Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 09:14
Tabular Output Report in Format: HTML
Building: ApartmentMidRise
Environment: RUNPERIOD 1 ** Buffalo Niagara Intl AP NY USA TMY3 WMO#=725280
Simulation Timestamp: 2023-10-16 09:14:20
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 09:14:20
Values gathered over 8760.00 hours| Total Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
| Total Site Energy | 1874.23 | 597.92 | 663.69 |
| Net Site Energy | 1874.23 | 597.92 | 663.69 |
| Total Source Energy | 4659.81 | 1486.57 | 1650.09 |
| Net Source Energy | 4659.81 | 1486.57 | 1650.09 |
| Site=>Source Conversion Factor | |
| Electricity | 3.167 |
| Natural Gas | 1.084 |
| District Cooling | 1.056 |
| District Heating | 3.613 |
| Steam | 1.200 |
| Gasoline | 1.050 |
| Diesel | 1.050 |
| Coal | 1.050 |
| Fuel Oil No 1 | 1.050 |
| Fuel Oil No 2 | 1.050 |
| Propane | 1.050 |
| Other Fuel 1 | 1.000 |
| Other Fuel 2 | 1.000 |
| Area [m2] | |
| Total Building Area | 3134.61 |
| Net Conditioned Building Area | 2823.98 |
| Unconditioned Building Area | 310.64 |
| Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
| Heating | 0.00 | 612.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Cooling | 77.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Lighting | 99.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Lighting | 50.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment | 458.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans | 96.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems | 480.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1875.32 |
| Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Total End Uses | 1261.71 | 612.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1875.32 |
| Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
| Heating | General | 0.00 | 612.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Cooling | General | 77.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Lighting | LightsWired | 94.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LightsPlugIn | 4.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Exterior Lighting | General | 50.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment | MiscPlug | 388.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| ElevatorLift | 65.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| ElevatorLightsFan | 5.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| General | 96.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems | Water Heater | 480.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1875.32 |
| Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
| Heating | Unassigned | 0.00 | 612.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Cooling | Unassigned | 77.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Lighting | GENERAL | 99.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Lighting | Unassigned | 50.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment | GENERAL | 458.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans | Unassigned | 96.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Pumps | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems | Unassigned | 480.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1875.32 |
| Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
| Lighting | 52.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| HVAC | 231.53 | 216.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.66 |
| Other | 162.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Total | 446.78 | 216.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.66 |
| Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
| Lighting | 47.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| HVAC | 208.58 | 195.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.60 |
| Other | 146.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Total | 402.51 | 195.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.60 |
| Electricity [GJ] | Percent Electricity [%] | |
| Fuel-Fired Power Generation | 0.000 | 0.00 |
| High Temperature Geothermal* | 0.000 | 0.00 |
| Photovoltaic Power | 0.000 | 0.00 |
| Wind Power | 0.000 | 0.00 |
| Power Conversion | 0.000 | 0.00 |
| Net Decrease in On-Site Storage | 0.000 | 0.00 |
| Total On-Site Electric Sources | 0.000 | 0.00 |
| Electricity Coming From Utility | 1261.709 | 100.00 |
| Surplus Electricity Going To Utility | 0.000 | 0.00 |
| Net Electricity From Utility | 1261.709 | 100.00 |
| Total On-Site and Utility Electric Sources | 1261.709 | 100.00 |
| Total Electricity End Uses | 1261.709 | 100.00 |
| Heat [GJ] | Percent Heat [%] | |
| Water-Side Heat Recovery | 0.00 | 0.00 |
| Air to Air Heat Recovery for Cooling | 0.00 | 49.88 |
| Air to Air Heat Recovery for Heating | 0.00 | 50.12 |
| High-Temperature Geothermal* | 0.00 | 0.00 |
| Solar Water Thermal | 0.00 | 0.00 |
| Solar Air Thermal | 0.00 | 0.00 |
| Total On-Site Thermal Sources | 0.00 | 100.00 |
| Water [m3] | Percent Water [%] | |
| Rainwater Collection | 0.00 | 0.00 |
| Condensate Collection | 0.00 | 0.00 |
| Groundwater Well | 0.00 | 0.00 |
| Total On Site Water Sources | 0.00 | 0.00 |
| - | - | - |
| Initial Storage | 0.00 | 0.00 |
| Final Storage | 0.00 | 0.00 |
| Change in Storage | 0.00 | 0.00 |
| - | - | - |
| Water Supplied by Utility | 1875.32 | 100.00 |
| - | - | - |
| Total On Site, Change in Storage, and Utility Water Sources | 1875.32 | 100.00 |
| Total Water End Uses | 1875.32 | 100.00 |
| Degrees [deltaC] | |
| Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
| Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
| Facility [Hours] | |
| Time Setpoint Not Met During Occupied Heating | 0.00 |
| Time Setpoint Not Met During Occupied Cooling | 0.00 |
| Time Not Comfortable Based on Simple ASHRAE 55-2004 | 8752.00 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2012
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME APARTMENTMIDRISE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 5A
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NY_BUFFALO
| Environment |ZoneCoolingSummaryMonthly
| G SW APARTMENT | G NW APARTMENT | OFFICE | G NE APARTMENT | G N1 APARTMENT | G N2 APARTMENT | G S1 APARTMENT | G S2 APARTMENT | M SW APARTMENT | M NW APARTMENT | M SE APARTMENT | M NE APARTMENT | M N1 APARTMENT | M N2 APARTMENT | M S1 APARTMENT | M S2 APARTMENT | T SW APARTMENT | T NW APARTMENT | T SE APARTMENT | T NE APARTMENT | T N1 APARTMENT | T N2 APARTMENT | T S1 APARTMENT | T S2 APARTMENT | T CORRIDOR | G CORRIDOR | M CORRIDOR |ZoneHeatingSummaryMonthly
| G SW APARTMENT | G NW APARTMENT | OFFICE | G NE APARTMENT | G N1 APARTMENT | G N2 APARTMENT | G S1 APARTMENT | G S2 APARTMENT | M SW APARTMENT | M NW APARTMENT | M SE APARTMENT | M NE APARTMENT | M N1 APARTMENT | M N2 APARTMENT | M S1 APARTMENT | M S2 APARTMENT | T SW APARTMENT | T NW APARTMENT | T SE APARTMENT | T NE APARTMENT | T N1 APARTMENT | T N2 APARTMENT | T S1 APARTMENT | T S2 APARTMENT | T CORRIDOR | G CORRIDOR | M CORRIDOR |ZoneElectricSummaryMonthly
| G SW APARTMENT | G NW APARTMENT | OFFICE | G NE APARTMENT | G N1 APARTMENT | G N2 APARTMENT | G S1 APARTMENT | G S2 APARTMENT | M SW APARTMENT | M NW APARTMENT | M SE APARTMENT | M NE APARTMENT | M N1 APARTMENT | M N2 APARTMENT | M S1 APARTMENT | M S2 APARTMENT | T SW APARTMENT | T NW APARTMENT | T SE APARTMENT | T NE APARTMENT | T N1 APARTMENT | T N2 APARTMENT | T S1 APARTMENT | T S2 APARTMENT | T CORRIDOR | G CORRIDOR | M CORRIDOR |SpaceGainsMonthly
| G SW APARTMENT | G NW APARTMENT | OFFICE | G NE APARTMENT | G N1 APARTMENT | G N2 APARTMENT | G S1 APARTMENT | G S2 APARTMENT | M SW APARTMENT | M NW APARTMENT | M SE APARTMENT | M NE APARTMENT | M N1 APARTMENT | M N2 APARTMENT | M S1 APARTMENT | M S2 APARTMENT | T SW APARTMENT | T NW APARTMENT | T SE APARTMENT | T NE APARTMENT | T N1 APARTMENT | T N2 APARTMENT | T S1 APARTMENT | T S2 APARTMENT | T CORRIDOR | G CORRIDOR | M CORRIDOR |PeakSpaceGainsMonthly
| G SW APARTMENT | G NW APARTMENT | OFFICE | G NE APARTMENT | G N1 APARTMENT | G N2 APARTMENT | G S1 APARTMENT | G S2 APARTMENT | M SW APARTMENT | M NW APARTMENT | M SE APARTMENT | M NE APARTMENT | M N1 APARTMENT | M N2 APARTMENT | M S1 APARTMENT | M S2 APARTMENT | T SW APARTMENT | T NW APARTMENT | T SE APARTMENT | T NE APARTMENT | T N1 APARTMENT | T N2 APARTMENT | T S1 APARTMENT | T S2 APARTMENT | T CORRIDOR | G CORRIDOR | M CORRIDOR |SpaceGainComponentsAtCoolingPeakMonthly
| G SW APARTMENT | G NW APARTMENT | OFFICE | G NE APARTMENT | G N1 APARTMENT | G N2 APARTMENT | G S1 APARTMENT | G S2 APARTMENT | M SW APARTMENT | M NW APARTMENT | M SE APARTMENT | M NE APARTMENT | M N1 APARTMENT | M N2 APARTMENT | M S1 APARTMENT | M S2 APARTMENT | T SW APARTMENT | T NW APARTMENT | T SE APARTMENT | T NE APARTMENT | T N1 APARTMENT | T N2 APARTMENT | T S1 APARTMENT | T S2 APARTMENT | T CORRIDOR | G CORRIDOR | M CORRIDOR |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| G SW APARTMENT | G NW APARTMENT | OFFICE | G NE APARTMENT | G N1 APARTMENT | G N2 APARTMENT | G S1 APARTMENT | G S2 APARTMENT | M SW APARTMENT | M NW APARTMENT | M SE APARTMENT | M NE APARTMENT | M N1 APARTMENT | M N2 APARTMENT | M S1 APARTMENT | M S2 APARTMENT | T SW APARTMENT | T NW APARTMENT | T SE APARTMENT | T NE APARTMENT | T N1 APARTMENT | T N2 APARTMENT | T S1 APARTMENT | T S2 APARTMENT | T CORRIDOR | G CORRIDOR | M CORRIDOR |ComfortReportSimple55Monthly
| G SW APARTMENT | G NW APARTMENT | OFFICE | G NE APARTMENT | G N1 APARTMENT | G N2 APARTMENT | G S1 APARTMENT | G S2 APARTMENT | M SW APARTMENT | M NW APARTMENT | M SE APARTMENT | M NE APARTMENT | M N1 APARTMENT | M N2 APARTMENT | M S1 APARTMENT | M S2 APARTMENT | T SW APARTMENT | T NW APARTMENT | T SE APARTMENT | T NE APARTMENT | T N1 APARTMENT | T N2 APARTMENT | T S1 APARTMENT | T S2 APARTMENT | T CORRIDOR | G CORRIDOR | M CORRIDOR |OccupantComfortDataSummaryMonthly
| OCCUP_GSW | OCCUP_GNW | OCCUP_OFFICE | OCCUP_GNE | OCCUP_GN1 | OCCUP_GN2 | OCCUP_GS1 | OCCUP_GS2 | OCCUP_MSW | OCCUP_MNW | OCCUP_MSE | OCCUP_MNE | OCCUP_MN1 | OCCUP_MN2 | OCCUP_MS1 | OCCUP_MS2 | OCCUP_TSW | OCCUP_TNW | OCCUP_TSE | OCCUP_TNE | OCCUP_TN1 | OCCUP_TN2 | OCCUP_TS1 | OCCUP_TS2 | OCCUP_T CORRIDOR | OCCUP_G CORRIDOR | OCCUP_M CORRIDOR |DXReportMonthly
| SPLIT GSW COOLING COIL | SPLIT GNW COOLING COIL | SPLIT OFFICE COOLING COIL | SPLIT GNE COOLING COIL | SPLIT GN1 COOLING COIL | SPLIT GN2 COOLING COIL | SPLIT GS1 COOLING COIL | SPLIT GS2 COOLING COIL | SPLIT MSW COOLING COIL | SPLIT MNW COOLING COIL | SPLIT MSE COOLING COIL | SPLIT MNE COOLING COIL | SPLIT MN1 COOLING COIL | SPLIT MN2 COOLING COIL | SPLIT MS1 COOLING COIL | SPLIT MS2 COOLING COIL | SPLIT TSW COOLING COIL | SPLIT TNW COOLING COIL | SPLIT TSE COOLING COIL | SPLIT TNE COOLING COIL | SPLIT TN1 COOLING COIL | SPLIT TN2 COOLING COIL | SPLIT TS1 COOLING COIL | SPLIT TS2 COOLING COIL |WindowReportMonthly
| GWINDOW1 S SWA | GWINDOW1 W SWA | GWINDOW1 W NWA | GWINDOW1 N NWA | GWINDOW1 S SEA | GWINDOW1 E SEA | GWINDOW1 E NEA | GWINDOW1 N NEA | GWINDOW1 N N1A | GWINDOW1 N N2A | GWINDOW1 S S1A | GWINDOW1 S S2A | MWINDOW1 S SWA | MWINDOW1 W SWA | MWINDOW1 W NWA | MWINDOW1 N NWA | MWINDOW1 S SEA | MWINDOW1 E SEA | MWINDOW1 E NEA | MWINDOW1 N NEA | MWINDOW1 N N1A | MWINDOW1 N N2A | MWINDOW1 S S1A | MWINDOW1 S S2A | TWINDOW1 S SWA | TWINDOW1 W SWA | TWINDOW1 W NWA | TWINDOW1 N NWA | TWINDOW1 S SEA | TWINDOW1 E SEA | TWINDOW1 E NEA | TWINDOW1 N NEA | TWINDOW1 N N1A | TWINDOW1 N N2A | TWINDOW1 S S1A | TWINDOW1 S S2A | TWINDOW14 | ENTRANCE DOOR | MWINDOW14 |WindowEnergyReportMonthly
| GWINDOW1 S SWA | GWINDOW1 W SWA | GWINDOW1 W NWA | GWINDOW1 N NWA | GWINDOW1 S SEA | GWINDOW1 E SEA | GWINDOW1 E NEA | GWINDOW1 N NEA | GWINDOW1 N N1A | GWINDOW1 N N2A | GWINDOW1 S S1A | GWINDOW1 S S2A | MWINDOW1 S SWA | MWINDOW1 W SWA | MWINDOW1 W NWA | MWINDOW1 N NWA | MWINDOW1 S SEA | MWINDOW1 E SEA | MWINDOW1 E NEA | MWINDOW1 N NEA | MWINDOW1 N N1A | MWINDOW1 N N2A | MWINDOW1 S S1A | MWINDOW1 S S2A | TWINDOW1 S SWA | TWINDOW1 W SWA | TWINDOW1 W NWA | TWINDOW1 N NWA | TWINDOW1 S SEA | TWINDOW1 E SEA | TWINDOW1 E NEA | TWINDOW1 N NEA | TWINDOW1 N N1A | TWINDOW1 N N2A | TWINDOW1 S S1A | TWINDOW1 S S2A | TWINDOW14 | ENTRANCE DOOR | MWINDOW14 |WindowZoneSummaryMonthly
| G SW APARTMENT | G NW APARTMENT | OFFICE | G NE APARTMENT | G N1 APARTMENT | G N2 APARTMENT | G S1 APARTMENT | G S2 APARTMENT | M SW APARTMENT | M NW APARTMENT | M SE APARTMENT | M NE APARTMENT | M N1 APARTMENT | M N2 APARTMENT | M S1 APARTMENT | M S2 APARTMENT | T SW APARTMENT | T NW APARTMENT | T SE APARTMENT | T NE APARTMENT | T N1 APARTMENT | T N2 APARTMENT | T S1 APARTMENT | T S2 APARTMENT | T CORRIDOR | G CORRIDOR | M CORRIDOR |WindowEnergyZoneSummaryMonthly
| G SW APARTMENT | G NW APARTMENT | OFFICE | G NE APARTMENT | G N1 APARTMENT | G N2 APARTMENT | G S1 APARTMENT | G S2 APARTMENT | M SW APARTMENT | M NW APARTMENT | M SE APARTMENT | M NE APARTMENT | M N1 APARTMENT | M N2 APARTMENT | M S1 APARTMENT | M S2 APARTMENT | T SW APARTMENT | T NW APARTMENT | T SE APARTMENT | T NE APARTMENT | T N1 APARTMENT | T N2 APARTMENT | T S1 APARTMENT | T S2 APARTMENT | T CORRIDOR | G CORRIDOR | M CORRIDOR |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| G SW APARTMENT WATER HEATER | G NW APARTMENT WATER HEATER | G NE APARTMENT WATER HEATER | G N1 APARTMENT WATER HEATER | G N2 APARTMENT WATER HEATER | G S1 APARTMENT WATER HEATER | G S2 APARTMENT WATER HEATER | M SW APARTMENT WATER HEATER | M NW APARTMENT WATER HEATER | M SE APARTMENT WATER HEATER | M NE APARTMENT WATER HEATER | M N1 APARTMENT WATER HEATER | M N2 APARTMENT WATER HEATER | M S1 APARTMENT WATER HEATER | M S2 APARTMENT WATER HEATER | T SW APARTMENT WATER HEATER | T NW APARTMENT WATER HEATER | T SE APARTMENT WATER HEATER | T NE APARTMENT WATER HEATER | T N1 APARTMENT WATER HEATER | T N2 APARTMENT WATER HEATER | T S1 APARTMENT WATER HEATER | T S2 APARTMENT WATER HEATER |DaylightingReportMonthly
| Environment |CoilReportMonthly
| SPLIT GSW HEATING COIL | SPLIT GNW HEATING COIL | SPLIT OFFICE HEATING COIL | SPLIT GNE HEATING COIL | SPLIT GN1 HEATING COIL | SPLIT GN2 HEATING COIL | SPLIT GS1 HEATING COIL | SPLIT GS2 HEATING COIL | SPLIT MSW HEATING COIL | SPLIT MNW HEATING COIL | SPLIT MSE HEATING COIL | SPLIT MNE HEATING COIL | SPLIT MN1 HEATING COIL | SPLIT MN2 HEATING COIL | SPLIT MS1 HEATING COIL | SPLIT MS2 HEATING COIL | SPLIT TSW HEATING COIL | SPLIT TNW HEATING COIL | SPLIT TSE HEATING COIL | SPLIT TNE HEATING COIL | SPLIT TN1 HEATING COIL | SPLIT TN2 HEATING COIL | SPLIT TS1 HEATING COIL | SPLIT TS2 HEATING COIL | SPLIT GSW COOLING COIL | SPLIT GNW COOLING COIL | SPLIT OFFICE COOLING COIL | SPLIT GNE COOLING COIL | SPLIT GN1 COOLING COIL | SPLIT GN2 COOLING COIL | SPLIT GS1 COOLING COIL | SPLIT GS2 COOLING COIL | SPLIT MSW COOLING COIL | SPLIT MNW COOLING COIL | SPLIT MSE COOLING COIL | SPLIT MNE COOLING COIL | SPLIT MN1 COOLING COIL | SPLIT MN2 COOLING COIL | SPLIT MS1 COOLING COIL | SPLIT MS2 COOLING COIL | SPLIT TSW COOLING COIL | SPLIT TNW COOLING COIL | SPLIT TSE COOLING COIL | SPLIT TNE COOLING COIL | SPLIT TN1 COOLING COIL | SPLIT TN2 COOLING COIL | SPLIT TS1 COOLING COIL | SPLIT TS2 COOLING COIL |FanReportMonthly
| SPLIT GSW SUPPLY FAN | G SW APARTMENT ERV SUP FAN | G SW APARTMENT ERV EXH FAN | SPLIT GNW SUPPLY FAN | G NW APARTMENT ERV SUP FAN | G NW APARTMENT ERV EXH FAN | SPLIT OFFICE SUPPLY FAN | SPLIT GNE SUPPLY FAN | G NE APARTMENT ERV SUP FAN | G NE APARTMENT ERV EXH FAN | SPLIT GN1 SUPPLY FAN | G N1 APARTMENT ERV SUP FAN | G N1 APARTMENT ERV EXH FAN | SPLIT GN2 SUPPLY FAN | G N2 APARTMENT ERV SUP FAN | G N2 APARTMENT ERV EXH FAN | SPLIT GS1 SUPPLY FAN | G S1 APARTMENT ERV SUP FAN | G S1 APARTMENT ERV EXH FAN | SPLIT GS2 SUPPLY FAN | G S2 APARTMENT ERV SUP FAN | G S2 APARTMENT ERV EXH FAN | SPLIT MSW SUPPLY FAN | M SW APARTMENT ERV SUP FAN | M SW APARTMENT ERV EXH FAN | SPLIT MNW SUPPLY FAN | M NW APARTMENT ERV SUP FAN | M NW APARTMENT ERV EXH FAN | SPLIT MSE SUPPLY FAN | M SE APARTMENT ERV SUP FAN | M SE APARTMENT ERV EXH FAN | SPLIT MNE SUPPLY FAN | M NE APARTMENT ERV SUP FAN | M NE APARTMENT ERV EXH FAN | SPLIT MN1 SUPPLY FAN | M N1 APARTMENT ERV SUP FAN | M N1 APARTMENT ERV EXH FAN | SPLIT MN2 SUPPLY FAN | M N2 APARTMENT ERV SUP FAN | M N2 APARTMENT ERV EXH FAN | SPLIT MS1 SUPPLY FAN | M S1 APARTMENT ERV SUP FAN | M S1 APARTMENT ERV EXH FAN | SPLIT MS2 SUPPLY FAN | M S2 APARTMENT ERV SUP FAN | M S2 APARTMENT ERV EXH FAN | SPLIT TSW SUPPLY FAN | T SW APARTMENT ERV SUP FAN | T SW APARTMENT ERV EXH FAN | SPLIT TNW SUPPLY FAN | T NW APARTMENT ERV SUP FAN | T NW APARTMENT ERV EXH FAN | SPLIT TSE SUPPLY FAN | T SE APARTMENT ERV SUP FAN | T SE APARTMENT ERV EXH FAN | SPLIT TNE SUPPLY FAN | T NE APARTMENT ERV SUP FAN | T NE APARTMENT ERV EXH FAN | SPLIT TN1 SUPPLY FAN | T N1 APARTMENT ERV SUP FAN | T N1 APARTMENT ERV EXH FAN | SPLIT TN2 SUPPLY FAN | T N2 APARTMENT ERV SUP FAN | T N2 APARTMENT ERV EXH FAN | SPLIT TS1 SUPPLY FAN | T S1 APARTMENT ERV SUP FAN | T S1 APARTMENT ERV EXH FAN | SPLIT TS2 SUPPLY FAN | T S2 APARTMENT ERV SUP FAN | T S2 APARTMENT ERV EXH FAN |ZoneTemperatureOscillationReportMonthly
| G SW APARTMENT | G NW APARTMENT | OFFICE | G NE APARTMENT | G N1 APARTMENT | G N2 APARTMENT | G S1 APARTMENT | G S2 APARTMENT | M SW APARTMENT | M NW APARTMENT | M SE APARTMENT | M NE APARTMENT | M N1 APARTMENT | M N2 APARTMENT | M S1 APARTMENT | M S2 APARTMENT | T SW APARTMENT | T NW APARTMENT | T SE APARTMENT | T NE APARTMENT | T N1 APARTMENT | T N2 APARTMENT | T S1 APARTMENT | T S2 APARTMENT | T CORRIDOR | G CORRIDOR | M CORRIDOR |AirLoopSystemEnergyAndWaterUseMonthly
| SPLIT GSW | SPLIT GNW | SPLIT OFFICE | SPLIT GNE | SPLIT GN1 | SPLIT GN2 | SPLIT GS1 | SPLIT GS2 | SPLIT MSW | SPLIT MNW | SPLIT MSE | SPLIT MNE | SPLIT MN1 | SPLIT MN2 | SPLIT MS1 | SPLIT MS2 | SPLIT TSW | SPLIT TNW | SPLIT TSE | SPLIT TNE | SPLIT TN1 | SPLIT TN2 | SPLIT TS1 | SPLIT TS2 |AirLoopSystemComponentLoadsMonthly
| SPLIT GSW | SPLIT GNW | SPLIT OFFICE | SPLIT GNE | SPLIT GN1 | SPLIT GN2 | SPLIT GS1 | SPLIT GS2 | SPLIT MSW | SPLIT MNW | SPLIT MSE | SPLIT MNE | SPLIT MN1 | SPLIT MN2 | SPLIT MS1 | SPLIT MS2 | SPLIT TSW | SPLIT TNW | SPLIT TSE | SPLIT TNE | SPLIT TN1 | SPLIT TN2 | SPLIT TS1 | SPLIT TS2 |AirLoopSystemComponentEnergyUseMonthly
| SPLIT GSW | SPLIT GNW | SPLIT OFFICE | SPLIT GNE | SPLIT GN1 | SPLIT GN2 | SPLIT GS1 | SPLIT GS2 | SPLIT MSW | SPLIT MNW | SPLIT MSE | SPLIT MNE | SPLIT MN1 | SPLIT MN2 | SPLIT MS1 | SPLIT MS2 | SPLIT TSW | SPLIT TNW | SPLIT TSE | SPLIT TNE | SPLIT TN1 | SPLIT TN2 | SPLIT TS1 | SPLIT TS2 |MechanicalVentilationLoadsMonthly
| G SW APARTMENT | G NW APARTMENT | OFFICE | G NE APARTMENT | G N1 APARTMENT | G N2 APARTMENT | G S1 APARTMENT | G S2 APARTMENT | M SW APARTMENT | M NW APARTMENT | M SE APARTMENT | M NE APARTMENT | M N1 APARTMENT | M N2 APARTMENT | M S1 APARTMENT | M S2 APARTMENT | T SW APARTMENT | T NW APARTMENT | T SE APARTMENT | T NE APARTMENT | T N1 APARTMENT | T N2 APARTMENT | T S1 APARTMENT | T S2 APARTMENT |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 09:14:20
General| Value | |
| Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 09:14 |
| RunPeriod | RUNPERIOD 1 |
| Weather File | Buffalo Niagara Intl AP NY USA TMY3 WMO#=725280 |
| Latitude [deg] | 42.93 |
| Longitude [deg] | -78.7 |
| Elevation [m] | 215.00 |
| Time Zone | -5.0 |
| North Axis Angle [deg] | 0.00 |
| Rotation for Appendix G [deg] | 0.00 |
| Hours Simulated [hrs] | 8760.00 |
| Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
| Gross Wall Area [m2] | 1542.04 | 564.80 | 206.22 | 564.80 | 206.22 |
| Above Ground Wall Area [m2] | 1542.04 | 564.80 | 206.22 | 564.80 | 206.22 |
| Window Opening Area [m2] | 306.92 | 112.97 | 43.82 | 112.97 | 37.16 |
| Gross Window-Wall Ratio [%] | 19.90 | 20.00 | 21.25 | 20.00 | 18.02 |
| Above Ground Window-Wall Ratio [%] | 19.90 | 20.00 | 21.25 | 20.00 | 18.02 |
| Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
| Gross Wall Area [m2] | 1501.17 | 564.80 | 185.79 | 564.80 | 185.79 |
| Above Ground Wall Area [m2] | 1501.17 | 564.80 | 185.79 | 564.80 | 185.79 |
| Window Opening Area [m2] | 300.26 | 112.97 | 37.16 | 112.97 | 37.16 |
| Gross Window-Wall Ratio [%] | 20.00 | 20.00 | 20.00 | 20.00 | 20.00 |
| Above Ground Window-Wall Ratio [%] | 20.00 | 20.00 | 20.00 | 20.00 | 20.00 |
| Total | |
| Gross Roof Area [m2] | 783.65 |
| Skylight Area [m2] | 0.00 |
| Skylight-Roof Ratio [%] | 0.00 |
| Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
| G SW APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 0.00 | 11.71 | 11.71 | 8.6918 | 35.30 | 6.6700 |
| G NW APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 0.00 | 11.71 | 11.71 | 8.6918 | 35.30 | 6.6700 |
| OFFICE | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 0.00 | 11.71 | 11.71 | 9.7532 | 18.58 | 6.6700 |
| G NE APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 0.00 | 11.71 | 11.71 | 8.6918 | 35.30 | 6.6700 |
| G N1 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 0.00 | 7.06 | 7.06 | 8.6918 | 35.30 | 6.6700 |
| G N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 0.00 | 7.06 | 7.06 | 8.6918 | 35.30 | 6.6700 |
| G S1 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 0.00 | 7.06 | 7.06 | 8.6918 | 35.30 | 6.6700 |
| G S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 0.00 | 7.06 | 7.06 | 8.6918 | 35.30 | 6.6700 |
| M SW APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 58.52 | 0.00 | 11.71 | 11.71 | 8.6918 | 35.30 | 6.6700 |
| M NW APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 58.52 | 0.00 | 11.71 | 11.71 | 8.6918 | 35.30 | 6.6700 |
| M SE APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 58.52 | 0.00 | 11.71 | 11.71 | 8.6918 | 35.30 | 6.6700 |
| M NE APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 58.52 | 0.00 | 11.71 | 11.71 | 8.6918 | 35.30 | 6.6700 |
| M N1 APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 35.30 | 0.00 | 7.06 | 7.06 | 8.6918 | 35.30 | 6.6700 |
| M N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 35.30 | 0.00 | 7.06 | 7.06 | 8.6918 | 35.30 | 6.6700 |
| M S1 APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 35.30 | 0.00 | 7.06 | 7.06 | 8.6918 | 35.30 | 6.6700 |
| M S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 35.30 | 0.00 | 7.06 | 7.06 | 8.6918 | 35.30 | 6.6700 |
| T SW APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 0.00 | 11.71 | 11.71 | 8.6918 | 35.30 | 6.6700 |
| T NW APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 0.00 | 11.71 | 11.71 | 8.6918 | 35.30 | 6.6700 |
| T SE APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 0.00 | 11.71 | 11.71 | 8.6918 | 35.30 | 6.6700 |
| T NE APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 0.00 | 11.71 | 11.71 | 8.6918 | 35.30 | 6.6700 |
| T N1 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 0.00 | 7.06 | 7.06 | 8.6918 | 35.30 | 6.6700 |
| T N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 0.00 | 7.06 | 7.06 | 8.6918 | 35.30 | 6.6700 |
| T S1 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 0.00 | 7.06 | 7.06 | 8.6918 | 35.30 | 6.6700 |
| T S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 0.00 | 7.06 | 7.06 | 8.6918 | 35.30 | 6.6700 |
| T CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 0.00 | 1.11 | 1.11 | 4.7725 | 18.58 | 0.0000 |
| G CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 0.00 | 3.32 | 3.32 | 4.7725 | 18.58 | 105.2565 |
| M CORRIDOR | 77.66 | No | Yes | 236.69 | 2.00 | 10.22 | 0.00 | 1.11 | 1.11 | 4.7725 | 18.58 | 0.0000 |
| Total | 3134.61 | 9553.84 | 1542.04 | 0.00 | 306.92 | 306.92 | 8.3333 | 31.67 | 8.6167 | |||
| Conditioned Total | 2823.98 | 8607.06 | 1501.17 | 0.00 | 300.26 | 300.26 | 8.7250 | 34.33 | 6.6700 | |||
| Unconditioned Total | 310.64 | 946.78 | 40.87 | 0.00 | 6.66 | 6.66 | 4.7725 | 18.58 | 26.3141 | |||
| Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
| G SW APARTMENT | 88.25 | Yes | Yes | 1.00 | G SW APARTMENT | GENERAL | G SW APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| G NW APARTMENT | 88.25 | Yes | Yes | 1.00 | G NW APARTMENT | GENERAL | G NW APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| OFFICE | 88.25 | Yes | Yes | 1.00 | OFFICE | GENERAL | OFFICE | 9.7532 | 18.58 | 6.6700 | |
| G NE APARTMENT | 88.25 | Yes | Yes | 1.00 | G NE APARTMENT | GENERAL | G NE APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| G N1 APARTMENT | 88.25 | Yes | Yes | 1.00 | G N1 APARTMENT | GENERAL | G N1 APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| G N2 APARTMENT | 88.25 | Yes | Yes | 1.00 | G N2 APARTMENT | GENERAL | G N2 APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| G S1 APARTMENT | 88.25 | Yes | Yes | 1.00 | G S1 APARTMENT | GENERAL | G S1 APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| G S2 APARTMENT | 88.25 | Yes | Yes | 1.00 | G S2 APARTMENT | GENERAL | G S2 APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| M SW APARTMENT | 88.25 | Yes | Yes | 2.00 | M SW APARTMENT | GENERAL | M SW APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| M NW APARTMENT | 88.25 | Yes | Yes | 2.00 | M NW APARTMENT | GENERAL | M NW APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| M SE APARTMENT | 88.25 | Yes | Yes | 2.00 | M SE APARTMENT | GENERAL | M SE APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| M NE APARTMENT | 88.25 | Yes | Yes | 2.00 | M NE APARTMENT | GENERAL | M NE APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| M N1 APARTMENT | 88.25 | Yes | Yes | 2.00 | M N1 APARTMENT | GENERAL | M N1 APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| M N2 APARTMENT | 88.25 | Yes | Yes | 2.00 | M N2 APARTMENT | GENERAL | M N2 APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| M S1 APARTMENT | 88.25 | Yes | Yes | 2.00 | M S1 APARTMENT | GENERAL | M S1 APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| M S2 APARTMENT | 88.25 | Yes | Yes | 2.00 | M S2 APARTMENT | GENERAL | M S2 APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| T SW APARTMENT | 88.25 | Yes | Yes | 1.00 | T SW APARTMENT | GENERAL | T SW APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| T NW APARTMENT | 88.25 | Yes | Yes | 1.00 | T NW APARTMENT | GENERAL | T NW APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| T SE APARTMENT | 88.25 | Yes | Yes | 1.00 | T SE APARTMENT | GENERAL | T SE APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| T NE APARTMENT | 88.25 | Yes | Yes | 1.00 | T NE APARTMENT | GENERAL | T NE APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| T N1 APARTMENT | 88.25 | Yes | Yes | 1.00 | T N1 APARTMENT | GENERAL | T N1 APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| T N2 APARTMENT | 88.25 | Yes | Yes | 1.00 | T N2 APARTMENT | GENERAL | T N2 APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| T S1 APARTMENT | 88.25 | Yes | Yes | 1.00 | T S1 APARTMENT | GENERAL | T S1 APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| T S2 APARTMENT | 88.25 | Yes | Yes | 1.00 | T S2 APARTMENT | GENERAL | T S2 APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| T CORRIDOR | 77.66 | No | Yes | 1.00 | T CORRIDOR | GENERAL | T CORRIDOR | 4.7725 | 18.58 | 0.0000 | |
| G CORRIDOR | 77.66 | No | Yes | 1.00 | G CORRIDOR | GENERAL | G CORRIDOR | 4.7725 | 18.58 | 105.2565 | |
| M CORRIDOR | 77.66 | No | Yes | 2.00 | M CORRIDOR | GENERAL | M CORRIDOR | 4.7725 | 18.58 | 0.0000 | |
| Total | 3134.61 | 8.3333 | 15.84 | 8.6167 | |||||||
| Conditioned Total | 2823.98 | 8.7250 | 17.17 | 6.6700 | |||||||
| Unconditioned Total | 310.64 | 4.7725 | 9.29 | 26.3141 | |||||||
| Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
| Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
| GENERAL | 3134.61 | 2823.98 | 310.64 | 0.00 | 6.2575 | 41.91 | 7.1145 |
| Total | 3134.61 | 2823.98 | 310.64 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 09:14:20
End Uses| Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
| Time of Peak | 13-AUG-16:10 | 06-FEB-09:00 | - | - | - | - | - | - | - | - | - | - | 01-JAN-07:10 |
| Heating | 0.00 | 123329.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Cooling | 22738.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Lighting | 4289.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment | 22609.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans | 8030.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems | 32286.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Total End Uses | 89955.36 | 123329.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
| Heating | General | 0.00 | 123329.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Cooling | General | 22738.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Lighting | LightsWired | 4034.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LightsPlugIn | 254.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment | MiscPlug | 18441.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| ElevatorLift | 4006.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| ElevatorLightsFan | 162.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| General | 8030.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems | Water Heater | 32286.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 09:14:20
Values gathered over 8760.00 hours| Source Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
| Heating | 0.00 | 663.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Cooling | 244.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Lighting | 314.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Lighting | 158.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment | 1452.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans | 304.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems | 1521.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Total Source Energy End Use Components | 3995.83 | 663.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
| Heating | 0.00 | 235.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Cooling | 86.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Lighting | 111.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Lighting | 56.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment | 514.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans | 107.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems | 538.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Total Source Energy End Use Components | 1414.97 | 235.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
| Heating | 0.00 | 211.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Cooling | 77.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Lighting | 100.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Lighting | 50.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment | 463.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans | 97.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems | 485.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Total Source Energy End Use Components | 1274.74 | 211.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 09:14:20
ZoneHVAC:EnergyRecoveryVentilator| User-Specified Supply Air Flow Rate [m3/s] | User-Specified Exhaust Air Flow Rate [m3/s] | |
| G SW APARTMENT ERV | 0.025955 | 0.025955 |
| G NW APARTMENT ERV | 0.025955 | 0.025955 |
| G NE APARTMENT ERV | 0.025955 | 0.025955 |
| G N1 APARTMENT ERV | 0.025955 | 0.025955 |
| G N2 APARTMENT ERV | 0.025955 | 0.025955 |
| G S1 APARTMENT ERV | 0.025955 | 0.025955 |
| G S2 APARTMENT ERV | 0.025955 | 0.025955 |
| M SW APARTMENT ERV | 0.051909 | 0.051909 |
| M NW APARTMENT ERV | 0.051909 | 0.051909 |
| M SE APARTMENT ERV | 0.051909 | 0.051909 |
| M NE APARTMENT ERV | 0.051909 | 0.051909 |
| M N1 APARTMENT ERV | 0.051909 | 0.051909 |
| M N2 APARTMENT ERV | 0.051909 | 0.051909 |
| M S1 APARTMENT ERV | 0.051909 | 0.051909 |
| M S2 APARTMENT ERV | 0.051909 | 0.051909 |
| T SW APARTMENT ERV | 0.025955 | 0.025955 |
| T NW APARTMENT ERV | 0.025955 | 0.025955 |
| T SE APARTMENT ERV | 0.025955 | 0.025955 |
| T NE APARTMENT ERV | 0.025955 | 0.025955 |
| T N1 APARTMENT ERV | 0.025955 | 0.025955 |
| T N2 APARTMENT ERV | 0.025955 | 0.025955 |
| T S1 APARTMENT ERV | 0.025955 | 0.025955 |
| T S2 APARTMENT ERV | 0.025955 | 0.025955 |
| Design Size Maximum Flow Rate [m3/s] | |
| G SW APARTMENT ERV SUP FAN | 0.025955 |
| G SW APARTMENT ERV EXH FAN | 0.025955 |
| G NW APARTMENT ERV SUP FAN | 0.025955 |
| G NW APARTMENT ERV EXH FAN | 0.025955 |
| G NE APARTMENT ERV SUP FAN | 0.025955 |
| G NE APARTMENT ERV EXH FAN | 0.025955 |
| G N1 APARTMENT ERV SUP FAN | 0.025955 |
| G N1 APARTMENT ERV EXH FAN | 0.025955 |
| G N2 APARTMENT ERV SUP FAN | 0.025955 |
| G N2 APARTMENT ERV EXH FAN | 0.025955 |
| G S1 APARTMENT ERV SUP FAN | 0.025955 |
| G S1 APARTMENT ERV EXH FAN | 0.025955 |
| G S2 APARTMENT ERV SUP FAN | 0.025955 |
| G S2 APARTMENT ERV EXH FAN | 0.025955 |
| M SW APARTMENT ERV SUP FAN | 0.051909 |
| M SW APARTMENT ERV EXH FAN | 0.051909 |
| M NW APARTMENT ERV SUP FAN | 0.051909 |
| M NW APARTMENT ERV EXH FAN | 0.051909 |
| M SE APARTMENT ERV SUP FAN | 0.051909 |
| M SE APARTMENT ERV EXH FAN | 0.051909 |
| M NE APARTMENT ERV SUP FAN | 0.051909 |
| M NE APARTMENT ERV EXH FAN | 0.051909 |
| M N1 APARTMENT ERV SUP FAN | 0.051909 |
| M N1 APARTMENT ERV EXH FAN | 0.051909 |
| M N2 APARTMENT ERV SUP FAN | 0.051909 |
| M N2 APARTMENT ERV EXH FAN | 0.051909 |
| M S1 APARTMENT ERV SUP FAN | 0.051909 |
| M S1 APARTMENT ERV EXH FAN | 0.051909 |
| M S2 APARTMENT ERV SUP FAN | 0.051909 |
| M S2 APARTMENT ERV EXH FAN | 0.051909 |
| T SW APARTMENT ERV SUP FAN | 0.025955 |
| T SW APARTMENT ERV EXH FAN | 0.025955 |
| T NW APARTMENT ERV SUP FAN | 0.025955 |
| T NW APARTMENT ERV EXH FAN | 0.025955 |
| T SE APARTMENT ERV SUP FAN | 0.025955 |
| T SE APARTMENT ERV EXH FAN | 0.025955 |
| T NE APARTMENT ERV SUP FAN | 0.025955 |
| T NE APARTMENT ERV EXH FAN | 0.025955 |
| T N1 APARTMENT ERV SUP FAN | 0.025955 |
| T N1 APARTMENT ERV EXH FAN | 0.025955 |
| T N2 APARTMENT ERV SUP FAN | 0.025955 |
| T N2 APARTMENT ERV EXH FAN | 0.025955 |
| T S1 APARTMENT ERV SUP FAN | 0.025955 |
| T S1 APARTMENT ERV EXH FAN | 0.025955 |
| T S2 APARTMENT ERV SUP FAN | 0.025955 |
| T S2 APARTMENT ERV EXH FAN | 0.025955 |
| SPLIT GSW SUPPLY FAN | 0.342918 |
| SPLIT GNW SUPPLY FAN | 0.322168 |
| SPLIT OFFICE SUPPLY FAN | 0.380355 |
| SPLIT GNE SUPPLY FAN | 0.287407 |
| SPLIT GN1 SUPPLY FAN | 0.263023 |
| SPLIT GN2 SUPPLY FAN | 0.262402 |
| SPLIT GS1 SUPPLY FAN | 0.285838 |
| SPLIT GS2 SUPPLY FAN | 0.287666 |
| SPLIT MSW SUPPLY FAN | 0.868808 |
| SPLIT MNW SUPPLY FAN | 0.836493 |
| SPLIT MSE SUPPLY FAN | 0.765178 |
| SPLIT MNE SUPPLY FAN | 0.733778 |
| SPLIT MN1 SUPPLY FAN | 0.659193 |
| SPLIT MN2 SUPPLY FAN | 0.657479 |
| SPLIT MS1 SUPPLY FAN | 0.696904 |
| SPLIT MS2 SUPPLY FAN | 0.695079 |
| SPLIT TSW SUPPLY FAN | 0.477665 |
| SPLIT TNW SUPPLY FAN | 0.470993 |
| SPLIT TSE SUPPLY FAN | 0.402580 |
| SPLIT TNE SUPPLY FAN | 0.395839 |
| SPLIT TN1 SUPPLY FAN | 0.371866 |
| SPLIT TN2 SUPPLY FAN | 0.369533 |
| SPLIT TS1 SUPPLY FAN | 0.380142 |
| SPLIT TS2 SUPPLY FAN | 0.377816 |
| Design Size Nominal Supply Air Flow Rate [m3/s] | |
| G SW APARTMENT OA HEAT EXCHANGER | 0.025955 |
| G NW APARTMENT OA HEAT EXCHANGER | 0.025955 |
| G NE APARTMENT OA HEAT EXCHANGER | 0.025955 |
| G N1 APARTMENT OA HEAT EXCHANGER | 0.025955 |
| G N2 APARTMENT OA HEAT EXCHANGER | 0.025955 |
| G S1 APARTMENT OA HEAT EXCHANGER | 0.025955 |
| G S2 APARTMENT OA HEAT EXCHANGER | 0.025955 |
| M SW APARTMENT OA HEAT EXCHANGER | 0.051909 |
| M NW APARTMENT OA HEAT EXCHANGER | 0.051909 |
| M SE APARTMENT OA HEAT EXCHANGER | 0.051909 |
| M NE APARTMENT OA HEAT EXCHANGER | 0.051909 |
| M N1 APARTMENT OA HEAT EXCHANGER | 0.051909 |
| M N2 APARTMENT OA HEAT EXCHANGER | 0.051909 |
| M S1 APARTMENT OA HEAT EXCHANGER | 0.051909 |
| M S2 APARTMENT OA HEAT EXCHANGER | 0.051909 |
| T SW APARTMENT OA HEAT EXCHANGER | 0.025955 |
| T NW APARTMENT OA HEAT EXCHANGER | 0.025955 |
| T SE APARTMENT OA HEAT EXCHANGER | 0.025955 |
| T NE APARTMENT OA HEAT EXCHANGER | 0.025955 |
| T N1 APARTMENT OA HEAT EXCHANGER | 0.025955 |
| T N2 APARTMENT OA HEAT EXCHANGER | 0.025955 |
| T S1 APARTMENT OA HEAT EXCHANGER | 0.025955 |
| T S2 APARTMENT OA HEAT EXCHANGER | 0.025955 |
| Design Size Maximum Air Flow Rate [m3/s] | |
| G SW APARTMENT DIRECT AIR | 0.342918 |
| G NW APARTMENT DIRECT AIR | 0.322168 |
| OFFICE DIRECT AIR | 0.380355 |
| G NE APARTMENT DIRECT AIR | 0.287407 |
| G N1 APARTMENT DIRECT AIR | 0.263023 |
| G N2 APARTMENT DIRECT AIR | 0.262402 |
| G S1 APARTMENT DIRECT AIR | 0.285838 |
| G S2 APARTMENT DIRECT AIR | 0.287666 |
| M SW APARTMENT DIRECT AIR | 0.868808 |
| M NW APARTMENT DIRECT AIR | 0.836493 |
| M SE APARTMENT DIRECT AIR | 0.765178 |
| M NE APARTMENT DIRECT AIR | 0.733778 |
| M N1 APARTMENT DIRECT AIR | 0.659193 |
| M N2 APARTMENT DIRECT AIR | 0.657479 |
| M S1 APARTMENT DIRECT AIR | 0.696904 |
| M S2 APARTMENT DIRECT AIR | 0.695079 |
| T SW APARTMENT DIRECT AIR | 0.477665 |
| T NW APARTMENT DIRECT AIR | 0.470993 |
| T SE APARTMENT DIRECT AIR | 0.402580 |
| T NE APARTMENT DIRECT AIR | 0.395839 |
| T N1 APARTMENT DIRECT AIR | 0.371866 |
| T N2 APARTMENT DIRECT AIR | 0.369533 |
| T S1 APARTMENT DIRECT AIR | 0.380142 |
| T S2 APARTMENT DIRECT AIR | 0.377816 |
| Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
| SPLIT GSW | 0.342918 | 0.342918 | 0.342918 | 0.342918 | 0.342918 | 0.342918 | 1.00 | 1.00 | 0.342918 |
| SPLIT GNW | 0.322168 | 0.322168 | 0.322168 | 0.322168 | 0.322168 | 0.322168 | 1.00 | 1.00 | 0.322168 |
| SPLIT OFFICE | 0.380355 | 0.380355 | 0.380355 | 0.380355 | 0.380355 | 0.380355 | 1.00 | 1.00 | 0.380355 |
| SPLIT GNE | 0.287407 | 0.287407 | 0.287407 | 0.287407 | 0.287407 | 0.287407 | 1.00 | 1.00 | 0.287407 |
| SPLIT GN1 | 0.263023 | 0.263023 | 0.263023 | 0.263023 | 0.263023 | 0.263023 | 1.00 | 1.00 | 0.263023 |
| SPLIT GN2 | 0.262402 | 0.262402 | 0.262402 | 0.262402 | 0.262402 | 0.262402 | 1.00 | 1.00 | 0.262402 |
| SPLIT GS1 | 0.285838 | 0.285838 | 0.285838 | 0.285838 | 0.285838 | 0.285838 | 1.00 | 1.00 | 0.285838 |
| SPLIT GS2 | 0.287666 | 0.287666 | 0.287666 | 0.287666 | 0.287666 | 0.287666 | 1.00 | 1.00 | 0.287666 |
| SPLIT MSW | 0.868808 | 0.868808 | 0.868808 | 0.868808 | 0.868808 | 0.868808 | 1.00 | 1.00 | 0.868808 |
| SPLIT MNW | 0.836493 | 0.836493 | 0.836493 | 0.836493 | 0.836493 | 0.836493 | 1.00 | 1.00 | 0.836493 |
| SPLIT MSE | 0.765178 | 0.765178 | 0.765178 | 0.765178 | 0.765178 | 0.765178 | 1.00 | 1.000000 | 0.765178 |
| SPLIT MNE | 0.733778 | 0.733778 | 0.733778 | 0.733778 | 0.733778 | 0.733778 | 1.00 | 1.000000 | 0.733778 |
| SPLIT MN1 | 0.659193 | 0.659193 | 0.659193 | 0.659193 | 0.659193 | 0.659193 | 1.00 | 1.000000 | 0.659193 |
| SPLIT MN2 | 0.657479 | 0.657479 | 0.657479 | 0.657479 | 0.657479 | 0.657479 | 1.00 | 1.000000 | 0.657479 |
| SPLIT MS1 | 0.696904 | 0.696904 | 0.696904 | 0.696904 | 0.696904 | 0.696904 | 1.00 | 1.00 | 0.696904 |
| SPLIT MS2 | 0.695079 | 0.695079 | 0.695079 | 0.695079 | 0.695079 | 0.695079 | 1.00 | 1.00 | 0.695079 |
| SPLIT TSW | 0.477665 | 0.477665 | 0.477665 | 0.477665 | 0.477665 | 0.477665 | 1.00 | 1.00 | 0.477665 |
| SPLIT TNW | 0.470993 | 0.470993 | 0.470993 | 0.470993 | 0.470993 | 0.470993 | 1.00 | 1.00 | 0.470993 |
| SPLIT TSE | 0.402580 | 0.402580 | 0.402580 | 0.402580 | 0.402580 | 0.402580 | 1.00 | 1.00 | 0.402580 |
| SPLIT TNE | 0.395839 | 0.395839 | 0.395839 | 0.395839 | 0.395839 | 0.395839 | 1.00 | 1.00 | 0.395839 |
| SPLIT TN1 | 0.371866 | 0.371866 | 0.371866 | 0.371866 | 0.371866 | 0.371866 | 1.00 | 1.00 | 0.371866 |
| SPLIT TN2 | 0.369533 | 0.369533 | 0.369533 | 0.369533 | 0.369533 | 0.369533 | 1.00 | 1.000000 | 0.369533 |
| SPLIT TS1 | 0.380142 | 0.380142 | 0.380142 | 0.380142 | 0.380142 | 0.380142 | 1.00 | 1.00 | 0.380142 |
| SPLIT TS2 | 0.377816 | 0.377816 | 0.377816 | 0.377816 | 0.377816 | 0.377816 | 1.00 | 1.00 | 0.377816 |
| Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
| SPLIT GSW_OA_CONTROLLER | 0.342918 | 0.025955 |
| SPLIT GNW_OA_CONTROLLER | 0.322168 | 0.025955 |
| SPLIT OFFICE_OA_CONTROLLER | 0.380355 | 0.038106 |
| SPLIT GNE_OA_CONTROLLER | 0.287407 | 0.025955 |
| SPLIT GN1_OA_CONTROLLER | 0.263023 | 0.025955 |
| SPLIT GN2_OA_CONTROLLER | 0.262402 | 0.025955 |
| SPLIT GS1_OA_CONTROLLER | 0.285838 | 0.025955 |
| SPLIT GS2_OA_CONTROLLER | 0.287666 | 0.025955 |
| SPLIT MSW_OA_CONTROLLER | 0.868808 | 0.051909 |
| SPLIT MNW_OA_CONTROLLER | 0.836493 | 0.051909 |
| SPLIT MSE_OA_CONTROLLER | 0.765178 | 0.051909 |
| SPLIT MNE_OA_CONTROLLER | 0.733778 | 0.051909 |
| SPLIT MN1_OA_CONTROLLER | 0.659193 | 0.051909 |
| SPLIT MN2_OA_CONTROLLER | 0.657479 | 0.051909 |
| SPLIT MS1_OA_CONTROLLER | 0.696904 | 0.051909 |
| SPLIT MS2_OA_CONTROLLER | 0.695079 | 0.051909 |
| SPLIT TSW_OA_CONTROLLER | 0.477665 | 0.025955 |
| SPLIT TNW_OA_CONTROLLER | 0.470993 | 0.025955 |
| SPLIT TSE_OA_CONTROLLER | 0.402580 | 0.025955 |
| SPLIT TNE_OA_CONTROLLER | 0.395839 | 0.025955 |
| SPLIT TN1_OA_CONTROLLER | 0.371866 | 0.025955 |
| SPLIT TN2_OA_CONTROLLER | 0.369533 | 0.025955 |
| SPLIT TS1_OA_CONTROLLER | 0.380142 | 0.025955 |
| SPLIT TS2_OA_CONTROLLER | 0.377816 | 0.025955 |
| Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | Design Size Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
| SPLIT GSW_UNITARY_PACKAGE_DX | 0.342918 | 0.342918 | 0.342918 | 0.342918 | 5716.92 | 8790.72 | 40.00 | 1.00 |
| SPLIT GNW_UNITARY_PACKAGE_DX | 0.322168 | 0.322168 | 0.322168 | 0.322168 | 5396.97 | 8328.05 | 40.00 | 1.00 |
| SPLIT OFFICE_UNITARY_PACKAGE_DX | 0.380355 | 0.380355 | 0.380355 | 0.380355 | 6296.23 | 10161.51 | 40.00 | 1.00 |
| SPLIT GNE_UNITARY_PACKAGE_DX | 0.287407 | 0.287407 | 0.287407 | 0.287407 | 4899.83 | 7553.02 | 40.00 | 1.00 |
| SPLIT GN1_UNITARY_PACKAGE_DX | 0.263023 | 0.263023 | 0.263023 | 0.263023 | 4486.35 | 7009.28 | 40.00 | 1.00 |
| SPLIT GN2_UNITARY_PACKAGE_DX | 0.262402 | 0.262402 | 0.262402 | 0.262402 | 4477.27 | 6995.42 | 40.00 | 1.00 |
| SPLIT GS1_UNITARY_PACKAGE_DX | 0.285838 | 0.285838 | 0.285838 | 0.285838 | 4842.71 | 7517.99 | 40.00 | 1.00 |
| SPLIT GS2_UNITARY_PACKAGE_DX | 0.287666 | 0.287666 | 0.287666 | 0.287666 | 4869.89 | 7558.75 | 40.00 | 1.00 |
| SPLIT MSW_UNITARY_PACKAGE_DX | 0.868808 | 0.868808 | 0.868808 | 0.868808 | 14381.86 | 21662.34 | 40.00 | 1.00 |
| SPLIT MNW_UNITARY_PACKAGE_DX | 0.836493 | 0.836493 | 0.836493 | 0.836493 | 13846.93 | 20941.52 | 40.00 | 1.00 |
| SPLIT MSE_UNITARY_PACKAGE_DX | 0.765178 | 0.765178 | 0.765178 | 0.765178 | 12729.02 | 19351.64 | 40.00 | 1.00 |
| SPLIT MNE_UNITARY_PACKAGE_DX | 0.733778 | 0.733778 | 0.733778 | 0.733778 | 12244.00 | 18651.27 | 40.00 | 1.00 |
| SPLIT MN1_UNITARY_PACKAGE_DX | 0.659193 | 0.659193 | 0.659193 | 0.659193 | 10993.53 | 16987.62 | 40.00 | 1.00 |
| SPLIT MN2_UNITARY_PACKAGE_DX | 0.657479 | 0.657479 | 0.657479 | 0.657479 | 10968.71 | 16949.42 | 40.00 | 1.00 |
| SPLIT MS1_UNITARY_PACKAGE_DX | 0.696904 | 0.696904 | 0.696904 | 0.696904 | 11571.12 | 17828.68 | 40.00 | 1.00 |
| SPLIT MS2_UNITARY_PACKAGE_DX | 0.695079 | 0.695079 | 0.695079 | 0.695079 | 11544.95 | 17787.98 | 40.00 | 1.00 |
| SPLIT TSW_UNITARY_PACKAGE_DX | 0.477665 | 0.477665 | 0.477665 | 0.477665 | 7907.05 | 11796.21 | 40.00 | 1.00 |
| SPLIT TNW_UNITARY_PACKAGE_DX | 0.470993 | 0.470993 | 0.470993 | 0.470993 | 7796.61 | 11647.28 | 40.00 | 1.00 |
| SPLIT TSE_UNITARY_PACKAGE_DX | 0.402580 | 0.402580 | 0.402580 | 0.402580 | 6719.99 | 10121.91 | 40.00 | 1.00 |
| SPLIT TNE_UNITARY_PACKAGE_DX | 0.395839 | 0.395839 | 0.395839 | 0.395839 | 6606.84 | 9971.48 | 40.00 | 1.00 |
| SPLIT TN1_UNITARY_PACKAGE_DX | 0.371866 | 0.371866 | 0.371866 | 0.371866 | 6155.71 | 9436.48 | 40.00 | 1.00 |
| SPLIT TN2_UNITARY_PACKAGE_DX | 0.369533 | 0.369533 | 0.369533 | 0.369533 | 6117.09 | 9384.45 | 40.00 | 1.00 |
| SPLIT TS1_UNITARY_PACKAGE_DX | 0.380142 | 0.380142 | 0.380142 | 0.380142 | 6292.71 | 9621.14 | 40.00 | 1.00 |
| SPLIT TS2_UNITARY_PACKAGE_DX | 0.377816 | 0.377816 | 0.377816 | 0.377816 | 6254.20 | 9569.26 | 40.00 | 1.00 |
| Design Size Rated Air Flow Rate [m3/s] | Design Size Gross Rated Total Cooling Capacity [W] | Design Size Gross Rated Sensible Heat Ratio | |
| SPLIT GSW COOLING COIL | 0.342918 | 5716.92 | 0.800057 |
| SPLIT GNW COOLING COIL | 0.322168 | 5396.97 | 0.800300 |
| SPLIT OFFICE COOLING COIL | 0.380355 | 6296.23 | 0.800655 |
| SPLIT GNE COOLING COIL | 0.287407 | 4899.83 | 0.800983 |
| SPLIT GN1 COOLING COIL | 0.263023 | 4486.35 | 0.800807 |
| SPLIT GN2 COOLING COIL | 0.262402 | 4477.27 | 0.800686 |
| SPLIT GS1 COOLING COIL | 0.285838 | 4842.71 | 0.800223 |
| SPLIT GS2 COOLING COIL | 0.287666 | 4869.89 | 0.800503 |
| SPLIT MSW COOLING COIL | 0.868808 | 14381.86 | 0.800655 |
| SPLIT MNW COOLING COIL | 0.836493 | 13846.93 | 0.800655 |
| SPLIT MSE COOLING COIL | 0.765178 | 12729.02 | 0.800847 |
| SPLIT MNE COOLING COIL | 0.733778 | 12244.00 | 0.800732 |
| SPLIT MN1 COOLING COIL | 0.659193 | 10993.53 | 0.800928 |
| SPLIT MN2 COOLING COIL | 0.657479 | 10968.71 | 0.800803 |
| SPLIT MS1 COOLING COIL | 0.696904 | 11571.12 | 0.800547 |
| SPLIT MS2 COOLING COIL | 0.695079 | 11544.95 | 0.800416 |
| SPLIT TSW COOLING COIL | 0.477665 | 7907.05 | 0.800655 |
| SPLIT TNW COOLING COIL | 0.470993 | 7796.61 | 0.800655 |
| SPLIT TSE COOLING COIL | 0.402580 | 6719.99 | 0.800598 |
| SPLIT TNE COOLING COIL | 0.395839 | 6606.84 | 0.800634 |
| SPLIT TN1 COOLING COIL | 0.371866 | 6155.71 | 0.800655 |
| SPLIT TN2 COOLING COIL | 0.369533 | 6117.09 | 0.800655 |
| SPLIT TS1 COOLING COIL | 0.380142 | 6292.71 | 0.800655 |
| SPLIT TS2 COOLING COIL | 0.377816 | 6254.20 | 0.800655 |
| Design Size Nominal Capacity [W] | |
| SPLIT GSW HEATING COIL | 8790.72 |
| SPLIT GNW HEATING COIL | 8328.05 |
| SPLIT OFFICE HEATING COIL | 10161.51 |
| SPLIT GNE HEATING COIL | 7553.02 |
| SPLIT GN1 HEATING COIL | 7009.28 |
| SPLIT GN2 HEATING COIL | 6995.42 |
| SPLIT GS1 HEATING COIL | 7517.99 |
| SPLIT GS2 HEATING COIL | 7558.75 |
| SPLIT MSW HEATING COIL | 21662.34 |
| SPLIT MNW HEATING COIL | 20941.52 |
| SPLIT MSE HEATING COIL | 19351.64 |
| SPLIT MNE HEATING COIL | 18651.27 |
| SPLIT MN1 HEATING COIL | 16987.62 |
| SPLIT MN2 HEATING COIL | 16949.42 |
| SPLIT MS1 HEATING COIL | 17828.68 |
| SPLIT MS2 HEATING COIL | 17787.98 |
| SPLIT TSW HEATING COIL | 11796.21 |
| SPLIT TNW HEATING COIL | 11647.28 |
| SPLIT TSE HEATING COIL | 10121.91 |
| SPLIT TNE HEATING COIL | 9971.48 |
| SPLIT TN1 HEATING COIL | 9436.48 |
| SPLIT TN2 HEATING COIL | 9384.45 |
| SPLIT TS1 HEATING COIL | 9621.14 |
| SPLIT TS2 HEATING COIL | 9569.26 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 09:14:20
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other Surfaces| None |
| Possible Shadow Receivers | |
| G SWALL SWA | GWINDOW1 S SWA | |
| G WWALL SWA | GWINDOW1 W SWA | |
| G NWALL NWA | GWINDOW1 N NWA | |
| G WWALL NWA | GWINDOW1 W NWA | |
| G SWALL SEA | GWINDOW1 S SEA | |
| G EWALL SEA | GWINDOW1 E SEA | |
| G NWALL NEA | GWINDOW1 N NEA | |
| G EWALL NEA | GWINDOW1 E NEA | |
| G NWALL N1A | GWINDOW1 N N1A | |
| G NWALL N2A | GWINDOW1 N N2A | |
| G SWALL S1A | GWINDOW1 S S1A | |
| G SWALL S2A | GWINDOW1 S S2A | |
| M WWALL SWA | MWINDOW1 W SWA | |
| M SWALL SWA | MWINDOW1 S SWA | |
| M NWALL NWA | MWINDOW1 N NWA | |
| M WWALL NWA | MWINDOW1 W NWA | |
| M EWALL SEA | MWINDOW1 E SEA | |
| M SWALL SEA | MWINDOW1 S SEA | |
| M NWALL NEA | MWINDOW1 N NEA | |
| M EWALL NEA | MWINDOW1 E NEA | |
| M NWALL N1A | MWINDOW1 N N1A | |
| M NWALL N2A | MWINDOW1 N N2A | |
| M SWALL S1A | MWINDOW1 S S1A | |
| M SWALL S2A | MWINDOW1 S S2A | |
| T WWALL SWA | TWINDOW1 W SWA | |
| T SWALL SWA | TWINDOW1 S SWA | |
| T NWALL NWA | TWINDOW1 N NWA | |
| T WWALL NWA | TWINDOW1 W NWA | |
| T EWALL SEA | TWINDOW1 E SEA | |
| T SWALL SEA | TWINDOW1 S SEA | |
| T NWALL NEA | TWINDOW1 N NEA | |
| T EWALL NEA | TWINDOW1 E NEA | |
| T NWALL N1A | TWINDOW1 N N1A | |
| T NWALL N2A | TWINDOW1 N N2A | |
| T SWALL S1A | TWINDOW1 S S1A | |
| T SWALL S2A | TWINDOW1 S S2A | |
| T EWALL C | TWINDOW14 | |
| G EWALL C | ENTRANCE DOOR | |
| M EWALL C | MWINDOW14 | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 09:14:20
Time Not Meeting the Adaptive Comfort Models during Occupied Hours| ASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 09:14:20
Version| Version ID | |
| 1 | 22.1 |
| #TimeSteps | Minutes per TimeStep {minutes} | |
| 1 | 6 | 10 |
| Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
| 1 | 1 | 20 | 2 | 8 |
| Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
| 1 | Yes | Yes | No | No | Yes | No |
| Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
| 1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
| Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
| 1 | 0.556 | 0.556 |
| Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
| 1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
| Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
| 1 | 9.70 | 6.00 | -2.20 | -3.40 | -4.20 | 2.70 | 7.50 | 13.70 | 18.60 | 22.00 | 20.70 | 16.50 |
| Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
| 1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
| Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
| 1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
| Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
| 1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
| Normal | Daylighting {dimensionless} | |
| 1 | 1.000 | 1.000 |
| Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
| 1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
| Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
| 1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
| Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
| 1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
| Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
| 1 | Buffalo Niagara Intl AP NY USA TMY3 WMO#=725280 | 42.93 | -78.73 | -5.00 | 215.00 | 98769 | 1.1739 |
| Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
| 1 | Correlation | NA | 8.97 | 26.20 | NA |
| Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
| 1 | ApartmentMidRise | 0.000 | City | 4.00000E-002 | 0.40000 | FullExterior | 25 | 6 |
| Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
| 1 | TARP |
| Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
| 1 | TARP |
| Value {Anisotropic} | |
| 1 | Anisotropic |
| Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
| 1 | ThirdOrderBackwardDifference |
| Simulation {Yes/No} | Carbon Dioxide Concentration | |
| 1 | No | N/A |
| Simulation {Yes/No} | Generic Contaminant Concentration | |
| 1 | No | N/A |
| Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
| 1 | No | N/A | N/A | N/A |
| Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
| 1 | RegulaFalsi |
| Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
| 1 | 0.330 | 460.000 | 6.500000E-003 |
| Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
| 1 | LowerLeftCorner | Clockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
| Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
| 1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
| Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
| 1 | 0 | 0 | 0 |
| Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
| 1 | 27 | 243 | 39 |
| Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
| 1 | G SW APARTMENT | 0.0 | 0.00 | 0.00 | 0.00 | 5.79 | 3.81 | 1.52 | 1 | 1 | 1 | 0.00 | 11.58 | 0.00 | 7.62 | 0.00 | 3.05 | 3.05 | 268.97 | TARP | TARP | 88.25 | 58.52 | 46.82 | 11.71 | 6 | 2 | 0 | Yes |
| 2 | G NW APARTMENT | 0.0 | 0.00 | 9.30 | 0.00 | 5.79 | 13.11 | 1.52 | 1 | 1 | 1 | 0.00 | 11.58 | 9.30 | 16.92 | 0.00 | 3.05 | 3.05 | 268.97 | TARP | TARP | 88.25 | 58.52 | 46.82 | 11.71 | 6 | 2 | 0 | Yes |
| 3 | OFFICE | 0.0 | 34.75 | 0.00 | 0.00 | 40.54 | 3.81 | 1.52 | 1 | 1 | 1 | 34.75 | 46.33 | 0.00 | 7.62 | 0.00 | 3.05 | 3.05 | 268.97 | TARP | TARP | 88.25 | 58.52 | 46.82 | 11.71 | 6 | 2 | 0 | Yes |
| 4 | G NE APARTMENT | 0.0 | 34.75 | 9.30 | 0.00 | 40.54 | 13.11 | 1.52 | 1 | 1 | 1 | 34.75 | 46.33 | 9.30 | 16.92 | 0.00 | 3.05 | 3.05 | 268.97 | TARP | TARP | 88.25 | 58.52 | 46.82 | 11.71 | 6 | 2 | 0 | Yes |
| 5 | G N1 APARTMENT | 0.0 | 11.58 | 9.30 | 0.00 | 17.37 | 13.11 | 1.52 | 1 | 1 | 1 | 11.58 | 23.16 | 9.30 | 16.92 | 0.00 | 3.05 | 3.05 | 268.97 | TARP | TARP | 88.25 | 35.30 | 28.24 | 7.06 | 6 | 1 | 0 | Yes |
| 6 | G N2 APARTMENT | 0.0 | 23.16 | 9.30 | 0.00 | 28.95 | 13.11 | 1.52 | 1 | 1 | 1 | 23.16 | 34.75 | 9.30 | 16.92 | 0.00 | 3.05 | 3.05 | 268.97 | TARP | TARP | 88.25 | 35.30 | 28.24 | 7.06 | 6 | 1 | 0 | Yes |
| 7 | G S1 APARTMENT | 0.0 | 11.58 | 0.00 | 0.00 | 17.37 | 3.81 | 1.52 | 1 | 1 | 1 | 11.58 | 23.16 | 0.00 | 7.62 | 0.00 | 3.05 | 3.05 | 268.97 | TARP | TARP | 88.25 | 35.30 | 28.24 | 7.06 | 6 | 1 | 0 | Yes |
| 8 | G S2 APARTMENT | 0.0 | 23.16 | 0.00 | 0.00 | 28.95 | 3.81 | 1.52 | 1 | 1 | 1 | 23.16 | 34.75 | 0.00 | 7.62 | 0.00 | 3.05 | 3.05 | 268.97 | TARP | TARP | 88.25 | 35.30 | 28.24 | 7.06 | 6 | 1 | 0 | Yes |
| 9 | M SW APARTMENT | 0.0 | 0.00 | 0.00 | 3.05 | 5.79 | 3.81 | 4.57 | 1 | 1 | 2 | 0.00 | 11.58 | 0.00 | 7.62 | 3.05 | 6.10 | 3.05 | 268.97 | TARP | TARP | 88.25 | 58.52 | 46.82 | 11.71 | 6 | 2 | 0 | Yes |
| 10 | M NW APARTMENT | 0.0 | 0.00 | 9.30 | 3.05 | 5.79 | 13.11 | 4.57 | 1 | 1 | 2 | 0.00 | 11.58 | 9.30 | 16.92 | 3.05 | 6.10 | 3.05 | 268.97 | TARP | TARP | 88.25 | 58.52 | 46.82 | 11.71 | 6 | 2 | 0 | Yes |
| 11 | M SE APARTMENT | 0.0 | 34.75 | 0.00 | 3.05 | 40.54 | 3.81 | 4.57 | 1 | 1 | 2 | 34.75 | 46.33 | 0.00 | 7.62 | 3.05 | 6.10 | 3.05 | 268.97 | TARP | TARP | 88.25 | 58.52 | 46.82 | 11.71 | 6 | 2 | 0 | Yes |
| 12 | M NE APARTMENT | 0.0 | 34.75 | 9.30 | 3.05 | 40.54 | 13.11 | 4.57 | 1 | 1 | 2 | 34.75 | 46.33 | 9.30 | 16.92 | 3.05 | 6.10 | 3.05 | 268.97 | TARP | TARP | 88.25 | 58.52 | 46.82 | 11.71 | 6 | 2 | 0 | Yes |
| 13 | M N1 APARTMENT | 0.0 | 11.58 | 9.30 | 3.05 | 17.37 | 13.11 | 4.57 | 1 | 1 | 2 | 11.58 | 23.16 | 9.30 | 16.92 | 3.05 | 6.10 | 3.05 | 268.97 | TARP | TARP | 88.25 | 35.30 | 28.24 | 7.06 | 6 | 1 | 0 | Yes |
| 14 | M N2 APARTMENT | 0.0 | 23.16 | 9.30 | 3.05 | 28.95 | 13.11 | 4.57 | 1 | 1 | 2 | 23.16 | 34.75 | 9.30 | 16.92 | 3.05 | 6.10 | 3.05 | 268.97 | TARP | TARP | 88.25 | 35.30 | 28.24 | 7.06 | 6 | 1 | 0 | Yes |
| 15 | M S1 APARTMENT | 0.0 | 11.58 | 0.00 | 3.05 | 17.37 | 3.81 | 4.57 | 1 | 1 | 2 | 11.58 | 23.16 | 0.00 | 7.62 | 3.05 | 6.10 | 3.05 | 268.97 | TARP | TARP | 88.25 | 35.30 | 28.24 | 7.06 | 6 | 1 | 0 | Yes |
| 16 | M S2 APARTMENT | 0.0 | 23.16 | 0.00 | 3.05 | 28.95 | 3.81 | 4.57 | 1 | 1 | 2 | 23.16 | 34.75 | 0.00 | 7.62 | 3.05 | 6.10 | 3.05 | 268.97 | TARP | TARP | 88.25 | 35.30 | 28.24 | 7.06 | 6 | 1 | 0 | Yes |
| 17 | T SW APARTMENT | 0.0 | 0.00 | 0.00 | 9.14 | 5.79 | 3.81 | 10.67 | 1 | 1 | 1 | 0.00 | 11.58 | 0.00 | 7.62 | 9.14 | 12.19 | 3.05 | 268.97 | TARP | TARP | 88.25 | 58.52 | 46.82 | 11.71 | 6 | 2 | 0 | Yes |
| 18 | T NW APARTMENT | 0.0 | 0.00 | 9.30 | 9.14 | 5.79 | 13.11 | 10.67 | 1 | 1 | 1 | 0.00 | 11.58 | 9.30 | 16.92 | 9.14 | 12.19 | 3.05 | 268.97 | TARP | TARP | 88.25 | 58.52 | 46.82 | 11.71 | 6 | 2 | 0 | Yes |
| 19 | T SE APARTMENT | 0.0 | 34.75 | 0.00 | 9.14 | 40.54 | 3.81 | 10.67 | 1 | 1 | 1 | 34.75 | 46.33 | 0.00 | 7.62 | 9.14 | 12.19 | 3.05 | 268.97 | TARP | TARP | 88.25 | 58.52 | 46.82 | 11.71 | 6 | 2 | 0 | Yes |
| 20 | T NE APARTMENT | 0.0 | 34.75 | 9.30 | 9.14 | 40.54 | 13.11 | 10.67 | 1 | 1 | 1 | 34.75 | 46.33 | 9.30 | 16.92 | 9.14 | 12.19 | 3.05 | 268.97 | TARP | TARP | 88.25 | 58.52 | 46.82 | 11.71 | 6 | 2 | 0 | Yes |
| 21 | T N1 APARTMENT | 0.0 | 11.58 | 9.30 | 9.14 | 17.37 | 13.11 | 10.67 | 1 | 1 | 1 | 11.58 | 23.16 | 9.30 | 16.92 | 9.14 | 12.19 | 3.05 | 268.97 | TARP | TARP | 88.25 | 35.30 | 28.24 | 7.06 | 6 | 1 | 0 | Yes |
| 22 | T N2 APARTMENT | 0.0 | 23.16 | 9.30 | 9.14 | 28.95 | 13.11 | 10.67 | 1 | 1 | 1 | 23.16 | 34.75 | 9.30 | 16.92 | 9.14 | 12.19 | 3.05 | 268.97 | TARP | TARP | 88.25 | 35.30 | 28.24 | 7.06 | 6 | 1 | 0 | Yes |
| 23 | T S1 APARTMENT | 0.0 | 11.58 | 0.00 | 9.14 | 17.37 | 3.81 | 10.67 | 1 | 1 | 1 | 11.58 | 23.16 | 0.00 | 7.62 | 9.14 | 12.19 | 3.05 | 268.97 | TARP | TARP | 88.25 | 35.30 | 28.24 | 7.06 | 6 | 1 | 0 | Yes |
| 24 | T S2 APARTMENT | 0.0 | 23.16 | 0.00 | 9.14 | 28.95 | 3.81 | 10.67 | 1 | 1 | 1 | 23.16 | 34.75 | 0.00 | 7.62 | 9.14 | 12.19 | 3.05 | 268.97 | TARP | TARP | 88.25 | 35.30 | 28.24 | 7.06 | 6 | 1 | 0 | Yes |
| 25 | T CORRIDOR | 0.0 | 0.00 | 7.62 | 9.14 | 23.16 | 8.46 | 10.67 | 1 | 1 | 1 | 0.00 | 46.33 | 7.62 | 9.30 | 9.14 | 12.19 | 3.05 | 236.69 | TARP | TARP | 77.66 | 10.22 | 9.10 | 1.11 | 12 | 1 | 0 | Yes |
| 26 | G CORRIDOR | 0.0 | 0.00 | 7.62 | 0.00 | 23.16 | 8.46 | 1.52 | 1 | 1 | 1 | 0.00 | 46.33 | 7.62 | 9.30 | 0.00 | 3.05 | 3.05 | 236.69 | TARP | TARP | 77.66 | 10.22 | 6.90 | 3.32 | 12 | 1 | 0 | Yes |
| 27 | M CORRIDOR | 0.0 | 0.00 | 7.62 | 3.05 | 23.16 | 8.46 | 4.57 | 1 | 1 | 2 | 0.00 | 46.33 | 7.62 | 9.30 | 3.05 | 6.10 | 3.05 | 236.69 | TARP | TARP | 77.66 | 10.22 | 9.10 | 1.11 | 12 | 1 | 0 | Yes |
| Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
| 1 | G SW APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 2 | G NW APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 3 | OFFICE | 88.25 | 4.7 | 18.581 | 5.382E-002 | 9.753 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 16.423 | No |
| 4 | G NE APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 5 | G N1 APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 6 | G N2 APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 7 | G S1 APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 8 | G S2 APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 9 | M SW APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 10 | M NW APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 11 | M SE APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 12 | M NE APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 13 | M N1 APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 14 | M N2 APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 15 | M S1 APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 16 | M S2 APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 17 | T SW APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 18 | T NW APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 19 | T SE APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 20 | T NE APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 21 | T N1 APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 22 | T N2 APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 23 | T S1 APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 24 | T S2 APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 25 | T CORRIDOR | 77.66 | 4.2 | 18.579 | 5.382E-002 | 4.772 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 4.772 | No |
| 26 | G CORRIDOR | 77.66 | 4.2 | 18.579 | 5.382E-002 | 4.772 | 105.256 | 0.000 | 0.000 | 0.000 | 0.000 | 110.029 | No |
| 27 | M CORRIDOR | 77.66 | 4.2 | 18.579 | 5.382E-002 | 4.772 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 4.772 | No |
| Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | |
| 1 | OCCUP_GSW | OCC_APT_SCH_WORKING_FAMILY | G SW APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 3 |
| 2 | OCCUP_GNW | OCC_APT_SCH_STAY_HOME_FAMILY | G NW APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 1 | 3 |
| 3 | OCCUP_OFFICE | OCC_OFF_W_SB_SCH | OFFICE | 88.25 | 4.7 | 4.7 | 5.382E-002 | 18.581 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 5 |
| 4 | OCCUP_GNE | OCC_APT_SCH_STAY_HOME_FAMILY | G NE APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 1 | 3 |
| 5 | OCCUP_GN1 | OCC_APT_SCH_STAY_HOME_FAMILY | G N1 APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 1 | 3 |
| 6 | OCCUP_GN2 | OCC_APT_SCH_STAY_HOME_FAMILY | G N2 APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 1 | 3 |
| 7 | OCCUP_GS1 | OCC_APT_SCH_WORKING_FAMILY | G S1 APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 3 |
| 8 | OCCUP_GS2 | OCC_APT_SCH_WORKING_FAMILY | G S2 APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 3 |
| 9 | OCCUP_MSW | OCC_APT_SCH_WORKING_FAMILY | M SW APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 3 |
| 10 | OCCUP_MNW | OCC_APT_SCH_STAY_HOME_FAMILY | M NW APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 1 | 3 |
| 11 | OCCUP_MSE | OCC_APT_SCH_WORKING_FAMILY | M SE APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 3 |
| 12 | OCCUP_MNE | OCC_APT_SCH_STAY_HOME_FAMILY | M NE APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 1 | 3 |
| 13 | OCCUP_MN1 | OCC_APT_SCH_STAY_HOME_FAMILY | M N1 APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 1 | 3 |
| 14 | OCCUP_MN2 | OCC_APT_SCH_STAY_HOME_FAMILY | M N2 APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 1 | 3 |
| 15 | OCCUP_MS1 | OCC_APT_SCH_WORKING_FAMILY | M S1 APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 3 |
| 16 | OCCUP_MS2 | OCC_APT_SCH_WORKING_FAMILY | M S2 APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 3 |
| 17 | OCCUP_TSW | OCC_APT_SCH_WORKING_FAMILY | T SW APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 3 |
| 18 | OCCUP_TNW | OCC_APT_SCH_STAY_HOME_FAMILY | T NW APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 1 | 3 |
| 19 | OCCUP_TSE | OCC_APT_SCH_WORKING_FAMILY | T SE APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 3 |
| 20 | OCCUP_TNE | OCC_APT_SCH_STAY_HOME_FAMILY | T NE APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 1 | 3 |
| 21 | OCCUP_TN1 | OCC_APT_SCH_STAY_HOME_FAMILY | T N1 APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 1 | 3 |
| 22 | OCCUP_TN2 | OCC_APT_SCH_STAY_HOME_FAMILY | T N2 APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 1 | 3 |
| 23 | OCCUP_TS1 | OCC_APT_SCH_WORKING_FAMILY | T S1 APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 3 |
| 24 | OCCUP_TS2 | OCC_APT_SCH_WORKING_FAMILY | T S2 APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 3 |
| 25 | OCCUP_T CORRIDOR | OCC_APT_SCH_CORRIDOR | T CORRIDOR | 77.66 | 4.2 | 4.2 | 5.382E-002 | 18.579 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 1 | 4 |
| 26 | OCCUP_G CORRIDOR | OCC_APT_SCH_CORRIDOR | G CORRIDOR | 77.66 | 4.2 | 4.2 | 5.382E-002 | 18.579 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 1 | 4 |
| 27 | OCCUP_M CORRIDOR | OCC_APT_SCH_CORRIDOR | M CORRIDOR | 77.66 | 4.2 | 4.2 | 5.382E-002 | 18.579 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 1 | 4 |
| Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
| 1 | LIGHTING_HARDWIRED_GSW | LTG_SCH_APARTMENT_HARDWIRED | G SW APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 2 | LIGHTING_HARDWIRED_GNW | LTG_SCH_APARTMENT_HARDWIRED | G NW APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 3 | LIGHTING_HARDWIRED_OFFICE | LTG_SCH_OFFICE | OFFICE | 88.25 | 4.7 | 860.710 | 9.753 | 181.220 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 860.710 |
| 4 | LIGHTING_HARDWIRED_GNE | LTG_SCH_APARTMENT_HARDWIRED | G NE APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 5 | LIGHTING_HARDWIRED_GN1 | LTG_SCH_APARTMENT_HARDWIRED | G N1 APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 6 | LIGHTING_HARDWIRED_GN2 | LTG_SCH_APARTMENT_HARDWIRED | G N2 APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 7 | LIGHTING_HARDWIRED_GS1 | LTG_SCH_APARTMENT_HARDWIRED | G S1 APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 8 | LIGHTING_HARDWIRED_GS2 | LTG_SCH_APARTMENT_HARDWIRED | G S2 APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 9 | LIGHTING_HARDWIRED_MSW | LTG_SCH_APARTMENT_HARDWIRED | M SW APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 10 | LIGHTING_HARDWIRED_MNW | LTG_SCH_APARTMENT_HARDWIRED | M NW APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 11 | LIGHTING_HARDWIRED_MSE | LTG_SCH_APARTMENT_HARDWIRED | M SE APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 12 | LIGHTING_HARDWIRED_MNE | LTG_SCH_APARTMENT_HARDWIRED | M NE APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 13 | LIGHTING_HARDWIRED_MN1 | LTG_SCH_APARTMENT_HARDWIRED | M N1 APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 14 | LIGHTING_HARDWIRED_MN2 | LTG_SCH_APARTMENT_HARDWIRED | M N2 APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 15 | LIGHTING_HARDWIRED_MS1 | LTG_SCH_APARTMENT_HARDWIRED | M S1 APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 16 | LIGHTING_HARDWIRED_MS2 | LTG_SCH_APARTMENT_HARDWIRED | M S2 APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 17 | LIGHTING_HARDWIRED_TSW | LTG_SCH_APARTMENT_HARDWIRED | T SW APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 18 | LIGHTING_HARDWIRED_TNW | LTG_SCH_APARTMENT_HARDWIRED | T NW APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 19 | LIGHTING_HARDWIRED_TSE | LTG_SCH_APARTMENT_HARDWIRED | T SE APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 20 | LIGHTING_HARDWIRED_TNE | LTG_SCH_APARTMENT_HARDWIRED | T NE APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 21 | LIGHTING_HARDWIRED_TN1 | LTG_SCH_APARTMENT_HARDWIRED | T N1 APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 22 | LIGHTING_HARDWIRED_TN2 | LTG_SCH_APARTMENT_HARDWIRED | T N2 APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 23 | LIGHTING_HARDWIRED_TS1 | LTG_SCH_APARTMENT_HARDWIRED | T S1 APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 24 | LIGHTING_HARDWIRED_TS2 | LTG_SCH_APARTMENT_HARDWIRED | T S2 APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 25 | LIGHTING_HARDWIRED_GC | LTG_SCH_CORRIDOR | G CORRIDOR | 77.66 | 4.2 | 370.628 | 4.772 | 88.667 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 370.628 |
| 26 | LIGHTING_HARDWIRED_MC | LTG_SCH_CORRIDOR | M CORRIDOR | 77.66 | 4.2 | 370.628 | 4.772 | 88.667 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 370.628 |
| 27 | LIGHTING_HARDWIRED_TC | LTG_SCH_CORRIDOR | T CORRIDOR | 77.66 | 4.2 | 370.628 | 4.772 | 88.667 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 370.628 |
| 28 | LIGHTING_PLUGIN_GSW | LTG_SCH_APARTMENT_PLUGIN | G SW APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| 29 | LIGHTING_PLUGIN_GNW | LTG_SCH_APARTMENT_PLUGIN | G NW APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| 30 | LIGHTING_PLUGIN_GNE | LTG_SCH_APARTMENT_PLUGIN | G NE APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| 31 | LIGHTING_PLUGIN_GN1 | LTG_SCH_APARTMENT_PLUGIN | G N1 APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| 32 | LIGHTING_PLUGIN_GN2 | LTG_SCH_APARTMENT_PLUGIN | G N2 APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| 33 | LIGHTING_PLUGIN_GS1 | LTG_SCH_APARTMENT_PLUGIN | G S1 APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| 34 | LIGHTING_PLUGIN_GS2 | LTG_SCH_APARTMENT_PLUGIN | G S2 APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| 35 | LIGHTING_PLUGIN_MSW | LTG_SCH_APARTMENT_PLUGIN | M SW APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| 36 | LIGHTING_PLUGIN_MNW | LTG_SCH_APARTMENT_PLUGIN | M NW APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| 37 | LIGHTING_PLUGIN_MSE | LTG_SCH_APARTMENT_PLUGIN | M SE APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| 38 | LIGHTING_PLUGIN_MNE | LTG_SCH_APARTMENT_PLUGIN | M NE APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| 39 | LIGHTING_PLUGIN_MN1 | LTG_SCH_APARTMENT_PLUGIN | M N1 APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| 40 | LIGHTING_PLUGIN_MN2 | LTG_SCH_APARTMENT_PLUGIN | M N2 APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| 41 | LIGHTING_PLUGIN_MS1 | LTG_SCH_APARTMENT_PLUGIN | M S1 APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| 42 | LIGHTING_PLUGIN_MS2 | LTG_SCH_APARTMENT_PLUGIN | M S2 APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| 43 | LIGHTING_PLUGIN_TSW | LTG_SCH_APARTMENT_PLUGIN | T SW APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| 44 | LIGHTING_PLUGIN_TNW | LTG_SCH_APARTMENT_PLUGIN | T NW APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| 45 | LIGHTING_PLUGIN_TSE | LTG_SCH_APARTMENT_PLUGIN | T SE APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| 46 | LIGHTING_PLUGIN_TNE | LTG_SCH_APARTMENT_PLUGIN | T NE APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| 47 | LIGHTING_PLUGIN_TN1 | LTG_SCH_APARTMENT_PLUGIN | T N1 APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| 48 | LIGHTING_PLUGIN_TN2 | LTG_SCH_APARTMENT_PLUGIN | T N2 APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| 49 | LIGHTING_PLUGIN_TS1 | LTG_SCH_APARTMENT_PLUGIN | T S1 APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| 50 | LIGHTING_PLUGIN_TS2 | LTG_SCH_APARTMENT_PLUGIN | T S2 APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
| 1 | PLUG_GSW | EQP_APT_SCH | G SW APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 2 | PLUG_GNW | EQP_APT_SCH | G NW APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 3 | PLUG_OFFICE | EQP_OFF_SCH | OFFICE | 88.25 | 4.7 | 588.623 | 6.670 | 123.933 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 588.623 |
| 4 | PLUG_GNE | EQP_APT_SCH | G NE APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 5 | PLUG_GN1 | EQP_APT_SCH | G N1 APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 6 | PLUG_GN2 | EQP_APT_SCH | G N2 APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 7 | PLUG_GS1 | EQP_APT_SCH | G S1 APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 8 | PLUG_GS2 | EQP_APT_SCH | G S2 APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 9 | PLUG_MSW | EQP_APT_SCH | M SW APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 10 | PLUG_MNW | EQP_APT_SCH | M NW APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 11 | PLUG_MSE | EQP_APT_SCH | M SE APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 12 | PLUG_MNE | EQP_APT_SCH | M NE APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 13 | PLUG_MN1 | EQP_APT_SCH | M N1 APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 14 | PLUG_MN2 | EQP_APT_SCH | M N2 APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 15 | PLUG_MS1 | EQP_APT_SCH | M S1 APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 16 | PLUG_MS2 | EQP_APT_SCH | M S2 APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 17 | PLUG_TSW | EQP_APT_SCH | T SW APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 18 | PLUG_TNW | EQP_APT_SCH | T NW APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 19 | PLUG_TSE | EQP_APT_SCH | T SE APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 20 | PLUG_TNE | EQP_APT_SCH | T NE APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 21 | PLUG_TN1 | EQP_APT_SCH | T N1 APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 22 | PLUG_TN2 | EQP_APT_SCH | T N2 APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 23 | PLUG_TS1 | EQP_APT_SCH | T S1 APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 24 | PLUG_TS2 | EQP_APT_SCH | T S2 APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 25 | G CORRIDOR_ELEVATORS_EQUIP | BLDG_ELEVATORS | G CORRIDOR | 77.66 | 4.2 | 8012.150 | 103.170 | 1916.782 | 0.000 | 0.000 | 0.950 | 5.000E-002 | ElevatorLift | 961.458 | 4006.075 |
| 26 | ELEVATORS_LIGHTS_FAN | ELEV_LIGHT_FAN_SCH_24_7 | G CORRIDOR | 77.66 | 4.2 | 162.000 | 2.086 | 38.756 | 0.000 | 0.000 | 0.950 | 5.000E-002 | ElevatorLightsFan | 162.000 | 162.000 |
| Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
| 1 | PolygonClipping | Periodic | 20 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
| Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
| 1 | WaterHeater:Mixed | G SW APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.496 | 0.7729 |
| 2 | WaterHeater:Mixed | G NW APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.496 | 0.7729 |
| 3 | WaterHeater:Mixed | G NE APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.496 | 0.7729 |
| 4 | WaterHeater:Mixed | G N1 APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.496 | 0.7729 |
| 5 | WaterHeater:Mixed | G N2 APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.496 | 0.7729 |
| 6 | WaterHeater:Mixed | G S1 APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.496 | 0.7729 |
| 7 | WaterHeater:Mixed | G S2 APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.496 | 0.7729 |
| 8 | WaterHeater:Mixed | M SW APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.498 | 0.7911 |
| 9 | WaterHeater:Mixed | M NW APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.498 | 0.7911 |
| 10 | WaterHeater:Mixed | M SE APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.498 | 0.7911 |
| 11 | WaterHeater:Mixed | M NE APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.498 | 0.7911 |
| 12 | WaterHeater:Mixed | M N1 APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.498 | 0.7911 |
| 13 | WaterHeater:Mixed | M N2 APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.498 | 0.7911 |
| 14 | WaterHeater:Mixed | M S1 APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.498 | 0.7911 |
| 15 | WaterHeater:Mixed | M S2 APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.498 | 0.7911 |
| 16 | WaterHeater:Mixed | T SW APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.496 | 0.7729 |
| 17 | WaterHeater:Mixed | T NW APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.496 | 0.7729 |
| 18 | WaterHeater:Mixed | T SE APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.496 | 0.7729 |
| 19 | WaterHeater:Mixed | T NE APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.496 | 0.7729 |
| 20 | WaterHeater:Mixed | T N1 APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.496 | 0.7729 |
| 21 | WaterHeater:Mixed | T N2 APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.496 | 0.7729 |
| 22 | WaterHeater:Mixed | T S1 APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.496 | 0.7729 |
| 23 | WaterHeater:Mixed | T S2 APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.496 | 0.7729 |
| Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
| 1 | G SWALL SWA | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 2 | GWINDOW1 S SWA | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 3 | G WWALL SWA | 0 | 154.67 | 58.21 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 4 | GWINDOW1 W SWA | 0 | 154.67 | 58.21 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 5 | G NIWALL SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 6 | G EIWALL SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 7 | G GFLOOR SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 8 | G CEILIN SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 9 | G INTERNALMASS SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 10 | G NWALL NWA | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 11 | GWINDOW1 N NWA | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 12 | G WWALL NWA | 0 | 154.67 | 58.21 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 13 | GWINDOW1 W NWA | 0 | 154.67 | 58.21 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 14 | G SIWALL NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 15 | G EIWALL NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 16 | G GFLOOR NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 17 | G CEILIN NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 18 | G INTERNALMASS NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 19 | G SWALL SEA | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 20 | GWINDOW1 S SEA | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 21 | G EWALL SEA | 0 | 154.67 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 22 | GWINDOW1 E SEA | 0 | 154.67 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 23 | G NIWALL SEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 24 | iz-G EIWALL S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 25 | G GFLOOR SEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 26 | G CEILIN SEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 27 | G INTERNALMASS SEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 28 | G NWALL NEA | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 29 | GWINDOW1 N NEA | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 30 | G EWALL NEA | 0 | 154.67 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 31 | GWINDOW1 E NEA | 0 | 154.67 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 32 | G SIWALL NEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 33 | iz-G EIWALL N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 34 | G GFLOOR NEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 35 | G CEILIN NEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 36 | G INTERNALMASS NEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 37 | G NWALL N1A | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 3 | No | No |
| 38 | GWINDOW1 N N1A | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 2 | No | No |
| 39 | G SIWALL N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 40 | G EIWALL N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 41 | iz-G EIWALL NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 42 | G GFLOOR N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 43 | G CEILIN N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 44 | G INTERNALMASS N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 45 | G NWALL N2A | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 3 | No | No |
| 46 | GWINDOW1 N N2A | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 2 | No | No |
| 47 | G SIWALL N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 48 | G EIWALL N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 49 | iz-G EIWALL N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 50 | G GFLOOR N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 51 | G CEILIN N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 52 | G INTERNALMASS N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 53 | G SWALL S1A | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 3 | No | No |
| 54 | GWINDOW1 S S1A | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 2 | No | No |
| 55 | G NIWALL S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 56 | G EIWALL S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 57 | iz-G EIWALL SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 58 | G GFLOOR S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 59 | G CEILIN S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 60 | G INTERNALMASS S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 61 | G SWALL S2A | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 3 | No | No |
| 62 | GWINDOW1 S S2A | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 2 | No | No |
| 63 | G NIWALL S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 64 | G EIWALL S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 65 | iz-G EIWALL S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 66 | G GFLOOR S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 67 | G CEILIN S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 68 | G INTERNALMASS S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 69 | M WWALL SWA | 0 | 154.67 | 58.21 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 70 | MWINDOW1 W SWA | 0 | 154.67 | 58.21 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 71 | M SWALL SWA | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 72 | MWINDOW1 S SWA | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 73 | M NIWALL SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 74 | M EIWALL SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 75 | M GFLOOR SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 76 | M CEILIN SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 77 | M INTERNALMASS SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 78 | M NWALL NWA | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 79 | MWINDOW1 N NWA | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 80 | M WWALL NWA | 0 | 154.67 | 58.21 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 81 | MWINDOW1 W NWA | 0 | 154.67 | 58.21 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 82 | M SIWALL NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 83 | M EIWALL NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 84 | M GFLOOR NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 85 | M CEILIN NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 86 | M INTERNALMASS NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 87 | M EWALL SEA | 0 | 154.67 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 88 | MWINDOW1 E SEA | 0 | 154.67 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 89 | M SWALL SEA | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 90 | MWINDOW1 S SEA | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 91 | M NIWALL SEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 92 | iz-M EIWALL S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 93 | M GFLOOR SEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 94 | M CEILIN SEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 95 | M INTERNALMASS SEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 96 | M NWALL NEA | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 97 | MWINDOW1 N NEA | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 98 | M EWALL NEA | 0 | 154.67 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 99 | MWINDOW1 E NEA | 0 | 154.67 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 100 | M SIWALL NEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 101 | iz-M EIWALL N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 102 | M GFLOOR NEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 103 | M CEILIN NEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 104 | M INTERNALMASS NEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 105 | M NWALL N1A | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 3 | No | No |
| 106 | MWINDOW1 N N1A | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 2 | No | No |
| 107 | M SIWALL N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 108 | M EIWALL N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 109 | iz-M EIWALL NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 110 | M GFLOOR N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 111 | M CEILIN N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 112 | M INTERNALMASS N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 113 | M NWALL N2A | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 3 | No | No |
| 114 | MWINDOW1 N N2A | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 2 | No | No |
| 115 | M SIWALL N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 116 | M EIWALL N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 117 | iz-M EIWALL N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 118 | M GFLOOR N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 119 | M CEILIN N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 120 | M INTERNALMASS N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 121 | M SWALL S1A | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 3 | No | No |
| 122 | MWINDOW1 S S1A | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 2 | No | No |
| 123 | M NIWALL S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 124 | M EIWALL S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 125 | iz-M EIWALL SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 126 | M GFLOOR S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 127 | M CEILIN S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 128 | M INTERNALMASS S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 129 | M SWALL S2A | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 3 | No | No |
| 130 | MWINDOW1 S S2A | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 2 | No | No |
| 131 | M NIWALL S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 132 | M EIWALL S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 133 | iz-M EIWALL S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 134 | M GFLOOR S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 135 | M CEILIN S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 136 | M INTERNALMASS S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 137 | T WWALL SWA | 0 | 154.67 | 58.21 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 138 | TWINDOW1 W SWA | 0 | 154.67 | 58.21 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 139 | T SWALL SWA | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 140 | TWINDOW1 S SWA | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 141 | T NIWALL SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 142 | T EIWALL SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 143 | T GFLOOR SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 144 | T ROOF SWA | 0 | 783.65 | 155.90 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 145 | T INTERNALMASS SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 146 | T NWALL NWA | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 147 | TWINDOW1 N NWA | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 148 | T WWALL NWA | 0 | 154.67 | 58.21 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 149 | TWINDOW1 W NWA | 0 | 154.67 | 58.21 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 150 | T SIWALL NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 151 | T EIWALL NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 152 | T GFLOOR NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 153 | T ROOF NWA | 0 | 783.65 | 155.90 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 154 | T INTERNALMASS NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 155 | T EWALL SEA | 0 | 154.67 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 156 | TWINDOW1 E SEA | 0 | 154.67 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 157 | T SWALL SEA | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 158 | TWINDOW1 S SEA | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 159 | T NIWALL SEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 160 | iz-T EIWALL S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 161 | T GFLOOR SEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 162 | T ROOF SEA | 0 | 783.65 | 155.90 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 163 | T INTERNALMASS SEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 164 | T NWALL NEA | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 165 | TWINDOW1 N NEA | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 166 | T EWALL NEA | 0 | 154.67 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 167 | TWINDOW1 E NEA | 0 | 154.67 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 168 | T SIWALL NEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 169 | iz-T EIWALL N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 170 | T GFLOOR NEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 171 | T ROOF NEA | 0 | 783.65 | 155.90 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 172 | T INTERNALMASS NEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 173 | T NWALL N1A | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 3 | No | No |
| 174 | TWINDOW1 N N1A | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 2 | No | No |
| 175 | T SIWALL N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 176 | T EIWALL N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 177 | iz-T EIWALL NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 178 | T GFLOOR N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 179 | T ROOF N1A | 0 | 783.65 | 155.90 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 180 | T INTERNALMASS N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 181 | T NWALL N2A | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 3 | No | No |
| 182 | TWINDOW1 N N2A | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 2 | No | No |
| 183 | T SIWALL N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 184 | T EIWALL N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 185 | iz-T EIWALL N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 186 | T GFLOOR N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 187 | T ROOF N2A | 0 | 783.65 | 155.90 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 188 | T INTERNALMASS N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 189 | T SWALL S1A | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 3 | No | No |
| 190 | TWINDOW1 S S1A | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 2 | No | No |
| 191 | T NIWALL S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 192 | T EIWALL S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 193 | iz-T EIWALL SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 194 | T GFLOOR S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 195 | T ROOF S1A | 0 | 783.65 | 155.90 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 196 | T INTERNALMASS S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 197 | T SWALL S2A | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 3 | No | No |
| 198 | TWINDOW1 S S2A | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 2 | No | No |
| 199 | T NIWALL S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 200 | T EIWALL S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 201 | iz-T EIWALL S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 202 | T GFLOOR S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 203 | T ROOF S2A | 0 | 783.65 | 155.90 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 204 | T INTERNALMASS S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 205 | T WWALL C | 0 | 154.67 | 58.21 | 12.19 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 3 | No | No |
| 206 | T EWALL C | 0 | 154.67 | 123.02 | 12.19 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 3 | No | No |
| 207 | TWINDOW14 | 0 | 154.67 | 123.02 | 12.19 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 2 | No | No |
| 208 | iz-T NIWALL SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 209 | iz-T NIWALL S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 210 | iz-T NIWALL S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 211 | iz-T NIWALL SEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 212 | iz-T SIWALL NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 213 | iz-T SIWALL N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 214 | iz-T SIWALL N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 215 | iz-T SIWALL NEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 216 | T FLOOR C | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 217 | T ROOF C | 0 | 783.65 | 155.90 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 218 | G WWALL C | 0 | 154.67 | 58.21 | 12.19 | 0 | 3.05 | 3.35 | 3.24 | 0.32 | 4 | No | No |
| 219 | G EWALL C | 0 | 154.67 | 123.02 | 12.19 | 0 | 3.05 | 3.35 | 3.24 | 0.32 | 4 | No | No |
| 220 | ENTRANCE DOOR | 0 | 154.67 | 123.02 | 12.19 | 0 | 3.05 | 3.35 | 3.24 | 0.32 | 1 | No | No |
| 221 | iz-G NIWALL SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.32 | 0 | No | No |
| 222 | iz-G NIWALL S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.32 | 0 | No | No |
| 223 | iz-G NIWALL S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.32 | 0 | No | No |
| 224 | iz-G NIWALL SEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.32 | 0 | No | No |
| 225 | iz-G SIWALL NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.32 | 0 | No | No |
| 226 | iz-G SIWALL N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.32 | 0 | No | No |
| 227 | iz-G SIWALL N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.32 | 0 | No | No |
| 228 | iz-G SIWALL NEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.32 | 0 | No | No |
| 229 | G FLOOR C | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.32 | 0 | No | No |
| 230 | G CEILING C | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.32 | 0 | No | No |
| 231 | M WWALL C | 0 | 154.67 | 58.21 | 12.19 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 4 | No | No |
| 232 | M EWALL C | 0 | 154.67 | 123.02 | 12.19 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 3 | No | No |
| 233 | MWINDOW14 | 0 | 154.67 | 123.02 | 12.19 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 2 | No | No |
| 234 | iz-M NIWALL SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 235 | iz-M NIWALL S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 236 | iz-M NIWALL S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 237 | iz-M NIWALL SEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 238 | iz-M SIWALL NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 239 | iz-M SIWALL N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 240 | iz-M SIWALL N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 241 | iz-M SIWALL NEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 242 | M FLOOR C | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 243 | M CEILING C | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
| 1 | INFIL_GSW | INF_APT_SCH | G SW APARTMENT | 88.25 | 2.5 | 3.333E-002 | 3.777E-004 | 5.696E-004 | 0.446 | 0.000 | 0.000 | 0.224 | 0.000 |
| 2 | INFIL_GNW | INF_APT_SCH | G NW APARTMENT | 88.25 | 2.5 | 3.333E-002 | 3.777E-004 | 5.696E-004 | 0.446 | 0.000 | 0.000 | 0.224 | 0.000 |
| 3 | INFIL_OFFICE | INF_OFF_SCH | OFFICE | 88.25 | 4.7 | 3.333E-002 | 3.777E-004 | 5.696E-004 | 0.446 | 0.000 | 0.000 | 0.224 | 0.000 |
| 4 | INFIL_GNE | INF_APT_SCH | G NE APARTMENT | 88.25 | 2.5 | 3.333E-002 | 3.777E-004 | 5.696E-004 | 0.446 | 0.000 | 0.000 | 0.224 | 0.000 |
| 5 | INFIL_GN1 | INF_APT_SCH | G N1 APARTMENT | 88.25 | 2.5 | 2.011E-002 | 2.278E-004 | 5.696E-004 | 0.269 | 0.000 | 0.000 | 0.224 | 0.000 |
| 6 | INFIL_GN2 | INF_APT_SCH | G N2 APARTMENT | 88.25 | 2.5 | 2.011E-002 | 2.278E-004 | 5.696E-004 | 0.269 | 0.000 | 0.000 | 0.224 | 0.000 |
| 7 | INFIL_GS1 | INF_APT_SCH | G S1 APARTMENT | 88.25 | 2.5 | 2.011E-002 | 2.278E-004 | 5.696E-004 | 0.269 | 0.000 | 0.000 | 0.224 | 0.000 |
| 8 | INFIL_GS2 | INF_APT_SCH | G S2 APARTMENT | 88.25 | 2.5 | 2.011E-002 | 2.278E-004 | 5.696E-004 | 0.269 | 0.000 | 0.000 | 0.224 | 0.000 |
| 9 | INFIL_MSW | INF_APT_SCH | M SW APARTMENT | 88.25 | 2.5 | 3.333E-002 | 3.777E-004 | 5.696E-004 | 0.446 | 0.000 | 0.000 | 0.224 | 0.000 |
| 10 | INFIL_MNW | INF_APT_SCH | M NW APARTMENT | 88.25 | 2.5 | 3.333E-002 | 3.777E-004 | 5.696E-004 | 0.446 | 0.000 | 0.000 | 0.224 | 0.000 |
| 11 | INFIL_MSE | INF_APT_SCH | M SE APARTMENT | 88.25 | 2.5 | 3.333E-002 | 3.777E-004 | 5.696E-004 | 0.446 | 0.000 | 0.000 | 0.224 | 0.000 |
| 12 | INFIL_MNE | INF_APT_SCH | M NE APARTMENT | 88.25 | 2.5 | 3.333E-002 | 3.777E-004 | 5.696E-004 | 0.446 | 0.000 | 0.000 | 0.224 | 0.000 |
| 13 | INFIL_MN1 | INF_APT_SCH | M N1 APARTMENT | 88.25 | 2.5 | 2.011E-002 | 2.278E-004 | 5.696E-004 | 0.269 | 0.000 | 0.000 | 0.224 | 0.000 |
| 14 | INFIL_MN2 | INF_APT_SCH | M N2 APARTMENT | 88.25 | 2.5 | 2.011E-002 | 2.278E-004 | 5.696E-004 | 0.269 | 0.000 | 0.000 | 0.224 | 0.000 |
| 15 | INFIL_MS1 | INF_APT_SCH | M S1 APARTMENT | 88.25 | 2.5 | 2.011E-002 | 2.278E-004 | 5.696E-004 | 0.269 | 0.000 | 0.000 | 0.224 | 0.000 |
| 16 | INFIL_MS2 | INF_APT_SCH | M S2 APARTMENT | 88.25 | 2.5 | 2.011E-002 | 2.278E-004 | 5.696E-004 | 0.269 | 0.000 | 0.000 | 0.224 | 0.000 |
| 17 | INFIL_SW | INF_APT_SCH | T SW APARTMENT | 88.25 | 2.5 | 3.333E-002 | 3.777E-004 | 2.271E-004 | 0.446 | 0.000 | 0.000 | 0.224 | 0.000 |
| 18 | INFIL_NW | INF_APT_SCH | T NW APARTMENT | 88.25 | 2.5 | 3.333E-002 | 3.777E-004 | 2.271E-004 | 0.446 | 0.000 | 0.000 | 0.224 | 0.000 |
| 19 | INFIL_SE | INF_APT_SCH | T SE APARTMENT | 88.25 | 2.5 | 3.333E-002 | 3.777E-004 | 2.271E-004 | 0.446 | 0.000 | 0.000 | 0.224 | 0.000 |
| 20 | INFIL_NE | INF_APT_SCH | T NE APARTMENT | 88.25 | 2.5 | 3.333E-002 | 3.777E-004 | 2.271E-004 | 0.446 | 0.000 | 0.000 | 0.224 | 0.000 |
| 21 | INFIL_TN1 | INF_APT_SCH | T N1 APARTMENT | 88.25 | 2.5 | 2.011E-002 | 2.278E-004 | 1.627E-004 | 0.269 | 0.000 | 0.000 | 0.224 | 0.000 |
| 22 | INFIL_TN2 | INF_APT_SCH | T N2 APARTMENT | 88.25 | 2.5 | 2.011E-002 | 2.278E-004 | 1.627E-004 | 0.269 | 0.000 | 0.000 | 0.224 | 0.000 |
| 23 | INFIL_TS1 | INF_APT_SCH | T S1 APARTMENT | 88.25 | 2.5 | 2.011E-002 | 2.278E-004 | 1.627E-004 | 0.269 | 0.000 | 0.000 | 0.224 | 0.000 |
| 24 | INFIL_TS2 | INF_APT_SCH | T S2 APARTMENT | 88.25 | 2.5 | 2.011E-002 | 2.278E-004 | 1.627E-004 | 0.269 | 0.000 | 0.000 | 0.224 | 0.000 |
| 25 | INFIL_GC | INF_COR_SCH | G CORRIDOR | 77.66 | 4.2 | 5.820E-003 | 7.494E-005 | 5.696E-004 | 8.852E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
| 26 | DOOR_INFIL_GC | INFIL_DOOR_OPENING_SCH | G CORRIDOR | 77.66 | 4.2 | 0.521 | 6.703E-003 | 5.094E-002 | 7.917 | 1.000 | 0.000 | 0.000 | 0.000 |
| 27 | INFIL_MC | INF_COR_SCH | M CORRIDOR | 77.66 | 4.2 | 5.820E-003 | 7.494E-005 | 5.696E-004 | 8.852E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
| 28 | INFIL_TC | INF_COR_SCH | T CORRIDOR | 77.66 | 4.2 | 5.820E-003 | 7.494E-005 | 6.623E-005 | 8.852E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
| Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
| 1 | G SW APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | G SW APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 2 | G NW APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | G NW APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 3 | G NE APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | G NE APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 4 | G N1 APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | G N1 APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 5 | G N2 APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | G N2 APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 6 | G S1 APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | G S1 APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 7 | G S2 APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | G S2 APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 8 | M SW APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | M SW APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 9 | M NW APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | M NW APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 10 | M SE APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | M SE APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 11 | M NE APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | M NE APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 12 | M N1 APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | M N1 APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 13 | M N2 APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | M N2 APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 14 | M S1 APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | M S1 APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 15 | M S2 APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | M S2 APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 16 | T SW APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | T SW APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 17 | T NW APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | T NW APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 18 | T SE APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | T SE APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 19 | T NE APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | T NE APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 20 | T N1 APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | T N1 APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 21 | T N2 APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | T N2 APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 22 | T S1 APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | T S1 APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 23 | T S2 APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | T S2 APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| Simple | |
| 1 | Simple |
| Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
| 1 | G SW APARTMENT | Mixing/Well-Stirred |
| 2 | G NW APARTMENT | Mixing/Well-Stirred |
| 3 | OFFICE | Mixing/Well-Stirred |
| 4 | G NE APARTMENT | Mixing/Well-Stirred |
| 5 | G N1 APARTMENT | Mixing/Well-Stirred |
| 6 | G N2 APARTMENT | Mixing/Well-Stirred |
| 7 | G S1 APARTMENT | Mixing/Well-Stirred |
| 8 | G S2 APARTMENT | Mixing/Well-Stirred |
| 9 | M SW APARTMENT | Mixing/Well-Stirred |
| 10 | M NW APARTMENT | Mixing/Well-Stirred |
| 11 | M SE APARTMENT | Mixing/Well-Stirred |
| 12 | M NE APARTMENT | Mixing/Well-Stirred |
| 13 | M N1 APARTMENT | Mixing/Well-Stirred |
| 14 | M N2 APARTMENT | Mixing/Well-Stirred |
| 15 | M S1 APARTMENT | Mixing/Well-Stirred |
| 16 | M S2 APARTMENT | Mixing/Well-Stirred |
| 17 | T SW APARTMENT | Mixing/Well-Stirred |
| 18 | T NW APARTMENT | Mixing/Well-Stirred |
| 19 | T SE APARTMENT | Mixing/Well-Stirred |
| 20 | T NE APARTMENT | Mixing/Well-Stirred |
| 21 | T N1 APARTMENT | Mixing/Well-Stirred |
| 22 | T N2 APARTMENT | Mixing/Well-Stirred |
| 23 | T S1 APARTMENT | Mixing/Well-Stirred |
| 24 | T S2 APARTMENT | Mixing/Well-Stirred |
| 25 | T CORRIDOR | Mixing/Well-Stirred |
| 26 | G CORRIDOR | Mixing/Well-Stirred |
| 27 | M CORRIDOR | Mixing/Well-Stirred |
| No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
| 1 | NoMultizoneOrDistribution |
| Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
| 1 | 1.000 | 1.000 | 1.000 | 1.000 |
| Value | |
| 1 | 6 |
| Sizing Factor ID | Value | |
| 1 | Global | 1.2000 |
| 2 | Zone G SW APARTMENT | 1.2000 |
| 3 | Zone G NW APARTMENT | 1.2000 |
| 4 | Zone OFFICE | 1.2000 |
| 5 | Zone G NE APARTMENT | 1.2000 |
| 6 | Zone G N1 APARTMENT | 1.2000 |
| 7 | Zone G N2 APARTMENT | 1.2000 |
| 8 | Zone G S1 APARTMENT | 1.2000 |
| 9 | Zone G S2 APARTMENT | 1.2000 |
| 10 | Zone M SW APARTMENT | 1.2000 |
| 11 | Zone M NW APARTMENT | 1.2000 |
| 12 | Zone M SE APARTMENT | 1.2000 |
| 13 | Zone M NE APARTMENT | 1.2000 |
| 14 | Zone M N1 APARTMENT | 1.2000 |
| 15 | Zone M N2 APARTMENT | 1.2000 |
| 16 | Zone M S1 APARTMENT | 1.2000 |
| 17 | Zone M S2 APARTMENT | 1.2000 |
| 18 | Zone T SW APARTMENT | 1.2000 |
| 19 | Zone T NW APARTMENT | 1.2000 |
| 20 | Zone T SE APARTMENT | 1.2000 |
| 21 | Zone T NE APARTMENT | 1.2000 |
| 22 | Zone T N1 APARTMENT | 1.2000 |
| 23 | Zone T N2 APARTMENT | 1.2000 |
| 24 | Zone T S1 APARTMENT | 1.2000 |
| 25 | Zone T S2 APARTMENT | 1.2000 |
| Sizing Factor ID | Value | |
| 1 | Global | 1.2000 |
| 2 | Zone G SW APARTMENT | 1.2000 |
| 3 | Zone G NW APARTMENT | 1.2000 |
| 4 | Zone OFFICE | 1.2000 |
| 5 | Zone G NE APARTMENT | 1.2000 |
| 6 | Zone G N1 APARTMENT | 1.2000 |
| 7 | Zone G N2 APARTMENT | 1.2000 |
| 8 | Zone G S1 APARTMENT | 1.2000 |
| 9 | Zone G S2 APARTMENT | 1.2000 |
| 10 | Zone M SW APARTMENT | 1.2000 |
| 11 | Zone M NW APARTMENT | 1.2000 |
| 12 | Zone M SE APARTMENT | 1.2000 |
| 13 | Zone M NE APARTMENT | 1.2000 |
| 14 | Zone M N1 APARTMENT | 1.2000 |
| 15 | Zone M N2 APARTMENT | 1.2000 |
| 16 | Zone M S1 APARTMENT | 1.2000 |
| 17 | Zone M S2 APARTMENT | 1.2000 |
| 18 | Zone T SW APARTMENT | 1.2000 |
| 19 | Zone T NW APARTMENT | 1.2000 |
| 20 | Zone T SE APARTMENT | 1.2000 |
| 21 | Zone T NE APARTMENT | 1.2000 |
| 22 | Zone T N1 APARTMENT | 1.2000 |
| 23 | Zone T N2 APARTMENT | 1.2000 |
| 24 | Zone T S1 APARTMENT | 1.2000 |
| 25 | Zone T S2 APARTMENT | 1.2000 |
| Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
| 1 | G SW APARTMENT | Cooling | 3947.36456 | 4736.83747 | 0.28576 | 0.34292 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 26.67300 | 1.33605E-002 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 2 | G SW APARTMENT | Heating | 2538.82836 | 3046.59403 | 0.11221 | 0.13465 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:50:00 | -16.30000 | 9.24091E-004 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 3 | G NW APARTMENT | Cooling | 3713.04857 | 4455.65829 | 0.26847 | 0.32217 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 26.67300 | 1.33605E-002 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 4 | G NW APARTMENT | Heating | 2416.62618 | 2899.95142 | 0.10681 | 0.12817 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -16.30000 | 9.24091E-004 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 5 | OFFICE | Cooling | 4311.59188 | 5173.91025 | 0.31696 | 0.38036 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 25.18500 | 1.33579E-002 | 88.24927 | 4.74953 | 3.81060E-002 | 0.00000 |
| 6 | OFFICE | Heating | 2988.53822 | 3586.24586 | 0.13209 | 0.15850 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 18:50:00 | -16.30000 | 9.24091E-004 | 88.24927 | 4.74953 | 3.81060E-002 | 0.00000 |
| 7 | G NE APARTMENT | Cooling | 3321.93278 | 3986.31934 | 0.23951 | 0.28741 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 26.67300 | 1.33605E-002 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 8 | G NE APARTMENT | Heating | 2407.39176 | 2888.87011 | 0.10640 | 0.12768 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -16.30000 | 9.24091E-004 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 9 | G N1 APARTMENT | Cooling | 3048.37847 | 3658.05416 | 0.21919 | 0.26302 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 26.67300 | 1.33605E-002 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 10 | G N1 APARTMENT | Heating | 1513.91901 | 1816.70281 | 6.69135E-002 | 8.02962E-002 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -16.30000 | 9.24091E-004 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 11 | G N2 APARTMENT | Cooling | 3041.35284 | 3649.62341 | 0.21867 | 0.26240 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 26.67300 | 1.33605E-002 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 12 | G N2 APARTMENT | Heating | 1513.65391 | 1816.38469 | 6.69018E-002 | 8.02822E-002 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -16.30000 | 9.24091E-004 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 13 | G S1 APARTMENT | Cooling | 3304.58081 | 3965.49697 | 0.23820 | 0.28584 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 26.67300 | 1.33605E-002 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 14 | G S1 APARTMENT | Heating | 1637.83406 | 1965.40087 | 7.23899E-002 | 8.68679E-002 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:50:00 | -16.30000 | 9.24091E-004 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 15 | G S2 APARTMENT | Cooling | 3325.03138 | 3990.03765 | 0.23972 | 0.28767 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 26.67300 | 1.33605E-002 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 16 | G S2 APARTMENT | Heating | 1645.73402 | 1974.88083 | 7.27391E-002 | 8.72869E-002 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:50:00 | -16.30000 | 9.24091E-004 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 17 | M SW APARTMENT | Cooling | 9949.27310 | 11939.12772 | 0.72401 | 0.86881 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 26.67300 | 1.33605E-002 | 88.24927 | 2.50000 | 5.19091E-002 | 0.00000 |
| 18 | M SW APARTMENT | Heating | 4526.34281 | 5431.61137 | 0.20004 | 0.24005 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | -16.30000 | 9.24091E-004 | 88.24927 | 2.50000 | 5.19091E-002 | 0.00000 |
| 19 | M NW APARTMENT | Cooling | 9584.65502 | 11501.58603 | 0.69708 | 0.83649 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 26.67300 | 1.33605E-002 | 88.24927 | 2.50000 | 5.19091E-002 | 0.00000 |
| 20 | M NW APARTMENT | Heating | 4234.41680 | 5081.30016 | 0.18714 | 0.22457 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | -16.30000 | 9.24091E-004 | 88.24927 | 2.50000 | 5.19091E-002 | 0.00000 |
| 21 | M SE APARTMENT | Cooling | 8783.43254 | 10540.11905 | 0.63765 | 0.76518 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 26.67300 | 1.33605E-002 | 88.24927 | 2.50000 | 5.19091E-002 | 0.00000 |
| 22 | M SE APARTMENT | Heating | 4504.53454 | 5405.44144 | 0.19908 | 0.23889 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | -16.30000 | 9.24091E-004 | 88.24927 | 2.50000 | 5.19091E-002 | 0.00000 |
| 23 | M NE APARTMENT | Cooling | 8431.00660 | 10117.20792 | 0.61148 | 0.73378 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 26.67300 | 1.33605E-002 | 88.24927 | 2.50000 | 5.19091E-002 | 0.00000 |
| 24 | M NE APARTMENT | Heating | 4212.57845 | 5055.09414 | 0.18618 | 0.22341 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | -16.30000 | 9.24091E-004 | 88.24927 | 2.50000 | 5.19091E-002 | 0.00000 |
| 25 | M N1 APARTMENT | Cooling | 7594.71530 | 9113.65836 | 0.54933 | 0.65919 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 26.67300 | 1.33605E-002 | 88.24927 | 2.50000 | 5.19091E-002 | 0.00000 |
| 26 | M N1 APARTMENT | Heating | 2316.76831 | 2780.12197 | 0.10239 | 0.12287 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | -16.30000 | 9.24091E-004 | 88.24927 | 2.50000 | 5.19091E-002 | 0.00000 |
| 27 | M N2 APARTMENT | Cooling | 7575.34326 | 9090.41191 | 0.54790 | 0.65748 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 26.67300 | 1.33605E-002 | 88.24927 | 2.50000 | 5.19091E-002 | 0.00000 |
| 28 | M N2 APARTMENT | Heating | 2316.21181 | 2779.45417 | 0.10237 | 0.12284 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | -16.30000 | 9.24091E-004 | 88.24927 | 2.50000 | 5.19091E-002 | 0.00000 |
| 29 | M S1 APARTMENT | Cooling | 8018.45121 | 9622.14146 | 0.58075 | 0.69690 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 26.67300 | 1.33605E-002 | 88.24927 | 2.50000 | 5.19091E-002 | 0.00000 |
| 30 | M S1 APARTMENT | Heating | 2602.83565 | 3123.40278 | 0.11504 | 0.13804 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | -16.30000 | 9.24091E-004 | 88.24927 | 2.50000 | 5.19091E-002 | 0.00000 |
| 31 | M S2 APARTMENT | Cooling | 7998.03301 | 9597.63961 | 0.57923 | 0.69508 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 26.67300 | 1.33605E-002 | 88.24927 | 2.50000 | 5.19091E-002 | 0.00000 |
| 32 | M S2 APARTMENT | Heating | 2602.28581 | 3122.74297 | 0.11501 | 0.13801 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | -16.30000 | 9.24091E-004 | 88.24927 | 2.50000 | 5.19091E-002 | 0.00000 |
| 33 | T SW APARTMENT | Cooling | 5464.22032 | 6557.06439 | 0.39805 | 0.47767 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 26.67300 | 1.33605E-002 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 34 | T SW APARTMENT | Heating | 3729.22232 | 4475.06678 | 0.16480 | 0.19777 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | -16.30000 | 9.24091E-004 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 35 | T NW APARTMENT | Cooling | 5389.18082 | 6467.01698 | 0.39249 | 0.47099 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 26.67300 | 1.33605E-002 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 36 | T NW APARTMENT | Heating | 3573.63901 | 4288.36681 | 0.15793 | 0.18952 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | -16.30000 | 9.24091E-004 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 37 | T SE APARTMENT | Cooling | 4619.32237 | 5543.18684 | 0.33548 | 0.40258 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 26.67300 | 1.33605E-002 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 38 | T SE APARTMENT | Heating | 3714.30394 | 4457.16473 | 0.16415 | 0.19697 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | -16.30000 | 9.24091E-004 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 39 | T NE APARTMENT | Cooling | 4542.78304 | 5451.33964 | 0.32987 | 0.39584 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 26.67300 | 1.33605E-002 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 40 | T NE APARTMENT | Heating | 3558.66311 | 4270.39573 | 0.15727 | 0.18872 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | -16.30000 | 9.24091E-004 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 41 | T N1 APARTMENT | Cooling | 4273.12657 | 5127.75188 | 0.30989 | 0.37187 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 26.67300 | 1.33605E-002 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 42 | T N1 APARTMENT | Heating | 2419.55318 | 2903.46382 | 0.10693 | 0.12832 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | -16.30000 | 9.24091E-004 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 43 | T N2 APARTMENT | Cooling | 4246.91411 | 5096.29693 | 0.30794 | 0.36953 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 26.67300 | 1.33605E-002 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 44 | T N2 APARTMENT | Heating | 2419.14841 | 2902.97809 | 0.10692 | 0.12830 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | -16.30000 | 9.24091E-004 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 45 | T S1 APARTMENT | Cooling | 4366.66264 | 5239.99516 | 0.31679 | 0.38014 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 26.67300 | 1.33605E-002 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 46 | T S1 APARTMENT | Heating | 2575.63217 | 3090.75861 | 0.11383 | 0.13660 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | -16.30000 | 9.24091E-004 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 47 | T S2 APARTMENT | Cooling | 4340.49712 | 5208.59654 | 0.31485 | 0.37782 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 26.67300 | 1.33605E-002 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 48 | T S2 APARTMENT | Heating | 2575.23237 | 3090.27884 | 0.11381 | 0.13658 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | -16.30000 | 9.24091E-004 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
| 1 | SPLIT GSW | Cooling | Sensible | 4627.69 | 0.34292 | 0.34292 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 2 | SPLIT GSW | Heating | Sensible | 4147.26 | 0.13465 | 0.13465 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:50:00 |
| 3 | SPLIT GNW | Cooling | Sensible | 4350.18 | 0.32217 | 0.32217 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 4 | SPLIT GNW | Heating | Sensible | 4002.76 | 0.12817 | 0.12817 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 |
| 5 | SPLIT OFFICE | Cooling | Sensible | 5058.19 | 0.38036 | 0.38036 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 6 | SPLIT OFFICE | Heating | Sensible | 5215.14 | 0.15850 | 0.15850 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 18:50:00 |
| 7 | SPLIT GNE | Cooling | Sensible | 3885.74 | 0.28741 | 0.28741 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 8 | SPLIT GNE | Heating | Sensible | 3991.84 | 0.12768 | 0.12768 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 |
| 9 | SPLIT GN1 | Cooling | Sensible | 3560.33 | 0.26302 | 0.26302 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 10 | SPLIT GN1 | Heating | Sensible | 2935.30 | 8.02962E-002 | 8.02962E-002 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 |
| 11 | SPLIT GN2 | Cooling | Sensible | 3552.00 | 0.26240 | 0.26240 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 12 | SPLIT GN2 | Heating | Sensible | 2934.98 | 8.02822E-002 | 8.02822E-002 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 |
| 13 | SPLIT GS1 | Cooling | Sensible | 3865.40 | 0.28584 | 0.28584 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 14 | SPLIT GS1 | Heating | Sensible | 3081.82 | 8.68679E-002 | 8.68679E-002 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:50:00 |
| 15 | SPLIT GS2 | Cooling | Sensible | 3889.68 | 0.28767 | 0.28767 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 16 | SPLIT GS2 | Heating | Sensible | 3091.17 | 8.72869E-002 | 8.72869E-002 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:50:00 |
| 17 | SPLIT MSW | Cooling | Sensible | 11695.00 | 0.86881 | 0.86881 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 18 | SPLIT MSW | Heating | Sensible | 7642.49 | 0.24005 | 0.24005 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 |
| 19 | SPLIT MNW | Cooling | Sensible | 11263.36 | 0.83649 | 0.83649 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 20 | SPLIT MNW | Heating | Sensible | 7297.30 | 0.22457 | 0.22457 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 |
| 21 | SPLIT MSE | Cooling | Sensible | 10312.70 | 0.76518 | 0.76518 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 22 | SPLIT MSE | Heating | Sensible | 7616.70 | 0.23889 | 0.23889 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 |
| 23 | SPLIT MNE | Cooling | Sensible | 9893.88 | 0.73378 | 0.73378 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 24 | SPLIT MNE | Heating | Sensible | 7271.48 | 0.22341 | 0.22341 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 |
| 25 | SPLIT MN1 | Cooling | Sensible | 8899.69 | 0.65919 | 0.65919 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 26 | SPLIT MN1 | Heating | Sensible | 5029.69 | 0.12287 | 0.12287 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 |
| 27 | SPLIT MN2 | Cooling | Sensible | 8876.78 | 0.65748 | 0.65748 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 28 | SPLIT MN2 | Heating | Sensible | 5029.03 | 0.12284 | 0.12284 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 |
| 29 | SPLIT MS1 | Cooling | Sensible | 9403.26 | 0.69690 | 0.69690 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 30 | SPLIT MS1 | Heating | Sensible | 5367.95 | 0.13804 | 0.13804 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 |
| 31 | SPLIT MS2 | Cooling | Sensible | 9378.96 | 0.69508 | 0.69508 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 32 | SPLIT MS2 | Heating | Sensible | 5367.30 | 0.13801 | 0.13801 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 |
| 33 | SPLIT TSW | Cooling | Sensible | 6426.03 | 0.47767 | 0.47767 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 34 | SPLIT TSW | Heating | Sensible | 5554.86 | 0.19777 | 0.19777 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 |
| 35 | SPLIT TNW | Cooling | Sensible | 6337.13 | 0.47099 | 0.47099 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 36 | SPLIT TNW | Heating | Sensible | 5370.89 | 0.18952 | 0.18952 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 |
| 37 | SPLIT TSE | Cooling | Sensible | 5425.14 | 0.40258 | 0.40258 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 38 | SPLIT TSE | Heating | Sensible | 5537.22 | 0.19697 | 0.19697 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 |
| 39 | SPLIT TNE | Cooling | Sensible | 5334.84 | 0.39584 | 0.39584 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 40 | SPLIT TNE | Heating | Sensible | 5353.18 | 0.18872 | 0.18872 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 |
| 41 | SPLIT TN1 | Cooling | Sensible | 5015.27 | 0.37187 | 0.37187 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 42 | SPLIT TN1 | Heating | Sensible | 4006.19 | 0.12832 | 0.12832 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 |
| 43 | SPLIT TN2 | Cooling | Sensible | 4984.18 | 0.36953 | 0.36953 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 44 | SPLIT TN2 | Heating | Sensible | 4005.71 | 0.12830 | 0.12830 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 |
| 45 | SPLIT TS1 | Cooling | Sensible | 5125.97 | 0.38014 | 0.38014 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 46 | SPLIT TS1 | Heating | Sensible | 4190.75 | 0.13660 | 0.13660 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 |
| 47 | SPLIT TS2 | Cooling | Sensible | 5094.95 | 0.37782 | 0.37782 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 48 | SPLIT TS2 | Heating | Sensible | 4190.27 | 0.13658 | 0.13658 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 |
| Component Type | Component Name | Input Field Description | Value | |
| 1 | ZoneHVAC:EnergyRecoveryVentilator | G SW APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 2 | ZoneHVAC:EnergyRecoveryVentilator | G SW APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 2.59546E-002 |
| 3 | Fan:OnOff | G SW APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 4 | Fan:OnOff | G SW APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 5 | HeatExchanger:AirToAir:SensibleAndLatent | G SW APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 6 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | G SW APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.34292 |
| 7 | ZoneHVAC:EnergyRecoveryVentilator | G NW APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 8 | ZoneHVAC:EnergyRecoveryVentilator | G NW APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 2.59546E-002 |
| 9 | Fan:OnOff | G NW APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 10 | Fan:OnOff | G NW APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 11 | HeatExchanger:AirToAir:SensibleAndLatent | G NW APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 12 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | G NW APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.32217 |
| 13 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | OFFICE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.38036 |
| 14 | ZoneHVAC:EnergyRecoveryVentilator | G NE APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 15 | ZoneHVAC:EnergyRecoveryVentilator | G NE APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 2.59546E-002 |
| 16 | Fan:OnOff | G NE APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 17 | Fan:OnOff | G NE APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 18 | HeatExchanger:AirToAir:SensibleAndLatent | G NE APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 19 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | G NE APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.28741 |
| 20 | ZoneHVAC:EnergyRecoveryVentilator | G N1 APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 21 | ZoneHVAC:EnergyRecoveryVentilator | G N1 APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 2.59546E-002 |
| 22 | Fan:OnOff | G N1 APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 23 | Fan:OnOff | G N1 APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 24 | HeatExchanger:AirToAir:SensibleAndLatent | G N1 APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 25 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | G N1 APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.26302 |
| 26 | ZoneHVAC:EnergyRecoveryVentilator | G N2 APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 27 | ZoneHVAC:EnergyRecoveryVentilator | G N2 APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 2.59546E-002 |
| 28 | Fan:OnOff | G N2 APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 29 | Fan:OnOff | G N2 APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 30 | HeatExchanger:AirToAir:SensibleAndLatent | G N2 APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 31 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | G N2 APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.26240 |
| 32 | ZoneHVAC:EnergyRecoveryVentilator | G S1 APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 33 | ZoneHVAC:EnergyRecoveryVentilator | G S1 APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 2.59546E-002 |
| 34 | Fan:OnOff | G S1 APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 35 | Fan:OnOff | G S1 APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 36 | HeatExchanger:AirToAir:SensibleAndLatent | G S1 APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 37 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | G S1 APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.28584 |
| 38 | ZoneHVAC:EnergyRecoveryVentilator | G S2 APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 39 | ZoneHVAC:EnergyRecoveryVentilator | G S2 APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 2.59546E-002 |
| 40 | Fan:OnOff | G S2 APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 41 | Fan:OnOff | G S2 APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 42 | HeatExchanger:AirToAir:SensibleAndLatent | G S2 APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 43 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | G S2 APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.28767 |
| 44 | ZoneHVAC:EnergyRecoveryVentilator | M SW APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 5.19091E-002 |
| 45 | ZoneHVAC:EnergyRecoveryVentilator | M SW APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 5.19091E-002 |
| 46 | Fan:OnOff | M SW APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 5.19091E-002 |
| 47 | Fan:OnOff | M SW APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 5.19091E-002 |
| 48 | HeatExchanger:AirToAir:SensibleAndLatent | M SW APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 5.19091E-002 |
| 49 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | M SW APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.86881 |
| 50 | ZoneHVAC:EnergyRecoveryVentilator | M NW APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 5.19091E-002 |
| 51 | ZoneHVAC:EnergyRecoveryVentilator | M NW APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 5.19091E-002 |
| 52 | Fan:OnOff | M NW APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 5.19091E-002 |
| 53 | Fan:OnOff | M NW APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 5.19091E-002 |
| 54 | HeatExchanger:AirToAir:SensibleAndLatent | M NW APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 5.19091E-002 |
| 55 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | M NW APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.83649 |
| 56 | ZoneHVAC:EnergyRecoveryVentilator | M SE APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 5.19091E-002 |
| 57 | ZoneHVAC:EnergyRecoveryVentilator | M SE APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 5.19091E-002 |
| 58 | Fan:OnOff | M SE APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 5.19091E-002 |
| 59 | Fan:OnOff | M SE APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 5.19091E-002 |
| 60 | HeatExchanger:AirToAir:SensibleAndLatent | M SE APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 5.19091E-002 |
| 61 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | M SE APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.76518 |
| 62 | ZoneHVAC:EnergyRecoveryVentilator | M NE APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 5.19091E-002 |
| 63 | ZoneHVAC:EnergyRecoveryVentilator | M NE APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 5.19091E-002 |
| 64 | Fan:OnOff | M NE APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 5.19091E-002 |
| 65 | Fan:OnOff | M NE APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 5.19091E-002 |
| 66 | HeatExchanger:AirToAir:SensibleAndLatent | M NE APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 5.19091E-002 |
| 67 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | M NE APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.73378 |
| 68 | ZoneHVAC:EnergyRecoveryVentilator | M N1 APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 5.19091E-002 |
| 69 | ZoneHVAC:EnergyRecoveryVentilator | M N1 APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 5.19091E-002 |
| 70 | Fan:OnOff | M N1 APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 5.19091E-002 |
| 71 | Fan:OnOff | M N1 APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 5.19091E-002 |
| 72 | HeatExchanger:AirToAir:SensibleAndLatent | M N1 APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 5.19091E-002 |
| 73 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | M N1 APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.65919 |
| 74 | ZoneHVAC:EnergyRecoveryVentilator | M N2 APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 5.19091E-002 |
| 75 | ZoneHVAC:EnergyRecoveryVentilator | M N2 APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 5.19091E-002 |
| 76 | Fan:OnOff | M N2 APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 5.19091E-002 |
| 77 | Fan:OnOff | M N2 APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 5.19091E-002 |
| 78 | HeatExchanger:AirToAir:SensibleAndLatent | M N2 APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 5.19091E-002 |
| 79 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | M N2 APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.65748 |
| 80 | ZoneHVAC:EnergyRecoveryVentilator | M S1 APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 5.19091E-002 |
| 81 | ZoneHVAC:EnergyRecoveryVentilator | M S1 APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 5.19091E-002 |
| 82 | Fan:OnOff | M S1 APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 5.19091E-002 |
| 83 | Fan:OnOff | M S1 APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 5.19091E-002 |
| 84 | HeatExchanger:AirToAir:SensibleAndLatent | M S1 APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 5.19091E-002 |
| 85 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | M S1 APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.69690 |
| 86 | ZoneHVAC:EnergyRecoveryVentilator | M S2 APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 5.19091E-002 |
| 87 | ZoneHVAC:EnergyRecoveryVentilator | M S2 APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 5.19091E-002 |
| 88 | Fan:OnOff | M S2 APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 5.19091E-002 |
| 89 | Fan:OnOff | M S2 APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 5.19091E-002 |
| 90 | HeatExchanger:AirToAir:SensibleAndLatent | M S2 APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 5.19091E-002 |
| 91 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | M S2 APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.69508 |
| 92 | ZoneHVAC:EnergyRecoveryVentilator | T SW APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 93 | ZoneHVAC:EnergyRecoveryVentilator | T SW APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 2.59546E-002 |
| 94 | Fan:OnOff | T SW APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 95 | Fan:OnOff | T SW APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 96 | HeatExchanger:AirToAir:SensibleAndLatent | T SW APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 97 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | T SW APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.47767 |
| 98 | ZoneHVAC:EnergyRecoveryVentilator | T NW APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 99 | ZoneHVAC:EnergyRecoveryVentilator | T NW APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 2.59546E-002 |
| 100 | Fan:OnOff | T NW APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 101 | Fan:OnOff | T NW APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 102 | HeatExchanger:AirToAir:SensibleAndLatent | T NW APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 103 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | T NW APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.47099 |
| 104 | ZoneHVAC:EnergyRecoveryVentilator | T SE APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 105 | ZoneHVAC:EnergyRecoveryVentilator | T SE APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 2.59546E-002 |
| 106 | Fan:OnOff | T SE APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 107 | Fan:OnOff | T SE APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 108 | HeatExchanger:AirToAir:SensibleAndLatent | T SE APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 109 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | T SE APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.40258 |
| 110 | ZoneHVAC:EnergyRecoveryVentilator | T NE APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 111 | ZoneHVAC:EnergyRecoveryVentilator | T NE APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 2.59546E-002 |
| 112 | Fan:OnOff | T NE APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 113 | Fan:OnOff | T NE APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 114 | HeatExchanger:AirToAir:SensibleAndLatent | T NE APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 115 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | T NE APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.39584 |
| 116 | ZoneHVAC:EnergyRecoveryVentilator | T N1 APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 117 | ZoneHVAC:EnergyRecoveryVentilator | T N1 APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 2.59546E-002 |
| 118 | Fan:OnOff | T N1 APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 119 | Fan:OnOff | T N1 APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 120 | HeatExchanger:AirToAir:SensibleAndLatent | T N1 APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 121 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | T N1 APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.37187 |
| 122 | ZoneHVAC:EnergyRecoveryVentilator | T N2 APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 123 | ZoneHVAC:EnergyRecoveryVentilator | T N2 APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 2.59546E-002 |
| 124 | Fan:OnOff | T N2 APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 125 | Fan:OnOff | T N2 APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 126 | HeatExchanger:AirToAir:SensibleAndLatent | T N2 APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 127 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | T N2 APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.36953 |
| 128 | ZoneHVAC:EnergyRecoveryVentilator | T S1 APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 129 | ZoneHVAC:EnergyRecoveryVentilator | T S1 APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 2.59546E-002 |
| 130 | Fan:OnOff | T S1 APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 131 | Fan:OnOff | T S1 APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 132 | HeatExchanger:AirToAir:SensibleAndLatent | T S1 APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 133 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | T S1 APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.38014 |
| 134 | ZoneHVAC:EnergyRecoveryVentilator | T S2 APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 135 | ZoneHVAC:EnergyRecoveryVentilator | T S2 APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 2.59546E-002 |
| 136 | Fan:OnOff | T S2 APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 137 | Fan:OnOff | T S2 APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 138 | HeatExchanger:AirToAir:SensibleAndLatent | T S2 APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 139 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | T S2 APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.37782 |
| 140 | AirLoopHVAC | SPLIT GSW | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.34292 |
| 141 | AirLoopHVAC | SPLIT GSW | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.34292 |
| 142 | AirLoopHVAC | SPLIT GSW | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.34292 |
| 143 | AirLoopHVAC | SPLIT GSW | Adjusted Heating Design Air Flow Rate [m3/s] | 0.34292 |
| 144 | AirLoopHVAC | SPLIT GSW | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.34292 |
| 145 | AirLoopHVAC | SPLIT GSW | Adjusted Main Design Air Flow Rate [m3/s] | 0.34292 |
| 146 | AirLoopHVAC | SPLIT GSW | User Heating Air Flow Ratio [] | 1.00000 |
| 147 | AirLoopHVAC | SPLIT GSW | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 148 | AirLoopHVAC | SPLIT GNW | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.32217 |
| 149 | AirLoopHVAC | SPLIT GNW | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.32217 |
| 150 | AirLoopHVAC | SPLIT GNW | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.32217 |
| 151 | AirLoopHVAC | SPLIT GNW | Adjusted Heating Design Air Flow Rate [m3/s] | 0.32217 |
| 152 | AirLoopHVAC | SPLIT GNW | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.32217 |
| 153 | AirLoopHVAC | SPLIT GNW | Adjusted Main Design Air Flow Rate [m3/s] | 0.32217 |
| 154 | AirLoopHVAC | SPLIT GNW | User Heating Air Flow Ratio [] | 1.00000 |
| 155 | AirLoopHVAC | SPLIT GNW | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 156 | AirLoopHVAC | SPLIT OFFICE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.38036 |
| 157 | AirLoopHVAC | SPLIT OFFICE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.38036 |
| 158 | AirLoopHVAC | SPLIT OFFICE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.38036 |
| 159 | AirLoopHVAC | SPLIT OFFICE | Adjusted Heating Design Air Flow Rate [m3/s] | 0.38036 |
| 160 | AirLoopHVAC | SPLIT OFFICE | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.38036 |
| 161 | AirLoopHVAC | SPLIT OFFICE | Adjusted Main Design Air Flow Rate [m3/s] | 0.38036 |
| 162 | AirLoopHVAC | SPLIT OFFICE | User Heating Air Flow Ratio [] | 1.00000 |
| 163 | AirLoopHVAC | SPLIT OFFICE | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 164 | AirLoopHVAC | SPLIT GNE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.28741 |
| 165 | AirLoopHVAC | SPLIT GNE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.28741 |
| 166 | AirLoopHVAC | SPLIT GNE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.28741 |
| 167 | AirLoopHVAC | SPLIT GNE | Adjusted Heating Design Air Flow Rate [m3/s] | 0.28741 |
| 168 | AirLoopHVAC | SPLIT GNE | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.28741 |
| 169 | AirLoopHVAC | SPLIT GNE | Adjusted Main Design Air Flow Rate [m3/s] | 0.28741 |
| 170 | AirLoopHVAC | SPLIT GNE | User Heating Air Flow Ratio [] | 1.00000 |
| 171 | AirLoopHVAC | SPLIT GNE | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 172 | AirLoopHVAC | SPLIT GN1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.26302 |
| 173 | AirLoopHVAC | SPLIT GN1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.26302 |
| 174 | AirLoopHVAC | SPLIT GN1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.26302 |
| 175 | AirLoopHVAC | SPLIT GN1 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.26302 |
| 176 | AirLoopHVAC | SPLIT GN1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.26302 |
| 177 | AirLoopHVAC | SPLIT GN1 | Adjusted Main Design Air Flow Rate [m3/s] | 0.26302 |
| 178 | AirLoopHVAC | SPLIT GN1 | User Heating Air Flow Ratio [] | 1.00000 |
| 179 | AirLoopHVAC | SPLIT GN1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 180 | AirLoopHVAC | SPLIT GN2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.26240 |
| 181 | AirLoopHVAC | SPLIT GN2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.26240 |
| 182 | AirLoopHVAC | SPLIT GN2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.26240 |
| 183 | AirLoopHVAC | SPLIT GN2 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.26240 |
| 184 | AirLoopHVAC | SPLIT GN2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.26240 |
| 185 | AirLoopHVAC | SPLIT GN2 | Adjusted Main Design Air Flow Rate [m3/s] | 0.26240 |
| 186 | AirLoopHVAC | SPLIT GN2 | User Heating Air Flow Ratio [] | 1.00000 |
| 187 | AirLoopHVAC | SPLIT GN2 | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 188 | AirLoopHVAC | SPLIT GS1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.28584 |
| 189 | AirLoopHVAC | SPLIT GS1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.28584 |
| 190 | AirLoopHVAC | SPLIT GS1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.28584 |
| 191 | AirLoopHVAC | SPLIT GS1 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.28584 |
| 192 | AirLoopHVAC | SPLIT GS1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.28584 |
| 193 | AirLoopHVAC | SPLIT GS1 | Adjusted Main Design Air Flow Rate [m3/s] | 0.28584 |
| 194 | AirLoopHVAC | SPLIT GS1 | User Heating Air Flow Ratio [] | 1.00000 |
| 195 | AirLoopHVAC | SPLIT GS1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 196 | AirLoopHVAC | SPLIT GS2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.28767 |
| 197 | AirLoopHVAC | SPLIT GS2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.28767 |
| 198 | AirLoopHVAC | SPLIT GS2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.28767 |
| 199 | AirLoopHVAC | SPLIT GS2 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.28767 |
| 200 | AirLoopHVAC | SPLIT GS2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.28767 |
| 201 | AirLoopHVAC | SPLIT GS2 | Adjusted Main Design Air Flow Rate [m3/s] | 0.28767 |
| 202 | AirLoopHVAC | SPLIT GS2 | User Heating Air Flow Ratio [] | 1.00000 |
| 203 | AirLoopHVAC | SPLIT GS2 | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 204 | AirLoopHVAC | SPLIT MSW | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.86881 |
| 205 | AirLoopHVAC | SPLIT MSW | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.86881 |
| 206 | AirLoopHVAC | SPLIT MSW | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.86881 |
| 207 | AirLoopHVAC | SPLIT MSW | Adjusted Heating Design Air Flow Rate [m3/s] | 0.86881 |
| 208 | AirLoopHVAC | SPLIT MSW | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.86881 |
| 209 | AirLoopHVAC | SPLIT MSW | Adjusted Main Design Air Flow Rate [m3/s] | 0.86881 |
| 210 | AirLoopHVAC | SPLIT MSW | User Heating Air Flow Ratio [] | 1.00000 |
| 211 | AirLoopHVAC | SPLIT MSW | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 212 | AirLoopHVAC | SPLIT MNW | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.83649 |
| 213 | AirLoopHVAC | SPLIT MNW | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.83649 |
| 214 | AirLoopHVAC | SPLIT MNW | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.83649 |
| 215 | AirLoopHVAC | SPLIT MNW | Adjusted Heating Design Air Flow Rate [m3/s] | 0.83649 |
| 216 | AirLoopHVAC | SPLIT MNW | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.83649 |
| 217 | AirLoopHVAC | SPLIT MNW | Adjusted Main Design Air Flow Rate [m3/s] | 0.83649 |
| 218 | AirLoopHVAC | SPLIT MNW | User Heating Air Flow Ratio [] | 1.00000 |
| 219 | AirLoopHVAC | SPLIT MNW | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 220 | AirLoopHVAC | SPLIT MSE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.76518 |
| 221 | AirLoopHVAC | SPLIT MSE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.76518 |
| 222 | AirLoopHVAC | SPLIT MSE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.76518 |
| 223 | AirLoopHVAC | SPLIT MSE | Adjusted Heating Design Air Flow Rate [m3/s] | 0.76518 |
| 224 | AirLoopHVAC | SPLIT MSE | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.76518 |
| 225 | AirLoopHVAC | SPLIT MSE | Adjusted Main Design Air Flow Rate [m3/s] | 0.76518 |
| 226 | AirLoopHVAC | SPLIT MSE | User Heating Air Flow Ratio [] | 1.00000 |
| 227 | AirLoopHVAC | SPLIT MSE | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 228 | AirLoopHVAC | SPLIT MNE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.73378 |
| 229 | AirLoopHVAC | SPLIT MNE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.73378 |
| 230 | AirLoopHVAC | SPLIT MNE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.73378 |
| 231 | AirLoopHVAC | SPLIT MNE | Adjusted Heating Design Air Flow Rate [m3/s] | 0.73378 |
| 232 | AirLoopHVAC | SPLIT MNE | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.73378 |
| 233 | AirLoopHVAC | SPLIT MNE | Adjusted Main Design Air Flow Rate [m3/s] | 0.73378 |
| 234 | AirLoopHVAC | SPLIT MNE | User Heating Air Flow Ratio [] | 1.00000 |
| 235 | AirLoopHVAC | SPLIT MNE | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 236 | AirLoopHVAC | SPLIT MN1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.65919 |
| 237 | AirLoopHVAC | SPLIT MN1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.65919 |
| 238 | AirLoopHVAC | SPLIT MN1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.65919 |
| 239 | AirLoopHVAC | SPLIT MN1 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.65919 |
| 240 | AirLoopHVAC | SPLIT MN1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.65919 |
| 241 | AirLoopHVAC | SPLIT MN1 | Adjusted Main Design Air Flow Rate [m3/s] | 0.65919 |
| 242 | AirLoopHVAC | SPLIT MN1 | User Heating Air Flow Ratio [] | 1.00000 |
| 243 | AirLoopHVAC | SPLIT MN1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 244 | AirLoopHVAC | SPLIT MN2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.65748 |
| 245 | AirLoopHVAC | SPLIT MN2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.65748 |
| 246 | AirLoopHVAC | SPLIT MN2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.65748 |
| 247 | AirLoopHVAC | SPLIT MN2 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.65748 |
| 248 | AirLoopHVAC | SPLIT MN2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.65748 |
| 249 | AirLoopHVAC | SPLIT MN2 | Adjusted Main Design Air Flow Rate [m3/s] | 0.65748 |
| 250 | AirLoopHVAC | SPLIT MN2 | User Heating Air Flow Ratio [] | 1.00000 |
| 251 | AirLoopHVAC | SPLIT MN2 | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 252 | AirLoopHVAC | SPLIT MS1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.69690 |
| 253 | AirLoopHVAC | SPLIT MS1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.69690 |
| 254 | AirLoopHVAC | SPLIT MS1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.69690 |
| 255 | AirLoopHVAC | SPLIT MS1 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.69690 |
| 256 | AirLoopHVAC | SPLIT MS1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.69690 |
| 257 | AirLoopHVAC | SPLIT MS1 | Adjusted Main Design Air Flow Rate [m3/s] | 0.69690 |
| 258 | AirLoopHVAC | SPLIT MS1 | User Heating Air Flow Ratio [] | 1.00000 |
| 259 | AirLoopHVAC | SPLIT MS1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 260 | AirLoopHVAC | SPLIT MS2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.69508 |
| 261 | AirLoopHVAC | SPLIT MS2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.69508 |
| 262 | AirLoopHVAC | SPLIT MS2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.69508 |
| 263 | AirLoopHVAC | SPLIT MS2 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.69508 |
| 264 | AirLoopHVAC | SPLIT MS2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.69508 |
| 265 | AirLoopHVAC | SPLIT MS2 | Adjusted Main Design Air Flow Rate [m3/s] | 0.69508 |
| 266 | AirLoopHVAC | SPLIT MS2 | User Heating Air Flow Ratio [] | 1.00000 |
| 267 | AirLoopHVAC | SPLIT MS2 | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 268 | AirLoopHVAC | SPLIT TSW | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.47767 |
| 269 | AirLoopHVAC | SPLIT TSW | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.47767 |
| 270 | AirLoopHVAC | SPLIT TSW | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.47767 |
| 271 | AirLoopHVAC | SPLIT TSW | Adjusted Heating Design Air Flow Rate [m3/s] | 0.47767 |
| 272 | AirLoopHVAC | SPLIT TSW | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.47767 |
| 273 | AirLoopHVAC | SPLIT TSW | Adjusted Main Design Air Flow Rate [m3/s] | 0.47767 |
| 274 | AirLoopHVAC | SPLIT TSW | User Heating Air Flow Ratio [] | 1.00000 |
| 275 | AirLoopHVAC | SPLIT TSW | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 276 | AirLoopHVAC | SPLIT TNW | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.47099 |
| 277 | AirLoopHVAC | SPLIT TNW | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.47099 |
| 278 | AirLoopHVAC | SPLIT TNW | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.47099 |
| 279 | AirLoopHVAC | SPLIT TNW | Adjusted Heating Design Air Flow Rate [m3/s] | 0.47099 |
| 280 | AirLoopHVAC | SPLIT TNW | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.47099 |
| 281 | AirLoopHVAC | SPLIT TNW | Adjusted Main Design Air Flow Rate [m3/s] | 0.47099 |
| 282 | AirLoopHVAC | SPLIT TNW | User Heating Air Flow Ratio [] | 1.00000 |
| 283 | AirLoopHVAC | SPLIT TNW | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 284 | AirLoopHVAC | SPLIT TSE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.40258 |
| 285 | AirLoopHVAC | SPLIT TSE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.40258 |
| 286 | AirLoopHVAC | SPLIT TSE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.40258 |
| 287 | AirLoopHVAC | SPLIT TSE | Adjusted Heating Design Air Flow Rate [m3/s] | 0.40258 |
| 288 | AirLoopHVAC | SPLIT TSE | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.40258 |
| 289 | AirLoopHVAC | SPLIT TSE | Adjusted Main Design Air Flow Rate [m3/s] | 0.40258 |
| 290 | AirLoopHVAC | SPLIT TSE | User Heating Air Flow Ratio [] | 1.00000 |
| 291 | AirLoopHVAC | SPLIT TSE | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 292 | AirLoopHVAC | SPLIT TNE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.39584 |
| 293 | AirLoopHVAC | SPLIT TNE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.39584 |
| 294 | AirLoopHVAC | SPLIT TNE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.39584 |
| 295 | AirLoopHVAC | SPLIT TNE | Adjusted Heating Design Air Flow Rate [m3/s] | 0.39584 |
| 296 | AirLoopHVAC | SPLIT TNE | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.39584 |
| 297 | AirLoopHVAC | SPLIT TNE | Adjusted Main Design Air Flow Rate [m3/s] | 0.39584 |
| 298 | AirLoopHVAC | SPLIT TNE | User Heating Air Flow Ratio [] | 1.00000 |
| 299 | AirLoopHVAC | SPLIT TNE | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 300 | AirLoopHVAC | SPLIT TN1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.37187 |
| 301 | AirLoopHVAC | SPLIT TN1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.37187 |
| 302 | AirLoopHVAC | SPLIT TN1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.37187 |
| 303 | AirLoopHVAC | SPLIT TN1 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.37187 |
| 304 | AirLoopHVAC | SPLIT TN1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.37187 |
| 305 | AirLoopHVAC | SPLIT TN1 | Adjusted Main Design Air Flow Rate [m3/s] | 0.37187 |
| 306 | AirLoopHVAC | SPLIT TN1 | User Heating Air Flow Ratio [] | 1.00000 |
| 307 | AirLoopHVAC | SPLIT TN1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 308 | AirLoopHVAC | SPLIT TN2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.36953 |
| 309 | AirLoopHVAC | SPLIT TN2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.36953 |
| 310 | AirLoopHVAC | SPLIT TN2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.36953 |
| 311 | AirLoopHVAC | SPLIT TN2 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.36953 |
| 312 | AirLoopHVAC | SPLIT TN2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.36953 |
| 313 | AirLoopHVAC | SPLIT TN2 | Adjusted Main Design Air Flow Rate [m3/s] | 0.36953 |
| 314 | AirLoopHVAC | SPLIT TN2 | User Heating Air Flow Ratio [] | 1.00000 |
| 315 | AirLoopHVAC | SPLIT TN2 | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 316 | AirLoopHVAC | SPLIT TS1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.38014 |
| 317 | AirLoopHVAC | SPLIT TS1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.38014 |
| 318 | AirLoopHVAC | SPLIT TS1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.38014 |
| 319 | AirLoopHVAC | SPLIT TS1 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.38014 |
| 320 | AirLoopHVAC | SPLIT TS1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.38014 |
| 321 | AirLoopHVAC | SPLIT TS1 | Adjusted Main Design Air Flow Rate [m3/s] | 0.38014 |
| 322 | AirLoopHVAC | SPLIT TS1 | User Heating Air Flow Ratio [] | 1.00000 |
| 323 | AirLoopHVAC | SPLIT TS1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 324 | AirLoopHVAC | SPLIT TS2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.37782 |
| 325 | AirLoopHVAC | SPLIT TS2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.37782 |
| 326 | AirLoopHVAC | SPLIT TS2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.37782 |
| 327 | AirLoopHVAC | SPLIT TS2 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.37782 |
| 328 | AirLoopHVAC | SPLIT TS2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.37782 |
| 329 | AirLoopHVAC | SPLIT TS2 | Adjusted Main Design Air Flow Rate [m3/s] | 0.37782 |
| 330 | AirLoopHVAC | SPLIT TS2 | User Heating Air Flow Ratio [] | 1.00000 |
| 331 | AirLoopHVAC | SPLIT TS2 | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 332 | AirLoopHVAC | SPLIT GSW | Design Supply Air Flow Rate [m3/s] | 0.34292 |
| 333 | AirLoopHVAC | SPLIT GNW | Design Supply Air Flow Rate [m3/s] | 0.32217 |
| 334 | AirLoopHVAC | SPLIT OFFICE | Design Supply Air Flow Rate [m3/s] | 0.38036 |
| 335 | AirLoopHVAC | SPLIT GNE | Design Supply Air Flow Rate [m3/s] | 0.28741 |
| 336 | AirLoopHVAC | SPLIT GN1 | Design Supply Air Flow Rate [m3/s] | 0.26302 |
| 337 | AirLoopHVAC | SPLIT GN2 | Design Supply Air Flow Rate [m3/s] | 0.26240 |
| 338 | AirLoopHVAC | SPLIT GS1 | Design Supply Air Flow Rate [m3/s] | 0.28584 |
| 339 | AirLoopHVAC | SPLIT GS2 | Design Supply Air Flow Rate [m3/s] | 0.28767 |
| 340 | AirLoopHVAC | SPLIT MSW | Design Supply Air Flow Rate [m3/s] | 0.86881 |
| 341 | AirLoopHVAC | SPLIT MNW | Design Supply Air Flow Rate [m3/s] | 0.83649 |
| 342 | AirLoopHVAC | SPLIT MSE | Design Supply Air Flow Rate [m3/s] | 0.76518 |
| 343 | AirLoopHVAC | SPLIT MNE | Design Supply Air Flow Rate [m3/s] | 0.73378 |
| 344 | AirLoopHVAC | SPLIT MN1 | Design Supply Air Flow Rate [m3/s] | 0.65919 |
| 345 | AirLoopHVAC | SPLIT MN2 | Design Supply Air Flow Rate [m3/s] | 0.65748 |
| 346 | AirLoopHVAC | SPLIT MS1 | Design Supply Air Flow Rate [m3/s] | 0.69690 |
| 347 | AirLoopHVAC | SPLIT MS2 | Design Supply Air Flow Rate [m3/s] | 0.69508 |
| 348 | AirLoopHVAC | SPLIT TSW | Design Supply Air Flow Rate [m3/s] | 0.47767 |
| 349 | AirLoopHVAC | SPLIT TNW | Design Supply Air Flow Rate [m3/s] | 0.47099 |
| 350 | AirLoopHVAC | SPLIT TSE | Design Supply Air Flow Rate [m3/s] | 0.40258 |
| 351 | AirLoopHVAC | SPLIT TNE | Design Supply Air Flow Rate [m3/s] | 0.39584 |
| 352 | AirLoopHVAC | SPLIT TN1 | Design Supply Air Flow Rate [m3/s] | 0.37187 |
| 353 | AirLoopHVAC | SPLIT TN2 | Design Supply Air Flow Rate [m3/s] | 0.36953 |
| 354 | AirLoopHVAC | SPLIT TS1 | Design Supply Air Flow Rate [m3/s] | 0.38014 |
| 355 | AirLoopHVAC | SPLIT TS2 | Design Supply Air Flow Rate [m3/s] | 0.37782 |
| 356 | Controller:OutdoorAir | SPLIT GSW_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.34292 |
| 357 | Controller:OutdoorAir | SPLIT GSW_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.59546E-002 |
| 358 | AirLoopHVAC:UnitarySystem | SPLIT GSW_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.34292 |
| 359 | AirLoopHVAC:UnitarySystem | SPLIT GSW_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.34292 |
| 360 | AirLoopHVAC:UnitarySystem | SPLIT GSW_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.34292 |
| 361 | AirLoopHVAC:UnitarySystem | SPLIT GSW_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.34292 |
| 362 | AirLoopHVAC:UnitarySystem | SPLIT GSW_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 5716.91760 |
| 363 | AirLoopHVAC:UnitarySystem | SPLIT GSW_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 8790.72433 |
| 364 | AirLoopHVAC:UnitarySystem | SPLIT GSW_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 365 | AirLoopHVAC:UnitarySystem | SPLIT GSW_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 366 | Fan:OnOff | SPLIT GSW SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.34292 |
| 367 | Coil:Cooling:DX:SingleSpeed | SPLIT GSW COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.34292 |
| 368 | Coil:Cooling:DX:SingleSpeed | SPLIT GSW COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 5716.91760 |
| 369 | Coil:Cooling:DX:SingleSpeed | SPLIT GSW COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80006 |
| 370 | Coil:Heating:Fuel | SPLIT GSW HEATING COIL | Design Size Nominal Capacity [W] | 8790.72433 |
| 371 | Controller:OutdoorAir | SPLIT GNW_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.32217 |
| 372 | Controller:OutdoorAir | SPLIT GNW_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.59546E-002 |
| 373 | AirLoopHVAC:UnitarySystem | SPLIT GNW_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.32217 |
| 374 | AirLoopHVAC:UnitarySystem | SPLIT GNW_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.32217 |
| 375 | AirLoopHVAC:UnitarySystem | SPLIT GNW_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.32217 |
| 376 | AirLoopHVAC:UnitarySystem | SPLIT GNW_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.32217 |
| 377 | AirLoopHVAC:UnitarySystem | SPLIT GNW_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 5396.96646 |
| 378 | AirLoopHVAC:UnitarySystem | SPLIT GNW_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 8328.05342 |
| 379 | AirLoopHVAC:UnitarySystem | SPLIT GNW_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 380 | AirLoopHVAC:UnitarySystem | SPLIT GNW_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 381 | Fan:OnOff | SPLIT GNW SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.32217 |
