Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 09:15
Tabular Output Report in Format: HTML
Building: ApartmentMidRise
Environment: RUNPERIOD 1 ** Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930
Simulation Timestamp: 2023-10-16 09:15:24
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 09:15:24
Values gathered over 8760.00 hours| Total Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
| Total Site Energy | 1444.03 | 460.67 | 511.35 |
| Net Site Energy | 1444.03 | 460.67 | 511.35 |
| Total Source Energy | 4062.16 | 1295.91 | 1438.46 |
| Net Source Energy | 4062.16 | 1295.91 | 1438.46 |
| Site=>Source Conversion Factor | |
| Electricity | 3.167 |
| Natural Gas | 1.084 |
| District Cooling | 1.056 |
| District Heating | 3.613 |
| Steam | 1.200 |
| Gasoline | 1.050 |
| Diesel | 1.050 |
| Coal | 1.050 |
| Fuel Oil No 1 | 1.050 |
| Fuel Oil No 2 | 1.050 |
| Propane | 1.050 |
| Other Fuel 1 | 1.000 |
| Other Fuel 2 | 1.000 |
| Area [m2] | |
| Total Building Area | 3134.61 |
| Net Conditioned Building Area | 2823.98 |
| Unconditioned Building Area | 310.64 |
| Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
| Heating | 0.00 | 245.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Cooling | 51.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Lighting | 99.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Lighting | 49.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment | 458.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans | 77.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems | 462.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1875.32 |
| Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Total End Uses | 1198.67 | 245.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1875.32 |
| Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
| Heating | General | 0.00 | 245.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Cooling | General | 51.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Lighting | LightsWired | 94.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LightsPlugIn | 4.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Exterior Lighting | General | 49.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment | MiscPlug | 388.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| ElevatorLift | 65.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| ElevatorLightsFan | 5.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| General | 77.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems | Water Heater | 462.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1875.32 |
| Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
| Heating | Unassigned | 0.00 | 245.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Cooling | Unassigned | 51.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Lighting | GENERAL | 99.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Lighting | Unassigned | 49.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment | GENERAL | 458.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans | Unassigned | 77.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Pumps | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems | Unassigned | 462.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1875.32 |
| Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
| Lighting | 52.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| HVAC | 209.23 | 86.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.66 |
| Other | 162.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Total | 424.46 | 86.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.66 |
| Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
| Lighting | 47.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| HVAC | 188.50 | 78.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.60 |
| Other | 146.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Total | 382.40 | 78.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.60 |
| Electricity [GJ] | Percent Electricity [%] | |
| Fuel-Fired Power Generation | 0.000 | 0.00 |
| High Temperature Geothermal* | 0.000 | 0.00 |
| Photovoltaic Power | 0.000 | 0.00 |
| Wind Power | 0.000 | 0.00 |
| Power Conversion | 0.000 | 0.00 |
| Net Decrease in On-Site Storage | 0.000 | 0.00 |
| Total On-Site Electric Sources | 0.000 | 0.00 |
| Electricity Coming From Utility | 1198.672 | 100.00 |
| Surplus Electricity Going To Utility | 0.000 | 0.00 |
| Net Electricity From Utility | 1198.672 | 100.00 |
| Total On-Site and Utility Electric Sources | 1198.672 | 100.00 |
| Total Electricity End Uses | 1198.672 | 100.00 |
| Heat [GJ] | Percent Heat [%] | |
| Water-Side Heat Recovery | 0.00 | 0.00 |
| Air to Air Heat Recovery for Cooling | 0.00 | 51.03 |
| Air to Air Heat Recovery for Heating | 0.00 | 48.97 |
| High-Temperature Geothermal* | 0.00 | 0.00 |
| Solar Water Thermal | 0.00 | 0.00 |
| Solar Air Thermal | 0.00 | 0.00 |
| Total On-Site Thermal Sources | 0.00 | 100.00 |
| Water [m3] | Percent Water [%] | |
| Rainwater Collection | 0.00 | 0.00 |
| Condensate Collection | 0.00 | 0.00 |
| Groundwater Well | 0.00 | 0.00 |
| Total On Site Water Sources | 0.00 | 0.00 |
| - | - | - |
| Initial Storage | 0.00 | 0.00 |
| Final Storage | 0.00 | 0.00 |
| Change in Storage | 0.00 | 0.00 |
| - | - | - |
| Water Supplied by Utility | 1875.32 | 100.00 |
| - | - | - |
| Total On Site, Change in Storage, and Utility Water Sources | 1875.32 | 100.00 |
| Total Water End Uses | 1875.32 | 100.00 |
| Degrees [deltaC] | |
| Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
| Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
| Facility [Hours] | |
| Time Setpoint Not Met During Occupied Heating | 0.00 |
| Time Setpoint Not Met During Occupied Cooling | 0.00 |
| Time Not Comfortable Based on Simple ASHRAE 55-2004 | 8760.00 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2012
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME APARTMENTMIDRISE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4C
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_WA_SEATTLE
| Environment |ZoneCoolingSummaryMonthly
| G SW APARTMENT | G NW APARTMENT | OFFICE | G NE APARTMENT | G N1 APARTMENT | G N2 APARTMENT | G S1 APARTMENT | G S2 APARTMENT | M SW APARTMENT | M NW APARTMENT | M SE APARTMENT | M NE APARTMENT | M N1 APARTMENT | M N2 APARTMENT | M S1 APARTMENT | M S2 APARTMENT | T SW APARTMENT | T NW APARTMENT | T SE APARTMENT | T NE APARTMENT | T N1 APARTMENT | T N2 APARTMENT | T S1 APARTMENT | T S2 APARTMENT | T CORRIDOR | G CORRIDOR | M CORRIDOR |ZoneHeatingSummaryMonthly
| G SW APARTMENT | G NW APARTMENT | OFFICE | G NE APARTMENT | G N1 APARTMENT | G N2 APARTMENT | G S1 APARTMENT | G S2 APARTMENT | M SW APARTMENT | M NW APARTMENT | M SE APARTMENT | M NE APARTMENT | M N1 APARTMENT | M N2 APARTMENT | M S1 APARTMENT | M S2 APARTMENT | T SW APARTMENT | T NW APARTMENT | T SE APARTMENT | T NE APARTMENT | T N1 APARTMENT | T N2 APARTMENT | T S1 APARTMENT | T S2 APARTMENT | T CORRIDOR | G CORRIDOR | M CORRIDOR |ZoneElectricSummaryMonthly
| G SW APARTMENT | G NW APARTMENT | OFFICE | G NE APARTMENT | G N1 APARTMENT | G N2 APARTMENT | G S1 APARTMENT | G S2 APARTMENT | M SW APARTMENT | M NW APARTMENT | M SE APARTMENT | M NE APARTMENT | M N1 APARTMENT | M N2 APARTMENT | M S1 APARTMENT | M S2 APARTMENT | T SW APARTMENT | T NW APARTMENT | T SE APARTMENT | T NE APARTMENT | T N1 APARTMENT | T N2 APARTMENT | T S1 APARTMENT | T S2 APARTMENT | T CORRIDOR | G CORRIDOR | M CORRIDOR |SpaceGainsMonthly
| G SW APARTMENT | G NW APARTMENT | OFFICE | G NE APARTMENT | G N1 APARTMENT | G N2 APARTMENT | G S1 APARTMENT | G S2 APARTMENT | M SW APARTMENT | M NW APARTMENT | M SE APARTMENT | M NE APARTMENT | M N1 APARTMENT | M N2 APARTMENT | M S1 APARTMENT | M S2 APARTMENT | T SW APARTMENT | T NW APARTMENT | T SE APARTMENT | T NE APARTMENT | T N1 APARTMENT | T N2 APARTMENT | T S1 APARTMENT | T S2 APARTMENT | T CORRIDOR | G CORRIDOR | M CORRIDOR |PeakSpaceGainsMonthly
| G SW APARTMENT | G NW APARTMENT | OFFICE | G NE APARTMENT | G N1 APARTMENT | G N2 APARTMENT | G S1 APARTMENT | G S2 APARTMENT | M SW APARTMENT | M NW APARTMENT | M SE APARTMENT | M NE APARTMENT | M N1 APARTMENT | M N2 APARTMENT | M S1 APARTMENT | M S2 APARTMENT | T SW APARTMENT | T NW APARTMENT | T SE APARTMENT | T NE APARTMENT | T N1 APARTMENT | T N2 APARTMENT | T S1 APARTMENT | T S2 APARTMENT | T CORRIDOR | G CORRIDOR | M CORRIDOR |SpaceGainComponentsAtCoolingPeakMonthly
| G SW APARTMENT | G NW APARTMENT | OFFICE | G NE APARTMENT | G N1 APARTMENT | G N2 APARTMENT | G S1 APARTMENT | G S2 APARTMENT | M SW APARTMENT | M NW APARTMENT | M SE APARTMENT | M NE APARTMENT | M N1 APARTMENT | M N2 APARTMENT | M S1 APARTMENT | M S2 APARTMENT | T SW APARTMENT | T NW APARTMENT | T SE APARTMENT | T NE APARTMENT | T N1 APARTMENT | T N2 APARTMENT | T S1 APARTMENT | T S2 APARTMENT | T CORRIDOR | G CORRIDOR | M CORRIDOR |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| G SW APARTMENT | G NW APARTMENT | OFFICE | G NE APARTMENT | G N1 APARTMENT | G N2 APARTMENT | G S1 APARTMENT | G S2 APARTMENT | M SW APARTMENT | M NW APARTMENT | M SE APARTMENT | M NE APARTMENT | M N1 APARTMENT | M N2 APARTMENT | M S1 APARTMENT | M S2 APARTMENT | T SW APARTMENT | T NW APARTMENT | T SE APARTMENT | T NE APARTMENT | T N1 APARTMENT | T N2 APARTMENT | T S1 APARTMENT | T S2 APARTMENT | T CORRIDOR | G CORRIDOR | M CORRIDOR |ComfortReportSimple55Monthly
| G SW APARTMENT | G NW APARTMENT | OFFICE | G NE APARTMENT | G N1 APARTMENT | G N2 APARTMENT | G S1 APARTMENT | G S2 APARTMENT | M SW APARTMENT | M NW APARTMENT | M SE APARTMENT | M NE APARTMENT | M N1 APARTMENT | M N2 APARTMENT | M S1 APARTMENT | M S2 APARTMENT | T SW APARTMENT | T NW APARTMENT | T SE APARTMENT | T NE APARTMENT | T N1 APARTMENT | T N2 APARTMENT | T S1 APARTMENT | T S2 APARTMENT | T CORRIDOR | G CORRIDOR | M CORRIDOR |OccupantComfortDataSummaryMonthly
| OCCUP_GSW | OCCUP_GNW | OCCUP_OFFICE | OCCUP_GNE | OCCUP_GN1 | OCCUP_GN2 | OCCUP_GS1 | OCCUP_GS2 | OCCUP_MSW | OCCUP_MNW | OCCUP_MSE | OCCUP_MNE | OCCUP_MN1 | OCCUP_MN2 | OCCUP_MS1 | OCCUP_MS2 | OCCUP_TSW | OCCUP_TNW | OCCUP_TSE | OCCUP_TNE | OCCUP_TN1 | OCCUP_TN2 | OCCUP_TS1 | OCCUP_TS2 | OCCUP_T CORRIDOR | OCCUP_G CORRIDOR | OCCUP_M CORRIDOR |DXReportMonthly
| SPLIT GSW COOLING COIL | SPLIT GNW COOLING COIL | SPLIT OFFICE COOLING COIL | SPLIT GNE COOLING COIL | SPLIT GN1 COOLING COIL | SPLIT GN2 COOLING COIL | SPLIT GS1 COOLING COIL | SPLIT GS2 COOLING COIL | SPLIT MSW COOLING COIL | SPLIT MNW COOLING COIL | SPLIT MSE COOLING COIL | SPLIT MNE COOLING COIL | SPLIT MN1 COOLING COIL | SPLIT MN2 COOLING COIL | SPLIT MS1 COOLING COIL | SPLIT MS2 COOLING COIL | SPLIT TSW COOLING COIL | SPLIT TNW COOLING COIL | SPLIT TSE COOLING COIL | SPLIT TNE COOLING COIL | SPLIT TN1 COOLING COIL | SPLIT TN2 COOLING COIL | SPLIT TS1 COOLING COIL | SPLIT TS2 COOLING COIL |WindowReportMonthly
| GWINDOW1 S SWA | GWINDOW1 W SWA | GWINDOW1 W NWA | GWINDOW1 N NWA | GWINDOW1 S SEA | GWINDOW1 E SEA | GWINDOW1 E NEA | GWINDOW1 N NEA | GWINDOW1 N N1A | GWINDOW1 N N2A | GWINDOW1 S S1A | GWINDOW1 S S2A | MWINDOW1 S SWA | MWINDOW1 W SWA | MWINDOW1 W NWA | MWINDOW1 N NWA | MWINDOW1 S SEA | MWINDOW1 E SEA | MWINDOW1 E NEA | MWINDOW1 N NEA | MWINDOW1 N N1A | MWINDOW1 N N2A | MWINDOW1 S S1A | MWINDOW1 S S2A | TWINDOW1 S SWA | TWINDOW1 W SWA | TWINDOW1 W NWA | TWINDOW1 N NWA | TWINDOW1 S SEA | TWINDOW1 E SEA | TWINDOW1 E NEA | TWINDOW1 N NEA | TWINDOW1 N N1A | TWINDOW1 N N2A | TWINDOW1 S S1A | TWINDOW1 S S2A | TWINDOW14 | ENTRANCE DOOR | MWINDOW14 |WindowEnergyReportMonthly
| GWINDOW1 S SWA | GWINDOW1 W SWA | GWINDOW1 W NWA | GWINDOW1 N NWA | GWINDOW1 S SEA | GWINDOW1 E SEA | GWINDOW1 E NEA | GWINDOW1 N NEA | GWINDOW1 N N1A | GWINDOW1 N N2A | GWINDOW1 S S1A | GWINDOW1 S S2A | MWINDOW1 S SWA | MWINDOW1 W SWA | MWINDOW1 W NWA | MWINDOW1 N NWA | MWINDOW1 S SEA | MWINDOW1 E SEA | MWINDOW1 E NEA | MWINDOW1 N NEA | MWINDOW1 N N1A | MWINDOW1 N N2A | MWINDOW1 S S1A | MWINDOW1 S S2A | TWINDOW1 S SWA | TWINDOW1 W SWA | TWINDOW1 W NWA | TWINDOW1 N NWA | TWINDOW1 S SEA | TWINDOW1 E SEA | TWINDOW1 E NEA | TWINDOW1 N NEA | TWINDOW1 N N1A | TWINDOW1 N N2A | TWINDOW1 S S1A | TWINDOW1 S S2A | TWINDOW14 | ENTRANCE DOOR | MWINDOW14 |WindowZoneSummaryMonthly
| G SW APARTMENT | G NW APARTMENT | OFFICE | G NE APARTMENT | G N1 APARTMENT | G N2 APARTMENT | G S1 APARTMENT | G S2 APARTMENT | M SW APARTMENT | M NW APARTMENT | M SE APARTMENT | M NE APARTMENT | M N1 APARTMENT | M N2 APARTMENT | M S1 APARTMENT | M S2 APARTMENT | T SW APARTMENT | T NW APARTMENT | T SE APARTMENT | T NE APARTMENT | T N1 APARTMENT | T N2 APARTMENT | T S1 APARTMENT | T S2 APARTMENT | T CORRIDOR | G CORRIDOR | M CORRIDOR |WindowEnergyZoneSummaryMonthly
| G SW APARTMENT | G NW APARTMENT | OFFICE | G NE APARTMENT | G N1 APARTMENT | G N2 APARTMENT | G S1 APARTMENT | G S2 APARTMENT | M SW APARTMENT | M NW APARTMENT | M SE APARTMENT | M NE APARTMENT | M N1 APARTMENT | M N2 APARTMENT | M S1 APARTMENT | M S2 APARTMENT | T SW APARTMENT | T NW APARTMENT | T SE APARTMENT | T NE APARTMENT | T N1 APARTMENT | T N2 APARTMENT | T S1 APARTMENT | T S2 APARTMENT | T CORRIDOR | G CORRIDOR | M CORRIDOR |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| G SW APARTMENT WATER HEATER | G NW APARTMENT WATER HEATER | G NE APARTMENT WATER HEATER | G N1 APARTMENT WATER HEATER | G N2 APARTMENT WATER HEATER | G S1 APARTMENT WATER HEATER | G S2 APARTMENT WATER HEATER | M SW APARTMENT WATER HEATER | M NW APARTMENT WATER HEATER | M SE APARTMENT WATER HEATER | M NE APARTMENT WATER HEATER | M N1 APARTMENT WATER HEATER | M N2 APARTMENT WATER HEATER | M S1 APARTMENT WATER HEATER | M S2 APARTMENT WATER HEATER | T SW APARTMENT WATER HEATER | T NW APARTMENT WATER HEATER | T SE APARTMENT WATER HEATER | T NE APARTMENT WATER HEATER | T N1 APARTMENT WATER HEATER | T N2 APARTMENT WATER HEATER | T S1 APARTMENT WATER HEATER | T S2 APARTMENT WATER HEATER |DaylightingReportMonthly
| Environment |CoilReportMonthly
| SPLIT GSW HEATING COIL | SPLIT GNW HEATING COIL | SPLIT OFFICE HEATING COIL | SPLIT GNE HEATING COIL | SPLIT GN1 HEATING COIL | SPLIT GN2 HEATING COIL | SPLIT GS1 HEATING COIL | SPLIT GS2 HEATING COIL | SPLIT MSW HEATING COIL | SPLIT MNW HEATING COIL | SPLIT MSE HEATING COIL | SPLIT MNE HEATING COIL | SPLIT MN1 HEATING COIL | SPLIT MN2 HEATING COIL | SPLIT MS1 HEATING COIL | SPLIT MS2 HEATING COIL | SPLIT TSW HEATING COIL | SPLIT TNW HEATING COIL | SPLIT TSE HEATING COIL | SPLIT TNE HEATING COIL | SPLIT TN1 HEATING COIL | SPLIT TN2 HEATING COIL | SPLIT TS1 HEATING COIL | SPLIT TS2 HEATING COIL | SPLIT GSW COOLING COIL | SPLIT GNW COOLING COIL | SPLIT OFFICE COOLING COIL | SPLIT GNE COOLING COIL | SPLIT GN1 COOLING COIL | SPLIT GN2 COOLING COIL | SPLIT GS1 COOLING COIL | SPLIT GS2 COOLING COIL | SPLIT MSW COOLING COIL | SPLIT MNW COOLING COIL | SPLIT MSE COOLING COIL | SPLIT MNE COOLING COIL | SPLIT MN1 COOLING COIL | SPLIT MN2 COOLING COIL | SPLIT MS1 COOLING COIL | SPLIT MS2 COOLING COIL | SPLIT TSW COOLING COIL | SPLIT TNW COOLING COIL | SPLIT TSE COOLING COIL | SPLIT TNE COOLING COIL | SPLIT TN1 COOLING COIL | SPLIT TN2 COOLING COIL | SPLIT TS1 COOLING COIL | SPLIT TS2 COOLING COIL |FanReportMonthly
| SPLIT GSW SUPPLY FAN | G SW APARTMENT ERV SUP FAN | G SW APARTMENT ERV EXH FAN | SPLIT GNW SUPPLY FAN | G NW APARTMENT ERV SUP FAN | G NW APARTMENT ERV EXH FAN | SPLIT OFFICE SUPPLY FAN | SPLIT GNE SUPPLY FAN | G NE APARTMENT ERV SUP FAN | G NE APARTMENT ERV EXH FAN | SPLIT GN1 SUPPLY FAN | G N1 APARTMENT ERV SUP FAN | G N1 APARTMENT ERV EXH FAN | SPLIT GN2 SUPPLY FAN | G N2 APARTMENT ERV SUP FAN | G N2 APARTMENT ERV EXH FAN | SPLIT GS1 SUPPLY FAN | G S1 APARTMENT ERV SUP FAN | G S1 APARTMENT ERV EXH FAN | SPLIT GS2 SUPPLY FAN | G S2 APARTMENT ERV SUP FAN | G S2 APARTMENT ERV EXH FAN | SPLIT MSW SUPPLY FAN | M SW APARTMENT ERV SUP FAN | M SW APARTMENT ERV EXH FAN | SPLIT MNW SUPPLY FAN | M NW APARTMENT ERV SUP FAN | M NW APARTMENT ERV EXH FAN | SPLIT MSE SUPPLY FAN | M SE APARTMENT ERV SUP FAN | M SE APARTMENT ERV EXH FAN | SPLIT MNE SUPPLY FAN | M NE APARTMENT ERV SUP FAN | M NE APARTMENT ERV EXH FAN | SPLIT MN1 SUPPLY FAN | M N1 APARTMENT ERV SUP FAN | M N1 APARTMENT ERV EXH FAN | SPLIT MN2 SUPPLY FAN | M N2 APARTMENT ERV SUP FAN | M N2 APARTMENT ERV EXH FAN | SPLIT MS1 SUPPLY FAN | M S1 APARTMENT ERV SUP FAN | M S1 APARTMENT ERV EXH FAN | SPLIT MS2 SUPPLY FAN | M S2 APARTMENT ERV SUP FAN | M S2 APARTMENT ERV EXH FAN | SPLIT TSW SUPPLY FAN | T SW APARTMENT ERV SUP FAN | T SW APARTMENT ERV EXH FAN | SPLIT TNW SUPPLY FAN | T NW APARTMENT ERV SUP FAN | T NW APARTMENT ERV EXH FAN | SPLIT TSE SUPPLY FAN | T SE APARTMENT ERV SUP FAN | T SE APARTMENT ERV EXH FAN | SPLIT TNE SUPPLY FAN | T NE APARTMENT ERV SUP FAN | T NE APARTMENT ERV EXH FAN | SPLIT TN1 SUPPLY FAN | T N1 APARTMENT ERV SUP FAN | T N1 APARTMENT ERV EXH FAN | SPLIT TN2 SUPPLY FAN | T N2 APARTMENT ERV SUP FAN | T N2 APARTMENT ERV EXH FAN | SPLIT TS1 SUPPLY FAN | T S1 APARTMENT ERV SUP FAN | T S1 APARTMENT ERV EXH FAN | SPLIT TS2 SUPPLY FAN | T S2 APARTMENT ERV SUP FAN | T S2 APARTMENT ERV EXH FAN |ZoneTemperatureOscillationReportMonthly
| G SW APARTMENT | G NW APARTMENT | OFFICE | G NE APARTMENT | G N1 APARTMENT | G N2 APARTMENT | G S1 APARTMENT | G S2 APARTMENT | M SW APARTMENT | M NW APARTMENT | M SE APARTMENT | M NE APARTMENT | M N1 APARTMENT | M N2 APARTMENT | M S1 APARTMENT | M S2 APARTMENT | T SW APARTMENT | T NW APARTMENT | T SE APARTMENT | T NE APARTMENT | T N1 APARTMENT | T N2 APARTMENT | T S1 APARTMENT | T S2 APARTMENT | T CORRIDOR | G CORRIDOR | M CORRIDOR |AirLoopSystemEnergyAndWaterUseMonthly
| SPLIT GSW | SPLIT GNW | SPLIT OFFICE | SPLIT GNE | SPLIT GN1 | SPLIT GN2 | SPLIT GS1 | SPLIT GS2 | SPLIT MSW | SPLIT MNW | SPLIT MSE | SPLIT MNE | SPLIT MN1 | SPLIT MN2 | SPLIT MS1 | SPLIT MS2 | SPLIT TSW | SPLIT TNW | SPLIT TSE | SPLIT TNE | SPLIT TN1 | SPLIT TN2 | SPLIT TS1 | SPLIT TS2 |AirLoopSystemComponentLoadsMonthly
| SPLIT GSW | SPLIT GNW | SPLIT OFFICE | SPLIT GNE | SPLIT GN1 | SPLIT GN2 | SPLIT GS1 | SPLIT GS2 | SPLIT MSW | SPLIT MNW | SPLIT MSE | SPLIT MNE | SPLIT MN1 | SPLIT MN2 | SPLIT MS1 | SPLIT MS2 | SPLIT TSW | SPLIT TNW | SPLIT TSE | SPLIT TNE | SPLIT TN1 | SPLIT TN2 | SPLIT TS1 | SPLIT TS2 |AirLoopSystemComponentEnergyUseMonthly
| SPLIT GSW | SPLIT GNW | SPLIT OFFICE | SPLIT GNE | SPLIT GN1 | SPLIT GN2 | SPLIT GS1 | SPLIT GS2 | SPLIT MSW | SPLIT MNW | SPLIT MSE | SPLIT MNE | SPLIT MN1 | SPLIT MN2 | SPLIT MS1 | SPLIT MS2 | SPLIT TSW | SPLIT TNW | SPLIT TSE | SPLIT TNE | SPLIT TN1 | SPLIT TN2 | SPLIT TS1 | SPLIT TS2 |MechanicalVentilationLoadsMonthly
| G SW APARTMENT | G NW APARTMENT | OFFICE | G NE APARTMENT | G N1 APARTMENT | G N2 APARTMENT | G S1 APARTMENT | G S2 APARTMENT | M SW APARTMENT | M NW APARTMENT | M SE APARTMENT | M NE APARTMENT | M N1 APARTMENT | M N2 APARTMENT | M S1 APARTMENT | M S2 APARTMENT | T SW APARTMENT | T NW APARTMENT | T SE APARTMENT | T NE APARTMENT | T N1 APARTMENT | T N2 APARTMENT | T S1 APARTMENT | T S2 APARTMENT |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 09:15:24
General| Value | |
| Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 09:15 |
| RunPeriod | RUNPERIOD 1 |
| Weather File | Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930 |
| Latitude [deg] | 47.47 |
| Longitude [deg] | -122.3 |
| Elevation [m] | 122.00 |
| Time Zone | -8.0 |
| North Axis Angle [deg] | 0.00 |
| Rotation for Appendix G [deg] | 0.00 |
| Hours Simulated [hrs] | 8760.00 |
| Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
| Gross Wall Area [m2] | 1542.04 | 564.80 | 206.22 | 564.80 | 206.22 |
| Above Ground Wall Area [m2] | 1542.04 | 564.80 | 206.22 | 564.80 | 206.22 |
| Window Opening Area [m2] | 306.92 | 112.97 | 43.82 | 112.97 | 37.16 |
| Gross Window-Wall Ratio [%] | 19.90 | 20.00 | 21.25 | 20.00 | 18.02 |
| Above Ground Window-Wall Ratio [%] | 19.90 | 20.00 | 21.25 | 20.00 | 18.02 |
| Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
| Gross Wall Area [m2] | 1501.17 | 564.80 | 185.79 | 564.80 | 185.79 |
| Above Ground Wall Area [m2] | 1501.17 | 564.80 | 185.79 | 564.80 | 185.79 |
| Window Opening Area [m2] | 300.26 | 112.97 | 37.16 | 112.97 | 37.16 |
| Gross Window-Wall Ratio [%] | 20.00 | 20.00 | 20.00 | 20.00 | 20.00 |
| Above Ground Window-Wall Ratio [%] | 20.00 | 20.00 | 20.00 | 20.00 | 20.00 |
| Total | |
| Gross Roof Area [m2] | 783.65 |
| Skylight Area [m2] | 0.00 |
| Skylight-Roof Ratio [%] | 0.00 |
| Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
| G SW APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 0.00 | 11.71 | 11.71 | 8.6918 | 35.30 | 6.6700 |
| G NW APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 0.00 | 11.71 | 11.71 | 8.6918 | 35.30 | 6.6700 |
| OFFICE | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 0.00 | 11.71 | 11.71 | 9.7532 | 18.58 | 6.6700 |
| G NE APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 0.00 | 11.71 | 11.71 | 8.6918 | 35.30 | 6.6700 |
| G N1 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 0.00 | 7.06 | 7.06 | 8.6918 | 35.30 | 6.6700 |
| G N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 0.00 | 7.06 | 7.06 | 8.6918 | 35.30 | 6.6700 |
| G S1 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 0.00 | 7.06 | 7.06 | 8.6918 | 35.30 | 6.6700 |
| G S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 0.00 | 7.06 | 7.06 | 8.6918 | 35.30 | 6.6700 |
| M SW APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 58.52 | 0.00 | 11.71 | 11.71 | 8.6918 | 35.30 | 6.6700 |
| M NW APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 58.52 | 0.00 | 11.71 | 11.71 | 8.6918 | 35.30 | 6.6700 |
| M SE APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 58.52 | 0.00 | 11.71 | 11.71 | 8.6918 | 35.30 | 6.6700 |
| M NE APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 58.52 | 0.00 | 11.71 | 11.71 | 8.6918 | 35.30 | 6.6700 |
| M N1 APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 35.30 | 0.00 | 7.06 | 7.06 | 8.6918 | 35.30 | 6.6700 |
| M N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 35.30 | 0.00 | 7.06 | 7.06 | 8.6918 | 35.30 | 6.6700 |
| M S1 APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 35.30 | 0.00 | 7.06 | 7.06 | 8.6918 | 35.30 | 6.6700 |
| M S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 35.30 | 0.00 | 7.06 | 7.06 | 8.6918 | 35.30 | 6.6700 |
| T SW APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 0.00 | 11.71 | 11.71 | 8.6918 | 35.30 | 6.6700 |
| T NW APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 0.00 | 11.71 | 11.71 | 8.6918 | 35.30 | 6.6700 |
| T SE APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 0.00 | 11.71 | 11.71 | 8.6918 | 35.30 | 6.6700 |
| T NE APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 0.00 | 11.71 | 11.71 | 8.6918 | 35.30 | 6.6700 |
| T N1 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 0.00 | 7.06 | 7.06 | 8.6918 | 35.30 | 6.6700 |
| T N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 0.00 | 7.06 | 7.06 | 8.6918 | 35.30 | 6.6700 |
| T S1 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 0.00 | 7.06 | 7.06 | 8.6918 | 35.30 | 6.6700 |
| T S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 0.00 | 7.06 | 7.06 | 8.6918 | 35.30 | 6.6700 |
| T CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 0.00 | 1.11 | 1.11 | 4.7725 | 18.58 | 0.0000 |
| G CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 0.00 | 3.32 | 3.32 | 4.7725 | 18.58 | 105.2565 |
| M CORRIDOR | 77.66 | No | Yes | 236.69 | 2.00 | 10.22 | 0.00 | 1.11 | 1.11 | 4.7725 | 18.58 | 0.0000 |
| Total | 3134.61 | 9553.84 | 1542.04 | 0.00 | 306.92 | 306.92 | 8.3333 | 31.67 | 8.6167 | |||
| Conditioned Total | 2823.98 | 8607.06 | 1501.17 | 0.00 | 300.26 | 300.26 | 8.7250 | 34.33 | 6.6700 | |||
| Unconditioned Total | 310.64 | 946.78 | 40.87 | 0.00 | 6.66 | 6.66 | 4.7725 | 18.58 | 26.3141 | |||
| Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
| G SW APARTMENT | 88.25 | Yes | Yes | 1.00 | G SW APARTMENT | GENERAL | G SW APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| G NW APARTMENT | 88.25 | Yes | Yes | 1.00 | G NW APARTMENT | GENERAL | G NW APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| OFFICE | 88.25 | Yes | Yes | 1.00 | OFFICE | GENERAL | OFFICE | 9.7532 | 18.58 | 6.6700 | |
| G NE APARTMENT | 88.25 | Yes | Yes | 1.00 | G NE APARTMENT | GENERAL | G NE APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| G N1 APARTMENT | 88.25 | Yes | Yes | 1.00 | G N1 APARTMENT | GENERAL | G N1 APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| G N2 APARTMENT | 88.25 | Yes | Yes | 1.00 | G N2 APARTMENT | GENERAL | G N2 APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| G S1 APARTMENT | 88.25 | Yes | Yes | 1.00 | G S1 APARTMENT | GENERAL | G S1 APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| G S2 APARTMENT | 88.25 | Yes | Yes | 1.00 | G S2 APARTMENT | GENERAL | G S2 APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| M SW APARTMENT | 88.25 | Yes | Yes | 2.00 | M SW APARTMENT | GENERAL | M SW APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| M NW APARTMENT | 88.25 | Yes | Yes | 2.00 | M NW APARTMENT | GENERAL | M NW APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| M SE APARTMENT | 88.25 | Yes | Yes | 2.00 | M SE APARTMENT | GENERAL | M SE APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| M NE APARTMENT | 88.25 | Yes | Yes | 2.00 | M NE APARTMENT | GENERAL | M NE APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| M N1 APARTMENT | 88.25 | Yes | Yes | 2.00 | M N1 APARTMENT | GENERAL | M N1 APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| M N2 APARTMENT | 88.25 | Yes | Yes | 2.00 | M N2 APARTMENT | GENERAL | M N2 APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| M S1 APARTMENT | 88.25 | Yes | Yes | 2.00 | M S1 APARTMENT | GENERAL | M S1 APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| M S2 APARTMENT | 88.25 | Yes | Yes | 2.00 | M S2 APARTMENT | GENERAL | M S2 APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| T SW APARTMENT | 88.25 | Yes | Yes | 1.00 | T SW APARTMENT | GENERAL | T SW APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| T NW APARTMENT | 88.25 | Yes | Yes | 1.00 | T NW APARTMENT | GENERAL | T NW APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| T SE APARTMENT | 88.25 | Yes | Yes | 1.00 | T SE APARTMENT | GENERAL | T SE APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| T NE APARTMENT | 88.25 | Yes | Yes | 1.00 | T NE APARTMENT | GENERAL | T NE APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| T N1 APARTMENT | 88.25 | Yes | Yes | 1.00 | T N1 APARTMENT | GENERAL | T N1 APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| T N2 APARTMENT | 88.25 | Yes | Yes | 1.00 | T N2 APARTMENT | GENERAL | T N2 APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| T S1 APARTMENT | 88.25 | Yes | Yes | 1.00 | T S1 APARTMENT | GENERAL | T S1 APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| T S2 APARTMENT | 88.25 | Yes | Yes | 1.00 | T S2 APARTMENT | GENERAL | T S2 APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| T CORRIDOR | 77.66 | No | Yes | 1.00 | T CORRIDOR | GENERAL | T CORRIDOR | 4.7725 | 18.58 | 0.0000 | |
| G CORRIDOR | 77.66 | No | Yes | 1.00 | G CORRIDOR | GENERAL | G CORRIDOR | 4.7725 | 18.58 | 105.2565 | |
| M CORRIDOR | 77.66 | No | Yes | 2.00 | M CORRIDOR | GENERAL | M CORRIDOR | 4.7725 | 18.58 | 0.0000 | |
| Total | 3134.61 | 8.3333 | 15.84 | 8.6167 | |||||||
| Conditioned Total | 2823.98 | 8.7250 | 17.17 | 6.6700 | |||||||
| Unconditioned Total | 310.64 | 4.7725 | 9.29 | 26.3141 | |||||||
| Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
| Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
| GENERAL | 3134.61 | 2823.98 | 310.64 | 0.00 | 6.2575 | 41.91 | 7.1145 |
| Total | 3134.61 | 2823.98 | 310.64 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 09:15:24
End Uses| Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
| Time of Peak | 10-AUG-17:19 | 19-FEB-05:00 | - | - | - | - | - | - | - | - | - | - | 01-JAN-07:10 |
| Heating | 0.00 | 63056.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Cooling | 20570.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Lighting | 5231.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment | 22609.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans | 7513.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems | 26752.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Total End Uses | 82678.05 | 63056.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
| Heating | General | 0.00 | 63056.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Cooling | General | 20570.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Lighting | LightsWired | 4887.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LightsPlugIn | 344.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment | MiscPlug | 18441.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| ElevatorLift | 4006.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| ElevatorLightsFan | 162.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| General | 7513.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems | Water Heater | 26752.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 09:15:24
Values gathered over 8760.00 hours| Source Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
| Heating | 0.00 | 265.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Cooling | 161.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Lighting | 314.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Lighting | 158.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment | 1452.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans | 244.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems | 1465.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Total Source Energy End Use Components | 3796.19 | 265.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
| Heating | 0.00 | 94.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Cooling | 57.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Lighting | 111.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Lighting | 55.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment | 514.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans | 86.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems | 518.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Total Source Energy End Use Components | 1344.27 | 94.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
| Heating | 0.00 | 84.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Cooling | 51.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Lighting | 100.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Lighting | 50.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment | 463.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans | 77.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems | 467.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Total Source Energy End Use Components | 1211.06 | 84.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 09:15:24
ZoneHVAC:EnergyRecoveryVentilator| User-Specified Supply Air Flow Rate [m3/s] | User-Specified Exhaust Air Flow Rate [m3/s] | |
| G SW APARTMENT ERV | 0.025955 | 0.025955 |
| G NW APARTMENT ERV | 0.025955 | 0.025955 |
| G NE APARTMENT ERV | 0.025955 | 0.025955 |
| G N1 APARTMENT ERV | 0.025955 | 0.025955 |
| G N2 APARTMENT ERV | 0.025955 | 0.025955 |
| G S1 APARTMENT ERV | 0.025955 | 0.025955 |
| G S2 APARTMENT ERV | 0.025955 | 0.025955 |
| M SW APARTMENT ERV | 0.051909 | 0.051909 |
| M NW APARTMENT ERV | 0.051909 | 0.051909 |
| M SE APARTMENT ERV | 0.051909 | 0.051909 |
| M NE APARTMENT ERV | 0.051909 | 0.051909 |
| M N1 APARTMENT ERV | 0.051909 | 0.051909 |
| M N2 APARTMENT ERV | 0.051909 | 0.051909 |
| M S1 APARTMENT ERV | 0.051909 | 0.051909 |
| M S2 APARTMENT ERV | 0.051909 | 0.051909 |
| T SW APARTMENT ERV | 0.025955 | 0.025955 |
| T NW APARTMENT ERV | 0.025955 | 0.025955 |
| T SE APARTMENT ERV | 0.025955 | 0.025955 |
| T NE APARTMENT ERV | 0.025955 | 0.025955 |
| T N1 APARTMENT ERV | 0.025955 | 0.025955 |
| T N2 APARTMENT ERV | 0.025955 | 0.025955 |
| T S1 APARTMENT ERV | 0.025955 | 0.025955 |
| T S2 APARTMENT ERV | 0.025955 | 0.025955 |
| Design Size Maximum Flow Rate [m3/s] | |
| G SW APARTMENT ERV SUP FAN | 0.025955 |
| G SW APARTMENT ERV EXH FAN | 0.025955 |
| G NW APARTMENT ERV SUP FAN | 0.025955 |
| G NW APARTMENT ERV EXH FAN | 0.025955 |
| G NE APARTMENT ERV SUP FAN | 0.025955 |
| G NE APARTMENT ERV EXH FAN | 0.025955 |
| G N1 APARTMENT ERV SUP FAN | 0.025955 |
| G N1 APARTMENT ERV EXH FAN | 0.025955 |
| G N2 APARTMENT ERV SUP FAN | 0.025955 |
| G N2 APARTMENT ERV EXH FAN | 0.025955 |
| G S1 APARTMENT ERV SUP FAN | 0.025955 |
| G S1 APARTMENT ERV EXH FAN | 0.025955 |
| G S2 APARTMENT ERV SUP FAN | 0.025955 |
| G S2 APARTMENT ERV EXH FAN | 0.025955 |
| M SW APARTMENT ERV SUP FAN | 0.051909 |
| M SW APARTMENT ERV EXH FAN | 0.051909 |
| M NW APARTMENT ERV SUP FAN | 0.051909 |
| M NW APARTMENT ERV EXH FAN | 0.051909 |
| M SE APARTMENT ERV SUP FAN | 0.051909 |
| M SE APARTMENT ERV EXH FAN | 0.051909 |
| M NE APARTMENT ERV SUP FAN | 0.051909 |
| M NE APARTMENT ERV EXH FAN | 0.051909 |
| M N1 APARTMENT ERV SUP FAN | 0.051909 |
| M N1 APARTMENT ERV EXH FAN | 0.051909 |
| M N2 APARTMENT ERV SUP FAN | 0.051909 |
| M N2 APARTMENT ERV EXH FAN | 0.051909 |
| M S1 APARTMENT ERV SUP FAN | 0.051909 |
| M S1 APARTMENT ERV EXH FAN | 0.051909 |
| M S2 APARTMENT ERV SUP FAN | 0.051909 |
| M S2 APARTMENT ERV EXH FAN | 0.051909 |
| T SW APARTMENT ERV SUP FAN | 0.025955 |
| T SW APARTMENT ERV EXH FAN | 0.025955 |
| T NW APARTMENT ERV SUP FAN | 0.025955 |
| T NW APARTMENT ERV EXH FAN | 0.025955 |
| T SE APARTMENT ERV SUP FAN | 0.025955 |
| T SE APARTMENT ERV EXH FAN | 0.025955 |
| T NE APARTMENT ERV SUP FAN | 0.025955 |
| T NE APARTMENT ERV EXH FAN | 0.025955 |
| T N1 APARTMENT ERV SUP FAN | 0.025955 |
| T N1 APARTMENT ERV EXH FAN | 0.025955 |
| T N2 APARTMENT ERV SUP FAN | 0.025955 |
| T N2 APARTMENT ERV EXH FAN | 0.025955 |
| T S1 APARTMENT ERV SUP FAN | 0.025955 |
| T S1 APARTMENT ERV EXH FAN | 0.025955 |
| T S2 APARTMENT ERV SUP FAN | 0.025955 |
| T S2 APARTMENT ERV EXH FAN | 0.025955 |
| SPLIT GSW SUPPLY FAN | 0.364812 |
| SPLIT GNW SUPPLY FAN | 0.306130 |
| SPLIT OFFICE SUPPLY FAN | 0.402388 |
| SPLIT GNE SUPPLY FAN | 0.268809 |
| SPLIT GN1 SUPPLY FAN | 0.245193 |
| SPLIT GN2 SUPPLY FAN | 0.244504 |
| SPLIT GS1 SUPPLY FAN | 0.308497 |
| SPLIT GS2 SUPPLY FAN | 0.310059 |
| SPLIT MSW SUPPLY FAN | 0.885532 |
| SPLIT MNW SUPPLY FAN | 0.775532 |
| SPLIT MSE SUPPLY FAN | 0.773653 |
| SPLIT MNE SUPPLY FAN | 0.666407 |
| SPLIT MN1 SUPPLY FAN | 0.602996 |
| SPLIT MN2 SUPPLY FAN | 0.601097 |
| SPLIT MS1 SUPPLY FAN | 0.723207 |
| SPLIT MS2 SUPPLY FAN | 0.721048 |
| SPLIT TSW SUPPLY FAN | 0.474453 |
| SPLIT TNW SUPPLY FAN | 0.429746 |
| SPLIT TSE SUPPLY FAN | 0.393521 |
| SPLIT TNE SUPPLY FAN | 0.349393 |
| SPLIT TN1 SUPPLY FAN | 0.332760 |
| SPLIT TN2 SUPPLY FAN | 0.330156 |
| SPLIT TS1 SUPPLY FAN | 0.380293 |
| SPLIT TS2 SUPPLY FAN | 0.377678 |
| Design Size Nominal Supply Air Flow Rate [m3/s] | |
| G SW APARTMENT OA HEAT EXCHANGER | 0.025955 |
| G NW APARTMENT OA HEAT EXCHANGER | 0.025955 |
| G NE APARTMENT OA HEAT EXCHANGER | 0.025955 |
| G N1 APARTMENT OA HEAT EXCHANGER | 0.025955 |
| G N2 APARTMENT OA HEAT EXCHANGER | 0.025955 |
| G S1 APARTMENT OA HEAT EXCHANGER | 0.025955 |
| G S2 APARTMENT OA HEAT EXCHANGER | 0.025955 |
| M SW APARTMENT OA HEAT EXCHANGER | 0.051909 |
| M NW APARTMENT OA HEAT EXCHANGER | 0.051909 |
| M SE APARTMENT OA HEAT EXCHANGER | 0.051909 |
| M NE APARTMENT OA HEAT EXCHANGER | 0.051909 |
| M N1 APARTMENT OA HEAT EXCHANGER | 0.051909 |
| M N2 APARTMENT OA HEAT EXCHANGER | 0.051909 |
| M S1 APARTMENT OA HEAT EXCHANGER | 0.051909 |
| M S2 APARTMENT OA HEAT EXCHANGER | 0.051909 |
| T SW APARTMENT OA HEAT EXCHANGER | 0.025955 |
| T NW APARTMENT OA HEAT EXCHANGER | 0.025955 |
| T SE APARTMENT OA HEAT EXCHANGER | 0.025955 |
| T NE APARTMENT OA HEAT EXCHANGER | 0.025955 |
| T N1 APARTMENT OA HEAT EXCHANGER | 0.025955 |
| T N2 APARTMENT OA HEAT EXCHANGER | 0.025955 |
| T S1 APARTMENT OA HEAT EXCHANGER | 0.025955 |
| T S2 APARTMENT OA HEAT EXCHANGER | 0.025955 |
| Design Size Maximum Air Flow Rate [m3/s] | |
| G SW APARTMENT DIRECT AIR | 0.364812 |
| G NW APARTMENT DIRECT AIR | 0.306130 |
| OFFICE DIRECT AIR | 0.402388 |
| G NE APARTMENT DIRECT AIR | 0.268809 |
| G N1 APARTMENT DIRECT AIR | 0.245193 |
| G N2 APARTMENT DIRECT AIR | 0.244504 |
| G S1 APARTMENT DIRECT AIR | 0.308497 |
| G S2 APARTMENT DIRECT AIR | 0.310059 |
| M SW APARTMENT DIRECT AIR | 0.885532 |
| M NW APARTMENT DIRECT AIR | 0.775532 |
| M SE APARTMENT DIRECT AIR | 0.773653 |
| M NE APARTMENT DIRECT AIR | 0.666407 |
| M N1 APARTMENT DIRECT AIR | 0.602996 |
| M N2 APARTMENT DIRECT AIR | 0.601097 |
| M S1 APARTMENT DIRECT AIR | 0.723207 |
| M S2 APARTMENT DIRECT AIR | 0.721048 |
| T SW APARTMENT DIRECT AIR | 0.474453 |
| T NW APARTMENT DIRECT AIR | 0.429746 |
| T SE APARTMENT DIRECT AIR | 0.393521 |
| T NE APARTMENT DIRECT AIR | 0.349393 |
| T N1 APARTMENT DIRECT AIR | 0.332760 |
| T N2 APARTMENT DIRECT AIR | 0.330156 |
| T S1 APARTMENT DIRECT AIR | 0.380293 |
| T S2 APARTMENT DIRECT AIR | 0.377678 |
| Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
| SPLIT GSW | 0.364812 | 0.364812 | 0.364812 | 0.364812 | 0.364812 | 0.364812 | 1.00 | 1.000000 | 0.364812 |
| SPLIT GNW | 0.306130 | 0.306130 | 0.306130 | 0.306130 | 0.306130 | 0.306130 | 1.00 | 1.00 | 0.306130 |
| SPLIT OFFICE | 0.402388 | 0.402388 | 0.402388 | 0.402388 | 0.402388 | 0.402388 | 1.00 | 1.00 | 0.402388 |
| SPLIT GNE | 0.268809 | 0.268809 | 0.268809 | 0.268809 | 0.268809 | 0.268809 | 1.00 | 1.000000 | 0.268809 |
| SPLIT GN1 | 0.245193 | 0.245193 | 0.245193 | 0.245193 | 0.245193 | 0.245193 | 1.00 | 1.00 | 0.245193 |
| SPLIT GN2 | 0.244504 | 0.244504 | 0.244504 | 0.244504 | 0.244504 | 0.244504 | 1.00 | 1.00 | 0.244504 |
| SPLIT GS1 | 0.308497 | 0.308497 | 0.308497 | 0.308497 | 0.308497 | 0.308497 | 1.00 | 1.00 | 0.308497 |
| SPLIT GS2 | 0.310059 | 0.310059 | 0.310059 | 0.310059 | 0.310059 | 0.310059 | 1.00 | 1.00 | 0.310059 |
| SPLIT MSW | 0.885532 | 0.885532 | 0.885532 | 0.885532 | 0.885532 | 0.885532 | 1.00 | 1.00 | 0.885532 |
| SPLIT MNW | 0.775532 | 0.775532 | 0.775532 | 0.775532 | 0.775532 | 0.775532 | 1.00 | 1.00 | 0.775532 |
| SPLIT MSE | 0.773653 | 0.773653 | 0.773653 | 0.773653 | 0.773653 | 0.773653 | 1.00 | 1.00 | 0.773653 |
| SPLIT MNE | 0.666407 | 0.666407 | 0.666407 | 0.666407 | 0.666407 | 0.666407 | 1.00 | 1.00 | 0.666407 |
| SPLIT MN1 | 0.602996 | 0.602996 | 0.602996 | 0.602996 | 0.602996 | 0.602996 | 1.00 | 1.00 | 0.602996 |
| SPLIT MN2 | 0.601097 | 0.601097 | 0.601097 | 0.601097 | 0.601097 | 0.601097 | 1.00 | 1.00 | 0.601097 |
| SPLIT MS1 | 0.723207 | 0.723207 | 0.723207 | 0.723207 | 0.723207 | 0.723207 | 1.00 | 1.000000 | 0.723207 |
| SPLIT MS2 | 0.721048 | 0.721048 | 0.721048 | 0.721048 | 0.721048 | 0.721048 | 1.00 | 1.00 | 0.721048 |
| SPLIT TSW | 0.474453 | 0.474453 | 0.474453 | 0.474453 | 0.474453 | 0.474453 | 1.00 | 1.000000 | 0.474453 |
| SPLIT TNW | 0.429746 | 0.429746 | 0.429746 | 0.429746 | 0.429746 | 0.429746 | 1.00 | 1.00 | 0.429746 |
| SPLIT TSE | 0.393521 | 0.393521 | 0.393521 | 0.393521 | 0.393521 | 0.393521 | 1.00 | 1.000000 | 0.393521 |
| SPLIT TNE | 0.349393 | 0.349393 | 0.349393 | 0.349393 | 0.349393 | 0.349393 | 1.00 | 1.00 | 0.349393 |
| SPLIT TN1 | 0.332760 | 0.332760 | 0.332760 | 0.332760 | 0.332760 | 0.332760 | 1.00 | 1.00 | 0.332760 |
| SPLIT TN2 | 0.330156 | 0.330156 | 0.330156 | 0.330156 | 0.330156 | 0.330156 | 1.00 | 1.00 | 0.330156 |
| SPLIT TS1 | 0.380293 | 0.380293 | 0.380293 | 0.380293 | 0.380293 | 0.380293 | 1.00 | 1.00 | 0.380293 |
| SPLIT TS2 | 0.377678 | 0.377678 | 0.377678 | 0.377678 | 0.377678 | 0.377678 | 1.00 | 1.00 | 0.377678 |
| Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
| SPLIT GSW_OA_CONTROLLER | 0.364812 | 0.025955 |
| SPLIT GNW_OA_CONTROLLER | 0.306130 | 0.025955 |
| SPLIT OFFICE_OA_CONTROLLER | 0.402388 | 0.038106 |
| SPLIT GNE_OA_CONTROLLER | 0.268809 | 0.025955 |
| SPLIT GN1_OA_CONTROLLER | 0.245193 | 0.025955 |
| SPLIT GN2_OA_CONTROLLER | 0.244504 | 0.025955 |
| SPLIT GS1_OA_CONTROLLER | 0.308497 | 0.025955 |
| SPLIT GS2_OA_CONTROLLER | 0.310059 | 0.025955 |
| SPLIT MSW_OA_CONTROLLER | 0.885532 | 0.051909 |
| SPLIT MNW_OA_CONTROLLER | 0.775532 | 0.051909 |
| SPLIT MSE_OA_CONTROLLER | 0.773653 | 0.051909 |
| SPLIT MNE_OA_CONTROLLER | 0.666407 | 0.051909 |
| SPLIT MN1_OA_CONTROLLER | 0.602996 | 0.051909 |
| SPLIT MN2_OA_CONTROLLER | 0.601097 | 0.051909 |
| SPLIT MS1_OA_CONTROLLER | 0.723207 | 0.051909 |
| SPLIT MS2_OA_CONTROLLER | 0.721048 | 0.051909 |
| SPLIT TSW_OA_CONTROLLER | 0.474453 | 0.025955 |
| SPLIT TNW_OA_CONTROLLER | 0.429746 | 0.025955 |
| SPLIT TSE_OA_CONTROLLER | 0.393521 | 0.025955 |
| SPLIT TNE_OA_CONTROLLER | 0.349393 | 0.025955 |
| SPLIT TN1_OA_CONTROLLER | 0.332760 | 0.025955 |
| SPLIT TN2_OA_CONTROLLER | 0.330156 | 0.025955 |
| SPLIT TS1_OA_CONTROLLER | 0.380293 | 0.025955 |
| SPLIT TS2_OA_CONTROLLER | 0.377678 | 0.025955 |
| Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | Design Size Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
| SPLIT GSW_UNITARY_PACKAGE_DX | 0.364812 | 0.364812 | 0.364812 | 0.364812 | 6038.93 | 9007.43 | 40.00 | 1.00 |
| SPLIT GNW_UNITARY_PACKAGE_DX | 0.306130 | 0.306130 | 0.306130 | 0.306130 | 5067.55 | 7684.47 | 40.00 | 1.00 |
| SPLIT OFFICE_UNITARY_PACKAGE_DX | 0.402388 | 0.402388 | 0.402388 | 0.402388 | 6660.94 | 10221.22 | 40.00 | 1.00 |
| SPLIT GNE_UNITARY_PACKAGE_DX | 0.268809 | 0.268809 | 0.268809 | 0.268809 | 4449.75 | 6843.13 | 40.00 | 1.00 |
| SPLIT GN1_UNITARY_PACKAGE_DX | 0.245193 | 0.245193 | 0.245193 | 0.245193 | 4058.81 | 6310.68 | 40.00 | 1.00 |
| SPLIT GN2_UNITARY_PACKAGE_DX | 0.244504 | 0.244504 | 0.244504 | 0.244504 | 4047.42 | 6295.16 | 40.00 | 1.00 |
| SPLIT GS1_UNITARY_PACKAGE_DX | 0.308497 | 0.308497 | 0.308497 | 0.308497 | 5106.72 | 7737.82 | 40.00 | 1.00 |
| SPLIT GS2_UNITARY_PACKAGE_DX | 0.310059 | 0.310059 | 0.310059 | 0.310059 | 5132.58 | 7773.03 | 40.00 | 1.00 |
| SPLIT MSW_UNITARY_PACKAGE_DX | 0.885532 | 0.885532 | 0.885532 | 0.885532 | 14658.71 | 21530.46 | 40.00 | 1.00 |
| SPLIT MNW_UNITARY_PACKAGE_DX | 0.775532 | 0.775532 | 0.775532 | 0.775532 | 12837.81 | 19050.28 | 40.00 | 1.00 |
| SPLIT MSE_UNITARY_PACKAGE_DX | 0.773653 | 0.773653 | 0.773653 | 0.773653 | 12806.70 | 19008.16 | 40.00 | 1.00 |
| SPLIT MNE_UNITARY_PACKAGE_DX | 0.666407 | 0.666407 | 0.666407 | 0.666407 | 11031.40 | 16590.11 | 40.00 | 1.00 |
| SPLIT MN1_UNITARY_PACKAGE_DX | 0.602996 | 0.602996 | 0.602996 | 0.602996 | 9981.72 | 15160.23 | 40.00 | 1.00 |
| SPLIT MN2_UNITARY_PACKAGE_DX | 0.601097 | 0.601097 | 0.601097 | 0.601097 | 9950.29 | 15117.42 | 40.00 | 1.00 |
| SPLIT MS1_UNITARY_PACKAGE_DX | 0.723207 | 0.723207 | 0.723207 | 0.723207 | 11971.64 | 17870.48 | 40.00 | 1.00 |
| SPLIT MS2_UNITARY_PACKAGE_DX | 0.721048 | 0.721048 | 0.721048 | 0.721048 | 11935.91 | 17821.82 | 40.00 | 1.00 |
| SPLIT TSW_UNITARY_PACKAGE_DX | 0.474453 | 0.474453 | 0.474453 | 0.474453 | 7853.87 | 11479.86 | 40.00 | 1.00 |
| SPLIT TNW_UNITARY_PACKAGE_DX | 0.429746 | 0.429746 | 0.429746 | 0.429746 | 7113.83 | 10471.79 | 40.00 | 1.00 |
| SPLIT TSE_UNITARY_PACKAGE_DX | 0.393521 | 0.393521 | 0.393521 | 0.393521 | 6514.17 | 9655.23 | 40.00 | 1.00 |
| SPLIT TNE_UNITARY_PACKAGE_DX | 0.349393 | 0.349393 | 0.349393 | 0.349393 | 5783.70 | 8660.24 | 40.00 | 1.00 |
| SPLIT TN1_UNITARY_PACKAGE_DX | 0.332760 | 0.332760 | 0.332760 | 0.332760 | 5508.35 | 8284.98 | 40.00 | 1.00 |
| SPLIT TN2_UNITARY_PACKAGE_DX | 0.330156 | 0.330156 | 0.330156 | 0.330156 | 5465.26 | 8226.28 | 40.00 | 1.00 |
| SPLIT TS1_UNITARY_PACKAGE_DX | 0.380293 | 0.380293 | 0.380293 | 0.380293 | 6295.20 | 9356.72 | 40.00 | 1.00 |
| SPLIT TS2_UNITARY_PACKAGE_DX | 0.377678 | 0.377678 | 0.377678 | 0.377678 | 6251.91 | 9297.76 | 40.00 | 1.00 |
| Design Size Rated Air Flow Rate [m3/s] | Design Size Gross Rated Total Cooling Capacity [W] | Design Size Gross Rated Sensible Heat Ratio | |
| SPLIT GSW COOLING COIL | 0.364812 | 6038.93 | 0.800655 |
| SPLIT GNW COOLING COIL | 0.306130 | 5067.55 | 0.800655 |
| SPLIT OFFICE COOLING COIL | 0.402388 | 6660.94 | 0.800655 |
| SPLIT GNE COOLING COIL | 0.268809 | 4449.75 | 0.800655 |
| SPLIT GN1 COOLING COIL | 0.245193 | 4058.81 | 0.800655 |
| SPLIT GN2 COOLING COIL | 0.244504 | 4047.42 | 0.800655 |
| SPLIT GS1 COOLING COIL | 0.308497 | 5106.72 | 0.800655 |
| SPLIT GS2 COOLING COIL | 0.310059 | 5132.58 | 0.800655 |
| SPLIT MSW COOLING COIL | 0.885532 | 14658.71 | 0.800655 |
| SPLIT MNW COOLING COIL | 0.775532 | 12837.81 | 0.800655 |
| SPLIT MSE COOLING COIL | 0.773653 | 12806.70 | 0.800655 |
| SPLIT MNE COOLING COIL | 0.666407 | 11031.40 | 0.800655 |
| SPLIT MN1 COOLING COIL | 0.602996 | 9981.72 | 0.800655 |
| SPLIT MN2 COOLING COIL | 0.601097 | 9950.29 | 0.800655 |
| SPLIT MS1 COOLING COIL | 0.723207 | 11971.64 | 0.800655 |
| SPLIT MS2 COOLING COIL | 0.721048 | 11935.91 | 0.800655 |
| SPLIT TSW COOLING COIL | 0.474453 | 7853.87 | 0.800655 |
| SPLIT TNW COOLING COIL | 0.429746 | 7113.83 | 0.800655 |
| SPLIT TSE COOLING COIL | 0.393521 | 6514.17 | 0.800655 |
| SPLIT TNE COOLING COIL | 0.349393 | 5783.70 | 0.800655 |
| SPLIT TN1 COOLING COIL | 0.332760 | 5508.35 | 0.800655 |
| SPLIT TN2 COOLING COIL | 0.330156 | 5465.26 | 0.800655 |
| SPLIT TS1 COOLING COIL | 0.380293 | 6295.20 | 0.800655 |
| SPLIT TS2 COOLING COIL | 0.377678 | 6251.91 | 0.800655 |
| Design Size Nominal Capacity [W] | |
| SPLIT GSW HEATING COIL | 9007.43 |
| SPLIT GNW HEATING COIL | 7684.47 |
| SPLIT OFFICE HEATING COIL | 10221.22 |
| SPLIT GNE HEATING COIL | 6843.13 |
| SPLIT GN1 HEATING COIL | 6310.68 |
| SPLIT GN2 HEATING COIL | 6295.16 |
| SPLIT GS1 HEATING COIL | 7737.82 |
| SPLIT GS2 HEATING COIL | 7773.03 |
| SPLIT MSW HEATING COIL | 21530.46 |
| SPLIT MNW HEATING COIL | 19050.28 |
| SPLIT MSE HEATING COIL | 19008.16 |
| SPLIT MNE HEATING COIL | 16590.11 |
| SPLIT MN1 HEATING COIL | 15160.23 |
| SPLIT MN2 HEATING COIL | 15117.42 |
| SPLIT MS1 HEATING COIL | 17870.48 |
| SPLIT MS2 HEATING COIL | 17821.82 |
| SPLIT TSW HEATING COIL | 11479.86 |
| SPLIT TNW HEATING COIL | 10471.79 |
| SPLIT TSE HEATING COIL | 9655.23 |
| SPLIT TNE HEATING COIL | 8660.24 |
| SPLIT TN1 HEATING COIL | 8284.98 |
| SPLIT TN2 HEATING COIL | 8226.28 |
| SPLIT TS1 HEATING COIL | 9356.72 |
| SPLIT TS2 HEATING COIL | 9297.76 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 09:15:24
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other Surfaces| None |
| Possible Shadow Receivers | |
| G SWALL SWA | GWINDOW1 S SWA | |
| G WWALL SWA | GWINDOW1 W SWA | |
| G NWALL NWA | GWINDOW1 N NWA | |
| G WWALL NWA | GWINDOW1 W NWA | |
| G SWALL SEA | GWINDOW1 S SEA | |
| G EWALL SEA | GWINDOW1 E SEA | |
| G NWALL NEA | GWINDOW1 N NEA | |
| G EWALL NEA | GWINDOW1 E NEA | |
| G NWALL N1A | GWINDOW1 N N1A | |
| G NWALL N2A | GWINDOW1 N N2A | |
| G SWALL S1A | GWINDOW1 S S1A | |
| G SWALL S2A | GWINDOW1 S S2A | |
| M WWALL SWA | MWINDOW1 W SWA | |
| M SWALL SWA | MWINDOW1 S SWA | |
| M NWALL NWA | MWINDOW1 N NWA | |
| M WWALL NWA | MWINDOW1 W NWA | |
| M EWALL SEA | MWINDOW1 E SEA | |
| M SWALL SEA | MWINDOW1 S SEA | |
| M NWALL NEA | MWINDOW1 N NEA | |
| M EWALL NEA | MWINDOW1 E NEA | |
| M NWALL N1A | MWINDOW1 N N1A | |
| M NWALL N2A | MWINDOW1 N N2A | |
| M SWALL S1A | MWINDOW1 S S1A | |
| M SWALL S2A | MWINDOW1 S S2A | |
| T WWALL SWA | TWINDOW1 W SWA | |
| T SWALL SWA | TWINDOW1 S SWA | |
| T NWALL NWA | TWINDOW1 N NWA | |
| T WWALL NWA | TWINDOW1 W NWA | |
| T EWALL SEA | TWINDOW1 E SEA | |
| T SWALL SEA | TWINDOW1 S SEA | |
| T NWALL NEA | TWINDOW1 N NEA | |
| T EWALL NEA | TWINDOW1 E NEA | |
| T NWALL N1A | TWINDOW1 N N1A | |
| T NWALL N2A | TWINDOW1 N N2A | |
| T SWALL S1A | TWINDOW1 S S1A | |
| T SWALL S2A | TWINDOW1 S S2A | |
| T EWALL C | TWINDOW14 | |
| G EWALL C | ENTRANCE DOOR | |
| M EWALL C | MWINDOW14 | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 09:15:24
Time Not Meeting the Adaptive Comfort Models during Occupied Hours| ASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 09:15:24
Version| Version ID | |
| 1 | 22.1 |
| #TimeSteps | Minutes per TimeStep {minutes} | |
| 1 | 6 | 10 |
| Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
| 1 | 1 | 20 | 2 | 8 |
| Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
| 1 | Yes | Yes | No | No | Yes | No |
| Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
| 1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
| Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
| 1 | 0.556 | 0.556 |
| Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
| 1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
| Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
| 1 | 11.40 | 8.10 | 5.40 | 4.50 | 5.80 | 8.30 | 10.90 | 13.00 | 15.60 | 17.70 | 18.80 | 15.10 |
| Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
| 1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
| Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
| 1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
| Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
| 1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
| Normal | Daylighting {dimensionless} | |
| 1 | 1.000 | 1.000 |
| Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
| 1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
| Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
| 1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
| Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
| 1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
| Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
| 1 | Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930 | 47.47 | -122.32 | -8.00 | 122.00 | 99868 | 1.1870 |
| Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
| 1 | Correlation | NA | 11.22 | 14.30 | NA |
| Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
| 1 | ApartmentMidRise | 0.000 | City | 4.00000E-002 | 0.40000 | FullExterior | 25 | 6 |
| Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
| 1 | TARP |
| Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
| 1 | TARP |
| Value {Anisotropic} | |
| 1 | Anisotropic |
| Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
| 1 | ThirdOrderBackwardDifference |
| Simulation {Yes/No} | Carbon Dioxide Concentration | |
| 1 | No | N/A |
| Simulation {Yes/No} | Generic Contaminant Concentration | |
| 1 | No | N/A |
| Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
| 1 | No | N/A | N/A | N/A |
| Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
| 1 | RegulaFalsi |
| Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
| 1 | 0.330 | 460.000 | 6.500000E-003 |
| Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
| 1 | LowerLeftCorner | Clockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
| Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
| 1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
| Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
| 1 | 0 | 0 | 0 |
| Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
| 1 | 27 | 243 | 39 |
| Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
| 1 | G SW APARTMENT | 0.0 | 0.00 | 0.00 | 0.00 | 5.79 | 3.81 | 1.52 | 1 | 1 | 1 | 0.00 | 11.58 | 0.00 | 7.62 | 0.00 | 3.05 | 3.05 | 268.97 | TARP | TARP | 88.25 | 58.52 | 46.82 | 11.71 | 6 | 2 | 0 | Yes |
| 2 | G NW APARTMENT | 0.0 | 0.00 | 9.30 | 0.00 | 5.79 | 13.11 | 1.52 | 1 | 1 | 1 | 0.00 | 11.58 | 9.30 | 16.92 | 0.00 | 3.05 | 3.05 | 268.97 | TARP | TARP | 88.25 | 58.52 | 46.82 | 11.71 | 6 | 2 | 0 | Yes |
| 3 | OFFICE | 0.0 | 34.75 | 0.00 | 0.00 | 40.54 | 3.81 | 1.52 | 1 | 1 | 1 | 34.75 | 46.33 | 0.00 | 7.62 | 0.00 | 3.05 | 3.05 | 268.97 | TARP | TARP | 88.25 | 58.52 | 46.82 | 11.71 | 6 | 2 | 0 | Yes |
| 4 | G NE APARTMENT | 0.0 | 34.75 | 9.30 | 0.00 | 40.54 | 13.11 | 1.52 | 1 | 1 | 1 | 34.75 | 46.33 | 9.30 | 16.92 | 0.00 | 3.05 | 3.05 | 268.97 | TARP | TARP | 88.25 | 58.52 | 46.82 | 11.71 | 6 | 2 | 0 | Yes |
| 5 | G N1 APARTMENT | 0.0 | 11.58 | 9.30 | 0.00 | 17.37 | 13.11 | 1.52 | 1 | 1 | 1 | 11.58 | 23.16 | 9.30 | 16.92 | 0.00 | 3.05 | 3.05 | 268.97 | TARP | TARP | 88.25 | 35.30 | 28.24 | 7.06 | 6 | 1 | 0 | Yes |
| 6 | G N2 APARTMENT | 0.0 | 23.16 | 9.30 | 0.00 | 28.95 | 13.11 | 1.52 | 1 | 1 | 1 | 23.16 | 34.75 | 9.30 | 16.92 | 0.00 | 3.05 | 3.05 | 268.97 | TARP | TARP | 88.25 | 35.30 | 28.24 | 7.06 | 6 | 1 | 0 | Yes |
| 7 | G S1 APARTMENT | 0.0 | 11.58 | 0.00 | 0.00 | 17.37 | 3.81 | 1.52 | 1 | 1 | 1 | 11.58 | 23.16 | 0.00 | 7.62 | 0.00 | 3.05 | 3.05 | 268.97 | TARP | TARP | 88.25 | 35.30 | 28.24 | 7.06 | 6 | 1 | 0 | Yes |
| 8 | G S2 APARTMENT | 0.0 | 23.16 | 0.00 | 0.00 | 28.95 | 3.81 | 1.52 | 1 | 1 | 1 | 23.16 | 34.75 | 0.00 | 7.62 | 0.00 | 3.05 | 3.05 | 268.97 | TARP | TARP | 88.25 | 35.30 | 28.24 | 7.06 | 6 | 1 | 0 | Yes |
| 9 | M SW APARTMENT | 0.0 | 0.00 | 0.00 | 3.05 | 5.79 | 3.81 | 4.57 | 1 | 1 | 2 | 0.00 | 11.58 | 0.00 | 7.62 | 3.05 | 6.10 | 3.05 | 268.97 | TARP | TARP | 88.25 | 58.52 | 46.82 | 11.71 | 6 | 2 | 0 | Yes |
| 10 | M NW APARTMENT | 0.0 | 0.00 | 9.30 | 3.05 | 5.79 | 13.11 | 4.57 | 1 | 1 | 2 | 0.00 | 11.58 | 9.30 | 16.92 | 3.05 | 6.10 | 3.05 | 268.97 | TARP | TARP | 88.25 | 58.52 | 46.82 | 11.71 | 6 | 2 | 0 | Yes |
| 11 | M SE APARTMENT | 0.0 | 34.75 | 0.00 | 3.05 | 40.54 | 3.81 | 4.57 | 1 | 1 | 2 | 34.75 | 46.33 | 0.00 | 7.62 | 3.05 | 6.10 | 3.05 | 268.97 | TARP | TARP | 88.25 | 58.52 | 46.82 | 11.71 | 6 | 2 | 0 | Yes |
| 12 | M NE APARTMENT | 0.0 | 34.75 | 9.30 | 3.05 | 40.54 | 13.11 | 4.57 | 1 | 1 | 2 | 34.75 | 46.33 | 9.30 | 16.92 | 3.05 | 6.10 | 3.05 | 268.97 | TARP | TARP | 88.25 | 58.52 | 46.82 | 11.71 | 6 | 2 | 0 | Yes |
| 13 | M N1 APARTMENT | 0.0 | 11.58 | 9.30 | 3.05 | 17.37 | 13.11 | 4.57 | 1 | 1 | 2 | 11.58 | 23.16 | 9.30 | 16.92 | 3.05 | 6.10 | 3.05 | 268.97 | TARP | TARP | 88.25 | 35.30 | 28.24 | 7.06 | 6 | 1 | 0 | Yes |
| 14 | M N2 APARTMENT | 0.0 | 23.16 | 9.30 | 3.05 | 28.95 | 13.11 | 4.57 | 1 | 1 | 2 | 23.16 | 34.75 | 9.30 | 16.92 | 3.05 | 6.10 | 3.05 | 268.97 | TARP | TARP | 88.25 | 35.30 | 28.24 | 7.06 | 6 | 1 | 0 | Yes |
| 15 | M S1 APARTMENT | 0.0 | 11.58 | 0.00 | 3.05 | 17.37 | 3.81 | 4.57 | 1 | 1 | 2 | 11.58 | 23.16 | 0.00 | 7.62 | 3.05 | 6.10 | 3.05 | 268.97 | TARP | TARP | 88.25 | 35.30 | 28.24 | 7.06 | 6 | 1 | 0 | Yes |
| 16 | M S2 APARTMENT | 0.0 | 23.16 | 0.00 | 3.05 | 28.95 | 3.81 | 4.57 | 1 | 1 | 2 | 23.16 | 34.75 | 0.00 | 7.62 | 3.05 | 6.10 | 3.05 | 268.97 | TARP | TARP | 88.25 | 35.30 | 28.24 | 7.06 | 6 | 1 | 0 | Yes |
| 17 | T SW APARTMENT | 0.0 | 0.00 | 0.00 | 9.14 | 5.79 | 3.81 | 10.67 | 1 | 1 | 1 | 0.00 | 11.58 | 0.00 | 7.62 | 9.14 | 12.19 | 3.05 | 268.97 | TARP | TARP | 88.25 | 58.52 | 46.82 | 11.71 | 6 | 2 | 0 | Yes |
| 18 | T NW APARTMENT | 0.0 | 0.00 | 9.30 | 9.14 | 5.79 | 13.11 | 10.67 | 1 | 1 | 1 | 0.00 | 11.58 | 9.30 | 16.92 | 9.14 | 12.19 | 3.05 | 268.97 | TARP | TARP | 88.25 | 58.52 | 46.82 | 11.71 | 6 | 2 | 0 | Yes |
| 19 | T SE APARTMENT | 0.0 | 34.75 | 0.00 | 9.14 | 40.54 | 3.81 | 10.67 | 1 | 1 | 1 | 34.75 | 46.33 | 0.00 | 7.62 | 9.14 | 12.19 | 3.05 | 268.97 | TARP | TARP | 88.25 | 58.52 | 46.82 | 11.71 | 6 | 2 | 0 | Yes |
| 20 | T NE APARTMENT | 0.0 | 34.75 | 9.30 | 9.14 | 40.54 | 13.11 | 10.67 | 1 | 1 | 1 | 34.75 | 46.33 | 9.30 | 16.92 | 9.14 | 12.19 | 3.05 | 268.97 | TARP | TARP | 88.25 | 58.52 | 46.82 | 11.71 | 6 | 2 | 0 | Yes |
| 21 | T N1 APARTMENT | 0.0 | 11.58 | 9.30 | 9.14 | 17.37 | 13.11 | 10.67 | 1 | 1 | 1 | 11.58 | 23.16 | 9.30 | 16.92 | 9.14 | 12.19 | 3.05 | 268.97 | TARP | TARP | 88.25 | 35.30 | 28.24 | 7.06 | 6 | 1 | 0 | Yes |
| 22 | T N2 APARTMENT | 0.0 | 23.16 | 9.30 | 9.14 | 28.95 | 13.11 | 10.67 | 1 | 1 | 1 | 23.16 | 34.75 | 9.30 | 16.92 | 9.14 | 12.19 | 3.05 | 268.97 | TARP | TARP | 88.25 | 35.30 | 28.24 | 7.06 | 6 | 1 | 0 | Yes |
| 23 | T S1 APARTMENT | 0.0 | 11.58 | 0.00 | 9.14 | 17.37 | 3.81 | 10.67 | 1 | 1 | 1 | 11.58 | 23.16 | 0.00 | 7.62 | 9.14 | 12.19 | 3.05 | 268.97 | TARP | TARP | 88.25 | 35.30 | 28.24 | 7.06 | 6 | 1 | 0 | Yes |
| 24 | T S2 APARTMENT | 0.0 | 23.16 | 0.00 | 9.14 | 28.95 | 3.81 | 10.67 | 1 | 1 | 1 | 23.16 | 34.75 | 0.00 | 7.62 | 9.14 | 12.19 | 3.05 | 268.97 | TARP | TARP | 88.25 | 35.30 | 28.24 | 7.06 | 6 | 1 | 0 | Yes |
| 25 | T CORRIDOR | 0.0 | 0.00 | 7.62 | 9.14 | 23.16 | 8.46 | 10.67 | 1 | 1 | 1 | 0.00 | 46.33 | 7.62 | 9.30 | 9.14 | 12.19 | 3.05 | 236.69 | TARP | TARP | 77.66 | 10.22 | 9.10 | 1.11 | 12 | 1 | 0 | Yes |
| 26 | G CORRIDOR | 0.0 | 0.00 | 7.62 | 0.00 | 23.16 | 8.46 | 1.52 | 1 | 1 | 1 | 0.00 | 46.33 | 7.62 | 9.30 | 0.00 | 3.05 | 3.05 | 236.69 | TARP | TARP | 77.66 | 10.22 | 6.90 | 3.32 | 12 | 1 | 0 | Yes |
| 27 | M CORRIDOR | 0.0 | 0.00 | 7.62 | 3.05 | 23.16 | 8.46 | 4.57 | 1 | 1 | 2 | 0.00 | 46.33 | 7.62 | 9.30 | 3.05 | 6.10 | 3.05 | 236.69 | TARP | TARP | 77.66 | 10.22 | 9.10 | 1.11 | 12 | 1 | 0 | Yes |
| Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
| 1 | G SW APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 2 | G NW APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 3 | OFFICE | 88.25 | 4.7 | 18.581 | 5.382E-002 | 9.753 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 16.423 | No |
| 4 | G NE APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 5 | G N1 APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 6 | G N2 APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 7 | G S1 APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 8 | G S2 APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 9 | M SW APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 10 | M NW APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 11 | M SE APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 12 | M NE APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 13 | M N1 APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 14 | M N2 APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 15 | M S1 APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 16 | M S2 APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 17 | T SW APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 18 | T NW APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 19 | T SE APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 20 | T NE APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 21 | T N1 APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 22 | T N2 APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 23 | T S1 APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 24 | T S2 APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 25 | T CORRIDOR | 77.66 | 4.2 | 18.579 | 5.382E-002 | 4.772 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 4.772 | No |
| 26 | G CORRIDOR | 77.66 | 4.2 | 18.579 | 5.382E-002 | 4.772 | 105.256 | 0.000 | 0.000 | 0.000 | 0.000 | 110.029 | No |
| 27 | M CORRIDOR | 77.66 | 4.2 | 18.579 | 5.382E-002 | 4.772 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 4.772 | No |
| Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | |
| 1 | OCCUP_GSW | OCC_APT_SCH_WORKING_FAMILY | G SW APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 3 |
| 2 | OCCUP_GNW | OCC_APT_SCH_STAY_HOME_FAMILY | G NW APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 1 | 3 |
| 3 | OCCUP_OFFICE | OCC_OFF_W_SB_SCH | OFFICE | 88.25 | 4.7 | 4.7 | 5.382E-002 | 18.581 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 5 |
| 4 | OCCUP_GNE | OCC_APT_SCH_STAY_HOME_FAMILY | G NE APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 1 | 3 |
| 5 | OCCUP_GN1 | OCC_APT_SCH_STAY_HOME_FAMILY | G N1 APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 1 | 3 |
| 6 | OCCUP_GN2 | OCC_APT_SCH_STAY_HOME_FAMILY | G N2 APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 1 | 3 |
| 7 | OCCUP_GS1 | OCC_APT_SCH_WORKING_FAMILY | G S1 APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 3 |
| 8 | OCCUP_GS2 | OCC_APT_SCH_WORKING_FAMILY | G S2 APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 3 |
| 9 | OCCUP_MSW | OCC_APT_SCH_WORKING_FAMILY | M SW APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 3 |
| 10 | OCCUP_MNW | OCC_APT_SCH_STAY_HOME_FAMILY | M NW APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 1 | 3 |
| 11 | OCCUP_MSE | OCC_APT_SCH_WORKING_FAMILY | M SE APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 3 |
| 12 | OCCUP_MNE | OCC_APT_SCH_STAY_HOME_FAMILY | M NE APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 1 | 3 |
| 13 | OCCUP_MN1 | OCC_APT_SCH_STAY_HOME_FAMILY | M N1 APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 1 | 3 |
| 14 | OCCUP_MN2 | OCC_APT_SCH_STAY_HOME_FAMILY | M N2 APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 1 | 3 |
| 15 | OCCUP_MS1 | OCC_APT_SCH_WORKING_FAMILY | M S1 APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 3 |
| 16 | OCCUP_MS2 | OCC_APT_SCH_WORKING_FAMILY | M S2 APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 3 |
| 17 | OCCUP_TSW | OCC_APT_SCH_WORKING_FAMILY | T SW APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 3 |
| 18 | OCCUP_TNW | OCC_APT_SCH_STAY_HOME_FAMILY | T NW APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 1 | 3 |
| 19 | OCCUP_TSE | OCC_APT_SCH_WORKING_FAMILY | T SE APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 3 |
| 20 | OCCUP_TNE | OCC_APT_SCH_STAY_HOME_FAMILY | T NE APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 1 | 3 |
| 21 | OCCUP_TN1 | OCC_APT_SCH_STAY_HOME_FAMILY | T N1 APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 1 | 3 |
| 22 | OCCUP_TN2 | OCC_APT_SCH_STAY_HOME_FAMILY | T N2 APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 1 | 3 |
| 23 | OCCUP_TS1 | OCC_APT_SCH_WORKING_FAMILY | T S1 APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 3 |
| 24 | OCCUP_TS2 | OCC_APT_SCH_WORKING_FAMILY | T S2 APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 3 |
| 25 | OCCUP_T CORRIDOR | OCC_APT_SCH_CORRIDOR | T CORRIDOR | 77.66 | 4.2 | 4.2 | 5.382E-002 | 18.579 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 1 | 4 |
| 26 | OCCUP_G CORRIDOR | OCC_APT_SCH_CORRIDOR | G CORRIDOR | 77.66 | 4.2 | 4.2 | 5.382E-002 | 18.579 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 1 | 4 |
| 27 | OCCUP_M CORRIDOR | OCC_APT_SCH_CORRIDOR | M CORRIDOR | 77.66 | 4.2 | 4.2 | 5.382E-002 | 18.579 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 1 | 4 |
| Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
| 1 | LIGHTING_HARDWIRED_GSW | LTG_SCH_APARTMENT_HARDWIRED | G SW APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 2 | LIGHTING_HARDWIRED_GNW | LTG_SCH_APARTMENT_HARDWIRED | G NW APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 3 | LIGHTING_HARDWIRED_OFFICE | LTG_SCH_OFFICE | OFFICE | 88.25 | 4.7 | 860.710 | 9.753 | 181.220 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 860.710 |
| 4 | LIGHTING_HARDWIRED_GNE | LTG_SCH_APARTMENT_HARDWIRED | G NE APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 5 | LIGHTING_HARDWIRED_GN1 | LTG_SCH_APARTMENT_HARDWIRED | G N1 APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 6 | LIGHTING_HARDWIRED_GN2 | LTG_SCH_APARTMENT_HARDWIRED | G N2 APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 7 | LIGHTING_HARDWIRED_GS1 | LTG_SCH_APARTMENT_HARDWIRED | G S1 APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 8 | LIGHTING_HARDWIRED_GS2 | LTG_SCH_APARTMENT_HARDWIRED | G S2 APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 9 | LIGHTING_HARDWIRED_MSW | LTG_SCH_APARTMENT_HARDWIRED | M SW APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 10 | LIGHTING_HARDWIRED_MNW | LTG_SCH_APARTMENT_HARDWIRED | M NW APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 11 | LIGHTING_HARDWIRED_MSE | LTG_SCH_APARTMENT_HARDWIRED | M SE APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 12 | LIGHTING_HARDWIRED_MNE | LTG_SCH_APARTMENT_HARDWIRED | M NE APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 13 | LIGHTING_HARDWIRED_MN1 | LTG_SCH_APARTMENT_HARDWIRED | M N1 APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 14 | LIGHTING_HARDWIRED_MN2 | LTG_SCH_APARTMENT_HARDWIRED | M N2 APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 15 | LIGHTING_HARDWIRED_MS1 | LTG_SCH_APARTMENT_HARDWIRED | M S1 APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 16 | LIGHTING_HARDWIRED_MS2 | LTG_SCH_APARTMENT_HARDWIRED | M S2 APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 17 | LIGHTING_HARDWIRED_TSW | LTG_SCH_APARTMENT_HARDWIRED | T SW APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 18 | LIGHTING_HARDWIRED_TNW | LTG_SCH_APARTMENT_HARDWIRED | T NW APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 19 | LIGHTING_HARDWIRED_TSE | LTG_SCH_APARTMENT_HARDWIRED | T SE APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 20 | LIGHTING_HARDWIRED_TNE | LTG_SCH_APARTMENT_HARDWIRED | T NE APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 21 | LIGHTING_HARDWIRED_TN1 | LTG_SCH_APARTMENT_HARDWIRED | T N1 APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 22 | LIGHTING_HARDWIRED_TN2 | LTG_SCH_APARTMENT_HARDWIRED | T N2 APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 23 | LIGHTING_HARDWIRED_TS1 | LTG_SCH_APARTMENT_HARDWIRED | T S1 APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 24 | LIGHTING_HARDWIRED_TS2 | LTG_SCH_APARTMENT_HARDWIRED | T S2 APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 25 | LIGHTING_HARDWIRED_GC | LTG_SCH_CORRIDOR | G CORRIDOR | 77.66 | 4.2 | 370.628 | 4.772 | 88.667 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 370.628 |
| 26 | LIGHTING_HARDWIRED_MC | LTG_SCH_CORRIDOR | M CORRIDOR | 77.66 | 4.2 | 370.628 | 4.772 | 88.667 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 370.628 |
| 27 | LIGHTING_HARDWIRED_TC | LTG_SCH_CORRIDOR | T CORRIDOR | 77.66 | 4.2 | 370.628 | 4.772 | 88.667 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 370.628 |
| 28 | LIGHTING_PLUGIN_GSW | LTG_SCH_APARTMENT_PLUGIN | G SW APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| 29 | LIGHTING_PLUGIN_GNW | LTG_SCH_APARTMENT_PLUGIN | G NW APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| 30 | LIGHTING_PLUGIN_GNE | LTG_SCH_APARTMENT_PLUGIN | G NE APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| 31 | LIGHTING_PLUGIN_GN1 | LTG_SCH_APARTMENT_PLUGIN | G N1 APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| 32 | LIGHTING_PLUGIN_GN2 | LTG_SCH_APARTMENT_PLUGIN | G N2 APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| 33 | LIGHTING_PLUGIN_GS1 | LTG_SCH_APARTMENT_PLUGIN | G S1 APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| 34 | LIGHTING_PLUGIN_GS2 | LTG_SCH_APARTMENT_PLUGIN | G S2 APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| 35 | LIGHTING_PLUGIN_MSW | LTG_SCH_APARTMENT_PLUGIN | M SW APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| 36 | LIGHTING_PLUGIN_MNW | LTG_SCH_APARTMENT_PLUGIN | M NW APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| 37 | LIGHTING_PLUGIN_MSE | LTG_SCH_APARTMENT_PLUGIN | M SE APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| 38 | LIGHTING_PLUGIN_MNE | LTG_SCH_APARTMENT_PLUGIN | M NE APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| 39 | LIGHTING_PLUGIN_MN1 | LTG_SCH_APARTMENT_PLUGIN | M N1 APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| 40 | LIGHTING_PLUGIN_MN2 | LTG_SCH_APARTMENT_PLUGIN | M N2 APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| 41 | LIGHTING_PLUGIN_MS1 | LTG_SCH_APARTMENT_PLUGIN | M S1 APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| 42 | LIGHTING_PLUGIN_MS2 | LTG_SCH_APARTMENT_PLUGIN | M S2 APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| 43 | LIGHTING_PLUGIN_TSW | LTG_SCH_APARTMENT_PLUGIN | T SW APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| 44 | LIGHTING_PLUGIN_TNW | LTG_SCH_APARTMENT_PLUGIN | T NW APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| 45 | LIGHTING_PLUGIN_TSE | LTG_SCH_APARTMENT_PLUGIN | T SE APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| 46 | LIGHTING_PLUGIN_TNE | LTG_SCH_APARTMENT_PLUGIN | T NE APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| 47 | LIGHTING_PLUGIN_TN1 | LTG_SCH_APARTMENT_PLUGIN | T N1 APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| 48 | LIGHTING_PLUGIN_TN2 | LTG_SCH_APARTMENT_PLUGIN | T N2 APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| 49 | LIGHTING_PLUGIN_TS1 | LTG_SCH_APARTMENT_PLUGIN | T S1 APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| 50 | LIGHTING_PLUGIN_TS2 | LTG_SCH_APARTMENT_PLUGIN | T S2 APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
| 1 | PLUG_GSW | EQP_APT_SCH | G SW APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 2 | PLUG_GNW | EQP_APT_SCH | G NW APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 3 | PLUG_OFFICE | EQP_OFF_SCH | OFFICE | 88.25 | 4.7 | 588.623 | 6.670 | 123.933 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 588.623 |
| 4 | PLUG_GNE | EQP_APT_SCH | G NE APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 5 | PLUG_GN1 | EQP_APT_SCH | G N1 APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 6 | PLUG_GN2 | EQP_APT_SCH | G N2 APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 7 | PLUG_GS1 | EQP_APT_SCH | G S1 APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 8 | PLUG_GS2 | EQP_APT_SCH | G S2 APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 9 | PLUG_MSW | EQP_APT_SCH | M SW APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 10 | PLUG_MNW | EQP_APT_SCH | M NW APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 11 | PLUG_MSE | EQP_APT_SCH | M SE APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 12 | PLUG_MNE | EQP_APT_SCH | M NE APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 13 | PLUG_MN1 | EQP_APT_SCH | M N1 APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 14 | PLUG_MN2 | EQP_APT_SCH | M N2 APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 15 | PLUG_MS1 | EQP_APT_SCH | M S1 APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 16 | PLUG_MS2 | EQP_APT_SCH | M S2 APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 17 | PLUG_TSW | EQP_APT_SCH | T SW APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 18 | PLUG_TNW | EQP_APT_SCH | T NW APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 19 | PLUG_TSE | EQP_APT_SCH | T SE APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 20 | PLUG_TNE | EQP_APT_SCH | T NE APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 21 | PLUG_TN1 | EQP_APT_SCH | T N1 APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 22 | PLUG_TN2 | EQP_APT_SCH | T N2 APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 23 | PLUG_TS1 | EQP_APT_SCH | T S1 APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 24 | PLUG_TS2 | EQP_APT_SCH | T S2 APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 25 | G CORRIDOR_ELEVATORS_EQUIP | BLDG_ELEVATORS | G CORRIDOR | 77.66 | 4.2 | 8012.150 | 103.170 | 1916.782 | 0.000 | 0.000 | 0.950 | 5.000E-002 | ElevatorLift | 961.458 | 4006.075 |
| 26 | ELEVATORS_LIGHTS_FAN | ELEV_LIGHT_FAN_SCH_24_7 | G CORRIDOR | 77.66 | 4.2 | 162.000 | 2.086 | 38.756 | 0.000 | 0.000 | 0.950 | 5.000E-002 | ElevatorLightsFan | 162.000 | 162.000 |
| Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
| 1 | PolygonClipping | Periodic | 20 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
| Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
| 1 | WaterHeater:Mixed | G SW APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.496 | 0.7729 |
| 2 | WaterHeater:Mixed | G NW APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.496 | 0.7729 |
| 3 | WaterHeater:Mixed | G NE APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.496 | 0.7729 |
| 4 | WaterHeater:Mixed | G N1 APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.496 | 0.7729 |
| 5 | WaterHeater:Mixed | G N2 APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.496 | 0.7729 |
| 6 | WaterHeater:Mixed | G S1 APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.496 | 0.7729 |
| 7 | WaterHeater:Mixed | G S2 APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.496 | 0.7729 |
| 8 | WaterHeater:Mixed | M SW APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.498 | 0.7911 |
| 9 | WaterHeater:Mixed | M NW APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.498 | 0.7911 |
| 10 | WaterHeater:Mixed | M SE APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.498 | 0.7911 |
| 11 | WaterHeater:Mixed | M NE APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.498 | 0.7911 |
| 12 | WaterHeater:Mixed | M N1 APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.498 | 0.7911 |
| 13 | WaterHeater:Mixed | M N2 APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.498 | 0.7911 |
| 14 | WaterHeater:Mixed | M S1 APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.498 | 0.7911 |
| 15 | WaterHeater:Mixed | M S2 APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.498 | 0.7911 |
| 16 | WaterHeater:Mixed | T SW APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.496 | 0.7729 |
| 17 | WaterHeater:Mixed | T NW APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.496 | 0.7729 |
| 18 | WaterHeater:Mixed | T SE APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.496 | 0.7729 |
| 19 | WaterHeater:Mixed | T NE APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.496 | 0.7729 |
| 20 | WaterHeater:Mixed | T N1 APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.496 | 0.7729 |
| 21 | WaterHeater:Mixed | T N2 APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.496 | 0.7729 |
| 22 | WaterHeater:Mixed | T S1 APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.496 | 0.7729 |
| 23 | WaterHeater:Mixed | T S2 APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.496 | 0.7729 |
| Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
| 1 | G SWALL SWA | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 2 | GWINDOW1 S SWA | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 3 | G WWALL SWA | 0 | 154.67 | 58.21 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 4 | GWINDOW1 W SWA | 0 | 154.67 | 58.21 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 5 | G NIWALL SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 6 | G EIWALL SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 7 | G GFLOOR SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 8 | G CEILIN SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 9 | G INTERNALMASS SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 10 | G NWALL NWA | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 11 | GWINDOW1 N NWA | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 12 | G WWALL NWA | 0 | 154.67 | 58.21 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 13 | GWINDOW1 W NWA | 0 | 154.67 | 58.21 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 14 | G SIWALL NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 15 | G EIWALL NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 16 | G GFLOOR NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 17 | G CEILIN NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 18 | G INTERNALMASS NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 19 | G SWALL SEA | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 20 | GWINDOW1 S SEA | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 21 | G EWALL SEA | 0 | 154.67 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 22 | GWINDOW1 E SEA | 0 | 154.67 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 23 | G NIWALL SEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 24 | iz-G EIWALL S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 25 | G GFLOOR SEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 26 | G CEILIN SEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 27 | G INTERNALMASS SEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 28 | G NWALL NEA | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 29 | GWINDOW1 N NEA | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 30 | G EWALL NEA | 0 | 154.67 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 31 | GWINDOW1 E NEA | 0 | 154.67 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 32 | G SIWALL NEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 33 | iz-G EIWALL N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 34 | G GFLOOR NEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 35 | G CEILIN NEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 36 | G INTERNALMASS NEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 37 | G NWALL N1A | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 3 | No | No |
