| Subtotal | 388.26 |
| Additional [MJ/m2] | |
| Subtotal | 0.00 |
| Miscellaneous | 0.00 |
| Percent [%] | |
| Interior Lighting (All) | 3.92 |
| Space Heating | 48.04 |
| Space Cooling | 1.79 |
| Fans (All) | 4.16 |
| Service Water Heating | 22.02 |
| Receptacle Equipment | 18.11 |
| Miscellaneous | 1.96 |
| Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
| OCC_APT_SCH_STAY_HOME_FAMILY | 5993. | 8760. |
| OCC_APT_SCH_CORRIDOR | 5993. | 8760. |
| OCC_APT_SCH_WORKING_FAMILY | 5845. | 6055. |
| OCC_OFF_SCH | 2210. | 2340. |
| OCC_OFF_W_SB_SCH | 1820. | 1820. |
| LTG_SCH_OFFICE | 2435. | 8760. |
| LTG_SCH_CORRIDOR | 8760. | 8760. |
| LTG_SCH_APARTMENT_HARDWIRED | 527. | 8760. |
| LTG_SCH_APARTMENT_PLUGIN | 527. | 8760. |
| EQP_APT_SCH | 5763. | 8760. |
| EQP_OFF_SCH | 4531. | 8760. |
| INF_APT_SCH | 8760. | 8760. |
| INF_OFF_SCH | 8760. | 8760. |
| INF_COR_SCH | 8760. | 8760. |
| INFIL_DOOR_OPENING_SCH | 1466. | 5840. |
| ALL OFF | 0. | 0. |
| ALL ON | 8760. | 8760. |
| ALWAYS_ON | 8760. | 8760. |
| ALLON_EXCEPT_DD | 8760. | 8760. |
| EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
| FAN_OFF_W_SB_SCH | 8240. | 8240. |
| APT_DHW_SCH | 4592. | 8760. |
| EXTERIOR_LTG_SCH | 4380. | 4380. |
| BLDG_ELEVATORS | 2270. | 8760. |
| ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
| ELEV_LIGHT_FAN_SCH_ADD_DF | 2154. | 8760. |
| SLIDING_DOORS_VENTILATION_AVAILABILITY_SCH | 5840. | 5840. |
| First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
| HTGSETP_APT_SCH | APTHEATINGSETPOINT | January | 21.10 | 365 | 21.10 | 365 |
| HTGSETP_DESIGN_OFF_SCH | OFFHEATINGSETPOINT | January | 21.10 | 365 | 21.10 | 365 |
| CLGSETP_APT_SCH | APTCOOLINGSETPOINT | July | 24.00 | 365 | 24.00 | 365 |
| CLGSETP_DESIGN_OFF_SCH | OFFCOOLINGSETPOINT | July | 23.90 | 365 | 23.90 | 365 |
| S HTGSETP_APT_SCH | S APARTMENT DUAL SP CONTROL | January | 21.10 | 365 | 21.10 | 365 |
| S CLGSETP_APT_SCH | S APARTMENT DUAL SP CONTROL | July | 24.00 | 365 | 24.00 | 365 |
| N HTGSETP_APT_SCH | N APARTMENT DUAL SP CONTROL | January | 21.10 | 365 | 21.10 | 365 |
| N CLGSETP_APT_SCH | N APARTMENT DUAL SP CONTROL | July | 24.00 | 365 | 24.00 | 365 |
| HTGSETP_OFF_SCH_YES_OPTIMUM | OFFICE DUAL SP CONTROL | January | 21.10 | 365 | 15.60 | 365 |
| CLGSETP_OFF_SCH_YES_OPTIMUM | OFFICE DUAL SP CONTROL | July | 24.00 | 365 | 29.40 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 09:14:30
Heat Index Hours| Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
| G SW APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| G NW APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| OFFICE | 8463.33 | 296.67 | 0.00 | 0.00 | 0.00 |
| G NE APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| G N1 APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| G N2 APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| G S1 APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| G S2 APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M SW APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M NW APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M SE APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M NE APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M N1 APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M N2 APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M S1 APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M S2 APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T SW APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T NW APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T SE APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T NE APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T N1 APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T N2 APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T S1 APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T S2 APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T CORRIDOR | 7752.83 | 999.00 | 8.17 | 0.00 | 0.00 |
| G CORRIDOR | 8750.33 | 9.67 | 0.00 | 0.00 | 0.00 |
| M CORRIDOR | 6606.50 | 2153.50 | 0.00 | 0.00 | 0.00 |
| Min | 6606.50 | 0.00 | 0.00 | 0.00 | 0.00 |
| Max | 8760.00 | 2153.50 | 8.17 | 0.00 | 0.00 |
| Average | 8631.59 | 128.10 | 0.30 | 0.00 | 0.00 |
| Sum | 233053.00 | 3458.83 | 8.17 | 0.00 | 0.00 |
| Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
| G SW APARTMENT | 11830.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| G NW APARTMENT | 10585.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| OFFICE | 7000.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| G NE APARTMENT | 10585.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| G N1 APARTMENT | 10585.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| G N2 APARTMENT | 10585.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| G S1 APARTMENT | 11830.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| G S2 APARTMENT | 11830.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M SW APARTMENT | 11830.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M NW APARTMENT | 10585.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M SE APARTMENT | 11830.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M NE APARTMENT | 10585.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M N1 APARTMENT | 10585.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M N2 APARTMENT | 10585.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M S1 APARTMENT | 11830.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M S2 APARTMENT | 11830.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T SW APARTMENT | 11830.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T NW APARTMENT | 10585.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T SE APARTMENT | 11830.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T NE APARTMENT | 10585.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T N1 APARTMENT | 10585.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T N2 APARTMENT | 10585.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T S1 APARTMENT | 11830.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T S2 APARTMENT | 11830.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T CORRIDOR | 20547.00 | 2419.50 | 28.50 | 0.00 | 0.00 |
| G CORRIDOR | 22963.33 | 31.67 | 0.00 | 0.00 | 0.00 |
| M CORRIDOR | 17403.17 | 5591.83 | 0.00 | 0.00 | 0.00 |
| Min | 7000.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Max | 22963.33 | 5591.83 | 28.50 | 0.00 | 0.00 |
| Average | 12039.39 | 297.89 | 1.06 | 0.00 | 0.00 |
| Sum | 325063.50 | 8043.00 | 28.50 | 0.00 | 0.00 |
| Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
| G SW APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| G NW APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| OFFICE | 8567.17 | 192.83 | 0.00 | 0.00 | 0.00 |
| G NE APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| G N1 APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| G N2 APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| G S1 APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| G S2 APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M SW APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M NW APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M SE APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M NE APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M N1 APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M N2 APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M S1 APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M S2 APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T SW APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T NW APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T SE APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T NE APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T N1 APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T N2 APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T S1 APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T S2 APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T CORRIDOR | 5285.17 | 3410.50 | 64.33 | 0.00 | 0.00 |
| G CORRIDOR | 8344.67 | 415.33 | 0.00 | 0.00 | 0.00 |
| M CORRIDOR | 2741.00 | 5878.67 | 140.33 | 0.00 | 0.00 |
| Min | 2741.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Max | 8760.00 | 5878.67 | 140.33 | 0.00 | 0.00 |
| Average | 8385.85 | 366.57 | 7.58 | 0.00 | 0.00 |
| Sum | 226418.00 | 9897.33 | 204.67 | 0.00 | 0.00 |
| Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
| G SW APARTMENT | 11830.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| G NW APARTMENT | 10585.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| OFFICE | 7000.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| G NE APARTMENT | 10585.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| G N1 APARTMENT | 10585.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| G N2 APARTMENT | 10585.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| G S1 APARTMENT | 11830.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| G S2 APARTMENT | 11830.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M SW APARTMENT | 11830.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M NW APARTMENT | 10585.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M SE APARTMENT | 11830.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M NE APARTMENT | 10585.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M N1 APARTMENT | 10585.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M N2 APARTMENT | 10585.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M S1 APARTMENT | 11830.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M S2 APARTMENT | 11830.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T SW APARTMENT | 11830.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T NW APARTMENT | 10585.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T SE APARTMENT | 11830.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T NE APARTMENT | 10585.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T N1 APARTMENT | 10585.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T N2 APARTMENT | 10585.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T S1 APARTMENT | 11830.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T S2 APARTMENT | 11830.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T CORRIDOR | 13858.67 | 8959.33 | 177.00 | 0.00 | 0.00 |
| G CORRIDOR | 21345.33 | 1649.67 | 0.00 | 0.00 | 0.00 |
| M CORRIDOR | 6941.00 | 15708.83 | 345.17 | 0.00 | 0.00 |
| Min | 6941.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Max | 21345.33 | 15708.83 | 345.17 | 0.00 | 0.00 |
| Average | 11344.26 | 974.73 | 19.34 | 0.00 | 0.00 |
| Sum | 306295.00 | 26317.83 | 522.17 | 0.00 | 0.00 |
| SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
| None |
| SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
| None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 09:14:30
CO2 Level Hours| Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
| None |
| Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
| None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 09:14:30
Illuminance Level Hours| A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
| None |
| A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
| None |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
| January | -17.62 |
| February | -15.41 |
| March | -10.29 |
| April | 0.726 |
| May | 10.596 |
| June | 15.955 |
| July | 16.857 |
| August | 14.239 |
| September | 6.723 |
| October | -3.07 |
| November | -17.64 |
| December | -19.26 |
| Annual Sum or Average | -1.44 |
| Minimum of Months | -19.26 |
| Maximum of Months | 16.857 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Environment
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
| January | -17.62 |
| February | -15.41 |
| March | -10.29 |
| April | 0.726 |
| May | 10.596 |
| June | 15.955 |
| July | 16.857 |
| August | 14.239 |
| September | 6.723 |
| October | -3.07 |
| November | -17.64 |
| December | -19.26 |
| Annual Sum or Average | -1.44 |
| Minimum of Months | -19.26 |
| Maximum of Months | 16.857 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2012
For: Environment
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
| January | -17.62 |
| February | -15.41 |
| March | -10.29 |
| April | 0.726 |
| May | 10.596 |
| June | 15.955 |
| July | 16.857 |
| August | 14.239 |
| September | 6.723 |
| October | -3.07 |
| November | -17.64 |
| December | -19.26 |
| Annual Sum or Average | -1.44 |
| Minimum of Months | -19.26 |
| Maximum of Months | 16.857 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
| January | -17.62 |
| February | -15.41 |
| March | -10.29 |
| April | 0.726 |
| May | 10.596 |
| June | 15.955 |
| July | 16.857 |
| August | 14.239 |
| September | 6.723 |
| October | -3.07 |
| November | -17.64 |
| December | -19.26 |
| Annual Sum or Average | -1.44 |
| Minimum of Months | -19.26 |
| Maximum of Months | 16.857 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME APARTMENTMIDRISE
For: Environment
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
| January | -17.62 |
| February | -15.41 |
| March | -10.29 |
| April | 0.726 |
| May | 10.596 |
| June | 15.955 |
| July | 16.857 |
| August | 14.239 |
| September | 6.723 |
| October | -3.07 |
| November | -17.64 |
| December | -19.26 |
| Annual Sum or Average | -1.44 |
| Minimum of Months | -19.26 |
| Maximum of Months | 16.857 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
| January | -17.62 |
| February | -15.41 |
| March | -10.29 |
| April | 0.726 |
| May | 10.596 |
| June | 15.955 |
| July | 16.857 |
| August | 14.239 |
| September | 6.723 |
| October | -3.07 |
| November | -17.64 |
| December | -19.26 |
| Annual Sum or Average | -1.44 |
| Minimum of Months | -19.26 |
| Maximum of Months | 16.857 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
| January | -17.62 |
| February | -15.41 |
| March | -10.29 |
| April | 0.726 |
| May | 10.596 |
| June | 15.955 |
| July | 16.857 |
| August | 14.239 |
| September | 6.723 |
| October | -3.07 |
| November | -17.64 |
| December | -19.26 |
| Annual Sum or Average | -1.44 |
| Minimum of Months | -19.26 |
| Maximum of Months | 16.857 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 8
For: Environment
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
| January | -17.62 |
| February | -15.41 |
| March | -10.29 |
| April | 0.726 |
| May | 10.596 |
| June | 15.955 |
| July | 16.857 |
| August | 14.239 |
| September | 6.723 |
| October | -3.07 |
| November | -17.64 |
| December | -19.26 |
| Annual Sum or Average | -1.44 |
| Minimum of Months | -19.26 |
| Maximum of Months | 16.857 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_AK_FAIRBANKS
For: Environment
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
| January | -17.62 |
| February | -15.41 |
| March | -10.29 |
| April | 0.726 |
| May | 10.596 |
| June | 15.955 |
| July | 16.857 |
| August | 14.239 |
| September | 6.723 |
| October | -3.07 |
| November | -17.64 |
| December | -19.26 |
| Annual Sum or Average | -1.44 |
| Minimum of Months | -19.26 |
| Maximum of Months | 16.857 |
Report: ZoneCoolingSummaryMonthly
For: G SW APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | -14.9 | -15.4 | 78198344.25 | 42.51 | 31-JAN-19:19 | -16.1 | -16.9 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | -20.2 | -20.7 | 69628662.61 | 42.51 | 27-FEB-19:10 | -26.2 | -26.4 |
| March | 9506031.48 | 341.04 | 22-MAR-16:08 | 5.60 | 2.47 | 74984713.52 | 42.51 | 16-MAR-17:00 | 5.60 | 2.47 |
| April | 0.419818E+09 | 660.41 | 23-APR-22:20 | -0.8 | -3.6 | 78630298.75 | 70.28 | 21-APR-18:00 | -0.8 | -3.6 |
| May | 0.838379E+09 | 879.00 | 15-MAY-16:25 | 15.00 | 6.93 | 95491969.24 | 70.37 | 21-MAY-20:49 | 13.35 | 7.08 |
| June | 0.141069E+10 | 1658.68 | 21-JUN-16:30 | 25.85 | 14.28 | 0.115834E+09 | 70.36 | 16-JUN-00:10 | 25.85 | 14.28 |
| July | 0.188169E+10 | 1950.51 | 12-JUL-16:30 | 25.00 | 13.76 | 0.127484E+09 | 70.37 | 04-JUL-18:40 | 25.00 | 13.76 |
| August | 0.176346E+10 | 2113.97 | 11-AUG-16:06 | 25.60 | 14.73 | 0.119998E+09 | 70.37 | 19-AUG-18:30 | 13.30 | 9.91 |
| September | 0.899732E+09 | 871.33 | 09-SEP-15:50 | 15.50 | 9.00 | 93741846.72 | 70.36 | 01-SEP-20:19 | 15.50 | 9.00 |
| October | 0.135837E+09 | 547.66 | 14-OCT-13:00 | 2.80 | -1.7 | 77325282.43 | 51.29 | 01-OCT-15:50 | 2.80 | -1.7 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | -10.0 | -10.9 | 74984713.60 | 42.51 | 03-NOV-18:10 | -5.6 | -7.1 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | -25.8 | -26.0 | 78198344.29 | 42.51 | 15-DEC-19:10 | -26.9 | -27.2 |
| Annual Sum or Average | 0.735912E+10 | 0.108450E+10 | ||||||||
| Minimum of Months | 0.00 | 0.00 | -25.8 | -26.0 | 69628662.61 | 42.51 | -26.9 | -27.2 | ||
| Maximum of Months | 0.188169E+10 | 2113.97 | 25.85 | 14.73 | 0.127484E+09 | 70.37 | 25.85 | 14.28 |
Report: ZoneCoolingSummaryMonthly
For: G NW APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | -14.9 | -15.4 | 77895344.74 | 42.51 | 18-JAN-23:10 | -11.3 | -11.4 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | -20.2 | -20.7 | 70357085.49 | 42.51 | 01-FEB-22:00 | -12.8 | -13.0 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | -28.9 | -29.2 | 77895344.63 | 42.51 | 16-MAR-21:00 | -6.1 | -7.9 |
| April | 64231013.65 | 372.28 | 20-APR-20:10 | 8.53 | 4.15 | 75629681.19 | 49.67 | 21-APR-20:10 | 11.83 | 4.93 |
| May | 0.476455E+09 | 507.62 | 19-MAY-04:10 | 3.98 | 1.52 | 84930679.36 | 62.43 | 14-MAY-20:40 | 3.98 | 1.52 |
| June | 0.103110E+10 | 1231.34 | 21-JUN-17:50 | 25.68 | 14.23 | 0.116960E+09 | 70.37 | 13-JUN-00:10 | 25.68 | 14.23 |
| July | 0.137548E+10 | 1481.44 | 11-JUL-19:00 | 25.60 | 14.96 | 0.125865E+09 | 70.36 | 01-JUL-01:10 | 25.60 | 14.96 |
| August | 0.110784E+10 | 1230.45 | 11-AUG-17:40 | 25.60 | 14.82 | 0.119871E+09 | 70.36 | 06-AUG-04:00 | 25.60 | 14.82 |
| September | 0.509475E+09 | 519.52 | 03-SEP-07:00 | 3.90 | 3.43 | 79359653.53 | 59.68 | 02-SEP-20:10 | 3.90 | 3.43 |
| October | 19117004.80 | 382.29 | 01-OCT-20:10 | 8.03 | 4.70 | 77882650.12 | 42.51 | 23-OCT-21:00 | -5.0 | -5.2 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | -10.0 | -10.9 | 75382591.63 | 42.51 | 10-NOV-06:49 | -15.5 | -16.3 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | -25.8 | -26.0 | 77895344.75 | 42.51 | 22-DEC-22:00 | -17.8 | -18.1 |
| Annual Sum or Average | 0.458370E+10 | 0.105992E+10 | ||||||||
| Minimum of Months | 0.00 | 0.00 | -28.9 | -29.2 | 70357085.49 | 42.51 | -17.8 | -18.1 | ||
| Maximum of Months | 0.137548E+10 | 1481.44 | 25.68 | 14.96 | 0.125865E+09 | 70.37 | 25.68 | 14.96 |
Report: ZoneCoolingSummaryMonthly
For: OFFICE
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.102925E+09 | 2214.23 | 12-JAN-07:03 | -38.3 | -38.4 | 38868427.82 | 80.76 | 03-JAN-13:00 | -38.3 | -38.4 |
| February | 0.208773E+09 | 1853.41 | 27-FEB-07:03 | -34.9 | -35.0 | 36925007.02 | 80.76 | 01-FEB-13:00 | -34.9 | -35.0 |
| March | 0.541711E+09 | 1792.80 | 01-MAR-07:03 | -28.8 | -29.2 | 44696972.19 | 80.76 | 02-MAR-15:30 | -11.1 | -13.0 |
| April | 0.713497E+09 | 1468.16 | 03-APR-06:03 | -21.5 | -22.1 | 43653902.88 | 133.51 | 21-APR-15:00 | 14.40 | 5.45 |
| May | 0.794251E+09 | 5716.60 | 15-MAY-08:62 | 10.87 | 4.39 | 71025641.73 | 164.46 | 15-MAY-08:09 | 10.87 | 4.39 |
| June | 0.126213E+10 | 6172.98 | 13-JUN-07:02 | 15.87 | 10.70 | 76592499.80 | 192.97 | 14-JUN-07:10 | 17.88 | 11.65 |
| July | 0.146903E+10 | 6537.67 | 13-JUL-07:01 | 11.38 | 8.77 | 70044560.92 | 217.45 | 24-JUL-07:10 | 15.87 | 13.75 |
| August | 0.152321E+10 | 6441.25 | 28-AUG-08:62 | 8.68 | 7.17 | 79818945.38 | 186.87 | 03-AUG-07:10 | 8.68 | 7.17 |
| September | 0.843254E+09 | 1835.46 | 01-SEP-08:65 | 9.08 | 7.58 | 57659404.86 | 150.09 | 01-SEP-08:09 | 9.08 | 7.58 |
| October | 0.716587E+09 | 1422.84 | 27-OCT-07:03 | -18.7 | -19.1 | 42733057.05 | 118.75 | 03-OCT-15:20 | -18.7 | -19.1 |
| November | 0.284105E+09 | 1818.62 | 30-NOV-08:03 | -28.3 | -28.5 | 38868418.85 | 80.76 | 01-NOV-12:09 | -28.3 | -28.5 |
| December | 62912171.15 | 2012.75 | 15-DEC-08:03 | -33.8 | -34.0 | 38868433.28 | 80.76 | 01-DEC-13:09 | -33.8 | -34.0 |
| Annual Sum or Average | 0.852238E+10 | 0.639755E+09 | ||||||||
| Minimum of Months | 62912171.15 | 1422.84 | -38.3 | -38.4 | 36925007.02 | 80.76 | -38.3 | -38.4 | ||
| Maximum of Months | 0.152321E+10 | 6537.67 | 15.87 | 10.70 | 79818945.38 | 217.45 | 17.88 | 13.75 |
Report: ZoneCoolingSummaryMonthly
For: G NE APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | -14.9 | -15.4 | 77895344.73 | 42.51 | 18-JAN-23:10 | -11.3 | -11.4 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | -20.2 | -20.7 | 70357085.49 | 42.51 | 01-FEB-22:00 | -12.8 | -13.0 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | -28.9 | -29.2 | 77895344.63 | 42.51 | 16-MAR-21:00 | -6.1 | -7.9 |
| April | 60648290.89 | 324.90 | 22-APR-10:00 | 10.00 | 4.59 | 75424030.19 | 42.88 | 21-APR-20:10 | 10.00 | 4.59 |
| May | 0.609926E+09 | 544.47 | 22-MAY-04:10 | 2.98 | 0.66 | 88224579.30 | 65.66 | 13-MAY-20:10 | 2.98 | 0.66 |
| June | 0.115868E+10 | 1084.91 | 13-JUN-17:15 | 24.60 | 13.98 | 0.118630E+09 | 70.37 | 18-JUN-20:30 | 17.20 | 11.43 |
| July | 0.161911E+10 | 1353.44 | 11-JUL-10:30 | 22.75 | 15.46 | 0.126281E+09 | 70.33 | 16-JUL-23:40 | 12.77 | 11.93 |
| August | 0.123434E+10 | 1062.46 | 11-AUG-17:20 | 25.60 | 14.70 | 0.121044E+09 | 70.36 | 26-AUG-00:30 | 13.35 | 11.33 |
| September | 0.576495E+09 | 531.37 | 03-SEP-07:00 | 3.90 | 3.43 | 80382681.14 | 58.75 | 02-SEP-20:10 | 3.90 | 3.43 |
| October | 30195818.05 | 382.61 | 01-OCT-20:10 | 8.03 | 4.70 | 77884249.63 | 42.51 | 23-OCT-21:00 | -5.0 | -5.2 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | -10.0 | -10.9 | 75382591.63 | 42.51 | 10-NOV-06:49 | -15.5 | -16.3 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | -25.8 | -26.0 | 77895344.75 | 42.51 | 22-DEC-22:00 | -17.8 | -18.1 |
| Annual Sum or Average | 0.528939E+10 | 0.106730E+10 | ||||||||
| Minimum of Months | 0.00 | 0.00 | -28.9 | -29.2 | 70357085.49 | 42.51 | -17.8 | -18.1 | ||
| Maximum of Months | 0.161911E+10 | 1353.44 | 25.60 | 15.46 | 0.126281E+09 | 70.37 | 17.20 | 11.93 |
Report: ZoneCoolingSummaryMonthly
For: G N1 APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | -14.9 | -15.4 | 77895344.70 | 42.51 | 18-JAN-23:10 | -11.3 | -11.4 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | -20.2 | -20.7 | 70357085.50 | 42.51 | 01-FEB-22:00 | -12.8 | -13.0 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | -28.9 | -29.2 | 77895344.65 | 42.51 | 16-MAR-21:00 | -6.1 | -7.9 |
| April | 81459925.18 | 302.06 | 21-APR-20:40 | 10.73 | 4.06 | 75437490.29 | 44.53 | 21-APR-20:10 | 10.73 | 4.06 |
| May | 0.646321E+09 | 546.31 | 17-MAY-04:40 | 2.93 | 2.29 | 86351679.33 | 61.36 | 14-MAY-20:49 | 2.93 | 2.29 |
| June | 0.100289E+10 | 864.81 | 21-JUN-20:00 | 25.00 | 13.79 | 0.119561E+09 | 70.38 | 25-JUN-20:30 | 15.00 | 11.47 |
| July | 0.134431E+10 | 1015.26 | 11-JUL-20:00 | 23.90 | 14.09 | 0.127473E+09 | 70.36 | 01-JUL-22:49 | 23.90 | 14.09 |
| August | 0.110756E+10 | 857.27 | 02-AUG-17:40 | 22.97 | 14.50 | 0.122828E+09 | 70.36 | 15-AUG-22:19 | 13.13 | 11.32 |
| September | 0.705855E+09 | 532.77 | 03-SEP-07:00 | 3.90 | 3.43 | 81249387.96 | 60.12 | 02-SEP-20:10 | 3.90 | 3.43 |
| October | 80886661.27 | 384.21 | 01-OCT-20:10 | 8.03 | 4.70 | 77890941.64 | 42.51 | 23-OCT-21:00 | -5.0 | -5.2 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | -10.0 | -10.9 | 75382591.62 | 42.51 | 10-NOV-06:49 | -15.5 | -16.3 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | -25.8 | -26.0 | 77895344.71 | 42.51 | 22-DEC-22:00 | -17.8 | -18.1 |
| Annual Sum or Average | 0.496929E+10 | 0.107022E+10 | ||||||||
| Minimum of Months | 0.00 | 0.00 | -28.9 | -29.2 | 70357085.50 | 42.51 | -17.8 | -18.1 | ||
| Maximum of Months | 0.134431E+10 | 1015.26 | 25.00 | 14.50 | 0.127473E+09 | 70.38 | 23.90 | 14.09 |
Report: ZoneCoolingSummaryMonthly
For: G N2 APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | -14.9 | -15.4 | 77895344.70 | 42.51 | 18-JAN-23:10 | -11.3 | -11.4 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | -20.2 | -20.7 | 70357085.50 | 42.51 | 01-FEB-22:00 | -12.8 | -13.0 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | -28.9 | -29.2 | 77895344.65 | 42.51 | 16-MAR-21:00 | -6.1 | -7.9 |
| April | 81466897.85 | 297.49 | 28-APR-17:12 | 10.90 | 4.91 | 75433634.51 | 44.28 | 21-APR-20:10 | 10.90 | 4.91 |
| May | 0.660933E+09 | 564.01 | 17-MAY-04:10 | 2.38 | 1.85 | 87013948.70 | 62.32 | 14-MAY-20:49 | 2.38 | 1.85 |
| June | 0.101506E+10 | 858.08 | 21-JUN-20:00 | 25.00 | 13.79 | 0.119800E+09 | 70.37 | 03-JUN-21:00 | 25.00 | 13.79 |
| July | 0.135922E+10 | 1013.93 | 11-JUL-20:00 | 23.90 | 14.09 | 0.127507E+09 | 70.35 | 20-JUL-02:39 | 13.17 | 12.13 |
| August | 0.111757E+10 | 857.81 | 02-AUG-17:30 | 23.05 | 14.51 | 0.122993E+09 | 70.36 | 01-AUG-02:39 | 23.05 | 14.51 |
| September | 0.712605E+09 | 534.16 | 03-SEP-07:00 | 3.90 | 3.43 | 81514406.51 | 60.48 | 02-SEP-20:10 | 3.90 | 3.43 |
| October | 82929217.66 | 384.24 | 01-OCT-20:10 | 8.03 | 4.70 | 77891183.72 | 42.51 | 23-OCT-21:00 | -5.0 | -5.2 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | -10.0 | -10.9 | 75382591.62 | 42.51 | 10-NOV-06:49 | -15.5 | -16.3 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | -25.8 | -26.0 | 77895344.71 | 42.51 | 22-DEC-22:00 | -17.8 | -18.1 |
| Annual Sum or Average | 0.502979E+10 | 0.107158E+10 | ||||||||
| Minimum of Months | 0.00 | 0.00 | -28.9 | -29.2 | 70357085.50 | 42.51 | -17.8 | -18.1 | ||
| Maximum of Months | 0.135922E+10 | 1013.93 | 25.00 | 14.51 | 0.127507E+09 | 70.37 | 25.00 | 14.51 |
Report: ZoneCoolingSummaryMonthly
For: G S1 APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | -14.9 | -15.4 | 78198344.19 | 42.51 | 31-JAN-19:19 | -16.1 | -16.9 |
| February | 1779931.48 | 139.81 | 15-FEB-14:00 | -8.3 | -9.2 | 69628662.59 | 42.51 | 27-FEB-19:10 | -26.2 | -26.4 |
| March | 71860323.18 | 462.20 | 22-MAR-16:10 | 5.60 | 2.47 | 74984713.53 | 42.51 | 10-MAR-18:00 | 5.60 | 2.47 |
| April | 0.635425E+09 | 690.69 | 24-APR-01:10 | -1.8 | -4.4 | 79330732.93 | 70.27 | 22-APR-16:40 | -1.8 | -4.4 |
| May | 0.100925E+10 | 854.29 | 15-MAY-16:10 | 15.00 | 6.98 | 0.101212E+09 | 70.36 | 09-MAY-19:00 | 15.00 | 6.98 |
| June | 0.142323E+10 | 1299.12 | 21-JUN-16:05 | 25.68 | 14.23 | 0.118277E+09 | 70.37 | 02-JUN-21:49 | 25.68 | 14.23 |
| July | 0.188369E+10 | 1695.94 | 23-JUL-15:10 | 25.60 | 15.39 | 0.128659E+09 | 70.37 | 05-JUL-20:19 | 25.60 | 15.39 |
| August | 0.182395E+10 | 1742.40 | 11-AUG-16:10 | 25.60 | 14.73 | 0.122101E+09 | 70.36 | 07-AUG-02:00 | 25.60 | 14.73 |
| September | 0.111225E+10 | 920.81 | 09-SEP-15:30 | 15.30 | 8.97 | 0.100056E+09 | 70.37 | 02-SEP-22:40 | 15.30 | 8.97 |
| October | 0.346911E+09 | 622.89 | 13-OCT-13:20 | 0.37 | -2.8 | 77781295.66 | 54.60 | 03-OCT-17:10 | 0.37 | -2.8 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | -10.0 | -10.9 | 74984713.57 | 42.51 | 03-NOV-18:10 | -5.6 | -7.1 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | -25.8 | -26.0 | 78198344.21 | 42.51 | 15-DEC-19:10 | -26.9 | -27.2 |
| Annual Sum or Average | 0.830834E+10 | 0.110341E+10 | ||||||||
| Minimum of Months | 0.00 | 0.00 | -25.8 | -26.0 | 69628662.59 | 42.51 | -26.9 | -27.2 | ||
| Maximum of Months | 0.188369E+10 | 1742.40 | 25.68 | 15.39 | 0.128659E+09 | 70.37 | 25.68 | 15.39 |
Report: ZoneCoolingSummaryMonthly
For: G S2 APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | -14.9 | -15.4 | 78198344.20 | 42.51 | 31-JAN-19:19 | -16.1 | -16.9 |
| February | 662114.23 | 91.63 | 15-FEB-14:00 | -8.3 | -9.2 | 69628662.60 | 42.51 | 27-FEB-19:10 | -26.2 | -26.4 |
| March | 48458049.17 | 461.97 | 22-MAR-16:03 | 5.60 | 2.47 | 74984713.53 | 42.51 | 10-MAR-18:00 | 5.60 | 2.47 |
| April | 0.586552E+09 | 684.50 | 24-APR-00:50 | -1.6 | -4.3 | 79047578.08 | 70.27 | 22-APR-16:40 | -1.6 | -4.3 |
| May | 0.105354E+10 | 950.08 | 13-MAY-15:10 | 20.00 | 9.32 | 0.102455E+09 | 70.34 | 18-MAY-21:10 | 11.23 | 5.49 |
| June | 0.153787E+10 | 1349.07 | 21-JUN-16:05 | 25.68 | 14.23 | 0.118698E+09 | 70.37 | 02-JUN-22:49 | 25.68 | 14.23 |
| July | 0.205714E+10 | 1851.28 | 23-JUL-15:10 | 25.60 | 15.39 | 0.128832E+09 | 70.35 | 05-JUL-21:10 | 25.60 | 15.39 |
| August | 0.196858E+10 | 1799.24 | 11-AUG-16:04 | 25.60 | 14.73 | 0.122369E+09 | 70.36 | 19-AUG-20:49 | 11.20 | 9.32 |
| September | 0.113676E+10 | 986.04 | 09-SEP-15:20 | 15.20 | 8.95 | 0.101051E+09 | 70.36 | 11-SEP-19:00 | 10.60 | 8.84 |
| October | 0.311707E+09 | 611.55 | 13-OCT-13:40 | 0.73 | -2.6 | 77703078.69 | 54.33 | 03-OCT-17:10 | 0.73 | -2.6 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | -10.0 | -10.9 | 74984713.57 | 42.51 | 03-NOV-18:10 | -5.6 | -7.1 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | -25.8 | -26.0 | 78198344.22 | 42.51 | 15-DEC-19:10 | -26.9 | -27.2 |
| Annual Sum or Average | 0.870127E+10 | 0.110615E+10 | ||||||||
| Minimum of Months | 0.00 | 0.00 | -25.8 | -26.0 | 69628662.60 | 42.51 | -26.9 | -27.2 | ||
| Maximum of Months | 0.205714E+10 | 1851.28 | 25.68 | 15.39 | 0.128832E+09 | 70.37 | 25.68 | 15.39 |
Report: ZoneCoolingSummaryMonthly
For: M SW APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | -14.9 | -15.4 | 78198344.18 | 42.51 | 31-JAN-19:19 | -16.1 | -16.9 |
| February | 51820277.71 | 726.09 | 15-FEB-14:00 | -8.3 | -9.2 | 69628662.58 | 42.51 | 27-FEB-19:10 | -26.2 | -26.4 |
| March | 0.373164E+09 | 996.23 | 15-MAR-16:35 | -11.7 | -13.8 | 75313329.62 | 56.66 | 22-MAR-17:10 | 5.13 | 1.52 |
| April | 0.134406E+10 | 2133.81 | 22-APR-16:05 | 14.90 | 6.55 | 91865605.13 | 70.28 | 09-APR-16:00 | 14.90 | 6.55 |
| May | 0.211808E+10 | 2318.31 | 31-MAY-15:30 | 21.65 | 10.77 | 0.116920E+09 | 70.31 | 02-MAY-18:49 | 21.65 | 10.77 |
| June | 0.269299E+10 | 2625.50 | 20-JUN-16:08 | 25.68 | 14.79 | 0.119847E+09 | 70.31 | 03-JUN-02:09 | 25.68 | 14.79 |
| July | 0.283316E+10 | 2748.02 | 29-JUL-15:30 | 29.70 | 18.13 | 0.128986E+09 | 70.31 | 03-JUL-02:09 | 29.70 | 18.13 |
| August | 0.238045E+10 | 2845.78 | 10-AUG-16:20 | 22.97 | 12.17 | 0.121708E+09 | 70.32 | 18-AUG-01:00 | 11.10 | 9.32 |
| September | 0.126573E+10 | 1856.54 | 09-SEP-15:50 | 15.50 | 9.00 | 0.101089E+09 | 70.31 | 13-SEP-18:00 | 11.70 | 8.14 |
| October | 0.315303E+09 | 704.18 | 12-OCT-12:20 | -2.2 | -4.3 | 78281954.21 | 59.75 | 03-OCT-17:10 | -2.2 | -4.3 |
| November | 1923108.42 | 222.08 | 08-NOV-15:30 | -15.0 | -15.5 | 74984713.57 | 42.51 | 03-NOV-18:10 | -15.0 | -15.5 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | -25.8 | -26.0 | 78198344.21 | 42.51 | 15-DEC-19:10 | -26.9 | -27.2 |
| Annual Sum or Average | 0.133767E+11 | 0.113502E+10 | ||||||||
| Minimum of Months | 0.00 | 0.00 | -25.8 | -26.0 | 69628662.58 | 42.51 | -26.9 | -27.2 | ||
| Maximum of Months | 0.283316E+10 | 2845.78 | 29.70 | 18.13 | 0.128986E+09 | 70.32 | 29.70 | 18.13 |
Report: ZoneCoolingSummaryMonthly
For: M NW APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | -14.9 | -15.4 | 77895344.70 | 42.51 | 18-JAN-23:10 | -11.3 | -11.4 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | -20.2 | -20.7 | 70357085.49 | 42.51 | 01-FEB-22:00 | -12.8 | -13.0 |
| March | 23896354.96 | 491.87 | 22-MAR-17:12 | 4.67 | 1.29 | 77896982.19 | 42.51 | 16-MAR-21:00 | 4.67 | 1.29 |
| April | 0.577748E+09 | 712.58 | 21-APR-03:00 | -2.2 | -2.9 | 80848073.80 | 70.28 | 21-APR-20:30 | 11.10 | 4.35 |
| May | 0.136647E+10 | 1514.43 | 31-MAY-17:30 | 21.70 | 10.89 | 0.115219E+09 | 70.31 | 19-MAY-20:49 | 21.70 | 10.89 |
| June | 0.222337E+10 | 1998.10 | 21-JUN-17:05 | 26.02 | 14.32 | 0.124091E+09 | 70.30 | 01-JUN-01:49 | 26.02 | 14.32 |
| July | 0.225576E+10 | 2142.58 | 11-JUL-18:00 | 26.10 | 15.12 | 0.128455E+09 | 70.31 | 03-JUL-01:10 | 26.10 | 15.12 |
| August | 0.158182E+10 | 1772.36 | 11-AUG-17:25 | 25.60 | 14.76 | 0.124588E+09 | 70.31 | 23-AUG-01:19 | 12.80 | 11.87 |
| September | 0.781706E+09 | 625.41 | 09-SEP-06:40 | 0.40 | 0.02 | 87522542.32 | 69.75 | 02-SEP-20:10 | 0.40 | 0.02 |
| October | 72583459.86 | 405.77 | 04-OCT-18:10 | 7.43 | 3.81 | 77939022.54 | 42.55 | 01-OCT-20:10 | 7.43 | 3.81 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | -10.0 | -10.9 | 75382591.61 | 42.51 | 10-NOV-06:49 | -15.5 | -16.3 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | -25.8 | -26.0 | 77895344.71 | 42.51 | 22-DEC-22:00 | -17.8 | -18.1 |
| Annual Sum or Average | 0.888334E+10 | 0.111809E+10 | ||||||||
| Minimum of Months | 0.00 | 0.00 | -25.8 | -26.0 | 70357085.49 | 42.51 | -17.8 | -18.1 | ||
| Maximum of Months | 0.225576E+10 | 2142.58 | 26.10 | 15.12 | 0.128455E+09 | 70.31 | 26.10 | 15.12 |
Report: ZoneCoolingSummaryMonthly
For: M SE APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 1979.25 | 3.30 | 23-JAN-13:00 | -10.6 | -11.1 | 78198344.18 | 42.51 | 31-JAN-19:19 | -16.1 | -16.9 |
| February | 66599219.74 | 839.19 | 15-FEB-14:00 | -8.3 | -9.2 | 69628662.58 | 42.51 | 27-FEB-19:10 | -26.2 | -26.4 |
| March | 0.488421E+09 | 1097.31 | 31-MAR-11:00 | -15.0 | -16.4 | 75308621.31 | 58.14 | 22-MAR-17:10 | -15.0 | -16.4 |
| April | 0.133877E+10 | 2021.92 | 22-APR-13:30 | 15.30 | 6.96 | 90893315.07 | 70.29 | 22-APR-21:00 | 6.10 | 1.79 |
| May | 0.242956E+10 | 2368.50 | 12-MAY-13:30 | 20.60 | 9.86 | 0.118023E+09 | 70.31 | 24-MAY-00:10 | 11.42 | 6.03 |
| June | 0.288604E+10 | 2494.39 | 29-JUN-14:10 | 25.68 | 16.21 | 0.119941E+09 | 70.31 | 01-JUN-04:10 | 25.68 | 16.21 |
| July | 0.311656E+10 | 2841.09 | 22-JUL-11:30 | 25.55 | 16.64 | 0.129038E+09 | 70.31 | 17-JUL-01:49 | 25.55 | 16.64 |
| August | 0.256755E+10 | 2695.45 | 10-AUG-14:10 | 22.20 | 12.05 | 0.121944E+09 | 70.31 | 14-AUG-01:19 | 12.60 | 11.10 |
| September | 0.136656E+10 | 1835.12 | 10-SEP-11:30 | 15.00 | 8.08 | 0.102058E+09 | 70.32 | 17-SEP-21:49 | 7.48 | 5.10 |
| October | 0.370174E+09 | 800.94 | 22-OCT-12:00 | -13.9 | -14.5 | 78679407.16 | 61.54 | 03-OCT-17:10 | -13.9 | -14.5 |
| November | 1304264.26 | 130.94 | 08-NOV-12:00 | -15.6 | -16.0 | 74984713.57 | 42.51 | 03-NOV-18:10 | -15.6 | -16.0 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | -25.8 | -26.0 | 78198344.21 | 42.51 | 15-DEC-19:10 | -26.9 | -27.2 |
| Annual Sum or Average | 0.146315E+11 | 0.113690E+10 | ||||||||
| Minimum of Months | 0.00 | 0.00 | -25.8 | -26.0 | 69628662.58 | 42.51 | -26.9 | -27.2 | ||
| Maximum of Months | 0.311656E+10 | 2841.09 | 25.68 | 16.64 | 0.129038E+09 | 70.32 | 25.68 | 16.64 |
Report: ZoneCoolingSummaryMonthly
For: M NE APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | -14.9 | -15.4 | 77895344.69 | 42.51 | 18-JAN-23:10 | -11.3 | -11.4 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | -20.2 | -20.7 | 70357085.49 | 42.51 | 01-FEB-22:00 | -12.8 | -13.0 |
| March | 43851018.88 | 492.76 | 22-MAR-17:12 | 4.67 | 1.29 | 77897260.43 | 42.51 | 16-MAR-21:00 | 4.67 | 1.29 |
| April | 0.586639E+09 | 671.51 | 21-APR-06:00 | -1.1 | -2.4 | 79748242.00 | 64.24 | 21-APR-20:10 | 11.83 | 4.93 |
| May | 0.163624E+10 | 1455.36 | 12-MAY-09:30 | 15.55 | 8.00 | 0.117329E+09 | 70.31 | 14-MAY-01:10 | 9.82 | 4.94 |
| June | 0.241718E+10 | 1860.07 | 13-JUN-06:50 | 15.13 | 10.46 | 0.124130E+09 | 70.31 | 02-JUN-00:20 | 15.13 | 10.46 |
| July | 0.253862E+10 | 1973.47 | 11-JUL-09:50 | 22.02 | 15.12 | 0.128465E+09 | 70.31 | 19-JUL-04:00 | 9.40 | 9.40 |
| August | 0.174608E+10 | 1524.40 | 10-AUG-09:20 | 15.53 | 10.53 | 0.125124E+09 | 70.29 | 27-AUG-02:49 | 10.78 | 9.85 |
| September | 0.825140E+09 | 658.98 | 16-SEP-07:00 | -0.6 | -0.8 | 90025681.92 | 68.02 | 02-SEP-20:10 | -0.6 | -0.8 |
| October | 0.103461E+09 | 450.79 | 04-OCT-18:50 | 5.97 | 3.03 | 77963544.32 | 42.94 | 01-OCT-20:10 | 5.97 | 3.03 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | -10.0 | -10.9 | 75382591.61 | 42.51 | 10-NOV-06:49 | -15.5 | -16.3 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | -25.8 | -26.0 | 77895344.71 | 42.51 | 22-DEC-22:00 | -17.8 | -18.1 |
| Annual Sum or Average | 0.989721E+10 | 0.112221E+10 | ||||||||
| Minimum of Months | 0.00 | 0.00 | -25.8 | -26.0 | 70357085.49 | 42.51 | -17.8 | -18.1 | ||
| Maximum of Months | 0.253862E+10 | 1973.47 | 22.02 | 15.12 | 0.128465E+09 | 70.31 | 15.13 | 10.46 |
Report: ZoneCoolingSummaryMonthly
For: M N1 APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 1431554.50 | 101.38 | 21-JAN-21:00 | -1.1 | -2.7 | 77895344.67 | 42.51 | 18-JAN-23:10 | -1.1 | -2.7 |
| February | 12295102.06 | 193.28 | 09-FEB-19:00 | -7.2 | -7.5 | 70357085.50 | 42.51 | 01-FEB-22:00 | -7.2 | -7.5 |
| March | 93734424.01 | 507.35 | 22-MAR-17:25 | 4.20 | 1.06 | 77897965.68 | 42.51 | 31-MAR-21:00 | -12.7 | -14.3 |
| April | 0.685982E+09 | 705.28 | 21-APR-03:00 | -2.2 | -2.9 | 79520055.75 | 62.01 | 21-APR-20:10 | 11.83 | 4.93 |
| May | 0.131126E+10 | 965.43 | 31-MAY-17:20 | 21.70 | 10.86 | 0.118376E+09 | 70.31 | 23-MAY-05:00 | 21.70 | 10.86 |
| June | 0.191027E+10 | 1301.65 | 21-JUN-20:00 | 25.00 | 13.79 | 0.124460E+09 | 70.31 | 06-JUN-01:00 | 25.00 | 13.79 |
| July | 0.199492E+10 | 1329.93 | 11-JUL-20:00 | 23.90 | 14.09 | 0.128705E+09 | 70.31 | 21-JUL-20:49 | 23.17 | 14.84 |
| August | 0.150202E+10 | 1107.91 | 02-AUG-17:30 | 23.05 | 14.51 | 0.126241E+09 | 70.32 | 18-AUG-02:30 | 10.85 | 9.22 |
| September | 0.950367E+09 | 676.64 | 15-SEP-06:00 | -0.6 | -0.8 | 93110026.61 | 69.15 | 02-SEP-20:10 | -0.6 | -0.8 |
| October | 0.259926E+09 | 536.14 | 04-OCT-20:00 | 3.30 | 1.48 | 78169251.40 | 45.74 | 01-OCT-20:10 | 3.30 | 1.48 |
| November | 735545.83 | 53.97 | 02-NOV-18:00 | -8.9 | -9.2 | 75382591.61 | 42.51 | 10-NOV-06:49 | -15.5 | -16.3 |
| December | 132404.55 | 26.66 | 24-DEC-21:00 | -7.2 | -7.4 | 77895344.68 | 42.51 | 22-DEC-22:00 | -7.2 | -7.4 |
| Annual Sum or Average | 0.872309E+10 | 0.112801E+10 | ||||||||
| Minimum of Months | 132404.55 | 26.66 | -8.9 | -9.2 | 70357085.50 | 42.51 | -15.5 | -16.3 | ||
| Maximum of Months | 0.199492E+10 | 1329.93 | 25.00 | 14.51 | 0.128705E+09 | 70.32 | 25.00 | 14.84 |
Report: ZoneCoolingSummaryMonthly
For: M N2 APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 1439108.02 | 101.70 | 21-JAN-21:00 | -1.1 | -2.7 | 77895344.67 | 42.51 | 18-JAN-23:10 | -1.1 | -2.7 |
| February | 12458046.27 | 193.63 | 09-FEB-19:00 | -7.2 | -7.5 | 70357085.50 | 42.51 | 01-FEB-22:00 | -7.2 | -7.5 |
| March | 96660739.51 | 507.67 | 22-MAR-17:25 | 4.20 | 1.06 | 77898271.80 | 42.51 | 31-MAR-21:00 | -12.7 | -14.3 |
| April | 0.685341E+09 | 688.25 | 21-APR-02:40 | -1.7 | -2.6 | 79489607.14 | 61.62 | 21-APR-20:10 | 11.83 | 4.93 |
| May | 0.132752E+10 | 964.76 | 31-MAY-17:20 | 21.70 | 10.86 | 0.118758E+09 | 70.31 | 17-MAY-22:30 | 21.70 | 10.86 |
| June | 0.191848E+10 | 1290.15 | 21-JUN-20:00 | 25.00 | 13.79 | 0.124462E+09 | 70.30 | 01-JUN-03:49 | 25.00 | 13.79 |
| July | 0.200640E+10 | 1324.59 | 11-JUL-20:00 | 23.90 | 14.09 | 0.128705E+09 | 70.31 | 19-JUL-02:49 | 8.98 | 8.98 |
| August | 0.151104E+10 | 1107.98 | 02-AUG-17:20 | 23.13 | 14.52 | 0.126300E+09 | 70.31 | 08-AUG-02:00 | 12.80 | 11.87 |
| September | 0.955585E+09 | 677.99 | 15-SEP-06:00 | -0.6 | -0.8 | 93733013.20 | 69.55 | 02-SEP-20:10 | -0.6 | -0.8 |
| October | 0.263664E+09 | 536.55 | 04-OCT-20:00 | 3.30 | 1.48 | 78180843.77 | 45.83 | 01-OCT-20:10 | 3.30 | 1.48 |
| November | 738467.92 | 54.16 | 02-NOV-18:00 | -8.9 | -9.2 | 75382591.61 | 42.51 | 10-NOV-06:49 | -15.5 | -16.3 |
| December | 132865.90 | 26.72 | 24-DEC-21:00 | -7.2 | -7.4 | 77895344.68 | 42.51 | 22-DEC-22:00 | -7.2 | -7.4 |
| Annual Sum or Average | 0.877945E+10 | 0.112906E+10 | ||||||||
| Minimum of Months | 132865.90 | 26.72 | -8.9 | -9.2 | 70357085.50 | 42.51 | -15.5 | -16.3 | ||
| Maximum of Months | 0.200640E+10 | 1324.59 | 25.00 | 14.52 | 0.128705E+09 | 70.31 | 25.00 | 13.79 |
Report: ZoneCoolingSummaryMonthly
For: M S1 APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 16429600.99 | 363.85 | 23-JAN-13:00 | -10.6 | -11.1 | 78198344.14 | 42.51 | 09-JAN-18:00 | -10.6 | -11.1 |
| February | 0.242452E+09 | 979.42 | 20-FEB-13:00 | -18.3 | -18.9 | 69628662.57 | 42.51 | 09-FEB-18:10 | -18.3 | -18.9 |
| March | 0.808635E+09 | 1097.34 | 13-MAR-12:00 | -15.0 | -16.2 | 75688858.29 | 57.98 | 22-MAR-17:10 | 5.13 | 1.52 |
| April | 0.155769E+10 | 1778.04 | 22-APR-15:20 | 14.60 | 6.32 | 94766879.12 | 70.31 | 28-APR-20:40 | 4.63 | 2.26 |
| May | 0.208504E+10 | 1883.56 | 12-MAY-13:30 | 20.60 | 9.86 | 0.120398E+09 | 70.32 | 28-MAY-22:10 | 11.42 | 5.83 |
| June | 0.238178E+10 | 1992.34 | 29-JUN-14:30 | 25.85 | 16.16 | 0.120273E+09 | 70.31 | 06-JUN-02:49 | 25.85 | 16.16 |
| July | 0.257472E+10 | 2288.36 | 23-JUL-13:40 | 25.00 | 15.26 | 0.129216E+09 | 70.31 | 21-JUL-20:49 | 25.00 | 15.26 |
| August | 0.232810E+10 | 2244.87 | 10-AUG-14:20 | 22.20 | 12.05 | 0.122949E+09 | 70.30 | 29-AUG-19:00 | 7.80 | 5.06 |
| September | 0.151948E+10 | 1729.29 | 09-SEP-15:10 | 15.10 | 8.93 | 0.106788E+09 | 70.32 | 16-SEP-22:00 | 7.80 | 5.22 |
| October | 0.678164E+09 | 1046.60 | 22-OCT-12:20 | -13.3 | -14.0 | 80514271.13 | 64.51 | 03-OCT-17:10 | -13.3 | -14.0 |
| November | 53157969.31 | 613.33 | 08-NOV-13:40 | -13.5 | -14.3 | 74984713.54 | 42.51 | 03-NOV-18:10 | -13.5 | -14.3 |
| December | 910224.61 | 66.37 | 24-DEC-21:00 | -7.2 | -7.4 | 78198344.15 | 42.51 | 15-DEC-19:10 | -7.2 | -7.4 |
| Annual Sum or Average | 0.142466E+11 | 0.115160E+10 | ||||||||
| Minimum of Months | 910224.61 | 66.37 | -18.3 | -18.9 | 69628662.57 | 42.51 | -18.3 | -18.9 | ||
| Maximum of Months | 0.257472E+10 | 2288.36 | 25.85 | 16.16 | 0.129216E+09 | 70.32 | 25.85 | 16.16 |
Report: ZoneCoolingSummaryMonthly
For: M S2 APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 16566531.87 | 365.26 | 23-JAN-13:00 | -10.6 | -11.1 | 78198344.14 | 42.51 | 09-JAN-18:00 | -10.6 | -11.1 |
| February | 0.244576E+09 | 989.40 | 20-FEB-13:00 | -18.3 | -18.9 | 69628662.57 | 42.51 | 09-FEB-18:10 | -18.3 | -18.9 |
| March | 0.818439E+09 | 1102.61 | 13-MAR-11:50 | -15.2 | -16.3 | 75706879.08 | 58.23 | 22-MAR-17:10 | 5.13 | 1.52 |
| April | 0.155955E+10 | 1783.60 | 22-APR-13:40 | 15.40 | 6.98 | 94741719.62 | 70.31 | 28-APR-20:40 | 4.63 | 2.26 |
| May | 0.210310E+10 | 1902.67 | 12-MAY-13:30 | 20.60 | 9.86 | 0.120495E+09 | 70.31 | 23-MAY-02:09 | 8.80 | 5.38 |
| June | 0.239029E+10 | 2000.58 | 29-JUN-14:30 | 25.85 | 16.16 | 0.120275E+09 | 70.32 | 06-JUN-02:49 | 25.85 | 16.16 |
| July | 0.258616E+10 | 2303.21 | 23-JUL-13:40 | 25.00 | 15.26 | 0.129217E+09 | 70.31 | 31-JUL-03:39 | 7.20 | 6.67 |
| August | 0.233803E+10 | 2258.53 | 10-AUG-14:10 | 22.20 | 12.05 | 0.122959E+09 | 70.32 | 29-AUG-19:00 | 7.80 | 5.06 |
| September | 0.152950E+10 | 1742.42 | 09-SEP-15:10 | 15.10 | 8.93 | 0.106902E+09 | 70.31 | 02-SEP-00:49 | 15.10 | 8.93 |
| October | 0.683283E+09 | 1046.79 | 22-OCT-12:20 | -13.3 | -14.0 | 80629708.73 | 64.78 | 03-OCT-17:10 | -13.3 | -14.0 |
| November | 53205442.13 | 615.90 | 08-NOV-13:40 | -13.5 | -14.3 | 74984713.54 | 42.51 | 03-NOV-18:10 | -13.5 | -14.3 |
| December | 911090.03 | 66.38 | 24-DEC-21:00 | -7.2 | -7.4 | 78198344.15 | 42.51 | 15-DEC-19:10 | -7.2 | -7.4 |
| Annual Sum or Average | 0.143236E+11 | 0.115194E+10 | ||||||||
| Minimum of Months | 911090.03 | 66.38 | -18.3 | -18.9 | 69628662.57 | 42.51 | -18.3 | -18.9 | ||
| Maximum of Months | 0.258616E+10 | 2303.21 | 25.85 | 16.16 | 0.129217E+09 | 70.32 | 25.85 | 16.16 |
Report: ZoneCoolingSummaryMonthly
For: T SW APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | -14.9 | -15.4 | 78198344.28 | 42.51 | 31-JAN-19:19 | -16.1 | -16.9 |
| February | 13267475.28 | 500.79 | 15-FEB-14:00 | -8.3 | -9.2 | 69628662.60 | 42.51 | 27-FEB-19:10 | -26.2 | -26.4 |
| March | 0.219048E+09 | 970.54 | 31-MAR-14:10 | -10.9 | -12.9 | 75402896.48 | 68.31 | 22-MAR-17:10 | -10.9 | -12.9 |
| April | 0.973820E+09 | 2561.77 | 21-APR-16:30 | 14.40 | 5.64 | 85930650.82 | 70.35 | 29-APR-18:40 | 10.00 | 4.62 |
| May | 0.170962E+10 | 3013.83 | 31-MAY-15:30 | 21.65 | 10.77 | 0.100825E+09 | 70.36 | 11-MAY-22:30 | 21.65 | 10.77 |
| June | 0.250160E+10 | 3406.43 | 20-JUN-16:05 | 25.68 | 14.79 | 0.113406E+09 | 70.35 | 18-JUN-23:49 | 25.68 | 14.79 |
| July | 0.268528E+10 | 3632.29 | 29-JUL-15:30 | 29.70 | 18.13 | 0.123807E+09 | 70.35 | 22-JUL-05:10 | 29.70 | 18.13 |
| August | 0.203442E+10 | 3514.61 | 10-AUG-16:10 | 22.88 | 12.15 | 0.111358E+09 | 70.36 | 15-AUG-20:00 | 13.90 | 11.43 |
| September | 0.713213E+09 | 2221.64 | 09-SEP-16:07 | 15.60 | 8.95 | 86301343.00 | 70.36 | 08-SEP-20:10 | 15.60 | 8.95 |
| October | 0.104471E+09 | 762.47 | 03-OCT-14:40 | 12.43 | 6.82 | 77679872.61 | 66.45 | 03-OCT-17:10 | 10.92 | 5.10 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | -10.0 | -10.9 | 74984713.63 | 42.51 | 03-NOV-18:10 | -5.6 | -7.1 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | -25.8 | -26.0 | 78198344.36 | 42.51 | 15-DEC-19:10 | -26.9 | -27.2 |
| Annual Sum or Average | 0.109547E+11 | 0.107572E+10 | ||||||||
| Minimum of Months | 0.00 | 0.00 | -25.8 | -26.0 | 69628662.60 | 42.51 | -26.9 | -27.2 | ||
| Maximum of Months | 0.268528E+10 | 3632.29 | 29.70 | 18.13 | 0.123807E+09 | 70.36 | 29.70 | 18.13 |
Report: ZoneCoolingSummaryMonthly
For: T NW APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | -14.9 | -15.4 | 77895344.74 | 42.51 | 18-JAN-23:10 | -11.3 | -11.4 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | -20.2 | -20.7 | 70357085.46 | 42.51 | 01-FEB-22:00 | -12.8 | -13.0 |
| March | 6713674.75 | 476.81 | 22-MAR-17:01 | 5.13 | 1.52 | 77896210.91 | 42.51 | 16-MAR-21:00 | 5.13 | 1.52 |
| April | 0.302243E+09 | 1021.99 | 21-APR-18:00 | 14.40 | 5.96 | 80139546.55 | 70.27 | 21-APR-20:10 | 11.83 | 4.93 |
| May | 0.980847E+09 | 1921.02 | 31-MAY-17:10 | 21.70 | 10.83 | 0.100442E+09 | 70.36 | 20-MAY-20:00 | 21.70 | 10.83 |
| June | 0.198448E+10 | 2530.08 | 20-JUN-17:30 | 26.40 | 15.03 | 0.119292E+09 | 70.36 | 15-JUN-23:00 | 26.40 | 15.03 |
| July | 0.206352E+10 | 2722.19 | 11-JUL-17:50 | 26.10 | 15.19 | 0.123570E+09 | 70.35 | 18-JUL-23:19 | 12.57 | 12.57 |
| August | 0.123735E+10 | 2116.04 | 11-AUG-17:30 | 25.60 | 14.76 | 0.112580E+09 | 70.35 | 04-AUG-00:49 | 25.60 | 14.76 |
| September | 0.265516E+09 | 448.92 | 02-SEP-19:10 | 15.13 | 9.81 | 80114958.70 | 68.19 | 02-SEP-20:10 | 12.52 | 8.98 |
| October | 12300761.30 | 381.80 | 01-OCT-20:10 | 8.03 | 4.70 | 77886862.09 | 42.51 | 23-OCT-21:00 | -5.0 | -5.2 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | -10.0 | -10.9 | 75382591.63 | 42.51 | 10-NOV-06:49 | -15.5 | -16.3 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | -25.8 | -26.0 | 77895344.79 | 42.51 | 22-DEC-22:00 | -17.8 | -18.1 |
| Annual Sum or Average | 0.685297E+10 | 0.107345E+10 | ||||||||
| Minimum of Months | 0.00 | 0.00 | -25.8 | -26.0 | 70357085.46 | 42.51 | -17.8 | -18.1 | ||
| Maximum of Months | 0.206352E+10 | 2722.19 | 26.40 | 15.19 | 0.123570E+09 | 70.36 | 26.40 | 15.03 |
Report: ZoneCoolingSummaryMonthly
For: T SE APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | -14.9 | -15.4 | 78198344.27 | 42.51 | 31-JAN-19:19 | -16.1 | -16.9 |
| February | 20299152.63 | 659.93 | 15-FEB-14:00 | -8.3 | -9.2 | 69628662.59 | 42.51 | 27-FEB-19:10 | -26.2 | -26.4 |
| March | 0.281222E+09 | 1063.43 | 31-MAR-11:30 | -13.9 | -15.4 | 75315574.41 | 68.11 | 22-MAR-17:10 | -13.9 | -15.4 |
| April | 0.948000E+09 | 2374.57 | 22-APR-13:30 | 15.30 | 6.96 | 84623173.87 | 70.30 | 28-APR-19:19 | 7.23 | 3.54 |
| May | 0.196852E+10 | 2866.77 | 31-MAY-14:00 | 20.00 | 10.15 | 0.101889E+09 | 70.35 | 20-MAY-20:49 | 20.00 | 10.15 |
| June | 0.267394E+10 | 3243.85 | 29-JUN-14:10 | 25.68 | 16.21 | 0.114404E+09 | 70.35 | 24-JUN-18:10 | 25.68 | 16.21 |
| July | 0.295999E+10 | 3629.94 | 23-JUL-13:30 | 25.00 | 15.26 | 0.124382E+09 | 70.36 | 13-JUL-02:00 | 25.00 | 15.26 |
| August | 0.219170E+10 | 3291.44 | 10-AUG-13:50 | 22.12 | 12.08 | 0.111871E+09 | 70.35 | 14-AUG-20:19 | 13.90 | 11.42 |
| September | 0.781183E+09 | 1941.59 | 09-SEP-14:10 | 14.08 | 8.86 | 86740150.50 | 70.34 | 09-SEP-20:40 | 10.37 | 6.41 |
| October | 0.133616E+09 | 881.09 | 03-OCT-14:30 | 12.25 | 6.76 | 77754064.20 | 66.79 | 03-OCT-17:10 | 10.92 | 5.10 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | -10.0 | -10.9 | 74984713.63 | 42.51 | 03-NOV-18:10 | -5.6 | -7.1 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | -25.8 | -26.0 | 78198344.36 | 42.51 | 15-DEC-19:10 | -26.9 | -27.2 |
| Annual Sum or Average | 0.119585E+11 | 0.107799E+10 | ||||||||
| Minimum of Months | 0.00 | 0.00 | -25.8 | -26.0 | 69628662.59 | 42.51 | -26.9 | -27.2 | ||
| Maximum of Months | 0.295999E+10 | 3629.94 | 25.68 | 16.21 | 0.124382E+09 | 70.36 | 25.68 | 16.21 |
Report: ZoneCoolingSummaryMonthly
For: T NE APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | -14.9 | -15.4 | 77895344.74 | 42.51 | 18-JAN-23:10 | -11.3 | -11.4 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | -20.2 | -20.7 | 70357085.47 | 42.51 | 01-FEB-22:00 | -12.8 | -13.0 |
| March | 13591187.07 | 462.08 | 22-MAR-16:07 | 5.60 | 2.47 | 77895339.55 | 42.51 | 16-MAR-21:00 | 5.60 | 2.47 |
| April | 0.293637E+09 | 583.75 | 28-APR-22:00 | 1.70 | 0.71 | 78725739.75 | 67.92 | 21-APR-20:10 | 1.70 | 0.71 |
| May | 0.116393E+10 | 1680.15 | 31-MAY-08:00 | 15.60 | 9.64 | 0.102872E+09 | 70.32 | 13-MAY-21:10 | 15.60 | 9.64 |
| June | 0.217465E+10 | 2218.80 | 29-JUN-10:50 | 22.02 | 15.69 | 0.119531E+09 | 70.36 | 27-JUN-00:49 | 22.02 | 15.69 |
| July | 0.234637E+10 | 2351.26 | 11-JUL-10:10 | 22.38 | 15.32 | 0.123802E+09 | 70.35 | 30-JUL-22:40 | 11.67 | 9.98 |
| August | 0.137232E+10 | 1561.51 | 02-AUG-16:04 | 23.30 | 14.82 | 0.113385E+09 | 70.36 | 06-AUG-20:49 | 12.80 | 11.20 |
| September | 0.316496E+09 | 511.32 | 08-SEP-08:50 | 4.03 | 2.32 | 79825328.25 | 60.55 | 10-SEP-20:10 | 12.43 | 7.73 |
| October | 13697674.15 | 381.67 | 01-OCT-20:10 | 8.03 | 4.70 | 77883447.88 | 42.51 | 23-OCT-21:00 | -5.0 | -5.2 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | -10.0 | -10.9 | 75382591.63 | 42.51 | 10-NOV-06:49 | -15.5 | -16.3 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | -25.8 | -26.0 | 77895344.78 | 42.51 | 22-DEC-22:00 | -17.8 | -18.1 |
| Annual Sum or Average | 0.769469E+10 | 0.107545E+10 | ||||||||
| Minimum of Months | 0.00 | 0.00 | -25.8 | -26.0 | 70357085.47 | 42.51 | -17.8 | -18.1 | ||
| Maximum of Months | 0.234637E+10 | 2351.26 | 23.30 | 15.69 | 0.123802E+09 | 70.36 | 22.02 | 15.69 |
Report: ZoneCoolingSummaryMonthly
For: T N1 APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | -14.9 | -15.4 | 77895344.71 | 42.51 | 18-JAN-23:10 | -11.3 | -11.4 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | -20.2 | -20.7 | 70357085.49 | 42.51 | 01-FEB-22:00 | -12.8 | -13.0 |
| March | 11554903.77 | 406.98 | 22-MAR-16:15 | 5.60 | 2.33 | 77895344.62 | 42.51 | 16-MAR-21:00 | 5.60 | 2.33 |
| April | 0.299443E+09 | 592.90 | 28-APR-22:10 | 1.60 | 0.62 | 78453716.71 | 67.35 | 21-APR-20:10 | 1.60 | 0.62 |
| May | 0.945672E+09 | 1234.93 | 31-MAY-16:25 | 21.95 | 10.80 | 0.102729E+09 | 70.35 | 31-MAY-00:30 | 21.95 | 10.80 |
| June | 0.168923E+10 | 1540.60 | 29-JUN-16:16 | 25.93 | 16.25 | 0.121413E+09 | 70.36 | 27-JUN-04:49 | 25.93 | 16.25 |
| July | 0.180425E+10 | 1607.74 | 11-JUL-17:30 | 26.10 | 15.32 | 0.125691E+09 | 70.36 | 28-JUL-00:40 | 13.33 | 11.44 |
| August | 0.114034E+10 | 1303.70 | 02-AUG-17:30 | 23.05 | 14.51 | 0.115808E+09 | 70.35 | 17-AUG-23:10 | 13.22 | 10.03 |
| September | 0.381020E+09 | 450.10 | 18-SEP-22:00 | 6.10 | 4.14 | 80126605.36 | 62.76 | 02-SEP-20:10 | 6.10 | 4.14 |
| October | 33207077.55 | 384.68 | 01-OCT-20:10 | 8.03 | 4.70 | 77899639.06 | 42.51 | 23-OCT-21:00 | -5.0 | -5.2 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | -10.0 | -10.9 | 75382591.62 | 42.51 | 10-NOV-06:49 | -15.5 | -16.3 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | -25.8 | -26.0 | 77895344.73 | 42.51 | 22-DEC-22:00 | -17.8 | -18.1 |
| Annual Sum or Average | 0.630471E+10 | 0.108155E+10 | ||||||||
| Minimum of Months | 0.00 | 0.00 | -25.8 | -26.0 | 70357085.49 | 42.51 | -17.8 | -18.1 | ||
| Maximum of Months | 0.180425E+10 | 1607.74 | 26.10 | 16.25 | 0.125691E+09 | 70.36 | 25.93 | 16.25 |
Report: ZoneCoolingSummaryMonthly
For: T N2 APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | -14.9 | -15.4 | 77895344.71 | 42.51 | 18-JAN-23:10 | -11.3 | -11.4 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | -20.2 | -20.7 | 70357085.49 | 42.51 | 01-FEB-22:00 | -12.8 | -13.0 |
| March | 12146071.10 | 411.74 | 22-MAR-16:15 | 5.60 | 2.33 | 77895344.62 | 42.51 | 16-MAR-21:00 | 5.60 | 2.33 |
| April | 0.299566E+09 | 591.57 | 28-APR-22:10 | 1.60 | 0.62 | 78402299.69 | 66.65 | 21-APR-20:10 | 1.60 | 0.62 |
| May | 0.963321E+09 | 1230.85 | 31-MAY-16:17 | 22.03 | 10.79 | 0.103145E+09 | 70.35 | 31-MAY-00:30 | 22.03 | 10.79 |
| June | 0.170050E+10 | 1538.13 | 29-JUN-16:14 | 25.93 | 16.25 | 0.121415E+09 | 70.36 | 28-JUN-00:20 | 25.93 | 16.25 |
| July | 0.181939E+10 | 1596.62 | 11-JUL-17:17 | 26.10 | 15.38 | 0.125693E+09 | 70.35 | 16-JUL-01:10 | 13.40 | 10.81 |
| August | 0.115294E+10 | 1297.00 | 02-AUG-17:20 | 23.13 | 14.52 | 0.115913E+09 | 70.37 | 17-AUG-22:00 | 13.30 | 10.07 |
| September | 0.385457E+09 | 448.14 | 18-SEP-22:00 | 6.10 | 4.14 | 80187611.39 | 62.01 | 02-SEP-20:10 | 6.10 | 4.14 |
| October | 34006849.85 | 384.67 | 01-OCT-20:10 | 8.03 | 4.70 | 77899724.38 | 42.51 | 23-OCT-21:00 | -5.0 | -5.2 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | -10.0 | -10.9 | 75382591.62 | 42.51 | 10-NOV-06:49 | -15.5 | -16.3 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | -25.8 | -26.0 | 77895344.73 | 42.51 | 22-DEC-22:00 | -17.8 | -18.1 |
| Annual Sum or Average | 0.636733E+10 | 0.108208E+10 | ||||||||
| Minimum of Months | 0.00 | 0.00 | -25.8 | -26.0 | 70357085.49 | 42.51 | -17.8 | -18.1 | ||
| Maximum of Months | 0.181939E+10 | 1596.62 | 26.10 | 16.25 | 0.125693E+09 | 70.37 | 25.93 | 16.25 |
Report: ZoneCoolingSummaryMonthly
For: T S1 APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | -14.9 | -15.4 | 78198344.21 | 42.51 | 31-JAN-19:19 | -16.1 | -16.9 |
| February | 54731808.92 | 902.05 | 15-FEB-13:40 | -8.7 | -9.6 | 69628662.59 | 42.51 | 27-FEB-19:10 | -26.2 | -26.4 |
| March | 0.365633E+09 | 1028.88 | 31-MAR-12:00 | -12.8 | -14.5 | 75629059.19 | 68.27 | 22-MAR-17:10 | -12.8 | -14.5 |
| April | 0.103547E+10 | 2069.38 | 20-APR-15:10 | 13.80 | 6.27 | 86727767.71 | 70.33 | 25-APR-18:00 | 7.80 | 2.08 |
| May | 0.169103E+10 | 2413.36 | 31-MAY-14:10 | 20.18 | 10.25 | 0.104246E+09 | 70.34 | 10-MAY-22:00 | 20.18 | 10.25 |
| June | 0.219815E+10 | 2711.73 | 29-JUN-14:30 | 25.85 | 16.16 | 0.115938E+09 | 70.36 | 05-JUN-23:30 | 25.85 | 16.16 |
| July | 0.242686E+10 | 3065.87 | 23-JUL-13:50 | 25.00 | 15.26 | 0.126054E+09 | 70.36 | 20-JUL-04:30 | 25.00 | 15.26 |
| August | 0.195269E+10 | 2833.72 | 10-AUG-14:20 | 22.20 | 12.05 | 0.114918E+09 | 70.36 | 07-AUG-22:40 | 22.20 | 12.05 |
| September | 0.898988E+09 | 1852.95 | 09-SEP-15:20 | 15.20 | 8.95 | 89269321.08 | 70.35 | 07-SEP-20:30 | 15.20 | 8.95 |
| October | 0.217440E+09 | 915.94 | 03-OCT-14:30 | 12.25 | 6.76 | 78177500.18 | 69.73 | 03-OCT-17:10 | 10.92 | 5.10 |
| November | 2823281.24 | 254.20 | 08-NOV-13:50 | -13.4 | -14.2 | 74984713.59 | 42.51 | 03-NOV-18:10 | -13.4 | -14.2 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | -25.8 | -26.0 | 78198344.25 | 42.51 | 15-DEC-19:10 | -26.9 | -27.2 |
| Annual Sum or Average | 0.108438E+11 | 0.109197E+10 | ||||||||
| Minimum of Months | 0.00 | 0.00 | -25.8 | -26.0 | 69628662.59 | 42.51 | -26.9 | -27.2 | ||
| Maximum of Months | 0.242686E+10 | 3065.87 | 25.85 | 16.16 | 0.126054E+09 | 70.36 | 25.85 | 16.16 |
Report: ZoneCoolingSummaryMonthly
For: T S2 APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | -14.9 | -15.4 | 78198344.21 | 42.51 | 31-JAN-19:19 | -16.1 | -16.9 |
| February | 55515043.39 | 902.32 | 15-FEB-13:40 | -8.7 | -9.6 | 69628662.59 | 42.51 | 27-FEB-19:10 | -26.2 | -26.4 |
| March | 0.370638E+09 | 1029.77 | 31-MAR-12:00 | -12.8 | -14.5 | 75640344.93 | 68.52 | 22-MAR-17:10 | -12.8 | -14.5 |
| April | 0.103948E+10 | 2075.63 | 20-APR-14:40 | 14.07 | 6.32 | 86629016.95 | 70.33 | 19-APR-20:00 | 14.07 | 6.32 |
| May | 0.171555E+10 | 2431.92 | 31-MAY-14:10 | 20.18 | 10.25 | 0.104307E+09 | 70.36 | 31-MAY-05:49 | 20.18 | 10.25 |
| June | 0.221176E+10 | 2725.88 | 29-JUN-14:30 | 25.85 | 16.16 | 0.115972E+09 | 70.36 | 05-JUN-00:40 | 25.85 | 16.16 |
| July | 0.244307E+10 | 3086.30 | 23-JUL-13:50 | 25.00 | 15.26 | 0.126064E+09 | 70.36 | 10-JUL-00:40 | 25.00 | 15.26 |
| August | 0.196716E+10 | 2857.44 | 10-AUG-14:20 | 22.20 | 12.05 | 0.114962E+09 | 70.36 | 16-AUG-23:49 | 13.30 | 11.13 |
| September | 0.907484E+09 | 1866.83 | 09-SEP-15:20 | 15.20 | 8.95 | 89351676.67 | 70.33 | 10-SEP-20:40 | 11.33 | 7.81 |
| October | 0.220416E+09 | 944.79 | 03-OCT-14:30 | 12.25 | 6.76 | 78200317.61 | 69.85 | 03-OCT-17:10 | 10.92 | 5.10 |
| November | 2858119.51 | 257.57 | 08-NOV-13:50 | -13.4 | -14.2 | 74984713.59 | 42.51 | 03-NOV-18:10 | -13.4 | -14.2 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | -25.8 | -26.0 | 78198344.25 | 42.51 | 15-DEC-19:10 | -26.9 | -27.2 |
| Annual Sum or Average | 0.109339E+11 | 0.109214E+10 | ||||||||
| Minimum of Months | 0.00 | 0.00 | -25.8 | -26.0 | 69628662.59 | 42.51 | -26.9 | -27.2 | ||
| Maximum of Months | 0.244307E+10 | 3086.30 | 25.85 | 16.16 | 0.126064E+09 | 70.36 | 25.85 | 16.16 |
Report: ZoneCoolingSummaryMonthly
For: T CORRIDOR
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | -14.9 | -15.4 | 71646977.51 | 55.60 | 21-JAN-22:19 | -3.3 | -4.1 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | -20.2 | -20.7 | 72209803.56 | 59.43 | 09-FEB-03:49 | 0.87 | 0.30 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | -28.9 | -29.2 | 98627604.59 | 88.25 | 22-MAR-20:10 | 2.70 | 0.26 |
| April | 0.00 | 0.00 | 01-APR-00:10 | -11.7 | -13.3 | 0.146792E+09 | 138.75 | 21-APR-20:10 | 11.83 | 4.93 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 6.70 | 2.18 | 0.217651E+09 | 162.41 | 31-MAY-20:10 | 17.12 | 10.08 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 | 8.14 | 0.259646E+09 | 174.88 | 29-JUN-20:10 | 24.72 | 16.63 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 | 13.77 | 0.269862E+09 | 176.02 | 11-JUL-20:10 | 23.62 | 14.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 16.35 | 11.83 | 0.243689E+09 | 166.98 | 11-AUG-20:10 | 24.13 | 14.70 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 8.08 | 5.90 | 0.156710E+09 | 130.94 | 02-SEP-20:10 | 12.52 | 8.98 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 1.42 | 0.12 | 0.108837E+09 | 94.62 | 03-OCT-20:10 | 6.28 | 2.75 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | -10.0 | -10.9 | 72133810.80 | 51.27 | 01-NOV-22:30 | -9.2 | -9.6 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | -25.8 | -26.0 | 68065078.82 | 55.12 | 24-DEC-22:10 | -4.7 | -5.1 |
| Annual Sum or Average | 0.00 | 0.178587E+10 | ||||||||
| Minimum of Months | 0.00 | 0.00 | -28.9 | -29.2 | 68065078.82 | 51.27 | -9.2 | -9.6 | ||
| Maximum of Months | 0.00 | 0.00 | 16.35 | 13.77 | 0.269862E+09 | 176.02 | 24.72 | 16.63 |
Report: ZoneCoolingSummaryMonthly
For: G CORRIDOR
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | -14.9 | -15.4 | 18382343.62 | 69.53 | 12-JAN-07:19 | -38.3 | -38.4 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | -20.2 | -20.7 | 19948213.03 | 48.19 | 27-FEB-07:19 | -34.8 | -34.9 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | -28.9 | -29.2 | 32078590.54 | 53.93 | 23-MAR-05:10 | -2.8 | -4.2 |
| April | 0.00 | 0.00 | 01-APR-00:10 | -11.7 | -13.3 | 75612442.84 | 88.24 | 22-APR-22:19 | 5.93 | 1.69 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 6.70 | 2.18 | 0.154623E+09 | 128.98 | 13-MAY-21:49 | 14.27 | 6.56 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 | 8.14 | 0.223441E+09 | 158.52 | 21-JUN-21:40 | 22.43 | 13.37 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 | 13.77 | 0.248217E+09 | 175.61 | 29-JUL-17:10 | 29.53 | 18.36 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 16.35 | 11.83 | 0.226140E+09 | 160.93 | 11-AUG-21:49 | 20.47 | 13.46 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 8.08 | 5.90 | 0.128919E+09 | 117.06 | 02-SEP-22:19 | 9.63 | 7.50 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 1.42 | 0.12 | 61185682.96 | 78.16 | 06-OCT-05:10 | 6.60 | 2.71 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | -10.0 | -10.9 | 20735969.80 | 38.96 | 02-NOV-05:10 | -11.0 | -11.4 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | -25.8 | -26.0 | 16442962.10 | 41.38 | 15-DEC-07:19 | -33.5 | -33.6 |
| Annual Sum or Average | 0.00 | 0.122573E+10 | ||||||||
| Minimum of Months | 0.00 | 0.00 | -28.9 | -29.2 | 16442962.10 | 38.96 | -38.3 | -38.4 | ||
| Maximum of Months | 0.00 | 0.00 | 16.35 | 13.77 | 0.248217E+09 | 175.61 | 29.53 | 18.36 |
Report: ZoneCoolingSummaryMonthly
For: M CORRIDOR
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | -14.9 | -15.4 | 0.120259E+09 | 75.39 | 22-JAN-22:10 | -7.3 | -7.6 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | -20.2 | -20.7 | 0.116530E+09 | 79.05 | 09-FEB-22:10 | -9.6 | -9.9 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | -28.9 | -29.2 | 0.144069E+09 | 94.40 | 22-MAR-20:10 | 2.70 | 0.26 |
| April | 0.00 | 0.00 | 01-APR-00:10 | -11.7 | -13.3 | 0.181547E+09 | 136.96 | 22-APR-20:10 | 9.72 | 3.90 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 6.70 | 2.18 | 0.257746E+09 | 157.48 | 31-MAY-20:10 | 17.12 | 10.08 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 | 8.14 | 0.273766E+09 | 164.31 | 29-JUN-20:10 | 24.72 | 16.63 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 | 13.77 | 0.282796E+09 | 165.55 | 11-JUL-20:10 | 23.62 | 14.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 16.35 | 11.83 | 0.271793E+09 | 161.83 | 11-AUG-20:10 | 24.13 | 14.70 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 8.08 | 5.90 | 0.204625E+09 | 141.04 | 02-SEP-20:10 | 12.52 | 8.98 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 1.42 | 0.12 | 0.149807E+09 | 100.83 | 04-OCT-20:10 | 3.30 | 1.48 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | -10.0 | -10.9 | 0.120522E+09 | 74.05 | 01-NOV-22:40 | -9.2 | -9.6 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | -25.8 | -26.0 | 0.117440E+09 | 74.31 | 24-DEC-22:10 | -4.7 | -5.1 |
| Annual Sum or Average | 0.00 | 0.224090E+10 | ||||||||
| Minimum of Months | 0.00 | 0.00 | -28.9 | -29.2 | 0.116530E+09 | 74.05 | -9.6 | -9.9 | ||
| Maximum of Months | 0.00 | 0.00 | 16.35 | 13.77 | 0.282796E+09 | 165.55 | 24.72 | 16.63 |
Report: ZoneHeatingSummaryMonthly
For: G SW APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.437042E+10 | 2767.01 | 29-JAN-00:10 | -25.0 |
| February | 0.337506E+10 | 2638.69 | 24-FEB-08:23 | -25.6 |
| March | 0.244729E+10 | 2259.73 | 01-MAR-08:19 | -27.9 |
| April | 0.613891E+09 | 1396.19 | 02-APR-07:02 | -15.9 |
| May | 23911948.23 | 362.51 | 28-MAY-03:00 | 0.60 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 16.35 |
| September | 47391842.24 | 460.13 | 28-SEP-07:20 | -2.6 |
| October | 0.108974E+10 | 1469.64 | 31-OCT-07:20 | -18.1 |
| November | 0.313160E+10 | 2215.56 | 29-NOV-08:10 | -29.0 |
| December | 0.441531E+10 | 2493.08 | 15-DEC-08:55 | -33.3 |
| Annual Sum or Average | 0.195146E+11 | |||
| Minimum of Months | 0.00 | 0.00 | -33.3 | |
| Maximum of Months | 0.441531E+10 | 2767.01 | 16.35 |
Report: ZoneHeatingSummaryMonthly
For: G NW APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.463718E+10 | 2933.25 | 29-JAN-00:10 | -25.0 |
| February | 0.411071E+10 | 2785.51 | 27-FEB-08:03 | -34.3 |
| March | 0.362835E+10 | 2541.63 | 02-MAR-08:19 | -25.9 |
| April | 0.141460E+10 | 1816.41 | 03-APR-07:18 | -19.7 |
| May | 76548995.54 | 643.05 | 29-MAY-07:01 | 8.40 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 16.35 |
| September | 0.141631E+09 | 593.47 | 30-SEP-05:00 | -4.4 |
| October | 0.163668E+10 | 1687.30 | 31-OCT-07:20 | -18.1 |
| November | 0.355754E+10 | 2299.33 | 29-NOV-08:10 | -29.0 |
| December | 0.451696E+10 | 2484.55 | 15-DEC-08:55 | -33.3 |
| Annual Sum or Average | 0.237202E+11 | |||
| Minimum of Months | 0.00 | 0.00 | -34.3 | |
| Maximum of Months | 0.463718E+10 | 2933.25 | 16.35 |
Report: ZoneHeatingSummaryMonthly
For: OFFICE
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.300013E+10 | 11104.52 | 19-JAN-07:01 | -4.1 |
| February | 0.213899E+10 | 11259.79 | 09-FEB-07:01 | -0.3 |
| March | 0.133683E+10 | 11125.51 | 22-MAR-06:01 | -2.9 |
| April | 0.317952E+09 | 11275.82 | 17-APR-07:01 | 1.88 |
| May | 39362423.74 | 292.26 | 30-MAY-18:00 | 20.60 |
| June | 96858579.31 | 450.16 | 29-JUN-16:12 | 25.93 |
| July | 95744324.65 | 540.40 | 21-JUL-16:12 | 28.67 |
| August | 55688314.05 | 407.59 | 23-AUG-16:12 | 25.00 |
| September | 11375979.44 | 11146.68 | 27-SEP-07:01 | 0.60 |
| October | 0.633655E+09 | 11138.34 | 03-OCT-07:01 | 0.00 |
| November | 0.199605E+10 | 10807.31 | 01-NOV-06:01 | -10.9 |
| December | 0.286614E+10 | 10841.56 | 26-DEC-08:61 | -10.1 |
| Annual Sum or Average | 0.125888E+11 | |||
| Minimum of Months | 11375979.44 | 292.26 | -10.9 | |
| Maximum of Months | 0.300013E+10 | 11275.82 | 28.67 |
Report: ZoneHeatingSummaryMonthly
For: G NE APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.461411E+10 | 2938.68 | 29-JAN-00:10 | -25.0 |
| February | 0.402257E+10 | 2797.58 | 27-FEB-08:03 | -34.3 |
| March | 0.338514E+10 | 2477.77 | 02-MAR-07:55 | -26.7 |
| April | 0.140428E+10 | 1808.22 | 03-APR-07:02 | -20.1 |
| May | 53266913.44 | 624.47 | 29-MAY-07:01 | 8.40 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 16.35 |
| September | 0.110304E+09 | 560.56 | 30-SEP-05:00 | -4.4 |
| October | 0.152698E+10 | 1672.38 | 31-OCT-07:20 | -18.1 |
| November | 0.355770E+10 | 2302.36 | 29-NOV-08:10 | -29.0 |
| December | 0.451323E+10 | 2488.32 | 15-DEC-08:55 | -33.3 |
| Annual Sum or Average | 0.231876E+11 | |||
| Minimum of Months | 0.00 | 0.00 | -34.3 | |
| Maximum of Months | 0.461411E+10 | 2938.68 | 16.35 |
Report: ZoneHeatingSummaryMonthly
For: G N1 APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.277304E+10 | 1783.01 | 12-JAN-08:19 | -38.1 |
| February | 0.245152E+10 | 1820.53 | 27-FEB-08:19 | -34.2 |
| March | 0.211409E+10 | 1646.39 | 02-MAR-08:19 | -25.9 |
| April | 0.746784E+09 | 1178.55 | 03-APR-07:18 | -19.7 |
| May | 5510016.54 | 147.08 | 29-MAY-07:01 | 8.40 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 16.35 |
| September | 23350071.68 | 219.49 | 29-SEP-07:07 | -5.4 |
| October | 0.739928E+09 | 1021.34 | 31-OCT-07:20 | -18.1 |
| November | 0.209220E+10 | 1481.40 | 29-NOV-08:10 | -29.0 |
| December | 0.271959E+10 | 1599.85 | 15-DEC-08:30 | -33.6 |
| Annual Sum or Average | 0.136660E+11 | |||
| Minimum of Months | 0.00 | 0.00 | -38.1 | |
| Maximum of Months | 0.277304E+10 | 1820.53 | 16.35 |
Report: ZoneHeatingSummaryMonthly
For: G N2 APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.277216E+10 | 1782.86 | 12-JAN-08:19 | -38.1 |
| February | 0.244793E+10 | 1820.71 | 27-FEB-08:19 | -34.2 |
| March | 0.210341E+10 | 1644.95 | 02-MAR-08:19 | -25.9 |
| April | 0.747496E+09 | 1180.31 | 03-APR-07:18 | -19.7 |
| May | 4858389.35 | 141.33 | 29-MAY-07:01 | 8.40 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 16.35 |
| September | 22475438.50 | 217.02 | 29-SEP-07:07 | -5.4 |
| October | 0.735419E+09 | 1020.16 | 31-OCT-07:20 | -18.1 |
| November | 0.209211E+10 | 1481.48 | 29-NOV-08:10 | -29.0 |
| December | 0.271944E+10 | 1599.93 | 15-DEC-08:30 | -33.6 |
| Annual Sum or Average | 0.136453E+11 | |||
| Minimum of Months | 0.00 | 0.00 | -38.1 | |
| Maximum of Months | 0.277216E+10 | 1820.71 | 16.35 |
Report: ZoneHeatingSummaryMonthly
For: G S1 APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.252264E+10 | 1748.64 | 12-JAN-08:19 | -38.1 |
| February | 0.173419E+10 | 1623.87 | 24-FEB-08:23 | -25.6 |
| March | 0.102475E+10 | 1425.53 | 01-MAR-08:19 | -27.9 |
| April | 0.176443E+09 | 713.32 | 02-APR-07:02 | -15.9 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 6.70 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 16.35 |
| September | 1637501.88 | 93.05 | 28-SEP-07:14 | -2.6 |
| October | 0.365134E+09 | 801.71 | 31-OCT-07:20 | -18.1 |
| November | 0.168025E+10 | 1402.24 | 29-NOV-08:12 | -29.1 |
| December | 0.263120E+10 | 1608.39 | 15-DEC-08:30 | -33.6 |
| Annual Sum or Average | 0.101362E+11 | |||
| Minimum of Months | 0.00 | 0.00 | -38.1 | |
| Maximum of Months | 0.263120E+10 | 1748.64 | 16.35 |
Report: ZoneHeatingSummaryMonthly
For: G S2 APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.288396E+10 | 1883.65 | 12-JAN-08:19 | -38.1 |
| February | 0.203090E+10 | 1794.12 | 27-FEB-08:19 | -34.2 |
| March | 0.127407E+10 | 1563.54 | 01-MAR-08:19 | -27.9 |
| April | 0.257146E+09 | 883.66 | 03-APR-07:18 | -19.7 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 6.70 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 16.35 |
| September | 2952852.07 | 131.10 | 28-SEP-07:10 | -2.7 |
| October | 0.498500E+09 | 962.97 | 30-OCT-07:17 | -16.0 |
| November | 0.200813E+10 | 1537.89 | 29-NOV-08:20 | -29.1 |
| December | 0.297919E+10 | 1732.36 | 15-DEC-08:30 | -33.6 |
| Annual Sum or Average | 0.119349E+11 | |||
| Minimum of Months | 0.00 | 0.00 | -38.1 | |
| Maximum of Months | 0.297919E+10 | 1883.65 | 16.35 |
Report: ZoneHeatingSummaryMonthly
For: M SW APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.275313E+10 | 2640.04 | 29-JAN-00:10 | -25.0 |
| February | 0.158383E+10 | 2028.33 | 25-FEB-01:00 | -26.1 |
| March | 0.877673E+09 | 1478.74 | 02-MAR-05:00 | -26.7 |
| April | 0.149111E+09 | 860.11 | 02-APR-07:00 | -16.7 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 6.70 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 16.35 |
| September | 19528678.58 | 336.04 | 30-SEP-05:00 | -4.4 |
| October | 0.726280E+09 | 1259.61 | 27-OCT-04:00 | -17.8 |
| November | 0.203929E+10 | 1673.74 | 29-NOV-08:00 | -28.9 |
| December | 0.304692E+10 | 1871.62 | 15-DEC-02:00 | -31.1 |
| Annual Sum or Average | 0.111958E+11 | |||
| Minimum of Months | 0.00 | 0.00 | -31.1 | |
| Maximum of Months | 0.304692E+10 | 2640.04 | 16.35 |
Report: ZoneHeatingSummaryMonthly
For: M NW APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.301820E+10 | 2809.06 | 29-JAN-00:10 | -25.0 |
| February | 0.226793E+10 | 2199.54 | 25-FEB-01:00 | -26.1 |
| March | 0.171199E+10 | 1788.02 | 02-MAR-05:00 | -26.7 |
| April | 0.449275E+09 | 1152.43 | 04-APR-00:10 | -11.7 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 6.70 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 16.35 |
| September | 61214718.05 | 483.68 | 30-SEP-05:00 | -4.4 |
| October | 0.115328E+10 | 1473.70 | 27-OCT-04:00 | -17.8 |
| November | 0.246106E+10 | 1735.06 | 29-NOV-07:55 | -28.9 |
| December | 0.313476E+10 | 1981.80 | 15-DEC-12:00 | -33.3 |
| Annual Sum or Average | 0.142577E+11 | |||
| Minimum of Months | 0.00 | 0.00 | -33.3 | |
| Maximum of Months | 0.313476E+10 | 2809.06 | 16.35 |
Report: ZoneHeatingSummaryMonthly
For: M SE APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.272959E+10 | 2649.16 | 29-JAN-00:10 | -25.0 |
| February | 0.151217E+10 | 2009.03 | 24-FEB-05:00 | -25.6 |
| March | 0.760066E+09 | 1467.96 | 02-MAR-05:00 | -26.7 |
| April | 0.155022E+09 | 856.39 | 03-APR-03:00 | -21.1 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 6.70 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 16.35 |
| September | 15905341.80 | 320.90 | 28-SEP-05:00 | -2.2 |
| October | 0.670395E+09 | 1251.51 | 27-OCT-04:00 | -17.8 |
| November | 0.204024E+10 | 1677.86 | 29-NOV-08:00 | -28.9 |
| December | 0.304317E+10 | 1878.06 | 15-DEC-02:00 | -31.1 |
| Annual Sum or Average | 0.109266E+11 | |||
| Minimum of Months | 0.00 | 0.00 | -31.1 | |
| Maximum of Months | 0.304317E+10 | 2649.16 | 16.35 |
Report: ZoneHeatingSummaryMonthly
For: M NE APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.299428E+10 | 2818.46 | 29-JAN-00:10 | -25.0 |
| February | 0.217912E+10 | 2168.84 | 25-FEB-01:00 | -26.1 |
| March | 0.148985E+10 | 1780.49 | 02-MAR-05:00 | -26.7 |
| April | 0.456756E+09 | 1242.89 | 03-APR-03:00 | -21.1 |
| May | 4447.31 | 7.25 | 28-MAY-03:00 | 0.60 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 16.35 |
| September | 41826278.76 | 450.16 | 30-SEP-05:00 | -4.4 |
| October | 0.106038E+10 | 1467.57 | 27-OCT-04:00 | -17.8 |
| November | 0.246282E+10 | 1739.24 | 29-NOV-07:55 | -28.9 |
| December | 0.313099E+10 | 1972.04 | 15-DEC-12:00 | -33.3 |
| Annual Sum or Average | 0.138160E+11 | |||
| Minimum of Months | 0.00 | 0.00 | -33.3 | |
| Maximum of Months | 0.313099E+10 | 2818.46 | 16.35 |
Report: ZoneHeatingSummaryMonthly
For: M N1 APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.128083E+10 | 1519.43 | 29-JAN-00:10 | -25.0 |
| February | 0.898574E+09 | 1150.75 | 25-FEB-01:00 | -26.1 |
| March | 0.597636E+09 | 922.76 | 02-MAR-05:00 | -26.7 |
| April | 0.135158E+09 | 579.24 | 03-APR-03:00 | -21.1 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 6.70 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 16.35 |
| September | 1147824.07 | 85.97 | 30-SEP-05:00 | -4.4 |
| October | 0.316911E+09 | 705.14 | 27-OCT-04:00 | -17.8 |
| November | 0.968588E+09 | 845.77 | 29-NOV-08:00 | -28.9 |
| December | 0.135903E+10 | 1014.86 | 15-DEC-12:00 | -33.3 |
| Annual Sum or Average | 0.555787E+10 | |||
| Minimum of Months | 0.00 | 0.00 | -33.3 | |
| Maximum of Months | 0.135903E+10 | 1519.43 | 16.35 |
Report: ZoneHeatingSummaryMonthly
For: M N2 APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.127997E+10 | 1519.44 | 29-JAN-00:10 | -25.0 |
| February | 0.895195E+09 | 1149.24 | 25-FEB-01:00 | -26.1 |
| March | 0.588947E+09 | 921.73 | 02-MAR-05:00 | -26.7 |
| April | 0.135800E+09 | 584.09 | 03-APR-03:00 | -21.1 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 6.70 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 16.35 |
| September | 1039198.42 | 82.94 | 30-SEP-05:00 | -4.4 |
| October | 0.314441E+09 | 705.28 | 27-OCT-04:00 | -17.8 |
| November | 0.968586E+09 | 845.79 | 29-NOV-07:55 | -28.9 |
| December | 0.135889E+10 | 1014.60 | 15-DEC-12:00 | -33.3 |
| Annual Sum or Average | 0.554287E+10 | |||
| Minimum of Months | 0.00 | 0.00 | -33.3 | |
| Maximum of Months | 0.135889E+10 | 1519.44 | 16.35 |
Report: ZoneHeatingSummaryMonthly
For: M S1 APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.103895E+10 | 1351.45 | 29-JAN-00:10 | -25.0 |
| February | 0.418470E+09 | 991.02 | 24-FEB-05:00 | -25.6 |
| March | 0.154437E+09 | 637.68 | 01-MAR-04:00 | -27.8 |
| April | 11882359.68 | 227.36 | 02-APR-07:00 | -16.7 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 6.70 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 16.35 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 8.08 |
| October | 0.119978E+09 | 508.89 | 27-OCT-04:00 | -17.8 |
| November | 0.607522E+09 | 777.78 | 29-NOV-07:55 | -28.9 |
| December | 0.127316E+10 | 967.18 | 15-DEC-02:00 | -31.1 |
| Annual Sum or Average | 0.362440E+10 | |||
| Minimum of Months | 0.00 | 0.00 | -31.1 | |
| Maximum of Months | 0.127316E+10 | 1351.45 | 16.35 |
Report: ZoneHeatingSummaryMonthly
For: M S2 APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.103821E+10 | 1351.42 | 29-JAN-00:10 | -25.0 |
| February | 0.416764E+09 | 990.10 | 24-FEB-05:00 | -25.6 |
| March | 0.151860E+09 | 637.02 | 01-MAR-04:00 | -27.8 |
| April | 12084890.47 | 230.55 | 02-APR-07:00 | -16.7 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 6.70 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 16.35 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 8.08 |
| October | 0.119099E+09 | 508.27 | 27-OCT-04:00 | -17.8 |
| November | 0.607536E+09 | 777.77 | 29-NOV-07:55 | -28.9 |
| December | 0.127302E+10 | 967.07 | 15-DEC-02:00 | -31.1 |
| Annual Sum or Average | 0.361858E+10 | |||
| Minimum of Months | 0.00 | 0.00 | -31.1 | |
| Maximum of Months | 0.127302E+10 | 1351.42 | 16.35 |
Report: ZoneHeatingSummaryMonthly
For: T SW APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.566253E+10 | 4456.69 | 29-JAN-00:10 | -25.0 |
| February | 0.391843E+10 | 3655.54 | 25-FEB-01:00 | -26.1 |
| March | 0.285577E+10 | 3114.57 | 02-MAR-05:00 | -26.7 |
| April | 0.981254E+09 | 2279.15 | 03-APR-06:00 | -21.7 |
| May | 75464513.35 | 977.36 | 27-MAY-04:00 | 0.00 |
| June | 48348.55 | 449.81 | 25-JUN-06:01 | 10.50 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 |
| August | 27855511.85 | 800.23 | 30-AUG-05:00 | 0.00 |
| September | 0.352013E+09 | 1277.45 | 30-SEP-05:00 | -4.4 |
| October | 0.234577E+10 | 2645.62 | 27-OCT-04:00 | -17.8 |
| November | 0.473496E+10 | 3186.29 | 29-NOV-07:55 | -28.9 |
| December | 0.604763E+10 | 3468.25 | 15-DEC-10:00 | -33.3 |
| Annual Sum or Average | 0.270017E+11 | |||
| Minimum of Months | 0.00 | 0.00 | -33.3 | |
| Maximum of Months | 0.604763E+10 | 4456.69 | 14.88 |
Report: ZoneHeatingSummaryMonthly
For: T NW APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.595765E+10 | 4584.37 | 29-JAN-00:10 | -25.0 |
| February | 0.471271E+10 | 3772.11 | 25-FEB-01:00 | -26.1 |
| March | 0.392007E+10 | 3287.49 | 02-MAR-05:00 | -26.7 |
| April | 0.150173E+10 | 2541.39 | 03-APR-03:00 | -21.1 |
| May | 97472715.53 | 983.12 | 27-MAY-04:00 | 0.00 |
| June | 29583.58 | 404.66 | 25-JUN-06:01 | 10.50 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 |
| August | 48767117.76 | 859.07 | 30-AUG-05:00 | 0.00 |
| September | 0.570607E+09 | 1343.84 | 30-SEP-05:00 | -4.4 |
| October | 0.296032E+10 | 2781.84 | 27-OCT-04:00 | -17.8 |
| November | 0.519641E+10 | 3217.88 | 29-NOV-08:00 | -28.9 |
| December | 0.614341E+10 | 3622.75 | 15-DEC-12:00 | -33.3 |
| Annual Sum or Average | 0.311092E+11 | |||
| Minimum of Months | 0.00 | 0.00 | -33.3 | |
| Maximum of Months | 0.614341E+10 | 4584.37 | 14.88 |
Report: ZoneHeatingSummaryMonthly
For: T SE APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.563691E+10 | 4474.87 | 29-JAN-00:10 | -25.0 |
| February | 0.383218E+10 | 3638.87 | 24-FEB-05:00 | -25.6 |
| March | 0.266183E+10 | 3115.43 | 02-MAR-05:00 | -26.7 |
| April | 0.963681E+09 | 2343.41 | 03-APR-06:00 | -21.7 |
| May | 65474828.87 | 940.40 | 27-MAY-04:00 | 0.00 |
| June | 21111.03 | 315.54 | 25-JUN-06:01 | 10.50 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 |
| August | 19688532.09 | 785.00 | 30-AUG-05:00 | 0.00 |
| September | 0.313912E+09 | 1264.23 | 30-SEP-05:00 | -4.4 |
| October | 0.225080E+10 | 2645.78 | 27-OCT-04:00 | -17.8 |
| November | 0.473911E+10 | 3192.24 | 29-NOV-07:55 | -28.9 |
| December | 0.604373E+10 | 3477.32 | 15-DEC-10:00 | -33.3 |
| Annual Sum or Average | 0.265273E+11 | |||
| Minimum of Months | 0.00 | 0.00 | -33.3 | |
| Maximum of Months | 0.604373E+10 | 4474.87 | 14.88 |
Report: ZoneHeatingSummaryMonthly
For: T NE APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.593168E+10 | 4602.44 | 29-JAN-00:10 | -25.0 |
| February | 0.461662E+10 | 3750.62 | 25-FEB-01:00 | -26.1 |
| March | 0.365614E+10 | 3290.11 | 02-MAR-05:00 | -26.7 |
| April | 0.148102E+10 | 2639.90 | 03-APR-03:00 | -21.1 |
| May | 87653451.98 | 1008.78 | 28-MAY-03:00 | 0.60 |
| June | 16964.28 | 271.11 | 25-JUN-06:01 | 10.50 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 |
| August | 33333851.80 | 855.77 | 31-AUG-04:00 | -0.6 |
| September | 0.501170E+09 | 1333.25 | 30-SEP-05:00 | -4.4 |
| October | 0.282857E+10 | 2779.49 | 27-OCT-04:00 | -17.8 |
| November | 0.520061E+10 | 3224.83 | 29-NOV-08:00 | -28.9 |
| December | 0.613950E+10 | 3609.27 | 15-DEC-12:00 | -33.3 |
| Annual Sum or Average | 0.304763E+11 | |||
| Minimum of Months | 0.00 | 0.00 | -33.3 | |
| Maximum of Months | 0.613950E+10 | 4602.44 | 14.88 |
Report: ZoneHeatingSummaryMonthly
For: T N1 APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.382697E+10 | 2925.56 | 29-JAN-00:10 | -25.0 |
| February | 0.300239E+10 | 2430.89 | 25-FEB-01:00 | -26.1 |
| March | 0.240066E+10 | 2170.02 | 02-MAR-05:00 | -26.7 |
| April | 0.841321E+09 | 1684.90 | 03-APR-03:00 | -21.1 |
| May | 26478275.95 | 500.47 | 28-MAY-03:00 | 0.60 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 |
| August | 16304770.89 | 436.39 | 31-AUG-04:00 | -0.6 |
| September | 0.209034E+09 | 775.80 | 30-SEP-05:00 | -4.4 |
| October | 0.167212E+10 | 1791.09 | 27-OCT-04:00 | -17.8 |
| November | 0.337513E+10 | 2120.50 | 29-NOV-07:55 | -28.9 |
| December | 0.398005E+10 | 2427.46 | 15-DEC-12:00 | -33.3 |
| Annual Sum or Average | 0.193504E+11 | |||
| Minimum of Months | 0.00 | 0.00 | -33.3 | |
| Maximum of Months | 0.398005E+10 | 2925.56 | 14.88 |
Report: ZoneHeatingSummaryMonthly
For: T N2 APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.382598E+10 | 2926.00 | 29-JAN-00:10 | -25.0 |
| February | 0.299854E+10 | 2429.90 | 25-FEB-01:00 | -26.1 |
| March | 0.238891E+10 | 2169.77 | 02-MAR-05:00 | -26.7 |
| April | 0.843510E+09 | 1691.06 | 03-APR-03:00 | -21.1 |
| May | 25900640.02 | 505.70 | 28-MAY-03:00 | 0.60 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 |
| August | 15682233.64 | 437.05 | 31-AUG-04:00 | -0.6 |
| September | 0.206743E+09 | 773.81 | 30-SEP-05:00 | -4.4 |
| October | 0.166638E+10 | 1792.14 | 27-OCT-04:00 | -17.8 |
| November | 0.337526E+10 | 2120.96 | 29-NOV-08:00 | -28.9 |
| December | 0.397990E+10 | 2427.41 | 15-DEC-12:00 | -33.3 |
| Annual Sum or Average | 0.193268E+11 | |||
| Minimum of Months | 0.00 | 0.00 | -33.3 | |
| Maximum of Months | 0.397990E+10 | 2926.00 | 14.88 |
Report: ZoneHeatingSummaryMonthly
For: T S1 APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.353274E+10 | 2791.75 | 29-JAN-00:10 | -25.0 |
| February | 0.225471E+10 | 2352.30 | 24-FEB-05:00 | -25.6 |
| March | 0.149473E+10 | 1983.68 | 02-MAR-05:00 | -26.7 |
| April | 0.430741E+09 | 1390.14 | 03-APR-06:00 | -21.7 |
| May | 20497355.37 | 441.94 | 27-MAY-04:00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 |
| August | 3382380.40 | 273.88 | 30-AUG-05:00 | 0.00 |
| September | 0.107154E+09 | 699.69 | 30-SEP-05:00 | -4.4 |
| October | 0.116771E+10 | 1646.86 | 27-OCT-04:00 | -17.8 |
| November | 0.291772E+10 | 2088.28 | 29-NOV-08:00 | -28.9 |
| December | 0.388421E+10 | 2335.55 | 15-DEC-10:00 | -33.3 |
| Annual Sum or Average | 0.158136E+11 | |||
| Minimum of Months | 0.00 | 0.00 | -33.3 | |
| Maximum of Months | 0.388421E+10 | 2791.75 | 14.88 |
Report: ZoneHeatingSummaryMonthly
For: T S2 APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.353172E+10 | 2792.19 | 29-JAN-00:10 | -25.0 |
| February | 0.225145E+10 | 2351.88 | 24-FEB-05:00 | -25.6 |
| March | 0.148757E+10 | 1983.17 | 02-MAR-05:00 | -26.7 |
| April | 0.432605E+09 | 1394.57 | 03-APR-06:00 | -21.7 |
| May | 20357043.97 | 439.13 | 27-MAY-04:00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 |
| August | 3201613.47 | 270.94 | 30-AUG-05:00 | 0.00 |
| September | 0.106368E+09 | 697.76 | 30-SEP-05:00 | -4.4 |
| October | 0.116405E+10 | 1646.63 | 27-OCT-04:00 | -17.8 |
| November | 0.291789E+10 | 2088.05 | 29-NOV-07:55 | -28.9 |
| December | 0.388407E+10 | 2336.13 | 15-DEC-10:00 | -33.3 |
| Annual Sum or Average | 0.157993E+11 | |||
| Minimum of Months | 0.00 | 0.00 | -33.3 | |
| Maximum of Months | 0.388407E+10 | 2792.19 | 14.88 |
Report: ZoneHeatingSummaryMonthly
For: T CORRIDOR
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | -14.9 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | -20.2 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | -28.9 |
| April | 0.00 | 0.00 | 01-APR-00:10 | -11.7 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 6.70 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 16.35 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 8.08 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 1.42 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | -10.0 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | -25.8 |
| Annual Sum or Average | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | -28.9 | |
| Maximum of Months | 0.00 | 0.00 | 16.35 |
Report: ZoneHeatingSummaryMonthly
For: G CORRIDOR
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | -14.9 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | -20.2 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | -28.9 |
| April | 0.00 | 0.00 | 01-APR-00:10 | -11.7 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 6.70 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 16.35 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 8.08 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 1.42 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | -10.0 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | -25.8 |
| Annual Sum or Average | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | -28.9 | |
| Maximum of Months | 0.00 | 0.00 | 16.35 |
Report: ZoneHeatingSummaryMonthly
For: M CORRIDOR
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | -14.9 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | -20.2 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | -28.9 |
| April | 0.00 | 0.00 | 01-APR-00:10 | -11.7 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 6.70 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 16.35 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 8.08 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 1.42 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | -10.0 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | -25.8 |
| Annual Sum or Average | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | -28.9 | |
| Maximum of Months | 0.00 | 0.00 | 16.35 |
Report: ZoneElectricSummaryMonthly
For: G SW APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: G NW APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: OFFICE
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.609777E+09 | 582.92 | 03-JAN-08:09 | 0.787690E+09 | 588.62 | 03-JAN-08:09 |
| February | 0.564682E+09 | 582.92 | 01-FEB-08:09 | 0.723971E+09 | 588.62 | 01-FEB-08:09 |
| March | 0.654405E+09 | 582.92 | 01-MAR-08:09 | 0.827804E+09 | 588.62 | 01-MAR-08:09 |
| April | 0.599704E+09 | 582.92 | 03-APR-07:10 | 0.770907E+09 | 588.62 | 03-APR-07:10 |
| May | 0.639529E+09 | 582.92 | 01-MAY-07:10 | 0.814432E+09 | 588.62 | 01-MAY-07:10 |
| June | 0.629456E+09 | 582.92 | 01-JUN-07:10 | 0.797650E+09 | 588.62 | 01-JUN-07:10 |
| July | 0.609777E+09 | 582.92 | 03-JUL-07:10 | 0.787690E+09 | 588.62 | 03-JUL-07:10 |
| August | 0.654405E+09 | 582.92 | 01-AUG-07:10 | 0.827804E+09 | 588.62 | 01-AUG-07:10 |
| September | 0.599704E+09 | 582.92 | 01-SEP-07:10 | 0.770907E+09 | 588.62 | 01-SEP-07:10 |
| October | 0.624653E+09 | 582.92 | 02-OCT-07:10 | 0.801061E+09 | 588.62 | 02-OCT-07:10 |
| November | 0.599704E+09 | 582.92 | 01-NOV-07:10 | 0.770907E+09 | 588.62 | 01-NOV-07:10 |
| December | 0.609777E+09 | 582.92 | 01-DEC-08:09 | 0.787690E+09 | 588.62 | 01-DEC-08:09 |
| Annual Sum or Average | 0.739557E+10 | 0.946851E+10 | ||||
| Minimum of Months | 0.564682E+09 | 582.92 | 0.723971E+09 | 588.62 | ||
| Maximum of Months | 0.654405E+09 | 582.92 | 0.827804E+09 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: G NE APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: G N1 APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: G N2 APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: G S1 APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: G S2 APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: M SW APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: M NW APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: M SE APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: M NE APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: M N1 APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: M N2 APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: M S1 APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: M S2 APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: T SW APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: T NW APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: T SE APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: T NE APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: T N1 APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: T N2 APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: T S1 APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: T S2 APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: T CORRIDOR
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
| January | 0.992689E+09 | 370.63 | 01-JAN-00:10 | 0.00 | 0.00 |
| February | 0.896622E+09 | 370.63 | 01-FEB-00:10 | 0.00 | 0.00 |
| March | 0.992689E+09 | 370.63 | 01-MAR-00:10 | 0.00 | 0.00 |
| April | 0.960667E+09 | 370.63 | 01-APR-00:10 | 0.00 | 0.00 |
| May | 0.992689E+09 | 370.63 | 01-MAY-00:10 | 0.00 | 0.00 |
| June | 0.960667E+09 | 370.63 | 01-JUN-00:10 | 0.00 | 0.00 |
| July | 0.992689E+09 | 370.63 | 01-JUL-00:10 | 0.00 | 0.00 |
| August | 0.992689E+09 | 370.63 | 01-AUG-00:10 | 0.00 | 0.00 |
| September | 0.960667E+09 | 370.63 | 01-SEP-00:10 | 0.00 | 0.00 |
| October | 0.992689E+09 | 370.63 | 01-OCT-00:10 | 0.00 | 0.00 |
| November | 0.960667E+09 | 370.63 | 01-NOV-00:10 | 0.00 | 0.00 |
| December | 0.992689E+09 | 370.63 | 01-DEC-00:10 | 0.00 | 0.00 |
| Annual Sum or Average | 0.116881E+11 | 0.00 | 0.00 | ||
| Minimum of Months | 0.896622E+09 | 370.63 | 0.00 | 0.00 | |
| Maximum of Months | 0.992689E+09 | 370.63 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: G CORRIDOR
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.992689E+09 | 370.63 | 01-JAN-00:10 | 0.599555E+10 | 4168.07 | 01-JAN-07:10 |
| February | 0.896622E+09 | 370.63 | 01-FEB-00:10 | 0.541534E+10 | 4168.07 | 01-FEB-07:10 |
| March | 0.992689E+09 | 370.63 | 01-MAR-00:10 | 0.599555E+10 | 4168.07 | 01-MAR-07:10 |
| April | 0.960667E+09 | 370.63 | 01-APR-00:10 | 0.580215E+10 | 4168.07 | 01-APR-06:10 |
| May | 0.992689E+09 | 370.63 | 01-MAY-00:10 | 0.599555E+10 | 4168.07 | 01-MAY-06:10 |
| June | 0.960667E+09 | 370.63 | 01-JUN-00:10 | 0.580215E+10 | 4168.07 | 01-JUN-06:10 |
| July | 0.992689E+09 | 370.63 | 01-JUL-00:10 | 0.599555E+10 | 4168.07 | 01-JUL-06:10 |
| August | 0.992689E+09 | 370.63 | 01-AUG-00:10 | 0.599555E+10 | 4168.07 | 01-AUG-06:10 |
| September | 0.960667E+09 | 370.63 | 01-SEP-00:10 | 0.580215E+10 | 4168.07 | 01-SEP-06:10 |
| October | 0.992689E+09 | 370.63 | 01-OCT-00:10 | 0.599555E+10 | 4168.07 | 01-OCT-06:10 |
| November | 0.960667E+09 | 370.63 | 01-NOV-00:10 | 0.580215E+10 | 4168.07 | 01-NOV-06:10 |
| December | 0.992689E+09 | 370.63 | 01-DEC-00:10 | 0.599555E+10 | 4168.07 | 01-DEC-07:10 |
| Annual Sum or Average | 0.116881E+11 | 0.705928E+11 | ||||
| Minimum of Months | 0.896622E+09 | 370.63 | 0.541534E+10 | 4168.07 | ||
| Maximum of Months | 0.992689E+09 | 370.63 | 0.599555E+10 | 4168.07 |
Report: ZoneElectricSummaryMonthly
For: M CORRIDOR
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
| January | 0.992689E+09 | 370.63 | 01-JAN-00:10 | 0.00 | 0.00 |
| February | 0.896622E+09 | 370.63 | 01-FEB-00:10 | 0.00 | 0.00 |
| March | 0.992689E+09 | 370.63 | 01-MAR-00:10 | 0.00 | 0.00 |
| April | 0.960667E+09 | 370.63 | 01-APR-00:10 | 0.00 | 0.00 |
| May | 0.992689E+09 | 370.63 | 01-MAY-00:10 | 0.00 | 0.00 |
| June | 0.960667E+09 | 370.63 | 01-JUN-00:10 | 0.00 | 0.00 |
| July | 0.992689E+09 | 370.63 | 01-JUL-00:10 | 0.00 | 0.00 |
| August | 0.992689E+09 | 370.63 | 01-AUG-00:10 | 0.00 | 0.00 |
| September | 0.960667E+09 | 370.63 | 01-SEP-00:10 | 0.00 | 0.00 |
| October | 0.992689E+09 | 370.63 | 01-OCT-00:10 | 0.00 | 0.00 |
| November | 0.960667E+09 | 370.63 | 01-NOV-00:10 | 0.00 | 0.00 |
| December | 0.992689E+09 | 370.63 | 01-DEC-00:10 | 0.00 | 0.00 |
| Annual Sum or Average | 0.116881E+11 | 0.00 | 0.00 | ||
| Minimum of Months | 0.896622E+09 | 370.63 | 0.00 | 0.00 | |
| Maximum of Months | 0.992689E+09 | 370.63 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: G SW APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.400025E+09 |
| February | 0.389025E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.332511E+09 |
| March | 0.418950E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.488563E+09 |
| April | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.471561E+09 |
| May | 0.424935E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.275765E+09 |
| June | 0.406980E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 982073.74 | 0.148836E+09 |
| July | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2901156.98 | 0.103436E+09 |
| August | 0.418950E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 459293.09 | 0.159522E+09 |
| September | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.185945E+09 |
| October | 0.430920E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.411014E+09 |
| November | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.151847E+09 |
| December | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.313236E+09 |
| Annual Sum or Average | 0.505732E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 4342523.81 | 0.344226E+10 |
| Minimum of Months | 0.389025E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103436E+09 |
| Maximum of Months | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2901156.98 | 0.488563E+09 |
Report: SpaceGainsMonthly
For: G NW APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.400025E+09 |
| February | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.332511E+09 |
| March | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.488563E+09 |
| April | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.465604E+09 |
| May | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.255328E+09 |
| June | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 982078.21 | 0.144753E+09 |
| July | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2901168.57 | 0.102641E+09 |
| August | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 459299.02 | 0.154856E+09 |
| September | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.174656E+09 |
| October | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.410504E+09 |
| November | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.151847E+09 |
| December | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.313236E+09 |
| Annual Sum or Average | 0.512427E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 4342545.80 | 0.339452E+10 |
| Minimum of Months | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102641E+09 |
| Maximum of Months | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2901168.57 | 0.488563E+09 |
Report: SpaceGainsMonthly
For: OFFICE
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.227408E+09 | 0.609777E+09 | 0.787690E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.353984E+09 |
| February | 0.216037E+09 | 0.564682E+09 | 0.723971E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.295044E+09 |
| March | 0.261519E+09 | 0.654405E+09 | 0.827804E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.429937E+09 |
| April | 0.227408E+09 | 0.599704E+09 | 0.770907E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.422050E+09 |
| May | 0.250148E+09 | 0.639529E+09 | 0.814432E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.295093E+09 |
| June | 0.250148E+09 | 0.629456E+09 | 0.797650E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 583115.13 | 0.176872E+09 |
| July | 0.227408E+09 | 0.609777E+09 | 0.787690E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 880261.07 | 0.135427E+09 |
| August | 0.261519E+09 | 0.654405E+09 | 0.827804E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 123369.47 | 0.186433E+09 |
| September | 0.227408E+09 | 0.599704E+09 | 0.770907E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.191008E+09 |
| October | 0.238778E+09 | 0.624653E+09 | 0.801061E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.369941E+09 |
| November | 0.227408E+09 | 0.599704E+09 | 0.770907E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.134100E+09 |
| December | 0.227408E+09 | 0.609777E+09 | 0.787690E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.281162E+09 |
| Annual Sum or Average | 0.284259E+10 | 0.739557E+10 | 0.946851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1586745.67 | 0.327105E+10 |
| Minimum of Months | 0.216037E+09 | 0.564682E+09 | 0.723971E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.134100E+09 |
| Maximum of Months | 0.261519E+09 | 0.654405E+09 | 0.827804E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 880261.07 | 0.429937E+09 |