| 382 | Coil:Cooling:DX:SingleSpeed | SPLIT GNW COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.32217 |
| 383 | Coil:Cooling:DX:SingleSpeed | SPLIT GNW COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 5396.96646 |
| 384 | Coil:Cooling:DX:SingleSpeed | SPLIT GNW COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80030 |
| 385 | Coil:Heating:Fuel | SPLIT GNW HEATING COIL | Design Size Nominal Capacity [W] | 8328.05342 |
| 386 | Controller:OutdoorAir | SPLIT OFFICE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.38036 |
| 387 | Controller:OutdoorAir | SPLIT OFFICE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 3.81060E-002 |
| 388 | AirLoopHVAC:UnitarySystem | SPLIT OFFICE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.38036 |
| 389 | AirLoopHVAC:UnitarySystem | SPLIT OFFICE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.38036 |
| 390 | AirLoopHVAC:UnitarySystem | SPLIT OFFICE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.38036 |
| 391 | AirLoopHVAC:UnitarySystem | SPLIT OFFICE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.38036 |
| 392 | AirLoopHVAC:UnitarySystem | SPLIT OFFICE_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 6296.22776 |
| 393 | AirLoopHVAC:UnitarySystem | SPLIT OFFICE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 10161.51236 |
| 394 | AirLoopHVAC:UnitarySystem | SPLIT OFFICE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 395 | AirLoopHVAC:UnitarySystem | SPLIT OFFICE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 396 | Fan:OnOff | SPLIT OFFICE SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.38036 |
| 397 | Coil:Cooling:DX:SingleSpeed | SPLIT OFFICE COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.38036 |
| 398 | Coil:Cooling:DX:SingleSpeed | SPLIT OFFICE COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 6296.22776 |
| 399 | Coil:Cooling:DX:SingleSpeed | SPLIT OFFICE COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
| 400 | Coil:Heating:Fuel | SPLIT OFFICE HEATING COIL | Design Size Nominal Capacity [W] | 10161.51236 |
| 401 | Controller:OutdoorAir | SPLIT GNE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.28741 |
| 402 | Controller:OutdoorAir | SPLIT GNE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.59546E-002 |
| 403 | AirLoopHVAC:UnitarySystem | SPLIT GNE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.28741 |
| 404 | AirLoopHVAC:UnitarySystem | SPLIT GNE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.28741 |
| 405 | AirLoopHVAC:UnitarySystem | SPLIT GNE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.28741 |
| 406 | AirLoopHVAC:UnitarySystem | SPLIT GNE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.28741 |
| 407 | AirLoopHVAC:UnitarySystem | SPLIT GNE_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 4899.83433 |
| 408 | AirLoopHVAC:UnitarySystem | SPLIT GNE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 7553.01871 |
| 409 | AirLoopHVAC:UnitarySystem | SPLIT GNE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 410 | AirLoopHVAC:UnitarySystem | SPLIT GNE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 411 | Fan:OnOff | SPLIT GNE SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.28741 |
| 412 | Coil:Cooling:DX:SingleSpeed | SPLIT GNE COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.28741 |
| 413 | Coil:Cooling:DX:SingleSpeed | SPLIT GNE COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 4899.83433 |
| 414 | Coil:Cooling:DX:SingleSpeed | SPLIT GNE COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80098 |
| 415 | Coil:Heating:Fuel | SPLIT GNE HEATING COIL | Design Size Nominal Capacity [W] | 7553.01871 |
| 416 | Controller:OutdoorAir | SPLIT GN1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.26302 |
| 417 | Controller:OutdoorAir | SPLIT GN1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.59546E-002 |
| 418 | AirLoopHVAC:UnitarySystem | SPLIT GN1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.26302 |
| 419 | AirLoopHVAC:UnitarySystem | SPLIT GN1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.26302 |
| 420 | AirLoopHVAC:UnitarySystem | SPLIT GN1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.26302 |
| 421 | AirLoopHVAC:UnitarySystem | SPLIT GN1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.26302 |
| 422 | AirLoopHVAC:UnitarySystem | SPLIT GN1_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 4486.35064 |
| 423 | AirLoopHVAC:UnitarySystem | SPLIT GN1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 7009.27794 |
| 424 | AirLoopHVAC:UnitarySystem | SPLIT GN1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 425 | AirLoopHVAC:UnitarySystem | SPLIT GN1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 426 | Fan:OnOff | SPLIT GN1 SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.26302 |
| 427 | Coil:Cooling:DX:SingleSpeed | SPLIT GN1 COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.26302 |
| 428 | Coil:Cooling:DX:SingleSpeed | SPLIT GN1 COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 4486.35064 |
| 429 | Coil:Cooling:DX:SingleSpeed | SPLIT GN1 COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80081 |
| 430 | Coil:Heating:Fuel | SPLIT GN1 HEATING COIL | Design Size Nominal Capacity [W] | 7009.27794 |
| 431 | Controller:OutdoorAir | SPLIT GN2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.26240 |
| 432 | Controller:OutdoorAir | SPLIT GN2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.59546E-002 |
| 433 | AirLoopHVAC:UnitarySystem | SPLIT GN2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.26240 |
| 434 | AirLoopHVAC:UnitarySystem | SPLIT GN2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.26240 |
| 435 | AirLoopHVAC:UnitarySystem | SPLIT GN2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.26240 |
| 436 | AirLoopHVAC:UnitarySystem | SPLIT GN2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.26240 |
| 437 | AirLoopHVAC:UnitarySystem | SPLIT GN2_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 4477.26845 |
| 438 | AirLoopHVAC:UnitarySystem | SPLIT GN2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 6995.41835 |
| 439 | AirLoopHVAC:UnitarySystem | SPLIT GN2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 440 | AirLoopHVAC:UnitarySystem | SPLIT GN2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 441 | Fan:OnOff | SPLIT GN2 SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.26240 |
| 442 | Coil:Cooling:DX:SingleSpeed | SPLIT GN2 COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.26240 |
| 443 | Coil:Cooling:DX:SingleSpeed | SPLIT GN2 COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 4477.26845 |
| 444 | Coil:Cooling:DX:SingleSpeed | SPLIT GN2 COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80069 |
| 445 | Coil:Heating:Fuel | SPLIT GN2 HEATING COIL | Design Size Nominal Capacity [W] | 6995.41835 |
| 446 | Controller:OutdoorAir | SPLIT GS1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.28584 |
| 447 | Controller:OutdoorAir | SPLIT GS1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.59546E-002 |
| 448 | AirLoopHVAC:UnitarySystem | SPLIT GS1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.28584 |
| 449 | AirLoopHVAC:UnitarySystem | SPLIT GS1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.28584 |
| 450 | AirLoopHVAC:UnitarySystem | SPLIT GS1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.28584 |
| 451 | AirLoopHVAC:UnitarySystem | SPLIT GS1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.28584 |
| 452 | AirLoopHVAC:UnitarySystem | SPLIT GS1_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 4842.71375 |
| 453 | AirLoopHVAC:UnitarySystem | SPLIT GS1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 7517.99033 |
| 454 | AirLoopHVAC:UnitarySystem | SPLIT GS1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 455 | AirLoopHVAC:UnitarySystem | SPLIT GS1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 456 | Fan:OnOff | SPLIT GS1 SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.28584 |
| 457 | Coil:Cooling:DX:SingleSpeed | SPLIT GS1 COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.28584 |
| 458 | Coil:Cooling:DX:SingleSpeed | SPLIT GS1 COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 4842.71375 |
| 459 | Coil:Cooling:DX:SingleSpeed | SPLIT GS1 COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80022 |
| 460 | Coil:Heating:Fuel | SPLIT GS1 HEATING COIL | Design Size Nominal Capacity [W] | 7517.99033 |
| 461 | Controller:OutdoorAir | SPLIT GS2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.28767 |
| 462 | Controller:OutdoorAir | SPLIT GS2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.59546E-002 |
| 463 | AirLoopHVAC:UnitarySystem | SPLIT GS2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.28767 |
| 464 | AirLoopHVAC:UnitarySystem | SPLIT GS2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.28767 |
| 465 | AirLoopHVAC:UnitarySystem | SPLIT GS2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.28767 |
| 466 | AirLoopHVAC:UnitarySystem | SPLIT GS2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.28767 |
| 467 | AirLoopHVAC:UnitarySystem | SPLIT GS2_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 4869.88883 |
| 468 | AirLoopHVAC:UnitarySystem | SPLIT GS2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 7558.74776 |
| 469 | AirLoopHVAC:UnitarySystem | SPLIT GS2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 470 | AirLoopHVAC:UnitarySystem | SPLIT GS2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 471 | Fan:OnOff | SPLIT GS2 SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.28767 |
| 472 | Coil:Cooling:DX:SingleSpeed | SPLIT GS2 COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.28767 |
| 473 | Coil:Cooling:DX:SingleSpeed | SPLIT GS2 COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 4869.88883 |
| 474 | Coil:Cooling:DX:SingleSpeed | SPLIT GS2 COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80050 |
| 475 | Coil:Heating:Fuel | SPLIT GS2 HEATING COIL | Design Size Nominal Capacity [W] | 7558.74776 |
| 476 | Controller:OutdoorAir | SPLIT MSW_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.86881 |
| 477 | Controller:OutdoorAir | SPLIT MSW_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 5.19091E-002 |
| 478 | AirLoopHVAC:UnitarySystem | SPLIT MSW_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.86881 |
| 479 | AirLoopHVAC:UnitarySystem | SPLIT MSW_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.86881 |
| 480 | AirLoopHVAC:UnitarySystem | SPLIT MSW_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.86881 |
| 481 | AirLoopHVAC:UnitarySystem | SPLIT MSW_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.86881 |
| 482 | AirLoopHVAC:UnitarySystem | SPLIT MSW_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 14381.85519 |
| 483 | AirLoopHVAC:UnitarySystem | SPLIT MSW_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 21662.34149 |
| 484 | AirLoopHVAC:UnitarySystem | SPLIT MSW_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 485 | AirLoopHVAC:UnitarySystem | SPLIT MSW_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 486 | Fan:OnOff | SPLIT MSW SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.86881 |
| 487 | Coil:Cooling:DX:SingleSpeed | SPLIT MSW COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.86881 |
| 488 | Coil:Cooling:DX:SingleSpeed | SPLIT MSW COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 14381.85519 |
| 489 | Coil:Cooling:DX:SingleSpeed | SPLIT MSW COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
| 490 | Coil:Heating:Fuel | SPLIT MSW HEATING COIL | Design Size Nominal Capacity [W] | 21662.34149 |
| 491 | Controller:OutdoorAir | SPLIT MNW_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.83649 |
| 492 | Controller:OutdoorAir | SPLIT MNW_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 5.19091E-002 |
| 493 | AirLoopHVAC:UnitarySystem | SPLIT MNW_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.83649 |
| 494 | AirLoopHVAC:UnitarySystem | SPLIT MNW_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.83649 |
| 495 | AirLoopHVAC:UnitarySystem | SPLIT MNW_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.83649 |
| 496 | AirLoopHVAC:UnitarySystem | SPLIT MNW_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.83649 |
| 497 | AirLoopHVAC:UnitarySystem | SPLIT MNW_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 13846.92613 |
| 498 | AirLoopHVAC:UnitarySystem | SPLIT MNW_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 20941.52103 |
| 499 | AirLoopHVAC:UnitarySystem | SPLIT MNW_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 500 | AirLoopHVAC:UnitarySystem | SPLIT MNW_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 501 | Fan:OnOff | SPLIT MNW SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.83649 |
| 502 | Coil:Cooling:DX:SingleSpeed | SPLIT MNW COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.83649 |
| 503 | Coil:Cooling:DX:SingleSpeed | SPLIT MNW COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 13846.92613 |
| 504 | Coil:Cooling:DX:SingleSpeed | SPLIT MNW COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
| 505 | Coil:Heating:Fuel | SPLIT MNW HEATING COIL | Design Size Nominal Capacity [W] | 20941.52103 |
| 506 | Controller:OutdoorAir | SPLIT MSE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.76518 |
| 507 | Controller:OutdoorAir | SPLIT MSE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 5.19091E-002 |
| 508 | AirLoopHVAC:UnitarySystem | SPLIT MSE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.76518 |
| 509 | AirLoopHVAC:UnitarySystem | SPLIT MSE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.76518 |
| 510 | AirLoopHVAC:UnitarySystem | SPLIT MSE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.76518 |
| 511 | AirLoopHVAC:UnitarySystem | SPLIT MSE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.76518 |
| 512 | AirLoopHVAC:UnitarySystem | SPLIT MSE_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 12729.01621 |
| 513 | AirLoopHVAC:UnitarySystem | SPLIT MSE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 19351.64060 |
| 514 | AirLoopHVAC:UnitarySystem | SPLIT MSE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 515 | AirLoopHVAC:UnitarySystem | SPLIT MSE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 516 | Fan:OnOff | SPLIT MSE SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.76518 |
| 517 | Coil:Cooling:DX:SingleSpeed | SPLIT MSE COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.76518 |
| 518 | Coil:Cooling:DX:SingleSpeed | SPLIT MSE COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 12729.01621 |
| 519 | Coil:Cooling:DX:SingleSpeed | SPLIT MSE COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80085 |
| 520 | Coil:Heating:Fuel | SPLIT MSE HEATING COIL | Design Size Nominal Capacity [W] | 19351.64060 |
| 521 | Controller:OutdoorAir | SPLIT MNE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.73378 |
| 522 | Controller:OutdoorAir | SPLIT MNE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 5.19091E-002 |
| 523 | AirLoopHVAC:UnitarySystem | SPLIT MNE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.73378 |
| 524 | AirLoopHVAC:UnitarySystem | SPLIT MNE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.73378 |
| 525 | AirLoopHVAC:UnitarySystem | SPLIT MNE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.73378 |
| 526 | AirLoopHVAC:UnitarySystem | SPLIT MNE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.73378 |
| 527 | AirLoopHVAC:UnitarySystem | SPLIT MNE_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 12243.99547 |
| 528 | AirLoopHVAC:UnitarySystem | SPLIT MNE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 18651.26930 |
| 529 | AirLoopHVAC:UnitarySystem | SPLIT MNE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 530 | AirLoopHVAC:UnitarySystem | SPLIT MNE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 531 | Fan:OnOff | SPLIT MNE SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.73378 |
| 532 | Coil:Cooling:DX:SingleSpeed | SPLIT MNE COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.73378 |
| 533 | Coil:Cooling:DX:SingleSpeed | SPLIT MNE COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 12243.99547 |
| 534 | Coil:Cooling:DX:SingleSpeed | SPLIT MNE COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80073 |
| 535 | Coil:Heating:Fuel | SPLIT MNE HEATING COIL | Design Size Nominal Capacity [W] | 18651.26930 |
| 536 | Controller:OutdoorAir | SPLIT MN1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.65919 |
| 537 | Controller:OutdoorAir | SPLIT MN1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 5.19091E-002 |
| 538 | AirLoopHVAC:UnitarySystem | SPLIT MN1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.65919 |
| 539 | AirLoopHVAC:UnitarySystem | SPLIT MN1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.65919 |
| 540 | AirLoopHVAC:UnitarySystem | SPLIT MN1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.65919 |
| 541 | AirLoopHVAC:UnitarySystem | SPLIT MN1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.65919 |
| 542 | AirLoopHVAC:UnitarySystem | SPLIT MN1_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 10993.52545 |
| 543 | AirLoopHVAC:UnitarySystem | SPLIT MN1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 16987.62486 |
| 544 | AirLoopHVAC:UnitarySystem | SPLIT MN1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 545 | AirLoopHVAC:UnitarySystem | SPLIT MN1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 546 | Fan:OnOff | SPLIT MN1 SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.65919 |
| 547 | Coil:Cooling:DX:SingleSpeed | SPLIT MN1 COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.65919 |
| 548 | Coil:Cooling:DX:SingleSpeed | SPLIT MN1 COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 10993.52545 |
| 549 | Coil:Cooling:DX:SingleSpeed | SPLIT MN1 COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80093 |
| 550 | Coil:Heating:Fuel | SPLIT MN1 HEATING COIL | Design Size Nominal Capacity [W] | 16987.62486 |
| 551 | Controller:OutdoorAir | SPLIT MN2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.65748 |
| 552 | Controller:OutdoorAir | SPLIT MN2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 5.19091E-002 |
| 553 | AirLoopHVAC:UnitarySystem | SPLIT MN2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.65748 |
| 554 | AirLoopHVAC:UnitarySystem | SPLIT MN2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.65748 |
| 555 | AirLoopHVAC:UnitarySystem | SPLIT MN2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.65748 |
| 556 | AirLoopHVAC:UnitarySystem | SPLIT MN2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.65748 |
| 557 | AirLoopHVAC:UnitarySystem | SPLIT MN2_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 10968.71285 |
| 558 | AirLoopHVAC:UnitarySystem | SPLIT MN2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 16949.42150 |
| 559 | AirLoopHVAC:UnitarySystem | SPLIT MN2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 560 | AirLoopHVAC:UnitarySystem | SPLIT MN2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 561 | Fan:OnOff | SPLIT MN2 SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.65748 |
| 562 | Coil:Cooling:DX:SingleSpeed | SPLIT MN2 COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.65748 |
| 563 | Coil:Cooling:DX:SingleSpeed | SPLIT MN2 COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 10968.71285 |
| 564 | Coil:Cooling:DX:SingleSpeed | SPLIT MN2 COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80080 |
| 565 | Coil:Heating:Fuel | SPLIT MN2 HEATING COIL | Design Size Nominal Capacity [W] | 16949.42150 |
| 566 | Controller:OutdoorAir | SPLIT MS1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.69690 |
| 567 | Controller:OutdoorAir | SPLIT MS1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 5.19091E-002 |
| 568 | AirLoopHVAC:UnitarySystem | SPLIT MS1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.69690 |
| 569 | AirLoopHVAC:UnitarySystem | SPLIT MS1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.69690 |
| 570 | AirLoopHVAC:UnitarySystem | SPLIT MS1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.69690 |
| 571 | AirLoopHVAC:UnitarySystem | SPLIT MS1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.69690 |
| 572 | AirLoopHVAC:UnitarySystem | SPLIT MS1_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 11571.11765 |
| 573 | AirLoopHVAC:UnitarySystem | SPLIT MS1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 17828.67979 |
| 574 | AirLoopHVAC:UnitarySystem | SPLIT MS1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 575 | AirLoopHVAC:UnitarySystem | SPLIT MS1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 576 | Fan:OnOff | SPLIT MS1 SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.69690 |
| 577 | Coil:Cooling:DX:SingleSpeed | SPLIT MS1 COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.69690 |
| 578 | Coil:Cooling:DX:SingleSpeed | SPLIT MS1 COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 11571.11765 |
| 579 | Coil:Cooling:DX:SingleSpeed | SPLIT MS1 COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80055 |
| 580 | Coil:Heating:Fuel | SPLIT MS1 HEATING COIL | Design Size Nominal Capacity [W] | 17828.67979 |
| 581 | Controller:OutdoorAir | SPLIT MS2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.69508 |
| 582 | Controller:OutdoorAir | SPLIT MS2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 5.19091E-002 |
| 583 | AirLoopHVAC:UnitarySystem | SPLIT MS2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.69508 |
| 584 | AirLoopHVAC:UnitarySystem | SPLIT MS2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.69508 |
| 585 | AirLoopHVAC:UnitarySystem | SPLIT MS2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.69508 |
| 586 | AirLoopHVAC:UnitarySystem | SPLIT MS2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.69508 |
| 587 | AirLoopHVAC:UnitarySystem | SPLIT MS2_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 11544.94685 |
| 588 | AirLoopHVAC:UnitarySystem | SPLIT MS2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 17787.98109 |
| 589 | AirLoopHVAC:UnitarySystem | SPLIT MS2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 590 | AirLoopHVAC:UnitarySystem | SPLIT MS2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 591 | Fan:OnOff | SPLIT MS2 SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.69508 |
| 592 | Coil:Cooling:DX:SingleSpeed | SPLIT MS2 COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.69508 |
| 593 | Coil:Cooling:DX:SingleSpeed | SPLIT MS2 COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 11544.94685 |
| 594 | Coil:Cooling:DX:SingleSpeed | SPLIT MS2 COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80042 |
| 595 | Coil:Heating:Fuel | SPLIT MS2 HEATING COIL | Design Size Nominal Capacity [W] | 17787.98109 |
| 596 | Controller:OutdoorAir | SPLIT TSW_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.47767 |
| 597 | Controller:OutdoorAir | SPLIT TSW_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.59546E-002 |
| 598 | AirLoopHVAC:UnitarySystem | SPLIT TSW_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.47767 |
| 599 | AirLoopHVAC:UnitarySystem | SPLIT TSW_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.47767 |
| 600 | AirLoopHVAC:UnitarySystem | SPLIT TSW_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.47767 |
| 601 | AirLoopHVAC:UnitarySystem | SPLIT TSW_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.47767 |
| 602 | AirLoopHVAC:UnitarySystem | SPLIT TSW_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 7907.05439 |
| 603 | AirLoopHVAC:UnitarySystem | SPLIT TSW_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 11796.21281 |
| 604 | AirLoopHVAC:UnitarySystem | SPLIT TSW_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 605 | AirLoopHVAC:UnitarySystem | SPLIT TSW_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 606 | Fan:OnOff | SPLIT TSW SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.47767 |
| 607 | Coil:Cooling:DX:SingleSpeed | SPLIT TSW COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.47767 |
| 608 | Coil:Cooling:DX:SingleSpeed | SPLIT TSW COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 7907.05439 |
| 609 | Coil:Cooling:DX:SingleSpeed | SPLIT TSW COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
| 610 | Coil:Heating:Fuel | SPLIT TSW HEATING COIL | Design Size Nominal Capacity [W] | 11796.21281 |
| 611 | Controller:OutdoorAir | SPLIT TNW_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.47099 |
| 612 | Controller:OutdoorAir | SPLIT TNW_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.59546E-002 |
| 613 | AirLoopHVAC:UnitarySystem | SPLIT TNW_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.47099 |
| 614 | AirLoopHVAC:UnitarySystem | SPLIT TNW_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.47099 |
| 615 | AirLoopHVAC:UnitarySystem | SPLIT TNW_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.47099 |
| 616 | AirLoopHVAC:UnitarySystem | SPLIT TNW_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.47099 |
| 617 | AirLoopHVAC:UnitarySystem | SPLIT TNW_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 7796.61065 |
| 618 | AirLoopHVAC:UnitarySystem | SPLIT TNW_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 11647.28094 |
| 619 | AirLoopHVAC:UnitarySystem | SPLIT TNW_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 620 | AirLoopHVAC:UnitarySystem | SPLIT TNW_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 621 | Fan:OnOff | SPLIT TNW SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.47099 |
| 622 | Coil:Cooling:DX:SingleSpeed | SPLIT TNW COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.47099 |
| 623 | Coil:Cooling:DX:SingleSpeed | SPLIT TNW COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 7796.61065 |
| 624 | Coil:Cooling:DX:SingleSpeed | SPLIT TNW COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
| 625 | Coil:Heating:Fuel | SPLIT TNW HEATING COIL | Design Size Nominal Capacity [W] | 11647.28094 |
| 626 | Controller:OutdoorAir | SPLIT TSE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.40258 |
| 627 | Controller:OutdoorAir | SPLIT TSE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.59546E-002 |
| 628 | AirLoopHVAC:UnitarySystem | SPLIT TSE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.40258 |
| 629 | AirLoopHVAC:UnitarySystem | SPLIT TSE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.40258 |
| 630 | AirLoopHVAC:UnitarySystem | SPLIT TSE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.40258 |
| 631 | AirLoopHVAC:UnitarySystem | SPLIT TSE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.40258 |
| 632 | AirLoopHVAC:UnitarySystem | SPLIT TSE_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 6719.99422 |
| 633 | AirLoopHVAC:UnitarySystem | SPLIT TSE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 10121.91493 |
| 634 | AirLoopHVAC:UnitarySystem | SPLIT TSE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 635 | AirLoopHVAC:UnitarySystem | SPLIT TSE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 636 | Fan:OnOff | SPLIT TSE SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.40258 |
| 637 | Coil:Cooling:DX:SingleSpeed | SPLIT TSE COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.40258 |
| 638 | Coil:Cooling:DX:SingleSpeed | SPLIT TSE COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 6719.99422 |
| 639 | Coil:Cooling:DX:SingleSpeed | SPLIT TSE COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80060 |
| 640 | Coil:Heating:Fuel | SPLIT TSE HEATING COIL | Design Size Nominal Capacity [W] | 10121.91493 |
| 641 | Controller:OutdoorAir | SPLIT TNE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.39584 |
| 642 | Controller:OutdoorAir | SPLIT TNE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.59546E-002 |
| 643 | AirLoopHVAC:UnitarySystem | SPLIT TNE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.39584 |
| 644 | AirLoopHVAC:UnitarySystem | SPLIT TNE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.39584 |
| 645 | AirLoopHVAC:UnitarySystem | SPLIT TNE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.39584 |
| 646 | AirLoopHVAC:UnitarySystem | SPLIT TNE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.39584 |
| 647 | AirLoopHVAC:UnitarySystem | SPLIT TNE_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 6606.84131 |
| 648 | AirLoopHVAC:UnitarySystem | SPLIT TNE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 9971.47748 |
| 649 | AirLoopHVAC:UnitarySystem | SPLIT TNE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 650 | AirLoopHVAC:UnitarySystem | SPLIT TNE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 651 | Fan:OnOff | SPLIT TNE SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.39584 |
| 652 | Coil:Cooling:DX:SingleSpeed | SPLIT TNE COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.39584 |
| 653 | Coil:Cooling:DX:SingleSpeed | SPLIT TNE COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 6606.84131 |
| 654 | Coil:Cooling:DX:SingleSpeed | SPLIT TNE COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80063 |
| 655 | Coil:Heating:Fuel | SPLIT TNE HEATING COIL | Design Size Nominal Capacity [W] | 9971.47748 |
| 656 | Controller:OutdoorAir | SPLIT TN1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.37187 |
| 657 | Controller:OutdoorAir | SPLIT TN1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.59546E-002 |
| 658 | AirLoopHVAC:UnitarySystem | SPLIT TN1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.37187 |
| 659 | AirLoopHVAC:UnitarySystem | SPLIT TN1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.37187 |
| 660 | AirLoopHVAC:UnitarySystem | SPLIT TN1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.37187 |
| 661 | AirLoopHVAC:UnitarySystem | SPLIT TN1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.37187 |
| 662 | AirLoopHVAC:UnitarySystem | SPLIT TN1_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 6155.71011 |
| 663 | AirLoopHVAC:UnitarySystem | SPLIT TN1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 9436.47577 |
| 664 | AirLoopHVAC:UnitarySystem | SPLIT TN1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 665 | AirLoopHVAC:UnitarySystem | SPLIT TN1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 666 | Fan:OnOff | SPLIT TN1 SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.37187 |
| 667 | Coil:Cooling:DX:SingleSpeed | SPLIT TN1 COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.37187 |
| 668 | Coil:Cooling:DX:SingleSpeed | SPLIT TN1 COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 6155.71011 |
| 669 | Coil:Cooling:DX:SingleSpeed | SPLIT TN1 COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
| 670 | Coil:Heating:Fuel | SPLIT TN1 HEATING COIL | Design Size Nominal Capacity [W] | 9436.47577 |
| 671 | Controller:OutdoorAir | SPLIT TN2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.36953 |
| 672 | Controller:OutdoorAir | SPLIT TN2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.59546E-002 |
| 673 | AirLoopHVAC:UnitarySystem | SPLIT TN2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.36953 |
| 674 | AirLoopHVAC:UnitarySystem | SPLIT TN2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.36953 |
| 675 | AirLoopHVAC:UnitarySystem | SPLIT TN2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.36953 |
| 676 | AirLoopHVAC:UnitarySystem | SPLIT TN2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.36953 |
| 677 | AirLoopHVAC:UnitarySystem | SPLIT TN2_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 6117.08782 |
| 678 | AirLoopHVAC:UnitarySystem | SPLIT TN2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 9384.45332 |
| 679 | AirLoopHVAC:UnitarySystem | SPLIT TN2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 680 | AirLoopHVAC:UnitarySystem | SPLIT TN2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 681 | Fan:OnOff | SPLIT TN2 SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.36953 |
| 682 | Coil:Cooling:DX:SingleSpeed | SPLIT TN2 COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.36953 |
| 683 | Coil:Cooling:DX:SingleSpeed | SPLIT TN2 COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 6117.08782 |
| 684 | Coil:Cooling:DX:SingleSpeed | SPLIT TN2 COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
| 685 | Coil:Heating:Fuel | SPLIT TN2 HEATING COIL | Design Size Nominal Capacity [W] | 9384.45332 |
| 686 | Controller:OutdoorAir | SPLIT TS1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.38014 |
| 687 | Controller:OutdoorAir | SPLIT TS1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.59546E-002 |
| 688 | AirLoopHVAC:UnitarySystem | SPLIT TS1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.38014 |
| 689 | AirLoopHVAC:UnitarySystem | SPLIT TS1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.38014 |
| 690 | AirLoopHVAC:UnitarySystem | SPLIT TS1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.38014 |
| 691 | AirLoopHVAC:UnitarySystem | SPLIT TS1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.38014 |
| 692 | AirLoopHVAC:UnitarySystem | SPLIT TS1_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 6292.70571 |
| 693 | AirLoopHVAC:UnitarySystem | SPLIT TS1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 9621.13549 |
| 694 | AirLoopHVAC:UnitarySystem | SPLIT TS1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 695 | AirLoopHVAC:UnitarySystem | SPLIT TS1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 696 | Fan:OnOff | SPLIT TS1 SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.38014 |
| 697 | Coil:Cooling:DX:SingleSpeed | SPLIT TS1 COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.38014 |
| 698 | Coil:Cooling:DX:SingleSpeed | SPLIT TS1 COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 6292.70571 |
| 699 | Coil:Cooling:DX:SingleSpeed | SPLIT TS1 COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
| 700 | Coil:Heating:Fuel | SPLIT TS1 HEATING COIL | Design Size Nominal Capacity [W] | 9621.13549 |
| 701 | Controller:OutdoorAir | SPLIT TS2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.37782 |
| 702 | Controller:OutdoorAir | SPLIT TS2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.59546E-002 |
| 703 | AirLoopHVAC:UnitarySystem | SPLIT TS2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.37782 |
| 704 | AirLoopHVAC:UnitarySystem | SPLIT TS2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.37782 |
| 705 | AirLoopHVAC:UnitarySystem | SPLIT TS2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.37782 |
| 706 | AirLoopHVAC:UnitarySystem | SPLIT TS2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.37782 |
| 707 | AirLoopHVAC:UnitarySystem | SPLIT TS2_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 6254.19616 |
| 708 | AirLoopHVAC:UnitarySystem | SPLIT TS2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 9569.26402 |
| 709 | AirLoopHVAC:UnitarySystem | SPLIT TS2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 710 | AirLoopHVAC:UnitarySystem | SPLIT TS2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 711 | Fan:OnOff | SPLIT TS2 SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.37782 |
| 712 | Coil:Cooling:DX:SingleSpeed | SPLIT TS2 COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.37782 |
| 713 | Coil:Cooling:DX:SingleSpeed | SPLIT TS2 COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 6254.19616 |
| 714 | Coil:Cooling:DX:SingleSpeed | SPLIT TS2 COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
| 715 | Coil:Heating:Fuel | SPLIT TS2 HEATING COIL | Design Size Nominal Capacity [W] | 9569.26402 |
| Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
| 1 | Coil:Cooling:DX:SingleSpeed | SPLIT GSW COOLING COIL | 5448.2 | 3.13 | 10.69 | 11.10 | 10.50 | 10.40 |
| 2 | Coil:Cooling:DX:SingleSpeed | SPLIT GNW COOLING COIL | 5144.4 | 3.13 | 10.70 | 11.12 | 10.52 | 10.41 |
| 3 | Coil:Cooling:DX:SingleSpeed | SPLIT OFFICE COOLING COIL | 5998.1 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 |
| 4 | Coil:Cooling:DX:SingleSpeed | SPLIT GNE COOLING COIL | 4674.5 | 3.15 | 10.73 | 11.16 | 10.55 | 10.47 |
| 5 | Coil:Cooling:DX:SingleSpeed | SPLIT GN1 COOLING COIL | 4280.1 | 3.15 | 10.74 | 11.16 | 10.55 | 10.47 |
| 6 | Coil:Cooling:DX:SingleSpeed | SPLIT GN2 COOLING COIL | 4271.5 | 3.15 | 10.74 | 11.16 | 10.56 | 10.47 |
| 7 | Coil:Cooling:DX:SingleSpeed | SPLIT GS1 COOLING COIL | 4618.6 | 3.14 | 10.72 | 11.14 | 10.54 | 10.45 |
| 8 | Coil:Cooling:DX:SingleSpeed | SPLIT GS2 COOLING COIL | 4644.4 | 3.14 | 10.72 | 11.14 | 10.54 | 10.45 |
| 9 | Coil:Cooling:DX:SingleSpeed | SPLIT MSW COOLING COIL | 13701.0 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 |
| 10 | Coil:Cooling:DX:SingleSpeed | SPLIT MNW COOLING COIL | 13191.4 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 |
| 11 | Coil:Cooling:DX:SingleSpeed | SPLIT MSE COOLING COIL | 12129.3 | 3.13 | 10.68 | 11.10 | 10.50 | 10.39 |
| 12 | Coil:Cooling:DX:SingleSpeed | SPLIT MNE COOLING COIL | 11668.9 | 3.13 | 10.69 | 11.11 | 10.51 | 10.40 |
| 13 | Coil:Cooling:DX:SingleSpeed | SPLIT MN1 COOLING COIL | 10476.9 | 3.13 | 10.69 | 11.11 | 10.51 | 10.40 |
| 14 | Coil:Cooling:DX:SingleSpeed | SPLIT MN2 COOLING COIL | 10453.4 | 3.13 | 10.69 | 11.11 | 10.51 | 10.40 |
| 15 | Coil:Cooling:DX:SingleSpeed | SPLIT MS1 COOLING COIL | 11024.9 | 3.13 | 10.68 | 11.10 | 10.50 | 10.39 |
| 16 | Coil:Cooling:DX:SingleSpeed | SPLIT MS2 COOLING COIL | 11000.2 | 3.13 | 10.68 | 11.10 | 10.50 | 10.39 |
| 17 | Coil:Cooling:DX:SingleSpeed | SPLIT TSW COOLING COIL | 7532.7 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 |
| 18 | Coil:Cooling:DX:SingleSpeed | SPLIT TNW COOLING COIL | 7427.5 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 |
| 19 | Coil:Cooling:DX:SingleSpeed | SPLIT TSE COOLING COIL | 6404.5 | 3.13 | 10.69 | 11.11 | 10.51 | 10.40 |
| 20 | Coil:Cooling:DX:SingleSpeed | SPLIT TNE COOLING COIL | 6296.6 | 3.13 | 10.69 | 11.11 | 10.51 | 10.40 |
| 21 | Coil:Cooling:DX:SingleSpeed | SPLIT TN1 COOLING COIL | 5864.3 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 |
| 22 | Coil:Cooling:DX:SingleSpeed | SPLIT TN2 COOLING COIL | 5827.5 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 |
| 23 | Coil:Cooling:DX:SingleSpeed | SPLIT TS1 COOLING COIL | 5994.8 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 |
| 24 | Coil:Cooling:DX:SingleSpeed | SPLIT TS2 COOLING COIL | 5958.1 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 |
| Zone Name | # Surfaces | |
| 1 | G SW APARTMENT | 9 |
| 2 | G NW APARTMENT | 9 |
| 3 | OFFICE | 9 |
| 4 | G NE APARTMENT | 9 |
| 5 | G N1 APARTMENT | 8 |
| 6 | G N2 APARTMENT | 8 |
| 7 | G S1 APARTMENT | 8 |
| 8 | G S2 APARTMENT | 8 |
| 9 | M SW APARTMENT | 9 |
| 10 | M NW APARTMENT | 9 |
| 11 | M SE APARTMENT | 9 |
| 12 | M NE APARTMENT | 9 |
| 13 | M N1 APARTMENT | 8 |
| 14 | M N2 APARTMENT | 8 |
| 15 | M S1 APARTMENT | 8 |
| 16 | M S2 APARTMENT | 8 |
| 17 | T SW APARTMENT | 9 |
| 18 | T NW APARTMENT | 9 |
| 19 | T SE APARTMENT | 9 |
| 20 | T NE APARTMENT | 9 |
| 21 | T N1 APARTMENT | 8 |
| 22 | T N2 APARTMENT | 8 |
| 23 | T S1 APARTMENT | 8 |
| 24 | T S2 APARTMENT | 8 |
| 25 | T CORRIDOR | 13 |
| 26 | G CORRIDOR | 13 |
| 27 | M CORRIDOR | 13 |
| Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
| 1 | G SWALL SWA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_GRD | 0.752 | 0.676 | 28.24 | 35.30 | 28.24 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 2 | GWINDOW1 S SWA | Window | G SWALL SWA | Window5 Detailed Fenestration | RESWINDOW_U_0.3972_SHGC_0.4 | N/A | 2.257 | No | 7.06 | 7.06 | 7.06 | 180.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 3 | G WWALL SWA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_GRD | 0.752 | 0.676 | 18.58 | 23.22 | 18.58 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 4 | GWINDOW1 W SWA | Window | G WWALL SWA | Window5 Detailed Fenestration | RESWINDOW_U_0.3972_SHGC_0.4 | N/A | 2.257 | No | 4.65 | 4.65 | 4.65 | 270.00 | 90.00 | 3.81 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 5 | G NIWALL SWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-G NIWALL SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 6 | G EIWALL SWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | iz-G EIWALL SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 7 | G GFLOOR SWA | Floor | CTF - ConductionTransferFunction | GGFLOORSWA_FFACTOR | 0.210 | 0.200 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 8 | G CEILIN SWA | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | G CEILIN SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 9 | G INTERNALMASS SWA | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 88.25 | 88.25 | 88.25 | 0.00 | 90.00 | 88.25 | 1.00 | 0.00 | G INTERNALMASS SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 10 | G NWALL NWA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_GRD | 0.752 | 0.676 | 28.24 | 35.30 | 28.24 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 11 | GWINDOW1 N NWA | Window | G NWALL NWA | Window5 Detailed Fenestration | RESWINDOW_U_0.3972_SHGC_0.4 | N/A | 2.257 | No | 7.06 | 7.06 | 7.06 | 0.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 12 | G WWALL NWA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_GRD | 0.752 | 0.676 | 18.58 | 23.22 | 18.58 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 13 | GWINDOW1 W NWA | Window | G WWALL NWA | Window5 Detailed Fenestration | RESWINDOW_U_0.3972_SHGC_0.4 | N/A | 2.257 | No | 4.65 | 4.65 | 4.65 | 270.00 | 90.00 | 3.81 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 14 | G SIWALL NWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-G SIWALL NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 15 | G EIWALL NWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | iz-G EIWALL NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 16 | G GFLOOR NWA | Floor | CTF - ConductionTransferFunction | GGFLOORNWA_FFACTOR | 0.210 | 0.200 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 17 | G CEILIN NWA | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | G CEILIN NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 18 | G INTERNALMASS NWA | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 88.25 | 88.25 | 88.25 | 0.00 | 90.00 | 88.25 | 1.00 | 0.00 | G INTERNALMASS NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 19 | G SWALL SEA | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.752 | 0.676 | 28.24 | 35.30 | 28.24 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 20 | GWINDOW1 S SEA | Window | G SWALL SEA | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3972_SHGC_0.4 | N/A | 2.257 | No | 7.06 | 7.06 | 7.06 | 180.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 21 | G EWALL SEA | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.752 | 0.676 | 18.58 | 23.22 | 18.58 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 22 | GWINDOW1 E SEA | Window | G EWALL SEA | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3972_SHGC_0.4 | N/A | 2.257 | No | 4.65 | 4.65 | 4.65 | 90.00 | 90.00 | 3.81 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 23 | G NIWALL SEA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-G NIWALL SEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 24 | iz-G EIWALL S2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | G EIWALL S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 25 | G GFLOOR SEA | Floor | CTF - ConductionTransferFunction | GGFLOORSEA_FFACTOR | 0.210 | 0.200 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 26 | G CEILIN SEA | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | G CEILIN SEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 27 | G INTERNALMASS SEA | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 88.25 | 88.25 | 88.25 | 0.00 | 90.00 | 88.25 | 1.00 | 0.00 | G INTERNALMASS SEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 28 | G NWALL NEA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_GRD | 0.752 | 0.676 | 28.24 | 35.30 | 28.24 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 29 | GWINDOW1 N NEA | Window | G NWALL NEA | Window5 Detailed Fenestration | RESWINDOW_U_0.3972_SHGC_0.4 | N/A | 2.257 | No | 7.06 | 7.06 | 7.06 | 0.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 30 | G EWALL NEA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_GRD | 0.752 | 0.676 | 18.58 | 23.22 | 18.58 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 31 | GWINDOW1 E NEA | Window | G EWALL NEA | Window5 Detailed Fenestration | RESWINDOW_U_0.3972_SHGC_0.4 | N/A | 2.257 | No | 4.65 | 4.65 | 4.65 | 90.00 | 90.00 | 3.81 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 32 | G SIWALL NEA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-G SIWALL NEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 33 | iz-G EIWALL N2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | G EIWALL N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 34 | G GFLOOR NEA | Floor | CTF - ConductionTransferFunction | GGFLOORNEA_FFACTOR | 0.210 | 0.200 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 35 | G CEILIN NEA | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | G CEILIN NEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 36 | G INTERNALMASS NEA | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 88.25 | 88.25 | 88.25 | 0.00 | 90.00 | 88.25 | 1.00 | 0.00 | G INTERNALMASS NEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 37 | G NWALL N1A | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_GRD | 0.752 | 0.676 | 28.24 | 35.30 | 28.24 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 38 | GWINDOW1 N N1A | Window | G NWALL N1A | Window5 Detailed Fenestration | RESWINDOW_U_0.3972_SHGC_0.4 | N/A | 2.257 | No | 7.06 | 7.06 | 7.06 | 0.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 39 | G SIWALL N1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-G SIWALL N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 40 | G EIWALL N1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | iz-G EIWALL N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 41 | iz-G EIWALL NWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | G EIWALL NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 42 | G GFLOOR N1A | Floor | CTF - ConductionTransferFunction | GGFLOORN1A_FFACTOR | 0.125 | 0.121 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 43 | G CEILIN N1A | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | G CEILIN N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 44 | G INTERNALMASS N1A | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 88.25 | 88.25 | 88.25 | 0.00 | 90.00 | 88.25 | 1.00 | 0.00 | G INTERNALMASS N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 45 | G NWALL N2A | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_GRD | 0.752 | 0.676 | 28.24 | 35.30 | 28.24 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 46 | GWINDOW1 N N2A | Window | G NWALL N2A | Window5 Detailed Fenestration | RESWINDOW_U_0.3972_SHGC_0.4 | N/A | 2.257 | No | 7.06 | 7.06 | 7.06 | 0.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 47 | G SIWALL N2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-G SIWALL N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 48 | G EIWALL N2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | iz-G EIWALL N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 49 | iz-G EIWALL N1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | G EIWALL N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 50 | G GFLOOR N2A | Floor | CTF - ConductionTransferFunction | GGFLOORN2A_FFACTOR | 0.125 | 0.121 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 51 | G CEILIN N2A | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | G CEILIN N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 52 | G INTERNALMASS N2A | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 88.25 | 88.25 | 88.25 | 0.00 | 90.00 | 88.25 | 1.00 | 0.00 | G INTERNALMASS N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 53 | G SWALL S1A | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_GRD | 0.752 | 0.676 | 28.24 | 35.30 | 28.24 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 54 | GWINDOW1 S S1A | Window | G SWALL S1A | Window5 Detailed Fenestration | RESWINDOW_U_0.3972_SHGC_0.4 | N/A | 2.257 | No | 7.06 | 7.06 | 7.06 | 180.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 55 | G NIWALL S1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-G NIWALL S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 56 | G EIWALL S1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | iz-G EIWALL S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 57 | iz-G EIWALL SWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | G EIWALL SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 58 | G GFLOOR S1A | Floor | CTF - ConductionTransferFunction | GGFLOORS1A_FFACTOR | 0.125 | 0.121 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 59 | G CEILIN S1A | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | G CEILIN S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 60 | G INTERNALMASS S1A | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 88.25 | 88.25 | 88.25 | 0.00 | 90.00 | 88.25 | 1.00 | 0.00 | G INTERNALMASS S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 61 | G SWALL S2A | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_GRD | 0.752 | 0.676 | 28.24 | 35.30 | 28.24 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 62 | GWINDOW1 S S2A | Window | G SWALL S2A | Window5 Detailed Fenestration | RESWINDOW_U_0.3972_SHGC_0.4 | N/A | 2.257 | No | 7.06 | 7.06 | 7.06 | 180.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 63 | G NIWALL S2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-G NIWALL S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 64 | G EIWALL S2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | iz-G EIWALL S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 65 | iz-G EIWALL S1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | G EIWALL S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 66 | G GFLOOR S2A | Floor | CTF - ConductionTransferFunction | GGFLOORS2A_FFACTOR | 0.125 | 0.121 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 67 | G CEILIN S2A | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | G CEILIN S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 68 | G INTERNALMASS S2A | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 88.25 | 88.25 | 88.25 | 0.00 | 90.00 | 88.25 | 1.00 | 0.00 | G INTERNALMASS S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 69 | M WWALL SWA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.761 | 0.683 | 18.58 | 23.22 | 18.58 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 70 | MWINDOW1 W SWA | Window | M WWALL SWA | Window5 Detailed Fenestration | RESWINDOW_U_0.3972_SHGC_0.4 | N/A | 2.257 | No | 4.65 | 4.65 | 4.65 | 270.00 | 90.00 | 3.81 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 71 | M SWALL SWA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.761 | 0.683 | 28.24 | 35.30 | 28.24 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 72 | MWINDOW1 S SWA | Window | M SWALL SWA | Window5 Detailed Fenestration | RESWINDOW_U_0.3972_SHGC_0.4 | N/A | 2.257 | No | 7.06 | 7.06 | 7.06 | 180.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 73 | M NIWALL SWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-M NIWALL SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 74 | M EIWALL SWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 90.00 | 90.00 | 3.05 | 7.62 | 0.00 | iz-M EIWALL SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 75 | M GFLOOR SWA | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | M GFLOOR SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 76 | M CEILIN SWA | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | M CEILIN SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 77 | M INTERNALMASS SWA | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 176.50 | 176.50 | 176.50 | 0.00 | 90.00 | 176.50 | 1.00 | 0.00 | M INTERNALMASS SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 78 | M NWALL NWA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.761 | 0.683 | 28.24 | 35.30 | 28.24 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 79 | MWINDOW1 N NWA | Window | M NWALL NWA | Window5 Detailed Fenestration | RESWINDOW_U_0.3972_SHGC_0.4 | N/A | 2.257 | No | 7.06 | 7.06 | 7.06 | 0.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 80 | M WWALL NWA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.761 | 0.683 | 18.58 | 23.22 | 18.58 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 81 | MWINDOW1 W NWA | Window | M WWALL NWA | Window5 Detailed Fenestration | RESWINDOW_U_0.3972_SHGC_0.4 | N/A | 2.257 | No | 4.65 | 4.65 | 4.65 | 270.00 | 90.00 | 3.81 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 82 | M SIWALL NWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-M SIWALL NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 83 | M EIWALL NWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | iz-M EIWALL NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 84 | M GFLOOR NWA | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | M GFLOOR NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 85 | M CEILIN NWA | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | M CEILIN NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 86 | M INTERNALMASS NWA | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 176.50 | 176.50 | 176.50 | 0.00 | 90.00 | 176.50 | 1.00 | 0.00 | M INTERNALMASS NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 87 | M EWALL SEA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.761 | 0.683 | 18.58 | 23.22 | 18.58 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 88 | MWINDOW1 E SEA | Window | M EWALL SEA | Window5 Detailed Fenestration | RESWINDOW_U_0.3972_SHGC_0.4 | N/A | 2.257 | No | 4.65 | 4.65 | 4.65 | 90.00 | 90.00 | 3.81 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 89 | M SWALL SEA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.761 | 0.683 | 28.24 | 35.30 | 28.24 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 90 | MWINDOW1 S SEA | Window | M SWALL SEA | Window5 Detailed Fenestration | RESWINDOW_U_0.3972_SHGC_0.4 | N/A | 2.257 | No | 7.06 | 7.06 | 7.06 | 180.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 91 | M NIWALL SEA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-M NIWALL SEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 92 | iz-M EIWALL S2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | M EIWALL S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 93 | M GFLOOR SEA | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | M GFLOOR SEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 94 | M CEILIN SEA | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | M CEILIN SEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 95 | M INTERNALMASS SEA | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 176.50 | 176.50 | 176.50 | 0.00 | 90.00 | 176.50 | 1.00 | 0.00 | M INTERNALMASS SEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 96 | M NWALL NEA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.761 | 0.683 | 28.24 | 35.30 | 28.24 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 97 | MWINDOW1 N NEA | Window | M NWALL NEA | Window5 Detailed Fenestration | RESWINDOW_U_0.3972_SHGC_0.4 | N/A | 2.257 | No | 7.06 | 7.06 | 7.06 | 0.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 98 | M EWALL NEA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.761 | 0.683 | 18.58 | 23.22 | 18.58 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 99 | MWINDOW1 E NEA | Window | M EWALL NEA | Window5 Detailed Fenestration | RESWINDOW_U_0.3972_SHGC_0.4 | N/A | 2.257 | No | 4.65 | 4.65 | 4.65 | 90.00 | 90.00 | 3.81 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 100 | M SIWALL NEA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-M SIWALL NEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 101 | iz-M EIWALL N2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | M EIWALL N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 102 | M GFLOOR NEA | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | M GFLOOR NEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 103 | M CEILIN NEA | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | M CEILIN NEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 104 | M INTERNALMASS NEA | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 176.50 | 176.50 | 176.50 | 0.00 | 90.00 | 176.50 | 1.00 | 0.00 | M INTERNALMASS NEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 105 | M NWALL N1A | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.761 | 0.683 | 28.24 | 35.30 | 28.24 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 106 | MWINDOW1 N N1A | Window | M NWALL N1A | Window5 Detailed Fenestration | RESWINDOW_U_0.3972_SHGC_0.4 | N/A | 2.257 | No | 7.06 | 7.06 | 7.06 | 0.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 107 | M SIWALL N1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-M SIWALL N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 108 | M EIWALL N1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | iz-M EIWALL N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 109 | iz-M EIWALL NWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | M EIWALL NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 110 | M GFLOOR N1A | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | M GFLOOR N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 111 | M CEILIN N1A | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | M CEILIN N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 112 | M INTERNALMASS N1A | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 176.50 | 176.50 | 176.50 | 0.00 | 90.00 | 176.50 | 1.00 | 0.00 | M INTERNALMASS N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 113 | M NWALL N2A | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.761 | 0.683 | 28.24 | 35.30 | 28.24 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 114 | MWINDOW1 N N2A | Window | M NWALL N2A | Window5 Detailed Fenestration | RESWINDOW_U_0.3972_SHGC_0.4 | N/A | 2.257 | No | 7.06 | 7.06 | 7.06 | 0.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 115 | M SIWALL N2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-M SIWALL N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 116 | M EIWALL N2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | iz-M EIWALL N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 117 | iz-M EIWALL N1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | M EIWALL N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 118 | M GFLOOR N2A | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | M GFLOOR N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 119 | M CEILIN N2A | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | M CEILIN N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 120 | M INTERNALMASS N2A | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 176.50 | 176.50 | 176.50 | 0.00 | 90.00 | 176.50 | 1.00 | 0.00 | M INTERNALMASS N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 121 | M SWALL S1A | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.761 | 0.683 | 28.24 | 35.30 | 28.24 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 122 | MWINDOW1 S S1A | Window | M SWALL S1A | Window5 Detailed Fenestration | RESWINDOW_U_0.3972_SHGC_0.4 | N/A | 2.257 | No | 7.06 | 7.06 | 7.06 | 180.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 123 | M NIWALL S1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-M NIWALL S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 124 | M EIWALL S1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | iz-M EIWALL S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 125 | iz-M EIWALL SWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 270.00 | 90.00 | 3.05 | 7.62 | 0.00 | M EIWALL SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 126 | M GFLOOR S1A | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | M GFLOOR S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 127 | M CEILIN S1A | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | M CEILIN S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 128 | M INTERNALMASS S1A | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 176.50 | 176.50 | 176.50 | 0.00 | 90.00 | 176.50 | 1.00 | 0.00 | M INTERNALMASS S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 129 | M SWALL S2A | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.761 | 0.683 | 28.24 | 35.30 | 28.24 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 130 | MWINDOW1 S S2A | Window | M SWALL S2A | Window5 Detailed Fenestration | RESWINDOW_U_0.3972_SHGC_0.4 | N/A | 2.257 | No | 7.06 | 7.06 | 7.06 | 180.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 131 | M NIWALL S2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-M NIWALL S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 132 | M EIWALL S2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | iz-M EIWALL S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 133 | iz-M EIWALL S1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | M EIWALL S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 134 | M GFLOOR S2A | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | M GFLOOR S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 135 | M CEILIN S2A | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | M CEILIN S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 136 | M INTERNALMASS S2A | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 176.50 | 176.50 | 176.50 | 0.00 | 90.00 | 176.50 | 1.00 | 0.00 | M INTERNALMASS S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 137 | T WWALL SWA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.098 | 0.943 | 18.58 | 23.22 | 18.58 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 138 | TWINDOW1 W SWA | Window | T WWALL SWA | Window5 Detailed Fenestration | RESWINDOW_U_0.3972_SHGC_0.4 | N/A | 2.257 | No | 4.65 | 4.65 | 4.65 | 270.00 | 90.00 | 3.81 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 139 | T SWALL SWA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.098 | 0.943 | 28.24 | 35.30 | 28.24 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 140 | TWINDOW1 S SWA | Window | T SWALL SWA | Window5 Detailed Fenestration | RESWINDOW_U_0.3972_SHGC_0.4 | N/A | 2.257 | No | 7.06 | 7.06 | 7.06 | 180.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 141 | T NIWALL SWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-T NIWALL SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 142 | T EIWALL SWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | iz-T EIWALL SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 143 | T GFLOOR SWA | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | T GFLOOR SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 144 | T ROOF SWA | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.228 | 0.219 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 145 | T INTERNALMASS SWA | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 88.25 | 88.25 | 88.25 | 0.00 | 90.00 | 88.25 | 1.00 | 0.00 | T INTERNALMASS SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 146 | T NWALL NWA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.098 | 0.943 | 28.24 | 35.30 | 28.24 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 147 | TWINDOW1 N NWA | Window | T NWALL NWA | Window5 Detailed Fenestration | RESWINDOW_U_0.3972_SHGC_0.4 | N/A | 2.257 | No | 7.06 | 7.06 | 7.06 | 0.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 148 | T WWALL NWA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.098 | 0.943 | 18.58 | 23.22 | 18.58 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 149 | TWINDOW1 W NWA | Window | T WWALL NWA | Window5 Detailed Fenestration | RESWINDOW_U_0.3972_SHGC_0.4 | N/A | 2.257 | No | 4.65 | 4.65 | 4.65 | 270.00 | 90.00 | 3.81 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 150 | T SIWALL NWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-T SIWALL NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 151 | T EIWALL NWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | iz-T EIWALL NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 152 | T GFLOOR NWA | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | T GFLOOR NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 153 | T ROOF NWA | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.228 | 0.219 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 154 | T INTERNALMASS NWA | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 88.25 | 88.25 | 88.25 | 0.00 | 90.00 | 88.25 | 1.00 | 0.00 | T INTERNALMASS NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 155 | T EWALL SEA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.098 | 0.943 | 18.58 | 23.22 | 18.58 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 156 | TWINDOW1 E SEA | Window | T EWALL SEA | Window5 Detailed Fenestration | RESWINDOW_U_0.3972_SHGC_0.4 | N/A | 2.257 | No | 4.65 | 4.65 | 4.65 | 90.00 | 90.00 | 3.81 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 157 | T SWALL SEA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.098 | 0.943 | 28.24 | 35.30 | 28.24 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 158 | TWINDOW1 S SEA | Window | T SWALL SEA | Window5 Detailed Fenestration | RESWINDOW_U_0.3972_SHGC_0.4 | N/A | 2.257 | No | 7.06 | 7.06 | 7.06 | 180.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 159 | T NIWALL SEA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-T NIWALL SEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 160 | iz-T EIWALL S2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | T EIWALL S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 161 | T GFLOOR SEA | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | T GFLOOR SEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 162 | T ROOF SEA | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.228 | 0.219 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 163 | T INTERNALMASS SEA | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 88.25 | 88.25 | 88.25 | 0.00 | 90.00 | 88.25 | 1.00 | 0.00 | T INTERNALMASS SEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 164 | T NWALL NEA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.098 | 0.943 | 28.24 | 35.30 | 28.24 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 165 | TWINDOW1 N NEA | Window | T NWALL NEA | Window5 Detailed Fenestration | RESWINDOW_U_0.3972_SHGC_0.4 | N/A | 2.257 | No | 7.06 | 7.06 | 7.06 | 0.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 166 | T EWALL NEA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.098 | 0.943 | 18.58 | 23.22 | 18.58 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 167 | TWINDOW1 E NEA | Window | T EWALL NEA | Window5 Detailed Fenestration | RESWINDOW_U_0.3972_SHGC_0.4 | N/A | 2.257 | No | 4.65 | 4.65 | 4.65 | 90.00 | 90.00 | 3.81 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 168 | T SIWALL NEA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-T SIWALL NEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 169 | iz-T EIWALL N2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | T EIWALL N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 170 | T GFLOOR NEA | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | T GFLOOR NEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 171 | T ROOF NEA | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.228 | 0.219 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 172 | T INTERNALMASS NEA | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 88.25 | 88.25 | 88.25 | 0.00 | 90.00 | 88.25 | 1.00 | 0.00 | T INTERNALMASS NEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 173 | T NWALL N1A | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.098 | 0.943 | 28.24 | 35.30 | 28.24 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 174 | TWINDOW1 N N1A | Window | T NWALL N1A | Window5 Detailed Fenestration | RESWINDOW_U_0.3972_SHGC_0.4 | N/A | 2.257 | No | 7.06 | 7.06 | 7.06 | 0.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 175 | T SIWALL N1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-T SIWALL N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 176 | T EIWALL N1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | iz-T EIWALL N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 177 | iz-T EIWALL NWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | T EIWALL NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 178 | T GFLOOR N1A | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | T GFLOOR N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 179 | T ROOF N1A | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.228 | 0.219 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 180 | T INTERNALMASS N1A | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 88.25 | 88.25 | 88.25 | 0.00 | 90.00 | 88.25 | 1.00 | 0.00 | T INTERNALMASS N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 181 | T NWALL N2A | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.098 | 0.943 | 28.24 | 35.30 | 28.24 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 182 | TWINDOW1 N N2A | Window | T NWALL N2A | Window5 Detailed Fenestration | RESWINDOW_U_0.3972_SHGC_0.4 | N/A | 2.257 | No | 7.06 | 7.06 | 7.06 | 0.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 183 | T SIWALL N2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-T SIWALL N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 184 | T EIWALL N2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | iz-T EIWALL N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 185 | iz-T EIWALL N1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | T EIWALL N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 186 | T GFLOOR N2A | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | T GFLOOR N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 187 | T ROOF N2A | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.228 | 0.219 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 188 | T INTERNALMASS N2A | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 88.25 | 88.25 | 88.25 | 0.00 | 90.00 | 88.25 | 1.00 | 0.00 | T INTERNALMASS N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 189 | T SWALL S1A | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.098 | 0.943 | 28.24 | 35.30 | 28.24 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 190 | TWINDOW1 S S1A | Window | T SWALL S1A | Window5 Detailed Fenestration | RESWINDOW_U_0.3972_SHGC_0.4 | N/A | 2.257 | No | 7.06 | 7.06 | 7.06 | 180.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 191 | T NIWALL S1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-T NIWALL S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 192 | T EIWALL S1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | iz-T EIWALL S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 193 | iz-T EIWALL SWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | T EIWALL SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 194 | T GFLOOR S1A | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | T GFLOOR S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 195 | T ROOF S1A | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.228 | 0.219 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 196 | T INTERNALMASS S1A | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 88.25 | 88.25 | 88.25 | 0.00 | 90.00 | 88.25 | 1.00 | 0.00 | T INTERNALMASS S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 197 | T SWALL S2A | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.098 | 0.943 | 28.24 | 35.30 | 28.24 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 198 | TWINDOW1 S S2A | Window | T SWALL S2A | Window5 Detailed Fenestration | RESWINDOW_U_0.3972_SHGC_0.4 | N/A | 2.257 | No | 7.06 | 7.06 | 7.06 | 180.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 199 | T NIWALL S2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-T NIWALL S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 200 | T EIWALL S2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | iz-T EIWALL S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 201 | iz-T EIWALL S1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | T EIWALL S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 202 | T GFLOOR S2A | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | T GFLOOR S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 203 | T ROOF S2A | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.228 | 0.219 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 204 | T INTERNALMASS S2A | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 88.25 | 88.25 | 88.25 | 0.00 | 90.00 | 88.25 | 1.00 | 0.00 | T INTERNALMASS S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 205 | T WWALL C | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.098 | 0.943 | 5.11 | 5.11 | 5.11 | 270.00 | 90.00 | 1.68 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 206 | T EWALL C | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.098 | 0.943 | 3.99 | 5.11 | 3.99 | 90.00 | 90.00 | 1.68 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 207 | TWINDOW14 | Window | T EWALL C | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3972_SHGC_0.4 | N/A | 2.257 | No | 1.11 | 1.11 | 1.11 | 90.00 | 90.00 | 0.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 208 | iz-T NIWALL SWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | T NIWALL SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 209 | iz-T NIWALL S1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | T NIWALL S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 210 | iz-T NIWALL S2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | T NIWALL S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 211 | iz-T NIWALL SEA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | T NIWALL SEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 212 | iz-T SIWALL NWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | T SIWALL NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 213 | iz-T SIWALL N1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | T SIWALL N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 214 | iz-T SIWALL N2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | T SIWALL N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 215 | iz-T SIWALL NEA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | T SIWALL NEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 216 | T FLOOR C | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 77.66 | 77.66 | 77.66 | 90.00 | 180.00 | 1.68 | 46.33 | 0.00 | T FLOOR C | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 217 | T ROOF C | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 77.66 | 77.66 | 77.66 | 180.00 | 0.00 | 46.33 | 1.68 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 218 | G WWALL C | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.752 | 0.676 | 5.11 | 5.11 | 5.11 | 270.00 | 90.00 | 1.68 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 219 | G EWALL C | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.752 | 0.676 | 1.79 | 5.11 | 1.79 | 90.00 | 90.00 | 1.68 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 220 | ENTRANCE DOOR | Window | G EWALL C | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3972_SHGC_0.4 | N/A | 2.257 | No | 3.32 | 3.32 | 3.32 | 90.00 | 90.00 | 1.57 | 2.11 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 221 | iz-G NIWALL SWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | G NIWALL SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 222 | iz-G NIWALL S1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | G NIWALL S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 223 | iz-G NIWALL S2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | G NIWALL S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 224 | iz-G NIWALL SEA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | G NIWALL SEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 225 | iz-G SIWALL NWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | G SIWALL NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 226 | iz-G SIWALL N1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | G SIWALL N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 227 | iz-G SIWALL N2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | G SIWALL N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 228 | iz-G SIWALL NEA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | G SIWALL NEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 229 | G FLOOR C | Floor | CTF - ConductionTransferFunction | GFLOORC_FFACTOR | 4.061E-002 | 4.021E-002 | 77.66 | 77.66 | 77.66 | 90.00 | 180.00 | 1.68 | 46.33 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 230 | G CEILING C | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 77.66 | 77.66 | 77.66 | 180.00 | 0.00 | 46.33 | 1.68 | 0.00 | G CEILING C | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 231 | M WWALL C | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.761 | 0.683 | 5.11 | 5.11 | 5.11 | 270.00 | 90.00 | 1.68 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 232 | M EWALL C | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.761 | 0.683 | 3.99 | 5.11 | 3.99 | 90.00 | 90.00 | 1.68 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 233 | MWINDOW14 | Window | M EWALL C | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3972_SHGC_0.4 | N/A | 2.257 | No | 1.11 | 1.11 | 1.11 | 90.00 | 90.00 | 0.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 234 | iz-M NIWALL SWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | M NIWALL SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 235 | iz-M NIWALL S1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | M NIWALL S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 236 | iz-M NIWALL S2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | M NIWALL S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 237 | iz-M NIWALL SEA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | M NIWALL SEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 238 | iz-M SIWALL NWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | M SIWALL NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 239 | iz-M SIWALL N1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | M SIWALL N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 240 | iz-M SIWALL N2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | M SIWALL N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 241 | iz-M SIWALL NEA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | M SIWALL NEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 242 | M FLOOR C | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 77.66 | 77.66 | 77.66 | 90.00 | 180.00 | 1.68 | 46.33 | 0.00 | M FLOOR C | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 243 | M CEILING C | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 77.66 | 77.66 | 77.66 | 180.00 | 0.00 | 46.33 | 1.68 | 0.00 | M CEILING C | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
| Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
| 1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | Yes | Yes | Yes | Clark and Allen |
| Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
| 1 | NEW YEAR'S DAY | Holiday | InputFile | 01/02 | 1Environment:Special Days |
| Daylight Saving Indicator | Source | Start Date | End Date | |
| 1 | Yes | InputFile | 03/12 | 11/05 |
| Style | Unit Conversion | |
| 1 | Commaandhtml | commaandhtml |
| Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
| 1 | G SW APARTMENT | RunPeriod: RUNPERIOD 1 | 2.4582059844E-008 | 1.2143537162E-007 | Pass | Pass | 1.7775767331E-002 | 1.6131269949E-002 | Pass | Pass |
| 2 | G NW APARTMENT | RunPeriod: RUNPERIOD 1 | 8.8645019892E-008 | 5.1742837888E-007 | Pass | Pass | 1.5690172407E-002 | 1.3766508335E-002 | Pass | Pass |
| 3 | OFFICE | RunPeriod: RUNPERIOD 1 | 8.2115579346E-003 | 3.0389815446E-002 | Pass | Pass | 0.2180949965 | 0.6367535053 | Pass | Pass |
| 4 | G NE APARTMENT | RunPeriod: RUNPERIOD 1 | 8.8333956742E-008 | 5.1524379955E-007 | Pass | Pass | 1.5528594772E-002 | 1.3746663760E-002 | Pass | Pass |
| 5 | G N1 APARTMENT | RunPeriod: RUNPERIOD 1 | 4.4379058872E-008 | 2.6534344878E-007 | Pass | Pass | 2.4864273873E-002 | 3.1491885155E-002 | Pass | Pass |
| 6 | G N2 APARTMENT | RunPeriod: RUNPERIOD 1 | 4.4370333259E-008 | 2.6527400044E-007 | Pass | Pass | 2.4862305475E-002 | 3.1487268873E-002 | Pass | Pass |
| 7 | G S1 APARTMENT | RunPeriod: RUNPERIOD 1 | 1.1215652456E-008 | 5.3849830068E-008 | Pass | Pass | 3.2044931192E-002 | 4.5049007643E-002 | Pass | Pass |
| 8 | G S2 APARTMENT | RunPeriod: RUNPERIOD 1 | 1.7586728123E-008 | 8.4441345719E-008 | Pass | Pass | 1.9584284641E-002 | 2.3947163028E-002 | Pass | Pass |
| 9 | M SW APARTMENT | RunPeriod: RUNPERIOD 1 | 1.2658142509E-008 | 7.3348760205E-008 | Pass | Pass | 3.9916776186E-002 | 3.9205318781E-002 | Pass | Pass |
| 10 | M NW APARTMENT | RunPeriod: RUNPERIOD 1 | 4.8374904823E-008 | 2.8641194117E-007 | Pass | Pass | 3.2106192025E-002 | 2.9503046464E-002 | Pass | Pass |
| 11 | M SE APARTMENT | RunPeriod: RUNPERIOD 1 | 1.2523205090E-008 | 7.2606310443E-008 | Pass | Pass | 3.9734686111E-002 | 3.8564102367E-002 | Pass | Pass |
| 12 | M NE APARTMENT | RunPeriod: RUNPERIOD 1 | 4.7916934470E-008 | 2.8322767283E-007 | Pass | Pass | 3.2053321430E-002 | 2.9149230389E-002 | Pass | Pass |
| 13 | M N1 APARTMENT | RunPeriod: RUNPERIOD 1 | 6.6446884291E-009 | 4.0187091461E-008 | Pass | Pass | 0.8721576281 | 3.5667588325 | Pass | Pass |
| 14 | M N2 APARTMENT | RunPeriod: RUNPERIOD 1 | 6.6331296998E-009 | 4.0099100619E-008 | Pass | Pass | 3.9662817708 | 39.2926608033 | Pass | Pass |
| 15 | M S1 APARTMENT | RunPeriod: RUNPERIOD 1 | 1.6024424997E-009 | 9.6990947682E-009 | Pass | Pass | 0.2863810586 | 0.5489372609 | Pass | Pass |
| 16 | M S2 APARTMENT | RunPeriod: RUNPERIOD 1 | 1.6001522576E-009 | 9.6962144734E-009 | Pass | Pass | 0.2836479983 | 0.5375137548 | Pass | Pass |
| 17 | T SW APARTMENT | RunPeriod: RUNPERIOD 1 | 3.8811833821E-008 | 2.1113159727E-007 | Pass | Pass | 1.9152480768E-002 | 1.5252917525E-002 | Pass | Pass |
| 18 | T NW APARTMENT | RunPeriod: RUNPERIOD 1 | 1.1924843503E-007 | 7.1174165033E-007 | Pass | Pass | 1.6840095186E-002 | 1.2963083778E-002 | Pass | Pass |
| 19 | T SE APARTMENT | RunPeriod: RUNPERIOD 1 | 3.8617071639E-008 | 2.0989509379E-007 | Pass | Pass | 1.9065325339E-002 | 1.5119088441E-002 | Pass | Pass |
| 20 | T NE APARTMENT | RunPeriod: RUNPERIOD 1 | 1.1857901513E-007 | 7.0726314736E-007 | Pass | Pass | 1.6711173011E-002 | 1.2936519408E-002 | Pass | Pass |
| 21 | T N1 APARTMENT | RunPeriod: RUNPERIOD 1 | 7.2990081189E-008 | 4.3729608641E-007 | Pass | Pass | 1.9865350144E-002 | 1.8839798361E-002 | Pass | Pass |
| 22 | T N2 APARTMENT | RunPeriod: RUNPERIOD 1 | 7.2973840205E-008 | 4.3716097735E-007 | Pass | Pass | 1.9864142830E-002 | 1.8844133442E-002 | Pass | Pass |
| 23 | T S1 APARTMENT | RunPeriod: RUNPERIOD 1 | 1.9667111248E-008 | 1.0280059955E-007 | Pass | Pass | 2.4933044659E-002 | 2.5173241178E-002 | Pass | Pass |
| 24 | T S2 APARTMENT | RunPeriod: RUNPERIOD 1 | 1.9662671195E-008 | 1.0277474005E-007 | Pass | Pass | 2.4938389131E-002 | 2.5162354251E-002 | Pass | Pass |
| 25 | T CORRIDOR | RunPeriod: RUNPERIOD 1 | 6.5366760874E-003 | 4.9726781367E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
| 26 | G CORRIDOR | RunPeriod: RUNPERIOD 1 | 0.2060643432 | 0.6795149778 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
| 27 | M CORRIDOR | RunPeriod: RUNPERIOD 1 | 5.3821488106E-003 | 3.9146465207E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 09:14:20
Heat Emission by Components| Envelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
| Heat Emissions [GJ] | 1891.70 | 201.88 | 0.00 | 17.89 | 508.52 | 2619.99 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 09:14:20
SizingPeriod:DesignDay| Maximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
| BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | -16.30 | 0.00 | -16.30 | Wetbulb [C] | 5.10 | 270.00 |
| BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 30.30 | 9.30 | 21.80 | Wetbulb [C] | 5.70 | 240.00 |
| Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
| Jan | 0.00 | 0 | |||
| Feb | 0.00 | 0 | |||
| Mar | 0.00 | 0 | |||
| Apr | 0.00 | 0 | |||
| May | 44.00 | 33 | |||
| Jun | 0.00 | 0 | |||
| Jul | 0.00 | 0 | |||
| Aug | 0.00 | 0 | |||
| Sep | 67.00 | 33 | |||
| Oct | 0.00 | 0 | |||
| Nov | 0.00 | 0 | |||
| Dec | 0.00 | 0 |
| Value | |
| None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 09:14:20
Opaque Exterior| Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
| G SWALL SWA | RES_EXT_WALL_GRD | 0.30 | 0.676 | 0.752 | 35.30 | 28.24 | 180.00 | 90.00 | S |
| G WWALL SWA | RES_EXT_WALL_GRD | 0.30 | 0.676 | 0.752 | 23.22 | 18.58 | 270.00 | 90.00 | W |
| G GFLOOR SWA | GGFLOORSWA_FFACTOR | 1.00 | 0.203 | 0.210 | 88.25 | 88.25 | 90.00 | 180.00 | |
| G NWALL NWA | RES_EXT_WALL_GRD | 0.30 | 0.676 | 0.752 | 35.30 | 28.24 | 0.00 | 90.00 | N |
| G WWALL NWA | RES_EXT_WALL_GRD | 0.30 | 0.676 | 0.752 | 23.22 | 18.58 | 270.00 | 90.00 | W |
| G GFLOOR NWA | GGFLOORNWA_FFACTOR | 1.00 | 0.203 | 0.210 | 88.25 | 88.25 | 90.00 | 180.00 | |
| G SWALL SEA | NONRES_EXT_WALL_GRD | 0.30 | 0.676 | 0.752 | 35.30 | 28.24 | 180.00 | 90.00 | S |
| G EWALL SEA | NONRES_EXT_WALL_GRD | 0.30 | 0.676 | 0.752 | 23.22 | 18.58 | 90.00 | 90.00 | E |
| G GFLOOR SEA | GGFLOORSEA_FFACTOR | 1.00 | 0.203 | 0.210 | 88.25 | 88.25 | 90.00 | 180.00 | |
| G NWALL NEA | RES_EXT_WALL_GRD | 0.30 | 0.676 | 0.752 | 35.30 | 28.24 | 0.00 | 90.00 | N |
| G EWALL NEA | RES_EXT_WALL_GRD | 0.30 | 0.676 | 0.752 | 23.22 | 18.58 | 90.00 | 90.00 | E |
| G GFLOOR NEA | GGFLOORNEA_FFACTOR | 1.00 | 0.203 | 0.210 | 88.25 | 88.25 | 90.00 | 180.00 | |
| G NWALL N1A | RES_EXT_WALL_GRD | 0.30 | 0.676 | 0.752 | 35.30 | 28.24 | 0.00 | 90.00 | N |
| G GFLOOR N1A | GGFLOORN1A_FFACTOR | 1.00 | 0.123 | 0.125 | 88.25 | 88.25 | 90.00 | 180.00 | |
| G NWALL N2A | RES_EXT_WALL_GRD | 0.30 | 0.676 | 0.752 | 35.30 | 28.24 | 0.00 | 90.00 | N |
| G GFLOOR N2A | GGFLOORN2A_FFACTOR | 1.00 | 0.123 | 0.125 | 88.25 | 88.25 | 90.00 | 180.00 | |
| G SWALL S1A | RES_EXT_WALL_GRD | 0.30 | 0.676 | 0.752 | 35.30 | 28.24 | 180.00 | 90.00 | S |
| G GFLOOR S1A | GGFLOORS1A_FFACTOR | 1.00 | 0.123 | 0.125 | 88.25 | 88.25 | 90.00 | 180.00 | |
| G SWALL S2A | RES_EXT_WALL_GRD | 0.30 | 0.676 | 0.752 | 35.30 | 28.24 | 180.00 | 90.00 | S |
| G GFLOOR S2A | GGFLOORS2A_FFACTOR | 1.00 | 0.123 | 0.125 | 88.25 | 88.25 | 90.00 | 180.00 | |
| M WWALL SWA | RES_EXT_WALL_MID | 0.30 | 0.683 | 0.761 | 46.45 | 37.16 | 270.00 | 90.00 | W |
| M SWALL SWA | RES_EXT_WALL_MID | 0.30 | 0.683 | 0.761 | 70.60 | 56.48 | 180.00 | 90.00 | S |
| M NWALL NWA | RES_EXT_WALL_MID | 0.30 | 0.683 | 0.761 | 70.60 | 56.48 | 0.00 | 90.00 | N |
| M WWALL NWA | RES_EXT_WALL_MID | 0.30 | 0.683 | 0.761 | 46.45 | 37.16 | 270.00 | 90.00 | W |
| M EWALL SEA | RES_EXT_WALL_MID | 0.30 | 0.683 | 0.761 | 46.45 | 37.16 | 90.00 | 90.00 | E |
| M SWALL SEA | RES_EXT_WALL_MID | 0.30 | 0.683 | 0.761 | 70.60 | 56.48 | 180.00 | 90.00 | S |
| M NWALL NEA | RES_EXT_WALL_MID | 0.30 | 0.683 | 0.761 | 70.60 | 56.48 | 0.00 | 90.00 | N |
| M EWALL NEA | RES_EXT_WALL_MID | 0.30 | 0.683 | 0.761 | 46.45 | 37.16 | 90.00 | 90.00 | E |
| M NWALL N1A | RES_EXT_WALL_MID | 0.30 | 0.683 | 0.761 | 70.60 | 56.48 | 0.00 | 90.00 | N |
| M NWALL N2A | RES_EXT_WALL_MID | 0.30 | 0.683 | 0.761 | 70.60 | 56.48 | 0.00 | 90.00 | N |
| M SWALL S1A | RES_EXT_WALL_MID | 0.30 | 0.683 | 0.761 | 70.60 | 56.48 | 180.00 | 90.00 | S |
| M SWALL S2A | RES_EXT_WALL_MID | 0.30 | 0.683 | 0.761 | 70.60 | 56.48 | 180.00 | 90.00 | S |
| T WWALL SWA | RES_EXT_WALL_TOP | 0.30 | 0.943 | 1.098 | 23.22 | 18.58 | 270.00 | 90.00 | W |
| T SWALL SWA | RES_EXT_WALL_TOP | 0.30 | 0.943 | 1.098 | 35.30 | 28.24 | 180.00 | 90.00 | S |
| T ROOF SWA | RES_ROOF | 0.30 | 0.221 | 0.228 | 88.25 | 88.25 | 180.00 | 0.00 | |
| T NWALL NWA | RES_EXT_WALL_TOP | 0.30 | 0.943 | 1.098 | 35.30 | 28.24 | 0.00 | 90.00 | N |
| T WWALL NWA | RES_EXT_WALL_TOP | 0.30 | 0.943 | 1.098 | 23.22 | 18.58 | 270.00 | 90.00 | W |
| T ROOF NWA | RES_ROOF | 0.30 | 0.221 | 0.228 | 88.25 | 88.25 | 180.00 | 0.00 | |
| T EWALL SEA | RES_EXT_WALL_TOP | 0.30 | 0.943 | 1.098 | 23.22 | 18.58 | 90.00 | 90.00 | E |
| T SWALL SEA | RES_EXT_WALL_TOP | 0.30 | 0.943 | 1.098 | 35.30 | 28.24 | 180.00 | 90.00 | S |
| T ROOF SEA | RES_ROOF | 0.30 | 0.221 | 0.228 | 88.25 | 88.25 | 180.00 | 0.00 | |
| T NWALL NEA | RES_EXT_WALL_TOP | 0.30 | 0.943 | 1.098 | 35.30 | 28.24 | 0.00 | 90.00 | N |
| T EWALL NEA | RES_EXT_WALL_TOP | 0.30 | 0.943 | 1.098 | 23.22 | 18.58 | 90.00 | 90.00 | E |
| T ROOF NEA | RES_ROOF | 0.30 | 0.221 | 0.228 | 88.25 | 88.25 | 180.00 | 0.00 | |
| T NWALL N1A | RES_EXT_WALL_TOP | 0.30 | 0.943 | 1.098 | 35.30 | 28.24 | 0.00 | 90.00 | N |
| T ROOF N1A | RES_ROOF | 0.30 | 0.221 | 0.228 | 88.25 | 88.25 | 180.00 | 0.00 | |
| T NWALL N2A | RES_EXT_WALL_TOP | 0.30 | 0.943 | 1.098 | 35.30 | 28.24 | 0.00 | 90.00 | N |
| T ROOF N2A | RES_ROOF | 0.30 | 0.221 | 0.228 | 88.25 | 88.25 | 180.00 | 0.00 | |
| T SWALL S1A | RES_EXT_WALL_TOP | 0.30 | 0.943 | 1.098 | 35.30 | 28.24 | 180.00 | 90.00 | S |
| T ROOF S1A | RES_ROOF | 0.30 | 0.221 | 0.228 | 88.25 | 88.25 | 180.00 | 0.00 | |
| T SWALL S2A | RES_EXT_WALL_TOP | 0.30 | 0.943 | 1.098 | 35.30 | 28.24 | 180.00 | 90.00 | S |
| T ROOF S2A | RES_ROOF | 0.30 | 0.221 | 0.228 | 88.25 | 88.25 | 180.00 | 0.00 | |
| T WWALL C | NONRES_EXT_WALL_TOP | 0.30 | 0.943 | 1.098 | 5.11 | 5.11 | 270.00 | 90.00 | W |
| T EWALL C | NONRES_EXT_WALL_TOP | 0.30 | 0.943 | 1.098 | 5.11 | 3.99 | 90.00 | 90.00 | E |
| T ROOF C | NONRES_ROOF | 0.30 | 0.221 | 0.228 | 77.66 | 77.66 | 180.00 | 0.00 | |
| G WWALL C | NONRES_EXT_WALL_GRD | 0.30 | 0.676 | 0.752 | 5.11 | 5.11 | 270.00 | 90.00 | W |
| G EWALL C | NONRES_EXT_WALL_GRD | 0.30 | 0.676 | 0.752 | 5.11 | 1.79 | 90.00 | 90.00 | E |
| G FLOOR C | GFLOORC_FFACTOR | 1.00 | 0.040 | 0.041 | 77.66 | 77.66 | 90.00 | 180.00 | |
| M WWALL C | NONRES_EXT_WALL_MID | 0.30 | 0.683 | 0.761 | 10.22 | 10.22 | 270.00 | 90.00 | W |
| M EWALL C | NONRES_EXT_WALL_MID | 0.30 | 0.683 | 0.761 | 10.22 | 7.99 | 90.00 | 90.00 | E |
| Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
| G NIWALL SWA | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 0.00 | 90.00 | N |
| G EIWALL SWA | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 90.00 | 90.00 | E |
| G CEILIN SWA | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 88.25 | 88.25 | 180.00 | 0.00 | |
| G SIWALL NWA | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 180.00 | 90.00 | S |
| G EIWALL NWA | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 90.00 | 90.00 | E |
| G CEILIN NWA | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 88.25 | 88.25 | 180.00 | 0.00 | |
| G NIWALL SEA | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 0.00 | 90.00 | N |
| iz-G EIWALL S2A | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 270.00 | 90.00 | W |
| G CEILIN SEA | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 88.25 | 88.25 | 180.00 | 0.00 | |
| G SIWALL NEA | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 180.00 | 90.00 | S |
| iz-G EIWALL N2A | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 270.00 | 90.00 | W |
| G CEILIN NEA | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 88.25 | 88.25 | 180.00 | 0.00 | |
| G SIWALL N1A | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 180.00 | 90.00 | S |
| G EIWALL N1A | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 90.00 | 90.00 | E |
| iz-G EIWALL NWA | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 270.00 | 90.00 | W |
| G CEILIN N1A | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 88.25 | 88.25 | 180.00 | 0.00 | |
| G SIWALL N2A | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 180.00 | 90.00 | S |
| G EIWALL N2A | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 90.00 | 90.00 | E |
| iz-G EIWALL N1A | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 270.00 | 90.00 | W |
| G CEILIN N2A | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 88.25 | 88.25 | 180.00 | 0.00 | |
| G NIWALL S1A | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 0.00 | 90.00 | N |
| G EIWALL S1A | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 90.00 | 90.00 | E |
| iz-G EIWALL SWA | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 270.00 | 90.00 | W |
| G CEILIN S1A | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 88.25 | 88.25 | 180.00 | 0.00 | |
| G NIWALL S2A | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 0.00 | 90.00 | N |
| G EIWALL S2A | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 90.00 | 90.00 | E |
| iz-G EIWALL S1A | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 270.00 | 90.00 | W |
| G CEILIN S2A | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 88.25 | 88.25 | 180.00 | 0.00 | |
| M NIWALL SWA | INT_WALL | 0.30 | 2.511 | 6.299 | 70.60 | 70.60 | 0.00 | 90.00 | N |
| M EIWALL SWA | INT_WALL | 0.30 | 2.511 | 6.299 | 46.45 | 46.45 | 90.00 | 90.00 | E |
| M GFLOOR SWA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 176.50 | 176.50 | 90.00 | 180.00 | |
| M CEILIN SWA | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 176.50 | 176.50 | 180.00 | 0.00 | |
| M SIWALL NWA | INT_WALL | 0.30 | 2.511 | 6.299 | 70.60 | 70.60 | 180.00 | 90.00 | S |
| M EIWALL NWA | INT_WALL | 0.30 | 2.511 | 6.299 | 46.45 | 46.45 | 90.00 | 90.00 | E |
| M GFLOOR NWA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 176.50 | 176.50 | 90.00 | 180.00 | |
| M CEILIN NWA | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 176.50 | 176.50 | 180.00 | 0.00 | |
| M NIWALL SEA | INT_WALL | 0.30 | 2.511 | 6.299 | 70.60 | 70.60 | 0.00 | 90.00 | N |
| iz-M EIWALL S2A | INT_WALL | 0.30 | 2.511 | 6.299 | 46.45 | 46.45 | 270.00 | 90.00 | W |
| M GFLOOR SEA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 176.50 | 176.50 | 90.00 | 180.00 | |
| M CEILIN SEA | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 176.50 | 176.50 | 180.00 | 0.00 | |
| M SIWALL NEA | INT_WALL | 0.30 | 2.511 | 6.299 | 70.60 | 70.60 | 180.00 | 90.00 | S |
| iz-M EIWALL N2A | INT_WALL | 0.30 | 2.511 | 6.299 | 46.45 | 46.45 | 270.00 | 90.00 | W |
| M GFLOOR NEA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 176.50 | 176.50 | 90.00 | 180.00 | |
| M CEILIN NEA | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 176.50 | 176.50 | 180.00 | 0.00 | |
| M SIWALL N1A | INT_WALL | 0.30 | 2.511 | 6.299 | 70.60 | 70.60 | 180.00 | 90.00 | S |
| M EIWALL N1A | INT_WALL | 0.30 | 2.511 | 6.299 | 46.45 | 46.45 | 90.00 | 90.00 | E |
| iz-M EIWALL NWA | INT_WALL | 0.30 | 2.511 | 6.299 | 46.45 | 46.45 | 270.00 | 90.00 | W |
| M GFLOOR N1A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 176.50 | 176.50 | 90.00 | 180.00 | |
| M CEILIN N1A | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 176.50 | 176.50 | 180.00 | 0.00 | |
| M SIWALL N2A | INT_WALL | 0.30 | 2.511 | 6.299 | 70.60 | 70.60 | 180.00 | 90.00 | S |
| M EIWALL N2A | INT_WALL | 0.30 | 2.511 | 6.299 | 46.45 | 46.45 | 90.00 | 90.00 | E |
| iz-M EIWALL N1A | INT_WALL | 0.30 | 2.511 | 6.299 | 46.45 | 46.45 | 270.00 | 90.00 | W |
| M GFLOOR N2A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 176.50 | 176.50 | 90.00 | 180.00 | |
| M CEILIN N2A | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 176.50 | 176.50 | 180.00 | 0.00 | |
| M NIWALL S1A | INT_WALL | 0.30 | 2.511 | 6.299 | 70.60 | 70.60 | 0.00 | 90.00 | N |
| M EIWALL S1A | INT_WALL | 0.30 | 2.511 | 6.299 | 46.45 | 46.45 | 90.00 | 90.00 | E |
| iz-M EIWALL SWA | INT_WALL | 0.30 | 2.511 | 6.299 | 46.45 | 46.45 | 270.00 | 90.00 | W |
| M GFLOOR S1A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 176.50 | 176.50 | 90.00 | 180.00 | |
| M CEILIN S1A | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 176.50 | 176.50 | 180.00 | 0.00 | |
| M NIWALL S2A | INT_WALL | 0.30 | 2.511 | 6.299 | 70.60 | 70.60 | 0.00 | 90.00 | N |
| M EIWALL S2A | INT_WALL | 0.30 | 2.511 | 6.299 | 46.45 | 46.45 | 90.00 | 90.00 | E |
| iz-M EIWALL S1A | INT_WALL | 0.30 | 2.511 | 6.299 | 46.45 | 46.45 | 270.00 | 90.00 | W |
| M GFLOOR S2A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 176.50 | 176.50 | 90.00 | 180.00 | |
| M CEILIN S2A | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 176.50 | 176.50 | 180.00 | 0.00 | |
| T NIWALL SWA | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 0.00 | 90.00 | N |
| T EIWALL SWA | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 90.00 | 90.00 | E |
| T GFLOOR SWA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 88.25 | 88.25 | 90.00 | 180.00 | |
| T SIWALL NWA | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 180.00 | 90.00 | S |
| T EIWALL NWA | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 90.00 | 90.00 | E |
| T GFLOOR NWA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 88.25 | 88.25 | 90.00 | 180.00 | |
| T NIWALL SEA | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 0.00 | 90.00 | N |
| iz-T EIWALL S2A | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 270.00 | 90.00 | W |
| T GFLOOR SEA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 88.25 | 88.25 | 90.00 | 180.00 | |
| T SIWALL NEA | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 180.00 | 90.00 | S |
| iz-T EIWALL N2A | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 270.00 | 90.00 | W |
| T GFLOOR NEA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 88.25 | 88.25 | 90.00 | 180.00 | |
| T SIWALL N1A | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 180.00 | 90.00 | S |
| T EIWALL N1A | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 90.00 | 90.00 | E |
| iz-T EIWALL NWA | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 270.00 | 90.00 | W |
| T GFLOOR N1A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 88.25 | 88.25 | 90.00 | 180.00 | |
| T SIWALL N2A | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 180.00 | 90.00 | S |
| T EIWALL N2A | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 90.00 | 90.00 | E |
| iz-T EIWALL N1A | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 270.00 | 90.00 | W |
| T GFLOOR N2A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 88.25 | 88.25 | 90.00 | 180.00 | |
| T NIWALL S1A | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 0.00 | 90.00 | N |
| T EIWALL S1A | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 90.00 | 90.00 | E |
| iz-T EIWALL SWA | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 270.00 | 90.00 | W |
| T GFLOOR S1A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 88.25 | 88.25 | 90.00 | 180.00 | |
| T NIWALL S2A | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 0.00 | 90.00 | N |
| T EIWALL S2A | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 90.00 | 90.00 | E |
| iz-T EIWALL S1A | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 270.00 | 90.00 | W |
| T GFLOOR S2A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 88.25 | 88.25 | 90.00 | 180.00 | |
| iz-T NIWALL SWA | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 180.00 | 90.00 | S |
| iz-T NIWALL S1A | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 180.00 | 90.00 | S |
| iz-T NIWALL S2A | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 180.00 | 90.00 | S |
| iz-T NIWALL SEA | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 180.00 | 90.00 | S |
| iz-T SIWALL NWA | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 0.00 | 90.00 | N |
| iz-T SIWALL N1A | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 0.00 | 90.00 | N |
| iz-T SIWALL N2A | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 0.00 | 90.00 | N |
| iz-T SIWALL NEA | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 0.00 | 90.00 | N |
| T FLOOR C | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 77.66 | 77.66 | 90.00 | 180.00 | |
| iz-G NIWALL SWA | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 180.00 | 90.00 | S |
| iz-G NIWALL S1A | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 180.00 | 90.00 | S |
| iz-G NIWALL S2A | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 180.00 | 90.00 | S |
| iz-G NIWALL SEA | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 180.00 | 90.00 | S |
| iz-G SIWALL NWA | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 0.00 | 90.00 | N |
| iz-G SIWALL N1A | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 0.00 | 90.00 | N |
| iz-G SIWALL N2A | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 0.00 | 90.00 | N |
| iz-G SIWALL NEA | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 0.00 | 90.00 | N |
| G CEILING C | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 77.66 | 77.66 | 180.00 | 0.00 | |
| iz-M NIWALL SWA | INT_WALL | 0.30 | 2.511 | 6.299 | 70.60 | 70.60 | 180.00 | 90.00 | S |
| iz-M NIWALL S1A | INT_WALL | 0.30 | 2.511 | 6.299 | 70.60 | 70.60 | 180.00 | 90.00 | S |
| iz-M NIWALL S2A | INT_WALL | 0.30 | 2.511 | 6.299 | 70.60 | 70.60 | 180.00 | 90.00 | S |
| iz-M NIWALL SEA | INT_WALL | 0.30 | 2.511 | 6.299 | 70.60 | 70.60 | 180.00 | 90.00 | S |
| iz-M SIWALL NWA | INT_WALL | 0.30 | 2.511 | 6.299 | 70.60 | 70.60 | 0.00 | 90.00 | N |
| iz-M SIWALL N1A | INT_WALL | 0.30 | 2.511 | 6.299 | 70.60 | 70.60 | 0.00 | 90.00 | N |
| iz-M SIWALL N2A | INT_WALL | 0.30 | 2.511 | 6.299 | 70.60 | 70.60 | 0.00 | 90.00 | N |
| iz-M SIWALL NEA | INT_WALL | 0.30 | 2.511 | 6.299 | 70.60 | 70.60 | 0.00 | 90.00 | N |
| M FLOOR C | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 155.32 | 155.32 | 90.00 | 180.00 | |
| M CEILING C | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 155.32 | 155.32 | 180.00 | 0.00 | |
| G INTERNALMASS SWA | INTERIORFURNISHINGS | 0.30 | 0.800 | 88.25 | 0.00 | 90.00 | N | ||
| G INTERNALMASS NWA | INTERIORFURNISHINGS | 0.30 | 0.800 | 88.25 | 0.00 | 90.00 | N | ||
| G INTERNALMASS SEA | INTERIORFURNISHINGS | 0.30 | 0.800 | 88.25 | 0.00 | 90.00 | N | ||
| G INTERNALMASS NEA | INTERIORFURNISHINGS | 0.30 | 0.800 | 88.25 | 0.00 | 90.00 | N | ||
| G INTERNALMASS N1A | INTERIORFURNISHINGS | 0.30 | 0.800 | 88.25 | 0.00 | 90.00 | N | ||
| G INTERNALMASS N2A | INTERIORFURNISHINGS | 0.30 | 0.800 | 88.25 | 0.00 | 90.00 | N | ||
| G INTERNALMASS S1A | INTERIORFURNISHINGS | 0.30 | 0.800 | 88.25 | 0.00 | 90.00 | N | ||
| G INTERNALMASS S2A | INTERIORFURNISHINGS | 0.30 | 0.800 | 88.25 | 0.00 | 90.00 | N | ||
| M INTERNALMASS SWA | INTERIORFURNISHINGS | 0.30 | 0.800 | 353.00 | 0.00 | 90.00 | N | ||
| M INTERNALMASS NWA | INTERIORFURNISHINGS | 0.30 | 0.800 | 353.00 | 0.00 | 90.00 | N | ||
| M INTERNALMASS SEA | INTERIORFURNISHINGS | 0.30 | 0.800 | 353.00 | 0.00 | 90.00 | N | ||
| M INTERNALMASS NEA | INTERIORFURNISHINGS | 0.30 | 0.800 | 353.00 | 0.00 | 90.00 | N | ||
| M INTERNALMASS N1A | INTERIORFURNISHINGS | 0.30 | 0.800 | 353.00 | 0.00 | 90.00 | N | ||
| M INTERNALMASS N2A | INTERIORFURNISHINGS | 0.30 | 0.800 | 353.00 | 0.00 | 90.00 | N | ||
| M INTERNALMASS S1A | INTERIORFURNISHINGS | 0.30 | 0.800 | 353.00 | 0.00 | 90.00 | N | ||
| M INTERNALMASS S2A | INTERIORFURNISHINGS | 0.30 | 0.800 | 353.00 | 0.00 | 90.00 | N | ||
| T INTERNALMASS SWA | INTERIORFURNISHINGS | 0.30 | 0.800 | 88.25 | 0.00 | 90.00 | N | ||
| T INTERNALMASS NWA | INTERIORFURNISHINGS | 0.30 | 0.800 | 88.25 | 0.00 | 90.00 | N | ||
| T INTERNALMASS SEA | INTERIORFURNISHINGS | 0.30 | 0.800 | 88.25 | 0.00 | 90.00 | N | ||
| T INTERNALMASS NEA | INTERIORFURNISHINGS | 0.30 | 0.800 | 88.25 | 0.00 | 90.00 | N | ||
| T INTERNALMASS N1A | INTERIORFURNISHINGS | 0.30 | 0.800 | 88.25 | 0.00 | 90.00 | N | ||
| T INTERNALMASS N2A | INTERIORFURNISHINGS | 0.30 | 0.800 | 88.25 | 0.00 | 90.00 | N | ||
| T INTERNALMASS S1A | INTERIORFURNISHINGS | 0.30 | 0.800 | 88.25 | 0.00 | 90.00 | N | ||
| T INTERNALMASS S2A | INTERIORFURNISHINGS | 0.30 | 0.800 | 88.25 | 0.00 | 90.00 | N |
| Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
| GWINDOW1 S SWA | RESWINDOW_U_0.3972_SHGC_0.4 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.257 | 0.401 | 0.402 | No | G SWALL SWA | 180.00 | 90.00 | S | |||||||
| GWINDOW1 W SWA | RESWINDOW_U_0.3972_SHGC_0.4 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 2.257 | 0.401 | 0.402 | No | G WWALL SWA | 270.00 | 90.00 | W | |||||||
| GWINDOW1 N NWA | RESWINDOW_U_0.3972_SHGC_0.4 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.257 | 0.401 | 0.402 | No | G NWALL NWA | 0.00 | 90.00 | N | |||||||
| GWINDOW1 W NWA | RESWINDOW_U_0.3972_SHGC_0.4 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 2.257 | 0.401 | 0.402 | No | G WWALL NWA | 270.00 | 90.00 | W | |||||||
| GWINDOW1 S SEA | NONRESWINDOW_U_0.3972_SHGC_0.4 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.257 | 0.401 | 0.402 | No | G SWALL SEA | 180.00 | 90.00 | S | |||||||
| GWINDOW1 E SEA | NONRESWINDOW_U_0.3972_SHGC_0.4 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 2.257 | 0.401 | 0.402 | No | G EWALL SEA | 90.00 | 90.00 | E | |||||||
| GWINDOW1 N NEA | RESWINDOW_U_0.3972_SHGC_0.4 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.257 | 0.401 | 0.402 | No | G NWALL NEA | 0.00 | 90.00 | N | |||||||
| GWINDOW1 E NEA | RESWINDOW_U_0.3972_SHGC_0.4 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 2.257 | 0.401 | 0.402 | No | G EWALL NEA | 90.00 | 90.00 | E | |||||||
| GWINDOW1 N N1A | RESWINDOW_U_0.3972_SHGC_0.4 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.257 | 0.401 | 0.402 | No | G NWALL N1A | 0.00 | 90.00 | N | |||||||
| GWINDOW1 N N2A | RESWINDOW_U_0.3972_SHGC_0.4 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.257 | 0.401 | 0.402 | No | G NWALL N2A | 0.00 | 90.00 | N | |||||||
| GWINDOW1 S S1A | RESWINDOW_U_0.3972_SHGC_0.4 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.257 | 0.401 | 0.402 | No | G SWALL S1A | 180.00 | 90.00 | S | |||||||
| GWINDOW1 S S2A | RESWINDOW_U_0.3972_SHGC_0.4 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.257 | 0.401 | 0.402 | No | G SWALL S2A | 180.00 | 90.00 | S | |||||||
| MWINDOW1 W SWA | RESWINDOW_U_0.3972_SHGC_0.4 | 4.65 | 0.00 | 0.00 | 4.65 | 9.29 | 2.257 | 0.401 | 0.402 | No | M WWALL SWA | 270.00 | 90.00 | W | |||||||
| MWINDOW1 S SWA | RESWINDOW_U_0.3972_SHGC_0.4 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 2.257 | 0.401 | 0.402 | No | M SWALL SWA | 180.00 | 90.00 | S | |||||||
| MWINDOW1 N NWA | RESWINDOW_U_0.3972_SHGC_0.4 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 2.257 | 0.401 | 0.402 | No | M NWALL NWA | 0.00 | 90.00 | N | |||||||
| MWINDOW1 W NWA | RESWINDOW_U_0.3972_SHGC_0.4 | 4.65 | 0.00 | 0.00 | 4.65 | 9.29 | 2.257 | 0.401 | 0.402 | No | M WWALL NWA | 270.00 | 90.00 | W | |||||||
| MWINDOW1 E SEA | RESWINDOW_U_0.3972_SHGC_0.4 | 4.65 | 0.00 | 0.00 | 4.65 | 9.29 | 2.257 | 0.401 | 0.402 | No | M EWALL SEA | 90.00 | 90.00 | E | |||||||
| MWINDOW1 S SEA | RESWINDOW_U_0.3972_SHGC_0.4 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 2.257 | 0.401 | 0.402 | No | M SWALL SEA | 180.00 | 90.00 | S | |||||||
| MWINDOW1 N NEA | RESWINDOW_U_0.3972_SHGC_0.4 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 2.257 | 0.401 | 0.402 | No | M NWALL NEA | 0.00 | 90.00 | N | |||||||
| MWINDOW1 E NEA | RESWINDOW_U_0.3972_SHGC_0.4 | 4.65 | 0.00 | 0.00 | 4.65 | 9.29 | 2.257 | 0.401 | 0.402 | No | M EWALL NEA | 90.00 | 90.00 | E | |||||||
| MWINDOW1 N N1A | RESWINDOW_U_0.3972_SHGC_0.4 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 2.257 | 0.401 | 0.402 | No | M NWALL N1A | 0.00 | 90.00 | N | |||||||
| MWINDOW1 N N2A | RESWINDOW_U_0.3972_SHGC_0.4 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 2.257 | 0.401 | 0.402 | No | M NWALL N2A | 0.00 | 90.00 | N | |||||||
| MWINDOW1 S S1A | RESWINDOW_U_0.3972_SHGC_0.4 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 2.257 | 0.401 | 0.402 | No | M SWALL S1A | 180.00 | 90.00 | S | |||||||
| MWINDOW1 S S2A | RESWINDOW_U_0.3972_SHGC_0.4 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 2.257 | 0.401 | 0.402 | No | M SWALL S2A | 180.00 | 90.00 | S | |||||||
| TWINDOW1 W SWA | RESWINDOW_U_0.3972_SHGC_0.4 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 2.257 | 0.401 | 0.402 | No | T WWALL SWA | 270.00 | 90.00 | W | |||||||
| TWINDOW1 S SWA | RESWINDOW_U_0.3972_SHGC_0.4 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.257 | 0.401 | 0.402 | No | T SWALL SWA | 180.00 | 90.00 | S | |||||||
| TWINDOW1 N NWA | RESWINDOW_U_0.3972_SHGC_0.4 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.257 | 0.401 | 0.402 | No | T NWALL NWA | 0.00 | 90.00 | N | |||||||
| TWINDOW1 W NWA | RESWINDOW_U_0.3972_SHGC_0.4 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 2.257 | 0.401 | 0.402 | No | T WWALL NWA | 270.00 | 90.00 | W | |||||||
| TWINDOW1 E SEA | RESWINDOW_U_0.3972_SHGC_0.4 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 2.257 | 0.401 | 0.402 | No | T EWALL SEA | 90.00 | 90.00 | E | |||||||
| TWINDOW1 S SEA | RESWINDOW_U_0.3972_SHGC_0.4 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.257 | 0.401 | 0.402 | No | T SWALL SEA | 180.00 | 90.00 | S | |||||||
| TWINDOW1 N NEA | RESWINDOW_U_0.3972_SHGC_0.4 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.257 | 0.401 | 0.402 | No | T NWALL NEA | 0.00 | 90.00 | N | |||||||
| TWINDOW1 E NEA | RESWINDOW_U_0.3972_SHGC_0.4 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 2.257 | 0.401 | 0.402 | No | T EWALL NEA | 90.00 | 90.00 | E | |||||||
| TWINDOW1 N N1A | RESWINDOW_U_0.3972_SHGC_0.4 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.257 | 0.401 | 0.402 | No | T NWALL N1A | 0.00 | 90.00 | N | |||||||
| TWINDOW1 N N2A | RESWINDOW_U_0.3972_SHGC_0.4 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.257 | 0.401 | 0.402 | No | T NWALL N2A | 0.00 | 90.00 | N | |||||||
| TWINDOW1 S S1A | RESWINDOW_U_0.3972_SHGC_0.4 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.257 | 0.401 | 0.402 | No | T SWALL S1A | 180.00 | 90.00 | S | |||||||
| TWINDOW1 S S2A | RESWINDOW_U_0.3972_SHGC_0.4 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.257 | 0.401 | 0.402 | No | T SWALL S2A | 180.00 | 90.00 | S | |||||||
| TWINDOW14 | NONRESWINDOW_U_0.3972_SHGC_0.4 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.257 | 0.401 | 0.402 | No | T EWALL C | 90.00 | 90.00 | E | |||||||
| ENTRANCE DOOR | NONRESWINDOW_U_0.3972_SHGC_0.4 | 3.32 | 0.00 | 0.00 | 3.32 | 3.32 | 2.257 | 0.401 | 0.402 | No | G EWALL C | 90.00 | 90.00 | E | |||||||
| MWINDOW14 | NONRESWINDOW_U_0.3972_SHGC_0.4 | 1.11 | 0.00 | 0.00 | 1.11 | 2.23 | 2.257 | 0.401 | 0.402 | No | M EWALL C | 90.00 | 90.00 | E | |||||||
| Total or Average | 306.92 | 2.257 | 0.401 | 0.402 | |||||||||||||||||
| North Total or Average | 112.97 | 2.257 | 0.401 | 0.402 | |||||||||||||||||
| Non-North Total or Average | 193.95 | 2.257 | 0.401 | 0.402 |
| Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
| None |
| Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
| Total or Average | 0.00 | - | - | - |
| Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
| None |
| Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
| None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 09:14:20
Sunlit Fraction| March 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
| GWINDOW1 S SWA | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| GWINDOW1 W SWA | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
| GWINDOW1 N NWA | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| GWINDOW1 W NWA | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
| GWINDOW1 S SEA | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| GWINDOW1 E SEA | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
| GWINDOW1 N NEA | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| GWINDOW1 E NEA | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
| GWINDOW1 N N1A | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| GWINDOW1 N N2A | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| GWINDOW1 S S1A | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| GWINDOW1 S S2A | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| MWINDOW1 W SWA | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
| MWINDOW1 S SWA | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| MWINDOW1 N NWA | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| MWINDOW1 W NWA | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
| MWINDOW1 E SEA | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
| MWINDOW1 S SEA | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| MWINDOW1 N NEA | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| MWINDOW1 E NEA | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
| MWINDOW1 N N1A | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| MWINDOW1 N N2A | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| MWINDOW1 S S1A | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| MWINDOW1 S S2A | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| TWINDOW1 W SWA | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
| TWINDOW1 S SWA | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| TWINDOW1 N NWA | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| TWINDOW1 W NWA | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
| TWINDOW1 E SEA | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
| TWINDOW1 S SEA | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| TWINDOW1 N NEA | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| TWINDOW1 E NEA | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
| TWINDOW1 N N1A | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| TWINDOW1 N N2A | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| TWINDOW1 S S1A | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| TWINDOW1 S S2A | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| TWINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
| ENTRANCE DOOR | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
| MWINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
| Name | Type | Shaded Construction | Control | Glare Control | |
| None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 09:14:20
Interior Lighting| Zone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
| LIGHTING_HARDWIRED_GSW | G SW APARTMENT | G SW APARTMENT | GENERAL | 7.8684 | 88.25 | 694.38 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.32 |
| LIGHTING_HARDWIRED_GNW | G NW APARTMENT | G NW APARTMENT | GENERAL | 7.8684 | 88.25 | 694.38 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.32 |
| LIGHTING_HARDWIRED_OFFICE | OFFICE | OFFICE | GENERAL | 9.7532 | 88.25 | 860.71 | LightsWired | LTG_SCH_OFFICE | 46.69 | 168.00 | 45.77 | 0.0000 | Y | 7.40 |
| LIGHTING_HARDWIRED_GNE | G NE APARTMENT | G NE APARTMENT | GENERAL | 7.8684 | 88.25 | 694.38 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.32 |
| LIGHTING_HARDWIRED_GN1 | G N1 APARTMENT | G N1 APARTMENT | GENERAL | 7.8684 | 88.25 | 694.38 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.32 |
| LIGHTING_HARDWIRED_GN2 | G N2 APARTMENT | G N2 APARTMENT | GENERAL | 7.8684 | 88.25 | 694.38 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.32 |
| LIGHTING_HARDWIRED_GS1 | G S1 APARTMENT | G S1 APARTMENT | GENERAL | 7.8684 | 88.25 | 694.38 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.32 |
| LIGHTING_HARDWIRED_GS2 | G S2 APARTMENT | G S2 APARTMENT | GENERAL | 7.8684 | 88.25 | 694.38 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.32 |
| LIGHTING_HARDWIRED_MSW | M SW APARTMENT | M SW APARTMENT | GENERAL | 7.8684 | 176.50 | 1388.76 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 2.63 |
| LIGHTING_HARDWIRED_MNW | M NW APARTMENT | M NW APARTMENT | GENERAL | 7.8684 | 176.50 | 1388.76 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 2.63 |
| LIGHTING_HARDWIRED_MSE | M SE APARTMENT | M SE APARTMENT | GENERAL | 7.8684 | 176.50 | 1388.76 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 2.63 |
| LIGHTING_HARDWIRED_MNE | M NE APARTMENT | M NE APARTMENT | GENERAL | 7.8684 | 176.50 | 1388.76 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 2.63 |
| LIGHTING_HARDWIRED_MN1 | M N1 APARTMENT | M N1 APARTMENT | GENERAL | 7.8684 | 176.50 | 1388.76 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 2.63 |
| LIGHTING_HARDWIRED_MN2 | M N2 APARTMENT | M N2 APARTMENT | GENERAL | 7.8684 | 176.50 | 1388.76 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 2.63 |
| LIGHTING_HARDWIRED_MS1 | M S1 APARTMENT | M S1 APARTMENT | GENERAL | 7.8684 | 176.50 | 1388.76 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 2.63 |
| LIGHTING_HARDWIRED_MS2 | M S2 APARTMENT | M S2 APARTMENT | GENERAL | 7.8684 | 176.50 | 1388.76 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 2.63 |
| LIGHTING_HARDWIRED_TSW | T SW APARTMENT | T SW APARTMENT | GENERAL | 7.8684 | 88.25 | 694.38 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.32 |
| LIGHTING_HARDWIRED_TNW | T NW APARTMENT | T NW APARTMENT | GENERAL | 7.8684 | 88.25 | 694.38 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.32 |
| LIGHTING_HARDWIRED_TSE | T SE APARTMENT | T SE APARTMENT | GENERAL | 7.8684 | 88.25 | 694.38 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.32 |
| LIGHTING_HARDWIRED_TNE | T NE APARTMENT | T NE APARTMENT | GENERAL | 7.8684 | 88.25 | 694.38 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.32 |
| LIGHTING_HARDWIRED_TN1 | T N1 APARTMENT | T N1 APARTMENT | GENERAL | 7.8684 | 88.25 | 694.38 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.32 |
| LIGHTING_HARDWIRED_TN2 | T N2 APARTMENT | T N2 APARTMENT | GENERAL | 7.8684 | 88.25 | 694.38 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.32 |
| LIGHTING_HARDWIRED_TS1 | T S1 APARTMENT | T S1 APARTMENT | GENERAL | 7.8684 | 88.25 | 694.38 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.32 |
| LIGHTING_HARDWIRED_TS2 | T S2 APARTMENT | T S2 APARTMENT | GENERAL | 7.8684 | 88.25 | 694.38 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.32 |
| LIGHTING_HARDWIRED_GC | G CORRIDOR | G CORRIDOR | GENERAL | 4.7725 | 77.66 | 370.63 | LightsWired | LTG_SCH_CORRIDOR | 168.00 | 168.00 | 168.00 | 0.0000 | N | 11.69 |
| LIGHTING_HARDWIRED_MC | M CORRIDOR | M CORRIDOR | GENERAL | 4.7725 | 155.32 | 741.26 | LightsWired | LTG_SCH_CORRIDOR | 168.00 | 168.00 | 168.00 | 0.0000 | N | 23.38 |
| LIGHTING_HARDWIRED_TC | T CORRIDOR | T CORRIDOR | GENERAL | 4.7725 | 77.66 | 370.63 | LightsWired | LTG_SCH_CORRIDOR | 168.00 | 168.00 | 168.00 | 0.0000 | N | 11.69 |
| LIGHTING_PLUGIN_GSW | G SW APARTMENT | G SW APARTMENT | GENERAL | 0.8234 | 88.25 | 72.67 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.14 |
| LIGHTING_PLUGIN_GNW | G NW APARTMENT | G NW APARTMENT | GENERAL | 0.8234 | 88.25 | 72.67 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.14 |
| LIGHTING_PLUGIN_GNE | G NE APARTMENT | G NE APARTMENT | GENERAL | 0.8234 | 88.25 | 72.67 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.14 |
| LIGHTING_PLUGIN_GN1 | G N1 APARTMENT | G N1 APARTMENT | GENERAL | 0.8234 | 88.25 | 72.67 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.14 |
| LIGHTING_PLUGIN_GN2 | G N2 APARTMENT | G N2 APARTMENT | GENERAL | 0.8234 | 88.25 | 72.67 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.14 |
| LIGHTING_PLUGIN_GS1 | G S1 APARTMENT | G S1 APARTMENT | GENERAL | 0.8234 | 88.25 | 72.67 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.14 |
| LIGHTING_PLUGIN_GS2 | G S2 APARTMENT | G S2 APARTMENT | GENERAL | 0.8234 | 88.25 | 72.67 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.14 |
| LIGHTING_PLUGIN_MSW | M SW APARTMENT | M SW APARTMENT | GENERAL | 0.8234 | 176.50 | 145.34 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.28 |
| LIGHTING_PLUGIN_MNW | M NW APARTMENT | M NW APARTMENT | GENERAL | 0.8234 | 176.50 | 145.34 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.28 |
| LIGHTING_PLUGIN_MSE | M SE APARTMENT | M SE APARTMENT | GENERAL | 0.8234 | 176.50 | 145.34 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.28 |
| LIGHTING_PLUGIN_MNE | M NE APARTMENT | M NE APARTMENT | GENERAL | 0.8234 | 176.50 | 145.34 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.28 |
| LIGHTING_PLUGIN_MN1 | M N1 APARTMENT | M N1 APARTMENT | GENERAL | 0.8234 | 176.50 | 145.34 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.28 |
| LIGHTING_PLUGIN_MN2 | M N2 APARTMENT | M N2 APARTMENT | GENERAL | 0.8234 | 176.50 | 145.34 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.28 |
| LIGHTING_PLUGIN_MS1 | M S1 APARTMENT | M S1 APARTMENT | GENERAL | 0.8234 | 176.50 | 145.34 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.28 |
| LIGHTING_PLUGIN_MS2 | M S2 APARTMENT | M S2 APARTMENT | GENERAL | 0.8234 | 176.50 | 145.34 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.28 |
| LIGHTING_PLUGIN_TSW | T SW APARTMENT | T SW APARTMENT | GENERAL | 0.8234 | 88.25 | 72.67 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.14 |
| LIGHTING_PLUGIN_TNW | T NW APARTMENT | T NW APARTMENT | GENERAL | 0.8234 | 88.25 | 72.67 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.14 |
| LIGHTING_PLUGIN_TSE | T SE APARTMENT | T SE APARTMENT | GENERAL | 0.8234 | 88.25 | 72.67 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.14 |
| LIGHTING_PLUGIN_TNE | T NE APARTMENT | T NE APARTMENT | GENERAL | 0.8234 | 88.25 | 72.67 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.14 |
| LIGHTING_PLUGIN_TN1 | T N1 APARTMENT | T N1 APARTMENT | GENERAL | 0.8234 | 88.25 | 72.67 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.14 |
| LIGHTING_PLUGIN_TN2 | T N2 APARTMENT | T N2 APARTMENT | GENERAL | 0.8234 | 88.25 | 72.67 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.14 |
| LIGHTING_PLUGIN_TS1 | T S1 APARTMENT | T S1 APARTMENT | GENERAL | 0.8234 | 88.25 | 72.67 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.14 |
| LIGHTING_PLUGIN_TS2 | T S2 APARTMENT | T S2 APARTMENT | GENERAL | 0.8234 | 88.25 | 72.67 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.14 |
| Interior Lighting Total | 4.4498 | 5870.34 | 26121.74 | 75.91 |
| Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
| None |
| Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
| FACADE LIGHTING | 3183.33 | AstronomicalClock | - | 83.67 | 83.67 | 50.00 | |
| Exterior Lighting Total | 3183.33 | 50.00 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 09:14:20
Central Plant| Type | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
| None |
| Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
| SPLIT GSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5716.92 | 4573.86 | 1143.06 | 0.80 | 3.91 | |||
| SPLIT GNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5396.97 | 4319.19 | 1077.78 | 0.80 | 3.91 | |||
| SPLIT OFFICE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 6296.23 | 5041.11 | 1255.12 | 0.80 | 3.91 | |||
| SPLIT GNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 4899.83 | 3924.68 | 975.15 | 0.80 | 3.91 | |||
| SPLIT GN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 4486.35 | 3592.70 | 893.65 | 0.80 | 3.91 | |||
| SPLIT GN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 4477.27 | 3584.88 | 892.38 | 0.80 | 3.91 | |||
| SPLIT GS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 4842.71 | 3875.25 | 967.46 | 0.80 | 3.91 | |||
| SPLIT GS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 4869.89 | 3898.36 | 971.53 | 0.80 | 3.91 | |||
| SPLIT MSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 14381.86 | 11514.91 | 2866.95 | 0.80 | 3.91 | |||
| SPLIT MNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 13846.93 | 11086.61 | 2760.31 | 0.80 | 3.91 | |||
| SPLIT MSE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 12729.02 | 10193.99 | 2535.02 | 0.80 | 3.91 | |||
| SPLIT MNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 12244.00 | 9804.16 | 2439.84 | 0.80 | 3.91 | |||
| SPLIT MN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10993.53 | 8805.02 | 2188.50 | 0.80 | 3.91 | |||
| SPLIT MN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10968.71 | 8783.78 | 2184.93 | 0.80 | 3.91 | |||
| SPLIT MS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 11571.12 | 9263.22 | 2307.90 | 0.80 | 3.91 | |||
| SPLIT MS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 11544.95 | 9240.76 | 2304.19 | 0.80 | 3.91 | |||
| SPLIT TSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7907.05 | 6330.82 | 1576.23 | 0.80 | 3.91 | |||
| SPLIT TNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7796.61 | 6242.40 | 1554.21 | 0.80 | 3.91 | |||
| SPLIT TSE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 6719.99 | 5380.02 | 1339.98 | 0.80 | 3.91 | |||
| SPLIT TNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 6606.84 | 5289.66 | 1317.18 | 0.80 | 3.91 | |||
| SPLIT TN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 6155.71 | 4928.60 | 1227.11 | 0.80 | 3.91 | |||
| SPLIT TN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 6117.09 | 4897.68 | 1219.41 | 0.80 | 3.91 | |||
| SPLIT TS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 6292.71 | 5038.29 | 1254.42 | 0.80 | 3.91 | |||
| SPLIT TS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 6254.20 | 5007.46 | 1246.74 | 0.80 | 3.91 |
| DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
| SPLIT GSW COOLING COIL | 5448.2 | 3.13 | 10.69 | 11.10 | 10.50 | 10.40 | |
| SPLIT GNW COOLING COIL | 5144.4 | 3.13 | 10.70 | 11.12 | 10.52 | 10.41 | |
| SPLIT OFFICE COOLING COIL | 5998.1 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 | |
| SPLIT GNE COOLING COIL | 4674.5 | 3.15 | 10.73 | 11.16 | 10.55 | 10.47 | |
| SPLIT GN1 COOLING COIL | 4280.1 | 3.15 | 10.74 | 11.16 | 10.55 | 10.47 | |
| SPLIT GN2 COOLING COIL | 4271.5 | 3.15 | 10.74 | 11.16 | 10.56 | 10.47 | |
| SPLIT GS1 COOLING COIL | 4618.6 | 3.14 | 10.72 | 11.14 | 10.54 | 10.45 | |
| SPLIT GS2 COOLING COIL | 4644.4 | 3.14 | 10.72 | 11.14 | 10.54 | 10.45 | |
| SPLIT MSW COOLING COIL | 13701.0 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 | |
| SPLIT MNW COOLING COIL | 13191.4 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 | |
| SPLIT MSE COOLING COIL | 12129.3 | 3.13 | 10.68 | 11.10 | 10.50 | 10.39 | |
| SPLIT MNE COOLING COIL | 11668.9 | 3.13 | 10.69 | 11.11 | 10.51 | 10.40 | |
| SPLIT MN1 COOLING COIL | 10476.9 | 3.13 | 10.69 | 11.11 | 10.51 | 10.40 | |
| SPLIT MN2 COOLING COIL | 10453.4 | 3.13 | 10.69 | 11.11 | 10.51 | 10.40 | |
| SPLIT MS1 COOLING COIL | 11024.9 | 3.13 | 10.68 | 11.10 | 10.50 | 10.39 | |
| SPLIT MS2 COOLING COIL | 11000.2 | 3.13 | 10.68 | 11.10 | 10.50 | 10.39 | |
| SPLIT TSW COOLING COIL | 7532.7 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 | |
| SPLIT TNW COOLING COIL | 7427.5 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 | |
| SPLIT TSE COOLING COIL | 6404.5 | 3.13 | 10.69 | 11.11 | 10.51 | 10.40 | |
| SPLIT TNE COOLING COIL | 6296.6 | 3.13 | 10.69 | 11.11 | 10.51 | 10.40 | |
| SPLIT TN1 COOLING COIL | 5864.3 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 | |
| SPLIT TN2 COOLING COIL | 5827.5 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 | |
| SPLIT TS1 COOLING COIL | 5994.8 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 | |
| SPLIT TS2 COOLING COIL | 5958.1 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 |
| DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
| SPLIT GSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT GNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT OFFICE COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT GNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT GN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT GN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT GS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT GS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT MSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT MNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT MSE COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT MNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT MN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT MN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT MS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT MS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT TSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT TNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT TSE COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT TNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT TN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT TN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT TS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT TS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed |
| DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
| None |
| Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
| SPLIT GSW HEATING COIL | Coil:Heating:Fuel | 8790.72 | 0.80 | |
| SPLIT GNW HEATING COIL | Coil:Heating:Fuel | 8328.05 | 0.80 | |
| SPLIT OFFICE HEATING COIL | Coil:Heating:Fuel | 10161.51 | 0.80 | |
| SPLIT GNE HEATING COIL | Coil:Heating:Fuel | 7553.02 | 0.80 | |
| SPLIT GN1 HEATING COIL | Coil:Heating:Fuel | 7009.28 | 0.80 | |
| SPLIT GN2 HEATING COIL | Coil:Heating:Fuel | 6995.42 | 0.80 | |
| SPLIT GS1 HEATING COIL | Coil:Heating:Fuel | 7517.99 | 0.80 | |
| SPLIT GS2 HEATING COIL | Coil:Heating:Fuel | 7558.75 | 0.80 | |
| SPLIT MSW HEATING COIL | Coil:Heating:Fuel | 21662.34 | 0.80 | |
| SPLIT MNW HEATING COIL | Coil:Heating:Fuel | 20941.52 | 0.80 | |
| SPLIT MSE HEATING COIL | Coil:Heating:Fuel | 19351.64 | 0.80 | |
| SPLIT MNE HEATING COIL | Coil:Heating:Fuel | 18651.27 | 0.80 | |
| SPLIT MN1 HEATING COIL | Coil:Heating:Fuel | 16987.62 | 0.80 | |
| SPLIT MN2 HEATING COIL | Coil:Heating:Fuel | 16949.42 | 0.80 | |
| SPLIT MS1 HEATING COIL | Coil:Heating:Fuel | 17828.68 | 0.80 | |
| SPLIT MS2 HEATING COIL | Coil:Heating:Fuel | 17787.98 | 0.80 | |
| SPLIT TSW HEATING COIL | Coil:Heating:Fuel | 11796.21 | 0.80 | |
| SPLIT TNW HEATING COIL | Coil:Heating:Fuel | 11647.28 | 0.80 | |
| SPLIT TSE HEATING COIL | Coil:Heating:Fuel | 10121.91 | 0.80 | |
| SPLIT TNE HEATING COIL | Coil:Heating:Fuel | 9971.48 | 0.80 | |
| SPLIT TN1 HEATING COIL | Coil:Heating:Fuel | 9436.48 | 0.80 | |
| SPLIT TN2 HEATING COIL | Coil:Heating:Fuel | 9384.45 | 0.80 | |
| SPLIT TS1 HEATING COIL | Coil:Heating:Fuel | 9621.14 | 0.80 | |
| SPLIT TS2 HEATING COIL | Coil:Heating:Fuel | 9569.26 | 0.80 |
| Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
| G SW APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| G SW APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| G NW APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| G NW APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| G NE APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| G NE APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| G N1 APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| G N1 APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| G N2 APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| G N2 APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| G S1 APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| G S1 APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| G S2 APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| G S2 APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| M SW APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.05 | 40.01 | 770.84 | 1.00 | 4.13 | General | ||
| M SW APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.05 | 40.01 | 770.84 | 1.00 | 4.13 | General | ||
| M NW APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.05 | 40.01 | 770.84 | 1.00 | 4.13 | General | ||
| M NW APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.05 | 40.01 | 770.84 | 1.00 | 4.13 | General | ||
| M SE APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.05 | 40.01 | 770.84 | 1.00 | 4.13 | General | ||
| M SE APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.05 | 40.01 | 770.84 | 1.00 | 4.13 | General | ||
| M NE APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.05 | 40.01 | 770.84 | 1.00 | 4.13 | General | ||
| M NE APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.05 | 40.01 | 770.84 | 1.00 | 4.13 | General | ||
| M N1 APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.05 | 40.01 | 770.84 | 1.00 | 4.13 | General | ||
| M N1 APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.05 | 40.01 | 770.84 | 1.00 | 4.13 | General | ||
| M N2 APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.05 | 40.01 | 770.84 | 1.00 | 4.13 | General | ||
| M N2 APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.05 | 40.01 | 770.84 | 1.00 | 4.13 | General | ||
| M S1 APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.05 | 40.01 | 770.84 | 1.00 | 4.13 | General | ||
| M S1 APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.05 | 40.01 | 770.84 | 1.00 | 4.13 | General | ||
| M S2 APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.05 | 40.01 | 770.84 | 1.00 | 4.13 | General | ||
| M S2 APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.05 | 40.01 | 770.84 | 1.00 | 4.13 | General | ||
| T SW APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| T SW APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| T NW APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| T NW APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| T SE APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| T SE APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| T NE APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| T NE APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| T N1 APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| T N1 APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| T N2 APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| T N2 APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| T S1 APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| T S1 APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| T S2 APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| T S2 APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| SPLIT GSW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.34 | 384.11 | 1120.11 | 1.00 | 1.81 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 |
| SPLIT GNW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.32 | 360.86 | 1120.11 | 1.00 | 1.85 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 |
| SPLIT OFFICE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.38 | 426.04 | 1120.11 | 1.00 | 1.74 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 |
| SPLIT GNE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.29 | 321.93 | 1120.11 | 1.00 | 1.93 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 |
| SPLIT GN1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.26 | 294.61 | 1120.11 | 1.00 | 2.00 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 |
| SPLIT GN2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.26 | 293.92 | 1120.11 | 1.00 | 2.00 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 |
| SPLIT GS1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.29 | 320.17 | 1120.11 | 1.00 | 1.93 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 |
| SPLIT GS2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.29 | 322.22 | 1120.11 | 1.00 | 1.93 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 |
| SPLIT MSW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.87 | 973.16 | 1120.11 | 1.00 | 1.41 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 |
| SPLIT MNW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.84 | 936.96 | 1120.11 | 1.00 | 1.42 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 |
| SPLIT MSE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.77 | 857.08 | 1120.11 | 1.00 | 1.45 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 |
| SPLIT MNE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.73 | 821.91 | 1120.11 | 1.00 | 1.46 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 |
| SPLIT MN1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.66 | 738.37 | 1120.11 | 1.00 | 1.50 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 |
| SPLIT MN2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.66 | 736.45 | 1120.11 | 1.00 | 1.50 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 |
| SPLIT MS1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.70 | 780.61 | 1120.11 | 1.00 | 1.48 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 |
| SPLIT MS2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.70 | 778.56 | 1120.11 | 1.00 | 1.48 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 |
| SPLIT TSW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.48 | 535.04 | 1120.11 | 1.00 | 1.63 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 |
| SPLIT TNW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.47 | 527.56 | 1120.11 | 1.00 | 1.63 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 |
| SPLIT TSE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.40 | 450.93 | 1120.11 | 1.00 | 1.71 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 |
| SPLIT TNE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.40 | 443.38 | 1120.11 | 1.00 | 1.72 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 |
| SPLIT TN1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.37 | 416.53 | 1120.11 | 1.00 | 1.76 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 |
| SPLIT TN2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.37 | 413.92 | 1120.11 | 1.00 | 1.76 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 |
| SPLIT TS1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.38 | 425.80 | 1120.11 | 1.00 | 1.74 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 |
| SPLIT TS2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.38 | 423.19 | 1120.11 | 1.00 | 1.75 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 |
| Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
| None |
| Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
| G SW APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.77 |
| G NW APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.77 |
| G NE APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.77 |
| G N1 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.77 |
| G N2 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.77 |
| G S1 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.77 |
| G S2 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.77 |
| M SW APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.79 |
| M NW APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.79 |
| M SE APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.79 |
| M NE APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.79 |
| M N1 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.79 |
| M N2 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.79 |
| M S1 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.79 |
| M S2 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.79 |
| T SW APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.77 |
| T NW APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.77 |
| T SE APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.77 |
| T NE APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.77 |
| T N1 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.77 |
| T N2 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.77 |
| T S1 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.77 |
| T S2 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.77 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 09:14:20
Zone Sensible Cooling| Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
| G SW APARTMENT | 3947.36 | 4736.84 | 53.68 | 0.286 | 0.343 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 24.00 | 24.00 | 0.00833 | 26.67 | 0.01336 | 0.026 | 0.00 |
| G NW APARTMENT | 3713.05 | 4455.66 | 50.49 | 0.268 | 0.322 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 24.00 | 24.00 | 0.00833 | 26.67 | 0.01336 | 0.026 | 0.00 |
| OFFICE | 4311.59 | 5173.91 | 58.63 | 0.317 | 0.380 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 23.90 | 23.90 | 0.00824 | 25.18 | 0.01336 | 0.038 | 0.00 |
| G NE APARTMENT | 3321.93 | 3986.32 | 45.17 | 0.240 | 0.287 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 24.00 | 24.00 | 0.00840 | 26.67 | 0.01336 | 0.026 | 0.00 |
| G N1 APARTMENT | 3048.38 | 3658.05 | 41.45 | 0.219 | 0.263 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 24.00 | 24.00 | 0.00835 | 26.67 | 0.01336 | 0.026 | 0.00 |
| G N2 APARTMENT | 3041.35 | 3649.62 | 41.36 | 0.219 | 0.262 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 24.00 | 24.00 | 0.00835 | 26.67 | 0.01336 | 0.026 | 0.00 |
| G S1 APARTMENT | 3304.58 | 3965.50 | 44.94 | 0.238 | 0.286 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 24.00 | 24.00 | 0.00835 | 26.67 | 0.01336 | 0.026 | 0.00 |
| G S2 APARTMENT | 3325.03 | 3990.04 | 45.21 | 0.240 | 0.288 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 24.00 | 24.00 | 0.00835 | 26.67 | 0.01336 | 0.026 | 0.00 |
| M SW APARTMENT | 9949.27 | 11939.13 | 135.29 | 0.724 | 0.869 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 24.00 | 24.00 | 0.00831 | 26.67 | 0.01336 | 0.052 | 0.00 |
| M NW APARTMENT | 9584.66 | 11501.59 | 130.33 | 0.697 | 0.836 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 24.00 | 24.00 | 0.00831 | 26.67 | 0.01336 | 0.052 | 0.00 |
| M SE APARTMENT | 8783.43 | 10540.12 | 119.44 | 0.638 | 0.765 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 24.00 | 24.00 | 0.00836 | 26.67 | 0.01336 | 0.052 | 0.00 |
| M NE APARTMENT | 8431.01 | 10117.21 | 114.64 | 0.611 | 0.734 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 24.00 | 24.00 | 0.00837 | 26.67 | 0.01336 | 0.052 | 0.00 |
| M N1 APARTMENT | 7594.72 | 9113.66 | 103.27 | 0.549 | 0.659 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 24.00 | 24.00 | 0.00831 | 26.67 | 0.01336 | 0.052 | 0.00 |
| M N2 APARTMENT | 7575.34 | 9090.41 | 103.01 | 0.548 | 0.657 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 24.00 | 24.00 | 0.00832 | 26.67 | 0.01336 | 0.052 | 0.00 |
| M S1 APARTMENT | 8018.45 | 9622.14 | 109.03 | 0.581 | 0.697 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 24.00 | 24.00 | 0.00831 | 26.67 | 0.01336 | 0.052 | 0.00 |
| M S2 APARTMENT | 7998.03 | 9597.64 | 108.76 | 0.579 | 0.695 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 24.00 | 24.00 | 0.00831 | 26.67 | 0.01336 | 0.052 | 0.00 |
| T SW APARTMENT | 5464.22 | 6557.06 | 74.30 | 0.398 | 0.478 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 24.00 | 24.00 | 0.00834 | 26.67 | 0.01336 | 0.026 | 0.00 |
| T NW APARTMENT | 5389.18 | 6467.02 | 73.28 | 0.392 | 0.471 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 24.00 | 24.00 | 0.00833 | 26.67 | 0.01336 | 0.026 | 0.00 |
| T SE APARTMENT | 4619.32 | 5543.19 | 62.81 | 0.335 | 0.403 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 24.00 | 24.00 | 0.00841 | 26.67 | 0.01336 | 0.026 | 0.00 |
| T NE APARTMENT | 4542.78 | 5451.34 | 61.77 | 0.330 | 0.396 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 24.00 | 24.00 | 0.00840 | 26.67 | 0.01336 | 0.026 | 0.00 |
| T N1 APARTMENT | 4273.13 | 5127.75 | 58.11 | 0.310 | 0.372 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 24.00 | 24.00 | 0.00830 | 26.67 | 0.01336 | 0.026 | 0.00 |
| T N2 APARTMENT | 4246.91 | 5096.30 | 57.75 | 0.308 | 0.370 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 24.00 | 24.00 | 0.00830 | 26.67 | 0.01336 | 0.026 | 0.00 |
| T S1 APARTMENT | 4366.66 | 5240.00 | 59.38 | 0.317 | 0.380 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 24.00 | 24.00 | 0.00831 | 26.67 | 0.01336 | 0.026 | 0.00 |
| T S2 APARTMENT | 4340.50 | 5208.60 | 59.02 | 0.315 | 0.378 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 24.00 | 24.00 | 0.00831 | 26.67 | 0.01336 | 0.026 | 0.00 |
| Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
| G SW APARTMENT | 2538.83 | 3046.59 | 34.52 | 0.112 | 0.135 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:50:00 | 21.10 | 21.10 | 0.00738 | -16.30 | 0.00092 | 0.026 | 0.00 |
| G NW APARTMENT | 2416.63 | 2899.95 | 32.86 | 0.107 | 0.128 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 21.10 | 21.10 | 0.00743 | -16.30 | 0.00092 | 0.026 | 0.00 |
| OFFICE | 2988.54 | 3586.25 | 40.64 | 0.132 | 0.159 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 18:50:00 | 21.10 | 21.10 | 0.00747 | -16.30 | 0.00092 | 0.038 | 0.00 |
| G NE APARTMENT | 2407.39 | 2888.87 | 32.74 | 0.106 | 0.128 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 21.10 | 21.10 | 0.00743 | -16.30 | 0.00092 | 0.026 | 0.00 |
| G N1 APARTMENT | 1513.92 | 1816.70 | 20.59 | 0.067 | 0.080 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 21.10 | 21.10 | 0.00751 | -16.30 | 0.00092 | 0.026 | 0.00 |
| G N2 APARTMENT | 1513.65 | 1816.38 | 20.58 | 0.067 | 0.080 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 21.10 | 21.10 | 0.00751 | -16.30 | 0.00092 | 0.026 | 0.00 |
| G S1 APARTMENT | 1637.83 | 1965.40 | 22.27 | 0.072 | 0.087 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:50:00 | 21.10 | 21.10 | 0.00741 | -16.30 | 0.00092 | 0.026 | 0.00 |
| G S2 APARTMENT | 1645.73 | 1974.88 | 22.38 | 0.073 | 0.087 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:50:00 | 21.10 | 21.10 | 0.00741 | -16.30 | 0.00092 | 0.026 | 0.00 |
| M SW APARTMENT | 4526.34 | 5431.61 | 61.55 | 0.200 | 0.240 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 21.10 | 21.10 | 0.00707 | -16.30 | 0.00092 | 0.052 | 0.00 |
| M NW APARTMENT | 4234.42 | 5081.30 | 57.58 | 0.187 | 0.225 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 21.10 | 21.10 | 0.00715 | -16.30 | 0.00092 | 0.052 | 0.00 |
| M SE APARTMENT | 4504.53 | 5405.44 | 61.25 | 0.199 | 0.239 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 21.10 | 21.10 | 0.00707 | -16.30 | 0.00092 | 0.052 | 0.00 |
| M NE APARTMENT | 4212.58 | 5055.09 | 57.28 | 0.186 | 0.223 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 21.10 | 21.10 | 0.00715 | -16.30 | 0.00092 | 0.052 | 0.00 |
| M N1 APARTMENT | 2316.77 | 2780.12 | 31.50 | 0.102 | 0.123 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 21.10 | 21.10 | 0.00717 | -16.30 | 0.00092 | 0.052 | 0.00 |
| M N2 APARTMENT | 2316.21 | 2779.45 | 31.50 | 0.102 | 0.123 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 21.10 | 21.10 | 0.00717 | -16.30 | 0.00092 | 0.052 | 0.00 |
| M S1 APARTMENT | 2602.84 | 3123.40 | 35.39 | 0.115 | 0.138 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 21.10 | 21.10 | 0.00703 | -16.30 | 0.00092 | 0.052 | 0.00 |
| M S2 APARTMENT | 2602.29 | 3122.74 | 35.39 | 0.115 | 0.138 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 21.10 | 21.10 | 0.00703 | -16.30 | 0.00092 | 0.052 | 0.00 |
| T SW APARTMENT | 3729.22 | 4475.07 | 50.71 | 0.165 | 0.198 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 21.10 | 21.10 | 0.00724 | -16.30 | 0.00092 | 0.026 | 0.00 |
| T NW APARTMENT | 3573.64 | 4288.37 | 48.59 | 0.158 | 0.190 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 21.10 | 21.10 | 0.00729 | -16.30 | 0.00092 | 0.026 | 0.00 |
| T SE APARTMENT | 3714.30 | 4457.16 | 50.51 | 0.164 | 0.197 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 21.10 | 21.10 | 0.00724 | -16.30 | 0.00092 | 0.026 | 0.00 |
| T NE APARTMENT | 3558.66 | 4270.40 | 48.39 | 0.157 | 0.189 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 21.10 | 21.10 | 0.00729 | -16.30 | 0.00092 | 0.026 | 0.00 |
| T N1 APARTMENT | 2419.55 | 2903.46 | 32.90 | 0.107 | 0.128 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 21.10 | 21.10 | 0.00741 | -16.30 | 0.00092 | 0.026 | 0.00 |
| T N2 APARTMENT | 2419.15 | 2902.98 | 32.90 | 0.107 | 0.128 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 21.10 | 21.10 | 0.00741 | -16.30 | 0.00092 | 0.026 | 0.00 |
| T S1 APARTMENT | 2575.63 | 3090.76 | 35.02 | 0.114 | 0.137 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 21.10 | 21.10 | 0.00733 | -16.30 | 0.00092 | 0.026 | 0.00 |
| T S2 APARTMENT | 2575.23 | 3090.28 | 35.02 | 0.114 | 0.137 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 21.10 | 21.10 | 0.00733 | -16.30 | 0.00092 | 0.026 | 0.00 |
| Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
| SPLIT GSW | 0.34 | 0.34 | 0.13 | 0.13 | 0.3429 | 0.3429 | 0.3429 | 1.0000 | 1.0000 |
| SPLIT GNW | 0.32 | 0.32 | 0.13 | 0.13 | 0.3222 | 0.3222 | 0.3222 | 1.0000 | 1.0000 |
| SPLIT OFFICE | 0.38 | 0.38 | 0.16 | 0.16 | 0.3804 | 0.3804 | 0.3804 | 1.0000 | 1.0000 |
| SPLIT GNE | 0.29 | 0.29 | 0.13 | 0.13 | 0.2874 | 0.2874 | 0.2874 | 1.0000 | 1.0000 |
| SPLIT GN1 | 0.26 | 0.26 | 0.08 | 0.08 | 0.2630 | 0.2630 | 0.2630 | 1.0000 | 1.0000 |
| SPLIT GN2 | 0.26 | 0.26 | 0.08 | 0.08 | 0.2624 | 0.2624 | 0.2624 | 1.0000 | 1.0000 |
| SPLIT GS1 | 0.29 | 0.29 | 0.09 | 0.09 | 0.2858 | 0.2858 | 0.2858 | 1.0000 | 1.0000 |
| SPLIT GS2 | 0.29 | 0.29 | 0.09 | 0.09 | 0.2877 | 0.2877 | 0.2877 | 1.0000 | 1.0000 |
| SPLIT MSW | 0.87 | 0.87 | 0.24 | 0.24 | 0.8688 | 0.8688 | 0.8688 | 1.0000 | 1.0000 |
| SPLIT MNW | 0.84 | 0.84 | 0.22 | 0.22 | 0.8365 | 0.8365 | 0.8365 | 1.0000 | 1.0000 |
| SPLIT MSE | 0.77 | 0.77 | 0.24 | 0.24 | 0.7652 | 0.7652 | 0.7652 | 1.0000 | 1.0000 |
| SPLIT MNE | 0.73 | 0.73 | 0.22 | 0.22 | 0.7338 | 0.7338 | 0.7338 | 1.0000 | 1.0000 |
| SPLIT MN1 | 0.66 | 0.66 | 0.12 | 0.12 | 0.6592 | 0.6592 | 0.6592 | 1.0000 | 1.0000 |
| SPLIT MN2 | 0.66 | 0.66 | 0.12 | 0.12 | 0.6575 | 0.6575 | 0.6575 | 1.0000 | 1.0000 |
| SPLIT MS1 | 0.70 | 0.70 | 0.14 | 0.14 | 0.6969 | 0.6969 | 0.6969 | 1.0000 | 1.0000 |
| SPLIT MS2 | 0.70 | 0.70 | 0.14 | 0.14 | 0.6951 | 0.6951 | 0.6951 | 1.0000 | 1.0000 |
| SPLIT TSW | 0.48 | 0.48 | 0.20 | 0.20 | 0.4777 | 0.4777 | 0.4777 | 1.0000 | 1.0000 |
| SPLIT TNW | 0.47 | 0.47 | 0.19 | 0.19 | 0.4710 | 0.4710 | 0.4710 | 1.0000 | 1.0000 |
| SPLIT TSE | 0.40 | 0.40 | 0.20 | 0.20 | 0.4026 | 0.4026 | 0.4026 | 1.0000 | 1.0000 |
| SPLIT TNE | 0.40 | 0.40 | 0.19 | 0.19 | 0.3958 | 0.3958 | 0.3958 | 1.0000 | 1.0000 |
| SPLIT TN1 | 0.37 | 0.37 | 0.13 | 0.13 | 0.3719 | 0.3719 | 0.3719 | 1.0000 | 1.0000 |
| SPLIT TN2 | 0.37 | 0.37 | 0.13 | 0.13 | 0.3695 | 0.3695 | 0.3695 | 1.0000 | 1.0000 |
| SPLIT TS1 | 0.38 | 0.38 | 0.14 | 0.14 | 0.3801 | 0.3801 | 0.3801 | 1.0000 | 1.0000 |
| SPLIT TS2 | 0.38 | 0.38 | 0.14 | 0.14 | 0.3778 | 0.3778 | 0.3778 | 1.0000 | 1.0000 |
| Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
| None |
| Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
| SPLIT GSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT GSW | 5716.918 | 4573.857 | 0.342918 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 5658.09 | 5053.64 | 0.342918 | 25.17 | 16.72 | 0.00871129 | 12.80 | 11.37 | 0.00800000 | 26.67 | 0.01336053 | 20.77 | 7.5687 | 24.00 | 0.00833059 | 43.7320 | 3947.36 | 0.00 | 5715.94 | 4509.14 |
| SPLIT GSW HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT GSW | 8790.724 | 8790.724 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:50:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:50:00 | 8790.72 | 8790.72 | 0.342918 | 18.27 | 12.51 | 0.00689539 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 7.5687 | 21.10 | 0.00738435 | 46.3026 | 2538.83 | 0.00 | -999.00 | -999.00 |
| SPLIT GNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT GNW | 5396.966 | 4319.191 | 0.322168 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 5344.46 | 4753.47 | 0.322168 | 25.18 | 16.74 | 0.00873970 | 12.80 | 11.37 | 0.00800000 | 26.67 | 0.01336053 | 20.77 | 8.0562 | 24.00 | 0.00833482 | 43.7538 | 3713.05 | 0.00 | 5396.05 | 4258.09 |
| SPLIT GNW HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT GNW | 8328.053 | 8328.053 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 8328.05 | 8328.05 | 0.322168 | 18.09 | 12.45 | 0.00691003 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 8.0562 | 21.10 | 0.00743452 | 46.6123 | 2416.63 | 0.00 | -999.00 | -999.00 |
| SPLIT OFFICE COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT OFFICE | 6296.228 | 5041.108 | 0.380355 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 6271.22 | 5558.03 | 0.380355 | 25.01 | 16.70 | 0.00875463 | 12.80 | 11.37 | 0.00800000 | 25.18 | 0.01335791 | 20.33 | 10.0185 | 23.90 | 0.00824210 | 43.5359 | 4311.59 | 0.00 | 6295.16 | 4969.17 |
| SPLIT OFFICE HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT OFFICE | 10161.512 | 10161.512 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 18:50:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 18:50:00 | 10161.51 | 10161.51 | 0.380355 | 17.35 | 12.06 | 0.00681701 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 10.0185 | 21.10 | 0.00747312 | 46.8527 | 2988.54 | 0.00 | -999.00 | -999.00 |
| SPLIT GNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT GNE | 4899.834 | 3924.685 | 0.287407 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 4862.25 | 4256.08 | 0.287407 | 25.20 | 16.84 | 0.00884817 | 12.80 | 11.37 | 0.00800000 | 26.67 | 0.01336053 | 20.77 | 9.0306 | 24.00 | 0.00840023 | 44.0928 | 3321.93 | 0.00 | 4899.00 | 3869.11 |
| SPLIT GNE HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT GNE | 7553.019 | 7553.019 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 7553.02 | 7553.02 | 0.287407 | 17.72 | 12.24 | 0.00684481 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 9.0306 | 21.10 | 0.00743256 | 46.6001 | 2407.39 | 0.00 | -999.00 | -999.00 |
| SPLIT GN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT GN1 | 4486.351 | 3592.700 | 0.263023 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 4452.23 | 3898.77 | 0.263023 | 25.21 | 16.84 | 0.00884616 | 12.80 | 11.37 | 0.00800000 | 26.67 | 0.01336053 | 20.77 | 9.8678 | 24.00 | 0.00835193 | 43.8422 | 3048.38 | 0.00 | 4485.59 | 3541.88 |
| SPLIT GN1 HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT GN1 | 7009.278 | 7009.278 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 7009.28 | 7009.28 | 0.263023 | 17.41 | 12.13 | 0.00686165 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 9.8678 | 21.10 | 0.00751170 | 47.0891 | 1513.92 | 0.00 | -999.00 | -999.00 |
| SPLIT GN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT GN2 | 4477.268 | 3584.884 | 0.262402 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 4443.40 | 3889.83 | 0.262402 | 25.21 | 16.84 | 0.00884829 | 12.80 | 11.37 | 0.00800000 | 26.67 | 0.01336053 | 20.77 | 9.8912 | 24.00 | 0.00835299 | 43.8477 | 3041.35 | 0.00 | 4476.51 | 3534.21 |
| SPLIT GN2 HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT GN2 | 6995.418 | 6995.418 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 6995.42 | 6995.42 | 0.262402 | 17.40 | 12.12 | 0.00686004 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 9.8912 | 21.10 | 0.00751162 | 47.0887 | 1513.65 | 0.00 | -999.00 | -999.00 |
| SPLIT GS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT GS1 | 4842.714 | 3875.249 | 0.285838 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 4802.01 | 4229.51 | 0.285838 | 25.20 | 16.80 | 0.00880624 | 12.80 | 11.37 | 0.00800000 | 26.67 | 0.01336053 | 20.77 | 9.0801 | 24.00 | 0.00835140 | 43.8396 | 3304.58 | 0.00 | 4841.89 | 3820.61 |
| SPLIT GS1 HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT GS1 | 7517.990 | 7517.990 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:50:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:50:00 | 7517.99 | 7517.99 | 0.285838 | 17.70 | 12.21 | 0.00682010 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 9.0801 | 21.10 | 0.00740893 | 46.4535 | 1637.83 | 0.00 | -999.00 | -999.00 |
| SPLIT GS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT GS2 | 4869.889 | 3898.359 | 0.287666 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 4828.51 | 4255.69 | 0.287666 | 25.20 | 16.80 | 0.00880166 | 12.80 | 11.37 | 0.00800000 | 26.67 | 0.01336053 | 20.77 | 9.0224 | 24.00 | 0.00834955 | 43.8300 | 3325.03 | 0.00 | 4869.06 | 3843.28 |