| 38 | GWINDOW1 N N1A | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 2 | No | No |
| 39 | G SIWALL N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 40 | G EIWALL N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 41 | iz-G EIWALL NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 42 | G GFLOOR N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 43 | G CEILIN N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 44 | G INTERNALMASS N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 45 | G NWALL N2A | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 3 | No | No |
| 46 | GWINDOW1 N N2A | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 2 | No | No |
| 47 | G SIWALL N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 48 | G EIWALL N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 49 | iz-G EIWALL N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 50 | G GFLOOR N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 51 | G CEILIN N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 52 | G INTERNALMASS N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 53 | G SWALL S1A | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 3 | No | No |
| 54 | GWINDOW1 S S1A | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 2 | No | No |
| 55 | G NIWALL S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 56 | G EIWALL S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 57 | iz-G EIWALL SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 58 | G GFLOOR S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 59 | G CEILIN S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 60 | G INTERNALMASS S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 61 | G SWALL S2A | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 3 | No | No |
| 62 | GWINDOW1 S S2A | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 2 | No | No |
| 63 | G NIWALL S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 64 | G EIWALL S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 65 | iz-G EIWALL S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 66 | G GFLOOR S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 67 | G CEILIN S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 68 | G INTERNALMASS S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 69 | M WWALL SWA | 0 | 154.67 | 58.21 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 70 | MWINDOW1 W SWA | 0 | 154.67 | 58.21 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 71 | M SWALL SWA | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 72 | MWINDOW1 S SWA | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 73 | M NIWALL SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 74 | M EIWALL SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 75 | M GFLOOR SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 76 | M CEILIN SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 77 | M INTERNALMASS SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 78 | M NWALL NWA | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 79 | MWINDOW1 N NWA | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 80 | M WWALL NWA | 0 | 154.67 | 58.21 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 81 | MWINDOW1 W NWA | 0 | 154.67 | 58.21 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 82 | M SIWALL NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 83 | M EIWALL NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 84 | M GFLOOR NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 85 | M CEILIN NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 86 | M INTERNALMASS NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 87 | M EWALL SEA | 0 | 154.67 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 88 | MWINDOW1 E SEA | 0 | 154.67 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 89 | M SWALL SEA | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 90 | MWINDOW1 S SEA | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 91 | M NIWALL SEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 92 | iz-M EIWALL S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 93 | M GFLOOR SEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 94 | M CEILIN SEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 95 | M INTERNALMASS SEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 96 | M NWALL NEA | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 97 | MWINDOW1 N NEA | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 98 | M EWALL NEA | 0 | 154.67 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 99 | MWINDOW1 E NEA | 0 | 154.67 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 100 | M SIWALL NEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 101 | iz-M EIWALL N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 102 | M GFLOOR NEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 103 | M CEILIN NEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 104 | M INTERNALMASS NEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 105 | M NWALL N1A | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 3 | No | No |
| 106 | MWINDOW1 N N1A | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 2 | No | No |
| 107 | M SIWALL N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 108 | M EIWALL N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 109 | iz-M EIWALL NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 110 | M GFLOOR N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 111 | M CEILIN N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 112 | M INTERNALMASS N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 113 | M NWALL N2A | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 3 | No | No |
| 114 | MWINDOW1 N N2A | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 2 | No | No |
| 115 | M SIWALL N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 116 | M EIWALL N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 117 | iz-M EIWALL N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 118 | M GFLOOR N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 119 | M CEILIN N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 120 | M INTERNALMASS N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 121 | M SWALL S1A | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 3 | No | No |
| 122 | MWINDOW1 S S1A | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 2 | No | No |
| 123 | M NIWALL S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 124 | M EIWALL S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 125 | iz-M EIWALL SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 126 | M GFLOOR S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 127 | M CEILIN S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 128 | M INTERNALMASS S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 129 | M SWALL S2A | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 3 | No | No |
| 130 | MWINDOW1 S S2A | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 2 | No | No |
| 131 | M NIWALL S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 132 | M EIWALL S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 133 | iz-M EIWALL S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 134 | M GFLOOR S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 135 | M CEILIN S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 136 | M INTERNALMASS S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 137 | T WWALL SWA | 0 | 154.67 | 58.21 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 138 | TWINDOW1 W SWA | 0 | 154.67 | 58.21 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 139 | T SWALL SWA | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 140 | TWINDOW1 S SWA | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 141 | T NIWALL SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 142 | T EIWALL SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 143 | T GFLOOR SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 144 | T ROOF SWA | 0 | 783.65 | 155.90 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 145 | T INTERNALMASS SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 146 | T NWALL NWA | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 147 | TWINDOW1 N NWA | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 148 | T WWALL NWA | 0 | 154.67 | 58.21 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 149 | TWINDOW1 W NWA | 0 | 154.67 | 58.21 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 150 | T SIWALL NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 151 | T EIWALL NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 152 | T GFLOOR NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 153 | T ROOF NWA | 0 | 783.65 | 155.90 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 154 | T INTERNALMASS NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 155 | T EWALL SEA | 0 | 154.67 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 156 | TWINDOW1 E SEA | 0 | 154.67 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 157 | T SWALL SEA | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 158 | TWINDOW1 S SEA | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 159 | T NIWALL SEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 160 | iz-T EIWALL S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 161 | T GFLOOR SEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 162 | T ROOF SEA | 0 | 783.65 | 155.90 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 163 | T INTERNALMASS SEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 164 | T NWALL NEA | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 165 | TWINDOW1 N NEA | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 166 | T EWALL NEA | 0 | 154.67 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 167 | TWINDOW1 E NEA | 0 | 154.67 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 168 | T SIWALL NEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 169 | iz-T EIWALL N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 170 | T GFLOOR NEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 171 | T ROOF NEA | 0 | 783.65 | 155.90 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 172 | T INTERNALMASS NEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 173 | T NWALL N1A | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 3 | No | No |
| 174 | TWINDOW1 N N1A | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 2 | No | No |
| 175 | T SIWALL N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 176 | T EIWALL N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 177 | iz-T EIWALL NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 178 | T GFLOOR N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 179 | T ROOF N1A | 0 | 783.65 | 155.90 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 180 | T INTERNALMASS N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 181 | T NWALL N2A | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 3 | No | No |
| 182 | TWINDOW1 N N2A | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 2 | No | No |
| 183 | T SIWALL N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 184 | T EIWALL N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 185 | iz-T EIWALL N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 186 | T GFLOOR N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 187 | T ROOF N2A | 0 | 783.65 | 155.90 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 188 | T INTERNALMASS N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 189 | T SWALL S1A | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 3 | No | No |
| 190 | TWINDOW1 S S1A | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 2 | No | No |
| 191 | T NIWALL S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 192 | T EIWALL S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 193 | iz-T EIWALL SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 194 | T GFLOOR S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 195 | T ROOF S1A | 0 | 783.65 | 155.90 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 196 | T INTERNALMASS S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 197 | T SWALL S2A | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 3 | No | No |
| 198 | TWINDOW1 S S2A | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 2 | No | No |
| 199 | T NIWALL S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 200 | T EIWALL S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 201 | iz-T EIWALL S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 202 | T GFLOOR S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 203 | T ROOF S2A | 0 | 783.65 | 155.90 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 204 | T INTERNALMASS S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 205 | T WWALL C | 0 | 154.67 | 58.21 | 12.19 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 3 | No | No |
| 206 | T EWALL C | 0 | 154.67 | 123.02 | 12.19 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 3 | No | No |
| 207 | TWINDOW14 | 0 | 154.67 | 123.02 | 12.19 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 2 | No | No |
| 208 | iz-T NIWALL SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 209 | iz-T NIWALL S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 210 | iz-T NIWALL S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 211 | iz-T NIWALL SEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 212 | iz-T SIWALL NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 213 | iz-T SIWALL N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 214 | iz-T SIWALL N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 215 | iz-T SIWALL NEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 216 | T FLOOR C | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 217 | T ROOF C | 0 | 783.65 | 155.90 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 218 | G WWALL C | 0 | 154.67 | 58.21 | 12.19 | 0 | 3.05 | 3.35 | 3.24 | 0.32 | 4 | No | No |
| 219 | G EWALL C | 0 | 154.67 | 123.02 | 12.19 | 0 | 3.05 | 3.35 | 3.24 | 0.32 | 4 | No | No |
| 220 | ENTRANCE DOOR | 0 | 154.67 | 123.02 | 12.19 | 0 | 3.05 | 3.35 | 3.24 | 0.32 | 1 | No | No |
| 221 | iz-G NIWALL SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.32 | 0 | No | No |
| 222 | iz-G NIWALL S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.32 | 0 | No | No |
| 223 | iz-G NIWALL S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.32 | 0 | No | No |
| 224 | iz-G NIWALL SEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.32 | 0 | No | No |
| 225 | iz-G SIWALL NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.32 | 0 | No | No |
| 226 | iz-G SIWALL N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.32 | 0 | No | No |
| 227 | iz-G SIWALL N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.32 | 0 | No | No |
| 228 | iz-G SIWALL NEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.32 | 0 | No | No |
| 229 | G FLOOR C | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.32 | 0 | No | No |
| 230 | G CEILING C | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.32 | 0 | No | No |
| 231 | M WWALL C | 0 | 154.67 | 58.21 | 12.19 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 4 | No | No |
| 232 | M EWALL C | 0 | 154.67 | 123.02 | 12.19 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 3 | No | No |
| 233 | MWINDOW14 | 0 | 154.67 | 123.02 | 12.19 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 2 | No | No |
| 234 | iz-M NIWALL SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 235 | iz-M NIWALL S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 236 | iz-M NIWALL S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 237 | iz-M NIWALL SEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 238 | iz-M SIWALL NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 239 | iz-M SIWALL N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 240 | iz-M SIWALL N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 241 | iz-M SIWALL NEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 242 | M FLOOR C | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 243 | M CEILING C | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
| 1 | INFIL_GSW | INF_APT_SCH | G SW APARTMENT | 88.25 | 2.5 | 3.333E-002 | 3.777E-004 | 5.696E-004 | 0.446 | 0.000 | 0.000 | 0.224 | 0.000 |
| 2 | INFIL_GNW | INF_APT_SCH | G NW APARTMENT | 88.25 | 2.5 | 3.333E-002 | 3.777E-004 | 5.696E-004 | 0.446 | 0.000 | 0.000 | 0.224 | 0.000 |
| 3 | INFIL_OFFICE | INF_OFF_SCH | OFFICE | 88.25 | 4.7 | 3.333E-002 | 3.777E-004 | 5.696E-004 | 0.446 | 0.000 | 0.000 | 0.224 | 0.000 |
| 4 | INFIL_GNE | INF_APT_SCH | G NE APARTMENT | 88.25 | 2.5 | 3.333E-002 | 3.777E-004 | 5.696E-004 | 0.446 | 0.000 | 0.000 | 0.224 | 0.000 |
| 5 | INFIL_GN1 | INF_APT_SCH | G N1 APARTMENT | 88.25 | 2.5 | 2.011E-002 | 2.278E-004 | 5.696E-004 | 0.269 | 0.000 | 0.000 | 0.224 | 0.000 |
| 6 | INFIL_GN2 | INF_APT_SCH | G N2 APARTMENT | 88.25 | 2.5 | 2.011E-002 | 2.278E-004 | 5.696E-004 | 0.269 | 0.000 | 0.000 | 0.224 | 0.000 |
| 7 | INFIL_GS1 | INF_APT_SCH | G S1 APARTMENT | 88.25 | 2.5 | 2.011E-002 | 2.278E-004 | 5.696E-004 | 0.269 | 0.000 | 0.000 | 0.224 | 0.000 |
| 8 | INFIL_GS2 | INF_APT_SCH | G S2 APARTMENT | 88.25 | 2.5 | 2.011E-002 | 2.278E-004 | 5.696E-004 | 0.269 | 0.000 | 0.000 | 0.224 | 0.000 |
| 9 | INFIL_MSW | INF_APT_SCH | M SW APARTMENT | 88.25 | 2.5 | 3.333E-002 | 3.777E-004 | 5.696E-004 | 0.446 | 0.000 | 0.000 | 0.224 | 0.000 |
| 10 | INFIL_MNW | INF_APT_SCH | M NW APARTMENT | 88.25 | 2.5 | 3.333E-002 | 3.777E-004 | 5.696E-004 | 0.446 | 0.000 | 0.000 | 0.224 | 0.000 |
| 11 | INFIL_MSE | INF_APT_SCH | M SE APARTMENT | 88.25 | 2.5 | 3.333E-002 | 3.777E-004 | 5.696E-004 | 0.446 | 0.000 | 0.000 | 0.224 | 0.000 |
| 12 | INFIL_MNE | INF_APT_SCH | M NE APARTMENT | 88.25 | 2.5 | 3.333E-002 | 3.777E-004 | 5.696E-004 | 0.446 | 0.000 | 0.000 | 0.224 | 0.000 |
| 13 | INFIL_MN1 | INF_APT_SCH | M N1 APARTMENT | 88.25 | 2.5 | 2.011E-002 | 2.278E-004 | 5.696E-004 | 0.269 | 0.000 | 0.000 | 0.224 | 0.000 |
| 14 | INFIL_MN2 | INF_APT_SCH | M N2 APARTMENT | 88.25 | 2.5 | 2.011E-002 | 2.278E-004 | 5.696E-004 | 0.269 | 0.000 | 0.000 | 0.224 | 0.000 |
| 15 | INFIL_MS1 | INF_APT_SCH | M S1 APARTMENT | 88.25 | 2.5 | 2.011E-002 | 2.278E-004 | 5.696E-004 | 0.269 | 0.000 | 0.000 | 0.224 | 0.000 |
| 16 | INFIL_MS2 | INF_APT_SCH | M S2 APARTMENT | 88.25 | 2.5 | 2.011E-002 | 2.278E-004 | 5.696E-004 | 0.269 | 0.000 | 0.000 | 0.224 | 0.000 |
| 17 | INFIL_SW | INF_APT_SCH | T SW APARTMENT | 88.25 | 2.5 | 3.333E-002 | 3.777E-004 | 2.271E-004 | 0.446 | 0.000 | 0.000 | 0.224 | 0.000 |
| 18 | INFIL_NW | INF_APT_SCH | T NW APARTMENT | 88.25 | 2.5 | 3.333E-002 | 3.777E-004 | 2.271E-004 | 0.446 | 0.000 | 0.000 | 0.224 | 0.000 |
| 19 | INFIL_SE | INF_APT_SCH | T SE APARTMENT | 88.25 | 2.5 | 3.333E-002 | 3.777E-004 | 2.271E-004 | 0.446 | 0.000 | 0.000 | 0.224 | 0.000 |
| 20 | INFIL_NE | INF_APT_SCH | T NE APARTMENT | 88.25 | 2.5 | 3.333E-002 | 3.777E-004 | 2.271E-004 | 0.446 | 0.000 | 0.000 | 0.224 | 0.000 |
| 21 | INFIL_TN1 | INF_APT_SCH | T N1 APARTMENT | 88.25 | 2.5 | 2.011E-002 | 2.278E-004 | 1.627E-004 | 0.269 | 0.000 | 0.000 | 0.224 | 0.000 |
| 22 | INFIL_TN2 | INF_APT_SCH | T N2 APARTMENT | 88.25 | 2.5 | 2.011E-002 | 2.278E-004 | 1.627E-004 | 0.269 | 0.000 | 0.000 | 0.224 | 0.000 |
| 23 | INFIL_TS1 | INF_APT_SCH | T S1 APARTMENT | 88.25 | 2.5 | 2.011E-002 | 2.278E-004 | 1.627E-004 | 0.269 | 0.000 | 0.000 | 0.224 | 0.000 |
| 24 | INFIL_TS2 | INF_APT_SCH | T S2 APARTMENT | 88.25 | 2.5 | 2.011E-002 | 2.278E-004 | 1.627E-004 | 0.269 | 0.000 | 0.000 | 0.224 | 0.000 |
| 25 | INFIL_GC | INF_COR_SCH | G CORRIDOR | 77.66 | 4.2 | 5.820E-003 | 7.494E-005 | 5.696E-004 | 8.852E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
| 26 | DOOR_INFIL_GC | INFIL_DOOR_OPENING_SCH | G CORRIDOR | 77.66 | 4.2 | 0.521 | 6.703E-003 | 5.094E-002 | 7.917 | 1.000 | 0.000 | 0.000 | 0.000 |
| 27 | INFIL_MC | INF_COR_SCH | M CORRIDOR | 77.66 | 4.2 | 5.820E-003 | 7.494E-005 | 5.696E-004 | 8.852E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
| 28 | INFIL_TC | INF_COR_SCH | T CORRIDOR | 77.66 | 4.2 | 5.820E-003 | 7.494E-005 | 6.623E-005 | 8.852E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
| Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
| 1 | G SW APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | G SW APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 2 | G NW APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | G NW APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 3 | G NE APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | G NE APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 4 | G N1 APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | G N1 APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 5 | G N2 APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | G N2 APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 6 | G S1 APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | G S1 APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 7 | G S2 APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | G S2 APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 8 | M SW APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | M SW APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 9 | M NW APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | M NW APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 10 | M SE APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | M SE APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 11 | M NE APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | M NE APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 12 | M N1 APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | M N1 APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 13 | M N2 APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | M N2 APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 14 | M S1 APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | M S1 APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 15 | M S2 APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | M S2 APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 16 | T SW APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | T SW APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 17 | T NW APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | T NW APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 18 | T SE APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | T SE APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 19 | T NE APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | T NE APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 20 | T N1 APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | T N1 APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 21 | T N2 APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | T N2 APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 22 | T S1 APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | T S1 APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 23 | T S2 APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | T S2 APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| Simple | |
| 1 | Simple |
| Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
| 1 | G SW APARTMENT | Mixing/Well-Stirred |
| 2 | G NW APARTMENT | Mixing/Well-Stirred |
| 3 | OFFICE | Mixing/Well-Stirred |
| 4 | G NE APARTMENT | Mixing/Well-Stirred |
| 5 | G N1 APARTMENT | Mixing/Well-Stirred |
| 6 | G N2 APARTMENT | Mixing/Well-Stirred |
| 7 | G S1 APARTMENT | Mixing/Well-Stirred |
| 8 | G S2 APARTMENT | Mixing/Well-Stirred |
| 9 | M SW APARTMENT | Mixing/Well-Stirred |
| 10 | M NW APARTMENT | Mixing/Well-Stirred |
| 11 | M SE APARTMENT | Mixing/Well-Stirred |
| 12 | M NE APARTMENT | Mixing/Well-Stirred |
| 13 | M N1 APARTMENT | Mixing/Well-Stirred |
| 14 | M N2 APARTMENT | Mixing/Well-Stirred |
| 15 | M S1 APARTMENT | Mixing/Well-Stirred |
| 16 | M S2 APARTMENT | Mixing/Well-Stirred |
| 17 | T SW APARTMENT | Mixing/Well-Stirred |
| 18 | T NW APARTMENT | Mixing/Well-Stirred |
| 19 | T SE APARTMENT | Mixing/Well-Stirred |
| 20 | T NE APARTMENT | Mixing/Well-Stirred |
| 21 | T N1 APARTMENT | Mixing/Well-Stirred |
| 22 | T N2 APARTMENT | Mixing/Well-Stirred |
| 23 | T S1 APARTMENT | Mixing/Well-Stirred |
| 24 | T S2 APARTMENT | Mixing/Well-Stirred |
| 25 | T CORRIDOR | Mixing/Well-Stirred |
| 26 | G CORRIDOR | Mixing/Well-Stirred |
| 27 | M CORRIDOR | Mixing/Well-Stirred |
| No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
| 1 | NoMultizoneOrDistribution |
| Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
| 1 | 1.000 | 1.000 | 1.000 | 1.000 |
| Value | |
| 1 | 6 |
| Sizing Factor ID | Value | |
| 1 | Global | 1.2000 |
| 2 | Zone G SW APARTMENT | 1.2000 |
| 3 | Zone G NW APARTMENT | 1.2000 |
| 4 | Zone OFFICE | 1.2000 |
| 5 | Zone G NE APARTMENT | 1.2000 |
| 6 | Zone G N1 APARTMENT | 1.2000 |
| 7 | Zone G N2 APARTMENT | 1.2000 |
| 8 | Zone G S1 APARTMENT | 1.2000 |
| 9 | Zone G S2 APARTMENT | 1.2000 |
| 10 | Zone M SW APARTMENT | 1.2000 |
| 11 | Zone M NW APARTMENT | 1.2000 |
| 12 | Zone M SE APARTMENT | 1.2000 |
| 13 | Zone M NE APARTMENT | 1.2000 |
| 14 | Zone M N1 APARTMENT | 1.2000 |
| 15 | Zone M N2 APARTMENT | 1.2000 |
| 16 | Zone M S1 APARTMENT | 1.2000 |
| 17 | Zone M S2 APARTMENT | 1.2000 |
| 18 | Zone T SW APARTMENT | 1.2000 |
| 19 | Zone T NW APARTMENT | 1.2000 |
| 20 | Zone T SE APARTMENT | 1.2000 |
| 21 | Zone T NE APARTMENT | 1.2000 |
| 22 | Zone T N1 APARTMENT | 1.2000 |
| 23 | Zone T N2 APARTMENT | 1.2000 |
| 24 | Zone T S1 APARTMENT | 1.2000 |
| 25 | Zone T S2 APARTMENT | 1.2000 |
| Sizing Factor ID | Value | |
| 1 | Global | 1.2000 |
| 2 | Zone G SW APARTMENT | 1.2000 |
| 3 | Zone G NW APARTMENT | 1.2000 |
| 4 | Zone OFFICE | 1.2000 |
| 5 | Zone G NE APARTMENT | 1.2000 |
| 6 | Zone G N1 APARTMENT | 1.2000 |
| 7 | Zone G N2 APARTMENT | 1.2000 |
| 8 | Zone G S1 APARTMENT | 1.2000 |
| 9 | Zone G S2 APARTMENT | 1.2000 |
| 10 | Zone M SW APARTMENT | 1.2000 |
| 11 | Zone M NW APARTMENT | 1.2000 |
| 12 | Zone M SE APARTMENT | 1.2000 |
| 13 | Zone M NE APARTMENT | 1.2000 |
| 14 | Zone M N1 APARTMENT | 1.2000 |
| 15 | Zone M N2 APARTMENT | 1.2000 |
| 16 | Zone M S1 APARTMENT | 1.2000 |
| 17 | Zone M S2 APARTMENT | 1.2000 |
| 18 | Zone T SW APARTMENT | 1.2000 |
| 19 | Zone T NW APARTMENT | 1.2000 |
| 20 | Zone T SE APARTMENT | 1.2000 |
| 21 | Zone T NE APARTMENT | 1.2000 |
| 22 | Zone T N1 APARTMENT | 1.2000 |
| 23 | Zone T N2 APARTMENT | 1.2000 |
| 24 | Zone T S1 APARTMENT | 1.2000 |
| 25 | Zone T S2 APARTMENT | 1.2000 |
| Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
| 1 | G SW APARTMENT | Cooling | 4239.21282 | 5087.05539 | 0.30401 | 0.36481 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 25.34400 | 8.81502E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 2 | G SW APARTMENT | Heating | 1469.76003 | 1763.71204 | 6.42463E-002 | 7.70956E-002 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:50:00 | -4.20000 | 2.69032E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 3 | G NW APARTMENT | Cooling | 3572.31620 | 4286.77944 | 0.25511 | 0.30613 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 25.34400 | 8.81502E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 4 | G NW APARTMENT | Heating | 1355.35234 | 1626.42281 | 5.92459E-002 | 7.10950E-002 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | -4.20000 | 2.69032E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 5 | OFFICE | Cooling | 4608.75658 | 5530.50789 | 0.33532 | 0.40239 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | 23.68000 | 8.81240E-003 | 88.24927 | 4.74953 | 3.81060E-002 | 0.00000 |
| 6 | OFFICE | Heating | 1912.11908 | 2294.54290 | 8.35827E-002 | 0.10030 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 18:50:00 | -4.20000 | 2.69032E-003 | 88.24927 | 4.74953 | 3.81060E-002 | 0.00000 |
| 7 | G NE APARTMENT | Cooling | 3148.92540 | 3778.71047 | 0.22401 | 0.26881 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 25.34400 | 8.81502E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 8 | G NE APARTMENT | Heating | 1358.52295 | 1630.22754 | 5.93845E-002 | 7.12613E-002 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | -4.20000 | 2.69032E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 9 | G N1 APARTMENT | Cooling | 2879.66113 | 3455.59336 | 0.20433 | 0.24519 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 25.34400 | 8.81502E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 10 | G N1 APARTMENT | Heating | 779.52322 | 935.42787 | 3.40753E-002 | 4.08903E-002 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | -4.20000 | 2.69032E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 11 | G N2 APARTMENT | Cooling | 2871.84197 | 3446.21036 | 0.20375 | 0.24450 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 25.34400 | 8.81502E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 12 | G N2 APARTMENT | Heating | 779.62189 | 935.54627 | 3.40796E-002 | 4.08955E-002 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | -4.20000 | 2.69032E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 13 | G S1 APARTMENT | Cooling | 3599.32298 | 4319.18758 | 0.25708 | 0.30850 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 25.34400 | 8.81502E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 14 | G S1 APARTMENT | Heating | 895.18102 | 1074.21722 | 3.91306E-002 | 4.69568E-002 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:50:00 | -4.20000 | 2.69032E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 15 | G S2 APARTMENT | Cooling | 3616.96903 | 4340.36284 | 0.25838 | 0.31006 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 25.34400 | 8.81502E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 16 | G S2 APARTMENT | Heating | 903.83503 | 1084.60203 | 3.95089E-002 | 4.74107E-002 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:50:00 | -4.20000 | 2.69032E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 17 | M SW APARTMENT | Cooling | 10252.61784 | 12303.14141 | 0.73794 | 0.88553 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 25.34400 | 8.81502E-003 | 88.24927 | 2.50000 | 5.19091E-002 | 0.00000 |
| 18 | M SW APARTMENT | Heating | 2659.75407 | 3191.70488 | 0.11626 | 0.13951 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | -4.20000 | 2.69032E-003 | 88.24927 | 2.50000 | 5.19091E-002 | 0.00000 |
| 19 | M NW APARTMENT | Cooling | 8999.92932 | 10799.91518 | 0.64628 | 0.77553 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 25.34400 | 8.81502E-003 | 88.24927 | 2.50000 | 5.19091E-002 | 0.00000 |
| 20 | M NW APARTMENT | Heating | 2386.52124 | 2863.82549 | 0.10432 | 0.12518 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | -4.20000 | 2.69032E-003 | 88.24927 | 2.50000 | 5.19091E-002 | 0.00000 |
| 21 | M SE APARTMENT | Cooling | 8978.25732 | 10773.90879 | 0.64471 | 0.77365 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 25.34400 | 8.81502E-003 | 88.24927 | 2.50000 | 5.19091E-002 | 0.00000 |
| 22 | M SE APARTMENT | Heating | 2667.54853 | 3201.05824 | 0.11660 | 0.13992 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | -4.20000 | 2.69032E-003 | 88.24927 | 2.50000 | 5.19091E-002 | 0.00000 |
| 23 | M NE APARTMENT | Cooling | 7763.40618 | 9316.08741 | 0.55534 | 0.66641 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 25.34400 | 8.81502E-003 | 88.24927 | 2.50000 | 5.19091E-002 | 0.00000 |
| 24 | M NE APARTMENT | Heating | 2394.38745 | 2873.26494 | 0.10466 | 0.12559 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | -4.20000 | 2.69032E-003 | 88.24927 | 2.50000 | 5.19091E-002 | 0.00000 |
| 25 | M N1 APARTMENT | Cooling | 7038.78259 | 8446.53910 | 0.50250 | 0.60300 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 25.34400 | 8.81502E-003 | 88.24927 | 2.50000 | 5.19091E-002 | 0.00000 |
| 26 | M N1 APARTMENT | Heating | 1159.51232 | 1391.41479 | 5.06846E-002 | 6.08215E-002 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | -4.20000 | 2.69032E-003 | 88.24927 | 2.50000 | 5.19091E-002 | 0.00000 |
| 27 | M N2 APARTMENT | Cooling | 7017.17890 | 8420.61468 | 0.50091 | 0.60110 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 25.34400 | 8.81502E-003 | 88.24927 | 2.50000 | 5.19091E-002 | 0.00000 |
| 28 | M N2 APARTMENT | Heating | 1159.72907 | 1391.67488 | 5.06941E-002 | 6.08329E-002 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | -4.20000 | 2.69032E-003 | 88.24927 | 2.50000 | 5.19091E-002 | 0.00000 |
| 29 | M S1 APARTMENT | Cooling | 8405.95268 | 10087.14322 | 0.60267 | 0.72321 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 25.34400 | 8.81502E-003 | 88.24927 | 2.50000 | 5.19091E-002 | 0.00000 |
| 30 | M S1 APARTMENT | Heating | 1424.88872 | 1709.86647 | 6.22837E-002 | 7.47404E-002 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | -4.20000 | 2.69032E-003 | 88.24927 | 2.50000 | 5.19091E-002 | 0.00000 |
| 31 | M S2 APARTMENT | Cooling | 8381.49939 | 10057.79927 | 0.60087 | 0.72105 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 25.34400 | 8.81502E-003 | 88.24927 | 2.50000 | 5.19091E-002 | 0.00000 |
| 32 | M S2 APARTMENT | Heating | 1425.10146 | 1710.12176 | 6.22930E-002 | 7.47516E-002 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | -4.20000 | 2.69032E-003 | 88.24927 | 2.50000 | 5.19091E-002 | 0.00000 |
| 33 | T SW APARTMENT | Cooling | 5489.31409 | 6587.17691 | 0.39538 | 0.47445 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 25.34400 | 8.81502E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 34 | T SW APARTMENT | Heating | 2335.07936 | 2802.09523 | 0.10206 | 0.12248 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | -4.20000 | 2.69032E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 35 | T NW APARTMENT | Cooling | 4981.49517 | 5977.79420 | 0.35812 | 0.42975 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 25.34400 | 8.81502E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 36 | T NW APARTMENT | Heating | 2191.33295 | 2629.59954 | 9.57826E-002 | 0.11494 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | -4.20000 | 2.69032E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 37 | T SE APARTMENT | Cooling | 4568.23534 | 5481.88241 | 0.32793 | 0.39352 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 25.34400 | 8.81502E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 38 | T SE APARTMENT | Heating | 2340.88221 | 2809.05865 | 0.10232 | 0.12278 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | -4.20000 | 2.69032E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 39 | T NE APARTMENT | Cooling | 4066.04842 | 4879.25811 | 0.29116 | 0.34939 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 25.34400 | 8.81502E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 40 | T NE APARTMENT | Heating | 2197.21307 | 2636.65569 | 9.60396E-002 | 0.11525 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | -4.20000 | 2.69032E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 41 | T N1 APARTMENT | Cooling | 3877.36830 | 4652.84196 | 0.27730 | 0.33276 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 25.34400 | 8.81502E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 42 | T N1 APARTMENT | Heating | 1459.68574 | 1751.62289 | 6.38048E-002 | 7.65657E-002 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | -4.20000 | 2.69032E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 43 | T N2 APARTMENT | Cooling | 3847.87790 | 4617.45348 | 0.27513 | 0.33016 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 25.34400 | 8.81502E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 44 | T N2 APARTMENT | Heating | 1459.86151 | 1751.83381 | 6.38125E-002 | 7.65750E-002 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | -4.20000 | 2.69032E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 45 | T S1 APARTMENT | Cooling | 4417.47130 | 5300.96556 | 0.31691 | 0.38029 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 25.34400 | 8.81502E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 46 | T S1 APARTMENT | Heating | 1603.39780 | 1924.07736 | 7.00854E-002 | 8.41025E-002 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | -4.20000 | 2.69032E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 47 | T S2 APARTMENT | Cooling | 4387.71779 | 5265.26135 | 0.31473 | 0.37768 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 25.34400 | 8.81502E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 48 | T S2 APARTMENT | Heating | 1603.56976 | 1924.28371 | 7.00929E-002 | 8.41115E-002 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | -4.20000 | 2.69032E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
| 1 | SPLIT GSW | Cooling | Sensible | 4933.26 | 0.36481 | 0.36481 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
| 2 | SPLIT GSW | Heating | Sensible | 2521.23 | 7.70956E-002 | 7.70956E-002 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:50:00 |
| 3 | SPLIT GNW | Cooling | Sensible | 4141.66 | 0.30613 | 0.30613 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
| 4 | SPLIT GNW | Heating | Sensible | 2385.95 | 7.10950E-002 | 7.10950E-002 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 |
| 5 | SPLIT OFFICE | Cooling | Sensible | 5341.35 | 0.40239 | 0.40239 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
| 6 | SPLIT OFFICE | Heating | Sensible | 3411.01 | 0.10030 | 0.10030 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 18:50:00 |
| 7 | SPLIT GNE | Cooling | Sensible | 3637.80 | 0.26881 | 0.26881 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
| 8 | SPLIT GNE | Heating | Sensible | 2389.70 | 7.12613E-002 | 7.12613E-002 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 |
| 9 | SPLIT GN1 | Cooling | Sensible | 3318.25 | 0.24519 | 0.24519 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
| 10 | SPLIT GN1 | Heating | Sensible | 1705.02 | 4.08903E-002 | 4.08903E-002 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 |
| 11 | SPLIT GN2 | Cooling | Sensible | 3308.93 | 0.24450 | 0.24450 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
| 12 | SPLIT GN2 | Heating | Sensible | 1705.14 | 4.08955E-002 | 4.08955E-002 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 |
| 13 | SPLIT GS1 | Cooling | Sensible | 4173.65 | 0.30850 | 0.30850 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
| 14 | SPLIT GS1 | Heating | Sensible | 1841.79 | 4.69568E-002 | 4.69568E-002 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:50:00 |
| 15 | SPLIT GS2 | Cooling | Sensible | 4194.58 | 0.31006 | 0.31006 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
| 16 | SPLIT GS2 | Heating | Sensible | 1852.02 | 4.74107E-002 | 4.74107E-002 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:50:00 |
| 17 | SPLIT MSW | Cooling | Sensible | 11970.17 | 0.88553 | 0.88553 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
| 18 | SPLIT MSW | Heating | Sensible | 4711.58 | 0.13951 | 0.13951 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 |
| 19 | SPLIT MNW | Cooling | Sensible | 10486.11 | 0.77553 | 0.77553 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
| 20 | SPLIT MNW | Heating | Sensible | 4388.50 | 0.12518 | 0.12518 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 |
| 21 | SPLIT MSE | Cooling | Sensible | 10460.41 | 0.77365 | 0.77365 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
| 22 | SPLIT MSE | Heating | Sensible | 4720.80 | 0.13992 | 0.13992 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 |
| 23 | SPLIT MNE | Cooling | Sensible | 9015.64 | 0.66641 | 0.66641 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
| 24 | SPLIT MNE | Heating | Sensible | 4397.80 | 0.12559 | 0.12559 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 |
| 25 | SPLIT MN1 | Cooling | Sensible | 8157.95 | 0.60300 | 0.60300 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
| 26 | SPLIT MN1 | Heating | Sensible | 2937.56 | 6.08215E-002 | 6.08215E-002 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 |
| 27 | SPLIT MN2 | Cooling | Sensible | 8132.31 | 0.60110 | 0.60110 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
| 28 | SPLIT MN2 | Heating | Sensible | 2937.82 | 6.08329E-002 | 6.08329E-002 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 |
| 29 | SPLIT MS1 | Cooling | Sensible | 9780.59 | 0.72321 | 0.72321 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
| 30 | SPLIT MS1 | Heating | Sensible | 3251.36 | 7.47404E-002 | 7.47404E-002 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 |
| 31 | SPLIT MS2 | Cooling | Sensible | 9751.52 | 0.72105 | 0.72105 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
| 32 | SPLIT MS2 | Heating | Sensible | 3251.61 | 7.47516E-002 | 7.47516E-002 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 |
| 33 | SPLIT TSW | Cooling | Sensible | 6413.77 | 0.47445 | 0.47445 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
| 34 | SPLIT TSW | Heating | Sensible | 3544.45 | 0.12248 | 0.12248 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 |
| 35 | SPLIT TNW | Cooling | Sensible | 5811.70 | 0.42975 | 0.42975 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
| 36 | SPLIT TNW | Heating | Sensible | 3374.47 | 0.11494 | 0.11494 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 |
| 37 | SPLIT TSE | Cooling | Sensible | 5322.82 | 0.39352 | 0.39352 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
| 38 | SPLIT TSE | Heating | Sensible | 3551.31 | 0.12278 | 0.12278 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 |
| 39 | SPLIT TNE | Cooling | Sensible | 4727.70 | 0.34939 | 0.34939 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
| 40 | SPLIT TNE | Heating | Sensible | 3381.43 | 0.11525 | 0.11525 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 |
| 41 | SPLIT TN1 | Cooling | Sensible | 4503.59 | 0.33276 | 0.33276 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
| 42 | SPLIT TN1 | Heating | Sensible | 2509.31 | 7.65657E-002 | 7.65657E-002 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 |
| 43 | SPLIT TN2 | Cooling | Sensible | 4468.54 | 0.33016 | 0.33016 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
| 44 | SPLIT TN2 | Heating | Sensible | 2509.52 | 7.65750E-002 | 7.65750E-002 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 |
| 45 | SPLIT TS1 | Cooling | Sensible | 5144.35 | 0.38029 | 0.38029 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
| 46 | SPLIT TS1 | Heating | Sensible | 2679.24 | 8.41025E-002 | 8.41025E-002 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 |
| 47 | SPLIT TS2 | Cooling | Sensible | 5109.09 | 0.37768 | 0.37768 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
| 48 | SPLIT TS2 | Heating | Sensible | 2679.44 | 8.41115E-002 | 8.41115E-002 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 |
| Component Type | Component Name | Input Field Description | Value | |
| 1 | ZoneHVAC:EnergyRecoveryVentilator | G SW APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 2 | ZoneHVAC:EnergyRecoveryVentilator | G SW APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 2.59546E-002 |
| 3 | Fan:OnOff | G SW APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 4 | Fan:OnOff | G SW APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 5 | HeatExchanger:AirToAir:SensibleAndLatent | G SW APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 6 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | G SW APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.36481 |
| 7 | ZoneHVAC:EnergyRecoveryVentilator | G NW APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 8 | ZoneHVAC:EnergyRecoveryVentilator | G NW APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 2.59546E-002 |
| 9 | Fan:OnOff | G NW APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 10 | Fan:OnOff | G NW APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 11 | HeatExchanger:AirToAir:SensibleAndLatent | G NW APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 12 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | G NW APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.30613 |
| 13 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | OFFICE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.40239 |
| 14 | ZoneHVAC:EnergyRecoveryVentilator | G NE APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 15 | ZoneHVAC:EnergyRecoveryVentilator | G NE APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 2.59546E-002 |
| 16 | Fan:OnOff | G NE APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 17 | Fan:OnOff | G NE APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 18 | HeatExchanger:AirToAir:SensibleAndLatent | G NE APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 19 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | G NE APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.26881 |
| 20 | ZoneHVAC:EnergyRecoveryVentilator | G N1 APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 21 | ZoneHVAC:EnergyRecoveryVentilator | G N1 APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 2.59546E-002 |
| 22 | Fan:OnOff | G N1 APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 23 | Fan:OnOff | G N1 APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 24 | HeatExchanger:AirToAir:SensibleAndLatent | G N1 APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 25 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | G N1 APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.24519 |
| 26 | ZoneHVAC:EnergyRecoveryVentilator | G N2 APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 27 | ZoneHVAC:EnergyRecoveryVentilator | G N2 APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 2.59546E-002 |
| 28 | Fan:OnOff | G N2 APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 29 | Fan:OnOff | G N2 APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 30 | HeatExchanger:AirToAir:SensibleAndLatent | G N2 APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 31 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | G N2 APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.24450 |
| 32 | ZoneHVAC:EnergyRecoveryVentilator | G S1 APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 33 | ZoneHVAC:EnergyRecoveryVentilator | G S1 APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 2.59546E-002 |
| 34 | Fan:OnOff | G S1 APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 35 | Fan:OnOff | G S1 APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 36 | HeatExchanger:AirToAir:SensibleAndLatent | G S1 APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 37 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | G S1 APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.30850 |
| 38 | ZoneHVAC:EnergyRecoveryVentilator | G S2 APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 39 | ZoneHVAC:EnergyRecoveryVentilator | G S2 APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 2.59546E-002 |
| 40 | Fan:OnOff | G S2 APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 41 | Fan:OnOff | G S2 APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 42 | HeatExchanger:AirToAir:SensibleAndLatent | G S2 APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 43 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | G S2 APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.31006 |
| 44 | ZoneHVAC:EnergyRecoveryVentilator | M SW APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 5.19091E-002 |
| 45 | ZoneHVAC:EnergyRecoveryVentilator | M SW APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 5.19091E-002 |
| 46 | Fan:OnOff | M SW APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 5.19091E-002 |
| 47 | Fan:OnOff | M SW APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 5.19091E-002 |
| 48 | HeatExchanger:AirToAir:SensibleAndLatent | M SW APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 5.19091E-002 |
| 49 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | M SW APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.88553 |
| 50 | ZoneHVAC:EnergyRecoveryVentilator | M NW APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 5.19091E-002 |
| 51 | ZoneHVAC:EnergyRecoveryVentilator | M NW APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 5.19091E-002 |
| 52 | Fan:OnOff | M NW APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 5.19091E-002 |
| 53 | Fan:OnOff | M NW APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 5.19091E-002 |
| 54 | HeatExchanger:AirToAir:SensibleAndLatent | M NW APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 5.19091E-002 |
| 55 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | M NW APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.77553 |
| 56 | ZoneHVAC:EnergyRecoveryVentilator | M SE APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 5.19091E-002 |
| 57 | ZoneHVAC:EnergyRecoveryVentilator | M SE APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 5.19091E-002 |
| 58 | Fan:OnOff | M SE APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 5.19091E-002 |
| 59 | Fan:OnOff | M SE APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 5.19091E-002 |
| 60 | HeatExchanger:AirToAir:SensibleAndLatent | M SE APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 5.19091E-002 |
| 61 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | M SE APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.77365 |
| 62 | ZoneHVAC:EnergyRecoveryVentilator | M NE APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 5.19091E-002 |
| 63 | ZoneHVAC:EnergyRecoveryVentilator | M NE APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 5.19091E-002 |
| 64 | Fan:OnOff | M NE APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 5.19091E-002 |
| 65 | Fan:OnOff | M NE APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 5.19091E-002 |
| 66 | HeatExchanger:AirToAir:SensibleAndLatent | M NE APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 5.19091E-002 |
| 67 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | M NE APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.66641 |
| 68 | ZoneHVAC:EnergyRecoveryVentilator | M N1 APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 5.19091E-002 |
| 69 | ZoneHVAC:EnergyRecoveryVentilator | M N1 APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 5.19091E-002 |
| 70 | Fan:OnOff | M N1 APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 5.19091E-002 |
| 71 | Fan:OnOff | M N1 APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 5.19091E-002 |
| 72 | HeatExchanger:AirToAir:SensibleAndLatent | M N1 APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 5.19091E-002 |
| 73 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | M N1 APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.60300 |
| 74 | ZoneHVAC:EnergyRecoveryVentilator | M N2 APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 5.19091E-002 |
| 75 | ZoneHVAC:EnergyRecoveryVentilator | M N2 APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 5.19091E-002 |
| 76 | Fan:OnOff | M N2 APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 5.19091E-002 |
| 77 | Fan:OnOff | M N2 APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 5.19091E-002 |
| 78 | HeatExchanger:AirToAir:SensibleAndLatent | M N2 APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 5.19091E-002 |
| 79 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | M N2 APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.60110 |
| 80 | ZoneHVAC:EnergyRecoveryVentilator | M S1 APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 5.19091E-002 |
| 81 | ZoneHVAC:EnergyRecoveryVentilator | M S1 APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 5.19091E-002 |
| 82 | Fan:OnOff | M S1 APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 5.19091E-002 |
| 83 | Fan:OnOff | M S1 APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 5.19091E-002 |
| 84 | HeatExchanger:AirToAir:SensibleAndLatent | M S1 APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 5.19091E-002 |
| 85 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | M S1 APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.72321 |
| 86 | ZoneHVAC:EnergyRecoveryVentilator | M S2 APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 5.19091E-002 |
| 87 | ZoneHVAC:EnergyRecoveryVentilator | M S2 APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 5.19091E-002 |
| 88 | Fan:OnOff | M S2 APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 5.19091E-002 |
| 89 | Fan:OnOff | M S2 APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 5.19091E-002 |
| 90 | HeatExchanger:AirToAir:SensibleAndLatent | M S2 APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 5.19091E-002 |
| 91 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | M S2 APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.72105 |
| 92 | ZoneHVAC:EnergyRecoveryVentilator | T SW APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 93 | ZoneHVAC:EnergyRecoveryVentilator | T SW APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 2.59546E-002 |
| 94 | Fan:OnOff | T SW APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 95 | Fan:OnOff | T SW APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 96 | HeatExchanger:AirToAir:SensibleAndLatent | T SW APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 97 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | T SW APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.47445 |
| 98 | ZoneHVAC:EnergyRecoveryVentilator | T NW APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 99 | ZoneHVAC:EnergyRecoveryVentilator | T NW APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 2.59546E-002 |
| 100 | Fan:OnOff | T NW APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 101 | Fan:OnOff | T NW APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 102 | HeatExchanger:AirToAir:SensibleAndLatent | T NW APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 103 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | T NW APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.42975 |
| 104 | ZoneHVAC:EnergyRecoveryVentilator | T SE APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 105 | ZoneHVAC:EnergyRecoveryVentilator | T SE APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 2.59546E-002 |
| 106 | Fan:OnOff | T SE APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 107 | Fan:OnOff | T SE APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 108 | HeatExchanger:AirToAir:SensibleAndLatent | T SE APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 109 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | T SE APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.39352 |
| 110 | ZoneHVAC:EnergyRecoveryVentilator | T NE APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 111 | ZoneHVAC:EnergyRecoveryVentilator | T NE APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 2.59546E-002 |
| 112 | Fan:OnOff | T NE APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 113 | Fan:OnOff | T NE APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 114 | HeatExchanger:AirToAir:SensibleAndLatent | T NE APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 115 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | T NE APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.34939 |
| 116 | ZoneHVAC:EnergyRecoveryVentilator | T N1 APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 117 | ZoneHVAC:EnergyRecoveryVentilator | T N1 APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 2.59546E-002 |
| 118 | Fan:OnOff | T N1 APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 119 | Fan:OnOff | T N1 APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 120 | HeatExchanger:AirToAir:SensibleAndLatent | T N1 APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 121 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | T N1 APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.33276 |
| 122 | ZoneHVAC:EnergyRecoveryVentilator | T N2 APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 123 | ZoneHVAC:EnergyRecoveryVentilator | T N2 APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 2.59546E-002 |
| 124 | Fan:OnOff | T N2 APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 125 | Fan:OnOff | T N2 APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 126 | HeatExchanger:AirToAir:SensibleAndLatent | T N2 APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 127 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | T N2 APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.33016 |
| 128 | ZoneHVAC:EnergyRecoveryVentilator | T S1 APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 129 | ZoneHVAC:EnergyRecoveryVentilator | T S1 APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 2.59546E-002 |
| 130 | Fan:OnOff | T S1 APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 131 | Fan:OnOff | T S1 APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 132 | HeatExchanger:AirToAir:SensibleAndLatent | T S1 APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 133 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | T S1 APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.38029 |
| 134 | ZoneHVAC:EnergyRecoveryVentilator | T S2 APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 135 | ZoneHVAC:EnergyRecoveryVentilator | T S2 APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 2.59546E-002 |
| 136 | Fan:OnOff | T S2 APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 137 | Fan:OnOff | T S2 APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 138 | HeatExchanger:AirToAir:SensibleAndLatent | T S2 APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 139 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | T S2 APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.37768 |
| 140 | AirLoopHVAC | SPLIT GSW | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.36481 |
| 141 | AirLoopHVAC | SPLIT GSW | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.36481 |
| 142 | AirLoopHVAC | SPLIT GSW | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.36481 |
| 143 | AirLoopHVAC | SPLIT GSW | Adjusted Heating Design Air Flow Rate [m3/s] | 0.36481 |
| 144 | AirLoopHVAC | SPLIT GSW | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.36481 |
| 145 | AirLoopHVAC | SPLIT GSW | Adjusted Main Design Air Flow Rate [m3/s] | 0.36481 |
| 146 | AirLoopHVAC | SPLIT GSW | User Heating Air Flow Ratio [] | 1.00000 |
| 147 | AirLoopHVAC | SPLIT GSW | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 148 | AirLoopHVAC | SPLIT GNW | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.30613 |
| 149 | AirLoopHVAC | SPLIT GNW | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.30613 |
| 150 | AirLoopHVAC | SPLIT GNW | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.30613 |
| 151 | AirLoopHVAC | SPLIT GNW | Adjusted Heating Design Air Flow Rate [m3/s] | 0.30613 |
| 152 | AirLoopHVAC | SPLIT GNW | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.30613 |
| 153 | AirLoopHVAC | SPLIT GNW | Adjusted Main Design Air Flow Rate [m3/s] | 0.30613 |
| 154 | AirLoopHVAC | SPLIT GNW | User Heating Air Flow Ratio [] | 1.00000 |
| 155 | AirLoopHVAC | SPLIT GNW | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 156 | AirLoopHVAC | SPLIT OFFICE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.40239 |
| 157 | AirLoopHVAC | SPLIT OFFICE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.40239 |
| 158 | AirLoopHVAC | SPLIT OFFICE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.40239 |
| 159 | AirLoopHVAC | SPLIT OFFICE | Adjusted Heating Design Air Flow Rate [m3/s] | 0.40239 |
| 160 | AirLoopHVAC | SPLIT OFFICE | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.40239 |
| 161 | AirLoopHVAC | SPLIT OFFICE | Adjusted Main Design Air Flow Rate [m3/s] | 0.40239 |
| 162 | AirLoopHVAC | SPLIT OFFICE | User Heating Air Flow Ratio [] | 1.00000 |
| 163 | AirLoopHVAC | SPLIT OFFICE | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 164 | AirLoopHVAC | SPLIT GNE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.26881 |
| 165 | AirLoopHVAC | SPLIT GNE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.26881 |
| 166 | AirLoopHVAC | SPLIT GNE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.26881 |
| 167 | AirLoopHVAC | SPLIT GNE | Adjusted Heating Design Air Flow Rate [m3/s] | 0.26881 |
| 168 | AirLoopHVAC | SPLIT GNE | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.26881 |
| 169 | AirLoopHVAC | SPLIT GNE | Adjusted Main Design Air Flow Rate [m3/s] | 0.26881 |
| 170 | AirLoopHVAC | SPLIT GNE | User Heating Air Flow Ratio [] | 1.00000 |
| 171 | AirLoopHVAC | SPLIT GNE | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 172 | AirLoopHVAC | SPLIT GN1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.24519 |
| 173 | AirLoopHVAC | SPLIT GN1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.24519 |
| 174 | AirLoopHVAC | SPLIT GN1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.24519 |
| 175 | AirLoopHVAC | SPLIT GN1 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.24519 |
| 176 | AirLoopHVAC | SPLIT GN1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.24519 |
| 177 | AirLoopHVAC | SPLIT GN1 | Adjusted Main Design Air Flow Rate [m3/s] | 0.24519 |
| 178 | AirLoopHVAC | SPLIT GN1 | User Heating Air Flow Ratio [] | 1.00000 |
| 179 | AirLoopHVAC | SPLIT GN1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 180 | AirLoopHVAC | SPLIT GN2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.24450 |
| 181 | AirLoopHVAC | SPLIT GN2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.24450 |
| 182 | AirLoopHVAC | SPLIT GN2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.24450 |
| 183 | AirLoopHVAC | SPLIT GN2 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.24450 |
| 184 | AirLoopHVAC | SPLIT GN2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.24450 |
| 185 | AirLoopHVAC | SPLIT GN2 | Adjusted Main Design Air Flow Rate [m3/s] | 0.24450 |
| 186 | AirLoopHVAC | SPLIT GN2 | User Heating Air Flow Ratio [] | 1.00000 |
| 187 | AirLoopHVAC | SPLIT GN2 | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 188 | AirLoopHVAC | SPLIT GS1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.30850 |
| 189 | AirLoopHVAC | SPLIT GS1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.30850 |
| 190 | AirLoopHVAC | SPLIT GS1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.30850 |
| 191 | AirLoopHVAC | SPLIT GS1 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.30850 |
| 192 | AirLoopHVAC | SPLIT GS1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.30850 |
| 193 | AirLoopHVAC | SPLIT GS1 | Adjusted Main Design Air Flow Rate [m3/s] | 0.30850 |
| 194 | AirLoopHVAC | SPLIT GS1 | User Heating Air Flow Ratio [] | 1.00000 |
| 195 | AirLoopHVAC | SPLIT GS1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 196 | AirLoopHVAC | SPLIT GS2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.31006 |
| 197 | AirLoopHVAC | SPLIT GS2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.31006 |
| 198 | AirLoopHVAC | SPLIT GS2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.31006 |
| 199 | AirLoopHVAC | SPLIT GS2 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.31006 |
| 200 | AirLoopHVAC | SPLIT GS2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.31006 |
| 201 | AirLoopHVAC | SPLIT GS2 | Adjusted Main Design Air Flow Rate [m3/s] | 0.31006 |
| 202 | AirLoopHVAC | SPLIT GS2 | User Heating Air Flow Ratio [] | 1.00000 |
| 203 | AirLoopHVAC | SPLIT GS2 | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 204 | AirLoopHVAC | SPLIT MSW | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.88553 |
| 205 | AirLoopHVAC | SPLIT MSW | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.88553 |
| 206 | AirLoopHVAC | SPLIT MSW | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.88553 |
| 207 | AirLoopHVAC | SPLIT MSW | Adjusted Heating Design Air Flow Rate [m3/s] | 0.88553 |
| 208 | AirLoopHVAC | SPLIT MSW | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.88553 |
| 209 | AirLoopHVAC | SPLIT MSW | Adjusted Main Design Air Flow Rate [m3/s] | 0.88553 |
| 210 | AirLoopHVAC | SPLIT MSW | User Heating Air Flow Ratio [] | 1.00000 |
| 211 | AirLoopHVAC | SPLIT MSW | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 212 | AirLoopHVAC | SPLIT MNW | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.77553 |
| 213 | AirLoopHVAC | SPLIT MNW | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.77553 |
| 214 | AirLoopHVAC | SPLIT MNW | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.77553 |
| 215 | AirLoopHVAC | SPLIT MNW | Adjusted Heating Design Air Flow Rate [m3/s] | 0.77553 |
| 216 | AirLoopHVAC | SPLIT MNW | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.77553 |
| 217 | AirLoopHVAC | SPLIT MNW | Adjusted Main Design Air Flow Rate [m3/s] | 0.77553 |
| 218 | AirLoopHVAC | SPLIT MNW | User Heating Air Flow Ratio [] | 1.00000 |
| 219 | AirLoopHVAC | SPLIT MNW | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 220 | AirLoopHVAC | SPLIT MSE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.77365 |
| 221 | AirLoopHVAC | SPLIT MSE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.77365 |
| 222 | AirLoopHVAC | SPLIT MSE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.77365 |
| 223 | AirLoopHVAC | SPLIT MSE | Adjusted Heating Design Air Flow Rate [m3/s] | 0.77365 |
| 224 | AirLoopHVAC | SPLIT MSE | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.77365 |
| 225 | AirLoopHVAC | SPLIT MSE | Adjusted Main Design Air Flow Rate [m3/s] | 0.77365 |
| 226 | AirLoopHVAC | SPLIT MSE | User Heating Air Flow Ratio [] | 1.00000 |
| 227 | AirLoopHVAC | SPLIT MSE | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 228 | AirLoopHVAC | SPLIT MNE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.66641 |
| 229 | AirLoopHVAC | SPLIT MNE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.66641 |
| 230 | AirLoopHVAC | SPLIT MNE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.66641 |
| 231 | AirLoopHVAC | SPLIT MNE | Adjusted Heating Design Air Flow Rate [m3/s] | 0.66641 |
| 232 | AirLoopHVAC | SPLIT MNE | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.66641 |
| 233 | AirLoopHVAC | SPLIT MNE | Adjusted Main Design Air Flow Rate [m3/s] | 0.66641 |
| 234 | AirLoopHVAC | SPLIT MNE | User Heating Air Flow Ratio [] | 1.00000 |
| 235 | AirLoopHVAC | SPLIT MNE | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 236 | AirLoopHVAC | SPLIT MN1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.60300 |
| 237 | AirLoopHVAC | SPLIT MN1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.60300 |
| 238 | AirLoopHVAC | SPLIT MN1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.60300 |
| 239 | AirLoopHVAC | SPLIT MN1 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.60300 |
| 240 | AirLoopHVAC | SPLIT MN1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.60300 |
| 241 | AirLoopHVAC | SPLIT MN1 | Adjusted Main Design Air Flow Rate [m3/s] | 0.60300 |
| 242 | AirLoopHVAC | SPLIT MN1 | User Heating Air Flow Ratio [] | 1.00000 |
| 243 | AirLoopHVAC | SPLIT MN1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 244 | AirLoopHVAC | SPLIT MN2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.60110 |
| 245 | AirLoopHVAC | SPLIT MN2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.60110 |
| 246 | AirLoopHVAC | SPLIT MN2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.60110 |
| 247 | AirLoopHVAC | SPLIT MN2 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.60110 |
| 248 | AirLoopHVAC | SPLIT MN2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.60110 |
| 249 | AirLoopHVAC | SPLIT MN2 | Adjusted Main Design Air Flow Rate [m3/s] | 0.60110 |
| 250 | AirLoopHVAC | SPLIT MN2 | User Heating Air Flow Ratio [] | 1.00000 |
| 251 | AirLoopHVAC | SPLIT MN2 | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 252 | AirLoopHVAC | SPLIT MS1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.72321 |
| 253 | AirLoopHVAC | SPLIT MS1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.72321 |
| 254 | AirLoopHVAC | SPLIT MS1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.72321 |
| 255 | AirLoopHVAC | SPLIT MS1 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.72321 |
| 256 | AirLoopHVAC | SPLIT MS1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.72321 |
| 257 | AirLoopHVAC | SPLIT MS1 | Adjusted Main Design Air Flow Rate [m3/s] | 0.72321 |
| 258 | AirLoopHVAC | SPLIT MS1 | User Heating Air Flow Ratio [] | 1.00000 |
| 259 | AirLoopHVAC | SPLIT MS1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 260 | AirLoopHVAC | SPLIT MS2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.72105 |
| 261 | AirLoopHVAC | SPLIT MS2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.72105 |
| 262 | AirLoopHVAC | SPLIT MS2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.72105 |
| 263 | AirLoopHVAC | SPLIT MS2 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.72105 |
| 264 | AirLoopHVAC | SPLIT MS2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.72105 |
| 265 | AirLoopHVAC | SPLIT MS2 | Adjusted Main Design Air Flow Rate [m3/s] | 0.72105 |
| 266 | AirLoopHVAC | SPLIT MS2 | User Heating Air Flow Ratio [] | 1.00000 |
| 267 | AirLoopHVAC | SPLIT MS2 | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 268 | AirLoopHVAC | SPLIT TSW | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.47445 |
| 269 | AirLoopHVAC | SPLIT TSW | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.47445 |
| 270 | AirLoopHVAC | SPLIT TSW | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.47445 |
| 271 | AirLoopHVAC | SPLIT TSW | Adjusted Heating Design Air Flow Rate [m3/s] | 0.47445 |
| 272 | AirLoopHVAC | SPLIT TSW | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.47445 |
| 273 | AirLoopHVAC | SPLIT TSW | Adjusted Main Design Air Flow Rate [m3/s] | 0.47445 |
| 274 | AirLoopHVAC | SPLIT TSW | User Heating Air Flow Ratio [] | 1.00000 |
| 275 | AirLoopHVAC | SPLIT TSW | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 276 | AirLoopHVAC | SPLIT TNW | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.42975 |
| 277 | AirLoopHVAC | SPLIT TNW | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.42975 |
| 278 | AirLoopHVAC | SPLIT TNW | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.42975 |
| 279 | AirLoopHVAC | SPLIT TNW | Adjusted Heating Design Air Flow Rate [m3/s] | 0.42975 |
| 280 | AirLoopHVAC | SPLIT TNW | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.42975 |
| 281 | AirLoopHVAC | SPLIT TNW | Adjusted Main Design Air Flow Rate [m3/s] | 0.42975 |
| 282 | AirLoopHVAC | SPLIT TNW | User Heating Air Flow Ratio [] | 1.00000 |
| 283 | AirLoopHVAC | SPLIT TNW | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 284 | AirLoopHVAC | SPLIT TSE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.39352 |
| 285 | AirLoopHVAC | SPLIT TSE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.39352 |
| 286 | AirLoopHVAC | SPLIT TSE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.39352 |
| 287 | AirLoopHVAC | SPLIT TSE | Adjusted Heating Design Air Flow Rate [m3/s] | 0.39352 |
| 288 | AirLoopHVAC | SPLIT TSE | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.39352 |
| 289 | AirLoopHVAC | SPLIT TSE | Adjusted Main Design Air Flow Rate [m3/s] | 0.39352 |
| 290 | AirLoopHVAC | SPLIT TSE | User Heating Air Flow Ratio [] | 1.00000 |
| 291 | AirLoopHVAC | SPLIT TSE | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 292 | AirLoopHVAC | SPLIT TNE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.34939 |
| 293 | AirLoopHVAC | SPLIT TNE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.34939 |
| 294 | AirLoopHVAC | SPLIT TNE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.34939 |
| 295 | AirLoopHVAC | SPLIT TNE | Adjusted Heating Design Air Flow Rate [m3/s] | 0.34939 |
| 296 | AirLoopHVAC | SPLIT TNE | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.34939 |
| 297 | AirLoopHVAC | SPLIT TNE | Adjusted Main Design Air Flow Rate [m3/s] | 0.34939 |
| 298 | AirLoopHVAC | SPLIT TNE | User Heating Air Flow Ratio [] | 1.00000 |
| 299 | AirLoopHVAC | SPLIT TNE | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 300 | AirLoopHVAC | SPLIT TN1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.33276 |
| 301 | AirLoopHVAC | SPLIT TN1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.33276 |
| 302 | AirLoopHVAC | SPLIT TN1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.33276 |
| 303 | AirLoopHVAC | SPLIT TN1 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.33276 |
| 304 | AirLoopHVAC | SPLIT TN1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.33276 |
| 305 | AirLoopHVAC | SPLIT TN1 | Adjusted Main Design Air Flow Rate [m3/s] | 0.33276 |
| 306 | AirLoopHVAC | SPLIT TN1 | User Heating Air Flow Ratio [] | 1.00000 |
| 307 | AirLoopHVAC | SPLIT TN1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 308 | AirLoopHVAC | SPLIT TN2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.33016 |
| 309 | AirLoopHVAC | SPLIT TN2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.33016 |
| 310 | AirLoopHVAC | SPLIT TN2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.33016 |
| 311 | AirLoopHVAC | SPLIT TN2 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.33016 |
| 312 | AirLoopHVAC | SPLIT TN2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.33016 |
| 313 | AirLoopHVAC | SPLIT TN2 | Adjusted Main Design Air Flow Rate [m3/s] | 0.33016 |
| 314 | AirLoopHVAC | SPLIT TN2 | User Heating Air Flow Ratio [] | 1.00000 |
| 315 | AirLoopHVAC | SPLIT TN2 | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 316 | AirLoopHVAC | SPLIT TS1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.38029 |
| 317 | AirLoopHVAC | SPLIT TS1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.38029 |
| 318 | AirLoopHVAC | SPLIT TS1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.38029 |
| 319 | AirLoopHVAC | SPLIT TS1 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.38029 |
| 320 | AirLoopHVAC | SPLIT TS1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.38029 |
| 321 | AirLoopHVAC | SPLIT TS1 | Adjusted Main Design Air Flow Rate [m3/s] | 0.38029 |
| 322 | AirLoopHVAC | SPLIT TS1 | User Heating Air Flow Ratio [] | 1.00000 |
| 323 | AirLoopHVAC | SPLIT TS1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 324 | AirLoopHVAC | SPLIT TS2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.37768 |
| 325 | AirLoopHVAC | SPLIT TS2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.37768 |