Report: SpaceGainsMonthly
For: G NE APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.400025E+09 |
| February | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.332511E+09 |
| March | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.488563E+09 |
| April | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.465336E+09 |
| May | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.262131E+09 |
| June | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 982079.98 | 0.147179E+09 |
| July | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2901172.98 | 0.102990E+09 |
| August | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 459302.54 | 0.156550E+09 |
| September | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.175784E+09 |
| October | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.410506E+09 |
| November | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.151847E+09 |
| December | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.313236E+09 |
| Annual Sum or Average | 0.512427E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 4342555.49 | 0.340666E+10 |
| Minimum of Months | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102990E+09 |
| Maximum of Months | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2901172.98 | 0.488563E+09 |
Report: SpaceGainsMonthly
For: G N1 APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.241285E+09 |
| February | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.200562E+09 |
| March | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.294689E+09 |
| April | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.280678E+09 |
| May | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.155735E+09 |
| June | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 592366.83 | 89099988.03 |
| July | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1749916.34 | 62533814.81 |
| August | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 277040.71 | 95346478.66 |
| September | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106279E+09 |
| October | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.247613E+09 |
| November | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91589995.57 |
| December | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.188936E+09 |
| Annual Sum or Average | 0.512427E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 2619323.87 | 0.205435E+10 |
| Minimum of Months | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62533814.81 |
| Maximum of Months | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1749916.34 | 0.294689E+09 |
Report: SpaceGainsMonthly
For: G N2 APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.241285E+09 |
| February | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.200562E+09 |
| March | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.294689E+09 |
| April | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.280676E+09 |
| May | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.156390E+09 |
| June | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 592366.83 | 89287769.36 |
| July | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1749916.34 | 62548933.26 |
| August | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 277040.70 | 95455747.15 |
| September | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106411E+09 |
| October | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.247613E+09 |
| November | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91589995.57 |
| December | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.188936E+09 |
| Annual Sum or Average | 0.512427E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 2619323.87 | 0.205544E+10 |
| Minimum of Months | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62548933.26 |
| Maximum of Months | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1749916.34 | 0.294689E+09 |
Report: SpaceGainsMonthly
For: G S1 APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.241285E+09 |
| February | 0.389025E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.200562E+09 |
| March | 0.418950E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.294689E+09 |
| April | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.285382E+09 |
| May | 0.424935E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.171522E+09 |
| June | 0.406980E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 592364.01 | 91229665.99 |
| July | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1749909.36 | 62805917.03 |
| August | 0.418950E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 277036.30 | 97577185.67 |
| September | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114920E+09 |
| October | 0.430920E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.248402E+09 |
| November | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91589995.60 |
| December | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.188936E+09 |
| Annual Sum or Average | 0.505732E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 2619309.66 | 0.208890E+10 |
| Minimum of Months | 0.389025E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62805917.03 |
| Maximum of Months | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1749909.36 | 0.294689E+09 |
Report: SpaceGainsMonthly
For: G S2 APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.241285E+09 |
| February | 0.389025E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.200562E+09 |
| March | 0.418950E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.294689E+09 |
| April | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.285124E+09 |
| May | 0.424935E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.172651E+09 |
| June | 0.406980E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 592363.92 | 91465062.74 |
| July | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1749908.21 | 62863475.60 |
| August | 0.418950E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 277036.28 | 97741882.21 |
| September | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115367E+09 |
| October | 0.430920E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.248359E+09 |
| November | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91589995.61 |
| December | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.188936E+09 |
| Annual Sum or Average | 0.505732E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 2619308.41 | 0.209063E+10 |
| Minimum of Months | 0.389025E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62863475.60 |
| Maximum of Months | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1749908.21 | 0.294689E+09 |
Report: SpaceGainsMonthly
For: M SW APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.575169E+09 |
| February | 0.389025E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.478111E+09 |
| March | 0.418950E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.703462E+09 |
| April | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.702977E+09 |
| May | 0.424935E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.436104E+09 |
| June | 0.406980E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1392285.53 | 0.219378E+09 |
| July | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4125046.43 | 0.150330E+09 |
| August | 0.418950E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 644467.18 | 0.232112E+09 |
| September | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.275303E+09 |
| October | 0.430920E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.593463E+09 |
| November | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.218341E+09 |
| December | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.450381E+09 |
| Annual Sum or Average | 0.505732E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 6161799.15 | 0.503513E+10 |
| Minimum of Months | 0.389025E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.150330E+09 |
| Maximum of Months | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4125046.43 | 0.703462E+09 |
Report: SpaceGainsMonthly
For: M NW APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.575169E+09 |
| February | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.478111E+09 |
| March | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.702554E+09 |
| April | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.680568E+09 |
| May | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.426362E+09 |
| June | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1392288.08 | 0.219237E+09 |
| July | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4125059.24 | 0.150318E+09 |
| August | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 644478.94 | 0.228839E+09 |
| September | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.260302E+09 |
| October | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.590549E+09 |
| November | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.218341E+09 |
| December | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.450381E+09 |
| Annual Sum or Average | 0.512427E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 6161826.25 | 0.498073E+10 |
| Minimum of Months | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.150318E+09 |
| Maximum of Months | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4125059.24 | 0.702554E+09 |
Report: SpaceGainsMonthly
For: M SE APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.575169E+09 |
| February | 0.389025E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.478111E+09 |
| March | 0.418950E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.703736E+09 |
| April | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.702564E+09 |
| May | 0.424935E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.438394E+09 |
| June | 0.406980E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1392291.46 | 0.219496E+09 |
| July | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4125055.12 | 0.150375E+09 |
| August | 0.418950E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 644472.80 | 0.232939E+09 |
| September | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.276591E+09 |
| October | 0.430920E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.594598E+09 |
| November | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.218341E+09 |
| December | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.450381E+09 |
| Annual Sum or Average | 0.505732E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 6161819.38 | 0.504069E+10 |
| Minimum of Months | 0.389025E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.150375E+09 |
| Maximum of Months | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4125055.12 | 0.703736E+09 |
Report: SpaceGainsMonthly
For: M NE APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.575169E+09 |
| February | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.478111E+09 |
| March | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.702554E+09 |
| April | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.679238E+09 |
| May | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.431228E+09 |
| June | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1392295.44 | 0.219320E+09 |
| July | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4125070.15 | 0.150320E+09 |
| August | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 644482.57 | 0.230451E+09 |
| September | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.263602E+09 |
| October | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.590595E+09 |
| November | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.218341E+09 |
| December | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.450381E+09 |
| Annual Sum or Average | 0.512427E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 6161848.16 | 0.498931E+10 |
| Minimum of Months | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.150320E+09 |
| Maximum of Months | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4125070.15 | 0.702554E+09 |
Report: SpaceGainsMonthly
For: M N1 APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.346927E+09 |
| February | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.288384E+09 |
| March | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.423763E+09 |
| April | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.409054E+09 |
| May | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.260833E+09 |
| June | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 839798.72 | 0.132823E+09 |
| July | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2488141.07 | 90764804.21 |
| August | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 388737.28 | 0.139594E+09 |
| September | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160545E+09 |
| October | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.356461E+09 |
| November | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131698E+09 |
| December | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.271658E+09 |
| Annual Sum or Average | 0.512427E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 3716677.08 | 0.301251E+10 |
| Minimum of Months | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90764804.21 |
| Maximum of Months | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2488141.07 | 0.423763E+09 |
Report: SpaceGainsMonthly
For: M N2 APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.346927E+09 |
| February | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.288384E+09 |
| March | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.423763E+09 |
| April | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.409052E+09 |
| May | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.261296E+09 |
| June | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 839798.76 | 0.132825E+09 |
| July | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2488141.13 | 90764540.95 |
| August | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 388737.29 | 0.139672E+09 |
| September | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160940E+09 |
| October | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.356476E+09 |
| November | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131698E+09 |
| December | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.271658E+09 |
| Annual Sum or Average | 0.512427E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 3716677.17 | 0.301346E+10 |
| Minimum of Months | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90764540.95 |
| Maximum of Months | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2488141.13 | 0.423763E+09 |
Report: SpaceGainsMonthly
For: M S1 APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.346927E+09 |
| February | 0.389025E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.288403E+09 |
| March | 0.418950E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.425124E+09 |
| April | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.427440E+09 |
| May | 0.424935E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.266699E+09 |
| June | 0.406980E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 839795.43 | 0.132890E+09 |
| July | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2488132.91 | 90766823.71 |
| August | 0.418950E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 388731.22 | 0.141102E+09 |
| September | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.169520E+09 |
| October | 0.430920E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.360613E+09 |
| November | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131698E+09 |
| December | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.271658E+09 |
| Annual Sum or Average | 0.505732E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 3716659.56 | 0.305284E+10 |
| Minimum of Months | 0.389025E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90766823.71 |
| Maximum of Months | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2488132.91 | 0.427440E+09 |
Report: SpaceGainsMonthly
For: M S2 APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.346927E+09 |
| February | 0.389025E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.288403E+09 |
| March | 0.418950E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.425167E+09 |
| April | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.427459E+09 |
| May | 0.424935E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.266822E+09 |
| June | 0.406980E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 839795.49 | 0.132891E+09 |
| July | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2488133.09 | 90767371.64 |
| August | 0.418950E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 388731.28 | 0.141120E+09 |
| September | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.169592E+09 |
| October | 0.430920E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.360742E+09 |
| November | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131698E+09 |
| December | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.271658E+09 |
| Annual Sum or Average | 0.505732E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 3716659.86 | 0.305325E+10 |
| Minimum of Months | 0.389025E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90767371.64 |
| Maximum of Months | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2488133.09 | 0.427459E+09 |
Report: SpaceGainsMonthly
For: T SW APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.761631E+09 |
| February | 0.389025E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.633150E+09 |
| March | 0.418950E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.931893E+09 |
| April | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.920514E+09 |
| May | 0.424935E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.545983E+09 |
| June | 0.406980E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1791507.15 | 0.280221E+09 |
| July | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5340811.90 | 0.194692E+09 |
| August | 0.418950E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 811783.73 | 0.289206E+09 |
| September | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.345712E+09 |
| October | 0.430920E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.784873E+09 |
| November | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.289153E+09 |
| December | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.596387E+09 |
| Annual Sum or Average | 0.505732E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 7944102.78 | 0.657341E+10 |
| Minimum of Months | 0.389025E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.194692E+09 |
| Maximum of Months | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5340811.90 | 0.931893E+09 |
Report: SpaceGainsMonthly
For: T NW APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.761631E+09 |
| February | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.633150E+09 |
| March | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.930530E+09 |
| April | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.899617E+09 |
| May | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.531941E+09 |
| June | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1791512.07 | 0.281139E+09 |
| July | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5340822.82 | 0.194704E+09 |
| August | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 811800.67 | 0.281611E+09 |
| September | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.334103E+09 |
| October | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.782335E+09 |
| November | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.289153E+09 |
| December | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.596387E+09 |
| Annual Sum or Average | 0.512427E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 7944135.56 | 0.651630E+10 |
| Minimum of Months | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.194704E+09 |
| Maximum of Months | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5340822.82 | 0.930530E+09 |
Report: SpaceGainsMonthly
For: T SE APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.761631E+09 |
| February | 0.389025E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.633150E+09 |
| March | 0.418950E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.932119E+09 |
| April | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.919435E+09 |
| May | 0.424935E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.551420E+09 |
| June | 0.406980E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1791520.23 | 0.281846E+09 |
| July | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5340844.99 | 0.195520E+09 |
| August | 0.418950E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 811796.04 | 0.292272E+09 |
| September | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.347113E+09 |
| October | 0.430920E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.785459E+09 |
| November | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.289153E+09 |
| December | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.596387E+09 |
| Annual Sum or Average | 0.505732E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 7944161.25 | 0.658551E+10 |
| Minimum of Months | 0.389025E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.195520E+09 |
| Maximum of Months | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5340844.99 | 0.932119E+09 |
Report: SpaceGainsMonthly
For: T NE APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.761631E+09 |
| February | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.633150E+09 |
| March | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.930530E+09 |
| April | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.897092E+09 |
| May | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.544141E+09 |
| June | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1791522.81 | 0.282038E+09 |
| July | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5340847.05 | 0.195143E+09 |
| August | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 811807.83 | 0.284918E+09 |
| September | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.334834E+09 |
| October | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.782316E+09 |
| November | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.289153E+09 |
| December | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.596387E+09 |
| Annual Sum or Average | 0.512427E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 7944177.68 | 0.653133E+10 |
| Minimum of Months | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.195143E+09 |
| Maximum of Months | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5340847.05 | 0.930530E+09 |
Report: SpaceGainsMonthly
For: T N1 APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.459397E+09 |
| February | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.381900E+09 |
| March | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.561272E+09 |
| April | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.540096E+09 |
| May | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.324521E+09 |
| June | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1080601.61 | 0.172407E+09 |
| July | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3221464.62 | 0.118876E+09 |
| August | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 489663.97 | 0.173888E+09 |
| September | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.201583E+09 |
| October | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.471907E+09 |
| November | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.174410E+09 |
| December | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.359726E+09 |
| Annual Sum or Average | 0.512427E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 4791730.20 | 0.393998E+10 |
| Minimum of Months | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118876E+09 |
| Maximum of Months | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3221464.62 | 0.561272E+09 |
Report: SpaceGainsMonthly
For: T N2 APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.459397E+09 |
| February | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.381900E+09 |
| March | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.561272E+09 |
| April | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.540101E+09 |
| May | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.325650E+09 |
| June | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1080601.78 | 0.172449E+09 |
| July | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3221464.99 | 0.118891E+09 |
| August | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 489664.04 | 0.174147E+09 |
| September | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.201691E+09 |
| October | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.471907E+09 |
| November | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.174410E+09 |
| December | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.359726E+09 |
| Annual Sum or Average | 0.512427E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 4791730.81 | 0.394154E+10 |
| Minimum of Months | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118891E+09 |
| Maximum of Months | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3221464.99 | 0.561272E+09 |
Report: SpaceGainsMonthly
For: T S1 APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.459397E+09 |
| February | 0.389025E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.381908E+09 |
| March | 0.418950E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.562918E+09 |
| April | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.556954E+09 |
| May | 0.424935E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.333926E+09 |
| June | 0.406980E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1080599.05 | 0.171981E+09 |
| July | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3221458.87 | 0.118867E+09 |
| August | 0.418950E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 489656.28 | 0.178890E+09 |
| September | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.211056E+09 |
| October | 0.430920E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.474572E+09 |
| November | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.174410E+09 |
| December | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.359726E+09 |
| Annual Sum or Average | 0.505732E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 4791714.20 | 0.398460E+10 |
| Minimum of Months | 0.389025E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118867E+09 |
| Maximum of Months | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3221458.87 | 0.562918E+09 |
Report: SpaceGainsMonthly
For: T S2 APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.459397E+09 |
| February | 0.389025E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.381909E+09 |
| March | 0.418950E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.562984E+09 |
| April | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.556928E+09 |
| May | 0.424935E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.334190E+09 |
| June | 0.406980E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1080599.30 | 0.172034E+09 |
| July | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3221459.52 | 0.118890E+09 |
| August | 0.418950E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 489656.52 | 0.179066E+09 |
| September | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.211162E+09 |
| October | 0.430920E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.474633E+09 |
| November | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.174410E+09 |
| December | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.359726E+09 |
| Annual Sum or Average | 0.505732E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 4791715.33 | 0.398533E+10 |
| Minimum of Months | 0.389025E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118890E+09 |
| Maximum of Months | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3221459.52 | 0.562984E+09 |
Report: SpaceGainsMonthly
For: T CORRIDOR
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.727675E+09 | 0.992689E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124044E+09 |
| February | 0.657255E+09 | 0.896622E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103966E+09 |
| March | 0.727675E+09 | 0.992689E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.156387E+09 |
| April | 0.704201E+09 | 0.960667E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.159537E+09 |
| May | 0.727675E+09 | 0.992689E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104760E+09 |
| June | 0.704201E+09 | 0.960667E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14721.70 | 61127526.55 |
| July | 0.727675E+09 | 0.992689E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 147369.42 | 44131851.29 |
| August | 0.727675E+09 | 0.992689E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58770677.01 |
| September | 0.704201E+09 | 0.960667E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61554271.37 |
| October | 0.727675E+09 | 0.992689E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131863E+09 |
| November | 0.704201E+09 | 0.960667E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47293200.45 |
| December | 0.727675E+09 | 0.992689E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97197579.99 |
| Annual Sum or Average | 0.856778E+10 | 0.116881E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 162091.12 | 0.115063E+10 |
| Minimum of Months | 0.657255E+09 | 0.896622E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44131851.29 |
| Maximum of Months | 0.727675E+09 | 0.992689E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 147369.42 | 0.159537E+09 |
Report: SpaceGainsMonthly
For: G CORRIDOR
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.727675E+09 | 0.992689E+09 | 0.299778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.816440E+10 |
| February | 0.657255E+09 | 0.896622E+09 | 0.270767E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.681067E+10 |
| March | 0.727675E+09 | 0.992689E+09 | 0.299778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.637336E+10 |
| April | 0.704201E+09 | 0.960667E+09 | 0.290107E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.390791E+10 |
| May | 0.727675E+09 | 0.992689E+09 | 0.299778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.229601E+10 |
| June | 0.704201E+09 | 0.960667E+09 | 0.290107E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1215836.81 | 0.167610E+10 |
| July | 0.727675E+09 | 0.992689E+09 | 0.299778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9368311.47 | 0.158210E+10 |
| August | 0.727675E+09 | 0.992689E+09 | 0.299778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.211259E+10 |
| September | 0.704201E+09 | 0.960667E+09 | 0.290107E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.306505E+10 |
| October | 0.727675E+09 | 0.992689E+09 | 0.299778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.498761E+10 |
| November | 0.704201E+09 | 0.960667E+09 | 0.290107E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.793615E+10 |
| December | 0.727675E+09 | 0.992689E+09 | 0.299778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.848690E+10 |
| Annual Sum or Average | 0.856778E+10 | 0.116881E+11 | 0.352964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10584148.28 | 0.573988E+11 |
| Minimum of Months | 0.657255E+09 | 0.896622E+09 | 0.270767E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.158210E+10 |
| Maximum of Months | 0.727675E+09 | 0.992689E+09 | 0.299778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9368311.47 | 0.848690E+10 |
Report: SpaceGainsMonthly
For: M CORRIDOR
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.727675E+09 | 0.992689E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99003286.31 |
| February | 0.657255E+09 | 0.896622E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83057918.86 |
| March | 0.727675E+09 | 0.992689E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124793E+09 |
| April | 0.704201E+09 | 0.960667E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127432E+09 |
| May | 0.727675E+09 | 0.992689E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86105641.89 |
| June | 0.704201E+09 | 0.960667E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23697.01 | 47956619.09 |
| July | 0.727675E+09 | 0.992689E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 158083.83 | 34178842.69 |
| August | 0.727675E+09 | 0.992689E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48088874.12 |
| September | 0.704201E+09 | 0.960667E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51439231.00 |
| October | 0.727675E+09 | 0.992689E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106184E+09 |
| November | 0.704201E+09 | 0.960667E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37837204.75 |
| December | 0.727675E+09 | 0.992689E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77563167.14 |
| Annual Sum or Average | 0.856778E+10 | 0.116881E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 181780.84 | 0.923640E+09 |
| Minimum of Months | 0.657255E+09 | 0.896622E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34178842.69 |
| Maximum of Months | 0.727675E+09 | 0.992689E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 158083.83 | 0.127432E+09 |
Report: PeakSpaceGainsMonthly
For: G SW APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 1134.56 | 28-JAN-24:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 694.13 | 23-FEB-18:55 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 506.24 | 25-MAR-09:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 706.57 | 01-APR-19:00 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 409.80 | 27-MAY-11:00 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 55.38 | 30-JUN-15:00 | 291.40 | 24-JUN-21:00 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 137.25 | 21-JUL-16:00 | 199.18 | 04-JUL-17:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.80 | 11-AUG-16:00 | 310.04 | 29-AUG-20:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 186.31 | 30-SEP-21:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 418.10 | 21-OCT-05:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 453.45 | 03-NOV-20:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 465.51 | 22-DEC-14:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 186.31 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 137.25 | 1134.56 |
Report: PeakSpaceGainsMonthly
For: G NW APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 1134.56 | 28-JAN-24:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 694.13 | 23-FEB-19:00 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 506.24 | 25-MAR-09:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 706.57 | 01-APR-19:00 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 409.80 | 27-MAY-11:00 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 55.38 | 30-JUN-15:00 | 287.55 | 24-JUN-21:00 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 137.25 | 21-JUL-16:00 | 193.67 | 04-JUL-17:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.80 | 11-AUG-16:00 | 298.05 | 29-AUG-20:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 186.31 | 30-SEP-21:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 418.10 | 21-OCT-05:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 453.45 | 03-NOV-20:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 465.51 | 22-DEC-14:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 186.31 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 137.25 | 1134.56 |
Report: PeakSpaceGainsMonthly
For: OFFICE
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 451.21 | 03-JAN-08:09 | 582.92 | 03-JAN-08:09 | 588.62 | 03-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 999.20 | 28-JAN-24:00 |
| February | 451.21 | 01-FEB-08:09 | 582.92 | 01-FEB-08:09 | 588.62 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 603.67 | 23-FEB-19:00 |
| March | 451.21 | 01-MAR-08:09 | 582.92 | 01-MAR-08:09 | 588.62 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 453.18 | 10-MAR-13:00 |
| April | 451.21 | 03-APR-07:10 | 582.92 | 03-APR-07:10 | 588.62 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 566.78 | 01-APR-19:00 |
| May | 451.21 | 01-MAY-07:10 | 582.92 | 01-MAY-07:10 | 588.62 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 383.38 | 27-MAY-11:00 |
| June | 451.21 | 01-JUN-07:10 | 582.92 | 01-JUN-07:10 | 588.62 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 55.38 | 30-JUN-15:00 | 310.67 | 25-JUN-06:00 |
| July | 451.21 | 03-JUL-07:10 | 582.92 | 03-JUL-07:10 | 588.62 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 137.25 | 21-JUL-16:00 | 208.92 | 04-JUL-17:00 |
| August | 451.21 | 01-AUG-07:10 | 582.92 | 01-AUG-07:10 | 588.62 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.80 | 11-AUG-16:00 | 329.82 | 29-AUG-20:00 |
| September | 451.21 | 01-SEP-07:10 | 582.92 | 01-SEP-07:10 | 588.62 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 198.04 | 21-SEP-14:00 |
| October | 451.21 | 02-OCT-07:10 | 582.92 | 02-OCT-07:10 | 588.62 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 362.98 | 31-OCT-15:00 |
| November | 451.21 | 01-NOV-07:10 | 582.92 | 01-NOV-07:10 | 588.62 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 365.41 | 01-NOV-09:00 |
| December | 451.21 | 01-DEC-08:09 | 582.92 | 01-DEC-08:09 | 588.62 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 465.51 | 22-DEC-14:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 451.21 | 582.92 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 198.04 | |||||
| Maximum of Months | 451.21 | 582.92 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 137.25 | 999.20 |
Report: PeakSpaceGainsMonthly
For: G NE APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 1134.56 | 28-JAN-24:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 694.13 | 23-FEB-19:00 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 506.24 | 25-MAR-09:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 706.57 | 01-APR-19:00 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 409.80 | 27-MAY-11:00 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 55.38 | 30-JUN-15:00 | 287.82 | 24-JUN-21:00 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 137.25 | 21-JUL-16:00 | 194.55 | 04-JUL-17:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.80 | 11-AUG-16:00 | 300.72 | 29-AUG-20:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 186.31 | 30-SEP-21:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 418.10 | 21-OCT-05:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 453.45 | 03-NOV-20:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 465.51 | 22-DEC-14:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 186.31 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 137.25 | 1134.56 |
Report: PeakSpaceGainsMonthly
For: G N1 APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 684.34 | 28-JAN-24:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 418.68 | 23-FEB-18:55 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 305.35 | 25-MAR-09:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 426.18 | 01-APR-19:00 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 247.18 | 27-MAY-11:00 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 33.41 | 30-JUN-15:00 | 182.23 | 25-JUN-06:00 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 82.78 | 21-JUL-16:00 | 120.19 | 04-JUL-17:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.55 | 11-AUG-16:00 | 185.66 | 29-AUG-20:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 112.38 | 30-SEP-21:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 252.19 | 21-OCT-05:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 273.51 | 03-NOV-20:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 280.78 | 22-DEC-14:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 112.38 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 82.78 | 684.34 |
Report: PeakSpaceGainsMonthly
For: G N2 APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 684.34 | 28-JAN-24:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 418.68 | 23-FEB-18:55 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 305.35 | 25-MAR-09:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 426.18 | 01-APR-19:00 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 247.18 | 27-MAY-11:00 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 33.41 | 30-JUN-15:00 | 182.26 | 25-JUN-06:00 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 82.78 | 21-JUL-16:00 | 120.10 | 04-JUL-17:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.55 | 11-AUG-16:00 | 185.93 | 29-AUG-20:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 112.38 | 30-SEP-21:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 252.19 | 21-OCT-05:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 273.51 | 03-NOV-20:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 280.78 | 22-DEC-14:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 112.38 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 82.78 | 684.34 |
Report: PeakSpaceGainsMonthly
For: G S1 APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 684.34 | 28-JAN-24:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 418.68 | 23-FEB-18:55 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 305.35 | 25-MAR-09:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 426.18 | 01-APR-19:00 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 247.18 | 27-MAY-11:00 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 33.41 | 30-JUN-15:00 | 183.87 | 25-JUN-06:00 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 82.78 | 21-JUL-16:00 | 120.11 | 04-JUL-17:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.55 | 11-AUG-16:00 | 192.63 | 29-AUG-20:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 114.34 | 04-SEP-14:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 252.19 | 21-OCT-05:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 273.51 | 03-NOV-20:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 280.78 | 22-DEC-14:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 114.34 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 82.78 | 684.34 |
Report: PeakSpaceGainsMonthly
For: G S2 APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 684.34 | 28-JAN-24:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 418.68 | 23-FEB-18:55 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 305.35 | 25-MAR-09:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 426.18 | 01-APR-19:00 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 247.18 | 27-MAY-11:00 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 33.41 | 30-JUN-15:00 | 185.03 | 25-JUN-06:00 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 82.78 | 21-JUL-16:00 | 120.11 | 04-JUL-17:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.55 | 11-AUG-16:00 | 193.56 | 29-AUG-20:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 114.86 | 04-SEP-14:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 252.19 | 21-OCT-05:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 273.51 | 03-NOV-20:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 280.78 | 22-DEC-14:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 114.86 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 82.78 | 684.34 |
Report: PeakSpaceGainsMonthly
For: M SW APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 1631.17 | 28-JAN-24:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 998.00 | 23-FEB-18:55 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 727.94 | 25-MAR-09:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1016.12 | 01-APR-19:00 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 589.52 | 27-MAY-11:00 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 79.22 | 30-JUN-15:00 | 435.35 | 24-JUN-21:00 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 196.51 | 21-JUL-16:00 | 286.64 | 04-JUL-17:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 29.53 | 11-AUG-16:00 | 449.27 | 29-AUG-20:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 271.03 | 04-SEP-14:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 601.29 | 21-OCT-05:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 652.12 | 03-NOV-20:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 669.27 | 22-DEC-14:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.03 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 196.51 | 1631.17 |
Report: PeakSpaceGainsMonthly
For: M NW APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 1631.17 | 28-JAN-24:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 998.00 | 23-FEB-19:00 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 727.94 | 25-MAR-09:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1016.12 | 01-APR-19:00 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 589.52 | 27-MAY-11:00 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 79.22 | 30-JUN-15:00 | 433.24 | 24-JUN-21:00 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 196.51 | 21-JUL-16:00 | 286.64 | 04-JUL-17:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 29.53 | 11-AUG-16:00 | 440.67 | 29-AUG-20:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 267.98 | 30-SEP-21:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 601.29 | 21-OCT-05:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 652.12 | 03-NOV-20:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 669.27 | 22-DEC-14:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 267.98 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 196.51 | 1631.17 |
Report: PeakSpaceGainsMonthly
For: M SE APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 1631.17 | 28-JAN-24:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 998.00 | 23-FEB-18:55 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 727.94 | 25-MAR-09:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1016.12 | 01-APR-19:00 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 591.91 | 27-MAY-11:00 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 79.22 | 30-JUN-15:00 | 435.61 | 24-JUN-21:00 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 196.51 | 21-JUL-16:00 | 286.64 | 04-JUL-17:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 29.53 | 11-AUG-16:00 | 450.11 | 29-AUG-20:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 273.28 | 04-SEP-14:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 601.29 | 21-OCT-05:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 652.12 | 03-NOV-20:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 669.27 | 22-DEC-14:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 273.28 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 196.51 | 1631.17 |
Report: PeakSpaceGainsMonthly
For: M NE APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 1631.17 | 28-JAN-24:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 998.00 | 23-FEB-19:00 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 727.94 | 25-MAR-09:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1016.12 | 01-APR-19:00 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 589.52 | 27-MAY-11:00 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 79.22 | 30-JUN-15:00 | 433.50 | 24-JUN-21:00 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 196.51 | 21-JUL-16:00 | 286.64 | 04-JUL-17:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 29.53 | 11-AUG-16:00 | 442.07 | 29-AUG-20:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 267.98 | 30-SEP-21:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 601.29 | 21-OCT-05:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 652.12 | 03-NOV-20:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 669.27 | 22-DEC-14:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 267.98 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 196.51 | 1631.17 |
Report: PeakSpaceGainsMonthly
For: M N1 APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 983.88 | 28-JAN-24:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 601.97 | 23-FEB-19:00 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 439.08 | 25-MAR-09:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 612.90 | 01-APR-19:00 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 364.12 | 27-MAY-11:00 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 47.78 | 30-JUN-15:00 | 272.35 | 25-JUN-06:00 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 118.53 | 21-JUL-16:00 | 172.89 | 04-JUL-17:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.81 | 11-AUG-16:00 | 274.14 | 29-AUG-20:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 161.64 | 30-SEP-21:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 362.68 | 21-OCT-05:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 393.34 | 03-NOV-20:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 403.69 | 22-DEC-14:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 161.64 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 118.53 | 983.88 |
Report: PeakSpaceGainsMonthly
For: M N2 APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 983.88 | 28-JAN-24:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 601.97 | 23-FEB-19:00 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 439.08 | 25-MAR-09:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 612.90 | 01-APR-19:00 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 364.78 | 27-MAY-11:00 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 47.78 | 30-JUN-15:00 | 272.38 | 25-JUN-06:00 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 118.53 | 21-JUL-16:00 | 172.89 | 04-JUL-17:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.81 | 11-AUG-16:00 | 274.25 | 29-AUG-20:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 162.14 | 04-SEP-14:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 362.68 | 21-OCT-05:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 393.34 | 03-NOV-20:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 403.69 | 22-DEC-14:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 162.14 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 118.53 | 983.88 |
Report: PeakSpaceGainsMonthly
For: M S1 APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 983.88 | 28-JAN-24:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 601.97 | 23-FEB-18:55 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 439.08 | 25-MAR-09:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 612.90 | 01-APR-19:00 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 370.69 | 27-MAY-11:00 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 47.78 | 30-JUN-15:00 | 272.82 | 25-JUN-06:00 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 118.53 | 21-JUL-16:00 | 172.89 | 04-JUL-17:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.81 | 11-AUG-16:00 | 278.39 | 29-AUG-20:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 170.06 | 04-SEP-14:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 362.68 | 21-OCT-05:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 393.34 | 03-NOV-20:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 403.69 | 22-DEC-14:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 170.06 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 118.53 | 983.88 |
Report: PeakSpaceGainsMonthly
For: M S2 APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 983.88 | 28-JAN-24:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 601.97 | 23-FEB-18:55 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 439.08 | 25-MAR-09:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 612.90 | 01-APR-19:00 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 371.46 | 27-MAY-11:00 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 47.78 | 30-JUN-15:00 | 272.86 | 25-JUN-06:00 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 118.53 | 21-JUL-16:00 | 172.89 | 04-JUL-17:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.81 | 11-AUG-16:00 | 278.43 | 29-AUG-20:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 170.20 | 04-SEP-14:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 362.68 | 21-OCT-05:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 393.34 | 03-NOV-20:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 403.69 | 22-DEC-14:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 170.20 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 118.53 | 983.88 |
Report: PeakSpaceGainsMonthly
For: T SW APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 2159.60 | 28-JAN-24:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1321.42 | 23-FEB-18:55 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 964.05 | 25-MAR-09:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1346.04 | 01-APR-19:00 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 781.41 | 27-MAY-11:00 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 103.82 | 30-JUN-15:00 | 529.84 | 24-JUN-21:00 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 258.02 | 21-JUL-16:00 | 379.85 | 04-JUL-17:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.08 | 11-AUG-16:00 | 522.02 | 29-AUG-20:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 355.12 | 30-SEP-21:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 796.57 | 21-OCT-05:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 863.88 | 03-NOV-20:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 886.11 | 22-DEC-14:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 355.12 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 258.02 | 2159.60 |
Report: PeakSpaceGainsMonthly
For: T NW APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 2159.60 | 28-JAN-24:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1321.42 | 23-FEB-19:00 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 964.05 | 25-MAR-09:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1346.04 | 01-APR-19:00 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 781.41 | 27-MAY-11:00 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 103.82 | 30-JUN-15:00 | 526.53 | 24-JUN-21:00 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 258.02 | 21-JUL-16:00 | 371.11 | 04-JUL-17:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.08 | 11-AUG-16:00 | 506.46 | 29-AUG-20:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 355.12 | 30-SEP-21:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 796.57 | 21-OCT-05:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 863.88 | 03-NOV-20:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 886.11 | 22-DEC-14:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 355.12 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 258.02 | 2159.60 |
Report: PeakSpaceGainsMonthly
For: T SE APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 2159.60 | 28-JAN-24:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1321.42 | 23-FEB-18:55 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 964.05 | 25-MAR-09:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1346.04 | 01-APR-19:00 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 781.41 | 27-MAY-11:00 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 103.82 | 30-JUN-15:00 | 530.75 | 24-JUN-21:00 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 258.02 | 21-JUL-16:00 | 379.67 | 04-JUL-17:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.08 | 11-AUG-16:00 | 525.59 | 31-AUG-10:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 372.35 | 28-SEP-13:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 796.57 | 21-OCT-05:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 863.88 | 03-NOV-20:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 886.11 | 22-DEC-14:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 372.35 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 258.02 | 2159.60 |
Report: PeakSpaceGainsMonthly
For: T NE APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 2159.60 | 28-JAN-24:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1321.42 | 23-FEB-19:00 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 964.05 | 25-MAR-09:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1346.04 | 01-APR-19:00 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 781.41 | 27-MAY-11:00 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 103.82 | 30-JUN-15:00 | 527.53 | 24-JUN-21:00 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 258.02 | 21-JUL-16:00 | 370.32 | 04-JUL-17:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.08 | 11-AUG-16:00 | 509.43 | 29-AUG-20:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 355.12 | 30-SEP-21:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 796.57 | 21-OCT-05:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 863.88 | 03-NOV-20:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 886.11 | 22-DEC-14:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 355.12 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 258.02 | 2159.60 |
Report: PeakSpaceGainsMonthly
For: T N1 APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 1302.62 | 28-JAN-24:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 797.04 | 23-FEB-19:00 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 581.49 | 25-MAR-09:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 811.90 | 01-APR-19:00 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 471.33 | 27-MAY-11:00 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 62.62 | 30-JUN-15:00 | 337.87 | 24-JUN-21:00 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 155.63 | 21-JUL-16:00 | 229.47 | 04-JUL-17:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.97 | 11-AUG-16:00 | 324.46 | 29-AUG-20:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 214.20 | 30-SEP-21:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 480.47 | 21-OCT-05:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 521.07 | 03-NOV-20:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 534.48 | 22-DEC-14:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 214.20 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 155.63 | 1302.62 |
Report: PeakSpaceGainsMonthly
For: T N2 APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 1302.62 | 28-JAN-24:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 797.04 | 23-FEB-19:00 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 581.49 | 25-MAR-09:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 811.90 | 01-APR-19:00 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 471.33 | 27-MAY-11:00 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 62.62 | 30-JUN-15:00 | 337.91 | 24-JUN-21:00 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 155.63 | 21-JUL-16:00 | 229.47 | 04-JUL-17:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.97 | 11-AUG-16:00 | 324.95 | 29-AUG-20:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 214.20 | 30-SEP-21:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 480.47 | 21-OCT-05:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 521.07 | 03-NOV-20:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 534.48 | 22-DEC-14:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 214.20 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 155.63 | 1302.62 |
Report: PeakSpaceGainsMonthly
For: T S1 APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 1302.62 | 28-JAN-24:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 797.04 | 23-FEB-18:55 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 581.49 | 25-MAR-09:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 811.90 | 01-APR-19:00 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 471.33 | 27-MAY-11:00 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 62.62 | 30-JUN-15:00 | 339.05 | 24-JUN-21:00 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 155.63 | 21-JUL-16:00 | 229.47 | 04-JUL-17:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.97 | 11-AUG-16:00 | 334.78 | 29-AUG-20:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 223.33 | 28-SEP-13:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 480.47 | 21-OCT-05:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 521.07 | 03-NOV-20:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 534.48 | 22-DEC-14:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 223.33 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 155.63 | 1302.62 |
Report: PeakSpaceGainsMonthly
For: T S2 APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 1302.62 | 28-JAN-24:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 797.04 | 23-FEB-18:55 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 581.49 | 25-MAR-09:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 811.90 | 01-APR-19:00 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 471.33 | 27-MAY-11:00 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 62.62 | 30-JUN-15:00 | 339.08 | 24-JUN-21:00 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 155.63 | 21-JUL-16:00 | 229.47 | 04-JUL-17:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.97 | 11-AUG-16:00 | 335.14 | 29-AUG-20:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 224.48 | 28-SEP-13:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 480.47 | 21-OCT-05:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 521.07 | 03-NOV-20:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 534.48 | 22-DEC-14:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 224.48 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 155.63 | 1302.62 |
Report: PeakSpaceGainsMonthly
For: T CORRIDOR
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 397.10 | 01-JAN-00:10 | 370.63 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 348.80 | 28-JAN-24:00 |
| February | 397.10 | 01-FEB-00:10 | 370.63 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 215.70 | 23-FEB-18:55 |
| March | 397.10 | 01-MAR-00:10 | 370.63 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 159.69 | 25-MAR-09:00 |
| April | 397.10 | 01-APR-00:10 | 370.63 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 233.00 | 01-APR-19:00 |
| May | 397.10 | 01-MAY-00:10 | 370.63 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 134.95 | 27-MAY-11:00 |
| June | 397.10 | 01-JUN-00:10 | 370.63 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.39 | 30-JUN-15:00 | 107.47 | 24-JUN-21:00 |
| July | 397.10 | 01-JUL-00:10 | 370.63 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.30 | 21-JUL-16:00 | 71.05 | 04-JUL-17:00 |
| August | 397.10 | 01-AUG-00:10 | 370.63 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 103.60 | 29-AUG-20:00 |
| September | 397.10 | 01-SEP-00:10 | 370.63 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 63.11 | 30-SEP-21:00 |
| October | 397.10 | 01-OCT-00:10 | 370.63 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 131.79 | 21-OCT-04:00 |
| November | 397.10 | 01-NOV-00:10 | 370.63 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 140.20 | 03-NOV-20:00 |
| December | 397.10 | 01-DEC-00:10 | 370.63 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 143.10 | 22-DEC-14:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
| Minimum of Months | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.11 | ||||
| Maximum of Months | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.30 | 348.80 |
Report: PeakSpaceGainsMonthly
For: G CORRIDOR
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 397.10 | 01-JAN-00:10 | 370.63 | 01-JAN-00:10 | 208.40 | 01-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 35034.42 | 12-JAN-07:01 |
| February | 397.10 | 01-FEB-00:10 | 370.63 | 01-FEB-00:10 | 208.40 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 32100.56 | 27-FEB-07:01 |
| March | 397.10 | 01-MAR-00:10 | 370.63 | 01-MAR-00:10 | 208.40 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 28115.27 | 01-MAR-07:01 |
| April | 397.10 | 01-APR-00:10 | 370.63 | 01-APR-00:10 | 208.40 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 23877.28 | 03-APR-06:01 |
| May | 397.10 | 01-MAY-00:10 | 370.63 | 01-MAY-00:10 | 208.40 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 11647.68 | 27-MAY-06:01 |
| June | 397.10 | 01-JUN-00:10 | 370.63 | 01-JUN-00:10 | 208.40 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 169.95 | 30-JUN-15:00 | 9098.79 | 07-JUN-06:01 |
| July | 397.10 | 01-JUL-00:10 | 370.63 | 01-JUL-00:10 | 208.40 | 01-JUL-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1547.44 | 29-JUL-16:03 | 8962.11 | 17-JUL-06:01 |
| August | 397.10 | 01-AUG-00:10 | 370.63 | 01-AUG-00:10 | 208.40 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 14052.36 | 31-AUG-06:01 |
| September | 397.10 | 01-SEP-00:10 | 370.63 | 01-SEP-00:10 | 208.40 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 14311.70 | 30-SEP-06:01 |
| October | 397.10 | 01-OCT-00:10 | 370.63 | 01-OCT-00:10 | 208.40 | 01-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 23735.97 | 22-OCT-06:01 |
| November | 397.10 | 01-NOV-00:10 | 370.63 | 01-NOV-00:10 | 208.40 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 28076.55 | 29-NOV-07:01 |
| December | 397.10 | 01-DEC-00:10 | 370.63 | 01-DEC-00:10 | 208.40 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 31624.41 | 15-DEC-07:01 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 397.10 | 370.63 | 208.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8962.11 | |||||
| Maximum of Months | 397.10 | 370.63 | 208.40 | 0.00 | 0.00 | 0.00 | 0.00 | 1547.44 | 35034.42 |
Report: PeakSpaceGainsMonthly
For: M CORRIDOR
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 397.10 | 01-JAN-00:10 | 370.63 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 278.08 | 28-JAN-24:00 |
| February | 397.10 | 01-FEB-00:10 | 370.63 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 171.65 | 23-FEB-18:55 |
| March | 397.10 | 01-MAR-00:10 | 370.63 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 128.00 | 25-MAR-09:00 |
| April | 397.10 | 01-APR-00:10 | 370.63 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 182.22 | 01-APR-19:00 |
| May | 397.10 | 01-MAY-00:10 | 370.63 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 115.30 | 27-MAY-11:00 |
| June | 397.10 | 01-JUN-00:10 | 370.63 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.94 | 30-JUN-15:00 | 87.52 | 25-JUN-06:00 |
| July | 397.10 | 01-JUL-00:10 | 370.63 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.31 | 21-JUL-16:00 | 56.90 | 04-JUL-17:00 |
| August | 397.10 | 01-AUG-00:10 | 370.63 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 86.86 | 29-AUG-20:00 |
| September | 397.10 | 01-SEP-00:10 | 370.63 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 52.22 | 04-SEP-14:00 |
| October | 397.10 | 01-OCT-00:10 | 370.63 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 106.02 | 21-OCT-04:00 |
| November | 397.10 | 01-NOV-00:10 | 370.63 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 112.65 | 03-NOV-20:00 |
| December | 397.10 | 01-DEC-00:10 | 370.63 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 114.40 | 22-DEC-14:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
| Minimum of Months | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.22 | ||||
| Maximum of Months | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.31 | 278.08 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: G SW APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 0.00 | 01-JAN-00:10 | 237.50 | 8.68 | 264.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 241.99 |
| February | 0.00 | 01-FEB-00:10 | 237.50 | 8.68 | 264.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 179.91 |
| March | 341.04 | 22-MAR-16:08 | 0.00 | 867.99 | 5886.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 660.41 | 23-APR-22:20 | 237.50 | 21.70 | 341.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 246.21 |
| May | 879.00 | 15-MAY-16:25 | 0.00 | 173.60 | 1177.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 115.19 |
| June | 1658.68 | 21-JUN-16:30 | 0.00 | 86.80 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 8.16 | 0.00 |
| July | 1950.51 | 12-JUL-16:30 | 0.00 | 173.60 | 1177.25 | 0.00 | 0.00 | 0.00 | 0.00 | 10.90 | 0.00 |
| August | 2113.97 | 11-AUG-16:06 | 0.00 | 434.00 | 2943.11 | 0.00 | 0.00 | 0.00 | 0.00 | 20.80 | 0.00 |
| September | 871.33 | 09-SEP-15:50 | 237.50 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.33 |
| October | 547.66 | 14-OCT-13:00 | 118.75 | 17.36 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 108.64 |
| November | 0.00 | 01-NOV-00:10 | 237.50 | 8.68 | 241.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 207.85 |
| December | 0.00 | 01-DEC-00:10 | 237.50 | 8.68 | 264.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 0.00 | 0.00 | 8.68 | 241.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 2113.97 | 237.50 | 867.99 | 5886.23 | 0.00 | 0.00 | 0.00 | 0.00 | 20.80 | 246.21 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: G NW APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 0.00 | 01-JAN-00:10 | 237.50 | 8.68 | 264.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 241.99 |
| February | 0.00 | 01-FEB-00:10 | 237.50 | 8.68 | 264.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 179.91 |
| March | 0.00 | 01-MAR-00:10 | 237.50 | 8.68 | 264.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.32 |
| April | 372.28 | 20-APR-20:10 | 237.50 | 95.48 | 500.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 124.43 |
| May | 507.62 | 19-MAY-04:10 | 237.50 | 56.42 | 253.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.20 |
| June | 1231.34 | 21-JUN-17:50 | 206.62 | 117.18 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 7.43 | 0.00 |
| July | 1481.44 | 11-JUL-19:00 | 206.62 | 138.88 | 547.42 | 0.00 | 0.00 | 0.00 | 0.00 | 25.86 | 0.00 |
| August | 1230.45 | 11-AUG-17:40 | 206.62 | 117.18 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 18.55 | 0.00 |
| September | 519.52 | 03-SEP-07:00 | 201.88 | 56.42 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 102.67 |
| October | 382.29 | 01-OCT-20:10 | 237.50 | 95.48 | 500.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.92 |
| November | 0.00 | 01-NOV-00:10 | 237.50 | 8.68 | 241.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 207.85 |
| December | 0.00 | 01-DEC-00:10 | 237.50 | 8.68 | 264.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 0.00 | 201.88 | 8.68 | 241.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 1481.44 | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 25.86 | 241.99 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: OFFICE
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 2214.23 | 12-JAN-07:03 | 0.00 | 1165.83 | 2943.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 1853.41 | 27-FEB-07:03 | 0.00 | 1165.83 | 2943.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 206.32 |
| March | 1792.80 | 01-MAR-07:03 | 0.00 | 1165.83 | 2943.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 151.84 |
| April | 1468.16 | 03-APR-06:03 | 0.00 | 1165.83 | 2943.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 256.51 |
| May | 5716.60 | 15-MAY-08:62 | 1804.82 | 2331.66 | 2354.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 151.13 |
| June | 6172.98 | 13-JUN-07:02 | 2707.23 | 3497.50 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.32 |
| July | 6537.67 | 13-JUL-07:01 | 3609.64 | 4663.33 | 4708.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 6441.25 | 28-AUG-08:62 | 2256.03 | 2914.58 | 2943.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.98 |
| September | 1835.46 | 01-SEP-08:65 | 902.41 | 1165.83 | 1177.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99.98 |
| October | 1422.84 | 27-OCT-07:03 | 4512.06 | 5829.16 | 5886.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 282.40 |
| November | 1818.62 | 30-NOV-08:03 | 4512.06 | 5829.16 | 5886.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 2012.75 | 15-DEC-08:03 | 4512.06 | 5829.16 | 5886.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.42 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 1422.84 | 0.00 | 1165.83 | 1177.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 6537.67 | 4512.06 | 5829.16 | 5886.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 282.40 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: G NE APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 0.00 | 01-JAN-00:10 | 237.50 | 8.68 | 264.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 241.99 |
| February | 0.00 | 01-FEB-00:10 | 237.50 | 8.68 | 264.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 179.91 |
| March | 0.00 | 01-MAR-00:10 | 237.50 | 8.68 | 264.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.32 |
| April | 324.90 | 22-APR-10:00 | 59.38 | 17.36 | 406.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.61 |
| May | 544.47 | 22-MAY-04:10 | 237.50 | 56.42 | 253.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.76 |
| June | 1084.91 | 13-JUN-17:15 | 413.25 | 234.36 | 1177.25 | 0.00 | 0.00 | 0.00 | 0.00 | 5.78 | 0.00 |
| July | 1353.44 | 11-JUL-10:30 | 59.38 | 17.36 | 412.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.44 |
| August | 1062.46 | 11-AUG-17:20 | 619.87 | 351.55 | 1765.87 | 0.00 | 0.00 | 0.00 | 0.00 | 19.67 | 0.00 |
| September | 531.37 | 03-SEP-07:00 | 201.88 | 56.42 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 104.92 |
| October | 382.61 | 01-OCT-20:10 | 237.50 | 95.48 | 500.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.96 |
| November | 0.00 | 01-NOV-00:10 | 237.50 | 8.68 | 241.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 207.85 |
| December | 0.00 | 01-DEC-00:10 | 237.50 | 8.68 | 264.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 0.00 | 59.38 | 8.68 | 241.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 1353.44 | 619.87 | 351.55 | 1765.87 | 0.00 | 0.00 | 0.00 | 0.00 | 19.67 | 241.99 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: G N1 APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 0.00 | 01-JAN-00:10 | 237.50 | 8.68 | 264.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 145.96 |
| February | 0.00 | 01-FEB-00:10 | 237.50 | 8.68 | 264.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 108.52 |
| March | 0.00 | 01-MAR-00:10 | 237.50 | 8.68 | 264.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.86 |
| April | 302.06 | 21-APR-20:40 | 237.50 | 95.48 | 500.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.27 |
| May | 546.31 | 17-MAY-04:40 | 237.50 | 56.42 | 253.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.14 |
| June | 864.81 | 21-JUN-20:00 | 206.62 | 138.88 | 523.87 | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 0.00 |
| July | 1015.26 | 11-JUL-20:00 | 206.62 | 138.88 | 523.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.79 |
| August | 857.27 | 02-AUG-17:40 | 206.62 | 117.18 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 |
| September | 532.77 | 03-SEP-07:00 | 201.88 | 56.42 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.44 |
| October | 384.21 | 01-OCT-20:10 | 237.50 | 95.48 | 500.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.07 |
| November | 0.00 | 01-NOV-00:10 | 237.50 | 8.68 | 241.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 125.37 |
| December | 0.00 | 01-DEC-00:10 | 237.50 | 8.68 | 264.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 0.00 | 201.88 | 8.68 | 241.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 1015.26 | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 145.96 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: G N2 APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 0.00 | 01-JAN-00:10 | 237.50 | 8.68 | 264.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 145.96 |
| February | 0.00 | 01-FEB-00:10 | 237.50 | 8.68 | 264.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 108.52 |
| March | 0.00 | 01-MAR-00:10 | 237.50 | 8.68 | 264.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.86 |
| April | 297.49 | 28-APR-17:12 | 826.50 | 468.73 | 2354.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.65 |
| May | 564.01 | 17-MAY-04:10 | 237.50 | 56.42 | 253.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.14 |
| June | 858.08 | 21-JUN-20:00 | 206.62 | 138.88 | 523.87 | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 0.00 |
| July | 1013.93 | 11-JUL-20:00 | 206.62 | 138.88 | 523.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.79 |
| August | 857.81 | 02-AUG-17:30 | 413.25 | 234.36 | 1177.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.92 |
| September | 534.16 | 03-SEP-07:00 | 201.88 | 56.42 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.60 |
| October | 384.24 | 01-OCT-20:10 | 237.50 | 95.48 | 500.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.07 |
| November | 0.00 | 01-NOV-00:10 | 237.50 | 8.68 | 241.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 125.37 |
| December | 0.00 | 01-DEC-00:10 | 237.50 | 8.68 | 264.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 0.00 | 201.88 | 8.68 | 241.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 1013.93 | 826.50 | 468.73 | 2354.49 | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 145.96 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: G S1 APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 0.00 | 01-JAN-00:10 | 237.50 | 8.68 | 264.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 145.96 |
| February | 139.81 | 15-FEB-14:00 | 0.00 | 17.36 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 462.20 | 22-MAR-16:10 | 0.00 | 867.99 | 5886.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 690.69 | 24-APR-01:10 | 237.50 | 8.68 | 229.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 181.21 |
| May | 854.29 | 15-MAY-16:10 | 0.00 | 694.39 | 4708.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.54 |
| June | 1299.12 | 21-JUN-16:05 | 0.00 | 347.20 | 2354.49 | 0.00 | 0.00 | 0.00 | 0.00 | 4.48 | 0.00 |
| July | 1695.94 | 23-JUL-15:10 | 237.50 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 4.89 | 0.00 |
| August | 1742.40 | 11-AUG-16:10 | 0.00 | 434.00 | 2943.11 | 0.00 | 0.00 | 0.00 | 0.00 | 12.55 | 0.00 |
| September | 920.81 | 09-SEP-15:30 | 237.50 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.09 |
| October | 622.89 | 13-OCT-13:20 | 0.00 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 202.56 |
| November | 0.00 | 01-NOV-00:10 | 237.50 | 8.68 | 241.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 125.37 |
| December | 0.00 | 01-DEC-00:10 | 237.50 | 8.68 | 264.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 0.00 | 0.00 | 8.68 | 229.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 1742.40 | 237.50 | 867.99 | 5886.23 | 0.00 | 0.00 | 0.00 | 0.00 | 12.55 | 202.56 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: G S2 APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 0.00 | 01-JAN-00:10 | 237.50 | 8.68 | 264.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 145.96 |
| February | 91.63 | 15-FEB-14:00 | 0.00 | 17.36 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 461.97 | 22-MAR-16:03 | 0.00 | 867.99 | 5886.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 684.50 | 24-APR-00:50 | 237.50 | 8.68 | 241.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 179.51 |
| May | 950.08 | 13-MAY-15:10 | 237.50 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.48 |
| June | 1349.07 | 21-JUN-16:05 | 0.00 | 347.20 | 2354.49 | 0.00 | 0.00 | 0.00 | 0.00 | 4.48 | 0.00 |
| July | 1851.28 | 23-JUL-15:10 | 237.50 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 4.89 | 0.00 |
| August | 1799.24 | 11-AUG-16:04 | 0.00 | 434.00 | 2943.11 | 0.00 | 0.00 | 0.00 | 0.00 | 12.55 | 0.00 |
| September | 986.04 | 09-SEP-15:20 | 237.50 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.50 |
| October | 611.55 | 13-OCT-13:40 | 0.00 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 193.95 |
| November | 0.00 | 01-NOV-00:10 | 237.50 | 8.68 | 241.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 125.37 |
| December | 0.00 | 01-DEC-00:10 | 237.50 | 8.68 | 264.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 0.00 | 0.00 | 8.68 | 241.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 1851.28 | 237.50 | 867.99 | 5886.23 | 0.00 | 0.00 | 0.00 | 0.00 | 12.55 | 193.95 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: M SW APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 0.00 | 01-JAN-00:10 | 237.50 | 8.68 | 264.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 347.95 |
| February | 726.09 | 15-FEB-14:00 | 0.00 | 17.36 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 996.23 | 15-MAR-16:35 | 0.00 | 173.60 | 1177.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 315.66 |
| April | 2133.81 | 22-APR-16:05 | 1425.00 | 520.80 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 191.10 |
| May | 2318.31 | 31-MAY-15:30 | 0.00 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.06 |
| June | 2625.50 | 20-JUN-16:08 | 0.00 | 347.20 | 2354.49 | 0.00 | 0.00 | 0.00 | 0.00 | 14.70 | 0.00 |
| July | 2748.02 | 29-JUL-15:30 | 237.50 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 74.69 | 0.00 |
| August | 2845.78 | 10-AUG-16:20 | 0.00 | 347.20 | 2354.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.44 |
| September | 1856.54 | 09-SEP-15:50 | 237.50 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86.89 |
| October | 704.18 | 12-OCT-12:20 | 0.00 | 17.36 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 217.14 |
| November | 222.08 | 08-NOV-15:30 | 0.00 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 131.33 |
| December | 0.00 | 01-DEC-00:10 | 237.50 | 8.68 | 264.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 0.00 | 0.00 | 8.68 | 264.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 2845.78 | 1425.00 | 520.80 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 74.69 | 347.95 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: M NW APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 0.00 | 01-JAN-00:10 | 237.50 | 8.68 | 264.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 347.95 |
| February | 0.00 | 01-FEB-00:10 | 237.50 | 8.68 | 264.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 258.67 |
| March | 491.87 | 22-MAR-17:12 | 1033.12 | 585.91 | 2943.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.32 |
| April | 712.58 | 21-APR-03:00 | 237.50 | 8.68 | 223.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 1514.43 | 31-MAY-17:30 | 206.62 | 117.18 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.17 |
| June | 1998.10 | 21-JUN-17:05 | 413.25 | 234.36 | 1177.25 | 0.00 | 0.00 | 0.00 | 0.00 | 12.66 | 0.00 |
| July | 2142.58 | 11-JUL-18:00 | 206.62 | 117.18 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 35.71 | 0.00 |
| August | 1772.36 | 11-AUG-17:25 | 413.25 | 234.36 | 1177.25 | 0.00 | 0.00 | 0.00 | 0.00 | 27.12 | 0.00 |
| September | 625.41 | 09-SEP-06:40 | 403.75 | 112.83 | 765.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.09 |
| October | 405.77 | 04-OCT-18:10 | 206.62 | 138.88 | 547.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 109.52 |
| November | 0.00 | 01-NOV-00:10 | 237.50 | 8.68 | 241.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 298.89 |
| December | 0.00 | 01-DEC-00:10 | 237.50 | 8.68 | 264.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 0.00 | 206.62 | 8.68 | 223.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 2142.58 | 1033.12 | 585.91 | 2943.11 | 0.00 | 0.00 | 0.00 | 0.00 | 35.71 | 347.95 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: M SE APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 3.30 | 23-JAN-13:00 | 0.00 | 17.36 | 406.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 839.19 | 15-FEB-14:00 | 0.00 | 17.36 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 1097.31 | 31-MAR-11:00 | 0.00 | 17.36 | 412.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 190.11 |
| April | 2021.92 | 22-APR-13:30 | 118.75 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83.60 |
| May | 2368.50 | 12-MAY-13:30 | 0.00 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.05 |
| June | 2494.39 | 29-JUN-14:10 | 0.00 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 13.01 | 0.00 |
| July | 2841.09 | 22-JUL-11:30 | 118.75 | 17.36 | 406.15 | 0.00 | 0.00 | 0.00 | 0.00 | 11.93 | 0.00 |
| August | 2695.45 | 10-AUG-14:10 | 0.00 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.46 |
| September | 1835.12 | 10-SEP-11:30 | 118.75 | 17.36 | 406.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86.46 |
| October | 800.94 | 22-OCT-12:00 | 118.75 | 17.36 | 406.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 130.94 | 08-NOV-12:00 | 0.00 | 17.36 | 412.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 01-DEC-00:10 | 237.50 | 8.68 | 264.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 0.00 | 0.00 | 8.68 | 264.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 2841.09 | 237.50 | 30.38 | 412.04 | 0.00 | 0.00 | 0.00 | 0.00 | 13.01 | 190.11 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: M NE APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 0.00 | 01-JAN-00:10 | 237.50 | 8.68 | 264.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 347.95 |
| February | 0.00 | 01-FEB-00:10 | 237.50 | 8.68 | 264.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 258.67 |
| March | 492.76 | 22-MAR-17:12 | 1033.12 | 585.91 | 2943.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.43 |
| April | 671.51 | 21-APR-06:00 | 237.50 | 60.76 | 317.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 1455.36 | 12-MAY-09:30 | 59.38 | 17.36 | 406.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.67 |
| June | 1860.07 | 13-JUN-06:50 | 201.88 | 56.42 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.94 |
| July | 1973.47 | 11-JUL-09:50 | 59.38 | 17.36 | 406.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.32 |
| August | 1524.40 | 10-AUG-09:20 | 59.38 | 17.36 | 406.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.56 |
| September | 658.98 | 16-SEP-07:00 | 201.88 | 56.42 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 188.70 |
| October | 450.79 | 04-OCT-18:50 | 206.62 | 138.88 | 547.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 105.56 |
| November | 0.00 | 01-NOV-00:10 | 237.50 | 8.68 | 241.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 298.89 |
| December | 0.00 | 01-DEC-00:10 | 237.50 | 8.68 | 264.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 0.00 | 59.38 | 8.68 | 241.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 1973.47 | 1033.12 | 585.91 | 2943.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 347.95 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: M N1 APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 101.38 | 21-JAN-21:00 | 206.62 | 138.88 | 523.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 193.28 | 09-FEB-19:00 | 206.62 | 117.18 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 507.35 | 22-MAR-17:25 | 413.25 | 234.36 | 1177.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.06 |
| April | 705.28 | 21-APR-03:00 | 237.50 | 8.68 | 223.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 965.43 | 31-MAY-17:20 | 413.25 | 234.36 | 1177.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.52 |
| June | 1301.65 | 21-JUN-20:00 | 206.62 | 138.88 | 523.87 | 0.00 | 0.00 | 0.00 | 0.00 | 3.76 | 0.00 |
| July | 1329.93 | 11-JUL-20:00 | 206.62 | 138.88 | 523.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.36 |
| August | 1107.91 | 02-AUG-17:30 | 413.25 | 234.36 | 1177.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.35 |
| September | 676.64 | 15-SEP-06:00 | 237.50 | 60.76 | 317.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 536.14 | 04-OCT-20:00 | 206.62 | 138.88 | 523.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.00 |
| November | 53.97 | 02-NOV-18:00 | 206.62 | 117.18 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 26.66 | 24-DEC-21:00 | 206.62 | 138.88 | 523.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85.19 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 26.66 | 206.62 | 8.68 | 223.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 1329.93 | 413.25 | 234.36 | 1177.25 | 0.00 | 0.00 | 0.00 | 0.00 | 3.76 | 85.19 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: M N2 APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 101.70 | 21-JAN-21:00 | 206.62 | 138.88 | 523.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 193.63 | 09-FEB-19:00 | 206.62 | 117.18 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 507.67 | 22-MAR-17:25 | 413.25 | 234.36 | 1177.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.10 |
| April | 688.25 | 21-APR-02:40 | 237.50 | 8.68 | 223.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.82 |
| May | 964.76 | 31-MAY-17:20 | 413.25 | 234.36 | 1177.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.52 |
| June | 1290.15 | 21-JUN-20:00 | 206.62 | 138.88 | 523.87 | 0.00 | 0.00 | 0.00 | 0.00 | 3.76 | 0.00 |
| July | 1324.59 | 11-JUL-20:00 | 206.62 | 138.88 | 523.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.36 |
| August | 1107.98 | 02-AUG-17:20 | 413.25 | 234.36 | 1177.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.64 |
| September | 677.99 | 15-SEP-06:00 | 237.50 | 60.76 | 317.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 536.55 | 04-OCT-20:00 | 206.62 | 138.88 | 523.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.06 |
| November | 54.16 | 02-NOV-18:00 | 206.62 | 117.18 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 26.72 | 24-DEC-21:00 | 206.62 | 138.88 | 523.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85.19 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 26.72 | 206.62 | 8.68 | 223.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 1324.59 | 413.25 | 234.36 | 1177.25 | 0.00 | 0.00 | 0.00 | 0.00 | 3.76 | 85.19 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: M S1 APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 363.85 | 23-JAN-13:00 | 0.00 | 17.36 | 406.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 979.42 | 20-FEB-13:00 | 118.75 | 17.36 | 406.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 1097.34 | 13-MAR-12:00 | 0.00 | 17.36 | 406.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 114.09 |
| April | 1778.04 | 22-APR-15:20 | 237.50 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 106.07 |
| May | 1883.56 | 12-MAY-13:30 | 0.00 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.16 |
| June | 1992.34 | 29-JUN-14:30 | 0.00 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 8.63 | 0.00 |
| July | 2288.36 | 23-JUL-13:40 | 118.75 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 3.75 | 0.00 |
| August | 2244.87 | 10-AUG-14:20 | 0.00 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.43 |
| September | 1729.29 | 09-SEP-15:10 | 237.50 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.21 |
| October | 1046.60 | 22-OCT-12:20 | 118.75 | 17.36 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.28 |
| November | 613.33 | 08-NOV-13:40 | 0.00 | 17.36 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 136.73 |
| December | 66.37 | 24-DEC-21:00 | 237.50 | 138.88 | 523.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85.19 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 66.37 | 0.00 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 2288.36 | 237.50 | 138.88 | 523.87 | 0.00 | 0.00 | 0.00 | 0.00 | 8.63 | 136.73 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: M S2 APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 365.26 | 23-JAN-13:00 | 0.00 | 17.36 | 406.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 989.40 | 20-FEB-13:00 | 118.75 | 17.36 | 406.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 1102.61 | 13-MAR-11:50 | 0.00 | 17.36 | 406.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 95.59 |
| April | 1783.60 | 22-APR-13:40 | 118.75 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.18 |
| May | 1902.67 | 12-MAY-13:30 | 0.00 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.16 |
| June | 2000.58 | 29-JUN-14:30 | 0.00 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 8.63 | 0.00 |
| July | 2303.21 | 23-JUL-13:40 | 118.75 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 3.75 | 0.00 |
| August | 2258.53 | 10-AUG-14:10 | 0.00 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.15 |
| September | 1742.42 | 09-SEP-15:10 | 237.50 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.21 |
| October | 1046.79 | 22-OCT-12:20 | 118.75 | 17.36 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.29 |
| November | 615.90 | 08-NOV-13:40 | 0.00 | 17.36 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 136.73 |
| December | 66.38 | 24-DEC-21:00 | 237.50 | 138.88 | 523.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85.19 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 66.38 | 0.00 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 2303.21 | 237.50 | 138.88 | 523.87 | 0.00 | 0.00 | 0.00 | 0.00 | 8.63 | 136.73 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: T SW APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 0.00 | 01-JAN-00:10 | 237.50 | 8.68 | 264.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 460.77 |
| February | 500.79 | 15-FEB-14:00 | 0.00 | 17.36 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 970.54 | 31-MAR-14:10 | 0.00 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 368.33 |
| April | 2561.77 | 21-APR-16:30 | 0.00 | 86.80 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 103.78 |
| May | 3013.83 | 31-MAY-15:30 | 0.00 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.42 |
| June | 3406.43 | 20-JUN-16:05 | 0.00 | 347.20 | 2354.49 | 0.00 | 0.00 | 0.00 | 0.00 | 18.98 | 0.00 |
| July | 3632.29 | 29-JUL-15:30 | 237.50 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 98.10 | 0.00 |
| August | 3514.61 | 10-AUG-16:10 | 0.00 | 434.00 | 2943.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.47 |
| September | 2221.64 | 09-SEP-16:07 | 1425.00 | 520.80 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 111.14 |
| October | 762.47 | 03-OCT-14:40 | 0.00 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 232.25 |
| November | 0.00 | 01-NOV-00:10 | 237.50 | 8.68 | 241.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 395.88 |
| December | 0.00 | 01-DEC-00:10 | 237.50 | 8.68 | 264.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 0.00 | 0.00 | 8.68 | 241.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 3632.29 | 1425.00 | 520.80 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 98.10 | 460.77 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: T NW APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 0.00 | 01-JAN-00:10 | 237.50 | 8.68 | 264.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 460.77 |
| February | 0.00 | 01-FEB-00:10 | 237.50 | 8.68 | 264.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 342.50 |
| March | 476.81 | 22-MAR-17:01 | 1653.00 | 937.46 | 4708.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.32 |
| April | 1021.99 | 21-APR-18:00 | 206.62 | 117.18 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 103.74 |
| May | 1921.02 | 31-MAY-17:10 | 413.25 | 234.36 | 1177.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.74 |
| June | 2530.08 | 20-JUN-17:30 | 206.62 | 117.18 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 16.73 | 0.00 |
| July | 2722.19 | 11-JUL-17:50 | 206.62 | 117.18 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 46.34 | 0.00 |
| August | 2116.04 | 11-AUG-17:30 | 413.25 | 234.36 | 1177.25 | 0.00 | 0.00 | 0.00 | 0.00 | 34.97 | 0.00 |
| September | 448.92 | 02-SEP-19:10 | 206.62 | 138.88 | 523.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97.23 |
| October | 381.80 | 01-OCT-20:10 | 237.50 | 95.48 | 500.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 100.95 |