| SPLIT GS2 HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT GS2 | 7558.748 | 7558.748 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:50:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:50:00 | 7558.75 | 7558.75 | 0.287666 | 17.73 | 12.22 | 0.00682627 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 9.0224 | 21.10 | 0.00741160 | 46.4701 | 1645.73 | 0.00 | -999.00 | -999.00 |
| SPLIT MSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT MSW | 14381.855 | 11514.908 | 0.868808 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 14203.96 | 12883.79 | 0.868808 | 25.15 | 16.62 | 0.00860821 | 12.80 | 11.37 | 0.00800000 | 26.67 | 0.01336053 | 20.77 | 5.9748 | 24.00 | 0.00830623 | 43.6059 | 19898.55 | 0.00 | 14379.41 | 11350.60 |
| SPLIT MSW HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT MSW | 21662.341 | 21662.341 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 21662.34 | 21662.34 | 0.868808 | 18.86 | 12.56 | 0.00670733 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 5.9748 | 21.10 | 0.00707482 | 44.3859 | 9052.69 | 0.00 | -999.00 | -999.00 |
| SPLIT MNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT MNW | 13846.926 | 11086.614 | 0.836493 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 13679.02 | 12385.04 | 0.836493 | 25.15 | 16.63 | 0.00862029 | 12.80 | 11.37 | 0.00800000 | 26.67 | 0.01336053 | 20.77 | 6.2056 | 24.00 | 0.00830667 | 43.6081 | 19169.31 | 0.00 | 13844.57 | 10928.41 |
| SPLIT MNW HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT MNW | 20941.521 | 20941.521 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 20941.52 | 20941.52 | 0.836493 | 18.78 | 12.59 | 0.00676495 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 6.2056 | 21.10 | 0.00715139 | 44.8600 | 8468.83 | 0.00 | -999.00 | -999.00 |
| SPLIT MSE COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT MSE | 12729.016 | 10193.995 | 0.765178 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 12594.75 | 11261.83 | 0.765178 | 25.16 | 16.71 | 0.00870318 | 12.80 | 11.37 | 0.00800000 | 26.67 | 0.01336053 | 20.77 | 6.7839 | 24.00 | 0.00836423 | 43.9065 | 17566.87 | 0.00 | 12726.85 | 10048.75 |
| SPLIT MSE HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT MSE | 19351.641 | 19351.641 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 19351.64 | 19351.64 | 0.765178 | 18.56 | 12.39 | 0.00665392 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 6.7839 | 21.10 | 0.00707092 | 44.3617 | 9009.07 | 0.00 | -999.00 | -999.00 |
| SPLIT MNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT MNE | 12243.995 | 9804.157 | 0.733778 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 12119.19 | 10808.40 | 0.733778 | 25.16 | 16.72 | 0.00872075 | 12.80 | 11.37 | 0.00800000 | 26.67 | 0.01336053 | 20.77 | 7.0742 | 24.00 | 0.00836753 | 43.9236 | 16862.01 | 0.00 | 12241.91 | 9664.80 |
| SPLIT MNE HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT MNE | 18651.269 | 18651.269 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 18651.27 | 18651.27 | 0.733778 | 18.45 | 12.40 | 0.00670733 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 7.0742 | 21.10 | 0.00714759 | 44.8365 | 8425.16 | 0.00 | -999.00 | -999.00 |
| SPLIT MN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT MN1 | 10993.525 | 8805.025 | 0.659193 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 10880.87 | 9718.32 | 0.659193 | 25.18 | 16.72 | 0.00871164 | 12.80 | 11.37 | 0.00800000 | 26.67 | 0.01336053 | 20.77 | 7.8746 | 24.00 | 0.00831426 | 43.6471 | 15189.43 | 0.00 | 10991.65 | 8679.66 |
| SPLIT MN1 HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT MN1 | 16987.625 | 16987.625 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 16987.62 | 16987.62 | 0.659193 | 18.15 | 12.25 | 0.00667655 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 7.8746 | 21.10 | 0.00716826 | 44.9623 | 4633.54 | 0.00 | -999.00 | -999.00 |
| SPLIT MN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT MN2 | 10968.713 | 8783.779 | 0.657479 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 10856.74 | 9693.76 | 0.657479 | 25.18 | 16.72 | 0.00871372 | 12.80 | 11.37 | 0.00800000 | 26.67 | 0.01336053 | 20.77 | 7.8952 | 24.00 | 0.00831540 | 43.6530 | 15150.69 | 0.00 | 10966.85 | 8658.85 |
| SPLIT MN2 HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT MN2 | 16949.421 | 16949.421 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 16949.42 | 16949.42 | 0.657479 | 18.15 | 12.24 | 0.00667511 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 7.8952 | 21.10 | 0.00716808 | 44.9612 | 4632.42 | 0.00 | -999.00 | -999.00 |
| SPLIT MS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT MS1 | 11571.118 | 9263.222 | 0.696904 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 11446.60 | 10262.64 | 0.696904 | 25.17 | 16.70 | 0.00868600 | 12.80 | 11.37 | 0.00800000 | 26.67 | 0.01336053 | 20.77 | 7.4485 | 24.00 | 0.00830979 | 43.6240 | 16036.90 | 0.00 | 11569.15 | 9131.39 |
| SPLIT MS1 HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT MS1 | 17828.680 | 17828.680 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 17828.68 | 17828.68 | 0.696904 | 18.31 | 12.21 | 0.00657732 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 7.4485 | 21.10 | 0.00703229 | 44.1199 | 5205.67 | 0.00 | -999.00 | -999.00 |
| SPLIT MS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT MS2 | 11544.947 | 9240.755 | 0.695079 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 11421.19 | 10236.60 | 0.695079 | 25.17 | 16.70 | 0.00868813 | 12.80 | 11.37 | 0.00800000 | 26.67 | 0.01336053 | 20.77 | 7.4681 | 24.00 | 0.00831103 | 43.6304 | 15996.07 | 0.00 | 11542.98 | 9109.40 |
| SPLIT MS2 HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT MS2 | 17787.981 | 17787.981 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 17787.98 | 17787.98 | 0.695079 | 18.31 | 12.21 | 0.00657596 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 7.4681 | 21.10 | 0.00703211 | 44.1188 | 5204.57 | 0.00 | -999.00 | -999.00 |
| SPLIT TSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT TSW | 7907.054 | 6330.825 | 0.477665 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 7808.87 | 7082.61 | 0.477665 | 25.14 | 16.62 | 0.00860837 | 12.80 | 11.37 | 0.00800000 | 26.67 | 0.01336053 | 20.77 | 5.4336 | 24.00 | 0.00833532 | 43.7570 | 5464.22 | 0.00 | 7905.71 | 6240.49 |
| SPLIT TSW HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT TSW | 11796.213 | 11796.213 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 11796.21 | 11796.21 | 0.477665 | 19.06 | 12.83 | 0.00689499 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 5.4336 | 21.10 | 0.00723807 | 45.4005 | 3729.22 | 0.00 | -999.00 | -999.00 |
| SPLIT TNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT TNW | 7796.611 | 6242.397 | 0.470993 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 7699.56 | 6986.01 | 0.470993 | 25.14 | 16.62 | 0.00860605 | 12.80 | 11.37 | 0.00800000 | 26.67 | 0.01336053 | 20.77 | 5.5106 | 24.00 | 0.00832877 | 43.7230 | 5389.18 | 0.00 | 7795.28 | 6153.32 |
| SPLIT TNW HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT TNW | 11647.281 | 11647.281 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 11647.28 | 11647.28 | 0.470993 | 19.04 | 12.86 | 0.00693805 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 5.5106 | 21.10 | 0.00728878 | 45.7141 | 3573.64 | 0.00 | -999.00 | -999.00 |
| SPLIT TSE COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT TSE | 6719.994 | 5380.017 | 0.402580 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 6651.76 | 5927.79 | 0.402580 | 25.16 | 16.72 | 0.00872553 | 12.80 | 11.37 | 0.00800000 | 26.67 | 0.01336053 | 20.77 | 6.4471 | 24.00 | 0.00840612 | 44.1238 | 4619.32 | 0.00 | 6718.85 | 5303.63 |
| SPLIT TSE HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT TSE | 10121.915 | 10121.915 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 10121.91 | 10121.91 | 0.402580 | 18.69 | 12.61 | 0.00682845 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 6.4471 | 21.10 | 0.00723534 | 45.3836 | 3714.30 | 0.00 | -999.00 | -999.00 |
| SPLIT TNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT TNE | 6606.841 | 5289.659 | 0.395839 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 6539.68 | 5828.88 | 0.395839 | 25.16 | 16.72 | 0.00872448 | 12.80 | 11.37 | 0.00800000 | 26.67 | 0.01336053 | 20.77 | 6.5568 | 24.00 | 0.00839917 | 44.0878 | 4542.78 | 0.00 | 6605.72 | 5214.53 |
| SPLIT TNE HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT TNE | 9971.477 | 9971.477 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 9971.48 | 9971.48 | 0.395839 | 18.65 | 12.63 | 0.00686897 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 6.5568 | 21.10 | 0.00728612 | 45.6976 | 3558.66 | 0.00 | -999.00 | -999.00 |
| SPLIT TN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT TN1 | 6155.710 | 4928.602 | 0.371866 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 6085.37 | 5484.47 | 0.371866 | 25.17 | 16.66 | 0.00865128 | 12.80 | 11.37 | 0.00800000 | 26.67 | 0.01336053 | 20.77 | 6.9795 | 24.00 | 0.00829793 | 43.5626 | 4273.13 | 0.00 | 6154.66 | 4858.27 |
| SPLIT TN1 HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT TN1 | 9436.476 | 9436.476 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 9436.48 | 9436.48 | 0.371866 | 18.49 | 12.65 | 0.00695354 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 6.9795 | 21.10 | 0.00740595 | 46.4371 | 2419.55 | 0.00 | -999.00 | -999.00 |
| SPLIT TN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT TN2 | 6117.088 | 4897.679 | 0.369533 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 6047.71 | 5446.94 | 0.369533 | 25.17 | 16.67 | 0.00865565 | 12.80 | 11.37 | 0.00800000 | 26.67 | 0.01336053 | 20.77 | 7.0236 | 24.00 | 0.00830024 | 43.5745 | 4246.91 | 0.00 | 6116.05 | 4827.79 |
| SPLIT TN2 HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT TN2 | 9384.453 | 9384.453 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 9384.45 | 9384.45 | 0.369533 | 18.47 | 12.64 | 0.00695060 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 7.0236 | 21.10 | 0.00740586 | 46.4365 | 2419.15 | 0.00 | -999.00 | -999.00 |
| SPLIT TS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT TS1 | 6292.706 | 5038.288 | 0.380142 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 6220.78 | 5605.82 | 0.380142 | 25.17 | 16.66 | 0.00865200 | 12.80 | 11.37 | 0.00800000 | 26.67 | 0.01336053 | 20.77 | 6.8276 | 24.00 | 0.00830697 | 43.6095 | 4366.66 | 0.00 | 6291.63 | 4966.39 |
| SPLIT TS1 HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT TS1 | 9621.135 | 9621.135 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 9621.14 | 9621.14 | 0.380142 | 18.54 | 12.61 | 0.00688809 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 6.8276 | 21.10 | 0.00732513 | 45.9371 | 2575.63 | 0.00 | -999.00 | -999.00 |
| SPLIT TS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT TS2 | 6254.196 | 5007.455 | 0.377816 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 6183.24 | 5568.37 | 0.377816 | 25.17 | 16.67 | 0.00865632 | 12.80 | 11.37 | 0.00800000 | 26.67 | 0.01336053 | 20.77 | 6.8696 | 24.00 | 0.00830932 | 43.6216 | 4340.50 | 0.00 | 6253.13 | 4936.00 |
| SPLIT TS2 HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT TS2 | 9569.264 | 9569.264 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 9569.26 | 9569.26 | 0.377816 | 18.53 | 12.60 | 0.00688531 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 6.8696 | 21.10 | 0.00732503 | 45.9365 | 2575.23 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 09:14:20
Coils| Coil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
| SPLIT GSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT GSW | G SW APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 5716.918 | 4573.857 | 0.342918 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.0339 | 1004.8586 | 1.1739 | SPLIT GSW SUPPLY FAN | Fan:OnOff | 0.342918 | 0.40255997 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | Sensible | 5658.09 | 5053.64 | 0.9897 | 0.40255997 | 0.342918 | 25.17 | 16.72 | 0.00871129 | 47490.5 | 12.80 | 11.37 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 384.105 | 5273.98 | 26.67 | 0.01336053 | 20.77 | 0.02595455 | 7.5687 | 24.04 | 0.00833059 | 24.00 | 0.00833059 | 43.7320 | 3947.36 | 0.00 | 5715.94 | 4509.14 | 0.38666189 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 15.27 | 14.48 | 0.00996096 | 40539.6 | |
| SPLIT GSW HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT GSW | G SW APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 8790.724 | 8790.724 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | SPLIT GSW SUPPLY FAN | Fan:OnOff | 0.342918 | 0.40255997 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:50:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:50:00 | Sensible | 8790.72 | 8790.72 | 1.0000 | 0.40255997 | 0.342918 | 18.27 | 12.51 | 0.00689539 | 35836.1 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8790.72 | -16.30 | 0.00092409 | -16.30 | 0.02595455 | 7.5687 | 21.10 | 0.00738435 | 21.10 | 0.00738435 | 46.3026 | 2538.83 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT GNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT GNW | G NW APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 5396.966 | 4319.191 | 0.322168 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.0867 | 1004.8586 | 1.1739 | SPLIT GNW SUPPLY FAN | Fan:OnOff | 0.322168 | 0.37820155 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | Sensible | 5344.46 | 4753.47 | 0.9903 | 0.37820155 | 0.322168 | 25.18 | 16.74 | 0.00873970 | 47569.6 | 12.80 | 11.37 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 360.863 | 4983.59 | 26.67 | 0.01336053 | 20.77 | 0.02595455 | 8.0562 | 24.03 | 0.00833482 | 24.00 | 0.00833482 | 43.7538 | 3713.05 | 0.00 | 5396.05 | 4258.09 | 0.36326545 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 15.21 | 14.45 | 0.00995645 | 40468.1 | |
| SPLIT GNW HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT GNW | G NW APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 8328.053 | 8328.053 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | SPLIT GNW SUPPLY FAN | Fan:OnOff | 0.322168 | 0.37820155 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | Sensible | 8328.05 | 8328.05 | 1.0000 | 0.37820155 | 0.322168 | 18.09 | 12.45 | 0.00691003 | 35687.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8328.05 | -16.30 | 0.00092409 | -16.30 | 0.02595455 | 8.0562 | 21.10 | 0.00743452 | 21.10 | 0.00743452 | 46.6123 | 2416.63 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT OFFICE COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT OFFICE | OFFICE | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 6296.228 | 5041.108 | 0.380355 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.1144 | 1004.8586 | 1.1739 | SPLIT OFFICE SUPPLY FAN | Fan:OnOff | 0.380355 | 0.44650850 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | Sensible | 6271.22 | 5558.03 | 0.9960 | 0.44650850 | 0.380355 | 25.01 | 16.70 | 0.00875463 | 47430.8 | 12.80 | 11.37 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 426.039 | 5845.18 | 25.18 | 0.01335791 | 20.33 | 0.03810604 | 10.0185 | 23.95 | 0.00824210 | 23.90 | 0.00824210 | 43.5359 | 4311.59 | 0.00 | 6295.16 | 4969.17 | 0.42887479 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 15.34 | 14.52 | 0.00997245 | 40644.1 | |
| SPLIT OFFICE HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT OFFICE | OFFICE | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 10161.512 | 10161.512 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | SPLIT OFFICE SUPPLY FAN | Fan:OnOff | 0.380355 | 0.44650850 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 18:50:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 18:50:00 | Sensible | 10161.51 | 10161.51 | 1.0000 | 0.44650850 | 0.380355 | 17.35 | 12.06 | 0.00681701 | 34705.1 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10161.51 | -16.30 | 0.00092409 | -16.30 | 0.03810604 | 10.0185 | 21.10 | 0.00747312 | 21.10 | 0.00747312 | 46.8527 | 2988.54 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT GNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT GNE | G NE APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 4899.834 | 3924.685 | 0.287407 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.2883 | 1004.8586 | 1.1739 | SPLIT GNE SUPPLY FAN | Fan:OnOff | 0.287407 | 0.33739423 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | Sensible | 4862.25 | 4256.08 | 0.9923 | 0.33739423 | 0.287407 | 25.20 | 16.84 | 0.00884817 | 47860.6 | 12.80 | 11.37 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 321.927 | 4540.32 | 26.67 | 0.01336053 | 20.77 | 0.02595455 | 9.0306 | 24.02 | 0.00840023 | 24.00 | 0.00840023 | 44.0928 | 3321.93 | 0.00 | 4899.00 | 3869.11 | 0.32406971 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 15.00 | 14.35 | 0.00993864 | 40205.3 | |
| SPLIT GNE HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT GNE | G NE APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 7553.019 | 7553.019 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | SPLIT GNE SUPPLY FAN | Fan:OnOff | 0.287407 | 0.33739423 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | Sensible | 7553.02 | 7553.02 | 1.0000 | 0.33739423 | 0.287407 | 17.72 | 12.24 | 0.00684481 | 35151.6 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 7553.02 | -16.30 | 0.00092409 | -16.30 | 0.02595455 | 9.0306 | 21.10 | 0.00743256 | 21.10 | 0.00743256 | 46.6001 | 2407.39 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT GN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT GN1 | G N1 APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 4486.351 | 3592.700 | 0.263023 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.2846 | 1004.8586 | 1.1739 | SPLIT GN1 SUPPLY FAN | Fan:OnOff | 0.263023 | 0.30876975 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | Sensible | 4452.23 | 3898.77 | 0.9924 | 0.30876975 | 0.263023 | 25.21 | 16.84 | 0.00884616 | 47869.5 | 12.80 | 11.37 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 294.615 | 4157.62 | 26.67 | 0.01336053 | 20.77 | 0.02595455 | 9.8678 | 24.01 | 0.00835193 | 24.00 | 0.00835193 | 43.8422 | 3048.38 | 0.00 | 4485.59 | 3541.88 | 0.29657568 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 15.00 | 14.35 | 0.00993706 | 40197.8 | |
| SPLIT GN1 HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT GN1 | G N1 APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 7009.278 | 7009.278 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | SPLIT GN1 SUPPLY FAN | Fan:OnOff | 0.263023 | 0.30876975 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | Sensible | 7009.28 | 7009.28 | 1.0000 | 0.30876975 | 0.263023 | 17.41 | 12.13 | 0.00686165 | 34876.0 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 7009.28 | -16.30 | 0.00092409 | -16.30 | 0.02595455 | 9.8678 | 21.10 | 0.00751170 | 21.10 | 0.00751170 | 47.0891 | 1513.92 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT GN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT GN2 | G N2 APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 4477.268 | 3584.884 | 0.262402 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.2885 | 1004.8586 | 1.1739 | SPLIT GN2 SUPPLY FAN | Fan:OnOff | 0.262402 | 0.30804000 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | Sensible | 4443.40 | 3889.83 | 0.9924 | 0.30804000 | 0.262402 | 25.21 | 16.84 | 0.00884829 | 47875.2 | 12.80 | 11.37 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 293.918 | 4149.48 | 26.67 | 0.01336053 | 20.77 | 0.02595455 | 9.8912 | 24.01 | 0.00835299 | 24.00 | 0.00835299 | 43.8477 | 3041.35 | 0.00 | 4476.51 | 3534.21 | 0.29587475 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.99 | 14.35 | 0.00993598 | 40192.7 | |
| SPLIT GN2 HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT GN2 | G N2 APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 6995.418 | 6995.418 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | SPLIT GN2 SUPPLY FAN | Fan:OnOff | 0.262402 | 0.30804000 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | Sensible | 6995.42 | 6995.42 | 1.0000 | 0.30804000 | 0.262402 | 17.40 | 12.12 | 0.00686004 | 34863.0 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 6995.42 | -16.30 | 0.00092409 | -16.30 | 0.02595455 | 9.8912 | 21.10 | 0.00751162 | 21.10 | 0.00751162 | 47.0887 | 1513.65 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT GS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT GS1 | G S1 APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 4842.714 | 3875.249 | 0.285838 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.2104 | 1004.8586 | 1.1739 | SPLIT GS1 SUPPLY FAN | Fan:OnOff | 0.285838 | 0.33555290 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | Sensible | 4802.01 | 4229.51 | 0.9916 | 0.33555290 | 0.285838 | 25.20 | 16.80 | 0.00880624 | 47756.5 | 12.80 | 11.37 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 320.170 | 4481.84 | 26.67 | 0.01336053 | 20.77 | 0.02595455 | 9.0801 | 24.02 | 0.00835140 | 24.00 | 0.00835140 | 43.8396 | 3304.58 | 0.00 | 4841.89 | 3820.61 | 0.32230110 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 15.08 | 14.39 | 0.00994228 | 40299.5 | |
| SPLIT GS1 HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT GS1 | G S1 APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 7517.990 | 7517.990 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | SPLIT GS1 SUPPLY FAN | Fan:OnOff | 0.285838 | 0.33555290 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:50:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:50:00 | Sensible | 7517.99 | 7517.99 | 1.0000 | 0.33555290 | 0.285838 | 17.70 | 12.21 | 0.00682010 | 35070.3 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 7517.99 | -16.30 | 0.00092409 | -16.30 | 0.02595455 | 9.0801 | 21.10 | 0.00740893 | 21.10 | 0.00740893 | 46.4535 | 1637.83 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT GS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT GS2 | G S2 APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 4869.889 | 3898.359 | 0.287666 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.2018 | 1004.8586 | 1.1739 | SPLIT GS2 SUPPLY FAN | Fan:OnOff | 0.287666 | 0.33769889 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | Sensible | 4828.51 | 4255.69 | 0.9915 | 0.33769889 | 0.287666 | 25.20 | 16.80 | 0.00880166 | 47743.5 | 12.80 | 11.37 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 322.217 | 4506.29 | 26.67 | 0.01336053 | 20.77 | 0.02595455 | 9.0224 | 24.02 | 0.00834955 | 24.00 | 0.00834955 | 43.8300 | 3325.03 | 0.00 | 4869.06 | 3843.28 | 0.32436234 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 15.09 | 14.39 | 0.00994474 | 40311.2 | |
| SPLIT GS2 HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT GS2 | G S2 APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 7558.748 | 7558.748 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | SPLIT GS2 SUPPLY FAN | Fan:OnOff | 0.287666 | 0.33769889 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:50:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:50:00 | Sensible | 7558.75 | 7558.75 | 1.0000 | 0.33769889 | 0.287666 | 17.73 | 12.22 | 0.00682627 | 35107.9 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 7558.75 | -16.30 | 0.00092409 | -16.30 | 0.02595455 | 9.0224 | 21.10 | 0.00741160 | 21.10 | 0.00741160 | 46.4701 | 1645.73 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT MSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT MSW | M SW APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 14381.855 | 11514.908 | 0.868808 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.8422 | 1004.8586 | 1.1739 | SPLIT MSW SUPPLY FAN | Fan:OnOff | 0.868808 | 1.01991555 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | Sensible | 14203.96 | 12883.79 | 0.9876 | 1.01991555 | 0.868808 | 25.15 | 16.62 | 0.00860821 | 47198.6 | 12.80 | 11.37 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 973.159 | 13230.80 | 26.67 | 0.01336053 | 20.77 | 0.05190911 | 5.9748 | 24.05 | 0.00830623 | 24.00 | 0.00830623 | 43.6059 | 19898.55 | 0.00 | 14379.41 | 11350.60 | 0.97963660 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 15.34 | 14.52 | 0.00997245 | 40644.1 | |
| SPLIT MSW HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT MSW | M SW APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 21662.341 | 21662.341 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | SPLIT MSW SUPPLY FAN | Fan:OnOff | 0.868808 | 1.01991555 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | Sensible | 21662.34 | 21662.34 | 1.0000 | 1.01991555 | 0.868808 | 18.86 | 12.56 | 0.00670733 | 35964.5 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 21662.34 | -16.30 | 0.00092409 | -16.30 | 0.05190911 | 5.9748 | 21.10 | 0.00707482 | 21.10 | 0.00707482 | 44.3859 | 9052.69 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT MNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT MNW | M NW APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 13846.926 | 11086.614 | 0.836493 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.8647 | 1004.8586 | 1.1739 | SPLIT MNW SUPPLY FAN | Fan:OnOff | 0.836493 | 0.98198008 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | Sensible | 13679.02 | 12385.04 | 0.9879 | 0.98198008 | 0.836493 | 25.15 | 16.63 | 0.00862029 | 47232.8 | 12.80 | 11.37 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 936.962 | 12742.06 | 26.67 | 0.01336053 | 20.77 | 0.05190911 | 6.2056 | 24.05 | 0.00830667 | 24.00 | 0.00830667 | 43.6081 | 19169.31 | 0.00 | 13844.57 | 10928.41 | 0.94319929 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 15.34 | 14.52 | 0.00997245 | 40644.1 | |
| SPLIT MNW HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT MNW | M NW APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 20941.521 | 20941.521 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | SPLIT MNW SUPPLY FAN | Fan:OnOff | 0.836493 | 0.98198008 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | Sensible | 20941.52 | 20941.52 | 1.0000 | 0.98198008 | 0.836493 | 18.78 | 12.59 | 0.00676495 | 36023.1 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 20941.52 | -16.30 | 0.00092409 | -16.30 | 0.05190911 | 6.2056 | 21.10 | 0.00715139 | 21.10 | 0.00715139 | 44.8600 | 8468.83 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT MSE COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT MSE | M SE APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 12729.016 | 10193.995 | 0.765178 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.0188 | 1004.8586 | 1.1739 | SPLIT MSE SUPPLY FAN | Fan:OnOff | 0.765178 | 0.89826174 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | Sensible | 12594.75 | 11261.83 | 0.9895 | 0.89826174 | 0.765178 | 25.16 | 16.71 | 0.00870318 | 47454.7 | 12.80 | 11.37 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 857.082 | 11737.67 | 26.67 | 0.01336053 | 20.77 | 0.05190911 | 6.7839 | 24.05 | 0.00836423 | 24.00 | 0.00836423 | 43.9065 | 17566.87 | 0.00 | 12726.85 | 10048.75 | 0.86278720 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 15.29 | 14.49 | 0.00996765 | 40571.5 | |
| SPLIT MSE HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT MSE | M SE APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 19351.641 | 19351.641 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | SPLIT MSE SUPPLY FAN | Fan:OnOff | 0.765178 | 0.89826174 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | Sensible | 19351.64 | 19351.64 | 1.0000 | 0.89826174 | 0.765178 | 18.56 | 12.39 | 0.00665392 | 35521.2 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 19351.64 | -16.30 | 0.00092409 | -16.30 | 0.05190911 | 6.7839 | 21.10 | 0.00707092 | 21.10 | 0.00707092 | 44.3617 | 9009.07 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT MNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT MNE | M NE APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 12243.995 | 9804.157 | 0.733778 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.0514 | 1004.8586 | 1.1739 | SPLIT MNE SUPPLY FAN | Fan:OnOff | 0.733778 | 0.86140101 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | Sensible | 12119.19 | 10808.40 | 0.9898 | 0.86140101 | 0.733778 | 25.16 | 16.72 | 0.00872075 | 47504.6 | 12.80 | 11.37 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 821.911 | 11297.28 | 26.67 | 0.01336053 | 20.77 | 0.05190911 | 7.0742 | 24.04 | 0.00836753 | 24.00 | 0.00836753 | 43.9236 | 16862.01 | 0.00 | 12241.91 | 9664.80 | 0.82738218 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 15.25 | 14.47 | 0.00996343 | 40526.4 | |
| SPLIT MNE HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT MNE | M NE APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 18651.269 | 18651.269 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | SPLIT MNE SUPPLY FAN | Fan:OnOff | 0.733778 | 0.86140101 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | Sensible | 18651.27 | 18651.27 | 1.0000 | 0.86140101 | 0.733778 | 18.45 | 12.40 | 0.00670733 | 35546.5 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 18651.27 | -16.30 | 0.00092409 | -16.30 | 0.05190911 | 7.0742 | 21.10 | 0.00714759 | 21.10 | 0.00714759 | 44.8365 | 8425.16 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT MN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT MN1 | M N1 APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 10993.525 | 8805.025 | 0.659193 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.0345 | 1004.8586 | 1.1739 | SPLIT MN1 SUPPLY FAN | Fan:OnOff | 0.659193 | 0.77384319 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | Sensible | 10880.87 | 9718.32 | 0.9898 | 0.77384319 | 0.659193 | 25.18 | 16.72 | 0.00871164 | 47496.5 | 12.80 | 11.37 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 738.367 | 10142.50 | 26.67 | 0.01336053 | 20.77 | 0.05190911 | 7.8746 | 24.04 | 0.00831426 | 24.00 | 0.00831426 | 43.6471 | 15189.43 | 0.00 | 10991.65 | 8679.66 | 0.74328223 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 15.26 | 14.48 | 0.00996510 | 40534.4 | |
| SPLIT MN1 HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT MN1 | M N1 APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 16987.625 | 16987.625 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | SPLIT MN1 SUPPLY FAN | Fan:OnOff | 0.659193 | 0.77384319 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | Sensible | 16987.62 | 16987.62 | 1.0000 | 0.77384319 | 0.659193 | 18.15 | 12.25 | 0.00667655 | 35164.7 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 16987.62 | -16.30 | 0.00092409 | -16.30 | 0.05190911 | 7.8746 | 21.10 | 0.00716826 | 21.10 | 0.00716826 | 44.9623 | 4633.54 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT MN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT MN2 | M N2 APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 10968.713 | 8783.779 | 0.657479 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.0384 | 1004.8586 | 1.1739 | SPLIT MN2 SUPPLY FAN | Fan:OnOff | 0.657479 | 0.77183174 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | Sensible | 10856.74 | 9693.76 | 0.9898 | 0.77183174 | 0.657479 | 25.18 | 16.72 | 0.00871372 | 47502.1 | 12.80 | 11.37 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 736.448 | 10120.30 | 26.67 | 0.01336053 | 20.77 | 0.05190911 | 7.8952 | 24.04 | 0.00831540 | 24.00 | 0.00831540 | 43.6530 | 15150.69 | 0.00 | 10966.85 | 8658.85 | 0.74135022 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 15.25 | 14.47 | 0.00996403 | 40529.3 | |
| SPLIT MN2 HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT MN2 | M N2 APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 16949.421 | 16949.421 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | SPLIT MN2 SUPPLY FAN | Fan:OnOff | 0.657479 | 0.77183174 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | Sensible | 16949.42 | 16949.42 | 1.0000 | 0.77183174 | 0.657479 | 18.15 | 12.24 | 0.00667511 | 35153.2 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 16949.42 | -16.30 | 0.00092409 | -16.30 | 0.05190911 | 7.8952 | 21.10 | 0.00716808 | 21.10 | 0.00716808 | 44.9612 | 4632.42 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT MS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT MS1 | M S1 APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 11571.118 | 9263.222 | 0.696904 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.9868 | 1004.8586 | 1.1739 | SPLIT MS1 SUPPLY FAN | Fan:OnOff | 0.696904 | 0.81811314 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | Sensible | 11446.60 | 10262.64 | 0.9892 | 0.81811314 | 0.696904 | 25.17 | 16.70 | 0.00868600 | 47424.3 | 12.80 | 11.37 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 780.608 | 10666.00 | 26.67 | 0.01336053 | 20.77 | 0.05190911 | 7.4485 | 24.04 | 0.00830979 | 24.00 | 0.00830979 | 43.6240 | 16036.90 | 0.00 | 11569.15 | 9131.39 | 0.78580386 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 15.31 | 14.50 | 0.00996834 | 40599.7 | |
| SPLIT MS1 HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT MS1 | M S1 APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 17828.680 | 17828.680 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | SPLIT MS1 SUPPLY FAN | Fan:OnOff | 0.696904 | 0.81811314 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | Sensible | 17828.68 | 17828.68 | 1.0000 | 0.81811314 | 0.696904 | 18.31 | 12.21 | 0.00657732 | 35075.0 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 17828.68 | -16.30 | 0.00092409 | -16.30 | 0.05190911 | 7.4485 | 21.10 | 0.00703229 | 21.10 | 0.00703229 | 44.1199 | 5205.67 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT MS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT MS2 | M S2 APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 11544.947 | 9240.755 | 0.695079 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.9908 | 1004.8586 | 1.1739 | SPLIT MS2 SUPPLY FAN | Fan:OnOff | 0.695079 | 0.81597034 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | Sensible | 11421.19 | 10236.60 | 0.9893 | 0.81597034 | 0.695079 | 25.17 | 16.70 | 0.00868813 | 47430.1 | 12.80 | 11.37 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 778.563 | 10642.63 | 26.67 | 0.01336053 | 20.77 | 0.05190911 | 7.4681 | 24.04 | 0.00831103 | 24.00 | 0.00831103 | 43.6304 | 15996.07 | 0.00 | 11542.98 | 9109.40 | 0.78374568 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 15.31 | 14.50 | 0.00996724 | 40594.4 | |
| SPLIT MS2 HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT MS2 | M S2 APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 17787.981 | 17787.981 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | SPLIT MS2 SUPPLY FAN | Fan:OnOff | 0.695079 | 0.81597034 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | Sensible | 17787.98 | 17787.98 | 1.0000 | 0.81597034 | 0.695079 | 18.31 | 12.21 | 0.00657596 | 35064.1 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 17787.98 | -16.30 | 0.00092409 | -16.30 | 0.05190911 | 7.4681 | 21.10 | 0.00703211 | 21.10 | 0.00703211 | 44.1188 | 5204.57 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT TSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT TSW | T SW APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 7907.054 | 6330.825 | 0.477665 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.8425 | 1004.8586 | 1.1739 | SPLIT TSW SUPPLY FAN | Fan:OnOff | 0.477665 | 0.56074322 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | Sensible | 7808.87 | 7082.61 | 0.9876 | 0.56074322 | 0.477665 | 25.14 | 16.62 | 0.00860837 | 47192.1 | 12.80 | 11.37 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 535.037 | 7273.83 | 26.67 | 0.01336053 | 20.77 | 0.02595455 | 5.4336 | 24.06 | 0.00833532 | 24.00 | 0.00833532 | 43.7570 | 5464.22 | 0.00 | 7905.71 | 6240.49 | 0.53859810 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 15.34 | 14.52 | 0.00997245 | 40644.1 | |
| SPLIT TSW HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT TSW | T SW APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 11796.213 | 11796.213 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | SPLIT TSW SUPPLY FAN | Fan:OnOff | 0.477665 | 0.56074322 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | Sensible | 11796.21 | 11796.21 | 1.0000 | 0.56074322 | 0.477665 | 19.06 | 12.83 | 0.00689499 | 36645.6 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 11796.21 | -16.30 | 0.00092409 | -16.30 | 0.02595455 | 5.4336 | 21.10 | 0.00723807 | 21.10 | 0.00723807 | 45.4005 | 3729.22 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT TNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT TNW | T NW APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 7796.611 | 6242.397 | 0.470993 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.8382 | 1004.8586 | 1.1739 | SPLIT TNW SUPPLY FAN | Fan:OnOff | 0.470993 | 0.55291090 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | Sensible | 7699.56 | 6986.01 | 0.9876 | 0.55291090 | 0.470993 | 25.14 | 16.62 | 0.00860605 | 47187.8 | 12.80 | 11.37 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 527.563 | 7172.00 | 26.67 | 0.01336053 | 20.77 | 0.02595455 | 5.5106 | 24.06 | 0.00832877 | 24.00 | 0.00832877 | 43.7230 | 5389.18 | 0.00 | 7795.28 | 6153.32 | 0.53107510 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 15.34 | 14.52 | 0.00997245 | 40644.1 | |
| SPLIT TNW HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT TNW | T NW APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 11647.281 | 11647.281 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | SPLIT TNW SUPPLY FAN | Fan:OnOff | 0.470993 | 0.55291090 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | Sensible | 11647.28 | 11647.28 | 1.0000 | 0.55291090 | 0.470993 | 19.04 | 12.86 | 0.00693805 | 36725.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 11647.28 | -16.30 | 0.00092409 | -16.30 | 0.02595455 | 5.5106 | 21.10 | 0.00728878 | 21.10 | 0.00728878 | 45.7141 | 3573.64 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT TSE COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT TSE | T SE APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 6719.994 | 5380.017 | 0.402580 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.0603 | 1004.8586 | 1.1739 | SPLIT TSE SUPPLY FAN | Fan:OnOff | 0.402580 | 0.47259843 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | Sensible | 6651.76 | 5927.79 | 0.9898 | 0.47259843 | 0.402580 | 25.16 | 16.72 | 0.00872553 | 47510.2 | 12.80 | 11.37 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 450.933 | 6200.82 | 26.67 | 0.01336053 | 20.77 | 0.02595455 | 6.4471 | 24.06 | 0.00840612 | 24.00 | 0.00840612 | 44.1238 | 4619.32 | 0.00 | 6718.85 | 5303.63 | 0.45393437 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 15.25 | 14.47 | 0.00996229 | 40521.0 | |
| SPLIT TSE HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT TSE | T SE APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 10121.915 | 10121.915 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | SPLIT TSE SUPPLY FAN | Fan:OnOff | 0.402580 | 0.47259843 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | Sensible | 10121.91 | 10121.91 | 1.0000 | 0.47259843 | 0.402580 | 18.69 | 12.61 | 0.00682845 | 36091.2 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10121.91 | -16.30 | 0.00092409 | -16.30 | 0.02595455 | 6.4471 | 21.10 | 0.00723534 | 21.10 | 0.00723534 | 45.3836 | 3714.30 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT TNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT TNE | T NE APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 6606.841 | 5289.659 | 0.395839 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.0584 | 1004.8586 | 1.1739 | SPLIT TNE SUPPLY FAN | Fan:OnOff | 0.395839 | 0.46468545 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | Sensible | 6539.68 | 5828.88 | 0.9898 | 0.46468545 | 0.395839 | 25.16 | 16.72 | 0.00872448 | 47508.7 | 12.80 | 11.37 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 443.382 | 6096.30 | 26.67 | 0.01336053 | 20.77 | 0.02595455 | 6.5568 | 24.05 | 0.00839917 | 24.00 | 0.00839917 | 44.0878 | 4542.78 | 0.00 | 6605.72 | 5214.53 | 0.44633388 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 15.25 | 14.47 | 0.00996259 | 40522.4 | |
| SPLIT TNE HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT TNE | T NE APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 9971.477 | 9971.477 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | SPLIT TNE SUPPLY FAN | Fan:OnOff | 0.395839 | 0.46468545 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | Sensible | 9971.48 | 9971.48 | 1.0000 | 0.46468545 | 0.395839 | 18.65 | 12.63 | 0.00686897 | 36152.4 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9971.48 | -16.30 | 0.00092409 | -16.30 | 0.02595455 | 6.5568 | 21.10 | 0.00728612 | 21.10 | 0.00728612 | 45.6976 | 3558.66 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT TN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT TN1 | T N1 APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 6155.710 | 4928.602 | 0.371866 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.9223 | 1004.8586 | 1.1739 | SPLIT TN1 SUPPLY FAN | Fan:OnOff | 0.371866 | 0.43654344 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | Sensible | 6085.37 | 5484.47 | 0.9886 | 0.43654344 | 0.371866 | 25.17 | 16.66 | 0.00865128 | 47330.5 | 12.80 | 11.37 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 416.531 | 5668.84 | 26.67 | 0.01336053 | 20.77 | 0.02595455 | 6.9795 | 24.05 | 0.00829793 | 24.00 | 0.00829793 | 43.5626 | 4273.13 | 0.00 | 6154.66 | 4858.27 | 0.41930327 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 15.34 | 14.52 | 0.00997245 | 40644.1 | |
| SPLIT TN1 HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT TN1 | T N1 APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 9436.476 | 9436.476 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | SPLIT TN1 SUPPLY FAN | Fan:OnOff | 0.371866 | 0.43654344 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | Sensible | 9436.48 | 9436.48 | 1.0000 | 0.43654344 | 0.371866 | 18.49 | 12.65 | 0.00695354 | 36207.0 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9436.48 | -16.30 | 0.00092409 | -16.30 | 0.02595455 | 6.9795 | 21.10 | 0.00740595 | 21.10 | 0.00740595 | 46.4371 | 2419.55 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT TN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT TN2 | T N2 APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 6117.088 | 4897.679 | 0.369533 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.9304 | 1004.8586 | 1.1739 | SPLIT TN2 SUPPLY FAN | Fan:OnOff | 0.369533 | 0.43380447 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | Sensible | 6047.71 | 5446.94 | 0.9887 | 0.43380447 | 0.369533 | 25.17 | 16.67 | 0.00865565 | 47342.5 | 12.80 | 11.37 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 413.917 | 5633.79 | 26.67 | 0.01336053 | 20.77 | 0.02595455 | 7.0236 | 24.05 | 0.00830024 | 24.00 | 0.00830024 | 43.5745 | 4246.91 | 0.00 | 6116.05 | 4827.79 | 0.41667247 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 15.34 | 14.52 | 0.00997245 | 40644.1 | |
| SPLIT TN2 HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT TN2 | T N2 APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 9384.453 | 9384.453 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | SPLIT TN2 SUPPLY FAN | Fan:OnOff | 0.369533 | 0.43380447 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | Sensible | 9384.45 | 9384.45 | 1.0000 | 0.43380447 | 0.369533 | 18.47 | 12.64 | 0.00695060 | 36182.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9384.45 | -16.30 | 0.00092409 | -16.30 | 0.02595455 | 7.0236 | 21.10 | 0.00740586 | 21.10 | 0.00740586 | 46.4365 | 2419.15 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT TS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT TS1 | T S1 APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 6292.706 | 5038.288 | 0.380142 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.9236 | 1004.8586 | 1.1739 | SPLIT TS1 SUPPLY FAN | Fan:OnOff | 0.380142 | 0.44625873 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | Sensible | 6220.78 | 5605.82 | 0.9886 | 0.44625873 | 0.380142 | 25.17 | 16.66 | 0.00865200 | 47330.3 | 12.80 | 11.37 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 425.800 | 5794.98 | 26.67 | 0.01336053 | 20.77 | 0.02595455 | 6.8276 | 24.05 | 0.00830697 | 24.00 | 0.00830697 | 43.6095 | 4366.66 | 0.00 | 6291.63 | 4966.39 | 0.42863488 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 15.34 | 14.52 | 0.00997245 | 40644.1 | |
| SPLIT TS1 HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT TS1 | T S1 APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 9621.135 | 9621.135 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | SPLIT TS1 SUPPLY FAN | Fan:OnOff | 0.380142 | 0.44625873 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | Sensible | 9621.14 | 9621.14 | 1.0000 | 0.44625873 | 0.380142 | 18.54 | 12.61 | 0.00688809 | 36098.6 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9621.14 | -16.30 | 0.00092409 | -16.30 | 0.02595455 | 6.8276 | 21.10 | 0.00732513 | 21.10 | 0.00732513 | 45.9371 | 2575.63 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT TS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT TS2 | T S2 APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 6254.196 | 5007.455 | 0.377816 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.9317 | 1004.8586 | 1.1739 | SPLIT TS2 SUPPLY FAN | Fan:OnOff | 0.377816 | 0.44352775 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | Sensible | 6183.24 | 5568.37 | 0.9887 | 0.44352775 | 0.377816 | 25.17 | 16.67 | 0.00865632 | 47342.1 | 12.80 | 11.37 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 423.195 | 5760.05 | 26.67 | 0.01336053 | 20.77 | 0.02595455 | 6.8696 | 24.05 | 0.00830932 | 24.00 | 0.00830932 | 43.6216 | 4340.50 | 0.00 | 6253.13 | 4936.00 | 0.42601176 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 15.34 | 14.52 | 0.00997245 | 40644.1 | |
| SPLIT TS2 HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT TS2 | T S2 APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 9569.264 | 9569.264 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | SPLIT TS2 SUPPLY FAN | Fan:OnOff | 0.377816 | 0.44352775 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | Sensible | 9569.26 | 9569.26 | 1.0000 | 0.44352775 | 0.377816 | 18.53 | 12.60 | 0.00688531 | 36075.6 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9569.26 | -16.30 | 0.00092409 | -16.30 | 0.02595455 | 6.8696 | 21.10 | 0.00732503 | 21.10 | 0.00732503 | 45.9365 | 2575.23 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 09:14:20
Economizer| High Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
| None |
| Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
| None |
| Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
| G SW APARTMENT | 3544.83 | 4610.50 | 2585.17 |
| G NW APARTMENT | 5275.50 | 6793.83 | 4123.33 |
| OFFICE | 1195.83 | 1114.17 | 684.83 |
| G NE APARTMENT | 5280.67 | 6799.83 | 4121.83 |
| G N1 APARTMENT | 4754.67 | 6736.83 | 3680.17 |
| G N2 APARTMENT | 4755.00 | 6736.33 | 3679.17 |
| G S1 APARTMENT | 3123.83 | 4461.00 | 2159.67 |
| G S2 APARTMENT | 3280.83 | 4367.50 | 2207.33 |
| M SW APARTMENT | 3025.33 | 4050.67 | 1850.33 |
| M NW APARTMENT | 4629.67 | 6062.83 | 3077.83 |
| M SE APARTMENT | 3022.33 | 4058.33 | 1864.17 |
| M NE APARTMENT | 4620.00 | 5986.33 | 3063.00 |
| M N1 APARTMENT | 3925.83 | 5972.33 | 2551.50 |
| M N2 APARTMENT | 3927.33 | 5970.67 | 2550.17 |
| M S1 APARTMENT | 2446.67 | 3888.67 | 1340.67 |
| M S2 APARTMENT | 2446.33 | 3887.67 | 1340.17 |
| T SW APARTMENT | 3759.83 | 4713.17 | 2818.33 |
| T NW APARTMENT | 5524.17 | 6811.00 | 4159.67 |
| T SE APARTMENT | 3741.83 | 4742.33 | 2841.50 |
| T NE APARTMENT | 5527.33 | 6741.67 | 4136.67 |
| T N1 APARTMENT | 5212.67 | 6735.50 | 3901.67 |
| T N2 APARTMENT | 5213.33 | 6727.50 | 3900.00 |
| T S1 APARTMENT | 3436.67 | 4589.83 | 2510.17 |
| T S2 APARTMENT | 3435.33 | 4593.00 | 2512.33 |
| T CORRIDOR | 7093.83 | 8645.17 | 7018.17 |
| G CORRIDOR | 6500.83 | 7463.17 | 5466.33 |
| M CORRIDOR | 5798.33 | 8757.00 | 5798.33 |
| Facility | 8752.17 | 8760.00 | 8752.00 |
| During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
| G SW APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| G NW APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| OFFICE | 0.00 | 0.00 | 0.00 | 0.00 |
| G NE APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| G N1 APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| G N2 APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| G S1 APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| G S2 APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| M SW APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| M NW APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| M SE APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| M NE APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| M N1 APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| M N2 APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| M S1 APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| M S2 APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| T SW APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| T NW APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| T SE APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| T NE APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| T N1 APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| T N2 APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| T S1 APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| T S2 APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| T CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
| G CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
| M CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
| Facility | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 09:14:20
Average Outdoor Air During Occupied Hours| Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
| G SW APARTMENT | 2.40 | 2.50 | 268.97 | 0.352 | 0.125 | 0.000 | 0.055 |
| G NW APARTMENT | 1.71 | 2.50 | 268.97 | 0.352 | 0.132 | 0.000 | 0.069 |
| OFFICE | 4.75 | 4.75 | 268.97 | 0.518 | 0.146 | 0.000 | 0.000 |
| G NE APARTMENT | 1.71 | 2.50 | 268.97 | 0.352 | 0.132 | 0.000 | 0.069 |
| G N1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.352 | 0.080 | 0.000 | 0.069 |
| G N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.352 | 0.080 | 0.000 | 0.069 |
| G S1 APARTMENT | 2.40 | 2.50 | 268.97 | 0.352 | 0.076 | 0.000 | 0.055 |
| G S2 APARTMENT | 2.40 | 2.50 | 268.97 | 0.352 | 0.076 | 0.000 | 0.055 |
| M SW APARTMENT | 2.40 | 2.50 | 268.97 | 0.353 | 0.180 | 0.000 | 0.070 |
| M NW APARTMENT | 1.71 | 2.50 | 268.97 | 0.352 | 0.190 | 0.000 | 0.089 |
| M SE APARTMENT | 2.40 | 2.50 | 268.97 | 0.353 | 0.180 | 0.000 | 0.070 |
| M NE APARTMENT | 1.71 | 2.50 | 268.97 | 0.352 | 0.190 | 0.000 | 0.089 |
| M N1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.115 | 0.000 | 0.089 |
| M N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.115 | 0.000 | 0.089 |
| M S1 APARTMENT | 2.40 | 2.50 | 268.97 | 0.353 | 0.109 | 0.000 | 0.070 |
| M S2 APARTMENT | 2.40 | 2.50 | 268.97 | 0.353 | 0.109 | 0.000 | 0.070 |
| T SW APARTMENT | 2.40 | 2.50 | 268.97 | 0.352 | 0.238 | 0.000 | 0.083 |
| T NW APARTMENT | 1.71 | 2.50 | 268.97 | 0.352 | 0.252 | 0.000 | 0.106 |
| T SE APARTMENT | 2.40 | 2.50 | 268.97 | 0.352 | 0.238 | 0.000 | 0.083 |
| T NE APARTMENT | 1.71 | 2.50 | 268.97 | 0.352 | 0.252 | 0.000 | 0.106 |
| T N1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.352 | 0.152 | 0.000 | 0.106 |
| T N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.352 | 0.152 | 0.000 | 0.106 |
| T S1 APARTMENT | 2.40 | 2.50 | 268.97 | 0.352 | 0.144 | 0.000 | 0.083 |
| T S2 APARTMENT | 2.40 | 2.50 | 268.97 | 0.352 | 0.144 | 0.000 | 0.083 |
| Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
| G SW APARTMENT | 2.40 | 2.50 | 268.97 | 0.338 | 0.000 | 0.000 | 0.000 |
| G NW APARTMENT | 1.71 | 2.50 | 268.97 | 0.338 | 0.000 | 0.000 | 0.000 |
| OFFICE | 4.75 | 4.75 | 268.97 | 0.491 | 0.000 | 0.000 | 0.000 |
| G NE APARTMENT | 1.71 | 2.50 | 268.97 | 0.338 | 0.000 | 0.000 | 0.000 |
| G N1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.338 | 0.000 | 0.000 | 0.000 |
| G N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.338 | 0.000 | 0.000 | 0.000 |
| G S1 APARTMENT | 2.40 | 2.50 | 268.97 | 0.338 | 0.000 | 0.000 | 0.000 |
| G S2 APARTMENT | 2.40 | 2.50 | 268.97 | 0.338 | 0.000 | 0.000 | 0.000 |
| M SW APARTMENT | 2.40 | 2.50 | 268.97 | 0.338 | 0.000 | 0.000 | 0.000 |
| M NW APARTMENT | 1.71 | 2.50 | 268.97 | 0.338 | 0.000 | 0.000 | 0.000 |
| M SE APARTMENT | 2.40 | 2.50 | 268.97 | 0.338 | 0.000 | 0.000 | 0.000 |
| M NE APARTMENT | 1.71 | 2.50 | 268.97 | 0.338 | 0.000 | 0.000 | 0.000 |
| M N1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.338 | 0.000 | 0.000 | 0.000 |
| M N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.338 | 0.000 | 0.000 | 0.000 |
| M S1 APARTMENT | 2.40 | 2.50 | 268.97 | 0.338 | 0.000 | 0.000 | 0.000 |
| M S2 APARTMENT | 2.40 | 2.50 | 268.97 | 0.338 | 0.000 | 0.000 | 0.000 |
| T SW APARTMENT | 2.40 | 2.50 | 268.97 | 0.338 | 0.000 | 0.000 | 0.000 |
| T NW APARTMENT | 1.71 | 2.50 | 268.97 | 0.338 | 0.000 | 0.000 | 0.000 |
| T SE APARTMENT | 2.40 | 2.50 | 268.97 | 0.338 | 0.000 | 0.000 | 0.000 |
| T NE APARTMENT | 1.71 | 2.50 | 268.97 | 0.338 | 0.000 | 0.000 | 0.000 |
| T N1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.338 | 0.000 | 0.000 | 0.000 |
| T N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.338 | 0.000 | 0.000 | 0.000 |
| T S1 APARTMENT | 2.40 | 2.50 | 268.97 | 0.338 | 0.000 | 0.000 | 0.000 |
| T S2 APARTMENT | 2.40 | 2.50 | 268.97 | 0.338 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 09:14:20
Mechanical Ventilation Parameters by Zone| AirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
| G SW APARTMENT | SPLIT GSW | 2.40 | 2.50 | 268.97 | 88.25 | 0.0260 | 0.026 |
| G NW APARTMENT | SPLIT GNW | 1.71 | 2.50 | 268.97 | 88.25 | 0.0260 | 0.026 |
| OFFICE | SPLIT OFFICE | 4.75 | 4.75 | 268.97 | 88.25 | 0.0381 | 0.038 |
| G NE APARTMENT | SPLIT GNE | 1.71 | 2.50 | 268.97 | 88.25 | 0.0260 | 0.026 |
| G N1 APARTMENT | SPLIT GN1 | 1.71 | 2.50 | 268.97 | 88.25 | 0.0260 | 0.026 |
| G N2 APARTMENT | SPLIT GN2 | 1.71 | 2.50 | 268.97 | 88.25 | 0.0260 | 0.026 |
| G S1 APARTMENT | SPLIT GS1 | 2.40 | 2.50 | 268.97 | 88.25 | 0.0260 | 0.026 |
| G S2 APARTMENT | SPLIT GS2 | 2.40 | 2.50 | 268.97 | 88.25 | 0.0260 | 0.026 |
| M SW APARTMENT | SPLIT MSW | 2.40 | 2.50 | 268.97 | 88.25 | 0.0519 | 0.052 |
| M NW APARTMENT | SPLIT MNW | 1.71 | 2.50 | 268.97 | 88.25 | 0.0519 | 0.052 |
| M SE APARTMENT | SPLIT MSE | 2.40 | 2.50 | 268.97 | 88.25 | 0.0519 | 0.052 |
| M NE APARTMENT | SPLIT MNE | 1.71 | 2.50 | 268.97 | 88.25 | 0.0519 | 0.052 |
| M N1 APARTMENT | SPLIT MN1 | 1.71 | 2.50 | 268.97 | 88.25 | 0.0519 | 0.052 |
| M N2 APARTMENT | SPLIT MN2 | 1.71 | 2.50 | 268.97 | 88.25 | 0.0519 | 0.052 |
| M S1 APARTMENT | SPLIT MS1 | 2.40 | 2.50 | 268.97 | 88.25 | 0.0519 | 0.052 |
| M S2 APARTMENT | SPLIT MS2 | 2.40 | 2.50 | 268.97 | 88.25 | 0.0519 | 0.052 |
| T SW APARTMENT | SPLIT TSW | 2.40 | 2.50 | 268.97 | 88.25 | 0.0260 | 0.026 |
| T NW APARTMENT | SPLIT TNW | 1.71 | 2.50 | 268.97 | 88.25 | 0.0260 | 0.026 |
| T SE APARTMENT | SPLIT TSE | 2.40 | 2.50 | 268.97 | 88.25 | 0.0260 | 0.026 |
| T NE APARTMENT | SPLIT TNE | 1.71 | 2.50 | 268.97 | 88.25 | 0.0260 | 0.026 |
| T N1 APARTMENT | SPLIT TN1 | 1.71 | 2.50 | 268.97 | 88.25 | 0.0260 | 0.026 |
| T N2 APARTMENT | SPLIT TN2 | 1.71 | 2.50 | 268.97 | 88.25 | 0.0260 | 0.026 |
| T S1 APARTMENT | SPLIT TS1 | 2.40 | 2.50 | 268.97 | 88.25 | 0.0260 | 0.026 |
| T S2 APARTMENT | SPLIT TS2 | 2.40 | 2.50 | 268.97 | 88.25 | 0.0260 | 0.026 |
| Total Facility | 68.19 | 82.25 | 8607.06 | 2823.98 | 0.8427 | 1.258 |
| Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
| G SW APARTMENT | 818502.78 | 163605.58 | 982108.36 | 307706.97 | 1289815.33 | 818502.78 | 0.00 | 7217.67 | 1542.33 | 2615.00 |
| G NW APARTMENT | 818502.78 | 159039.23 | 977542.01 | 307706.97 | 1285248.97 | 818502.78 | 0.00 | 7217.67 | 1542.33 | 0.00 |
| OFFICE | 1201711.97 | 0.00 | 1201711.97 | 307706.97 | 1509418.94 | 1201711.97 | 0.00 | 8760.00 | 0.00 | 7010.00 |
| G NE APARTMENT | 818502.78 | 159362.20 | 977864.97 | 307706.97 | 1285571.94 | 818502.78 | 0.00 | 7217.67 | 1542.33 | 0.00 |
| G N1 APARTMENT | 818502.78 | 159479.05 | 977981.83 | 185601.03 | 1163582.86 | 818502.78 | 0.00 | 7217.67 | 1542.33 | 0.00 |
| G N2 APARTMENT | 818502.78 | 159500.93 | 978003.71 | 185601.03 | 1163604.74 | 818502.78 | 0.00 | 7217.67 | 1542.33 | 0.00 |
| G S1 APARTMENT | 818502.78 | 164240.71 | 982743.48 | 185601.03 | 1168344.52 | 818502.78 | 0.00 | 7217.67 | 1542.33 | 2615.00 |
| G S2 APARTMENT | 818502.78 | 164388.87 | 982891.65 | 185601.03 | 1168492.68 | 818502.78 | 0.00 | 7217.67 | 1542.33 | 2615.00 |
| M SW APARTMENT | 1637005.55 | 210347.21 | 1847352.77 | 442199.25 | 2289552.02 | 1637005.55 | 0.00 | 7184.17 | 1575.83 | 2615.00 |
| M NW APARTMENT | 1637005.55 | 205321.19 | 1842326.75 | 442199.25 | 2284526.00 | 1637005.55 | 0.00 | 7184.17 | 1575.83 | 0.00 |
| M SE APARTMENT | 1637005.55 | 210453.06 | 1847458.62 | 442199.25 | 2289657.87 | 1637005.55 | 0.00 | 7184.17 | 1575.83 | 2615.00 |
| M NE APARTMENT | 1637005.55 | 205571.64 | 1842577.20 | 442199.25 | 2284776.45 | 1637005.55 | 0.00 | 7184.17 | 1575.83 | 0.00 |
| M N1 APARTMENT | 1637005.55 | 205519.42 | 1842524.97 | 266723.36 | 2109248.33 | 1637005.55 | 0.00 | 7184.17 | 1575.83 | 0.00 |
| M N2 APARTMENT | 1637005.55 | 205538.23 | 1842543.78 | 266723.36 | 2109267.14 | 1637005.55 | 0.00 | 7184.17 | 1575.83 | 0.00 |
| M S1 APARTMENT | 1637005.55 | 210538.99 | 1847544.55 | 266723.36 | 2114267.91 | 1637005.55 | 0.00 | 7184.17 | 1575.83 | 2615.00 |
| M S2 APARTMENT | 1637005.55 | 210544.30 | 1847549.85 | 266723.36 | 2114273.22 | 1637005.55 | 0.00 | 7184.17 | 1575.83 | 2615.00 |
| T SW APARTMENT | 818502.78 | 250455.09 | 1068957.87 | 584940.44 | 1653898.31 | 818502.78 | 0.00 | 7220.33 | 1539.67 | 2615.00 |
| T NW APARTMENT | 818502.78 | 243805.02 | 1062307.80 | 584940.44 | 1647248.24 | 818502.78 | 0.00 | 7220.33 | 1539.67 | 0.00 |
| T SE APARTMENT | 818502.78 | 251001.50 | 1069504.27 | 584940.44 | 1654444.71 | 818502.78 | 0.00 | 7220.33 | 1539.67 | 2615.00 |
| T NE APARTMENT | 818502.78 | 244610.01 | 1063112.78 | 584940.44 | 1648053.22 | 818502.78 | 0.00 | 7220.33 | 1539.67 | 0.00 |
| T N1 APARTMENT | 818502.78 | 244152.95 | 1062655.72 | 352821.22 | 1415476.95 | 818502.78 | 0.00 | 7220.33 | 1539.67 | 0.00 |
| T N2 APARTMENT | 818502.78 | 244223.06 | 1062725.84 | 352821.22 | 1415547.06 | 818502.78 | 0.00 | 7220.33 | 1539.67 | 0.00 |
| T S1 APARTMENT | 818502.78 | 250891.87 | 1069394.64 | 352821.22 | 1422215.87 | 818502.78 | 0.00 | 7220.33 | 1539.67 | 2615.00 |
| T S2 APARTMENT | 818502.78 | 250924.45 | 1069427.22 | 352821.22 | 1422248.44 | 818502.78 | 0.00 | 7220.33 | 1539.67 | 2615.00 |
| Total Facility | 39671342.50 | 6437348.60 | 46108691.11 | 11395659.55 | 57504350.66 | 39671342.50 | 0.00 | 8760.00 | 1579.17 | 8760.00 |
| Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
| G SW APARTMENT | 0.0260 | 0.0040 | 0.0300 | 0.0092 | 0.0392 | 0.0260 | 0.00 | 5298.67 | 846.33 |
| G NW APARTMENT | 0.0260 | 0.0050 | 0.0310 | 0.0098 | 0.0408 | 0.0260 | 0.00 | 7217.67 | 1542.33 |
| OFFICE | 0.0381 | 0.0000 | 0.0381 | 0.0107 | 0.0488 | 0.0381 | 0.00 | 1750.00 | 0.00 |
| G NE APARTMENT | 0.0260 | 0.0051 | 0.0310 | 0.0098 | 0.0408 | 0.0260 | 0.00 | 7217.67 | 1542.33 |
| G N1 APARTMENT | 0.0260 | 0.0051 | 0.0310 | 0.0059 | 0.0369 | 0.0260 | 0.00 | 7217.67 | 1542.33 |
| G N2 APARTMENT | 0.0260 | 0.0051 | 0.0310 | 0.0059 | 0.0369 | 0.0260 | 0.00 | 7217.67 | 1542.33 |
| G S1 APARTMENT | 0.0260 | 0.0040 | 0.0300 | 0.0056 | 0.0356 | 0.0260 | 0.00 | 5298.67 | 846.33 |
| G S2 APARTMENT | 0.0260 | 0.0040 | 0.0300 | 0.0056 | 0.0356 | 0.0260 | 0.00 | 5298.67 | 846.33 |
| M SW APARTMENT | 0.0519 | 0.0051 | 0.0570 | 0.0133 | 0.0703 | 0.0519 | 0.00 | 5283.50 | 861.50 |
| M NW APARTMENT | 0.0519 | 0.0065 | 0.0584 | 0.0140 | 0.0724 | 0.0519 | 0.00 | 7184.17 | 1575.83 |
| M SE APARTMENT | 0.0519 | 0.0051 | 0.0570 | 0.0133 | 0.0703 | 0.0519 | 0.00 | 5283.50 | 861.50 |
| M NE APARTMENT | 0.0519 | 0.0065 | 0.0584 | 0.0140 | 0.0724 | 0.0519 | 0.00 | 7184.17 | 1575.83 |
| M N1 APARTMENT | 0.0519 | 0.0065 | 0.0584 | 0.0085 | 0.0669 | 0.0519 | 0.00 | 7184.17 | 1575.83 |
| M N2 APARTMENT | 0.0519 | 0.0065 | 0.0584 | 0.0085 | 0.0669 | 0.0519 | 0.00 | 7184.17 | 1575.83 |
| M S1 APARTMENT | 0.0519 | 0.0051 | 0.0570 | 0.0080 | 0.0650 | 0.0519 | 0.00 | 5283.50 | 861.50 |
| M S2 APARTMENT | 0.0519 | 0.0051 | 0.0570 | 0.0080 | 0.0650 | 0.0519 | 0.00 | 5283.50 | 861.50 |
| T SW APARTMENT | 0.0260 | 0.0061 | 0.0320 | 0.0175 | 0.0496 | 0.0260 | 0.00 | 5305.00 | 840.00 |
| T NW APARTMENT | 0.0260 | 0.0077 | 0.0337 | 0.0185 | 0.0522 | 0.0260 | 0.00 | 7220.33 | 1539.67 |
| T SE APARTMENT | 0.0260 | 0.0061 | 0.0320 | 0.0175 | 0.0496 | 0.0260 | 0.00 | 5305.00 | 840.00 |
| T NE APARTMENT | 0.0260 | 0.0078 | 0.0337 | 0.0185 | 0.0523 | 0.0260 | 0.00 | 7220.33 | 1539.67 |
| T N1 APARTMENT | 0.0260 | 0.0077 | 0.0337 | 0.0112 | 0.0449 | 0.0260 | 0.00 | 7220.33 | 1539.67 |
| T N2 APARTMENT | 0.0260 | 0.0077 | 0.0337 | 0.0112 | 0.0449 | 0.0260 | 0.00 | 7220.33 | 1539.67 |
| T S1 APARTMENT | 0.0260 | 0.0061 | 0.0320 | 0.0106 | 0.0426 | 0.0260 | 0.00 | 5305.00 | 840.00 |
| T S2 APARTMENT | 0.0260 | 0.0061 | 0.0320 | 0.0106 | 0.0426 | 0.0260 | 0.00 | 5305.00 | 840.00 |
| Total Facility | 1.2580 | 0.1807 | 1.4387 | 0.3530 | 1.7917 | 1.2580 | 0.00 | 8760.00 | 1579.17 |
| Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
| SPLIT GSW | 0.00 | 163605.58 | 163605.58 | 818502.78 | 7747.67 | 36.33 | 976.00 | 696.00 |
| SPLIT GNW | 0.00 | 159039.23 | 159039.23 | 818502.78 | 7777.33 | 45.01 | 937.66 | 0.00 |
| SPLIT OFFICE | 1656080.04 | 0.00 | 1656080.04 | 1201711.97 | 0.00 | 0.00 | 8760.00 | 7010.00 |
| SPLIT GNE | 0.00 | 159362.20 | 159362.20 | 818502.78 | 7771.83 | 44.58 | 943.58 | 0.00 |
| SPLIT GN1 | 0.00 | 159479.05 | 159479.05 | 818502.78 | 7770.67 | 40.75 | 948.58 | 0.00 |
| SPLIT GN2 | 0.00 | 159500.93 | 159500.93 | 818502.78 | 7770.83 | 40.42 | 948.75 | 0.00 |
| SPLIT GS1 | 0.00 | 164240.71 | 164240.71 | 818502.78 | 7742.25 | 36.25 | 981.50 | 696.00 |
| SPLIT GS2 | 0.00 | 164388.87 | 164388.87 | 818502.78 | 7741.17 | 36.17 | 982.67 | 696.00 |
| SPLIT MSW | 0.00 | 210347.21 | 210347.21 | 1637005.55 | 8540.67 | 24.33 | 195.00 | 714.33 |
| SPLIT MNW | 0.00 | 205321.19 | 205321.19 | 1637005.55 | 8575.50 | 22.33 | 162.17 | 0.00 |
| SPLIT MSE | 0.00 | 210453.06 | 210453.06 | 1637005.55 | 8539.63 | 25.38 | 195.00 | 714.33 |
| SPLIT MNE | 0.00 | 205571.64 | 205571.64 | 1637005.55 | 8574.33 | 23.00 | 162.67 | 0.00 |
| SPLIT MN1 | 0.00 | 205519.42 | 205519.42 | 1637005.55 | 8575.00 | 22.67 | 162.33 | 0.00 |
| SPLIT MN2 | 0.00 | 205538.23 | 205538.23 | 1637005.55 | 8575.00 | 22.50 | 162.50 | 0.00 |
| SPLIT MS1 | 0.00 | 210538.99 | 210538.99 | 1637005.55 | 8539.17 | 25.17 | 195.67 | 714.33 |
| SPLIT MS2 | 0.00 | 210544.30 | 210544.30 | 1637005.55 | 8539.17 | 25.33 | 195.50 | 714.33 |
| SPLIT TSW | 0.00 | 250455.09 | 250455.09 | 818502.78 | 7339.17 | 15.40 | 1405.43 | 699.67 |
| SPLIT TNW | 0.00 | 243805.02 | 243805.02 | 818502.78 | 7350.43 | 15.73 | 1393.83 | 0.00 |
| SPLIT TSE | 0.00 | 251001.50 | 251001.50 | 818502.78 | 7336.83 | 14.50 | 1408.67 | 699.67 |
| SPLIT TNE | 0.00 | 244610.01 | 244610.01 | 818502.78 | 7346.00 | 16.17 | 1397.83 | 0.00 |
| SPLIT TN1 | 0.00 | 244152.95 | 244152.95 | 818502.78 | 7348.23 | 14.77 | 1397.00 | 0.00 |
| SPLIT TN2 | 0.00 | 244223.06 | 244223.06 | 818502.78 | 7348.07 | 14.77 | 1397.17 | 0.00 |
| SPLIT TS1 | 0.00 | 250891.87 | 250891.87 | 818502.78 | 7337.50 | 13.50 | 1409.00 | 699.67 |
| SPLIT TS2 | 0.00 | 250924.45 | 250924.45 | 818502.78 | 7337.33 | 13.67 | 1409.00 | 699.67 |
| Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
| SPLIT GSW | 0.0000 | 0.0040 | 0.0040 | 0.0260 | 5597.50 | 22.17 | 525.33 |
| SPLIT GNW | 0.0000 | 0.0050 | 0.0050 | 0.0260 | 7777.33 | 45.01 | 937.66 |
| SPLIT OFFICE | 0.0525 | 0.0000 | 0.0525 | 0.0381 | 0.00 | 0.00 | 1750.00 |
| SPLIT GNE | 0.0000 | 0.0051 | 0.0051 | 0.0260 | 7771.83 | 44.58 | 943.58 |
| SPLIT GN1 | 0.0000 | 0.0051 | 0.0051 | 0.0260 | 7770.67 | 40.75 | 948.58 |
| SPLIT GN2 | 0.0000 | 0.0051 | 0.0051 | 0.0260 | 7770.83 | 40.42 | 948.75 |
| SPLIT GS1 | 0.0000 | 0.0040 | 0.0040 | 0.0260 | 5595.67 | 21.50 | 527.83 |
| SPLIT GS2 | 0.0000 | 0.0040 | 0.0040 | 0.0260 | 5595.67 | 21.33 | 528.00 |
| SPLIT MSW | 0.0000 | 0.0051 | 0.0051 | 0.0519 | 6035.50 | 10.33 | 99.17 |
| SPLIT MNW | 0.0000 | 0.0065 | 0.0065 | 0.0519 | 8575.50 | 22.33 | 162.17 |
| SPLIT MSE | 0.0000 | 0.0051 | 0.0051 | 0.0519 | 6034.63 | 10.87 | 99.50 |
| SPLIT MNE | 0.0000 | 0.0065 | 0.0065 | 0.0519 | 8574.33 | 23.00 | 162.67 |
| SPLIT MN1 | 0.0000 | 0.0065 | 0.0065 | 0.0519 | 8575.00 | 22.67 | 162.33 |
| SPLIT MN2 | 0.0000 | 0.0065 | 0.0065 | 0.0519 | 8575.00 | 22.50 | 162.50 |
| SPLIT MS1 | 0.0000 | 0.0051 | 0.0051 | 0.0519 | 6034.17 | 10.83 | 100.00 |
| SPLIT MS2 | 0.0000 | 0.0051 | 0.0051 | 0.0519 | 6034.17 | 11.00 | 99.83 |
| SPLIT TSW | 0.0000 | 0.0061 | 0.0061 | 0.0260 | 5367.67 | 9.33 | 768.00 |
| SPLIT TNW | 0.0000 | 0.0077 | 0.0077 | 0.0260 | 7350.43 | 15.73 | 1393.83 |
| SPLIT TSE | 0.0000 | 0.0061 | 0.0061 | 0.0260 | 5366.50 | 9.17 | 769.33 |
| SPLIT TNE | 0.0000 | 0.0078 | 0.0078 | 0.0260 | 7346.00 | 16.17 | 1397.83 |
| SPLIT TN1 | 0.0000 | 0.0077 | 0.0077 | 0.0260 | 7348.23 | 14.77 | 1397.00 |
| SPLIT TN2 | 0.0000 | 0.0077 | 0.0077 | 0.0260 | 7348.07 | 14.77 | 1397.17 |
| SPLIT TS1 | 0.0000 | 0.0061 | 0.0061 | 0.0260 | 5367.00 | 8.00 | 770.00 |
| SPLIT TS2 | 0.0000 | 0.0061 | 0.0061 | 0.0260 | 5367.00 | 8.00 | 770.00 |
| No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
| SPLIT GSW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT GNW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT OFFICE | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT GNE | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT GN1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT GN2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT GS1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT GS2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT MSW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT MNW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT MSE | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT MNE | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT MN1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT MN2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT MS1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT MS2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT TSW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT TNW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT TSE | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT TNE | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT TN1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT TN2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT TS1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT TS2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
| SPLIT GSW | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT GNW | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT OFFICE | 0.0525 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT GNE | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT GN1 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT GN2 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT GS1 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT GS2 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT MSW | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT MNW | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT MSE | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT MNE | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT MN1 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT MN2 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT MS1 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT MS2 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT TSW | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT TNW | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT TSE | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT TNE | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT TN1 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT TN2 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT TS1 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT TS2 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 09:14:20
Surfaces by Class| Total | Outdoors | |
| Wall | 126 | 42 |
| Floor | 27 | 9 |
| Roof | 27 | 9 |
| Internal Mass | 24 | 0 |
| Building Detached Shading | 0 | 0 |
| Fixed Detached Shading | 0 | 0 |
| Window | 39 | 39 |
| Door | 0 | 0 |
| Glass Door | 0 | 0 |
| Shading | 0 | 0 |
| Overhang | 0 | 0 |
| Fin | 0 | 0 |
| Tubular Daylighting Device Dome | 0 | 0 |
| Tubular Daylighting Device Diffuser | 0 | 0 |
| Count | |
| HVAC Air Loops | 24 |
| Conditioned Zones | 24 |
| Unconditioned Zones | 3 |
| Supply Plenums | 0 |
| Return Plenums | 0 |
| Count | |
| IDF Objects | 1536 |
| Defaulted Fields | 1816 |
| Fields with Defaults | 5921 |
| Autosized Fields | 617 |
| Autosizable Fields | 759 |
| Autocalculated Fields | 331 |
| Autocalculatable Fields | 508 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 09:14:20
Annual and Peak Values - Electricity| Electricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
| Electricity:Facility | 1261.71 | 16919.74 | 25-MAY-02:30 | 89955.36 | 13-AUG-16:10 |
| Electricity:Building | 557.89 | 10119.94 | 01-JAN-03:10 | 27841.36 | 01-JAN-18:10 |
| Electricity:Zone:G SW APARTMENT | 13.67 | 232.36 | 01-JAN-03:10 | 705.80 | 01-JAN-18:10 |
| Electricity:SpaceType:GENERAL | 557.89 | 10119.94 | 01-JAN-03:10 | 27841.36 | 01-JAN-18:10 |
| InteriorLights:Electricity | 99.23 | 1868.27 | 01-JAN-00:10 | 5904.43 | 01-JAN-19:10 |
| InteriorLights:Electricity:Zone:G SW APARTMENT | 1.45 | 8.68 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 |
| InteriorLights:Electricity:SpaceType:GENERAL | 99.23 | 1868.27 | 01-JAN-00:10 | 5904.43 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity | 94.96 | 1842.77 | 01-JAN-00:10 | 5496.56 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:G SW APARTMENT | 1.32 | 7.86 | 01-JAN-00:10 | 125.72 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 94.96 | 1842.77 | 01-JAN-00:10 | 5496.56 | 01-JAN-19:10 |
| Electricity:Zone:G NW APARTMENT | 13.67 | 232.36 | 01-JAN-03:10 | 705.80 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:G NW APARTMENT | 1.45 | 8.68 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:G NW APARTMENT | 1.32 | 7.86 | 01-JAN-00:10 | 125.72 | 01-JAN-19:10 |
| Electricity:Zone:OFFICE | 16.86 | 310.83 | 01-JAN-00:10 | 1171.54 | 03-JAN-08:10 |
| InteriorLights:Electricity:Zone:OFFICE | 7.40 | 116.58 | 01-JAN-00:10 | 582.92 | 03-JAN-08:10 |
| LightsWired:InteriorLights:Electricity:Zone:OFFICE | 7.40 | 116.58 | 01-JAN-00:10 | 582.92 | 03-JAN-08:10 |
| Electricity:Zone:G NE APARTMENT | 13.67 | 232.36 | 01-JAN-03:10 | 705.80 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:G NE APARTMENT | 1.45 | 8.68 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:G NE APARTMENT | 1.32 | 7.86 | 01-JAN-00:10 | 125.72 | 01-JAN-19:10 |
| Electricity:Zone:G N1 APARTMENT | 13.67 | 232.36 | 01-JAN-03:10 | 705.80 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:G N1 APARTMENT | 1.45 | 8.68 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:G N1 APARTMENT | 1.32 | 7.86 | 01-JAN-00:10 | 125.72 | 01-JAN-19:10 |
| Electricity:Zone:G N2 APARTMENT | 13.67 | 232.36 | 01-JAN-03:10 | 705.80 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:G N2 APARTMENT | 1.45 | 8.68 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:G N2 APARTMENT | 1.32 | 7.86 | 01-JAN-00:10 | 125.72 | 01-JAN-19:10 |
| Electricity:Zone:G S1 APARTMENT | 13.67 | 232.36 | 01-JAN-03:10 | 705.80 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:G S1 APARTMENT | 1.45 | 8.68 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:G S1 APARTMENT | 1.32 | 7.86 | 01-JAN-00:10 | 125.72 | 01-JAN-19:10 |
| Electricity:Zone:G S2 APARTMENT | 13.67 | 232.36 | 01-JAN-03:10 | 705.80 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:G S2 APARTMENT | 1.45 | 8.68 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:G S2 APARTMENT | 1.32 | 7.86 | 01-JAN-00:10 | 125.72 | 01-JAN-19:10 |
| Electricity:Zone:M SW APARTMENT | 27.33 | 464.72 | 01-JAN-03:10 | 1411.61 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:M SW APARTMENT | 2.91 | 17.37 | 01-JAN-00:10 | 277.76 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:M SW APARTMENT | 2.63 | 15.72 | 01-JAN-00:10 | 251.45 | 01-JAN-19:10 |
| Electricity:Zone:M NW APARTMENT | 27.33 | 464.72 | 01-JAN-03:10 | 1411.61 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:M NW APARTMENT | 2.91 | 17.37 | 01-JAN-00:10 | 277.76 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:M NW APARTMENT | 2.63 | 15.72 | 01-JAN-00:10 | 251.45 | 01-JAN-19:10 |
| Electricity:Zone:M SE APARTMENT | 27.33 | 464.72 | 01-JAN-03:10 | 1411.61 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:M SE APARTMENT | 2.91 | 17.37 | 01-JAN-00:10 | 277.76 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:M SE APARTMENT | 2.63 | 15.72 | 01-JAN-00:10 | 251.45 | 01-JAN-19:10 |
| Electricity:Zone:M NE APARTMENT | 27.33 | 464.72 | 01-JAN-03:10 | 1411.61 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:M NE APARTMENT | 2.91 | 17.37 | 01-JAN-00:10 | 277.76 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:M NE APARTMENT | 2.63 | 15.72 | 01-JAN-00:10 | 251.45 | 01-JAN-19:10 |
| Electricity:Zone:M N1 APARTMENT | 27.33 | 464.72 | 01-JAN-03:10 | 1411.61 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:M N1 APARTMENT | 2.91 | 17.37 | 01-JAN-00:10 | 277.76 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:M N1 APARTMENT | 2.63 | 15.72 | 01-JAN-00:10 | 251.45 | 01-JAN-19:10 |
| Electricity:Zone:M N2 APARTMENT | 27.33 | 464.72 | 01-JAN-03:10 | 1411.61 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:M N2 APARTMENT | 2.91 | 17.37 | 01-JAN-00:10 | 277.76 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:M N2 APARTMENT | 2.63 | 15.72 | 01-JAN-00:10 | 251.45 | 01-JAN-19:10 |
| Electricity:Zone:M S1 APARTMENT | 27.33 | 464.72 | 01-JAN-03:10 | 1411.61 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:M S1 APARTMENT | 2.91 | 17.37 | 01-JAN-00:10 | 277.76 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:M S1 APARTMENT | 2.63 | 15.72 | 01-JAN-00:10 | 251.45 | 01-JAN-19:10 |
| Electricity:Zone:M S2 APARTMENT | 27.33 | 464.72 | 01-JAN-03:10 | 1411.61 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:M S2 APARTMENT | 2.91 | 17.37 | 01-JAN-00:10 | 277.76 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:M S2 APARTMENT | 2.63 | 15.72 | 01-JAN-00:10 | 251.45 | 01-JAN-19:10 |
| Electricity:Zone:T SW APARTMENT | 13.67 | 232.36 | 01-JAN-03:10 | 705.80 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:T SW APARTMENT | 1.45 | 8.68 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:T SW APARTMENT | 1.32 | 7.86 | 01-JAN-00:10 | 125.72 | 01-JAN-19:10 |
| Electricity:Zone:T NW APARTMENT | 13.67 | 232.36 | 01-JAN-03:10 | 705.80 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:T NW APARTMENT | 1.45 | 8.68 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:T NW APARTMENT | 1.32 | 7.86 | 01-JAN-00:10 | 125.72 | 01-JAN-19:10 |
| Electricity:Zone:T SE APARTMENT | 13.67 | 232.36 | 01-JAN-03:10 | 705.80 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:T SE APARTMENT | 1.45 | 8.68 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:T SE APARTMENT | 1.32 | 7.86 | 01-JAN-00:10 | 125.72 | 01-JAN-19:10 |
| Electricity:Zone:T NE APARTMENT | 13.67 | 232.36 | 01-JAN-03:10 | 705.80 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:T NE APARTMENT | 1.45 | 8.68 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:T NE APARTMENT | 1.32 | 7.86 | 01-JAN-00:10 | 125.72 | 01-JAN-19:10 |
| Electricity:Zone:T N1 APARTMENT | 13.67 | 232.36 | 01-JAN-03:10 | 705.80 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:T N1 APARTMENT | 1.45 | 8.68 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:T N1 APARTMENT | 1.32 | 7.86 | 01-JAN-00:10 | 125.72 | 01-JAN-19:10 |
| Electricity:Zone:T N2 APARTMENT | 13.67 | 232.36 | 01-JAN-03:10 | 705.80 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:T N2 APARTMENT | 1.45 | 8.68 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:T N2 APARTMENT | 1.32 | 7.86 | 01-JAN-00:10 | 125.72 | 01-JAN-19:10 |
| Electricity:Zone:T S1 APARTMENT | 13.67 | 232.36 | 01-JAN-03:10 | 705.80 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:T S1 APARTMENT | 1.45 | 8.68 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:T S1 APARTMENT | 1.32 | 7.86 | 01-JAN-00:10 | 125.72 | 01-JAN-19:10 |
| Electricity:Zone:T S2 APARTMENT | 13.67 | 232.36 | 01-JAN-03:10 | 705.80 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:T S2 APARTMENT | 1.45 | 8.68 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:T S2 APARTMENT | 1.32 | 7.86 | 01-JAN-00:10 | 125.72 | 01-JAN-19:10 |
| Electricity:Zone:G CORRIDOR | 82.28 | 1494.09 | 01-JAN-00:10 | 4538.70 | 01-JAN-07:10 |
| InteriorLights:Electricity:Zone:G CORRIDOR | 11.69 | 370.63 | 01-JAN-00:10 | 370.63 | 01-JAN-00:10 |
| LightsWired:InteriorLights:Electricity:Zone:G CORRIDOR | 11.69 | 370.63 | 01-JAN-00:10 | 370.63 | 01-JAN-00:10 |
| Electricity:Zone:M CORRIDOR | 23.38 | 741.26 | 01-JAN-00:10 | 741.26 | 01-JAN-00:10 |
| InteriorLights:Electricity:Zone:M CORRIDOR | 23.38 | 741.26 | 01-JAN-00:10 | 741.26 | 01-JAN-00:10 |
| LightsWired:InteriorLights:Electricity:Zone:M CORRIDOR | 23.38 | 741.26 | 01-JAN-00:10 | 741.26 | 01-JAN-00:10 |
| Electricity:Zone:T CORRIDOR | 11.69 | 370.63 | 01-JAN-00:10 | 370.63 | 01-JAN-00:10 |
| InteriorLights:Electricity:Zone:T CORRIDOR | 11.69 | 370.63 | 01-JAN-00:10 | 370.63 | 01-JAN-00:10 |
| LightsWired:InteriorLights:Electricity:Zone:T CORRIDOR | 11.69 | 370.63 | 01-JAN-00:10 | 370.63 | 01-JAN-00:10 |
| LightsPlugIn:InteriorLights:Electricity | 4.27 | 25.50 | 01-JAN-00:10 | 407.87 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:G SW APARTMENT | 0.14 | 0.82 | 01-JAN-00:10 | 13.16 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:SpaceType:GENERAL | 4.27 | 25.50 | 01-JAN-00:10 | 407.87 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:G NW APARTMENT | 0.14 | 0.82 | 01-JAN-00:10 | 13.16 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:G NE APARTMENT | 0.14 | 0.82 | 01-JAN-00:10 | 13.16 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:G N1 APARTMENT | 0.14 | 0.82 | 01-JAN-00:10 | 13.16 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:G N2 APARTMENT | 0.14 | 0.82 | 01-JAN-00:10 | 13.16 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:G S1 APARTMENT | 0.14 | 0.82 | 01-JAN-00:10 | 13.16 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:G S2 APARTMENT | 0.14 | 0.82 | 01-JAN-00:10 | 13.16 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:M SW APARTMENT | 0.28 | 1.65 | 01-JAN-00:10 | 26.31 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:M NW APARTMENT | 0.28 | 1.65 | 01-JAN-00:10 | 26.31 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:M SE APARTMENT | 0.28 | 1.65 | 01-JAN-00:10 | 26.31 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:M NE APARTMENT | 0.28 | 1.65 | 01-JAN-00:10 | 26.31 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:M N1 APARTMENT | 0.28 | 1.65 | 01-JAN-00:10 | 26.31 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:M N2 APARTMENT | 0.28 | 1.65 | 01-JAN-00:10 | 26.31 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:M S1 APARTMENT | 0.28 | 1.65 | 01-JAN-00:10 | 26.31 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:M S2 APARTMENT | 0.28 | 1.65 | 01-JAN-00:10 | 26.31 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:T SW APARTMENT | 0.14 | 0.82 | 01-JAN-00:10 | 13.16 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:T NW APARTMENT | 0.14 | 0.82 | 01-JAN-00:10 | 13.16 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:T SE APARTMENT | 0.14 | 0.82 | 01-JAN-00:10 | 13.16 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:T NE APARTMENT | 0.14 | 0.82 | 01-JAN-00:10 | 13.16 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:T N1 APARTMENT | 0.14 | 0.82 | 01-JAN-00:10 | 13.16 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:T N2 APARTMENT | 0.14 | 0.82 | 01-JAN-00:10 | 13.16 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:T S1 APARTMENT | 0.14 | 0.82 | 01-JAN-00:10 | 13.16 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:T S2 APARTMENT | 0.14 | 0.82 | 01-JAN-00:10 | 13.16 | 01-JAN-19:10 |
| InteriorEquipment:Electricity | 458.66 | 8251.68 | 01-JAN-03:10 | 22709.69 | 03-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:G SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:SpaceType:GENERAL | 458.66 | 8251.68 | 01-JAN-03:10 | 22709.69 | 03-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity | 388.06 | 7128.22 | 01-JAN-03:10 | 18541.61 | 03-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:G SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 388.06 | 7128.22 | 01-JAN-03:10 | 18541.61 | 03-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:G NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:G NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:OFFICE | 9.47 | 194.25 | 01-JAN-00:10 | 588.62 | 03-JAN-08:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:OFFICE | 9.47 | 194.25 | 01-JAN-00:10 | 588.62 | 03-JAN-08:10 |
| InteriorEquipment:Electricity:Zone:G NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:G NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:G N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:G N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:G N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:G N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:G S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:G S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:G S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:G S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:M SW APARTMENT | 24.43 | 447.35 | 01-JAN-03:10 | 1177.25 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:M SW APARTMENT | 24.43 | 447.35 | 01-JAN-03:10 | 1177.25 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:M NW APARTMENT | 24.43 | 447.35 | 01-JAN-03:10 | 1177.25 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:M NW APARTMENT | 24.43 | 447.35 | 01-JAN-03:10 | 1177.25 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:M SE APARTMENT | 24.43 | 447.35 | 01-JAN-03:10 | 1177.25 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:M SE APARTMENT | 24.43 | 447.35 | 01-JAN-03:10 | 1177.25 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:M NE APARTMENT | 24.43 | 447.35 | 01-JAN-03:10 | 1177.25 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:M NE APARTMENT | 24.43 | 447.35 | 01-JAN-03:10 | 1177.25 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:M N1 APARTMENT | 24.43 | 447.35 | 01-JAN-03:10 | 1177.25 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:M N1 APARTMENT | 24.43 | 447.35 | 01-JAN-03:10 | 1177.25 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:M N2 APARTMENT | 24.43 | 447.35 | 01-JAN-03:10 | 1177.25 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:M N2 APARTMENT | 24.43 | 447.35 | 01-JAN-03:10 | 1177.25 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:M S1 APARTMENT | 24.43 | 447.35 | 01-JAN-03:10 | 1177.25 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:M S1 APARTMENT | 24.43 | 447.35 | 01-JAN-03:10 | 1177.25 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:M S2 APARTMENT | 24.43 | 447.35 | 01-JAN-03:10 | 1177.25 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:M S2 APARTMENT | 24.43 | 447.35 | 01-JAN-03:10 | 1177.25 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:T SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:T SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:T NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:T NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:T SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:T SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:T NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:T NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:T N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:T N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:T N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:T N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:T S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:T S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:T S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:T S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:G CORRIDOR | 70.59 | 1123.46 | 01-JAN-00:10 | 4168.07 | 01-JAN-07:10 |
| ElevatorLift:InteriorEquipment:Electricity | 65.48 | 961.46 | 01-JAN-00:10 | 4006.07 | 01-JAN-07:10 |
| ElevatorLift:InteriorEquipment:Electricity:Zone:G CORRIDOR | 65.48 | 961.46 | 01-JAN-00:10 | 4006.07 | 01-JAN-07:10 |
| ElevatorLift:InteriorEquipment:Electricity:SpaceType:GENERAL | 65.48 | 961.46 | 01-JAN-00:10 | 4006.07 | 01-JAN-07:10 |
| ElevatorLightsFan:InteriorEquipment:Electricity | 5.11 | 162.00 | 01-JAN-00:10 | 162.00 | 01-JAN-00:10 |
| ElevatorLightsFan:InteriorEquipment:Electricity:Zone:G CORRIDOR | 5.11 | 162.00 | 01-JAN-00:10 | 162.00 | 01-JAN-00:10 |
| ElevatorLightsFan:InteriorEquipment:Electricity:SpaceType:GENERAL | 5.11 | 162.00 | 01-JAN-00:10 | 162.00 | 01-JAN-00:10 |
| Fans:Electricity | 96.23 | 1666.47 | 17-MAY-16:10 | 8208.87 | 13-AUG-15:30 |
| Fans:Electricity:Zone:G SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:G SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:G NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:G NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:G NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:G NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:G N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:G N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:G N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:G N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:G S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:G S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:G S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:G S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:M SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:M SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:M NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:M NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:M SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:M SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:M NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:M NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:M N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:M N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:M N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:M N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:M S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:M S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:M S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:M S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:T SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:T SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:T NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:T NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:T SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:T SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:T NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:T NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:T N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:T N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:T N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:T N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:T S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:T S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:T S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:T S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| ElectricityPurchased:Facility | 1261.71 | 16919.74 | 25-MAY-02:30 | 89955.36 | 13-AUG-16:10 |
| ElectricityPurchased:Plant | 1261.71 | 16919.74 | 25-MAY-02:30 | 89955.36 | 13-AUG-16:10 |
| Cogeneration:ElectricityPurchased | 1261.71 | 16919.74 | 25-MAY-02:30 | 89955.36 | 13-AUG-16:10 |
| General:Cogeneration:ElectricityPurchased | 1261.71 | 16919.74 | 25-MAY-02:30 | 89955.36 | 13-AUG-16:10 |
| ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| ElectricityNet:Facility | 1261.71 | 16919.74 | 25-MAY-02:30 | 89955.36 | 13-AUG-16:10 |
| ElectricityNet:Plant | 1261.71 | 16919.74 | 25-MAY-02:30 | 89955.36 | 13-AUG-16:10 |
| Cogeneration:ElectricityNet | 1261.71 | 16919.74 | 25-MAY-02:30 | 89955.36 | 13-AUG-16:10 |
| General:Cogeneration:ElectricityNet | 1261.71 | 16919.74 | 25-MAY-02:30 | 89955.36 | 13-AUG-16:10 |
| Electricity:HVAC | 173.42 | 1666.47 | 17-MAY-16:10 | 32162.85 | 19-JUL-15:10 |
| HeatRecovery:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:HeatRecovery:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:Fans:Electricity | 96.23 | 1666.47 | 17-MAY-16:10 | 8208.87 | 13-AUG-15:30 |
| Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Cooling:Electricity | 77.19 | 0.00 | 01-JAN-00:10 | 24142.25 | 19-JUL-15:10 |
| General:Cooling:Electricity | 77.19 | 0.00 | 01-JAN-00:10 | 24142.25 | 19-JUL-15:10 |
| ExteriorLights:Electricity | 50.00 | 0.00 | 01-JAN-08:00 | 3183.33 | 01-JAN-00:10 |
| General:ExteriorLights:Electricity | 50.00 | 0.00 | 01-JAN-08:00 | 3183.33 | 01-JAN-00:10 |
| Electricity:Plant | 480.41 | 1950.00 | 01-JAN-00:10 | 42107.34 | 08-FEB-07:40 |
| WaterSystems:Electricity | 480.41 | 1950.00 | 01-JAN-00:10 | 42107.34 | 08-FEB-07:40 |
| Water Heater:WaterSystems:Electricity | 480.41 | 1950.00 | 01-JAN-00:10 | 42107.34 | 08-FEB-07:40 |
| Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
| NaturalGas:Facility | 612.52 | 0.00 | 14-MAR-10:10 | 123329.04 | 06-FEB-10:00 |
| NaturalGas:HVAC | 612.52 | 0.00 | 14-MAR-10:10 | 123329.04 | 06-FEB-10:00 |
| Heating:NaturalGas | 612.52 | 0.00 | 14-MAR-10:10 | 123329.04 | 06-FEB-10:00 |
| General:Heating:NaturalGas | 612.52 | 0.00 | 14-MAR-10:10 | 123329.04 | 06-FEB-10:00 |
| Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
| None |
| Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
| Water:Facility | 1875.32 | 0.00 | 01-JAN-02:10 | 0.00 | 01-JAN-07:10 |
| Water:Plant | 1875.32 | 0.00 | 01-JAN-02:10 | 0.00 | 01-JAN-07:10 |
| WaterSystems:Water | 1875.32 | 0.00 | 01-JAN-02:10 | 0.00 | 01-JAN-07:10 |
| Water Heater:WaterSystems:Water | 1875.32 | 0.00 | 01-JAN-02:10 | 0.00 | 01-JAN-07:10 |
| MainsWater:Facility | 1875.32 | 0.00 | 01-JAN-02:10 | 0.00 | 01-JAN-07:10 |
| MainsWater:Plant | 1875.32 | 0.00 | 01-JAN-02:10 | 0.00 | 01-JAN-07:10 |
| WaterSystems:MainsWater | 1875.32 | 0.00 | 01-JAN-02:10 | 0.00 | 01-JAN-07:10 |
| Water Heater:WaterSystems:MainsWater | 1875.32 | 0.00 | 01-JAN-02:10 | 0.00 | 01-JAN-07:10 |
| Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
| Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
| CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
| Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
| None |
| Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
| None |
| Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
| EnergyTransfer:Facility | 1398.04 | 1812.74 | 14-MAR-10:20 | 166522.82 | 06-FEB-10:00 |
| EnergyTransfer:Building | 599.20 | 1722.65 | 14-MAR-10:50 | 67859.58 | 06-FEB-10:00 |
| EnergyTransfer:Zone:G SW APARTMENT | 18.04 | 0.01 | 11-NOV-14:40 | 2293.11 | 07-FEB-08:20 |
| Heating:EnergyTransfer | 243.84 | 0.00 | 16-MAR-06:00 | 67859.58 | 06-FEB-10:00 |
| Heating:EnergyTransfer:Zone:G SW APARTMENT | 8.83 | 0.00 | 06-JAN-14:50 | 2293.11 | 07-FEB-08:20 |
| General:Heating:EnergyTransfer | 243.84 | 0.00 | 16-MAR-06:00 | 67859.58 | 06-FEB-10:00 |
| General:Heating:EnergyTransfer:Zone:G SW APARTMENT | 8.83 | 0.00 | 06-JAN-14:50 | 2293.11 | 07-FEB-08:20 |
| Cooling:EnergyTransfer | 355.36 | 0.00 | 01-JAN-00:10 | 61594.34 | 09-AUG-15:20 |
| Cooling:EnergyTransfer:Zone:G SW APARTMENT | 9.21 | 0.00 | 01-JAN-00:10 | 2122.52 | 21-SEP-16:10 |
| General:Cooling:EnergyTransfer | 355.36 | 0.00 | 01-JAN-00:10 | 61594.34 | 09-AUG-15:20 |
| General:Cooling:EnergyTransfer:Zone:G SW APARTMENT | 9.21 | 0.00 | 01-JAN-00:10 | 2122.52 | 21-SEP-16:10 |
| EnergyTransfer:Zone:G NW APARTMENT | 18.72 | 0.03 | 18-NOV-17:30 | 2464.09 | 07-FEB-08:20 |
| Heating:EnergyTransfer:Zone:G NW APARTMENT | 11.82 | 0.00 | 12-MAR-15:10 | 2464.09 | 07-FEB-08:20 |
| General:Heating:EnergyTransfer:Zone:G NW APARTMENT | 11.82 | 0.00 | 12-MAR-15:10 | 2464.09 | 07-FEB-08:20 |
| Cooling:EnergyTransfer:Zone:G NW APARTMENT | 6.90 | 0.00 | 01-JAN-00:10 | 1660.36 | 10-AUG-17:30 |
| General:Cooling:EnergyTransfer:Zone:G NW APARTMENT | 6.90 | 0.00 | 01-JAN-00:10 | 1660.36 | 10-AUG-17:30 |
| EnergyTransfer:Zone:OFFICE | 14.61 | 0.00 | 07-JUN-07:50 | 4918.12 | 06-FEB-09:10 |
| Heating:EnergyTransfer:Zone:OFFICE | 5.70 | 0.00 | 01-JAN-12:50 | 4918.12 | 06-FEB-09:10 |
| General:Heating:EnergyTransfer:Zone:OFFICE | 5.70 | 0.00 | 01-JAN-12:50 | 4918.12 | 06-FEB-09:10 |
| Cooling:EnergyTransfer:Zone:OFFICE | 8.91 | 0.00 | 01-JAN-00:10 | 3478.35 | 17-JUL-08:10 |
| General:Cooling:EnergyTransfer:Zone:OFFICE | 8.91 | 0.00 | 01-JAN-00:10 | 3478.35 | 17-JUL-08:10 |
| EnergyTransfer:Zone:G NE APARTMENT | 18.60 | 0.02 | 20-OCT-22:50 | 2374.72 | 07-FEB-08:10 |
| Heating:EnergyTransfer:Zone:G NE APARTMENT | 11.68 | 0.00 | 12-MAR-16:10 | 2374.72 | 07-FEB-08:10 |
| General:Heating:EnergyTransfer:Zone:G NE APARTMENT | 11.68 | 0.00 | 12-MAR-16:10 | 2374.72 | 07-FEB-08:10 |
| Cooling:EnergyTransfer:Zone:G NE APARTMENT | 6.92 | 0.00 | 01-JAN-00:10 | 1424.37 | 21-JUL-16:30 |
| General:Cooling:EnergyTransfer:Zone:G NE APARTMENT | 6.92 | 0.00 | 01-JAN-00:10 | 1424.37 | 21-JUL-16:30 |
| EnergyTransfer:Zone:G N1 APARTMENT | 12.56 | 0.02 | 09-APR-04:00 | 1502.69 | 07-FEB-08:20 |
| Heating:EnergyTransfer:Zone:G N1 APARTMENT | 5.71 | 0.00 | 12-MAR-10:50 | 1502.69 | 07-FEB-08:20 |
| General:Heating:EnergyTransfer:Zone:G N1 APARTMENT | 5.71 | 0.00 | 12-MAR-10:50 | 1502.69 | 07-FEB-08:20 |
| Cooling:EnergyTransfer:Zone:G N1 APARTMENT | 6.85 | 0.00 | 01-JAN-00:10 | 1153.49 | 21-JUL-17:10 |
| General:Cooling:EnergyTransfer:Zone:G N1 APARTMENT | 6.85 | 0.00 | 01-JAN-00:10 | 1153.49 | 21-JUL-17:10 |
| EnergyTransfer:Zone:G N2 APARTMENT | 12.56 | 0.01 | 29-APR-06:30 | 1502.21 | 07-FEB-08:20 |
| Heating:EnergyTransfer:Zone:G N2 APARTMENT | 5.70 | 0.00 | 12-MAR-10:50 | 1502.21 | 07-FEB-08:20 |
| General:Heating:EnergyTransfer:Zone:G N2 APARTMENT | 5.70 | 0.00 | 12-MAR-10:50 | 1502.21 | 07-FEB-08:20 |
| Cooling:EnergyTransfer:Zone:G N2 APARTMENT | 6.86 | 0.00 | 01-JAN-00:10 | 1153.65 | 21-JUL-17:10 |
| General:Cooling:EnergyTransfer:Zone:G N2 APARTMENT | 6.86 | 0.00 | 01-JAN-00:10 | 1153.65 | 21-JUL-17:10 |
| EnergyTransfer:Zone:G S1 APARTMENT | 13.08 | 0.01 | 10-MAY-11:50 | 1664.83 | 21-SEP-15:10 |
| Heating:EnergyTransfer:Zone:G S1 APARTMENT | 3.38 | 0.00 | 05-JAN-13:00 | 1333.41 | 07-FEB-08:20 |
| General:Heating:EnergyTransfer:Zone:G S1 APARTMENT | 3.38 | 0.00 | 05-JAN-13:00 | 1333.41 | 07-FEB-08:20 |
| Cooling:EnergyTransfer:Zone:G S1 APARTMENT | 9.70 | 0.00 | 01-JAN-00:10 | 1664.83 | 21-SEP-15:10 |
| General:Cooling:EnergyTransfer:Zone:G S1 APARTMENT | 9.70 | 0.00 | 01-JAN-00:10 | 1664.83 | 21-SEP-15:10 |
| EnergyTransfer:Zone:G S2 APARTMENT | 14.54 | 0.04 | 09-MAR-13:00 | 1715.28 | 21-SEP-15:10 |
| Heating:EnergyTransfer:Zone:G S2 APARTMENT | 4.34 | 0.00 | 06-JAN-11:00 | 1473.35 | 07-FEB-08:10 |
| General:Heating:EnergyTransfer:Zone:G S2 APARTMENT | 4.34 | 0.00 | 06-JAN-11:00 | 1473.35 | 07-FEB-08:10 |
| Cooling:EnergyTransfer:Zone:G S2 APARTMENT | 10.21 | 0.00 | 01-JAN-00:10 | 1715.28 | 21-SEP-15:10 |
| General:Cooling:EnergyTransfer:Zone:G S2 APARTMENT | 10.21 | 0.00 | 01-JAN-00:10 | 1715.28 | 21-SEP-15:10 |
| EnergyTransfer:Zone:M SW APARTMENT | 40.88 | 0.12 | 12-MAR-07:30 | 5434.87 | 21-SEP-16:10 |
| Heating:EnergyTransfer:Zone:M SW APARTMENT | 12.16 | 0.00 | 05-JAN-13:10 | 4350.13 | 06-FEB-10:00 |
| General:Heating:EnergyTransfer:Zone:M SW APARTMENT | 12.16 | 0.00 | 05-JAN-13:10 | 4350.13 | 06-FEB-10:00 |
| Cooling:EnergyTransfer:Zone:M SW APARTMENT | 28.72 | 0.00 | 01-JAN-00:10 | 5434.87 | 21-SEP-16:10 |
| General:Cooling:EnergyTransfer:Zone:M SW APARTMENT | 28.72 | 0.00 | 01-JAN-00:10 | 5434.87 | 21-SEP-16:10 |
| EnergyTransfer:Zone:M NW APARTMENT | 38.93 | 0.00 | 31-MAR-05:50 | 4538.51 | 06-FEB-10:00 |
| Heating:EnergyTransfer:Zone:M NW APARTMENT | 16.69 | 0.00 | 15-JAN-16:10 | 4538.51 | 06-FEB-10:00 |
| General:Heating:EnergyTransfer:Zone:M NW APARTMENT | 16.69 | 0.00 | 15-JAN-16:10 | 4538.51 | 06-FEB-10:00 |
| Cooling:EnergyTransfer:Zone:M NW APARTMENT | 22.23 | 0.00 | 01-JAN-00:10 | 4358.06 | 18-JUL-17:40 |
| General:Cooling:EnergyTransfer:Zone:M NW APARTMENT | 22.23 | 0.00 | 01-JAN-00:10 | 4358.06 | 18-JUL-17:40 |
| EnergyTransfer:Zone:M SE APARTMENT | 40.75 | 0.05 | 13-JAN-14:30 | 4766.79 | 21-SEP-13:30 |
| Heating:EnergyTransfer:Zone:M SE APARTMENT | 11.92 | 0.00 | 05-JAN-13:00 | 4268.44 | 06-FEB-10:00 |
| General:Heating:EnergyTransfer:Zone:M SE APARTMENT | 11.92 | 0.00 | 05-JAN-13:00 | 4268.44 | 06-FEB-10:00 |
| Cooling:EnergyTransfer:Zone:M SE APARTMENT | 28.83 | 0.00 | 01-JAN-00:10 | 4766.79 | 21-SEP-13:30 |
| General:Cooling:EnergyTransfer:Zone:M SE APARTMENT | 28.83 | 0.00 | 01-JAN-00:10 | 4766.79 | 21-SEP-13:30 |
| EnergyTransfer:Zone:M NE APARTMENT | 38.65 | 0.05 | 08-NOV-18:00 | 4459.94 | 06-FEB-10:00 |
| Heating:EnergyTransfer:Zone:M NE APARTMENT | 16.40 | 0.00 | 08-MAR-17:10 | 4459.94 | 06-FEB-10:00 |
| General:Heating:EnergyTransfer:Zone:M NE APARTMENT | 16.40 | 0.00 | 08-MAR-17:10 | 4459.94 | 06-FEB-10:00 |
| Cooling:EnergyTransfer:Zone:M NE APARTMENT | 22.25 | 0.00 | 01-JAN-00:10 | 3790.46 | 12-JUN-11:00 |
| General:Cooling:EnergyTransfer:Zone:M NE APARTMENT | 22.25 | 0.00 | 01-JAN-00:10 | 3790.46 | 12-JUN-11:00 |
| EnergyTransfer:Zone:M N1 APARTMENT | 26.84 | 0.01 | 18-DEC-16:50 | 2806.98 | 21-JUL-16:30 |
| Heating:EnergyTransfer:Zone:M N1 APARTMENT | 5.69 | 0.00 | 01-JAN-13:00 | 2315.85 | 06-FEB-10:00 |
| General:Heating:EnergyTransfer:Zone:M N1 APARTMENT | 5.69 | 0.00 | 01-JAN-13:00 | 2315.85 | 06-FEB-10:00 |
| Cooling:EnergyTransfer:Zone:M N1 APARTMENT | 21.15 | 0.00 | 01-JAN-00:10 | 2806.98 | 21-JUL-16:30 |
| General:Cooling:EnergyTransfer:Zone:M N1 APARTMENT | 21.15 | 0.00 | 01-JAN-00:10 | 2806.98 | 21-JUL-16:30 |
| EnergyTransfer:Zone:M N2 APARTMENT | 26.85 | 0.00 | 29-NOV-24:00 | 2809.91 | 21-JUL-16:30 |
| Heating:EnergyTransfer:Zone:M N2 APARTMENT | 5.68 | 0.00 | 01-JAN-13:00 | 2313.85 | 06-FEB-10:00 |
| General:Heating:EnergyTransfer:Zone:M N2 APARTMENT | 5.68 | 0.00 | 01-JAN-13:00 | 2313.85 | 06-FEB-10:00 |
| Cooling:EnergyTransfer:Zone:M N2 APARTMENT | 21.17 | 0.00 | 01-JAN-00:10 | 2809.91 | 21-JUL-16:30 |
| General:Cooling:EnergyTransfer:Zone:M N2 APARTMENT | 21.17 | 0.00 | 01-JAN-00:10 | 2809.91 | 21-JUL-16:30 |
| EnergyTransfer:Zone:M S1 APARTMENT | 32.27 | 0.04 | 22-NOV-04:40 | 4164.93 | 21-SEP-14:10 |
| Heating:EnergyTransfer:Zone:M S1 APARTMENT | 3.05 | 0.00 | 01-JAN-06:00 | 2083.65 | 06-FEB-10:00 |
| General:Heating:EnergyTransfer:Zone:M S1 APARTMENT | 3.05 | 0.00 | 01-JAN-06:00 | 2083.65 | 06-FEB-10:00 |
| Cooling:EnergyTransfer:Zone:M S1 APARTMENT | 29.22 | 0.00 | 01-JAN-00:10 | 4164.93 | 21-SEP-14:10 |
| General:Cooling:EnergyTransfer:Zone:M S1 APARTMENT | 29.22 | 0.00 | 01-JAN-00:10 | 4164.93 | 21-SEP-14:10 |
| EnergyTransfer:Zone:M S2 APARTMENT | 32.29 | 0.02 | 01-DEC-20:30 | 4171.46 | 21-SEP-14:10 |
| Heating:EnergyTransfer:Zone:M S2 APARTMENT | 3.05 | 0.00 | 01-JAN-06:00 | 2081.36 | 06-FEB-10:00 |
| General:Heating:EnergyTransfer:Zone:M S2 APARTMENT | 3.05 | 0.00 | 01-JAN-06:00 | 2081.36 | 06-FEB-10:00 |
| Cooling:EnergyTransfer:Zone:M S2 APARTMENT | 29.24 | 0.00 | 01-JAN-00:10 | 4171.46 | 21-SEP-14:10 |
| General:Cooling:EnergyTransfer:Zone:M S2 APARTMENT | 29.24 | 0.00 | 01-JAN-00:10 | 4171.46 | 21-SEP-14:10 |
| EnergyTransfer:Zone:T SW APARTMENT | 29.54 | 0.00 | 05-NOV-07:50 | 3797.75 | 06-FEB-10:00 |
| Heating:EnergyTransfer:Zone:T SW APARTMENT | 16.61 | 0.00 | 06-JAN-12:30 | 3797.75 | 06-FEB-10:00 |
| General:Heating:EnergyTransfer:Zone:T SW APARTMENT | 16.61 | 0.00 | 06-JAN-12:30 | 3797.75 | 06-FEB-10:00 |
| Cooling:EnergyTransfer:Zone:T SW APARTMENT | 12.94 | 0.00 | 01-JAN-00:10 | 3464.91 | 10-AUG-16:10 |
| General:Cooling:EnergyTransfer:Zone:T SW APARTMENT | 12.94 | 0.00 | 01-JAN-00:10 | 3464.91 | 10-AUG-16:10 |
| EnergyTransfer:Zone:T NW APARTMENT | 29.58 | 0.04 | 07-APR-08:20 | 3812.53 | 06-FEB-10:00 |
| Heating:EnergyTransfer:Zone:T NW APARTMENT | 19.55 | 0.00 | 08-MAR-14:30 | 3812.53 | 06-FEB-10:00 |
| General:Heating:EnergyTransfer:Zone:T NW APARTMENT | 19.55 | 0.00 | 08-MAR-14:30 | 3812.53 | 06-FEB-10:00 |
| Cooling:EnergyTransfer:Zone:T NW APARTMENT | 10.03 | 0.00 | 01-JAN-00:10 | 2956.10 | 18-JUL-17:20 |
| General:Cooling:EnergyTransfer:Zone:T NW APARTMENT | 10.03 | 0.00 | 01-JAN-00:10 | 2956.10 | 18-JUL-17:20 |
| EnergyTransfer:Zone:T SE APARTMENT | 29.31 | 0.14 | 18-OCT-13:00 | 3746.67 | 06-FEB-10:00 |
| Heating:EnergyTransfer:Zone:T SE APARTMENT | 16.42 | 0.00 | 06-JAN-11:00 | 3746.67 | 06-FEB-10:00 |
| General:Heating:EnergyTransfer:Zone:T SE APARTMENT | 16.42 | 0.00 | 06-JAN-11:00 | 3746.67 | 06-FEB-10:00 |
| Cooling:EnergyTransfer:Zone:T SE APARTMENT | 12.89 | 0.00 | 01-JAN-00:10 | 3194.72 | 21-JUL-13:30 |
| General:Cooling:EnergyTransfer:Zone:T SE APARTMENT | 12.89 | 0.00 | 01-JAN-00:10 | 3194.72 | 21-JUL-13:30 |
| EnergyTransfer:Zone:T NE APARTMENT | 29.23 | 0.01 | 07-OCT-12:00 | 3761.88 | 06-FEB-10:00 |
| Heating:EnergyTransfer:Zone:T NE APARTMENT | 19.32 | 0.00 | 12-MAR-10:10 | 3761.88 | 06-FEB-10:00 |
| General:Heating:EnergyTransfer:Zone:T NE APARTMENT | 19.32 | 0.00 | 12-MAR-10:10 | 3761.88 | 06-FEB-10:00 |
| Cooling:EnergyTransfer:Zone:T NE APARTMENT | 9.91 | 0.00 | 01-JAN-00:10 | 2605.81 | 12-JUN-11:20 |
| General:Cooling:EnergyTransfer:Zone:T NE APARTMENT | 9.91 | 0.00 | 01-JAN-00:10 | 2605.81 | 12-JUN-11:20 |
| EnergyTransfer:Zone:T N1 APARTMENT | 19.98 | 0.06 | 11-APR-12:10 | 2442.47 | 07-FEB-08:10 |
| Heating:EnergyTransfer:Zone:T N1 APARTMENT | 11.30 | 0.00 | 08-MAR-14:00 | 2442.47 | 07-FEB-08:10 |
| General:Heating:EnergyTransfer:Zone:T N1 APARTMENT | 11.30 | 0.00 | 08-MAR-14:00 | 2442.47 | 07-FEB-08:10 |
| Cooling:EnergyTransfer:Zone:T N1 APARTMENT | 8.68 | 0.00 | 01-JAN-00:10 | 1945.53 | 21-JUL-16:30 |
| General:Cooling:EnergyTransfer:Zone:T N1 APARTMENT | 8.68 | 0.00 | 01-JAN-00:10 | 1945.53 | 21-JUL-16:30 |
| EnergyTransfer:Zone:T N2 APARTMENT | 19.99 | 0.06 | 24-OCT-18:40 | 2440.74 | 07-FEB-08:10 |
| Heating:EnergyTransfer:Zone:T N2 APARTMENT | 11.29 | 0.00 | 08-MAR-13:50 | 2440.74 | 07-FEB-08:10 |
| General:Heating:EnergyTransfer:Zone:T N2 APARTMENT | 11.29 | 0.00 | 08-MAR-13:50 | 2440.74 | 07-FEB-08:10 |
| Cooling:EnergyTransfer:Zone:T N2 APARTMENT | 8.69 | 0.00 | 01-JAN-00:10 | 1945.42 | 21-JUL-16:30 |
| General:Cooling:EnergyTransfer:Zone:T N2 APARTMENT | 8.69 | 0.00 | 01-JAN-00:10 | 1945.42 | 21-JUL-16:30 |
| EnergyTransfer:Zone:T S1 APARTMENT | 20.69 | 0.01 | 31-MAR-22:00 | 2684.37 | 21-SEP-14:10 |
| Heating:EnergyTransfer:Zone:T S1 APARTMENT | 8.78 | 0.00 | 04-JAN-12:30 | 2405.10 | 07-FEB-05:00 |
| General:Heating:EnergyTransfer:Zone:T S1 APARTMENT | 8.78 | 0.00 | 04-JAN-12:30 | 2405.10 | 07-FEB-05:00 |
| Cooling:EnergyTransfer:Zone:T S1 APARTMENT | 11.91 | 0.00 | 01-JAN-00:10 | 2684.37 | 21-SEP-14:10 |
| General:Cooling:EnergyTransfer:Zone:T S1 APARTMENT | 11.91 | 0.00 | 01-JAN-00:10 | 2684.37 | 21-SEP-14:10 |
| EnergyTransfer:Zone:T S2 APARTMENT | 20.72 | 0.03 | 25-MAR-18:50 | 2691.81 | 21-SEP-14:10 |
| Heating:EnergyTransfer:Zone:T S2 APARTMENT | 8.78 | 0.00 | 04-JAN-12:30 | 2406.08 | 07-FEB-05:00 |
| General:Heating:EnergyTransfer:Zone:T S2 APARTMENT | 8.78 | 0.00 | 04-JAN-12:30 | 2406.08 | 07-FEB-05:00 |
| Cooling:EnergyTransfer:Zone:T S2 APARTMENT | 11.94 | 0.00 | 01-JAN-00:10 | 2691.81 | 21-SEP-14:10 |
| General:Cooling:EnergyTransfer:Zone:T S2 APARTMENT | 11.94 | 0.00 | 01-JAN-00:10 | 2691.81 | 21-SEP-14:10 |
| EnergyTransfer:Zone:T CORRIDOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Heating:EnergyTransfer:Zone:T CORRIDOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:Heating:EnergyTransfer:Zone:T CORRIDOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Cooling:EnergyTransfer:Zone:T CORRIDOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:Cooling:EnergyTransfer:Zone:T CORRIDOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| EnergyTransfer:Zone:G CORRIDOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Heating:EnergyTransfer:Zone:G CORRIDOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:Heating:EnergyTransfer:Zone:G CORRIDOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Cooling:EnergyTransfer:Zone:G CORRIDOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:Cooling:EnergyTransfer:Zone:G CORRIDOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| EnergyTransfer:Zone:M CORRIDOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Heating:EnergyTransfer:Zone:M CORRIDOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:Heating:EnergyTransfer:Zone:M CORRIDOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Cooling:EnergyTransfer:Zone:M CORRIDOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:Cooling:EnergyTransfer:Zone:M CORRIDOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| EnergyTransfer:HVAC | 798.84 | 0.00 | 14-MAR-10:10 | 98663.23 | 06-FEB-10:00 |
| HeatRecoveryForHeating:EnergyTransfer | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 21-JUL-15:00 |
| HeatRecoveryForCooling:EnergyTransfer | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 17-JUN-16:10 |
| HeatingCoils:EnergyTransfer | 490.02 | 0.00 | 14-MAR-10:10 | 98663.23 | 06-FEB-10:00 |
| CoolingCoils:EnergyTransfer | 308.82 | 0.00 | 01-JAN-00:10 | 91730.40 | 13-AUG-15:30 |
| PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 09:14:20
Annual Building Sensible Heat Gain Components| HVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
| G SW APARTMENT | 0.189 | -12.393 | 18.002 | -6.171 | 0.000 | 0.000 | 3.928 | 1.454 | 12.213 | 10.280 | 0.000 | 0.060 | 0.000 | 0.000 | -6.442 | 0.000 | -6.032 | -15.087 |
| G NW APARTMENT | 0.192 | -12.269 | 21.671 | -4.678 | 0.000 | 0.000 | 4.001 | 1.454 | 12.213 | 5.602 | 0.000 | 0.061 | 0.000 | 0.000 | -6.644 | 0.000 | -5.916 | -15.687 |
| OFFICE | 0.000 | 0.000 | 5.702 | -8.905 | 0.000 | 0.000 | 2.166 | 7.396 | 9.469 | 10.243 | 0.000 | 0.031 | 0.000 | 0.000 | -6.023 | 0.000 | -4.869 | -15.208 |
| G NE APARTMENT | 0.192 | -12.274 | 21.491 | -4.656 | 0.000 | 0.000 | 4.003 | 1.454 | 12.213 | 5.527 | 0.000 | 0.060 | 0.000 | 0.000 | -6.510 | 0.000 | -5.926 | -15.575 |
| G N1 APARTMENT | 0.192 | -12.321 | 15.035 | -4.053 | 0.000 | 0.000 | 3.990 | 1.454 | 12.213 | 2.045 | 0.000 | 0.037 | 0.000 | 0.000 | -4.198 | 0.000 | -3.896 | -10.497 |
| G N2 APARTMENT | 0.192 | -12.322 | 15.028 | -4.056 | 0.000 | 0.000 | 3.990 | 1.454 | 12.213 | 2.044 | 0.000 | 0.037 | 0.000 | 0.000 | -4.198 | 0.000 | -3.896 | -10.486 |
| G S1 APARTMENT | 0.189 | -12.490 | 11.648 | -5.670 | 0.000 | 0.000 | 3.908 | 1.454 | 12.213 | 6.765 | 0.000 | 0.036 | 0.000 | 0.000 | -3.967 | 0.000 | -4.012 | -10.074 |
| G S2 APARTMENT | 0.189 | -12.501 | 12.722 | -6.280 | 0.000 | 0.000 | 3.906 | 1.454 | 12.213 | 6.762 | 0.000 | 0.036 | 0.000 | 0.000 | -3.960 | 0.000 | -4.019 | -10.520 |
| M SW APARTMENT | 0.377 | -25.327 | 28.079 | -19.690 | 0.000 | 0.000 | 7.744 | 2.908 | 24.426 | 20.041 | 0.000 | 0.168 | 0.000 | 0.000 | -13.579 | 0.000 | -17.446 | -7.701 |
| M NW APARTMENT | 0.377 | -25.032 | 34.537 | -15.423 | 0.000 | 0.000 | 7.897 | 2.908 | 24.426 | 10.776 | 0.000 | 0.169 | 0.000 | 0.000 | -14.034 | 0.000 | -17.149 | -9.453 |
| M SE APARTMENT | 0.377 | -25.345 | 27.797 | -19.742 | 0.000 | 0.000 | 7.745 | 2.908 | 24.426 | 19.976 | 0.000 | 0.168 | 0.000 | 0.000 | -13.381 | 0.000 | -17.468 | -7.461 |
| M NE APARTMENT | 0.377 | -25.056 | 34.214 | -15.378 | 0.000 | 0.000 | 7.897 | 2.908 | 24.426 | 10.614 | 0.000 | 0.168 | 0.000 | 0.000 | -13.746 | 0.000 | -17.184 | -9.241 |
| M N1 APARTMENT | 0.377 | -25.168 | 21.815 | -12.491 | 0.000 | 0.000 | 7.868 | 2.908 | 24.426 | 3.886 | 0.000 | 0.102 | 0.000 | 0.000 | -8.839 | 0.000 | -11.230 | -3.652 |
| M N2 APARTMENT | 0.377 | -25.171 | 21.804 | -12.502 | 0.000 | 0.000 | 7.867 | 2.908 | 24.426 | 3.884 | 0.000 | 0.102 | 0.000 | 0.000 | -8.840 | 0.000 | -11.233 | -3.622 |
| M S1 APARTMENT | 0.377 | -25.565 | 16.028 | -17.004 | 0.000 | 0.000 | 7.695 | 2.908 | 24.426 | 13.248 | 0.000 | 0.102 | 0.000 | 0.000 | -8.344 | 0.000 | -11.509 | -2.362 |
| M S2 APARTMENT | 0.377 | -25.566 | 16.021 | -17.025 | 0.000 | 0.000 | 7.695 | 2.908 | 24.426 | 13.247 | 0.000 | 0.102 | 0.001 | 0.000 | -8.343 | 0.000 | -11.510 | -2.330 |
| T SW APARTMENT | 0.188 | -12.404 | 25.996 | -10.112 | 0.000 | 0.000 | 3.932 | 1.454 | 12.213 | 10.007 | 0.000 | 0.110 | 0.000 | 0.000 | -6.447 | 0.000 | -11.177 | -13.760 |
| T NW APARTMENT | 0.188 | -12.295 | 29.482 | -7.860 | 0.000 | 0.000 | 3.999 | 1.454 | 12.213 | 5.398 | 0.000 | 0.110 | 0.000 | 0.000 | -6.699 | 0.000 | -11.013 | -14.977 |
| T SE APARTMENT | 0.188 | -12.424 | 25.786 | -10.018 | 0.000 | 0.000 | 3.933 | 1.454 | 12.213 | 9.979 | 0.000 | 0.110 | 0.000 | 0.000 | -6.358 | 0.000 | -11.216 | -13.646 |
| T NE APARTMENT | 0.188 | -12.320 | 29.246 | -7.698 | 0.000 | 0.000 | 3.999 | 1.454 | 12.213 | 5.320 | 0.000 | 0.110 | 0.000 | 0.000 | -6.563 | 0.000 | -11.066 | -14.882 |
| T N1 APARTMENT | 0.188 | -12.351 | 20.922 | -6.141 | 0.000 | 0.000 | 3.986 | 1.454 | 12.213 | 1.959 | 0.000 | 0.066 | 0.000 | 0.000 | -4.233 | 0.000 | -7.127 | -10.936 |
| T N2 APARTMENT | 0.188 | -12.354 | 20.918 | -6.152 | 0.000 | 0.000 | 3.986 | 1.454 | 12.213 | 1.957 | 0.000 | 0.066 | 0.000 | 0.000 | -4.233 | 0.000 | -7.132 | -10.912 |
| T S1 APARTMENT | 0.188 | -12.494 | 17.551 | -8.374 | 0.000 | 0.000 | 3.913 | 1.454 | 12.213 | 6.627 | 0.000 | 0.066 | 0.000 | 0.000 | -3.971 | 0.000 | -7.287 | -9.887 |
| T S2 APARTMENT | 0.188 | -12.496 | 17.551 | -8.399 | 0.000 | 0.000 | 3.913 | 1.454 | 12.213 | 6.625 | 0.000 | 0.066 | 0.000 | 0.000 | -3.970 | 0.000 | -7.289 | -9.858 |
| T CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 6.520 | 11.688 | 0.000 | 0.828 | 0.000 | 0.004 | 0.000 | 0.000 | -0.662 | 0.000 | -1.721 | -16.658 |
| G CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 6.874 | 11.688 | 3.530 | 2.555 | 0.000 | 0.135 | 9.566 | 0.000 | -1.782 | 0.000 | -32.566 | -0.002 |
| M CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 12.258 | 23.376 | 0.000 | 1.624 | 0.000 | 0.010 | 0.000 | 0.000 | -1.433 | 0.000 | -2.817 | -33.018 |
| Total Facility | 5.860 | -387.939 | 509.046 | -238.479 | 0.000 | 0.000 | 149.612 | 99.229 | 391.594 | 197.817 | 0.000 | 2.289 | 9.566 | 0.000 | -177.398 | 0.000 | -263.706 | -297.492 |
| Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
| G SW APARTMENT | 21-SEP-16:04 | 0.00 | 82.60 | 0.00 | -2205.34 | 0.00 | 0.00 | 0.00 | 86.80 | 588.62 | 2050.40 | 0.00 | 8.47 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -611.56 |
| G NW APARTMENT | 10-AUG-17:30 | 0.00 | 136.65 | 0.00 | -1797.19 | 0.00 | 0.00 | 145.49 | 117.18 | 588.62 | 1418.93 | 0.00 | 40.10 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -649.78 |
| OFFICE | 11-SEP-08:62 | 0.00 | 0.00 | 0.00 | -5908.93 | 0.00 | 0.00 | 284.40 | 582.92 | 588.62 | 1516.03 | 0.00 | 0.00 | 3033.67 | 0.00 | -0.00 | 0.00 | -96.71 | 0.00 |
| G NE APARTMENT | 21-JUL-16:25 | 0.00 | 180.51 | 0.00 | -1605.28 | 0.00 | 0.00 | 86.96 | 86.80 | 588.62 | 601.10 | 0.00 | 60.17 | 1.11 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| G N1 APARTMENT | 21-JUL-17:05 | 0.00 | 172.76 | 0.00 | -1326.46 | 0.00 | 0.00 | 145.49 | 117.18 | 588.62 | 239.68 | 0.00 | 41.49 | 21.22 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| G N2 APARTMENT | 21-JUL-17:05 | 0.00 | 172.76 | 0.00 | -1326.62 | 0.00 | 0.00 | 145.49 | 117.18 | 588.62 | 239.68 | 0.00 | 41.49 | 21.40 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| G S1 APARTMENT | 21-SEP-15:10 | 0.00 | 85.21 | 0.00 | -1750.02 | 0.00 | 0.00 | 0.00 | 60.76 | 470.90 | 1287.02 | 0.00 | 7.80 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -161.67 |
| G S2 APARTMENT | 21-SEP-15:10 | 0.00 | 85.21 | 0.00 | -1800.46 | 0.00 | 0.00 | 0.00 | 60.76 | 470.90 | 1286.44 | 0.00 | 7.80 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -110.64 |
| M SW APARTMENT | 21-SEP-16:10 | 0.00 | 165.20 | 0.00 | -5601.90 | 0.00 | 0.00 | 0.00 | 173.60 | 1177.25 | 4087.88 | 0.00 | 24.10 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -26.12 |
| M NW APARTMENT | 18-JUL-17:40 | 0.00 | 241.15 | 0.00 | -4599.11 | 0.00 | 0.00 | 290.97 | 234.36 | 1177.25 | 3034.81 | 0.00 | 75.82 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -455.25 |
| M SE APARTMENT | 21-SEP-13:30 | 0.00 | 120.72 | 0.00 | -4887.39 | 0.00 | 0.00 | 0.00 | 34.72 | 765.21 | 4159.50 | 0.00 | 31.78 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -224.54 |
| M NE APARTMENT | 12-JUN-11:00 | 0.00 | 345.06 | 0.00 | -4135.44 | 0.00 | 0.00 | 83.61 | 34.72 | 824.07 | 2185.38 | 0.00 | 342.00 | 320.60 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| M N1 APARTMENT | 21-JUL-16:30 | 0.00 | 361.02 | 0.00 | -3168.33 | 0.00 | 0.00 | 173.92 | 173.60 | 1177.25 | 726.84 | 0.00 | 103.91 | 451.80 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| M N2 APARTMENT | 21-JUL-16:30 | 0.00 | 361.02 | 0.00 | -3171.26 | 0.00 | 0.00 | 173.92 | 173.60 | 1177.25 | 726.80 | 0.00 | 103.91 | 454.77 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| M S1 APARTMENT | 21-SEP-14:10 | 0.00 | 144.54 | 0.00 | -4309.38 | 0.00 | 0.00 | 0.00 | 60.77 | 800.53 | 3429.26 | 0.00 | 23.86 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -149.57 |
| M S2 APARTMENT | 21-SEP-14:10 | 0.00 | 144.53 | 0.00 | -4315.91 | 0.00 | 0.00 | 0.00 | 60.77 | 800.53 | 3429.19 | 0.00 | 23.86 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -142.97 |
| T SW APARTMENT | 10-AUG-16:04 | 0.00 | 182.17 | 0.00 | -3647.27 | 0.00 | 0.00 | 0.00 | 86.80 | 588.62 | 1791.27 | 0.00 | 132.33 | 866.08 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| T NW APARTMENT | 18-JUL-17:15 | 0.00 | 137.13 | 0.00 | -3093.46 | 0.00 | 0.00 | 145.49 | 117.18 | 588.62 | 1540.79 | 0.00 | 62.66 | 501.58 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| T SE APARTMENT | 21-JUL-13:30 | 0.00 | 242.56 | 0.00 | -3437.15 | 0.00 | 0.00 | 0.00 | 17.36 | 382.60 | 1423.28 | 0.00 | 157.98 | 1213.37 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| T NE APARTMENT | 12-JUN-11:20 | 0.00 | 177.67 | 0.00 | -2783.47 | 0.00 | 0.00 | 41.81 | 17.36 | 406.15 | 984.58 | 0.00 | 222.06 | 933.85 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| T N1 APARTMENT | 21-JUL-16:30 | 0.00 | 180.40 | 0.00 | -2126.02 | 0.00 | 0.00 | 86.96 | 86.80 | 588.62 | 355.12 | 0.00 | 68.20 | 759.92 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| T N2 APARTMENT | 21-JUL-16:30 | 0.00 | 180.40 | 0.00 | -2125.92 | 0.00 | 0.00 | 86.96 | 86.80 | 588.62 | 355.11 | 0.00 | 68.20 | 759.83 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| T S1 APARTMENT | 21-SEP-14:10 | 0.00 | 72.26 | 0.00 | -2756.57 | 0.00 | 0.00 | 0.00 | 30.38 | 400.26 | 1701.13 | 0.00 | 15.41 | 537.13 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| T S2 APARTMENT | 21-SEP-14:10 | 0.00 | 72.26 | 0.00 | -2764.01 | 0.00 | 0.00 | 0.00 | 30.38 | 400.26 | 1701.05 | 0.00 | 15.41 | 544.65 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| T CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| G CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Total Facility | 09-AUG-15:20 | 0.00 | 5821.23 | 0.00 | -67415.65 | 0.00 | 0.00 | 1392.46 | 3948.92 | 15334.78 | 32603.73 | 0.00 | 2359.23 | 5955.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
| G SW APARTMENT | 07-FEB-08:12 | -1105.68 | 0.00 | 3399.75 | 0.00 | 0.00 | 0.00 | 0.00 | 26.04 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -253.71 | 0.00 | -791.81 | -1663.08 |
| G NW APARTMENT | 07-FEB-08:12 | -1105.68 | 0.00 | 3570.67 | 0.00 | 0.00 | 0.00 | 76.05 | 26.04 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -627.38 | 0.00 | -791.81 | -1536.38 |
| OFFICE | 17-JAN-07:01 | 0.00 | 0.00 | 9717.86 | 0.00 | 0.00 | 0.00 | 0.00 | 116.58 | 294.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -237.26 | 0.00 | -140.34 | -9751.15 |
| G NE APARTMENT | 07-FEB-08:10 | -1105.69 | 0.00 | 3480.87 | 0.00 | 0.00 | 0.00 | 76.05 | 26.04 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -218.14 | 0.00 | -791.81 | -1855.80 |
| G N1 APARTMENT | 07-FEB-08:12 | -1105.81 | 0.00 | 2609.36 | 0.00 | 0.00 | 0.00 | 76.05 | 26.04 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -377.91 | 0.00 | -477.60 | -1138.61 |
| G N2 APARTMENT | 07-FEB-08:12 | -1105.81 | 0.00 | 2608.87 | 0.00 | 0.00 | 0.00 | 76.05 | 26.04 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -377.92 | 0.00 | -477.60 | -1138.13 |
| G S1 APARTMENT | 07-FEB-08:12 | -1105.81 | 0.00 | 2440.11 | 0.00 | 0.00 | 0.00 | 0.00 | 26.04 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2.89 | 0.00 | -477.60 | -1268.34 |
| G S2 APARTMENT | 07-FEB-08:10 | -1105.83 | 0.00 | 2579.64 | 0.00 | 0.00 | 0.00 | 0.00 | 26.04 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -76.30 | 0.00 | -477.60 | -1334.45 |
| M SW APARTMENT | 06-FEB-10:00 | -2174.45 | 0.00 | 6524.52 | 0.00 | 0.00 | 0.00 | 0.00 | 34.72 | 788.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -830.25 | 0.00 | -2728.98 | -1614.31 |
| M NW APARTMENT | 06-FEB-10:00 | -2174.61 | 0.00 | 6713.07 | 0.00 | 0.00 | 0.00 | 97.50 | 34.72 | 788.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -951.54 | 0.00 | -2728.98 | -1778.91 |
| M SE APARTMENT | 06-FEB-10:00 | -2174.45 | 0.00 | 6442.82 | 0.00 | 0.00 | 0.00 | 0.00 | 34.72 | 788.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -708.90 | 0.00 | -2728.98 | -1653.97 |
| M NE APARTMENT | 06-FEB-10:00 | -2174.61 | 0.00 | 6634.50 | 0.00 | 0.00 | 0.00 | 97.50 | 34.72 | 788.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -830.11 | 0.00 | -2728.98 | -1821.76 |
| M N1 APARTMENT | 06-FEB-10:00 | -2174.79 | 0.00 | 4490.61 | 0.00 | 0.00 | 0.00 | 97.50 | 34.72 | 788.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -565.91 | 0.00 | -1646.05 | -1024.83 |
| M N2 APARTMENT | 06-FEB-10:00 | -2174.79 | 0.00 | 4488.61 | 0.00 | 0.00 | 0.00 | 97.50 | 34.72 | 788.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -565.93 | 0.00 | -1646.05 | -1022.80 |
| M S1 APARTMENT | 06-FEB-10:00 | -2174.61 | 0.00 | 4258.22 | 0.00 | 0.00 | 0.00 | 0.00 | 34.72 | 788.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -444.28 | 0.00 | -1646.05 | -816.74 |
| M S2 APARTMENT | 06-FEB-10:00 | -2174.61 | 0.00 | 4255.93 | 0.00 | 0.00 | 0.00 | 0.00 | 34.72 | 788.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -444.32 | 0.00 | -1646.05 | -814.42 |
| T SW APARTMENT | 06-FEB-10:00 | -1087.19 | 0.00 | 4884.90 | 0.00 | 0.00 | 0.00 | 0.00 | 17.36 | 394.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -399.35 | 0.00 | -1806.95 | -2003.14 |
| T NW APARTMENT | 06-FEB-10:00 | -1087.26 | 0.00 | 4899.76 | 0.00 | 0.00 | 0.00 | 48.75 | 17.36 | 394.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -459.99 | 0.00 | -1806.95 | -2006.04 |
| T SE APARTMENT | 06-FEB-10:00 | -1087.19 | 0.00 | 4833.82 | 0.00 | 0.00 | 0.00 | 0.00 | 17.36 | 394.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -338.17 | 0.00 | -1806.95 | -2013.24 |
| T NE APARTMENT | 06-FEB-10:00 | -1087.26 | 0.00 | 4849.11 | 0.00 | 0.00 | 0.00 | 48.75 | 17.36 | 394.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -398.79 | 0.00 | -1806.95 | -2016.59 |
| T N1 APARTMENT | 07-FEB-08:10 | -1105.65 | 0.00 | 3548.57 | 0.00 | 0.00 | 0.00 | 76.05 | 26.04 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -399.91 | 0.00 | -909.39 | -1624.20 |
| T N2 APARTMENT | 07-FEB-08:10 | -1105.65 | 0.00 | 3546.84 | 0.00 | 0.00 | 0.00 | 76.05 | 26.04 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -399.92 | 0.00 | -909.39 | -1622.46 |
| T S1 APARTMENT | 07-FEB-05:00 | -1105.87 | 0.00 | 3510.97 | 0.00 | 0.00 | 0.00 | 194.99 | 26.04 | 223.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -501.37 | 0.00 | -796.54 | -1551.91 |
| T S2 APARTMENT | 07-FEB-05:00 | -1105.87 | 0.00 | 3511.95 | 0.00 | 0.00 | 0.00 | 194.99 | 26.04 | 223.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -501.36 | 0.00 | -796.54 | -1552.90 |
| T CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| G CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Total Facility | 07-FEB-08:61 | -34277.13 | 0.00 | 104641.97 | 0.00 | 0.00 | 0.00 | 2197.43 | 2872.71 | 12840.25 | 707.40 | 0.00 | 0.00 | 0.00 | 0.00 | -8990.99 | 0.00 | -32068.32 | -47923.31 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 09:14:20
System Ventilation Requirements for Cooling| Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
| SPLIT GSW | 0.3429 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.3429 | 0.0757 | 1.0000 | Not calculated | 0.0260 | 0.0757 | ||
| SPLIT GNW | 0.3222 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.3222 | 0.0806 | 1.0000 | Not calculated | 0.0260 | 0.0806 | ||
| SPLIT OFFICE | 0.3804 | 0.0000 | 4.7495 | 1.0000 | Calculated from schedules | 0.0381 | 0.3804 | 0.1002 | 1.0000 | Not calculated | 0.0381 | 0.1002 | ||
| SPLIT GNE | 0.2874 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.2874 | 0.0903 | 1.0000 | Not calculated | 0.0260 | 0.0903 | ||
| SPLIT GN1 | 0.2630 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.2630 | 0.0987 | 1.0000 | Not calculated | 0.0260 | 0.0987 | ||
| SPLIT GN2 | 0.2624 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.2624 | 0.0989 | 1.0000 | Not calculated | 0.0260 | 0.0989 | ||
| SPLIT GS1 | 0.2858 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.2858 | 0.0908 | 1.0000 | Not calculated | 0.0260 | 0.0908 | ||
| SPLIT GS2 | 0.2877 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.2877 | 0.0902 | 1.0000 | Not calculated | 0.0260 | 0.0902 | ||
| SPLIT MSW | 0.8688 | 0.0000 | 5.0000 | 1.0000 | Calculated from schedules | 0.0519 | 0.8688 | 0.0597 | 1.0000 | Not calculated | 0.0519 | 0.0597 | ||
| SPLIT MNW | 0.8365 | 0.0000 | 5.0000 | 1.0000 | Calculated from schedules | 0.0519 | 0.8365 | 0.0621 | 1.0000 | Not calculated | 0.0519 | 0.0621 | ||
| SPLIT MSE | 0.7652 | 0.0000 | 5.0000 | 1.0000 | Calculated from schedules | 0.0519 | 0.7652 | 0.0678 | 1.0000 | Not calculated | 0.0519 | 0.0678 | ||
| SPLIT MNE | 0.7338 | 0.0000 | 5.0000 | 1.0000 | Calculated from schedules | 0.0519 | 0.7338 | 0.0707 | 1.0000 | Not calculated | 0.0519 | 0.0707 | ||
| SPLIT MN1 | 0.6592 | 0.0000 | 5.0000 | 1.0000 | Calculated from schedules | 0.0519 | 0.6592 | 0.0787 | 1.0000 | Not calculated | 0.0519 | 0.0787 | ||
| SPLIT MN2 | 0.6575 | 0.0000 | 5.0000 | 1.0000 | Calculated from schedules | 0.0519 | 0.6575 | 0.0790 | 1.0000 | Not calculated | 0.0519 | 0.0790 | ||
| SPLIT MS1 | 0.6969 | 0.0000 | 5.0000 | 1.0000 | Calculated from schedules | 0.0519 | 0.6969 | 0.0745 | 1.0000 | Not calculated | 0.0519 | 0.0745 | ||
| SPLIT MS2 | 0.6951 | 0.0000 | 5.0000 | 1.0000 | Calculated from schedules | 0.0519 | 0.6951 | 0.0747 | 1.0000 | Not calculated | 0.0519 | 0.0747 | ||
| SPLIT TSW | 0.4777 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.4777 | 0.0543 | 1.0000 | Not calculated | 0.0260 | 0.0543 | ||
| SPLIT TNW | 0.4710 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.4710 | 0.0551 | 1.0000 | Not calculated | 0.0260 | 0.0551 | ||
| SPLIT TSE | 0.4026 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.4026 | 0.0645 | 1.0000 | Not calculated | 0.0260 | 0.0645 | ||
| SPLIT TNE | 0.3958 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.3958 | 0.0656 | 1.0000 | Not calculated | 0.0260 | 0.0656 | ||
| SPLIT TN1 | 0.3719 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.3719 | 0.0698 | 1.0000 | Not calculated | 0.0260 | 0.0698 | ||
| SPLIT TN2 | 0.3695 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.3695 | 0.0702 | 1.0000 | Not calculated | 0.0260 | 0.0702 | ||
| SPLIT TS1 | 0.3801 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.3801 | 0.0683 | 1.0000 | Not calculated | 0.0260 | 0.0683 | ||
| SPLIT TS2 | 0.3778 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.3778 | 0.0687 | 1.0000 | Not calculated | 0.0260 | 0.0687 |
| Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
| SPLIT GSW | 0.3429 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.3429 | 1.0000 | 1.0000 | Not calculated | 0.0260 | 0.0757 | ||
| SPLIT GNW | 0.3222 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.3222 | 1.0000 | 1.0000 | Not calculated | 0.0260 | 0.0806 | ||
| SPLIT OFFICE | 0.3804 | 0.0000 | 4.7495 | 1.0000 | Calculated from schedules | 0.0381 | 0.3804 | 1.0000 | 1.0000 | Not calculated | 0.0381 | 0.1002 | ||
| SPLIT GNE | 0.2874 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.2874 | 1.0000 | 1.0000 | Not calculated | 0.0260 | 0.0903 | ||
| SPLIT GN1 | 0.2630 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.2630 | 1.0000 | 1.0000 | Not calculated | 0.0260 | 0.0987 | ||
| SPLIT GN2 | 0.2624 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.2624 | 1.0000 | 1.0000 | Not calculated | 0.0260 | 0.0989 | ||
| SPLIT GS1 | 0.2858 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.2858 | 1.0000 | 1.0000 | Not calculated | 0.0260 | 0.0908 | ||
| SPLIT GS2 | 0.2877 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.2877 | 1.0000 | 1.0000 | Not calculated | 0.0260 | 0.0902 | ||
| SPLIT MSW | 0.8688 | 0.0000 | 5.0000 | 1.0000 | Calculated from schedules | 0.0519 | 0.8688 | 1.0000 | 1.0000 | Not calculated | 0.0519 | 0.0597 | ||
| SPLIT MNW | 0.8365 | 0.0000 | 5.0000 | 1.0000 | Calculated from schedules | 0.0519 | 0.8365 | 1.0000 | 1.0000 | Not calculated | 0.0519 | 0.0621 | ||
| SPLIT MSE | 0.7652 | 0.0000 | 5.0000 | 1.0000 | Calculated from schedules | 0.0519 | 0.7652 | 1.0000 | 1.0000 | Not calculated | 0.0519 | 0.0678 | ||
| SPLIT MNE | 0.7338 | 0.0000 | 5.0000 | 1.0000 | Calculated from schedules | 0.0519 | 0.7338 | 1.0000 | 1.0000 | Not calculated | 0.0519 | 0.0707 | ||
| SPLIT MN1 | 0.6592 | 0.0000 | 5.0000 | 1.0000 | Calculated from schedules | 0.0519 | 0.6592 | 1.0000 | 1.0000 | Not calculated | 0.0519 | 0.0787 | ||
| SPLIT MN2 | 0.6575 | 0.0000 | 5.0000 | 1.0000 | Calculated from schedules | 0.0519 | 0.6575 | 1.0000 | 1.0000 | Not calculated | 0.0519 | 0.0790 | ||
| SPLIT MS1 | 0.6969 | 0.0000 | 5.0000 | 1.0000 | Calculated from schedules | 0.0519 | 0.6969 | 1.0000 | 1.0000 | Not calculated | 0.0519 | 0.0745 | ||
| SPLIT MS2 | 0.6951 | 0.0000 | 5.0000 | 1.0000 | Calculated from schedules | 0.0519 | 0.6951 | 1.0000 | 1.0000 | Not calculated | 0.0519 | 0.0747 | ||
| SPLIT TSW | 0.4777 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.4777 | 1.0000 | 1.0000 | Not calculated | 0.0260 | 0.0543 | ||
| SPLIT TNW | 0.4710 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.4710 | 1.0000 | 1.0000 | Not calculated | 0.0260 | 0.0551 | ||
| SPLIT TSE | 0.4026 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.4026 | 1.0000 | 1.0000 | Not calculated | 0.0260 | 0.0645 | ||
| SPLIT TNE | 0.3958 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.3958 | 1.0000 | 1.0000 | Not calculated | 0.0260 | 0.0656 | ||
| SPLIT TN1 | 0.3719 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.3719 | 1.0000 | 1.0000 | Not calculated | 0.0260 | 0.0698 | ||
| SPLIT TN2 | 0.3695 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.3695 | 1.0000 | 1.0000 | Not calculated | 0.0260 | 0.0702 | ||
| SPLIT TS1 | 0.3801 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.3801 | 1.0000 | 1.0000 | Not calculated | 0.0260 | 0.0683 | ||
| SPLIT TS2 | 0.3778 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.3778 | 1.0000 | 1.0000 | Not calculated | 0.0260 | 0.0687 |
| AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
| G SW APARTMENT | SPLIT GSW | 0.000000 | 2.5000 | 0.000294 | 88.25 | 0.0260 | 1.0000 | 0.0260 | 1.000 | 0.0260 |
| G NW APARTMENT | SPLIT GNW | 0.000000 | 2.5000 | 0.000294 | 88.25 | 0.0260 | 1.0000 | 0.0260 | 1.000 | 0.0260 |
| OFFICE | SPLIT OFFICE | 0.000000 | 4.7495 | 0.000432 | 88.25 | 0.0381 | 1.0000 | 0.0381 | 1.000 | 0.0381 |
| G NE APARTMENT | SPLIT GNE | 0.000000 | 2.5000 | 0.000294 | 88.25 | 0.0260 | 1.0000 | 0.0260 | 1.000 | 0.0260 |
| G N1 APARTMENT | SPLIT GN1 | 0.000000 | 2.5000 | 0.000294 | 88.25 | 0.0260 | 1.0000 | 0.0260 | 1.000 | 0.0260 |
| G N2 APARTMENT | SPLIT GN2 | 0.000000 | 2.5000 | 0.000294 | 88.25 | 0.0260 | 1.0000 | 0.0260 | 1.000 | 0.0260 |
| G S1 APARTMENT | SPLIT GS1 | 0.000000 | 2.5000 | 0.000294 | 88.25 | 0.0260 | 1.0000 | 0.0260 | 1.000 | 0.0260 |
| G S2 APARTMENT | SPLIT GS2 | 0.000000 | 2.5000 | 0.000294 | 88.25 | 0.0260 | 1.0000 | 0.0260 | 1.000 | 0.0260 |
| M SW APARTMENT | SPLIT MSW | 0.000000 | 5.0000 | 0.000294 | 176.50 | 0.0519 | 1.0000 | 0.0519 | 1.000 | 0.0519 |
| M NW APARTMENT | SPLIT MNW | 0.000000 | 5.0000 | 0.000294 | 176.50 | 0.0519 | 1.0000 | 0.0519 | 1.000 | 0.0519 |
| M SE APARTMENT | SPLIT MSE | 0.000000 | 5.0000 | 0.000294 | 176.50 | 0.0519 | 1.0000 | 0.0519 | 1.000 | 0.0519 |
| M NE APARTMENT | SPLIT MNE | 0.000000 | 5.0000 | 0.000294 | 176.50 | 0.0519 | 1.0000 | 0.0519 | 1.000 | 0.0519 |
| M N1 APARTMENT | SPLIT MN1 | 0.000000 | 5.0000 | 0.000294 | 176.50 | 0.0519 | 1.0000 | 0.0519 | 1.000 | 0.0519 |
| M N2 APARTMENT | SPLIT MN2 | 0.000000 | 5.0000 | 0.000294 | 176.50 | 0.0519 | 1.0000 | 0.0519 | 1.000 | 0.0519 |
| M S1 APARTMENT | SPLIT MS1 | 0.000000 | 5.0000 | 0.000294 | 176.50 | 0.0519 | 1.0000 | 0.0519 | 1.000 | 0.0519 |
| M S2 APARTMENT | SPLIT MS2 | 0.000000 | 5.0000 | 0.000294 | 176.50 | 0.0519 | 1.0000 | 0.0519 | 1.000 | 0.0519 |
| T SW APARTMENT | SPLIT TSW | 0.000000 | 2.5000 | 0.000294 | 88.25 | 0.0260 | 1.0000 | 0.0260 | 1.000 | 0.0260 |
| T NW APARTMENT | SPLIT TNW | 0.000000 | 2.5000 | 0.000294 | 88.25 | 0.0260 | 1.0000 | 0.0260 | 1.000 | 0.0260 |
| T SE APARTMENT | SPLIT TSE | 0.000000 | 2.5000 | 0.000294 | 88.25 | 0.0260 | 1.0000 | 0.0260 | 1.000 | 0.0260 |
| T NE APARTMENT | SPLIT TNE | 0.000000 | 2.5000 | 0.000294 | 88.25 | 0.0260 | 1.0000 | 0.0260 | 1.000 | 0.0260 |
| T N1 APARTMENT | SPLIT TN1 | 0.000000 | 2.5000 | 0.000294 | 88.25 | 0.0260 | 1.0000 | 0.0260 | 1.000 | 0.0260 |
| T N2 APARTMENT | SPLIT TN2 | 0.000000 | 2.5000 | 0.000294 | 88.25 | 0.0260 | 1.0000 | 0.0260 | 1.000 | 0.0260 |
| T S1 APARTMENT | SPLIT TS1 | 0.000000 | 2.5000 | 0.000294 | 88.25 | 0.0260 | 1.0000 | 0.0260 | 1.000 | 0.0260 |
| T S2 APARTMENT | SPLIT TS2 | 0.000000 | 2.5000 | 0.000294 | 88.25 | 0.0260 | 1.0000 | 0.0260 | 1.000 | 0.0260 |
| People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
| SPLIT GSW | 0.000000 | 2.50 | 0.000294 | 88.2493 | 0.0260 | 0.0260 | 0.0260 |
| SPLIT GNW | 0.000000 | 2.50 | 0.000294 | 88.2493 | 0.0260 | 0.0260 | 0.0260 |
| SPLIT OFFICE | 0.000000 | 4.75 | 0.000432 | 88.2493 | 0.0381 | 0.0381 | 0.0381 |
| SPLIT GNE | 0.000000 | 2.50 | 0.000294 | 88.2493 | 0.0260 | 0.0260 | 0.0260 |
| SPLIT GN1 | 0.000000 | 2.50 | 0.000294 | 88.2493 | 0.0260 | 0.0260 | 0.0260 |
| SPLIT GN2 | 0.000000 | 2.50 | 0.000294 | 88.2493 | 0.0260 | 0.0260 | 0.0260 |
| SPLIT GS1 | 0.000000 | 2.50 | 0.000294 | 88.2493 | 0.0260 | 0.0260 | 0.0260 |
| SPLIT GS2 | 0.000000 | 2.50 | 0.000294 | 88.2493 | 0.0260 | 0.0260 | 0.0260 |
| SPLIT MSW | 0.000000 | 5.00 | 0.000294 | 176.4985 | 0.0519 | 0.0519 | 0.0519 |
| SPLIT MNW | 0.000000 | 5.00 | 0.000294 | 176.4985 | 0.0519 | 0.0519 | 0.0519 |
| SPLIT MSE | 0.000000 | 5.00 | 0.000294 | 176.4985 | 0.0519 | 0.0519 | 0.0519 |
| SPLIT MNE | 0.000000 | 5.00 | 0.000294 | 176.4985 | 0.0519 | 0.0519 | 0.0519 |
| SPLIT MN1 | 0.000000 | 5.00 | 0.000294 | 176.4985 | 0.0519 | 0.0519 | 0.0519 |
| SPLIT MN2 | 0.000000 | 5.00 | 0.000294 | 176.4985 | 0.0519 | 0.0519 | 0.0519 |
| SPLIT MS1 | 0.000000 | 5.00 | 0.000294 | 176.4985 | 0.0519 | 0.0519 | 0.0519 |
| SPLIT MS2 | 0.000000 | 5.00 | 0.000294 | 176.4985 | 0.0519 | 0.0519 | 0.0519 |
| SPLIT TSW | 0.000000 | 2.50 | 0.000294 | 88.2493 | 0.0260 | 0.0260 | 0.0260 |
| SPLIT TNW | 0.000000 | 2.50 | 0.000294 | 88.2493 | 0.0260 | 0.0260 | 0.0260 |
| SPLIT TSE | 0.000000 | 2.50 | 0.000294 | 88.2493 | 0.0260 | 0.0260 | 0.0260 |
| SPLIT TNE | 0.000000 | 2.50 | 0.000294 | 88.2493 | 0.0260 | 0.0260 | 0.0260 |
| SPLIT TN1 | 0.000000 | 2.50 | 0.000294 | 88.2493 | 0.0260 | 0.0260 | 0.0260 |
| SPLIT TN2 | 0.000000 | 2.50 | 0.000294 | 88.2493 | 0.0260 | 0.0260 | 0.0260 |
| SPLIT TS1 | 0.000000 | 2.50 | 0.000294 | 88.2493 | 0.0260 | 0.0260 | 0.0260 |
| SPLIT TS2 | 0.000000 | 2.50 | 0.000294 | 88.2493 | 0.0260 | 0.0260 | 0.0260 |
| AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
| G SW APARTMENT | SPLIT GSW | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.3429 | 0.3429 | 0.3429 | No | 0.0260 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| G NW APARTMENT | SPLIT GNW | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.3222 | 0.3222 | 0.3222 | No | 0.0260 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| OFFICE | SPLIT OFFICE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.3804 | 0.3804 | 0.3804 | No | 0.0381 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| G NE APARTMENT | SPLIT GNE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.2874 | 0.2874 | 0.2874 | No | 0.0260 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| G N1 APARTMENT | SPLIT GN1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.2630 | 0.2630 | 0.2630 | No | 0.0260 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| G N2 APARTMENT | SPLIT GN2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.2624 | 0.2624 | 0.2624 | No | 0.0260 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| G S1 APARTMENT | SPLIT GS1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.2858 | 0.2858 | 0.2858 | No | 0.0260 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| G S2 APARTMENT | SPLIT GS2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.2877 | 0.2877 | 0.2877 | No | 0.0260 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| M SW APARTMENT | SPLIT MSW | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8688 | 0.8688 | 0.8688 | No | 0.0519 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| M NW APARTMENT | SPLIT MNW | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8365 | 0.8365 | 0.8365 | No | 0.0519 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| M SE APARTMENT | SPLIT MSE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.7652 | 0.7652 | 0.7652 | No | 0.0519 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| M NE APARTMENT | SPLIT MNE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.7338 | 0.7338 | 0.7338 | No | 0.0519 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| M N1 APARTMENT | SPLIT MN1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.6592 | 0.6592 | 0.6592 | No | 0.0519 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| M N2 APARTMENT | SPLIT MN2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.6575 | 0.6575 | 0.6575 | No | 0.0519 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| M S1 APARTMENT | SPLIT MS1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.6969 | 0.6969 | 0.6969 | No | 0.0519 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| M S2 APARTMENT | SPLIT MS2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.6951 | 0.6951 | 0.6951 | No | 0.0519 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| T SW APARTMENT | SPLIT TSW | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4777 | 0.4777 | 0.4777 | No | 0.0260 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| T NW APARTMENT | SPLIT TNW | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4710 | 0.4710 | 0.4710 | No | 0.0260 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| T SE APARTMENT | SPLIT TSE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4026 | 0.4026 | 0.4026 | No | 0.0260 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| T NE APARTMENT | SPLIT TNE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.3958 | 0.3958 | 0.3958 | No | 0.0260 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| T N1 APARTMENT | SPLIT TN1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.3719 | 0.3719 | 0.3719 | No | 0.0260 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| T N2 APARTMENT | SPLIT TN2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.3695 | 0.3695 | 0.3695 | No | 0.0260 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| T S1 APARTMENT | SPLIT TS1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.3801 | 0.3801 | 0.3801 | No | 0.0260 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| T S2 APARTMENT | SPLIT TS2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.3778 | 0.3778 | 0.3778 | No | 0.0260 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
| SPLIT GSW | 0.3429 | 0.3429 | 0.3429 | 0.3429 | 0.0260 | 1.0000 |
| SPLIT GNW | 0.3222 | 0.3222 | 0.3222 | 0.3222 | 0.0260 | 1.0000 |
| SPLIT OFFICE | 0.3804 | 0.3804 | 0.3804 | 0.3804 | 0.0381 | 1.0000 |
| SPLIT GNE | 0.2874 | 0.2874 | 0.2874 | 0.2874 | 0.0260 | 1.0000 |
| SPLIT GN1 | 0.2630 | 0.2630 | 0.2630 | 0.2630 | 0.0260 | 1.0000 |
| SPLIT GN2 | 0.2624 | 0.2624 | 0.2624 | 0.2624 | 0.0260 | 1.0000 |
| SPLIT GS1 | 0.2858 | 0.2858 | 0.2858 | 0.2858 | 0.0260 | 1.0000 |
| SPLIT GS2 | 0.2877 | 0.2877 | 0.2877 | 0.2877 | 0.0260 | 1.0000 |
| SPLIT MSW | 0.8688 | 0.8688 | 0.8688 | 0.8688 | 0.0519 | 1.0000 |
| SPLIT MNW | 0.8365 | 0.8365 | 0.8365 | 0.8365 | 0.0519 | 1.0000 |
| SPLIT MSE | 0.7652 | 0.7652 | 0.7652 | 0.7652 | 0.0519 | 1.0000 |
| SPLIT MNE | 0.7338 | 0.7338 | 0.7338 | 0.7338 | 0.0519 | 1.0000 |
| SPLIT MN1 | 0.6592 | 0.6592 | 0.6592 | 0.6592 | 0.0519 | 1.0000 |
| SPLIT MN2 | 0.6575 | 0.6575 | 0.6575 | 0.6575 | 0.0519 | 1.0000 |
| SPLIT MS1 | 0.6969 | 0.6969 | 0.6969 | 0.6969 | 0.0519 | 1.0000 |
| SPLIT MS2 | 0.6951 | 0.6951 | 0.6951 | 0.6951 | 0.0519 | 1.0000 |
| SPLIT TSW | 0.4777 | 0.4777 | 0.4777 | 0.4777 | 0.0260 | 1.0000 |
| SPLIT TNW | 0.4710 | 0.4710 | 0.4710 | 0.4710 | 0.0260 | 1.0000 |
| SPLIT TSE | 0.4026 | 0.4026 | 0.4026 | 0.4026 | 0.0260 | 1.0000 |
| SPLIT TNE | 0.3958 | 0.3958 | 0.3958 | 0.3958 | 0.0260 | 1.0000 |
| SPLIT TN1 | 0.3719 | 0.3719 | 0.3719 | 0.3719 | 0.0260 | 1.0000 |
| SPLIT TN2 | 0.3695 | 0.3695 | 0.3695 | 0.3695 | 0.0260 | 1.0000 |
| SPLIT TS1 | 0.3801 | 0.3801 | 0.3801 | 0.3801 | 0.0260 | 1.0000 |
| SPLIT TS2 | 0.3778 | 0.3778 | 0.3778 | 0.3778 | 0.0260 | 1.0000 |
| AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
| G SW APARTMENT | SPLIT GSW | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.3429 | 0.3429 | 0.3429 | No | 0.0260 | 0.1928 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| G NW APARTMENT | SPLIT GNW | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.3222 | 0.3222 | 0.3222 | No | 0.0260 | 0.2025 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| OFFICE | SPLIT OFFICE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.3804 | 0.3804 | 0.3804 | No | 0.0381 | 0.2404 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| G NE APARTMENT | SPLIT GNE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.2874 | 0.2874 | 0.2874 | No | 0.0260 | 0.2033 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| G N1 APARTMENT | SPLIT GN1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.2630 | 0.2630 | 0.2630 | No | 0.0260 | 0.3232 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| G N2 APARTMENT | SPLIT GN2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.2624 | 0.2624 | 0.2624 | No | 0.0260 | 0.3233 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| G S1 APARTMENT | SPLIT GS1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.2858 | 0.2858 | 0.2858 | No | 0.0260 | 0.2988 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| G S2 APARTMENT | SPLIT GS2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.2877 | 0.2877 | 0.2877 | No | 0.0260 | 0.2973 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| M SW APARTMENT | SPLIT MSW | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8688 | 0.8688 | 0.8688 | No | 0.0519 | 0.2162 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| M NW APARTMENT | SPLIT MNW | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8365 | 0.8365 | 0.8365 | No | 0.0519 | 0.2311 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| M SE APARTMENT | SPLIT MSE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.7652 | 0.7652 | 0.7652 | No | 0.0519 | 0.2173 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| M NE APARTMENT | SPLIT MNE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.7338 | 0.7338 | 0.7338 | No | 0.0519 | 0.2323 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| M N1 APARTMENT | SPLIT MN1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.6592 | 0.6592 | 0.6592 | No | 0.0519 | 0.4225 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| M N2 APARTMENT | SPLIT MN2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.6575 | 0.6575 | 0.6575 | No | 0.0519 | 0.4226 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| M S1 APARTMENT | SPLIT MS1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.6969 | 0.6969 | 0.6969 | No | 0.0519 | 0.3760 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| M S2 APARTMENT | SPLIT MS2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.6951 | 0.6951 | 0.6951 | No | 0.0519 | 0.3761 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| T SW APARTMENT | SPLIT TSW | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4777 | 0.4777 | 0.4777 | No | 0.0260 | 0.1312 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| T NW APARTMENT | SPLIT TNW | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4710 | 0.4710 | 0.4710 | No | 0.0260 | 0.1370 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| T SE APARTMENT | SPLIT TSE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4026 | 0.4026 | 0.4026 | No | 0.0260 | 0.1318 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| T NE APARTMENT | SPLIT TNE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.3958 | 0.3958 | 0.3958 | No | 0.0260 | 0.1375 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| T N1 APARTMENT | SPLIT TN1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.3719 | 0.3719 | 0.3719 | No | 0.0260 | 0.2023 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| T N2 APARTMENT | SPLIT TN2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.3695 | 0.3695 | 0.3695 | No | 0.0260 | 0.2023 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| T S1 APARTMENT | SPLIT TS1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.3801 | 0.3801 | 0.3801 | No | 0.0260 | 0.1900 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| T S2 APARTMENT | SPLIT TS2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.3778 | 0.3778 | 0.3778 | No | 0.0260 | 0.1900 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
| SPLIT GSW | 0.3429 | 0.3429 | 0.3429 | 0.3429 | 0.0260 | 1.0000 |
| SPLIT GNW | 0.3222 | 0.3222 | 0.3222 | 0.3222 | 0.0260 | 1.0000 |
| SPLIT OFFICE | 0.3804 | 0.3804 | 0.3804 | 0.3804 | 0.0381 | 1.0000 |
| SPLIT GNE | 0.2874 | 0.2874 | 0.2874 | 0.2874 | 0.0260 | 1.0000 |
| SPLIT GN1 | 0.2630 | 0.2630 | 0.2630 | 0.2630 | 0.0260 | 1.0000 |
| SPLIT GN2 | 0.2624 | 0.2624 | 0.2624 | 0.2624 | 0.0260 | 1.0000 |
| SPLIT GS1 | 0.2858 | 0.2858 | 0.2858 | 0.2858 | 0.0260 | 1.0000 |
| SPLIT GS2 | 0.2877 | 0.2877 | 0.2877 | 0.2877 | 0.0260 | 1.0000 |
| SPLIT MSW | 0.8688 | 0.8688 | 0.8688 | 0.8688 | 0.0519 | 1.0000 |
| SPLIT MNW | 0.8365 | 0.8365 | 0.8365 | 0.8365 | 0.0519 | 1.0000 |
| SPLIT MSE | 0.7652 | 0.7652 | 0.7652 | 0.7652 | 0.0519 | 1.0000 |
| SPLIT MNE | 0.7338 | 0.7338 | 0.7338 | 0.7338 | 0.0519 | 1.0000 |
| SPLIT MN1 | 0.6592 | 0.6592 | 0.6592 | 0.6592 | 0.0519 | 1.0000 |
| SPLIT MN2 | 0.6575 | 0.6575 | 0.6575 | 0.6575 | 0.0519 | 1.0000 |
| SPLIT MS1 | 0.6969 | 0.6969 | 0.6969 | 0.6969 | 0.0519 | 1.0000 |
| SPLIT MS2 | 0.6951 | 0.6951 | 0.6951 | 0.6951 | 0.0519 | 1.0000 |
| SPLIT TSW | 0.4777 | 0.4777 | 0.4777 | 0.4777 | 0.0260 | 1.0000 |
| SPLIT TNW | 0.4710 | 0.4710 | 0.4710 | 0.4710 | 0.0260 | 1.0000 |
| SPLIT TSE | 0.4026 | 0.4026 | 0.4026 | 0.4026 | 0.0260 | 1.0000 |
| SPLIT TNE | 0.3958 | 0.3958 | 0.3958 | 0.3958 | 0.0260 | 1.0000 |
| SPLIT TN1 | 0.3719 | 0.3719 | 0.3719 | 0.3719 | 0.0260 | 1.0000 |
| SPLIT TN2 | 0.3695 | 0.3695 | 0.3695 | 0.3695 | 0.0260 | 1.0000 |
| SPLIT TS1 | 0.3801 | 0.3801 | 0.3801 | 0.3801 | 0.0260 | 1.0000 |
| SPLIT TS2 | 0.3778 | 0.3778 | 0.3778 | 0.3778 | 0.0260 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 09:14:20
Sec1.1A-General Information| Data | |
| Weather File | RUNPERIOD 1 ** Buffalo Niagara Intl AP NY USA TMY3 WMO#=725280 |
| Total gross floor area [m2] | 3134.61 |
| Principal Heating Source | Natural Gas |
| Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
| G SW APARTMENT | 88.25 | 88.25 | 0.00 | 117.85 |
| G NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
| OFFICE | 88.25 | 88.25 | 0.00 | 33.56 |
| G NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
| G N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
| G N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
| G S1 APARTMENT | 88.25 | 88.25 | 0.00 | 117.85 |
| G S2 APARTMENT | 88.25 | 88.25 | 0.00 | 117.85 |
| M SW APARTMENT | 88.25 | 88.25 | 0.00 | 117.85 |
| M NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
| M SE APARTMENT | 88.25 | 88.25 | 0.00 | 117.85 |
| M NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
| M N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
| M N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
| M S1 APARTMENT | 88.25 | 88.25 | 0.00 | 117.85 |
| M S2 APARTMENT | 88.25 | 88.25 | 0.00 | 117.85 |
| T SW APARTMENT | 88.25 | 88.25 | 0.00 | 117.85 |
| T NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
| T SE APARTMENT | 88.25 | 88.25 | 0.00 | 117.85 |
| T NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
| T N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
| T N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
| T S1 APARTMENT | 88.25 | 88.25 | 0.00 | 117.85 |
| T S2 APARTMENT | 88.25 | 88.25 | 0.00 | 117.85 |
| T CORRIDOR | 77.66 | 0.00 | 77.66 | 168.00 |
| G CORRIDOR | 77.66 | 0.00 | 77.66 | 168.00 |
| M CORRIDOR | 77.66 | 0.00 | 77.66 | 168.00 |
| Totals | 3134.61 | 2823.98 | 310.64 |
| Data | |
| Number of hours heating loads not met | 0.00 |
| Number of hours cooling loads not met | 0.00 |
| Number of hours not met | 0.00 |
| Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
| None |
| Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
| Heating -- General | 0.00 | 0.00 | 612.52 | 123329.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Cooling -- General | 77.19 | 24142.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Lighting -- LightsWired | 94.96 | 5496.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Lighting -- LightsPlugIn | 4.27 | 407.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Lighting -- General | 50.00 | 3183.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment -- MiscPlug | 388.06 | 18541.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment -- ElevatorLift | 65.48 | 4006.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment -- ElevatorLightsFan | 5.11 | 162.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans -- Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans -- General | 96.23 | 8208.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Recovery -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems -- Water Heater | 480.41 | 42107.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Process Subtotal [GJ] | Total Energy Use [GJ] | |
| Electricity | 458.66 | 1261.71 |
| Natural Gas | 0.00 | 612.52 |
| Additional | 0.00 | 0.00 |
| Total | 458.66 | 1874.23 |
| Process Subtotal [$] | Total Energy Cost [$] | |
| Electricity | 0.00 | |
| Natural Gas | 0.00 | |
| Additional | 0.00 | |
| Total | 0.00 |
| Rated Capacity [kW] | Annual Energy Generated [GJ] | |
| Photovoltaic | 0.00 | 0.00 |
| Wind | 0.00 | 0.00 |
| Electricty [MJ/m2] | |
| Interior Lighting (All) | 31.66 |
| Space Heating | 0.00 |
| Space Cooling | 24.63 |
| Fans (All) | 30.70 |
| Service Water Heating | 153.26 |
| Receptacle Equipment | 146.32 |
| Miscellaneous (All) | 402.51 |
| Subtotal | 402.51 |
| Natural Gas [MJ/m2] | |
| Space Heating | 195.41 |
| Service Water Heating | 0.00 |
| Miscellaneous (All) | 195.41 |
| Subtotal | 195.41 |
| Additional [MJ/m2] | |
| Subtotal | 0.00 |
| Miscellaneous | 0.00 |
| Percent [%] | |
| Interior Lighting (All) | 5.29 |
| Space Heating | 32.68 |
| Space Cooling | 4.12 |
| Fans (All) | 5.13 |
| Service Water Heating | 25.63 |
| Receptacle Equipment | 24.47 |
| Miscellaneous | 2.67 |
| Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
| OCC_APT_SCH_STAY_HOME_FAMILY | 5993. | 8760. |
| OCC_APT_SCH_CORRIDOR | 5993. | 8760. |
| OCC_APT_SCH_WORKING_FAMILY | 5845. | 6055. |
| OCC_OFF_SCH | 2210. | 2340. |
| OCC_OFF_W_SB_SCH | 1820. | 1820. |
| LTG_SCH_OFFICE | 2435. | 8760. |
| LTG_SCH_CORRIDOR | 8760. | 8760. |
| LTG_SCH_APARTMENT_HARDWIRED | 527. | 8760. |
| LTG_SCH_APARTMENT_PLUGIN | 527. | 8760. |
| EQP_APT_SCH | 5763. | 8760. |
| EQP_OFF_SCH | 4531. | 8760. |
| INF_APT_SCH | 8760. | 8760. |
| INF_OFF_SCH | 8760. | 8760. |
| INF_COR_SCH | 8760. | 8760. |
| INFIL_DOOR_OPENING_SCH | 1466. | 5840. |
| ALL OFF | 0. | 0. |
| ALL ON | 8760. | 8760. |
| ALWAYS_ON | 8760. | 8760. |
| ALLON_EXCEPT_DD | 8760. | 8760. |
| EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
| FAN_OFF_W_SB_SCH | 8240. | 8240. |
| APT_DHW_SCH | 4592. | 8760. |
| EXTERIOR_LTG_SCH | 4380. | 4380. |
| BLDG_ELEVATORS | 2270. | 8760. |
| ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
| ELEV_LIGHT_FAN_SCH_ADD_DF | 2154. | 8760. |
| SLIDING_DOORS_VENTILATION_AVAILABILITY_SCH | 5840. | 5840. |
| First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
| HTGSETP_APT_SCH | APTHEATINGSETPOINT | January | 21.10 | 365 | 21.10 | 365 |
| HTGSETP_DESIGN_OFF_SCH | OFFHEATINGSETPOINT | January | 21.10 | 365 | 21.10 | 365 |
| CLGSETP_APT_SCH | APTCOOLINGSETPOINT | July | 24.00 | 365 | 24.00 | 365 |
| CLGSETP_DESIGN_OFF_SCH | OFFCOOLINGSETPOINT | July | 23.90 | 365 | 23.90 | 365 |
| S HTGSETP_APT_SCH | S APARTMENT DUAL SP CONTROL | January | 21.10 | 365 | 21.10 | 365 |
| S CLGSETP_APT_SCH | S APARTMENT DUAL SP CONTROL | July | 24.00 | 365 | 24.00 | 365 |
| N HTGSETP_APT_SCH | N APARTMENT DUAL SP CONTROL | January | 21.10 | 365 | 21.10 | 365 |
| N CLGSETP_APT_SCH | N APARTMENT DUAL SP CONTROL | July | 24.00 | 365 | 24.00 | 365 |
| HTGSETP_OFF_SCH_YES_OPTIMUM | OFFICE DUAL SP CONTROL | January | 21.10 | 365 | 15.60 | 365 |
| CLGSETP_OFF_SCH_YES_OPTIMUM | OFFICE DUAL SP CONTROL | July | 24.00 | 365 | 29.40 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 09:14:20
Heat Index Hours| Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
| G SW APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| G NW APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| OFFICE | 7813.00 | 947.00 | 0.00 | 0.00 | 0.00 |
| G NE APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| G N1 APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| G N2 APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| G S1 APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| G S2 APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M SW APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M NW APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M SE APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M NE APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M N1 APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M N2 APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M S1 APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M S2 APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T SW APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T NW APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T SE APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T NE APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T N1 APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T N2 APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T S1 APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T S2 APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T CORRIDOR | 7377.67 | 1378.83 | 3.50 | 0.00 | 0.00 |
| G CORRIDOR | 8334.17 | 425.83 | 0.00 | 0.00 | 0.00 |
| M CORRIDOR | 6193.33 | 2566.67 | 0.00 | 0.00 | 0.00 |
| Min | 6193.33 | 0.00 | 0.00 | 0.00 | 0.00 |
| Max | 8760.00 | 2566.67 | 3.50 | 0.00 | 0.00 |
| Average | 8562.90 | 196.98 | 0.13 | 0.00 | 0.00 |
| Sum | 231198.17 | 5318.33 | 3.50 | 0.00 | 0.00 |
| Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
| G SW APARTMENT | 11830.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| G NW APARTMENT | 10585.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| OFFICE | 7000.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| G NE APARTMENT | 10585.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| G N1 APARTMENT | 10585.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| G N2 APARTMENT | 10585.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| G S1 APARTMENT | 11830.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| G S2 APARTMENT | 11830.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M SW APARTMENT | 11830.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M NW APARTMENT | 10585.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M SE APARTMENT | 11830.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M NE APARTMENT | 10585.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M N1 APARTMENT | 10585.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M N2 APARTMENT | 10585.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M S1 APARTMENT | 11830.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M S2 APARTMENT | 11830.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T SW APARTMENT | 11830.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T NW APARTMENT | 10585.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T SE APARTMENT | 11830.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T NE APARTMENT | 10585.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T N1 APARTMENT | 10585.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T N2 APARTMENT | 10585.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T S1 APARTMENT | 11830.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T S2 APARTMENT | 11830.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T CORRIDOR | 19601.50 | 3381.83 | 11.67 | 0.00 | 0.00 |
| G CORRIDOR | 21740.50 | 1254.50 | 0.00 | 0.00 | 0.00 |
| M CORRIDOR | 16264.17 | 6730.83 | 0.00 | 0.00 | 0.00 |
| Min | 7000.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Max | 21740.50 | 6730.83 | 11.67 | 0.00 | 0.00 |
| Average | 11916.90 | 421.01 | 0.43 | 0.00 | 0.00 |
| Sum | 321756.17 | 11367.17 | 11.67 | 0.00 | 0.00 |
| Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
| G SW APARTMENT | 8503.17 | 256.83 | 0.00 | 0.00 | 0.00 |
| G NW APARTMENT | 8451.00 | 309.00 | 0.00 | 0.00 | 0.00 |
| OFFICE | 7503.33 | 1256.67 | 0.00 | 0.00 | 0.00 |
| G NE APARTMENT | 8452.50 | 307.50 | 0.00 | 0.00 | 0.00 |