| 326 | AirLoopHVAC | SPLIT TS2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.37768 |
| 327 | AirLoopHVAC | SPLIT TS2 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.37768 |
| 328 | AirLoopHVAC | SPLIT TS2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.37768 |
| 329 | AirLoopHVAC | SPLIT TS2 | Adjusted Main Design Air Flow Rate [m3/s] | 0.37768 |
| 330 | AirLoopHVAC | SPLIT TS2 | User Heating Air Flow Ratio [] | 1.00000 |
| 331 | AirLoopHVAC | SPLIT TS2 | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 332 | AirLoopHVAC | SPLIT GSW | Design Supply Air Flow Rate [m3/s] | 0.36481 |
| 333 | AirLoopHVAC | SPLIT GNW | Design Supply Air Flow Rate [m3/s] | 0.30613 |
| 334 | AirLoopHVAC | SPLIT OFFICE | Design Supply Air Flow Rate [m3/s] | 0.40239 |
| 335 | AirLoopHVAC | SPLIT GNE | Design Supply Air Flow Rate [m3/s] | 0.26881 |
| 336 | AirLoopHVAC | SPLIT GN1 | Design Supply Air Flow Rate [m3/s] | 0.24519 |
| 337 | AirLoopHVAC | SPLIT GN2 | Design Supply Air Flow Rate [m3/s] | 0.24450 |
| 338 | AirLoopHVAC | SPLIT GS1 | Design Supply Air Flow Rate [m3/s] | 0.30850 |
| 339 | AirLoopHVAC | SPLIT GS2 | Design Supply Air Flow Rate [m3/s] | 0.31006 |
| 340 | AirLoopHVAC | SPLIT MSW | Design Supply Air Flow Rate [m3/s] | 0.88553 |
| 341 | AirLoopHVAC | SPLIT MNW | Design Supply Air Flow Rate [m3/s] | 0.77553 |
| 342 | AirLoopHVAC | SPLIT MSE | Design Supply Air Flow Rate [m3/s] | 0.77365 |
| 343 | AirLoopHVAC | SPLIT MNE | Design Supply Air Flow Rate [m3/s] | 0.66641 |
| 344 | AirLoopHVAC | SPLIT MN1 | Design Supply Air Flow Rate [m3/s] | 0.60300 |
| 345 | AirLoopHVAC | SPLIT MN2 | Design Supply Air Flow Rate [m3/s] | 0.60110 |
| 346 | AirLoopHVAC | SPLIT MS1 | Design Supply Air Flow Rate [m3/s] | 0.72321 |
| 347 | AirLoopHVAC | SPLIT MS2 | Design Supply Air Flow Rate [m3/s] | 0.72105 |
| 348 | AirLoopHVAC | SPLIT TSW | Design Supply Air Flow Rate [m3/s] | 0.47445 |
| 349 | AirLoopHVAC | SPLIT TNW | Design Supply Air Flow Rate [m3/s] | 0.42975 |
| 350 | AirLoopHVAC | SPLIT TSE | Design Supply Air Flow Rate [m3/s] | 0.39352 |
| 351 | AirLoopHVAC | SPLIT TNE | Design Supply Air Flow Rate [m3/s] | 0.34939 |
| 352 | AirLoopHVAC | SPLIT TN1 | Design Supply Air Flow Rate [m3/s] | 0.33276 |
| 353 | AirLoopHVAC | SPLIT TN2 | Design Supply Air Flow Rate [m3/s] | 0.33016 |
| 354 | AirLoopHVAC | SPLIT TS1 | Design Supply Air Flow Rate [m3/s] | 0.38029 |
| 355 | AirLoopHVAC | SPLIT TS2 | Design Supply Air Flow Rate [m3/s] | 0.37768 |
| 356 | Controller:OutdoorAir | SPLIT GSW_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.36481 |
| 357 | Controller:OutdoorAir | SPLIT GSW_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.59546E-002 |
| 358 | AirLoopHVAC:UnitarySystem | SPLIT GSW_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.36481 |
| 359 | AirLoopHVAC:UnitarySystem | SPLIT GSW_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.36481 |
| 360 | AirLoopHVAC:UnitarySystem | SPLIT GSW_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.36481 |
| 361 | AirLoopHVAC:UnitarySystem | SPLIT GSW_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.36481 |
| 362 | AirLoopHVAC:UnitarySystem | SPLIT GSW_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 6038.92921 |
| 363 | AirLoopHVAC:UnitarySystem | SPLIT GSW_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 9007.42793 |
| 364 | AirLoopHVAC:UnitarySystem | SPLIT GSW_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 365 | AirLoopHVAC:UnitarySystem | SPLIT GSW_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 366 | Fan:OnOff | SPLIT GSW SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.36481 |
| 367 | Coil:Cooling:DX:SingleSpeed | SPLIT GSW COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.36481 |
| 368 | Coil:Cooling:DX:SingleSpeed | SPLIT GSW COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 6038.92921 |
| 369 | Coil:Cooling:DX:SingleSpeed | SPLIT GSW COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
| 370 | Coil:Heating:Fuel | SPLIT GSW HEATING COIL | Design Size Nominal Capacity [W] | 9007.42793 |
| 371 | Controller:OutdoorAir | SPLIT GNW_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.30613 |
| 372 | Controller:OutdoorAir | SPLIT GNW_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.59546E-002 |
| 373 | AirLoopHVAC:UnitarySystem | SPLIT GNW_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.30613 |
| 374 | AirLoopHVAC:UnitarySystem | SPLIT GNW_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.30613 |
| 375 | AirLoopHVAC:UnitarySystem | SPLIT GNW_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.30613 |
| 376 | AirLoopHVAC:UnitarySystem | SPLIT GNW_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.30613 |
| 377 | AirLoopHVAC:UnitarySystem | SPLIT GNW_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 5067.54560 |
| 378 | AirLoopHVAC:UnitarySystem | SPLIT GNW_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 7684.47275 |
| 379 | AirLoopHVAC:UnitarySystem | SPLIT GNW_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 380 | AirLoopHVAC:UnitarySystem | SPLIT GNW_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 381 | Fan:OnOff | SPLIT GNW SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.30613 |
| 382 | Coil:Cooling:DX:SingleSpeed | SPLIT GNW COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.30613 |
| 383 | Coil:Cooling:DX:SingleSpeed | SPLIT GNW COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 5067.54560 |
| 384 | Coil:Cooling:DX:SingleSpeed | SPLIT GNW COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
| 385 | Coil:Heating:Fuel | SPLIT GNW HEATING COIL | Design Size Nominal Capacity [W] | 7684.47275 |
| 386 | Controller:OutdoorAir | SPLIT OFFICE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.40239 |
| 387 | Controller:OutdoorAir | SPLIT OFFICE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 3.81060E-002 |
| 388 | AirLoopHVAC:UnitarySystem | SPLIT OFFICE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.40239 |
| 389 | AirLoopHVAC:UnitarySystem | SPLIT OFFICE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.40239 |
| 390 | AirLoopHVAC:UnitarySystem | SPLIT OFFICE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.40239 |
| 391 | AirLoopHVAC:UnitarySystem | SPLIT OFFICE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.40239 |
| 392 | AirLoopHVAC:UnitarySystem | SPLIT OFFICE_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 6660.94313 |
| 393 | AirLoopHVAC:UnitarySystem | SPLIT OFFICE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 10221.21737 |
| 394 | AirLoopHVAC:UnitarySystem | SPLIT OFFICE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 395 | AirLoopHVAC:UnitarySystem | SPLIT OFFICE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 396 | Fan:OnOff | SPLIT OFFICE SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.40239 |
| 397 | Coil:Cooling:DX:SingleSpeed | SPLIT OFFICE COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.40239 |
| 398 | Coil:Cooling:DX:SingleSpeed | SPLIT OFFICE COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 6660.94313 |
| 399 | Coil:Cooling:DX:SingleSpeed | SPLIT OFFICE COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
| 400 | Coil:Heating:Fuel | SPLIT OFFICE HEATING COIL | Design Size Nominal Capacity [W] | 10221.21737 |
| 401 | Controller:OutdoorAir | SPLIT GNE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.26881 |
| 402 | Controller:OutdoorAir | SPLIT GNE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.59546E-002 |
| 403 | AirLoopHVAC:UnitarySystem | SPLIT GNE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.26881 |
| 404 | AirLoopHVAC:UnitarySystem | SPLIT GNE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.26881 |
| 405 | AirLoopHVAC:UnitarySystem | SPLIT GNE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.26881 |
| 406 | AirLoopHVAC:UnitarySystem | SPLIT GNE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.26881 |
| 407 | AirLoopHVAC:UnitarySystem | SPLIT GNE_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 4449.75093 |
| 408 | AirLoopHVAC:UnitarySystem | SPLIT GNE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 6843.12649 |
| 409 | AirLoopHVAC:UnitarySystem | SPLIT GNE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 410 | AirLoopHVAC:UnitarySystem | SPLIT GNE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 411 | Fan:OnOff | SPLIT GNE SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.26881 |
| 412 | Coil:Cooling:DX:SingleSpeed | SPLIT GNE COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.26881 |
| 413 | Coil:Cooling:DX:SingleSpeed | SPLIT GNE COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 4449.75093 |
| 414 | Coil:Cooling:DX:SingleSpeed | SPLIT GNE COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
| 415 | Coil:Heating:Fuel | SPLIT GNE HEATING COIL | Design Size Nominal Capacity [W] | 6843.12649 |
| 416 | Controller:OutdoorAir | SPLIT GN1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.24519 |
| 417 | Controller:OutdoorAir | SPLIT GN1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.59546E-002 |
| 418 | AirLoopHVAC:UnitarySystem | SPLIT GN1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.24519 |
| 419 | AirLoopHVAC:UnitarySystem | SPLIT GN1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.24519 |
| 420 | AirLoopHVAC:UnitarySystem | SPLIT GN1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.24519 |
| 421 | AirLoopHVAC:UnitarySystem | SPLIT GN1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.24519 |
| 422 | AirLoopHVAC:UnitarySystem | SPLIT GN1_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 4058.81214 |
| 423 | AirLoopHVAC:UnitarySystem | SPLIT GN1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 6310.67710 |
| 424 | AirLoopHVAC:UnitarySystem | SPLIT GN1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 425 | AirLoopHVAC:UnitarySystem | SPLIT GN1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 426 | Fan:OnOff | SPLIT GN1 SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.24519 |
| 427 | Coil:Cooling:DX:SingleSpeed | SPLIT GN1 COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.24519 |
| 428 | Coil:Cooling:DX:SingleSpeed | SPLIT GN1 COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 4058.81214 |
| 429 | Coil:Cooling:DX:SingleSpeed | SPLIT GN1 COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
| 430 | Coil:Heating:Fuel | SPLIT GN1 HEATING COIL | Design Size Nominal Capacity [W] | 6310.67710 |
| 431 | Controller:OutdoorAir | SPLIT GN2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.24450 |
| 432 | Controller:OutdoorAir | SPLIT GN2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.59546E-002 |
| 433 | AirLoopHVAC:UnitarySystem | SPLIT GN2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.24450 |
| 434 | AirLoopHVAC:UnitarySystem | SPLIT GN2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.24450 |
| 435 | AirLoopHVAC:UnitarySystem | SPLIT GN2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.24450 |
| 436 | AirLoopHVAC:UnitarySystem | SPLIT GN2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.24450 |
| 437 | AirLoopHVAC:UnitarySystem | SPLIT GN2_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 4047.41691 |
| 438 | AirLoopHVAC:UnitarySystem | SPLIT GN2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 6295.15861 |
| 439 | AirLoopHVAC:UnitarySystem | SPLIT GN2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 440 | AirLoopHVAC:UnitarySystem | SPLIT GN2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 441 | Fan:OnOff | SPLIT GN2 SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.24450 |
| 442 | Coil:Cooling:DX:SingleSpeed | SPLIT GN2 COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.24450 |
| 443 | Coil:Cooling:DX:SingleSpeed | SPLIT GN2 COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 4047.41691 |
| 444 | Coil:Cooling:DX:SingleSpeed | SPLIT GN2 COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
| 445 | Coil:Heating:Fuel | SPLIT GN2 HEATING COIL | Design Size Nominal Capacity [W] | 6295.15861 |
| 446 | Controller:OutdoorAir | SPLIT GS1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.30850 |
| 447 | Controller:OutdoorAir | SPLIT GS1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.59546E-002 |
| 448 | AirLoopHVAC:UnitarySystem | SPLIT GS1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.30850 |
| 449 | AirLoopHVAC:UnitarySystem | SPLIT GS1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.30850 |
| 450 | AirLoopHVAC:UnitarySystem | SPLIT GS1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.30850 |
| 451 | AirLoopHVAC:UnitarySystem | SPLIT GS1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.30850 |
| 452 | AirLoopHVAC:UnitarySystem | SPLIT GS1_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 5106.72105 |
| 453 | AirLoopHVAC:UnitarySystem | SPLIT GS1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 7737.81998 |
| 454 | AirLoopHVAC:UnitarySystem | SPLIT GS1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 455 | AirLoopHVAC:UnitarySystem | SPLIT GS1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 456 | Fan:OnOff | SPLIT GS1 SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.30850 |
| 457 | Coil:Cooling:DX:SingleSpeed | SPLIT GS1 COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.30850 |
| 458 | Coil:Cooling:DX:SingleSpeed | SPLIT GS1 COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 5106.72105 |
| 459 | Coil:Cooling:DX:SingleSpeed | SPLIT GS1 COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
| 460 | Coil:Heating:Fuel | SPLIT GS1 HEATING COIL | Design Size Nominal Capacity [W] | 7737.81998 |
| 461 | Controller:OutdoorAir | SPLIT GS2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.31006 |
| 462 | Controller:OutdoorAir | SPLIT GS2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.59546E-002 |
| 463 | AirLoopHVAC:UnitarySystem | SPLIT GS2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.31006 |
| 464 | AirLoopHVAC:UnitarySystem | SPLIT GS2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.31006 |
| 465 | AirLoopHVAC:UnitarySystem | SPLIT GS2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.31006 |
| 466 | AirLoopHVAC:UnitarySystem | SPLIT GS2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.31006 |
| 467 | AirLoopHVAC:UnitarySystem | SPLIT GS2_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 5132.57841 |
| 468 | AirLoopHVAC:UnitarySystem | SPLIT GS2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 7773.03397 |
| 469 | AirLoopHVAC:UnitarySystem | SPLIT GS2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 470 | AirLoopHVAC:UnitarySystem | SPLIT GS2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 471 | Fan:OnOff | SPLIT GS2 SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.31006 |
| 472 | Coil:Cooling:DX:SingleSpeed | SPLIT GS2 COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.31006 |
| 473 | Coil:Cooling:DX:SingleSpeed | SPLIT GS2 COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 5132.57841 |
| 474 | Coil:Cooling:DX:SingleSpeed | SPLIT GS2 COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
| 475 | Coil:Heating:Fuel | SPLIT GS2 HEATING COIL | Design Size Nominal Capacity [W] | 7773.03397 |
| 476 | Controller:OutdoorAir | SPLIT MSW_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.88553 |
| 477 | Controller:OutdoorAir | SPLIT MSW_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 5.19091E-002 |
| 478 | AirLoopHVAC:UnitarySystem | SPLIT MSW_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.88553 |
| 479 | AirLoopHVAC:UnitarySystem | SPLIT MSW_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.88553 |
| 480 | AirLoopHVAC:UnitarySystem | SPLIT MSW_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.88553 |
| 481 | AirLoopHVAC:UnitarySystem | SPLIT MSW_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.88553 |
| 482 | AirLoopHVAC:UnitarySystem | SPLIT MSW_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 14658.70549 |
| 483 | AirLoopHVAC:UnitarySystem | SPLIT MSW_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 21530.46131 |
| 484 | AirLoopHVAC:UnitarySystem | SPLIT MSW_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 485 | AirLoopHVAC:UnitarySystem | SPLIT MSW_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 486 | Fan:OnOff | SPLIT MSW SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.88553 |
| 487 | Coil:Cooling:DX:SingleSpeed | SPLIT MSW COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.88553 |
| 488 | Coil:Cooling:DX:SingleSpeed | SPLIT MSW COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 14658.70549 |
| 489 | Coil:Cooling:DX:SingleSpeed | SPLIT MSW COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
| 490 | Coil:Heating:Fuel | SPLIT MSW HEATING COIL | Design Size Nominal Capacity [W] | 21530.46131 |
| 491 | Controller:OutdoorAir | SPLIT MNW_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.77553 |
| 492 | Controller:OutdoorAir | SPLIT MNW_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 5.19091E-002 |
| 493 | AirLoopHVAC:UnitarySystem | SPLIT MNW_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.77553 |
| 494 | AirLoopHVAC:UnitarySystem | SPLIT MNW_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.77553 |
| 495 | AirLoopHVAC:UnitarySystem | SPLIT MNW_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.77553 |
| 496 | AirLoopHVAC:UnitarySystem | SPLIT MNW_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.77553 |
| 497 | AirLoopHVAC:UnitarySystem | SPLIT MNW_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 12837.81457 |
| 498 | AirLoopHVAC:UnitarySystem | SPLIT MNW_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 19050.28068 |
| 499 | AirLoopHVAC:UnitarySystem | SPLIT MNW_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 500 | AirLoopHVAC:UnitarySystem | SPLIT MNW_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 501 | Fan:OnOff | SPLIT MNW SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.77553 |
| 502 | Coil:Cooling:DX:SingleSpeed | SPLIT MNW COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.77553 |
| 503 | Coil:Cooling:DX:SingleSpeed | SPLIT MNW COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 12837.81457 |
| 504 | Coil:Cooling:DX:SingleSpeed | SPLIT MNW COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
| 505 | Coil:Heating:Fuel | SPLIT MNW HEATING COIL | Design Size Nominal Capacity [W] | 19050.28068 |
| 506 | Controller:OutdoorAir | SPLIT MSE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.77365 |
| 507 | Controller:OutdoorAir | SPLIT MSE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 5.19091E-002 |
| 508 | AirLoopHVAC:UnitarySystem | SPLIT MSE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.77365 |
| 509 | AirLoopHVAC:UnitarySystem | SPLIT MSE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.77365 |
| 510 | AirLoopHVAC:UnitarySystem | SPLIT MSE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.77365 |
| 511 | AirLoopHVAC:UnitarySystem | SPLIT MSE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.77365 |
| 512 | AirLoopHVAC:UnitarySystem | SPLIT MSE_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 12806.69985 |
| 513 | AirLoopHVAC:UnitarySystem | SPLIT MSE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 19008.16393 |
| 514 | AirLoopHVAC:UnitarySystem | SPLIT MSE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 515 | AirLoopHVAC:UnitarySystem | SPLIT MSE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 516 | Fan:OnOff | SPLIT MSE SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.77365 |
| 517 | Coil:Cooling:DX:SingleSpeed | SPLIT MSE COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.77365 |
| 518 | Coil:Cooling:DX:SingleSpeed | SPLIT MSE COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 12806.69985 |
| 519 | Coil:Cooling:DX:SingleSpeed | SPLIT MSE COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
| 520 | Coil:Heating:Fuel | SPLIT MSE HEATING COIL | Design Size Nominal Capacity [W] | 19008.16393 |
| 521 | Controller:OutdoorAir | SPLIT MNE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.66641 |
| 522 | Controller:OutdoorAir | SPLIT MNE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 5.19091E-002 |
| 523 | AirLoopHVAC:UnitarySystem | SPLIT MNE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.66641 |
| 524 | AirLoopHVAC:UnitarySystem | SPLIT MNE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.66641 |
| 525 | AirLoopHVAC:UnitarySystem | SPLIT MNE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.66641 |
| 526 | AirLoopHVAC:UnitarySystem | SPLIT MNE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.66641 |
| 527 | AirLoopHVAC:UnitarySystem | SPLIT MNE_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 11031.39885 |
| 528 | AirLoopHVAC:UnitarySystem | SPLIT MNE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 16590.11250 |
| 529 | AirLoopHVAC:UnitarySystem | SPLIT MNE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 530 | AirLoopHVAC:UnitarySystem | SPLIT MNE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 531 | Fan:OnOff | SPLIT MNE SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.66641 |
| 532 | Coil:Cooling:DX:SingleSpeed | SPLIT MNE COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.66641 |
| 533 | Coil:Cooling:DX:SingleSpeed | SPLIT MNE COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 11031.39885 |
| 534 | Coil:Cooling:DX:SingleSpeed | SPLIT MNE COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
| 535 | Coil:Heating:Fuel | SPLIT MNE HEATING COIL | Design Size Nominal Capacity [W] | 16590.11250 |
| 536 | Controller:OutdoorAir | SPLIT MN1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.60300 |
| 537 | Controller:OutdoorAir | SPLIT MN1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 5.19091E-002 |
| 538 | AirLoopHVAC:UnitarySystem | SPLIT MN1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.60300 |
| 539 | AirLoopHVAC:UnitarySystem | SPLIT MN1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.60300 |
| 540 | AirLoopHVAC:UnitarySystem | SPLIT MN1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.60300 |
| 541 | AirLoopHVAC:UnitarySystem | SPLIT MN1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.60300 |
| 542 | AirLoopHVAC:UnitarySystem | SPLIT MN1_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 9981.72461 |
| 543 | AirLoopHVAC:UnitarySystem | SPLIT MN1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 15160.22856 |
| 544 | AirLoopHVAC:UnitarySystem | SPLIT MN1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 545 | AirLoopHVAC:UnitarySystem | SPLIT MN1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 546 | Fan:OnOff | SPLIT MN1 SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.60300 |
| 547 | Coil:Cooling:DX:SingleSpeed | SPLIT MN1 COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.60300 |
| 548 | Coil:Cooling:DX:SingleSpeed | SPLIT MN1 COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 9981.72461 |
| 549 | Coil:Cooling:DX:SingleSpeed | SPLIT MN1 COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
| 550 | Coil:Heating:Fuel | SPLIT MN1 HEATING COIL | Design Size Nominal Capacity [W] | 15160.22856 |
| 551 | Controller:OutdoorAir | SPLIT MN2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.60110 |
| 552 | Controller:OutdoorAir | SPLIT MN2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 5.19091E-002 |
| 553 | AirLoopHVAC:UnitarySystem | SPLIT MN2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.60110 |
| 554 | AirLoopHVAC:UnitarySystem | SPLIT MN2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.60110 |
| 555 | AirLoopHVAC:UnitarySystem | SPLIT MN2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.60110 |
| 556 | AirLoopHVAC:UnitarySystem | SPLIT MN2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.60110 |
| 557 | AirLoopHVAC:UnitarySystem | SPLIT MN2_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 9950.29262 |
| 558 | AirLoopHVAC:UnitarySystem | SPLIT MN2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 15117.42227 |
| 559 | AirLoopHVAC:UnitarySystem | SPLIT MN2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 560 | AirLoopHVAC:UnitarySystem | SPLIT MN2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 561 | Fan:OnOff | SPLIT MN2 SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.60110 |
| 562 | Coil:Cooling:DX:SingleSpeed | SPLIT MN2 COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.60110 |
| 563 | Coil:Cooling:DX:SingleSpeed | SPLIT MN2 COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 9950.29262 |
| 564 | Coil:Cooling:DX:SingleSpeed | SPLIT MN2 COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
| 565 | Coil:Heating:Fuel | SPLIT MN2 HEATING COIL | Design Size Nominal Capacity [W] | 15117.42227 |
| 566 | Controller:OutdoorAir | SPLIT MS1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.72321 |
| 567 | Controller:OutdoorAir | SPLIT MS1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 5.19091E-002 |
| 568 | AirLoopHVAC:UnitarySystem | SPLIT MS1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.72321 |
| 569 | AirLoopHVAC:UnitarySystem | SPLIT MS1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.72321 |
| 570 | AirLoopHVAC:UnitarySystem | SPLIT MS1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.72321 |
| 571 | AirLoopHVAC:UnitarySystem | SPLIT MS1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.72321 |
| 572 | AirLoopHVAC:UnitarySystem | SPLIT MS1_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 11971.63750 |
| 573 | AirLoopHVAC:UnitarySystem | SPLIT MS1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 17870.48291 |
| 574 | AirLoopHVAC:UnitarySystem | SPLIT MS1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 575 | AirLoopHVAC:UnitarySystem | SPLIT MS1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 576 | Fan:OnOff | SPLIT MS1 SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.72321 |
| 577 | Coil:Cooling:DX:SingleSpeed | SPLIT MS1 COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.72321 |
| 578 | Coil:Cooling:DX:SingleSpeed | SPLIT MS1 COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 11971.63750 |
| 579 | Coil:Cooling:DX:SingleSpeed | SPLIT MS1 COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
| 580 | Coil:Heating:Fuel | SPLIT MS1 HEATING COIL | Design Size Nominal Capacity [W] | 17870.48291 |
| 581 | Controller:OutdoorAir | SPLIT MS2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.72105 |
| 582 | Controller:OutdoorAir | SPLIT MS2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 5.19091E-002 |
| 583 | AirLoopHVAC:UnitarySystem | SPLIT MS2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.72105 |
| 584 | AirLoopHVAC:UnitarySystem | SPLIT MS2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.72105 |
| 585 | AirLoopHVAC:UnitarySystem | SPLIT MS2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.72105 |
| 586 | AirLoopHVAC:UnitarySystem | SPLIT MS2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.72105 |
| 587 | AirLoopHVAC:UnitarySystem | SPLIT MS2_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 11935.90587 |
| 588 | AirLoopHVAC:UnitarySystem | SPLIT MS2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 17821.82026 |
| 589 | AirLoopHVAC:UnitarySystem | SPLIT MS2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 590 | AirLoopHVAC:UnitarySystem | SPLIT MS2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 591 | Fan:OnOff | SPLIT MS2 SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.72105 |
| 592 | Coil:Cooling:DX:SingleSpeed | SPLIT MS2 COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.72105 |
| 593 | Coil:Cooling:DX:SingleSpeed | SPLIT MS2 COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 11935.90587 |
| 594 | Coil:Cooling:DX:SingleSpeed | SPLIT MS2 COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
| 595 | Coil:Heating:Fuel | SPLIT MS2 HEATING COIL | Design Size Nominal Capacity [W] | 17821.82026 |
| 596 | Controller:OutdoorAir | SPLIT TSW_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.47445 |
| 597 | Controller:OutdoorAir | SPLIT TSW_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.59546E-002 |
| 598 | AirLoopHVAC:UnitarySystem | SPLIT TSW_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.47445 |
| 599 | AirLoopHVAC:UnitarySystem | SPLIT TSW_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.47445 |
| 600 | AirLoopHVAC:UnitarySystem | SPLIT TSW_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.47445 |
| 601 | AirLoopHVAC:UnitarySystem | SPLIT TSW_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.47445 |
| 602 | AirLoopHVAC:UnitarySystem | SPLIT TSW_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 7853.87365 |
| 603 | AirLoopHVAC:UnitarySystem | SPLIT TSW_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 11479.85538 |
| 604 | AirLoopHVAC:UnitarySystem | SPLIT TSW_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 605 | AirLoopHVAC:UnitarySystem | SPLIT TSW_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 606 | Fan:OnOff | SPLIT TSW SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.47445 |
| 607 | Coil:Cooling:DX:SingleSpeed | SPLIT TSW COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.47445 |
| 608 | Coil:Cooling:DX:SingleSpeed | SPLIT TSW COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 7853.87365 |
| 609 | Coil:Cooling:DX:SingleSpeed | SPLIT TSW COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
| 610 | Coil:Heating:Fuel | SPLIT TSW HEATING COIL | Design Size Nominal Capacity [W] | 11479.85538 |
| 611 | Controller:OutdoorAir | SPLIT TNW_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.42975 |
| 612 | Controller:OutdoorAir | SPLIT TNW_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.59546E-002 |
| 613 | AirLoopHVAC:UnitarySystem | SPLIT TNW_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.42975 |
| 614 | AirLoopHVAC:UnitarySystem | SPLIT TNW_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.42975 |
| 615 | AirLoopHVAC:UnitarySystem | SPLIT TNW_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.42975 |
| 616 | AirLoopHVAC:UnitarySystem | SPLIT TNW_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.42975 |
| 617 | AirLoopHVAC:UnitarySystem | SPLIT TNW_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 7113.82740 |
| 618 | AirLoopHVAC:UnitarySystem | SPLIT TNW_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 10471.79111 |
| 619 | AirLoopHVAC:UnitarySystem | SPLIT TNW_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 620 | AirLoopHVAC:UnitarySystem | SPLIT TNW_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 621 | Fan:OnOff | SPLIT TNW SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.42975 |
| 622 | Coil:Cooling:DX:SingleSpeed | SPLIT TNW COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.42975 |
| 623 | Coil:Cooling:DX:SingleSpeed | SPLIT TNW COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 7113.82740 |
| 624 | Coil:Cooling:DX:SingleSpeed | SPLIT TNW COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
| 625 | Coil:Heating:Fuel | SPLIT TNW HEATING COIL | Design Size Nominal Capacity [W] | 10471.79111 |
| 626 | Controller:OutdoorAir | SPLIT TSE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.39352 |
| 627 | Controller:OutdoorAir | SPLIT TSE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.59546E-002 |
| 628 | AirLoopHVAC:UnitarySystem | SPLIT TSE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.39352 |
| 629 | AirLoopHVAC:UnitarySystem | SPLIT TSE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.39352 |
| 630 | AirLoopHVAC:UnitarySystem | SPLIT TSE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.39352 |
| 631 | AirLoopHVAC:UnitarySystem | SPLIT TSE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.39352 |
| 632 | AirLoopHVAC:UnitarySystem | SPLIT TSE_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 6514.17492 |
| 633 | AirLoopHVAC:UnitarySystem | SPLIT TSE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 9655.23492 |
| 634 | AirLoopHVAC:UnitarySystem | SPLIT TSE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 635 | AirLoopHVAC:UnitarySystem | SPLIT TSE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 636 | Fan:OnOff | SPLIT TSE SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.39352 |
| 637 | Coil:Cooling:DX:SingleSpeed | SPLIT TSE COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.39352 |
| 638 | Coil:Cooling:DX:SingleSpeed | SPLIT TSE COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 6514.17492 |
| 639 | Coil:Cooling:DX:SingleSpeed | SPLIT TSE COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
| 640 | Coil:Heating:Fuel | SPLIT TSE HEATING COIL | Design Size Nominal Capacity [W] | 9655.23492 |
| 641 | Controller:OutdoorAir | SPLIT TNE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.34939 |
| 642 | Controller:OutdoorAir | SPLIT TNE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.59546E-002 |
| 643 | AirLoopHVAC:UnitarySystem | SPLIT TNE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.34939 |
| 644 | AirLoopHVAC:UnitarySystem | SPLIT TNE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.34939 |
| 645 | AirLoopHVAC:UnitarySystem | SPLIT TNE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.34939 |
| 646 | AirLoopHVAC:UnitarySystem | SPLIT TNE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.34939 |
| 647 | AirLoopHVAC:UnitarySystem | SPLIT TNE_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 5783.70076 |
| 648 | AirLoopHVAC:UnitarySystem | SPLIT TNE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 8660.23701 |
| 649 | AirLoopHVAC:UnitarySystem | SPLIT TNE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 650 | AirLoopHVAC:UnitarySystem | SPLIT TNE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 651 | Fan:OnOff | SPLIT TNE SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.34939 |
| 652 | Coil:Cooling:DX:SingleSpeed | SPLIT TNE COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.34939 |
| 653 | Coil:Cooling:DX:SingleSpeed | SPLIT TNE COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 5783.70076 |
| 654 | Coil:Cooling:DX:SingleSpeed | SPLIT TNE COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
| 655 | Coil:Heating:Fuel | SPLIT TNE HEATING COIL | Design Size Nominal Capacity [W] | 8660.23701 |
| 656 | Controller:OutdoorAir | SPLIT TN1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.33276 |
| 657 | Controller:OutdoorAir | SPLIT TN1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.59546E-002 |
| 658 | AirLoopHVAC:UnitarySystem | SPLIT TN1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.33276 |
| 659 | AirLoopHVAC:UnitarySystem | SPLIT TN1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.33276 |
| 660 | AirLoopHVAC:UnitarySystem | SPLIT TN1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.33276 |
| 661 | AirLoopHVAC:UnitarySystem | SPLIT TN1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.33276 |
| 662 | AirLoopHVAC:UnitarySystem | SPLIT TN1_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 5508.35358 |
| 663 | AirLoopHVAC:UnitarySystem | SPLIT TN1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 8284.97831 |
| 664 | AirLoopHVAC:UnitarySystem | SPLIT TN1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 665 | AirLoopHVAC:UnitarySystem | SPLIT TN1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 666 | Fan:OnOff | SPLIT TN1 SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.33276 |
| 667 | Coil:Cooling:DX:SingleSpeed | SPLIT TN1 COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.33276 |
| 668 | Coil:Cooling:DX:SingleSpeed | SPLIT TN1 COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 5508.35358 |
| 669 | Coil:Cooling:DX:SingleSpeed | SPLIT TN1 COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
| 670 | Coil:Heating:Fuel | SPLIT TN1 HEATING COIL | Design Size Nominal Capacity [W] | 8284.97831 |
| 671 | Controller:OutdoorAir | SPLIT TN2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.33016 |
| 672 | Controller:OutdoorAir | SPLIT TN2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.59546E-002 |
| 673 | AirLoopHVAC:UnitarySystem | SPLIT TN2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.33016 |
| 674 | AirLoopHVAC:UnitarySystem | SPLIT TN2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.33016 |
| 675 | AirLoopHVAC:UnitarySystem | SPLIT TN2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.33016 |
| 676 | AirLoopHVAC:UnitarySystem | SPLIT TN2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.33016 |
| 677 | AirLoopHVAC:UnitarySystem | SPLIT TN2_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 5465.25569 |
| 678 | AirLoopHVAC:UnitarySystem | SPLIT TN2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 8226.28366 |
| 679 | AirLoopHVAC:UnitarySystem | SPLIT TN2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 680 | AirLoopHVAC:UnitarySystem | SPLIT TN2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 681 | Fan:OnOff | SPLIT TN2 SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.33016 |
| 682 | Coil:Cooling:DX:SingleSpeed | SPLIT TN2 COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.33016 |
| 683 | Coil:Cooling:DX:SingleSpeed | SPLIT TN2 COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 5465.25569 |
| 684 | Coil:Cooling:DX:SingleSpeed | SPLIT TN2 COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
| 685 | Coil:Heating:Fuel | SPLIT TN2 HEATING COIL | Design Size Nominal Capacity [W] | 8226.28366 |
| 686 | Controller:OutdoorAir | SPLIT TS1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.38029 |
| 687 | Controller:OutdoorAir | SPLIT TS1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.59546E-002 |
| 688 | AirLoopHVAC:UnitarySystem | SPLIT TS1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.38029 |
| 689 | AirLoopHVAC:UnitarySystem | SPLIT TS1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.38029 |
| 690 | AirLoopHVAC:UnitarySystem | SPLIT TS1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.38029 |
| 691 | AirLoopHVAC:UnitarySystem | SPLIT TS1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.38029 |
| 692 | AirLoopHVAC:UnitarySystem | SPLIT TS1_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 6295.20096 |
| 693 | AirLoopHVAC:UnitarySystem | SPLIT TS1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 9356.71633 |
| 694 | AirLoopHVAC:UnitarySystem | SPLIT TS1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 695 | AirLoopHVAC:UnitarySystem | SPLIT TS1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 696 | Fan:OnOff | SPLIT TS1 SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.38029 |
| 697 | Coil:Cooling:DX:SingleSpeed | SPLIT TS1 COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.38029 |
| 698 | Coil:Cooling:DX:SingleSpeed | SPLIT TS1 COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 6295.20096 |
| 699 | Coil:Cooling:DX:SingleSpeed | SPLIT TS1 COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
| 700 | Coil:Heating:Fuel | SPLIT TS1 HEATING COIL | Design Size Nominal Capacity [W] | 9356.71633 |
| 701 | Controller:OutdoorAir | SPLIT TS2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.37768 |
| 702 | Controller:OutdoorAir | SPLIT TS2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.59546E-002 |
| 703 | AirLoopHVAC:UnitarySystem | SPLIT TS2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.37768 |
| 704 | AirLoopHVAC:UnitarySystem | SPLIT TS2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.37768 |
| 705 | AirLoopHVAC:UnitarySystem | SPLIT TS2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.37768 |
| 706 | AirLoopHVAC:UnitarySystem | SPLIT TS2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.37768 |
| 707 | AirLoopHVAC:UnitarySystem | SPLIT TS2_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 6251.90910 |
| 708 | AirLoopHVAC:UnitarySystem | SPLIT TS2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 9297.75651 |
| 709 | AirLoopHVAC:UnitarySystem | SPLIT TS2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 710 | AirLoopHVAC:UnitarySystem | SPLIT TS2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 711 | Fan:OnOff | SPLIT TS2 SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.37768 |
| 712 | Coil:Cooling:DX:SingleSpeed | SPLIT TS2 COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.37768 |
| 713 | Coil:Cooling:DX:SingleSpeed | SPLIT TS2 COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 6251.90910 |
| 714 | Coil:Cooling:DX:SingleSpeed | SPLIT TS2 COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
| 715 | Coil:Heating:Fuel | SPLIT TS2 HEATING COIL | Design Size Nominal Capacity [W] | 9297.75651 |
| Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
| 1 | Coil:Cooling:DX:SingleSpeed | SPLIT GSW COOLING COIL | 5753.0 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 |
| 2 | Coil:Cooling:DX:SingleSpeed | SPLIT GNW COOLING COIL | 4827.6 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 |
| 3 | Coil:Cooling:DX:SingleSpeed | SPLIT OFFICE COOLING COIL | 6345.6 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 |
| 4 | Coil:Cooling:DX:SingleSpeed | SPLIT GNE COOLING COIL | 4239.1 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 |
| 5 | Coil:Cooling:DX:SingleSpeed | SPLIT GN1 COOLING COIL | 3866.7 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 |
| 6 | Coil:Cooling:DX:SingleSpeed | SPLIT GN2 COOLING COIL | 3855.8 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 |
| 7 | Coil:Cooling:DX:SingleSpeed | SPLIT GS1 COOLING COIL | 4865.0 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 |
| 8 | Coil:Cooling:DX:SingleSpeed | SPLIT GS2 COOLING COIL | 4889.6 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 |
| 9 | Coil:Cooling:DX:SingleSpeed | SPLIT MSW COOLING COIL | 13964.7 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 |
| 10 | Coil:Cooling:DX:SingleSpeed | SPLIT MNW COOLING COIL | 12230.0 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 |
| 11 | Coil:Cooling:DX:SingleSpeed | SPLIT MSE COOLING COIL | 12200.4 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 |
| 12 | Coil:Cooling:DX:SingleSpeed | SPLIT MNE COOLING COIL | 10509.1 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 |
| 13 | Coil:Cooling:DX:SingleSpeed | SPLIT MN1 COOLING COIL | 9509.2 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 |
| 14 | Coil:Cooling:DX:SingleSpeed | SPLIT MN2 COOLING COIL | 9479.2 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 |
| 15 | Coil:Cooling:DX:SingleSpeed | SPLIT MS1 COOLING COIL | 11404.9 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 |
| 16 | Coil:Cooling:DX:SingleSpeed | SPLIT MS2 COOLING COIL | 11370.8 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 |
| 17 | Coil:Cooling:DX:SingleSpeed | SPLIT TSW COOLING COIL | 7482.1 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 |
| 18 | Coil:Cooling:DX:SingleSpeed | SPLIT TNW COOLING COIL | 6777.0 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 |
| 19 | Coil:Cooling:DX:SingleSpeed | SPLIT TSE COOLING COIL | 6205.8 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 |
| 20 | Coil:Cooling:DX:SingleSpeed | SPLIT TNE COOLING COIL | 5509.9 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 |
| 21 | Coil:Cooling:DX:SingleSpeed | SPLIT TN1 COOLING COIL | 5247.6 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 |
| 22 | Coil:Cooling:DX:SingleSpeed | SPLIT TN2 COOLING COIL | 5206.5 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 |
| 23 | Coil:Cooling:DX:SingleSpeed | SPLIT TS1 COOLING COIL | 5997.2 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 |
| 24 | Coil:Cooling:DX:SingleSpeed | SPLIT TS2 COOLING COIL | 5955.9 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 |
| Zone Name | # Surfaces | |
| 1 | G SW APARTMENT | 9 |
| 2 | G NW APARTMENT | 9 |
| 3 | OFFICE | 9 |
| 4 | G NE APARTMENT | 9 |
| 5 | G N1 APARTMENT | 8 |
| 6 | G N2 APARTMENT | 8 |
| 7 | G S1 APARTMENT | 8 |
| 8 | G S2 APARTMENT | 8 |
| 9 | M SW APARTMENT | 9 |
| 10 | M NW APARTMENT | 9 |
| 11 | M SE APARTMENT | 9 |
| 12 | M NE APARTMENT | 9 |
| 13 | M N1 APARTMENT | 8 |
| 14 | M N2 APARTMENT | 8 |
| 15 | M S1 APARTMENT | 8 |
| 16 | M S2 APARTMENT | 8 |
| 17 | T SW APARTMENT | 9 |
| 18 | T NW APARTMENT | 9 |
| 19 | T SE APARTMENT | 9 |
| 20 | T NE APARTMENT | 9 |
| 21 | T N1 APARTMENT | 8 |
| 22 | T N2 APARTMENT | 8 |
| 23 | T S1 APARTMENT | 8 |
| 24 | T S2 APARTMENT | 8 |
| 25 | T CORRIDOR | 13 |
| 26 | G CORRIDOR | 13 |
| 27 | M CORRIDOR | 13 |
| Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
| 1 | G SWALL SWA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_GRD | 0.752 | 0.676 | 28.24 | 35.30 | 28.24 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 2 | GWINDOW1 S SWA | Window | G SWALL SWA | Window5 Detailed Fenestration | RESWINDOW_U_0.3972_SHGC_0.4 | N/A | 2.257 | No | 7.06 | 7.06 | 7.06 | 180.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 3 | G WWALL SWA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_GRD | 0.752 | 0.676 | 18.58 | 23.22 | 18.58 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 4 | GWINDOW1 W SWA | Window | G WWALL SWA | Window5 Detailed Fenestration | RESWINDOW_U_0.3972_SHGC_0.4 | N/A | 2.257 | No | 4.65 | 4.65 | 4.65 | 270.00 | 90.00 | 3.81 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 5 | G NIWALL SWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-G NIWALL SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 6 | G EIWALL SWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | iz-G EIWALL SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 7 | G GFLOOR SWA | Floor | CTF - ConductionTransferFunction | GGFLOORSWA_FFACTOR | 0.210 | 0.200 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 8 | G CEILIN SWA | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | G CEILIN SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 9 | G INTERNALMASS SWA | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 88.25 | 88.25 | 88.25 | 0.00 | 90.00 | 88.25 | 1.00 | 0.00 | G INTERNALMASS SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 10 | G NWALL NWA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_GRD | 0.752 | 0.676 | 28.24 | 35.30 | 28.24 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 11 | GWINDOW1 N NWA | Window | G NWALL NWA | Window5 Detailed Fenestration | RESWINDOW_U_0.3972_SHGC_0.4 | N/A | 2.257 | No | 7.06 | 7.06 | 7.06 | 0.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 12 | G WWALL NWA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_GRD | 0.752 | 0.676 | 18.58 | 23.22 | 18.58 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 13 | GWINDOW1 W NWA | Window | G WWALL NWA | Window5 Detailed Fenestration | RESWINDOW_U_0.3972_SHGC_0.4 | N/A | 2.257 | No | 4.65 | 4.65 | 4.65 | 270.00 | 90.00 | 3.81 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 14 | G SIWALL NWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-G SIWALL NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 15 | G EIWALL NWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | iz-G EIWALL NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 16 | G GFLOOR NWA | Floor | CTF - ConductionTransferFunction | GGFLOORNWA_FFACTOR | 0.210 | 0.200 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 17 | G CEILIN NWA | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | G CEILIN NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 18 | G INTERNALMASS NWA | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 88.25 | 88.25 | 88.25 | 0.00 | 90.00 | 88.25 | 1.00 | 0.00 | G INTERNALMASS NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 19 | G SWALL SEA | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.752 | 0.676 | 28.24 | 35.30 | 28.24 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 20 | GWINDOW1 S SEA | Window | G SWALL SEA | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3972_SHGC_0.4 | N/A | 2.257 | No | 7.06 | 7.06 | 7.06 | 180.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 21 | G EWALL SEA | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.752 | 0.676 | 18.58 | 23.22 | 18.58 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 22 | GWINDOW1 E SEA | Window | G EWALL SEA | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3972_SHGC_0.4 | N/A | 2.257 | No | 4.65 | 4.65 | 4.65 | 90.00 | 90.00 | 3.81 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 23 | G NIWALL SEA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-G NIWALL SEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 24 | iz-G EIWALL S2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | G EIWALL S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 25 | G GFLOOR SEA | Floor | CTF - ConductionTransferFunction | GGFLOORSEA_FFACTOR | 0.210 | 0.200 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 26 | G CEILIN SEA | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | G CEILIN SEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 27 | G INTERNALMASS SEA | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 88.25 | 88.25 | 88.25 | 0.00 | 90.00 | 88.25 | 1.00 | 0.00 | G INTERNALMASS SEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 28 | G NWALL NEA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_GRD | 0.752 | 0.676 | 28.24 | 35.30 | 28.24 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 29 | GWINDOW1 N NEA | Window | G NWALL NEA | Window5 Detailed Fenestration | RESWINDOW_U_0.3972_SHGC_0.4 | N/A | 2.257 | No | 7.06 | 7.06 | 7.06 | 0.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 30 | G EWALL NEA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_GRD | 0.752 | 0.676 | 18.58 | 23.22 | 18.58 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 31 | GWINDOW1 E NEA | Window | G EWALL NEA | Window5 Detailed Fenestration | RESWINDOW_U_0.3972_SHGC_0.4 | N/A | 2.257 | No | 4.65 | 4.65 | 4.65 | 90.00 | 90.00 | 3.81 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 32 | G SIWALL NEA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-G SIWALL NEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 33 | iz-G EIWALL N2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | G EIWALL N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 34 | G GFLOOR NEA | Floor | CTF - ConductionTransferFunction | GGFLOORNEA_FFACTOR | 0.210 | 0.200 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 35 | G CEILIN NEA | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | G CEILIN NEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 36 | G INTERNALMASS NEA | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 88.25 | 88.25 | 88.25 | 0.00 | 90.00 | 88.25 | 1.00 | 0.00 | G INTERNALMASS NEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 37 | G NWALL N1A | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_GRD | 0.752 | 0.676 | 28.24 | 35.30 | 28.24 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 38 | GWINDOW1 N N1A | Window | G NWALL N1A | Window5 Detailed Fenestration | RESWINDOW_U_0.3972_SHGC_0.4 | N/A | 2.257 | No | 7.06 | 7.06 | 7.06 | 0.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 39 | G SIWALL N1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-G SIWALL N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 40 | G EIWALL N1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | iz-G EIWALL N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 41 | iz-G EIWALL NWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | G EIWALL NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 42 | G GFLOOR N1A | Floor | CTF - ConductionTransferFunction | GGFLOORN1A_FFACTOR | 0.125 | 0.121 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 43 | G CEILIN N1A | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | G CEILIN N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 44 | G INTERNALMASS N1A | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 88.25 | 88.25 | 88.25 | 0.00 | 90.00 | 88.25 | 1.00 | 0.00 | G INTERNALMASS N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 45 | G NWALL N2A | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_GRD | 0.752 | 0.676 | 28.24 | 35.30 | 28.24 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 46 | GWINDOW1 N N2A | Window | G NWALL N2A | Window5 Detailed Fenestration | RESWINDOW_U_0.3972_SHGC_0.4 | N/A | 2.257 | No | 7.06 | 7.06 | 7.06 | 0.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 47 | G SIWALL N2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-G SIWALL N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 48 | G EIWALL N2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | iz-G EIWALL N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 49 | iz-G EIWALL N1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | G EIWALL N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 50 | G GFLOOR N2A | Floor | CTF - ConductionTransferFunction | GGFLOORN2A_FFACTOR | 0.125 | 0.121 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 51 | G CEILIN N2A | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | G CEILIN N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 52 | G INTERNALMASS N2A | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 88.25 | 88.25 | 88.25 | 0.00 | 90.00 | 88.25 | 1.00 | 0.00 | G INTERNALMASS N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 53 | G SWALL S1A | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_GRD | 0.752 | 0.676 | 28.24 | 35.30 | 28.24 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 54 | GWINDOW1 S S1A | Window | G SWALL S1A | Window5 Detailed Fenestration | RESWINDOW_U_0.3972_SHGC_0.4 | N/A | 2.257 | No | 7.06 | 7.06 | 7.06 | 180.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 55 | G NIWALL S1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-G NIWALL S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 56 | G EIWALL S1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | iz-G EIWALL S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 57 | iz-G EIWALL SWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | G EIWALL SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 58 | G GFLOOR S1A | Floor | CTF - ConductionTransferFunction | GGFLOORS1A_FFACTOR | 0.125 | 0.121 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 59 | G CEILIN S1A | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | G CEILIN S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 60 | G INTERNALMASS S1A | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 88.25 | 88.25 | 88.25 | 0.00 | 90.00 | 88.25 | 1.00 | 0.00 | G INTERNALMASS S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 61 | G SWALL S2A | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_GRD | 0.752 | 0.676 | 28.24 | 35.30 | 28.24 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 62 | GWINDOW1 S S2A | Window | G SWALL S2A | Window5 Detailed Fenestration | RESWINDOW_U_0.3972_SHGC_0.4 | N/A | 2.257 | No | 7.06 | 7.06 | 7.06 | 180.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 63 | G NIWALL S2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-G NIWALL S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 64 | G EIWALL S2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | iz-G EIWALL S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 65 | iz-G EIWALL S1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | G EIWALL S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 66 | G GFLOOR S2A | Floor | CTF - ConductionTransferFunction | GGFLOORS2A_FFACTOR | 0.125 | 0.121 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 67 | G CEILIN S2A | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | G CEILIN S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 68 | G INTERNALMASS S2A | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 88.25 | 88.25 | 88.25 | 0.00 | 90.00 | 88.25 | 1.00 | 0.00 | G INTERNALMASS S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 69 | M WWALL SWA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.761 | 0.683 | 18.58 | 23.22 | 18.58 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 70 | MWINDOW1 W SWA | Window | M WWALL SWA | Window5 Detailed Fenestration | RESWINDOW_U_0.3972_SHGC_0.4 | N/A | 2.257 | No | 4.65 | 4.65 | 4.65 | 270.00 | 90.00 | 3.81 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 71 | M SWALL SWA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.761 | 0.683 | 28.24 | 35.30 | 28.24 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 72 | MWINDOW1 S SWA | Window | M SWALL SWA | Window5 Detailed Fenestration | RESWINDOW_U_0.3972_SHGC_0.4 | N/A | 2.257 | No | 7.06 | 7.06 | 7.06 | 180.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 73 | M NIWALL SWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-M NIWALL SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 74 | M EIWALL SWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 90.00 | 90.00 | 3.05 | 7.62 | 0.00 | iz-M EIWALL SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 75 | M GFLOOR SWA | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | M GFLOOR SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 76 | M CEILIN SWA | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | M CEILIN SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 77 | M INTERNALMASS SWA | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 176.50 | 176.50 | 176.50 | 0.00 | 90.00 | 176.50 | 1.00 | 0.00 | M INTERNALMASS SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 78 | M NWALL NWA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.761 | 0.683 | 28.24 | 35.30 | 28.24 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 79 | MWINDOW1 N NWA | Window | M NWALL NWA | Window5 Detailed Fenestration | RESWINDOW_U_0.3972_SHGC_0.4 | N/A | 2.257 | No | 7.06 | 7.06 | 7.06 | 0.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 80 | M WWALL NWA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.761 | 0.683 | 18.58 | 23.22 | 18.58 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 81 | MWINDOW1 W NWA | Window | M WWALL NWA | Window5 Detailed Fenestration | RESWINDOW_U_0.3972_SHGC_0.4 | N/A | 2.257 | No | 4.65 | 4.65 | 4.65 | 270.00 | 90.00 | 3.81 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 82 | M SIWALL NWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-M SIWALL NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 83 | M EIWALL NWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | iz-M EIWALL NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 84 | M GFLOOR NWA | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | M GFLOOR NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 85 | M CEILIN NWA | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | M CEILIN NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 86 | M INTERNALMASS NWA | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 176.50 | 176.50 | 176.50 | 0.00 | 90.00 | 176.50 | 1.00 | 0.00 | M INTERNALMASS NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 87 | M EWALL SEA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.761 | 0.683 | 18.58 | 23.22 | 18.58 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 88 | MWINDOW1 E SEA | Window | M EWALL SEA | Window5 Detailed Fenestration | RESWINDOW_U_0.3972_SHGC_0.4 | N/A | 2.257 | No | 4.65 | 4.65 | 4.65 | 90.00 | 90.00 | 3.81 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 89 | M SWALL SEA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.761 | 0.683 | 28.24 | 35.30 | 28.24 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 90 | MWINDOW1 S SEA | Window | M SWALL SEA | Window5 Detailed Fenestration | RESWINDOW_U_0.3972_SHGC_0.4 | N/A | 2.257 | No | 7.06 | 7.06 | 7.06 | 180.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 91 | M NIWALL SEA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-M NIWALL SEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 92 | iz-M EIWALL S2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | M EIWALL S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 93 | M GFLOOR SEA | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | M GFLOOR SEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 94 | M CEILIN SEA | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | M CEILIN SEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 95 | M INTERNALMASS SEA | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 176.50 | 176.50 | 176.50 | 0.00 | 90.00 | 176.50 | 1.00 | 0.00 | M INTERNALMASS SEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 96 | M NWALL NEA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.761 | 0.683 | 28.24 | 35.30 | 28.24 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 97 | MWINDOW1 N NEA | Window | M NWALL NEA | Window5 Detailed Fenestration | RESWINDOW_U_0.3972_SHGC_0.4 | N/A | 2.257 | No | 7.06 | 7.06 | 7.06 | 0.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 98 | M EWALL NEA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.761 | 0.683 | 18.58 | 23.22 | 18.58 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 99 | MWINDOW1 E NEA | Window | M EWALL NEA | Window5 Detailed Fenestration | RESWINDOW_U_0.3972_SHGC_0.4 | N/A | 2.257 | No | 4.65 | 4.65 | 4.65 | 90.00 | 90.00 | 3.81 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 100 | M SIWALL NEA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-M SIWALL NEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 101 | iz-M EIWALL N2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | M EIWALL N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 102 | M GFLOOR NEA | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | M GFLOOR NEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 103 | M CEILIN NEA | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | M CEILIN NEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 104 | M INTERNALMASS NEA | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 176.50 | 176.50 | 176.50 | 0.00 | 90.00 | 176.50 | 1.00 | 0.00 | M INTERNALMASS NEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 105 | M NWALL N1A | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.761 | 0.683 | 28.24 | 35.30 | 28.24 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 106 | MWINDOW1 N N1A | Window | M NWALL N1A | Window5 Detailed Fenestration | RESWINDOW_U_0.3972_SHGC_0.4 | N/A | 2.257 | No | 7.06 | 7.06 | 7.06 | 0.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 107 | M SIWALL N1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-M SIWALL N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 108 | M EIWALL N1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | iz-M EIWALL N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 109 | iz-M EIWALL NWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | M EIWALL NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 110 | M GFLOOR N1A | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | M GFLOOR N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 111 | M CEILIN N1A | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | M CEILIN N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 112 | M INTERNALMASS N1A | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 176.50 | 176.50 | 176.50 | 0.00 | 90.00 | 176.50 | 1.00 | 0.00 | M INTERNALMASS N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 113 | M NWALL N2A | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.761 | 0.683 | 28.24 | 35.30 | 28.24 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 114 | MWINDOW1 N N2A | Window | M NWALL N2A | Window5 Detailed Fenestration | RESWINDOW_U_0.3972_SHGC_0.4 | N/A | 2.257 | No | 7.06 | 7.06 | 7.06 | 0.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 115 | M SIWALL N2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-M SIWALL N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 116 | M EIWALL N2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | iz-M EIWALL N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 117 | iz-M EIWALL N1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | M EIWALL N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 118 | M GFLOOR N2A | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | M GFLOOR N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 119 | M CEILIN N2A | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | M CEILIN N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 120 | M INTERNALMASS N2A | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 176.50 | 176.50 | 176.50 | 0.00 | 90.00 | 176.50 | 1.00 | 0.00 | M INTERNALMASS N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 121 | M SWALL S1A | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.761 | 0.683 | 28.24 | 35.30 | 28.24 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 122 | MWINDOW1 S S1A | Window | M SWALL S1A | Window5 Detailed Fenestration | RESWINDOW_U_0.3972_SHGC_0.4 | N/A | 2.257 | No | 7.06 | 7.06 | 7.06 | 180.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 123 | M NIWALL S1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-M NIWALL S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 124 | M EIWALL S1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | iz-M EIWALL S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 125 | iz-M EIWALL SWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 270.00 | 90.00 | 3.05 | 7.62 | 0.00 | M EIWALL SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 126 | M GFLOOR S1A | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | M GFLOOR S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 127 | M CEILIN S1A | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | M CEILIN S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 128 | M INTERNALMASS S1A | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 176.50 | 176.50 | 176.50 | 0.00 | 90.00 | 176.50 | 1.00 | 0.00 | M INTERNALMASS S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 129 | M SWALL S2A | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.761 | 0.683 | 28.24 | 35.30 | 28.24 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 130 | MWINDOW1 S S2A | Window | M SWALL S2A | Window5 Detailed Fenestration | RESWINDOW_U_0.3972_SHGC_0.4 | N/A | 2.257 | No | 7.06 | 7.06 | 7.06 | 180.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 131 | M NIWALL S2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-M NIWALL S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 132 | M EIWALL S2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | iz-M EIWALL S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 133 | iz-M EIWALL S1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | M EIWALL S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 134 | M GFLOOR S2A | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | M GFLOOR S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 135 | M CEILIN S2A | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | M CEILIN S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 136 | M INTERNALMASS S2A | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 176.50 | 176.50 | 176.50 | 0.00 | 90.00 | 176.50 | 1.00 | 0.00 | M INTERNALMASS S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 137 | T WWALL SWA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.098 | 0.943 | 18.58 | 23.22 | 18.58 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 138 | TWINDOW1 W SWA | Window | T WWALL SWA | Window5 Detailed Fenestration | RESWINDOW_U_0.3972_SHGC_0.4 | N/A | 2.257 | No | 4.65 | 4.65 | 4.65 | 270.00 | 90.00 | 3.81 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 139 | T SWALL SWA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.098 | 0.943 | 28.24 | 35.30 | 28.24 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 140 | TWINDOW1 S SWA | Window | T SWALL SWA | Window5 Detailed Fenestration | RESWINDOW_U_0.3972_SHGC_0.4 | N/A | 2.257 | No | 7.06 | 7.06 | 7.06 | 180.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 141 | T NIWALL SWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-T NIWALL SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 142 | T EIWALL SWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | iz-T EIWALL SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 143 | T GFLOOR SWA | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | T GFLOOR SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 144 | T ROOF SWA | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.228 | 0.219 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 145 | T INTERNALMASS SWA | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 88.25 | 88.25 | 88.25 | 0.00 | 90.00 | 88.25 | 1.00 | 0.00 | T INTERNALMASS SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 146 | T NWALL NWA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.098 | 0.943 | 28.24 | 35.30 | 28.24 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 147 | TWINDOW1 N NWA | Window | T NWALL NWA | Window5 Detailed Fenestration | RESWINDOW_U_0.3972_SHGC_0.4 | N/A | 2.257 | No | 7.06 | 7.06 | 7.06 | 0.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 148 | T WWALL NWA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.098 | 0.943 | 18.58 | 23.22 | 18.58 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 149 | TWINDOW1 W NWA | Window | T WWALL NWA | Window5 Detailed Fenestration | RESWINDOW_U_0.3972_SHGC_0.4 | N/A | 2.257 | No | 4.65 | 4.65 | 4.65 | 270.00 | 90.00 | 3.81 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 150 | T SIWALL NWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-T SIWALL NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 151 | T EIWALL NWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | iz-T EIWALL NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 152 | T GFLOOR NWA | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | T GFLOOR NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 153 | T ROOF NWA | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.228 | 0.219 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 154 | T INTERNALMASS NWA | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 88.25 | 88.25 | 88.25 | 0.00 | 90.00 | 88.25 | 1.00 | 0.00 | T INTERNALMASS NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 155 | T EWALL SEA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.098 | 0.943 | 18.58 | 23.22 | 18.58 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 156 | TWINDOW1 E SEA | Window | T EWALL SEA | Window5 Detailed Fenestration | RESWINDOW_U_0.3972_SHGC_0.4 | N/A | 2.257 | No | 4.65 | 4.65 | 4.65 | 90.00 | 90.00 | 3.81 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 157 | T SWALL SEA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.098 | 0.943 | 28.24 | 35.30 | 28.24 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 158 | TWINDOW1 S SEA | Window | T SWALL SEA | Window5 Detailed Fenestration | RESWINDOW_U_0.3972_SHGC_0.4 | N/A | 2.257 | No | 7.06 | 7.06 | 7.06 | 180.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 159 | T NIWALL SEA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-T NIWALL SEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 160 | iz-T EIWALL S2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | T EIWALL S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 161 | T GFLOOR SEA | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | T GFLOOR SEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 162 | T ROOF SEA | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.228 | 0.219 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 163 | T INTERNALMASS SEA | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 88.25 | 88.25 | 88.25 | 0.00 | 90.00 | 88.25 | 1.00 | 0.00 | T INTERNALMASS SEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 164 | T NWALL NEA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.098 | 0.943 | 28.24 | 35.30 | 28.24 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 165 | TWINDOW1 N NEA | Window | T NWALL NEA | Window5 Detailed Fenestration | RESWINDOW_U_0.3972_SHGC_0.4 | N/A | 2.257 | No | 7.06 | 7.06 | 7.06 | 0.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 166 | T EWALL NEA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.098 | 0.943 | 18.58 | 23.22 | 18.58 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 167 | TWINDOW1 E NEA | Window | T EWALL NEA | Window5 Detailed Fenestration | RESWINDOW_U_0.3972_SHGC_0.4 | N/A | 2.257 | No | 4.65 | 4.65 | 4.65 | 90.00 | 90.00 | 3.81 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 168 | T SIWALL NEA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-T SIWALL NEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 169 | iz-T EIWALL N2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | T EIWALL N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 170 | T GFLOOR NEA | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | T GFLOOR NEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 171 | T ROOF NEA | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.228 | 0.219 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 172 | T INTERNALMASS NEA | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 88.25 | 88.25 | 88.25 | 0.00 | 90.00 | 88.25 | 1.00 | 0.00 | T INTERNALMASS NEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 173 | T NWALL N1A | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.098 | 0.943 | 28.24 | 35.30 | 28.24 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 174 | TWINDOW1 N N1A | Window | T NWALL N1A | Window5 Detailed Fenestration | RESWINDOW_U_0.3972_SHGC_0.4 | N/A | 2.257 | No | 7.06 | 7.06 | 7.06 | 0.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 175 | T SIWALL N1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-T SIWALL N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 176 | T EIWALL N1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | iz-T EIWALL N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 177 | iz-T EIWALL NWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | T EIWALL NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 178 | T GFLOOR N1A | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | T GFLOOR N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 179 | T ROOF N1A | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.228 | 0.219 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 180 | T INTERNALMASS N1A | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 88.25 | 88.25 | 88.25 | 0.00 | 90.00 | 88.25 | 1.00 | 0.00 | T INTERNALMASS N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 181 | T NWALL N2A | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.098 | 0.943 | 28.24 | 35.30 | 28.24 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 182 | TWINDOW1 N N2A | Window | T NWALL N2A | Window5 Detailed Fenestration | RESWINDOW_U_0.3972_SHGC_0.4 | N/A | 2.257 | No | 7.06 | 7.06 | 7.06 | 0.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 183 | T SIWALL N2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-T SIWALL N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 184 | T EIWALL N2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | iz-T EIWALL N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 185 | iz-T EIWALL N1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | T EIWALL N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 186 | T GFLOOR N2A | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | T GFLOOR N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 187 | T ROOF N2A | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.228 | 0.219 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 188 | T INTERNALMASS N2A | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 88.25 | 88.25 | 88.25 | 0.00 | 90.00 | 88.25 | 1.00 | 0.00 | T INTERNALMASS N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 189 | T SWALL S1A | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.098 | 0.943 | 28.24 | 35.30 | 28.24 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 190 | TWINDOW1 S S1A | Window | T SWALL S1A | Window5 Detailed Fenestration | RESWINDOW_U_0.3972_SHGC_0.4 | N/A | 2.257 | No | 7.06 | 7.06 | 7.06 | 180.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 191 | T NIWALL S1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-T NIWALL S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 192 | T EIWALL S1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | iz-T EIWALL S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 193 | iz-T EIWALL SWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | T EIWALL SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 194 | T GFLOOR S1A | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | T GFLOOR S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 195 | T ROOF S1A | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.228 | 0.219 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 196 | T INTERNALMASS S1A | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 88.25 | 88.25 | 88.25 | 0.00 | 90.00 | 88.25 | 1.00 | 0.00 | T INTERNALMASS S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 197 | T SWALL S2A | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.098 | 0.943 | 28.24 | 35.30 | 28.24 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 198 | TWINDOW1 S S2A | Window | T SWALL S2A | Window5 Detailed Fenestration | RESWINDOW_U_0.3972_SHGC_0.4 | N/A | 2.257 | No | 7.06 | 7.06 | 7.06 | 180.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 199 | T NIWALL S2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-T NIWALL S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 200 | T EIWALL S2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | iz-T EIWALL S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 201 | iz-T EIWALL S1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | T EIWALL S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 202 | T GFLOOR S2A | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | T GFLOOR S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 203 | T ROOF S2A | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.228 | 0.219 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 204 | T INTERNALMASS S2A | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 88.25 | 88.25 | 88.25 | 0.00 | 90.00 | 88.25 | 1.00 | 0.00 | T INTERNALMASS S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 205 | T WWALL C | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.098 | 0.943 | 5.11 | 5.11 | 5.11 | 270.00 | 90.00 | 1.68 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 206 | T EWALL C | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.098 | 0.943 | 3.99 | 5.11 | 3.99 | 90.00 | 90.00 | 1.68 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 207 | TWINDOW14 | Window | T EWALL C | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3972_SHGC_0.4 | N/A | 2.257 | No | 1.11 | 1.11 | 1.11 | 90.00 | 90.00 | 0.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 208 | iz-T NIWALL SWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | T NIWALL SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 209 | iz-T NIWALL S1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | T NIWALL S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 210 | iz-T NIWALL S2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | T NIWALL S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 211 | iz-T NIWALL SEA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | T NIWALL SEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 212 | iz-T SIWALL NWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | T SIWALL NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 213 | iz-T SIWALL N1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | T SIWALL N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 214 | iz-T SIWALL N2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | T SIWALL N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 215 | iz-T SIWALL NEA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | T SIWALL NEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 216 | T FLOOR C | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 77.66 | 77.66 | 77.66 | 90.00 | 180.00 | 1.68 | 46.33 | 0.00 | T FLOOR C | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 217 | T ROOF C | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 77.66 | 77.66 | 77.66 | 180.00 | 0.00 | 46.33 | 1.68 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 218 | G WWALL C | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.752 | 0.676 | 5.11 | 5.11 | 5.11 | 270.00 | 90.00 | 1.68 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 219 | G EWALL C | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.752 | 0.676 | 1.79 | 5.11 | 1.79 | 90.00 | 90.00 | 1.68 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 220 | ENTRANCE DOOR | Window | G EWALL C | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3972_SHGC_0.4 | N/A | 2.257 | No | 3.32 | 3.32 | 3.32 | 90.00 | 90.00 | 1.57 | 2.11 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 221 | iz-G NIWALL SWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | G NIWALL SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 222 | iz-G NIWALL S1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | G NIWALL S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 223 | iz-G NIWALL S2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | G NIWALL S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 224 | iz-G NIWALL SEA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | G NIWALL SEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 225 | iz-G SIWALL NWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | G SIWALL NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 226 | iz-G SIWALL N1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | G SIWALL N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 227 | iz-G SIWALL N2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | G SIWALL N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 228 | iz-G SIWALL NEA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | G SIWALL NEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 229 | G FLOOR C | Floor | CTF - ConductionTransferFunction | GFLOORC_FFACTOR | 4.061E-002 | 4.021E-002 | 77.66 | 77.66 | 77.66 | 90.00 | 180.00 | 1.68 | 46.33 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 230 | G CEILING C | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 77.66 | 77.66 | 77.66 | 180.00 | 0.00 | 46.33 | 1.68 | 0.00 | G CEILING C | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 231 | M WWALL C | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.761 | 0.683 | 5.11 | 5.11 | 5.11 | 270.00 | 90.00 | 1.68 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 232 | M EWALL C | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.761 | 0.683 | 3.99 | 5.11 | 3.99 | 90.00 | 90.00 | 1.68 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 233 | MWINDOW14 | Window | M EWALL C | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3972_SHGC_0.4 | N/A | 2.257 | No | 1.11 | 1.11 | 1.11 | 90.00 | 90.00 | 0.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 234 | iz-M NIWALL SWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | M NIWALL SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 235 | iz-M NIWALL S1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | M NIWALL S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 236 | iz-M NIWALL S2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | M NIWALL S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 237 | iz-M NIWALL SEA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | M NIWALL SEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 238 | iz-M SIWALL NWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | M SIWALL NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 239 | iz-M SIWALL N1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | M SIWALL N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 240 | iz-M SIWALL N2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | M SIWALL N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 241 | iz-M SIWALL NEA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | M SIWALL NEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 242 | M FLOOR C | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 77.66 | 77.66 | 77.66 | 90.00 | 180.00 | 1.68 | 46.33 | 0.00 | M FLOOR C | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 243 | M CEILING C | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 77.66 | 77.66 | 77.66 | 180.00 | 0.00 | 46.33 | 1.68 | 0.00 | M CEILING C | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
| Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
| 1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | Yes | Yes | Yes | Clark and Allen |
| Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
| 1 | NEW YEAR'S DAY | Holiday | InputFile | 01/02 | 1Environment:Special Days |
| Daylight Saving Indicator | Source | Start Date | End Date | |
| 1 | Yes | InputFile | 03/12 | 11/05 |
| Style | Unit Conversion | |
| 1 | Commaandhtml | commaandhtml |
| Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
| 1 | G SW APARTMENT | RunPeriod: RUNPERIOD 1 | 6.1860298316E-008 | 3.3404280082E-007 | Pass | Pass | 2.7382771245E-002 | 3.2394051172E-002 | Pass | Pass |
| 2 | G NW APARTMENT | RunPeriod: RUNPERIOD 1 | 4.3437982372E-008 | 2.4359936472E-007 | Pass | Pass | 2.3341057586E-002 | 2.6931967678E-002 | Pass | Pass |
| 3 | OFFICE | RunPeriod: RUNPERIOD 1 | 1.5163943842E-002 | 1.2111288071E-002 | Pass | Pass | 0.3232105524 | 0.9614998490 | Pass | Pass |
| 4 | G NE APARTMENT | RunPeriod: RUNPERIOD 1 | 4.3137000688E-008 | 2.4221042209E-007 | Pass | Pass | 2.3689761157E-002 | 2.7332206443E-002 | Pass | Pass |
| 5 | G N1 APARTMENT | RunPeriod: RUNPERIOD 1 | 9.4059749619E-009 | 6.1898944942E-008 | Pass | Pass | 0.3128175457 | 2.3847848788 | Pass | Pass |
| 6 | G N2 APARTMENT | RunPeriod: RUNPERIOD 1 | 9.3945315724E-009 | 6.1847299571E-008 | Pass | Pass | 0.2837611481 | 2.2676204407 | Pass | Pass |
| 7 | G S1 APARTMENT | RunPeriod: RUNPERIOD 1 | 1.5512686814E-008 | 8.6869319609E-008 | Pass | Pass | 0.2960836791 | 0.8214877271 | Pass | Pass |
| 8 | G S2 APARTMENT | RunPeriod: RUNPERIOD 1 | 3.3407703394E-008 | 1.8341653585E-007 | Pass | Pass | 4.2414160039E-002 | 8.5997103811E-002 | Pass | Pass |
| 9 | M SW APARTMENT | RunPeriod: RUNPERIOD 1 | 3.0985736841E-008 | 1.6842874344E-007 | Pass | Pass | 0.8966268634 | 7.7263008025 | Pass | Pass |
| 10 | M NW APARTMENT | RunPeriod: RUNPERIOD 1 | 2.1880441409E-008 | 1.4092633899E-007 | Pass | Pass | 0.1683579293 | 0.8213951941 | Pass | Pass |
| 11 | M SE APARTMENT | RunPeriod: RUNPERIOD 1 | 3.0500943105E-008 | 1.6592300010E-007 | Pass | Pass | 0.3653190685 | 1.1084638894 | Pass | Pass |
| 12 | M NE APARTMENT | RunPeriod: RUNPERIOD 1 | 2.1530245858E-008 | 1.3939289584E-007 | Pass | Pass | 0.1544386024 | 0.5862744343 | Pass | Pass |
| 13 | M N1 APARTMENT | RunPeriod: RUNPERIOD 1 | 1.1710229922E-008 | 6.8435264526E-008 | Pass | Pass | 0.3019030426 | 0.7929798236 | Pass | Pass |
| 14 | M N2 APARTMENT | RunPeriod: RUNPERIOD 1 | 1.1725621733E-008 | 6.8506535073E-008 | Pass | Pass | 0.3061755153 | 0.8370005741 | Pass | Pass |
| 15 | M S1 APARTMENT | RunPeriod: RUNPERIOD 1 | 1.5892801421E-008 | 8.4134723531E-008 | Pass | Pass | 0.2693384049 | 0.7946119671 | Pass | Pass |
| 16 | M S2 APARTMENT | RunPeriod: RUNPERIOD 1 | 1.5916137124E-008 | 8.4251494756E-008 | Pass | Pass | 0.2657670669 | 0.7473121801 | Pass | Pass |
| 17 | T SW APARTMENT | RunPeriod: RUNPERIOD 1 | 1.1303139597E-007 | 6.1125667180E-007 | Pass | Pass | 2.9046862262E-002 | 2.3910199124E-002 | Pass | Pass |
| 18 | T NW APARTMENT | RunPeriod: RUNPERIOD 1 | 7.9701025236E-008 | 4.7738523927E-007 | Pass | Pass | 2.4986304631E-002 | 2.0434908571E-002 | Pass | Pass |
| 19 | T SE APARTMENT | RunPeriod: RUNPERIOD 1 | 1.1241719084E-007 | 6.0816067576E-007 | Pass | Pass | 2.9641596602E-002 | 2.4593399752E-002 | Pass | Pass |
| 20 | T NE APARTMENT | RunPeriod: RUNPERIOD 1 | 7.9222455633E-008 | 4.7547456151E-007 | Pass | Pass | 2.5420658295E-002 | 2.0933946014E-002 | Pass | Pass |
| 21 | T N1 APARTMENT | RunPeriod: RUNPERIOD 1 | 3.6202087254E-008 | 2.1949493606E-007 | Pass | Pass | 3.9260951825E-002 | 4.5120297248E-002 | Pass | Pass |
| 22 | T N2 APARTMENT | RunPeriod: RUNPERIOD 1 | 3.6185980484E-008 | 2.1942547904E-007 | Pass | Pass | 3.9305264882E-002 | 4.5180938636E-002 | Pass | Pass |
| 23 | T S1 APARTMENT | RunPeriod: RUNPERIOD 1 | 5.4131785104E-008 | 2.9577290270E-007 | Pass | Pass | 5.4967408973E-002 | 6.5285004106E-002 | Pass | Pass |
| 24 | T S2 APARTMENT | RunPeriod: RUNPERIOD 1 | 5.4112139140E-008 | 2.9567442603E-007 | Pass | Pass | 5.5066361778E-002 | 6.5423995511E-002 | Pass | Pass |
| 25 | T CORRIDOR | RunPeriod: RUNPERIOD 1 | 6.4520325052E-003 | 4.4766183419E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
| 26 | G CORRIDOR | RunPeriod: RUNPERIOD 1 | 0.1557896906 | 0.4909662218 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
| 27 | M CORRIDOR | RunPeriod: RUNPERIOD 1 | 4.2382454926E-003 | 3.0524959716E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 09:15:24
Heat Emission by Components| Envelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
| Heat Emissions [GJ] | 1625.66 | 143.41 | 0.00 | 16.56 | 301.26 | 2086.89 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 09:15:24
SizingPeriod:DesignDay| Maximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
| SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | -4.20 | 0.00 | -4.20 | Wetbulb [C] | 4.30 | 20.00 |
| SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 29.40 | 10.40 | 18.30 | Wetbulb [C] | 4.20 | 350.00 |
| Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
| Jan | 0.00 | 0 | |||
| Feb | 0.00 | 0 | |||
| Mar | 22.00 | 23 | |||
| Apr | 0.00 | 0 | |||
| May | 0.00 | 0 | |||
| Jun | 16.00 | 20 | |||
| Jul | 0.00 | 0 | |||
| Aug | 24.00 | 18 | |||
| Sep | 12.00 | 15 | |||
| Oct | 61.00 | 41 | |||
| Nov | 0.00 | 0 | |||
| Dec | 45.00 | 41 |
| Value | |
| None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 09:15:24
Opaque Exterior| Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
| G SWALL SWA | RES_EXT_WALL_GRD | 0.30 | 0.676 | 0.752 | 35.30 | 28.24 | 180.00 | 90.00 | S |
| G WWALL SWA | RES_EXT_WALL_GRD | 0.30 | 0.676 | 0.752 | 23.22 | 18.58 | 270.00 | 90.00 | W |
| G GFLOOR SWA | GGFLOORSWA_FFACTOR | 1.00 | 0.203 | 0.210 | 88.25 | 88.25 | 90.00 | 180.00 | |
| G NWALL NWA | RES_EXT_WALL_GRD | 0.30 | 0.676 | 0.752 | 35.30 | 28.24 | 0.00 | 90.00 | N |
| G WWALL NWA | RES_EXT_WALL_GRD | 0.30 | 0.676 | 0.752 | 23.22 | 18.58 | 270.00 | 90.00 | W |
| G GFLOOR NWA | GGFLOORNWA_FFACTOR | 1.00 | 0.203 | 0.210 | 88.25 | 88.25 | 90.00 | 180.00 | |
| G SWALL SEA | NONRES_EXT_WALL_GRD | 0.30 | 0.676 | 0.752 | 35.30 | 28.24 | 180.00 | 90.00 | S |
| G EWALL SEA | NONRES_EXT_WALL_GRD | 0.30 | 0.676 | 0.752 | 23.22 | 18.58 | 90.00 | 90.00 | E |
| G GFLOOR SEA | GGFLOORSEA_FFACTOR | 1.00 | 0.203 | 0.210 | 88.25 | 88.25 | 90.00 | 180.00 | |
| G NWALL NEA | RES_EXT_WALL_GRD | 0.30 | 0.676 | 0.752 | 35.30 | 28.24 | 0.00 | 90.00 | N |
| G EWALL NEA | RES_EXT_WALL_GRD | 0.30 | 0.676 | 0.752 | 23.22 | 18.58 | 90.00 | 90.00 | E |
| G GFLOOR NEA | GGFLOORNEA_FFACTOR | 1.00 | 0.203 | 0.210 | 88.25 | 88.25 | 90.00 | 180.00 | |
| G NWALL N1A | RES_EXT_WALL_GRD | 0.30 | 0.676 | 0.752 | 35.30 | 28.24 | 0.00 | 90.00 | N |
| G GFLOOR N1A | GGFLOORN1A_FFACTOR | 1.00 | 0.123 | 0.125 | 88.25 | 88.25 | 90.00 | 180.00 | |
| G NWALL N2A | RES_EXT_WALL_GRD | 0.30 | 0.676 | 0.752 | 35.30 | 28.24 | 0.00 | 90.00 | N |
| G GFLOOR N2A | GGFLOORN2A_FFACTOR | 1.00 | 0.123 | 0.125 | 88.25 | 88.25 | 90.00 | 180.00 | |
| G SWALL S1A | RES_EXT_WALL_GRD | 0.30 | 0.676 | 0.752 | 35.30 | 28.24 | 180.00 | 90.00 | S |
| G GFLOOR S1A | GGFLOORS1A_FFACTOR | 1.00 | 0.123 | 0.125 | 88.25 | 88.25 | 90.00 | 180.00 | |
| G SWALL S2A | RES_EXT_WALL_GRD | 0.30 | 0.676 | 0.752 | 35.30 | 28.24 | 180.00 | 90.00 | S |
| G GFLOOR S2A | GGFLOORS2A_FFACTOR | 1.00 | 0.123 | 0.125 | 88.25 | 88.25 | 90.00 | 180.00 | |
| M WWALL SWA | RES_EXT_WALL_MID | 0.30 | 0.683 | 0.761 | 46.45 | 37.16 | 270.00 | 90.00 | W |
| M SWALL SWA | RES_EXT_WALL_MID | 0.30 | 0.683 | 0.761 | 70.60 | 56.48 | 180.00 | 90.00 | S |
| M NWALL NWA | RES_EXT_WALL_MID | 0.30 | 0.683 | 0.761 | 70.60 | 56.48 | 0.00 | 90.00 | N |
| M WWALL NWA | RES_EXT_WALL_MID | 0.30 | 0.683 | 0.761 | 46.45 | 37.16 | 270.00 | 90.00 | W |
| M EWALL SEA | RES_EXT_WALL_MID | 0.30 | 0.683 | 0.761 | 46.45 | 37.16 | 90.00 | 90.00 | E |
| M SWALL SEA | RES_EXT_WALL_MID | 0.30 | 0.683 | 0.761 | 70.60 | 56.48 | 180.00 | 90.00 | S |
| M NWALL NEA | RES_EXT_WALL_MID | 0.30 | 0.683 | 0.761 | 70.60 | 56.48 | 0.00 | 90.00 | N |
| M EWALL NEA | RES_EXT_WALL_MID | 0.30 | 0.683 | 0.761 | 46.45 | 37.16 | 90.00 | 90.00 | E |
| M NWALL N1A | RES_EXT_WALL_MID | 0.30 | 0.683 | 0.761 | 70.60 | 56.48 | 0.00 | 90.00 | N |
| M NWALL N2A | RES_EXT_WALL_MID | 0.30 | 0.683 | 0.761 | 70.60 | 56.48 | 0.00 | 90.00 | N |
| M SWALL S1A | RES_EXT_WALL_MID | 0.30 | 0.683 | 0.761 | 70.60 | 56.48 | 180.00 | 90.00 | S |
| M SWALL S2A | RES_EXT_WALL_MID | 0.30 | 0.683 | 0.761 | 70.60 | 56.48 | 180.00 | 90.00 | S |
| T WWALL SWA | RES_EXT_WALL_TOP | 0.30 | 0.943 | 1.098 | 23.22 | 18.58 | 270.00 | 90.00 | W |
| T SWALL SWA | RES_EXT_WALL_TOP | 0.30 | 0.943 | 1.098 | 35.30 | 28.24 | 180.00 | 90.00 | S |
| T ROOF SWA | RES_ROOF | 0.30 | 0.221 | 0.228 | 88.25 | 88.25 | 180.00 | 0.00 | |
| T NWALL NWA | RES_EXT_WALL_TOP | 0.30 | 0.943 | 1.098 | 35.30 | 28.24 | 0.00 | 90.00 | N |
| T WWALL NWA | RES_EXT_WALL_TOP | 0.30 | 0.943 | 1.098 | 23.22 | 18.58 | 270.00 | 90.00 | W |
| T ROOF NWA | RES_ROOF | 0.30 | 0.221 | 0.228 | 88.25 | 88.25 | 180.00 | 0.00 | |
| T EWALL SEA | RES_EXT_WALL_TOP | 0.30 | 0.943 | 1.098 | 23.22 | 18.58 | 90.00 | 90.00 | E |
| T SWALL SEA | RES_EXT_WALL_TOP | 0.30 | 0.943 | 1.098 | 35.30 | 28.24 | 180.00 | 90.00 | S |
| T ROOF SEA | RES_ROOF | 0.30 | 0.221 | 0.228 | 88.25 | 88.25 | 180.00 | 0.00 | |
| T NWALL NEA | RES_EXT_WALL_TOP | 0.30 | 0.943 | 1.098 | 35.30 | 28.24 | 0.00 | 90.00 | N |
| T EWALL NEA | RES_EXT_WALL_TOP | 0.30 | 0.943 | 1.098 | 23.22 | 18.58 | 90.00 | 90.00 | E |
| T ROOF NEA | RES_ROOF | 0.30 | 0.221 | 0.228 | 88.25 | 88.25 | 180.00 | 0.00 | |
| T NWALL N1A | RES_EXT_WALL_TOP | 0.30 | 0.943 | 1.098 | 35.30 | 28.24 | 0.00 | 90.00 | N |
| T ROOF N1A | RES_ROOF | 0.30 | 0.221 | 0.228 | 88.25 | 88.25 | 180.00 | 0.00 | |
| T NWALL N2A | RES_EXT_WALL_TOP | 0.30 | 0.943 | 1.098 | 35.30 | 28.24 | 0.00 | 90.00 | N |
| T ROOF N2A | RES_ROOF | 0.30 | 0.221 | 0.228 | 88.25 | 88.25 | 180.00 | 0.00 | |
| T SWALL S1A | RES_EXT_WALL_TOP | 0.30 | 0.943 | 1.098 | 35.30 | 28.24 | 180.00 | 90.00 | S |
| T ROOF S1A | RES_ROOF | 0.30 | 0.221 | 0.228 | 88.25 | 88.25 | 180.00 | 0.00 | |
| T SWALL S2A | RES_EXT_WALL_TOP | 0.30 | 0.943 | 1.098 | 35.30 | 28.24 | 180.00 | 90.00 | S |
| T ROOF S2A | RES_ROOF | 0.30 | 0.221 | 0.228 | 88.25 | 88.25 | 180.00 | 0.00 | |
| T WWALL C | NONRES_EXT_WALL_TOP | 0.30 | 0.943 | 1.098 | 5.11 | 5.11 | 270.00 | 90.00 | W |
| T EWALL C | NONRES_EXT_WALL_TOP | 0.30 | 0.943 | 1.098 | 5.11 | 3.99 | 90.00 | 90.00 | E |
| T ROOF C | NONRES_ROOF | 0.30 | 0.221 | 0.228 | 77.66 | 77.66 | 180.00 | 0.00 | |
| G WWALL C | NONRES_EXT_WALL_GRD | 0.30 | 0.676 | 0.752 | 5.11 | 5.11 | 270.00 | 90.00 | W |
| G EWALL C | NONRES_EXT_WALL_GRD | 0.30 | 0.676 | 0.752 | 5.11 | 1.79 | 90.00 | 90.00 | E |
| G FLOOR C | GFLOORC_FFACTOR | 1.00 | 0.040 | 0.041 | 77.66 | 77.66 | 90.00 | 180.00 | |
| M WWALL C | NONRES_EXT_WALL_MID | 0.30 | 0.683 | 0.761 | 10.22 | 10.22 | 270.00 | 90.00 | W |
| M EWALL C | NONRES_EXT_WALL_MID | 0.30 | 0.683 | 0.761 | 10.22 | 7.99 | 90.00 | 90.00 | E |
| Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
| G NIWALL SWA | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 0.00 | 90.00 | N |
| G EIWALL SWA | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 90.00 | 90.00 | E |
| G CEILIN SWA | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 88.25 | 88.25 | 180.00 | 0.00 | |
| G SIWALL NWA | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 180.00 | 90.00 | S |
| G EIWALL NWA | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 90.00 | 90.00 | E |
| G CEILIN NWA | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 88.25 | 88.25 | 180.00 | 0.00 | |
| G NIWALL SEA | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 0.00 | 90.00 | N |
| iz-G EIWALL S2A | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 270.00 | 90.00 | W |
| G CEILIN SEA | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 88.25 | 88.25 | 180.00 | 0.00 | |
| G SIWALL NEA | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 180.00 | 90.00 | S |
| iz-G EIWALL N2A | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 270.00 | 90.00 | W |
| G CEILIN NEA | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 88.25 | 88.25 | 180.00 | 0.00 | |
| G SIWALL N1A | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 180.00 | 90.00 | S |
| G EIWALL N1A | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 90.00 | 90.00 | E |
| iz-G EIWALL NWA | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 270.00 | 90.00 | W |
| G CEILIN N1A | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 88.25 | 88.25 | 180.00 | 0.00 | |
| G SIWALL N2A | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 180.00 | 90.00 | S |
| G EIWALL N2A | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 90.00 | 90.00 | E |
| iz-G EIWALL N1A | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 270.00 | 90.00 | W |
| G CEILIN N2A | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 88.25 | 88.25 | 180.00 | 0.00 | |
| G NIWALL S1A | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 0.00 | 90.00 | N |
| G EIWALL S1A | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 90.00 | 90.00 | E |
| iz-G EIWALL SWA | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 270.00 | 90.00 | W |
| G CEILIN S1A | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 88.25 | 88.25 | 180.00 | 0.00 | |
| G NIWALL S2A | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 0.00 | 90.00 | N |
| G EIWALL S2A | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 90.00 | 90.00 | E |
| iz-G EIWALL S1A | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 270.00 | 90.00 | W |
| G CEILIN S2A | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 88.25 | 88.25 | 180.00 | 0.00 | |
| M NIWALL SWA | INT_WALL | 0.30 | 2.511 | 6.299 | 70.60 | 70.60 | 0.00 | 90.00 | N |
| M EIWALL SWA | INT_WALL | 0.30 | 2.511 | 6.299 | 46.45 | 46.45 | 90.00 | 90.00 | E |
| M GFLOOR SWA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 176.50 | 176.50 | 90.00 | 180.00 | |
| M CEILIN SWA | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 176.50 | 176.50 | 180.00 | 0.00 | |
| M SIWALL NWA | INT_WALL | 0.30 | 2.511 | 6.299 | 70.60 | 70.60 | 180.00 | 90.00 | S |
| M EIWALL NWA | INT_WALL | 0.30 | 2.511 | 6.299 | 46.45 | 46.45 | 90.00 | 90.00 | E |
| M GFLOOR NWA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 176.50 | 176.50 | 90.00 | 180.00 | |
| M CEILIN NWA | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 176.50 | 176.50 | 180.00 | 0.00 | |
| M NIWALL SEA | INT_WALL | 0.30 | 2.511 | 6.299 | 70.60 | 70.60 | 0.00 | 90.00 | N |
| iz-M EIWALL S2A | INT_WALL | 0.30 | 2.511 | 6.299 | 46.45 | 46.45 | 270.00 | 90.00 | W |
| M GFLOOR SEA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 176.50 | 176.50 | 90.00 | 180.00 | |
| M CEILIN SEA | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 176.50 | 176.50 | 180.00 | 0.00 | |
| M SIWALL NEA | INT_WALL | 0.30 | 2.511 | 6.299 | 70.60 | 70.60 | 180.00 | 90.00 | S |
| iz-M EIWALL N2A | INT_WALL | 0.30 | 2.511 | 6.299 | 46.45 | 46.45 | 270.00 | 90.00 | W |
| M GFLOOR NEA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 176.50 | 176.50 | 90.00 | 180.00 | |
| M CEILIN NEA | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 176.50 | 176.50 | 180.00 | 0.00 | |
| M SIWALL N1A | INT_WALL | 0.30 | 2.511 | 6.299 | 70.60 | 70.60 | 180.00 | 90.00 | S |
| M EIWALL N1A | INT_WALL | 0.30 | 2.511 | 6.299 | 46.45 | 46.45 | 90.00 | 90.00 | E |
| iz-M EIWALL NWA | INT_WALL | 0.30 | 2.511 | 6.299 | 46.45 | 46.45 | 270.00 | 90.00 | W |
| M GFLOOR N1A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 176.50 | 176.50 | 90.00 | 180.00 | |
| M CEILIN N1A | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 176.50 | 176.50 | 180.00 | 0.00 | |
| M SIWALL N2A | INT_WALL | 0.30 | 2.511 | 6.299 | 70.60 | 70.60 | 180.00 | 90.00 | S |
| M EIWALL N2A | INT_WALL | 0.30 | 2.511 | 6.299 | 46.45 | 46.45 | 90.00 | 90.00 | E |
| iz-M EIWALL N1A | INT_WALL | 0.30 | 2.511 | 6.299 | 46.45 | 46.45 | 270.00 | 90.00 | W |
| M GFLOOR N2A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 176.50 | 176.50 | 90.00 | 180.00 | |
| M CEILIN N2A | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 176.50 | 176.50 | 180.00 | 0.00 | |
| M NIWALL S1A | INT_WALL | 0.30 | 2.511 | 6.299 | 70.60 | 70.60 | 0.00 | 90.00 | N |
| M EIWALL S1A | INT_WALL | 0.30 | 2.511 | 6.299 | 46.45 | 46.45 | 90.00 | 90.00 | E |
| iz-M EIWALL SWA | INT_WALL | 0.30 | 2.511 | 6.299 | 46.45 | 46.45 | 270.00 | 90.00 | W |
| M GFLOOR S1A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 176.50 | 176.50 | 90.00 | 180.00 | |
| M CEILIN S1A | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 176.50 | 176.50 | 180.00 | 0.00 | |
| M NIWALL S2A | INT_WALL | 0.30 | 2.511 | 6.299 | 70.60 | 70.60 | 0.00 | 90.00 | N |
| M EIWALL S2A | INT_WALL | 0.30 | 2.511 | 6.299 | 46.45 | 46.45 | 90.00 | 90.00 | E |
| iz-M EIWALL S1A | INT_WALL | 0.30 | 2.511 | 6.299 | 46.45 | 46.45 | 270.00 | 90.00 | W |
| M GFLOOR S2A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 176.50 | 176.50 | 90.00 | 180.00 | |
| M CEILIN S2A | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 176.50 | 176.50 | 180.00 | 0.00 | |
| T NIWALL SWA | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 0.00 | 90.00 | N |
| T EIWALL SWA | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 90.00 | 90.00 | E |
| T GFLOOR SWA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 88.25 | 88.25 | 90.00 | 180.00 | |
| T SIWALL NWA | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 180.00 | 90.00 | S |
| T EIWALL NWA | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 90.00 | 90.00 | E |
| T GFLOOR NWA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 88.25 | 88.25 | 90.00 | 180.00 | |
| T NIWALL SEA | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 0.00 | 90.00 | N |
| iz-T EIWALL S2A | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 270.00 | 90.00 | W |
| T GFLOOR SEA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 88.25 | 88.25 | 90.00 | 180.00 | |
| T SIWALL NEA | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 180.00 | 90.00 | S |
| iz-T EIWALL N2A | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 270.00 | 90.00 | W |
| T GFLOOR NEA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 88.25 | 88.25 | 90.00 | 180.00 | |
| T SIWALL N1A | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 180.00 | 90.00 | S |
| T EIWALL N1A | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 90.00 | 90.00 | E |
| iz-T EIWALL NWA | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 270.00 | 90.00 | W |
| T GFLOOR N1A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 88.25 | 88.25 | 90.00 | 180.00 | |
| T SIWALL N2A | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 180.00 | 90.00 | S |
| T EIWALL N2A | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 90.00 | 90.00 | E |
| iz-T EIWALL N1A | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 270.00 | 90.00 | W |
| T GFLOOR N2A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 88.25 | 88.25 | 90.00 | 180.00 | |
| T NIWALL S1A | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 0.00 | 90.00 | N |
| T EIWALL S1A | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 90.00 | 90.00 | E |
| iz-T EIWALL SWA | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 270.00 | 90.00 | W |
| T GFLOOR S1A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 88.25 | 88.25 | 90.00 | 180.00 | |
| T NIWALL S2A | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 0.00 | 90.00 | N |
| T EIWALL S2A | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 90.00 | 90.00 | E |
| iz-T EIWALL S1A | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 270.00 | 90.00 | W |
| T GFLOOR S2A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 88.25 | 88.25 | 90.00 | 180.00 | |
| iz-T NIWALL SWA | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 180.00 | 90.00 | S |
| iz-T NIWALL S1A | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 180.00 | 90.00 | S |
| iz-T NIWALL S2A | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 180.00 | 90.00 | S |
| iz-T NIWALL SEA | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 180.00 | 90.00 | S |
| iz-T SIWALL NWA | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 0.00 | 90.00 | N |
| iz-T SIWALL N1A | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 0.00 | 90.00 | N |
| iz-T SIWALL N2A | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 0.00 | 90.00 | N |
| iz-T SIWALL NEA | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 0.00 | 90.00 | N |
| T FLOOR C | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 77.66 | 77.66 | 90.00 | 180.00 | |
| iz-G NIWALL SWA | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 180.00 | 90.00 | S |
| iz-G NIWALL S1A | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 180.00 | 90.00 | S |
| iz-G NIWALL S2A | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 180.00 | 90.00 | S |
| iz-G NIWALL SEA | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 180.00 | 90.00 | S |
| iz-G SIWALL NWA | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 0.00 | 90.00 | N |
| iz-G SIWALL N1A | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 0.00 | 90.00 | N |
| iz-G SIWALL N2A | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 0.00 | 90.00 | N |
| iz-G SIWALL NEA | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 0.00 | 90.00 | N |
| G CEILING C | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 77.66 | 77.66 | 180.00 | 0.00 | |
| iz-M NIWALL SWA | INT_WALL | 0.30 | 2.511 | 6.299 | 70.60 | 70.60 | 180.00 | 90.00 | S |
| iz-M NIWALL S1A | INT_WALL | 0.30 | 2.511 | 6.299 | 70.60 | 70.60 | 180.00 | 90.00 | S |
| iz-M NIWALL S2A | INT_WALL | 0.30 | 2.511 | 6.299 | 70.60 | 70.60 | 180.00 | 90.00 | S |
| iz-M NIWALL SEA | INT_WALL | 0.30 | 2.511 | 6.299 | 70.60 | 70.60 | 180.00 | 90.00 | S |
| iz-M SIWALL NWA | INT_WALL | 0.30 | 2.511 | 6.299 | 70.60 | 70.60 | 0.00 | 90.00 | N |
| iz-M SIWALL N1A | INT_WALL | 0.30 | 2.511 | 6.299 | 70.60 | 70.60 | 0.00 | 90.00 | N |
| iz-M SIWALL N2A | INT_WALL | 0.30 | 2.511 | 6.299 | 70.60 | 70.60 | 0.00 | 90.00 | N |
| iz-M SIWALL NEA | INT_WALL | 0.30 | 2.511 | 6.299 | 70.60 | 70.60 | 0.00 | 90.00 | N |
| M FLOOR C | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 155.32 | 155.32 | 90.00 | 180.00 | |
| M CEILING C | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 155.32 | 155.32 | 180.00 | 0.00 | |
| G INTERNALMASS SWA | INTERIORFURNISHINGS | 0.30 | 0.800 | 88.25 | 0.00 | 90.00 | N | ||
| G INTERNALMASS NWA | INTERIORFURNISHINGS | 0.30 | 0.800 | 88.25 | 0.00 | 90.00 | N | ||
| G INTERNALMASS SEA | INTERIORFURNISHINGS | 0.30 | 0.800 | 88.25 | 0.00 | 90.00 | N | ||
| G INTERNALMASS NEA | INTERIORFURNISHINGS | 0.30 | 0.800 | 88.25 | 0.00 | 90.00 | N | ||
| G INTERNALMASS N1A | INTERIORFURNISHINGS | 0.30 | 0.800 | 88.25 | 0.00 | 90.00 | N | ||
| G INTERNALMASS N2A | INTERIORFURNISHINGS | 0.30 | 0.800 | 88.25 | 0.00 | 90.00 | N | ||
| G INTERNALMASS S1A | INTERIORFURNISHINGS | 0.30 | 0.800 | 88.25 | 0.00 | 90.00 | N | ||
| G INTERNALMASS S2A | INTERIORFURNISHINGS | 0.30 | 0.800 | 88.25 | 0.00 | 90.00 | N | ||
| M INTERNALMASS SWA | INTERIORFURNISHINGS | 0.30 | 0.800 | 353.00 | 0.00 | 90.00 | N | ||
| M INTERNALMASS NWA | INTERIORFURNISHINGS | 0.30 | 0.800 | 353.00 | 0.00 | 90.00 | N | ||
| M INTERNALMASS SEA | INTERIORFURNISHINGS | 0.30 | 0.800 | 353.00 | 0.00 | 90.00 | N | ||
| M INTERNALMASS NEA | INTERIORFURNISHINGS | 0.30 | 0.800 | 353.00 | 0.00 | 90.00 | N | ||
| M INTERNALMASS N1A | INTERIORFURNISHINGS | 0.30 | 0.800 | 353.00 | 0.00 | 90.00 | N | ||
| M INTERNALMASS N2A | INTERIORFURNISHINGS | 0.30 | 0.800 | 353.00 | 0.00 | 90.00 | N | ||
| M INTERNALMASS S1A | INTERIORFURNISHINGS | 0.30 | 0.800 | 353.00 | 0.00 | 90.00 | N | ||
| M INTERNALMASS S2A | INTERIORFURNISHINGS | 0.30 | 0.800 | 353.00 | 0.00 | 90.00 | N | ||
| T INTERNALMASS SWA | INTERIORFURNISHINGS | 0.30 | 0.800 | 88.25 | 0.00 | 90.00 | N | ||
| T INTERNALMASS NWA | INTERIORFURNISHINGS | 0.30 | 0.800 | 88.25 | 0.00 | 90.00 | N | ||
| T INTERNALMASS SEA | INTERIORFURNISHINGS | 0.30 | 0.800 | 88.25 | 0.00 | 90.00 | N | ||
| T INTERNALMASS NEA | INTERIORFURNISHINGS | 0.30 | 0.800 | 88.25 | 0.00 | 90.00 | N | ||
| T INTERNALMASS N1A | INTERIORFURNISHINGS | 0.30 | 0.800 | 88.25 | 0.00 | 90.00 | N | ||
| T INTERNALMASS N2A | INTERIORFURNISHINGS | 0.30 | 0.800 | 88.25 | 0.00 | 90.00 | N | ||
| T INTERNALMASS S1A | INTERIORFURNISHINGS | 0.30 | 0.800 | 88.25 | 0.00 | 90.00 | N | ||
| T INTERNALMASS S2A | INTERIORFURNISHINGS | 0.30 | 0.800 | 88.25 | 0.00 | 90.00 | N |
| Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
| GWINDOW1 S SWA | RESWINDOW_U_0.3972_SHGC_0.4 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.257 | 0.401 | 0.402 | No | G SWALL SWA | 180.00 | 90.00 | S | |||||||
| GWINDOW1 W SWA | RESWINDOW_U_0.3972_SHGC_0.4 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 2.257 | 0.401 | 0.402 | No | G WWALL SWA | 270.00 | 90.00 | W | |||||||
| GWINDOW1 N NWA | RESWINDOW_U_0.3972_SHGC_0.4 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.257 | 0.401 | 0.402 | No | G NWALL NWA | 0.00 | 90.00 | N | |||||||
| GWINDOW1 W NWA | RESWINDOW_U_0.3972_SHGC_0.4 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 2.257 | 0.401 | 0.402 | No | G WWALL NWA | 270.00 | 90.00 | W | |||||||
| GWINDOW1 S SEA | NONRESWINDOW_U_0.3972_SHGC_0.4 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.257 | 0.401 | 0.402 | No | G SWALL SEA | 180.00 | 90.00 | S | |||||||
| GWINDOW1 E SEA | NONRESWINDOW_U_0.3972_SHGC_0.4 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 2.257 | 0.401 | 0.402 | No | G EWALL SEA | 90.00 | 90.00 | E | |||||||
| GWINDOW1 N NEA | RESWINDOW_U_0.3972_SHGC_0.4 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.257 | 0.401 | 0.402 | No | G NWALL NEA | 0.00 | 90.00 | N | |||||||
| GWINDOW1 E NEA | RESWINDOW_U_0.3972_SHGC_0.4 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 2.257 | 0.401 | 0.402 | No | G EWALL NEA | 90.00 | 90.00 | E | |||||||
| GWINDOW1 N N1A | RESWINDOW_U_0.3972_SHGC_0.4 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.257 | 0.401 | 0.402 | No | G NWALL N1A | 0.00 | 90.00 | N | |||||||
| GWINDOW1 N N2A | RESWINDOW_U_0.3972_SHGC_0.4 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.257 | 0.401 | 0.402 | No | G NWALL N2A | 0.00 | 90.00 | N | |||||||
| GWINDOW1 S S1A | RESWINDOW_U_0.3972_SHGC_0.4 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.257 | 0.401 | 0.402 | No | G SWALL S1A | 180.00 | 90.00 | S | |||||||
| GWINDOW1 S S2A | RESWINDOW_U_0.3972_SHGC_0.4 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.257 | 0.401 | 0.402 | No | G SWALL S2A | 180.00 | 90.00 | S | |||||||
| MWINDOW1 W SWA | RESWINDOW_U_0.3972_SHGC_0.4 | 4.65 | 0.00 | 0.00 | 4.65 | 9.29 | 2.257 | 0.401 | 0.402 | No | M WWALL SWA | 270.00 | 90.00 | W | |||||||
| MWINDOW1 S SWA | RESWINDOW_U_0.3972_SHGC_0.4 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 2.257 | 0.401 | 0.402 | No | M SWALL SWA | 180.00 | 90.00 | S | |||||||
| MWINDOW1 N NWA | RESWINDOW_U_0.3972_SHGC_0.4 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 2.257 | 0.401 | 0.402 | No | M NWALL NWA | 0.00 | 90.00 | N | |||||||
| MWINDOW1 W NWA | RESWINDOW_U_0.3972_SHGC_0.4 | 4.65 | 0.00 | 0.00 | 4.65 | 9.29 | 2.257 | 0.401 | 0.402 | No | M WWALL NWA | 270.00 | 90.00 | W | |||||||
| MWINDOW1 E SEA | RESWINDOW_U_0.3972_SHGC_0.4 | 4.65 | 0.00 | 0.00 | 4.65 | 9.29 | 2.257 | 0.401 | 0.402 | No | M EWALL SEA | 90.00 | 90.00 | E | |||||||
| MWINDOW1 S SEA | RESWINDOW_U_0.3972_SHGC_0.4 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 2.257 | 0.401 | 0.402 | No | M SWALL SEA | 180.00 | 90.00 | S | |||||||
| MWINDOW1 N NEA | RESWINDOW_U_0.3972_SHGC_0.4 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 2.257 | 0.401 | 0.402 | No | M NWALL NEA | 0.00 | 90.00 | N | |||||||
| MWINDOW1 E NEA | RESWINDOW_U_0.3972_SHGC_0.4 | 4.65 | 0.00 | 0.00 | 4.65 | 9.29 | 2.257 | 0.401 | 0.402 | No | M EWALL NEA | 90.00 | 90.00 | E | |||||||
| MWINDOW1 N N1A | RESWINDOW_U_0.3972_SHGC_0.4 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 2.257 | 0.401 | 0.402 | No | M NWALL N1A | 0.00 | 90.00 | N | |||||||
| MWINDOW1 N N2A | RESWINDOW_U_0.3972_SHGC_0.4 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 2.257 | 0.401 | 0.402 | No | M NWALL N2A | 0.00 | 90.00 | N | |||||||
| MWINDOW1 S S1A | RESWINDOW_U_0.3972_SHGC_0.4 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 2.257 | 0.401 | 0.402 | No | M SWALL S1A | 180.00 | 90.00 | S | |||||||
| MWINDOW1 S S2A | RESWINDOW_U_0.3972_SHGC_0.4 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 2.257 | 0.401 | 0.402 | No | M SWALL S2A | 180.00 | 90.00 | S | |||||||
| TWINDOW1 W SWA | RESWINDOW_U_0.3972_SHGC_0.4 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 2.257 | 0.401 | 0.402 | No | T WWALL SWA | 270.00 | 90.00 | W | |||||||
| TWINDOW1 S SWA | RESWINDOW_U_0.3972_SHGC_0.4 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.257 | 0.401 | 0.402 | No | T SWALL SWA | 180.00 | 90.00 | S | |||||||
| TWINDOW1 N NWA | RESWINDOW_U_0.3972_SHGC_0.4 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.257 | 0.401 | 0.402 | No | T NWALL NWA | 0.00 | 90.00 | N | |||||||
| TWINDOW1 W NWA | RESWINDOW_U_0.3972_SHGC_0.4 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 2.257 | 0.401 | 0.402 | No | T WWALL NWA | 270.00 | 90.00 | W | |||||||
| TWINDOW1 E SEA | RESWINDOW_U_0.3972_SHGC_0.4 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 2.257 | 0.401 | 0.402 | No | T EWALL SEA | 90.00 | 90.00 | E | |||||||
| TWINDOW1 S SEA | RESWINDOW_U_0.3972_SHGC_0.4 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.257 | 0.401 | 0.402 | No | T SWALL SEA | 180.00 | 90.00 | S | |||||||
| TWINDOW1 N NEA | RESWINDOW_U_0.3972_SHGC_0.4 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.257 | 0.401 | 0.402 | No | T NWALL NEA | 0.00 | 90.00 | N | |||||||
| TWINDOW1 E NEA | RESWINDOW_U_0.3972_SHGC_0.4 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 2.257 | 0.401 | 0.402 | No | T EWALL NEA | 90.00 | 90.00 | E | |||||||
| TWINDOW1 N N1A | RESWINDOW_U_0.3972_SHGC_0.4 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.257 | 0.401 | 0.402 | No | T NWALL N1A | 0.00 | 90.00 | N | |||||||
| TWINDOW1 N N2A | RESWINDOW_U_0.3972_SHGC_0.4 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.257 | 0.401 | 0.402 | No | T NWALL N2A | 0.00 | 90.00 | N | |||||||
| TWINDOW1 S S1A | RESWINDOW_U_0.3972_SHGC_0.4 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.257 | 0.401 | 0.402 | No | T SWALL S1A | 180.00 | 90.00 | S | |||||||
| TWINDOW1 S S2A | RESWINDOW_U_0.3972_SHGC_0.4 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.257 | 0.401 | 0.402 | No | T SWALL S2A | 180.00 | 90.00 | S | |||||||
| TWINDOW14 | NONRESWINDOW_U_0.3972_SHGC_0.4 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.257 | 0.401 | 0.402 | No | T EWALL C | 90.00 | 90.00 | E | |||||||
| ENTRANCE DOOR | NONRESWINDOW_U_0.3972_SHGC_0.4 | 3.32 | 0.00 | 0.00 | 3.32 | 3.32 | 2.257 | 0.401 | 0.402 | No | G EWALL C | 90.00 | 90.00 | E | |||||||
| MWINDOW14 | NONRESWINDOW_U_0.3972_SHGC_0.4 | 1.11 | 0.00 | 0.00 | 1.11 | 2.23 | 2.257 | 0.401 | 0.402 | No | M EWALL C | 90.00 | 90.00 | E | |||||||
| Total or Average | 306.92 | 2.257 | 0.401 | 0.402 | |||||||||||||||||
| North Total or Average | 112.97 | 2.257 | 0.401 | 0.402 | |||||||||||||||||
| Non-North Total or Average | 193.95 | 2.257 | 0.401 | 0.402 |
| Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
| None |
| Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
| Total or Average | 0.00 | - | - | - |
| Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
| None |
| Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
| None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 09:15:24
Sunlit Fraction| March 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
| GWINDOW1 S SWA | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| GWINDOW1 W SWA | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
| GWINDOW1 N NWA | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| GWINDOW1 W NWA | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
| GWINDOW1 S SEA | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| GWINDOW1 E SEA | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
| GWINDOW1 N NEA | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| GWINDOW1 E NEA | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
| GWINDOW1 N N1A | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| GWINDOW1 N N2A | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| GWINDOW1 S S1A | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| GWINDOW1 S S2A | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| MWINDOW1 W SWA | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
| MWINDOW1 S SWA | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| MWINDOW1 N NWA | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| MWINDOW1 W NWA | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
| MWINDOW1 E SEA | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
| MWINDOW1 S SEA | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| MWINDOW1 N NEA | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| MWINDOW1 E NEA | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
| MWINDOW1 N N1A | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| MWINDOW1 N N2A | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| MWINDOW1 S S1A | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| MWINDOW1 S S2A | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| TWINDOW1 W SWA | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
| TWINDOW1 S SWA | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| TWINDOW1 N NWA | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| TWINDOW1 W NWA | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
| TWINDOW1 E SEA | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
| TWINDOW1 S SEA | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| TWINDOW1 N NEA | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| TWINDOW1 E NEA | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
| TWINDOW1 N N1A | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| TWINDOW1 N N2A | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| TWINDOW1 S S1A | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| TWINDOW1 S S2A | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| TWINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
| ENTRANCE DOOR | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
| MWINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
| Name | Type | Shaded Construction | Control | Glare Control | |
| None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 09:15:24
Interior Lighting| Zone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
| LIGHTING_HARDWIRED_GSW | G SW APARTMENT | G SW APARTMENT | GENERAL | 7.8684 | 88.25 | 694.38 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.32 |
| LIGHTING_HARDWIRED_GNW | G NW APARTMENT | G NW APARTMENT | GENERAL | 7.8684 | 88.25 | 694.38 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.32 |
| LIGHTING_HARDWIRED_OFFICE | OFFICE | OFFICE | GENERAL | 9.7532 | 88.25 | 860.71 | LightsWired | LTG_SCH_OFFICE | 46.69 | 168.00 | 45.77 | 0.0000 | Y | 7.40 |
| LIGHTING_HARDWIRED_GNE | G NE APARTMENT | G NE APARTMENT | GENERAL | 7.8684 | 88.25 | 694.38 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.32 |
| LIGHTING_HARDWIRED_GN1 | G N1 APARTMENT | G N1 APARTMENT | GENERAL | 7.8684 | 88.25 | 694.38 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.32 |
| LIGHTING_HARDWIRED_GN2 | G N2 APARTMENT | G N2 APARTMENT | GENERAL | 7.8684 | 88.25 | 694.38 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.32 |
| LIGHTING_HARDWIRED_GS1 | G S1 APARTMENT | G S1 APARTMENT | GENERAL | 7.8684 | 88.25 | 694.38 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.32 |
| LIGHTING_HARDWIRED_GS2 | G S2 APARTMENT | G S2 APARTMENT | GENERAL | 7.8684 | 88.25 | 694.38 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.32 |
| LIGHTING_HARDWIRED_MSW | M SW APARTMENT | M SW APARTMENT | GENERAL | 7.8684 | 176.50 | 1388.76 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 2.63 |
| LIGHTING_HARDWIRED_MNW | M NW APARTMENT | M NW APARTMENT | GENERAL | 7.8684 | 176.50 | 1388.76 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 2.63 |
| LIGHTING_HARDWIRED_MSE | M SE APARTMENT | M SE APARTMENT | GENERAL | 7.8684 | 176.50 | 1388.76 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 2.63 |
| LIGHTING_HARDWIRED_MNE | M NE APARTMENT | M NE APARTMENT | GENERAL | 7.8684 | 176.50 | 1388.76 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 2.63 |
| LIGHTING_HARDWIRED_MN1 | M N1 APARTMENT | M N1 APARTMENT | GENERAL | 7.8684 | 176.50 | 1388.76 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 2.63 |
| LIGHTING_HARDWIRED_MN2 | M N2 APARTMENT | M N2 APARTMENT | GENERAL | 7.8684 | 176.50 | 1388.76 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 2.63 |
| LIGHTING_HARDWIRED_MS1 | M S1 APARTMENT | M S1 APARTMENT | GENERAL | 7.8684 | 176.50 | 1388.76 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 2.63 |
| LIGHTING_HARDWIRED_MS2 | M S2 APARTMENT | M S2 APARTMENT | GENERAL | 7.8684 | 176.50 | 1388.76 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 2.63 |
| LIGHTING_HARDWIRED_TSW | T SW APARTMENT | T SW APARTMENT | GENERAL | 7.8684 | 88.25 | 694.38 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.32 |
| LIGHTING_HARDWIRED_TNW | T NW APARTMENT | T NW APARTMENT | GENERAL | 7.8684 | 88.25 | 694.38 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.32 |
| LIGHTING_HARDWIRED_TSE | T SE APARTMENT | T SE APARTMENT | GENERAL | 7.8684 | 88.25 | 694.38 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.32 |
| LIGHTING_HARDWIRED_TNE | T NE APARTMENT | T NE APARTMENT | GENERAL | 7.8684 | 88.25 | 694.38 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.32 |
| LIGHTING_HARDWIRED_TN1 | T N1 APARTMENT | T N1 APARTMENT | GENERAL | 7.8684 | 88.25 | 694.38 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.32 |
| LIGHTING_HARDWIRED_TN2 | T N2 APARTMENT | T N2 APARTMENT | GENERAL | 7.8684 | 88.25 | 694.38 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.32 |
| LIGHTING_HARDWIRED_TS1 | T S1 APARTMENT | T S1 APARTMENT | GENERAL | 7.8684 | 88.25 | 694.38 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.32 |
| LIGHTING_HARDWIRED_TS2 | T S2 APARTMENT | T S2 APARTMENT | GENERAL | 7.8684 | 88.25 | 694.38 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.32 |
| LIGHTING_HARDWIRED_GC | G CORRIDOR | G CORRIDOR | GENERAL | 4.7725 | 77.66 | 370.63 | LightsWired | LTG_SCH_CORRIDOR | 168.00 | 168.00 | 168.00 | 0.0000 | N | 11.69 |
| LIGHTING_HARDWIRED_MC | M CORRIDOR | M CORRIDOR | GENERAL | 4.7725 | 155.32 | 741.26 | LightsWired | LTG_SCH_CORRIDOR | 168.00 | 168.00 | 168.00 | 0.0000 | N | 23.38 |
| LIGHTING_HARDWIRED_TC | T CORRIDOR | T CORRIDOR | GENERAL | 4.7725 | 77.66 | 370.63 | LightsWired | LTG_SCH_CORRIDOR | 168.00 | 168.00 | 168.00 | 0.0000 | N | 11.69 |
| LIGHTING_PLUGIN_GSW | G SW APARTMENT | G SW APARTMENT | GENERAL | 0.8234 | 88.25 | 72.67 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.14 |
| LIGHTING_PLUGIN_GNW | G NW APARTMENT | G NW APARTMENT | GENERAL | 0.8234 | 88.25 | 72.67 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.14 |
| LIGHTING_PLUGIN_GNE | G NE APARTMENT | G NE APARTMENT | GENERAL | 0.8234 | 88.25 | 72.67 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.14 |
| LIGHTING_PLUGIN_GN1 | G N1 APARTMENT | G N1 APARTMENT | GENERAL | 0.8234 | 88.25 | 72.67 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.14 |
| LIGHTING_PLUGIN_GN2 | G N2 APARTMENT | G N2 APARTMENT | GENERAL | 0.8234 | 88.25 | 72.67 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.14 |
| LIGHTING_PLUGIN_GS1 | G S1 APARTMENT | G S1 APARTMENT | GENERAL | 0.8234 | 88.25 | 72.67 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.14 |
| LIGHTING_PLUGIN_GS2 | G S2 APARTMENT | G S2 APARTMENT | GENERAL | 0.8234 | 88.25 | 72.67 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.14 |
| LIGHTING_PLUGIN_MSW | M SW APARTMENT | M SW APARTMENT | GENERAL | 0.8234 | 176.50 | 145.34 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.28 |
| LIGHTING_PLUGIN_MNW | M NW APARTMENT | M NW APARTMENT | GENERAL | 0.8234 | 176.50 | 145.34 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.28 |
| LIGHTING_PLUGIN_MSE | M SE APARTMENT | M SE APARTMENT | GENERAL | 0.8234 | 176.50 | 145.34 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.28 |
| LIGHTING_PLUGIN_MNE | M NE APARTMENT | M NE APARTMENT | GENERAL | 0.8234 | 176.50 | 145.34 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.28 |
| LIGHTING_PLUGIN_MN1 | M N1 APARTMENT | M N1 APARTMENT | GENERAL | 0.8234 | 176.50 | 145.34 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.28 |
| LIGHTING_PLUGIN_MN2 | M N2 APARTMENT | M N2 APARTMENT | GENERAL | 0.8234 | 176.50 | 145.34 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.28 |
| LIGHTING_PLUGIN_MS1 | M S1 APARTMENT | M S1 APARTMENT | GENERAL | 0.8234 | 176.50 | 145.34 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.28 |
| LIGHTING_PLUGIN_MS2 | M S2 APARTMENT | M S2 APARTMENT | GENERAL | 0.8234 | 176.50 | 145.34 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.28 |
| LIGHTING_PLUGIN_TSW | T SW APARTMENT | T SW APARTMENT | GENERAL | 0.8234 | 88.25 | 72.67 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.14 |
| LIGHTING_PLUGIN_TNW | T NW APARTMENT | T NW APARTMENT | GENERAL | 0.8234 | 88.25 | 72.67 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.14 |
| LIGHTING_PLUGIN_TSE | T SE APARTMENT | T SE APARTMENT | GENERAL | 0.8234 | 88.25 | 72.67 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.14 |
| LIGHTING_PLUGIN_TNE | T NE APARTMENT | T NE APARTMENT | GENERAL | 0.8234 | 88.25 | 72.67 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.14 |
| LIGHTING_PLUGIN_TN1 | T N1 APARTMENT | T N1 APARTMENT | GENERAL | 0.8234 | 88.25 | 72.67 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.14 |
| LIGHTING_PLUGIN_TN2 | T N2 APARTMENT | T N2 APARTMENT | GENERAL | 0.8234 | 88.25 | 72.67 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.14 |
| LIGHTING_PLUGIN_TS1 | T S1 APARTMENT | T S1 APARTMENT | GENERAL | 0.8234 | 88.25 | 72.67 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.14 |
| LIGHTING_PLUGIN_TS2 | T S2 APARTMENT | T S2 APARTMENT | GENERAL | 0.8234 | 88.25 | 72.67 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.14 |
| Interior Lighting Total | 4.4498 | 5870.34 | 26121.74 | 75.91 |
| Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
| None |
| Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
| FACADE LIGHTING | 3183.33 | AstronomicalClock | - | 83.55 | 83.55 | 49.92 | |
| Exterior Lighting Total | 3183.33 | 49.92 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 09:15:24
Central Plant| Type | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
| None |
| Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
| SPLIT GSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 6038.93 | 4835.10 | 1203.83 | 0.80 | 3.91 | |||
| SPLIT GNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5067.55 | 4057.36 | 1010.19 | 0.80 | 3.91 | |||
| SPLIT OFFICE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 6660.94 | 5333.12 | 1327.82 | 0.80 | 3.91 | |||
| SPLIT GNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 4449.75 | 3562.72 | 887.03 | 0.80 | 3.91 | |||
| SPLIT GN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 4058.81 | 3249.71 | 809.10 | 0.80 | 3.91 | |||
| SPLIT GN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 4047.42 | 3240.59 | 806.83 | 0.80 | 3.91 | |||
| SPLIT GS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5106.72 | 4088.72 | 1018.00 | 0.80 | 3.91 | |||
| SPLIT GS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5132.58 | 4109.43 | 1023.15 | 0.80 | 3.91 | |||
| SPLIT MSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 14658.71 | 11736.57 | 2922.14 | 0.80 | 3.91 | |||
| SPLIT MNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 12837.81 | 10278.66 | 2559.15 | 0.80 | 3.91 | |||
| SPLIT MSE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 12806.70 | 10253.75 | 2552.95 | 0.80 | 3.91 | |||
| SPLIT MNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 11031.40 | 8832.35 | 2199.05 | 0.80 | 3.91 | |||
| SPLIT MN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 9981.72 | 7991.92 | 1989.80 | 0.80 | 3.91 | |||
| SPLIT MN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 9950.29 | 7966.75 | 1983.54 | 0.80 | 3.91 | |||
| SPLIT MS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 11971.64 | 9585.15 | 2386.48 | 0.80 | 3.91 | |||
| SPLIT MS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 11935.91 | 9556.55 | 2379.36 | 0.80 | 3.91 | |||
| SPLIT TSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7853.87 | 6288.25 | 1565.63 | 0.80 | 3.91 | |||
| SPLIT TNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7113.83 | 5695.72 | 1418.10 | 0.80 | 3.91 | |||
| SPLIT TSE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 6514.17 | 5215.61 | 1298.57 | 0.80 | 3.91 | |||
| SPLIT TNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5783.70 | 4630.75 | 1152.95 | 0.80 | 3.91 | |||
| SPLIT TN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5508.35 | 4410.29 | 1098.06 | 0.80 | 3.91 | |||
| SPLIT TN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5465.26 | 4375.79 | 1089.47 | 0.80 | 3.91 | |||
| SPLIT TS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 6295.20 | 5040.29 | 1254.92 | 0.80 | 3.91 | |||
| SPLIT TS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 6251.91 | 5005.62 | 1246.29 | 0.80 | 3.91 |
| DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
| SPLIT GSW COOLING COIL | 5753.0 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 | |
| SPLIT GNW COOLING COIL | 4827.6 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 | |
| SPLIT OFFICE COOLING COIL | 6345.6 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 | |
| SPLIT GNE COOLING COIL | 4239.1 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 | |
| SPLIT GN1 COOLING COIL | 3866.7 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 | |
| SPLIT GN2 COOLING COIL | 3855.8 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 | |
| SPLIT GS1 COOLING COIL | 4865.0 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 | |
| SPLIT GS2 COOLING COIL | 4889.6 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 | |
| SPLIT MSW COOLING COIL | 13964.7 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 | |
| SPLIT MNW COOLING COIL | 12230.0 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 | |
| SPLIT MSE COOLING COIL | 12200.4 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 | |
| SPLIT MNE COOLING COIL | 10509.1 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 | |
| SPLIT MN1 COOLING COIL | 9509.2 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 | |
| SPLIT MN2 COOLING COIL | 9479.2 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 | |
| SPLIT MS1 COOLING COIL | 11404.9 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 | |
| SPLIT MS2 COOLING COIL | 11370.8 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 | |
| SPLIT TSW COOLING COIL | 7482.1 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 | |
| SPLIT TNW COOLING COIL | 6777.0 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 | |
| SPLIT TSE COOLING COIL | 6205.8 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 | |
| SPLIT TNE COOLING COIL | 5509.9 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 | |
| SPLIT TN1 COOLING COIL | 5247.6 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 | |
| SPLIT TN2 COOLING COIL | 5206.5 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 | |
| SPLIT TS1 COOLING COIL | 5997.2 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 | |
| SPLIT TS2 COOLING COIL | 5955.9 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 |
| DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
| SPLIT GSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT GNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT OFFICE COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT GNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT GN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT GN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT GS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT GS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT MSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT MNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT MSE COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT MNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT MN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT MN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT MS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT MS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT TSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT TNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT TSE COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT TNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT TN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT TN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT TS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT TS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed |
| DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
| None |
| Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
| SPLIT GSW HEATING COIL | Coil:Heating:Fuel | 9007.43 | 0.80 | |
| SPLIT GNW HEATING COIL | Coil:Heating:Fuel | 7684.47 | 0.80 | |
| SPLIT OFFICE HEATING COIL | Coil:Heating:Fuel | 10221.22 | 0.80 | |
| SPLIT GNE HEATING COIL | Coil:Heating:Fuel | 6843.13 | 0.80 | |
| SPLIT GN1 HEATING COIL | Coil:Heating:Fuel | 6310.68 | 0.80 | |
| SPLIT GN2 HEATING COIL | Coil:Heating:Fuel | 6295.16 | 0.80 | |
| SPLIT GS1 HEATING COIL | Coil:Heating:Fuel | 7737.82 | 0.80 | |
| SPLIT GS2 HEATING COIL | Coil:Heating:Fuel | 7773.03 | 0.80 | |
| SPLIT MSW HEATING COIL | Coil:Heating:Fuel | 21530.46 | 0.80 | |
| SPLIT MNW HEATING COIL | Coil:Heating:Fuel | 19050.28 | 0.80 | |
| SPLIT MSE HEATING COIL | Coil:Heating:Fuel | 19008.16 | 0.80 | |
| SPLIT MNE HEATING COIL | Coil:Heating:Fuel | 16590.11 | 0.80 | |
| SPLIT MN1 HEATING COIL | Coil:Heating:Fuel | 15160.23 | 0.80 | |
| SPLIT MN2 HEATING COIL | Coil:Heating:Fuel | 15117.42 | 0.80 | |
| SPLIT MS1 HEATING COIL | Coil:Heating:Fuel | 17870.48 | 0.80 | |
| SPLIT MS2 HEATING COIL | Coil:Heating:Fuel | 17821.82 | 0.80 | |
| SPLIT TSW HEATING COIL | Coil:Heating:Fuel | 11479.86 | 0.80 | |
| SPLIT TNW HEATING COIL | Coil:Heating:Fuel | 10471.79 | 0.80 | |
| SPLIT TSE HEATING COIL | Coil:Heating:Fuel | 9655.23 | 0.80 | |
| SPLIT TNE HEATING COIL | Coil:Heating:Fuel | 8660.24 | 0.80 | |
| SPLIT TN1 HEATING COIL | Coil:Heating:Fuel | 8284.98 | 0.80 | |
| SPLIT TN2 HEATING COIL | Coil:Heating:Fuel | 8226.28 | 0.80 | |
| SPLIT TS1 HEATING COIL | Coil:Heating:Fuel | 9356.72 | 0.80 | |
| SPLIT TS2 HEATING COIL | Coil:Heating:Fuel | 9297.76 | 0.80 |
| Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
| G SW APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| G SW APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| G NW APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| G NW APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| G NE APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| G NE APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| G N1 APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| G N1 APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| G N2 APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| G N2 APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| G S1 APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| G S1 APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| G S2 APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| G S2 APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| M SW APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.05 | 40.01 | 770.84 | 1.00 | 4.13 | General | ||
| M SW APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.05 | 40.01 | 770.84 | 1.00 | 4.13 | General | ||
| M NW APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.05 | 40.01 | 770.84 | 1.00 | 4.13 | General | ||
| M NW APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.05 | 40.01 | 770.84 | 1.00 | 4.13 | General | ||
| M SE APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.05 | 40.01 | 770.84 | 1.00 | 4.13 | General | ||
| M SE APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.05 | 40.01 | 770.84 | 1.00 | 4.13 | General | ||
| M NE APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.05 | 40.01 | 770.84 | 1.00 | 4.13 | General | ||
| M NE APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.05 | 40.01 | 770.84 | 1.00 | 4.13 | General | ||
| M N1 APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.05 | 40.01 | 770.84 | 1.00 | 4.13 | General | ||
| M N1 APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.05 | 40.01 | 770.84 | 1.00 | 4.13 | General | ||
| M N2 APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.05 | 40.01 | 770.84 | 1.00 | 4.13 | General | ||
| M N2 APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.05 | 40.01 | 770.84 | 1.00 | 4.13 | General | ||
| M S1 APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.05 | 40.01 | 770.84 | 1.00 | 4.13 | General | ||
| M S1 APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.05 | 40.01 | 770.84 | 1.00 | 4.13 | General | ||
| M S2 APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.05 | 40.01 | 770.84 | 1.00 | 4.13 | General | ||
| M S2 APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.05 | 40.01 | 770.84 | 1.00 | 4.13 | General | ||
| T SW APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| T SW APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| T NW APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| T NW APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| T SE APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| T SE APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| T NE APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| T NE APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| T N1 APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| T N1 APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| T N2 APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| T N2 APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| T S1 APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| T S1 APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| T S2 APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| T S2 APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| SPLIT GSW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.36 | 408.63 | 1120.11 | 1.00 | 1.77 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 |
| SPLIT GNW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.31 | 342.90 | 1120.11 | 1.00 | 1.88 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 |
| SPLIT OFFICE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.40 | 450.72 | 1120.11 | 1.00 | 1.71 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 |
| SPLIT GNE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.27 | 301.10 | 1120.11 | 1.00 | 1.98 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 |
| SPLIT GN1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.25 | 274.64 | 1120.11 | 1.00 | 2.05 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 |
| SPLIT GN2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.24 | 273.87 | 1120.11 | 1.00 | 2.06 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 |
| SPLIT GS1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.31 | 345.55 | 1120.11 | 1.00 | 1.88 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 |
| SPLIT GS2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.31 | 347.30 | 1120.11 | 1.00 | 1.87 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 |
| SPLIT MSW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.89 | 991.89 | 1120.11 | 1.00 | 1.40 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 |
| SPLIT MNW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.78 | 868.68 | 1120.11 | 1.00 | 1.44 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 |
| SPLIT MSE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.77 | 866.57 | 1120.11 | 1.00 | 1.44 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 |
| SPLIT MNE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.67 | 746.45 | 1120.11 | 1.00 | 1.49 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 |
| SPLIT MN1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.60 | 675.42 | 1120.11 | 1.00 | 1.53 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 |
| SPLIT MN2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.60 | 673.29 | 1120.11 | 1.00 | 1.53 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 |
| SPLIT MS1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.72 | 810.07 | 1120.11 | 1.00 | 1.46 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 |
| SPLIT MS2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.72 | 807.65 | 1120.11 | 1.00 | 1.47 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 |
| SPLIT TSW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.47 | 531.44 | 1120.11 | 1.00 | 1.63 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 |
| SPLIT TNW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.43 | 481.36 | 1120.11 | 1.00 | 1.68 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 |
| SPLIT TSE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.39 | 440.79 | 1120.11 | 1.00 | 1.73 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 |
| SPLIT TNE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.35 | 391.36 | 1120.11 | 1.00 | 1.79 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 |
| SPLIT TN1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.33 | 372.73 | 1120.11 | 1.00 | 1.83 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 |
| SPLIT TN2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.33 | 369.81 | 1120.11 | 1.00 | 1.83 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 |
| SPLIT TS1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.38 | 425.97 | 1120.11 | 1.00 | 1.74 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 |
| SPLIT TS2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.38 | 423.04 | 1120.11 | 1.00 | 1.75 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 |
| Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
| None |
| Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
| G SW APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.77 |
| G NW APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.77 |
| G NE APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.77 |
| G N1 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.77 |
| G N2 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.77 |
| G S1 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.77 |
| G S2 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.77 |
| M SW APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.79 |
| M NW APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.79 |
| M SE APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.79 |
| M NE APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.79 |
| M N1 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.79 |
| M N2 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.79 |
| M S1 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.79 |
| M S2 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.79 |
| T SW APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.77 |
| T NW APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.77 |
| T SE APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.77 |
| T NE APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.77 |
| T N1 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.77 |
| T N2 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.77 |
| T S1 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.77 |
| T S2 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.77 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 09:15:24
Zone Sensible Cooling| Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
| G SW APARTMENT | 4239.21 | 5087.06 | 57.64 | 0.304 | 0.365 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 24.00 | 24.00 | 0.00812 | 25.34 | 0.00882 | 0.026 | 0.00 |
| G NW APARTMENT | 3572.32 | 4286.78 | 48.58 | 0.255 | 0.306 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 24.00 | 24.00 | 0.00812 | 25.34 | 0.00882 | 0.026 | 0.00 |
| OFFICE | 4608.76 | 5530.51 | 62.67 | 0.335 | 0.402 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | 23.90 | 23.90 | 0.00802 | 23.68 | 0.00881 | 0.038 | 0.00 |
| G NE APARTMENT | 3148.93 | 3778.71 | 42.82 | 0.224 | 0.269 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 24.00 | 24.00 | 0.00815 | 25.34 | 0.00882 | 0.026 | 0.00 |
| G N1 APARTMENT | 2879.66 | 3455.59 | 39.16 | 0.204 | 0.245 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 24.00 | 24.00 | 0.00817 | 25.34 | 0.00882 | 0.026 | 0.00 |
| G N2 APARTMENT | 2871.84 | 3446.21 | 39.05 | 0.204 | 0.245 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 24.00 | 24.00 | 0.00817 | 25.34 | 0.00882 | 0.026 | 0.00 |
| G S1 APARTMENT | 3599.32 | 4319.19 | 48.94 | 0.257 | 0.308 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 24.00 | 24.00 | 0.00815 | 25.34 | 0.00882 | 0.026 | 0.00 |
| G S2 APARTMENT | 3616.97 | 4340.36 | 49.18 | 0.258 | 0.310 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 24.00 | 24.00 | 0.00815 | 25.34 | 0.00882 | 0.026 | 0.00 |
| M SW APARTMENT | 10252.62 | 12303.14 | 139.41 | 0.738 | 0.886 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 24.00 | 24.00 | 0.00809 | 25.34 | 0.00882 | 0.052 | 0.00 |
| M NW APARTMENT | 8999.93 | 10799.92 | 122.38 | 0.646 | 0.776 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 24.00 | 24.00 | 0.00810 | 25.34 | 0.00882 | 0.052 | 0.00 |
| M SE APARTMENT | 8978.26 | 10773.91 | 122.08 | 0.645 | 0.774 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 24.00 | 24.00 | 0.00812 | 25.34 | 0.00882 | 0.052 | 0.00 |
| M NE APARTMENT | 7763.41 | 9316.09 | 105.57 | 0.555 | 0.666 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 24.00 | 24.00 | 0.00812 | 25.34 | 0.00882 | 0.052 | 0.00 |
| M N1 APARTMENT | 7038.78 | 8446.54 | 95.71 | 0.502 | 0.603 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 24.00 | 24.00 | 0.00813 | 25.34 | 0.00882 | 0.052 | 0.00 |
| M N2 APARTMENT | 7017.18 | 8420.61 | 95.42 | 0.501 | 0.601 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 24.00 | 24.00 | 0.00813 | 25.34 | 0.00882 | 0.052 | 0.00 |
| M S1 APARTMENT | 8405.95 | 10087.14 | 114.30 | 0.603 | 0.723 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 24.00 | 24.00 | 0.00812 | 25.34 | 0.00882 | 0.052 | 0.00 |
| M S2 APARTMENT | 8381.50 | 10057.80 | 113.97 | 0.601 | 0.721 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 24.00 | 24.00 | 0.00812 | 25.34 | 0.00882 | 0.052 | 0.00 |
| T SW APARTMENT | 5489.31 | 6587.18 | 74.64 | 0.395 | 0.474 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 24.00 | 24.00 | 0.00809 | 25.34 | 0.00882 | 0.026 | 0.00 |
| T NW APARTMENT | 4981.50 | 5977.79 | 67.74 | 0.358 | 0.430 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 24.00 | 24.00 | 0.00809 | 25.34 | 0.00882 | 0.026 | 0.00 |
| T SE APARTMENT | 4568.24 | 5481.88 | 62.12 | 0.328 | 0.394 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 24.00 | 24.00 | 0.00812 | 25.34 | 0.00882 | 0.026 | 0.00 |
| T NE APARTMENT | 4066.05 | 4879.26 | 55.29 | 0.291 | 0.349 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 24.00 | 24.00 | 0.00812 | 25.34 | 0.00882 | 0.026 | 0.00 |
| T N1 APARTMENT | 3877.37 | 4652.84 | 52.72 | 0.277 | 0.333 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 24.00 | 24.00 | 0.00811 | 25.34 | 0.00882 | 0.026 | 0.00 |
| T N2 APARTMENT | 3847.88 | 4617.45 | 52.32 | 0.275 | 0.330 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 24.00 | 24.00 | 0.00811 | 25.34 | 0.00882 | 0.026 | 0.00 |
| T S1 APARTMENT | 4417.47 | 5300.97 | 60.07 | 0.317 | 0.380 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 24.00 | 24.00 | 0.00811 | 25.34 | 0.00882 | 0.026 | 0.00 |
| T S2 APARTMENT | 4387.72 | 5265.26 | 59.66 | 0.315 | 0.378 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 24.00 | 24.00 | 0.00811 | 25.34 | 0.00882 | 0.026 | 0.00 |
| Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
| G SW APARTMENT | 1469.76 | 1763.71 | 19.99 | 0.064 | 0.077 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:50:00 | 21.10 | 21.10 | 0.00737 | -4.20 | 0.00269 | 0.026 | 0.00 |
| G NW APARTMENT | 1355.35 | 1626.42 | 18.43 | 0.059 | 0.071 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | 21.10 | 21.10 | 0.00748 | -4.20 | 0.00269 | 0.026 | 0.00 |
| OFFICE | 1912.12 | 2294.54 | 26.00 | 0.084 | 0.100 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 18:50:00 | 21.10 | 21.10 | 0.00751 | -4.20 | 0.00269 | 0.038 | 0.00 |
| G NE APARTMENT | 1358.52 | 1630.23 | 18.47 | 0.059 | 0.071 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | 21.10 | 21.10 | 0.00748 | -4.20 | 0.00269 | 0.026 | 0.00 |
| G N1 APARTMENT | 779.52 | 935.43 | 10.60 | 0.034 | 0.041 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | 21.10 | 21.10 | 0.00759 | -4.20 | 0.00269 | 0.026 | 0.00 |
| G N2 APARTMENT | 779.62 | 935.55 | 10.60 | 0.034 | 0.041 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | 21.10 | 21.10 | 0.00759 | -4.20 | 0.00269 | 0.026 | 0.00 |
| G S1 APARTMENT | 895.18 | 1074.22 | 12.17 | 0.039 | 0.047 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:50:00 | 21.10 | 21.10 | 0.00737 | -4.20 | 0.00269 | 0.026 | 0.00 |
| G S2 APARTMENT | 903.84 | 1084.60 | 12.29 | 0.040 | 0.047 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:50:00 | 21.10 | 21.10 | 0.00737 | -4.20 | 0.00269 | 0.026 | 0.00 |