| November | 0.00 | 01-NOV-00:10 | 237.50 | 8.68 | 241.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 395.88 |
| December | 0.00 | 01-DEC-00:10 | 237.50 | 8.68 | 264.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 0.00 | 206.62 | 8.68 | 241.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 2722.19 | 1653.00 | 937.46 | 4708.98 | 0.00 | 0.00 | 0.00 | 0.00 | 46.34 | 460.77 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: T SE APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 0.00 | 01-JAN-00:10 | 237.50 | 8.68 | 264.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 460.77 |
| February | 659.93 | 15-FEB-14:00 | 0.00 | 17.36 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 1063.43 | 31-MAR-11:30 | 0.00 | 17.36 | 406.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 121.55 |
| April | 2374.57 | 22-APR-13:30 | 118.75 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 111.09 |
| May | 2866.77 | 31-MAY-14:00 | 0.00 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.95 |
| June | 3243.85 | 29-JUN-14:10 | 0.00 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 16.80 | 0.00 |
| July | 3629.94 | 23-JUL-13:30 | 118.75 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 7.90 | 0.00 |
| August | 3291.44 | 10-AUG-13:50 | 0.00 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.83 |
| September | 1941.59 | 09-SEP-14:10 | 0.00 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 187.34 |
| October | 881.09 | 03-OCT-14:30 | 0.00 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 241.02 |
| November | 0.00 | 01-NOV-00:10 | 237.50 | 8.68 | 241.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 395.88 |
| December | 0.00 | 01-DEC-00:10 | 237.50 | 8.68 | 264.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 0.00 | 0.00 | 8.68 | 241.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 3629.94 | 237.50 | 30.38 | 406.15 | 0.00 | 0.00 | 0.00 | 0.00 | 16.80 | 460.77 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: T NE APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 0.00 | 01-JAN-00:10 | 237.50 | 8.68 | 264.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 460.77 |
| February | 0.00 | 01-FEB-00:10 | 237.50 | 8.68 | 264.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 342.50 |
| March | 462.08 | 22-MAR-16:07 | 1235.00 | 867.99 | 5886.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 583.75 | 28-APR-22:00 | 237.50 | 52.08 | 417.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 1680.15 | 31-MAY-08:00 | 92.63 | 26.04 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 108.70 |
| June | 2218.80 | 29-JUN-10:50 | 59.38 | 17.36 | 412.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.06 |
| July | 2351.26 | 11-JUL-10:10 | 59.38 | 17.36 | 412.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.41 |
| August | 1561.51 | 02-AUG-16:04 | 617.50 | 434.00 | 2943.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.17 |
| September | 511.32 | 08-SEP-08:50 | 59.38 | 17.36 | 394.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.91 |
| October | 381.67 | 01-OCT-20:10 | 237.50 | 95.48 | 500.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 100.92 |
| November | 0.00 | 01-NOV-00:10 | 237.50 | 8.68 | 241.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 395.88 |
| December | 0.00 | 01-DEC-00:10 | 237.50 | 8.68 | 264.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 0.00 | 59.38 | 8.68 | 241.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 2351.26 | 1235.00 | 867.99 | 5886.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 460.77 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: T N1 APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 0.00 | 01-JAN-00:10 | 237.50 | 8.68 | 264.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 277.93 |
| February | 0.00 | 01-FEB-00:10 | 237.50 | 8.68 | 264.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 206.59 |
| March | 406.98 | 22-MAR-16:15 | 494.00 | 347.20 | 2354.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 592.90 | 28-APR-22:10 | 237.50 | 21.70 | 341.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.77 |
| May | 1234.93 | 31-MAY-16:25 | 247.00 | 173.60 | 1177.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.92 |
| June | 1540.60 | 29-JUN-16:16 | 617.50 | 434.00 | 2943.11 | 0.00 | 0.00 | 0.00 | 0.00 | 17.66 | 0.00 |
| July | 1607.74 | 11-JUL-17:30 | 413.25 | 234.36 | 1177.25 | 0.00 | 0.00 | 0.00 | 0.00 | 27.95 | 0.00 |
| August | 1303.70 | 02-AUG-17:30 | 413.25 | 234.36 | 1177.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.86 |
| September | 450.10 | 18-SEP-22:00 | 237.50 | 52.08 | 417.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81.11 |
| October | 384.68 | 01-OCT-20:10 | 237.50 | 95.48 | 500.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.32 |
| November | 0.00 | 01-NOV-00:10 | 237.50 | 8.68 | 241.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 238.79 |
| December | 0.00 | 01-DEC-00:10 | 237.50 | 8.68 | 264.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 0.00 | 237.50 | 8.68 | 241.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 1607.74 | 617.50 | 434.00 | 2943.11 | 0.00 | 0.00 | 0.00 | 0.00 | 27.95 | 277.93 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: T N2 APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 0.00 | 01-JAN-00:10 | 237.50 | 8.68 | 264.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 277.93 |
| February | 0.00 | 01-FEB-00:10 | 237.50 | 8.68 | 264.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 206.59 |
| March | 411.74 | 22-MAR-16:15 | 494.00 | 347.20 | 2354.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 591.57 | 28-APR-22:10 | 237.50 | 21.70 | 341.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.71 |
| May | 1230.85 | 31-MAY-16:17 | 370.50 | 260.40 | 1765.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.29 |
| June | 1538.13 | 29-JUN-16:14 | 617.50 | 434.00 | 2943.11 | 0.00 | 0.00 | 0.00 | 0.00 | 17.66 | 0.00 |
| July | 1596.62 | 11-JUL-17:17 | 619.87 | 351.55 | 1765.87 | 0.00 | 0.00 | 0.00 | 0.00 | 27.95 | 0.00 |
| August | 1297.00 | 02-AUG-17:20 | 413.25 | 234.36 | 1177.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.27 |
| September | 448.14 | 18-SEP-22:00 | 237.50 | 52.08 | 417.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80.77 |
| October | 384.67 | 01-OCT-20:10 | 237.50 | 95.48 | 500.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.32 |
| November | 0.00 | 01-NOV-00:10 | 237.50 | 8.68 | 241.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 238.79 |
| December | 0.00 | 01-DEC-00:10 | 237.50 | 8.68 | 264.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 0.00 | 237.50 | 8.68 | 241.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 1596.62 | 619.87 | 434.00 | 2943.11 | 0.00 | 0.00 | 0.00 | 0.00 | 27.95 | 277.93 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: T S1 APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 0.00 | 01-JAN-00:10 | 237.50 | 8.68 | 264.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 277.93 |
| February | 902.05 | 15-FEB-13:40 | 0.00 | 17.36 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 1028.88 | 31-MAR-12:00 | 0.00 | 17.36 | 406.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 2069.38 | 20-APR-15:10 | 0.00 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82.22 |
| May | 2413.36 | 31-MAY-14:10 | 0.00 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.84 |
| June | 2711.73 | 29-JUN-14:30 | 0.00 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 11.17 | 0.00 |
| July | 3065.87 | 23-JUL-13:50 | 118.75 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 4.76 | 0.00 |
| August | 2833.72 | 10-AUG-14:20 | 0.00 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.51 |
| September | 1852.95 | 09-SEP-15:20 | 237.50 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83.26 |
| October | 915.94 | 03-OCT-14:30 | 0.00 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 145.38 |
| November | 254.20 | 08-NOV-13:50 | 0.00 | 17.36 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 189.98 |
| December | 0.00 | 01-DEC-00:10 | 237.50 | 8.68 | 264.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 0.00 | 0.00 | 8.68 | 264.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 3065.87 | 237.50 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 11.17 | 277.93 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: T S2 APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 0.00 | 01-JAN-00:10 | 237.50 | 8.68 | 264.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 277.93 |
| February | 902.32 | 15-FEB-13:40 | 0.00 | 17.36 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 1029.77 | 31-MAR-12:00 | 0.00 | 17.36 | 406.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 2075.63 | 20-APR-14:40 | 0.00 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.84 |
| May | 2431.92 | 31-MAY-14:10 | 0.00 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.84 |
| June | 2725.88 | 29-JUN-14:30 | 0.00 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 11.17 | 0.00 |
| July | 3086.30 | 23-JUL-13:50 | 118.75 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 4.76 | 0.00 |
| August | 2857.44 | 10-AUG-14:20 | 0.00 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.51 |
| September | 1866.83 | 09-SEP-15:20 | 237.50 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83.26 |
| October | 944.79 | 03-OCT-14:30 | 0.00 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 145.38 |
| November | 257.57 | 08-NOV-13:50 | 0.00 | 17.36 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 189.98 |
| December | 0.00 | 01-DEC-00:10 | 237.50 | 8.68 | 264.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 0.00 | 0.00 | 8.68 | 264.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 3086.30 | 237.50 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 11.17 | 277.93 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: T CORRIDOR
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 0.00 | 01-JAN-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.41 |
| February | 0.00 | 01-FEB-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.14 |
| March | 0.00 | 01-MAR-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.41 |
| April | 0.00 | 01-APR-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 109.12 |
| May | 0.00 | 01-MAY-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.48 |
| June | 0.00 | 01-JUN-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.48 |
| July | 0.00 | 01-JUL-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.79 |
| August | 0.00 | 01-AUG-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.67 |
| September | 0.00 | 01-SEP-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.09 |
| October | 0.00 | 01-OCT-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.89 |
| November | 0.00 | 01-NOV-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.91 |
| December | 0.00 | 01-DEC-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
| Minimum of Months | 0.00 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 109.12 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: G CORRIDOR
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 0.00 | 01-JAN-00:10 | 397.10 | 370.63 | 56.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.35 |
| February | 0.00 | 01-FEB-00:10 | 397.10 | 370.63 | 56.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.86 |
| March | 0.00 | 01-MAR-00:10 | 397.10 | 370.63 | 56.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.15 |
| April | 0.00 | 01-APR-00:10 | 397.10 | 370.63 | 56.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.48 |
| May | 0.00 | 01-MAY-00:10 | 397.10 | 370.63 | 56.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.92 |
| June | 0.00 | 01-JUN-00:10 | 397.10 | 370.63 | 56.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.75 |
| July | 0.00 | 01-JUL-00:10 | 397.10 | 370.63 | 56.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.25 |
| August | 0.00 | 01-AUG-00:10 | 397.10 | 370.63 | 56.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.88 |
| September | 0.00 | 01-SEP-00:10 | 397.10 | 370.63 | 56.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.98 |
| October | 0.00 | 01-OCT-00:10 | 397.10 | 370.63 | 56.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.34 |
| November | 0.00 | 01-NOV-00:10 | 397.10 | 370.63 | 56.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.59 |
| December | 0.00 | 01-DEC-00:10 | 397.10 | 370.63 | 56.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 0.00 | 397.10 | 370.63 | 56.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 397.10 | 370.63 | 56.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.48 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: M CORRIDOR
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 0.00 | 01-JAN-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.07 |
| February | 0.00 | 01-FEB-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.62 |
| March | 0.00 | 01-MAR-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.99 |
| April | 0.00 | 01-APR-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.78 |
| May | 0.00 | 01-MAY-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.14 |
| June | 0.00 | 01-JUN-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.69 |
| July | 0.00 | 01-JUL-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.22 |
| August | 0.00 | 01-AUG-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.50 |
| September | 0.00 | 01-SEP-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.75 |
| October | 0.00 | 01-OCT-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.63 |
| November | 0.00 | 01-NOV-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.11 |
| December | 0.00 | 01-DEC-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
| Minimum of Months | 0.00 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.78 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
| January | 0.115341E+12 | 77824.06 | 13-JAN-08:00 | 0.238813E+12 | 151176.37 | 12-JAN-03:00 |
| February | 0.102217E+12 | 78197.24 | 25-FEB-07:49 | 0.185802E+12 | 140201.11 | 27-FEB-08:09 |
| March | 0.110284E+12 | 77765.80 | 03-MAR-07:49 | 0.150055E+12 | 120315.73 | 02-MAR-04:00 |
| April | 0.103870E+12 | 70281.56 | 19-APR-17:30 | 0.559805E+11 | 92623.17 | 03-APR-07:10 |
| May | 0.109366E+12 | 74293.68 | 31-MAY-17:30 | 0.398120E+10 | 24704.30 | 28-MAY-02:00 |
| June | 0.113986E+12 | 82869.64 | 21-JUN-17:19 | 11163676.21 | 1333.65 | 25-JUN-05:49 |
| July | 0.119529E+12 | 81444.59 | 21-JUL-17:10 | 582545.84 | 161.94 | 06-JUL-04:00 |
| August | 0.111995E+12 | 78904.63 | 10-AUG-16:10 | 0.765988E+09 | 11876.52 | 31-AUG-04:00 |
| September | 0.994485E+11 | 64853.27 | 09-SEP-16:30 | 0.180220E+11 | 44812.78 | 30-SEP-04:00 |
| October | 0.106047E+12 | 68088.37 | 19-OCT-17:00 | 0.104053E+12 | 97289.51 | 31-OCT-07:10 |
| November | 0.108435E+12 | 72478.18 | 20-NOV-18:00 | 0.209413E+12 | 128541.05 | 29-NOV-08:09 |
| December | 0.115579E+12 | 74070.23 | 14-DEC-07:49 | 0.250148E+12 | 141160.82 | 15-DEC-09:09 |
| Annual Sum or Average | 0.131610E+13 | 0.121705E+13 | ||||
| Minimum of Months | 0.994485E+11 | 64853.27 | 582545.84 | 161.94 | ||
| Maximum of Months | 0.119529E+12 | 82869.64 | 0.250148E+12 | 151176.37 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| INTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [J] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
| January | 0.840929E+10 | 0.684925E+10 | 0.389380E+11 | 0.00 | 0.120112E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.491328E+11 | 0.00 |
| February | 0.760941E+10 | 0.512452E+10 | 0.351823E+11 | 0.00 | 0.991223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.443889E+11 | 0.00 |
| March | 0.845392E+10 | 0.447131E+10 | 0.389781E+11 | 0.00 | 0.925265E+10 | 0.00 | 0.00 | 907440.16 | 0.00 | 0.00 | 0.00 | 0.491268E+11 | 0.00 |
| April | 0.814762E+10 | 0.314768E+10 | 0.376905E+11 | 0.00 | 0.645958E+10 | 0.00 | 0.00 | 0.922939E+09 | 0.00 | 0.00 | 0.00 | 0.475018E+11 | 0.00 |
| May | 0.843904E+10 | 0.205707E+10 | 0.389647E+11 | 0.00 | 0.621678E+10 | 0.00 | 0.00 | 0.504008E+10 | 0.00 | 0.00 | 0.00 | 0.486484E+11 | 0.00 |
| June | 0.817737E+10 | 0.114600E+10 | 0.377173E+11 | 0.00 | 0.832320E+10 | 0.00 | 0.00 | 0.130561E+11 | 0.00 | 0.00 | 0.00 | 0.455663E+11 | 0.00 |
| July | 0.840929E+10 | 0.159294E+10 | 0.389380E+11 | 0.00 | 0.922072E+10 | 0.00 | 0.00 | 0.157006E+11 | 0.00 | 0.00 | 0.00 | 0.456673E+11 | 0.00 |
| August | 0.845392E+10 | 0.274849E+10 | 0.389781E+11 | 0.00 | 0.741544E+10 | 0.00 | 0.00 | 0.960056E+10 | 0.00 | 0.00 | 0.00 | 0.447988E+11 | 0.00 |
| September | 0.814762E+10 | 0.382191E+10 | 0.376905E+11 | 0.00 | 0.529995E+10 | 0.00 | 0.00 | 0.106367E+10 | 0.00 | 0.00 | 0.00 | 0.434248E+11 | 0.00 |
| October | 0.842417E+10 | 0.515508E+10 | 0.389514E+11 | 0.00 | 0.785320E+10 | 0.00 | 0.00 | 4906239.72 | 0.00 | 0.00 | 0.00 | 0.456581E+11 | 0.00 |
| November | 0.814762E+10 | 0.618266E+10 | 0.376905E+11 | 0.00 | 0.109688E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.454452E+11 | 0.00 |
| December | 0.840929E+10 | 0.733439E+10 | 0.389380E+11 | 0.00 | 0.123763E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.485211E+11 | 0.00 |
| Annual Sum or Average | 0.992286E+11 | 0.496313E+11 | 0.458657E+12 | 0.00 | 0.105310E+12 | 0.00 | 0.00 | 0.453898E+11 | 0.00 | 0.00 | 0.00 | 0.557880E+12 | 0.00 |
| Minimum of Months | 0.760941E+10 | 0.114600E+10 | 0.351823E+11 | 0.00 | 0.529995E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.434248E+11 | 0.00 |
| Maximum of Months | 0.845392E+10 | 0.733439E+10 | 0.389781E+11 | 0.00 | 0.123763E+11 | 0.00 | 0.00 | 0.157006E+11 | 0.00 | 0.00 | 0.00 | 0.491328E+11 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| INTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
| January | 0.00 | 0.00 | 0.238813E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.185802E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.150055E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.559805E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.398120E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 11163676.21 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 582545.84 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.765988E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.180220E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.104053E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.209413E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.250148E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.121705E+13 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 582545.84 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.250148E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| INTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
| January | 5904.43 | 01-JAN-19:10 | 3183.33 | 01-JAN-00:10 | 22709.69 | 03-JAN-17:10 | 0.00 | 6460.73 | 12-JAN-03:00 | 0.00 | 0.00 | 01-JAN-00:10 |
| February | 5904.43 | 01-FEB-19:10 | 3183.33 | 01-FEB-00:10 | 22709.69 | 01-FEB-17:10 | 0.00 | 5922.75 | 27-FEB-07:00 | 0.00 | 0.00 | 01-FEB-00:10 |
| March | 5904.43 | 01-MAR-19:10 | 3183.33 | 01-MAR-00:10 | 22709.69 | 01-MAR-17:10 | 0.00 | 5493.94 | 02-MAR-04:00 | 0.00 | 0.00 | 01-MAR-00:10 |
| April | 5904.43 | 01-APR-18:10 | 3183.33 | 01-APR-00:10 | 22709.69 | 03-APR-16:10 | 0.00 | 4599.79 | 03-APR-02:00 | 0.00 | 0.00 | 01-APR-00:10 |
| May | 5904.43 | 01-MAY-18:10 | 3183.33 | 01-MAY-00:10 | 22709.69 | 01-MAY-16:10 | 0.00 | 5319.12 | 31-MAY-16:10 | 0.00 | 0.00 | 01-MAY-00:10 |
| June | 5904.43 | 01-JUN-18:10 | 3183.33 | 01-JUN-00:10 | 22709.69 | 01-JUN-16:10 | 0.00 | 6587.13 | 30-JUN-14:30 | 0.00 | 0.00 | 01-JUN-00:10 |
| July | 5904.43 | 01-JUL-18:10 | 3183.33 | 01-JUL-00:10 | 22709.69 | 03-JUL-16:10 | 0.00 | 7344.40 | 29-JUL-16:10 | 0.00 | 0.00 | 01-JUL-00:10 |
| August | 5904.43 | 01-AUG-18:10 | 3183.33 | 01-AUG-00:10 | 22709.69 | 01-AUG-16:10 | 0.00 | 6590.58 | 11-AUG-16:10 | 0.00 | 0.00 | 01-AUG-00:10 |
| September | 5904.43 | 01-SEP-18:10 | 3183.33 | 01-SEP-00:10 | 22709.69 | 01-SEP-16:10 | 0.00 | 3486.28 | 09-SEP-15:30 | 0.00 | 0.00 | 01-SEP-00:10 |
| October | 5904.43 | 01-OCT-18:10 | 3183.33 | 01-OCT-00:10 | 22709.69 | 02-OCT-16:10 | 0.00 | 4719.72 | 27-OCT-03:00 | 0.00 | 0.00 | 01-OCT-00:10 |
| November | 5904.43 | 01-NOV-18:10 | 3183.33 | 01-NOV-00:10 | 22709.69 | 01-NOV-16:10 | 0.00 | 5626.05 | 29-NOV-07:00 | 0.00 | 0.00 | 01-NOV-00:10 |
| December | 5904.43 | 01-DEC-19:10 | 3183.33 | 01-DEC-00:10 | 22709.69 | 01-DEC-17:10 | 0.00 | 6007.11 | 15-DEC-11:00 | 0.00 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 5904.43 | 3183.33 | 22709.69 | 0.00 | 3486.28 | 0.00 | 0.00 | |||||
| Maximum of Months | 5904.43 | 3183.33 | 22709.69 | 0.00 | 7344.40 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| COOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY {Maximum} [W] | HEATRECOVERY:ELECTRICITY {TIMESTAMP} | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
| January | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 49965.29 | 26-JAN-07:49 | 0.00 |
| February | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 49970.39 | 13-FEB-07:49 | 0.00 |
| March | 172.64 | 22-MAR-15:09 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 50200.01 | 09-MAR-07:49 | 0.00 |
| April | 5859.99 | 22-APR-16:10 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 45899.89 | 20-APR-06:49 | 0.00 |
| May | 11661.86 | 31-MAY-15:00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 37883.37 | 30-MAY-06:30 | 0.00 |
| June | 17457.47 | 30-JUN-14:30 | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 38758.46 | 13-JUN-06:10 | 0.00 |
| July | 19724.99 | 29-JUL-16:10 | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 37023.82 | 07-JUL-06:30 | 0.00 |
| August | 16475.88 | 11-AUG-15:00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 36428.18 | 07-AUG-06:00 | 0.00 |
| September | 5765.86 | 09-SEP-15:30 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 35336.10 | 07-SEP-06:40 | 0.00 |
| October | 605.17 | 03-OCT-14:30 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 37464.90 | 29-OCT-06:00 | 0.00 |
| November | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 43011.25 | 19-NOV-07:19 | 0.00 |
| December | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 46175.02 | 14-DEC-07:49 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 35336.10 | 0.00 | |||
| Maximum of Months | 19724.99 | 0.00 | 0.00 | 0.00 | 50200.01 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
| January | 77824.06 | 13-JAN-08:00 | 2872.71 | 16799.92 | 3183.33 | 0.00 | 5710.61 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 78197.24 | 25-FEB-07:49 | 3348.00 | 16223.07 | 3183.33 | 0.00 | 5496.25 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 77765.80 | 03-MAR-07:49 | 3348.00 | 16323.13 | 3183.33 | 0.00 | 4970.66 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 70281.56 | 19-APR-17:30 | 5231.74 | 22609.62 | 0.00 | 0.00 | 2494.21 | 0.00 | 0.00 | 2492.68 | 0.00 |
| May | 74293.68 | 31-MAY-17:30 | 5231.74 | 22609.62 | 0.00 | 0.00 | 4972.99 | 0.00 | 0.00 | 10493.68 | 0.00 |
| June | 82869.64 | 21-JUN-17:19 | 5231.74 | 22609.62 | 0.00 | 0.00 | 6344.29 | 0.00 | 0.00 | 15367.63 | 0.00 |
| July | 81444.59 | 21-JUL-17:10 | 5231.74 | 22609.62 | 0.00 | 0.00 | 6472.42 | 0.00 | 0.00 | 15891.66 | 0.00 |
| August | 78904.63 | 10-AUG-16:10 | 4289.87 | 22709.69 | 0.00 | 0.00 | 6239.45 | 0.00 | 0.00 | 14624.65 | 0.00 |
| September | 64853.27 | 09-SEP-16:30 | 4289.87 | 22609.62 | 0.00 | 0.00 | 3094.83 | 0.00 | 0.00 | 4501.81 | 0.00 |
| October | 68088.37 | 19-OCT-17:00 | 5231.74 | 22609.62 | 3183.33 | 0.00 | 2763.77 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 72478.18 | 20-NOV-18:00 | 5231.74 | 22609.62 | 3183.33 | 0.00 | 3810.62 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 74070.23 | 14-DEC-07:49 | 3348.00 | 16323.13 | 3183.33 | 0.00 | 5040.75 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
| Minimum of Months | 64853.27 | 2872.71 | 16223.07 | 0.00 | 0.00 | 2494.21 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 82869.64 | 5231.74 | 22709.69 | 3183.33 | 0.00 | 6472.42 | 0.00 | 0.00 | 15891.66 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| INTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | |
| January | 0.00 | 0.00 | 151176.37 | 12-JAN-03:00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 140201.11 | 27-FEB-08:09 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 120315.73 | 02-MAR-04:00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 92623.17 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 24704.30 | 28-MAY-02:00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 1333.65 | 25-JUN-05:49 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 161.94 | 06-JUL-04:00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 11876.52 | 31-AUG-04:00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 44812.78 | 30-SEP-04:00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 97289.51 | 31-OCT-07:10 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 128541.05 | 29-NOV-08:09 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 141160.82 | 15-DEC-09:09 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 161.94 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 151176.37 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: G SW APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: G NW APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: OFFICE
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: G NE APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: G N1 APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: G N2 APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: G S1 APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: G S2 APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: M SW APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: M NW APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: M SE APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: M NE APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: M N1 APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: M N2 APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: M S1 APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: M S2 APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: T SW APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: T NW APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: T SE APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: T NE APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: T N1 APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: T N2 APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: T S1 APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: T S2 APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: T CORRIDOR
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: G CORRIDOR
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: M CORRIDOR
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: G SW APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 533.00 | 21.10 | 533.00 | 21.10 | 533.00 | 21.10 |
| February | 473.00 | 21.10 | 473.00 | 21.10 | 473.00 | 21.10 |
| March | 506.00 | 21.10 | 506.00 | 21.10 | 506.00 | 21.10 |
| April | 510.00 | 21.33 | 319.33 | 21.24 | 319.33 | 21.20 |
| May | 513.17 | 22.26 | 44.50 | 22.17 | 44.50 | 22.09 |
| June | 235.83 | 23.46 | 11.33 | 23.48 | 0.00 | 23.48 |
| July | 78.33 | 23.44 | 138.00 | 23.80 | 0.00 | 23.80 |
| August | 160.83 | 23.32 | 70.83 | 23.53 | 0.00 | 23.53 |
| September | 501.00 | 22.22 | 78.83 | 22.07 | 78.83 | 21.96 |
| October | 524.00 | 21.11 | 405.33 | 21.11 | 405.33 | 21.10 |
| November | 510.00 | 21.10 | 510.00 | 21.10 | 510.00 | 21.10 |
| December | 533.00 | 21.10 | 533.00 | 21.10 | 533.00 | 21.10 |
| Annual Sum or Average | 5078.17 | 21.57 | 3623.17 | 21.45 | 3403.00 | 21.35 |
| Minimum of Months | 78.33 | 21.10 | 11.33 | 21.10 | 0.00 | 21.10 |
| Maximum of Months | 533.00 | 23.46 | 533.00 | 23.80 | 533.00 | 23.80 |
Report: ComfortReportSimple55Monthly
For: G NW APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 744.00 | 21.10 | 744.00 | 21.10 | 744.00 | 21.10 |
| February | 672.00 | 21.10 | 672.00 | 21.10 | 672.00 | 21.10 |
| March | 744.00 | 21.10 | 744.00 | 21.10 | 744.00 | 21.10 |
| April | 720.00 | 21.11 | 697.67 | 21.11 | 697.67 | 21.11 |
| May | 744.00 | 21.55 | 174.33 | 21.46 | 174.33 | 21.40 |
| June | 491.00 | 23.41 | 6.50 | 23.42 | 0.00 | 23.42 |
| July | 149.83 | 23.40 | 55.83 | 23.56 | 0.00 | 23.56 |
| August | 441.50 | 23.22 | 14.67 | 23.24 | 0.00 | 23.24 |
| September | 720.00 | 21.36 | 183.50 | 21.31 | 183.50 | 21.27 |
| October | 744.00 | 21.10 | 717.67 | 21.10 | 717.67 | 21.10 |
| November | 720.00 | 21.10 | 720.00 | 21.10 | 720.00 | 21.10 |
| December | 744.00 | 21.10 | 744.00 | 21.10 | 744.00 | 21.10 |
| Annual Sum or Average | 7634.33 | 21.49 | 5474.17 | 21.34 | 5397.17 | 21.27 |
| Minimum of Months | 149.83 | 21.10 | 6.50 | 21.10 | 0.00 | 21.10 |
| Maximum of Months | 744.00 | 23.41 | 744.00 | 23.56 | 744.00 | 23.56 |
Report: ComfortReportSimple55Monthly
For: OFFICE
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 140.00 | 20.94 | 140.00 | 20.94 | 140.00 | 20.94 |
| February | 133.00 | 20.94 | 133.00 | 20.94 | 133.00 | 20.94 |
| March | 161.00 | 20.94 | 161.00 | 20.94 | 161.00 | 20.94 |
| April | 140.00 | 21.49 | 93.17 | 21.26 | 93.17 | 21.16 |
| May | 112.33 | 23.62 | 0.67 | 23.60 | 0.67 | 23.58 |
| June | 5.83 | 24.06 | 106.67 | 24.25 | 0.00 | 24.25 |
| July | 1.17 | 24.03 | 130.50 | 24.22 | 0.00 | 24.22 |
| August | 8.17 | 23.87 | 123.17 | 24.21 | 0.00 | 24.21 |
| September | 112.83 | 22.75 | 29.50 | 22.38 | 28.83 | 22.13 |
| October | 147.00 | 21.15 | 118.83 | 21.05 | 118.83 | 21.01 |
| November | 140.00 | 20.94 | 140.00 | 20.94 | 140.00 | 20.94 |
| December | 140.00 | 20.94 | 140.00 | 20.94 | 140.00 | 20.94 |
| Annual Sum or Average | 1241.33 | 21.47 | 1316.50 | 21.66 | 955.50 | 21.46 |
| Minimum of Months | 1.17 | 20.94 | 0.67 | 20.94 | 0.00 | 20.94 |
| Maximum of Months | 161.00 | 24.06 | 161.00 | 24.25 | 161.00 | 24.25 |
Report: ComfortReportSimple55Monthly
For: G NE APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 744.00 | 21.10 | 744.00 | 21.10 | 744.00 | 21.10 |
| February | 672.00 | 21.10 | 672.00 | 21.10 | 672.00 | 21.10 |
| March | 744.00 | 21.10 | 744.00 | 21.10 | 744.00 | 21.10 |
| April | 720.00 | 21.10 | 712.17 | 21.10 | 712.17 | 21.10 |
| May | 744.00 | 21.85 | 108.50 | 21.75 | 108.50 | 21.68 |
| June | 432.83 | 23.53 | 9.17 | 23.54 | 0.00 | 23.54 |
| July | 112.50 | 23.37 | 159.33 | 23.74 | 0.00 | 23.74 |
| August | 352.67 | 23.22 | 18.83 | 23.26 | 0.00 | 23.26 |
| September | 720.00 | 21.45 | 164.67 | 21.39 | 164.67 | 21.34 |
| October | 744.00 | 21.10 | 705.67 | 21.10 | 705.67 | 21.10 |
| November | 720.00 | 21.10 | 720.00 | 21.10 | 720.00 | 21.10 |
| December | 744.00 | 21.10 | 744.00 | 21.10 | 744.00 | 21.10 |
| Annual Sum or Average | 7450.00 | 21.49 | 5502.33 | 21.36 | 5315.00 | 21.29 |
| Minimum of Months | 112.50 | 21.10 | 9.17 | 21.10 | 0.00 | 21.10 |
| Maximum of Months | 744.00 | 23.53 | 744.00 | 23.74 | 744.00 | 23.74 |
Report: ComfortReportSimple55Monthly
For: G N1 APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 744.00 | 21.10 | 744.00 | 21.10 | 744.00 | 21.10 |
| February | 672.00 | 21.10 | 672.00 | 21.10 | 672.00 | 21.10 |
| March | 744.00 | 21.10 | 744.00 | 21.10 | 744.00 | 21.10 |
| April | 720.00 | 21.10 | 717.17 | 21.10 | 717.17 | 21.10 |
| May | 744.00 | 21.66 | 97.33 | 21.59 | 97.33 | 21.54 |
| June | 453.50 | 23.59 | 4.17 | 23.59 | 0.00 | 23.59 |
| July | 98.17 | 23.63 | 55.50 | 23.76 | 0.00 | 23.76 |
| August | 386.67 | 23.42 | 14.00 | 23.44 | 0.00 | 23.44 |
| September | 720.00 | 21.48 | 143.33 | 21.42 | 143.33 | 21.37 |
| October | 744.00 | 21.10 | 639.67 | 21.10 | 639.67 | 21.10 |
| November | 720.00 | 21.10 | 720.00 | 21.10 | 720.00 | 21.10 |
| December | 744.00 | 21.10 | 744.00 | 21.10 | 744.00 | 21.10 |
| Annual Sum or Average | 7490.33 | 21.50 | 5295.17 | 21.35 | 5221.50 | 21.28 |
| Minimum of Months | 98.17 | 21.10 | 4.17 | 21.10 | 0.00 | 21.10 |
| Maximum of Months | 744.00 | 23.63 | 744.00 | 23.76 | 744.00 | 23.76 |
Report: ComfortReportSimple55Monthly
For: G N2 APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 744.00 | 21.10 | 744.00 | 21.10 | 744.00 | 21.10 |
| February | 672.00 | 21.10 | 672.00 | 21.10 | 672.00 | 21.10 |
| March | 744.00 | 21.10 | 744.00 | 21.10 | 744.00 | 21.10 |
| April | 720.00 | 21.10 | 717.83 | 21.10 | 717.83 | 21.10 |
| May | 744.00 | 21.70 | 86.83 | 21.64 | 86.83 | 21.59 |
| June | 447.00 | 23.60 | 4.17 | 23.61 | 0.00 | 23.61 |
| July | 93.83 | 23.63 | 60.17 | 23.77 | 0.00 | 23.77 |
| August | 376.83 | 23.43 | 14.33 | 23.45 | 0.00 | 23.45 |
| September | 720.00 | 21.50 | 143.33 | 21.43 | 143.33 | 21.39 |
| October | 744.00 | 21.10 | 637.33 | 21.10 | 637.33 | 21.10 |
| November | 720.00 | 21.10 | 720.00 | 21.10 | 720.00 | 21.10 |
| December | 744.00 | 21.10 | 744.00 | 21.10 | 744.00 | 21.10 |
| Annual Sum or Average | 7469.67 | 21.50 | 5288.00 | 21.35 | 5209.33 | 21.28 |
| Minimum of Months | 93.83 | 21.10 | 4.17 | 21.10 | 0.00 | 21.10 |
| Maximum of Months | 744.00 | 23.63 | 744.00 | 23.77 | 744.00 | 23.77 |
Report: ComfortReportSimple55Monthly
For: G S1 APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 533.00 | 21.10 | 533.00 | 21.10 | 533.00 | 21.10 |
| February | 473.00 | 21.10 | 473.00 | 21.10 | 473.00 | 21.10 |
| March | 506.00 | 21.10 | 506.00 | 21.10 | 506.00 | 21.10 |
| April | 510.00 | 21.38 | 274.83 | 21.28 | 274.83 | 21.23 |
| May | 510.50 | 22.59 | 5.83 | 22.58 | 5.83 | 22.56 |
| June | 175.33 | 23.67 | 5.50 | 23.68 | 0.00 | 23.68 |
| July | 24.17 | 23.54 | 152.50 | 23.94 | 0.00 | 23.94 |
| August | 88.67 | 23.44 | 49.67 | 23.64 | 0.00 | 23.64 |
| September | 490.67 | 22.57 | 17.83 | 22.52 | 17.83 | 22.47 |
| October | 524.00 | 21.14 | 334.83 | 21.13 | 334.83 | 21.12 |
| November | 510.00 | 21.10 | 510.00 | 21.10 | 510.00 | 21.10 |
| December | 533.00 | 21.10 | 533.00 | 21.10 | 533.00 | 21.10 |
| Annual Sum or Average | 4878.33 | 21.58 | 3396.00 | 21.46 | 3188.33 | 21.36 |
| Minimum of Months | 24.17 | 21.10 | 5.50 | 21.10 | 0.00 | 21.10 |
| Maximum of Months | 533.00 | 23.67 | 533.00 | 23.94 | 533.00 | 23.94 |
Report: ComfortReportSimple55Monthly
For: G S2 APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 533.00 | 21.10 | 533.00 | 21.10 | 533.00 | 21.10 |
| February | 473.00 | 21.10 | 473.00 | 21.10 | 473.00 | 21.10 |
| March | 506.00 | 21.10 | 506.00 | 21.10 | 506.00 | 21.10 |
| April | 510.00 | 21.36 | 292.17 | 21.26 | 292.17 | 21.22 |
| May | 507.83 | 22.66 | 5.50 | 22.64 | 5.50 | 22.63 |
| June | 123.83 | 23.64 | 5.67 | 23.65 | 0.00 | 23.65 |
| July | 22.67 | 23.58 | 181.17 | 23.95 | 0.00 | 23.95 |
| August | 77.83 | 23.45 | 78.83 | 23.73 | 0.00 | 23.73 |
| September | 483.83 | 22.61 | 23.83 | 22.54 | 23.83 | 22.48 |
| October | 524.00 | 21.14 | 362.33 | 21.12 | 362.33 | 21.11 |
| November | 510.00 | 21.10 | 510.00 | 21.10 | 510.00 | 21.10 |
| December | 533.00 | 21.10 | 533.00 | 21.10 | 533.00 | 21.10 |
| Annual Sum or Average | 4805.00 | 21.56 | 3504.50 | 21.46 | 3238.83 | 21.36 |
| Minimum of Months | 22.67 | 21.10 | 5.50 | 21.10 | 0.00 | 21.10 |
| Maximum of Months | 533.00 | 23.64 | 533.00 | 23.95 | 533.00 | 23.95 |
Report: ComfortReportSimple55Monthly
For: M SW APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 533.00 | 21.10 | 533.00 | 21.10 | 533.00 | 21.10 |
| February | 473.00 | 21.10 | 473.00 | 21.10 | 473.00 | 21.10 |
| March | 506.00 | 21.12 | 446.17 | 21.11 | 446.17 | 21.11 |
| April | 489.67 | 22.04 | 113.67 | 21.86 | 113.67 | 21.74 |
| May | 381.00 | 23.33 | 0.00 | 23.33 | 0.00 | 23.33 |
| June | 41.17 | 23.62 | 55.33 | 23.84 | 0.00 | 23.84 |
| July | 17.00 | 23.65 | 232.00 | 23.98 | 0.00 | 23.98 |
| August | 96.17 | 23.38 | 88.33 | 23.68 | 0.00 | 23.68 |
| September | 463.67 | 22.56 | 21.33 | 22.49 | 21.33 | 22.43 |
| October | 524.00 | 21.17 | 336.83 | 21.14 | 336.83 | 21.13 |
| November | 510.00 | 21.10 | 510.00 | 21.10 | 510.00 | 21.10 |
| December | 533.00 | 21.10 | 533.00 | 21.10 | 533.00 | 21.10 |
| Annual Sum or Average | 4567.67 | 21.63 | 3342.67 | 21.54 | 2967.00 | 21.42 |
| Minimum of Months | 17.00 | 21.10 | 0.00 | 21.10 | 0.00 | 21.10 |
| Maximum of Months | 533.00 | 23.65 | 533.00 | 23.98 | 533.00 | 23.98 |
Report: ComfortReportSimple55Monthly
For: M NW APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 744.00 | 21.10 | 744.00 | 21.10 | 744.00 | 21.10 |
| February | 672.00 | 21.10 | 672.00 | 21.10 | 672.00 | 21.10 |
| March | 744.00 | 21.10 | 736.00 | 21.10 | 736.00 | 21.10 |
| April | 720.00 | 21.44 | 356.83 | 21.33 | 356.83 | 21.27 |
| May | 698.33 | 23.27 | 0.00 | 23.27 | 0.00 | 23.27 |
| June | 69.67 | 23.75 | 68.33 | 23.88 | 0.00 | 23.88 |
| July | 21.17 | 23.70 | 204.33 | 23.97 | 0.00 | 23.97 |
| August | 204.17 | 23.24 | 28.33 | 23.33 | 0.00 | 23.33 |
| September | 720.00 | 21.86 | 125.50 | 21.75 | 125.50 | 21.66 |
| October | 744.00 | 21.10 | 588.33 | 21.10 | 588.33 | 21.10 |
| November | 720.00 | 21.10 | 720.00 | 21.10 | 720.00 | 21.10 |
| December | 744.00 | 21.10 | 744.00 | 21.10 | 744.00 | 21.10 |
| Annual Sum or Average | 6801.33 | 21.54 | 4987.67 | 21.43 | 4686.67 | 21.33 |
| Minimum of Months | 21.17 | 21.10 | 0.00 | 21.10 | 0.00 | 21.10 |
| Maximum of Months | 744.00 | 23.75 | 744.00 | 23.97 | 744.00 | 23.97 |
Report: ComfortReportSimple55Monthly
For: M SE APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 533.00 | 21.10 | 533.00 | 21.10 | 533.00 | 21.10 |
| February | 473.00 | 21.10 | 473.00 | 21.10 | 473.00 | 21.10 |
| March | 506.00 | 21.12 | 433.83 | 21.11 | 433.83 | 21.11 |
| April | 493.17 | 22.00 | 117.33 | 21.83 | 117.33 | 21.71 |
| May | 379.00 | 23.42 | 0.00 | 23.42 | 0.00 | 23.42 |
| June | 30.83 | 23.58 | 48.83 | 23.84 | 0.00 | 23.84 |
| July | 15.17 | 23.68 | 239.17 | 23.98 | 0.00 | 23.98 |
| August | 87.33 | 23.40 | 87.00 | 23.70 | 0.00 | 23.70 |
| September | 442.67 | 22.56 | 17.50 | 22.50 | 17.50 | 22.45 |
| October | 524.00 | 21.20 | 325.50 | 21.16 | 325.50 | 21.14 |
| November | 510.00 | 21.10 | 510.00 | 21.10 | 510.00 | 21.10 |
| December | 533.00 | 21.10 | 533.00 | 21.10 | 533.00 | 21.10 |
| Annual Sum or Average | 4527.17 | 21.62 | 3318.17 | 21.54 | 2943.17 | 21.42 |
| Minimum of Months | 15.17 | 21.10 | 0.00 | 21.10 | 0.00 | 21.10 |
| Maximum of Months | 533.00 | 23.68 | 533.00 | 23.98 | 533.00 | 23.98 |
Report: ComfortReportSimple55Monthly
For: M NE APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 744.00 | 21.10 | 744.00 | 21.10 | 744.00 | 21.10 |
| February | 672.00 | 21.10 | 672.00 | 21.10 | 672.00 | 21.10 |
| March | 744.00 | 21.10 | 724.50 | 21.10 | 724.50 | 21.10 |
| April | 720.00 | 21.44 | 349.50 | 21.33 | 349.50 | 21.27 |
| May | 648.00 | 23.40 | 0.00 | 23.40 | 0.00 | 23.40 |
| June | 45.00 | 23.65 | 65.17 | 23.86 | 0.00 | 23.86 |
| July | 19.33 | 23.67 | 279.67 | 23.98 | 0.00 | 23.98 |
| August | 188.17 | 23.37 | 42.00 | 23.49 | 0.00 | 23.49 |
| September | 720.00 | 22.06 | 125.00 | 21.92 | 125.00 | 21.81 |
| October | 744.00 | 21.11 | 566.17 | 21.10 | 566.17 | 21.10 |
| November | 720.00 | 21.10 | 720.00 | 21.10 | 720.00 | 21.10 |
| December | 744.00 | 21.10 | 744.00 | 21.10 | 744.00 | 21.10 |
| Annual Sum or Average | 6708.50 | 21.55 | 5032.00 | 21.45 | 4645.17 | 21.35 |
| Minimum of Months | 19.33 | 21.10 | 0.00 | 21.10 | 0.00 | 21.10 |
| Maximum of Months | 744.00 | 23.67 | 744.00 | 23.98 | 744.00 | 23.98 |
Report: ComfortReportSimple55Monthly
For: M N1 APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 744.00 | 21.10 | 744.00 | 21.10 | 744.00 | 21.10 |
| February | 672.00 | 21.10 | 672.00 | 21.10 | 672.00 | 21.10 |
| March | 744.00 | 21.10 | 697.33 | 21.10 | 697.33 | 21.10 |
| April | 720.00 | 21.38 | 341.00 | 21.29 | 341.00 | 21.24 |
| May | 736.50 | 23.48 | 0.00 | 23.48 | 0.00 | 23.48 |
| June | 72.83 | 23.93 | 26.50 | 23.95 | 0.00 | 23.95 |
| July | 5.00 | 23.82 | 136.50 | 23.99 | 0.00 | 23.99 |
| August | 171.83 | 23.45 | 16.83 | 23.50 | 0.00 | 23.50 |
| September | 720.00 | 22.20 | 49.50 | 22.13 | 49.50 | 22.06 |
| October | 744.00 | 21.12 | 491.00 | 21.11 | 491.00 | 21.11 |
| November | 720.00 | 21.10 | 720.00 | 21.10 | 720.00 | 21.10 |
| December | 744.00 | 21.10 | 744.00 | 21.10 | 744.00 | 21.10 |
| Annual Sum or Average | 6794.17 | 21.60 | 4638.67 | 21.44 | 4458.83 | 21.35 |
| Minimum of Months | 5.00 | 21.10 | 0.00 | 21.10 | 0.00 | 21.10 |
| Maximum of Months | 744.00 | 23.93 | 744.00 | 23.99 | 744.00 | 23.99 |
Report: ComfortReportSimple55Monthly
For: M N2 APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 744.00 | 21.10 | 744.00 | 21.10 | 744.00 | 21.10 |
| February | 672.00 | 21.10 | 672.00 | 21.10 | 672.00 | 21.10 |
| March | 744.00 | 21.10 | 695.83 | 21.10 | 695.83 | 21.10 |
| April | 720.00 | 21.38 | 340.83 | 21.29 | 340.83 | 21.24 |
| May | 736.00 | 23.51 | 0.00 | 23.51 | 0.00 | 23.51 |
| June | 71.33 | 23.93 | 26.50 | 23.95 | 0.00 | 23.95 |
| July | 5.17 | 23.82 | 139.50 | 23.99 | 0.00 | 23.99 |
| August | 170.83 | 23.46 | 16.83 | 23.51 | 0.00 | 23.51 |
| September | 720.00 | 22.23 | 49.00 | 22.16 | 49.00 | 22.10 |
| October | 744.00 | 21.12 | 488.67 | 21.11 | 488.67 | 21.11 |
| November | 720.00 | 21.10 | 720.00 | 21.10 | 720.00 | 21.10 |
| December | 744.00 | 21.10 | 744.00 | 21.10 | 744.00 | 21.10 |
| Annual Sum or Average | 6791.33 | 21.60 | 4637.17 | 21.45 | 4454.33 | 21.35 |
| Minimum of Months | 5.17 | 21.10 | 0.00 | 21.10 | 0.00 | 21.10 |
| Maximum of Months | 744.00 | 23.93 | 744.00 | 23.99 | 744.00 | 23.99 |
Report: ComfortReportSimple55Monthly
For: M S1 APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 533.00 | 21.10 | 533.00 | 21.10 | 533.00 | 21.10 |
| February | 473.00 | 21.10 | 463.50 | 21.10 | 463.50 | 21.10 |
| March | 506.00 | 21.15 | 372.67 | 21.13 | 372.67 | 21.12 |
| April | 497.33 | 22.25 | 72.00 | 22.11 | 72.00 | 21.99 |
| May | 412.83 | 23.63 | 0.00 | 23.63 | 0.00 | 23.63 |
| June | 17.17 | 23.83 | 26.83 | 23.93 | 0.00 | 23.93 |
| July | 3.83 | 23.74 | 174.17 | 23.99 | 0.00 | 23.99 |
| August | 61.33 | 23.55 | 53.83 | 23.76 | 0.00 | 23.76 |
| September | 422.17 | 22.81 | 1.83 | 22.81 | 1.83 | 22.80 |
| October | 524.00 | 21.31 | 237.67 | 21.25 | 237.67 | 21.21 |
| November | 510.00 | 21.10 | 510.00 | 21.10 | 510.00 | 21.10 |
| December | 533.00 | 21.10 | 533.00 | 21.10 | 533.00 | 21.10 |
| Annual Sum or Average | 4493.67 | 21.70 | 2978.50 | 21.56 | 2723.67 | 21.44 |
| Minimum of Months | 3.83 | 21.10 | 0.00 | 21.10 | 0.00 | 21.10 |
| Maximum of Months | 533.00 | 23.83 | 533.00 | 23.99 | 533.00 | 23.99 |
Report: ComfortReportSimple55Monthly
For: M S2 APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 533.00 | 21.10 | 533.00 | 21.10 | 533.00 | 21.10 |
| February | 473.00 | 21.10 | 463.50 | 21.10 | 463.50 | 21.10 |
| March | 506.00 | 21.15 | 370.83 | 21.13 | 370.83 | 21.12 |
| April | 497.17 | 22.25 | 72.50 | 22.10 | 72.50 | 21.99 |
| May | 410.67 | 23.64 | 0.00 | 23.64 | 0.00 | 23.64 |
| June | 16.50 | 23.83 | 26.83 | 23.93 | 0.00 | 23.93 |
| July | 3.67 | 23.74 | 176.17 | 23.99 | 0.00 | 23.99 |
| August | 61.17 | 23.56 | 53.50 | 23.76 | 0.00 | 23.76 |
| September | 419.67 | 22.82 | 1.67 | 22.81 | 1.67 | 22.80 |
| October | 524.00 | 21.32 | 237.33 | 21.25 | 237.33 | 21.21 |
| November | 510.00 | 21.10 | 510.00 | 21.10 | 510.00 | 21.10 |
| December | 533.00 | 21.10 | 533.00 | 21.10 | 533.00 | 21.10 |
| Annual Sum or Average | 4487.83 | 21.70 | 2978.33 | 21.56 | 2721.83 | 21.44 |
| Minimum of Months | 3.67 | 21.10 | 0.00 | 21.10 | 0.00 | 21.10 |
| Maximum of Months | 533.00 | 23.83 | 533.00 | 23.99 | 533.00 | 23.99 |
Report: ComfortReportSimple55Monthly
For: T SW APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 533.00 | 21.10 | 533.00 | 21.10 | 533.00 | 21.10 |
| February | 473.00 | 21.10 | 473.00 | 21.10 | 473.00 | 21.10 |
| March | 506.00 | 21.13 | 473.67 | 21.11 | 473.67 | 21.11 |
| April | 469.00 | 21.56 | 274.67 | 21.39 | 273.33 | 21.31 |
| May | 398.83 | 22.16 | 46.17 | 22.08 | 42.33 | 21.99 |
| June | 196.67 | 22.97 | 96.50 | 23.31 | 0.00 | 23.31 |
| July | 160.83 | 23.07 | 206.67 | 23.59 | 0.00 | 23.59 |
| August | 257.17 | 22.58 | 107.17 | 22.89 | 12.83 | 22.83 |
| September | 477.67 | 21.65 | 141.83 | 21.55 | 137.17 | 21.47 |
| October | 524.00 | 21.13 | 470.17 | 21.12 | 470.17 | 21.11 |
| November | 510.00 | 21.10 | 510.00 | 21.10 | 510.00 | 21.10 |
| December | 533.00 | 21.10 | 533.00 | 21.10 | 533.00 | 21.10 |
| Annual Sum or Average | 5039.17 | 21.50 | 3865.83 | 21.46 | 3458.50 | 21.36 |
| Minimum of Months | 160.83 | 21.10 | 46.17 | 21.10 | 0.00 | 21.10 |
| Maximum of Months | 533.00 | 23.07 | 533.00 | 23.59 | 533.00 | 23.59 |
Report: ComfortReportSimple55Monthly
For: T NW APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 744.00 | 21.10 | 744.00 | 21.10 | 744.00 | 21.10 |
| February | 672.00 | 21.10 | 672.00 | 21.10 | 672.00 | 21.10 |
| March | 744.00 | 21.10 | 740.83 | 21.10 | 740.83 | 21.10 |
| April | 720.00 | 21.38 | 509.67 | 21.26 | 509.67 | 21.22 |
| May | 672.00 | 22.34 | 60.50 | 22.23 | 60.50 | 22.15 |
| June | 208.83 | 23.14 | 108.33 | 23.43 | 0.00 | 23.43 |
| July | 173.83 | 23.04 | 280.00 | 23.63 | 0.00 | 23.63 |
| August | 443.67 | 22.55 | 107.33 | 22.67 | 30.00 | 22.59 |
| September | 720.00 | 21.38 | 292.33 | 21.30 | 292.33 | 21.26 |
| October | 744.00 | 21.10 | 721.50 | 21.10 | 721.50 | 21.10 |
| November | 720.00 | 21.10 | 720.00 | 21.10 | 720.00 | 21.10 |
| December | 744.00 | 21.10 | 744.00 | 21.10 | 744.00 | 21.10 |
| Annual Sum or Average | 7306.33 | 21.46 | 5700.50 | 21.41 | 5234.83 | 21.32 |
| Minimum of Months | 173.83 | 21.10 | 60.50 | 21.10 | 0.00 | 21.10 |
| Maximum of Months | 744.00 | 23.14 | 744.00 | 23.63 | 744.00 | 23.63 |
Report: ComfortReportSimple55Monthly
For: T SE APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 533.00 | 21.10 | 533.00 | 21.10 | 533.00 | 21.10 |
| February | 473.00 | 21.10 | 473.00 | 21.10 | 473.00 | 21.10 |
| March | 506.00 | 21.12 | 474.33 | 21.11 | 474.33 | 21.11 |
| April | 487.33 | 21.59 | 279.50 | 21.41 | 279.50 | 21.33 |
| May | 407.00 | 22.29 | 43.50 | 22.24 | 33.83 | 22.16 |
| June | 185.50 | 23.07 | 82.50 | 23.36 | 0.00 | 23.36 |
| July | 139.00 | 23.04 | 213.50 | 23.62 | 0.00 | 23.62 |
| August | 258.17 | 22.65 | 101.00 | 22.93 | 12.33 | 22.87 |
| September | 475.33 | 21.69 | 134.00 | 21.57 | 131.33 | 21.49 |
| October | 524.00 | 21.14 | 463.67 | 21.12 | 463.67 | 21.11 |
| November | 510.00 | 21.10 | 510.00 | 21.10 | 510.00 | 21.10 |
| December | 533.00 | 21.10 | 533.00 | 21.10 | 533.00 | 21.10 |
| Annual Sum or Average | 5031.33 | 21.51 | 3841.00 | 21.46 | 3444.00 | 21.36 |
| Minimum of Months | 139.00 | 21.10 | 43.50 | 21.10 | 0.00 | 21.10 |
| Maximum of Months | 533.00 | 23.07 | 533.00 | 23.62 | 533.00 | 23.62 |
Report: ComfortReportSimple55Monthly
For: T NE APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 744.00 | 21.10 | 744.00 | 21.10 | 744.00 | 21.10 |
| February | 672.00 | 21.10 | 672.00 | 21.10 | 672.00 | 21.10 |
| March | 744.00 | 21.10 | 736.67 | 21.10 | 736.67 | 21.10 |
| April | 720.00 | 21.37 | 499.83 | 21.26 | 499.83 | 21.21 |
| May | 638.00 | 22.61 | 53.17 | 22.51 | 50.50 | 22.41 |
| June | 189.17 | 23.13 | 154.67 | 23.52 | 0.00 | 23.52 |
| July | 154.00 | 23.01 | 348.33 | 23.69 | 0.00 | 23.69 |
| August | 399.17 | 22.60 | 115.17 | 22.81 | 18.17 | 22.75 |
| September | 720.00 | 21.42 | 269.50 | 21.33 | 269.50 | 21.28 |
| October | 744.00 | 21.10 | 710.83 | 21.10 | 710.83 | 21.10 |
| November | 720.00 | 21.10 | 720.00 | 21.10 | 720.00 | 21.10 |
| December | 744.00 | 21.10 | 744.00 | 21.10 | 744.00 | 21.10 |
| Annual Sum or Average | 7188.33 | 21.47 | 5768.17 | 21.44 | 5165.50 | 21.34 |
| Minimum of Months | 154.00 | 21.10 | 53.17 | 21.10 | 0.00 | 21.10 |
| Maximum of Months | 744.00 | 23.13 | 744.00 | 23.69 | 744.00 | 23.69 |
Report: ComfortReportSimple55Monthly
For: T N1 APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 744.00 | 21.10 | 744.00 | 21.10 | 744.00 | 21.10 |
| February | 672.00 | 21.10 | 672.00 | 21.10 | 672.00 | 21.10 |
| March | 744.00 | 21.10 | 740.83 | 21.10 | 740.83 | 21.10 |
| April | 720.00 | 21.29 | 514.50 | 21.21 | 514.50 | 21.18 |
| May | 724.33 | 22.61 | 35.00 | 22.54 | 35.00 | 22.48 |
| June | 188.50 | 23.43 | 63.17 | 23.57 | 0.00 | 23.57 |
| July | 126.67 | 23.26 | 205.17 | 23.72 | 0.00 | 23.72 |
| August | 419.00 | 22.78 | 68.50 | 22.80 | 25.67 | 22.71 |
| September | 720.00 | 21.39 | 230.83 | 21.32 | 230.83 | 21.28 |
| October | 744.00 | 21.10 | 689.17 | 21.10 | 689.17 | 21.10 |
| November | 720.00 | 21.10 | 720.00 | 21.10 | 720.00 | 21.10 |
| December | 744.00 | 21.10 | 744.00 | 21.10 | 744.00 | 21.10 |
| Annual Sum or Average | 7266.50 | 21.49 | 5427.17 | 21.40 | 5116.00 | 21.31 |
| Minimum of Months | 126.67 | 21.10 | 35.00 | 21.10 | 0.00 | 21.10 |
| Maximum of Months | 744.00 | 23.43 | 744.00 | 23.72 | 744.00 | 23.72 |
Report: ComfortReportSimple55Monthly
For: T N2 APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 744.00 | 21.10 | 744.00 | 21.10 | 744.00 | 21.10 |
| February | 672.00 | 21.10 | 672.00 | 21.10 | 672.00 | 21.10 |
| March | 744.00 | 21.10 | 740.50 | 21.10 | 740.50 | 21.10 |
| April | 720.00 | 21.30 | 515.67 | 21.21 | 515.67 | 21.18 |
| May | 724.50 | 22.66 | 34.17 | 22.59 | 34.17 | 22.52 |
| June | 187.50 | 23.43 | 63.50 | 23.58 | 0.00 | 23.58 |
| July | 125.67 | 23.26 | 208.67 | 23.72 | 0.00 | 23.72 |
| August | 412.83 | 22.78 | 69.50 | 22.81 | 24.67 | 22.73 |
| September | 720.00 | 21.40 | 226.33 | 21.33 | 226.33 | 21.28 |
| October | 744.00 | 21.10 | 687.00 | 21.10 | 687.00 | 21.10 |
| November | 720.00 | 21.10 | 720.00 | 21.10 | 720.00 | 21.10 |
| December | 744.00 | 21.10 | 744.00 | 21.10 | 744.00 | 21.10 |
| Annual Sum or Average | 7258.50 | 21.50 | 5425.33 | 21.40 | 5108.33 | 21.31 |
| Minimum of Months | 125.67 | 21.10 | 34.17 | 21.10 | 0.00 | 21.10 |
| Maximum of Months | 744.00 | 23.43 | 744.00 | 23.72 | 744.00 | 23.72 |
Report: ComfortReportSimple55Monthly
For: T S1 APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 533.00 | 21.10 | 533.00 | 21.10 | 533.00 | 21.10 |
| February | 473.00 | 21.10 | 472.33 | 21.10 | 472.33 | 21.10 |
| March | 506.00 | 21.14 | 461.67 | 21.12 | 461.67 | 21.12 |
| April | 491.83 | 21.73 | 225.83 | 21.53 | 225.83 | 21.43 |
| May | 423.67 | 22.52 | 19.83 | 22.46 | 18.83 | 22.40 |
| June | 177.50 | 23.28 | 57.17 | 23.45 | 0.00 | 23.45 |
| July | 114.83 | 23.26 | 187.00 | 23.72 | 0.00 | 23.72 |
| August | 230.83 | 22.87 | 86.83 | 23.10 | 8.33 | 23.05 |
| September | 478.67 | 21.86 | 96.33 | 21.74 | 95.50 | 21.65 |
| October | 524.00 | 21.17 | 426.00 | 21.14 | 426.00 | 21.13 |
| November | 510.00 | 21.10 | 510.00 | 21.10 | 510.00 | 21.10 |
| December | 533.00 | 21.10 | 533.00 | 21.10 | 533.00 | 21.10 |
| Annual Sum or Average | 4996.33 | 21.57 | 3609.00 | 21.48 | 3284.50 | 21.38 |
| Minimum of Months | 114.83 | 21.10 | 19.83 | 21.10 | 0.00 | 21.10 |
| Maximum of Months | 533.00 | 23.28 | 533.00 | 23.72 | 533.00 | 23.72 |
Report: ComfortReportSimple55Monthly
For: T S2 APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 533.00 | 21.10 | 533.00 | 21.10 | 533.00 | 21.10 |
| February | 473.00 | 21.10 | 472.17 | 21.10 | 472.17 | 21.10 |
| March | 506.00 | 21.14 | 461.67 | 21.12 | 461.67 | 21.12 |
| April | 491.83 | 21.72 | 227.00 | 21.53 | 227.00 | 21.42 |
| May | 423.33 | 22.52 | 20.33 | 22.46 | 19.00 | 22.41 |
| June | 177.67 | 23.29 | 57.17 | 23.46 | 0.00 | 23.46 |
| July | 114.50 | 23.26 | 187.00 | 23.72 | 0.00 | 23.72 |
| August | 231.17 | 22.88 | 86.50 | 23.11 | 8.17 | 23.06 |
| September | 478.50 | 21.86 | 96.50 | 21.74 | 95.50 | 21.65 |
| October | 524.00 | 21.17 | 425.00 | 21.14 | 425.00 | 21.13 |
| November | 510.00 | 21.10 | 510.00 | 21.10 | 510.00 | 21.10 |
| December | 533.00 | 21.10 | 533.00 | 21.10 | 533.00 | 21.10 |
| Annual Sum or Average | 4996.00 | 21.58 | 3609.33 | 21.49 | 3284.50 | 21.38 |
| Minimum of Months | 114.50 | 21.10 | 20.33 | 21.10 | 0.00 | 21.10 |
| Maximum of Months | 533.00 | 23.29 | 533.00 | 23.72 | 533.00 | 23.72 |
Report: ComfortReportSimple55Monthly
For: T CORRIDOR
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 744.00 | 18.63 | 744.00 | 18.63 | 744.00 | 18.63 |
| February | 672.00 | 19.05 | 588.17 | 18.98 | 588.17 | 18.96 |
| March | 744.00 | 19.89 | 594.50 | 19.82 | 594.50 | 19.80 |
| April | 703.33 | 21.73 | 353.17 | 21.76 | 349.67 | 21.76 |
| May | 700.17 | 24.03 | 665.50 | 24.16 | 628.33 | 24.19 |
| June | 720.00 | 25.61 | 720.00 | 25.61 | 720.00 | 25.61 |
| July | 744.00 | 25.67 | 744.00 | 25.67 | 744.00 | 25.67 |
| August | 739.00 | 24.82 | 738.67 | 24.82 | 735.50 | 24.83 |
| September | 720.00 | 22.16 | 720.00 | 22.16 | 720.00 | 22.16 |
| October | 744.00 | 20.24 | 474.17 | 20.17 | 474.17 | 20.14 |
| November | 720.00 | 18.77 | 720.00 | 18.77 | 720.00 | 18.77 |
| December | 744.00 | 18.47 | 744.00 | 18.47 | 744.00 | 18.47 |
| Annual Sum or Average | 8694.50 | 21.59 | 7806.17 | 21.63 | 7762.33 | 21.64 |
| Minimum of Months | 672.00 | 18.47 | 353.17 | 18.47 | 349.67 | 18.47 |
| Maximum of Months | 744.00 | 25.67 | 744.00 | 25.67 | 744.00 | 25.67 |
Report: ComfortReportSimple55Monthly
For: G CORRIDOR
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 744.00 | 13.03 | 744.00 | 13.03 | 744.00 | 13.03 |
| February | 672.00 | 13.65 | 672.00 | 13.65 | 672.00 | 13.65 |
| March | 744.00 | 15.03 | 744.00 | 15.03 | 744.00 | 15.03 |
| April | 720.00 | 18.14 | 639.83 | 17.94 | 639.83 | 17.87 |
| May | 741.50 | 21.66 | 136.00 | 21.22 | 136.00 | 20.90 |
| June | 248.33 | 22.87 | 319.33 | 24.22 | 26.67 | 24.23 |
| July | 233.17 | 24.01 | 572.17 | 24.99 | 135.33 | 25.07 |
| August | 320.50 | 22.89 | 382.83 | 24.05 | 80.33 | 24.10 |
| September | 720.00 | 20.63 | 239.67 | 19.99 | 239.67 | 19.61 |
| October | 744.00 | 17.05 | 695.17 | 16.90 | 695.17 | 16.85 |
| November | 720.00 | 13.38 | 720.00 | 13.38 | 720.00 | 13.38 |
| December | 744.00 | 12.74 | 744.00 | 12.74 | 744.00 | 12.74 |
| Annual Sum or Average | 7351.50 | 16.93 | 6609.00 | 16.88 | 5577.00 | 16.42 |
| Minimum of Months | 233.17 | 12.74 | 136.00 | 12.74 | 26.67 | 12.74 |
| Maximum of Months | 744.00 | 24.01 | 744.00 | 24.99 | 744.00 | 25.07 |
Report: ComfortReportSimple55Monthly
For: M CORRIDOR
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 744.00 | 20.69 | 683.00 | 20.70 | 683.00 | 20.71 |
| February | 672.00 | 21.05 | 573.00 | 21.09 | 573.00 | 21.10 |
| March | 744.00 | 21.63 | 637.17 | 21.63 | 637.17 | 21.63 |
| April | 720.00 | 23.08 | 548.67 | 23.21 | 548.67 | 23.27 |
| May | 739.50 | 25.30 | 738.00 | 25.31 | 738.00 | 25.31 |
| June | 720.00 | 26.01 | 720.00 | 26.01 | 720.00 | 26.01 |
| July | 744.00 | 26.01 | 744.00 | 26.01 | 744.00 | 26.01 |
| August | 744.00 | 25.69 | 744.00 | 25.69 | 744.00 | 25.69 |
| September | 720.00 | 23.83 | 720.00 | 23.83 | 720.00 | 23.83 |
| October | 744.00 | 21.80 | 722.33 | 21.81 | 722.33 | 21.81 |
| November | 720.00 | 20.86 | 704.17 | 20.86 | 704.17 | 20.86 |
| December | 744.00 | 20.58 | 744.00 | 20.58 | 744.00 | 20.58 |
| Annual Sum or Average | 8755.50 | 23.06 | 8278.33 | 23.10 | 8278.33 | 23.12 |
| Minimum of Months | 672.00 | 20.58 | 548.67 | 20.58 | 548.67 | 20.58 |
| Maximum of Months | 744.00 | 26.01 | 744.00 | 26.01 | 744.00 | 26.01 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_GSW
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 515.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 492.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 524.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 6145.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_GNW
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 8760.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_OFFICE
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 140.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 133.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 161.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 140.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 154.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 154.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 140.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 161.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 140.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 147.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 140.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 140.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 1750.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 133.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 161.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_GNE
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 8760.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_GN1
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 8760.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_GN2
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 8760.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_GS1
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 515.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 492.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 524.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 6145.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_GS2
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 515.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 492.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 524.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 6145.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_MSW
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 515.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 492.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 524.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 6145.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_MNW
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 8760.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_MSE
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 515.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 492.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 524.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 6145.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_MNE
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 8760.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_MN1
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 8760.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_MN2
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 8760.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_MS1
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 515.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 492.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 524.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 6145.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_MS2
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 515.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 492.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 524.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 6145.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_TSW
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 515.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 492.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 524.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 6145.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_TNW
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 8760.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_TSE
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 515.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 492.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 524.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 6145.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_TNE
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 8760.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_TN1
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 8760.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_TN2
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 8760.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_TS1
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 515.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 492.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 524.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 6145.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_TS2
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 515.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 492.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 524.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 6145.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_T CORRIDOR
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 8760.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_G CORRIDOR
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 8760.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_M CORRIDOR
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 8760.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: DXReportMonthly
For: SPLIT GSW COOLING COIL
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
| April | 3106947.16 | 830111.37 | 6.17 | 3106947.16 | -0.0 | 0.00 | 0.05 | 22-APR-16:03 | 0.00 | 01-APR-00:10 | 276.82 | 22-APR-16:03 | 276.82 | 22-APR-16:03 | 0.00 | 22-APR-16:05 | 73.69 | 22-APR-16:03 | 0.00 | 01-APR-00:10 |
| May | 87085144.88 | 23049120.44 | 83.56 | 87085144.88 | -0.0 | 0.00 | 0.15 | 31-MAY-16:05 | 0.00 | 01-MAY-00:10 | 791.22 | 31-MAY-16:05 | 791.22 | 31-MAY-16:05 | 0.00 | 13-MAY-16:02 | 206.86 | 31-MAY-16:05 | 0.00 | 01-MAY-00:10 |
| June | 0.913223E+09 | 0.236123E+09 | 432.51 | 0.900053E+09 | 13169203.61 | 0.00 | 0.34 | 21-JUN-16:40 | 0.00 | 01-JUN-00:10 | 1883.88 | 21-JUN-16:30 | 1883.88 | 21-JUN-16:30 | 214.74 | 30-JUN-19:00 | 487.43 | 21-JUN-16:40 | 0.00 | 01-JUN-00:10 |
| July | 0.152377E+10 | 0.389200E+09 | 579.33 | 0.145959E+10 | 64177230.45 | 0.00 | 0.42 | 29-JUL-16:10 | 0.00 | 01-JUL-02:40 | 2359.81 | 29-JUL-16:10 | 2279.71 | 29-JUL-16:03 | 162.53 | 08-JUL-18:00 | 635.22 | 29-JUL-16:10 | 0.00 | 01-JUL-00:10 |
| August | 0.113189E+10 | 0.288904E+09 | 493.40 | 0.110308E+10 | 28814806.30 | 0.00 | 0.42 | 11-AUG-16:06 | 0.00 | 04-AUG-03:50 | 2367.12 | 11-AUG-16:06 | 2367.12 | 11-AUG-16:06 | 155.66 | 12-AUG-21:05 | 602.85 | 11-AUG-16:06 | 0.00 | 01-AUG-00:10 |
| September | 44781883.61 | 11765773.49 | 51.64 | 44781883.61 | -0.0 | 0.00 | 0.13 | 09-SEP-15:50 | 0.00 | 01-SEP-00:10 | 681.04 | 09-SEP-15:50 | 681.04 | 09-SEP-15:50 | 0.00 | 08-SEP-16:50 | 177.57 | 09-SEP-15:50 | 0.00 | 01-SEP-00:10 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.370386E+10 | 0.949872E+09 | 1646.61 | 0.359770E+10 | 0.106161E+09 | 0.00 | ||||||||||||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | -0.0 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Maximum of Months | 0.152377E+10 | 0.389200E+09 | 579.33 | 0.145959E+10 | 64177230.45 | 0.00 | 0.42 | 0.00 | 2367.12 | 2367.12 | 214.74 | 635.22 | 0.00 |
Report: DXReportMonthly
For: SPLIT GNW COOLING COIL
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 |
| May | 46944.89 | 12533.60 | 0.58 | 46944.89 | -0.0 | 0.00 | 0.01 | 31-MAY-17:20 | 0.00 | 01-MAY-00:10 | 30.71 | 31-MAY-17:20 | 30.71 | 31-MAY-17:20 | 0.00 | 31-MAY-17:20 | 8.20 | 31-MAY-17:20 | 0.00 | 01-MAY-00:10 |
| June | 0.513538E+09 | 0.132982E+09 | 319.94 | 0.503833E+09 | 9705148.25 | 0.00 | 0.31 | 21-JUN-17:30 | 0.00 | 01-JUN-00:10 | 1416.36 | 21-JUN-17:30 | 1416.36 | 21-JUN-17:30 | 176.18 | 30-JUN-19:00 | 367.90 | 21-JUN-17:10 | 0.00 | 01-JUN-00:10 |
| July | 0.955689E+09 | 0.245221E+09 | 512.97 | 0.914125E+09 | 41564310.97 | 0.00 | 0.36 | 11-JUL-18:00 | 0.00 | 01-JUL-00:50 | 1689.34 | 11-JUL-18:00 | 1689.34 | 11-JUL-18:00 | 134.10 | 24-JUL-18:00 | 433.73 | 11-JUL-18:00 | 0.00 | 01-JUL-00:10 |
| August | 0.440216E+09 | 0.113070E+09 | 309.27 | 0.424401E+09 | 15814590.36 | 0.00 | 0.31 | 11-AUG-17:40 | 0.00 | 01-AUG-02:20 | 1411.20 | 11-AUG-17:40 | 1411.20 | 11-AUG-17:40 | 107.75 | 12-AUG-21:05 | 365.12 | 11-AUG-17:40 | 0.00 | 01-AUG-00:10 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.190949E+10 | 0.491285E+09 | 1142.77 | 0.184241E+10 | 67084049.59 | 0.00 | ||||||||||||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | -0.0 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Maximum of Months | 0.955689E+09 | 0.245221E+09 | 512.97 | 0.914125E+09 | 41564310.97 | 0.00 | 0.36 | 0.00 | 1689.34 | 1689.34 | 176.18 | 433.73 | 0.00 |
Report: DXReportMonthly
For: SPLIT OFFICE COOLING COIL
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
| April | 5678279.49 | 1519732.09 | 8.83 | 5678279.49 | 0.00 | 0.00 | 0.07 | 21-APR-15:40 | 0.00 | 01-APR-00:10 | 406.99 | 21-APR-15:40 | 406.99 | 21-APR-15:40 | 0.00 | 21-APR-15:30 | 108.53 | 21-APR-15:40 | 0.00 | 01-APR-00:10 |
| May | 0.438268E+09 | 0.113931E+09 | 133.24 | 0.438268E+09 | 0.00 | 0.00 | 0.97 | 15-MAY-08:62 | 0.00 | 01-MAY-00:10 | 6161.42 | 15-MAY-08:62 | 6161.42 | 15-MAY-08:62 | 0.00 | 12-MAY-13:50 | 1415.30 | 15-MAY-08:62 | 0.00 | 01-MAY-00:10 |
| June | 0.127326E+10 | 0.319099E+09 | 194.17 | 0.125150E+10 | 21759000.55 | 0.00 | 1.00 | 05-JUN-08:62 | 0.00 | 01-JUN-00:10 | 6935.94 | 30-JUN-08:62 | 6751.75 | 22-JUN-08:62 | 761.73 | 30-JUN-08:62 | 1514.83 | 30-JUN-08:62 | 0.00 | 01-JUN-00:10 |
| July | 0.154978E+10 | 0.380900E+09 | 201.50 | 0.148876E+10 | 61016419.55 | 0.00 | 1.00 | 03-JUL-08:62 | 0.00 | 01-JUL-00:10 | 7027.39 | 25-JUL-07:01 | 6883.28 | 11-JUL-07:02 | 1046.22 | 25-JUL-08:62 | 1519.75 | 25-JUL-07:01 | 0.00 | 01-JUL-00:10 |
| August | 0.137148E+10 | 0.340622E+09 | 201.15 | 0.132776E+10 | 43722421.06 | 0.00 | 1.00 | 01-AUG-08:62 | 0.00 | 01-AUG-00:10 | 6925.22 | 04-AUG-08:62 | 6715.92 | 09-AUG-08:62 | 847.79 | 04-AUG-08:62 | 1514.17 | 04-AUG-08:62 | 0.00 | 01-AUG-00:10 |
| September | 0.179683E+09 | 46947571.21 | 84.92 | 0.179683E+09 | 0.00 | 0.00 | 0.33 | 01-SEP-08:65 | 0.00 | 01-SEP-00:10 | 1902.33 | 01-SEP-08:65 | 1902.33 | 01-SEP-08:65 | 0.00 | 01-SEP-12:30 | 481.78 | 01-SEP-08:65 | 0.00 | 01-SEP-00:10 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.481815E+10 | 0.120302E+10 | 823.81 | 0.469165E+10 | 0.126498E+09 | 0.00 | ||||||||||||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Maximum of Months | 0.154978E+10 | 0.380900E+09 | 201.50 | 0.148876E+10 | 61016419.55 | 0.00 | 1.00 | 0.00 | 7027.39 | 6883.28 | 1046.22 | 1519.75 | 0.00 |
Report: DXReportMonthly
For: SPLIT GNE COOLING COIL
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 |
| May | 313456.57 | 83809.91 | 2.61 | 313456.57 | -0.0 | 0.00 | 0.02 | 13-MAY-16:02 | 0.00 | 01-MAY-00:10 | 76.94 | 13-MAY-16:02 | 76.94 | 13-MAY-16:02 | 0.00 | 31-MAY-16:35 | 20.58 | 13-MAY-16:02 | 0.00 | 01-MAY-00:10 |
| June | 0.641417E+09 | 0.165894E+09 | 400.19 | 0.632082E+09 | 9334832.90 | 0.00 | 0.31 | 13-JUN-18:00 | 0.00 | 01-JUN-00:10 | 1226.50 | 13-JUN-18:00 | 1226.50 | 13-JUN-18:00 | 153.19 | 30-JUN-11:30 | 321.07 | 30-JUN-15:00 | 0.00 | 01-JUN-00:10 |
| July | 0.123140E+10 | 0.313503E+09 | 559.10 | 0.117613E+10 | 55276896.22 | 0.00 | 0.40 | 21-JUL-16:06 | 0.00 | 01-JUL-00:50 | 1587.38 | 22-JUL-11:20 | 1579.70 | 21-JUL-16:04 | 132.25 | 29-JUL-20:00 | 425.19 | 21-JUL-16:04 | 0.00 | 01-JUL-00:10 |
| August | 0.566135E+09 | 0.145054E+09 | 370.67 | 0.546843E+09 | 19292020.92 | 0.00 | 0.31 | 11-AUG-17:13 | 0.00 | 01-AUG-02:70 | 1228.98 | 11-AUG-17:20 | 1228.98 | 11-AUG-17:20 | 113.17 | 12-AUG-21:05 | 318.17 | 11-AUG-17:20 | 0.00 | 01-AUG-00:10 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.243927E+10 | 0.624535E+09 | 1332.57 | 0.235536E+10 | 83903750.04 | 0.00 | ||||||||||||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | -0.0 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Maximum of Months | 0.123140E+10 | 0.313503E+09 | 559.10 | 0.117613E+10 | 55276896.22 | 0.00 | 0.40 | 0.00 | 1587.38 | 1579.70 | 153.19 | 425.19 | 0.00 |
Report: DXReportMonthly
For: SPLIT GN1 COOLING COIL
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 |
| June | 0.470156E+09 | 0.121762E+09 | 392.40 | 0.460776E+09 | 9379875.91 | 0.00 | 0.28 | 30-JUN-15:10 | 0.00 | 01-JUN-00:10 | 1007.73 | 30-JUN-15:10 | 994.18 | 21-JUN-20:00 | 143.34 | 30-JUN-19:20 | 267.96 | 30-JUN-15:00 | 0.00 | 01-JUN-00:10 |
| July | 0.921216E+09 | 0.235744E+09 | 580.21 | 0.873499E+09 | 47716857.09 | 0.00 | 0.35 | 29-JUL-17:00 | 0.00 | 01-JUL-01:50 | 1251.56 | 29-JUL-17:00 | 1210.94 | 21-JUL-16:08 | 125.43 | 17-JUL-19:40 | 340.43 | 29-JUL-17:00 | 0.00 | 01-JUL-00:10 |
| August | 0.418563E+09 | 0.107444E+09 | 368.32 | 0.400832E+09 | 17730515.79 | 0.00 | 0.27 | 11-AUG-18:00 | 0.00 | 01-AUG-02:30 | 967.08 | 11-AUG-18:00 | 967.08 | 11-AUG-18:00 | 108.97 | 12-AUG-21:05 | 251.63 | 11-AUG-18:00 | 0.00 | 01-AUG-00:10 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.180994E+10 | 0.464951E+09 | 1340.92 | 0.173511E+10 | 74827248.79 | 0.00 | ||||||||||||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Maximum of Months | 0.921216E+09 | 0.235744E+09 | 580.21 | 0.873499E+09 | 47716857.09 | 0.00 | 0.35 | 0.00 | 1251.56 | 1210.94 | 143.34 | 340.43 | 0.00 |
Report: DXReportMonthly
For: SPLIT GN2 COOLING COIL
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 |
| June | 0.482009E+09 | 0.124847E+09 | 401.12 | 0.472722E+09 | 9287170.78 | 0.00 | 0.28 | 30-JUN-15:00 | 0.00 | 01-JUN-00:10 | 1006.81 | 30-JUN-15:10 | 986.89 | 21-JUN-20:00 | 142.44 | 30-JUN-19:20 | 268.20 | 30-JUN-15:00 | 0.00 | 01-JUN-00:10 |
| July | 0.938213E+09 | 0.240008E+09 | 583.80 | 0.889537E+09 | 48675667.84 | 0.00 | 0.35 | 29-JUL-17:00 | 0.00 | 01-JUL-01:50 | 1256.12 | 29-JUL-17:00 | 1219.22 | 21-JUL-16:04 | 125.40 | 17-JUL-19:40 | 341.58 | 29-JUL-17:00 | 0.00 | 01-JUL-00:10 |
| August | 0.428792E+09 | 0.110062E+09 | 377.05 | 0.410782E+09 | 18009873.20 | 0.00 | 0.27 | 11-AUG-17:50 | 0.00 | 01-AUG-02:30 | 970.05 | 11-AUG-17:50 | 970.05 | 11-AUG-17:50 | 109.53 | 12-AUG-21:05 | 252.40 | 11-AUG-17:50 | 0.00 | 01-AUG-00:10 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.184901E+10 | 0.474917E+09 | 1361.96 | 0.177304E+10 | 75972711.82 | 0.00 | ||||||||||||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Maximum of Months | 0.938213E+09 | 0.240008E+09 | 583.80 | 0.889537E+09 | 48675667.84 | 0.00 | 0.35 | 0.00 | 1256.12 | 1219.22 | 142.44 | 341.58 | 0.00 |
Report: DXReportMonthly
For: SPLIT GS1 COOLING COIL
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
| April | 1353845.24 | 361594.74 | 3.67 | 1353845.24 | 0.00 | 0.00 | 0.04 | 22-APR-16:07 | 0.00 | 01-APR-00:10 | 190.42 | 22-APR-16:07 | 190.42 | 22-APR-16:07 | 0.00 | 22-APR-16:30 | 50.75 | 22-APR-16:07 | 0.00 | 01-APR-00:10 |
| May | 0.115461E+09 | 30478029.78 | 114.77 | 0.115461E+09 | -0.0 | 0.00 | 0.18 | 13-MAY-15:10 | 0.00 | 01-MAY-00:10 | 814.12 | 13-MAY-15:10 | 814.12 | 13-MAY-15:10 | 0.00 | 13-MAY-14:40 | 212.48 | 13-MAY-15:10 | 0.00 | 01-MAY-00:10 |
| June | 0.917062E+09 | 0.236975E+09 | 522.80 | 0.903181E+09 | 13880966.32 | 0.00 | 0.34 | 30-JUN-14:30 | 0.00 | 01-JUN-00:10 | 1585.59 | 30-JUN-14:30 | 1533.59 | 30-JUN-14:30 | 182.62 | 30-JUN-19:00 | 417.64 | 30-JUN-14:30 | 0.00 | 01-JUN-00:10 |
| July | 0.152957E+10 | 0.389663E+09 | 652.97 | 0.145698E+10 | 72590912.13 | 0.00 | 0.43 | 29-JUL-16:10 | 0.00 | 01-JUL-15:20 | 2043.50 | 29-JUL-16:10 | 1972.28 | 29-JUL-16:07 | 146.65 | 15-JUL-20:10 | 548.83 | 29-JUL-16:10 | 0.00 | 01-JUL-00:10 |
| August | 0.119217E+10 | 0.304072E+09 | 597.61 | 0.115904E+10 | 33132335.00 | 0.00 | 0.42 | 11-AUG-16:10 | 0.00 | 07-AUG-02:50 | 1964.48 | 11-AUG-16:10 | 1964.48 | 11-AUG-16:10 | 159.45 | 12-AUG-21:05 | 500.57 | 11-AUG-16:10 | 0.00 | 01-AUG-00:10 |
| September | 90647390.44 | 23793325.33 | 108.61 | 90647390.44 | 0.00 | 0.00 | 0.16 | 09-SEP-15:30 | 0.00 | 01-SEP-00:10 | 727.73 | 09-SEP-15:30 | 727.73 | 09-SEP-15:30 | 0.00 | 01-SEP-15:10 | 188.74 | 09-SEP-15:30 | 0.00 | 01-SEP-00:10 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.384626E+10 | 0.985343E+09 | 2000.44 | 0.372666E+10 | 0.119604E+09 | 0.00 | ||||||||||||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | -0.0 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Maximum of Months | 0.152957E+10 | 0.389663E+09 | 652.97 | 0.145698E+10 | 72590912.13 | 0.00 | 0.43 | 0.00 | 2043.50 | 1972.28 | 182.62 | 548.83 | 0.00 |
Report: DXReportMonthly
For: SPLIT GS2 COOLING COIL
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
| April | 1140158.57 | 304684.11 | 3.42 | 1140158.57 | 0.00 | 0.00 | 0.04 | 22-APR-16:05 | 0.00 | 01-APR-00:10 | 173.22 | 22-APR-16:05 | 173.22 | 22-APR-16:05 | 0.00 | 22-APR-15:30 | 46.20 | 22-APR-16:05 | 0.00 | 01-APR-00:10 |
| May | 0.150136E+09 | 39576179.07 | 138.05 | 0.150136E+09 | 0.00 | 0.00 | 0.20 | 13-MAY-15:10 | 0.00 | 01-MAY-00:10 | 920.75 | 13-MAY-15:10 | 920.75 | 13-MAY-15:10 | 0.00 | 13-MAY-16:06 | 239.50 | 13-MAY-15:10 | 0.00 | 01-MAY-00:10 |
| June | 0.104138E+10 | 0.268777E+09 | 557.11 | 0.102596E+10 | 15418097.17 | 0.00 | 0.34 | 30-JUN-14:30 | 0.00 | 01-JUN-00:10 | 1642.53 | 30-JUN-14:30 | 1591.10 | 30-JUN-14:30 | 192.41 | 30-JUN-19:30 | 432.05 | 30-JUN-14:30 | 0.00 | 01-JUN-00:10 |
| July | 0.172769E+10 | 0.439214E+09 | 678.58 | 0.164483E+10 | 82853214.81 | 0.00 | 0.45 | 29-JUL-16:10 | 0.00 | 01-JUL-23:50 | 2161.20 | 29-JUL-16:10 | 2088.14 | 29-JUL-16:07 | 161.37 | 15-JUL-20:10 | 578.57 | 29-JUL-16:10 | 0.00 | 01-JUL-00:10 |
| August | 0.135274E+10 | 0.344642E+09 | 633.06 | 0.131495E+10 | 37790961.81 | 0.00 | 0.43 | 11-AUG-16:04 | 0.00 | 08-AUG-03:50 | 2025.85 | 11-AUG-16:04 | 2025.85 | 11-AUG-16:04 | 172.75 | 12-AUG-21:05 | 515.42 | 11-AUG-16:04 | 0.00 | 01-AUG-00:10 |
| September | 0.116009E+09 | 30424684.96 | 124.67 | 0.116009E+09 | 0.00 | 0.00 | 0.17 | 09-SEP-15:30 | 0.00 | 01-SEP-00:10 | 797.09 | 09-SEP-15:30 | 797.09 | 09-SEP-15:30 | 0.00 | 02-SEP-14:50 | 206.29 | 09-SEP-15:30 | 0.00 | 01-SEP-00:10 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.438909E+10 | 0.112294E+10 | 2134.88 | 0.425303E+10 | 0.136062E+09 | 0.00 | ||||||||||||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Maximum of Months | 0.172769E+10 | 0.439214E+09 | 678.58 | 0.164483E+10 | 82853214.81 | 0.00 | 0.45 | 0.00 | 2161.20 | 2088.14 | 192.41 | 578.57 | 0.00 |
Report: DXReportMonthly
For: SPLIT MSW COOLING COIL
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
| April | 0.568471E+09 | 0.148859E+09 | 110.91 | 0.568471E+09 | 0.00 | 0.00 | 0.30 | 22-APR-16:05 | 0.00 | 01-APR-00:10 | 4068.55 | 22-APR-16:05 | 4068.55 | 22-APR-16:05 | 0.00 | 21-APR-17:02 | 1043.01 | 22-APR-16:05 | 0.00 | 01-APR-00:10 |
| May | 0.237958E+10 | 0.620169E+09 | 411.36 | 0.237958E+10 | 0.00 | 0.00 | 0.36 | 31-MAY-16:10 | 0.00 | 01-MAY-00:10 | 4926.27 | 31-MAY-16:10 | 4926.27 | 31-MAY-16:10 | 0.00 | 10-MAY-16:25 | 1247.11 | 31-MAY-16:10 | 0.00 | 01-MAY-00:10 |
| June | 0.461464E+10 | 0.118425E+10 | 664.35 | 0.455217E+10 | 62473033.35 | 0.00 | 0.41 | 20-JUN-16:20 | 0.00 | 01-JUN-03:10 | 5846.42 | 20-JUN-16:08 | 5846.42 | 20-JUN-16:08 | 641.26 | 30-JUN-19:00 | 1489.67 | 20-JUN-16:20 | 0.00 | 01-JUN-00:10 |
| July | 0.518780E+10 | 0.131997E+10 | 701.34 | 0.497480E+10 | 0.213006E+09 | 0.00 | 0.46 | 29-JUL-15:30 | 0.00 | 02-JUL-02:30 | 6516.55 | 29-JUL-15:30 | 6393.01 | 29-JUL-15:30 | 465.54 | 17-JUL-19:30 | 1739.69 | 29-JUL-15:40 | 0.00 | 01-JUL-00:10 |
| August | 0.360989E+10 | 0.920527E+09 | 589.98 | 0.353028E+10 | 79611893.31 | 0.00 | 0.44 | 11-AUG-16:02 | 0.00 | 07-AUG-01:50 | 6195.43 | 11-AUG-16:04 | 6195.43 | 11-AUG-16:04 | 354.89 | 12-AUG-21:05 | 1573.51 | 11-AUG-16:04 | 0.00 | 01-AUG-00:10 |
| September | 0.558250E+09 | 0.145819E+09 | 152.58 | 0.558250E+09 | -0.0 | 0.00 | 0.25 | 09-SEP-15:50 | 0.00 | 01-SEP-00:10 | 3499.81 | 09-SEP-15:50 | 3499.81 | 09-SEP-15:50 | 0.00 | 09-SEP-15:10 | 894.91 | 09-SEP-15:50 | 0.00 | 01-SEP-00:10 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.169186E+11 | 0.433959E+10 | 2630.51 | 0.165635E+11 | 0.355091E+09 | 0.00 | ||||||||||||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | -0.0 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Maximum of Months | 0.518780E+10 | 0.131997E+10 | 701.34 | 0.497480E+10 | 0.213006E+09 | 0.00 | 0.46 | 0.00 | 6516.55 | 6393.01 | 641.26 | 1739.69 | 0.00 |
Report: DXReportMonthly
For: SPLIT MNW COOLING COIL
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
| April | 5802605.80 | 1551122.37 | 5.83 | 5802605.80 | -0.0 | 0.00 | 0.04 | 21-APR-18:00 | 0.00 | 01-APR-00:10 | 479.14 | 21-APR-18:00 | 479.14 | 21-APR-18:00 | 0.00 | 21-APR-17:10 | 127.93 | 21-APR-18:00 | 0.00 | 01-APR-00:10 |
| May | 0.815830E+09 | 0.214448E+09 | 272.37 | 0.815830E+09 | 0.00 | 0.00 | 0.27 | 31-MAY-17:15 | 0.00 | 01-MAY-00:10 | 3179.91 | 31-MAY-17:30 | 3179.91 | 31-MAY-17:30 | 0.00 | 31-MAY-17:05 | 815.48 | 31-MAY-17:30 | 0.00 | 01-MAY-00:10 |
| June | 0.359151E+10 | 0.924301E+09 | 664.09 | 0.353309E+10 | 58416411.41 | 0.00 | 0.37 | 20-JUN-17:40 | 0.00 | 01-JUN-01:40 | 4556.11 | 29-JUN-19:30 | 4534.08 | 20-JUN-17:40 | 585.77 | 30-JUN-19:00 | 1174.54 | 20-JUN-17:50 | 0.00 | 01-JUN-00:10 |
| July | 0.390064E+10 | 0.996571E+09 | 691.34 | 0.372179E+10 | 0.178849E+09 | 0.00 | 0.39 | 11-JUL-18:00 | 0.00 | 01-JUL-23:50 | 4826.54 | 11-JUL-18:00 | 4826.54 | 11-JUL-18:00 | 429.68 | 17-JUL-19:30 | 1233.71 | 11-JUL-18:00 | 0.00 | 01-JUL-00:10 |
| August | 0.187895E+10 | 0.482404E+09 | 495.62 | 0.182117E+10 | 57772470.13 | 0.00 | 0.33 | 11-AUG-17:25 | 0.00 | 02-AUG-03:30 | 3997.38 | 11-AUG-17:25 | 3997.38 | 11-AUG-17:25 | 296.70 | 12-AUG-21:05 | 1030.66 | 11-AUG-17:25 | 0.00 | 01-AUG-00:10 |
| September | 944715.79 | 249801.80 | 1.58 | 944715.79 | 0.00 | 0.00 | 0.03 | 02-SEP-19:20 | 0.00 | 01-SEP-00:10 | 341.49 | 02-SEP-19:20 | 341.49 | 02-SEP-19:20 | 0.00 | 02-SEP-17:17 | 90.13 | 02-SEP-19:20 | 0.00 | 01-SEP-00:10 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.101937E+11 | 0.261952E+10 | 2130.84 | 0.989864E+10 | 0.295038E+09 | 0.00 | ||||||||||||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | -0.0 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Maximum of Months | 0.390064E+10 | 0.996571E+09 | 691.34 | 0.372179E+10 | 0.178849E+09 | 0.00 | 0.39 | 0.00 | 4826.54 | 4826.54 | 585.77 | 1233.71 | 0.00 |
Report: DXReportMonthly
For: SPLIT MSE COOLING COIL
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
| April | 0.534768E+09 | 0.139783E+09 | 118.31 | 0.534768E+09 | -0.0 | 0.00 | 0.33 | 22-APR-13:30 | 0.00 | 01-APR-00:10 | 3849.53 | 22-APR-13:30 | 3849.53 | 22-APR-13:30 | 0.00 | 22-APR-12:40 | 981.26 | 22-APR-13:30 | 0.00 | 01-APR-00:10 |
| May | 0.303786E+10 | 0.786182E+09 | 465.25 | 0.303786E+10 | -0.0 | 0.00 | 0.42 | 12-MAY-13:30 | 0.00 | 01-MAY-00:10 | 4955.74 | 12-MAY-13:30 | 4955.74 | 12-MAY-13:30 | 0.00 | 31-MAY-15:50 | 1246.24 | 12-MAY-13:30 | 0.00 | 01-MAY-00:10 |
| June | 0.502999E+10 | 0.128415E+10 | 679.95 | 0.496854E+10 | 61447074.84 | 0.00 | 0.46 | 30-JUN-12:30 | 0.00 | 01-JUN-04:00 | 5761.75 | 30-JUN-12:30 | 5558.12 | 29-JUN-14:10 | 578.17 | 30-JUN-19:00 | 1445.73 | 30-JUN-12:30 | 0.00 | 01-JUN-00:10 |
| July | 0.581941E+10 | 0.146885E+10 | 709.21 | 0.558668E+10 | 0.232739E+09 | 0.00 | 0.52 | 22-JUL-11:30 | 0.00 | 02-JUL-02:40 | 6602.31 | 22-JUL-11:30 | 6316.15 | 22-JUL-11:40 | 439.45 | 17-JUL-19:30 | 1662.48 | 29-JUL-15:30 | 0.00 | 01-JUL-00:10 |
| August | 0.401757E+10 | 0.101893E+10 | 616.56 | 0.393065E+10 | 86917255.23 | 0.00 | 0.47 | 10-AUG-14:10 | 0.00 | 07-AUG-02:00 | 5762.48 | 11-AUG-14:30 | 5762.48 | 11-AUG-14:30 | 366.25 | 04-AUG-11:00 | 1433.78 | 11-AUG-15:10 | 0.00 | 01-AUG-00:10 |
| September | 0.699777E+09 | 0.182218E+09 | 175.50 | 0.699777E+09 | 0.00 | 0.00 | 0.29 | 10-SEP-11:30 | 0.00 | 01-SEP-00:10 | 3420.87 | 10-SEP-11:30 | 3420.87 | 10-SEP-11:30 | 0.00 | 09-SEP-16:05 | 873.23 | 10-SEP-11:30 | 0.00 | 01-SEP-00:10 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.191394E+11 | 0.488012E+10 | 2764.77 | 0.187583E+11 | 0.381103E+09 | 0.00 | ||||||||||||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | -0.0 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Maximum of Months | 0.581941E+10 | 0.146885E+10 | 709.21 | 0.558668E+10 | 0.232739E+09 | 0.00 | 0.52 | 0.00 | 6602.31 | 6316.15 | 578.17 | 1662.48 | 0.00 |
Report: DXReportMonthly
For: SPLIT MNE COOLING COIL
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 |
| May | 0.136069E+10 | 0.355928E+09 | 363.17 | 0.136069E+10 | 0.00 | 0.00 | 0.28 | 31-MAY-16:17 | 0.00 | 01-MAY-00:10 | 2726.57 | 31-MAY-16:17 | 2726.57 | 31-MAY-16:17 | 0.00 | 31-MAY-10:40 | 698.60 | 31-MAY-16:17 | 0.00 | 01-MAY-00:10 |
| June | 0.400876E+10 | 0.102591E+10 | 671.30 | 0.395181E+10 | 56948396.39 | 0.00 | 0.38 | 29-JUN-10:40 | 0.00 | 01-JUN-01:50 | 4043.42 | 29-JUN-10:40 | 3806.83 | 29-JUN-10:40 | 518.75 | 30-JUN-19:00 | 1009.63 | 30-JUN-15:00 | 0.00 | 01-JUN-00:10 |
| July | 0.453396E+10 | 0.114844E+10 | 695.87 | 0.433373E+10 | 0.200235E+09 | 0.00 | 0.43 | 21-JUL-16:06 | 0.00 | 01-JUL-24:00 | 4436.41 | 22-JUL-10:50 | 4253.50 | 21-JUL-16:06 | 404.05 | 17-JUL-19:30 | 1139.93 | 21-JUL-16:06 | 0.00 | 01-JUL-00:10 |
| August | 0.223079E+10 | 0.570443E+09 | 529.18 | 0.216428E+10 | 66514869.54 | 0.00 | 0.31 | 11-AUG-17:13 | 0.00 | 02-AUG-02:40 | 3116.81 | 11-AUG-17:13 | 3116.81 | 11-AUG-17:13 | 299.00 | 12-AUG-21:05 | 806.52 | 11-AUG-17:13 | 0.00 | 01-AUG-00:10 |
| September | 449771.42 | 118571.68 | 1.50 | 449771.42 | -0.0 | 0.00 | 0.02 | 01-SEP-16:40 | 0.00 | 01-SEP-00:10 | 166.45 | 01-SEP-16:40 | 166.45 | 01-SEP-16:40 | 0.00 | 01-SEP-17:12 | 43.84 | 01-SEP-16:40 | 0.00 | 01-SEP-00:10 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.121346E+11 | 0.310084E+10 | 2261.01 | 0.118109E+11 | 0.323698E+09 | 0.00 | ||||||||||||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | -0.0 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Maximum of Months | 0.453396E+10 | 0.114844E+10 | 695.87 | 0.433373E+10 | 0.200235E+09 | 0.00 | 0.43 | 0.00 | 4436.41 | 4253.50 | 518.75 | 1139.93 | 0.00 |
Report: DXReportMonthly
For: SPLIT MN1 COOLING COIL
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 |
| May | 0.631129E+09 | 0.166394E+09 | 307.13 | 0.631129E+09 | -0.0 | 0.00 | 0.23 | 31-MAY-17:20 | 0.00 | 01-MAY-00:10 | 1987.62 | 31-MAY-17:20 | 1987.62 | 31-MAY-17:20 | 0.00 | 31-MAY-16:00 | 513.15 | 31-MAY-17:20 | 0.00 | 01-MAY-00:10 |
| June | 0.290128E+10 | 0.747119E+09 | 691.17 | 0.284940E+10 | 51880113.03 | 0.00 | 0.33 | 29-JUN-20:00 | 0.00 | 01-JUN-02:70 | 3040.53 | 29-JUN-20:00 | 2934.67 | 21-JUN-20:00 | 452.43 | 30-JUN-19:20 | 781.60 | 30-JUN-15:00 | 0.00 | 01-JUN-00:10 |
| July | 0.332374E+10 | 0.847958E+09 | 725.33 | 0.315321E+10 | 0.170530E+09 | 0.00 | 0.36 | 21-JUL-16:02 | 0.00 | 03-JUL-02:20 | 3176.30 | 29-JUL-17:10 | 3151.42 | 21-JUL-16:02 | 395.29 | 17-JUL-19:30 | 863.57 | 29-JUL-17:00 | 0.00 | 01-JUL-00:10 |
| August | 0.168995E+10 | 0.433875E+09 | 574.41 | 0.162810E+10 | 61842833.27 | 0.00 | 0.28 | 11-AUG-17:50 | 0.00 | 07-AUG-02:40 | 2477.95 | 11-AUG-18:00 | 2477.95 | 11-AUG-18:00 | 290.03 | 12-AUG-21:05 | 644.12 | 11-AUG-18:00 | 0.00 | 01-AUG-00:10 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.854610E+10 | 0.219535E+10 | 2298.04 | 0.826185E+10 | 0.284253E+09 | 0.00 | ||||||||||||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | -0.0 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Maximum of Months | 0.332374E+10 | 0.847958E+09 | 725.33 | 0.315321E+10 | 0.170530E+09 | 0.00 | 0.36 | 0.00 | 3176.30 | 3151.42 | 452.43 | 863.57 | 0.00 |
Report: DXReportMonthly
For: SPLIT MN2 COOLING COIL
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 |
| May | 0.662279E+09 | 0.174579E+09 | 315.93 | 0.662279E+09 | -0.0 | 0.00 | 0.23 | 31-MAY-17:20 | 0.00 | 01-MAY-00:10 | 1986.16 | 31-MAY-17:20 | 1986.16 | 31-MAY-17:20 | 0.00 | 12-MAY-15:10 | 512.74 | 31-MAY-17:20 | 0.00 | 01-MAY-00:10 |
| June | 0.291897E+10 | 0.751599E+09 | 691.67 | 0.286718E+10 | 51794847.19 | 0.00 | 0.33 | 29-JUN-20:00 | 0.00 | 01-JUN-02:70 | 3025.95 | 29-JUN-20:00 | 2913.89 | 29-JUN-19:40 | 451.16 | 30-JUN-19:20 | 783.39 | 30-JUN-15:00 | 0.00 | 01-JUN-00:10 |
| July | 0.334966E+10 | 0.854371E+09 | 725.17 | 0.317811E+10 | 0.171551E+09 | 0.00 | 0.36 | 21-JUL-16:04 | 0.00 | 03-JUL-02:20 | 3182.86 | 29-JUL-17:10 | 3167.19 | 21-JUL-16:04 | 395.88 | 17-JUL-19:30 | 865.06 | 29-JUL-17:00 | 0.00 | 01-JUL-00:10 |
| August | 0.170922E+10 | 0.438784E+09 | 577.78 | 0.164695E+10 | 62268820.68 | 0.00 | 0.28 | 11-AUG-17:40 | 0.00 | 07-AUG-02:50 | 2470.13 | 11-AUG-18:00 | 2470.13 | 11-AUG-18:00 | 290.30 | 12-AUG-21:05 | 642.26 | 11-AUG-17:40 | 0.00 | 01-AUG-00:10 |
| September | 15632.28 | 4142.90 | 0.17 | 15632.28 | 0.00 | 0.00 | 0.00 | 02-SEP-19:30 | 0.00 | 01-SEP-00:10 | 26.05 | 02-SEP-19:30 | 26.05 | 02-SEP-19:30 | 0.00 | 01-SEP-00:10 | 6.90 | 02-SEP-19:30 | 0.00 | 01-SEP-00:10 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.864015E+10 | 0.221934E+10 | 2310.72 | 0.835454E+10 | 0.285614E+09 | 0.00 | ||||||||||||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | -0.0 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Maximum of Months | 0.334966E+10 | 0.854371E+09 | 725.17 | 0.317811E+10 | 0.171551E+09 | 0.00 | 0.36 | 0.00 | 3182.86 | 3167.19 | 451.16 | 865.06 | 0.00 |
Report: DXReportMonthly
For: SPLIT MS1 COOLING COIL
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
| April | 0.502393E+09 | 0.131472E+09 | 121.86 | 0.502393E+09 | 0.00 | 0.00 | 0.31 | 22-APR-13:50 | 0.00 | 01-APR-00:10 | 3324.84 | 22-APR-13:50 | 3324.84 | 22-APR-13:50 | 0.00 | 20-APR-13:30 | 850.22 | 22-APR-13:50 | 0.00 | 01-APR-00:10 |
| May | 0.226228E+10 | 0.588975E+09 | 473.29 | 0.226228E+10 | 0.00 | 0.00 | 0.36 | 12-MAY-13:30 | 0.00 | 01-MAY-00:10 | 3906.00 | 12-MAY-13:30 | 3906.00 | 12-MAY-13:30 | 0.00 | 10-MAY-16:10 | 991.34 | 12-MAY-13:30 | 0.00 | 01-MAY-00:10 |
| June | 0.393011E+10 | 0.100880E+10 | 697.21 | 0.387280E+10 | 57302918.58 | 0.00 | 0.40 | 30-JUN-12:30 | 0.00 | 02-JUN-00:50 | 4678.92 | 30-JUN-12:30 | 4486.24 | 29-JUN-14:30 | 513.95 | 30-JUN-19:00 | 1187.68 | 30-JUN-14:30 | 0.00 | 01-JUN-00:10 |
| July | 0.461868E+10 | 0.117294E+10 | 729.56 | 0.441159E+10 | 0.207090E+09 | 0.00 | 0.47 | 29-JUL-15:30 | 0.00 | 05-JUL-00:30 | 5296.56 | 29-JUL-15:30 | 5196.87 | 29-JUL-15:20 | 431.79 | 17-JUL-19:30 | 1409.80 | 29-JUL-15:30 | 0.00 | 01-JUL-00:10 |
| August | 0.349145E+10 | 0.889142E+09 | 669.00 | 0.340591E+10 | 85538720.50 | 0.00 | 0.44 | 11-AUG-15:10 | 0.00 | 09-AUG-03:40 | 4943.66 | 11-AUG-15:10 | 4943.66 | 11-AUG-15:10 | 352.40 | 12-AUG-21:05 | 1239.00 | 11-AUG-15:20 | 0.00 | 01-AUG-00:10 |
| September | 0.748887E+09 | 0.195029E+09 | 221.02 | 0.748887E+09 | 0.00 | 0.00 | 0.29 | 09-SEP-15:20 | 0.00 | 01-SEP-00:10 | 3197.62 | 09-SEP-15:20 | 3197.62 | 09-SEP-15:20 | 0.00 | 02-SEP-15:10 | 812.89 | 09-SEP-15:20 | 0.00 | 01-SEP-00:10 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.155538E+11 | 0.398635E+10 | 2911.94 | 0.152039E+11 | 0.349932E+09 | 0.00 | ||||||||||||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Maximum of Months | 0.461868E+10 | 0.117294E+10 | 729.56 | 0.441159E+10 | 0.207090E+09 | 0.00 | 0.47 | 0.00 | 5296.56 | 5196.87 | 513.95 | 1409.80 | 0.00 |
Report: DXReportMonthly
For: SPLIT MS2 COOLING COIL
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
| April | 0.507757E+09 | 0.132868E+09 | 123.86 | 0.507757E+09 | -0.0 | 0.00 | 0.31 | 22-APR-13:50 | 0.00 | 01-APR-00:10 | 3345.46 | 22-APR-13:50 | 3345.46 | 22-APR-13:50 | 0.00 | 22-APR-14:40 | 855.15 | 22-APR-13:50 | 0.00 | 01-APR-00:10 |
| May | 0.230053E+10 | 0.598762E+09 | 476.99 | 0.230053E+10 | 0.00 | 0.00 | 0.36 | 12-MAY-13:30 | 0.00 | 01-MAY-00:10 | 3947.30 | 12-MAY-13:30 | 3947.30 | 12-MAY-13:30 | 0.00 | 13-MAY-17:00 | 1001.12 | 12-MAY-13:30 | 0.00 | 01-MAY-00:10 |
| June | 0.394846E+10 | 0.101336E+10 | 697.42 | 0.389123E+10 | 57230829.15 | 0.00 | 0.41 | 30-JUN-12:30 | 0.00 | 02-JUN-00:50 | 4696.84 | 30-JUN-12:30 | 4503.91 | 29-JUN-14:30 | 512.87 | 30-JUN-19:00 | 1189.78 | 30-JUN-14:30 | 0.00 | 01-JUN-00:10 |
| July | 0.464431E+10 | 0.117917E+10 | 729.32 | 0.443636E+10 | 0.207948E+09 | 0.00 | 0.47 | 29-JUL-15:30 | 0.00 | 05-JUL-00:20 | 5310.42 | 29-JUL-15:30 | 5213.09 | 29-JUL-15:20 | 432.25 | 17-JUL-19:30 | 1412.99 | 29-JUL-15:30 | 0.00 | 01-JUL-00:10 |
| August | 0.351312E+10 | 0.894521E+09 | 671.42 | 0.342728E+10 | 85846302.04 | 0.00 | 0.44 | 11-AUG-15:10 | 0.00 | 09-AUG-03:50 | 4956.61 | 11-AUG-15:10 | 4956.61 | 11-AUG-15:10 | 352.68 | 12-AUG-21:05 | 1241.24 | 11-AUG-15:20 | 0.00 | 01-AUG-00:10 |
| September | 0.766712E+09 | 0.199618E+09 | 225.30 | 0.766712E+09 | -0.0 | 0.00 | 0.29 | 09-SEP-15:20 | 0.00 | 01-SEP-00:10 | 3224.06 | 09-SEP-15:20 | 3224.06 | 09-SEP-15:20 | 0.00 | 09-SEP-14:00 | 819.23 | 09-SEP-15:20 | 0.00 | 01-SEP-00:10 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.156809E+11 | 0.401830E+10 | 2924.30 | 0.153299E+11 | 0.351025E+09 | 0.00 | ||||||||||||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | -0.0 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Maximum of Months | 0.464431E+10 | 0.117917E+10 | 729.32 | 0.443636E+10 | 0.207948E+09 | 0.00 | 0.47 | 0.00 | 5310.42 | 5213.09 | 512.87 | 1412.99 | 0.00 |
Report: DXReportMonthly
For: SPLIT TSW COOLING COIL
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
| March | 474252.28 | 126962.47 | 1.67 | 474252.28 | -0.0 | 0.00 | 0.02 | 22-MAR-15:20 | 0.00 | 01-MAR-00:10 | 125.94 | 22-MAR-15:20 | 125.94 | 22-MAR-15:20 | 0.00 | 22-MAR-16:08 | 33.69 | 22-MAR-15:20 | 0.00 | 01-MAR-00:10 |
| April | 0.399648E+09 | 0.104367E+09 | 120.00 | 0.399648E+09 | 0.00 | 0.00 | 0.34 | 21-APR-16:30 | 0.00 | 01-APR-00:10 | 2483.19 | 21-APR-16:30 | 2483.19 | 21-APR-16:30 | 0.00 | 20-APR-17:10 | 634.44 | 21-APR-16:30 | 0.00 | 01-APR-00:10 |
| May | 0.102786E+10 | 0.266924E+09 | 286.61 | 0.102786E+10 | 0.00 | 0.00 | 0.42 | 31-MAY-15:40 | 0.00 | 01-MAY-00:10 | 3212.85 | 31-MAY-15:40 | 3212.85 | 31-MAY-15:40 | 0.00 | 10-MAY-16:25 | 804.42 | 31-MAY-15:40 | 0.00 | 01-MAY-00:10 |
| June | 0.211994E+10 | 0.541122E+09 | 482.77 | 0.209383E+10 | 26110911.81 | 0.00 | 0.48 | 20-JUN-16:08 | 0.00 | 01-JUN-00:10 | 3765.70 | 20-JUN-16:05 | 3765.70 | 20-JUN-16:05 | 354.89 | 30-JUN-18:50 | 947.74 | 20-JUN-16:15 | 0.00 | 01-JUN-00:10 |
| July | 0.242527E+10 | 0.613956E+09 | 502.43 | 0.234614E+10 | 79131396.80 | 0.00 | 0.54 | 29-JUL-15:40 | 0.00 | 01-JUL-01:40 | 4228.66 | 29-JUL-15:40 | 4150.60 | 29-JUL-15:30 | 260.57 | 08-JUL-17:35 | 1114.30 | 29-JUL-15:40 | 0.00 | 01-JUL-00:10 |
| August | 0.152804E+10 | 0.387379E+09 | 372.83 | 0.150239E+10 | 25651660.44 | 0.00 | 0.49 | 10-AUG-16:10 | 0.00 | 01-AUG-02:70 | 3790.29 | 10-AUG-16:10 | 3790.29 | 10-AUG-16:10 | 197.10 | 04-AUG-11:20 | 949.84 | 11-AUG-16:06 | 0.00 | 01-AUG-00:10 |
| September | 0.217503E+09 | 56622141.85 | 86.83 | 0.217503E+09 | 0.00 | 0.00 | 0.29 | 09-SEP-16:07 | 0.00 | 01-SEP-00:10 | 2148.99 | 09-SEP-16:07 | 2148.99 | 09-SEP-16:07 | 0.00 | 02-SEP-17:05 | 546.87 | 09-SEP-16:07 | 0.00 | 01-SEP-00:10 |
| October | 2798510.98 | 742046.97 | 2.67 | 2798510.98 | 0.00 | 0.00 | 0.06 | 03-OCT-14:40 | 0.00 | 01-OCT-00:10 | 460.05 | 03-OCT-14:40 | 460.05 | 03-OCT-14:40 | 0.00 | 03-OCT-15:10 | 121.71 | 03-OCT-14:40 | 0.00 | 01-OCT-00:10 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.772153E+10 | 0.197124E+10 | 1855.81 | 0.759063E+10 | 0.130894E+09 | 0.00 | ||||||||||||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | -0.0 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Maximum of Months | 0.242527E+10 | 0.613956E+09 | 502.43 | 0.234614E+10 | 79131396.80 | 0.00 | 0.54 | 0.00 | 4228.66 | 4150.60 | 354.89 | 1114.30 | 0.00 |
Report: DXReportMonthly
For: SPLIT TNW COOLING COIL
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
| April | 22393702.06 | 5941943.53 | 17.55 | 22393702.06 | 0.00 | 0.00 | 0.13 | 21-APR-18:00 | 0.00 | 01-APR-00:10 | 810.85 | 21-APR-18:00 | 810.85 | 21-APR-18:00 | 0.00 | 21-APR-17:17 | 213.71 | 21-APR-18:00 | 0.00 | 01-APR-00:10 |
| May | 0.301016E+09 | 78921794.95 | 156.01 | 0.301016E+09 | -0.0 | 0.00 | 0.31 | 31-MAY-16:20 | 0.00 | 01-MAY-00:10 | 2034.84 | 31-MAY-16:20 | 2034.84 | 31-MAY-16:20 | 0.00 | 10-MAY-19:10 | 518.66 | 31-MAY-16:20 | 0.00 | 01-MAY-00:10 |
| June | 0.155319E+10 | 0.398529E+09 | 499.27 | 0.152809E+10 | 25099128.03 | 0.00 | 0.42 | 20-JUN-17:40 | 0.00 | 01-JUN-00:10 | 2844.36 | 20-JUN-17:30 | 2844.36 | 20-JUN-17:30 | 329.17 | 30-JUN-19:00 | 730.93 | 20-JUN-17:40 | 0.00 | 01-JUN-00:10 |
| July | 0.173498E+10 | 0.442615E+09 | 512.78 | 0.167041E+10 | 64569308.42 | 0.00 | 0.44 | 11-JUL-18:00 | 0.00 | 01-JUL-01:20 | 3038.97 | 11-JUL-17:50 | 3038.97 | 11-JUL-17:50 | 231.50 | 08-JUL-18:00 | 770.63 | 11-JUL-17:50 | 0.00 | 01-JUL-00:10 |
| August | 0.703623E+09 | 0.180204E+09 | 280.64 | 0.685912E+09 | 17711272.12 | 0.00 | 0.36 | 11-AUG-17:25 | 0.00 | 01-AUG-01:30 | 2370.81 | 11-AUG-17:30 | 2370.81 | 11-AUG-17:30 | 150.80 | 03-AUG-15:10 | 609.12 | 11-AUG-17:30 | 0.00 | 01-AUG-00:10 |
| September | 964923.47 | 255140.83 | 2.58 | 964923.47 | -0.0 | 0.00 | 0.03 | 02-SEP-19:10 | 0.00 | 01-SEP-00:10 | 208.98 | 02-SEP-19:10 | 208.98 | 02-SEP-19:10 | 0.00 | 09-SEP-17:30 | 55.13 | 02-SEP-19:10 | 0.00 | 01-SEP-00:10 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.431617E+10 | 0.110647E+10 | 1468.83 | 0.420879E+10 | 0.107380E+09 | 0.00 | ||||||||||||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | -0.0 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Maximum of Months | 0.173498E+10 | 0.442615E+09 | 512.78 | 0.167041E+10 | 64569308.42 | 0.00 | 0.44 | 0.00 | 3038.97 | 3038.97 | 329.17 | 770.63 | 0.00 |
Report: DXReportMonthly
For: SPLIT TSE COOLING COIL
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
| March | 1704068.65 | 454827.12 | 3.17 | 1704068.65 | -0.0 | 0.00 | 0.05 | 22-MAR-14:40 | 0.00 | 01-MAR-00:10 | 262.60 | 22-MAR-14:40 | 262.60 | 22-MAR-14:40 | 0.00 | 22-MAR-15:10 | 69.96 | 22-MAR-14:40 | 0.00 | 01-MAR-00:10 |
| April | 0.355358E+09 | 92516931.32 | 117.43 | 0.355358E+09 | 0.00 | 0.00 | 0.38 | 22-APR-13:40 | 0.00 | 01-APR-00:10 | 2307.21 | 22-APR-13:40 | 2307.21 | 22-APR-13:40 | 0.00 | 22-APR-12:40 | 583.35 | 22-APR-13:40 | 0.00 | 01-APR-00:10 |
| May | 0.125918E+10 | 0.324233E+09 | 334.86 | 0.125918E+10 | -0.0 | 0.00 | 0.48 | 31-MAY-14:10 | 0.00 | 01-MAY-00:10 | 2995.01 | 31-MAY-14:10 | 2995.01 | 31-MAY-14:10 | 0.00 | 31-MAY-17:10 | 741.85 | 31-MAY-14:10 | 0.00 | 01-MAY-00:10 |
| June | 0.229930E+10 | 0.582724E+09 | 521.54 | 0.227359E+10 | 25711519.22 | 0.00 | 0.56 | 29-JUN-14:10 | 0.00 | 01-JUN-00:10 | 3637.74 | 30-JUN-12:30 | 3584.88 | 29-JUN-14:10 | 301.13 | 30-JUN-19:00 | 899.16 | 30-JUN-12:30 | 0.00 | 01-JUN-00:10 |
| July | 0.272785E+10 | 0.682787E+09 | 545.74 | 0.263787E+10 | 89971720.89 | 0.00 | 0.62 | 22-JUL-11:40 | 0.00 | 01-JUL-01:30 | 4103.89 | 22-JUL-11:40 | 3974.40 | 23-JUL-13:30 | 252.08 | 19-JUL-12:20 | 1025.61 | 29-JUL-15:30 | 0.00 | 01-JUL-00:10 |
| August | 0.167909E+10 | 0.422067E+09 | 406.13 | 0.165026E+10 | 28832651.87 | 0.00 | 0.55 | 10-AUG-14:10 | 0.00 | 01-AUG-01:40 | 3521.01 | 10-AUG-14:10 | 3521.01 | 10-AUG-14:10 | 229.72 | 04-AUG-11:00 | 858.31 | 10-AUG-14:10 | 0.00 | 01-AUG-00:10 |
| September | 0.238649E+09 | 62010767.72 | 97.00 | 0.238649E+09 | -0.0 | 0.00 | 0.30 | 09-SEP-15:20 | 0.00 | 01-SEP-00:10 | 1826.59 | 09-SEP-15:20 | 1826.59 | 09-SEP-15:20 | 0.00 | 09-SEP-13:30 | 463.83 | 09-SEP-15:20 | 0.00 | 01-SEP-00:10 |
| October | 4816968.30 | 1272084.63 | 3.83 | 4816968.30 | -0.0 | 0.00 | 0.10 | 03-OCT-14:30 | 0.00 | 01-OCT-00:10 | 582.80 | 03-OCT-14:30 | 582.80 | 03-OCT-14:30 | 0.00 | 03-OCT-14:00 | 153.34 | 03-OCT-14:30 | 0.00 | 01-OCT-00:10 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.856595E+10 | 0.216807E+10 | 2029.71 | 0.842144E+10 | 0.144516E+09 | 0.00 | ||||||||||||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | -0.0 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Maximum of Months | 0.272785E+10 | 0.682787E+09 | 545.74 | 0.263787E+10 | 89971720.89 | 0.00 | 0.62 | 0.00 | 4103.89 | 3974.40 | 301.13 | 1025.61 | 0.00 |