| G N1 APARTMENT | 8471.17 | 288.83 | 0.00 | 0.00 | 0.00 |
| G N2 APARTMENT | 8471.67 | 288.33 | 0.00 | 0.00 | 0.00 |
| G S1 APARTMENT | 8546.83 | 213.17 | 0.00 | 0.00 | 0.00 |
| G S2 APARTMENT | 8594.17 | 165.83 | 0.00 | 0.00 | 0.00 |
| M SW APARTMENT | 8605.50 | 154.50 | 0.00 | 0.00 | 0.00 |
| M NW APARTMENT | 8586.17 | 173.83 | 0.00 | 0.00 | 0.00 |
| M SE APARTMENT | 8607.17 | 152.83 | 0.00 | 0.00 | 0.00 |
| M NE APARTMENT | 8584.50 | 175.50 | 0.00 | 0.00 | 0.00 |
| M N1 APARTMENT | 8589.33 | 170.67 | 0.00 | 0.00 | 0.00 |
| M N2 APARTMENT | 8589.50 | 170.50 | 0.00 | 0.00 | 0.00 |
| M S1 APARTMENT | 8610.83 | 149.17 | 0.00 | 0.00 | 0.00 |
| M S2 APARTMENT | 8610.83 | 149.17 | 0.00 | 0.00 | 0.00 |
| T SW APARTMENT | 8466.83 | 293.17 | 0.00 | 0.00 | 0.00 |
| T NW APARTMENT | 8450.00 | 310.00 | 0.00 | 0.00 | 0.00 |
| T SE APARTMENT | 8464.00 | 296.00 | 0.00 | 0.00 | 0.00 |
| T NE APARTMENT | 8445.50 | 314.50 | 0.00 | 0.00 | 0.00 |
| T N1 APARTMENT | 8475.67 | 284.33 | 0.00 | 0.00 | 0.00 |
| T N2 APARTMENT | 8474.83 | 285.17 | 0.00 | 0.00 | 0.00 |
| T S1 APARTMENT | 8490.50 | 269.50 | 0.00 | 0.00 | 0.00 |
| T S2 APARTMENT | 8491.83 | 268.17 | 0.00 | 0.00 | 0.00 |
| T CORRIDOR | 4827.17 | 3869.17 | 63.67 | 0.00 | 0.00 |
| G CORRIDOR | 7080.50 | 1672.17 | 7.33 | 0.00 | 0.00 |
| M CORRIDOR | 3465.17 | 5257.33 | 37.50 | 0.00 | 0.00 |
| Min | 3465.17 | 149.17 | 0.00 | 0.00 | 0.00 |
| Max | 8610.83 | 5257.33 | 63.67 | 0.00 | 0.00 |
| Average | 8107.77 | 648.22 | 4.02 | 0.00 | 0.00 |
| Sum | 218909.67 | 17501.83 | 108.50 | 0.00 | 0.00 |
| Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
| G SW APARTMENT | 11452.00 | 378.00 | 0.00 | 0.00 | 0.00 |
| G NW APARTMENT | 10209.50 | 375.50 | 0.00 | 0.00 | 0.00 |
| OFFICE | 6840.00 | 160.00 | 0.00 | 0.00 | 0.00 |
| G NE APARTMENT | 10183.00 | 402.00 | 0.00 | 0.00 | 0.00 |
| G N1 APARTMENT | 10233.50 | 351.50 | 0.00 | 0.00 | 0.00 |
| G N2 APARTMENT | 10233.17 | 351.83 | 0.00 | 0.00 | 0.00 |
| G S1 APARTMENT | 11519.50 | 310.50 | 0.00 | 0.00 | 0.00 |
| G S2 APARTMENT | 11593.67 | 236.33 | 0.00 | 0.00 | 0.00 |
| M SW APARTMENT | 11606.67 | 223.33 | 0.00 | 0.00 | 0.00 |
| M NW APARTMENT | 10378.00 | 207.00 | 0.00 | 0.00 | 0.00 |
| M SE APARTMENT | 11600.17 | 229.83 | 0.00 | 0.00 | 0.00 |
| M NE APARTMENT | 10353.67 | 231.33 | 0.00 | 0.00 | 0.00 |
| M N1 APARTMENT | 10391.67 | 193.33 | 0.00 | 0.00 | 0.00 |
| M N2 APARTMENT | 10392.00 | 193.00 | 0.00 | 0.00 | 0.00 |
| M S1 APARTMENT | 11629.17 | 200.83 | 0.00 | 0.00 | 0.00 |
| M S2 APARTMENT | 11629.50 | 200.50 | 0.00 | 0.00 | 0.00 |
| T SW APARTMENT | 11383.67 | 446.33 | 0.00 | 0.00 | 0.00 |
| T NW APARTMENT | 10169.50 | 415.50 | 0.00 | 0.00 | 0.00 |
| T SE APARTMENT | 11358.67 | 471.33 | 0.00 | 0.00 | 0.00 |
| T NE APARTMENT | 10134.83 | 450.17 | 0.00 | 0.00 | 0.00 |
| T N1 APARTMENT | 10212.83 | 372.17 | 0.00 | 0.00 | 0.00 |
| T N2 APARTMENT | 10211.17 | 373.83 | 0.00 | 0.00 | 0.00 |
| T S1 APARTMENT | 11431.67 | 398.33 | 0.00 | 0.00 | 0.00 |
| T S2 APARTMENT | 11432.67 | 397.33 | 0.00 | 0.00 | 0.00 |
| T CORRIDOR | 12694.83 | 10089.17 | 211.00 | 0.00 | 0.00 |
| G CORRIDOR | 18055.67 | 4910.00 | 29.33 | 0.00 | 0.00 |
| M CORRIDOR | 9041.83 | 13833.33 | 119.83 | 0.00 | 0.00 |
| Min | 6840.00 | 160.00 | 0.00 | 0.00 | 0.00 |
| Max | 18055.67 | 13833.33 | 211.00 | 0.00 | 0.00 |
| Average | 10976.76 | 1348.23 | 13.34 | 0.00 | 0.00 |
| Sum | 296372.50 | 36402.33 | 360.17 | 0.00 | 0.00 |
| SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
| None |
| SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
| None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 09:14:20
CO2 Level Hours| Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
| None |
| Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
| None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 09:14:20
Illuminance Level Hours| A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
| None |
| A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
| None |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
| January | -3.40 |
| February | -4.23 |
| March | 2.667 |
| April | 7.472 |
| May | 13.731 |
| June | 18.627 |
| July | 22.029 |
| August | 20.690 |
| September | 16.545 |
| October | 9.725 |
| November | 6.035 |
| December | -2.18 |
| Annual Sum or Average | 9.049 |
| Minimum of Months | -4.23 |
| Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Environment
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
| January | -3.40 |
| February | -4.23 |
| March | 2.667 |
| April | 7.472 |
| May | 13.731 |
| June | 18.627 |
| July | 22.029 |
| August | 20.690 |
| September | 16.545 |
| October | 9.725 |
| November | 6.035 |
| December | -2.18 |
| Annual Sum or Average | 9.049 |
| Minimum of Months | -4.23 |
| Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2012
For: Environment
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
| January | -3.40 |
| February | -4.23 |
| March | 2.667 |
| April | 7.472 |
| May | 13.731 |
| June | 18.627 |
| July | 22.029 |
| August | 20.690 |
| September | 16.545 |
| October | 9.725 |
| November | 6.035 |
| December | -2.18 |
| Annual Sum or Average | 9.049 |
| Minimum of Months | -4.23 |
| Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
| January | -3.40 |
| February | -4.23 |
| March | 2.667 |
| April | 7.472 |
| May | 13.731 |
| June | 18.627 |
| July | 22.029 |
| August | 20.690 |
| September | 16.545 |
| October | 9.725 |
| November | 6.035 |
| December | -2.18 |
| Annual Sum or Average | 9.049 |
| Minimum of Months | -4.23 |
| Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME APARTMENTMIDRISE
For: Environment
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
| January | -3.40 |
| February | -4.23 |
| March | 2.667 |
| April | 7.472 |
| May | 13.731 |
| June | 18.627 |
| July | 22.029 |
| August | 20.690 |
| September | 16.545 |
| October | 9.725 |
| November | 6.035 |
| December | -2.18 |
| Annual Sum or Average | 9.049 |
| Minimum of Months | -4.23 |
| Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
| January | -3.40 |
| February | -4.23 |
| March | 2.667 |
| April | 7.472 |
| May | 13.731 |
| June | 18.627 |
| July | 22.029 |
| August | 20.690 |
| September | 16.545 |
| October | 9.725 |
| November | 6.035 |
| December | -2.18 |
| Annual Sum or Average | 9.049 |
| Minimum of Months | -4.23 |
| Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
| January | -3.40 |
| February | -4.23 |
| March | 2.667 |
| April | 7.472 |
| May | 13.731 |
| June | 18.627 |
| July | 22.029 |
| August | 20.690 |
| September | 16.545 |
| October | 9.725 |
| November | 6.035 |
| December | -2.18 |
| Annual Sum or Average | 9.049 |
| Minimum of Months | -4.23 |
| Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 5A
For: Environment
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
| January | -3.40 |
| February | -4.23 |
| March | 2.667 |
| April | 7.472 |
| May | 13.731 |
| June | 18.627 |
| July | 22.029 |
| August | 20.690 |
| September | 16.545 |
| October | 9.725 |
| November | 6.035 |
| December | -2.18 |
| Annual Sum or Average | 9.049 |
| Minimum of Months | -4.23 |
| Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NY_BUFFALO
For: Environment
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
| January | -3.40 |
| February | -4.23 |
| March | 2.667 |
| April | 7.472 |
| May | 13.731 |
| June | 18.627 |
| July | 22.029 |
| August | 20.690 |
| September | 16.545 |
| October | 9.725 |
| November | 6.035 |
| December | -2.18 |
| Annual Sum or Average | 9.049 |
| Minimum of Months | -4.23 |
| Maximum of Months | 22.029 |
Report: ZoneCoolingSummaryMonthly
For: G SW APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 4334219.36 | 338.45 | 15-JAN-15:30 | 5.30 | 1.42 | 78198344.11 | 42.51 | 07-JAN-08:50 | 5.30 | 1.42 |
| February | 1777301.95 | 166.83 | 28-FEB-16:10 | 0.40 | -2.4 | 69628662.55 | 42.51 | 07-FEB-18:00 | 0.40 | -2.4 |
| March | 74716525.92 | 416.83 | 08-MAR-16:40 | 6.87 | 1.50 | 76249090.38 | 70.27 | 15-MAR-17:19 | 24.63 | 15.85 |
| April | 0.206438E+09 | 418.53 | 25-APR-18:30 | 6.95 | 4.76 | 76986174.68 | 61.03 | 23-APR-15:09 | 6.95 | 4.76 |
| May | 0.485471E+09 | 428.08 | 06-MAY-22:10 | 6.60 | 5.24 | 90106199.12 | 70.37 | 26-MAY-18:49 | 19.60 | 10.81 |
| June | 0.127583E+10 | 1501.45 | 27-JUN-16:40 | 26.50 | 22.69 | 0.115800E+09 | 70.36 | 14-JUN-18:40 | 26.50 | 22.69 |
| July | 0.218830E+10 | 1702.70 | 18-JUL-17:20 | 27.77 | 19.70 | 0.129133E+09 | 70.35 | 10-JUL-05:00 | 27.77 | 19.70 |
| August | 0.226602E+10 | 2019.75 | 10-AUG-16:04 | 29.22 | 19.52 | 0.123765E+09 | 70.36 | 02-AUG-04:00 | 29.22 | 19.52 |
| September | 0.161233E+10 | 2122.72 | 21-SEP-16:04 | 26.02 | 17.14 | 0.120954E+09 | 70.36 | 12-SEP-01:10 | 26.02 | 17.14 |
| October | 0.820178E+09 | 1177.91 | 11-OCT-16:07 | 21.70 | 14.52 | 93890077.79 | 70.33 | 11-OCT-19:00 | 16.10 | 11.00 |
| November | 0.262197E+09 | 540.07 | 01-NOV-23:50 | 2.98 | 2.53 | 76821934.67 | 55.58 | 04-NOV-16:49 | 17.38 | 13.10 |
| December | 7699703.63 | 388.85 | 16-DEC-14:00 | 5.60 | 2.84 | 78198344.13 | 42.51 | 12-DEC-18:00 | 5.60 | 2.84 |
| Annual Sum or Average | 0.920530E+10 | 0.112973E+10 | ||||||||
| Minimum of Months | 1777301.95 | 166.83 | 0.40 | -2.4 | 69628662.55 | 42.51 | 0.40 | -2.4 | ||
| Maximum of Months | 0.226602E+10 | 2122.72 | 29.22 | 22.69 | 0.129133E+09 | 70.37 | 29.22 | 22.69 |
Report: ZoneCoolingSummaryMonthly
For: G NW APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | -1.0 | -1.6 | 77895344.60 | 42.51 | 30-JAN-22:00 | -10.6 | -11.5 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | -3.3 | -4.7 | 70357085.45 | 42.51 | 09-FEB-06:49 | -9.2 | -9.6 |
| March | 31069757.77 | 357.55 | 16-MAR-16:55 | 9.40 | 8.82 | 78713834.82 | 58.77 | 15-MAR-20:10 | 9.40 | 8.82 |
| April | 84091573.65 | 369.18 | 29-APR-18:50 | 8.40 | 7.18 | 75734695.59 | 43.02 | 09-APR-17:10 | 8.40 | 7.18 |
| May | 0.361865E+09 | 407.62 | 27-MAY-03:50 | 7.30 | 6.52 | 86793097.21 | 65.98 | 23-MAY-20:10 | 7.30 | 6.52 |
| June | 0.110863E+10 | 1409.72 | 27-JUN-17:20 | 26.33 | 22.54 | 0.118562E+09 | 70.34 | 10-JUN-22:40 | 26.33 | 22.54 |
| July | 0.192432E+10 | 1566.37 | 18-JUL-17:50 | 26.97 | 19.48 | 0.128593E+09 | 70.35 | 01-JUL-03:30 | 26.97 | 19.48 |
| August | 0.182989E+10 | 1660.47 | 10-AUG-17:30 | 27.75 | 19.82 | 0.128390E+09 | 70.35 | 22-AUG-01:30 | 14.15 | 12.43 |
| September | 0.102505E+10 | 1270.86 | 16-SEP-16:10 | 26.60 | 19.60 | 0.118633E+09 | 70.36 | 10-SEP-22:10 | 26.60 | 19.60 |
| October | 0.481680E+09 | 501.13 | 03-OCT-05:10 | 4.40 | 4.40 | 85716425.33 | 60.24 | 11-OCT-17:10 | 21.23 | 14.34 |
| November | 52804619.43 | 341.41 | 01-NOV-16:03 | 9.40 | 6.76 | 75562357.60 | 47.45 | 04-NOV-20:10 | 14.82 | 11.32 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 4.95 | 3.07 | 77895344.66 | 42.51 | 07-DEC-22:00 | -7.8 | -8.5 |
| Annual Sum or Average | 0.689940E+10 | 0.112285E+10 | ||||||||
| Minimum of Months | 0.00 | 0.00 | -3.3 | -4.7 | 70357085.45 | 42.51 | -10.6 | -11.5 | ||
| Maximum of Months | 0.192432E+10 | 1660.47 | 27.75 | 22.54 | 0.128593E+09 | 70.36 | 26.97 | 22.54 |
Report: ZoneCoolingSummaryMonthly
For: OFFICE
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.427538E+09 | 1194.47 | 06-JAN-08:03 | -12.9 | -13.4 | 38868503.26 | 80.76 | 25-JAN-13:50 | -5.6 | -7.0 |
| February | 0.384485E+09 | 1256.31 | 07-FEB-07:03 | -16.5 | -17.1 | 36925074.87 | 80.76 | 03-FEB-13:09 | -16.5 | -17.1 |
| March | 0.483827E+09 | 1150.12 | 07-MAR-07:03 | -12.9 | -13.7 | 48546312.23 | 133.51 | 15-MAR-15:30 | 25.30 | 16.10 |
| April | 0.338597E+09 | 792.83 | 17-APR-07:03 | -2.9 | -4.4 | 43782624.62 | 129.04 | 26-APR-14:39 | 15.57 | 8.89 |
| May | 0.278422E+09 | 1442.82 | 17-MAY-08:65 | 18.98 | 13.69 | 66443738.35 | 149.55 | 17-MAY-08:09 | 18.98 | 13.69 |
| June | 0.100223E+10 | 5573.42 | 16-JUN-08:62 | 17.38 | 12.49 | 76346949.17 | 197.28 | 27-JUN-07:10 | 23.58 | 21.23 |
| July | 0.146107E+10 | 5788.64 | 06-JUL-08:62 | 15.97 | 12.31 | 70413487.71 | 217.47 | 21-JUL-07:10 | 26.20 | 22.38 |
| August | 0.165020E+10 | 5741.78 | 03-AUG-08:62 | 18.45 | 13.54 | 80851285.60 | 217.47 | 14-AUG-07:10 | 23.48 | 21.75 |
| September | 0.120448E+10 | 5908.90 | 11-SEP-08:62 | 12.98 | 9.95 | 69527069.91 | 192.09 | 14-SEP-07:10 | 20.60 | 19.08 |
| October | 0.674677E+09 | 2934.46 | 12-OCT-08:63 | 15.10 | 13.11 | 62780189.23 | 154.88 | 12-OCT-08:09 | 15.10 | 13.11 |
| November | 0.487530E+09 | 794.58 | 24-NOV-08:03 | -2.6 | -3.4 | 43536743.53 | 133.51 | 01-NOV-14:50 | -2.6 | -3.4 |
| December | 0.512549E+09 | 1276.35 | 11-DEC-07:03 | -16.4 | -16.9 | 38905546.91 | 81.97 | 01-DEC-09:20 | -16.4 | -16.9 |
| Annual Sum or Average | 0.890561E+10 | 0.676928E+09 | ||||||||
| Minimum of Months | 0.278422E+09 | 792.83 | -16.5 | -17.1 | 36925074.87 | 80.76 | -16.5 | -17.1 | ||
| Maximum of Months | 0.165020E+10 | 5908.90 | 18.98 | 13.69 | 80851285.60 | 217.47 | 26.20 | 22.38 |
Report: ZoneCoolingSummaryMonthly
For: G NE APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | -1.0 | -1.6 | 77895344.61 | 42.51 | 30-JAN-22:00 | -10.6 | -11.5 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | -3.3 | -4.7 | 70357085.46 | 42.51 | 09-FEB-06:49 | -9.2 | -9.6 |
| March | 32065370.32 | 359.13 | 16-MAR-16:55 | 9.40 | 8.82 | 78777402.02 | 59.05 | 15-MAR-20:10 | 9.40 | 8.82 |
| April | 91597007.74 | 368.98 | 29-APR-18:50 | 8.40 | 7.18 | 75599013.10 | 43.31 | 07-APR-20:10 | 8.40 | 7.18 |
| May | 0.370254E+09 | 406.03 | 23-MAY-03:10 | 7.20 | 5.65 | 86189162.31 | 66.17 | 23-MAY-20:10 | 21.02 | 13.04 |
| June | 0.107279E+10 | 1141.07 | 27-JUN-13:00 | 30.60 | 23.75 | 0.117867E+09 | 70.35 | 23-JUN-20:49 | 30.60 | 23.75 |
| July | 0.193682E+10 | 1424.76 | 21-JUL-16:25 | 29.15 | 21.61 | 0.128561E+09 | 70.37 | 07-JUL-00:40 | 29.15 | 21.61 |
| August | 0.182193E+10 | 1383.81 | 09-AUG-16:04 | 29.40 | 18.45 | 0.128338E+09 | 70.35 | 31-AUG-20:49 | 13.98 | 11.76 |
| September | 0.103688E+10 | 1112.22 | 16-SEP-16:10 | 26.60 | 19.60 | 0.118768E+09 | 70.38 | 07-SEP-20:00 | 26.60 | 19.60 |
| October | 0.505496E+09 | 499.95 | 03-OCT-05:10 | 4.40 | 4.40 | 85823620.20 | 60.50 | 22-OCT-22:10 | 18.30 | 13.71 |
| November | 56530257.38 | 341.42 | 01-NOV-16:07 | 9.40 | 6.76 | 75570330.10 | 47.35 | 04-NOV-20:10 | 14.82 | 11.32 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 4.95 | 3.07 | 77895344.66 | 42.51 | 07-DEC-22:00 | -7.8 | -8.5 |
| Annual Sum or Average | 0.692436E+10 | 0.112164E+10 | ||||||||
| Minimum of Months | 0.00 | 0.00 | -3.3 | -4.7 | 70357085.46 | 42.51 | -10.6 | -11.5 | ||
| Maximum of Months | 0.193682E+10 | 1424.76 | 30.60 | 23.75 | 0.128561E+09 | 70.38 | 30.60 | 23.75 |
Report: ZoneCoolingSummaryMonthly
For: G N1 APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | -1.0 | -1.6 | 77895344.64 | 42.51 | 30-JAN-22:00 | -10.6 | -11.5 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | -3.3 | -4.7 | 70357085.48 | 42.51 | 09-FEB-06:49 | -9.2 | -9.6 |
| March | 63050668.72 | 369.88 | 16-MAR-16:55 | 9.40 | 8.82 | 79057853.61 | 59.76 | 15-MAR-20:10 | 9.40 | 8.82 |
| April | 0.143294E+09 | 371.53 | 29-APR-18:50 | 8.40 | 7.18 | 75718529.12 | 44.82 | 07-APR-20:10 | 8.40 | 7.18 |
| May | 0.474935E+09 | 424.99 | 27-MAY-04:00 | 7.20 | 6.43 | 89346558.25 | 65.19 | 23-MAY-20:10 | 7.20 | 6.43 |
| June | 0.990570E+09 | 970.98 | 27-JUN-17:40 | 25.97 | 22.30 | 0.120340E+09 | 70.35 | 22-JUN-02:09 | 25.97 | 22.30 |
| July | 0.169074E+10 | 1153.68 | 21-JUL-17:05 | 28.90 | 21.59 | 0.128728E+09 | 70.36 | 06-JUL-03:20 | 28.90 | 21.59 |
| August | 0.160679E+10 | 1103.54 | 09-AUG-17:05 | 29.32 | 18.15 | 0.128666E+09 | 70.36 | 04-AUG-04:00 | 29.32 | 18.15 |
| September | 0.996007E+09 | 938.90 | 16-SEP-16:20 | 26.50 | 19.63 | 0.121151E+09 | 70.37 | 23-SEP-03:30 | 13.90 | 11.47 |
| October | 0.703920E+09 | 544.15 | 23-OCT-22:00 | 2.80 | 1.04 | 88968453.23 | 63.64 | 03-OCT-22:10 | 2.80 | 1.04 |
| November | 0.182432E+09 | 383.65 | 01-NOV-18:10 | 8.03 | 4.73 | 75909596.26 | 50.08 | 04-NOV-20:10 | 14.82 | 11.32 |
| December | 1657648.88 | 120.96 | 01-DEC-13:00 | 13.90 | 12.22 | 77895344.66 | 42.51 | 07-DEC-22:00 | -7.8 | -8.5 |
| Annual Sum or Average | 0.685339E+10 | 0.113403E+10 | ||||||||
| Minimum of Months | 0.00 | 0.00 | -3.3 | -4.7 | 70357085.48 | 42.51 | -10.6 | -11.5 | ||
| Maximum of Months | 0.169074E+10 | 1153.68 | 29.32 | 22.30 | 0.128728E+09 | 70.37 | 29.32 | 22.30 |
Report: ZoneCoolingSummaryMonthly
For: G N2 APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | -1.0 | -1.6 | 77895344.64 | 42.51 | 30-JAN-22:00 | -10.6 | -11.5 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | -3.3 | -4.7 | 70357085.48 | 42.51 | 09-FEB-06:49 | -9.2 | -9.6 |
| March | 63180640.21 | 370.16 | 16-MAR-16:55 | 9.40 | 8.82 | 79068509.47 | 59.82 | 15-MAR-20:10 | 9.40 | 8.82 |
| April | 0.144420E+09 | 371.53 | 29-APR-18:50 | 8.40 | 7.18 | 75722787.85 | 44.87 | 07-APR-20:10 | 8.40 | 7.18 |
| May | 0.474755E+09 | 425.19 | 27-MAY-04:00 | 7.20 | 6.43 | 89353937.89 | 65.31 | 23-MAY-20:10 | 7.20 | 6.43 |
| June | 0.989247E+09 | 964.41 | 27-JUN-17:40 | 25.97 | 22.30 | 0.120286E+09 | 70.38 | 10-JUN-22:00 | 25.97 | 22.30 |
| July | 0.169163E+10 | 1153.85 | 21-JUL-17:05 | 28.90 | 21.59 | 0.128726E+09 | 70.36 | 07-JUL-01:39 | 28.90 | 21.59 |
| August | 0.160647E+10 | 1099.76 | 09-AUG-17:05 | 29.32 | 18.15 | 0.128664E+09 | 70.36 | 04-AUG-03:49 | 29.32 | 18.15 |
| September | 0.998916E+09 | 937.75 | 16-SEP-16:20 | 26.50 | 19.63 | 0.121169E+09 | 70.37 | 10-SEP-21:00 | 26.50 | 19.63 |
| October | 0.705542E+09 | 544.11 | 23-OCT-22:00 | 2.80 | 1.04 | 89025985.25 | 63.67 | 01-OCT-20:10 | 2.80 | 1.04 |
| November | 0.183260E+09 | 383.74 | 01-NOV-18:10 | 8.03 | 4.73 | 75912297.53 | 50.10 | 04-NOV-20:10 | 14.82 | 11.32 |
| December | 1677857.15 | 121.59 | 01-DEC-13:00 | 13.90 | 12.22 | 77895344.66 | 42.51 | 07-DEC-22:00 | -7.8 | -8.5 |
| Annual Sum or Average | 0.685910E+10 | 0.113408E+10 | ||||||||
| Minimum of Months | 0.00 | 0.00 | -3.3 | -4.7 | 70357085.48 | 42.51 | -10.6 | -11.5 | ||
| Maximum of Months | 0.169163E+10 | 1153.85 | 29.32 | 22.30 | 0.128726E+09 | 70.38 | 29.32 | 22.30 |
Report: ZoneCoolingSummaryMonthly
For: G S1 APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 23105297.96 | 482.25 | 15-JAN-13:40 | 4.80 | 2.14 | 78198821.84 | 42.51 | 07-JAN-08:50 | 4.80 | 2.14 |
| February | 18211995.60 | 312.71 | 28-FEB-15:10 | 0.10 | -2.7 | 69628662.56 | 42.51 | 07-FEB-18:00 | 0.10 | -2.7 |
| March | 0.186593E+09 | 487.17 | 17-MAR-18:50 | 4.68 | 2.69 | 76891916.28 | 70.29 | 15-MAR-18:19 | 4.68 | 2.69 |
| April | 0.403123E+09 | 470.20 | 23-APR-23:40 | 5.20 | 2.50 | 77760242.54 | 60.78 | 23-APR-15:30 | 5.20 | 2.50 |
| May | 0.603829E+09 | 446.09 | 06-MAY-23:00 | 6.10 | 4.76 | 94683480.85 | 70.35 | 26-MAY-18:19 | 20.20 | 11.25 |
| June | 0.117237E+10 | 1115.47 | 27-JUN-13:00 | 30.60 | 23.75 | 0.117697E+09 | 70.36 | 14-JUN-20:19 | 30.60 | 23.75 |
| July | 0.196917E+10 | 1369.84 | 21-JUL-13:30 | 31.15 | 21.91 | 0.129256E+09 | 70.35 | 07-JUL-03:09 | 31.15 | 21.91 |
| August | 0.206406E+10 | 1481.69 | 10-AUG-15:10 | 29.90 | 19.74 | 0.123931E+09 | 70.36 | 03-AUG-03:00 | 29.90 | 19.74 |
| September | 0.163643E+10 | 1664.83 | 21-SEP-15:10 | 26.10 | 16.73 | 0.122795E+09 | 70.37 | 06-SEP-01:10 | 26.10 | 16.73 |
| October | 0.103700E+10 | 990.69 | 11-OCT-15:10 | 22.12 | 14.59 | 0.101393E+09 | 70.37 | 12-OCT-01:49 | 14.40 | 10.80 |
| November | 0.550120E+09 | 596.28 | 18-NOV-20:00 | 1.10 | -0.2 | 79038293.82 | 59.71 | 01-NOV-17:10 | 1.10 | -0.2 |
| December | 38541717.15 | 562.40 | 17-DEC-13:30 | 2.20 | 0.48 | 78204868.66 | 42.51 | 12-DEC-18:00 | 2.20 | 0.48 |
| Annual Sum or Average | 0.970255E+10 | 0.114948E+10 | ||||||||
| Minimum of Months | 18211995.60 | 312.71 | 0.10 | -2.7 | 69628662.56 | 42.51 | 0.10 | -2.7 | ||
| Maximum of Months | 0.206406E+10 | 1664.83 | 31.15 | 23.75 | 0.129256E+09 | 70.37 | 31.15 | 23.75 |
Report: ZoneCoolingSummaryMonthly
For: G S2 APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 12917426.49 | 407.57 | 15-JAN-14:30 | 5.30 | 1.93 | 78198344.11 | 42.51 | 07-JAN-08:50 | 5.30 | 1.93 |
| February | 11141298.29 | 255.64 | 28-FEB-15:10 | 0.10 | -2.7 | 69628662.56 | 42.51 | 07-FEB-18:00 | 0.10 | -2.7 |
| March | 0.153764E+09 | 497.12 | 17-MAR-19:00 | 4.40 | 2.49 | 76858257.51 | 70.29 | 15-MAR-18:19 | 4.40 | 2.49 |
| April | 0.382045E+09 | 459.33 | 23-APR-23:00 | 5.60 | 2.59 | 77651868.50 | 60.50 | 23-APR-15:09 | 5.60 | 2.59 |
| May | 0.617103E+09 | 446.93 | 06-MAY-23:00 | 6.10 | 4.76 | 95765223.24 | 70.36 | 26-MAY-18:49 | 19.60 | 10.81 |
| June | 0.126464E+10 | 1177.04 | 27-JUN-13:00 | 30.60 | 23.75 | 0.118138E+09 | 70.37 | 11-JUN-05:10 | 30.60 | 23.75 |
| July | 0.216165E+10 | 1447.90 | 21-JUL-13:30 | 31.15 | 21.91 | 0.129270E+09 | 70.30 | 04-JUL-20:00 | 31.15 | 21.91 |
| August | 0.225615E+10 | 1577.17 | 13-AUG-15:20 | 29.80 | 23.30 | 0.123947E+09 | 70.35 | 31-AUG-01:00 | 12.80 | 12.15 |
| September | 0.175556E+10 | 1715.28 | 21-SEP-15:10 | 26.10 | 16.73 | 0.123009E+09 | 70.37 | 28-SEP-18:10 | 11.10 | 10.18 |
| October | 0.105319E+10 | 1016.71 | 11-OCT-15:10 | 22.12 | 14.59 | 0.102207E+09 | 70.37 | 13-OCT-18:30 | 9.70 | 7.73 |
| November | 0.512431E+09 | 583.86 | 18-NOV-19:20 | 1.50 | 0.09 | 78886134.86 | 60.34 | 01-NOV-17:10 | 1.50 | 0.09 |
| December | 24938546.74 | 475.92 | 16-DEC-12:30 | 5.00 | 2.46 | 78200461.48 | 42.51 | 12-DEC-18:00 | 5.00 | 2.46 |
| Annual Sum or Average | 0.102055E+11 | 0.115176E+10 | ||||||||
| Minimum of Months | 11141298.29 | 255.64 | 0.10 | -2.7 | 69628662.56 | 42.51 | 0.10 | -2.7 | ||
| Maximum of Months | 0.225615E+10 | 1715.28 | 31.15 | 23.75 | 0.129270E+09 | 70.37 | 31.15 | 23.75 |
Report: ZoneCoolingSummaryMonthly
For: M SW APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 36101150.11 | 681.29 | 06-JAN-15:20 | -2.2 | -4.9 | 78266107.99 | 52.00 | 15-JAN-16:10 | 4.82 | 1.15 |
| February | 51725568.00 | 664.29 | 28-FEB-17:25 | -0.9 | -3.1 | 69645342.67 | 44.75 | 18-FEB-16:30 | -0.9 | -3.1 |
| March | 0.498407E+09 | 1370.59 | 15-MAR-13:50 | 25.92 | 15.99 | 80024079.27 | 70.29 | 15-MAR-18:19 | 22.97 | 15.37 |
| April | 0.820644E+09 | 1197.29 | 09-APR-16:03 | 15.22 | 11.74 | 89820974.58 | 70.31 | 08-APR-16:49 | 15.22 | 11.74 |
| May | 0.139746E+10 | 1788.50 | 14-MAY-14:30 | 25.55 | 18.01 | 0.118257E+09 | 70.31 | 21-MAY-02:20 | 14.23 | 11.79 |
| June | 0.231338E+10 | 2263.59 | 12-JUN-16:10 | 27.57 | 19.99 | 0.119524E+09 | 70.31 | 09-JUN-02:30 | 27.57 | 19.99 |
| July | 0.305831E+10 | 2333.25 | 18-JUL-17:20 | 27.77 | 19.70 | 0.129269E+09 | 70.30 | 04-JUL-20:00 | 27.77 | 19.70 |
| August | 0.284496E+10 | 2573.90 | 10-AUG-16:10 | 29.22 | 19.52 | 0.123893E+09 | 70.30 | 01-AUG-17:49 | 29.22 | 19.52 |
| September | 0.198525E+10 | 2718.34 | 21-SEP-16:10 | 26.02 | 17.14 | 0.121552E+09 | 70.31 | 06-SEP-00:00 | 26.02 | 17.14 |
| October | 0.954875E+09 | 1959.92 | 11-OCT-16:10 | 21.70 | 14.52 | 97643063.25 | 70.30 | 23-OCT-01:10 | 16.70 | 13.43 |
| November | 0.363144E+09 | 604.47 | 18-NOV-20:30 | 0.85 | -0.4 | 78958994.73 | 60.40 | 26-NOV-18:10 | 14.90 | 9.50 |
| December | 36678813.38 | 601.87 | 04-DEC-15:30 | -0.3 | -3.1 | 78257903.61 | 47.54 | 16-DEC-16:10 | 4.22 | 2.19 |
| Annual Sum or Average | 0.143609E+11 | 0.118511E+10 | ||||||||
| Minimum of Months | 36101150.11 | 601.87 | -2.2 | -4.9 | 69645342.67 | 44.75 | -0.9 | -3.1 | ||
| Maximum of Months | 0.305831E+10 | 2718.34 | 29.22 | 19.99 | 0.129269E+09 | 70.31 | 29.22 | 19.99 |
Report: ZoneCoolingSummaryMonthly
For: M NW APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 10043.13 | 11.60 | 15-JAN-16:10 | 4.82 | 1.15 | 77895344.60 | 42.51 | 30-JAN-22:00 | -10.6 | -11.5 |
| February | 5965.46 | 10.55 | 22-FEB-17:03 | 11.88 | 5.66 | 70357085.45 | 42.51 | 12-FEB-22:00 | 11.88 | 5.66 |
| March | 0.203314E+09 | 725.56 | 15-MAR-17:10 | 24.82 | 15.90 | 82351734.41 | 70.31 | 16-MAR-02:20 | 18.90 | 13.75 |
| April | 0.563588E+09 | 613.36 | 22-APR-06:00 | 0.60 | 0.13 | 82318787.93 | 64.50 | 09-APR-20:10 | 0.60 | 0.13 |
| May | 0.111388E+10 | 1616.30 | 31-MAY-18:00 | 21.10 | 14.05 | 0.117944E+09 | 70.31 | 30-MAY-23:10 | 21.10 | 14.05 |
| June | 0.210805E+10 | 2120.08 | 27-JUN-17:05 | 26.52 | 22.66 | 0.123604E+09 | 70.32 | 07-JUN-03:49 | 26.52 | 22.66 |
| July | 0.277196E+10 | 2179.03 | 18-JUL-17:40 | 27.23 | 19.56 | 0.128771E+09 | 70.30 | 04-JUL-05:40 | 27.23 | 19.56 |
| August | 0.237516E+10 | 2153.50 | 10-AUG-17:17 | 27.93 | 19.70 | 0.128670E+09 | 70.31 | 30-AUG-22:00 | 12.80 | 12.52 |
| September | 0.131383E+10 | 1661.71 | 21-SEP-16:30 | 25.85 | 17.07 | 0.120426E+09 | 70.30 | 13-SEP-05:00 | 25.85 | 17.07 |
| October | 0.560719E+09 | 532.31 | 23-OCT-20:00 | 3.30 | 1.70 | 89449058.75 | 66.44 | 12-OCT-21:49 | 3.30 | 1.70 |
| November | 0.105870E+09 | 408.80 | 03-NOV-17:25 | 7.20 | 4.04 | 76106637.42 | 50.46 | 04-NOV-20:10 | 14.82 | 11.32 |
| December | 56773.78 | 20.00 | 01-DEC-13:00 | 13.90 | 12.22 | 77895344.65 | 42.51 | 07-DEC-22:00 | -7.8 | -8.5 |
| Annual Sum or Average | 0.111164E+11 | 0.117579E+10 | ||||||||
| Minimum of Months | 5965.46 | 10.55 | 0.60 | 0.13 | 70357085.45 | 42.51 | -10.6 | -11.5 | ||
| Maximum of Months | 0.277196E+10 | 2179.03 | 27.93 | 22.66 | 0.128771E+09 | 70.32 | 27.23 | 22.66 |
Report: ZoneCoolingSummaryMonthly
For: M SE APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 35986699.82 | 573.51 | 06-JAN-13:40 | -3.0 | -5.3 | 78242943.79 | 47.82 | 15-JAN-16:10 | 4.82 | 1.15 |
| February | 56654548.35 | 675.00 | 08-FEB-13:00 | -7.2 | -8.8 | 69628753.04 | 42.51 | 07-FEB-18:00 | -7.2 | -8.8 |
| March | 0.491337E+09 | 1395.84 | 15-MAR-13:30 | 25.55 | 15.84 | 79677985.87 | 70.29 | 15-MAR-18:19 | 22.97 | 15.37 |
| April | 0.842623E+09 | 1070.25 | 22-APR-13:30 | 15.00 | 6.82 | 89584587.54 | 70.28 | 23-APR-19:49 | 9.78 | 5.01 |
| May | 0.139870E+10 | 1514.82 | 14-MAY-14:10 | 25.18 | 18.10 | 0.118045E+09 | 70.32 | 04-MAY-20:19 | 25.18 | 18.10 |
| June | 0.227406E+10 | 2179.15 | 12-JUN-13:00 | 29.40 | 19.72 | 0.119450E+09 | 70.32 | 03-JUN-05:10 | 29.40 | 19.72 |
| July | 0.307408E+10 | 2251.53 | 21-JUL-13:30 | 31.15 | 21.91 | 0.129270E+09 | 70.31 | 03-JUL-03:49 | 31.15 | 21.91 |
| August | 0.284090E+10 | 2294.93 | 18-AUG-13:30 | 29.70 | 20.75 | 0.123886E+09 | 70.31 | 03-AUG-02:00 | 29.70 | 20.75 |
| September | 0.201684E+10 | 2383.40 | 21-SEP-13:30 | 25.30 | 16.56 | 0.121470E+09 | 70.31 | 02-SEP-23:49 | 25.30 | 16.56 |
| October | 0.974423E+09 | 1685.99 | 11-OCT-12:30 | 21.95 | 13.79 | 98065612.67 | 70.31 | 01-OCT-19:10 | 21.95 | 13.79 |
| November | 0.374308E+09 | 599.49 | 18-NOV-20:10 | 1.02 | -0.3 | 79010522.59 | 60.37 | 26-NOV-18:10 | 14.90 | 9.50 |
| December | 34966446.00 | 583.83 | 17-DEC-11:40 | 1.50 | -0.3 | 78257420.44 | 45.18 | 16-DEC-16:10 | 1.50 | -0.3 |
| Annual Sum or Average | 0.144149E+11 | 0.118459E+10 | ||||||||
| Minimum of Months | 34966446.00 | 573.51 | -7.2 | -8.8 | 69628753.04 | 42.51 | -7.2 | -8.8 | ||
| Maximum of Months | 0.307408E+10 | 2383.40 | 31.15 | 21.91 | 0.129270E+09 | 70.32 | 31.15 | 21.91 |
Report: ZoneCoolingSummaryMonthly
For: M NE APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | -1.0 | -1.6 | 77895344.60 | 42.51 | 30-JAN-22:00 | -10.6 | -11.5 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | -3.3 | -4.7 | 70357085.45 | 42.51 | 12-FEB-22:00 | -8.3 | -8.7 |
| March | 0.191567E+09 | 676.88 | 15-MAR-16:20 | 25.00 | 15.96 | 82404860.54 | 70.31 | 15-MAR-23:49 | 17.20 | 13.28 |
| April | 0.571246E+09 | 619.22 | 22-APR-06:00 | 0.60 | 0.13 | 82340195.53 | 64.12 | 09-APR-20:10 | 0.60 | 0.13 |
| May | 0.110280E+10 | 1178.50 | 23-MAY-16:10 | 23.80 | 13.18 | 0.117739E+09 | 70.31 | 21-MAY-22:40 | 23.80 | 13.18 |
| June | 0.206816E+10 | 1895.23 | 12-JUN-11:00 | 28.90 | 19.72 | 0.123561E+09 | 70.31 | 05-JUN-22:00 | 28.90 | 19.72 |
| July | 0.278790E+10 | 1857.61 | 21-JUL-10:30 | 28.85 | 21.90 | 0.128765E+09 | 70.31 | 06-JUL-03:39 | 28.85 | 21.90 |
| August | 0.237085E+10 | 1714.48 | 09-AUG-16:04 | 29.40 | 18.45 | 0.128648E+09 | 70.30 | 22-AUG-02:00 | 14.40 | 12.82 |
| September | 0.133466E+10 | 1348.72 | 16-SEP-16:10 | 26.60 | 19.60 | 0.120385E+09 | 70.31 | 06-SEP-23:30 | 26.60 | 19.60 |
| October | 0.588148E+09 | 537.00 | 23-OCT-21:25 | 3.05 | 1.16 | 89559593.72 | 66.25 | 22-OCT-22:10 | 3.05 | 1.16 |
| November | 0.108128E+09 | 432.66 | 01-NOV-21:00 | 4.40 | 3.43 | 76138064.93 | 50.18 | 04-NOV-20:10 | 14.82 | 11.32 |
| December | 148749.87 | 48.57 | 16-DEC-12:00 | 4.40 | 1.70 | 77895344.65 | 42.51 | 07-DEC-22:00 | 4.40 | 1.70 |
| Annual Sum or Average | 0.111236E+11 | 0.117569E+10 | ||||||||
| Minimum of Months | 0.00 | 0.00 | -3.3 | -4.7 | 70357085.45 | 42.51 | -10.6 | -11.5 | ||
| Maximum of Months | 0.278790E+10 | 1895.23 | 29.40 | 21.90 | 0.128765E+09 | 70.31 | 28.90 | 21.90 |
Report: ZoneCoolingSummaryMonthly
For: M N1 APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 18537803.71 | 212.01 | 17-JAN-20:00 | 5.60 | 4.80 | 77895344.64 | 42.51 | 30-JAN-22:00 | -10.6 | -11.5 |
| February | 8283483.03 | 190.25 | 22-FEB-19:00 | 12.80 | 6.30 | 70357085.48 | 42.51 | 12-FEB-22:00 | 12.80 | 6.30 |
| March | 0.366506E+09 | 633.49 | 18-MAR-10:00 | 0.00 | -0.5 | 83444370.73 | 70.27 | 16-MAR-21:30 | 0.00 | -0.5 |
| April | 0.735322E+09 | 624.09 | 22-APR-06:00 | 0.60 | 0.13 | 84048278.15 | 64.81 | 09-APR-20:10 | 0.60 | 0.13 |
| May | 0.105446E+10 | 992.99 | 25-MAY-16:04 | 15.32 | 11.70 | 0.121204E+09 | 70.31 | 29-MAY-22:00 | 12.20 | 11.28 |
| June | 0.172474E+10 | 1338.60 | 27-JUN-17:50 | 25.78 | 22.18 | 0.124108E+09 | 70.30 | 16-JUN-02:39 | 25.78 | 22.18 |
| July | 0.225123E+10 | 1403.67 | 21-JUL-16:30 | 29.15 | 21.61 | 0.128775E+09 | 70.30 | 04-JUL-20:00 | 29.15 | 21.61 |
| August | 0.198000E+10 | 1311.75 | 09-AUG-16:17 | 29.40 | 18.38 | 0.128765E+09 | 70.29 | 03-AUG-04:10 | 29.40 | 18.38 |
| September | 0.123405E+10 | 1100.42 | 16-SEP-16:20 | 26.50 | 19.63 | 0.122607E+09 | 70.31 | 21-SEP-03:09 | 12.70 | 11.69 |
| October | 0.820440E+09 | 621.76 | 24-OCT-03:30 | 0.30 | -0.9 | 94425642.36 | 69.13 | 05-OCT-21:40 | 0.30 | -0.9 |
| November | 0.359739E+09 | 504.47 | 01-NOV-21:00 | 4.40 | 3.43 | 76943270.72 | 53.25 | 04-NOV-20:10 | 14.82 | 11.32 |
| December | 23186329.82 | 233.31 | 01-DEC-13:10 | 12.97 | 11.34 | 77895882.69 | 42.51 | 07-DEC-22:00 | -7.8 | -8.5 |
| Annual Sum or Average | 0.105765E+11 | 0.119047E+10 | ||||||||
| Minimum of Months | 8283483.03 | 190.25 | 0.00 | -0.9 | 70357085.48 | 42.51 | -10.6 | -11.5 | ||
| Maximum of Months | 0.225123E+10 | 1403.67 | 29.40 | 22.18 | 0.128775E+09 | 70.31 | 29.40 | 22.18 |
Report: ZoneCoolingSummaryMonthly
For: M N2 APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 18444667.22 | 211.62 | 17-JAN-20:00 | 5.60 | 4.80 | 77895344.64 | 42.51 | 30-JAN-22:00 | -10.6 | -11.5 |
| February | 8150610.61 | 188.19 | 22-FEB-19:00 | 12.80 | 6.30 | 70357085.48 | 42.51 | 12-FEB-22:00 | 12.80 | 6.30 |
| March | 0.366475E+09 | 633.69 | 18-MAR-10:00 | 0.00 | -0.5 | 83448340.59 | 70.27 | 15-MAR-20:10 | 0.00 | -0.5 |
| April | 0.736480E+09 | 623.99 | 22-APR-06:00 | 0.60 | 0.13 | 84161589.65 | 65.07 | 09-APR-20:10 | 0.60 | 0.13 |
| May | 0.105662E+10 | 1026.86 | 25-MAY-16:04 | 15.32 | 11.70 | 0.121218E+09 | 70.31 | 15-MAY-22:19 | 15.32 | 11.70 |
| June | 0.172409E+10 | 1330.26 | 27-JUN-17:40 | 25.97 | 22.30 | 0.124102E+09 | 70.31 | 05-JUN-23:49 | 25.97 | 22.30 |
| July | 0.225210E+10 | 1405.13 | 21-JUL-16:30 | 29.15 | 21.61 | 0.128775E+09 | 70.30 | 04-JUL-20:00 | 29.15 | 21.61 |
| August | 0.198009E+10 | 1307.62 | 09-AUG-16:17 | 29.40 | 18.38 | 0.128765E+09 | 70.31 | 03-AUG-05:10 | 29.40 | 18.38 |
| September | 0.123669E+10 | 1097.54 | 16-SEP-16:20 | 26.50 | 19.63 | 0.122598E+09 | 70.32 | 20-SEP-01:39 | 12.60 | 11.01 |
| October | 0.821704E+09 | 624.54 | 24-OCT-03:40 | 0.20 | -0.9 | 94502191.19 | 69.24 | 05-OCT-21:40 | 0.20 | -0.9 |
| November | 0.360742E+09 | 504.67 | 01-NOV-21:00 | 4.40 | 3.43 | 76950422.08 | 53.25 | 04-NOV-20:10 | 14.82 | 11.32 |
| December | 23229530.16 | 233.38 | 01-DEC-13:10 | 12.97 | 11.34 | 77895923.76 | 42.51 | 07-DEC-22:00 | -7.8 | -8.5 |
| Annual Sum or Average | 0.105848E+11 | 0.119067E+10 | ||||||||
| Minimum of Months | 8150610.61 | 188.19 | 0.00 | -0.9 | 70357085.48 | 42.51 | -10.6 | -11.5 | ||
| Maximum of Months | 0.225210E+10 | 1405.13 | 29.40 | 22.30 | 0.128775E+09 | 70.32 | 29.40 | 22.30 |
Report: ZoneCoolingSummaryMonthly
For: M S1 APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.205365E+09 | 744.79 | 06-JAN-12:10 | -3.8 | -5.6 | 78381012.82 | 54.39 | 15-JAN-16:10 | 4.82 | 1.15 |
| February | 0.188235E+09 | 853.87 | 08-FEB-13:00 | -7.2 | -8.8 | 69731219.68 | 48.41 | 22-FEB-19:10 | 12.70 | 6.24 |
| March | 0.879276E+09 | 1227.40 | 15-MAR-13:30 | 25.55 | 15.84 | 81798851.46 | 70.31 | 16-MAR-22:19 | 11.30 | 10.59 |
| April | 0.101027E+10 | 1020.20 | 09-APR-16:03 | 15.22 | 11.74 | 94281982.74 | 70.32 | 26-APR-18:00 | 11.70 | 7.81 |
| May | 0.135196E+10 | 1340.62 | 14-MAY-14:10 | 25.18 | 18.10 | 0.121551E+09 | 70.31 | 29-MAY-23:30 | 12.20 | 11.28 |
| June | 0.193142E+10 | 1589.44 | 12-JUN-13:20 | 29.80 | 19.89 | 0.119978E+09 | 70.31 | 16-JUN-04:19 | 12.43 | 9.65 |
| July | 0.253862E+10 | 1711.97 | 21-JUL-13:30 | 31.15 | 21.91 | 0.129274E+09 | 70.30 | 04-JUL-20:00 | 31.15 | 21.91 |
| August | 0.245337E+10 | 1798.38 | 18-AUG-14:10 | 30.00 | 20.99 | 0.123959E+09 | 70.30 | 01-AUG-17:49 | 30.00 | 20.99 |
| September | 0.194021E+10 | 2082.47 | 21-SEP-14:10 | 25.68 | 16.62 | 0.123124E+09 | 70.32 | 02-SEP-04:49 | 25.68 | 16.62 |
| October | 0.120989E+10 | 1605.10 | 11-OCT-14:30 | 22.20 | 14.37 | 0.106298E+09 | 70.32 | 13-OCT-20:19 | 8.90 | 7.16 |
| November | 0.731227E+09 | 660.56 | 18-NOV-22:00 | -0.6 | -1.4 | 83115037.57 | 66.83 | 01-NOV-17:10 | -0.6 | -1.4 |
| December | 0.168906E+09 | 672.81 | 04-DEC-16:30 | -1.4 | -3.9 | 78404520.19 | 51.06 | 16-DEC-16:10 | 4.22 | 2.19 |
| Annual Sum or Average | 0.146088E+11 | 0.120990E+10 | ||||||||
| Minimum of Months | 0.168906E+09 | 660.56 | -7.2 | -8.8 | 69731219.68 | 48.41 | -0.6 | -1.4 | ||
| Maximum of Months | 0.253862E+10 | 2082.47 | 31.15 | 21.91 | 0.129274E+09 | 70.32 | 31.15 | 21.91 |
Report: ZoneCoolingSummaryMonthly
For: M S2 APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.205977E+09 | 747.24 | 06-JAN-12:00 | -3.9 | -5.7 | 78378977.33 | 54.30 | 15-JAN-16:10 | 4.82 | 1.15 |
| February | 0.189049E+09 | 854.30 | 08-FEB-13:00 | -7.2 | -8.8 | 69729026.01 | 48.34 | 22-FEB-19:10 | 12.70 | 6.24 |
| March | 0.878919E+09 | 1232.63 | 15-MAR-13:30 | 25.55 | 15.84 | 81778336.70 | 70.31 | 16-MAR-22:30 | 11.40 | 10.64 |
| April | 0.101312E+10 | 1030.15 | 09-APR-16:03 | 15.22 | 11.74 | 94321471.63 | 70.31 | 23-APR-20:40 | 7.93 | 4.16 |
| May | 0.135418E+10 | 1336.79 | 14-MAY-14:10 | 25.18 | 18.10 | 0.121529E+09 | 70.32 | 12-MAY-18:49 | 25.18 | 18.10 |
| June | 0.193088E+10 | 1595.47 | 12-JUN-13:20 | 29.80 | 19.89 | 0.119970E+09 | 70.32 | 13-JUN-21:00 | 8.90 | 6.20 |
| July | 0.253954E+10 | 1717.61 | 21-JUL-13:30 | 31.15 | 21.91 | 0.129274E+09 | 70.30 | 25-JUL-05:49 | 15.92 | 13.99 |
| August | 0.245356E+10 | 1802.82 | 18-AUG-14:10 | 30.00 | 20.99 | 0.123959E+09 | 70.30 | 01-AUG-17:49 | 30.00 | 20.99 |
| September | 0.194186E+10 | 2085.73 | 21-SEP-14:10 | 25.68 | 16.62 | 0.123114E+09 | 70.32 | 02-SEP-03:00 | 25.68 | 16.62 |
| October | 0.121343E+10 | 1611.73 | 11-OCT-14:30 | 22.20 | 14.37 | 0.106378E+09 | 70.31 | 13-OCT-20:19 | 8.90 | 7.16 |
| November | 0.731812E+09 | 660.50 | 18-NOV-22:00 | -0.6 | -1.4 | 83134716.46 | 66.93 | 01-NOV-17:10 | -0.6 | -1.4 |
| December | 0.169004E+09 | 672.65 | 04-DEC-16:30 | -1.4 | -3.9 | 78404949.49 | 51.02 | 16-DEC-16:10 | 4.22 | 2.19 |
| Annual Sum or Average | 0.146213E+11 | 0.120997E+10 | ||||||||
| Minimum of Months | 0.169004E+09 | 660.50 | -7.2 | -8.8 | 69729026.01 | 48.34 | -0.6 | -1.4 | ||
| Maximum of Months | 0.253954E+10 | 2085.73 | 31.15 | 21.91 | 0.129274E+09 | 70.32 | 30.00 | 20.99 |
Report: ZoneCoolingSummaryMonthly
For: T SW APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 17381582.51 | 581.90 | 15-JAN-17:45 | 1.57 | -0.4 | 78299818.57 | 58.57 | 15-JAN-16:10 | 1.57 | -0.4 |
| February | 35553114.27 | 673.97 | 28-FEB-17:01 | -0.7 | -3.0 | 69641649.59 | 45.90 | 18-FEB-16:10 | -0.7 | -3.0 |
| March | 0.309693E+09 | 2243.05 | 15-MAR-13:50 | 25.92 | 15.99 | 78687670.73 | 70.36 | 16-MAR-00:40 | 17.20 | 13.12 |
| April | 0.554318E+09 | 1723.50 | 22-APR-15:00 | 15.60 | 7.04 | 83900966.04 | 70.35 | 09-APR-19:19 | 15.60 | 7.04 |
| May | 0.114619E+10 | 2490.14 | 14-MAY-14:40 | 25.73 | 17.96 | 0.101205E+09 | 70.36 | 30-MAY-20:40 | 13.67 | 11.55 |
| June | 0.229594E+10 | 3132.38 | 12-JUN-15:30 | 29.15 | 20.10 | 0.112985E+09 | 70.36 | 23-JUN-23:30 | 14.15 | 12.07 |
| July | 0.325840E+10 | 3220.59 | 18-JUL-16:15 | 29.03 | 20.67 | 0.127531E+09 | 70.34 | 08-JUL-03:39 | 29.03 | 20.67 |
| August | 0.288572E+10 | 3465.12 | 10-AUG-16:04 | 29.22 | 19.52 | 0.120784E+09 | 70.37 | 13-AUG-00:30 | 15.30 | 11.44 |
| September | 0.171186E+10 | 3438.11 | 21-SEP-15:30 | 26.10 | 16.91 | 0.109685E+09 | 70.37 | 22-SEP-23:10 | 14.60 | 11.66 |
| October | 0.551534E+09 | 2551.62 | 11-OCT-15:30 | 21.95 | 14.56 | 87671972.29 | 70.36 | 21-OCT-17:00 | 16.70 | 12.00 |
| November | 0.150393E+09 | 598.02 | 03-NOV-15:10 | 9.82 | 5.39 | 76866032.82 | 67.70 | 25-NOV-16:10 | 11.93 | 5.11 |
| December | 19871788.35 | 567.58 | 17-DEC-13:40 | 2.20 | 0.48 | 78282147.15 | 51.41 | 16-DEC-16:10 | 2.20 | 0.48 |
| Annual Sum or Average | 0.129368E+11 | 0.112554E+10 | ||||||||
| Minimum of Months | 17381582.51 | 567.58 | -0.7 | -3.0 | 69641649.59 | 45.90 | -0.7 | -3.0 | ||
| Maximum of Months | 0.325840E+10 | 3465.12 | 29.22 | 20.67 | 0.127531E+09 | 70.37 | 29.03 | 20.67 |
Report: ZoneCoolingSummaryMonthly
For: T NW APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | -1.0 | -1.6 | 77895344.50 | 42.51 | 30-JAN-22:00 | -10.6 | -11.5 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | -3.3 | -4.7 | 70357085.37 | 42.51 | 12-FEB-22:00 | -8.3 | -8.7 |
| March | 0.131763E+09 | 1359.55 | 15-MAR-16:30 | 25.00 | 15.96 | 81125700.70 | 70.32 | 15-MAR-23:19 | 17.20 | 13.28 |
| April | 0.280709E+09 | 799.60 | 09-APR-16:03 | 15.22 | 11.74 | 81253340.71 | 61.98 | 09-APR-20:10 | 9.32 | 8.45 |
| May | 0.865649E+09 | 1960.55 | 31-MAY-18:00 | 21.10 | 14.05 | 0.101667E+09 | 70.34 | 14-MAY-20:19 | 21.10 | 14.05 |
| June | 0.208172E+10 | 2886.01 | 12-JUN-16:05 | 27.57 | 19.99 | 0.117053E+09 | 70.36 | 03-JUN-22:10 | 27.57 | 19.99 |
| July | 0.295207E+10 | 2956.36 | 18-JUL-17:15 | 27.77 | 19.70 | 0.127154E+09 | 70.35 | 12-JUL-01:39 | 27.77 | 19.70 |
| August | 0.239707E+10 | 2915.79 | 10-AUG-16:30 | 28.85 | 19.49 | 0.125133E+09 | 70.36 | 04-AUG-00:30 | 28.85 | 19.49 |
| September | 0.105879E+10 | 2177.22 | 16-SEP-16:10 | 26.60 | 19.60 | 0.107042E+09 | 70.35 | 10-SEP-20:40 | 26.60 | 19.60 |
| October | 0.229282E+09 | 1004.90 | 11-OCT-16:30 | 21.70 | 14.52 | 83454874.83 | 67.50 | 22-OCT-22:10 | 18.30 | 13.71 |
| November | 36226876.03 | 359.30 | 03-NOV-16:03 | 8.80 | 4.88 | 75665567.20 | 49.05 | 04-NOV-20:10 | 14.82 | 11.32 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 4.95 | 3.07 | 77895344.61 | 42.51 | 07-DEC-22:00 | -7.8 | -8.5 |
| Annual Sum or Average | 0.100333E+11 | 0.112570E+10 | ||||||||
| Minimum of Months | 0.00 | 0.00 | -3.3 | -4.7 | 70357085.37 | 42.51 | -10.6 | -11.5 | ||
| Maximum of Months | 0.295207E+10 | 2956.36 | 28.85 | 19.99 | 0.127154E+09 | 70.36 | 28.85 | 19.99 |
Report: ZoneCoolingSummaryMonthly
For: T SE APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 16298479.85 | 540.56 | 15-JAN-17:12 | 2.97 | 0.29 | 78257106.67 | 50.62 | 15-JAN-16:10 | 2.97 | 0.29 |
| February | 36173544.37 | 725.97 | 08-FEB-13:00 | -7.2 | -8.8 | 69628620.07 | 42.51 | 07-FEB-18:00 | -7.2 | -8.8 |
| March | 0.302854E+09 | 2238.21 | 15-MAR-13:40 | 25.73 | 15.91 | 78307001.25 | 70.36 | 16-MAR-00:20 | 17.20 | 13.20 |
| April | 0.563296E+09 | 1596.86 | 22-APR-13:40 | 15.20 | 6.94 | 83361103.78 | 70.36 | 23-APR-18:40 | 12.07 | 6.49 |
| May | 0.112070E+10 | 2136.99 | 14-MAY-14:10 | 25.18 | 18.10 | 0.101031E+09 | 70.36 | 19-MAY-18:30 | 13.05 | 9.18 |
| June | 0.224467E+10 | 3081.40 | 12-JUN-13:00 | 29.40 | 19.72 | 0.112887E+09 | 70.35 | 15-JUN-19:30 | 16.65 | 9.66 |
| July | 0.327093E+10 | 3194.72 | 21-JUL-13:30 | 31.15 | 21.91 | 0.127662E+09 | 70.34 | 14-JUL-01:30 | 31.15 | 21.91 |
| August | 0.287485E+10 | 3190.14 | 09-AUG-13:30 | 29.15 | 18.13 | 0.120746E+09 | 70.36 | 02-AUG-23:30 | 29.15 | 18.13 |
| September | 0.172180E+10 | 3015.22 | 21-SEP-13:40 | 25.40 | 16.58 | 0.109796E+09 | 70.35 | 23-SEP-18:00 | 15.60 | 14.89 |
| October | 0.561270E+09 | 2201.05 | 11-OCT-12:40 | 22.03 | 13.91 | 87635557.00 | 70.34 | 22-OCT-19:00 | 17.80 | 13.82 |
| November | 0.154638E+09 | 525.02 | 18-NOV-14:00 | 5.00 | 1.95 | 76850498.63 | 63.34 | 25-NOV-16:10 | 11.93 | 5.11 |
| December | 19472435.84 | 567.99 | 17-DEC-13:30 | 2.20 | 0.48 | 78278837.99 | 46.90 | 16-DEC-16:10 | 2.20 | 0.48 |
| Annual Sum or Average | 0.128870E+11 | 0.112444E+10 | ||||||||
| Minimum of Months | 16298479.85 | 525.02 | -7.2 | -8.8 | 69628620.07 | 42.51 | -7.2 | -8.8 | ||
| Maximum of Months | 0.327093E+10 | 3194.72 | 31.15 | 21.91 | 0.127662E+09 | 70.36 | 31.15 | 21.91 |
Report: ZoneCoolingSummaryMonthly
For: T NE APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | -1.0 | -1.6 | 77895344.51 | 42.51 | 30-JAN-22:00 | -10.6 | -11.5 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | -3.3 | -4.7 | 70357085.38 | 42.51 | 12-FEB-22:00 | -8.3 | -8.7 |
| March | 0.128572E+09 | 1243.12 | 15-MAR-16:20 | 25.00 | 15.96 | 81147340.50 | 70.27 | 15-MAR-20:10 | 20.73 | 14.37 |
| April | 0.271057E+09 | 577.70 | 09-APR-16:03 | 15.22 | 11.74 | 80769678.68 | 61.14 | 06-APR-17:10 | 15.22 | 11.74 |
| May | 0.820108E+09 | 1531.94 | 14-MAY-15:10 | 25.92 | 17.84 | 0.101518E+09 | 70.35 | 20-MAY-22:30 | 17.75 | 11.80 |
| June | 0.202580E+10 | 2605.81 | 12-JUN-11:20 | 29.07 | 19.85 | 0.117023E+09 | 70.35 | 22-JUN-20:19 | 17.03 | 13.06 |
| July | 0.296884E+10 | 2571.93 | 21-JUL-11:00 | 29.40 | 21.64 | 0.127237E+09 | 70.36 | 01-JUL-00:30 | 29.40 | 21.64 |
| August | 0.238688E+10 | 2348.23 | 09-AUG-15:20 | 29.40 | 18.24 | 0.125096E+09 | 70.36 | 12-AUG-23:10 | 15.50 | 11.06 |
| September | 0.103661E+10 | 1814.55 | 16-SEP-13:30 | 27.20 | 19.64 | 0.107370E+09 | 70.28 | 17-SEP-03:00 | 23.30 | 18.82 |
| October | 0.236332E+09 | 501.50 | 11-OCT-16:07 | 21.70 | 14.52 | 83052989.12 | 68.09 | 22-OCT-21:00 | 18.30 | 13.76 |
| November | 33692808.75 | 341.32 | 01-NOV-16:03 | 9.40 | 6.76 | 75668915.73 | 48.27 | 04-NOV-20:10 | 14.82 | 11.32 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 4.95 | 3.07 | 77895344.62 | 42.51 | 07-DEC-22:00 | -7.8 | -8.5 |
| Annual Sum or Average | 0.990790E+10 | 0.112503E+10 | ||||||||
| Minimum of Months | 0.00 | 0.00 | -3.3 | -4.7 | 70357085.38 | 42.51 | -10.6 | -11.5 | ||
| Maximum of Months | 0.296884E+10 | 2605.81 | 29.40 | 21.64 | 0.127237E+09 | 70.36 | 29.40 | 21.64 |
Report: ZoneCoolingSummaryMonthly
For: T N1 APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | -1.0 | -1.6 | 77895344.59 | 42.51 | 30-JAN-22:00 | -10.6 | -11.5 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | -3.3 | -4.7 | 70357085.44 | 42.51 | 09-FEB-06:49 | -9.2 | -9.6 |
| March | 0.157720E+09 | 1034.05 | 15-MAR-16:30 | 25.00 | 15.96 | 81741674.87 | 70.34 | 16-MAR-01:39 | 18.33 | 13.53 |
| April | 0.326020E+09 | 588.52 | 09-APR-16:03 | 15.22 | 11.74 | 81075294.29 | 62.78 | 09-APR-20:10 | 9.32 | 8.45 |
| May | 0.788233E+09 | 1279.06 | 14-MAY-15:20 | 25.73 | 17.84 | 0.104745E+09 | 70.36 | 27-MAY-20:30 | 16.15 | 9.71 |
| June | 0.168574E+10 | 1928.88 | 12-JUN-16:08 | 27.57 | 19.99 | 0.118928E+09 | 70.37 | 04-JUN-23:40 | 27.57 | 19.99 |
| July | 0.242615E+10 | 1945.62 | 21-JUL-16:30 | 29.15 | 21.61 | 0.127911E+09 | 70.35 | 14-JUL-02:39 | 29.15 | 21.61 |
| August | 0.198595E+10 | 1888.34 | 09-AUG-16:02 | 29.40 | 18.45 | 0.126643E+09 | 70.36 | 31-AUG-20:10 | 14.32 | 11.86 |
| September | 0.942556E+09 | 1455.82 | 16-SEP-16:10 | 26.60 | 19.60 | 0.110613E+09 | 70.36 | 07-SEP-22:00 | 26.60 | 19.60 |
| October | 0.310373E+09 | 440.25 | 23-OCT-11:50 | 6.28 | 5.95 | 84745947.57 | 70.33 | 22-OCT-21:00 | 6.28 | 5.95 |
| November | 56999081.47 | 341.39 | 01-NOV-16:03 | 9.40 | 6.76 | 76029755.19 | 52.37 | 04-NOV-20:10 | 14.82 | 11.32 |
| December | 78709.75 | 39.80 | 01-DEC-13:00 | 13.90 | 12.22 | 77895344.65 | 42.51 | 07-DEC-22:00 | -7.8 | -8.5 |
| Annual Sum or Average | 0.867983E+10 | 0.113858E+10 | ||||||||
| Minimum of Months | 0.00 | 0.00 | -3.3 | -4.7 | 70357085.44 | 42.51 | -10.6 | -11.5 | ||
| Maximum of Months | 0.242615E+10 | 1945.62 | 29.40 | 21.61 | 0.127911E+09 | 70.37 | 29.15 | 21.61 |
Report: ZoneCoolingSummaryMonthly
For: T N2 APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | -1.0 | -1.6 | 77895344.59 | 42.51 | 30-JAN-22:00 | -10.6 | -11.5 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | -3.3 | -4.7 | 70357085.44 | 42.51 | 09-FEB-06:49 | -9.2 | -9.6 |
| March | 0.158249E+09 | 1036.49 | 15-MAR-16:20 | 25.00 | 15.96 | 81749139.36 | 70.35 | 16-MAR-01:39 | 18.33 | 13.53 |
| April | 0.326980E+09 | 586.70 | 09-APR-16:03 | 15.22 | 11.74 | 81100951.13 | 62.68 | 09-APR-20:10 | 9.32 | 8.45 |
| May | 0.790621E+09 | 1269.92 | 14-MAY-15:10 | 25.92 | 17.84 | 0.104766E+09 | 70.36 | 16-MAY-23:49 | 16.10 | 11.47 |
| June | 0.168659E+10 | 1919.83 | 12-JUN-16:10 | 27.57 | 19.99 | 0.118912E+09 | 70.36 | 04-JUN-23:40 | 27.57 | 19.99 |
| July | 0.242866E+10 | 1945.52 | 21-JUL-16:30 | 29.15 | 21.61 | 0.127899E+09 | 70.35 | 01-JUL-01:00 | 29.15 | 21.61 |
| August | 0.198771E+10 | 1877.56 | 09-AUG-16:04 | 29.40 | 18.45 | 0.126623E+09 | 70.35 | 24-AUG-01:49 | 16.70 | 14.00 |
| September | 0.946403E+09 | 1446.55 | 16-SEP-16:10 | 26.60 | 19.60 | 0.110661E+09 | 70.35 | 17-SEP-23:19 | 15.20 | 12.29 |
| October | 0.311135E+09 | 444.41 | 23-OCT-12:00 | 6.10 | 5.81 | 84744334.28 | 70.27 | 22-OCT-22:10 | 6.10 | 5.81 |
| November | 57118187.19 | 341.40 | 01-NOV-16:03 | 9.40 | 6.76 | 76031706.71 | 52.30 | 04-NOV-20:10 | 14.82 | 11.32 |
| December | 81385.32 | 40.17 | 01-DEC-13:00 | 13.90 | 12.22 | 77895344.65 | 42.51 | 07-DEC-22:00 | -7.8 | -8.5 |
| Annual Sum or Average | 0.869355E+10 | 0.113863E+10 | ||||||||
| Minimum of Months | 0.00 | 0.00 | -3.3 | -4.7 | 70357085.44 | 42.51 | -10.6 | -11.5 | ||
| Maximum of Months | 0.242866E+10 | 1945.52 | 29.40 | 21.61 | 0.127899E+09 | 70.36 | 29.15 | 21.61 |
Report: ZoneCoolingSummaryMonthly
For: T S1 APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 46130269.86 | 726.28 | 06-JAN-13:10 | -3.2 | -5.2 | 78362681.15 | 60.34 | 15-JAN-16:10 | 4.82 | 1.15 |
| February | 68488385.01 | 854.44 | 08-FEB-13:10 | -7.2 | -8.8 | 69671915.70 | 46.89 | 18-FEB-16:10 | 2.02 | -0.3 |
| March | 0.418209E+09 | 1956.27 | 15-MAR-13:50 | 25.92 | 15.99 | 79358169.06 | 70.31 | 16-MAR-04:49 | 15.33 | 12.06 |
| April | 0.615073E+09 | 1338.15 | 22-APR-14:10 | 15.60 | 7.15 | 85321357.17 | 70.36 | 21-APR-18:00 | 15.60 | 7.15 |
| May | 0.106017E+10 | 1896.42 | 14-MAY-14:10 | 25.18 | 18.10 | 0.105126E+09 | 70.36 | 08-MAY-19:49 | 25.18 | 18.10 |
| June | 0.189824E+10 | 2377.41 | 12-JUN-13:30 | 30.00 | 19.98 | 0.114928E+09 | 70.37 | 13-JUN-18:49 | 12.88 | 7.99 |
| July | 0.273345E+10 | 2546.35 | 21-JUL-13:30 | 31.15 | 21.91 | 0.128281E+09 | 70.35 | 13-JUL-00:40 | 31.15 | 21.91 |
| August | 0.248036E+10 | 2613.73 | 09-AUG-13:50 | 29.32 | 18.11 | 0.122195E+09 | 70.36 | 20-AUG-03:30 | 15.00 | 13.07 |
| September | 0.161552E+10 | 2684.37 | 21-SEP-14:10 | 25.68 | 16.62 | 0.113563E+09 | 70.35 | 13-SEP-01:00 | 25.68 | 16.62 |
| October | 0.690566E+09 | 1959.32 | 11-OCT-14:30 | 22.20 | 14.37 | 90985779.61 | 70.36 | 10-OCT-20:49 | 22.20 | 14.37 |
| November | 0.236782E+09 | 613.65 | 03-NOV-14:30 | 9.70 | 5.23 | 78167925.55 | 68.15 | 25-NOV-16:10 | 11.93 | 5.11 |
| December | 48373181.03 | 637.50 | 04-DEC-12:30 | -0.3 | -3.0 | 78384850.15 | 55.15 | 16-DEC-16:10 | 4.22 | 2.19 |
| Annual Sum or Average | 0.119114E+11 | 0.114435E+10 | ||||||||
| Minimum of Months | 46130269.86 | 613.65 | -7.2 | -8.8 | 69671915.70 | 46.89 | 2.02 | -0.3 | ||
| Maximum of Months | 0.273345E+10 | 2684.37 | 31.15 | 21.91 | 0.128281E+09 | 70.37 | 31.15 | 21.91 |
Report: ZoneCoolingSummaryMonthly
For: T S2 APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 46474196.34 | 726.48 | 06-JAN-13:10 | -3.2 | -5.2 | 78359579.42 | 60.06 | 15-JAN-16:10 | 4.82 | 1.15 |
| February | 68935758.19 | 855.49 | 08-FEB-13:10 | -7.2 | -8.8 | 69668734.05 | 46.56 | 18-FEB-16:10 | 2.02 | -0.3 |
| March | 0.418606E+09 | 1964.35 | 15-MAR-13:40 | 25.73 | 15.91 | 79336520.88 | 70.33 | 12-MAR-16:00 | 25.73 | 15.91 |
| April | 0.618629E+09 | 1361.64 | 22-APR-14:10 | 15.60 | 7.15 | 85294804.30 | 70.37 | 09-APR-19:49 | 15.60 | 7.15 |
| May | 0.106509E+10 | 1894.11 | 14-MAY-14:10 | 25.18 | 18.10 | 0.105076E+09 | 70.37 | 14-MAY-00:20 | 25.18 | 18.10 |
| June | 0.190016E+10 | 2388.61 | 12-JUN-13:30 | 30.00 | 19.98 | 0.114883E+09 | 70.36 | 13-JUN-18:10 | 13.22 | 8.26 |
| July | 0.273632E+10 | 2556.51 | 21-JUL-13:30 | 31.15 | 21.91 | 0.128270E+09 | 70.36 | 13-JUL-00:40 | 31.15 | 21.91 |
| August | 0.248224E+10 | 2620.36 | 09-AUG-13:50 | 29.32 | 18.11 | 0.122175E+09 | 70.36 | 05-AUG-04:10 | 29.32 | 18.11 |
| September | 0.162021E+10 | 2691.81 | 21-SEP-14:10 | 25.68 | 16.62 | 0.113553E+09 | 70.37 | 30-SEP-19:10 | 15.50 | 11.72 |
| October | 0.693836E+09 | 1966.63 | 11-OCT-14:30 | 22.20 | 14.37 | 90999590.60 | 70.36 | 30-OCT-18:40 | 11.30 | 6.96 |
| November | 0.237108E+09 | 630.57 | 03-NOV-14:30 | 9.70 | 5.23 | 78171926.22 | 68.08 | 25-NOV-16:10 | 11.93 | 5.11 |
| December | 48486827.43 | 640.64 | 04-DEC-12:40 | -0.4 | -3.1 | 78385286.21 | 55.01 | 16-DEC-16:10 | 4.22 | 2.19 |
| Annual Sum or Average | 0.119361E+11 | 0.114417E+10 | ||||||||
| Minimum of Months | 46474196.34 | 630.57 | -7.2 | -8.8 | 69668734.05 | 46.56 | 2.02 | -0.3 | ||
| Maximum of Months | 0.273632E+10 | 2691.81 | 31.15 | 21.91 | 0.128270E+09 | 70.37 | 31.15 | 21.91 |
Report: ZoneCoolingSummaryMonthly
For: T CORRIDOR
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | -1.0 | -1.6 | 88206054.54 | 64.95 | 15-JAN-18:10 | 0.92 | -0.7 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | -3.3 | -4.7 | 79249176.03 | 72.33 | 22-FEB-21:10 | 9.13 | 5.01 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | -4.9 | -6.9 | 0.124673E+09 | 150.62 | 15-MAR-20:10 | 20.73 | 14.37 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 4.10 | 3.72 | 0.148714E+09 | 128.94 | 09-APR-20:10 | 9.32 | 8.45 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 6.67 | 6.11 | 0.210168E+09 | 152.90 | 31-MAY-20:10 | 18.22 | 12.84 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 | 14.04 | 0.251409E+09 | 169.92 | 27-JUN-20:10 | 23.62 | 21.83 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 | 13.50 | 0.280913E+09 | 173.13 | 20-JUL-20:10 | 26.52 | 23.62 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 | 16.93 | 0.271630E+09 | 170.95 | 10-AUG-20:10 | 25.68 | 18.92 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 | 12.90 | 0.226179E+09 | 161.70 | 16-SEP-20:10 | 23.90 | 18.52 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 14.42 | 12.28 | 0.158060E+09 | 135.60 | 11-OCT-20:10 | 16.02 | 10.93 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 6.53 | 4.43 | 0.118036E+09 | 98.79 | 26-NOV-21:10 | 14.32 | 8.85 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 4.95 | 3.07 | 90198642.35 | 64.75 | 16-DEC-21:10 | 2.70 | 1.17 |
| Annual Sum or Average | 0.00 | 0.204744E+10 | ||||||||
| Minimum of Months | 0.00 | 0.00 | -4.9 | -6.9 | 79249176.03 | 64.75 | 0.92 | -0.7 | ||
| Maximum of Months | 0.00 | 0.00 | 18.85 | 16.93 | 0.280913E+09 | 173.13 | 26.52 | 23.62 |
Report: ZoneCoolingSummaryMonthly
For: G CORRIDOR
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | -1.0 | -1.6 | 44377768.40 | 56.93 | 18-JAN-06:10 | 2.80 | 1.63 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | -3.3 | -4.7 | 37461030.37 | 53.26 | 23-FEB-06:10 | 2.30 | 1.81 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | -4.9 | -6.9 | 72769837.10 | 104.99 | 15-MAR-17:10 | 24.82 | 15.90 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 4.10 | 3.72 | 94357630.77 | 88.01 | 08-APR-21:49 | 14.18 | 12.23 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 6.67 | 6.11 | 0.152519E+09 | 119.64 | 31-MAY-21:49 | 17.63 | 13.29 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 | 14.04 | 0.231336E+09 | 160.30 | 27-JUN-21:49 | 21.78 | 20.28 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 | 13.50 | 0.277165E+09 | 174.49 | 20-JUL-20:10 | 26.52 | 23.62 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 | 16.93 | 0.270236E+09 | 173.62 | 09-AUG-17:10 | 29.32 | 18.15 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 | 12.90 | 0.225285E+09 | 162.23 | 16-SEP-21:49 | 23.90 | 18.77 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 14.42 | 12.28 | 0.143680E+09 | 122.72 | 12-OCT-21:49 | 14.60 | 13.81 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 6.53 | 4.43 | 93303057.60 | 93.11 | 06-NOV-06:10 | 8.90 | 6.87 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 4.95 | 3.07 | 51322017.99 | 64.64 | 01-DEC-06:10 | 10.10 | 8.62 |
| Annual Sum or Average | 0.00 | 0.169381E+10 | ||||||||
| Minimum of Months | 0.00 | 0.00 | -4.9 | -6.9 | 37461030.37 | 53.26 | 2.30 | 1.63 | ||
| Maximum of Months | 0.00 | 0.00 | 18.85 | 16.93 | 0.277165E+09 | 174.49 | 29.32 | 23.62 |
Report: ZoneCoolingSummaryMonthly
For: M CORRIDOR
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | -1.0 | -1.6 | 0.133853E+09 | 84.04 | 16-JAN-22:10 | 2.80 | 0.63 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | -3.3 | -4.7 | 0.120497E+09 | 82.06 | 18-FEB-21:10 | -1.2 | -2.2 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | -4.9 | -6.9 | 0.165102E+09 | 139.54 | 15-MAR-20:40 | 19.63 | 14.02 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 4.10 | 3.72 | 0.182572E+09 | 135.55 | 09-APR-20:10 | 9.32 | 8.45 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 6.67 | 6.11 | 0.252209E+09 | 153.71 | 31-MAY-20:10 | 18.22 | 12.84 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 | 14.04 | 0.267796E+09 | 160.58 | 27-JUN-20:10 | 23.62 | 21.83 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 | 13.50 | 0.284178E+09 | 162.18 | 18-JUL-20:10 | 23.80 | 19.04 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 | 16.93 | 0.280789E+09 | 161.98 | 10-AUG-20:10 | 25.68 | 18.92 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 | 12.90 | 0.258423E+09 | 156.74 | 16-SEP-20:10 | 23.90 | 18.52 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 14.42 | 12.28 | 0.202485E+09 | 138.47 | 05-OCT-20:10 | 16.10 | 12.53 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 6.53 | 4.43 | 0.156874E+09 | 108.17 | 05-NOV-20:10 | 10.00 | 9.14 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 4.95 | 3.07 | 0.133972E+09 | 83.05 | 16-DEC-21:10 | 2.70 | 1.17 |
| Annual Sum or Average | 0.00 | 0.243875E+10 | ||||||||
| Minimum of Months | 0.00 | 0.00 | -4.9 | -6.9 | 0.120497E+09 | 82.06 | -1.2 | -2.2 | ||
| Maximum of Months | 0.00 | 0.00 | 18.85 | 16.93 | 0.284178E+09 | 162.18 | 25.68 | 21.83 |
Report: ZoneHeatingSummaryMonthly
For: G SW APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.238634E+10 | 1872.91 | 24-JAN-06:00 | -12.2 |
| February | 0.238888E+10 | 2294.08 | 07-FEB-08:12 | -15.6 |
| March | 0.112581E+10 | 1345.37 | 05-MAR-01:00 | -7.2 |
| April | 0.477631E+09 | 1213.41 | 16-APR-07:00 | -3.9 |
| May | 20814374.30 | 846.79 | 13-MAY-07:02 | 11.57 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 |
| October | 11580679.14 | 363.39 | 30-OCT-05:00 | 0.00 |
| November | 0.340527E+09 | 653.64 | 24-NOV-04:00 | -3.3 |
| December | 0.208098E+10 | 1735.91 | 26-DEC-08:00 | -12.8 |
| Annual Sum or Average | 0.883257E+10 | |||
| Minimum of Months | 0.00 | 0.00 | -15.6 | |
| Maximum of Months | 0.238888E+10 | 2294.08 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: G NW APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.299289E+10 | 2047.81 | 12-JAN-09:00 | -11.1 |
| February | 0.292352E+10 | 2465.00 | 07-FEB-08:12 | -15.6 |
| March | 0.184093E+10 | 1768.65 | 06-MAR-09:00 | -8.3 |
| April | 0.779907E+09 | 1264.03 | 16-APR-07:00 | -3.9 |
| May | 54577766.85 | 945.21 | 22-MAY-06:01 | 10.18 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 |
| October | 68360032.76 | 461.61 | 30-OCT-05:00 | 0.00 |
| November | 0.605489E+09 | 726.41 | 25-NOV-05:00 | -1.7 |
| December | 0.255063E+10 | 1831.76 | 26-DEC-08:00 | -12.8 |
| Annual Sum or Average | 0.118163E+11 | |||
| Minimum of Months | 0.00 | 0.00 | -15.6 | |
| Maximum of Months | 0.299289E+10 | 2465.00 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: OFFICE
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.132954E+10 | 9717.85 | 17-JAN-07:01 | 7.12 |
| February | 0.135407E+10 | 9668.20 | 01-FEB-07:01 | 5.92 |
| March | 0.615362E+09 | 9532.44 | 13-MAR-07:01 | 6.70 |
| April | 0.183112E+09 | 9493.69 | 04-APR-07:01 | 6.52 |
| May | 0.126337E+09 | 6770.00 | 01-MAY-07:01 | 6.05 |
| June | 0.214684E+09 | 506.79 | 12-JUN-07:05 | 24.08 |
| July | 0.315967E+09 | 560.25 | 19-JUL-16:12 | 29.43 |
| August | 0.208911E+09 | 547.34 | 18-AUG-16:12 | 29.40 |
| September | 90961468.67 | 402.79 | 21-SEP-16:12 | 25.93 |
| October | 30831525.42 | 9346.00 | 30-OCT-07:01 | 0.87 |
| November | 0.140082E+09 | 9534.77 | 14-NOV-08:61 | 7.57 |
| December | 0.109177E+10 | 9503.50 | 13-DEC-07:01 | 1.70 |
| Annual Sum or Average | 0.570162E+10 | |||
| Minimum of Months | 30831525.42 | 402.79 | 0.87 | |
| Maximum of Months | 0.135407E+10 | 9717.85 | 29.43 |
Report: ZoneHeatingSummaryMonthly
For: G NE APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.294460E+10 | 1930.55 | 12-JAN-08:30 | -10.2 |
| February | 0.288626E+10 | 2375.19 | 07-FEB-08:10 | -15.6 |
| March | 0.184607E+10 | 1642.05 | 07-MAR-04:55 | -13.3 |
| April | 0.744765E+09 | 1217.54 | 16-APR-04:00 | -2.2 |
| May | 57759254.05 | 332.68 | 03-MAY-04:00 | 6.70 |
| June | 21505.75 | 15.55 | 01-JUN-14:30 | 23.85 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 |
| October | 61759106.99 | 480.75 | 30-OCT-05:00 | 0.00 |
| November | 0.594984E+09 | 767.19 | 25-NOV-05:00 | -1.7 |
| December | 0.254198E+10 | 1817.74 | 26-DEC-08:00 | -12.8 |
| Annual Sum or Average | 0.116782E+11 | |||
| Minimum of Months | 0.00 | 0.00 | -15.6 | |
| Maximum of Months | 0.294460E+10 | 2375.19 | 23.85 |
Report: ZoneHeatingSummaryMonthly
For: G N1 APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.156739E+10 | 1148.65 | 12-JAN-09:00 | -11.1 |
| February | 0.158532E+10 | 1503.55 | 07-FEB-08:12 | -15.6 |
| March | 0.933231E+09 | 1070.64 | 07-MAR-08:20 | -10.5 |
| April | 0.252470E+09 | 626.25 | 16-APR-07:10 | -3.7 |
| May | 4366183.37 | 120.04 | 10-MAY-14:00 | 26.10 |
| June | 2237.95 | 3.73 | 01-JUN-14:10 | 23.48 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 |
| October | 2901893.02 | 116.45 | 30-OCT-05:00 | 0.00 |
| November | 0.105033E+09 | 340.14 | 25-NOV-05:00 | -1.7 |
| December | 0.125496E+10 | 1017.73 | 26-DEC-08:04 | -12.8 |
| Annual Sum or Average | 0.570566E+10 | |||
| Minimum of Months | 0.00 | 0.00 | -15.6 | |
| Maximum of Months | 0.158532E+10 | 1503.55 | 26.10 |
Report: ZoneHeatingSummaryMonthly
For: G N2 APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.156553E+10 | 1146.68 | 12-JAN-09:00 | -11.1 |
| February | 0.158392E+10 | 1503.07 | 07-FEB-08:12 | -15.6 |
| March | 0.933524E+09 | 1066.70 | 07-MAR-08:20 | -10.5 |
| April | 0.251665E+09 | 624.39 | 16-APR-07:10 | -3.7 |
| May | 4464904.18 | 119.88 | 10-MAY-14:00 | 26.10 |
| June | 2324.72 | 3.87 | 01-JUN-14:10 | 23.48 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 |
| October | 2882722.63 | 116.88 | 30-OCT-05:00 | 0.00 |
| November | 0.105039E+09 | 342.27 | 25-NOV-05:00 | -1.7 |
| December | 0.125467E+10 | 1017.52 | 26-DEC-08:04 | -12.8 |
| Annual Sum or Average | 0.570169E+10 | |||
| Minimum of Months | 0.00 | 0.00 | -15.6 | |
| Maximum of Months | 0.158392E+10 | 1503.07 | 26.10 |
Report: ZoneHeatingSummaryMonthly
For: G S1 APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.100222E+10 | 1011.62 | 24-JAN-05:00 | -11.7 |
| February | 0.108253E+10 | 1334.31 | 07-FEB-08:12 | -15.6 |
| March | 0.321441E+09 | 629.06 | 05-MAR-01:10 | -7.4 |
| April | 0.110449E+09 | 567.45 | 16-APR-07:00 | -3.9 |
| May | 996779.19 | 88.16 | 10-MAY-14:00 | 26.10 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 14.42 |
| November | 29671933.06 | 374.29 | 10-NOV-11:00 | 15.60 |
| December | 0.832570E+09 | 924.97 | 26-DEC-08:03 | -12.8 |
| Annual Sum or Average | 0.337988E+10 | |||
| Minimum of Months | 0.00 | 0.00 | -15.6 | |
| Maximum of Months | 0.108253E+10 | 1334.31 | 26.10 |
Report: ZoneHeatingSummaryMonthly
For: G S2 APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.128404E+10 | 1154.18 | 24-JAN-05:00 | -11.7 |
| February | 0.133100E+10 | 1473.82 | 07-FEB-08:10 | -15.6 |
| March | 0.452347E+09 | 772.90 | 05-MAR-01:10 | -7.4 |
| April | 0.155530E+09 | 671.41 | 16-APR-07:09 | -3.7 |
| May | 660462.84 | 85.62 | 10-MAY-14:00 | 26.10 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 14.42 |
| November | 49908267.55 | 384.27 | 10-NOV-11:00 | 15.60 |
| December | 0.106158E+10 | 1091.08 | 26-DEC-08:03 | -12.8 |
| Annual Sum or Average | 0.433506E+10 | |||
| Minimum of Months | 0.00 | 0.00 | -15.6 | |
| Maximum of Months | 0.133100E+10 | 1473.82 | 26.10 |
Report: ZoneHeatingSummaryMonthly
For: M SW APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.172722E+10 | 1914.33 | 24-JAN-06:00 | -12.2 |
| February | 0.171107E+10 | 2175.07 | 06-FEB-10:00 | -15.0 |
| March | 0.403772E+09 | 1059.91 | 05-MAR-01:00 | -7.2 |
| April | 0.109775E+09 | 937.33 | 16-APR-04:00 | -2.2 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 6.67 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 |
| October | 14230616.57 | 469.90 | 30-OCT-05:00 | 0.00 |
| November | 0.324196E+09 | 658.21 | 30-NOV-15:00 | 3.90 |
| December | 0.178981E+10 | 1842.73 | 26-DEC-04:00 | -11.7 |
| Annual Sum or Average | 0.608008E+10 | |||
| Minimum of Months | 0.00 | 0.00 | -15.0 | |
| Maximum of Months | 0.178981E+10 | 2175.07 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: M NW APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.230381E+10 | 2069.48 | 12-JAN-09:00 | -11.1 |
| February | 0.218789E+10 | 2269.26 | 06-FEB-10:00 | -15.0 |
| March | 0.851931E+09 | 1301.82 | 06-MAR-09:00 | -8.3 |
| April | 0.178334E+09 | 966.73 | 16-APR-04:00 | -2.2 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 6.67 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 |
| October | 67079220.64 | 554.56 | 30-OCT-05:00 | 0.00 |
| November | 0.528431E+09 | 714.57 | 29-NOV-04:00 | 1.10 |
| December | 0.222888E+10 | 1938.89 | 26-DEC-04:00 | -11.7 |
| Annual Sum or Average | 0.834636E+10 | |||
| Minimum of Months | 0.00 | 0.00 | -15.0 | |
| Maximum of Months | 0.230381E+10 | 2269.26 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: M SE APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.167639E+10 | 1888.37 | 24-JAN-06:00 | -12.2 |
| February | 0.167496E+10 | 2134.22 | 06-FEB-10:00 | -15.0 |
| March | 0.393630E+09 | 1056.65 | 05-MAR-01:00 | -7.2 |
| April | 0.100535E+09 | 921.75 | 16-APR-04:00 | -2.2 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 6.67 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 |
| October | 14161977.84 | 491.33 | 30-OCT-05:00 | 0.00 |
| November | 0.320256E+09 | 643.06 | 30-NOV-15:00 | 3.90 |
| December | 0.177813E+10 | 1833.11 | 26-DEC-04:00 | -11.7 |
| Annual Sum or Average | 0.595806E+10 | |||
| Minimum of Months | 0.00 | 0.00 | -15.0 | |
| Maximum of Months | 0.177813E+10 | 2134.22 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: M NE APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.225202E+10 | 1953.02 | 24-JAN-06:00 | -12.2 |
| February | 0.214759E+10 | 2229.97 | 06-FEB-10:00 | -15.0 |
| March | 0.844260E+09 | 1294.17 | 05-MAR-01:00 | -7.2 |
| April | 0.161469E+09 | 950.85 | 16-APR-04:00 | -2.2 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 6.67 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 |
| October | 62507369.30 | 578.15 | 30-OCT-05:00 | 0.00 |
| November | 0.515451E+09 | 715.07 | 25-NOV-05:00 | -1.7 |
| December | 0.221898E+10 | 1929.64 | 26-DEC-04:00 | -11.7 |
| Annual Sum or Average | 0.820228E+10 | |||
| Minimum of Months | 0.00 | 0.00 | -15.0 | |
| Maximum of Months | 0.225202E+10 | 2229.97 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: M N1 APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.854448E+09 | 1012.14 | 12-JAN-09:00 | -11.1 |
| February | 0.848029E+09 | 1157.93 | 06-FEB-10:00 | -15.0 |
| March | 0.270402E+09 | 589.52 | 05-MAR-01:00 | -7.2 |
| April | 16470776.63 | 384.72 | 16-APR-04:00 | -2.2 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 6.67 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 |
| October | 1267437.42 | 131.72 | 30-OCT-05:00 | 0.00 |
| November | 44316169.37 | 602.51 | 10-NOV-11:00 | 15.60 |
| December | 0.807955E+09 | 948.87 | 26-DEC-04:00 | -11.7 |
| Annual Sum or Average | 0.284289E+10 | |||
| Minimum of Months | 0.00 | 0.00 | -15.0 | |
| Maximum of Months | 0.854448E+09 | 1157.93 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: M N2 APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.852479E+09 | 1010.26 | 12-JAN-09:00 | -11.1 |
| February | 0.846516E+09 | 1156.93 | 06-FEB-10:00 | -15.0 |
| March | 0.270082E+09 | 588.94 | 05-MAR-01:00 | -7.2 |
| April | 16339038.65 | 383.83 | 16-APR-04:00 | -2.2 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 6.67 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 |
| October | 1294859.33 | 132.88 | 30-OCT-05:00 | 0.00 |
| November | 44302834.26 | 600.37 | 10-NOV-11:00 | 15.60 |
| December | 0.807686E+09 | 948.63 | 26-DEC-04:00 | -11.7 |
| Annual Sum or Average | 0.283870E+10 | |||
| Minimum of Months | 0.00 | 0.00 | -15.0 | |
| Maximum of Months | 0.852479E+09 | 1156.93 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: M S1 APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.448656E+09 | 901.74 | 24-JAN-06:00 | -12.2 |
| February | 0.513371E+09 | 1041.82 | 06-FEB-10:00 | -15.0 |
| March | 48625890.43 | 399.65 | 05-MAR-01:10 | -7.4 |
| April | 7838874.65 | 347.84 | 16-APR-04:00 | -2.2 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 6.67 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 14.42 |
| November | 13576652.68 | 314.29 | 10-NOV-11:00 | 15.60 |
| December | 0.494315E+09 | 865.61 | 26-DEC-04:00 | -11.7 |
| Annual Sum or Average | 0.152638E+10 | |||
| Minimum of Months | 0.00 | 0.00 | -15.0 | |
| Maximum of Months | 0.513371E+09 | 1041.82 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: M S2 APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.447280E+09 | 900.14 | 24-JAN-06:00 | -12.2 |
| February | 0.512745E+09 | 1040.68 | 06-FEB-10:00 | -15.0 |
| March | 48999182.47 | 399.21 | 05-MAR-01:10 | -7.4 |
| April | 7786123.60 | 346.97 | 16-APR-04:00 | -2.2 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 6.67 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 14.42 |
| November | 13621023.43 | 321.20 | 10-NOV-11:00 | 15.60 |
| December | 0.494112E+09 | 865.41 | 26-DEC-04:00 | -11.7 |
| Annual Sum or Average | 0.152454E+10 | |||
| Minimum of Months | 0.00 | 0.00 | -15.0 | |
| Maximum of Months | 0.512745E+09 | 1040.68 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: T SW APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.403959E+10 | 3489.98 | 24-JAN-06:00 | -12.2 |
| February | 0.382646E+10 | 3797.75 | 06-FEB-10:00 | -15.0 |
| March | 0.175914E+10 | 2381.00 | 05-MAR-01:00 | -7.2 |
| April | 0.755938E+09 | 2011.95 | 16-APR-04:00 | -2.2 |
| May | 45922411.23 | 924.10 | 22-MAY-06:01 | 10.18 |
| June | 4394066.81 | 360.44 | 14-JUN-05:00 | 6.70 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 |
| September | 27297441.21 | 541.40 | 30-SEP-06:00 | 7.20 |
| October | 0.546682E+09 | 1532.23 | 30-OCT-05:00 | 0.00 |
| November | 0.155414E+10 | 1687.02 | 29-NOV-04:00 | 1.10 |
| December | 0.404634E+10 | 3494.47 | 26-DEC-04:00 | -11.7 |
| Annual Sum or Average | 0.166059E+11 | |||
| Minimum of Months | 0.00 | 0.00 | -15.0 | |
| Maximum of Months | 0.404634E+10 | 3797.75 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: T NW APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.467747E+10 | 3598.48 | 12-JAN-09:00 | -11.1 |
| February | 0.435075E+10 | 3812.53 | 06-FEB-10:00 | -15.0 |
| March | 0.234028E+10 | 2517.36 | 05-MAR-01:00 | -7.2 |
| April | 0.909463E+09 | 2036.55 | 16-APR-04:00 | -2.2 |
| May | 54509147.80 | 706.70 | 20-MAY-07:01 | 10.28 |
| June | 3121619.35 | 341.43 | 14-JUN-04:40 | 6.70 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 |
| September | 34088262.26 | 597.20 | 30-SEP-06:00 | 7.20 |
| October | 0.766124E+09 | 1580.67 | 30-OCT-05:00 | 0.00 |
| November | 0.188614E+10 | 1703.13 | 29-NOV-04:00 | 1.10 |
| December | 0.452674E+10 | 3521.47 | 26-DEC-04:00 | -11.7 |
| Annual Sum or Average | 0.195487E+11 | |||
| Minimum of Months | 0.00 | 0.00 | -15.0 | |
| Maximum of Months | 0.467747E+10 | 3812.53 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: T SE APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.397883E+10 | 3470.75 | 24-JAN-06:00 | -12.2 |
| February | 0.377720E+10 | 3746.67 | 06-FEB-10:00 | -15.0 |
| March | 0.174772E+10 | 2381.48 | 05-MAR-01:00 | -7.2 |
| April | 0.733863E+09 | 1990.96 | 16-APR-04:00 | -2.2 |
| May | 45948709.46 | 521.11 | 07-MAY-05:00 | 3.90 |
| June | 4759438.77 | 414.99 | 14-JUN-04:40 | 6.70 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 |
| September | 27847619.67 | 581.86 | 30-SEP-06:00 | 7.20 |
| October | 0.530825E+09 | 1556.89 | 30-OCT-05:00 | 0.00 |
| November | 0.154002E+10 | 1678.71 | 29-NOV-04:00 | 1.10 |
| December | 0.403208E+10 | 3480.32 | 26-DEC-04:00 | -11.7 |
| Annual Sum or Average | 0.164191E+11 | |||
| Minimum of Months | 0.00 | 0.00 | -15.0 | |
| Maximum of Months | 0.403208E+10 | 3746.67 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: T NE APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.461696E+10 | 3493.70 | 24-JAN-06:00 | -12.2 |
| February | 0.430132E+10 | 3761.88 | 06-FEB-10:00 | -15.0 |
| March | 0.233495E+10 | 2570.42 | 07-MAR-04:55 | -13.3 |
| April | 0.869822E+09 | 2015.22 | 16-APR-04:00 | -2.2 |
| May | 57502801.06 | 602.93 | 07-MAY-05:00 | 3.90 |
| June | 4511086.86 | 416.38 | 14-JUN-04:40 | 6.70 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 |
| September | 33963057.40 | 633.17 | 30-SEP-06:00 | 7.20 |
| October | 0.726176E+09 | 1605.13 | 30-OCT-05:00 | 0.00 |
| November | 0.186511E+10 | 1694.54 | 29-NOV-04:00 | 1.10 |
| December | 0.451297E+10 | 3506.58 | 26-DEC-04:00 | -11.7 |
| Annual Sum or Average | 0.193233E+11 | |||
| Minimum of Months | 0.00 | 0.00 | -15.0 | |
| Maximum of Months | 0.461696E+10 | 3761.88 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: T N1 APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.285350E+10 | 2262.33 | 24-JAN-06:00 | -12.2 |
| February | 0.265400E+10 | 2442.94 | 07-FEB-08:10 | -15.6 |
| March | 0.137509E+10 | 1712.54 | 07-MAR-04:55 | -13.3 |
| April | 0.407516E+09 | 1200.39 | 16-APR-04:00 | -2.2 |
| May | 3602699.36 | 210.51 | 07-MAY-05:00 | 3.90 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 |
| September | 6902593.91 | 244.75 | 30-SEP-05:00 | 7.20 |
| October | 0.322176E+09 | 967.61 | 30-OCT-05:00 | 0.00 |
| November | 0.950355E+09 | 1048.33 | 24-NOV-04:00 | -3.3 |
| December | 0.272552E+10 | 2261.13 | 26-DEC-04:00 | -11.7 |
| Annual Sum or Average | 0.112987E+11 | |||
| Minimum of Months | 0.00 | 0.00 | -15.6 | |
| Maximum of Months | 0.285350E+10 | 2442.94 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: T N2 APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.285131E+10 | 2261.52 | 24-JAN-06:00 | -12.2 |
| February | 0.265240E+10 | 2441.20 | 07-FEB-08:10 | -15.6 |
| March | 0.137595E+10 | 1715.96 | 07-MAR-04:55 | -13.3 |
| April | 0.407190E+09 | 1199.07 | 16-APR-04:00 | -2.2 |
| May | 4021231.04 | 214.04 | 07-MAY-05:00 | 3.90 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 |
| September | 7039976.41 | 249.35 | 30-SEP-05:00 | 7.20 |
| October | 0.321613E+09 | 969.04 | 30-OCT-05:00 | 0.00 |
| November | 0.949702E+09 | 1050.23 | 25-NOV-05:00 | -1.7 |
| December | 0.272514E+10 | 2262.01 | 26-DEC-04:00 | -11.7 |
| Annual Sum or Average | 0.112944E+11 | |||
| Minimum of Months | 0.00 | 0.00 | -15.6 | |
| Maximum of Months | 0.285131E+10 | 2441.20 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: T S1 APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.224742E+10 | 2237.59 | 24-JAN-06:00 | -12.2 |
| February | 0.216645E+10 | 2405.10 | 07-FEB-05:00 | -15.6 |
| March | 0.879745E+09 | 1509.98 | 07-MAR-04:55 | -13.3 |
| April | 0.303669E+09 | 1174.21 | 16-APR-04:00 | -2.2 |
| May | 1105923.66 | 87.11 | 13-MAY-07:02 | 11.57 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 |
| September | 3410709.18 | 184.15 | 30-SEP-06:00 | 7.20 |
| October | 0.199379E+09 | 913.24 | 30-OCT-05:00 | 0.00 |
| November | 0.704369E+09 | 1024.54 | 24-NOV-04:00 | -3.3 |
| December | 0.227664E+10 | 2230.55 | 26-DEC-04:00 | -11.7 |
| Annual Sum or Average | 0.878220E+10 | |||
| Minimum of Months | 0.00 | 0.00 | -15.6 | |
| Maximum of Months | 0.227664E+10 | 2405.10 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: T S2 APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.224551E+10 | 2236.71 | 24-JAN-06:00 | -12.2 |
| February | 0.216536E+10 | 2406.08 | 07-FEB-05:00 | -15.6 |
| March | 0.881262E+09 | 1513.67 | 07-MAR-04:55 | -13.3 |
| April | 0.304325E+09 | 1172.78 | 16-APR-04:00 | -2.2 |
| May | 1369767.40 | 101.88 | 13-MAY-07:02 | 11.57 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 |
| September | 3546373.67 | 188.31 | 30-SEP-06:00 | 7.20 |
| October | 0.199243E+09 | 915.92 | 30-OCT-05:00 | 0.00 |
| November | 0.704318E+09 | 1025.53 | 24-NOV-04:00 | -3.3 |
| December | 0.227646E+10 | 2231.39 | 26-DEC-04:00 | -11.7 |
| Annual Sum or Average | 0.878140E+10 | |||
| Minimum of Months | 0.00 | 0.00 | -15.6 | |
| Maximum of Months | 0.227646E+10 | 2406.08 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: T CORRIDOR
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | -1.0 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | -3.3 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | -4.9 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 4.10 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 6.67 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 14.42 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 6.53 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 4.95 |
| Annual Sum or Average | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | -4.9 | |
| Maximum of Months | 0.00 | 0.00 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: G CORRIDOR
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | -1.0 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | -3.3 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | -4.9 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 4.10 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 6.67 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 14.42 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 6.53 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 4.95 |
| Annual Sum or Average | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | -4.9 | |
| Maximum of Months | 0.00 | 0.00 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: M CORRIDOR
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | -1.0 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | -3.3 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | -4.9 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 4.10 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 6.67 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 14.42 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 6.53 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 4.95 |
| Annual Sum or Average | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | -4.9 | |
| Maximum of Months | 0.00 | 0.00 | 18.85 |
Report: ZoneElectricSummaryMonthly
For: G SW APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: G NW APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: OFFICE
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.609777E+09 | 582.92 | 03-JAN-08:09 | 0.787690E+09 | 588.62 | 03-JAN-08:09 |
| February | 0.564682E+09 | 582.92 | 01-FEB-08:09 | 0.723971E+09 | 588.62 | 01-FEB-08:09 |
| March | 0.654405E+09 | 582.92 | 01-MAR-08:09 | 0.827804E+09 | 588.62 | 01-MAR-08:09 |
| April | 0.599704E+09 | 582.92 | 03-APR-07:10 | 0.770907E+09 | 588.62 | 03-APR-07:10 |
| May | 0.639529E+09 | 582.92 | 01-MAY-07:10 | 0.814432E+09 | 588.62 | 01-MAY-07:10 |
| June | 0.629456E+09 | 582.92 | 01-JUN-07:10 | 0.797650E+09 | 588.62 | 01-JUN-07:10 |
| July | 0.609777E+09 | 582.92 | 03-JUL-07:10 | 0.787690E+09 | 588.62 | 03-JUL-07:10 |
| August | 0.654405E+09 | 582.92 | 01-AUG-07:10 | 0.827804E+09 | 588.62 | 01-AUG-07:10 |
| September | 0.599704E+09 | 582.92 | 01-SEP-07:10 | 0.770907E+09 | 588.62 | 01-SEP-07:10 |
| October | 0.624653E+09 | 582.92 | 02-OCT-07:10 | 0.801061E+09 | 588.62 | 02-OCT-07:10 |
| November | 0.599704E+09 | 582.92 | 01-NOV-07:10 | 0.770907E+09 | 588.62 | 01-NOV-07:10 |
| December | 0.609777E+09 | 582.92 | 01-DEC-08:09 | 0.787690E+09 | 588.62 | 01-DEC-08:09 |
| Annual Sum or Average | 0.739557E+10 | 0.946851E+10 | ||||
| Minimum of Months | 0.564682E+09 | 582.92 | 0.723971E+09 | 588.62 | ||
| Maximum of Months | 0.654405E+09 | 582.92 | 0.827804E+09 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: G NE APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: G N1 APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: G N2 APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: G S1 APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: G S2 APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: M SW APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: M NW APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: M SE APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: M NE APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: M N1 APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: M N2 APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: M S1 APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: M S2 APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: T SW APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: T NW APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: T SE APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: T NE APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: T N1 APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: T N2 APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: T S1 APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: T S2 APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: T CORRIDOR
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
| January | 0.992689E+09 | 370.63 | 01-JAN-00:10 | 0.00 | 0.00 |
| February | 0.896622E+09 | 370.63 | 01-FEB-00:10 | 0.00 | 0.00 |
| March | 0.992689E+09 | 370.63 | 01-MAR-00:10 | 0.00 | 0.00 |
| April | 0.960667E+09 | 370.63 | 01-APR-00:10 | 0.00 | 0.00 |
| May | 0.992689E+09 | 370.63 | 01-MAY-00:10 | 0.00 | 0.00 |
| June | 0.960667E+09 | 370.63 | 01-JUN-00:10 | 0.00 | 0.00 |
| July | 0.992689E+09 | 370.63 | 01-JUL-00:10 | 0.00 | 0.00 |
| August | 0.992689E+09 | 370.63 | 01-AUG-00:10 | 0.00 | 0.00 |
| September | 0.960667E+09 | 370.63 | 01-SEP-00:10 | 0.00 | 0.00 |
| October | 0.992689E+09 | 370.63 | 01-OCT-00:10 | 0.00 | 0.00 |
| November | 0.960667E+09 | 370.63 | 01-NOV-00:10 | 0.00 | 0.00 |
| December | 0.992689E+09 | 370.63 | 01-DEC-00:10 | 0.00 | 0.00 |
| Annual Sum or Average | 0.116881E+11 | 0.00 | 0.00 | ||
| Minimum of Months | 0.896622E+09 | 370.63 | 0.00 | 0.00 | |
| Maximum of Months | 0.992689E+09 | 370.63 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: G CORRIDOR
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.992689E+09 | 370.63 | 01-JAN-00:10 | 0.599555E+10 | 4168.07 | 01-JAN-07:10 |
| February | 0.896622E+09 | 370.63 | 01-FEB-00:10 | 0.541534E+10 | 4168.07 | 01-FEB-07:10 |
| March | 0.992689E+09 | 370.63 | 01-MAR-00:10 | 0.599555E+10 | 4168.07 | 01-MAR-07:10 |
| April | 0.960667E+09 | 370.63 | 01-APR-00:10 | 0.580215E+10 | 4168.07 | 01-APR-06:10 |
| May | 0.992689E+09 | 370.63 | 01-MAY-00:10 | 0.599555E+10 | 4168.07 | 01-MAY-06:10 |
| June | 0.960667E+09 | 370.63 | 01-JUN-00:10 | 0.580215E+10 | 4168.07 | 01-JUN-06:10 |
| July | 0.992689E+09 | 370.63 | 01-JUL-00:10 | 0.599555E+10 | 4168.07 | 01-JUL-06:10 |
| August | 0.992689E+09 | 370.63 | 01-AUG-00:10 | 0.599555E+10 | 4168.07 | 01-AUG-06:10 |
| September | 0.960667E+09 | 370.63 | 01-SEP-00:10 | 0.580215E+10 | 4168.07 | 01-SEP-06:10 |
| October | 0.992689E+09 | 370.63 | 01-OCT-00:10 | 0.599555E+10 | 4168.07 | 01-OCT-06:10 |
| November | 0.960667E+09 | 370.63 | 01-NOV-00:10 | 0.580215E+10 | 4168.07 | 01-NOV-06:10 |
| December | 0.992689E+09 | 370.63 | 01-DEC-00:10 | 0.599555E+10 | 4168.07 | 01-DEC-07:10 |
| Annual Sum or Average | 0.116881E+11 | 0.705928E+11 | ||||
| Minimum of Months | 0.896622E+09 | 370.63 | 0.541534E+10 | 4168.07 | ||
| Maximum of Months | 0.992689E+09 | 370.63 | 0.599555E+10 | 4168.07 |
Report: ZoneElectricSummaryMonthly
For: M CORRIDOR
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
| January | 0.992689E+09 | 370.63 | 01-JAN-00:10 | 0.00 | 0.00 |
| February | 0.896622E+09 | 370.63 | 01-FEB-00:10 | 0.00 | 0.00 |
| March | 0.992689E+09 | 370.63 | 01-MAR-00:10 | 0.00 | 0.00 |
| April | 0.960667E+09 | 370.63 | 01-APR-00:10 | 0.00 | 0.00 |
| May | 0.992689E+09 | 370.63 | 01-MAY-00:10 | 0.00 | 0.00 |
| June | 0.960667E+09 | 370.63 | 01-JUN-00:10 | 0.00 | 0.00 |
| July | 0.992689E+09 | 370.63 | 01-JUL-00:10 | 0.00 | 0.00 |
| August | 0.992689E+09 | 370.63 | 01-AUG-00:10 | 0.00 | 0.00 |
| September | 0.960667E+09 | 370.63 | 01-SEP-00:10 | 0.00 | 0.00 |
| October | 0.992689E+09 | 370.63 | 01-OCT-00:10 | 0.00 | 0.00 |
| November | 0.960667E+09 | 370.63 | 01-NOV-00:10 | 0.00 | 0.00 |
| December | 0.992689E+09 | 370.63 | 01-DEC-00:10 | 0.00 | 0.00 |
| Annual Sum or Average | 0.116881E+11 | 0.00 | 0.00 | ||
| Minimum of Months | 0.896622E+09 | 370.63 | 0.00 | 0.00 | |
| Maximum of Months | 0.992689E+09 | 370.63 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: G SW APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.886472E+09 |
| February | 0.389025E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.940386E+09 |
| March | 0.418950E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 751514.62 | 0.586830E+09 |
| April | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.416589E+09 |
| May | 0.424935E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 477357.01 | 0.208226E+09 |
| June | 0.406980E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12168880.47 | 0.133704E+09 |
| July | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25747224.95 | 53165270.62 |
| August | 0.418950E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18699840.38 | 73729652.56 |
| September | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1539109.27 | 0.148712E+09 |
| October | 0.430920E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.328046E+09 |
| November | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.486913E+09 |
| December | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.931446E+09 |
| Annual Sum or Average | 0.505732E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 59383926.70 | 0.519422E+10 |
| Minimum of Months | 0.389025E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53165270.62 |
| Maximum of Months | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25747224.95 | 0.940386E+09 |
Report: SpaceGainsMonthly
For: G NW APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.886472E+09 |
| February | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.940386E+09 |
| March | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1289895.26 | 0.586042E+09 |
| April | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.412487E+09 |
| May | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 797144.84 | 0.197295E+09 |
| June | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12168891.09 | 0.131576E+09 |
| July | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25747232.32 | 53151322.34 |
| August | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18699847.96 | 73592400.12 |
| September | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1539110.39 | 0.145125E+09 |
| October | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.308935E+09 |
| November | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.482656E+09 |
| December | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.931446E+09 |
| Annual Sum or Average | 0.512427E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 60242121.86 | 0.514916E+10 |
| Minimum of Months | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53151322.34 |
| Maximum of Months | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25747232.32 | 0.940386E+09 |
Report: SpaceGainsMonthly
For: OFFICE
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.227408E+09 | 0.609777E+09 | 0.787690E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.751775E+09 |
| February | 0.216037E+09 | 0.564682E+09 | 0.723971E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.808911E+09 |
| March | 0.261519E+09 | 0.654405E+09 | 0.827804E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 462025.80 | 0.518024E+09 |
| April | 0.227408E+09 | 0.599704E+09 | 0.770907E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.381578E+09 |
| May | 0.250148E+09 | 0.639529E+09 | 0.814432E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 265724.62 | 0.232883E+09 |
| June | 0.250148E+09 | 0.629456E+09 | 0.797650E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7149404.69 | 0.169214E+09 |
| July | 0.227408E+09 | 0.609777E+09 | 0.787690E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13429056.01 | 0.102926E+09 |
| August | 0.261519E+09 | 0.654405E+09 | 0.827804E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9370099.72 | 0.122316E+09 |
| September | 0.227408E+09 | 0.599704E+09 | 0.770907E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 306950.82 | 0.183077E+09 |
| October | 0.238778E+09 | 0.624653E+09 | 0.801061E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.344184E+09 |
| November | 0.227408E+09 | 0.599704E+09 | 0.770907E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.458058E+09 |
| December | 0.227408E+09 | 0.609777E+09 | 0.787690E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.795680E+09 |
| Annual Sum or Average | 0.284259E+10 | 0.739557E+10 | 0.946851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30983261.67 | 0.486863E+10 |
| Minimum of Months | 0.216037E+09 | 0.564682E+09 | 0.723971E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102926E+09 |
| Maximum of Months | 0.261519E+09 | 0.654405E+09 | 0.827804E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13429056.01 | 0.808911E+09 |
Report: SpaceGainsMonthly
For: G NE APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.886472E+09 |
| February | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.940386E+09 |
| March | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1184445.89 | 0.586128E+09 |
| April | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.412415E+09 |
| May | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 814808.45 | 0.197560E+09 |
| June | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12168904.51 | 0.131555E+09 |
| July | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25747258.38 | 53155798.90 |
| August | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18699865.37 | 73615851.60 |
| September | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1539112.76 | 0.145758E+09 |
| October | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.309818E+09 |
| November | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.482725E+09 |
| December | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.931446E+09 |
| Annual Sum or Average | 0.512427E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 60154395.36 | 0.515103E+10 |
| Minimum of Months | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53155798.90 |
| Maximum of Months | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25747258.38 | 0.940386E+09 |
Report: SpaceGainsMonthly
For: G N1 APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.534698E+09 |
| February | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.567217E+09 |
| March | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 744591.05 | 0.353762E+09 |
| April | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.248803E+09 |
| May | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 529464.33 | 0.121385E+09 |
| June | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7339978.37 | 80765225.28 |
| July | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15530096.42 | 32117001.89 |
| August | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11279289.06 | 44542998.78 |
| September | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 928354.29 | 89664826.25 |
| October | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.189648E+09 |
| November | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.291629E+09 |
| December | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.561824E+09 |
| Annual Sum or Average | 0.512427E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 36351773.52 | 0.311606E+10 |
| Minimum of Months | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32117001.89 |
| Maximum of Months | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15530096.42 | 0.567217E+09 |
Report: SpaceGainsMonthly
For: G N2 APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.534698E+09 |
| February | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.567217E+09 |
| March | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 740657.21 | 0.353770E+09 |
| April | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.248816E+09 |
| May | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 528347.10 | 0.121428E+09 |
| June | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7339978.46 | 80748471.61 |
| July | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15530096.62 | 32116994.42 |
| August | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11279289.17 | 44543306.48 |
| September | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 928354.30 | 89685838.18 |
| October | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.189734E+09 |
| November | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.291634E+09 |
| December | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.561824E+09 |
| Annual Sum or Average | 0.512427E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 36346722.87 | 0.311621E+10 |
| Minimum of Months | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32116994.42 |
| Maximum of Months | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15530096.62 | 0.567217E+09 |
Report: SpaceGainsMonthly
For: G S1 APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.534700E+09 |
| February | 0.389025E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.567217E+09 |
| March | 0.418950E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 402431.39 | 0.354701E+09 |
| April | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.252294E+09 |
| May | 0.424935E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 281830.63 | 0.130118E+09 |
| June | 0.406980E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7339971.82 | 82189544.47 |
| July | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15530090.99 | 32123305.88 |
| August | 0.418950E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11279283.32 | 44582197.43 |
| September | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 928353.79 | 91322802.80 |
| October | 0.430920E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.205316E+09 |
| November | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.296825E+09 |
| December | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.561832E+09 |
| Annual Sum or Average | 0.505732E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 35761961.93 | 0.315322E+10 |
| Minimum of Months | 0.389025E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32123305.88 |
| Maximum of Months | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15530090.99 | 0.567217E+09 |
Report: SpaceGainsMonthly
For: G S2 APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.534698E+09 |
| February | 0.389025E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.567217E+09 |
| March | 0.418950E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 412623.81 | 0.354686E+09 |
| April | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.252184E+09 |
| May | 0.424935E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 277254.52 | 0.131300E+09 |
| June | 0.406980E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7339971.52 | 82590739.84 |
| July | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15530091.99 | 32132163.46 |
| August | 0.418950E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11279283.84 | 44595270.42 |
| September | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 928353.85 | 91504307.88 |
| October | 0.430920E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.206233E+09 |
| November | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.296668E+09 |
| December | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.561827E+09 |
| Annual Sum or Average | 0.505732E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 35767579.53 | 0.315563E+10 |
| Minimum of Months | 0.389025E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32132163.46 |
| Maximum of Months | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15530091.99 | 0.567217E+09 |
Report: SpaceGainsMonthly
For: M SW APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127524E+10 |
| February | 0.389025E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.135286E+10 |
| March | 0.418950E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 611492.49 | 0.855911E+09 |
| April | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.633125E+09 |
| May | 0.424935E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 639760.81 | 0.361427E+09 |
| June | 0.406980E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17322498.78 | 0.199351E+09 |
| July | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36724263.21 | 76992516.40 |
| August | 0.418950E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26676117.79 | 0.106663E+09 |
| September | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2185061.14 | 0.215219E+09 |
| October | 0.430920E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.481680E+09 |
| November | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.707557E+09 |
| December | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133991E+10 |
| Annual Sum or Average | 0.505732E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 84159194.22 | 0.760593E+10 |
| Minimum of Months | 0.389025E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76992516.40 |
| Maximum of Months | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36724263.21 | 0.135286E+10 |
Report: SpaceGainsMonthly
For: M NW APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127498E+10 |
| February | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.135247E+10 |
| March | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 751899.72 | 0.850472E+09 |
| April | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.612107E+09 |
| May | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 639761.49 | 0.354690E+09 |
| June | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17322502.79 | 0.199124E+09 |
| July | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36724262.74 | 76997939.55 |
| August | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26676120.34 | 0.106624E+09 |
| September | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2185061.78 | 0.211703E+09 |
| October | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.453467E+09 |
| November | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.696465E+09 |
| December | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133972E+10 |
| Annual Sum or Average | 0.512427E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 84299608.86 | 0.752882E+10 |
| Minimum of Months | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76997939.55 |
| Maximum of Months | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36724262.74 | 0.135247E+10 |
Report: SpaceGainsMonthly
For: M SE APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127518E+10 |
| February | 0.389025E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.135257E+10 |
| March | 0.418950E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 611492.92 | 0.855441E+09 |
| April | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.634069E+09 |
| May | 0.424935E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 639762.01 | 0.362361E+09 |
| June | 0.406980E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17322523.53 | 0.199761E+09 |
| July | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36724303.59 | 76996538.54 |
| August | 0.418950E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26676148.72 | 0.106690E+09 |
| September | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2185065.57 | 0.215180E+09 |
| October | 0.430920E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.484438E+09 |
| November | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.708158E+09 |
| December | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133990E+10 |
| Annual Sum or Average | 0.505732E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 84159296.33 | 0.761075E+10 |
| Minimum of Months | 0.389025E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76996538.54 |
| Maximum of Months | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36724303.59 | 0.135257E+10 |
Report: SpaceGainsMonthly
For: M NE APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127498E+10 |
| February | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.135247E+10 |
| March | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 676206.33 | 0.850729E+09 |
| April | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.613594E+09 |
| May | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 639762.66 | 0.356584E+09 |
| June | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17322527.23 | 0.199621E+09 |
| July | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36724302.40 | 76993647.50 |
| August | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26676149.45 | 0.106647E+09 |
| September | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2185065.15 | 0.212191E+09 |
| October | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.455233E+09 |
| November | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.696735E+09 |
| December | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133972E+10 |
| Annual Sum or Average | 0.512427E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 84224013.23 | 0.753550E+10 |
| Minimum of Months | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76993647.50 |
| Maximum of Months | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36724302.40 | 0.135247E+10 |
Report: SpaceGainsMonthly
For: M N1 APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.769038E+09 |
| February | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.815778E+09 |
| March | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 449472.41 | 0.514697E+09 |
| April | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.371653E+09 |
| May | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 385889.08 | 0.217334E+09 |
| June | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10448513.85 | 0.120731E+09 |
| July | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22151173.00 | 46446292.18 |
| August | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16090386.15 | 64387392.38 |
| September | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1317977.18 | 0.130547E+09 |
| October | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.280636E+09 |
| November | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.421928E+09 |
| December | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.808087E+09 |
| Annual Sum or Average | 0.512427E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 50843411.67 | 0.456126E+10 |
| Minimum of Months | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46446292.18 |
| Maximum of Months | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22151173.00 | 0.815778E+09 |
Report: SpaceGainsMonthly
For: M N2 APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.769038E+09 |
| February | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.815778E+09 |
| March | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 447394.00 | 0.514710E+09 |
| April | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.371877E+09 |
| May | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 385889.09 | 0.217433E+09 |
| June | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10448514.07 | 0.120742E+09 |
| July | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22151173.38 | 46446272.90 |
| August | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16090386.43 | 64387560.45 |
| September | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1317977.20 | 0.130552E+09 |
| October | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.280805E+09 |
| November | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.421949E+09 |
| December | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.808088E+09 |
| Annual Sum or Average | 0.512427E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 50841334.17 | 0.456181E+10 |
| Minimum of Months | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46446272.90 |
| Maximum of Months | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22151173.38 | 0.815778E+09 |
Report: SpaceGainsMonthly
For: M S1 APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.769433E+09 |
| February | 0.389025E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.816495E+09 |
| March | 0.418950E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 368837.35 | 0.520448E+09 |
| April | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.388304E+09 |
| May | 0.424935E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 385888.53 | 0.221415E+09 |
| June | 0.406980E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10448508.52 | 0.120830E+09 |
| July | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22151169.22 | 46445051.24 |
| August | 0.418950E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16090380.38 | 64392311.65 |
| September | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1317976.70 | 0.131957E+09 |
| October | 0.430920E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.302545E+09 |
| November | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.434508E+09 |
| December | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.808603E+09 |
| Annual Sum or Average | 0.505732E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 50762760.71 | 0.462538E+10 |
| Minimum of Months | 0.389025E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46445051.24 |
| Maximum of Months | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22151169.22 | 0.816495E+09 |
Report: SpaceGainsMonthly
For: M S2 APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.769432E+09 |
| February | 0.389025E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.816494E+09 |
| March | 0.418950E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 368837.36 | 0.520459E+09 |
| April | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.388410E+09 |
| May | 0.424935E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 385888.54 | 0.221432E+09 |
| June | 0.406980E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10448508.81 | 0.120834E+09 |
| July | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22151169.71 | 46445127.88 |
| August | 0.418950E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16090380.82 | 64392235.58 |
| September | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1317976.77 | 0.131951E+09 |
| October | 0.430920E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.302692E+09 |
| November | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.434562E+09 |
| December | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.808606E+09 |
| Annual Sum or Average | 0.505732E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 50762762.01 | 0.462571E+10 |
| Minimum of Months | 0.389025E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46445127.88 |
| Maximum of Months | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22151169.71 | 0.816494E+09 |
Report: SpaceGainsMonthly
For: T SW APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.168984E+10 |
| February | 0.389025E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.179257E+10 |
| March | 0.418950E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 774659.57 | 0.112995E+10 |
| April | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.823696E+09 |
| May | 0.424935E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 818518.26 | 0.439540E+09 |
| June | 0.406980E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22480876.14 | 0.250560E+09 |
| July | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 47849597.98 | 0.100604E+09 |
| August | 0.418950E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34766944.60 | 0.137507E+09 |
| September | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2820217.41 | 0.262802E+09 |
| October | 0.430920E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.607696E+09 |
| November | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.930539E+09 |
| December | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.177556E+10 |
| Annual Sum or Average | 0.505732E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109511E+09 | 0.994087E+10 |
| Minimum of Months | 0.389025E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100604E+09 |
| Maximum of Months | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 47849597.98 | 0.179257E+10 |
Report: SpaceGainsMonthly
For: T NW APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.168934E+10 |
| February | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.179187E+10 |
| March | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 774722.73 | 0.112299E+10 |
| April | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.809239E+09 |
| May | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 818518.13 | 0.430455E+09 |
| June | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22480869.75 | 0.249675E+09 |
| July | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 47849577.03 | 0.100954E+09 |
| August | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34766943.85 | 0.136975E+09 |
| September | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2820215.24 | 0.253625E+09 |
| October | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.583563E+09 |
| November | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.921609E+09 |
| December | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.177523E+10 |
| Annual Sum or Average | 0.512427E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109511E+09 | 0.986552E+10 |
| Minimum of Months | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100954E+09 |
| Maximum of Months | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 47849577.03 | 0.179187E+10 |
Report: SpaceGainsMonthly
For: T SE APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.168970E+10 |
| February | 0.389025E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.179210E+10 |
| March | 0.418950E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 774662.65 | 0.112981E+10 |
| April | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.824524E+09 |
| May | 0.424935E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 818520.97 | 0.443763E+09 |
| June | 0.406980E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22480931.61 | 0.252769E+09 |
| July | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 47849685.93 | 0.101190E+09 |
| August | 0.418950E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34767009.63 | 0.138109E+09 |
| September | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2820226.88 | 0.264523E+09 |
| October | 0.430920E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.610569E+09 |
| November | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.930906E+09 |
| December | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.177553E+10 |
| Annual Sum or Average | 0.505732E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109511E+09 | 0.995349E+10 |
| Minimum of Months | 0.389025E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101190E+09 |
| Maximum of Months | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 47849685.93 | 0.179210E+10 |
Report: SpaceGainsMonthly
For: T NE APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.168934E+10 |
| February | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.179187E+10 |
| March | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 774663.91 | 0.112330E+10 |
| April | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.810046E+09 |
| May | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 818520.44 | 0.436921E+09 |
| June | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22480921.61 | 0.252592E+09 |
| July | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 47849659.31 | 0.101279E+09 |
| August | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34767001.12 | 0.137508E+09 |
| September | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2820221.92 | 0.257600E+09 |
| October | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.584022E+09 |
| November | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.921858E+09 |
| December | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.177523E+10 |
| Annual Sum or Average | 0.512427E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109511E+09 | 0.988157E+10 |
| Minimum of Months | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101279E+09 |
| Maximum of Months | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 47849659.31 | 0.179187E+10 |
Report: SpaceGainsMonthly
For: T N1 APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101896E+10 |
| February | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108081E+10 |
| March | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 467602.57 | 0.678284E+09 |
| April | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.487474E+09 |
| May | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 493710.99 | 0.264339E+09 |
| June | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13559914.28 | 0.153338E+09 |
| July | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28861687.94 | 61518441.32 |
| August | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20970571.79 | 83978743.74 |
| September | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1701086.74 | 0.157445E+09 |
| October | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.354183E+09 |
| November | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.556821E+09 |
| December | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107077E+10 |
| Annual Sum or Average | 0.512427E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 66054574.31 | 0.596793E+10 |
| Minimum of Months | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61518441.32 |
| Maximum of Months | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28861687.94 | 0.108081E+10 |
Report: SpaceGainsMonthly
For: T N2 APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101896E+10 |
| February | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108081E+10 |
| March | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 467288.93 | 0.678310E+09 |
| April | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.487686E+09 |
| May | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 493711.02 | 0.264765E+09 |
| June | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13559915.18 | 0.153493E+09 |
| July | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28861689.43 | 61517504.29 |
| August | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20970572.73 | 83985307.00 |
| September | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1701086.81 | 0.157664E+09 |
| October | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.354298E+09 |
| November | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.556839E+09 |
| December | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107077E+10 |
| Annual Sum or Average | 0.512427E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 66054264.10 | 0.596911E+10 |
| Minimum of Months | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61517504.29 |
| Maximum of Months | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28861689.43 | 0.108081E+10 |
Report: SpaceGainsMonthly
For: T S1 APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101946E+10 |
| February | 0.389025E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108164E+10 |
| March | 0.418950E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 467256.74 | 0.684173E+09 |
| April | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.499835E+09 |
| May | 0.424935E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 493711.00 | 0.271298E+09 |
| June | 0.406980E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13559917.14 | 0.153996E+09 |
| July | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28861700.31 | 61337226.34 |
| August | 0.418950E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20970578.65 | 84263430.19 |
| September | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1701088.34 | 0.163121E+09 |
| October | 0.430920E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.373692E+09 |
| November | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.565013E+09 |
| December | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107125E+10 |
| Annual Sum or Average | 0.505732E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 66054252.18 | 0.602908E+10 |
| Minimum of Months | 0.389025E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61337226.34 |
| Maximum of Months | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28861700.31 | 0.108164E+10 |
Report: SpaceGainsMonthly
For: T S2 APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101945E+10 |
| February | 0.389025E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108164E+10 |
| March | 0.418950E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 467256.79 | 0.684259E+09 |
| April | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.499953E+09 |
| May | 0.424935E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 493711.05 | 0.271433E+09 |
| June | 0.406980E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13559918.18 | 0.154045E+09 |
| July | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28861702.04 | 61346702.37 |
| August | 0.418950E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20970580.10 | 84271818.07 |
| September | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1701088.56 | 0.163174E+09 |
| October | 0.430920E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.373864E+09 |
| November | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.565066E+09 |
| December | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107125E+10 |
| Annual Sum or Average | 0.505732E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 66054256.71 | 0.602975E+10 |
| Minimum of Months | 0.389025E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61346702.37 |
| Maximum of Months | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28861702.04 | 0.108164E+10 |
Report: SpaceGainsMonthly
For: T CORRIDOR
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.727675E+09 | 0.992689E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.274626E+09 |
| February | 0.657255E+09 | 0.896622E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.291583E+09 |
| March | 0.727675E+09 | 0.992689E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19138.23 | 0.191290E+09 |
| April | 0.704201E+09 | 0.960667E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.144908E+09 |
| May | 0.727675E+09 | 0.992689E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10170.46 | 86791329.54 |
| June | 0.704201E+09 | 0.960667E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 743815.94 | 57460162.97 |
| July | 0.727675E+09 | 0.992689E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2038765.51 | 29322899.50 |
| August | 0.727675E+09 | 0.992689E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1633093.78 | 35511185.42 |
| September | 0.704201E+09 | 0.960667E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26934.05 | 55016766.62 |
| October | 0.727675E+09 | 0.992689E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108517E+09 |
| November | 0.704201E+09 | 0.960667E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.157847E+09 |
| December | 0.727675E+09 | 0.992689E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.288431E+09 |
| Annual Sum or Average | 0.856778E+10 | 0.116881E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4471917.96 | 0.172130E+10 |
| Minimum of Months | 0.657255E+09 | 0.896622E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29322899.50 |
| Maximum of Months | 0.727675E+09 | 0.992689E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2038765.51 | 0.291583E+09 |
Report: SpaceGainsMonthly
For: G CORRIDOR
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.727675E+09 | 0.992689E+09 | 0.299778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.500611E+10 |
| February | 0.657255E+09 | 0.896622E+09 | 0.270767E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.467061E+10 |
| March | 0.727675E+09 | 0.992689E+09 | 0.299778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10249658.05 | 0.375070E+10 |
| April | 0.704201E+09 | 0.960667E+09 | 0.290107E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.263074E+10 |
| May | 0.727675E+09 | 0.992689E+09 | 0.299778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4735564.06 | 0.166358E+10 |
| June | 0.704201E+09 | 0.960667E+09 | 0.290107E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 21210162.99 | 0.114523E+10 |
| July | 0.727675E+09 | 0.992689E+09 | 0.299778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 52799980.30 | 0.708101E+09 |
| August | 0.727675E+09 | 0.992689E+09 | 0.299778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 45434319.14 | 0.955283E+09 |
| September | 0.704201E+09 | 0.960667E+09 | 0.290107E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 632668.18 | 0.159260E+10 |
| October | 0.727675E+09 | 0.992689E+09 | 0.299778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.263122E+10 |
| November | 0.704201E+09 | 0.960667E+09 | 0.290107E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.303404E+10 |
| December | 0.727675E+09 | 0.992689E+09 | 0.299778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.477754E+10 |
| Annual Sum or Average | 0.856778E+10 | 0.116881E+11 | 0.352964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.135062E+09 | 0.325658E+11 |
| Minimum of Months | 0.657255E+09 | 0.896622E+09 | 0.270767E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.708101E+09 |
| Maximum of Months | 0.727675E+09 | 0.992689E+09 | 0.299778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 52799980.30 | 0.500611E+10 |
Report: SpaceGainsMonthly
For: M CORRIDOR
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.727675E+09 | 0.992689E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.223598E+09 |
| February | 0.657255E+09 | 0.896622E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.236717E+09 |
| March | 0.727675E+09 | 0.992689E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65188.74 | 0.156129E+09 |
| April | 0.704201E+09 | 0.960667E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118256E+09 |
| May | 0.727675E+09 | 0.992689E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9447.79 | 73407896.57 |
| June | 0.704201E+09 | 0.960667E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 795931.23 | 46087310.72 |
| July | 0.727675E+09 | 0.992689E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2185647.94 | 22241056.65 |
| August | 0.727675E+09 | 0.992689E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1701734.83 | 27732070.20 |
| September | 0.704201E+09 | 0.960667E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60103.50 | 46899780.38 |
| October | 0.727675E+09 | 0.992689E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91721508.52 |
| November | 0.704201E+09 | 0.960667E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130959E+09 |
| December | 0.727675E+09 | 0.992689E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.234953E+09 |
| Annual Sum or Average | 0.856778E+10 | 0.116881E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4818054.02 | 0.140870E+10 |
| Minimum of Months | 0.657255E+09 | 0.896622E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22241056.65 |
| Maximum of Months | 0.727675E+09 | 0.992689E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2185647.94 | 0.236717E+09 |
Report: PeakSpaceGainsMonthly
For: G SW APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 1033.45 | 12-JAN-09:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 988.84 | 13-FEB-06:00 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 29.74 | 14-MAR-14:00 | 678.45 | 01-MAR-15:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 548.38 | 16-APR-04:00 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 44.69 | 14-MAY-15:00 | 261.93 | 11-MAY-15:00 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 131.31 | 12-JUN-13:00 | 271.37 | 13-JUN-16:00 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 180.05 | 15-JUL-15:00 | 177.59 | 06-JUL-02:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 140.00 | 13-AUG-13:00 | 180.04 | 30-AUG-18:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 58.70 | 16-SEP-13:00 | 281.49 | 29-SEP-19:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 311.82 | 23-OCT-15:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 577.34 | 17-NOV-09:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1018.39 | 09-DEC-15:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 177.59 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 180.05 | 1033.45 |
Report: PeakSpaceGainsMonthly
For: G NW APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 1033.45 | 12-JAN-09:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 988.84 | 13-FEB-06:00 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 47.80 | 14-MAR-14:00 | 678.45 | 01-MAR-15:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 548.38 | 16-APR-04:00 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 49.54 | 14-MAY-15:00 | 261.93 | 11-MAY-15:00 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 131.31 | 12-JUN-13:00 | 266.59 | 13-JUN-16:00 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 180.05 | 15-JUL-15:00 | 176.82 | 06-JUL-02:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 140.00 | 13-AUG-13:00 | 180.04 | 30-AUG-18:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 58.70 | 16-SEP-13:00 | 271.46 | 29-SEP-19:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 297.32 | 23-OCT-15:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 577.34 | 17-NOV-09:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1018.39 | 09-DEC-15:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 176.82 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 180.05 | 1033.45 |
Report: PeakSpaceGainsMonthly
For: OFFICE
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 451.21 | 03-JAN-08:09 | 582.92 | 03-JAN-08:09 | 588.62 | 03-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 1026.97 | 12-JAN-09:10 |
| February | 451.21 | 01-FEB-08:09 | 582.92 | 01-FEB-08:09 | 588.62 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 983.50 | 07-FEB-11:00 |
| March | 451.21 | 01-MAR-08:09 | 582.92 | 01-MAR-08:09 | 588.62 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 29.38 | 15-MAR-14:00 | 678.45 | 01-MAR-15:00 |
| April | 451.21 | 03-APR-07:10 | 582.92 | 03-APR-07:10 | 588.62 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 475.95 | 04-APR-15:00 |
| May | 451.21 | 01-MAY-07:10 | 582.92 | 01-MAY-07:10 | 588.62 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.54 | 10-MAY-14:00 | 291.18 | 11-MAY-15:00 |
| June | 451.21 | 01-JUN-07:10 | 582.92 | 01-JUN-07:10 | 588.62 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 131.28 | 12-JUN-13:00 | 280.19 | 14-JUN-09:00 |
| July | 451.21 | 03-JUL-07:10 | 582.92 | 03-JUL-07:10 | 588.62 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 153.81 | 19-JUL-14:00 | 213.16 | 06-JUL-02:00 |
| August | 451.21 | 01-AUG-07:10 | 582.92 | 01-AUG-07:10 | 588.62 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 101.52 | 15-AUG-13:00 | 202.80 | 30-AUG-18:00 |
| September | 451.21 | 01-SEP-07:10 | 582.92 | 01-SEP-07:10 | 588.62 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.86 | 15-SEP-12:00 | 293.89 | 29-SEP-19:00 |
| October | 451.21 | 02-OCT-07:10 | 582.92 | 02-OCT-07:10 | 588.62 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 337.87 | 23-OCT-15:00 |
| November | 451.21 | 01-NOV-07:10 | 582.92 | 01-NOV-07:10 | 588.62 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 567.36 | 17-NOV-09:07 |
| December | 451.21 | 01-DEC-08:09 | 582.92 | 01-DEC-08:09 | 588.62 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 808.50 | 09-DEC-15:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 451.21 | 582.92 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 202.80 | |||||
| Maximum of Months | 451.21 | 582.92 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 153.81 | 1026.97 |
Report: PeakSpaceGainsMonthly
For: G NE APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 1033.45 | 12-JAN-09:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 988.84 | 13-FEB-06:00 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 45.96 | 14-MAR-14:00 | 678.45 | 01-MAR-15:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 548.38 | 16-APR-04:00 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 55.66 | 14-MAY-15:00 | 261.93 | 11-MAY-15:00 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 131.31 | 12-JUN-13:00 | 262.76 | 13-JUN-16:00 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 180.05 | 15-JUL-15:00 | 175.91 | 06-JUL-02:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 140.00 | 13-AUG-13:00 | 180.04 | 30-AUG-18:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 58.70 | 16-SEP-13:00 | 267.16 | 29-SEP-19:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 297.32 | 23-OCT-15:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 577.34 | 17-NOV-09:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1018.39 | 09-DEC-15:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 175.91 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 180.05 | 1033.45 |
Report: PeakSpaceGainsMonthly
For: G N1 APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 623.35 | 12-JAN-09:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 596.45 | 13-FEB-06:00 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 28.61 | 14-MAR-14:00 | 409.23 | 01-MAR-15:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 330.77 | 16-APR-04:00 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 33.87 | 14-MAY-15:00 | 157.99 | 11-MAY-15:00 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 79.20 | 12-JUN-13:00 | 163.68 | 13-JUN-16:00 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 108.60 | 15-JUL-15:00 | 107.25 | 06-JUL-02:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 84.45 | 13-AUG-13:00 | 108.59 | 30-AUG-18:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 35.40 | 16-SEP-13:00 | 172.68 | 29-SEP-19:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 182.39 | 23-OCT-15:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 348.24 | 17-NOV-09:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 614.27 | 09-DEC-15:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 107.25 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 108.60 | 623.35 |
Report: PeakSpaceGainsMonthly
For: G N2 APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 623.35 | 12-JAN-09:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 596.45 | 13-FEB-06:00 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 28.52 | 14-MAR-14:00 | 409.23 | 01-MAR-15:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 330.77 | 16-APR-04:00 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 34.03 | 14-MAY-15:00 | 157.99 | 11-MAY-15:00 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 79.20 | 12-JUN-13:00 | 163.65 | 13-JUN-16:00 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 108.60 | 15-JUL-15:00 | 107.25 | 06-JUL-02:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 84.45 | 13-AUG-13:00 | 108.59 | 30-AUG-18:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 35.40 | 16-SEP-13:00 | 172.54 | 29-SEP-19:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 182.53 | 23-OCT-15:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 348.24 | 17-NOV-09:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 614.27 | 09-DEC-15:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 107.25 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 108.60 | 623.35 |
Report: PeakSpaceGainsMonthly
For: G S1 APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 623.35 | 12-JAN-09:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 596.45 | 13-FEB-06:00 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.72 | 15-MAR-14:00 | 409.23 | 01-MAR-15:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 330.77 | 16-APR-04:00 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 26.95 | 14-MAY-15:00 | 160.98 | 11-MAY-15:00 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 79.20 | 12-JUN-13:00 | 167.00 | 13-JUN-16:00 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 108.60 | 15-JUL-15:00 | 107.25 | 06-JUL-02:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 84.45 | 13-AUG-13:00 | 108.59 | 30-AUG-18:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 35.40 | 16-SEP-13:00 | 178.92 | 29-SEP-19:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 194.61 | 23-OCT-15:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 348.24 | 17-NOV-09:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 614.27 | 09-DEC-15:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 107.25 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 108.60 | 623.35 |
Report: PeakSpaceGainsMonthly
For: G S2 APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 623.35 | 12-JAN-09:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 596.45 | 13-FEB-06:00 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.72 | 15-MAR-14:00 | 409.23 | 01-MAR-15:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 330.77 | 16-APR-04:00 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 26.95 | 14-MAY-15:00 | 162.53 | 11-MAY-15:00 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 79.20 | 12-JUN-13:00 | 167.24 | 13-JUN-16:00 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 108.60 | 15-JUL-15:00 | 107.25 | 06-JUL-02:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 84.45 | 13-AUG-13:00 | 108.59 | 30-AUG-18:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 35.40 | 16-SEP-13:00 | 180.04 | 29-SEP-19:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 195.72 | 23-OCT-15:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 348.24 | 17-NOV-09:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 614.27 | 09-DEC-15:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 107.25 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 108.60 | 623.35 |
Report: PeakSpaceGainsMonthly
For: M SW APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 1486.07 | 12-JAN-09:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1421.98 | 13-FEB-06:00 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 41.82 | 15-MAR-14:00 | 980.50 | 01-MAR-15:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 788.74 | 16-APR-04:00 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 63.61 | 14-MAY-15:00 | 432.69 | 11-MAY-15:00 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 188.01 | 12-JUN-13:00 | 399.16 | 13-JUN-16:00 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 258.02 | 15-JUL-15:00 | 256.14 | 06-JUL-02:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 200.53 | 13-AUG-13:00 | 259.23 | 30-AUG-18:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 83.83 | 16-SEP-13:00 | 409.90 | 29-SEP-19:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 459.20 | 23-OCT-15:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 830.67 | 17-NOV-09:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1464.60 | 09-DEC-15:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 256.14 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 258.02 | 1486.07 |
Report: PeakSpaceGainsMonthly
For: M NW APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 1486.07 | 12-JAN-09:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1421.98 | 13-FEB-06:00 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 41.82 | 15-MAR-14:00 | 975.94 | 01-MAR-15:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 788.74 | 16-APR-04:00 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 63.61 | 14-MAY-15:00 | 429.25 | 11-MAY-15:00 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 188.01 | 12-JUN-13:00 | 399.16 | 13-JUN-16:00 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 258.02 | 15-JUL-15:00 | 256.14 | 06-JUL-02:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 200.53 | 13-AUG-13:00 | 259.23 | 30-AUG-18:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 83.83 | 16-SEP-13:00 | 395.58 | 29-SEP-19:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 437.45 | 23-OCT-15:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 830.67 | 17-NOV-09:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1464.60 | 09-DEC-15:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 256.14 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 258.02 | 1486.07 |
Report: PeakSpaceGainsMonthly
For: M SE APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 1486.07 | 12-JAN-09:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1421.98 | 13-FEB-06:00 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 41.82 | 15-MAR-14:00 | 975.94 | 01-MAR-15:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 788.74 | 16-APR-04:00 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 63.61 | 14-MAY-15:00 | 433.68 | 11-MAY-15:00 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 188.01 | 12-JUN-13:00 | 403.31 | 14-JUN-09:00 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 258.02 | 15-JUL-15:00 | 256.14 | 06-JUL-02:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 200.53 | 13-AUG-13:00 | 259.23 | 30-AUG-18:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 83.83 | 16-SEP-13:00 | 401.70 | 29-SEP-19:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 460.36 | 23-OCT-15:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 830.67 | 17-NOV-09:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1464.60 | 09-DEC-15:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 256.14 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 258.02 | 1486.07 |
Report: PeakSpaceGainsMonthly
For: M NE APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 1486.07 | 12-JAN-09:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1421.98 | 13-FEB-06:00 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 41.82 | 15-MAR-14:00 | 975.94 | 01-MAR-15:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 788.74 | 16-APR-04:00 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 63.61 | 14-MAY-15:00 | 430.72 | 11-MAY-15:00 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 188.01 | 12-JUN-13:00 | 403.31 | 14-JUN-09:00 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 258.02 | 15-JUL-15:00 | 256.14 | 06-JUL-02:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 200.53 | 13-AUG-13:00 | 259.23 | 30-AUG-18:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 83.83 | 16-SEP-13:00 | 387.48 | 29-SEP-19:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 439.61 | 23-OCT-15:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 830.67 | 17-NOV-09:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1464.60 | 09-DEC-15:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 256.14 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 258.02 | 1486.07 |
Report: PeakSpaceGainsMonthly
For: M N1 APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 896.36 | 12-JAN-09:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 857.70 | 13-FEB-06:00 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.23 | 15-MAR-14:00 | 588.66 | 01-MAR-15:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 475.75 | 16-APR-04:00 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.37 | 14-MAY-15:00 | 270.09 | 11-MAY-15:00 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 113.40 | 12-JUN-13:00 | 240.76 | 13-JUN-16:00 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 155.63 | 15-JUL-15:00 | 154.50 | 06-JUL-02:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 120.95 | 13-AUG-13:00 | 156.36 | 30-AUG-18:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 50.56 | 16-SEP-13:00 | 252.69 | 29-SEP-19:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 273.93 | 23-OCT-15:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 501.04 | 17-NOV-09:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 883.41 | 09-DEC-15:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 154.50 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 155.63 | 896.36 |
Report: PeakSpaceGainsMonthly
For: M N2 APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 896.36 | 12-JAN-09:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 857.70 | 13-FEB-06:00 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.23 | 15-MAR-14:00 | 588.66 | 01-MAR-15:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 475.75 | 16-APR-04:00 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.37 | 14-MAY-15:00 | 270.21 | 11-MAY-15:00 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 113.40 | 12-JUN-13:00 | 240.76 | 13-JUN-16:00 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 155.63 | 15-JUL-15:00 | 154.50 | 06-JUL-02:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 120.95 | 13-AUG-13:00 | 156.36 | 30-AUG-18:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 50.56 | 16-SEP-13:00 | 252.40 | 29-SEP-19:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 274.23 | 23-OCT-15:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 501.04 | 17-NOV-09:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 883.41 | 09-DEC-15:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 154.50 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 155.63 | 896.36 |
Report: PeakSpaceGainsMonthly
For: M S1 APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 896.36 | 12-JAN-09:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 857.70 | 13-FEB-06:00 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.23 | 15-MAR-14:00 | 608.58 | 01-MAR-15:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 475.75 | 16-APR-04:00 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.37 | 14-MAY-15:00 | 271.59 | 11-MAY-15:00 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 113.40 | 12-JUN-13:00 | 240.76 | 13-JUN-16:00 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 155.63 | 15-JUL-15:00 | 154.50 | 06-JUL-02:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 120.95 | 13-AUG-13:00 | 156.36 | 30-AUG-18:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 50.56 | 16-SEP-13:00 | 260.72 | 29-SEP-19:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 288.19 | 23-OCT-15:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 501.04 | 17-NOV-09:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 883.41 | 09-DEC-15:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 154.50 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 155.63 | 896.36 |
Report: PeakSpaceGainsMonthly
For: M S2 APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 896.36 | 12-JAN-09:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 857.70 | 13-FEB-06:00 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.23 | 15-MAR-14:00 | 608.76 | 01-MAR-15:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 475.75 | 16-APR-04:00 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.37 | 14-MAY-15:00 | 271.64 | 11-MAY-15:00 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 113.40 | 12-JUN-13:00 | 240.76 | 13-JUN-16:00 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 155.63 | 15-JUL-15:00 | 154.50 | 06-JUL-02:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 120.95 | 13-AUG-13:00 | 156.36 | 30-AUG-18:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 50.56 | 16-SEP-13:00 | 260.46 | 29-SEP-19:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 288.33 | 23-OCT-15:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 501.04 | 17-NOV-09:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 883.41 | 09-DEC-15:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 154.50 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 155.63 | 896.36 |
Report: PeakSpaceGainsMonthly
For: T SW APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 1968.20 | 12-JAN-09:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1883.45 | 13-FEB-06:00 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 54.27 | 15-MAR-14:00 | 1293.47 | 01-MAR-15:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1045.12 | 16-APR-04:00 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 82.54 | 14-MAY-15:00 | 500.34 | 11-MAY-15:00 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 246.86 | 12-JUN-13:00 | 502.34 | 13-JUN-16:00 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 339.40 | 15-JUL-15:00 | 318.26 | 06-JUL-02:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 263.50 | 13-AUG-13:00 | 344.25 | 30-AUG-18:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 109.51 | 16-SEP-13:00 | 470.42 | 29-SEP-19:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 567.28 | 23-OCT-15:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1101.41 | 17-NOV-09:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1940.26 | 09-DEC-15:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 318.26 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 339.40 | 1968.20 |
Report: PeakSpaceGainsMonthly
For: T NW APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 1968.20 | 12-JAN-09:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1883.45 | 13-FEB-06:00 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 54.27 | 15-MAR-14:00 | 1293.47 | 01-MAR-15:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1045.12 | 16-APR-04:00 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 82.54 | 14-MAY-15:00 | 500.34 | 11-MAY-15:00 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 246.86 | 12-JUN-13:00 | 491.65 | 13-JUN-16:00 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 339.40 | 15-JUL-15:00 | 317.76 | 06-JUL-02:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 263.50 | 13-AUG-13:00 | 344.25 | 30-AUG-18:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 109.51 | 16-SEP-13:00 | 444.31 | 29-SEP-19:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 567.28 | 23-OCT-15:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1101.41 | 17-NOV-09:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1940.26 | 09-DEC-15:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 317.76 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 339.40 | 1968.20 |
Report: PeakSpaceGainsMonthly
For: T SE APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 1968.20 | 12-JAN-09:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1883.45 | 13-FEB-06:00 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 54.27 | 15-MAR-14:00 | 1293.47 | 01-MAR-15:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1045.12 | 16-APR-04:00 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 82.54 | 14-MAY-15:00 | 500.34 | 11-MAY-15:00 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 246.86 | 12-JUN-13:00 | 486.22 | 13-JUN-16:00 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 339.40 | 15-JUL-15:00 | 315.48 | 06-JUL-02:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 263.50 | 13-AUG-13:00 | 344.25 | 30-AUG-18:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 109.51 | 16-SEP-13:00 | 448.91 | 29-SEP-19:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 567.28 | 23-OCT-15:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1101.41 | 17-NOV-09:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1940.26 | 09-DEC-15:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 315.48 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 339.40 | 1968.20 |
Report: PeakSpaceGainsMonthly
For: T NE APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 1968.20 | 12-JAN-09:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1883.45 | 13-FEB-06:00 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 54.27 | 15-MAR-14:00 | 1293.47 | 01-MAR-15:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1045.12 | 16-APR-04:00 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 82.54 | 14-MAY-15:00 | 500.34 | 11-MAY-15:00 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 246.86 | 12-JUN-13:00 | 491.11 | 14-JUN-09:00 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 339.40 | 15-JUL-15:00 | 315.04 | 06-JUL-02:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 263.50 | 13-AUG-13:00 | 344.25 | 30-AUG-18:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 109.51 | 16-SEP-13:00 | 444.22 | 29-SEP-19:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 567.28 | 23-OCT-15:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1101.41 | 17-NOV-09:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1940.26 | 09-DEC-15:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 315.04 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 339.40 | 1968.20 |
Report: PeakSpaceGainsMonthly
For: T N1 APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 1187.17 | 12-JAN-09:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1136.05 | 13-FEB-06:00 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 32.73 | 15-MAR-14:00 | 780.19 | 01-MAR-15:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 630.39 | 16-APR-04:00 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 49.79 | 14-MAY-15:00 | 314.25 | 11-MAY-15:00 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 148.90 | 12-JUN-13:00 | 301.47 | 13-JUN-16:00 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 204.72 | 15-JUL-15:00 | 200.96 | 06-JUL-02:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 158.94 | 13-AUG-13:00 | 207.65 | 30-AUG-18:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 66.05 | 16-SEP-13:00 | 276.30 | 29-SEP-19:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 342.17 | 23-OCT-15:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 664.35 | 17-NOV-09:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1170.32 | 09-DEC-15:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 200.96 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 204.72 | 1187.17 |
Report: PeakSpaceGainsMonthly
For: T N2 APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 1187.17 | 12-JAN-09:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1136.05 | 13-FEB-06:00 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 32.73 | 15-MAR-14:00 | 780.19 | 01-MAR-15:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 630.39 | 16-APR-04:00 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 49.79 | 14-MAY-15:00 | 314.38 | 11-MAY-15:00 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 148.90 | 12-JUN-13:00 | 301.35 | 13-JUN-16:00 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 204.72 | 15-JUL-15:00 | 200.83 | 06-JUL-02:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 158.94 | 13-AUG-13:00 | 207.65 | 30-AUG-18:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 66.05 | 16-SEP-13:00 | 274.97 | 29-SEP-19:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 342.17 | 23-OCT-15:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 664.35 | 17-NOV-09:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1170.32 | 09-DEC-15:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 200.83 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 204.72 | 1187.17 |
Report: PeakSpaceGainsMonthly
For: T S1 APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 1187.17 | 12-JAN-09:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1136.05 | 13-FEB-06:00 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 32.73 | 15-MAR-14:00 | 804.29 | 01-MAR-15:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 630.39 | 16-APR-04:00 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 49.79 | 14-MAY-15:00 | 313.28 | 11-MAY-15:00 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 148.90 | 12-JUN-13:00 | 308.56 | 13-JUN-16:00 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 204.72 | 15-JUL-15:00 | 201.30 | 06-JUL-02:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 158.94 | 13-AUG-13:00 | 207.65 | 30-AUG-18:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 66.05 | 16-SEP-13:00 | 294.55 | 29-SEP-19:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 342.17 | 23-OCT-15:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 664.35 | 17-NOV-09:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1170.32 | 09-DEC-15:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 201.30 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 204.72 | 1187.17 |
Report: PeakSpaceGainsMonthly
For: T S2 APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 1187.17 | 12-JAN-09:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1136.05 | 13-FEB-06:00 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 32.73 | 15-MAR-14:00 | 804.79 | 01-MAR-15:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 630.39 | 16-APR-04:00 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 49.79 | 14-MAY-15:00 | 313.37 | 11-MAY-15:00 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 148.90 | 12-JUN-13:00 | 308.45 | 13-JUN-16:00 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 204.72 | 15-JUL-15:00 | 201.12 | 06-JUL-02:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 158.94 | 13-AUG-13:00 | 207.65 | 30-AUG-18:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 66.05 | 16-SEP-13:00 | 293.18 | 29-SEP-19:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 342.17 | 23-OCT-15:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 664.35 | 17-NOV-09:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1170.32 | 09-DEC-15:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 201.12 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 204.72 | 1187.17 |
Report: PeakSpaceGainsMonthly
For: T CORRIDOR
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 397.10 | 01-JAN-00:10 | 370.63 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 315.96 | 12-JAN-09:00 |
| February | 397.10 | 01-FEB-00:10 | 370.63 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 299.41 | 13-FEB-06:00 |
| March | 397.10 | 01-MAR-00:10 | 370.63 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.02 | 14-MAR-13:00 | 221.23 | 01-MAR-15:00 |
| April | 397.10 | 01-APR-00:10 | 370.63 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 177.06 | 04-APR-17:00 |
| May | 397.10 | 01-MAY-00:10 | 370.63 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.30 | 10-MAY-14:00 | 97.83 | 11-MAY-15:00 |
| June | 397.10 | 01-JUN-00:10 | 370.63 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.79 | 27-JUN-13:00 | 93.02 | 13-JUN-16:00 |
| July | 397.10 | 01-JUL-00:10 | 370.63 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.62 | 15-JUL-15:00 | 67.17 | 06-JUL-02:00 |
| August | 397.10 | 01-AUG-00:10 | 370.63 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.30 | 13-AUG-13:00 | 68.86 | 30-AUG-18:00 |
| September | 397.10 | 01-SEP-00:10 | 370.63 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.60 | 16-SEP-13:00 | 88.91 | 29-SEP-19:00 |
| October | 397.10 | 01-OCT-00:10 | 370.63 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 104.30 | 23-OCT-15:00 |
| November | 397.10 | 01-NOV-00:10 | 370.63 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 183.11 | 17-NOV-09:00 |
| December | 397.10 | 01-DEC-00:10 | 370.63 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 314.03 | 09-DEC-15:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
| Minimum of Months | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.17 | ||||
| Maximum of Months | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.62 | 315.96 |
Report: PeakSpaceGainsMonthly
For: G CORRIDOR
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 397.10 | 01-JAN-00:10 | 370.63 | 01-JAN-00:10 | 208.40 | 01-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 18373.93 | 04-JAN-07:01 |
| February | 397.10 | 01-FEB-00:10 | 370.63 | 01-FEB-00:10 | 208.40 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 20291.48 | 07-FEB-07:01 |
| March | 397.10 | 01-MAR-00:10 | 370.63 | 01-MAR-00:10 | 208.40 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 744.57 | 15-MAR-16:05 | 18600.61 | 07-MAR-07:01 |
| April | 397.10 | 01-APR-00:10 | 370.63 | 01-APR-00:10 | 208.40 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 13334.98 | 17-APR-06:01 |
| May | 397.10 | 01-MAY-00:10 | 370.63 | 01-MAY-00:10 | 208.40 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 385.98 | 10-MAY-16:05 | 10141.27 | 01-MAY-06:01 |
| June | 397.10 | 01-JUN-00:10 | 370.63 | 01-JUN-00:10 | 208.40 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1198.47 | 17-JUN-16:03 | 8964.43 | 14-JUN-06:01 |
| July | 397.10 | 01-JUL-00:10 | 370.63 | 01-JUL-00:10 | 208.40 | 01-JUL-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1357.26 | 16-JUL-16:03 | 6741.19 | 03-JUL-06:01 |
| August | 397.10 | 01-AUG-00:10 | 370.63 | 01-AUG-00:10 | 208.40 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1202.21 | 18-AUG-16:02 | 7497.33 | 01-AUG-06:01 |
| September | 397.10 | 01-SEP-00:10 | 370.63 | 01-SEP-00:10 | 208.40 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 65.57 | 16-SEP-13:00 | 9927.46 | 05-SEP-06:01 |
| October | 397.10 | 01-OCT-00:10 | 370.63 | 01-OCT-00:10 | 208.40 | 01-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 13549.62 | 17-OCT-06:01 |
| November | 397.10 | 01-NOV-00:10 | 370.63 | 01-NOV-00:10 | 208.40 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 12842.97 | 24-NOV-07:01 |
| December | 397.10 | 01-DEC-00:10 | 370.63 | 01-DEC-00:10 | 208.40 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 20519.14 | 11-DEC-07:01 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 397.10 | 370.63 | 208.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6741.19 | |||||
| Maximum of Months | 397.10 | 370.63 | 208.40 | 0.00 | 0.00 | 0.00 | 0.00 | 1357.26 | 20519.14 |
Report: PeakSpaceGainsMonthly
For: M CORRIDOR
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 397.10 | 01-JAN-00:10 | 370.63 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 256.41 | 12-JAN-09:00 |
| February | 397.10 | 01-FEB-00:10 | 370.63 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 244.22 | 13-FEB-06:00 |
| March | 397.10 | 01-MAR-00:10 | 370.63 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.04 | 14-MAR-14:00 | 175.86 | 01-MAR-15:00 |
| April | 397.10 | 01-APR-00:10 | 370.63 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 143.70 | 04-APR-17:00 |