| M SW APARTMENT | 2659.75 | 3191.70 | 36.17 | 0.116 | 0.140 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | 21.10 | 21.10 | 0.00708 | -4.20 | 0.00269 | 0.052 | 0.00 |
| M NW APARTMENT | 2386.52 | 2863.83 | 32.45 | 0.104 | 0.125 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | 21.10 | 21.10 | 0.00722 | -4.20 | 0.00269 | 0.052 | 0.00 |
| M SE APARTMENT | 2667.55 | 3201.06 | 36.27 | 0.117 | 0.140 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | 21.10 | 21.10 | 0.00709 | -4.20 | 0.00269 | 0.052 | 0.00 |
| M NE APARTMENT | 2394.39 | 2873.26 | 32.56 | 0.105 | 0.126 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | 21.10 | 21.10 | 0.00722 | -4.20 | 0.00269 | 0.052 | 0.00 |
| M N1 APARTMENT | 1159.51 | 1391.41 | 15.77 | 0.051 | 0.061 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | 21.10 | 21.10 | 0.00722 | -4.20 | 0.00269 | 0.052 | 0.00 |
| M N2 APARTMENT | 1159.73 | 1391.67 | 15.77 | 0.051 | 0.061 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | 21.10 | 21.10 | 0.00722 | -4.20 | 0.00269 | 0.052 | 0.00 |
| M S1 APARTMENT | 1424.89 | 1709.87 | 19.38 | 0.062 | 0.075 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | 21.10 | 21.10 | 0.00697 | -4.20 | 0.00269 | 0.052 | 0.00 |
| M S2 APARTMENT | 1425.10 | 1710.12 | 19.38 | 0.062 | 0.075 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | 21.10 | 21.10 | 0.00697 | -4.20 | 0.00269 | 0.052 | 0.00 |
| T SW APARTMENT | 2335.08 | 2802.10 | 31.75 | 0.102 | 0.122 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | 21.10 | 21.10 | 0.00728 | -4.20 | 0.00269 | 0.026 | 0.00 |
| T NW APARTMENT | 2191.33 | 2629.60 | 29.80 | 0.096 | 0.115 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | 21.10 | 21.10 | 0.00737 | -4.20 | 0.00269 | 0.026 | 0.00 |
| T SE APARTMENT | 2340.88 | 2809.06 | 31.83 | 0.102 | 0.123 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | 21.10 | 21.10 | 0.00728 | -4.20 | 0.00269 | 0.026 | 0.00 |
| T NE APARTMENT | 2197.21 | 2636.66 | 29.88 | 0.096 | 0.115 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | 21.10 | 21.10 | 0.00737 | -4.20 | 0.00269 | 0.026 | 0.00 |
| T N1 APARTMENT | 1459.69 | 1751.62 | 19.85 | 0.064 | 0.077 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | 21.10 | 21.10 | 0.00749 | -4.20 | 0.00269 | 0.026 | 0.00 |
| T N2 APARTMENT | 1459.86 | 1751.83 | 19.85 | 0.064 | 0.077 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | 21.10 | 21.10 | 0.00749 | -4.20 | 0.00269 | 0.026 | 0.00 |
| T S1 APARTMENT | 1603.40 | 1924.08 | 21.80 | 0.070 | 0.084 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | 21.10 | 21.10 | 0.00736 | -4.20 | 0.00269 | 0.026 | 0.00 |
| T S2 APARTMENT | 1603.57 | 1924.28 | 21.81 | 0.070 | 0.084 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | 21.10 | 21.10 | 0.00736 | -4.20 | 0.00269 | 0.026 | 0.00 |
| Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
| SPLIT GSW | 0.36 | 0.36 | 0.08 | 0.08 | 0.3648 | 0.3648 | 0.3648 | 1.0000 | 1.0000 |
| SPLIT GNW | 0.31 | 0.31 | 0.07 | 0.07 | 0.3061 | 0.3061 | 0.3061 | 1.0000 | 1.0000 |
| SPLIT OFFICE | 0.40 | 0.40 | 0.10 | 0.10 | 0.4024 | 0.4024 | 0.4024 | 1.0000 | 1.0000 |
| SPLIT GNE | 0.27 | 0.27 | 0.07 | 0.07 | 0.2688 | 0.2688 | 0.2688 | 1.0000 | 1.0000 |
| SPLIT GN1 | 0.25 | 0.25 | 0.04 | 0.04 | 0.2452 | 0.2452 | 0.2452 | 1.0000 | 1.0000 |
| SPLIT GN2 | 0.24 | 0.24 | 0.04 | 0.04 | 0.2445 | 0.2445 | 0.2445 | 1.0000 | 1.0000 |
| SPLIT GS1 | 0.31 | 0.31 | 0.05 | 0.05 | 0.3085 | 0.3085 | 0.3085 | 1.0000 | 1.0000 |
| SPLIT GS2 | 0.31 | 0.31 | 0.05 | 0.05 | 0.3101 | 0.3101 | 0.3101 | 1.0000 | 1.0000 |
| SPLIT MSW | 0.89 | 0.89 | 0.14 | 0.14 | 0.8855 | 0.8855 | 0.8855 | 1.0000 | 1.0000 |
| SPLIT MNW | 0.78 | 0.78 | 0.13 | 0.13 | 0.7755 | 0.7755 | 0.7755 | 1.0000 | 1.0000 |
| SPLIT MSE | 0.77 | 0.77 | 0.14 | 0.14 | 0.7737 | 0.7737 | 0.7737 | 1.0000 | 1.0000 |
| SPLIT MNE | 0.67 | 0.67 | 0.13 | 0.13 | 0.6664 | 0.6664 | 0.6664 | 1.0000 | 1.0000 |
| SPLIT MN1 | 0.60 | 0.60 | 0.06 | 0.06 | 0.6030 | 0.6030 | 0.6030 | 1.0000 | 1.0000 |
| SPLIT MN2 | 0.60 | 0.60 | 0.06 | 0.06 | 0.6011 | 0.6011 | 0.6011 | 1.0000 | 1.0000 |
| SPLIT MS1 | 0.72 | 0.72 | 0.07 | 0.07 | 0.7232 | 0.7232 | 0.7232 | 1.0000 | 1.0000 |
| SPLIT MS2 | 0.72 | 0.72 | 0.07 | 0.07 | 0.7210 | 0.7210 | 0.7210 | 1.0000 | 1.0000 |
| SPLIT TSW | 0.47 | 0.47 | 0.12 | 0.12 | 0.4745 | 0.4745 | 0.4745 | 1.0000 | 1.0000 |
| SPLIT TNW | 0.43 | 0.43 | 0.11 | 0.11 | 0.4297 | 0.4297 | 0.4297 | 1.0000 | 1.0000 |
| SPLIT TSE | 0.39 | 0.39 | 0.12 | 0.12 | 0.3935 | 0.3935 | 0.3935 | 1.0000 | 1.0000 |
| SPLIT TNE | 0.35 | 0.35 | 0.12 | 0.12 | 0.3494 | 0.3494 | 0.3494 | 1.0000 | 1.0000 |
| SPLIT TN1 | 0.33 | 0.33 | 0.08 | 0.08 | 0.3328 | 0.3328 | 0.3328 | 1.0000 | 1.0000 |
| SPLIT TN2 | 0.33 | 0.33 | 0.08 | 0.08 | 0.3302 | 0.3302 | 0.3302 | 1.0000 | 1.0000 |
| SPLIT TS1 | 0.38 | 0.38 | 0.08 | 0.08 | 0.3803 | 0.3803 | 0.3803 | 1.0000 | 1.0000 |
| SPLIT TS2 | 0.38 | 0.38 | 0.08 | 0.08 | 0.3777 | 0.3777 | 0.3777 | 1.0000 | 1.0000 |
| Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
| None |
| Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
| SPLIT GSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT GSW | 6038.929 | 4835.100 | 0.364812 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 5964.68 | 5798.88 | 0.364812 | 25.06 | 16.33 | 0.00816686 | 12.80 | 11.47 | 0.00800000 | 25.34 | 0.00881502 | 16.98 | 7.1145 | 24.00 | 0.00811722 | 43.1000 | 4239.21 | 0.00 | 6037.90 | 4793.72 |
| SPLIT GSW HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT GSW | 9007.428 | 9007.428 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:50:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:50:00 | 9007.43 | 9007.43 | 0.364812 | 19.30 | 13.16 | 0.00703985 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 7.1145 | 21.10 | 0.00737300 | 46.7447 | 1469.76 | 0.00 | -999.00 | -999.00 |
| SPLIT GNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT GNW | 5067.546 | 4057.357 | 0.306130 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 5006.83 | 4855.31 | 0.306130 | 25.07 | 16.35 | 0.00818220 | 12.80 | 11.47 | 0.00800000 | 25.34 | 0.00881502 | 16.98 | 8.4783 | 24.00 | 0.00812358 | 43.1331 | 3572.32 | 0.00 | 5066.68 | 4022.63 |
| SPLIT GNW HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT GNW | 7684.473 | 7684.473 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | 7684.47 | 7684.47 | 0.306130 | 18.95 | 13.06 | 0.00707453 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 8.4783 | 21.10 | 0.00748067 | 47.4188 | 1355.35 | 0.00 | -999.00 | -999.00 |
| SPLIT OFFICE COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT OFFICE | 6660.943 | 5333.119 | 0.402388 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:10:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | 6600.33 | 6488.33 | 0.402388 | 24.85 | 16.20 | 0.00809932 | 12.80 | 11.47 | 0.00800000 | 23.68 | 0.00881240 | 16.40 | 9.4700 | 23.90 | 0.00801766 | 42.8335 | 4419.31 | 0.00 | 6659.81 | 5287.48 |
| SPLIT OFFICE HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT OFFICE | 10221.217 | 10221.217 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 18:50:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 18:50:00 | 10221.22 | 10221.22 | 0.402388 | 18.70 | 12.93 | 0.00704975 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 9.4700 | 21.10 | 0.00750578 | 47.5765 | 1912.12 | 0.00 | -999.00 | -999.00 |
| SPLIT GNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT GNE | 4449.751 | 3562.716 | 0.268809 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 4399.21 | 4242.65 | 0.268809 | 25.07 | 16.38 | 0.00821548 | 12.80 | 11.47 | 0.00800000 | 25.34 | 0.00881502 | 16.98 | 9.6554 | 24.00 | 0.00815140 | 43.2791 | 3148.93 | 0.00 | 4448.99 | 3532.23 |
| SPLIT GNE HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT GNE | 6843.126 | 6843.126 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | 6843.13 | 6843.13 | 0.268809 | 18.66 | 12.89 | 0.00701906 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 9.6554 | 21.10 | 0.00748169 | 47.4252 | 1358.52 | 0.00 | -999.00 | -999.00 |
| SPLIT GN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT GN1 | 4058.812 | 3249.709 | 0.245193 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 4014.19 | 3858.39 | 0.245193 | 25.07 | 16.39 | 0.00823580 | 12.80 | 11.47 | 0.00800000 | 25.34 | 0.00881502 | 16.98 | 10.5854 | 24.00 | 0.00816723 | 43.3621 | 2879.66 | 0.00 | 4058.12 | 3221.90 |
| SPLIT GN1 HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT GN1 | 6310.677 | 6310.677 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | 6310.68 | 6310.68 | 0.245193 | 18.42 | 12.84 | 0.00707278 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 10.5854 | 21.10 | 0.00759160 | 48.1127 | 779.52 | 0.00 | -999.00 | -999.00 |
| SPLIT GN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT GN2 | 4047.417 | 3240.586 | 0.244504 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 4002.97 | 3847.17 | 0.244504 | 25.07 | 16.39 | 0.00823649 | 12.80 | 11.47 | 0.00800000 | 25.34 | 0.00881502 | 16.98 | 10.6152 | 24.00 | 0.00816779 | 43.3650 | 2871.84 | 0.00 | 4046.73 | 3212.85 |
| SPLIT GN2 HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT GN2 | 6295.159 | 6295.159 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | 6295.16 | 6295.16 | 0.244504 | 18.41 | 12.84 | 0.00707136 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 10.6152 | 21.10 | 0.00759164 | 48.1130 | 779.62 | 0.00 | -999.00 | -999.00 |
| SPLIT GS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT GS1 | 5106.721 | 4088.723 | 0.308497 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 5048.00 | 4873.47 | 0.308497 | 25.07 | 16.37 | 0.00820908 | 12.80 | 11.47 | 0.00800000 | 25.34 | 0.00881502 | 16.98 | 8.4132 | 24.00 | 0.00815342 | 43.2899 | 3599.32 | 0.00 | 5105.85 | 4053.73 |
| SPLIT GS1 HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT GS1 | 7737.820 | 7737.820 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:50:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:50:00 | 7737.82 | 7737.82 | 0.308497 | 18.97 | 12.97 | 0.00697574 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 8.4132 | 21.10 | 0.00736940 | 46.7215 | 895.18 | 0.00 | -999.00 | -999.00 |
| SPLIT GS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT GS2 | 5132.578 | 4109.426 | 0.310059 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 5073.45 | 4898.79 | 0.310059 | 25.07 | 16.37 | 0.00820815 | 12.80 | 11.47 | 0.00800000 | 25.34 | 0.00881502 | 16.98 | 8.3708 | 24.00 | 0.00815271 | 43.2863 | 3616.97 | 0.00 | 5131.70 | 4074.26 |
| SPLIT GS2 HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT GS2 | 7773.034 | 7773.034 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:50:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:50:00 | 7773.03 | 7773.03 | 0.310059 | 18.98 | 12.98 | 0.00698264 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 8.3708 | 21.10 | 0.00737477 | 46.7551 | 903.84 | 0.00 | -999.00 | -999.00 |
| SPLIT MSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT MSW | 14658.705 | 11736.570 | 0.885532 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 14470.17 | 14137.77 | 0.885532 | 25.06 | 16.30 | 0.00813718 | 12.80 | 11.47 | 0.00800000 | 25.34 | 0.00881502 | 16.98 | 5.8619 | 24.00 | 0.00809497 | 42.9831 | 20505.24 | 0.00 | 14656.21 | 11636.13 |
| SPLIT MSW HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT MSW | 21530.461 | 21530.461 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | 21530.46 | 21530.46 | 0.885532 | 19.62 | 13.08 | 0.00682627 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 5.8619 | 21.10 | 0.00708381 | 44.9338 | 5319.51 | 0.00 | -999.00 | -999.00 |
| SPLIT MNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT MNW | 12837.815 | 10278.664 | 0.775532 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 12675.04 | 12365.62 | 0.775532 | 25.06 | 16.31 | 0.00814603 | 12.80 | 11.47 | 0.00800000 | 25.34 | 0.00881502 | 16.98 | 6.6934 | 24.00 | 0.00809804 | 42.9990 | 17999.86 | 0.00 | 12835.63 | 10190.70 |
| SPLIT MNW HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT MNW | 19050.281 | 19050.281 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | 19050.28 | 19050.28 | 0.775532 | 19.41 | 13.08 | 0.00691589 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 6.6934 | 21.10 | 0.00721901 | 45.7808 | 4773.04 | 0.00 | -999.00 | -999.00 |
| SPLIT MSE COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT MSE | 12806.700 | 10253.752 | 0.773653 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 12648.28 | 12303.86 | 0.773653 | 25.06 | 16.33 | 0.00816336 | 12.80 | 11.47 | 0.00800000 | 25.34 | 0.00881502 | 16.98 | 6.7096 | 24.00 | 0.00811649 | 43.0961 | 17956.51 | 0.00 | 12804.52 | 10166.00 |
| SPLIT MSE HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT MSE | 19008.164 | 19008.164 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | 19008.16 | 19008.16 | 0.773653 | 19.40 | 12.96 | 0.00679112 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 6.7096 | 21.10 | 0.00708605 | 44.9479 | 5335.10 | 0.00 | -999.00 | -999.00 |
| SPLIT MNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT MNE | 11031.399 | 8832.348 | 0.666407 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 10897.99 | 10579.07 | 0.666407 | 25.07 | 16.34 | 0.00817600 | 12.80 | 11.47 | 0.00800000 | 25.34 | 0.00881502 | 16.98 | 7.7894 | 24.00 | 0.00812202 | 43.1249 | 15526.81 | 0.00 | 11029.52 | 8756.76 |
| SPLIT MNE HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT MNE | 16590.112 | 16590.112 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | 16590.11 | 16590.11 | 0.666407 | 19.13 | 12.93 | 0.00686820 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 7.7894 | 21.10 | 0.00722112 | 45.7940 | 4788.77 | 0.00 | -999.00 | -999.00 |
| SPLIT MN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT MN1 | 9981.725 | 7991.920 | 0.602996 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 9863.62 | 9551.99 | 0.602996 | 25.07 | 16.35 | 0.00819048 | 12.80 | 11.47 | 0.00800000 | 25.34 | 0.00881502 | 16.98 | 8.6085 | 24.00 | 0.00813165 | 43.1754 | 14077.57 | 0.00 | 9980.03 | 7923.52 |
| SPLIT MN1 HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT MN1 | 15160.229 | 15160.229 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | 15160.23 | 15160.23 | 0.602996 | 18.92 | 12.80 | 0.00682606 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 8.6085 | 21.10 | 0.00721562 | 45.7581 | 2319.02 | 0.00 | -999.00 | -999.00 |
| SPLIT MN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT MN2 | 9950.293 | 7966.754 | 0.601097 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 9832.69 | 9520.93 | 0.601097 | 25.07 | 16.35 | 0.00819117 | 12.80 | 11.47 | 0.00800000 | 25.34 | 0.00881502 | 16.98 | 8.6357 | 24.00 | 0.00813221 | 43.1783 | 14034.36 | 0.00 | 9948.60 | 7898.57 |
| SPLIT MN2 HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT MN2 | 15117.422 | 15117.422 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | 15117.42 | 15117.42 | 0.601097 | 18.91 | 12.80 | 0.00682495 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 8.6357 | 21.10 | 0.00721575 | 45.7589 | 2319.46 | 0.00 | -999.00 | -999.00 |
| SPLIT MS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT MS1 | 11971.638 | 9585.155 | 0.723207 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 11825.39 | 11489.07 | 0.723207 | 25.06 | 16.34 | 0.00817086 | 12.80 | 11.47 | 0.00800000 | 25.34 | 0.00881502 | 16.98 | 7.1776 | 24.00 | 0.00812105 | 43.1200 | 16811.91 | 0.00 | 11969.60 | 9503.12 |
| SPLIT MS1 HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT MS1 | 17870.483 | 17870.483 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | 17870.48 | 17870.48 | 0.723207 | 19.28 | 12.79 | 0.00666131 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 7.1776 | 21.10 | 0.00696837 | 44.2084 | 2849.78 | 0.00 | -999.00 | -999.00 |
| SPLIT MS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT MS2 | 11935.906 | 9556.546 | 0.721048 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 11790.26 | 11453.57 | 0.721048 | 25.06 | 16.34 | 0.00817158 | 12.80 | 11.47 | 0.00800000 | 25.34 | 0.00881502 | 16.98 | 7.1991 | 24.00 | 0.00812166 | 43.1232 | 16763.00 | 0.00 | 11933.87 | 9474.76 |
| SPLIT MS2 HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT MS2 | 17821.820 | 17821.820 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | 17821.82 | 17821.82 | 0.721048 | 19.28 | 12.79 | 0.00666051 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 7.1991 | 21.10 | 0.00696850 | 44.2092 | 2850.20 | 0.00 | -999.00 | -999.00 |
| SPLIT TSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT TSW | 7853.874 | 6288.245 | 0.474453 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 7752.38 | 7578.99 | 0.474453 | 25.06 | 16.30 | 0.00813349 | 12.80 | 11.47 | 0.00800000 | 25.34 | 0.00881502 | 16.98 | 5.4704 | 24.00 | 0.00809405 | 42.9783 | 5489.31 | 0.00 | 7852.54 | 6234.43 |
| SPLIT TSW HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT TSW | 11479.855 | 11479.855 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | 11479.86 | 11479.86 | 0.474453 | 19.71 | 13.31 | 0.00703013 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 5.4704 | 21.10 | 0.00728127 | 46.1733 | 2335.08 | 0.00 | -999.00 | -999.00 |
| SPLIT TNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT TNW | 7113.827 | 5695.723 | 0.429746 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 7022.63 | 6861.12 | 0.429746 | 25.06 | 16.31 | 0.00813739 | 12.80 | 11.47 | 0.00800000 | 25.34 | 0.00881502 | 16.98 | 6.0395 | 24.00 | 0.00809384 | 42.9770 | 4981.50 | 0.00 | 7112.62 | 5646.98 |
| SPLIT TNW HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT TNW | 10471.791 | 10471.791 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | 10471.79 | 10471.79 | 0.429746 | 19.57 | 13.31 | 0.00708470 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 6.0395 | 21.10 | 0.00736715 | 46.7106 | 2191.33 | 0.00 | -999.00 | -999.00 |
| SPLIT TSE COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT TSE | 6514.175 | 5215.608 | 0.393521 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 6433.92 | 6257.76 | 0.393521 | 25.07 | 16.33 | 0.00816433 | 12.80 | 11.47 | 0.00800000 | 25.34 | 0.00881502 | 16.98 | 6.5955 | 24.00 | 0.00811838 | 43.1060 | 4568.24 | 0.00 | 6513.07 | 5170.97 |
| SPLIT TSE HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT TSE | 9655.235 | 9655.235 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | 9655.23 | 9655.23 | 0.393521 | 19.43 | 13.15 | 0.00697992 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 6.5955 | 21.10 | 0.00728282 | 46.1830 | 2340.88 | 0.00 | -999.00 | -999.00 |
| SPLIT TNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT TNE | 5783.701 | 4630.750 | 0.349393 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 5713.33 | 5550.73 | 0.349393 | 25.07 | 16.34 | 0.00817104 | 12.80 | 11.47 | 0.00800000 | 25.34 | 0.00881502 | 16.98 | 7.4285 | 24.00 | 0.00811936 | 43.1109 | 4066.05 | 0.00 | 5782.72 | 4591.12 |
| SPLIT TNE HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT TNE | 8660.237 | 8660.237 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | 8660.24 | 8660.24 | 0.349393 | 19.22 | 13.11 | 0.00702108 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 7.4285 | 21.10 | 0.00736861 | 46.7198 | 2197.21 | 0.00 | -999.00 | -999.00 |
| SPLIT TN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT TN1 | 5508.354 | 4410.292 | 0.332760 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 5440.98 | 5290.15 | 0.332760 | 25.07 | 16.33 | 0.00816651 | 12.80 | 11.47 | 0.00800000 | 25.34 | 0.00881502 | 16.98 | 7.7998 | 24.00 | 0.00811165 | 43.0704 | 3877.37 | 0.00 | 5507.42 | 4372.55 |
| SPLIT TN1 HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT TN1 | 8284.978 | 8284.978 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | 8284.98 | 8284.98 | 0.332760 | 19.13 | 13.17 | 0.00711957 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 7.7998 | 21.10 | 0.00749427 | 47.5050 | 1459.69 | 0.00 | -999.00 | -999.00 |
| SPLIT TN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT TN2 | 5465.256 | 4375.786 | 0.330156 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 5398.57 | 5247.65 | 0.330156 | 25.07 | 16.34 | 0.00816796 | 12.80 | 11.47 | 0.00800000 | 25.34 | 0.00881502 | 16.98 | 7.8613 | 24.00 | 0.00811275 | 43.0762 | 3847.88 | 0.00 | 5464.33 | 4338.34 |
| SPLIT TN2 HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT TN2 | 8226.284 | 8226.284 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | 8226.28 | 8226.28 | 0.330156 | 19.11 | 13.16 | 0.00711667 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 7.8613 | 21.10 | 0.00749433 | 47.5054 | 1459.86 | 0.00 | -999.00 | -999.00 |
| SPLIT TS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT TS1 | 6295.201 | 5040.286 | 0.380293 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 6217.12 | 6052.01 | 0.380293 | 25.07 | 16.33 | 0.00815927 | 12.80 | 11.47 | 0.00800000 | 25.34 | 0.00881502 | 16.98 | 6.8249 | 24.00 | 0.00811124 | 43.0684 | 4417.47 | 0.00 | 6294.13 | 4997.15 |
| SPLIT TS1 HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT TS1 | 9356.716 | 9356.716 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | 9356.72 | 9356.72 | 0.380293 | 19.37 | 13.19 | 0.00703838 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 6.8249 | 21.10 | 0.00735687 | 46.6451 | 1603.40 | 0.00 | -999.00 | -999.00 |
| SPLIT TS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT TS2 | 6251.909 | 5005.624 | 0.377678 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 6174.53 | 6009.22 | 0.377678 | 25.07 | 16.33 | 0.00816059 | 12.80 | 11.47 | 0.00800000 | 25.34 | 0.00881502 | 16.98 | 6.8721 | 24.00 | 0.00811230 | 43.0740 | 4387.72 | 0.00 | 6250.85 | 4962.79 |
| SPLIT TS2 HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT TS2 | 9297.757 | 9297.757 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | 9297.76 | 9297.76 | 0.377678 | 19.36 | 13.18 | 0.00703623 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 6.8721 | 21.10 | 0.00735693 | 46.6455 | 1603.57 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 09:15:24
Coils| Coil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
| SPLIT GSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT GSW | G SW APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 6038.929 | 4835.100 | 0.364812 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.0218 | 1004.8586 | 1.1870 | SPLIT GSW SUPPLY FAN | Fan:OnOff | 0.364812 | 0.43302814 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | Sensible | 5964.68 | 5798.88 | 0.9877 | 0.43302814 | 0.364812 | 25.06 | 16.33 | 0.00816686 | 45989.1 | 12.80 | 11.47 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 408.629 | 5556.05 | 25.34 | 0.00881502 | 16.98 | 0.02595455 | 7.1145 | 24.04 | 0.00811722 | 24.00 | 0.00811722 | 43.1000 | 4239.21 | 0.00 | 6037.90 | 4793.72 | 0.41592680 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 15.41 | 14.58 | 0.01001182 | 40805.6 | |
| SPLIT GSW HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT GSW | G SW APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 9007.428 | 9007.428 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | SPLIT GSW SUPPLY FAN | Fan:OnOff | 0.364812 | 0.43302814 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:50:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:50:00 | Sensible | 9007.43 | 9007.43 | 1.0000 | 0.43302814 | 0.364812 | 19.30 | 13.16 | 0.00703985 | 37251.8 | 40.00 | 21.01 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9007.43 | -4.20 | 0.00269032 | -4.20 | 0.02595455 | 7.1145 | 21.10 | 0.00737300 | 21.10 | 0.00737300 | 46.7447 | 1469.76 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT GNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT GNW | G NW APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 5067.546 | 4057.357 | 0.306130 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.0503 | 1004.8586 | 1.1870 | SPLIT GNW SUPPLY FAN | Fan:OnOff | 0.306130 | 0.36337400 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | Sensible | 5006.83 | 4855.31 | 0.9880 | 0.36337400 | 0.306130 | 25.07 | 16.35 | 0.00818220 | 46033.6 | 12.80 | 11.47 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 342.899 | 4663.94 | 25.34 | 0.00881502 | 16.98 | 0.02595455 | 8.4783 | 24.03 | 0.00812358 | 24.00 | 0.00812358 | 43.1331 | 3572.32 | 0.00 | 5066.68 | 4022.63 | 0.34902347 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 15.41 | 14.58 | 0.01001182 | 40805.6 | |
| SPLIT GNW HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT GNW | G NW APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 7684.473 | 7684.473 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | SPLIT GNW SUPPLY FAN | Fan:OnOff | 0.306130 | 0.36337400 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | Sensible | 7684.47 | 7684.47 | 1.0000 | 0.36337400 | 0.306130 | 18.95 | 13.06 | 0.00707453 | 36988.7 | 40.00 | 21.01 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 7684.47 | -4.20 | 0.00269032 | -4.20 | 0.02595455 | 8.4783 | 21.10 | 0.00748067 | 21.10 | 0.00748067 | 47.4188 | 1355.35 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT OFFICE COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT OFFICE | OFFICE | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 6660.943 | 5333.119 | 0.402388 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.8962 | 1004.8586 | 1.1870 | SPLIT OFFICE SUPPLY FAN | Fan:OnOff | 0.402388 | 0.47763034 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:10:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:10:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | Sensible | 6600.33 | 6488.33 | 0.9909 | 0.47763034 | 0.402388 | 24.85 | 16.20 | 0.00809932 | 45604.6 | 12.80 | 11.47 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 450.718 | 6149.61 | 23.68 | 0.00881240 | 16.40 | 0.03810604 | 9.4700 | 23.95 | 0.00802472 | 23.90 | 0.00801766 | 42.8335 | 4419.31 | 0.00 | 6659.81 | 5287.48 | 0.45876755 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 15.41 | 14.58 | 0.01001182 | 40805.6 | |
| SPLIT OFFICE HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT OFFICE | OFFICE | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 10221.217 | 10221.217 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | SPLIT OFFICE SUPPLY FAN | Fan:OnOff | 0.402388 | 0.47763034 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 18:50:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 18:50:00 | Sensible | 10221.22 | 10221.22 | 1.0000 | 0.47763034 | 0.402388 | 18.70 | 12.93 | 0.00704975 | 36670.3 | 40.00 | 21.01 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10221.22 | -4.20 | 0.00269032 | -4.20 | 0.03810604 | 9.4700 | 21.10 | 0.00750578 | 21.10 | 0.00750578 | 47.5765 | 1912.12 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT GNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT GNE | G NE APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 4449.751 | 3562.716 | 0.268809 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.1122 | 1004.8586 | 1.1870 | SPLIT GNE SUPPLY FAN | Fan:OnOff | 0.268809 | 0.31907434 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | Sensible | 4399.21 | 4242.65 | 0.9886 | 0.31907434 | 0.268809 | 25.07 | 16.38 | 0.00821548 | 46121.7 | 12.80 | 11.47 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 301.096 | 4098.11 | 25.34 | 0.00881502 | 16.98 | 0.02595455 | 9.6554 | 24.02 | 0.00815140 | 24.00 | 0.00815140 | 43.2791 | 3148.93 | 0.00 | 4448.99 | 3532.23 | 0.30647332 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 15.41 | 14.58 | 0.01001182 | 40805.6 | |
| SPLIT GNE HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT GNE | G NE APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 6843.126 | 6843.126 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | SPLIT GNE SUPPLY FAN | Fan:OnOff | 0.268809 | 0.31907434 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | Sensible | 6843.13 | 6843.13 | 1.0000 | 0.31907434 | 0.268809 | 18.66 | 12.89 | 0.00701906 | 36544.9 | 40.00 | 21.01 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 6843.13 | -4.20 | 0.00269032 | -4.20 | 0.02595455 | 9.6554 | 21.10 | 0.00748169 | 21.10 | 0.00748169 | 47.4252 | 1358.52 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT GN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT GN1 | G N1 APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 4058.812 | 3249.709 | 0.245193 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.1499 | 1004.8586 | 1.1870 | SPLIT GN1 SUPPLY FAN | Fan:OnOff | 0.245193 | 0.29104164 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | Sensible | 4014.19 | 3858.39 | 0.9890 | 0.29104164 | 0.245193 | 25.07 | 16.39 | 0.00823580 | 46173.6 | 12.80 | 11.47 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 274.642 | 3739.55 | 25.34 | 0.00881502 | 16.98 | 0.02595455 | 10.5854 | 24.00 | 0.00816723 | 24.00 | 0.00816723 | 43.3621 | 2879.66 | 0.00 | 4058.12 | 3221.90 | 0.27954770 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 15.41 | 14.58 | 0.01001182 | 40805.6 | |
| SPLIT GN1 HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT GN1 | G N1 APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 6310.677 | 6310.677 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | SPLIT GN1 SUPPLY FAN | Fan:OnOff | 0.245193 | 0.29104164 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | Sensible | 6310.68 | 6310.68 | 1.0000 | 0.29104164 | 0.245193 | 18.42 | 12.84 | 0.00707278 | 36441.7 | 40.00 | 21.01 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 6310.68 | -4.20 | 0.00269032 | -4.20 | 0.02595455 | 10.5854 | 21.10 | 0.00759160 | 21.10 | 0.00759160 | 48.1127 | 779.52 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT GN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT GN2 | G N2 APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 4047.417 | 3240.586 | 0.244504 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.1512 | 1004.8586 | 1.1870 | SPLIT GN2 SUPPLY FAN | Fan:OnOff | 0.244504 | 0.29022454 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | Sensible | 4002.97 | 3847.17 | 0.9890 | 0.29022454 | 0.244504 | 25.07 | 16.39 | 0.00823649 | 46175.4 | 12.80 | 11.47 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 273.871 | 3729.10 | 25.34 | 0.00881502 | 16.98 | 0.02595455 | 10.6152 | 24.00 | 0.00816779 | 24.00 | 0.00816779 | 43.3650 | 2871.84 | 0.00 | 4046.73 | 3212.85 | 0.27876286 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 15.41 | 14.58 | 0.01001182 | 40805.6 | |
| SPLIT GN2 HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT GN2 | G N2 APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 6295.159 | 6295.159 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | SPLIT GN2 SUPPLY FAN | Fan:OnOff | 0.244504 | 0.29022454 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | Sensible | 6295.16 | 6295.16 | 1.0000 | 0.29022454 | 0.244504 | 18.41 | 12.84 | 0.00707136 | 36430.5 | 40.00 | 21.01 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 6295.16 | -4.20 | 0.00269032 | -4.20 | 0.02595455 | 10.6152 | 21.10 | 0.00759164 | 21.10 | 0.00759164 | 48.1130 | 779.62 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT GS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT GS1 | G S1 APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 5106.721 | 4088.723 | 0.308497 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.1003 | 1004.8586 | 1.1870 | SPLIT GS1 SUPPLY FAN | Fan:OnOff | 0.308497 | 0.36618312 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | Sensible | 5048.00 | 4873.47 | 0.9885 | 0.36618312 | 0.308497 | 25.07 | 16.37 | 0.00820908 | 46101.9 | 12.80 | 11.47 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 345.550 | 4702.45 | 25.34 | 0.00881502 | 16.98 | 0.02595455 | 8.4132 | 24.03 | 0.00815342 | 24.00 | 0.00815342 | 43.2899 | 3599.32 | 0.00 | 5105.85 | 4053.73 | 0.35172165 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 15.41 | 14.58 | 0.01001182 | 40805.6 | |
| SPLIT GS1 HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT GS1 | G S1 APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 7737.820 | 7737.820 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | SPLIT GS1 SUPPLY FAN | Fan:OnOff | 0.308497 | 0.36618312 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:50:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:50:00 | Sensible | 7737.82 | 7737.82 | 1.0000 | 0.36618312 | 0.308497 | 18.97 | 12.97 | 0.00697574 | 36754.9 | 40.00 | 21.01 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 7737.82 | -4.20 | 0.00269032 | -4.20 | 0.02595455 | 8.4132 | 21.10 | 0.00736940 | 21.10 | 0.00736940 | 46.7215 | 895.18 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT GS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT GS2 | G S2 APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 5132.578 | 4109.426 | 0.310059 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.0985 | 1004.8586 | 1.1870 | SPLIT GS2 SUPPLY FAN | Fan:OnOff | 0.310059 | 0.36803725 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | Sensible | 5073.45 | 4898.79 | 0.9885 | 0.36803725 | 0.310059 | 25.07 | 16.37 | 0.00820815 | 46099.0 | 12.80 | 11.47 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 347.300 | 4726.15 | 25.34 | 0.00881502 | 16.98 | 0.02595455 | 8.3708 | 24.03 | 0.00815271 | 24.00 | 0.00815271 | 43.2863 | 3616.97 | 0.00 | 5131.70 | 4074.26 | 0.35350256 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 15.41 | 14.58 | 0.01001182 | 40805.6 | |
| SPLIT GS2 HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT GS2 | G S2 APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 7773.034 | 7773.034 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | SPLIT GS2 SUPPLY FAN | Fan:OnOff | 0.310059 | 0.36803725 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:50:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:50:00 | Sensible | 7773.03 | 7773.03 | 1.0000 | 0.36803725 | 0.310059 | 18.98 | 12.98 | 0.00698264 | 36783.3 | 40.00 | 21.01 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 7773.03 | -4.20 | 0.00269032 | -4.20 | 0.02595455 | 8.3708 | 21.10 | 0.00737477 | 21.10 | 0.00737477 | 46.7551 | 903.84 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT MSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT MSW | M SW APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 14658.705 | 11736.570 | 0.885532 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.9666 | 1004.8586 | 1.1870 | SPLIT MSW SUPPLY FAN | Fan:OnOff | 0.885532 | 1.05111880 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | Sensible | 14470.17 | 14137.77 | 0.9871 | 1.05111880 | 0.885532 | 25.06 | 16.30 | 0.00813718 | 45909.1 | 12.80 | 11.47 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 991.892 | 13478.28 | 25.34 | 0.00881502 | 16.98 | 0.05190911 | 5.8619 | 24.06 | 0.00809497 | 24.00 | 0.00809497 | 42.9831 | 20505.24 | 0.00 | 14656.21 | 11636.13 | 1.00960755 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 15.41 | 14.58 | 0.01001182 | 40805.6 | |
| SPLIT MSW HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT MSW | M SW APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 21530.461 | 21530.461 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | SPLIT MSW SUPPLY FAN | Fan:OnOff | 0.885532 | 1.05111880 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | Sensible | 21530.46 | 21530.46 | 1.0000 | 1.05111880 | 0.885532 | 19.62 | 13.08 | 0.00682627 | 37031.6 | 40.00 | 21.01 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 21530.46 | -4.20 | 0.00269032 | -4.20 | 0.05190911 | 5.8619 | 21.10 | 0.00708381 | 21.10 | 0.00708381 | 44.9338 | 5319.51 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT MNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT MNW | M NW APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 12837.815 | 10278.664 | 0.775532 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.9831 | 1004.8586 | 1.1870 | SPLIT MNW SUPPLY FAN | Fan:OnOff | 0.775532 | 0.92054979 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | Sensible | 12675.04 | 12365.62 | 0.9873 | 0.92054979 | 0.775532 | 25.06 | 16.31 | 0.00814603 | 45934.7 | 12.80 | 11.47 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 868.680 | 11806.36 | 25.34 | 0.00881502 | 16.98 | 0.05190911 | 6.6934 | 24.05 | 0.00809804 | 24.00 | 0.00809804 | 42.9990 | 17999.86 | 0.00 | 12835.63 | 10190.70 | 0.88419503 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 15.41 | 14.58 | 0.01001182 | 40805.6 | |
| SPLIT MNW HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT MNW | M NW APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 19050.281 | 19050.281 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | SPLIT MNW SUPPLY FAN | Fan:OnOff | 0.775532 | 0.92054979 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | Sensible | 19050.28 | 19050.28 | 1.0000 | 0.92054979 | 0.775532 | 19.41 | 13.08 | 0.00691589 | 37045.2 | 40.00 | 21.01 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 19050.28 | -4.20 | 0.00269032 | -4.20 | 0.05190911 | 6.6934 | 21.10 | 0.00721901 | 21.10 | 0.00721901 | 45.7808 | 4773.04 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT MSE COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT MSE | M SE APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 12806.700 | 10253.752 | 0.773653 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.0153 | 1004.8586 | 1.1870 | SPLIT MSE SUPPLY FAN | Fan:OnOff | 0.773653 | 0.91831867 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | Sensible | 12648.28 | 12303.86 | 0.9876 | 0.91831867 | 0.773653 | 25.06 | 16.33 | 0.00816336 | 45978.6 | 12.80 | 11.47 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 866.575 | 11781.70 | 25.34 | 0.00881502 | 16.98 | 0.05190911 | 6.7096 | 24.05 | 0.00811649 | 24.00 | 0.00811649 | 43.0961 | 17956.51 | 0.00 | 12804.52 | 10166.00 | 0.88205202 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 15.41 | 14.58 | 0.01001182 | 40805.6 | |
| SPLIT MSE HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT MSE | M SE APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 19008.164 | 19008.164 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | SPLIT MSE SUPPLY FAN | Fan:OnOff | 0.773653 | 0.91831867 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | Sensible | 19008.16 | 19008.16 | 1.0000 | 0.91831867 | 0.773653 | 19.40 | 12.96 | 0.00679112 | 36724.2 | 40.00 | 21.01 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 19008.16 | -4.20 | 0.00269032 | -4.20 | 0.05190911 | 6.7096 | 21.10 | 0.00708605 | 21.10 | 0.00708605 | 44.9479 | 5335.10 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT MNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT MNE | M NE APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 11031.399 | 8832.348 | 0.666407 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.0388 | 1004.8586 | 1.1870 | SPLIT MNE SUPPLY FAN | Fan:OnOff | 0.666407 | 0.79101873 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | Sensible | 10897.99 | 10579.07 | 0.9879 | 0.79101873 | 0.666407 | 25.07 | 16.34 | 0.00817600 | 46017.5 | 12.80 | 11.47 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 746.448 | 10151.54 | 25.34 | 0.00881502 | 16.98 | 0.05190911 | 7.7894 | 24.04 | 0.00812202 | 24.00 | 0.00812202 | 43.1249 | 15526.81 | 0.00 | 11029.52 | 8756.76 | 0.75977947 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 15.41 | 14.58 | 0.01001182 | 40805.6 | |
| SPLIT MNE HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT MNE | M NE APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 16590.112 | 16590.112 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | SPLIT MNE SUPPLY FAN | Fan:OnOff | 0.666407 | 0.79101873 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | Sensible | 16590.11 | 16590.11 | 1.0000 | 0.79101873 | 0.666407 | 19.13 | 12.93 | 0.00686820 | 36642.1 | 40.00 | 21.01 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 16590.11 | -4.20 | 0.00269032 | -4.20 | 0.05190911 | 7.7894 | 21.10 | 0.00722112 | 21.10 | 0.00722112 | 45.7940 | 4788.77 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT MN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT MN1 | M N1 APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 9981.725 | 7991.920 | 0.602996 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.0657 | 1004.8586 | 1.1870 | SPLIT MN1 SUPPLY FAN | Fan:OnOff | 0.602996 | 0.71575068 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | Sensible | 9863.62 | 9551.99 | 0.9882 | 0.71575068 | 0.602996 | 25.07 | 16.35 | 0.00819048 | 46054.6 | 12.80 | 11.47 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 675.421 | 9188.20 | 25.34 | 0.00881502 | 16.98 | 0.05190911 | 8.6085 | 24.03 | 0.00813165 | 24.00 | 0.00813165 | 43.1754 | 14077.57 | 0.00 | 9980.03 | 7923.52 | 0.68748393 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 15.41 | 14.58 | 0.01001182 | 40805.6 | |
| SPLIT MN1 HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT MN1 | M N1 APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 15160.229 | 15160.229 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | SPLIT MN1 SUPPLY FAN | Fan:OnOff | 0.602996 | 0.71575068 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | Sensible | 15160.23 | 15160.23 | 1.0000 | 0.71575068 | 0.602996 | 18.92 | 12.80 | 0.00682606 | 36324.8 | 40.00 | 21.01 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 15160.23 | -4.20 | 0.00269032 | -4.20 | 0.05190911 | 8.6085 | 21.10 | 0.00721562 | 21.10 | 0.00721562 | 45.7581 | 2319.02 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT MN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT MN2 | M N2 APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 9950.293 | 7966.754 | 0.601097 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.0670 | 1004.8586 | 1.1870 | SPLIT MN2 SUPPLY FAN | Fan:OnOff | 0.601097 | 0.71349681 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | Sensible | 9832.69 | 9520.93 | 0.9882 | 0.71349681 | 0.601097 | 25.07 | 16.35 | 0.00819117 | 46056.5 | 12.80 | 11.47 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 673.294 | 9159.39 | 25.34 | 0.00881502 | 16.98 | 0.05190911 | 8.6357 | 24.03 | 0.00813221 | 24.00 | 0.00813221 | 43.1783 | 14034.36 | 0.00 | 9948.60 | 7898.57 | 0.68531908 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 15.41 | 14.58 | 0.01001182 | 40805.6 | |
| SPLIT MN2 HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT MN2 | M N2 APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 15117.422 | 15117.422 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | SPLIT MN2 SUPPLY FAN | Fan:OnOff | 0.601097 | 0.71349681 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | Sensible | 15117.42 | 15117.42 | 1.0000 | 0.71349681 | 0.601097 | 18.91 | 12.80 | 0.00682495 | 36315.0 | 40.00 | 21.01 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 15117.42 | -4.20 | 0.00269032 | -4.20 | 0.05190911 | 8.6357 | 21.10 | 0.00721575 | 21.10 | 0.00721575 | 45.7589 | 2319.46 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT MS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT MS1 | M S1 APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 11971.638 | 9585.155 | 0.723207 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.0292 | 1004.8586 | 1.1870 | SPLIT MS1 SUPPLY FAN | Fan:OnOff | 0.723207 | 0.85843959 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | Sensible | 11825.39 | 11489.07 | 0.9878 | 0.85843959 | 0.723207 | 25.06 | 16.34 | 0.00817086 | 46000.3 | 12.80 | 11.47 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 810.069 | 11015.32 | 25.34 | 0.00881502 | 16.98 | 0.05190911 | 7.1776 | 24.05 | 0.00812105 | 24.00 | 0.00812105 | 43.1200 | 16811.91 | 0.00 | 11969.60 | 9503.12 | 0.82453772 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 15.41 | 14.58 | 0.01001182 | 40805.6 | |
| SPLIT MS1 HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT MS1 | M S1 APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 17870.483 | 17870.483 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | SPLIT MS1 SUPPLY FAN | Fan:OnOff | 0.723207 | 0.85843959 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | Sensible | 17870.48 | 17870.48 | 1.0000 | 0.85843959 | 0.723207 | 19.28 | 12.79 | 0.00666131 | 36274.9 | 40.00 | 21.01 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 17870.48 | -4.20 | 0.00269032 | -4.20 | 0.05190911 | 7.1776 | 21.10 | 0.00696837 | 21.10 | 0.00696837 | 44.2084 | 2849.78 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT MS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT MS2 | M S2 APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 11935.906 | 9556.546 | 0.721048 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.0306 | 1004.8586 | 1.1870 | SPLIT MS2 SUPPLY FAN | Fan:OnOff | 0.721048 | 0.85587742 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | Sensible | 11790.26 | 11453.57 | 0.9878 | 0.85587742 | 0.721048 | 25.06 | 16.34 | 0.00817158 | 46002.3 | 12.80 | 11.47 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 807.652 | 10982.61 | 25.34 | 0.00881502 | 16.98 | 0.05190911 | 7.1991 | 24.04 | 0.00812166 | 24.00 | 0.00812166 | 43.1232 | 16763.00 | 0.00 | 11933.87 | 9474.76 | 0.82207673 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 15.41 | 14.58 | 0.01001182 | 40805.6 | |
| SPLIT MS2 HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT MS2 | M S2 APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 17821.820 | 17821.820 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | SPLIT MS2 SUPPLY FAN | Fan:OnOff | 0.721048 | 0.85587742 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | Sensible | 17821.82 | 17821.82 | 1.0000 | 0.85587742 | 0.721048 | 19.28 | 12.79 | 0.00666051 | 36267.4 | 40.00 | 21.01 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 17821.82 | -4.20 | 0.00269032 | -4.20 | 0.05190911 | 7.1991 | 21.10 | 0.00696850 | 21.10 | 0.00696850 | 44.2092 | 2850.20 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT TSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT TSW | T SW APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 7853.874 | 6288.245 | 0.474453 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.9597 | 1004.8586 | 1.1870 | SPLIT TSW SUPPLY FAN | Fan:OnOff | 0.474453 | 0.56317075 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | Sensible | 7752.38 | 7578.99 | 0.9871 | 0.56317075 | 0.474453 | 25.06 | 16.30 | 0.00813349 | 45900.3 | 12.80 | 11.47 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 531.438 | 7220.94 | 25.34 | 0.00881502 | 16.98 | 0.02595455 | 5.4704 | 24.06 | 0.00809405 | 24.00 | 0.00809405 | 42.9783 | 5489.31 | 0.00 | 7852.54 | 6234.43 | 0.54092977 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 15.41 | 14.58 | 0.01001182 | 40805.6 | |
| SPLIT TSW HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT TSW | T SW APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 11479.855 | 11479.855 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | SPLIT TSW SUPPLY FAN | Fan:OnOff | 0.474453 | 0.56317075 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | Sensible | 11479.86 | 11479.86 | 1.0000 | 0.56317075 | 0.474453 | 19.71 | 13.31 | 0.00703013 | 37649.2 | 40.00 | 21.01 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 11479.86 | -4.20 | 0.00269032 | -4.20 | 0.02595455 | 5.4704 | 21.10 | 0.00728127 | 21.10 | 0.00728127 | 46.1733 | 2335.08 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT TNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT TNW | T NW APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 7113.827 | 5695.723 | 0.429746 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.9670 | 1004.8586 | 1.1870 | SPLIT TNW SUPPLY FAN | Fan:OnOff | 0.429746 | 0.51010491 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | Sensible | 7022.63 | 6861.12 | 0.9872 | 0.51010491 | 0.429746 | 25.06 | 16.31 | 0.00813739 | 45914.8 | 12.80 | 11.47 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 481.362 | 6541.27 | 25.34 | 0.00881502 | 16.98 | 0.02595455 | 6.0395 | 24.06 | 0.00809384 | 24.00 | 0.00809384 | 42.9770 | 4981.50 | 0.00 | 7112.62 | 5646.98 | 0.48995963 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 15.41 | 14.58 | 0.01001182 | 40805.6 | |
| SPLIT TNW HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT TNW | T NW APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 10471.791 | 10471.791 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | SPLIT TNW SUPPLY FAN | Fan:OnOff | 0.429746 | 0.51010491 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | Sensible | 10471.79 | 10471.79 | 1.0000 | 0.51010491 | 0.429746 | 19.57 | 13.31 | 0.00708470 | 37641.4 | 40.00 | 21.01 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10471.79 | -4.20 | 0.00269032 | -4.20 | 0.02595455 | 6.0395 | 21.10 | 0.00736715 | 21.10 | 0.00736715 | 46.7106 | 2191.33 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT TSE COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT TSE | T SE APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 6514.175 | 5215.608 | 0.393521 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.0171 | 1004.8586 | 1.1870 | SPLIT TSE SUPPLY FAN | Fan:OnOff | 0.393521 | 0.46710616 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | Sensible | 6433.92 | 6257.76 | 0.9877 | 0.46710616 | 0.393521 | 25.07 | 16.33 | 0.00816433 | 45985.6 | 12.80 | 11.47 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 440.786 | 5993.14 | 25.34 | 0.00881502 | 16.98 | 0.02595455 | 6.5955 | 24.06 | 0.00811838 | 24.00 | 0.00811838 | 43.1060 | 4568.24 | 0.00 | 6513.07 | 5170.97 | 0.44865900 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 15.41 | 14.58 | 0.01001182 | 40805.6 | |
| SPLIT TSE HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT TSE | T SE APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 9655.235 | 9655.235 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | SPLIT TSE SUPPLY FAN | Fan:OnOff | 0.393521 | 0.46710616 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | Sensible | 9655.23 | 9655.23 | 1.0000 | 0.46710616 | 0.393521 | 19.43 | 13.15 | 0.00697992 | 37232.1 | 40.00 | 21.01 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9655.23 | -4.20 | 0.00269032 | -4.20 | 0.02595455 | 6.5955 | 21.10 | 0.00728282 | 21.10 | 0.00728282 | 46.1830 | 2340.88 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT TNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT TNE | T NE APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 5783.701 | 4630.750 | 0.349393 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.0296 | 1004.8586 | 1.1870 | SPLIT TNE SUPPLY FAN | Fan:OnOff | 0.349393 | 0.41472670 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | Sensible | 5713.33 | 5550.73 | 0.9878 | 0.41472670 | 0.349393 | 25.07 | 16.34 | 0.00817104 | 46007.0 | 12.80 | 11.47 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 391.358 | 5321.97 | 25.34 | 0.00881502 | 16.98 | 0.02595455 | 7.4285 | 24.05 | 0.00811936 | 24.00 | 0.00811936 | 43.1109 | 4066.05 | 0.00 | 5782.72 | 4591.12 | 0.39834813 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 15.41 | 14.58 | 0.01001182 | 40805.6 | |
| SPLIT TNE HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT TNE | T NE APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 8660.237 | 8660.237 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | SPLIT TNE SUPPLY FAN | Fan:OnOff | 0.349393 | 0.41472670 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | Sensible | 8660.24 | 8660.24 | 1.0000 | 0.41472670 | 0.349393 | 19.22 | 13.11 | 0.00702108 | 37122.3 | 40.00 | 21.01 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8660.24 | -4.20 | 0.00269032 | -4.20 | 0.02595455 | 7.4285 | 21.10 | 0.00736861 | 21.10 | 0.00736861 | 46.7198 | 2197.21 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT TN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT TN1 | T N1 APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 5508.354 | 4410.292 | 0.332760 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.0211 | 1004.8586 | 1.1870 | SPLIT TN1 SUPPLY FAN | Fan:OnOff | 0.332760 | 0.39498263 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | Sensible | 5440.98 | 5290.15 | 0.9878 | 0.39498263 | 0.332760 | 25.07 | 16.33 | 0.00816651 | 45997.9 | 12.80 | 11.47 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 372.727 | 5068.25 | 25.34 | 0.00881502 | 16.98 | 0.02595455 | 7.7998 | 24.05 | 0.00811165 | 24.00 | 0.00811165 | 43.0704 | 3877.37 | 0.00 | 5507.42 | 4372.55 | 0.37938380 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 15.41 | 14.58 | 0.01001182 | 40805.6 | |
| SPLIT TN1 HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT TN1 | T N1 APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 8284.978 | 8284.978 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | SPLIT TN1 SUPPLY FAN | Fan:OnOff | 0.332760 | 0.39498263 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | Sensible | 8284.98 | 8284.98 | 1.0000 | 0.39498263 | 0.332760 | 19.13 | 13.17 | 0.00711957 | 37277.2 | 40.00 | 21.01 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8284.98 | -4.20 | 0.00269032 | -4.20 | 0.02595455 | 7.7998 | 21.10 | 0.00749427 | 21.10 | 0.00749427 | 47.5050 | 1459.69 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT TN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT TN2 | T N2 APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 5465.256 | 4375.786 | 0.330156 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.0238 | 1004.8586 | 1.1870 | SPLIT TN2 SUPPLY FAN | Fan:OnOff | 0.330156 | 0.39189224 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | Sensible | 5398.57 | 5247.65 | 0.9878 | 0.39189224 | 0.330156 | 25.07 | 16.34 | 0.00816796 | 46002.1 | 12.80 | 11.47 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 369.810 | 5028.76 | 25.34 | 0.00881502 | 16.98 | 0.02595455 | 7.8613 | 24.05 | 0.00811275 | 24.00 | 0.00811275 | 43.0762 | 3847.88 | 0.00 | 5464.33 | 4338.34 | 0.37641546 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 15.41 | 14.58 | 0.01001182 | 40805.6 | |
| SPLIT TN2 HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT TN2 | T N2 APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 8226.284 | 8226.284 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | SPLIT TN2 SUPPLY FAN | Fan:OnOff | 0.330156 | 0.39189224 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | Sensible | 8226.28 | 8226.28 | 1.0000 | 0.39189224 | 0.330156 | 19.11 | 13.16 | 0.00711667 | 37254.0 | 40.00 | 21.01 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8226.28 | -4.20 | 0.00269032 | -4.20 | 0.02595455 | 7.8613 | 21.10 | 0.00749433 | 21.10 | 0.00749433 | 47.5054 | 1459.86 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT TS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT TS1 | T S1 APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 6295.201 | 5040.286 | 0.380293 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.0077 | 1004.8586 | 1.1870 | SPLIT TS1 SUPPLY FAN | Fan:OnOff | 0.380293 | 0.45140439 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | Sensible | 6217.12 | 6052.01 | 0.9876 | 0.45140439 | 0.380293 | 25.07 | 16.33 | 0.00815927 | 45973.7 | 12.80 | 11.47 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 425.969 | 5791.15 | 25.34 | 0.00881502 | 16.98 | 0.02595455 | 6.8249 | 24.05 | 0.00811124 | 24.00 | 0.00811124 | 43.0684 | 4417.47 | 0.00 | 6294.13 | 4997.15 | 0.43357733 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 15.41 | 14.58 | 0.01001182 | 40805.6 | |
| SPLIT TS1 HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT TS1 | T S1 APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 9356.716 | 9356.716 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | SPLIT TS1 SUPPLY FAN | Fan:OnOff | 0.380293 | 0.45140439 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | Sensible | 9356.72 | 9356.72 | 1.0000 | 0.45140439 | 0.380293 | 19.37 | 13.19 | 0.00703838 | 37322.0 | 40.00 | 21.01 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9356.72 | -4.20 | 0.00269032 | -4.20 | 0.02595455 | 6.8249 | 21.10 | 0.00735687 | 21.10 | 0.00735687 | 46.6451 | 1603.40 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT TS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT TS2 | T S2 APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 6251.909 | 5005.624 | 0.377678 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.0101 | 1004.8586 | 1.1870 | SPLIT TS2 SUPPLY FAN | Fan:OnOff | 0.377678 | 0.44830010 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | Sensible | 6174.53 | 6009.22 | 0.9876 | 0.44830010 | 0.377678 | 25.07 | 16.33 | 0.00816059 | 45977.4 | 12.80 | 11.47 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 423.040 | 5751.49 | 25.34 | 0.00881502 | 16.98 | 0.02595455 | 6.8721 | 24.05 | 0.00811230 | 24.00 | 0.00811230 | 43.0740 | 4387.72 | 0.00 | 6250.85 | 4962.79 | 0.43059564 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 15.41 | 14.58 | 0.01001182 | 40805.6 | |
| SPLIT TS2 HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT TS2 | T S2 APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 9297.757 | 9297.757 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | SPLIT TS2 SUPPLY FAN | Fan:OnOff | 0.377678 | 0.44830010 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | Sensible | 9297.76 | 9297.76 | 1.0000 | 0.44830010 | 0.377678 | 19.36 | 13.18 | 0.00703623 | 37304.4 | 40.00 | 21.01 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9297.76 | -4.20 | 0.00269032 | -4.20 | 0.02595455 | 6.8721 | 21.10 | 0.00735693 | 21.10 | 0.00735693 | 46.6455 | 1603.57 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 09:15:24
Economizer| High Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
| None |
| Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
| None |
| Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
| G SW APARTMENT | 1702.67 | 4555.00 | 1242.17 |
| G NW APARTMENT | 2917.50 | 7088.83 | 2591.67 |
| OFFICE | 834.50 | 1038.17 | 373.83 |
| G NE APARTMENT | 2889.17 | 7125.17 | 2577.50 |
| G N1 APARTMENT | 1656.50 | 6844.33 | 1494.00 |
| G N2 APARTMENT | 1657.00 | 6851.50 | 1493.17 |
| G S1 APARTMENT | 916.00 | 4243.50 | 494.33 |
| G S2 APARTMENT | 1167.17 | 4157.33 | 661.33 |
| M SW APARTMENT | 972.00 | 3879.17 | 365.83 |
| M NW APARTMENT | 1639.67 | 5944.83 | 1038.17 |
| M SE APARTMENT | 923.17 | 3920.83 | 370.33 |
| M NE APARTMENT | 1587.67 | 5963.17 | 1013.17 |
| M N1 APARTMENT | 637.50 | 5669.17 | 340.17 |
| M N2 APARTMENT | 635.67 | 5668.33 | 340.33 |
| M S1 APARTMENT | 508.83 | 3557.67 | 61.83 |
| M S2 APARTMENT | 506.33 | 3559.33 | 61.67 |
| T SW APARTMENT | 2308.83 | 4886.17 | 1720.00 |
| T NW APARTMENT | 3502.17 | 7120.33 | 2718.00 |
| T SE APARTMENT | 2270.83 | 4902.17 | 1728.33 |
| T NE APARTMENT | 3530.00 | 7030.33 | 2719.33 |
| T N1 APARTMENT | 2776.50 | 7050.17 | 2193.33 |
| T N2 APARTMENT | 2781.33 | 7044.67 | 2194.17 |
| T S1 APARTMENT | 1673.50 | 4730.33 | 1185.33 |
| T S2 APARTMENT | 1674.17 | 4736.00 | 1186.50 |
| T CORRIDOR | 6761.33 | 8722.83 | 6734.17 |
| G CORRIDOR | 4996.17 | 6821.00 | 3619.00 |
| M CORRIDOR | 8506.50 | 8760.00 | 8506.50 |
| Facility | 8760.00 | 8760.00 | 8760.00 |
| During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
| G SW APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| G NW APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| OFFICE | 0.00 | 0.00 | 0.00 | 0.00 |
| G NE APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| G N1 APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| G N2 APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| G S1 APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| G S2 APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| M SW APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| M NW APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| M SE APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| M NE APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| M N1 APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| M N2 APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| M S1 APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| M S2 APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| T SW APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| T NW APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| T SE APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| T NE APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| T N1 APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| T N2 APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| T S1 APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| T S2 APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| T CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
| G CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
| M CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
| Facility | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 09:15:24
Average Outdoor Air During Occupied Hours| Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
| G SW APARTMENT | 2.40 | 2.50 | 268.97 | 0.353 | 0.091 | 0.000 | 0.045 |
| G NW APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.094 | 0.000 | 0.061 |
| OFFICE | 4.75 | 4.75 | 268.97 | 0.519 | 0.099 | 0.000 | 0.000 |
| G NE APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.094 | 0.000 | 0.061 |
| G N1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.057 | 0.000 | 0.061 |
| G N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.057 | 0.000 | 0.061 |
| G S1 APARTMENT | 2.40 | 2.50 | 268.97 | 0.353 | 0.055 | 0.000 | 0.045 |
| G S2 APARTMENT | 2.40 | 2.50 | 268.97 | 0.353 | 0.055 | 0.000 | 0.045 |
| M SW APARTMENT | 2.40 | 2.50 | 268.97 | 0.353 | 0.131 | 0.000 | 0.052 |
| M NW APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.135 | 0.000 | 0.073 |
| M SE APARTMENT | 2.40 | 2.50 | 268.97 | 0.353 | 0.131 | 0.000 | 0.052 |
| M NE APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.135 | 0.000 | 0.073 |
| M N1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.081 | 0.000 | 0.073 |
| M N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.081 | 0.000 | 0.073 |
| M S1 APARTMENT | 2.40 | 2.50 | 268.97 | 0.353 | 0.079 | 0.000 | 0.052 |
| M S2 APARTMENT | 2.40 | 2.50 | 268.97 | 0.353 | 0.079 | 0.000 | 0.052 |
| T SW APARTMENT | 2.40 | 2.50 | 268.97 | 0.353 | 0.173 | 0.000 | 0.058 |
| T NW APARTMENT | 1.71 | 2.50 | 268.97 | 0.352 | 0.178 | 0.000 | 0.082 |
| T SE APARTMENT | 2.40 | 2.50 | 268.97 | 0.353 | 0.173 | 0.000 | 0.058 |
| T NE APARTMENT | 1.71 | 2.50 | 268.97 | 0.352 | 0.178 | 0.000 | 0.082 |
| T N1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.108 | 0.000 | 0.082 |
| T N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.108 | 0.000 | 0.082 |
| T S1 APARTMENT | 2.40 | 2.50 | 268.97 | 0.353 | 0.104 | 0.000 | 0.058 |
| T S2 APARTMENT | 2.40 | 2.50 | 268.97 | 0.353 | 0.104 | 0.000 | 0.058 |
| Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
| G SW APARTMENT | 2.40 | 2.50 | 268.97 | 0.341 | 0.000 | 0.000 | 0.000 |
| G NW APARTMENT | 1.71 | 2.50 | 268.97 | 0.341 | 0.000 | 0.000 | 0.000 |
| OFFICE | 4.75 | 4.75 | 268.97 | 0.499 | 0.000 | 0.000 | 0.000 |
| G NE APARTMENT | 1.71 | 2.50 | 268.97 | 0.341 | 0.000 | 0.000 | 0.000 |
| G N1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.341 | 0.000 | 0.000 | 0.000 |
| G N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.341 | 0.000 | 0.000 | 0.000 |
| G S1 APARTMENT | 2.40 | 2.50 | 268.97 | 0.342 | 0.000 | 0.000 | 0.000 |
| G S2 APARTMENT | 2.40 | 2.50 | 268.97 | 0.341 | 0.000 | 0.000 | 0.000 |
| M SW APARTMENT | 2.40 | 2.50 | 268.97 | 0.342 | 0.000 | 0.000 | 0.000 |
| M NW APARTMENT | 1.71 | 2.50 | 268.97 | 0.341 | 0.000 | 0.000 | 0.000 |
| M SE APARTMENT | 2.40 | 2.50 | 268.97 | 0.342 | 0.000 | 0.000 | 0.000 |
| M NE APARTMENT | 1.71 | 2.50 | 268.97 | 0.341 | 0.000 | 0.000 | 0.000 |
| M N1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.341 | 0.000 | 0.000 | 0.000 |
| M N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.341 | 0.000 | 0.000 | 0.000 |
| M S1 APARTMENT | 2.40 | 2.50 | 268.97 | 0.342 | 0.000 | 0.000 | 0.000 |
| M S2 APARTMENT | 2.40 | 2.50 | 268.97 | 0.342 | 0.000 | 0.000 | 0.000 |
| T SW APARTMENT | 2.40 | 2.50 | 268.97 | 0.342 | 0.000 | 0.000 | 0.000 |
| T NW APARTMENT | 1.71 | 2.50 | 268.97 | 0.341 | 0.000 | 0.000 | 0.000 |
| T SE APARTMENT | 2.40 | 2.50 | 268.97 | 0.342 | 0.000 | 0.000 | 0.000 |
| T NE APARTMENT | 1.71 | 2.50 | 268.97 | 0.341 | 0.000 | 0.000 | 0.000 |
| T N1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.341 | 0.000 | 0.000 | 0.000 |
| T N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.341 | 0.000 | 0.000 | 0.000 |
| T S1 APARTMENT | 2.40 | 2.50 | 268.97 | 0.342 | 0.000 | 0.000 | 0.000 |
| T S2 APARTMENT | 2.40 | 2.50 | 268.97 | 0.342 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 09:15:24
Mechanical Ventilation Parameters by Zone| AirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
| G SW APARTMENT | SPLIT GSW | 2.40 | 2.50 | 268.97 | 88.25 | 0.0260 | 0.026 |
| G NW APARTMENT | SPLIT GNW | 1.71 | 2.50 | 268.97 | 88.25 | 0.0260 | 0.026 |
| OFFICE | SPLIT OFFICE | 4.75 | 4.75 | 268.97 | 88.25 | 0.0381 | 0.038 |
| G NE APARTMENT | SPLIT GNE | 1.71 | 2.50 | 268.97 | 88.25 | 0.0260 | 0.026 |
| G N1 APARTMENT | SPLIT GN1 | 1.71 | 2.50 | 268.97 | 88.25 | 0.0260 | 0.026 |
| G N2 APARTMENT | SPLIT GN2 | 1.71 | 2.50 | 268.97 | 88.25 | 0.0260 | 0.026 |
| G S1 APARTMENT | SPLIT GS1 | 2.40 | 2.50 | 268.97 | 88.25 | 0.0260 | 0.026 |
| G S2 APARTMENT | SPLIT GS2 | 2.40 | 2.50 | 268.97 | 88.25 | 0.0260 | 0.026 |
| M SW APARTMENT | SPLIT MSW | 2.40 | 2.50 | 268.97 | 88.25 | 0.0519 | 0.052 |
| M NW APARTMENT | SPLIT MNW | 1.71 | 2.50 | 268.97 | 88.25 | 0.0519 | 0.052 |
| M SE APARTMENT | SPLIT MSE | 2.40 | 2.50 | 268.97 | 88.25 | 0.0519 | 0.052 |
| M NE APARTMENT | SPLIT MNE | 1.71 | 2.50 | 268.97 | 88.25 | 0.0519 | 0.052 |
| M N1 APARTMENT | SPLIT MN1 | 1.71 | 2.50 | 268.97 | 88.25 | 0.0519 | 0.052 |
| M N2 APARTMENT | SPLIT MN2 | 1.71 | 2.50 | 268.97 | 88.25 | 0.0519 | 0.052 |
| M S1 APARTMENT | SPLIT MS1 | 2.40 | 2.50 | 268.97 | 88.25 | 0.0519 | 0.052 |
| M S2 APARTMENT | SPLIT MS2 | 2.40 | 2.50 | 268.97 | 88.25 | 0.0519 | 0.052 |
| T SW APARTMENT | SPLIT TSW | 2.40 | 2.50 | 268.97 | 88.25 | 0.0260 | 0.026 |
| T NW APARTMENT | SPLIT TNW | 1.71 | 2.50 | 268.97 | 88.25 | 0.0260 | 0.026 |
| T SE APARTMENT | SPLIT TSE | 2.40 | 2.50 | 268.97 | 88.25 | 0.0260 | 0.026 |
| T NE APARTMENT | SPLIT TNE | 1.71 | 2.50 | 268.97 | 88.25 | 0.0260 | 0.026 |
| T N1 APARTMENT | SPLIT TN1 | 1.71 | 2.50 | 268.97 | 88.25 | 0.0260 | 0.026 |
| T N2 APARTMENT | SPLIT TN2 | 1.71 | 2.50 | 268.97 | 88.25 | 0.0260 | 0.026 |
| T S1 APARTMENT | SPLIT TS1 | 2.40 | 2.50 | 268.97 | 88.25 | 0.0260 | 0.026 |
| T S2 APARTMENT | SPLIT TS2 | 2.40 | 2.50 | 268.97 | 88.25 | 0.0260 | 0.026 |
| Total Facility | 68.19 | 82.25 | 8607.06 | 2823.98 | 0.8427 | 1.258 |
| Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
| G SW APARTMENT | 818502.78 | 139903.66 | 958406.44 | 217554.53 | 1175960.97 | 818502.78 | 0.00 | 7297.83 | 1462.17 | 2615.00 |
| G NW APARTMENT | 818502.78 | 140112.75 | 958615.53 | 217554.53 | 1176170.06 | 818502.78 | 0.00 | 7297.83 | 1462.17 | 0.00 |
| OFFICE | 1201711.97 | 0.00 | 1201711.97 | 217554.53 | 1419266.50 | 1201711.97 | 0.00 | 8760.00 | 0.00 | 7010.00 |
| G NE APARTMENT | 818502.78 | 140301.22 | 958804.00 | 217554.53 | 1176358.53 | 818502.78 | 0.00 | 7297.83 | 1462.17 | 0.00 |
| G N1 APARTMENT | 818502.78 | 140417.78 | 958920.55 | 131223.37 | 1090143.93 | 818502.78 | 0.00 | 7297.83 | 1462.17 | 0.00 |
| G N2 APARTMENT | 818502.78 | 140421.66 | 958924.44 | 131223.37 | 1090147.81 | 818502.78 | 0.00 | 7297.83 | 1462.17 | 0.00 |
| G S1 APARTMENT | 818502.78 | 140296.73 | 958799.51 | 131223.37 | 1090022.88 | 818502.78 | 0.00 | 7297.83 | 1462.17 | 2615.00 |
| G S2 APARTMENT | 818502.78 | 140421.19 | 958923.96 | 131223.37 | 1090147.34 | 818502.78 | 0.00 | 7297.83 | 1462.17 | 2615.00 |
| M SW APARTMENT | 1637005.55 | 163659.00 | 1800664.55 | 312642.79 | 2113307.35 | 1637005.55 | 0.00 | 7290.67 | 1469.33 | 2615.00 |
| M NW APARTMENT | 1637005.55 | 167655.20 | 1804660.76 | 312642.79 | 2117303.55 | 1637005.55 | 0.00 | 7290.67 | 1469.33 | 0.00 |
| M SE APARTMENT | 1637005.55 | 163687.38 | 1800692.94 | 312642.79 | 2113335.73 | 1637005.55 | 0.00 | 7290.67 | 1469.33 | 2615.00 |
| M NE APARTMENT | 1637005.55 | 167735.11 | 1804740.67 | 312642.79 | 2117383.46 | 1637005.55 | 0.00 | 7290.67 | 1469.33 | 0.00 |
| M N1 APARTMENT | 1637005.55 | 167769.39 | 1804774.95 | 188578.19 | 1993353.14 | 1637005.55 | 0.00 | 7290.67 | 1469.33 | 0.00 |
| M N2 APARTMENT | 1637005.55 | 167778.04 | 1804783.59 | 188578.19 | 1993361.78 | 1637005.55 | 0.00 | 7290.67 | 1469.33 | 0.00 |
| M S1 APARTMENT | 1637005.55 | 163740.23 | 1800745.78 | 188578.19 | 1989323.98 | 1637005.55 | 0.00 | 7290.67 | 1469.33 | 2615.00 |
| M S2 APARTMENT | 1637005.55 | 163741.69 | 1800747.24 | 188578.19 | 1989325.43 | 1637005.55 | 0.00 | 7290.67 | 1469.33 | 2615.00 |
| T SW APARTMENT | 818502.78 | 183499.08 | 1002001.86 | 413562.63 | 1415564.48 | 818502.78 | 0.00 | 7330.83 | 1429.17 | 2615.00 |
| T NW APARTMENT | 818502.78 | 189149.16 | 1007651.94 | 413562.63 | 1421214.56 | 818502.78 | 0.00 | 7330.83 | 1429.17 | 0.00 |
| T SE APARTMENT | 818502.78 | 183967.32 | 1002470.10 | 413562.63 | 1416032.72 | 818502.78 | 0.00 | 7330.83 | 1429.17 | 2615.00 |
| T NE APARTMENT | 818502.78 | 189909.73 | 1008412.51 | 413562.63 | 1421975.14 | 818502.78 | 0.00 | 7330.83 | 1429.17 | 0.00 |
| T N1 APARTMENT | 818502.78 | 189368.84 | 1007871.62 | 249450.48 | 1257322.09 | 818502.78 | 0.00 | 7330.83 | 1429.17 | 0.00 |
| T N2 APARTMENT | 818502.78 | 189438.39 | 1007941.17 | 249450.48 | 1257391.65 | 818502.78 | 0.00 | 7330.83 | 1429.17 | 0.00 |
| T S1 APARTMENT | 818502.78 | 183883.56 | 1002386.34 | 249450.48 | 1251836.81 | 818502.78 | 0.00 | 7330.83 | 1429.17 | 2615.00 |
| T S2 APARTMENT | 818502.78 | 183909.47 | 1002412.24 | 249450.48 | 1251862.72 | 818502.78 | 0.00 | 7330.83 | 1429.17 | 2615.00 |
| Total Facility | 39671342.50 | 5126532.63 | 44797875.13 | 8056931.90 | 52854807.04 | 39671342.50 | 0.00 | 8760.00 | 1474.83 | 8760.00 |
| Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
| G SW APARTMENT | 0.0260 | 0.0033 | 0.0292 | 0.0067 | 0.0359 | 0.0260 | 0.00 | 5378.17 | 766.83 |
| G NW APARTMENT | 0.0260 | 0.0044 | 0.0304 | 0.0069 | 0.0373 | 0.0260 | 0.00 | 7297.83 | 1462.17 |
| OFFICE | 0.0381 | 0.0000 | 0.0381 | 0.0073 | 0.0454 | 0.0381 | 0.00 | 1750.00 | 0.00 |
| G NE APARTMENT | 0.0260 | 0.0044 | 0.0304 | 0.0069 | 0.0373 | 0.0260 | 0.00 | 7297.83 | 1462.17 |
| G N1 APARTMENT | 0.0260 | 0.0045 | 0.0304 | 0.0042 | 0.0346 | 0.0260 | 0.00 | 7297.83 | 1462.17 |
| G N2 APARTMENT | 0.0260 | 0.0045 | 0.0304 | 0.0042 | 0.0346 | 0.0260 | 0.00 | 7297.83 | 1462.17 |
| G S1 APARTMENT | 0.0260 | 0.0033 | 0.0292 | 0.0040 | 0.0333 | 0.0260 | 0.00 | 5378.17 | 766.83 |
| G S2 APARTMENT | 0.0260 | 0.0033 | 0.0293 | 0.0040 | 0.0333 | 0.0260 | 0.00 | 5378.17 | 766.83 |
| M SW APARTMENT | 0.0519 | 0.0038 | 0.0557 | 0.0096 | 0.0653 | 0.0519 | 0.00 | 5375.67 | 769.33 |
| M NW APARTMENT | 0.0519 | 0.0053 | 0.0572 | 0.0099 | 0.0671 | 0.0519 | 0.00 | 7290.67 | 1469.33 |
| M SE APARTMENT | 0.0519 | 0.0038 | 0.0557 | 0.0096 | 0.0653 | 0.0519 | 0.00 | 5375.67 | 769.33 |
| M NE APARTMENT | 0.0519 | 0.0053 | 0.0572 | 0.0099 | 0.0671 | 0.0519 | 0.00 | 7290.67 | 1469.33 |
| M N1 APARTMENT | 0.0519 | 0.0053 | 0.0572 | 0.0060 | 0.0632 | 0.0519 | 0.00 | 7290.67 | 1469.33 |
| M N2 APARTMENT | 0.0519 | 0.0053 | 0.0572 | 0.0060 | 0.0632 | 0.0519 | 0.00 | 7290.67 | 1469.33 |
| M S1 APARTMENT | 0.0519 | 0.0038 | 0.0557 | 0.0058 | 0.0615 | 0.0519 | 0.00 | 5375.67 | 769.33 |
| M S2 APARTMENT | 0.0519 | 0.0038 | 0.0557 | 0.0058 | 0.0615 | 0.0519 | 0.00 | 5375.67 | 769.33 |
| T SW APARTMENT | 0.0260 | 0.0042 | 0.0302 | 0.0127 | 0.0429 | 0.0260 | 0.00 | 5396.83 | 748.17 |
| T NW APARTMENT | 0.0260 | 0.0060 | 0.0320 | 0.0131 | 0.0451 | 0.0260 | 0.00 | 7330.83 | 1429.17 |
| T SE APARTMENT | 0.0260 | 0.0042 | 0.0302 | 0.0127 | 0.0429 | 0.0260 | 0.00 | 5396.83 | 748.17 |
| T NE APARTMENT | 0.0260 | 0.0060 | 0.0320 | 0.0131 | 0.0451 | 0.0260 | 0.00 | 7330.83 | 1429.17 |
| T N1 APARTMENT | 0.0260 | 0.0060 | 0.0320 | 0.0079 | 0.0399 | 0.0260 | 0.00 | 7330.83 | 1429.17 |
| T N2 APARTMENT | 0.0260 | 0.0060 | 0.0320 | 0.0079 | 0.0399 | 0.0260 | 0.00 | 7330.83 | 1429.17 |
| T S1 APARTMENT | 0.0260 | 0.0042 | 0.0302 | 0.0077 | 0.0378 | 0.0260 | 0.00 | 5396.83 | 748.17 |
| T S2 APARTMENT | 0.0260 | 0.0042 | 0.0302 | 0.0077 | 0.0378 | 0.0260 | 0.00 | 5396.83 | 748.17 |
| Total Facility | 1.2580 | 0.1415 | 1.3994 | 0.2520 | 1.6514 | 1.2580 | 0.00 | 8760.00 | 1474.83 |
| Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
| SPLIT GSW | 0.00 | 139903.66 | 139903.66 | 818502.78 | 7897.67 | 41.52 | 820.82 | 695.33 |
| SPLIT GNW | 0.00 | 140112.75 | 140112.75 | 818502.78 | 7893.25 | 52.44 | 814.31 | 0.00 |
| SPLIT OFFICE | 1693148.62 | 0.00 | 1693148.62 | 1201711.97 | 0.00 | 0.00 | 8760.00 | 7010.00 |
| SPLIT GNE | 0.00 | 140301.22 | 140301.22 | 818502.78 | 7887.51 | 54.64 | 817.85 | 0.00 |
| SPLIT GN1 | 0.00 | 140417.78 | 140417.78 | 818502.78 | 7888.50 | 49.11 | 822.39 | 0.00 |
| SPLIT GN2 | 0.00 | 140421.66 | 140421.66 | 818502.78 | 7887.83 | 49.69 | 822.47 | 0.00 |
| SPLIT GS1 | 0.00 | 140296.73 | 140296.73 | 818502.78 | 7892.00 | 41.83 | 826.17 | 695.33 |
| SPLIT GS2 | 0.00 | 140421.19 | 140421.19 | 818502.78 | 7891.00 | 42.00 | 827.00 | 695.33 |
| SPLIT MSW | 0.00 | 163659.00 | 163659.00 | 1637005.55 | 8724.83 | 7.50 | 27.67 | 700.00 |
| SPLIT MNW | 0.00 | 167655.20 | 167655.20 | 1637005.55 | 8717.33 | 8.83 | 33.83 | 0.00 |
| SPLIT MSE | 0.00 | 163687.38 | 163687.38 | 1637005.55 | 8724.83 | 7.50 | 27.67 | 700.00 |
| SPLIT MNE | 0.00 | 167735.11 | 167735.11 | 1637005.55 | 8717.83 | 8.50 | 33.67 | 0.00 |
| SPLIT MN1 | 0.00 | 167769.39 | 167769.39 | 1637005.55 | 8718.00 | 8.00 | 34.00 | 0.00 |
| SPLIT MN2 | 0.00 | 167778.04 | 167778.04 | 1637005.55 | 8718.00 | 8.00 | 34.00 | 0.00 |
| SPLIT MS1 | 0.00 | 163740.23 | 163740.23 | 1637005.55 | 8724.50 | 7.83 | 27.67 | 700.00 |
| SPLIT MS2 | 0.00 | 163741.69 | 163741.69 | 1637005.55 | 8724.50 | 7.83 | 27.67 | 700.00 |
| SPLIT TSW | 0.00 | 183499.08 | 183499.08 | 818502.78 | 7550.25 | 21.48 | 1188.27 | 681.00 |
| SPLIT TNW | 0.00 | 189149.16 | 189149.16 | 818502.78 | 7527.23 | 17.13 | 1215.63 | 0.00 |
| SPLIT TSE | 0.00 | 183967.32 | 183967.32 | 818502.78 | 7548.43 | 21.65 | 1189.92 | 681.00 |
| SPLIT TNE | 0.00 | 189909.73 | 189909.73 | 818502.78 | 7523.17 | 17.50 | 1219.33 | 0.00 |
| SPLIT TN1 | 0.00 | 189368.84 | 189368.84 | 818502.78 | 7524.60 | 18.94 | 1216.46 | 0.00 |
| SPLIT TN2 | 0.00 | 189438.39 | 189438.39 | 818502.78 | 7524.07 | 19.27 | 1216.67 | 0.00 |
| SPLIT TS1 | 0.00 | 183883.56 | 183883.56 | 818502.78 | 7548.58 | 21.33 | 1190.08 | 681.00 |
| SPLIT TS2 | 0.00 | 183909.47 | 183909.47 | 818502.78 | 7548.58 | 21.33 | 1190.08 | 681.00 |
| Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
| SPLIT GSW | 0.0000 | 0.0033 | 0.0033 | 0.0260 | 5699.50 | 20.75 | 424.75 |
| SPLIT GNW | 0.0000 | 0.0044 | 0.0044 | 0.0260 | 7893.25 | 52.44 | 814.31 |
| SPLIT OFFICE | 0.0537 | 0.0000 | 0.0537 | 0.0381 | 0.00 | 0.00 | 1750.00 |
| SPLIT GNE | 0.0000 | 0.0044 | 0.0044 | 0.0260 | 7887.51 | 54.64 | 817.85 |
| SPLIT GN1 | 0.0000 | 0.0045 | 0.0045 | 0.0260 | 7888.50 | 49.11 | 822.39 |
| SPLIT GN2 | 0.0000 | 0.0045 | 0.0045 | 0.0260 | 7887.83 | 49.69 | 822.47 |