Report: DXReportMonthly
For: SPLIT TNE COOLING COIL
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
| April | 401408.02 | 107618.54 | 3.30 | 401408.02 | 0.00 | 0.00 | 0.03 | 22-APR-16:05 | 0.00 | 01-APR-00:10 | 135.97 | 22-APR-16:05 | 135.97 | 22-APR-16:05 | 0.00 | 22-APR-13:10 | 36.36 | 22-APR-16:05 | 0.00 | 01-APR-00:10 |
| May | 0.438258E+09 | 0.114578E+09 | 242.08 | 0.438258E+09 | -0.0 | 0.00 | 0.32 | 31-MAY-11:00 | 0.00 | 01-MAY-00:10 | 1640.03 | 31-MAY-11:00 | 1640.03 | 31-MAY-11:00 | 0.00 | 31-MAY-15:40 | 415.66 | 31-MAY-11:00 | 0.00 | 01-MAY-00:10 |
| June | 0.175540E+10 | 0.447779E+09 | 530.67 | 0.173091E+10 | 24491428.83 | 0.00 | 0.45 | 29-JUN-11:00 | 0.00 | 01-JUN-00:10 | 2493.05 | 29-JUN-11:00 | 2365.75 | 29-JUN-11:00 | 273.81 | 30-JUN-19:00 | 606.26 | 29-JUN-11:00 | 0.00 | 01-JUN-00:10 |
| July | 0.205088E+10 | 0.517673E+09 | 545.81 | 0.197441E+10 | 76475614.25 | 0.00 | 0.49 | 22-JUL-10:50 | 0.00 | 01-JUL-01:10 | 2688.25 | 22-JUL-10:50 | 2530.47 | 22-JUL-10:50 | 176.40 | 19-JUL-12:20 | 659.36 | 21-JUL-16:00 | 0.00 | 01-JUL-00:10 |
| August | 0.824835E+09 | 0.210347E+09 | 326.05 | 0.803639E+09 | 21196251.49 | 0.00 | 0.33 | 11-AUG-16:15 | 0.00 | 01-AUG-01:00 | 1696.79 | 02-AUG-16:04 | 1692.59 | 11-AUG-16:15 | 159.93 | 04-AUG-11:10 | 437.16 | 11-AUG-16:15 | 0.00 | 01-AUG-00:10 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.506978E+10 | 0.129048E+10 | 1647.91 | 0.494762E+10 | 0.122163E+09 | 0.00 | ||||||||||||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | -0.0 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Maximum of Months | 0.205088E+10 | 0.517673E+09 | 545.81 | 0.197441E+10 | 76475614.25 | 0.00 | 0.49 | 0.00 | 2688.25 | 2530.47 | 273.81 | 659.36 | 0.00 |
Report: DXReportMonthly
For: SPLIT TN1 COOLING COIL
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 |
| May | 0.147075E+09 | 38668988.22 | 133.74 | 0.147075E+09 | -0.0 | 0.00 | 0.27 | 31-MAY-16:17 | 0.00 | 01-MAY-00:10 | 1295.64 | 31-MAY-16:17 | 1295.64 | 31-MAY-16:17 | 0.00 | 31-MAY-15:30 | 332.33 | 31-MAY-16:17 | 0.00 | 01-MAY-00:10 |
| June | 0.121912E+10 | 0.313502E+09 | 552.98 | 0.119688E+10 | 22244130.62 | 0.00 | 0.37 | 30-JUN-15:00 | 0.00 | 01-JUN-00:10 | 1817.64 | 30-JUN-15:10 | 1771.18 | 30-JUN-15:00 | 249.36 | 30-JUN-19:00 | 480.89 | 30-JUN-15:00 | 0.00 | 01-JUN-00:10 |
| July | 0.144369E+10 | 0.368104E+09 | 568.13 | 0.138011E+10 | 63582615.71 | 0.00 | 0.40 | 29-JUL-16:40 | 0.00 | 01-JUL-01:50 | 1967.90 | 29-JUL-17:10 | 1907.36 | 21-JUL-16:04 | 174.55 | 17-JUL-19:40 | 531.38 | 29-JUL-16:40 | 0.00 | 01-JUL-00:10 |
| August | 0.555736E+09 | 0.142401E+09 | 310.34 | 0.537241E+09 | 18494194.42 | 0.00 | 0.29 | 11-AUG-17:40 | 0.00 | 01-AUG-01:40 | 1405.41 | 02-AUG-17:20 | 1403.36 | 02-AUG-17:20 | 132.62 | 03-AUG-15:10 | 363.88 | 11-AUG-17:40 | 0.00 | 01-AUG-00:10 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.336563E+10 | 0.862676E+09 | 1565.19 | 0.326131E+10 | 0.104321E+09 | 0.00 | ||||||||||||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | -0.0 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Maximum of Months | 0.144369E+10 | 0.368104E+09 | 568.13 | 0.138011E+10 | 63582615.71 | 0.00 | 0.40 | 0.00 | 1967.90 | 1907.36 | 249.36 | 531.38 | 0.00 |
Report: DXReportMonthly
For: SPLIT TN2 COOLING COIL
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 |
| May | 0.159122E+09 | 41839576.92 | 144.65 | 0.159122E+09 | -0.0 | 0.00 | 0.27 | 31-MAY-16:17 | 0.00 | 01-MAY-00:10 | 1293.04 | 31-MAY-16:17 | 1293.04 | 31-MAY-16:17 | 0.00 | 31-MAY-14:10 | 331.59 | 31-MAY-16:17 | 0.00 | 01-MAY-00:10 |
| June | 0.123118E+10 | 0.316559E+09 | 553.45 | 0.120900E+10 | 22180483.72 | 0.00 | 0.37 | 30-JUN-15:00 | 0.00 | 01-JUN-00:10 | 1822.36 | 30-JUN-15:00 | 1776.33 | 30-JUN-15:00 | 247.57 | 30-JUN-19:00 | 481.92 | 30-JUN-15:00 | 0.00 | 01-JUN-00:10 |
| July | 0.146070E+10 | 0.372294E+09 | 571.00 | 0.139646E+10 | 64235683.55 | 0.00 | 0.40 | 29-JUL-16:40 | 0.00 | 01-JUL-01:50 | 1965.14 | 29-JUL-16:40 | 1912.30 | 21-JUL-16:02 | 174.07 | 17-JUL-19:40 | 530.60 | 29-JUL-16:40 | 0.00 | 01-JUL-00:10 |
| August | 0.567600E+09 | 0.145416E+09 | 315.24 | 0.548846E+09 | 18753886.23 | 0.00 | 0.29 | 11-AUG-17:30 | 0.00 | 01-AUG-01:40 | 1399.82 | 02-AUG-17:20 | 1397.83 | 02-AUG-17:20 | 132.75 | 03-AUG-15:10 | 361.22 | 11-AUG-17:30 | 0.00 | 01-AUG-00:10 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.341860E+10 | 0.876109E+09 | 1584.35 | 0.331343E+10 | 0.105170E+09 | 0.00 | ||||||||||||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | -0.0 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Maximum of Months | 0.146070E+10 | 0.372294E+09 | 571.00 | 0.139646E+10 | 64235683.55 | 0.00 | 0.40 | 0.00 | 1965.14 | 1912.30 | 247.57 | 530.60 | 0.00 |
Report: DXReportMonthly
For: SPLIT TS1 COOLING COIL
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
| March | 475832.66 | 127318.77 | 1.83 | 475832.66 | 0.00 | 0.00 | 0.02 | 22-MAR-15:10 | 0.00 | 01-MAR-00:10 | 126.62 | 22-MAR-15:10 | 126.62 | 22-MAR-15:10 | 0.00 | 22-MAR-15:30 | 33.85 | 22-MAR-15:10 | 0.00 | 01-MAR-00:10 |
| April | 0.308249E+09 | 80507948.44 | 121.46 | 0.308249E+09 | 0.00 | 0.00 | 0.34 | 20-APR-14:40 | 0.00 | 01-APR-00:10 | 1929.25 | 20-APR-14:40 | 1929.25 | 20-APR-14:40 | 0.00 | 22-APR-15:40 | 491.86 | 20-APR-14:40 | 0.00 | 01-APR-00:10 |
| May | 0.879101E+09 | 0.228062E+09 | 306.45 | 0.879101E+09 | 0.00 | 0.00 | 0.43 | 31-MAY-15:10 | 0.00 | 01-MAY-00:10 | 2542.98 | 31-MAY-15:10 | 2542.98 | 31-MAY-15:10 | 0.00 | 31-MAY-14:20 | 635.62 | 31-MAY-15:10 | 0.00 | 01-MAY-00:10 |
| June | 0.177637E+10 | 0.453200E+09 | 524.70 | 0.175254E+10 | 23832000.54 | 0.00 | 0.50 | 29-JUN-14:30 | 0.00 | 01-JUN-00:50 | 3049.56 | 29-JUN-14:30 | 3018.13 | 29-JUN-14:30 | 278.05 | 30-JUN-19:00 | 762.62 | 29-JUN-14:30 | 0.00 | 01-JUN-00:10 |
| July | 0.213421E+10 | 0.538603E+09 | 556.63 | 0.205548E+10 | 78731460.49 | 0.00 | 0.57 | 29-JUL-15:30 | 0.00 | 01-JUL-02:20 | 3450.14 | 29-JUL-15:30 | 3392.71 | 29-JUL-15:20 | 224.32 | 19-JUL-12:30 | 904.07 | 29-JUL-15:30 | 0.00 | 01-JUL-00:10 |
| August | 0.139784E+10 | 0.353308E+09 | 415.46 | 0.137020E+10 | 27639414.08 | 0.00 | 0.50 | 11-AUG-15:10 | 0.00 | 01-AUG-02:30 | 3053.91 | 11-AUG-15:10 | 3053.91 | 11-AUG-15:10 | 193.94 | 04-AUG-11:20 | 757.17 | 11-AUG-15:20 | 0.00 | 01-AUG-00:10 |
| September | 0.206126E+09 | 53631870.33 | 98.17 | 0.206126E+09 | 0.00 | 0.00 | 0.30 | 09-SEP-15:20 | 0.00 | 01-SEP-00:10 | 1734.88 | 09-SEP-15:20 | 1734.88 | 09-SEP-15:20 | 0.00 | 09-SEP-14:10 | 440.67 | 09-SEP-15:20 | 0.00 | 01-SEP-00:10 |
| October | 5264220.39 | 1388738.12 | 3.83 | 5264220.39 | 0.00 | 0.00 | 0.11 | 03-OCT-14:30 | 0.00 | 01-OCT-00:10 | 620.66 | 03-OCT-14:30 | 620.66 | 03-OCT-14:30 | 0.00 | 03-OCT-14:30 | 163.03 | 03-OCT-14:30 | 0.00 | 01-OCT-00:10 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.670764E+10 | 0.170883E+10 | 2028.53 | 0.657744E+10 | 0.130203E+09 | 0.00 | ||||||||||||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Maximum of Months | 0.213421E+10 | 0.538603E+09 | 556.63 | 0.205548E+10 | 78731460.49 | 0.00 | 0.57 | 0.00 | 3450.14 | 3392.71 | 278.05 | 904.07 | 0.00 |
Report: DXReportMonthly
For: SPLIT TS2 COOLING COIL
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
| March | 741777.06 | 198331.81 | 2.17 | 741777.06 | 0.00 | 0.00 | 0.03 | 22-MAR-15:10 | 0.00 | 01-MAR-00:10 | 161.03 | 22-MAR-15:10 | 161.03 | 22-MAR-15:10 | 0.00 | 22-MAR-15:30 | 43.01 | 22-MAR-15:10 | 0.00 | 01-MAR-00:10 |
| April | 0.313880E+09 | 81948682.97 | 121.88 | 0.313880E+09 | 0.00 | 0.00 | 0.34 | 22-APR-14:00 | 0.00 | 01-APR-00:10 | 1954.71 | 22-APR-14:00 | 1954.71 | 22-APR-14:00 | 0.00 | 20-APR-15:00 | 497.35 | 22-APR-14:00 | 0.00 | 01-APR-00:10 |
| May | 0.903609E+09 | 0.234284E+09 | 313.69 | 0.903609E+09 | -0.0 | 0.00 | 0.43 | 31-MAY-15:10 | 0.00 | 01-MAY-00:10 | 2551.45 | 31-MAY-15:10 | 2551.45 | 31-MAY-15:10 | 0.00 | 31-MAY-15:20 | 637.34 | 31-MAY-15:10 | 0.00 | 01-MAY-00:10 |
| June | 0.179076E+10 | 0.456721E+09 | 527.61 | 0.176696E+10 | 23792732.35 | 0.00 | 0.50 | 29-JUN-14:30 | 0.00 | 01-JUN-00:50 | 3064.42 | 29-JUN-14:30 | 3033.22 | 29-JUN-14:30 | 276.37 | 30-JUN-19:00 | 765.70 | 29-JUN-14:30 | 0.00 | 01-JUN-00:10 |
| July | 0.215219E+10 | 0.542876E+09 | 558.74 | 0.207283E+10 | 79352818.66 | 0.00 | 0.57 | 29-JUL-15:30 | 0.00 | 01-JUL-02:20 | 3456.15 | 29-JUL-15:30 | 3401.15 | 29-JUL-15:20 | 225.32 | 19-JUL-12:30 | 905.03 | 29-JUL-15:30 | 0.00 | 01-JUL-00:10 |
| August | 0.141274E+10 | 0.356930E+09 | 419.18 | 0.138489E+10 | 27848815.78 | 0.00 | 0.51 | 11-AUG-15:10 | 0.00 | 01-AUG-02:30 | 3062.93 | 11-AUG-15:10 | 3062.93 | 11-AUG-15:10 | 195.22 | 04-AUG-11:20 | 758.46 | 11-AUG-15:20 | 0.00 | 01-AUG-00:10 |
| September | 0.212072E+09 | 55164182.38 | 99.92 | 0.212072E+09 | 0.00 | 0.00 | 0.30 | 09-SEP-15:20 | 0.00 | 01-SEP-00:10 | 1749.84 | 09-SEP-15:20 | 1749.84 | 09-SEP-15:20 | 0.00 | 09-SEP-16:07 | 444.17 | 09-SEP-15:20 | 0.00 | 01-SEP-00:10 |
| October | 5702773.90 | 1503370.00 | 4.00 | 5702773.90 | 0.00 | 0.00 | 0.12 | 03-OCT-14:30 | 0.00 | 01-OCT-00:10 | 652.04 | 03-OCT-14:30 | 652.04 | 03-OCT-14:30 | 0.00 | 03-OCT-14:20 | 171.11 | 03-OCT-14:30 | 0.00 | 01-OCT-00:10 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.679169E+10 | 0.172963E+10 | 2047.19 | 0.666070E+10 | 0.130994E+09 | 0.00 | ||||||||||||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | -0.0 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Maximum of Months | 0.215219E+10 | 0.542876E+09 | 558.74 | 0.207283E+10 | 79352818.66 | 0.00 | 0.57 | 0.00 | 3456.15 | 3401.15 | 276.37 | 905.03 | 0.00 |
Report: WindowReportMonthly
For: GWINDOW1 S SWA
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 62.86 | 41.89 | 20.97 | 35.80 | 350.74 | 0.00 | 0.00 | 0.00 |
| February | 210.30 | 146.25 | 64.06 | 176.08 | 278.87 | 0.00 | 0.00 | 0.00 |
| March | 356.49 | 240.42 | 116.08 | 350.25 | 210.88 | 0.00 | 0.00 | 0.00 |
| April | 442.26 | 276.03 | 166.22 | 489.28 | 131.63 | 0.00 | 0.00 | 0.00 |
| May | 362.92 | 188.15 | 174.77 | 415.32 | 67.08 | 0.00 | 0.00 | 0.00 |
| June | 331.84 | 136.41 | 195.43 | 385.72 | 36.81 | 0.00 | 0.00 | 0.00 |
| July | 319.80 | 139.68 | 180.11 | 379.89 | 39.94 | 0.00 | 0.00 | 0.00 |
| August | 330.90 | 182.57 | 148.33 | 384.72 | 61.91 | 0.00 | 0.00 | 0.00 |
| September | 263.41 | 157.17 | 106.24 | 278.90 | 107.43 | 0.00 | 0.00 | 0.00 |
| October | 193.59 | 122.71 | 70.88 | 176.09 | 182.77 | 0.00 | 0.00 | 0.00 |
| November | 104.52 | 73.34 | 31.18 | 66.74 | 327.80 | 0.00 | 0.00 | 0.00 |
| December | 18.41 | 12.95 | 5.45 | 3.13 | 392.12 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 249.71 | 142.91 | 106.79 | 262.06 | 181.88 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 18.41 | 12.95 | 5.45 | 3.13 | 36.81 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 442.26 | 276.03 | 195.43 | 489.28 | 392.12 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: GWINDOW1 W SWA
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 4.63 | 0.81 | 3.82 | 0.00 | 254.92 | 0.00 | 0.00 | 0.00 |
| February | 27.54 | 9.65 | 17.89 | 5.35 | 216.16 | 0.00 | 0.00 | 0.00 |
| March | 82.77 | 35.84 | 46.93 | 47.58 | 154.75 | 0.00 | 0.00 | 0.00 |
| April | 195.26 | 101.23 | 94.03 | 189.91 | 85.06 | 0.00 | 0.00 | 0.00 |
| May | 189.63 | 86.39 | 103.24 | 197.20 | 40.45 | 0.00 | 0.00 | 0.00 |
| June | 207.92 | 88.75 | 119.18 | 230.91 | 21.93 | 0.00 | 0.00 | 0.00 |
| July | 173.76 | 65.68 | 108.08 | 194.08 | 24.52 | 0.00 | 0.00 | 0.00 |
| August | 143.25 | 60.87 | 82.38 | 149.96 | 39.13 | 0.00 | 0.00 | 0.00 |
| September | 86.32 | 36.03 | 50.29 | 70.17 | 72.55 | 0.00 | 0.00 | 0.00 |
| October | 33.80 | 10.12 | 23.68 | 12.42 | 138.19 | 0.00 | 0.00 | 0.00 |
| November | 13.55 | 4.91 | 8.64 | 1.23 | 243.30 | 0.00 | 0.00 | 0.00 |
| December | 1.22 | 0.13 | 1.09 | 0.00 | 270.24 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 96.89 | 41.79 | 55.10 | 91.93 | 129.66 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 1.22 | 0.13 | 1.09 | 0.00 | 21.93 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 207.92 | 101.23 | 119.18 | 230.91 | 270.24 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: GWINDOW1 W NWA
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 4.63 | 0.81 | 3.82 | 0.00 | 254.35 | 0.00 | 0.00 | 0.00 |
| February | 27.54 | 9.65 | 17.89 | 5.58 | 214.53 | 0.00 | 0.00 | 0.00 |
| March | 82.77 | 35.84 | 46.93 | 48.68 | 152.62 | 0.00 | 0.00 | 0.00 |
| April | 195.26 | 101.23 | 94.03 | 193.92 | 82.59 | 0.00 | 0.00 | 0.00 |
| May | 189.63 | 86.39 | 103.24 | 202.58 | 37.61 | 0.00 | 0.00 | 0.00 |
| June | 207.92 | 88.75 | 119.18 | 232.90 | 21.17 | 0.00 | 0.00 | 0.00 |
| July | 173.76 | 65.68 | 108.08 | 195.48 | 24.00 | 0.00 | 0.00 | 0.00 |
| August | 143.25 | 60.87 | 82.38 | 152.46 | 37.48 | 0.00 | 0.00 | 0.00 |
| September | 86.32 | 36.03 | 50.29 | 73.92 | 67.75 | 0.00 | 0.00 | 0.00 |
| October | 33.80 | 10.12 | 23.68 | 13.02 | 136.25 | 0.00 | 0.00 | 0.00 |
| November | 13.55 | 4.91 | 8.64 | 1.29 | 242.34 | 0.00 | 0.00 | 0.00 |
| December | 1.22 | 0.13 | 1.09 | 0.00 | 270.03 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 96.89 | 41.79 | 55.10 | 93.69 | 127.96 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 1.22 | 0.13 | 1.09 | 0.00 | 21.17 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 207.92 | 101.23 | 119.18 | 232.90 | 270.03 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: GWINDOW1 N NWA
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 5.09 | 0.00 | 5.09 | 0.00 | 391.14 | 0.00 | 0.00 | 0.00 |
| February | 22.48 | 0.00 | 22.48 | 0.00 | 347.58 | 0.00 | 0.00 | 0.00 |
| March | 60.31 | 0.02 | 60.29 | 5.38 | 253.74 | 0.00 | 0.00 | 0.00 |
| April | 109.72 | 3.07 | 106.66 | 50.72 | 128.47 | 0.00 | 0.00 | 0.00 |
| May | 168.20 | 27.17 | 141.03 | 146.14 | 50.18 | 0.00 | 0.00 | 0.00 |
| June | 216.85 | 47.59 | 169.26 | 219.00 | 24.61 | 0.00 | 0.00 | 0.00 |
| July | 183.01 | 30.11 | 152.90 | 187.04 | 31.15 | 0.00 | 0.00 | 0.00 |
| August | 117.57 | 6.36 | 111.22 | 97.12 | 53.83 | 0.00 | 0.00 | 0.00 |
| September | 65.40 | 0.19 | 65.21 | 27.87 | 107.30 | 0.00 | 0.00 | 0.00 |
| October | 31.65 | 0.00 | 31.65 | 2.51 | 218.59 | 0.00 | 0.00 | 0.00 |
| November | 9.82 | 0.00 | 9.82 | 0.00 | 384.05 | 0.00 | 0.00 | 0.00 |
| December | 1.54 | 0.00 | 1.54 | 0.00 | 411.88 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 82.94 | 9.59 | 73.35 | 61.68 | 199.43 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 1.54 | 0.00 | 1.54 | 0.00 | 24.61 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 216.85 | 47.59 | 169.26 | 219.00 | 411.88 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: GWINDOW1 S SEA
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 62.86 | 41.89 | 20.97 | 38.05 | 315.94 | 0.00 | 0.00 | 0.00 |
| February | 210.30 | 146.25 | 64.06 | 182.28 | 250.18 | 0.00 | 0.00 | 0.00 |
| March | 356.49 | 240.42 | 116.08 | 358.47 | 188.03 | 0.00 | 0.00 | 0.00 |
| April | 442.26 | 276.03 | 166.22 | 494.71 | 120.21 | 0.00 | 0.00 | 0.00 |
| May | 362.92 | 188.15 | 174.77 | 410.78 | 71.77 | 0.00 | 0.00 | 0.00 |
| June | 331.84 | 136.41 | 195.43 | 379.00 | 43.03 | 0.00 | 0.00 | 0.00 |
| July | 319.80 | 139.68 | 180.11 | 370.64 | 48.43 | 0.00 | 0.00 | 0.00 |
| August | 330.90 | 182.57 | 148.33 | 379.26 | 71.12 | 0.00 | 0.00 | 0.00 |
| September | 263.41 | 157.17 | 106.24 | 277.34 | 110.90 | 0.00 | 0.00 | 0.00 |
| October | 193.59 | 122.71 | 70.88 | 180.48 | 166.66 | 0.00 | 0.00 | 0.00 |
| November | 104.52 | 73.34 | 31.18 | 70.43 | 295.94 | 0.00 | 0.00 | 0.00 |
| December | 18.41 | 12.95 | 5.45 | 3.47 | 355.95 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 249.71 | 142.91 | 106.79 | 262.26 | 169.49 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 18.41 | 12.95 | 5.45 | 3.47 | 43.03 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 442.26 | 276.03 | 195.43 | 494.71 | 355.95 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: GWINDOW1 E SEA
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 9.91 | 3.77 | 6.14 | 1.55 | 224.98 | 0.00 | 0.00 | 0.00 |
| February | 50.00 | 24.13 | 25.87 | 27.75 | 185.68 | 0.00 | 0.00 | 0.00 |
| March | 142.82 | 72.14 | 70.68 | 125.72 | 133.12 | 0.00 | 0.00 | 0.00 |
| April | 191.41 | 97.00 | 94.41 | 184.38 | 72.99 | 0.00 | 0.00 | 0.00 |
| May | 278.66 | 157.05 | 121.61 | 307.28 | 40.74 | 0.00 | 0.00 | 0.00 |
| June | 255.59 | 119.26 | 136.33 | 286.11 | 22.55 | 0.00 | 0.00 | 0.00 |
| July | 243.28 | 118.27 | 125.02 | 276.40 | 27.09 | 0.00 | 0.00 | 0.00 |
| August | 194.04 | 94.51 | 99.53 | 209.98 | 42.30 | 0.00 | 0.00 | 0.00 |
| September | 122.21 | 55.30 | 66.91 | 113.51 | 72.30 | 0.00 | 0.00 | 0.00 |
| October | 64.80 | 26.09 | 38.71 | 48.53 | 119.51 | 0.00 | 0.00 | 0.00 |
| November | 13.50 | 4.79 | 8.71 | 1.25 | 220.63 | 0.00 | 0.00 | 0.00 |
| December | 1.92 | 0.45 | 1.47 | 0.00 | 245.25 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 131.18 | 64.68 | 66.50 | 132.57 | 116.92 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 1.92 | 0.45 | 1.47 | 0.00 | 22.55 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 278.66 | 157.05 | 136.33 | 307.28 | 245.25 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: GWINDOW1 E NEA
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 9.91 | 3.77 | 6.14 | 1.36 | 248.80 | 0.00 | 0.00 | 0.00 |
| February | 50.00 | 24.13 | 25.87 | 25.97 | 205.46 | 0.00 | 0.00 | 0.00 |
| March | 142.82 | 72.14 | 70.68 | 122.18 | 147.55 | 0.00 | 0.00 | 0.00 |
| April | 191.41 | 97.00 | 94.41 | 183.78 | 77.10 | 0.00 | 0.00 | 0.00 |
| May | 278.66 | 157.05 | 121.61 | 313.96 | 35.96 | 0.00 | 0.00 | 0.00 |
| June | 255.59 | 119.26 | 136.33 | 292.23 | 18.80 | 0.00 | 0.00 | 0.00 |
| July | 243.28 | 118.27 | 125.02 | 283.99 | 22.10 | 0.00 | 0.00 | 0.00 |
| August | 194.04 | 94.51 | 99.53 | 215.97 | 35.64 | 0.00 | 0.00 | 0.00 |
| September | 122.21 | 55.30 | 66.91 | 117.65 | 65.59 | 0.00 | 0.00 | 0.00 |
| October | 64.80 | 26.09 | 38.71 | 47.33 | 129.73 | 0.00 | 0.00 | 0.00 |
| November | 13.50 | 4.79 | 8.71 | 1.02 | 242.92 | 0.00 | 0.00 | 0.00 |
| December | 1.92 | 0.45 | 1.47 | 0.00 | 269.17 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 131.18 | 64.68 | 66.50 | 134.51 | 124.50 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 1.92 | 0.45 | 1.47 | 0.00 | 18.80 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 278.66 | 157.05 | 136.33 | 313.96 | 269.17 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: GWINDOW1 N NEA
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 5.09 | 0.00 | 5.09 | 0.00 | 391.21 | 0.00 | 0.00 | 0.00 |
| February | 22.48 | 0.00 | 22.48 | 0.00 | 347.90 | 0.00 | 0.00 | 0.00 |
| March | 60.31 | 0.02 | 60.29 | 5.24 | 254.47 | 0.00 | 0.00 | 0.00 |
| April | 109.72 | 3.07 | 106.66 | 50.52 | 128.17 | 0.00 | 0.00 | 0.00 |
| May | 168.20 | 27.17 | 141.03 | 142.48 | 50.95 | 0.00 | 0.00 | 0.00 |
| June | 216.85 | 47.59 | 169.26 | 217.08 | 24.81 | 0.00 | 0.00 | 0.00 |
| July | 183.01 | 30.11 | 152.90 | 185.60 | 31.27 | 0.00 | 0.00 | 0.00 |
| August | 117.57 | 6.36 | 111.22 | 95.74 | 54.22 | 0.00 | 0.00 | 0.00 |
| September | 65.40 | 0.19 | 65.21 | 26.99 | 108.04 | 0.00 | 0.00 | 0.00 |
| October | 31.65 | 0.00 | 31.65 | 2.43 | 219.11 | 0.00 | 0.00 | 0.00 |
| November | 9.82 | 0.00 | 9.82 | 0.00 | 384.05 | 0.00 | 0.00 | 0.00 |
| December | 1.54 | 0.00 | 1.54 | 0.00 | 411.89 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 82.94 | 9.59 | 73.35 | 60.86 | 199.73 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 1.54 | 0.00 | 1.54 | 0.00 | 24.81 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 216.85 | 47.59 | 169.26 | 217.08 | 411.89 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: GWINDOW1 N N1A
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 5.09 | 0.00 | 5.09 | 0.00 | 396.39 | 0.00 | 0.00 | 0.00 |
| February | 22.48 | 0.00 | 22.48 | 0.00 | 352.91 | 0.00 | 0.00 | 0.00 |
| March | 60.31 | 0.02 | 60.29 | 5.08 | 257.89 | 0.00 | 0.00 | 0.00 |
| April | 109.72 | 3.07 | 106.66 | 50.32 | 129.93 | 0.00 | 0.00 | 0.00 |
| May | 168.20 | 27.17 | 141.03 | 144.83 | 51.02 | 0.00 | 0.00 | 0.00 |
| June | 216.85 | 47.59 | 169.26 | 218.28 | 25.06 | 0.00 | 0.00 | 0.00 |
| July | 183.01 | 30.11 | 152.90 | 186.81 | 31.49 | 0.00 | 0.00 | 0.00 |
| August | 117.57 | 6.36 | 111.22 | 96.51 | 54.67 | 0.00 | 0.00 | 0.00 |
| September | 65.40 | 0.19 | 65.21 | 27.19 | 109.24 | 0.00 | 0.00 | 0.00 |
| October | 31.65 | 0.00 | 31.65 | 2.39 | 221.72 | 0.00 | 0.00 | 0.00 |
| November | 9.82 | 0.00 | 9.82 | 0.00 | 388.52 | 0.00 | 0.00 | 0.00 |
| December | 1.54 | 0.00 | 1.54 | 0.00 | 416.94 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 82.94 | 9.59 | 73.35 | 61.31 | 202.19 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 1.54 | 0.00 | 1.54 | 0.00 | 25.06 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 216.85 | 47.59 | 169.26 | 218.28 | 416.94 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: GWINDOW1 N N2A
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 5.09 | 0.00 | 5.09 | 0.00 | 396.40 | 0.00 | 0.00 | 0.00 |
| February | 22.48 | 0.00 | 22.48 | 0.00 | 352.92 | 0.00 | 0.00 | 0.00 |
| March | 60.31 | 0.02 | 60.29 | 5.07 | 257.93 | 0.00 | 0.00 | 0.00 |
| April | 109.72 | 3.07 | 106.66 | 50.31 | 129.91 | 0.00 | 0.00 | 0.00 |
| May | 168.20 | 27.17 | 141.03 | 144.41 | 51.19 | 0.00 | 0.00 | 0.00 |
| June | 216.85 | 47.59 | 169.26 | 218.09 | 25.11 | 0.00 | 0.00 | 0.00 |
| July | 183.01 | 30.11 | 152.90 | 186.73 | 31.51 | 0.00 | 0.00 | 0.00 |
| August | 117.57 | 6.36 | 111.22 | 96.40 | 54.73 | 0.00 | 0.00 | 0.00 |
| September | 65.40 | 0.19 | 65.21 | 27.09 | 109.39 | 0.00 | 0.00 | 0.00 |
| October | 31.65 | 0.00 | 31.65 | 2.38 | 221.76 | 0.00 | 0.00 | 0.00 |
| November | 9.82 | 0.00 | 9.82 | 0.00 | 388.52 | 0.00 | 0.00 | 0.00 |
| December | 1.54 | 0.00 | 1.54 | 0.00 | 416.94 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 82.94 | 9.59 | 73.35 | 61.23 | 202.23 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 1.54 | 0.00 | 1.54 | 0.00 | 25.11 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 216.85 | 47.59 | 169.26 | 218.09 | 416.94 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: GWINDOW1 S S1A
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 62.86 | 41.89 | 20.97 | 35.39 | 355.61 | 0.00 | 0.00 | 0.00 |
| February | 210.30 | 146.25 | 64.06 | 174.76 | 283.20 | 0.00 | 0.00 | 0.00 |
| March | 356.49 | 240.42 | 116.08 | 348.53 | 214.25 | 0.00 | 0.00 | 0.00 |
| April | 442.26 | 276.03 | 166.22 | 487.90 | 133.52 | 0.00 | 0.00 | 0.00 |
| May | 362.92 | 188.15 | 174.77 | 413.14 | 69.41 | 0.00 | 0.00 | 0.00 |
| June | 331.84 | 136.41 | 195.43 | 385.24 | 37.48 | 0.00 | 0.00 | 0.00 |
| July | 319.80 | 139.68 | 180.11 | 379.80 | 40.36 | 0.00 | 0.00 | 0.00 |
| August | 330.90 | 182.57 | 148.33 | 384.33 | 62.74 | 0.00 | 0.00 | 0.00 |
| September | 263.41 | 157.17 | 106.24 | 277.06 | 110.77 | 0.00 | 0.00 | 0.00 |
| October | 193.59 | 122.71 | 70.88 | 175.00 | 185.60 | 0.00 | 0.00 | 0.00 |
| November | 104.52 | 73.34 | 31.18 | 66.10 | 331.78 | 0.00 | 0.00 | 0.00 |
| December | 18.41 | 12.95 | 5.45 | 3.06 | 397.08 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 249.71 | 142.91 | 106.79 | 261.09 | 184.69 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 18.41 | 12.95 | 5.45 | 3.06 | 37.48 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 442.26 | 276.03 | 195.43 | 487.90 | 397.08 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: GWINDOW1 S S2A
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 62.86 | 41.89 | 20.97 | 35.47 | 354.49 | 0.00 | 0.00 | 0.00 |
| February | 210.30 | 146.25 | 64.06 | 175.00 | 282.28 | 0.00 | 0.00 | 0.00 |
| March | 356.49 | 240.42 | 116.08 | 348.89 | 213.44 | 0.00 | 0.00 | 0.00 |
| April | 442.26 | 276.03 | 166.22 | 488.28 | 132.90 | 0.00 | 0.00 | 0.00 |
| May | 362.92 | 188.15 | 174.77 | 412.56 | 69.90 | 0.00 | 0.00 | 0.00 |
| June | 331.84 | 136.41 | 195.43 | 384.77 | 37.79 | 0.00 | 0.00 | 0.00 |
| July | 319.80 | 139.68 | 180.11 | 379.31 | 40.70 | 0.00 | 0.00 | 0.00 |
| August | 330.90 | 182.57 | 148.33 | 383.94 | 63.13 | 0.00 | 0.00 | 0.00 |
| September | 263.41 | 157.17 | 106.24 | 276.73 | 111.23 | 0.00 | 0.00 | 0.00 |
| October | 193.59 | 122.71 | 70.88 | 175.21 | 184.91 | 0.00 | 0.00 | 0.00 |
| November | 104.52 | 73.34 | 31.18 | 66.25 | 330.71 | 0.00 | 0.00 | 0.00 |
| December | 18.41 | 12.95 | 5.45 | 3.07 | 395.95 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 249.71 | 142.91 | 106.79 | 261.02 | 184.33 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 18.41 | 12.95 | 5.45 | 3.07 | 37.79 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 442.26 | 276.03 | 195.43 | 488.28 | 395.95 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MWINDOW1 S SWA
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 62.86 | 41.89 | 20.97 | 34.96 | 360.19 | 0.00 | 0.00 | 0.00 |
| February | 210.30 | 146.25 | 64.06 | 172.97 | 287.98 | 0.00 | 0.00 | 0.00 |
| March | 356.49 | 240.42 | 116.08 | 344.80 | 219.36 | 0.00 | 0.00 | 0.00 |
| April | 442.26 | 276.03 | 166.22 | 479.92 | 141.94 | 0.00 | 0.00 | 0.00 |
| May | 362.92 | 188.15 | 174.77 | 404.56 | 77.02 | 0.00 | 0.00 | 0.00 |
| June | 331.84 | 136.41 | 195.43 | 380.56 | 39.65 | 0.00 | 0.00 | 0.00 |
| July | 319.80 | 139.68 | 180.11 | 376.81 | 41.48 | 0.00 | 0.00 | 0.00 |
| August | 330.90 | 182.57 | 148.33 | 382.43 | 63.44 | 0.00 | 0.00 | 0.00 |
| September | 263.41 | 157.17 | 106.24 | 275.39 | 112.23 | 0.00 | 0.00 | 0.00 |
| October | 193.59 | 122.71 | 70.88 | 173.81 | 187.54 | 0.00 | 0.00 | 0.00 |
| November | 104.52 | 73.34 | 31.18 | 65.63 | 334.04 | 0.00 | 0.00 | 0.00 |
| December | 18.41 | 12.95 | 5.45 | 3.00 | 401.23 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 249.71 | 142.91 | 106.79 | 258.14 | 188.38 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 18.41 | 12.95 | 5.45 | 3.00 | 39.65 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 442.26 | 276.03 | 195.43 | 479.92 | 401.23 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MWINDOW1 W SWA
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 4.63 | 0.81 | 3.82 | 0.00 | 261.84 | 0.00 | 0.00 | 0.00 |
| February | 27.54 | 9.65 | 17.89 | 4.96 | 223.84 | 0.00 | 0.00 | 0.00 |
| March | 82.77 | 35.84 | 46.93 | 45.62 | 161.93 | 0.00 | 0.00 | 0.00 |
| April | 195.26 | 101.23 | 94.03 | 183.31 | 91.47 | 0.00 | 0.00 | 0.00 |
| May | 189.63 | 86.39 | 103.24 | 189.40 | 46.29 | 0.00 | 0.00 | 0.00 |
| June | 207.92 | 88.75 | 119.18 | 227.30 | 23.60 | 0.00 | 0.00 | 0.00 |
| July | 173.76 | 65.68 | 108.08 | 192.02 | 25.46 | 0.00 | 0.00 | 0.00 |
| August | 143.25 | 60.87 | 82.38 | 148.44 | 40.09 | 0.00 | 0.00 | 0.00 |
| September | 86.32 | 36.03 | 50.29 | 68.20 | 76.03 | 0.00 | 0.00 | 0.00 |
| October | 33.80 | 10.12 | 23.68 | 11.84 | 142.27 | 0.00 | 0.00 | 0.00 |
| November | 13.55 | 4.91 | 8.64 | 1.15 | 248.15 | 0.00 | 0.00 | 0.00 |
| December | 1.22 | 0.13 | 1.09 | 0.00 | 276.53 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 96.89 | 41.79 | 55.10 | 89.71 | 134.33 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 1.22 | 0.13 | 1.09 | 0.00 | 23.60 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 207.92 | 101.23 | 119.18 | 227.30 | 276.53 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MWINDOW1 W NWA
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 4.63 | 0.81 | 3.82 | 0.00 | 261.29 | 0.00 | 0.00 | 0.00 |
| February | 27.54 | 9.65 | 17.89 | 5.24 | 222.10 | 0.00 | 0.00 | 0.00 |
| March | 82.77 | 35.84 | 46.93 | 46.98 | 159.45 | 0.00 | 0.00 | 0.00 |
| April | 195.26 | 101.23 | 94.03 | 188.61 | 87.86 | 0.00 | 0.00 | 0.00 |
| May | 189.63 | 86.39 | 103.24 | 192.03 | 44.92 | 0.00 | 0.00 | 0.00 |
| June | 207.92 | 88.75 | 119.18 | 228.26 | 23.53 | 0.00 | 0.00 | 0.00 |
| July | 173.76 | 65.68 | 108.08 | 193.03 | 25.27 | 0.00 | 0.00 | 0.00 |
| August | 143.25 | 60.87 | 82.38 | 150.27 | 39.23 | 0.00 | 0.00 | 0.00 |
| September | 86.32 | 36.03 | 50.29 | 71.63 | 71.64 | 0.00 | 0.00 | 0.00 |
| October | 33.80 | 10.12 | 23.68 | 12.56 | 140.26 | 0.00 | 0.00 | 0.00 |
| November | 13.55 | 4.91 | 8.64 | 1.22 | 247.25 | 0.00 | 0.00 | 0.00 |
| December | 1.22 | 0.13 | 1.09 | 0.00 | 276.36 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 96.89 | 41.79 | 55.10 | 91.18 | 132.81 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 1.22 | 0.13 | 1.09 | 0.00 | 23.53 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 207.92 | 101.23 | 119.18 | 228.26 | 276.36 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MWINDOW1 N NWA
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 5.09 | 0.00 | 5.09 | 0.00 | 401.69 | 0.00 | 0.00 | 0.00 |
| February | 22.48 | 0.00 | 22.48 | 0.00 | 359.72 | 0.00 | 0.00 | 0.00 |
| March | 60.31 | 0.02 | 60.29 | 4.46 | 265.52 | 0.00 | 0.00 | 0.00 |
| April | 109.72 | 3.07 | 106.66 | 44.57 | 137.89 | 0.00 | 0.00 | 0.00 |
| May | 168.20 | 27.17 | 141.03 | 128.31 | 59.41 | 0.00 | 0.00 | 0.00 |
| June | 216.85 | 47.59 | 169.26 | 211.04 | 27.05 | 0.00 | 0.00 | 0.00 |
| July | 183.01 | 30.11 | 152.90 | 183.14 | 32.67 | 0.00 | 0.00 | 0.00 |
| August | 117.57 | 6.36 | 111.22 | 93.91 | 56.26 | 0.00 | 0.00 | 0.00 |
| September | 65.40 | 0.19 | 65.21 | 25.19 | 113.80 | 0.00 | 0.00 | 0.00 |
| October | 31.65 | 0.00 | 31.65 | 2.20 | 224.97 | 0.00 | 0.00 | 0.00 |
| November | 9.82 | 0.00 | 9.82 | 0.00 | 391.64 | 0.00 | 0.00 | 0.00 |
| December | 1.54 | 0.00 | 1.54 | 0.00 | 421.40 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 82.94 | 9.59 | 73.35 | 58.07 | 206.86 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 1.54 | 0.00 | 1.54 | 0.00 | 27.05 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 216.85 | 47.59 | 169.26 | 211.04 | 421.40 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MWINDOW1 S SEA
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 62.86 | 41.89 | 20.97 | 34.92 | 360.23 | 0.00 | 0.00 | 0.00 |
| February | 210.30 | 146.25 | 64.06 | 172.69 | 288.09 | 0.00 | 0.00 | 0.00 |
| March | 356.49 | 240.42 | 116.08 | 343.83 | 219.67 | 0.00 | 0.00 | 0.00 |
| April | 442.26 | 276.03 | 166.22 | 479.00 | 141.28 | 0.00 | 0.00 | 0.00 |
| May | 362.92 | 188.15 | 174.77 | 402.98 | 77.33 | 0.00 | 0.00 | 0.00 |
| June | 331.84 | 136.41 | 195.43 | 379.80 | 39.60 | 0.00 | 0.00 | 0.00 |
| July | 319.80 | 139.68 | 180.11 | 375.87 | 41.48 | 0.00 | 0.00 | 0.00 |
| August | 330.90 | 182.57 | 148.33 | 381.60 | 63.53 | 0.00 | 0.00 | 0.00 |
| September | 263.41 | 157.17 | 106.24 | 274.42 | 112.61 | 0.00 | 0.00 | 0.00 |
| October | 193.59 | 122.71 | 70.88 | 173.25 | 187.91 | 0.00 | 0.00 | 0.00 |
| November | 104.52 | 73.34 | 31.18 | 65.61 | 334.01 | 0.00 | 0.00 | 0.00 |
| December | 18.41 | 12.95 | 5.45 | 3.00 | 401.24 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 249.71 | 142.91 | 106.79 | 257.48 | 188.45 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 18.41 | 12.95 | 5.45 | 3.00 | 39.60 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 442.26 | 276.03 | 195.43 | 479.00 | 401.24 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MWINDOW1 E SEA
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 9.91 | 3.77 | 6.14 | 1.24 | 256.28 | 0.00 | 0.00 | 0.00 |
| February | 50.00 | 24.13 | 25.87 | 24.84 | 214.48 | 0.00 | 0.00 | 0.00 |
| March | 142.82 | 72.14 | 70.68 | 118.61 | 156.72 | 0.00 | 0.00 | 0.00 |
| April | 191.41 | 97.00 | 94.41 | 173.42 | 86.43 | 0.00 | 0.00 | 0.00 |
| May | 278.66 | 157.05 | 121.61 | 300.91 | 43.45 | 0.00 | 0.00 | 0.00 |
| June | 255.59 | 119.26 | 136.33 | 286.96 | 20.65 | 0.00 | 0.00 | 0.00 |
| July | 243.28 | 118.27 | 125.02 | 280.61 | 23.33 | 0.00 | 0.00 | 0.00 |
| August | 194.04 | 94.51 | 99.53 | 212.08 | 37.88 | 0.00 | 0.00 | 0.00 |
| September | 122.21 | 55.30 | 66.91 | 111.68 | 73.59 | 0.00 | 0.00 | 0.00 |
| October | 64.80 | 26.09 | 38.71 | 45.68 | 135.61 | 0.00 | 0.00 | 0.00 |
| November | 13.50 | 4.79 | 8.71 | 0.93 | 248.90 | 0.00 | 0.00 | 0.00 |
| December | 1.92 | 0.45 | 1.47 | 0.00 | 275.71 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 131.18 | 64.68 | 66.50 | 130.46 | 130.66 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 1.92 | 0.45 | 1.47 | 0.00 | 20.65 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 278.66 | 157.05 | 136.33 | 300.91 | 275.71 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MWINDOW1 E NEA
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 9.91 | 3.77 | 6.14 | 1.27 | 255.75 | 0.00 | 0.00 | 0.00 |
| February | 50.00 | 24.13 | 25.87 | 25.14 | 212.73 | 0.00 | 0.00 | 0.00 |
| March | 142.82 | 72.14 | 70.68 | 119.77 | 153.91 | 0.00 | 0.00 | 0.00 |
| April | 191.41 | 97.00 | 94.41 | 178.34 | 82.19 | 0.00 | 0.00 | 0.00 |
| May | 278.66 | 157.05 | 121.61 | 303.14 | 42.24 | 0.00 | 0.00 | 0.00 |
| June | 255.59 | 119.26 | 136.33 | 287.83 | 20.45 | 0.00 | 0.00 | 0.00 |
| July | 243.28 | 118.27 | 125.02 | 281.57 | 23.07 | 0.00 | 0.00 | 0.00 |
| August | 194.04 | 94.51 | 99.53 | 213.76 | 37.03 | 0.00 | 0.00 | 0.00 |
| September | 122.21 | 55.30 | 66.91 | 114.72 | 69.57 | 0.00 | 0.00 | 0.00 |
| October | 64.80 | 26.09 | 38.71 | 46.46 | 133.41 | 0.00 | 0.00 | 0.00 |
| November | 13.50 | 4.79 | 8.71 | 0.95 | 247.96 | 0.00 | 0.00 | 0.00 |
| December | 1.92 | 0.45 | 1.47 | 0.00 | 275.54 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 131.18 | 64.68 | 66.50 | 131.79 | 129.07 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 1.92 | 0.45 | 1.47 | 0.00 | 20.45 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 278.66 | 157.05 | 136.33 | 303.14 | 275.54 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MWINDOW1 N NEA
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 5.09 | 0.00 | 5.09 | 0.00 | 401.76 | 0.00 | 0.00 | 0.00 |
| February | 22.48 | 0.00 | 22.48 | 0.00 | 360.05 | 0.00 | 0.00 | 0.00 |
| March | 60.31 | 0.02 | 60.29 | 4.29 | 266.40 | 0.00 | 0.00 | 0.00 |
| April | 109.72 | 3.07 | 106.66 | 44.02 | 137.27 | 0.00 | 0.00 | 0.00 |
| May | 168.20 | 27.17 | 141.03 | 125.71 | 59.71 | 0.00 | 0.00 | 0.00 |
| June | 216.85 | 47.59 | 169.26 | 210.19 | 26.95 | 0.00 | 0.00 | 0.00 |
| July | 183.01 | 30.11 | 152.90 | 182.08 | 32.62 | 0.00 | 0.00 | 0.00 |
| August | 117.57 | 6.36 | 111.22 | 92.81 | 56.41 | 0.00 | 0.00 | 0.00 |
| September | 65.40 | 0.19 | 65.21 | 23.87 | 115.07 | 0.00 | 0.00 | 0.00 |
| October | 31.65 | 0.00 | 31.65 | 2.13 | 225.49 | 0.00 | 0.00 | 0.00 |
| November | 9.82 | 0.00 | 9.82 | 0.00 | 391.63 | 0.00 | 0.00 | 0.00 |
| December | 1.54 | 0.00 | 1.54 | 0.00 | 421.41 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 82.94 | 9.59 | 73.35 | 57.42 | 207.09 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 1.54 | 0.00 | 1.54 | 0.00 | 26.95 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 216.85 | 47.59 | 169.26 | 210.19 | 421.41 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MWINDOW1 N N1A
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 5.09 | 0.00 | 5.09 | 0.00 | 406.00 | 0.00 | 0.00 | 0.00 |
| February | 22.48 | 0.00 | 22.48 | 0.00 | 363.68 | 0.00 | 0.00 | 0.00 |
| March | 60.31 | 0.02 | 60.29 | 4.27 | 268.46 | 0.00 | 0.00 | 0.00 |
| April | 109.72 | 3.07 | 106.66 | 45.02 | 138.07 | 0.00 | 0.00 | 0.00 |
| May | 168.20 | 27.17 | 141.03 | 127.94 | 59.97 | 0.00 | 0.00 | 0.00 |
| June | 216.85 | 47.59 | 169.26 | 212.21 | 26.93 | 0.00 | 0.00 | 0.00 |
| July | 183.01 | 30.11 | 152.90 | 184.07 | 32.56 | 0.00 | 0.00 | 0.00 |
| August | 117.57 | 6.36 | 111.22 | 94.00 | 56.64 | 0.00 | 0.00 | 0.00 |
| September | 65.40 | 0.19 | 65.21 | 24.07 | 116.97 | 0.00 | 0.00 | 0.00 |
| October | 31.65 | 0.00 | 31.65 | 2.10 | 228.16 | 0.00 | 0.00 | 0.00 |
| November | 9.82 | 0.00 | 9.82 | 0.00 | 395.77 | 0.00 | 0.00 | 0.00 |
| December | 1.54 | 0.00 | 1.54 | 0.00 | 425.84 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 82.94 | 9.59 | 73.35 | 58.14 | 209.10 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 1.54 | 0.00 | 1.54 | 0.00 | 26.93 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 216.85 | 47.59 | 169.26 | 212.21 | 425.84 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MWINDOW1 N N2A
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 5.09 | 0.00 | 5.09 | 0.00 | 406.01 | 0.00 | 0.00 | 0.00 |
| February | 22.48 | 0.00 | 22.48 | 0.00 | 363.70 | 0.00 | 0.00 | 0.00 |
| March | 60.31 | 0.02 | 60.29 | 4.26 | 268.51 | 0.00 | 0.00 | 0.00 |
| April | 109.72 | 3.07 | 106.66 | 44.99 | 138.04 | 0.00 | 0.00 | 0.00 |
| May | 168.20 | 27.17 | 141.03 | 127.71 | 60.07 | 0.00 | 0.00 | 0.00 |
| June | 216.85 | 47.59 | 169.26 | 212.18 | 26.93 | 0.00 | 0.00 | 0.00 |
| July | 183.01 | 30.11 | 152.90 | 184.03 | 32.56 | 0.00 | 0.00 | 0.00 |
| August | 117.57 | 6.36 | 111.22 | 93.95 | 56.67 | 0.00 | 0.00 | 0.00 |
| September | 65.40 | 0.19 | 65.21 | 23.90 | 117.25 | 0.00 | 0.00 | 0.00 |
| October | 31.65 | 0.00 | 31.65 | 2.09 | 228.20 | 0.00 | 0.00 | 0.00 |
| November | 9.82 | 0.00 | 9.82 | 0.00 | 395.77 | 0.00 | 0.00 | 0.00 |
| December | 1.54 | 0.00 | 1.54 | 0.00 | 425.84 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 82.94 | 9.59 | 73.35 | 58.10 | 209.14 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 1.54 | 0.00 | 1.54 | 0.00 | 26.93 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 216.85 | 47.59 | 169.26 | 212.18 | 425.84 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MWINDOW1 S S1A
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 62.86 | 41.89 | 20.97 | 34.61 | 364.31 | 0.00 | 0.00 | 0.00 |
| February | 210.30 | 146.25 | 64.06 | 171.89 | 291.54 | 0.00 | 0.00 | 0.00 |
| March | 356.49 | 240.42 | 116.08 | 343.37 | 222.01 | 0.00 | 0.00 | 0.00 |
| April | 442.26 | 276.03 | 166.22 | 479.05 | 143.46 | 0.00 | 0.00 | 0.00 |
| May | 362.92 | 188.15 | 174.77 | 404.32 | 77.88 | 0.00 | 0.00 | 0.00 |
| June | 331.84 | 136.41 | 195.43 | 381.50 | 39.42 | 0.00 | 0.00 | 0.00 |
| July | 319.80 | 139.68 | 180.11 | 377.59 | 41.33 | 0.00 | 0.00 | 0.00 |
| August | 330.90 | 182.57 | 148.33 | 382.58 | 63.78 | 0.00 | 0.00 | 0.00 |
| September | 263.41 | 157.17 | 106.24 | 273.99 | 115.13 | 0.00 | 0.00 | 0.00 |
| October | 193.59 | 122.71 | 70.88 | 172.48 | 190.97 | 0.00 | 0.00 | 0.00 |
| November | 104.52 | 73.34 | 31.18 | 65.03 | 337.89 | 0.00 | 0.00 | 0.00 |
| December | 18.41 | 12.95 | 5.45 | 2.94 | 405.64 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 249.71 | 142.91 | 106.79 | 257.68 | 190.64 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 18.41 | 12.95 | 5.45 | 2.94 | 39.42 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 442.26 | 276.03 | 195.43 | 479.05 | 405.64 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MWINDOW1 S S2A
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 62.86 | 41.89 | 20.97 | 34.60 | 364.31 | 0.00 | 0.00 | 0.00 |
| February | 210.30 | 146.25 | 64.06 | 171.88 | 291.55 | 0.00 | 0.00 | 0.00 |
| March | 356.49 | 240.42 | 116.08 | 343.32 | 222.04 | 0.00 | 0.00 | 0.00 |
| April | 442.26 | 276.03 | 166.22 | 479.00 | 143.44 | 0.00 | 0.00 | 0.00 |
| May | 362.92 | 188.15 | 174.77 | 404.23 | 77.92 | 0.00 | 0.00 | 0.00 |
| June | 331.84 | 136.41 | 195.43 | 381.47 | 39.42 | 0.00 | 0.00 | 0.00 |
| July | 319.80 | 139.68 | 180.11 | 377.55 | 41.33 | 0.00 | 0.00 | 0.00 |
| August | 330.90 | 182.57 | 148.33 | 382.54 | 63.79 | 0.00 | 0.00 | 0.00 |
| September | 263.41 | 157.17 | 106.24 | 273.93 | 115.19 | 0.00 | 0.00 | 0.00 |
| October | 193.59 | 122.71 | 70.88 | 172.43 | 191.04 | 0.00 | 0.00 | 0.00 |
| November | 104.52 | 73.34 | 31.18 | 65.03 | 337.89 | 0.00 | 0.00 | 0.00 |
| December | 18.41 | 12.95 | 5.45 | 2.94 | 405.64 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 249.71 | 142.91 | 106.79 | 257.65 | 190.66 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 18.41 | 12.95 | 5.45 | 2.94 | 39.42 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 442.26 | 276.03 | 195.43 | 479.00 | 405.64 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: TWINDOW1 S SWA
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 62.86 | 41.89 | 20.97 | 35.52 | 351.57 | 0.00 | 0.00 | 0.00 |
| February | 210.30 | 146.25 | 64.06 | 174.32 | 280.69 | 0.00 | 0.00 | 0.00 |
| March | 356.49 | 240.42 | 116.08 | 345.48 | 213.57 | 0.00 | 0.00 | 0.00 |
| April | 442.26 | 276.03 | 166.22 | 480.08 | 135.92 | 0.00 | 0.00 | 0.00 |
| May | 362.92 | 188.15 | 174.77 | 406.58 | 70.19 | 0.00 | 0.00 | 0.00 |
| June | 331.84 | 136.41 | 195.43 | 379.79 | 37.16 | 0.00 | 0.00 | 0.00 |
| July | 319.80 | 139.68 | 180.11 | 375.84 | 39.14 | 0.00 | 0.00 | 0.00 |
| August | 330.90 | 182.57 | 148.33 | 383.40 | 58.58 | 0.00 | 0.00 | 0.00 |
| September | 263.41 | 157.17 | 106.24 | 278.79 | 102.92 | 0.00 | 0.00 | 0.00 |
| October | 193.59 | 122.71 | 70.88 | 174.97 | 181.66 | 0.00 | 0.00 | 0.00 |
| November | 104.52 | 73.34 | 31.18 | 66.72 | 325.41 | 0.00 | 0.00 | 0.00 |
| December | 18.41 | 12.95 | 5.45 | 3.13 | 391.93 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 249.71 | 142.91 | 106.79 | 258.94 | 181.94 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 18.41 | 12.95 | 5.45 | 3.13 | 37.16 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 442.26 | 276.03 | 195.43 | 480.08 | 391.93 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: TWINDOW1 W SWA
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 4.63 | 0.81 | 3.82 | 0.00 | 255.70 | 0.00 | 0.00 | 0.00 |
| February | 27.54 | 9.65 | 17.89 | 5.02 | 218.18 | 0.00 | 0.00 | 0.00 |
| March | 82.77 | 35.84 | 46.93 | 45.42 | 157.42 | 0.00 | 0.00 | 0.00 |
| April | 195.26 | 101.23 | 94.03 | 182.91 | 86.98 | 0.00 | 0.00 | 0.00 |
| May | 189.63 | 86.39 | 103.24 | 190.83 | 41.74 | 0.00 | 0.00 | 0.00 |
| June | 207.92 | 88.75 | 119.18 | 226.84 | 21.91 | 0.00 | 0.00 | 0.00 |
| July | 173.76 | 65.68 | 108.08 | 191.40 | 23.85 | 0.00 | 0.00 | 0.00 |
| August | 143.25 | 60.87 | 82.38 | 149.04 | 36.76 | 0.00 | 0.00 | 0.00 |
| September | 86.32 | 36.03 | 50.29 | 69.89 | 69.28 | 0.00 | 0.00 | 0.00 |
| October | 33.80 | 10.12 | 23.68 | 11.96 | 137.69 | 0.00 | 0.00 | 0.00 |
| November | 13.55 | 4.91 | 8.64 | 1.20 | 241.70 | 0.00 | 0.00 | 0.00 |
| December | 1.22 | 0.13 | 1.09 | 0.00 | 270.21 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 96.89 | 41.79 | 55.10 | 89.90 | 129.67 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 1.22 | 0.13 | 1.09 | 0.00 | 21.91 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 207.92 | 101.23 | 119.18 | 226.84 | 270.21 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: TWINDOW1 W NWA
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 4.63 | 0.81 | 3.82 | 0.00 | 255.09 | 0.00 | 0.00 | 0.00 |
| February | 27.54 | 9.65 | 17.89 | 5.43 | 216.42 | 0.00 | 0.00 | 0.00 |
| March | 82.77 | 35.84 | 46.93 | 47.44 | 155.11 | 0.00 | 0.00 | 0.00 |
| April | 195.26 | 101.23 | 94.03 | 188.89 | 84.91 | 0.00 | 0.00 | 0.00 |
| May | 189.63 | 86.39 | 103.24 | 194.28 | 40.89 | 0.00 | 0.00 | 0.00 |
| June | 207.92 | 88.75 | 119.18 | 227.87 | 22.14 | 0.00 | 0.00 | 0.00 |
| July | 173.76 | 65.68 | 108.08 | 192.68 | 23.79 | 0.00 | 0.00 | 0.00 |
| August | 143.25 | 60.87 | 82.38 | 151.96 | 35.81 | 0.00 | 0.00 | 0.00 |
| September | 86.32 | 36.03 | 50.29 | 73.41 | 66.86 | 0.00 | 0.00 | 0.00 |
| October | 33.80 | 10.12 | 23.68 | 12.88 | 135.98 | 0.00 | 0.00 | 0.00 |
| November | 13.55 | 4.91 | 8.64 | 1.30 | 240.77 | 0.00 | 0.00 | 0.00 |
| December | 1.22 | 0.13 | 1.09 | 0.00 | 270.03 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 96.89 | 41.79 | 55.10 | 91.71 | 128.54 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 1.22 | 0.13 | 1.09 | 0.00 | 22.14 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 207.92 | 101.23 | 119.18 | 227.87 | 270.03 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: TWINDOW1 N NWA
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 5.09 | 0.00 | 5.09 | 0.00 | 392.63 | 0.00 | 0.00 | 0.00 |
| February | 22.48 | 0.00 | 22.48 | 0.00 | 351.23 | 0.00 | 0.00 | 0.00 |
| March | 60.31 | 0.02 | 60.29 | 4.77 | 258.78 | 0.00 | 0.00 | 0.00 |
| April | 109.72 | 3.07 | 106.66 | 45.30 | 133.68 | 0.00 | 0.00 | 0.00 |
| May | 168.20 | 27.17 | 141.03 | 133.57 | 55.18 | 0.00 | 0.00 | 0.00 |
| June | 216.85 | 47.59 | 169.26 | 211.26 | 25.69 | 0.00 | 0.00 | 0.00 |
| July | 183.01 | 30.11 | 152.90 | 183.33 | 31.14 | 0.00 | 0.00 | 0.00 |
| August | 117.57 | 6.36 | 111.22 | 97.41 | 51.99 | 0.00 | 0.00 | 0.00 |
| September | 65.40 | 0.19 | 65.21 | 27.75 | 106.48 | 0.00 | 0.00 | 0.00 |
| October | 31.65 | 0.00 | 31.65 | 2.42 | 218.43 | 0.00 | 0.00 | 0.00 |
| November | 9.82 | 0.00 | 9.82 | 0.00 | 382.07 | 0.00 | 0.00 | 0.00 |
| December | 1.54 | 0.00 | 1.54 | 0.00 | 412.12 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 82.94 | 9.59 | 73.35 | 59.17 | 200.82 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 1.54 | 0.00 | 1.54 | 0.00 | 25.69 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 216.85 | 47.59 | 169.26 | 211.26 | 412.12 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: TWINDOW1 S SEA
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 62.86 | 41.89 | 20.97 | 35.47 | 351.60 | 0.00 | 0.00 | 0.00 |
| February | 210.30 | 146.25 | 64.06 | 173.93 | 280.71 | 0.00 | 0.00 | 0.00 |
| March | 356.49 | 240.42 | 116.08 | 344.15 | 213.57 | 0.00 | 0.00 | 0.00 |
| April | 442.26 | 276.03 | 166.22 | 478.60 | 134.69 | 0.00 | 0.00 | 0.00 |
| May | 362.92 | 188.15 | 174.77 | 403.23 | 69.88 | 0.00 | 0.00 | 0.00 |
| June | 331.84 | 136.41 | 195.43 | 378.17 | 36.98 | 0.00 | 0.00 | 0.00 |
| July | 319.80 | 139.68 | 180.11 | 374.15 | 38.98 | 0.00 | 0.00 | 0.00 |
| August | 330.90 | 182.57 | 148.33 | 381.58 | 58.52 | 0.00 | 0.00 | 0.00 |
| September | 263.41 | 157.17 | 106.24 | 277.29 | 102.84 | 0.00 | 0.00 | 0.00 |
| October | 193.59 | 122.71 | 70.88 | 174.30 | 181.75 | 0.00 | 0.00 | 0.00 |
| November | 104.52 | 73.34 | 31.18 | 66.68 | 325.36 | 0.00 | 0.00 | 0.00 |
| December | 18.41 | 12.95 | 5.45 | 3.13 | 391.94 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 249.71 | 142.91 | 106.79 | 257.78 | 181.78 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 18.41 | 12.95 | 5.45 | 3.13 | 36.98 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 442.26 | 276.03 | 195.43 | 478.60 | 391.94 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: TWINDOW1 E SEA
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 9.91 | 3.77 | 6.14 | 1.29 | 250.24 | 0.00 | 0.00 | 0.00 |
| February | 50.00 | 24.13 | 25.87 | 25.29 | 209.29 | 0.00 | 0.00 | 0.00 |
| March | 142.82 | 72.14 | 70.68 | 119.21 | 152.99 | 0.00 | 0.00 | 0.00 |
| April | 191.41 | 97.00 | 94.41 | 174.06 | 82.90 | 0.00 | 0.00 | 0.00 |
| May | 278.66 | 157.05 | 121.61 | 302.65 | 40.12 | 0.00 | 0.00 | 0.00 |
| June | 255.59 | 119.26 | 136.33 | 286.60 | 19.57 | 0.00 | 0.00 | 0.00 |
| July | 243.28 | 118.27 | 125.02 | 280.01 | 22.18 | 0.00 | 0.00 | 0.00 |
| August | 194.04 | 94.51 | 99.53 | 212.84 | 35.33 | 0.00 | 0.00 | 0.00 |
| September | 122.21 | 55.30 | 66.91 | 114.24 | 67.76 | 0.00 | 0.00 | 0.00 |
| October | 64.80 | 26.09 | 38.71 | 46.25 | 131.39 | 0.00 | 0.00 | 0.00 |
| November | 13.50 | 4.79 | 8.71 | 0.99 | 242.54 | 0.00 | 0.00 | 0.00 |
| December | 1.92 | 0.45 | 1.47 | 0.00 | 269.42 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 131.18 | 64.68 | 66.50 | 131.00 | 126.56 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 1.92 | 0.45 | 1.47 | 0.00 | 19.57 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 278.66 | 157.05 | 136.33 | 302.65 | 269.42 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: TWINDOW1 E NEA
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 9.91 | 3.77 | 6.14 | 1.33 | 249.66 | 0.00 | 0.00 | 0.00 |
| February | 50.00 | 24.13 | 25.87 | 25.67 | 207.47 | 0.00 | 0.00 | 0.00 |
| March | 142.82 | 72.14 | 70.68 | 120.68 | 149.98 | 0.00 | 0.00 | 0.00 |
| April | 191.41 | 97.00 | 94.41 | 179.17 | 79.66 | 0.00 | 0.00 | 0.00 |
| May | 278.66 | 157.05 | 121.61 | 305.07 | 39.07 | 0.00 | 0.00 | 0.00 |
| June | 255.59 | 119.26 | 136.33 | 287.53 | 19.42 | 0.00 | 0.00 | 0.00 |
| July | 243.28 | 118.27 | 125.02 | 281.24 | 21.94 | 0.00 | 0.00 | 0.00 |
| August | 194.04 | 94.51 | 99.53 | 215.44 | 34.18 | 0.00 | 0.00 | 0.00 |
| September | 122.21 | 55.30 | 66.91 | 117.28 | 64.62 | 0.00 | 0.00 | 0.00 |
| October | 64.80 | 26.09 | 38.71 | 47.06 | 129.43 | 0.00 | 0.00 | 0.00 |
| November | 13.50 | 4.79 | 8.71 | 1.03 | 241.55 | 0.00 | 0.00 | 0.00 |
| December | 1.92 | 0.45 | 1.47 | 0.00 | 269.23 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 131.18 | 64.68 | 66.50 | 132.50 | 125.11 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 1.92 | 0.45 | 1.47 | 0.00 | 19.42 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 278.66 | 157.05 | 136.33 | 305.07 | 269.23 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: TWINDOW1 N NEA
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 5.09 | 0.00 | 5.09 | 0.00 | 392.71 | 0.00 | 0.00 | 0.00 |
| February | 22.48 | 0.00 | 22.48 | 0.00 | 351.57 | 0.00 | 0.00 | 0.00 |
| March | 60.31 | 0.02 | 60.29 | 4.53 | 259.59 | 0.00 | 0.00 | 0.00 |
| April | 109.72 | 3.07 | 106.66 | 44.41 | 132.65 | 0.00 | 0.00 | 0.00 |
| May | 168.20 | 27.17 | 141.03 | 128.72 | 54.88 | 0.00 | 0.00 | 0.00 |
| June | 216.85 | 47.59 | 169.26 | 209.79 | 25.42 | 0.00 | 0.00 | 0.00 |
| July | 183.01 | 30.11 | 152.90 | 181.62 | 30.91 | 0.00 | 0.00 | 0.00 |
| August | 117.57 | 6.36 | 111.22 | 95.09 | 51.78 | 0.00 | 0.00 | 0.00 |
| September | 65.40 | 0.19 | 65.21 | 26.55 | 106.41 | 0.00 | 0.00 | 0.00 |
| October | 31.65 | 0.00 | 31.65 | 2.31 | 218.89 | 0.00 | 0.00 | 0.00 |
| November | 9.82 | 0.00 | 9.82 | 0.00 | 382.05 | 0.00 | 0.00 | 0.00 |
| December | 1.54 | 0.00 | 1.54 | 0.00 | 412.13 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 82.94 | 9.59 | 73.35 | 58.09 | 200.79 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 1.54 | 0.00 | 1.54 | 0.00 | 25.42 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 216.85 | 47.59 | 169.26 | 209.79 | 412.13 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: TWINDOW1 N N1A
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 5.09 | 0.00 | 5.09 | 0.00 | 397.76 | 0.00 | 0.00 | 0.00 |
| February | 22.48 | 0.00 | 22.48 | 0.00 | 355.88 | 0.00 | 0.00 | 0.00 |
| March | 60.31 | 0.02 | 60.29 | 4.58 | 262.13 | 0.00 | 0.00 | 0.00 |
| April | 109.72 | 3.07 | 106.66 | 45.97 | 134.10 | 0.00 | 0.00 | 0.00 |
| May | 168.20 | 27.17 | 141.03 | 133.38 | 55.69 | 0.00 | 0.00 | 0.00 |
| June | 216.85 | 47.59 | 169.26 | 212.06 | 25.95 | 0.00 | 0.00 | 0.00 |
| July | 183.01 | 30.11 | 152.90 | 183.89 | 31.48 | 0.00 | 0.00 | 0.00 |
| August | 117.57 | 6.36 | 111.22 | 97.04 | 52.77 | 0.00 | 0.00 | 0.00 |
| September | 65.40 | 0.19 | 65.21 | 27.52 | 107.83 | 0.00 | 0.00 | 0.00 |
| October | 31.65 | 0.00 | 31.65 | 2.32 | 221.82 | 0.00 | 0.00 | 0.00 |
| November | 9.82 | 0.00 | 9.82 | 0.00 | 386.96 | 0.00 | 0.00 | 0.00 |
| December | 1.54 | 0.00 | 1.54 | 0.00 | 417.42 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 82.94 | 9.59 | 73.35 | 59.24 | 203.34 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 1.54 | 0.00 | 1.54 | 0.00 | 25.95 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 216.85 | 47.59 | 169.26 | 212.06 | 417.42 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: TWINDOW1 N N2A
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 5.09 | 0.00 | 5.09 | 0.00 | 397.76 | 0.00 | 0.00 | 0.00 |
| February | 22.48 | 0.00 | 22.48 | 0.00 | 355.90 | 0.00 | 0.00 | 0.00 |
| March | 60.31 | 0.02 | 60.29 | 4.57 | 262.17 | 0.00 | 0.00 | 0.00 |
| April | 109.72 | 3.07 | 106.66 | 45.88 | 134.02 | 0.00 | 0.00 | 0.00 |
| May | 168.20 | 27.17 | 141.03 | 132.87 | 55.75 | 0.00 | 0.00 | 0.00 |
| June | 216.85 | 47.59 | 169.26 | 211.98 | 25.94 | 0.00 | 0.00 | 0.00 |
| July | 183.01 | 30.11 | 152.90 | 183.80 | 31.47 | 0.00 | 0.00 | 0.00 |
| August | 117.57 | 6.36 | 111.22 | 96.85 | 52.79 | 0.00 | 0.00 | 0.00 |
| September | 65.40 | 0.19 | 65.21 | 27.41 | 107.85 | 0.00 | 0.00 | 0.00 |
| October | 31.65 | 0.00 | 31.65 | 2.32 | 221.84 | 0.00 | 0.00 | 0.00 |
| November | 9.82 | 0.00 | 9.82 | 0.00 | 386.96 | 0.00 | 0.00 | 0.00 |
| December | 1.54 | 0.00 | 1.54 | 0.00 | 417.42 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 82.94 | 9.59 | 73.35 | 59.15 | 203.35 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 1.54 | 0.00 | 1.54 | 0.00 | 25.94 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 216.85 | 47.59 | 169.26 | 211.98 | 417.42 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: TWINDOW1 S S1A
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 62.86 | 41.89 | 20.97 | 35.11 | 356.36 | 0.00 | 0.00 | 0.00 |
| February | 210.30 | 146.25 | 64.06 | 173.14 | 284.52 | 0.00 | 0.00 | 0.00 |
| March | 356.49 | 240.42 | 116.08 | 344.01 | 216.46 | 0.00 | 0.00 | 0.00 |
| April | 442.26 | 276.03 | 166.22 | 479.56 | 137.16 | 0.00 | 0.00 | 0.00 |
| May | 362.92 | 188.15 | 174.77 | 406.28 | 71.26 | 0.00 | 0.00 | 0.00 |
| June | 331.84 | 136.41 | 195.43 | 380.47 | 37.54 | 0.00 | 0.00 | 0.00 |
| July | 319.80 | 139.68 | 180.11 | 376.37 | 39.62 | 0.00 | 0.00 | 0.00 |
| August | 330.90 | 182.57 | 148.33 | 383.05 | 59.82 | 0.00 | 0.00 | 0.00 |
| September | 263.41 | 157.17 | 106.24 | 277.77 | 105.25 | 0.00 | 0.00 | 0.00 |
| October | 193.59 | 122.71 | 70.88 | 173.81 | 184.70 | 0.00 | 0.00 | 0.00 |
| November | 104.52 | 73.34 | 31.18 | 66.02 | 329.75 | 0.00 | 0.00 | 0.00 |
| December | 18.41 | 12.95 | 5.45 | 3.05 | 397.16 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 249.71 | 142.91 | 106.79 | 258.45 | 184.50 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 18.41 | 12.95 | 5.45 | 3.05 | 37.54 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 442.26 | 276.03 | 195.43 | 479.56 | 397.16 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: TWINDOW1 S S2A
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 62.86 | 41.89 | 20.97 | 35.11 | 356.36 | 0.00 | 0.00 | 0.00 |
| February | 210.30 | 146.25 | 64.06 | 173.13 | 284.52 | 0.00 | 0.00 | 0.00 |
| March | 356.49 | 240.42 | 116.08 | 343.92 | 216.47 | 0.00 | 0.00 | 0.00 |
| April | 442.26 | 276.03 | 166.22 | 479.45 | 137.07 | 0.00 | 0.00 | 0.00 |
| May | 362.92 | 188.15 | 174.77 | 406.03 | 71.25 | 0.00 | 0.00 | 0.00 |
| June | 331.84 | 136.41 | 195.43 | 380.36 | 37.52 | 0.00 | 0.00 | 0.00 |
| July | 319.80 | 139.68 | 180.11 | 376.28 | 39.61 | 0.00 | 0.00 | 0.00 |
| August | 330.90 | 182.57 | 148.33 | 382.92 | 59.83 | 0.00 | 0.00 | 0.00 |
| September | 263.41 | 157.17 | 106.24 | 277.65 | 105.27 | 0.00 | 0.00 | 0.00 |
| October | 193.59 | 122.71 | 70.88 | 173.77 | 184.72 | 0.00 | 0.00 | 0.00 |
| November | 104.52 | 73.34 | 31.18 | 66.02 | 329.75 | 0.00 | 0.00 | 0.00 |
| December | 18.41 | 12.95 | 5.45 | 3.05 | 397.16 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 249.71 | 142.91 | 106.79 | 258.37 | 184.50 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 18.41 | 12.95 | 5.45 | 3.05 | 37.52 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 442.26 | 276.03 | 195.43 | 479.45 | 397.16 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: TWINDOW14
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 2.38 | 0.90 | 1.47 | 0.32 | 59.88 | 502.17 | 0.00 | 0.00 |
| February | 12.00 | 5.79 | 6.21 | 6.13 | 50.18 | 421.67 | 0.00 | 0.00 |
| March | 34.27 | 17.31 | 16.96 | 28.69 | 37.00 | 205.50 | 0.00 | 0.00 |
| April | 45.93 | 23.27 | 22.65 | 42.03 | 20.67 | 73.17 | 0.00 | 0.00 |
| May | 66.87 | 37.69 | 29.18 | 72.16 | 10.61 | 102.00 | 0.00 | 0.00 |
| June | 61.33 | 28.62 | 32.71 | 67.51 | 5.49 | 214.00 | 0.00 | 0.00 |
| July | 58.38 | 28.38 | 30.00 | 66.01 | 6.19 | 293.17 | 0.00 | 0.00 |
| August | 46.56 | 22.68 | 23.88 | 50.49 | 9.49 | 308.83 | 0.00 | 0.00 |
| September | 29.32 | 13.27 | 16.05 | 27.35 | 17.17 | 508.83 | 0.00 | 0.00 |
| October | 15.55 | 6.26 | 9.29 | 11.02 | 32.20 | 172.83 | 0.00 | 0.00 |
| November | 3.24 | 1.15 | 2.09 | 0.25 | 57.85 | 629.83 | 0.00 | 0.00 |
| December | 0.46 | 0.11 | 0.35 | 0.00 | 64.43 | 679.17 | 0.00 | 0.00 |
| Annual Sum or Average | 31.48 | 15.52 | 15.96 | 31.17 | 30.83 | 4111.17 | 0.00 | 0.00 |
| Minimum of Months | 0.46 | 0.11 | 0.35 | 0.00 | 5.49 | 73.17 | 0.00 | 0.00 |
| Maximum of Months | 66.87 | 37.69 | 32.71 | 72.16 | 64.43 | 679.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ENTRANCE DOOR
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 7.08 | 2.69 | 4.39 | 1.25 | 155.87 | 0.00 | 0.00 | 0.00 |
| February | 35.73 | 17.24 | 18.49 | 20.50 | 129.71 | 0.00 | 0.00 | 0.00 |
| March | 102.06 | 51.55 | 50.51 | 90.77 | 95.31 | 0.00 | 0.00 | 0.00 |
| April | 136.79 | 69.32 | 67.47 | 133.00 | 53.76 | 0.00 | 0.00 | 0.00 |
| May | 199.15 | 112.24 | 86.91 | 221.81 | 28.00 | 0.00 | 0.00 | 0.00 |
| June | 182.66 | 85.23 | 97.43 | 205.40 | 15.30 | 0.00 | 0.00 | 0.00 |
| July | 173.86 | 84.52 | 89.34 | 199.08 | 18.01 | 0.00 | 0.00 | 0.00 |
| August | 138.67 | 67.54 | 71.13 | 152.08 | 28.17 | 0.00 | 0.00 | 0.00 |
| September | 87.33 | 39.52 | 47.82 | 83.38 | 48.77 | 0.00 | 0.00 | 0.00 |
| October | 46.31 | 18.64 | 27.67 | 34.79 | 85.52 | 0.00 | 0.00 | 0.00 |
| November | 9.65 | 3.42 | 6.22 | 1.02 | 152.24 | 0.00 | 0.00 | 0.00 |
| December | 1.37 | 0.32 | 1.05 | 0.00 | 168.64 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 93.75 | 46.22 | 47.53 | 95.76 | 81.37 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 1.37 | 0.32 | 1.05 | 0.00 | 15.30 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 199.15 | 112.24 | 97.43 | 221.81 | 168.64 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MWINDOW14
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 2.38 | 0.90 | 1.47 | 0.28 | 63.14 | 673.83 | 0.00 | 0.00 |
| February | 12.00 | 5.79 | 6.21 | 5.82 | 53.03 | 652.17 | 0.00 | 0.00 |
| March | 34.27 | 17.31 | 16.96 | 28.05 | 39.03 | 614.00 | 0.00 | 0.00 |
| April | 45.93 | 23.27 | 22.65 | 41.17 | 21.77 | 289.33 | 0.00 | 0.00 |
| May | 66.87 | 37.69 | 29.18 | 71.00 | 11.34 | 268.33 | 0.00 | 0.00 |
| June | 61.33 | 28.62 | 32.71 | 67.23 | 5.69 | 290.17 | 0.00 | 0.00 |
| July | 58.38 | 28.38 | 30.00 | 65.81 | 6.40 | 369.67 | 0.00 | 0.00 |
| August | 46.56 | 22.68 | 23.88 | 49.77 | 10.09 | 425.67 | 0.00 | 0.00 |
| September | 29.32 | 13.27 | 16.05 | 26.29 | 18.83 | 618.33 | 0.00 | 0.00 |
| October | 15.55 | 6.26 | 9.29 | 10.64 | 34.24 | 690.67 | 0.00 | 0.00 |
| November | 3.24 | 1.15 | 2.09 | 0.21 | 61.20 | 711.33 | 0.00 | 0.00 |
| December | 0.46 | 0.11 | 0.35 | 0.00 | 67.80 | 744.00 | 0.00 | 0.00 |
| Annual Sum or Average | 31.48 | 15.52 | 15.96 | 30.69 | 32.61 | 6347.50 | 0.00 | 0.00 |
| Minimum of Months | 0.46 | 0.11 | 0.35 | 0.00 | 5.69 | 268.33 | 0.00 | 0.00 |
| Maximum of Months | 66.87 | 37.69 | 32.71 | 71.00 | 67.80 | 744.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: GWINDOW1 S SWA
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.168362E+09 | 0.112209E+09 | 56153171.53 | 95893383.20 | 0.939432E+09 |
| February | 0.508763E+09 | 0.353800E+09 | 0.154963E+09 | 0.425980E+09 | 0.674645E+09 |
| March | 0.954830E+09 | 0.643929E+09 | 0.310901E+09 | 0.938103E+09 | 0.564830E+09 |
| April | 0.114633E+10 | 0.715481E+09 | 0.430854E+09 | 0.126822E+10 | 0.341194E+09 |
| May | 0.972042E+09 | 0.503946E+09 | 0.468096E+09 | 0.111240E+10 | 0.179672E+09 |
| June | 0.860130E+09 | 0.353576E+09 | 0.506554E+09 | 0.999793E+09 | 95411486.20 |
| July | 0.856544E+09 | 0.374127E+09 | 0.482417E+09 | 0.101748E+10 | 0.106985E+09 |
| August | 0.886282E+09 | 0.489006E+09 | 0.397275E+09 | 0.103043E+10 | 0.165813E+09 |
| September | 0.682766E+09 | 0.407384E+09 | 0.275382E+09 | 0.722914E+09 | 0.278451E+09 |
| October | 0.518517E+09 | 0.328661E+09 | 0.189855E+09 | 0.471633E+09 | 0.489535E+09 |
| November | 0.270924E+09 | 0.190106E+09 | 80818039.55 | 0.172990E+09 | 0.849664E+09 |
| December | 49301472.86 | 34692762.25 | 14608710.60 | 8381473.78 | 0.105026E+10 |
| Annual Sum or Average | 0.787479E+10 | 0.450692E+10 | 0.336788E+10 | 0.826423E+10 | 0.573589E+10 |
| Minimum of Months | 49301472.86 | 34692762.25 | 14608710.60 | 8381473.78 | 95411486.20 |
| Maximum of Months | 0.114633E+10 | 0.715481E+09 | 0.506554E+09 | 0.126822E+10 | 0.105026E+10 |
Report: WindowEnergyReportMonthly
For: GWINDOW1 W SWA
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 12395449.17 | 2158724.03 | 10236725.14 | 0.00 | 0.682769E+09 |
| February | 66617010.46 | 23337954.53 | 43279055.93 | 12937121.25 | 0.522929E+09 |
| March | 0.221691E+09 | 96003775.73 | 0.125687E+09 | 0.127435E+09 | 0.414488E+09 |
| April | 0.506114E+09 | 0.262380E+09 | 0.243735E+09 | 0.492254E+09 | 0.220488E+09 |
| May | 0.507899E+09 | 0.231383E+09 | 0.276515E+09 | 0.528172E+09 | 0.108329E+09 |
| June | 0.538932E+09 | 0.230030E+09 | 0.308902E+09 | 0.598520E+09 | 56845403.37 |
| July | 0.465400E+09 | 0.175926E+09 | 0.289474E+09 | 0.519835E+09 | 65685991.08 |
| August | 0.383669E+09 | 0.163036E+09 | 0.220633E+09 | 0.401644E+09 | 0.104801E+09 |
| September | 0.223736E+09 | 93392747.47 | 0.130344E+09 | 0.181885E+09 | 0.188038E+09 |
| October | 90539706.51 | 27112847.54 | 63426858.97 | 33276517.72 | 0.370119E+09 |
| November | 35122936.17 | 12723436.19 | 22399499.98 | 3178481.02 | 0.630630E+09 |
| December | 3265476.43 | 350119.80 | 2915356.63 | 0.00 | 0.723818E+09 |
| Annual Sum or Average | 0.305538E+10 | 0.131783E+10 | 0.173755E+10 | 0.289914E+10 | 0.408894E+10 |
| Minimum of Months | 3265476.43 | 350119.80 | 2915356.63 | 0.00 | 56845403.37 |
| Maximum of Months | 0.538932E+09 | 0.262380E+09 | 0.308902E+09 | 0.598520E+09 | 0.723818E+09 |
Report: WindowEnergyReportMonthly
For: GWINDOW1 W NWA
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 12395449.17 | 2158724.03 | 10236725.14 | 0.00 | 0.681248E+09 |
| February | 66617010.46 | 23337954.53 | 43279055.93 | 13509383.59 | 0.518988E+09 |
| March | 0.221691E+09 | 96003775.73 | 0.125687E+09 | 0.130374E+09 | 0.408766E+09 |
| April | 0.506114E+09 | 0.262380E+09 | 0.243735E+09 | 0.502653E+09 | 0.214083E+09 |
| May | 0.507899E+09 | 0.231383E+09 | 0.276515E+09 | 0.542603E+09 | 0.100739E+09 |
| June | 0.538932E+09 | 0.230030E+09 | 0.308902E+09 | 0.603674E+09 | 54865302.72 |
| July | 0.465400E+09 | 0.175926E+09 | 0.289474E+09 | 0.523574E+09 | 64288799.41 |
| August | 0.383669E+09 | 0.163036E+09 | 0.220633E+09 | 0.408341E+09 | 0.100396E+09 |
| September | 0.223736E+09 | 93392747.47 | 0.130344E+09 | 0.191605E+09 | 0.175612E+09 |
| October | 90539706.51 | 27112847.54 | 63426858.97 | 34873496.11 | 0.364920E+09 |
| November | 35122936.17 | 12723436.19 | 22399499.98 | 3331021.19 | 0.628133E+09 |
| December | 3265476.43 | 350119.80 | 2915356.63 | 0.00 | 0.723252E+09 |
| Annual Sum or Average | 0.305538E+10 | 0.131783E+10 | 0.173755E+10 | 0.295454E+10 | 0.403529E+10 |
| Minimum of Months | 3265476.43 | 350119.80 | 2915356.63 | 0.00 | 54865302.72 |
| Maximum of Months | 0.538932E+09 | 0.262380E+09 | 0.308902E+09 | 0.603674E+09 | 0.723252E+09 |
Report: WindowEnergyReportMonthly
For: GWINDOW1 N NWA
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 13622807.86 | 0.00 | 13622807.86 | 0.00 | 0.104763E+10 |
| February | 54391655.15 | 0.00 | 54391655.15 | 0.00 | 0.840871E+09 |
| March | 0.161541E+09 | 53990.51 | 0.161487E+09 | 14421030.51 | 0.679604E+09 |
| April | 0.284403E+09 | 7945724.46 | 0.276457E+09 | 0.131460E+09 | 0.332998E+09 |
| May | 0.450494E+09 | 72760735.29 | 0.377733E+09 | 0.391426E+09 | 0.134389E+09 |
| June | 0.562063E+09 | 0.123352E+09 | 0.438711E+09 | 0.567642E+09 | 63789785.22 |
| July | 0.490169E+09 | 80654755.81 | 0.409514E+09 | 0.500973E+09 | 83420539.88 |
| August | 0.314910E+09 | 17029021.46 | 0.297881E+09 | 0.260129E+09 | 0.144172E+09 |
| September | 0.169525E+09 | 489125.69 | 0.169036E+09 | 72230807.88 | 0.278111E+09 |
| October | 84775064.66 | 0.00 | 84775064.66 | 6722532.59 | 0.585464E+09 |
| November | 25460057.00 | 0.00 | 25460057.00 | 0.00 | 0.995457E+09 |
| December | 4132448.42 | 0.00 | 4132448.42 | 0.00 | 0.110317E+10 |
| Annual Sum or Average | 0.261549E+10 | 0.302286E+09 | 0.231320E+10 | 0.194500E+10 | 0.628908E+10 |
| Minimum of Months | 4132448.42 | 0.00 | 4132448.42 | 0.00 | 63789785.22 |
| Maximum of Months | 0.562063E+09 | 0.123352E+09 | 0.438711E+09 | 0.567642E+09 | 0.110317E+10 |
Report: WindowEnergyReportMonthly
For: GWINDOW1 S SEA
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.168362E+09 | 0.112209E+09 | 56153171.53 | 0.101926E+09 | 0.846226E+09 |
| February | 0.508763E+09 | 0.353800E+09 | 0.154963E+09 | 0.440976E+09 | 0.605228E+09 |
| March | 0.954830E+09 | 0.643929E+09 | 0.310901E+09 | 0.960118E+09 | 0.503608E+09 |
| April | 0.114633E+10 | 0.715481E+09 | 0.430854E+09 | 0.128230E+10 | 0.311586E+09 |
| May | 0.972042E+09 | 0.503946E+09 | 0.468096E+09 | 0.110024E+10 | 0.192238E+09 |
| June | 0.860130E+09 | 0.353576E+09 | 0.506554E+09 | 0.982365E+09 | 0.111523E+09 |
| July | 0.856544E+09 | 0.374127E+09 | 0.482417E+09 | 0.992724E+09 | 0.129714E+09 |
| August | 0.886282E+09 | 0.489006E+09 | 0.397275E+09 | 0.101580E+10 | 0.190484E+09 |
| September | 0.682766E+09 | 0.407384E+09 | 0.275382E+09 | 0.718860E+09 | 0.287463E+09 |
| October | 0.518517E+09 | 0.328661E+09 | 0.189855E+09 | 0.483410E+09 | 0.446371E+09 |
| November | 0.270924E+09 | 0.190106E+09 | 80818039.55 | 0.182559E+09 | 0.767065E+09 |
| December | 49301472.86 | 34692762.25 | 14608710.60 | 9283201.48 | 0.953376E+09 |
| Annual Sum or Average | 0.787479E+10 | 0.450692E+10 | 0.336788E+10 | 0.827056E+10 | 0.534488E+10 |
| Minimum of Months | 49301472.86 | 34692762.25 | 14608710.60 | 9283201.48 | 0.111523E+09 |
| Maximum of Months | 0.114633E+10 | 0.715481E+09 | 0.506554E+09 | 0.128230E+10 | 0.953376E+09 |
Report: WindowEnergyReportMonthly
For: GWINDOW1 E SEA
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 26537662.32 | 10088926.42 | 16448735.90 | 4150803.50 | 0.602587E+09 |
| February | 0.120964E+09 | 58372632.04 | 62591246.70 | 67124166.51 | 0.449208E+09 |
| March | 0.382521E+09 | 0.193221E+09 | 0.189300E+09 | 0.336720E+09 | 0.356556E+09 |
| April | 0.496126E+09 | 0.251415E+09 | 0.244711E+09 | 0.477915E+09 | 0.189184E+09 |
| May | 0.746373E+09 | 0.420655E+09 | 0.325718E+09 | 0.823022E+09 | 0.109110E+09 |
| June | 0.662499E+09 | 0.309131E+09 | 0.353368E+09 | 0.741597E+09 | 58453336.05 |
| July | 0.651612E+09 | 0.316771E+09 | 0.334841E+09 | 0.740299E+09 | 72569328.62 |
| August | 0.519730E+09 | 0.253138E+09 | 0.266592E+09 | 0.562415E+09 | 0.113293E+09 |
| September | 0.316758E+09 | 0.143332E+09 | 0.173426E+09 | 0.294214E+09 | 0.187401E+09 |
| October | 0.173562E+09 | 69874289.31 | 0.103688E+09 | 0.129970E+09 | 0.320098E+09 |
| November | 34987210.79 | 12420027.48 | 22567183.31 | 3227533.44 | 0.571866E+09 |
| December | 5140450.97 | 1193013.76 | 3947437.20 | 0.00 | 0.656888E+09 |
| Annual Sum or Average | 0.413681E+10 | 0.203961E+10 | 0.209720E+10 | 0.418066E+10 | 0.368721E+10 |
| Minimum of Months | 5140450.97 | 1193013.76 | 3947437.20 | 0.00 | 58453336.05 |
| Maximum of Months | 0.746373E+09 | 0.420655E+09 | 0.353368E+09 | 0.823022E+09 | 0.656888E+09 |
Report: WindowEnergyReportMonthly
For: GWINDOW1 E NEA
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 26537662.32 | 10088926.42 | 16448735.90 | 3630437.66 | 0.666395E+09 |
| February | 0.120964E+09 | 58372632.04 | 62591246.70 | 62831901.00 | 0.497039E+09 |
| March | 0.382521E+09 | 0.193221E+09 | 0.189300E+09 | 0.327253E+09 | 0.395197E+09 |
| April | 0.496126E+09 | 0.251415E+09 | 0.244711E+09 | 0.476363E+09 | 0.199847E+09 |
| May | 0.746373E+09 | 0.420655E+09 | 0.325718E+09 | 0.840898E+09 | 96326861.15 |
| June | 0.662499E+09 | 0.309131E+09 | 0.353368E+09 | 0.757468E+09 | 48724756.84 |
| July | 0.651612E+09 | 0.316771E+09 | 0.334841E+09 | 0.760642E+09 | 59192915.72 |
| August | 0.519730E+09 | 0.253138E+09 | 0.266592E+09 | 0.578459E+09 | 95462409.35 |
| September | 0.316758E+09 | 0.143332E+09 | 0.173426E+09 | 0.304940E+09 | 0.170022E+09 |
| October | 0.173562E+09 | 69874289.31 | 0.103688E+09 | 0.126770E+09 | 0.347478E+09 |
| November | 34987210.79 | 12420027.48 | 22567183.31 | 2649169.33 | 0.629657E+09 |
| December | 5140450.97 | 1193013.76 | 3947437.20 | 0.00 | 0.720951E+09 |
| Annual Sum or Average | 0.413681E+10 | 0.203961E+10 | 0.209720E+10 | 0.424191E+10 | 0.392629E+10 |
| Minimum of Months | 5140450.97 | 1193013.76 | 3947437.20 | 0.00 | 48724756.84 |
| Maximum of Months | 0.746373E+09 | 0.420655E+09 | 0.353368E+09 | 0.840898E+09 | 0.720951E+09 |
Report: WindowEnergyReportMonthly
For: GWINDOW1 N NEA
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 13622807.86 | 0.00 | 13622807.86 | 0.00 | 0.104782E+10 |
| February | 54391655.15 | 0.00 | 54391655.15 | 0.00 | 0.841638E+09 |
| March | 0.161541E+09 | 53990.51 | 0.161487E+09 | 14040282.88 | 0.681577E+09 |
| April | 0.284403E+09 | 7945724.46 | 0.276457E+09 | 0.130953E+09 | 0.332210E+09 |
| May | 0.450494E+09 | 72760735.29 | 0.377733E+09 | 0.381620E+09 | 0.136471E+09 |
| June | 0.562063E+09 | 0.123352E+09 | 0.438711E+09 | 0.562680E+09 | 64307674.87 |
| July | 0.490169E+09 | 80654755.81 | 0.409514E+09 | 0.497100E+09 | 83744101.90 |
| August | 0.314910E+09 | 17029021.46 | 0.297881E+09 | 0.256422E+09 | 0.145234E+09 |
| September | 0.169525E+09 | 489125.69 | 0.169036E+09 | 69961815.52 | 0.280042E+09 |
| October | 84775064.66 | 0.00 | 84775064.66 | 6502243.74 | 0.586857E+09 |
| November | 25460057.00 | 0.00 | 25460057.00 | 0.00 | 0.995461E+09 |
| December | 4132448.42 | 0.00 | 4132448.42 | 0.00 | 0.110320E+10 |
| Annual Sum or Average | 0.261549E+10 | 0.302286E+09 | 0.231320E+10 | 0.191928E+10 | 0.629857E+10 |
| Minimum of Months | 4132448.42 | 0.00 | 4132448.42 | 0.00 | 64307674.87 |
| Maximum of Months | 0.562063E+09 | 0.123352E+09 | 0.438711E+09 | 0.562680E+09 | 0.110320E+10 |
Report: WindowEnergyReportMonthly
For: GWINDOW1 N N1A
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 13622807.86 | 0.00 | 13622807.86 | 0.00 | 0.106170E+10 |
| February | 54391655.15 | 0.00 | 54391655.15 | 0.00 | 0.853748E+09 |
| March | 0.161541E+09 | 53990.51 | 0.161487E+09 | 13595345.98 | 0.690738E+09 |
| April | 0.284403E+09 | 7945724.46 | 0.276457E+09 | 0.130418E+09 | 0.336767E+09 |
| May | 0.450494E+09 | 72760735.29 | 0.377733E+09 | 0.387916E+09 | 0.136647E+09 |
| June | 0.562063E+09 | 0.123352E+09 | 0.438711E+09 | 0.565791E+09 | 64963772.28 |
| July | 0.490169E+09 | 80654755.81 | 0.409514E+09 | 0.500353E+09 | 84345682.59 |
| August | 0.314910E+09 | 17029021.46 | 0.297881E+09 | 0.258483E+09 | 0.146420E+09 |
| September | 0.169525E+09 | 489125.69 | 0.169036E+09 | 70475933.50 | 0.283159E+09 |
| October | 84775064.66 | 0.00 | 84775064.66 | 6401986.86 | 0.593864E+09 |
| November | 25460057.00 | 0.00 | 25460057.00 | 0.00 | 0.100705E+10 |
| December | 4132448.42 | 0.00 | 4132448.42 | 0.00 | 0.111672E+10 |
| Annual Sum or Average | 0.261549E+10 | 0.302286E+09 | 0.231320E+10 | 0.193343E+10 | 0.637612E+10 |
| Minimum of Months | 4132448.42 | 0.00 | 4132448.42 | 0.00 | 64963772.28 |
| Maximum of Months | 0.562063E+09 | 0.123352E+09 | 0.438711E+09 | 0.565791E+09 | 0.111672E+10 |
Report: WindowEnergyReportMonthly
For: GWINDOW1 N N2A
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 13622807.86 | 0.00 | 13622807.86 | 0.00 | 0.106171E+10 |
| February | 54391655.15 | 0.00 | 54391655.15 | 0.00 | 0.853780E+09 |
| March | 0.161541E+09 | 53990.51 | 0.161487E+09 | 13580214.59 | 0.690830E+09 |
| April | 0.284403E+09 | 7945724.46 | 0.276457E+09 | 0.130398E+09 | 0.336728E+09 |
| May | 0.450494E+09 | 72760735.29 | 0.377733E+09 | 0.386784E+09 | 0.137103E+09 |
| June | 0.562063E+09 | 0.123352E+09 | 0.438711E+09 | 0.565297E+09 | 65084438.73 |
| July | 0.490169E+09 | 80654755.81 | 0.409514E+09 | 0.500143E+09 | 84393725.46 |
| August | 0.314910E+09 | 17029021.46 | 0.297881E+09 | 0.258203E+09 | 0.146595E+09 |
| September | 0.169525E+09 | 489125.69 | 0.169036E+09 | 70221355.89 | 0.283529E+09 |
| October | 84775064.66 | 0.00 | 84775064.66 | 6386969.23 | 0.593962E+09 |
| November | 25460057.00 | 0.00 | 25460057.00 | 0.00 | 0.100705E+10 |
| December | 4132448.42 | 0.00 | 4132448.42 | 0.00 | 0.111672E+10 |
| Annual Sum or Average | 0.261549E+10 | 0.302286E+09 | 0.231320E+10 | 0.193101E+10 | 0.637748E+10 |
| Minimum of Months | 4132448.42 | 0.00 | 4132448.42 | 0.00 | 65084438.73 |
| Maximum of Months | 0.562063E+09 | 0.123352E+09 | 0.438711E+09 | 0.565297E+09 | 0.111672E+10 |
Report: WindowEnergyReportMonthly
For: GWINDOW1 S S1A
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.168362E+09 | 0.112209E+09 | 56153171.53 | 94787601.20 | 0.952477E+09 |
| February | 0.508763E+09 | 0.353800E+09 | 0.154963E+09 | 0.422774E+09 | 0.685117E+09 |
| March | 0.954830E+09 | 0.643929E+09 | 0.310901E+09 | 0.933493E+09 | 0.573845E+09 |
| April | 0.114633E+10 | 0.715481E+09 | 0.430854E+09 | 0.126465E+10 | 0.346080E+09 |
| May | 0.972042E+09 | 0.503946E+09 | 0.468096E+09 | 0.110654E+10 | 0.185911E+09 |
| June | 0.860130E+09 | 0.353576E+09 | 0.506554E+09 | 0.998549E+09 | 97159889.88 |
| July | 0.856544E+09 | 0.374127E+09 | 0.482417E+09 | 0.101725E+10 | 0.108099E+09 |
| August | 0.886282E+09 | 0.489006E+09 | 0.397275E+09 | 0.102938E+10 | 0.168053E+09 |
| September | 0.682766E+09 | 0.407384E+09 | 0.275382E+09 | 0.718131E+09 | 0.287126E+09 |
| October | 0.518517E+09 | 0.328661E+09 | 0.189855E+09 | 0.468716E+09 | 0.497101E+09 |
| November | 0.270924E+09 | 0.190106E+09 | 80818039.55 | 0.171339E+09 | 0.859962E+09 |
| December | 49301472.86 | 34692762.25 | 14608710.60 | 8188213.19 | 0.106355E+10 |
| Annual Sum or Average | 0.787479E+10 | 0.450692E+10 | 0.336788E+10 | 0.823380E+10 | 0.582448E+10 |
| Minimum of Months | 49301472.86 | 34692762.25 | 14608710.60 | 8188213.19 | 97159889.88 |
| Maximum of Months | 0.114633E+10 | 0.715481E+09 | 0.506554E+09 | 0.126465E+10 | 0.106355E+10 |
Report: WindowEnergyReportMonthly
For: GWINDOW1 S S2A
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.168362E+09 | 0.112209E+09 | 56153171.53 | 94999950.09 | 0.949464E+09 |
| February | 0.508763E+09 | 0.353800E+09 | 0.154963E+09 | 0.423363E+09 | 0.682882E+09 |
| March | 0.954830E+09 | 0.643929E+09 | 0.310901E+09 | 0.934458E+09 | 0.571674E+09 |
| April | 0.114633E+10 | 0.715481E+09 | 0.430854E+09 | 0.126561E+10 | 0.344481E+09 |
| May | 0.972042E+09 | 0.503946E+09 | 0.468096E+09 | 0.110500E+10 | 0.187223E+09 |
| June | 0.860130E+09 | 0.353576E+09 | 0.506554E+09 | 0.997327E+09 | 97939586.53 |
| July | 0.856544E+09 | 0.374127E+09 | 0.482417E+09 | 0.101594E+10 | 0.109001E+09 |
| August | 0.886282E+09 | 0.489006E+09 | 0.397275E+09 | 0.102835E+10 | 0.169100E+09 |
| September | 0.682766E+09 | 0.407384E+09 | 0.275382E+09 | 0.717279E+09 | 0.288315E+09 |
| October | 0.518517E+09 | 0.328661E+09 | 0.189855E+09 | 0.469273E+09 | 0.495257E+09 |
| November | 0.270924E+09 | 0.190106E+09 | 80818039.55 | 0.171708E+09 | 0.857202E+09 |
| December | 49301472.86 | 34692762.25 | 14608710.60 | 8218942.89 | 0.106051E+10 |
| Annual Sum or Average | 0.787479E+10 | 0.450692E+10 | 0.336788E+10 | 0.823152E+10 | 0.581305E+10 |
| Minimum of Months | 49301472.86 | 34692762.25 | 14608710.60 | 8218942.89 | 97939586.53 |
| Maximum of Months | 0.114633E+10 | 0.715481E+09 | 0.506554E+09 | 0.126561E+10 | 0.106051E+10 |
Report: WindowEnergyReportMonthly
For: MWINDOW1 S SWA
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.168362E+09 | 0.112209E+09 | 56153171.53 | 93625795.35 | 0.964741E+09 |
| February | 0.508763E+09 | 0.353800E+09 | 0.154963E+09 | 0.418438E+09 | 0.696677E+09 |
| March | 0.954830E+09 | 0.643929E+09 | 0.310901E+09 | 0.923502E+09 | 0.587522E+09 |
| April | 0.114633E+10 | 0.715481E+09 | 0.430854E+09 | 0.124396E+10 | 0.367901E+09 |
| May | 0.972042E+09 | 0.503946E+09 | 0.468096E+09 | 0.108357E+10 | 0.206299E+09 |
| June | 0.860130E+09 | 0.353576E+09 | 0.506554E+09 | 0.986404E+09 | 0.102782E+09 |
| July | 0.856544E+09 | 0.374127E+09 | 0.482417E+09 | 0.100925E+10 | 0.111103E+09 |
| August | 0.886282E+09 | 0.489006E+09 | 0.397275E+09 | 0.102429E+10 | 0.169915E+09 |
| September | 0.682766E+09 | 0.407384E+09 | 0.275382E+09 | 0.713822E+09 | 0.290905E+09 |
| October | 0.518517E+09 | 0.328661E+09 | 0.189855E+09 | 0.465535E+09 | 0.502307E+09 |
| November | 0.270924E+09 | 0.190106E+09 | 80818039.55 | 0.170123E+09 | 0.865827E+09 |
| December | 49301472.86 | 34692762.25 | 14608710.60 | 8044996.72 | 0.107466E+10 |
| Annual Sum or Average | 0.787479E+10 | 0.450692E+10 | 0.336788E+10 | 0.814056E+10 | 0.594064E+10 |
| Minimum of Months | 49301472.86 | 34692762.25 | 14608710.60 | 8044996.72 | 0.102782E+09 |
| Maximum of Months | 0.114633E+10 | 0.715481E+09 | 0.506554E+09 | 0.124396E+10 | 0.107466E+10 |
Report: WindowEnergyReportMonthly
For: MWINDOW1 W SWA
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 12395449.17 | 2158724.03 | 10236725.14 | 0.00 | 0.701320E+09 |
| February | 66617010.46 | 23337954.53 | 43279055.93 | 12005541.14 | 0.541515E+09 |
| March | 0.221691E+09 | 96003775.73 | 0.125687E+09 | 0.122177E+09 | 0.433716E+09 |
| April | 0.506114E+09 | 0.262380E+09 | 0.243735E+09 | 0.475132E+09 | 0.237099E+09 |
| May | 0.507899E+09 | 0.231383E+09 | 0.276515E+09 | 0.507301E+09 | 0.123995E+09 |
| June | 0.538932E+09 | 0.230030E+09 | 0.308902E+09 | 0.589157E+09 | 61167712.09 |
| July | 0.465400E+09 | 0.175926E+09 | 0.289474E+09 | 0.514293E+09 | 68181940.41 |
| August | 0.383669E+09 | 0.163036E+09 | 0.220633E+09 | 0.397586E+09 | 0.107387E+09 |
| September | 0.223736E+09 | 93392747.47 | 0.130344E+09 | 0.176762E+09 | 0.197075E+09 |
| October | 90539706.51 | 27112847.54 | 63426858.97 | 31723461.84 | 0.381058E+09 |
| November | 35122936.17 | 12723436.19 | 22399499.98 | 2992187.39 | 0.643199E+09 |
| December | 3265476.43 | 350119.80 | 2915356.63 | 0.00 | 0.740651E+09 |
| Annual Sum or Average | 0.305538E+10 | 0.131783E+10 | 0.173755E+10 | 0.282913E+10 | 0.423636E+10 |
| Minimum of Months | 3265476.43 | 350119.80 | 2915356.63 | 0.00 | 61167712.09 |
| Maximum of Months | 0.538932E+09 | 0.262380E+09 | 0.308902E+09 | 0.589157E+09 | 0.740651E+09 |
Report: WindowEnergyReportMonthly
For: MWINDOW1 W NWA
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 12395449.17 | 2158724.03 | 10236725.14 | 0.00 | 0.699830E+09 |
| February | 66617010.46 | 23337954.53 | 43279055.93 | 12668671.39 | 0.537308E+09 |
| March | 0.221691E+09 | 96003775.73 | 0.125687E+09 | 0.125835E+09 | 0.427082E+09 |
| April | 0.506114E+09 | 0.262380E+09 | 0.243735E+09 | 0.488866E+09 | 0.227729E+09 |
| May | 0.507899E+09 | 0.231383E+09 | 0.276515E+09 | 0.514338E+09 | 0.120316E+09 |
| June | 0.538932E+09 | 0.230030E+09 | 0.308902E+09 | 0.591640E+09 | 60992719.24 |
| July | 0.465400E+09 | 0.175926E+09 | 0.289474E+09 | 0.517022E+09 | 67688384.16 |
| August | 0.383669E+09 | 0.163036E+09 | 0.220633E+09 | 0.402476E+09 | 0.105071E+09 |
| September | 0.223736E+09 | 93392747.47 | 0.130344E+09 | 0.185668E+09 | 0.185694E+09 |
| October | 90539706.51 | 27112847.54 | 63426858.97 | 33650663.91 | 0.375677E+09 |
| November | 35122936.17 | 12723436.19 | 22399499.98 | 3158852.49 | 0.640876E+09 |
| December | 3265476.43 | 350119.80 | 2915356.63 | 0.00 | 0.740189E+09 |
| Annual Sum or Average | 0.305538E+10 | 0.131783E+10 | 0.173755E+10 | 0.287532E+10 | 0.418845E+10 |
| Minimum of Months | 3265476.43 | 350119.80 | 2915356.63 | 0.00 | 60992719.24 |
| Maximum of Months | 0.538932E+09 | 0.262380E+09 | 0.308902E+09 | 0.591640E+09 | 0.740189E+09 |
Report: WindowEnergyReportMonthly
For: MWINDOW1 N NWA
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 13622807.86 | 0.00 | 13622807.86 | 0.00 | 0.107589E+10 |
| February | 54391655.15 | 0.00 | 54391655.15 | 0.00 | 0.870235E+09 |
| March | 0.161541E+09 | 53990.51 | 0.161487E+09 | 11932340.07 | 0.711163E+09 |
| April | 0.284403E+09 | 7945724.46 | 0.276457E+09 | 0.115527E+09 | 0.357413E+09 |
| May | 0.450494E+09 | 72760735.29 | 0.377733E+09 | 0.343661E+09 | 0.159112E+09 |
| June | 0.562063E+09 | 0.123352E+09 | 0.438711E+09 | 0.547011E+09 | 70105521.73 |
| July | 0.490169E+09 | 80654755.81 | 0.409514E+09 | 0.490530E+09 | 87508088.87 |
| August | 0.314910E+09 | 17029021.46 | 0.297881E+09 | 0.251530E+09 | 0.150697E+09 |
| September | 0.169525E+09 | 489125.69 | 0.169036E+09 | 65290392.13 | 0.294963E+09 |
| October | 84775064.66 | 0.00 | 84775064.66 | 5903898.42 | 0.602554E+09 |
| November | 25460057.00 | 0.00 | 25460057.00 | 0.00 | 0.101512E+10 |
| December | 4132448.42 | 0.00 | 4132448.42 | 0.00 | 0.112868E+10 |
| Annual Sum or Average | 0.261549E+10 | 0.302286E+09 | 0.231320E+10 | 0.183139E+10 | 0.652345E+10 |
| Minimum of Months | 4132448.42 | 0.00 | 4132448.42 | 0.00 | 70105521.73 |
| Maximum of Months | 0.562063E+09 | 0.123352E+09 | 0.438711E+09 | 0.547011E+09 | 0.112868E+10 |
Report: WindowEnergyReportMonthly
For: MWINDOW1 S SEA
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.168362E+09 | 0.112209E+09 | 56153171.53 | 93520694.69 | 0.964846E+09 |
| February | 0.508763E+09 | 0.353800E+09 | 0.154963E+09 | 0.417782E+09 | 0.696958E+09 |
| March | 0.954830E+09 | 0.643929E+09 | 0.310901E+09 | 0.920922E+09 | 0.588376E+09 |
| April | 0.114633E+10 | 0.715481E+09 | 0.430854E+09 | 0.124156E+10 | 0.366195E+09 |
| May | 0.972042E+09 | 0.503946E+09 | 0.468096E+09 | 0.107935E+10 | 0.207130E+09 |
| June | 0.860130E+09 | 0.353576E+09 | 0.506554E+09 | 0.984436E+09 | 0.102633E+09 |
| July | 0.856544E+09 | 0.374127E+09 | 0.482417E+09 | 0.100673E+10 | 0.111102E+09 |
| August | 0.886282E+09 | 0.489006E+09 | 0.397275E+09 | 0.102209E+10 | 0.170147E+09 |
| September | 0.682766E+09 | 0.407384E+09 | 0.275382E+09 | 0.711304E+09 | 0.291893E+09 |
| October | 0.518517E+09 | 0.328661E+09 | 0.189855E+09 | 0.464044E+09 | 0.503301E+09 |
| November | 0.270924E+09 | 0.190106E+09 | 80818039.55 | 0.170055E+09 | 0.865756E+09 |
| December | 49301472.86 | 34692762.25 | 14608710.60 | 8040102.75 | 0.107468E+10 |
| Annual Sum or Average | 0.787479E+10 | 0.450692E+10 | 0.336788E+10 | 0.811983E+10 | 0.594302E+10 |
| Minimum of Months | 49301472.86 | 34692762.25 | 14608710.60 | 8040102.75 | 0.102633E+09 |
| Maximum of Months | 0.114633E+10 | 0.715481E+09 | 0.506554E+09 | 0.124156E+10 | 0.107468E+10 |
Report: WindowEnergyReportMonthly
For: MWINDOW1 E SEA
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 26537662.32 | 10088926.42 | 16448735.90 | 3316219.01 | 0.686429E+09 |
| February | 0.120964E+09 | 58372632.04 | 62591246.70 | 60099675.23 | 0.518882E+09 |
| March | 0.382521E+09 | 0.193221E+09 | 0.189300E+09 | 0.317677E+09 | 0.419751E+09 |
| April | 0.496126E+09 | 0.251415E+09 | 0.244711E+09 | 0.449505E+09 | 0.224021E+09 |
| May | 0.746373E+09 | 0.420655E+09 | 0.325718E+09 | 0.805967E+09 | 0.116368E+09 |
| June | 0.662499E+09 | 0.309131E+09 | 0.353368E+09 | 0.743807E+09 | 53524246.94 |
| July | 0.651612E+09 | 0.316771E+09 | 0.334841E+09 | 0.751583E+09 | 62489993.30 |
| August | 0.519730E+09 | 0.253138E+09 | 0.266592E+09 | 0.568032E+09 | 0.101459E+09 |
| September | 0.316758E+09 | 0.143332E+09 | 0.173426E+09 | 0.289470E+09 | 0.190743E+09 |
| October | 0.173562E+09 | 69874289.31 | 0.103688E+09 | 0.122356E+09 | 0.363229E+09 |
| November | 34987210.79 | 12420027.48 | 22567183.31 | 2403818.40 | 0.645152E+09 |
| December | 5140450.97 | 1193013.76 | 3947437.20 | 0.00 | 0.738459E+09 |
| Annual Sum or Average | 0.413681E+10 | 0.203961E+10 | 0.209720E+10 | 0.411422E+10 | 0.412051E+10 |
| Minimum of Months | 5140450.97 | 1193013.76 | 3947437.20 | 0.00 | 53524246.94 |
| Maximum of Months | 0.746373E+09 | 0.420655E+09 | 0.353368E+09 | 0.805967E+09 | 0.738459E+09 |
Report: WindowEnergyReportMonthly
For: MWINDOW1 E NEA
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 26537662.32 | 10088926.42 | 16448735.90 | 3390128.03 | 0.684993E+09 |
| February | 0.120964E+09 | 58372632.04 | 62591246.70 | 60821830.56 | 0.514632E+09 |
| March | 0.382521E+09 | 0.193221E+09 | 0.189300E+09 | 0.320795E+09 | 0.412219E+09 |
| April | 0.496126E+09 | 0.251415E+09 | 0.244711E+09 | 0.462257E+09 | 0.213041E+09 |
| May | 0.746373E+09 | 0.420655E+09 | 0.325718E+09 | 0.811932E+09 | 0.113127E+09 |
| June | 0.662499E+09 | 0.309131E+09 | 0.353368E+09 | 0.746048E+09 | 53018137.04 |
| July | 0.651612E+09 | 0.316771E+09 | 0.334841E+09 | 0.754147E+09 | 61793535.78 |
| August | 0.519730E+09 | 0.253138E+09 | 0.266592E+09 | 0.572544E+09 | 99176432.35 |
| September | 0.316758E+09 | 0.143332E+09 | 0.173426E+09 | 0.297359E+09 | 0.180326E+09 |
| October | 0.173562E+09 | 69874289.31 | 0.103688E+09 | 0.124427E+09 | 0.357334E+09 |
| November | 34987210.79 | 12420027.48 | 22567183.31 | 2472812.06 | 0.642722E+09 |
| December | 5140450.97 | 1193013.76 | 3947437.20 | 0.00 | 0.737996E+09 |
| Annual Sum or Average | 0.413681E+10 | 0.203961E+10 | 0.209720E+10 | 0.415619E+10 | 0.407038E+10 |
| Minimum of Months | 5140450.97 | 1193013.76 | 3947437.20 | 0.00 | 53018137.04 |
| Maximum of Months | 0.746373E+09 | 0.420655E+09 | 0.353368E+09 | 0.811932E+09 | 0.737996E+09 |
Report: WindowEnergyReportMonthly
For: MWINDOW1 N NEA
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 13622807.86 | 0.00 | 13622807.86 | 0.00 | 0.107608E+10 |
| February | 54391655.15 | 0.00 | 54391655.15 | 0.00 | 0.871027E+09 |
| March | 0.161541E+09 | 53990.51 | 0.161487E+09 | 11478226.37 | 0.713524E+09 |
| April | 0.284403E+09 | 7945724.46 | 0.276457E+09 | 0.114104E+09 | 0.355795E+09 |
| May | 0.450494E+09 | 72760735.29 | 0.377733E+09 | 0.336703E+09 | 0.159939E+09 |
| June | 0.562063E+09 | 0.123352E+09 | 0.438711E+09 | 0.544802E+09 | 69858847.28 |
| July | 0.490169E+09 | 80654755.81 | 0.409514E+09 | 0.487696E+09 | 87379427.49 |
| August | 0.314910E+09 | 17029021.46 | 0.297881E+09 | 0.248586E+09 | 0.151095E+09 |
| September | 0.169525E+09 | 489125.69 | 0.169036E+09 | 61860622.62 | 0.298258E+09 |
| October | 84775064.66 | 0.00 | 84775064.66 | 5695132.17 | 0.603941E+09 |
| November | 25460057.00 | 0.00 | 25460057.00 | 0.00 | 0.101511E+10 |
| December | 4132448.42 | 0.00 | 4132448.42 | 0.00 | 0.112871E+10 |
| Annual Sum or Average | 0.261549E+10 | 0.302286E+09 | 0.231320E+10 | 0.181092E+10 | 0.653073E+10 |
| Minimum of Months | 4132448.42 | 0.00 | 4132448.42 | 0.00 | 69858847.28 |
| Maximum of Months | 0.562063E+09 | 0.123352E+09 | 0.438711E+09 | 0.544802E+09 | 0.112871E+10 |
Report: WindowEnergyReportMonthly
For: MWINDOW1 N N1A
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 13622807.86 | 0.00 | 13622807.86 | 0.00 | 0.108744E+10 |
| February | 54391655.15 | 0.00 | 54391655.15 | 0.00 | 0.879814E+09 |
| March | 0.161541E+09 | 53990.51 | 0.161487E+09 | 11430537.78 | 0.719037E+09 |
| April | 0.284403E+09 | 7945724.46 | 0.276457E+09 | 0.116692E+09 | 0.357889E+09 |
| May | 0.450494E+09 | 72760735.29 | 0.377733E+09 | 0.342676E+09 | 0.160622E+09 |
| June | 0.562063E+09 | 0.123352E+09 | 0.438711E+09 | 0.550049E+09 | 69798475.18 |
| July | 0.490169E+09 | 80654755.81 | 0.409514E+09 | 0.493003E+09 | 87204090.50 |
| August | 0.314910E+09 | 17029021.46 | 0.297881E+09 | 0.251781E+09 | 0.151708E+09 |
| September | 0.169525E+09 | 489125.69 | 0.169036E+09 | 62382902.11 | 0.303181E+09 |
| October | 84775064.66 | 0.00 | 84775064.66 | 5617269.83 | 0.611098E+09 |
| November | 25460057.00 | 0.00 | 25460057.00 | 0.00 | 0.102584E+10 |
| December | 4132448.42 | 0.00 | 4132448.42 | 0.00 | 0.114057E+10 |
| Annual Sum or Average | 0.261549E+10 | 0.302286E+09 | 0.231320E+10 | 0.183363E+10 | 0.659420E+10 |
| Minimum of Months | 4132448.42 | 0.00 | 4132448.42 | 0.00 | 69798475.18 |
| Maximum of Months | 0.562063E+09 | 0.123352E+09 | 0.438711E+09 | 0.550049E+09 | 0.114057E+10 |
Report: WindowEnergyReportMonthly
For: MWINDOW1 N N2A
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 13622807.86 | 0.00 | 13622807.86 | 0.00 | 0.108745E+10 |
| February | 54391655.15 | 0.00 | 54391655.15 | 0.00 | 0.879852E+09 |
| March | 0.161541E+09 | 53990.51 | 0.161487E+09 | 11408789.37 | 0.719178E+09 |
| April | 0.284403E+09 | 7945724.46 | 0.276457E+09 | 0.116606E+09 | 0.357808E+09 |
| May | 0.450494E+09 | 72760735.29 | 0.377733E+09 | 0.342072E+09 | 0.160899E+09 |
| June | 0.562063E+09 | 0.123352E+09 | 0.438711E+09 | 0.549966E+09 | 69797661.10 |
| July | 0.490169E+09 | 80654755.81 | 0.409514E+09 | 0.492901E+09 | 87210384.67 |
| August | 0.314910E+09 | 17029021.46 | 0.297881E+09 | 0.251634E+09 | 0.151781E+09 |
| September | 0.169525E+09 | 489125.69 | 0.169036E+09 | 61940244.16 | 0.303920E+09 |
| October | 84775064.66 | 0.00 | 84775064.66 | 5602105.39 | 0.611201E+09 |
| November | 25460057.00 | 0.00 | 25460057.00 | 0.00 | 0.102584E+10 |
| December | 4132448.42 | 0.00 | 4132448.42 | 0.00 | 0.114057E+10 |
| Annual Sum or Average | 0.261549E+10 | 0.302286E+09 | 0.231320E+10 | 0.183213E+10 | 0.659551E+10 |
| Minimum of Months | 4132448.42 | 0.00 | 4132448.42 | 0.00 | 69797661.10 |
| Maximum of Months | 0.562063E+09 | 0.123352E+09 | 0.438711E+09 | 0.549966E+09 | 0.114057E+10 |
Report: WindowEnergyReportMonthly
For: MWINDOW1 S S1A
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.168362E+09 | 0.112209E+09 | 56153171.53 | 92687705.63 | 0.975766E+09 |
| February | 0.508763E+09 | 0.353800E+09 | 0.154963E+09 | 0.415833E+09 | 0.705297E+09 |
| March | 0.954830E+09 | 0.643929E+09 | 0.310901E+09 | 0.919693E+09 | 0.594622E+09 |
| April | 0.114633E+10 | 0.715481E+09 | 0.430854E+09 | 0.124169E+10 | 0.371856E+09 |
| May | 0.972042E+09 | 0.503946E+09 | 0.468096E+09 | 0.108292E+10 | 0.208585E+09 |
| June | 0.860130E+09 | 0.353576E+09 | 0.506554E+09 | 0.988848E+09 | 0.102167E+09 |
| July | 0.856544E+09 | 0.374127E+09 | 0.482417E+09 | 0.101133E+10 | 0.110696E+09 |
| August | 0.886282E+09 | 0.489006E+09 | 0.397275E+09 | 0.102469E+10 | 0.170833E+09 |
| September | 0.682766E+09 | 0.407384E+09 | 0.275382E+09 | 0.710184E+09 | 0.298420E+09 |
| October | 0.518517E+09 | 0.328661E+09 | 0.189855E+09 | 0.461962E+09 | 0.511493E+09 |
| November | 0.270924E+09 | 0.190106E+09 | 80818039.55 | 0.168552E+09 | 0.875805E+09 |
| December | 49301472.86 | 34692762.25 | 14608710.60 | 7882760.39 | 0.108648E+10 |
| Annual Sum or Average | 0.787479E+10 | 0.450692E+10 | 0.336788E+10 | 0.812627E+10 | 0.601202E+10 |
| Minimum of Months | 49301472.86 | 34692762.25 | 14608710.60 | 7882760.39 | 0.102167E+09 |
| Maximum of Months | 0.114633E+10 | 0.715481E+09 | 0.506554E+09 | 0.124169E+10 | 0.108648E+10 |
Report: WindowEnergyReportMonthly
For: MWINDOW1 S S2A
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.168362E+09 | 0.112209E+09 | 56153171.53 | 92684791.54 | 0.975774E+09 |
| February | 0.508763E+09 | 0.353800E+09 | 0.154963E+09 | 0.415809E+09 | 0.705326E+09 |
| March | 0.954830E+09 | 0.643929E+09 | 0.310901E+09 | 0.919553E+09 | 0.594723E+09 |
| April | 0.114633E+10 | 0.715481E+09 | 0.430854E+09 | 0.124156E+10 | 0.371804E+09 |
| May | 0.972042E+09 | 0.503946E+09 | 0.468096E+09 | 0.108270E+10 | 0.208693E+09 |
| June | 0.860130E+09 | 0.353576E+09 | 0.506554E+09 | 0.988773E+09 | 0.102166E+09 |
| July | 0.856544E+09 | 0.374127E+09 | 0.482417E+09 | 0.101124E+10 | 0.110703E+09 |
| August | 0.886282E+09 | 0.489006E+09 | 0.397275E+09 | 0.102460E+10 | 0.170854E+09 |
| September | 0.682766E+09 | 0.407384E+09 | 0.275382E+09 | 0.710024E+09 | 0.298567E+09 |
| October | 0.518517E+09 | 0.328661E+09 | 0.189855E+09 | 0.461844E+09 | 0.511681E+09 |
| November | 0.270924E+09 | 0.190106E+09 | 80818039.55 | 0.168549E+09 | 0.875803E+09 |
| December | 49301472.86 | 34692762.25 | 14608710.60 | 7882677.98 | 0.108648E+10 |
| Annual Sum or Average | 0.787479E+10 | 0.450692E+10 | 0.336788E+10 | 0.812522E+10 | 0.601257E+10 |
| Minimum of Months | 49301472.86 | 34692762.25 | 14608710.60 | 7882677.98 | 0.102166E+09 |
| Maximum of Months | 0.114633E+10 | 0.715481E+09 | 0.506554E+09 | 0.124156E+10 | 0.108648E+10 |
Report: WindowEnergyReportMonthly
For: TWINDOW1 S SWA
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.168362E+09 | 0.112209E+09 | 56153171.53 | 95149371.48 | 0.941653E+09 |
| February | 0.508763E+09 | 0.353800E+09 | 0.154963E+09 | 0.421718E+09 | 0.679040E+09 |
| March | 0.954830E+09 | 0.643929E+09 | 0.310901E+09 | 0.925336E+09 | 0.572022E+09 |
| April | 0.114633E+10 | 0.715481E+09 | 0.430854E+09 | 0.124436E+10 | 0.352315E+09 |
| May | 0.972042E+09 | 0.503946E+09 | 0.468096E+09 | 0.108900E+10 | 0.188001E+09 |
| June | 0.860130E+09 | 0.353576E+09 | 0.506554E+09 | 0.984410E+09 | 96328171.66 |
| July | 0.856544E+09 | 0.374127E+09 | 0.482417E+09 | 0.100666E+10 | 0.104842E+09 |
| August | 0.886282E+09 | 0.489006E+09 | 0.397275E+09 | 0.102690E+10 | 0.156905E+09 |
| September | 0.682766E+09 | 0.407384E+09 | 0.275382E+09 | 0.722613E+09 | 0.266766E+09 |
| October | 0.518517E+09 | 0.328661E+09 | 0.189855E+09 | 0.468644E+09 | 0.486562E+09 |
| November | 0.270924E+09 | 0.190106E+09 | 80818039.55 | 0.172931E+09 | 0.843469E+09 |
| December | 49301472.86 | 34692762.25 | 14608710.60 | 8379845.96 | 0.104974E+10 |
| Annual Sum or Average | 0.787479E+10 | 0.450692E+10 | 0.336788E+10 | 0.816609E+10 | 0.573765E+10 |
| Minimum of Months | 49301472.86 | 34692762.25 | 14608710.60 | 8379845.96 | 96328171.66 |
| Maximum of Months | 0.114633E+10 | 0.715481E+09 | 0.506554E+09 | 0.124436E+10 | 0.104974E+10 |
Report: WindowEnergyReportMonthly
For: TWINDOW1 W SWA
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 12395449.17 | 2158724.03 | 10236725.14 | 0.00 | 0.684855E+09 |
| February | 66617010.46 | 23337954.53 | 43279055.93 | 12155086.95 | 0.527826E+09 |
| March | 0.221691E+09 | 96003775.73 | 0.125687E+09 | 0.121641E+09 | 0.421646E+09 |
| April | 0.506114E+09 | 0.262380E+09 | 0.243735E+09 | 0.474116E+09 | 0.225441E+09 |
| May | 0.507899E+09 | 0.231383E+09 | 0.276515E+09 | 0.511115E+09 | 0.111786E+09 |
| June | 0.538932E+09 | 0.230030E+09 | 0.308902E+09 | 0.587979E+09 | 56790128.23 |
| July | 0.465400E+09 | 0.175926E+09 | 0.289474E+09 | 0.512651E+09 | 63878130.81 |
| August | 0.383669E+09 | 0.163036E+09 | 0.220633E+09 | 0.399181E+09 | 98445531.01 |
| September | 0.223736E+09 | 93392747.47 | 0.130344E+09 | 0.181165E+09 | 0.179576E+09 |
| October | 90539706.51 | 27112847.54 | 63426858.97 | 32027298.81 | 0.368777E+09 |
| November | 35122936.17 | 12723436.19 | 22399499.98 | 3098058.48 | 0.626481E+09 |
| December | 3265476.43 | 350119.80 | 2915356.63 | 0.00 | 0.723739E+09 |
| Annual Sum or Average | 0.305538E+10 | 0.131783E+10 | 0.173755E+10 | 0.283513E+10 | 0.408924E+10 |
| Minimum of Months | 3265476.43 | 350119.80 | 2915356.63 | 0.00 | 56790128.23 |
| Maximum of Months | 0.538932E+09 | 0.262380E+09 | 0.308902E+09 | 0.587979E+09 | 0.723739E+09 |
Report: WindowEnergyReportMonthly
For: TWINDOW1 W NWA
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 12395449.17 | 2158724.03 | 10236725.14 | 0.00 | 0.683228E+09 |
| February | 66617010.46 | 23337954.53 | 43279055.93 | 13124324.65 | 0.523575E+09 |
| March | 0.221691E+09 | 96003775.73 | 0.125687E+09 | 0.127066E+09 | 0.415445E+09 |
| April | 0.506114E+09 | 0.262380E+09 | 0.243735E+09 | 0.489616E+09 | 0.220076E+09 |
| May | 0.507899E+09 | 0.231383E+09 | 0.276515E+09 | 0.520358E+09 | 0.109517E+09 |
| June | 0.538932E+09 | 0.230030E+09 | 0.308902E+09 | 0.590650E+09 | 57381636.52 |
| July | 0.465400E+09 | 0.175926E+09 | 0.289474E+09 | 0.516068E+09 | 63720188.94 |
| August | 0.383669E+09 | 0.163036E+09 | 0.220633E+09 | 0.407020E+09 | 95903680.55 |
| September | 0.223736E+09 | 93392747.47 | 0.130344E+09 | 0.190268E+09 | 0.173308E+09 |
| October | 90539706.51 | 27112847.54 | 63426858.97 | 34498455.25 | 0.364216E+09 |
| November | 35122936.17 | 12723436.19 | 22399499.98 | 3364577.24 | 0.624085E+09 |
| December | 3265476.43 | 350119.80 | 2915356.63 | 0.00 | 0.723241E+09 |
| Annual Sum or Average | 0.305538E+10 | 0.131783E+10 | 0.173755E+10 | 0.289203E+10 | 0.405370E+10 |
| Minimum of Months | 3265476.43 | 350119.80 | 2915356.63 | 0.00 | 57381636.52 |
| Maximum of Months | 0.538932E+09 | 0.262380E+09 | 0.308902E+09 | 0.590650E+09 | 0.723241E+09 |
Report: WindowEnergyReportMonthly
For: TWINDOW1 N NWA
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 13622807.86 | 0.00 | 13622807.86 | 0.00 | 0.105162E+10 |
| February | 54391655.15 | 0.00 | 54391655.15 | 0.00 | 0.849691E+09 |
| March | 0.161541E+09 | 53990.51 | 0.161487E+09 | 12778631.11 | 0.693123E+09 |
| April | 0.284403E+09 | 7945724.46 | 0.276457E+09 | 0.117422E+09 | 0.346499E+09 |
| May | 0.450494E+09 | 72760735.29 | 0.377733E+09 | 0.357751E+09 | 0.147804E+09 |
| June | 0.562063E+09 | 0.123352E+09 | 0.438711E+09 | 0.547578E+09 | 66599435.58 |
| July | 0.490169E+09 | 80654755.81 | 0.409514E+09 | 0.491037E+09 | 83405110.47 |