| May | 397.10 | 01-MAY-00:10 | 370.63 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.62 | 14-MAY-15:00 | 85.36 | 11-MAY-15:00 |
| June | 397.10 | 01-JUN-00:10 | 370.63 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.50 | 27-JUN-13:00 | 78.86 | 13-JUN-16:00 |
| July | 397.10 | 01-JUL-00:10 | 370.63 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.80 | 15-JUL-15:00 | 53.53 | 06-JUL-02:00 |
| August | 397.10 | 01-AUG-00:10 | 370.63 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.07 | 13-AUG-13:00 | 52.55 | 30-AUG-18:00 |
| September | 397.10 | 01-SEP-00:10 | 370.63 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.96 | 16-SEP-13:00 | 79.67 | 29-SEP-19:00 |
| October | 397.10 | 01-OCT-00:10 | 370.63 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 87.85 | 23-OCT-15:00 |
| November | 397.10 | 01-NOV-00:10 | 370.63 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 152.51 | 17-NOV-09:00 |
| December | 397.10 | 01-DEC-00:10 | 370.63 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 251.91 | 09-DEC-15:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
| Minimum of Months | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.55 | ||||
| Maximum of Months | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.80 | 256.41 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: G SW APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 338.45 | 15-JAN-15:30 | 0.00 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 193.48 |
| February | 166.83 | 28-FEB-16:10 | 0.00 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 288.83 |
| March | 416.83 | 08-MAR-16:40 | 0.00 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 154.33 |
| April | 418.53 | 25-APR-18:30 | 237.50 | 138.88 | 547.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 227.08 |
| May | 428.08 | 06-MAY-22:10 | 237.50 | 21.70 | 341.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 1501.45 | 27-JUN-16:40 | 0.00 | 86.80 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 43.88 | 0.00 |
| July | 1702.70 | 18-JUL-17:20 | 475.00 | 234.36 | 1177.25 | 0.00 | 0.00 | 0.00 | 0.00 | 33.49 | 0.00 |
| August | 2019.75 | 10-AUG-16:04 | 0.00 | 434.00 | 2943.11 | 0.00 | 0.00 | 0.00 | 0.00 | 70.42 | 0.00 |
| September | 2122.72 | 21-SEP-16:04 | 0.00 | 434.00 | 2943.11 | 0.00 | 0.00 | 0.00 | 0.00 | 8.47 | 0.00 |
| October | 1177.91 | 11-OCT-16:07 | 0.00 | 260.40 | 1765.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.43 |
| November | 540.07 | 01-NOV-23:50 | 237.50 | 8.68 | 264.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 105.59 |
| December | 388.85 | 16-DEC-14:00 | 118.75 | 17.36 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 125.36 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 166.83 | 0.00 | 8.68 | 264.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 2122.72 | 475.00 | 434.00 | 2943.11 | 0.00 | 0.00 | 0.00 | 0.00 | 70.42 | 288.83 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: G NW APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 0.00 | 01-JAN-00:10 | 237.50 | 8.68 | 264.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 220.29 |
| February | 0.00 | 01-FEB-00:10 | 237.50 | 8.68 | 264.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 270.12 |
| March | 357.55 | 16-MAR-16:55 | 247.00 | 173.60 | 1177.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 122.83 |
| April | 369.18 | 29-APR-18:50 | 206.62 | 138.88 | 547.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83.31 |
| May | 407.62 | 27-MAY-03:50 | 237.50 | 26.04 | 223.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 1409.72 | 27-JUN-17:20 | 413.25 | 234.36 | 1177.25 | 0.00 | 0.00 | 0.00 | 0.00 | 43.55 | 0.00 |
| July | 1566.37 | 18-JUL-17:50 | 206.62 | 117.18 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 23.34 | 0.00 |
| August | 1660.47 | 10-AUG-17:30 | 413.25 | 234.36 | 1177.25 | 0.00 | 0.00 | 0.00 | 0.00 | 40.10 | 0.00 |
| September | 1270.86 | 16-SEP-16:10 | 123.50 | 86.80 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 41.28 | 0.00 |
| October | 501.13 | 03-OCT-05:10 | 1187.50 | 303.79 | 1589.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.58 |
| November | 341.41 | 01-NOV-16:03 | 1235.00 | 867.99 | 5886.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 109.90 |
| December | 0.00 | 01-DEC-00:10 | 237.50 | 8.68 | 264.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 216.05 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 0.00 | 123.50 | 8.68 | 223.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 1660.47 | 1235.00 | 867.99 | 5886.23 | 0.00 | 0.00 | 0.00 | 0.00 | 43.55 | 270.12 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: OFFICE
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 1194.47 | 06-JAN-08:03 | 4512.06 | 5829.16 | 5886.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 206.96 |
| February | 1256.31 | 07-FEB-07:03 | 0.00 | 1165.83 | 2943.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 561.80 |
| March | 1150.12 | 07-MAR-07:03 | 0.00 | 1165.83 | 2943.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 212.42 |
| April | 792.83 | 17-APR-07:03 | 4512.06 | 5829.16 | 5886.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 150.51 |
| May | 1442.82 | 17-MAY-08:65 | 902.41 | 1165.83 | 1177.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.41 |
| June | 5573.42 | 16-JUN-08:62 | 1804.82 | 2331.66 | 2354.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.48 |
| July | 5788.64 | 06-JUL-08:62 | 2256.03 | 2914.58 | 2943.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86.44 |
| August | 5741.78 | 03-AUG-08:62 | 2256.03 | 2914.58 | 2943.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.24 |
| September | 5908.90 | 11-SEP-08:62 | 2256.03 | 2914.58 | 2943.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96.71 |
| October | 2934.46 | 12-OCT-08:63 | 1353.62 | 1748.75 | 1765.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 177.32 |
| November | 794.58 | 24-NOV-08:03 | 4512.06 | 5829.16 | 5886.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80.11 |
| December | 1276.35 | 11-DEC-07:03 | 0.00 | 1165.83 | 2943.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 185.51 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 792.83 | 0.00 | 1165.83 | 1177.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.24 | |
| Maximum of Months | 5908.90 | 4512.06 | 5829.16 | 5886.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 561.80 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: G NE APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 0.00 | 01-JAN-00:10 | 237.50 | 8.68 | 264.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 220.29 |
| February | 0.00 | 01-FEB-00:10 | 237.50 | 8.68 | 264.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 270.12 |
| March | 359.13 | 16-MAR-16:55 | 247.00 | 173.60 | 1177.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 123.35 |
| April | 368.98 | 29-APR-18:50 | 206.62 | 138.88 | 547.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83.27 |
| May | 406.03 | 23-MAY-03:10 | 237.50 | 26.04 | 223.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 95.72 |
| June | 1141.07 | 27-JUN-13:00 | 59.38 | 17.36 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 126.15 | 0.00 |
| July | 1424.76 | 21-JUL-16:25 | 247.00 | 173.60 | 1177.25 | 0.00 | 0.00 | 0.00 | 0.00 | 60.17 | 0.00 |
| August | 1383.81 | 09-AUG-16:04 | 617.50 | 434.00 | 2943.11 | 0.00 | 0.00 | 0.00 | 0.00 | 56.14 | 0.00 |
| September | 1112.22 | 16-SEP-16:10 | 123.50 | 86.80 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 41.28 | 0.00 |
| October | 499.95 | 03-OCT-05:10 | 1187.50 | 303.79 | 1589.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.36 |
| November | 341.42 | 01-NOV-16:07 | 1235.00 | 867.99 | 5886.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 109.90 |
| December | 0.00 | 01-DEC-00:10 | 237.50 | 8.68 | 264.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 216.05 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 0.00 | 59.38 | 8.68 | 223.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 1424.76 | 1235.00 | 867.99 | 5886.23 | 0.00 | 0.00 | 0.00 | 0.00 | 126.15 | 270.12 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: G N1 APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 0.00 | 01-JAN-00:10 | 237.50 | 8.68 | 264.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 132.87 |
| February | 0.00 | 01-FEB-00:10 | 237.50 | 8.68 | 264.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 162.93 |
| March | 369.88 | 16-MAR-16:55 | 247.00 | 173.60 | 1177.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.51 |
| April | 371.53 | 29-APR-18:50 | 206.62 | 138.88 | 547.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.55 |
| May | 424.99 | 27-MAY-04:00 | 237.50 | 26.04 | 223.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 970.98 | 27-JUN-17:40 | 206.62 | 117.18 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 22.57 | 0.00 |
| July | 1153.68 | 21-JUL-17:05 | 413.25 | 234.36 | 1177.25 | 0.00 | 0.00 | 0.00 | 0.00 | 41.49 | 0.00 |
| August | 1103.54 | 09-AUG-17:05 | 413.25 | 234.36 | 1177.25 | 0.00 | 0.00 | 0.00 | 0.00 | 25.03 | 0.00 |
| September | 938.90 | 16-SEP-16:20 | 123.50 | 86.80 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 23.69 | 0.00 |
| October | 544.15 | 23-OCT-22:00 | 237.50 | 52.08 | 417.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 115.60 |
| November | 383.65 | 01-NOV-18:10 | 206.62 | 138.88 | 547.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77.06 |
| December | 120.96 | 01-DEC-13:00 | 59.38 | 17.36 | 406.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 95.14 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 0.00 | 59.38 | 8.68 | 223.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 1153.68 | 413.25 | 234.36 | 1177.25 | 0.00 | 0.00 | 0.00 | 0.00 | 41.49 | 162.93 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: G N2 APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 0.00 | 01-JAN-00:10 | 237.50 | 8.68 | 264.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 132.87 |
| February | 0.00 | 01-FEB-00:10 | 237.50 | 8.68 | 264.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 162.93 |
| March | 370.16 | 16-MAR-16:55 | 247.00 | 173.60 | 1177.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.56 |
| April | 371.53 | 29-APR-18:50 | 206.62 | 138.88 | 547.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.55 |
| May | 425.19 | 27-MAY-04:00 | 237.50 | 26.04 | 223.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 964.41 | 27-JUN-17:40 | 206.62 | 117.18 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 22.57 | 0.00 |
| July | 1153.85 | 21-JUL-17:05 | 413.25 | 234.36 | 1177.25 | 0.00 | 0.00 | 0.00 | 0.00 | 41.49 | 0.00 |
| August | 1099.76 | 09-AUG-17:05 | 413.25 | 234.36 | 1177.25 | 0.00 | 0.00 | 0.00 | 0.00 | 25.03 | 0.00 |
| September | 937.75 | 16-SEP-16:20 | 123.50 | 86.80 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 23.69 | 0.00 |
| October | 544.11 | 23-OCT-22:00 | 237.50 | 52.08 | 417.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 115.59 |
| November | 383.74 | 01-NOV-18:10 | 206.62 | 138.88 | 547.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77.07 |
| December | 121.59 | 01-DEC-13:00 | 59.38 | 17.36 | 406.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 95.14 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 0.00 | 59.38 | 8.68 | 223.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 1153.85 | 413.25 | 234.36 | 1177.25 | 0.00 | 0.00 | 0.00 | 0.00 | 41.49 | 162.93 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: G S1 APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 482.25 | 15-JAN-13:40 | 118.75 | 17.36 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 138.38 |
| February | 312.71 | 28-FEB-15:10 | 0.00 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 179.37 |
| March | 487.17 | 17-MAR-18:50 | 237.50 | 138.88 | 547.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 186.30 |
| April | 470.20 | 23-APR-23:40 | 237.50 | 8.68 | 264.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91.87 |
| May | 446.09 | 06-MAY-23:00 | 237.50 | 21.70 | 341.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 1115.47 | 27-JUN-13:00 | 0.00 | 17.36 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 76.09 | 0.00 |
| July | 1369.84 | 21-JUL-13:30 | 0.00 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 50.55 | 0.00 |
| August | 1481.69 | 10-AUG-15:10 | 0.00 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 49.15 | 0.00 |
| September | 1664.83 | 21-SEP-15:10 | 0.00 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 7.80 | 0.00 |
| October | 990.69 | 11-OCT-15:10 | 0.00 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.05 |
| November | 596.28 | 18-NOV-20:00 | 237.50 | 138.88 | 547.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.80 |
| December | 562.40 | 17-DEC-13:30 | 118.75 | 17.36 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 199.44 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 312.71 | 0.00 | 8.68 | 264.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 1664.83 | 237.50 | 138.88 | 547.42 | 0.00 | 0.00 | 0.00 | 0.00 | 76.09 | 199.44 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: G S2 APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 407.57 | 15-JAN-14:30 | 118.75 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 133.94 |
| February | 255.64 | 28-FEB-15:10 | 0.00 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 179.37 |
| March | 497.12 | 17-MAR-19:00 | 237.50 | 138.88 | 547.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 184.20 |
| April | 459.33 | 23-APR-23:00 | 237.50 | 21.70 | 341.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 118.88 |
| May | 446.93 | 06-MAY-23:00 | 237.50 | 21.70 | 341.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 1177.04 | 27-JUN-13:00 | 0.00 | 17.36 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 76.09 | 0.00 |
| July | 1447.90 | 21-JUL-13:30 | 0.00 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 50.55 | 0.00 |
| August | 1577.17 | 13-AUG-15:20 | 237.50 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 73.24 | 0.00 |
| September | 1715.28 | 21-SEP-15:10 | 0.00 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 7.80 | 0.00 |
| October | 1016.71 | 11-OCT-15:10 | 0.00 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.05 |
| November | 583.86 | 18-NOV-19:20 | 237.50 | 138.88 | 547.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.91 |
| December | 475.92 | 16-DEC-12:30 | 118.75 | 17.36 | 406.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.34 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 255.64 | 0.00 | 17.36 | 341.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 1715.28 | 237.50 | 138.88 | 547.42 | 0.00 | 0.00 | 0.00 | 0.00 | 76.09 | 184.20 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: M SW APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 681.29 | 06-JAN-15:20 | 0.00 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 188.57 |
| February | 664.29 | 28-FEB-17:25 | 0.00 | 173.60 | 1177.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 359.11 |
| March | 1370.59 | 15-MAR-13:50 | 0.00 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 39.11 | 0.00 |
| April | 1197.29 | 09-APR-16:03 | 1425.00 | 520.80 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82.33 |
| May | 1788.50 | 14-MAY-14:30 | 0.00 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 44.63 | 0.00 |
| June | 2263.59 | 12-JUN-16:10 | 0.00 | 347.20 | 2354.49 | 0.00 | 0.00 | 0.00 | 0.00 | 83.86 | 0.00 |
| July | 2333.25 | 18-JUL-17:20 | 475.00 | 234.36 | 1177.25 | 0.00 | 0.00 | 0.00 | 0.00 | 47.88 | 0.00 |
| August | 2573.90 | 10-AUG-16:10 | 0.00 | 434.00 | 2943.11 | 0.00 | 0.00 | 0.00 | 0.00 | 100.81 | 0.00 |
| September | 2718.34 | 21-SEP-16:10 | 0.00 | 434.00 | 2943.11 | 0.00 | 0.00 | 0.00 | 0.00 | 12.05 | 0.00 |
| October | 1959.92 | 11-OCT-16:10 | 0.00 | 260.40 | 1765.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.57 |
| November | 604.47 | 18-NOV-20:30 | 237.50 | 138.88 | 523.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 121.34 |
| December | 601.87 | 04-DEC-15:30 | 0.00 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 436.53 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 601.87 | 0.00 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 2718.34 | 1425.00 | 520.80 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 100.81 | 436.53 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: M NW APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 11.60 | 15-JAN-16:10 | 71.25 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 240.51 |
| February | 10.55 | 22-FEB-17:03 | 741.00 | 520.80 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 339.33 |
| March | 725.56 | 15-MAR-17:10 | 206.62 | 117.18 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 6.03 | 0.00 |
| April | 613.36 | 22-APR-06:00 | 237.50 | 60.76 | 317.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 1616.30 | 31-MAY-18:00 | 206.62 | 117.18 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.00 |
| June | 2120.08 | 27-JUN-17:05 | 413.25 | 234.36 | 1177.25 | 0.00 | 0.00 | 0.00 | 0.00 | 66.32 | 0.00 |
| July | 2179.03 | 18-JUL-17:40 | 206.62 | 117.18 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 37.91 | 0.00 |
| August | 2153.50 | 10-AUG-17:17 | 619.87 | 351.55 | 1765.87 | 0.00 | 0.00 | 0.00 | 0.00 | 62.25 | 0.00 |
| September | 1661.71 | 21-SEP-16:30 | 247.00 | 173.60 | 1177.25 | 0.00 | 0.00 | 0.00 | 0.00 | 9.95 | 0.00 |
| October | 532.31 | 23-OCT-20:00 | 206.62 | 138.88 | 523.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 304.61 |
| November | 408.80 | 03-NOV-17:25 | 413.25 | 234.36 | 1177.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 104.35 |
| December | 20.00 | 01-DEC-13:00 | 59.38 | 17.36 | 406.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 227.31 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 10.55 | 59.38 | 17.36 | 317.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 2179.03 | 741.00 | 520.80 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 66.32 | 339.33 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: M SE APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 573.51 | 06-JAN-13:40 | 0.00 | 17.36 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 249.09 |
| February | 675.00 | 08-FEB-13:00 | 0.00 | 17.36 | 406.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 396.63 |
| March | 1395.84 | 15-MAR-13:30 | 0.00 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 33.12 | 0.00 |
| April | 1070.25 | 22-APR-13:30 | 118.75 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86.74 |
| May | 1514.82 | 14-MAY-14:10 | 0.00 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 32.83 | 0.00 |
| June | 2179.15 | 12-JUN-13:00 | 0.00 | 17.36 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 188.01 | 0.00 |
| July | 2251.53 | 21-JUL-13:30 | 0.00 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 120.09 | 0.00 |
| August | 2294.93 | 18-AUG-13:30 | 0.00 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 100.32 | 0.00 |
| September | 2383.40 | 21-SEP-13:30 | 0.00 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 15.89 | 0.00 |
| October | 1685.99 | 11-OCT-12:30 | 0.00 | 17.36 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.26 |
| November | 599.49 | 18-NOV-20:10 | 237.50 | 138.88 | 523.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 106.93 |
| December | 583.83 | 17-DEC-11:40 | 118.75 | 17.36 | 412.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 561.40 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 573.51 | 0.00 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 2383.40 | 237.50 | 138.88 | 523.87 | 0.00 | 0.00 | 0.00 | 0.00 | 188.01 | 561.40 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: M NE APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 0.00 | 01-JAN-00:10 | 237.50 | 8.68 | 264.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 316.86 |
| February | 0.00 | 01-FEB-00:10 | 237.50 | 8.68 | 264.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 388.51 |
| March | 676.88 | 15-MAR-16:20 | 123.50 | 86.80 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 8.65 | 0.00 |
| April | 619.22 | 22-APR-06:00 | 237.50 | 60.76 | 317.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 1178.50 | 23-MAY-16:10 | 247.00 | 173.60 | 1177.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.02 |
| June | 1895.23 | 12-JUN-11:00 | 59.38 | 17.36 | 412.04 | 0.00 | 0.00 | 0.00 | 0.00 | 171.00 | 0.00 |
| July | 1857.61 | 21-JUL-10:30 | 59.38 | 17.36 | 412.04 | 0.00 | 0.00 | 0.00 | 0.00 | 103.57 | 0.00 |
| August | 1714.48 | 09-AUG-16:04 | 617.50 | 434.00 | 2943.11 | 0.00 | 0.00 | 0.00 | 0.00 | 80.38 | 0.00 |
| September | 1348.72 | 16-SEP-16:10 | 123.50 | 86.80 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 58.87 | 0.00 |
| October | 537.00 | 23-OCT-21:25 | 475.00 | 104.17 | 835.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 272.05 |
| November | 432.66 | 01-NOV-21:00 | 237.50 | 95.48 | 500.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 48.57 | 16-DEC-12:00 | 59.38 | 17.36 | 412.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 0.00 | 59.38 | 8.68 | 264.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 1895.23 | 617.50 | 434.00 | 2943.11 | 0.00 | 0.00 | 0.00 | 0.00 | 171.00 | 388.51 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: M N1 APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 212.01 | 17-JAN-20:00 | 206.62 | 138.88 | 547.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 156.90 |
| February | 190.25 | 22-FEB-19:00 | 206.62 | 117.18 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 199.42 |
| March | 633.49 | 18-MAR-10:00 | 59.38 | 17.36 | 406.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 322.01 |
| April | 624.09 | 22-APR-06:00 | 237.50 | 60.76 | 317.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 992.99 | 25-MAY-16:04 | 864.50 | 607.59 | 4120.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96.08 |
| June | 1338.60 | 27-JUN-17:50 | 206.62 | 117.18 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 29.36 | 0.00 |
| July | 1403.67 | 21-JUL-16:30 | 247.00 | 173.60 | 1177.25 | 0.00 | 0.00 | 0.00 | 0.00 | 51.96 | 0.00 |
| August | 1311.75 | 09-AUG-16:17 | 494.00 | 347.20 | 2354.49 | 0.00 | 0.00 | 0.00 | 0.00 | 46.71 | 0.00 |
| September | 1100.42 | 16-SEP-16:20 | 123.50 | 86.80 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 33.77 | 0.00 |
| October | 621.76 | 24-OCT-03:30 | 237.50 | 26.04 | 223.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74.78 |
| November | 504.47 | 01-NOV-21:00 | 237.50 | 95.48 | 500.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 233.31 | 01-DEC-13:10 | 59.38 | 17.36 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 168.55 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 190.25 | 59.38 | 17.36 | 223.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 1403.67 | 864.50 | 607.59 | 4120.36 | 0.00 | 0.00 | 0.00 | 0.00 | 51.96 | 322.01 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: M N2 APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 211.62 | 17-JAN-20:00 | 206.62 | 138.88 | 547.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 156.90 |
| February | 188.19 | 22-FEB-19:00 | 206.62 | 117.18 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 199.42 |
| March | 633.69 | 18-MAR-10:00 | 59.38 | 17.36 | 406.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 322.11 |
| April | 623.99 | 22-APR-06:00 | 237.50 | 60.76 | 317.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 1026.86 | 25-MAY-16:04 | 864.50 | 607.59 | 4120.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96.08 |
| June | 1330.26 | 27-JUN-17:40 | 206.62 | 117.18 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 32.11 | 0.00 |
| July | 1405.13 | 21-JUL-16:30 | 247.00 | 173.60 | 1177.25 | 0.00 | 0.00 | 0.00 | 0.00 | 51.96 | 0.00 |
| August | 1307.62 | 09-AUG-16:17 | 494.00 | 347.20 | 2354.49 | 0.00 | 0.00 | 0.00 | 0.00 | 46.71 | 0.00 |
| September | 1097.54 | 16-SEP-16:20 | 123.50 | 86.80 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 33.77 | 0.00 |
| October | 624.54 | 24-OCT-03:40 | 237.50 | 26.04 | 223.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.29 |
| November | 504.67 | 01-NOV-21:00 | 237.50 | 95.48 | 500.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 233.38 | 01-DEC-13:10 | 59.38 | 17.36 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 168.59 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 188.19 | 59.38 | 17.36 | 223.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 1405.13 | 864.50 | 607.59 | 4120.36 | 0.00 | 0.00 | 0.00 | 0.00 | 51.96 | 322.11 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: M S1 APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 744.79 | 06-JAN-12:10 | 0.00 | 17.36 | 406.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 135.26 |
| February | 853.87 | 08-FEB-13:00 | 0.00 | 17.36 | 406.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 240.67 |
| March | 1227.40 | 15-MAR-13:30 | 0.00 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 19.98 | 0.00 |
| April | 1020.20 | 09-APR-16:03 | 1425.00 | 520.80 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.66 |
| May | 1340.62 | 14-MAY-14:10 | 0.00 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 19.80 | 0.00 |
| June | 1589.44 | 12-JUN-13:20 | 0.00 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 109.26 | 0.00 |
| July | 1711.97 | 21-JUL-13:30 | 0.00 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 72.44 | 0.00 |
| August | 1798.38 | 18-AUG-14:10 | 0.00 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 61.86 | 0.00 |
| September | 2082.47 | 21-SEP-14:10 | 0.00 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 11.93 | 0.00 |
| October | 1605.10 | 11-OCT-14:30 | 0.00 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.68 |
| November | 660.56 | 18-NOV-22:00 | 237.50 | 95.48 | 500.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.80 |
| December | 672.81 | 04-DEC-16:30 | 0.00 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 244.93 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 660.56 | 0.00 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 2082.47 | 1425.00 | 520.80 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 109.26 | 244.93 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: M S2 APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 747.24 | 06-JAN-12:00 | 0.00 | 17.36 | 412.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 131.58 |
| February | 854.30 | 08-FEB-13:00 | 0.00 | 17.36 | 406.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 240.79 |
| March | 1232.63 | 15-MAR-13:30 | 0.00 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 19.98 | 0.00 |
| April | 1030.15 | 09-APR-16:03 | 1425.00 | 520.80 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.66 |
| May | 1336.79 | 14-MAY-14:10 | 0.00 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 19.80 | 0.00 |
| June | 1595.47 | 12-JUN-13:20 | 0.00 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 109.26 | 0.00 |
| July | 1717.61 | 21-JUL-13:30 | 0.00 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 72.44 | 0.00 |
| August | 1802.82 | 18-AUG-14:10 | 0.00 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 61.86 | 0.00 |
| September | 2085.73 | 21-SEP-14:10 | 0.00 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 11.93 | 0.00 |
| October | 1611.73 | 11-OCT-14:30 | 0.00 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.68 |
| November | 660.50 | 18-NOV-22:00 | 237.50 | 95.48 | 500.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.80 |
| December | 672.65 | 04-DEC-16:30 | 0.00 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 244.88 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 660.50 | 0.00 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 2085.73 | 1425.00 | 520.80 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 109.26 | 244.88 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: T SW APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 581.90 | 15-JAN-17:45 | 475.00 | 173.60 | 1177.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 430.36 |
| February | 673.97 | 28-FEB-17:01 | 0.00 | 867.99 | 5886.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 534.96 |
| March | 2243.05 | 15-MAR-13:50 | 0.00 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 50.65 | 0.00 |
| April | 1723.50 | 22-APR-15:00 | 0.00 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 124.52 |
| May | 2490.14 | 14-MAY-14:40 | 0.00 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 65.63 | 0.00 |
| June | 3132.38 | 12-JUN-15:30 | 0.00 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 158.37 | 0.00 |
| July | 3220.59 | 18-JUL-16:15 | 0.00 | 347.20 | 2354.49 | 0.00 | 0.00 | 0.00 | 0.00 | 83.77 | 0.00 |
| August | 3465.12 | 10-AUG-16:04 | 0.00 | 434.00 | 2943.11 | 0.00 | 0.00 | 0.00 | 0.00 | 132.33 | 0.00 |
| September | 3438.11 | 21-SEP-15:30 | 0.00 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 21.17 | 0.00 |
| October | 2551.62 | 11-OCT-15:30 | 0.00 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.17 |
| November | 598.02 | 03-NOV-15:10 | 0.00 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 229.31 |
| December | 567.58 | 17-DEC-13:40 | 118.75 | 17.36 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 650.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 567.58 | 0.00 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 3465.12 | 475.00 | 867.99 | 5886.23 | 0.00 | 0.00 | 0.00 | 0.00 | 158.37 | 650.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: T NW APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 0.00 | 01-JAN-00:10 | 237.50 | 8.68 | 264.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 419.89 |
| February | 0.00 | 01-FEB-00:10 | 237.50 | 8.68 | 264.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 514.75 |
| March | 1359.55 | 15-MAR-16:30 | 123.50 | 86.80 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 10.66 | 0.00 |
| April | 799.60 | 09-APR-16:03 | 741.00 | 520.80 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 109.40 |
| May | 1960.55 | 31-MAY-18:00 | 206.62 | 117.18 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.38 |
| June | 2886.01 | 12-JUN-16:05 | 494.00 | 347.20 | 2354.49 | 0.00 | 0.00 | 0.00 | 0.00 | 109.70 | 0.00 |
| July | 2956.36 | 18-JUL-17:15 | 413.25 | 234.36 | 1177.25 | 0.00 | 0.00 | 0.00 | 0.00 | 62.66 | 0.00 |
| August | 2915.79 | 10-AUG-16:30 | 123.50 | 86.80 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 116.79 | 0.00 |
| September | 2177.22 | 16-SEP-16:10 | 123.50 | 86.80 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 76.68 | 0.00 |
| October | 1004.90 | 11-OCT-16:30 | 247.00 | 173.60 | 1177.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.04 |
| November | 359.30 | 03-NOV-16:03 | 1235.00 | 867.99 | 5886.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 130.54 |
| December | 0.00 | 01-DEC-00:10 | 237.50 | 8.68 | 264.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 412.21 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 0.00 | 123.50 | 8.68 | 264.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 2956.36 | 1235.00 | 867.99 | 5886.23 | 0.00 | 0.00 | 0.00 | 0.00 | 116.79 | 514.75 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: T SE APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 540.56 | 15-JAN-17:12 | 1187.50 | 434.00 | 2943.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 354.99 |
| February | 725.97 | 08-FEB-13:00 | 0.00 | 17.36 | 406.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 525.40 |
| March | 2238.21 | 15-MAR-13:40 | 0.00 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 46.79 | 0.00 |
| April | 1596.86 | 22-APR-13:40 | 118.75 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 118.66 |
| May | 2136.99 | 14-MAY-14:10 | 0.00 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 41.95 | 0.00 |
| June | 3081.40 | 12-JUN-13:00 | 0.00 | 17.36 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 246.86 | 0.00 |
| July | 3194.72 | 21-JUL-13:30 | 0.00 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 157.98 | 0.00 |
| August | 3190.14 | 09-AUG-13:30 | 0.00 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 109.32 | 0.00 |
| September | 3015.22 | 21-SEP-13:40 | 0.00 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 22.00 | 0.00 |
| October | 2201.05 | 11-OCT-12:40 | 0.00 | 17.36 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.34 |
| November | 525.02 | 18-NOV-14:00 | 118.75 | 17.36 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 399.15 |
| December | 567.99 | 17-DEC-13:30 | 118.75 | 17.36 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 636.68 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 525.02 | 0.00 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 3194.72 | 1187.50 | 434.00 | 2943.11 | 0.00 | 0.00 | 0.00 | 0.00 | 246.86 | 636.68 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: T NE APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 0.00 | 01-JAN-00:10 | 237.50 | 8.68 | 264.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 419.89 |
| February | 0.00 | 01-FEB-00:10 | 237.50 | 8.68 | 264.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 514.75 |
| March | 1243.12 | 15-MAR-16:20 | 123.50 | 86.80 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 10.98 | 0.00 |
| April | 577.70 | 09-APR-16:03 | 741.00 | 520.80 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 109.40 |
| May | 1531.94 | 14-MAY-15:10 | 71.25 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 71.39 | 0.00 |
| June | 2605.81 | 12-JUN-11:20 | 59.38 | 17.36 | 406.15 | 0.00 | 0.00 | 0.00 | 0.00 | 222.06 | 0.00 |
| July | 2571.93 | 21-JUL-11:00 | 59.38 | 17.36 | 412.04 | 0.00 | 0.00 | 0.00 | 0.00 | 140.68 | 0.00 |
| August | 2348.23 | 09-AUG-15:20 | 71.25 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 109.40 | 0.00 |
| September | 1814.55 | 16-SEP-13:30 | 59.38 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 109.46 | 0.00 |
| October | 501.50 | 11-OCT-16:07 | 370.50 | 260.40 | 1765.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.30 |
| November | 341.32 | 01-NOV-16:03 | 1235.00 | 867.99 | 5886.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 209.90 |
| December | 0.00 | 01-DEC-00:10 | 237.50 | 8.68 | 264.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 412.21 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 0.00 | 59.38 | 8.68 | 264.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 2605.81 | 1235.00 | 867.99 | 5886.23 | 0.00 | 0.00 | 0.00 | 0.00 | 222.06 | 514.75 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: T N1 APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 0.00 | 01-JAN-00:10 | 237.50 | 8.68 | 264.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 253.27 |
| February | 0.00 | 01-FEB-00:10 | 237.50 | 8.68 | 264.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 310.48 |
| March | 1034.05 | 15-MAR-16:30 | 123.50 | 86.80 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 6.43 | 0.00 |
| April | 588.52 | 09-APR-16:03 | 741.00 | 520.80 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.99 |
| May | 1279.06 | 14-MAY-15:20 | 71.25 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 36.78 | 0.00 |
| June | 1928.88 | 12-JUN-16:08 | 494.00 | 347.20 | 2354.49 | 0.00 | 0.00 | 0.00 | 0.00 | 66.17 | 0.00 |
| July | 1945.62 | 21-JUL-16:30 | 247.00 | 173.60 | 1177.25 | 0.00 | 0.00 | 0.00 | 0.00 | 68.20 | 0.00 |
| August | 1888.34 | 09-AUG-16:02 | 617.50 | 434.00 | 2943.11 | 0.00 | 0.00 | 0.00 | 0.00 | 63.66 | 0.00 |
| September | 1455.82 | 16-SEP-16:10 | 123.50 | 86.80 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 46.25 | 0.00 |
| October | 440.25 | 23-OCT-11:50 | 59.38 | 17.36 | 406.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 266.16 |
| November | 341.39 | 01-NOV-16:03 | 1235.00 | 867.99 | 5886.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 126.64 |
| December | 39.80 | 01-DEC-13:00 | 59.38 | 17.36 | 406.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 182.36 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 0.00 | 59.38 | 8.68 | 264.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 1945.62 | 1235.00 | 867.99 | 5886.23 | 0.00 | 0.00 | 0.00 | 0.00 | 68.20 | 310.48 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: T N2 APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 0.00 | 01-JAN-00:10 | 237.50 | 8.68 | 264.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 253.27 |
| February | 0.00 | 01-FEB-00:10 | 237.50 | 8.68 | 264.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 310.48 |
| March | 1036.49 | 15-MAR-16:20 | 123.50 | 86.80 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 6.62 | 0.00 |
| April | 586.70 | 09-APR-16:03 | 741.00 | 520.80 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.99 |
| May | 1269.92 | 14-MAY-15:10 | 71.25 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 43.06 | 0.00 |
| June | 1919.83 | 12-JUN-16:10 | 494.00 | 347.20 | 2354.49 | 0.00 | 0.00 | 0.00 | 0.00 | 66.17 | 0.00 |
| July | 1945.52 | 21-JUL-16:30 | 247.00 | 173.60 | 1177.25 | 0.00 | 0.00 | 0.00 | 0.00 | 68.20 | 0.00 |
| August | 1877.56 | 09-AUG-16:04 | 617.50 | 434.00 | 2943.11 | 0.00 | 0.00 | 0.00 | 0.00 | 63.66 | 0.00 |
| September | 1446.55 | 16-SEP-16:10 | 123.50 | 86.80 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 46.25 | 0.00 |
| October | 444.41 | 23-OCT-12:00 | 59.38 | 17.36 | 406.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 278.43 |
| November | 341.40 | 01-NOV-16:03 | 1235.00 | 867.99 | 5886.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 126.64 |
| December | 40.17 | 01-DEC-13:00 | 59.38 | 17.36 | 406.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 182.36 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 0.00 | 59.38 | 8.68 | 264.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 1945.52 | 1235.00 | 867.99 | 5886.23 | 0.00 | 0.00 | 0.00 | 0.00 | 68.20 | 310.48 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: T S1 APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 726.28 | 06-JAN-13:10 | 0.00 | 17.36 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 201.23 |
| February | 854.44 | 08-FEB-13:10 | 0.00 | 17.36 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 339.77 |
| March | 1956.27 | 15-MAR-13:50 | 0.00 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 30.55 | 0.00 |
| April | 1338.15 | 22-APR-14:10 | 0.00 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.17 |
| May | 1896.42 | 14-MAY-14:10 | 0.00 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 25.30 | 0.00 |
| June | 2377.41 | 12-JUN-13:30 | 0.00 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 140.02 | 0.00 |
| July | 2546.35 | 21-JUL-13:30 | 0.00 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 95.29 | 0.00 |
| August | 2613.73 | 09-AUG-13:50 | 0.00 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 70.12 | 0.00 |
| September | 2684.37 | 21-SEP-14:10 | 0.00 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 15.41 | 0.00 |
| October | 1959.32 | 11-OCT-14:30 | 0.00 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.49 |
| November | 613.65 | 03-NOV-14:30 | 0.00 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 168.49 |
| December | 637.50 | 04-DEC-12:30 | 0.00 | 17.36 | 406.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 494.57 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 613.65 | 0.00 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 2684.37 | 0.00 | 30.38 | 406.15 | 0.00 | 0.00 | 0.00 | 0.00 | 140.02 | 494.57 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: T S2 APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 726.48 | 06-JAN-13:10 | 0.00 | 17.36 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 201.28 |
| February | 855.49 | 08-FEB-13:10 | 0.00 | 17.36 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 340.18 |
| March | 1964.35 | 15-MAR-13:40 | 0.00 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 28.22 | 0.00 |
| April | 1361.64 | 22-APR-14:10 | 0.00 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.17 |
| May | 1894.11 | 14-MAY-14:10 | 0.00 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 25.30 | 0.00 |
| June | 2388.61 | 12-JUN-13:30 | 0.00 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 140.02 | 0.00 |
| July | 2556.51 | 21-JUL-13:30 | 0.00 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 95.29 | 0.00 |
| August | 2620.36 | 09-AUG-13:50 | 0.00 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 70.12 | 0.00 |
| September | 2691.81 | 21-SEP-14:10 | 0.00 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 15.41 | 0.00 |
| October | 1966.63 | 11-OCT-14:30 | 0.00 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.49 |
| November | 630.57 | 03-NOV-14:30 | 0.00 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 168.49 |
| December | 640.64 | 04-DEC-12:40 | 0.00 | 17.36 | 406.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 497.11 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 630.57 | 0.00 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 2691.81 | 0.00 | 30.38 | 406.15 | 0.00 | 0.00 | 0.00 | 0.00 | 140.02 | 497.11 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: T CORRIDOR
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 0.00 | 01-JAN-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.88 |
| February | 0.00 | 01-FEB-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81.51 |
| March | 0.00 | 01-MAR-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.03 |
| April | 0.00 | 01-APR-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.71 |
| May | 0.00 | 01-MAY-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.14 |
| June | 0.00 | 01-JUN-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.54 |
| July | 0.00 | 01-JUL-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.67 |
| August | 0.00 | 01-AUG-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.80 |
| September | 0.00 | 01-SEP-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.96 |
| October | 0.00 | 01-OCT-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.39 |
| November | 0.00 | 01-NOV-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.84 |
| December | 0.00 | 01-DEC-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.64 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
| Minimum of Months | 0.00 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.80 | |
| Maximum of Months | 0.00 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81.51 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: G CORRIDOR
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 0.00 | 01-JAN-00:10 | 397.10 | 370.63 | 56.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.59 |
| February | 0.00 | 01-FEB-00:10 | 397.10 | 370.63 | 56.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.94 |
| March | 0.00 | 01-MAR-00:10 | 397.10 | 370.63 | 56.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.28 |
| April | 0.00 | 01-APR-00:10 | 397.10 | 370.63 | 56.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.93 |
| May | 0.00 | 01-MAY-00:10 | 397.10 | 370.63 | 56.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.10 |
| June | 0.00 | 01-JUN-00:10 | 397.10 | 370.63 | 56.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.86 |
| July | 0.00 | 01-JUL-00:10 | 397.10 | 370.63 | 56.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.03 |
| August | 0.00 | 01-AUG-00:10 | 397.10 | 370.63 | 56.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.06 |
| September | 0.00 | 01-SEP-00:10 | 397.10 | 370.63 | 56.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.79 |
| October | 0.00 | 01-OCT-00:10 | 397.10 | 370.63 | 56.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.06 |
| November | 0.00 | 01-NOV-00:10 | 397.10 | 370.63 | 56.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.49 |
| December | 0.00 | 01-DEC-00:10 | 397.10 | 370.63 | 56.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.62 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 0.00 | 397.10 | 370.63 | 56.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.06 | |
| Maximum of Months | 0.00 | 397.10 | 370.63 | 56.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.94 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: M CORRIDOR
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 0.00 | 01-JAN-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.05 |
| February | 0.00 | 01-FEB-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.35 |
| March | 0.00 | 01-MAR-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.16 |
| April | 0.00 | 01-APR-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.22 |
| May | 0.00 | 01-MAY-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.68 |
| June | 0.00 | 01-JUN-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.89 |
| July | 0.00 | 01-JUL-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.84 |
| August | 0.00 | 01-AUG-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.33 |
| September | 0.00 | 01-SEP-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.13 |
| October | 0.00 | 01-OCT-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.05 |
| November | 0.00 | 01-NOV-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.34 |
| December | 0.00 | 01-DEC-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.02 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
| Minimum of Months | 0.00 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.33 | |
| Maximum of Months | 0.00 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.35 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
| January | 0.106451E+12 | 73010.27 | 31-JAN-18:19 | 0.148971E+12 | 105955.91 | 24-JAN-05:00 |
| February | 0.965333E+11 | 74058.88 | 06-FEB-18:00 | 0.142045E+12 | 123329.04 | 06-FEB-09:00 |
| March | 0.103649E+12 | 72013.53 | 04-MAR-18:30 | 0.772077E+11 | 81776.57 | 07-MAR-04:00 |
| April | 0.968834E+11 | 63387.63 | 20-APR-17:10 | 0.313896E+11 | 61063.43 | 16-APR-03:00 |
| May | 0.100189E+12 | 70745.11 | 26-MAY-17:10 | 0.284661E+10 | 13212.83 | 01-MAY-04:00 |
| June | 0.109957E+12 | 83456.34 | 27-JUN-17:40 | 0.117257E+09 | 5654.84 | 14-JUN-04:40 |
| July | 0.126683E+12 | 81614.44 | 21-JUL-17:10 | 0.00 | 0.00 | 01-JUL-00:10 |
| August | 0.120092E+12 | 89955.36 | 13-AUG-16:10 | 0.00 | 0.00 | 01-AUG-00:10 |
| September | 0.102969E+12 | 75751.50 | 16-SEP-17:30 | 0.560109E+09 | 7777.09 | 30-SEP-05:00 |
| October | 0.968623E+11 | 63551.43 | 14-OCT-17:00 | 0.159231E+11 | 42666.48 | 30-OCT-04:00 |
| November | 0.965038E+11 | 63639.48 | 30-NOV-19:30 | 0.514959E+11 | 51777.93 | 24-NOV-03:00 |
| December | 0.104936E+12 | 68233.48 | 26-DEC-18:00 | 0.141969E+12 | 105356.37 | 26-DEC-08:09 |
| Annual Sum or Average | 0.126171E+13 | 0.612525E+12 | ||||
| Minimum of Months | 0.965038E+11 | 63387.63 | 0.00 | 0.00 | ||
| Maximum of Months | 0.126683E+12 | 89955.36 | 0.148971E+12 | 123329.04 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| INTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [J] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
| January | 0.840929E+10 | 0.525058E+10 | 0.389380E+11 | 0.00 | 0.960747E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.442455E+11 | 0.00 |
| February | 0.760941E+10 | 0.438154E+10 | 0.351823E+11 | 0.00 | 0.892933E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.404307E+11 | 0.00 |
| March | 0.845392E+10 | 0.435289E+10 | 0.389781E+11 | 0.00 | 0.724565E+10 | 0.00 | 0.00 | 0.370977E+09 | 0.00 | 0.00 | 0.00 | 0.442476E+11 | 0.00 |
| April | 0.814762E+10 | 0.370922E+10 | 0.376905E+11 | 0.00 | 0.551787E+10 | 0.00 | 0.00 | 0.341454E+09 | 0.00 | 0.00 | 0.00 | 0.414767E+11 | 0.00 |
| May | 0.843904E+10 | 0.339025E+10 | 0.389647E+11 | 0.00 | 0.549109E+10 | 0.00 | 0.00 | 0.308218E+10 | 0.00 | 0.00 | 0.00 | 0.408217E+11 | 0.00 |
| June | 0.817737E+10 | 0.306746E+10 | 0.377173E+11 | 0.00 | 0.865108E+10 | 0.00 | 0.00 | 0.148048E+11 | 0.00 | 0.00 | 0.00 | 0.375394E+11 | 0.00 |
| July | 0.840929E+10 | 0.325464E+10 | 0.389380E+11 | 0.00 | 0.121554E+11 | 0.00 | 0.00 | 0.265739E+11 | 0.00 | 0.00 | 0.00 | 0.373514E+11 | 0.00 |
| August | 0.845392E+10 | 0.363473E+10 | 0.389781E+11 | 0.00 | 0.106974E+11 | 0.00 | 0.00 | 0.215154E+11 | 0.00 | 0.00 | 0.00 | 0.368130E+11 | 0.00 |
| September | 0.814762E+10 | 0.399572E+10 | 0.376905E+11 | 0.00 | 0.719695E+10 | 0.00 | 0.00 | 0.980089E+10 | 0.00 | 0.00 | 0.00 | 0.361369E+11 | 0.00 |
| October | 0.842417E+10 | 0.464512E+10 | 0.389514E+11 | 0.00 | 0.522333E+10 | 0.00 | 0.00 | 0.698242E+09 | 0.00 | 0.00 | 0.00 | 0.389201E+11 | 0.00 |
| November | 0.814762E+10 | 0.494307E+10 | 0.376905E+11 | 0.00 | 0.612814E+10 | 0.00 | 0.00 | 2693026.84 | 0.00 | 0.00 | 0.00 | 0.395917E+11 | 0.00 |
| December | 0.840929E+10 | 0.537091E+10 | 0.389380E+11 | 0.00 | 0.938264E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.428350E+11 | 0.00 |
| Annual Sum or Average | 0.992286E+11 | 0.499961E+11 | 0.458657E+12 | 0.00 | 0.962264E+11 | 0.00 | 0.00 | 0.771906E+11 | 0.00 | 0.00 | 0.00 | 0.480410E+12 | 0.00 |
| Minimum of Months | 0.760941E+10 | 0.306746E+10 | 0.351823E+11 | 0.00 | 0.522333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.361369E+11 | 0.00 |
| Maximum of Months | 0.845392E+10 | 0.537091E+10 | 0.389781E+11 | 0.00 | 0.121554E+11 | 0.00 | 0.00 | 0.265739E+11 | 0.00 | 0.00 | 0.00 | 0.442476E+11 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| INTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
| January | 0.00 | 0.00 | 0.148971E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.142045E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.772077E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.313896E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.284661E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.117257E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.560109E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.159231E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.514959E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.141969E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.612525E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.148971E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| INTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
| January | 5904.43 | 01-JAN-19:10 | 3183.33 | 01-JAN-00:10 | 22709.69 | 03-JAN-17:10 | 0.00 | 5339.80 | 24-JAN-05:00 | 0.00 | 0.00 | 01-JAN-00:10 |
| February | 5904.43 | 01-FEB-19:10 | 3183.33 | 01-FEB-00:10 | 22709.69 | 01-FEB-17:10 | 0.00 | 5769.23 | 06-FEB-09:00 | 0.00 | 0.00 | 01-FEB-00:10 |
| March | 5904.43 | 01-MAR-19:10 | 3183.33 | 01-MAR-00:10 | 22709.69 | 01-MAR-17:10 | 0.00 | 4503.99 | 07-MAR-04:00 | 0.00 | 0.00 | 01-MAR-00:10 |
| April | 5904.43 | 01-APR-18:10 | 3183.33 | 01-APR-00:10 | 22709.69 | 03-APR-16:10 | 0.00 | 3817.19 | 16-APR-03:00 | 0.00 | 0.00 | 01-APR-00:10 |
| May | 5904.43 | 01-MAY-18:10 | 3183.33 | 01-MAY-00:10 | 22709.69 | 01-MAY-16:10 | 0.00 | 5101.36 | 14-MAY-15:09 | 0.00 | 0.00 | 01-MAY-00:10 |
| June | 5904.43 | 01-JUN-18:10 | 3183.33 | 01-JUN-00:10 | 22709.69 | 01-JUN-16:10 | 0.00 | 7795.67 | 27-JUN-12:00 | 0.00 | 0.00 | 01-JUN-00:10 |
| July | 5904.43 | 01-JUL-18:10 | 3183.33 | 01-JUL-00:10 | 22709.69 | 03-JUL-16:10 | 0.00 | 8020.60 | 19-JUL-15:09 | 0.00 | 0.00 | 01-JUL-00:10 |
| August | 5904.43 | 01-AUG-18:10 | 3183.33 | 01-AUG-00:10 | 22709.69 | 01-AUG-16:10 | 0.00 | 8208.87 | 13-AUG-15:30 | 0.00 | 0.00 | 01-AUG-00:10 |
| September | 5904.43 | 01-SEP-18:10 | 3183.33 | 01-SEP-00:10 | 22709.69 | 01-SEP-16:10 | 0.00 | 6648.86 | 16-SEP-16:10 | 0.00 | 0.00 | 01-SEP-00:10 |
| October | 5904.43 | 01-OCT-18:10 | 3183.33 | 01-OCT-00:10 | 22709.69 | 02-OCT-16:10 | 0.00 | 3847.24 | 11-OCT-15:20 | 0.00 | 0.00 | 01-OCT-00:10 |
| November | 5904.43 | 01-NOV-18:10 | 3183.33 | 01-NOV-00:10 | 22709.69 | 01-NOV-16:10 | 0.00 | 3491.14 | 24-NOV-03:00 | 0.00 | 0.00 | 01-NOV-00:10 |
| December | 5904.43 | 01-DEC-19:10 | 3183.33 | 01-DEC-00:10 | 22709.69 | 01-DEC-17:10 | 0.00 | 5254.43 | 26-DEC-03:00 | 0.00 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 5904.43 | 3183.33 | 22709.69 | 0.00 | 3491.14 | 0.00 | 0.00 | |||||
| Maximum of Months | 5904.43 | 3183.33 | 22709.69 | 0.00 | 8208.87 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| COOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY {Maximum} [W] | HEATRECOVERY:ELECTRICITY {TIMESTAMP} | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
| January | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 41329.81 | 26-JAN-07:49 | 0.00 |
| February | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 42107.34 | 08-FEB-07:40 | 0.00 |
| March | 8253.85 | 15-MAR-14:09 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 40207.42 | 08-MAR-07:19 | 0.00 |
| April | 3432.13 | 09-APR-16:10 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 36321.80 | 18-APR-06:30 | 0.00 |
| May | 11622.93 | 14-MAY-15:09 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 35264.71 | 06-MAY-06:40 | 0.00 |
| June | 23290.00 | 27-JUN-12:00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 32388.10 | 22-JUN-07:00 | 0.00 |
| July | 24142.25 | 19-JUL-15:09 | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 32835.96 | 31-JUL-06:19 | 0.00 |
| August | 23572.13 | 13-AUG-15:20 | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 32999.89 | 28-AUG-06:40 | 0.00 |
| September | 17205.16 | 16-SEP-13:30 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 32331.40 | 29-SEP-07:19 | 0.00 |
| October | 7576.77 | 11-OCT-15:20 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 32481.70 | 14-OCT-06:10 | 0.00 |
| November | 233.29 | 01-NOV-12:30 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 31525.75 | 30-NOV-06:19 | 0.00 |
| December | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 34238.33 | 20-DEC-07:49 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 31525.75 | 0.00 | |||
| Maximum of Months | 24142.25 | 0.00 | 0.00 | 0.00 | 42107.34 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
| January | 73010.27 | 31-JAN-18:19 | 5231.74 | 22609.62 | 3183.33 | 0.00 | 4385.70 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 74058.88 | 06-FEB-18:00 | 5231.74 | 22609.62 | 3183.33 | 0.00 | 5426.95 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 72013.53 | 04-MAR-18:30 | 5231.74 | 22609.62 | 3183.33 | 0.00 | 3390.38 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 63387.63 | 20-APR-17:10 | 5231.74 | 22609.62 | 0.00 | 0.00 | 1997.24 | 0.00 | 0.00 | 1075.67 | 0.00 |
| May | 70745.11 | 26-MAY-17:10 | 5231.74 | 22609.62 | 0.00 | 0.00 | 4021.79 | 0.00 | 0.00 | 7646.93 | 0.00 |
| June | 83456.34 | 27-JUN-17:40 | 5231.74 | 22609.62 | 0.00 | 0.00 | 7335.16 | 0.00 | 0.00 | 19477.59 | 0.00 |
| July | 81614.44 | 21-JUL-17:10 | 5231.74 | 22609.62 | 0.00 | 0.00 | 7420.79 | 0.00 | 0.00 | 20336.41 | 0.00 |
| August | 89955.36 | 13-AUG-16:10 | 4289.87 | 22609.62 | 0.00 | 0.00 | 8030.62 | 0.00 | 0.00 | 22738.48 | 0.00 |
| September | 75751.50 | 16-SEP-17:30 | 5231.74 | 22609.62 | 0.00 | 0.00 | 6225.78 | 0.00 | 0.00 | 15472.41 | 0.00 |
| October | 63551.43 | 14-OCT-17:00 | 5231.74 | 22609.62 | 3183.33 | 0.00 | 1845.94 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 63639.48 | 30-NOV-19:30 | 5904.43 | 20531.10 | 3183.33 | 0.00 | 2775.51 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 68233.48 | 26-DEC-18:00 | 5231.74 | 22609.62 | 3183.33 | 0.00 | 4256.37 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
| Minimum of Months | 63387.63 | 4289.87 | 20531.10 | 0.00 | 0.00 | 1845.94 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 89955.36 | 5904.43 | 22609.62 | 3183.33 | 0.00 | 8030.62 | 0.00 | 0.00 | 22738.48 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| INTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | |
| January | 0.00 | 0.00 | 105955.91 | 24-JAN-05:00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 123329.04 | 06-FEB-09:00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 81776.57 | 07-MAR-04:00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 61063.43 | 16-APR-03:00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 13212.83 | 01-MAY-04:00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 5654.84 | 14-JUN-04:40 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 7777.09 | 30-SEP-05:00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 42666.48 | 30-OCT-04:00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 51777.93 | 24-NOV-03:00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 105356.37 | 26-DEC-08:09 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 123329.04 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: G SW APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: G NW APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: OFFICE
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: G NE APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: G N1 APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: G N2 APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: G S1 APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: G S2 APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: M SW APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: M NW APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: M SE APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: M NE APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: M N1 APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: M N2 APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: M S1 APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: M S2 APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: T SW APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: T NW APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: T SE APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: T NE APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: T N1 APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: T N2 APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: T S1 APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: T S2 APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: T CORRIDOR
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: G CORRIDOR
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: M CORRIDOR
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: G SW APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 533.00 | 21.10 | 528.00 | 21.10 | 528.00 | 21.10 |
| February | 473.00 | 21.10 | 472.17 | 21.10 | 472.17 | 21.10 |
| March | 506.00 | 21.17 | 402.50 | 21.14 | 402.50 | 21.13 |
| April | 510.00 | 21.23 | 219.67 | 21.19 | 219.67 | 21.17 |
| May | 514.83 | 21.96 | 19.17 | 21.93 | 19.17 | 21.90 |
| June | 224.67 | 23.45 | 178.33 | 23.68 | 46.67 | 23.70 |
| July | 115.17 | 23.99 | 462.17 | 24.00 | 112.67 | 24.00 |
| August | 49.67 | 23.93 | 342.33 | 23.99 | 43.00 | 23.99 |
| September | 130.83 | 23.40 | 199.00 | 23.76 | 19.83 | 23.77 |
| October | 510.33 | 22.05 | 9.83 | 22.03 | 9.83 | 22.01 |
| November | 510.00 | 21.22 | 192.17 | 21.19 | 192.17 | 21.17 |
| December | 533.00 | 21.10 | 519.50 | 21.10 | 519.50 | 21.10 |
| Annual Sum or Average | 4610.50 | 21.62 | 3544.83 | 21.81 | 2585.17 | 21.70 |
| Minimum of Months | 49.67 | 21.10 | 9.83 | 21.10 | 9.83 | 21.10 |
| Maximum of Months | 533.00 | 23.99 | 528.00 | 24.00 | 528.00 | 24.00 |
Report: ComfortReportSimple55Monthly
For: G NW APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 744.00 | 21.10 | 739.17 | 21.10 | 739.17 | 21.10 |
| February | 672.00 | 21.10 | 672.00 | 21.10 | 672.00 | 21.10 |
| March | 744.00 | 21.16 | 605.33 | 21.13 | 605.33 | 21.12 |
| April | 720.00 | 21.13 | 434.33 | 21.12 | 434.33 | 21.11 |
| May | 744.00 | 21.67 | 89.83 | 21.61 | 89.83 | 21.56 |
| June | 367.33 | 23.40 | 258.67 | 23.63 | 78.33 | 23.66 |
| July | 163.67 | 23.99 | 616.67 | 24.00 | 160.50 | 24.00 |
| August | 96.33 | 23.92 | 432.83 | 23.98 | 75.67 | 23.99 |
| September | 334.50 | 23.36 | 194.17 | 23.59 | 35.67 | 23.62 |
| October | 744.00 | 21.59 | 63.00 | 21.55 | 63.00 | 21.52 |
| November | 720.00 | 21.12 | 438.50 | 21.11 | 438.50 | 21.11 |
| December | 744.00 | 21.10 | 731.00 | 21.10 | 731.00 | 21.10 |
| Annual Sum or Average | 6793.83 | 21.57 | 5275.50 | 21.73 | 4123.33 | 21.63 |
| Minimum of Months | 96.33 | 21.10 | 63.00 | 21.10 | 35.67 | 21.10 |
| Maximum of Months | 744.00 | 23.99 | 739.17 | 24.00 | 739.17 | 24.00 |
Report: ComfortReportSimple55Monthly
For: OFFICE
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 140.00 | 20.94 | 140.00 | 20.94 | 140.00 | 20.94 |
| February | 133.00 | 20.94 | 133.00 | 20.94 | 133.00 | 20.94 |
| March | 161.00 | 21.31 | 126.83 | 21.14 | 126.83 | 21.08 |
| April | 140.00 | 21.50 | 64.33 | 21.30 | 64.33 | 21.19 |
| May | 132.83 | 23.19 | 6.17 | 23.08 | 5.83 | 22.99 |
| June | 8.17 | 24.43 | 101.33 | 24.25 | 4.17 | 24.27 |
| July | 8.50 | 25.33 | 140.00 | 24.30 | 8.50 | 24.36 |
| August | 6.33 | 25.41 | 161.00 | 24.28 | 6.33 | 24.32 |
| September | 5.67 | 24.18 | 121.67 | 24.21 | 1.33 | 24.22 |
| October | 98.67 | 22.84 | 11.50 | 22.82 | 4.50 | 22.73 |
| November | 140.00 | 21.46 | 55.83 | 21.28 | 55.83 | 21.18 |
| December | 140.00 | 20.94 | 134.17 | 20.94 | 134.17 | 20.94 |
| Annual Sum or Average | 1114.17 | 21.67 | 1195.83 | 22.04 | 684.83 | 21.81 |
| Minimum of Months | 5.67 | 20.94 | 6.17 | 20.94 | 1.33 | 20.94 |
| Maximum of Months | 161.00 | 25.41 | 161.00 | 24.30 | 140.00 | 24.36 |
Report: ComfortReportSimple55Monthly
For: G NE APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 744.00 | 21.10 | 739.17 | 21.10 | 739.17 | 21.10 |
| February | 672.00 | 21.10 | 672.00 | 21.10 | 672.00 | 21.10 |
| March | 744.00 | 21.16 | 605.50 | 21.13 | 605.50 | 21.12 |
| April | 720.00 | 21.12 | 431.67 | 21.12 | 431.67 | 21.11 |
| May | 744.00 | 21.68 | 81.67 | 21.62 | 81.67 | 21.58 |
| June | 378.33 | 23.40 | 244.67 | 23.61 | 75.83 | 23.64 |
| July | 168.00 | 23.99 | 624.67 | 24.00 | 163.00 | 24.00 |
| August | 103.67 | 23.93 | 443.67 | 23.99 | 83.00 | 23.99 |
| September | 317.83 | 23.40 | 200.83 | 23.63 | 33.17 | 23.65 |
| October | 744.00 | 21.61 | 58.50 | 21.57 | 58.50 | 21.54 |
| November | 720.00 | 21.12 | 447.67 | 21.11 | 447.67 | 21.11 |
| December | 744.00 | 21.10 | 730.67 | 21.10 | 730.67 | 21.10 |
| Annual Sum or Average | 6799.83 | 21.58 | 5280.67 | 21.73 | 4121.83 | 21.63 |
| Minimum of Months | 103.67 | 21.10 | 58.50 | 21.10 | 33.17 | 21.10 |
| Maximum of Months | 744.00 | 23.99 | 739.17 | 24.00 | 739.17 | 24.00 |
Report: ComfortReportSimple55Monthly
For: G N1 APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 744.00 | 21.10 | 733.17 | 21.10 | 733.17 | 21.10 |
| February | 672.00 | 21.10 | 672.00 | 21.10 | 672.00 | 21.10 |
| March | 744.00 | 21.18 | 532.83 | 21.14 | 532.83 | 21.13 |
| April | 720.00 | 21.13 | 352.50 | 21.12 | 352.50 | 21.11 |
| May | 744.00 | 21.82 | 38.17 | 21.78 | 38.17 | 21.75 |
| June | 364.67 | 23.57 | 244.00 | 23.74 | 75.33 | 23.76 |
| July | 156.67 | 24.00 | 582.00 | 24.00 | 156.67 | 24.00 |
| August | 74.33 | 24.00 | 372.00 | 24.00 | 74.33 | 24.00 |
| September | 309.17 | 23.61 | 216.00 | 23.77 | 33.17 | 23.78 |
| October | 744.00 | 21.78 | 29.67 | 21.75 | 29.67 | 21.73 |
| November | 720.00 | 21.14 | 276.17 | 21.13 | 276.17 | 21.12 |
| December | 744.00 | 21.10 | 706.17 | 21.10 | 706.17 | 21.10 |
| Annual Sum or Average | 6736.83 | 21.62 | 4754.67 | 21.76 | 3680.17 | 21.66 |
| Minimum of Months | 74.33 | 21.10 | 29.67 | 21.10 | 29.67 | 21.10 |
| Maximum of Months | 744.00 | 24.00 | 733.17 | 24.00 | 733.17 | 24.00 |
Report: ComfortReportSimple55Monthly
For: G N2 APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 744.00 | 21.10 | 733.17 | 21.10 | 733.17 | 21.10 |
| February | 672.00 | 21.10 | 672.00 | 21.10 | 672.00 | 21.10 |
| March | 744.00 | 21.18 | 532.83 | 21.14 | 532.83 | 21.13 |
| April | 720.00 | 21.13 | 351.00 | 21.12 | 351.00 | 21.11 |
| May | 744.00 | 21.82 | 38.83 | 21.79 | 38.83 | 21.75 |
| June | 365.67 | 23.57 | 244.17 | 23.73 | 75.33 | 23.76 |
| July | 156.67 | 24.00 | 581.50 | 24.00 | 156.67 | 24.00 |
| August | 74.83 | 24.00 | 373.50 | 24.00 | 74.83 | 24.00 |
| September | 307.17 | 23.61 | 216.33 | 23.77 | 32.83 | 23.78 |
| October | 744.00 | 21.78 | 29.67 | 21.75 | 29.67 | 21.73 |
| November | 720.00 | 21.14 | 275.67 | 21.13 | 275.67 | 21.12 |
| December | 744.00 | 21.10 | 706.33 | 21.10 | 706.33 | 21.10 |
| Annual Sum or Average | 6736.33 | 21.62 | 4755.00 | 21.76 | 3679.17 | 21.66 |
| Minimum of Months | 74.83 | 21.10 | 29.67 | 21.10 | 29.67 | 21.10 |
| Maximum of Months | 744.00 | 24.00 | 733.17 | 24.00 | 733.17 | 24.00 |
Report: ComfortReportSimple55Monthly
For: G S1 APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 533.00 | 21.10 | 515.17 | 21.10 | 515.17 | 21.10 |
| February | 473.00 | 21.10 | 466.00 | 21.10 | 466.00 | 21.10 |
| March | 506.00 | 21.21 | 307.50 | 21.17 | 307.50 | 21.15 |
| April | 510.00 | 21.29 | 118.50 | 21.25 | 118.50 | 21.23 |
| May | 515.00 | 22.24 | 0.00 | 22.24 | 0.00 | 22.24 |
| June | 211.83 | 23.66 | 172.83 | 23.81 | 42.33 | 23.82 |
| July | 102.83 | 24.00 | 455.17 | 24.00 | 102.83 | 24.00 |
| August | 31.83 | 24.00 | 322.67 | 24.00 | 31.83 | 24.00 |
| September | 76.50 | 23.61 | 198.83 | 23.89 | 12.83 | 23.90 |
| October | 458.00 | 22.34 | 4.50 | 22.35 | 0.00 | 22.35 |
| November | 510.00 | 21.37 | 103.17 | 21.32 | 103.17 | 21.29 |
| December | 533.00 | 21.10 | 459.50 | 21.10 | 459.50 | 21.10 |
| Annual Sum or Average | 4461.00 | 21.68 | 3123.83 | 21.88 | 2159.67 | 21.76 |
| Minimum of Months | 31.83 | 21.10 | 0.00 | 21.10 | 0.00 | 21.10 |
| Maximum of Months | 533.00 | 24.00 | 515.17 | 24.00 | 515.17 | 24.00 |
Report: ComfortReportSimple55Monthly
For: G S2 APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 533.00 | 21.10 | 521.67 | 21.10 | 521.67 | 21.10 |
| February | 473.00 | 21.10 | 471.50 | 21.10 | 471.50 | 21.10 |
| March | 506.00 | 21.21 | 327.00 | 21.17 | 327.00 | 21.15 |
| April | 510.00 | 21.28 | 135.67 | 21.24 | 135.67 | 21.22 |
| May | 515.00 | 22.31 | 0.00 | 22.31 | 0.00 | 22.31 |
| June | 181.83 | 23.68 | 180.33 | 23.84 | 37.50 | 23.85 |
| July | 80.67 | 24.00 | 473.50 | 24.00 | 80.67 | 24.00 |
| August | 23.17 | 24.00 | 353.17 | 24.00 | 23.17 | 24.00 |
| September | 56.83 | 23.57 | 206.67 | 23.91 | 4.83 | 23.91 |
| October | 445.00 | 22.35 | 6.00 | 22.37 | 0.00 | 22.37 |
| November | 510.00 | 21.35 | 107.83 | 21.31 | 107.83 | 21.28 |
| December | 533.00 | 21.10 | 497.50 | 21.10 | 497.50 | 21.10 |
| Annual Sum or Average | 4367.50 | 21.64 | 3280.83 | 21.87 | 2207.33 | 21.74 |
| Minimum of Months | 23.17 | 21.10 | 0.00 | 21.10 | 0.00 | 21.10 |
| Maximum of Months | 533.00 | 24.00 | 521.67 | 24.00 | 521.67 | 24.00 |
Report: ComfortReportSimple55Monthly
For: M SW APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 533.00 | 21.11 | 480.33 | 21.10 | 480.33 | 21.10 |
| February | 473.00 | 21.10 | 419.17 | 21.10 | 419.17 | 21.10 |
| March | 485.17 | 21.28 | 204.50 | 21.23 | 204.50 | 21.20 |
| April | 491.00 | 21.94 | 26.67 | 21.90 | 26.67 | 21.86 |
| May | 270.50 | 23.26 | 31.33 | 23.33 | 0.00 | 23.33 |
| June | 82.33 | 23.72 | 249.00 | 23.93 | 25.83 | 23.93 |
| July | 75.17 | 24.00 | 483.00 | 24.00 | 75.17 | 24.00 |
| August | 28.33 | 23.96 | 342.50 | 24.00 | 25.00 | 24.00 |
| September | 107.83 | 23.41 | 204.17 | 23.80 | 14.50 | 23.81 |
| October | 461.33 | 22.08 | 13.83 | 22.09 | 8.33 | 22.07 |
| November | 510.00 | 21.36 | 124.33 | 21.31 | 124.33 | 21.28 |
| December | 533.00 | 21.11 | 446.50 | 21.10 | 446.50 | 21.10 |
| Annual Sum or Average | 4050.67 | 21.70 | 3025.33 | 21.98 | 1850.33 | 21.85 |
| Minimum of Months | 28.33 | 21.10 | 13.83 | 21.10 | 0.00 | 21.10 |
| Maximum of Months | 533.00 | 24.00 | 483.00 | 24.00 | 480.33 | 24.00 |
Report: ComfortReportSimple55Monthly
For: M NW APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 744.00 | 21.10 | 721.33 | 21.10 | 721.33 | 21.10 |
| February | 672.00 | 21.10 | 658.00 | 21.10 | 658.00 | 21.10 |
| March | 722.67 | 21.29 | 401.83 | 21.22 | 401.83 | 21.19 |
| April | 720.00 | 21.57 | 57.33 | 21.53 | 57.33 | 21.50 |
| May | 473.33 | 23.15 | 36.83 | 23.20 | 0.00 | 23.20 |
| June | 135.33 | 23.77 | 367.33 | 23.94 | 40.83 | 23.94 |
| July | 104.50 | 24.00 | 668.67 | 24.00 | 104.50 | 24.00 |
| August | 49.50 | 23.96 | 460.33 | 24.00 | 44.33 | 24.00 |
| September | 233.50 | 23.36 | 231.67 | 23.68 | 23.33 | 23.69 |
| October | 744.00 | 21.80 | 37.00 | 21.77 | 37.00 | 21.74 |
| November | 720.00 | 21.15 | 295.83 | 21.14 | 295.83 | 21.13 |
| December | 744.00 | 21.10 | 693.50 | 21.10 | 693.50 | 21.10 |
| Annual Sum or Average | 6062.83 | 21.65 | 4629.67 | 21.89 | 3077.83 | 21.76 |
| Minimum of Months | 49.50 | 21.10 | 36.83 | 21.10 | 0.00 | 21.10 |
| Maximum of Months | 744.00 | 24.00 | 721.33 | 24.00 | 721.33 | 24.00 |
Report: ComfortReportSimple55Monthly
For: M SE APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 533.00 | 21.10 | 478.33 | 21.10 | 478.33 | 21.10 |
| February | 473.00 | 21.10 | 421.17 | 21.10 | 421.17 | 21.10 |
| March | 484.17 | 21.26 | 214.83 | 21.21 | 214.83 | 21.18 |
| April | 488.17 | 21.92 | 26.33 | 21.88 | 26.33 | 21.84 |
| May | 279.17 | 23.25 | 28.50 | 23.32 | 0.00 | 23.32 |
| June | 89.33 | 23.73 | 241.17 | 23.93 | 27.17 | 23.93 |
| July | 77.17 | 24.00 | 485.00 | 24.00 | 77.17 | 24.00 |
| August | 31.00 | 23.97 | 340.67 | 24.00 | 28.67 | 24.00 |
| September | 102.50 | 23.37 | 204.17 | 23.79 | 13.33 | 23.80 |
| October | 457.83 | 22.11 | 13.83 | 22.11 | 8.83 | 22.09 |
| November | 510.00 | 21.37 | 122.83 | 21.32 | 122.83 | 21.28 |
| December | 533.00 | 21.11 | 445.50 | 21.10 | 445.50 | 21.10 |
| Annual Sum or Average | 4058.33 | 21.71 | 3022.33 | 21.98 | 1864.17 | 21.85 |
| Minimum of Months | 31.00 | 21.10 | 13.83 | 21.10 | 0.00 | 21.10 |
| Maximum of Months | 533.00 | 24.00 | 485.00 | 24.00 | 478.33 | 24.00 |
Report: ComfortReportSimple55Monthly
For: M NE APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 744.00 | 21.10 | 721.33 | 21.10 | 721.33 | 21.10 |
| February | 672.00 | 21.10 | 660.67 | 21.10 | 660.67 | 21.10 |
| March | 720.50 | 21.29 | 401.17 | 21.22 | 401.17 | 21.19 |
| April | 720.00 | 21.61 | 54.67 | 21.58 | 54.67 | 21.55 |
| May | 450.67 | 23.17 | 34.33 | 23.22 | 0.00 | 23.22 |
| June | 121.00 | 23.77 | 354.83 | 23.94 | 40.83 | 23.95 |
| July | 103.33 | 24.00 | 682.67 | 24.00 | 103.33 | 24.00 |
| August | 52.33 | 23.98 | 464.33 | 24.00 | 48.33 | 24.00 |
| September | 194.50 | 23.28 | 234.67 | 23.67 | 21.33 | 23.69 |
| October | 744.00 | 21.83 | 32.17 | 21.80 | 32.17 | 21.77 |
| November | 720.00 | 21.15 | 286.17 | 21.14 | 286.17 | 21.13 |
| December | 744.00 | 21.10 | 693.00 | 21.10 | 693.00 | 21.10 |
| Annual Sum or Average | 5986.33 | 21.64 | 4620.00 | 21.89 | 3063.00 | 21.76 |
| Minimum of Months | 52.33 | 21.10 | 32.17 | 21.10 | 0.00 | 21.10 |
| Maximum of Months | 744.00 | 24.00 | 721.33 | 24.00 | 721.33 | 24.00 |
Report: ComfortReportSimple55Monthly
For: M N1 APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 744.00 | 21.10 | 659.67 | 21.10 | 659.67 | 21.10 |
| February | 672.00 | 21.10 | 582.17 | 21.10 | 582.17 | 21.10 |
| March | 716.67 | 21.33 | 378.83 | 21.25 | 378.83 | 21.21 |
| April | 720.00 | 21.67 | 41.17 | 21.64 | 41.17 | 21.62 |
| May | 457.33 | 23.39 | 29.00 | 23.42 | 0.00 | 23.42 |
| June | 126.33 | 23.89 | 316.83 | 23.97 | 36.83 | 23.97 |
| July | 103.83 | 24.00 | 621.83 | 24.00 | 103.83 | 24.00 |
| August | 45.17 | 24.00 | 380.67 | 24.00 | 45.17 | 24.00 |
| September | 179.33 | 23.61 | 232.00 | 23.83 | 20.17 | 23.84 |
| October | 743.67 | 22.08 | 3.83 | 22.08 | 3.83 | 22.07 |
| November | 720.00 | 21.20 | 142.33 | 21.19 | 142.33 | 21.17 |
| December | 744.00 | 21.10 | 537.50 | 21.10 | 537.50 | 21.10 |
| Annual Sum or Average | 5972.33 | 21.71 | 3925.83 | 21.93 | 2551.50 | 21.81 |
| Minimum of Months | 45.17 | 21.10 | 3.83 | 21.10 | 0.00 | 21.10 |
| Maximum of Months | 744.00 | 24.00 | 659.67 | 24.00 | 659.67 | 24.00 |
Report: ComfortReportSimple55Monthly
For: M N2 APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 744.00 | 21.10 | 659.67 | 21.10 | 659.67 | 21.10 |
| February | 672.00 | 21.10 | 582.17 | 21.10 | 582.17 | 21.10 |
| March | 716.50 | 21.33 | 379.17 | 21.25 | 379.17 | 21.21 |
| April | 720.00 | 21.68 | 41.00 | 21.65 | 41.00 | 21.62 |
| May | 456.83 | 23.39 | 29.00 | 23.42 | 0.00 | 23.42 |
| June | 125.67 | 23.89 | 317.33 | 23.97 | 36.67 | 23.97 |
| July | 104.17 | 24.00 | 623.33 | 24.00 | 104.17 | 24.00 |
| August | 45.33 | 24.00 | 381.67 | 24.00 | 45.33 | 24.00 |
| September | 178.83 | 23.61 | 232.17 | 23.83 | 20.17 | 23.84 |
| October | 743.33 | 22.09 | 3.50 | 22.08 | 3.50 | 22.08 |
| November | 720.00 | 21.20 | 141.17 | 21.19 | 141.17 | 21.17 |
| December | 744.00 | 21.10 | 537.17 | 21.10 | 537.17 | 21.10 |
| Annual Sum or Average | 5970.67 | 21.71 | 3927.33 | 21.93 | 2550.17 | 21.81 |
| Minimum of Months | 45.33 | 21.10 | 3.50 | 21.10 | 0.00 | 21.10 |
| Maximum of Months | 744.00 | 24.00 | 659.67 | 24.00 | 659.67 | 24.00 |
Report: ComfortReportSimple55Monthly
For: M S1 APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 533.00 | 21.11 | 372.83 | 21.11 | 372.83 | 21.11 |
| February | 473.00 | 21.11 | 342.50 | 21.10 | 342.50 | 21.10 |
| March | 480.50 | 21.37 | 143.50 | 21.31 | 143.50 | 21.27 |
| April | 490.17 | 22.22 | 12.50 | 22.19 | 12.50 | 22.17 |
| May | 241.33 | 23.54 | 24.67 | 23.58 | 0.00 | 23.58 |
| June | 73.17 | 23.84 | 219.00 | 23.96 | 20.17 | 23.96 |
| July | 73.33 | 24.00 | 472.33 | 24.00 | 73.33 | 24.00 |
| August | 24.17 | 24.00 | 309.83 | 24.00 | 24.17 | 24.00 |
| September | 53.00 | 23.60 | 198.00 | 23.92 | 8.00 | 23.92 |
| October | 404.00 | 22.48 | 7.83 | 22.50 | 0.00 | 22.50 |
| November | 510.00 | 21.62 | 34.00 | 21.59 | 34.00 | 21.56 |
| December | 533.00 | 21.12 | 309.67 | 21.11 | 309.67 | 21.11 |
| Annual Sum or Average | 3888.67 | 21.80 | 2446.67 | 22.09 | 1340.67 | 21.97 |
| Minimum of Months | 24.17 | 21.11 | 7.83 | 21.10 | 0.00 | 21.10 |
| Maximum of Months | 533.00 | 24.00 | 472.33 | 24.00 | 372.83 | 24.00 |
Report: ComfortReportSimple55Monthly
For: M S2 APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 533.00 | 21.11 | 372.00 | 21.11 | 372.00 | 21.11 |
| February | 473.00 | 21.11 | 342.33 | 21.10 | 342.33 | 21.10 |
| March | 480.50 | 21.37 | 144.00 | 21.31 | 144.00 | 21.27 |
| April | 489.00 | 22.22 | 12.33 | 22.19 | 12.33 | 22.16 |
| May | 242.17 | 23.54 | 25.33 | 23.58 | 0.00 | 23.58 |
| June | 73.50 | 23.84 | 218.67 | 23.96 | 20.17 | 23.96 |
| July | 73.17 | 24.00 | 472.17 | 24.00 | 73.17 | 24.00 |
| August | 24.50 | 24.00 | 309.67 | 24.00 | 24.50 | 24.00 |
| September | 52.83 | 23.60 | 198.00 | 23.92 | 7.83 | 23.92 |
| October | 403.00 | 22.48 | 8.00 | 22.51 | 0.00 | 22.51 |
| November | 510.00 | 21.62 | 34.00 | 21.59 | 34.00 | 21.56 |
| December | 533.00 | 21.12 | 309.83 | 21.11 | 309.83 | 21.11 |
| Annual Sum or Average | 3887.67 | 21.80 | 2446.33 | 22.09 | 1340.17 | 21.97 |
| Minimum of Months | 24.50 | 21.11 | 8.00 | 21.10 | 0.00 | 21.10 |
| Maximum of Months | 533.00 | 24.00 | 472.17 | 24.00 | 372.00 | 24.00 |
Report: ComfortReportSimple55Monthly
For: T SW APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 533.00 | 21.11 | 522.33 | 21.10 | 522.33 | 21.10 |
| February | 473.00 | 21.10 | 460.50 | 21.10 | 460.50 | 21.10 |
| March | 487.17 | 21.21 | 345.33 | 21.18 | 341.50 | 21.16 |
| April | 475.33 | 21.49 | 195.33 | 21.40 | 191.17 | 21.33 |
| May | 393.00 | 22.19 | 45.67 | 22.28 | 14.83 | 22.25 |
| June | 193.33 | 22.92 | 242.00 | 23.51 | 36.50 | 23.54 |
| July | 172.83 | 23.74 | 435.33 | 23.92 | 122.50 | 23.93 |
| August | 164.33 | 23.48 | 313.50 | 23.82 | 66.00 | 23.84 |
| September | 292.83 | 22.61 | 168.50 | 23.10 | 38.00 | 23.16 |
| October | 485.33 | 21.55 | 157.00 | 21.47 | 150.67 | 21.40 |
| November | 510.00 | 21.24 | 357.83 | 21.18 | 357.83 | 21.16 |
| December | 533.00 | 21.11 | 516.50 | 21.10 | 516.50 | 21.10 |
| Annual Sum or Average | 4713.17 | 21.65 | 3759.83 | 21.82 | 2818.33 | 21.71 |
| Minimum of Months | 164.33 | 21.10 | 45.67 | 21.10 | 14.83 | 21.10 |
| Maximum of Months | 533.00 | 23.74 | 522.33 | 23.92 | 522.33 | 23.93 |
Report: ComfortReportSimple55Monthly
For: T NW APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 744.00 | 21.10 | 737.17 | 21.10 | 737.17 | 21.10 |
| February | 672.00 | 21.10 | 671.17 | 21.10 | 671.17 | 21.10 |
| March | 720.83 | 21.21 | 530.83 | 21.17 | 526.33 | 21.15 |
| April | 704.50 | 21.46 | 281.17 | 21.36 | 281.17 | 21.30 |
| May | 605.83 | 22.24 | 62.33 | 22.30 | 24.00 | 22.26 |
| June | 264.50 | 22.97 | 381.17 | 23.57 | 53.50 | 23.60 |
| July | 211.33 | 23.79 | 626.00 | 23.95 | 156.17 | 23.95 |
| August | 232.67 | 23.48 | 477.83 | 23.83 | 96.50 | 23.85 |
| September | 457.67 | 22.50 | 192.83 | 22.93 | 50.00 | 22.98 |
| October | 733.67 | 21.41 | 254.33 | 21.33 | 254.33 | 21.29 |
| November | 720.00 | 21.12 | 573.83 | 21.11 | 573.83 | 21.11 |
| December | 744.00 | 21.10 | 735.50 | 21.10 | 735.50 | 21.10 |
| Annual Sum or Average | 6811.00 | 21.62 | 5524.17 | 21.79 | 4159.67 | 21.68 |
| Minimum of Months | 211.33 | 21.10 | 62.33 | 21.10 | 24.00 | 21.10 |
| Maximum of Months | 744.00 | 23.79 | 737.17 | 23.95 | 737.17 | 23.95 |
Report: ComfortReportSimple55Monthly
For: T SE APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 533.00 | 21.11 | 520.67 | 21.10 | 520.67 | 21.10 |
| February | 473.00 | 21.10 | 464.50 | 21.10 | 464.50 | 21.10 |
| March | 491.67 | 21.21 | 351.50 | 21.18 | 348.33 | 21.15 |
| April | 478.67 | 21.49 | 195.50 | 21.38 | 193.67 | 21.32 |
| May | 396.67 | 22.21 | 45.17 | 22.31 | 13.67 | 22.27 |
| June | 202.33 | 22.96 | 232.67 | 23.50 | 40.67 | 23.54 |
| July | 173.67 | 23.77 | 430.83 | 23.93 | 124.50 | 23.94 |
| August | 171.17 | 23.51 | 308.17 | 23.82 | 73.67 | 23.84 |
| September | 293.50 | 22.63 | 163.83 | 23.10 | 38.17 | 23.15 |
| October | 485.67 | 21.55 | 154.00 | 21.47 | 148.67 | 21.40 |
| November | 510.00 | 21.24 | 359.67 | 21.18 | 359.67 | 21.16 |
| December | 533.00 | 21.11 | 515.33 | 21.10 | 515.33 | 21.10 |
| Annual Sum or Average | 4742.33 | 21.67 | 3741.83 | 21.82 | 2841.50 | 21.71 |
| Minimum of Months | 171.17 | 21.10 | 45.17 | 21.10 | 13.67 | 21.10 |
| Maximum of Months | 533.00 | 23.77 | 520.67 | 23.93 | 520.67 | 23.94 |
Report: ComfortReportSimple55Monthly
For: T NE APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 744.00 | 21.10 | 737.17 | 21.10 | 737.17 | 21.10 |
| February | 672.00 | 21.10 | 672.00 | 21.10 | 672.00 | 21.10 |
| March | 717.33 | 21.20 | 540.83 | 21.17 | 535.17 | 21.15 |
| April | 711.50 | 21.52 | 258.83 | 21.41 | 258.83 | 21.34 |
| May | 583.00 | 22.32 | 58.00 | 22.37 | 21.83 | 22.33 |
| June | 255.00 | 23.06 | 381.67 | 23.61 | 58.50 | 23.64 |
| July | 201.33 | 23.81 | 636.33 | 23.95 | 152.83 | 23.96 |
| August | 224.83 | 23.51 | 492.83 | 23.84 | 99.50 | 23.86 |
| September | 434.33 | 22.58 | 198.17 | 23.00 | 49.33 | 23.05 |
| October | 734.33 | 21.41 | 246.17 | 21.34 | 246.17 | 21.29 |
| November | 720.00 | 21.13 | 569.83 | 21.11 | 569.83 | 21.11 |
| December | 744.00 | 21.10 | 735.50 | 21.10 | 735.50 | 21.10 |
| Annual Sum or Average | 6741.67 | 21.63 | 5527.33 | 21.80 | 4136.67 | 21.69 |
| Minimum of Months | 201.33 | 21.10 | 58.00 | 21.10 | 21.83 | 21.10 |
| Maximum of Months | 744.00 | 23.81 | 737.17 | 23.95 | 737.17 | 23.96 |
Report: ComfortReportSimple55Monthly
For: T N1 APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 744.00 | 21.10 | 732.00 | 21.10 | 732.00 | 21.10 |
| February | 672.00 | 21.10 | 672.00 | 21.10 | 672.00 | 21.10 |
| March | 713.33 | 21.22 | 499.33 | 21.17 | 499.33 | 21.15 |
| April | 716.67 | 21.49 | 228.00 | 21.39 | 228.00 | 21.34 |
| May | 625.50 | 22.50 | 22.50 | 22.53 | 5.33 | 22.52 |
| June | 252.00 | 23.21 | 352.00 | 23.67 | 51.67 | 23.69 |
| July | 179.17 | 23.90 | 624.00 | 23.98 | 147.83 | 23.98 |
| August | 181.33 | 23.64 | 456.67 | 23.90 | 85.67 | 23.91 |
| September | 443.67 | 22.78 | 181.83 | 23.13 | 35.50 | 23.18 |
| October | 743.83 | 21.51 | 188.33 | 21.43 | 188.33 | 21.38 |
| November | 720.00 | 21.14 | 527.33 | 21.12 | 527.33 | 21.12 |
| December | 744.00 | 21.10 | 728.67 | 21.10 | 728.67 | 21.10 |
| Annual Sum or Average | 6735.50 | 21.67 | 5212.67 | 21.81 | 3901.67 | 21.70 |
| Minimum of Months | 179.17 | 21.10 | 22.50 | 21.10 | 5.33 | 21.10 |
| Maximum of Months | 744.00 | 23.90 | 732.00 | 23.98 | 732.00 | 23.98 |
Report: ComfortReportSimple55Monthly
For: T N2 APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 744.00 | 21.10 | 732.00 | 21.10 | 732.00 | 21.10 |
| February | 672.00 | 21.10 | 672.00 | 21.10 | 672.00 | 21.10 |
| March | 712.83 | 21.21 | 499.17 | 21.17 | 499.17 | 21.15 |
| April | 715.67 | 21.49 | 226.17 | 21.40 | 226.17 | 21.34 |
| May | 622.17 | 22.51 | 22.17 | 22.53 | 5.33 | 22.52 |
| June | 251.50 | 23.22 | 351.17 | 23.67 | 51.67 | 23.69 |
| July | 179.50 | 23.90 | 624.17 | 23.98 | 148.17 | 23.98 |
| August | 181.00 | 23.64 | 459.83 | 23.90 | 85.83 | 23.91 |
| September | 441.50 | 22.78 | 182.33 | 23.14 | 35.33 | 23.18 |
| October | 743.33 | 21.52 | 188.00 | 21.43 | 188.00 | 21.38 |
| November | 720.00 | 21.14 | 527.67 | 21.13 | 527.67 | 21.12 |
| December | 744.00 | 21.10 | 728.67 | 21.10 | 728.67 | 21.10 |
| Annual Sum or Average | 6727.50 | 21.67 | 5213.33 | 21.82 | 3900.00 | 21.70 |
| Minimum of Months | 179.50 | 21.10 | 22.17 | 21.10 | 5.33 | 21.10 |
| Maximum of Months | 744.00 | 23.90 | 732.00 | 23.98 | 732.00 | 23.98 |
Report: ComfortReportSimple55Monthly
For: T S1 APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 533.00 | 21.11 | 510.17 | 21.11 | 510.17 | 21.10 |
| February | 473.00 | 21.10 | 454.50 | 21.10 | 454.50 | 21.10 |
| March | 486.33 | 21.25 | 304.17 | 21.20 | 301.33 | 21.17 |
| April | 482.33 | 21.62 | 130.00 | 21.51 | 129.67 | 21.44 |
| May | 398.33 | 22.52 | 21.50 | 22.57 | 3.00 | 22.56 |
| June | 183.67 | 23.18 | 225.50 | 23.62 | 34.33 | 23.65 |
| July | 147.17 | 23.85 | 433.17 | 23.96 | 113.17 | 23.97 |
| August | 123.00 | 23.64 | 305.83 | 23.90 | 57.50 | 23.91 |
| September | 247.33 | 22.82 | 164.67 | 23.29 | 24.17 | 23.33 |
| October | 473.00 | 21.70 | 98.00 | 21.62 | 93.17 | 21.55 |
| November | 509.67 | 21.32 | 288.33 | 21.24 | 288.33 | 21.20 |
| December | 533.00 | 21.12 | 500.83 | 21.11 | 500.83 | 21.11 |
| Annual Sum or Average | 4589.83 | 21.72 | 3436.67 | 21.87 | 2510.17 | 21.75 |
| Minimum of Months | 123.00 | 21.10 | 21.50 | 21.10 | 3.00 | 21.10 |
| Maximum of Months | 533.00 | 23.85 | 510.17 | 23.96 | 510.17 | 23.97 |
Report: ComfortReportSimple55Monthly
For: T S2 APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 533.00 | 21.11 | 509.50 | 21.11 | 509.50 | 21.10 |
| February | 473.00 | 21.10 | 454.67 | 21.10 | 454.67 | 21.10 |
| March | 486.83 | 21.25 | 304.50 | 21.20 | 301.67 | 21.17 |
| April | 482.33 | 21.62 | 131.50 | 21.51 | 131.00 | 21.44 |
| May | 397.67 | 22.51 | 21.00 | 22.56 | 3.17 | 22.55 |
| June | 185.33 | 23.17 | 224.67 | 23.62 | 34.17 | 23.65 |
| July | 147.83 | 23.85 | 432.17 | 23.96 | 113.83 | 23.97 |
| August | 124.17 | 23.64 | 305.50 | 23.90 | 58.17 | 23.91 |
| September | 247.83 | 22.82 | 164.83 | 23.29 | 23.83 | 23.33 |
| October | 472.50 | 21.70 | 98.00 | 21.62 | 93.33 | 21.55 |
| November | 509.50 | 21.32 | 288.17 | 21.24 | 288.17 | 21.20 |
| December | 533.00 | 21.12 | 500.83 | 21.11 | 500.83 | 21.11 |
| Annual Sum or Average | 4593.00 | 21.72 | 3435.33 | 21.87 | 2512.33 | 21.75 |
| Minimum of Months | 124.17 | 21.10 | 21.00 | 21.10 | 3.17 | 21.10 |
| Maximum of Months | 533.00 | 23.85 | 509.50 | 23.96 | 509.50 | 23.97 |
Report: ComfortReportSimple55Monthly
For: T CORRIDOR
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 744.00 | 19.43 | 701.17 | 19.40 | 701.17 | 19.39 |
| February | 672.00 | 19.43 | 649.83 | 19.41 | 649.83 | 19.40 |
| March | 744.00 | 20.84 | 466.67 | 20.79 | 466.67 | 20.76 |
| April | 663.00 | 21.71 | 338.00 | 21.89 | 304.17 | 21.91 |
| May | 723.83 | 23.79 | 744.00 | 23.80 | 723.83 | 23.79 |
| June | 704.50 | 25.37 | 714.67 | 25.37 | 701.67 | 25.37 |
| July | 744.00 | 26.00 | 744.00 | 26.00 | 744.00 | 26.00 |
| August | 744.00 | 25.72 | 744.00 | 25.72 | 744.00 | 25.72 |
| September | 715.33 | 24.55 | 685.33 | 24.60 | 685.33 | 24.62 |
| October | 726.50 | 22.00 | 396.17 | 22.18 | 387.50 | 22.25 |
| November | 720.00 | 20.80 | 240.17 | 20.68 | 240.17 | 20.61 |
| December | 744.00 | 19.51 | 669.83 | 19.46 | 669.83 | 19.44 |
| Annual Sum or Average | 8645.17 | 22.44 | 7093.83 | 22.58 | 7018.17 | 22.62 |
| Minimum of Months | 663.00 | 19.43 | 240.17 | 19.40 | 240.17 | 19.39 |
| Maximum of Months | 744.00 | 26.00 | 744.00 | 26.00 | 744.00 | 26.00 |
Report: ComfortReportSimple55Monthly
For: G CORRIDOR
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 744.00 | 16.31 | 744.00 | 16.31 | 744.00 | 16.31 |
| February | 672.00 | 16.11 | 672.00 | 16.11 | 672.00 | 16.11 |
| March | 744.00 | 17.98 | 642.50 | 17.72 | 642.50 | 17.62 |
| April | 720.00 | 19.39 | 515.50 | 19.09 | 515.50 | 18.97 |
| May | 743.33 | 21.70 | 115.50 | 21.41 | 115.50 | 21.19 |
| June | 421.50 | 24.34 | 471.67 | 24.82 | 261.00 | 24.92 |
| July | 512.50 | 25.87 | 727.50 | 25.88 | 500.83 | 25.90 |
| August | 379.17 | 25.55 | 695.67 | 25.70 | 353.00 | 25.73 |
| September | 345.33 | 24.01 | 453.83 | 24.62 | 202.67 | 24.74 |
| October | 717.33 | 21.08 | 198.83 | 20.64 | 195.50 | 20.35 |
| November | 720.00 | 19.26 | 519.83 | 18.94 | 519.83 | 18.81 |
| December | 744.00 | 16.72 | 744.00 | 16.72 | 744.00 | 16.72 |
| Annual Sum or Average | 7463.17 | 20.01 | 6500.83 | 20.14 | 5466.33 | 19.91 |
| Minimum of Months | 345.33 | 16.11 | 115.50 | 16.11 | 115.50 | 16.11 |
| Maximum of Months | 744.00 | 25.87 | 744.00 | 25.88 | 744.00 | 25.90 |
Report: ComfortReportSimple55Monthly
For: M CORRIDOR
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 744.00 | 21.23 | 77.17 | 21.24 | 77.17 | 21.25 |
| February | 672.00 | 21.22 | 44.50 | 21.18 | 44.50 | 21.14 |
| March | 744.00 | 22.32 | 273.50 | 22.52 | 273.50 | 22.64 |
| April | 717.00 | 23.12 | 543.17 | 23.25 | 543.17 | 23.30 |
| May | 744.00 | 25.12 | 744.00 | 25.12 | 744.00 | 25.12 |
| June | 720.00 | 25.83 | 720.00 | 25.83 | 720.00 | 25.83 |
| July | 744.00 | 26.05 | 744.00 | 26.05 | 744.00 | 26.05 |
| August | 744.00 | 25.95 | 744.00 | 25.95 | 744.00 | 25.95 |
| September | 720.00 | 25.55 | 720.00 | 25.55 | 720.00 | 25.55 |
| October | 744.00 | 23.56 | 741.33 | 23.56 | 741.33 | 23.56 |
| November | 720.00 | 22.24 | 395.83 | 22.30 | 395.83 | 22.33 |
| December | 744.00 | 21.23 | 50.83 | 21.26 | 50.83 | 21.28 |
| Annual Sum or Average | 8757.00 | 23.63 | 5798.33 | 24.07 | 5798.33 | 24.26 |
| Minimum of Months | 672.00 | 21.22 | 44.50 | 21.18 | 44.50 | 21.14 |
| Maximum of Months | 744.00 | 26.05 | 744.00 | 26.05 | 744.00 | 26.05 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_GSW
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 515.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 492.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 524.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 6145.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_GNW
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 8760.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_OFFICE
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 140.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 133.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 161.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 140.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 154.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 154.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 140.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 161.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 140.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 147.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 140.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 140.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 1750.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 133.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 161.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_GNE
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 8760.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_GN1
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 8760.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_GN2
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 8760.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_GS1
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 515.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 492.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 524.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 6145.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_GS2
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 515.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 492.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 524.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 6145.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_MSW
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 515.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 492.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 524.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 6145.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_MNW
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 8760.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_MSE
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 515.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 492.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 524.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 6145.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_MNE
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 8760.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_MN1
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 8760.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_MN2
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 8760.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_MS1
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 515.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 492.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 524.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 6145.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_MS2
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 515.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 492.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 524.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 6145.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_TSW
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 515.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 492.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 524.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 6145.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_TNW
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 8760.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_TSE
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 515.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 492.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 524.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 6145.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_TNE
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 8760.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_TN1
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 8760.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_TN2
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 8760.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_TS1
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 515.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 492.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 524.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 6145.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_TS2
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 515.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 492.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 524.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 6145.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_T CORRIDOR
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 8760.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_G CORRIDOR
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 8760.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_M CORRIDOR
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 8760.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: DXReportMonthly
For: SPLIT GSW COOLING COIL
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
| March | 1032688.59 | 274999.96 | 4.33 | 1013805.67 | 18882.92 | 0.00 | 0.02 | 15-MAR-16:30 | 0.00 | 01-MAR-00:10 | 118.37 | 15-MAR-16:30 | 116.07 | 15-MAR-16:30 | 2.44 | 15-MAR-17:40 | 31.43 | 15-MAR-16:30 | 0.00 | 01-MAR-00:10 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 |
| May | 21210952.10 | 5555708.84 | 27.17 | 20345034.23 | 865917.86 | 0.00 | 0.11 | 14-MAY-15:10 | 0.00 | 01-MAY-00:10 | 555.69 | 14-MAY-15:10 | 459.09 | 14-MAY-15:10 | 97.85 | 14-MAY-14:40 | 144.56 | 14-MAY-15:10 | 0.00 | 01-MAY-00:10 |
| June | 0.121814E+10 | 0.306136E+09 | 433.52 | 0.100363E+10 | 0.214512E+09 | 0.00 | 0.44 | 27-JUN-16:40 | 0.00 | 01-JUN-00:10 | 2409.24 | 27-JUN-16:40 | 1798.29 | 12-JUN-15:10 | 648.30 | 27-JUN-16:23 | 601.77 | 27-JUN-13:00 | 0.00 | 01-JUN-00:10 |
| July | 0.291949E+10 | 0.726999E+09 | 707.63 | 0.228672E+10 | 0.632770E+09 | 0.00 | 0.51 | 19-JUL-15:10 | 0.00 | 01-JUL-04:00 | 2681.16 | 19-JUL-15:10 | 2126.36 | 19-JUL-15:10 | 763.89 | 15-JUL-14:00 | 707.69 | 19-JUL-15:10 | 0.00 | 01-JUL-00:10 |
| August | 0.263024E+10 | 0.660042E+09 | 697.08 | 0.223698E+10 | 0.393265E+09 | 0.00 | 0.56 | 13-AUG-15:30 | 0.00 | 01-AUG-05:00 | 3043.56 | 13-AUG-15:30 | 2394.81 | 10-AUG-16:04 | 687.99 | 13-AUG-16:05 | 778.24 | 13-AUG-15:30 | 0.00 | 01-AUG-00:10 |
| September | 0.135054E+10 | 0.337956E+09 | 519.95 | 0.117581E+10 | 0.174724E+09 | 0.00 | 0.48 | 21-SEP-16:10 | 0.00 | 01-SEP-00:10 | 2454.74 | 21-SEP-16:10 | 2387.57 | 21-SEP-16:04 | 425.77 | 17-SEP-11:00 | 616.46 | 21-SEP-16:10 | 0.00 | 01-SEP-00:10 |
| October | 44656957.56 | 11491113.87 | 41.22 | 43404672.53 | 1252285.03 | 0.00 | 0.25 | 11-OCT-16:07 | 0.00 | 01-OCT-00:10 | 1220.95 | 11-OCT-16:07 | 1220.95 | 11-OCT-16:07 | 71.89 | 12-OCT-15:30 | 309.50 | 11-OCT-16:07 | 0.00 | 01-OCT-00:10 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.818531E+10 | 0.204846E+10 | 2430.91 | 0.676791E+10 | 0.141741E+10 | 0.00 | ||||||||||||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Maximum of Months | 0.291949E+10 | 0.726999E+09 | 707.63 | 0.228672E+10 | 0.632770E+09 | 0.00 | 0.56 | 0.00 | 3043.56 | 2394.81 | 763.89 | 778.24 | 0.00 |
Report: DXReportMonthly
For: SPLIT GNW COOLING COIL
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 |
| May | 404426.17 | 105960.16 | 1.58 | 403092.76 | 1333.41 | 0.00 | 0.03 | 31-MAY-18:00 | 0.00 | 01-MAY-00:10 | 126.77 | 31-MAY-18:00 | 126.30 | 31-MAY-18:00 | 0.47 | 31-MAY-18:00 | 33.15 | 31-MAY-18:00 | 0.00 | 01-MAY-00:10 |
| June | 0.102517E+10 | 0.257292E+09 | 392.29 | 0.827677E+09 | 0.197497E+09 | 0.00 | 0.45 | 27-JUN-17:10 | 0.00 | 01-JUN-00:10 | 2320.38 | 27-JUN-17:10 | 1662.21 | 27-JUN-17:10 | 664.30 | 27-JUN-16:23 | 568.02 | 27-JUN-17:00 | 0.00 | 01-JUN-00:10 |
| July | 0.259042E+10 | 0.645105E+09 | 706.15 | 0.199798E+10 | 0.592434E+09 | 0.00 | 0.48 | 19-JUL-15:10 | 0.00 | 01-JUL-03:10 | 2398.12 | 20-JUL-16:02 | 1847.57 | 16-JUL-16:07 | 707.41 | 21-JUL-03:00 | 629.75 | 19-JUL-15:10 | 0.00 | 01-JUL-00:10 |
| August | 0.211101E+10 | 0.531067E+09 | 670.02 | 0.176258E+10 | 0.348430E+09 | 0.00 | 0.49 | 13-AUG-15:30 | 0.00 | 01-AUG-04:30 | 2505.76 | 13-AUG-15:30 | 1969.13 | 10-AUG-16:30 | 630.79 | 13-AUG-16:05 | 645.45 | 13-AUG-15:30 | 0.00 | 01-AUG-00:10 |
| September | 0.676624E+09 | 0.169056E+09 | 354.17 | 0.551057E+09 | 0.125566E+09 | 0.00 | 0.36 | 16-SEP-16:10 | 0.00 | 01-SEP-00:10 | 1785.79 | 16-SEP-16:10 | 1500.27 | 16-SEP-16:10 | 371.16 | 17-SEP-11:00 | 452.52 | 16-SEP-16:10 | 0.00 | 01-SEP-00:10 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.640363E+10 | 0.160263E+10 | 2124.21 | 0.513970E+10 | 0.126393E+10 | 0.00 | ||||||||||||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Maximum of Months | 0.259042E+10 | 0.645105E+09 | 706.15 | 0.199798E+10 | 0.592434E+09 | 0.00 | 0.49 | 0.00 | 2505.76 | 1969.13 | 707.41 | 645.45 | 0.00 |
Report: DXReportMonthly
For: SPLIT OFFICE COOLING COIL
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
| March | 16902764.45 | 4402969.63 | 9.17 | 15830166.37 | 1072598.08 | 0.00 | 0.17 | 15-MAR-14:20 | 0.00 | 01-MAR-00:10 | 906.82 | 15-MAR-14:20 | 884.47 | 15-MAR-14:10 | 64.98 | 16-MAR-15:00 | 238.81 | 15-MAR-14:10 | 0.00 | 01-MAR-00:10 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 |
| May | 0.203090E+09 | 52312244.38 | 98.00 | 0.191735E+09 | 11355478.87 | 0.00 | 0.36 | 24-MAY-08:65 | 0.00 | 01-MAY-00:10 | 2078.21 | 24-MAY-08:65 | 1905.05 | 17-MAY-08:65 | 453.46 | 24-MAY-08:65 | 501.55 | 24-MAY-08:65 | 0.00 | 01-MAY-00:10 |
| June | 0.130037E+10 | 0.319933E+09 | 190.09 | 0.111526E+10 | 0.185115E+09 | 0.00 | 1.00 | 02-JUN-08:62 | 0.00 | 01-JUN-00:10 | 6968.50 | 27-JUN-07:03 | 6221.34 | 16-JUN-08:62 | 2488.74 | 27-JUN-08:04 | 1448.76 | 27-JUN-08:62 | 0.00 | 01-JUN-00:10 |
| July | 0.208649E+10 | 0.504106E+09 | 197.49 | 0.174080E+10 | 0.345691E+09 | 0.00 | 1.00 | 03-JUL-08:62 | 0.00 | 01-JUL-00:10 | 7207.60 | 21-JUL-07:02 | 6215.04 | 06-JUL-08:62 | 3232.48 | 21-JUL-07:05 | 1484.64 | 21-JUL-08:15 | 0.00 | 01-JUL-00:10 |
| August | 0.217351E+10 | 0.526898E+09 | 231.14 | 0.189852E+10 | 0.274987E+09 | 0.00 | 1.00 | 01-AUG-08:62 | 0.00 | 01-AUG-00:10 | 7148.04 | 14-AUG-07:02 | 6277.92 | 03-AUG-08:62 | 2956.69 | 14-AUG-07:03 | 1428.42 | 14-AUG-08:15 | 0.00 | 01-AUG-00:10 |
| September | 0.129492E+10 | 0.315739E+09 | 174.49 | 0.117142E+10 | 0.123500E+09 | 0.00 | 1.00 | 01-SEP-08:62 | 0.00 | 01-SEP-00:10 | 6810.17 | 14-SEP-08:62 | 6251.39 | 12-SEP-08:62 | 2261.73 | 14-SEP-08:62 | 1416.91 | 14-SEP-08:62 | 0.00 | 01-SEP-00:10 |
| October | 0.227398E+09 | 58153701.81 | 80.22 | 0.216871E+09 | 10527606.22 | 0.00 | 0.60 | 12-OCT-08:63 | 0.00 | 01-OCT-00:10 | 3542.95 | 12-OCT-08:63 | 3320.27 | 12-OCT-08:63 | 222.69 | 12-OCT-08:63 | 840.68 | 12-OCT-08:63 | 0.00 | 01-OCT-00:10 |
| November | 1394366.58 | 373150.67 | 3.33 | 1394366.58 | -0.0 | 0.00 | 0.04 | 01-NOV-12:50 | 0.00 | 01-NOV-00:10 | 215.00 | 01-NOV-12:50 | 215.00 | 01-NOV-12:50 | 0.00 | 01-NOV-13:20 | 57.43 | 01-NOV-12:50 | 0.00 | 01-NOV-00:10 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.730408E+10 | 0.178192E+10 | 983.94 | 0.635183E+10 | 0.952248E+09 | 0.00 | ||||||||||||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | -0.0 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Maximum of Months | 0.217351E+10 | 0.526898E+09 | 231.14 | 0.189852E+10 | 0.345691E+09 | 0.00 | 1.00 | 0.00 | 7207.60 | 6277.92 | 3232.48 | 1484.64 | 0.00 |
Report: DXReportMonthly
For: SPLIT GNE COOLING COIL
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 |
| June | 0.981350E+09 | 0.245809E+09 | 391.04 | 0.787559E+09 | 0.193791E+09 | 0.00 | 0.45 | 27-JUN-13:00 | 0.00 | 01-JUN-00:10 | 2051.73 | 27-JUN-13:00 | 1507.57 | 27-JUN-13:00 | 598.37 | 27-JUN-08:50 | 539.15 | 27-JUN-13:00 | 0.00 | 01-JUN-00:10 |
| July | 0.260142E+10 | 0.645658E+09 | 707.08 | 0.200735E+10 | 0.594075E+09 | 0.00 | 0.51 | 20-JUL-16:02 | 0.00 | 01-JUL-02:30 | 2348.11 | 20-JUL-16:02 | 1756.19 | 21-JUL-16:15 | 706.64 | 21-JUL-03:00 | 598.62 | 20-JUL-16:02 | 0.00 | 01-JUL-00:10 |
| August | 0.209754E+10 | 0.526205E+09 | 670.90 | 0.175045E+10 | 0.347087E+09 | 0.00 | 0.48 | 13-AUG-16:05 | 0.00 | 01-AUG-04:00 | 2216.26 | 13-AUG-16:05 | 1704.21 | 09-AUG-16:04 | 597.74 | 15-AUG-13:00 | 566.09 | 13-AUG-15:10 | 0.00 | 01-AUG-00:10 |
| September | 0.689213E+09 | 0.171727E+09 | 384.32 | 0.560392E+09 | 0.128821E+09 | 0.00 | 0.35 | 16-SEP-16:10 | 0.00 | 01-SEP-00:10 | 1585.35 | 16-SEP-16:10 | 1325.10 | 16-SEP-16:10 | 371.87 | 15-SEP-20:00 | 401.90 | 16-SEP-16:10 | 0.00 | 01-SEP-00:10 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.636953E+10 | 0.158940E+10 | 2153.34 | 0.510575E+10 | 0.126377E+10 | 0.00 | ||||||||||||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Maximum of Months | 0.260142E+10 | 0.645658E+09 | 707.08 | 0.200735E+10 | 0.594075E+09 | 0.00 | 0.51 | 0.00 | 2348.11 | 1756.19 | 706.64 | 598.62 | 0.00 |
Report: DXReportMonthly
For: SPLIT GN1 COOLING COIL
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 |
| June | 0.868475E+09 | 0.217603E+09 | 418.06 | 0.689146E+09 | 0.179329E+09 | 0.00 | 0.40 | 27-JUN-13:00 | 0.00 | 01-JUN-00:10 | 1689.65 | 27-JUN-17:10 | 1193.10 | 27-JUN-13:00 | 518.40 | 27-JUN-17:10 | 437.95 | 27-JUN-13:00 | 0.00 | 01-JUN-00:10 |
| July | 0.228211E+10 | 0.566783E+09 | 722.77 | 0.173848E+10 | 0.543635E+09 | 0.00 | 0.47 | 20-JUL-16:02 | 0.00 | 01-JUL-06:00 | 1998.21 | 20-JUL-16:02 | 1457.13 | 21-JUL-16:30 | 627.42 | 21-JUL-03:00 | 511.65 | 20-JUL-16:02 | 0.00 | 01-JUL-00:10 |
| August | 0.183972E+10 | 0.461927E+09 | 700.27 | 0.151577E+10 | 0.323952E+09 | 0.00 | 0.45 | 13-AUG-16:05 | 0.00 | 01-AUG-05:00 | 1879.04 | 13-AUG-16:05 | 1398.97 | 09-AUG-16:15 | 518.60 | 14-AUG-07:40 | 480.69 | 13-AUG-16:05 | 0.00 | 01-AUG-00:10 |
| September | 0.633418E+09 | 0.157685E+09 | 418.85 | 0.506817E+09 | 0.126601E+09 | 0.00 | 0.33 | 16-SEP-16:10 | 0.00 | 01-SEP-00:10 | 1364.73 | 16-SEP-16:10 | 1135.04 | 16-SEP-16:10 | 362.30 | 15-SEP-20:00 | 346.87 | 16-SEP-16:10 | 0.00 | 01-SEP-00:10 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.562373E+10 | 0.140400E+10 | 2259.96 | 0.445021E+10 | 0.117352E+10 | 0.00 | ||||||||||||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Maximum of Months | 0.228211E+10 | 0.566783E+09 | 722.77 | 0.173848E+10 | 0.543635E+09 | 0.00 | 0.47 | 0.00 | 1998.21 | 1457.13 | 627.42 | 511.65 | 0.00 |
Report: DXReportMonthly
For: SPLIT GN2 COOLING COIL
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 |
| June | 0.866994E+09 | 0.217224E+09 | 415.92 | 0.687824E+09 | 0.179170E+09 | 0.00 | 0.40 | 27-JUN-13:00 | 0.00 | 01-JUN-00:10 | 1681.18 | 27-JUN-17:10 | 1196.68 | 27-JUN-13:00 | 516.49 | 27-JUN-17:10 | 438.89 | 27-JUN-13:00 | 0.00 | 01-JUN-00:10 |
| July | 0.228327E+10 | 0.567036E+09 | 722.36 | 0.173939E+10 | 0.543882E+09 | 0.00 | 0.47 | 20-JUL-16:02 | 0.00 | 01-JUL-06:00 | 1997.79 | 20-JUL-16:02 | 1458.49 | 21-JUL-16:30 | 627.55 | 21-JUL-03:00 | 511.48 | 20-JUL-16:02 | 0.00 | 01-JUL-00:10 |
| August | 0.183931E+10 | 0.461811E+09 | 700.68 | 0.151538E+10 | 0.323935E+09 | 0.00 | 0.44 | 13-AUG-16:05 | 0.00 | 01-AUG-05:00 | 1871.10 | 13-AUG-16:05 | 1395.57 | 09-AUG-16:15 | 518.01 | 14-AUG-07:40 | 478.71 | 13-AUG-16:05 | 0.00 | 01-AUG-00:10 |
| September | 0.636822E+09 | 0.158534E+09 | 421.28 | 0.509826E+09 | 0.126996E+09 | 0.00 | 0.33 | 16-SEP-16:10 | 0.00 | 01-SEP-00:10 | 1363.31 | 16-SEP-16:10 | 1133.96 | 16-SEP-16:10 | 362.99 | 15-SEP-20:00 | 346.50 | 16-SEP-16:10 | 0.00 | 01-SEP-00:10 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.562640E+10 | 0.140460E+10 | 2260.24 | 0.445242E+10 | 0.117398E+10 | 0.00 | ||||||||||||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Maximum of Months | 0.228327E+10 | 0.567036E+09 | 722.36 | 0.173939E+10 | 0.543882E+09 | 0.00 | 0.47 | 0.00 | 1997.79 | 1458.49 | 627.55 | 511.48 | 0.00 |
Report: DXReportMonthly
For: SPLIT GS1 COOLING COIL
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
| March | 1761378.03 | 468962.37 | 4.83 | 1732245.46 | 29132.56 | 0.00 | 0.03 | 15-MAR-16:30 | 0.00 | 01-MAR-00:10 | 137.77 | 15-MAR-16:30 | 135.26 | 15-MAR-16:30 | 3.54 | 15-MAR-17:50 | 36.53 | 15-MAR-16:30 | 0.00 | 01-MAR-00:10 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 |
| May | 15844479.86 | 4158792.99 | 30.17 | 15226252.21 | 618227.64 | 0.00 | 0.09 | 14-MAY-15:10 | 0.00 | 01-MAY-00:10 | 374.84 | 14-MAY-15:10 | 307.63 | 14-MAY-15:10 | 67.21 | 14-MAY-15:10 | 97.74 | 14-MAY-15:10 | 0.00 | 01-MAY-00:10 |
| June | 0.108096E+10 | 0.271361E+09 | 475.97 | 0.880314E+09 | 0.200648E+09 | 0.00 | 0.44 | 27-JUN-13:00 | 0.00 | 01-JUN-00:10 | 1982.60 | 27-JUN-13:00 | 1478.82 | 27-JUN-13:00 | 509.73 | 27-JUN-16:03 | 522.59 | 27-JUN-13:00 | 0.00 | 01-JUN-00:10 |
| July | 0.263171E+10 | 0.653766E+09 | 726.94 | 0.204292E+10 | 0.588789E+09 | 0.00 | 0.48 | 21-JUL-13:30 | 0.00 | 01-JUL-06:00 | 2141.08 | 20-JUL-13:30 | 1763.66 | 21-JUL-13:30 | 658.10 | 15-JUL-12:50 | 566.93 | 21-JUL-13:30 | 0.00 | 01-JUL-00:10 |
| August | 0.238631E+10 | 0.597782E+09 | 727.32 | 0.201316E+10 | 0.373144E+09 | 0.00 | 0.52 | 13-AUG-15:20 | 0.00 | 01-AUG-07:35 | 2356.52 | 13-AUG-15:30 | 1833.51 | 10-AUG-15:10 | 568.96 | 13-AUG-16:05 | 607.33 | 13-AUG-15:20 | 0.00 | 01-AUG-00:10 |
| September | 0.137296E+10 | 0.343160E+09 | 593.47 | 0.119234E+10 | 0.180615E+09 | 0.00 | 0.45 | 21-SEP-15:10 | 0.00 | 01-SEP-00:10 | 1941.58 | 21-SEP-15:10 | 1892.72 | 21-SEP-15:10 | 402.80 | 15-SEP-20:00 | 490.58 | 21-SEP-15:10 | 0.00 | 01-SEP-00:10 |
| October | 67367609.59 | 17363945.09 | 87.32 | 65186285.05 | 2181324.53 | 0.00 | 0.25 | 11-OCT-15:10 | 0.00 | 01-OCT-00:10 | 1030.87 | 11-OCT-15:10 | 1030.87 | 11-OCT-15:10 | 70.65 | 12-OCT-21:05 | 261.62 | 11-OCT-15:10 | 0.00 | 01-OCT-00:10 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.755692E+10 | 0.188806E+10 | 2646.01 | 0.621089E+10 | 0.134603E+10 | 0.00 | ||||||||||||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Maximum of Months | 0.263171E+10 | 0.653766E+09 | 727.32 | 0.204292E+10 | 0.588789E+09 | 0.00 | 0.52 | 0.00 | 2356.52 | 1892.72 | 658.10 | 607.33 | 0.00 |
Report: DXReportMonthly
For: SPLIT GS2 COOLING COIL
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
| March | 1610262.51 | 428885.32 | 4.83 | 1584210.36 | 26052.14 | 0.00 | 0.03 | 15-MAR-16:20 | 0.00 | 01-MAR-00:10 | 130.96 | 15-MAR-16:20 | 128.61 | 15-MAR-16:20 | 3.14 | 15-MAR-17:50 | 34.74 | 15-MAR-16:20 | 0.00 | 01-MAR-00:10 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 |
| May | 23892882.29 | 6265343.94 | 41.33 | 23127876.16 | 765006.13 | 0.00 | 0.09 | 14-MAY-15:10 | 0.00 | 01-MAY-00:10 | 404.45 | 14-MAY-15:10 | 333.04 | 14-MAY-15:10 | 71.41 | 14-MAY-15:10 | 105.41 | 14-MAY-15:10 | 0.00 | 01-MAY-00:10 |
| June | 0.119460E+10 | 0.299557E+09 | 509.53 | 0.978815E+09 | 0.215780E+09 | 0.00 | 0.45 | 27-JUN-13:00 | 0.00 | 01-JUN-00:10 | 2055.35 | 27-JUN-13:00 | 1545.50 | 27-JUN-13:00 | 517.67 | 27-JUN-16:03 | 541.08 | 27-JUN-13:00 | 0.00 | 01-JUN-00:10 |
| July | 0.287636E+10 | 0.713196E+09 | 738.32 | 0.225264E+10 | 0.623721E+09 | 0.00 | 0.50 | 21-JUL-13:30 | 0.00 | 01-JUL-06:00 | 2239.62 | 15-JUL-14:10 | 1847.93 | 21-JUL-13:30 | 678.75 | 15-JUL-12:40 | 589.19 | 21-JUL-13:30 | 0.00 | 01-JUL-00:10 |
| August | 0.261987E+10 | 0.654881E+09 | 734.25 | 0.222197E+10 | 0.397899E+09 | 0.00 | 0.55 | 13-AUG-15:20 | 0.00 | 03-AUG-07:25 | 2492.54 | 13-AUG-15:20 | 1949.90 | 13-AUG-15:10 | 585.01 | 14-AUG-07:40 | 640.82 | 13-AUG-15:20 | 0.00 | 01-AUG-00:10 |
| September | 0.151415E+10 | 0.378148E+09 | 621.69 | 0.132102E+10 | 0.193126E+09 | 0.00 | 0.46 | 21-SEP-15:10 | 0.00 | 01-SEP-05:00 | 2014.06 | 16-SEP-13:30 | 1947.07 | 21-SEP-15:10 | 432.15 | 17-SEP-11:00 | 509.52 | 16-SEP-13:30 | 0.00 | 01-SEP-00:10 |
| October | 79216186.77 | 20419919.31 | 97.47 | 76558995.15 | 2657191.62 | 0.00 | 0.25 | 11-OCT-15:10 | 0.00 | 01-OCT-00:10 | 1059.03 | 11-OCT-15:10 | 1059.03 | 11-OCT-15:10 | 75.57 | 12-OCT-21:05 | 268.55 | 11-OCT-15:10 | 0.00 | 01-OCT-00:10 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.830969E+10 | 0.207289E+10 | 2747.43 | 0.687571E+10 | 0.143397E+10 | 0.00 | ||||||||||||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Maximum of Months | 0.287636E+10 | 0.713196E+09 | 738.32 | 0.225264E+10 | 0.623721E+09 | 0.00 | 0.55 | 0.00 | 2492.54 | 1949.90 | 678.75 | 640.82 | 0.00 |
Report: DXReportMonthly
For: SPLIT MSW COOLING COIL
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
| March | 0.136795E+09 | 35251335.35 | 32.74 | 0.129490E+09 | 7305306.71 | 0.00 | 0.25 | 15-MAR-13:50 | 0.00 | 01-MAR-00:10 | 3149.73 | 15-MAR-13:50 | 3146.46 | 15-MAR-13:50 | 291.47 | 14-MAR-13:30 | 820.78 | 15-MAR-13:50 | 0.00 | 01-MAR-00:10 |
| April | 0.150564E+09 | 39543642.50 | 54.32 | 0.150535E+09 | 28708.79 | 0.00 | 0.17 | 09-APR-16:03 | 0.00 | 01-APR-00:10 | 2052.34 | 09-APR-16:03 | 2052.34 | 09-APR-16:03 | 6.46 | 30-APR-17:30 | 527.94 | 09-APR-16:03 | 0.00 | 01-APR-00:10 |
| May | 0.141156E+10 | 0.363808E+09 | 345.78 | 0.137251E+10 | 39044012.22 | 0.00 | 0.35 | 14-MAY-14:30 | 0.00 | 01-MAY-00:10 | 4620.40 | 14-MAY-14:30 | 4054.67 | 14-MAY-14:40 | 606.64 | 14-MAY-13:20 | 1159.88 | 14-MAY-14:30 | 0.00 | 01-MAY-00:10 |
| June | 0.495205E+10 | 0.124193E+10 | 632.21 | 0.424057E+10 | 0.711482E+09 | 0.00 | 0.49 | 27-JUN-16:23 | 0.00 | 01-JUN-05:05 | 6713.03 | 27-JUN-16:23 | 5287.74 | 12-JUN-15:20 | 1608.82 | 27-JUN-16:23 | 1641.35 | 27-JUN-16:40 | 0.00 | 01-JUN-00:10 |
| July | 0.808663E+10 | 0.201361E+10 | 738.26 | 0.648019E+10 | 0.160644E+10 | 0.00 | 0.52 | 19-JUL-15:10 | 0.00 | 01-JUL-06:00 | 6886.68 | 15-JUL-15:10 | 5524.49 | 19-JUL-15:10 | 1922.28 | 15-JUL-12:40 | 1811.35 | 19-JUL-15:10 | 0.00 | 01-JUL-00:10 |
| August | 0.669653E+10 | 0.168277E+10 | 724.34 | 0.574096E+10 | 0.955577E+09 | 0.00 | 0.56 | 13-AUG-15:30 | 0.00 | 03-AUG-04:00 | 7595.29 | 13-AUG-15:30 | 5996.29 | 10-AUG-16:10 | 1638.70 | 13-AUG-15:30 | 1945.19 | 13-AUG-15:30 | 0.00 | 01-AUG-00:10 |
| September | 0.358682E+10 | 0.898842E+09 | 551.44 | 0.316178E+10 | 0.425047E+09 | 0.00 | 0.48 | 21-SEP-16:10 | 0.00 | 01-SEP-00:10 | 6217.18 | 21-SEP-16:10 | 6067.17 | 21-SEP-16:10 | 1017.26 | 15-SEP-11:20 | 1561.06 | 21-SEP-16:10 | 0.00 | 01-SEP-00:10 |
| October | 0.299865E+09 | 77084070.58 | 94.13 | 0.291645E+09 | 8220746.47 | 0.00 | 0.33 | 11-OCT-16:10 | 0.00 | 01-OCT-00:10 | 4135.17 | 11-OCT-16:10 | 4135.17 | 11-OCT-16:10 | 243.00 | 12-OCT-15:30 | 1035.11 | 11-OCT-16:10 | 0.00 | 01-OCT-00:10 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.253208E+11 | 0.635284E+10 | 3173.22 | 0.215677E+11 | 0.375315E+10 | 0.00 | ||||||||||||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Maximum of Months | 0.808663E+10 | 0.201361E+10 | 738.26 | 0.648019E+10 | 0.160644E+10 | 0.00 | 0.56 | 0.00 | 7595.29 | 6067.17 | 1922.28 | 1945.19 | 0.00 |
Report: DXReportMonthly
For: SPLIT MNW COOLING COIL
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
| March | 44049262.37 | 11495466.83 | 15.67 | 42593701.90 | 1455560.47 | 0.00 | 0.15 | 15-MAR-17:10 | 0.00 | 01-MAR-00:10 | 1728.25 | 15-MAR-17:10 | 1677.23 | 15-MAR-17:10 | 63.17 | 15-MAR-18:00 | 448.81 | 15-MAR-16:40 | 0.00 | 01-MAR-00:10 |
| April | 857810.16 | 225639.39 | 1.50 | 857810.16 | 0.00 | 0.00 | 0.05 | 09-APR-16:20 | 0.00 | 01-APR-00:10 | 524.49 | 09-APR-16:20 | 524.49 | 09-APR-16:20 | 0.00 | 09-APR-16:20 | 137.48 | 09-APR-16:20 | 0.00 | 01-APR-00:10 |
| May | 0.815690E+09 | 0.210555E+09 | 254.34 | 0.788425E+09 | 27265105.93 | 0.00 | 0.28 | 14-MAY-15:10 | 0.00 | 01-MAY-00:10 | 3477.24 | 14-MAY-15:10 | 3352.03 | 31-MAY-18:00 | 478.41 | 14-MAY-14:30 | 888.02 | 14-MAY-15:10 | 0.00 | 01-MAY-00:10 |
| June | 0.448615E+10 | 0.112464E+10 | 616.90 | 0.379512E+10 | 0.691024E+09 | 0.00 | 0.49 | 27-JUN-17:05 | 0.00 | 01-JUN-05:05 | 6517.82 | 27-JUN-17:10 | 4887.41 | 27-JUN-17:05 | 1658.54 | 27-JUN-16:23 | 1593.62 | 27-JUN-17:00 | 0.00 | 01-JUN-00:10 |
| July | 0.739812E+10 | 0.184333E+10 | 739.95 | 0.585729E+10 | 0.154084E+10 | 0.00 | 0.49 | 11-JUL-18:00 | 0.00 | 04-JUL-05:03 | 6249.91 | 11-JUL-18:00 | 5085.76 | 11-JUL-18:00 | 1841.27 | 05-JUL-16:12 | 1634.01 | 15-JUL-15:00 | 0.00 | 01-JUL-00:10 |
| August | 0.559953E+10 | 0.141075E+10 | 715.16 | 0.472053E+10 | 0.878998E+09 | 0.00 | 0.49 | 13-AUG-15:30 | 0.00 | 03-AUG-03:20 | 6348.67 | 13-AUG-15:30 | 5024.98 | 10-AUG-16:30 | 1526.69 | 13-AUG-15:30 | 1638.78 | 13-AUG-15:30 | 0.00 | 01-AUG-00:10 |
| September | 0.205505E+10 | 0.515661E+09 | 437.24 | 0.171910E+10 | 0.335947E+09 | 0.00 | 0.36 | 16-SEP-16:10 | 0.00 | 01-SEP-00:10 | 4469.11 | 16-SEP-16:10 | 3793.85 | 16-SEP-16:10 | 951.55 | 25-SEP-16:25 | 1135.36 | 16-SEP-16:10 | 0.00 | 01-SEP-00:10 |
| October | 3732081.57 | 975114.15 | 3.83 | 3717365.35 | 14716.22 | 0.00 | 0.05 | 11-OCT-16:30 | 0.00 | 01-OCT-00:10 | 621.28 | 11-OCT-16:30 | 619.13 | 11-OCT-16:30 | 4.43 | 11-OCT-17:10 | 161.91 | 11-OCT-16:30 | 0.00 | 01-OCT-00:10 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.204032E+11 | 0.511762E+10 | 2784.59 | 0.169276E+11 | 0.347554E+10 | 0.00 | ||||||||||||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Maximum of Months | 0.739812E+10 | 0.184333E+10 | 739.95 | 0.585729E+10 | 0.154084E+10 | 0.00 | 0.49 | 0.00 | 6517.82 | 5085.76 | 1841.27 | 1638.78 | 0.00 |
Report: DXReportMonthly
For: SPLIT MSE COOLING COIL
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
| March | 0.150056E+09 | 38528039.43 | 36.70 | 0.141670E+09 | 8385600.28 | 0.00 | 0.29 | 15-MAR-13:40 | 0.00 | 01-MAR-00:10 | 3184.02 | 15-MAR-13:40 | 3180.55 | 15-MAR-13:40 | 314.54 | 14-MAR-13:00 | 823.02 | 15-MAR-13:40 | 0.00 | 01-MAR-00:10 |
| April | 0.181032E+09 | 47533740.31 | 67.08 | 0.180932E+09 | 99837.73 | 0.00 | 0.17 | 22-APR-13:40 | 0.00 | 01-APR-00:10 | 1782.31 | 22-APR-13:40 | 1782.31 | 22-APR-13:40 | 18.42 | 09-APR-10:10 | 465.53 | 22-APR-13:40 | 0.00 | 01-APR-00:10 |
| May | 0.140961E+10 | 0.363212E+09 | 368.58 | 0.137108E+10 | 38529719.15 | 0.00 | 0.34 | 14-MAY-14:10 | 0.00 | 01-MAY-00:10 | 3964.79 | 14-MAY-14:10 | 3449.75 | 14-MAY-15:10 | 582.71 | 14-MAY-13:20 | 990.87 | 14-MAY-14:30 | 0.00 | 01-MAY-00:10 |
| June | 0.485786E+10 | 0.121460E+10 | 643.75 | 0.415096E+10 | 0.706903E+09 | 0.00 | 0.55 | 27-JUN-13:00 | 0.00 | 01-JUN-05:05 | 6498.50 | 27-JUN-13:00 | 5158.54 | 12-JUN-13:00 | 1641.10 | 18-JUN-07:40 | 1692.60 | 27-JUN-13:00 | 0.00 | 01-JUN-00:10 |
| July | 0.812646E+10 | 0.201323E+10 | 739.22 | 0.650874E+10 | 0.161772E+10 | 0.00 | 0.55 | 21-JUL-13:30 | 0.00 | 03-JUL-03:40 | 6458.17 | 20-JUL-13:00 | 5450.34 | 21-JUL-13:30 | 1904.79 | 15-JUL-12:40 | 1692.35 | 21-JUL-13:30 | 0.00 | 01-JUL-00:10 |
| August | 0.668989E+10 | 0.167331E+10 | 725.83 | 0.572747E+10 | 0.962418E+09 | 0.00 | 0.55 | 13-AUG-15:10 | 0.00 | 03-AUG-02:50 | 6641.15 | 13-AUG-15:20 | 5464.80 | 10-AUG-14:10 | 1544.47 | 13-AUG-16:05 | 1705.46 | 13-AUG-15:10 | 0.00 | 01-AUG-00:10 |
| September | 0.366182E+10 | 0.914626E+09 | 555.82 | 0.322852E+10 | 0.433300E+09 | 0.00 | 0.47 | 21-SEP-13:30 | 0.00 | 01-SEP-00:10 | 5546.90 | 16-SEP-13:30 | 5300.25 | 21-SEP-14:10 | 1069.02 | 15-SEP-11:10 | 1399.61 | 16-SEP-13:30 | 0.00 | 01-SEP-00:10 |
| October | 0.305880E+09 | 78600505.95 | 105.83 | 0.298508E+09 | 7371840.33 | 0.00 | 0.32 | 11-OCT-12:40 | 0.00 | 01-OCT-00:10 | 3559.92 | 11-OCT-12:40 | 3559.92 | 11-OCT-12:40 | 167.81 | 12-OCT-15:30 | 894.04 | 11-OCT-12:40 | 0.00 | 01-OCT-00:10 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.253826E+11 | 0.634365E+10 | 3242.82 | 0.216079E+11 | 0.377473E+10 | 0.00 | ||||||||||||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Maximum of Months | 0.812646E+10 | 0.201323E+10 | 739.22 | 0.650874E+10 | 0.161772E+10 | 0.00 | 0.55 | 0.00 | 6641.15 | 5464.80 | 1904.79 | 1705.46 | 0.00 |
Report: DXReportMonthly
For: SPLIT MNE COOLING COIL
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
| March | 50059107.42 | 13034939.90 | 20.33 | 48280583.77 | 1778523.65 | 0.00 | 0.15 | 15-MAR-16:20 | 0.00 | 01-MAR-00:10 | 1622.68 | 15-MAR-16:20 | 1582.07 | 15-MAR-16:20 | 59.15 | 15-MAR-18:00 | 422.19 | 15-MAR-16:20 | 0.00 | 01-MAR-00:10 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 |
| May | 0.783817E+09 | 0.202409E+09 | 281.94 | 0.757257E+09 | 26560227.71 | 0.00 | 0.26 | 14-MAY-15:10 | 0.00 | 01-MAY-00:10 | 2885.78 | 14-MAY-15:10 | 2588.05 | 23-MAY-16:10 | 403.91 | 14-MAY-13:30 | 738.00 | 14-MAY-15:10 | 0.00 | 01-MAY-00:10 |
| June | 0.438910E+10 | 0.109743E+10 | 632.78 | 0.370351E+10 | 0.685598E+09 | 0.00 | 0.50 | 27-JUN-13:00 | 0.00 | 01-JUN-05:05 | 5663.18 | 27-JUN-13:00 | 4510.60 | 12-JUN-11:00 | 1602.64 | 18-JUN-07:40 | 1482.87 | 27-JUN-13:00 | 0.00 | 01-JUN-00:10 |
| July | 0.743706E+10 | 0.184439E+10 | 737.06 | 0.588519E+10 | 0.155187E+10 | 0.00 | 0.51 | 20-JUL-16:02 | 0.00 | 03-JUL-03:20 | 5864.46 | 20-JUL-16:02 | 4462.56 | 21-JUL-10:40 | 1700.12 | 21-JUL-03:00 | 1498.28 | 20-JUL-16:02 | 0.00 | 01-JUL-00:10 |
| August | 0.559238E+10 | 0.140358E+10 | 713.00 | 0.470640E+10 | 0.885979E+09 | 0.00 | 0.47 | 13-AUG-15:10 | 0.00 | 02-AUG-04:40 | 5420.61 | 13-AUG-16:05 | 4133.26 | 09-AUG-16:04 | 1450.07 | 15-AUG-13:00 | 1398.80 | 13-AUG-15:10 | 0.00 | 01-AUG-00:10 |
| September | 0.210608E+10 | 0.527453E+09 | 482.53 | 0.176069E+10 | 0.345388E+09 | 0.00 | 0.34 | 16-SEP-13:00 | 0.00 | 01-SEP-00:10 | 3778.17 | 16-SEP-16:10 | 3175.11 | 16-SEP-13:00 | 908.07 | 16-SEP-07:25 | 969.20 | 16-SEP-13:00 | 0.00 | 01-SEP-00:10 |
| October | 240528.53 | 63198.89 | 1.27 | 239991.57 | 536.95 | 0.00 | 0.01 | 05-OCT-16:08 | 0.00 | 01-OCT-00:10 | 143.06 | 05-OCT-16:08 | 143.06 | 05-OCT-16:08 | 0.29 | 11-OCT-16:30 | 37.63 | 05-OCT-16:08 | 0.00 | 01-OCT-00:10 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.203587E+11 | 0.508836E+10 | 2868.90 | 0.168616E+11 | 0.349718E+10 | 0.00 | ||||||||||||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Maximum of Months | 0.743706E+10 | 0.184439E+10 | 737.06 | 0.588519E+10 | 0.155187E+10 | 0.00 | 0.51 | 0.00 | 5864.46 | 4510.60 | 1700.12 | 1498.28 | 0.00 |
Report: DXReportMonthly
For: SPLIT MN1 COOLING COIL
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
| March | 43200670.48 | 11248983.90 | 25.80 | 41260886.67 | 1939783.81 | 0.00 | 0.14 | 15-MAR-17:10 | 0.00 | 01-MAR-00:10 | 1316.22 | 15-MAR-17:10 | 1275.08 | 15-MAR-17:10 | 146.14 | 16-MAR-16:10 | 342.00 | 15-MAR-17:10 | 0.00 | 01-MAR-00:10 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 |
| May | 0.657872E+09 | 0.169947E+09 | 291.17 | 0.628217E+09 | 29654644.49 | 0.00 | 0.25 | 14-MAY-15:10 | 0.00 | 01-MAY-00:10 | 2451.05 | 14-MAY-15:10 | 2124.23 | 14-MAY-15:20 | 446.51 | 17-MAY-16:17 | 627.91 | 14-MAY-15:10 | 0.00 | 01-MAY-00:10 |
| June | 0.354560E+10 | 0.888627E+09 | 645.46 | 0.295202E+10 | 0.593585E+09 | 0.00 | 0.42 | 27-JUN-17:15 | 0.00 | 01-JUN-05:05 | 4379.97 | 27-JUN-17:15 | 3229.64 | 12-JUN-15:10 | 1233.58 | 18-JUN-07:40 | 1127.99 | 27-JUN-13:00 | 0.00 | 01-JUN-00:10 |
| July | 0.605459E+10 | 0.150513E+10 | 743.67 | 0.471361E+10 | 0.134097E+10 | 0.00 | 0.46 | 20-JUL-16:02 | 0.00 | 04-JUL-05:03 | 4739.06 | 20-JUL-16:02 | 3486.76 | 20-JUL-16:04 | 1434.17 | 21-JUL-03:00 | 1218.49 | 20-JUL-16:02 | 0.00 | 01-JUL-00:10 |
| August | 0.463856E+10 | 0.116642E+10 | 735.57 | 0.385475E+10 | 0.783816E+09 | 0.00 | 0.43 | 13-AUG-16:05 | 0.00 | 03-AUG-04:00 | 4415.96 | 13-AUG-16:05 | 3261.49 | 09-AUG-16:17 | 1233.47 | 14-AUG-07:40 | 1133.87 | 13-AUG-16:05 | 0.00 | 01-AUG-00:10 |
| September | 0.185335E+10 | 0.463840E+09 | 519.31 | 0.152387E+10 | 0.329475E+09 | 0.00 | 0.32 | 16-SEP-16:10 | 0.00 | 01-SEP-09:30 | 3145.57 | 16-SEP-16:10 | 2630.18 | 16-SEP-16:10 | 818.10 | 15-SEP-20:00 | 802.44 | 16-SEP-16:10 | 0.00 | 01-SEP-00:10 |
| October | 3108617.00 | 815628.57 | 7.72 | 3068554.48 | 40062.52 | 0.00 | 0.03 | 05-OCT-16:06 | 0.00 | 01-OCT-00:10 | 256.19 | 05-OCT-16:06 | 256.19 | 05-OCT-16:06 | 17.72 | 01-OCT-16:07 | 67.25 | 05-OCT-16:06 | 0.00 | 01-OCT-00:10 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.167963E+11 | 0.420604E+10 | 2968.70 | 0.137168E+11 | 0.307948E+10 | 0.00 | ||||||||||||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Maximum of Months | 0.605459E+10 | 0.150513E+10 | 743.67 | 0.471361E+10 | 0.134097E+10 | 0.00 | 0.46 | 0.00 | 4739.06 | 3486.76 | 1434.17 | 1218.49 | 0.00 |
Report: DXReportMonthly
For: SPLIT MN2 COOLING COIL
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
| March | 44203032.59 | 11507630.92 | 26.21 | 42196836.28 | 2006196.31 | 0.00 | 0.14 | 15-MAR-17:10 | 0.00 | 01-MAR-00:10 | 1324.37 | 15-MAR-17:10 | 1282.94 | 15-MAR-17:10 | 133.94 | 16-MAR-16:10 | 344.07 | 15-MAR-17:10 | 0.00 | 01-MAR-00:10 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 |
| May | 0.662179E+09 | 0.171062E+09 | 294.22 | 0.632368E+09 | 29810658.31 | 0.00 | 0.25 | 14-MAY-15:10 | 0.00 | 01-MAY-00:10 | 2435.33 | 14-MAY-15:10 | 2109.41 | 14-MAY-15:20 | 450.81 | 17-MAY-16:17 | 623.97 | 14-MAY-15:10 | 0.00 | 01-MAY-00:10 |
| June | 0.354382E+10 | 0.888174E+09 | 646.98 | 0.295048E+10 | 0.593342E+09 | 0.00 | 0.42 | 27-JUN-13:00 | 0.00 | 01-JUN-05:05 | 4358.55 | 27-JUN-17:15 | 3230.25 | 12-JUN-15:10 | 1237.26 | 18-JUN-07:40 | 1131.02 | 27-JUN-13:00 | 0.00 | 01-JUN-00:10 |
| July | 0.605682E+10 | 0.150558E+10 | 743.67 | 0.471531E+10 | 0.134151E+10 | 0.00 | 0.46 | 20-JUL-16:02 | 0.00 | 04-JUL-05:03 | 4738.92 | 20-JUL-16:02 | 3486.82 | 20-JUL-16:04 | 1434.46 | 21-JUL-03:00 | 1218.29 | 20-JUL-16:02 | 0.00 | 01-JUL-00:10 |
| August | 0.463890E+10 | 0.116645E+10 | 735.22 | 0.385483E+10 | 0.784070E+09 | 0.00 | 0.43 | 13-AUG-16:05 | 0.00 | 03-AUG-04:00 | 4397.71 | 13-AUG-16:05 | 3252.42 | 09-AUG-16:17 | 1232.81 | 14-AUG-07:40 | 1129.27 | 13-AUG-16:05 | 0.00 | 01-AUG-00:10 |
| September | 0.185971E+10 | 0.465433E+09 | 521.04 | 0.152957E+10 | 0.330139E+09 | 0.00 | 0.32 | 16-SEP-16:10 | 0.00 | 01-SEP-09:30 | 3138.74 | 16-SEP-16:10 | 2624.47 | 16-SEP-16:10 | 819.24 | 15-SEP-20:00 | 800.71 | 16-SEP-16:10 | 0.00 | 01-SEP-00:10 |
| October | 3335822.15 | 874955.64 | 7.83 | 3288582.75 | 47239.41 | 0.00 | 0.03 | 05-OCT-16:06 | 0.00 | 01-OCT-00:10 | 267.30 | 05-OCT-16:06 | 267.30 | 05-OCT-16:06 | 17.58 | 01-OCT-16:17 | 70.15 | 05-OCT-16:06 | 0.00 | 01-OCT-00:10 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.168090E+11 | 0.420909E+10 | 2975.17 | 0.137280E+11 | 0.308092E+10 | 0.00 | ||||||||||||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Maximum of Months | 0.605682E+10 | 0.150558E+10 | 743.67 | 0.471531E+10 | 0.134151E+10 | 0.00 | 0.46 | 0.00 | 4738.92 | 3486.82 | 1434.46 | 1218.29 | 0.00 |
Report: DXReportMonthly
For: SPLIT MS1 COOLING COIL
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
| March | 0.152621E+09 | 39196654.39 | 44.72 | 0.143527E+09 | 9093731.86 | 0.00 | 0.28 | 15-MAR-13:40 | 0.00 | 01-MAR-00:10 | 2825.42 | 15-MAR-13:40 | 2817.85 | 15-MAR-13:40 | 288.02 | 14-MAR-13:00 | 730.98 | 15-MAR-13:40 | 0.00 | 01-MAR-00:10 |
| April | 0.140351E+09 | 36873761.96 | 63.61 | 0.140244E+09 | 106639.10 | 0.00 | 0.17 | 09-APR-16:03 | 0.00 | 01-APR-00:10 | 1667.21 | 09-APR-16:03 | 1667.21 | 09-APR-16:03 | 17.26 | 09-APR-10:20 | 428.73 | 09-APR-16:03 | 0.00 | 01-APR-00:10 |
| May | 0.128635E+10 | 0.331987E+09 | 429.16 | 0.124239E+10 | 43963675.66 | 0.00 | 0.34 | 14-MAY-14:10 | 0.00 | 01-MAY-00:10 | 3525.93 | 14-MAY-14:10 | 3064.14 | 14-MAY-14:30 | 521.48 | 14-MAY-13:20 | 882.34 | 14-MAY-14:30 | 0.00 | 01-MAY-00:10 |
| June | 0.402062E+10 | 0.100854E+10 | 661.35 | 0.340218E+10 | 0.618441E+09 | 0.00 | 0.47 | 27-JUN-13:00 | 0.00 | 01-JUN-05:05 | 5094.80 | 27-JUN-13:00 | 3920.05 | 12-JUN-13:30 | 1268.18 | 18-JUN-07:40 | 1340.11 | 27-JUN-13:00 | 0.00 | 01-JUN-00:10 |
| July | 0.675715E+10 | 0.167902E+10 | 741.77 | 0.534140E+10 | 0.141575E+10 | 0.00 | 0.48 | 21-JUL-13:30 | 0.00 | 01-JUL-06:00 | 5217.46 | 15-JUL-14:10 | 4279.99 | 21-JUL-13:30 | 1692.17 | 15-JUL-12:40 | 1364.13 | 15-JUL-14:10 | 0.00 | 01-JUL-00:10 |
| August | 0.575324E+10 | 0.144300E+10 | 738.95 | 0.488513E+10 | 0.868113E+09 | 0.00 | 0.51 | 13-AUG-15:20 | 0.00 | 03-AUG-07:25 | 5535.22 | 13-AUG-15:20 | 4376.45 | 18-AUG-14:10 | 1279.48 | 13-AUG-16:05 | 1430.72 | 13-AUG-15:10 | 0.00 | 01-AUG-00:10 |
| September | 0.347300E+10 | 0.869247E+09 | 637.67 | 0.304923E+10 | 0.423778E+09 | 0.00 | 0.46 | 21-SEP-14:10 | 0.00 | 02-SEP-04:00 | 4804.20 | 21-SEP-14:10 | 4667.91 | 21-SEP-14:10 | 955.73 | 15-SEP-11:20 | 1203.15 | 21-SEP-14:10 | 0.00 | 01-SEP-00:10 |
| October | 0.438793E+09 | 0.112791E+09 | 168.83 | 0.424671E+09 | 14121615.14 | 0.00 | 0.33 | 11-OCT-14:30 | 0.00 | 01-OCT-00:10 | 3399.71 | 11-OCT-14:30 | 3399.71 | 11-OCT-14:30 | 208.86 | 12-OCT-21:05 | 851.42 | 11-OCT-14:30 | 0.00 | 01-OCT-00:10 |
| November | 2051508.60 | 545511.50 | 2.67 | 2051508.60 | -0.0 | 0.00 | 0.03 | 01-NOV-12:30 | 0.00 | 01-NOV-00:10 | 325.01 | 01-NOV-12:30 | 325.01 | 01-NOV-12:30 | 0.00 | 01-NOV-12:30 | 86.47 | 01-NOV-12:30 | 0.00 | 01-NOV-00:10 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.220242E+11 | 0.552119E+10 | 3488.73 | 0.186308E+11 | 0.339337E+10 | 0.00 | ||||||||||||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | -0.0 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Maximum of Months | 0.675715E+10 | 0.167902E+10 | 741.77 | 0.534140E+10 | 0.141575E+10 | 0.00 | 0.51 | 0.00 | 5535.22 | 4667.91 | 1692.17 | 1430.72 | 0.00 |
Report: DXReportMonthly
For: SPLIT MS2 COOLING COIL
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
| March | 0.153346E+09 | 39378995.26 | 44.89 | 0.144201E+09 | 9145310.15 | 0.00 | 0.28 | 15-MAR-13:40 | 0.00 | 01-MAR-00:10 | 2835.86 | 15-MAR-13:40 | 2828.08 | 15-MAR-13:40 | 289.14 | 14-MAR-13:00 | 733.50 | 15-MAR-13:40 | 0.00 | 01-MAR-00:10 |
| April | 0.146065E+09 | 38360741.87 | 64.60 | 0.145944E+09 | 120627.06 | 0.00 | 0.17 | 09-APR-16:03 | 0.00 | 01-APR-00:10 | 1688.71 | 09-APR-16:03 | 1688.71 | 09-APR-16:03 | 19.18 | 09-APR-10:20 | 434.10 | 09-APR-16:03 | 0.00 | 01-APR-00:10 |
| May | 0.129121E+10 | 0.333232E+09 | 430.06 | 0.124717E+10 | 44033270.39 | 0.00 | 0.34 | 14-MAY-14:10 | 0.00 | 01-MAY-00:10 | 3516.79 | 14-MAY-14:10 | 3053.21 | 14-MAY-14:30 | 521.29 | 14-MAY-13:20 | 879.73 | 14-MAY-14:20 | 0.00 | 01-MAY-00:10 |
| June | 0.401909E+10 | 0.100812E+10 | 660.95 | 0.340085E+10 | 0.618241E+09 | 0.00 | 0.48 | 27-JUN-13:00 | 0.00 | 01-JUN-05:05 | 5107.23 | 27-JUN-13:00 | 3931.90 | 12-JUN-13:30 | 1271.93 | 18-JUN-07:40 | 1343.03 | 27-JUN-13:00 | 0.00 | 01-JUN-00:10 |
| July | 0.675949E+10 | 0.167944E+10 | 741.84 | 0.534319E+10 | 0.141630E+10 | 0.00 | 0.49 | 21-JUL-13:30 | 0.00 | 01-JUL-06:00 | 5211.83 | 15-JUL-14:10 | 4291.95 | 21-JUL-13:30 | 1692.62 | 15-JUL-12:40 | 1362.55 | 15-JUL-14:10 | 0.00 | 01-JUL-00:10 |
| August | 0.575380E+10 | 0.144302E+10 | 738.95 | 0.488536E+10 | 0.868445E+09 | 0.00 | 0.51 | 13-AUG-15:20 | 0.00 | 03-AUG-07:25 | 5521.96 | 13-AUG-15:20 | 4385.83 | 18-AUG-14:10 | 1277.03 | 13-AUG-16:05 | 1427.67 | 13-AUG-15:10 | 0.00 | 01-AUG-00:10 |
| September | 0.347710E+10 | 0.870185E+09 | 637.87 | 0.305278E+10 | 0.424319E+09 | 0.00 | 0.46 | 21-SEP-14:10 | 0.00 | 02-SEP-03:50 | 4811.09 | 21-SEP-14:10 | 4674.75 | 21-SEP-14:10 | 958.01 | 15-SEP-11:10 | 1204.59 | 21-SEP-14:10 | 0.00 | 01-SEP-00:10 |
| October | 0.445092E+09 | 0.114404E+09 | 171.76 | 0.430798E+09 | 14294316.79 | 0.00 | 0.34 | 11-OCT-14:30 | 0.00 | 01-OCT-00:10 | 3413.87 | 11-OCT-14:30 | 3413.87 | 11-OCT-14:30 | 208.68 | 12-OCT-21:05 | 854.70 | 11-OCT-14:30 | 0.00 | 01-OCT-00:10 |
| November | 2247010.84 | 597400.84 | 3.00 | 2247010.84 | 0.00 | 0.00 | 0.04 | 01-NOV-12:00 | 0.00 | 01-NOV-00:10 | 345.43 | 01-NOV-12:00 | 345.43 | 01-NOV-12:00 | 0.00 | 01-NOV-12:10 | 91.87 | 01-NOV-12:00 | 0.00 | 01-NOV-00:10 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.220474E+11 | 0.552674E+10 | 3493.92 | 0.186525E+11 | 0.339489E+10 | 0.00 | ||||||||||||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Maximum of Months | 0.675949E+10 | 0.167944E+10 | 741.84 | 0.534319E+10 | 0.141630E+10 | 0.00 | 0.51 | 0.00 | 5521.96 | 4674.75 | 1692.62 | 1427.67 | 0.00 |
Report: DXReportMonthly
For: SPLIT TSW COOLING COIL
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
| March | 0.110085E+09 | 27988560.90 | 28.50 | 0.103947E+09 | 6137785.94 | 0.00 | 0.36 | 15-MAR-13:50 | 0.00 | 01-MAR-00:10 | 2516.43 | 15-MAR-13:50 | 2516.09 | 15-MAR-13:50 | 294.23 | 14-MAR-12:20 | 645.00 | 15-MAR-14:00 | 0.00 | 01-MAR-00:10 |
| April | 0.192316E+09 | 50170095.81 | 80.17 | 0.192053E+09 | 263628.83 | 0.00 | 0.24 | 22-APR-15:00 | 0.00 | 01-APR-00:10 | 1615.63 | 22-APR-15:00 | 1615.63 | 22-APR-15:00 | 28.37 | 30-APR-17:10 | 417.58 | 22-APR-15:00 | 0.00 | 01-APR-00:10 |
| May | 0.666824E+09 | 0.170894E+09 | 202.75 | 0.651046E+09 | 15777470.37 | 0.00 | 0.43 | 14-MAY-14:30 | 0.00 | 01-MAY-00:10 | 3133.97 | 14-MAY-14:30 | 2792.68 | 14-MAY-14:40 | 404.18 | 14-MAY-13:20 | 778.69 | 14-MAY-14:40 | 0.00 | 01-MAY-00:10 |
| June | 0.249142E+10 | 0.621557E+09 | 477.54 | 0.214625E+10 | 0.345175E+09 | 0.00 | 0.57 | 27-JUN-16:23 | 0.00 | 01-JUN-00:20 | 4343.95 | 27-JUN-16:23 | 3606.50 | 12-JUN-15:20 | 951.62 | 27-JUN-15:20 | 1084.84 | 27-JUN-13:00 | 0.00 | 01-JUN-00:10 |
| July | 0.427648E+10 | 0.106156E+10 | 647.45 | 0.346192E+10 | 0.814563E+09 | 0.00 | 0.62 | 19-JUL-15:10 | 0.00 | 01-JUL-01:10 | 4564.93 | 19-JUL-15:10 | 3752.90 | 19-JUL-15:10 | 1228.91 | 15-JUL-12:40 | 1187.90 | 19-JUL-15:10 | 0.00 | 01-JUL-00:10 |
| August | 0.337590E+10 | 0.845609E+09 | 575.88 | 0.292455E+10 | 0.451347E+09 | 0.00 | 0.65 | 13-AUG-15:30 | 0.00 | 01-AUG-02:50 | 4903.93 | 13-AUG-15:30 | 3964.94 | 10-AUG-15:30 | 989.23 | 13-AUG-15:30 | 1239.93 | 13-AUG-15:30 | 0.00 | 01-AUG-00:10 |
| September | 0.156693E+10 | 0.390740E+09 | 350.36 | 0.138423E+10 | 0.182692E+09 | 0.00 | 0.54 | 21-SEP-15:30 | 0.00 | 01-SEP-00:10 | 3879.33 | 21-SEP-15:30 | 3811.64 | 21-SEP-15:30 | 654.43 | 15-SEP-11:10 | 966.61 | 21-SEP-15:30 | 0.00 | 01-SEP-00:10 |
| October | 0.200094E+09 | 51342065.48 | 76.61 | 0.197283E+09 | 2811003.57 | 0.00 | 0.39 | 11-OCT-15:30 | 0.00 | 01-OCT-00:10 | 2715.04 | 11-OCT-15:30 | 2715.04 | 11-OCT-15:30 | 111.32 | 12-OCT-15:30 | 673.55 | 11-OCT-15:30 | 0.00 | 01-OCT-00:10 |
| November | 1105309.90 | 294804.11 | 2.83 | 1105309.90 | -0.0 | 0.00 | 0.03 | 03-NOV-15:10 | 0.00 | 01-NOV-00:10 | 197.13 | 03-NOV-15:10 | 197.13 | 03-NOV-15:10 | 0.00 | 03-NOV-15:00 | 52.52 | 03-NOV-15:10 | 0.00 | 01-NOV-00:10 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.128812E+11 | 0.322016E+10 | 2442.09 | 0.110624E+11 | 0.181877E+10 | 0.00 | ||||||||||||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | -0.0 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Maximum of Months | 0.427648E+10 | 0.106156E+10 | 647.45 | 0.346192E+10 | 0.814563E+09 | 0.00 | 0.65 | 0.00 | 4903.93 | 3964.94 | 1228.91 | 1239.93 | 0.00 |
Report: DXReportMonthly
For: SPLIT TNW COOLING COIL
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
| March | 58415971.21 | 15049974.84 | 19.83 | 55100320.17 | 3315651.04 | 0.00 | 0.23 | 15-MAR-16:30 | 0.00 | 01-MAR-00:10 | 1565.54 | 15-MAR-16:30 | 1532.07 | 15-MAR-16:30 | 139.73 | 14-MAR-14:10 | 402.77 | 15-MAR-16:30 | 0.00 | 01-MAR-00:10 |
| April | 20877389.52 | 5493714.99 | 25.50 | 20802587.07 | 74802.44 | 0.00 | 0.09 | 09-APR-16:03 | 0.00 | 01-APR-00:10 | 595.03 | 09-APR-16:03 | 595.03 | 09-APR-16:03 | 11.17 | 30-APR-17:30 | 154.98 | 09-APR-16:03 | 0.00 | 01-APR-00:10 |
| May | 0.389164E+09 | 0.100120E+09 | 149.47 | 0.377993E+09 | 11171177.36 | 0.00 | 0.34 | 14-MAY-15:10 | 0.00 | 01-MAY-00:10 | 2400.75 | 14-MAY-15:10 | 2134.03 | 14-MAY-15:10 | 309.40 | 14-MAY-14:20 | 608.38 | 14-MAY-15:10 | 0.00 | 01-MAY-00:10 |
| June | 0.225051E+10 | 0.562065E+09 | 471.00 | 0.191200E+10 | 0.338509E+09 | 0.00 | 0.56 | 27-JUN-16:40 | 0.00 | 01-JUN-00:20 | 4212.32 | 27-JUN-16:40 | 3285.85 | 12-JUN-16:05 | 972.79 | 27-JUN-16:23 | 1020.68 | 27-JUN-16:40 | 0.00 | 01-JUN-00:10 |
| July | 0.391641E+10 | 0.974644E+09 | 652.47 | 0.312909E+10 | 0.787324E+09 | 0.00 | 0.56 | 19-JUL-15:10 | 0.00 | 01-JUL-01:10 | 4097.61 | 19-JUL-15:10 | 3370.82 | 18-JUL-17:10 | 1157.06 | 05-JUL-16:12 | 1072.88 | 19-JUL-15:10 | 0.00 | 01-JUL-00:10 |
| August | 0.281438E+10 | 0.708694E+09 | 561.14 | 0.239642E+10 | 0.417964E+09 | 0.00 | 0.56 | 13-AUG-15:30 | 0.00 | 01-AUG-02:50 | 4147.30 | 13-AUG-15:30 | 3360.43 | 10-AUG-16:15 | 931.09 | 13-AUG-15:30 | 1060.35 | 13-AUG-15:30 | 0.00 | 01-AUG-00:10 |
| September | 0.859417E+09 | 0.215009E+09 | 278.36 | 0.713635E+09 | 0.145782E+09 | 0.00 | 0.41 | 16-SEP-16:10 | 0.00 | 01-SEP-00:10 | 2888.60 | 16-SEP-16:10 | 2488.64 | 16-SEP-16:10 | 562.94 | 25-SEP-16:25 | 729.37 | 16-SEP-16:10 | 0.00 | 01-SEP-00:10 |
| October | 13143563.95 | 3402320.48 | 9.00 | 13063859.61 | 79704.34 | 0.00 | 0.16 | 11-OCT-16:30 | 0.00 | 01-OCT-00:10 | 1039.46 | 11-OCT-16:30 | 1035.26 | 11-OCT-16:30 | 9.42 | 11-OCT-17:20 | 266.72 | 11-OCT-16:30 | 0.00 | 01-OCT-00:10 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.103223E+11 | 0.258448E+10 | 2166.77 | 0.861810E+10 | 0.170422E+10 | 0.00 | ||||||||||||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Maximum of Months | 0.391641E+10 | 0.974644E+09 | 652.47 | 0.312909E+10 | 0.787324E+09 | 0.00 | 0.56 | 0.00 | 4212.32 | 3370.82 | 1157.06 | 1072.88 | 0.00 |
Report: DXReportMonthly
For: SPLIT TSE COOLING COIL
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
| March | 0.116795E+09 | 29451334.51 | 27.00 | 0.109932E+09 | 6863311.32 | 0.00 | 0.42 | 15-MAR-13:50 | 0.00 | 01-MAR-00:10 | 2502.24 | 15-MAR-13:50 | 2502.24 | 15-MAR-13:50 | 358.79 | 14-MAR-12:00 | 635.35 | 15-MAR-13:50 | 0.00 | 01-MAR-00:10 |
| April | 0.188665E+09 | 49213542.50 | 87.33 | 0.188624E+09 | 41019.85 | 0.00 | 0.26 | 22-APR-14:00 | 0.00 | 01-APR-00:10 | 1462.93 | 22-APR-14:00 | 1462.93 | 22-APR-14:00 | 7.76 | 30-APR-16:10 | 376.96 | 22-APR-14:00 | 0.00 | 01-APR-00:10 |
| May | 0.623881E+09 | 0.159679E+09 | 215.58 | 0.609346E+09 | 14535203.72 | 0.00 | 0.44 | 14-MAY-14:10 | 0.00 | 01-MAY-00:10 | 2726.82 | 14-MAY-14:10 | 2394.16 | 14-MAY-14:30 | 396.51 | 14-MAY-13:10 | 671.29 | 14-MAY-14:20 | 0.00 | 01-MAY-00:10 |
| June | 0.242725E+10 | 0.602101E+09 | 489.91 | 0.208242E+10 | 0.344823E+09 | 0.00 | 0.68 | 27-JUN-13:00 | 0.00 | 01-JUN-00:10 | 4379.38 | 27-JUN-13:00 | 3552.13 | 12-JUN-13:00 | 956.58 | 18-JUN-07:40 | 1117.98 | 27-JUN-13:00 | 0.00 | 01-JUN-00:10 |
| July | 0.429335E+10 | 0.105727E+10 | 662.03 | 0.346921E+10 | 0.824143E+09 | 0.00 | 0.69 | 21-JUL-13:30 | 0.00 | 01-JUL-00:40 | 4291.92 | 21-JUL-13:30 | 3741.99 | 21-JUL-13:30 | 1217.82 | 15-JUL-12:40 | 1115.36 | 21-JUL-13:30 | 0.00 | 01-JUL-00:10 |
| August | 0.336519E+10 | 0.836765E+09 | 583.13 | 0.290768E+10 | 0.457507E+09 | 0.00 | 0.67 | 13-AUG-15:20 | 0.00 | 01-AUG-02:30 | 4273.88 | 13-AUG-15:20 | 3652.46 | 18-AUG-13:40 | 926.14 | 15-AUG-13:00 | 1078.92 | 13-AUG-15:10 | 0.00 | 01-AUG-00:10 |
| September | 0.157676E+10 | 0.391059E+09 | 366.50 | 0.139017E+10 | 0.186591E+09 | 0.00 | 0.58 | 16-SEP-13:30 | 0.00 | 01-SEP-00:10 | 3644.56 | 16-SEP-13:30 | 3329.41 | 21-SEP-13:50 | 677.38 | 15-SEP-11:00 | 905.25 | 16-SEP-13:30 | 0.00 | 01-SEP-00:10 |
| October | 0.191540E+09 | 49067568.32 | 79.96 | 0.189508E+09 | 2032368.31 | 0.00 | 0.39 | 11-OCT-12:40 | 0.00 | 01-OCT-00:10 | 2337.26 | 11-OCT-12:40 | 2337.26 | 11-OCT-12:40 | 66.95 | 10-OCT-14:20 | 580.35 | 11-OCT-12:40 | 0.00 | 01-OCT-00:10 |
| November | 11620.04 | 3108.80 | 0.17 | 11620.04 | 0.00 | 0.00 | 0.00 | 03-NOV-14:40 | 0.00 | 01-NOV-00:10 | 19.37 | 03-NOV-14:40 | 19.37 | 03-NOV-14:40 | 0.00 | 01-NOV-00:10 | 5.18 | 03-NOV-14:40 | 0.00 | 01-NOV-00:10 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.127834E+11 | 0.317461E+10 | 2511.62 | 0.109469E+11 | 0.183654E+10 | 0.00 | ||||||||||||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Maximum of Months | 0.429335E+10 | 0.105727E+10 | 662.03 | 0.346921E+10 | 0.824143E+09 | 0.00 | 0.69 | 0.00 | 4379.38 | 3741.99 | 1217.82 | 1117.98 | 0.00 |
Report: DXReportMonthly
For: SPLIT TNE COOLING COIL
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
| March | 63073528.00 | 16179309.42 | 21.33 | 59197207.67 | 3876320.33 | 0.00 | 0.25 | 15-MAR-16:20 | 0.00 | 01-MAR-00:10 | 1434.56 | 15-MAR-16:20 | 1404.26 | 15-MAR-16:20 | 150.15 | 14-MAR-13:00 | 368.04 | 15-MAR-16:20 | 0.00 | 01-MAR-00:10 |
| April | 6370889.47 | 1675490.87 | 13.06 | 6370889.47 | 0.00 | 0.00 | 0.07 | 08-APR-13:00 | 0.00 | 01-APR-00:10 | 386.85 | 08-APR-13:00 | 386.85 | 08-APR-13:00 | 0.00 | 08-APR-13:10 | 101.02 | 08-APR-13:00 | 0.00 | 01-APR-00:10 |
| May | 0.319302E+09 | 82074193.38 | 140.42 | 0.309730E+09 | 9571994.10 | 0.00 | 0.34 | 14-MAY-15:10 | 0.00 | 01-MAY-00:10 | 1995.26 | 14-MAY-15:10 | 1758.09 | 14-MAY-15:10 | 282.90 | 14-MAY-13:20 | 505.58 | 14-MAY-15:10 | 0.00 | 01-MAY-00:10 |
| June | 0.218345E+10 | 0.542658E+09 | 487.59 | 0.184481E+10 | 0.338643E+09 | 0.00 | 0.61 | 27-JUN-13:00 | 0.00 | 01-JUN-00:10 | 3810.92 | 27-JUN-13:00 | 3031.94 | 12-JUN-11:30 | 943.83 | 27-JUN-08:30 | 982.28 | 27-JUN-13:00 | 0.00 | 01-JUN-00:10 |
| July | 0.394083E+10 | 0.973906E+09 | 664.99 | 0.314254E+10 | 0.798287E+09 | 0.00 | 0.60 | 21-JUL-10:40 | 0.00 | 01-JUL-00:20 | 3725.38 | 21-JUL-10:30 | 3059.82 | 21-JUL-13:30 | 995.37 | 17-JUL-07:40 | 946.99 | 20-JUL-13:00 | 0.00 | 01-JUL-00:10 |
| August | 0.280628E+10 | 0.702659E+09 | 570.07 | 0.238161E+10 | 0.424667E+09 | 0.00 | 0.56 | 13-AUG-15:10 | 0.00 | 01-AUG-02:30 | 3515.58 | 13-AUG-15:20 | 2750.22 | 09-AUG-15:20 | 887.98 | 15-AUG-13:00 | 900.23 | 13-AUG-15:10 | 0.00 | 01-AUG-00:10 |
| September | 0.829763E+09 | 0.206505E+09 | 297.42 | 0.680320E+09 | 0.149443E+09 | 0.00 | 0.41 | 16-SEP-13:00 | 0.00 | 01-SEP-00:10 | 2476.51 | 16-SEP-13:00 | 2112.47 | 16-SEP-13:30 | 561.26 | 15-SEP-10:50 | 629.91 | 16-SEP-13:00 | 0.00 | 01-SEP-00:10 |
| October | 8746408.86 | 2280735.39 | 11.17 | 8699994.96 | 46413.90 | 0.00 | 0.09 | 11-OCT-16:10 | 0.00 | 01-OCT-00:10 | 488.87 | 11-OCT-16:10 | 488.68 | 11-OCT-16:07 | 4.86 | 22-OCT-17:00 | 126.79 | 11-OCT-16:10 | 0.00 | 01-OCT-00:10 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.101578E+11 | 0.252794E+10 | 2206.04 | 0.843328E+10 | 0.172453E+10 | 0.00 | ||||||||||||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Maximum of Months | 0.394083E+10 | 0.973906E+09 | 664.99 | 0.314254E+10 | 0.798287E+09 | 0.00 | 0.61 | 0.00 | 3810.92 | 3059.82 | 995.37 | 982.28 | 0.00 |
Report: DXReportMonthly
For: SPLIT TN1 COOLING COIL
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
| March | 48136796.01 | 12400513.11 | 24.83 | 45315479.95 | 2821316.06 | 0.00 | 0.23 | 15-MAR-16:30 | 0.00 | 01-MAR-00:10 | 1206.24 | 15-MAR-16:30 | 1178.73 | 15-MAR-16:30 | 104.10 | 14-MAR-14:10 | 310.54 | 15-MAR-16:30 | 0.00 | 01-MAR-00:10 |
| April | 1085936.39 | 285283.87 | 3.61 | 1085936.39 | -0.0 | 0.00 | 0.07 | 09-APR-16:03 | 0.00 | 01-APR-00:10 | 365.62 | 09-APR-16:03 | 365.62 | 09-APR-16:03 | 0.00 | 09-APR-16:13 | 95.51 | 09-APR-16:03 | 0.00 | 01-APR-00:10 |
| May | 0.212419E+09 | 54739503.47 | 118.45 | 0.204106E+09 | 8312697.02 | 0.00 | 0.31 | 14-MAY-15:10 | 0.00 | 01-MAY-00:10 | 1688.05 | 14-MAY-15:10 | 1483.55 | 14-MAY-15:10 | 235.51 | 14-MAY-13:30 | 429.59 | 14-MAY-15:10 | 0.00 | 01-MAY-00:10 |
| June | 0.175342E+10 | 0.437829E+09 | 478.64 | 0.146034E+10 | 0.293073E+09 | 0.00 | 0.51 | 27-JUN-13:00 | 0.00 | 01-JUN-00:40 | 2930.96 | 27-JUN-13:00 | 2303.27 | 12-JUN-15:10 | 712.72 | 27-JUN-17:20 | 766.65 | 27-JUN-13:00 | 0.00 | 01-JUN-00:10 |
| July | 0.324449E+10 | 0.806074E+09 | 670.24 | 0.255131E+10 | 0.693179E+09 | 0.00 | 0.52 | 19-JUL-15:10 | 0.00 | 01-JUL-01:50 | 2969.20 | 20-JUL-16:02 | 2382.37 | 21-JUL-13:50 | 873.59 | 05-JUL-16:10 | 776.98 | 19-JUL-15:10 | 0.00 | 01-JUL-00:10 |
| August | 0.231893E+10 | 0.583234E+09 | 592.33 | 0.194241E+10 | 0.376520E+09 | 0.00 | 0.50 | 13-AUG-15:20 | 0.00 | 01-AUG-03:10 | 2856.55 | 13-AUG-16:05 | 2255.74 | 09-AUG-16:10 | 734.21 | 07-AUG-14:50 | 737.81 | 13-AUG-15:20 | 0.00 | 01-AUG-00:10 |
| September | 0.671910E+09 | 0.167070E+09 | 283.19 | 0.535859E+09 | 0.136051E+09 | 0.00 | 0.36 | 16-SEP-16:10 | 0.00 | 01-SEP-00:10 | 2002.92 | 16-SEP-16:10 | 1703.25 | 16-SEP-16:10 | 461.17 | 15-SEP-11:20 | 508.72 | 16-SEP-16:10 | 0.00 | 01-SEP-00:10 |
| October | 3706297.88 | 967541.58 | 7.00 | 3676721.89 | 29575.99 | 0.00 | 0.06 | 11-OCT-16:10 | 0.00 | 01-OCT-00:10 | 331.19 | 11-OCT-16:10 | 330.95 | 11-OCT-16:10 | 3.74 | 22-OCT-17:00 | 86.20 | 11-OCT-16:10 | 0.00 | 01-OCT-00:10 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.825409E+10 | 0.206260E+10 | 2178.29 | 0.674411E+10 | 0.150999E+10 | 0.00 | ||||||||||||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | -0.0 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Maximum of Months | 0.324449E+10 | 0.806074E+09 | 670.24 | 0.255131E+10 | 0.693179E+09 | 0.00 | 0.52 | 0.00 | 2969.20 | 2382.37 | 873.59 | 776.98 | 0.00 |
Report: DXReportMonthly
For: SPLIT TN2 COOLING COIL
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
| March | 48827218.91 | 12574627.32 | 25.00 | 45946904.17 | 2880314.74 | 0.00 | 0.23 | 15-MAR-16:30 | 0.00 | 01-MAR-00:10 | 1208.71 | 15-MAR-16:30 | 1181.32 | 15-MAR-16:20 | 105.95 | 14-MAR-14:10 | 311.09 | 15-MAR-16:30 | 0.00 | 01-MAR-00:10 |
| April | 1284824.33 | 337540.00 | 4.22 | 1284824.33 | -0.0 | 0.00 | 0.07 | 09-APR-16:03 | 0.00 | 01-APR-00:10 | 363.64 | 09-APR-16:03 | 363.64 | 09-APR-16:03 | 0.00 | 09-APR-17:02 | 94.99 | 09-APR-16:03 | 0.00 | 01-APR-00:10 |
| May | 0.214901E+09 | 55375467.77 | 120.07 | 0.206592E+09 | 8309146.58 | 0.00 | 0.31 | 14-MAY-15:10 | 0.00 | 01-MAY-00:10 | 1677.64 | 14-MAY-15:10 | 1474.28 | 14-MAY-15:10 | 235.85 | 14-MAY-13:30 | 426.93 | 14-MAY-15:10 | 0.00 | 01-MAY-00:10 |
| June | 0.175411E+10 | 0.437929E+09 | 479.47 | 0.146118E+10 | 0.292931E+09 | 0.00 | 0.52 | 27-JUN-13:00 | 0.00 | 01-JUN-00:30 | 2944.63 | 27-JUN-13:00 | 2301.04 | 12-JUN-15:10 | 709.83 | 27-JUN-16:03 | 769.67 | 27-JUN-13:00 | 0.00 | 01-JUN-00:10 |
| July | 0.324746E+10 | 0.806600E+09 | 670.52 | 0.255400E+10 | 0.693459E+09 | 0.00 | 0.52 | 19-JUL-15:10 | 0.00 | 01-JUL-01:40 | 2967.23 | 20-JUL-16:02 | 2390.95 | 21-JUL-13:50 | 868.27 | 15-JUL-12:40 | 774.33 | 19-JUL-15:10 | 0.00 | 01-JUL-00:10 |
| August | 0.232099E+10 | 0.583627E+09 | 592.00 | 0.194429E+10 | 0.376705E+09 | 0.00 | 0.50 | 13-AUG-15:20 | 0.00 | 01-AUG-03:00 | 2840.62 | 13-AUG-15:20 | 2243.99 | 09-AUG-16:04 | 733.24 | 07-AUG-14:50 | 734.47 | 13-AUG-15:20 | 0.00 | 01-AUG-00:10 |
| September | 0.675978E+09 | 0.168070E+09 | 287.53 | 0.539563E+09 | 0.136415E+09 | 0.00 | 0.36 | 16-SEP-16:10 | 0.00 | 01-SEP-00:10 | 1991.33 | 16-SEP-16:10 | 1693.12 | 16-SEP-16:10 | 464.18 | 15-SEP-11:20 | 505.75 | 16-SEP-16:10 | 0.00 | 01-SEP-00:10 |
| October | 3842203.02 | 1003176.64 | 7.50 | 3811506.98 | 30696.04 | 0.00 | 0.06 | 11-OCT-16:03 | 0.00 | 01-OCT-00:10 | 327.32 | 11-OCT-16:03 | 327.32 | 11-OCT-16:03 | 3.88 | 22-OCT-17:00 | 85.21 | 11-OCT-16:03 | 0.00 | 01-OCT-00:10 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.826739E+10 | 0.206552E+10 | 2186.32 | 0.675666E+10 | 0.151073E+10 | 0.00 | ||||||||||||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | -0.0 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Maximum of Months | 0.324746E+10 | 0.806600E+09 | 670.52 | 0.255400E+10 | 0.693459E+09 | 0.00 | 0.52 | 0.00 | 2967.23 | 2390.95 | 868.27 | 774.33 | 0.00 |
Report: DXReportMonthly
For: SPLIT TS1 COOLING COIL
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
| March | 0.102473E+09 | 25968800.48 | 32.38 | 96516134.05 | 5956814.67 | 0.00 | 0.40 | 15-MAR-13:50 | 0.00 | 01-MAR-00:10 | 2206.24 | 15-MAR-13:50 | 2204.50 | 15-MAR-13:50 | 287.20 | 14-MAR-12:10 | 562.20 | 15-MAR-13:50 | 0.00 | 01-MAR-00:10 |
| April | 0.135108E+09 | 35323682.43 | 79.33 | 0.135026E+09 | 81468.69 | 0.00 | 0.23 | 22-APR-14:10 | 0.00 | 01-APR-00:10 | 1196.28 | 22-APR-14:10 | 1196.28 | 22-APR-14:10 | 10.28 | 30-APR-16:10 | 309.74 | 22-APR-14:10 | 0.00 | 01-APR-00:10 |
| May | 0.473434E+09 | 0.121588E+09 | 217.14 | 0.459879E+09 | 13555093.32 | 0.00 | 0.42 | 14-MAY-14:10 | 0.00 | 01-MAY-00:10 | 2427.40 | 14-MAY-14:10 | 2138.45 | 14-MAY-14:30 | 354.03 | 14-MAY-13:10 | 600.16 | 14-MAY-14:20 | 0.00 | 01-MAY-00:10 |
| June | 0.199143E+10 | 0.496679E+09 | 492.38 | 0.169127E+10 | 0.300157E+09 | 0.00 | 0.59 | 27-JUN-13:00 | 0.00 | 01-JUN-00:40 | 3497.06 | 27-JUN-13:00 | 2813.51 | 12-JUN-13:40 | 732.07 | 27-JUN-13:30 | 905.84 | 27-JUN-13:00 | 0.00 | 01-JUN-00:10 |
| July | 0.360716E+10 | 0.893500E+09 | 665.03 | 0.288513E+10 | 0.722037E+09 | 0.00 | 0.61 | 21-JUL-13:30 | 0.00 | 01-JUL-02:70 | 3508.84 | 21-JUL-13:30 | 3043.14 | 21-JUL-13:30 | 1095.17 | 15-JUL-12:40 | 923.49 | 21-JUL-13:30 | 0.00 | 01-JUL-00:10 |
| August | 0.288943E+10 | 0.722293E+09 | 610.33 | 0.247707E+10 | 0.412353E+09 | 0.00 | 0.61 | 13-AUG-15:20 | 0.00 | 01-AUG-03:10 | 3609.04 | 13-AUG-15:20 | 3050.44 | 18-AUG-14:10 | 765.62 | 07-AUG-14:50 | 920.87 | 13-AUG-15:20 | 0.00 | 01-AUG-00:10 |
| September | 0.141518E+10 | 0.351966E+09 | 391.17 | 0.123757E+10 | 0.177603E+09 | 0.00 | 0.54 | 16-SEP-13:30 | 0.00 | 01-SEP-00:10 | 3126.17 | 16-SEP-13:30 | 2983.22 | 21-SEP-14:10 | 614.78 | 15-SEP-11:10 | 782.14 | 16-SEP-13:30 | 0.00 | 01-SEP-00:10 |
| October | 0.187934E+09 | 48205211.34 | 95.72 | 0.185146E+09 | 2788023.29 | 0.00 | 0.37 | 11-OCT-14:30 | 0.00 | 01-OCT-00:10 | 2082.98 | 11-OCT-14:30 | 2082.98 | 11-OCT-14:30 | 71.77 | 12-OCT-15:30 | 518.39 | 11-OCT-14:30 | 0.00 | 01-OCT-00:10 |
| November | 1553071.29 | 413610.77 | 4.32 | 1553071.29 | -0.0 | 0.00 | 0.04 | 03-NOV-14:30 | 0.00 | 01-NOV-00:10 | 210.26 | 03-NOV-14:30 | 210.26 | 03-NOV-14:30 | 0.00 | 03-NOV-14:00 | 55.93 | 03-NOV-14:30 | 0.00 | 01-NOV-00:10 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.108037E+11 | 0.269594E+10 | 2587.79 | 0.916917E+10 | 0.163453E+10 | 0.00 | ||||||||||||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | -0.0 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Maximum of Months | 0.360716E+10 | 0.893500E+09 | 665.03 | 0.288513E+10 | 0.722037E+09 | 0.00 | 0.61 | 0.00 | 3609.04 | 3050.44 | 1095.17 | 923.49 | 0.00 |
Report: DXReportMonthly
For: SPLIT TS2 COOLING COIL
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
| March | 0.103218E+09 | 26145961.41 | 32.05 | 97204879.04 | 6013401.37 | 0.00 | 0.40 | 15-MAR-13:50 | 0.00 | 01-MAR-00:10 | 2214.32 | 15-MAR-13:50 | 2212.63 | 15-MAR-13:50 | 291.57 | 14-MAR-12:10 | 563.94 | 15-MAR-13:50 | 0.00 | 01-MAR-00:10 |
| April | 0.139341E+09 | 36416904.73 | 79.92 | 0.139267E+09 | 74385.11 | 0.00 | 0.23 | 22-APR-14:10 | 0.00 | 01-APR-00:10 | 1221.74 | 22-APR-14:10 | 1221.74 | 22-APR-14:10 | 9.71 | 30-APR-16:10 | 316.03 | 22-APR-14:10 | 0.00 | 01-APR-00:10 |
| May | 0.479399E+09 | 0.123098E+09 | 219.15 | 0.465845E+09 | 13553405.02 | 0.00 | 0.42 | 14-MAY-14:10 | 0.00 | 01-MAY-00:10 | 2424.30 | 14-MAY-14:10 | 2132.70 | 14-MAY-14:30 | 354.40 | 14-MAY-13:10 | 598.64 | 14-MAY-14:10 | 0.00 | 01-MAY-00:10 |
| June | 0.199337E+10 | 0.497051E+09 | 491.71 | 0.169340E+10 | 0.299974E+09 | 0.00 | 0.60 | 27-JUN-13:00 | 0.00 | 01-JUN-00:40 | 3510.99 | 27-JUN-13:00 | 2825.22 | 12-JUN-13:30 | 732.18 | 27-JUN-13:30 | 908.71 | 27-JUN-13:00 | 0.00 | 01-JUN-00:10 |
| July | 0.361038E+10 | 0.894000E+09 | 664.82 | 0.288813E+10 | 0.722255E+09 | 0.00 | 0.61 | 21-JUL-13:30 | 0.00 | 01-JUL-02:00 | 3519.41 | 21-JUL-13:30 | 3053.89 | 21-JUL-13:30 | 1095.65 | 15-JUL-12:40 | 925.54 | 21-JUL-13:30 | 0.00 | 01-JUL-00:10 |
| August | 0.289153E+10 | 0.722586E+09 | 609.51 | 0.247903E+10 | 0.412498E+09 | 0.00 | 0.61 | 13-AUG-15:20 | 0.00 | 01-AUG-03:10 | 3597.22 | 13-AUG-15:20 | 3057.64 | 18-AUG-14:10 | 763.89 | 07-AUG-14:50 | 917.60 | 13-AUG-15:20 | 0.00 | 01-AUG-00:10 |
| September | 0.142048E+10 | 0.353179E+09 | 391.58 | 0.124263E+10 | 0.177846E+09 | 0.00 | 0.54 | 16-SEP-13:30 | 0.00 | 01-SEP-00:10 | 3133.12 | 16-SEP-13:30 | 2991.08 | 21-SEP-14:10 | 616.45 | 15-SEP-11:10 | 783.39 | 16-SEP-13:30 | 0.00 | 01-SEP-00:10 |
| October | 0.190829E+09 | 48936969.82 | 96.35 | 0.188041E+09 | 2788862.28 | 0.00 | 0.38 | 11-OCT-14:30 | 0.00 | 01-OCT-00:10 | 2090.81 | 11-OCT-14:30 | 2090.81 | 11-OCT-14:30 | 70.28 | 12-OCT-15:30 | 520.04 | 11-OCT-14:30 | 0.00 | 01-OCT-00:10 |
| November | 1748436.46 | 465440.15 | 4.90 | 1748436.46 | 0.00 | 0.00 | 0.04 | 03-NOV-14:30 | 0.00 | 01-NOV-00:10 | 228.69 | 03-NOV-14:30 | 228.69 | 03-NOV-14:30 | 0.00 | 03-NOV-15:10 | 60.80 | 03-NOV-14:30 | 0.00 | 01-NOV-00:10 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.108303E+11 | 0.270188E+10 | 2589.99 | 0.919530E+10 | 0.163500E+10 | 0.00 | ||||||||||||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Maximum of Months | 0.361038E+10 | 0.894000E+09 | 664.82 | 0.288813E+10 | 0.722255E+09 | 0.00 | 0.61 | 0.00 | 3597.22 | 3057.64 | 1095.65 | 925.54 | 0.00 |
Report: WindowReportMonthly
For: GWINDOW1 S SWA
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 180.27 | 105.03 | 75.24 | 147.54 | 225.91 | 0.00 | 0.00 | 0.00 |
| February | 206.02 | 99.18 | 106.84 | 166.82 | 219.82 | 0.00 | 0.00 | 0.00 |
| March | 247.91 | 137.55 | 110.37 | 251.18 | 154.58 | 0.00 | 0.00 | 0.00 |
| April | 210.81 | 85.55 | 125.27 | 227.42 | 114.51 | 0.00 | 0.00 | 0.00 |
| May | 182.43 | 52.89 | 129.55 | 215.39 | 72.24 | 0.00 | 0.00 | 0.00 |
| June | 177.91 | 38.10 | 139.80 | 225.33 | 51.58 | 0.00 | 0.00 | 0.00 |
| July | 180.52 | 43.36 | 137.16 | 251.51 | 34.42 | 0.00 | 0.00 | 0.00 |
| August | 201.50 | 64.10 | 137.39 | 273.53 | 47.04 | 0.00 | 0.00 | 0.00 |
| September | 239.25 | 118.00 | 121.25 | 299.03 | 78.70 | 0.00 | 0.00 | 0.00 |
| October | 226.76 | 129.79 | 96.98 | 249.06 | 116.76 | 0.00 | 0.00 | 0.00 |
| November | 162.43 | 91.95 | 70.48 | 157.65 | 148.62 | 0.00 | 0.00 | 0.00 |
| December | 151.12 | 78.23 | 72.90 | 116.93 | 221.56 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 197.17 | 86.92 | 110.25 | 215.38 | 123.30 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 151.12 | 38.10 | 70.48 | 116.93 | 34.42 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 247.91 | 137.55 | 139.80 | 299.03 | 225.91 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: GWINDOW1 W SWA
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 43.51 | 10.25 | 33.26 | 11.87 | 165.99 | 0.00 | 0.00 | 0.00 |
| February | 70.50 | 18.19 | 52.31 | 30.49 | 154.57 | 0.00 | 0.00 | 0.00 |
| March | 110.83 | 47.64 | 63.19 | 92.25 | 105.02 | 0.00 | 0.00 | 0.00 |
| April | 134.82 | 55.18 | 79.64 | 133.71 | 73.01 | 0.00 | 0.00 | 0.00 |
| May | 159.16 | 71.87 | 87.29 | 183.27 | 46.09 | 0.00 | 0.00 | 0.00 |
| June | 192.29 | 90.47 | 101.82 | 240.09 | 32.96 | 0.00 | 0.00 | 0.00 |
| July | 171.71 | 75.18 | 96.53 | 227.95 | 22.33 | 0.00 | 0.00 | 0.00 |
| August | 155.14 | 65.79 | 89.34 | 201.00 | 30.53 | 0.00 | 0.00 | 0.00 |
| September | 122.15 | 52.78 | 69.37 | 140.62 | 51.53 | 0.00 | 0.00 | 0.00 |
| October | 79.15 | 27.88 | 51.27 | 69.52 | 79.64 | 0.00 | 0.00 | 0.00 |
| November | 46.52 | 13.21 | 33.32 | 27.89 | 102.87 | 0.00 | 0.00 | 0.00 |
| December | 40.59 | 8.79 | 31.79 | 11.16 | 159.29 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 110.71 | 44.90 | 65.81 | 114.60 | 84.97 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 40.59 | 8.79 | 31.79 | 11.16 | 22.33 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 192.29 | 90.47 | 101.82 | 240.09 | 165.99 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: GWINDOW1 W NWA
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 43.51 | 10.25 | 33.26 | 12.29 | 164.31 | 0.00 | 0.00 | 0.00 |
| February | 70.50 | 18.19 | 52.31 | 31.19 | 153.22 | 0.00 | 0.00 | 0.00 |
| March | 110.83 | 47.64 | 63.19 | 93.89 | 103.14 | 0.00 | 0.00 | 0.00 |
| April | 134.82 | 55.18 | 79.64 | 135.78 | 71.51 | 0.00 | 0.00 | 0.00 |
| May | 159.16 | 71.87 | 87.29 | 185.81 | 44.34 | 0.00 | 0.00 | 0.00 |
| June | 192.29 | 90.47 | 101.82 | 241.06 | 32.45 | 0.00 | 0.00 | 0.00 |
| July | 171.71 | 75.18 | 96.53 | 228.61 | 22.08 | 0.00 | 0.00 | 0.00 |
| August | 155.14 | 65.79 | 89.34 | 202.06 | 29.99 | 0.00 | 0.00 | 0.00 |
| September | 122.15 | 52.78 | 69.37 | 142.66 | 49.70 | 0.00 | 0.00 | 0.00 |
| October | 79.15 | 27.88 | 51.27 | 72.73 | 75.17 | 0.00 | 0.00 | 0.00 |
| November | 46.52 | 13.21 | 33.32 | 29.15 | 100.33 | 0.00 | 0.00 | 0.00 |
| December | 40.59 | 8.79 | 31.79 | 11.54 | 157.91 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 110.71 | 44.90 | 65.81 | 116.02 | 83.33 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 40.59 | 8.79 | 31.79 | 11.54 | 22.08 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 192.29 | 90.47 | 101.82 | 241.06 | 164.31 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: GWINDOW1 N NWA
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 42.04 | 0.00 | 42.04 | 0.14 | 264.26 | 0.00 | 0.00 | 0.00 |
| February | 64.05 | 0.00 | 64.05 | 3.61 | 245.19 | 0.00 | 0.00 | 0.00 |
| March | 77.69 | 0.00 | 77.69 | 29.17 | 168.00 | 0.00 | 0.00 | 0.00 |
| April | 99.04 | 0.48 | 98.56 | 63.19 | 110.55 | 0.00 | 0.00 | 0.00 |
| May | 115.05 | 4.95 | 110.10 | 106.35 | 64.10 | 0.00 | 0.00 | 0.00 |
| June | 138.33 | 11.76 | 126.56 | 154.65 | 46.14 | 0.00 | 0.00 | 0.00 |
| July | 128.83 | 8.76 | 120.07 | 164.51 | 31.41 | 0.00 | 0.00 | 0.00 |
| August | 111.54 | 2.15 | 109.38 | 132.93 | 44.18 | 0.00 | 0.00 | 0.00 |
| September | 84.53 | 0.04 | 84.50 | 77.26 | 76.84 | 0.00 | 0.00 | 0.00 |
| October | 63.16 | 0.00 | 63.16 | 34.02 | 117.57 | 0.00 | 0.00 | 0.00 |
| November | 42.44 | 0.00 | 42.44 | 9.97 | 156.79 | 0.00 | 0.00 | 0.00 |
| December | 39.35 | 0.00 | 39.35 | 0.57 | 251.74 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 83.92 | 2.36 | 81.56 | 65.07 | 130.83 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 39.35 | 0.00 | 39.35 | 0.14 | 31.41 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 138.33 | 11.76 | 126.56 | 164.51 | 264.26 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: GWINDOW1 S SEA
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 180.27 | 105.03 | 75.24 | 155.02 | 192.11 | 0.00 | 0.00 | 0.00 |
| February | 206.02 | 99.18 | 106.84 | 176.14 | 188.27 | 0.00 | 0.00 | 0.00 |
| March | 247.91 | 137.55 | 110.37 | 258.20 | 136.30 | 0.00 | 0.00 | 0.00 |
| April | 210.81 | 85.55 | 125.27 | 230.58 | 106.05 | 0.00 | 0.00 | 0.00 |
| May | 182.43 | 52.89 | 129.55 | 211.28 | 76.60 | 0.00 | 0.00 | 0.00 |
| June | 177.91 | 38.10 | 139.80 | 218.98 | 59.65 | 0.00 | 0.00 | 0.00 |
| July | 180.52 | 43.36 | 137.16 | 239.93 | 47.14 | 0.00 | 0.00 | 0.00 |
| August | 201.50 | 64.10 | 137.39 | 264.40 | 61.33 | 0.00 | 0.00 | 0.00 |
| September | 239.25 | 118.00 | 121.25 | 293.79 | 90.12 | 0.00 | 0.00 | 0.00 |
| October | 226.76 | 129.79 | 96.98 | 247.48 | 120.91 | 0.00 | 0.00 | 0.00 |
| November | 162.43 | 91.95 | 70.48 | 160.31 | 140.02 | 0.00 | 0.00 | 0.00 |
| December | 151.12 | 78.23 | 72.90 | 123.33 | 191.29 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 197.17 | 86.92 | 110.25 | 215.15 | 117.10 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 151.12 | 38.10 | 70.48 | 123.33 | 47.14 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 247.91 | 137.55 | 139.80 | 293.79 | 192.11 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: GWINDOW1 E SEA
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 50.74 | 16.47 | 34.26 | 22.09 | 135.50 | 0.00 | 0.00 | 0.00 |
| February | 74.09 | 22.13 | 51.96 | 39.48 | 127.76 | 0.00 | 0.00 | 0.00 |
| March | 106.72 | 44.62 | 62.10 | 90.70 | 90.31 | 0.00 | 0.00 | 0.00 |
| April | 140.96 | 62.31 | 78.65 | 143.16 | 65.45 | 0.00 | 0.00 | 0.00 |
| May | 157.90 | 69.80 | 88.10 | 178.59 | 46.98 | 0.00 | 0.00 | 0.00 |
| June | 176.51 | 78.02 | 98.49 | 213.78 | 36.15 | 0.00 | 0.00 | 0.00 |
| July | 169.28 | 74.41 | 94.87 | 215.83 | 28.60 | 0.00 | 0.00 | 0.00 |
| August | 152.83 | 63.97 | 88.86 | 189.66 | 37.96 | 0.00 | 0.00 | 0.00 |
| September | 126.87 | 56.06 | 70.81 | 142.80 | 57.15 | 0.00 | 0.00 | 0.00 |
| October | 86.20 | 35.52 | 50.68 | 77.23 | 79.94 | 0.00 | 0.00 | 0.00 |
| November | 48.95 | 15.66 | 33.29 | 31.90 | 94.76 | 0.00 | 0.00 | 0.00 |
| December | 39.45 | 8.17 | 31.28 | 11.87 | 135.03 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 111.04 | 45.71 | 65.33 | 113.48 | 77.72 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 39.45 | 8.17 | 31.28 | 11.87 | 28.60 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 176.51 | 78.02 | 98.49 | 215.83 | 135.50 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: GWINDOW1 E NEA