| SPLIT GS1 | 0.0000 | 0.0033 | 0.0033 | 0.0260 | 5697.67 | 20.50 | 426.83 |
| SPLIT GS2 | 0.0000 | 0.0033 | 0.0033 | 0.0260 | 5697.00 | 20.67 | 427.33 |
| SPLIT MSW | 0.0000 | 0.0038 | 0.0038 | 0.0519 | 6134.33 | 3.00 | 7.67 |
| SPLIT MNW | 0.0000 | 0.0053 | 0.0053 | 0.0519 | 8717.33 | 8.83 | 33.83 |
| SPLIT MSE | 0.0000 | 0.0038 | 0.0038 | 0.0519 | 6134.33 | 3.00 | 7.67 |
| SPLIT MNE | 0.0000 | 0.0053 | 0.0053 | 0.0519 | 8717.83 | 8.50 | 33.67 |
| SPLIT MN1 | 0.0000 | 0.0053 | 0.0053 | 0.0519 | 8718.00 | 8.00 | 34.00 |
| SPLIT MN2 | 0.0000 | 0.0053 | 0.0053 | 0.0519 | 8718.00 | 8.00 | 34.00 |
| SPLIT MS1 | 0.0000 | 0.0038 | 0.0038 | 0.0519 | 6134.00 | 3.33 | 7.67 |
| SPLIT MS2 | 0.0000 | 0.0038 | 0.0038 | 0.0519 | 6134.00 | 3.33 | 7.67 |
| SPLIT TSW | 0.0000 | 0.0042 | 0.0042 | 0.0260 | 5516.67 | 10.67 | 617.67 |
| SPLIT TNW | 0.0000 | 0.0060 | 0.0060 | 0.0260 | 7527.23 | 17.13 | 1215.63 |
| SPLIT TSE | 0.0000 | 0.0042 | 0.0042 | 0.0260 | 5515.67 | 11.17 | 618.17 |
| SPLIT TNE | 0.0000 | 0.0060 | 0.0060 | 0.0260 | 7523.17 | 17.50 | 1219.33 |
| SPLIT TN1 | 0.0000 | 0.0060 | 0.0060 | 0.0260 | 7524.60 | 18.94 | 1216.46 |
| SPLIT TN2 | 0.0000 | 0.0060 | 0.0060 | 0.0260 | 7524.07 | 19.27 | 1216.67 |
| SPLIT TS1 | 0.0000 | 0.0042 | 0.0042 | 0.0260 | 5515.92 | 11.00 | 618.08 |
| SPLIT TS2 | 0.0000 | 0.0042 | 0.0042 | 0.0260 | 5515.92 | 11.00 | 618.08 |
| No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
| SPLIT GSW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT GNW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT OFFICE | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT GNE | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT GN1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT GN2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT GS1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT GS2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT MSW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT MNW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT MSE | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT MNE | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT MN1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT MN2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT MS1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT MS2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT TSW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT TNW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT TSE | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT TNE | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT TN1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT TN2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT TS1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT TS2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
| SPLIT GSW | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT GNW | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT OFFICE | 0.0537 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT GNE | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT GN1 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT GN2 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT GS1 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT GS2 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT MSW | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT MNW | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT MSE | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT MNE | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT MN1 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT MN2 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT MS1 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT MS2 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT TSW | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT TNW | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT TSE | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT TNE | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT TN1 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT TN2 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT TS1 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT TS2 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 09:15:24
Surfaces by Class| Total | Outdoors | |
| Wall | 126 | 42 |
| Floor | 27 | 9 |
| Roof | 27 | 9 |
| Internal Mass | 24 | 0 |
| Building Detached Shading | 0 | 0 |
| Fixed Detached Shading | 0 | 0 |
| Window | 39 | 39 |
| Door | 0 | 0 |
| Glass Door | 0 | 0 |
| Shading | 0 | 0 |
| Overhang | 0 | 0 |
| Fin | 0 | 0 |
| Tubular Daylighting Device Dome | 0 | 0 |
| Tubular Daylighting Device Diffuser | 0 | 0 |
| Count | |
| HVAC Air Loops | 24 |
| Conditioned Zones | 24 |
| Unconditioned Zones | 3 |
| Supply Plenums | 0 |
| Return Plenums | 0 |
| Count | |
| IDF Objects | 1536 |
| Defaulted Fields | 1816 |
| Fields with Defaults | 5921 |
| Autosized Fields | 617 |
| Autosizable Fields | 759 |
| Autocalculated Fields | 331 |
| Autocalculatable Fields | 508 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 09:15:24
Annual and Peak Values - Electricity| Electricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
| Electricity:Facility | 1198.67 | 16944.42 | 29-APR-02:10 | 82678.05 | 10-AUG-17:20 |
| Electricity:Building | 557.89 | 10119.94 | 01-JAN-03:10 | 27841.36 | 01-JAN-18:10 |
| Electricity:Zone:G SW APARTMENT | 13.67 | 232.36 | 01-JAN-03:10 | 705.80 | 01-JAN-18:10 |
| Electricity:SpaceType:GENERAL | 557.89 | 10119.94 | 01-JAN-03:10 | 27841.36 | 01-JAN-18:10 |
| InteriorLights:Electricity | 99.23 | 1868.27 | 01-JAN-00:10 | 5904.43 | 01-JAN-19:10 |
| InteriorLights:Electricity:Zone:G SW APARTMENT | 1.45 | 8.68 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 |
| InteriorLights:Electricity:SpaceType:GENERAL | 99.23 | 1868.27 | 01-JAN-00:10 | 5904.43 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity | 94.96 | 1842.77 | 01-JAN-00:10 | 5496.56 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:G SW APARTMENT | 1.32 | 7.86 | 01-JAN-00:10 | 125.72 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 94.96 | 1842.77 | 01-JAN-00:10 | 5496.56 | 01-JAN-19:10 |
| Electricity:Zone:G NW APARTMENT | 13.67 | 232.36 | 01-JAN-03:10 | 705.80 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:G NW APARTMENT | 1.45 | 8.68 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:G NW APARTMENT | 1.32 | 7.86 | 01-JAN-00:10 | 125.72 | 01-JAN-19:10 |
| Electricity:Zone:OFFICE | 16.86 | 310.83 | 01-JAN-00:10 | 1171.54 | 03-JAN-08:10 |
| InteriorLights:Electricity:Zone:OFFICE | 7.40 | 116.58 | 01-JAN-00:10 | 582.92 | 03-JAN-08:10 |
| LightsWired:InteriorLights:Electricity:Zone:OFFICE | 7.40 | 116.58 | 01-JAN-00:10 | 582.92 | 03-JAN-08:10 |
| Electricity:Zone:G NE APARTMENT | 13.67 | 232.36 | 01-JAN-03:10 | 705.80 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:G NE APARTMENT | 1.45 | 8.68 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:G NE APARTMENT | 1.32 | 7.86 | 01-JAN-00:10 | 125.72 | 01-JAN-19:10 |
| Electricity:Zone:G N1 APARTMENT | 13.67 | 232.36 | 01-JAN-03:10 | 705.80 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:G N1 APARTMENT | 1.45 | 8.68 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:G N1 APARTMENT | 1.32 | 7.86 | 01-JAN-00:10 | 125.72 | 01-JAN-19:10 |
| Electricity:Zone:G N2 APARTMENT | 13.67 | 232.36 | 01-JAN-03:10 | 705.80 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:G N2 APARTMENT | 1.45 | 8.68 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:G N2 APARTMENT | 1.32 | 7.86 | 01-JAN-00:10 | 125.72 | 01-JAN-19:10 |
| Electricity:Zone:G S1 APARTMENT | 13.67 | 232.36 | 01-JAN-03:10 | 705.80 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:G S1 APARTMENT | 1.45 | 8.68 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:G S1 APARTMENT | 1.32 | 7.86 | 01-JAN-00:10 | 125.72 | 01-JAN-19:10 |
| Electricity:Zone:G S2 APARTMENT | 13.67 | 232.36 | 01-JAN-03:10 | 705.80 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:G S2 APARTMENT | 1.45 | 8.68 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:G S2 APARTMENT | 1.32 | 7.86 | 01-JAN-00:10 | 125.72 | 01-JAN-19:10 |
| Electricity:Zone:M SW APARTMENT | 27.33 | 464.72 | 01-JAN-03:10 | 1411.61 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:M SW APARTMENT | 2.91 | 17.37 | 01-JAN-00:10 | 277.76 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:M SW APARTMENT | 2.63 | 15.72 | 01-JAN-00:10 | 251.45 | 01-JAN-19:10 |
| Electricity:Zone:M NW APARTMENT | 27.33 | 464.72 | 01-JAN-03:10 | 1411.61 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:M NW APARTMENT | 2.91 | 17.37 | 01-JAN-00:10 | 277.76 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:M NW APARTMENT | 2.63 | 15.72 | 01-JAN-00:10 | 251.45 | 01-JAN-19:10 |
| Electricity:Zone:M SE APARTMENT | 27.33 | 464.72 | 01-JAN-03:10 | 1411.61 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:M SE APARTMENT | 2.91 | 17.37 | 01-JAN-00:10 | 277.76 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:M SE APARTMENT | 2.63 | 15.72 | 01-JAN-00:10 | 251.45 | 01-JAN-19:10 |
| Electricity:Zone:M NE APARTMENT | 27.33 | 464.72 | 01-JAN-03:10 | 1411.61 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:M NE APARTMENT | 2.91 | 17.37 | 01-JAN-00:10 | 277.76 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:M NE APARTMENT | 2.63 | 15.72 | 01-JAN-00:10 | 251.45 | 01-JAN-19:10 |
| Electricity:Zone:M N1 APARTMENT | 27.33 | 464.72 | 01-JAN-03:10 | 1411.61 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:M N1 APARTMENT | 2.91 | 17.37 | 01-JAN-00:10 | 277.76 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:M N1 APARTMENT | 2.63 | 15.72 | 01-JAN-00:10 | 251.45 | 01-JAN-19:10 |
| Electricity:Zone:M N2 APARTMENT | 27.33 | 464.72 | 01-JAN-03:10 | 1411.61 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:M N2 APARTMENT | 2.91 | 17.37 | 01-JAN-00:10 | 277.76 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:M N2 APARTMENT | 2.63 | 15.72 | 01-JAN-00:10 | 251.45 | 01-JAN-19:10 |
| Electricity:Zone:M S1 APARTMENT | 27.33 | 464.72 | 01-JAN-03:10 | 1411.61 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:M S1 APARTMENT | 2.91 | 17.37 | 01-JAN-00:10 | 277.76 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:M S1 APARTMENT | 2.63 | 15.72 | 01-JAN-00:10 | 251.45 | 01-JAN-19:10 |
| Electricity:Zone:M S2 APARTMENT | 27.33 | 464.72 | 01-JAN-03:10 | 1411.61 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:M S2 APARTMENT | 2.91 | 17.37 | 01-JAN-00:10 | 277.76 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:M S2 APARTMENT | 2.63 | 15.72 | 01-JAN-00:10 | 251.45 | 01-JAN-19:10 |
| Electricity:Zone:T SW APARTMENT | 13.67 | 232.36 | 01-JAN-03:10 | 705.80 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:T SW APARTMENT | 1.45 | 8.68 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:T SW APARTMENT | 1.32 | 7.86 | 01-JAN-00:10 | 125.72 | 01-JAN-19:10 |
| Electricity:Zone:T NW APARTMENT | 13.67 | 232.36 | 01-JAN-03:10 | 705.80 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:T NW APARTMENT | 1.45 | 8.68 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:T NW APARTMENT | 1.32 | 7.86 | 01-JAN-00:10 | 125.72 | 01-JAN-19:10 |
| Electricity:Zone:T SE APARTMENT | 13.67 | 232.36 | 01-JAN-03:10 | 705.80 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:T SE APARTMENT | 1.45 | 8.68 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:T SE APARTMENT | 1.32 | 7.86 | 01-JAN-00:10 | 125.72 | 01-JAN-19:10 |
| Electricity:Zone:T NE APARTMENT | 13.67 | 232.36 | 01-JAN-03:10 | 705.80 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:T NE APARTMENT | 1.45 | 8.68 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:T NE APARTMENT | 1.32 | 7.86 | 01-JAN-00:10 | 125.72 | 01-JAN-19:10 |
| Electricity:Zone:T N1 APARTMENT | 13.67 | 232.36 | 01-JAN-03:10 | 705.80 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:T N1 APARTMENT | 1.45 | 8.68 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:T N1 APARTMENT | 1.32 | 7.86 | 01-JAN-00:10 | 125.72 | 01-JAN-19:10 |
| Electricity:Zone:T N2 APARTMENT | 13.67 | 232.36 | 01-JAN-03:10 | 705.80 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:T N2 APARTMENT | 1.45 | 8.68 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:T N2 APARTMENT | 1.32 | 7.86 | 01-JAN-00:10 | 125.72 | 01-JAN-19:10 |
| Electricity:Zone:T S1 APARTMENT | 13.67 | 232.36 | 01-JAN-03:10 | 705.80 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:T S1 APARTMENT | 1.45 | 8.68 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:T S1 APARTMENT | 1.32 | 7.86 | 01-JAN-00:10 | 125.72 | 01-JAN-19:10 |
| Electricity:Zone:T S2 APARTMENT | 13.67 | 232.36 | 01-JAN-03:10 | 705.80 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:T S2 APARTMENT | 1.45 | 8.68 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:T S2 APARTMENT | 1.32 | 7.86 | 01-JAN-00:10 | 125.72 | 01-JAN-19:10 |
| Electricity:Zone:G CORRIDOR | 82.28 | 1494.09 | 01-JAN-00:10 | 4538.70 | 01-JAN-07:10 |
| InteriorLights:Electricity:Zone:G CORRIDOR | 11.69 | 370.63 | 01-JAN-00:10 | 370.63 | 01-JAN-00:10 |
| LightsWired:InteriorLights:Electricity:Zone:G CORRIDOR | 11.69 | 370.63 | 01-JAN-00:10 | 370.63 | 01-JAN-00:10 |
| Electricity:Zone:M CORRIDOR | 23.38 | 741.26 | 01-JAN-00:10 | 741.26 | 01-JAN-00:10 |
| InteriorLights:Electricity:Zone:M CORRIDOR | 23.38 | 741.26 | 01-JAN-00:10 | 741.26 | 01-JAN-00:10 |
| LightsWired:InteriorLights:Electricity:Zone:M CORRIDOR | 23.38 | 741.26 | 01-JAN-00:10 | 741.26 | 01-JAN-00:10 |
| Electricity:Zone:T CORRIDOR | 11.69 | 370.63 | 01-JAN-00:10 | 370.63 | 01-JAN-00:10 |
| InteriorLights:Electricity:Zone:T CORRIDOR | 11.69 | 370.63 | 01-JAN-00:10 | 370.63 | 01-JAN-00:10 |
| LightsWired:InteriorLights:Electricity:Zone:T CORRIDOR | 11.69 | 370.63 | 01-JAN-00:10 | 370.63 | 01-JAN-00:10 |
| LightsPlugIn:InteriorLights:Electricity | 4.27 | 25.50 | 01-JAN-00:10 | 407.87 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:G SW APARTMENT | 0.14 | 0.82 | 01-JAN-00:10 | 13.16 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:SpaceType:GENERAL | 4.27 | 25.50 | 01-JAN-00:10 | 407.87 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:G NW APARTMENT | 0.14 | 0.82 | 01-JAN-00:10 | 13.16 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:G NE APARTMENT | 0.14 | 0.82 | 01-JAN-00:10 | 13.16 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:G N1 APARTMENT | 0.14 | 0.82 | 01-JAN-00:10 | 13.16 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:G N2 APARTMENT | 0.14 | 0.82 | 01-JAN-00:10 | 13.16 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:G S1 APARTMENT | 0.14 | 0.82 | 01-JAN-00:10 | 13.16 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:G S2 APARTMENT | 0.14 | 0.82 | 01-JAN-00:10 | 13.16 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:M SW APARTMENT | 0.28 | 1.65 | 01-JAN-00:10 | 26.31 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:M NW APARTMENT | 0.28 | 1.65 | 01-JAN-00:10 | 26.31 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:M SE APARTMENT | 0.28 | 1.65 | 01-JAN-00:10 | 26.31 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:M NE APARTMENT | 0.28 | 1.65 | 01-JAN-00:10 | 26.31 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:M N1 APARTMENT | 0.28 | 1.65 | 01-JAN-00:10 | 26.31 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:M N2 APARTMENT | 0.28 | 1.65 | 01-JAN-00:10 | 26.31 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:M S1 APARTMENT | 0.28 | 1.65 | 01-JAN-00:10 | 26.31 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:M S2 APARTMENT | 0.28 | 1.65 | 01-JAN-00:10 | 26.31 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:T SW APARTMENT | 0.14 | 0.82 | 01-JAN-00:10 | 13.16 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:T NW APARTMENT | 0.14 | 0.82 | 01-JAN-00:10 | 13.16 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:T SE APARTMENT | 0.14 | 0.82 | 01-JAN-00:10 | 13.16 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:T NE APARTMENT | 0.14 | 0.82 | 01-JAN-00:10 | 13.16 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:T N1 APARTMENT | 0.14 | 0.82 | 01-JAN-00:10 | 13.16 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:T N2 APARTMENT | 0.14 | 0.82 | 01-JAN-00:10 | 13.16 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:T S1 APARTMENT | 0.14 | 0.82 | 01-JAN-00:10 | 13.16 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:T S2 APARTMENT | 0.14 | 0.82 | 01-JAN-00:10 | 13.16 | 01-JAN-19:10 |
| InteriorEquipment:Electricity | 458.66 | 8251.68 | 01-JAN-03:10 | 22709.69 | 03-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:G SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:SpaceType:GENERAL | 458.66 | 8251.68 | 01-JAN-03:10 | 22709.69 | 03-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity | 388.06 | 7128.22 | 01-JAN-03:10 | 18541.61 | 03-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:G SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 388.06 | 7128.22 | 01-JAN-03:10 | 18541.61 | 03-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:G NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:G NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:OFFICE | 9.47 | 194.25 | 01-JAN-00:10 | 588.62 | 03-JAN-08:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:OFFICE | 9.47 | 194.25 | 01-JAN-00:10 | 588.62 | 03-JAN-08:10 |
| InteriorEquipment:Electricity:Zone:G NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:G NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:G N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:G N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:G N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:G N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:G S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:G S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:G S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:G S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:M SW APARTMENT | 24.43 | 447.35 | 01-JAN-03:10 | 1177.25 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:M SW APARTMENT | 24.43 | 447.35 | 01-JAN-03:10 | 1177.25 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:M NW APARTMENT | 24.43 | 447.35 | 01-JAN-03:10 | 1177.25 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:M NW APARTMENT | 24.43 | 447.35 | 01-JAN-03:10 | 1177.25 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:M SE APARTMENT | 24.43 | 447.35 | 01-JAN-03:10 | 1177.25 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:M SE APARTMENT | 24.43 | 447.35 | 01-JAN-03:10 | 1177.25 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:M NE APARTMENT | 24.43 | 447.35 | 01-JAN-03:10 | 1177.25 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:M NE APARTMENT | 24.43 | 447.35 | 01-JAN-03:10 | 1177.25 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:M N1 APARTMENT | 24.43 | 447.35 | 01-JAN-03:10 | 1177.25 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:M N1 APARTMENT | 24.43 | 447.35 | 01-JAN-03:10 | 1177.25 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:M N2 APARTMENT | 24.43 | 447.35 | 01-JAN-03:10 | 1177.25 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:M N2 APARTMENT | 24.43 | 447.35 | 01-JAN-03:10 | 1177.25 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:M S1 APARTMENT | 24.43 | 447.35 | 01-JAN-03:10 | 1177.25 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:M S1 APARTMENT | 24.43 | 447.35 | 01-JAN-03:10 | 1177.25 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:M S2 APARTMENT | 24.43 | 447.35 | 01-JAN-03:10 | 1177.25 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:M S2 APARTMENT | 24.43 | 447.35 | 01-JAN-03:10 | 1177.25 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:T SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:T SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:T NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:T NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:T SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:T SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:T NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:T NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:T N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:T N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:T N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:T N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:T S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:T S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:T S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:T S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:G CORRIDOR | 70.59 | 1123.46 | 01-JAN-00:10 | 4168.07 | 01-JAN-07:10 |
| ElevatorLift:InteriorEquipment:Electricity | 65.48 | 961.46 | 01-JAN-00:10 | 4006.07 | 01-JAN-07:10 |
| ElevatorLift:InteriorEquipment:Electricity:Zone:G CORRIDOR | 65.48 | 961.46 | 01-JAN-00:10 | 4006.07 | 01-JAN-07:10 |
| ElevatorLift:InteriorEquipment:Electricity:SpaceType:GENERAL | 65.48 | 961.46 | 01-JAN-00:10 | 4006.07 | 01-JAN-07:10 |
| ElevatorLightsFan:InteriorEquipment:Electricity | 5.11 | 162.00 | 01-JAN-00:10 | 162.00 | 01-JAN-00:10 |
| ElevatorLightsFan:InteriorEquipment:Electricity:Zone:G CORRIDOR | 5.11 | 162.00 | 01-JAN-00:10 | 162.00 | 01-JAN-00:10 |
| ElevatorLightsFan:InteriorEquipment:Electricity:SpaceType:GENERAL | 5.11 | 162.00 | 01-JAN-00:10 | 162.00 | 01-JAN-00:10 |
| Fans:Electricity | 77.17 | 1691.15 | 24-FEB-18:00 | 7599.85 | 10-AUG-16:20 |
| Fans:Electricity:Zone:G SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:G SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:G NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:G NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:G NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:G NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:G N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:G N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:G N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:G N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:G S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:G S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:G S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:G S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:M SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:M SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:M NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:M NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:M SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:M SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:M NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:M NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:M N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:M N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:M N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:M N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:M S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:M S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:M S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:M S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:T SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:T SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:T NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:T NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:T SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:T SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:T NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:T NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:T N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:T N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:T N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:T N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:T S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:T S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:T S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:T S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| ElectricityPurchased:Facility | 1198.67 | 16944.42 | 29-APR-02:10 | 82678.05 | 10-AUG-17:20 |
| ElectricityPurchased:Plant | 1198.67 | 16944.42 | 29-APR-02:10 | 82678.05 | 10-AUG-17:20 |
| Cogeneration:ElectricityPurchased | 1198.67 | 16944.42 | 29-APR-02:10 | 82678.05 | 10-AUG-17:20 |
| General:Cogeneration:ElectricityPurchased | 1198.67 | 16944.42 | 29-APR-02:10 | 82678.05 | 10-AUG-17:20 |
| ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| ElectricityNet:Facility | 1198.67 | 16944.42 | 29-APR-02:10 | 82678.05 | 10-AUG-17:20 |
| ElectricityNet:Plant | 1198.67 | 16944.42 | 29-APR-02:10 | 82678.05 | 10-AUG-17:20 |
| Cogeneration:ElectricityNet | 1198.67 | 16944.42 | 29-APR-02:10 | 82678.05 | 10-AUG-17:20 |
| General:Cogeneration:ElectricityNet | 1198.67 | 16944.42 | 29-APR-02:10 | 82678.05 | 10-AUG-17:20 |
| Electricity:HVAC | 128.24 | 1691.15 | 24-FEB-18:00 | 28886.84 | 10-AUG-15:30 |
| HeatRecovery:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:HeatRecovery:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:Fans:Electricity | 77.17 | 1691.15 | 24-FEB-18:00 | 7599.85 | 10-AUG-16:20 |
| Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Cooling:Electricity | 51.06 | 0.00 | 01-JAN-00:10 | 21407.18 | 10-AUG-15:30 |
| General:Cooling:Electricity | 51.06 | 0.00 | 01-JAN-00:10 | 21407.18 | 10-AUG-15:30 |
| ExteriorLights:Electricity | 49.92 | 0.00 | 01-JAN-08:10 | 3183.33 | 01-JAN-00:10 |
| General:ExteriorLights:Electricity | 49.92 | 0.00 | 01-JAN-08:10 | 3183.33 | 01-JAN-00:10 |
| Electricity:Plant | 462.63 | 1950.00 | 01-JAN-00:10 | 37762.84 | 01-FEB-08:00 |
| WaterSystems:Electricity | 462.63 | 1950.00 | 01-JAN-00:10 | 37762.84 | 01-FEB-08:00 |
| Water Heater:WaterSystems:Electricity | 462.63 | 1950.00 | 01-JAN-00:10 | 37762.84 | 01-FEB-08:00 |
| Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
| NaturalGas:Facility | 245.36 | 0.00 | 24-FEB-18:00 | 63056.36 | 19-FEB-06:00 |
| NaturalGas:HVAC | 245.36 | 0.00 | 24-FEB-18:00 | 63056.36 | 19-FEB-06:00 |
| Heating:NaturalGas | 245.36 | 0.00 | 24-FEB-18:00 | 63056.36 | 19-FEB-06:00 |
| General:Heating:NaturalGas | 245.36 | 0.00 | 24-FEB-18:00 | 63056.36 | 19-FEB-06:00 |
| Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
| None |
| Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
| Water:Facility | 1875.32 | 0.00 | 01-JAN-02:10 | 0.00 | 01-JAN-07:10 |
| Water:Plant | 1875.32 | 0.00 | 01-JAN-02:10 | 0.00 | 01-JAN-07:10 |
| WaterSystems:Water | 1875.32 | 0.00 | 01-JAN-02:10 | 0.00 | 01-JAN-07:10 |
| Water Heater:WaterSystems:Water | 1875.32 | 0.00 | 01-JAN-02:10 | 0.00 | 01-JAN-07:10 |
| MainsWater:Facility | 1875.32 | 0.00 | 01-JAN-02:10 | 0.00 | 01-JAN-07:10 |
| MainsWater:Plant | 1875.32 | 0.00 | 01-JAN-02:10 | 0.00 | 01-JAN-07:10 |
| WaterSystems:MainsWater | 1875.32 | 0.00 | 01-JAN-02:10 | 0.00 | 01-JAN-07:10 |
| Water Heater:WaterSystems:MainsWater | 1875.32 | 0.00 | 01-JAN-02:10 | 0.00 | 01-JAN-07:10 |
| Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
| Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
| CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
| Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
| None |
| Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
| None |
| Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
| EnergyTransfer:Facility | 830.49 | 3932.28 | 09-MAR-12:00 | 142556.36 | 10-AUG-15:10 |
| EnergyTransfer:Building | 433.07 | 3929.66 | 01-APR-11:10 | 62455.94 | 10-AUG-15:10 |
| EnergyTransfer:Zone:G SW APARTMENT | 12.07 | 0.02 | 21-NOV-13:20 | 2213.44 | 10-AUG-17:20 |
| Heating:EnergyTransfer | 68.48 | 0.00 | 03-FEB-16:50 | 27643.41 | 19-FEB-07:00 |
| Heating:EnergyTransfer:Zone:G SW APARTMENT | 2.35 | 0.00 | 05-JAN-13:30 | 1014.80 | 19-FEB-07:00 |
| General:Heating:EnergyTransfer | 68.48 | 0.00 | 03-FEB-16:50 | 27643.41 | 19-FEB-07:00 |
| General:Heating:EnergyTransfer:Zone:G SW APARTMENT | 2.35 | 0.00 | 05-JAN-13:30 | 1014.80 | 19-FEB-07:00 |
| Cooling:EnergyTransfer | 364.60 | 0.00 | 16-FEB-08:30 | 62455.94 | 10-AUG-15:10 |
| Cooling:EnergyTransfer:Zone:G SW APARTMENT | 9.72 | 0.00 | 01-JAN-00:10 | 2213.44 | 10-AUG-17:20 |
| General:Cooling:EnergyTransfer | 364.60 | 0.00 | 16-FEB-08:30 | 62455.94 | 10-AUG-15:10 |
| General:Cooling:EnergyTransfer:Zone:G SW APARTMENT | 9.72 | 0.00 | 01-JAN-00:10 | 2213.44 | 10-AUG-17:20 |
| EnergyTransfer:Zone:G NW APARTMENT | 10.36 | 0.00 | 14-APR-23:30 | 1723.41 | 10-AUG-18:00 |
| Heating:EnergyTransfer:Zone:G NW APARTMENT | 4.09 | 0.00 | 11-JAN-17:10 | 1192.55 | 19-FEB-08:20 |
| General:Heating:EnergyTransfer:Zone:G NW APARTMENT | 4.09 | 0.00 | 11-JAN-17:10 | 1192.55 | 19-FEB-08:20 |
| Cooling:EnergyTransfer:Zone:G NW APARTMENT | 6.27 | 0.00 | 01-JAN-00:10 | 1723.41 | 10-AUG-18:00 |
| General:Cooling:EnergyTransfer:Zone:G NW APARTMENT | 6.27 | 0.00 | 01-JAN-00:10 | 1723.41 | 10-AUG-18:00 |
| EnergyTransfer:Zone:OFFICE | 9.36 | 0.00 | 17-MAR-17:00 | 3566.40 | 14-AUG-08:10 |
| Heating:EnergyTransfer:Zone:OFFICE | 1.52 | 0.00 | 01-JAN-00:10 | 2887.09 | 17-JAN-09:10 |
| General:Heating:EnergyTransfer:Zone:OFFICE | 1.52 | 0.00 | 01-JAN-00:10 | 2887.09 | 17-JAN-09:10 |
| Cooling:EnergyTransfer:Zone:OFFICE | 7.84 | 0.00 | 01-JAN-05:40 | 3566.40 | 14-AUG-08:10 |
| General:Cooling:EnergyTransfer:Zone:OFFICE | 7.84 | 0.00 | 01-JAN-05:40 | 3566.40 | 14-AUG-08:10 |
| EnergyTransfer:Zone:G NE APARTMENT | 10.20 | 0.01 | 15-APR-06:50 | 1353.37 | 24-JUL-18:00 |
| Heating:EnergyTransfer:Zone:G NE APARTMENT | 4.06 | 0.00 | 11-JAN-18:50 | 1123.24 | 19-FEB-07:00 |
| General:Heating:EnergyTransfer:Zone:G NE APARTMENT | 4.06 | 0.00 | 11-JAN-18:50 | 1123.24 | 19-FEB-07:00 |
| Cooling:EnergyTransfer:Zone:G NE APARTMENT | 6.14 | 0.00 | 01-JAN-00:10 | 1353.37 | 24-JUL-18:00 |
| General:Cooling:EnergyTransfer:Zone:G NE APARTMENT | 6.14 | 0.00 | 01-JAN-00:10 | 1353.37 | 24-JUL-18:00 |
| EnergyTransfer:Zone:G N1 APARTMENT | 7.78 | 0.01 | 31-DEC-23:30 | 1066.92 | 24-JUL-18:00 |
| Heating:EnergyTransfer:Zone:G N1 APARTMENT | 1.03 | 0.00 | 01-JAN-17:20 | 621.23 | 19-FEB-08:20 |
| General:Heating:EnergyTransfer:Zone:G N1 APARTMENT | 1.03 | 0.00 | 01-JAN-17:20 | 621.23 | 19-FEB-08:20 |
| Cooling:EnergyTransfer:Zone:G N1 APARTMENT | 6.75 | 0.00 | 01-JAN-00:10 | 1066.92 | 24-JUL-18:00 |
| General:Cooling:EnergyTransfer:Zone:G N1 APARTMENT | 6.75 | 0.00 | 01-JAN-00:10 | 1066.92 | 24-JUL-18:00 |
| EnergyTransfer:Zone:G N2 APARTMENT | 7.78 | 0.01 | 31-DEC-23:40 | 1063.37 | 24-JUL-18:00 |
| Heating:EnergyTransfer:Zone:G N2 APARTMENT | 1.03 | 0.00 | 01-JAN-17:20 | 618.75 | 19-FEB-08:20 |
| General:Heating:EnergyTransfer:Zone:G N2 APARTMENT | 1.03 | 0.00 | 01-JAN-17:20 | 618.75 | 19-FEB-08:20 |
| Cooling:EnergyTransfer:Zone:G N2 APARTMENT | 6.75 | 0.00 | 01-JAN-00:10 | 1063.37 | 24-JUL-18:00 |
| General:Cooling:EnergyTransfer:Zone:G N2 APARTMENT | 6.75 | 0.00 | 01-JAN-00:10 | 1063.37 | 24-JUL-18:00 |
| EnergyTransfer:Zone:G S1 APARTMENT | 11.47 | 0.03 | 31-DEC-02:00 | 1616.35 | 10-AUG-15:10 |
| Heating:EnergyTransfer:Zone:G S1 APARTMENT | 0.34 | 0.00 | 01-JAN-10:30 | 439.90 | 19-FEB-07:00 |
| General:Heating:EnergyTransfer:Zone:G S1 APARTMENT | 0.34 | 0.00 | 01-JAN-10:30 | 439.90 | 19-FEB-07:00 |
| Cooling:EnergyTransfer:Zone:G S1 APARTMENT | 11.13 | 0.00 | 01-JAN-00:10 | 1616.35 | 10-AUG-15:10 |
| General:Cooling:EnergyTransfer:Zone:G S1 APARTMENT | 11.13 | 0.00 | 01-JAN-00:10 | 1616.35 | 10-AUG-15:10 |
| EnergyTransfer:Zone:G S2 APARTMENT | 12.04 | 0.03 | 09-DEC-07:50 | 1692.06 | 13-AUG-15:10 |
| Heating:EnergyTransfer:Zone:G S2 APARTMENT | 0.58 | 0.00 | 03-JAN-10:30 | 560.67 | 19-FEB-07:00 |
| General:Heating:EnergyTransfer:Zone:G S2 APARTMENT | 0.58 | 0.00 | 03-JAN-10:30 | 560.67 | 19-FEB-07:00 |
| Cooling:EnergyTransfer:Zone:G S2 APARTMENT | 11.46 | 0.00 | 01-JAN-00:10 | 1692.06 | 13-AUG-15:10 |
| General:Cooling:EnergyTransfer:Zone:G S2 APARTMENT | 11.46 | 0.00 | 01-JAN-00:10 | 1692.06 | 13-AUG-15:10 |
| EnergyTransfer:Zone:M SW APARTMENT | 33.12 | 0.10 | 19-JAN-11:20 | 5670.54 | 10-AUG-16:20 |
| Heating:EnergyTransfer:Zone:M SW APARTMENT | 1.87 | 0.00 | 01-JAN-10:40 | 1613.31 | 19-FEB-07:00 |
| General:Heating:EnergyTransfer:Zone:M SW APARTMENT | 1.87 | 0.00 | 01-JAN-10:40 | 1613.31 | 19-FEB-07:00 |
| Cooling:EnergyTransfer:Zone:M SW APARTMENT | 31.26 | 0.00 | 01-JAN-00:10 | 5670.54 | 10-AUG-16:20 |
| General:Cooling:EnergyTransfer:Zone:M SW APARTMENT | 31.26 | 0.00 | 01-JAN-00:10 | 5670.54 | 10-AUG-16:20 |
| EnergyTransfer:Zone:M NW APARTMENT | 24.88 | 0.02 | 31-DEC-16:50 | 4554.58 | 10-AUG-17:30 |
| Heating:EnergyTransfer:Zone:M NW APARTMENT | 3.43 | 0.00 | 03-JAN-15:00 | 1848.58 | 19-FEB-07:00 |
| General:Heating:EnergyTransfer:Zone:M NW APARTMENT | 3.43 | 0.00 | 03-JAN-15:00 | 1848.58 | 19-FEB-07:00 |
| Cooling:EnergyTransfer:Zone:M NW APARTMENT | 21.45 | 0.00 | 01-JAN-00:10 | 4554.58 | 10-AUG-17:30 |
| General:Cooling:EnergyTransfer:Zone:M NW APARTMENT | 21.45 | 0.00 | 01-JAN-00:10 | 4554.58 | 10-AUG-17:30 |
| EnergyTransfer:Zone:M SE APARTMENT | 32.82 | 0.05 | 15-FEB-19:50 | 4927.45 | 10-AUG-13:30 |
| Heating:EnergyTransfer:Zone:M SE APARTMENT | 1.87 | 0.00 | 01-JAN-10:30 | 1604.46 | 19-FEB-07:00 |
| General:Heating:EnergyTransfer:Zone:M SE APARTMENT | 1.87 | 0.00 | 01-JAN-10:30 | 1604.46 | 19-FEB-07:00 |
| Cooling:EnergyTransfer:Zone:M SE APARTMENT | 30.95 | 0.00 | 01-JAN-00:10 | 4927.45 | 10-AUG-13:30 |
| General:Cooling:EnergyTransfer:Zone:M SE APARTMENT | 30.95 | 0.00 | 01-JAN-00:10 | 4927.45 | 10-AUG-13:30 |
| EnergyTransfer:Zone:M NE APARTMENT | 24.54 | 0.04 | 27-JAN-10:20 | 3471.35 | 24-JUL-18:00 |
| Heating:EnergyTransfer:Zone:M NE APARTMENT | 3.40 | 0.00 | 01-JAN-18:00 | 1838.48 | 19-FEB-07:00 |
| General:Heating:EnergyTransfer:Zone:M NE APARTMENT | 3.40 | 0.00 | 01-JAN-18:00 | 1838.48 | 19-FEB-07:00 |
| Cooling:EnergyTransfer:Zone:M NE APARTMENT | 21.14 | 0.00 | 01-JAN-00:10 | 3471.35 | 24-JUL-18:00 |
| General:Cooling:EnergyTransfer:Zone:M NE APARTMENT | 21.14 | 0.00 | 01-JAN-00:10 | 3471.35 | 24-JUL-18:00 |
| EnergyTransfer:Zone:M N1 APARTMENT | 23.04 | 0.02 | 05-JAN-02:40 | 2680.07 | 24-JUL-18:00 |
| Heating:EnergyTransfer:Zone:M N1 APARTMENT | 0.21 | 0.00 | 01-JAN-04:50 | 657.90 | 19-FEB-06:00 |
| General:Heating:EnergyTransfer:Zone:M N1 APARTMENT | 0.21 | 0.00 | 01-JAN-04:50 | 657.90 | 19-FEB-06:00 |
| Cooling:EnergyTransfer:Zone:M N1 APARTMENT | 22.83 | 0.00 | 01-JAN-00:10 | 2680.07 | 24-JUL-18:00 |
| General:Cooling:EnergyTransfer:Zone:M N1 APARTMENT | 22.83 | 0.00 | 01-JAN-00:10 | 2680.07 | 24-JUL-18:00 |
| EnergyTransfer:Zone:M N2 APARTMENT | 23.04 | 0.01 | 15-NOV-04:40 | 2671.64 | 24-JUL-18:00 |
| Heating:EnergyTransfer:Zone:M N2 APARTMENT | 0.21 | 0.00 | 01-JAN-04:50 | 656.87 | 19-FEB-06:00 |
| General:Heating:EnergyTransfer:Zone:M N2 APARTMENT | 0.21 | 0.00 | 01-JAN-04:50 | 656.87 | 19-FEB-06:00 |
| Cooling:EnergyTransfer:Zone:M N2 APARTMENT | 22.82 | 0.00 | 01-JAN-00:10 | 2671.64 | 24-JUL-18:00 |
| General:Cooling:EnergyTransfer:Zone:M N2 APARTMENT | 22.82 | 0.00 | 01-JAN-00:10 | 2671.64 | 24-JUL-18:00 |
| EnergyTransfer:Zone:M S1 APARTMENT | 33.71 | 0.09 | 21-DEC-02:10 | 4165.87 | 23-SEP-13:30 |
| Heating:EnergyTransfer:Zone:M S1 APARTMENT | 0.05 | 0.00 | 01-JAN-01:00 | 500.75 | 19-FEB-06:00 |
| General:Heating:EnergyTransfer:Zone:M S1 APARTMENT | 0.05 | 0.00 | 01-JAN-01:00 | 500.75 | 19-FEB-06:00 |
| Cooling:EnergyTransfer:Zone:M S1 APARTMENT | 33.66 | 0.00 | 01-JAN-00:10 | 4165.87 | 23-SEP-13:30 |
| General:Cooling:EnergyTransfer:Zone:M S1 APARTMENT | 33.66 | 0.00 | 01-JAN-00:10 | 4165.87 | 23-SEP-13:30 |
| EnergyTransfer:Zone:M S2 APARTMENT | 33.71 | 0.08 | 19-JAN-03:40 | 4173.86 | 23-SEP-13:30 |
| Heating:EnergyTransfer:Zone:M S2 APARTMENT | 0.05 | 0.00 | 01-JAN-01:00 | 499.91 | 19-FEB-06:00 |
| General:Heating:EnergyTransfer:Zone:M S2 APARTMENT | 0.05 | 0.00 | 01-JAN-01:00 | 499.91 | 19-FEB-06:00 |
| Cooling:EnergyTransfer:Zone:M S2 APARTMENT | 33.66 | 0.00 | 01-JAN-00:10 | 4173.86 | 23-SEP-13:30 |
| General:Cooling:EnergyTransfer:Zone:M S2 APARTMENT | 33.66 | 0.00 | 01-JAN-00:10 | 4173.86 | 23-SEP-13:30 |
| EnergyTransfer:Zone:T SW APARTMENT | 19.10 | 0.04 | 22-JAN-14:00 | 3870.78 | 10-AUG-16:10 |
| Heating:EnergyTransfer:Zone:T SW APARTMENT | 6.49 | 0.00 | 05-JAN-13:20 | 1995.26 | 19-FEB-07:00 |
| General:Heating:EnergyTransfer:Zone:T SW APARTMENT | 6.49 | 0.00 | 05-JAN-13:20 | 1995.26 | 19-FEB-07:00 |
| Cooling:EnergyTransfer:Zone:T SW APARTMENT | 12.62 | 0.00 | 01-JAN-00:10 | 3870.78 | 10-AUG-16:10 |
| General:Cooling:EnergyTransfer:Zone:T SW APARTMENT | 12.62 | 0.00 | 01-JAN-00:10 | 3870.78 | 10-AUG-16:10 |
| EnergyTransfer:Zone:T NW APARTMENT | 16.64 | 0.03 | 19-NOV-14:10 | 3118.97 | 10-AUG-17:20 |
| Heating:EnergyTransfer:Zone:T NW APARTMENT | 8.30 | 0.00 | 11-JAN-16:10 | 2057.19 | 19-FEB-07:00 |
| General:Heating:EnergyTransfer:Zone:T NW APARTMENT | 8.30 | 0.00 | 11-JAN-16:10 | 2057.19 | 19-FEB-07:00 |
| Cooling:EnergyTransfer:Zone:T NW APARTMENT | 8.34 | 0.00 | 01-JAN-00:10 | 3118.97 | 10-AUG-17:20 |
| General:Cooling:EnergyTransfer:Zone:T NW APARTMENT | 8.34 | 0.00 | 01-JAN-00:10 | 3118.97 | 10-AUG-17:20 |
| EnergyTransfer:Zone:T SE APARTMENT | 18.83 | 0.05 | 11-MAR-07:40 | 3388.44 | 10-AUG-13:30 |
| Heating:EnergyTransfer:Zone:T SE APARTMENT | 6.45 | 0.00 | 05-JAN-13:20 | 1996.58 | 19-FEB-07:00 |
| General:Heating:EnergyTransfer:Zone:T SE APARTMENT | 6.45 | 0.00 | 05-JAN-13:20 | 1996.58 | 19-FEB-07:00 |
| Cooling:EnergyTransfer:Zone:T SE APARTMENT | 12.38 | 0.00 | 01-JAN-00:10 | 3388.44 | 10-AUG-13:30 |
| General:Cooling:EnergyTransfer:Zone:T SE APARTMENT | 12.38 | 0.00 | 01-JAN-00:10 | 3388.44 | 10-AUG-13:30 |
| EnergyTransfer:Zone:T NE APARTMENT | 16.33 | 0.05 | 02-MAR-21:50 | 2294.91 | 24-JUL-16:10 |
| Heating:EnergyTransfer:Zone:T NE APARTMENT | 8.25 | 0.00 | 11-JAN-16:10 | 2059.77 | 19-FEB-07:00 |
| General:Heating:EnergyTransfer:Zone:T NE APARTMENT | 8.25 | 0.00 | 11-JAN-16:10 | 2059.77 | 19-FEB-07:00 |
| Cooling:EnergyTransfer:Zone:T NE APARTMENT | 8.08 | 0.00 | 01-JAN-00:10 | 2294.91 | 24-JUL-16:10 |
| General:Cooling:EnergyTransfer:Zone:T NE APARTMENT | 8.08 | 0.00 | 01-JAN-00:10 | 2294.91 | 24-JUL-16:10 |
| EnergyTransfer:Zone:T N1 APARTMENT | 11.34 | 0.04 | 29-MAR-10:40 | 1843.07 | 24-JUL-18:00 |
| Heating:EnergyTransfer:Zone:T N1 APARTMENT | 3.85 | 0.00 | 10-JAN-17:10 | 1290.95 | 19-FEB-06:00 |
| General:Heating:EnergyTransfer:Zone:T N1 APARTMENT | 3.85 | 0.00 | 10-JAN-17:10 | 1290.95 | 19-FEB-06:00 |
| Cooling:EnergyTransfer:Zone:T N1 APARTMENT | 7.50 | 0.00 | 01-JAN-00:10 | 1843.07 | 24-JUL-18:00 |
| General:Cooling:EnergyTransfer:Zone:T N1 APARTMENT | 7.50 | 0.00 | 01-JAN-00:10 | 1843.07 | 24-JUL-18:00 |
| EnergyTransfer:Zone:T N2 APARTMENT | 11.36 | 0.03 | 12-OCT-08:50 | 1830.18 | 24-JUL-18:00 |
| Heating:EnergyTransfer:Zone:T N2 APARTMENT | 3.85 | 0.00 | 10-JAN-17:10 | 1290.60 | 19-FEB-06:00 |
| General:Heating:EnergyTransfer:Zone:T N2 APARTMENT | 3.85 | 0.00 | 10-JAN-17:10 | 1290.60 | 19-FEB-06:00 |
| Cooling:EnergyTransfer:Zone:T N2 APARTMENT | 7.51 | 0.00 | 01-JAN-00:10 | 1830.18 | 24-JUL-18:00 |
| General:Cooling:EnergyTransfer:Zone:T N2 APARTMENT | 7.51 | 0.00 | 01-JAN-00:10 | 1830.18 | 24-JUL-18:00 |
| EnergyTransfer:Zone:T S1 APARTMENT | 14.75 | 0.01 | 23-FEB-12:50 | 2886.61 | 10-AUG-14:20 |
| Heating:EnergyTransfer:Zone:T S1 APARTMENT | 2.59 | 0.00 | 03-JAN-10:30 | 1216.15 | 19-FEB-07:00 |
| General:Heating:EnergyTransfer:Zone:T S1 APARTMENT | 2.59 | 0.00 | 03-JAN-10:30 | 1216.15 | 19-FEB-07:00 |
| Cooling:EnergyTransfer:Zone:T S1 APARTMENT | 12.16 | 0.00 | 01-JAN-00:10 | 2886.61 | 10-AUG-14:20 |
| General:Cooling:EnergyTransfer:Zone:T S1 APARTMENT | 12.16 | 0.00 | 01-JAN-00:10 | 2886.61 | 10-AUG-14:20 |
| EnergyTransfer:Zone:T S2 APARTMENT | 14.78 | 0.01 | 08-NOV-09:00 | 2894.23 | 10-AUG-14:20 |
| Heating:EnergyTransfer:Zone:T S2 APARTMENT | 2.60 | 0.00 | 03-JAN-10:30 | 1215.72 | 19-FEB-07:00 |
| General:Heating:EnergyTransfer:Zone:T S2 APARTMENT | 2.60 | 0.00 | 03-JAN-10:30 | 1215.72 | 19-FEB-07:00 |
| Cooling:EnergyTransfer:Zone:T S2 APARTMENT | 12.18 | 0.00 | 01-JAN-00:10 | 2894.23 | 10-AUG-14:20 |
| General:Cooling:EnergyTransfer:Zone:T S2 APARTMENT | 12.18 | 0.00 | 01-JAN-00:10 | 2894.23 | 10-AUG-14:20 |
| EnergyTransfer:Zone:T CORRIDOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Heating:EnergyTransfer:Zone:T CORRIDOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:Heating:EnergyTransfer:Zone:T CORRIDOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Cooling:EnergyTransfer:Zone:T CORRIDOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:Cooling:EnergyTransfer:Zone:T CORRIDOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| EnergyTransfer:Zone:G CORRIDOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Heating:EnergyTransfer:Zone:G CORRIDOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:Heating:EnergyTransfer:Zone:G CORRIDOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Cooling:EnergyTransfer:Zone:G CORRIDOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:Cooling:EnergyTransfer:Zone:G CORRIDOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| EnergyTransfer:Zone:M CORRIDOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Heating:EnergyTransfer:Zone:M CORRIDOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:Heating:EnergyTransfer:Zone:M CORRIDOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Cooling:EnergyTransfer:Zone:M CORRIDOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:Cooling:EnergyTransfer:Zone:M CORRIDOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| EnergyTransfer:HVAC | 397.41 | 0.00 | 24-FEB-18:00 | 80100.42 | 10-AUG-15:10 |
| HeatRecoveryForHeating:EnergyTransfer | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 30-AUG-05:30 |
| HeatRecoveryForCooling:EnergyTransfer | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 28-JUL-13:20 |
| HeatingCoils:EnergyTransfer | 196.29 | 0.00 | 24-FEB-18:00 | 50445.08 | 19-FEB-06:00 |
| CoolingCoils:EnergyTransfer | 201.13 | 0.00 | 01-JAN-00:10 | 80100.42 | 10-AUG-15:10 |
| PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 09:15:24
Annual Building Sensible Heat Gain Components| HVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
| G SW APARTMENT | 0.076 | -10.425 | 7.522 | -4.540 | 0.000 | 0.000 | 3.906 | 1.454 | 12.213 | 10.510 | 0.000 | 0.016 | 0.000 | 0.000 | -5.484 | 0.000 | -3.791 | -11.457 |
| G NW APARTMENT | 0.077 | -10.198 | 10.387 | -2.439 | 0.000 | 0.000 | 4.000 | 1.454 | 12.213 | 5.331 | 0.000 | 0.017 | 0.000 | 0.000 | -5.438 | 0.000 | -3.681 | -11.722 |
| OFFICE | 0.000 | 0.000 | 1.522 | -7.840 | 0.000 | 0.000 | 2.132 | 7.396 | 9.469 | 10.156 | 0.000 | 0.009 | 0.000 | 0.000 | -5.409 | 0.000 | -2.909 | -14.526 |
| G NE APARTMENT | 0.077 | -10.194 | 10.340 | -2.301 | 0.000 | 0.000 | 4.004 | 1.454 | 12.213 | 5.035 | 0.000 | 0.017 | 0.000 | 0.000 | -5.338 | 0.000 | -3.683 | -11.623 |
| G N1 APARTMENT | 0.078 | -10.294 | 6.446 | -1.952 | 0.000 | 0.000 | 3.979 | 1.454 | 12.213 | 1.821 | 0.000 | 0.010 | 0.000 | 0.000 | -3.411 | 0.000 | -2.580 | -7.764 |
| G N2 APARTMENT | 0.078 | -10.293 | 6.445 | -1.948 | 0.000 | 0.000 | 3.980 | 1.454 | 12.213 | 1.821 | 0.000 | 0.010 | 0.000 | 0.000 | -3.411 | 0.000 | -2.580 | -7.768 |
| G S1 APARTMENT | 0.076 | -10.591 | 4.008 | -4.292 | 0.000 | 0.000 | 3.873 | 1.454 | 12.213 | 7.049 | 0.000 | 0.010 | 0.000 | 0.000 | -3.414 | 0.000 | -2.683 | -7.703 |
| G S2 APARTMENT | 0.076 | -10.613 | 4.427 | -4.775 | 0.000 | 0.000 | 3.869 | 1.454 | 12.213 | 7.043 | 0.000 | 0.010 | 0.000 | 0.000 | -3.417 | 0.000 | -2.690 | -7.595 |
| M SW APARTMENT | 0.151 | -21.572 | 8.852 | -16.822 | 0.000 | 0.000 | 7.669 | 2.908 | 24.426 | 20.537 | 0.000 | 0.047 | 0.000 | 0.000 | -11.658 | 0.000 | -10.734 | -3.804 |
| M NW APARTMENT | 0.152 | -21.076 | 13.204 | -10.305 | 0.000 | 0.000 | 7.856 | 2.908 | 24.426 | 10.223 | 0.000 | 0.047 | 0.000 | 0.000 | -11.595 | 0.000 | -10.533 | -5.306 |
| M SE APARTMENT | 0.151 | -21.587 | 8.832 | -16.481 | 0.000 | 0.000 | 7.671 | 2.908 | 24.426 | 19.972 | 0.000 | 0.047 | 0.000 | 0.000 | -11.495 | 0.000 | -10.742 | -3.701 |
| M NE APARTMENT | 0.152 | -21.088 | 13.161 | -9.958 | 0.000 | 0.000 | 7.860 | 2.908 | 24.426 | 9.620 | 0.000 | 0.047 | 0.000 | 0.000 | -11.392 | 0.000 | -10.541 | -5.193 |
| M N1 APARTMENT | 0.152 | -21.350 | 6.815 | -8.232 | 0.000 | 0.000 | 7.798 | 2.908 | 24.426 | 3.422 | 0.000 | 0.028 | 0.000 | 0.000 | -7.273 | 0.000 | -7.270 | -1.425 |
| M N2 APARTMENT | 0.152 | -21.352 | 6.817 | -8.225 | 0.000 | 0.000 | 7.798 | 2.908 | 24.426 | 3.421 | 0.000 | 0.028 | 0.000 | 0.000 | -7.273 | 0.000 | -7.271 | -1.430 |
| M S1 APARTMENT | 0.151 | -22.011 | 3.541 | -15.286 | 0.000 | 0.000 | 7.578 | 2.908 | 24.426 | 13.831 | 0.000 | 0.028 | 0.000 | 0.000 | -7.254 | 0.000 | -7.435 | -0.477 |
| M S2 APARTMENT | 0.151 | -22.012 | 3.543 | -15.287 | 0.000 | 0.000 | 7.578 | 2.908 | 24.426 | 13.830 | 0.000 | 0.028 | 0.000 | 0.000 | -7.254 | 0.000 | -7.435 | -0.475 |
| T SW APARTMENT | 0.076 | -10.330 | 12.302 | -8.179 | 0.000 | 0.000 | 3.938 | 1.454 | 12.213 | 10.303 | 0.000 | 0.030 | 0.000 | 0.000 | -5.407 | 0.000 | -6.630 | -9.770 |
| T NW APARTMENT | 0.076 | -10.142 | 14.919 | -4.896 | 0.000 | 0.000 | 4.016 | 1.454 | 12.213 | 5.178 | 0.000 | 0.030 | 0.000 | 0.000 | -5.419 | 0.000 | -6.519 | -10.910 |
| T SE APARTMENT | 0.076 | -10.348 | 12.228 | -7.877 | 0.000 | 0.000 | 3.941 | 1.454 | 12.213 | 10.028 | 0.000 | 0.030 | 0.000 | 0.000 | -5.338 | 0.000 | -6.653 | -9.754 |
| T NE APARTMENT | 0.076 | -10.158 | 14.821 | -4.574 | 0.000 | 0.000 | 4.019 | 1.454 | 12.213 | 4.880 | 0.000 | 0.030 | 0.000 | 0.000 | -5.326 | 0.000 | -6.550 | -10.886 |
| T N1 APARTMENT | 0.076 | -10.233 | 9.925 | -3.418 | 0.000 | 0.000 | 3.995 | 1.454 | 12.213 | 1.762 | 0.000 | 0.018 | 0.000 | 0.000 | -3.400 | 0.000 | -4.405 | -7.988 |
| T N2 APARTMENT | 0.076 | -10.233 | 9.928 | -3.429 | 0.000 | 0.000 | 3.996 | 1.454 | 12.213 | 1.760 | 0.000 | 0.018 | 0.000 | 0.000 | -3.399 | 0.000 | -4.408 | -7.976 |
| T S1 APARTMENT | 0.076 | -10.479 | 7.542 | -6.702 | 0.000 | 0.000 | 3.906 | 1.454 | 12.213 | 6.950 | 0.000 | 0.018 | 0.000 | 0.000 | -3.366 | 0.000 | -4.506 | -7.106 |
| T S2 APARTMENT | 0.076 | -10.479 | 7.546 | -6.724 | 0.000 | 0.000 | 3.907 | 1.454 | 12.213 | 6.948 | 0.000 | 0.018 | 0.000 | 0.000 | -3.364 | 0.000 | -4.507 | -7.088 |
| T CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 6.437 | 11.688 | 0.000 | 0.754 | 0.000 | 0.001 | 0.000 | 0.000 | -0.564 | 0.000 | -0.997 | -17.320 |
| G CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 6.749 | 11.688 | 3.530 | 2.311 | 0.000 | 0.082 | 4.321 | 0.000 | -1.557 | 0.000 | -27.125 | -0.000 |
| M CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 11.998 | 23.376 | 0.000 | 1.464 | 0.000 | 0.003 | 0.000 | 0.000 | -1.237 | 0.000 | -1.664 | -33.940 |
| Total Facility | 2.352 | -327.058 | 205.071 | -176.484 | 0.000 | 0.000 | 148.452 | 99.229 | 391.594 | 195.960 | 0.000 | 0.681 | 4.322 | 0.000 | -148.893 | 0.000 | -170.520 | -224.706 |
| Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
| G SW APARTMENT | 10-AUG-17:20 | 0.00 | 253.56 | 0.00 | -2467.51 | 0.00 | 0.00 | 167.23 | 117.18 | 588.62 | 1693.38 | 0.00 | 39.78 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -392.25 |
| G NW APARTMENT | 10-AUG-18:00 | 0.00 | 230.60 | 0.00 | -1954.14 | 0.00 | 0.00 | 145.49 | 117.18 | 588.62 | 1504.50 | 0.00 | 35.95 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -668.20 |
| OFFICE | 15-AUG-07:01 | 0.00 | 0.00 | 0.00 | -6380.41 | 0.00 | 0.00 | 261.53 | 582.92 | 588.62 | 44.17 | 0.00 | 0.00 | 4956.10 | 0.00 | -0.00 | 0.00 | -52.92 | 0.00 |
| G NE APARTMENT | 24-JUL-18:00 | 0.00 | 174.02 | 0.00 | -1527.37 | 0.00 | 0.00 | 145.49 | 117.18 | 588.62 | 521.49 | 0.00 | 47.02 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -66.45 |
| G N1 APARTMENT | 24-JUL-18:00 | 0.00 | 174.05 | 0.00 | -1240.95 | 0.00 | 0.00 | 145.49 | 117.18 | 588.62 | 373.89 | 0.00 | 28.36 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -186.64 |
| G N2 APARTMENT | 24-JUL-18:00 | 0.00 | 174.05 | 0.00 | -1237.40 | 0.00 | 0.00 | 145.49 | 117.18 | 588.62 | 373.92 | 0.00 | 28.36 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -190.22 |
| G S1 APARTMENT | 10-AUG-15:10 | 0.00 | 220.13 | 0.00 | -1836.40 | 0.00 | 0.00 | 0.00 | 60.76 | 470.90 | 1025.26 | 0.00 | 22.50 | 36.86 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| G S2 APARTMENT | 13-AUG-15:10 | 0.00 | 149.41 | 0.00 | -1841.53 | 0.00 | 0.00 | 167.23 | 60.76 | 470.90 | 853.10 | 0.00 | 23.51 | 116.63 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| M SW APARTMENT | 10-AUG-16:17 | 0.00 | 504.99 | 0.00 | -6176.06 | 0.00 | 0.00 | 0.00 | 173.60 | 1177.25 | 4083.07 | 0.00 | 81.56 | 155.59 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| M NW APARTMENT | 10-AUG-17:30 | 0.00 | 495.66 | 0.00 | -5050.35 | 0.00 | 0.00 | 290.97 | 234.36 | 1177.25 | 3329.76 | 0.00 | 111.29 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -588.96 |
| M SE APARTMENT | 10-AUG-13:30 | 0.00 | 310.24 | 0.00 | -5237.64 | 0.00 | 0.00 | 0.00 | 34.72 | 765.21 | 3657.95 | 0.00 | 65.40 | 404.12 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| M NE APARTMENT | 24-JUL-18:00 | 0.00 | 347.99 | 0.00 | -3819.30 | 0.00 | 0.00 | 290.97 | 234.36 | 1177.25 | 1033.96 | 0.00 | 134.59 | 600.17 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| M N1 APARTMENT | 24-JUL-18:00 | 0.00 | 348.05 | 0.00 | -3028.08 | 0.00 | 0.00 | 290.97 | 234.36 | 1177.25 | 742.42 | 0.00 | 81.18 | 153.84 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| M N2 APARTMENT | 24-JUL-18:00 | 0.00 | 348.05 | 0.00 | -3019.64 | 0.00 | 0.00 | 290.97 | 234.36 | 1177.25 | 742.48 | 0.00 | 81.18 | 145.35 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| M S1 APARTMENT | 23-SEP-13:30 | 0.00 | -38.78 | 0.00 | -4127.01 | 0.00 | 0.00 | 167.23 | 34.72 | 765.21 | 3880.98 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -51.90 | -630.44 |
| M S2 APARTMENT | 23-SEP-13:30 | 0.00 | -38.78 | 0.00 | -4135.01 | 0.00 | 0.00 | 167.23 | 34.72 | 765.21 | 3880.91 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -51.90 | -622.38 |
| T SW APARTMENT | 10-AUG-16:03 | 0.00 | 249.32 | 0.00 | -4120.29 | 0.00 | 0.00 | 0.00 | 86.80 | 588.62 | 2070.05 | 0.00 | 47.75 | 1077.75 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| T NW APARTMENT | 10-AUG-17:17 | 0.00 | 253.55 | 0.00 | -3372.61 | 0.00 | 0.00 | 145.49 | 117.18 | 588.62 | 1676.18 | 0.00 | 75.02 | 516.56 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| T SE APARTMENT | 10-AUG-13:30 | 0.00 | 155.09 | 0.00 | -3543.49 | 0.00 | 0.00 | 0.00 | 17.36 | 382.60 | 1804.42 | 0.00 | 42.85 | 1141.17 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| T NE APARTMENT | 24-JUL-16:03 | 0.00 | 170.82 | 0.00 | -2465.97 | 0.00 | 0.00 | 86.96 | 86.80 | 588.62 | 577.21 | 0.00 | 84.95 | 870.61 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| T N1 APARTMENT | 24-JUL-18:00 | 0.00 | 173.99 | 0.00 | -2017.04 | 0.00 | 0.00 | 145.49 | 117.18 | 588.62 | 363.31 | 0.00 | 53.26 | 575.19 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| T N2 APARTMENT | 24-JUL-18:00 | 0.00 | 173.99 | 0.00 | -2004.14 | 0.00 | 0.00 | 145.49 | 117.18 | 588.62 | 363.44 | 0.00 | 53.26 | 562.16 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| T S1 APARTMENT | 10-AUG-14:20 | 0.00 | 198.05 | 0.00 | -3084.58 | 0.00 | 0.00 | 0.00 | 30.38 | 400.26 | 1368.38 | 0.00 | 27.12 | 1060.38 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| T S2 APARTMENT | 10-AUG-14:20 | 0.00 | 198.05 | 0.00 | -3092.19 | 0.00 | 0.00 | 0.00 | 30.38 | 400.26 | 1368.30 | 0.00 | 27.12 | 1068.08 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| T CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| G CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Total Facility | 10-AUG-15:10 | 0.00 | 6824.55 | 0.00 | -69277.72 | 0.00 | 0.00 | 1393.44 | 3948.92 | 15334.78 | 33662.08 | 0.00 | 1667.23 | 6446.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
| G SW APARTMENT | 19-FEB-07:00 | -791.90 | 0.00 | 1806.68 | 0.00 | 0.00 | 0.00 | 194.99 | 60.76 | 317.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -576.18 | 0.00 | -316.84 | -695.37 |
| G NW APARTMENT | 19-FEB-08:13 | -774.15 | 0.00 | 1967.87 | 0.00 | 0.00 | 0.00 | 76.05 | 26.04 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -435.58 | 0.00 | -309.62 | -939.11 |
| OFFICE | 18-JAN-07:01 | 0.00 | 0.00 | 9581.96 | 0.00 | 0.00 | 0.00 | 0.00 | 116.58 | 294.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -322.48 | 0.00 | -92.04 | -9578.33 |
| G NE APARTMENT | 19-FEB-07:00 | -791.90 | 0.00 | 1915.12 | 0.00 | 0.00 | 0.00 | 194.99 | 60.76 | 317.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -588.39 | 0.00 | -316.84 | -791.60 |
| G N1 APARTMENT | 19-FEB-08:13 | -774.23 | 0.00 | 1396.62 | 0.00 | 0.00 | 0.00 | 76.05 | 26.04 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -271.85 | 0.00 | -186.75 | -654.38 |
| G N2 APARTMENT | 19-FEB-08:13 | -774.23 | 0.00 | 1394.15 | 0.00 | 0.00 | 0.00 | 76.05 | 26.04 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -271.87 | 0.00 | -186.75 | -651.87 |
| G S1 APARTMENT | 19-FEB-07:00 | -791.97 | 0.00 | 1231.87 | 0.00 | 0.00 | 0.00 | 194.99 | 60.76 | 317.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -353.25 | 0.00 | -191.11 | -469.14 |
| G S2 APARTMENT | 19-FEB-07:00 | -791.98 | 0.00 | 1352.64 | 0.00 | 0.00 | 0.00 | 194.99 | 60.76 | 317.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -351.60 | 0.00 | -191.11 | -591.56 |
| M SW APARTMENT | 19-FEB-07:00 | -1583.62 | 0.00 | 3196.91 | 0.00 | 0.00 | 0.00 | 389.98 | 121.52 | 635.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1183.69 | 0.00 | -911.35 | -665.46 |
| M NW APARTMENT | 19-FEB-07:00 | -1583.62 | 0.00 | 3432.18 | 0.00 | 0.00 | 0.00 | 389.98 | 121.52 | 635.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1198.27 | 0.00 | -911.35 | -886.15 |
| M SE APARTMENT | 19-FEB-07:00 | -1583.62 | 0.00 | 3188.06 | 0.00 | 0.00 | 0.00 | 389.98 | 121.52 | 635.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1197.60 | 0.00 | -911.35 | -642.70 |
| M NE APARTMENT | 19-FEB-07:00 | -1583.62 | 0.00 | 3422.08 | 0.00 | 0.00 | 0.00 | 389.98 | 121.52 | 635.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1212.10 | 0.00 | -911.35 | -862.22 |
| M N1 APARTMENT | 19-FEB-06:00 | -1621.29 | 0.00 | 2279.17 | 0.00 | 0.00 | 0.00 | 389.98 | 112.83 | 506.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -765.14 | 0.00 | -498.55 | -403.22 |
| M N2 APARTMENT | 19-FEB-06:00 | -1621.29 | 0.00 | 2278.15 | 0.00 | 0.00 | 0.00 | 389.98 | 112.83 | 506.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -765.16 | 0.00 | -498.55 | -402.17 |
| M S1 APARTMENT | 19-FEB-06:00 | -1621.30 | 0.00 | 2122.03 | 0.00 | 0.00 | 0.00 | 389.98 | 112.83 | 506.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -749.99 | 0.00 | -498.55 | -261.23 |
| M S2 APARTMENT | 19-FEB-06:00 | -1621.30 | 0.00 | 2121.19 | 0.00 | 0.00 | 0.00 | 389.98 | 112.83 | 506.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -750.01 | 0.00 | -498.55 | -260.37 |
| T SW APARTMENT | 19-FEB-07:00 | -791.76 | 0.00 | 2786.98 | 0.00 | 0.00 | 0.00 | 194.99 | 60.76 | 317.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -571.37 | 0.00 | -603.68 | -1393.78 |
| T NW APARTMENT | 19-FEB-07:00 | -791.76 | 0.00 | 2848.91 | 0.00 | 0.00 | 0.00 | 194.99 | 60.76 | 317.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -580.60 | 0.00 | -603.68 | -1446.47 |
| T SE APARTMENT | 19-FEB-07:00 | -791.76 | 0.00 | 2788.30 | 0.00 | 0.00 | 0.00 | 194.99 | 60.76 | 317.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -578.45 | 0.00 | -603.68 | -1388.02 |
| T NE APARTMENT | 19-FEB-07:00 | -791.76 | 0.00 | 2851.50 | 0.00 | 0.00 | 0.00 | 194.99 | 60.76 | 317.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -587.64 | 0.00 | -603.68 | -1442.03 |
| T N1 APARTMENT | 19-FEB-06:00 | -810.61 | 0.00 | 2101.52 | 0.00 | 0.00 | 0.00 | 194.99 | 56.42 | 253.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -371.87 | 0.00 | -330.23 | -1093.32 |
| T N2 APARTMENT | 19-FEB-06:00 | -810.61 | 0.00 | 2101.17 | 0.00 | 0.00 | 0.00 | 194.99 | 56.42 | 253.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -371.88 | 0.00 | -330.23 | -1092.97 |
| T S1 APARTMENT | 19-FEB-07:00 | -791.87 | 0.00 | 2008.00 | 0.00 | 0.00 | 0.00 | 194.99 | 60.76 | 317.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -350.24 | 0.00 | -364.13 | -1075.37 |
| T S2 APARTMENT | 19-FEB-07:00 | -791.87 | 0.00 | 2007.57 | 0.00 | 0.00 | 0.00 | 194.99 | 60.76 | 317.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -350.25 | 0.00 | -364.13 | -1074.93 |
| T CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| G CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Total Facility | 19-FEB-07:00 | -24850.74 | 302.87 | 52190.83 | -302.87 | 0.00 | 0.00 | 7423.11 | 3482.59 | 10216.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -15467.35 | 0.00 | -14074.12 | -18920.45 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 09:15:24
System Ventilation Requirements for Cooling| Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
| SPLIT GSW | 0.3648 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.3648 | 0.0711 | 1.0000 | Not calculated | 0.0260 | 0.0711 | ||
| SPLIT GNW | 0.3061 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.3061 | 0.0848 | 1.0000 | Not calculated | 0.0260 | 0.0848 | ||
| SPLIT OFFICE | 0.4024 | 0.0000 | 4.7495 | 1.0000 | Calculated from schedules | 0.0381 | 0.4024 | 0.0947 | 1.0000 | Not calculated | 0.0381 | 0.0947 | ||
| SPLIT GNE | 0.2688 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.2688 | 0.0966 | 1.0000 | Not calculated | 0.0260 | 0.0966 | ||
| SPLIT GN1 | 0.2452 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.2452 | 0.1059 | 1.0000 | Not calculated | 0.0260 | 0.1059 | ||
| SPLIT GN2 | 0.2445 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.2445 | 0.1062 | 1.0000 | Not calculated | 0.0260 | 0.1062 | ||
| SPLIT GS1 | 0.3085 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.3085 | 0.0841 | 1.0000 | Not calculated | 0.0260 | 0.0841 | ||
| SPLIT GS2 | 0.3101 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.3101 | 0.0837 | 1.0000 | Not calculated | 0.0260 | 0.0837 | ||
| SPLIT MSW | 0.8855 | 0.0000 | 5.0000 | 1.0000 | Calculated from schedules | 0.0519 | 0.8855 | 0.0586 | 1.0000 | Not calculated | 0.0519 | 0.0586 | ||
| SPLIT MNW | 0.7755 | 0.0000 | 5.0000 | 1.0000 | Calculated from schedules | 0.0519 | 0.7755 | 0.0669 | 1.0000 | Not calculated | 0.0519 | 0.0669 | ||
| SPLIT MSE | 0.7737 | 0.0000 | 5.0000 | 1.0000 | Calculated from schedules | 0.0519 | 0.7737 | 0.0671 | 1.0000 | Not calculated | 0.0519 | 0.0671 | ||
| SPLIT MNE | 0.6664 | 0.0000 | 5.0000 | 1.0000 | Calculated from schedules | 0.0519 | 0.6664 | 0.0779 | 1.0000 | Not calculated | 0.0519 | 0.0779 | ||
| SPLIT MN1 | 0.6030 | 0.0000 | 5.0000 | 1.0000 | Calculated from schedules | 0.0519 | 0.6030 | 0.0861 | 1.0000 | Not calculated | 0.0519 | 0.0861 | ||
| SPLIT MN2 | 0.6011 | 0.0000 | 5.0000 | 1.0000 | Calculated from schedules | 0.0519 | 0.6011 | 0.0864 | 1.0000 | Not calculated | 0.0519 | 0.0864 | ||
| SPLIT MS1 | 0.7232 | 0.0000 | 5.0000 | 1.0000 | Calculated from schedules | 0.0519 | 0.7232 | 0.0718 | 1.0000 | Not calculated | 0.0519 | 0.0718 | ||
| SPLIT MS2 | 0.7210 | 0.0000 | 5.0000 | 1.0000 | Calculated from schedules | 0.0519 | 0.7210 | 0.0720 | 1.0000 | Not calculated | 0.0519 | 0.0720 | ||
| SPLIT TSW | 0.4745 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.4745 | 0.0547 | 1.0000 | Not calculated | 0.0260 | 0.0547 | ||
| SPLIT TNW | 0.4297 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.4297 | 0.0604 | 1.0000 | Not calculated | 0.0260 | 0.0604 | ||
| SPLIT TSE | 0.3935 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.3935 | 0.0660 | 1.0000 | Not calculated | 0.0260 | 0.0660 | ||
| SPLIT TNE | 0.3494 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.3494 | 0.0743 | 1.0000 | Not calculated | 0.0260 | 0.0743 | ||
| SPLIT TN1 | 0.3328 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.3328 | 0.0780 | 1.0000 | Not calculated | 0.0260 | 0.0780 | ||
| SPLIT TN2 | 0.3302 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.3302 | 0.0786 | 1.0000 | Not calculated | 0.0260 | 0.0786 | ||
| SPLIT TS1 | 0.3803 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.3803 | 0.0682 | 1.0000 | Not calculated | 0.0260 | 0.0682 | ||
| SPLIT TS2 | 0.3777 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.3777 | 0.0687 | 1.0000 | Not calculated | 0.0260 | 0.0687 |
| Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
| SPLIT GSW | 0.3648 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.3648 | 1.0000 | 1.0000 | Not calculated | 0.0260 | 0.0711 | ||
| SPLIT GNW | 0.3061 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.3061 | 1.0000 | 1.0000 | Not calculated | 0.0260 | 0.0848 | ||
| SPLIT OFFICE | 0.4024 | 0.0000 | 4.7495 | 1.0000 | Calculated from schedules | 0.0381 | 0.4024 | 1.0000 | 1.0000 | Not calculated | 0.0381 | 0.0947 | ||
| SPLIT GNE | 0.2688 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.2688 | 1.0000 | 1.0000 | Not calculated | 0.0260 | 0.0966 | ||
| SPLIT GN1 | 0.2452 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.2452 | 1.0000 | 1.0000 | Not calculated | 0.0260 | 0.1059 | ||
| SPLIT GN2 | 0.2445 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.2445 | 1.0000 | 1.0000 | Not calculated | 0.0260 | 0.1062 | ||
| SPLIT GS1 | 0.3085 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.3085 | 1.0000 | 1.0000 | Not calculated | 0.0260 | 0.0841 | ||
| SPLIT GS2 | 0.3101 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.3101 | 1.0000 | 1.0000 | Not calculated | 0.0260 | 0.0837 | ||
| SPLIT MSW | 0.8855 | 0.0000 | 5.0000 | 1.0000 | Calculated from schedules | 0.0519 | 0.8855 | 1.0000 | 1.0000 | Not calculated | 0.0519 | 0.0586 | ||
| SPLIT MNW | 0.7755 | 0.0000 | 5.0000 | 1.0000 | Calculated from schedules | 0.0519 | 0.7755 | 1.0000 | 1.0000 | Not calculated | 0.0519 | 0.0669 | ||
| SPLIT MSE | 0.7737 | 0.0000 | 5.0000 | 1.0000 | Calculated from schedules | 0.0519 | 0.7737 | 1.0000 | 1.0000 | Not calculated | 0.0519 | 0.0671 | ||
| SPLIT MNE | 0.6664 | 0.0000 | 5.0000 | 1.0000 | Calculated from schedules | 0.0519 | 0.6664 | 1.0000 | 1.0000 | Not calculated | 0.0519 | 0.0779 | ||
| SPLIT MN1 | 0.6030 | 0.0000 | 5.0000 | 1.0000 | Calculated from schedules | 0.0519 | 0.6030 | 1.0000 | 1.0000 | Not calculated | 0.0519 | 0.0861 | ||
| SPLIT MN2 | 0.6011 | 0.0000 | 5.0000 | 1.0000 | Calculated from schedules | 0.0519 | 0.6011 | 1.0000 | 1.0000 | Not calculated | 0.0519 | 0.0864 | ||
| SPLIT MS1 | 0.7232 | 0.0000 | 5.0000 | 1.0000 | Calculated from schedules | 0.0519 | 0.7232 | 1.0000 | 1.0000 | Not calculated | 0.0519 | 0.0718 | ||
| SPLIT MS2 | 0.7210 | 0.0000 | 5.0000 | 1.0000 | Calculated from schedules | 0.0519 | 0.7210 | 1.0000 | 1.0000 | Not calculated | 0.0519 | 0.0720 | ||
| SPLIT TSW | 0.4745 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.4745 | 1.0000 | 1.0000 | Not calculated | 0.0260 | 0.0547 | ||
| SPLIT TNW | 0.4297 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.4297 | 1.0000 | 1.0000 | Not calculated | 0.0260 | 0.0604 | ||
| SPLIT TSE | 0.3935 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.3935 | 1.0000 | 1.0000 | Not calculated | 0.0260 | 0.0660 | ||
| SPLIT TNE | 0.3494 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.3494 | 1.0000 | 1.0000 | Not calculated | 0.0260 | 0.0743 | ||
| SPLIT TN1 | 0.3328 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.3328 | 1.0000 | 1.0000 | Not calculated | 0.0260 | 0.0780 | ||
| SPLIT TN2 | 0.3302 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.3302 | 1.0000 | 1.0000 | Not calculated | 0.0260 | 0.0786 | ||
| SPLIT TS1 | 0.3803 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.3803 | 1.0000 | 1.0000 | Not calculated | 0.0260 | 0.0682 | ||
| SPLIT TS2 | 0.3777 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.3777 | 1.0000 | 1.0000 | Not calculated | 0.0260 | 0.0687 |
| AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
| G SW APARTMENT | SPLIT GSW | 0.000000 | 2.5000 | 0.000294 | 88.25 | 0.0260 | 1.0000 | 0.0260 | 1.000 | 0.0260 |
| G NW APARTMENT | SPLIT GNW | 0.000000 | 2.5000 | 0.000294 | 88.25 | 0.0260 | 1.0000 | 0.0260 | 1.000 | 0.0260 |
| OFFICE | SPLIT OFFICE | 0.000000 | 4.7495 | 0.000432 | 88.25 | 0.0381 | 1.0000 | 0.0381 | 1.000 | 0.0381 |
| G NE APARTMENT | SPLIT GNE | 0.000000 | 2.5000 | 0.000294 | 88.25 | 0.0260 | 1.0000 | 0.0260 | 1.000 | 0.0260 |
| G N1 APARTMENT | SPLIT GN1 | 0.000000 | 2.5000 | 0.000294 | 88.25 | 0.0260 | 1.0000 | 0.0260 | 1.000 | 0.0260 |
| G N2 APARTMENT | SPLIT GN2 | 0.000000 | 2.5000 | 0.000294 | 88.25 | 0.0260 | 1.0000 | 0.0260 | 1.000 | 0.0260 |
| G S1 APARTMENT | SPLIT GS1 | 0.000000 | 2.5000 | 0.000294 | 88.25 | 0.0260 | 1.0000 | 0.0260 | 1.000 | 0.0260 |
| G S2 APARTMENT | SPLIT GS2 | 0.000000 | 2.5000 | 0.000294 | 88.25 | 0.0260 | 1.0000 | 0.0260 | 1.000 | 0.0260 |
| M SW APARTMENT | SPLIT MSW | 0.000000 | 5.0000 | 0.000294 | 176.50 | 0.0519 | 1.0000 | 0.0519 | 1.000 | 0.0519 |
| M NW APARTMENT | SPLIT MNW | 0.000000 | 5.0000 | 0.000294 | 176.50 | 0.0519 | 1.0000 | 0.0519 | 1.000 | 0.0519 |
| M SE APARTMENT | SPLIT MSE | 0.000000 | 5.0000 | 0.000294 | 176.50 | 0.0519 | 1.0000 | 0.0519 | 1.000 | 0.0519 |
| M NE APARTMENT | SPLIT MNE | 0.000000 | 5.0000 | 0.000294 | 176.50 | 0.0519 | 1.0000 | 0.0519 | 1.000 | 0.0519 |
| M N1 APARTMENT | SPLIT MN1 | 0.000000 | 5.0000 | 0.000294 | 176.50 | 0.0519 | 1.0000 | 0.0519 | 1.000 | 0.0519 |
| M N2 APARTMENT | SPLIT MN2 | 0.000000 | 5.0000 | 0.000294 | 176.50 | 0.0519 | 1.0000 | 0.0519 | 1.000 | 0.0519 |
| M S1 APARTMENT | SPLIT MS1 | 0.000000 | 5.0000 | 0.000294 | 176.50 | 0.0519 | 1.0000 | 0.0519 | 1.000 | 0.0519 |
| M S2 APARTMENT | SPLIT MS2 | 0.000000 | 5.0000 | 0.000294 | 176.50 | 0.0519 | 1.0000 | 0.0519 | 1.000 | 0.0519 |
| T SW APARTMENT | SPLIT TSW | 0.000000 | 2.5000 | 0.000294 | 88.25 | 0.0260 | 1.0000 | 0.0260 | 1.000 | 0.0260 |
| T NW APARTMENT | SPLIT TNW | 0.000000 | 2.5000 | 0.000294 | 88.25 | 0.0260 | 1.0000 | 0.0260 | 1.000 | 0.0260 |
| T SE APARTMENT | SPLIT TSE | 0.000000 | 2.5000 | 0.000294 | 88.25 | 0.0260 | 1.0000 | 0.0260 | 1.000 | 0.0260 |
| T NE APARTMENT | SPLIT TNE | 0.000000 | 2.5000 | 0.000294 | 88.25 | 0.0260 | 1.0000 | 0.0260 | 1.000 | 0.0260 |
| T N1 APARTMENT | SPLIT TN1 | 0.000000 | 2.5000 | 0.000294 | 88.25 | 0.0260 | 1.0000 | 0.0260 | 1.000 | 0.0260 |
| T N2 APARTMENT | SPLIT TN2 | 0.000000 | 2.5000 | 0.000294 | 88.25 | 0.0260 | 1.0000 | 0.0260 | 1.000 | 0.0260 |
| T S1 APARTMENT | SPLIT TS1 | 0.000000 | 2.5000 | 0.000294 | 88.25 | 0.0260 | 1.0000 | 0.0260 | 1.000 | 0.0260 |
| T S2 APARTMENT | SPLIT TS2 | 0.000000 | 2.5000 | 0.000294 | 88.25 | 0.0260 | 1.0000 | 0.0260 | 1.000 | 0.0260 |
| People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
| SPLIT GSW | 0.000000 | 2.50 | 0.000294 | 88.2493 | 0.0260 | 0.0260 | 0.0260 |
| SPLIT GNW | 0.000000 | 2.50 | 0.000294 | 88.2493 | 0.0260 | 0.0260 | 0.0260 |
| SPLIT OFFICE | 0.000000 | 4.75 | 0.000432 | 88.2493 | 0.0381 | 0.0381 | 0.0381 |
| SPLIT GNE | 0.000000 | 2.50 | 0.000294 | 88.2493 | 0.0260 | 0.0260 | 0.0260 |
| SPLIT GN1 | 0.000000 | 2.50 | 0.000294 | 88.2493 | 0.0260 | 0.0260 | 0.0260 |
| SPLIT GN2 | 0.000000 | 2.50 | 0.000294 | 88.2493 | 0.0260 | 0.0260 | 0.0260 |
| SPLIT GS1 | 0.000000 | 2.50 | 0.000294 | 88.2493 | 0.0260 | 0.0260 | 0.0260 |
| SPLIT GS2 | 0.000000 | 2.50 | 0.000294 | 88.2493 | 0.0260 | 0.0260 | 0.0260 |
| SPLIT MSW | 0.000000 | 5.00 | 0.000294 | 176.4985 | 0.0519 | 0.0519 | 0.0519 |
| SPLIT MNW | 0.000000 | 5.00 | 0.000294 | 176.4985 | 0.0519 | 0.0519 | 0.0519 |
| SPLIT MSE | 0.000000 | 5.00 | 0.000294 | 176.4985 | 0.0519 | 0.0519 | 0.0519 |
| SPLIT MNE | 0.000000 | 5.00 | 0.000294 | 176.4985 | 0.0519 | 0.0519 | 0.0519 |
| SPLIT MN1 | 0.000000 | 5.00 | 0.000294 | 176.4985 | 0.0519 | 0.0519 | 0.0519 |
| SPLIT MN2 | 0.000000 | 5.00 | 0.000294 | 176.4985 | 0.0519 | 0.0519 | 0.0519 |
| SPLIT MS1 | 0.000000 | 5.00 | 0.000294 | 176.4985 | 0.0519 | 0.0519 | 0.0519 |
| SPLIT MS2 | 0.000000 | 5.00 | 0.000294 | 176.4985 | 0.0519 | 0.0519 | 0.0519 |
| SPLIT TSW | 0.000000 | 2.50 | 0.000294 | 88.2493 | 0.0260 | 0.0260 | 0.0260 |
| SPLIT TNW | 0.000000 | 2.50 | 0.000294 | 88.2493 | 0.0260 | 0.0260 | 0.0260 |
| SPLIT TSE | 0.000000 | 2.50 | 0.000294 | 88.2493 | 0.0260 | 0.0260 | 0.0260 |
| SPLIT TNE | 0.000000 | 2.50 | 0.000294 | 88.2493 | 0.0260 | 0.0260 | 0.0260 |
| SPLIT TN1 | 0.000000 | 2.50 | 0.000294 | 88.2493 | 0.0260 | 0.0260 | 0.0260 |
| SPLIT TN2 | 0.000000 | 2.50 | 0.000294 | 88.2493 | 0.0260 | 0.0260 | 0.0260 |
| SPLIT TS1 | 0.000000 | 2.50 | 0.000294 | 88.2493 | 0.0260 | 0.0260 | 0.0260 |
| SPLIT TS2 | 0.000000 | 2.50 | 0.000294 | 88.2493 | 0.0260 | 0.0260 | 0.0260 |
| AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
| G SW APARTMENT | SPLIT GSW | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.3648 | 0.3648 | 0.3648 | No | 0.0260 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| G NW APARTMENT | SPLIT GNW | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.3061 | 0.3061 | 0.3061 | No | 0.0260 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| OFFICE | SPLIT OFFICE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4024 | 0.4024 | 0.4024 | No | 0.0381 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| G NE APARTMENT | SPLIT GNE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.2688 | 0.2688 | 0.2688 | No | 0.0260 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| G N1 APARTMENT | SPLIT GN1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.2452 | 0.2452 | 0.2452 | No | 0.0260 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| G N2 APARTMENT | SPLIT GN2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.2445 | 0.2445 | 0.2445 | No | 0.0260 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| G S1 APARTMENT | SPLIT GS1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.3085 | 0.3085 | 0.3085 | No | 0.0260 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| G S2 APARTMENT | SPLIT GS2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.3101 | 0.3101 | 0.3101 | No | 0.0260 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| M SW APARTMENT | SPLIT MSW | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8855 | 0.8855 | 0.8855 | No | 0.0519 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| M NW APARTMENT | SPLIT MNW | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.7755 | 0.7755 | 0.7755 | No | 0.0519 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| M SE APARTMENT | SPLIT MSE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.7737 | 0.7737 | 0.7737 | No | 0.0519 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| M NE APARTMENT | SPLIT MNE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.6664 | 0.6664 | 0.6664 | No | 0.0519 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| M N1 APARTMENT | SPLIT MN1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.6030 | 0.6030 | 0.6030 | No | 0.0519 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| M N2 APARTMENT | SPLIT MN2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.6011 | 0.6011 | 0.6011 | No | 0.0519 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| M S1 APARTMENT | SPLIT MS1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.7232 | 0.7232 | 0.7232 | No | 0.0519 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| M S2 APARTMENT | SPLIT MS2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.7210 | 0.7210 | 0.7210 | No | 0.0519 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| T SW APARTMENT | SPLIT TSW | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4745 | 0.4745 | 0.4745 | No | 0.0260 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| T NW APARTMENT | SPLIT TNW | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4297 | 0.4297 | 0.4297 | No | 0.0260 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| T SE APARTMENT | SPLIT TSE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.3935 | 0.3935 | 0.3935 | No | 0.0260 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| T NE APARTMENT | SPLIT TNE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.3494 | 0.3494 | 0.3494 | No | 0.0260 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| T N1 APARTMENT | SPLIT TN1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.3328 | 0.3328 | 0.3328 | No | 0.0260 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| T N2 APARTMENT | SPLIT TN2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.3302 | 0.3302 | 0.3302 | No | 0.0260 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| T S1 APARTMENT | SPLIT TS1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.3803 | 0.3803 | 0.3803 | No | 0.0260 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| T S2 APARTMENT | SPLIT TS2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.3777 | 0.3777 | 0.3777 | No | 0.0260 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
| SPLIT GSW | 0.3648 | 0.3648 | 0.3648 | 0.3648 | 0.0260 | 1.0000 |
| SPLIT GNW | 0.3061 | 0.3061 | 0.3061 | 0.3061 | 0.0260 | 1.0000 |
| SPLIT OFFICE | 0.4024 | 0.4024 | 0.4024 | 0.4024 | 0.0381 | 1.0000 |
| SPLIT GNE | 0.2688 | 0.2688 | 0.2688 | 0.2688 | 0.0260 | 1.0000 |
| SPLIT GN1 | 0.2452 | 0.2452 | 0.2452 | 0.2452 | 0.0260 | 1.0000 |
| SPLIT GN2 | 0.2445 | 0.2445 | 0.2445 | 0.2445 | 0.0260 | 1.0000 |
| SPLIT GS1 | 0.3085 | 0.3085 | 0.3085 | 0.3085 | 0.0260 | 1.0000 |
| SPLIT GS2 | 0.3101 | 0.3101 | 0.3101 | 0.3101 | 0.0260 | 1.0000 |
| SPLIT MSW | 0.8855 | 0.8855 | 0.8855 | 0.8855 | 0.0519 | 1.0000 |
| SPLIT MNW | 0.7755 | 0.7755 | 0.7755 | 0.7755 | 0.0519 | 1.0000 |
| SPLIT MSE | 0.7737 | 0.7737 | 0.7737 | 0.7737 | 0.0519 | 1.0000 |
| SPLIT MNE | 0.6664 | 0.6664 | 0.6664 | 0.6664 | 0.0519 | 1.0000 |
| SPLIT MN1 | 0.6030 | 0.6030 | 0.6030 | 0.6030 | 0.0519 | 1.0000 |
| SPLIT MN2 | 0.6011 | 0.6011 | 0.6011 | 0.6011 | 0.0519 | 1.0000 |
| SPLIT MS1 | 0.7232 | 0.7232 | 0.7232 | 0.7232 | 0.0519 | 1.0000 |
| SPLIT MS2 | 0.7210 | 0.7210 | 0.7210 | 0.7210 | 0.0519 | 1.0000 |
| SPLIT TSW | 0.4745 | 0.4745 | 0.4745 | 0.4745 | 0.0260 | 1.0000 |
| SPLIT TNW | 0.4297 | 0.4297 | 0.4297 | 0.4297 | 0.0260 | 1.0000 |
| SPLIT TSE | 0.3935 | 0.3935 | 0.3935 | 0.3935 | 0.0260 | 1.0000 |
| SPLIT TNE | 0.3494 | 0.3494 | 0.3494 | 0.3494 | 0.0260 | 1.0000 |
| SPLIT TN1 | 0.3328 | 0.3328 | 0.3328 | 0.3328 | 0.0260 | 1.0000 |
| SPLIT TN2 | 0.3302 | 0.3302 | 0.3302 | 0.3302 | 0.0260 | 1.0000 |
| SPLIT TS1 | 0.3803 | 0.3803 | 0.3803 | 0.3803 | 0.0260 | 1.0000 |
| SPLIT TS2 | 0.3777 | 0.3777 | 0.3777 | 0.3777 | 0.0260 | 1.0000 |
| AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