| August | 0.314910E+09 | 17029021.46 | 0.297881E+09 | 0.260898E+09 | 0.139238E+09 |
| September | 0.169525E+09 | 489125.69 | 0.169036E+09 | 71919721.94 | 0.275986E+09 |
| October | 84775064.66 | 0.00 | 84775064.66 | 6491503.24 | 0.585036E+09 |
| November | 25460057.00 | 0.00 | 25460057.00 | 0.00 | 0.990316E+09 |
| December | 4132448.42 | 0.00 | 4132448.42 | 0.00 | 0.110381E+10 |
| Annual Sum or Average | 0.261549E+10 | 0.302286E+09 | 0.231320E+10 | 0.186588E+10 | 0.633313E+10 |
| Minimum of Months | 4132448.42 | 0.00 | 4132448.42 | 0.00 | 66599435.58 |
| Maximum of Months | 0.562063E+09 | 0.123352E+09 | 0.438711E+09 | 0.547578E+09 | 0.110381E+10 |
Report: WindowEnergyReportMonthly
For: TWINDOW1 S SEA
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.168362E+09 | 0.112209E+09 | 56153171.53 | 94994731.40 | 0.941725E+09 |
| February | 0.508763E+09 | 0.353800E+09 | 0.154963E+09 | 0.420767E+09 | 0.679082E+09 |
| March | 0.954830E+09 | 0.643929E+09 | 0.310901E+09 | 0.921768E+09 | 0.572038E+09 |
| April | 0.114633E+10 | 0.715481E+09 | 0.430854E+09 | 0.124054E+10 | 0.349126E+09 |
| May | 0.972042E+09 | 0.503946E+09 | 0.468096E+09 | 0.108000E+10 | 0.187168E+09 |
| June | 0.860130E+09 | 0.353576E+09 | 0.506554E+09 | 0.980216E+09 | 95857393.20 |
| July | 0.856544E+09 | 0.374127E+09 | 0.482417E+09 | 0.100211E+10 | 0.104416E+09 |
| August | 0.886282E+09 | 0.489006E+09 | 0.397275E+09 | 0.102202E+10 | 0.156744E+09 |
| September | 0.682766E+09 | 0.407384E+09 | 0.275382E+09 | 0.718746E+09 | 0.266558E+09 |
| October | 0.518517E+09 | 0.328661E+09 | 0.189855E+09 | 0.466849E+09 | 0.486810E+09 |
| November | 0.270924E+09 | 0.190106E+09 | 80818039.55 | 0.172824E+09 | 0.843339E+09 |
| December | 49301472.86 | 34692762.25 | 14608710.60 | 8372376.52 | 0.104977E+10 |
| Annual Sum or Average | 0.787479E+10 | 0.450692E+10 | 0.336788E+10 | 0.812920E+10 | 0.573263E+10 |
| Minimum of Months | 49301472.86 | 34692762.25 | 14608710.60 | 8372376.52 | 95857393.20 |
| Maximum of Months | 0.114633E+10 | 0.715481E+09 | 0.506554E+09 | 0.124054E+10 | 0.104977E+10 |
Report: WindowEnergyReportMonthly
For: TWINDOW1 E SEA
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 26537662.32 | 10088926.42 | 16448735.90 | 3452962.05 | 0.670239E+09 |
| February | 0.120964E+09 | 58372632.04 | 62591246.70 | 61173857.79 | 0.506306E+09 |
| March | 0.382521E+09 | 0.193221E+09 | 0.189300E+09 | 0.319294E+09 | 0.409776E+09 |
| April | 0.496126E+09 | 0.251415E+09 | 0.244711E+09 | 0.451164E+09 | 0.214864E+09 |
| May | 0.746373E+09 | 0.420655E+09 | 0.325718E+09 | 0.810621E+09 | 0.107451E+09 |
| June | 0.662499E+09 | 0.309131E+09 | 0.353368E+09 | 0.742859E+09 | 50714831.46 |
| July | 0.651612E+09 | 0.316771E+09 | 0.334841E+09 | 0.749977E+09 | 59415615.75 |
| August | 0.519730E+09 | 0.253138E+09 | 0.266592E+09 | 0.570077E+09 | 94622306.35 |
| September | 0.316758E+09 | 0.143332E+09 | 0.173426E+09 | 0.296120E+09 | 0.175634E+09 |
| October | 0.173562E+09 | 69874289.31 | 0.103688E+09 | 0.123875E+09 | 0.351914E+09 |
| November | 34987210.79 | 12420027.48 | 22567183.31 | 2564009.93 | 0.628673E+09 |
| December | 5140450.97 | 1193013.76 | 3947437.20 | 0.00 | 0.721613E+09 |
| Annual Sum or Average | 0.413681E+10 | 0.203961E+10 | 0.209720E+10 | 0.413118E+10 | 0.399122E+10 |
| Minimum of Months | 5140450.97 | 1193013.76 | 3947437.20 | 0.00 | 50714831.46 |
| Maximum of Months | 0.746373E+09 | 0.420655E+09 | 0.353368E+09 | 0.810621E+09 | 0.721613E+09 |
Report: WindowEnergyReportMonthly
For: TWINDOW1 E NEA
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 26537662.32 | 10088926.42 | 16448735.90 | 3557591.49 | 0.668692E+09 |
| February | 0.120964E+09 | 58372632.04 | 62591246.70 | 62106948.66 | 0.501921E+09 |
| March | 0.382521E+09 | 0.193221E+09 | 0.189300E+09 | 0.323223E+09 | 0.401709E+09 |
| April | 0.496126E+09 | 0.251415E+09 | 0.244711E+09 | 0.464409E+09 | 0.206471E+09 |
| May | 0.746373E+09 | 0.420655E+09 | 0.325718E+09 | 0.817096E+09 | 0.104654E+09 |
| June | 0.662499E+09 | 0.309131E+09 | 0.353368E+09 | 0.745278E+09 | 50343216.94 |
| July | 0.651612E+09 | 0.316771E+09 | 0.334841E+09 | 0.753263E+09 | 58773357.57 |
| August | 0.519730E+09 | 0.253138E+09 | 0.266592E+09 | 0.577032E+09 | 91545843.19 |
| September | 0.316758E+09 | 0.143332E+09 | 0.173426E+09 | 0.303990E+09 | 0.167495E+09 |
| October | 0.173562E+09 | 69874289.31 | 0.103688E+09 | 0.126058E+09 | 0.346673E+09 |
| November | 34987210.79 | 12420027.48 | 22567183.31 | 2659913.45 | 0.626097E+09 |
| December | 5140450.97 | 1193013.76 | 3947437.20 | 0.00 | 0.721112E+09 |
| Annual Sum or Average | 0.413681E+10 | 0.203961E+10 | 0.209720E+10 | 0.417867E+10 | 0.394549E+10 |
| Minimum of Months | 5140450.97 | 1193013.76 | 3947437.20 | 0.00 | 50343216.94 |
| Maximum of Months | 0.746373E+09 | 0.420655E+09 | 0.353368E+09 | 0.817096E+09 | 0.721112E+09 |
Report: WindowEnergyReportMonthly
For: TWINDOW1 N NEA
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 13622807.86 | 0.00 | 13622807.86 | 0.00 | 0.105183E+10 |
| February | 54391655.15 | 0.00 | 54391655.15 | 0.00 | 0.850522E+09 |
| March | 0.161541E+09 | 53990.51 | 0.161487E+09 | 12129094.82 | 0.695286E+09 |
| April | 0.284403E+09 | 7945724.46 | 0.276457E+09 | 0.115116E+09 | 0.343841E+09 |
| May | 0.450494E+09 | 72760735.29 | 0.377733E+09 | 0.344763E+09 | 0.146977E+09 |
| June | 0.562063E+09 | 0.123352E+09 | 0.438711E+09 | 0.543763E+09 | 65882080.40 |
| July | 0.490169E+09 | 80654755.81 | 0.409514E+09 | 0.486454E+09 | 82785225.27 |
| August | 0.314910E+09 | 17029021.46 | 0.297881E+09 | 0.254700E+09 | 0.138683E+09 |
| September | 0.169525E+09 | 489125.69 | 0.169036E+09 | 68826364.49 | 0.275806E+09 |
| October | 84775064.66 | 0.00 | 84775064.66 | 6189545.21 | 0.586284E+09 |
| November | 25460057.00 | 0.00 | 25460057.00 | 0.00 | 0.990284E+09 |
| December | 4132448.42 | 0.00 | 4132448.42 | 0.00 | 0.110384E+10 |
| Annual Sum or Average | 0.261549E+10 | 0.302286E+09 | 0.231320E+10 | 0.183194E+10 | 0.633202E+10 |
| Minimum of Months | 4132448.42 | 0.00 | 4132448.42 | 0.00 | 65882080.40 |
| Maximum of Months | 0.562063E+09 | 0.123352E+09 | 0.438711E+09 | 0.543763E+09 | 0.110384E+10 |
Report: WindowEnergyReportMonthly
For: TWINDOW1 N N1A
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 13622807.86 | 0.00 | 13622807.86 | 0.00 | 0.106535E+10 |
| February | 54391655.15 | 0.00 | 54391655.15 | 0.00 | 0.860955E+09 |
| March | 0.161541E+09 | 53990.51 | 0.161487E+09 | 12271507.27 | 0.702082E+09 |
| April | 0.284403E+09 | 7945724.46 | 0.276457E+09 | 0.119152E+09 | 0.347577E+09 |
| May | 0.450494E+09 | 72760735.29 | 0.377733E+09 | 0.357232E+09 | 0.149165E+09 |
| June | 0.562063E+09 | 0.123352E+09 | 0.438711E+09 | 0.549671E+09 | 67270213.55 |
| July | 0.490169E+09 | 80654755.81 | 0.409514E+09 | 0.492529E+09 | 84310069.57 |
| August | 0.314910E+09 | 17029021.46 | 0.297881E+09 | 0.259913E+09 | 0.141352E+09 |
| September | 0.169525E+09 | 489125.69 | 0.169036E+09 | 71320109.03 | 0.279483E+09 |
| October | 84775064.66 | 0.00 | 84775064.66 | 6224794.07 | 0.594120E+09 |
| November | 25460057.00 | 0.00 | 25460057.00 | 0.00 | 0.100299E+10 |
| December | 4132448.42 | 0.00 | 4132448.42 | 0.00 | 0.111800E+10 |
| Annual Sum or Average | 0.261549E+10 | 0.302286E+09 | 0.231320E+10 | 0.186831E+10 | 0.641267E+10 |
| Minimum of Months | 4132448.42 | 0.00 | 4132448.42 | 0.00 | 67270213.55 |
| Maximum of Months | 0.562063E+09 | 0.123352E+09 | 0.438711E+09 | 0.549671E+09 | 0.111800E+10 |
Report: WindowEnergyReportMonthly
For: TWINDOW1 N N2A
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 13622807.86 | 0.00 | 13622807.86 | 0.00 | 0.106536E+10 |
| February | 54391655.15 | 0.00 | 54391655.15 | 0.00 | 0.860989E+09 |
| March | 0.161541E+09 | 53990.51 | 0.161487E+09 | 12236762.57 | 0.702187E+09 |
| April | 0.284403E+09 | 7945724.46 | 0.276457E+09 | 0.118923E+09 | 0.347384E+09 |
| May | 0.450494E+09 | 72760735.29 | 0.377733E+09 | 0.355891E+09 | 0.149321E+09 |
| June | 0.562063E+09 | 0.123352E+09 | 0.438711E+09 | 0.549463E+09 | 67236185.02 |
| July | 0.490169E+09 | 80654755.81 | 0.409514E+09 | 0.492294E+09 | 84280361.95 |
| August | 0.314910E+09 | 17029021.46 | 0.297881E+09 | 0.259399E+09 | 0.141386E+09 |
| September | 0.169525E+09 | 489125.69 | 0.169036E+09 | 71050704.95 | 0.279544E+09 |
| October | 84775064.66 | 0.00 | 84775064.66 | 6204179.71 | 0.594187E+09 |
| November | 25460057.00 | 0.00 | 25460057.00 | 0.00 | 0.100299E+10 |
| December | 4132448.42 | 0.00 | 4132448.42 | 0.00 | 0.111801E+10 |
| Annual Sum or Average | 0.261549E+10 | 0.302286E+09 | 0.231320E+10 | 0.186546E+10 | 0.641287E+10 |
| Minimum of Months | 4132448.42 | 0.00 | 4132448.42 | 0.00 | 67236185.02 |
| Maximum of Months | 0.562063E+09 | 0.123352E+09 | 0.438711E+09 | 0.549463E+09 | 0.111801E+10 |
Report: WindowEnergyReportMonthly
For: TWINDOW1 S S1A
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.168362E+09 | 0.112209E+09 | 56153171.53 | 94047295.02 | 0.954471E+09 |
| February | 0.508763E+09 | 0.353800E+09 | 0.154963E+09 | 0.418869E+09 | 0.688307E+09 |
| March | 0.954830E+09 | 0.643929E+09 | 0.310901E+09 | 0.921391E+09 | 0.579762E+09 |
| April | 0.114633E+10 | 0.715481E+09 | 0.430854E+09 | 0.124302E+10 | 0.355510E+09 |
| May | 0.972042E+09 | 0.503946E+09 | 0.468096E+09 | 0.108817E+10 | 0.190866E+09 |
| June | 0.860130E+09 | 0.353576E+09 | 0.506554E+09 | 0.986166E+09 | 97290860.69 |
| July | 0.856544E+09 | 0.374127E+09 | 0.482417E+09 | 0.100807E+10 | 0.106127E+09 |
| August | 0.886282E+09 | 0.489006E+09 | 0.397275E+09 | 0.102597E+10 | 0.160231E+09 |
| September | 0.682766E+09 | 0.407384E+09 | 0.275382E+09 | 0.719978E+09 | 0.272805E+09 |
| October | 0.518517E+09 | 0.328661E+09 | 0.189855E+09 | 0.465532E+09 | 0.494693E+09 |
| November | 0.270924E+09 | 0.190106E+09 | 80818039.55 | 0.171117E+09 | 0.854716E+09 |
| December | 49301472.86 | 34692762.25 | 14608710.60 | 8174668.19 | 0.106374E+10 |
| Annual Sum or Average | 0.787479E+10 | 0.450692E+10 | 0.336788E+10 | 0.815052E+10 | 0.581852E+10 |
| Minimum of Months | 49301472.86 | 34692762.25 | 14608710.60 | 8174668.19 | 97290860.69 |
| Maximum of Months | 0.114633E+10 | 0.715481E+09 | 0.506554E+09 | 0.124302E+10 | 0.106374E+10 |
Report: WindowEnergyReportMonthly
For: TWINDOW1 S S2A
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.168362E+09 | 0.112209E+09 | 56153171.53 | 94042405.65 | 0.954476E+09 |
| February | 0.508763E+09 | 0.353800E+09 | 0.154963E+09 | 0.418829E+09 | 0.688318E+09 |
| March | 0.954830E+09 | 0.643929E+09 | 0.310901E+09 | 0.921159E+09 | 0.579803E+09 |
| April | 0.114633E+10 | 0.715481E+09 | 0.430854E+09 | 0.124273E+10 | 0.355274E+09 |
| May | 0.972042E+09 | 0.503946E+09 | 0.468096E+09 | 0.108751E+10 | 0.190833E+09 |
| June | 0.860130E+09 | 0.353576E+09 | 0.506554E+09 | 0.985886E+09 | 97246750.34 |
| July | 0.856544E+09 | 0.374127E+09 | 0.482417E+09 | 0.100782E+10 | 0.106093E+09 |
| August | 0.886282E+09 | 0.489006E+09 | 0.397275E+09 | 0.102562E+10 | 0.160244E+09 |
| September | 0.682766E+09 | 0.407384E+09 | 0.275382E+09 | 0.719676E+09 | 0.272864E+09 |
| October | 0.518517E+09 | 0.328661E+09 | 0.189855E+09 | 0.465417E+09 | 0.494748E+09 |
| November | 0.270924E+09 | 0.190106E+09 | 80818039.55 | 0.171112E+09 | 0.854710E+09 |
| December | 49301472.86 | 34692762.25 | 14608710.60 | 8174510.36 | 0.106375E+10 |
| Annual Sum or Average | 0.787479E+10 | 0.450692E+10 | 0.336788E+10 | 0.814798E+10 | 0.581836E+10 |
| Minimum of Months | 49301472.86 | 34692762.25 | 14608710.60 | 8174510.36 | 97246750.34 |
| Maximum of Months | 0.114633E+10 | 0.715481E+09 | 0.506554E+09 | 0.124273E+10 | 0.106375E+10 |
Report: WindowEnergyReportMonthly
For: TWINDOW14
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 6367820.09 | 2420878.96 | 3946941.13 | 849223.16 | 0.160380E+09 |
| February | 29025775.07 | 14006750.66 | 15019024.42 | 14837220.77 | 0.121397E+09 |
| March | 91787564.27 | 46364175.95 | 45423388.32 | 76849954.45 | 99113911.46 |
| April | 0.119048E+09 | 60328019.93 | 58719500.19 | 0.108938E+09 | 53572021.43 |
| May | 0.179095E+09 | 0.100938E+09 | 78157425.01 | 0.193287E+09 | 28415359.31 |
| June | 0.158969E+09 | 74177353.37 | 84792050.43 | 0.174997E+09 | 14241343.75 |
| July | 0.156357E+09 | 76010480.34 | 80346501.78 | 0.176794E+09 | 16569677.09 |
| August | 0.124711E+09 | 60741565.17 | 63969741.86 | 0.135246E+09 | 25409076.26 |
| September | 76007325.25 | 34393055.66 | 41614269.59 | 70886824.73 | 44507406.40 |
| October | 41646905.03 | 16766620.14 | 24880284.89 | 29521947.35 | 86237834.85 |
| November | 8395323.64 | 2980236.15 | 5415087.49 | 635924.38 | 0.149950E+09 |
| December | 1233472.13 | 286268.51 | 947203.62 | 0.00 | 0.172557E+09 |
| Annual Sum or Average | 0.992645E+09 | 0.489413E+09 | 0.503231E+09 | 0.982843E+09 | 0.972350E+09 |
| Minimum of Months | 1233472.13 | 286268.51 | 947203.62 | 0.00 | 14241343.75 |
| Maximum of Months | 0.179095E+09 | 0.100938E+09 | 84792050.43 | 0.193287E+09 | 0.172557E+09 |
Report: WindowEnergyReportMonthly
For: ENTRANCE DOOR
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 18964952.95 | 7209980.01 | 11754972.94 | 3349913.24 | 0.417490E+09 |
| February | 86445981.62 | 41715589.22 | 44730392.40 | 49598597.42 | 0.313789E+09 |
| March | 0.273366E+09 | 0.138084E+09 | 0.135282E+09 | 0.243123E+09 | 0.255269E+09 |
| April | 0.354553E+09 | 0.179672E+09 | 0.174881E+09 | 0.344735E+09 | 0.139356E+09 |
| May | 0.533390E+09 | 0.300618E+09 | 0.232772E+09 | 0.594091E+09 | 74984262.57 |
| June | 0.473450E+09 | 0.220919E+09 | 0.252532E+09 | 0.532391E+09 | 39647124.78 |
| July | 0.465670E+09 | 0.226378E+09 | 0.239292E+09 | 0.533223E+09 | 48242555.58 |
| August | 0.371421E+09 | 0.180903E+09 | 0.190518E+09 | 0.407333E+09 | 75446917.32 |
| September | 0.226369E+09 | 0.102431E+09 | 0.123938E+09 | 0.216116E+09 | 0.126415E+09 |
| October | 0.124035E+09 | 49935167.36 | 74099680.19 | 93188404.39 | 0.229050E+09 |
| November | 25003363.09 | 8875884.92 | 16127478.17 | 2631827.30 | 0.394596E+09 |
| December | 3673586.98 | 852578.86 | 2821008.12 | 0.00 | 0.451695E+09 |
| Annual Sum or Average | 0.295634E+10 | 0.145759E+10 | 0.149875E+10 | 0.301978E+10 | 0.256598E+10 |
| Minimum of Months | 3673586.98 | 852578.86 | 2821008.12 | 0.00 | 39647124.78 |
| Maximum of Months | 0.533390E+09 | 0.300618E+09 | 0.252532E+09 | 0.594091E+09 | 0.451695E+09 |
Report: WindowEnergyReportMonthly
For: MWINDOW14
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 6367820.09 | 2420878.96 | 3946941.13 | 749890.07 | 0.169114E+09 |
| February | 29025775.07 | 14006750.66 | 15019024.42 | 14072401.66 | 0.128296E+09 |
| March | 91787564.27 | 46364175.95 | 45423388.32 | 75129135.18 | 0.104543E+09 |
| April | 0.119048E+09 | 60328019.93 | 58719500.19 | 0.106709E+09 | 56419066.78 |
| May | 0.179095E+09 | 0.100938E+09 | 78157425.01 | 0.190166E+09 | 30372700.47 |
| June | 0.158969E+09 | 74177353.37 | 84792050.43 | 0.174272E+09 | 14757381.96 |
| July | 0.156357E+09 | 76010480.34 | 80346501.78 | 0.176261E+09 | 17131406.19 |
| August | 0.124711E+09 | 60741565.17 | 63969741.86 | 0.133298E+09 | 27021442.93 |
| September | 76007325.25 | 34393055.66 | 41614269.59 | 68137402.25 | 48817579.14 |
| October | 41646905.03 | 16766620.14 | 24880284.89 | 28502119.70 | 91712786.95 |
| November | 8395323.64 | 2980236.15 | 5415087.49 | 533296.39 | 0.158621E+09 |
| December | 1233472.13 | 286268.51 | 947203.62 | 0.00 | 0.181602E+09 |
| Annual Sum or Average | 0.992645E+09 | 0.489413E+09 | 0.503231E+09 | 0.967830E+09 | 0.102841E+10 |
| Minimum of Months | 1233472.13 | 286268.51 | 947203.62 | 0.00 | 14757381.96 |
| Maximum of Months | 0.179095E+09 | 0.100938E+09 | 84792050.43 | 0.190166E+09 | 0.181602E+09 |
Report: WindowZoneSummaryMonthly
For: G SW APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 22.51 | 592.37 | 67.49 | 42.70 | 24.79 | 0.00 | 0.00 |
| February | 155.03 | 468.63 | 237.84 | 155.89 | 81.95 | 0.00 | 0.00 |
| March | 381.62 | 349.43 | 439.26 | 276.26 | 163.00 | 0.00 | 0.00 |
| April | 670.92 | 208.42 | 637.52 | 377.26 | 260.26 | 0.00 | 0.00 |
| May | 609.48 | 104.49 | 552.55 | 274.54 | 278.01 | 0.00 | 0.00 |
| June | 615.01 | 57.12 | 539.76 | 225.16 | 314.60 | 0.00 | 0.00 |
| July | 572.83 | 63.33 | 493.56 | 205.37 | 288.19 | 0.00 | 0.00 |
| August | 532.88 | 99.24 | 474.15 | 243.44 | 230.70 | 0.00 | 0.00 |
| September | 345.70 | 176.60 | 349.73 | 193.20 | 156.53 | 0.00 | 0.00 |
| October | 174.10 | 306.54 | 227.40 | 132.83 | 94.56 | 0.00 | 0.00 |
| November | 50.66 | 553.80 | 118.07 | 78.25 | 39.82 | 0.00 | 0.00 |
| December | 0.72 | 659.95 | 19.63 | 13.08 | 6.54 | 0.00 | 0.00 |
| Annual Sum or Average | 345.01 | 302.56 | 346.59 | 184.70 | 161.89 | 0.00 | 0.00 |
| Minimum of Months | 0.72 | 57.12 | 19.63 | 13.08 | 6.54 | 0.00 | 0.00 |
| Maximum of Months | 670.92 | 659.95 | 637.52 | 377.26 | 314.60 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: G NW APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 0.00 | 645.49 | 9.71 | 0.81 | 8.91 | 0.00 | 0.00 |
| February | 0.25 | 556.78 | 50.02 | 9.65 | 40.37 | 0.00 | 0.00 |
| March | 40.69 | 392.98 | 143.08 | 35.86 | 107.22 | 0.00 | 0.00 |
| April | 238.96 | 205.38 | 304.98 | 104.29 | 200.69 | 0.00 | 0.00 |
| May | 343.60 | 82.66 | 357.82 | 113.55 | 244.27 | 0.00 | 0.00 |
| June | 447.71 | 41.59 | 424.77 | 136.34 | 288.43 | 0.00 | 0.00 |
| July | 379.59 | 52.22 | 356.77 | 95.80 | 260.97 | 0.00 | 0.00 |
| August | 246.35 | 88.08 | 260.82 | 67.23 | 193.59 | 0.00 | 0.00 |
| September | 98.41 | 171.67 | 151.72 | 36.22 | 115.50 | 0.00 | 0.00 |
| October | 11.00 | 350.30 | 65.46 | 10.12 | 55.33 | 0.00 | 0.00 |
| November | 0.00 | 625.10 | 23.37 | 4.91 | 18.46 | 0.00 | 0.00 |
| December | 0.00 | 681.91 | 2.76 | 0.13 | 2.63 | 0.00 | 0.00 |
| Annual Sum or Average | 151.28 | 323.30 | 179.82 | 51.37 | 128.45 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 41.59 | 2.76 | 0.13 | 2.63 | 0.00 | 0.00 |
| Maximum of Months | 447.71 | 681.91 | 424.77 | 136.34 | 288.43 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: OFFICE
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 31.21 | 532.53 | 72.77 | 45.66 | 27.11 | 0.00 | 0.00 |
| February | 195.12 | 420.96 | 260.30 | 170.38 | 89.93 | 0.00 | 0.00 |
| March | 472.06 | 309.02 | 499.31 | 312.56 | 186.75 | 0.00 | 0.00 |
| April | 669.82 | 183.92 | 633.67 | 373.03 | 260.63 | 0.00 | 0.00 |
| May | 709.38 | 103.83 | 641.58 | 345.21 | 296.38 | 0.00 | 0.00 |
| June | 658.55 | 59.02 | 587.43 | 255.67 | 331.76 | 0.00 | 0.00 |
| July | 641.77 | 70.26 | 563.08 | 257.95 | 305.13 | 0.00 | 0.00 |
| August | 583.02 | 107.20 | 524.94 | 277.08 | 247.86 | 0.00 | 0.00 |
| September | 384.93 | 177.29 | 385.62 | 212.47 | 173.15 | 0.00 | 0.00 |
| October | 221.76 | 278.91 | 258.39 | 148.80 | 109.60 | 0.00 | 0.00 |
| November | 54.06 | 498.95 | 118.02 | 78.14 | 39.89 | 0.00 | 0.00 |
| December | 1.22 | 598.96 | 20.33 | 13.40 | 6.93 | 0.00 | 0.00 |
| Annual Sum or Average | 386.18 | 277.77 | 380.89 | 207.59 | 173.30 | 0.00 | 0.00 |
| Minimum of Months | 1.22 | 59.02 | 20.33 | 13.40 | 6.93 | 0.00 | 0.00 |
| Maximum of Months | 709.38 | 598.96 | 641.58 | 373.03 | 331.76 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: G NE APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 0.00 | 638.66 | 14.99 | 3.77 | 11.23 | 0.00 | 0.00 |
| February | 5.88 | 533.26 | 72.48 | 24.13 | 48.36 | 0.00 | 0.00 |
| March | 99.40 | 374.00 | 203.13 | 72.16 | 130.97 | 0.00 | 0.00 |
| April | 223.17 | 194.13 | 301.13 | 100.06 | 201.07 | 0.00 | 0.00 |
| May | 455.22 | 85.70 | 446.86 | 184.22 | 262.64 | 0.00 | 0.00 |
| June | 508.03 | 42.32 | 472.44 | 166.85 | 305.59 | 0.00 | 0.00 |
| July | 468.91 | 52.69 | 426.29 | 148.38 | 277.91 | 0.00 | 0.00 |
| August | 310.60 | 88.76 | 311.62 | 100.87 | 210.75 | 0.00 | 0.00 |
| September | 136.96 | 165.96 | 187.61 | 55.49 | 132.12 | 0.00 | 0.00 |
| October | 34.83 | 333.91 | 96.45 | 26.09 | 70.36 | 0.00 | 0.00 |
| November | 0.00 | 625.95 | 23.32 | 4.79 | 18.53 | 0.00 | 0.00 |
| December | 0.00 | 681.06 | 3.46 | 0.45 | 3.02 | 0.00 | 0.00 |
| Annual Sum or Average | 188.07 | 316.93 | 214.11 | 74.26 | 139.85 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 42.32 | 3.46 | 0.45 | 3.02 | 0.00 | 0.00 |
| Maximum of Months | 508.03 | 681.06 | 472.44 | 184.22 | 305.59 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: G N1 APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 0.00 | 396.39 | 5.09 | 0.00 | 5.09 | 0.00 | 0.00 |
| February | 0.00 | 352.91 | 22.48 | 0.00 | 22.48 | 0.00 | 0.00 |
| March | 5.08 | 257.89 | 60.31 | 0.02 | 60.29 | 0.00 | 0.00 |
| April | 50.32 | 129.93 | 109.72 | 3.07 | 106.66 | 0.00 | 0.00 |
| May | 144.83 | 51.02 | 168.20 | 27.17 | 141.03 | 0.00 | 0.00 |
| June | 218.28 | 25.06 | 216.85 | 47.59 | 169.26 | 0.00 | 0.00 |
| July | 186.81 | 31.49 | 183.01 | 30.11 | 152.90 | 0.00 | 0.00 |
| August | 96.51 | 54.67 | 117.57 | 6.36 | 111.22 | 0.00 | 0.00 |
| September | 27.19 | 109.24 | 65.40 | 0.19 | 65.21 | 0.00 | 0.00 |
| October | 2.39 | 221.72 | 31.65 | 0.00 | 31.65 | 0.00 | 0.00 |
| November | 0.00 | 388.52 | 9.82 | 0.00 | 9.82 | 0.00 | 0.00 |
| December | 0.00 | 416.94 | 1.54 | 0.00 | 1.54 | 0.00 | 0.00 |
| Annual Sum or Average | 61.31 | 202.19 | 82.94 | 9.59 | 73.35 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 25.06 | 1.54 | 0.00 | 1.54 | 0.00 | 0.00 |
| Maximum of Months | 218.28 | 416.94 | 216.85 | 47.59 | 169.26 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: G N2 APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 0.00 | 396.40 | 5.09 | 0.00 | 5.09 | 0.00 | 0.00 |
| February | 0.00 | 352.92 | 22.48 | 0.00 | 22.48 | 0.00 | 0.00 |
| March | 5.07 | 257.93 | 60.31 | 0.02 | 60.29 | 0.00 | 0.00 |
| April | 50.31 | 129.91 | 109.72 | 3.07 | 106.66 | 0.00 | 0.00 |
| May | 144.41 | 51.19 | 168.20 | 27.17 | 141.03 | 0.00 | 0.00 |
| June | 218.09 | 25.11 | 216.85 | 47.59 | 169.26 | 0.00 | 0.00 |
| July | 186.73 | 31.51 | 183.01 | 30.11 | 152.90 | 0.00 | 0.00 |
| August | 96.40 | 54.73 | 117.57 | 6.36 | 111.22 | 0.00 | 0.00 |
| September | 27.09 | 109.39 | 65.40 | 0.19 | 65.21 | 0.00 | 0.00 |
| October | 2.38 | 221.76 | 31.65 | 0.00 | 31.65 | 0.00 | 0.00 |
| November | 0.00 | 388.52 | 9.82 | 0.00 | 9.82 | 0.00 | 0.00 |
| December | 0.00 | 416.94 | 1.54 | 0.00 | 1.54 | 0.00 | 0.00 |
| Annual Sum or Average | 61.23 | 202.23 | 82.94 | 9.59 | 73.35 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 25.11 | 1.54 | 0.00 | 1.54 | 0.00 | 0.00 |
| Maximum of Months | 218.09 | 416.94 | 216.85 | 47.59 | 169.26 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: G S1 APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 35.39 | 355.61 | 62.86 | 41.89 | 20.97 | 0.00 | 0.00 |
| February | 174.76 | 283.20 | 210.30 | 146.25 | 64.06 | 0.00 | 0.00 |
| March | 348.53 | 214.25 | 356.49 | 240.42 | 116.08 | 0.00 | 0.00 |
| April | 487.90 | 133.52 | 442.26 | 276.03 | 166.22 | 0.00 | 0.00 |
| May | 413.14 | 69.41 | 362.92 | 188.15 | 174.77 | 0.00 | 0.00 |
| June | 385.24 | 37.48 | 331.84 | 136.41 | 195.43 | 0.00 | 0.00 |
| July | 379.80 | 40.36 | 319.80 | 139.68 | 180.11 | 0.00 | 0.00 |
| August | 384.33 | 62.74 | 330.90 | 182.57 | 148.33 | 0.00 | 0.00 |
| September | 277.06 | 110.77 | 263.41 | 157.17 | 106.24 | 0.00 | 0.00 |
| October | 175.00 | 185.60 | 193.59 | 122.71 | 70.88 | 0.00 | 0.00 |
| November | 66.10 | 331.78 | 104.52 | 73.34 | 31.18 | 0.00 | 0.00 |
| December | 3.06 | 397.08 | 18.41 | 12.95 | 5.45 | 0.00 | 0.00 |
| Annual Sum or Average | 261.09 | 184.69 | 249.71 | 142.91 | 106.79 | 0.00 | 0.00 |
| Minimum of Months | 3.06 | 37.48 | 18.41 | 12.95 | 5.45 | 0.00 | 0.00 |
| Maximum of Months | 487.90 | 397.08 | 442.26 | 276.03 | 195.43 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: G S2 APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 35.47 | 354.49 | 62.86 | 41.89 | 20.97 | 0.00 | 0.00 |
| February | 175.00 | 282.28 | 210.30 | 146.25 | 64.06 | 0.00 | 0.00 |
| March | 348.89 | 213.44 | 356.49 | 240.42 | 116.08 | 0.00 | 0.00 |
| April | 488.28 | 132.90 | 442.26 | 276.03 | 166.22 | 0.00 | 0.00 |
| May | 412.56 | 69.90 | 362.92 | 188.15 | 174.77 | 0.00 | 0.00 |
| June | 384.77 | 37.79 | 331.84 | 136.41 | 195.43 | 0.00 | 0.00 |
| July | 379.31 | 40.70 | 319.80 | 139.68 | 180.11 | 0.00 | 0.00 |
| August | 383.94 | 63.13 | 330.90 | 182.57 | 148.33 | 0.00 | 0.00 |
| September | 276.73 | 111.23 | 263.41 | 157.17 | 106.24 | 0.00 | 0.00 |
| October | 175.21 | 184.91 | 193.59 | 122.71 | 70.88 | 0.00 | 0.00 |
| November | 66.25 | 330.71 | 104.52 | 73.34 | 31.18 | 0.00 | 0.00 |
| December | 3.07 | 395.95 | 18.41 | 12.95 | 5.45 | 0.00 | 0.00 |
| Annual Sum or Average | 261.02 | 184.33 | 249.71 | 142.91 | 106.79 | 0.00 | 0.00 |
| Minimum of Months | 3.07 | 37.79 | 18.41 | 12.95 | 5.45 | 0.00 | 0.00 |
| Maximum of Months | 488.28 | 395.95 | 442.26 | 276.03 | 195.43 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: M SW APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 21.63 | 608.71 | 67.49 | 42.70 | 24.79 | 0.00 | 0.00 |
| February | 150.61 | 484.50 | 237.84 | 155.89 | 81.95 | 0.00 | 0.00 |
| March | 372.94 | 363.81 | 439.26 | 276.26 | 163.00 | 0.00 | 0.00 |
| April | 653.57 | 223.75 | 637.52 | 377.26 | 260.26 | 0.00 | 0.00 |
| May | 590.24 | 119.60 | 552.55 | 274.54 | 278.01 | 0.00 | 0.00 |
| June | 606.07 | 61.46 | 539.76 | 225.16 | 314.60 | 0.00 | 0.00 |
| July | 567.61 | 65.73 | 493.56 | 205.37 | 288.19 | 0.00 | 0.00 |
| August | 528.98 | 101.64 | 474.15 | 243.44 | 230.70 | 0.00 | 0.00 |
| September | 339.96 | 184.64 | 349.73 | 193.20 | 156.53 | 0.00 | 0.00 |
| October | 170.76 | 314.92 | 227.40 | 132.83 | 94.56 | 0.00 | 0.00 |
| November | 49.34 | 564.74 | 118.07 | 78.25 | 39.82 | 0.00 | 0.00 |
| December | 0.65 | 675.40 | 19.63 | 13.08 | 6.54 | 0.00 | 0.00 |
| Annual Sum or Average | 338.42 | 313.28 | 346.59 | 184.70 | 161.89 | 0.00 | 0.00 |
| Minimum of Months | 0.65 | 61.46 | 19.63 | 13.08 | 6.54 | 0.00 | 0.00 |
| Maximum of Months | 653.57 | 675.40 | 637.52 | 377.26 | 314.60 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: M NW APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 0.00 | 662.98 | 9.71 | 0.81 | 8.91 | 0.00 | 0.00 |
| February | 0.17 | 576.75 | 50.02 | 9.65 | 40.37 | 0.00 | 0.00 |
| March | 37.37 | 410.90 | 143.08 | 35.86 | 107.22 | 0.00 | 0.00 |
| April | 226.46 | 219.04 | 304.98 | 104.29 | 200.69 | 0.00 | 0.00 |
| May | 313.49 | 97.48 | 357.82 | 113.55 | 244.27 | 0.00 | 0.00 |
| June | 434.38 | 45.66 | 424.77 | 136.34 | 288.43 | 0.00 | 0.00 |
| July | 373.04 | 54.81 | 356.77 | 95.80 | 260.97 | 0.00 | 0.00 |
| August | 240.67 | 91.99 | 260.82 | 67.23 | 193.59 | 0.00 | 0.00 |
| September | 93.05 | 181.67 | 151.72 | 36.22 | 115.50 | 0.00 | 0.00 |
| October | 10.19 | 360.65 | 65.46 | 10.12 | 55.33 | 0.00 | 0.00 |
| November | 0.00 | 637.67 | 23.37 | 4.91 | 18.46 | 0.00 | 0.00 |
| December | 0.00 | 697.76 | 2.76 | 0.13 | 2.63 | 0.00 | 0.00 |
| Annual Sum or Average | 144.76 | 335.19 | 179.82 | 51.37 | 128.45 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 45.66 | 2.76 | 0.13 | 2.63 | 0.00 | 0.00 |
| Maximum of Months | 434.38 | 697.76 | 424.77 | 136.34 | 288.43 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: M SE APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 27.26 | 607.62 | 72.77 | 45.66 | 27.11 | 0.00 | 0.00 |
| February | 180.17 | 485.21 | 260.30 | 170.38 | 89.93 | 0.00 | 0.00 |
| March | 446.94 | 360.89 | 499.31 | 312.56 | 186.75 | 0.00 | 0.00 |
| April | 640.88 | 216.17 | 633.67 | 373.03 | 260.63 | 0.00 | 0.00 |
| May | 693.90 | 110.78 | 641.58 | 345.21 | 296.38 | 0.00 | 0.00 |
| June | 660.56 | 54.05 | 587.43 | 255.67 | 331.76 | 0.00 | 0.00 |
| July | 652.08 | 60.41 | 563.08 | 257.95 | 305.13 | 0.00 | 0.00 |
| August | 588.11 | 95.83 | 524.94 | 277.08 | 247.86 | 0.00 | 0.00 |
| September | 379.64 | 179.74 | 385.62 | 212.47 | 173.15 | 0.00 | 0.00 |
| October | 210.44 | 315.03 | 258.39 | 148.80 | 109.60 | 0.00 | 0.00 |
| November | 48.21 | 564.59 | 118.02 | 78.14 | 39.89 | 0.00 | 0.00 |
| December | 0.95 | 674.89 | 20.33 | 13.40 | 6.93 | 0.00 | 0.00 |
| Annual Sum or Average | 378.45 | 309.62 | 380.89 | 207.59 | 173.30 | 0.00 | 0.00 |
| Minimum of Months | 0.95 | 54.05 | 20.33 | 13.40 | 6.93 | 0.00 | 0.00 |
| Maximum of Months | 693.90 | 674.89 | 641.58 | 373.03 | 331.76 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: M NE APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 0.00 | 656.24 | 14.99 | 3.77 | 11.23 | 0.00 | 0.00 |
| February | 5.07 | 552.71 | 72.48 | 24.13 | 48.36 | 0.00 | 0.00 |
| March | 94.15 | 390.40 | 203.13 | 72.16 | 130.97 | 0.00 | 0.00 |
| April | 209.89 | 206.98 | 301.13 | 100.06 | 201.07 | 0.00 | 0.00 |
| May | 427.35 | 100.45 | 446.86 | 184.22 | 262.64 | 0.00 | 0.00 |
| June | 496.59 | 45.99 | 472.44 | 166.85 | 305.59 | 0.00 | 0.00 |
| July | 462.94 | 54.98 | 426.29 | 148.38 | 277.91 | 0.00 | 0.00 |
| August | 305.35 | 92.21 | 311.62 | 100.87 | 210.75 | 0.00 | 0.00 |
| September | 130.01 | 176.06 | 187.61 | 55.49 | 132.12 | 0.00 | 0.00 |
| October | 33.35 | 343.66 | 96.45 | 26.09 | 70.36 | 0.00 | 0.00 |
| November | 0.00 | 638.64 | 23.32 | 4.79 | 18.53 | 0.00 | 0.00 |
| December | 0.00 | 696.95 | 3.46 | 0.45 | 3.02 | 0.00 | 0.00 |
| Annual Sum or Average | 181.52 | 328.46 | 214.11 | 74.26 | 139.85 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 45.99 | 3.46 | 0.45 | 3.02 | 0.00 | 0.00 |
| Maximum of Months | 496.59 | 696.95 | 472.44 | 184.22 | 305.59 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: M N1 APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 0.00 | 406.00 | 5.09 | 0.00 | 5.09 | 0.00 | 0.00 |
| February | 0.00 | 363.68 | 22.48 | 0.00 | 22.48 | 0.00 | 0.00 |
| March | 4.27 | 268.46 | 60.31 | 0.02 | 60.29 | 0.00 | 0.00 |
| April | 45.02 | 138.07 | 109.72 | 3.07 | 106.66 | 0.00 | 0.00 |
| May | 127.94 | 59.97 | 168.20 | 27.17 | 141.03 | 0.00 | 0.00 |
| June | 212.21 | 26.93 | 216.85 | 47.59 | 169.26 | 0.00 | 0.00 |
| July | 184.07 | 32.56 | 183.01 | 30.11 | 152.90 | 0.00 | 0.00 |
| August | 94.00 | 56.64 | 117.57 | 6.36 | 111.22 | 0.00 | 0.00 |
| September | 24.07 | 116.97 | 65.40 | 0.19 | 65.21 | 0.00 | 0.00 |
| October | 2.10 | 228.16 | 31.65 | 0.00 | 31.65 | 0.00 | 0.00 |
| November | 0.00 | 395.77 | 9.82 | 0.00 | 9.82 | 0.00 | 0.00 |
| December | 0.00 | 425.84 | 1.54 | 0.00 | 1.54 | 0.00 | 0.00 |
| Annual Sum or Average | 58.14 | 209.10 | 82.94 | 9.59 | 73.35 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 26.93 | 1.54 | 0.00 | 1.54 | 0.00 | 0.00 |
| Maximum of Months | 212.21 | 425.84 | 216.85 | 47.59 | 169.26 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: M N2 APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 0.00 | 406.01 | 5.09 | 0.00 | 5.09 | 0.00 | 0.00 |
| February | 0.00 | 363.70 | 22.48 | 0.00 | 22.48 | 0.00 | 0.00 |
| March | 4.26 | 268.51 | 60.31 | 0.02 | 60.29 | 0.00 | 0.00 |
| April | 44.99 | 138.04 | 109.72 | 3.07 | 106.66 | 0.00 | 0.00 |
| May | 127.71 | 60.07 | 168.20 | 27.17 | 141.03 | 0.00 | 0.00 |
| June | 212.18 | 26.93 | 216.85 | 47.59 | 169.26 | 0.00 | 0.00 |
| July | 184.03 | 32.56 | 183.01 | 30.11 | 152.90 | 0.00 | 0.00 |
| August | 93.95 | 56.67 | 117.57 | 6.36 | 111.22 | 0.00 | 0.00 |
| September | 23.90 | 117.25 | 65.40 | 0.19 | 65.21 | 0.00 | 0.00 |
| October | 2.09 | 228.20 | 31.65 | 0.00 | 31.65 | 0.00 | 0.00 |
| November | 0.00 | 395.77 | 9.82 | 0.00 | 9.82 | 0.00 | 0.00 |
| December | 0.00 | 425.84 | 1.54 | 0.00 | 1.54 | 0.00 | 0.00 |
| Annual Sum or Average | 58.10 | 209.14 | 82.94 | 9.59 | 73.35 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 26.93 | 1.54 | 0.00 | 1.54 | 0.00 | 0.00 |
| Maximum of Months | 212.18 | 425.84 | 216.85 | 47.59 | 169.26 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: M S1 APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 34.61 | 364.31 | 62.86 | 41.89 | 20.97 | 0.00 | 0.00 |
| February | 171.89 | 291.54 | 210.30 | 146.25 | 64.06 | 0.00 | 0.00 |
| March | 343.37 | 222.01 | 356.49 | 240.42 | 116.08 | 0.00 | 0.00 |
| April | 479.05 | 143.46 | 442.26 | 276.03 | 166.22 | 0.00 | 0.00 |
| May | 404.32 | 77.88 | 362.92 | 188.15 | 174.77 | 0.00 | 0.00 |
| June | 381.50 | 39.42 | 331.84 | 136.41 | 195.43 | 0.00 | 0.00 |
| July | 377.59 | 41.33 | 319.80 | 139.68 | 180.11 | 0.00 | 0.00 |
| August | 382.58 | 63.78 | 330.90 | 182.57 | 148.33 | 0.00 | 0.00 |
| September | 273.99 | 115.13 | 263.41 | 157.17 | 106.24 | 0.00 | 0.00 |
| October | 172.48 | 190.97 | 193.59 | 122.71 | 70.88 | 0.00 | 0.00 |
| November | 65.03 | 337.89 | 104.52 | 73.34 | 31.18 | 0.00 | 0.00 |
| December | 2.94 | 405.64 | 18.41 | 12.95 | 5.45 | 0.00 | 0.00 |
| Annual Sum or Average | 257.68 | 190.64 | 249.71 | 142.91 | 106.79 | 0.00 | 0.00 |
| Minimum of Months | 2.94 | 39.42 | 18.41 | 12.95 | 5.45 | 0.00 | 0.00 |
| Maximum of Months | 479.05 | 405.64 | 442.26 | 276.03 | 195.43 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: M S2 APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 34.60 | 364.31 | 62.86 | 41.89 | 20.97 | 0.00 | 0.00 |
| February | 171.88 | 291.55 | 210.30 | 146.25 | 64.06 | 0.00 | 0.00 |
| March | 343.32 | 222.04 | 356.49 | 240.42 | 116.08 | 0.00 | 0.00 |
| April | 479.00 | 143.44 | 442.26 | 276.03 | 166.22 | 0.00 | 0.00 |
| May | 404.23 | 77.92 | 362.92 | 188.15 | 174.77 | 0.00 | 0.00 |
| June | 381.47 | 39.42 | 331.84 | 136.41 | 195.43 | 0.00 | 0.00 |
| July | 377.55 | 41.33 | 319.80 | 139.68 | 180.11 | 0.00 | 0.00 |
| August | 382.54 | 63.79 | 330.90 | 182.57 | 148.33 | 0.00 | 0.00 |
| September | 273.93 | 115.19 | 263.41 | 157.17 | 106.24 | 0.00 | 0.00 |
| October | 172.43 | 191.04 | 193.59 | 122.71 | 70.88 | 0.00 | 0.00 |
| November | 65.03 | 337.89 | 104.52 | 73.34 | 31.18 | 0.00 | 0.00 |
| December | 2.94 | 405.64 | 18.41 | 12.95 | 5.45 | 0.00 | 0.00 |
| Annual Sum or Average | 257.65 | 190.66 | 249.71 | 142.91 | 106.79 | 0.00 | 0.00 |
| Minimum of Months | 2.94 | 39.42 | 18.41 | 12.95 | 5.45 | 0.00 | 0.00 |
| Maximum of Months | 479.00 | 405.64 | 442.26 | 276.03 | 195.43 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: T SW APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 22.17 | 593.91 | 67.49 | 42.70 | 24.79 | 0.00 | 0.00 |
| February | 152.45 | 471.97 | 237.84 | 155.89 | 81.95 | 0.00 | 0.00 |
| March | 373.81 | 353.91 | 439.26 | 276.26 | 163.00 | 0.00 | 0.00 |
| April | 653.33 | 213.23 | 637.52 | 377.26 | 260.26 | 0.00 | 0.00 |
| May | 593.60 | 108.11 | 552.55 | 274.54 | 278.01 | 0.00 | 0.00 |
| June | 604.78 | 57.22 | 539.76 | 225.16 | 314.60 | 0.00 | 0.00 |
| July | 565.98 | 61.73 | 493.56 | 205.37 | 288.19 | 0.00 | 0.00 |
| August | 530.56 | 93.47 | 474.15 | 243.44 | 230.70 | 0.00 | 0.00 |
| September | 345.30 | 168.82 | 349.73 | 193.20 | 156.53 | 0.00 | 0.00 |
| October | 172.38 | 304.80 | 227.40 | 132.83 | 94.56 | 0.00 | 0.00 |
| November | 50.52 | 549.71 | 118.07 | 78.25 | 39.82 | 0.00 | 0.00 |
| December | 0.72 | 659.73 | 19.63 | 13.08 | 6.54 | 0.00 | 0.00 |
| Annual Sum or Average | 339.51 | 302.27 | 346.59 | 184.70 | 161.89 | 0.00 | 0.00 |
| Minimum of Months | 0.72 | 57.22 | 19.63 | 13.08 | 6.54 | 0.00 | 0.00 |
| Maximum of Months | 653.33 | 659.73 | 637.52 | 377.26 | 314.60 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: T NW APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 0.00 | 647.72 | 9.71 | 0.81 | 8.91 | 0.00 | 0.00 |
| February | 0.21 | 562.44 | 50.02 | 9.65 | 40.37 | 0.00 | 0.00 |
| March | 38.31 | 399.99 | 143.08 | 35.86 | 107.22 | 0.00 | 0.00 |
| April | 227.32 | 211.70 | 304.98 | 104.29 | 200.69 | 0.00 | 0.00 |
| May | 322.09 | 90.31 | 357.82 | 113.55 | 244.27 | 0.00 | 0.00 |
| June | 434.68 | 43.38 | 424.77 | 136.34 | 288.43 | 0.00 | 0.00 |
| July | 373.14 | 52.06 | 356.77 | 95.80 | 260.97 | 0.00 | 0.00 |
| August | 246.28 | 84.70 | 260.82 | 67.23 | 193.59 | 0.00 | 0.00 |
| September | 97.45 | 169.64 | 151.72 | 36.22 | 115.50 | 0.00 | 0.00 |
| October | 10.75 | 349.85 | 65.46 | 10.12 | 55.33 | 0.00 | 0.00 |
| November | 0.00 | 621.54 | 23.37 | 4.91 | 18.46 | 0.00 | 0.00 |
| December | 0.00 | 682.14 | 2.76 | 0.13 | 2.63 | 0.00 | 0.00 |
| Annual Sum or Average | 146.57 | 325.06 | 179.82 | 51.37 | 128.45 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 43.38 | 2.76 | 0.13 | 2.63 | 0.00 | 0.00 |
| Maximum of Months | 434.68 | 682.14 | 424.77 | 136.34 | 288.43 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: T SE APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 27.91 | 592.99 | 72.77 | 45.66 | 27.11 | 0.00 | 0.00 |
| February | 182.06 | 472.84 | 260.30 | 170.38 | 89.93 | 0.00 | 0.00 |
| March | 447.89 | 351.10 | 499.31 | 312.56 | 186.75 | 0.00 | 0.00 |
| April | 641.60 | 206.52 | 633.67 | 373.03 | 260.63 | 0.00 | 0.00 |
| May | 697.83 | 101.95 | 641.58 | 345.21 | 296.38 | 0.00 | 0.00 |
| June | 659.26 | 51.04 | 587.43 | 255.67 | 331.76 | 0.00 | 0.00 |
| July | 650.25 | 57.26 | 563.08 | 257.95 | 305.13 | 0.00 | 0.00 |
| August | 589.81 | 89.24 | 524.94 | 277.08 | 247.86 | 0.00 | 0.00 |
| September | 385.89 | 164.95 | 385.62 | 212.47 | 173.15 | 0.00 | 0.00 |
| October | 212.08 | 304.68 | 258.39 | 148.80 | 109.60 | 0.00 | 0.00 |
| November | 49.34 | 549.58 | 118.02 | 78.14 | 39.89 | 0.00 | 0.00 |
| December | 1.02 | 659.25 | 20.33 | 13.40 | 6.93 | 0.00 | 0.00 |
| Annual Sum or Average | 379.76 | 299.32 | 380.89 | 207.59 | 173.30 | 0.00 | 0.00 |
| Minimum of Months | 1.02 | 51.04 | 20.33 | 13.40 | 6.93 | 0.00 | 0.00 |
| Maximum of Months | 697.83 | 659.25 | 641.58 | 373.03 | 331.76 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: T NE APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 0.00 | 641.04 | 14.99 | 3.77 | 11.23 | 0.00 | 0.00 |
| February | 5.60 | 538.97 | 72.48 | 24.13 | 48.36 | 0.00 | 0.00 |
| March | 96.17 | 380.53 | 203.13 | 72.16 | 130.97 | 0.00 | 0.00 |
| April | 211.73 | 200.46 | 301.13 | 100.06 | 201.07 | 0.00 | 0.00 |
| May | 432.37 | 92.53 | 446.86 | 184.22 | 262.64 | 0.00 | 0.00 |
| June | 495.89 | 43.41 | 472.44 | 166.85 | 305.59 | 0.00 | 0.00 |
| July | 462.14 | 52.13 | 426.29 | 148.38 | 277.91 | 0.00 | 0.00 |
| August | 309.59 | 85.02 | 311.62 | 100.87 | 210.75 | 0.00 | 0.00 |
| September | 136.31 | 163.50 | 187.61 | 55.49 | 132.12 | 0.00 | 0.00 |
| October | 34.42 | 333.38 | 96.45 | 26.09 | 70.36 | 0.00 | 0.00 |
| November | 0.00 | 622.58 | 23.32 | 4.79 | 18.53 | 0.00 | 0.00 |
| December | 0.00 | 681.36 | 3.46 | 0.45 | 3.02 | 0.00 | 0.00 |
| Annual Sum or Average | 183.15 | 318.45 | 214.11 | 74.26 | 139.85 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 43.41 | 3.46 | 0.45 | 3.02 | 0.00 | 0.00 |
| Maximum of Months | 495.89 | 681.36 | 472.44 | 184.22 | 305.59 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: T N1 APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 0.00 | 397.76 | 5.09 | 0.00 | 5.09 | 0.00 | 0.00 |
| February | 0.00 | 355.88 | 22.48 | 0.00 | 22.48 | 0.00 | 0.00 |
| March | 4.58 | 262.13 | 60.31 | 0.02 | 60.29 | 0.00 | 0.00 |
| April | 45.97 | 134.10 | 109.72 | 3.07 | 106.66 | 0.00 | 0.00 |
| May | 133.38 | 55.69 | 168.20 | 27.17 | 141.03 | 0.00 | 0.00 |
| June | 212.06 | 25.95 | 216.85 | 47.59 | 169.26 | 0.00 | 0.00 |
| July | 183.89 | 31.48 | 183.01 | 30.11 | 152.90 | 0.00 | 0.00 |
| August | 97.04 | 52.77 | 117.57 | 6.36 | 111.22 | 0.00 | 0.00 |
| September | 27.52 | 107.83 | 65.40 | 0.19 | 65.21 | 0.00 | 0.00 |
| October | 2.32 | 221.82 | 31.65 | 0.00 | 31.65 | 0.00 | 0.00 |
| November | 0.00 | 386.96 | 9.82 | 0.00 | 9.82 | 0.00 | 0.00 |
| December | 0.00 | 417.42 | 1.54 | 0.00 | 1.54 | 0.00 | 0.00 |
| Annual Sum or Average | 59.24 | 203.34 | 82.94 | 9.59 | 73.35 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 25.95 | 1.54 | 0.00 | 1.54 | 0.00 | 0.00 |
| Maximum of Months | 212.06 | 417.42 | 216.85 | 47.59 | 169.26 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: T N2 APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 0.00 | 397.76 | 5.09 | 0.00 | 5.09 | 0.00 | 0.00 |
| February | 0.00 | 355.90 | 22.48 | 0.00 | 22.48 | 0.00 | 0.00 |
| March | 4.57 | 262.17 | 60.31 | 0.02 | 60.29 | 0.00 | 0.00 |
| April | 45.88 | 134.02 | 109.72 | 3.07 | 106.66 | 0.00 | 0.00 |
| May | 132.87 | 55.75 | 168.20 | 27.17 | 141.03 | 0.00 | 0.00 |
| June | 211.98 | 25.94 | 216.85 | 47.59 | 169.26 | 0.00 | 0.00 |
| July | 183.80 | 31.47 | 183.01 | 30.11 | 152.90 | 0.00 | 0.00 |
| August | 96.85 | 52.79 | 117.57 | 6.36 | 111.22 | 0.00 | 0.00 |
| September | 27.41 | 107.85 | 65.40 | 0.19 | 65.21 | 0.00 | 0.00 |
| October | 2.32 | 221.84 | 31.65 | 0.00 | 31.65 | 0.00 | 0.00 |
| November | 0.00 | 386.96 | 9.82 | 0.00 | 9.82 | 0.00 | 0.00 |
| December | 0.00 | 417.42 | 1.54 | 0.00 | 1.54 | 0.00 | 0.00 |
| Annual Sum or Average | 59.15 | 203.35 | 82.94 | 9.59 | 73.35 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 25.94 | 1.54 | 0.00 | 1.54 | 0.00 | 0.00 |
| Maximum of Months | 211.98 | 417.42 | 216.85 | 47.59 | 169.26 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: T S1 APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 35.11 | 356.36 | 62.86 | 41.89 | 20.97 | 0.00 | 0.00 |
| February | 173.14 | 284.52 | 210.30 | 146.25 | 64.06 | 0.00 | 0.00 |
| March | 344.01 | 216.46 | 356.49 | 240.42 | 116.08 | 0.00 | 0.00 |
| April | 479.56 | 137.16 | 442.26 | 276.03 | 166.22 | 0.00 | 0.00 |
| May | 406.28 | 71.26 | 362.92 | 188.15 | 174.77 | 0.00 | 0.00 |
| June | 380.47 | 37.54 | 331.84 | 136.41 | 195.43 | 0.00 | 0.00 |
| July | 376.37 | 39.62 | 319.80 | 139.68 | 180.11 | 0.00 | 0.00 |
| August | 383.05 | 59.82 | 330.90 | 182.57 | 148.33 | 0.00 | 0.00 |
| September | 277.77 | 105.25 | 263.41 | 157.17 | 106.24 | 0.00 | 0.00 |
| October | 173.81 | 184.70 | 193.59 | 122.71 | 70.88 | 0.00 | 0.00 |
| November | 66.02 | 329.75 | 104.52 | 73.34 | 31.18 | 0.00 | 0.00 |
| December | 3.05 | 397.16 | 18.41 | 12.95 | 5.45 | 0.00 | 0.00 |
| Annual Sum or Average | 258.45 | 184.50 | 249.71 | 142.91 | 106.79 | 0.00 | 0.00 |
| Minimum of Months | 3.05 | 37.54 | 18.41 | 12.95 | 5.45 | 0.00 | 0.00 |
| Maximum of Months | 479.56 | 397.16 | 442.26 | 276.03 | 195.43 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: T S2 APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 35.11 | 356.36 | 62.86 | 41.89 | 20.97 | 0.00 | 0.00 |
| February | 173.13 | 284.52 | 210.30 | 146.25 | 64.06 | 0.00 | 0.00 |
| March | 343.92 | 216.47 | 356.49 | 240.42 | 116.08 | 0.00 | 0.00 |
| April | 479.45 | 137.07 | 442.26 | 276.03 | 166.22 | 0.00 | 0.00 |
| May | 406.03 | 71.25 | 362.92 | 188.15 | 174.77 | 0.00 | 0.00 |
| June | 380.36 | 37.52 | 331.84 | 136.41 | 195.43 | 0.00 | 0.00 |
| July | 376.28 | 39.61 | 319.80 | 139.68 | 180.11 | 0.00 | 0.00 |
| August | 382.92 | 59.83 | 330.90 | 182.57 | 148.33 | 0.00 | 0.00 |
| September | 277.65 | 105.27 | 263.41 | 157.17 | 106.24 | 0.00 | 0.00 |
| October | 173.77 | 184.72 | 193.59 | 122.71 | 70.88 | 0.00 | 0.00 |
| November | 66.02 | 329.75 | 104.52 | 73.34 | 31.18 | 0.00 | 0.00 |
| December | 3.05 | 397.16 | 18.41 | 12.95 | 5.45 | 0.00 | 0.00 |
| Annual Sum or Average | 258.37 | 184.50 | 249.71 | 142.91 | 106.79 | 0.00 | 0.00 |
| Minimum of Months | 3.05 | 37.52 | 18.41 | 12.95 | 5.45 | 0.00 | 0.00 |
| Maximum of Months | 479.45 | 397.16 | 442.26 | 276.03 | 195.43 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: T CORRIDOR
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 0.32 | 59.88 | 2.38 | 0.90 | 1.47 | 0.00 | 0.00 |
| February | 6.13 | 50.18 | 12.00 | 5.79 | 6.21 | 0.00 | 0.00 |
| March | 28.69 | 37.00 | 34.27 | 17.31 | 16.96 | 0.00 | 0.00 |
| April | 42.03 | 20.67 | 45.93 | 23.27 | 22.65 | 0.00 | 0.00 |
| May | 72.16 | 10.61 | 66.87 | 37.69 | 29.18 | 0.00 | 0.00 |
| June | 67.51 | 5.49 | 61.33 | 28.62 | 32.71 | 0.00 | 0.00 |
| July | 66.01 | 6.19 | 58.38 | 28.38 | 30.00 | 0.00 | 0.00 |
| August | 50.49 | 9.49 | 46.56 | 22.68 | 23.88 | 0.00 | 0.00 |
| September | 27.35 | 17.17 | 29.32 | 13.27 | 16.05 | 0.00 | 0.00 |
| October | 11.02 | 32.20 | 15.55 | 6.26 | 9.29 | 0.00 | 0.00 |
| November | 0.25 | 57.85 | 3.24 | 1.15 | 2.09 | 0.00 | 0.00 |
| December | 0.00 | 64.43 | 0.46 | 0.11 | 0.35 | 0.00 | 0.00 |
| Annual Sum or Average | 31.17 | 30.83 | 31.48 | 15.52 | 15.96 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 5.49 | 0.46 | 0.11 | 0.35 | 0.00 | 0.00 |
| Maximum of Months | 72.16 | 64.43 | 66.87 | 37.69 | 32.71 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: G CORRIDOR
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 1.25 | 155.87 | 7.08 | 2.69 | 4.39 | 0.00 | 0.00 |
| February | 20.50 | 129.71 | 35.73 | 17.24 | 18.49 | 0.00 | 0.00 |
| March | 90.77 | 95.31 | 102.06 | 51.55 | 50.51 | 0.00 | 0.00 |
| April | 133.00 | 53.76 | 136.79 | 69.32 | 67.47 | 0.00 | 0.00 |
| May | 221.81 | 28.00 | 199.15 | 112.24 | 86.91 | 0.00 | 0.00 |
| June | 205.40 | 15.30 | 182.66 | 85.23 | 97.43 | 0.00 | 0.00 |
| July | 199.08 | 18.01 | 173.86 | 84.52 | 89.34 | 0.00 | 0.00 |
| August | 152.08 | 28.17 | 138.67 | 67.54 | 71.13 | 0.00 | 0.00 |
| September | 83.38 | 48.77 | 87.33 | 39.52 | 47.82 | 0.00 | 0.00 |
| October | 34.79 | 85.52 | 46.31 | 18.64 | 27.67 | 0.00 | 0.00 |
| November | 1.02 | 152.24 | 9.65 | 3.42 | 6.22 | 0.00 | 0.00 |
| December | 0.00 | 168.64 | 1.37 | 0.32 | 1.05 | 0.00 | 0.00 |
| Annual Sum or Average | 95.76 | 81.37 | 93.75 | 46.22 | 47.53 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 15.30 | 1.37 | 0.32 | 1.05 | 0.00 | 0.00 |
| Maximum of Months | 221.81 | 168.64 | 199.15 | 112.24 | 97.43 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: M CORRIDOR
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 0.28 | 63.14 | 2.38 | 0.90 | 1.47 | 0.00 | 0.00 |
| February | 5.82 | 53.03 | 12.00 | 5.79 | 6.21 | 0.00 | 0.00 |
| March | 28.05 | 39.03 | 34.27 | 17.31 | 16.96 | 0.00 | 0.00 |
| April | 41.17 | 21.77 | 45.93 | 23.27 | 22.65 | 0.00 | 0.00 |
| May | 71.00 | 11.34 | 66.87 | 37.69 | 29.18 | 0.00 | 0.00 |
| June | 67.23 | 5.69 | 61.33 | 28.62 | 32.71 | 0.00 | 0.00 |
| July | 65.81 | 6.40 | 58.38 | 28.38 | 30.00 | 0.00 | 0.00 |
| August | 49.77 | 10.09 | 46.56 | 22.68 | 23.88 | 0.00 | 0.00 |
| September | 26.29 | 18.83 | 29.32 | 13.27 | 16.05 | 0.00 | 0.00 |
| October | 10.64 | 34.24 | 15.55 | 6.26 | 9.29 | 0.00 | 0.00 |
| November | 0.21 | 61.20 | 3.24 | 1.15 | 2.09 | 0.00 | 0.00 |
| December | 0.00 | 67.80 | 0.46 | 0.11 | 0.35 | 0.00 | 0.00 |
| Annual Sum or Average | 30.69 | 32.61 | 31.48 | 15.52 | 15.96 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 5.69 | 0.46 | 0.11 | 0.35 | 0.00 | 0.00 |
| Maximum of Months | 71.00 | 67.80 | 66.87 | 37.69 | 32.71 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: G SW APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 60297454.42 | 0.158661E+10 | 0.180758E+09 | 0.114368E+09 | 66389896.67 | 0.00 | 0.00 |
| February | 0.375050E+09 | 0.113371E+10 | 0.575380E+09 | 0.377138E+09 | 0.198242E+09 | 0.00 | 0.00 |
| March | 0.102212E+10 | 0.935904E+09 | 0.117652E+10 | 0.739933E+09 | 0.436588E+09 | 0.00 | 0.00 |
| April | 0.173901E+10 | 0.540218E+09 | 0.165245E+10 | 0.977860E+09 | 0.674588E+09 | 0.00 | 0.00 |
| May | 0.163243E+10 | 0.279858E+09 | 0.147994E+10 | 0.735330E+09 | 0.744611E+09 | 0.00 | 0.00 |
| June | 0.159411E+10 | 0.148053E+09 | 0.139906E+10 | 0.583606E+09 | 0.815456E+09 | 0.00 | 0.00 |
| July | 0.153428E+10 | 0.169628E+09 | 0.132194E+10 | 0.550053E+09 | 0.771891E+09 | 0.00 | 0.00 |
| August | 0.142726E+10 | 0.265796E+09 | 0.126995E+10 | 0.652042E+09 | 0.617909E+09 | 0.00 | 0.00 |
| September | 0.896067E+09 | 0.457757E+09 | 0.906502E+09 | 0.500776E+09 | 0.405725E+09 | 0.00 | 0.00 |
| October | 0.466297E+09 | 0.821041E+09 | 0.609056E+09 | 0.355774E+09 | 0.253282E+09 | 0.00 | 0.00 |
| November | 0.131313E+09 | 0.143544E+10 | 0.306047E+09 | 0.202830E+09 | 0.103218E+09 | 0.00 | 0.00 |
| December | 1923034.00 | 0.176761E+10 | 52566949.28 | 35042882.05 | 17524067.23 | 0.00 | 0.00 |
| Annual Sum or Average | 0.108802E+11 | 0.954162E+10 | 0.109302E+11 | 0.582475E+10 | 0.510542E+10 | 0.00 | 0.00 |
| Minimum of Months | 1923034.00 | 0.148053E+09 | 52566949.28 | 35042882.05 | 17524067.23 | 0.00 | 0.00 |
| Maximum of Months | 0.173901E+10 | 0.176761E+10 | 0.165245E+10 | 0.977860E+09 | 0.815456E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: G NW APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.00 | 0.172888E+10 | 26018257.04 | 2158724.03 | 23859533.01 | 0.00 | 0.00 |
| February | 605124.41 | 0.134695E+10 | 0.121009E+09 | 23337954.53 | 97670711.08 | 0.00 | 0.00 |
| March | 0.108984E+09 | 0.105256E+10 | 0.383232E+09 | 96057766.23 | 0.287174E+09 | 0.00 | 0.00 |
| April | 0.619387E+09 | 0.532355E+09 | 0.790517E+09 | 0.270325E+09 | 0.520191E+09 | 0.00 | 0.00 |
| May | 0.920305E+09 | 0.221404E+09 | 0.958393E+09 | 0.304144E+09 | 0.654249E+09 | 0.00 | 0.00 |
| June | 0.116046E+10 | 0.107799E+09 | 0.110100E+10 | 0.353383E+09 | 0.747613E+09 | 0.00 | 0.00 |
| July | 0.101671E+10 | 0.139869E+09 | 0.955569E+09 | 0.256580E+09 | 0.698989E+09 | 0.00 | 0.00 |
| August | 0.659825E+09 | 0.235923E+09 | 0.698579E+09 | 0.180065E+09 | 0.518514E+09 | 0.00 | 0.00 |
| September | 0.255090E+09 | 0.444978E+09 | 0.393262E+09 | 93881873.16 | 0.299380E+09 | 0.00 | 0.00 |
| October | 29461311.62 | 0.938250E+09 | 0.175315E+09 | 27112847.54 | 0.148202E+09 | 0.00 | 0.00 |
| November | 547.34 | 0.162026E+10 | 60582993.17 | 12723436.19 | 47859556.98 | 0.00 | 0.00 |
| December | 0.00 | 0.182642E+10 | 7397924.85 | 350119.80 | 7047805.05 | 0.00 | 0.00 |
| Annual Sum or Average | 0.477083E+10 | 0.101957E+11 | 0.567087E+10 | 0.162012E+10 | 0.405075E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.107799E+09 | 7397924.85 | 350119.80 | 7047805.05 | 0.00 | 0.00 |
| Maximum of Months | 0.116046E+10 | 0.182642E+10 | 0.110100E+10 | 0.353383E+09 | 0.747613E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: OFFICE
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 83586625.48 | 0.142632E+10 | 0.194900E+09 | 0.122298E+09 | 72601907.43 | 0.00 | 0.00 |
| February | 0.472045E+09 | 0.101838E+10 | 0.629727E+09 | 0.412172E+09 | 0.217555E+09 | 0.00 | 0.00 |
| March | 0.126437E+10 | 0.827692E+09 | 0.133735E+10 | 0.837150E+09 | 0.500201E+09 | 0.00 | 0.00 |
| April | 0.173617E+10 | 0.476731E+09 | 0.164246E+10 | 0.966896E+09 | 0.675565E+09 | 0.00 | 0.00 |
| May | 0.190001E+10 | 0.278102E+09 | 0.171842E+10 | 0.924601E+09 | 0.793814E+09 | 0.00 | 0.00 |
| June | 0.170697E+10 | 0.152985E+09 | 0.152263E+10 | 0.662708E+09 | 0.859921E+09 | 0.00 | 0.00 |
| July | 0.171891E+10 | 0.188175E+09 | 0.150816E+10 | 0.690898E+09 | 0.817258E+09 | 0.00 | 0.00 |
| August | 0.156156E+10 | 0.287128E+09 | 0.140601E+10 | 0.742144E+09 | 0.663867E+09 | 0.00 | 0.00 |
| September | 0.997740E+09 | 0.459529E+09 | 0.999523E+09 | 0.550716E+09 | 0.448808E+09 | 0.00 | 0.00 |
| October | 0.593949E+09 | 0.747037E+09 | 0.692079E+09 | 0.398535E+09 | 0.293543E+09 | 0.00 | 0.00 |
| November | 0.140123E+09 | 0.129327E+10 | 0.305911E+09 | 0.202526E+09 | 0.103385E+09 | 0.00 | 0.00 |
| December | 3269761.25 | 0.160425E+10 | 54441923.82 | 35885776.02 | 18556147.81 | 0.00 | 0.00 |
| Annual Sum or Average | 0.121787E+11 | 0.875960E+10 | 0.120116E+11 | 0.654653E+10 | 0.546508E+10 | 0.00 | 0.00 |
| Minimum of Months | 3269761.25 | 0.152985E+09 | 54441923.82 | 35885776.02 | 18556147.81 | 0.00 | 0.00 |
| Maximum of Months | 0.190001E+10 | 0.160425E+10 | 0.171842E+10 | 0.966896E+09 | 0.859921E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: G NE APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.00 | 0.171059E+10 | 40160470.18 | 10088926.42 | 30071543.77 | 0.00 | 0.00 |
| February | 14228768.53 | 0.129007E+10 | 0.175356E+09 | 58372632.04 | 0.116983E+09 | 0.00 | 0.00 |
| March | 0.266230E+09 | 0.100171E+10 | 0.544062E+09 | 0.193275E+09 | 0.350787E+09 | 0.00 | 0.00 |
| April | 0.578444E+09 | 0.503184E+09 | 0.780529E+09 | 0.259361E+09 | 0.521168E+09 | 0.00 | 0.00 |
| May | 0.121926E+10 | 0.229535E+09 | 0.119687E+10 | 0.493416E+09 | 0.703452E+09 | 0.00 | 0.00 |
| June | 0.131681E+10 | 0.109696E+09 | 0.122456E+10 | 0.432484E+09 | 0.792079E+09 | 0.00 | 0.00 |
| July | 0.125593E+10 | 0.141129E+09 | 0.114178E+10 | 0.397426E+09 | 0.744356E+09 | 0.00 | 0.00 |
| August | 0.831917E+09 | 0.237732E+09 | 0.834640E+09 | 0.270167E+09 | 0.564472E+09 | 0.00 | 0.00 |
| September | 0.354994E+09 | 0.430157E+09 | 0.486283E+09 | 0.143821E+09 | 0.342462E+09 | 0.00 | 0.00 |
| October | 93294538.39 | 0.894358E+09 | 0.258337E+09 | 69874289.31 | 0.188463E+09 | 0.00 | 0.00 |
| November | 0.00 | 0.162247E+10 | 60447267.79 | 12420027.48 | 48027240.31 | 0.00 | 0.00 |
| December | 0.00 | 0.182415E+10 | 9272899.39 | 1193013.76 | 8079885.62 | 0.00 | 0.00 |
| Annual Sum or Average | 0.593111E+10 | 0.999478E+10 | 0.675230E+10 | 0.234190E+10 | 0.441040E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.109696E+09 | 9272899.39 | 1193013.76 | 8079885.62 | 0.00 | 0.00 |
| Maximum of Months | 0.131681E+10 | 0.182415E+10 | 0.122456E+10 | 0.493416E+09 | 0.792079E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: G N1 APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.00 | 0.106170E+10 | 13622807.86 | 0.00 | 13622807.86 | 0.00 | 0.00 |
| February | 0.00 | 0.853748E+09 | 54391655.15 | 0.00 | 54391655.15 | 0.00 | 0.00 |
| March | 13595345.98 | 0.690738E+09 | 0.161541E+09 | 53990.51 | 0.161487E+09 | 0.00 | 0.00 |
| April | 0.130418E+09 | 0.336767E+09 | 0.284403E+09 | 7945724.46 | 0.276457E+09 | 0.00 | 0.00 |
| May | 0.387916E+09 | 0.136647E+09 | 0.450494E+09 | 72760735.29 | 0.377733E+09 | 0.00 | 0.00 |
| June | 0.565791E+09 | 64963772.28 | 0.562063E+09 | 0.123352E+09 | 0.438711E+09 | 0.00 | 0.00 |
| July | 0.500353E+09 | 84345682.59 | 0.490169E+09 | 80654755.81 | 0.409514E+09 | 0.00 | 0.00 |
| August | 0.258483E+09 | 0.146420E+09 | 0.314910E+09 | 17029021.46 | 0.297881E+09 | 0.00 | 0.00 |
| September | 70475933.50 | 0.283159E+09 | 0.169525E+09 | 489125.69 | 0.169036E+09 | 0.00 | 0.00 |
| October | 6401986.86 | 0.593864E+09 | 84775064.66 | 0.00 | 84775064.66 | 0.00 | 0.00 |
| November | 0.00 | 0.100705E+10 | 25460057.00 | 0.00 | 25460057.00 | 0.00 | 0.00 |
| December | 0.00 | 0.111672E+10 | 4132448.42 | 0.00 | 4132448.42 | 0.00 | 0.00 |
| Annual Sum or Average | 0.193343E+10 | 0.637612E+10 | 0.261549E+10 | 0.302286E+09 | 0.231320E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 64963772.28 | 4132448.42 | 0.00 | 4132448.42 | 0.00 | 0.00 |
| Maximum of Months | 0.565791E+09 | 0.111672E+10 | 0.562063E+09 | 0.123352E+09 | 0.438711E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: G N2 APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.00 | 0.106171E+10 | 13622807.86 | 0.00 | 13622807.86 | 0.00 | 0.00 |
| February | 0.00 | 0.853780E+09 | 54391655.15 | 0.00 | 54391655.15 | 0.00 | 0.00 |
| March | 13580214.59 | 0.690830E+09 | 0.161541E+09 | 53990.51 | 0.161487E+09 | 0.00 | 0.00 |
| April | 0.130398E+09 | 0.336728E+09 | 0.284403E+09 | 7945724.46 | 0.276457E+09 | 0.00 | 0.00 |
| May | 0.386784E+09 | 0.137103E+09 | 0.450494E+09 | 72760735.29 | 0.377733E+09 | 0.00 | 0.00 |
| June | 0.565297E+09 | 65084438.73 | 0.562063E+09 | 0.123352E+09 | 0.438711E+09 | 0.00 | 0.00 |
| July | 0.500143E+09 | 84393725.46 | 0.490169E+09 | 80654755.81 | 0.409514E+09 | 0.00 | 0.00 |
| August | 0.258203E+09 | 0.146595E+09 | 0.314910E+09 | 17029021.46 | 0.297881E+09 | 0.00 | 0.00 |
| September | 70221355.89 | 0.283529E+09 | 0.169525E+09 | 489125.69 | 0.169036E+09 | 0.00 | 0.00 |
| October | 6386969.23 | 0.593962E+09 | 84775064.66 | 0.00 | 84775064.66 | 0.00 | 0.00 |
| November | 0.00 | 0.100705E+10 | 25460057.00 | 0.00 | 25460057.00 | 0.00 | 0.00 |
| December | 0.00 | 0.111672E+10 | 4132448.42 | 0.00 | 4132448.42 | 0.00 | 0.00 |
| Annual Sum or Average | 0.193101E+10 | 0.637748E+10 | 0.261549E+10 | 0.302286E+09 | 0.231320E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 65084438.73 | 4132448.42 | 0.00 | 4132448.42 | 0.00 | 0.00 |
| Maximum of Months | 0.565297E+09 | 0.111672E+10 | 0.562063E+09 | 0.123352E+09 | 0.438711E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: G S1 APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 94787601.20 | 0.952477E+09 | 0.168362E+09 | 0.112209E+09 | 56153171.53 | 0.00 | 0.00 |
| February | 0.422774E+09 | 0.685117E+09 | 0.508763E+09 | 0.353800E+09 | 0.154963E+09 | 0.00 | 0.00 |
| March | 0.933493E+09 | 0.573845E+09 | 0.954830E+09 | 0.643929E+09 | 0.310901E+09 | 0.00 | 0.00 |
| April | 0.126465E+10 | 0.346080E+09 | 0.114633E+10 | 0.715481E+09 | 0.430854E+09 | 0.00 | 0.00 |
| May | 0.110654E+10 | 0.185911E+09 | 0.972042E+09 | 0.503946E+09 | 0.468096E+09 | 0.00 | 0.00 |
| June | 0.998549E+09 | 97159889.88 | 0.860130E+09 | 0.353576E+09 | 0.506554E+09 | 0.00 | 0.00 |
| July | 0.101725E+10 | 0.108099E+09 | 0.856544E+09 | 0.374127E+09 | 0.482417E+09 | 0.00 | 0.00 |
| August | 0.102938E+10 | 0.168053E+09 | 0.886282E+09 | 0.489006E+09 | 0.397275E+09 | 0.00 | 0.00 |
| September | 0.718131E+09 | 0.287126E+09 | 0.682766E+09 | 0.407384E+09 | 0.275382E+09 | 0.00 | 0.00 |
| October | 0.468716E+09 | 0.497101E+09 | 0.518517E+09 | 0.328661E+09 | 0.189855E+09 | 0.00 | 0.00 |
| November | 0.171339E+09 | 0.859962E+09 | 0.270924E+09 | 0.190106E+09 | 80818039.55 | 0.00 | 0.00 |
| December | 8188213.19 | 0.106355E+10 | 49301472.86 | 34692762.25 | 14608710.60 | 0.00 | 0.00 |
| Annual Sum or Average | 0.823380E+10 | 0.582448E+10 | 0.787479E+10 | 0.450692E+10 | 0.336788E+10 | 0.00 | 0.00 |
| Minimum of Months | 8188213.19 | 97159889.88 | 49301472.86 | 34692762.25 | 14608710.60 | 0.00 | 0.00 |
| Maximum of Months | 0.126465E+10 | 0.106355E+10 | 0.114633E+10 | 0.715481E+09 | 0.506554E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: G S2 APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 94999950.09 | 0.949464E+09 | 0.168362E+09 | 0.112209E+09 | 56153171.53 | 0.00 | 0.00 |
| February | 0.423363E+09 | 0.682882E+09 | 0.508763E+09 | 0.353800E+09 | 0.154963E+09 | 0.00 | 0.00 |
| March | 0.934458E+09 | 0.571674E+09 | 0.954830E+09 | 0.643929E+09 | 0.310901E+09 | 0.00 | 0.00 |
| April | 0.126561E+10 | 0.344481E+09 | 0.114633E+10 | 0.715481E+09 | 0.430854E+09 | 0.00 | 0.00 |
| May | 0.110500E+10 | 0.187223E+09 | 0.972042E+09 | 0.503946E+09 | 0.468096E+09 | 0.00 | 0.00 |
| June | 0.997327E+09 | 97939586.53 | 0.860130E+09 | 0.353576E+09 | 0.506554E+09 | 0.00 | 0.00 |
| July | 0.101594E+10 | 0.109001E+09 | 0.856544E+09 | 0.374127E+09 | 0.482417E+09 | 0.00 | 0.00 |
| August | 0.102835E+10 | 0.169100E+09 | 0.886282E+09 | 0.489006E+09 | 0.397275E+09 | 0.00 | 0.00 |
| September | 0.717279E+09 | 0.288315E+09 | 0.682766E+09 | 0.407384E+09 | 0.275382E+09 | 0.00 | 0.00 |
| October | 0.469273E+09 | 0.495257E+09 | 0.518517E+09 | 0.328661E+09 | 0.189855E+09 | 0.00 | 0.00 |
| November | 0.171708E+09 | 0.857202E+09 | 0.270924E+09 | 0.190106E+09 | 80818039.55 | 0.00 | 0.00 |
| December | 8218942.89 | 0.106051E+10 | 49301472.86 | 34692762.25 | 14608710.60 | 0.00 | 0.00 |
| Annual Sum or Average | 0.823152E+10 | 0.581305E+10 | 0.787479E+10 | 0.450692E+10 | 0.336788E+10 | 0.00 | 0.00 |
| Minimum of Months | 8218942.89 | 97939586.53 | 49301472.86 | 34692762.25 | 14608710.60 | 0.00 | 0.00 |
| Maximum of Months | 0.126561E+10 | 0.106051E+10 | 0.114633E+10 | 0.715481E+09 | 0.506554E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: M SW APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 57928342.93 | 0.163036E+10 | 0.180758E+09 | 0.114368E+09 | 66389896.67 | 0.00 | 0.00 |
| February | 0.364353E+09 | 0.117210E+10 | 0.575380E+09 | 0.377138E+09 | 0.198242E+09 | 0.00 | 0.00 |
| March | 0.998874E+09 | 0.974432E+09 | 0.117652E+10 | 0.739933E+09 | 0.436588E+09 | 0.00 | 0.00 |
| April | 0.169405E+10 | 0.579958E+09 | 0.165245E+10 | 0.977860E+09 | 0.674588E+09 | 0.00 | 0.00 |
| May | 0.158091E+10 | 0.320332E+09 | 0.147994E+10 | 0.735330E+09 | 0.744611E+09 | 0.00 | 0.00 |
| June | 0.157093E+10 | 0.159314E+09 | 0.139906E+10 | 0.583606E+09 | 0.815456E+09 | 0.00 | 0.00 |
| July | 0.152030E+10 | 0.176043E+09 | 0.132194E+10 | 0.550053E+09 | 0.771891E+09 | 0.00 | 0.00 |
| August | 0.141682E+10 | 0.272241E+09 | 0.126995E+10 | 0.652042E+09 | 0.617909E+09 | 0.00 | 0.00 |
| September | 0.881187E+09 | 0.478584E+09 | 0.906502E+09 | 0.500776E+09 | 0.405725E+09 | 0.00 | 0.00 |
| October | 0.457375E+09 | 0.843482E+09 | 0.609056E+09 | 0.355774E+09 | 0.253282E+09 | 0.00 | 0.00 |
| November | 0.127889E+09 | 0.146380E+10 | 0.306047E+09 | 0.202830E+09 | 0.103218E+09 | 0.00 | 0.00 |
| December | 1734881.06 | 0.180900E+10 | 52566949.28 | 35042882.05 | 17524067.23 | 0.00 | 0.00 |
| Annual Sum or Average | 0.106723E+11 | 0.987965E+10 | 0.109302E+11 | 0.582475E+10 | 0.510542E+10 | 0.00 | 0.00 |
| Minimum of Months | 1734881.06 | 0.159314E+09 | 52566949.28 | 35042882.05 | 17524067.23 | 0.00 | 0.00 |
| Maximum of Months | 0.169405E+10 | 0.180900E+10 | 0.165245E+10 | 0.977860E+09 | 0.815456E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: M NW APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.00 | 0.177572E+10 | 26018257.04 | 2158724.03 | 23859533.01 | 0.00 | 0.00 |
| February | 409631.74 | 0.139528E+10 | 0.121009E+09 | 23337954.53 | 97670711.08 | 0.00 | 0.00 |
| March | 0.100083E+09 | 0.110056E+10 | 0.383232E+09 | 96057766.23 | 0.287174E+09 | 0.00 | 0.00 |
| April | 0.586994E+09 | 0.567742E+09 | 0.790517E+09 | 0.270325E+09 | 0.520191E+09 | 0.00 | 0.00 |
| May | 0.839649E+09 | 0.261078E+09 | 0.958393E+09 | 0.304144E+09 | 0.654249E+09 | 0.00 | 0.00 |
| June | 0.112590E+10 | 0.118347E+09 | 0.110100E+10 | 0.353383E+09 | 0.747613E+09 | 0.00 | 0.00 |
| July | 0.999159E+09 | 0.146803E+09 | 0.955569E+09 | 0.256580E+09 | 0.698989E+09 | 0.00 | 0.00 |
| August | 0.644613E+09 | 0.246374E+09 | 0.698579E+09 | 0.180065E+09 | 0.518514E+09 | 0.00 | 0.00 |
| September | 0.241187E+09 | 0.470886E+09 | 0.393262E+09 | 93881873.16 | 0.299380E+09 | 0.00 | 0.00 |
| October | 27289496.02 | 0.965966E+09 | 0.175315E+09 | 27112847.54 | 0.148202E+09 | 0.00 | 0.00 |
| November | 0.00 | 0.165284E+10 | 60582993.17 | 12723436.19 | 47859556.98 | 0.00 | 0.00 |
| December | 0.00 | 0.186887E+10 | 7397924.85 | 350119.80 | 7047805.05 | 0.00 | 0.00 |
| Annual Sum or Average | 0.456528E+10 | 0.105705E+11 | 0.567087E+10 | 0.162012E+10 | 0.405075E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.118347E+09 | 7397924.85 | 350119.80 | 7047805.05 | 0.00 | 0.00 |
| Maximum of Months | 0.112590E+10 | 0.186887E+10 | 0.110100E+10 | 0.353383E+09 | 0.747613E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: M SE APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 73024622.48 | 0.162746E+10 | 0.194900E+09 | 0.122298E+09 | 72601907.43 | 0.00 | 0.00 |
| February | 0.435873E+09 | 0.117383E+10 | 0.629727E+09 | 0.412172E+09 | 0.217555E+09 | 0.00 | 0.00 |
| March | 0.119709E+10 | 0.966613E+09 | 0.133735E+10 | 0.837150E+09 | 0.500201E+09 | 0.00 | 0.00 |
| April | 0.166116E+10 | 0.560310E+09 | 0.164246E+10 | 0.966896E+09 | 0.675565E+09 | 0.00 | 0.00 |
| May | 0.185854E+10 | 0.296722E+09 | 0.171842E+10 | 0.924601E+09 | 0.793814E+09 | 0.00 | 0.00 |
| June | 0.171218E+10 | 0.140090E+09 | 0.152263E+10 | 0.662708E+09 | 0.859921E+09 | 0.00 | 0.00 |
| July | 0.174652E+10 | 0.161803E+09 | 0.150816E+10 | 0.690898E+09 | 0.817258E+09 | 0.00 | 0.00 |
| August | 0.157519E+10 | 0.256675E+09 | 0.140601E+10 | 0.742144E+09 | 0.663867E+09 | 0.00 | 0.00 |
| September | 0.984031E+09 | 0.465893E+09 | 0.999523E+09 | 0.550716E+09 | 0.448808E+09 | 0.00 | 0.00 |
| October | 0.563639E+09 | 0.843769E+09 | 0.692079E+09 | 0.398535E+09 | 0.293543E+09 | 0.00 | 0.00 |
| November | 0.124960E+09 | 0.146341E+10 | 0.305911E+09 | 0.202526E+09 | 0.103385E+09 | 0.00 | 0.00 |
| December | 2531100.59 | 0.180763E+10 | 54441923.82 | 35885776.02 | 18556147.81 | 0.00 | 0.00 |
| Annual Sum or Average | 0.119347E+11 | 0.976421E+10 | 0.120116E+11 | 0.654653E+10 | 0.546508E+10 | 0.00 | 0.00 |
| Minimum of Months | 2531100.59 | 0.140090E+09 | 54441923.82 | 35885776.02 | 18556147.81 | 0.00 | 0.00 |
| Maximum of Months | 0.185854E+10 | 0.180763E+10 | 0.171842E+10 | 0.966896E+09 | 0.859921E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: M NE APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.00 | 0.175769E+10 | 40160470.18 | 10088926.42 | 30071543.77 | 0.00 | 0.00 |
| February | 12268065.52 | 0.133711E+10 | 0.175356E+09 | 58372632.04 | 0.116983E+09 | 0.00 | 0.00 |
| March | 0.252175E+09 | 0.104564E+10 | 0.544062E+09 | 0.193275E+09 | 0.350787E+09 | 0.00 | 0.00 |
| April | 0.544026E+09 | 0.536501E+09 | 0.780529E+09 | 0.259361E+09 | 0.521168E+09 | 0.00 | 0.00 |
| May | 0.114461E+10 | 0.269041E+09 | 0.119687E+10 | 0.493416E+09 | 0.703452E+09 | 0.00 | 0.00 |
| June | 0.128717E+10 | 0.119195E+09 | 0.122456E+10 | 0.432484E+09 | 0.792079E+09 | 0.00 | 0.00 |
| July | 0.123994E+10 | 0.147266E+09 | 0.114178E+10 | 0.397426E+09 | 0.744356E+09 | 0.00 | 0.00 |
| August | 0.817847E+09 | 0.246987E+09 | 0.834640E+09 | 0.270167E+09 | 0.564472E+09 | 0.00 | 0.00 |
| September | 0.336987E+09 | 0.456352E+09 | 0.486283E+09 | 0.143821E+09 | 0.342462E+09 | 0.00 | 0.00 |
| October | 89311395.69 | 0.920464E+09 | 0.258337E+09 | 69874289.31 | 0.188463E+09 | 0.00 | 0.00 |
| November | 0.00 | 0.165536E+10 | 60447267.79 | 12420027.48 | 48027240.31 | 0.00 | 0.00 |
| December | 0.00 | 0.186671E+10 | 9272899.39 | 1193013.76 | 8079885.62 | 0.00 | 0.00 |
| Annual Sum or Average | 0.572433E+10 | 0.103583E+11 | 0.675230E+10 | 0.234190E+10 | 0.441040E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.119195E+09 | 9272899.39 | 1193013.76 | 8079885.62 | 0.00 | 0.00 |
| Maximum of Months | 0.128717E+10 | 0.186671E+10 | 0.122456E+10 | 0.493416E+09 | 0.792079E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: M N1 APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.00 | 0.108744E+10 | 13622807.86 | 0.00 | 13622807.86 | 0.00 | 0.00 |
| February | 0.00 | 0.879814E+09 | 54391655.15 | 0.00 | 54391655.15 | 0.00 | 0.00 |
| March | 11430537.78 | 0.719037E+09 | 0.161541E+09 | 53990.51 | 0.161487E+09 | 0.00 | 0.00 |
| April | 0.116692E+09 | 0.357889E+09 | 0.284403E+09 | 7945724.46 | 0.276457E+09 | 0.00 | 0.00 |
| May | 0.342676E+09 | 0.160622E+09 | 0.450494E+09 | 72760735.29 | 0.377733E+09 | 0.00 | 0.00 |
| June | 0.550049E+09 | 69798475.18 | 0.562063E+09 | 0.123352E+09 | 0.438711E+09 | 0.00 | 0.00 |
| July | 0.493003E+09 | 87204090.50 | 0.490169E+09 | 80654755.81 | 0.409514E+09 | 0.00 | 0.00 |
| August | 0.251781E+09 | 0.151708E+09 | 0.314910E+09 | 17029021.46 | 0.297881E+09 | 0.00 | 0.00 |
| September | 62382902.11 | 0.303181E+09 | 0.169525E+09 | 489125.69 | 0.169036E+09 | 0.00 | 0.00 |
| October | 5617269.83 | 0.611098E+09 | 84775064.66 | 0.00 | 84775064.66 | 0.00 | 0.00 |
| November | 0.00 | 0.102584E+10 | 25460057.00 | 0.00 | 25460057.00 | 0.00 | 0.00 |
| December | 0.00 | 0.114057E+10 | 4132448.42 | 0.00 | 4132448.42 | 0.00 | 0.00 |
| Annual Sum or Average | 0.183363E+10 | 0.659420E+10 | 0.261549E+10 | 0.302286E+09 | 0.231320E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 69798475.18 | 4132448.42 | 0.00 | 4132448.42 | 0.00 | 0.00 |
| Maximum of Months | 0.550049E+09 | 0.114057E+10 | 0.562063E+09 | 0.123352E+09 | 0.438711E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: M N2 APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.00 | 0.108745E+10 | 13622807.86 | 0.00 | 13622807.86 | 0.00 | 0.00 |
| February | 0.00 | 0.879852E+09 | 54391655.15 | 0.00 | 54391655.15 | 0.00 | 0.00 |
| March | 11408789.37 | 0.719178E+09 | 0.161541E+09 | 53990.51 | 0.161487E+09 | 0.00 | 0.00 |
| April | 0.116606E+09 | 0.357808E+09 | 0.284403E+09 | 7945724.46 | 0.276457E+09 | 0.00 | 0.00 |
| May | 0.342072E+09 | 0.160899E+09 | 0.450494E+09 | 72760735.29 | 0.377733E+09 | 0.00 | 0.00 |
| June | 0.549966E+09 | 69797661.10 | 0.562063E+09 | 0.123352E+09 | 0.438711E+09 | 0.00 | 0.00 |
| July | 0.492901E+09 | 87210384.67 | 0.490169E+09 | 80654755.81 | 0.409514E+09 | 0.00 | 0.00 |
| August | 0.251634E+09 | 0.151781E+09 | 0.314910E+09 | 17029021.46 | 0.297881E+09 | 0.00 | 0.00 |
| September | 61940244.16 | 0.303920E+09 | 0.169525E+09 | 489125.69 | 0.169036E+09 | 0.00 | 0.00 |
| October | 5602105.39 | 0.611201E+09 | 84775064.66 | 0.00 | 84775064.66 | 0.00 | 0.00 |
| November | 0.00 | 0.102584E+10 | 25460057.00 | 0.00 | 25460057.00 | 0.00 | 0.00 |
| December | 0.00 | 0.114057E+10 | 4132448.42 | 0.00 | 4132448.42 | 0.00 | 0.00 |
| Annual Sum or Average | 0.183213E+10 | 0.659551E+10 | 0.261549E+10 | 0.302286E+09 | 0.231320E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 69797661.10 | 4132448.42 | 0.00 | 4132448.42 | 0.00 | 0.00 |
| Maximum of Months | 0.549966E+09 | 0.114057E+10 | 0.562063E+09 | 0.123352E+09 | 0.438711E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: M S1 APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 92687705.63 | 0.975766E+09 | 0.168362E+09 | 0.112209E+09 | 56153171.53 | 0.00 | 0.00 |
| February | 0.415833E+09 | 0.705297E+09 | 0.508763E+09 | 0.353800E+09 | 0.154963E+09 | 0.00 | 0.00 |
| March | 0.919693E+09 | 0.594622E+09 | 0.954830E+09 | 0.643929E+09 | 0.310901E+09 | 0.00 | 0.00 |
| April | 0.124169E+10 | 0.371856E+09 | 0.114633E+10 | 0.715481E+09 | 0.430854E+09 | 0.00 | 0.00 |
| May | 0.108292E+10 | 0.208585E+09 | 0.972042E+09 | 0.503946E+09 | 0.468096E+09 | 0.00 | 0.00 |
| June | 0.988848E+09 | 0.102167E+09 | 0.860130E+09 | 0.353576E+09 | 0.506554E+09 | 0.00 | 0.00 |
| July | 0.101133E+10 | 0.110696E+09 | 0.856544E+09 | 0.374127E+09 | 0.482417E+09 | 0.00 | 0.00 |
| August | 0.102469E+10 | 0.170833E+09 | 0.886282E+09 | 0.489006E+09 | 0.397275E+09 | 0.00 | 0.00 |
| September | 0.710184E+09 | 0.298420E+09 | 0.682766E+09 | 0.407384E+09 | 0.275382E+09 | 0.00 | 0.00 |
| October | 0.461962E+09 | 0.511493E+09 | 0.518517E+09 | 0.328661E+09 | 0.189855E+09 | 0.00 | 0.00 |
| November | 0.168552E+09 | 0.875805E+09 | 0.270924E+09 | 0.190106E+09 | 80818039.55 | 0.00 | 0.00 |
| December | 7882760.39 | 0.108648E+10 | 49301472.86 | 34692762.25 | 14608710.60 | 0.00 | 0.00 |
| Annual Sum or Average | 0.812627E+10 | 0.601202E+10 | 0.787479E+10 | 0.450692E+10 | 0.336788E+10 | 0.00 | 0.00 |
| Minimum of Months | 7882760.39 | 0.102167E+09 | 49301472.86 | 34692762.25 | 14608710.60 | 0.00 | 0.00 |
| Maximum of Months | 0.124169E+10 | 0.108648E+10 | 0.114633E+10 | 0.715481E+09 | 0.506554E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: M S2 APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 92684791.54 | 0.975774E+09 | 0.168362E+09 | 0.112209E+09 | 56153171.53 | 0.00 | 0.00 |
| February | 0.415809E+09 | 0.705326E+09 | 0.508763E+09 | 0.353800E+09 | 0.154963E+09 | 0.00 | 0.00 |
| March | 0.919553E+09 | 0.594723E+09 | 0.954830E+09 | 0.643929E+09 | 0.310901E+09 | 0.00 | 0.00 |
| April | 0.124156E+10 | 0.371804E+09 | 0.114633E+10 | 0.715481E+09 | 0.430854E+09 | 0.00 | 0.00 |
| May | 0.108270E+10 | 0.208693E+09 | 0.972042E+09 | 0.503946E+09 | 0.468096E+09 | 0.00 | 0.00 |
| June | 0.988773E+09 | 0.102166E+09 | 0.860130E+09 | 0.353576E+09 | 0.506554E+09 | 0.00 | 0.00 |
| July | 0.101124E+10 | 0.110703E+09 | 0.856544E+09 | 0.374127E+09 | 0.482417E+09 | 0.00 | 0.00 |
| August | 0.102460E+10 | 0.170854E+09 | 0.886282E+09 | 0.489006E+09 | 0.397275E+09 | 0.00 | 0.00 |
| September | 0.710024E+09 | 0.298567E+09 | 0.682766E+09 | 0.407384E+09 | 0.275382E+09 | 0.00 | 0.00 |
| October | 0.461844E+09 | 0.511681E+09 | 0.518517E+09 | 0.328661E+09 | 0.189855E+09 | 0.00 | 0.00 |
| November | 0.168549E+09 | 0.875803E+09 | 0.270924E+09 | 0.190106E+09 | 80818039.55 | 0.00 | 0.00 |
| December | 7882677.98 | 0.108648E+10 | 49301472.86 | 34692762.25 | 14608710.60 | 0.00 | 0.00 |
| Annual Sum or Average | 0.812522E+10 | 0.601257E+10 | 0.787479E+10 | 0.450692E+10 | 0.336788E+10 | 0.00 | 0.00 |
| Minimum of Months | 7882677.98 | 0.102166E+09 | 49301472.86 | 34692762.25 | 14608710.60 | 0.00 | 0.00 |
| Maximum of Months | 0.124156E+10 | 0.108648E+10 | 0.114633E+10 | 0.715481E+09 | 0.506554E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: T SW APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 59378634.83 | 0.159074E+10 | 0.180758E+09 | 0.114368E+09 | 66389896.67 | 0.00 | 0.00 |
| February | 0.368808E+09 | 0.114180E+10 | 0.575380E+09 | 0.377138E+09 | 0.198242E+09 | 0.00 | 0.00 |
| March | 0.100121E+10 | 0.947901E+09 | 0.117652E+10 | 0.739933E+09 | 0.436588E+09 | 0.00 | 0.00 |
| April | 0.169342E+10 | 0.552704E+09 | 0.165245E+10 | 0.977860E+09 | 0.674588E+09 | 0.00 | 0.00 |
| May | 0.158990E+10 | 0.289572E+09 | 0.147994E+10 | 0.735330E+09 | 0.744611E+09 | 0.00 | 0.00 |
| June | 0.156759E+10 | 0.148320E+09 | 0.139906E+10 | 0.583606E+09 | 0.815456E+09 | 0.00 | 0.00 |
| July | 0.151593E+10 | 0.165342E+09 | 0.132194E+10 | 0.550053E+09 | 0.771891E+09 | 0.00 | 0.00 |
| August | 0.142107E+10 | 0.250337E+09 | 0.126995E+10 | 0.652042E+09 | 0.617909E+09 | 0.00 | 0.00 |
| September | 0.895005E+09 | 0.437569E+09 | 0.906502E+09 | 0.500776E+09 | 0.405725E+09 | 0.00 | 0.00 |
| October | 0.461697E+09 | 0.816365E+09 | 0.609056E+09 | 0.355774E+09 | 0.253282E+09 | 0.00 | 0.00 |
| November | 0.130938E+09 | 0.142486E+10 | 0.306047E+09 | 0.202830E+09 | 0.103218E+09 | 0.00 | 0.00 |
| December | 1920496.39 | 0.176702E+10 | 52566949.28 | 35042882.05 | 17524067.23 | 0.00 | 0.00 |
| Annual Sum or Average | 0.107069E+11 | 0.953253E+10 | 0.109302E+11 | 0.582475E+10 | 0.510542E+10 | 0.00 | 0.00 |
| Minimum of Months | 1920496.39 | 0.148320E+09 | 52566949.28 | 35042882.05 | 17524067.23 | 0.00 | 0.00 |
| Maximum of Months | 0.169342E+10 | 0.176702E+10 | 0.165245E+10 | 0.977860E+09 | 0.815456E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: T NW APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.00 | 0.173485E+10 | 26018257.04 | 2158724.03 | 23859533.01 | 0.00 | 0.00 |
| February | 511305.98 | 0.136065E+10 | 0.121009E+09 | 23337954.53 | 97670711.08 | 0.00 | 0.00 |
| March | 0.102618E+09 | 0.107134E+10 | 0.383232E+09 | 96057766.23 | 0.287174E+09 | 0.00 | 0.00 |
| April | 0.589201E+09 | 0.548738E+09 | 0.790517E+09 | 0.270325E+09 | 0.520191E+09 | 0.00 | 0.00 |
| May | 0.862679E+09 | 0.241891E+09 | 0.958393E+09 | 0.304144E+09 | 0.654249E+09 | 0.00 | 0.00 |
| June | 0.112669E+10 | 0.112447E+09 | 0.110100E+10 | 0.353383E+09 | 0.747613E+09 | 0.00 | 0.00 |
| July | 0.999420E+09 | 0.139440E+09 | 0.955569E+09 | 0.256580E+09 | 0.698989E+09 | 0.00 | 0.00 |
| August | 0.659641E+09 | 0.226865E+09 | 0.698579E+09 | 0.180065E+09 | 0.518514E+09 | 0.00 | 0.00 |
| September | 0.252594E+09 | 0.439701E+09 | 0.393262E+09 | 93881873.16 | 0.299380E+09 | 0.00 | 0.00 |
| October | 28787672.32 | 0.937050E+09 | 0.175315E+09 | 27112847.54 | 0.148202E+09 | 0.00 | 0.00 |
| November | 0.00 | 0.161104E+10 | 60582993.17 | 12723436.19 | 47859556.98 | 0.00 | 0.00 |
| December | 0.00 | 0.182705E+10 | 7397924.85 | 350119.80 | 7047805.05 | 0.00 | 0.00 |
| Annual Sum or Average | 0.462215E+10 | 0.102511E+11 | 0.567087E+10 | 0.162012E+10 | 0.405075E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.112447E+09 | 7397924.85 | 350119.80 | 7047805.05 | 0.00 | 0.00 |
| Maximum of Months | 0.112669E+10 | 0.182705E+10 | 0.110100E+10 | 0.353383E+09 | 0.747613E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: T SE APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 74755413.06 | 0.158827E+10 | 0.194900E+09 | 0.122298E+09 | 72601907.43 | 0.00 | 0.00 |
| February | 0.440438E+09 | 0.114389E+10 | 0.629727E+09 | 0.412172E+09 | 0.217555E+09 | 0.00 | 0.00 |
| March | 0.119963E+10 | 0.940380E+09 | 0.133735E+10 | 0.837150E+09 | 0.500201E+09 | 0.00 | 0.00 |
| April | 0.166302E+10 | 0.535303E+09 | 0.164246E+10 | 0.966896E+09 | 0.675565E+09 | 0.00 | 0.00 |
| May | 0.186907E+10 | 0.273065E+09 | 0.171842E+10 | 0.924601E+09 | 0.793814E+09 | 0.00 | 0.00 |
| June | 0.170879E+10 | 0.132290E+09 | 0.152263E+10 | 0.662708E+09 | 0.859921E+09 | 0.00 | 0.00 |
| July | 0.174163E+10 | 0.153375E+09 | 0.150816E+10 | 0.690898E+09 | 0.817258E+09 | 0.00 | 0.00 |
| August | 0.157974E+10 | 0.239017E+09 | 0.140601E+10 | 0.742144E+09 | 0.663867E+09 | 0.00 | 0.00 |
| September | 0.100023E+10 | 0.427552E+09 | 0.999523E+09 | 0.550716E+09 | 0.448808E+09 | 0.00 | 0.00 |
| October | 0.568044E+09 | 0.816044E+09 | 0.692079E+09 | 0.398535E+09 | 0.293543E+09 | 0.00 | 0.00 |
| November | 0.127892E+09 | 0.142452E+10 | 0.305911E+09 | 0.202526E+09 | 0.103385E+09 | 0.00 | 0.00 |
| December | 2725459.59 | 0.176573E+10 | 54441923.82 | 35885776.02 | 18556147.81 | 0.00 | 0.00 |
| Annual Sum or Average | 0.119760E+11 | 0.943943E+10 | 0.120116E+11 | 0.654653E+10 | 0.546508E+10 | 0.00 | 0.00 |
| Minimum of Months | 2725459.59 | 0.132290E+09 | 54441923.82 | 35885776.02 | 18556147.81 | 0.00 | 0.00 |
| Maximum of Months | 0.186907E+10 | 0.176573E+10 | 0.171842E+10 | 0.966896E+09 | 0.859921E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: T NE APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.00 | 0.171696E+10 | 40160470.18 | 10088926.42 | 30071543.77 | 0.00 | 0.00 |
| February | 13540204.40 | 0.130388E+10 | 0.175356E+09 | 58372632.04 | 0.116983E+09 | 0.00 | 0.00 |
| March | 0.257576E+09 | 0.101922E+10 | 0.544062E+09 | 0.193275E+09 | 0.350787E+09 | 0.00 | 0.00 |
| April | 0.548801E+09 | 0.519588E+09 | 0.780529E+09 | 0.259361E+09 | 0.521168E+09 | 0.00 | 0.00 |
| May | 0.115807E+10 | 0.247845E+09 | 0.119687E+10 | 0.493416E+09 | 0.703452E+09 | 0.00 | 0.00 |
| June | 0.128534E+10 | 0.112528E+09 | 0.122456E+10 | 0.432484E+09 | 0.792079E+09 | 0.00 | 0.00 |
| July | 0.123779E+10 | 0.139633E+09 | 0.114178E+10 | 0.397426E+09 | 0.744356E+09 | 0.00 | 0.00 |
| August | 0.829211E+09 | 0.227708E+09 | 0.834640E+09 | 0.270167E+09 | 0.564472E+09 | 0.00 | 0.00 |
| September | 0.353314E+09 | 0.423799E+09 | 0.486283E+09 | 0.143821E+09 | 0.342462E+09 | 0.00 | 0.00 |
| October | 92203643.76 | 0.892913E+09 | 0.258337E+09 | 69874289.31 | 0.188463E+09 | 0.00 | 0.00 |
| November | 0.00 | 0.161372E+10 | 60447267.79 | 12420027.48 | 48027240.31 | 0.00 | 0.00 |
| December | 0.00 | 0.182495E+10 | 9272899.39 | 1193013.76 | 8079885.62 | 0.00 | 0.00 |
| Annual Sum or Average | 0.577585E+10 | 0.100427E+11 | 0.675230E+10 | 0.234190E+10 | 0.441040E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.112528E+09 | 9272899.39 | 1193013.76 | 8079885.62 | 0.00 | 0.00 |
| Maximum of Months | 0.128534E+10 | 0.182495E+10 | 0.122456E+10 | 0.493416E+09 | 0.792079E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: T N1 APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.00 | 0.106535E+10 | 13622807.86 | 0.00 | 13622807.86 | 0.00 | 0.00 |
| February | 0.00 | 0.860955E+09 | 54391655.15 | 0.00 | 54391655.15 | 0.00 | 0.00 |
| March | 12271507.27 | 0.702082E+09 | 0.161541E+09 | 53990.51 | 0.161487E+09 | 0.00 | 0.00 |
| April | 0.119152E+09 | 0.347577E+09 | 0.284403E+09 | 7945724.46 | 0.276457E+09 | 0.00 | 0.00 |
| May | 0.357232E+09 | 0.149165E+09 | 0.450494E+09 | 72760735.29 | 0.377733E+09 | 0.00 | 0.00 |
| June | 0.549671E+09 | 67270213.55 | 0.562063E+09 | 0.123352E+09 | 0.438711E+09 | 0.00 | 0.00 |
| July | 0.492529E+09 | 84310069.57 | 0.490169E+09 | 80654755.81 | 0.409514E+09 | 0.00 | 0.00 |
| August | 0.259913E+09 | 0.141352E+09 | 0.314910E+09 | 17029021.46 | 0.297881E+09 | 0.00 | 0.00 |
| September | 71320109.03 | 0.279483E+09 | 0.169525E+09 | 489125.69 | 0.169036E+09 | 0.00 | 0.00 |
| October | 6224794.07 | 0.594120E+09 | 84775064.66 | 0.00 | 84775064.66 | 0.00 | 0.00 |
| November | 0.00 | 0.100299E+10 | 25460057.00 | 0.00 | 25460057.00 | 0.00 | 0.00 |
| December | 0.00 | 0.111800E+10 | 4132448.42 | 0.00 | 4132448.42 | 0.00 | 0.00 |
| Annual Sum or Average | 0.186831E+10 | 0.641267E+10 | 0.261549E+10 | 0.302286E+09 | 0.231320E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 67270213.55 | 4132448.42 | 0.00 | 4132448.42 | 0.00 | 0.00 |
| Maximum of Months | 0.549671E+09 | 0.111800E+10 | 0.562063E+09 | 0.123352E+09 | 0.438711E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: T N2 APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.00 | 0.106536E+10 | 13622807.86 | 0.00 | 13622807.86 | 0.00 | 0.00 |
| February | 0.00 | 0.860989E+09 | 54391655.15 | 0.00 | 54391655.15 | 0.00 | 0.00 |
| March | 12236762.57 | 0.702187E+09 | 0.161541E+09 | 53990.51 | 0.161487E+09 | 0.00 | 0.00 |
| April | 0.118923E+09 | 0.347384E+09 | 0.284403E+09 | 7945724.46 | 0.276457E+09 | 0.00 | 0.00 |
| May | 0.355891E+09 | 0.149321E+09 | 0.450494E+09 | 72760735.29 | 0.377733E+09 | 0.00 | 0.00 |
| June | 0.549463E+09 | 67236185.02 | 0.562063E+09 | 0.123352E+09 | 0.438711E+09 | 0.00 | 0.00 |
| July | 0.492294E+09 | 84280361.95 | 0.490169E+09 | 80654755.81 | 0.409514E+09 | 0.00 | 0.00 |
| August | 0.259399E+09 | 0.141386E+09 | 0.314910E+09 | 17029021.46 | 0.297881E+09 | 0.00 | 0.00 |
| September | 71050704.95 | 0.279544E+09 | 0.169525E+09 | 489125.69 | 0.169036E+09 | 0.00 | 0.00 |
| October | 6204179.71 | 0.594187E+09 | 84775064.66 | 0.00 | 84775064.66 | 0.00 | 0.00 |
| November | 0.00 | 0.100299E+10 | 25460057.00 | 0.00 | 25460057.00 | 0.00 | 0.00 |
| December | 0.00 | 0.111801E+10 | 4132448.42 | 0.00 | 4132448.42 | 0.00 | 0.00 |
| Annual Sum or Average | 0.186546E+10 | 0.641287E+10 | 0.261549E+10 | 0.302286E+09 | 0.231320E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 67236185.02 | 4132448.42 | 0.00 | 4132448.42 | 0.00 | 0.00 |
| Maximum of Months | 0.549463E+09 | 0.111801E+10 | 0.562063E+09 | 0.123352E+09 | 0.438711E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: T S1 APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 94047295.02 | 0.954471E+09 | 0.168362E+09 | 0.112209E+09 | 56153171.53 | 0.00 | 0.00 |
| February | 0.418869E+09 | 0.688307E+09 | 0.508763E+09 | 0.353800E+09 | 0.154963E+09 | 0.00 | 0.00 |
| March | 0.921391E+09 | 0.579762E+09 | 0.954830E+09 | 0.643929E+09 | 0.310901E+09 | 0.00 | 0.00 |
| April | 0.124302E+10 | 0.355510E+09 | 0.114633E+10 | 0.715481E+09 | 0.430854E+09 | 0.00 | 0.00 |
| May | 0.108817E+10 | 0.190866E+09 | 0.972042E+09 | 0.503946E+09 | 0.468096E+09 | 0.00 | 0.00 |
| June | 0.986166E+09 | 97290860.69 | 0.860130E+09 | 0.353576E+09 | 0.506554E+09 | 0.00 | 0.00 |
| July | 0.100807E+10 | 0.106127E+09 | 0.856544E+09 | 0.374127E+09 | 0.482417E+09 | 0.00 | 0.00 |
| August | 0.102597E+10 | 0.160231E+09 | 0.886282E+09 | 0.489006E+09 | 0.397275E+09 | 0.00 | 0.00 |
| September | 0.719978E+09 | 0.272805E+09 | 0.682766E+09 | 0.407384E+09 | 0.275382E+09 | 0.00 | 0.00 |
| October | 0.465532E+09 | 0.494693E+09 | 0.518517E+09 | 0.328661E+09 | 0.189855E+09 | 0.00 | 0.00 |
| November | 0.171117E+09 | 0.854716E+09 | 0.270924E+09 | 0.190106E+09 | 80818039.55 | 0.00 | 0.00 |
| December | 8174668.19 | 0.106374E+10 | 49301472.86 | 34692762.25 | 14608710.60 | 0.00 | 0.00 |
| Annual Sum or Average | 0.815052E+10 | 0.581852E+10 | 0.787479E+10 | 0.450692E+10 | 0.336788E+10 | 0.00 | 0.00 |
| Minimum of Months | 8174668.19 | 97290860.69 | 49301472.86 | 34692762.25 | 14608710.60 | 0.00 | 0.00 |
| Maximum of Months | 0.124302E+10 | 0.106374E+10 | 0.114633E+10 | 0.715481E+09 | 0.506554E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: T S2 APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 94042405.65 | 0.954476E+09 | 0.168362E+09 | 0.112209E+09 | 56153171.53 | 0.00 | 0.00 |
| February | 0.418829E+09 | 0.688318E+09 | 0.508763E+09 | 0.353800E+09 | 0.154963E+09 | 0.00 | 0.00 |
| March | 0.921159E+09 | 0.579803E+09 | 0.954830E+09 | 0.643929E+09 | 0.310901E+09 | 0.00 | 0.00 |
| April | 0.124273E+10 | 0.355274E+09 | 0.114633E+10 | 0.715481E+09 | 0.430854E+09 | 0.00 | 0.00 |
| May | 0.108751E+10 | 0.190833E+09 | 0.972042E+09 | 0.503946E+09 | 0.468096E+09 | 0.00 | 0.00 |
| June | 0.985886E+09 | 97246750.34 | 0.860130E+09 | 0.353576E+09 | 0.506554E+09 | 0.00 | 0.00 |
| July | 0.100782E+10 | 0.106093E+09 | 0.856544E+09 | 0.374127E+09 | 0.482417E+09 | 0.00 | 0.00 |
| August | 0.102562E+10 | 0.160244E+09 | 0.886282E+09 | 0.489006E+09 | 0.397275E+09 | 0.00 | 0.00 |
| September | 0.719676E+09 | 0.272864E+09 | 0.682766E+09 | 0.407384E+09 | 0.275382E+09 | 0.00 | 0.00 |
| October | 0.465417E+09 | 0.494748E+09 | 0.518517E+09 | 0.328661E+09 | 0.189855E+09 | 0.00 | 0.00 |
| November | 0.171112E+09 | 0.854710E+09 | 0.270924E+09 | 0.190106E+09 | 80818039.55 | 0.00 | 0.00 |
| December | 8174510.36 | 0.106375E+10 | 49301472.86 | 34692762.25 | 14608710.60 | 0.00 | 0.00 |
| Annual Sum or Average | 0.814798E+10 | 0.581836E+10 | 0.787479E+10 | 0.450692E+10 | 0.336788E+10 | 0.00 | 0.00 |
| Minimum of Months | 8174510.36 | 97246750.34 | 49301472.86 | 34692762.25 | 14608710.60 | 0.00 | 0.00 |
| Maximum of Months | 0.124273E+10 | 0.106375E+10 | 0.114633E+10 | 0.715481E+09 | 0.506554E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: T CORRIDOR
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 849223.16 | 0.160380E+09 | 6367820.09 | 2420878.96 | 3946941.13 | 0.00 | 0.00 |
| February | 14837220.77 | 0.121397E+09 | 29025775.07 | 14006750.66 | 15019024.42 | 0.00 | 0.00 |
| March | 76849954.45 | 99113911.46 | 91787564.27 | 46364175.95 | 45423388.32 | 0.00 | 0.00 |
| April | 0.108938E+09 | 53572021.43 | 0.119048E+09 | 60328019.93 | 58719500.19 | 0.00 | 0.00 |
| May | 0.193287E+09 | 28415359.31 | 0.179095E+09 | 0.100938E+09 | 78157425.01 | 0.00 | 0.00 |
| June | 0.174997E+09 | 14241343.75 | 0.158969E+09 | 74177353.37 | 84792050.43 | 0.00 | 0.00 |
| July | 0.176794E+09 | 16569677.09 | 0.156357E+09 | 76010480.34 | 80346501.78 | 0.00 | 0.00 |
| August | 0.135246E+09 | 25409076.26 | 0.124711E+09 | 60741565.17 | 63969741.86 | 0.00 | 0.00 |
| September | 70886824.73 | 44507406.40 | 76007325.25 | 34393055.66 | 41614269.59 | 0.00 | 0.00 |
| October | 29521947.35 | 86237834.85 | 41646905.03 | 16766620.14 | 24880284.89 | 0.00 | 0.00 |
| November | 635924.38 | 0.149950E+09 | 8395323.64 | 2980236.15 | 5415087.49 | 0.00 | 0.00 |
| December | 0.00 | 0.172557E+09 | 1233472.13 | 286268.51 | 947203.62 | 0.00 | 0.00 |
| Annual Sum or Average | 0.982843E+09 | 0.972350E+09 | 0.992645E+09 | 0.489413E+09 | 0.503231E+09 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 14241343.75 | 1233472.13 | 286268.51 | 947203.62 | 0.00 | 0.00 |
| Maximum of Months | 0.193287E+09 | 0.172557E+09 | 0.179095E+09 | 0.100938E+09 | 84792050.43 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: G CORRIDOR
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 3349913.24 | 0.417490E+09 | 18964952.95 | 7209980.01 | 11754972.94 | 0.00 | 0.00 |
| February | 49598597.42 | 0.313789E+09 | 86445981.62 | 41715589.22 | 44730392.40 | 0.00 | 0.00 |
| March | 0.243123E+09 | 0.255269E+09 | 0.273366E+09 | 0.138084E+09 | 0.135282E+09 | 0.00 | 0.00 |
| April | 0.344735E+09 | 0.139356E+09 | 0.354553E+09 | 0.179672E+09 | 0.174881E+09 | 0.00 | 0.00 |
| May | 0.594091E+09 | 74984262.57 | 0.533390E+09 | 0.300618E+09 | 0.232772E+09 | 0.00 | 0.00 |
| June | 0.532391E+09 | 39647124.78 | 0.473450E+09 | 0.220919E+09 | 0.252532E+09 | 0.00 | 0.00 |
| July | 0.533223E+09 | 48242555.58 | 0.465670E+09 | 0.226378E+09 | 0.239292E+09 | 0.00 | 0.00 |
| August | 0.407333E+09 | 75446917.32 | 0.371421E+09 | 0.180903E+09 | 0.190518E+09 | 0.00 | 0.00 |
| September | 0.216116E+09 | 0.126415E+09 | 0.226369E+09 | 0.102431E+09 | 0.123938E+09 | 0.00 | 0.00 |
| October | 93188404.39 | 0.229050E+09 | 0.124035E+09 | 49935167.36 | 74099680.19 | 0.00 | 0.00 |
| November | 2631827.30 | 0.394596E+09 | 25003363.09 | 8875884.92 | 16127478.17 | 0.00 | 0.00 |
| December | 0.00 | 0.451695E+09 | 3673586.98 | 852578.86 | 2821008.12 | 0.00 | 0.00 |
| Annual Sum or Average | 0.301978E+10 | 0.256598E+10 | 0.295634E+10 | 0.145759E+10 | 0.149875E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 39647124.78 | 3673586.98 | 852578.86 | 2821008.12 | 0.00 | 0.00 |
| Maximum of Months | 0.594091E+09 | 0.451695E+09 | 0.533390E+09 | 0.300618E+09 | 0.252532E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: M CORRIDOR
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 749890.07 | 0.169114E+09 | 6367820.09 | 2420878.96 | 3946941.13 | 0.00 | 0.00 |
| February | 14072401.66 | 0.128296E+09 | 29025775.07 | 14006750.66 | 15019024.42 | 0.00 | 0.00 |
| March | 75129135.18 | 0.104543E+09 | 91787564.27 | 46364175.95 | 45423388.32 | 0.00 | 0.00 |
| April | 0.106709E+09 | 56419066.78 | 0.119048E+09 | 60328019.93 | 58719500.19 | 0.00 | 0.00 |
| May | 0.190166E+09 | 30372700.47 | 0.179095E+09 | 0.100938E+09 | 78157425.01 | 0.00 | 0.00 |
| June | 0.174272E+09 | 14757381.96 | 0.158969E+09 | 74177353.37 | 84792050.43 | 0.00 | 0.00 |
| July | 0.176261E+09 | 17131406.19 | 0.156357E+09 | 76010480.34 | 80346501.78 | 0.00 | 0.00 |
| August | 0.133298E+09 | 27021442.93 | 0.124711E+09 | 60741565.17 | 63969741.86 | 0.00 | 0.00 |
| September | 68137402.25 | 48817579.14 | 76007325.25 | 34393055.66 | 41614269.59 | 0.00 | 0.00 |
| October | 28502119.70 | 91712786.95 | 41646905.03 | 16766620.14 | 24880284.89 | 0.00 | 0.00 |
| November | 533296.39 | 0.158621E+09 | 8395323.64 | 2980236.15 | 5415087.49 | 0.00 | 0.00 |
| December | 0.00 | 0.181602E+09 | 1233472.13 | 286268.51 | 947203.62 | 0.00 | 0.00 |
| Annual Sum or Average | 0.967830E+09 | 0.102841E+10 | 0.992645E+09 | 0.489413E+09 | 0.503231E+09 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 14757381.96 | 1233472.13 | 286268.51 | 947203.62 | 0.00 | 0.00 |
| Maximum of Months | 0.190166E+09 | 0.181602E+09 | 0.179095E+09 | 0.100938E+09 | 84792050.43 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
| January | -17.6 | -17.9 | -19.9 | 1.62 | -32.2 | 4.20 | 17.57 | 0.00 |
| February | -15.4 | -16.0 | -18.9 | 1.58 | -31.2 | 17.68 | 68.90 | 0.00 |
| March | -10.3 | -11.6 | -17.1 | 2.46 | -25.4 | 47.11 | 147.56 | 0.00 |
| April | 0.73 | -2.7 | -8.8 | 3.74 | -14.2 | 75.81 | 230.75 | 0.00 |
| May | 10.60 | 5.25 | -1.5 | 3.99 | -2.1 | 92.54 | 252.99 | 0.00 |
| June | 15.96 | 10.88 | 6.41 | 3.45 | 5.66 | 116.77 | 222.76 | 0.00 |
| July | 16.86 | 12.85 | 9.90 | 2.85 | 7.58 | 107.92 | 197.90 | 0.00 |
| August | 14.24 | 10.70 | 7.59 | 2.94 | 4.33 | 81.01 | 176.65 | 0.00 |
| September | 6.72 | 4.45 | 1.76 | 2.11 | -4.1 | 51.38 | 110.92 | 0.00 |
| October | -3.1 | -4.4 | -7.1 | 2.79 | -14.3 | 26.50 | 62.95 | 0.00 |
| November | -17.6 | -18.1 | -20.3 | 0.70 | -32.8 | 8.03 | 31.72 | 0.00 |
| December | -19.3 | -19.6 | -21.9 | 1.25 | -33.6 | 1.27 | 5.23 | 0.00 |
| Annual Sum or Average | -1.4 | -3.8 | -7.4 | 2.46 | -14.3 | 52.69 | 127.40 | 0.00 |
| Minimum of Months | -19.3 | -19.6 | -21.9 | 0.70 | -33.6 | 1.27 | 5.23 | 0.00 |
| Maximum of Months | 16.86 | 12.85 | 9.90 | 3.99 | 7.58 | 116.77 | 252.99 | 0.00 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
| January | -1.1 | 21-JAN-20:00 | -2.7 | -5.6 | 0.00 | -9.0 | 0.00 | 0.00 |
| February | 2.80 | 08-FEB-15:09 | -0.7 | -6.5 | 2.68 | -7.9 | 21.67 | 32.33 |
| March | 6.70 | 20-MAR-14:09 | 2.60 | -3.5 | 1.37 | -7.5 | 138.33 | 487.67 |
| April | 15.60 | 22-APR-13:00 | 7.03 | -3.3 | 4.10 | -0.8 | 117.50 | 760.50 |
| May | 22.20 | 31-MAY-15:00 | 10.79 | -1.1 | 3.10 | 7.75 | 143.50 | 516.50 |
| June | 28.30 | 30-JUN-14:00 | 17.30 | 10.60 | 6.20 | 17.57 | 223.50 | 277.50 |
| July | 30.00 | 29-JUL-16:19 | 18.34 | 11.70 | 4.67 | 18.88 | 163.67 | 322.83 |
| August | 25.60 | 11-AUG-15:00 | 14.77 | 6.70 | 6.20 | 12.22 | 99.50 | 604.00 |
| September | 17.20 | 07-SEP-15:00 | 8.91 | 0.00 | 1.50 | 2.64 | 77.00 | 480.50 |
| October | 13.90 | 01-OCT-14:00 | 8.01 | 1.70 | 2.60 | 1.58 | 78.50 | 227.50 |
| November | -3.9 | 18-NOV-03:00 | -5.6 | -8.9 | 1.50 | -12.4 | 0.00 | 0.00 |
| December | 1.70 | 24-DEC-11:00 | -0.1 | -2.8 | 2.60 | -8.8 | 13.50 | 31.50 |
| Annual Sum or Average | ||||||||
| Minimum of Months | -3.9 | -5.6 | -8.9 | 0.00 | -12.4 | 0.00 | 0.00 | |
| Maximum of Months | 30.00 | 18.34 | 11.70 | 6.20 | 18.88 | 223.50 | 760.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
| January | -38.3 | 12-JAN-05:00 | -38.4 | -40.4 | 0.00 | -60.9 | 0.00 | 0.00 |
| February | -36.1 | 27-FEB-04:00 | -36.2 | -39.4 | 0.00 | -58.7 | 0.00 | 0.00 |
| March | -28.9 | 01-MAR-00:10 | -29.2 | -34.0 | 0.65 | -51.0 | 0.00 | 0.00 |
| April | -21.7 | 03-APR-05:00 | -22.3 | -27.2 | 2.60 | -42.7 | 0.00 | 0.00 |
| May | 0.00 | 27-MAY-03:00 | -1.1 | -2.8 | 6.20 | -7.1 | 29.00 | 14.00 |
| June | 3.30 | 02-JUN-03:00 | 2.38 | 1.10 | 1.50 | -11.2 | 45.50 | 266.00 |
| July | 7.20 | 31-JUL-03:49 | 6.67 | 6.10 | 2.18 | -7.6 | 0.00 | 0.00 |
| August | -1.7 | 31-AUG-05:00 | -2.9 | -5.0 | 2.60 | -18.6 | 25.00 | 538.50 |
| September | -5.6 | 29-SEP-06:00 | -6.1 | -7.2 | 2.60 | -21.6 | 0.00 | 0.00 |
| October | -20.6 | 22-OCT-05:00 | -20.8 | -22.2 | 2.60 | -40.2 | 0.00 | 0.00 |
| November | -30.0 | 29-NOV-09:00 | -30.2 | -33.3 | 0.00 | -51.8 | 0.00 | 0.00 |
| December | -33.9 | 15-DEC-07:00 | -34.0 | -37.8 | 0.00 | -56.5 | 0.00 | 0.00 |
| Annual Sum or Average | ||||||||
| Minimum of Months | -38.3 | -38.4 | -40.4 | 0.00 | -60.9 | 0.00 | 0.00 | |
| Maximum of Months | 7.20 | 6.67 | 6.10 | 6.20 | -7.1 | 45.50 | 538.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| SITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
| January | -2.7 | 21-JAN-20:00 | -1.1 | -5.6 | 0.00 | -9.0 | 0.00 | 0.00 |
| February | 1.24 | 09-FEB-01:00 | 2.80 | -1.1 | 8.80 | -4.1 | 0.00 | 0.00 |
| March | 2.65 | 20-MAR-13:00 | 6.70 | -3.3 | 0.00 | -7.6 | 139.00 | 515.00 |
| April | 7.03 | 22-APR-13:00 | 15.60 | -3.3 | 4.10 | -0.8 | 117.50 | 760.50 |
| May | 10.97 | 31-MAY-17:00 | 21.70 | 0.00 | 2.60 | 11.07 | 73.50 | 187.00 |
| June | 18.33 | 30-JUN-11:00 | 25.60 | 14.40 | 1.50 | 15.21 | 221.00 | 616.00 |
| July | 18.36 | 29-JUL-17:19 | 29.07 | 12.23 | 3.10 | 19.29 | 141.00 | 225.33 |
| August | 16.14 | 04-AUG-19:00 | 21.70 | 12.80 | 3.10 | 14.28 | 25.50 | 28.50 |
| September | 10.82 | 01-SEP-15:00 | 15.60 | 6.70 | 2.60 | 4.31 | 145.50 | 176.00 |
| October | 8.01 | 01-OCT-14:00 | 13.90 | 1.70 | 2.60 | 1.58 | 78.50 | 227.50 |
| November | -5.6 | 18-NOV-03:00 | -3.9 | -8.9 | 1.50 | -12.4 | 0.00 | 0.00 |
| December | -0.1 | 24-DEC-11:00 | 1.70 | -2.8 | 2.60 | -8.8 | 13.50 | 31.50 |
| Annual Sum or Average | ||||||||
| Minimum of Months | -5.6 | -3.9 | -8.9 | 0.00 | -12.4 | 0.00 | 0.00 | |
| Maximum of Months | 18.36 | 29.07 | 14.40 | 8.80 | 19.29 | 221.00 | 760.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| SITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
| January | -4.4 | 06-JAN-19:00 | -1.7 | -2.7 | 2.60 | -12.4 | 0.00 | 0.00 |
| February | -0.6 | 09-FEB-00:00 | 1.70 | 0.78 | 3.60 | -5.0 | 0.00 | 0.00 |
| March | 0.00 | 21-MAR-15:00 | 1.10 | 0.62 | 2.10 | -5.5 | 70.50 | 4.00 |
| April | 0.00 | 30-APR-07:00 | 3.30 | 1.91 | 2.60 | -8.3 | 198.00 | 170.00 |
| May | 6.10 | 16-MAY-19:00 | 8.90 | 7.49 | 5.20 | 3.69 | 16.00 | 15.00 |
| June | 15.60 | 30-JUN-17:00 | 18.90 | 16.75 | 3.60 | 12.22 | 99.50 | 223.00 |
| July | 17.80 | 03-JUL-14:00 | 19.40 | 18.27 | 1.50 | 10.11 | 223.00 | 401.50 |
| August | 15.00 | 12-AUG-22:00 | 16.10 | 15.38 | 0.00 | 12.79 | 0.00 | 0.00 |
| September | 8.90 | 04-SEP-11:00 | 10.00 | 9.41 | 2.60 | 5.33 | 238.50 | 0.50 |
| October | 5.60 | 02-OCT-11:09 | 7.30 | 6.41 | 4.95 | 0.30 | 123.67 | 16.00 |
| November | -8.3 | 18-NOV-04:00 | -5.0 | -6.1 | 1.50 | -13.4 | 0.00 | 0.00 |
| December | -2.8 | 24-DEC-09:00 | 1.10 | -0.5 | 3.10 | -6.2 | 0.00 | 0.00 |
| Annual Sum or Average | ||||||||
| Minimum of Months | -8.3 | -5.0 | -6.1 | 0.00 | -13.4 | 0.00 | 0.00 | |
| Maximum of Months | 17.80 | 19.40 | 18.27 | 5.20 | 12.79 | 238.50 | 401.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| SITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
| January | 18.00 | 13.00 | 16.00 | 0.00 | 1.10 | 0.00 |
| February | 18.00 | 13.00 | 16.00 | 0.00 | 5.89 | 0.00 |
| March | 18.00 | 13.00 | 16.00 | 0.00 | 18.25 | 0.00 |
| April | 18.00 | 13.00 | 16.00 | 0.00 | 35.02 | 0.00 |
| May | 18.00 | 13.00 | 16.00 | 0.44 | 43.39 | 0.00 |
| June | 18.00 | 13.00 | 16.00 | 2.62 | 46.67 | 0.00 |
| July | 18.00 | 13.00 | 16.00 | 4.74 | 42.09 | 0.00 |
| August | 18.00 | 13.00 | 16.00 | 6.08 | 32.30 | 0.00 |
| September | 18.00 | 13.00 | 16.00 | 6.25 | 18.21 | 0.00 |
| October | 18.00 | 13.00 | 16.00 | 5.21 | 8.04 | 0.00 |
| November | 18.00 | 13.00 | 16.00 | 3.27 | 2.12 | 0.00 |
| December | 18.00 | 13.00 | 16.00 | 0.94 | 0.28 | 0.00 |
| Annual Sum or Average | 18.00 | 13.00 | 16.00 | 2.48 | 21.19 | 0.00 |
| Minimum of Months | 18.00 | 13.00 | 16.00 | 0.00 | 0.28 | 0.00 |
| Maximum of Months | 18.00 | 13.00 | 16.00 | 6.25 | 46.67 | 0.00 |
Report: WaterHeaterReportMonthly
For: G SW APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.146467E+10 | -0.127805E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186624191.8 | 59.45 | 0.00 | 0.00 |