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 50.74 | 16.47 | 34.26 | 19.70 | 158.15 | 0.00 | 0.00 | 0.00 |
| February | 74.09 | 22.13 | 51.96 | 35.33 | 148.29 | 0.00 | 0.00 | 0.00 |
| March | 106.72 | 44.62 | 62.10 | 87.66 | 100.43 | 0.00 | 0.00 | 0.00 |
| April | 140.96 | 62.31 | 78.65 | 142.06 | 68.60 | 0.00 | 0.00 | 0.00 |
| May | 157.90 | 69.80 | 88.10 | 183.30 | 42.15 | 0.00 | 0.00 | 0.00 |
| June | 176.51 | 78.02 | 98.49 | 219.07 | 30.41 | 0.00 | 0.00 | 0.00 |
| July | 169.28 | 74.41 | 94.87 | 224.36 | 20.54 | 0.00 | 0.00 | 0.00 |
| August | 152.83 | 63.97 | 88.86 | 197.08 | 28.49 | 0.00 | 0.00 | 0.00 |
| September | 126.87 | 56.06 | 70.81 | 148.02 | 47.98 | 0.00 | 0.00 | 0.00 |
| October | 86.20 | 35.52 | 50.68 | 80.81 | 72.62 | 0.00 | 0.00 | 0.00 |
| November | 48.95 | 15.66 | 33.29 | 31.65 | 98.20 | 0.00 | 0.00 | 0.00 |
| December | 39.45 | 8.17 | 31.28 | 10.06 | 155.48 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 111.04 | 45.71 | 65.33 | 115.36 | 80.61 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 39.45 | 8.17 | 31.28 | 10.06 | 20.54 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 176.51 | 78.02 | 98.49 | 224.36 | 158.15 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: GWINDOW1 N NEA
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 42.04 | 0.00 | 42.04 | 0.13 | 264.47 | 0.00 | 0.00 | 0.00 |
| February | 64.05 | 0.00 | 64.05 | 3.55 | 245.30 | 0.00 | 0.00 | 0.00 |
| March | 77.69 | 0.00 | 77.69 | 28.96 | 167.84 | 0.00 | 0.00 | 0.00 |
| April | 99.04 | 0.48 | 98.56 | 62.74 | 110.39 | 0.00 | 0.00 | 0.00 |
| May | 115.05 | 4.95 | 110.10 | 105.78 | 63.72 | 0.00 | 0.00 | 0.00 |
| June | 138.33 | 11.76 | 126.56 | 154.35 | 45.55 | 0.00 | 0.00 | 0.00 |
| July | 128.83 | 8.76 | 120.07 | 164.13 | 31.14 | 0.00 | 0.00 | 0.00 |
| August | 111.54 | 2.15 | 109.38 | 132.66 | 43.89 | 0.00 | 0.00 | 0.00 |
| September | 84.53 | 0.04 | 84.50 | 76.61 | 76.71 | 0.00 | 0.00 | 0.00 |
| October | 63.16 | 0.00 | 63.16 | 33.57 | 117.64 | 0.00 | 0.00 | 0.00 |
| November | 42.44 | 0.00 | 42.44 | 9.87 | 156.83 | 0.00 | 0.00 | 0.00 |
| December | 39.35 | 0.00 | 39.35 | 0.57 | 251.76 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 83.92 | 2.36 | 81.56 | 64.78 | 130.70 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 39.35 | 0.00 | 39.35 | 0.13 | 31.14 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 138.33 | 11.76 | 126.56 | 164.13 | 264.47 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: GWINDOW1 N N1A
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 42.04 | 0.00 | 42.04 | 0.09 | 269.12 | 0.00 | 0.00 | 0.00 |
| February | 64.05 | 0.00 | 64.05 | 3.27 | 249.67 | 0.00 | 0.00 | 0.00 |
| March | 77.69 | 0.00 | 77.69 | 28.39 | 171.11 | 0.00 | 0.00 | 0.00 |
| April | 99.04 | 0.48 | 98.56 | 62.38 | 112.49 | 0.00 | 0.00 | 0.00 |
| May | 115.05 | 4.95 | 110.10 | 105.20 | 65.89 | 0.00 | 0.00 | 0.00 |
| June | 138.33 | 11.76 | 126.56 | 154.66 | 46.61 | 0.00 | 0.00 | 0.00 |
| July | 128.83 | 8.76 | 120.07 | 165.40 | 31.19 | 0.00 | 0.00 | 0.00 |
| August | 111.54 | 2.15 | 109.38 | 133.79 | 44.01 | 0.00 | 0.00 | 0.00 |
| September | 84.53 | 0.04 | 84.50 | 77.04 | 78.03 | 0.00 | 0.00 | 0.00 |
| October | 63.16 | 0.00 | 63.16 | 33.12 | 120.38 | 0.00 | 0.00 | 0.00 |
| November | 42.44 | 0.00 | 42.44 | 9.62 | 159.74 | 0.00 | 0.00 | 0.00 |
| December | 39.35 | 0.00 | 39.35 | 0.52 | 256.07 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 83.92 | 2.36 | 81.56 | 64.83 | 133.12 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 39.35 | 0.00 | 39.35 | 0.09 | 31.19 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 138.33 | 11.76 | 126.56 | 165.40 | 269.12 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: GWINDOW1 N N2A
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 42.04 | 0.00 | 42.04 | 0.09 | 269.13 | 0.00 | 0.00 | 0.00 |
| February | 64.05 | 0.00 | 64.05 | 3.27 | 249.67 | 0.00 | 0.00 | 0.00 |
| March | 77.69 | 0.00 | 77.69 | 28.38 | 171.11 | 0.00 | 0.00 | 0.00 |
| April | 99.04 | 0.48 | 98.56 | 62.35 | 112.49 | 0.00 | 0.00 | 0.00 |
| May | 115.05 | 4.95 | 110.10 | 105.17 | 65.88 | 0.00 | 0.00 | 0.00 |
| June | 138.33 | 11.76 | 126.56 | 154.66 | 46.58 | 0.00 | 0.00 | 0.00 |
| July | 128.83 | 8.76 | 120.07 | 165.39 | 31.18 | 0.00 | 0.00 | 0.00 |
| August | 111.54 | 2.15 | 109.38 | 133.78 | 44.00 | 0.00 | 0.00 | 0.00 |
| September | 84.53 | 0.04 | 84.50 | 77.01 | 78.04 | 0.00 | 0.00 | 0.00 |
| October | 63.16 | 0.00 | 63.16 | 33.09 | 120.41 | 0.00 | 0.00 | 0.00 |
| November | 42.44 | 0.00 | 42.44 | 9.61 | 159.74 | 0.00 | 0.00 | 0.00 |
| December | 39.35 | 0.00 | 39.35 | 0.52 | 256.07 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 83.92 | 2.36 | 81.56 | 64.82 | 133.12 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 39.35 | 0.00 | 39.35 | 0.09 | 31.18 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 138.33 | 11.76 | 126.56 | 165.39 | 269.13 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: GWINDOW1 S S1A
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 180.27 | 105.03 | 75.24 | 146.32 | 230.07 | 0.00 | 0.00 | 0.00 |
| February | 206.02 | 99.18 | 106.84 | 165.36 | 223.66 | 0.00 | 0.00 | 0.00 |
| March | 247.91 | 137.55 | 110.37 | 249.55 | 157.81 | 0.00 | 0.00 | 0.00 |
| April | 210.81 | 85.55 | 125.27 | 226.05 | 116.96 | 0.00 | 0.00 | 0.00 |
| May | 182.43 | 52.89 | 129.55 | 213.55 | 74.98 | 0.00 | 0.00 | 0.00 |
| June | 177.91 | 38.10 | 139.80 | 225.27 | 52.24 | 0.00 | 0.00 | 0.00 |
| July | 180.52 | 43.36 | 137.16 | 252.35 | 34.24 | 0.00 | 0.00 | 0.00 |
| August | 201.50 | 64.10 | 137.39 | 274.27 | 46.90 | 0.00 | 0.00 | 0.00 |
| September | 239.25 | 118.00 | 121.25 | 298.82 | 79.73 | 0.00 | 0.00 | 0.00 |
| October | 226.76 | 129.79 | 96.98 | 246.92 | 121.16 | 0.00 | 0.00 | 0.00 |
| November | 162.43 | 91.95 | 70.48 | 156.41 | 152.35 | 0.00 | 0.00 | 0.00 |
| December | 151.12 | 78.23 | 72.90 | 116.00 | 225.48 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 197.17 | 86.92 | 110.25 | 214.50 | 125.78 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 151.12 | 38.10 | 70.48 | 116.00 | 34.24 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 247.91 | 137.55 | 139.80 | 298.82 | 230.07 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: GWINDOW1 S S2A
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 180.27 | 105.03 | 75.24 | 146.67 | 228.74 | 0.00 | 0.00 | 0.00 |
| February | 206.02 | 99.18 | 106.84 | 165.78 | 222.51 | 0.00 | 0.00 | 0.00 |
| March | 247.91 | 137.55 | 110.37 | 249.92 | 157.02 | 0.00 | 0.00 | 0.00 |
| April | 210.81 | 85.55 | 125.27 | 226.24 | 116.53 | 0.00 | 0.00 | 0.00 |
| May | 182.43 | 52.89 | 129.55 | 212.99 | 75.49 | 0.00 | 0.00 | 0.00 |
| June | 177.91 | 38.10 | 139.80 | 224.74 | 52.69 | 0.00 | 0.00 | 0.00 |
| July | 180.52 | 43.36 | 137.16 | 251.75 | 34.70 | 0.00 | 0.00 | 0.00 |
| August | 201.50 | 64.10 | 137.39 | 273.76 | 47.42 | 0.00 | 0.00 | 0.00 |
| September | 239.25 | 118.00 | 121.25 | 298.48 | 80.20 | 0.00 | 0.00 | 0.00 |
| October | 226.76 | 129.79 | 96.98 | 246.61 | 121.65 | 0.00 | 0.00 | 0.00 |
| November | 162.43 | 91.95 | 70.48 | 156.55 | 151.88 | 0.00 | 0.00 | 0.00 |
| December | 151.12 | 78.23 | 72.90 | 116.29 | 224.28 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 197.17 | 86.92 | 110.25 | 214.41 | 125.58 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 151.12 | 38.10 | 70.48 | 116.29 | 34.70 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 247.91 | 137.55 | 139.80 | 298.48 | 228.74 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MWINDOW1 S SWA
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 180.27 | 105.03 | 75.24 | 144.32 | 234.37 | 0.00 | 0.00 | 0.00 |
| February | 206.02 | 99.18 | 106.84 | 162.18 | 228.81 | 0.00 | 0.00 | 0.00 |
| March | 247.91 | 137.55 | 110.37 | 243.97 | 164.81 | 0.00 | 0.00 | 0.00 |
| April | 210.81 | 85.55 | 125.27 | 217.66 | 127.83 | 0.00 | 0.00 | 0.00 |
| May | 182.43 | 52.89 | 129.55 | 201.27 | 89.47 | 0.00 | 0.00 | 0.00 |
| June | 177.91 | 38.10 | 139.80 | 220.15 | 55.60 | 0.00 | 0.00 | 0.00 |
| July | 180.52 | 43.36 | 137.16 | 248.97 | 35.64 | 0.00 | 0.00 | 0.00 |
| August | 201.50 | 64.10 | 137.39 | 271.78 | 47.81 | 0.00 | 0.00 | 0.00 |
| September | 239.25 | 118.00 | 121.25 | 297.19 | 79.81 | 0.00 | 0.00 | 0.00 |
| October | 226.76 | 129.79 | 96.98 | 245.95 | 120.35 | 0.00 | 0.00 | 0.00 |
| November | 162.43 | 91.95 | 70.48 | 155.09 | 153.45 | 0.00 | 0.00 | 0.00 |
| December | 151.12 | 78.23 | 72.90 | 114.47 | 228.77 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 197.17 | 86.92 | 110.25 | 210.51 | 130.04 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 151.12 | 38.10 | 70.48 | 114.47 | 35.64 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 247.91 | 137.55 | 139.80 | 297.19 | 234.37 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MWINDOW1 W SWA
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 43.51 | 10.25 | 33.26 | 11.20 | 173.09 | 0.00 | 0.00 | 0.00 |
| February | 70.50 | 18.19 | 52.31 | 28.67 | 161.61 | 0.00 | 0.00 | 0.00 |
| March | 110.83 | 47.64 | 63.19 | 88.04 | 112.21 | 0.00 | 0.00 | 0.00 |
| April | 134.82 | 55.18 | 79.64 | 126.84 | 81.30 | 0.00 | 0.00 | 0.00 |
| May | 159.16 | 71.87 | 87.29 | 173.25 | 56.75 | 0.00 | 0.00 | 0.00 |
| June | 192.29 | 90.47 | 101.82 | 236.27 | 35.50 | 0.00 | 0.00 | 0.00 |
| July | 171.71 | 75.18 | 96.53 | 226.10 | 23.12 | 0.00 | 0.00 | 0.00 |
| August | 155.14 | 65.79 | 89.34 | 199.83 | 31.04 | 0.00 | 0.00 | 0.00 |
| September | 122.15 | 52.78 | 69.37 | 139.49 | 52.29 | 0.00 | 0.00 | 0.00 |
| October | 79.15 | 27.88 | 51.27 | 67.83 | 82.24 | 0.00 | 0.00 | 0.00 |
| November | 46.52 | 13.21 | 33.32 | 26.77 | 106.44 | 0.00 | 0.00 | 0.00 |
| December | 40.59 | 8.79 | 31.79 | 10.51 | 164.98 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 110.71 | 44.90 | 65.81 | 111.68 | 89.69 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 40.59 | 8.79 | 31.79 | 10.51 | 23.12 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 192.29 | 90.47 | 101.82 | 236.27 | 173.09 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MWINDOW1 W NWA
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 43.51 | 10.25 | 33.26 | 11.68 | 171.29 | 0.00 | 0.00 | 0.00 |
| February | 70.50 | 18.19 | 52.31 | 29.47 | 160.12 | 0.00 | 0.00 | 0.00 |
| March | 110.83 | 47.64 | 63.19 | 89.92 | 110.17 | 0.00 | 0.00 | 0.00 |
| April | 134.82 | 55.18 | 79.64 | 129.96 | 78.39 | 0.00 | 0.00 | 0.00 |
| May | 159.16 | 71.87 | 87.29 | 174.77 | 55.67 | 0.00 | 0.00 | 0.00 |
| June | 192.29 | 90.47 | 101.82 | 236.78 | 35.40 | 0.00 | 0.00 | 0.00 |
| July | 171.71 | 75.18 | 96.53 | 226.67 | 22.98 | 0.00 | 0.00 | 0.00 |
| August | 155.14 | 65.79 | 89.34 | 200.73 | 30.70 | 0.00 | 0.00 | 0.00 |
| September | 122.15 | 52.78 | 69.37 | 141.21 | 51.10 | 0.00 | 0.00 | 0.00 |
| October | 79.15 | 27.88 | 51.27 | 71.13 | 77.95 | 0.00 | 0.00 | 0.00 |
| November | 46.52 | 13.21 | 33.32 | 28.26 | 103.69 | 0.00 | 0.00 | 0.00 |
| December | 40.59 | 8.79 | 31.79 | 10.95 | 163.65 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 110.71 | 44.90 | 65.81 | 113.08 | 88.07 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 40.59 | 8.79 | 31.79 | 10.95 | 22.98 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 192.29 | 90.47 | 101.82 | 236.78 | 171.29 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MWINDOW1 N NWA
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 42.04 | 0.00 | 42.04 | 0.04 | 275.09 | 0.00 | 0.00 | 0.00 |
| February | 64.05 | 0.00 | 64.05 | 2.68 | 256.27 | 0.00 | 0.00 | 0.00 |
| March | 77.69 | 0.00 | 77.69 | 25.29 | 179.90 | 0.00 | 0.00 | 0.00 |
| April | 99.04 | 0.48 | 98.56 | 56.06 | 121.84 | 0.00 | 0.00 | 0.00 |
| May | 115.05 | 4.95 | 110.10 | 89.88 | 80.48 | 0.00 | 0.00 | 0.00 |
| June | 138.33 | 11.76 | 126.56 | 148.53 | 50.14 | 0.00 | 0.00 | 0.00 |
| July | 128.83 | 8.76 | 120.07 | 162.09 | 32.63 | 0.00 | 0.00 | 0.00 |
| August | 111.54 | 2.15 | 109.38 | 131.43 | 45.22 | 0.00 | 0.00 | 0.00 |
| September | 84.53 | 0.04 | 84.50 | 75.62 | 79.00 | 0.00 | 0.00 | 0.00 |
| October | 63.16 | 0.00 | 63.16 | 32.26 | 121.86 | 0.00 | 0.00 | 0.00 |
| November | 42.44 | 0.00 | 42.44 | 9.16 | 161.85 | 0.00 | 0.00 | 0.00 |
| December | 39.35 | 0.00 | 39.35 | 0.46 | 260.40 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 83.92 | 2.36 | 81.56 | 61.48 | 138.14 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 39.35 | 0.00 | 39.35 | 0.04 | 32.63 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 138.33 | 11.76 | 126.56 | 162.09 | 275.09 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MWINDOW1 S SEA
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 180.27 | 105.03 | 75.24 | 144.12 | 234.41 | 0.00 | 0.00 | 0.00 |
| February | 206.02 | 99.18 | 106.84 | 161.93 | 228.76 | 0.00 | 0.00 | 0.00 |
| March | 247.91 | 137.55 | 110.37 | 243.58 | 164.34 | 0.00 | 0.00 | 0.00 |
| April | 210.81 | 85.55 | 125.27 | 216.65 | 127.47 | 0.00 | 0.00 | 0.00 |
| May | 182.43 | 52.89 | 129.55 | 200.53 | 89.01 | 0.00 | 0.00 | 0.00 |
| June | 177.91 | 38.10 | 139.80 | 219.78 | 55.14 | 0.00 | 0.00 | 0.00 |
| July | 180.52 | 43.36 | 137.16 | 248.62 | 35.35 | 0.00 | 0.00 | 0.00 |
| August | 201.50 | 64.10 | 137.39 | 271.49 | 47.52 | 0.00 | 0.00 | 0.00 |
| September | 239.25 | 118.00 | 121.25 | 296.75 | 79.51 | 0.00 | 0.00 | 0.00 |
| October | 226.76 | 129.79 | 96.98 | 245.15 | 120.43 | 0.00 | 0.00 | 0.00 |
| November | 162.43 | 91.95 | 70.48 | 154.86 | 153.41 | 0.00 | 0.00 | 0.00 |
| December | 151.12 | 78.23 | 72.90 | 114.38 | 228.72 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 197.17 | 86.92 | 110.25 | 210.08 | 129.82 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 151.12 | 38.10 | 70.48 | 114.38 | 35.35 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 247.91 | 137.55 | 139.80 | 296.75 | 234.41 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MWINDOW1 E SEA
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 50.74 | 16.47 | 34.26 | 18.48 | 166.43 | 0.00 | 0.00 | 0.00 |
| February | 74.09 | 22.13 | 51.96 | 33.04 | 156.40 | 0.00 | 0.00 | 0.00 |
| March | 106.72 | 44.62 | 62.10 | 82.42 | 109.67 | 0.00 | 0.00 | 0.00 |
| April | 140.96 | 62.31 | 78.65 | 133.11 | 78.37 | 0.00 | 0.00 | 0.00 |
| May | 157.90 | 69.80 | 88.10 | 170.69 | 54.18 | 0.00 | 0.00 | 0.00 |
| June | 176.51 | 78.02 | 98.49 | 214.39 | 33.37 | 0.00 | 0.00 | 0.00 |
| July | 169.28 | 74.41 | 94.87 | 222.01 | 21.51 | 0.00 | 0.00 | 0.00 |
| August | 152.83 | 63.97 | 88.86 | 194.86 | 29.53 | 0.00 | 0.00 | 0.00 |
| September | 126.87 | 56.06 | 70.81 | 145.00 | 50.40 | 0.00 | 0.00 | 0.00 |
| October | 86.20 | 35.52 | 50.68 | 75.97 | 79.64 | 0.00 | 0.00 | 0.00 |
| November | 48.95 | 15.66 | 33.29 | 29.46 | 104.36 | 0.00 | 0.00 | 0.00 |
| December | 39.45 | 8.17 | 31.28 | 9.34 | 162.56 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 111.04 | 45.71 | 65.33 | 111.15 | 86.86 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 39.45 | 8.17 | 31.28 | 9.34 | 21.51 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 176.51 | 78.02 | 98.49 | 222.01 | 166.43 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MWINDOW1 E NEA
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 50.74 | 16.47 | 34.26 | 18.84 | 164.51 | 0.00 | 0.00 | 0.00 |
| February | 74.09 | 22.13 | 51.96 | 33.63 | 154.74 | 0.00 | 0.00 | 0.00 |
| March | 106.72 | 44.62 | 62.10 | 83.87 | 107.35 | 0.00 | 0.00 | 0.00 |
| April | 140.96 | 62.31 | 78.65 | 136.05 | 75.41 | 0.00 | 0.00 | 0.00 |
| May | 157.90 | 69.80 | 88.10 | 172.08 | 53.13 | 0.00 | 0.00 | 0.00 |
| June | 176.51 | 78.02 | 98.49 | 214.88 | 33.25 | 0.00 | 0.00 | 0.00 |
| July | 169.28 | 74.41 | 94.87 | 222.56 | 21.36 | 0.00 | 0.00 | 0.00 |
| August | 152.83 | 63.97 | 88.86 | 195.76 | 29.18 | 0.00 | 0.00 | 0.00 |
| September | 126.87 | 56.06 | 70.81 | 146.62 | 49.23 | 0.00 | 0.00 | 0.00 |
| October | 86.20 | 35.52 | 50.68 | 79.17 | 75.20 | 0.00 | 0.00 | 0.00 |
| November | 48.95 | 15.66 | 33.29 | 30.72 | 101.40 | 0.00 | 0.00 | 0.00 |
| December | 39.45 | 8.17 | 31.28 | 9.55 | 161.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 111.04 | 45.71 | 65.33 | 112.40 | 85.14 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 39.45 | 8.17 | 31.28 | 9.55 | 21.36 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 176.51 | 78.02 | 98.49 | 222.56 | 164.51 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MWINDOW1 N NEA
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 42.04 | 0.00 | 42.04 | 0.04 | 275.30 | 0.00 | 0.00 | 0.00 |
| February | 64.05 | 0.00 | 64.05 | 2.62 | 256.39 | 0.00 | 0.00 | 0.00 |
| March | 77.69 | 0.00 | 77.69 | 25.01 | 179.70 | 0.00 | 0.00 | 0.00 |
| April | 99.04 | 0.48 | 98.56 | 55.08 | 121.68 | 0.00 | 0.00 | 0.00 |
| May | 115.05 | 4.95 | 110.10 | 88.97 | 80.12 | 0.00 | 0.00 | 0.00 |
| June | 138.33 | 11.76 | 126.56 | 148.14 | 49.71 | 0.00 | 0.00 | 0.00 |
| July | 128.83 | 8.76 | 120.07 | 161.70 | 32.34 | 0.00 | 0.00 | 0.00 |
| August | 111.54 | 2.15 | 109.38 | 131.13 | 44.94 | 0.00 | 0.00 | 0.00 |
| September | 84.53 | 0.04 | 84.50 | 75.02 | 78.75 | 0.00 | 0.00 | 0.00 |
| October | 63.16 | 0.00 | 63.16 | 31.70 | 121.87 | 0.00 | 0.00 | 0.00 |
| November | 42.44 | 0.00 | 42.44 | 9.03 | 161.88 | 0.00 | 0.00 | 0.00 |
| December | 39.35 | 0.00 | 39.35 | 0.45 | 260.43 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 83.92 | 2.36 | 81.56 | 61.10 | 138.01 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 39.35 | 0.00 | 39.35 | 0.04 | 32.34 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 138.33 | 11.76 | 126.56 | 161.70 | 275.30 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MWINDOW1 N N1A
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 42.04 | 0.00 | 42.04 | 0.02 | 279.46 | 0.00 | 0.00 | 0.00 |
| February | 64.05 | 0.00 | 64.05 | 2.46 | 260.14 | 0.00 | 0.00 | 0.00 |
| March | 77.69 | 0.00 | 77.69 | 24.84 | 182.24 | 0.00 | 0.00 | 0.00 |
| April | 99.04 | 0.48 | 98.56 | 55.64 | 123.35 | 0.00 | 0.00 | 0.00 |
| May | 115.05 | 4.95 | 110.10 | 89.72 | 81.71 | 0.00 | 0.00 | 0.00 |
| June | 138.33 | 11.76 | 126.56 | 149.80 | 49.80 | 0.00 | 0.00 | 0.00 |
| July | 128.83 | 8.76 | 120.07 | 163.67 | 32.06 | 0.00 | 0.00 | 0.00 |
| August | 111.54 | 2.15 | 109.38 | 132.69 | 44.81 | 0.00 | 0.00 | 0.00 |
| September | 84.53 | 0.04 | 84.50 | 75.67 | 79.94 | 0.00 | 0.00 | 0.00 |
| October | 63.16 | 0.00 | 63.16 | 31.20 | 125.50 | 0.00 | 0.00 | 0.00 |
| November | 42.44 | 0.00 | 42.44 | 8.79 | 165.05 | 0.00 | 0.00 | 0.00 |
| December | 39.35 | 0.00 | 39.35 | 0.42 | 264.71 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 83.92 | 2.36 | 81.56 | 61.60 | 140.14 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 39.35 | 0.00 | 39.35 | 0.02 | 32.06 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 138.33 | 11.76 | 126.56 | 163.67 | 279.46 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MWINDOW1 N N2A
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 42.04 | 0.00 | 42.04 | 0.02 | 279.47 | 0.00 | 0.00 | 0.00 |
| February | 64.05 | 0.00 | 64.05 | 2.46 | 260.14 | 0.00 | 0.00 | 0.00 |
| March | 77.69 | 0.00 | 77.69 | 24.83 | 182.23 | 0.00 | 0.00 | 0.00 |
| April | 99.04 | 0.48 | 98.56 | 55.56 | 123.40 | 0.00 | 0.00 | 0.00 |
| May | 115.05 | 4.95 | 110.10 | 89.66 | 81.71 | 0.00 | 0.00 | 0.00 |
| June | 138.33 | 11.76 | 126.56 | 149.79 | 49.79 | 0.00 | 0.00 | 0.00 |
| July | 128.83 | 8.76 | 120.07 | 163.66 | 32.05 | 0.00 | 0.00 | 0.00 |
| August | 111.54 | 2.15 | 109.38 | 132.68 | 44.80 | 0.00 | 0.00 | 0.00 |
| September | 84.53 | 0.04 | 84.50 | 75.65 | 79.93 | 0.00 | 0.00 | 0.00 |
| October | 63.16 | 0.00 | 63.16 | 31.16 | 125.54 | 0.00 | 0.00 | 0.00 |
| November | 42.44 | 0.00 | 42.44 | 8.79 | 165.06 | 0.00 | 0.00 | 0.00 |
| December | 39.35 | 0.00 | 39.35 | 0.42 | 264.71 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 83.92 | 2.36 | 81.56 | 61.58 | 140.15 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 39.35 | 0.00 | 39.35 | 0.02 | 32.05 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 138.33 | 11.76 | 126.56 | 163.66 | 279.47 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MWINDOW1 S S1A
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 180.27 | 105.03 | 75.24 | 143.22 | 238.38 | 0.00 | 0.00 | 0.00 |
| February | 206.02 | 99.18 | 106.84 | 160.92 | 232.38 | 0.00 | 0.00 | 0.00 |
| March | 247.91 | 137.55 | 110.37 | 242.80 | 167.38 | 0.00 | 0.00 | 0.00 |
| April | 210.81 | 85.55 | 125.27 | 216.46 | 130.55 | 0.00 | 0.00 | 0.00 |
| May | 182.43 | 52.89 | 129.55 | 201.00 | 90.82 | 0.00 | 0.00 | 0.00 |
| June | 177.91 | 38.10 | 139.80 | 221.35 | 55.19 | 0.00 | 0.00 | 0.00 |
| July | 180.52 | 43.36 | 137.16 | 250.49 | 35.03 | 0.00 | 0.00 | 0.00 |
| August | 201.50 | 64.10 | 137.39 | 272.93 | 47.38 | 0.00 | 0.00 | 0.00 |
| September | 239.25 | 118.00 | 121.25 | 297.28 | 80.57 | 0.00 | 0.00 | 0.00 |
| October | 226.76 | 129.79 | 96.98 | 243.73 | 125.26 | 0.00 | 0.00 | 0.00 |
| November | 162.43 | 91.95 | 70.48 | 153.64 | 157.99 | 0.00 | 0.00 | 0.00 |
| December | 151.12 | 78.23 | 72.90 | 113.55 | 232.81 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 197.17 | 86.92 | 110.25 | 210.05 | 132.29 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 151.12 | 38.10 | 70.48 | 113.55 | 35.03 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 247.91 | 137.55 | 139.80 | 297.28 | 238.38 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MWINDOW1 S S2A
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 180.27 | 105.03 | 75.24 | 143.21 | 238.38 | 0.00 | 0.00 | 0.00 |
| February | 206.02 | 99.18 | 106.84 | 160.91 | 232.38 | 0.00 | 0.00 | 0.00 |
| March | 247.91 | 137.55 | 110.37 | 242.78 | 167.36 | 0.00 | 0.00 | 0.00 |
| April | 210.81 | 85.55 | 125.27 | 216.39 | 130.56 | 0.00 | 0.00 | 0.00 |
| May | 182.43 | 52.89 | 129.55 | 200.97 | 90.80 | 0.00 | 0.00 | 0.00 |
| June | 177.91 | 38.10 | 139.80 | 221.34 | 55.17 | 0.00 | 0.00 | 0.00 |
| July | 180.52 | 43.36 | 137.16 | 250.48 | 35.02 | 0.00 | 0.00 | 0.00 |
| August | 201.50 | 64.10 | 137.39 | 272.92 | 47.37 | 0.00 | 0.00 | 0.00 |
| September | 239.25 | 118.00 | 121.25 | 297.27 | 80.56 | 0.00 | 0.00 | 0.00 |
| October | 226.76 | 129.79 | 96.98 | 243.68 | 125.30 | 0.00 | 0.00 | 0.00 |
| November | 162.43 | 91.95 | 70.48 | 153.63 | 158.01 | 0.00 | 0.00 | 0.00 |
| December | 151.12 | 78.23 | 72.90 | 113.54 | 232.81 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 197.17 | 86.92 | 110.25 | 210.03 | 132.28 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 151.12 | 38.10 | 70.48 | 113.54 | 35.02 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 247.91 | 137.55 | 139.80 | 297.27 | 238.38 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: TWINDOW1 S SWA
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 180.27 | 105.03 | 75.24 | 144.98 | 226.99 | 0.00 | 0.00 | 0.00 |
| February | 206.02 | 99.18 | 106.84 | 162.64 | 222.04 | 0.00 | 0.00 | 0.00 |
| March | 247.91 | 137.55 | 110.37 | 243.75 | 158.34 | 0.00 | 0.00 | 0.00 |
| April | 210.81 | 85.55 | 125.27 | 217.59 | 120.85 | 0.00 | 0.00 | 0.00 |
| May | 182.43 | 52.89 | 129.55 | 203.46 | 79.94 | 0.00 | 0.00 | 0.00 |
| June | 177.91 | 38.10 | 139.80 | 218.56 | 51.87 | 0.00 | 0.00 | 0.00 |
| July | 180.52 | 43.36 | 137.16 | 245.40 | 34.23 | 0.00 | 0.00 | 0.00 |
| August | 201.50 | 64.10 | 137.39 | 269.13 | 45.42 | 0.00 | 0.00 | 0.00 |
| September | 239.25 | 118.00 | 121.25 | 297.76 | 72.24 | 0.00 | 0.00 | 0.00 |
| October | 226.76 | 129.79 | 96.98 | 247.75 | 110.84 | 0.00 | 0.00 | 0.00 |
| November | 162.43 | 91.95 | 70.48 | 155.59 | 145.98 | 0.00 | 0.00 | 0.00 |
| December | 151.12 | 78.23 | 72.90 | 114.90 | 221.55 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 197.17 | 86.92 | 110.25 | 210.38 | 123.68 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 151.12 | 38.10 | 70.48 | 114.90 | 34.23 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 247.91 | 137.55 | 139.80 | 297.76 | 226.99 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: TWINDOW1 W SWA
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 43.51 | 10.25 | 33.26 | 11.14 | 167.66 | 0.00 | 0.00 | 0.00 |
| February | 70.50 | 18.19 | 52.31 | 28.64 | 156.58 | 0.00 | 0.00 | 0.00 |
| March | 110.83 | 47.64 | 63.19 | 87.57 | 107.51 | 0.00 | 0.00 | 0.00 |
| April | 134.82 | 55.18 | 79.64 | 126.47 | 76.31 | 0.00 | 0.00 | 0.00 |
| May | 159.16 | 71.87 | 87.29 | 174.56 | 50.32 | 0.00 | 0.00 | 0.00 |
| June | 192.29 | 90.47 | 101.82 | 234.98 | 32.90 | 0.00 | 0.00 | 0.00 |
| July | 171.71 | 75.18 | 96.53 | 223.59 | 22.10 | 0.00 | 0.00 | 0.00 |
| August | 155.14 | 65.79 | 89.34 | 198.01 | 29.38 | 0.00 | 0.00 | 0.00 |
| September | 122.15 | 52.78 | 69.37 | 139.56 | 46.95 | 0.00 | 0.00 | 0.00 |
| October | 79.15 | 27.88 | 51.27 | 68.59 | 75.40 | 0.00 | 0.00 | 0.00 |
| November | 46.52 | 13.21 | 33.32 | 26.77 | 101.00 | 0.00 | 0.00 | 0.00 |
| December | 40.59 | 8.79 | 31.79 | 10.46 | 159.73 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 110.71 | 44.90 | 65.81 | 111.31 | 85.13 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 40.59 | 8.79 | 31.79 | 10.46 | 22.10 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 192.29 | 90.47 | 101.82 | 234.98 | 167.66 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: TWINDOW1 W NWA
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 43.51 | 10.25 | 33.26 | 11.88 | 166.02 | 0.00 | 0.00 | 0.00 |
| February | 70.50 | 18.19 | 52.31 | 29.80 | 155.33 | 0.00 | 0.00 | 0.00 |
| March | 110.83 | 47.64 | 63.19 | 90.16 | 105.91 | 0.00 | 0.00 | 0.00 |
| April | 134.82 | 55.18 | 79.64 | 129.47 | 75.02 | 0.00 | 0.00 | 0.00 |
| May | 159.16 | 71.87 | 87.29 | 176.46 | 49.67 | 0.00 | 0.00 | 0.00 |
| June | 192.29 | 90.47 | 101.82 | 235.71 | 32.90 | 0.00 | 0.00 | 0.00 |
| July | 171.71 | 75.18 | 96.53 | 224.30 | 22.07 | 0.00 | 0.00 | 0.00 |
| August | 155.14 | 65.79 | 89.34 | 199.29 | 29.08 | 0.00 | 0.00 | 0.00 |
| September | 122.15 | 52.78 | 69.37 | 142.51 | 45.51 | 0.00 | 0.00 | 0.00 |
| October | 79.15 | 27.88 | 51.27 | 72.26 | 72.74 | 0.00 | 0.00 | 0.00 |
| November | 46.52 | 13.21 | 33.32 | 28.63 | 99.24 | 0.00 | 0.00 | 0.00 |
| December | 40.59 | 8.79 | 31.79 | 11.15 | 158.55 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 110.71 | 44.90 | 65.81 | 113.08 | 83.98 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 40.59 | 8.79 | 31.79 | 11.15 | 22.07 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 192.29 | 90.47 | 101.82 | 235.71 | 166.02 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: TWINDOW1 N NWA
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 42.04 | 0.00 | 42.04 | 0.08 | 266.89 | 0.00 | 0.00 | 0.00 |
| February | 64.05 | 0.00 | 64.05 | 2.94 | 248.63 | 0.00 | 0.00 | 0.00 |
| March | 77.69 | 0.00 | 77.69 | 25.77 | 173.48 | 0.00 | 0.00 | 0.00 |
| April | 99.04 | 0.48 | 98.56 | 55.92 | 117.11 | 0.00 | 0.00 | 0.00 |
| May | 115.05 | 4.95 | 110.10 | 93.40 | 72.25 | 0.00 | 0.00 | 0.00 |
| June | 138.33 | 11.76 | 126.56 | 148.13 | 47.19 | 0.00 | 0.00 | 0.00 |
| July | 128.83 | 8.76 | 120.07 | 159.30 | 31.68 | 0.00 | 0.00 | 0.00 |
| August | 111.54 | 2.15 | 109.38 | 129.82 | 43.12 | 0.00 | 0.00 | 0.00 |
| September | 84.53 | 0.04 | 84.50 | 77.80 | 70.66 | 0.00 | 0.00 | 0.00 |
| October | 63.16 | 0.00 | 63.16 | 33.99 | 113.96 | 0.00 | 0.00 | 0.00 |
| November | 42.44 | 0.00 | 42.44 | 9.61 | 155.00 | 0.00 | 0.00 | 0.00 |
| December | 39.35 | 0.00 | 39.35 | 0.52 | 252.37 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 83.92 | 2.36 | 81.56 | 61.80 | 132.13 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 39.35 | 0.00 | 39.35 | 0.08 | 31.68 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 138.33 | 11.76 | 126.56 | 159.30 | 266.89 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: TWINDOW1 S SEA
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 180.27 | 105.03 | 75.24 | 144.67 | 226.96 | 0.00 | 0.00 | 0.00 |
| February | 206.02 | 99.18 | 106.84 | 162.26 | 221.87 | 0.00 | 0.00 | 0.00 |
| March | 247.91 | 137.55 | 110.37 | 243.03 | 157.64 | 0.00 | 0.00 | 0.00 |
| April | 210.81 | 85.55 | 125.27 | 216.03 | 119.94 | 0.00 | 0.00 | 0.00 |
| May | 182.43 | 52.89 | 129.55 | 201.57 | 78.97 | 0.00 | 0.00 | 0.00 |
| June | 177.91 | 38.10 | 139.80 | 217.40 | 50.99 | 0.00 | 0.00 | 0.00 |
| July | 180.52 | 43.36 | 137.16 | 244.60 | 33.76 | 0.00 | 0.00 | 0.00 |
| August | 201.50 | 64.10 | 137.39 | 268.42 | 44.91 | 0.00 | 0.00 | 0.00 |
| September | 239.25 | 118.00 | 121.25 | 296.48 | 71.68 | 0.00 | 0.00 | 0.00 |
| October | 226.76 | 129.79 | 96.98 | 246.64 | 110.53 | 0.00 | 0.00 | 0.00 |
| November | 162.43 | 91.95 | 70.48 | 155.25 | 145.79 | 0.00 | 0.00 | 0.00 |
| December | 151.12 | 78.23 | 72.90 | 114.76 | 221.47 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 197.17 | 86.92 | 110.25 | 209.51 | 123.19 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 151.12 | 38.10 | 70.48 | 114.76 | 33.76 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 247.91 | 137.55 | 139.80 | 296.48 | 226.96 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: TWINDOW1 E SEA
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 50.74 | 16.47 | 34.26 | 18.82 | 161.22 | 0.00 | 0.00 | 0.00 |
| February | 74.09 | 22.13 | 51.96 | 33.49 | 151.62 | 0.00 | 0.00 | 0.00 |
| March | 106.72 | 44.62 | 62.10 | 82.66 | 105.59 | 0.00 | 0.00 | 0.00 |
| April | 140.96 | 62.31 | 78.65 | 133.34 | 73.85 | 0.00 | 0.00 | 0.00 |
| May | 157.90 | 69.80 | 88.10 | 172.32 | 48.43 | 0.00 | 0.00 | 0.00 |
| June | 176.51 | 78.02 | 98.49 | 213.51 | 31.21 | 0.00 | 0.00 | 0.00 |
| July | 169.28 | 74.41 | 94.87 | 219.76 | 20.71 | 0.00 | 0.00 | 0.00 |
| August | 152.83 | 63.97 | 88.86 | 193.21 | 28.09 | 0.00 | 0.00 | 0.00 |
| September | 126.87 | 56.06 | 70.81 | 145.39 | 45.72 | 0.00 | 0.00 | 0.00 |
| October | 86.20 | 35.52 | 50.68 | 77.29 | 73.26 | 0.00 | 0.00 | 0.00 |
| November | 48.95 | 15.66 | 33.29 | 29.88 | 99.28 | 0.00 | 0.00 | 0.00 |
| December | 39.45 | 8.17 | 31.28 | 9.57 | 157.44 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 111.04 | 45.71 | 65.33 | 111.19 | 82.70 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 39.45 | 8.17 | 31.28 | 9.57 | 20.71 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 176.51 | 78.02 | 98.49 | 219.76 | 161.22 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: TWINDOW1 E NEA
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 50.74 | 16.47 | 34.26 | 19.29 | 159.33 | 0.00 | 0.00 | 0.00 |
| February | 74.09 | 22.13 | 51.96 | 34.30 | 150.07 | 0.00 | 0.00 | 0.00 |
| March | 106.72 | 44.62 | 62.10 | 84.49 | 103.33 | 0.00 | 0.00 | 0.00 |
| April | 140.96 | 62.31 | 78.65 | 136.00 | 72.23 | 0.00 | 0.00 | 0.00 |
| May | 157.90 | 69.80 | 88.10 | 173.90 | 47.71 | 0.00 | 0.00 | 0.00 |
| June | 176.51 | 78.02 | 98.49 | 214.16 | 31.20 | 0.00 | 0.00 | 0.00 |
| July | 169.28 | 74.41 | 94.87 | 220.47 | 20.65 | 0.00 | 0.00 | 0.00 |
| August | 152.83 | 63.97 | 88.86 | 194.46 | 27.76 | 0.00 | 0.00 | 0.00 |
| September | 126.87 | 56.06 | 70.81 | 147.97 | 44.25 | 0.00 | 0.00 | 0.00 |
| October | 86.20 | 35.52 | 50.68 | 80.67 | 70.15 | 0.00 | 0.00 | 0.00 |
| November | 48.95 | 15.66 | 33.29 | 31.25 | 97.04 | 0.00 | 0.00 | 0.00 |
| December | 39.45 | 8.17 | 31.28 | 9.86 | 155.89 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 111.04 | 45.71 | 65.33 | 112.66 | 81.30 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 39.45 | 8.17 | 31.28 | 9.86 | 20.65 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 176.51 | 78.02 | 98.49 | 220.47 | 159.33 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: TWINDOW1 N NEA
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 42.04 | 0.00 | 42.04 | 0.07 | 267.13 | 0.00 | 0.00 | 0.00 |
| February | 64.05 | 0.00 | 64.05 | 2.85 | 248.73 | 0.00 | 0.00 | 0.00 |
| March | 77.69 | 0.00 | 77.69 | 25.30 | 173.08 | 0.00 | 0.00 | 0.00 |
| April | 99.04 | 0.48 | 98.56 | 54.42 | 116.31 | 0.00 | 0.00 | 0.00 |
| May | 115.05 | 4.95 | 110.10 | 91.30 | 71.48 | 0.00 | 0.00 | 0.00 |
| June | 138.33 | 11.76 | 126.56 | 146.93 | 46.45 | 0.00 | 0.00 | 0.00 |
| July | 128.83 | 8.76 | 120.07 | 158.52 | 31.19 | 0.00 | 0.00 | 0.00 |
| August | 111.54 | 2.15 | 109.38 | 129.08 | 42.60 | 0.00 | 0.00 | 0.00 |
| September | 84.53 | 0.04 | 84.50 | 76.03 | 70.15 | 0.00 | 0.00 | 0.00 |
| October | 63.16 | 0.00 | 63.16 | 33.20 | 113.52 | 0.00 | 0.00 | 0.00 |
| November | 42.44 | 0.00 | 42.44 | 9.40 | 154.94 | 0.00 | 0.00 | 0.00 |
| December | 39.35 | 0.00 | 39.35 | 0.51 | 252.41 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 83.92 | 2.36 | 81.56 | 60.99 | 131.76 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 39.35 | 0.00 | 39.35 | 0.07 | 31.19 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 138.33 | 11.76 | 126.56 | 158.52 | 267.13 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: TWINDOW1 N N1A
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 42.04 | 0.00 | 42.04 | 0.05 | 271.55 | 0.00 | 0.00 | 0.00 |
| February | 64.05 | 0.00 | 64.05 | 2.72 | 252.77 | 0.00 | 0.00 | 0.00 |
| March | 77.69 | 0.00 | 77.69 | 25.42 | 175.79 | 0.00 | 0.00 | 0.00 |
| April | 99.04 | 0.48 | 98.56 | 56.12 | 118.17 | 0.00 | 0.00 | 0.00 |
| May | 115.05 | 4.95 | 110.10 | 93.72 | 73.77 | 0.00 | 0.00 | 0.00 |
| June | 138.33 | 11.76 | 126.56 | 149.39 | 47.52 | 0.00 | 0.00 | 0.00 |
| July | 128.83 | 8.76 | 120.07 | 161.07 | 31.50 | 0.00 | 0.00 | 0.00 |
| August | 111.54 | 2.15 | 109.38 | 131.14 | 43.41 | 0.00 | 0.00 | 0.00 |
| September | 84.53 | 0.04 | 84.50 | 77.87 | 72.41 | 0.00 | 0.00 | 0.00 |
| October | 63.16 | 0.00 | 63.16 | 33.68 | 116.09 | 0.00 | 0.00 | 0.00 |
| November | 42.44 | 0.00 | 42.44 | 9.34 | 157.99 | 0.00 | 0.00 | 0.00 |
| December | 39.35 | 0.00 | 39.35 | 0.47 | 256.87 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 83.92 | 2.36 | 81.56 | 62.11 | 134.24 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 39.35 | 0.00 | 39.35 | 0.05 | 31.50 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 138.33 | 11.76 | 126.56 | 161.07 | 271.55 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: TWINDOW1 N N2A
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 42.04 | 0.00 | 42.04 | 0.05 | 271.56 | 0.00 | 0.00 | 0.00 |
| February | 64.05 | 0.00 | 64.05 | 2.72 | 252.77 | 0.00 | 0.00 | 0.00 |
| March | 77.69 | 0.00 | 77.69 | 25.39 | 175.77 | 0.00 | 0.00 | 0.00 |
| April | 99.04 | 0.48 | 98.56 | 55.98 | 118.14 | 0.00 | 0.00 | 0.00 |
| May | 115.05 | 4.95 | 110.10 | 93.52 | 73.73 | 0.00 | 0.00 | 0.00 |
| June | 138.33 | 11.76 | 126.56 | 149.30 | 47.47 | 0.00 | 0.00 | 0.00 |
| July | 128.83 | 8.76 | 120.07 | 161.03 | 31.47 | 0.00 | 0.00 | 0.00 |
| August | 111.54 | 2.15 | 109.38 | 131.10 | 43.37 | 0.00 | 0.00 | 0.00 |
| September | 84.53 | 0.04 | 84.50 | 77.72 | 72.40 | 0.00 | 0.00 | 0.00 |
| October | 63.16 | 0.00 | 63.16 | 33.61 | 116.07 | 0.00 | 0.00 | 0.00 |
| November | 42.44 | 0.00 | 42.44 | 9.33 | 157.99 | 0.00 | 0.00 | 0.00 |
| December | 39.35 | 0.00 | 39.35 | 0.47 | 256.87 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 83.92 | 2.36 | 81.56 | 62.04 | 134.22 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 39.35 | 0.00 | 39.35 | 0.05 | 31.47 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 138.33 | 11.76 | 126.56 | 161.03 | 271.56 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: TWINDOW1 S S1A
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 180.27 | 105.03 | 75.24 | 143.87 | 231.01 | 0.00 | 0.00 | 0.00 |
| February | 206.02 | 99.18 | 106.84 | 161.43 | 225.69 | 0.00 | 0.00 | 0.00 |
| March | 247.91 | 137.55 | 110.37 | 242.77 | 160.82 | 0.00 | 0.00 | 0.00 |
| April | 210.81 | 85.55 | 125.27 | 217.14 | 122.70 | 0.00 | 0.00 | 0.00 |
| May | 182.43 | 52.89 | 129.55 | 203.32 | 81.75 | 0.00 | 0.00 | 0.00 |
| June | 177.91 | 38.10 | 139.80 | 219.75 | 52.17 | 0.00 | 0.00 | 0.00 |
| July | 180.52 | 43.36 | 137.16 | 247.16 | 34.10 | 0.00 | 0.00 | 0.00 |
| August | 201.50 | 64.10 | 137.39 | 270.36 | 45.74 | 0.00 | 0.00 | 0.00 |
| September | 239.25 | 118.00 | 121.25 | 297.57 | 74.19 | 0.00 | 0.00 | 0.00 |
| October | 226.76 | 129.79 | 96.98 | 246.56 | 113.95 | 0.00 | 0.00 | 0.00 |
| November | 162.43 | 91.95 | 70.48 | 154.58 | 149.41 | 0.00 | 0.00 | 0.00 |
| December | 151.12 | 78.23 | 72.90 | 113.99 | 225.59 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 197.17 | 86.92 | 110.25 | 210.14 | 125.90 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 151.12 | 38.10 | 70.48 | 113.99 | 34.10 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 247.91 | 137.55 | 139.80 | 297.57 | 231.01 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: TWINDOW1 S S2A
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 180.27 | 105.03 | 75.24 | 143.85 | 231.01 | 0.00 | 0.00 | 0.00 |
| February | 206.02 | 99.18 | 106.84 | 161.41 | 225.68 | 0.00 | 0.00 | 0.00 |
| March | 247.91 | 137.55 | 110.37 | 242.71 | 160.77 | 0.00 | 0.00 | 0.00 |
| April | 210.81 | 85.55 | 125.27 | 217.02 | 122.64 | 0.00 | 0.00 | 0.00 |
| May | 182.43 | 52.89 | 129.55 | 203.18 | 81.68 | 0.00 | 0.00 | 0.00 |
| June | 177.91 | 38.10 | 139.80 | 219.67 | 52.11 | 0.00 | 0.00 | 0.00 |
| July | 180.52 | 43.36 | 137.16 | 247.12 | 34.07 | 0.00 | 0.00 | 0.00 |
| August | 201.50 | 64.10 | 137.39 | 270.32 | 45.70 | 0.00 | 0.00 | 0.00 |
| September | 239.25 | 118.00 | 121.25 | 297.49 | 74.16 | 0.00 | 0.00 | 0.00 |
| October | 226.76 | 129.79 | 96.98 | 246.48 | 113.94 | 0.00 | 0.00 | 0.00 |
| November | 162.43 | 91.95 | 70.48 | 154.55 | 149.40 | 0.00 | 0.00 | 0.00 |
| December | 151.12 | 78.23 | 72.90 | 113.98 | 225.59 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 197.17 | 86.92 | 110.25 | 210.08 | 125.87 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 151.12 | 38.10 | 70.48 | 113.98 | 34.07 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 247.91 | 137.55 | 139.80 | 297.49 | 231.01 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: TWINDOW14
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 12.17 | 3.95 | 8.22 | 4.51 | 39.15 | 0.83 | 0.00 | 0.00 |
| February | 17.78 | 5.31 | 12.47 | 8.03 | 36.87 | 0.00 | 0.00 | 0.00 |
| March | 25.61 | 10.71 | 14.90 | 19.72 | 26.29 | 49.33 | 0.00 | 0.00 |
| April | 33.82 | 14.95 | 18.87 | 31.87 | 19.11 | 81.00 | 0.00 | 0.00 |
| May | 37.89 | 16.75 | 21.14 | 40.83 | 13.25 | 208.50 | 0.00 | 0.00 |
| June | 42.35 | 18.72 | 23.63 | 50.07 | 8.91 | 225.50 | 0.00 | 0.00 |
| July | 40.62 | 17.86 | 22.76 | 51.30 | 6.22 | 296.17 | 0.00 | 0.00 |
| August | 36.67 | 15.35 | 21.32 | 45.21 | 8.20 | 310.00 | 0.00 | 0.00 |
| September | 30.44 | 13.45 | 16.99 | 34.47 | 12.59 | 301.83 | 0.00 | 0.00 |
| October | 20.68 | 8.52 | 12.16 | 18.53 | 18.89 | 195.83 | 0.00 | 0.00 |
| November | 11.75 | 3.76 | 7.99 | 7.10 | 25.00 | 25.83 | 0.00 | 0.00 |
| December | 9.47 | 1.96 | 7.51 | 2.28 | 38.42 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 26.64 | 10.97 | 15.68 | 26.26 | 20.99 | 1694.83 | 0.00 | 0.00 |
| Minimum of Months | 9.47 | 1.96 | 7.51 | 2.28 | 6.22 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 42.35 | 18.72 | 23.63 | 51.30 | 39.15 | 310.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ENTRANCE DOOR
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 36.26 | 11.77 | 24.49 | 15.45 | 101.79 | 0.00 | 0.00 | 0.00 |
| February | 52.95 | 15.82 | 37.13 | 28.09 | 95.60 | 0.00 | 0.00 | 0.00 |
| March | 76.27 | 31.89 | 44.38 | 64.20 | 68.06 | 0.00 | 0.00 | 0.00 |
| April | 100.74 | 44.53 | 56.21 | 101.55 | 49.50 | 0.00 | 0.00 | 0.00 |
| May | 112.84 | 49.88 | 62.96 | 127.99 | 33.68 | 0.00 | 0.00 | 0.00 |
| June | 126.14 | 55.75 | 70.39 | 152.06 | 25.37 | 11.50 | 0.00 | 0.00 |
| July | 120.97 | 53.18 | 67.80 | 154.11 | 18.66 | 20.67 | 0.00 | 0.00 |
| August | 109.22 | 45.71 | 63.50 | 135.54 | 24.83 | 18.67 | 0.00 | 0.00 |
| September | 90.66 | 40.06 | 50.60 | 102.89 | 38.46 | 8.00 | 0.00 | 0.00 |
| October | 61.60 | 25.38 | 36.21 | 56.35 | 54.81 | 0.00 | 0.00 | 0.00 |
| November | 34.98 | 11.19 | 23.79 | 22.67 | 68.97 | 0.00 | 0.00 | 0.00 |
| December | 28.19 | 5.84 | 22.36 | 8.13 | 100.73 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 79.35 | 32.66 | 46.69 | 81.03 | 56.51 | 58.83 | 0.00 | 0.00 |
| Minimum of Months | 28.19 | 5.84 | 22.36 | 8.13 | 18.66 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 126.14 | 55.75 | 70.39 | 154.11 | 101.79 | 20.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MWINDOW14
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 12.17 | 3.95 | 8.22 | 4.18 | 42.31 | 98.67 | 0.00 | 0.00 |
| February | 17.78 | 5.31 | 12.47 | 7.49 | 39.78 | 42.50 | 0.00 | 0.00 |
| March | 25.61 | 10.71 | 14.90 | 19.03 | 28.39 | 225.33 | 0.00 | 0.00 |
| April | 33.82 | 14.95 | 18.87 | 31.05 | 20.54 | 291.00 | 0.00 | 0.00 |
| May | 37.89 | 16.75 | 21.14 | 39.66 | 14.65 | 399.67 | 0.00 | 0.00 |
| June | 42.35 | 18.72 | 23.63 | 49.72 | 9.36 | 319.50 | 0.00 | 0.00 |
| July | 40.62 | 17.86 | 22.76 | 51.49 | 6.35 | 335.33 | 0.00 | 0.00 |
| August | 36.67 | 15.35 | 21.32 | 45.19 | 8.49 | 366.17 | 0.00 | 0.00 |
| September | 30.44 | 13.45 | 16.99 | 33.68 | 13.79 | 411.50 | 0.00 | 0.00 |
| October | 20.68 | 8.52 | 12.16 | 17.62 | 20.98 | 469.17 | 0.00 | 0.00 |
| November | 11.75 | 3.76 | 7.99 | 6.68 | 27.38 | 173.33 | 0.00 | 0.00 |
| December | 9.47 | 1.96 | 7.51 | 2.06 | 41.56 | 46.83 | 0.00 | 0.00 |
| Annual Sum or Average | 26.64 | 10.97 | 15.68 | 25.75 | 22.71 | 3179.00 | 0.00 | 0.00 |
| Minimum of Months | 9.47 | 1.96 | 7.51 | 2.06 | 6.35 | 42.50 | 0.00 | 0.00 |
| Maximum of Months | 42.35 | 18.72 | 23.63 | 51.49 | 42.31 | 469.17 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: GWINDOW1 S SWA
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.482833E+09 | 0.281306E+09 | 0.201526E+09 | 0.395161E+09 | 0.605078E+09 |
| February | 0.498407E+09 | 0.239946E+09 | 0.258461E+09 | 0.403562E+09 | 0.531797E+09 |
| March | 0.664013E+09 | 0.368403E+09 | 0.295610E+09 | 0.672768E+09 | 0.414028E+09 |
| April | 0.546431E+09 | 0.221740E+09 | 0.324691E+09 | 0.589463E+09 | 0.296815E+09 |
| May | 0.488630E+09 | 0.141655E+09 | 0.346974E+09 | 0.576903E+09 | 0.193475E+09 |
| June | 0.461133E+09 | 98760793.79 | 0.362372E+09 | 0.584048E+09 | 0.133695E+09 |
| July | 0.483493E+09 | 0.116133E+09 | 0.367360E+09 | 0.673641E+09 | 92186496.20 |
| August | 0.539686E+09 | 0.171693E+09 | 0.367993E+09 | 0.732623E+09 | 0.126000E+09 |
| September | 0.620130E+09 | 0.305851E+09 | 0.314279E+09 | 0.775077E+09 | 0.203980E+09 |
| October | 0.607366E+09 | 0.347628E+09 | 0.259738E+09 | 0.667075E+09 | 0.312731E+09 |
| November | 0.421012E+09 | 0.238333E+09 | 0.182679E+09 | 0.408629E+09 | 0.385218E+09 |
| December | 0.404762E+09 | 0.209518E+09 | 0.195244E+09 | 0.313184E+09 | 0.593433E+09 |
| Annual Sum or Average | 0.621789E+10 | 0.274097E+10 | 0.347693E+10 | 0.679213E+10 | 0.388844E+10 |
| Minimum of Months | 0.404762E+09 | 98760793.79 | 0.182679E+09 | 0.313184E+09 | 92186496.20 |
| Maximum of Months | 0.664013E+09 | 0.368403E+09 | 0.367993E+09 | 0.775077E+09 | 0.605078E+09 |
Report: WindowEnergyReportMonthly
For: GWINDOW1 W SWA
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.116536E+09 | 27445700.15 | 89090096.08 | 31800025.56 | 0.444599E+09 |
| February | 0.170553E+09 | 44016659.46 | 0.126537E+09 | 73756278.46 | 0.373934E+09 |
| March | 0.296845E+09 | 0.127608E+09 | 0.169238E+09 | 0.247071E+09 | 0.281298E+09 |
| April | 0.349452E+09 | 0.143028E+09 | 0.206424E+09 | 0.346578E+09 | 0.189249E+09 |
| May | 0.426295E+09 | 0.192492E+09 | 0.233803E+09 | 0.490875E+09 | 0.123455E+09 |
| June | 0.498417E+09 | 0.234488E+09 | 0.263929E+09 | 0.622310E+09 | 85444868.96 |
| July | 0.459915E+09 | 0.201360E+09 | 0.258555E+09 | 0.610532E+09 | 59797985.90 |
| August | 0.415514E+09 | 0.176222E+09 | 0.239292E+09 | 0.538364E+09 | 81763138.40 |
| September | 0.316621E+09 | 0.136805E+09 | 0.179815E+09 | 0.364493E+09 | 0.133554E+09 |
| October | 0.212008E+09 | 74680744.99 | 0.137328E+09 | 0.186211E+09 | 0.213295E+09 |
| November | 0.120589E+09 | 34234006.48 | 86355470.88 | 72289839.21 | 0.266635E+09 |
| December | 0.108704E+09 | 23553783.07 | 85150677.71 | 29901052.38 | 0.426640E+09 |
| Annual Sum or Average | 0.349145E+10 | 0.141593E+10 | 0.207552E+10 | 0.361418E+10 | 0.267966E+10 |
| Minimum of Months | 0.108704E+09 | 23553783.07 | 85150677.71 | 29901052.38 | 59797985.90 |
| Maximum of Months | 0.498417E+09 | 0.234488E+09 | 0.263929E+09 | 0.622310E+09 | 0.444599E+09 |
Report: WindowEnergyReportMonthly
For: GWINDOW1 W NWA
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.116536E+09 | 27445700.15 | 89090096.08 | 32915101.08 | 0.440078E+09 |
| February | 0.170553E+09 | 44016659.46 | 0.126537E+09 | 75464288.98 | 0.370659E+09 |
| March | 0.296845E+09 | 0.127608E+09 | 0.169238E+09 | 0.251467E+09 | 0.276248E+09 |
| April | 0.349452E+09 | 0.143028E+09 | 0.206424E+09 | 0.351951E+09 | 0.185354E+09 |
| May | 0.426295E+09 | 0.192492E+09 | 0.233803E+09 | 0.497661E+09 | 0.118750E+09 |
| June | 0.498417E+09 | 0.234488E+09 | 0.263929E+09 | 0.624839E+09 | 84117991.42 |
| July | 0.459915E+09 | 0.201360E+09 | 0.258555E+09 | 0.612314E+09 | 59134047.47 |
| August | 0.415514E+09 | 0.176222E+09 | 0.239292E+09 | 0.541185E+09 | 80318995.95 |
| September | 0.316621E+09 | 0.136805E+09 | 0.179815E+09 | 0.369766E+09 | 0.128810E+09 |
| October | 0.212008E+09 | 74680744.99 | 0.137328E+09 | 0.194803E+09 | 0.201327E+09 |
| November | 0.120589E+09 | 34234006.48 | 86355470.88 | 75557594.49 | 0.260067E+09 |
| December | 0.108704E+09 | 23553783.07 | 85150677.71 | 30917061.28 | 0.422945E+09 |
| Annual Sum or Average | 0.349145E+10 | 0.141593E+10 | 0.207552E+10 | 0.365884E+10 | 0.262781E+10 |
| Minimum of Months | 0.108704E+09 | 23553783.07 | 85150677.71 | 30917061.28 | 59134047.47 |
| Maximum of Months | 0.498417E+09 | 0.234488E+09 | 0.263929E+09 | 0.624839E+09 | 0.440078E+09 |
Report: WindowEnergyReportMonthly
For: GWINDOW1 N NWA
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.112596E+09 | 0.00 | 0.112596E+09 | 365311.25 | 0.707804E+09 |
| February | 0.154952E+09 | 0.00 | 0.154952E+09 | 8736966.76 | 0.593152E+09 |
| March | 0.208080E+09 | 7369.23 | 0.208072E+09 | 78141909.90 | 0.449980E+09 |
| April | 0.256713E+09 | 1237747.44 | 0.255475E+09 | 0.163788E+09 | 0.286541E+09 |
| May | 0.308157E+09 | 13268987.07 | 0.294888E+09 | 0.284860E+09 | 0.171675E+09 |
| June | 0.358543E+09 | 30487239.06 | 0.328056E+09 | 0.400849E+09 | 0.119602E+09 |
| July | 0.345055E+09 | 23472851.36 | 0.321583E+09 | 0.440611E+09 | 84130293.24 |
| August | 0.298739E+09 | 5766984.46 | 0.292972E+09 | 0.356046E+09 | 0.118332E+09 |
| September | 0.219114E+09 | 96969.17 | 0.219018E+09 | 0.200269E+09 | 0.199172E+09 |
| October | 0.169177E+09 | 0.00 | 0.169177E+09 | 91112066.78 | 0.314890E+09 |
| November | 0.110016E+09 | 0.00 | 0.110016E+09 | 25847672.34 | 0.406406E+09 |
| December | 0.105386E+09 | 0.00 | 0.105386E+09 | 1539278.94 | 0.674250E+09 |
| Annual Sum or Average | 0.264653E+10 | 74338147.80 | 0.257219E+10 | 0.205217E+10 | 0.412594E+10 |
| Minimum of Months | 0.105386E+09 | 0.00 | 0.105386E+09 | 365311.25 | 84130293.24 |
| Maximum of Months | 0.358543E+09 | 30487239.06 | 0.328056E+09 | 0.440611E+09 | 0.707804E+09 |
Report: WindowEnergyReportMonthly
For: GWINDOW1 S SEA
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.482833E+09 | 0.281306E+09 | 0.201526E+09 | 0.415215E+09 | 0.514537E+09 |
| February | 0.498407E+09 | 0.239946E+09 | 0.258461E+09 | 0.426119E+09 | 0.455452E+09 |
| March | 0.664013E+09 | 0.368403E+09 | 0.295610E+09 | 0.691572E+09 | 0.365062E+09 |
| April | 0.546431E+09 | 0.221740E+09 | 0.324691E+09 | 0.597660E+09 | 0.274876E+09 |
| May | 0.488630E+09 | 0.141655E+09 | 0.346974E+09 | 0.565880E+09 | 0.205174E+09 |
| June | 0.461133E+09 | 98760793.79 | 0.362372E+09 | 0.567598E+09 | 0.154611E+09 |
| July | 0.483493E+09 | 0.116133E+09 | 0.367360E+09 | 0.642639E+09 | 0.126250E+09 |
| August | 0.539686E+09 | 0.171693E+09 | 0.367993E+09 | 0.708165E+09 | 0.164259E+09 |
| September | 0.620130E+09 | 0.305851E+09 | 0.314279E+09 | 0.761510E+09 | 0.233581E+09 |
| October | 0.607366E+09 | 0.347628E+09 | 0.259738E+09 | 0.662855E+09 | 0.323854E+09 |
| November | 0.421012E+09 | 0.238333E+09 | 0.182679E+09 | 0.415516E+09 | 0.362934E+09 |
| December | 0.404762E+09 | 0.209518E+09 | 0.195244E+09 | 0.330321E+09 | 0.512354E+09 |
| Annual Sum or Average | 0.621789E+10 | 0.274097E+10 | 0.347693E+10 | 0.678505E+10 | 0.369294E+10 |
| Minimum of Months | 0.404762E+09 | 98760793.79 | 0.182679E+09 | 0.330321E+09 | 0.126250E+09 |
| Maximum of Months | 0.664013E+09 | 0.368403E+09 | 0.367993E+09 | 0.761510E+09 | 0.514537E+09 |
Report: WindowEnergyReportMonthly
For: GWINDOW1 E SEA
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.135890E+09 | 44115383.46 | 91774696.76 | 59176425.44 | 0.362917E+09 |
| February | 0.179236E+09 | 53538670.03 | 0.125697E+09 | 95511961.04 | 0.309087E+09 |
| March | 0.285846E+09 | 0.119504E+09 | 0.166342E+09 | 0.242923E+09 | 0.241880E+09 |
| April | 0.365368E+09 | 0.161509E+09 | 0.203860E+09 | 0.371065E+09 | 0.169656E+09 |
| May | 0.422918E+09 | 0.186952E+09 | 0.235966E+09 | 0.478324E+09 | 0.125826E+09 |
| June | 0.457507E+09 | 0.202221E+09 | 0.255286E+09 | 0.554106E+09 | 93711113.20 |
| July | 0.453399E+09 | 0.199308E+09 | 0.254091E+09 | 0.578085E+09 | 76595121.61 |
| August | 0.409339E+09 | 0.171330E+09 | 0.238009E+09 | 0.507980E+09 | 0.101666E+09 |
| September | 0.328838E+09 | 0.145303E+09 | 0.183535E+09 | 0.370136E+09 | 0.148124E+09 |
| October | 0.230869E+09 | 95139569.63 | 0.135729E+09 | 0.206844E+09 | 0.214104E+09 |
| November | 0.126873E+09 | 40598305.06 | 86275191.41 | 82687181.48 | 0.245622E+09 |
| December | 0.105661E+09 | 21871167.95 | 83789688.80 | 31803625.32 | 0.361673E+09 |
| Annual Sum or Average | 0.350174E+10 | 0.144139E+10 | 0.206035E+10 | 0.357864E+10 | 0.245086E+10 |
| Minimum of Months | 0.105661E+09 | 21871167.95 | 83789688.80 | 31803625.32 | 76595121.61 |
| Maximum of Months | 0.457507E+09 | 0.202221E+09 | 0.255286E+09 | 0.578085E+09 | 0.362917E+09 |
Report: WindowEnergyReportMonthly
For: GWINDOW1 E NEA
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.135890E+09 | 44115383.46 | 91774696.76 | 52760499.08 | 0.423599E+09 |
| February | 0.179236E+09 | 53538670.03 | 0.125697E+09 | 85476876.06 | 0.358755E+09 |
| March | 0.285846E+09 | 0.119504E+09 | 0.166342E+09 | 0.234796E+09 | 0.268996E+09 |
| April | 0.365368E+09 | 0.161509E+09 | 0.203860E+09 | 0.368224E+09 | 0.177802E+09 |
| May | 0.422918E+09 | 0.186952E+09 | 0.235966E+09 | 0.490964E+09 | 0.112884E+09 |
| June | 0.457507E+09 | 0.202221E+09 | 0.255286E+09 | 0.567839E+09 | 78830424.09 |
| July | 0.453399E+09 | 0.199308E+09 | 0.254091E+09 | 0.600920E+09 | 55021293.78 |
| August | 0.409339E+09 | 0.171330E+09 | 0.238009E+09 | 0.527848E+09 | 76299820.43 |
| September | 0.328838E+09 | 0.145303E+09 | 0.183535E+09 | 0.383655E+09 | 0.124368E+09 |
| October | 0.230869E+09 | 95139569.63 | 0.135729E+09 | 0.216445E+09 | 0.194518E+09 |
| November | 0.126873E+09 | 40598305.06 | 86275191.41 | 82024622.74 | 0.254528E+09 |
| December | 0.105661E+09 | 21871167.95 | 83789688.80 | 26942216.60 | 0.416438E+09 |
| Annual Sum or Average | 0.350174E+10 | 0.144139E+10 | 0.206035E+10 | 0.363789E+10 | 0.254204E+10 |
| Minimum of Months | 0.105661E+09 | 21871167.95 | 83789688.80 | 26942216.60 | 55021293.78 |
| Maximum of Months | 0.457507E+09 | 0.202221E+09 | 0.255286E+09 | 0.600920E+09 | 0.423599E+09 |
Report: WindowEnergyReportMonthly
For: GWINDOW1 N NEA
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.112596E+09 | 0.00 | 0.112596E+09 | 354347.21 | 0.708360E+09 |
| February | 0.154952E+09 | 0.00 | 0.154952E+09 | 8586367.71 | 0.593420E+09 |
| March | 0.208080E+09 | 7369.23 | 0.208072E+09 | 77565771.74 | 0.449548E+09 |
| April | 0.256713E+09 | 1237747.44 | 0.255475E+09 | 0.162614E+09 | 0.286127E+09 |
| May | 0.308157E+09 | 13268987.07 | 0.294888E+09 | 0.283331E+09 | 0.170664E+09 |
| June | 0.358543E+09 | 30487239.06 | 0.328056E+09 | 0.400083E+09 | 0.118057E+09 |
| July | 0.345055E+09 | 23472851.36 | 0.321583E+09 | 0.439614E+09 | 83399975.44 |
| August | 0.298739E+09 | 5766984.46 | 0.292972E+09 | 0.355314E+09 | 0.117548E+09 |
| September | 0.219114E+09 | 96969.17 | 0.219018E+09 | 0.198581E+09 | 0.198835E+09 |
| October | 0.169177E+09 | 0.00 | 0.169177E+09 | 89901307.16 | 0.315091E+09 |
| November | 0.110016E+09 | 0.00 | 0.110016E+09 | 25579975.71 | 0.406493E+09 |
| December | 0.105386E+09 | 0.00 | 0.105386E+09 | 1525115.93 | 0.674327E+09 |
| Annual Sum or Average | 0.264653E+10 | 74338147.80 | 0.257219E+10 | 0.204305E+10 | 0.412187E+10 |
| Minimum of Months | 0.105386E+09 | 0.00 | 0.105386E+09 | 354347.21 | 83399975.44 |
| Maximum of Months | 0.358543E+09 | 30487239.06 | 0.328056E+09 | 0.439614E+09 | 0.708360E+09 |
Report: WindowEnergyReportMonthly
For: GWINDOW1 N N1A
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.112596E+09 | 0.00 | 0.112596E+09 | 246666.40 | 0.720809E+09 |
| February | 0.154952E+09 | 0.00 | 0.154952E+09 | 7908502.86 | 0.603998E+09 |
| March | 0.208080E+09 | 7369.23 | 0.208072E+09 | 76026905.56 | 0.458299E+09 |
| April | 0.256713E+09 | 1237747.44 | 0.255475E+09 | 0.161678E+09 | 0.291575E+09 |
| May | 0.308157E+09 | 13268987.07 | 0.294888E+09 | 0.281779E+09 | 0.176475E+09 |
| June | 0.358543E+09 | 30487239.06 | 0.328056E+09 | 0.400877E+09 | 0.120821E+09 |
| July | 0.345055E+09 | 23472851.36 | 0.321583E+09 | 0.443011E+09 | 83535667.50 |
| August | 0.298739E+09 | 5766984.46 | 0.292972E+09 | 0.358349E+09 | 0.117874E+09 |
| September | 0.219114E+09 | 96969.17 | 0.219018E+09 | 0.199700E+09 | 0.202254E+09 |
| October | 0.169177E+09 | 0.00 | 0.169177E+09 | 88719053.69 | 0.322413E+09 |
| November | 0.110016E+09 | 0.00 | 0.110016E+09 | 24929851.09 | 0.414034E+09 |
| December | 0.105386E+09 | 0.00 | 0.105386E+09 | 1382409.71 | 0.685863E+09 |
| Annual Sum or Average | 0.264653E+10 | 74338147.80 | 0.257219E+10 | 0.204461E+10 | 0.419795E+10 |
| Minimum of Months | 0.105386E+09 | 0.00 | 0.105386E+09 | 246666.40 | 83535667.50 |
| Maximum of Months | 0.358543E+09 | 30487239.06 | 0.328056E+09 | 0.443011E+09 | 0.720809E+09 |
Report: WindowEnergyReportMonthly
For: GWINDOW1 N N2A
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.112596E+09 | 0.00 | 0.112596E+09 | 246373.50 | 0.720834E+09 |
| February | 0.154952E+09 | 0.00 | 0.154952E+09 | 7902738.98 | 0.604010E+09 |
| March | 0.208080E+09 | 7369.23 | 0.208072E+09 | 76000388.55 | 0.458298E+09 |
| April | 0.256713E+09 | 1237747.44 | 0.255475E+09 | 0.161614E+09 | 0.291580E+09 |
| May | 0.308157E+09 | 13268987.07 | 0.294888E+09 | 0.281675E+09 | 0.176451E+09 |
| June | 0.358543E+09 | 30487239.06 | 0.328056E+09 | 0.400876E+09 | 0.120735E+09 |
| July | 0.345055E+09 | 23472851.36 | 0.321583E+09 | 0.442976E+09 | 83514825.03 |
| August | 0.298739E+09 | 5766984.46 | 0.292972E+09 | 0.358326E+09 | 0.117846E+09 |
| September | 0.219114E+09 | 96969.17 | 0.219018E+09 | 0.199608E+09 | 0.202278E+09 |
| October | 0.169177E+09 | 0.00 | 0.169177E+09 | 88628648.01 | 0.322509E+09 |
| November | 0.110016E+09 | 0.00 | 0.110016E+09 | 24917448.60 | 0.414049E+09 |
| December | 0.105386E+09 | 0.00 | 0.105386E+09 | 1381943.16 | 0.685868E+09 |
| Annual Sum or Average | 0.264653E+10 | 74338147.80 | 0.257219E+10 | 0.204415E+10 | 0.419797E+10 |
| Minimum of Months | 0.105386E+09 | 0.00 | 0.105386E+09 | 246373.50 | 83514825.03 |
| Maximum of Months | 0.358543E+09 | 30487239.06 | 0.328056E+09 | 0.442976E+09 | 0.720834E+09 |
Report: WindowEnergyReportMonthly
For: GWINDOW1 S S1A
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.482833E+09 | 0.281306E+09 | 0.201526E+09 | 0.391917E+09 | 0.616210E+09 |
| February | 0.498407E+09 | 0.239946E+09 | 0.258461E+09 | 0.400047E+09 | 0.541084E+09 |
| March | 0.664013E+09 | 0.368403E+09 | 0.295610E+09 | 0.668383E+09 | 0.422674E+09 |
| April | 0.546431E+09 | 0.221740E+09 | 0.324691E+09 | 0.585912E+09 | 0.303159E+09 |
| May | 0.488630E+09 | 0.141655E+09 | 0.346974E+09 | 0.571964E+09 | 0.200816E+09 |
| June | 0.461133E+09 | 98760793.79 | 0.362372E+09 | 0.583888E+09 | 0.135399E+09 |
| July | 0.483493E+09 | 0.116133E+09 | 0.367360E+09 | 0.675899E+09 | 91696081.75 |
| August | 0.539686E+09 | 0.171693E+09 | 0.367993E+09 | 0.734608E+09 | 0.125610E+09 |
| September | 0.620130E+09 | 0.305851E+09 | 0.314279E+09 | 0.774542E+09 | 0.206650E+09 |
| October | 0.607366E+09 | 0.347628E+09 | 0.259738E+09 | 0.661348E+09 | 0.324524E+09 |
| November | 0.421012E+09 | 0.238333E+09 | 0.182679E+09 | 0.405407E+09 | 0.394889E+09 |
| December | 0.404762E+09 | 0.209518E+09 | 0.195244E+09 | 0.310707E+09 | 0.603938E+09 |
| Annual Sum or Average | 0.621789E+10 | 0.274097E+10 | 0.347693E+10 | 0.676462E+10 | 0.396665E+10 |
| Minimum of Months | 0.404762E+09 | 98760793.79 | 0.182679E+09 | 0.310707E+09 | 91696081.75 |
| Maximum of Months | 0.664013E+09 | 0.368403E+09 | 0.367993E+09 | 0.774542E+09 | 0.616210E+09 |
Report: WindowEnergyReportMonthly
For: GWINDOW1 S S2A
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.482833E+09 | 0.281306E+09 | 0.201526E+09 | 0.392833E+09 | 0.612667E+09 |
| February | 0.498407E+09 | 0.239946E+09 | 0.258461E+09 | 0.401055E+09 | 0.538298E+09 |
| March | 0.664013E+09 | 0.368403E+09 | 0.295610E+09 | 0.669382E+09 | 0.420569E+09 |
| April | 0.546431E+09 | 0.221740E+09 | 0.324691E+09 | 0.586425E+09 | 0.302057E+09 |
| May | 0.488630E+09 | 0.141655E+09 | 0.346974E+09 | 0.570476E+09 | 0.202203E+09 |
| June | 0.461133E+09 | 98760793.79 | 0.362372E+09 | 0.582527E+09 | 0.136564E+09 |
| July | 0.483493E+09 | 0.116133E+09 | 0.367360E+09 | 0.674299E+09 | 92945618.44 |
| August | 0.539686E+09 | 0.171693E+09 | 0.367993E+09 | 0.733232E+09 | 0.127011E+09 |
| September | 0.620130E+09 | 0.305851E+09 | 0.314279E+09 | 0.773652E+09 | 0.207890E+09 |
| October | 0.607366E+09 | 0.347628E+09 | 0.259738E+09 | 0.660509E+09 | 0.325823E+09 |
| November | 0.421012E+09 | 0.238333E+09 | 0.182679E+09 | 0.405789E+09 | 0.393668E+09 |
| December | 0.404762E+09 | 0.209518E+09 | 0.195244E+09 | 0.311477E+09 | 0.600701E+09 |
| Annual Sum or Average | 0.621789E+10 | 0.274097E+10 | 0.347693E+10 | 0.676166E+10 | 0.396040E+10 |
| Minimum of Months | 0.404762E+09 | 98760793.79 | 0.182679E+09 | 0.311477E+09 | 92945618.44 |
| Maximum of Months | 0.664013E+09 | 0.368403E+09 | 0.367993E+09 | 0.773652E+09 | 0.612667E+09 |
Report: WindowEnergyReportMonthly
For: MWINDOW1 S SWA
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.482833E+09 | 0.281306E+09 | 0.201526E+09 | 0.386553E+09 | 0.627734E+09 |
| February | 0.498407E+09 | 0.239946E+09 | 0.258461E+09 | 0.392342E+09 | 0.553547E+09 |
| March | 0.664013E+09 | 0.368403E+09 | 0.295610E+09 | 0.653442E+09 | 0.441430E+09 |
| April | 0.546431E+09 | 0.221740E+09 | 0.324691E+09 | 0.564178E+09 | 0.331345E+09 |
| May | 0.488630E+09 | 0.141655E+09 | 0.346974E+09 | 0.539085E+09 | 0.239640E+09 |
| June | 0.461133E+09 | 98760793.79 | 0.362372E+09 | 0.570627E+09 | 0.144115E+09 |
| July | 0.483493E+09 | 0.116133E+09 | 0.367360E+09 | 0.666853E+09 | 95455355.59 |
| August | 0.539686E+09 | 0.171693E+09 | 0.367993E+09 | 0.727942E+09 | 0.128046E+09 |
| September | 0.620130E+09 | 0.305851E+09 | 0.314279E+09 | 0.770311E+09 | 0.206867E+09 |
| October | 0.607366E+09 | 0.347628E+09 | 0.259738E+09 | 0.658757E+09 | 0.322337E+09 |
| November | 0.421012E+09 | 0.238333E+09 | 0.182679E+09 | 0.401995E+09 | 0.397734E+09 |
| December | 0.404762E+09 | 0.209518E+09 | 0.195244E+09 | 0.306609E+09 | 0.612741E+09 |
| Annual Sum or Average | 0.621789E+10 | 0.274097E+10 | 0.347693E+10 | 0.663870E+10 | 0.410099E+10 |
| Minimum of Months | 0.404762E+09 | 98760793.79 | 0.182679E+09 | 0.306609E+09 | 95455355.59 |
| Maximum of Months | 0.664013E+09 | 0.368403E+09 | 0.367993E+09 | 0.770311E+09 | 0.627734E+09 |
Report: WindowEnergyReportMonthly
For: MWINDOW1 W SWA
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.116536E+09 | 27445700.15 | 89090096.08 | 30003127.09 | 0.463611E+09 |
| February | 0.170553E+09 | 44016659.46 | 0.126537E+09 | 69369007.86 | 0.390966E+09 |
| March | 0.296845E+09 | 0.127608E+09 | 0.169238E+09 | 0.235805E+09 | 0.300539E+09 |
| April | 0.349452E+09 | 0.143028E+09 | 0.206424E+09 | 0.328762E+09 | 0.210724E+09 |
| May | 0.426295E+09 | 0.192492E+09 | 0.233803E+09 | 0.464027E+09 | 0.152000E+09 |
| June | 0.498417E+09 | 0.234488E+09 | 0.263929E+09 | 0.612408E+09 | 92015683.92 |
| July | 0.459915E+09 | 0.201360E+09 | 0.258555E+09 | 0.605597E+09 | 61919068.21 |
| August | 0.415514E+09 | 0.176222E+09 | 0.239292E+09 | 0.535214E+09 | 83130495.77 |
| September | 0.316621E+09 | 0.136805E+09 | 0.179815E+09 | 0.361555E+09 | 0.135547E+09 |
| October | 0.212008E+09 | 74680744.99 | 0.137328E+09 | 0.181673E+09 | 0.220263E+09 |
| November | 0.120589E+09 | 34234006.48 | 86355470.88 | 69385987.02 | 0.275895E+09 |
| December | 0.108704E+09 | 23553783.07 | 85150677.71 | 28147527.22 | 0.441895E+09 |
| Annual Sum or Average | 0.349145E+10 | 0.141593E+10 | 0.207552E+10 | 0.352195E+10 | 0.282851E+10 |
| Minimum of Months | 0.108704E+09 | 23553783.07 | 85150677.71 | 28147527.22 | 61919068.21 |
| Maximum of Months | 0.498417E+09 | 0.234488E+09 | 0.263929E+09 | 0.612408E+09 | 0.463611E+09 |
Report: WindowEnergyReportMonthly
For: MWINDOW1 W NWA
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.116536E+09 | 27445700.15 | 89090096.08 | 31286307.84 | 0.458791E+09 |
| February | 0.170553E+09 | 44016659.46 | 0.126537E+09 | 71302469.27 | 0.387358E+09 |
| March | 0.296845E+09 | 0.127608E+09 | 0.169238E+09 | 0.240846E+09 | 0.295072E+09 |
| April | 0.349452E+09 | 0.143028E+09 | 0.206424E+09 | 0.336853E+09 | 0.203198E+09 |
| May | 0.426295E+09 | 0.192492E+09 | 0.233803E+09 | 0.468112E+09 | 0.149099E+09 |
| June | 0.498417E+09 | 0.234488E+09 | 0.263929E+09 | 0.613744E+09 | 91761486.35 |
| July | 0.459915E+09 | 0.201360E+09 | 0.258555E+09 | 0.607122E+09 | 61551237.07 |
| August | 0.415514E+09 | 0.176222E+09 | 0.239292E+09 | 0.537633E+09 | 82226450.43 |
| September | 0.316621E+09 | 0.136805E+09 | 0.179815E+09 | 0.366021E+09 | 0.132455E+09 |
| October | 0.212008E+09 | 74680744.99 | 0.137328E+09 | 0.190525E+09 | 0.208781E+09 |
| November | 0.120589E+09 | 34234006.48 | 86355470.88 | 73242350.13 | 0.268759E+09 |
| December | 0.108704E+09 | 23553783.07 | 85150677.71 | 29332393.95 | 0.438308E+09 |
| Annual Sum or Average | 0.349145E+10 | 0.141593E+10 | 0.207552E+10 | 0.356602E+10 | 0.277736E+10 |
| Minimum of Months | 0.108704E+09 | 23553783.07 | 85150677.71 | 29332393.95 | 61551237.07 |
| Maximum of Months | 0.498417E+09 | 0.234488E+09 | 0.263929E+09 | 0.613744E+09 | 0.458791E+09 |
Report: WindowEnergyReportMonthly
For: MWINDOW1 N NWA
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.112596E+09 | 0.00 | 0.112596E+09 | 109985.36 | 0.736790E+09 |
| February | 0.154952E+09 | 0.00 | 0.154952E+09 | 6491440.56 | 0.619977E+09 |
| March | 0.208080E+09 | 7369.23 | 0.208072E+09 | 67746543.13 | 0.481833E+09 |
| April | 0.256713E+09 | 1237747.44 | 0.255475E+09 | 0.145307E+09 | 0.315797E+09 |
| May | 0.308157E+09 | 13268987.07 | 0.294888E+09 | 0.240740E+09 | 0.215551E+09 |
| June | 0.358543E+09 | 30487239.06 | 0.328056E+09 | 0.384978E+09 | 0.129964E+09 |
| July | 0.345055E+09 | 23472851.36 | 0.321583E+09 | 0.434129E+09 | 87386575.28 |
| August | 0.298739E+09 | 5766984.46 | 0.292972E+09 | 0.352015E+09 | 0.121116E+09 |
| September | 0.219114E+09 | 96969.17 | 0.219018E+09 | 0.196011E+09 | 0.204764E+09 |
| October | 0.169177E+09 | 0.00 | 0.169177E+09 | 86409781.64 | 0.326391E+09 |
| November | 0.110016E+09 | 0.00 | 0.110016E+09 | 23733232.98 | 0.419503E+09 |
| December | 0.105386E+09 | 0.00 | 0.105386E+09 | 1229120.13 | 0.697460E+09 |
| Annual Sum or Average | 0.264653E+10 | 74338147.80 | 0.257219E+10 | 0.193890E+10 | 0.435653E+10 |
| Minimum of Months | 0.105386E+09 | 0.00 | 0.105386E+09 | 109985.36 | 87386575.28 |
| Maximum of Months | 0.358543E+09 | 30487239.06 | 0.328056E+09 | 0.434129E+09 | 0.736790E+09 |
Report: WindowEnergyReportMonthly
For: MWINDOW1 S SEA
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.482833E+09 | 0.281306E+09 | 0.201526E+09 | 0.386011E+09 | 0.627848E+09 |
| February | 0.498407E+09 | 0.239946E+09 | 0.258461E+09 | 0.391745E+09 | 0.553404E+09 |
| March | 0.664013E+09 | 0.368403E+09 | 0.295610E+09 | 0.652402E+09 | 0.440176E+09 |
| April | 0.546431E+09 | 0.221740E+09 | 0.324691E+09 | 0.561553E+09 | 0.330408E+09 |
| May | 0.488630E+09 | 0.141655E+09 | 0.346974E+09 | 0.537101E+09 | 0.238404E+09 |
| June | 0.461133E+09 | 98760793.79 | 0.362372E+09 | 0.569665E+09 | 0.142918E+09 |
| July | 0.483493E+09 | 0.116133E+09 | 0.367360E+09 | 0.665910E+09 | 94685037.22 |
| August | 0.539686E+09 | 0.171693E+09 | 0.367993E+09 | 0.727167E+09 | 0.127267E+09 |
| September | 0.620130E+09 | 0.305851E+09 | 0.314279E+09 | 0.769187E+09 | 0.206083E+09 |
| October | 0.607366E+09 | 0.347628E+09 | 0.259738E+09 | 0.656615E+09 | 0.322550E+09 |
| November | 0.421012E+09 | 0.238333E+09 | 0.182679E+09 | 0.401401E+09 | 0.397640E+09 |
| December | 0.404762E+09 | 0.209518E+09 | 0.195244E+09 | 0.306365E+09 | 0.612614E+09 |
| Annual Sum or Average | 0.621789E+10 | 0.274097E+10 | 0.347693E+10 | 0.662512E+10 | 0.409400E+10 |
| Minimum of Months | 0.404762E+09 | 98760793.79 | 0.182679E+09 | 0.306365E+09 | 94685037.22 |
| Maximum of Months | 0.664013E+09 | 0.368403E+09 | 0.367993E+09 | 0.769187E+09 | 0.627848E+09 |
Report: WindowEnergyReportMonthly
For: MWINDOW1 E SEA
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.135890E+09 | 44115383.46 | 91774696.76 | 49503355.77 | 0.445757E+09 |
| February | 0.179236E+09 | 53538670.03 | 0.125697E+09 | 79922597.19 | 0.378354E+09 |
| March | 0.285846E+09 | 0.119504E+09 | 0.166342E+09 | 0.220754E+09 | 0.293743E+09 |
| April | 0.365368E+09 | 0.161509E+09 | 0.203860E+09 | 0.345019E+09 | 0.203141E+09 |
| May | 0.422918E+09 | 0.186952E+09 | 0.235966E+09 | 0.457187E+09 | 0.145108E+09 |
| June | 0.457507E+09 | 0.202221E+09 | 0.255286E+09 | 0.555690E+09 | 86491331.39 |
| July | 0.453399E+09 | 0.199308E+09 | 0.254091E+09 | 0.594625E+09 | 57601546.50 |
| August | 0.409339E+09 | 0.171330E+09 | 0.238009E+09 | 0.521924E+09 | 79093652.59 |
| September | 0.328838E+09 | 0.145303E+09 | 0.183535E+09 | 0.375841E+09 | 0.130629E+09 |
| October | 0.230869E+09 | 95139569.63 | 0.135729E+09 | 0.203490E+09 | 0.213320E+09 |
| November | 0.126873E+09 | 40598305.06 | 86275191.41 | 76348651.29 | 0.270509E+09 |
| December | 0.105661E+09 | 21871167.95 | 83789688.80 | 25015016.04 | 0.435408E+09 |
| Annual Sum or Average | 0.350174E+10 | 0.144139E+10 | 0.206035E+10 | 0.350532E+10 | 0.273915E+10 |
| Minimum of Months | 0.105661E+09 | 21871167.95 | 83789688.80 | 25015016.04 | 57601546.50 |
| Maximum of Months | 0.457507E+09 | 0.202221E+09 | 0.255286E+09 | 0.594625E+09 | 0.445757E+09 |
Report: WindowEnergyReportMonthly
For: MWINDOW1 E NEA
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.135890E+09 | 44115383.46 | 91774696.76 | 50453842.84 | 0.440629E+09 |
| February | 0.179236E+09 | 53538670.03 | 0.125697E+09 | 81351565.32 | 0.374356E+09 |
| March | 0.285846E+09 | 0.119504E+09 | 0.166342E+09 | 0.224626E+09 | 0.287515E+09 |
| April | 0.365368E+09 | 0.161509E+09 | 0.203860E+09 | 0.352634E+09 | 0.195460E+09 |
| May | 0.422918E+09 | 0.186952E+09 | 0.235966E+09 | 0.460908E+09 | 0.142297E+09 |
| June | 0.457507E+09 | 0.202221E+09 | 0.255286E+09 | 0.556973E+09 | 86185806.43 |
| July | 0.453399E+09 | 0.199308E+09 | 0.254091E+09 | 0.596111E+09 | 57203665.57 |
| August | 0.409339E+09 | 0.171330E+09 | 0.238009E+09 | 0.524322E+09 | 78150272.81 |
| September | 0.328838E+09 | 0.145303E+09 | 0.183535E+09 | 0.380042E+09 | 0.127613E+09 |
| October | 0.230869E+09 | 95139569.63 | 0.135729E+09 | 0.212043E+09 | 0.201413E+09 |
| November | 0.126873E+09 | 40598305.06 | 86275191.41 | 79634763.86 | 0.262820E+09 |
| December | 0.105661E+09 | 21871167.95 | 83789688.80 | 25568143.24 | 0.431234E+09 |
| Annual Sum or Average | 0.350174E+10 | 0.144139E+10 | 0.206035E+10 | 0.354467E+10 | 0.268488E+10 |
| Minimum of Months | 0.105661E+09 | 21871167.95 | 83789688.80 | 25568143.24 | 57203665.57 |
| Maximum of Months | 0.457507E+09 | 0.202221E+09 | 0.255286E+09 | 0.596111E+09 | 0.440629E+09 |
Report: WindowEnergyReportMonthly
For: MWINDOW1 N NEA
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.112596E+09 | 0.00 | 0.112596E+09 | 101630.33 | 0.737365E+09 |
| February | 0.154952E+09 | 0.00 | 0.154952E+09 | 6343606.15 | 0.620266E+09 |
| March | 0.208080E+09 | 7369.23 | 0.208072E+09 | 66999207.64 | 0.481307E+09 |
| April | 0.256713E+09 | 1237747.44 | 0.255475E+09 | 0.142764E+09 | 0.315389E+09 |
| May | 0.308157E+09 | 13268987.07 | 0.294888E+09 | 0.238296E+09 | 0.214591E+09 |
| June | 0.358543E+09 | 30487239.06 | 0.328056E+09 | 0.383966E+09 | 0.128860E+09 |
| July | 0.345055E+09 | 23472851.36 | 0.321583E+09 | 0.433101E+09 | 86607238.01 |
| August | 0.298739E+09 | 5766984.46 | 0.292972E+09 | 0.351206E+09 | 0.120354E+09 |
| September | 0.219114E+09 | 96969.17 | 0.219018E+09 | 0.194447E+09 | 0.204116E+09 |
| October | 0.169177E+09 | 0.00 | 0.169177E+09 | 84908026.14 | 0.326409E+09 |
| November | 0.110016E+09 | 0.00 | 0.110016E+09 | 23414615.57 | 0.419588E+09 |
| December | 0.105386E+09 | 0.00 | 0.105386E+09 | 1216467.84 | 0.697542E+09 |
| Annual Sum or Average | 0.264653E+10 | 74338147.80 | 0.257219E+10 | 0.192676E+10 | 0.435239E+10 |
| Minimum of Months | 0.105386E+09 | 0.00 | 0.105386E+09 | 101630.33 | 86607238.01 |
| Maximum of Months | 0.358543E+09 | 30487239.06 | 0.328056E+09 | 0.433101E+09 | 0.737365E+09 |
Report: WindowEnergyReportMonthly
For: MWINDOW1 N N1A
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.112596E+09 | 0.00 | 0.112596E+09 | 61752.59 | 0.748493E+09 |
| February | 0.154952E+09 | 0.00 | 0.154952E+09 | 5953740.85 | 0.629320E+09 |
| March | 0.208080E+09 | 7369.23 | 0.208072E+09 | 66526808.62 | 0.488099E+09 |
| April | 0.256713E+09 | 1237747.44 | 0.255475E+09 | 0.144214E+09 | 0.319728E+09 |
| May | 0.308157E+09 | 13268987.07 | 0.294888E+09 | 0.240308E+09 | 0.218844E+09 |
| June | 0.358543E+09 | 30487239.06 | 0.328056E+09 | 0.388292E+09 | 0.129088E+09 |
| July | 0.345055E+09 | 23472851.36 | 0.321583E+09 | 0.438374E+09 | 85861613.34 |
| August | 0.298739E+09 | 5766984.46 | 0.292972E+09 | 0.355410E+09 | 0.120011E+09 |
| September | 0.219114E+09 | 96969.17 | 0.219018E+09 | 0.196145E+09 | 0.207203E+09 |
| October | 0.169177E+09 | 0.00 | 0.169177E+09 | 83567208.48 | 0.336130E+09 |
| November | 0.110016E+09 | 0.00 | 0.110016E+09 | 22791590.92 | 0.427816E+09 |
| December | 0.105386E+09 | 0.00 | 0.105386E+09 | 1114336.51 | 0.709000E+09 |
| Annual Sum or Average | 0.264653E+10 | 74338147.80 | 0.257219E+10 | 0.194276E+10 | 0.441959E+10 |
| Minimum of Months | 0.105386E+09 | 0.00 | 0.105386E+09 | 61752.59 | 85861613.34 |
| Maximum of Months | 0.358543E+09 | 30487239.06 | 0.328056E+09 | 0.438374E+09 | 0.748493E+09 |
Report: WindowEnergyReportMonthly
For: MWINDOW1 N N2A
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.112596E+09 | 0.00 | 0.112596E+09 | 61598.14 | 0.748521E+09 |
| February | 0.154952E+09 | 0.00 | 0.154952E+09 | 5946657.42 | 0.629337E+09 |
| March | 0.208080E+09 | 7369.23 | 0.208072E+09 | 66494484.03 | 0.488088E+09 |
| April | 0.256713E+09 | 1237747.44 | 0.255475E+09 | 0.144001E+09 | 0.319864E+09 |
| May | 0.308157E+09 | 13268987.07 | 0.294888E+09 | 0.240157E+09 | 0.218840E+09 |
| June | 0.358543E+09 | 30487239.06 | 0.328056E+09 | 0.388254E+09 | 0.129049E+09 |
| July | 0.345055E+09 | 23472851.36 | 0.321583E+09 | 0.438340E+09 | 85837305.77 |
| August | 0.298739E+09 | 5766984.46 | 0.292972E+09 | 0.355382E+09 | 0.119984E+09 |
| September | 0.219114E+09 | 96969.17 | 0.219018E+09 | 0.196082E+09 | 0.207179E+09 |
| October | 0.169177E+09 | 0.00 | 0.169177E+09 | 83449610.24 | 0.336239E+09 |
| November | 0.110016E+09 | 0.00 | 0.110016E+09 | 22776556.88 | 0.427836E+09 |
| December | 0.105386E+09 | 0.00 | 0.105386E+09 | 1113773.77 | 0.709006E+09 |
| Annual Sum or Average | 0.264653E+10 | 74338147.80 | 0.257219E+10 | 0.194206E+10 | 0.441978E+10 |
| Minimum of Months | 0.105386E+09 | 0.00 | 0.105386E+09 | 61598.14 | 85837305.77 |
| Maximum of Months | 0.358543E+09 | 30487239.06 | 0.328056E+09 | 0.438340E+09 | 0.748521E+09 |
Report: WindowEnergyReportMonthly
For: MWINDOW1 S S1A
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.482833E+09 | 0.281306E+09 | 0.201526E+09 | 0.383603E+09 | 0.638473E+09 |
| February | 0.498407E+09 | 0.239946E+09 | 0.258461E+09 | 0.389308E+09 | 0.562176E+09 |
| March | 0.664013E+09 | 0.368403E+09 | 0.295610E+09 | 0.650311E+09 | 0.448312E+09 |
| April | 0.546431E+09 | 0.221740E+09 | 0.324691E+09 | 0.561053E+09 | 0.338376E+09 |
| May | 0.488630E+09 | 0.141655E+09 | 0.346974E+09 | 0.538363E+09 | 0.243254E+09 |
| June | 0.461133E+09 | 98760793.79 | 0.362372E+09 | 0.573749E+09 | 0.143058E+09 |
| July | 0.483493E+09 | 0.116133E+09 | 0.367360E+09 | 0.670908E+09 | 93820878.23 |
| August | 0.539686E+09 | 0.171693E+09 | 0.367993E+09 | 0.731022E+09 | 0.126896E+09 |
| September | 0.620130E+09 | 0.305851E+09 | 0.314279E+09 | 0.770556E+09 | 0.208831E+09 |
| October | 0.607366E+09 | 0.347628E+09 | 0.259738E+09 | 0.652797E+09 | 0.335494E+09 |
| November | 0.421012E+09 | 0.238333E+09 | 0.182679E+09 | 0.398245E+09 | 0.409519E+09 |
| December | 0.404762E+09 | 0.209518E+09 | 0.195244E+09 | 0.304120E+09 | 0.623565E+09 |
| Annual Sum or Average | 0.621789E+10 | 0.274097E+10 | 0.347693E+10 | 0.662403E+10 | 0.417177E+10 |
| Minimum of Months | 0.404762E+09 | 98760793.79 | 0.182679E+09 | 0.304120E+09 | 93820878.23 |
| Maximum of Months | 0.664013E+09 | 0.368403E+09 | 0.367993E+09 | 0.770556E+09 | 0.638473E+09 |
Report: WindowEnergyReportMonthly
For: MWINDOW1 S S2A
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.482833E+09 | 0.281306E+09 | 0.201526E+09 | 0.383583E+09 | 0.638489E+09 |
| February | 0.498407E+09 | 0.239946E+09 | 0.258461E+09 | 0.389282E+09 | 0.562177E+09 |
| March | 0.664013E+09 | 0.368403E+09 | 0.295610E+09 | 0.650263E+09 | 0.448252E+09 |
| April | 0.546431E+09 | 0.221740E+09 | 0.324691E+09 | 0.560892E+09 | 0.338406E+09 |
| May | 0.488630E+09 | 0.141655E+09 | 0.346974E+09 | 0.538284E+09 | 0.243202E+09 |
| June | 0.461133E+09 | 98760793.79 | 0.362372E+09 | 0.573711E+09 | 0.143009E+09 |
| July | 0.483493E+09 | 0.116133E+09 | 0.367360E+09 | 0.670873E+09 | 93793720.07 |
| August | 0.539686E+09 | 0.171693E+09 | 0.367993E+09 | 0.730995E+09 | 0.126867E+09 |
| September | 0.620130E+09 | 0.305851E+09 | 0.314279E+09 | 0.770523E+09 | 0.208801E+09 |
| October | 0.607366E+09 | 0.347628E+09 | 0.259738E+09 | 0.652660E+09 | 0.335611E+09 |
| November | 0.421012E+09 | 0.238333E+09 | 0.182679E+09 | 0.398208E+09 | 0.409549E+09 |
| December | 0.404762E+09 | 0.209518E+09 | 0.195244E+09 | 0.304108E+09 | 0.623562E+09 |
| Annual Sum or Average | 0.621789E+10 | 0.274097E+10 | 0.347693E+10 | 0.662338E+10 | 0.417172E+10 |
| Minimum of Months | 0.404762E+09 | 98760793.79 | 0.182679E+09 | 0.304108E+09 | 93793720.07 |
| Maximum of Months | 0.664013E+09 | 0.368403E+09 | 0.367993E+09 | 0.770523E+09 | 0.638489E+09 |
Report: WindowEnergyReportMonthly
For: TWINDOW1 S SWA
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.482833E+09 | 0.281306E+09 | 0.201526E+09 | 0.388312E+09 | 0.607983E+09 |
| February | 0.498407E+09 | 0.239946E+09 | 0.258461E+09 | 0.393468E+09 | 0.537150E+09 |
| March | 0.664013E+09 | 0.368403E+09 | 0.295610E+09 | 0.652868E+09 | 0.424107E+09 |
| April | 0.546431E+09 | 0.221740E+09 | 0.324691E+09 | 0.564001E+09 | 0.313254E+09 |
| May | 0.488630E+09 | 0.141655E+09 | 0.346974E+09 | 0.544957E+09 | 0.214119E+09 |
| June | 0.461133E+09 | 98760793.79 | 0.362372E+09 | 0.566501E+09 | 0.134447E+09 |
| July | 0.483493E+09 | 0.116133E+09 | 0.367360E+09 | 0.657272E+09 | 91694886.13 |
| August | 0.539686E+09 | 0.171693E+09 | 0.367993E+09 | 0.720826E+09 | 0.121649E+09 |
| September | 0.620130E+09 | 0.305851E+09 | 0.314279E+09 | 0.771785E+09 | 0.187252E+09 |
| October | 0.607366E+09 | 0.347628E+09 | 0.259738E+09 | 0.663568E+09 | 0.296883E+09 |
| November | 0.421012E+09 | 0.238333E+09 | 0.182679E+09 | 0.403299E+09 | 0.378369E+09 |
| December | 0.404762E+09 | 0.209518E+09 | 0.195244E+09 | 0.307757E+09 | 0.593400E+09 |
| Annual Sum or Average | 0.621789E+10 | 0.274097E+10 | 0.347693E+10 | 0.663461E+10 | 0.390031E+10 |
| Minimum of Months | 0.404762E+09 | 98760793.79 | 0.182679E+09 | 0.307757E+09 | 91694886.13 |
| Maximum of Months | 0.664013E+09 | 0.368403E+09 | 0.367993E+09 | 0.771785E+09 | 0.607983E+09 |
Report: WindowEnergyReportMonthly
For: TWINDOW1 W SWA
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.116536E+09 | 27445700.15 | 89090096.08 | 29838887.14 | 0.449057E+09 |
| February | 0.170553E+09 | 44016659.46 | 0.126537E+09 | 69281396.64 | 0.378810E+09 |
| March | 0.296845E+09 | 0.127608E+09 | 0.169238E+09 | 0.234560E+09 | 0.287966E+09 |
| April | 0.349452E+09 | 0.143028E+09 | 0.206424E+09 | 0.327805E+09 | 0.197800E+09 |
| May | 0.426295E+09 | 0.192492E+09 | 0.233803E+09 | 0.467548E+09 | 0.134769E+09 |
| June | 0.498417E+09 | 0.234488E+09 | 0.263929E+09 | 0.609062E+09 | 85267076.88 |
| July | 0.459915E+09 | 0.201360E+09 | 0.258555E+09 | 0.598875E+09 | 59186785.30 |
| August | 0.415514E+09 | 0.176222E+09 | 0.239292E+09 | 0.530339E+09 | 78692116.93 |
| September | 0.316621E+09 | 0.136805E+09 | 0.179815E+09 | 0.361739E+09 | 0.121682E+09 |
| October | 0.212008E+09 | 74680744.99 | 0.137328E+09 | 0.183721E+09 | 0.201963E+09 |
| November | 0.120589E+09 | 34234006.48 | 86355470.88 | 69390945.18 | 0.261800E+09 |
| December | 0.108704E+09 | 23553783.07 | 85150677.71 | 28004199.69 | 0.427817E+09 |
| Annual Sum or Average | 0.349145E+10 | 0.141593E+10 | 0.207552E+10 | 0.351017E+10 | 0.268481E+10 |
| Minimum of Months | 0.108704E+09 | 23553783.07 | 85150677.71 | 28004199.69 | 59186785.30 |
| Maximum of Months | 0.498417E+09 | 0.234488E+09 | 0.263929E+09 | 0.609062E+09 | 0.449057E+09 |
Report: WindowEnergyReportMonthly
For: TWINDOW1 W NWA
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.116536E+09 | 27445700.15 | 89090096.08 | 31812788.80 | 0.444658E+09 |
| February | 0.170553E+09 | 44016659.46 | 0.126537E+09 | 72100814.43 | 0.375772E+09 |
| March | 0.296845E+09 | 0.127608E+09 | 0.169238E+09 | 0.241480E+09 | 0.283669E+09 |
| April | 0.349452E+09 | 0.143028E+09 | 0.206424E+09 | 0.335592E+09 | 0.194442E+09 |
| May | 0.426295E+09 | 0.192492E+09 | 0.233803E+09 | 0.472643E+09 | 0.133048E+09 |
| June | 0.498417E+09 | 0.234488E+09 | 0.263929E+09 | 0.610958E+09 | 85272433.98 |
| July | 0.459915E+09 | 0.201360E+09 | 0.258555E+09 | 0.600775E+09 | 59113794.65 |
| August | 0.415514E+09 | 0.176222E+09 | 0.239292E+09 | 0.533767E+09 | 77894056.16 |
| September | 0.316621E+09 | 0.136805E+09 | 0.179815E+09 | 0.369382E+09 | 0.117952E+09 |
| October | 0.212008E+09 | 74680744.99 | 0.137328E+09 | 0.193540E+09 | 0.194824E+09 |
| November | 0.120589E+09 | 34234006.48 | 86355470.88 | 74207946.63 | 0.257224E+09 |
| December | 0.108704E+09 | 23553783.07 | 85150677.71 | 29859870.63 | 0.424652E+09 |
| Annual Sum or Average | 0.349145E+10 | 0.141593E+10 | 0.207552E+10 | 0.356612E+10 | 0.264852E+10 |
| Minimum of Months | 0.108704E+09 | 23553783.07 | 85150677.71 | 29859870.63 | 59113794.65 |
| Maximum of Months | 0.498417E+09 | 0.234488E+09 | 0.263929E+09 | 0.610958E+09 | 0.444658E+09 |
Report: WindowEnergyReportMonthly
For: TWINDOW1 N NWA
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.112596E+09 | 0.00 | 0.112596E+09 | 208116.76 | 0.714840E+09 |
| February | 0.154952E+09 | 0.00 | 0.154952E+09 | 7122136.96 | 0.601475E+09 |
| March | 0.208080E+09 | 7369.23 | 0.208072E+09 | 69026964.36 | 0.464658E+09 |
| April | 0.256713E+09 | 1237747.44 | 0.255475E+09 | 0.144957E+09 | 0.303543E+09 |
| May | 0.308157E+09 | 13268987.07 | 0.294888E+09 | 0.250150E+09 | 0.193505E+09 |
| June | 0.358543E+09 | 30487239.06 | 0.328056E+09 | 0.383948E+09 | 0.122306E+09 |
| July | 0.345055E+09 | 23472851.36 | 0.321583E+09 | 0.426676E+09 | 84855971.05 |
| August | 0.298739E+09 | 5766984.46 | 0.292972E+09 | 0.347708E+09 | 0.115489E+09 |
| September | 0.219114E+09 | 96969.17 | 0.219018E+09 | 0.201664E+09 | 0.183145E+09 |
| October | 0.169177E+09 | 0.00 | 0.169177E+09 | 91045982.34 | 0.305236E+09 |
| November | 0.110016E+09 | 0.00 | 0.110016E+09 | 24904521.71 | 0.401759E+09 |
| December | 0.105386E+09 | 0.00 | 0.105386E+09 | 1383935.69 | 0.675951E+09 |
| Annual Sum or Average | 0.264653E+10 | 74338147.80 | 0.257219E+10 | 0.194880E+10 | 0.416676E+10 |
| Minimum of Months | 0.105386E+09 | 0.00 | 0.105386E+09 | 208116.76 | 84855971.05 |
| Maximum of Months | 0.358543E+09 | 30487239.06 | 0.328056E+09 | 0.426676E+09 | 0.714840E+09 |
Report: WindowEnergyReportMonthly
For: TWINDOW1 S SEA
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.482833E+09 | 0.281306E+09 | 0.201526E+09 | 0.387476E+09 | 0.607896E+09 |
| February | 0.498407E+09 | 0.239946E+09 | 0.258461E+09 | 0.392551E+09 | 0.536748E+09 |
| March | 0.664013E+09 | 0.368403E+09 | 0.295610E+09 | 0.650923E+09 | 0.422218E+09 |
| April | 0.546431E+09 | 0.221740E+09 | 0.324691E+09 | 0.559948E+09 | 0.310883E+09 |
| May | 0.488630E+09 | 0.141655E+09 | 0.346974E+09 | 0.539889E+09 | 0.211500E+09 |
| June | 0.461133E+09 | 98760793.79 | 0.362372E+09 | 0.563491E+09 | 0.132167E+09 |
| July | 0.483493E+09 | 0.116133E+09 | 0.367360E+09 | 0.655140E+09 | 90412663.61 |
| August | 0.539686E+09 | 0.171693E+09 | 0.367993E+09 | 0.718928E+09 | 0.120290E+09 |
| September | 0.620130E+09 | 0.305851E+09 | 0.314279E+09 | 0.768471E+09 | 0.185790E+09 |
| October | 0.607366E+09 | 0.347628E+09 | 0.259738E+09 | 0.660589E+09 | 0.296053E+09 |
| November | 0.421012E+09 | 0.238333E+09 | 0.182679E+09 | 0.402409E+09 | 0.377895E+09 |
| December | 0.404762E+09 | 0.209518E+09 | 0.195244E+09 | 0.307384E+09 | 0.593175E+09 |
| Annual Sum or Average | 0.621789E+10 | 0.274097E+10 | 0.347693E+10 | 0.660720E+10 | 0.388503E+10 |
| Minimum of Months | 0.404762E+09 | 98760793.79 | 0.182679E+09 | 0.307384E+09 | 90412663.61 |
| Maximum of Months | 0.664013E+09 | 0.368403E+09 | 0.367993E+09 | 0.768471E+09 | 0.607896E+09 |
Report: WindowEnergyReportMonthly
For: TWINDOW1 E SEA
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.135890E+09 | 44115383.46 | 91774696.76 | 50394697.38 | 0.431812E+09 |
| February | 0.179236E+09 | 53538670.03 | 0.125697E+09 | 81010842.46 | 0.366794E+09 |
| March | 0.285846E+09 | 0.119504E+09 | 0.166342E+09 | 0.221399E+09 | 0.282817E+09 |
| April | 0.365368E+09 | 0.161509E+09 | 0.203860E+09 | 0.345624E+09 | 0.191415E+09 |
| May | 0.422918E+09 | 0.186952E+09 | 0.235966E+09 | 0.461554E+09 | 0.129713E+09 |
| June | 0.457507E+09 | 0.202221E+09 | 0.255286E+09 | 0.553431E+09 | 80895613.24 |
| July | 0.453399E+09 | 0.199308E+09 | 0.254091E+09 | 0.588600E+09 | 55469410.75 |
| August | 0.409339E+09 | 0.171330E+09 | 0.238009E+09 | 0.517486E+09 | 75248303.91 |
| September | 0.328838E+09 | 0.145303E+09 | 0.183535E+09 | 0.376848E+09 | 0.118513E+09 |
| October | 0.230869E+09 | 95139569.63 | 0.135729E+09 | 0.207015E+09 | 0.196213E+09 |
| November | 0.126873E+09 | 40598305.06 | 86275191.41 | 77445999.53 | 0.257343E+09 |
| December | 0.105661E+09 | 21871167.95 | 83789688.80 | 25627463.49 | 0.421688E+09 |
| Annual Sum or Average | 0.350174E+10 | 0.144139E+10 | 0.206035E+10 | 0.350644E+10 | 0.260792E+10 |
| Minimum of Months | 0.105661E+09 | 21871167.95 | 83789688.80 | 25627463.49 | 55469410.75 |
| Maximum of Months | 0.457507E+09 | 0.202221E+09 | 0.255286E+09 | 0.588600E+09 | 0.431812E+09 |
Report: WindowEnergyReportMonthly
For: TWINDOW1 E NEA
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.135890E+09 | 44115383.46 | 91774696.76 | 51658122.00 | 0.426746E+09 |
| February | 0.179236E+09 | 53538670.03 | 0.125697E+09 | 82969261.84 | 0.363040E+09 |
| March | 0.285846E+09 | 0.119504E+09 | 0.166342E+09 | 0.226289E+09 | 0.276754E+09 |
| April | 0.365368E+09 | 0.161509E+09 | 0.203860E+09 | 0.352512E+09 | 0.187233E+09 |
| May | 0.422918E+09 | 0.186952E+09 | 0.235966E+09 | 0.465783E+09 | 0.127795E+09 |
| June | 0.457507E+09 | 0.202221E+09 | 0.255286E+09 | 0.555105E+09 | 80866444.10 |
| July | 0.453399E+09 | 0.199308E+09 | 0.254091E+09 | 0.590516E+09 | 55301124.90 |
| August | 0.409339E+09 | 0.171330E+09 | 0.238009E+09 | 0.520848E+09 | 74353032.31 |
| September | 0.328838E+09 | 0.145303E+09 | 0.183535E+09 | 0.383548E+09 | 0.114702E+09 |
| October | 0.230869E+09 | 95139569.63 | 0.135729E+09 | 0.216075E+09 | 0.187902E+09 |
| November | 0.126873E+09 | 40598305.06 | 86275191.41 | 81002649.97 | 0.251523E+09 |
| December | 0.105661E+09 | 21871167.95 | 83789688.80 | 26399595.86 | 0.417527E+09 |
| Annual Sum or Average | 0.350174E+10 | 0.144139E+10 | 0.206035E+10 | 0.355271E+10 | 0.256374E+10 |
| Minimum of Months | 0.105661E+09 | 21871167.95 | 83789688.80 | 26399595.86 | 55301124.90 |
| Maximum of Months | 0.457507E+09 | 0.202221E+09 | 0.255286E+09 | 0.590516E+09 | 0.426746E+09 |
Report: WindowEnergyReportMonthly
For: TWINDOW1 N NEA
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.112596E+09 | 0.00 | 0.112596E+09 | 190787.71 | 0.715481E+09 |
| February | 0.154952E+09 | 0.00 | 0.154952E+09 | 6891709.47 | 0.601724E+09 |
| March | 0.208080E+09 | 7369.23 | 0.208072E+09 | 67772215.36 | 0.463586E+09 |
| April | 0.256713E+09 | 1237747.44 | 0.255475E+09 | 0.141063E+09 | 0.301487E+09 |
| May | 0.308157E+09 | 13268987.07 | 0.294888E+09 | 0.244530E+09 | 0.191459E+09 |
| June | 0.358543E+09 | 30487239.06 | 0.328056E+09 | 0.380846E+09 | 0.120393E+09 |
| July | 0.345055E+09 | 23472851.36 | 0.321583E+09 | 0.424591E+09 | 83531390.91 |
| August | 0.298739E+09 | 5766984.46 | 0.292972E+09 | 0.345723E+09 | 0.114095E+09 |
| September | 0.219114E+09 | 96969.17 | 0.219018E+09 | 0.197070E+09 | 0.181835E+09 |
| October | 0.169177E+09 | 0.00 | 0.169177E+09 | 88928255.04 | 0.304062E+09 |
| November | 0.110016E+09 | 0.00 | 0.110016E+09 | 24365276.85 | 0.401602E+09 |
| December | 0.105386E+09 | 0.00 | 0.105386E+09 | 1359074.07 | 0.676048E+09 |
| Annual Sum or Average | 0.264653E+10 | 74338147.80 | 0.257219E+10 | 0.192333E+10 | 0.415530E+10 |
| Minimum of Months | 0.105386E+09 | 0.00 | 0.105386E+09 | 190787.71 | 83531390.91 |
| Maximum of Months | 0.358543E+09 | 30487239.06 | 0.328056E+09 | 0.424591E+09 | 0.715481E+09 |
Report: WindowEnergyReportMonthly
For: TWINDOW1 N N1A
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.112596E+09 | 0.00 | 0.112596E+09 | 137215.53 | 0.727329E+09 |
| February | 0.154952E+09 | 0.00 | 0.154952E+09 | 6582539.74 | 0.611500E+09 |
| March | 0.208080E+09 | 7369.23 | 0.208072E+09 | 68082871.74 | 0.470823E+09 |
| April | 0.256713E+09 | 1237747.44 | 0.255475E+09 | 0.145460E+09 | 0.306296E+09 |
| May | 0.308157E+09 | 13268987.07 | 0.294888E+09 | 0.251033E+09 | 0.197592E+09 |
| June | 0.358543E+09 | 30487239.06 | 0.328056E+09 | 0.387231E+09 | 0.123170E+09 |
| July | 0.345055E+09 | 23472851.36 | 0.321583E+09 | 0.431398E+09 | 84369292.87 |
| August | 0.298739E+09 | 5766984.46 | 0.292972E+09 | 0.351243E+09 | 0.116259E+09 |
| September | 0.219114E+09 | 96969.17 | 0.219018E+09 | 0.201841E+09 | 0.187677E+09 |
| October | 0.169177E+09 | 0.00 | 0.169177E+09 | 90212003.34 | 0.310939E+09 |
| November | 0.110016E+09 | 0.00 | 0.110016E+09 | 24219994.38 | 0.409518E+09 |
| December | 0.105386E+09 | 0.00 | 0.105386E+09 | 1269748.40 | 0.688001E+09 |
| Annual Sum or Average | 0.264653E+10 | 74338147.80 | 0.257219E+10 | 0.195871E+10 | 0.423347E+10 |
| Minimum of Months | 0.105386E+09 | 0.00 | 0.105386E+09 | 137215.53 | 84369292.87 |
| Maximum of Months | 0.358543E+09 | 30487239.06 | 0.328056E+09 | 0.431398E+09 | 0.727329E+09 |
Report: WindowEnergyReportMonthly
For: TWINDOW1 N N2A
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.112596E+09 | 0.00 | 0.112596E+09 | 136536.72 | 0.727356E+09 |
| February | 0.154952E+09 | 0.00 | 0.154952E+09 | 6570549.10 | 0.611506E+09 |
| March | 0.208080E+09 | 7369.23 | 0.208072E+09 | 67999214.26 | 0.470771E+09 |
| April | 0.256713E+09 | 1237747.44 | 0.255475E+09 | 0.145089E+09 | 0.306211E+09 |
| May | 0.308157E+09 | 13268987.07 | 0.294888E+09 | 0.250488E+09 | 0.197488E+09 |
| June | 0.358543E+09 | 30487239.06 | 0.328056E+09 | 0.386976E+09 | 0.123049E+09 |
| July | 0.345055E+09 | 23472851.36 | 0.321583E+09 | 0.431293E+09 | 84292396.55 |
| August | 0.298739E+09 | 5766984.46 | 0.292972E+09 | 0.351128E+09 | 0.116170E+09 |
| September | 0.219114E+09 | 96969.17 | 0.219018E+09 | 0.201455E+09 | 0.187649E+09 |
| October | 0.169177E+09 | 0.00 | 0.169177E+09 | 90028606.75 | 0.310879E+09 |
| November | 0.110016E+09 | 0.00 | 0.110016E+09 | 24185761.83 | 0.409514E+09 |
| December | 0.105386E+09 | 0.00 | 0.105386E+09 | 1268683.09 | 0.688005E+09 |
| Annual Sum or Average | 0.264653E+10 | 74338147.80 | 0.257219E+10 | 0.195662E+10 | 0.423289E+10 |
| Minimum of Months | 0.105386E+09 | 0.00 | 0.105386E+09 | 136536.72 | 84292396.55 |
| Maximum of Months | 0.358543E+09 | 30487239.06 | 0.328056E+09 | 0.431293E+09 | 0.727356E+09 |
Report: WindowEnergyReportMonthly
For: TWINDOW1 S S1A
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.482833E+09 | 0.281306E+09 | 0.201526E+09 | 0.385331E+09 | 0.618747E+09 |
| February | 0.498407E+09 | 0.239946E+09 | 0.258461E+09 | 0.390534E+09 | 0.545993E+09 |
| March | 0.664013E+09 | 0.368403E+09 | 0.295610E+09 | 0.650240E+09 | 0.430730E+09 |
| April | 0.546431E+09 | 0.221740E+09 | 0.324691E+09 | 0.562830E+09 | 0.318040E+09 |
| May | 0.488630E+09 | 0.141655E+09 | 0.346974E+09 | 0.544561E+09 | 0.218967E+09 |
| June | 0.461133E+09 | 98760793.79 | 0.362372E+09 | 0.569601E+09 | 0.135229E+09 |
| July | 0.483493E+09 | 0.116133E+09 | 0.367360E+09 | 0.662001E+09 | 91328558.06 |
| August | 0.539686E+09 | 0.171693E+09 | 0.367993E+09 | 0.724145E+09 | 0.122498E+09 |
| September | 0.620130E+09 | 0.305851E+09 | 0.314279E+09 | 0.771292E+09 | 0.192300E+09 |
| October | 0.607366E+09 | 0.347628E+09 | 0.259738E+09 | 0.660396E+09 | 0.305200E+09 |
| November | 0.421012E+09 | 0.238333E+09 | 0.182679E+09 | 0.400674E+09 | 0.387277E+09 |
| December | 0.404762E+09 | 0.209518E+09 | 0.195244E+09 | 0.305308E+09 | 0.604225E+09 |
| Annual Sum or Average | 0.621789E+10 | 0.274097E+10 | 0.347693E+10 | 0.662691E+10 | 0.397054E+10 |
| Minimum of Months | 0.404762E+09 | 98760793.79 | 0.182679E+09 | 0.305308E+09 | 91328558.06 |
| Maximum of Months | 0.664013E+09 | 0.368403E+09 | 0.367993E+09 | 0.771292E+09 | 0.618747E+09 |
Report: WindowEnergyReportMonthly
For: TWINDOW1 S S2A
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.482833E+09 | 0.281306E+09 | 0.201526E+09 | 0.385289E+09 | 0.618742E+09 |
| February | 0.498407E+09 | 0.239946E+09 | 0.258461E+09 | 0.390480E+09 | 0.545967E+09 |
| March | 0.664013E+09 | 0.368403E+09 | 0.295610E+09 | 0.650079E+09 | 0.430617E+09 |
| April | 0.546431E+09 | 0.221740E+09 | 0.324691E+09 | 0.562509E+09 | 0.317896E+09 |
| May | 0.488630E+09 | 0.141655E+09 | 0.346974E+09 | 0.544186E+09 | 0.218779E+09 |
| June | 0.461133E+09 | 98760793.79 | 0.362372E+09 | 0.569387E+09 | 0.135059E+09 |
| July | 0.483493E+09 | 0.116133E+09 | 0.367360E+09 | 0.661875E+09 | 91242597.51 |
| August | 0.539686E+09 | 0.171693E+09 | 0.367993E+09 | 0.724031E+09 | 0.122406E+09 |
| September | 0.620130E+09 | 0.305851E+09 | 0.314279E+09 | 0.771095E+09 | 0.192221E+09 |
| October | 0.607366E+09 | 0.347628E+09 | 0.259738E+09 | 0.660169E+09 | 0.305186E+09 |
| November | 0.421012E+09 | 0.238333E+09 | 0.182679E+09 | 0.400598E+09 | 0.387252E+09 |
| December | 0.404762E+09 | 0.209518E+09 | 0.195244E+09 | 0.305283E+09 | 0.604211E+09 |
| Annual Sum or Average | 0.621789E+10 | 0.274097E+10 | 0.347693E+10 | 0.662498E+10 | 0.396958E+10 |
| Minimum of Months | 0.404762E+09 | 98760793.79 | 0.182679E+09 | 0.305283E+09 | 91242597.51 |
| Maximum of Months | 0.664013E+09 | 0.368403E+09 | 0.367993E+09 | 0.771095E+09 | 0.618742E+09 |
Report: WindowEnergyReportMonthly
For: TWINDOW14
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 32607377.88 | 10585665.83 | 22021712.05 | 12084995.06 | 0.104851E+09 |
| February | 43008306.31 | 12846821.80 | 30161484.51 | 19434719.46 | 89206105.60 |
| March | 68589906.46 | 28675506.35 | 39914400.11 | 52831088.74 | 70410034.84 |
| April | 87671579.98 | 38754634.11 | 48916945.87 | 82603122.26 | 49526231.12 |
| May | 0.101481E+09 | 44859895.33 | 56620984.02 | 0.109352E+09 | 35486913.28 |
| June | 0.109781E+09 | 48523725.46 | 61256964.76 | 0.129772E+09 | 23087784.81 |
| July | 0.108795E+09 | 47824768.75 | 60970274.18 | 0.137393E+09 | 16665179.20 |
| August | 98222508.48 | 41111387.15 | 57111121.33 | 0.121093E+09 | 21954079.61 |
| September | 78906023.05 | 34865991.41 | 44040031.64 | 89338191.69 | 32622057.46 |
| October | 55397912.72 | 22829126.99 | 32568785.73 | 49624645.26 | 50583468.78 |
| November | 30443811.91 | 9741728.55 | 20702083.35 | 18401089.50 | 64789760.51 |
| December | 25353752.66 | 5248075.77 | 20105676.88 | 6103084.01 | 0.102897E+09 |
| Annual Sum or Average | 0.840258E+09 | 0.345867E+09 | 0.494390E+09 | 0.828030E+09 | 0.662079E+09 |
| Minimum of Months | 25353752.66 | 5248075.77 | 20105676.88 | 6103084.01 | 16665179.20 |
| Maximum of Months | 0.109781E+09 | 48523725.46 | 61256964.76 | 0.137393E+09 | 0.104851E+09 |
Report: WindowEnergyReportMonthly
For: ENTRANCE DOOR
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 97112886.10 | 31526747.22 | 65586138.88 | 41385967.53 | 0.272644E+09 |
| February | 0.128089E+09 | 38261032.42 | 89828406.96 | 67961675.12 | 0.231278E+09 |
| March | 0.204278E+09 | 85402794.19 | 0.118875E+09 | 0.171940E+09 | 0.182289E+09 |
| April | 0.261108E+09 | 0.115421E+09 | 0.145687E+09 | 0.263215E+09 | 0.128311E+09 |
| May | 0.302235E+09 | 0.133604E+09 | 0.168631E+09 | 0.342806E+09 | 90211512.94 |
| June | 0.326954E+09 | 0.144516E+09 | 0.182438E+09 | 0.394139E+09 | 65767263.30 |
| July | 0.324019E+09 | 0.142434E+09 | 0.181585E+09 | 0.412767E+09 | 49986256.44 |
| August | 0.292531E+09 | 0.122440E+09 | 0.170091E+09 | 0.363019E+09 | 66501258.17 |
| September | 0.235002E+09 | 0.103840E+09 | 0.131162E+09 | 0.266687E+09 | 99679195.50 |
| October | 0.164989E+09 | 67990821.50 | 96997949.08 | 0.150916E+09 | 0.146813E+09 |
| November | 90669248.20 | 29013291.99 | 61655956.22 | 58766972.52 | 0.178770E+09 |
| December | 75509785.03 | 15630075.71 | 59879709.33 | 21782366.59 | 0.269787E+09 |
| Annual Sum or Average | 0.250250E+10 | 0.103008E+10 | 0.147242E+10 | 0.255538E+10 | 0.178204E+10 |
| Minimum of Months | 75509785.03 | 15630075.71 | 59879709.33 | 21782366.59 | 49986256.44 |
| Maximum of Months | 0.326954E+09 | 0.144516E+09 | 0.182438E+09 | 0.412767E+09 | 0.272644E+09 |
Report: WindowEnergyReportMonthly
For: MWINDOW14
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 32607377.88 | 10585665.83 | 22021712.05 | 11199527.39 | 0.113332E+09 |
| February | 43008306.31 | 12846821.80 | 30161484.51 | 18110291.62 | 96224693.40 |
| March | 68589906.46 | 28675506.35 | 39914400.11 | 50966902.21 | 76047381.84 |
| April | 87671579.98 | 38754634.11 | 48916945.87 | 80474850.90 | 53240603.01 |
| May | 0.101481E+09 | 44859895.33 | 56620984.02 | 0.106212E+09 | 39227481.66 |
| June | 0.109781E+09 | 48523725.46 | 61256964.76 | 0.128879E+09 | 24269781.07 |
| July | 0.108795E+09 | 47824768.75 | 60970274.18 | 0.137903E+09 | 16997934.79 |
| August | 98222508.48 | 41111387.15 | 57111121.33 | 0.121034E+09 | 22748601.04 |
| September | 78906023.05 | 34865991.41 | 44040031.64 | 87294799.61 | 35756606.94 |
| October | 55397912.72 | 22829126.99 | 32568785.73 | 47197215.02 | 56205486.28 |
| November | 30443811.91 | 9741728.55 | 20702083.35 | 17315437.39 | 70972878.16 |
| December | 25353752.66 | 5248075.77 | 20105676.88 | 5522620.38 | 0.111313E+09 |
| Annual Sum or Average | 0.840258E+09 | 0.345867E+09 | 0.494390E+09 | 0.812109E+09 | 0.716336E+09 |
| Minimum of Months | 25353752.66 | 5248075.77 | 20105676.88 | 5522620.38 | 16997934.79 |
| Maximum of Months | 0.109781E+09 | 48523725.46 | 61256964.76 | 0.137903E+09 | 0.113332E+09 |
Report: WindowZoneSummaryMonthly
For: G SW APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 147.88 | 380.38 | 223.78 | 115.27 | 108.50 | 0.00 | 0.00 |
| February | 189.55 | 366.63 | 276.52 | 117.38 | 159.14 | 0.00 | 0.00 |
| March | 336.13 | 252.31 | 358.74 | 185.19 | 173.55 | 0.00 | 0.00 |
| April | 357.78 | 184.18 | 345.63 | 140.73 | 204.91 | 0.00 | 0.00 |
| May | 397.10 | 116.77 | 341.59 | 124.76 | 216.84 | 0.00 | 0.00 |
| June | 464.27 | 83.39 | 370.20 | 128.57 | 241.63 | 0.00 | 0.00 |
| July | 479.17 | 56.46 | 352.23 | 118.54 | 233.69 | 0.00 | 0.00 |
| August | 474.19 | 77.23 | 356.63 | 129.90 | 226.73 | 0.00 | 0.00 |
| September | 438.33 | 128.90 | 361.40 | 170.78 | 190.62 | 0.00 | 0.00 |
| October | 316.01 | 193.82 | 305.92 | 157.67 | 148.25 | 0.00 | 0.00 |
| November | 182.33 | 248.28 | 208.95 | 105.16 | 103.79 | 0.00 | 0.00 |
| December | 120.29 | 373.05 | 191.71 | 87.02 | 104.69 | 0.00 | 0.00 |
| Annual Sum or Average | 325.98 | 204.27 | 307.88 | 131.81 | 176.07 | 0.00 | 0.00 |
| Minimum of Months | 120.29 | 56.46 | 191.71 | 87.02 | 103.79 | 0.00 | 0.00 |
| Maximum of Months | 479.17 | 380.38 | 370.20 | 185.19 | 241.63 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: G NW APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 5.90 | 422.04 | 85.55 | 10.25 | 75.30 | 0.00 | 0.00 |
| February | 27.23 | 390.83 | 134.55 | 18.19 | 116.36 | 0.00 | 0.00 |
| March | 113.87 | 261.95 | 188.52 | 47.65 | 140.87 | 0.00 | 0.00 |
| April | 196.72 | 179.80 | 233.86 | 55.66 | 178.20 | 0.00 | 0.00 |
| May | 291.26 | 107.53 | 274.21 | 76.82 | 197.39 | 0.00 | 0.00 |
| June | 394.05 | 76.94 | 330.62 | 102.23 | 228.39 | 0.00 | 0.00 |
| July | 391.97 | 52.34 | 300.54 | 83.94 | 216.60 | 0.00 | 0.00 |
| August | 334.45 | 73.63 | 266.67 | 67.95 | 198.72 | 0.00 | 0.00 |
| September | 218.92 | 125.54 | 206.69 | 52.82 | 153.87 | 0.00 | 0.00 |
| October | 104.61 | 190.59 | 142.32 | 27.88 | 114.44 | 0.00 | 0.00 |
| November | 36.16 | 254.17 | 88.97 | 13.21 | 75.76 | 0.00 | 0.00 |
| December | 6.23 | 403.75 | 79.93 | 8.79 | 71.14 | 0.00 | 0.00 |
| Annual Sum or Average | 177.63 | 210.70 | 194.63 | 47.26 | 147.38 | 0.00 | 0.00 |
| Minimum of Months | 5.90 | 52.34 | 79.93 | 8.79 | 71.14 | 0.00 | 0.00 |
| Maximum of Months | 394.05 | 422.04 | 330.62 | 102.23 | 228.39 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: OFFICE
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 170.41 | 320.90 | 231.00 | 121.50 | 109.51 | 0.00 | 0.00 |
| February | 211.30 | 311.71 | 280.11 | 121.31 | 158.80 | 0.00 | 0.00 |
| March | 344.08 | 221.79 | 354.64 | 182.16 | 172.47 | 0.00 | 0.00 |
| April | 369.27 | 167.04 | 351.77 | 147.86 | 203.92 | 0.00 | 0.00 |
| May | 386.22 | 119.94 | 340.33 | 122.69 | 217.64 | 0.00 | 0.00 |
| June | 429.20 | 92.25 | 354.41 | 116.12 | 238.29 | 0.00 | 0.00 |
| July | 452.90 | 72.87 | 349.80 | 117.77 | 232.02 | 0.00 | 0.00 |
| August | 451.23 | 96.46 | 354.33 | 128.07 | 226.26 | 0.00 | 0.00 |
| September | 433.89 | 144.56 | 366.11 | 174.06 | 192.06 | 0.00 | 0.00 |
| October | 322.94 | 199.08 | 312.96 | 165.31 | 147.65 | 0.00 | 0.00 |
| November | 189.99 | 232.57 | 211.38 | 107.61 | 103.76 | 0.00 | 0.00 |
| December | 129.04 | 320.16 | 190.57 | 86.39 | 104.18 | 0.00 | 0.00 |
| Annual Sum or Average | 324.79 | 190.98 | 308.21 | 132.62 | 175.59 | 0.00 | 0.00 |
| Minimum of Months | 129.04 | 72.87 | 190.57 | 86.39 | 103.76 | 0.00 | 0.00 |
| Maximum of Months | 452.90 | 320.90 | 366.11 | 182.16 | 238.29 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: G NE APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 8.11 | 410.91 | 92.77 | 16.47 | 76.30 | 0.00 | 0.00 |
| February | 27.85 | 382.56 | 138.14 | 22.13 | 116.01 | 0.00 | 0.00 |
| March | 105.78 | 257.43 | 184.41 | 44.62 | 139.79 | 0.00 | 0.00 |
| April | 199.98 | 174.17 | 240.00 | 62.79 | 177.21 | 0.00 | 0.00 |
| May | 287.99 | 104.76 | 272.95 | 74.75 | 198.20 | 0.00 | 0.00 |
| June | 372.70 | 75.24 | 314.83 | 89.78 | 225.05 | 0.00 | 0.00 |
| July | 388.29 | 51.48 | 298.11 | 83.18 | 214.93 | 0.00 | 0.00 |
| August | 329.18 | 71.82 | 264.37 | 66.12 | 198.25 | 0.00 | 0.00 |
| September | 221.62 | 121.68 | 211.40 | 56.10 | 155.31 | 0.00 | 0.00 |
| October | 109.65 | 185.54 | 149.36 | 35.52 | 113.84 | 0.00 | 0.00 |
| November | 37.21 | 250.72 | 91.39 | 15.66 | 75.73 | 0.00 | 0.00 |
| December | 4.71 | 401.32 | 78.80 | 8.17 | 70.63 | 0.00 | 0.00 |
| Annual Sum or Average | 175.26 | 206.43 | 194.96 | 48.06 | 146.90 | 0.00 | 0.00 |
| Minimum of Months | 4.71 | 51.48 | 78.80 | 8.17 | 70.63 | 0.00 | 0.00 |
| Maximum of Months | 388.29 | 410.91 | 314.83 | 89.78 | 225.05 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: G N1 APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 0.09 | 269.12 | 42.04 | 0.00 | 42.04 | 0.00 | 0.00 |
| February | 3.27 | 249.67 | 64.05 | 0.00 | 64.05 | 0.00 | 0.00 |
| March | 28.39 | 171.11 | 77.69 | 0.00 | 77.69 | 0.00 | 0.00 |
| April | 62.38 | 112.49 | 99.04 | 0.48 | 98.56 | 0.00 | 0.00 |
| May | 105.20 | 65.89 | 115.05 | 4.95 | 110.10 | 0.00 | 0.00 |
| June | 154.66 | 46.61 | 138.33 | 11.76 | 126.56 | 0.00 | 0.00 |
| July | 165.40 | 31.19 | 128.83 | 8.76 | 120.07 | 0.00 | 0.00 |
| August | 133.79 | 44.01 | 111.54 | 2.15 | 109.38 | 0.00 | 0.00 |
| September | 77.04 | 78.03 | 84.53 | 0.04 | 84.50 | 0.00 | 0.00 |
| October | 33.12 | 120.38 | 63.16 | 0.00 | 63.16 | 0.00 | 0.00 |
| November | 9.62 | 159.74 | 42.44 | 0.00 | 42.44 | 0.00 | 0.00 |
| December | 0.52 | 256.07 | 39.35 | 0.00 | 39.35 | 0.00 | 0.00 |
| Annual Sum or Average | 64.83 | 133.12 | 83.92 | 2.36 | 81.56 | 0.00 | 0.00 |
| Minimum of Months | 0.09 | 31.19 | 39.35 | 0.00 | 39.35 | 0.00 | 0.00 |
| Maximum of Months | 165.40 | 269.12 | 138.33 | 11.76 | 126.56 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: G N2 APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 0.09 | 269.13 | 42.04 | 0.00 | 42.04 | 0.00 | 0.00 |
| February | 3.27 | 249.67 | 64.05 | 0.00 | 64.05 | 0.00 | 0.00 |
| March | 28.38 | 171.11 | 77.69 | 0.00 | 77.69 | 0.00 | 0.00 |
| April | 62.35 | 112.49 | 99.04 | 0.48 | 98.56 | 0.00 | 0.00 |
| May | 105.17 | 65.88 | 115.05 | 4.95 | 110.10 | 0.00 | 0.00 |
| June | 154.66 | 46.58 | 138.33 | 11.76 | 126.56 | 0.00 | 0.00 |
| July | 165.39 | 31.18 | 128.83 | 8.76 | 120.07 | 0.00 | 0.00 |
| August | 133.78 | 44.00 | 111.54 | 2.15 | 109.38 | 0.00 | 0.00 |
| September | 77.01 | 78.04 | 84.53 | 0.04 | 84.50 | 0.00 | 0.00 |
| October | 33.09 | 120.41 | 63.16 | 0.00 | 63.16 | 0.00 | 0.00 |
| November | 9.61 | 159.74 | 42.44 | 0.00 | 42.44 | 0.00 | 0.00 |
| December | 0.52 | 256.07 | 39.35 | 0.00 | 39.35 | 0.00 | 0.00 |
| Annual Sum or Average | 64.82 | 133.12 | 83.92 | 2.36 | 81.56 | 0.00 | 0.00 |
| Minimum of Months | 0.09 | 31.18 | 39.35 | 0.00 | 39.35 | 0.00 | 0.00 |
| Maximum of Months | 165.39 | 269.13 | 138.33 | 11.76 | 126.56 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: G S1 APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 146.32 | 230.07 | 180.27 | 105.03 | 75.24 | 0.00 | 0.00 |
| February | 165.36 | 223.66 | 206.02 | 99.18 | 106.84 | 0.00 | 0.00 |
| March | 249.55 | 157.81 | 247.91 | 137.55 | 110.37 | 0.00 | 0.00 |
| April | 226.05 | 116.96 | 210.81 | 85.55 | 125.27 | 0.00 | 0.00 |
| May | 213.55 | 74.98 | 182.43 | 52.89 | 129.55 | 0.00 | 0.00 |
| June | 225.27 | 52.24 | 177.91 | 38.10 | 139.80 | 0.00 | 0.00 |
| July | 252.35 | 34.24 | 180.52 | 43.36 | 137.16 | 0.00 | 0.00 |
| August | 274.27 | 46.90 | 201.50 | 64.10 | 137.39 | 0.00 | 0.00 |
| September | 298.82 | 79.73 | 239.25 | 118.00 | 121.25 | 0.00 | 0.00 |
| October | 246.92 | 121.16 | 226.76 | 129.79 | 96.98 | 0.00 | 0.00 |
| November | 156.41 | 152.35 | 162.43 | 91.95 | 70.48 | 0.00 | 0.00 |
| December | 116.00 | 225.48 | 151.12 | 78.23 | 72.90 | 0.00 | 0.00 |
| Annual Sum or Average | 214.50 | 125.78 | 197.17 | 86.92 | 110.25 | 0.00 | 0.00 |
| Minimum of Months | 116.00 | 34.24 | 151.12 | 38.10 | 70.48 | 0.00 | 0.00 |
| Maximum of Months | 298.82 | 230.07 | 247.91 | 137.55 | 139.80 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: G S2 APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 146.67 | 228.74 | 180.27 | 105.03 | 75.24 | 0.00 | 0.00 |
| February | 165.78 | 222.51 | 206.02 | 99.18 | 106.84 | 0.00 | 0.00 |
| March | 249.92 | 157.02 | 247.91 | 137.55 | 110.37 | 0.00 | 0.00 |
| April | 226.24 | 116.53 | 210.81 | 85.55 | 125.27 | 0.00 | 0.00 |
| May | 212.99 | 75.49 | 182.43 | 52.89 | 129.55 | 0.00 | 0.00 |
| June | 224.74 | 52.69 | 177.91 | 38.10 | 139.80 | 0.00 | 0.00 |
| July | 251.75 | 34.70 | 180.52 | 43.36 | 137.16 | 0.00 | 0.00 |
| August | 273.76 | 47.42 | 201.50 | 64.10 | 137.39 | 0.00 | 0.00 |
| September | 298.48 | 80.20 | 239.25 | 118.00 | 121.25 | 0.00 | 0.00 |
| October | 246.61 | 121.65 | 226.76 | 129.79 | 96.98 | 0.00 | 0.00 |
| November | 156.55 | 151.88 | 162.43 | 91.95 | 70.48 | 0.00 | 0.00 |
| December | 116.29 | 224.28 | 151.12 | 78.23 | 72.90 | 0.00 | 0.00 |
| Annual Sum or Average | 214.41 | 125.58 | 197.17 | 86.92 | 110.25 | 0.00 | 0.00 |
| Minimum of Months | 116.29 | 34.70 | 151.12 | 38.10 | 70.48 | 0.00 | 0.00 |
| Maximum of Months | 298.48 | 228.74 | 247.91 | 137.55 | 139.80 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: M SW APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 143.18 | 395.11 | 223.78 | 115.27 | 108.50 | 0.00 | 0.00 |
| February | 182.31 | 381.88 | 276.52 | 117.38 | 159.14 | 0.00 | 0.00 |
| March | 323.88 | 268.89 | 358.74 | 185.19 | 173.55 | 0.00 | 0.00 |
| April | 340.35 | 204.98 | 345.63 | 140.73 | 204.91 | 0.00 | 0.00 |
| May | 372.14 | 143.84 | 341.59 | 124.76 | 216.84 | 0.00 | 0.00 |
| June | 455.08 | 89.76 | 370.20 | 128.57 | 241.63 | 0.00 | 0.00 |
| July | 474.76 | 58.43 | 352.23 | 118.54 | 233.69 | 0.00 | 0.00 |
| August | 471.24 | 78.48 | 356.63 | 129.90 | 226.73 | 0.00 | 0.00 |
| September | 435.29 | 130.72 | 361.40 | 170.78 | 190.62 | 0.00 | 0.00 |
| October | 311.05 | 199.86 | 305.92 | 157.67 | 148.25 | 0.00 | 0.00 |
| November | 178.42 | 256.45 | 208.95 | 105.16 | 103.79 | 0.00 | 0.00 |
| December | 116.70 | 385.47 | 191.71 | 87.02 | 104.69 | 0.00 | 0.00 |
| Annual Sum or Average | 317.75 | 215.30 | 307.88 | 131.81 | 176.07 | 0.00 | 0.00 |
| Minimum of Months | 116.70 | 58.43 | 191.71 | 87.02 | 103.79 | 0.00 | 0.00 |
| Maximum of Months | 474.76 | 395.11 | 370.20 | 185.19 | 241.63 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: M NW APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 5.11 | 439.76 | 85.55 | 10.25 | 75.30 | 0.00 | 0.00 |
| February | 24.26 | 408.49 | 134.55 | 18.19 | 116.36 | 0.00 | 0.00 |
| March | 104.90 | 279.75 | 188.52 | 47.65 | 140.87 | 0.00 | 0.00 |
| April | 183.01 | 197.22 | 233.86 | 55.66 | 178.20 | 0.00 | 0.00 |
| May | 263.64 | 135.13 | 274.21 | 76.82 | 197.39 | 0.00 | 0.00 |
| June | 383.50 | 83.74 | 330.62 | 102.23 | 228.39 | 0.00 | 0.00 |
| July | 387.56 | 54.41 | 300.54 | 83.94 | 216.60 | 0.00 | 0.00 |
| August | 331.61 | 75.38 | 266.67 | 67.95 | 198.72 | 0.00 | 0.00 |
| September | 215.74 | 129.01 | 206.69 | 52.82 | 153.87 | 0.00 | 0.00 |
| October | 101.09 | 197.50 | 142.32 | 27.88 | 114.44 | 0.00 | 0.00 |
| November | 34.29 | 262.41 | 88.97 | 13.21 | 75.76 | 0.00 | 0.00 |
| December | 5.53 | 418.17 | 79.93 | 8.79 | 71.14 | 0.00 | 0.00 |
| Annual Sum or Average | 170.85 | 222.50 | 194.63 | 47.26 | 147.38 | 0.00 | 0.00 |
| Minimum of Months | 5.11 | 54.41 | 79.93 | 8.79 | 71.14 | 0.00 | 0.00 |
| Maximum of Months | 387.56 | 439.76 | 330.62 | 102.23 | 228.39 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: M SE APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 154.14 | 392.37 | 231.00 | 121.50 | 109.51 | 0.00 | 0.00 |
| February | 188.77 | 378.95 | 280.11 | 121.31 | 158.80 | 0.00 | 0.00 |
| March | 319.37 | 267.38 | 354.64 | 182.16 | 172.47 | 0.00 | 0.00 |
| April | 344.14 | 200.23 | 351.77 | 147.86 | 203.92 | 0.00 | 0.00 |
| May | 366.66 | 138.62 | 340.33 | 122.69 | 217.64 | 0.00 | 0.00 |
| June | 430.73 | 85.07 | 354.41 | 116.12 | 238.29 | 0.00 | 0.00 |
| July | 468.33 | 54.56 | 349.80 | 117.77 | 232.02 | 0.00 | 0.00 |
| August | 464.19 | 74.88 | 354.33 | 128.07 | 226.26 | 0.00 | 0.00 |
| September | 439.39 | 127.54 | 366.11 | 174.06 | 192.06 | 0.00 | 0.00 |
| October | 319.29 | 198.24 | 312.96 | 165.31 | 147.65 | 0.00 | 0.00 |
| November | 181.62 | 255.08 | 211.38 | 107.61 | 103.76 | 0.00 | 0.00 |
| December | 115.74 | 383.30 | 190.57 | 86.39 | 104.18 | 0.00 | 0.00 |
| Annual Sum or Average | 316.72 | 212.16 | 308.21 | 132.62 | 175.59 | 0.00 | 0.00 |
| Minimum of Months | 115.74 | 54.56 | 190.57 | 86.39 | 103.76 | 0.00 | 0.00 |
| Maximum of Months | 468.33 | 392.37 | 366.11 | 182.16 | 238.29 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: M NE APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 6.87 | 427.80 | 92.77 | 16.47 | 76.30 | 0.00 | 0.00 |
| February | 24.72 | 399.61 | 138.14 | 22.13 | 116.01 | 0.00 | 0.00 |
| March | 97.10 | 275.26 | 184.41 | 44.62 | 139.79 | 0.00 | 0.00 |
| April | 185.47 | 191.43 | 240.00 | 62.79 | 177.21 | 0.00 | 0.00 |
| May | 259.29 | 131.48 | 272.95 | 74.75 | 198.20 | 0.00 | 0.00 |
| June | 362.13 | 82.08 | 314.83 | 89.78 | 225.05 | 0.00 | 0.00 |
| July | 384.03 | 53.46 | 298.11 | 83.18 | 214.93 | 0.00 | 0.00 |
| August | 326.29 | 73.52 | 264.37 | 66.12 | 198.25 | 0.00 | 0.00 |
| September | 218.48 | 124.82 | 211.40 | 56.10 | 155.31 | 0.00 | 0.00 |
| October | 105.93 | 192.13 | 149.36 | 35.52 | 113.84 | 0.00 | 0.00 |
| November | 35.25 | 258.77 | 91.39 | 15.66 | 75.73 | 0.00 | 0.00 |
| December | 4.08 | 415.52 | 78.80 | 8.17 | 70.63 | 0.00 | 0.00 |
| Annual Sum or Average | 168.28 | 217.94 | 194.96 | 48.06 | 146.90 | 0.00 | 0.00 |
| Minimum of Months | 4.08 | 53.46 | 78.80 | 8.17 | 70.63 | 0.00 | 0.00 |
| Maximum of Months | 384.03 | 427.80 | 314.83 | 89.78 | 225.05 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: M N1 APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 0.02 | 279.46 | 42.04 | 0.00 | 42.04 | 0.00 | 0.00 |
| February | 2.46 | 260.14 | 64.05 | 0.00 | 64.05 | 0.00 | 0.00 |
| March | 24.84 | 182.24 | 77.69 | 0.00 | 77.69 | 0.00 | 0.00 |
| April | 55.64 | 123.35 | 99.04 | 0.48 | 98.56 | 0.00 | 0.00 |
| May | 89.72 | 81.71 | 115.05 | 4.95 | 110.10 | 0.00 | 0.00 |
| June | 149.80 | 49.80 | 138.33 | 11.76 | 126.56 | 0.00 | 0.00 |
| July | 163.67 | 32.06 | 128.83 | 8.76 | 120.07 | 0.00 | 0.00 |
| August | 132.69 | 44.81 | 111.54 | 2.15 | 109.38 | 0.00 | 0.00 |
| September | 75.67 | 79.94 | 84.53 | 0.04 | 84.50 | 0.00 | 0.00 |
| October | 31.20 | 125.50 | 63.16 | 0.00 | 63.16 | 0.00 | 0.00 |
| November | 8.79 | 165.05 | 42.44 | 0.00 | 42.44 | 0.00 | 0.00 |
| December | 0.42 | 264.71 | 39.35 | 0.00 | 39.35 | 0.00 | 0.00 |
| Annual Sum or Average | 61.60 | 140.14 | 83.92 | 2.36 | 81.56 | 0.00 | 0.00 |
| Minimum of Months | 0.02 | 32.06 | 39.35 | 0.00 | 39.35 | 0.00 | 0.00 |
| Maximum of Months | 163.67 | 279.46 | 138.33 | 11.76 | 126.56 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: M N2 APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 0.02 | 279.47 | 42.04 | 0.00 | 42.04 | 0.00 | 0.00 |
| February | 2.46 | 260.14 | 64.05 | 0.00 | 64.05 | 0.00 | 0.00 |
| March | 24.83 | 182.23 | 77.69 | 0.00 | 77.69 | 0.00 | 0.00 |
| April | 55.56 | 123.40 | 99.04 | 0.48 | 98.56 | 0.00 | 0.00 |
| May | 89.66 | 81.71 | 115.05 | 4.95 | 110.10 | 0.00 | 0.00 |
| June | 149.79 | 49.79 | 138.33 | 11.76 | 126.56 | 0.00 | 0.00 |
| July | 163.66 | 32.05 | 128.83 | 8.76 | 120.07 | 0.00 | 0.00 |
| August | 132.68 | 44.80 | 111.54 | 2.15 | 109.38 | 0.00 | 0.00 |
| September | 75.65 | 79.93 | 84.53 | 0.04 | 84.50 | 0.00 | 0.00 |
| October | 31.16 | 125.54 | 63.16 | 0.00 | 63.16 | 0.00 | 0.00 |
| November | 8.79 | 165.06 | 42.44 | 0.00 | 42.44 | 0.00 | 0.00 |
| December | 0.42 | 264.71 | 39.35 | 0.00 | 39.35 | 0.00 | 0.00 |
| Annual Sum or Average | 61.58 | 140.15 | 83.92 | 2.36 | 81.56 | 0.00 | 0.00 |
| Minimum of Months | 0.02 | 32.05 | 39.35 | 0.00 | 39.35 | 0.00 | 0.00 |
| Maximum of Months | 163.66 | 279.47 | 138.33 | 11.76 | 126.56 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: M S1 APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 143.22 | 238.38 | 180.27 | 105.03 | 75.24 | 0.00 | 0.00 |
| February | 160.92 | 232.38 | 206.02 | 99.18 | 106.84 | 0.00 | 0.00 |
| March | 242.80 | 167.38 | 247.91 | 137.55 | 110.37 | 0.00 | 0.00 |
| April | 216.46 | 130.55 | 210.81 | 85.55 | 125.27 | 0.00 | 0.00 |
| May | 201.00 | 90.82 | 182.43 | 52.89 | 129.55 | 0.00 | 0.00 |
| June | 221.35 | 55.19 | 177.91 | 38.10 | 139.80 | 0.00 | 0.00 |
| July | 250.49 | 35.03 | 180.52 | 43.36 | 137.16 | 0.00 | 0.00 |
| August | 272.93 | 47.38 | 201.50 | 64.10 | 137.39 | 0.00 | 0.00 |
| September | 297.28 | 80.57 | 239.25 | 118.00 | 121.25 | 0.00 | 0.00 |
| October | 243.73 | 125.26 | 226.76 | 129.79 | 96.98 | 0.00 | 0.00 |
| November | 153.64 | 157.99 | 162.43 | 91.95 | 70.48 | 0.00 | 0.00 |
| December | 113.55 | 232.81 | 151.12 | 78.23 | 72.90 | 0.00 | 0.00 |
| Annual Sum or Average | 210.05 | 132.29 | 197.17 | 86.92 | 110.25 | 0.00 | 0.00 |
| Minimum of Months | 113.55 | 35.03 | 151.12 | 38.10 | 70.48 | 0.00 | 0.00 |
| Maximum of Months | 297.28 | 238.38 | 247.91 | 137.55 | 139.80 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: M S2 APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 143.21 | 238.38 | 180.27 | 105.03 | 75.24 | 0.00 | 0.00 |
| February | 160.91 | 232.38 | 206.02 | 99.18 | 106.84 | 0.00 | 0.00 |
| March | 242.78 | 167.36 | 247.91 | 137.55 | 110.37 | 0.00 | 0.00 |
| April | 216.39 | 130.56 | 210.81 | 85.55 | 125.27 | 0.00 | 0.00 |
| May | 200.97 | 90.80 | 182.43 | 52.89 | 129.55 | 0.00 | 0.00 |
| June | 221.34 | 55.17 | 177.91 | 38.10 | 139.80 | 0.00 | 0.00 |
| July | 250.48 | 35.02 | 180.52 | 43.36 | 137.16 | 0.00 | 0.00 |
| August | 272.92 | 47.37 | 201.50 | 64.10 | 137.39 | 0.00 | 0.00 |
| September | 297.27 | 80.56 | 239.25 | 118.00 | 121.25 | 0.00 | 0.00 |
| October | 243.68 | 125.30 | 226.76 | 129.79 | 96.98 | 0.00 | 0.00 |
| November | 153.63 | 158.01 | 162.43 | 91.95 | 70.48 | 0.00 | 0.00 |
| December | 113.54 | 232.81 | 151.12 | 78.23 | 72.90 | 0.00 | 0.00 |
| Annual Sum or Average | 210.03 | 132.28 | 197.17 | 86.92 | 110.25 | 0.00 | 0.00 |
| Minimum of Months | 113.54 | 35.02 | 151.12 | 38.10 | 70.48 | 0.00 | 0.00 |
| Maximum of Months | 297.27 | 238.38 | 247.91 | 137.55 | 139.80 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: T SW APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 144.02 | 382.55 | 223.78 | 115.27 | 108.50 | 0.00 | 0.00 |
| February | 182.97 | 370.31 | 276.52 | 117.38 | 159.14 | 0.00 | 0.00 |
| March | 323.32 | 257.85 | 358.74 | 185.19 | 173.55 | 0.00 | 0.00 |
| April | 339.80 | 192.90 | 345.63 | 140.73 | 204.91 | 0.00 | 0.00 |
| May | 375.54 | 127.77 | 341.59 | 124.76 | 216.84 | 0.00 | 0.00 |
| June | 452.09 | 83.32 | 370.20 | 128.57 | 241.63 | 0.00 | 0.00 |
| July | 468.60 | 55.94 | 352.23 | 118.54 | 233.69 | 0.00 | 0.00 |
| August | 466.70 | 74.37 | 356.63 | 129.90 | 226.73 | 0.00 | 0.00 |
| September | 436.00 | 117.87 | 361.40 | 170.78 | 190.62 | 0.00 | 0.00 |
| October | 313.92 | 183.83 | 305.92 | 157.67 | 148.25 | 0.00 | 0.00 |
| November | 179.15 | 243.77 | 208.95 | 105.16 | 103.79 | 0.00 | 0.00 |
| December | 117.22 | 373.14 | 191.71 | 87.02 | 104.69 | 0.00 | 0.00 |
| Annual Sum or Average | 317.32 | 204.45 | 307.88 | 131.81 | 176.07 | 0.00 | 0.00 |
| Minimum of Months | 117.22 | 55.94 | 191.71 | 87.02 | 103.79 | 0.00 | 0.00 |
| Maximum of Months | 468.60 | 382.55 | 370.20 | 185.19 | 241.63 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: T NW APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 5.36 | 426.32 | 85.55 | 10.25 | 75.30 | 0.00 | 0.00 |
| February | 24.89 | 396.10 | 134.55 | 18.19 | 116.36 | 0.00 | 0.00 |
| March | 105.66 | 269.12 | 188.52 | 47.65 | 140.87 | 0.00 | 0.00 |
| April | 182.12 | 188.85 | 233.86 | 55.66 | 178.20 | 0.00 | 0.00 |
| May | 268.82 | 120.88 | 274.21 | 76.82 | 197.39 | 0.00 | 0.00 |
| June | 382.32 | 78.56 | 330.62 | 102.23 | 228.39 | 0.00 | 0.00 |
| July | 382.53 | 52.68 | 300.54 | 83.94 | 216.60 | 0.00 | 0.00 |
| August | 328.57 | 71.66 | 266.67 | 67.95 | 198.72 | 0.00 | 0.00 |
| September | 219.19 | 115.04 | 206.69 | 52.82 | 153.87 | 0.00 | 0.00 |
| October | 103.94 | 184.39 | 142.32 | 27.88 | 114.44 | 0.00 | 0.00 |
| November | 35.17 | 251.17 | 88.97 | 13.21 | 75.76 | 0.00 | 0.00 |
| December | 5.79 | 405.04 | 79.93 | 8.79 | 71.14 | 0.00 | 0.00 |
| Annual Sum or Average | 171.18 | 212.42 | 194.63 | 47.26 | 147.38 | 0.00 | 0.00 |
| Minimum of Months | 5.36 | 52.68 | 79.93 | 8.79 | 71.14 | 0.00 | 0.00 |
| Maximum of Months | 382.53 | 426.32 | 330.62 | 102.23 | 228.39 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: T SE APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 154.97 | 379.67 | 231.00 | 121.50 | 109.51 | 0.00 | 0.00 |
| February | 189.58 | 367.31 | 280.11 | 121.31 | 158.80 | 0.00 | 0.00 |
| March | 318.95 | 256.49 | 354.64 | 182.16 | 172.47 | 0.00 | 0.00 |
| April | 344.23 | 188.64 | 351.77 | 147.86 | 203.92 | 0.00 | 0.00 |
| May | 370.20 | 123.70 | 340.33 | 122.69 | 217.64 | 0.00 | 0.00 |
| June | 428.09 | 79.38 | 354.41 | 116.12 | 238.29 | 0.00 | 0.00 |
| July | 462.37 | 52.48 | 349.80 | 117.77 | 232.02 | 0.00 | 0.00 |
| August | 459.79 | 71.17 | 354.33 | 128.07 | 226.26 | 0.00 | 0.00 |
| September | 439.98 | 115.52 | 366.11 | 174.06 | 192.06 | 0.00 | 0.00 |
| October | 322.16 | 182.02 | 312.96 | 165.31 | 147.65 | 0.00 | 0.00 |
| November | 182.32 | 242.26 | 211.38 | 107.61 | 103.76 | 0.00 | 0.00 |
| December | 116.38 | 370.95 | 190.57 | 86.39 | 104.18 | 0.00 | 0.00 |
| Annual Sum or Average | 316.43 | 201.62 | 308.21 | 132.62 | 175.59 | 0.00 | 0.00 |
| Minimum of Months | 116.38 | 52.48 | 190.57 | 86.39 | 103.76 | 0.00 | 0.00 |
| Maximum of Months | 462.37 | 379.67 | 366.11 | 182.16 | 238.29 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: T NE APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 7.49 | 414.59 | 92.77 | 16.47 | 76.30 | 0.00 | 0.00 |
| February | 25.83 | 387.48 | 138.14 | 22.13 | 116.01 | 0.00 | 0.00 |
| March | 98.37 | 264.99 | 184.41 | 44.62 | 139.79 | 0.00 | 0.00 |
| April | 185.25 | 183.37 | 240.00 | 62.79 | 177.21 | 0.00 | 0.00 |
| May | 263.74 | 117.73 | 272.95 | 74.75 | 198.20 | 0.00 | 0.00 |
| June | 360.24 | 76.80 | 314.83 | 89.78 | 225.05 | 0.00 | 0.00 |
| July | 378.76 | 51.60 | 298.11 | 83.18 | 214.93 | 0.00 | 0.00 |
| August | 323.08 | 69.90 | 264.37 | 66.12 | 198.25 | 0.00 | 0.00 |
| September | 221.66 | 112.06 | 211.40 | 56.10 | 155.31 | 0.00 | 0.00 |
| October | 109.40 | 179.21 | 149.36 | 35.52 | 113.84 | 0.00 | 0.00 |
| November | 36.37 | 247.70 | 91.39 | 15.66 | 75.73 | 0.00 | 0.00 |
| December | 4.44 | 402.37 | 78.80 | 8.17 | 70.63 | 0.00 | 0.00 |
| Annual Sum or Average | 168.69 | 208.11 | 194.96 | 48.06 | 146.90 | 0.00 | 0.00 |
| Minimum of Months | 4.44 | 51.60 | 78.80 | 8.17 | 70.63 | 0.00 | 0.00 |
| Maximum of Months | 378.76 | 414.59 | 314.83 | 89.78 | 225.05 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: T N1 APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 0.05 | 271.55 | 42.04 | 0.00 | 42.04 | 0.00 | 0.00 |
| February | 2.72 | 252.77 | 64.05 | 0.00 | 64.05 | 0.00 | 0.00 |
| March | 25.42 | 175.79 | 77.69 | 0.00 | 77.69 | 0.00 | 0.00 |
| April | 56.12 | 118.17 | 99.04 | 0.48 | 98.56 | 0.00 | 0.00 |
| May | 93.72 | 73.77 | 115.05 | 4.95 | 110.10 | 0.00 | 0.00 |
| June | 149.39 | 47.52 | 138.33 | 11.76 | 126.56 | 0.00 | 0.00 |
| July | 161.07 | 31.50 | 128.83 | 8.76 | 120.07 | 0.00 | 0.00 |
| August | 131.14 | 43.41 | 111.54 | 2.15 | 109.38 | 0.00 | 0.00 |
| September | 77.87 | 72.41 | 84.53 | 0.04 | 84.50 | 0.00 | 0.00 |
| October | 33.68 | 116.09 | 63.16 | 0.00 | 63.16 | 0.00 | 0.00 |
| November | 9.34 | 157.99 | 42.44 | 0.00 | 42.44 | 0.00 | 0.00 |
| December | 0.47 | 256.87 | 39.35 | 0.00 | 39.35 | 0.00 | 0.00 |
| Annual Sum or Average | 62.11 | 134.24 | 83.92 | 2.36 | 81.56 | 0.00 | 0.00 |
| Minimum of Months | 0.05 | 31.50 | 39.35 | 0.00 | 39.35 | 0.00 | 0.00 |
| Maximum of Months | 161.07 | 271.55 | 138.33 | 11.76 | 126.56 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: T N2 APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 0.05 | 271.56 | 42.04 | 0.00 | 42.04 | 0.00 | 0.00 |
| February | 2.72 | 252.77 | 64.05 | 0.00 | 64.05 | 0.00 | 0.00 |
| March | 25.39 | 175.77 | 77.69 | 0.00 | 77.69 | 0.00 | 0.00 |
| April | 55.98 | 118.14 | 99.04 | 0.48 | 98.56 | 0.00 | 0.00 |
| May | 93.52 | 73.73 | 115.05 | 4.95 | 110.10 | 0.00 | 0.00 |
| June | 149.30 | 47.47 | 138.33 | 11.76 | 126.56 | 0.00 | 0.00 |
| July | 161.03 | 31.47 | 128.83 | 8.76 | 120.07 | 0.00 | 0.00 |
| August | 131.10 | 43.37 | 111.54 | 2.15 | 109.38 | 0.00 | 0.00 |
| September | 77.72 | 72.40 | 84.53 | 0.04 | 84.50 | 0.00 | 0.00 |
| October | 33.61 | 116.07 | 63.16 | 0.00 | 63.16 | 0.00 | 0.00 |
| November | 9.33 | 157.99 | 42.44 | 0.00 | 42.44 | 0.00 | 0.00 |
| December | 0.47 | 256.87 | 39.35 | 0.00 | 39.35 | 0.00 | 0.00 |
| Annual Sum or Average | 62.04 | 134.22 | 83.92 | 2.36 | 81.56 | 0.00 | 0.00 |
| Minimum of Months | 0.05 | 31.47 | 39.35 | 0.00 | 39.35 | 0.00 | 0.00 |
| Maximum of Months | 161.03 | 271.56 | 138.33 | 11.76 | 126.56 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: T S1 APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 143.87 | 231.01 | 180.27 | 105.03 | 75.24 | 0.00 | 0.00 |
| February | 161.43 | 225.69 | 206.02 | 99.18 | 106.84 | 0.00 | 0.00 |
| March | 242.77 | 160.82 | 247.91 | 137.55 | 110.37 | 0.00 | 0.00 |
| April | 217.14 | 122.70 | 210.81 | 85.55 | 125.27 | 0.00 | 0.00 |
| May | 203.32 | 81.75 | 182.43 | 52.89 | 129.55 | 0.00 | 0.00 |
| June | 219.75 | 52.17 | 177.91 | 38.10 | 139.80 | 0.00 | 0.00 |
| July | 247.16 | 34.10 | 180.52 | 43.36 | 137.16 | 0.00 | 0.00 |
| August | 270.36 | 45.74 | 201.50 | 64.10 | 137.39 | 0.00 | 0.00 |
| September | 297.57 | 74.19 | 239.25 | 118.00 | 121.25 | 0.00 | 0.00 |
| October | 246.56 | 113.95 | 226.76 | 129.79 | 96.98 | 0.00 | 0.00 |
| November | 154.58 | 149.41 | 162.43 | 91.95 | 70.48 | 0.00 | 0.00 |
| December | 113.99 | 225.59 | 151.12 | 78.23 | 72.90 | 0.00 | 0.00 |
| Annual Sum or Average | 210.14 | 125.90 | 197.17 | 86.92 | 110.25 | 0.00 | 0.00 |
| Minimum of Months | 113.99 | 34.10 | 151.12 | 38.10 | 70.48 | 0.00 | 0.00 |
| Maximum of Months | 297.57 | 231.01 | 247.91 | 137.55 | 139.80 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: T S2 APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 143.85 | 231.01 | 180.27 | 105.03 | 75.24 | 0.00 | 0.00 |
| February | 161.41 | 225.68 | 206.02 | 99.18 | 106.84 | 0.00 | 0.00 |
| March | 242.71 | 160.77 | 247.91 | 137.55 | 110.37 | 0.00 | 0.00 |
| April | 217.02 | 122.64 | 210.81 | 85.55 | 125.27 | 0.00 | 0.00 |
| May | 203.18 | 81.68 | 182.43 | 52.89 | 129.55 | 0.00 | 0.00 |
| June | 219.67 | 52.11 | 177.91 | 38.10 | 139.80 | 0.00 | 0.00 |
| July | 247.12 | 34.07 | 180.52 | 43.36 | 137.16 | 0.00 | 0.00 |
| August | 270.32 | 45.70 | 201.50 | 64.10 | 137.39 | 0.00 | 0.00 |
| September | 297.49 | 74.16 | 239.25 | 118.00 | 121.25 | 0.00 | 0.00 |
| October | 246.48 | 113.94 | 226.76 | 129.79 | 96.98 | 0.00 | 0.00 |
| November | 154.55 | 149.40 | 162.43 | 91.95 | 70.48 | 0.00 | 0.00 |
| December | 113.98 | 225.59 | 151.12 | 78.23 | 72.90 | 0.00 | 0.00 |
| Annual Sum or Average | 210.08 | 125.87 | 197.17 | 86.92 | 110.25 | 0.00 | 0.00 |
| Minimum of Months | 113.98 | 34.07 | 151.12 | 38.10 | 70.48 | 0.00 | 0.00 |
| Maximum of Months | 297.49 | 231.01 | 247.91 | 137.55 | 139.80 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: T CORRIDOR
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 4.51 | 39.15 | 12.17 | 3.95 | 8.22 | 0.00 | 0.00 |
| February | 8.03 | 36.87 | 17.78 | 5.31 | 12.47 | 0.00 | 0.00 |
| March | 19.72 | 26.29 | 25.61 | 10.71 | 14.90 | 0.00 | 0.00 |
| April | 31.87 | 19.11 | 33.82 | 14.95 | 18.87 | 0.00 | 0.00 |
| May | 40.83 | 13.25 | 37.89 | 16.75 | 21.14 | 0.00 | 0.00 |
| June | 50.07 | 8.91 | 42.35 | 18.72 | 23.63 | 0.00 | 0.00 |
| July | 51.30 | 6.22 | 40.62 | 17.86 | 22.76 | 0.00 | 0.00 |
| August | 45.21 | 8.20 | 36.67 | 15.35 | 21.32 | 0.00 | 0.00 |
| September | 34.47 | 12.59 | 30.44 | 13.45 | 16.99 | 0.00 | 0.00 |
| October | 18.53 | 18.89 | 20.68 | 8.52 | 12.16 | 0.00 | 0.00 |
| November | 7.10 | 25.00 | 11.75 | 3.76 | 7.99 | 0.00 | 0.00 |
| December | 2.28 | 38.42 | 9.47 | 1.96 | 7.51 | 0.00 | 0.00 |
| Annual Sum or Average | 26.26 | 20.99 | 26.64 | 10.97 | 15.68 | 0.00 | 0.00 |
| Minimum of Months | 2.28 | 6.22 | 9.47 | 1.96 | 7.51 | 0.00 | 0.00 |
| Maximum of Months | 51.30 | 39.15 | 42.35 | 18.72 | 23.63 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: G CORRIDOR
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 15.45 | 101.79 | 36.26 | 11.77 | 24.49 | 0.00 | 0.00 |
| February | 28.09 | 95.60 | 52.95 | 15.82 | 37.13 | 0.00 | 0.00 |
| March | 64.20 | 68.06 | 76.27 | 31.89 | 44.38 | 0.00 | 0.00 |
| April | 101.55 | 49.50 | 100.74 | 44.53 | 56.21 | 0.00 | 0.00 |
| May | 127.99 | 33.68 | 112.84 | 49.88 | 62.96 | 0.00 | 0.00 |
| June | 152.06 | 25.37 | 126.14 | 55.75 | 70.39 | 0.00 | 0.00 |
| July | 154.11 | 18.66 | 120.97 | 53.18 | 67.80 | 0.00 | 0.00 |
| August | 135.54 | 24.83 | 109.22 | 45.71 | 63.50 | 0.00 | 0.00 |
| September | 102.89 | 38.46 | 90.66 | 40.06 | 50.60 | 0.00 | 0.00 |
| October | 56.35 | 54.81 | 61.60 | 25.38 | 36.21 | 0.00 | 0.00 |
| November | 22.67 | 68.97 | 34.98 | 11.19 | 23.79 | 0.00 | 0.00 |
| December | 8.13 | 100.73 | 28.19 | 5.84 | 22.36 | 0.00 | 0.00 |
| Annual Sum or Average | 81.03 | 56.51 | 79.35 | 32.66 | 46.69 | 0.00 | 0.00 |
| Minimum of Months | 8.13 | 18.66 | 28.19 | 5.84 | 22.36 | 0.00 | 0.00 |
| Maximum of Months | 154.11 | 101.79 | 126.14 | 55.75 | 70.39 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: M CORRIDOR
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 4.18 | 42.31 | 12.17 | 3.95 | 8.22 | 0.00 | 0.00 |
| February | 7.49 | 39.78 | 17.78 | 5.31 | 12.47 | 0.00 | 0.00 |
| March | 19.03 | 28.39 | 25.61 | 10.71 | 14.90 | 0.00 | 0.00 |
| April | 31.05 | 20.54 | 33.82 | 14.95 | 18.87 | 0.00 | 0.00 |
| May | 39.66 | 14.65 | 37.89 | 16.75 | 21.14 | 0.00 | 0.00 |
| June | 49.72 | 9.36 | 42.35 | 18.72 | 23.63 | 0.00 | 0.00 |
| July | 51.49 | 6.35 | 40.62 | 17.86 | 22.76 | 0.00 | 0.00 |
| August | 45.19 | 8.49 | 36.67 | 15.35 | 21.32 | 0.00 | 0.00 |
| September | 33.68 | 13.79 | 30.44 | 13.45 | 16.99 | 0.00 | 0.00 |
| October | 17.62 | 20.98 | 20.68 | 8.52 | 12.16 | 0.00 | 0.00 |
| November | 6.68 | 27.38 | 11.75 | 3.76 | 7.99 | 0.00 | 0.00 |
| December | 2.06 | 41.56 | 9.47 | 1.96 | 7.51 | 0.00 | 0.00 |
| Annual Sum or Average | 25.75 | 22.71 | 26.64 | 10.97 | 15.68 | 0.00 | 0.00 |
| Minimum of Months | 2.06 | 6.35 | 9.47 | 1.96 | 7.51 | 0.00 | 0.00 |
| Maximum of Months | 51.49 | 42.31 | 42.35 | 18.72 | 23.63 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: G SW APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.396082E+09 | 0.101880E+10 | 0.599368E+09 | 0.308752E+09 | 0.290616E+09 | 0.00 | 0.00 |
| February | 0.458549E+09 | 0.886962E+09 | 0.668961E+09 | 0.283963E+09 | 0.384998E+09 | 0.00 | 0.00 |
| March | 0.900291E+09 | 0.675777E+09 | 0.960858E+09 | 0.496010E+09 | 0.464848E+09 | 0.00 | 0.00 |
| April | 0.927366E+09 | 0.477390E+09 | 0.895884E+09 | 0.364769E+09 | 0.531115E+09 | 0.00 | 0.00 |
| May | 0.106360E+10 | 0.312751E+09 | 0.914925E+09 | 0.334147E+09 | 0.580778E+09 | 0.00 | 0.00 |
| June | 0.120338E+10 | 0.216160E+09 | 0.959550E+09 | 0.333248E+09 | 0.626301E+09 | 0.00 | 0.00 |
| July | 0.128342E+10 | 0.151227E+09 | 0.943408E+09 | 0.317493E+09 | 0.625915E+09 | 0.00 | 0.00 |
| August | 0.127008E+10 | 0.206853E+09 | 0.955200E+09 | 0.347915E+09 | 0.607285E+09 | 0.00 | 0.00 |
| September | 0.113615E+10 | 0.334116E+09 | 0.936750E+09 | 0.442656E+09 | 0.494095E+09 | 0.00 | 0.00 |
| October | 0.846389E+09 | 0.519129E+09 | 0.819374E+09 | 0.422309E+09 | 0.397066E+09 | 0.00 | 0.00 |
| November | 0.472604E+09 | 0.643537E+09 | 0.541601E+09 | 0.272567E+09 | 0.269034E+09 | 0.00 | 0.00 |
| December | 0.322190E+09 | 0.999178E+09 | 0.513467E+09 | 0.233072E+09 | 0.280395E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.102801E+11 | 0.644188E+10 | 0.970935E+10 | 0.415690E+10 | 0.555245E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.322190E+09 | 0.151227E+09 | 0.513467E+09 | 0.233072E+09 | 0.269034E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.128342E+10 | 0.101880E+10 | 0.960858E+09 | 0.496010E+09 | 0.626301E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: G NW APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 15797332.09 | 0.113040E+10 | 0.229132E+09 | 27445700.15 | 0.201686E+09 | 0.00 | 0.00 |
| February | 65885749.67 | 0.945496E+09 | 0.325506E+09 | 44016659.46 | 0.281489E+09 | 0.00 | 0.00 |
| March | 0.305001E+09 | 0.701620E+09 | 0.504925E+09 | 0.127615E+09 | 0.377310E+09 | 0.00 | 0.00 |
| April | 0.509888E+09 | 0.466044E+09 | 0.606165E+09 | 0.144266E+09 | 0.461899E+09 | 0.00 | 0.00 |
| May | 0.780105E+09 | 0.288010E+09 | 0.734452E+09 | 0.205761E+09 | 0.528691E+09 | 0.00 | 0.00 |
| June | 0.102139E+10 | 0.199419E+09 | 0.856960E+09 | 0.264975E+09 | 0.591985E+09 | 0.00 | 0.00 |
| July | 0.104985E+10 | 0.140186E+09 | 0.804971E+09 | 0.224833E+09 | 0.580138E+09 | 0.00 | 0.00 |
| August | 0.895798E+09 | 0.197218E+09 | 0.714253E+09 | 0.181989E+09 | 0.532264E+09 | 0.00 | 0.00 |
| September | 0.567450E+09 | 0.325397E+09 | 0.535735E+09 | 0.136902E+09 | 0.398833E+09 | 0.00 | 0.00 |
| October | 0.280182E+09 | 0.510484E+09 | 0.381186E+09 | 74680744.99 | 0.306505E+09 | 0.00 | 0.00 |
| November | 93737383.90 | 0.658806E+09 | 0.230605E+09 | 34234006.48 | 0.196371E+09 | 0.00 | 0.00 |
| December | 16674419.95 | 0.108141E+10 | 0.214091E+09 | 23553783.07 | 0.190537E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.560175E+10 | 0.664449E+10 | 0.613798E+10 | 0.149027E+10 | 0.464771E+10 | 0.00 | 0.00 |
| Minimum of Months | 15797332.09 | 0.140186E+09 | 0.214091E+09 | 23553783.07 | 0.190537E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.104985E+10 | 0.113040E+10 | 0.856960E+09 | 0.264975E+09 | 0.591985E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: OFFICE
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.456429E+09 | 0.859492E+09 | 0.618723E+09 | 0.325422E+09 | 0.293301E+09 | 0.00 | 0.00 |
| February | 0.511187E+09 | 0.754095E+09 | 0.677643E+09 | 0.293485E+09 | 0.384158E+09 | 0.00 | 0.00 |
| March | 0.921596E+09 | 0.594042E+09 | 0.949859E+09 | 0.487907E+09 | 0.461952E+09 | 0.00 | 0.00 |
| April | 0.957155E+09 | 0.432963E+09 | 0.911799E+09 | 0.383249E+09 | 0.528551E+09 | 0.00 | 0.00 |
| May | 0.103446E+10 | 0.321257E+09 | 0.911548E+09 | 0.328607E+09 | 0.582940E+09 | 0.00 | 0.00 |
| June | 0.111249E+10 | 0.239109E+09 | 0.918640E+09 | 0.300982E+09 | 0.617658E+09 | 0.00 | 0.00 |
| July | 0.121306E+10 | 0.195180E+09 | 0.936892E+09 | 0.315441E+09 | 0.621451E+09 | 0.00 | 0.00 |
| August | 0.120858E+10 | 0.258364E+09 | 0.949024E+09 | 0.343023E+09 | 0.606001E+09 | 0.00 | 0.00 |
| September | 0.112464E+10 | 0.374695E+09 | 0.948968E+09 | 0.451153E+09 | 0.497815E+09 | 0.00 | 0.00 |
| October | 0.864957E+09 | 0.533217E+09 | 0.838235E+09 | 0.442767E+09 | 0.395468E+09 | 0.00 | 0.00 |
| November | 0.492463E+09 | 0.602816E+09 | 0.547885E+09 | 0.278931E+09 | 0.268954E+09 | 0.00 | 0.00 |
| December | 0.345621E+09 | 0.857523E+09 | 0.510423E+09 | 0.231389E+09 | 0.279034E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.102426E+11 | 0.602275E+10 | 0.971964E+10 | 0.418236E+10 | 0.553728E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.345621E+09 | 0.195180E+09 | 0.510423E+09 | 0.231389E+09 | 0.268954E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.121306E+10 | 0.859492E+09 | 0.949859E+09 | 0.487907E+09 | 0.621451E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: G NE APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 21729813.98 | 0.110057E+10 | 0.248486E+09 | 44115383.46 | 0.204371E+09 | 0.00 | 0.00 |
| February | 67378065.25 | 0.925489E+09 | 0.334188E+09 | 53538670.03 | 0.280649E+09 | 0.00 | 0.00 |
| March | 0.283329E+09 | 0.689512E+09 | 0.493926E+09 | 0.119512E+09 | 0.374414E+09 | 0.00 | 0.00 |
| April | 0.518346E+09 | 0.451437E+09 | 0.622081E+09 | 0.162746E+09 | 0.459335E+09 | 0.00 | 0.00 |
| May | 0.771347E+09 | 0.280599E+09 | 0.731075E+09 | 0.200221E+09 | 0.530854E+09 | 0.00 | 0.00 |
| June | 0.966045E+09 | 0.195010E+09 | 0.816050E+09 | 0.232708E+09 | 0.583342E+09 | 0.00 | 0.00 |
| July | 0.103998E+10 | 0.137871E+09 | 0.798455E+09 | 0.222781E+09 | 0.575674E+09 | 0.00 | 0.00 |
| August | 0.881685E+09 | 0.192371E+09 | 0.708078E+09 | 0.177097E+09 | 0.530981E+09 | 0.00 | 0.00 |
| September | 0.574436E+09 | 0.315403E+09 | 0.547953E+09 | 0.145400E+09 | 0.402553E+09 | 0.00 | 0.00 |
| October | 0.293694E+09 | 0.496957E+09 | 0.400046E+09 | 95139569.63 | 0.304906E+09 | 0.00 | 0.00 |
| November | 96448490.64 | 0.649864E+09 | 0.236889E+09 | 40598305.06 | 0.196291E+09 | 0.00 | 0.00 |
| December | 12604580.25 | 0.107490E+10 | 0.211047E+09 | 21871167.95 | 0.189176E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.552703E+10 | 0.650999E+10 | 0.614827E+10 | 0.151573E+10 | 0.463255E+10 | 0.00 | 0.00 |
| Minimum of Months | 12604580.25 | 0.137871E+09 | 0.211047E+09 | 21871167.95 | 0.189176E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.103998E+10 | 0.110057E+10 | 0.816050E+09 | 0.232708E+09 | 0.583342E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: G N1 APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 246666.40 | 0.720809E+09 | 0.112596E+09 | 0.00 | 0.112596E+09 | 0.00 | 0.00 |
| February | 7908502.86 | 0.603998E+09 | 0.154952E+09 | 0.00 | 0.154952E+09 | 0.00 | 0.00 |
| March | 76026905.56 | 0.458299E+09 | 0.208080E+09 | 7369.23 | 0.208072E+09 | 0.00 | 0.00 |
| April | 0.161678E+09 | 0.291575E+09 | 0.256713E+09 | 1237747.44 | 0.255475E+09 | 0.00 | 0.00 |
| May | 0.281779E+09 | 0.176475E+09 | 0.308157E+09 | 13268987.07 | 0.294888E+09 | 0.00 | 0.00 |
| June | 0.400877E+09 | 0.120821E+09 | 0.358543E+09 | 30487239.06 | 0.328056E+09 | 0.00 | 0.00 |
| July | 0.443011E+09 | 83535667.50 | 0.345055E+09 | 23472851.36 | 0.321583E+09 | 0.00 | 0.00 |
| August | 0.358349E+09 | 0.117874E+09 | 0.298739E+09 | 5766984.46 | 0.292972E+09 | 0.00 | 0.00 |
| September | 0.199700E+09 | 0.202254E+09 | 0.219114E+09 | 96969.17 | 0.219018E+09 | 0.00 | 0.00 |
| October | 88719053.69 | 0.322413E+09 | 0.169177E+09 | 0.00 | 0.169177E+09 | 0.00 | 0.00 |
| November | 24929851.09 | 0.414034E+09 | 0.110016E+09 | 0.00 | 0.110016E+09 | 0.00 | 0.00 |
| December | 1382409.71 | 0.685863E+09 | 0.105386E+09 | 0.00 | 0.105386E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.204461E+10 | 0.419795E+10 | 0.264653E+10 | 74338147.80 | 0.257219E+10 | 0.00 | 0.00 |
| Minimum of Months | 246666.40 | 83535667.50 | 0.105386E+09 | 0.00 | 0.105386E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.443011E+09 | 0.720809E+09 | 0.358543E+09 | 30487239.06 | 0.328056E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: G N2 APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 246373.50 | 0.720834E+09 | 0.112596E+09 | 0.00 | 0.112596E+09 | 0.00 | 0.00 |
| February | 7902738.98 | 0.604010E+09 | 0.154952E+09 | 0.00 | 0.154952E+09 | 0.00 | 0.00 |
| March | 76000388.55 | 0.458298E+09 | 0.208080E+09 | 7369.23 | 0.208072E+09 | 0.00 | 0.00 |
| April | 0.161614E+09 | 0.291580E+09 | 0.256713E+09 | 1237747.44 | 0.255475E+09 | 0.00 | 0.00 |
| May | 0.281675E+09 | 0.176451E+09 | 0.308157E+09 | 13268987.07 | 0.294888E+09 | 0.00 | 0.00 |
| June | 0.400876E+09 | 0.120735E+09 | 0.358543E+09 | 30487239.06 | 0.328056E+09 | 0.00 | 0.00 |
| July | 0.442976E+09 | 83514825.03 | 0.345055E+09 | 23472851.36 | 0.321583E+09 | 0.00 | 0.00 |
| August | 0.358326E+09 | 0.117846E+09 | 0.298739E+09 | 5766984.46 | 0.292972E+09 | 0.00 | 0.00 |
| September | 0.199608E+09 | 0.202278E+09 | 0.219114E+09 | 96969.17 | 0.219018E+09 | 0.00 | 0.00 |
| October | 88628648.01 | 0.322509E+09 | 0.169177E+09 | 0.00 | 0.169177E+09 | 0.00 | 0.00 |
| November | 24917448.60 | 0.414049E+09 | 0.110016E+09 | 0.00 | 0.110016E+09 | 0.00 | 0.00 |
| December | 1381943.16 | 0.685868E+09 | 0.105386E+09 | 0.00 | 0.105386E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.204415E+10 | 0.419797E+10 | 0.264653E+10 | 74338147.80 | 0.257219E+10 | 0.00 | 0.00 |
| Minimum of Months | 246373.50 | 83514825.03 | 0.105386E+09 | 0.00 | 0.105386E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.442976E+09 | 0.720834E+09 | 0.358543E+09 | 30487239.06 | 0.328056E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: G S1 APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.391917E+09 | 0.616210E+09 | 0.482833E+09 | 0.281306E+09 | 0.201526E+09 | 0.00 | 0.00 |
| February | 0.400047E+09 | 0.541084E+09 | 0.498407E+09 | 0.239946E+09 | 0.258461E+09 | 0.00 | 0.00 |
| March | 0.668383E+09 | 0.422674E+09 | 0.664013E+09 | 0.368403E+09 | 0.295610E+09 | 0.00 | 0.00 |
| April | 0.585912E+09 | 0.303159E+09 | 0.546431E+09 | 0.221740E+09 | 0.324691E+09 | 0.00 | 0.00 |
| May | 0.571964E+09 | 0.200816E+09 | 0.488630E+09 | 0.141655E+09 | 0.346974E+09 | 0.00 | 0.00 |
| June | 0.583888E+09 | 0.135399E+09 | 0.461133E+09 | 98760793.79 | 0.362372E+09 | 0.00 | 0.00 |
| July | 0.675899E+09 | 91696081.75 | 0.483493E+09 | 0.116133E+09 | 0.367360E+09 | 0.00 | 0.00 |
| August | 0.734608E+09 | 0.125610E+09 | 0.539686E+09 | 0.171693E+09 | 0.367993E+09 | 0.00 | 0.00 |
| September | 0.774542E+09 | 0.206650E+09 | 0.620130E+09 | 0.305851E+09 | 0.314279E+09 | 0.00 | 0.00 |
| October | 0.661348E+09 | 0.324524E+09 | 0.607366E+09 | 0.347628E+09 | 0.259738E+09 | 0.00 | 0.00 |
| November | 0.405407E+09 | 0.394889E+09 | 0.421012E+09 | 0.238333E+09 | 0.182679E+09 | 0.00 | 0.00 |
| December | 0.310707E+09 | 0.603938E+09 | 0.404762E+09 | 0.209518E+09 | 0.195244E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.676462E+10 | 0.396665E+10 | 0.621789E+10 | 0.274097E+10 | 0.347693E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.310707E+09 | 91696081.75 | 0.404762E+09 | 98760793.79 | 0.182679E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.774542E+09 | 0.616210E+09 | 0.664013E+09 | 0.368403E+09 | 0.367993E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: G S2 APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.392833E+09 | 0.612667E+09 | 0.482833E+09 | 0.281306E+09 | 0.201526E+09 | 0.00 | 0.00 |
| February | 0.401055E+09 | 0.538298E+09 | 0.498407E+09 | 0.239946E+09 | 0.258461E+09 | 0.00 | 0.00 |
| March | 0.669382E+09 | 0.420569E+09 | 0.664013E+09 | 0.368403E+09 | 0.295610E+09 | 0.00 | 0.00 |
| April | 0.586425E+09 | 0.302057E+09 | 0.546431E+09 | 0.221740E+09 | 0.324691E+09 | 0.00 | 0.00 |
| May | 0.570476E+09 | 0.202203E+09 | 0.488630E+09 | 0.141655E+09 | 0.346974E+09 | 0.00 | 0.00 |
| June | 0.582527E+09 | 0.136564E+09 | 0.461133E+09 | 98760793.79 | 0.362372E+09 | 0.00 | 0.00 |
| July | 0.674299E+09 | 92945618.44 | 0.483493E+09 | 0.116133E+09 | 0.367360E+09 | 0.00 | 0.00 |
| August | 0.733232E+09 | 0.127011E+09 | 0.539686E+09 | 0.171693E+09 | 0.367993E+09 | 0.00 | 0.00 |
| September | 0.773652E+09 | 0.207890E+09 | 0.620130E+09 | 0.305851E+09 | 0.314279E+09 | 0.00 | 0.00 |
| October | 0.660509E+09 | 0.325823E+09 | 0.607366E+09 | 0.347628E+09 | 0.259738E+09 | 0.00 | 0.00 |
| November | 0.405789E+09 | 0.393668E+09 | 0.421012E+09 | 0.238333E+09 | 0.182679E+09 | 0.00 | 0.00 |
| December | 0.311477E+09 | 0.600701E+09 | 0.404762E+09 | 0.209518E+09 | 0.195244E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.676166E+10 | 0.396040E+10 | 0.621789E+10 | 0.274097E+10 | 0.347693E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.311477E+09 | 92945618.44 | 0.404762E+09 | 98760793.79 | 0.182679E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.773652E+09 | 0.612667E+09 | 0.664013E+09 | 0.368403E+09 | 0.367993E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: M SW APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.383486E+09 | 0.105827E+10 | 0.599368E+09 | 0.308752E+09 | 0.290616E+09 | 0.00 | 0.00 |
| February | 0.441043E+09 | 0.923845E+09 | 0.668961E+09 | 0.283963E+09 | 0.384998E+09 | 0.00 | 0.00 |
| March | 0.867469E+09 | 0.720192E+09 | 0.960858E+09 | 0.496010E+09 | 0.464848E+09 | 0.00 | 0.00 |
| April | 0.882182E+09 | 0.531310E+09 | 0.895884E+09 | 0.364769E+09 | 0.531115E+09 | 0.00 | 0.00 |
| May | 0.996743E+09 | 0.385270E+09 | 0.914925E+09 | 0.334147E+09 | 0.580778E+09 | 0.00 | 0.00 |
| June | 0.117957E+10 | 0.232664E+09 | 0.959550E+09 | 0.333248E+09 | 0.626301E+09 | 0.00 | 0.00 |
| July | 0.127159E+10 | 0.156509E+09 | 0.943408E+09 | 0.317493E+09 | 0.625915E+09 | 0.00 | 0.00 |
| August | 0.126217E+10 | 0.210192E+09 | 0.955200E+09 | 0.347915E+09 | 0.607285E+09 | 0.00 | 0.00 |
| September | 0.112828E+10 | 0.338832E+09 | 0.936750E+09 | 0.442656E+09 | 0.494095E+09 | 0.00 | 0.00 |
| October | 0.833122E+09 | 0.535292E+09 | 0.819374E+09 | 0.422309E+09 | 0.397066E+09 | 0.00 | 0.00 |
| November | 0.462461E+09 | 0.664709E+09 | 0.541601E+09 | 0.272567E+09 | 0.269034E+09 | 0.00 | 0.00 |
| December | 0.312576E+09 | 0.103245E+10 | 0.513467E+09 | 0.233072E+09 | 0.280395E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.100207E+11 | 0.678954E+10 | 0.970935E+10 | 0.415690E+10 | 0.555245E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.312576E+09 | 0.156509E+09 | 0.513467E+09 | 0.233072E+09 | 0.269034E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.127159E+10 | 0.105827E+10 | 0.960858E+09 | 0.496010E+09 | 0.626301E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: M NW APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 13681409.99 | 0.117787E+10 | 0.229132E+09 | 27445700.15 | 0.201686E+09 | 0.00 | 0.00 |
| February | 58685799.53 | 0.988227E+09 | 0.325506E+09 | 44016659.46 | 0.281489E+09 | 0.00 | 0.00 |
| March | 0.280977E+09 | 0.749289E+09 | 0.504925E+09 | 0.127615E+09 | 0.377310E+09 | 0.00 | 0.00 |
| April | 0.474358E+09 | 0.511192E+09 | 0.606165E+09 | 0.144266E+09 | 0.461899E+09 | 0.00 | 0.00 |
| May | 0.706135E+09 | 0.361935E+09 | 0.734452E+09 | 0.205761E+09 | 0.528691E+09 | 0.00 | 0.00 |
| June | 0.994043E+09 | 0.217047E+09 | 0.856960E+09 | 0.264975E+09 | 0.591985E+09 | 0.00 | 0.00 |
| July | 0.103805E+10 | 0.145736E+09 | 0.804971E+09 | 0.224833E+09 | 0.580138E+09 | 0.00 | 0.00 |
| August | 0.888197E+09 | 0.201892E+09 | 0.714253E+09 | 0.181989E+09 | 0.532264E+09 | 0.00 | 0.00 |
| September | 0.559200E+09 | 0.334387E+09 | 0.535735E+09 | 0.136902E+09 | 0.398833E+09 | 0.00 | 0.00 |
| October | 0.270759E+09 | 0.528996E+09 | 0.381186E+09 | 74680744.99 | 0.306505E+09 | 0.00 | 0.00 |
| November | 88888075.16 | 0.680174E+09 | 0.230605E+09 | 34234006.48 | 0.196371E+09 | 0.00 | 0.00 |
| December | 14813256.93 | 0.112002E+10 | 0.214091E+09 | 23553783.07 | 0.190537E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.538779E+10 | 0.701676E+10 | 0.613798E+10 | 0.149027E+10 | 0.464771E+10 | 0.00 | 0.00 |
| Minimum of Months | 13681409.99 | 0.145736E+09 | 0.214091E+09 | 23553783.07 | 0.190537E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.103805E+10 | 0.117787E+10 | 0.856960E+09 | 0.264975E+09 | 0.591985E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: M SE APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.412839E+09 | 0.105093E+10 | 0.618723E+09 | 0.325422E+09 | 0.293301E+09 | 0.00 | 0.00 |
| February | 0.456671E+09 | 0.916761E+09 | 0.677643E+09 | 0.293485E+09 | 0.384158E+09 | 0.00 | 0.00 |
| March | 0.855390E+09 | 0.716153E+09 | 0.949859E+09 | 0.487907E+09 | 0.461952E+09 | 0.00 | 0.00 |
| April | 0.892008E+09 | 0.518985E+09 | 0.911799E+09 | 0.383249E+09 | 0.528551E+09 | 0.00 | 0.00 |
| May | 0.982067E+09 | 0.371291E+09 | 0.911548E+09 | 0.328607E+09 | 0.582940E+09 | 0.00 | 0.00 |
| June | 0.111645E+10 | 0.220504E+09 | 0.918640E+09 | 0.300982E+09 | 0.617658E+09 | 0.00 | 0.00 |
| July | 0.125437E+10 | 0.146124E+09 | 0.936892E+09 | 0.315441E+09 | 0.621451E+09 | 0.00 | 0.00 |
| August | 0.124328E+10 | 0.200554E+09 | 0.949024E+09 | 0.343023E+09 | 0.606001E+09 | 0.00 | 0.00 |
| September | 0.113890E+10 | 0.330581E+09 | 0.948968E+09 | 0.451153E+09 | 0.497815E+09 | 0.00 | 0.00 |
| October | 0.855188E+09 | 0.530954E+09 | 0.838235E+09 | 0.442767E+09 | 0.395468E+09 | 0.00 | 0.00 |
| November | 0.470772E+09 | 0.661171E+09 | 0.547885E+09 | 0.278931E+09 | 0.268954E+09 | 0.00 | 0.00 |
| December | 0.309991E+09 | 0.102663E+10 | 0.510423E+09 | 0.231389E+09 | 0.279034E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.998793E+10 | 0.669064E+10 | 0.971964E+10 | 0.418236E+10 | 0.553728E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.309991E+09 | 0.146124E+09 | 0.510423E+09 | 0.231389E+09 | 0.268954E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.125437E+10 | 0.105093E+10 | 0.949859E+09 | 0.487907E+09 | 0.621451E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: M NE APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 18393455.25 | 0.114583E+10 | 0.248486E+09 | 44115383.46 | 0.204371E+09 | 0.00 | 0.00 |
| February | 59810496.41 | 0.966737E+09 | 0.334188E+09 | 53538670.03 | 0.280649E+09 | 0.00 | 0.00 |
| March | 0.260067E+09 | 0.737264E+09 | 0.493926E+09 | 0.119512E+09 | 0.374414E+09 | 0.00 | 0.00 |
| April | 0.480743E+09 | 0.496195E+09 | 0.622081E+09 | 0.162746E+09 | 0.459335E+09 | 0.00 | 0.00 |
| May | 0.694481E+09 | 0.352166E+09 | 0.731075E+09 | 0.200221E+09 | 0.530854E+09 | 0.00 | 0.00 |
| June | 0.938638E+09 | 0.212745E+09 | 0.816050E+09 | 0.232708E+09 | 0.583342E+09 | 0.00 | 0.00 |
| July | 0.102858E+10 | 0.143179E+09 | 0.798455E+09 | 0.222781E+09 | 0.575674E+09 | 0.00 | 0.00 |
| August | 0.873929E+09 | 0.196906E+09 | 0.708078E+09 | 0.177097E+09 | 0.530981E+09 | 0.00 | 0.00 |
| September | 0.566288E+09 | 0.323528E+09 | 0.547953E+09 | 0.145400E+09 | 0.402553E+09 | 0.00 | 0.00 |
| October | 0.283728E+09 | 0.514599E+09 | 0.400046E+09 | 95139569.63 | 0.304906E+09 | 0.00 | 0.00 |
| November | 91369153.94 | 0.670728E+09 | 0.236889E+09 | 40598305.06 | 0.196291E+09 | 0.00 | 0.00 |
| December | 10932004.30 | 0.111292E+10 | 0.211047E+09 | 21871167.95 | 0.189176E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.530696E+10 | 0.687280E+10 | 0.614827E+10 | 0.151573E+10 | 0.463255E+10 | 0.00 | 0.00 |
| Minimum of Months | 10932004.30 | 0.143179E+09 | 0.211047E+09 | 21871167.95 | 0.189176E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.102858E+10 | 0.114583E+10 | 0.816050E+09 | 0.232708E+09 | 0.583342E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: M N1 APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 61752.59 | 0.748493E+09 | 0.112596E+09 | 0.00 | 0.112596E+09 | 0.00 | 0.00 |
| February | 5953740.85 | 0.629320E+09 | 0.154952E+09 | 0.00 | 0.154952E+09 | 0.00 | 0.00 |
| March | 66526808.62 | 0.488099E+09 | 0.208080E+09 | 7369.23 | 0.208072E+09 | 0.00 | 0.00 |
| April | 0.144214E+09 | 0.319728E+09 | 0.256713E+09 | 1237747.44 | 0.255475E+09 | 0.00 | 0.00 |
| May | 0.240308E+09 | 0.218844E+09 | 0.308157E+09 | 13268987.07 | 0.294888E+09 | 0.00 | 0.00 |
| June | 0.388292E+09 | 0.129088E+09 | 0.358543E+09 | 30487239.06 | 0.328056E+09 | 0.00 | 0.00 |
| July | 0.438374E+09 | 85861613.34 | 0.345055E+09 | 23472851.36 | 0.321583E+09 | 0.00 | 0.00 |
| August | 0.355410E+09 | 0.120011E+09 | 0.298739E+09 | 5766984.46 | 0.292972E+09 | 0.00 | 0.00 |
| September | 0.196145E+09 | 0.207203E+09 | 0.219114E+09 | 96969.17 | 0.219018E+09 | 0.00 | 0.00 |
| October | 83567208.48 | 0.336130E+09 | 0.169177E+09 | 0.00 | 0.169177E+09 | 0.00 | 0.00 |
| November | 22791590.92 | 0.427816E+09 | 0.110016E+09 | 0.00 | 0.110016E+09 | 0.00 | 0.00 |
| December | 1114336.51 | 0.709000E+09 | 0.105386E+09 | 0.00 | 0.105386E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.194276E+10 | 0.441959E+10 | 0.264653E+10 | 74338147.80 | 0.257219E+10 | 0.00 | 0.00 |
| Minimum of Months | 61752.59 | 85861613.34 | 0.105386E+09 | 0.00 | 0.105386E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.438374E+09 | 0.748493E+09 | 0.358543E+09 | 30487239.06 | 0.328056E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: M N2 APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 61598.14 | 0.748521E+09 | 0.112596E+09 | 0.00 | 0.112596E+09 | 0.00 | 0.00 |
| February | 5946657.42 | 0.629337E+09 | 0.154952E+09 | 0.00 | 0.154952E+09 | 0.00 | 0.00 |
| March | 66494484.03 | 0.488088E+09 | 0.208080E+09 | 7369.23 | 0.208072E+09 | 0.00 | 0.00 |
| April | 0.144001E+09 | 0.319864E+09 | 0.256713E+09 | 1237747.44 | 0.255475E+09 | 0.00 | 0.00 |
| May | 0.240157E+09 | 0.218840E+09 | 0.308157E+09 | 13268987.07 | 0.294888E+09 | 0.00 | 0.00 |
| June | 0.388254E+09 | 0.129049E+09 | 0.358543E+09 | 30487239.06 | 0.328056E+09 | 0.00 | 0.00 |
| July | 0.438340E+09 | 85837305.77 | 0.345055E+09 | 23472851.36 | 0.321583E+09 | 0.00 | 0.00 |
| August | 0.355382E+09 | 0.119984E+09 | 0.298739E+09 | 5766984.46 | 0.292972E+09 | 0.00 | 0.00 |
| September | 0.196082E+09 | 0.207179E+09 | 0.219114E+09 | 96969.17 | 0.219018E+09 | 0.00 | 0.00 |
| October | 83449610.24 | 0.336239E+09 | 0.169177E+09 | 0.00 | 0.169177E+09 | 0.00 | 0.00 |
| November | 22776556.88 | 0.427836E+09 | 0.110016E+09 | 0.00 | 0.110016E+09 | 0.00 | 0.00 |
| December | 1113773.77 | 0.709006E+09 | 0.105386E+09 | 0.00 | 0.105386E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.194206E+10 | 0.441978E+10 | 0.264653E+10 | 74338147.80 | 0.257219E+10 | 0.00 | 0.00 |
| Minimum of Months | 61598.14 | 85837305.77 | 0.105386E+09 | 0.00 | 0.105386E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.438340E+09 | 0.748521E+09 | 0.358543E+09 | 30487239.06 | 0.328056E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: M S1 APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.383603E+09 | 0.638473E+09 | 0.482833E+09 | 0.281306E+09 | 0.201526E+09 | 0.00 | 0.00 |
| February | 0.389308E+09 | 0.562176E+09 | 0.498407E+09 | 0.239946E+09 | 0.258461E+09 | 0.00 | 0.00 |
| March | 0.650311E+09 | 0.448312E+09 | 0.664013E+09 | 0.368403E+09 | 0.295610E+09 | 0.00 | 0.00 |
| April | 0.561053E+09 | 0.338376E+09 | 0.546431E+09 | 0.221740E+09 | 0.324691E+09 | 0.00 | 0.00 |
| May | 0.538363E+09 | 0.243254E+09 | 0.488630E+09 | 0.141655E+09 | 0.346974E+09 | 0.00 | 0.00 |
| June | 0.573749E+09 | 0.143058E+09 | 0.461133E+09 | 98760793.79 | 0.362372E+09 | 0.00 | 0.00 |
| July | 0.670908E+09 | 93820878.23 | 0.483493E+09 | 0.116133E+09 | 0.367360E+09 | 0.00 | 0.00 |
| August | 0.731022E+09 | 0.126896E+09 | 0.539686E+09 | 0.171693E+09 | 0.367993E+09 | 0.00 | 0.00 |
| September | 0.770556E+09 | 0.208831E+09 | 0.620130E+09 | 0.305851E+09 | 0.314279E+09 | 0.00 | 0.00 |
| October | 0.652797E+09 | 0.335494E+09 | 0.607366E+09 | 0.347628E+09 | 0.259738E+09 | 0.00 | 0.00 |
| November | 0.398245E+09 | 0.409519E+09 | 0.421012E+09 | 0.238333E+09 | 0.182679E+09 | 0.00 | 0.00 |
| December | 0.304120E+09 | 0.623565E+09 | 0.404762E+09 | 0.209518E+09 | 0.195244E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.662403E+10 | 0.417177E+10 | 0.621789E+10 | 0.274097E+10 | 0.347693E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.304120E+09 | 93820878.23 | 0.404762E+09 | 98760793.79 | 0.182679E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.770556E+09 | 0.638473E+09 | 0.664013E+09 | 0.368403E+09 | 0.367993E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: M S2 APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.383583E+09 | 0.638489E+09 | 0.482833E+09 | 0.281306E+09 | 0.201526E+09 | 0.00 | 0.00 |
| February | 0.389282E+09 | 0.562177E+09 | 0.498407E+09 | 0.239946E+09 | 0.258461E+09 | 0.00 | 0.00 |
| March | 0.650263E+09 | 0.448252E+09 | 0.664013E+09 | 0.368403E+09 | 0.295610E+09 | 0.00 | 0.00 |
| April | 0.560892E+09 | 0.338406E+09 | 0.546431E+09 | 0.221740E+09 | 0.324691E+09 | 0.00 | 0.00 |
| May | 0.538284E+09 | 0.243202E+09 | 0.488630E+09 | 0.141655E+09 | 0.346974E+09 | 0.00 | 0.00 |
| June | 0.573711E+09 | 0.143009E+09 | 0.461133E+09 | 98760793.79 | 0.362372E+09 | 0.00 | 0.00 |
| July | 0.670873E+09 | 93793720.07 | 0.483493E+09 | 0.116133E+09 | 0.367360E+09 | 0.00 | 0.00 |
| August | 0.730995E+09 | 0.126867E+09 | 0.539686E+09 | 0.171693E+09 | 0.367993E+09 | 0.00 | 0.00 |
| September | 0.770523E+09 | 0.208801E+09 | 0.620130E+09 | 0.305851E+09 | 0.314279E+09 | 0.00 | 0.00 |
| October | 0.652660E+09 | 0.335611E+09 | 0.607366E+09 | 0.347628E+09 | 0.259738E+09 | 0.00 | 0.00 |
| November | 0.398208E+09 | 0.409549E+09 | 0.421012E+09 | 0.238333E+09 | 0.182679E+09 | 0.00 | 0.00 |
| December | 0.304108E+09 | 0.623562E+09 | 0.404762E+09 | 0.209518E+09 | 0.195244E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.662338E+10 | 0.417172E+10 | 0.621789E+10 | 0.274097E+10 | 0.347693E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.304108E+09 | 93793720.07 | 0.404762E+09 | 98760793.79 | 0.182679E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.770523E+09 | 0.638489E+09 | 0.664013E+09 | 0.368403E+09 | 0.367993E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: T SW APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.385733E+09 | 0.102462E+10 | 0.599368E+09 | 0.308752E+09 | 0.290616E+09 | 0.00 | 0.00 |
| February | 0.442632E+09 | 0.895843E+09 | 0.668961E+09 | 0.283963E+09 | 0.384998E+09 | 0.00 | 0.00 |
| March | 0.865985E+09 | 0.690630E+09 | 0.960858E+09 | 0.496010E+09 | 0.464848E+09 | 0.00 | 0.00 |
| April | 0.880749E+09 | 0.499997E+09 | 0.895884E+09 | 0.364769E+09 | 0.531115E+09 | 0.00 | 0.00 |
| May | 0.100583E+10 | 0.342217E+09 | 0.914925E+09 | 0.334147E+09 | 0.580778E+09 | 0.00 | 0.00 |
| June | 0.117181E+10 | 0.215960E+09 | 0.959550E+09 | 0.333248E+09 | 0.626301E+09 | 0.00 | 0.00 |
| July | 0.125509E+10 | 0.149827E+09 | 0.943408E+09 | 0.317493E+09 | 0.625915E+09 | 0.00 | 0.00 |
| August | 0.125001E+10 | 0.199188E+09 | 0.955200E+09 | 0.347915E+09 | 0.607285E+09 | 0.00 | 0.00 |
| September | 0.113011E+10 | 0.305516E+09 | 0.936750E+09 | 0.442656E+09 | 0.494095E+09 | 0.00 | 0.00 |
| October | 0.840811E+09 | 0.492368E+09 | 0.819374E+09 | 0.422309E+09 | 0.397066E+09 | 0.00 | 0.00 |
| November | 0.464361E+09 | 0.631840E+09 | 0.541601E+09 | 0.272567E+09 | 0.269034E+09 | 0.00 | 0.00 |
| December | 0.313958E+09 | 0.999414E+09 | 0.513467E+09 | 0.233072E+09 | 0.280395E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.100071E+11 | 0.644742E+10 | 0.970935E+10 | 0.415690E+10 | 0.555245E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.313958E+09 | 0.149827E+09 | 0.513467E+09 | 0.233072E+09 | 0.269034E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.125509E+10 | 0.102462E+10 | 0.960858E+09 | 0.496010E+09 | 0.626301E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: T NW APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 14366411.65 | 0.114184E+10 | 0.229132E+09 | 27445700.15 | 0.201686E+09 | 0.00 | 0.00 |
| February | 60215236.10 | 0.958240E+09 | 0.325506E+09 | 44016659.46 | 0.281489E+09 | 0.00 | 0.00 |
| March | 0.282993E+09 | 0.720813E+09 | 0.504925E+09 | 0.127615E+09 | 0.377310E+09 | 0.00 | 0.00 |
| April | 0.472058E+09 | 0.489495E+09 | 0.606165E+09 | 0.144266E+09 | 0.461899E+09 | 0.00 | 0.00 |
| May | 0.719999E+09 | 0.323758E+09 | 0.734452E+09 | 0.205761E+09 | 0.528691E+09 | 0.00 | 0.00 |
| June | 0.990968E+09 | 0.203640E+09 | 0.856960E+09 | 0.264975E+09 | 0.591985E+09 | 0.00 | 0.00 |
| July | 0.102458E+10 | 0.141101E+09 | 0.804971E+09 | 0.224833E+09 | 0.580138E+09 | 0.00 | 0.00 |
| August | 0.880029E+09 | 0.191937E+09 | 0.714253E+09 | 0.181989E+09 | 0.532264E+09 | 0.00 | 0.00 |
| September | 0.568128E+09 | 0.298179E+09 | 0.535735E+09 | 0.136902E+09 | 0.398833E+09 | 0.00 | 0.00 |
| October | 0.278390E+09 | 0.493865E+09 | 0.381186E+09 | 74680744.99 | 0.306505E+09 | 0.00 | 0.00 |
| November | 91168322.93 | 0.651039E+09 | 0.230605E+09 | 34234006.48 | 0.196371E+09 | 0.00 | 0.00 |
| December | 15511913.05 | 0.108487E+10 | 0.214091E+09 | 23553783.07 | 0.190537E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.539841E+10 | 0.669878E+10 | 0.613798E+10 | 0.149027E+10 | 0.464771E+10 | 0.00 | 0.00 |
| Minimum of Months | 14366411.65 | 0.141101E+09 | 0.214091E+09 | 23553783.07 | 0.190537E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.102458E+10 | 0.114184E+10 | 0.856960E+09 | 0.264975E+09 | 0.591985E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: T SE APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.415059E+09 | 0.101690E+10 | 0.618723E+09 | 0.325422E+09 | 0.293301E+09 | 0.00 | 0.00 |
| February | 0.458624E+09 | 0.888604E+09 | 0.677643E+09 | 0.293485E+09 | 0.384158E+09 | 0.00 | 0.00 |
| March | 0.854280E+09 | 0.686992E+09 | 0.949859E+09 | 0.487907E+09 | 0.461952E+09 | 0.00 | 0.00 |
| April | 0.892239E+09 | 0.488965E+09 | 0.911799E+09 | 0.383249E+09 | 0.528551E+09 | 0.00 | 0.00 |
| May | 0.991539E+09 | 0.331309E+09 | 0.911548E+09 | 0.328607E+09 | 0.582940E+09 | 0.00 | 0.00 |