| G SW APARTMENT | SPLIT GSW | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.3648 | 0.3648 | 0.3648 | No | 0.0260 | 0.3367 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| G NW APARTMENT | SPLIT GNW | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.3061 | 0.3061 | 0.3061 | No | 0.0260 | 0.3651 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| OFFICE | SPLIT OFFICE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4024 | 0.4024 | 0.4024 | No | 0.0381 | 0.3799 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| G NE APARTMENT | SPLIT GNE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.2688 | 0.2688 | 0.2688 | No | 0.0260 | 0.3642 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| G N1 APARTMENT | SPLIT GN1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.2452 | 0.2452 | 0.2452 | No | 0.0260 | 0.6347 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| G N2 APARTMENT | SPLIT GN2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.2445 | 0.2445 | 0.2445 | No | 0.0260 | 0.6347 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| G S1 APARTMENT | SPLIT GS1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.3085 | 0.3085 | 0.3085 | No | 0.0260 | 0.5527 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| G S2 APARTMENT | SPLIT GS2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.3101 | 0.3101 | 0.3101 | No | 0.0260 | 0.5474 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| M SW APARTMENT | SPLIT MSW | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8855 | 0.8855 | 0.8855 | No | 0.0519 | 0.3721 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| M NW APARTMENT | SPLIT MNW | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.7755 | 0.7755 | 0.7755 | No | 0.0519 | 0.4147 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| M SE APARTMENT | SPLIT MSE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.7737 | 0.7737 | 0.7737 | No | 0.0519 | 0.3710 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| M NE APARTMENT | SPLIT MNE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.6664 | 0.6664 | 0.6664 | No | 0.0519 | 0.4133 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| M N1 APARTMENT | SPLIT MN1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.6030 | 0.6030 | 0.6030 | No | 0.0519 | 0.8535 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| M N2 APARTMENT | SPLIT MN2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.6011 | 0.6011 | 0.6011 | No | 0.0519 | 0.8533 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| M S1 APARTMENT | SPLIT MS1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.7232 | 0.7232 | 0.7232 | No | 0.0519 | 0.6945 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| M S2 APARTMENT | SPLIT MS2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.7210 | 0.7210 | 0.7210 | No | 0.0519 | 0.6944 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| T SW APARTMENT | SPLIT TSW | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4745 | 0.4745 | 0.4745 | No | 0.0260 | 0.2119 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| T NW APARTMENT | SPLIT TNW | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4297 | 0.4297 | 0.4297 | No | 0.0260 | 0.2258 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| T SE APARTMENT | SPLIT TSE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.3935 | 0.3935 | 0.3935 | No | 0.0260 | 0.2114 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| T NE APARTMENT | SPLIT TNE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.3494 | 0.3494 | 0.3494 | No | 0.0260 | 0.2252 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| T N1 APARTMENT | SPLIT TN1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.3328 | 0.3328 | 0.3328 | No | 0.0260 | 0.3390 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| T N2 APARTMENT | SPLIT TN2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.3302 | 0.3302 | 0.3302 | No | 0.0260 | 0.3389 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| T S1 APARTMENT | SPLIT TS1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.3803 | 0.3803 | 0.3803 | No | 0.0260 | 0.3086 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| T S2 APARTMENT | SPLIT TS2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.3777 | 0.3777 | 0.3777 | No | 0.0260 | 0.3086 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
| SPLIT GSW | 0.3648 | 0.3648 | 0.3648 | 0.3648 | 0.0260 | 1.0000 |
| SPLIT GNW | 0.3061 | 0.3061 | 0.3061 | 0.3061 | 0.0260 | 1.0000 |
| SPLIT OFFICE | 0.4024 | 0.4024 | 0.4024 | 0.4024 | 0.0381 | 1.0000 |
| SPLIT GNE | 0.2688 | 0.2688 | 0.2688 | 0.2688 | 0.0260 | 1.0000 |
| SPLIT GN1 | 0.2452 | 0.2452 | 0.2452 | 0.2452 | 0.0260 | 1.0000 |
| SPLIT GN2 | 0.2445 | 0.2445 | 0.2445 | 0.2445 | 0.0260 | 1.0000 |
| SPLIT GS1 | 0.3085 | 0.3085 | 0.3085 | 0.3085 | 0.0260 | 1.0000 |
| SPLIT GS2 | 0.3101 | 0.3101 | 0.3101 | 0.3101 | 0.0260 | 1.0000 |
| SPLIT MSW | 0.8855 | 0.8855 | 0.8855 | 0.8855 | 0.0519 | 1.0000 |
| SPLIT MNW | 0.7755 | 0.7755 | 0.7755 | 0.7755 | 0.0519 | 1.0000 |
| SPLIT MSE | 0.7737 | 0.7737 | 0.7737 | 0.7737 | 0.0519 | 1.0000 |
| SPLIT MNE | 0.6664 | 0.6664 | 0.6664 | 0.6664 | 0.0519 | 1.0000 |
| SPLIT MN1 | 0.6030 | 0.6030 | 0.6030 | 0.6030 | 0.0519 | 1.0000 |
| SPLIT MN2 | 0.6011 | 0.6011 | 0.6011 | 0.6011 | 0.0519 | 1.0000 |
| SPLIT MS1 | 0.7232 | 0.7232 | 0.7232 | 0.7232 | 0.0519 | 1.0000 |
| SPLIT MS2 | 0.7210 | 0.7210 | 0.7210 | 0.7210 | 0.0519 | 1.0000 |
| SPLIT TSW | 0.4745 | 0.4745 | 0.4745 | 0.4745 | 0.0260 | 1.0000 |
| SPLIT TNW | 0.4297 | 0.4297 | 0.4297 | 0.4297 | 0.0260 | 1.0000 |
| SPLIT TSE | 0.3935 | 0.3935 | 0.3935 | 0.3935 | 0.0260 | 1.0000 |
| SPLIT TNE | 0.3494 | 0.3494 | 0.3494 | 0.3494 | 0.0260 | 1.0000 |
| SPLIT TN1 | 0.3328 | 0.3328 | 0.3328 | 0.3328 | 0.0260 | 1.0000 |
| SPLIT TN2 | 0.3302 | 0.3302 | 0.3302 | 0.3302 | 0.0260 | 1.0000 |
| SPLIT TS1 | 0.3803 | 0.3803 | 0.3803 | 0.3803 | 0.0260 | 1.0000 |
| SPLIT TS2 | 0.3777 | 0.3777 | 0.3777 | 0.3777 | 0.0260 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 09:15:24
Sec1.1A-General Information| Data | |
| Weather File | RUNPERIOD 1 ** Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930 |
| Total gross floor area [m2] | 3134.61 |
| Principal Heating Source | Natural Gas |
| Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
| G SW APARTMENT | 88.25 | 88.25 | 0.00 | 117.85 |
| G NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
| OFFICE | 88.25 | 88.25 | 0.00 | 33.56 |
| G NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
| G N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
| G N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
| G S1 APARTMENT | 88.25 | 88.25 | 0.00 | 117.85 |
| G S2 APARTMENT | 88.25 | 88.25 | 0.00 | 117.85 |
| M SW APARTMENT | 88.25 | 88.25 | 0.00 | 117.85 |
| M NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
| M SE APARTMENT | 88.25 | 88.25 | 0.00 | 117.85 |
| M NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
| M N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
| M N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
| M S1 APARTMENT | 88.25 | 88.25 | 0.00 | 117.85 |
| M S2 APARTMENT | 88.25 | 88.25 | 0.00 | 117.85 |
| T SW APARTMENT | 88.25 | 88.25 | 0.00 | 117.85 |
| T NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
| T SE APARTMENT | 88.25 | 88.25 | 0.00 | 117.85 |
| T NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
| T N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
| T N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
| T S1 APARTMENT | 88.25 | 88.25 | 0.00 | 117.85 |
| T S2 APARTMENT | 88.25 | 88.25 | 0.00 | 117.85 |
| T CORRIDOR | 77.66 | 0.00 | 77.66 | 168.00 |
| G CORRIDOR | 77.66 | 0.00 | 77.66 | 168.00 |
| M CORRIDOR | 77.66 | 0.00 | 77.66 | 168.00 |
| Totals | 3134.61 | 2823.98 | 310.64 |
| Data | |
| Number of hours heating loads not met | 0.00 |
| Number of hours cooling loads not met | 0.00 |
| Number of hours not met | 0.00 |
| Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
| None |
| Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
| Heating -- General | 0.00 | 0.00 | 245.36 | 63056.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Cooling -- General | 51.06 | 21407.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Lighting -- LightsWired | 94.96 | 5496.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Lighting -- LightsPlugIn | 4.27 | 407.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Lighting -- General | 49.92 | 3183.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment -- MiscPlug | 388.06 | 18541.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment -- ElevatorLift | 65.48 | 4006.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment -- ElevatorLightsFan | 5.11 | 162.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans -- Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans -- General | 77.17 | 7599.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Recovery -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems -- Water Heater | 462.63 | 37762.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Process Subtotal [GJ] | Total Energy Use [GJ] | |
| Electricity | 458.66 | 1198.67 |
| Natural Gas | 0.00 | 245.36 |
| Additional | 0.00 | 0.00 |
| Total | 458.66 | 1444.03 |
| Process Subtotal [$] | Total Energy Cost [$] | |
| Electricity | 0.00 | |
| Natural Gas | 0.00 | |
| Additional | 0.00 | |
| Total | 0.00 |
| Rated Capacity [kW] | Annual Energy Generated [GJ] | |
| Photovoltaic | 0.00 | 0.00 |
| Wind | 0.00 | 0.00 |
| Electricty [MJ/m2] | |
| Interior Lighting (All) | 31.66 |
| Space Heating | 0.00 |
| Space Cooling | 16.29 |
| Fans (All) | 24.62 |
| Service Water Heating | 147.59 |
| Receptacle Equipment | 146.32 |
| Miscellaneous (All) | 382.40 |
| Subtotal | 382.40 |
| Natural Gas [MJ/m2] | |
| Space Heating | 78.27 |
| Service Water Heating | 0.00 |
| Miscellaneous (All) | 78.27 |
| Subtotal | 78.27 |
| Additional [MJ/m2] | |
| Subtotal | 0.00 |
| Miscellaneous | 0.00 |
| Percent [%] | |
| Interior Lighting (All) | 6.87 |
| Space Heating | 16.99 |
| Space Cooling | 3.54 |
| Fans (All) | 5.34 |
| Service Water Heating | 32.04 |
| Receptacle Equipment | 31.76 |
| Miscellaneous | 3.46 |
| Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
| OCC_APT_SCH_STAY_HOME_FAMILY | 5993. | 8760. |
| OCC_APT_SCH_CORRIDOR | 5993. | 8760. |
| OCC_APT_SCH_WORKING_FAMILY | 5845. | 6055. |
| OCC_OFF_SCH | 2210. | 2340. |
| OCC_OFF_W_SB_SCH | 1820. | 1820. |
| LTG_SCH_OFFICE | 2435. | 8760. |
| LTG_SCH_CORRIDOR | 8760. | 8760. |
| LTG_SCH_APARTMENT_HARDWIRED | 527. | 8760. |
| LTG_SCH_APARTMENT_PLUGIN | 527. | 8760. |
| EQP_APT_SCH | 5763. | 8760. |
| EQP_OFF_SCH | 4531. | 8760. |
| INF_APT_SCH | 8760. | 8760. |
| INF_OFF_SCH | 8760. | 8760. |
| INF_COR_SCH | 8760. | 8760. |
| INFIL_DOOR_OPENING_SCH | 1466. | 5840. |
| ALL OFF | 0. | 0. |
| ALL ON | 8760. | 8760. |
| ALWAYS_ON | 8760. | 8760. |
| ALLON_EXCEPT_DD | 8760. | 8760. |
| EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
| FAN_OFF_W_SB_SCH | 8240. | 8240. |
| APT_DHW_SCH | 4592. | 8760. |
| EXTERIOR_LTG_SCH | 4380. | 4380. |
| BLDG_ELEVATORS | 2270. | 8760. |
| ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
| ELEV_LIGHT_FAN_SCH_ADD_DF | 2154. | 8760. |
| SLIDING_DOORS_VENTILATION_AVAILABILITY_SCH | 5840. | 5840. |
| First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
| HTGSETP_APT_SCH | APTHEATINGSETPOINT | January | 21.10 | 365 | 21.10 | 365 |
| HTGSETP_DESIGN_OFF_SCH | OFFHEATINGSETPOINT | January | 21.10 | 365 | 21.10 | 365 |
| CLGSETP_APT_SCH | APTCOOLINGSETPOINT | July | 24.00 | 365 | 24.00 | 365 |
| CLGSETP_DESIGN_OFF_SCH | OFFCOOLINGSETPOINT | July | 23.90 | 365 | 23.90 | 365 |
| S HTGSETP_APT_SCH | S APARTMENT DUAL SP CONTROL | January | 21.10 | 365 | 21.10 | 365 |
| S CLGSETP_APT_SCH | S APARTMENT DUAL SP CONTROL | July | 24.00 | 365 | 24.00 | 365 |
| N HTGSETP_APT_SCH | N APARTMENT DUAL SP CONTROL | January | 21.10 | 365 | 21.10 | 365 |
| N CLGSETP_APT_SCH | N APARTMENT DUAL SP CONTROL | July | 24.00 | 365 | 24.00 | 365 |
| HTGSETP_OFF_SCH_YES_OPTIMUM | OFFICE DUAL SP CONTROL | January | 21.10 | 365 | 15.60 | 365 |
| CLGSETP_OFF_SCH_YES_OPTIMUM | OFFICE DUAL SP CONTROL | July | 24.00 | 365 | 29.40 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 09:15:24
Heat Index Hours| Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
| G SW APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| G NW APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| OFFICE | 8376.33 | 383.67 | 0.00 | 0.00 | 0.00 |
| G NE APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| G N1 APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| G N2 APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| G S1 APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| G S2 APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M SW APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M NW APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M SE APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M NE APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M N1 APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M N2 APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M S1 APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M S2 APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T SW APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T NW APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T SE APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T NE APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T N1 APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T N2 APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T S1 APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T S2 APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T CORRIDOR | 8012.17 | 745.00 | 2.83 | 0.00 | 0.00 |
| G CORRIDOR | 8691.83 | 68.17 | 0.00 | 0.00 | 0.00 |
| M CORRIDOR | 6372.50 | 2387.50 | 0.00 | 0.00 | 0.00 |
| Min | 6372.50 | 0.00 | 0.00 | 0.00 | 0.00 |
| Max | 8760.00 | 2387.50 | 2.83 | 0.00 | 0.00 |
| Average | 8627.14 | 132.75 | 0.10 | 0.00 | 0.00 |
| Sum | 232932.83 | 3584.33 | 2.83 | 0.00 | 0.00 |
| Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
| G SW APARTMENT | 11830.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| G NW APARTMENT | 10585.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| OFFICE | 7000.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| G NE APARTMENT | 10585.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| G N1 APARTMENT | 10585.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| G N2 APARTMENT | 10585.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| G S1 APARTMENT | 11830.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| G S2 APARTMENT | 11830.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M SW APARTMENT | 11830.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M NW APARTMENT | 10585.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M SE APARTMENT | 11830.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M NE APARTMENT | 10585.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M N1 APARTMENT | 10585.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M N2 APARTMENT | 10585.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M S1 APARTMENT | 11830.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M S2 APARTMENT | 11830.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T SW APARTMENT | 11830.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T NW APARTMENT | 10585.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T SE APARTMENT | 11830.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T NE APARTMENT | 10585.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T N1 APARTMENT | 10585.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T N2 APARTMENT | 10585.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T S1 APARTMENT | 11830.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T S2 APARTMENT | 11830.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T CORRIDOR | 21197.67 | 1788.00 | 9.33 | 0.00 | 0.00 |
| G CORRIDOR | 22831.33 | 163.67 | 0.00 | 0.00 | 0.00 |
| M CORRIDOR | 16752.83 | 6242.17 | 0.00 | 0.00 | 0.00 |
| Min | 7000.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Max | 22831.33 | 6242.17 | 9.33 | 0.00 | 0.00 |
| Average | 12034.51 | 303.48 | 0.35 | 0.00 | 0.00 |
| Sum | 324931.83 | 8193.83 | 9.33 | 0.00 | 0.00 |
| Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
| G SW APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| G NW APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| OFFICE | 8354.00 | 406.00 | 0.00 | 0.00 | 0.00 |
| G NE APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| G N1 APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| G N2 APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| G S1 APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| G S2 APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M SW APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M NW APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M SE APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M NE APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M N1 APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M N2 APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M S1 APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M S2 APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T SW APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T NW APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T SE APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T NE APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T N1 APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T N2 APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T S1 APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T S2 APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T CORRIDOR | 3924.33 | 4829.17 | 6.50 | 0.00 | 0.00 |
| G CORRIDOR | 7937.83 | 822.17 | 0.00 | 0.00 | 0.00 |
| M CORRIDOR | 989.67 | 7754.00 | 16.33 | 0.00 | 0.00 |
| Min | 989.67 | 0.00 | 0.00 | 0.00 | 0.00 |
| Max | 8760.00 | 7754.00 | 16.33 | 0.00 | 0.00 |
| Average | 8247.62 | 511.53 | 0.85 | 0.00 | 0.00 |
| Sum | 222685.83 | 13811.33 | 22.83 | 0.00 | 0.00 |
| Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
| G SW APARTMENT | 11830.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| G NW APARTMENT | 10585.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| OFFICE | 6997.33 | 2.67 | 0.00 | 0.00 | 0.00 |
| G NE APARTMENT | 10585.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| G N1 APARTMENT | 10585.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| G N2 APARTMENT | 10585.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| G S1 APARTMENT | 11830.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| G S2 APARTMENT | 11830.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M SW APARTMENT | 11830.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M NW APARTMENT | 10585.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M SE APARTMENT | 11830.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M NE APARTMENT | 10585.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M N1 APARTMENT | 10585.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M N2 APARTMENT | 10585.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M S1 APARTMENT | 11830.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M S2 APARTMENT | 11830.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T SW APARTMENT | 11830.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T NW APARTMENT | 10585.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T SE APARTMENT | 11830.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T NE APARTMENT | 10585.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T N1 APARTMENT | 10585.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T N2 APARTMENT | 10585.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T S1 APARTMENT | 11830.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T S2 APARTMENT | 11830.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T CORRIDOR | 10259.83 | 12712.17 | 23.00 | 0.00 | 0.00 |
| G CORRIDOR | 20025.00 | 2970.00 | 0.00 | 0.00 | 0.00 |
| M CORRIDOR | 2585.33 | 20357.33 | 52.33 | 0.00 | 0.00 |
| Min | 2585.33 | 0.00 | 0.00 | 0.00 | 0.00 |
| Max | 20025.00 | 20357.33 | 52.33 | 0.00 | 0.00 |
| Average | 11000.65 | 1334.90 | 2.79 | 0.00 | 0.00 |
| Sum | 297017.50 | 36042.17 | 75.33 | 0.00 | 0.00 |
| SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
| None |
| SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
| None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 09:15:24
CO2 Level Hours| Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
| None |
| Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
| None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 09:15:24
Illuminance Level Hours| A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
| None |
| A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
| None |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
| January | 4.496 |
| February | 5.822 |
| March | 8.326 |
| April | 10.851 |
| May | 12.973 |
| June | 15.587 |
| July | 17.665 |
| August | 18.800 |
| September | 15.086 |
| October | 11.426 |
| November | 8.070 |
| December | 5.416 |
| Annual Sum or Average | 11.241 |
| Minimum of Months | 4.496 |
| Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Environment
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
| January | 4.496 |
| February | 5.822 |
| March | 8.326 |
| April | 10.851 |
| May | 12.973 |
| June | 15.587 |
| July | 17.665 |
| August | 18.800 |
| September | 15.086 |
| October | 11.426 |
| November | 8.070 |
| December | 5.416 |
| Annual Sum or Average | 11.241 |
| Minimum of Months | 4.496 |
| Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2012
For: Environment
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
| January | 4.496 |
| February | 5.822 |
| March | 8.326 |
| April | 10.851 |
| May | 12.973 |
| June | 15.587 |
| July | 17.665 |
| August | 18.800 |
| September | 15.086 |
| October | 11.426 |
| November | 8.070 |
| December | 5.416 |
| Annual Sum or Average | 11.241 |
| Minimum of Months | 4.496 |
| Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
| January | 4.496 |
| February | 5.822 |
| March | 8.326 |
| April | 10.851 |
| May | 12.973 |
| June | 15.587 |
| July | 17.665 |
| August | 18.800 |
| September | 15.086 |
| October | 11.426 |
| November | 8.070 |
| December | 5.416 |
| Annual Sum or Average | 11.241 |
| Minimum of Months | 4.496 |
| Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME APARTMENTMIDRISE
For: Environment
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
| January | 4.496 |
| February | 5.822 |
| March | 8.326 |
| April | 10.851 |
| May | 12.973 |
| June | 15.587 |
| July | 17.665 |
| August | 18.800 |
| September | 15.086 |
| October | 11.426 |
| November | 8.070 |
| December | 5.416 |
| Annual Sum or Average | 11.241 |
| Minimum of Months | 4.496 |
| Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
| January | 4.496 |
| February | 5.822 |
| March | 8.326 |
| April | 10.851 |
| May | 12.973 |
| June | 15.587 |
| July | 17.665 |
| August | 18.800 |
| September | 15.086 |
| October | 11.426 |
| November | 8.070 |
| December | 5.416 |
| Annual Sum or Average | 11.241 |
| Minimum of Months | 4.496 |
| Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
| January | 4.496 |
| February | 5.822 |
| March | 8.326 |
| April | 10.851 |
| May | 12.973 |
| June | 15.587 |
| July | 17.665 |
| August | 18.800 |
| September | 15.086 |
| October | 11.426 |
| November | 8.070 |
| December | 5.416 |
| Annual Sum or Average | 11.241 |
| Minimum of Months | 4.496 |
| Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4C
For: Environment
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
| January | 4.496 |
| February | 5.822 |
| March | 8.326 |
| April | 10.851 |
| May | 12.973 |
| June | 15.587 |
| July | 17.665 |
| August | 18.800 |
| September | 15.086 |
| October | 11.426 |
| November | 8.070 |
| December | 5.416 |
| Annual Sum or Average | 11.241 |
| Minimum of Months | 4.496 |
| Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_WA_SEATTLE
For: Environment
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
| January | 4.496 |
| February | 5.822 |
| March | 8.326 |
| April | 10.851 |
| May | 12.973 |
| June | 15.587 |
| July | 17.665 |
| August | 18.800 |
| September | 15.086 |
| October | 11.426 |
| November | 8.070 |
| December | 5.416 |
| Annual Sum or Average | 11.241 |
| Minimum of Months | 4.496 |
| Maximum of Months | 18.800 |
Report: ZoneCoolingSummaryMonthly
For: G SW APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 30564411.49 | 475.36 | 08-JAN-14:20 | 5.20 | 2.69 | 78198328.66 | 42.51 | 26-JAN-18:49 | 8.30 | 7.74 |
| February | 0.169080E+09 | 517.96 | 09-FEB-17:25 | 3.90 | 1.98 | 69986590.55 | 57.67 | 27-FEB-18:10 | 17.02 | 11.99 |
| March | 0.351486E+09 | 505.63 | 01-MAR-22:50 | 4.27 | 3.20 | 77104624.20 | 69.66 | 18-MAR-16:40 | 19.80 | 9.88 |
| April | 0.572466E+09 | 1068.98 | 27-APR-16:07 | 27.02 | 16.89 | 85673557.16 | 70.36 | 29-APR-19:30 | 16.40 | 12.16 |
| May | 0.969534E+09 | 1400.35 | 15-MAY-16:03 | 23.98 | 12.88 | 0.101932E+09 | 70.37 | 04-MAY-23:10 | 23.98 | 12.88 |
| June | 0.105028E+10 | 1550.67 | 28-JUN-16:27 | 26.40 | 16.52 | 0.111821E+09 | 70.36 | 21-JUN-02:20 | 26.40 | 16.52 |
| July | 0.172985E+10 | 1912.96 | 31-JUL-17:17 | 27.77 | 18.62 | 0.127924E+09 | 70.36 | 19-JUL-02:30 | 27.77 | 18.62 |
| August | 0.194943E+10 | 2213.89 | 10-AUG-17:20 | 31.43 | 18.98 | 0.122811E+09 | 70.36 | 19-AUG-23:19 | 14.43 | 12.75 |
| September | 0.149563E+10 | 1978.44 | 11-SEP-16:04 | 23.12 | 16.02 | 0.119881E+09 | 70.36 | 03-SEP-03:00 | 23.12 | 16.02 |
| October | 0.952446E+09 | 1556.78 | 04-OCT-16:08 | 21.02 | 11.40 | 99353647.21 | 70.37 | 09-OCT-20:30 | 13.05 | 11.04 |
| November | 0.323241E+09 | 521.02 | 11-NOV-19:10 | 3.80 | 3.06 | 78129239.49 | 70.27 | 04-NOV-15:30 | 3.80 | 3.06 |
| December | 0.122961E+09 | 558.59 | 06-DEC-16:20 | 2.57 | 2.27 | 78376789.23 | 50.33 | 03-DEC-16:10 | 2.57 | 2.27 |
| Annual Sum or Average | 0.971697E+10 | 0.115119E+10 | ||||||||
| Minimum of Months | 30564411.49 | 475.36 | 2.57 | 1.98 | 69986590.55 | 42.51 | 2.57 | 2.27 | ||
| Maximum of Months | 0.194943E+10 | 2213.89 | 31.43 | 18.98 | 0.127924E+09 | 70.37 | 27.77 | 18.62 |
Report: ZoneCoolingSummaryMonthly
For: G NW APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 7720.40 | 4.35 | 11-JAN-20:00 | 12.80 | 10.11 | 77895344.65 | 42.51 | 10-JAN-22:40 | 12.80 | 10.11 |
| February | 34448466.46 | 321.71 | 25-FEB-19:50 | 10.10 | 9.47 | 70402555.76 | 43.03 | 27-FEB-21:10 | 12.20 | 10.06 |
| March | 96857934.53 | 371.53 | 30-MAR-19:50 | 8.40 | 4.98 | 78032425.36 | 46.00 | 18-MAR-17:10 | 8.40 | 4.98 |
| April | 0.293379E+09 | 393.29 | 29-APR-05:00 | 8.30 | 8.30 | 80239435.28 | 68.52 | 27-APR-20:10 | 8.30 | 8.30 |
| May | 0.739167E+09 | 786.61 | 15-MAY-16:30 | 24.15 | 12.93 | 96522472.91 | 70.27 | 07-MAY-21:10 | 24.15 | 12.93 |
| June | 0.839733E+09 | 1300.55 | 28-JUN-18:00 | 25.60 | 16.63 | 0.111674E+09 | 70.36 | 10-JUN-22:30 | 25.60 | 16.63 |
| July | 0.131584E+10 | 1580.84 | 24-JUL-18:00 | 28.90 | 17.96 | 0.126594E+09 | 70.36 | 23-JUL-03:00 | 28.90 | 17.96 |
| August | 0.137966E+10 | 1723.41 | 10-AUG-18:00 | 30.70 | 19.49 | 0.126844E+09 | 70.36 | 16-AUG-23:30 | 14.30 | 11.96 |
| September | 0.888056E+09 | 1159.27 | 14-SEP-16:30 | 24.70 | 16.87 | 0.114961E+09 | 70.35 | 08-SEP-22:49 | 24.70 | 16.87 |
| October | 0.536668E+09 | 449.02 | 12-OCT-07:00 | 6.10 | 4.77 | 87478747.11 | 64.14 | 04-OCT-20:00 | 6.10 | 4.77 |
| November | 0.142298E+09 | 324.11 | 05-NOV-20:00 | 10.60 | 9.38 | 76140630.77 | 50.50 | 04-NOV-20:10 | 10.60 | 9.38 |
| December | 1033397.48 | 76.29 | 10-DEC-15:10 | 10.50 | 8.73 | 77895344.66 | 42.51 | 11-DEC-06:49 | 2.80 | 2.57 |
| Annual Sum or Average | 0.626715E+10 | 0.112468E+10 | ||||||||
| Minimum of Months | 7720.40 | 4.35 | 6.10 | 4.77 | 70402555.76 | 42.51 | 2.80 | 2.57 | ||
| Maximum of Months | 0.137966E+10 | 1723.41 | 30.70 | 19.49 | 0.126844E+09 | 70.36 | 28.90 | 17.96 |
Report: ZoneCoolingSummaryMonthly
For: OFFICE
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.366751E+09 | 802.20 | 06-JAN-08:03 | -2.7 | -2.7 | 39023781.23 | 90.57 | 11-JAN-16:19 | 13.67 | 10.10 |
| February | 0.362227E+09 | 742.72 | 09-FEB-08:02 | -0.6 | -1.1 | 39936287.18 | 133.51 | 27-FEB-16:49 | 18.98 | 12.21 |
| March | 0.357737E+09 | 606.50 | 24-MAR-07:02 | 2.48 | -1.6 | 53999760.14 | 134.28 | 14-MAR-14:50 | 2.48 | -1.6 |
| April | 0.365649E+09 | 2832.82 | 27-APR-08:63 | 16.38 | 12.13 | 56552810.79 | 152.96 | 27-APR-08:09 | 16.38 | 12.13 |
| May | 0.600889E+09 | 5933.83 | 15-MAY-08:62 | 15.37 | 10.96 | 72528163.64 | 166.80 | 15-MAY-08:09 | 15.37 | 10.96 |
| June | 0.831025E+09 | 5981.62 | 09-JUN-08:62 | 14.68 | 10.55 | 75491188.20 | 169.66 | 28-JUN-07:10 | 16.38 | 12.64 |
| July | 0.111561E+10 | 6308.36 | 24-JUL-07:02 | 19.37 | 15.37 | 69892287.93 | 216.28 | 24-JUL-07:10 | 19.37 | 15.37 |
| August | 0.150736E+10 | 6380.28 | 15-AUG-07:01 | 14.72 | 12.03 | 80565166.90 | 215.53 | 14-AUG-07:10 | 14.72 | 12.03 |
| September | 0.102574E+10 | 6035.48 | 11-SEP-08:62 | 15.28 | 12.74 | 68900129.82 | 182.15 | 11-SEP-07:10 | 15.28 | 12.74 |
| October | 0.587285E+09 | 5934.98 | 04-OCT-08:62 | 14.18 | 9.87 | 66135577.46 | 165.67 | 04-OCT-08:09 | 14.18 | 9.87 |
| November | 0.331303E+09 | 576.60 | 22-NOV-08:02 | 2.88 | 2.41 | 47526285.60 | 133.51 | 02-NOV-14:09 | 2.88 | 2.41 |
| December | 0.388980E+09 | 717.98 | 26-DEC-08:03 | -1.1 | -1.2 | 39966902.83 | 113.26 | 05-DEC-13:00 | -1.1 | -1.2 |
| Annual Sum or Average | 0.784056E+10 | 0.710518E+09 | ||||||||
| Minimum of Months | 0.331303E+09 | 576.60 | -2.7 | -2.7 | 39023781.23 | 90.57 | -1.1 | -1.6 | ||
| Maximum of Months | 0.150736E+10 | 6380.28 | 19.37 | 15.37 | 80565166.90 | 216.28 | 19.37 | 15.37 |
Report: ZoneCoolingSummaryMonthly
For: G NE APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 7364.17 | 6.87 | 11-JAN-20:00 | 12.80 | 10.11 | 77895344.65 | 42.51 | 10-JAN-22:40 | 12.80 | 10.11 |
| February | 32514482.74 | 321.68 | 25-FEB-19:50 | 10.10 | 9.47 | 70370572.99 | 42.51 | 27-FEB-21:10 | 12.20 | 10.06 |
| March | 89809469.23 | 371.73 | 30-MAR-19:50 | 8.40 | 4.98 | 77907866.23 | 43.51 | 18-MAR-20:30 | 8.40 | 4.98 |
| April | 0.319346E+09 | 390.45 | 29-APR-05:00 | 8.30 | 8.30 | 79849710.15 | 66.94 | 27-APR-20:10 | 8.30 | 8.30 |
| May | 0.706548E+09 | 531.19 | 15-MAY-16:15 | 24.07 | 12.90 | 95112427.31 | 69.77 | 07-MAY-21:10 | 24.07 | 12.90 |
| June | 0.854461E+09 | 1007.66 | 28-JUN-18:00 | 25.60 | 16.63 | 0.112435E+09 | 70.37 | 23-JUN-20:00 | 25.60 | 16.63 |
| July | 0.121392E+10 | 1353.37 | 24-JUL-18:00 | 28.90 | 17.96 | 0.125684E+09 | 70.36 | 06-JUL-22:30 | 28.90 | 17.96 |
| August | 0.137783E+10 | 1297.24 | 10-AUG-17:07 | 31.62 | 18.84 | 0.126711E+09 | 70.36 | 03-AUG-21:49 | 31.62 | 18.84 |
| September | 0.861528E+09 | 912.08 | 14-SEP-16:30 | 24.70 | 16.87 | 0.113573E+09 | 70.37 | 04-SEP-21:10 | 24.70 | 16.87 |
| October | 0.541816E+09 | 443.07 | 12-OCT-06:50 | 6.28 | 4.91 | 86758653.33 | 61.82 | 04-OCT-20:00 | 6.28 | 4.91 |
| November | 0.141300E+09 | 322.74 | 19-NOV-19:10 | 10.10 | 8.69 | 76087557.79 | 49.60 | 04-NOV-20:10 | 10.10 | 8.69 |
| December | 10031.67 | 13.55 | 30-DEC-13:00 | 8.90 | 7.75 | 77895344.66 | 42.51 | 11-DEC-06:49 | 8.90 | 7.75 |
| Annual Sum or Average | 0.613909E+10 | 0.112028E+10 | ||||||||
| Minimum of Months | 7364.17 | 6.87 | 6.28 | 4.91 | 70370572.99 | 42.51 | 6.28 | 4.91 | ||
| Maximum of Months | 0.137783E+10 | 1353.37 | 31.62 | 18.84 | 0.126711E+09 | 70.37 | 31.62 | 18.84 |
Report: ZoneCoolingSummaryMonthly
For: G N1 APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 15035838.76 | 196.28 | 11-JAN-20:00 | 12.80 | 10.11 | 77895344.66 | 42.51 | 15-JAN-06:49 | -3.1 | -4.0 |
| February | 88245054.48 | 346.32 | 28-FEB-20:00 | 9.40 | 7.97 | 70484032.37 | 45.74 | 27-FEB-21:10 | 9.40 | 7.97 |
| March | 0.252974E+09 | 373.77 | 30-MAR-19:50 | 8.40 | 4.98 | 78149906.70 | 46.35 | 18-MAR-20:49 | 8.40 | 4.98 |
| April | 0.463552E+09 | 402.98 | 29-APR-05:00 | 8.30 | 8.30 | 80652712.92 | 64.68 | 27-APR-20:10 | 8.30 | 8.30 |
| May | 0.783343E+09 | 521.32 | 11-MAY-03:00 | 4.40 | 3.92 | 0.100762E+09 | 70.33 | 07-MAY-21:19 | 4.40 | 3.92 |
| June | 0.806735E+09 | 858.01 | 28-JUN-18:00 | 25.60 | 16.63 | 0.115755E+09 | 70.36 | 21-JUN-23:00 | 25.60 | 16.63 |
| July | 0.113526E+10 | 1066.92 | 24-JUL-18:00 | 28.90 | 17.96 | 0.127833E+09 | 70.37 | 05-JUL-23:30 | 28.90 | 17.96 |
| August | 0.122957E+10 | 1044.43 | 10-AUG-18:50 | 30.03 | 18.64 | 0.128070E+09 | 70.36 | 21-AUG-23:49 | 14.62 | 11.71 |
| September | 0.845855E+09 | 755.18 | 14-SEP-17:10 | 24.45 | 16.70 | 0.118643E+09 | 70.36 | 01-SEP-23:40 | 24.45 | 16.70 |
| October | 0.748071E+09 | 477.47 | 13-OCT-05:00 | 5.60 | 4.51 | 91502723.35 | 64.85 | 04-OCT-21:10 | 5.60 | 4.51 |
| November | 0.340262E+09 | 383.66 | 08-NOV-23:10 | 8.22 | 7.34 | 77287806.15 | 53.32 | 06-NOV-22:10 | 8.22 | 7.34 |
| December | 43186903.59 | 190.71 | 29-DEC-19:00 | 9.40 | 7.98 | 77895344.66 | 42.51 | 28-DEC-22:40 | 9.40 | 7.98 |
| Annual Sum or Average | 0.675209E+10 | 0.114493E+10 | ||||||||
| Minimum of Months | 15035838.76 | 190.71 | 4.40 | 3.92 | 70484032.37 | 42.51 | -3.1 | -4.0 | ||
| Maximum of Months | 0.122957E+10 | 1066.92 | 30.03 | 18.64 | 0.128070E+09 | 70.37 | 28.90 | 17.96 |
Report: ZoneCoolingSummaryMonthly
For: G N2 APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 15059135.71 | 196.54 | 11-JAN-20:00 | 12.80 | 10.11 | 77895344.66 | 42.51 | 15-JAN-06:49 | -3.1 | -4.0 |
| February | 88060366.75 | 343.32 | 28-FEB-19:50 | 9.50 | 8.03 | 70481781.08 | 45.69 | 27-FEB-21:10 | 9.50 | 8.03 |
| March | 0.252730E+09 | 373.77 | 30-MAR-19:50 | 8.40 | 4.98 | 78143841.54 | 46.23 | 18-MAR-20:49 | 8.40 | 4.98 |
| April | 0.465963E+09 | 402.80 | 29-APR-05:00 | 8.30 | 8.30 | 80656008.53 | 64.69 | 27-APR-20:10 | 8.30 | 8.30 |
| May | 0.782542E+09 | 520.38 | 11-MAY-03:00 | 4.40 | 3.92 | 0.100611E+09 | 70.32 | 05-MAY-21:30 | 4.40 | 3.92 |
| June | 0.810519E+09 | 853.54 | 28-JUN-18:00 | 25.60 | 16.63 | 0.115882E+09 | 70.37 | 10-JUN-23:30 | 25.60 | 16.63 |
| July | 0.112851E+10 | 1063.37 | 24-JUL-18:00 | 28.90 | 17.96 | 0.127777E+09 | 70.36 | 01-JUL-01:19 | 28.90 | 17.96 |
| August | 0.123062E+10 | 1036.83 | 10-AUG-18:50 | 30.03 | 18.64 | 0.128055E+09 | 70.36 | 17-AUG-23:40 | 13.90 | 11.30 |
| September | 0.844106E+09 | 752.81 | 14-SEP-17:10 | 24.45 | 16.70 | 0.118517E+09 | 70.36 | 03-SEP-00:10 | 24.45 | 16.70 |
| October | 0.747857E+09 | 477.37 | 13-OCT-05:00 | 5.60 | 4.51 | 91401150.78 | 64.60 | 09-OCT-20:10 | 5.60 | 4.51 |
| November | 0.340173E+09 | 383.59 | 08-NOV-23:10 | 8.22 | 7.34 | 77283098.34 | 53.30 | 06-NOV-22:10 | 8.22 | 7.34 |
| December | 42940008.04 | 190.90 | 29-DEC-19:00 | 9.40 | 7.98 | 77895344.66 | 42.51 | 28-DEC-22:40 | 9.40 | 7.98 |
| Annual Sum or Average | 0.674907E+10 | 0.114460E+10 | ||||||||
| Minimum of Months | 15059135.71 | 190.90 | 4.40 | 3.92 | 70481781.08 | 42.51 | -3.1 | -4.0 | ||
| Maximum of Months | 0.123062E+10 | 1063.37 | 30.03 | 18.64 | 0.128055E+09 | 70.37 | 28.90 | 17.96 |
Report: ZoneCoolingSummaryMonthly
For: G S1 APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.168967E+09 | 547.50 | 07-JAN-14:10 | 2.88 | 1.87 | 78231723.95 | 44.73 | 11-JAN-20:10 | 12.52 | 10.15 |
| February | 0.381775E+09 | 560.27 | 09-FEB-18:00 | 2.80 | 1.24 | 70605178.41 | 58.74 | 27-FEB-18:10 | 17.02 | 11.99 |
| March | 0.706016E+09 | 544.29 | 02-MAR-02:70 | 3.03 | 2.83 | 79009960.22 | 68.26 | 18-MAR-16:30 | 20.00 | 10.02 |
| April | 0.791711E+09 | 742.02 | 27-APR-15:10 | 27.20 | 17.22 | 89175021.41 | 70.35 | 28-APR-17:10 | 16.52 | 12.24 |
| May | 0.990119E+09 | 1001.94 | 15-MAY-15:10 | 23.40 | 12.66 | 0.108822E+09 | 70.37 | 13-MAY-20:00 | 23.40 | 12.66 |
| June | 0.105087E+10 | 1095.72 | 28-JUN-15:10 | 26.10 | 15.67 | 0.115796E+09 | 70.38 | 08-JUN-21:00 | 26.10 | 15.67 |
| July | 0.157328E+10 | 1400.22 | 24-JUL-15:10 | 30.32 | 18.75 | 0.128864E+09 | 70.36 | 03-JUL-00:40 | 30.32 | 18.75 |
| August | 0.183101E+10 | 1616.35 | 10-AUG-15:10 | 30.37 | 18.88 | 0.123724E+09 | 70.36 | 05-AUG-06:40 | 30.37 | 18.88 |
| September | 0.152582E+10 | 1565.55 | 14-SEP-15:10 | 23.98 | 16.97 | 0.122295E+09 | 70.37 | 27-SEP-18:10 | 12.62 | 9.73 |
| October | 0.112909E+10 | 1350.20 | 04-OCT-15:10 | 21.60 | 11.48 | 0.108037E+09 | 70.36 | 12-OCT-20:00 | 8.90 | 7.75 |
| November | 0.635965E+09 | 604.47 | 11-NOV-23:00 | 1.10 | 0.63 | 80941143.92 | 70.31 | 04-NOV-18:40 | 1.10 | 0.63 |
| December | 0.349500E+09 | 611.54 | 06-DEC-17:10 | 1.10 | 0.97 | 78786629.19 | 53.51 | 03-DEC-16:10 | 1.10 | 0.97 |
| Annual Sum or Average | 0.111341E+11 | 0.118429E+10 | ||||||||
| Minimum of Months | 0.168967E+09 | 544.29 | 1.10 | 0.63 | 70605178.41 | 44.73 | 1.10 | 0.63 | ||
| Maximum of Months | 0.183101E+10 | 1616.35 | 30.37 | 18.88 | 0.128864E+09 | 70.38 | 30.37 | 18.88 |
Report: ZoneCoolingSummaryMonthly
For: G S2 APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.118367E+09 | 514.41 | 08-JAN-12:50 | 3.95 | 2.33 | 78217426.27 | 44.17 | 11-JAN-18:19 | 12.60 | 9.50 |
| February | 0.335637E+09 | 559.11 | 09-FEB-18:00 | 2.80 | 1.24 | 70495632.20 | 58.38 | 27-FEB-18:10 | 17.02 | 11.99 |
| March | 0.695233E+09 | 544.48 | 02-MAR-02:70 | 3.03 | 2.83 | 78973630.94 | 68.21 | 18-MAR-16:30 | 20.00 | 10.02 |
| April | 0.805183E+09 | 792.11 | 29-APR-15:10 | 21.83 | 15.11 | 89724612.69 | 70.35 | 28-APR-20:00 | 21.83 | 15.11 |
| May | 0.102257E+10 | 1054.76 | 15-MAY-15:10 | 23.40 | 12.66 | 0.110059E+09 | 70.37 | 03-MAY-21:00 | 23.40 | 12.66 |
| June | 0.112371E+10 | 1142.68 | 28-JUN-15:10 | 26.10 | 15.67 | 0.116547E+09 | 70.38 | 14-JUN-18:49 | 26.10 | 15.67 |
| July | 0.168831E+10 | 1476.40 | 24-JUL-15:10 | 30.32 | 18.75 | 0.129000E+09 | 70.36 | 12-JUL-04:40 | 30.32 | 18.75 |
| August | 0.198166E+10 | 1692.06 | 13-AUG-15:10 | 28.12 | 19.08 | 0.123837E+09 | 70.36 | 19-AUG-01:49 | 13.77 | 11.00 |
| September | 0.162172E+10 | 1623.73 | 14-SEP-15:10 | 23.98 | 16.97 | 0.122590E+09 | 70.35 | 08-SEP-03:20 | 23.98 | 16.97 |
| October | 0.115719E+10 | 1382.59 | 04-OCT-14:10 | 21.20 | 11.42 | 0.109194E+09 | 70.37 | 14-OCT-15:39 | 11.30 | 8.64 |
| November | 0.612556E+09 | 604.83 | 11-NOV-23:00 | 1.10 | 0.63 | 81388704.89 | 70.35 | 05-NOV-15:39 | 1.10 | 0.63 |
| December | 0.302364E+09 | 611.04 | 06-DEC-17:10 | 1.10 | 0.97 | 78676449.89 | 52.54 | 03-DEC-16:10 | 1.10 | 0.97 |
| Annual Sum or Average | 0.114645E+11 | 0.118870E+10 | ||||||||
| Minimum of Months | 0.118367E+09 | 514.41 | 1.10 | 0.63 | 70495632.20 | 44.17 | 1.10 | 0.63 | ||
| Maximum of Months | 0.198166E+10 | 1692.06 | 30.32 | 19.08 | 0.129000E+09 | 70.38 | 30.32 | 18.75 |
Report: ZoneCoolingSummaryMonthly
For: M SW APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.190726E+09 | 625.37 | 07-JAN-12:50 | 0.40 | 0.02 | 78371100.65 | 51.84 | 08-JAN-16:10 | 4.03 | 1.75 |
| February | 0.491444E+09 | 872.69 | 27-FEB-15:30 | 19.70 | 12.30 | 73123410.59 | 70.21 | 27-FEB-19:00 | 13.90 | 10.81 |
| March | 0.980216E+09 | 1263.50 | 02-MAR-16:10 | 13.22 | 8.39 | 87892140.72 | 70.31 | 18-MAR-20:00 | 13.90 | 7.23 |
| April | 0.126060E+10 | 2360.47 | 27-APR-16:03 | 27.02 | 16.89 | 0.104228E+09 | 70.31 | 27-APR-03:09 | 27.02 | 16.89 |
| May | 0.170276E+10 | 2366.93 | 15-MAY-16:05 | 23.98 | 12.88 | 0.118298E+09 | 70.31 | 08-MAY-03:30 | 23.98 | 12.88 |
| June | 0.181977E+10 | 2260.88 | 28-JUN-16:30 | 26.40 | 16.52 | 0.118443E+09 | 70.31 | 13-JUN-18:00 | 26.40 | 16.52 |
| July | 0.247894E+10 | 2558.13 | 23-JUL-16:20 | 27.43 | 15.97 | 0.129081E+09 | 70.30 | 06-JUL-03:30 | 27.43 | 15.97 |
| August | 0.255884E+10 | 2835.58 | 10-AUG-16:17 | 31.40 | 18.73 | 0.123641E+09 | 70.31 | 22-AUG-02:39 | 12.87 | 11.04 |
| September | 0.203817E+10 | 2593.64 | 11-SEP-16:04 | 23.12 | 16.02 | 0.122189E+09 | 70.31 | 25-SEP-19:49 | 13.30 | 13.30 |
| October | 0.125671E+10 | 2314.96 | 04-OCT-15:10 | 21.60 | 11.48 | 0.106962E+09 | 70.32 | 10-OCT-18:30 | 11.40 | 10.15 |
| November | 0.532508E+09 | 1314.93 | 04-NOV-15:20 | 20.73 | 15.94 | 81297942.32 | 70.31 | 05-NOV-19:19 | 12.80 | 11.29 |
| December | 0.317632E+09 | 641.32 | 06-DEC-21:00 | 0.20 | 0.14 | 79427544.21 | 59.89 | 03-DEC-16:10 | 0.20 | 0.14 |
| Annual Sum or Average | 0.156283E+11 | 0.122295E+10 | ||||||||
| Minimum of Months | 0.190726E+09 | 625.37 | 0.20 | 0.02 | 73123410.59 | 51.84 | 0.20 | 0.14 | ||
| Maximum of Months | 0.255884E+10 | 2835.58 | 31.40 | 18.73 | 0.129081E+09 | 70.32 | 27.43 | 16.89 |
Report: ZoneCoolingSummaryMonthly
For: M NW APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 18732588.63 | 259.56 | 11-JAN-19:00 | 12.20 | 9.27 | 77897163.93 | 42.51 | 15-JAN-06:49 | -3.1 | -4.0 |
| February | 0.170998E+09 | 457.55 | 28-FEB-24:00 | 6.10 | 4.84 | 71408309.16 | 53.98 | 27-FEB-21:10 | 6.10 | 4.84 |
| March | 0.561815E+09 | 518.50 | 01-MAR-23:00 | 3.90 | 2.96 | 81424794.43 | 56.43 | 18-MAR-20:49 | 14.18 | 7.30 |
| April | 0.887418E+09 | 1503.86 | 27-APR-17:20 | 26.10 | 16.52 | 94134370.29 | 70.31 | 28-APR-22:49 | 11.78 | 10.52 |
| May | 0.130853E+10 | 1825.73 | 15-MAY-16:25 | 24.15 | 12.93 | 0.119075E+09 | 70.32 | 15-MAY-02:09 | 24.15 | 12.93 |
| June | 0.150405E+10 | 1980.12 | 22-JUN-18:30 | 23.60 | 16.07 | 0.122109E+09 | 70.32 | 26-JUN-01:49 | 13.30 | 10.57 |
| July | 0.200774E+10 | 2150.56 | 31-JUL-18:00 | 26.70 | 18.39 | 0.128456E+09 | 70.31 | 10-JUL-03:49 | 26.70 | 18.39 |
| August | 0.193123E+10 | 2277.30 | 10-AUG-17:25 | 31.25 | 19.12 | 0.128285E+09 | 70.31 | 21-AUG-01:19 | 13.80 | 12.12 |
| September | 0.125468E+10 | 1671.24 | 12-SEP-16:25 | 23.85 | 16.75 | 0.121248E+09 | 70.31 | 30-SEP-21:10 | 13.35 | 11.53 |
| October | 0.769158E+09 | 895.23 | 04-OCT-16:30 | 20.85 | 11.39 | 96224581.35 | 70.27 | 04-OCT-22:10 | 15.73 | 10.00 |
| November | 0.268861E+09 | 370.10 | 08-NOV-20:00 | 8.90 | 7.50 | 78109204.45 | 59.47 | 04-NOV-21:10 | 8.90 | 7.50 |
| December | 43868864.95 | 321.79 | 10-DEC-15:40 | 10.20 | 8.63 | 77896619.54 | 42.51 | 11-DEC-06:49 | 2.80 | 2.57 |
| Annual Sum or Average | 0.107271E+11 | 0.119627E+10 | ||||||||
| Minimum of Months | 18732588.63 | 259.56 | 3.90 | 2.96 | 71408309.16 | 42.51 | -3.1 | -4.0 | ||
| Maximum of Months | 0.200774E+10 | 2277.30 | 31.25 | 19.12 | 0.128456E+09 | 70.32 | 26.70 | 18.39 |
Report: ZoneCoolingSummaryMonthly
For: M SE APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.189025E+09 | 631.65 | 07-JAN-12:40 | 0.20 | -0.1 | 78324811.75 | 47.92 | 08-JAN-16:10 | 4.03 | 1.75 |
| February | 0.490036E+09 | 636.06 | 19-FEB-12:00 | 0.00 | -2.3 | 72820640.95 | 68.95 | 27-FEB-19:00 | 13.90 | 10.81 |
| March | 0.982974E+09 | 1090.30 | 02-MAR-13:50 | 13.12 | 8.00 | 87550237.03 | 70.30 | 14-MAR-17:49 | 15.78 | 9.99 |
| April | 0.127144E+10 | 2157.36 | 27-APR-13:30 | 26.10 | 16.55 | 0.105156E+09 | 70.31 | 27-APR-02:20 | 26.10 | 16.55 |
| May | 0.164789E+10 | 2038.79 | 15-MAY-13:30 | 23.05 | 13.66 | 0.117746E+09 | 70.31 | 08-MAY-01:30 | 23.05 | 13.66 |
| June | 0.189576E+10 | 1913.82 | 28-JUN-13:00 | 24.40 | 15.72 | 0.118390E+09 | 70.32 | 05-JUN-01:49 | 24.40 | 15.72 |
| July | 0.235504E+10 | 2314.40 | 24-JUL-13:30 | 28.85 | 18.23 | 0.128964E+09 | 70.31 | 10-JUL-04:10 | 28.85 | 18.23 |
| August | 0.256085E+10 | 2463.73 | 10-AUG-13:30 | 28.30 | 18.98 | 0.123570E+09 | 70.31 | 21-AUG-02:09 | 13.92 | 12.28 |
| September | 0.198136E+10 | 2314.03 | 23-SEP-13:30 | 22.75 | 17.56 | 0.121826E+09 | 70.31 | 04-SEP-02:49 | 22.75 | 17.56 |
| October | 0.126024E+10 | 2036.14 | 04-OCT-13:30 | 20.85 | 11.31 | 0.106842E+09 | 70.31 | 05-OCT-22:10 | 10.10 | 9.49 |
| November | 0.528699E+09 | 1087.93 | 04-NOV-14:00 | 21.10 | 15.94 | 81267645.99 | 70.27 | 04-NOV-15:20 | 20.73 | 15.94 |
| December | 0.314135E+09 | 638.78 | 06-DEC-21:00 | 0.20 | 0.14 | 79334892.60 | 57.50 | 03-DEC-16:10 | 0.20 | 0.14 |
| Annual Sum or Average | 0.154774E+11 | 0.122179E+10 | ||||||||
| Minimum of Months | 0.189025E+09 | 631.65 | 0.00 | -2.3 | 72820640.95 | 47.92 | 0.20 | 0.14 | ||
| Maximum of Months | 0.256085E+10 | 2463.73 | 28.85 | 18.98 | 0.128964E+09 | 70.32 | 28.85 | 18.23 |
Report: ZoneCoolingSummaryMonthly
For: M NE APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 18893853.32 | 259.67 | 11-JAN-19:00 | 12.20 | 9.27 | 77897366.29 | 42.51 | 15-JAN-06:49 | -3.1 | -4.0 |
| February | 0.159270E+09 | 453.68 | 28-FEB-24:00 | 6.10 | 4.84 | 71287391.41 | 52.57 | 27-FEB-21:10 | 6.10 | 4.84 |
| March | 0.575816E+09 | 524.45 | 01-MAR-08:45 | 3.62 | 0.41 | 80852091.14 | 54.23 | 14-MAR-20:10 | 14.13 | 9.38 |
| April | 0.896201E+09 | 1105.34 | 27-APR-16:20 | 26.83 | 16.88 | 94817467.18 | 70.31 | 28-APR-00:40 | 14.60 | 11.93 |
| May | 0.124777E+10 | 1283.18 | 15-MAY-16:20 | 24.07 | 12.90 | 0.118546E+09 | 70.31 | 07-MAY-04:40 | 24.07 | 12.90 |
| June | 0.157524E+10 | 1479.52 | 28-JUN-18:00 | 25.60 | 16.63 | 0.122113E+09 | 70.31 | 06-JUN-20:10 | 25.60 | 16.63 |
| July | 0.188454E+10 | 1735.68 | 24-JUL-18:00 | 28.90 | 17.96 | 0.128290E+09 | 70.31 | 21-JUL-03:49 | 28.90 | 17.96 |
| August | 0.193217E+10 | 1614.67 | 10-AUG-10:10 | 23.38 | 17.24 | 0.128200E+09 | 70.31 | 17-AUG-23:00 | 13.80 | 11.14 |
| September | 0.120825E+10 | 1188.07 | 14-SEP-16:30 | 24.70 | 16.87 | 0.120523E+09 | 70.30 | 03-SEP-01:39 | 24.70 | 16.87 |
| October | 0.768700E+09 | 497.92 | 07-OCT-17:20 | 15.37 | 11.61 | 95836332.73 | 70.27 | 06-OCT-20:10 | 15.37 | 11.61 |
| November | 0.265464E+09 | 368.58 | 08-NOV-20:00 | 8.90 | 7.50 | 78028324.28 | 58.21 | 04-NOV-21:10 | 8.90 | 7.50 |
| December | 37516928.66 | 246.48 | 30-DEC-13:00 | 8.90 | 7.75 | 77895344.66 | 42.51 | 11-DEC-06:49 | 8.90 | 7.75 |
| Annual Sum or Average | 0.105698E+11 | 0.119429E+10 | ||||||||
| Minimum of Months | 18893853.32 | 246.48 | 3.62 | 0.41 | 71287391.41 | 42.51 | -3.1 | -4.0 | ||
| Maximum of Months | 0.193217E+10 | 1735.68 | 28.90 | 17.96 | 0.128290E+09 | 70.31 | 28.90 | 17.96 |
Report: ZoneCoolingSummaryMonthly
For: M N1 APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.276104E+09 | 369.81 | 11-JAN-23:40 | 8.67 | 7.91 | 77968512.17 | 45.86 | 11-JAN-21:10 | 8.67 | 7.91 |
| February | 0.400921E+09 | 476.50 | 28-FEB-24:00 | 6.10 | 4.84 | 72532110.53 | 56.53 | 27-FEB-21:10 | 6.10 | 4.84 |
| March | 0.889050E+09 | 629.66 | 01-MAR-06:10 | -0.1 | -1.5 | 84197483.15 | 57.40 | 10-MAR-21:10 | 11.70 | 11.07 |
| April | 0.958378E+09 | 806.12 | 27-APR-18:00 | 26.10 | 15.89 | 99314955.72 | 70.31 | 28-APR-01:10 | 14.03 | 11.94 |
| May | 0.121650E+10 | 1008.07 | 15-MAY-17:10 | 23.85 | 12.97 | 0.123281E+09 | 70.31 | 16-MAY-02:49 | 11.70 | 10.20 |
| June | 0.137946E+10 | 1209.23 | 28-JUN-18:40 | 24.80 | 16.02 | 0.123712E+09 | 70.31 | 15-JUN-23:40 | 24.80 | 16.02 |
| July | 0.163996E+10 | 1340.04 | 24-JUL-18:00 | 28.90 | 17.96 | 0.128738E+09 | 70.31 | 05-JUL-03:09 | 28.90 | 17.96 |
| August | 0.163605E+10 | 1268.10 | 10-AUG-18:50 | 30.03 | 18.64 | 0.128702E+09 | 70.31 | 06-AUG-02:39 | 30.03 | 18.64 |
| September | 0.116888E+10 | 965.91 | 14-SEP-17:10 | 24.45 | 16.70 | 0.123377E+09 | 70.31 | 05-SEP-02:09 | 24.45 | 16.70 |
| October | 0.904473E+09 | 600.17 | 01-OCT-18:20 | 15.40 | 13.24 | 0.104536E+09 | 70.32 | 05-OCT-20:00 | 11.10 | 9.86 |
| November | 0.592186E+09 | 472.11 | 09-NOV-23:10 | 5.40 | 4.43 | 80952868.89 | 62.40 | 06-NOV-22:10 | 5.40 | 4.43 |
| December | 0.351992E+09 | 406.03 | 10-DEC-18:25 | 7.50 | 6.96 | 77911659.22 | 43.15 | 29-DEC-21:10 | 9.32 | 7.69 |
| Annual Sum or Average | 0.114140E+11 | 0.122522E+10 | ||||||||
| Minimum of Months | 0.276104E+09 | 369.81 | -0.1 | -1.5 | 72532110.53 | 43.15 | 5.40 | 4.43 | ||
| Maximum of Months | 0.163996E+10 | 1340.04 | 30.03 | 18.64 | 0.128738E+09 | 70.32 | 30.03 | 18.64 |
Report: ZoneCoolingSummaryMonthly
For: M N2 APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.276054E+09 | 369.81 | 11-JAN-23:40 | 8.67 | 7.91 | 77968894.13 | 45.88 | 11-JAN-21:10 | 8.67 | 7.91 |
| February | 0.400809E+09 | 476.01 | 28-FEB-24:00 | 6.10 | 4.84 | 72522981.78 | 56.43 | 27-FEB-21:10 | 6.10 | 4.84 |
| March | 0.889008E+09 | 627.23 | 01-MAR-07:16 | 0.33 | -1.4 | 84143234.21 | 57.43 | 10-MAR-21:10 | 11.70 | 11.07 |
| April | 0.960382E+09 | 805.43 | 27-APR-18:00 | 26.10 | 15.89 | 99541935.38 | 70.28 | 30-APR-03:09 | 12.02 | 11.72 |
| May | 0.121542E+10 | 1001.90 | 15-MAY-17:10 | 23.85 | 12.97 | 0.123236E+09 | 70.32 | 21-MAY-21:00 | 11.70 | 8.53 |
| June | 0.138345E+10 | 1201.25 | 28-JUN-18:40 | 24.80 | 16.02 | 0.123710E+09 | 70.31 | 04-JUN-04:40 | 24.80 | 16.02 |
| July | 0.163508E+10 | 1335.82 | 24-JUL-18:00 | 28.90 | 17.96 | 0.128735E+09 | 70.30 | 18-JUL-03:39 | 28.90 | 17.96 |
| August | 0.163668E+10 | 1257.24 | 10-AUG-18:50 | 30.03 | 18.64 | 0.128698E+09 | 70.31 | 19-AUG-04:40 | 12.50 | 10.66 |
| September | 0.116595E+10 | 960.91 | 14-SEP-17:10 | 24.45 | 16.70 | 0.123338E+09 | 70.31 | 07-SEP-03:30 | 24.45 | 16.70 |
| October | 0.904537E+09 | 576.25 | 09-OCT-18:30 | 15.25 | 11.79 | 0.104528E+09 | 70.32 | 08-OCT-22:10 | 15.25 | 11.79 |
| November | 0.591977E+09 | 472.04 | 09-NOV-23:10 | 5.40 | 4.43 | 80947304.23 | 62.34 | 06-NOV-22:10 | 5.40 | 4.43 |
| December | 0.351613E+09 | 405.59 | 05-DEC-21:00 | 5.60 | 1.73 | 77911263.82 | 43.15 | 29-DEC-21:10 | 9.32 | 7.69 |
| Annual Sum or Average | 0.114110E+11 | 0.122528E+10 | ||||||||
| Minimum of Months | 0.276054E+09 | 369.81 | 0.33 | -1.4 | 72522981.78 | 43.15 | 5.40 | 4.43 | ||
| Maximum of Months | 0.163668E+10 | 1335.82 | 30.03 | 18.64 | 0.128735E+09 | 70.32 | 28.90 | 17.96 |
Report: ZoneCoolingSummaryMonthly
For: M S1 APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.658302E+09 | 679.93 | 07-JAN-11:20 | -1.3 | -1.5 | 79064143.87 | 55.27 | 08-JAN-16:10 | 4.03 | 1.75 |
| February | 0.848637E+09 | 780.53 | 27-FEB-15:10 | 19.90 | 12.22 | 77078986.38 | 70.30 | 28-FEB-18:10 | 10.92 | 8.68 |
| March | 0.121177E+10 | 1249.82 | 02-MAR-14:00 | 13.30 | 8.13 | 97057371.15 | 70.31 | 02-MAR-21:49 | 7.62 | 6.24 |
| April | 0.132767E+10 | 1793.35 | 27-APR-14:10 | 26.28 | 16.91 | 0.111943E+09 | 70.31 | 14-APR-20:40 | 26.28 | 16.91 |
| May | 0.163524E+10 | 1654.93 | 15-MAY-14:10 | 23.30 | 13.36 | 0.122074E+09 | 70.31 | 02-MAY-23:49 | 23.30 | 13.36 |
| June | 0.170583E+10 | 1496.13 | 28-JUN-14:10 | 25.18 | 15.64 | 0.119758E+09 | 70.31 | 05-JUN-04:10 | 25.18 | 15.64 |
| July | 0.211501E+10 | 1770.29 | 24-JUL-13:30 | 28.85 | 18.23 | 0.129267E+09 | 70.31 | 04-JUL-03:00 | 28.85 | 18.23 |
| August | 0.227039E+10 | 1987.40 | 10-AUG-14:10 | 29.53 | 19.11 | 0.123945E+09 | 70.30 | 12-AUG-17:00 | 23.30 | 16.16 |
| September | 0.198799E+10 | 2082.93 | 23-SEP-13:30 | 22.75 | 17.56 | 0.123471E+09 | 70.31 | 18-SEP-02:09 | 22.75 | 17.56 |
| October | 0.141593E+10 | 1921.72 | 04-OCT-14:10 | 21.20 | 11.42 | 0.116383E+09 | 70.32 | 13-OCT-17:10 | 12.12 | 8.80 |
| November | 0.910630E+09 | 1258.60 | 04-NOV-14:00 | 21.10 | 15.94 | 86561945.29 | 70.30 | 04-NOV-23:49 | 13.30 | 12.93 |
| December | 0.742119E+09 | 670.41 | 06-DEC-21:00 | 0.20 | 0.14 | 81814687.43 | 64.67 | 03-DEC-16:10 | 0.20 | 0.14 |
| Annual Sum or Average | 0.168295E+11 | 0.126842E+10 | ||||||||
| Minimum of Months | 0.658302E+09 | 670.41 | -1.3 | -1.5 | 77078986.38 | 55.27 | 0.20 | 0.14 | ||
| Maximum of Months | 0.227039E+10 | 2082.93 | 29.53 | 19.11 | 0.129267E+09 | 70.32 | 28.85 | 18.23 |
Report: ZoneCoolingSummaryMonthly
For: M S2 APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.657652E+09 | 679.97 | 07-JAN-11:20 | -1.3 | -1.5 | 79059099.06 | 55.13 | 08-JAN-16:10 | 4.03 | 1.75 |
| February | 0.848424E+09 | 777.41 | 27-FEB-15:10 | 19.90 | 12.22 | 77053742.52 | 70.28 | 27-FEB-18:30 | 16.65 | 12.04 |
| March | 0.121190E+10 | 1259.15 | 02-MAR-14:00 | 13.30 | 8.13 | 97077761.81 | 70.31 | 02-MAR-21:49 | 7.62 | 6.24 |
| April | 0.133393E+10 | 1799.18 | 27-APR-14:10 | 26.28 | 16.91 | 0.112093E+09 | 70.31 | 13-APR-18:00 | 26.28 | 16.91 |
| May | 0.163349E+10 | 1659.66 | 15-MAY-14:10 | 23.30 | 13.36 | 0.122026E+09 | 70.31 | 23-MAY-19:00 | 8.30 | 7.98 |
| June | 0.170951E+10 | 1501.31 | 28-JUN-14:10 | 25.18 | 15.64 | 0.119751E+09 | 70.31 | 24-JUN-04:10 | 25.18 | 15.64 |
| July | 0.211025E+10 | 1778.17 | 24-JUL-13:30 | 28.85 | 18.23 | 0.129267E+09 | 70.32 | 04-JUL-02:49 | 28.85 | 18.23 |
| August | 0.227085E+10 | 1993.51 | 10-AUG-14:10 | 29.53 | 19.11 | 0.123943E+09 | 70.31 | 05-AUG-02:09 | 29.53 | 19.11 |
| September | 0.198487E+10 | 2086.93 | 23-SEP-13:30 | 22.75 | 17.56 | 0.123456E+09 | 70.31 | 30-SEP-01:30 | 11.95 | 11.46 |
| October | 0.141680E+10 | 1923.34 | 04-OCT-14:10 | 21.20 | 11.42 | 0.116392E+09 | 70.31 | 05-OCT-04:10 | 9.22 | 5.88 |
| November | 0.910680E+09 | 1264.47 | 04-NOV-14:00 | 21.10 | 15.94 | 86557794.55 | 70.31 | 04-NOV-23:49 | 13.30 | 12.93 |
| December | 0.741673E+09 | 670.27 | 06-DEC-21:00 | 0.20 | 0.14 | 81797943.12 | 64.56 | 03-DEC-16:10 | 0.20 | 0.14 |
| Annual Sum or Average | 0.168300E+11 | 0.126847E+10 | ||||||||
| Minimum of Months | 0.657652E+09 | 670.27 | -1.3 | -1.5 | 77053742.52 | 55.13 | 0.20 | 0.14 | ||
| Maximum of Months | 0.227085E+10 | 2086.93 | 29.53 | 19.11 | 0.129267E+09 | 70.32 | 29.53 | 19.11 |
Report: ZoneCoolingSummaryMonthly
For: T SW APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 64981501.80 | 595.98 | 07-JAN-13:20 | 1.33 | 0.73 | 78292766.67 | 53.29 | 08-JAN-16:10 | 4.03 | 1.75 |
| February | 0.248829E+09 | 1794.61 | 27-FEB-15:30 | 19.70 | 12.30 | 71551423.29 | 70.34 | 27-FEB-20:19 | 13.33 | 10.57 |
| March | 0.500336E+09 | 2036.09 | 14-MAR-16:05 | 17.12 | 10.96 | 81150926.44 | 70.30 | 18-MAR-19:10 | 16.52 | 8.06 |
| April | 0.976710E+09 | 3172.87 | 27-APR-15:10 | 27.20 | 17.22 | 90675428.28 | 70.36 | 30-APR-18:10 | 12.70 | 11.86 |
| May | 0.144526E+10 | 3079.35 | 15-MAY-16:05 | 23.98 | 12.88 | 0.100203E+09 | 70.34 | 24-MAY-19:19 | 12.03 | 9.78 |
| June | 0.165784E+10 | 3045.63 | 28-JUN-16:14 | 26.30 | 16.44 | 0.106104E+09 | 70.35 | 02-JUN-21:49 | 26.30 | 16.44 |
| July | 0.244377E+10 | 3456.42 | 31-JUL-16:15 | 28.70 | 19.03 | 0.121085E+09 | 70.37 | 08-JUL-00:40 | 28.70 | 19.03 |
| August | 0.247487E+10 | 3871.00 | 10-AUG-16:03 | 31.30 | 18.74 | 0.116685E+09 | 70.36 | 18-AUG-21:00 | 15.80 | 12.29 |
| September | 0.175899E+10 | 3302.77 | 14-SEP-15:20 | 24.07 | 16.99 | 0.106900E+09 | 70.34 | 16-SEP-17:00 | 12.80 | 11.78 |
| October | 0.704175E+09 | 2730.31 | 04-OCT-15:10 | 21.60 | 11.48 | 89816637.79 | 70.37 | 08-OCT-20:40 | 13.73 | 10.97 |
| November | 0.213410E+09 | 2249.01 | 04-NOV-15:20 | 20.73 | 15.94 | 77789868.26 | 70.33 | 04-NOV-20:10 | 16.42 | 13.92 |
| December | 0.127961E+09 | 668.25 | 05-DEC-14:30 | 10.30 | 6.71 | 78922912.77 | 64.18 | 03-DEC-16:10 | 10.30 | 6.71 |
| Annual Sum or Average | 0.126171E+11 | 0.111918E+10 | ||||||||
| Minimum of Months | 64981501.80 | 595.98 | 1.33 | 0.73 | 71551423.29 | 53.29 | 4.03 | 1.75 | ||
| Maximum of Months | 0.247487E+10 | 3871.00 | 31.30 | 19.03 | 0.121085E+09 | 70.37 | 28.70 | 19.03 |
Report: ZoneCoolingSummaryMonthly
For: T NW APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 171561.51 | 31.77 | 11-JAN-16:10 | 14.03 | 10.30 | 77895344.63 | 42.51 | 10-JAN-22:40 | 14.03 | 10.30 |
| February | 56868888.48 | 351.20 | 28-FEB-20:00 | 9.40 | 7.97 | 70877048.33 | 55.36 | 27-FEB-18:10 | 9.40 | 7.97 |
| March | 0.199059E+09 | 421.47 | 01-MAR-19:10 | 7.02 | 2.84 | 80223372.52 | 61.18 | 18-MAR-17:49 | 18.48 | 9.34 |
| April | 0.559921E+09 | 2216.97 | 27-APR-16:35 | 26.47 | 16.86 | 87314714.23 | 70.36 | 29-APR-22:10 | 14.82 | 11.92 |
| May | 0.105235E+10 | 2420.01 | 15-MAY-16:25 | 24.15 | 12.93 | 0.101042E+09 | 70.34 | 07-MAY-22:30 | 24.15 | 12.93 |
| June | 0.134148E+10 | 2635.03 | 28-JUN-16:35 | 26.50 | 16.59 | 0.109059E+09 | 70.35 | 29-JUN-21:49 | 16.10 | 13.41 |
| July | 0.194652E+10 | 2902.86 | 31-JUL-17:17 | 27.77 | 18.62 | 0.120408E+09 | 70.36 | 21-JUL-23:40 | 27.77 | 18.62 |
| August | 0.183125E+10 | 3119.01 | 10-AUG-17:17 | 31.43 | 18.98 | 0.120632E+09 | 70.36 | 11-AUG-23:00 | 16.60 | 14.04 |
| September | 0.100372E+10 | 2107.40 | 12-SEP-16:25 | 23.85 | 16.75 | 0.103416E+09 | 70.33 | 06-SEP-20:10 | 23.85 | 16.75 |
| October | 0.279780E+09 | 993.93 | 04-OCT-16:30 | 20.85 | 11.39 | 83505685.81 | 65.39 | 04-OCT-20:00 | 13.90 | 9.05 |
| November | 68404549.62 | 430.99 | 04-NOV-16:03 | 19.82 | 15.68 | 76271933.04 | 61.14 | 04-NOV-17:10 | 18.25 | 14.42 |
| December | 3427624.83 | 264.08 | 10-DEC-15:00 | 10.60 | 8.77 | 77895344.66 | 42.51 | 11-DEC-06:49 | 2.80 | 2.57 |
| Annual Sum or Average | 0.834295E+10 | 0.110854E+10 | ||||||||
| Minimum of Months | 171561.51 | 31.77 | 7.02 | 2.84 | 70877048.33 | 42.51 | 2.80 | 2.57 | ||
| Maximum of Months | 0.194652E+10 | 3119.01 | 31.43 | 18.98 | 0.120632E+09 | 70.36 | 27.77 | 18.62 |
Report: ZoneCoolingSummaryMonthly
For: T SE APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 59979617.48 | 596.16 | 07-JAN-13:20 | 1.33 | 0.73 | 78251871.04 | 46.74 | 08-JAN-16:10 | 4.03 | 1.75 |
| February | 0.242520E+09 | 1344.89 | 27-FEB-15:00 | 20.00 | 12.17 | 71255448.12 | 70.32 | 27-FEB-19:00 | 13.90 | 10.81 |
| March | 0.497312E+09 | 1912.27 | 14-MAR-13:40 | 15.20 | 10.17 | 80573414.50 | 70.29 | 14-MAR-20:19 | 13.87 | 9.27 |
| April | 0.979524E+09 | 2925.50 | 27-APR-13:40 | 26.10 | 16.65 | 90588278.03 | 70.35 | 29-APR-22:49 | 14.08 | 12.02 |
| May | 0.137381E+10 | 2712.12 | 15-MAY-13:50 | 23.22 | 13.56 | 99698557.86 | 70.35 | 05-MAY-00:20 | 23.22 | 13.56 |
| June | 0.171632E+10 | 2635.57 | 28-JUN-13:20 | 24.60 | 15.70 | 0.106272E+09 | 70.35 | 03-JUN-22:30 | 24.60 | 15.70 |
| July | 0.230862E+10 | 3225.89 | 24-JUL-13:30 | 28.85 | 18.23 | 0.120731E+09 | 70.36 | 08-JUL-00:30 | 28.85 | 18.23 |
| August | 0.245843E+10 | 3388.44 | 10-AUG-13:30 | 28.30 | 18.98 | 0.116867E+09 | 70.35 | 12-AUG-00:20 | 16.53 | 13.97 |
| September | 0.170090E+10 | 2969.55 | 14-SEP-13:50 | 23.72 | 17.23 | 0.106081E+09 | 70.35 | 03-SEP-19:00 | 23.72 | 17.23 |
| October | 0.702084E+09 | 2388.60 | 04-OCT-13:40 | 20.93 | 11.34 | 89557301.46 | 70.36 | 05-OCT-18:10 | 13.40 | 11.08 |
| November | 0.211576E+09 | 1971.04 | 04-NOV-14:00 | 21.10 | 15.94 | 77746625.70 | 70.27 | 04-NOV-15:00 | 20.00 | 15.91 |
| December | 0.124420E+09 | 560.59 | 06-DEC-16:20 | 2.57 | 2.27 | 78852354.78 | 60.03 | 03-DEC-16:10 | 2.57 | 2.27 |
| Annual Sum or Average | 0.123755E+11 | 0.111647E+10 | ||||||||
| Minimum of Months | 59979617.48 | 560.59 | 1.33 | 0.73 | 71255448.12 | 46.74 | 2.57 | 1.75 | ||
| Maximum of Months | 0.245843E+10 | 3388.44 | 28.85 | 18.98 | 0.120731E+09 | 70.36 | 28.85 | 18.23 |
Report: ZoneCoolingSummaryMonthly
For: T NE APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 44097.23 | 9.90 | 11-JAN-20:00 | 12.80 | 10.11 | 77895344.63 | 42.51 | 10-JAN-22:40 | 12.80 | 10.11 |
| February | 52471358.66 | 344.18 | 28-FEB-19:50 | 9.50 | 8.03 | 70740271.59 | 51.44 | 27-FEB-21:10 | 9.50 | 8.03 |
| March | 0.205733E+09 | 385.57 | 25-MAR-10:10 | 8.07 | 1.18 | 79413013.05 | 56.11 | 18-MAR-17:10 | 8.07 | 1.18 |
| April | 0.555959E+09 | 1616.36 | 27-APR-16:07 | 27.02 | 16.89 | 87078975.46 | 70.37 | 01-APR-22:40 | 27.02 | 16.89 |
| May | 0.968586E+09 | 1654.63 | 15-MAY-16:03 | 23.98 | 12.88 | 0.100573E+09 | 70.35 | 03-MAY-20:49 | 23.98 | 12.88 |
| June | 0.138593E+10 | 1889.53 | 28-JUN-16:05 | 26.20 | 16.37 | 0.109422E+09 | 70.35 | 11-JUN-23:10 | 26.20 | 16.37 |
| July | 0.181240E+10 | 2295.13 | 24-JUL-16:03 | 28.80 | 18.46 | 0.119902E+09 | 70.36 | 06-JUL-22:19 | 28.80 | 18.46 |
| August | 0.180880E+10 | 2169.12 | 08-AUG-16:15 | 29.93 | 18.24 | 0.120722E+09 | 70.36 | 03-AUG-20:49 | 29.93 | 18.24 |
| September | 0.937752E+09 | 1443.89 | 14-SEP-16:15 | 24.60 | 16.93 | 0.102307E+09 | 70.31 | 10-SEP-22:30 | 24.60 | 16.93 |
| October | 0.288719E+09 | 421.94 | 04-OCT-16:15 | 20.93 | 11.39 | 82659295.72 | 63.05 | 04-OCT-20:00 | 13.90 | 9.05 |
| November | 65594442.45 | 321.73 | 05-NOV-20:00 | 10.60 | 9.38 | 76163601.26 | 59.05 | 04-NOV-17:10 | 10.60 | 9.38 |
| December | 168821.84 | 31.33 | 10-DEC-15:00 | 10.60 | 8.77 | 77895344.66 | 42.51 | 11-DEC-06:49 | 2.80 | 2.57 |
| Annual Sum or Average | 0.808215E+10 | 0.110477E+10 | ||||||||
| Minimum of Months | 44097.23 | 9.90 | 8.07 | 1.18 | 70740271.59 | 42.51 | 2.80 | 1.18 | ||
| Maximum of Months | 0.181240E+10 | 2295.13 | 29.93 | 18.46 | 0.120722E+09 | 70.37 | 29.93 | 18.46 |
Report: ZoneCoolingSummaryMonthly
For: T N1 APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 6183811.51 | 208.97 | 11-JAN-20:00 | 12.80 | 10.11 | 77895344.65 | 42.51 | 15-JAN-06:49 | -3.1 | -4.0 |
| February | 90116891.38 | 386.68 | 28-FEB-22:03 | 8.12 | 7.00 | 71052714.22 | 55.15 | 27-FEB-21:10 | 8.12 | 7.00 |
| March | 0.294674E+09 | 417.51 | 19-MAR-20:00 | 7.20 | 5.33 | 80080001.56 | 57.64 | 18-MAR-20:40 | 7.20 | 5.33 |
| April | 0.586795E+09 | 1253.37 | 27-APR-16:27 | 26.65 | 16.87 | 88451962.85 | 70.33 | 01-APR-23:10 | 26.65 | 16.87 |
| May | 0.953566E+09 | 1346.22 | 15-MAY-16:15 | 24.07 | 12.90 | 0.104221E+09 | 70.34 | 15-MAY-22:10 | 12.70 | 11.06 |
| June | 0.117051E+10 | 1590.89 | 28-JUN-17:40 | 25.97 | 16.68 | 0.113400E+09 | 70.36 | 11-JUN-00:30 | 25.97 | 16.68 |
| July | 0.152733E+10 | 1843.07 | 24-JUL-18:00 | 28.90 | 17.96 | 0.123575E+09 | 70.37 | 08-JUL-00:49 | 28.90 | 17.96 |
| August | 0.148525E+10 | 1759.47 | 08-AUG-16:30 | 29.90 | 18.18 | 0.123756E+09 | 70.36 | 05-AUG-22:49 | 29.90 | 18.18 |
| September | 0.857148E+09 | 1204.39 | 14-SEP-16:25 | 24.70 | 16.87 | 0.107401E+09 | 70.36 | 02-SEP-22:40 | 24.70 | 16.87 |
| October | 0.398163E+09 | 383.86 | 11-OCT-22:00 | 8.30 | 6.18 | 84395922.01 | 64.29 | 04-OCT-20:00 | 8.30 | 6.18 |
| November | 0.119549E+09 | 346.62 | 05-NOV-20:00 | 10.60 | 9.38 | 76741044.44 | 59.46 | 04-NOV-21:10 | 10.60 | 9.38 |
| December | 6502616.82 | 156.61 | 10-DEC-15:00 | 10.60 | 8.77 | 77895344.66 | 42.51 | 11-DEC-06:49 | 2.80 | 2.57 |
| Annual Sum or Average | 0.749579E+10 | 0.112887E+10 | ||||||||
| Minimum of Months | 6183811.51 | 156.61 | 7.20 | 5.33 | 71052714.22 | 42.51 | -3.1 | -4.0 | ||
| Maximum of Months | 0.152733E+10 | 1843.07 | 29.90 | 18.18 | 0.123756E+09 | 70.37 | 29.90 | 18.18 |
Report: ZoneCoolingSummaryMonthly
For: T N2 APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 6186110.90 | 208.56 | 11-JAN-20:00 | 12.80 | 10.11 | 77895344.65 | 42.51 | 15-JAN-06:49 | -3.1 | -4.0 |
| February | 89793025.11 | 381.16 | 28-FEB-22:00 | 8.30 | 7.18 | 71037178.55 | 54.84 | 27-FEB-21:10 | 8.30 | 7.18 |
| March | 0.294642E+09 | 416.44 | 19-MAR-20:00 | 7.20 | 5.33 | 80026447.17 | 57.17 | 18-MAR-20:40 | 7.20 | 5.33 |
| April | 0.589703E+09 | 1248.13 | 27-APR-16:27 | 26.65 | 16.87 | 88483824.56 | 70.31 | 01-APR-23:10 | 26.65 | 16.87 |
| May | 0.953813E+09 | 1336.98 | 15-MAY-16:15 | 24.07 | 12.90 | 0.104163E+09 | 70.37 | 22-MAY-20:49 | 12.80 | 9.12 |
| June | 0.117793E+10 | 1571.58 | 28-JUN-17:40 | 25.97 | 16.68 | 0.113407E+09 | 70.37 | 03-JUN-22:00 | 25.97 | 16.68 |
| July | 0.152504E+10 | 1830.18 | 24-JUL-18:00 | 28.90 | 17.96 | 0.123483E+09 | 70.36 | 08-JUL-00:49 | 28.90 | 17.96 |
| August | 0.148900E+10 | 1746.35 | 08-AUG-16:15 | 29.93 | 18.24 | 0.123732E+09 | 70.36 | 19-AUG-22:30 | 14.50 | 12.40 |
| September | 0.857996E+09 | 1194.39 | 14-SEP-16:15 | 24.60 | 16.93 | 0.107238E+09 | 70.36 | 08-SEP-20:49 | 24.60 | 16.93 |
| October | 0.398040E+09 | 382.55 | 11-OCT-22:00 | 8.30 | 6.18 | 84327187.96 | 64.18 | 04-OCT-20:00 | 8.30 | 6.18 |
| November | 0.119680E+09 | 346.01 | 05-NOV-20:00 | 10.60 | 9.38 | 76729463.87 | 59.24 | 04-NOV-21:10 | 10.60 | 9.38 |
| December | 6391202.68 | 150.97 | 10-DEC-15:00 | 10.60 | 8.77 | 77895344.66 | 42.51 | 11-DEC-06:49 | 2.80 | 2.57 |
| Annual Sum or Average | 0.750821E+10 | 0.112842E+10 | ||||||||
| Minimum of Months | 6186110.90 | 150.97 | 7.20 | 5.33 | 71037178.55 | 42.51 | -3.1 | -4.0 | ||
| Maximum of Months | 0.152504E+10 | 1830.18 | 29.93 | 18.24 | 0.123732E+09 | 70.37 | 28.90 | 17.96 |
Report: ZoneCoolingSummaryMonthly
For: T S1 APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.134576E+09 | 669.07 | 20-JAN-13:30 | 6.70 | 4.72 | 78423554.00 | 56.20 | 08-JAN-16:10 | 6.70 | 4.72 |
| February | 0.352062E+09 | 1348.18 | 27-FEB-15:10 | 19.90 | 12.22 | 72727955.32 | 70.35 | 27-FEB-20:49 | 12.48 | 10.19 |
| March | 0.637715E+09 | 1735.29 | 14-MAR-14:00 | 15.60 | 10.50 | 83082816.08 | 70.35 | 18-MAR-18:00 | 16.70 | 8.15 |
| April | 0.101293E+10 | 2494.09 | 27-APR-14:20 | 26.47 | 16.98 | 93953399.22 | 70.36 | 09-APR-18:40 | 26.47 | 16.98 |
| May | 0.134346E+10 | 2265.30 | 15-MAY-14:10 | 23.30 | 13.36 | 0.104073E+09 | 70.37 | 03-MAY-22:00 | 23.30 | 13.36 |
| June | 0.149656E+10 | 2179.20 | 28-JUN-14:10 | 25.18 | 15.64 | 0.110378E+09 | 70.37 | 28-JUN-00:40 | 25.18 | 15.64 |
| July | 0.203103E+10 | 2605.39 | 24-JUL-13:40 | 29.03 | 18.20 | 0.124365E+09 | 70.37 | 01-JUL-22:40 | 29.03 | 18.20 |
| August | 0.214083E+10 | 2886.61 | 10-AUG-14:20 | 29.67 | 19.07 | 0.119729E+09 | 70.36 | 09-AUG-03:49 | 29.67 | 19.07 |
| September | 0.161728E+10 | 2710.71 | 23-SEP-13:40 | 22.93 | 17.70 | 0.111760E+09 | 70.36 | 01-SEP-00:10 | 22.93 | 17.70 |
| October | 0.851369E+09 | 2246.08 | 04-OCT-14:10 | 21.20 | 11.42 | 94054965.74 | 70.36 | 01-OCT-20:49 | 21.20 | 11.42 |
| November | 0.336760E+09 | 1919.59 | 04-NOV-14:00 | 21.10 | 15.94 | 79030232.47 | 70.36 | 04-NOV-21:49 | 13.58 | 12.53 |
| December | 0.203529E+09 | 727.85 | 05-DEC-14:30 | 10.30 | 6.71 | 79406860.60 | 66.78 | 03-DEC-16:10 | 10.30 | 6.71 |
| Annual Sum or Average | 0.121581E+11 | 0.115098E+10 | ||||||||
| Minimum of Months | 0.134576E+09 | 669.07 | 6.70 | 4.72 | 72727955.32 | 56.20 | 6.70 | 4.72 | ||
| Maximum of Months | 0.214083E+10 | 2886.61 | 29.67 | 19.07 | 0.124365E+09 | 70.37 | 29.67 | 19.07 |
Report: ZoneCoolingSummaryMonthly
For: T S2 APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.134406E+09 | 667.25 | 20-JAN-13:30 | 6.70 | 4.72 | 78418691.92 | 55.91 | 08-JAN-16:10 | 6.70 | 4.72 |
| February | 0.352124E+09 | 1344.19 | 27-FEB-15:10 | 19.90 | 12.22 | 72696375.41 | 70.34 | 26-FEB-16:30 | 19.90 | 12.22 |
| March | 0.639130E+09 | 1752.82 | 14-MAR-14:00 | 15.60 | 10.50 | 83035117.44 | 70.27 | 18-MAR-15:20 | 20.20 | 10.37 |
| April | 0.101882E+10 | 2504.68 | 27-APR-14:10 | 26.28 | 16.91 | 93962396.48 | 70.37 | 07-APR-18:10 | 26.28 | 16.91 |
| May | 0.134496E+10 | 2278.07 | 15-MAY-14:10 | 23.30 | 13.36 | 0.103976E+09 | 70.36 | 11-MAY-19:49 | 23.30 | 13.36 |
| June | 0.150465E+10 | 2189.18 | 28-JUN-14:10 | 25.18 | 15.64 | 0.110348E+09 | 70.36 | 19-JUN-23:30 | 25.18 | 15.64 |
| July | 0.202892E+10 | 2619.00 | 24-JUL-13:40 | 29.03 | 18.20 | 0.124280E+09 | 70.37 | 01-JUL-09:50 | 29.03 | 18.20 |
| August | 0.214454E+10 | 2894.23 | 10-AUG-14:20 | 29.67 | 19.07 | 0.119708E+09 | 70.36 | 13-AUG-03:39 | 16.30 | 12.74 |
| September | 0.161700E+10 | 2718.37 | 23-SEP-13:40 | 22.93 | 17.70 | 0.111641E+09 | 70.36 | 20-SEP-22:19 | 22.93 | 17.70 |
| October | 0.854029E+09 | 2253.49 | 04-OCT-14:10 | 21.20 | 11.42 | 94023249.75 | 70.37 | 24-OCT-19:49 | 14.08 | 9.82 |
| November | 0.337026E+09 | 1924.16 | 04-NOV-14:00 | 21.10 | 15.94 | 79025503.26 | 70.32 | 04-NOV-21:49 | 13.58 | 12.53 |
| December | 0.203320E+09 | 732.82 | 05-DEC-14:30 | 10.30 | 6.71 | 79396357.11 | 66.61 | 03-DEC-16:10 | 10.30 | 6.71 |
| Annual Sum or Average | 0.121789E+11 | 0.115051E+10 | ||||||||
| Minimum of Months | 0.134406E+09 | 667.25 | 6.70 | 4.72 | 72696375.41 | 55.91 | 6.70 | 4.72 | ||
| Maximum of Months | 0.214454E+10 | 2894.23 | 29.67 | 19.07 | 0.124280E+09 | 70.37 | 29.03 | 18.20 |
Report: ZoneCoolingSummaryMonthly
For: T CORRIDOR
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 5.92 | 4.99 | 0.112050E+09 | 78.04 | 11-JAN-22:10 | 10.82 | 10.11 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 7.00 | 6.66 | 0.113499E+09 | 115.74 | 27-FEB-21:10 | 12.20 | 10.06 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 5.92 | 4.69 | 0.146768E+09 | 122.91 | 18-MAR-20:10 | 15.32 | 7.57 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 7.93 | 7.13 | 0.175327E+09 | 158.84 | 27-APR-20:10 | 19.03 | 13.28 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 | 9.30 | 0.210926E+09 | 156.21 | 15-MAY-20:10 | 16.65 | 11.18 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 | 10.29 | 0.231141E+09 | 167.01 | 28-JUN-20:10 | 20.87 | 15.11 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 | 12.22 | 0.257634E+09 | 175.20 | 24-JUL-20:10 | 23.72 | 16.62 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 | 13.75 | 0.258696E+09 | 176.36 | 10-AUG-20:10 | 25.17 | 17.56 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 | 13.40 | 0.217240E+09 | 155.63 | 13-SEP-20:10 | 18.80 | 15.34 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 | 12.42 | 0.165956E+09 | 134.90 | 04-OCT-20:10 | 16.65 | 10.41 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 9.22 | 8.04 | 0.126264E+09 | 124.35 | 04-NOV-20:10 | 16.42 | 13.92 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 4.40 | 3.48 | 0.115123E+09 | 79.25 | 03-DEC-21:10 | 6.70 | 2.36 |
| Annual Sum or Average | 0.00 | 0.213062E+10 | ||||||||
| Minimum of Months | 0.00 | 0.00 | 4.40 | 3.48 | 0.112050E+09 | 78.04 | 6.70 | 2.36 | ||
| Maximum of Months | 0.00 | 0.00 | 17.17 | 13.75 | 0.258696E+09 | 176.36 | 25.17 | 17.56 |
Report: ZoneCoolingSummaryMonthly
For: G CORRIDOR
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 5.92 | 4.99 | 73525260.80 | 70.37 | 12-JAN-06:10 | 6.70 | 6.36 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 7.00 | 6.66 | 76338483.56 | 85.79 | 28-FEB-06:10 | 10.60 | 9.74 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 5.92 | 4.69 | 0.105596E+09 | 86.90 | 18-MAR-21:49 | 12.07 | 7.17 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 7.93 | 7.13 | 0.129481E+09 | 124.85 | 27-APR-17:10 | 26.10 | 16.67 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 | 9.30 | 0.175935E+09 | 139.12 | 07-MAY-22:10 | 13.90 | 12.30 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 | 10.29 | 0.207793E+09 | 153.85 | 28-JUN-21:49 | 18.03 | 13.98 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 | 12.22 | 0.244301E+09 | 166.81 | 24-JUL-21:49 | 20.97 | 15.91 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 | 13.75 | 0.254886E+09 | 193.59 | 10-AUG-17:10 | 31.62 | 18.84 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 | 13.40 | 0.211403E+09 | 154.89 | 14-SEP-21:49 | 17.38 | 14.54 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 | 12.42 | 0.156163E+09 | 130.25 | 04-OCT-22:10 | 15.73 | 10.00 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 9.22 | 8.04 | 0.102429E+09 | 103.50 | 05-NOV-05:10 | 12.80 | 12.39 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 4.40 | 3.48 | 81128757.94 | 74.09 | 04-DEC-06:10 | 3.22 | 1.95 |
| Annual Sum or Average | 0.00 | 0.181898E+10 | ||||||||
| Minimum of Months | 0.00 | 0.00 | 4.40 | 3.48 | 73525260.80 | 70.37 | 3.22 | 1.95 | ||
| Maximum of Months | 0.00 | 0.00 | 17.17 | 13.75 | 0.254886E+09 | 193.59 | 31.62 | 18.84 |
Report: ZoneCoolingSummaryMonthly
For: M CORRIDOR
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 5.92 | 4.99 | 0.151036E+09 | 91.28 | 11-JAN-22:10 | 10.82 | 10.11 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 7.00 | 6.66 | 0.147912E+09 | 117.92 | 28-FEB-21:10 | 9.22 | 7.84 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 5.92 | 4.69 | 0.187002E+09 | 118.97 | 18-MAR-20:10 | 15.32 | 7.57 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 7.93 | 7.13 | 0.214489E+09 | 152.56 | 27-APR-20:10 | 19.03 | 13.28 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 | 9.30 | 0.256233E+09 | 156.02 | 15-MAY-20:10 | 16.65 | 11.18 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 | 10.29 | 0.260714E+09 | 159.67 | 28-JUN-20:10 | 20.87 | 15.11 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 | 12.22 | 0.276401E+09 | 163.07 | 24-JUL-20:10 | 23.72 | 16.62 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 | 13.75 | 0.276784E+09 | 164.38 | 10-AUG-20:10 | 25.17 | 17.56 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 | 13.40 | 0.257459E+09 | 156.86 | 13-SEP-20:10 | 18.80 | 15.34 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 | 12.42 | 0.220899E+09 | 146.93 | 04-OCT-20:10 | 16.65 | 10.41 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 9.22 | 8.04 | 0.165339E+09 | 126.16 | 05-NOV-20:10 | 10.60 | 9.44 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 4.40 | 3.48 | 0.154540E+09 | 98.77 | 05-DEC-21:19 | 5.40 | 1.80 |
| Annual Sum or Average | 0.00 | 0.256881E+10 | ||||||||
| Minimum of Months | 0.00 | 0.00 | 4.40 | 3.48 | 0.147912E+09 | 91.28 | 5.40 | 1.80 | ||
| Maximum of Months | 0.00 | 0.00 | 17.17 | 13.75 | 0.276784E+09 | 164.38 | 25.17 | 17.56 |
Report: ZoneHeatingSummaryMonthly
For: G SW APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.857936E+09 | 759.01 | 16-JAN-08:30 | -0.9 |
| February | 0.507962E+09 | 1014.80 | 19-FEB-07:00 | -5.0 |
| March | 0.164192E+09 | 460.07 | 24-MAR-07:07 | 2.48 |
| April | 50143402.25 | 351.08 | 11-APR-04:00 | 5.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 |
| October | 1033898.13 | 83.09 | 28-OCT-04:00 | 7.80 |
| November | 0.169547E+09 | 506.10 | 30-NOV-01:00 | 5.60 |
| December | 0.598415E+09 | 773.23 | 26-DEC-14:00 | 1.20 |
| Annual Sum or Average | 0.234923E+10 | |||
| Minimum of Months | 0.00 | 0.00 | -5.0 | |
| Maximum of Months | 0.857936E+09 | 1014.80 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: G NW APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.126830E+10 | 936.58 | 16-JAN-09:00 | -0.6 |
| February | 0.930369E+09 | 1193.73 | 19-FEB-08:13 | -4.4 |
| March | 0.456171E+09 | 717.03 | 26-MAR-17:02 | 10.50 |
| April | 0.147603E+09 | 828.90 | 02-APR-07:01 | 10.78 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 |
| October | 17536747.23 | 220.31 | 30-OCT-02:00 | 6.70 |
| November | 0.339222E+09 | 548.71 | 30-NOV-00:50 | 5.60 |
| December | 0.933976E+09 | 816.13 | 26-DEC-14:00 | 1.20 |
| Annual Sum or Average | 0.409318E+10 | |||
| Minimum of Months | 0.00 | 0.00 | -4.4 | |
| Maximum of Months | 0.126830E+10 | 1193.73 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: OFFICE
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.410207E+09 | 9581.95 | 18-JAN-07:01 | 2.88 |
| February | 0.230133E+09 | 9548.54 | 21-FEB-07:01 | 1.60 |
| March | 41364177.04 | 9550.66 | 06-MAR-08:61 | 6.78 |
| April | 55880743.12 | 7291.01 | 18-APR-07:01 | 3.98 |
| May | 61456428.53 | 370.00 | 05-MAY-16:25 | 23.90 |
| June | 84507738.67 | 463.62 | 28-JUN-16:12 | 26.30 |
| July | 0.131839E+09 | 538.69 | 31-JUL-16:12 | 28.70 |
| August | 0.144606E+09 | 655.52 | 29-AUG-16:12 | 31.23 |
| September | 38338125.89 | 364.72 | 14-SEP-16:12 | 24.60 |
| October | 12809675.27 | 251.30 | 04-OCT-08:05 | 14.18 |
| November | 66542368.90 | 9526.83 | 14-NOV-08:61 | 5.00 |
| December | 0.244769E+09 | 9541.39 | 15-DEC-08:61 | 5.37 |
| Annual Sum or Average | 0.152245E+10 | |||
| Minimum of Months | 12809675.27 | 251.30 | 1.60 | |
| Maximum of Months | 0.410207E+09 | 9581.95 | 31.23 |
Report: ZoneHeatingSummaryMonthly
For: G NE APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.127494E+10 | 927.27 | 16-JAN-09:00 | -0.6 |
| February | 0.928379E+09 | 1123.24 | 19-FEB-07:00 | -5.0 |
| March | 0.432078E+09 | 862.48 | 27-MAR-17:01 | 9.32 |
| April | 0.129416E+09 | 779.76 | 02-APR-07:01 | 10.78 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 |
| October | 18116604.38 | 230.05 | 30-OCT-02:00 | 6.70 |
| November | 0.338733E+09 | 545.84 | 30-NOV-01:00 | 5.60 |
| December | 0.939344E+09 | 824.45 | 26-DEC-14:00 | 1.20 |
| Annual Sum or Average | 0.406101E+10 | |||
| Minimum of Months | 0.00 | 0.00 | -5.0 | |
| Maximum of Months | 0.127494E+10 | 1123.24 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: G N1 APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.411924E+09 | 457.53 | 16-JAN-08:40 | -0.8 |
| February | 0.306140E+09 | 622.40 | 19-FEB-08:13 | -4.4 |
| March | 56623916.31 | 230.56 | 27-MAR-17:01 | 9.32 |
| April | 13162190.84 | 160.65 | 01-APR-16:00 | 27.20 |
| May | 4952.94 | 7.87 | 04-MAY-13:50 | 23.62 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 |
| November | 31759129.15 | 181.65 | 30-NOV-01:10 | 5.60 |
| December | 0.210057E+09 | 373.21 | 26-DEC-14:00 | 1.20 |
| Annual Sum or Average | 0.102967E+10 | |||
| Minimum of Months | 0.00 | 0.00 | -4.4 | |