| February | 0.132293E+10 | -0.115437E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -168563331.5 | 59.45 | 0.00 | 0.00 |
| March | 0.146467E+10 | -0.127806E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186617536.4 | 59.45 | 0.00 | 0.00 |
| April | 0.141613E+10 | -0.123683E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -179303034.0 | 59.45 | 0.00 | 0.00 |
| May | 0.144880E+10 | -0.126857E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -180229539.1 | 59.44 | 0.00 | 0.00 |
| June | 0.135029E+10 | -0.118234E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -167950480.2 | 59.44 | 0.00 | 0.00 |
| July | 0.134912E+10 | -0.117623E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172891642.1 | 59.44 | 0.00 | 0.00 |
| August | 0.132080E+10 | -0.114736E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -173437743.1 | 59.44 | 0.00 | 0.00 |
| September | 0.128196E+10 | -0.110688E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -175078901.4 | 59.44 | 0.00 | 0.00 |
| October | 0.135251E+10 | -0.116601E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186504140.8 | 59.44 | 0.00 | 0.00 |
| November | 0.134946E+10 | -0.116888E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -180584691.6 | 59.44 | 0.00 | 0.00 |
| December | 0.144449E+10 | -0.125788E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186605424.6 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.165658E+11 | -0.144214E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.214439E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.128196E+10 | -0.127806E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -186624191.8 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.146467E+10 | -0.110688E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -167950480.2 | 59.45 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: G NW APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.146467E+10 | -0.127805E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186624191.8 | 59.45 | 0.00 | 0.00 |
| February | 0.132293E+10 | -0.115437E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -168563331.5 | 59.45 | 0.00 | 0.00 |
| March | 0.146467E+10 | -0.127806E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186617536.3 | 59.45 | 0.00 | 0.00 |
| April | 0.141736E+10 | -0.123682E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -180537183.0 | 59.45 | 0.00 | 0.00 |
| May | 0.145299E+10 | -0.126856E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -184426269.8 | 59.44 | 0.00 | 0.00 |
| June | 0.135117E+10 | -0.118234E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -168826833.9 | 59.44 | 0.00 | 0.00 |
| July | 0.134938E+10 | -0.117623E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -173150213.6 | 59.44 | 0.00 | 0.00 |
| August | 0.132212E+10 | -0.114736E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -174762476.2 | 59.44 | 0.00 | 0.00 |
| September | 0.128625E+10 | -0.110688E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -179361627.9 | 59.44 | 0.00 | 0.00 |
| October | 0.135261E+10 | -0.116601E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186607050.9 | 59.44 | 0.00 | 0.00 |
| November | 0.134946E+10 | -0.116888E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -180586105.3 | 59.44 | 0.00 | 0.00 |
| December | 0.144449E+10 | -0.125788E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186605716.3 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.165781E+11 | -0.144214E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.215667E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.128625E+10 | -0.127806E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -186624191.8 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.146467E+10 | -0.110688E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -168563331.5 | 59.45 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: G NE APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.146467E+10 | -0.127805E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186624191.8 | 59.45 | 0.00 | 0.00 |
| February | 0.132293E+10 | -0.115437E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -168563331.5 | 59.45 | 0.00 | 0.00 |
| March | 0.146467E+10 | -0.127806E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186617536.3 | 59.45 | 0.00 | 0.00 |
| April | 0.141741E+10 | -0.123682E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -180584752.1 | 59.45 | 0.00 | 0.00 |
| May | 0.145152E+10 | -0.126856E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -182960060.2 | 59.44 | 0.00 | 0.00 |
| June | 0.135061E+10 | -0.118234E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -168275692.7 | 59.44 | 0.00 | 0.00 |
| July | 0.134924E+10 | -0.117623E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -173012718.8 | 59.44 | 0.00 | 0.00 |
| August | 0.132166E+10 | -0.114737E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -174299035.2 | 59.44 | 0.00 | 0.00 |
| September | 0.128580E+10 | -0.110689E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -178911668.7 | 59.44 | 0.00 | 0.00 |
| October | 0.135261E+10 | -0.116601E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186608327.3 | 59.44 | 0.00 | 0.00 |
| November | 0.134946E+10 | -0.116888E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -180584240.2 | 59.44 | 0.00 | 0.00 |
| December | 0.144449E+10 | -0.125788E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186605398.1 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.165751E+11 | -0.144214E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.215365E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.128580E+10 | -0.127806E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -186624191.8 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.146467E+10 | -0.110689E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -168275692.7 | 59.45 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: G N1 APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.146467E+10 | -0.127805E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186624191.8 | 59.45 | 0.00 | 0.00 |
| February | 0.132293E+10 | -0.115437E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -168563331.4 | 59.45 | 0.00 | 0.00 |
| March | 0.146467E+10 | -0.127806E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186617536.3 | 59.45 | 0.00 | 0.00 |
| April | 0.141741E+10 | -0.123682E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -180586697.7 | 59.45 | 0.00 | 0.00 |
| May | 0.145245E+10 | -0.126856E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -183883199.7 | 59.44 | 0.00 | 0.00 |
| June | 0.135051E+10 | -0.118234E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -168167551.5 | 59.44 | 0.00 | 0.00 |
| July | 0.134900E+10 | -0.117623E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172776121.3 | 59.44 | 0.00 | 0.00 |
| August | 0.132134E+10 | -0.114736E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -173977255.0 | 59.44 | 0.00 | 0.00 |
| September | 0.128567E+10 | -0.110689E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -178781058.2 | 59.44 | 0.00 | 0.00 |
| October | 0.135261E+10 | -0.116601E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186602349.6 | 59.44 | 0.00 | 0.00 |
| November | 0.134946E+10 | -0.116888E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -180585662.2 | 59.44 | 0.00 | 0.00 |
| December | 0.144449E+10 | -0.125788E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186605463.5 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.165752E+11 | -0.144214E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.215377E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.128567E+10 | -0.127806E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -186624191.8 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.146467E+10 | -0.110689E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -168167551.5 | 59.45 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: G N2 APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.146467E+10 | -0.127805E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186624191.8 | 59.45 | 0.00 | 0.00 |
| February | 0.132293E+10 | -0.115437E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -168563331.4 | 59.45 | 0.00 | 0.00 |
| March | 0.146467E+10 | -0.127806E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186617536.3 | 59.45 | 0.00 | 0.00 |
| April | 0.141741E+10 | -0.123682E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -180587594.9 | 59.45 | 0.00 | 0.00 |
| May | 0.145223E+10 | -0.126856E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -183668574.2 | 59.44 | 0.00 | 0.00 |
| June | 0.135044E+10 | -0.118234E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -168098949.0 | 59.44 | 0.00 | 0.00 |
| July | 0.134899E+10 | -0.117623E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172765885.3 | 59.44 | 0.00 | 0.00 |
| August | 0.132129E+10 | -0.114736E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -173927736.3 | 59.44 | 0.00 | 0.00 |
| September | 0.128558E+10 | -0.110689E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -178696398.6 | 59.44 | 0.00 | 0.00 |
| October | 0.135261E+10 | -0.116601E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186602121.5 | 59.44 | 0.00 | 0.00 |
| November | 0.134946E+10 | -0.116888E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -180585866.3 | 59.44 | 0.00 | 0.00 |
| December | 0.144449E+10 | -0.125788E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186605054.0 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.165748E+11 | -0.144214E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.215334E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.128558E+10 | -0.127806E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -186624191.8 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.146467E+10 | -0.110689E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -168098949.0 | 59.45 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: G S1 APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.146467E+10 | -0.127805E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186624191.8 | 59.45 | 0.00 | 0.00 |
| February | 0.132293E+10 | -0.115437E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -168563331.4 | 59.45 | 0.00 | 0.00 |
| March | 0.146467E+10 | -0.127806E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186617618.9 | 59.45 | 0.00 | 0.00 |
| April | 0.141576E+10 | -0.123683E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -178933954.8 | 59.44 | 0.00 | 0.00 |
| May | 0.144706E+10 | -0.126856E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -178493831.6 | 59.44 | 0.00 | 0.00 |
| June | 0.134973E+10 | -0.118234E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -167390831.9 | 59.44 | 0.00 | 0.00 |
| July | 0.134885E+10 | -0.117623E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172622138.5 | 59.44 | 0.00 | 0.00 |
| August | 0.132027E+10 | -0.114736E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172909471.5 | 59.44 | 0.00 | 0.00 |
| September | 0.128019E+10 | -0.110688E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -173310921.4 | 59.44 | 0.00 | 0.00 |
| October | 0.135233E+10 | -0.116601E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186321895.4 | 59.44 | 0.00 | 0.00 |
| November | 0.134946E+10 | -0.116888E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -180586139.6 | 59.44 | 0.00 | 0.00 |
| December | 0.144449E+10 | -0.125788E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186605728.6 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.165604E+11 | -0.144214E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.213898E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.128019E+10 | -0.127806E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -186624191.8 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.146467E+10 | -0.110688E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -167390831.9 | 59.45 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: G S2 APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.146467E+10 | -0.127805E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186624191.8 | 59.45 | 0.00 | 0.00 |
| February | 0.132293E+10 | -0.115437E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -168563331.4 | 59.45 | 0.00 | 0.00 |
| March | 0.146467E+10 | -0.127806E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186617553.9 | 59.45 | 0.00 | 0.00 |
| April | 0.141586E+10 | -0.123683E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -179027711.3 | 59.44 | 0.00 | 0.00 |
| May | 0.144669E+10 | -0.126857E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -178121297.2 | 59.44 | 0.00 | 0.00 |
| June | 0.134964E+10 | -0.118234E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -167299288.5 | 59.44 | 0.00 | 0.00 |
| July | 0.134881E+10 | -0.117623E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172584712.7 | 59.44 | 0.00 | 0.00 |
| August | 0.132021E+10 | -0.114737E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172841314.8 | 59.44 | 0.00 | 0.00 |
| September | 0.127990E+10 | -0.110689E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -173011260.8 | 59.44 | 0.00 | 0.00 |
| October | 0.135235E+10 | -0.116601E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186340503.3 | 59.44 | 0.00 | 0.00 |
| November | 0.134946E+10 | -0.116888E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -180587686.9 | 59.44 | 0.00 | 0.00 |
| December | 0.144449E+10 | -0.125788E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186604615.1 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.165597E+11 | -0.144214E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.213822E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.127990E+10 | -0.127806E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -186624191.8 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.146467E+10 | -0.110689E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -167299288.5 | 59.45 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: M SW APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.274274E+10 | -0.255613E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186604001.7 | 59.44 | 0.00 | 0.00 |
| February | 0.247731E+10 | -0.230877E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -168545815.7 | 59.44 | 0.00 | 0.00 |
| March | 0.274252E+10 | -0.255613E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186384682.3 | 59.44 | 0.00 | 0.00 |
| April | 0.264891E+10 | -0.247368E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -175229106.4 | 59.44 | 0.00 | 0.00 |
| May | 0.271152E+10 | -0.253713E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -174381023.3 | 59.44 | 0.00 | 0.00 |
| June | 0.253172E+10 | -0.236469E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -167034572.7 | 59.44 | 0.00 | 0.00 |
| July | 0.252501E+10 | -0.235246E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172540478.7 | 59.44 | 0.00 | 0.00 |
| August | 0.246773E+10 | -0.229473E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -173000575.3 | 59.44 | 0.00 | 0.00 |
| September | 0.238678E+10 | -0.221378E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -172999150.7 | 59.44 | 0.00 | 0.00 |
| October | 0.251815E+10 | -0.233202E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186134191.3 | 59.44 | 0.00 | 0.00 |
| November | 0.251834E+10 | -0.233776E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -180583598.2 | 59.44 | 0.00 | 0.00 |
| December | 0.270237E+10 | -0.251577E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186603512.4 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.309731E+11 | -0.288430E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.213004E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.238678E+10 | -0.255613E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -186604001.7 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.274274E+10 | -0.221378E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -167034572.7 | 59.44 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: M NW APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.274274E+10 | -0.255613E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186604001.7 | 59.44 | 0.00 | 0.00 |
| February | 0.247731E+10 | -0.230877E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -168545815.7 | 59.44 | 0.00 | 0.00 |
| March | 0.274274E+10 | -0.255613E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186603437.6 | 59.44 | 0.00 | 0.00 |
| April | 0.265266E+10 | -0.247368E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -178976668.2 | 59.44 | 0.00 | 0.00 |
| May | 0.271294E+10 | -0.253714E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -175805193.6 | 59.44 | 0.00 | 0.00 |
| June | 0.253173E+10 | -0.236469E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -167042486.5 | 59.44 | 0.00 | 0.00 |
| July | 0.252501E+10 | -0.235246E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172547172.2 | 59.44 | 0.00 | 0.00 |
| August | 0.246827E+10 | -0.229473E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -173540378.1 | 59.44 | 0.00 | 0.00 |
| September | 0.239078E+10 | -0.221378E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -177007189.4 | 59.44 | 0.00 | 0.00 |
| October | 0.251861E+10 | -0.233202E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186589078.4 | 59.44 | 0.00 | 0.00 |
| November | 0.251834E+10 | -0.233776E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -180584672.1 | 59.44 | 0.00 | 0.00 |
| December | 0.270238E+10 | -0.251577E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186607521.5 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.309835E+11 | -0.288431E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.214045E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.239078E+10 | -0.255613E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -186607521.5 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.274274E+10 | -0.221378E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -167042486.5 | 59.44 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: M SE APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.274274E+10 | -0.255613E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186604001.7 | 59.44 | 0.00 | 0.00 |
| February | 0.247731E+10 | -0.230877E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -168545815.7 | 59.44 | 0.00 | 0.00 |
| March | 0.274242E+10 | -0.255613E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186285477.5 | 59.44 | 0.00 | 0.00 |
| April | 0.264877E+10 | -0.247368E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -175088482.7 | 59.44 | 0.00 | 0.00 |
| May | 0.271116E+10 | -0.253714E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -174019116.5 | 59.44 | 0.00 | 0.00 |
| June | 0.253170E+10 | -0.236468E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -167018074.8 | 59.44 | 0.00 | 0.00 |
| July | 0.252500E+10 | -0.235246E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172531169.8 | 59.44 | 0.00 | 0.00 |
| August | 0.246761E+10 | -0.229473E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172883306.7 | 59.44 | 0.00 | 0.00 |
| September | 0.238638E+10 | -0.221377E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -172612173.7 | 59.44 | 0.00 | 0.00 |
| October | 0.251797E+10 | -0.233202E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -185945952.4 | 59.44 | 0.00 | 0.00 |
| November | 0.251834E+10 | -0.233776E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -180583798.2 | 59.44 | 0.00 | 0.00 |
| December | 0.270237E+10 | -0.251577E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186603520.6 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.309718E+11 | -0.288431E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.212872E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.238638E+10 | -0.255613E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -186604001.7 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.274274E+10 | -0.221377E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -167018074.8 | 59.44 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: M NE APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.274274E+10 | -0.255613E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186604001.7 | 59.44 | 0.00 | 0.00 |
| February | 0.247731E+10 | -0.230877E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -168545815.7 | 59.44 | 0.00 | 0.00 |
| March | 0.274274E+10 | -0.255613E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186603334.0 | 59.44 | 0.00 | 0.00 |
| April | 0.265267E+10 | -0.247368E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -178994820.5 | 59.44 | 0.00 | 0.00 |
| May | 0.271216E+10 | -0.253714E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -175022617.3 | 59.44 | 0.00 | 0.00 |
| June | 0.253172E+10 | -0.236469E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -167035591.8 | 59.44 | 0.00 | 0.00 |
| July | 0.252500E+10 | -0.235246E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172544252.9 | 59.44 | 0.00 | 0.00 |
| August | 0.246802E+10 | -0.229473E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -173288085.1 | 59.44 | 0.00 | 0.00 |
| September | 0.238982E+10 | -0.221377E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -176047564.8 | 59.44 | 0.00 | 0.00 |
| October | 0.251860E+10 | -0.233202E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186580135.8 | 59.44 | 0.00 | 0.00 |
| November | 0.251834E+10 | -0.233776E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -180584646.8 | 59.44 | 0.00 | 0.00 |
| December | 0.270238E+10 | -0.251577E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186607530.2 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.309815E+11 | -0.288430E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.213846E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.238982E+10 | -0.255613E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -186607530.2 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.274274E+10 | -0.221377E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -167035591.8 | 59.44 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: M N1 APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.274274E+10 | -0.255613E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186604001.7 | 59.44 | 0.00 | 0.00 |
| February | 0.247731E+10 | -0.230877E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -168545815.6 | 59.44 | 0.00 | 0.00 |
| March | 0.274274E+10 | -0.255613E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186603180.3 | 59.44 | 0.00 | 0.00 |
| April | 0.265295E+10 | -0.247368E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -179274485.6 | 59.44 | 0.00 | 0.00 |
| May | 0.271212E+10 | -0.253714E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -174978390.7 | 59.44 | 0.00 | 0.00 |
| June | 0.253165E+10 | -0.236469E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -166959111.8 | 59.44 | 0.00 | 0.00 |
| July | 0.252496E+10 | -0.235246E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172500591.4 | 59.44 | 0.00 | 0.00 |
| August | 0.246785E+10 | -0.229473E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -173122096.7 | 59.44 | 0.00 | 0.00 |
| September | 0.238920E+10 | -0.221378E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -175418435.1 | 59.44 | 0.00 | 0.00 |
| October | 0.251854E+10 | -0.233202E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186517808.1 | 59.44 | 0.00 | 0.00 |
| November | 0.251834E+10 | -0.233776E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -180582958.2 | 59.44 | 0.00 | 0.00 |
| December | 0.270237E+10 | -0.251577E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186602978.9 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.309808E+11 | -0.288431E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.213771E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.238920E+10 | -0.255613E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -186604001.7 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.274274E+10 | -0.221378E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -166959111.8 | 59.44 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: M N2 APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.274274E+10 | -0.255613E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186604001.7 | 59.44 | 0.00 | 0.00 |
| February | 0.247731E+10 | -0.230877E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -168545815.6 | 59.44 | 0.00 | 0.00 |
| March | 0.274274E+10 | -0.255613E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186603105.7 | 59.44 | 0.00 | 0.00 |
| April | 0.265295E+10 | -0.247368E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -179270440.1 | 59.44 | 0.00 | 0.00 |
| May | 0.271200E+10 | -0.253714E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -174864133.5 | 59.44 | 0.00 | 0.00 |
| June | 0.253164E+10 | -0.236469E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -166957407.5 | 59.44 | 0.00 | 0.00 |
| July | 0.252496E+10 | -0.235246E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172501098.1 | 59.44 | 0.00 | 0.00 |
| August | 0.246784E+10 | -0.229473E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -173103866.5 | 59.44 | 0.00 | 0.00 |
| September | 0.238901E+10 | -0.221378E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -175237920.5 | 59.44 | 0.00 | 0.00 |
| October | 0.251854E+10 | -0.233202E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186515051.0 | 59.44 | 0.00 | 0.00 |
| November | 0.251834E+10 | -0.233776E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -180584628.3 | 59.44 | 0.00 | 0.00 |
| December | 0.270238E+10 | -0.251577E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186607536.3 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.309804E+11 | -0.288430E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.213740E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.238901E+10 | -0.255613E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -186607536.3 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.274274E+10 | -0.221378E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -166957407.5 | 59.44 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: M S1 APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.274274E+10 | -0.255613E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186604001.7 | 59.44 | 0.00 | 0.00 |
| February | 0.247730E+10 | -0.230877E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -168530589.4 | 59.44 | 0.00 | 0.00 |
| March | 0.274226E+10 | -0.255613E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186124389.9 | 59.44 | 0.00 | 0.00 |
| April | 0.264798E+10 | -0.247368E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -174298638.8 | 59.44 | 0.00 | 0.00 |
| May | 0.271071E+10 | -0.253714E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -173576297.5 | 59.44 | 0.00 | 0.00 |
| June | 0.253163E+10 | -0.236468E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -166950054.9 | 59.44 | 0.00 | 0.00 |
| July | 0.252496E+10 | -0.235246E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172499745.3 | 59.44 | 0.00 | 0.00 |
| August | 0.246745E+10 | -0.229473E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172715905.7 | 59.44 | 0.00 | 0.00 |
| September | 0.238523E+10 | -0.221377E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -171456706.5 | 59.44 | 0.00 | 0.00 |
| October | 0.251742E+10 | -0.233202E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -185397951.8 | 59.44 | 0.00 | 0.00 |
| November | 0.251834E+10 | -0.233776E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -180582939.9 | 59.44 | 0.00 | 0.00 |
| December | 0.270238E+10 | -0.251577E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186606316.3 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.309684E+11 | -0.288430E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.212534E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.238523E+10 | -0.255613E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -186606316.3 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.274274E+10 | -0.221377E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -166950054.9 | 59.44 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: M S2 APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.274274E+10 | -0.255613E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186604001.7 | 59.44 | 0.00 | 0.00 |
| February | 0.247730E+10 | -0.230877E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -168530163.1 | 59.44 | 0.00 | 0.00 |
| March | 0.274224E+10 | -0.255613E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186109105.5 | 59.44 | 0.00 | 0.00 |
| April | 0.264797E+10 | -0.247368E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -174289311.3 | 59.44 | 0.00 | 0.00 |
| May | 0.271068E+10 | -0.253714E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -173549603.0 | 59.44 | 0.00 | 0.00 |
| June | 0.253164E+10 | -0.236469E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -166951521.5 | 59.44 | 0.00 | 0.00 |
| July | 0.252496E+10 | -0.235246E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172497613.6 | 59.44 | 0.00 | 0.00 |
| August | 0.246744E+10 | -0.229474E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172706203.9 | 59.44 | 0.00 | 0.00 |
| September | 0.238520E+10 | -0.221377E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -171422559.2 | 59.44 | 0.00 | 0.00 |
| October | 0.251738E+10 | -0.233202E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -185359800.6 | 59.44 | 0.00 | 0.00 |
| November | 0.251834E+10 | -0.233776E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -180582291.9 | 59.44 | 0.00 | 0.00 |
| December | 0.270238E+10 | -0.251577E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186603604.9 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.309683E+11 | -0.288431E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.212521E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.238520E+10 | -0.255613E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -186604001.7 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.274274E+10 | -0.221377E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -166951521.5 | 59.44 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: T SW APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.146467E+10 | -0.127805E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186624191.8 | 59.45 | 0.00 | 0.00 |
| February | 0.132293E+10 | -0.115437E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -168563331.5 | 59.45 | 0.00 | 0.00 |
| March | 0.146439E+10 | -0.127805E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186340866.4 | 59.45 | 0.00 | 0.00 |
| April | 0.141360E+10 | -0.123683E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -176762584.4 | 59.44 | 0.00 | 0.00 |
| May | 0.144699E+10 | -0.126857E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -178427630.7 | 59.44 | 0.00 | 0.00 |
| June | 0.135074E+10 | -0.118234E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -168401247.8 | 59.44 | 0.00 | 0.00 |
| July | 0.134993E+10 | -0.117623E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -173697267.4 | 59.44 | 0.00 | 0.00 |
| August | 0.132305E+10 | -0.114737E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -175682758.6 | 59.44 | 0.00 | 0.00 |
| September | 0.128391E+10 | -0.110688E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -177028259.6 | 59.44 | 0.00 | 0.00 |
| October | 0.135234E+10 | -0.116601E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186327658.6 | 59.44 | 0.00 | 0.00 |
| November | 0.134946E+10 | -0.116887E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -180584406.0 | 59.44 | 0.00 | 0.00 |
| December | 0.144449E+10 | -0.125788E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186602041.2 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.165665E+11 | -0.144215E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.214504E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.128391E+10 | -0.127805E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -186624191.8 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.146467E+10 | -0.110688E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -168401247.8 | 59.45 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: T NW APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.146467E+10 | -0.127805E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186624191.8 | 59.45 | 0.00 | 0.00 |
| February | 0.132293E+10 | -0.115437E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -168563331.6 | 59.45 | 0.00 | 0.00 |
| March | 0.146467E+10 | -0.127806E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186617208.0 | 59.45 | 0.00 | 0.00 |
| April | 0.141611E+10 | -0.123683E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -179280090.3 | 59.44 | 0.00 | 0.00 |
| May | 0.144836E+10 | -0.126856E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -179800465.9 | 59.44 | 0.00 | 0.00 |
| June | 0.135046E+10 | -0.118234E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -168119428.1 | 59.44 | 0.00 | 0.00 |
| July | 0.134985E+10 | -0.117623E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -173621479.8 | 59.44 | 0.00 | 0.00 |
| August | 0.132408E+10 | -0.114736E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -176713591.3 | 59.44 | 0.00 | 0.00 |
| September | 0.128613E+10 | -0.110688E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -179248136.5 | 59.44 | 0.00 | 0.00 |
| October | 0.135261E+10 | -0.116601E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186603133.2 | 59.44 | 0.00 | 0.00 |
| November | 0.134946E+10 | -0.116887E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -180586747.0 | 59.44 | 0.00 | 0.00 |
| December | 0.144449E+10 | -0.125788E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186602524.3 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.165738E+11 | -0.144214E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.215238E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.128613E+10 | -0.127806E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -186624191.8 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.146467E+10 | -0.110688E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -168119428.1 | 59.45 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: T SE APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.146467E+10 | -0.127805E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186624191.8 | 59.45 | 0.00 | 0.00 |
| February | 0.132293E+10 | -0.115437E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -168563331.5 | 59.45 | 0.00 | 0.00 |
| March | 0.146432E+10 | -0.127805E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186263504.1 | 59.45 | 0.00 | 0.00 |
| April | 0.141349E+10 | -0.123683E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -176652554.4 | 59.44 | 0.00 | 0.00 |
| May | 0.144615E+10 | -0.126856E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -177586360.0 | 59.44 | 0.00 | 0.00 |
| June | 0.135044E+10 | -0.118234E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -168101192.8 | 59.44 | 0.00 | 0.00 |
| July | 0.134972E+10 | -0.117623E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -173498056.6 | 59.44 | 0.00 | 0.00 |
| August | 0.132257E+10 | -0.114736E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -175212634.7 | 59.44 | 0.00 | 0.00 |
| September | 0.128356E+10 | -0.110689E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -176676864.8 | 59.44 | 0.00 | 0.00 |
| October | 0.135226E+10 | -0.116601E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186255869.1 | 59.44 | 0.00 | 0.00 |
| November | 0.134946E+10 | -0.116887E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -180585965.1 | 59.44 | 0.00 | 0.00 |
| December | 0.144449E+10 | -0.125788E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186602271.3 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.165641E+11 | -0.144214E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.214262E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.128356E+10 | -0.127805E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -186624191.8 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.146467E+10 | -0.110689E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -168101192.8 | 59.45 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: T NE APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.146467E+10 | -0.127805E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186624191.8 | 59.45 | 0.00 | 0.00 |
| February | 0.132293E+10 | -0.115437E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -168563331.5 | 59.45 | 0.00 | 0.00 |
| March | 0.146467E+10 | -0.127806E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186617540.7 | 59.45 | 0.00 | 0.00 |
| April | 0.141617E+10 | -0.123683E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -179344927.0 | 59.44 | 0.00 | 0.00 |
| May | 0.144683E+10 | -0.126857E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -178265056.9 | 59.44 | 0.00 | 0.00 |
| June | 0.135035E+10 | -0.118234E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -168007011.2 | 59.44 | 0.00 | 0.00 |
| July | 0.134975E+10 | -0.117623E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -173519424.6 | 59.44 | 0.00 | 0.00 |
| August | 0.132351E+10 | -0.114736E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -176143000.2 | 59.44 | 0.00 | 0.00 |
| September | 0.128595E+10 | -0.110689E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -179064665.1 | 59.44 | 0.00 | 0.00 |
| October | 0.135261E+10 | -0.116601E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186607574.4 | 59.44 | 0.00 | 0.00 |
| November | 0.134946E+10 | -0.116887E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -180584887.0 | 59.44 | 0.00 | 0.00 |
| December | 0.144449E+10 | -0.125788E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186605430.1 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.165714E+11 | -0.144214E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.214995E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.128595E+10 | -0.127806E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -186624191.8 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.146467E+10 | -0.110689E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -168007011.2 | 59.45 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: T N1 APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.146467E+10 | -0.127805E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186624191.8 | 59.45 | 0.00 | 0.00 |
| February | 0.132293E+10 | -0.115437E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -168563331.5 | 59.45 | 0.00 | 0.00 |
| March | 0.146467E+10 | -0.127806E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186617536.4 | 59.45 | 0.00 | 0.00 |
| April | 0.141651E+10 | -0.123683E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -179680283.1 | 59.45 | 0.00 | 0.00 |
| May | 0.144762E+10 | -0.126857E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -179058181.6 | 59.44 | 0.00 | 0.00 |
| June | 0.134997E+10 | -0.118234E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -167632289.3 | 59.44 | 0.00 | 0.00 |
| July | 0.134937E+10 | -0.117623E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -173145712.8 | 59.44 | 0.00 | 0.00 |
| August | 0.132321E+10 | -0.114736E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -175842079.6 | 59.44 | 0.00 | 0.00 |
| September | 0.128610E+10 | -0.110689E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -179219811.7 | 59.44 | 0.00 | 0.00 |
| October | 0.135261E+10 | -0.116601E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186599821.3 | 59.44 | 0.00 | 0.00 |
| November | 0.134946E+10 | -0.116887E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -180584986.6 | 59.44 | 0.00 | 0.00 |
| December | 0.144449E+10 | -0.125788E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186602113.8 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.165716E+11 | -0.144214E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.215017E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.128610E+10 | -0.127806E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -186624191.8 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.146467E+10 | -0.110689E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -167632289.3 | 59.45 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: T N2 APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.146467E+10 | -0.127805E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186624191.8 | 59.45 | 0.00 | 0.00 |
| February | 0.132293E+10 | -0.115437E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -168563331.5 | 59.45 | 0.00 | 0.00 |
| March | 0.146467E+10 | -0.127806E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186617536.4 | 59.45 | 0.00 | 0.00 |
| April | 0.141650E+10 | -0.123683E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -179671416.8 | 59.45 | 0.00 | 0.00 |
| May | 0.144742E+10 | -0.126856E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -178858445.3 | 59.44 | 0.00 | 0.00 |
| June | 0.134997E+10 | -0.118234E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -167628491.5 | 59.44 | 0.00 | 0.00 |
| July | 0.134937E+10 | -0.117623E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -173140560.8 | 59.44 | 0.00 | 0.00 |
| August | 0.132315E+10 | -0.114736E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -175787429.3 | 59.44 | 0.00 | 0.00 |
| September | 0.128607E+10 | -0.110689E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -179184169.6 | 59.44 | 0.00 | 0.00 |
| October | 0.135261E+10 | -0.116601E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186599098.6 | 59.44 | 0.00 | 0.00 |
| November | 0.134946E+10 | -0.116888E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -180586690.1 | 59.44 | 0.00 | 0.00 |
| December | 0.144449E+10 | -0.125788E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186604919.2 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.165713E+11 | -0.144214E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.214987E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.128607E+10 | -0.127806E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -186624191.8 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.146467E+10 | -0.110689E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -167628491.5 | 59.45 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: T S1 APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.146467E+10 | -0.127805E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186624191.8 | 59.45 | 0.00 | 0.00 |
| February | 0.132293E+10 | -0.115437E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -168559961.8 | 59.45 | 0.00 | 0.00 |
| March | 0.146421E+10 | -0.127805E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186156476.4 | 59.45 | 0.00 | 0.00 |
| April | 0.141323E+10 | -0.123683E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -176396071.1 | 59.44 | 0.00 | 0.00 |
| May | 0.144607E+10 | -0.126857E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -177506258.6 | 59.44 | 0.00 | 0.00 |
| June | 0.135018E+10 | -0.118234E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -167842126.2 | 59.44 | 0.00 | 0.00 |
| July | 0.134942E+10 | -0.117623E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -173193484.0 | 59.44 | 0.00 | 0.00 |
| August | 0.132208E+10 | -0.114736E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -174719288.7 | 59.44 | 0.00 | 0.00 |
| September | 0.128309E+10 | -0.110689E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -176205899.4 | 59.44 | 0.00 | 0.00 |
| October | 0.135212E+10 | -0.116601E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186116347.9 | 59.44 | 0.00 | 0.00 |
| November | 0.134946E+10 | -0.116887E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -180584859.5 | 59.44 | 0.00 | 0.00 |
| December | 0.144449E+10 | -0.125788E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186605429.7 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.165620E+11 | -0.144214E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.214051E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.128309E+10 | -0.127805E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -186624191.8 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.146467E+10 | -0.110689E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -167842126.2 | 59.45 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: T S2 APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.146467E+10 | -0.127805E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186624191.8 | 59.45 | 0.00 | 0.00 |
| February | 0.132293E+10 | -0.115437E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -168559628.5 | 59.45 | 0.00 | 0.00 |
| March | 0.146419E+10 | -0.127805E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186138400.7 | 59.45 | 0.00 | 0.00 |
| April | 0.141323E+10 | -0.123683E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -176390393.2 | 59.44 | 0.00 | 0.00 |
| May | 0.144601E+10 | -0.126857E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -177448609.6 | 59.44 | 0.00 | 0.00 |
| June | 0.135017E+10 | -0.118234E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -167826512.4 | 59.44 | 0.00 | 0.00 |
| July | 0.134941E+10 | -0.117623E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -173183929.1 | 59.44 | 0.00 | 0.00 |
| August | 0.132205E+10 | -0.114736E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -174686323.0 | 59.44 | 0.00 | 0.00 |
| September | 0.128306E+10 | -0.110689E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -176169568.0 | 59.44 | 0.00 | 0.00 |
| October | 0.135211E+10 | -0.116601E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186105271.0 | 59.44 | 0.00 | 0.00 |
| November | 0.134946E+10 | -0.116888E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -180580895.3 | 59.44 | 0.00 | 0.00 |
| December | 0.144448E+10 | -0.125788E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186603804.2 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.165618E+11 | -0.144214E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.214032E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.128306E+10 | -0.127805E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -186624191.8 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.146467E+10 | -0.110689E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -167826512.4 | 59.45 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
| January | 108.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 205.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 329.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 421.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 545.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 583.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 562.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 467.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 356.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 265.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 135.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 71.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 4053.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 71.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 583.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT GSW HEATING COIL
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.723545E+10 | 4299.88 | 12-JAN-08:19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.582644E+10 | 4096.67 | 27-FEB-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.479483E+10 | 3610.33 | 01-MAR-08:19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.173563E+10 | 2504.50 | 03-APR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.189869E+09 | 941.28 | 28-MAY-03:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.378288E+09 | 1132.58 | 28-SEP-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.279863E+10 | 2560.49 | 31-OCT-07:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.594815E+10 | 3599.35 | 29-NOV-08:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.740784E+10 | 3994.15 | 15-DEC-08:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.363151E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.740784E+10 | 4299.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT GNW HEATING COIL
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.750315E+10 | 4342.13 | 12-JAN-08:19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.654322E+10 | 4311.93 | 27-FEB-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.594786E+10 | 3827.52 | 02-MAR-08:19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.282801E+10 | 2953.49 | 03-APR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.445302E+09 | 1078.17 | 28-MAY-03:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 35759.52 | 34.56 | 02-JUN-02:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 7682462.90 | 312.30 | 31-AUG-07:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.734620E+09 | 1341.59 | 29-SEP-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.344296E+10 | 2773.86 | 31-OCT-07:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.636708E+10 | 3685.42 | 29-NOV-08:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.751692E+10 | 3992.02 | 15-DEC-08:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.413368E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.751692E+10 | 4342.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT OFFICE HEATING COIL
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.588802E+10 | 12084.91 | 03-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.439824E+10 | 12084.91 | 01-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.293819E+10 | 12084.91 | 01-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.623771E+09 | 12084.91 | 03-APR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 42635168.94 | 12084.91 | 25-SEP-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.133738E+10 | 12084.91 | 03-OCT-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.461395E+10 | 12084.91 | 01-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.599177E+10 | 12084.91 | 01-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.258340E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.599177E+10 | 12084.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT GNE HEATING COIL
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.748892E+10 | 4344.21 | 12-JAN-08:19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.646528E+10 | 4328.15 | 27-FEB-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.571990E+10 | 3793.04 | 02-MAR-07:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.282374E+10 | 2956.65 | 03-APR-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.318205E+09 | 1071.23 | 28-MAY-02:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 1926801.57 | 197.58 | 31-AUG-05:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.648060E+09 | 1315.12 | 29-SEP-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.332977E+10 | 2762.44 | 31-OCT-07:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.637402E+10 | 3692.27 | 29-NOV-08:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.752133E+10 | 3999.90 | 15-DEC-08:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.406911E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.752133E+10 | 4344.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT GN1 HEATING COIL
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.572108E+10 | 3467.85 | 12-JAN-08:19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.495679E+10 | 3390.14 | 27-FEB-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.450000E+10 | 2977.68 | 01-MAR-08:19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.217250E+10 | 2338.70 | 03-APR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.220842E+09 | 727.24 | 28-MAY-02:70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.442367E+09 | 991.89 | 29-SEP-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.252366E+10 | 2137.47 | 31-OCT-07:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.496720E+10 | 2906.18 | 29-NOV-08:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.579925E+10 | 3156.09 | 15-DEC-08:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.313037E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.579925E+10 | 3467.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT GN2 HEATING COIL
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.572034E+10 | 3467.76 | 12-JAN-08:19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.495342E+10 | 3390.38 | 27-FEB-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.448979E+10 | 2977.23 | 01-MAR-08:19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.217321E+10 | 2340.77 | 03-APR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.209660E+09 | 722.04 | 28-MAY-02:70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.436422E+09 | 989.63 | 29-SEP-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.251735E+10 | 2136.38 | 31-OCT-07:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.496720E+10 | 2906.32 | 29-NOV-08:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.579922E+10 | 3156.23 | 15-DEC-08:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.312666E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.579922E+10 | 3467.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT GS1 HEATING COIL
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.546737E+10 | 3427.02 | 12-JAN-08:19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.425383E+10 | 3176.36 | 27-FEB-08:19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.337264E+10 | 2812.56 | 01-MAR-08:19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.111419E+10 | 1876.18 | 03-APR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 56012802.39 | 581.95 | 28-MAY-03:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.200226E+09 | 780.04 | 28-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.190518E+10 | 1921.37 | 31-OCT-07:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.455972E+10 | 2824.11 | 29-NOV-08:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.570123E+10 | 3157.25 | 15-DEC-08:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.266304E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.570123E+10 | 3427.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT GS2 HEATING COIL
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.581476E+10 | 3556.76 | 12-JAN-08:19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.454018E+10 | 3354.61 | 27-FEB-08:19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.363489E+10 | 2945.22 | 01-MAR-08:19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.123709E+10 | 2049.97 | 03-APR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 50101233.84 | 572.37 | 28-MAY-03:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.205109E+09 | 818.83 | 28-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.206696E+10 | 2059.00 | 22-OCT-07:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.487498E+10 | 2954.44 | 29-NOV-08:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.603579E+10 | 3276.39 | 15-DEC-08:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.284599E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.603579E+10 | 3556.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT MSW HEATING COIL
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.113457E+11 | 7764.76 | 29-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.809875E+10 | 6656.80 | 25-FEB-01:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.587270E+10 | 5710.49 | 01-MAR-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.142930E+10 | 3971.71 | 03-APR-03:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 13086672.66 | 708.85 | 28-MAY-03:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.481450E+09 | 2127.86 | 30-SEP-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.455915E+10 | 4690.61 | 27-OCT-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.977875E+10 | 6143.45 | 29-NOV-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.121676E+11 | 6761.73 | 15-DEC-10:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.537466E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.121676E+11 | 7764.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT MNW HEATING COIL
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.118662E+11 | 8097.04 | 29-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.952031E+10 | 6992.26 | 25-FEB-01:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.814473E+10 | 6237.83 | 02-MAR-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.285969E+10 | 4670.35 | 03-APR-03:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 29734927.46 | 1066.54 | 28-MAY-03:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 3883813.31 | 260.28 | 31-AUG-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.867410E+09 | 2413.56 | 30-SEP-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.583518E+10 | 5106.49 | 27-OCT-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.106023E+11 | 6267.34 | 29-NOV-07:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.123485E+11 | 7000.88 | 15-DEC-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.620779E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.123485E+11 | 8097.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT MSE HEATING COIL
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.113117E+11 | 7789.95 | 29-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.794072E+10 | 6599.04 | 25-FEB-01:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.543447E+10 | 5719.59 | 01-MAR-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.142710E+10 | 4115.97 | 03-APR-03:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 9073566.26 | 799.42 | 28-MAY-03:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.419197E+09 | 2085.42 | 30-SEP-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.435699E+10 | 4679.68 | 27-OCT-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.979142E+10 | 6157.43 | 29-NOV-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.121724E+11 | 6779.51 | 15-DEC-10:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.528631E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.121724E+11 | 7789.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT MNE HEATING COIL
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.118351E+11 | 8125.32 | 29-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.936149E+10 | 6942.02 | 25-FEB-01:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.768939E+10 | 6231.20 | 02-MAR-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.285485E+10 | 4864.48 | 03-APR-03:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 18090217.78 | 1200.63 | 28-MAY-03:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 145925.32 | 63.41 | 31-AUG-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.778848E+09 | 2352.13 | 30-SEP-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.560465E+10 | 5101.12 | 27-OCT-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.106190E+11 | 6283.26 | 29-NOV-07:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.123568E+11 | 6990.92 | 15-DEC-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.611184E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.123568E+11 | 8125.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT MN1 HEATING COIL
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.854485E+10 | 5693.60 | 12-JAN-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.688140E+10 | 5018.90 | 27-FEB-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.588304E+10 | 4585.85 | 02-MAR-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.203817E+10 | 3591.58 | 03-APR-03:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 232629.24 | 103.61 | 28-MAY-03:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.480864E+09 | 1653.35 | 30-SEP-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.387958E+10 | 3638.27 | 27-OCT-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.775089E+10 | 4568.99 | 29-NOV-07:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.895681E+10 | 5154.68 | 15-DEC-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.444158E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.895681E+10 | 5693.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT MN2 HEATING COIL
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.854336E+10 | 5693.47 | 12-JAN-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.687473E+10 | 5019.86 | 27-FEB-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.586081E+10 | 4583.97 | 02-MAR-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.204082E+10 | 3600.99 | 03-APR-03:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 191267.27 | 91.36 | 28-MAY-03:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.476637E+09 | 1647.55 | 30-SEP-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.386785E+10 | 3638.62 | 27-OCT-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.775105E+10 | 4569.14 | 29-NOV-07:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.895674E+10 | 5154.30 | 15-DEC-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.443722E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.895674E+10 | 5693.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT MS1 HEATING COIL
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.803741E+10 | 5582.97 | 12-JAN-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.550585E+10 | 4643.99 | 24-FEB-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.366367E+10 | 4122.40 | 01-MAR-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.729960E+09 | 2825.62 | 03-APR-03:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.176871E+09 | 1323.01 | 28-SEP-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.272804E+10 | 3255.26 | 27-OCT-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.694375E+10 | 4431.02 | 29-NOV-07:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.877584E+10 | 5009.55 | 15-DEC-10:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.365614E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.877584E+10 | 5582.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT MS2 HEATING COIL
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.803587E+10 | 5582.80 | 12-JAN-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.549861E+10 | 4642.31 | 24-FEB-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.364044E+10 | 4121.46 | 01-MAR-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.731829E+09 | 2834.66 | 03-APR-03:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.174502E+09 | 1321.57 | 28-SEP-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.271779E+10 | 3254.14 | 27-OCT-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.694381E+10 | 4431.09 | 29-NOV-07:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.877573E+10 | 5009.75 | 15-DEC-10:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.365186E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.877573E+10 | 5582.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT TSW HEATING COIL
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.846014E+10 | 5622.55 | 29-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.632317E+10 | 4887.18 | 25-FEB-01:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.498105E+10 | 4386.40 | 02-MAR-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.194379E+10 | 3437.14 | 03-APR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.262467E+09 | 1547.58 | 27-MAY-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 2387620.82 | 733.10 | 25-JUN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 466036.67 | 129.55 | 06-JUL-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 84380936.10 | 1377.40 | 30-AUG-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.968620E+09 | 1966.18 | 30-SEP-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.403287E+10 | 3673.26 | 27-OCT-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.747393E+10 | 4520.77 | 29-NOV-07:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.895845E+10 | 4920.99 | 15-DEC-10:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.434917E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 466036.67 | 129.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.895845E+10 | 5622.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT TNW HEATING COIL
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.875017E+10 | 5749.56 | 29-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.710327E+10 | 5002.97 | 25-FEB-01:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.620523E+10 | 4555.88 | 02-MAR-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.271568E+10 | 3673.71 | 03-APR-03:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.318857E+09 | 1554.35 | 27-MAY-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 3077951.09 | 690.07 | 25-JUN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.130308E+09 | 1434.97 | 30-AUG-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.138150E+10 | 2031.46 | 30-SEP-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.470985E+10 | 3806.94 | 27-OCT-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.792280E+10 | 4554.68 | 29-NOV-07:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.905757E+10 | 5072.98 | 15-DEC-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.482983E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.905757E+10 | 5749.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT TSE HEATING COIL
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.844670E+10 | 5647.44 | 29-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.624195E+10 | 4871.95 | 25-FEB-01:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.474403E+10 | 4393.02 | 02-MAR-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.191711E+10 | 3503.38 | 03-APR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.222533E+09 | 1514.13 | 27-MAY-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 1617635.93 | 604.43 | 25-JUN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 64431444.74 | 1364.59 | 30-AUG-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.892499E+09 | 1956.08 | 30-SEP-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.392197E+10 | 3678.27 | 27-OCT-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.748779E+10 | 4532.45 | 29-NOV-07:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.896653E+10 | 4936.19 | 15-DEC-10:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.429072E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.896653E+10 | 5647.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT TNE HEATING COIL
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.873979E+10 | 5776.52 | 29-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.702273E+10 | 4990.65 | 25-FEB-01:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.595524E+10 | 4565.99 | 02-MAR-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.268813E+10 | 3774.54 | 03-APR-03:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.280792E+09 | 1562.92 | 28-MAY-03:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 1811973.61 | 562.17 | 25-JUN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 98669321.20 | 1457.99 | 31-AUG-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.127009E+10 | 2024.67 | 30-SEP-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.458982E+10 | 3811.03 | 27-OCT-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.794005E+10 | 4568.92 | 29-NOV-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.906891E+10 | 5068.48 | 15-DEC-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.476560E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.906891E+10 | 5776.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT TN1 HEATING COIL
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.671967E+10 | 4280.33 | 12-JAN-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.547355E+10 | 3850.59 | 27-FEB-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.475260E+10 | 3490.92 | 02-MAR-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.206281E+10 | 2857.90 | 03-APR-03:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.161189E+09 | 1074.84 | 28-MAY-03:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 73984037.14 | 1049.32 | 31-AUG-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.925026E+09 | 1489.55 | 30-SEP-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.345918E+10 | 2862.29 | 27-OCT-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.618806E+10 | 3508.96 | 29-NOV-07:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.699628E+10 | 3934.20 | 15-DEC-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.368123E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.699628E+10 | 4280.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT TN2 HEATING COIL
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.671912E+10 | 4280.59 | 12-JAN-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.547017E+10 | 3851.36 | 27-FEB-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.474101E+10 | 3490.88 | 02-MAR-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.206507E+10 | 2864.00 | 03-APR-03:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.157646E+09 | 1079.94 | 28-MAY-03:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 72507317.10 | 1050.42 | 31-AUG-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.919209E+09 | 1487.72 | 30-SEP-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.345307E+10 | 2863.47 | 27-OCT-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.618855E+10 | 3509.57 | 29-NOV-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.699655E+10 | 3934.39 | 15-DEC-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.367829E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.699655E+10 | 4280.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT TS1 HEATING COIL
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.642815E+10 | 4237.90 | 12-JAN-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.469564E+10 | 3743.57 | 27-FEB-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.354412E+10 | 3347.77 | 01-MAR-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.128443E+10 | 2588.88 | 03-APR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.111070E+09 | 1035.87 | 27-MAY-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 37671717.84 | 874.15 | 30-AUG-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.560062E+09 | 1414.48 | 30-SEP-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.280514E+10 | 2719.97 | 27-OCT-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.573780E+10 | 3473.36 | 29-NOV-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.689495E+10 | 3840.96 | 15-DEC-10:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.320990E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.689495E+10 | 4237.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT TS2 HEATING COIL
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.642746E+10 | 4238.09 | 12-JAN-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.469196E+10 | 3744.35 | 27-FEB-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.353312E+10 | 3348.07 | 01-MAR-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.128749E+10 | 2593.24 | 03-APR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.110003E+09 | 1033.22 | 27-MAY-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 37198107.51 | 871.36 | 30-AUG-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.557054E+09 | 1412.69 | 30-SEP-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.279947E+10 | 2719.86 | 27-OCT-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.573818E+10 | 3473.31 | 29-NOV-07:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.689512E+10 | 3841.69 | 15-DEC-10:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.320771E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.689512E+10 | 4238.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT GSW COOLING COIL
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 3106947.16 | 3106947.16 | 276.82 | 22-APR-16:03 | 276.82 | 0.00 |
| May | 0.00 | 0.00 | 87085144.88 | 87085144.88 | 791.22 | 31-MAY-16:05 | 791.22 | 0.00 |
| June | 0.00 | 0.00 | 0.913223E+09 | 0.900053E+09 | 1883.88 | 21-JUN-16:30 | 1883.88 | 0.00 |
| July | 0.00 | 0.00 | 0.152377E+10 | 0.145959E+10 | 2359.81 | 29-JUL-16:10 | 2279.39 | 0.00 |
| August | 0.00 | 0.00 | 0.113189E+10 | 0.110308E+10 | 2367.12 | 11-AUG-16:06 | 2367.12 | 0.00 |
| September | 0.00 | 0.00 | 44781883.61 | 44781883.61 | 681.04 | 09-SEP-15:50 | 681.04 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.370386E+10 | 0.359770E+10 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.152377E+10 | 0.145959E+10 | 2367.12 | 2367.12 | 0.00 |
Report: CoilReportMonthly
For: SPLIT GNW COOLING COIL
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 46944.89 | 46944.89 | 30.71 | 31-MAY-17:20 | 30.71 | 0.00 |
| June | 0.00 | 0.00 | 0.513538E+09 | 0.503833E+09 | 1416.36 | 21-JUN-17:30 | 1416.36 | 0.00 |
| July | 0.00 | 0.00 | 0.955689E+09 | 0.914125E+09 | 1689.34 | 11-JUL-18:00 | 1689.34 | 0.00 |
| August | 0.00 | 0.00 | 0.440216E+09 | 0.424401E+09 | 1411.20 | 11-AUG-17:40 | 1411.20 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.190949E+10 | 0.184241E+10 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.955689E+09 | 0.914125E+09 | 1689.34 | 1689.34 | 0.00 |
Report: CoilReportMonthly
For: SPLIT OFFICE COOLING COIL
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 5678279.49 | 5678279.49 | 406.99 | 21-APR-15:40 | 406.99 | 0.00 |
| May | 0.00 | 0.00 | 0.438268E+09 | 0.438268E+09 | 6161.42 | 15-MAY-08:62 | 6161.42 | 0.00 |
| June | 0.00 | 0.00 | 0.127326E+10 | 0.125150E+10 | 6935.94 | 30-JUN-08:62 | 6174.20 | 0.00 |
| July | 0.00 | 0.00 | 0.154978E+10 | 0.148876E+10 | 7027.39 | 25-JUL-07:01 | 6221.40 | 0.00 |
| August | 0.00 | 0.00 | 0.137148E+10 | 0.132776E+10 | 6925.22 | 04-AUG-08:62 | 6077.43 | 0.00 |
| September | 0.00 | 0.00 | 0.179683E+09 | 0.179683E+09 | 1902.33 | 01-SEP-08:65 | 1902.33 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.481815E+10 | 0.469165E+10 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.154978E+10 | 0.148876E+10 | 7027.39 | 6221.40 | 0.00 |
Report: CoilReportMonthly
For: SPLIT GNE COOLING COIL
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 313456.57 | 313456.57 | 76.94 | 13-MAY-16:02 | 76.94 | 0.00 |
| June | 0.00 | 0.00 | 0.641417E+09 | 0.632082E+09 | 1226.50 | 13-JUN-18:00 | 1226.50 | 0.00 |
| July | 0.00 | 0.00 | 0.123140E+10 | 0.117613E+10 | 1587.38 | 22-JUL-11:20 | 1487.38 | 0.00 |
| August | 0.00 | 0.00 | 0.566135E+09 | 0.546843E+09 | 1228.98 | 11-AUG-17:20 | 1228.98 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.243927E+10 | 0.235536E+10 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.123140E+10 | 0.117613E+10 | 1587.38 | 1487.38 | 0.00 |
Report: CoilReportMonthly
For: SPLIT GN1 COOLING COIL
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.470156E+09 | 0.460776E+09 | 1007.73 | 30-JUN-15:10 | 961.52 | 0.00 |
| July | 0.00 | 0.00 | 0.921216E+09 | 0.873499E+09 | 1251.56 | 29-JUL-17:00 | 1200.97 | 0.00 |
| August | 0.00 | 0.00 | 0.418563E+09 | 0.400832E+09 | 967.08 | 11-AUG-18:00 | 967.08 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.180994E+10 | 0.173511E+10 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.921216E+09 | 0.873499E+09 | 1251.56 | 1200.97 | 0.00 |
Report: CoilReportMonthly
For: SPLIT GN2 COOLING COIL
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.482009E+09 | 0.472722E+09 | 1006.81 | 30-JUN-15:10 | 960.73 | 0.00 |
| July | 0.00 | 0.00 | 0.938213E+09 | 0.889537E+09 | 1256.12 | 29-JUL-17:00 | 1205.51 | 0.00 |
| August | 0.00 | 0.00 | 0.428792E+09 | 0.410782E+09 | 970.05 | 11-AUG-17:50 | 970.05 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.184901E+10 | 0.177304E+10 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.938213E+09 | 0.889537E+09 | 1256.12 | 1205.51 | 0.00 |
Report: CoilReportMonthly
For: SPLIT GS1 COOLING COIL
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 1353845.24 | 1353845.24 | 190.42 | 22-APR-16:07 | 190.42 | 0.00 |
| May | 0.00 | 0.00 | 0.115461E+09 | 0.115461E+09 | 814.12 | 13-MAY-15:10 | 814.12 | 0.00 |
| June | 0.00 | 0.00 | 0.917062E+09 | 0.903181E+09 | 1585.59 | 30-JUN-14:30 | 1533.59 | 0.00 |
| July | 0.00 | 0.00 | 0.152957E+10 | 0.145698E+10 | 2043.50 | 29-JUL-16:10 | 1972.05 | 0.00 |
| August | 0.00 | 0.00 | 0.119217E+10 | 0.115904E+10 | 1964.48 | 11-AUG-16:10 | 1964.48 | 0.00 |
| September | 0.00 | 0.00 | 90647390.44 | 90647390.44 | 727.73 | 09-SEP-15:30 | 727.73 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.384626E+10 | 0.372666E+10 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.152957E+10 | 0.145698E+10 | 2043.50 | 1972.05 | 0.00 |
Report: CoilReportMonthly
For: SPLIT GS2 COOLING COIL
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 1140158.57 | 1140158.57 | 173.22 | 22-APR-16:05 | 173.22 | 0.00 |
| May | 0.00 | 0.00 | 0.150136E+09 | 0.150136E+09 | 920.75 | 13-MAY-15:10 | 920.75 | 0.00 |
| June | 0.00 | 0.00 | 0.104138E+10 | 0.102596E+10 | 1642.53 | 30-JUN-14:30 | 1591.10 | 0.00 |
| July | 0.00 | 0.00 | 0.172769E+10 | 0.164483E+10 | 2161.20 | 29-JUL-16:10 | 2087.92 | 0.00 |
| August | 0.00 | 0.00 | 0.135274E+10 | 0.131495E+10 | 2025.85 | 11-AUG-16:04 | 2025.85 | 0.00 |
| September | 0.00 | 0.00 | 0.116009E+09 | 0.116009E+09 | 797.09 | 09-SEP-15:30 | 797.09 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.438909E+10 | 0.425303E+10 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.172769E+10 | 0.164483E+10 | 2161.20 | 2087.92 | 0.00 |
Report: CoilReportMonthly
For: SPLIT MSW COOLING COIL
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.568471E+09 | 0.568471E+09 | 4068.55 | 22-APR-16:05 | 4068.55 | 0.00 |
| May | 0.00 | 0.00 | 0.237958E+10 | 0.237958E+10 | 4926.27 | 31-MAY-16:10 | 4926.27 | 0.00 |
| June | 0.00 | 0.00 | 0.461464E+10 | 0.455217E+10 | 5846.42 | 20-JUN-16:08 | 5846.42 | 0.00 |
| July | 0.00 | 0.00 | 0.518780E+10 | 0.497480E+10 | 6516.55 | 29-JUL-15:30 | 6393.01 | 0.00 |
| August | 0.00 | 0.00 | 0.360989E+10 | 0.353028E+10 | 6195.43 | 11-AUG-16:04 | 6195.43 | 0.00 |
| September | 0.00 | 0.00 | 0.558250E+09 | 0.558250E+09 | 3499.81 | 09-SEP-15:50 | 3499.81 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.169186E+11 | 0.165635E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.518780E+10 | 0.497480E+10 | 6516.55 | 6393.01 | 0.00 |
Report: CoilReportMonthly
For: SPLIT MNW COOLING COIL
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 5802605.80 | 5802605.80 | 479.14 | 21-APR-18:00 | 479.14 | 0.00 |
| May | 0.00 | 0.00 | 0.815830E+09 | 0.815830E+09 | 3179.91 | 31-MAY-17:30 | 3179.91 | 0.00 |
| June | 0.00 | 0.00 | 0.359151E+10 | 0.353309E+10 | 4556.11 | 29-JUN-19:30 | 4442.94 | 0.00 |
| July | 0.00 | 0.00 | 0.390064E+10 | 0.372179E+10 | 4826.54 | 11-JUL-18:00 | 4826.54 | 0.00 |
| August | 0.00 | 0.00 | 0.187895E+10 | 0.182117E+10 | 3997.38 | 11-AUG-17:25 | 3997.38 | 0.00 |
| September | 0.00 | 0.00 | 944715.79 | 944715.79 | 341.49 | 02-SEP-19:20 | 341.49 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.101937E+11 | 0.989864E+10 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.390064E+10 | 0.372179E+10 | 4826.54 | 4826.54 | 0.00 |
Report: CoilReportMonthly
For: SPLIT MSE COOLING COIL
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.534768E+09 | 0.534768E+09 | 3849.53 | 22-APR-13:30 | 3849.53 | 0.00 |
| May | 0.00 | 0.00 | 0.303786E+10 | 0.303786E+10 | 4955.74 | 12-MAY-13:30 | 4955.74 | 0.00 |
| June | 0.00 | 0.00 | 0.502999E+10 | 0.496854E+10 | 5761.75 | 30-JUN-12:30 | 5360.20 | 0.00 |
| July | 0.00 | 0.00 | 0.581941E+10 | 0.558668E+10 | 6602.31 | 22-JUL-11:30 | 6305.41 | 0.00 |
| August | 0.00 | 0.00 | 0.401757E+10 | 0.393065E+10 | 5762.48 | 11-AUG-14:30 | 5762.48 | 0.00 |
| September | 0.00 | 0.00 | 0.699777E+09 | 0.699777E+09 | 3420.87 | 10-SEP-11:30 | 3420.87 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.191394E+11 | 0.187583E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.581941E+10 | 0.558668E+10 | 6602.31 | 6305.41 | 0.00 |
Report: CoilReportMonthly
For: SPLIT MNE COOLING COIL
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.136069E+10 | 0.136069E+10 | 2726.57 | 31-MAY-16:17 | 2726.57 | 0.00 |
| June | 0.00 | 0.00 | 0.400876E+10 | 0.395181E+10 | 4043.42 | 29-JUN-10:40 | 3806.83 | 0.00 |
| July | 0.00 | 0.00 | 0.453396E+10 | 0.433373E+10 | 4436.41 | 22-JUL-10:50 | 4161.41 | 0.00 |
| August | 0.00 | 0.00 | 0.223079E+10 | 0.216428E+10 | 3116.81 | 11-AUG-17:13 | 3116.81 | 0.00 |
| September | 0.00 | 0.00 | 449771.42 | 449771.42 | 166.45 | 01-SEP-16:40 | 166.45 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.121346E+11 | 0.118109E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.453396E+10 | 0.433373E+10 | 4436.41 | 4161.41 | 0.00 |
Report: CoilReportMonthly
For: SPLIT MN1 COOLING COIL
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.631129E+09 | 0.631129E+09 | 1987.62 | 31-MAY-17:20 | 1987.62 | 0.00 |
| June | 0.00 | 0.00 | 0.290128E+10 | 0.284940E+10 | 3040.53 | 29-JUN-20:00 | 2920.62 | 0.00 |
| July | 0.00 | 0.00 | 0.332374E+10 | 0.315321E+10 | 3176.30 | 29-JUL-17:10 | 3048.42 | 0.00 |
| August | 0.00 | 0.00 | 0.168995E+10 | 0.162810E+10 | 2477.95 | 11-AUG-18:00 | 2477.95 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.854610E+10 | 0.826185E+10 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.332374E+10 | 0.315321E+10 | 3176.30 | 3048.42 | 0.00 |
Report: CoilReportMonthly
For: SPLIT MN2 COOLING COIL
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.662279E+09 | 0.662279E+09 | 1986.16 | 31-MAY-17:20 | 1986.16 | 0.00 |
| June | 0.00 | 0.00 | 0.291897E+10 | 0.286718E+10 | 3025.95 | 29-JUN-20:00 | 2906.46 | 0.00 |
| July | 0.00 | 0.00 | 0.334966E+10 | 0.317811E+10 | 3182.86 | 29-JUL-17:10 | 3054.97 | 0.00 |
| August | 0.00 | 0.00 | 0.170922E+10 | 0.164695E+10 | 2470.13 | 11-AUG-18:00 | 2470.13 | 0.00 |
| September | 0.00 | 0.00 | 15632.28 | 15632.28 | 26.05 | 02-SEP-19:30 | 26.05 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.864015E+10 | 0.835454E+10 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.334966E+10 | 0.317811E+10 | 3182.86 | 3054.97 | 0.00 |
Report: CoilReportMonthly
For: SPLIT MS1 COOLING COIL
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.502393E+09 | 0.502393E+09 | 3324.84 | 22-APR-13:50 | 3324.84 | 0.00 |
| May | 0.00 | 0.00 | 0.226228E+10 | 0.226228E+10 | 3906.00 | 12-MAY-13:30 | 3906.00 | 0.00 |
| June | 0.00 | 0.00 | 0.393011E+10 | 0.387280E+10 | 4678.92 | 30-JUN-12:30 | 4290.13 | 0.00 |
| July | 0.00 | 0.00 | 0.461868E+10 | 0.441159E+10 | 5296.56 | 29-JUL-15:30 | 5192.71 | 0.00 |
| August | 0.00 | 0.00 | 0.349145E+10 | 0.340591E+10 | 4943.66 | 11-AUG-15:10 | 4943.66 | 0.00 |
| September | 0.00 | 0.00 | 0.748887E+09 | 0.748887E+09 | 3197.62 | 09-SEP-15:20 | 3197.62 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.155538E+11 | 0.152039E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.461868E+10 | 0.441159E+10 | 5296.56 | 5192.71 | 0.00 |
Report: CoilReportMonthly
For: SPLIT MS2 COOLING COIL
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.507757E+09 | 0.507757E+09 | 3345.46 | 22-APR-13:50 | 3345.46 | 0.00 |
| May | 0.00 | 0.00 | 0.230053E+10 | 0.230053E+10 | 3947.30 | 12-MAY-13:30 | 3947.30 | 0.00 |
| June | 0.00 | 0.00 | 0.394846E+10 | 0.389123E+10 | 4696.84 | 30-JUN-12:30 | 4307.99 | 0.00 |
| July | 0.00 | 0.00 | 0.464431E+10 | 0.443636E+10 | 5310.42 | 29-JUL-15:30 | 5206.65 | 0.00 |
| August | 0.00 | 0.00 | 0.351312E+10 | 0.342728E+10 | 4956.61 | 11-AUG-15:10 | 4956.61 | 0.00 |
| September | 0.00 | 0.00 | 0.766712E+09 | 0.766712E+09 | 3224.06 | 09-SEP-15:20 | 3224.06 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.156809E+11 | 0.153299E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.464431E+10 | 0.443636E+10 | 5310.42 | 5206.65 | 0.00 |
Report: CoilReportMonthly
For: SPLIT TSW COOLING COIL
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 474252.28 | 474252.28 | 125.94 | 22-MAR-15:20 | 125.94 | 0.00 |
| April | 0.00 | 0.00 | 0.399648E+09 | 0.399648E+09 | 2483.19 | 21-APR-16:30 | 2483.19 | 0.00 |
| May | 0.00 | 0.00 | 0.102786E+10 | 0.102786E+10 | 3212.85 | 31-MAY-15:40 | 3212.85 | 0.00 |
| June | 0.00 | 0.00 | 0.211994E+10 | 0.209383E+10 | 3765.70 | 20-JUN-16:05 | 3765.70 | 0.00 |
| July | 0.00 | 0.00 | 0.242527E+10 | 0.234614E+10 | 4228.66 | 29-JUL-15:40 | 4148.49 | 0.00 |
| August | 0.00 | 0.00 | 0.152804E+10 | 0.150239E+10 | 3790.29 | 10-AUG-16:10 | 3790.29 | 0.00 |
| September | 0.00 | 0.00 | 0.217503E+09 | 0.217503E+09 | 2148.99 | 09-SEP-16:07 | 2148.99 | 0.00 |
| October | 0.00 | 0.00 | 2798510.98 | 2798510.98 | 460.05 | 03-OCT-14:40 | 460.05 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.772153E+10 | 0.759063E+10 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.242527E+10 | 0.234614E+10 | 4228.66 | 4148.49 | 0.00 |
Report: CoilReportMonthly
For: SPLIT TNW COOLING COIL
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 22393702.06 | 22393702.06 | 810.85 | 21-APR-18:00 | 810.85 | 0.00 |
| May | 0.00 | 0.00 | 0.301016E+09 | 0.301016E+09 | 2034.84 | 31-MAY-16:20 | 2034.84 | 0.00 |
| June | 0.00 | 0.00 | 0.155319E+10 | 0.152809E+10 | 2844.36 | 20-JUN-17:30 | 2844.36 | 0.00 |
| July | 0.00 | 0.00 | 0.173498E+10 | 0.167041E+10 | 3038.97 | 11-JUL-17:50 | 3038.97 | 0.00 |
| August | 0.00 | 0.00 | 0.703623E+09 | 0.685912E+09 | 2370.81 | 11-AUG-17:30 | 2370.81 | 0.00 |
| September | 0.00 | 0.00 | 964923.47 | 964923.47 | 208.98 | 02-SEP-19:10 | 208.98 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.431617E+10 | 0.420879E+10 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.173498E+10 | 0.167041E+10 | 3038.97 | 3038.97 | 0.00 |
Report: CoilReportMonthly
For: SPLIT TSE COOLING COIL
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 1704068.65 | 1704068.65 | 262.60 | 22-MAR-14:40 | 262.60 | 0.00 |
| April | 0.00 | 0.00 | 0.355358E+09 | 0.355358E+09 | 2307.21 | 22-APR-13:40 | 2307.21 | 0.00 |
| May | 0.00 | 0.00 | 0.125918E+10 | 0.125918E+10 | 2995.01 | 31-MAY-14:10 | 2995.01 | 0.00 |
| June | 0.00 | 0.00 | 0.229930E+10 | 0.227359E+10 | 3637.74 | 30-JUN-12:30 | 3411.33 | 0.00 |
| July | 0.00 | 0.00 | 0.272785E+10 | 0.263787E+10 | 4103.89 | 22-JUL-11:40 | 3956.84 | 0.00 |
| August | 0.00 | 0.00 | 0.167909E+10 | 0.165026E+10 | 3521.01 | 10-AUG-14:10 | 3521.01 | 0.00 |
| September | 0.00 | 0.00 | 0.238649E+09 | 0.238649E+09 | 1826.59 | 09-SEP-15:20 | 1826.59 | 0.00 |
| October | 0.00 | 0.00 | 4816968.30 | 4816968.30 | 582.80 | 03-OCT-14:30 | 582.80 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.856595E+10 | 0.842144E+10 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.272785E+10 | 0.263787E+10 | 4103.89 | 3956.84 | 0.00 |
Report: CoilReportMonthly
For: SPLIT TNE COOLING COIL
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 401408.02 | 401408.02 | 135.97 | 22-APR-16:05 | 135.97 | 0.00 |
| May | 0.00 | 0.00 | 0.438258E+09 | 0.438258E+09 | 1640.03 | 31-MAY-11:00 | 1640.03 | 0.00 |
| June | 0.00 | 0.00 | 0.175540E+10 | 0.173091E+10 | 2493.05 | 29-JUN-11:00 | 2365.75 | 0.00 |
| July | 0.00 | 0.00 | 0.205088E+10 | 0.197441E+10 | 2688.25 | 22-JUL-10:50 | 2530.47 | 0.00 |
| August | 0.00 | 0.00 | 0.824835E+09 | 0.803639E+09 | 1696.79 | 02-AUG-16:04 | 1687.67 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.506978E+10 | 0.494762E+10 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.205088E+10 | 0.197441E+10 | 2688.25 | 2530.47 | 0.00 |
Report: CoilReportMonthly
For: SPLIT TN1 COOLING COIL
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.147075E+09 | 0.147075E+09 | 1295.64 | 31-MAY-16:17 | 1295.64 | 0.00 |
| June | 0.00 | 0.00 | 0.121912E+10 | 0.119688E+10 | 1817.64 | 30-JUN-15:10 | 1767.57 | 0.00 |
| July | 0.00 | 0.00 | 0.144369E+10 | 0.138011E+10 | 1967.90 | 29-JUL-17:10 | 1894.37 | 0.00 |
| August | 0.00 | 0.00 | 0.555736E+09 | 0.537241E+09 | 1405.41 | 02-AUG-17:20 | 1403.36 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.336563E+10 | 0.326131E+10 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.144369E+10 | 0.138011E+10 | 1967.90 | 1894.37 | 0.00 |
Report: CoilReportMonthly
For: SPLIT TN2 COOLING COIL
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.159122E+09 | 0.159122E+09 | 1293.04 | 31-MAY-16:17 | 1293.04 | 0.00 |
| June | 0.00 | 0.00 | 0.123118E+10 | 0.120900E+10 | 1822.36 | 30-JUN-15:00 | 1776.33 | 0.00 |
| July | 0.00 | 0.00 | 0.146070E+10 | 0.139646E+10 | 1965.14 | 29-JUL-16:40 | 1903.31 | 0.00 |
| August | 0.00 | 0.00 | 0.567600E+09 | 0.548846E+09 | 1399.82 | 02-AUG-17:20 | 1397.83 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.341860E+10 | 0.331343E+10 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.146070E+10 | 0.139646E+10 | 1965.14 | 1903.31 | 0.00 |
Report: CoilReportMonthly
For: SPLIT TS1 COOLING COIL
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 475832.66 | 475832.66 | 126.62 | 22-MAR-15:10 | 126.62 | 0.00 |
| April | 0.00 | 0.00 | 0.308249E+09 | 0.308249E+09 | 1929.25 | 20-APR-14:40 | 1929.25 | 0.00 |
| May | 0.00 | 0.00 | 0.879101E+09 | 0.879101E+09 | 2542.98 | 31-MAY-15:10 | 2542.98 | 0.00 |
| June | 0.00 | 0.00 | 0.177637E+10 | 0.175254E+10 | 3049.56 | 29-JUN-14:30 | 3018.13 | 0.00 |
| July | 0.00 | 0.00 | 0.213421E+10 | 0.205548E+10 | 3450.14 | 29-JUL-15:30 | 3391.92 | 0.00 |
| August | 0.00 | 0.00 | 0.139784E+10 | 0.137020E+10 | 3053.91 | 11-AUG-15:10 | 3053.91 | 0.00 |
| September | 0.00 | 0.00 | 0.206126E+09 | 0.206126E+09 | 1734.88 | 09-SEP-15:20 | 1734.88 | 0.00 |
| October | 0.00 | 0.00 | 5264220.39 | 5264220.39 | 620.66 | 03-OCT-14:30 | 620.66 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.670764E+10 | 0.657744E+10 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.213421E+10 | 0.205548E+10 | 3450.14 | 3391.92 | 0.00 |
Report: CoilReportMonthly
For: SPLIT TS2 COOLING COIL
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 741777.06 | 741777.06 | 161.03 | 22-MAR-15:10 | 161.03 | 0.00 |
| April | 0.00 | 0.00 | 0.313880E+09 | 0.313880E+09 | 1954.71 | 22-APR-14:00 | 1954.71 | 0.00 |
| May | 0.00 | 0.00 | 0.903609E+09 | 0.903609E+09 | 2551.45 | 31-MAY-15:10 | 2551.45 | 0.00 |
| June | 0.00 | 0.00 | 0.179076E+10 | 0.176696E+10 | 3064.42 | 29-JUN-14:30 | 3033.22 | 0.00 |
| July | 0.00 | 0.00 | 0.215219E+10 | 0.207283E+10 | 3456.15 | 29-JUL-15:30 | 3398.06 | 0.00 |
| August | 0.00 | 0.00 | 0.141274E+10 | 0.138489E+10 | 3062.93 | 11-AUG-15:10 | 3062.93 | 0.00 |
| September | 0.00 | 0.00 | 0.212072E+09 | 0.212072E+09 | 1749.84 | 09-SEP-15:20 | 1749.84 | 0.00 |
| October | 0.00 | 0.00 | 5702773.90 | 5702773.90 | 652.04 | 03-OCT-14:30 | 652.04 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.679169E+10 | 0.666070E+10 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.215219E+10 | 0.207283E+10 | 3456.15 | 3398.06 | 0.00 |
Report: FanReportMonthly
For: SPLIT GSW SUPPLY FAN
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.294587E+09 | 0.94 | 175.07 | 12-JAN-08:19 | 0.94 |
| February | 0.237220E+09 | 0.94 | 166.79 | 27-FEB-08:03 | 0.94 |
| March | 0.195218E+09 | 0.94 | 146.99 | 01-MAR-08:19 | 0.94 |
| April | 70925326.78 | 0.69 | 101.97 | 03-APR-07:02 | 0.94 |
| May | 14937041.94 | 0.30 | 64.53 | 31-MAY-16:05 | 1.07 |
| June | 72590072.94 | 0.65 | 147.34 | 21-JUN-16:40 | 1.04 |
| July | 0.118541E+09 | 0.83 | 182.05 | 29-JUL-16:10 | 1.02 |
| August | 88557317.57 | 0.71 | 183.15 | 11-AUG-16:06 | 1.03 |
| September | 19043394.12 | 0.34 | 55.02 | 09-SEP-15:50 | 1.07 |
| October | 0.113945E+09 | 0.89 | 104.25 | 31-OCT-07:20 | 0.94 |
| November | 0.242175E+09 | 0.94 | 146.55 | 29-NOV-08:10 | 0.94 |
| December | 0.301605E+09 | 0.94 | 162.62 | 15-DEC-08:55 | 0.94 |
| Annual Sum or Average | 0.176934E+10 | 0.76 | |||
| Minimum of Months | 14937041.94 | 0.30 | 55.02 | 0.94 | |
| Maximum of Months | 0.301605E+09 | 0.94 | 183.15 | 1.07 |
Report: FanReportMonthly
For: G SW APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.65 | 20.01 | 01-JAN-00:10 | 0.65 |
| February | 48400714.57 | 0.65 | 20.01 | 01-FEB-00:10 | 0.65 |
| March | 53586505.42 | 0.65 | 20.01 | 01-MAR-00:10 | 0.65 |
| April | 51857908.47 | 0.64 | 20.01 | 01-APR-00:10 | 0.65 |
| May | 53586505.42 | 0.64 | 20.01 | 01-MAY-00:10 | 0.64 |
| June | 51857908.47 | 0.64 | 20.01 | 01-JUN-00:10 | 0.64 |
| July | 53586505.42 | 0.64 | 20.01 | 01-JUL-00:10 | 0.64 |
| August | 53586505.42 | 0.64 | 20.01 | 01-AUG-00:10 | 0.64 |
| September | 51857908.47 | 0.64 | 20.01 | 01-SEP-00:10 | 0.64 |
| October | 53586505.42 | 0.64 | 20.01 | 01-OCT-00:10 | 0.64 |
| November | 51857908.47 | 0.65 | 20.01 | 01-NOV-00:10 | 0.65 |
| December | 53586505.42 | 0.65 | 20.01 | 01-DEC-00:10 | 0.65 |
| Annual Sum or Average | 0.630938E+09 | 0.64 | |||
| Minimum of Months | 48400714.57 | 0.64 | 20.01 | 0.64 | |
| Maximum of Months | 53586505.42 | 0.65 | 20.01 | 0.65 |
Report: FanReportMonthly
For: G SW APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.65 | 20.01 | 01-JAN-00:10 | 0.65 |
| February | 48400714.57 | 0.65 | 20.01 | 01-FEB-00:10 | 0.65 |
| March | 53586505.42 | 0.65 | 20.01 | 01-MAR-00:10 | 0.65 |
| April | 51857908.47 | 0.64 | 20.01 | 01-APR-00:10 | 0.65 |
| May | 53586505.42 | 0.64 | 20.01 | 01-MAY-00:10 | 0.64 |
| June | 51857908.47 | 0.64 | 20.01 | 01-JUN-00:10 | 0.64 |
| July | 53586505.42 | 0.64 | 20.01 | 01-JUL-00:10 | 0.64 |
| August | 53586505.42 | 0.64 | 20.01 | 01-AUG-00:10 | 0.64 |
| September | 51857908.47 | 0.64 | 20.01 | 01-SEP-00:10 | 0.64 |
| October | 53586505.42 | 0.64 | 20.01 | 01-OCT-00:10 | 0.64 |
| November | 51857908.47 | 0.65 | 20.01 | 01-NOV-00:10 | 0.65 |
| December | 53586505.42 | 0.65 | 20.01 | 01-DEC-00:10 | 0.65 |
| Annual Sum or Average | 0.630938E+09 | 0.64 | |||
| Minimum of Months | 48400714.57 | 0.64 | 20.01 | 0.64 | |
| Maximum of Months | 53586505.42 | 0.65 | 20.01 | 0.65 |
Report: FanReportMonthly
For: SPLIT GNW SUPPLY FAN
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.293669E+09 | 0.94 | 169.95 | 12-JAN-08:19 | 0.94 |
| February | 0.256097E+09 | 0.94 | 168.77 | 27-FEB-08:03 | 0.94 |
| March | 0.232796E+09 | 0.94 | 149.81 | 02-MAR-08:19 | 0.94 |
| April | 0.110686E+09 | 0.90 | 115.60 | 03-APR-07:02 | 0.94 |
| May | 17432759.57 | 0.43 | 42.20 | 28-MAY-03:00 | 0.94 |
| June | 40802636.09 | 0.48 | 111.11 | 21-JUN-17:30 | 1.04 |
| July | 74661373.27 | 0.74 | 129.89 | 11-JUL-18:00 | 1.03 |
| August | 34895335.67 | 0.46 | 110.71 | 11-AUG-17:40 | 1.04 |
| September | 28752559.50 | 0.55 | 52.51 | 29-SEP-07:00 | 0.94 |
| October | 0.134755E+09 | 0.93 | 108.57 | 31-OCT-07:20 | 0.94 |
| November | 0.249203E+09 | 0.94 | 144.25 | 29-NOV-08:10 | 0.94 |
| December | 0.294207E+09 | 0.94 | 156.25 | 15-DEC-08:55 | 0.94 |
| Annual Sum or Average | 0.176796E+10 | 0.76 | |||
| Minimum of Months | 17432759.57 | 0.43 | 42.20 | 0.94 | |
| Maximum of Months | 0.294207E+09 | 0.94 | 169.95 | 1.04 |
Report: FanReportMonthly
For: G NW APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.65 | 20.01 | 01-JAN-00:10 | 0.65 |
| February | 48400714.57 | 0.65 | 20.01 | 01-FEB-00:10 | 0.65 |
| March | 53586505.42 | 0.65 | 20.01 | 01-MAR-00:10 | 0.65 |
| April | 51857908.47 | 0.64 | 20.01 | 01-APR-00:10 | 0.65 |
| May | 53586505.42 | 0.64 | 20.01 | 01-MAY-00:10 | 0.64 |
| June | 51857908.47 | 0.64 | 20.01 | 01-JUN-00:10 | 0.64 |
| July | 53586505.42 | 0.64 | 20.01 | 01-JUL-00:10 | 0.64 |
| August | 53586505.42 | 0.64 | 20.01 | 01-AUG-00:10 | 0.64 |
| September | 51857908.47 | 0.64 | 20.01 | 01-SEP-00:10 | 0.64 |
| October | 53586505.42 | 0.64 | 20.01 | 01-OCT-00:10 | 0.64 |
| November | 51857908.47 | 0.65 | 20.01 | 01-NOV-00:10 | 0.65 |
| December | 53586505.42 | 0.65 | 20.01 | 01-DEC-00:10 | 0.65 |
| Annual Sum or Average | 0.630938E+09 | 0.64 | |||
| Minimum of Months | 48400714.57 | 0.64 | 20.01 | 0.64 | |
| Maximum of Months | 53586505.42 | 0.65 | 20.01 | 0.65 |
Report: FanReportMonthly
For: G NW APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.65 | 20.01 | 01-JAN-00:10 | 0.65 |