| June | 0.110961E+10 | 0.205749E+09 | 0.918640E+09 | 0.300982E+09 | 0.617658E+09 | 0.00 | 0.00 |
| July | 0.123842E+10 | 0.140567E+09 | 0.936892E+09 | 0.315441E+09 | 0.621451E+09 | 0.00 | 0.00 |
| August | 0.123151E+10 | 0.190630E+09 | 0.949024E+09 | 0.343023E+09 | 0.606001E+09 | 0.00 | 0.00 |
| September | 0.114044E+10 | 0.299421E+09 | 0.948968E+09 | 0.451153E+09 | 0.497815E+09 | 0.00 | 0.00 |
| October | 0.862872E+09 | 0.487534E+09 | 0.838235E+09 | 0.442767E+09 | 0.395468E+09 | 0.00 | 0.00 |
| November | 0.472565E+09 | 0.627948E+09 | 0.547885E+09 | 0.278931E+09 | 0.268954E+09 | 0.00 | 0.00 |
| December | 0.311701E+09 | 0.993553E+09 | 0.510423E+09 | 0.231389E+09 | 0.279034E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.997885E+10 | 0.635817E+10 | 0.971964E+10 | 0.418236E+10 | 0.553728E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.311701E+09 | 0.140567E+09 | 0.510423E+09 | 0.231389E+09 | 0.268954E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.123842E+10 | 0.101690E+10 | 0.949859E+09 | 0.487907E+09 | 0.621451E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: T NE APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 20063650.41 | 0.111044E+10 | 0.248486E+09 | 44115383.46 | 0.204371E+09 | 0.00 | 0.00 |
| February | 62496275.77 | 0.937399E+09 | 0.334188E+09 | 53538670.03 | 0.280649E+09 | 0.00 | 0.00 |
| March | 0.263472E+09 | 0.709751E+09 | 0.493926E+09 | 0.119512E+09 | 0.374414E+09 | 0.00 | 0.00 |
| April | 0.480158E+09 | 0.475301E+09 | 0.622081E+09 | 0.162746E+09 | 0.459335E+09 | 0.00 | 0.00 |
| May | 0.706389E+09 | 0.315329E+09 | 0.731075E+09 | 0.200221E+09 | 0.530854E+09 | 0.00 | 0.00 |
| June | 0.933753E+09 | 0.199062E+09 | 0.816050E+09 | 0.232708E+09 | 0.583342E+09 | 0.00 | 0.00 |
| July | 0.101448E+10 | 0.138209E+09 | 0.798455E+09 | 0.222781E+09 | 0.575674E+09 | 0.00 | 0.00 |
| August | 0.865348E+09 | 0.187225E+09 | 0.708078E+09 | 0.177097E+09 | 0.530981E+09 | 0.00 | 0.00 |
| September | 0.574542E+09 | 0.290461E+09 | 0.547953E+09 | 0.145400E+09 | 0.402553E+09 | 0.00 | 0.00 |
| October | 0.293024E+09 | 0.479985E+09 | 0.400046E+09 | 95139569.63 | 0.304906E+09 | 0.00 | 0.00 |
| November | 94271726.93 | 0.642029E+09 | 0.236889E+09 | 40598305.06 | 0.196291E+09 | 0.00 | 0.00 |
| December | 11891254.69 | 0.107771E+10 | 0.211047E+09 | 21871167.95 | 0.189176E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.531989E+10 | 0.656290E+10 | 0.614827E+10 | 0.151573E+10 | 0.463255E+10 | 0.00 | 0.00 |
| Minimum of Months | 11891254.69 | 0.138209E+09 | 0.211047E+09 | 21871167.95 | 0.189176E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.101448E+10 | 0.111044E+10 | 0.816050E+09 | 0.232708E+09 | 0.583342E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: T N1 APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 137215.53 | 0.727329E+09 | 0.112596E+09 | 0.00 | 0.112596E+09 | 0.00 | 0.00 |
| February | 6582539.74 | 0.611500E+09 | 0.154952E+09 | 0.00 | 0.154952E+09 | 0.00 | 0.00 |
| March | 68082871.74 | 0.470823E+09 | 0.208080E+09 | 7369.23 | 0.208072E+09 | 0.00 | 0.00 |
| April | 0.145460E+09 | 0.306296E+09 | 0.256713E+09 | 1237747.44 | 0.255475E+09 | 0.00 | 0.00 |
| May | 0.251033E+09 | 0.197592E+09 | 0.308157E+09 | 13268987.07 | 0.294888E+09 | 0.00 | 0.00 |
| June | 0.387231E+09 | 0.123170E+09 | 0.358543E+09 | 30487239.06 | 0.328056E+09 | 0.00 | 0.00 |
| July | 0.431398E+09 | 84369292.87 | 0.345055E+09 | 23472851.36 | 0.321583E+09 | 0.00 | 0.00 |
| August | 0.351243E+09 | 0.116259E+09 | 0.298739E+09 | 5766984.46 | 0.292972E+09 | 0.00 | 0.00 |
| September | 0.201841E+09 | 0.187677E+09 | 0.219114E+09 | 96969.17 | 0.219018E+09 | 0.00 | 0.00 |
| October | 90212003.34 | 0.310939E+09 | 0.169177E+09 | 0.00 | 0.169177E+09 | 0.00 | 0.00 |
| November | 24219994.38 | 0.409518E+09 | 0.110016E+09 | 0.00 | 0.110016E+09 | 0.00 | 0.00 |
| December | 1269748.40 | 0.688001E+09 | 0.105386E+09 | 0.00 | 0.105386E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.195871E+10 | 0.423347E+10 | 0.264653E+10 | 74338147.80 | 0.257219E+10 | 0.00 | 0.00 |
| Minimum of Months | 137215.53 | 84369292.87 | 0.105386E+09 | 0.00 | 0.105386E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.431398E+09 | 0.727329E+09 | 0.358543E+09 | 30487239.06 | 0.328056E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: T N2 APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 136536.72 | 0.727356E+09 | 0.112596E+09 | 0.00 | 0.112596E+09 | 0.00 | 0.00 |
| February | 6570549.10 | 0.611506E+09 | 0.154952E+09 | 0.00 | 0.154952E+09 | 0.00 | 0.00 |
| March | 67999214.26 | 0.470771E+09 | 0.208080E+09 | 7369.23 | 0.208072E+09 | 0.00 | 0.00 |
| April | 0.145089E+09 | 0.306211E+09 | 0.256713E+09 | 1237747.44 | 0.255475E+09 | 0.00 | 0.00 |
| May | 0.250488E+09 | 0.197488E+09 | 0.308157E+09 | 13268987.07 | 0.294888E+09 | 0.00 | 0.00 |
| June | 0.386976E+09 | 0.123049E+09 | 0.358543E+09 | 30487239.06 | 0.328056E+09 | 0.00 | 0.00 |
| July | 0.431293E+09 | 84292396.55 | 0.345055E+09 | 23472851.36 | 0.321583E+09 | 0.00 | 0.00 |
| August | 0.351128E+09 | 0.116170E+09 | 0.298739E+09 | 5766984.46 | 0.292972E+09 | 0.00 | 0.00 |
| September | 0.201455E+09 | 0.187649E+09 | 0.219114E+09 | 96969.17 | 0.219018E+09 | 0.00 | 0.00 |
| October | 90028606.75 | 0.310879E+09 | 0.169177E+09 | 0.00 | 0.169177E+09 | 0.00 | 0.00 |
| November | 24185761.83 | 0.409514E+09 | 0.110016E+09 | 0.00 | 0.110016E+09 | 0.00 | 0.00 |
| December | 1268683.09 | 0.688005E+09 | 0.105386E+09 | 0.00 | 0.105386E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.195662E+10 | 0.423289E+10 | 0.264653E+10 | 74338147.80 | 0.257219E+10 | 0.00 | 0.00 |
| Minimum of Months | 136536.72 | 84292396.55 | 0.105386E+09 | 0.00 | 0.105386E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.431293E+09 | 0.727356E+09 | 0.358543E+09 | 30487239.06 | 0.328056E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: T S1 APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.385331E+09 | 0.618747E+09 | 0.482833E+09 | 0.281306E+09 | 0.201526E+09 | 0.00 | 0.00 |
| February | 0.390534E+09 | 0.545993E+09 | 0.498407E+09 | 0.239946E+09 | 0.258461E+09 | 0.00 | 0.00 |
| March | 0.650240E+09 | 0.430730E+09 | 0.664013E+09 | 0.368403E+09 | 0.295610E+09 | 0.00 | 0.00 |
| April | 0.562830E+09 | 0.318040E+09 | 0.546431E+09 | 0.221740E+09 | 0.324691E+09 | 0.00 | 0.00 |
| May | 0.544561E+09 | 0.218967E+09 | 0.488630E+09 | 0.141655E+09 | 0.346974E+09 | 0.00 | 0.00 |
| June | 0.569601E+09 | 0.135229E+09 | 0.461133E+09 | 98760793.79 | 0.362372E+09 | 0.00 | 0.00 |
| July | 0.662001E+09 | 91328558.06 | 0.483493E+09 | 0.116133E+09 | 0.367360E+09 | 0.00 | 0.00 |
| August | 0.724145E+09 | 0.122498E+09 | 0.539686E+09 | 0.171693E+09 | 0.367993E+09 | 0.00 | 0.00 |
| September | 0.771292E+09 | 0.192300E+09 | 0.620130E+09 | 0.305851E+09 | 0.314279E+09 | 0.00 | 0.00 |
| October | 0.660396E+09 | 0.305200E+09 | 0.607366E+09 | 0.347628E+09 | 0.259738E+09 | 0.00 | 0.00 |
| November | 0.400674E+09 | 0.387277E+09 | 0.421012E+09 | 0.238333E+09 | 0.182679E+09 | 0.00 | 0.00 |
| December | 0.305308E+09 | 0.604225E+09 | 0.404762E+09 | 0.209518E+09 | 0.195244E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.662691E+10 | 0.397054E+10 | 0.621789E+10 | 0.274097E+10 | 0.347693E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.305308E+09 | 91328558.06 | 0.404762E+09 | 98760793.79 | 0.182679E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.771292E+09 | 0.618747E+09 | 0.664013E+09 | 0.368403E+09 | 0.367993E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: T S2 APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.385289E+09 | 0.618742E+09 | 0.482833E+09 | 0.281306E+09 | 0.201526E+09 | 0.00 | 0.00 |
| February | 0.390480E+09 | 0.545967E+09 | 0.498407E+09 | 0.239946E+09 | 0.258461E+09 | 0.00 | 0.00 |
| March | 0.650079E+09 | 0.430617E+09 | 0.664013E+09 | 0.368403E+09 | 0.295610E+09 | 0.00 | 0.00 |
| April | 0.562509E+09 | 0.317896E+09 | 0.546431E+09 | 0.221740E+09 | 0.324691E+09 | 0.00 | 0.00 |
| May | 0.544186E+09 | 0.218779E+09 | 0.488630E+09 | 0.141655E+09 | 0.346974E+09 | 0.00 | 0.00 |
| June | 0.569387E+09 | 0.135059E+09 | 0.461133E+09 | 98760793.79 | 0.362372E+09 | 0.00 | 0.00 |
| July | 0.661875E+09 | 91242597.51 | 0.483493E+09 | 0.116133E+09 | 0.367360E+09 | 0.00 | 0.00 |
| August | 0.724031E+09 | 0.122406E+09 | 0.539686E+09 | 0.171693E+09 | 0.367993E+09 | 0.00 | 0.00 |
| September | 0.771095E+09 | 0.192221E+09 | 0.620130E+09 | 0.305851E+09 | 0.314279E+09 | 0.00 | 0.00 |
| October | 0.660169E+09 | 0.305186E+09 | 0.607366E+09 | 0.347628E+09 | 0.259738E+09 | 0.00 | 0.00 |
| November | 0.400598E+09 | 0.387252E+09 | 0.421012E+09 | 0.238333E+09 | 0.182679E+09 | 0.00 | 0.00 |
| December | 0.305283E+09 | 0.604211E+09 | 0.404762E+09 | 0.209518E+09 | 0.195244E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.662498E+10 | 0.396958E+10 | 0.621789E+10 | 0.274097E+10 | 0.347693E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.305283E+09 | 91242597.51 | 0.404762E+09 | 98760793.79 | 0.182679E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.771095E+09 | 0.618742E+09 | 0.664013E+09 | 0.368403E+09 | 0.367993E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: T CORRIDOR
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 12084995.06 | 0.104851E+09 | 32607377.88 | 10585665.83 | 22021712.05 | 0.00 | 0.00 |
| February | 19434719.46 | 89206105.60 | 43008306.31 | 12846821.80 | 30161484.51 | 0.00 | 0.00 |
| March | 52831088.74 | 70410034.84 | 68589906.46 | 28675506.35 | 39914400.11 | 0.00 | 0.00 |
| April | 82603122.26 | 49526231.12 | 87671579.98 | 38754634.11 | 48916945.87 | 0.00 | 0.00 |
| May | 0.109352E+09 | 35486913.28 | 0.101481E+09 | 44859895.33 | 56620984.02 | 0.00 | 0.00 |
| June | 0.129772E+09 | 23087784.81 | 0.109781E+09 | 48523725.46 | 61256964.76 | 0.00 | 0.00 |
| July | 0.137393E+09 | 16665179.20 | 0.108795E+09 | 47824768.75 | 60970274.18 | 0.00 | 0.00 |
| August | 0.121093E+09 | 21954079.61 | 98222508.48 | 41111387.15 | 57111121.33 | 0.00 | 0.00 |
| September | 89338191.69 | 32622057.46 | 78906023.05 | 34865991.41 | 44040031.64 | 0.00 | 0.00 |
| October | 49624645.26 | 50583468.78 | 55397912.72 | 22829126.99 | 32568785.73 | 0.00 | 0.00 |
| November | 18401089.50 | 64789760.51 | 30443811.91 | 9741728.55 | 20702083.35 | 0.00 | 0.00 |
| December | 6103084.01 | 0.102897E+09 | 25353752.66 | 5248075.77 | 20105676.88 | 0.00 | 0.00 |
| Annual Sum or Average | 0.828030E+09 | 0.662079E+09 | 0.840258E+09 | 0.345867E+09 | 0.494390E+09 | 0.00 | 0.00 |
| Minimum of Months | 6103084.01 | 16665179.20 | 25353752.66 | 5248075.77 | 20105676.88 | 0.00 | 0.00 |
| Maximum of Months | 0.137393E+09 | 0.104851E+09 | 0.109781E+09 | 48523725.46 | 61256964.76 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: G CORRIDOR
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 41385967.53 | 0.272644E+09 | 97112886.10 | 31526747.22 | 65586138.88 | 0.00 | 0.00 |
| February | 67961675.12 | 0.231278E+09 | 0.128089E+09 | 38261032.42 | 89828406.96 | 0.00 | 0.00 |
| March | 0.171940E+09 | 0.182289E+09 | 0.204278E+09 | 85402794.19 | 0.118875E+09 | 0.00 | 0.00 |
| April | 0.263215E+09 | 0.128311E+09 | 0.261108E+09 | 0.115421E+09 | 0.145687E+09 | 0.00 | 0.00 |
| May | 0.342806E+09 | 90211512.94 | 0.302235E+09 | 0.133604E+09 | 0.168631E+09 | 0.00 | 0.00 |
| June | 0.394139E+09 | 65767263.30 | 0.326954E+09 | 0.144516E+09 | 0.182438E+09 | 0.00 | 0.00 |
| July | 0.412767E+09 | 49986256.44 | 0.324019E+09 | 0.142434E+09 | 0.181585E+09 | 0.00 | 0.00 |
| August | 0.363019E+09 | 66501258.17 | 0.292531E+09 | 0.122440E+09 | 0.170091E+09 | 0.00 | 0.00 |
| September | 0.266687E+09 | 99679195.50 | 0.235002E+09 | 0.103840E+09 | 0.131162E+09 | 0.00 | 0.00 |
| October | 0.150916E+09 | 0.146813E+09 | 0.164989E+09 | 67990821.50 | 96997949.08 | 0.00 | 0.00 |
| November | 58766972.52 | 0.178770E+09 | 90669248.20 | 29013291.99 | 61655956.22 | 0.00 | 0.00 |
| December | 21782366.59 | 0.269787E+09 | 75509785.03 | 15630075.71 | 59879709.33 | 0.00 | 0.00 |
| Annual Sum or Average | 0.255538E+10 | 0.178204E+10 | 0.250250E+10 | 0.103008E+10 | 0.147242E+10 | 0.00 | 0.00 |
| Minimum of Months | 21782366.59 | 49986256.44 | 75509785.03 | 15630075.71 | 59879709.33 | 0.00 | 0.00 |
| Maximum of Months | 0.412767E+09 | 0.272644E+09 | 0.326954E+09 | 0.144516E+09 | 0.182438E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: M CORRIDOR
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 11199527.39 | 0.113332E+09 | 32607377.88 | 10585665.83 | 22021712.05 | 0.00 | 0.00 |
| February | 18110291.62 | 96224693.40 | 43008306.31 | 12846821.80 | 30161484.51 | 0.00 | 0.00 |
| March | 50966902.21 | 76047381.84 | 68589906.46 | 28675506.35 | 39914400.11 | 0.00 | 0.00 |
| April | 80474850.90 | 53240603.01 | 87671579.98 | 38754634.11 | 48916945.87 | 0.00 | 0.00 |
| May | 0.106212E+09 | 39227481.66 | 0.101481E+09 | 44859895.33 | 56620984.02 | 0.00 | 0.00 |
| June | 0.128879E+09 | 24269781.07 | 0.109781E+09 | 48523725.46 | 61256964.76 | 0.00 | 0.00 |
| July | 0.137903E+09 | 16997934.79 | 0.108795E+09 | 47824768.75 | 60970274.18 | 0.00 | 0.00 |
| August | 0.121034E+09 | 22748601.04 | 98222508.48 | 41111387.15 | 57111121.33 | 0.00 | 0.00 |
| September | 87294799.61 | 35756606.94 | 78906023.05 | 34865991.41 | 44040031.64 | 0.00 | 0.00 |
| October | 47197215.02 | 56205486.28 | 55397912.72 | 22829126.99 | 32568785.73 | 0.00 | 0.00 |
| November | 17315437.39 | 70972878.16 | 30443811.91 | 9741728.55 | 20702083.35 | 0.00 | 0.00 |
| December | 5522620.38 | 0.111313E+09 | 25353752.66 | 5248075.77 | 20105676.88 | 0.00 | 0.00 |
| Annual Sum or Average | 0.812109E+09 | 0.716336E+09 | 0.840258E+09 | 0.345867E+09 | 0.494390E+09 | 0.00 | 0.00 |
| Minimum of Months | 5522620.38 | 16997934.79 | 25353752.66 | 5248075.77 | 20105676.88 | 0.00 | 0.00 |
| Maximum of Months | 0.137903E+09 | 0.113332E+09 | 0.109781E+09 | 48523725.46 | 61256964.76 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
| January | -3.4 | -4.9 | -8.7 | 5.96 | -14.4 | 41.15 | 62.17 | 0.00 |
| February | -4.2 | -5.4 | -8.1 | 6.66 | -15.1 | 65.72 | 71.39 | 0.00 |
| March | 2.67 | 0.66 | -2.8 | 5.20 | -8.9 | 69.76 | 141.76 | 0.00 |
| April | 7.47 | 4.95 | 1.92 | 5.29 | -2.7 | 89.32 | 159.79 | 0.00 |
| May | 13.73 | 9.66 | 5.81 | 4.79 | 3.34 | 93.75 | 203.34 | 0.03 |
| June | 18.63 | 14.47 | 11.49 | 5.10 | 8.69 | 105.42 | 236.95 | 0.00 |
| July | 22.03 | 18.19 | 16.11 | 4.43 | 13.39 | 102.98 | 214.28 | 0.00 |
| August | 20.69 | 16.39 | 13.72 | 4.23 | 11.88 | 99.24 | 178.64 | 0.00 |
| September | 16.55 | 13.42 | 11.22 | 4.10 | 7.08 | 75.66 | 154.97 | 0.03 |
| October | 9.73 | 7.36 | 4.97 | 4.79 | 0.13 | 58.70 | 104.01 | 0.00 |
| November | 6.03 | 3.70 | 0.77 | 5.87 | -3.2 | 41.19 | 58.47 | 0.00 |
| December | -2.2 | -3.2 | -5.3 | 6.59 | -12.0 | 40.52 | 44.30 | 0.00 |
| Annual Sum or Average | 9.05 | 6.33 | 3.49 | 5.24 | -0.9 | 73.64 | 136.19 | 0.01 |
| Minimum of Months | -4.2 | -5.4 | -8.7 | 4.10 | -15.1 | 40.52 | 44.30 | 0.00 |
| Maximum of Months | 22.03 | 18.19 | 16.11 | 6.66 | 13.39 | 105.42 | 236.95 | 0.03 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
| January | 11.70 | 11-JAN-15:00 | 10.14 | 8.90 | 13.40 | 7.15 | 65.50 | 1.00 |
| February | 12.80 | 22-FEB-17:00 | 6.18 | -2.2 | 14.90 | 3.48 | 0.00 | 0.00 |
| March | 26.10 | 15-MAR-13:00 | 16.06 | 9.40 | 6.70 | 14.65 | 249.50 | 400.00 |
| April | 21.10 | 08-APR-12:00 | 13.43 | 7.80 | 8.20 | 11.46 | 330.00 | 283.50 |
| May | 26.10 | 10-MAY-13:00 | 17.84 | 13.30 | 5.20 | 13.35 | 258.50 | 457.00 |
| June | 30.60 | 12-JUN-13:00 | 20.23 | 15.00 | 8.20 | 17.93 | 252.00 | 572.00 |
| July | 31.70 | 21-JUL-13:00 | 21.73 | 17.20 | 5.20 | 22.47 | 330.00 | 231.00 |
| August | 30.60 | 10-AUG-13:00 | 20.24 | 15.00 | 5.70 | 19.70 | 220.50 | 635.00 |
| September | 27.20 | 16-SEP-13:09 | 19.53 | 15.68 | 8.80 | 17.30 | 207.00 | 564.67 |
| October | 22.20 | 11-OCT-12:00 | 14.14 | 8.30 | 6.20 | 6.95 | 121.00 | 665.00 |
| November | 19.40 | 05-NOV-13:00 | 13.85 | 10.00 | 12.40 | 14.84 | 133.00 | 3.50 |
| December | 15.00 | 01-DEC-10:00 | 12.41 | 10.60 | 12.90 | 10.69 | 56.50 | 11.50 |
| Annual Sum or Average | ||||||||
| Minimum of Months | 11.70 | 6.18 | -2.2 | 5.20 | 3.48 | 0.00 | 0.00 | |
| Maximum of Months | 31.70 | 21.73 | 17.20 | 14.90 | 22.47 | 330.00 | 665.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
| January | -13.9 | 31-JAN-01:00 | -14.5 | -17.2 | 1.50 | -25.9 | 0.00 | 0.00 |
| February | -16.7 | 07-FEB-06:00 | -17.3 | -20.6 | 6.20 | -35.1 | 0.00 | 0.00 |
| March | -13.3 | 07-MAR-05:19 | -13.9 | -16.7 | 2.43 | -32.2 | 0.00 | 0.00 |
| April | -4.4 | 17-APR-05:00 | -5.4 | -7.8 | 2.10 | -20.5 | 35.00 | 151.50 |
| May | 1.70 | 01-MAY-04:00 | 0.96 | 0.00 | 0.00 | -14.2 | 0.00 | 0.00 |
| June | 6.70 | 04-JUN-04:00 | 5.40 | 3.90 | 2.10 | -7.3 | 20.00 | 104.00 |
| July | 11.70 | 03-JUL-03:00 | 11.07 | 10.60 | 2.10 | -1.2 | 0.00 | 0.00 |
| August | 11.10 | 01-AUG-04:00 | 10.75 | 10.60 | 2.10 | -0.8 | 0.00 | 0.00 |
| September | 6.10 | 05-SEP-05:00 | 5.59 | 5.00 | 2.10 | -6.2 | 24.50 | 41.00 |
| October | -2.8 | 17-OCT-04:10 | -3.2 | -4.0 | 2.18 | -19.4 | 0.00 | 0.00 |
| November | -3.9 | 24-NOV-05:00 | -4.5 | -5.6 | 2.10 | -18.1 | 0.00 | 0.00 |
| December | -18.9 | 11-DEC-05:00 | -19.4 | -23.3 | 2.10 | -35.1 | 0.00 | 0.00 |
| Annual Sum or Average | ||||||||
| Minimum of Months | -18.9 | -19.4 | -23.3 | 0.00 | -35.1 | 0.00 | 0.00 | |
| Maximum of Months | 11.70 | 11.07 | 10.60 | 6.20 | -0.8 | 35.00 | 151.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| SITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
| January | 10.21 | 11-JAN-17:00 | 11.10 | 9.40 | 10.30 | 6.55 | 0.00 | 0.00 |
| February | 6.89 | 01-FEB-03:00 | 7.20 | 6.70 | 3.60 | 2.22 | 0.00 | 0.00 |
| March | 17.83 | 14-MAR-12:00 | 25.00 | 13.90 | 6.20 | 14.10 | 197.00 | 562.50 |
| April | 13.78 | 08-APR-13:00 | 20.60 | 8.90 | 10.30 | 9.72 | 268.50 | 325.50 |
| May | 18.19 | 10-MAY-14:00 | 26.10 | 13.90 | 5.20 | 16.85 | 273.00 | 238.00 |
| June | 23.75 | 27-JUN-12:00 | 30.60 | 21.10 | 9.30 | 21.09 | 304.00 | 606.00 |
| July | 24.79 | 21-JUL-01:00 | 28.90 | 23.30 | 8.80 | 27.46 | 0.00 | 0.00 |
| August | 23.42 | 13-AUG-15:00 | 29.40 | 21.10 | 9.80 | 19.87 | 212.00 | 276.00 |
| September | 21.17 | 15-SEP-11:00 | 26.10 | 18.90 | 3.60 | 16.30 | 204.00 | 464.50 |
| October | 15.23 | 12-OCT-14:00 | 18.30 | 13.30 | 10.30 | 9.13 | 148.00 | 367.50 |
| November | 13.96 | 05-NOV-14:00 | 18.30 | 11.10 | 11.30 | 14.10 | 72.00 | 6.00 |
| December | 12.41 | 01-DEC-10:00 | 15.00 | 10.60 | 12.90 | 10.69 | 56.50 | 11.50 |
| Annual Sum or Average | ||||||||
| Minimum of Months | 6.89 | 7.20 | 6.70 | 3.60 | 2.22 | 0.00 | 0.00 | |
| Maximum of Months | 24.79 | 30.60 | 23.30 | 12.90 | 27.46 | 304.00 | 606.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| SITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
| January | 9.40 | 11-JAN-13:00 | 10.00 | 9.66 | 12.90 | 5.54 | 95.50 | 2.00 |
| February | 6.70 | 01-FEB-04:10 | 7.20 | 6.89 | 3.52 | 2.22 | 0.00 | 0.00 |
| March | 15.00 | 14-MAR-10:20 | 20.33 | 16.97 | 4.80 | 10.50 | 159.17 | 592.83 |
| April | 11.10 | 08-APR-21:00 | 13.90 | 12.23 | 12.90 | 9.72 | 0.00 | 0.00 |
| May | 15.60 | 17-MAY-12:00 | 16.70 | 15.97 | 6.70 | 13.54 | 184.00 | 0.00 |
| June | 21.70 | 27-JUN-14:00 | 25.60 | 22.78 | 8.20 | 16.85 | 255.50 | 530.00 |
| July | 23.30 | 20-JUL-20:00 | 25.60 | 24.03 | 4.60 | 24.16 | 0.00 | 0.00 |
| August | 21.70 | 14-AUG-03:20 | 23.70 | 22.19 | 5.00 | 21.90 | 0.00 | 0.00 |
| September | 20.00 | 15-SEP-18:00 | 21.70 | 20.51 | 0.00 | 19.52 | 0.00 | 0.00 |
| October | 14.40 | 01-OCT-07:19 | 14.60 | 14.50 | 3.77 | 10.56 | 67.50 | 30.17 |
| November | 11.70 | 05-NOV-15:00 | 12.80 | 12.14 | 7.20 | 8.74 | 28.00 | 4.50 |
| December | 11.10 | 01-DEC-12:00 | 13.90 | 12.22 | 10.30 | 6.35 | 158.00 | 84.50 |
| Annual Sum or Average | ||||||||
| Minimum of Months | 6.70 | 7.20 | 6.89 | 0.00 | 2.22 | 0.00 | 0.00 | |
| Maximum of Months | 23.30 | 25.60 | 24.03 | 12.90 | 24.16 | 255.50 | 592.83 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| SITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
| January | 18.00 | 13.00 | 16.00 | 7.32 | 12.49 | 0.00 |
| February | 18.00 | 13.00 | 16.00 | 6.57 | 19.26 | 0.00 |
| March | 18.00 | 13.00 | 16.00 | 7.29 | 28.63 | 0.00 |
| April | 18.00 | 13.00 | 16.00 | 9.34 | 37.44 | 0.00 |
| May | 18.00 | 13.00 | 16.00 | 12.19 | 46.60 | 0.00 |
| June | 18.00 | 13.00 | 16.00 | 15.07 | 54.01 | 0.00 |
| July | 18.00 | 13.00 | 16.00 | 17.20 | 50.29 | 0.00 |
| August | 18.00 | 13.00 | 16.00 | 18.01 | 43.20 | 0.00 |
| September | 18.00 | 13.00 | 16.00 | 17.27 | 32.93 | 0.00 |
| October | 18.00 | 13.00 | 16.00 | 15.18 | 21.28 | 0.00 |
| November | 18.00 | 13.00 | 16.00 | 12.32 | 12.54 | 0.00 |
| December | 18.00 | 13.00 | 16.00 | 9.45 | 10.96 | 0.00 |
| Annual Sum or Average | 18.00 | 13.00 | 16.00 | 12.30 | 30.86 | 0.00 |
| Minimum of Months | 18.00 | 13.00 | 16.00 | 6.57 | 10.96 | 0.00 |
| Maximum of Months | 18.00 | 13.00 | 16.00 | 18.01 | 54.01 | 0.00 |
Report: WaterHeaterReportMonthly
For: G SW APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.130720E+10 | -0.112059E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186606421.5 | 59.44 | 0.00 | 0.00 |
| February | 0.119526E+10 | -0.102672E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -168542915.3 | 59.44 | 0.00 | 0.00 |
| March | 0.130742E+10 | -0.112133E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186086640.7 | 59.44 | 0.00 | 0.00 |
| April | 0.122232E+10 | -0.104253E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -179791102.7 | 59.44 | 0.00 | 0.00 |
| May | 0.119810E+10 | -0.101600E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -182100305.7 | 59.44 | 0.00 | 0.00 |
| June | 0.109136E+10 | -923299612.8 | 0.00 | 0.00 | 720.00 | 0.00 | -168058871.7 | 59.44 | 0.00 | 0.00 |
| July | 0.108077E+10 | -908250532.2 | 0.00 | 0.00 | 744.00 | 0.00 | -172519281.1 | 59.44 | 0.00 | 0.00 |
| August | 0.106328E+10 | -890734248.3 | 0.00 | 0.00 | 744.00 | 0.00 | -172543966.7 | 59.44 | 0.00 | 0.00 |
| September | 0.104511E+10 | -877502757.6 | 0.00 | 0.00 | 720.00 | 0.00 | -167606299.8 | 59.44 | 0.00 | 0.00 |
| October | 0.113287E+10 | -951672466.5 | 0.00 | 0.00 | 744.00 | 0.00 | -181201930.4 | 59.44 | 0.00 | 0.00 |
| November | 0.116041E+10 | -980500826.0 | 0.00 | 0.00 | 720.00 | 0.00 | -179909111.7 | 59.44 | 0.00 | 0.00 |
| December | 0.126141E+10 | -0.107481E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186603676.3 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.140655E+11 | -0.119339E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.213157E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.104511E+10 | -0.112133E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -186606421.5 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.130742E+10 | -877502757.6 | 0.00 | 0.00 | 744.00 | 0.00 | -167606299.8 | 59.44 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: G NW APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.130720E+10 | -0.112059E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186606421.5 | 59.44 | 0.00 | 0.00 |
| February | 0.119526E+10 | -0.102672E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -168542915.3 | 59.44 | 0.00 | 0.00 |
| March | 0.130766E+10 | -0.112133E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186330620.9 | 59.44 | 0.00 | 0.00 |
| April | 0.122298E+10 | -0.104253E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -180449946.1 | 59.44 | 0.00 | 0.00 |
| May | 0.119983E+10 | -0.101600E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -183834201.4 | 59.44 | 0.00 | 0.00 |
| June | 0.109172E+10 | -923296938.1 | 0.00 | 0.00 | 720.00 | 0.00 | -168418789.7 | 59.44 | 0.00 | 0.00 |
| July | 0.108078E+10 | -908255595.4 | 0.00 | 0.00 | 744.00 | 0.00 | -172521424.3 | 59.44 | 0.00 | 0.00 |
| August | 0.106331E+10 | -890735593.0 | 0.00 | 0.00 | 744.00 | 0.00 | -172575517.4 | 59.44 | 0.00 | 0.00 |
| September | 0.104590E+10 | -877503589.5 | 0.00 | 0.00 | 720.00 | 0.00 | -168398335.7 | 59.44 | 0.00 | 0.00 |
| October | 0.113591E+10 | -951671773.8 | 0.00 | 0.00 | 744.00 | 0.00 | -184234300.3 | 59.44 | 0.00 | 0.00 |
| November | 0.116101E+10 | -980501776.9 | 0.00 | 0.00 | 720.00 | 0.00 | -180509150.2 | 59.44 | 0.00 | 0.00 |
| December | 0.126141E+10 | -0.107481E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186603567.7 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.140730E+11 | -0.119339E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.213903E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.104590E+10 | -0.112133E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -186606421.5 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.130766E+10 | -877503589.5 | 0.00 | 0.00 | 744.00 | 0.00 | -168398335.7 | 59.44 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: G NE APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.130720E+10 | -0.112059E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186606421.5 | 59.44 | 0.00 | 0.00 |
| February | 0.119526E+10 | -0.102672E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -168542915.3 | 59.44 | 0.00 | 0.00 |
| March | 0.130763E+10 | -0.112133E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186299392.0 | 59.44 | 0.00 | 0.00 |
| April | 0.122299E+10 | -0.104253E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -180466837.6 | 59.44 | 0.00 | 0.00 |
| May | 0.119977E+10 | -0.101600E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -183772986.5 | 59.44 | 0.00 | 0.00 |
| June | 0.109174E+10 | -923295546.6 | 0.00 | 0.00 | 720.00 | 0.00 | -168447675.7 | 59.44 | 0.00 | 0.00 |
| July | 0.108078E+10 | -908255109.9 | 0.00 | 0.00 | 744.00 | 0.00 | -172522989.6 | 59.44 | 0.00 | 0.00 |
| August | 0.106331E+10 | -890735354.4 | 0.00 | 0.00 | 744.00 | 0.00 | -172575814.1 | 59.44 | 0.00 | 0.00 |
| September | 0.104576E+10 | -877501777.7 | 0.00 | 0.00 | 720.00 | 0.00 | -168262279.7 | 59.44 | 0.00 | 0.00 |
| October | 0.113580E+10 | -951675346.3 | 0.00 | 0.00 | 744.00 | 0.00 | -184127171.2 | 59.44 | 0.00 | 0.00 |
| November | 0.116100E+10 | -980499482.3 | 0.00 | 0.00 | 720.00 | 0.00 | -180504850.9 | 59.44 | 0.00 | 0.00 |
| December | 0.126141E+10 | -0.107481E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186603572.6 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.140727E+11 | -0.119339E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.213873E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.104576E+10 | -0.112133E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -186606421.5 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.130763E+10 | -877501777.7 | 0.00 | 0.00 | 744.00 | 0.00 | -168262279.7 | 59.44 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: G N1 APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.130720E+10 | -0.112059E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186606421.4 | 59.44 | 0.00 | 0.00 |
| February | 0.119526E+10 | -0.102672E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -168542915.2 | 59.44 | 0.00 | 0.00 |
| March | 0.130756E+10 | -0.112133E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186230341.3 | 59.44 | 0.00 | 0.00 |
| April | 0.122298E+10 | -0.104253E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -180451513.6 | 59.44 | 0.00 | 0.00 |
| May | 0.119911E+10 | -0.101600E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -183102784.7 | 59.44 | 0.00 | 0.00 |
| June | 0.109127E+10 | -923297693.5 | 0.00 | 0.00 | 720.00 | 0.00 | -167971159.4 | 59.44 | 0.00 | 0.00 |
| July | 0.108075E+10 | -908253165.6 | 0.00 | 0.00 | 744.00 | 0.00 | -172494603.7 | 59.44 | 0.00 | 0.00 |
| August | 0.106325E+10 | -890735254.8 | 0.00 | 0.00 | 744.00 | 0.00 | -172515291.0 | 59.44 | 0.00 | 0.00 |
| September | 0.104527E+10 | -877501256.7 | 0.00 | 0.00 | 720.00 | 0.00 | -167764094.7 | 59.44 | 0.00 | 0.00 |
| October | 0.113499E+10 | -951672889.7 | 0.00 | 0.00 | 744.00 | 0.00 | -183313009.4 | 59.44 | 0.00 | 0.00 |
| November | 0.116091E+10 | -980499570.8 | 0.00 | 0.00 | 720.00 | 0.00 | -180411457.2 | 59.44 | 0.00 | 0.00 |
| December | 0.126141E+10 | -0.107481E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186603538.4 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.140699E+11 | -0.119339E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.213601E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.104527E+10 | -0.112133E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -186606421.4 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.130756E+10 | -877501256.7 | 0.00 | 0.00 | 744.00 | 0.00 | -167764094.7 | 59.44 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: G N2 APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.130720E+10 | -0.112059E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186606421.4 | 59.44 | 0.00 | 0.00 |
| February | 0.119526E+10 | -0.102672E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -168542915.2 | 59.44 | 0.00 | 0.00 |
| March | 0.130756E+10 | -0.112133E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186226768.2 | 59.44 | 0.00 | 0.00 |
| April | 0.122298E+10 | -0.104253E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -180448890.1 | 59.44 | 0.00 | 0.00 |
| May | 0.119909E+10 | -0.101600E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -183091118.9 | 59.44 | 0.00 | 0.00 |
| June | 0.109128E+10 | -923297735.5 | 0.00 | 0.00 | 720.00 | 0.00 | -167978872.5 | 59.44 | 0.00 | 0.00 |
| July | 0.108075E+10 | -908253166.3 | 0.00 | 0.00 | 744.00 | 0.00 | -172494708.7 | 59.44 | 0.00 | 0.00 |
| August | 0.106325E+10 | -890735251.9 | 0.00 | 0.00 | 744.00 | 0.00 | -172515341.3 | 59.44 | 0.00 | 0.00 |
| September | 0.104526E+10 | -877501361.4 | 0.00 | 0.00 | 720.00 | 0.00 | -167756336.6 | 59.44 | 0.00 | 0.00 |
| October | 0.113497E+10 | -951673101.2 | 0.00 | 0.00 | 744.00 | 0.00 | -183292755.4 | 59.44 | 0.00 | 0.00 |
| November | 0.116091E+10 | -980499466.7 | 0.00 | 0.00 | 720.00 | 0.00 | -180410574.7 | 59.44 | 0.00 | 0.00 |
| December | 0.126141E+10 | -0.107481E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186603431.1 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.140699E+11 | -0.119339E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.213597E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.104526E+10 | -0.112133E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -186606421.4 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.130756E+10 | -877501361.4 | 0.00 | 0.00 | 744.00 | 0.00 | -167756336.6 | 59.44 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: G S1 APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.130719E+10 | -0.112059E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186605940.9 | 59.44 | 0.00 | 0.00 |
| February | 0.119526E+10 | -0.102672E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -168542918.4 | 59.44 | 0.00 | 0.00 |
| March | 0.130719E+10 | -0.112133E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -185859725.1 | 59.44 | 0.00 | 0.00 |
| April | 0.122206E+10 | -0.104253E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -179529883.6 | 59.44 | 0.00 | 0.00 |
| May | 0.119674E+10 | -0.101600E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -180736528.9 | 59.44 | 0.00 | 0.00 |
| June | 0.109087E+10 | -923301402.0 | 0.00 | 0.00 | 720.00 | 0.00 | -167569067.9 | 59.44 | 0.00 | 0.00 |
| July | 0.108075E+10 | -908256875.1 | 0.00 | 0.00 | 744.00 | 0.00 | -172491632.1 | 59.44 | 0.00 | 0.00 |
| August | 0.106323E+10 | -890734005.9 | 0.00 | 0.00 | 744.00 | 0.00 | -172495457.1 | 59.44 | 0.00 | 0.00 |
| September | 0.104468E+10 | -877498225.0 | 0.00 | 0.00 | 720.00 | 0.00 | -167180715.0 | 59.44 | 0.00 | 0.00 |
| October | 0.113080E+10 | -951674215.5 | 0.00 | 0.00 | 744.00 | 0.00 | -179124303.4 | 59.44 | 0.00 | 0.00 |
| November | 0.115972E+10 | -980499564.3 | 0.00 | 0.00 | 720.00 | 0.00 | -179216677.6 | 59.44 | 0.00 | 0.00 |
| December | 0.126141E+10 | -0.107481E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186601669.5 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.140599E+11 | -0.119339E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.212595E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.104468E+10 | -0.112133E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -186605940.9 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.130719E+10 | -877498225.0 | 0.00 | 0.00 | 744.00 | 0.00 | -167180715.0 | 59.44 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: G S2 APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.130720E+10 | -0.112059E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186606421.4 | 59.44 | 0.00 | 0.00 |
| February | 0.119526E+10 | -0.102672E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -168542915.3 | 59.44 | 0.00 | 0.00 |
| March | 0.130720E+10 | -0.112133E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -185868236.2 | 59.44 | 0.00 | 0.00 |
| April | 0.122209E+10 | -0.104253E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -179562884.6 | 59.44 | 0.00 | 0.00 |
| May | 0.119640E+10 | -0.101600E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -180404347.0 | 59.44 | 0.00 | 0.00 |
| June | 0.109076E+10 | -923299291.8 | 0.00 | 0.00 | 720.00 | 0.00 | -167455801.0 | 59.44 | 0.00 | 0.00 |
| July | 0.108074E+10 | -908249889.0 | 0.00 | 0.00 | 744.00 | 0.00 | -172491877.2 | 59.44 | 0.00 | 0.00 |
| August | 0.106323E+10 | -890734265.6 | 0.00 | 0.00 | 744.00 | 0.00 | -172492725.2 | 59.44 | 0.00 | 0.00 |
| September | 0.104463E+10 | -877501425.0 | 0.00 | 0.00 | 720.00 | 0.00 | -167125054.3 | 59.44 | 0.00 | 0.00 |
| October | 0.113056E+10 | -951672660.3 | 0.00 | 0.00 | 744.00 | 0.00 | -178887749.1 | 59.44 | 0.00 | 0.00 |
| November | 0.115976E+10 | -980500629.1 | 0.00 | 0.00 | 720.00 | 0.00 | -179255885.8 | 59.44 | 0.00 | 0.00 |
| December | 0.126141E+10 | -0.107481E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186603577.0 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.140592E+11 | -0.119339E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.212530E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.104463E+10 | -0.112133E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -186606421.4 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.130720E+10 | -877501425.0 | 0.00 | 0.00 | 744.00 | 0.00 | -167125054.3 | 59.44 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: M SW APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.242776E+10 | -0.224119E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186579701.4 | 59.44 | 0.00 | 0.00 |
| February | 0.222196E+10 | -0.205344E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -168519800.6 | 59.44 | 0.00 | 0.00 |
| March | 0.242742E+10 | -0.224267E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -184757173.3 | 59.44 | 0.00 | 0.00 |
| April | 0.226101E+10 | -0.208506E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -175950003.7 | 59.44 | 0.00 | 0.00 |
| May | 0.220632E+10 | -0.203201E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -174317548.5 | 59.44 | 0.00 | 0.00 |
| June | 0.201374E+10 | -0.184661E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -167130888.7 | 59.44 | 0.00 | 0.00 |
| July | 0.198900E+10 | -0.181651E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172488529.6 | 59.44 | 0.00 | 0.00 |
| August | 0.195398E+10 | -0.178147E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172511317.5 | 59.44 | 0.00 | 0.00 |
| September | 0.192249E+10 | -0.175501E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -167477989.8 | 59.44 | 0.00 | 0.00 |
| October | 0.208347E+10 | -0.190335E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -180111447.4 | 59.44 | 0.00 | 0.00 |
| November | 0.214021E+10 | -0.196101E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -179206884.5 | 59.44 | 0.00 | 0.00 |
| December | 0.233620E+10 | -0.214962E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186576124.8 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.259836E+11 | -0.238679E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.211563E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.192249E+10 | -0.224267E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -186579701.4 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.242776E+10 | -0.175501E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -167130888.7 | 59.44 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: M NW APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.242779E+10 | -0.224119E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186604904.2 | 59.44 | 0.00 | 0.00 |
| February | 0.222199E+10 | -0.205344E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -168545512.9 | 59.44 | 0.00 | 0.00 |
| March | 0.242796E+10 | -0.224266E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -185301369.8 | 59.44 | 0.00 | 0.00 |
| April | 0.226345E+10 | -0.208506E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -178392656.3 | 59.44 | 0.00 | 0.00 |
| May | 0.220721E+10 | -0.203201E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -175203855.3 | 59.44 | 0.00 | 0.00 |
| June | 0.201376E+10 | -0.184661E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -167152964.0 | 59.44 | 0.00 | 0.00 |
| July | 0.198900E+10 | -0.181651E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172487354.6 | 59.44 | 0.00 | 0.00 |
| August | 0.195399E+10 | -0.178147E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172518338.2 | 59.44 | 0.00 | 0.00 |
| September | 0.192297E+10 | -0.175501E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -167956818.6 | 59.44 | 0.00 | 0.00 |
| October | 0.208655E+10 | -0.190335E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -183195547.4 | 59.44 | 0.00 | 0.00 |
| November | 0.214136E+10 | -0.196101E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -180349747.0 | 59.44 | 0.00 | 0.00 |
| December | 0.233622E+10 | -0.214962E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186602684.4 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.259922E+11 | -0.238679E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.212431E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.192297E+10 | -0.224266E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -186604904.2 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.242796E+10 | -0.175501E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -167152964.0 | 59.44 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: M SE APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.242777E+10 | -0.224119E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186586374.0 | 59.44 | 0.00 | 0.00 |
| February | 0.222198E+10 | -0.205344E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -168537367.0 | 59.44 | 0.00 | 0.00 |
| March | 0.242746E+10 | -0.224267E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -184790926.3 | 59.44 | 0.00 | 0.00 |
| April | 0.226085E+10 | -0.208506E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -175786859.7 | 59.44 | 0.00 | 0.00 |
| May | 0.220623E+10 | -0.203201E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -174222772.5 | 59.44 | 0.00 | 0.00 |
| June | 0.201371E+10 | -0.184661E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -167105258.0 | 59.44 | 0.00 | 0.00 |
| July | 0.198900E+10 | -0.181651E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172487675.4 | 59.44 | 0.00 | 0.00 |
| August | 0.195398E+10 | -0.178147E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172508915.1 | 59.44 | 0.00 | 0.00 |
| September | 0.192249E+10 | -0.175501E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -167484406.6 | 59.44 | 0.00 | 0.00 |
| October | 0.208320E+10 | -0.190335E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -179845476.0 | 59.44 | 0.00 | 0.00 |
| November | 0.214018E+10 | -0.196101E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -179169141.5 | 59.44 | 0.00 | 0.00 |
| December | 0.233620E+10 | -0.214962E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186577141.2 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.259830E+11 | -0.238679E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.211510E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.192249E+10 | -0.224267E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -186586374.0 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.242777E+10 | -0.175501E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -167105258.0 | 59.44 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: M NE APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.242779E+10 | -0.224119E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186604904.2 | 59.44 | 0.00 | 0.00 |
| February | 0.222199E+10 | -0.205344E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -168545512.9 | 59.44 | 0.00 | 0.00 |
| March | 0.242793E+10 | -0.224266E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -185263698.6 | 59.44 | 0.00 | 0.00 |
| April | 0.226322E+10 | -0.208506E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -178162104.8 | 59.44 | 0.00 | 0.00 |
| May | 0.220701E+10 | -0.203201E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -175002720.8 | 59.44 | 0.00 | 0.00 |
| June | 0.201373E+10 | -0.184660E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -167125464.4 | 59.44 | 0.00 | 0.00 |
| July | 0.198900E+10 | -0.181651E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172493383.3 | 59.44 | 0.00 | 0.00 |
| August | 0.195398E+10 | -0.178147E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172515197.8 | 59.44 | 0.00 | 0.00 |
| September | 0.192290E+10 | -0.175501E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -167889707.0 | 59.44 | 0.00 | 0.00 |
| October | 0.208641E+10 | -0.190335E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -183061191.9 | 59.44 | 0.00 | 0.00 |
| November | 0.214134E+10 | -0.196101E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -180331537.0 | 59.44 | 0.00 | 0.00 |
| December | 0.233622E+10 | -0.214962E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186602834.1 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.259915E+11 | -0.238679E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.212360E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.192290E+10 | -0.224266E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -186604904.2 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.242793E+10 | -0.175501E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -167125464.4 | 59.44 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: M N1 APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.242779E+10 | -0.224119E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186604904.1 | 59.44 | 0.00 | 0.00 |
| February | 0.222199E+10 | -0.205344E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -168545512.8 | 59.44 | 0.00 | 0.00 |
| March | 0.242768E+10 | -0.224266E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -185014960.4 | 59.44 | 0.00 | 0.00 |
| April | 0.226294E+10 | -0.208506E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -177880305.1 | 59.44 | 0.00 | 0.00 |
| May | 0.220638E+10 | -0.203200E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -174379540.7 | 59.44 | 0.00 | 0.00 |
| June | 0.201364E+10 | -0.184660E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -167035870.3 | 59.44 | 0.00 | 0.00 |
| July | 0.198900E+10 | -0.181651E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172492379.0 | 59.44 | 0.00 | 0.00 |
| August | 0.195396E+10 | -0.178147E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172494155.9 | 59.44 | 0.00 | 0.00 |
| September | 0.192242E+10 | -0.175501E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -167407928.1 | 59.44 | 0.00 | 0.00 |
| October | 0.208517E+10 | -0.190335E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -181814386.1 | 59.44 | 0.00 | 0.00 |
| November | 0.214111E+10 | -0.196101E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -180102892.8 | 59.44 | 0.00 | 0.00 |
| December | 0.233622E+10 | -0.214962E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186603653.6 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.259883E+11 | -0.238679E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.212038E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.192242E+10 | -0.224266E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -186604904.1 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.242779E+10 | -0.175501E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -167035870.3 | 59.44 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: M N2 APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.242779E+10 | -0.224119E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186604904.1 | 59.44 | 0.00 | 0.00 |
| February | 0.222199E+10 | -0.205344E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -168545512.8 | 59.44 | 0.00 | 0.00 |
| March | 0.242768E+10 | -0.224266E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -185012641.5 | 59.44 | 0.00 | 0.00 |
| April | 0.226290E+10 | -0.208506E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -177837736.8 | 59.44 | 0.00 | 0.00 |
| May | 0.220637E+10 | -0.203200E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -174364669.2 | 59.44 | 0.00 | 0.00 |
| June | 0.201364E+10 | -0.184660E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -167035441.0 | 59.44 | 0.00 | 0.00 |
| July | 0.198900E+10 | -0.181651E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172492382.0 | 59.44 | 0.00 | 0.00 |
| August | 0.195396E+10 | -0.178147E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172494121.9 | 59.44 | 0.00 | 0.00 |
| September | 0.192242E+10 | -0.175501E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -167407734.0 | 59.44 | 0.00 | 0.00 |
| October | 0.208514E+10 | -0.190335E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -181787755.7 | 59.44 | 0.00 | 0.00 |
| November | 0.214111E+10 | -0.196101E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -180100403.6 | 59.44 | 0.00 | 0.00 |
| December | 0.233622E+10 | -0.214962E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186603627.6 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.259882E+11 | -0.238679E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.212029E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.192242E+10 | -0.224266E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -186604904.1 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.242779E+10 | -0.175501E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -167035441.0 | 59.44 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: M S1 APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.242772E+10 | -0.224118E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186535915.3 | 59.44 | 0.00 | 0.00 |
| February | 0.222191E+10 | -0.205344E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -168468328.7 | 59.44 | 0.00 | 0.00 |
| March | 0.242682E+10 | -0.224267E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -184150909.6 | 59.44 | 0.00 | 0.00 |
| April | 0.225976E+10 | -0.208506E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -174695863.0 | 59.44 | 0.00 | 0.00 |
| May | 0.220548E+10 | -0.203200E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -173477947.8 | 59.44 | 0.00 | 0.00 |
| June | 0.201362E+10 | -0.184660E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -167021151.9 | 59.44 | 0.00 | 0.00 |
| July | 0.198900E+10 | -0.181651E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172492230.4 | 59.44 | 0.00 | 0.00 |
| August | 0.195396E+10 | -0.178147E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172492793.5 | 59.44 | 0.00 | 0.00 |
| September | 0.192212E+10 | -0.175501E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -167108540.2 | 59.44 | 0.00 | 0.00 |
| October | 0.208112E+10 | -0.190335E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -177770445.8 | 59.44 | 0.00 | 0.00 |
| November | 0.213900E+10 | -0.196101E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -177994890.2 | 59.44 | 0.00 | 0.00 |
| December | 0.233613E+10 | -0.214962E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186515708.7 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.259766E+11 | -0.238679E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.210872E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.192212E+10 | -0.224267E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -186535915.3 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.242772E+10 | -0.175501E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -167021151.9 | 59.44 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: M S2 APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.242772E+10 | -0.224118E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186536264.4 | 59.44 | 0.00 | 0.00 |
| February | 0.222191E+10 | -0.205344E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -168468252.1 | 59.44 | 0.00 | 0.00 |
| March | 0.242682E+10 | -0.224267E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -184151577.0 | 59.44 | 0.00 | 0.00 |
| April | 0.225974E+10 | -0.208507E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -174676880.4 | 59.44 | 0.00 | 0.00 |
| May | 0.220548E+10 | -0.203200E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -173478115.8 | 59.44 | 0.00 | 0.00 |
| June | 0.201362E+10 | -0.184660E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -167021358.5 | 59.44 | 0.00 | 0.00 |
| July | 0.198900E+10 | -0.181651E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172492206.4 | 59.44 | 0.00 | 0.00 |
| August | 0.195396E+10 | -0.178147E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172492819.2 | 59.44 | 0.00 | 0.00 |
| September | 0.192212E+10 | -0.175501E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -167110308.4 | 59.44 | 0.00 | 0.00 |
| October | 0.208109E+10 | -0.190335E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -177744308.2 | 59.44 | 0.00 | 0.00 |
| November | 0.213899E+10 | -0.196101E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -177987678.5 | 59.44 | 0.00 | 0.00 |
| December | 0.233613E+10 | -0.214962E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186515096.6 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.259766E+11 | -0.238679E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.210867E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.192212E+10 | -0.224267E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -186536264.4 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.242772E+10 | -0.175501E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -167021358.5 | 59.44 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: T SW APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.130716E+10 | -0.112059E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186568260.8 | 59.44 | 0.00 | 0.00 |
| February | 0.119522E+10 | -0.102672E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -168505448.5 | 59.44 | 0.00 | 0.00 |
| March | 0.130646E+10 | -0.112133E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -185128420.1 | 59.44 | 0.00 | 0.00 |
| April | 0.121997E+10 | -0.104253E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -177444977.4 | 59.44 | 0.00 | 0.00 |
| May | 0.119472E+10 | -0.101600E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -178717435.4 | 59.44 | 0.00 | 0.00 |
| June | 0.109201E+10 | -923299520.1 | 0.00 | 0.00 | 720.00 | 0.00 | -168711934.6 | 59.44 | 0.00 | 0.00 |
| July | 0.108111E+10 | -908255272.8 | 0.00 | 0.00 | 744.00 | 0.00 | -172857789.6 | 59.44 | 0.00 | 0.00 |
| August | 0.106397E+10 | -890735019.8 | 0.00 | 0.00 | 744.00 | 0.00 | -173238630.7 | 59.44 | 0.00 | 0.00 |
| September | 0.104788E+10 | -877500019.7 | 0.00 | 0.00 | 720.00 | 0.00 | -170378989.3 | 59.44 | 0.00 | 0.00 |
| October | 0.113462E+10 | -951675285.5 | 0.00 | 0.00 | 744.00 | 0.00 | -182945642.8 | 59.44 | 0.00 | 0.00 |
| November | 0.116023E+10 | -980501369.7 | 0.00 | 0.00 | 720.00 | 0.00 | -179731336.2 | 59.44 | 0.00 | 0.00 |
| December | 0.126137E+10 | -0.107481E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186564714.8 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.140647E+11 | -0.119339E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.213079E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.104788E+10 | -0.112133E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -186568260.8 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.130716E+10 | -877500019.7 | 0.00 | 0.00 | 744.00 | 0.00 | -168505448.5 | 59.44 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: T NW APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.130720E+10 | -0.112059E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186606421.7 | 59.44 | 0.00 | 0.00 |
| February | 0.119526E+10 | -0.102672E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -168542915.4 | 59.44 | 0.00 | 0.00 |
| March | 0.130697E+10 | -0.112133E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -185643480.4 | 59.44 | 0.00 | 0.00 |
| April | 0.122117E+10 | -0.104253E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -178643990.2 | 59.44 | 0.00 | 0.00 |
| May | 0.119548E+10 | -0.101600E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -179478072.7 | 59.44 | 0.00 | 0.00 |
| June | 0.109204E+10 | -923299169.4 | 0.00 | 0.00 | 720.00 | 0.00 | -168741783.2 | 59.44 | 0.00 | 0.00 |
| July | 0.108106E+10 | -908255376.0 | 0.00 | 0.00 | 744.00 | 0.00 | -172806953.7 | 59.44 | 0.00 | 0.00 |
| August | 0.106405E+10 | -890734777.6 | 0.00 | 0.00 | 744.00 | 0.00 | -173313187.7 | 59.44 | 0.00 | 0.00 |
| September | 0.104894E+10 | -877503118.7 | 0.00 | 0.00 | 720.00 | 0.00 | -171432211.7 | 59.44 | 0.00 | 0.00 |
| October | 0.113657E+10 | -951673240.0 | 0.00 | 0.00 | 744.00 | 0.00 | -184901436.7 | 59.44 | 0.00 | 0.00 |
| November | 0.116098E+10 | -980502423.9 | 0.00 | 0.00 | 720.00 | 0.00 | -180472843.0 | 59.44 | 0.00 | 0.00 |
| December | 0.126141E+10 | -0.107481E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186602085.3 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.140711E+11 | -0.119339E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.213719E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.104894E+10 | -0.112133E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -186606421.7 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.130720E+10 | -877503118.7 | 0.00 | 0.00 | 744.00 | 0.00 | -168542915.4 | 59.44 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: T SE APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.130717E+10 | -0.112059E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186580308.4 | 59.44 | 0.00 | 0.00 |
| February | 0.119525E+10 | -0.102672E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -168527694.3 | 59.44 | 0.00 | 0.00 |
| March | 0.130647E+10 | -0.112133E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -185134764.8 | 59.44 | 0.00 | 0.00 |
| April | 0.121983E+10 | -0.104253E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -177300178.4 | 59.44 | 0.00 | 0.00 |
| May | 0.119437E+10 | -0.101600E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -178366097.0 | 59.44 | 0.00 | 0.00 |
| June | 0.109183E+10 | -923299054.1 | 0.00 | 0.00 | 720.00 | 0.00 | -168532700.2 | 59.44 | 0.00 | 0.00 |
| July | 0.108103E+10 | -908251947.2 | 0.00 | 0.00 | 744.00 | 0.00 | -172780521.8 | 59.44 | 0.00 | 0.00 |
| August | 0.106390E+10 | -890735658.9 | 0.00 | 0.00 | 744.00 | 0.00 | -173162818.4 | 59.44 | 0.00 | 0.00 |
| September | 0.104766E+10 | -877501474.8 | 0.00 | 0.00 | 720.00 | 0.00 | -170159475.7 | 59.44 | 0.00 | 0.00 |
| October | 0.113441E+10 | -951673261.1 | 0.00 | 0.00 | 744.00 | 0.00 | -182737932.0 | 59.44 | 0.00 | 0.00 |
| November | 0.116023E+10 | -980501846.3 | 0.00 | 0.00 | 720.00 | 0.00 | -179724197.9 | 59.44 | 0.00 | 0.00 |
| December | 0.126137E+10 | -0.107481E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186566490.0 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.140635E+11 | -0.119339E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.212957E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.104766E+10 | -0.112133E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -186580308.4 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.130717E+10 | -877501474.8 | 0.00 | 0.00 | 744.00 | 0.00 | -168527694.3 | 59.44 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: T NE APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.130720E+10 | -0.112059E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186606421.6 | 59.44 | 0.00 | 0.00 |
| February | 0.119526E+10 | -0.102672E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -168542915.4 | 59.44 | 0.00 | 0.00 |
| March | 0.130694E+10 | -0.112133E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -185611602.5 | 59.44 | 0.00 | 0.00 |
| April | 0.122101E+10 | -0.104253E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -178478183.3 | 59.44 | 0.00 | 0.00 |
| May | 0.119495E+10 | -0.101600E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -178945436.4 | 59.44 | 0.00 | 0.00 |
| June | 0.109182E+10 | -923298985.3 | 0.00 | 0.00 | 720.00 | 0.00 | -168524380.0 | 59.44 | 0.00 | 0.00 |
| July | 0.108102E+10 | -908256776.1 | 0.00 | 0.00 | 744.00 | 0.00 | -172761213.2 | 59.44 | 0.00 | 0.00 |
| August | 0.106398E+10 | -890734834.5 | 0.00 | 0.00 | 744.00 | 0.00 | -173247080.5 | 59.44 | 0.00 | 0.00 |
| September | 0.104849E+10 | -877500857.5 | 0.00 | 0.00 | 720.00 | 0.00 | -170990964.4 | 59.44 | 0.00 | 0.00 |
| October | 0.113658E+10 | -951673403.7 | 0.00 | 0.00 | 744.00 | 0.00 | -184906126.8 | 59.44 | 0.00 | 0.00 |
| November | 0.116097E+10 | -980503310.9 | 0.00 | 0.00 | 720.00 | 0.00 | -180464103.8 | 59.44 | 0.00 | 0.00 |
| December | 0.126141E+10 | -0.107481E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186601689.3 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.140696E+11 | -0.119339E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.213568E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.104849E+10 | -0.112133E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -186606421.6 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.130720E+10 | -877500857.5 | 0.00 | 0.00 | 744.00 | 0.00 | -168524380.0 | 59.44 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: T N1 APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.130720E+10 | -0.112059E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186606421.5 | 59.44 | 0.00 | 0.00 |
| February | 0.119526E+10 | -0.102672E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -168542915.3 | 59.44 | 0.00 | 0.00 |
| March | 0.130682E+10 | -0.112133E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -185486692.7 | 59.44 | 0.00 | 0.00 |
| April | 0.122123E+10 | -0.104253E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -178705685.1 | 59.44 | 0.00 | 0.00 |
| May | 0.119466E+10 | -0.101600E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -178656963.7 | 59.44 | 0.00 | 0.00 |
| June | 0.109156E+10 | -923298366.0 | 0.00 | 0.00 | 720.00 | 0.00 | -168262116.4 | 59.44 | 0.00 | 0.00 |
| July | 0.108091E+10 | -908252189.8 | 0.00 | 0.00 | 744.00 | 0.00 | -172656265.2 | 59.44 | 0.00 | 0.00 |
| August | 0.106370E+10 | -890733101.8 | 0.00 | 0.00 | 744.00 | 0.00 | -172970093.2 | 59.44 | 0.00 | 0.00 |
| September | 0.104802E+10 | -877501524.2 | 0.00 | 0.00 | 720.00 | 0.00 | -170515953.2 | 59.44 | 0.00 | 0.00 |
| October | 0.113625E+10 | -951676283.0 | 0.00 | 0.00 | 744.00 | 0.00 | -184575751.5 | 59.44 | 0.00 | 0.00 |
| November | 0.116088E+10 | -980501738.9 | 0.00 | 0.00 | 720.00 | 0.00 | -180379901.0 | 59.44 | 0.00 | 0.00 |
| December | 0.126141E+10 | -0.107481E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186601694.8 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.140679E+11 | -0.119339E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.213396E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.104802E+10 | -0.112133E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -186606421.5 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.130720E+10 | -877501524.2 | 0.00 | 0.00 | 744.00 | 0.00 | -168262116.4 | 59.44 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: T N2 APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.130720E+10 | -0.112059E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186606421.5 | 59.44 | 0.00 | 0.00 |
| February | 0.119526E+10 | -0.102672E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -168542915.3 | 59.44 | 0.00 | 0.00 |
| March | 0.130681E+10 | -0.112133E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -185483036.5 | 59.44 | 0.00 | 0.00 |
| April | 0.122120E+10 | -0.104253E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -178673610.8 | 59.44 | 0.00 | 0.00 |
| May | 0.119461E+10 | -0.101600E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -178607661.7 | 59.44 | 0.00 | 0.00 |
| June | 0.109155E+10 | -923296587.6 | 0.00 | 0.00 | 720.00 | 0.00 | -168251197.2 | 59.44 | 0.00 | 0.00 |
| July | 0.108091E+10 | -908256834.4 | 0.00 | 0.00 | 744.00 | 0.00 | -172650603.3 | 59.44 | 0.00 | 0.00 |
| August | 0.106370E+10 | -890734750.7 | 0.00 | 0.00 | 744.00 | 0.00 | -172969425.5 | 59.44 | 0.00 | 0.00 |
| September | 0.104798E+10 | -877502756.2 | 0.00 | 0.00 | 720.00 | 0.00 | -170477853.0 | 59.44 | 0.00 | 0.00 |
| October | 0.113624E+10 | -951674717.3 | 0.00 | 0.00 | 744.00 | 0.00 | -184565725.3 | 59.44 | 0.00 | 0.00 |
| November | 0.116088E+10 | -980502911.2 | 0.00 | 0.00 | 720.00 | 0.00 | -180377878.3 | 59.44 | 0.00 | 0.00 |
| December | 0.126141E+10 | -0.107481E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186600799.2 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.140678E+11 | -0.119339E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.213381E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.104798E+10 | -0.112133E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -186606421.5 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.130720E+10 | -877502756.2 | 0.00 | 0.00 | 744.00 | 0.00 | -168251197.2 | 59.44 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: T S1 APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.130713E+10 | -0.112059E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186545464.4 | 59.44 | 0.00 | 0.00 |
| February | 0.119519E+10 | -0.102672E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -168472080.1 | 59.44 | 0.00 | 0.00 |
| March | 0.130616E+10 | -0.112133E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -184825428.2 | 59.44 | 0.00 | 0.00 |
| April | 0.121956E+10 | -0.104253E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -177028029.9 | 59.44 | 0.00 | 0.00 |
| May | 0.119367E+10 | -0.101600E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -177667395.0 | 59.44 | 0.00 | 0.00 |
| June | 0.109152E+10 | -923303667.4 | 0.00 | 0.00 | 720.00 | 0.00 | -168215831.7 | 59.44 | 0.00 | 0.00 |
| July | 0.108095E+10 | -908250758.0 | 0.00 | 0.00 | 744.00 | 0.00 | -172697447.7 | 59.44 | 0.00 | 0.00 |
| August | 0.106364E+10 | -890734925.4 | 0.00 | 0.00 | 744.00 | 0.00 | -172905293.5 | 59.44 | 0.00 | 0.00 |
| September | 0.104693E+10 | -877500166.5 | 0.00 | 0.00 | 720.00 | 0.00 | -169424855.2 | 59.44 | 0.00 | 0.00 |
| October | 0.113364E+10 | -951674384.9 | 0.00 | 0.00 | 744.00 | 0.00 | -181962968.7 | 59.44 | 0.00 | 0.00 |
| November | 0.115980E+10 | -980502578.3 | 0.00 | 0.00 | 720.00 | 0.00 | -179294740.0 | 59.44 | 0.00 | 0.00 |
| December | 0.126133E+10 | -0.107481E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186522724.0 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.140595E+11 | -0.119339E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.212556E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.104693E+10 | -0.112133E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -186545464.4 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.130713E+10 | -877500166.5 | 0.00 | 0.00 | 744.00 | 0.00 | -168215831.7 | 59.44 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: T S2 APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.130713E+10 | -0.112059E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186545818.1 | 59.44 | 0.00 | 0.00 |
| February | 0.119519E+10 | -0.102672E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -168472276.0 | 59.44 | 0.00 | 0.00 |
| March | 0.130615E+10 | -0.112133E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -184817917.6 | 59.44 | 0.00 | 0.00 |
| April | 0.121954E+10 | -0.104253E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -177010615.7 | 59.44 | 0.00 | 0.00 |
| May | 0.119366E+10 | -0.101600E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -177654236.1 | 59.44 | 0.00 | 0.00 |
| June | 0.109151E+10 | -923297897.9 | 0.00 | 0.00 | 720.00 | 0.00 | -168217079.3 | 59.44 | 0.00 | 0.00 |
| July | 0.108095E+10 | -908252788.2 | 0.00 | 0.00 | 744.00 | 0.00 | -172697932.0 | 59.44 | 0.00 | 0.00 |
| August | 0.106364E+10 | -890734388.1 | 0.00 | 0.00 | 744.00 | 0.00 | -172904114.5 | 59.44 | 0.00 | 0.00 |
| September | 0.104692E+10 | -877499469.5 | 0.00 | 0.00 | 720.00 | 0.00 | -169418388.3 | 59.44 | 0.00 | 0.00 |
| October | 0.113362E+10 | -951674604.8 | 0.00 | 0.00 | 744.00 | 0.00 | -181941659.7 | 59.44 | 0.00 | 0.00 |
| November | 0.115979E+10 | -980501942.4 | 0.00 | 0.00 | 720.00 | 0.00 | -179292922.6 | 59.44 | 0.00 | 0.00 |
| December | 0.126133E+10 | -0.107481E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186525431.3 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.140594E+11 | -0.119339E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.212550E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.104692E+10 | -0.112133E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -186545818.1 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.130713E+10 | -877499469.5 | 0.00 | 0.00 | 744.00 | 0.00 | -168217079.3 | 59.44 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
| January | 255.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 262.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 339.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 371.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 332.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 430.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 439.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 406.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 289.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 314.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 258.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 230.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 3928.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 230.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 439.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT GSW HEATING COIL
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.416383E+10 | 2754.22 | 24-JAN-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.404625E+10 | 3257.44 | 07-FEB-08:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.242206E+10 | 2157.56 | 07-MAR-04:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.127086E+10 | 1880.85 | 16-APR-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.182497E+09 | 1083.78 | 13-MAY-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.203483E+09 | 952.27 | 30-OCT-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.119086E+10 | 1327.12 | 24-NOV-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.377383E+10 | 2640.67 | 26-DEC-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.172537E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.416383E+10 | 3257.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT GNW HEATING COIL
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.475079E+10 | 2890.64 | 12-JAN-09:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.456180E+10 | 3422.39 | 07-FEB-08:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.314821E+10 | 2576.40 | 07-MAR-08:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.167456E+10 | 1930.01 | 16-APR-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.292366E+09 | 1217.25 | 22-MAY-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.495900E+09 | 1046.74 | 30-OCT-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.163885E+10 | 1395.62 | 24-NOV-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.423267E+10 | 2733.45 | 26-DEC-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.207951E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.475079E+10 | 3422.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT OFFICE HEATING COIL
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.226485E+10 | 10161.51 | 03-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.229574E+10 | 10161.51 | 01-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.959692E+09 | 10161.51 | 01-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.217863E+09 | 10161.51 | 03-APR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 1152951.93 | 7297.83 | 01-MAY-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 3446009.03 | 10161.51 | 30-OCT-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.204436E+09 | 10161.51 | 14-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.183885E+10 | 10161.51 | 04-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.778603E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.229574E+10 | 10161.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT GNE HEATING COIL
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.470770E+10 | 2808.96 | 24-JAN-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.452916E+10 | 3338.58 | 07-FEB-08:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.315437E+10 | 2568.43 | 07-MAR-04:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.163320E+10 | 1871.56 | 16-APR-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.286535E+09 | 869.39 | 01-MAY-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.468932E+09 | 1065.81 | 30-OCT-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.162596E+10 | 1412.12 | 24-NOV-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.422726E+10 | 2721.85 | 26-DEC-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.206331E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.470770E+10 | 3338.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT GN1 HEATING COIL
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.338884E+10 | 2031.59 | 12-JAN-09:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.328338E+10 | 2504.12 | 07-FEB-08:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.224905E+10 | 1939.91 | 07-MAR-08:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.110685E+10 | 1314.98 | 16-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.142038E+09 | 562.15 | 01-MAY-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.234299E+09 | 720.10 | 17-OCT-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.103537E+10 | 1007.31 | 24-NOV-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.299307E+10 | 2005.94 | 11-DEC-08:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.144329E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.338884E+10 | 2504.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT GN2 HEATING COIL
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.338711E+10 | 2029.76 | 31-JAN-08:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.328209E+10 | 2503.69 | 07-FEB-08:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.224929E+10 | 1936.16 | 07-MAR-08:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.110500E+10 | 1313.22 | 16-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.142445E+09 | 565.62 | 01-MAY-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.233056E+09 | 719.55 | 17-OCT-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.103461E+10 | 1008.20 | 24-NOV-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.299282E+10 | 2005.29 | 11-DEC-08:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.144264E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.338711E+10 | 2503.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT GS1 HEATING COIL
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.282280E+10 | 1924.68 | 24-JAN-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.278191E+10 | 2340.46 | 07-FEB-08:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.154994E+10 | 1543.17 | 07-MAR-04:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.733286E+09 | 1263.46 | 16-APR-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 66034277.57 | 496.48 | 01-MAY-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 37934777.26 | 566.99 | 30-OCT-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.629204E+09 | 936.20 | 24-NOV-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.255101E+10 | 1865.78 | 26-DEC-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.111721E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.282280E+10 | 2340.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT GS2 HEATING COIL
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.310275E+10 | 2062.85 | 24-JAN-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.302689E+10 | 2474.18 | 07-FEB-08:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.170665E+10 | 1684.11 | 07-MAR-04:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.796205E+09 | 1362.39 | 16-APR-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 65402024.31 | 526.40 | 01-MAY-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 36364690.91 | 575.76 | 30-OCT-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.684076E+09 | 1028.71 | 24-NOV-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.278358E+10 | 2025.03 | 26-DEC-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.122019E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.310275E+10 | 2474.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT MSW HEATING COIL
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.699612E+10 | 5581.02 | 24-JAN-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.669065E+10 | 6244.10 | 06-FEB-10:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.280034E+10 | 3654.92 | 05-MAR-01:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.911471E+09 | 3130.32 | 16-APR-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.369399E+09 | 2106.04 | 30-OCT-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.217720E+10 | 2545.96 | 24-NOV-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.692669E+10 | 5426.18 | 26-DEC-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.268719E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.699612E+10 | 6244.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT MNW HEATING COIL
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.816938E+10 | 5814.57 | 12-JAN-09:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.770279E+10 | 6425.65 | 06-FEB-10:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.412958E+10 | 4181.32 | 06-MAR-09:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.132377E+10 | 3187.15 | 16-APR-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.871730E+09 | 2268.48 | 30-OCT-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.302388E+10 | 2672.64 | 24-NOV-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.783766E+10 | 5600.21 | 26-DEC-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.330588E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.816938E+10 | 6425.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT MSE HEATING COIL
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.690300E+10 | 5534.69 | 24-JAN-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.661555E+10 | 6169.66 | 06-FEB-10:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.280583E+10 | 3650.88 | 05-MAR-01:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.884238E+09 | 3102.38 | 16-APR-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.346844E+09 | 2148.36 | 30-OCT-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.215081E+10 | 2587.66 | 24-NOV-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.691178E+10 | 5411.09 | 26-DEC-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.266181E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.691178E+10 | 6169.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT MNE HEATING COIL
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.807546E+10 | 5659.71 | 24-JAN-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.763058E+10 | 6354.54 | 06-FEB-10:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.414633E+10 | 4282.24 | 07-MAR-04:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.128431E+10 | 3158.79 | 16-APR-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 772794.61 | 279.24 | 01-MAY-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.812388E+09 | 2315.13 | 30-OCT-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.299722E+10 | 2708.08 | 24-NOV-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.782359E+10 | 5586.11 | 26-DEC-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.327706E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.807546E+10 | 6354.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT MN1 HEATING COIL
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.536617E+10 | 3801.50 | 24-JAN-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.512853E+10 | 4303.61 | 06-FEB-10:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.271568E+10 | 3047.25 | 07-MAR-04:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.702144E+09 | 2075.87 | 16-APR-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.292978E+09 | 1460.94 | 30-OCT-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.162130E+10 | 1782.95 | 24-NOV-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.507974E+10 | 3709.77 | 26-DEC-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.209066E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.536617E+10 | 4303.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT MN2 HEATING COIL
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.536266E+10 | 3798.92 | 24-JAN-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.512597E+10 | 4301.76 | 06-FEB-10:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.271606E+10 | 3051.26 | 07-MAR-04:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.701067E+09 | 2074.19 | 16-APR-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.291682E+09 | 1463.18 | 30-OCT-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.161946E+10 | 1784.89 | 24-NOV-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.507922E+10 | 3709.37 | 26-DEC-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.208961E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.536266E+10 | 4301.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT MS1 HEATING COIL
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.423130E+10 | 3647.15 | 24-JAN-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.414340E+10 | 4079.67 | 06-FEB-10:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.142538E+10 | 2498.99 | 07-MAR-04:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.385865E+09 | 2004.58 | 16-APR-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 47738333.05 | 1144.05 | 30-OCT-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.920705E+09 | 1696.55 | 24-NOV-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.420086E+10 | 3557.93 | 26-DEC-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.153553E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.423130E+10 | 4079.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT MS2 HEATING COIL
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.422754E+10 | 3644.14 | 24-JAN-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.414070E+10 | 4078.49 | 07-FEB-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.142738E+10 | 2501.47 | 07-MAR-04:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.385952E+09 | 2002.94 | 16-APR-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 47222570.56 | 1145.27 | 30-OCT-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.920100E+09 | 1698.19 | 24-NOV-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.420036E+10 | 3557.59 | 26-DEC-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.153493E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.422754E+10 | 4078.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT TSW HEATING COIL
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.572669E+10 | 4296.57 | 24-JAN-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.538314E+10 | 4673.00 | 06-FEB-10:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.290525E+10 | 3210.88 | 07-MAR-04:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.140672E+10 | 2592.42 | 16-APR-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.184094E+09 | 1194.74 | 22-MAY-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 21053804.34 | 751.29 | 14-JUN-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 69102494.78 | 910.28 | 30-SEP-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.107997E+10 | 2068.79 | 30-OCT-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.246124E+10 | 2246.64 | 24-NOV-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.563672E+10 | 4286.48 | 26-DEC-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.248740E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.572669E+10 | 4673.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT TNW HEATING COIL
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.635325E+10 | 4368.37 | 12-JAN-09:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.591842E+10 | 4687.48 | 06-FEB-10:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.358027E+10 | 3393.32 | 07-MAR-04:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.164536E+10 | 2616.11 | 16-APR-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.207731E+09 | 1018.30 | 07-MAY-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 17262168.55 | 733.15 | 14-JUN-04:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 92933199.64 | 963.72 | 30-SEP-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.141117E+10 | 2115.25 | 30-OCT-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.287883E+10 | 2266.60 | 24-NOV-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.611501E+10 | 4312.55 | 26-DEC-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.282202E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.635325E+10 | 4687.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT TSE HEATING COIL
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.567376E+10 | 4281.47 | 24-JAN-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.533917E+10 | 4627.71 | 06-FEB-10:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.290829E+10 | 3270.06 | 07-MAR-04:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.137750E+10 | 2574.32 | 16-APR-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.177355E+09 | 988.30 | 07-MAY-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 19660790.88 | 804.09 | 14-JUN-04:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 70185626.88 | 949.73 | 30-SEP-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.105287E+10 | 2093.99 | 30-OCT-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.244474E+10 | 2261.32 | 24-NOV-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.562778E+10 | 4276.23 | 26-DEC-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.246913E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.567376E+10 | 4627.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT TNE HEATING COIL
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.630036E+10 | 4303.80 | 24-JAN-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.587579E+10 | 4642.71 | 06-FEB-10:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.358517E+10 | 3452.64 | 07-MAR-04:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.160793E+10 | 2597.76 | 16-APR-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.202514E+09 | 1066.71 | 07-MAY-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 18917472.24 | 805.48 | 14-JUN-04:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 92438482.86 | 998.92 | 30-SEP-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.136325E+10 | 2140.35 | 30-OCT-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.286307E+10 | 2282.09 | 24-NOV-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.610668E+10 | 4301.73 | 26-DEC-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.280161E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.630036E+10 | 4642.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT TN1 HEATING COIL
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.461357E+10 | 3125.96 | 24-JAN-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.430009E+10 | 3398.57 | 07-FEB-08:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.262870E+10 | 2632.19 | 07-MAR-04:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.110478E+10 | 1818.38 | 16-APR-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 91739659.44 | 691.28 | 07-MAY-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 3489824.85 | 358.90 | 14-JUN-04:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 36554296.58 | 627.27 | 30-SEP-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.899852E+09 | 1562.95 | 17-OCT-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.196341E+10 | 1704.53 | 24-NOV-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.439678E+10 | 3110.40 | 26-DEC-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.200390E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.461357E+10 | 3398.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT TN2 HEATING COIL
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.461163E+10 | 3125.28 | 24-JAN-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.429870E+10 | 3397.03 | 07-FEB-08:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.262972E+10 | 2635.54 | 07-MAR-04:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.110428E+10 | 1817.17 | 16-APR-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 92866934.10 | 694.69 | 07-MAY-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 3688864.44 | 368.96 | 14-JUN-04:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 36843562.77 | 631.70 | 30-SEP-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.898919E+09 | 1564.64 | 17-OCT-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.196277E+10 | 1704.83 | 24-NOV-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.439656E+10 | 3111.34 | 26-DEC-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.200360E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.461163E+10 | 3397.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT TS1 HEATING COIL
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.398951E+10 | 3101.92 | 24-JAN-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.376831E+10 | 3362.17 | 07-FEB-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.196054E+10 | 2437.91 | 07-MAR-04:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.873599E+09 | 1793.10 | 16-APR-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 70344281.28 | 562.35 | 07-MAY-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 4801706.58 | 377.13 | 14-JUN-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 24892815.77 | 569.18 | 30-SEP-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.619708E+09 | 1478.29 | 30-OCT-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.157434E+10 | 1681.57 | 24-NOV-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.392143E+10 | 3090.54 | 26-DEC-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.168075E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.398951E+10 | 3362.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT TS2 HEATING COIL
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.398747E+10 | 3101.17 | 24-JAN-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.376695E+10 | 3363.21 | 07-FEB-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.196240E+10 | 2441.53 | 07-MAR-04:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.874845E+09 | 1791.80 | 16-APR-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 71402996.19 | 567.64 | 07-MAY-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 4930680.69 | 386.50 | 14-JUN-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 25136787.14 | 573.18 | 30-SEP-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.619336E+09 | 1480.90 | 30-OCT-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.157428E+10 | 1682.56 | 24-NOV-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.392128E+10 | 3089.49 | 26-DEC-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.168080E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.398747E+10 | 3363.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT GSW COOLING COIL
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 1032688.59 | 1013805.67 | 118.37 | 15-MAR-16:30 | 116.07 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 21210952.10 | 20345034.23 | 555.69 | 14-MAY-15:10 | 459.09 | 0.00 |
| June | 0.00 | 0.00 | 0.121814E+10 | 0.100363E+10 | 2409.24 | 27-JUN-16:40 | 1765.04 | 0.00 |
| July | 0.00 | 0.00 | 0.291949E+10 | 0.228672E+10 | 2681.16 | 19-JUL-15:10 | 2126.36 | 0.00 |
| August | 0.00 | 0.00 | 0.263024E+10 | 0.223698E+10 | 3043.56 | 13-AUG-15:30 | 2363.58 | 0.00 |
| September | 0.00 | 0.00 | 0.135054E+10 | 0.117581E+10 | 2454.74 | 21-SEP-16:10 | 2387.20 | 0.00 |
| October | 0.00 | 0.00 | 44656957.56 | 43404672.53 | 1220.95 | 11-OCT-16:07 | 1220.95 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.818531E+10 | 0.676791E+10 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.291949E+10 | 0.228672E+10 | 3043.56 | 2387.20 | 0.00 |
Report: CoilReportMonthly
For: SPLIT GNW COOLING COIL
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 404426.17 | 403092.76 | 126.77 | 31-MAY-18:00 | 126.30 | 0.00 |
| June | 0.00 | 0.00 | 0.102517E+10 | 0.827677E+09 | 2320.38 | 27-JUN-17:10 | 1662.21 | 0.00 |
| July | 0.00 | 0.00 | 0.259042E+10 | 0.199798E+10 | 2398.12 | 20-JUL-16:02 | 1751.57 | 0.00 |
| August | 0.00 | 0.00 | 0.211101E+10 | 0.176258E+10 | 2505.76 | 13-AUG-15:30 | 1880.97 | 0.00 |
| September | 0.00 | 0.00 | 0.676624E+09 | 0.551057E+09 | 1785.79 | 16-SEP-16:10 | 1500.27 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.640363E+10 | 0.513970E+10 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.259042E+10 | 0.199798E+10 | 2505.76 | 1880.97 | 0.00 |
Report: CoilReportMonthly
For: SPLIT OFFICE COOLING COIL
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 16902764.45 | 15830166.37 | 906.82 | 15-MAR-14:20 | 883.67 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.203090E+09 | 0.191735E+09 | 2078.21 | 24-MAY-08:65 | 1624.75 | 0.00 |
| June | 0.00 | 0.00 | 0.130037E+10 | 0.111526E+10 | 6968.50 | 27-JUN-07:03 | 4593.65 | 0.00 |
| July | 0.00 | 0.00 | 0.208649E+10 | 0.174080E+10 | 7207.60 | 21-JUL-07:02 | 4100.30 | 0.00 |
| August | 0.00 | 0.00 | 0.217351E+10 | 0.189852E+10 | 7148.04 | 14-AUG-07:02 | 4262.71 | 0.00 |
| September | 0.00 | 0.00 | 0.129492E+10 | 0.117142E+10 | 6810.17 | 14-SEP-08:62 | 4548.44 | 0.00 |
| October | 0.00 | 0.00 | 0.227398E+09 | 0.216871E+09 | 3542.95 | 12-OCT-08:63 | 3320.27 | 0.00 |
| November | 0.00 | 0.00 | 1394366.58 | 1394366.58 | 215.00 | 01-NOV-12:50 | 215.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.730408E+10 | 0.635183E+10 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.217351E+10 | 0.189852E+10 | 7207.60 | 4593.65 | 0.00 |
Report: CoilReportMonthly
For: SPLIT GNE COOLING COIL
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.981350E+09 | 0.787559E+09 | 2051.73 | 27-JUN-13:00 | 1507.57 | 0.00 |
| July | 0.00 | 0.00 | 0.260142E+10 | 0.200735E+10 | 2348.11 | 20-JUL-16:02 | 1713.17 | 0.00 |
| August | 0.00 | 0.00 | 0.209754E+10 | 0.175045E+10 | 2216.26 | 13-AUG-16:05 | 1620.95 | 0.00 |
| September | 0.00 | 0.00 | 0.689213E+09 | 0.560392E+09 | 1585.35 | 16-SEP-16:10 | 1325.10 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.636953E+10 | 0.510575E+10 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.260142E+10 | 0.200735E+10 | 2348.11 | 1713.17 | 0.00 |
Report: CoilReportMonthly
For: SPLIT GN1 COOLING COIL
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.868475E+09 | 0.689146E+09 | 1689.65 | 27-JUN-17:10 | 1171.25 | 0.00 |
| July | 0.00 | 0.00 | 0.228211E+10 | 0.173848E+10 | 1998.21 | 20-JUL-16:02 | 1444.42 | 0.00 |
| August | 0.00 | 0.00 | 0.183972E+10 | 0.151577E+10 | 1879.04 | 13-AUG-16:05 | 1371.22 | 0.00 |
| September | 0.00 | 0.00 | 0.633418E+09 | 0.506817E+09 | 1364.73 | 16-SEP-16:10 | 1135.04 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.562373E+10 | 0.445021E+10 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.228211E+10 | 0.173848E+10 | 1998.21 | 1444.42 | 0.00 |
Report: CoilReportMonthly
For: SPLIT GN2 COOLING COIL
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.866994E+09 | 0.687824E+09 | 1681.18 | 27-JUN-17:10 | 1164.69 | 0.00 |
| July | 0.00 | 0.00 | 0.228327E+10 | 0.173939E+10 | 1997.79 | 20-JUL-16:02 | 1444.13 | 0.00 |
| August | 0.00 | 0.00 | 0.183931E+10 | 0.151538E+10 | 1871.10 | 13-AUG-16:05 | 1364.65 | 0.00 |
| September | 0.00 | 0.00 | 0.636822E+09 | 0.509826E+09 | 1363.31 | 16-SEP-16:10 | 1133.96 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.562640E+10 | 0.445242E+10 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.228327E+10 | 0.173939E+10 | 1997.79 | 1444.13 | 0.00 |
Report: CoilReportMonthly
For: SPLIT GS1 COOLING COIL
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 1761378.03 | 1732245.46 | 137.77 | 15-MAR-16:30 | 135.26 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 15844479.86 | 15226252.21 | 374.84 | 14-MAY-15:10 | 307.63 | 0.00 |
| June | 0.00 | 0.00 | 0.108096E+10 | 0.880314E+09 | 1982.60 | 27-JUN-13:00 | 1478.82 | 0.00 |
| July | 0.00 | 0.00 | 0.263171E+10 | 0.204292E+10 | 2141.08 | 20-JUL-13:30 | 1643.01 | 0.00 |
| August | 0.00 | 0.00 | 0.238631E+10 | 0.201316E+10 | 2356.52 | 13-AUG-15:30 | 1817.28 | 0.00 |
| September | 0.00 | 0.00 | 0.137296E+10 | 0.119234E+10 | 1941.58 | 21-SEP-15:10 | 1892.72 | 0.00 |
| October | 0.00 | 0.00 | 67367609.59 | 65186285.05 | 1030.87 | 11-OCT-15:10 | 1030.87 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.755692E+10 | 0.621089E+10 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.263171E+10 | 0.204292E+10 | 2356.52 | 1892.72 | 0.00 |
Report: CoilReportMonthly
For: SPLIT GS2 COOLING COIL
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 1610262.51 | 1584210.36 | 130.96 | 15-MAR-16:20 | 128.61 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 23892882.29 | 23127876.16 | 404.45 | 14-MAY-15:10 | 333.04 | 0.00 |
| June | 0.00 | 0.00 | 0.119460E+10 | 0.978815E+09 | 2055.35 | 27-JUN-13:00 | 1545.50 | 0.00 |
| July | 0.00 | 0.00 | 0.287636E+10 | 0.225264E+10 | 2239.62 | 15-JUL-14:10 | 1594.72 | 0.00 |
| August | 0.00 | 0.00 | 0.261987E+10 | 0.222197E+10 | 2492.54 | 13-AUG-15:20 | 1949.27 | 0.00 |
| September | 0.00 | 0.00 | 0.151415E+10 | 0.132102E+10 | 2014.06 | 16-SEP-13:30 | 1729.65 | 0.00 |
| October | 0.00 | 0.00 | 79216186.77 | 76558995.15 | 1059.03 | 11-OCT-15:10 | 1059.03 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.830969E+10 | 0.687571E+10 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.287636E+10 | 0.225264E+10 | 2492.54 | 1949.27 | 0.00 |
Report: CoilReportMonthly
For: SPLIT MSW COOLING COIL
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.136795E+09 | 0.129490E+09 | 3149.73 | 15-MAR-13:50 | 3146.46 | 0.00 |
| April | 0.00 | 0.00 | 0.150564E+09 | 0.150535E+09 | 2052.34 | 09-APR-16:03 | 2052.34 | 0.00 |
| May | 0.00 | 0.00 | 0.141156E+10 | 0.137251E+10 | 4620.40 | 14-MAY-14:30 | 4053.58 | 0.00 |
| June | 0.00 | 0.00 | 0.495205E+10 | 0.424057E+10 | 6713.03 | 27-JUN-16:23 | 5104.21 | 0.00 |
| July | 0.00 | 0.00 | 0.808663E+10 | 0.648019E+10 | 6886.68 | 15-JUL-15:10 | 5231.87 | 0.00 |
| August | 0.00 | 0.00 | 0.669653E+10 | 0.574096E+10 | 7595.29 | 13-AUG-15:30 | 5956.59 | 0.00 |
| September | 0.00 | 0.00 | 0.358682E+10 | 0.316178E+10 | 6217.18 | 21-SEP-16:10 | 6067.17 | 0.00 |
| October | 0.00 | 0.00 | 0.299865E+09 | 0.291645E+09 | 4135.17 | 11-OCT-16:10 | 4135.17 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.253208E+11 | 0.215677E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.808663E+10 | 0.648019E+10 | 7595.29 | 6067.17 | 0.00 |
Report: CoilReportMonthly
For: SPLIT MNW COOLING COIL
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 44049262.37 | 42593701.90 | 1728.25 | 15-MAR-17:10 | 1677.23 | 0.00 |
| April | 0.00 | 0.00 | 857810.16 | 857810.16 | 524.49 | 09-APR-16:20 | 524.49 | 0.00 |
| May | 0.00 | 0.00 | 0.815690E+09 | 0.788425E+09 | 3477.24 | 14-MAY-15:10 | 3047.37 | 0.00 |
| June | 0.00 | 0.00 | 0.448615E+10 | 0.379512E+10 | 6517.82 | 27-JUN-17:10 | 4886.28 | 0.00 |
| July | 0.00 | 0.00 | 0.739812E+10 | 0.585729E+10 | 6249.91 | 11-JUL-18:00 | 5085.76 | 0.00 |
| August | 0.00 | 0.00 | 0.559953E+10 | 0.472053E+10 | 6348.67 | 13-AUG-15:30 | 4821.98 | 0.00 |
| September | 0.00 | 0.00 | 0.205505E+10 | 0.171910E+10 | 4469.11 | 16-SEP-16:10 | 3793.85 | 0.00 |
| October | 0.00 | 0.00 | 3732081.57 | 3717365.35 | 621.28 | 11-OCT-16:30 | 619.13 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.204032E+11 | 0.169276E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.739812E+10 | 0.585729E+10 | 6517.82 | 5085.76 | 0.00 |
Report: CoilReportMonthly
For: SPLIT MSE COOLING COIL
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.150056E+09 | 0.141670E+09 | 3184.02 | 15-MAR-13:40 | 3180.55 | 0.00 |
| April | 0.00 | 0.00 | 0.181032E+09 | 0.180932E+09 | 1782.31 | 22-APR-13:40 | 1782.31 | 0.00 |
| May | 0.00 | 0.00 | 0.140961E+10 | 0.137108E+10 | 3964.79 | 14-MAY-14:10 | 3432.59 | 0.00 |
| June | 0.00 | 0.00 | 0.485786E+10 | 0.415096E+10 | 6498.50 | 27-JUN-13:00 | 5066.71 | 0.00 |
| July | 0.00 | 0.00 | 0.812646E+10 | 0.650874E+10 | 6458.17 | 20-JUL-13:00 | 5081.22 | 0.00 |
| August | 0.00 | 0.00 | 0.668989E+10 | 0.572747E+10 | 6641.15 | 13-AUG-15:20 | 5161.75 | 0.00 |
| September | 0.00 | 0.00 | 0.366182E+10 | 0.322852E+10 | 5546.90 | 16-SEP-13:30 | 4805.93 | 0.00 |
| October | 0.00 | 0.00 | 0.305880E+09 | 0.298508E+09 | 3559.92 | 11-OCT-12:40 | 3559.92 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.253826E+11 | 0.216079E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.812646E+10 | 0.650874E+10 | 6641.15 | 5161.75 | 0.00 |
Report: CoilReportMonthly
For: SPLIT MNE COOLING COIL
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 50059107.42 | 48280583.77 | 1622.68 | 15-MAR-16:20 | 1582.07 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.783817E+09 | 0.757257E+09 | 2885.78 | 14-MAY-15:10 | 2505.63 | 0.00 |
| June | 0.00 | 0.00 | 0.438910E+10 | 0.370351E+10 | 5663.18 | 27-JUN-13:00 | 4306.20 | 0.00 |
| July | 0.00 | 0.00 | 0.743706E+10 | 0.588519E+10 | 5864.46 | 20-JUL-16:02 | 4362.92 | 0.00 |
| August | 0.00 | 0.00 | 0.559238E+10 | 0.470640E+10 | 5420.61 | 13-AUG-16:05 | 3996.47 | 0.00 |
| September | 0.00 | 0.00 | 0.210608E+10 | 0.176069E+10 | 3778.17 | 16-SEP-16:10 | 3173.18 | 0.00 |
| October | 0.00 | 0.00 | 240528.53 | 239991.57 | 143.06 | 05-OCT-16:08 | 143.06 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.203587E+11 | 0.168616E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.743706E+10 | 0.588519E+10 | 5864.46 | 4362.92 | 0.00 |
Report: CoilReportMonthly
For: SPLIT MN1 COOLING COIL
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 43200670.48 | 41260886.67 | 1316.22 | 15-MAR-17:10 | 1275.08 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.657872E+09 | 0.628217E+09 | 2451.05 | 14-MAY-15:10 | 2121.91 | 0.00 |
| June | 0.00 | 0.00 | 0.354560E+10 | 0.295202E+10 | 4379.97 | 27-JUN-17:15 | 3146.44 | 0.00 |
| July | 0.00 | 0.00 | 0.605459E+10 | 0.471361E+10 | 4739.06 | 20-JUL-16:02 | 3485.87 | 0.00 |
| August | 0.00 | 0.00 | 0.463856E+10 | 0.385475E+10 | 4415.96 | 13-AUG-16:05 | 3250.13 | 0.00 |
| September | 0.00 | 0.00 | 0.185335E+10 | 0.152387E+10 | 3145.57 | 16-SEP-16:10 | 2630.18 | 0.00 |
| October | 0.00 | 0.00 | 3108617.00 | 3068554.48 | 256.19 | 05-OCT-16:06 | 256.19 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.167963E+11 | 0.137168E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.605459E+10 | 0.471361E+10 | 4739.06 | 3485.87 | 0.00 |
Report: CoilReportMonthly
For: SPLIT MN2 COOLING COIL
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 44203032.59 | 42196836.28 | 1324.37 | 15-MAR-17:10 | 1282.94 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.662179E+09 | 0.632368E+09 | 2435.33 | 14-MAY-15:10 | 2107.61 | 0.00 |
| June | 0.00 | 0.00 | 0.354382E+10 | 0.295048E+10 | 4358.55 | 27-JUN-17:15 | 3129.28 | 0.00 |
| July | 0.00 | 0.00 | 0.605682E+10 | 0.471531E+10 | 4738.92 | 20-JUL-16:02 | 3485.93 | 0.00 |
| August | 0.00 | 0.00 | 0.463890E+10 | 0.385483E+10 | 4397.71 | 13-AUG-16:05 | 3234.92 | 0.00 |
| September | 0.00 | 0.00 | 0.185971E+10 | 0.152957E+10 | 3138.74 | 16-SEP-16:10 | 2624.47 | 0.00 |
| October | 0.00 | 0.00 | 3335822.15 | 3288582.75 | 267.30 | 05-OCT-16:06 | 267.30 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.168090E+11 | 0.137280E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.605682E+10 | 0.471531E+10 | 4738.92 | 3485.93 | 0.00 |
Report: CoilReportMonthly
For: SPLIT MS1 COOLING COIL
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.152621E+09 | 0.143527E+09 | 2825.42 | 15-MAR-13:40 | 2817.85 | 0.00 |
| April | 0.00 | 0.00 | 0.140351E+09 | 0.140244E+09 | 1667.21 | 09-APR-16:03 | 1667.21 | 0.00 |
| May | 0.00 | 0.00 | 0.128635E+10 | 0.124239E+10 | 3525.93 | 14-MAY-14:10 | 3053.00 | 0.00 |
| June | 0.00 | 0.00 | 0.402062E+10 | 0.340218E+10 | 5094.80 | 27-JUN-13:00 | 3912.68 | 0.00 |
| July | 0.00 | 0.00 | 0.675715E+10 | 0.534140E+10 | 5217.46 | 15-JUL-14:10 | 3771.76 | 0.00 |
| August | 0.00 | 0.00 | 0.575324E+10 | 0.488513E+10 | 5535.22 | 13-AUG-15:20 | 4320.93 | 0.00 |
| September | 0.00 | 0.00 | 0.347300E+10 | 0.304923E+10 | 4804.20 | 21-SEP-14:10 | 4667.91 | 0.00 |
| October | 0.00 | 0.00 | 0.438793E+09 | 0.424671E+09 | 3399.71 | 11-OCT-14:30 | 3399.71 | 0.00 |
| November | 0.00 | 0.00 | 2051508.60 | 2051508.60 | 325.01 | 01-NOV-12:30 | 325.01 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.220242E+11 | 0.186308E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.675715E+10 | 0.534140E+10 | 5535.22 | 4667.91 | 0.00 |
Report: CoilReportMonthly
For: SPLIT MS2 COOLING COIL
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.153346E+09 | 0.144201E+09 | 2835.86 | 15-MAR-13:40 | 2828.08 | 0.00 |
| April | 0.00 | 0.00 | 0.146065E+09 | 0.145944E+09 | 1688.71 | 09-APR-16:03 | 1688.71 | 0.00 |
| May | 0.00 | 0.00 | 0.129121E+10 | 0.124717E+10 | 3516.79 | 14-MAY-14:10 | 3044.57 | 0.00 |
| June | 0.00 | 0.00 | 0.401909E+10 | 0.340085E+10 | 5107.23 | 27-JUN-13:00 | 3924.56 | 0.00 |
| July | 0.00 | 0.00 | 0.675949E+10 | 0.534319E+10 | 5211.83 | 15-JUL-14:10 | 3767.31 | 0.00 |
| August | 0.00 | 0.00 | 0.575380E+10 | 0.488536E+10 | 5521.96 | 13-AUG-15:20 | 4309.64 | 0.00 |
| September | 0.00 | 0.00 | 0.347710E+10 | 0.305278E+10 | 4811.09 | 21-SEP-14:10 | 4674.75 | 0.00 |
| October | 0.00 | 0.00 | 0.445092E+09 | 0.430798E+09 | 3413.87 | 11-OCT-14:30 | 3413.87 | 0.00 |
| November | 0.00 | 0.00 | 2247010.84 | 2247010.84 | 345.43 | 01-NOV-12:00 | 345.43 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.220474E+11 | 0.186525E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.675949E+10 | 0.534319E+10 | 5521.96 | 4674.75 | 0.00 |
Report: CoilReportMonthly
For: SPLIT TSW COOLING COIL
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.110085E+09 | 0.103947E+09 | 2516.43 | 15-MAR-13:50 | 2516.09 | 0.00 |
| April | 0.00 | 0.00 | 0.192316E+09 | 0.192053E+09 | 1615.63 | 22-APR-15:00 | 1615.63 | 0.00 |
| May | 0.00 | 0.00 | 0.666824E+09 | 0.651046E+09 | 3133.97 | 14-MAY-14:30 | 2784.26 | 0.00 |
| June | 0.00 | 0.00 | 0.249142E+10 | 0.214625E+10 | 4343.95 | 27-JUN-16:23 | 3402.79 | 0.00 |
| July | 0.00 | 0.00 | 0.427648E+10 | 0.346192E+10 | 4564.93 | 19-JUL-15:10 | 3752.90 | 0.00 |
| August | 0.00 | 0.00 | 0.337590E+10 | 0.292455E+10 | 4903.93 | 13-AUG-15:30 | 3914.70 | 0.00 |
| September | 0.00 | 0.00 | 0.156693E+10 | 0.138423E+10 | 3879.33 | 21-SEP-15:30 | 3811.64 | 0.00 |
| October | 0.00 | 0.00 | 0.200094E+09 | 0.197283E+09 | 2715.04 | 11-OCT-15:30 | 2715.04 | 0.00 |
| November | 0.00 | 0.00 | 1105309.90 | 1105309.90 | 197.13 | 03-NOV-15:10 | 197.13 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.128812E+11 | 0.110624E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.427648E+10 | 0.346192E+10 | 4903.93 | 3914.70 | 0.00 |
Report: CoilReportMonthly
For: SPLIT TNW COOLING COIL
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 58415971.21 | 55100320.17 | 1565.54 | 15-MAR-16:30 | 1532.07 | 0.00 |
| April | 0.00 | 0.00 | 20877389.52 | 20802587.07 | 595.03 | 09-APR-16:03 | 595.03 | 0.00 |
| May | 0.00 | 0.00 | 0.389164E+09 | 0.377993E+09 | 2400.75 | 14-MAY-15:10 | 2134.03 | 0.00 |
| June | 0.00 | 0.00 | 0.225051E+10 | 0.191200E+10 | 4212.32 | 27-JUN-16:40 | 3246.16 | 0.00 |
| July | 0.00 | 0.00 | 0.391641E+10 | 0.312909E+10 | 4097.61 | 19-JUL-15:10 | 3288.32 | 0.00 |
| August | 0.00 | 0.00 | 0.281438E+10 | 0.239642E+10 | 4147.30 | 13-AUG-15:30 | 3216.22 | 0.00 |
| September | 0.00 | 0.00 | 0.859417E+09 | 0.713635E+09 | 2888.60 | 16-SEP-16:10 | 2488.64 | 0.00 |
| October | 0.00 | 0.00 | 13143563.95 | 13063859.61 | 1039.46 | 11-OCT-16:30 | 1035.26 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.103223E+11 | 0.861810E+10 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.391641E+10 | 0.312909E+10 | 4212.32 | 3288.32 | 0.00 |
Report: CoilReportMonthly
For: SPLIT TSE COOLING COIL
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.116795E+09 | 0.109932E+09 | 2502.24 | 15-MAR-13:50 | 2502.24 | 0.00 |
| April | 0.00 | 0.00 | 0.188665E+09 | 0.188624E+09 | 1462.93 | 22-APR-14:00 | 1462.93 | 0.00 |
| May | 0.00 | 0.00 | 0.623881E+09 | 0.609346E+09 | 2726.82 | 14-MAY-14:10 | 2389.73 | 0.00 |
| June | 0.00 | 0.00 | 0.242725E+10 | 0.208242E+10 | 4379.38 | 27-JUN-13:00 | 3499.07 | 0.00 |
| July | 0.00 | 0.00 | 0.429335E+10 | 0.346921E+10 | 4291.92 | 21-JUL-13:30 | 3741.99 | 0.00 |
| August | 0.00 | 0.00 | 0.336519E+10 | 0.290768E+10 | 4273.88 | 13-AUG-15:20 | 3378.57 | 0.00 |
| September | 0.00 | 0.00 | 0.157676E+10 | 0.139017E+10 | 3644.56 | 16-SEP-13:30 | 3199.14 | 0.00 |
| October | 0.00 | 0.00 | 0.191540E+09 | 0.189508E+09 | 2337.26 | 11-OCT-12:40 | 2337.26 | 0.00 |
| November | 0.00 | 0.00 | 11620.04 | 11620.04 | 19.37 | 03-NOV-14:40 | 19.37 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.127834E+11 | 0.109469E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.429335E+10 | 0.346921E+10 | 4379.38 | 3741.99 | 0.00 |
Report: CoilReportMonthly
For: SPLIT TNE COOLING COIL
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 63073528.00 | 59197207.67 | 1434.56 | 15-MAR-16:20 | 1404.26 | 0.00 |
| April | 0.00 | 0.00 | 6370889.47 | 6370889.47 | 386.85 | 08-APR-13:00 | 386.85 | 0.00 |
| May | 0.00 | 0.00 | 0.319302E+09 | 0.309730E+09 | 1995.26 | 14-MAY-15:10 | 1758.09 | 0.00 |
| June | 0.00 | 0.00 | 0.218345E+10 | 0.184481E+10 | 3810.92 | 27-JUN-13:00 | 2972.81 | 0.00 |
| July | 0.00 | 0.00 | 0.394083E+10 | 0.314254E+10 | 3725.38 | 21-JUL-10:30 | 2972.06 | 0.00 |
| August | 0.00 | 0.00 | 0.280628E+10 | 0.238161E+10 | 3515.58 | 13-AUG-15:20 | 2685.37 | 0.00 |
| September | 0.00 | 0.00 | 0.829763E+09 | 0.680320E+09 | 2476.51 | 16-SEP-13:00 | 2109.24 | 0.00 |
| October | 0.00 | 0.00 | 8746408.86 | 8699994.96 | 488.87 | 11-OCT-16:10 | 488.46 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.101578E+11 | 0.843328E+10 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.394083E+10 | 0.314254E+10 | 3810.92 | 2972.81 | 0.00 |
Report: CoilReportMonthly
For: SPLIT TN1 COOLING COIL
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 48136796.01 | 45315479.95 | 1206.24 | 15-MAR-16:30 | 1178.73 | 0.00 |
| April | 0.00 | 0.00 | 1085936.39 | 1085936.39 | 365.62 | 09-APR-16:03 | 365.62 | 0.00 |
| May | 0.00 | 0.00 | 0.212419E+09 | 0.204106E+09 | 1688.05 | 14-MAY-15:10 | 1483.55 | 0.00 |
| June | 0.00 | 0.00 | 0.175342E+10 | 0.146034E+10 | 2930.96 | 27-JUN-13:00 | 2254.31 | 0.00 |
| July | 0.00 | 0.00 | 0.324449E+10 | 0.255131E+10 | 2969.20 | 20-JUL-16:02 | 2254.13 | 0.00 |
| August | 0.00 | 0.00 | 0.231893E+10 | 0.194241E+10 | 2856.55 | 13-AUG-16:05 | 2165.97 | 0.00 |
| September | 0.00 | 0.00 | 0.671910E+09 | 0.535859E+09 | 2002.92 | 16-SEP-16:10 | 1703.25 | 0.00 |
| October | 0.00 | 0.00 | 3706297.88 | 3676721.89 | 331.19 | 11-OCT-16:10 | 330.95 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.825409E+10 | 0.674411E+10 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.324449E+10 | 0.255131E+10 | 2969.20 | 2254.31 | 0.00 |
Report: CoilReportMonthly
For: SPLIT TN2 COOLING COIL
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 48827218.91 | 45946904.17 | 1208.71 | 15-MAR-16:30 | 1181.19 | 0.00 |
| April | 0.00 | 0.00 | 1284824.33 | 1284824.33 | 363.64 | 09-APR-16:03 | 363.64 | 0.00 |
| May | 0.00 | 0.00 | 0.214901E+09 | 0.206592E+09 | 1677.64 | 14-MAY-15:10 | 1474.28 | 0.00 |
| June | 0.00 | 0.00 | 0.175411E+10 | 0.146118E+10 | 2944.63 | 27-JUN-13:00 | 2267.70 | 0.00 |
| July | 0.00 | 0.00 | 0.324746E+10 | 0.255400E+10 | 2967.23 | 20-JUL-16:02 | 2252.79 | 0.00 |
| August | 0.00 | 0.00 | 0.232099E+10 | 0.194429E+10 | 2840.62 | 13-AUG-15:20 | 2178.58 | 0.00 |
| September | 0.00 | 0.00 | 0.675978E+09 | 0.539563E+09 | 1991.33 | 16-SEP-16:10 | 1693.12 | 0.00 |
| October | 0.00 | 0.00 | 3842203.02 | 3811506.98 | 327.32 | 11-OCT-16:03 | 327.32 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.826739E+10 | 0.675666E+10 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.324746E+10 | 0.255400E+10 | 2967.23 | 2267.70 | 0.00 |
Report: CoilReportMonthly
For: SPLIT TS1 COOLING COIL
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.102473E+09 | 96516134.05 | 2206.24 | 15-MAR-13:50 | 2204.50 | 0.00 |
| April | 0.00 | 0.00 | 0.135108E+09 | 0.135026E+09 | 1196.28 | 22-APR-14:10 | 1196.28 | 0.00 |
| May | 0.00 | 0.00 | 0.473434E+09 | 0.459879E+09 | 2427.40 | 14-MAY-14:10 | 2129.79 | 0.00 |
| June | 0.00 | 0.00 | 0.199143E+10 | 0.169127E+10 | 3497.06 | 27-JUN-13:00 | 2775.92 | 0.00 |
| July | 0.00 | 0.00 | 0.360716E+10 | 0.288513E+10 | 3508.84 | 21-JUL-13:30 | 3043.14 | 0.00 |
| August | 0.00 | 0.00 | 0.288943E+10 | 0.247707E+10 | 3609.04 | 13-AUG-15:20 | 2886.28 | 0.00 |
| September | 0.00 | 0.00 | 0.141518E+10 | 0.123757E+10 | 3126.17 | 16-SEP-13:30 | 2742.33 | 0.00 |
| October | 0.00 | 0.00 | 0.187934E+09 | 0.185146E+09 | 2082.98 | 11-OCT-14:30 | 2082.98 | 0.00 |
| November | 0.00 | 0.00 | 1553071.29 | 1553071.29 | 210.26 | 03-NOV-14:30 | 210.26 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.108037E+11 | 0.916917E+10 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.360716E+10 | 0.288513E+10 | 3609.04 | 3043.14 | 0.00 |
Report: CoilReportMonthly
For: SPLIT TS2 COOLING COIL
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.103218E+09 | 97204879.04 | 2214.32 | 15-MAR-13:50 | 2212.63 | 0.00 |
| April | 0.00 | 0.00 | 0.139341E+09 | 0.139267E+09 | 1221.74 | 22-APR-14:10 | 1221.74 | 0.00 |
| May | 0.00 | 0.00 | 0.479399E+09 | 0.465845E+09 | 2424.30 | 14-MAY-14:10 | 2127.21 | 0.00 |
| June | 0.00 | 0.00 | 0.199337E+10 | 0.169340E+10 | 3510.99 | 27-JUN-13:00 | 2789.78 | 0.00 |
| July | 0.00 | 0.00 | 0.361038E+10 | 0.288813E+10 | 3519.41 | 21-JUL-13:30 | 3053.89 | 0.00 |
| August | 0.00 | 0.00 | 0.289153E+10 | 0.247903E+10 | 3597.22 | 13-AUG-15:20 | 2876.20 | 0.00 |
| September | 0.00 | 0.00 | 0.142048E+10 | 0.124263E+10 | 3133.12 | 16-SEP-13:30 | 2749.63 | 0.00 |
| October | 0.00 | 0.00 | 0.190829E+09 | 0.188041E+09 | 2090.81 | 11-OCT-14:30 | 2090.81 | 0.00 |
| November | 0.00 | 0.00 | 1748436.46 | 1748436.46 | 228.69 | 03-NOV-14:30 | 228.69 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.108303E+11 | 0.919530E+10 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.361038E+10 | 0.288813E+10 | 3597.22 | 3053.89 | 0.00 |
Report: FanReportMonthly
For: SPLIT GSW SUPPLY FAN
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.181936E+09 | 0.95 | 120.34 | 24-JAN-06:00 | 0.95 |
| February | 0.176798E+09 | 0.95 | 142.33 | 07-FEB-08:12 | 0.95 |
| March | 0.105913E+09 | 0.86 | 94.27 | 07-MAR-04:55 | 0.95 |
| April | 55529606.32 | 0.73 | 82.18 | 16-APR-07:00 | 0.94 |
| May | 9664433.10 | 0.26 | 47.35 | 13-MAY-07:02 | 0.94 |
| June | 90990194.26 | 0.65 | 170.61 | 27-JUN-16:40 | 1.02 |
| July | 0.214116E+09 | 1.01 | 194.84 | 19-JUL-15:10 | 1.01 |
| August | 0.196002E+09 | 1.00 | 216.76 | 13-AUG-15:30 | 1.00 |
| September | 0.101862E+09 | 0.78 | 182.96 | 21-SEP-16:10 | 1.02 |
| October | 12388402.58 | 0.29 | 94.41 | 11-OCT-16:07 | 1.06 |
| November | 52033796.52 | 0.74 | 57.99 | 24-NOV-04:00 | 0.94 |
| December | 0.164895E+09 | 0.94 | 115.38 | 26-DEC-08:00 | 0.95 |
| Annual Sum or Average | 0.136213E+10 | 0.76 | |||
| Minimum of Months | 9664433.10 | 0.26 | 47.35 | 0.94 | |
| Maximum of Months | 0.214116E+09 | 1.01 | 216.76 | 1.06 |
Report: FanReportMonthly
For: G SW APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.65 | 20.01 | 01-JAN-00:10 | 0.65 |
| February | 48400714.57 | 0.65 | 20.01 | 01-FEB-00:10 | 0.65 |
| March | 53586505.42 | 0.65 | 20.01 | 01-MAR-00:10 | 0.65 |
| April | 51857908.47 | 0.65 | 20.01 | 01-APR-00:10 | 0.65 |
| May | 53586505.42 | 0.65 | 20.01 | 01-MAY-00:10 | 0.65 |
| June | 51857908.47 | 0.64 | 20.01 | 01-JUN-00:10 | 0.64 |
| July | 53586505.42 | 0.64 | 20.01 | 01-JUL-00:10 | 0.64 |
| August | 53586505.42 | 0.64 | 20.01 | 01-AUG-00:10 | 0.64 |
| September | 51857908.47 | 0.64 | 20.01 | 01-SEP-00:10 | 0.64 |
| October | 53586505.42 | 0.65 | 20.01 | 01-OCT-00:10 | 0.64 |
| November | 51857908.47 | 0.65 | 20.01 | 01-NOV-00:10 | 0.65 |
| December | 53586505.42 | 0.65 | 20.01 | 01-DEC-00:10 | 0.65 |
| Annual Sum or Average | 0.630938E+09 | 0.65 | |||
| Minimum of Months | 48400714.57 | 0.64 | 20.01 | 0.64 | |
| Maximum of Months | 53586505.42 | 0.65 | 20.01 | 0.65 |
Report: FanReportMonthly
For: G SW APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.65 | 20.01 | 01-JAN-00:10 | 0.65 |
| February | 48400714.57 | 0.65 | 20.01 | 01-FEB-00:10 | 0.65 |
| March | 53586505.42 | 0.65 | 20.01 | 01-MAR-00:10 | 0.65 |
| April | 51857908.47 | 0.65 | 20.01 | 01-APR-00:10 | 0.65 |
| May | 53586505.42 | 0.65 | 20.01 | 01-MAY-00:10 | 0.64 |
| June | 51857908.47 | 0.64 | 20.01 | 01-JUN-00:10 | 0.64 |
| July | 53586505.42 | 0.64 | 20.01 | 01-JUL-00:10 | 0.65 |
| August | 53586505.42 | 0.64 | 20.01 | 01-AUG-00:10 | 0.64 |
| September | 51857908.47 | 0.64 | 20.01 | 01-SEP-00:10 | 0.64 |
| October | 53586505.42 | 0.65 | 20.01 | 01-OCT-00:10 | 0.64 |
| November | 51857908.47 | 0.65 | 20.01 | 01-NOV-00:10 | 0.65 |
| December | 53586505.42 | 0.65 | 20.01 | 01-DEC-00:10 | 0.65 |
| Annual Sum or Average | 0.630938E+09 | 0.65 | |||
| Minimum of Months | 48400714.57 | 0.64 | 20.01 | 0.64 | |
| Maximum of Months | 53586505.42 | 0.65 | 20.01 | 0.65 |
Report: FanReportMonthly
For: SPLIT GNW SUPPLY FAN
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.205857E+09 | 0.95 | 125.25 | 12-JAN-09:00 | 0.95 |
| February | 0.197667E+09 | 0.95 | 148.30 | 07-FEB-08:12 | 0.95 |
| March | 0.136415E+09 | 0.88 | 111.64 | 07-MAR-08:20 | 0.95 |
| April | 72560641.28 | 0.85 | 83.63 | 16-APR-07:00 | 0.94 |
| May | 12700653.67 | 0.34 | 52.74 | 22-MAY-06:01 | 0.94 |
| June | 75958091.66 | 0.58 | 162.68 | 27-JUN-17:10 | 1.02 |
| July | 0.188926E+09 | 1.01 | 172.02 | 19-JUL-15:10 | 1.02 |
| August | 0.156735E+09 | 0.96 | 178.36 | 13-AUG-15:30 | 1.01 |
| September | 50465505.63 | 0.53 | 130.93 | 16-SEP-16:10 | 1.04 |
| October | 21487885.70 | 0.48 | 45.36 | 30-OCT-05:00 | 0.94 |
| November | 71013063.94 | 0.88 | 60.47 | 24-NOV-04:00 | 0.94 |
| December | 0.183406E+09 | 0.94 | 118.44 | 26-DEC-08:00 | 0.95 |
| Annual Sum or Average | 0.137319E+10 | 0.78 | |||
| Minimum of Months | 12700653.67 | 0.34 | 45.36 | 0.94 | |
| Maximum of Months | 0.205857E+09 | 1.01 | 178.36 | 1.04 |
Report: FanReportMonthly
For: G NW APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.65 | 20.01 | 01-JAN-00:10 | 0.65 |
| February | 48400714.57 | 0.65 | 20.01 | 01-FEB-00:10 | 0.65 |
| March | 53586505.42 | 0.65 | 20.01 | 01-MAR-00:10 | 0.65 |
| April | 51857908.47 | 0.65 | 20.01 | 01-APR-00:10 | 0.65 |
| May | 53586505.42 | 0.65 | 20.01 | 01-MAY-00:10 | 0.65 |
| June | 51857908.47 | 0.64 | 20.01 | 01-JUN-00:10 | 0.64 |
| July | 53586505.42 | 0.64 | 20.01 | 01-JUL-00:10 | 0.64 |
| August | 53586505.42 | 0.64 | 20.01 | 01-AUG-00:10 | 0.64 |
| September | 51857908.47 | 0.64 | 20.01 | 01-SEP-00:10 | 0.64 |
| October | 53586505.42 | 0.65 | 20.01 | 01-OCT-00:10 | 0.64 |
| November | 51857908.47 | 0.65 | 20.01 | 01-NOV-00:10 | 0.65 |
| December | 53586505.42 | 0.65 | 20.01 | 01-DEC-00:10 | 0.65 |
| Annual Sum or Average | 0.630938E+09 | 0.65 | |||
| Minimum of Months | 48400714.57 | 0.64 | 20.01 | 0.64 | |
| Maximum of Months | 53586505.42 | 0.65 | 20.01 | 0.65 |
Report: FanReportMonthly
For: G NW APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.65 | 20.01 | 01-JAN-00:10 | 0.65 |
| February | 48400714.57 | 0.65 | 20.01 | 01-FEB-00:10 | 0.65 |
| March | 53586505.42 | 0.65 | 20.01 | 01-MAR-00:10 | 0.65 |
| April | 51857908.47 | 0.65 | 20.01 | 01-APR-00:10 | 0.65 |
| May | 53586505.42 | 0.65 | 20.01 | 01-MAY-00:10 | 0.64 |
| June | 51857908.47 | 0.64 | 20.01 | 01-JUN-00:10 | 0.64 |
| July | 53586505.42 | 0.64 | 20.01 | 01-JUL-00:10 | 0.65 |
| August | 53586505.42 | 0.64 | 20.01 | 01-AUG-00:10 | 0.64 |
| September | 51857908.47 | 0.64 | 20.01 | 01-SEP-00:10 | 0.64 |
| October | 53586505.42 | 0.65 | 20.01 | 01-OCT-00:10 | 0.64 |
| November | 51857908.47 | 0.65 | 20.01 | 01-NOV-00:10 | 0.65 |
| December | 53586505.42 | 0.65 | 20.01 | 01-DEC-00:10 | 0.65 |
| Annual Sum or Average | 0.630938E+09 | 0.65 | |||
| Minimum of Months | 48400714.57 | 0.64 | 20.01 | 0.64 | |
| Maximum of Months | 53586505.42 | 0.65 | 20.01 | 0.65 |
Report: FanReportMonthly
For: SPLIT OFFICE SUPPLY FAN
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.114110E+10 | 0.95 | 426.04 | 01-JAN-00:10 | 0.94 |
| February | 0.103067E+10 | 0.95 | 426.04 | 01-FEB-00:10 | 0.95 |
| March | 0.114110E+10 | 0.94 | 426.04 | 01-MAR-00:10 | 0.95 |
| April | 0.110429E+10 | 0.94 | 426.04 | 01-APR-00:10 | 0.94 |
| May | 0.114110E+10 | 0.94 | 426.04 | 01-MAY-00:10 | 0.94 |
| June | 0.110429E+10 | 0.93 | 426.04 | 01-JUN-00:10 | 0.94 |
| July | 0.114110E+10 | 0.93 | 426.04 | 01-JUL-00:10 | 0.94 |
| August | 0.114110E+10 | 0.93 | 426.04 | 01-AUG-00:10 | 0.93 |
| September | 0.110429E+10 | 0.93 | 426.04 | 01-SEP-00:10 | 0.93 |
| October | 0.114110E+10 | 0.94 | 426.04 | 01-OCT-00:10 | 0.94 |
| November | 0.110429E+10 | 0.94 | 426.04 | 01-NOV-00:10 | 0.94 |
| December | 0.114110E+10 | 0.94 | 426.04 | 01-DEC-00:10 | 0.94 |
| Annual Sum or Average | 0.134356E+11 | 0.94 | |||
| Minimum of Months | 0.103067E+10 | 0.93 | 426.04 | 0.93 | |
| Maximum of Months | 0.114110E+10 | 0.95 | 426.04 | 0.95 |
Report: FanReportMonthly
For: SPLIT GNE SUPPLY FAN
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.200653E+09 | 0.95 | 119.72 | 24-JAN-06:00 | 0.95 |
| February | 0.193043E+09 | 0.95 | 142.30 | 07-FEB-08:10 | 0.95 |
| March | 0.134446E+09 | 0.88 | 109.47 | 07-MAR-04:55 | 0.95 |
| April | 69610629.46 | 0.84 | 79.77 | 16-APR-07:00 | 0.94 |
| May | 12212749.38 | 0.32 | 37.06 | 01-MAY-05:00 | 0.94 |
| June | 71240789.27 | 0.58 | 144.58 | 27-JUN-13:00 | 1.02 |
| July | 0.185871E+09 | 1.01 | 162.75 | 20-JUL-16:02 | 1.01 |
| August | 0.152616E+09 | 0.96 | 154.08 | 13-AUG-16:05 | 1.02 |
| September | 50361064.80 | 0.58 | 114.20 | 16-SEP-16:10 | 1.04 |
| October | 19986949.33 | 0.47 | 45.43 | 30-OCT-05:00 | 0.94 |
| November | 69302046.50 | 0.88 | 60.19 | 24-NOV-04:00 | 0.94 |
| December | 0.180175E+09 | 0.94 | 116.01 | 26-DEC-08:00 | 0.95 |
| Annual Sum or Average | 0.133952E+10 | 0.78 | |||
| Minimum of Months | 12212749.38 | 0.32 | 37.06 | 0.94 | |
| Maximum of Months | 0.200653E+09 | 1.01 | 162.75 | 1.04 |
Report: FanReportMonthly
For: G NE APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.65 | 20.01 | 01-JAN-00:10 | 0.65 |
| February | 48400714.57 | 0.65 | 20.01 | 01-FEB-00:10 | 0.65 |
| March | 53586505.42 | 0.65 | 20.01 | 01-MAR-00:10 | 0.65 |
| April | 51857908.47 | 0.65 | 20.01 | 01-APR-00:10 | 0.65 |
| May | 53586505.42 | 0.65 | 20.01 | 01-MAY-00:10 | 0.65 |
| June | 51857908.47 | 0.64 | 20.01 | 01-JUN-00:10 | 0.64 |
| July | 53586505.42 | 0.64 | 20.01 | 01-JUL-00:10 | 0.64 |
| August | 53586505.42 | 0.64 | 20.01 | 01-AUG-00:10 | 0.64 |
| September | 51857908.47 | 0.64 | 20.01 | 01-SEP-00:10 | 0.64 |
| October | 53586505.42 | 0.65 | 20.01 | 01-OCT-00:10 | 0.64 |
| November | 51857908.47 | 0.65 | 20.01 | 01-NOV-00:10 | 0.65 |
| December | 53586505.42 | 0.65 | 20.01 | 01-DEC-00:10 | 0.65 |
| Annual Sum or Average | 0.630938E+09 | 0.65 | |||
| Minimum of Months | 48400714.57 | 0.64 | 20.01 | 0.64 | |
| Maximum of Months | 53586505.42 | 0.65 | 20.01 | 0.65 |
Report: FanReportMonthly
For: G NE APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.65 | 20.01 | 01-JAN-00:10 | 0.65 |
| February | 48400714.57 | 0.65 | 20.01 | 01-FEB-00:10 | 0.65 |
| March | 53586505.42 | 0.65 | 20.01 | 01-MAR-00:10 | 0.65 |
| April | 51857908.47 | 0.65 | 20.01 | 01-APR-00:10 | 0.65 |
| May | 53586505.42 | 0.65 | 20.01 | 01-MAY-00:10 | 0.64 |
| June | 51857908.47 | 0.64 | 20.01 | 01-JUN-00:10 | 0.64 |
| July | 53586505.42 | 0.64 | 20.01 | 01-JUL-00:10 | 0.65 |
| August | 53586505.42 | 0.64 | 20.01 | 01-AUG-00:10 | 0.64 |
| September | 51857908.47 | 0.64 | 20.01 | 01-SEP-00:10 | 0.64 |
| October | 53586505.42 | 0.65 | 20.01 | 01-OCT-00:10 | 0.64 |
| November | 51857908.47 | 0.65 | 20.01 | 01-NOV-00:10 | 0.65 |
| December | 53586505.42 | 0.65 | 20.01 | 01-DEC-00:10 | 0.65 |
| Annual Sum or Average | 0.630938E+09 | 0.65 | |||
| Minimum of Months | 48400714.57 | 0.64 | 20.01 | 0.64 | |
| Maximum of Months | 53586505.42 | 0.65 | 20.01 | 0.65 |
Report: FanReportMonthly
For: SPLIT GN1 SUPPLY FAN
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.142440E+09 | 0.95 | 85.39 | 12-JAN-09:00 | 0.95 |
| February | 0.138007E+09 | 0.95 | 105.25 | 07-FEB-08:12 | 0.95 |
| March | 94532365.28 | 0.85 | 81.54 | 07-MAR-08:20 | 0.95 |
| April | 46523236.09 | 0.83 | 55.27 | 16-APR-07:10 | 0.94 |
| May | 5970156.02 | 0.23 | 23.63 | 01-MAY-05:00 | 0.94 |
| June | 63065600.78 | 0.62 | 117.18 | 27-JUN-13:00 | 1.03 |
| July | 0.163110E+09 | 1.03 | 138.93 | 20-JUL-16:02 | 1.02 |
| August | 0.133972E+09 | 1.00 | 131.21 | 13-AUG-16:05 | 1.02 |
| September | 46189502.62 | 0.63 | 98.48 | 16-SEP-16:10 | 1.04 |
| October | 9848066.16 | 0.33 | 30.27 | 17-OCT-05:00 | 0.94 |
| November | 43518642.85 | 0.84 | 42.34 | 24-NOV-04:00 | 0.94 |
| December | 0.125805E+09 | 0.94 | 84.31 | 11-DEC-08:20 | 0.95 |
| Annual Sum or Average | 0.101298E+10 | 0.77 | |||
| Minimum of Months | 5970156.02 | 0.23 | 23.63 | 0.94 | |
| Maximum of Months | 0.163110E+09 | 1.03 | 138.93 | 1.04 |
Report: FanReportMonthly
For: G N1 APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.65 | 20.01 | 01-JAN-00:10 | 0.65 |
| February | 48400714.57 | 0.65 | 20.01 | 01-FEB-00:10 | 0.65 |
| March | 53586505.42 | 0.65 | 20.01 | 01-MAR-00:10 | 0.65 |
| April | 51857908.47 | 0.65 | 20.01 | 01-APR-00:10 | 0.65 |
| May | 53586505.42 | 0.65 | 20.01 | 01-MAY-00:10 | 0.65 |
| June | 51857908.47 | 0.64 | 20.01 | 01-JUN-00:10 | 0.64 |
| July | 53586505.42 | 0.64 | 20.01 | 01-JUL-00:10 | 0.64 |
| August | 53586505.42 | 0.64 | 20.01 | 01-AUG-00:10 | 0.64 |
| September | 51857908.47 | 0.64 | 20.01 | 01-SEP-00:10 | 0.64 |
| October | 53586505.42 | 0.65 | 20.01 | 01-OCT-00:10 | 0.64 |
| November | 51857908.47 | 0.65 | 20.01 | 01-NOV-00:10 | 0.65 |
| December | 53586505.42 | 0.65 | 20.01 | 01-DEC-00:10 | 0.65 |
| Annual Sum or Average | 0.630938E+09 | 0.65 | |||
| Minimum of Months | 48400714.57 | 0.64 | 20.01 | 0.64 | |
| Maximum of Months | 53586505.42 | 0.65 | 20.01 | 0.65 |
Report: FanReportMonthly
For: G N1 APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.65 | 20.01 | 01-JAN-00:10 | 0.65 |
| February | 48400714.57 | 0.65 | 20.01 | 01-FEB-00:10 | 0.65 |
| March | 53586505.42 | 0.65 | 20.01 | 01-MAR-00:10 | 0.65 |
| April | 51857908.47 | 0.65 | 20.01 | 01-APR-00:10 | 0.65 |
| May | 53586505.42 | 0.65 | 20.01 | 01-MAY-00:10 | 0.64 |
| June | 51857908.47 | 0.64 | 20.01 | 01-JUN-00:10 | 0.64 |
| July | 53586505.42 | 0.64 | 20.01 | 01-JUL-00:10 | 0.65 |
| August | 53586505.42 | 0.64 | 20.01 | 01-AUG-00:10 | 0.64 |
| September | 51857908.47 | 0.64 | 20.01 | 01-SEP-00:10 | 0.64 |
| October | 53586505.42 | 0.65 | 20.01 | 01-OCT-00:10 | 0.64 |
| November | 51857908.47 | 0.65 | 20.01 | 01-NOV-00:10 | 0.65 |
| December | 53586505.42 | 0.65 | 20.01 | 01-DEC-00:10 | 0.65 |
| Annual Sum or Average | 0.630938E+09 | 0.65 | |||
| Minimum of Months | 48400714.57 | 0.64 | 20.01 | 0.64 | |
| Maximum of Months | 53586505.42 | 0.65 | 20.01 | 0.65 |
Report: FanReportMonthly
For: SPLIT GN2 SUPPLY FAN
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.142312E+09 | 0.95 | 85.28 | 31-JAN-08:55 | 0.95 |
| February | 0.137900E+09 | 0.95 | 105.19 | 07-FEB-08:12 | 0.95 |
| March | 94505946.30 | 0.85 | 81.35 | 07-MAR-08:20 | 0.95 |
| April | 46427377.99 | 0.83 | 55.18 | 16-APR-07:10 | 0.94 |
| May | 5984945.48 | 0.23 | 23.77 | 01-MAY-05:00 | 0.94 |
| June | 62931619.54 | 0.62 | 117.40 | 27-JUN-13:00 | 1.03 |
| July | 0.163128E+09 | 1.03 | 138.84 | 20-JUL-16:02 | 1.02 |
| August | 0.133893E+09 | 1.01 | 130.62 | 13-AUG-16:05 | 1.02 |
| September | 46424563.19 | 0.63 | 98.34 | 16-SEP-16:10 | 1.04 |
| October | 9792058.87 | 0.33 | 30.23 | 17-OCT-05:00 | 0.94 |
| November | 43469823.31 | 0.84 | 42.36 | 24-NOV-04:00 | 0.94 |
| December | 0.125746E+09 | 0.94 | 84.25 | 11-DEC-08:20 | 0.95 |
| Annual Sum or Average | 0.101252E+10 | 0.77 | |||
| Minimum of Months | 5984945.48 | 0.23 | 23.77 | 0.94 | |
| Maximum of Months | 0.163128E+09 | 1.03 | 138.84 | 1.04 |
Report: FanReportMonthly
For: G N2 APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.65 | 20.01 | 01-JAN-00:10 | 0.65 |
| February | 48400714.57 | 0.65 | 20.01 | 01-FEB-00:10 | 0.65 |
| March | 53586505.42 | 0.65 | 20.01 | 01-MAR-00:10 | 0.65 |
| April | 51857908.47 | 0.65 | 20.01 | 01-APR-00:10 | 0.65 |
| May | 53586505.42 | 0.65 | 20.01 | 01-MAY-00:10 | 0.65 |
| June | 51857908.47 | 0.64 | 20.01 | 01-JUN-00:10 | 0.64 |
| July | 53586505.42 | 0.64 | 20.01 | 01-JUL-00:10 | 0.64 |
| August | 53586505.42 | 0.64 | 20.01 | 01-AUG-00:10 | 0.64 |
| September | 51857908.47 | 0.64 | 20.01 | 01-SEP-00:10 | 0.64 |
| October | 53586505.42 | 0.65 | 20.01 | 01-OCT-00:10 | 0.64 |
| November | 51857908.47 | 0.65 | 20.01 | 01-NOV-00:10 | 0.65 |
| December | 53586505.42 | 0.65 | 20.01 | 01-DEC-00:10 | 0.65 |
| Annual Sum or Average | 0.630938E+09 | 0.65 | |||
| Minimum of Months | 48400714.57 | 0.64 | 20.01 | 0.64 | |
| Maximum of Months | 53586505.42 | 0.65 | 20.01 | 0.65 |
Report: FanReportMonthly
For: G N2 APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.65 | 20.01 | 01-JAN-00:10 | 0.65 |
| February | 48400714.57 | 0.65 | 20.01 | 01-FEB-00:10 | 0.65 |
| March | 53586505.42 | 0.65 | 20.01 | 01-MAR-00:10 | 0.65 |
| April | 51857908.47 | 0.65 | 20.01 | 01-APR-00:10 | 0.65 |
| May | 53586505.42 | 0.65 | 20.01 | 01-MAY-00:10 | 0.64 |
| June | 51857908.47 | 0.64 | 20.01 | 01-JUN-00:10 | 0.64 |
| July | 53586505.42 | 0.64 | 20.01 | 01-JUL-00:10 | 0.65 |
| August | 53586505.42 | 0.64 | 20.01 | 01-AUG-00:10 | 0.64 |
| September | 51857908.47 | 0.64 | 20.01 | 01-SEP-00:10 | 0.64 |
| October | 53586505.42 | 0.65 | 20.01 | 01-OCT-00:10 | 0.64 |
| November | 51857908.47 | 0.65 | 20.01 | 01-NOV-00:10 | 0.65 |
| December | 53586505.42 | 0.65 | 20.01 | 01-DEC-00:10 | 0.65 |
| Annual Sum or Average | 0.630938E+09 | 0.65 | |||
| Minimum of Months | 48400714.57 | 0.64 | 20.01 | 0.64 | |
| Maximum of Months | 53586505.42 | 0.65 | 20.01 | 0.65 |
Report: FanReportMonthly
For: SPLIT GS1 SUPPLY FAN
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.120215E+09 | 0.94 | 81.97 | 24-JAN-06:00 | 0.95 |
| February | 0.118474E+09 | 0.95 | 99.67 | 07-FEB-08:12 | 0.95 |
| March | 66145717.60 | 0.82 | 65.72 | 07-MAR-04:55 | 0.95 |
| April | 31228569.17 | 0.65 | 53.81 | 16-APR-07:00 | 0.94 |
| May | 4058461.33 | 0.16 | 28.15 | 14-MAY-15:10 | 1.08 |
| June | 79366702.29 | 0.71 | 141.22 | 27-JUN-13:00 | 1.02 |
| July | 0.189585E+09 | 1.03 | 154.03 | 21-JUL-13:30 | 1.02 |
| August | 0.174795E+09 | 1.04 | 166.21 | 13-AUG-15:20 | 1.01 |
| September | 0.101772E+09 | 0.89 | 143.16 | 21-SEP-15:10 | 1.03 |
| October | 6814476.10 | 0.19 | 78.61 | 11-OCT-15:10 | 1.06 |
| November | 26796026.49 | 0.60 | 39.87 | 24-NOV-04:00 | 0.94 |
| December | 0.108640E+09 | 0.94 | 79.46 | 26-DEC-08:03 | 0.95 |
| Annual Sum or Average | 0.102789E+10 | 0.74 | |||
| Minimum of Months | 4058461.33 | 0.16 | 28.15 | 0.94 | |
| Maximum of Months | 0.189585E+09 | 1.04 | 166.21 | 1.08 |
Report: FanReportMonthly
For: G S1 APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.65 | 20.01 | 01-JAN-00:10 | 0.65 |
| February | 48400714.57 | 0.65 | 20.01 | 01-FEB-00:10 | 0.65 |
| March | 53586505.42 | 0.65 | 20.01 | 01-MAR-00:10 | 0.65 |
| April | 51857908.47 | 0.65 | 20.01 | 01-APR-00:10 | 0.65 |
| May | 53586505.42 | 0.65 | 20.01 | 01-MAY-00:10 | 0.65 |
| June | 51857908.47 | 0.64 | 20.01 | 01-JUN-00:10 | 0.64 |
| July | 53586505.42 | 0.64 | 20.01 | 01-JUL-00:10 | 0.64 |
| August | 53586505.42 | 0.64 | 20.01 | 01-AUG-00:10 | 0.64 |
| September | 51857908.47 | 0.64 | 20.01 | 01-SEP-00:10 | 0.64 |
| October | 53586505.42 | 0.65 | 20.01 | 01-OCT-00:10 | 0.64 |
| November | 51857908.47 | 0.65 | 20.01 | 01-NOV-00:10 | 0.65 |
| December | 53586505.42 | 0.65 | 20.01 | 01-DEC-00:10 | 0.65 |
| Annual Sum or Average | 0.630938E+09 | 0.65 | |||
| Minimum of Months | 48400714.57 | 0.64 | 20.01 | 0.64 | |
| Maximum of Months | 53586505.42 | 0.65 | 20.01 | 0.65 |
Report: FanReportMonthly
For: G S1 APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.65 | 20.01 | 01-JAN-00:10 | 0.65 |
| February | 48400714.57 | 0.65 | 20.01 | 01-FEB-00:10 | 0.65 |
| March | 53586505.42 | 0.65 | 20.01 | 01-MAR-00:10 | 0.65 |
| April | 51857908.47 | 0.65 | 20.01 | 01-APR-00:10 | 0.65 |
| May | 53586505.42 | 0.65 | 20.01 | 01-MAY-00:10 | 0.64 |
| June | 51857908.47 | 0.64 | 20.01 | 01-JUN-00:10 | 0.64 |
| July | 53586505.42 | 0.64 | 20.01 | 01-JUL-00:10 | 0.65 |
| August | 53586505.42 | 0.64 | 20.01 | 01-AUG-00:10 | 0.64 |
| September | 51857908.47 | 0.64 | 20.01 | 01-SEP-00:10 | 0.64 |
| October | 53586505.42 | 0.65 | 20.01 | 01-OCT-00:10 | 0.64 |
| November | 51857908.47 | 0.65 | 20.01 | 01-NOV-00:10 | 0.65 |
| December | 53586505.42 | 0.65 | 20.01 | 01-DEC-00:10 | 0.65 |
| Annual Sum or Average | 0.630938E+09 | 0.65 | |||
| Minimum of Months | 48400714.57 | 0.64 | 20.01 | 0.64 | |
| Maximum of Months | 53586505.42 | 0.65 | 20.01 | 0.65 |
Report: FanReportMonthly
For: SPLIT GS2 SUPPLY FAN
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.132265E+09 | 0.95 | 87.94 | 24-JAN-06:00 | 0.95 |
| February | 0.129031E+09 | 0.95 | 105.47 | 07-FEB-08:10 | 0.95 |
| March | 72878311.38 | 0.82 | 71.79 | 07-MAR-04:55 | 0.95 |
| April | 33940956.29 | 0.66 | 58.08 | 16-APR-07:00 | 0.94 |
| May | 4668828.13 | 0.17 | 30.39 | 14-MAY-15:10 | 1.08 |
| June | 87760456.13 | 0.76 | 146.44 | 27-JUN-13:00 | 1.02 |
| July | 0.207180E+09 | 1.05 | 160.32 | 21-JUL-13:30 | 1.02 |
| August | 0.191788E+09 | 1.05 | 175.66 | 13-AUG-15:20 | 1.01 |
| September | 0.112267E+09 | 0.93 | 147.07 | 21-SEP-15:10 | 1.03 |
| October | 7667951.07 | 0.20 | 80.75 | 11-OCT-15:10 | 1.06 |
| November | 29161090.96 | 0.62 | 43.85 | 24-NOV-04:00 | 0.94 |
| December | 0.118660E+09 | 0.94 | 86.32 | 26-DEC-08:03 | 0.95 |
| Annual Sum or Average | 0.112727E+10 | 0.76 | |||
| Minimum of Months | 4668828.13 | 0.17 | 30.39 | 0.94 | |
| Maximum of Months | 0.207180E+09 | 1.05 | 175.66 | 1.08 |
Report: FanReportMonthly
For: G S2 APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.65 | 20.01 | 01-JAN-00:10 | 0.65 |
| February | 48400714.57 | 0.65 | 20.01 | 01-FEB-00:10 | 0.65 |
| March | 53586505.42 | 0.65 | 20.01 | 01-MAR-00:10 | 0.65 |
| April | 51857908.47 | 0.65 | 20.01 | 01-APR-00:10 | 0.65 |
| May | 53586505.42 | 0.65 | 20.01 | 01-MAY-00:10 | 0.65 |
| June | 51857908.47 | 0.64 | 20.01 | 01-JUN-00:10 | 0.64 |
| July | 53586505.42 | 0.64 | 20.01 | 01-JUL-00:10 | 0.64 |
| August | 53586505.42 | 0.64 | 20.01 | 01-AUG-00:10 | 0.64 |
| September | 51857908.47 | 0.64 | 20.01 | 01-SEP-00:10 | 0.64 |
| October | 53586505.42 | 0.65 | 20.01 | 01-OCT-00:10 | 0.64 |
| November | 51857908.47 | 0.65 | 20.01 | 01-NOV-00:10 | 0.65 |
| December | 53586505.42 | 0.65 | 20.01 | 01-DEC-00:10 | 0.65 |
| Annual Sum or Average | 0.630938E+09 | 0.65 | |||
| Minimum of Months | 48400714.57 | 0.64 | 20.01 | 0.64 | |
| Maximum of Months | 53586505.42 | 0.65 | 20.01 | 0.65 |
Report: FanReportMonthly
For: G S2 APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.65 | 20.01 | 01-JAN-00:10 | 0.65 |
| February | 48400714.57 | 0.65 | 20.01 | 01-FEB-00:10 | 0.65 |
| March | 53586505.42 | 0.65 | 20.01 | 01-MAR-00:10 | 0.65 |
| April | 51857908.47 | 0.65 | 20.01 | 01-APR-00:10 | 0.65 |
| May | 53586505.42 | 0.65 | 20.01 | 01-MAY-00:10 | 0.64 |
| June | 51857908.47 | 0.64 | 20.01 | 01-JUN-00:10 | 0.64 |
| July | 53586505.42 | 0.64 | 20.01 | 01-JUL-00:10 | 0.65 |
| August | 53586505.42 | 0.64 | 20.01 | 01-AUG-00:10 | 0.64 |
| September | 51857908.47 | 0.64 | 20.01 | 01-SEP-00:10 | 0.64 |
| October | 53586505.42 | 0.65 | 20.01 | 01-OCT-00:10 | 0.64 |
| November | 51857908.47 | 0.65 | 20.01 | 01-NOV-00:10 | 0.65 |
| December | 53586505.42 | 0.65 | 20.01 | 01-DEC-00:10 | 0.65 |
| Annual Sum or Average | 0.630938E+09 | 0.65 | |||
| Minimum of Months | 48400714.57 | 0.64 | 20.01 | 0.64 | |
| Maximum of Months | 53586505.42 | 0.65 | 20.01 | 0.65 |
Report: FanReportMonthly
For: SPLIT MSW SUPPLY FAN
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.314294E+09 | 0.94 | 250.72 | 24-JAN-06:00 | 0.95 |
| February | 0.300571E+09 | 0.92 | 280.51 | 06-FEB-10:00 | 0.95 |
| March | 0.136482E+09 | 0.72 | 246.31 | 15-MAR-13:50 | 1.06 |
| April | 53233374.39 | 0.39 | 162.52 | 09-APR-16:03 | 1.08 |
| May | 0.111979E+09 | 0.51 | 345.19 | 14-MAY-14:30 | 1.04 |
| June | 0.373992E+09 | 0.94 | 478.27 | 27-JUN-16:23 | 1.01 |
| July | 0.598670E+09 | 1.05 | 503.05 | 19-JUL-15:10 | 1.01 |
| August | 0.503696E+09 | 1.04 | 546.13 | 13-AUG-15:30 | 1.00 |
| September | 0.273097E+09 | 0.82 | 466.76 | 21-SEP-16:10 | 1.02 |
| October | 40234001.00 | 0.34 | 318.07 | 11-OCT-16:10 | 1.05 |
| November | 97808634.98 | 0.64 | 114.37 | 24-NOV-04:00 | 0.94 |
| December | 0.311174E+09 | 0.93 | 243.77 | 26-DEC-05:00 | 0.95 |
| Annual Sum or Average | 0.311523E+10 | 0.77 | |||
| Minimum of Months | 40234001.00 | 0.34 | 114.37 | 0.94 | |
| Maximum of Months | 0.598670E+09 | 1.05 | 546.13 | 1.08 |
Report: FanReportMonthly
For: M SW APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.107173E+09 | 0.65 | 40.01 | 01-JAN-00:10 | 0.65 |
| February | 96801429.15 | 0.65 | 40.01 | 01-FEB-00:10 | 0.65 |
| March | 0.107173E+09 | 0.65 | 40.01 | 01-MAR-00:10 | 0.65 |
| April | 0.103716E+09 | 0.65 | 40.01 | 01-APR-00:10 | 0.65 |
| May | 0.107173E+09 | 0.65 | 40.01 | 01-MAY-00:10 | 0.65 |
| June | 0.103716E+09 | 0.64 | 40.01 | 01-JUN-00:10 | 0.64 |
| July | 0.107173E+09 | 0.64 | 40.01 | 01-JUL-00:10 | 0.64 |
| August | 0.107173E+09 | 0.64 | 40.01 | 01-AUG-00:10 | 0.64 |
| September | 0.103716E+09 | 0.64 | 40.01 | 01-SEP-00:10 | 0.64 |
| October | 0.107173E+09 | 0.65 | 40.01 | 01-OCT-00:10 | 0.64 |
| November | 0.103716E+09 | 0.65 | 40.01 | 01-NOV-00:10 | 0.65 |
| December | 0.107173E+09 | 0.65 | 40.01 | 01-DEC-00:10 | 0.65 |
| Annual Sum or Average | 0.126188E+10 | 0.65 | |||
| Minimum of Months | 96801429.15 | 0.64 | 40.01 | 0.64 | |
| Maximum of Months | 0.107173E+09 | 0.65 | 40.01 | 0.65 |
Report: FanReportMonthly
For: M SW APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.107173E+09 | 0.65 | 40.01 | 01-JAN-00:10 | 0.65 |
| February | 96801429.15 | 0.65 | 40.01 | 01-FEB-00:10 | 0.65 |
| March | 0.107173E+09 | 0.65 | 40.01 | 01-MAR-00:10 | 0.65 |
| April | 0.103716E+09 | 0.65 | 40.01 | 01-APR-00:10 | 0.65 |
| May | 0.107173E+09 | 0.65 | 40.01 | 01-MAY-00:10 | 0.64 |
| June | 0.103716E+09 | 0.64 | 40.01 | 01-JUN-00:10 | 0.64 |
| July | 0.107173E+09 | 0.64 | 40.01 | 01-JUL-00:10 | 0.65 |
| August | 0.107173E+09 | 0.64 | 40.01 | 01-AUG-00:10 | 0.64 |
| September | 0.103716E+09 | 0.64 | 40.01 | 01-SEP-00:10 | 0.64 |
| October | 0.107173E+09 | 0.65 | 40.01 | 01-OCT-00:10 | 0.64 |
| November | 0.103716E+09 | 0.65 | 40.01 | 01-NOV-00:10 | 0.65 |
| December | 0.107173E+09 | 0.65 | 40.01 | 01-DEC-00:10 | 0.65 |
| Annual Sum or Average | 0.126188E+10 | 0.65 | |||
| Minimum of Months | 96801429.15 | 0.64 | 40.01 | 0.64 | |
| Maximum of Months | 0.107173E+09 | 0.65 | 40.01 | 0.65 |
Report: FanReportMonthly
For: SPLIT MNW SUPPLY FAN
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.365513E+09 | 0.95 | 260.15 | 12-JAN-09:00 | 0.95 |
| February | 0.344637E+09 | 0.95 | 287.50 | 06-FEB-10:00 | 0.95 |
| March | 0.188247E+09 | 0.80 | 187.08 | 06-MAR-09:00 | 0.95 |
| April | 59297178.65 | 0.45 | 142.60 | 16-APR-04:00 | 0.94 |
| May | 64671050.18 | 0.37 | 263.09 | 14-MAY-15:10 | 1.05 |
| June | 0.338344E+09 | 0.92 | 463.12 | 27-JUN-17:05 | 1.01 |
| July | 0.547845E+09 | 1.05 | 455.39 | 11-JUL-18:00 | 1.02 |
| August | 0.421946E+09 | 1.03 | 458.74 | 13-AUG-15:30 | 1.01 |
| September | 0.156095E+09 | 0.66 | 332.72 | 16-SEP-16:10 | 1.04 |
| October | 39301932.51 | 0.41 | 101.50 | 30-OCT-05:00 | 0.94 |
| November | 0.135294E+09 | 0.83 | 119.58 | 24-NOV-04:00 | 0.94 |
| December | 0.350672E+09 | 0.94 | 250.56 | 26-DEC-04:00 | 0.95 |
| Annual Sum or Average | 0.301186E+10 | 0.78 | |||
| Minimum of Months | 39301932.51 | 0.37 | 101.50 | 0.94 | |
| Maximum of Months | 0.547845E+09 | 1.05 | 463.12 | 1.05 |
Report: FanReportMonthly
For: M NW APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.107173E+09 | 0.65 | 40.01 | 01-JAN-00:10 | 0.65 |
| February | 96801429.15 | 0.65 | 40.01 | 01-FEB-00:10 | 0.65 |
| March | 0.107173E+09 | 0.65 | 40.01 | 01-MAR-00:10 | 0.65 |
| April | 0.103716E+09 | 0.65 | 40.01 | 01-APR-00:10 | 0.65 |
| May | 0.107173E+09 | 0.65 | 40.01 | 01-MAY-00:10 | 0.65 |
| June | 0.103716E+09 | 0.64 | 40.01 | 01-JUN-00:10 | 0.64 |
| July | 0.107173E+09 | 0.64 | 40.01 | 01-JUL-00:10 | 0.64 |
| August | 0.107173E+09 | 0.64 | 40.01 | 01-AUG-00:10 | 0.64 |
| September | 0.103716E+09 | 0.64 | 40.01 | 01-SEP-00:10 | 0.64 |
| October | 0.107173E+09 | 0.65 | 40.01 | 01-OCT-00:10 | 0.64 |
| November | 0.103716E+09 | 0.65 | 40.01 | 01-NOV-00:10 | 0.65 |
| December | 0.107173E+09 | 0.65 | 40.01 | 01-DEC-00:10 | 0.65 |
| Annual Sum or Average | 0.126188E+10 | 0.65 | |||
| Minimum of Months | 96801429.15 | 0.64 | 40.01 | 0.64 | |
| Maximum of Months | 0.107173E+09 | 0.65 | 40.01 | 0.65 |
Report: FanReportMonthly
For: M NW APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.107173E+09 | 0.65 | 40.01 | 01-JAN-00:10 | 0.65 |
| February | 96801429.15 | 0.65 | 40.01 | 01-FEB-00:10 | 0.65 |
| March | 0.107173E+09 | 0.65 | 40.01 | 01-MAR-00:10 | 0.65 |
| April | 0.103716E+09 | 0.65 | 40.01 | 01-APR-00:10 | 0.65 |
| May | 0.107173E+09 | 0.65 | 40.01 | 01-MAY-00:10 | 0.64 |
| June | 0.103716E+09 | 0.64 | 40.01 | 01-JUN-00:10 | 0.64 |
| July | 0.107173E+09 | 0.64 | 40.01 | 01-JUL-00:10 | 0.65 |
| August | 0.107173E+09 | 0.64 | 40.01 | 01-AUG-00:10 | 0.64 |
| September | 0.103716E+09 | 0.64 | 40.01 | 01-SEP-00:10 | 0.64 |
| October | 0.107173E+09 | 0.65 | 40.01 | 01-OCT-00:10 | 0.64 |
| November | 0.103716E+09 | 0.65 | 40.01 | 01-NOV-00:10 | 0.65 |
| December | 0.107173E+09 | 0.65 | 40.01 | 01-DEC-00:10 | 0.65 |
| Annual Sum or Average | 0.126188E+10 | 0.65 | |||
| Minimum of Months | 96801429.15 | 0.64 | 40.01 | 0.64 | |
| Maximum of Months | 0.107173E+09 | 0.65 | 40.01 | 0.65 |
Report: FanReportMonthly
For: SPLIT MSE SUPPLY FAN
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.305733E+09 | 0.94 | 245.13 | 24-JAN-06:00 | 0.95 |
| February | 0.293002E+09 | 0.93 | 273.25 | 06-FEB-10:00 | 0.95 |
| March | 0.135888E+09 | 0.74 | 246.23 | 15-MAR-13:40 | 1.05 |
| April | 53867127.59 | 0.40 | 144.92 | 22-APR-13:40 | 1.08 |
| May | 0.111211E+09 | 0.54 | 294.04 | 14-MAY-14:10 | 1.04 |
| June | 0.363899E+09 | 0.96 | 467.86 | 27-JUN-13:00 | 1.01 |
| July | 0.595885E+09 | 1.05 | 469.86 | 21-JUL-13:30 | 1.01 |
| August | 0.498534E+09 | 1.04 | 475.15 | 13-AUG-15:10 | 1.00 |
| September | 0.276533E+09 | 0.83 | 406.52 | 21-SEP-13:30 | 1.02 |
| October | 39357781.24 | 0.34 | 273.80 | 11-OCT-12:40 | 1.05 |
| November | 95259228.94 | 0.62 | 114.61 | 24-NOV-04:00 | 0.94 |
| December | 0.306122E+09 | 0.93 | 239.66 | 26-DEC-05:00 | 0.95 |
| Annual Sum or Average | 0.307529E+10 | 0.78 | |||
| Minimum of Months | 39357781.24 | 0.34 | 114.61 | 0.94 | |
| Maximum of Months | 0.595885E+09 | 1.05 | 475.15 | 1.08 |
Report: FanReportMonthly
For: M SE APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.107173E+09 | 0.65 | 40.01 | 01-JAN-00:10 | 0.65 |
| February | 96801429.15 | 0.65 | 40.01 | 01-FEB-00:10 | 0.65 |
| March | 0.107173E+09 | 0.65 | 40.01 | 01-MAR-00:10 | 0.65 |
| April | 0.103716E+09 | 0.65 | 40.01 | 01-APR-00:10 | 0.65 |
| May | 0.107173E+09 | 0.65 | 40.01 | 01-MAY-00:10 | 0.65 |
| June | 0.103716E+09 | 0.64 | 40.01 | 01-JUN-00:10 | 0.64 |
| July | 0.107173E+09 | 0.64 | 40.01 | 01-JUL-00:10 | 0.64 |
| August | 0.107173E+09 | 0.64 | 40.01 | 01-AUG-00:10 | 0.64 |
| September | 0.103716E+09 | 0.64 | 40.01 | 01-SEP-00:10 | 0.64 |
| October | 0.107173E+09 | 0.65 | 40.01 | 01-OCT-00:10 | 0.64 |
| November | 0.103716E+09 | 0.65 | 40.01 | 01-NOV-00:10 | 0.65 |
| December | 0.107173E+09 | 0.65 | 40.01 | 01-DEC-00:10 | 0.65 |
| Annual Sum or Average | 0.126188E+10 | 0.65 | |||
| Minimum of Months | 96801429.15 | 0.64 | 40.01 | 0.64 | |
| Maximum of Months | 0.107173E+09 | 0.65 | 40.01 | 0.65 |
Report: FanReportMonthly
For: M SE APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.107173E+09 | 0.65 | 40.01 | 01-JAN-00:10 | 0.65 |
| February | 96801429.15 | 0.65 | 40.01 | 01-FEB-00:10 | 0.65 |
| March | 0.107173E+09 | 0.65 | 40.01 | 01-MAR-00:10 | 0.65 |
| April | 0.103716E+09 | 0.65 | 40.01 | 01-APR-00:10 | 0.65 |
| May | 0.107173E+09 | 0.65 | 40.01 | 01-MAY-00:10 | 0.64 |
| June | 0.103716E+09 | 0.64 | 40.01 | 01-JUN-00:10 | 0.64 |
| July | 0.107173E+09 | 0.64 | 40.01 | 01-JUL-00:10 | 0.65 |
| August | 0.107173E+09 | 0.64 | 40.01 | 01-AUG-00:10 | 0.64 |
| September | 0.103716E+09 | 0.64 | 40.01 | 01-SEP-00:10 | 0.64 |
| October | 0.107173E+09 | 0.65 | 40.01 | 01-OCT-00:10 | 0.64 |
| November | 0.103716E+09 | 0.65 | 40.01 | 01-NOV-00:10 | 0.65 |
| December | 0.107173E+09 | 0.65 | 40.01 | 01-DEC-00:10 | 0.65 |
| Annual Sum or Average | 0.126188E+10 | 0.65 | |||
| Minimum of Months | 96801429.15 | 0.64 | 40.01 | 0.64 | |
| Maximum of Months | 0.107173E+09 | 0.65 | 40.01 | 0.65 |
Report: FanReportMonthly
For: SPLIT MNE SUPPLY FAN
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.355864E+09 | 0.95 | 249.41 | 24-JAN-06:00 | 0.95 |
| February | 0.336259E+09 | 0.95 | 280.03 | 06-FEB-10:00 | 0.95 |
| March | 0.186636E+09 | 0.81 | 188.71 | 07-MAR-04:55 | 0.95 |
| April | 56596034.50 | 0.45 | 139.20 | 16-APR-04:00 | 0.94 |
| May | 61666975.06 | 0.42 | 216.73 | 14-MAY-15:10 | 1.05 |
| June | 0.327461E+09 | 0.94 | 407.62 | 27-JUN-13:00 | 1.01 |
| July | 0.544068E+09 | 1.05 | 416.84 | 20-JUL-16:02 | 1.01 |
| August | 0.416589E+09 | 1.02 | 387.13 | 13-AUG-15:10 | 1.02 |
| September | 0.158390E+09 | 0.72 | 279.54 | 16-SEP-13:00 | 1.04 |
| October | 35818981.09 | 0.39 | 102.02 | 30-OCT-05:00 | 0.94 |
| November | 0.132079E+09 | 0.82 | 119.34 | 24-NOV-04:00 | 0.94 |
| December | 0.344764E+09 | 0.94 | 246.16 | 26-DEC-04:00 | 0.95 |
| Annual Sum or Average | 0.295619E+10 | 0.79 | |||
| Minimum of Months | 35818981.09 | 0.39 | 102.02 | 0.94 | |
| Maximum of Months | 0.544068E+09 | 1.05 | 416.84 | 1.05 |
Report: FanReportMonthly
For: M NE APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.107173E+09 | 0.65 | 40.01 | 01-JAN-00:10 | 0.65 |
| February | 96801429.15 | 0.65 | 40.01 | 01-FEB-00:10 | 0.65 |
| March | 0.107173E+09 | 0.65 | 40.01 | 01-MAR-00:10 | 0.65 |
| April | 0.103716E+09 | 0.65 | 40.01 | 01-APR-00:10 | 0.65 |
| May | 0.107173E+09 | 0.65 | 40.01 | 01-MAY-00:10 | 0.65 |
| June | 0.103716E+09 | 0.64 | 40.01 | 01-JUN-00:10 | 0.64 |
| July | 0.107173E+09 | 0.64 | 40.01 | 01-JUL-00:10 | 0.64 |
| August | 0.107173E+09 | 0.64 | 40.01 | 01-AUG-00:10 | 0.64 |
| September | 0.103716E+09 | 0.64 | 40.01 | 01-SEP-00:10 | 0.64 |
| October | 0.107173E+09 | 0.65 | 40.01 | 01-OCT-00:10 | 0.64 |
| November | 0.103716E+09 | 0.65 | 40.01 | 01-NOV-00:10 | 0.65 |
| December | 0.107173E+09 | 0.65 | 40.01 | 01-DEC-00:10 | 0.65 |
| Annual Sum or Average | 0.126188E+10 | 0.65 | |||
| Minimum of Months | 96801429.15 | 0.64 | 40.01 | 0.64 | |
| Maximum of Months | 0.107173E+09 | 0.65 | 40.01 | 0.65 |
Report: FanReportMonthly
For: M NE APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.107173E+09 | 0.65 | 40.01 | 01-JAN-00:10 | 0.65 |
| February | 96801429.15 | 0.65 | 40.01 | 01-FEB-00:10 | 0.65 |
| March | 0.107173E+09 | 0.65 | 40.01 | 01-MAR-00:10 | 0.65 |
| April | 0.103716E+09 | 0.65 | 40.01 | 01-APR-00:10 | 0.65 |
| May | 0.107173E+09 | 0.65 | 40.01 | 01-MAY-00:10 | 0.64 |
| June | 0.103716E+09 | 0.64 | 40.01 | 01-JUN-00:10 | 0.64 |
| July | 0.107173E+09 | 0.64 | 40.01 | 01-JUL-00:10 | 0.65 |
| August | 0.107173E+09 | 0.64 | 40.01 | 01-AUG-00:10 | 0.64 |
| September | 0.103716E+09 | 0.64 | 40.01 | 01-SEP-00:10 | 0.64 |
| October | 0.107173E+09 | 0.65 | 40.01 | 01-OCT-00:10 | 0.64 |
| November | 0.103716E+09 | 0.65 | 40.01 | 01-NOV-00:10 | 0.65 |
| December | 0.107173E+09 | 0.65 | 40.01 | 01-DEC-00:10 | 0.65 |
| Annual Sum or Average | 0.126188E+10 | 0.65 | |||
| Minimum of Months | 96801429.15 | 0.64 | 40.01 | 0.64 | |
| Maximum of Months | 0.107173E+09 | 0.65 | 40.01 | 0.65 |
Report: FanReportMonthly
For: SPLIT MN1 SUPPLY FAN
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.233241E+09 | 0.95 | 165.23 | 24-JAN-06:00 | 0.95 |
| February | 0.222912E+09 | 0.95 | 187.06 | 06-FEB-10:00 | 0.95 |
| March | 0.121422E+09 | 0.76 | 132.45 | 07-MAR-04:55 | 0.95 |
| April | 30518705.01 | 0.35 | 90.23 | 16-APR-04:00 | 0.94 |
| May | 51693700.12 | 0.43 | 184.45 | 14-MAY-15:10 | 1.06 |
| June | 0.265184E+09 | 0.96 | 309.92 | 27-JUN-17:15 | 1.02 |
| July | 0.444045E+09 | 1.06 | 338.86 | 20-JUL-16:02 | 1.02 |
| August | 0.346459E+09 | 1.06 | 316.74 | 13-AUG-16:05 | 1.02 |
| September | 0.139240E+09 | 0.78 | 233.11 | 16-SEP-16:10 | 1.05 |
| October | 12982896.08 | 0.23 | 63.50 | 30-OCT-05:00 | 0.94 |
| November | 70469747.24 | 0.76 | 77.50 | 24-NOV-04:00 | 0.94 |
| December | 0.220791E+09 | 0.94 | 161.24 | 26-DEC-04:00 | 0.95 |
| Annual Sum or Average | 0.215896E+10 | 0.77 | |||
| Minimum of Months | 12982896.08 | 0.23 | 63.50 | 0.94 | |
| Maximum of Months | 0.444045E+09 | 1.06 | 338.86 | 1.06 |
Report: FanReportMonthly
For: M N1 APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.107173E+09 | 0.65 | 40.01 | 01-JAN-00:10 | 0.65 |
| February | 96801429.15 | 0.65 | 40.01 | 01-FEB-00:10 | 0.65 |
| March | 0.107173E+09 | 0.65 | 40.01 | 01-MAR-00:10 | 0.65 |
| April | 0.103716E+09 | 0.65 | 40.01 | 01-APR-00:10 | 0.65 |
| May | 0.107173E+09 | 0.65 | 40.01 | 01-MAY-00:10 | 0.65 |
| June | 0.103716E+09 | 0.64 | 40.01 | 01-JUN-00:10 | 0.64 |
| July | 0.107173E+09 | 0.64 | 40.01 | 01-JUL-00:10 | 0.64 |
| August | 0.107173E+09 | 0.64 | 40.01 | 01-AUG-00:10 | 0.64 |
| September | 0.103716E+09 | 0.64 | 40.01 | 01-SEP-00:10 | 0.64 |
| October | 0.107173E+09 | 0.65 | 40.01 | 01-OCT-00:10 | 0.64 |
| November | 0.103716E+09 | 0.65 | 40.01 | 01-NOV-00:10 | 0.65 |
| December | 0.107173E+09 | 0.65 | 40.01 | 01-DEC-00:10 | 0.65 |
| Annual Sum or Average | 0.126188E+10 | 0.65 | |||
| Minimum of Months | 96801429.15 | 0.64 | 40.01 | 0.64 | |
| Maximum of Months | 0.107173E+09 | 0.65 | 40.01 | 0.65 |
Report: FanReportMonthly
For: M N1 APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.107173E+09 | 0.65 | 40.01 | 01-JAN-00:10 | 0.65 |
| February | 96801429.15 | 0.65 | 40.01 | 01-FEB-00:10 | 0.65 |
| March | 0.107173E+09 | 0.65 | 40.01 | 01-MAR-00:10 | 0.65 |
| April | 0.103716E+09 | 0.65 | 40.01 | 01-APR-00:10 | 0.65 |
| May | 0.107173E+09 | 0.65 | 40.01 | 01-MAY-00:10 | 0.64 |
| June | 0.103716E+09 | 0.64 | 40.01 | 01-JUN-00:10 | 0.64 |
| July | 0.107173E+09 | 0.64 | 40.01 | 01-JUL-00:10 | 0.65 |
| August | 0.107173E+09 | 0.64 | 40.01 | 01-AUG-00:10 | 0.64 |
| September | 0.103716E+09 | 0.64 | 40.01 | 01-SEP-00:10 | 0.64 |
| October | 0.107173E+09 | 0.65 | 40.01 | 01-OCT-00:10 | 0.64 |
| November | 0.103716E+09 | 0.65 | 40.01 | 01-NOV-00:10 | 0.65 |
| December | 0.107173E+09 | 0.65 | 40.01 | 01-DEC-00:10 | 0.65 |
| Annual Sum or Average | 0.126188E+10 | 0.65 | |||
| Minimum of Months | 96801429.15 | 0.64 | 40.01 | 0.64 | |
| Maximum of Months | 0.107173E+09 | 0.65 | 40.01 | 0.65 |
Report: FanReportMonthly
For: SPLIT MN2 SUPPLY FAN
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.233006E+09 | 0.95 | 165.06 | 24-JAN-06:00 | 0.95 |
| February | 0.222722E+09 | 0.95 | 186.91 | 06-FEB-10:00 | 0.95 |
| March | 0.121474E+09 | 0.77 | 132.58 | 07-MAR-04:55 | 0.95 |
| April | 30461160.59 | 0.35 | 90.12 | 16-APR-04:00 | 0.94 |
| May | 52016934.49 | 0.43 | 183.23 | 14-MAY-15:10 | 1.06 |
| June | 0.264958E+09 | 0.96 | 310.30 | 27-JUN-13:00 | 1.03 |
| July | 0.444028E+09 | 1.06 | 338.69 | 20-JUL-16:02 | 1.02 |
| August | 0.346348E+09 | 1.06 | 315.34 | 13-AUG-16:05 | 1.02 |
| September | 0.139674E+09 | 0.78 | 232.53 | 16-SEP-16:10 | 1.05 |
| October | 12940084.86 | 0.23 | 63.57 | 30-OCT-05:00 | 0.94 |
| November | 70365216.31 | 0.76 | 77.55 | 24-NOV-04:00 | 0.94 |
| December | 0.220691E+09 | 0.94 | 161.17 | 26-DEC-04:00 | 0.95 |
| Annual Sum or Average | 0.215869E+10 | 0.77 | |||
| Minimum of Months | 12940084.86 | 0.23 | 63.57 | 0.94 | |
| Maximum of Months | 0.444028E+09 | 1.06 | 338.69 | 1.06 |
Report: FanReportMonthly
For: M N2 APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.107173E+09 | 0.65 | 40.01 | 01-JAN-00:10 | 0.65 |
| February | 96801429.15 | 0.65 | 40.01 | 01-FEB-00:10 | 0.65 |
| March | 0.107173E+09 | 0.65 | 40.01 | 01-MAR-00:10 | 0.65 |
| April | 0.103716E+09 | 0.65 | 40.01 | 01-APR-00:10 | 0.65 |
| May | 0.107173E+09 | 0.65 | 40.01 | 01-MAY-00:10 | 0.65 |
| June | 0.103716E+09 | 0.64 | 40.01 | 01-JUN-00:10 | 0.64 |
| July | 0.107173E+09 | 0.64 | 40.01 | 01-JUL-00:10 | 0.64 |
| August | 0.107173E+09 | 0.64 | 40.01 | 01-AUG-00:10 | 0.64 |
| September | 0.103716E+09 | 0.64 | 40.01 | 01-SEP-00:10 | 0.64 |
| October | 0.107173E+09 | 0.65 | 40.01 | 01-OCT-00:10 | 0.64 |
| November | 0.103716E+09 | 0.65 | 40.01 | 01-NOV-00:10 | 0.65 |
| December | 0.107173E+09 | 0.65 | 40.01 | 01-DEC-00:10 | 0.65 |
| Annual Sum or Average | 0.126188E+10 | 0.65 | |||
| Minimum of Months | 96801429.15 | 0.64 | 40.01 | 0.64 | |
| Maximum of Months | 0.107173E+09 | 0.65 | 40.01 | 0.65 |
Report: FanReportMonthly
For: M N2 APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.107173E+09 | 0.65 | 40.01 | 01-JAN-00:10 | 0.65 |
| February | 96801429.15 | 0.65 | 40.01 | 01-FEB-00:10 | 0.65 |
| March | 0.107173E+09 | 0.65 | 40.01 | 01-MAR-00:10 | 0.65 |
| April | 0.103716E+09 | 0.65 | 40.01 | 01-APR-00:10 | 0.65 |
| May | 0.107173E+09 | 0.65 | 40.01 | 01-MAY-00:10 | 0.64 |
| June | 0.103716E+09 | 0.64 | 40.01 | 01-JUN-00:10 | 0.64 |
| July | 0.107173E+09 | 0.64 | 40.01 | 01-JUL-00:10 | 0.65 |
| August | 0.107173E+09 | 0.64 | 40.01 | 01-AUG-00:10 | 0.64 |
| September | 0.103716E+09 | 0.64 | 40.01 | 01-SEP-00:10 | 0.64 |
| October | 0.107173E+09 | 0.65 | 40.01 | 01-OCT-00:10 | 0.64 |
| November | 0.103716E+09 | 0.65 | 40.01 | 01-NOV-00:10 | 0.65 |
| December | 0.107173E+09 | 0.65 | 40.01 | 01-DEC-00:10 | 0.65 |
| Annual Sum or Average | 0.126188E+10 | 0.65 | |||
| Minimum of Months | 96801429.15 | 0.64 | 40.01 | 0.64 | |
| Maximum of Months | 0.107173E+09 | 0.65 | 40.01 | 0.65 |
Report: FanReportMonthly
For: SPLIT MS1 SUPPLY FAN
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.185263E+09 | 0.92 | 159.69 | 24-JAN-06:00 | 0.95 |
| February | 0.181414E+09 | 0.90 | 178.62 | 06-FEB-10:00 | 0.95 |
| March | 74258258.68 | 0.58 | 219.09 | 15-MAR-13:40 | 1.06 |
| April | 28316256.87 | 0.31 | 131.57 | 09-APR-16:03 | 1.08 |
| May | 0.101759E+09 | 0.63 | 262.31 | 14-MAY-14:10 | 1.04 |
| June | 0.302682E+09 | 0.98 | 370.56 | 27-JUN-13:00 | 1.02 |
| July | 0.497736E+09 | 1.05 | 377.28 | 21-JUL-13:30 | 1.02 |
| August | 0.430851E+09 | 1.06 | 399.76 | 13-AUG-15:20 | 1.01 |
| September | 0.263274E+09 | 0.95 | 359.76 | 21-SEP-14:10 | 1.03 |
| October | 36561974.59 | 0.28 | 261.15 | 11-OCT-14:30 | 1.05 |
| November | 40481386.79 | 0.51 | 74.28 | 24-NOV-04:00 | 0.94 |
| December | 0.183930E+09 | 0.91 | 155.78 | 26-DEC-05:00 | 0.95 |
| Annual Sum or Average | 0.232653E+10 | 0.76 | |||
| Minimum of Months | 28316256.87 | 0.28 | 74.28 | 0.94 | |
| Maximum of Months | 0.497736E+09 | 1.06 | 399.76 | 1.08 |
Report: FanReportMonthly
For: M S1 APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.107173E+09 | 0.65 | 40.01 | 01-JAN-00:10 | 0.65 |
| February | 96801429.15 | 0.65 | 40.01 | 01-FEB-00:10 | 0.65 |
| March | 0.107173E+09 | 0.65 | 40.01 | 01-MAR-00:10 | 0.65 |
| April | 0.103716E+09 | 0.65 | 40.01 | 01-APR-00:10 | 0.65 |
| May | 0.107173E+09 | 0.65 | 40.01 | 01-MAY-00:10 | 0.65 |
| June | 0.103716E+09 | 0.64 | 40.01 | 01-JUN-00:10 | 0.64 |
| July | 0.107173E+09 | 0.64 | 40.01 | 01-JUL-00:10 | 0.64 |
| August | 0.107173E+09 | 0.64 | 40.01 | 01-AUG-00:10 | 0.64 |
| September | 0.103716E+09 | 0.64 | 40.01 | 01-SEP-00:10 | 0.64 |
| October | 0.107173E+09 | 0.65 | 40.01 | 01-OCT-00:10 | 0.64 |
| November | 0.103716E+09 | 0.65 | 40.01 | 01-NOV-00:10 | 0.65 |
| December | 0.107173E+09 | 0.65 | 40.01 | 01-DEC-00:10 | 0.65 |
| Annual Sum or Average | 0.126188E+10 | 0.65 | |||
| Minimum of Months | 96801429.15 | 0.64 | 40.01 | 0.64 | |
| Maximum of Months | 0.107173E+09 | 0.65 | 40.01 | 0.65 |
Report: FanReportMonthly
For: M S1 APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.107173E+09 | 0.65 | 40.01 | 01-JAN-00:10 | 0.65 |
| February | 96801429.15 | 0.65 | 40.01 | 01-FEB-00:10 | 0.65 |
| March | 0.107173E+09 | 0.65 | 40.01 | 01-MAR-00:10 | 0.65 |
| April | 0.103716E+09 | 0.65 | 40.01 | 01-APR-00:10 | 0.65 |
| May | 0.107173E+09 | 0.65 | 40.01 | 01-MAY-00:10 | 0.64 |
| June | 0.103716E+09 | 0.64 | 40.01 | 01-JUN-00:10 | 0.64 |
| July | 0.107173E+09 | 0.64 | 40.01 | 01-JUL-00:10 | 0.65 |
| August | 0.107173E+09 | 0.64 | 40.01 | 01-AUG-00:10 | 0.64 |
| September | 0.103716E+09 | 0.64 | 40.01 | 01-SEP-00:10 | 0.64 |
| October | 0.107173E+09 | 0.65 | 40.01 | 01-OCT-00:10 | 0.64 |
| November | 0.103716E+09 | 0.65 | 40.01 | 01-NOV-00:10 | 0.65 |
| December | 0.107173E+09 | 0.65 | 40.01 | 01-DEC-00:10 | 0.65 |
| Annual Sum or Average | 0.126188E+10 | 0.65 | |||
| Minimum of Months | 96801429.15 | 0.64 | 40.01 | 0.64 | |
| Maximum of Months | 0.107173E+09 | 0.65 | 40.01 | 0.65 |
Report: FanReportMonthly
For: SPLIT MS2 SUPPLY FAN
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.185035E+09 | 0.92 | 159.50 | 24-JAN-06:00 | 0.95 |
| February | 0.181235E+09 | 0.90 | 178.51 | 07-FEB-05:00 | 0.95 |
| March | 74375769.63 | 0.58 | 219.77 | 15-MAR-13:40 | 1.06 |
| April | 28770455.39 | 0.31 | 133.17 | 09-APR-16:03 | 1.07 |
| May | 0.102108E+09 | 0.63 | 261.54 | 14-MAY-14:10 | 1.04 |
| June | 0.302449E+09 | 0.98 | 371.27 | 27-JUN-13:00 | 1.02 |
| July | 0.497688E+09 | 1.05 | 377.97 | 21-JUL-13:30 | 1.02 |
| August | 0.430704E+09 | 1.06 | 398.66 | 13-AUG-15:20 | 1.01 |
| September | 0.263465E+09 | 0.95 | 360.07 | 21-SEP-14:10 | 1.02 |
| October | 37020291.41 | 0.28 | 262.06 | 11-OCT-14:30 | 1.05 |
| November | 40457364.88 | 0.51 | 74.33 | 24-NOV-04:00 | 0.94 |
| December | 0.183846E+09 | 0.91 | 155.71 | 26-DEC-05:00 | 0.95 |
| Annual Sum or Average | 0.232715E+10 | 0.76 | |||
| Minimum of Months | 28770455.39 | 0.28 | 74.33 | 0.94 | |