| February | 48400714.57 | 0.65 | 20.01 | 01-FEB-00:10 | 0.65 |
| March | 53586505.42 | 0.65 | 20.01 | 01-MAR-00:10 | 0.65 |
| April | 51857908.47 | 0.64 | 20.01 | 01-APR-00:10 | 0.65 |
| May | 53586505.42 | 0.64 | 20.01 | 01-MAY-00:10 | 0.64 |
| June | 51857908.47 | 0.64 | 20.01 | 01-JUN-00:10 | 0.64 |
| July | 53586505.42 | 0.64 | 20.01 | 01-JUL-00:10 | 0.64 |
| August | 53586505.42 | 0.64 | 20.01 | 01-AUG-00:10 | 0.64 |
| September | 51857908.47 | 0.64 | 20.01 | 01-SEP-00:10 | 0.64 |
| October | 53586505.42 | 0.64 | 20.01 | 01-OCT-00:10 | 0.64 |
| November | 51857908.47 | 0.65 | 20.01 | 01-NOV-00:10 | 0.65 |
| December | 53586505.42 | 0.65 | 20.01 | 01-DEC-00:10 | 0.65 |
| Annual Sum or Average | 0.630938E+09 | 0.64 | |||
| Minimum of Months | 48400714.57 | 0.64 | 20.01 | 0.64 | |
| Maximum of Months | 53586505.42 | 0.65 | 20.01 | 0.65 |
Report: FanReportMonthly
For: SPLIT OFFICE SUPPLY FAN
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.122932E+10 | 0.94 | 458.98 | 01-JAN-00:10 | 0.94 |
| February | 0.111035E+10 | 0.94 | 458.98 | 01-FEB-00:10 | 0.94 |
| March | 0.122932E+10 | 0.94 | 458.98 | 01-MAR-00:10 | 0.94 |
| April | 0.118966E+10 | 0.94 | 458.98 | 01-APR-00:20 | 0.94 |
| May | 0.122932E+10 | 0.93 | 458.98 | 01-MAY-00:10 | 0.94 |
| June | 0.118966E+10 | 0.93 | 458.98 | 01-JUN-00:10 | 0.93 |
| July | 0.122932E+10 | 0.93 | 458.98 | 01-JUL-00:10 | 0.93 |
| August | 0.122932E+10 | 0.93 | 458.98 | 01-AUG-00:10 | 0.93 |
| September | 0.118966E+10 | 0.93 | 458.98 | 01-SEP-00:10 | 0.93 |
| October | 0.122932E+10 | 0.94 | 458.98 | 01-OCT-00:10 | 0.94 |
| November | 0.118966E+10 | 0.94 | 458.98 | 01-NOV-00:10 | 0.94 |
| December | 0.122932E+10 | 0.94 | 458.98 | 01-DEC-00:10 | 0.94 |
| Annual Sum or Average | 0.144742E+11 | 0.93 | |||
| Minimum of Months | 0.111035E+10 | 0.93 | 458.98 | 0.93 | |
| Maximum of Months | 0.122932E+10 | 0.94 | 458.98 | 0.94 |
Report: FanReportMonthly
For: SPLIT GNE SUPPLY FAN
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.284829E+09 | 0.94 | 165.23 | 12-JAN-08:19 | 0.94 |
| February | 0.245896E+09 | 0.94 | 164.61 | 27-FEB-08:03 | 0.94 |
| March | 0.217547E+09 | 0.94 | 144.26 | 02-MAR-07:55 | 0.94 |
| April | 0.107397E+09 | 0.92 | 112.45 | 03-APR-07:00 | 0.94 |
| May | 12128635.59 | 0.30 | 40.74 | 28-MAY-02:50 | 0.94 |
| June | 50988754.75 | 0.60 | 96.31 | 13-JUN-18:00 | 1.04 |
| July | 95507794.68 | 0.80 | 125.35 | 21-JUL-16:06 | 1.03 |
| August | 44472694.52 | 0.54 | 96.50 | 11-AUG-17:13 | 1.04 |
| September | 24647928.33 | 0.48 | 50.02 | 29-SEP-07:00 | 0.94 |
| October | 0.126642E+09 | 0.93 | 105.07 | 31-OCT-07:20 | 0.94 |
| November | 0.242426E+09 | 0.94 | 140.43 | 29-NOV-08:10 | 0.94 |
| December | 0.286062E+09 | 0.94 | 152.13 | 15-DEC-08:55 | 0.94 |
| Annual Sum or Average | 0.173855E+10 | 0.77 | |||
| Minimum of Months | 12128635.59 | 0.30 | 40.74 | 0.94 | |
| Maximum of Months | 0.286062E+09 | 0.94 | 165.23 | 1.04 |
Report: FanReportMonthly
For: G NE APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.65 | 20.01 | 01-JAN-00:10 | 0.65 |
| February | 48400714.57 | 0.65 | 20.01 | 01-FEB-00:10 | 0.65 |
| March | 53586505.42 | 0.65 | 20.01 | 01-MAR-00:10 | 0.65 |
| April | 51857908.47 | 0.64 | 20.01 | 01-APR-00:10 | 0.65 |
| May | 53586505.42 | 0.64 | 20.01 | 01-MAY-00:10 | 0.64 |
| June | 51857908.47 | 0.64 | 20.01 | 01-JUN-00:10 | 0.64 |
| July | 53586505.42 | 0.64 | 20.01 | 01-JUL-00:10 | 0.64 |
| August | 53586505.42 | 0.64 | 20.01 | 01-AUG-00:10 | 0.64 |
| September | 51857908.47 | 0.64 | 20.01 | 01-SEP-00:10 | 0.64 |
| October | 53586505.42 | 0.64 | 20.01 | 01-OCT-00:10 | 0.64 |
| November | 51857908.47 | 0.65 | 20.01 | 01-NOV-00:10 | 0.65 |
| December | 53586505.42 | 0.65 | 20.01 | 01-DEC-00:10 | 0.65 |
| Annual Sum or Average | 0.630938E+09 | 0.64 | |||
| Minimum of Months | 48400714.57 | 0.64 | 20.01 | 0.64 | |
| Maximum of Months | 53586505.42 | 0.65 | 20.01 | 0.65 |
Report: FanReportMonthly
For: G NE APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.65 | 20.01 | 01-JAN-00:10 | 0.65 |
| February | 48400714.57 | 0.65 | 20.01 | 01-FEB-00:10 | 0.65 |
| March | 53586505.42 | 0.65 | 20.01 | 01-MAR-00:10 | 0.65 |
| April | 51857908.47 | 0.64 | 20.01 | 01-APR-00:10 | 0.65 |
| May | 53586505.42 | 0.64 | 20.01 | 01-MAY-00:10 | 0.64 |
| June | 51857908.47 | 0.64 | 20.01 | 01-JUN-00:10 | 0.64 |
| July | 53586505.42 | 0.64 | 20.01 | 01-JUL-00:10 | 0.64 |
| August | 53586505.42 | 0.64 | 20.01 | 01-AUG-00:10 | 0.64 |
| September | 51857908.47 | 0.64 | 20.01 | 01-SEP-00:10 | 0.64 |
| October | 53586505.42 | 0.64 | 20.01 | 01-OCT-00:10 | 0.64 |
| November | 51857908.47 | 0.65 | 20.01 | 01-NOV-00:10 | 0.65 |
| December | 53586505.42 | 0.65 | 20.01 | 01-DEC-00:10 | 0.65 |
| Annual Sum or Average | 0.630938E+09 | 0.64 | |||
| Minimum of Months | 48400714.57 | 0.64 | 20.01 | 0.64 | |
| Maximum of Months | 53586505.42 | 0.65 | 20.01 | 0.65 |
Report: FanReportMonthly
For: SPLIT GN1 SUPPLY FAN
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.211674E+09 | 0.94 | 128.31 | 12-JAN-08:19 | 0.94 |
| February | 0.183396E+09 | 0.94 | 125.43 | 27-FEB-08:03 | 0.94 |
| March | 0.166495E+09 | 0.94 | 110.17 | 01-MAR-08:19 | 0.94 |
| April | 80380363.89 | 0.91 | 86.53 | 03-APR-07:02 | 0.94 |
| May | 8170934.15 | 0.29 | 26.91 | 28-MAY-02:70 | 0.94 |
| June | 37365164.82 | 0.59 | 78.10 | 30-JUN-15:10 | 1.04 |
| July | 71762621.64 | 0.83 | 97.46 | 29-JUL-17:00 | 1.03 |
| August | 32853093.13 | 0.53 | 76.26 | 11-AUG-18:00 | 1.05 |
| September | 16367095.42 | 0.41 | 36.70 | 29-SEP-07:00 | 0.94 |
| October | 93372935.24 | 0.93 | 79.08 | 31-OCT-07:20 | 0.94 |
| November | 0.183781E+09 | 0.94 | 107.53 | 29-NOV-08:20 | 0.94 |
| December | 0.214566E+09 | 0.94 | 116.77 | 15-DEC-08:30 | 0.94 |
| Annual Sum or Average | 0.130018E+10 | 0.77 | |||
| Minimum of Months | 8170934.15 | 0.29 | 26.91 | 0.94 | |
| Maximum of Months | 0.214566E+09 | 0.94 | 128.31 | 1.05 |
Report: FanReportMonthly
For: G N1 APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.65 | 20.01 | 01-JAN-00:10 | 0.65 |
| February | 48400714.57 | 0.65 | 20.01 | 01-FEB-00:10 | 0.65 |
| March | 53586505.42 | 0.65 | 20.01 | 01-MAR-00:10 | 0.65 |
| April | 51857908.47 | 0.64 | 20.01 | 01-APR-00:10 | 0.65 |
| May | 53586505.42 | 0.64 | 20.01 | 01-MAY-00:10 | 0.64 |
| June | 51857908.47 | 0.64 | 20.01 | 01-JUN-00:10 | 0.64 |
| July | 53586505.42 | 0.64 | 20.01 | 01-JUL-00:10 | 0.64 |
| August | 53586505.42 | 0.64 | 20.01 | 01-AUG-00:10 | 0.64 |
| September | 51857908.47 | 0.64 | 20.01 | 01-SEP-00:10 | 0.64 |
| October | 53586505.42 | 0.64 | 20.01 | 01-OCT-00:10 | 0.64 |
| November | 51857908.47 | 0.65 | 20.01 | 01-NOV-00:10 | 0.65 |
| December | 53586505.42 | 0.65 | 20.01 | 01-DEC-00:10 | 0.65 |
| Annual Sum or Average | 0.630938E+09 | 0.64 | |||
| Minimum of Months | 48400714.57 | 0.64 | 20.01 | 0.64 | |
| Maximum of Months | 53586505.42 | 0.65 | 20.01 | 0.65 |
Report: FanReportMonthly
For: G N1 APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.65 | 20.01 | 01-JAN-00:10 | 0.65 |
| February | 48400714.57 | 0.65 | 20.01 | 01-FEB-00:10 | 0.65 |
| March | 53586505.42 | 0.65 | 20.01 | 01-MAR-00:10 | 0.65 |
| April | 51857908.47 | 0.64 | 20.01 | 01-APR-00:10 | 0.65 |
| May | 53586505.42 | 0.64 | 20.01 | 01-MAY-00:10 | 0.64 |
| June | 51857908.47 | 0.64 | 20.01 | 01-JUN-00:10 | 0.64 |
| July | 53586505.42 | 0.64 | 20.01 | 01-JUL-00:10 | 0.64 |
| August | 53586505.42 | 0.64 | 20.01 | 01-AUG-00:10 | 0.64 |
| September | 51857908.47 | 0.64 | 20.01 | 01-SEP-00:10 | 0.64 |
| October | 53586505.42 | 0.64 | 20.01 | 01-OCT-00:10 | 0.64 |
| November | 51857908.47 | 0.65 | 20.01 | 01-NOV-00:10 | 0.65 |
| December | 53586505.42 | 0.65 | 20.01 | 01-DEC-00:10 | 0.65 |
| Annual Sum or Average | 0.630938E+09 | 0.64 | |||
| Minimum of Months | 48400714.57 | 0.64 | 20.01 | 0.64 | |
| Maximum of Months | 53586505.42 | 0.65 | 20.01 | 0.65 |
Report: FanReportMonthly
For: SPLIT GN2 SUPPLY FAN
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.211534E+09 | 0.94 | 128.24 | 12-JAN-08:19 | 0.94 |
| February | 0.183174E+09 | 0.94 | 125.37 | 27-FEB-08:03 | 0.94 |
| March | 0.166029E+09 | 0.94 | 110.10 | 01-MAR-08:19 | 0.94 |
| April | 80363576.82 | 0.91 | 86.56 | 03-APR-07:02 | 0.94 |
| May | 7753060.60 | 0.27 | 26.70 | 28-MAY-02:70 | 0.94 |
| June | 38320896.67 | 0.60 | 78.04 | 30-JUN-15:00 | 1.04 |
| July | 73062375.72 | 0.84 | 97.79 | 29-JUL-17:00 | 1.03 |
| August | 33655148.95 | 0.55 | 76.52 | 11-AUG-17:50 | 1.05 |
| September | 16138522.74 | 0.41 | 36.60 | 29-SEP-07:00 | 0.94 |
| October | 93089643.60 | 0.93 | 79.00 | 31-OCT-07:20 | 0.94 |
| November | 0.183683E+09 | 0.94 | 107.47 | 29-NOV-08:20 | 0.94 |
| December | 0.214451E+09 | 0.94 | 116.71 | 15-DEC-08:30 | 0.94 |
| Annual Sum or Average | 0.130125E+10 | 0.77 | |||
| Minimum of Months | 7753060.60 | 0.27 | 26.70 | 0.94 | |
| Maximum of Months | 0.214451E+09 | 0.94 | 128.24 | 1.05 |
Report: FanReportMonthly
For: G N2 APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.65 | 20.01 | 01-JAN-00:10 | 0.65 |
| February | 48400714.57 | 0.65 | 20.01 | 01-FEB-00:10 | 0.65 |
| March | 53586505.42 | 0.65 | 20.01 | 01-MAR-00:10 | 0.65 |
| April | 51857908.47 | 0.64 | 20.01 | 01-APR-00:10 | 0.65 |
| May | 53586505.42 | 0.64 | 20.01 | 01-MAY-00:10 | 0.64 |
| June | 51857908.47 | 0.64 | 20.01 | 01-JUN-00:10 | 0.64 |
| July | 53586505.42 | 0.64 | 20.01 | 01-JUL-00:10 | 0.64 |
| August | 53586505.42 | 0.64 | 20.01 | 01-AUG-00:10 | 0.64 |
| September | 51857908.47 | 0.64 | 20.01 | 01-SEP-00:10 | 0.64 |
| October | 53586505.42 | 0.64 | 20.01 | 01-OCT-00:10 | 0.64 |
| November | 51857908.47 | 0.65 | 20.01 | 01-NOV-00:10 | 0.65 |
| December | 53586505.42 | 0.65 | 20.01 | 01-DEC-00:10 | 0.65 |
| Annual Sum or Average | 0.630938E+09 | 0.64 | |||
| Minimum of Months | 48400714.57 | 0.64 | 20.01 | 0.64 | |
| Maximum of Months | 53586505.42 | 0.65 | 20.01 | 0.65 |
Report: FanReportMonthly
For: G N2 APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.65 | 20.01 | 01-JAN-00:10 | 0.65 |
| February | 48400714.57 | 0.65 | 20.01 | 01-FEB-00:10 | 0.65 |
| March | 53586505.42 | 0.65 | 20.01 | 01-MAR-00:10 | 0.65 |
| April | 51857908.47 | 0.64 | 20.01 | 01-APR-00:10 | 0.65 |
| May | 53586505.42 | 0.64 | 20.01 | 01-MAY-00:10 | 0.64 |
| June | 51857908.47 | 0.64 | 20.01 | 01-JUN-00:10 | 0.64 |
| July | 53586505.42 | 0.64 | 20.01 | 01-JUL-00:10 | 0.64 |
| August | 53586505.42 | 0.64 | 20.01 | 01-AUG-00:10 | 0.64 |
| September | 51857908.47 | 0.64 | 20.01 | 01-SEP-00:10 | 0.64 |
| October | 53586505.42 | 0.64 | 20.01 | 01-OCT-00:10 | 0.64 |
| November | 51857908.47 | 0.65 | 20.01 | 01-NOV-00:10 | 0.65 |
| December | 53586505.42 | 0.65 | 20.01 | 01-DEC-00:10 | 0.65 |
| Annual Sum or Average | 0.630938E+09 | 0.64 | |||
| Minimum of Months | 48400714.57 | 0.64 | 20.01 | 0.64 | |
| Maximum of Months | 53586505.42 | 0.65 | 20.01 | 0.65 |
Report: FanReportMonthly
For: SPLIT GS1 SUPPLY FAN
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.214969E+09 | 0.94 | 134.75 | 12-JAN-08:19 | 0.94 |
| February | 0.167254E+09 | 0.94 | 124.89 | 27-FEB-08:19 | 0.94 |
| March | 0.132607E+09 | 0.94 | 110.59 | 01-MAR-08:19 | 0.94 |
| April | 43921398.29 | 0.60 | 73.77 | 03-APR-07:02 | 0.94 |
| May | 11730135.05 | 0.26 | 66.59 | 13-MAY-15:10 | 1.07 |
| June | 72865714.79 | 0.78 | 122.41 | 30-JUN-14:30 | 1.04 |
| July | 0.118676E+09 | 0.94 | 157.28 | 29-JUL-16:10 | 1.02 |
| August | 93200985.05 | 0.86 | 152.08 | 11-AUG-16:10 | 1.03 |
| September | 15240070.42 | 0.36 | 58.47 | 09-SEP-15:30 | 1.07 |
| October | 74908692.06 | 0.81 | 75.55 | 31-OCT-07:20 | 0.94 |
| November | 0.179281E+09 | 0.94 | 111.04 | 29-NOV-08:12 | 0.94 |
| December | 0.224164E+09 | 0.94 | 124.14 | 15-DEC-08:30 | 0.94 |
| Annual Sum or Average | 0.134882E+10 | 0.78 | |||
| Minimum of Months | 11730135.05 | 0.26 | 58.47 | 0.94 | |
| Maximum of Months | 0.224164E+09 | 0.94 | 157.28 | 1.07 |
Report: FanReportMonthly
For: G S1 APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.65 | 20.01 | 01-JAN-00:10 | 0.65 |
| February | 48400714.57 | 0.65 | 20.01 | 01-FEB-00:10 | 0.65 |
| March | 53586505.42 | 0.65 | 20.01 | 01-MAR-00:10 | 0.65 |
| April | 51857908.47 | 0.64 | 20.01 | 01-APR-00:10 | 0.65 |
| May | 53586505.42 | 0.64 | 20.01 | 01-MAY-00:10 | 0.64 |
| June | 51857908.47 | 0.64 | 20.01 | 01-JUN-00:10 | 0.64 |
| July | 53586505.42 | 0.64 | 20.01 | 01-JUL-00:10 | 0.64 |
| August | 53586505.42 | 0.64 | 20.01 | 01-AUG-00:10 | 0.64 |
| September | 51857908.47 | 0.64 | 20.01 | 01-SEP-00:10 | 0.64 |
| October | 53586505.42 | 0.64 | 20.01 | 01-OCT-00:10 | 0.64 |
| November | 51857908.47 | 0.65 | 20.01 | 01-NOV-00:10 | 0.65 |
| December | 53586505.42 | 0.65 | 20.01 | 01-DEC-00:10 | 0.65 |
| Annual Sum or Average | 0.630938E+09 | 0.64 | |||
| Minimum of Months | 48400714.57 | 0.64 | 20.01 | 0.64 | |
| Maximum of Months | 53586505.42 | 0.65 | 20.01 | 0.65 |
Report: FanReportMonthly
For: G S1 APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.65 | 20.01 | 01-JAN-00:10 | 0.65 |
| February | 48400714.57 | 0.65 | 20.01 | 01-FEB-00:10 | 0.65 |
| March | 53586505.42 | 0.65 | 20.01 | 01-MAR-00:10 | 0.65 |
| April | 51857908.47 | 0.64 | 20.01 | 01-APR-00:10 | 0.65 |
| May | 53586505.42 | 0.64 | 20.01 | 01-MAY-00:10 | 0.64 |
| June | 51857908.47 | 0.64 | 20.01 | 01-JUN-00:10 | 0.64 |
| July | 53586505.42 | 0.64 | 20.01 | 01-JUL-00:10 | 0.64 |
| August | 53586505.42 | 0.64 | 20.01 | 01-AUG-00:10 | 0.64 |
| September | 51857908.47 | 0.64 | 20.01 | 01-SEP-00:10 | 0.64 |
| October | 53586505.42 | 0.64 | 20.01 | 01-OCT-00:10 | 0.64 |
| November | 51857908.47 | 0.65 | 20.01 | 01-NOV-00:10 | 0.65 |
| December | 53586505.42 | 0.65 | 20.01 | 01-DEC-00:10 | 0.65 |
| Annual Sum or Average | 0.630938E+09 | 0.64 | |||
| Minimum of Months | 48400714.57 | 0.64 | 20.01 | 0.64 | |
| Maximum of Months | 53586505.42 | 0.65 | 20.01 | 0.65 |
Report: FanReportMonthly
For: SPLIT GS2 SUPPLY FAN
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.228898E+09 | 0.94 | 140.01 | 12-JAN-08:19 | 0.94 |
| February | 0.178725E+09 | 0.94 | 132.05 | 27-FEB-08:19 | 0.94 |
| March | 0.143088E+09 | 0.94 | 115.94 | 01-MAR-08:19 | 0.94 |
| April | 48793714.34 | 0.62 | 80.70 | 03-APR-07:02 | 0.94 |
| May | 14343087.36 | 0.29 | 75.06 | 13-MAY-15:10 | 1.07 |
| June | 82658803.42 | 0.83 | 126.66 | 30-JUN-14:30 | 1.03 |
| July | 0.133789E+09 | 0.97 | 165.83 | 29-JUL-16:10 | 1.02 |
| August | 0.105637E+09 | 0.91 | 156.62 | 11-AUG-16:04 | 1.02 |
| September | 17496607.98 | 0.39 | 63.91 | 09-SEP-15:30 | 1.07 |
| October | 81366034.15 | 0.82 | 81.05 | 22-OCT-07:20 | 0.94 |
| November | 0.191904E+09 | 0.94 | 116.30 | 29-NOV-08:20 | 0.94 |
| December | 0.237599E+09 | 0.94 | 128.98 | 15-DEC-08:30 | 0.94 |
| Annual Sum or Average | 0.146430E+10 | 0.79 | |||
| Minimum of Months | 14343087.36 | 0.29 | 63.91 | 0.94 | |
| Maximum of Months | 0.237599E+09 | 0.97 | 165.83 | 1.07 |
Report: FanReportMonthly
For: G S2 APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.65 | 20.01 | 01-JAN-00:10 | 0.65 |
| February | 48400714.57 | 0.65 | 20.01 | 01-FEB-00:10 | 0.65 |
| March | 53586505.42 | 0.65 | 20.01 | 01-MAR-00:10 | 0.65 |
| April | 51857908.47 | 0.64 | 20.01 | 01-APR-00:10 | 0.65 |
| May | 53586505.42 | 0.64 | 20.01 | 01-MAY-00:10 | 0.64 |
| June | 51857908.47 | 0.64 | 20.01 | 01-JUN-00:10 | 0.64 |
| July | 53586505.42 | 0.64 | 20.01 | 01-JUL-00:10 | 0.64 |
| August | 53586505.42 | 0.64 | 20.01 | 01-AUG-00:10 | 0.64 |
| September | 51857908.47 | 0.64 | 20.01 | 01-SEP-00:10 | 0.64 |
| October | 53586505.42 | 0.64 | 20.01 | 01-OCT-00:10 | 0.64 |
| November | 51857908.47 | 0.65 | 20.01 | 01-NOV-00:10 | 0.65 |
| December | 53586505.42 | 0.65 | 20.01 | 01-DEC-00:10 | 0.65 |
| Annual Sum or Average | 0.630938E+09 | 0.64 | |||
| Minimum of Months | 48400714.57 | 0.64 | 20.01 | 0.64 | |
| Maximum of Months | 53586505.42 | 0.65 | 20.01 | 0.65 |
Report: FanReportMonthly
For: G S2 APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.65 | 20.01 | 01-JAN-00:10 | 0.65 |
| February | 48400714.57 | 0.65 | 20.01 | 01-FEB-00:10 | 0.65 |
| March | 53586505.42 | 0.65 | 20.01 | 01-MAR-00:10 | 0.65 |
| April | 51857908.47 | 0.64 | 20.01 | 01-APR-00:10 | 0.65 |
| May | 53586505.42 | 0.64 | 20.01 | 01-MAY-00:10 | 0.64 |
| June | 51857908.47 | 0.64 | 20.01 | 01-JUN-00:10 | 0.64 |
| July | 53586505.42 | 0.64 | 20.01 | 01-JUL-00:10 | 0.64 |
| August | 53586505.42 | 0.64 | 20.01 | 01-AUG-00:10 | 0.64 |
| September | 51857908.47 | 0.64 | 20.01 | 01-SEP-00:10 | 0.64 |
| October | 53586505.42 | 0.64 | 20.01 | 01-OCT-00:10 | 0.64 |
| November | 51857908.47 | 0.65 | 20.01 | 01-NOV-00:10 | 0.65 |
| December | 53586505.42 | 0.65 | 20.01 | 01-DEC-00:10 | 0.65 |
| Annual Sum or Average | 0.630938E+09 | 0.64 | |||
| Minimum of Months | 48400714.57 | 0.64 | 20.01 | 0.64 | |
| Maximum of Months | 53586505.42 | 0.65 | 20.01 | 0.65 |
Report: FanReportMonthly
For: SPLIT MSW SUPPLY FAN
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.479601E+09 | 0.94 | 328.23 | 29-JAN-00:10 | 0.94 |
| February | 0.342346E+09 | 0.94 | 281.39 | 25-FEB-01:00 | 0.94 |
| March | 0.248247E+09 | 0.86 | 241.39 | 01-MAR-07:00 | 0.94 |
| April | 0.107106E+09 | 0.50 | 326.94 | 22-APR-16:05 | 1.05 |
| May | 0.194193E+09 | 0.61 | 389.07 | 31-MAY-16:10 | 1.04 |
| June | 0.364436E+09 | 0.99 | 450.24 | 20-JUN-16:20 | 1.03 |
| July | 0.402371E+09 | 1.01 | 500.57 | 29-JUL-15:30 | 1.02 |
| August | 0.282398E+09 | 0.85 | 478.04 | 11-AUG-16:02 | 1.02 |
| September | 65557407.16 | 0.43 | 277.33 | 09-SEP-15:50 | 1.05 |
| October | 0.192722E+09 | 0.79 | 198.28 | 27-OCT-04:00 | 0.94 |
| November | 0.413362E+09 | 0.94 | 259.69 | 29-NOV-08:00 | 0.94 |
| December | 0.514344E+09 | 0.94 | 285.83 | 15-DEC-10:00 | 0.94 |
| Annual Sum or Average | 0.360668E+10 | 0.82 | |||
| Minimum of Months | 65557407.16 | 0.43 | 198.28 | 0.94 | |
| Maximum of Months | 0.514344E+09 | 1.01 | 500.57 | 1.05 |
Report: FanReportMonthly
For: M SW APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.107173E+09 | 0.65 | 40.01 | 01-JAN-00:10 | 0.65 |
| February | 96801429.15 | 0.65 | 40.01 | 01-FEB-00:10 | 0.65 |
| March | 0.107173E+09 | 0.65 | 40.01 | 01-MAR-00:10 | 0.65 |
| April | 0.103716E+09 | 0.64 | 40.01 | 01-APR-00:10 | 0.65 |
| May | 0.107173E+09 | 0.64 | 40.01 | 01-MAY-00:10 | 0.64 |
| June | 0.103716E+09 | 0.64 | 40.01 | 01-JUN-00:10 | 0.64 |
| July | 0.107173E+09 | 0.64 | 40.01 | 01-JUL-00:10 | 0.64 |
| August | 0.107173E+09 | 0.64 | 40.01 | 01-AUG-00:10 | 0.64 |
| September | 0.103716E+09 | 0.64 | 40.01 | 01-SEP-00:10 | 0.64 |
| October | 0.107173E+09 | 0.64 | 40.01 | 01-OCT-00:10 | 0.64 |
| November | 0.103716E+09 | 0.65 | 40.01 | 01-NOV-00:10 | 0.65 |
| December | 0.107173E+09 | 0.65 | 40.01 | 01-DEC-00:10 | 0.65 |
| Annual Sum or Average | 0.126188E+10 | 0.64 | |||
| Minimum of Months | 96801429.15 | 0.64 | 40.01 | 0.64 | |
| Maximum of Months | 0.107173E+09 | 0.65 | 40.01 | 0.65 |
Report: FanReportMonthly
For: M SW APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.107173E+09 | 0.65 | 40.01 | 01-JAN-00:10 | 0.65 |
| February | 96801429.15 | 0.65 | 40.01 | 01-FEB-00:10 | 0.65 |
| March | 0.107173E+09 | 0.65 | 40.01 | 01-MAR-00:10 | 0.65 |
| April | 0.103716E+09 | 0.64 | 40.01 | 01-APR-00:10 | 0.65 |
| May | 0.107173E+09 | 0.64 | 40.01 | 01-MAY-00:10 | 0.64 |
| June | 0.103716E+09 | 0.64 | 40.01 | 01-JUN-00:10 | 0.64 |
| July | 0.107173E+09 | 0.64 | 40.01 | 01-JUL-00:10 | 0.64 |
| August | 0.107173E+09 | 0.64 | 40.01 | 01-AUG-00:10 | 0.64 |
| September | 0.103716E+09 | 0.64 | 40.01 | 01-SEP-00:10 | 0.64 |
| October | 0.107173E+09 | 0.64 | 40.01 | 01-OCT-00:10 | 0.64 |
| November | 0.103716E+09 | 0.65 | 40.01 | 01-NOV-00:10 | 0.65 |
| December | 0.107173E+09 | 0.65 | 40.01 | 01-DEC-00:10 | 0.65 |
| Annual Sum or Average | 0.126188E+10 | 0.64 | |||
| Minimum of Months | 96801429.15 | 0.64 | 40.01 | 0.64 | |
| Maximum of Months | 0.107173E+09 | 0.65 | 40.01 | 0.65 |
Report: FanReportMonthly
For: SPLIT MNW SUPPLY FAN
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.489353E+09 | 0.94 | 333.92 | 29-JAN-00:10 | 0.94 |
| February | 0.392611E+09 | 0.94 | 288.36 | 25-FEB-01:00 | 0.94 |
| March | 0.335883E+09 | 0.94 | 257.24 | 02-MAR-05:00 | 0.94 |
| April | 0.118418E+09 | 0.61 | 192.60 | 03-APR-03:00 | 0.94 |
| May | 68158384.41 | 0.42 | 254.32 | 31-MAY-17:15 | 1.05 |
| June | 0.284217E+09 | 0.99 | 351.97 | 20-JUN-17:40 | 1.03 |
| July | 0.303726E+09 | 0.99 | 369.66 | 11-JUL-18:00 | 1.03 |
| August | 0.147868E+09 | 0.73 | 312.59 | 11-AUG-17:25 | 1.04 |
| September | 35848602.12 | 0.32 | 99.53 | 30-SEP-05:00 | 0.93 |
| October | 0.240638E+09 | 0.91 | 210.59 | 27-OCT-04:00 | 0.94 |
| November | 0.437231E+09 | 0.94 | 258.46 | 29-NOV-07:55 | 0.94 |
| December | 0.509242E+09 | 0.94 | 288.71 | 15-DEC-12:00 | 0.94 |
| Annual Sum or Average | 0.336319E+10 | 0.80 | |||
| Minimum of Months | 35848602.12 | 0.32 | 99.53 | 0.93 | |
| Maximum of Months | 0.509242E+09 | 0.99 | 369.66 | 1.05 |
Report: FanReportMonthly
For: M NW APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.107173E+09 | 0.65 | 40.01 | 01-JAN-00:10 | 0.65 |
| February | 96801429.15 | 0.65 | 40.01 | 01-FEB-00:10 | 0.65 |
| March | 0.107173E+09 | 0.65 | 40.01 | 01-MAR-00:10 | 0.65 |
| April | 0.103716E+09 | 0.64 | 40.01 | 01-APR-00:10 | 0.65 |
| May | 0.107173E+09 | 0.64 | 40.01 | 01-MAY-00:10 | 0.64 |
| June | 0.103716E+09 | 0.64 | 40.01 | 01-JUN-00:10 | 0.64 |
| July | 0.107173E+09 | 0.64 | 40.01 | 01-JUL-00:10 | 0.64 |
| August | 0.107173E+09 | 0.64 | 40.01 | 01-AUG-00:10 | 0.64 |
| September | 0.103716E+09 | 0.64 | 40.01 | 01-SEP-00:10 | 0.64 |
| October | 0.107173E+09 | 0.64 | 40.01 | 01-OCT-00:10 | 0.64 |
| November | 0.103716E+09 | 0.65 | 40.01 | 01-NOV-00:10 | 0.65 |
| December | 0.107173E+09 | 0.65 | 40.01 | 01-DEC-00:10 | 0.65 |
| Annual Sum or Average | 0.126188E+10 | 0.64 | |||
| Minimum of Months | 96801429.15 | 0.64 | 40.01 | 0.64 | |
| Maximum of Months | 0.107173E+09 | 0.65 | 40.01 | 0.65 |
Report: FanReportMonthly
For: M NW APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.107173E+09 | 0.65 | 40.01 | 01-JAN-00:10 | 0.65 |
| February | 96801429.15 | 0.65 | 40.01 | 01-FEB-00:10 | 0.65 |
| March | 0.107173E+09 | 0.65 | 40.01 | 01-MAR-00:10 | 0.65 |
| April | 0.103716E+09 | 0.64 | 40.01 | 01-APR-00:10 | 0.65 |
| May | 0.107173E+09 | 0.64 | 40.01 | 01-MAY-00:10 | 0.64 |
| June | 0.103716E+09 | 0.64 | 40.01 | 01-JUN-00:10 | 0.64 |
| July | 0.107173E+09 | 0.64 | 40.01 | 01-JUL-00:10 | 0.64 |
| August | 0.107173E+09 | 0.64 | 40.01 | 01-AUG-00:10 | 0.64 |
| September | 0.103716E+09 | 0.64 | 40.01 | 01-SEP-00:10 | 0.64 |
| October | 0.107173E+09 | 0.64 | 40.01 | 01-OCT-00:10 | 0.64 |
| November | 0.103716E+09 | 0.65 | 40.01 | 01-NOV-00:10 | 0.65 |
| December | 0.107173E+09 | 0.65 | 40.01 | 01-DEC-00:10 | 0.65 |
| Annual Sum or Average | 0.126188E+10 | 0.64 | |||
| Minimum of Months | 96801429.15 | 0.64 | 40.01 | 0.64 | |
| Maximum of Months | 0.107173E+09 | 0.65 | 40.01 | 0.65 |
Report: FanReportMonthly
For: SPLIT MSE SUPPLY FAN
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.466530E+09 | 0.94 | 321.28 | 29-JAN-00:10 | 0.94 |
| February | 0.327499E+09 | 0.94 | 272.16 | 25-FEB-01:00 | 0.94 |
| March | 0.224134E+09 | 0.83 | 235.89 | 01-MAR-07:00 | 0.94 |
| April | 0.102690E+09 | 0.51 | 307.07 | 22-APR-13:30 | 1.05 |
| May | 0.245835E+09 | 0.68 | 390.27 | 12-MAY-13:30 | 1.03 |
| June | 0.395327E+09 | 1.01 | 429.26 | 30-JUN-12:30 | 1.01 |
| July | 0.447965E+09 | 1.01 | 488.77 | 22-JUL-11:30 | 1.00 |
| August | 0.312663E+09 | 0.88 | 441.01 | 10-AUG-14:10 | 1.02 |
| September | 73790735.58 | 0.45 | 271.79 | 10-SEP-11:30 | 1.05 |
| October | 0.179695E+09 | 0.76 | 193.00 | 27-OCT-04:00 | 0.94 |
| November | 0.403827E+09 | 0.94 | 253.95 | 29-NOV-08:00 | 0.94 |
| December | 0.502027E+09 | 0.94 | 279.61 | 15-DEC-10:00 | 0.94 |
| Annual Sum or Average | 0.368198E+10 | 0.82 | |||
| Minimum of Months | 73790735.58 | 0.45 | 193.00 | 0.94 | |
| Maximum of Months | 0.502027E+09 | 1.01 | 488.77 | 1.05 |
Report: FanReportMonthly
For: M SE APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.107173E+09 | 0.65 | 40.01 | 01-JAN-00:10 | 0.65 |
| February | 96801429.15 | 0.65 | 40.01 | 01-FEB-00:10 | 0.65 |
| March | 0.107173E+09 | 0.65 | 40.01 | 01-MAR-00:10 | 0.65 |
| April | 0.103716E+09 | 0.64 | 40.01 | 01-APR-00:10 | 0.65 |
| May | 0.107173E+09 | 0.64 | 40.01 | 01-MAY-00:10 | 0.64 |
| June | 0.103716E+09 | 0.64 | 40.01 | 01-JUN-00:10 | 0.64 |
| July | 0.107173E+09 | 0.64 | 40.01 | 01-JUL-00:10 | 0.64 |
| August | 0.107173E+09 | 0.64 | 40.01 | 01-AUG-00:10 | 0.64 |
| September | 0.103716E+09 | 0.64 | 40.01 | 01-SEP-00:10 | 0.64 |
| October | 0.107173E+09 | 0.64 | 40.01 | 01-OCT-00:10 | 0.64 |
| November | 0.103716E+09 | 0.65 | 40.01 | 01-NOV-00:10 | 0.65 |
| December | 0.107173E+09 | 0.65 | 40.01 | 01-DEC-00:10 | 0.65 |
| Annual Sum or Average | 0.126188E+10 | 0.64 | |||
| Minimum of Months | 96801429.15 | 0.64 | 40.01 | 0.64 | |
| Maximum of Months | 0.107173E+09 | 0.65 | 40.01 | 0.65 |
Report: FanReportMonthly
For: M SE APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.107173E+09 | 0.65 | 40.01 | 01-JAN-00:10 | 0.65 |
| February | 96801429.15 | 0.65 | 40.01 | 01-FEB-00:10 | 0.65 |
| March | 0.107173E+09 | 0.65 | 40.01 | 01-MAR-00:10 | 0.65 |
| April | 0.103716E+09 | 0.64 | 40.01 | 01-APR-00:10 | 0.65 |
| May | 0.107173E+09 | 0.64 | 40.01 | 01-MAY-00:10 | 0.64 |
| June | 0.103716E+09 | 0.64 | 40.01 | 01-JUN-00:10 | 0.64 |
| July | 0.107173E+09 | 0.64 | 40.01 | 01-JUL-00:10 | 0.64 |
| August | 0.107173E+09 | 0.64 | 40.01 | 01-AUG-00:10 | 0.64 |
| September | 0.103716E+09 | 0.64 | 40.01 | 01-SEP-00:10 | 0.64 |
| October | 0.107173E+09 | 0.64 | 40.01 | 01-OCT-00:10 | 0.64 |
| November | 0.103716E+09 | 0.65 | 40.01 | 01-NOV-00:10 | 0.65 |
| December | 0.107173E+09 | 0.65 | 40.01 | 01-DEC-00:10 | 0.65 |
| Annual Sum or Average | 0.126188E+10 | 0.64 | |||
| Minimum of Months | 96801429.15 | 0.64 | 40.01 | 0.64 | |
| Maximum of Months | 0.107173E+09 | 0.65 | 40.01 | 0.65 |
Report: FanReportMonthly
For: SPLIT MNE SUPPLY FAN
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.472577E+09 | 0.94 | 324.44 | 29-JAN-00:10 | 0.94 |
| February | 0.373805E+09 | 0.94 | 277.20 | 25-FEB-01:00 | 0.94 |
| March | 0.307038E+09 | 0.93 | 248.81 | 02-MAR-05:00 | 0.94 |
| April | 0.113995E+09 | 0.60 | 194.24 | 03-APR-03:00 | 0.94 |
| May | 0.111810E+09 | 0.54 | 217.85 | 31-MAY-16:17 | 1.05 |
| June | 0.315635E+09 | 0.99 | 302.93 | 29-JUN-10:40 | 1.03 |
| July | 0.350213E+09 | 0.99 | 336.17 | 21-JUL-16:06 | 1.02 |
| August | 0.174696E+09 | 0.76 | 244.63 | 11-AUG-17:13 | 1.04 |
| September | 31135994.51 | 0.29 | 93.92 | 30-SEP-05:00 | 0.93 |
| October | 0.223794E+09 | 0.90 | 203.69 | 27-OCT-04:00 | 0.94 |
| November | 0.424019E+09 | 0.94 | 250.89 | 29-NOV-07:55 | 0.94 |
| December | 0.493407E+09 | 0.94 | 279.15 | 15-DEC-12:00 | 0.94 |
| Annual Sum or Average | 0.339213E+10 | 0.81 | |||
| Minimum of Months | 31135994.51 | 0.29 | 93.92 | 0.93 | |
| Maximum of Months | 0.493407E+09 | 0.99 | 336.17 | 1.05 |
Report: FanReportMonthly
For: M NE APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.107173E+09 | 0.65 | 40.01 | 01-JAN-00:10 | 0.65 |
| February | 96801429.15 | 0.65 | 40.01 | 01-FEB-00:10 | 0.65 |
| March | 0.107173E+09 | 0.65 | 40.01 | 01-MAR-00:10 | 0.65 |
| April | 0.103716E+09 | 0.64 | 40.01 | 01-APR-00:10 | 0.65 |
| May | 0.107173E+09 | 0.64 | 40.01 | 01-MAY-00:10 | 0.64 |
| June | 0.103716E+09 | 0.64 | 40.01 | 01-JUN-00:10 | 0.64 |
| July | 0.107173E+09 | 0.64 | 40.01 | 01-JUL-00:10 | 0.64 |
| August | 0.107173E+09 | 0.64 | 40.01 | 01-AUG-00:10 | 0.64 |
| September | 0.103716E+09 | 0.64 | 40.01 | 01-SEP-00:10 | 0.64 |
| October | 0.107173E+09 | 0.64 | 40.01 | 01-OCT-00:10 | 0.64 |
| November | 0.103716E+09 | 0.65 | 40.01 | 01-NOV-00:10 | 0.65 |
| December | 0.107173E+09 | 0.65 | 40.01 | 01-DEC-00:10 | 0.65 |
| Annual Sum or Average | 0.126188E+10 | 0.64 | |||
| Minimum of Months | 96801429.15 | 0.64 | 40.01 | 0.64 | |
| Maximum of Months | 0.107173E+09 | 0.65 | 40.01 | 0.65 |
Report: FanReportMonthly
For: M NE APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.107173E+09 | 0.65 | 40.01 | 01-JAN-00:10 | 0.65 |
| February | 96801429.15 | 0.65 | 40.01 | 01-FEB-00:10 | 0.65 |
| March | 0.107173E+09 | 0.65 | 40.01 | 01-MAR-00:10 | 0.65 |
| April | 0.103716E+09 | 0.64 | 40.01 | 01-APR-00:10 | 0.65 |
| May | 0.107173E+09 | 0.64 | 40.01 | 01-MAY-00:10 | 0.64 |
| June | 0.103716E+09 | 0.64 | 40.01 | 01-JUN-00:10 | 0.64 |
| July | 0.107173E+09 | 0.64 | 40.01 | 01-JUL-00:10 | 0.64 |
| August | 0.107173E+09 | 0.64 | 40.01 | 01-AUG-00:10 | 0.64 |
| September | 0.103716E+09 | 0.64 | 40.01 | 01-SEP-00:10 | 0.64 |
| October | 0.107173E+09 | 0.64 | 40.01 | 01-OCT-00:10 | 0.64 |
| November | 0.103716E+09 | 0.65 | 40.01 | 01-NOV-00:10 | 0.65 |
| December | 0.107173E+09 | 0.65 | 40.01 | 01-DEC-00:10 | 0.65 |
| Annual Sum or Average | 0.126188E+10 | 0.64 | |||
| Minimum of Months | 96801429.15 | 0.64 | 40.01 | 0.64 | |
| Maximum of Months | 0.107173E+09 | 0.65 | 40.01 | 0.65 |
Report: FanReportMonthly
For: SPLIT MN1 SUPPLY FAN
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.333280E+09 | 0.94 | 222.07 | 12-JAN-04:00 | 0.94 |
| February | 0.268399E+09 | 0.94 | 195.75 | 27-FEB-07:00 | 0.94 |
| March | 0.229460E+09 | 0.94 | 178.86 | 02-MAR-05:00 | 0.94 |
| April | 79496119.06 | 0.57 | 140.08 | 03-APR-03:00 | 0.94 |
| May | 51923754.28 | 0.45 | 160.01 | 31-MAY-17:20 | 1.06 |
| June | 0.229664E+09 | 1.03 | 231.72 | 29-JUN-20:00 | 1.04 |
| July | 0.258391E+09 | 1.04 | 251.64 | 21-JUL-16:02 | 1.04 |
| August | 0.132755E+09 | 0.83 | 195.26 | 11-AUG-17:50 | 1.05 |
| September | 18755409.69 | 0.23 | 64.49 | 30-SEP-05:00 | 0.93 |
| October | 0.151318E+09 | 0.86 | 141.91 | 27-OCT-04:00 | 0.94 |
| November | 0.302312E+09 | 0.94 | 178.21 | 29-NOV-07:55 | 0.94 |
| December | 0.349348E+09 | 0.94 | 201.05 | 15-DEC-12:00 | 0.94 |
| Annual Sum or Average | 0.240510E+10 | 0.81 | |||
| Minimum of Months | 18755409.69 | 0.23 | 64.49 | 0.93 | |
| Maximum of Months | 0.349348E+09 | 1.04 | 251.64 | 1.06 |
Report: FanReportMonthly
For: M N1 APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.107173E+09 | 0.65 | 40.01 | 01-JAN-00:10 | 0.65 |
| February | 96801429.15 | 0.65 | 40.01 | 01-FEB-00:10 | 0.65 |
| March | 0.107173E+09 | 0.65 | 40.01 | 01-MAR-00:10 | 0.65 |
| April | 0.103716E+09 | 0.64 | 40.01 | 01-APR-00:10 | 0.65 |
| May | 0.107173E+09 | 0.64 | 40.01 | 01-MAY-00:10 | 0.64 |
| June | 0.103716E+09 | 0.64 | 40.01 | 01-JUN-00:10 | 0.64 |
| July | 0.107173E+09 | 0.64 | 40.01 | 01-JUL-00:10 | 0.64 |
| August | 0.107173E+09 | 0.64 | 40.01 | 01-AUG-00:10 | 0.64 |
| September | 0.103716E+09 | 0.64 | 40.01 | 01-SEP-00:10 | 0.64 |
| October | 0.107173E+09 | 0.64 | 40.01 | 01-OCT-00:10 | 0.64 |
| November | 0.103716E+09 | 0.65 | 40.01 | 01-NOV-00:10 | 0.65 |
| December | 0.107173E+09 | 0.65 | 40.01 | 01-DEC-00:10 | 0.65 |
| Annual Sum or Average | 0.126188E+10 | 0.64 | |||
| Minimum of Months | 96801429.15 | 0.64 | 40.01 | 0.64 | |
| Maximum of Months | 0.107173E+09 | 0.65 | 40.01 | 0.65 |
Report: FanReportMonthly
For: M N1 APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.107173E+09 | 0.65 | 40.01 | 01-JAN-00:10 | 0.65 |
| February | 96801429.15 | 0.65 | 40.01 | 01-FEB-00:10 | 0.65 |
| March | 0.107173E+09 | 0.65 | 40.01 | 01-MAR-00:10 | 0.65 |
| April | 0.103716E+09 | 0.64 | 40.01 | 01-APR-00:10 | 0.65 |
| May | 0.107173E+09 | 0.64 | 40.01 | 01-MAY-00:10 | 0.64 |
| June | 0.103716E+09 | 0.64 | 40.01 | 01-JUN-00:10 | 0.64 |
| July | 0.107173E+09 | 0.64 | 40.01 | 01-JUL-00:10 | 0.64 |
| August | 0.107173E+09 | 0.64 | 40.01 | 01-AUG-00:10 | 0.64 |
| September | 0.103716E+09 | 0.64 | 40.01 | 01-SEP-00:10 | 0.64 |
| October | 0.107173E+09 | 0.64 | 40.01 | 01-OCT-00:10 | 0.64 |
| November | 0.103716E+09 | 0.65 | 40.01 | 01-NOV-00:10 | 0.65 |
| December | 0.107173E+09 | 0.65 | 40.01 | 01-DEC-00:10 | 0.65 |
| Annual Sum or Average | 0.126188E+10 | 0.64 | |||
| Minimum of Months | 96801429.15 | 0.64 | 40.01 | 0.64 | |
| Maximum of Months | 0.107173E+09 | 0.65 | 40.01 | 0.65 |
Report: FanReportMonthly
For: SPLIT MN2 SUPPLY FAN
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.333031E+09 | 0.94 | 221.94 | 12-JAN-04:00 | 0.94 |
| February | 0.267986E+09 | 0.94 | 195.68 | 27-FEB-07:00 | 0.94 |
| March | 0.228462E+09 | 0.93 | 178.69 | 02-MAR-05:00 | 0.94 |
| April | 79553807.18 | 0.57 | 140.37 | 03-APR-03:00 | 0.94 |
| May | 54477155.51 | 0.46 | 159.88 | 31-MAY-17:20 | 1.06 |
| June | 0.231050E+09 | 1.03 | 230.63 | 29-JUN-20:00 | 1.04 |
| July | 0.260349E+09 | 1.04 | 252.79 | 21-JUL-16:04 | 1.04 |
| August | 0.134260E+09 | 0.84 | 194.74 | 11-AUG-17:40 | 1.05 |
| September | 18581189.41 | 0.23 | 64.22 | 30-SEP-05:00 | 0.93 |
| October | 0.150774E+09 | 0.86 | 141.84 | 27-OCT-04:00 | 0.94 |
| November | 0.302146E+09 | 0.94 | 178.11 | 29-NOV-07:55 | 0.94 |
| December | 0.349145E+09 | 0.94 | 200.92 | 15-DEC-12:00 | 0.94 |
| Annual Sum or Average | 0.240981E+10 | 0.81 | |||
| Minimum of Months | 18581189.41 | 0.23 | 64.22 | 0.93 | |
| Maximum of Months | 0.349145E+09 | 1.04 | 252.79 | 1.06 |
Report: FanReportMonthly
For: M N2 APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.107173E+09 | 0.65 | 40.01 | 01-JAN-00:10 | 0.65 |
| February | 96801429.15 | 0.65 | 40.01 | 01-FEB-00:10 | 0.65 |
| March | 0.107173E+09 | 0.65 | 40.01 | 01-MAR-00:10 | 0.65 |
| April | 0.103716E+09 | 0.64 | 40.01 | 01-APR-00:10 | 0.65 |
| May | 0.107173E+09 | 0.64 | 40.01 | 01-MAY-00:10 | 0.64 |
| June | 0.103716E+09 | 0.64 | 40.01 | 01-JUN-00:10 | 0.64 |
| July | 0.107173E+09 | 0.64 | 40.01 | 01-JUL-00:10 | 0.64 |
| August | 0.107173E+09 | 0.64 | 40.01 | 01-AUG-00:10 | 0.64 |
| September | 0.103716E+09 | 0.64 | 40.01 | 01-SEP-00:10 | 0.64 |
| October | 0.107173E+09 | 0.64 | 40.01 | 01-OCT-00:10 | 0.64 |
| November | 0.103716E+09 | 0.65 | 40.01 | 01-NOV-00:10 | 0.65 |
| December | 0.107173E+09 | 0.65 | 40.01 | 01-DEC-00:10 | 0.65 |
| Annual Sum or Average | 0.126188E+10 | 0.64 | |||
| Minimum of Months | 96801429.15 | 0.64 | 40.01 | 0.64 | |
| Maximum of Months | 0.107173E+09 | 0.65 | 40.01 | 0.65 |
Report: FanReportMonthly
For: M N2 APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.107173E+09 | 0.65 | 40.01 | 01-JAN-00:10 | 0.65 |
| February | 96801429.15 | 0.65 | 40.01 | 01-FEB-00:10 | 0.65 |
| March | 0.107173E+09 | 0.65 | 40.01 | 01-MAR-00:10 | 0.65 |
| April | 0.103716E+09 | 0.64 | 40.01 | 01-APR-00:10 | 0.65 |
| May | 0.107173E+09 | 0.64 | 40.01 | 01-MAY-00:10 | 0.64 |
| June | 0.103716E+09 | 0.64 | 40.01 | 01-JUN-00:10 | 0.64 |
| July | 0.107173E+09 | 0.64 | 40.01 | 01-JUL-00:10 | 0.64 |
| August | 0.107173E+09 | 0.64 | 40.01 | 01-AUG-00:10 | 0.64 |
| September | 0.103716E+09 | 0.64 | 40.01 | 01-SEP-00:10 | 0.64 |
| October | 0.107173E+09 | 0.64 | 40.01 | 01-OCT-00:10 | 0.64 |
| November | 0.103716E+09 | 0.65 | 40.01 | 01-NOV-00:10 | 0.65 |
| December | 0.107173E+09 | 0.65 | 40.01 | 01-DEC-00:10 | 0.65 |
| Annual Sum or Average | 0.126188E+10 | 0.64 | |||
| Minimum of Months | 96801429.15 | 0.64 | 40.01 | 0.64 | |
| Maximum of Months | 0.107173E+09 | 0.65 | 40.01 | 0.65 |
Report: FanReportMonthly
For: SPLIT MS1 SUPPLY FAN
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.326928E+09 | 0.94 | 227.09 | 12-JAN-04:00 | 0.94 |
| February | 0.223955E+09 | 0.92 | 188.90 | 24-FEB-05:00 | 0.94 |
| March | 0.149023E+09 | 0.79 | 167.68 | 01-MAR-07:00 | 0.94 |
| April | 70911309.62 | 0.42 | 266.04 | 22-APR-13:50 | 1.05 |
| May | 0.183858E+09 | 0.69 | 310.43 | 12-MAY-13:30 | 1.04 |
| June | 0.310393E+09 | 1.04 | 350.42 | 30-JUN-12:30 | 1.02 |
| July | 0.357503E+09 | 1.04 | 406.11 | 29-JUL-15:30 | 1.01 |
| August | 0.272730E+09 | 0.96 | 380.01 | 11-AUG-15:10 | 1.02 |
| September | 67642478.77 | 0.44 | 251.89 | 09-SEP-15:20 | 1.05 |
| October | 0.110965E+09 | 0.66 | 132.41 | 27-OCT-04:00 | 0.94 |
| November | 0.282443E+09 | 0.94 | 180.24 | 29-NOV-07:55 | 0.94 |
| December | 0.356964E+09 | 0.94 | 203.77 | 15-DEC-10:00 | 0.94 |
| Annual Sum or Average | 0.271332E+10 | 0.82 | |||
| Minimum of Months | 67642478.77 | 0.42 | 132.41 | 0.94 | |
| Maximum of Months | 0.357503E+09 | 1.04 | 406.11 | 1.05 |
Report: FanReportMonthly
For: M S1 APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.107173E+09 | 0.65 | 40.01 | 01-JAN-00:10 | 0.65 |
| February | 96801429.15 | 0.65 | 40.01 | 01-FEB-00:10 | 0.65 |
| March | 0.107173E+09 | 0.65 | 40.01 | 01-MAR-00:10 | 0.65 |
| April | 0.103716E+09 | 0.64 | 40.01 | 01-APR-00:10 | 0.65 |
| May | 0.107173E+09 | 0.64 | 40.01 | 01-MAY-00:10 | 0.64 |
| June | 0.103716E+09 | 0.64 | 40.01 | 01-JUN-00:10 | 0.64 |
| July | 0.107173E+09 | 0.64 | 40.01 | 01-JUL-00:10 | 0.64 |
| August | 0.107173E+09 | 0.64 | 40.01 | 01-AUG-00:10 | 0.64 |
| September | 0.103716E+09 | 0.64 | 40.01 | 01-SEP-00:10 | 0.64 |
| October | 0.107173E+09 | 0.64 | 40.01 | 01-OCT-00:10 | 0.64 |
| November | 0.103716E+09 | 0.65 | 40.01 | 01-NOV-00:10 | 0.65 |
| December | 0.107173E+09 | 0.65 | 40.01 | 01-DEC-00:10 | 0.65 |
| Annual Sum or Average | 0.126188E+10 | 0.64 | |||
| Minimum of Months | 96801429.15 | 0.64 | 40.01 | 0.64 | |
| Maximum of Months | 0.107173E+09 | 0.65 | 40.01 | 0.65 |
Report: FanReportMonthly
For: M S1 APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.107173E+09 | 0.65 | 40.01 | 01-JAN-00:10 | 0.65 |
| February | 96801429.15 | 0.65 | 40.01 | 01-FEB-00:10 | 0.65 |
| March | 0.107173E+09 | 0.65 | 40.01 | 01-MAR-00:10 | 0.65 |
| April | 0.103716E+09 | 0.64 | 40.01 | 01-APR-00:10 | 0.65 |
| May | 0.107173E+09 | 0.64 | 40.01 | 01-MAY-00:10 | 0.64 |
| June | 0.103716E+09 | 0.64 | 40.01 | 01-JUN-00:10 | 0.64 |
| July | 0.107173E+09 | 0.64 | 40.01 | 01-JUL-00:10 | 0.64 |
| August | 0.107173E+09 | 0.64 | 40.01 | 01-AUG-00:10 | 0.64 |
| September | 0.103716E+09 | 0.64 | 40.01 | 01-SEP-00:10 | 0.64 |
| October | 0.107173E+09 | 0.64 | 40.01 | 01-OCT-00:10 | 0.64 |
| November | 0.103716E+09 | 0.65 | 40.01 | 01-NOV-00:10 | 0.65 |
| December | 0.107173E+09 | 0.65 | 40.01 | 01-DEC-00:10 | 0.65 |
| Annual Sum or Average | 0.126188E+10 | 0.64 | |||
| Minimum of Months | 96801429.15 | 0.64 | 40.01 | 0.64 | |
| Maximum of Months | 0.107173E+09 | 0.65 | 40.01 | 0.65 |
Report: FanReportMonthly
For: SPLIT MS2 SUPPLY FAN
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.326715E+09 | 0.94 | 226.98 | 12-JAN-04:00 | 0.94 |
| February | 0.223557E+09 | 0.92 | 188.74 | 24-FEB-05:00 | 0.94 |
| March | 0.148010E+09 | 0.79 | 167.57 | 01-MAR-07:00 | 0.94 |
| April | 71411926.57 | 0.42 | 267.59 | 22-APR-13:50 | 1.05 |
| May | 0.186913E+09 | 0.69 | 313.49 | 12-MAY-13:30 | 1.04 |
| June | 0.311806E+09 | 1.04 | 351.65 | 30-JUN-12:30 | 1.02 |
| July | 0.359408E+09 | 1.04 | 407.03 | 29-JUL-15:30 | 1.01 |
| August | 0.274387E+09 | 0.97 | 380.88 | 11-AUG-15:10 | 1.02 |
| September | 68964887.70 | 0.44 | 253.86 | 09-SEP-15:20 | 1.05 |
| October | 0.110497E+09 | 0.66 | 132.30 | 27-OCT-04:00 | 0.94 |
| November | 0.282315E+09 | 0.94 | 180.16 | 29-NOV-07:55 | 0.94 |
| December | 0.356796E+09 | 0.94 | 203.68 | 15-DEC-10:00 | 0.94 |
| Annual Sum or Average | 0.272078E+10 | 0.82 | |||
| Minimum of Months | 68964887.70 | 0.42 | 132.30 | 0.94 | |
| Maximum of Months | 0.359408E+09 | 1.04 | 407.03 | 1.05 |
Report: FanReportMonthly
For: M S2 APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.107173E+09 | 0.65 | 40.01 | 01-JAN-00:10 | 0.65 |
| February | 96801429.15 | 0.65 | 40.01 | 01-FEB-00:10 | 0.65 |
| March | 0.107173E+09 | 0.65 | 40.01 | 01-MAR-00:10 | 0.65 |
| April | 0.103716E+09 | 0.64 | 40.01 | 01-APR-00:10 | 0.65 |
| May | 0.107173E+09 | 0.64 | 40.01 | 01-MAY-00:10 | 0.64 |
| June | 0.103716E+09 | 0.64 | 40.01 | 01-JUN-00:10 | 0.64 |
| July | 0.107173E+09 | 0.64 | 40.01 | 01-JUL-00:10 | 0.64 |
| August | 0.107173E+09 | 0.64 | 40.01 | 01-AUG-00:10 | 0.64 |
| September | 0.103716E+09 | 0.64 | 40.01 | 01-SEP-00:10 | 0.64 |
| October | 0.107173E+09 | 0.64 | 40.01 | 01-OCT-00:10 | 0.64 |
| November | 0.103716E+09 | 0.65 | 40.01 | 01-NOV-00:10 | 0.65 |
| December | 0.107173E+09 | 0.65 | 40.01 | 01-DEC-00:10 | 0.65 |
| Annual Sum or Average | 0.126188E+10 | 0.64 | |||
| Minimum of Months | 96801429.15 | 0.64 | 40.01 | 0.64 | |
| Maximum of Months | 0.107173E+09 | 0.65 | 40.01 | 0.65 |
Report: FanReportMonthly
For: M S2 APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.107173E+09 | 0.65 | 40.01 | 01-JAN-00:10 | 0.65 |
| February | 96801429.15 | 0.65 | 40.01 | 01-FEB-00:10 | 0.65 |
| March | 0.107173E+09 | 0.65 | 40.01 | 01-MAR-00:10 | 0.65 |
| April | 0.103716E+09 | 0.64 | 40.01 | 01-APR-00:10 | 0.65 |
| May | 0.107173E+09 | 0.64 | 40.01 | 01-MAY-00:10 | 0.64 |
| June | 0.103716E+09 | 0.64 | 40.01 | 01-JUN-00:10 | 0.64 |
| July | 0.107173E+09 | 0.64 | 40.01 | 01-JUL-00:10 | 0.64 |
| August | 0.107173E+09 | 0.64 | 40.01 | 01-AUG-00:10 | 0.64 |
| September | 0.103716E+09 | 0.64 | 40.01 | 01-SEP-00:10 | 0.64 |
| October | 0.107173E+09 | 0.64 | 40.01 | 01-OCT-00:10 | 0.64 |
| November | 0.103716E+09 | 0.65 | 40.01 | 01-NOV-00:10 | 0.65 |
| December | 0.107173E+09 | 0.65 | 40.01 | 01-DEC-00:10 | 0.65 |
| Annual Sum or Average | 0.126188E+10 | 0.64 | |||
| Minimum of Months | 96801429.15 | 0.64 | 40.01 | 0.64 | |
| Maximum of Months | 0.107173E+09 | 0.65 | 40.01 | 0.65 |
Report: FanReportMonthly
For: SPLIT TSW SUPPLY FAN
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.361871E+09 | 0.94 | 240.50 | 29-JAN-00:10 | 0.94 |
| February | 0.270466E+09 | 0.94 | 209.04 | 25-FEB-01:00 | 0.94 |
| March | 0.213098E+09 | 0.88 | 187.62 | 02-MAR-05:00 | 0.94 |
| April | 0.115908E+09 | 0.72 | 199.55 | 21-APR-16:30 | 1.05 |
| May | 94607870.89 | 0.60 | 250.85 | 31-MAY-15:40 | 1.03 |
| June | 0.166636E+09 | 0.72 | 286.58 | 20-JUN-16:08 | 1.01 |
| July | 0.187125E+09 | 0.72 | 320.76 | 29-JUL-15:40 | 1.00 |
| August | 0.122520E+09 | 0.59 | 290.49 | 10-AUG-16:10 | 1.02 |
| September | 59000158.25 | 0.65 | 169.51 | 09-SEP-16:07 | 1.05 |
| October | 0.172732E+09 | 0.88 | 157.12 | 27-OCT-04:00 | 0.94 |
| November | 0.319688E+09 | 0.94 | 193.37 | 29-NOV-07:55 | 0.94 |
| December | 0.383186E+09 | 0.94 | 210.49 | 15-DEC-10:00 | 0.94 |
| Annual Sum or Average | 0.246684E+10 | 0.79 | |||
| Minimum of Months | 59000158.25 | 0.59 | 157.12 | 0.94 | |
| Maximum of Months | 0.383186E+09 | 0.94 | 320.76 | 1.05 |
Report: FanReportMonthly
For: T SW APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.65 | 20.01 | 01-JAN-00:10 | 0.65 |
| February | 48400714.57 | 0.65 | 20.01 | 01-FEB-00:10 | 0.65 |
| March | 53586505.42 | 0.65 | 20.01 | 01-MAR-00:10 | 0.65 |
| April | 51857908.47 | 0.64 | 20.01 | 01-APR-00:10 | 0.65 |
| May | 53586505.42 | 0.64 | 20.01 | 01-MAY-00:10 | 0.64 |
| June | 51857908.47 | 0.64 | 20.01 | 01-JUN-00:10 | 0.64 |
| July | 53586505.42 | 0.64 | 20.01 | 01-JUL-00:10 | 0.64 |
| August | 53586505.42 | 0.64 | 20.01 | 01-AUG-00:10 | 0.64 |
| September | 51857908.47 | 0.64 | 20.01 | 01-SEP-00:10 | 0.64 |
| October | 53586505.42 | 0.64 | 20.01 | 01-OCT-00:10 | 0.64 |
| November | 51857908.47 | 0.65 | 20.01 | 01-NOV-00:10 | 0.65 |
| December | 53586505.42 | 0.65 | 20.01 | 01-DEC-00:10 | 0.65 |
| Annual Sum or Average | 0.630938E+09 | 0.64 | |||
| Minimum of Months | 48400714.57 | 0.64 | 20.01 | 0.64 | |
| Maximum of Months | 53586505.42 | 0.65 | 20.01 | 0.65 |
Report: FanReportMonthly
For: T SW APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.65 | 20.01 | 01-JAN-00:10 | 0.65 |
| February | 48400714.57 | 0.65 | 20.01 | 01-FEB-00:10 | 0.65 |
| March | 53586505.42 | 0.65 | 20.01 | 01-MAR-00:10 | 0.65 |
| April | 51857908.47 | 0.64 | 20.01 | 01-APR-00:10 | 0.65 |
| May | 53586505.42 | 0.64 | 20.01 | 01-MAY-00:10 | 0.64 |
| June | 51857908.47 | 0.64 | 20.01 | 01-JUN-00:10 | 0.64 |
| July | 53586505.42 | 0.64 | 20.01 | 01-JUL-00:10 | 0.64 |
| August | 53586505.42 | 0.64 | 20.01 | 01-AUG-00:10 | 0.64 |
| September | 51857908.47 | 0.64 | 20.01 | 01-SEP-00:10 | 0.64 |
| October | 53586505.42 | 0.64 | 20.01 | 01-OCT-00:10 | 0.64 |
| November | 51857908.47 | 0.65 | 20.01 | 01-NOV-00:10 | 0.65 |
| December | 53586505.42 | 0.65 | 20.01 | 01-DEC-00:10 | 0.65 |
| Annual Sum or Average | 0.630938E+09 | 0.64 | |||
| Minimum of Months | 48400714.57 | 0.64 | 20.01 | 0.64 | |
| Maximum of Months | 53586505.42 | 0.65 | 20.01 | 0.65 |
Report: FanReportMonthly
For: SPLIT TNW SUPPLY FAN
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.366987E+09 | 0.94 | 241.14 | 29-JAN-00:10 | 0.94 |
| February | 0.297915E+09 | 0.94 | 209.83 | 25-FEB-01:00 | 0.94 |
| March | 0.260251E+09 | 0.94 | 191.08 | 02-MAR-05:00 | 0.94 |
| April | 0.115761E+09 | 0.76 | 154.08 | 03-APR-03:00 | 0.94 |
| May | 38010004.69 | 0.44 | 161.78 | 31-MAY-16:20 | 1.05 |
| June | 0.122646E+09 | 0.75 | 219.15 | 20-JUN-17:40 | 1.02 |
| July | 0.134848E+09 | 0.74 | 230.92 | 11-JUL-18:00 | 1.02 |
| August | 60662237.21 | 0.48 | 184.74 | 11-AUG-17:25 | 1.04 |
| September | 58019943.76 | 0.68 | 85.20 | 30-SEP-05:00 | 0.94 |
| October | 0.197534E+09 | 0.93 | 159.67 | 27-OCT-04:00 | 0.94 |
| November | 0.332287E+09 | 0.94 | 191.03 | 29-NOV-07:55 | 0.94 |
| December | 0.379879E+09 | 0.94 | 212.76 | 15-DEC-12:00 | 0.94 |
| Annual Sum or Average | 0.236480E+10 | 0.79 | |||
| Minimum of Months | 38010004.69 | 0.44 | 85.20 | 0.94 | |
| Maximum of Months | 0.379879E+09 | 0.94 | 241.14 | 1.05 |
Report: FanReportMonthly
For: T NW APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.65 | 20.01 | 01-JAN-00:10 | 0.65 |
| February | 48400714.57 | 0.65 | 20.01 | 01-FEB-00:10 | 0.65 |
| March | 53586505.42 | 0.65 | 20.01 | 01-MAR-00:10 | 0.65 |
| April | 51857908.47 | 0.64 | 20.01 | 01-APR-00:10 | 0.65 |
| May | 53586505.42 | 0.64 | 20.01 | 01-MAY-00:10 | 0.64 |
| June | 51857908.47 | 0.64 | 20.01 | 01-JUN-00:10 | 0.64 |
| July | 53586505.42 | 0.64 | 20.01 | 01-JUL-00:10 | 0.64 |
| August | 53586505.42 | 0.64 | 20.01 | 01-AUG-00:10 | 0.64 |
| September | 51857908.47 | 0.64 | 20.01 | 01-SEP-00:10 | 0.64 |
| October | 53586505.42 | 0.64 | 20.01 | 01-OCT-00:10 | 0.64 |
| November | 51857908.47 | 0.65 | 20.01 | 01-NOV-00:10 | 0.65 |
| December | 53586505.42 | 0.65 | 20.01 | 01-DEC-00:10 | 0.65 |
| Annual Sum or Average | 0.630938E+09 | 0.64 | |||
| Minimum of Months | 48400714.57 | 0.64 | 20.01 | 0.64 | |
| Maximum of Months | 53586505.42 | 0.65 | 20.01 | 0.65 |
Report: FanReportMonthly
For: T NW APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.65 | 20.01 | 01-JAN-00:10 | 0.65 |
| February | 48400714.57 | 0.65 | 20.01 | 01-FEB-00:10 | 0.65 |
| March | 53586505.42 | 0.65 | 20.01 | 01-MAR-00:10 | 0.65 |
| April | 51857908.47 | 0.64 | 20.01 | 01-APR-00:10 | 0.65 |
| May | 53586505.42 | 0.64 | 20.01 | 01-MAY-00:10 | 0.64 |
| June | 51857908.47 | 0.64 | 20.01 | 01-JUN-00:10 | 0.64 |
| July | 53586505.42 | 0.64 | 20.01 | 01-JUL-00:10 | 0.64 |
| August | 53586505.42 | 0.64 | 20.01 | 01-AUG-00:10 | 0.64 |
| September | 51857908.47 | 0.64 | 20.01 | 01-SEP-00:10 | 0.64 |
| October | 53586505.42 | 0.64 | 20.01 | 01-OCT-00:10 | 0.64 |
| November | 51857908.47 | 0.65 | 20.01 | 01-NOV-00:10 | 0.65 |
| December | 53586505.42 | 0.65 | 20.01 | 01-DEC-00:10 | 0.65 |
| Annual Sum or Average | 0.630938E+09 | 0.64 | |||
| Minimum of Months | 48400714.57 | 0.64 | 20.01 | 0.64 | |
| Maximum of Months | 53586505.42 | 0.65 | 20.01 | 0.65 |
Report: FanReportMonthly
For: SPLIT TSE SUPPLY FAN
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.349680E+09 | 0.94 | 233.80 | 29-JAN-00:10 | 0.94 |
| February | 0.258407E+09 | 0.94 | 201.69 | 25-FEB-01:00 | 0.94 |
| March | 0.196538E+09 | 0.86 | 181.86 | 02-MAR-05:00 | 0.94 |
| April | 0.108410E+09 | 0.71 | 182.63 | 22-APR-13:40 | 1.04 |
| May | 0.110495E+09 | 0.63 | 230.97 | 31-MAY-14:10 | 1.02 |
| June | 0.179480E+09 | 0.77 | 268.59 | 29-JUN-14:10 | 1.00 |
| July | 0.208216E+09 | 0.77 | 299.87 | 22-JUL-11:40 | 0.99 |
| August | 0.132240E+09 | 0.62 | 266.05 | 10-AUG-14:10 | 1.00 |
| September | 56197215.96 | 0.63 | 143.78 | 09-SEP-15:20 | 1.05 |
| October | 0.162760E+09 | 0.87 | 152.27 | 27-OCT-04:00 | 0.94 |
| November | 0.309983E+09 | 0.94 | 187.64 | 29-NOV-07:55 | 0.94 |
| December | 0.371201E+09 | 0.94 | 204.35 | 15-DEC-10:00 | 0.94 |
| Annual Sum or Average | 0.244361E+10 | 0.80 | |||
| Minimum of Months | 56197215.96 | 0.62 | 143.78 | 0.94 | |
| Maximum of Months | 0.371201E+09 | 0.94 | 299.87 | 1.05 |
Report: FanReportMonthly
For: T SE APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.65 | 20.01 | 01-JAN-00:10 | 0.65 |
| February | 48400714.57 | 0.65 | 20.01 | 01-FEB-00:10 | 0.65 |
| March | 53586505.42 | 0.65 | 20.01 | 01-MAR-00:10 | 0.65 |
| April | 51857908.47 | 0.64 | 20.01 | 01-APR-00:10 | 0.65 |
| May | 53586505.42 | 0.64 | 20.01 | 01-MAY-00:10 | 0.64 |
| June | 51857908.47 | 0.64 | 20.01 | 01-JUN-00:10 | 0.64 |
| July | 53586505.42 | 0.64 | 20.01 | 01-JUL-00:10 | 0.64 |
| August | 53586505.42 | 0.64 | 20.01 | 01-AUG-00:10 | 0.64 |
| September | 51857908.47 | 0.64 | 20.01 | 01-SEP-00:10 | 0.64 |
| October | 53586505.42 | 0.64 | 20.01 | 01-OCT-00:10 | 0.64 |
| November | 51857908.47 | 0.65 | 20.01 | 01-NOV-00:10 | 0.65 |
| December | 53586505.42 | 0.65 | 20.01 | 01-DEC-00:10 | 0.65 |
| Annual Sum or Average | 0.630938E+09 | 0.64 | |||
| Minimum of Months | 48400714.57 | 0.64 | 20.01 | 0.64 | |
| Maximum of Months | 53586505.42 | 0.65 | 20.01 | 0.65 |
Report: FanReportMonthly
For: T SE APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.65 | 20.01 | 01-JAN-00:10 | 0.65 |
| February | 48400714.57 | 0.65 | 20.01 | 01-FEB-00:10 | 0.65 |
| March | 53586505.42 | 0.65 | 20.01 | 01-MAR-00:10 | 0.65 |
| April | 51857908.47 | 0.64 | 20.01 | 01-APR-00:10 | 0.65 |
| May | 53586505.42 | 0.64 | 20.01 | 01-MAY-00:10 | 0.64 |
| June | 51857908.47 | 0.64 | 20.01 | 01-JUN-00:10 | 0.64 |
| July | 53586505.42 | 0.64 | 20.01 | 01-JUL-00:10 | 0.64 |
| August | 53586505.42 | 0.64 | 20.01 | 01-AUG-00:10 | 0.64 |
| September | 51857908.47 | 0.64 | 20.01 | 01-SEP-00:10 | 0.64 |
| October | 53586505.42 | 0.64 | 20.01 | 01-OCT-00:10 | 0.64 |
| November | 51857908.47 | 0.65 | 20.01 | 01-NOV-00:10 | 0.65 |
| December | 53586505.42 | 0.65 | 20.01 | 01-DEC-00:10 | 0.65 |
| Annual Sum or Average | 0.630938E+09 | 0.64 | |||
| Minimum of Months | 48400714.57 | 0.64 | 20.01 | 0.64 | |
| Maximum of Months | 53586505.42 | 0.65 | 20.01 | 0.65 |
Report: FanReportMonthly
For: SPLIT TNE SUPPLY FAN
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.351391E+09 | 0.94 | 232.25 | 29-JAN-00:10 | 0.94 |
| February | 0.282356E+09 | 0.94 | 200.65 | 25-FEB-01:00 | 0.94 |
| March | 0.239436E+09 | 0.94 | 183.58 | 02-MAR-05:00 | 0.94 |
| April | 0.108112E+09 | 0.74 | 151.76 | 03-APR-03:00 | 0.94 |
| May | 47057955.50 | 0.53 | 128.94 | 31-MAY-11:00 | 1.04 |
| June | 0.137819E+09 | 0.79 | 185.08 | 29-JUN-11:00 | 1.02 |
| July | 0.157850E+09 | 0.78 | 198.35 | 22-JUL-10:50 | 1.01 |
| August | 68400671.23 | 0.53 | 132.66 | 11-AUG-16:15 | 1.04 |
| September | 51065312.96 | 0.63 | 81.40 | 30-SEP-05:00 | 0.94 |
| October | 0.184538E+09 | 0.93 | 153.23 | 27-OCT-04:00 | 0.94 |
| November | 0.319237E+09 | 0.94 | 183.70 | 29-NOV-08:00 | 0.94 |
| December | 0.364624E+09 | 0.94 | 203.78 | 15-DEC-12:00 | 0.94 |
| Annual Sum or Average | 0.231189E+10 | 0.80 | |||
| Minimum of Months | 47057955.50 | 0.53 | 81.40 | 0.94 | |
| Maximum of Months | 0.364624E+09 | 0.94 | 232.25 | 1.04 |
Report: FanReportMonthly
For: T NE APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.65 | 20.01 | 01-JAN-00:10 | 0.65 |
| February | 48400714.57 | 0.65 | 20.01 | 01-FEB-00:10 | 0.65 |
| March | 53586505.42 | 0.65 | 20.01 | 01-MAR-00:10 | 0.65 |
| April | 51857908.47 | 0.64 | 20.01 | 01-APR-00:10 | 0.65 |
| May | 53586505.42 | 0.64 | 20.01 | 01-MAY-00:10 | 0.64 |
| June | 51857908.47 | 0.64 | 20.01 | 01-JUN-00:10 | 0.64 |
| July | 53586505.42 | 0.64 | 20.01 | 01-JUL-00:10 | 0.64 |
| August | 53586505.42 | 0.64 | 20.01 | 01-AUG-00:10 | 0.64 |
| September | 51857908.47 | 0.64 | 20.01 | 01-SEP-00:10 | 0.64 |
| October | 53586505.42 | 0.64 | 20.01 | 01-OCT-00:10 | 0.64 |
| November | 51857908.47 | 0.65 | 20.01 | 01-NOV-00:10 | 0.65 |
| December | 53586505.42 | 0.65 | 20.01 | 01-DEC-00:10 | 0.65 |
| Annual Sum or Average | 0.630938E+09 | 0.64 | |||
| Minimum of Months | 48400714.57 | 0.64 | 20.01 | 0.64 | |
| Maximum of Months | 53586505.42 | 0.65 | 20.01 | 0.65 |
Report: FanReportMonthly
For: T NE APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.65 | 20.01 | 01-JAN-00:10 | 0.65 |
| February | 48400714.57 | 0.65 | 20.01 | 01-FEB-00:10 | 0.65 |
| March | 53586505.42 | 0.65 | 20.01 | 01-MAR-00:10 | 0.65 |
| April | 51857908.47 | 0.64 | 20.01 | 01-APR-00:10 | 0.65 |
| May | 53586505.42 | 0.64 | 20.01 | 01-MAY-00:10 | 0.64 |
| June | 51857908.47 | 0.64 | 20.01 | 01-JUN-00:10 | 0.64 |
| July | 53586505.42 | 0.64 | 20.01 | 01-JUL-00:10 | 0.64 |
| August | 53586505.42 | 0.64 | 20.01 | 01-AUG-00:10 | 0.64 |
| September | 51857908.47 | 0.64 | 20.01 | 01-SEP-00:10 | 0.64 |
| October | 53586505.42 | 0.64 | 20.01 | 01-OCT-00:10 | 0.64 |
| November | 51857908.47 | 0.65 | 20.01 | 01-NOV-00:10 | 0.65 |
| December | 53586505.42 | 0.65 | 20.01 | 01-DEC-00:10 | 0.65 |
| Annual Sum or Average | 0.630938E+09 | 0.64 | |||
| Minimum of Months | 48400714.57 | 0.64 | 20.01 | 0.64 | |
| Maximum of Months | 53586505.42 | 0.65 | 20.01 | 0.65 |
Report: FanReportMonthly
For: SPLIT TN1 SUPPLY FAN
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.266916E+09 | 0.94 | 170.02 | 12-JAN-04:00 | 0.94 |
| February | 0.217418E+09 | 0.94 | 152.95 | 27-FEB-07:00 | 0.94 |
| March | 0.188781E+09 | 0.94 | 138.66 | 02-MAR-05:00 | 0.94 |
| April | 81938237.03 | 0.75 | 113.52 | 03-APR-03:00 | 0.94 |
| May | 18464792.06 | 0.34 | 103.64 | 31-MAY-16:17 | 1.05 |
| June | 96343603.46 | 0.82 | 140.31 | 30-JUN-15:00 | 1.03 |
| July | 0.112126E+09 | 0.81 | 152.35 | 29-JUL-16:40 | 1.03 |
| August | 46513037.45 | 0.50 | 110.33 | 11-AUG-17:40 | 1.05 |
| September | 36743470.38 | 0.61 | 59.17 | 30-SEP-05:00 | 0.93 |
| October | 0.137404E+09 | 0.93 | 113.69 | 27-OCT-04:00 | 0.94 |
| November | 0.245799E+09 | 0.94 | 139.38 | 29-NOV-07:55 | 0.94 |
| December | 0.277903E+09 | 0.94 | 156.27 | 15-DEC-12:00 | 0.94 |
| Annual Sum or Average | 0.172635E+10 | 0.79 | |||
| Minimum of Months | 18464792.06 | 0.34 | 59.17 | 0.93 | |
| Maximum of Months | 0.277903E+09 | 0.94 | 170.02 | 1.05 |
Report: FanReportMonthly
For: T N1 APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.65 | 20.01 | 01-JAN-00:10 | 0.65 |
| February | 48400714.57 | 0.65 | 20.01 | 01-FEB-00:10 | 0.65 |
| March | 53586505.42 | 0.65 | 20.01 | 01-MAR-00:10 | 0.65 |
| April | 51857908.47 | 0.64 | 20.01 | 01-APR-00:10 | 0.65 |
| May | 53586505.42 | 0.64 | 20.01 | 01-MAY-00:10 | 0.64 |
| June | 51857908.47 | 0.64 | 20.01 | 01-JUN-00:10 | 0.64 |
| July | 53586505.42 | 0.64 | 20.01 | 01-JUL-00:10 | 0.64 |
| August | 53586505.42 | 0.64 | 20.01 | 01-AUG-00:10 | 0.64 |
| September | 51857908.47 | 0.64 | 20.01 | 01-SEP-00:10 | 0.64 |
| October | 53586505.42 | 0.64 | 20.01 | 01-OCT-00:10 | 0.64 |
| November | 51857908.47 | 0.65 | 20.01 | 01-NOV-00:10 | 0.65 |
| December | 53586505.42 | 0.65 | 20.01 | 01-DEC-00:10 | 0.65 |
| Annual Sum or Average | 0.630938E+09 | 0.64 | |||
| Minimum of Months | 48400714.57 | 0.64 | 20.01 | 0.64 | |
| Maximum of Months | 53586505.42 | 0.65 | 20.01 | 0.65 |
Report: FanReportMonthly
For: T N1 APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.65 | 20.01 | 01-JAN-00:10 | 0.65 |
| February | 48400714.57 | 0.65 | 20.01 | 01-FEB-00:10 | 0.65 |
| March | 53586505.42 | 0.65 | 20.01 | 01-MAR-00:10 | 0.65 |
| April | 51857908.47 | 0.64 | 20.01 | 01-APR-00:10 | 0.65 |
| May | 53586505.42 | 0.64 | 20.01 | 01-MAY-00:10 | 0.64 |
| June | 51857908.47 | 0.64 | 20.01 | 01-JUN-00:10 | 0.64 |
| July | 53586505.42 | 0.64 | 20.01 | 01-JUL-00:10 | 0.64 |
| August | 53586505.42 | 0.64 | 20.01 | 01-AUG-00:10 | 0.64 |
| September | 51857908.47 | 0.64 | 20.01 | 01-SEP-00:10 | 0.64 |
| October | 53586505.42 | 0.64 | 20.01 | 01-OCT-00:10 | 0.64 |
| November | 51857908.47 | 0.65 | 20.01 | 01-NOV-00:10 | 0.65 |
| December | 53586505.42 | 0.65 | 20.01 | 01-DEC-00:10 | 0.65 |
| Annual Sum or Average | 0.630938E+09 | 0.64 | |||
| Minimum of Months | 48400714.57 | 0.64 | 20.01 | 0.64 | |
| Maximum of Months | 53586505.42 | 0.65 | 20.01 | 0.65 |
Report: FanReportMonthly
For: SPLIT TN2 SUPPLY FAN
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.266485E+09 | 0.94 | 169.77 | 12-JAN-04:00 | 0.94 |
| February | 0.216951E+09 | 0.94 | 152.75 | 27-FEB-07:00 | 0.94 |
| March | 0.188032E+09 | 0.94 | 138.45 | 02-MAR-05:00 | 0.94 |
| April | 81902149.23 | 0.75 | 113.59 | 03-APR-03:00 | 0.94 |
| May | 19304680.84 | 0.36 | 103.41 | 31-MAY-16:17 | 1.05 |
| June | 97289337.38 | 0.82 | 140.62 | 30-JUN-15:00 | 1.03 |
| July | 0.113406E+09 | 0.82 | 152.13 | 29-JUL-16:40 | 1.02 |
| August | 47374156.10 | 0.51 | 109.54 | 11-AUG-17:30 | 1.05 |
| September | 36456464.87 | 0.61 | 59.00 | 30-SEP-05:00 | 0.93 |
| October | 0.136951E+09 | 0.93 | 113.57 | 27-OCT-04:00 | 0.94 |
| November | 0.245442E+09 | 0.94 | 139.19 | 29-NOV-08:00 | 0.94 |
| December | 0.277488E+09 | 0.94 | 156.04 | 15-DEC-12:00 | 0.94 |
| Annual Sum or Average | 0.172708E+10 | 0.79 | |||
| Minimum of Months | 19304680.84 | 0.36 | 59.00 | 0.93 | |
| Maximum of Months | 0.277488E+09 | 0.94 | 169.77 | 1.05 |
Report: FanReportMonthly
For: T N2 APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.65 | 20.01 | 01-JAN-00:10 | 0.65 |
| February | 48400714.57 | 0.65 | 20.01 | 01-FEB-00:10 | 0.65 |
| March | 53586505.42 | 0.65 | 20.01 | 01-MAR-00:10 | 0.65 |
| April | 51857908.47 | 0.64 | 20.01 | 01-APR-00:10 | 0.65 |
| May | 53586505.42 | 0.64 | 20.01 | 01-MAY-00:10 | 0.64 |
| June | 51857908.47 | 0.64 | 20.01 | 01-JUN-00:10 | 0.64 |
| July | 53586505.42 | 0.64 | 20.01 | 01-JUL-00:10 | 0.64 |
| August | 53586505.42 | 0.64 | 20.01 | 01-AUG-00:10 | 0.64 |
| September | 51857908.47 | 0.64 | 20.01 | 01-SEP-00:10 | 0.64 |
| October | 53586505.42 | 0.64 | 20.01 | 01-OCT-00:10 | 0.64 |
| November | 51857908.47 | 0.65 | 20.01 | 01-NOV-00:10 | 0.65 |
| December | 53586505.42 | 0.65 | 20.01 | 01-DEC-00:10 | 0.65 |
| Annual Sum or Average | 0.630938E+09 | 0.64 | |||
| Minimum of Months | 48400714.57 | 0.64 | 20.01 | 0.64 | |
| Maximum of Months | 53586505.42 | 0.65 | 20.01 | 0.65 |
Report: FanReportMonthly
For: T N2 APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.65 | 20.01 | 01-JAN-00:10 | 0.65 |
| February | 48400714.57 | 0.65 | 20.01 | 01-FEB-00:10 | 0.65 |
| March | 53586505.42 | 0.65 | 20.01 | 01-MAR-00:10 | 0.65 |
| April | 51857908.47 | 0.64 | 20.01 | 01-APR-00:10 | 0.65 |
| May | 53586505.42 | 0.64 | 20.01 | 01-MAY-00:10 | 0.64 |
| June | 51857908.47 | 0.64 | 20.01 | 01-JUN-00:10 | 0.64 |
| July | 53586505.42 | 0.64 | 20.01 | 01-JUL-00:10 | 0.64 |
| August | 53586505.42 | 0.64 | 20.01 | 01-AUG-00:10 | 0.64 |
| September | 51857908.47 | 0.64 | 20.01 | 01-SEP-00:10 | 0.64 |
| October | 53586505.42 | 0.64 | 20.01 | 01-OCT-00:10 | 0.64 |
| November | 51857908.47 | 0.65 | 20.01 | 01-NOV-00:10 | 0.65 |
| December | 53586505.42 | 0.65 | 20.01 | 01-DEC-00:10 | 0.65 |
| Annual Sum or Average | 0.630938E+09 | 0.64 | |||
| Minimum of Months | 48400714.57 | 0.64 | 20.01 | 0.64 | |
| Maximum of Months | 53586505.42 | 0.65 | 20.01 | 0.65 |
Report: FanReportMonthly
For: SPLIT TS1 SUPPLY FAN
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.264184E+09 | 0.94 | 174.17 | 12-JAN-04:00 | 0.94 |
| February | 0.192981E+09 | 0.93 | 153.85 | 27-FEB-07:00 | 0.94 |
| March | 0.145696E+09 | 0.84 | 137.59 | 01-MAR-07:00 | 0.94 |
| April | 78061988.26 | 0.67 | 154.23 | 20-APR-14:40 | 1.04 |
| May | 75798797.59 | 0.55 | 198.12 | 31-MAY-15:10 | 1.03 |
| June | 0.139461E+09 | 0.78 | 228.70 | 29-JUN-14:30 | 1.01 |
| July | 0.164120E+09 | 0.79 | 260.58 | 29-JUL-15:30 | 1.00 |
| August | 0.109964E+09 | 0.62 | 232.23 | 11-AUG-15:10 | 1.01 |
| September | 39660111.70 | 0.55 | 136.58 | 09-SEP-15:20 | 1.05 |
| October | 0.115718E+09 | 0.85 | 111.79 | 27-OCT-04:00 | 0.94 |
| November | 0.235812E+09 | 0.94 | 142.75 | 29-NOV-08:00 | 0.94 |
| December | 0.283369E+09 | 0.94 | 157.86 | 15-DEC-10:00 | 0.94 |
| Annual Sum or Average | 0.184483E+10 | 0.78 | |||
| Minimum of Months | 39660111.70 | 0.55 | 111.79 | 0.94 | |
| Maximum of Months | 0.283369E+09 | 0.94 | 260.58 | 1.05 |
Report: FanReportMonthly
For: T S1 APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.65 | 20.01 | 01-JAN-00:10 | 0.65 |
| February | 48400714.57 | 0.65 | 20.01 | 01-FEB-00:10 | 0.65 |
| March | 53586505.42 | 0.65 | 20.01 | 01-MAR-00:10 | 0.65 |
| April | 51857908.47 | 0.64 | 20.01 | 01-APR-00:10 | 0.65 |
| May | 53586505.42 | 0.64 | 20.01 | 01-MAY-00:10 | 0.64 |
| June | 51857908.47 | 0.64 | 20.01 | 01-JUN-00:10 | 0.64 |
| July | 53586505.42 | 0.64 | 20.01 | 01-JUL-00:10 | 0.64 |
| August | 53586505.42 | 0.64 | 20.01 | 01-AUG-00:10 | 0.64 |
| September | 51857908.47 | 0.64 | 20.01 | 01-SEP-00:10 | 0.64 |
| October | 53586505.42 | 0.64 | 20.01 | 01-OCT-00:10 | 0.64 |
| November | 51857908.47 | 0.65 | 20.01 | 01-NOV-00:10 | 0.65 |
| December | 53586505.42 | 0.65 | 20.01 | 01-DEC-00:10 | 0.65 |
| Annual Sum or Average | 0.630938E+09 | 0.64 | |||
| Minimum of Months | 48400714.57 | 0.64 | 20.01 | 0.64 | |
| Maximum of Months | 53586505.42 | 0.65 | 20.01 | 0.65 |
Report: FanReportMonthly
For: T S1 APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.65 | 20.01 | 01-JAN-00:10 | 0.65 |
| February | 48400714.57 | 0.65 | 20.01 | 01-FEB-00:10 | 0.65 |
| March | 53586505.42 | 0.65 | 20.01 | 01-MAR-00:10 | 0.65 |
| April | 51857908.47 | 0.64 | 20.01 | 01-APR-00:10 | 0.65 |
| May | 53586505.42 | 0.64 | 20.01 | 01-MAY-00:10 | 0.64 |
| June | 51857908.47 | 0.64 | 20.01 | 01-JUN-00:10 | 0.64 |
| July | 53586505.42 | 0.64 | 20.01 | 01-JUL-00:10 | 0.64 |
| August | 53586505.42 | 0.64 | 20.01 | 01-AUG-00:10 | 0.64 |
| September | 51857908.47 | 0.64 | 20.01 | 01-SEP-00:10 | 0.64 |
| October | 53586505.42 | 0.64 | 20.01 | 01-OCT-00:10 | 0.64 |
| November | 51857908.47 | 0.65 | 20.01 | 01-NOV-00:10 | 0.65 |
| December | 53586505.42 | 0.65 | 20.01 | 01-DEC-00:10 | 0.65 |
| Annual Sum or Average | 0.630938E+09 | 0.64 | |||
| Minimum of Months | 48400714.57 | 0.64 | 20.01 | 0.64 | |
| Maximum of Months | 53586505.42 | 0.65 | 20.01 | 0.65 |
Report: FanReportMonthly
For: SPLIT TS2 SUPPLY FAN
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.263862E+09 | 0.94 | 173.98 | 12-JAN-04:00 | 0.94 |
| February | 0.192616E+09 | 0.93 | 153.71 | 27-FEB-07:00 | 0.94 |
| March | 0.145105E+09 | 0.84 | 137.45 | 01-MAR-07:00 | 0.94 |
| April | 78581626.70 | 0.68 | 155.71 | 22-APR-14:00 | 1.04 |
| May | 77693485.67 | 0.56 | 198.65 | 31-MAY-15:10 | 1.03 |
| June | 0.140551E+09 | 0.78 | 229.63 | 29-JUN-14:30 | 1.01 |
| July | 0.165426E+09 | 0.80 | 260.86 | 29-JUL-15:30 | 1.00 |
| August | 0.111058E+09 | 0.63 | 232.75 | 11-AUG-15:10 | 1.01 |
| September | 39987381.63 | 0.55 | 137.67 | 09-SEP-15:20 | 1.05 |
| October | 0.115393E+09 | 0.85 | 111.66 | 27-OCT-04:00 | 0.94 |
| November | 0.235566E+09 | 0.94 | 142.59 | 29-NOV-07:55 | 0.94 |
| December | 0.283061E+09 | 0.94 | 157.71 | 15-DEC-10:00 | 0.94 |
| Annual Sum or Average | 0.184890E+10 | 0.79 | |||
| Minimum of Months | 39987381.63 | 0.55 | 111.66 | 0.94 | |
| Maximum of Months | 0.283061E+09 | 0.94 | 260.86 | 1.05 |
Report: FanReportMonthly
For: T S2 APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.65 | 20.01 | 01-JAN-00:10 | 0.65 |
| February | 48400714.57 | 0.65 | 20.01 | 01-FEB-00:10 | 0.65 |
| March | 53586505.42 | 0.65 | 20.01 | 01-MAR-00:10 | 0.65 |
| April | 51857908.47 | 0.64 | 20.01 | 01-APR-00:10 | 0.65 |
| May | 53586505.42 | 0.64 | 20.01 | 01-MAY-00:10 | 0.64 |
| June | 51857908.47 | 0.64 | 20.01 | 01-JUN-00:10 | 0.64 |
| July | 53586505.42 | 0.64 | 20.01 | 01-JUL-00:10 | 0.64 |
| August | 53586505.42 | 0.64 | 20.01 | 01-AUG-00:10 | 0.64 |
| September | 51857908.47 | 0.64 | 20.01 | 01-SEP-00:10 | 0.64 |
| October | 53586505.42 | 0.64 | 20.01 | 01-OCT-00:10 | 0.64 |
| November | 51857908.47 | 0.65 | 20.01 | 01-NOV-00:10 | 0.65 |
| December | 53586505.42 | 0.65 | 20.01 | 01-DEC-00:10 | 0.65 |
| Annual Sum or Average | 0.630938E+09 | 0.64 | |||
| Minimum of Months | 48400714.57 | 0.64 | 20.01 | 0.64 | |
| Maximum of Months | 53586505.42 | 0.65 | 20.01 | 0.65 |
Report: FanReportMonthly
For: T S2 APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.65 | 20.01 | 01-JAN-00:10 | 0.65 |
| February | 48400714.57 | 0.65 | 20.01 | 01-FEB-00:10 | 0.65 |
| March | 53586505.42 | 0.65 | 20.01 | 01-MAR-00:10 | 0.65 |
| April | 51857908.47 | 0.64 | 20.01 | 01-APR-00:10 | 0.65 |
| May | 53586505.42 | 0.64 | 20.01 | 01-MAY-00:10 | 0.64 |
| June | 51857908.47 | 0.64 | 20.01 | 01-JUN-00:10 | 0.64 |
| July | 53586505.42 | 0.64 | 20.01 | 01-JUL-00:10 | 0.64 |
| August | 53586505.42 | 0.64 | 20.01 | 01-AUG-00:10 | 0.64 |
| September | 51857908.47 | 0.64 | 20.01 | 01-SEP-00:10 | 0.64 |
| October | 53586505.42 | 0.64 | 20.01 | 01-OCT-00:10 | 0.64 |
| November | 51857908.47 | 0.65 | 20.01 | 01-NOV-00:10 | 0.65 |
| December | 53586505.42 | 0.65 | 20.01 | 01-DEC-00:10 | 0.65 |
| Annual Sum or Average | 0.630938E+09 | 0.64 | |||
| Minimum of Months | 48400714.57 | 0.64 | 20.01 | 0.64 | |
| Maximum of Months | 53586505.42 | 0.65 | 20.01 | 0.65 |
Report: ZoneTemperatureOscillationReportMonthly
For: G SW APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: G NW APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: OFFICE
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: G NE APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: G N1 APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: G N2 APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: G S1 APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: G S2 APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: M SW APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: M NW APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: M SE APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: M NE APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: M N1 APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: M N2 APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: M S1 APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: M S2 APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: T SW APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: T NW APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: T SE APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: T NE APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: T N1 APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: T N2 APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: T S1 APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: T S2 APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: T CORRIDOR
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: G CORRIDOR
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: M CORRIDOR
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT GSW
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.294587E+09 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.237220E+09 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.195218E+09 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 71755438.14 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 37986162.38 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.308713E+09 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.507742E+09 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.377461E+09 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 30809167.61 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.113945E+09 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.242175E+09 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.301605E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.271922E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 30809167.61 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.507742E+09 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT GNW
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.293669E+09 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.256097E+09 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.232796E+09 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.110686E+09 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 17445293.17 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.173784E+09 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.319882E+09 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.147966E+09 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 28752559.50 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.134755E+09 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.249203E+09 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.294207E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.225924E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 17445293.17 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.319882E+09 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT OFFICE
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.122932E+10 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.111035E+10 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.122932E+10 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.119118E+10 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.134325E+10 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.150876E+10 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.161022E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.156994E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.123661E+10 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.122932E+10 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.118966E+10 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.122932E+10 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.156773E+11 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.111035E+10 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.161022E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT GNE
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.284829E+09 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.245896E+09 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.217547E+09 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.107397E+09 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 12212445.50 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.216882E+09 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.409011E+09 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.189527E+09 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 24647928.33 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.126642E+09 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.242426E+09 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.286062E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.236308E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 12212445.50 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.409011E+09 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT GN1
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.211674E+09 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.183396E+09 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.166495E+09 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 80380363.89 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 8170934.15 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.159127E+09 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.307507E+09 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.140297E+09 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 16367095.42 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 93372935.24 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.183781E+09 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.214566E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.176514E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 8170934.15 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.307507E+09 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT GN2
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.211534E+09 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.183174E+09 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.166029E+09 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 80363576.82 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 7753060.60 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.163168E+09 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.313070E+09 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.143717E+09 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 16138522.74 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 93089643.60 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.183683E+09 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.214451E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.177617E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 7753060.60 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.313070E+09 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT GS1
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.214969E+09 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.167254E+09 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.132607E+09 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 44282993.03 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 42208164.83 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.309841E+09 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.508339E+09 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.397273E+09 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 39033395.76 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 74908692.06 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.179281E+09 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.224164E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.233416E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 39033395.76 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.508339E+09 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT GS2
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.228898E+09 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.178725E+09 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.143088E+09 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 49098398.45 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 53919266.42 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.351436E+09 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.573003E+09 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.450279E+09 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 47921292.95 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 81366034.15 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.191904E+09 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.237599E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.258724E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 47921292.95 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.573003E+09 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT MSW
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.479601E+09 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.342346E+09 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.248247E+09 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.255965E+09 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.814362E+09 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.154869E+10 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.172234E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.120293E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.211376E+09 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.192722E+09 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.413362E+09 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.514344E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.794628E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.192722E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.172234E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT MNW
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.489353E+09 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.392611E+09 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.335883E+09 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.119969E+09 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.282606E+09 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.120852E+10 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.130030E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.630272E+09 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 36098403.92 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.240638E+09 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.437231E+09 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.509242E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.598272E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 36098403.92 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.130030E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT MSE
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.466530E+09 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.327499E+09 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.224134E+09 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.242472E+09 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.103202E+10 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.167948E+10 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.191681E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.133160E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.256008E+09 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.179695E+09 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.403827E+09 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.502027E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.856210E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.179695E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.191681E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT MNE
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.472577E+09 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.373805E+09 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.307038E+09 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.113995E+09 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.467738E+09 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.134154E+10 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.149866E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.745139E+09 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 31254566.19 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.223794E+09 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.424019E+09 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.493407E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.649297E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 31254566.19 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.149866E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT MN1
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.333280E+09 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.268399E+09 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.229460E+09 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 79496119.06 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.218318E+09 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.976782E+09 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.110635E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.566630E+09 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 18755409.69 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.151318E+09 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.302312E+09 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.349348E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.460045E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 18755409.69 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.110635E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT MN2
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.333031E+09 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.267986E+09 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.228462E+09 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 79553807.18 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.229057E+09 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.982649E+09 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.111472E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.573044E+09 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 18585332.31 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.150774E+09 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.302146E+09 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.349145E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.462915E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 18585332.31 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.111472E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT MS1
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.326928E+09 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.223955E+09 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.149023E+09 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.202383E+09 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.772833E+09 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.131919E+10 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.153044E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.116187E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.262671E+09 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.110965E+09 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.282443E+09 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.356964E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.669967E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.110965E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.153044E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT MS2
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.326715E+09 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.223557E+09 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.148010E+09 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.204280E+09 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.785676E+09 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.132517E+10 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.153858E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.116891E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.268583E+09 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.110497E+09 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.282315E+09 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.356796E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.673908E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.110497E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.153858E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT TSW
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.361871E+09 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.270466E+09 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.213225E+09 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.220275E+09 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.361532E+09 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.707758E+09 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.801080E+09 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.509900E+09 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.115622E+09 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.173474E+09 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.319688E+09 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.383186E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.443808E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.115622E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.801080E+09 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT TNW
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.366987E+09 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.297915E+09 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.260251E+09 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.121703E+09 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.116932E+09 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.521175E+09 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.577463E+09 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.240866E+09 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 58275084.58 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.197534E+09 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.332287E+09 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.379879E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.347127E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 58275084.58 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.577463E+09 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT TSE
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.349680E+09 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.258407E+09 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.196993E+09 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.200927E+09 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.434728E+09 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.762204E+09 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.891003E+09 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.554307E+09 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.118208E+09 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.164032E+09 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.309983E+09 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.371201E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.461167E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.118208E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.891003E+09 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT TNE
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.351391E+09 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.282356E+09 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.239436E+09 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.108220E+09 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.161636E+09 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.585599E+09 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.675523E+09 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.278748E+09 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 51065312.96 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.184538E+09 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.319237E+09 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.364624E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.360237E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 51065312.96 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.675523E+09 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT TN1
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.266916E+09 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.217418E+09 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.188781E+09 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 81938237.03 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 57133780.28 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.409846E+09 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.480229E+09 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.188914E+09 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 36743470.38 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.137404E+09 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.245799E+09 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.277903E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.258903E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 36743470.38 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.480229E+09 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT TN2
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.266485E+09 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.216951E+09 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.188032E+09 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 81902149.23 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 61144257.75 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.413849E+09 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.485700E+09 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.192790E+09 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 36456464.87 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.136951E+09 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.245442E+09 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.277488E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.260319E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 36456464.87 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.485700E+09 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT TS1
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.264184E+09 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.192981E+09 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.145823E+09 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.158570E+09 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.303861E+09 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.592661E+09 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.702723E+09 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.463272E+09 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 93291982.02 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.117107E+09 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.235812E+09 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.283369E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.355366E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 93291982.02 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.702723E+09 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT TS2
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.263862E+09 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.192616E+09 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.145303E+09 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.160530E+09 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.311978E+09 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.597273E+09 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.708303E+09 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.467989E+09 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 95151564.02 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.116897E+09 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.235566E+09 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.283061E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.357853E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 95151564.02 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.708303E+09 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT GSW
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 0.294587E+09 | 0.00 | 0.723545E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.237220E+09 | 0.00 | 0.582644E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.195218E+09 | 0.00 | 0.479483E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 70925326.78 | 3106947.16 | 0.173563E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 14937041.94 | 87085144.88 | 0.189869E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 72590072.94 | 0.913223E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.118541E+09 | 0.152377E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 88557317.57 | 0.113189E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 19043394.12 | 44781883.61 | 0.378288E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.113945E+09 | 0.00 | 0.279863E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.242175E+09 | 0.00 | 0.594815E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.301605E+09 | 0.00 | 0.740784E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.176934E+10 | 0.370386E+10 | 0.363151E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 14937041.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.301605E+09 | 0.152377E+10 | 0.740784E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT GNW
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 0.293669E+09 | 0.00 | 0.750315E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.256097E+09 | 0.00 | 0.654322E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.232796E+09 | 0.00 | 0.594786E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.110686E+09 | 0.00 | 0.282801E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 17432759.57 | 46944.89 | 0.445302E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 40802636.09 | 0.513538E+09 | 35759.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 74661373.27 | 0.955689E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 34895335.67 | 0.440216E+09 | 7682462.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 28752559.50 | 0.00 | 0.734620E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.134755E+09 | 0.00 | 0.344296E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.249203E+09 | 0.00 | 0.636708E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.294207E+09 | 0.00 | 0.751692E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.176796E+10 | 0.190949E+10 | 0.413368E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 17432759.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.294207E+09 | 0.955689E+09 | 0.751692E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT OFFICE
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 0.122932E+10 | 0.00 | 0.588802E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.111035E+10 | 0.00 | 0.439824E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.122932E+10 | 0.00 | 0.293819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.118966E+10 | 5678279.49 | 0.623771E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.122932E+10 | 0.438268E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.118966E+10 | 0.127326E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.122932E+10 | 0.154978E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.122932E+10 | 0.137148E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.118966E+10 | 0.179683E+09 | 42635168.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.122932E+10 | 0.00 | 0.133738E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.118966E+10 | 0.00 | 0.461395E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.122932E+10 | 0.00 | 0.599177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.144742E+11 | 0.481815E+10 | 0.258340E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 0.111035E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.122932E+10 | 0.154978E+10 | 0.599177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT GNE
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 0.284829E+09 | 0.00 | 0.748892E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.245896E+09 | 0.00 | 0.646528E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.217547E+09 | 0.00 | 0.571990E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.107397E+09 | 0.00 | 0.282374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 12128635.59 | 313456.57 | 0.318205E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 50988754.75 | 0.641417E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 95507794.68 | 0.123140E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 44472694.52 | 0.566135E+09 | 1926801.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 24647928.33 | 0.00 | 0.648060E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.126642E+09 | 0.00 | 0.332977E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.242426E+09 | 0.00 | 0.637402E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.286062E+09 | 0.00 | 0.752133E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.173855E+10 | 0.243927E+10 | 0.406911E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 12128635.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.286062E+09 | 0.123140E+10 | 0.752133E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT GN1
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 0.211674E+09 | 0.00 | 0.572108E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.183396E+09 | 0.00 | 0.495679E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.166495E+09 | 0.00 | 0.450000E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 80380363.89 | 0.00 | 0.217250E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 8170934.15 | 0.00 | 0.220842E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 37365164.82 | 0.470156E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 71762621.64 | 0.921216E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 32853093.13 | 0.418563E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 16367095.42 | 0.00 | 0.442367E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 93372935.24 | 0.00 | 0.252366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.183781E+09 | 0.00 | 0.496720E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.214566E+09 | 0.00 | 0.579925E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.130018E+10 | 0.180994E+10 | 0.313037E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 8170934.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.214566E+09 | 0.921216E+09 | 0.579925E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT GN2
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 0.211534E+09 | 0.00 | 0.572034E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.183174E+09 | 0.00 | 0.495342E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.166029E+09 | 0.00 | 0.448979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 80363576.82 | 0.00 | 0.217321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 7753060.60 | 0.00 | 0.209660E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 38320896.67 | 0.482009E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 73062375.72 | 0.938213E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 33655148.95 | 0.428792E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 16138522.74 | 0.00 | 0.436422E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 93089643.60 | 0.00 | 0.251735E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.183683E+09 | 0.00 | 0.496720E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.214451E+09 | 0.00 | 0.579922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.130125E+10 | 0.184901E+10 | 0.312666E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 7753060.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.214451E+09 | 0.938213E+09 | 0.579922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT GS1
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 0.214969E+09 | 0.00 | 0.546737E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.167254E+09 | 0.00 | 0.425383E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.132607E+09 | 0.00 | 0.337264E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 43921398.29 | 1353845.24 | 0.111419E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 11730135.05 | 0.115461E+09 | 56012802.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 72865714.79 | 0.917062E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.118676E+09 | 0.152957E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 93200985.05 | 0.119217E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 15240070.42 | 90647390.44 | 0.200226E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 74908692.06 | 0.00 | 0.190518E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.179281E+09 | 0.00 | 0.455972E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.224164E+09 | 0.00 | 0.570123E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.134882E+10 | 0.384626E+10 | 0.266304E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 11730135.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.224164E+09 | 0.152957E+10 | 0.570123E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT GS2
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 0.228898E+09 | 0.00 | 0.581476E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.178725E+09 | 0.00 | 0.454018E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.143088E+09 | 0.00 | 0.363489E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 48793714.34 | 1140158.57 | 0.123709E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 14343087.36 | 0.150136E+09 | 50101233.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 82658803.42 | 0.104138E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.133789E+09 | 0.172769E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.105637E+09 | 0.135274E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 17496607.98 | 0.116009E+09 | 0.205109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 81366034.15 | 0.00 | 0.206696E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.191904E+09 | 0.00 | 0.487498E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.237599E+09 | 0.00 | 0.603579E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.146430E+10 | 0.438909E+10 | 0.284599E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 14343087.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.237599E+09 | 0.172769E+10 | 0.603579E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT MSW
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 0.479601E+09 | 0.00 | 0.113457E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.342346E+09 | 0.00 | 0.809875E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.248247E+09 | 0.00 | 0.587270E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.107106E+09 | 0.568471E+09 | 0.142930E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.194193E+09 | 0.237958E+10 | 13086672.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.364436E+09 | 0.461464E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.402371E+09 | 0.518780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.282398E+09 | 0.360989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 65557407.16 | 0.558250E+09 | 0.481450E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.192722E+09 | 0.00 | 0.455915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.413362E+09 | 0.00 | 0.977875E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.514344E+09 | 0.00 | 0.121676E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.360668E+10 | 0.169186E+11 | 0.537466E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 65557407.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.514344E+09 | 0.518780E+10 | 0.121676E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT MNW
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 0.489353E+09 | 0.00 | 0.118662E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.392611E+09 | 0.00 | 0.952031E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.335883E+09 | 0.00 | 0.814473E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.118418E+09 | 5802605.80 | 0.285969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 68158384.41 | 0.815830E+09 | 29734927.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.284217E+09 | 0.359151E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.303726E+09 | 0.390064E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.147868E+09 | 0.187895E+10 | 3883813.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 35848602.12 | 944715.79 | 0.867410E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.240638E+09 | 0.00 | 0.583518E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.437231E+09 | 0.00 | 0.106023E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.509242E+09 | 0.00 | 0.123485E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.336319E+10 | 0.101937E+11 | 0.620779E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 35848602.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.509242E+09 | 0.390064E+10 | 0.123485E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT MSE
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 0.466530E+09 | 0.00 | 0.113117E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.327499E+09 | 0.00 | 0.794072E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.224134E+09 | 0.00 | 0.543447E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.102690E+09 | 0.534768E+09 | 0.142710E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.245835E+09 | 0.303786E+10 | 9073566.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.395327E+09 | 0.502999E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.447965E+09 | 0.581941E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.312663E+09 | 0.401757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 73790735.58 | 0.699777E+09 | 0.419197E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.179695E+09 | 0.00 | 0.435699E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.403827E+09 | 0.00 | 0.979142E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.502027E+09 | 0.00 | 0.121724E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.368198E+10 | 0.191394E+11 | 0.528631E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 73790735.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.502027E+09 | 0.581941E+10 | 0.121724E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT MNE
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 0.472577E+09 | 0.00 | 0.118351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.373805E+09 | 0.00 | 0.936149E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.307038E+09 | 0.00 | 0.768939E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.113995E+09 | 0.00 | 0.285485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.111810E+09 | 0.136069E+10 | 18090217.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.315635E+09 | 0.400876E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.350213E+09 | 0.453396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.174696E+09 | 0.223079E+10 | 145925.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 31135994.51 | 449771.42 | 0.778848E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.223794E+09 | 0.00 | 0.560465E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.424019E+09 | 0.00 | 0.106190E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.493407E+09 | 0.00 | 0.123568E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.339213E+10 | 0.121346E+11 | 0.611184E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 31135994.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.493407E+09 | 0.453396E+10 | 0.123568E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT MN1
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 0.333280E+09 | 0.00 | 0.854485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.268399E+09 | 0.00 | 0.688140E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.229460E+09 | 0.00 | 0.588304E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 79496119.06 | 0.00 | 0.203817E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 51923754.28 | 0.631129E+09 | 232629.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.229664E+09 | 0.290128E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.258391E+09 | 0.332374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.132755E+09 | 0.168995E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 18755409.69 | 0.00 | 0.480864E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.151318E+09 | 0.00 | 0.387958E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.302312E+09 | 0.00 | 0.775089E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.349348E+09 | 0.00 | 0.895681E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.240510E+10 | 0.854610E+10 | 0.444158E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 18755409.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.349348E+09 | 0.332374E+10 | 0.895681E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT MN2
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 0.333031E+09 | 0.00 | 0.854336E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.267986E+09 | 0.00 | 0.687473E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.228462E+09 | 0.00 | 0.586081E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 79553807.18 | 0.00 | 0.204082E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 54477155.51 | 0.662279E+09 | 191267.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.231050E+09 | 0.291897E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.260349E+09 | 0.334966E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.134260E+09 | 0.170922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 18581189.41 | 15632.28 | 0.476637E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.150774E+09 | 0.00 | 0.386785E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.302146E+09 | 0.00 | 0.775105E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.349145E+09 | 0.00 | 0.895674E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.240981E+10 | 0.864015E+10 | 0.443722E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 18581189.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.349145E+09 | 0.334966E+10 | 0.895674E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT MS1
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 0.326928E+09 | 0.00 | 0.803741E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.223955E+09 | 0.00 | 0.550585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.149023E+09 | 0.00 | 0.366367E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 70911309.62 | 0.502393E+09 | 0.729960E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.183858E+09 | 0.226228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.310393E+09 | 0.393011E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.357503E+09 | 0.461868E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.272730E+09 | 0.349145E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 67642478.77 | 0.748887E+09 | 0.176871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.110965E+09 | 0.00 | 0.272804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.282443E+09 | 0.00 | 0.694375E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.356964E+09 | 0.00 | 0.877584E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.271332E+10 | 0.155538E+11 | 0.365614E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 67642478.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.357503E+09 | 0.461868E+10 | 0.877584E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT MS2
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 0.326715E+09 | 0.00 | 0.803587E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.223557E+09 | 0.00 | 0.549861E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.148010E+09 | 0.00 | 0.364044E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 71411926.57 | 0.507757E+09 | 0.731829E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.186913E+09 | 0.230053E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.311806E+09 | 0.394846E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.359408E+09 | 0.464431E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.274387E+09 | 0.351312E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 68964887.70 | 0.766712E+09 | 0.174502E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.110497E+09 | 0.00 | 0.271779E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.282315E+09 | 0.00 | 0.694381E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.356796E+09 | 0.00 | 0.877573E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.272078E+10 | 0.156809E+11 | 0.365186E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 68964887.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.359408E+09 | 0.464431E+10 | 0.877573E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT TSW
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 0.361871E+09 | 0.00 | 0.846014E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.270466E+09 | 0.00 | 0.632317E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.213098E+09 | 474252.28 | 0.498105E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.115908E+09 | 0.399648E+09 | 0.194379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 94607870.89 | 0.102786E+10 | 0.262467E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.166636E+09 | 0.211994E+10 | 2387620.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.187125E+09 | 0.242527E+10 | 466036.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.122520E+09 | 0.152804E+10 | 84380936.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 59000158.25 | 0.217503E+09 | 0.968620E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.172732E+09 | 2798510.98 | 0.403287E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.319688E+09 | 0.00 | 0.747393E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.383186E+09 | 0.00 | 0.895845E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.246684E+10 | 0.772153E+10 | 0.434917E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 59000158.25 | 0.00 | 466036.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.383186E+09 | 0.242527E+10 | 0.895845E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT TNW
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 0.366987E+09 | 0.00 | 0.875017E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.297915E+09 | 0.00 | 0.710327E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.260251E+09 | 0.00 | 0.620523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.115761E+09 | 22393702.06 | 0.271568E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 38010004.69 | 0.301016E+09 | 0.318857E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.122646E+09 | 0.155319E+10 | 3077951.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.134848E+09 | 0.173498E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 60662237.21 | 0.703623E+09 | 0.130308E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 58019943.76 | 964923.47 | 0.138150E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.197534E+09 | 0.00 | 0.470985E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.332287E+09 | 0.00 | 0.792280E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.379879E+09 | 0.00 | 0.905757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.236480E+10 | 0.431617E+10 | 0.482983E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 38010004.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.379879E+09 | 0.173498E+10 | 0.905757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT TSE
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 0.349680E+09 | 0.00 | 0.844670E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.258407E+09 | 0.00 | 0.624195E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.196538E+09 | 1704068.65 | 0.474403E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.108410E+09 | 0.355358E+09 | 0.191711E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.110495E+09 | 0.125918E+10 | 0.222533E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.179480E+09 | 0.229930E+10 | 1617635.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.208216E+09 | 0.272785E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.132240E+09 | 0.167909E+10 | 64431444.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 56197215.96 | 0.238649E+09 | 0.892499E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.162760E+09 | 4816968.30 | 0.392197E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.309983E+09 | 0.00 | 0.748779E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.371201E+09 | 0.00 | 0.896653E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.244361E+10 | 0.856595E+10 | 0.429072E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 56197215.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.371201E+09 | 0.272785E+10 | 0.896653E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT TNE
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 0.351391E+09 | 0.00 | 0.873979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.282356E+09 | 0.00 | 0.702273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.239436E+09 | 0.00 | 0.595524E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.108112E+09 | 401408.02 | 0.268813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 47057955.50 | 0.438258E+09 | 0.280792E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.137819E+09 | 0.175540E+10 | 1811973.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.157850E+09 | 0.205088E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 68400671.23 | 0.824835E+09 | 98669321.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 51065312.96 | 0.00 | 0.127009E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.184538E+09 | 0.00 | 0.458982E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.319237E+09 | 0.00 | 0.794005E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.364624E+09 | 0.00 | 0.906891E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.231189E+10 | 0.506978E+10 | 0.476560E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 47057955.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.364624E+09 | 0.205088E+10 | 0.906891E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT TN1
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 0.266916E+09 | 0.00 | 0.671967E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.217418E+09 | 0.00 | 0.547355E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.188781E+09 | 0.00 | 0.475260E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 81938237.03 | 0.00 | 0.206281E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 18464792.06 | 0.147075E+09 | 0.161189E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 96343603.46 | 0.121912E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.112126E+09 | 0.144369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 46513037.45 | 0.555736E+09 | 73984037.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 36743470.38 | 0.00 | 0.925026E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.137404E+09 | 0.00 | 0.345918E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.245799E+09 | 0.00 | 0.618806E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.277903E+09 | 0.00 | 0.699628E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.172635E+10 | 0.336563E+10 | 0.368123E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 18464792.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.277903E+09 | 0.144369E+10 | 0.699628E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT TN2
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 0.266485E+09 | 0.00 | 0.671912E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.216951E+09 | 0.00 | 0.547017E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.188032E+09 | 0.00 | 0.474101E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 81902149.23 | 0.00 | 0.206507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 19304680.84 | 0.159122E+09 | 0.157646E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 97289337.38 | 0.123118E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.113406E+09 | 0.146070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 47374156.10 | 0.567600E+09 | 72507317.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 36456464.87 | 0.00 | 0.919209E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.136951E+09 | 0.00 | 0.345307E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.245442E+09 | 0.00 | 0.618855E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.277488E+09 | 0.00 | 0.699655E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.172708E+10 | 0.341860E+10 | 0.367829E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 19304680.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.277488E+09 | 0.146070E+10 | 0.699655E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT TS1
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 0.264184E+09 | 0.00 | 0.642815E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.192981E+09 | 0.00 | 0.469564E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.145696E+09 | 475832.66 | 0.354412E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 78061988.26 | 0.308249E+09 | 0.128443E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 75798797.59 | 0.879101E+09 | 0.111070E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.139461E+09 | 0.177637E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.164120E+09 | 0.213421E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.109964E+09 | 0.139784E+10 | 37671717.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 39660111.70 | 0.206126E+09 | 0.560062E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.115718E+09 | 5264220.39 | 0.280514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.235812E+09 | 0.00 | 0.573780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.283369E+09 | 0.00 | 0.689495E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.184483E+10 | 0.670764E+10 | 0.320990E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 39660111.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.283369E+09 | 0.213421E+10 | 0.689495E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT TS2
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 0.263862E+09 | 0.00 | 0.642746E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.192616E+09 | 0.00 | 0.469196E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.145105E+09 | 741777.06 | 0.353312E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 78581626.70 | 0.313880E+09 | 0.128749E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 77693485.67 | 0.903609E+09 | 0.110003E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.140551E+09 | 0.179076E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.165426E+09 | 0.215219E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.111058E+09 | 0.141274E+10 | 37198107.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 39987381.63 | 0.212072E+09 | 0.557054E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.115393E+09 | 5702773.90 | 0.279947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.235566E+09 | 0.00 | 0.573818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.283061E+09 | 0.00 | 0.689512E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.184890E+10 | 0.679169E+10 | 0.320771E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 39987381.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.283061E+09 | 0.215219E+10 | 0.689512E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT GSW
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 0.294587E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.237220E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.195218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 70925326.78 | 0.00 | 0.00 | 0.00 | 830111.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 14937041.94 | 0.00 | 0.00 | 0.00 | 23049120.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 72590072.94 | 0.00 | 0.00 | 0.00 | 0.236123E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.118541E+09 | 0.00 | 0.00 | 0.00 | 0.389200E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 88557317.57 | 0.00 | 0.00 | 0.00 | 0.288904E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 19043394.12 | 0.00 | 0.00 | 0.00 | 11765773.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.113945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.242175E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.301605E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.176934E+10 | 0.00 | 0.00 | 0.00 | 0.949872E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 14937041.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.301605E+09 | 0.00 | 0.00 | 0.00 | 0.389200E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT GNW
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 0.293669E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.256097E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.232796E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.110686E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 17432759.57 | 0.00 | 0.00 | 0.00 | 12533.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 40802636.09 | 0.00 | 0.00 | 0.00 | 0.132982E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 74661373.27 | 0.00 | 0.00 | 0.00 | 0.245221E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 34895335.67 | 0.00 | 0.00 | 0.00 | 0.113070E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 28752559.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.134755E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.249203E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.294207E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.176796E+10 | 0.00 | 0.00 | 0.00 | 0.491285E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 17432759.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.294207E+09 | 0.00 | 0.00 | 0.00 | 0.245221E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT OFFICE
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 0.122932E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.111035E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.122932E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.118966E+10 | 0.00 | 0.00 | 0.00 | 1519732.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.122932E+10 | 0.00 | 0.00 | 0.00 | 0.113931E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.118966E+10 | 0.00 | 0.00 | 0.00 | 0.319099E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.122932E+10 | 0.00 | 0.00 | 0.00 | 0.380900E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.122932E+10 | 0.00 | 0.00 | 0.00 | 0.340622E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.118966E+10 | 0.00 | 0.00 | 0.00 | 46947571.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.122932E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.118966E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.122932E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.144742E+11 | 0.00 | 0.00 | 0.00 | 0.120302E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 0.111035E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.122932E+10 | 0.00 | 0.00 | 0.00 | 0.380900E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT GNE
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 0.284829E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.245896E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.217547E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.107397E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 12128635.59 | 0.00 | 0.00 | 0.00 | 83809.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 50988754.75 | 0.00 | 0.00 | 0.00 | 0.165894E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 95507794.68 | 0.00 | 0.00 | 0.00 | 0.313503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 44472694.52 | 0.00 | 0.00 | 0.00 | 0.145054E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 24647928.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.126642E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.242426E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.286062E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.173855E+10 | 0.00 | 0.00 | 0.00 | 0.624535E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 12128635.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.286062E+09 | 0.00 | 0.00 | 0.00 | 0.313503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT GN1
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 0.211674E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.183396E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.166495E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 80380363.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 8170934.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 37365164.82 | 0.00 | 0.00 | 0.00 | 0.121762E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 71762621.64 | 0.00 | 0.00 | 0.00 | 0.235744E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 32853093.13 | 0.00 | 0.00 | 0.00 | 0.107444E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 16367095.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 93372935.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.183781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.214566E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.130018E+10 | 0.00 | 0.00 | 0.00 | 0.464951E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 8170934.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.214566E+09 | 0.00 | 0.00 | 0.00 | 0.235744E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT GN2
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 0.211534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.183174E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.166029E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 80363576.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 7753060.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 38320896.67 | 0.00 | 0.00 | 0.00 | 0.124847E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 73062375.72 | 0.00 | 0.00 | 0.00 | 0.240008E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 33655148.95 | 0.00 | 0.00 | 0.00 | 0.110062E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 16138522.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 93089643.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.183683E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.214451E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.130125E+10 | 0.00 | 0.00 | 0.00 | 0.474917E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 7753060.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.214451E+09 | 0.00 | 0.00 | 0.00 | 0.240008E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT GS1
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 0.214969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.167254E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.132607E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 43921398.29 | 0.00 | 0.00 | 0.00 | 361594.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 11730135.05 | 0.00 | 0.00 | 0.00 | 30478029.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 72865714.79 | 0.00 | 0.00 | 0.00 | 0.236975E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.118676E+09 | 0.00 | 0.00 | 0.00 | 0.389663E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 93200985.05 | 0.00 | 0.00 | 0.00 | 0.304072E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 15240070.42 | 0.00 | 0.00 | 0.00 | 23793325.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 74908692.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.179281E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.224164E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.134882E+10 | 0.00 | 0.00 | 0.00 | 0.985343E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 11730135.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.224164E+09 | 0.00 | 0.00 | 0.00 | 0.389663E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT GS2
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 0.228898E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.178725E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.143088E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 48793714.34 | 0.00 | 0.00 | 0.00 | 304684.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 14343087.36 | 0.00 | 0.00 | 0.00 | 39576179.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 82658803.42 | 0.00 | 0.00 | 0.00 | 0.268777E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.133789E+09 | 0.00 | 0.00 | 0.00 | 0.439214E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.105637E+09 | 0.00 | 0.00 | 0.00 | 0.344642E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 17496607.98 | 0.00 | 0.00 | 0.00 | 30424684.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 81366034.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.191904E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.237599E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.146430E+10 | 0.00 | 0.00 | 0.00 | 0.112294E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 14343087.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.237599E+09 | 0.00 | 0.00 | 0.00 | 0.439214E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT MSW
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 0.479601E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.342346E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.248247E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.107106E+09 | 0.00 | 0.00 | 0.00 | 0.148859E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.194193E+09 | 0.00 | 0.00 | 0.00 | 0.620169E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.364436E+09 | 0.00 | 0.00 | 0.00 | 0.118425E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.402371E+09 | 0.00 | 0.00 | 0.00 | 0.131997E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.282398E+09 | 0.00 | 0.00 | 0.00 | 0.920527E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 65557407.16 | 0.00 | 0.00 | 0.00 | 0.145819E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.192722E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.413362E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.514344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.360668E+10 | 0.00 | 0.00 | 0.00 | 0.433959E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 65557407.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.514344E+09 | 0.00 | 0.00 | 0.00 | 0.131997E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT MNW
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 0.489353E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.392611E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.335883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.118418E+09 | 0.00 | 0.00 | 0.00 | 1551122.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 68158384.41 | 0.00 | 0.00 | 0.00 | 0.214448E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.284217E+09 | 0.00 | 0.00 | 0.00 | 0.924301E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.303726E+09 | 0.00 | 0.00 | 0.00 | 0.996571E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.147868E+09 | 0.00 | 0.00 | 0.00 | 0.482404E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 35848602.12 | 0.00 | 0.00 | 0.00 | 249801.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.240638E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.437231E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.509242E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.336319E+10 | 0.00 | 0.00 | 0.00 | 0.261952E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 35848602.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.509242E+09 | 0.00 | 0.00 | 0.00 | 0.996571E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT MSE
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 0.466530E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.327499E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.224134E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.102690E+09 | 0.00 | 0.00 | 0.00 | 0.139783E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.245835E+09 | 0.00 | 0.00 | 0.00 | 0.786182E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.395327E+09 | 0.00 | 0.00 | 0.00 | 0.128415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.447965E+09 | 0.00 | 0.00 | 0.00 | 0.146885E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.312663E+09 | 0.00 | 0.00 | 0.00 | 0.101893E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 73790735.58 | 0.00 | 0.00 | 0.00 | 0.182218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.179695E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.403827E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.502027E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.368198E+10 | 0.00 | 0.00 | 0.00 | 0.488012E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 73790735.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.502027E+09 | 0.00 | 0.00 | 0.00 | 0.146885E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT MNE
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 0.472577E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.373805E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.307038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.113995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.111810E+09 | 0.00 | 0.00 | 0.00 | 0.355928E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.315635E+09 | 0.00 | 0.00 | 0.00 | 0.102591E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.350213E+09 | 0.00 | 0.00 | 0.00 | 0.114844E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.174696E+09 | 0.00 | 0.00 | 0.00 | 0.570443E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 31135994.51 | 0.00 | 0.00 | 0.00 | 118571.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.223794E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.424019E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.493407E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.339213E+10 | 0.00 | 0.00 | 0.00 | 0.310084E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 31135994.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.493407E+09 | 0.00 | 0.00 | 0.00 | 0.114844E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT MN1
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 0.333280E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.268399E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.229460E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 79496119.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 51923754.28 | 0.00 | 0.00 | 0.00 | 0.166394E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.229664E+09 | 0.00 | 0.00 | 0.00 | 0.747119E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.258391E+09 | 0.00 | 0.00 | 0.00 | 0.847958E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.132755E+09 | 0.00 | 0.00 | 0.00 | 0.433875E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 18755409.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.151318E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.302312E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.349348E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.240510E+10 | 0.00 | 0.00 | 0.00 | 0.219535E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 18755409.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.349348E+09 | 0.00 | 0.00 | 0.00 | 0.847958E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT MN2
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 0.333031E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.267986E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.228462E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 79553807.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 54477155.51 | 0.00 | 0.00 | 0.00 | 0.174579E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.231050E+09 | 0.00 | 0.00 | 0.00 | 0.751599E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.260349E+09 | 0.00 | 0.00 | 0.00 | 0.854371E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.134260E+09 | 0.00 | 0.00 | 0.00 | 0.438784E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 18581189.41 | 0.00 | 0.00 | 0.00 | 4142.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.150774E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.302146E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.349145E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.240981E+10 | 0.00 | 0.00 | 0.00 | 0.221934E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 18581189.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.349145E+09 | 0.00 | 0.00 | 0.00 | 0.854371E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT MS1
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 0.326928E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.223955E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.149023E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 70911309.62 | 0.00 | 0.00 | 0.00 | 0.131472E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.183858E+09 | 0.00 | 0.00 | 0.00 | 0.588975E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.310393E+09 | 0.00 | 0.00 | 0.00 | 0.100880E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.357503E+09 | 0.00 | 0.00 | 0.00 | 0.117294E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.272730E+09 | 0.00 | 0.00 | 0.00 | 0.889142E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 67642478.77 | 0.00 | 0.00 | 0.00 | 0.195029E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.110965E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.282443E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.356964E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.271332E+10 | 0.00 | 0.00 | 0.00 | 0.398635E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 67642478.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.357503E+09 | 0.00 | 0.00 | 0.00 | 0.117294E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT MS2
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 0.326715E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.223557E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.148010E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 71411926.57 | 0.00 | 0.00 | 0.00 | 0.132868E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.186913E+09 | 0.00 | 0.00 | 0.00 | 0.598762E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.311806E+09 | 0.00 | 0.00 | 0.00 | 0.101336E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.359408E+09 | 0.00 | 0.00 | 0.00 | 0.117917E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.274387E+09 | 0.00 | 0.00 | 0.00 | 0.894521E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 68964887.70 | 0.00 | 0.00 | 0.00 | 0.199618E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.110497E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.282315E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.356796E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.272078E+10 | 0.00 | 0.00 | 0.00 | 0.401830E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 68964887.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.359408E+09 | 0.00 | 0.00 | 0.00 | 0.117917E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT TSW
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 0.361871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.270466E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.213098E+09 | 0.00 | 0.00 | 0.00 | 126962.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.115908E+09 | 0.00 | 0.00 | 0.00 | 0.104367E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 94607870.89 | 0.00 | 0.00 | 0.00 | 0.266924E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.166636E+09 | 0.00 | 0.00 | 0.00 | 0.541122E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.187125E+09 | 0.00 | 0.00 | 0.00 | 0.613956E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.122520E+09 | 0.00 | 0.00 | 0.00 | 0.387379E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 59000158.25 | 0.00 | 0.00 | 0.00 | 56622141.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.172732E+09 | 0.00 | 0.00 | 0.00 | 742046.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.319688E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.383186E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.246684E+10 | 0.00 | 0.00 | 0.00 | 0.197124E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 59000158.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.383186E+09 | 0.00 | 0.00 | 0.00 | 0.613956E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT TNW
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 0.366987E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.297915E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.260251E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.115761E+09 | 0.00 | 0.00 | 0.00 | 5941943.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 38010004.69 | 0.00 | 0.00 | 0.00 | 78921794.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.122646E+09 | 0.00 | 0.00 | 0.00 | 0.398529E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.134848E+09 | 0.00 | 0.00 | 0.00 | 0.442615E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 60662237.21 | 0.00 | 0.00 | 0.00 | 0.180204E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 58019943.76 | 0.00 | 0.00 | 0.00 | 255140.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.197534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.332287E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.379879E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.236480E+10 | 0.00 | 0.00 | 0.00 | 0.110647E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 38010004.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.379879E+09 | 0.00 | 0.00 | 0.00 | 0.442615E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT TSE
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 0.349680E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.258407E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.196538E+09 | 0.00 | 0.00 | 0.00 | 454827.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.108410E+09 | 0.00 | 0.00 | 0.00 | 92516931.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.110495E+09 | 0.00 | 0.00 | 0.00 | 0.324233E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.179480E+09 | 0.00 | 0.00 | 0.00 | 0.582724E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.208216E+09 | 0.00 | 0.00 | 0.00 | 0.682787E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.132240E+09 | 0.00 | 0.00 | 0.00 | 0.422067E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 56197215.96 | 0.00 | 0.00 | 0.00 | 62010767.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.162760E+09 | 0.00 | 0.00 | 0.00 | 1272084.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.309983E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.371201E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.244361E+10 | 0.00 | 0.00 | 0.00 | 0.216807E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 56197215.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.371201E+09 | 0.00 | 0.00 | 0.00 | 0.682787E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT TNE
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 0.351391E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.282356E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.239436E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.108112E+09 | 0.00 | 0.00 | 0.00 | 107618.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 47057955.50 | 0.00 | 0.00 | 0.00 | 0.114578E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.137819E+09 | 0.00 | 0.00 | 0.00 | 0.447779E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.157850E+09 | 0.00 | 0.00 | 0.00 | 0.517673E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 68400671.23 | 0.00 | 0.00 | 0.00 | 0.210347E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 51065312.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.184538E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.319237E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.364624E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.231189E+10 | 0.00 | 0.00 | 0.00 | 0.129048E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 47057955.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.364624E+09 | 0.00 | 0.00 | 0.00 | 0.517673E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT TN1
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 0.266916E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.217418E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.188781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 81938237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 18464792.06 | 0.00 | 0.00 | 0.00 | 38668988.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 96343603.46 | 0.00 | 0.00 | 0.00 | 0.313502E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.112126E+09 | 0.00 | 0.00 | 0.00 | 0.368104E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 46513037.45 | 0.00 | 0.00 | 0.00 | 0.142401E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 36743470.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.137404E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.245799E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.277903E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.172635E+10 | 0.00 | 0.00 | 0.00 | 0.862676E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 18464792.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.277903E+09 | 0.00 | 0.00 | 0.00 | 0.368104E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT TN2
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 0.266485E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.216951E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.188032E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 81902149.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 19304680.84 | 0.00 | 0.00 | 0.00 | 41839576.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 97289337.38 | 0.00 | 0.00 | 0.00 | 0.316559E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.113406E+09 | 0.00 | 0.00 | 0.00 | 0.372294E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 47374156.10 | 0.00 | 0.00 | 0.00 | 0.145416E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 36456464.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.136951E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.245442E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.277488E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.172708E+10 | 0.00 | 0.00 | 0.00 | 0.876109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 19304680.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.277488E+09 | 0.00 | 0.00 | 0.00 | 0.372294E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT TS1
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 0.264184E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.192981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.145696E+09 | 0.00 | 0.00 | 0.00 | 127318.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 78061988.26 | 0.00 | 0.00 | 0.00 | 80507948.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 75798797.59 | 0.00 | 0.00 | 0.00 | 0.228062E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.139461E+09 | 0.00 | 0.00 | 0.00 | 0.453200E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.164120E+09 | 0.00 | 0.00 | 0.00 | 0.538603E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.109964E+09 | 0.00 | 0.00 | 0.00 | 0.353308E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 39660111.70 | 0.00 | 0.00 | 0.00 | 53631870.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.115718E+09 | 0.00 | 0.00 | 0.00 | 1388738.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.235812E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.283369E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.184483E+10 | 0.00 | 0.00 | 0.00 | 0.170883E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 39660111.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.283369E+09 | 0.00 | 0.00 | 0.00 | 0.538603E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT TS2
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 0.263862E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.192616E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.145105E+09 | 0.00 | 0.00 | 0.00 | 198331.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 78581626.70 | 0.00 | 0.00 | 0.00 | 81948682.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 77693485.67 | 0.00 | 0.00 | 0.00 | 0.234284E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.140551E+09 | 0.00 | 0.00 | 0.00 | 0.456721E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.165426E+09 | 0.00 | 0.00 | 0.00 | 0.542876E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.111058E+09 | 0.00 | 0.00 | 0.00 | 0.356930E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 39987381.63 | 0.00 | 0.00 | 0.00 | 55164182.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.115393E+09 | 0.00 | 0.00 | 0.00 | 1503370.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.235566E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.283061E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.184890E+10 | 0.00 | 0.00 | 0.00 | 0.172963E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 39987381.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.283061E+09 | 0.00 | 0.00 | 0.00 | 0.542876E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: G SW APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.322788E+10 | 0.00 | 0.00 | 0.35 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.275077E+10 | 0.00 | 0.00 | 0.35 |
| March | 51933282.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.256264E+10 | 0.00 | 0.00 | 0.35 |
| April | 0.654735E+09 | 0.00 | 0.00 | 32584.97 | 0.00 | 0.100245E+10 | 11381429.92 | 0.00 | 0.35 |
| May | 0.820740E+09 | 0.00 | 0.00 | 334614.94 | 0.00 | 91848360.08 | 85632738.09 | 0.00 | 0.35 |
| June | 0.289891E+09 | 6527984.19 | 0.00 | 1923391.47 | 0.00 | 0.00 | 0.365049E+09 | 0.00 | 0.36 |
| July | 0.152400E+09 | 17792089.48 | 0.00 | 2629712.94 | 0.00 | 0.00 | 0.459113E+09 | 0.00 | 0.36 |
| August | 0.287128E+09 | 2152260.30 | 0.00 | 2867051.94 | 0.00 | 0.00 | 0.534186E+09 | 0.00 | 0.35 |
| September | 0.975631E+09 | 0.00 | 0.00 | 272650.23 | 0.00 | 0.210068E+09 | 0.100029E+09 | 0.00 | 0.35 |
| October | 0.325916E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.169771E+10 | 0.00 | 0.00 | 0.35 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.312977E+10 | 0.00 | 0.00 | 0.35 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.336281E+10 | 0.00 | 0.00 | 0.35 |
| Annual Sum or Average | 0.355837E+10 | 26472333.97 | 0.00 | 8060006.51 | 0.00 | 0.180360E+11 | 0.155539E+10 | 0.00 | 0.35 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
| Maximum of Months | 0.975631E+09 | 17792089.48 | 0.00 | 2867051.94 | 0.00 | 0.336281E+10 | 0.534186E+09 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: G NW APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.322797E+10 | 0.00 | 0.00 | 0.35 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.275130E+10 | 0.00 | 0.00 | 0.35 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.261667E+10 | 0.00 | 0.00 | 0.35 |
| April | 0.140259E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.150528E+10 | 0.00 | 0.00 | 0.35 |
| May | 0.699304E+09 | 0.00 | 0.00 | 477.32 | 0.00 | 0.219884E+09 | 357419.81 | 0.00 | 0.35 |
| June | 0.377679E+09 | 4949954.13 | 0.00 | 1156196.01 | 0.00 | 0.00 | 0.262699E+09 | 0.00 | 0.36 |
| July | 0.217513E+09 | 15841033.95 | 0.00 | 1928374.01 | 0.00 | 0.00 | 0.401863E+09 | 0.00 | 0.36 |
| August | 0.527214E+09 | 1579568.50 | 0.00 | 1243242.77 | 0.00 | 0.00 | 0.280559E+09 | 0.00 | 0.35 |
| September | 0.811654E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.389392E+09 | 0.00 | 0.00 | 0.35 |
| October | 71372630.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.195072E+10 | 0.00 | 0.00 | 0.35 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.313006E+10 | 0.00 | 0.00 | 0.35 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.336254E+10 | 0.00 | 0.00 | 0.35 |
| Annual Sum or Average | 0.284500E+10 | 22370556.59 | 0.00 | 4328290.12 | 0.00 | 0.191538E+11 | 0.945478E+09 | 0.00 | 0.35 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
| Maximum of Months | 0.811654E+09 | 15841033.95 | 0.00 | 1928374.01 | 0.00 | 0.336254E+10 | 0.401863E+09 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: OFFICE
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.493136E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.376439E+10 | 0.00 | 0.00 | 0.51 |
| February | 0.769645E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.284832E+10 | 0.00 | 0.00 | 0.51 |
| March | 0.156418E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.185793E+10 | 0.00 | 0.00 | 0.51 |
| April | 0.182841E+10 | 0.00 | 0.00 | 11537.78 | 0.00 | 0.400063E+09 | 19334186.53 | 0.00 | 0.51 |
| May | 0.137047E+10 | 0.00 | 0.00 | 717718.29 | 0.00 | 0.00 | 0.234353E+09 | 0.00 | 0.52 |
| June | 0.909427E+09 | 3505239.50 | 0.00 | 1988076.29 | 22038.90 | 0.00 | 0.237524E+09 | 0.00 | 0.53 |
| July | 0.969075E+09 | 2990183.20 | 0.00 | 2365663.20 | 1017364.19 | 0.00 | 0.159272E+09 | 0.00 | 0.53 |
| August | 0.111417E+10 | 120116.89 | 0.00 | 2382584.27 | 7401.16 | 0.00 | 0.291389E+09 | 0.00 | 0.52 |
| September | 0.171250E+10 | 0.00 | 0.00 | 370095.62 | 0.00 | 25046436.57 | 0.206873E+09 | 0.00 | 0.52 |
| October | 0.181968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.877158E+09 | 0.00 | 0.00 | 0.51 |
| November | 0.122360E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.290881E+10 | 0.00 | 0.00 | 0.51 |
| December | 0.342890E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.411056E+10 | 0.00 | 0.00 | 0.51 |
| Annual Sum or Average | 0.141172E+11 | 6615539.59 | 0.00 | 7835675.45 | 1046804.25 | 0.167923E+11 | 0.114874E+10 | 0.00 | 0.52 |
| Minimum of Months | 0.342890E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.51 |
| Maximum of Months | 0.182841E+10 | 3505239.50 | 0.00 | 2382584.27 | 1017364.19 | 0.411056E+10 | 0.291389E+09 | 0.00 | 0.53 |
Report: MechanicalVentilationLoadsMonthly
For: G NE APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.322797E+10 | 0.00 | 0.00 | 0.35 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.275128E+10 | 0.00 | 0.00 | 0.35 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.261668E+10 | 0.00 | 0.00 | 0.35 |
| April | 0.167728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147680E+10 | 0.00 | 0.00 | 0.35 |
| May | 0.775087E+09 | 0.00 | 0.00 | 4722.22 | 0.00 | 0.169319E+09 | 2279461.88 | 0.00 | 0.35 |
| June | 0.306573E+09 | 5193255.22 | 0.00 | 1680343.89 | 0.00 | 0.00 | 0.344699E+09 | 0.00 | 0.36 |
| July | 0.184600E+09 | 16604180.48 | 0.00 | 2506545.75 | 0.00 | 0.00 | 0.429806E+09 | 0.00 | 0.36 |
| August | 0.453327E+09 | 1598720.48 | 0.00 | 1635802.93 | 0.00 | 0.00 | 0.360687E+09 | 0.00 | 0.35 |
| September | 0.836793E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.372791E+09 | 0.00 | 0.00 | 0.35 |
| October | 0.109657E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.191244E+10 | 0.00 | 0.00 | 0.35 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.313005E+10 | 0.00 | 0.00 | 0.35 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.336253E+10 | 0.00 | 0.00 | 0.35 |
| Annual Sum or Average | 0.283376E+10 | 23396156.18 | 0.00 | 5827414.79 | 0.00 | 0.190199E+11 | 0.113747E+10 | 0.00 | 0.35 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
| Maximum of Months | 0.836793E+09 | 16604180.48 | 0.00 | 2506545.75 | 0.00 | 0.336253E+10 | 0.429806E+09 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: G N1 APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.323078E+10 | 0.00 | 0.00 | 0.35 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.275381E+10 | 0.00 | 0.00 | 0.35 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.262095E+10 | 0.00 | 0.00 | 0.35 |
| April | 0.239093E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.141076E+10 | 0.00 | 0.00 | 0.35 |
| May | 0.868943E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 66323440.49 | 0.00 | 0.00 | 0.35 |
| June | 0.277770E+09 | 4722143.97 | 0.00 | 1377144.57 | 0.00 | 0.00 | 0.379858E+09 | 0.00 | 0.36 |
| July | 0.123787E+09 | 15499301.86 | 0.00 | 2185647.01 | 0.00 | 0.00 | 0.501493E+09 | 0.00 | 0.36 |
| August | 0.395116E+09 | 1531012.55 | 0.00 | 1424136.31 | 0.00 | 0.00 | 0.432000E+09 | 0.00 | 0.35 |
| September | 0.103676E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.179460E+09 | 0.00 | 0.00 | 0.35 |
| October | 0.308162E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.171867E+10 | 0.00 | 0.00 | 0.35 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.313133E+10 | 0.00 | 0.00 | 0.35 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.336486E+10 | 0.00 | 0.00 | 0.35 |
| Annual Sum or Average | 0.324963E+10 | 21752458.38 | 0.00 | 4986927.89 | 0.00 | 0.184769E+11 | 0.131335E+10 | 0.00 | 0.35 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
| Maximum of Months | 0.103676E+10 | 15499301.86 | 0.00 | 2185647.01 | 0.00 | 0.336486E+10 | 0.501493E+09 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: G N2 APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.323078E+10 | 0.00 | 0.00 | 0.35 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.275381E+10 | 0.00 | 0.00 | 0.35 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.262095E+10 | 0.00 | 0.00 | 0.35 |
| April | 0.239184E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.141065E+10 | 0.00 | 0.00 | 0.35 |
| May | 0.880367E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 59097903.63 | 0.00 | 0.00 | 0.35 |
| June | 0.265244E+09 | 4723582.85 | 0.00 | 1426285.35 | 0.00 | 0.00 | 0.393752E+09 | 0.00 | 0.36 |
| July | 0.119810E+09 | 15541600.71 | 0.00 | 2220903.37 | 0.00 | 0.00 | 0.505031E+09 | 0.00 | 0.36 |
| August | 0.387203E+09 | 1533282.44 | 0.00 | 1465757.02 | 0.00 | 0.00 | 0.440667E+09 | 0.00 | 0.35 |
| September | 0.104284E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.175060E+09 | 0.00 | 0.00 | 0.35 |
| October | 0.311387E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.171545E+10 | 0.00 | 0.00 | 0.35 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.313133E+10 | 0.00 | 0.00 | 0.35 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.336486E+10 | 0.00 | 0.00 | 0.35 |
| Annual Sum or Average | 0.324604E+10 | 21798466.00 | 0.00 | 5112945.74 | 0.00 | 0.184620E+11 | 0.133945E+10 | 0.00 | 0.35 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
| Maximum of Months | 0.104284E+10 | 15541600.71 | 0.00 | 2220903.37 | 0.00 | 0.336486E+10 | 0.505031E+09 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: G S1 APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.323082E+10 | 0.00 | 0.00 | 0.35 |
| February | 22768723.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.273046E+10 | 0.00 | 0.00 | 0.35 |
| March | 0.336047E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.228260E+10 | 0.00 | 0.00 | 0.35 |
| April | 0.103506E+10 | 0.00 | 0.00 | 16695.72 | 0.00 | 0.637789E+09 | 8182634.54 | 0.00 | 0.35 |
| May | 0.890890E+09 | 0.00 | 0.00 | 477506.77 | 0.00 | 0.00 | 0.147583E+09 | 0.00 | 0.35 |
| June | 0.151328E+09 | 6411243.98 | 0.00 | 2269927.83 | 0.00 | 0.00 | 0.518451E+09 | 0.00 | 0.36 |
| July | 49955818.36 | 17532843.42 | 0.00 | 3010997.72 | 0.00 | 0.00 | 0.562849E+09 | 0.00 | 0.36 |
| August | 0.162661E+09 | 2155582.39 | 0.00 | 3393608.36 | 0.00 | 0.00 | 0.670453E+09 | 0.00 | 0.35 |
| September | 0.109826E+10 | 0.00 | 0.00 | 516932.63 | 0.00 | 31255195.48 | 0.196157E+09 | 0.00 | 0.35 |
| October | 0.780715E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125106E+10 | 0.00 | 0.00 | 0.35 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.313104E+10 | 0.00 | 0.00 | 0.35 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.336514E+10 | 0.00 | 0.00 | 0.35 |
| Annual Sum or Average | 0.452769E+10 | 26099669.79 | 0.00 | 9685669.02 | 0.00 | 0.166602E+11 | 0.210368E+10 | 0.00 | 0.35 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
| Maximum of Months | 0.109826E+10 | 17532843.42 | 0.00 | 3393608.36 | 0.00 | 0.336514E+10 | 0.670453E+09 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: G S2 APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.323081E+10 | 0.00 | 0.00 | 0.35 |
| February | 13951094.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.273928E+10 | 0.00 | 0.00 | 0.35 |
| March | 0.260953E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.235771E+10 | 0.00 | 0.00 | 0.35 |
| April | 0.929275E+09 | 0.00 | 0.00 | 15155.67 | 0.00 | 0.742321E+09 | 7621480.91 | 0.00 | 0.35 |
| May | 0.858621E+09 | 0.00 | 0.00 | 593127.48 | 0.00 | 0.00 | 0.187046E+09 | 0.00 | 0.35 |
| June | 0.126379E+09 | 6508742.74 | 0.00 | 2606450.06 | 0.00 | 0.00 | 0.544025E+09 | 0.00 | 0.36 |
| July | 34336942.38 | 17787633.41 | 0.00 | 3397371.52 | 0.00 | 0.00 | 0.571748E+09 | 0.00 | 0.36 |
| August | 0.144967E+09 | 2169176.13 | 0.00 | 3790948.52 | 0.00 | 0.00 | 0.685545E+09 | 0.00 | 0.35 |
| September | 0.105928E+10 | 0.00 | 0.00 | 617893.84 | 0.00 | 42008101.61 | 0.230128E+09 | 0.00 | 0.35 |
| October | 0.685961E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.134543E+10 | 0.00 | 0.00 | 0.35 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.313104E+10 | 0.00 | 0.00 | 0.35 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.336513E+10 | 0.00 | 0.00 | 0.35 |
| Annual Sum or Average | 0.411373E+10 | 26465552.29 | 0.00 | 11020947.11 | 0.00 | 0.169537E+11 | 0.222611E+10 | 0.00 | 0.35 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
| Maximum of Months | 0.105928E+10 | 17787633.41 | 0.00 | 3790948.52 | 0.00 | 0.336513E+10 | 0.685545E+09 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: M SW APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.645018E+10 | 0.00 | 0.00 | 0.35 |
| February | 0.348828E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.514795E+10 | 0.00 | 0.00 | 0.35 |
| March | 0.150048E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.372909E+10 | 0.00 | 0.00 | 0.35 |
| April | 0.220677E+10 | 0.00 | 0.00 | 2243632.50 | 0.00 | 0.818050E+09 | 0.457489E+09 | 0.00 | 0.35 |
| May | 0.103645E+10 | 0.00 | 0.00 | 6671262.87 | 0.00 | 0.00 | 0.117268E+10 | 0.00 | 0.36 |
| June | 93254950.28 | 14918220.90 | 0.00 | 9962051.79 | 0.00 | 0.00 | 0.121584E+10 | 0.00 | 0.36 |
| July | 46752345.77 | 38069333.53 | 0.00 | 8945549.76 | 0.00 | 0.00 | 0.113170E+10 | 0.00 | 0.36 |
| August | 0.349326E+09 | 4426095.41 | 0.00 | 8666504.62 | 0.00 | 0.00 | 0.128278E+10 | 0.00 | 0.35 |
| September | 0.194947E+10 | 0.00 | 0.00 | 2091259.35 | 0.00 | 0.192967E+09 | 0.501986E+09 | 0.00 | 0.35 |
| October | 0.114207E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.291049E+10 | 0.00 | 0.00 | 0.35 |
| November | 52231215.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.620478E+10 | 0.00 | 0.00 | 0.35 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.672105E+10 | 0.00 | 0.00 | 0.35 |
| Annual Sum or Average | 0.872562E+10 | 57413649.84 | 0.00 | 38580260.89 | 0.00 | 0.321746E+11 | 0.576248E+10 | 0.00 | 0.35 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
| Maximum of Months | 0.220677E+10 | 38069333.53 | 0.00 | 9962051.79 | 0.00 | 0.672105E+10 | 0.128278E+10 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: M NW APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.645063E+10 | 0.00 | 0.00 | 0.35 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.549774E+10 | 0.00 | 0.00 | 0.35 |
| March | 0.213639E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.501176E+10 | 0.00 | 0.00 | 0.35 |
| April | 0.161420E+10 | 0.00 | 0.00 | 49523.28 | 0.00 | 0.170733E+10 | 19854761.81 | 0.00 | 0.35 |
| May | 0.139396E+10 | 0.00 | 0.00 | 2985420.94 | 0.00 | 0.00 | 0.767237E+09 | 0.00 | 0.35 |
| June | 83331845.20 | 12255334.01 | 0.00 | 8727808.87 | 0.00 | 0.00 | 0.122838E+10 | 0.00 | 0.36 |
| July | 49185992.31 | 34516916.10 | 0.00 | 7846413.36 | 0.00 | 0.00 | 0.114471E+10 | 0.00 | 0.36 |
| August | 0.570046E+09 | 3418446.08 | 0.00 | 5285770.65 | 0.00 | 0.00 | 0.106218E+10 | 0.00 | 0.35 |
| September | 0.197610E+10 | 0.00 | 0.00 | 13077.67 | 0.00 | 0.504577E+09 | 7897622.18 | 0.00 | 0.35 |
| October | 0.418900E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.361714E+10 | 0.00 | 0.00 | 0.35 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.625760E+10 | 0.00 | 0.00 | 0.35 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.672049E+10 | 0.00 | 0.00 | 0.35 |
| Annual Sum or Average | 0.631936E+10 | 50190696.19 | 0.00 | 24908014.78 | 0.00 | 0.357673E+11 | 0.423025E+10 | 0.00 | 0.35 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
| Maximum of Months | 0.197610E+10 | 34516916.10 | 0.00 | 8727808.87 | 0.00 | 0.672049E+10 | 0.122838E+10 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: M SE APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 1159260.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.644900E+10 | 0.00 | 0.00 | 0.35 |
| February | 0.458497E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.503823E+10 | 0.00 | 0.00 | 0.35 |
| March | 0.184012E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.339279E+10 | 0.00 | 0.00 | 0.35 |
| April | 0.218205E+10 | 0.00 | 0.00 | 2036346.74 | 0.00 | 0.802742E+09 | 0.501402E+09 | 0.00 | 0.35 |
| May | 0.874410E+09 | 0.00 | 0.00 | 8617348.20 | 0.00 | 0.00 | 0.134726E+10 | 0.00 | 0.36 |
| June | 71401118.33 | 15268829.52 | 0.00 | 11189198.17 | 0.00 | 0.00 | 0.124045E+10 | 0.00 | 0.36 |
| July | 32173696.18 | 38927977.95 | 0.00 | 10373284.76 | 0.00 | 0.00 | 0.113744E+10 | 0.00 | 0.36 |
| August | 0.287286E+09 | 4453564.01 | 0.00 | 9823337.79 | 0.00 | 0.00 | 0.134472E+10 | 0.00 | 0.35 |
| September | 0.189394E+10 | 0.00 | 0.00 | 2417141.36 | 0.00 | 0.157804E+09 | 0.607198E+09 | 0.00 | 0.35 |
| October | 0.129045E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.276902E+10 | 0.00 | 0.00 | 0.35 |
| November | 46365677.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.621061E+10 | 0.00 | 0.00 | 0.35 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.672105E+10 | 0.00 | 0.00 | 0.35 |
| Annual Sum or Average | 0.897785E+10 | 58650371.47 | 0.00 | 44456657.03 | 0.00 | 0.315412E+11 | 0.617847E+10 | 0.00 | 0.35 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
| Maximum of Months | 0.218205E+10 | 38927977.95 | 0.00 | 11189198.17 | 0.00 | 0.672105E+10 | 0.134726E+10 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: M NE APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.645061E+10 | 0.00 | 0.00 | 0.35 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.549770E+10 | 0.00 | 0.00 | 0.35 |
| March | 0.327805E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.489763E+10 | 0.00 | 0.00 | 0.35 |
| April | 0.162373E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.171555E+10 | 0.00 | 0.00 | 0.35 |
| May | 0.116353E+10 | 0.00 | 0.00 | 4898440.12 | 0.00 | 1562917.93 | 0.102425E+10 | 0.00 | 0.36 |
| June | 76683508.77 | 12783005.09 | 0.00 | 9926416.30 | 0.00 | 0.00 | 0.123770E+10 | 0.00 | 0.36 |
| July | 52329287.60 | 35736828.61 | 0.00 | 9295148.41 | 0.00 | 0.00 | 0.113177E+10 | 0.00 | 0.36 |
| August | 0.498384E+09 | 3439217.66 | 0.00 | 6363870.18 | 0.00 | 0.00 | 0.113755E+10 | 0.00 | 0.35 |
| September | 0.213053E+10 | 0.00 | 0.00 | 21014.72 | 0.00 | 0.374855E+09 | 20231596.36 | 0.00 | 0.35 |
| October | 0.528452E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.350791E+10 | 0.00 | 0.00 | 0.35 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.625757E+10 | 0.00 | 0.00 | 0.35 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.672049E+10 | 0.00 | 0.00 | 0.35 |
| Annual Sum or Average | 0.640144E+10 | 51959051.36 | 0.00 | 30504889.73 | 0.00 | 0.354239E+11 | 0.455150E+10 | 0.00 | 0.35 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
| Maximum of Months | 0.213053E+10 | 35736828.61 | 0.00 | 9926416.30 | 0.00 | 0.672049E+10 | 0.123770E+10 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: M N1 APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 43295862.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.641449E+10 | 0.00 | 0.00 | 0.35 |
| February | 0.287143E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.521713E+10 | 0.00 | 0.00 | 0.35 |
| March | 0.896294E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.433993E+10 | 0.00 | 0.00 | 0.35 |
| April | 0.223588E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110723E+10 | 0.00 | 0.00 | 0.35 |
| May | 0.123431E+10 | 0.00 | 0.00 | 2991341.16 | 0.00 | 0.00 | 0.977742E+09 | 0.00 | 0.36 |
| June | 31392341.13 | 11338763.43 | 0.00 | 7857934.21 | 0.00 | 0.00 | 0.129719E+10 | 0.00 | 0.36 |
| July | 959608.58 | 33177432.25 | 0.00 | 7558569.04 | 0.00 | 0.00 | 0.120271E+10 | 0.00 | 0.36 |
| August | 0.374118E+09 | 3294415.76 | 0.00 | 5629273.55 | 0.00 | 0.00 | 0.128376E+10 | 0.00 | 0.35 |
| September | 0.247635E+10 | 0.00 | 0.00 | 11128.72 | 0.00 | 68040094.34 | 18962309.12 | 0.00 | 0.35 |
| October | 0.157800E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.247273E+10 | 0.00 | 0.00 | 0.35 |
| November | 56196406.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.620474E+10 | 0.00 | 0.00 | 0.35 |
| December | 22361220.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.670431E+10 | 0.00 | 0.00 | 0.35 |
| Annual Sum or Average | 0.923630E+10 | 47810611.44 | 0.00 | 24048246.68 | 0.00 | 0.325286E+11 | 0.478036E+10 | 0.00 | 0.35 |
| Minimum of Months | 959608.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
| Maximum of Months | 0.247635E+10 | 33177432.25 | 0.00 | 7857934.21 | 0.00 | 0.670431E+10 | 0.129719E+10 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: M N2 APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 43295875.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.641449E+10 | 0.00 | 0.00 | 0.35 |
| February | 0.288866E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.521541E+10 | 0.00 | 0.00 | 0.35 |
| March | 0.925057E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.431117E+10 | 0.00 | 0.00 | 0.35 |
| April | 0.222723E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111597E+10 | 0.00 | 0.00 | 0.35 |
| May | 0.120552E+10 | 0.00 | 0.00 | 3132927.47 | 0.00 | 0.00 | 0.101087E+10 | 0.00 | 0.36 |
| June | 30076382.38 | 11360785.43 | 0.00 | 7897771.08 | 0.00 | 0.00 | 0.129863E+10 | 0.00 | 0.36 |
| July | 896839.04 | 33238788.67 | 0.00 | 7602367.78 | 0.00 | 0.00 | 0.120222E+10 | 0.00 | 0.36 |
| August | 0.370071E+09 | 3297473.78 | 0.00 | 5678545.45 | 0.00 | 0.00 | 0.128828E+10 | 0.00 | 0.35 |
| September | 0.248206E+10 | 0.00 | 0.00 | 23043.85 | 0.00 | 64113180.04 | 24488119.12 | 0.00 | 0.35 |
| October | 0.159584E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.245504E+10 | 0.00 | 0.00 | 0.35 |
| November | 55034028.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.620591E+10 | 0.00 | 0.00 | 0.35 |
| December | 22449496.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.670422E+10 | 0.00 | 0.00 | 0.35 |
| Annual Sum or Average | 0.924639E+10 | 47897047.89 | 0.00 | 24334655.65 | 0.00 | 0.324863E+11 | 0.482449E+10 | 0.00 | 0.35 |
| Minimum of Months | 896839.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
| Maximum of Months | 0.248206E+10 | 33238788.67 | 0.00 | 7897771.08 | 0.00 | 0.670422E+10 | 0.129863E+10 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: M S1 APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.372119E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.608554E+10 | 0.00 | 0.00 | 0.35 |
| February | 0.182352E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.368020E+10 | 0.00 | 0.00 | 0.35 |
| March | 0.336332E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.188606E+10 | 0.00 | 0.00 | 0.35 |
| April | 0.271589E+10 | 0.00 | 0.00 | 2102602.23 | 0.00 | 0.255926E+09 | 0.563442E+09 | 0.00 | 0.35 |
| May | 0.750577E+09 | 0.00 | 0.00 | 6985479.64 | 0.00 | 0.00 | 0.150926E+10 | 0.00 | 0.36 |
| June | 22338629.85 | 14330762.16 | 0.00 | 9186649.26 | 0.00 | 0.00 | 0.130303E+10 | 0.00 | 0.36 |
| July | 2542183.92 | 37021307.57 | 0.00 | 8706191.94 | 0.00 | 0.00 | 0.118290E+10 | 0.00 | 0.36 |
| August | 0.183144E+09 | 4414309.27 | 0.00 | 9130805.53 | 0.00 | 0.00 | 0.146716E+10 | 0.00 | 0.35 |
| September | 0.182846E+10 | 0.00 | 0.00 | 2969838.17 | 0.00 | 0.00 | 0.889530E+09 | 0.00 | 0.36 |
| October | 0.274882E+10 | 0.00 | 0.00 | 3007.58 | 0.00 | 0.134002E+10 | 4681585.40 | 0.00 | 0.35 |
| November | 0.801408E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.545895E+10 | 0.00 | 0.00 | 0.35 |
| December | 35932607.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.669130E+10 | 0.00 | 0.00 | 0.35 |
| Annual Sum or Average | 0.146481E+11 | 55766379.00 | 0.00 | 39084574.35 | 0.00 | 0.253980E+11 | 0.692001E+10 | 0.00 | 0.35 |
| Minimum of Months | 2542183.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
| Maximum of Months | 0.336332E+10 | 37021307.57 | 0.00 | 9186649.26 | 0.00 | 0.669130E+10 | 0.150926E+10 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: M S2 APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.372119E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.608553E+10 | 0.00 | 0.00 | 0.35 |
| February | 0.182951E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.367421E+10 | 0.00 | 0.00 | 0.35 |
| March | 0.339336E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.185657E+10 | 0.00 | 0.00 | 0.35 |
| April | 0.271165E+10 | 0.00 | 0.00 | 2123043.33 | 0.00 | 0.256509E+09 | 0.567365E+09 | 0.00 | 0.35 |
| May | 0.740013E+09 | 0.00 | 0.00 | 7104174.11 | 0.00 | 0.00 | 0.152078E+10 | 0.00 | 0.36 |
| June | 22194673.07 | 14344486.15 | 0.00 | 9228107.65 | 0.00 | 0.00 | 0.130329E+10 | 0.00 | 0.36 |
| July | 1811320.66 | 37065813.41 | 0.00 | 8751099.43 | 0.00 | 0.00 | 0.118319E+10 | 0.00 | 0.36 |
| August | 0.179431E+09 | 4416632.14 | 0.00 | 9177532.08 | 0.00 | 0.00 | 0.147081E+10 | 0.00 | 0.35 |
| September | 0.180870E+10 | 0.00 | 0.00 | 3022522.35 | 0.00 | 0.00 | 0.910579E+09 | 0.00 | 0.36 |
| October | 0.276113E+10 | 0.00 | 0.00 | 4049.59 | 0.00 | 0.132873E+10 | 5124279.18 | 0.00 | 0.35 |
| November | 0.805374E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.545498E+10 | 0.00 | 0.00 | 0.35 |
| December | 35932603.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.669130E+10 | 0.00 | 0.00 | 0.35 |
| Annual Sum or Average | 0.146612E+11 | 55826931.71 | 0.00 | 39410528.54 | 0.00 | 0.253478E+11 | 0.696113E+10 | 0.00 | 0.35 |
| Minimum of Months | 1811320.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
| Maximum of Months | 0.339336E+10 | 37065813.41 | 0.00 | 9228107.65 | 0.00 | 0.669130E+10 | 0.152078E+10 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: T SW APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.322252E+10 | 0.00 | 0.00 | 0.35 |
| February | 52776317.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.269346E+10 | 0.00 | 0.00 | 0.35 |
| March | 0.357302E+09 | 0.00 | 0.00 | 16716.75 | 0.00 | 0.224966E+10 | 5552981.45 | 0.00 | 0.35 |
| April | 0.535615E+09 | 0.00 | 0.00 | 1483061.39 | 0.00 | 0.952132E+09 | 0.217586E+09 | 0.00 | 0.35 |
| May | 0.587537E+09 | 0.00 | 0.00 | 2649889.05 | 0.00 | 0.120776E+09 | 0.310849E+09 | 0.00 | 0.35 |
| June | 0.266101E+09 | 7615434.49 | 0.00 | 3765471.93 | 0.00 | 512218.08 | 0.362010E+09 | 0.00 | 0.36 |
| July | 0.263962E+09 | 19407071.13 | 0.00 | 3116137.21 | 0.00 | 0.00 | 0.322387E+09 | 0.00 | 0.36 |
| August | 0.440317E+09 | 2225194.16 | 0.00 | 3003174.37 | 0.00 | 42308575.51 | 0.287675E+09 | 0.00 | 0.35 |
| September | 0.568786E+09 | 0.00 | 0.00 | 735235.22 | 0.00 | 0.549417E+09 | 0.120071E+09 | 0.00 | 0.35 |
| October | 0.174818E+09 | 0.00 | 0.00 | 14866.33 | 0.00 | 0.183892E+10 | 4695428.74 | 0.00 | 0.35 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.312735E+10 | 0.00 | 0.00 | 0.35 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.335829E+10 | 0.00 | 0.00 | 0.35 |
| Annual Sum or Average | 0.324721E+10 | 29247699.78 | 0.00 | 14784552.25 | 0.00 | 0.181553E+11 | 0.163083E+10 | 0.00 | 0.35 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
| Maximum of Months | 0.587537E+09 | 19407071.13 | 0.00 | 3765471.93 | 0.00 | 0.335829E+10 | 0.362010E+09 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: T NW APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.322286E+10 | 0.00 | 0.00 | 0.35 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.274662E+10 | 0.00 | 0.00 | 0.35 |
| March | 22985703.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.258612E+10 | 0.00 | 0.00 | 0.35 |
| April | 0.374140E+09 | 0.00 | 0.00 | 110932.81 | 0.00 | 0.125678E+10 | 29730101.71 | 0.00 | 0.35 |
| May | 0.675033E+09 | 0.00 | 0.00 | 938155.06 | 0.00 | 0.152934E+09 | 0.169241E+09 | 0.00 | 0.35 |
| June | 0.224345E+09 | 6351733.39 | 0.00 | 3214088.60 | 0.00 | 42267.86 | 0.410558E+09 | 0.00 | 0.36 |
| July | 0.244506E+09 | 17688127.12 | 0.00 | 2713323.04 | 0.00 | 0.00 | 0.347868E+09 | 0.00 | 0.36 |
| August | 0.496749E+09 | 1734042.54 | 0.00 | 1516917.43 | 0.00 | 65412323.20 | 0.195625E+09 | 0.00 | 0.35 |
| September | 0.388433E+09 | 0.00 | 0.00 | 10533.58 | 0.00 | 0.802304E+09 | 6083557.02 | 0.00 | 0.35 |
| October | 25556526.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.198812E+10 | 0.00 | 0.00 | 0.35 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.312766E+10 | 0.00 | 0.00 | 0.35 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.335801E+10 | 0.00 | 0.00 | 0.35 |
| Annual Sum or Average | 0.245175E+10 | 25773903.05 | 0.00 | 8503950.53 | 0.00 | 0.193069E+11 | 0.115911E+10 | 0.00 | 0.35 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
| Maximum of Months | 0.675033E+09 | 17688127.12 | 0.00 | 3214088.60 | 0.00 | 0.335801E+10 | 0.410558E+09 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: T SE APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.322251E+10 | 0.00 | 0.00 | 0.35 |
| February | 69560507.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.267663E+10 | 0.00 | 0.00 | 0.35 |
| March | 0.435123E+09 | 0.00 | 0.00 | 25529.18 | 0.00 | 0.216788E+10 | 10743190.49 | 0.00 | 0.35 |
| April | 0.554471E+09 | 0.00 | 0.00 | 1211990.79 | 0.00 | 0.935965E+09 | 0.216425E+09 | 0.00 | 0.35 |
| May | 0.561371E+09 | 0.00 | 0.00 | 3037807.80 | 0.00 | 0.104594E+09 | 0.368045E+09 | 0.00 | 0.35 |
| June | 0.227534E+09 | 7803868.98 | 0.00 | 4401960.28 | 0.00 | 42304.38 | 0.407878E+09 | 0.00 | 0.36 |
| July | 0.222930E+09 | 19792367.10 | 0.00 | 3955252.50 | 0.00 | 0.00 | 0.363223E+09 | 0.00 | 0.36 |
| August | 0.420763E+09 | 2235662.70 | 0.00 | 3330957.48 | 0.00 | 30859409.13 | 0.325705E+09 | 0.00 | 0.35 |
| September | 0.606744E+09 | 0.00 | 0.00 | 730278.93 | 0.00 | 0.498548E+09 | 0.139323E+09 | 0.00 | 0.35 |
| October | 0.199972E+09 | 0.00 | 0.00 | 21102.79 | 0.00 | 0.181294E+10 | 6764742.85 | 0.00 | 0.35 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.312732E+10 | 0.00 | 0.00 | 0.35 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.335829E+10 | 0.00 | 0.00 | 0.35 |
| Annual Sum or Average | 0.329847E+10 | 29831898.78 | 0.00 | 16714879.75 | 0.00 | 0.179356E+11 | 0.183811E+10 | 0.00 | 0.35 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
| Maximum of Months | 0.606744E+09 | 19792367.10 | 0.00 | 4401960.28 | 0.00 | 0.335829E+10 | 0.407878E+09 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: T NE APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.322284E+10 | 0.00 | 0.00 | 0.35 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.274658E+10 | 0.00 | 0.00 | 0.35 |
| March | 32836866.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.257629E+10 | 0.00 | 0.00 | 0.35 |
| April | 0.424498E+09 | 0.00 | 0.00 | 19771.05 | 0.00 | 0.122298E+10 | 11298864.89 | 0.00 | 0.35 |
| May | 0.605177E+09 | 0.00 | 0.00 | 1331973.54 | 0.00 | 0.141681E+09 | 0.277749E+09 | 0.00 | 0.35 |
| June | 0.200413E+09 | 6640968.23 | 0.00 | 3911489.44 | 0.00 | 42295.84 | 0.437469E+09 | 0.00 | 0.36 |
| July | 0.224709E+09 | 18258419.07 | 0.00 | 3562592.12 | 0.00 | 0.00 | 0.364960E+09 | 0.00 | 0.36 |
| August | 0.470494E+09 | 1743472.33 | 0.00 | 1848295.73 | 0.00 | 46552554.74 | 0.249068E+09 | 0.00 | 0.35 |
| September | 0.445303E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.754477E+09 | 0.00 | 0.00 | 0.35 |
| October | 36379700.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.197724E+10 | 0.00 | 0.00 | 0.35 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.312763E+10 | 0.00 | 0.00 | 0.35 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.335801E+10 | 0.00 | 0.00 | 0.35 |
| Annual Sum or Average | 0.243981E+10 | 26642859.62 | 0.00 | 10674121.87 | 0.00 | 0.191743E+11 | 0.134055E+10 | 0.00 | 0.35 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
| Maximum of Months | 0.605177E+09 | 18258419.07 | 0.00 | 3911489.44 | 0.00 | 0.335801E+10 | 0.437469E+09 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: T N1 APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.322710E+10 | 0.00 | 0.00 | 0.35 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.275053E+10 | 0.00 | 0.00 | 0.35 |
| March | 48936117.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.256647E+10 | 0.00 | 0.00 | 0.35 |
| April | 0.501658E+09 | 0.00 | 0.00 | 11.53 | 0.00 | 0.115849E+10 | 425762.75 | 0.00 | 0.35 |
| May | 0.783170E+09 | 0.00 | 0.00 | 578585.48 | 0.00 | 73993571.59 | 0.163545E+09 | 0.00 | 0.35 |
| June | 0.167513E+09 | 5941274.30 | 0.00 | 2953024.39 | 0.00 | 0.00 | 0.484000E+09 | 0.00 | 0.36 |
| July | 0.186187E+09 | 17021723.87 | 0.00 | 2686426.76 | 0.00 | 0.00 | 0.419264E+09 | 0.00 | 0.36 |
| August | 0.489865E+09 | 1668415.34 | 0.00 | 1369545.43 | 0.00 | 47156393.80 | 0.244442E+09 | 0.00 | 0.35 |
| September | 0.652066E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.550957E+09 | 0.00 | 0.00 | 0.35 |
| October | 95040174.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.192566E+10 | 0.00 | 0.00 | 0.35 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.312968E+10 | 0.00 | 0.00 | 0.35 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.336179E+10 | 0.00 | 0.00 | 0.35 |
| Annual Sum or Average | 0.292443E+10 | 24631413.51 | 0.00 | 7587593.60 | 0.00 | 0.187918E+11 | 0.131168E+10 | 0.00 | 0.35 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
| Maximum of Months | 0.783170E+09 | 17021723.87 | 0.00 | 2953024.39 | 0.00 | 0.336179E+10 | 0.484000E+09 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: T N2 APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.322709E+10 | 0.00 | 0.00 | 0.35 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.275053E+10 | 0.00 | 0.00 | 0.35 |
| March | 50187668.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.256522E+10 | 0.00 | 0.00 | 0.35 |
| April | 0.501705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115899E+10 | 0.00 | 0.00 | 0.35 |
| May | 0.771660E+09 | 0.00 | 0.00 | 626668.72 | 0.00 | 72038055.58 | 0.180697E+09 | 0.00 | 0.35 |
| June | 0.166612E+09 | 5959935.46 | 0.00 | 2984575.73 | 0.00 | 0.00 | 0.485089E+09 | 0.00 | 0.36 |
| July | 0.183769E+09 | 17063624.30 | 0.00 | 2722229.87 | 0.00 | 0.00 | 0.421497E+09 | 0.00 | 0.36 |
| August | 0.484341E+09 | 1671516.66 | 0.00 | 1401837.13 | 0.00 | 46580621.08 | 0.251449E+09 | 0.00 | 0.35 |
| September | 0.656043E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.547652E+09 | 0.00 | 0.00 | 0.35 |
| October | 96753569.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.192395E+10 | 0.00 | 0.00 | 0.35 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.312968E+10 | 0.00 | 0.00 | 0.35 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.336179E+10 | 0.00 | 0.00 | 0.35 |
| Annual Sum or Average | 0.291107E+10 | 24695076.42 | 0.00 | 7735311.45 | 0.00 | 0.187835E+11 | 0.133873E+10 | 0.00 | 0.35 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
| Maximum of Months | 0.771660E+09 | 17063624.30 | 0.00 | 2984575.73 | 0.00 | 0.336179E+10 | 0.485089E+09 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: T S1 APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.322694E+10 | 0.00 | 0.00 | 0.35 |
| February | 0.144789E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.260532E+10 | 0.00 | 0.00 | 0.35 |
| March | 0.594317E+09 | 0.00 | 0.00 | 19302.45 | 0.00 | 0.201919E+10 | 8345000.12 | 0.00 | 0.35 |
| April | 0.748297E+09 | 0.00 | 0.00 | 1216328.26 | 0.00 | 0.744404E+09 | 0.228317E+09 | 0.00 | 0.35 |
| May | 0.639245E+09 | 0.00 | 0.00 | 2356716.22 | 0.00 | 52539838.78 | 0.354902E+09 | 0.00 | 0.35 |
| June | 0.226836E+09 | 7369365.39 | 0.00 | 3400559.65 | 0.00 | 0.00 | 0.420002E+09 | 0.00 | 0.36 |
| July | 0.201174E+09 | 18920626.64 | 0.00 | 3099645.31 | 0.00 | 0.00 | 0.398107E+09 | 0.00 | 0.36 |
| August | 0.414787E+09 | 2224995.07 | 0.00 | 2886858.84 | 0.00 | 24566161.20 | 0.355724E+09 | 0.00 | 0.35 |
| September | 0.825908E+09 | 0.00 | 0.00 | 707999.82 | 0.00 | 0.290408E+09 | 0.144548E+09 | 0.00 | 0.35 |
| October | 0.374762E+09 | 0.00 | 0.00 | 23206.80 | 0.00 | 0.164710E+10 | 7596955.50 | 0.00 | 0.35 |
| November | 20463331.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.310892E+10 | 0.00 | 0.00 | 0.35 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.336208E+10 | 0.00 | 0.00 | 0.35 |
| Annual Sum or Average | 0.419058E+10 | 28514987.10 | 0.00 | 13710617.36 | 0.00 | 0.170815E+11 | 0.191754E+10 | 0.00 | 0.35 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
| Maximum of Months | 0.825908E+09 | 18920626.64 | 0.00 | 3400559.65 | 0.00 | 0.336208E+10 | 0.420002E+09 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: T S2 APARTMENT
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.322694E+10 | 0.00 | 0.00 | 0.35 |
| February | 0.145461E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.260465E+10 | 0.00 | 0.00 | 0.35 |
| March | 0.596797E+09 | 0.00 | 0.00 | 21186.34 | 0.00 | 0.201636E+10 | 8997781.01 | 0.00 | 0.35 |
| April | 0.746496E+09 | 0.00 | 0.00 | 1224964.79 | 0.00 | 0.744659E+09 | 0.229878E+09 | 0.00 | 0.35 |
| May | 0.635165E+09 | 0.00 | 0.00 | 2408626.71 | 0.00 | 52898548.69 | 0.359605E+09 | 0.00 | 0.35 |
| June | 0.223876E+09 | 7379848.98 | 0.00 | 3439560.41 | 0.00 | 0.00 | 0.423330E+09 | 0.00 | 0.36 |
| July | 0.198416E+09 | 18949972.85 | 0.00 | 3140358.86 | 0.00 | 0.00 | 0.400784E+09 | 0.00 | 0.36 |
| August | 0.411203E+09 | 2226981.79 | 0.00 | 2918430.23 | 0.00 | 23415296.45 | 0.360956E+09 | 0.00 | 0.35 |
| September | 0.825754E+09 | 0.00 | 0.00 | 722073.85 | 0.00 | 0.288309E+09 | 0.147506E+09 | 0.00 | 0.35 |
| October | 0.378285E+09 | 0.00 | 0.00 | 24689.24 | 0.00 | 0.164323E+10 | 8168343.95 | 0.00 | 0.35 |
| November | 20463334.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.310892E+10 | 0.00 | 0.00 | 0.35 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.336208E+10 | 0.00 | 0.00 | 0.35 |
| Annual Sum or Average | 0.418192E+10 | 28556803.63 | 0.00 | 13899890.43 | 0.00 | 0.170715E+11 | 0.193923E+10 | 0.00 | 0.35 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
| Maximum of Months | 0.825754E+09 | 18949972.85 | 0.00 | 3439560.41 | 0.00 | 0.336208E+10 | 0.423330E+09 | 0.00 | 0.36 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 09:14:30
Custom Monthly Report| SITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
| January | 0.163499E+10 | 0.198512E+11 | 0.00 | 0.425669E+10 | 0.477520E+11 |
| February | 0.353570E+11 | 0.165633E+11 | 0.00 | 0.361796E+10 | 0.371604E+11 |
| March | 0.123542E+12 | 0.207870E+11 | 0.00 | 0.342211E+10 | 0.300152E+11 |
| April | 0.193486E+12 | 0.182677E+11 | 0.00 | 0.224782E+10 | 0.156494E+11 |
| May | 0.230436E+12 | 0.143833E+11 | 0.00 | 0.160554E+10 | 0.251930E+11 |
| June | 0.235299E+12 | 0.123351E+11 | 0.00 | 0.114541E+10 | 0.639993E+11 |
| July | 0.214201E+12 | 0.908868E+10 | 0.00 | 0.112670E+10 | 0.775861E+11 |
| August | 0.163960E+12 | 0.114608E+11 | 0.00 | 0.140782E+10 | 0.474662E+11 |
| September | 0.842048E+11 | 0.951833E+10 | 0.00 | 0.194478E+10 | 0.874954E+10 |
| October | 0.425480E+11 | 0.173360E+11 | 0.00 | 0.269684E+10 | 0.208341E+11 |
| November | 0.114016E+11 | 0.124280E+11 | 0.00 | 0.413242E+10 | 0.418826E+11 |
| December | -0.619659E+10 | 0.176672E+11 | 0.00 | 0.445345E+10 | 0.500295E+11 |
| Annual Sum or Average | 0.132987E+13 | 0.179687E+12 | 0.00 | 0.320575E+11 | 0.466317E+12 |
| Minimum of Months | -0.619659E+10 | 0.908868E+10 | 0.00 | 0.112670E+10 | 0.874954E+10 |
| Maximum of Months | 0.235299E+12 | 0.207870E+11 | 0.00 | 0.445345E+10 | 0.775861E+11 |