| Maximum of Months | 0.497688E+09 | 1.06 | 398.66 | 1.07 |
Report: FanReportMonthly
For: M S2 APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.107173E+09 | 0.65 | 40.01 | 01-JAN-00:10 | 0.65 |
| February | 96801429.15 | 0.65 | 40.01 | 01-FEB-00:10 | 0.65 |
| March | 0.107173E+09 | 0.65 | 40.01 | 01-MAR-00:10 | 0.65 |
| April | 0.103716E+09 | 0.65 | 40.01 | 01-APR-00:10 | 0.65 |
| May | 0.107173E+09 | 0.65 | 40.01 | 01-MAY-00:10 | 0.65 |
| June | 0.103716E+09 | 0.64 | 40.01 | 01-JUN-00:10 | 0.64 |
| July | 0.107173E+09 | 0.64 | 40.01 | 01-JUL-00:10 | 0.64 |
| August | 0.107173E+09 | 0.64 | 40.01 | 01-AUG-00:10 | 0.64 |
| September | 0.103716E+09 | 0.64 | 40.01 | 01-SEP-00:10 | 0.64 |
| October | 0.107173E+09 | 0.65 | 40.01 | 01-OCT-00:10 | 0.64 |
| November | 0.103716E+09 | 0.65 | 40.01 | 01-NOV-00:10 | 0.65 |
| December | 0.107173E+09 | 0.65 | 40.01 | 01-DEC-00:10 | 0.65 |
| Annual Sum or Average | 0.126188E+10 | 0.65 | |||
| Minimum of Months | 96801429.15 | 0.64 | 40.01 | 0.64 | |
| Maximum of Months | 0.107173E+09 | 0.65 | 40.01 | 0.65 |
Report: FanReportMonthly
For: M S2 APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.107173E+09 | 0.65 | 40.01 | 01-JAN-00:10 | 0.65 |
| February | 96801429.15 | 0.65 | 40.01 | 01-FEB-00:10 | 0.65 |
| March | 0.107173E+09 | 0.65 | 40.01 | 01-MAR-00:10 | 0.65 |
| April | 0.103716E+09 | 0.65 | 40.01 | 01-APR-00:10 | 0.65 |
| May | 0.107173E+09 | 0.65 | 40.01 | 01-MAY-00:10 | 0.64 |
| June | 0.103716E+09 | 0.64 | 40.01 | 01-JUN-00:10 | 0.64 |
| July | 0.107173E+09 | 0.64 | 40.01 | 01-JUL-00:10 | 0.65 |
| August | 0.107173E+09 | 0.64 | 40.01 | 01-AUG-00:10 | 0.64 |
| September | 0.103716E+09 | 0.64 | 40.01 | 01-SEP-00:10 | 0.64 |
| October | 0.107173E+09 | 0.65 | 40.01 | 01-OCT-00:10 | 0.64 |
| November | 0.103716E+09 | 0.65 | 40.01 | 01-NOV-00:10 | 0.65 |
| December | 0.107173E+09 | 0.65 | 40.01 | 01-DEC-00:10 | 0.65 |
| Annual Sum or Average | 0.126188E+10 | 0.65 | |||
| Minimum of Months | 96801429.15 | 0.64 | 40.01 | 0.64 | |
| Maximum of Months | 0.107173E+09 | 0.65 | 40.01 | 0.65 |
Report: FanReportMonthly
For: SPLIT TSW SUPPLY FAN
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.259743E+09 | 0.94 | 194.88 | 24-JAN-06:00 | 0.95 |
| February | 0.244161E+09 | 0.93 | 211.95 | 06-FEB-10:00 | 0.95 |
| March | 0.140246E+09 | 0.80 | 193.54 | 15-MAR-13:50 | 1.04 |
| April | 79398599.71 | 0.69 | 130.85 | 22-APR-15:00 | 1.07 |
| May | 60990981.57 | 0.47 | 231.88 | 14-MAY-14:30 | 1.03 |
| June | 0.187728E+09 | 0.73 | 307.15 | 27-JUN-16:23 | 1.00 |
| July | 0.314862E+09 | 0.92 | 330.73 | 19-JUL-15:10 | 1.00 |
| August | 0.252409E+09 | 0.82 | 348.75 | 13-AUG-15:30 | 0.99 |
| September | 0.121797E+09 | 0.58 | 289.00 | 21-SEP-15:30 | 1.01 |
| October | 64792751.86 | 0.62 | 207.02 | 11-OCT-15:30 | 1.04 |
| November | 0.111726E+09 | 0.79 | 101.90 | 24-NOV-04:00 | 0.94 |
| December | 0.255663E+09 | 0.94 | 194.42 | 26-DEC-04:00 | 0.95 |
| Annual Sum or Average | 0.209352E+10 | 0.77 | |||
| Minimum of Months | 60990981.57 | 0.47 | 101.90 | 0.94 | |
| Maximum of Months | 0.314862E+09 | 0.94 | 348.75 | 1.07 |
Report: FanReportMonthly
For: T SW APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.65 | 20.01 | 01-JAN-00:10 | 0.65 |
| February | 48400714.57 | 0.65 | 20.01 | 01-FEB-00:10 | 0.65 |
| March | 53586505.42 | 0.65 | 20.01 | 01-MAR-00:10 | 0.65 |
| April | 51857908.47 | 0.65 | 20.01 | 01-APR-00:10 | 0.65 |
| May | 53586505.42 | 0.65 | 20.01 | 01-MAY-00:10 | 0.65 |
| June | 51857908.47 | 0.64 | 20.01 | 01-JUN-00:10 | 0.64 |
| July | 53586505.42 | 0.64 | 20.01 | 01-JUL-00:10 | 0.64 |
| August | 53586505.42 | 0.64 | 20.01 | 01-AUG-00:10 | 0.64 |
| September | 51857908.47 | 0.64 | 20.01 | 01-SEP-00:10 | 0.64 |
| October | 53586505.42 | 0.65 | 20.01 | 01-OCT-00:10 | 0.64 |
| November | 51857908.47 | 0.65 | 20.01 | 01-NOV-00:10 | 0.65 |
| December | 53586505.42 | 0.65 | 20.01 | 01-DEC-00:10 | 0.65 |
| Annual Sum or Average | 0.630938E+09 | 0.65 | |||
| Minimum of Months | 48400714.57 | 0.64 | 20.01 | 0.64 | |
| Maximum of Months | 53586505.42 | 0.65 | 20.01 | 0.65 |
Report: FanReportMonthly
For: T SW APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.65 | 20.01 | 01-JAN-00:10 | 0.65 |
| February | 48400714.57 | 0.65 | 20.01 | 01-FEB-00:10 | 0.65 |
| March | 53586505.42 | 0.65 | 20.01 | 01-MAR-00:10 | 0.65 |
| April | 51857908.47 | 0.65 | 20.01 | 01-APR-00:10 | 0.65 |
| May | 53586505.42 | 0.65 | 20.01 | 01-MAY-00:10 | 0.64 |
| June | 51857908.47 | 0.64 | 20.01 | 01-JUN-00:10 | 0.64 |
| July | 53586505.42 | 0.64 | 20.01 | 01-JUL-00:10 | 0.64 |
| August | 53586505.42 | 0.64 | 20.01 | 01-AUG-00:10 | 0.64 |
| September | 51857908.47 | 0.64 | 20.01 | 01-SEP-00:10 | 0.64 |
| October | 53586505.42 | 0.65 | 20.01 | 01-OCT-00:10 | 0.64 |
| November | 51857908.47 | 0.65 | 20.01 | 01-NOV-00:10 | 0.65 |
| December | 53586505.42 | 0.65 | 20.01 | 01-DEC-00:10 | 0.65 |
| Annual Sum or Average | 0.630938E+09 | 0.65 | |||
| Minimum of Months | 48400714.57 | 0.64 | 20.01 | 0.64 | |
| Maximum of Months | 53586505.42 | 0.65 | 20.01 | 0.65 |
Report: FanReportMonthly
For: SPLIT TNW SUPPLY FAN
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.287770E+09 | 0.95 | 197.87 | 12-JAN-09:00 | 0.95 |
| February | 0.268075E+09 | 0.95 | 212.32 | 06-FEB-10:00 | 0.95 |
| March | 0.166722E+09 | 0.87 | 153.70 | 07-MAR-04:55 | 0.95 |
| April | 76225476.79 | 0.70 | 118.50 | 16-APR-04:00 | 0.94 |
| May | 40185047.30 | 0.41 | 180.48 | 14-MAY-15:10 | 1.04 |
| June | 0.169472E+09 | 0.72 | 297.50 | 27-JUN-16:40 | 1.00 |
| July | 0.288951E+09 | 0.93 | 297.88 | 19-JUL-15:10 | 1.00 |
| August | 0.211336E+09 | 0.80 | 297.39 | 13-AUG-15:30 | 1.00 |
| September | 69187766.08 | 0.50 | 214.02 | 16-SEP-16:10 | 1.03 |
| October | 64962705.37 | 0.65 | 95.81 | 30-OCT-05:00 | 0.94 |
| November | 0.130396E+09 | 0.89 | 102.67 | 24-NOV-04:00 | 0.94 |
| December | 0.276979E+09 | 0.94 | 195.34 | 26-DEC-04:00 | 0.95 |
| Annual Sum or Average | 0.205026E+10 | 0.77 | |||
| Minimum of Months | 40185047.30 | 0.41 | 95.81 | 0.94 | |
| Maximum of Months | 0.288951E+09 | 0.95 | 297.88 | 1.04 |
Report: FanReportMonthly
For: T NW APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.65 | 20.01 | 01-JAN-00:10 | 0.65 |
| February | 48400714.57 | 0.65 | 20.01 | 01-FEB-00:10 | 0.65 |
| March | 53586505.42 | 0.65 | 20.01 | 01-MAR-00:10 | 0.65 |
| April | 51857908.47 | 0.65 | 20.01 | 01-APR-00:10 | 0.65 |
| May | 53586505.42 | 0.65 | 20.01 | 01-MAY-00:10 | 0.65 |
| June | 51857908.47 | 0.64 | 20.01 | 01-JUN-00:10 | 0.64 |
| July | 53586505.42 | 0.64 | 20.01 | 01-JUL-00:10 | 0.64 |
| August | 53586505.42 | 0.64 | 20.01 | 01-AUG-00:10 | 0.64 |
| September | 51857908.47 | 0.64 | 20.01 | 01-SEP-00:10 | 0.64 |
| October | 53586505.42 | 0.65 | 20.01 | 01-OCT-00:10 | 0.64 |
| November | 51857908.47 | 0.65 | 20.01 | 01-NOV-00:10 | 0.65 |
| December | 53586505.42 | 0.65 | 20.01 | 01-DEC-00:10 | 0.65 |
| Annual Sum or Average | 0.630938E+09 | 0.65 | |||
| Minimum of Months | 48400714.57 | 0.64 | 20.01 | 0.64 | |
| Maximum of Months | 53586505.42 | 0.65 | 20.01 | 0.65 |
Report: FanReportMonthly
For: T NW APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.65 | 20.01 | 01-JAN-00:10 | 0.65 |
| February | 48400714.57 | 0.65 | 20.01 | 01-FEB-00:10 | 0.65 |
| March | 53586505.42 | 0.65 | 20.01 | 01-MAR-00:10 | 0.65 |
| April | 51857908.47 | 0.65 | 20.01 | 01-APR-00:10 | 0.65 |
| May | 53586505.42 | 0.65 | 20.01 | 01-MAY-00:10 | 0.64 |
| June | 51857908.47 | 0.64 | 20.01 | 01-JUN-00:10 | 0.64 |
| July | 53586505.42 | 0.64 | 20.01 | 01-JUL-00:10 | 0.64 |
| August | 53586505.42 | 0.64 | 20.01 | 01-AUG-00:10 | 0.64 |
| September | 51857908.47 | 0.64 | 20.01 | 01-SEP-00:10 | 0.64 |
| October | 53586505.42 | 0.65 | 20.01 | 01-OCT-00:10 | 0.64 |
| November | 51857908.47 | 0.65 | 20.01 | 01-NOV-00:10 | 0.65 |
| December | 53586505.42 | 0.65 | 20.01 | 01-DEC-00:10 | 0.65 |
| Annual Sum or Average | 0.630938E+09 | 0.65 | |||
| Minimum of Months | 48400714.57 | 0.64 | 20.01 | 0.64 | |
| Maximum of Months | 53586505.42 | 0.65 | 20.01 | 0.65 |
Report: FanReportMonthly
For: SPLIT TSE SUPPLY FAN
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.252767E+09 | 0.94 | 190.74 | 24-JAN-06:00 | 0.95 |
| February | 0.237861E+09 | 0.93 | 206.16 | 06-FEB-10:00 | 0.95 |
| March | 0.138408E+09 | 0.81 | 189.14 | 15-MAR-13:50 | 1.03 |
| April | 76552276.07 | 0.69 | 117.02 | 22-APR-14:00 | 1.07 |
| May | 56657080.29 | 0.48 | 198.97 | 14-MAY-14:10 | 1.03 |
| June | 0.180230E+09 | 0.74 | 308.81 | 27-JUN-13:00 | 0.98 |
| July | 0.311167E+09 | 0.93 | 309.49 | 21-JUL-13:30 | 0.99 |
| August | 0.247782E+09 | 0.83 | 300.25 | 13-AUG-15:20 | 0.99 |
| September | 0.120892E+09 | 0.61 | 262.09 | 16-SEP-13:30 | 1.00 |
| October | 61892691.47 | 0.61 | 177.18 | 11-OCT-12:40 | 1.04 |
| November | 0.108914E+09 | 0.78 | 100.74 | 24-NOV-04:00 | 0.94 |
| December | 0.250718E+09 | 0.94 | 190.51 | 26-DEC-04:00 | 0.95 |
| Annual Sum or Average | 0.204384E+10 | 0.77 | |||
| Minimum of Months | 56657080.29 | 0.48 | 100.74 | 0.94 | |
| Maximum of Months | 0.311167E+09 | 0.94 | 309.49 | 1.07 |
Report: FanReportMonthly
For: T SE APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.65 | 20.01 | 01-JAN-00:10 | 0.65 |
| February | 48400714.57 | 0.65 | 20.01 | 01-FEB-00:10 | 0.65 |
| March | 53586505.42 | 0.65 | 20.01 | 01-MAR-00:10 | 0.65 |
| April | 51857908.47 | 0.65 | 20.01 | 01-APR-00:10 | 0.65 |
| May | 53586505.42 | 0.65 | 20.01 | 01-MAY-00:10 | 0.65 |
| June | 51857908.47 | 0.64 | 20.01 | 01-JUN-00:10 | 0.64 |
| July | 53586505.42 | 0.64 | 20.01 | 01-JUL-00:10 | 0.64 |
| August | 53586505.42 | 0.64 | 20.01 | 01-AUG-00:10 | 0.64 |
| September | 51857908.47 | 0.64 | 20.01 | 01-SEP-00:10 | 0.64 |
| October | 53586505.42 | 0.65 | 20.01 | 01-OCT-00:10 | 0.64 |
| November | 51857908.47 | 0.65 | 20.01 | 01-NOV-00:10 | 0.65 |
| December | 53586505.42 | 0.65 | 20.01 | 01-DEC-00:10 | 0.65 |
| Annual Sum or Average | 0.630938E+09 | 0.65 | |||
| Minimum of Months | 48400714.57 | 0.64 | 20.01 | 0.64 | |
| Maximum of Months | 53586505.42 | 0.65 | 20.01 | 0.65 |
Report: FanReportMonthly
For: T SE APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.65 | 20.01 | 01-JAN-00:10 | 0.65 |
| February | 48400714.57 | 0.65 | 20.01 | 01-FEB-00:10 | 0.65 |
| March | 53586505.42 | 0.65 | 20.01 | 01-MAR-00:10 | 0.65 |
| April | 51857908.47 | 0.65 | 20.01 | 01-APR-00:10 | 0.65 |
| May | 53586505.42 | 0.65 | 20.01 | 01-MAY-00:10 | 0.64 |
| June | 51857908.47 | 0.64 | 20.01 | 01-JUN-00:10 | 0.64 |
| July | 53586505.42 | 0.64 | 20.01 | 01-JUL-00:10 | 0.64 |
| August | 53586505.42 | 0.64 | 20.01 | 01-AUG-00:10 | 0.64 |
| September | 51857908.47 | 0.64 | 20.01 | 01-SEP-00:10 | 0.64 |
| October | 53586505.42 | 0.65 | 20.01 | 01-OCT-00:10 | 0.64 |
| November | 51857908.47 | 0.65 | 20.01 | 01-NOV-00:10 | 0.65 |
| December | 53586505.42 | 0.65 | 20.01 | 01-DEC-00:10 | 0.65 |
| Annual Sum or Average | 0.630938E+09 | 0.65 | |||
| Minimum of Months | 48400714.57 | 0.64 | 20.01 | 0.64 | |
| Maximum of Months | 53586505.42 | 0.65 | 20.01 | 0.65 |
Report: FanReportMonthly
For: SPLIT TNE SUPPLY FAN
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.280146E+09 | 0.95 | 191.37 | 24-JAN-06:00 | 0.95 |
| February | 0.261268E+09 | 0.95 | 206.44 | 06-FEB-10:00 | 0.95 |
| March | 0.164270E+09 | 0.87 | 153.52 | 07-MAR-04:55 | 0.95 |
| April | 72009771.22 | 0.68 | 115.51 | 16-APR-04:00 | 0.94 |
| May | 33990236.57 | 0.38 | 148.63 | 14-MAY-15:10 | 1.04 |
| June | 0.162276E+09 | 0.74 | 270.66 | 27-JUN-13:00 | 1.00 |
| July | 0.286552E+09 | 0.94 | 264.41 | 21-JUL-10:40 | 1.00 |
| August | 0.207897E+09 | 0.81 | 249.54 | 13-AUG-15:10 | 1.00 |
| September | 65948934.55 | 0.53 | 181.84 | 16-SEP-13:00 | 1.03 |
| October | 61311087.66 | 0.65 | 95.17 | 30-OCT-05:00 | 0.94 |
| November | 0.127307E+09 | 0.89 | 101.47 | 24-NOV-04:00 | 0.94 |
| December | 0.271534E+09 | 0.94 | 191.28 | 26-DEC-04:00 | 0.95 |
| Annual Sum or Average | 0.199451E+10 | 0.78 | |||
| Minimum of Months | 33990236.57 | 0.38 | 95.17 | 0.94 | |
| Maximum of Months | 0.286552E+09 | 0.95 | 270.66 | 1.04 |
Report: FanReportMonthly
For: T NE APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.65 | 20.01 | 01-JAN-00:10 | 0.65 |
| February | 48400714.57 | 0.65 | 20.01 | 01-FEB-00:10 | 0.65 |
| March | 53586505.42 | 0.65 | 20.01 | 01-MAR-00:10 | 0.65 |
| April | 51857908.47 | 0.65 | 20.01 | 01-APR-00:10 | 0.65 |
| May | 53586505.42 | 0.65 | 20.01 | 01-MAY-00:10 | 0.65 |
| June | 51857908.47 | 0.64 | 20.01 | 01-JUN-00:10 | 0.64 |
| July | 53586505.42 | 0.64 | 20.01 | 01-JUL-00:10 | 0.64 |
| August | 53586505.42 | 0.64 | 20.01 | 01-AUG-00:10 | 0.64 |
| September | 51857908.47 | 0.64 | 20.01 | 01-SEP-00:10 | 0.64 |
| October | 53586505.42 | 0.65 | 20.01 | 01-OCT-00:10 | 0.64 |
| November | 51857908.47 | 0.65 | 20.01 | 01-NOV-00:10 | 0.65 |
| December | 53586505.42 | 0.65 | 20.01 | 01-DEC-00:10 | 0.65 |
| Annual Sum or Average | 0.630938E+09 | 0.65 | |||
| Minimum of Months | 48400714.57 | 0.64 | 20.01 | 0.64 | |
| Maximum of Months | 53586505.42 | 0.65 | 20.01 | 0.65 |
Report: FanReportMonthly
For: T NE APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.65 | 20.01 | 01-JAN-00:10 | 0.65 |
| February | 48400714.57 | 0.65 | 20.01 | 01-FEB-00:10 | 0.65 |
| March | 53586505.42 | 0.65 | 20.01 | 01-MAR-00:10 | 0.65 |
| April | 51857908.47 | 0.65 | 20.01 | 01-APR-00:10 | 0.65 |
| May | 53586505.42 | 0.65 | 20.01 | 01-MAY-00:10 | 0.64 |
| June | 51857908.47 | 0.64 | 20.01 | 01-JUN-00:10 | 0.64 |
| July | 53586505.42 | 0.64 | 20.01 | 01-JUL-00:10 | 0.64 |
| August | 53586505.42 | 0.64 | 20.01 | 01-AUG-00:10 | 0.64 |
| September | 51857908.47 | 0.64 | 20.01 | 01-SEP-00:10 | 0.64 |
| October | 53586505.42 | 0.65 | 20.01 | 01-OCT-00:10 | 0.64 |
| November | 51857908.47 | 0.65 | 20.01 | 01-NOV-00:10 | 0.65 |
| December | 53586505.42 | 0.65 | 20.01 | 01-DEC-00:10 | 0.65 |
| Annual Sum or Average | 0.630938E+09 | 0.65 | |||
| Minimum of Months | 48400714.57 | 0.64 | 20.01 | 0.64 | |
| Maximum of Months | 53586505.42 | 0.65 | 20.01 | 0.65 |
Report: FanReportMonthly
For: SPLIT TN1 SUPPLY FAN
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.203645E+09 | 0.95 | 137.98 | 24-JAN-06:00 | 0.95 |
| February | 0.189808E+09 | 0.95 | 150.01 | 07-FEB-08:10 | 0.95 |
| March | 0.119786E+09 | 0.85 | 116.19 | 07-MAR-04:55 | 0.95 |
| April | 48853280.11 | 0.64 | 80.26 | 16-APR-04:00 | 0.94 |
| May | 20824095.30 | 0.29 | 127.31 | 14-MAY-15:10 | 1.05 |
| June | 0.131393E+09 | 0.72 | 212.67 | 27-JUN-13:00 | 1.01 |
| July | 0.239025E+09 | 0.95 | 215.51 | 19-JUL-15:10 | 1.01 |
| August | 0.173992E+09 | 0.85 | 206.48 | 13-AUG-15:20 | 1.01 |
| September | 51978677.19 | 0.47 | 149.10 | 16-SEP-16:10 | 1.04 |
| October | 40016642.19 | 0.58 | 68.99 | 17-OCT-05:00 | 0.94 |
| November | 86665928.19 | 0.86 | 75.24 | 24-NOV-04:00 | 0.94 |
| December | 0.194076E+09 | 0.94 | 137.29 | 26-DEC-04:00 | 0.95 |
| Annual Sum or Average | 0.150006E+10 | 0.75 | |||
| Minimum of Months | 20824095.30 | 0.29 | 68.99 | 0.94 | |
| Maximum of Months | 0.239025E+09 | 0.95 | 215.51 | 1.05 |
Report: FanReportMonthly
For: T N1 APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.65 | 20.01 | 01-JAN-00:10 | 0.65 |
| February | 48400714.57 | 0.65 | 20.01 | 01-FEB-00:10 | 0.65 |
| March | 53586505.42 | 0.65 | 20.01 | 01-MAR-00:10 | 0.65 |
| April | 51857908.47 | 0.65 | 20.01 | 01-APR-00:10 | 0.65 |
| May | 53586505.42 | 0.65 | 20.01 | 01-MAY-00:10 | 0.65 |
| June | 51857908.47 | 0.64 | 20.01 | 01-JUN-00:10 | 0.64 |
| July | 53586505.42 | 0.64 | 20.01 | 01-JUL-00:10 | 0.64 |
| August | 53586505.42 | 0.64 | 20.01 | 01-AUG-00:10 | 0.64 |
| September | 51857908.47 | 0.64 | 20.01 | 01-SEP-00:10 | 0.64 |
| October | 53586505.42 | 0.65 | 20.01 | 01-OCT-00:10 | 0.64 |
| November | 51857908.47 | 0.65 | 20.01 | 01-NOV-00:10 | 0.65 |
| December | 53586505.42 | 0.65 | 20.01 | 01-DEC-00:10 | 0.65 |
| Annual Sum or Average | 0.630938E+09 | 0.65 | |||
| Minimum of Months | 48400714.57 | 0.64 | 20.01 | 0.64 | |
| Maximum of Months | 53586505.42 | 0.65 | 20.01 | 0.65 |
Report: FanReportMonthly
For: T N1 APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.65 | 20.01 | 01-JAN-00:10 | 0.65 |
| February | 48400714.57 | 0.65 | 20.01 | 01-FEB-00:10 | 0.65 |
| March | 53586505.42 | 0.65 | 20.01 | 01-MAR-00:10 | 0.65 |
| April | 51857908.47 | 0.65 | 20.01 | 01-APR-00:10 | 0.65 |
| May | 53586505.42 | 0.65 | 20.01 | 01-MAY-00:10 | 0.64 |
| June | 51857908.47 | 0.64 | 20.01 | 01-JUN-00:10 | 0.64 |
| July | 53586505.42 | 0.64 | 20.01 | 01-JUL-00:10 | 0.65 |
| August | 53586505.42 | 0.64 | 20.01 | 01-AUG-00:10 | 0.64 |
| September | 51857908.47 | 0.64 | 20.01 | 01-SEP-00:10 | 0.64 |
| October | 53586505.42 | 0.65 | 20.01 | 01-OCT-00:10 | 0.64 |
| November | 51857908.47 | 0.65 | 20.01 | 01-NOV-00:10 | 0.65 |
| December | 53586505.42 | 0.65 | 20.01 | 01-DEC-00:10 | 0.65 |
| Annual Sum or Average | 0.630938E+09 | 0.65 | |||
| Minimum of Months | 48400714.57 | 0.64 | 20.01 | 0.64 | |
| Maximum of Months | 53586505.42 | 0.65 | 20.01 | 0.65 |
Report: FanReportMonthly
For: SPLIT TN2 SUPPLY FAN
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.203404E+09 | 0.95 | 137.85 | 24-JAN-06:00 | 0.95 |
| February | 0.189601E+09 | 0.95 | 149.83 | 07-FEB-08:10 | 0.95 |
| March | 0.119794E+09 | 0.85 | 116.25 | 07-MAR-04:55 | 0.95 |
| April | 48809952.36 | 0.64 | 80.15 | 16-APR-04:00 | 0.94 |
| May | 21067038.08 | 0.29 | 126.52 | 14-MAY-15:10 | 1.05 |
| June | 0.131433E+09 | 0.72 | 213.54 | 27-JUN-13:00 | 1.01 |
| July | 0.239186E+09 | 0.95 | 214.78 | 19-JUL-15:10 | 1.01 |
| August | 0.174110E+09 | 0.85 | 205.54 | 13-AUG-15:20 | 1.01 |
| September | 52294885.46 | 0.48 | 148.23 | 16-SEP-16:10 | 1.04 |
| October | 39956015.15 | 0.58 | 69.01 | 17-OCT-05:00 | 0.94 |
| November | 86571257.96 | 0.86 | 75.19 | 24-NOV-04:00 | 0.94 |
| December | 0.193918E+09 | 0.94 | 137.23 | 26-DEC-04:00 | 0.95 |
| Annual Sum or Average | 0.150014E+10 | 0.75 | |||
| Minimum of Months | 21067038.08 | 0.29 | 69.01 | 0.94 | |
| Maximum of Months | 0.239186E+09 | 0.95 | 214.78 | 1.05 |
Report: FanReportMonthly
For: T N2 APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.65 | 20.01 | 01-JAN-00:10 | 0.65 |
| February | 48400714.57 | 0.65 | 20.01 | 01-FEB-00:10 | 0.65 |
| March | 53586505.42 | 0.65 | 20.01 | 01-MAR-00:10 | 0.65 |
| April | 51857908.47 | 0.65 | 20.01 | 01-APR-00:10 | 0.65 |
| May | 53586505.42 | 0.65 | 20.01 | 01-MAY-00:10 | 0.65 |
| June | 51857908.47 | 0.64 | 20.01 | 01-JUN-00:10 | 0.64 |
| July | 53586505.42 | 0.64 | 20.01 | 01-JUL-00:10 | 0.64 |
| August | 53586505.42 | 0.64 | 20.01 | 01-AUG-00:10 | 0.64 |
| September | 51857908.47 | 0.64 | 20.01 | 01-SEP-00:10 | 0.64 |
| October | 53586505.42 | 0.65 | 20.01 | 01-OCT-00:10 | 0.64 |
| November | 51857908.47 | 0.65 | 20.01 | 01-NOV-00:10 | 0.65 |
| December | 53586505.42 | 0.65 | 20.01 | 01-DEC-00:10 | 0.65 |
| Annual Sum or Average | 0.630938E+09 | 0.65 | |||
| Minimum of Months | 48400714.57 | 0.64 | 20.01 | 0.64 | |
| Maximum of Months | 53586505.42 | 0.65 | 20.01 | 0.65 |
Report: FanReportMonthly
For: T N2 APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.65 | 20.01 | 01-JAN-00:10 | 0.65 |
| February | 48400714.57 | 0.65 | 20.01 | 01-FEB-00:10 | 0.65 |
| March | 53586505.42 | 0.65 | 20.01 | 01-MAR-00:10 | 0.65 |
| April | 51857908.47 | 0.65 | 20.01 | 01-APR-00:10 | 0.65 |
| May | 53586505.42 | 0.65 | 20.01 | 01-MAY-00:10 | 0.64 |
| June | 51857908.47 | 0.64 | 20.01 | 01-JUN-00:10 | 0.64 |
| July | 53586505.42 | 0.64 | 20.01 | 01-JUL-00:10 | 0.65 |
| August | 53586505.42 | 0.64 | 20.01 | 01-AUG-00:10 | 0.64 |
| September | 51857908.47 | 0.64 | 20.01 | 01-SEP-00:10 | 0.64 |
| October | 53586505.42 | 0.65 | 20.01 | 01-OCT-00:10 | 0.64 |
| November | 51857908.47 | 0.65 | 20.01 | 01-NOV-00:10 | 0.65 |
| December | 53586505.42 | 0.65 | 20.01 | 01-DEC-00:10 | 0.65 |
| Annual Sum or Average | 0.630938E+09 | 0.65 | |||
| Minimum of Months | 48400714.57 | 0.64 | 20.01 | 0.64 | |
| Maximum of Months | 53586505.42 | 0.65 | 20.01 | 0.65 |
Report: FanReportMonthly
For: SPLIT TS1 SUPPLY FAN
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.176563E+09 | 0.93 | 137.28 | 24-JAN-06:00 | 0.95 |
| February | 0.166773E+09 | 0.92 | 148.80 | 07-FEB-05:00 | 0.95 |
| March | 94631557.72 | 0.75 | 168.75 | 15-MAR-13:50 | 1.04 |
| April | 49644943.53 | 0.64 | 96.94 | 22-APR-14:10 | 1.07 |
| May | 40516649.47 | 0.41 | 179.23 | 14-MAY-14:10 | 1.03 |
| June | 0.149333E+09 | 0.74 | 252.11 | 27-JUN-13:00 | 1.00 |
| July | 0.265078E+09 | 0.94 | 258.20 | 21-JUL-13:30 | 1.00 |
| August | 0.215703E+09 | 0.87 | 258.75 | 13-AUG-15:20 | 1.00 |
| September | 0.107936E+09 | 0.61 | 228.32 | 16-SEP-13:30 | 1.01 |
| October | 42268782.83 | 0.54 | 159.48 | 11-OCT-14:30 | 1.04 |
| November | 69804168.85 | 0.73 | 74.42 | 24-NOV-04:00 | 0.94 |
| December | 0.173550E+09 | 0.93 | 136.78 | 26-DEC-05:00 | 0.95 |
| Annual Sum or Average | 0.155180E+10 | 0.75 | |||
| Minimum of Months | 40516649.47 | 0.41 | 74.42 | 0.94 | |
| Maximum of Months | 0.265078E+09 | 0.94 | 258.75 | 1.07 |
Report: FanReportMonthly
For: T S1 APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.65 | 20.01 | 01-JAN-00:10 | 0.65 |
| February | 48400714.57 | 0.65 | 20.01 | 01-FEB-00:10 | 0.65 |
| March | 53586505.42 | 0.65 | 20.01 | 01-MAR-00:10 | 0.65 |
| April | 51857908.47 | 0.65 | 20.01 | 01-APR-00:10 | 0.65 |
| May | 53586505.42 | 0.65 | 20.01 | 01-MAY-00:10 | 0.65 |
| June | 51857908.47 | 0.64 | 20.01 | 01-JUN-00:10 | 0.64 |
| July | 53586505.42 | 0.64 | 20.01 | 01-JUL-00:10 | 0.64 |
| August | 53586505.42 | 0.64 | 20.01 | 01-AUG-00:10 | 0.64 |
| September | 51857908.47 | 0.64 | 20.01 | 01-SEP-00:10 | 0.64 |
| October | 53586505.42 | 0.65 | 20.01 | 01-OCT-00:10 | 0.64 |
| November | 51857908.47 | 0.65 | 20.01 | 01-NOV-00:10 | 0.65 |
| December | 53586505.42 | 0.65 | 20.01 | 01-DEC-00:10 | 0.65 |
| Annual Sum or Average | 0.630938E+09 | 0.65 | |||
| Minimum of Months | 48400714.57 | 0.64 | 20.01 | 0.64 | |
| Maximum of Months | 53586505.42 | 0.65 | 20.01 | 0.65 |
Report: FanReportMonthly
For: T S1 APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.65 | 20.01 | 01-JAN-00:10 | 0.65 |
| February | 48400714.57 | 0.65 | 20.01 | 01-FEB-00:10 | 0.65 |
| March | 53586505.42 | 0.65 | 20.01 | 01-MAR-00:10 | 0.65 |
| April | 51857908.47 | 0.65 | 20.01 | 01-APR-00:10 | 0.65 |
| May | 53586505.42 | 0.65 | 20.01 | 01-MAY-00:10 | 0.64 |
| June | 51857908.47 | 0.64 | 20.01 | 01-JUN-00:10 | 0.64 |
| July | 53586505.42 | 0.64 | 20.01 | 01-JUL-00:10 | 0.65 |
| August | 53586505.42 | 0.64 | 20.01 | 01-AUG-00:10 | 0.64 |
| September | 51857908.47 | 0.64 | 20.01 | 01-SEP-00:10 | 0.64 |
| October | 53586505.42 | 0.65 | 20.01 | 01-OCT-00:10 | 0.64 |
| November | 51857908.47 | 0.65 | 20.01 | 01-NOV-00:10 | 0.65 |
| December | 53586505.42 | 0.65 | 20.01 | 01-DEC-00:10 | 0.65 |
| Annual Sum or Average | 0.630938E+09 | 0.65 | |||
| Minimum of Months | 48400714.57 | 0.64 | 20.01 | 0.64 | |
| Maximum of Months | 53586505.42 | 0.65 | 20.01 | 0.65 |
Report: FanReportMonthly
For: SPLIT TS2 SUPPLY FAN
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.176343E+09 | 0.93 | 137.15 | 24-JAN-06:00 | 0.95 |
| February | 0.166591E+09 | 0.92 | 148.74 | 07-FEB-05:00 | 0.95 |
| March | 94704122.19 | 0.75 | 169.27 | 15-MAR-13:50 | 1.04 |
| April | 50012387.06 | 0.64 | 98.91 | 22-APR-14:10 | 1.07 |
| May | 41028860.83 | 0.42 | 178.95 | 14-MAY-14:10 | 1.03 |
| June | 0.149454E+09 | 0.74 | 252.94 | 27-JUN-13:00 | 1.00 |
| July | 0.265233E+09 | 0.94 | 258.79 | 21-JUL-13:30 | 1.00 |
| August | 0.215792E+09 | 0.87 | 257.82 | 13-AUG-15:20 | 1.00 |
| September | 0.108317E+09 | 0.61 | 228.70 | 16-SEP-13:30 | 1.01 |
| October | 42458507.65 | 0.54 | 159.99 | 11-OCT-14:30 | 1.04 |
| November | 69766599.90 | 0.73 | 74.41 | 24-NOV-04:00 | 0.94 |
| December | 0.173416E+09 | 0.93 | 136.63 | 26-DEC-05:00 | 0.95 |
| Annual Sum or Average | 0.155312E+10 | 0.75 | |||
| Minimum of Months | 41028860.83 | 0.42 | 74.41 | 0.94 | |
| Maximum of Months | 0.265233E+09 | 0.94 | 258.79 | 1.07 |
Report: FanReportMonthly
For: T S2 APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.65 | 20.01 | 01-JAN-00:10 | 0.65 |
| February | 48400714.57 | 0.65 | 20.01 | 01-FEB-00:10 | 0.65 |
| March | 53586505.42 | 0.65 | 20.01 | 01-MAR-00:10 | 0.65 |
| April | 51857908.47 | 0.65 | 20.01 | 01-APR-00:10 | 0.65 |
| May | 53586505.42 | 0.65 | 20.01 | 01-MAY-00:10 | 0.65 |
| June | 51857908.47 | 0.64 | 20.01 | 01-JUN-00:10 | 0.64 |
| July | 53586505.42 | 0.64 | 20.01 | 01-JUL-00:10 | 0.64 |
| August | 53586505.42 | 0.64 | 20.01 | 01-AUG-00:10 | 0.64 |
| September | 51857908.47 | 0.64 | 20.01 | 01-SEP-00:10 | 0.64 |
| October | 53586505.42 | 0.65 | 20.01 | 01-OCT-00:10 | 0.64 |
| November | 51857908.47 | 0.65 | 20.01 | 01-NOV-00:10 | 0.65 |
| December | 53586505.42 | 0.65 | 20.01 | 01-DEC-00:10 | 0.65 |
| Annual Sum or Average | 0.630938E+09 | 0.65 | |||
| Minimum of Months | 48400714.57 | 0.64 | 20.01 | 0.64 | |
| Maximum of Months | 53586505.42 | 0.65 | 20.01 | 0.65 |
Report: FanReportMonthly
For: T S2 APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.65 | 20.01 | 01-JAN-00:10 | 0.65 |
| February | 48400714.57 | 0.65 | 20.01 | 01-FEB-00:10 | 0.65 |
| March | 53586505.42 | 0.65 | 20.01 | 01-MAR-00:10 | 0.65 |
| April | 51857908.47 | 0.65 | 20.01 | 01-APR-00:10 | 0.65 |
| May | 53586505.42 | 0.65 | 20.01 | 01-MAY-00:10 | 0.64 |
| June | 51857908.47 | 0.64 | 20.01 | 01-JUN-00:10 | 0.64 |
| July | 53586505.42 | 0.64 | 20.01 | 01-JUL-00:10 | 0.65 |
| August | 53586505.42 | 0.64 | 20.01 | 01-AUG-00:10 | 0.64 |
| September | 51857908.47 | 0.64 | 20.01 | 01-SEP-00:10 | 0.64 |
| October | 53586505.42 | 0.65 | 20.01 | 01-OCT-00:10 | 0.64 |
| November | 51857908.47 | 0.65 | 20.01 | 01-NOV-00:10 | 0.65 |
| December | 53586505.42 | 0.65 | 20.01 | 01-DEC-00:10 | 0.65 |
| Annual Sum or Average | 0.630938E+09 | 0.65 | |||
| Minimum of Months | 48400714.57 | 0.64 | 20.01 | 0.64 | |
| Maximum of Months | 53586505.42 | 0.65 | 20.01 | 0.65 |
Report: ZoneTemperatureOscillationReportMonthly
For: G SW APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: G NW APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: OFFICE
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: G NE APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: G N1 APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: G N2 APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: G S1 APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: G S2 APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: M SW APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: M NW APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: M SE APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: M NE APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: M N1 APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: M N2 APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: M S1 APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: M S2 APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: T SW APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: T NW APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: T SE APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: T NE APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: T N1 APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: T N2 APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: T S1 APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: T S2 APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: T CORRIDOR
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: G CORRIDOR
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: M CORRIDOR
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT GSW
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.181936E+09 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.176798E+09 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.106188E+09 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 55529606.32 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 15220141.94 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.397126E+09 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.941115E+09 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.856045E+09 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.439818E+09 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 23879516.46 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 52033796.52 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.164895E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.341058E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 15220141.94 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.941115E+09 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT GNW
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.205857E+09 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.197667E+09 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.136415E+09 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 72560641.28 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 12806613.83 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.333250E+09 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.834030E+09 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.687802E+09 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.219522E+09 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 21487885.70 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 71013063.94 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.183406E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.297582E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 12806613.83 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.834030E+09 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT OFFICE
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.114110E+10 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.103067E+10 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.114551E+10 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.110429E+10 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.119341E+10 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.142423E+10 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.164521E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.166800E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.142003E+10 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.119926E+10 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.110467E+10 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.114110E+10 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.152175E+11 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.103067E+10 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.166800E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT GNE
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.200653E+09 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.193043E+09 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.134446E+09 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 69610629.46 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 12212749.38 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.317050E+09 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.831529E+09 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.678821E+09 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.222088E+09 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 19986949.33 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 69302046.50 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.180175E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.292892E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 12212749.38 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.831529E+09 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT GN1
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.142440E+09 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.138007E+09 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 94532365.28 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 46523236.09 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 5970156.02 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.280668E+09 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.729893E+09 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.595899E+09 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.203874E+09 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 9848066.16 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 43518642.85 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.125805E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.241698E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 5970156.02 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.729893E+09 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT GN2
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.142312E+09 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.137900E+09 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 94505946.30 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 46427377.99 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 5984945.48 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.280155E+09 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.730164E+09 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.595704E+09 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.204959E+09 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 9792058.87 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 43469823.31 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.125746E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.241712E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 5984945.48 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.730164E+09 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT GS1
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.120215E+09 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.118474E+09 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 66614679.97 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 31228569.17 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 8217254.32 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.350728E+09 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.843351E+09 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.772577E+09 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.444931E+09 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 24178421.18 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 26796026.49 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.108640E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.291595E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 8217254.32 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.843351E+09 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT GS2
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.132265E+09 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.129031E+09 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 73307196.70 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 33940956.29 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 10934172.07 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.387317E+09 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.920376E+09 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.846668E+09 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.490415E+09 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 28087870.38 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 29161090.96 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.118660E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.320016E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 10934172.07 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.920376E+09 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT MSW
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.314294E+09 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.300571E+09 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.171734E+09 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 92777016.89 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.475786E+09 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.161593E+10 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.261228E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.218646E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.117194E+10 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.117318E+09 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 97808634.98 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.311174E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.946807E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 92777016.89 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.261228E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT MNW
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.365513E+09 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.344637E+09 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.199743E+09 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 59522818.05 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.275226E+09 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.146298E+10 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.239117E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.183269E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.671757E+09 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 40277046.66 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.135294E+09 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.350672E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.812948E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 40277046.66 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.239117E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT MSE
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.305733E+09 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.293002E+09 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.174416E+09 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.101401E+09 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.474423E+09 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.157850E+10 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.260912E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.217185E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.119116E+10 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.117958E+09 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 95259228.94 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.306122E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.941894E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 95259228.94 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.260912E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT MNE
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.355864E+09 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.336259E+09 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.199671E+09 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 56596034.50 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.264076E+09 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.142489E+10 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.238846E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.182017E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.685843E+09 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 35882179.98 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.132079E+09 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.344764E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.804455E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 35882179.98 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.238846E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT MN1
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.233241E+09 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.222912E+09 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.132671E+09 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 30518705.01 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.221641E+09 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.115381E+10 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.194918E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.151288E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.603081E+09 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 13798524.65 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 70469747.24 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.220791E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.636499E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 13798524.65 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.194918E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT MN2
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.233006E+09 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.222722E+09 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.132982E+09 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 30461160.59 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.223079E+09 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.115313E+10 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.194961E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.151280E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.605108E+09 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 13815040.50 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 70365216.31 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.220691E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.636778E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 13815040.50 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.194961E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT MS1
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.185263E+09 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.181414E+09 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.113455E+09 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 65190018.82 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.433745E+09 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.131122E+10 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.217675E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.187385E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.113252E+10 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.149353E+09 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 41026898.29 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.183930E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.784772E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 41026898.29 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.217675E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT MS2
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.185035E+09 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.181235E+09 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.113755E+09 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 67131197.26 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.435340E+09 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.131057E+10 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.217713E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.187373E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.113365E+10 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.151424E+09 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 41054765.71 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.183846E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.785390E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 41054765.71 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.217713E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT TSW
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.259743E+09 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.244161E+09 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.168235E+09 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.129569E+09 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.231885E+09 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.809285E+09 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.137643E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.109802E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.512538E+09 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.116135E+09 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.112020E+09 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.255663E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.531368E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.112020E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.137643E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT TNW
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.287770E+09 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.268075E+09 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.181772E+09 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 81719191.78 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.140305E+09 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.731537E+09 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.126360E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.920030E+09 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.284196E+09 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 68365025.85 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.130396E+09 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.276979E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.463474E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 68365025.85 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.126360E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT TSE
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.252767E+09 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.237861E+09 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.167860E+09 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.125766E+09 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.216336E+09 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.782331E+09 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.136844E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.108455E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.511952E+09 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.110960E+09 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.108918E+09 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.250718E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.521845E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.108918E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.136844E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT TNE
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.280146E+09 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.261268E+09 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.180449E+09 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 73685262.09 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.116064E+09 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.704934E+09 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.126046E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.910556E+09 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.272454E+09 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 63591823.04 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.127307E+09 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.271534E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.452245E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 63591823.04 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.126046E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT TN1
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.203645E+09 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.189808E+09 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.132186E+09 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 49138563.98 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 75563598.78 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.569222E+09 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.104510E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.757226E+09 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.219049E+09 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 40984183.77 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 86665928.19 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.194076E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.356266E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 40984183.77 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.104510E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT TN2
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.203404E+09 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.189601E+09 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.132369E+09 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 49147492.35 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 76442505.85 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.569362E+09 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.104579E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.757737E+09 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.220365E+09 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 40959191.79 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 86571257.96 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.193918E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.356566E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 40959191.79 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.104579E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT TS1
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.176563E+09 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.166773E+09 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.120600E+09 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 84968625.96 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.162104E+09 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.646012E+09 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.115858E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.937996E+09 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.459901E+09 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 90473994.17 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 70217779.63 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.173550E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.424774E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 70217779.63 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.115858E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT TS2
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.176343E+09 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.166591E+09 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.120850E+09 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 86429291.79 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.164127E+09 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.646505E+09 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.115923E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.938378E+09 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.461496E+09 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 91395477.47 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 70232040.05 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.173416E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.425500E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 70232040.05 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.115923E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT GSW
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 0.181936E+09 | 0.00 | 0.416383E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.176798E+09 | 0.00 | 0.404625E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.105913E+09 | 1032688.59 | 0.242206E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 55529606.32 | 0.00 | 0.127086E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 9664433.10 | 21210952.10 | 0.182497E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 90990194.26 | 0.121814E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.214116E+09 | 0.291949E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.196002E+09 | 0.263024E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.101862E+09 | 0.135054E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 12388402.58 | 44656957.56 | 0.203483E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 52033796.52 | 0.00 | 0.119086E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.164895E+09 | 0.00 | 0.377383E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.136213E+10 | 0.818531E+10 | 0.172537E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 9664433.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.214116E+09 | 0.291949E+10 | 0.416383E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT GNW
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 0.205857E+09 | 0.00 | 0.475079E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.197667E+09 | 0.00 | 0.456180E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.136415E+09 | 0.00 | 0.314821E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 72560641.28 | 0.00 | 0.167456E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 12700653.67 | 404426.17 | 0.292366E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 75958091.66 | 0.102517E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.188926E+09 | 0.259042E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.156735E+09 | 0.211101E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 50465505.63 | 0.676624E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 21487885.70 | 0.00 | 0.495900E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 71013063.94 | 0.00 | 0.163885E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.183406E+09 | 0.00 | 0.423267E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.137319E+10 | 0.640363E+10 | 0.207951E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 12700653.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.205857E+09 | 0.259042E+10 | 0.475079E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT OFFICE
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 0.114110E+10 | 0.00 | 0.226485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.103067E+10 | 0.00 | 0.229574E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.114110E+10 | 16902764.45 | 0.959692E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.110429E+10 | 0.00 | 0.217863E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.114110E+10 | 0.203090E+09 | 1152951.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.110429E+10 | 0.130037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.114110E+10 | 0.208649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.114110E+10 | 0.217351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.110429E+10 | 0.129492E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.114110E+10 | 0.227398E+09 | 3446009.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.110429E+10 | 1394366.58 | 0.204436E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.114110E+10 | 0.00 | 0.183885E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.134356E+11 | 0.730408E+10 | 0.778603E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 0.103067E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.114110E+10 | 0.217351E+10 | 0.229574E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT GNE
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 0.200653E+09 | 0.00 | 0.470770E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.193043E+09 | 0.00 | 0.452916E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.134446E+09 | 0.00 | 0.315437E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 69610629.46 | 0.00 | 0.163320E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 12212749.38 | 0.00 | 0.286535E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 71240789.27 | 0.981350E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.185871E+09 | 0.260142E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.152616E+09 | 0.209754E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 50361064.80 | 0.689213E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 19986949.33 | 0.00 | 0.468932E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 69302046.50 | 0.00 | 0.162596E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.180175E+09 | 0.00 | 0.422726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.133952E+10 | 0.636953E+10 | 0.206331E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 12212749.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.200653E+09 | 0.260142E+10 | 0.470770E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT GN1
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 0.142440E+09 | 0.00 | 0.338884E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.138007E+09 | 0.00 | 0.328338E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 94532365.28 | 0.00 | 0.224905E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 46523236.09 | 0.00 | 0.110685E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 5970156.02 | 0.00 | 0.142038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 63065600.78 | 0.868475E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.163110E+09 | 0.228211E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.133972E+09 | 0.183972E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 46189502.62 | 0.633418E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 9848066.16 | 0.00 | 0.234299E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 43518642.85 | 0.00 | 0.103537E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.125805E+09 | 0.00 | 0.299307E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.101298E+10 | 0.562373E+10 | 0.144329E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 5970156.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.163110E+09 | 0.228211E+10 | 0.338884E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT GN2
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 0.142312E+09 | 0.00 | 0.338711E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.137900E+09 | 0.00 | 0.328209E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 94505946.30 | 0.00 | 0.224929E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 46427377.99 | 0.00 | 0.110500E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 5984945.48 | 0.00 | 0.142445E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 62931619.54 | 0.866994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.163128E+09 | 0.228327E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.133893E+09 | 0.183931E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 46424563.19 | 0.636822E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 9792058.87 | 0.00 | 0.233056E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 43469823.31 | 0.00 | 0.103461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.125746E+09 | 0.00 | 0.299282E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.101252E+10 | 0.562640E+10 | 0.144264E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 5984945.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.163128E+09 | 0.228327E+10 | 0.338711E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT GS1
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 0.120215E+09 | 0.00 | 0.282280E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.118474E+09 | 0.00 | 0.278191E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 66145717.60 | 1761378.03 | 0.154994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 31228569.17 | 0.00 | 0.733286E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 4058461.33 | 15844479.86 | 66034277.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 79366702.29 | 0.108096E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.189585E+09 | 0.263171E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.174795E+09 | 0.238631E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.101772E+09 | 0.137296E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 6814476.10 | 67367609.59 | 37934777.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 26796026.49 | 0.00 | 0.629204E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.108640E+09 | 0.00 | 0.255101E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.102789E+10 | 0.755692E+10 | 0.111721E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 4058461.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.189585E+09 | 0.263171E+10 | 0.282280E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT GS2
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 0.132265E+09 | 0.00 | 0.310275E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.129031E+09 | 0.00 | 0.302689E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 72878311.38 | 1610262.51 | 0.170665E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 33940956.29 | 0.00 | 0.796205E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 4668828.13 | 23892882.29 | 65402024.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 87760456.13 | 0.119460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.207180E+09 | 0.287636E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.191788E+09 | 0.261987E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.112267E+09 | 0.151415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 7667951.07 | 79216186.77 | 36364690.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 29161090.96 | 0.00 | 0.684076E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.118660E+09 | 0.00 | 0.278358E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.112727E+10 | 0.830969E+10 | 0.122019E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 4668828.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.207180E+09 | 0.287636E+10 | 0.310275E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT MSW
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 0.314294E+09 | 0.00 | 0.699612E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.300571E+09 | 0.00 | 0.669065E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.136482E+09 | 0.136795E+09 | 0.280034E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 53233374.39 | 0.150564E+09 | 0.911471E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.111979E+09 | 0.141156E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.373992E+09 | 0.495205E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.598670E+09 | 0.808663E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.503696E+09 | 0.669653E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.273097E+09 | 0.358682E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 40234001.00 | 0.299865E+09 | 0.369399E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 97808634.98 | 0.00 | 0.217720E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.311174E+09 | 0.00 | 0.692669E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.311523E+10 | 0.253208E+11 | 0.268719E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 40234001.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.598670E+09 | 0.808663E+10 | 0.699612E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT MNW
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 0.365513E+09 | 0.00 | 0.816938E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.344637E+09 | 0.00 | 0.770279E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.188247E+09 | 44049262.37 | 0.412958E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 59297178.65 | 857810.16 | 0.132377E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 64671050.18 | 0.815690E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.338344E+09 | 0.448615E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.547845E+09 | 0.739812E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.421946E+09 | 0.559953E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.156095E+09 | 0.205505E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 39301932.51 | 3732081.57 | 0.871730E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.135294E+09 | 0.00 | 0.302388E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.350672E+09 | 0.00 | 0.783766E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.301186E+10 | 0.204032E+11 | 0.330588E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 39301932.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.547845E+09 | 0.739812E+10 | 0.816938E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT MSE
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 0.305733E+09 | 0.00 | 0.690300E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.293002E+09 | 0.00 | 0.661555E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.135888E+09 | 0.150056E+09 | 0.280583E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 53867127.59 | 0.181032E+09 | 0.884238E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.111211E+09 | 0.140961E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.363899E+09 | 0.485786E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.595885E+09 | 0.812646E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.498534E+09 | 0.668989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.276533E+09 | 0.366182E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 39357781.24 | 0.305880E+09 | 0.346844E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 95259228.94 | 0.00 | 0.215081E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.306122E+09 | 0.00 | 0.691178E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.307529E+10 | 0.253826E+11 | 0.266181E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 39357781.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.595885E+09 | 0.812646E+10 | 0.691178E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT MNE
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 0.355864E+09 | 0.00 | 0.807546E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.336259E+09 | 0.00 | 0.763058E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.186636E+09 | 50059107.42 | 0.414633E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 56596034.50 | 0.00 | 0.128431E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 61666975.06 | 0.783817E+09 | 772794.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.327461E+09 | 0.438910E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.544068E+09 | 0.743706E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.416589E+09 | 0.559238E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.158390E+09 | 0.210608E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 35818981.09 | 240528.53 | 0.812388E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.132079E+09 | 0.00 | 0.299722E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.344764E+09 | 0.00 | 0.782359E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.295619E+10 | 0.203587E+11 | 0.327706E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 35818981.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.544068E+09 | 0.743706E+10 | 0.807546E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT MN1
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 0.233241E+09 | 0.00 | 0.536617E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.222912E+09 | 0.00 | 0.512853E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.121422E+09 | 43200670.48 | 0.271568E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 30518705.01 | 0.00 | 0.702144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 51693700.12 | 0.657872E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.265184E+09 | 0.354560E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.444045E+09 | 0.605459E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.346459E+09 | 0.463856E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.139240E+09 | 0.185335E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 12982896.08 | 3108617.00 | 0.292978E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 70469747.24 | 0.00 | 0.162130E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.220791E+09 | 0.00 | 0.507974E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.215896E+10 | 0.167963E+11 | 0.209066E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 12982896.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.444045E+09 | 0.605459E+10 | 0.536617E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT MN2
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 0.233006E+09 | 0.00 | 0.536266E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.222722E+09 | 0.00 | 0.512597E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.121474E+09 | 44203032.59 | 0.271606E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 30461160.59 | 0.00 | 0.701067E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 52016934.49 | 0.662179E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.264958E+09 | 0.354382E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.444028E+09 | 0.605682E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.346348E+09 | 0.463890E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.139674E+09 | 0.185971E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 12940084.86 | 3335822.15 | 0.291682E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 70365216.31 | 0.00 | 0.161946E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.220691E+09 | 0.00 | 0.507922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.215869E+10 | 0.168090E+11 | 0.208961E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 12940084.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.444028E+09 | 0.605682E+10 | 0.536266E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT MS1
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 0.185263E+09 | 0.00 | 0.423130E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.181414E+09 | 0.00 | 0.414340E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 74258258.68 | 0.152621E+09 | 0.142538E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 28316256.87 | 0.140351E+09 | 0.385865E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.101759E+09 | 0.128635E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.302682E+09 | 0.402062E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.497736E+09 | 0.675715E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.430851E+09 | 0.575324E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.263274E+09 | 0.347300E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 36561974.59 | 0.438793E+09 | 47738333.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 40481386.79 | 2051508.60 | 0.920705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.183930E+09 | 0.00 | 0.420086E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.232653E+10 | 0.220242E+11 | 0.153553E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 28316256.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.497736E+09 | 0.675715E+10 | 0.423130E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT MS2
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 0.185035E+09 | 0.00 | 0.422754E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.181235E+09 | 0.00 | 0.414070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 74375769.63 | 0.153346E+09 | 0.142738E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 28770455.39 | 0.146065E+09 | 0.385952E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.102108E+09 | 0.129121E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.302449E+09 | 0.401909E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.497688E+09 | 0.675949E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.430704E+09 | 0.575380E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.263465E+09 | 0.347710E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 37020291.41 | 0.445092E+09 | 47222570.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 40457364.88 | 2247010.84 | 0.920100E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.183846E+09 | 0.00 | 0.420036E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.232715E+10 | 0.220474E+11 | 0.153493E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 28770455.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.497688E+09 | 0.675949E+10 | 0.422754E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT TSW
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 0.259743E+09 | 0.00 | 0.572669E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.244161E+09 | 0.00 | 0.538314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.140246E+09 | 0.110085E+09 | 0.290525E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 79398599.71 | 0.192316E+09 | 0.140672E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 60990981.57 | 0.666824E+09 | 0.184094E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.187728E+09 | 0.249142E+10 | 21053804.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.314862E+09 | 0.427648E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.252409E+09 | 0.337590E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.121797E+09 | 0.156693E+10 | 69102494.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 64792751.86 | 0.200094E+09 | 0.107997E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.111726E+09 | 1105309.90 | 0.246124E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.255663E+09 | 0.00 | 0.563672E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.209352E+10 | 0.128812E+11 | 0.248740E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 60990981.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.314862E+09 | 0.427648E+10 | 0.572669E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT TNW
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 0.287770E+09 | 0.00 | 0.635325E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.268075E+09 | 0.00 | 0.591842E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.166722E+09 | 58415971.21 | 0.358027E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 76225476.79 | 20877389.52 | 0.164536E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 40185047.30 | 0.389164E+09 | 0.207731E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.169472E+09 | 0.225051E+10 | 17262168.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.288951E+09 | 0.391641E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.211336E+09 | 0.281438E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 69187766.08 | 0.859417E+09 | 92933199.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 64962705.37 | 13143563.95 | 0.141117E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.130396E+09 | 0.00 | 0.287883E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.276979E+09 | 0.00 | 0.611501E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.205026E+10 | 0.103223E+11 | 0.282202E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 40185047.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.288951E+09 | 0.391641E+10 | 0.635325E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT TSE
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 0.252767E+09 | 0.00 | 0.567376E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.237861E+09 | 0.00 | 0.533917E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.138408E+09 | 0.116795E+09 | 0.290829E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 76552276.07 | 0.188665E+09 | 0.137750E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 56657080.29 | 0.623881E+09 | 0.177355E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.180230E+09 | 0.242725E+10 | 19660790.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.311167E+09 | 0.429335E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.247782E+09 | 0.336519E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.120892E+09 | 0.157676E+10 | 70185626.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 61892691.47 | 0.191540E+09 | 0.105287E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.108914E+09 | 11620.04 | 0.244474E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.250718E+09 | 0.00 | 0.562778E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.204384E+10 | 0.127834E+11 | 0.246913E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 56657080.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.311167E+09 | 0.429335E+10 | 0.567376E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT TNE
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 0.280146E+09 | 0.00 | 0.630036E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.261268E+09 | 0.00 | 0.587579E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.164270E+09 | 63073528.00 | 0.358517E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 72009771.22 | 6370889.47 | 0.160793E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 33990236.57 | 0.319302E+09 | 0.202514E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.162276E+09 | 0.218345E+10 | 18917472.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.286552E+09 | 0.394083E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.207897E+09 | 0.280628E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 65948934.55 | 0.829763E+09 | 92438482.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 61311087.66 | 8746408.86 | 0.136325E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.127307E+09 | 0.00 | 0.286307E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.271534E+09 | 0.00 | 0.610668E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.199451E+10 | 0.101578E+11 | 0.280161E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 33990236.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.286552E+09 | 0.394083E+10 | 0.630036E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT TN1
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 0.203645E+09 | 0.00 | 0.461357E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.189808E+09 | 0.00 | 0.430009E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.119786E+09 | 48136796.01 | 0.262870E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 48853280.11 | 1085936.39 | 0.110478E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 20824095.30 | 0.212419E+09 | 91739659.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.131393E+09 | 0.175342E+10 | 3489824.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.239025E+09 | 0.324449E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.173992E+09 | 0.231893E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 51978677.19 | 0.671910E+09 | 36554296.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 40016642.19 | 3706297.88 | 0.899852E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 86665928.19 | 0.00 | 0.196341E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.194076E+09 | 0.00 | 0.439678E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.150006E+10 | 0.825409E+10 | 0.200390E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 20824095.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.239025E+09 | 0.324449E+10 | 0.461357E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT TN2
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 0.203404E+09 | 0.00 | 0.461163E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.189601E+09 | 0.00 | 0.429870E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.119794E+09 | 48827218.91 | 0.262972E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 48809952.36 | 1284824.33 | 0.110428E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 21067038.08 | 0.214901E+09 | 92866934.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.131433E+09 | 0.175411E+10 | 3688864.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.239186E+09 | 0.324746E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.174110E+09 | 0.232099E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 52294885.46 | 0.675978E+09 | 36843562.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 39956015.15 | 3842203.02 | 0.898919E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 86571257.96 | 0.00 | 0.196277E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.193918E+09 | 0.00 | 0.439656E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.150014E+10 | 0.826739E+10 | 0.200360E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 21067038.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.239186E+09 | 0.324746E+10 | 0.461163E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT TS1
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 0.176563E+09 | 0.00 | 0.398951E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.166773E+09 | 0.00 | 0.376831E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 94631557.72 | 0.102473E+09 | 0.196054E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 49644943.53 | 0.135108E+09 | 0.873599E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 40516649.47 | 0.473434E+09 | 70344281.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.149333E+09 | 0.199143E+10 | 4801706.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.265078E+09 | 0.360716E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.215703E+09 | 0.288943E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.107936E+09 | 0.141518E+10 | 24892815.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 42268782.83 | 0.187934E+09 | 0.619708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 69804168.85 | 1553071.29 | 0.157434E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.173550E+09 | 0.00 | 0.392143E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.155180E+10 | 0.108037E+11 | 0.168075E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 40516649.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.265078E+09 | 0.360716E+10 | 0.398951E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT TS2
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 0.176343E+09 | 0.00 | 0.398747E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.166591E+09 | 0.00 | 0.376695E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 94704122.19 | 0.103218E+09 | 0.196240E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 50012387.06 | 0.139341E+09 | 0.874845E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 41028860.83 | 0.479399E+09 | 71402996.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.149454E+09 | 0.199337E+10 | 4930680.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.265233E+09 | 0.361038E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.215792E+09 | 0.289153E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.108317E+09 | 0.142048E+10 | 25136787.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 42458507.65 | 0.190829E+09 | 0.619336E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 69766599.90 | 1748436.46 | 0.157428E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.173416E+09 | 0.00 | 0.392128E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.155312E+10 | 0.108303E+11 | 0.168080E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 41028860.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.265233E+09 | 0.361038E+10 | 0.398747E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT GSW
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 0.181936E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.176798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.105913E+09 | 0.00 | 0.00 | 0.00 | 274999.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 55529606.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 9664433.10 | 0.00 | 0.00 | 0.00 | 5555708.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 90990194.26 | 0.00 | 0.00 | 0.00 | 0.306136E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.214116E+09 | 0.00 | 0.00 | 0.00 | 0.726999E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.196002E+09 | 0.00 | 0.00 | 0.00 | 0.660042E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.101862E+09 | 0.00 | 0.00 | 0.00 | 0.337956E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 12388402.58 | 0.00 | 0.00 | 0.00 | 11491113.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 52033796.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.164895E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.136213E+10 | 0.00 | 0.00 | 0.00 | 0.204846E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 9664433.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.214116E+09 | 0.00 | 0.00 | 0.00 | 0.726999E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT GNW
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 0.205857E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.197667E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.136415E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 72560641.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 12700653.67 | 0.00 | 0.00 | 0.00 | 105960.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 75958091.66 | 0.00 | 0.00 | 0.00 | 0.257292E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.188926E+09 | 0.00 | 0.00 | 0.00 | 0.645105E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.156735E+09 | 0.00 | 0.00 | 0.00 | 0.531067E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 50465505.63 | 0.00 | 0.00 | 0.00 | 0.169056E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 21487885.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 71013063.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.183406E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.137319E+10 | 0.00 | 0.00 | 0.00 | 0.160263E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 12700653.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.205857E+09 | 0.00 | 0.00 | 0.00 | 0.645105E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT OFFICE
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 0.114110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.103067E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.114110E+10 | 0.00 | 0.00 | 0.00 | 4402969.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.110429E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.114110E+10 | 0.00 | 0.00 | 0.00 | 52312244.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.110429E+10 | 0.00 | 0.00 | 0.00 | 0.319933E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.114110E+10 | 0.00 | 0.00 | 0.00 | 0.504106E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.114110E+10 | 0.00 | 0.00 | 0.00 | 0.526898E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.110429E+10 | 0.00 | 0.00 | 0.00 | 0.315739E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.114110E+10 | 0.00 | 0.00 | 0.00 | 58153701.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.110429E+10 | 0.00 | 0.00 | 0.00 | 373150.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.114110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.134356E+11 | 0.00 | 0.00 | 0.00 | 0.178192E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 0.103067E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.114110E+10 | 0.00 | 0.00 | 0.00 | 0.526898E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT GNE
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 0.200653E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.193043E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.134446E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 69610629.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 12212749.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 71240789.27 | 0.00 | 0.00 | 0.00 | 0.245809E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.185871E+09 | 0.00 | 0.00 | 0.00 | 0.645658E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.152616E+09 | 0.00 | 0.00 | 0.00 | 0.526205E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 50361064.80 | 0.00 | 0.00 | 0.00 | 0.171727E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 19986949.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 69302046.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.180175E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.133952E+10 | 0.00 | 0.00 | 0.00 | 0.158940E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 12212749.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.200653E+09 | 0.00 | 0.00 | 0.00 | 0.645658E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT GN1
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 0.142440E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.138007E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 94532365.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 46523236.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 5970156.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 63065600.78 | 0.00 | 0.00 | 0.00 | 0.217603E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.163110E+09 | 0.00 | 0.00 | 0.00 | 0.566783E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.133972E+09 | 0.00 | 0.00 | 0.00 | 0.461927E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 46189502.62 | 0.00 | 0.00 | 0.00 | 0.157685E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 9848066.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 43518642.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.125805E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.101298E+10 | 0.00 | 0.00 | 0.00 | 0.140400E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 5970156.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.163110E+09 | 0.00 | 0.00 | 0.00 | 0.566783E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT GN2
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 0.142312E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.137900E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 94505946.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 46427377.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 5984945.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 62931619.54 | 0.00 | 0.00 | 0.00 | 0.217224E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.163128E+09 | 0.00 | 0.00 | 0.00 | 0.567036E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.133893E+09 | 0.00 | 0.00 | 0.00 | 0.461811E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 46424563.19 | 0.00 | 0.00 | 0.00 | 0.158534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 9792058.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 43469823.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.125746E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.101252E+10 | 0.00 | 0.00 | 0.00 | 0.140460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 5984945.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.163128E+09 | 0.00 | 0.00 | 0.00 | 0.567036E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT GS1
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 0.120215E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.118474E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 66145717.60 | 0.00 | 0.00 | 0.00 | 468962.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 31228569.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 4058461.33 | 0.00 | 0.00 | 0.00 | 4158792.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 79366702.29 | 0.00 | 0.00 | 0.00 | 0.271361E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.189585E+09 | 0.00 | 0.00 | 0.00 | 0.653766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.174795E+09 | 0.00 | 0.00 | 0.00 | 0.597782E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.101772E+09 | 0.00 | 0.00 | 0.00 | 0.343160E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 6814476.10 | 0.00 | 0.00 | 0.00 | 17363945.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 26796026.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.108640E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.102789E+10 | 0.00 | 0.00 | 0.00 | 0.188806E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 4058461.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.189585E+09 | 0.00 | 0.00 | 0.00 | 0.653766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT GS2
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 0.132265E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.129031E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 72878311.38 | 0.00 | 0.00 | 0.00 | 428885.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 33940956.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 4668828.13 | 0.00 | 0.00 | 0.00 | 6265343.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 87760456.13 | 0.00 | 0.00 | 0.00 | 0.299557E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.207180E+09 | 0.00 | 0.00 | 0.00 | 0.713196E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.191788E+09 | 0.00 | 0.00 | 0.00 | 0.654881E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.112267E+09 | 0.00 | 0.00 | 0.00 | 0.378148E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 7667951.07 | 0.00 | 0.00 | 0.00 | 20419919.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 29161090.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.118660E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.112727E+10 | 0.00 | 0.00 | 0.00 | 0.207289E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 4668828.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.207180E+09 | 0.00 | 0.00 | 0.00 | 0.713196E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT MSW
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 0.314294E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.300571E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.136482E+09 | 0.00 | 0.00 | 0.00 | 35251335.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 53233374.39 | 0.00 | 0.00 | 0.00 | 39543642.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.111979E+09 | 0.00 | 0.00 | 0.00 | 0.363808E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.373992E+09 | 0.00 | 0.00 | 0.00 | 0.124193E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.598670E+09 | 0.00 | 0.00 | 0.00 | 0.201361E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.503696E+09 | 0.00 | 0.00 | 0.00 | 0.168277E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.273097E+09 | 0.00 | 0.00 | 0.00 | 0.898842E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 40234001.00 | 0.00 | 0.00 | 0.00 | 77084070.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 97808634.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.311174E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.311523E+10 | 0.00 | 0.00 | 0.00 | 0.635284E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 40234001.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.598670E+09 | 0.00 | 0.00 | 0.00 | 0.201361E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT MNW
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 0.365513E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.344637E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.188247E+09 | 0.00 | 0.00 | 0.00 | 11495466.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 59297178.65 | 0.00 | 0.00 | 0.00 | 225639.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 64671050.18 | 0.00 | 0.00 | 0.00 | 0.210555E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.338344E+09 | 0.00 | 0.00 | 0.00 | 0.112464E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.547845E+09 | 0.00 | 0.00 | 0.00 | 0.184333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.421946E+09 | 0.00 | 0.00 | 0.00 | 0.141075E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.156095E+09 | 0.00 | 0.00 | 0.00 | 0.515661E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 39301932.51 | 0.00 | 0.00 | 0.00 | 975114.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.135294E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.350672E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.301186E+10 | 0.00 | 0.00 | 0.00 | 0.511762E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 39301932.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.547845E+09 | 0.00 | 0.00 | 0.00 | 0.184333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT MSE
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 0.305733E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.293002E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.135888E+09 | 0.00 | 0.00 | 0.00 | 38528039.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 53867127.59 | 0.00 | 0.00 | 0.00 | 47533740.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.111211E+09 | 0.00 | 0.00 | 0.00 | 0.363212E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.363899E+09 | 0.00 | 0.00 | 0.00 | 0.121460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.595885E+09 | 0.00 | 0.00 | 0.00 | 0.201323E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.498534E+09 | 0.00 | 0.00 | 0.00 | 0.167331E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.276533E+09 | 0.00 | 0.00 | 0.00 | 0.914626E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 39357781.24 | 0.00 | 0.00 | 0.00 | 78600505.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 95259228.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.306122E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.307529E+10 | 0.00 | 0.00 | 0.00 | 0.634365E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 39357781.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.595885E+09 | 0.00 | 0.00 | 0.00 | 0.201323E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT MNE
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 0.355864E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.336259E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.186636E+09 | 0.00 | 0.00 | 0.00 | 13034939.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 56596034.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 61666975.06 | 0.00 | 0.00 | 0.00 | 0.202409E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.327461E+09 | 0.00 | 0.00 | 0.00 | 0.109743E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.544068E+09 | 0.00 | 0.00 | 0.00 | 0.184439E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.416589E+09 | 0.00 | 0.00 | 0.00 | 0.140358E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.158390E+09 | 0.00 | 0.00 | 0.00 | 0.527453E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 35818981.09 | 0.00 | 0.00 | 0.00 | 63198.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.132079E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.344764E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.295619E+10 | 0.00 | 0.00 | 0.00 | 0.508836E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 35818981.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.544068E+09 | 0.00 | 0.00 | 0.00 | 0.184439E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT MN1
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 0.233241E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.222912E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.121422E+09 | 0.00 | 0.00 | 0.00 | 11248983.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 30518705.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 51693700.12 | 0.00 | 0.00 | 0.00 | 0.169947E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.265184E+09 | 0.00 | 0.00 | 0.00 | 0.888627E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.444045E+09 | 0.00 | 0.00 | 0.00 | 0.150513E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.346459E+09 | 0.00 | 0.00 | 0.00 | 0.116642E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.139240E+09 | 0.00 | 0.00 | 0.00 | 0.463840E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 12982896.08 | 0.00 | 0.00 | 0.00 | 815628.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 70469747.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.220791E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.215896E+10 | 0.00 | 0.00 | 0.00 | 0.420604E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 12982896.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.444045E+09 | 0.00 | 0.00 | 0.00 | 0.150513E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT MN2
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 0.233006E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.222722E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.121474E+09 | 0.00 | 0.00 | 0.00 | 11507630.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 30461160.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 52016934.49 | 0.00 | 0.00 | 0.00 | 0.171062E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.264958E+09 | 0.00 | 0.00 | 0.00 | 0.888174E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.444028E+09 | 0.00 | 0.00 | 0.00 | 0.150558E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.346348E+09 | 0.00 | 0.00 | 0.00 | 0.116645E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.139674E+09 | 0.00 | 0.00 | 0.00 | 0.465433E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 12940084.86 | 0.00 | 0.00 | 0.00 | 874955.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 70365216.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.220691E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.215869E+10 | 0.00 | 0.00 | 0.00 | 0.420909E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 12940084.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.444028E+09 | 0.00 | 0.00 | 0.00 | 0.150558E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT MS1
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 0.185263E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.181414E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 74258258.68 | 0.00 | 0.00 | 0.00 | 39196654.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 28316256.87 | 0.00 | 0.00 | 0.00 | 36873761.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.101759E+09 | 0.00 | 0.00 | 0.00 | 0.331987E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.302682E+09 | 0.00 | 0.00 | 0.00 | 0.100854E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.497736E+09 | 0.00 | 0.00 | 0.00 | 0.167902E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.430851E+09 | 0.00 | 0.00 | 0.00 | 0.144300E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.263274E+09 | 0.00 | 0.00 | 0.00 | 0.869247E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 36561974.59 | 0.00 | 0.00 | 0.00 | 0.112791E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 40481386.79 | 0.00 | 0.00 | 0.00 | 545511.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.183930E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.232653E+10 | 0.00 | 0.00 | 0.00 | 0.552119E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 28316256.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.497736E+09 | 0.00 | 0.00 | 0.00 | 0.167902E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT MS2
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 0.185035E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.181235E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 74375769.63 | 0.00 | 0.00 | 0.00 | 39378995.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 28770455.39 | 0.00 | 0.00 | 0.00 | 38360741.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.102108E+09 | 0.00 | 0.00 | 0.00 | 0.333232E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.302449E+09 | 0.00 | 0.00 | 0.00 | 0.100812E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.497688E+09 | 0.00 | 0.00 | 0.00 | 0.167944E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.430704E+09 | 0.00 | 0.00 | 0.00 | 0.144302E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.263465E+09 | 0.00 | 0.00 | 0.00 | 0.870185E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 37020291.41 | 0.00 | 0.00 | 0.00 | 0.114404E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 40457364.88 | 0.00 | 0.00 | 0.00 | 597400.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.183846E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.232715E+10 | 0.00 | 0.00 | 0.00 | 0.552674E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 28770455.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.497688E+09 | 0.00 | 0.00 | 0.00 | 0.167944E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT TSW
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 0.259743E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.244161E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.140246E+09 | 0.00 | 0.00 | 0.00 | 27988560.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 79398599.71 | 0.00 | 0.00 | 0.00 | 50170095.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 60990981.57 | 0.00 | 0.00 | 0.00 | 0.170894E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.187728E+09 | 0.00 | 0.00 | 0.00 | 0.621557E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.314862E+09 | 0.00 | 0.00 | 0.00 | 0.106156E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.252409E+09 | 0.00 | 0.00 | 0.00 | 0.845609E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.121797E+09 | 0.00 | 0.00 | 0.00 | 0.390740E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 64792751.86 | 0.00 | 0.00 | 0.00 | 51342065.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.111726E+09 | 0.00 | 0.00 | 0.00 | 294804.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.255663E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.209352E+10 | 0.00 | 0.00 | 0.00 | 0.322016E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 60990981.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.314862E+09 | 0.00 | 0.00 | 0.00 | 0.106156E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT TNW
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 0.287770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.268075E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.166722E+09 | 0.00 | 0.00 | 0.00 | 15049974.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 76225476.79 | 0.00 | 0.00 | 0.00 | 5493714.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 40185047.30 | 0.00 | 0.00 | 0.00 | 0.100120E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.169472E+09 | 0.00 | 0.00 | 0.00 | 0.562065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.288951E+09 | 0.00 | 0.00 | 0.00 | 0.974644E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.211336E+09 | 0.00 | 0.00 | 0.00 | 0.708694E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 69187766.08 | 0.00 | 0.00 | 0.00 | 0.215009E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 64962705.37 | 0.00 | 0.00 | 0.00 | 3402320.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.130396E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.276979E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.205026E+10 | 0.00 | 0.00 | 0.00 | 0.258448E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 40185047.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.288951E+09 | 0.00 | 0.00 | 0.00 | 0.974644E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT TSE
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 0.252767E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.237861E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.138408E+09 | 0.00 | 0.00 | 0.00 | 29451334.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 76552276.07 | 0.00 | 0.00 | 0.00 | 49213542.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 56657080.29 | 0.00 | 0.00 | 0.00 | 0.159679E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.180230E+09 | 0.00 | 0.00 | 0.00 | 0.602101E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.311167E+09 | 0.00 | 0.00 | 0.00 | 0.105727E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.247782E+09 | 0.00 | 0.00 | 0.00 | 0.836765E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.120892E+09 | 0.00 | 0.00 | 0.00 | 0.391059E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 61892691.47 | 0.00 | 0.00 | 0.00 | 49067568.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.108914E+09 | 0.00 | 0.00 | 0.00 | 3108.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.250718E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.204384E+10 | 0.00 | 0.00 | 0.00 | 0.317461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 56657080.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.311167E+09 | 0.00 | 0.00 | 0.00 | 0.105727E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT TNE
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 0.280146E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.261268E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.164270E+09 | 0.00 | 0.00 | 0.00 | 16179309.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 72009771.22 | 0.00 | 0.00 | 0.00 | 1675490.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 33990236.57 | 0.00 | 0.00 | 0.00 | 82074193.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.162276E+09 | 0.00 | 0.00 | 0.00 | 0.542658E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.286552E+09 | 0.00 | 0.00 | 0.00 | 0.973906E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.207897E+09 | 0.00 | 0.00 | 0.00 | 0.702659E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 65948934.55 | 0.00 | 0.00 | 0.00 | 0.206505E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 61311087.66 | 0.00 | 0.00 | 0.00 | 2280735.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.127307E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.271534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.199451E+10 | 0.00 | 0.00 | 0.00 | 0.252794E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 33990236.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.286552E+09 | 0.00 | 0.00 | 0.00 | 0.973906E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT TN1
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 0.203645E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.189808E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.119786E+09 | 0.00 | 0.00 | 0.00 | 12400513.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 48853280.11 | 0.00 | 0.00 | 0.00 | 285283.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 20824095.30 | 0.00 | 0.00 | 0.00 | 54739503.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.131393E+09 | 0.00 | 0.00 | 0.00 | 0.437829E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.239025E+09 | 0.00 | 0.00 | 0.00 | 0.806074E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.173992E+09 | 0.00 | 0.00 | 0.00 | 0.583234E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 51978677.19 | 0.00 | 0.00 | 0.00 | 0.167070E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 40016642.19 | 0.00 | 0.00 | 0.00 | 967541.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 86665928.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.194076E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.150006E+10 | 0.00 | 0.00 | 0.00 | 0.206260E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 20824095.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.239025E+09 | 0.00 | 0.00 | 0.00 | 0.806074E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT TN2
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 0.203404E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.189601E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.119794E+09 | 0.00 | 0.00 | 0.00 | 12574627.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 48809952.36 | 0.00 | 0.00 | 0.00 | 337540.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 21067038.08 | 0.00 | 0.00 | 0.00 | 55375467.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.131433E+09 | 0.00 | 0.00 | 0.00 | 0.437929E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.239186E+09 | 0.00 | 0.00 | 0.00 | 0.806600E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.174110E+09 | 0.00 | 0.00 | 0.00 | 0.583627E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 52294885.46 | 0.00 | 0.00 | 0.00 | 0.168070E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 39956015.15 | 0.00 | 0.00 | 0.00 | 1003176.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 86571257.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.193918E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.150014E+10 | 0.00 | 0.00 | 0.00 | 0.206552E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 21067038.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.239186E+09 | 0.00 | 0.00 | 0.00 | 0.806600E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT TS1
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 0.176563E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.166773E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 94631557.72 | 0.00 | 0.00 | 0.00 | 25968800.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 49644943.53 | 0.00 | 0.00 | 0.00 | 35323682.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 40516649.47 | 0.00 | 0.00 | 0.00 | 0.121588E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.149333E+09 | 0.00 | 0.00 | 0.00 | 0.496679E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.265078E+09 | 0.00 | 0.00 | 0.00 | 0.893500E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.215703E+09 | 0.00 | 0.00 | 0.00 | 0.722293E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.107936E+09 | 0.00 | 0.00 | 0.00 | 0.351966E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 42268782.83 | 0.00 | 0.00 | 0.00 | 48205211.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 69804168.85 | 0.00 | 0.00 | 0.00 | 413610.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.173550E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.155180E+10 | 0.00 | 0.00 | 0.00 | 0.269594E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 40516649.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.265078E+09 | 0.00 | 0.00 | 0.00 | 0.893500E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT TS2
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 0.176343E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.166591E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 94704122.19 | 0.00 | 0.00 | 0.00 | 26145961.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 50012387.06 | 0.00 | 0.00 | 0.00 | 36416904.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 41028860.83 | 0.00 | 0.00 | 0.00 | 0.123098E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.149454E+09 | 0.00 | 0.00 | 0.00 | 0.497051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.265233E+09 | 0.00 | 0.00 | 0.00 | 0.894000E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.215792E+09 | 0.00 | 0.00 | 0.00 | 0.722586E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.108317E+09 | 0.00 | 0.00 | 0.00 | 0.353179E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 42458507.65 | 0.00 | 0.00 | 0.00 | 48936969.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 69766599.90 | 0.00 | 0.00 | 0.00 | 465440.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.173416E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.155312E+10 | 0.00 | 0.00 | 0.00 | 0.270188E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 41028860.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.265233E+09 | 0.00 | 0.00 | 0.00 | 0.894000E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: G SW APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 12728641.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.200686E+10 | 0.00 | 0.00 | 0.35 |
| February | 15137661.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.186782E+10 | 0.00 | 0.00 | 0.35 |
| March | 0.152647E+09 | 340786.60 | 5953.41 | 0.00 | 2206829.22 | 0.137978E+10 | 0.00 | 7.42 | 0.35 |
| April | 0.369844E+09 | 0.00 | 0.00 | 0.00 | 4850.35 | 0.738109E+09 | 0.00 | 0.00 | 0.35 |
| May | 0.594309E+09 | 1087131.94 | 0.00 | 33231.35 | 1835019.05 | 96864403.66 | 7326491.32 | 0.00 | 0.35 |
| June | 0.269632E+09 | 0.108555E+09 | 0.00 | 857291.31 | 0.00 | 0.00 | 0.151589E+09 | 0.00 | 0.36 |
| July | 13184681.89 | 0.353802E+09 | 0.00 | 882343.54 | 0.00 | 0.00 | 0.130197E+09 | 0.00 | 0.36 |
| August | 22937667.35 | 0.201416E+09 | 0.00 | 1747496.30 | 0.00 | 0.00 | 0.239273E+09 | 0.00 | 0.36 |
| September | 0.190825E+09 | 53134315.23 | 0.00 | 1971156.34 | 0.00 | 0.00 | 0.381901E+09 | 0.00 | 0.35 |
| October | 0.949720E+09 | 0.00 | 0.00 | 157890.55 | 0.00 | 59147830.30 | 45733901.14 | 0.00 | 0.35 |
| November | 0.441465E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.778717E+09 | 0.00 | 0.00 | 0.35 |
| December | 24222563.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.189464E+10 | 0.00 | 0.00 | 0.35 |
| Annual Sum or Average | 0.305665E+10 | 0.718335E+09 | 5953.41 | 5649409.39 | 4046698.61 | 0.882194E+10 | 0.956021E+09 | 7.42 | 0.35 |
| Minimum of Months | 12728641.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
| Maximum of Months | 0.949720E+09 | 0.353802E+09 | 5953.41 | 1971156.34 | 2206829.22 | 0.200686E+10 | 0.381901E+09 | 7.42 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: G NW APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.201934E+10 | 0.00 | 0.00 | 0.35 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.188316E+10 | 0.00 | 0.00 | 0.35 |
| March | 52135293.86 | 0.00 | 63673.40 | 0.00 | 3437826.47 | 0.147845E+10 | 0.00 | 681.43 | 0.35 |
| April | 0.135265E+09 | 0.00 | 0.00 | 0.00 | 52319.75 | 0.960681E+09 | 0.00 | 0.00 | 0.35 |
| May | 0.485349E+09 | 0.00 | 0.00 | 1669.58 | 3929203.21 | 0.182072E+09 | 913377.40 | 0.00 | 0.35 |
| June | 0.292587E+09 | 0.101717E+09 | 0.00 | 673703.09 | 15617.83 | 0.00 | 0.126038E+09 | 0.00 | 0.36 |
| July | 16823285.62 | 0.334210E+09 | 0.00 | 846907.69 | 0.00 | 0.00 | 0.131727E+09 | 0.00 | 0.36 |
| August | 36938889.66 | 0.184770E+09 | 0.00 | 1410682.46 | 0.00 | 0.00 | 0.238227E+09 | 0.00 | 0.36 |
| September | 0.349404E+09 | 41524315.21 | 0.00 | 811492.17 | 0.00 | 0.00 | 0.225303E+09 | 0.00 | 0.35 |
| October | 0.734173E+09 | 0.00 | 0.00 | 0.00 | 131887.82 | 0.263768E+09 | 0.00 | 0.00 | 0.35 |
| November | 0.128587E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108047E+10 | 0.00 | 0.00 | 0.35 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.191872E+10 | 0.00 | 0.00 | 0.35 |
| Annual Sum or Average | 0.223126E+10 | 0.662222E+09 | 63673.40 | 3744454.99 | 7566855.08 | 0.978667E+10 | 0.722209E+09 | 681.43 | 0.35 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
| Maximum of Months | 0.734173E+09 | 0.334210E+09 | 63673.40 | 1410682.46 | 3929203.21 | 0.201934E+10 | 0.238227E+09 | 681.43 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: OFFICE
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.119899E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.134392E+10 | 0.00 | 0.00 | 0.51 |
| February | 0.102581E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136444E+10 | 0.00 | 0.00 | 0.51 |
| March | 0.133444E+10 | 416313.27 | 0.00 | 4083.46 | 404755.47 | 0.658351E+09 | 3756102.49 | 0.00 | 0.51 |
| April | 0.134678E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.169231E+09 | 0.00 | 0.00 | 0.51 |
| May | 0.103622E+10 | 1793889.03 | 0.00 | 228030.86 | 1187779.55 | 508579.52 | 0.112108E+09 | 0.00 | 0.52 |
| June | 0.660186E+09 | 80564197.94 | 0.00 | 897630.80 | 10117868.13 | 0.00 | 0.123236E+09 | 0.00 | 0.52 |
| July | 0.527238E+09 | 0.207905E+09 | 0.00 | 833109.27 | 35051454.62 | 0.00 | 28759824.68 | 0.00 | 0.53 |
| August | 0.611079E+09 | 0.127763E+09 | 0.00 | 1496557.83 | 19139434.60 | 0.00 | 67214344.29 | 0.00 | 0.53 |
| September | 0.901728E+09 | 41012883.27 | 0.00 | 1362082.21 | 4102954.65 | 0.00 | 0.143381E+09 | 0.00 | 0.52 |
| October | 0.149096E+10 | 0.00 | 0.00 | 357007.29 | 0.00 | 816936.49 | 0.130109E+09 | 0.00 | 0.52 |
| November | 0.147544E+10 | 0.00 | 0.00 | 7549.46 | 4757.62 | 0.205391E+09 | 11515120.14 | 0.00 | 0.51 |
| December | 0.138539E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105265E+10 | 0.00 | 0.00 | 0.51 |
| Annual Sum or Average | 0.129942E+11 | 0.459455E+09 | 0.00 | 5186051.18 | 70009004.64 | 0.479530E+10 | 0.620080E+09 | 0.00 | 0.52 |
| Minimum of Months | 0.527238E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.51 |
| Maximum of Months | 0.149096E+10 | 0.207905E+09 | 0.00 | 1496557.83 | 35051454.62 | 0.136444E+10 | 0.143381E+09 | 0.00 | 0.53 |
Report: MechanicalVentilationLoadsMonthly
For: G NE APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.201932E+10 | 0.00 | 0.00 | 0.35 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.188315E+10 | 0.00 | 0.00 | 0.35 |
| March | 54368855.14 | 0.00 | 12554.20 | 0.00 | 3189027.22 | 0.147645E+10 | 0.00 | 254.19 | 0.35 |
| April | 0.147380E+09 | 0.00 | 0.00 | 0.00 | 23286.32 | 0.948109E+09 | 0.00 | 0.00 | 0.35 |
| May | 0.498300E+09 | 0.00 | 0.00 | 0.00 | 3816731.28 | 0.170480E+09 | 0.00 | 0.00 | 0.35 |
| June | 0.306649E+09 | 0.101986E+09 | 0.00 | 649067.68 | 16316.43 | 0.00 | 0.114204E+09 | 0.00 | 0.36 |
| July | 19213546.17 | 0.335116E+09 | 0.00 | 938915.09 | 0.00 | 0.00 | 0.131161E+09 | 0.00 | 0.36 |
| August | 40163241.64 | 0.183213E+09 | 0.00 | 1476010.53 | 0.00 | 0.00 | 0.235848E+09 | 0.00 | 0.36 |
| September | 0.322613E+09 | 43480864.33 | 0.00 | 837639.53 | 0.00 | 0.00 | 0.254783E+09 | 0.00 | 0.35 |
| October | 0.761359E+09 | 0.00 | 0.00 | 0.00 | 87124.61 | 0.238312E+09 | 0.00 | 0.00 | 0.35 |
| November | 0.130894E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107824E+10 | 0.00 | 0.00 | 0.35 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.191870E+10 | 0.00 | 0.00 | 0.35 |
| Annual Sum or Average | 0.228094E+10 | 0.663796E+09 | 12554.20 | 3901632.83 | 7132485.86 | 0.973277E+10 | 0.735995E+09 | 254.19 | 0.35 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
| Maximum of Months | 0.761359E+09 | 0.335116E+09 | 12554.20 | 1476010.53 | 3816731.28 | 0.201932E+10 | 0.254783E+09 | 254.19 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: G N1 APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.202661E+10 | 0.00 | 0.00 | 0.35 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.188975E+10 | 0.00 | 0.00 | 0.35 |
| March | 0.115727E+09 | 0.00 | 14014.83 | 0.00 | 3253511.46 | 0.142295E+10 | 0.00 | 92.00 | 0.35 |
| April | 0.379806E+09 | 0.00 | 0.00 | 0.00 | 43146.95 | 0.721815E+09 | 0.00 | 0.00 | 0.35 |
| May | 0.660409E+09 | 0.00 | 0.00 | 0.00 | 4151964.71 | 27681637.16 | 0.00 | 0.00 | 0.35 |
| June | 0.273003E+09 | 99961931.06 | 0.00 | 676682.42 | 0.00 | 0.00 | 0.157826E+09 | 0.00 | 0.36 |
| July | 2950739.47 | 0.327052E+09 | 0.00 | 901267.40 | 0.00 | 0.00 | 0.144704E+09 | 0.00 | 0.36 |
| August | 10793152.96 | 0.179374E+09 | 0.00 | 1479119.78 | 0.00 | 0.00 | 0.262914E+09 | 0.00 | 0.36 |
| September | 0.272663E+09 | 42063476.56 | 0.00 | 953355.90 | 0.00 | 0.00 | 0.313646E+09 | 0.00 | 0.36 |
| October | 0.974064E+09 | 0.00 | 0.00 | 0.00 | 156960.02 | 48540696.95 | 0.00 | 0.00 | 0.35 |
| November | 0.611561E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.606340E+09 | 0.00 | 0.00 | 0.35 |
| December | 5740083.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.192067E+10 | 0.00 | 0.00 | 0.35 |
| Annual Sum or Average | 0.330672E+10 | 0.648451E+09 | 14014.83 | 4010425.51 | 7605583.14 | 0.866437E+10 | 0.879090E+09 | 92.00 | 0.35 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
| Maximum of Months | 0.974064E+09 | 0.327052E+09 | 14014.83 | 1479119.78 | 4151964.71 | 0.202661E+10 | 0.313646E+09 | 92.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: G N2 APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.202661E+10 | 0.00 | 0.00 | 0.35 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.188975E+10 | 0.00 | 0.00 | 0.35 |
| March | 0.115333E+09 | 0.00 | 14014.23 | 0.00 | 3235934.19 | 0.142339E+10 | 0.00 | 91.92 | 0.35 |
| April | 0.382032E+09 | 0.00 | 0.00 | 0.00 | 41219.04 | 0.719633E+09 | 0.00 | 0.00 | 0.35 |
| May | 0.656984E+09 | 0.00 | 0.00 | 0.00 | 4137294.30 | 31286749.17 | 0.00 | 0.00 | 0.35 |
| June | 0.273884E+09 | 0.100042E+09 | 0.00 | 671505.02 | 0.00 | 0.00 | 0.156969E+09 | 0.00 | 0.36 |
| July | 3023625.91 | 0.327253E+09 | 0.00 | 901618.12 | 0.00 | 0.00 | 0.144708E+09 | 0.00 | 0.36 |
| August | 10285416.76 | 0.179351E+09 | 0.00 | 1477981.51 | 0.00 | 0.00 | 0.263458E+09 | 0.00 | 0.36 |
| September | 0.269911E+09 | 42209622.65 | 0.00 | 960895.92 | 0.00 | 0.00 | 0.316434E+09 | 0.00 | 0.36 |
| October | 0.974441E+09 | 0.00 | 0.00 | 0.00 | 150881.65 | 48540953.20 | 0.00 | 0.00 | 0.35 |
| November | 0.612743E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.605176E+09 | 0.00 | 0.00 | 0.35 |
| December | 5740160.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.192067E+10 | 0.00 | 0.00 | 0.35 |
| Annual Sum or Average | 0.330438E+10 | 0.648856E+09 | 14014.23 | 4012000.58 | 7565329.17 | 0.866507E+10 | 0.881570E+09 | 91.92 | 0.35 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
| Maximum of Months | 0.974441E+09 | 0.327253E+09 | 14014.23 | 1477981.51 | 4137294.30 | 0.202661E+10 | 0.316434E+09 | 91.92 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: G S1 APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 98211927.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.192870E+10 | 0.00 | 0.00 | 0.35 |
| February | 87832213.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.180163E+10 | 0.00 | 0.00 | 0.35 |
| March | 0.521496E+09 | 1041349.59 | 0.00 | 41.78 | 1241686.39 | 0.102120E+10 | 10191.32 | 0.00 | 0.35 |
| April | 0.700851E+09 | 0.00 | 0.00 | 0.00 | 637.40 | 0.417851E+09 | 0.00 | 0.00 | 0.35 |
| May | 0.721676E+09 | 1116636.26 | 0.00 | 27287.22 | 1587733.81 | 0.00 | 8675203.01 | 0.00 | 0.35 |
| June | 0.203409E+09 | 0.108587E+09 | 0.00 | 929551.25 | 0.00 | 0.00 | 0.228578E+09 | 0.00 | 0.36 |
| July | 2766325.23 | 0.351133E+09 | 0.00 | 959491.50 | 0.00 | 0.00 | 0.138524E+09 | 0.00 | 0.36 |
| August | 2854805.40 | 0.199280E+09 | 0.00 | 1833010.75 | 0.00 | 0.00 | 0.255380E+09 | 0.00 | 0.36 |
| September | 78338669.44 | 54799429.36 | 0.00 | 2304483.20 | 0.00 | 0.00 | 0.497942E+09 | 0.00 | 0.36 |
| October | 0.970017E+09 | 0.00 | 0.00 | 331711.79 | 0.00 | 0.00 | 0.132001E+09 | 0.00 | 0.35 |
| November | 0.100023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.240287E+09 | 0.00 | 0.00 | 0.35 |
| December | 0.149832E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.177681E+10 | 0.00 | 0.00 | 0.35 |
| Annual Sum or Average | 0.453751E+10 | 0.715957E+09 | 0.00 | 6385577.49 | 2830057.60 | 0.718646E+10 | 0.126111E+10 | 0.00 | 0.35 |
| Minimum of Months | 2766325.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
| Maximum of Months | 0.100023E+10 | 0.351133E+09 | 0.00 | 2304483.20 | 1587733.81 | 0.192870E+10 | 0.497942E+09 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: G S2 APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 59453598.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.196747E+10 | 0.00 | 0.00 | 0.35 |
| February | 63411822.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.182604E+10 | 0.00 | 0.00 | 0.35 |
| March | 0.410096E+09 | 904550.08 | 0.00 | 22.32 | 1419524.54 | 0.113245E+10 | 10430.49 | 0.00 | 0.35 |
| April | 0.667330E+09 | 0.00 | 0.00 | 0.00 | 1191.35 | 0.450737E+09 | 0.00 | 0.00 | 0.35 |
| May | 0.725612E+09 | 1236406.00 | 0.00 | 39850.90 | 1461792.15 | 0.00 | 11085170.52 | 0.00 | 0.35 |
| June | 0.178346E+09 | 0.113100E+09 | 0.00 | 1073129.72 | 0.00 | 0.00 | 0.250795E+09 | 0.00 | 0.36 |
| July | 1142596.47 | 0.367387E+09 | 0.00 | 1056071.30 | 0.00 | 0.00 | 0.132956E+09 | 0.00 | 0.36 |
| August | 1005397.27 | 0.207207E+09 | 0.00 | 2028755.01 | 0.00 | 0.00 | 0.248682E+09 | 0.00 | 0.36 |
| September | 65467054.59 | 57937443.04 | 0.00 | 2541439.02 | 0.00 | 0.00 | 0.506796E+09 | 0.00 | 0.36 |
| October | 0.953760E+09 | 0.00 | 0.00 | 381975.00 | 0.00 | 0.00 | 0.152616E+09 | 0.00 | 0.35 |
| November | 0.936128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.303590E+09 | 0.00 | 0.00 | 0.35 |
| December | 81423818.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.184518E+10 | 0.00 | 0.00 | 0.35 |
| Annual Sum or Average | 0.414318E+10 | 0.747773E+09 | 0.00 | 7121243.28 | 2882508.04 | 0.752548E+10 | 0.130294E+10 | 0.00 | 0.35 |
| Minimum of Months | 1005397.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
| Maximum of Months | 0.953760E+09 | 0.367387E+09 | 0.00 | 2541439.02 | 1461792.15 | 0.196747E+10 | 0.506796E+09 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: M SW APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.176569E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.385114E+10 | 0.00 | 0.00 | 0.35 |
| February | 0.208855E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.354724E+10 | 0.00 | 0.00 | 0.35 |
| March | 0.143088E+10 | 4224885.41 | 0.00 | 149869.64 | 108952.17 | 0.161684E+10 | 52402087.48 | 0.00 | 0.35 |
| April | 0.167419E+10 | 0.00 | 0.00 | 647584.07 | 0.00 | 0.523511E+09 | 0.153821E+09 | 0.00 | 0.35 |
| May | 0.928673E+09 | 9671236.68 | 0.00 | 3443014.11 | 0.00 | 0.00 | 0.742476E+09 | 0.00 | 0.35 |
| June | 0.164048E+09 | 0.264636E+09 | 0.00 | 4529525.83 | 0.00 | 0.00 | 0.638675E+09 | 0.00 | 0.36 |
| July | 799108.03 | 0.776401E+09 | 0.00 | 2550133.53 | 0.00 | 0.00 | 0.247444E+09 | 0.00 | 0.36 |
| August | 17267184.83 | 0.416842E+09 | 0.00 | 4347946.34 | 0.00 | 0.00 | 0.476416E+09 | 0.00 | 0.36 |
| September | 0.307676E+09 | 0.110981E+09 | 0.00 | 5073379.78 | 0.00 | 0.00 | 0.820654E+09 | 0.00 | 0.35 |
| October | 0.178827E+10 | 0.00 | 0.00 | 975192.39 | 0.00 | 0.115219E+09 | 0.231257E+09 | 0.00 | 0.35 |
| November | 0.106633E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138884E+10 | 0.00 | 0.00 | 0.35 |
| December | 0.175300E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.365069E+10 | 0.00 | 0.00 | 0.35 |
| Annual Sum or Average | 0.793886E+10 | 0.158276E+10 | 0.00 | 21716645.69 | 108952.17 | 0.146935E+11 | 0.336315E+10 | 0.00 | 0.35 |
| Minimum of Months | 799108.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
| Maximum of Months | 0.178827E+10 | 0.776401E+09 | 0.00 | 5073379.78 | 108952.17 | 0.385114E+10 | 0.820654E+09 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: M NW APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 1246235.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.402504E+10 | 0.00 | 0.00 | 0.35 |
| February | 317510.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.375512E+10 | 0.00 | 0.00 | 0.35 |
| March | 0.676657E+09 | 2458354.99 | 0.00 | 42217.68 | 949935.14 | 0.238396E+10 | 25272099.00 | 0.00 | 0.35 |
| April | 0.146555E+10 | 0.00 | 0.00 | 18192.03 | 0.00 | 0.787552E+09 | 6132283.44 | 0.00 | 0.35 |
| May | 0.112836E+10 | 7747196.45 | 0.00 | 2103254.12 | 0.00 | 0.00 | 0.515965E+09 | 0.00 | 0.35 |
| June | 0.185687E+09 | 0.256372E+09 | 0.00 | 4087599.28 | 0.00 | 0.00 | 0.618978E+09 | 0.00 | 0.36 |
| July | 132553.43 | 0.747455E+09 | 0.00 | 2547533.13 | 0.00 | 0.00 | 0.252527E+09 | 0.00 | 0.36 |
| August | 23561817.04 | 0.389719E+09 | 0.00 | 3854940.85 | 0.00 | 0.00 | 0.487385E+09 | 0.00 | 0.36 |
| September | 0.533326E+09 | 91678900.14 | 0.00 | 2732242.53 | 0.00 | 0.00 | 0.602538E+09 | 0.00 | 0.35 |
| October | 0.155122E+10 | 0.00 | 0.00 | 19858.21 | 73092.56 | 0.467507E+09 | 5178373.73 | 0.00 | 0.35 |
| November | 0.469303E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.194309E+10 | 0.00 | 0.00 | 0.35 |
| December | 2092381.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.382267E+10 | 0.00 | 0.00 | 0.35 |
| Annual Sum or Average | 0.603746E+10 | 0.149543E+10 | 0.00 | 15405837.83 | 1023027.70 | 0.171849E+11 | 0.251398E+10 | 0.00 | 0.35 |
| Minimum of Months | 132553.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
| Maximum of Months | 0.155122E+10 | 0.747455E+09 | 0.00 | 4087599.28 | 949935.14 | 0.402504E+10 | 0.618978E+09 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: M SE APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.181534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.384586E+10 | 0.00 | 0.00 | 0.35 |
| February | 0.249814E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.350565E+10 | 0.00 | 0.00 | 0.35 |
| March | 0.137311E+10 | 4620541.30 | 0.00 | 168376.79 | 4327.21 | 0.166933E+10 | 55758928.39 | 0.00 | 0.35 |
| April | 0.167876E+10 | 0.00 | 0.00 | 691195.10 | 0.00 | 0.497931E+09 | 0.179969E+09 | 0.00 | 0.35 |
| May | 0.897436E+09 | 9767381.27 | 0.00 | 3445014.04 | 0.00 | 0.00 | 0.777581E+09 | 0.00 | 0.35 |
| June | 0.146834E+09 | 0.263730E+09 | 0.00 | 4675777.77 | 0.00 | 0.00 | 0.661076E+09 | 0.00 | 0.36 |
| July | 265416.69 | 0.778761E+09 | 0.00 | 2861681.69 | 0.00 | 0.00 | 0.249792E+09 | 0.00 | 0.36 |
| August | 14048625.79 | 0.415441E+09 | 0.00 | 4601417.58 | 0.00 | 0.00 | 0.478686E+09 | 0.00 | 0.36 |
| September | 0.306338E+09 | 0.113699E+09 | 0.00 | 5215282.63 | 0.00 | 0.00 | 0.822333E+09 | 0.00 | 0.35 |
| October | 0.179871E+10 | 0.00 | 0.00 | 947164.51 | 0.00 | 0.106286E+09 | 0.239474E+09 | 0.00 | 0.35 |
| November | 0.106062E+10 | 0.00 | 0.00 | 29.03 | 0.00 | 0.139463E+10 | 1233709.21 | 0.00 | 0.35 |
| December | 0.153526E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.367243E+10 | 0.00 | 0.00 | 0.35 |
| Annual Sum or Average | 0.786100E+10 | 0.158602E+10 | 0.00 | 22605939.14 | 4327.21 | 0.146921E+11 | 0.346590E+10 | 0.00 | 0.35 |
| Minimum of Months | 265416.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
| Maximum of Months | 0.179871E+10 | 0.778761E+09 | 0.00 | 5215282.63 | 4327.21 | 0.384586E+10 | 0.822333E+09 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: M NE APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.402625E+10 | 0.00 | 0.00 | 0.35 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.375544E+10 | 0.00 | 0.00 | 0.35 |
| March | 0.613283E+09 | 2498467.45 | 0.00 | 56453.11 | 555698.90 | 0.244043E+10 | 32912110.64 | 0.00 | 0.35 |
| April | 0.149883E+10 | 0.00 | 0.00 | 2900.93 | 0.00 | 0.765680E+09 | 2495116.26 | 0.00 | 0.35 |
| May | 0.107276E+10 | 7907843.20 | 0.00 | 2102827.69 | 0.00 | 0.00 | 0.578603E+09 | 0.00 | 0.35 |
| June | 0.154626E+09 | 0.255500E+09 | 0.00 | 4273513.47 | 0.00 | 0.00 | 0.655663E+09 | 0.00 | 0.36 |
| July | 132752.38 | 0.750385E+09 | 0.00 | 2851071.56 | 0.00 | 0.00 | 0.254670E+09 | 0.00 | 0.36 |
| August | 19050098.77 | 0.388395E+09 | 0.00 | 4070702.53 | 0.00 | 0.00 | 0.490914E+09 | 0.00 | 0.36 |
| September | 0.483570E+09 | 95402022.55 | 0.00 | 2886801.06 | 0.00 | 0.00 | 0.655075E+09 | 0.00 | 0.35 |
| October | 0.160029E+10 | 0.00 | 0.00 | 6621.70 | 21628.94 | 0.425181E+09 | 3048735.05 | 0.00 | 0.35 |
| November | 0.459027E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.195398E+10 | 0.00 | 0.00 | 0.35 |
| December | 4159626.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.382057E+10 | 0.00 | 0.00 | 0.35 |
| Annual Sum or Average | 0.590573E+10 | 0.150009E+10 | 0.00 | 16250892.04 | 577327.84 | 0.171875E+11 | 0.267338E+10 | 0.00 | 0.35 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
| Maximum of Months | 0.160029E+10 | 0.750385E+09 | 0.00 | 4273513.47 | 555698.90 | 0.402625E+10 | 0.655663E+09 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: M N1 APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.244322E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.379875E+10 | 0.00 | 0.00 | 0.35 |
| February | 0.176973E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.359346E+10 | 0.00 | 0.00 | 0.35 |
| March | 0.126631E+10 | 2348599.09 | 0.00 | 109679.63 | 773044.70 | 0.179268E+10 | 53034083.09 | 0.00 | 0.35 |
| April | 0.204929E+10 | 0.00 | 0.00 | 270.95 | 0.00 | 0.243295E+09 | 1685904.69 | 0.00 | 0.35 |
| May | 0.954377E+09 | 7500759.92 | 0.00 | 2090076.62 | 0.00 | 0.00 | 0.735028E+09 | 0.00 | 0.35 |
| June | 0.104571E+09 | 0.244273E+09 | 0.00 | 3787065.04 | 0.00 | 0.00 | 0.715929E+09 | 0.00 | 0.36 |
| July | 0.00 | 0.715302E+09 | 0.00 | 2435420.55 | 0.00 | 0.00 | 0.258022E+09 | 0.00 | 0.36 |
| August | 194696.09 | 0.375067E+09 | 0.00 | 3782131.26 | 0.00 | 0.00 | 0.511697E+09 | 0.00 | 0.36 |
| September | 0.313238E+09 | 90948140.33 | 0.00 | 3041888.39 | 0.00 | 0.00 | 0.840986E+09 | 0.00 | 0.36 |
| October | 0.199927E+10 | 0.00 | 0.00 | 91008.64 | 73841.77 | 45056316.86 | 50376657.57 | 0.00 | 0.35 |
| November | 0.175401E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.683896E+09 | 0.00 | 0.00 | 0.35 |
| December | 0.340214E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.350197E+10 | 0.00 | 0.00 | 0.35 |
| Annual Sum or Average | 0.920277E+10 | 0.143544E+10 | 0.00 | 15337541.08 | 846886.47 | 0.136591E+11 | 0.316676E+10 | 0.00 | 0.35 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
| Maximum of Months | 0.204929E+10 | 0.715302E+09 | 0.00 | 3787065.04 | 773044.70 | 0.379875E+10 | 0.840986E+09 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: M N2 APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.245079E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.379800E+10 | 0.00 | 0.00 | 0.35 |
| February | 0.178696E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.359174E+10 | 0.00 | 0.00 | 0.35 |
| March | 0.127294E+10 | 2354706.28 | 0.00 | 111835.63 | 762149.39 | 0.178609E+10 | 53012891.41 | 0.00 | 0.35 |
| April | 0.204959E+10 | 0.00 | 0.00 | 658.87 | 0.00 | 0.243805E+09 | 2485012.43 | 0.00 | 0.35 |
| May | 0.952449E+09 | 7526401.80 | 0.00 | 2102149.43 | 0.00 | 0.00 | 0.737378E+09 | 0.00 | 0.35 |
| June | 0.103862E+09 | 0.244326E+09 | 0.00 | 3789275.13 | 0.00 | 0.00 | 0.716904E+09 | 0.00 | 0.36 |
| July | 0.00 | 0.715667E+09 | 0.00 | 2439092.98 | 0.00 | 0.00 | 0.258182E+09 | 0.00 | 0.36 |
| August | 228430.55 | 0.375097E+09 | 0.00 | 3781638.48 | 0.00 | 0.00 | 0.511668E+09 | 0.00 | 0.36 |
| September | 0.310933E+09 | 91187592.74 | 0.00 | 3052098.66 | 0.00 | 0.00 | 0.843173E+09 | 0.00 | 0.36 |
| October | 0.199982E+10 | 0.00 | 0.00 | 94270.24 | 68158.57 | 45056391.21 | 50820260.50 | 0.00 | 0.35 |
| November | 0.175319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.684816E+09 | 0.00 | 0.00 | 0.35 |
| December | 0.338273E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.350391E+10 | 0.00 | 0.00 | 0.35 |
| Annual Sum or Average | 0.920507E+10 | 0.143616E+10 | 0.00 | 15371019.43 | 830307.96 | 0.136534E+11 | 0.317362E+10 | 0.00 | 0.35 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
| Maximum of Months | 0.204959E+10 | 0.715667E+09 | 0.00 | 3789275.13 | 762149.39 | 0.379800E+10 | 0.843173E+09 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: M S1 APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.118691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.285934E+10 | 0.00 | 0.00 | 0.35 |
| February | 0.109634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.267638E+10 | 0.00 | 0.00 | 0.35 |
| March | 0.240031E+10 | 4453109.33 | 0.00 | 252177.35 | 26211.63 | 0.652821E+09 | 83532138.63 | 0.00 | 0.35 |
| April | 0.212592E+10 | 0.00 | 0.00 | 643296.18 | 0.00 | 93816975.42 | 0.196991E+09 | 0.00 | 0.35 |
| May | 0.661269E+09 | 9685565.11 | 0.00 | 3702787.49 | 0.00 | 0.00 | 0.105346E+10 | 0.00 | 0.35 |
| June | 87526112.23 | 0.255157E+09 | 0.00 | 4209273.55 | 0.00 | 0.00 | 0.729244E+09 | 0.00 | 0.36 |
| July | 0.00 | 0.753167E+09 | 0.00 | 2448748.30 | 0.00 | 0.00 | 0.252117E+09 | 0.00 | 0.36 |
| August | 0.00 | 0.408505E+09 | 0.00 | 4279411.26 | 0.00 | 0.00 | 0.491273E+09 | 0.00 | 0.36 |
| September | 0.123213E+09 | 0.112326E+09 | 0.00 | 5660466.35 | 0.00 | 0.00 | 0.101161E+10 | 0.00 | 0.36 |
| October | 0.173104E+10 | 0.00 | 0.00 | 1633064.01 | 0.00 | 0.00 | 0.508877E+09 | 0.00 | 0.35 |
| November | 0.223906E+10 | 0.00 | 0.00 | 23546.08 | 0.00 | 0.259807E+09 | 19666105.79 | 0.00 | 0.35 |
| December | 0.100690E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.283885E+10 | 0.00 | 0.00 | 0.35 |
| Annual Sum or Average | 0.126585E+11 | 0.154329E+10 | 0.00 | 22852770.56 | 26211.63 | 0.938102E+10 | 0.434677E+10 | 0.00 | 0.35 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
| Maximum of Months | 0.240031E+10 | 0.753167E+09 | 0.00 | 5660466.35 | 26211.63 | 0.285934E+10 | 0.105346E+10 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: M S2 APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.118855E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.285769E+10 | 0.00 | 0.00 | 0.35 |
| February | 0.109892E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.267381E+10 | 0.00 | 0.00 | 0.35 |
| March | 0.239110E+10 | 4465512.46 | 0.00 | 253866.50 | 25606.21 | 0.661960E+09 | 83520355.59 | 0.00 | 0.35 |
| April | 0.212286E+10 | 0.00 | 0.00 | 657391.99 | 0.00 | 94511245.45 | 0.200037E+09 | 0.00 | 0.35 |
| May | 0.658259E+09 | 9697686.28 | 0.00 | 3712277.14 | 0.00 | 0.00 | 0.105642E+10 | 0.00 | 0.35 |
| June | 87423779.76 | 0.255207E+09 | 0.00 | 4211144.86 | 0.00 | 0.00 | 0.729569E+09 | 0.00 | 0.36 |
| July | 86986.63 | 0.753497E+09 | 0.00 | 2451554.96 | 0.00 | 0.00 | 0.252167E+09 | 0.00 | 0.36 |
| August | 0.00 | 0.408550E+09 | 0.00 | 4280647.71 | 0.00 | 0.00 | 0.491240E+09 | 0.00 | 0.36 |
| September | 0.124778E+09 | 0.112516E+09 | 0.00 | 5659818.87 | 0.00 | 0.00 | 0.100991E+10 | 0.00 | 0.36 |
| October | 0.172436E+10 | 0.00 | 0.00 | 1657260.62 | 0.00 | 0.00 | 0.516437E+09 | 0.00 | 0.35 |
| November | 0.223687E+10 | 0.00 | 0.00 | 24624.26 | 0.00 | 0.262268E+09 | 19674888.33 | 0.00 | 0.35 |
| December | 0.100943E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.283633E+10 | 0.00 | 0.00 | 0.35 |
| Annual Sum or Average | 0.126426E+11 | 0.154393E+10 | 0.00 | 22908586.91 | 25606.21 | 0.938656E+10 | 0.435897E+10 | 0.00 | 0.35 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
| Maximum of Months | 0.239110E+10 | 0.753497E+09 | 0.00 | 5659818.87 | 25606.21 | 0.285769E+10 | 0.105642E+10 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: T SW APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 29940410.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.197904E+10 | 0.00 | 0.00 | 0.35 |
| February | 61164580.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.181266E+10 | 0.00 | 0.00 | 0.35 |
| March | 0.286593E+09 | 2992203.24 | 0.00 | 57180.60 | 23060.03 | 0.123458E+10 | 17050725.95 | 0.00 | 0.35 |
| April | 0.374633E+09 | 0.00 | 0.00 | 616799.27 | 0.00 | 0.674773E+09 | 91721042.74 | 0.00 | 0.35 |
| May | 0.480535E+09 | 4974372.18 | 0.00 | 1318302.31 | 0.00 | 0.107945E+09 | 0.159285E+09 | 0.00 | 0.35 |
| June | 0.232096E+09 | 0.128266E+09 | 0.00 | 1625487.78 | 0.00 | 11063418.69 | 0.148109E+09 | 0.00 | 0.36 |
| July | 77209936.65 | 0.374730E+09 | 0.00 | 837537.95 | 0.00 | 0.00 | 67137587.79 | 0.00 | 0.36 |
| August | 0.137164E+09 | 0.200061E+09 | 0.00 | 1354642.21 | 0.00 | 0.00 | 0.128562E+09 | 0.00 | 0.36 |
| September | 0.336361E+09 | 50092720.39 | 0.00 | 1709547.68 | 0.00 | 31252755.14 | 0.158320E+09 | 0.00 | 0.35 |
| October | 0.403268E+09 | 0.00 | 0.00 | 539241.34 | 0.00 | 0.535178E+09 | 69807178.19 | 0.00 | 0.35 |
| November | 0.185656E+09 | 0.00 | 0.00 | 18644.83 | 0.00 | 0.101796E+10 | 9076551.75 | 0.00 | 0.35 |
| December | 30681241.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.187729E+10 | 0.00 | 0.00 | 0.35 |
| Annual Sum or Average | 0.263530E+10 | 0.761117E+09 | 0.00 | 8077383.96 | 23060.03 | 0.928174E+10 | 0.849069E+09 | 0.00 | 0.35 |
| Minimum of Months | 29940410.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
| Maximum of Months | 0.480535E+09 | 0.374730E+09 | 0.00 | 1709547.68 | 23060.03 | 0.197904E+10 | 0.159285E+09 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: T NW APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.200807E+10 | 0.00 | 0.00 | 0.35 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.187327E+10 | 0.00 | 0.00 | 0.35 |
| March | 0.120801E+09 | 1737806.50 | 0.00 | 25399.56 | 199750.10 | 0.140533E+10 | 4403504.03 | 0.00 | 0.35 |
| April | 0.314269E+09 | 0.00 | 0.00 | 134362.43 | 0.00 | 0.772399E+09 | 33161377.22 | 0.00 | 0.35 |
| May | 0.509227E+09 | 4102833.86 | 0.00 | 765961.61 | 0.00 | 0.119197E+09 | 0.107546E+09 | 0.00 | 0.35 |
| June | 0.239113E+09 | 0.125249E+09 | 0.00 | 1402026.63 | 0.00 | 8729139.86 | 0.142668E+09 | 0.00 | 0.36 |
| July | 77082894.48 | 0.363984E+09 | 0.00 | 830831.16 | 0.00 | 0.00 | 68805825.38 | 0.00 | 0.36 |
| August | 0.149096E+09 | 0.189180E+09 | 0.00 | 1153228.01 | 0.00 | 0.00 | 0.120917E+09 | 0.00 | 0.36 |
| September | 0.371368E+09 | 41636503.80 | 0.00 | 786451.36 | 18689.30 | 42923744.45 | 98212163.97 | 0.00 | 0.35 |
| October | 0.278522E+09 | 0.00 | 0.00 | 31848.61 | 0.00 | 0.692813E+09 | 2752233.65 | 0.00 | 0.35 |
| November | 51306819.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114778E+10 | 0.00 | 0.00 | 0.35 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.190718E+10 | 0.00 | 0.00 | 0.35 |
| Annual Sum or Average | 0.211079E+10 | 0.725891E+09 | 0.00 | 5130109.36 | 218439.40 | 0.997769E+10 | 0.578466E+09 | 0.00 | 0.35 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
| Maximum of Months | 0.509227E+09 | 0.363984E+09 | 0.00 | 1402026.63 | 199750.10 | 0.200807E+10 | 0.142668E+09 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: T SE APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 30566009.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.197815E+10 | 0.00 | 0.00 | 0.35 |
| February | 66079116.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.180734E+10 | 0.00 | 0.00 | 0.35 |
| March | 0.284190E+09 | 3238286.36 | 0.00 | 43960.65 | 0.00 | 0.124296E+10 | 10656676.99 | 0.00 | 0.35 |
| April | 0.375884E+09 | 0.00 | 0.00 | 561240.19 | 0.00 | 0.667829E+09 | 99808299.57 | 0.00 | 0.35 |
| May | 0.482435E+09 | 5050260.98 | 0.00 | 1164350.05 | 0.00 | 99606581.21 | 0.172190E+09 | 0.00 | 0.35 |
| June | 0.224180E+09 | 0.128715E+09 | 0.00 | 1606852.95 | 0.00 | 10502384.21 | 0.161797E+09 | 0.00 | 0.36 |
| July | 71283083.70 | 0.376581E+09 | 0.00 | 988458.80 | 0.00 | 0.00 | 75245586.06 | 0.00 | 0.36 |
| August | 0.135965E+09 | 0.200317E+09 | 0.00 | 1448970.03 | 0.00 | 0.00 | 0.130462E+09 | 0.00 | 0.36 |
| September | 0.329515E+09 | 51260587.22 | 0.00 | 1650167.03 | 0.00 | 31186872.85 | 0.169592E+09 | 0.00 | 0.35 |
| October | 0.415842E+09 | 0.00 | 0.00 | 477428.37 | 0.00 | 0.526761E+09 | 69383086.12 | 0.00 | 0.35 |
| November | 0.196958E+09 | 0.00 | 0.00 | 3993.80 | 0.00 | 0.101160E+10 | 4221343.08 | 0.00 | 0.35 |
| December | 34007436.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.187391E+10 | 0.00 | 0.00 | 0.35 |
| Annual Sum or Average | 0.264690E+10 | 0.765162E+09 | 0.00 | 7945421.87 | 0.00 | 0.924985E+10 | 0.893356E+09 | 0.00 | 0.35 |
| Minimum of Months | 30566009.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
| Maximum of Months | 0.482435E+09 | 0.376581E+09 | 0.00 | 1650167.03 | 0.00 | 0.197815E+10 | 0.172190E+09 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: T NE APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.200806E+10 | 0.00 | 0.00 | 0.35 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.187326E+10 | 0.00 | 0.00 | 0.35 |
| March | 0.106641E+09 | 1990783.14 | 0.00 | 26217.36 | 27211.07 | 0.141944E+10 | 4794111.22 | 0.00 | 0.35 |
| April | 0.346245E+09 | 0.00 | 0.00 | 54611.51 | 0.00 | 0.755208E+09 | 21009252.03 | 0.00 | 0.35 |
| May | 0.531187E+09 | 4193465.15 | 0.00 | 549470.89 | 0.00 | 0.113046E+09 | 0.101274E+09 | 0.00 | 0.35 |
| June | 0.225544E+09 | 0.125708E+09 | 0.00 | 1390628.04 | 0.00 | 9501315.41 | 0.161185E+09 | 0.00 | 0.36 |
| July | 68937376.56 | 0.366253E+09 | 0.00 | 1017094.78 | 0.00 | 0.00 | 78134957.60 | 0.00 | 0.36 |
| August | 0.147769E+09 | 0.189731E+09 | 0.00 | 1267141.89 | 0.00 | 0.00 | 0.122680E+09 | 0.00 | 0.36 |
| September | 0.363042E+09 | 43281992.00 | 0.00 | 678696.00 | 0.00 | 43623514.08 | 0.114108E+09 | 0.00 | 0.35 |
| October | 0.298463E+09 | 0.00 | 0.00 | 21856.93 | 0.00 | 0.672551E+09 | 2679866.03 | 0.00 | 0.35 |
| November | 48502562.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115073E+10 | 0.00 | 0.00 | 0.35 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.190715E+10 | 0.00 | 0.00 | 0.35 |
| Annual Sum or Average | 0.213633E+10 | 0.731159E+09 | 0.00 | 5005717.38 | 27211.07 | 0.995257E+10 | 0.605865E+09 | 0.00 | 0.35 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
| Maximum of Months | 0.531187E+09 | 0.366253E+09 | 0.00 | 1390628.04 | 27211.07 | 0.200806E+10 | 0.161185E+09 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: T N1 APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.201715E+10 | 0.00 | 0.00 | 0.35 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.188124E+10 | 0.00 | 0.00 | 0.35 |
| March | 0.195622E+09 | 1546413.57 | 0.00 | 36789.57 | 189308.83 | 0.133355E+10 | 12737201.74 | 0.00 | 0.35 |
| April | 0.489378E+09 | 0.00 | 0.00 | 19539.28 | 0.00 | 0.630425E+09 | 7209240.03 | 0.00 | 0.35 |
| May | 0.636709E+09 | 3893228.32 | 0.00 | 381360.77 | 0.00 | 35661504.50 | 88266893.82 | 0.00 | 0.35 |
| June | 0.242074E+09 | 0.123011E+09 | 0.00 | 1129997.86 | 0.00 | 0.00 | 0.161127E+09 | 0.00 | 0.36 |
| July | 58920711.28 | 0.358715E+09 | 0.00 | 798158.72 | 0.00 | 0.00 | 87861997.26 | 0.00 | 0.36 |
| August | 0.122783E+09 | 0.186529E+09 | 0.00 | 1124143.30 | 0.00 | 0.00 | 0.150580E+09 | 0.00 | 0.36 |
| September | 0.390468E+09 | 41746641.59 | 0.00 | 573425.16 | 0.00 | 22200961.59 | 0.121769E+09 | 0.00 | 0.35 |
| October | 0.458981E+09 | 0.00 | 0.00 | 12746.66 | 0.00 | 0.526938E+09 | 3176565.23 | 0.00 | 0.35 |
| November | 0.103115E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110647E+10 | 0.00 | 0.00 | 0.35 |
| December | 544867.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.191587E+10 | 0.00 | 0.00 | 0.35 |
| Annual Sum or Average | 0.269860E+10 | 0.715441E+09 | 0.00 | 4076161.33 | 189308.83 | 0.946950E+10 | 0.632728E+09 | 0.00 | 0.35 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
| Maximum of Months | 0.636709E+09 | 0.358715E+09 | 0.00 | 1129997.86 | 189308.83 | 0.201715E+10 | 0.161127E+09 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: T N2 APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.201715E+10 | 0.00 | 0.00 | 0.35 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.188124E+10 | 0.00 | 0.00 | 0.35 |
| March | 0.194174E+09 | 1565910.30 | 0.00 | 37785.89 | 179629.00 | 0.133475E+10 | 13030674.64 | 0.00 | 0.35 |
| April | 0.487815E+09 | 0.00 | 0.00 | 19926.07 | 0.00 | 0.631765E+09 | 7986568.29 | 0.00 | 0.35 |
| May | 0.632377E+09 | 3909303.67 | 0.00 | 386240.51 | 0.00 | 38131056.50 | 90982782.11 | 0.00 | 0.35 |
| June | 0.240999E+09 | 0.123048E+09 | 0.00 | 1132183.47 | 0.00 | 0.00 | 0.162615E+09 | 0.00 | 0.36 |
| July | 58948171.26 | 0.358850E+09 | 0.00 | 805267.79 | 0.00 | 0.00 | 87949712.81 | 0.00 | 0.36 |
| August | 0.122621E+09 | 0.186559E+09 | 0.00 | 1125362.14 | 0.00 | 0.00 | 0.150773E+09 | 0.00 | 0.36 |
| September | 0.389371E+09 | 41895821.47 | 0.00 | 579289.37 | 0.00 | 22200353.37 | 0.123494E+09 | 0.00 | 0.35 |
| October | 0.459322E+09 | 0.00 | 0.00 | 13159.52 | 0.00 | 0.526635E+09 | 3305826.36 | 0.00 | 0.35 |
| November | 0.101385E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110822E+10 | 0.00 | 0.00 | 0.35 |
| December | 544879.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.191587E+10 | 0.00 | 0.00 | 0.35 |
| Annual Sum or Average | 0.268756E+10 | 0.715827E+09 | 0.00 | 4099214.76 | 179629.00 | 0.947596E+10 | 0.640138E+09 | 0.00 | 0.35 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
| Maximum of Months | 0.632377E+09 | 0.358850E+09 | 0.00 | 1132183.47 | 179629.00 | 0.201715E+10 | 0.162615E+09 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: T S1 APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.104664E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.191387E+10 | 0.00 | 0.00 | 0.35 |
| February | 0.112842E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.176945E+10 | 0.00 | 0.00 | 0.35 |
| March | 0.472877E+09 | 3008378.02 | 0.00 | 69688.28 | 13051.70 | 0.105463E+10 | 24210540.55 | 0.00 | 0.35 |
| April | 0.566073E+09 | 0.00 | 0.00 | 467879.59 | 0.00 | 0.493976E+09 | 97743372.95 | 0.00 | 0.35 |
| May | 0.572517E+09 | 4948150.28 | 0.00 | 994166.80 | 0.00 | 16803729.19 | 0.187188E+09 | 0.00 | 0.35 |
| June | 0.232735E+09 | 0.126822E+09 | 0.00 | 1357088.89 | 0.00 | 0.00 | 0.171511E+09 | 0.00 | 0.36 |
| July | 61809861.06 | 0.372201E+09 | 0.00 | 801659.71 | 0.00 | 0.00 | 83384758.79 | 0.00 | 0.36 |
| August | 0.106920E+09 | 0.199744E+09 | 0.00 | 1338303.49 | 0.00 | 0.00 | 0.160798E+09 | 0.00 | 0.36 |
| September | 0.332450E+09 | 51402390.35 | 0.00 | 1580795.04 | 0.00 | 15964459.51 | 0.197717E+09 | 0.00 | 0.35 |
| October | 0.575063E+09 | 0.00 | 0.00 | 534786.05 | 0.00 | 0.368238E+09 | 92605218.33 | 0.00 | 0.35 |
| November | 0.316987E+09 | 0.00 | 0.00 | 26881.68 | 0.00 | 0.897099E+09 | 15476660.38 | 0.00 | 0.35 |
| December | 92244259.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.182569E+10 | 0.00 | 0.00 | 0.35 |
| Annual Sum or Average | 0.354718E+10 | 0.758125E+09 | 0.00 | 7171249.52 | 13051.70 | 0.835572E+10 | 0.103064E+10 | 0.00 | 0.35 |
| Minimum of Months | 61809861.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
| Maximum of Months | 0.575063E+09 | 0.372201E+09 | 0.00 | 1580795.04 | 13051.70 | 0.191387E+10 | 0.197717E+09 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: T S2 APARTMENT
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.105656E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.191287E+10 | 0.00 | 0.00 | 0.35 |
| February | 0.112745E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.176954E+10 | 0.00 | 0.00 | 0.35 |
| March | 0.472597E+09 | 3026857.30 | 0.00 | 70085.58 | 11603.37 | 0.105530E+10 | 23918301.31 | 0.00 | 0.35 |
| April | 0.563015E+09 | 0.00 | 0.00 | 477207.19 | 0.00 | 0.495554E+09 | 99475486.03 | 0.00 | 0.35 |
| May | 0.570075E+09 | 4958612.67 | 0.00 | 1003476.76 | 0.00 | 18084697.32 | 0.188561E+09 | 0.00 | 0.35 |
| June | 0.232549E+09 | 0.126850E+09 | 0.00 | 1360347.23 | 0.00 | 0.00 | 0.171911E+09 | 0.00 | 0.36 |
| July | 61628964.31 | 0.372299E+09 | 0.00 | 806028.92 | 0.00 | 0.00 | 83728187.38 | 0.00 | 0.36 |
| August | 0.107635E+09 | 0.199742E+09 | 0.00 | 1340860.93 | 0.00 | 0.00 | 0.160117E+09 | 0.00 | 0.36 |
| September | 0.331243E+09 | 51491739.31 | 0.00 | 1585799.68 | 0.00 | 16199309.76 | 0.198841E+09 | 0.00 | 0.35 |
| October | 0.575510E+09 | 0.00 | 0.00 | 539463.04 | 0.00 | 0.367976E+09 | 92751705.18 | 0.00 | 0.35 |
| November | 0.317059E+09 | 0.00 | 0.00 | 27777.21 | 0.00 | 0.896765E+09 | 15820565.72 | 0.00 | 0.35 |
| December | 92669993.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.182527E+10 | 0.00 | 0.00 | 0.35 |
| Annual Sum or Average | 0.354238E+10 | 0.758369E+09 | 0.00 | 7211046.53 | 11603.37 | 0.835756E+10 | 0.103512E+10 | 0.00 | 0.35 |
| Minimum of Months | 61628964.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
| Maximum of Months | 0.575510E+09 | 0.372299E+09 | 0.00 | 1585799.68 | 11603.37 | 0.191287E+10 | 0.198841E+09 | 0.00 | 0.36 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 09:14:20
Custom Monthly Report| SITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
| January | 0.825229E+11 | 0.309564E+11 | 0.00 | 0.254245E+10 | 0.297881E+11 |
| February | 0.120744E+12 | 0.320479E+11 | 0.00 | 0.239024E+10 | 0.284090E+11 |
| March | 0.171622E+12 | 0.216570E+11 | 0.00 | 0.199573E+10 | 0.172592E+11 |
| April | 0.193794E+12 | 0.167440E+11 | 0.00 | 0.151601E+10 | 0.792328E+10 |
| May | 0.232078E+12 | 0.144634E+11 | 0.00 | 0.114608E+10 | 0.156136E+11 |
| June | 0.248775E+12 | 0.815068E+10 | 0.00 | 0.693637E+09 | 0.740236E+11 |
| July | 0.232203E+12 | -0.112890E+10 | 0.00 | 0.313874E+09 | 0.133658E+12 |
| August | 0.201482E+12 | 0.324499E+10 | 0.00 | 0.532887E+09 | 0.107358E+12 |
| September | 0.158808E+12 | 0.102307E+11 | 0.00 | 0.100136E+10 | 0.491709E+11 |
| October | 0.113501E+12 | 0.148684E+11 | 0.00 | 0.162224E+10 | 0.660138E+10 |
| November | 0.626133E+11 | 0.185924E+11 | 0.00 | 0.169235E+10 | 0.103120E+11 |
| December | 0.735558E+11 | 0.320550E+11 | 0.00 | 0.243804E+10 | 0.283938E+11 |
| Annual Sum or Average | 0.189170E+13 | 0.201882E+12 | 0.00 | 0.178849E+11 | 0.508511E+12 |
| Minimum of Months | 0.626133E+11 | -0.112890E+10 | 0.00 | 0.313874E+09 | 0.660138E+10 |
| Maximum of Months | 0.248775E+12 | 0.320550E+11 | 0.00 | 0.254245E+10 | 0.133658E+12 |