| Maximum of Months | 0.411924E+09 | 622.40 | 27.20 |
Report: ZoneHeatingSummaryMonthly
For: G N2 APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.412321E+09 | 457.60 | 16-JAN-08:40 | -0.8 |
| February | 0.306098E+09 | 619.92 | 19-FEB-08:13 | -4.4 |
| March | 56525988.77 | 229.37 | 05-MAR-04:00 | 2.80 |
| April | 13081947.63 | 160.58 | 01-APR-16:00 | 27.20 |
| May | 127.10 | 0.21 | 04-MAY-13:40 | 23.33 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 |
| November | 31856970.68 | 181.62 | 30-NOV-01:10 | 5.60 |
| December | 0.210234E+09 | 373.37 | 26-DEC-14:00 | 1.20 |
| Annual Sum or Average | 0.103012E+10 | |||
| Minimum of Months | 0.00 | 0.00 | -4.4 | |
| Maximum of Months | 0.412321E+09 | 619.92 | 27.20 |
Report: ZoneHeatingSummaryMonthly
For: G S1 APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.153333E+09 | 285.71 | 14-JAN-04:00 | 1.70 |
| February | 83651863.79 | 439.90 | 19-FEB-07:00 | -5.0 |
| March | 1576360.11 | 59.96 | 24-MAR-05:00 | 2.80 |
| April | 350063.66 | 74.87 | 01-APR-14:50 | 25.73 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 |
| November | 5856391.51 | 139.26 | 30-NOV-01:10 | 5.60 |
| December | 90340978.17 | 327.67 | 26-DEC-14:00 | 1.20 |
| Annual Sum or Average | 0.335109E+09 | |||
| Minimum of Months | 0.00 | 0.00 | -5.0 | |
| Maximum of Months | 0.153333E+09 | 439.90 | 25.73 |
Report: ZoneHeatingSummaryMonthly
For: G S2 APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.277007E+09 | 416.03 | 16-JAN-08:30 | -0.9 |
| February | 0.132765E+09 | 560.67 | 19-FEB-07:00 | -5.0 |
| March | 3398873.62 | 82.25 | 06-MAR-05:00 | 6.70 |
| April | 416846.81 | 74.94 | 01-APR-14:50 | 25.73 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 |
| November | 11970915.33 | 171.25 | 30-NOV-01:10 | 5.60 |
| December | 0.152834E+09 | 430.52 | 26-DEC-08:20 | -1.1 |
| Annual Sum or Average | 0.578393E+09 | |||
| Minimum of Months | 0.00 | 0.00 | -5.0 | |
| Maximum of Months | 0.277007E+09 | 560.67 | 25.73 |
Report: ZoneHeatingSummaryMonthly
For: M SW APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.352793E+09 | 607.36 | 14-JAN-04:00 | 1.70 |
| February | 0.170601E+09 | 806.66 | 19-FEB-07:00 | -5.0 |
| March | 7959162.80 | 192.38 | 06-MAR-05:00 | 6.70 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 7.93 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 |
| November | 0.108377E+09 | 512.24 | 30-NOV-01:00 | 5.60 |
| December | 0.293441E+09 | 656.82 | 26-DEC-14:00 | 1.20 |
| Annual Sum or Average | 0.933171E+09 | |||
| Minimum of Months | 0.00 | 0.00 | -5.0 | |
| Maximum of Months | 0.352793E+09 | 806.66 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: M NW APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.609112E+09 | 716.85 | 15-JAN-05:00 | -2.8 |
| February | 0.373006E+09 | 924.29 | 19-FEB-07:00 | -5.0 |
| March | 59019345.30 | 400.27 | 05-MAR-04:00 | 2.80 |
| April | 3799941.85 | 135.06 | 19-APR-05:00 | 1.70 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 |
| October | 5580064.99 | 138.94 | 31-OCT-23:10 | 8.60 |
| November | 0.195668E+09 | 537.60 | 30-NOV-01:00 | 5.60 |
| December | 0.467946E+09 | 689.70 | 26-DEC-14:00 | 1.20 |
| Annual Sum or Average | 0.171413E+10 | |||
| Minimum of Months | 0.00 | 0.00 | -5.0 | |
| Maximum of Months | 0.609112E+09 | 924.29 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: M SE APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.355605E+09 | 600.37 | 14-JAN-04:00 | 1.70 |
| February | 0.169264E+09 | 802.23 | 19-FEB-07:00 | -5.0 |
| March | 6024115.50 | 200.60 | 24-MAR-06:00 | 1.70 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 7.93 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 |
| November | 0.108586E+09 | 510.49 | 30-NOV-01:00 | 5.60 |
| December | 0.295318E+09 | 666.31 | 26-DEC-14:00 | 1.20 |
| Annual Sum or Average | 0.934797E+09 | |||
| Minimum of Months | 0.00 | 0.00 | -5.0 | |
| Maximum of Months | 0.355605E+09 | 802.23 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: M NE APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.615740E+09 | 739.80 | 15-JAN-05:00 | -2.8 |
| February | 0.361233E+09 | 919.24 | 19-FEB-07:00 | -5.0 |
| March | 52510762.70 | 387.62 | 24-MAR-06:00 | 1.70 |
| April | 5009641.61 | 137.29 | 19-APR-05:00 | 1.70 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 |
| October | 6877743.33 | 143.79 | 31-OCT-23:10 | 8.60 |
| November | 0.192602E+09 | 534.98 | 30-NOV-01:00 | 5.60 |
| December | 0.468417E+09 | 699.73 | 26-DEC-14:00 | 1.20 |
| Annual Sum or Average | 0.170239E+10 | |||
| Minimum of Months | 0.00 | 0.00 | -5.0 | |
| Maximum of Months | 0.615740E+09 | 919.24 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: M N1 APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 47331561.07 | 234.80 | 15-JAN-05:00 | -2.8 |
| February | 35107945.52 | 328.95 | 19-FEB-06:00 | -5.6 |
| March | 9275.38 | 7.35 | 05-MAR-04:00 | 2.80 |
| April | 1732916.66 | 130.89 | 01-APR-16:00 | 27.20 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 |
| November | 2496782.61 | 119.80 | 30-NOV-01:00 | 5.60 |
| December | 19992752.79 | 199.16 | 26-DEC-14:00 | 1.20 |
| Annual Sum or Average | 0.106671E+09 | |||
| Minimum of Months | 0.00 | 0.00 | -5.6 | |
| Maximum of Months | 47331561.07 | 328.95 | 27.20 |
Report: ZoneHeatingSummaryMonthly
For: M N2 APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 47584702.06 | 235.65 | 15-JAN-05:00 | -2.8 |
| February | 35000468.39 | 328.44 | 19-FEB-06:00 | -5.6 |
| March | 4701.38 | 5.23 | 05-MAR-04:00 | 2.80 |
| April | 1723601.98 | 130.59 | 01-APR-16:00 | 27.20 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 |
| November | 2495014.52 | 119.48 | 30-NOV-01:10 | 5.60 |
| December | 20066427.99 | 198.69 | 26-DEC-14:00 | 1.20 |
| Annual Sum or Average | 0.106875E+09 | |||
| Minimum of Months | 0.00 | 0.00 | -5.6 | |
| Maximum of Months | 47584702.06 | 328.44 | 27.20 |
Report: ZoneHeatingSummaryMonthly
For: M S1 APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 8894719.16 | 163.68 | 14-JAN-04:00 | 1.70 |
| February | 9728273.92 | 250.37 | 19-FEB-06:00 | -5.6 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 5.92 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 7.93 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 |
| November | 1318507.75 | 97.96 | 30-NOV-01:10 | 5.60 |
| December | 7304099.70 | 170.89 | 26-DEC-14:00 | 1.20 |
| Annual Sum or Average | 27245600.53 | |||
| Minimum of Months | 0.00 | 0.00 | -5.6 | |
| Maximum of Months | 9728273.92 | 250.37 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: M S2 APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 8919378.43 | 163.36 | 14-JAN-04:00 | 1.70 |
| February | 9701455.17 | 249.95 | 19-FEB-06:00 | -5.6 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 5.92 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 7.93 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 |
| November | 1313265.36 | 97.79 | 30-NOV-01:10 | 5.60 |
| December | 7312375.20 | 170.94 | 26-DEC-14:00 | 1.20 |
| Annual Sum or Average | 27246474.15 | |||
| Minimum of Months | 0.00 | 0.00 | -5.6 | |
| Maximum of Months | 9701455.17 | 249.95 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: T SW APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.173788E+10 | 1618.85 | 15-JAN-05:00 | -2.8 |
| February | 0.108247E+10 | 1995.26 | 19-FEB-07:00 | -5.0 |
| March | 0.586151E+09 | 1134.55 | 24-MAR-06:00 | 1.70 |
| April | 0.251257E+09 | 1057.05 | 11-APR-04:00 | 5.00 |
| May | 61008615.03 | 873.18 | 18-MAY-05:00 | 5.60 |
| June | 4971347.31 | 490.37 | 15-JUN-07:01 | 10.78 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 |
| September | 9601280.69 | 354.99 | 27-SEP-03:00 | 8.30 |
| October | 0.253091E+09 | 871.19 | 28-OCT-04:00 | 7.80 |
| November | 0.941153E+09 | 1263.51 | 30-NOV-01:00 | 5.60 |
| December | 0.155838E+10 | 1435.33 | 26-DEC-14:00 | 1.20 |
| Annual Sum or Average | 0.648597E+10 | |||
| Minimum of Months | 0.00 | 0.00 | -5.0 | |
| Maximum of Months | 0.173788E+10 | 1995.26 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: T NW APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.213043E+10 | 1744.99 | 15-JAN-05:00 | -2.8 |
| February | 0.146135E+10 | 2057.19 | 19-FEB-07:00 | -5.0 |
| March | 0.811569E+09 | 1235.22 | 24-MAR-06:00 | 1.70 |
| April | 0.333150E+09 | 1097.60 | 11-APR-04:00 | 5.00 |
| May | 70325021.53 | 858.44 | 18-MAY-05:00 | 5.60 |
| June | 5621177.45 | 355.49 | 15-JUN-07:01 | 10.78 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 |
| September | 13869092.72 | 386.97 | 27-SEP-03:00 | 8.30 |
| October | 0.387487E+09 | 866.17 | 28-OCT-04:00 | 7.80 |
| November | 0.117512E+10 | 1258.46 | 30-NOV-01:00 | 5.60 |
| December | 0.191067E+10 | 1430.97 | 26-DEC-04:00 | -1.1 |
| Annual Sum or Average | 0.829959E+10 | |||
| Minimum of Months | 0.00 | 0.00 | -5.0 | |
| Maximum of Months | 0.213043E+10 | 2057.19 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: T SE APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.173584E+10 | 1639.24 | 15-JAN-05:00 | -2.8 |
| February | 0.107751E+10 | 1996.58 | 19-FEB-07:00 | -5.0 |
| March | 0.571542E+09 | 1144.34 | 24-MAR-06:00 | 1.70 |
| April | 0.233233E+09 | 1090.52 | 11-APR-04:00 | 5.00 |
| May | 62117997.15 | 870.32 | 18-MAY-05:00 | 5.60 |
| June | 7294764.91 | 311.25 | 14-JUN-03:00 | 10.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 |
| September | 11241346.09 | 422.72 | 27-SEP-03:00 | 8.30 |
| October | 0.252494E+09 | 867.84 | 28-OCT-04:00 | 7.80 |
| November | 0.942405E+09 | 1260.51 | 30-NOV-00:50 | 5.60 |
| December | 0.156007E+10 | 1453.43 | 26-DEC-14:00 | 1.20 |
| Annual Sum or Average | 0.645375E+10 | |||
| Minimum of Months | 0.00 | 0.00 | -5.0 | |
| Maximum of Months | 0.173584E+10 | 1996.58 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: T NE APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.213591E+10 | 1764.28 | 15-JAN-05:00 | -2.8 |
| February | 0.145615E+10 | 2059.77 | 19-FEB-07:00 | -5.0 |
| March | 0.783157E+09 | 1242.55 | 24-MAR-06:00 | 1.70 |
| April | 0.307143E+09 | 1131.65 | 11-APR-04:00 | 5.00 |
| May | 73023751.38 | 857.89 | 18-MAY-05:00 | 5.60 |
| June | 8335036.81 | 334.89 | 14-JUN-03:00 | 10.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 |
| September | 14969908.54 | 452.46 | 27-SEP-03:00 | 8.30 |
| October | 0.382287E+09 | 919.34 | 22-OCT-16:01 | 12.12 |
| November | 0.117131E+10 | 1256.57 | 30-NOV-01:00 | 5.60 |
| December | 0.191403E+10 | 1442.85 | 26-DEC-14:00 | 1.20 |
| Annual Sum or Average | 0.824630E+10 | |||
| Minimum of Months | 0.00 | 0.00 | -5.0 | |
| Maximum of Months | 0.213591E+10 | 2059.77 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: T N1 APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.110807E+10 | 1117.79 | 15-JAN-05:00 | -2.8 |
| February | 0.739300E+09 | 1290.95 | 19-FEB-06:00 | -5.6 |
| March | 0.320318E+09 | 676.62 | 25-MAR-05:00 | 2.20 |
| April | 95551386.17 | 583.37 | 11-APR-04:00 | 5.00 |
| May | 10472948.27 | 380.87 | 18-MAY-05:00 | 5.60 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 |
| September | 859779.43 | 101.98 | 27-SEP-03:00 | 8.30 |
| October | 99656227.44 | 432.33 | 28-OCT-04:00 | 7.80 |
| November | 0.507884E+09 | 706.59 | 11-NOV-06:00 | 0.60 |
| December | 0.964067E+09 | 884.01 | 26-DEC-04:00 | -1.1 |
| Annual Sum or Average | 0.384618E+10 | |||
| Minimum of Months | 0.00 | 0.00 | -5.6 | |
| Maximum of Months | 0.110807E+10 | 1290.95 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: T N2 APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.110847E+10 | 1118.98 | 15-JAN-05:00 | -2.8 |
| February | 0.739633E+09 | 1290.60 | 19-FEB-06:00 | -5.6 |
| March | 0.321078E+09 | 676.63 | 25-MAR-05:00 | 2.20 |
| April | 95047406.39 | 587.41 | 11-APR-04:00 | 5.00 |
| May | 10655979.69 | 381.07 | 18-MAY-05:00 | 5.60 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 |
| September | 996058.93 | 110.53 | 27-SEP-03:00 | 8.30 |
| October | 0.100347E+09 | 431.96 | 28-OCT-04:00 | 7.80 |
| November | 0.508147E+09 | 708.07 | 11-NOV-06:00 | 0.60 |
| December | 0.964535E+09 | 884.12 | 26-DEC-04:00 | -1.1 |
| Annual Sum or Average | 0.384891E+10 | |||
| Minimum of Months | 0.00 | 0.00 | -5.6 | |
| Maximum of Months | 0.110847E+10 | 1290.60 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: T S1 APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.788144E+09 | 980.43 | 15-JAN-05:00 | -2.8 |
| February | 0.456908E+09 | 1216.15 | 19-FEB-07:00 | -5.0 |
| March | 0.174075E+09 | 559.75 | 24-MAR-06:00 | 1.70 |
| April | 59993369.02 | 535.11 | 11-APR-04:00 | 5.00 |
| May | 9339611.71 | 397.20 | 18-MAY-05:00 | 5.60 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 |
| September | 339816.39 | 63.63 | 27-SEP-03:00 | 8.30 |
| October | 43053511.11 | 434.52 | 28-OCT-04:00 | 7.80 |
| November | 0.361562E+09 | 699.07 | 30-NOV-01:00 | 5.60 |
| December | 0.700810E+09 | 853.25 | 26-DEC-09:20 | -0.7 |
| Annual Sum or Average | 0.259422E+10 | |||
| Minimum of Months | 0.00 | 0.00 | -5.0 | |
| Maximum of Months | 0.788144E+09 | 1216.15 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: T S2 APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.788690E+09 | 981.83 | 15-JAN-05:00 | -2.8 |
| February | 0.457589E+09 | 1215.72 | 19-FEB-07:00 | -5.0 |
| March | 0.174212E+09 | 561.43 | 24-MAR-06:00 | 1.70 |
| April | 60067282.05 | 539.10 | 11-APR-04:00 | 5.00 |
| May | 9417973.21 | 397.49 | 18-MAY-05:00 | 5.60 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 |
| September | 416188.61 | 73.17 | 27-SEP-03:00 | 8.30 |
| October | 43439163.97 | 434.26 | 28-OCT-04:00 | 7.80 |
| November | 0.361890E+09 | 698.89 | 30-NOV-01:00 | 5.60 |
| December | 0.701350E+09 | 852.98 | 26-DEC-09:10 | -0.9 |
| Annual Sum or Average | 0.259707E+10 | |||
| Minimum of Months | 0.00 | 0.00 | -5.0 | |
| Maximum of Months | 0.788690E+09 | 1215.72 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: T CORRIDOR
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 5.92 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 7.00 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 5.92 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 7.93 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 9.22 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 4.40 |
| Annual Sum or Average | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 4.40 | |
| Maximum of Months | 0.00 | 0.00 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: G CORRIDOR
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 5.92 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 7.00 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 5.92 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 7.93 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 9.22 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 4.40 |
| Annual Sum or Average | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 4.40 | |
| Maximum of Months | 0.00 | 0.00 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: M CORRIDOR
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 5.92 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 7.00 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 5.92 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 7.93 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 9.22 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 4.40 |
| Annual Sum or Average | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 4.40 | |
| Maximum of Months | 0.00 | 0.00 | 17.17 |
Report: ZoneElectricSummaryMonthly
For: G SW APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: G NW APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: OFFICE
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.609777E+09 | 582.92 | 03-JAN-08:09 | 0.787690E+09 | 588.62 | 03-JAN-08:09 |
| February | 0.564682E+09 | 582.92 | 01-FEB-08:09 | 0.723971E+09 | 588.62 | 01-FEB-08:09 |
| March | 0.654405E+09 | 582.92 | 01-MAR-08:09 | 0.827804E+09 | 588.62 | 01-MAR-08:09 |
| April | 0.599704E+09 | 582.92 | 03-APR-07:10 | 0.770907E+09 | 588.62 | 03-APR-07:10 |
| May | 0.639529E+09 | 582.92 | 01-MAY-07:10 | 0.814432E+09 | 588.62 | 01-MAY-07:10 |
| June | 0.629456E+09 | 582.92 | 01-JUN-07:10 | 0.797650E+09 | 588.62 | 01-JUN-07:10 |
| July | 0.609777E+09 | 582.92 | 03-JUL-07:10 | 0.787690E+09 | 588.62 | 03-JUL-07:10 |
| August | 0.654405E+09 | 582.92 | 01-AUG-07:10 | 0.827804E+09 | 588.62 | 01-AUG-07:10 |
| September | 0.599704E+09 | 582.92 | 01-SEP-07:10 | 0.770907E+09 | 588.62 | 01-SEP-07:10 |
| October | 0.624653E+09 | 582.92 | 02-OCT-07:10 | 0.801061E+09 | 588.62 | 02-OCT-07:10 |
| November | 0.599704E+09 | 582.92 | 01-NOV-07:10 | 0.770907E+09 | 588.62 | 01-NOV-07:10 |
| December | 0.609777E+09 | 582.92 | 01-DEC-08:09 | 0.787690E+09 | 588.62 | 01-DEC-08:09 |
| Annual Sum or Average | 0.739557E+10 | 0.946851E+10 | ||||
| Minimum of Months | 0.564682E+09 | 582.92 | 0.723971E+09 | 588.62 | ||
| Maximum of Months | 0.654405E+09 | 582.92 | 0.827804E+09 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: G NE APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: G N1 APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: G N2 APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: G S1 APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: G S2 APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: M SW APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: M NW APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: M SE APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: M NE APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: M N1 APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: M N2 APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: M S1 APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: M S2 APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: T SW APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: T NW APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: T SE APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: T NE APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: T N1 APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: T N2 APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: T S1 APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: T S2 APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: T CORRIDOR
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
| January | 0.992689E+09 | 370.63 | 01-JAN-00:10 | 0.00 | 0.00 |
| February | 0.896622E+09 | 370.63 | 01-FEB-00:10 | 0.00 | 0.00 |
| March | 0.992689E+09 | 370.63 | 01-MAR-00:10 | 0.00 | 0.00 |
| April | 0.960667E+09 | 370.63 | 01-APR-00:10 | 0.00 | 0.00 |
| May | 0.992689E+09 | 370.63 | 01-MAY-00:10 | 0.00 | 0.00 |
| June | 0.960667E+09 | 370.63 | 01-JUN-00:10 | 0.00 | 0.00 |
| July | 0.992689E+09 | 370.63 | 01-JUL-00:10 | 0.00 | 0.00 |
| August | 0.992689E+09 | 370.63 | 01-AUG-00:10 | 0.00 | 0.00 |
| September | 0.960667E+09 | 370.63 | 01-SEP-00:10 | 0.00 | 0.00 |
| October | 0.992689E+09 | 370.63 | 01-OCT-00:10 | 0.00 | 0.00 |
| November | 0.960667E+09 | 370.63 | 01-NOV-00:10 | 0.00 | 0.00 |
| December | 0.992689E+09 | 370.63 | 01-DEC-00:10 | 0.00 | 0.00 |
| Annual Sum or Average | 0.116881E+11 | 0.00 | 0.00 | ||
| Minimum of Months | 0.896622E+09 | 370.63 | 0.00 | 0.00 | |
| Maximum of Months | 0.992689E+09 | 370.63 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: G CORRIDOR
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.992689E+09 | 370.63 | 01-JAN-00:10 | 0.599555E+10 | 4168.07 | 01-JAN-07:10 |
| February | 0.896622E+09 | 370.63 | 01-FEB-00:10 | 0.541534E+10 | 4168.07 | 01-FEB-07:10 |
| March | 0.992689E+09 | 370.63 | 01-MAR-00:10 | 0.599555E+10 | 4168.07 | 01-MAR-07:10 |
| April | 0.960667E+09 | 370.63 | 01-APR-00:10 | 0.580215E+10 | 4168.07 | 01-APR-06:10 |
| May | 0.992689E+09 | 370.63 | 01-MAY-00:10 | 0.599555E+10 | 4168.07 | 01-MAY-06:10 |
| June | 0.960667E+09 | 370.63 | 01-JUN-00:10 | 0.580215E+10 | 4168.07 | 01-JUN-06:10 |
| July | 0.992689E+09 | 370.63 | 01-JUL-00:10 | 0.599555E+10 | 4168.07 | 01-JUL-06:10 |
| August | 0.992689E+09 | 370.63 | 01-AUG-00:10 | 0.599555E+10 | 4168.07 | 01-AUG-06:10 |
| September | 0.960667E+09 | 370.63 | 01-SEP-00:10 | 0.580215E+10 | 4168.07 | 01-SEP-06:10 |
| October | 0.992689E+09 | 370.63 | 01-OCT-00:10 | 0.599555E+10 | 4168.07 | 01-OCT-06:10 |
| November | 0.960667E+09 | 370.63 | 01-NOV-00:10 | 0.580215E+10 | 4168.07 | 01-NOV-06:10 |
| December | 0.992689E+09 | 370.63 | 01-DEC-00:10 | 0.599555E+10 | 4168.07 | 01-DEC-07:10 |
| Annual Sum or Average | 0.116881E+11 | 0.705928E+11 | ||||
| Minimum of Months | 0.896622E+09 | 370.63 | 0.541534E+10 | 4168.07 | ||
| Maximum of Months | 0.992689E+09 | 370.63 | 0.599555E+10 | 4168.07 |
Report: ZoneElectricSummaryMonthly
For: M CORRIDOR
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
| January | 0.992689E+09 | 370.63 | 01-JAN-00:10 | 0.00 | 0.00 |
| February | 0.896622E+09 | 370.63 | 01-FEB-00:10 | 0.00 | 0.00 |
| March | 0.992689E+09 | 370.63 | 01-MAR-00:10 | 0.00 | 0.00 |
| April | 0.960667E+09 | 370.63 | 01-APR-00:10 | 0.00 | 0.00 |
| May | 0.992689E+09 | 370.63 | 01-MAY-00:10 | 0.00 | 0.00 |
| June | 0.960667E+09 | 370.63 | 01-JUN-00:10 | 0.00 | 0.00 |
| July | 0.992689E+09 | 370.63 | 01-JUL-00:10 | 0.00 | 0.00 |
| August | 0.992689E+09 | 370.63 | 01-AUG-00:10 | 0.00 | 0.00 |
| September | 0.960667E+09 | 370.63 | 01-SEP-00:10 | 0.00 | 0.00 |
| October | 0.992689E+09 | 370.63 | 01-OCT-00:10 | 0.00 | 0.00 |
| November | 0.960667E+09 | 370.63 | 01-NOV-00:10 | 0.00 | 0.00 |
| December | 0.992689E+09 | 370.63 | 01-DEC-00:10 | 0.00 | 0.00 |
| Annual Sum or Average | 0.116881E+11 | 0.00 | 0.00 | ||
| Minimum of Months | 0.896622E+09 | 370.63 | 0.00 | 0.00 | |
| Maximum of Months | 0.992689E+09 | 370.63 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: G SW APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.377433E+09 |
| February | 0.389025E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.323230E+09 |
| March | 0.418950E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.299315E+09 |
| April | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 901185.41 | 0.267369E+09 |
| May | 0.424935E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 46260.01 | 0.222253E+09 |
| June | 0.406980E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 466060.70 | 0.181443E+09 |
| July | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5064846.68 | 0.134163E+09 |
| August | 0.418950E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9854874.95 | 0.119132E+09 |
| September | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 46139.97 | 0.107167E+09 |
| October | 0.430920E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.254633E+09 |
| November | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.286790E+09 |
| December | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.316438E+09 |
| Annual Sum or Average | 0.505732E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 16379367.72 | 0.288937E+10 |
| Minimum of Months | 0.389025E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107167E+09 |
| Maximum of Months | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9854874.95 | 0.377433E+09 |
Report: SpaceGainsMonthly
For: G NW APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.377430E+09 |
| February | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.322137E+09 |
| March | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.295206E+09 |
| April | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1257905.58 | 0.258214E+09 |
| May | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 46261.51 | 0.210507E+09 |
| June | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 466066.70 | 0.176124E+09 |
| July | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5064854.08 | 0.133236E+09 |
| August | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9854881.21 | 0.118270E+09 |
| September | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 46140.14 | 0.103075E+09 |
| October | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.237538E+09 |
| November | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.283543E+09 |
| December | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.315786E+09 |
| Annual Sum or Average | 0.512427E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 16736109.22 | 0.283107E+10 |
| Minimum of Months | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103075E+09 |
| Maximum of Months | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9854881.21 | 0.377430E+09 |
Report: SpaceGainsMonthly
For: OFFICE
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.227408E+09 | 0.609777E+09 | 0.787690E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.321494E+09 |
| February | 0.216037E+09 | 0.564682E+09 | 0.723971E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.287247E+09 |
| March | 0.261519E+09 | 0.654405E+09 | 0.827804E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.291250E+09 |
| April | 0.227408E+09 | 0.599704E+09 | 0.770907E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 711915.53 | 0.277465E+09 |
| May | 0.250148E+09 | 0.639529E+09 | 0.814432E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 38511.24 | 0.244351E+09 |
| June | 0.250148E+09 | 0.629456E+09 | 0.797650E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 235809.04 | 0.207829E+09 |
| July | 0.227408E+09 | 0.609777E+09 | 0.787690E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2092025.22 | 0.166976E+09 |
| August | 0.261519E+09 | 0.654405E+09 | 0.827804E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6227195.46 | 0.155038E+09 |
| September | 0.227408E+09 | 0.599704E+09 | 0.770907E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 26259.71 | 0.122970E+09 |
| October | 0.238778E+09 | 0.624653E+09 | 0.801061E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.274633E+09 |
| November | 0.227408E+09 | 0.599704E+09 | 0.770907E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.278984E+09 |
| December | 0.227408E+09 | 0.609777E+09 | 0.787690E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.280514E+09 |
| Annual Sum or Average | 0.284259E+10 | 0.739557E+10 | 0.946851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9331716.21 | 0.290875E+10 |
| Minimum of Months | 0.216037E+09 | 0.564682E+09 | 0.723971E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122970E+09 |
| Maximum of Months | 0.261519E+09 | 0.654405E+09 | 0.827804E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6227195.46 | 0.321494E+09 |
Report: SpaceGainsMonthly
For: G NE APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.377430E+09 |
| February | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.322090E+09 |
| March | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.295009E+09 |
| April | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1297533.80 | 0.258242E+09 |
| May | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 46261.86 | 0.209771E+09 |
| June | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 466067.99 | 0.178019E+09 |
| July | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5064857.76 | 0.132582E+09 |
| August | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9854885.72 | 0.118309E+09 |
| September | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 46140.32 | 0.102192E+09 |
| October | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.236865E+09 |
| November | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.283501E+09 |
| December | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.315786E+09 |
| Annual Sum or Average | 0.512427E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 16775747.45 | 0.282980E+10 |
| Minimum of Months | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102192E+09 |
| Maximum of Months | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9854885.72 | 0.377430E+09 |
Report: SpaceGainsMonthly
For: G N1 APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.227656E+09 |
| February | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.194393E+09 |
| March | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.178146E+09 |
| April | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 855808.58 | 0.156307E+09 |
| May | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27904.11 | 0.130347E+09 |
| June | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 281121.73 | 0.109343E+09 |
| July | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3054995.55 | 81086310.43 |
| August | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5944218.60 | 72069955.98 |
| September | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27830.74 | 63732367.07 |
| October | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.146312E+09 |
| November | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.172257E+09 |
| December | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.190474E+09 |
| Annual Sum or Average | 0.512427E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 10191879.31 | 0.172212E+10 |
| Minimum of Months | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63732367.07 |
| Maximum of Months | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5944218.60 | 0.227656E+09 |
Report: SpaceGainsMonthly
For: G N2 APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.227656E+09 |
| February | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.194391E+09 |
| March | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.178140E+09 |
| April | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 853155.58 | 0.156329E+09 |
| May | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27904.11 | 0.130271E+09 |
| June | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 281121.73 | 0.109469E+09 |
| July | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3054995.58 | 81057775.72 |
| August | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5944218.65 | 72065541.78 |
| September | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27830.74 | 63672322.05 |
| October | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.146240E+09 |
| November | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.172251E+09 |
| December | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.190474E+09 |
| Annual Sum or Average | 0.512427E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 10189226.39 | 0.172202E+10 |
| Minimum of Months | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63672322.05 |
| Maximum of Months | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5944218.65 | 0.227656E+09 |
Report: SpaceGainsMonthly
For: G S1 APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.227751E+09 |
| February | 0.389025E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.195766E+09 |
| March | 0.418950E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.182634E+09 |
| April | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 538544.68 | 0.164784E+09 |
| May | 0.424935E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27903.19 | 0.139430E+09 |
| June | 0.406980E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 281117.67 | 0.112502E+09 |
| July | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3054992.34 | 81439225.59 |
| August | 0.418950E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5944214.27 | 72372839.31 |
| September | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27830.59 | 65732201.53 |
| October | 0.430920E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160819E+09 |
| November | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.175946E+09 |
| December | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.191407E+09 |
| Annual Sum or Average | 0.505732E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 9874602.74 | 0.177058E+10 |
| Minimum of Months | 0.389025E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65732201.53 |
| Maximum of Months | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5944214.27 | 0.227751E+09 |
Report: SpaceGainsMonthly
For: G S2 APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.227718E+09 |
| February | 0.389025E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.195631E+09 |
| March | 0.418950E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.182654E+09 |
| April | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 538556.05 | 0.165400E+09 |
| May | 0.424935E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27903.16 | 0.140464E+09 |
| June | 0.406980E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 281117.55 | 0.113101E+09 |
| July | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3054992.13 | 81523540.29 |
| August | 0.418950E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5944214.53 | 72442218.31 |
| September | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27830.59 | 65874823.23 |
| October | 0.430920E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.161896E+09 |
| November | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.176435E+09 |
| December | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.191291E+09 |
| Annual Sum or Average | 0.505732E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 9874614.00 | 0.177443E+10 |
| Minimum of Months | 0.389025E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65874823.23 |
| Maximum of Months | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5944214.53 | 0.227718E+09 |
Report: SpaceGainsMonthly
For: M SW APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.543904E+09 |
| February | 0.389025E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.473167E+09 |
| March | 0.418950E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.454475E+09 |
| April | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1262053.90 | 0.425891E+09 |
| May | 0.424935E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 62726.14 | 0.346887E+09 |
| June | 0.406980E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 654422.55 | 0.272561E+09 |
| July | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7218092.81 | 0.194886E+09 |
| August | 0.418950E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14065891.13 | 0.172868E+09 |
| September | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 63131.81 | 0.156844E+09 |
| October | 0.430920E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.381739E+09 |
| November | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.419501E+09 |
| December | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.458459E+09 |
| Annual Sum or Average | 0.505732E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 23326318.34 | 0.430118E+10 |
| Minimum of Months | 0.389025E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.156844E+09 |
| Maximum of Months | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14065891.13 | 0.543904E+09 |
Report: SpaceGainsMonthly
For: M NW APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.543076E+09 |
| February | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.465639E+09 |
| March | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.432257E+09 |
| April | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1324709.14 | 0.400979E+09 |
| May | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 62727.45 | 0.342519E+09 |
| June | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 654429.84 | 0.271692E+09 |
| July | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7218100.29 | 0.194707E+09 |
| August | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14065896.69 | 0.172600E+09 |
| September | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 63131.87 | 0.155008E+09 |
| October | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.357727E+09 |
| November | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.412389E+09 |
| December | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.454420E+09 |
| Annual Sum or Average | 0.512427E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 23388995.28 | 0.420301E+10 |
| Minimum of Months | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.155008E+09 |
| Maximum of Months | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14065896.69 | 0.543076E+09 |
Report: SpaceGainsMonthly
For: M SE APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.543792E+09 |
| February | 0.389025E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.472809E+09 |
| March | 0.418950E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.455059E+09 |
| April | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1262058.06 | 0.429311E+09 |
| May | 0.424935E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 62726.65 | 0.346655E+09 |
| June | 0.406980E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 654425.06 | 0.272714E+09 |
| July | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7218101.26 | 0.194785E+09 |
| August | 0.418950E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14065903.13 | 0.172784E+09 |
| September | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 63132.09 | 0.156517E+09 |
| October | 0.430920E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.382189E+09 |
| November | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.419644E+09 |
| December | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.458237E+09 |
| Annual Sum or Average | 0.505732E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 23326346.25 | 0.430450E+10 |
| Minimum of Months | 0.389025E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.156517E+09 |
| Maximum of Months | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14065903.13 | 0.543792E+09 |
Report: SpaceGainsMonthly
For: M NE APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.543077E+09 |
| February | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.465488E+09 |
| March | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.431412E+09 |
| April | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1313812.35 | 0.404636E+09 |
| May | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 62727.91 | 0.342824E+09 |
| June | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 654432.11 | 0.272079E+09 |
| July | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7218107.00 | 0.194591E+09 |
| August | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14065905.24 | 0.172544E+09 |
| September | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 63132.19 | 0.154340E+09 |
| October | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.357866E+09 |
| November | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.412313E+09 |
| December | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.454415E+09 |
| Annual Sum or Average | 0.512427E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 23378116.81 | 0.420558E+10 |
| Minimum of Months | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.154340E+09 |
| Maximum of Months | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14065905.24 | 0.543077E+09 |
Report: SpaceGainsMonthly
For: M N1 APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.327698E+09 |
| February | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.282184E+09 |
| March | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.263853E+09 |
| April | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 841133.62 | 0.248972E+09 |
| May | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 37836.30 | 0.211139E+09 |
| June | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 394738.53 | 0.165681E+09 |
| July | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4353782.32 | 0.117660E+09 |
| August | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8484199.49 | 0.104440E+09 |
| September | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 38079.86 | 94864225.13 |
| October | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.225344E+09 |
| November | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.252937E+09 |
| December | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.274118E+09 |
| Annual Sum or Average | 0.512427E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 14149770.13 | 0.256889E+10 |
| Minimum of Months | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94864225.13 |
| Maximum of Months | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8484199.49 | 0.327698E+09 |
Report: SpaceGainsMonthly
For: M N2 APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.327699E+09 |
| February | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.282179E+09 |
| March | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.263813E+09 |
| April | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 838490.89 | 0.249337E+09 |
| May | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 37836.31 | 0.211126E+09 |
| June | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 394738.54 | 0.165689E+09 |
| July | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4353782.40 | 0.117659E+09 |
| August | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8484199.57 | 0.104438E+09 |
| September | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 38079.86 | 94838761.02 |
| October | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.225361E+09 |
| November | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.252926E+09 |
| December | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.274118E+09 |
| Annual Sum or Average | 0.512427E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 14147127.58 | 0.256918E+10 |
| Minimum of Months | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94838761.02 |
| Maximum of Months | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8484199.57 | 0.327699E+09 |
Report: SpaceGainsMonthly
For: M S1 APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.329340E+09 |
| February | 0.389025E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.289869E+09 |
| March | 0.418950E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.285169E+09 |
| April | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 761241.82 | 0.266517E+09 |
| May | 0.424935E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 37835.30 | 0.213108E+09 |
| June | 0.406980E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 394733.74 | 0.165939E+09 |
| July | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4353776.32 | 0.117691E+09 |
| August | 0.418950E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8484195.26 | 0.104508E+09 |
| September | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 38079.71 | 95433787.76 |
| October | 0.430920E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.241643E+09 |
| November | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.260173E+09 |
| December | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.279142E+09 |
| Annual Sum or Average | 0.505732E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 14069862.15 | 0.264853E+10 |
| Minimum of Months | 0.389025E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 95433787.76 |
| Maximum of Months | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8484195.26 | 0.329340E+09 |
Report: SpaceGainsMonthly
For: M S2 APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.329338E+09 |
| February | 0.389025E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.289859E+09 |
| March | 0.418950E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.285242E+09 |
| April | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 761241.83 | 0.266720E+09 |
| May | 0.424935E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 37835.31 | 0.213077E+09 |
| June | 0.406980E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 394733.78 | 0.165937E+09 |
| July | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4353776.43 | 0.117691E+09 |
| August | 0.418950E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8484195.45 | 0.104507E+09 |
| September | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 38079.71 | 95425315.32 |
| October | 0.430920E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.241669E+09 |
| November | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.260182E+09 |
| December | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.279126E+09 |
| Annual Sum or Average | 0.505732E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 14069862.50 | 0.264877E+10 |
| Minimum of Months | 0.389025E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 95425315.32 |
| Maximum of Months | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8484195.45 | 0.329338E+09 |
Report: SpaceGainsMonthly
For: T SW APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.720943E+09 |
| February | 0.389025E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.625148E+09 |
| March | 0.418950E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.587634E+09 |
| April | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1633511.92 | 0.529978E+09 |
| May | 0.424935E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 73254.92 | 0.422511E+09 |
| June | 0.406980E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 825727.51 | 0.334302E+09 |
| July | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9389732.91 | 0.245771E+09 |
| August | 0.418950E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18352593.08 | 0.216751E+09 |
| September | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 75318.90 | 0.188693E+09 |
| October | 0.430920E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.468521E+09 |
| November | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.545220E+09 |
| December | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.607097E+09 |
| Annual Sum or Average | 0.505732E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 30350139.24 | 0.549257E+10 |
| Minimum of Months | 0.389025E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.188693E+09 |
| Maximum of Months | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18352593.08 | 0.720943E+09 |
Report: SpaceGainsMonthly
For: T NW APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.720163E+09 |
| February | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.616238E+09 |
| March | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.570654E+09 |
| April | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1633515.50 | 0.513663E+09 |
| May | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 73256.00 | 0.414871E+09 |
| June | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 825735.01 | 0.331650E+09 |
| July | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9389733.53 | 0.244641E+09 |
| August | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18352588.51 | 0.214669E+09 |
| September | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 75318.49 | 0.182102E+09 |
| October | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.445763E+09 |
| November | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.541174E+09 |
| December | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.602703E+09 |
| Annual Sum or Average | 0.512427E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 30350147.04 | 0.539829E+10 |
| Minimum of Months | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.182102E+09 |
| Maximum of Months | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18352588.51 | 0.720163E+09 |
Report: SpaceGainsMonthly
For: T SE APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.720750E+09 |
| February | 0.389025E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.624531E+09 |
| March | 0.418950E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.587918E+09 |
| April | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1633520.03 | 0.533151E+09 |
| May | 0.424935E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 73256.00 | 0.423653E+09 |
| June | 0.406980E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 825733.18 | 0.336678E+09 |
| July | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9389750.45 | 0.246075E+09 |
| August | 0.418950E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18352619.91 | 0.218018E+09 |
| September | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 75319.46 | 0.188024E+09 |
| October | 0.430920E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.469614E+09 |
| November | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.545282E+09 |
| December | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.606829E+09 |
| Annual Sum or Average | 0.505732E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 30350199.04 | 0.550052E+10 |
| Minimum of Months | 0.389025E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.188024E+09 |
| Maximum of Months | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18352619.91 | 0.720750E+09 |
Report: SpaceGainsMonthly
For: T NE APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.720163E+09 |
| February | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.615871E+09 |
| March | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.568662E+09 |
| April | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1633522.84 | 0.516339E+09 |
| May | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 73256.88 | 0.417193E+09 |
| June | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 825739.53 | 0.335033E+09 |
| July | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9389747.73 | 0.244876E+09 |
| August | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18352608.83 | 0.216270E+09 |
| September | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 75319.09 | 0.181774E+09 |
| October | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.444821E+09 |
| November | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.541046E+09 |
| December | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.602703E+09 |
| Annual Sum or Average | 0.512427E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 30350194.89 | 0.540475E+10 |
| Minimum of Months | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.181774E+09 |
| Maximum of Months | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18352608.83 | 0.720163E+09 |
Report: SpaceGainsMonthly
For: T N1 APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.434384E+09 |
| February | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.372038E+09 |
| March | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.343917E+09 |
| April | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 985302.26 | 0.311608E+09 |
| May | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 44187.18 | 0.254346E+09 |
| June | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 498066.70 | 0.205919E+09 |
| July | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5663657.73 | 0.151160E+09 |
| August | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11069825.87 | 0.133123E+09 |
| September | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 45430.64 | 0.113081E+09 |
| October | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.269615E+09 |
| November | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.327110E+09 |
| December | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.363535E+09 |
| Annual Sum or Average | 0.512427E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 18306470.39 | 0.327984E+10 |
| Minimum of Months | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113081E+09 |
| Maximum of Months | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11069825.87 | 0.434384E+09 |
Report: SpaceGainsMonthly
For: T N2 APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.434384E+09 |
| February | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.372022E+09 |
| March | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.343861E+09 |
| April | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 985302.26 | 0.311840E+09 |
| May | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 44187.18 | 0.254480E+09 |
| June | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 498066.84 | 0.206060E+09 |
| July | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5663653.90 | 0.151102E+09 |
| August | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11069826.32 | 0.133160E+09 |
| September | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 45430.65 | 0.112997E+09 |
| October | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.269594E+09 |
| November | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.327099E+09 |
| December | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.363535E+09 |
| Annual Sum or Average | 0.512427E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 18306467.15 | 0.328013E+10 |
| Minimum of Months | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112997E+09 |
| Maximum of Months | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11069826.32 | 0.434384E+09 |
Report: SpaceGainsMonthly
For: T S1 APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.435354E+09 |
| February | 0.389025E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.379346E+09 |
| March | 0.418950E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.358081E+09 |
| April | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 985296.68 | 0.325221E+09 |
| May | 0.424935E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 44186.20 | 0.260059E+09 |
| June | 0.406980E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 498061.63 | 0.207437E+09 |
| July | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5663654.85 | 0.151767E+09 |
| August | 0.418950E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11069828.90 | 0.134241E+09 |
| September | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 45430.73 | 0.117669E+09 |
| October | 0.430920E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.288222E+09 |
| November | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.330657E+09 |
| December | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.367399E+09 |
| Annual Sum or Average | 0.505732E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 18306458.99 | 0.335545E+10 |
| Minimum of Months | 0.389025E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.117669E+09 |
| Maximum of Months | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11069828.90 | 0.435354E+09 |
Report: SpaceGainsMonthly
For: T S2 APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.435350E+09 |
| February | 0.389025E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.379336E+09 |
| March | 0.418950E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.358122E+09 |
| April | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 985296.92 | 0.325390E+09 |
| May | 0.424935E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 44186.23 | 0.260035E+09 |
| June | 0.406980E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 498061.53 | 0.207480E+09 |
| July | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5663655.33 | 0.151716E+09 |
| August | 0.418950E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11069829.59 | 0.134253E+09 |
| September | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 45430.75 | 0.117590E+09 |
| October | 0.430920E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.288247E+09 |
| November | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.330664E+09 |
| December | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.367387E+09 |
| Annual Sum or Average | 0.505732E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 18306460.35 | 0.335557E+10 |
| Minimum of Months | 0.389025E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.117590E+09 |
| Maximum of Months | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11069829.59 | 0.435350E+09 |
Report: SpaceGainsMonthly
For: T CORRIDOR
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.727675E+09 | 0.992689E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120678E+09 |
| February | 0.657255E+09 | 0.896622E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106021E+09 |
| March | 0.727675E+09 | 0.992689E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102995E+09 |
| April | 0.704201E+09 | 0.960667E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83578.18 | 97220147.03 |
| May | 0.727675E+09 | 0.992689E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81764095.53 |
| June | 0.704201E+09 | 0.960667E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69053235.41 |
| July | 0.727675E+09 | 0.992689E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 279476.67 | 53844152.17 |
| August | 0.727675E+09 | 0.992689E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 858420.57 | 47968196.44 |
| September | 0.704201E+09 | 0.960667E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37729418.07 |
| October | 0.727675E+09 | 0.992689E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84197028.01 |
| November | 0.704201E+09 | 0.960667E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93939806.09 |
| December | 0.727675E+09 | 0.992689E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101492E+09 |
| Annual Sum or Average | 0.856778E+10 | 0.116881E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1221475.42 | 0.996903E+09 |
| Minimum of Months | 0.657255E+09 | 0.896622E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37729418.07 |
| Maximum of Months | 0.727675E+09 | 0.992689E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 858420.57 | 0.120678E+09 |
Report: SpaceGainsMonthly
For: G CORRIDOR
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.727675E+09 | 0.992689E+09 | 0.299778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.332558E+10 |
| February | 0.657255E+09 | 0.896622E+09 | 0.270767E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.275626E+10 |
| March | 0.727675E+09 | 0.992689E+09 | 0.299778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.262560E+10 |
| April | 0.704201E+09 | 0.960667E+09 | 0.290107E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15924468.58 | 0.214401E+10 |
| May | 0.727675E+09 | 0.992689E+09 | 0.299778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.201317E+10 |
| June | 0.704201E+09 | 0.960667E+09 | 0.290107E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 241823.55 | 0.163721E+10 |
| July | 0.727675E+09 | 0.992689E+09 | 0.299778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15224614.13 | 0.138891E+10 |
| August | 0.727675E+09 | 0.992689E+09 | 0.299778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 50971346.73 | 0.124696E+10 |
| September | 0.704201E+09 | 0.960667E+09 | 0.290107E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.180888E+10 |
| October | 0.727675E+09 | 0.992689E+09 | 0.299778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.231859E+10 |
| November | 0.704201E+09 | 0.960667E+09 | 0.290107E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.269327E+10 |
| December | 0.727675E+09 | 0.992689E+09 | 0.299778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.316640E+10 |
| Annual Sum or Average | 0.856778E+10 | 0.116881E+11 | 0.352964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 82362252.98 | 0.271248E+11 |
| Minimum of Months | 0.657255E+09 | 0.896622E+09 | 0.270767E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124696E+10 |
| Maximum of Months | 0.727675E+09 | 0.992689E+09 | 0.299778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 50971346.73 | 0.332558E+10 |
Report: SpaceGainsMonthly
For: M CORRIDOR
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.727675E+09 | 0.992689E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99332401.06 |
| February | 0.657255E+09 | 0.896622E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86998688.53 |
| March | 0.727675E+09 | 0.992689E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85517020.87 |
| April | 0.704201E+09 | 0.960667E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 140067.73 | 81574829.58 |
| May | 0.727675E+09 | 0.992689E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69558557.42 |
| June | 0.704201E+09 | 0.960667E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1523.43 | 57314569.48 |
| July | 0.727675E+09 | 0.992689E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 351471.71 | 43240158.09 |
| August | 0.727675E+09 | 0.992689E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 922271.81 | 39032672.65 |
| September | 0.704201E+09 | 0.960667E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32435384.91 |
| October | 0.727675E+09 | 0.992689E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73904346.81 |
| November | 0.704201E+09 | 0.960667E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79114493.28 |
| December | 0.727675E+09 | 0.992689E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83824163.78 |
| Annual Sum or Average | 0.856778E+10 | 0.116881E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1415334.68 | 0.831847E+09 |
| Minimum of Months | 0.657255E+09 | 0.896622E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32435384.91 |
| Maximum of Months | 0.727675E+09 | 0.992689E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 922271.81 | 99332401.06 |
Report: PeakSpaceGainsMonthly
For: G SW APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 393.84 | 28-JAN-08:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 354.66 | 16-FEB-04:00 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 309.05 | 29-MAR-05:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 48.24 | 01-APR-16:00 | 307.45 | 10-APR-21:00 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.51 | 05-MAY-16:00 | 295.83 | 17-MAY-19:00 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.42 | 28-JUN-16:00 | 310.12 | 13-JUN-03:00 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 65.47 | 23-JUL-16:00 | 163.79 | 02-JUL-04:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 81.22 | 08-AUG-17:00 | 222.78 | 11-AUG-04:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.58 | 14-SEP-17:00 | 178.66 | 30-SEP-07:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 303.21 | 31-OCT-20:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 389.54 | 29-NOV-21:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 332.00 | 26-DEC-14:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 163.79 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 81.22 | 393.84 |
Report: PeakSpaceGainsMonthly
For: G NW APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 393.84 | 28-JAN-08:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 354.66 | 16-FEB-04:00 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 309.05 | 29-MAR-05:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 61.99 | 01-APR-16:00 | 307.45 | 10-APR-21:00 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.51 | 05-MAY-16:00 | 288.06 | 17-MAY-19:00 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.42 | 28-JUN-16:00 | 304.45 | 13-JUN-03:00 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 65.47 | 23-JUL-16:00 | 161.42 | 02-JUL-04:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 81.22 | 08-AUG-17:00 | 220.90 | 11-AUG-04:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.58 | 14-SEP-17:00 | 167.26 | 30-SEP-07:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 303.21 | 31-OCT-20:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 389.54 | 29-NOV-21:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 332.00 | 26-DEC-14:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 161.42 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 81.22 | 393.84 |
Report: PeakSpaceGainsMonthly
For: OFFICE
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 451.21 | 03-JAN-08:09 | 582.92 | 03-JAN-08:09 | 588.62 | 03-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 317.84 | 12-JAN-24:00 |
| February | 451.21 | 01-FEB-08:09 | 582.92 | 01-FEB-08:09 | 588.62 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 335.43 | 16-FEB-15:00 |
| March | 451.21 | 01-MAR-08:09 | 582.92 | 01-MAR-08:09 | 588.62 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 299.44 | 22-MAR-09:00 |
| April | 451.21 | 03-APR-07:10 | 582.92 | 03-APR-07:10 | 588.62 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 41.83 | 01-APR-16:00 | 314.97 | 07-APR-24:00 |
| May | 451.21 | 01-MAY-07:10 | 582.92 | 01-MAY-07:10 | 588.62 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 05-MAY-16:00 | 310.32 | 17-MAY-19:00 |
| June | 451.21 | 01-JUN-07:10 | 582.92 | 01-JUN-07:10 | 588.62 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.41 | 28-JUN-16:00 | 344.45 | 13-JUN-03:00 |
| July | 451.21 | 03-JUL-07:10 | 582.92 | 03-JUL-07:10 | 588.62 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 51.73 | 24-JUL-14:00 | 176.61 | 02-JUL-04:00 |
| August | 451.21 | 01-AUG-07:10 | 582.92 | 01-AUG-07:10 | 588.62 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 57.65 | 08-AUG-16:00 | 259.89 | 11-AUG-04:00 |
| September | 451.21 | 01-SEP-07:10 | 582.92 | 01-SEP-07:10 | 588.62 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.63 | 12-SEP-14:10 | 188.70 | 30-SEP-07:00 |
| October | 451.21 | 02-OCT-07:10 | 582.92 | 02-OCT-07:10 | 588.62 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 296.82 | 31-OCT-20:00 |
| November | 451.21 | 01-NOV-07:10 | 582.92 | 01-NOV-07:10 | 588.62 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 360.91 | 29-NOV-12:00 |
| December | 451.21 | 01-DEC-08:09 | 582.92 | 01-DEC-08:09 | 588.62 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 332.00 | 26-DEC-14:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 451.21 | 582.92 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 176.61 | |||||
| Maximum of Months | 451.21 | 582.92 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 57.65 | 360.91 |
Report: PeakSpaceGainsMonthly
For: G NE APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 393.84 | 28-JAN-08:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 354.66 | 16-FEB-04:00 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 309.05 | 29-MAR-05:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 66.01 | 01-APR-16:00 | 307.45 | 10-APR-21:00 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.51 | 05-MAY-16:00 | 287.48 | 17-MAY-19:00 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.42 | 28-JUN-16:00 | 310.32 | 13-JUN-03:00 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 65.47 | 23-JUL-16:00 | 160.00 | 02-JUL-04:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 81.22 | 08-AUG-17:00 | 219.24 | 11-AUG-04:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.58 | 14-SEP-17:00 | 163.88 | 30-SEP-07:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 303.21 | 31-OCT-20:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 389.54 | 29-NOV-21:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 332.00 | 26-DEC-14:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 160.00 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 81.22 | 393.84 |
Report: PeakSpaceGainsMonthly
For: G N1 APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 237.55 | 28-JAN-08:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 213.92 | 16-FEB-04:00 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 186.41 | 29-MAR-05:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 40.87 | 01-APR-16:00 | 185.45 | 10-APR-21:00 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.32 | 05-MAY-16:00 | 182.31 | 17-MAY-19:00 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.31 | 28-JUN-16:00 | 194.99 | 13-JUN-03:00 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 39.49 | 23-JUL-16:00 | 100.98 | 02-JUL-04:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 48.99 | 08-AUG-17:00 | 134.18 | 11-AUG-04:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.97 | 14-SEP-17:00 | 105.98 | 30-SEP-07:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 182.89 | 31-OCT-20:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 234.96 | 29-NOV-21:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 200.26 | 26-DEC-14:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 100.98 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 48.99 | 237.55 |
Report: PeakSpaceGainsMonthly
For: G N2 APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 237.55 | 28-JAN-08:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 213.92 | 16-FEB-04:00 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 186.41 | 29-MAR-05:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 40.85 | 01-APR-16:00 | 185.45 | 10-APR-21:00 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.32 | 05-MAY-16:00 | 182.32 | 17-MAY-19:00 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.31 | 28-JUN-16:00 | 195.50 | 13-JUN-03:00 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 39.49 | 23-JUL-16:00 | 100.91 | 02-JUL-04:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 48.99 | 08-AUG-17:00 | 134.19 | 11-AUG-04:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.97 | 14-SEP-17:00 | 105.71 | 30-SEP-07:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 182.89 | 31-OCT-20:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 234.96 | 29-NOV-21:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 200.26 | 26-DEC-14:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 100.91 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 48.99 | 237.55 |
Report: PeakSpaceGainsMonthly
For: G S1 APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 237.55 | 28-JAN-08:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 213.92 | 16-FEB-04:00 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 186.41 | 29-MAR-05:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 29.10 | 01-APR-16:00 | 185.45 | 10-APR-21:00 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.32 | 05-MAY-16:00 | 188.01 | 17-MAY-19:00 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.31 | 28-JUN-16:00 | 197.76 | 13-JUN-03:00 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 39.49 | 23-JUL-16:00 | 102.38 | 02-JUL-04:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 48.99 | 08-AUG-17:00 | 134.38 | 11-AUG-04:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.97 | 14-SEP-17:00 | 113.34 | 30-SEP-07:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 185.07 | 31-OCT-20:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 234.96 | 29-NOV-21:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 200.26 | 26-DEC-14:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 102.38 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 48.99 | 237.55 |
Report: PeakSpaceGainsMonthly
For: G S2 APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 237.55 | 28-JAN-08:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 213.92 | 16-FEB-04:00 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 186.41 | 29-MAR-05:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 29.10 | 01-APR-16:00 | 187.04 | 07-APR-24:00 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.32 | 05-MAY-16:00 | 189.30 | 17-MAY-19:00 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.31 | 28-JUN-16:00 | 199.34 | 13-JUN-03:00 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 39.49 | 23-JUL-16:00 | 102.92 | 02-JUL-04:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 48.99 | 08-AUG-17:00 | 134.38 | 11-AUG-04:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.97 | 14-SEP-17:00 | 114.04 | 30-SEP-07:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 185.99 | 31-OCT-20:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 234.96 | 29-NOV-21:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 200.26 | 26-DEC-14:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 102.92 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 48.99 | 237.55 |
Report: PeakSpaceGainsMonthly
For: M SW APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 566.73 | 28-JAN-08:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 510.26 | 16-FEB-04:00 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 445.56 | 28-MAR-24:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 68.89 | 01-APR-16:00 | 475.26 | 07-APR-24:00 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.76 | 05-MAY-16:00 | 448.34 | 17-MAY-19:00 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 29.06 | 28-JUN-16:00 | 461.13 | 13-JUN-03:00 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 93.60 | 23-JUL-16:00 | 243.66 | 02-JUL-04:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 116.32 | 08-AUG-17:00 | 320.70 | 11-AUG-04:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.26 | 14-SEP-17:00 | 269.48 | 30-SEP-07:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 436.36 | 31-OCT-20:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 560.49 | 29-NOV-21:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 477.59 | 26-DEC-14:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 243.66 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 116.32 | 566.73 |
Report: PeakSpaceGainsMonthly
For: M NW APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 566.73 | 28-JAN-08:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 510.26 | 16-FEB-04:00 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 444.66 | 29-MAR-05:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 68.89 | 01-APR-16:00 | 447.57 | 07-APR-24:00 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.76 | 05-MAY-16:00 | 448.62 | 17-MAY-19:00 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 29.06 | 28-JUN-16:00 | 460.72 | 13-JUN-03:00 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 93.60 | 23-JUL-16:00 | 241.55 | 02-JUL-04:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 116.32 | 08-AUG-17:00 | 318.55 | 11-AUG-04:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.26 | 14-SEP-17:00 | 261.03 | 30-SEP-07:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 436.36 | 31-OCT-20:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 560.49 | 29-NOV-21:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 477.59 | 26-DEC-14:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 241.55 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 116.32 | 566.73 |
Report: PeakSpaceGainsMonthly
For: M SE APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 566.73 | 28-JAN-08:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 510.26 | 16-FEB-04:00 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 450.13 | 28-MAR-24:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 68.89 | 01-APR-16:00 | 484.43 | 07-APR-24:00 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.76 | 05-MAY-16:00 | 447.04 | 17-MAY-19:00 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 29.06 | 28-JUN-16:00 | 463.02 | 13-JUN-03:00 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 93.60 | 23-JUL-16:00 | 242.11 | 02-JUL-04:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 116.32 | 08-AUG-17:00 | 320.54 | 11-AUG-04:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.26 | 14-SEP-17:00 | 267.10 | 30-SEP-07:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 436.36 | 31-OCT-20:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 560.49 | 29-NOV-21:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 477.59 | 26-DEC-14:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 242.11 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 116.32 | 566.73 |
Report: PeakSpaceGainsMonthly
For: M NE APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 566.73 | 28-JAN-08:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 510.26 | 16-FEB-04:00 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 444.66 | 29-MAR-05:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 68.90 | 01-APR-16:00 | 461.37 | 07-APR-24:00 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.76 | 05-MAY-16:00 | 447.26 | 17-MAY-19:00 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 29.06 | 28-JUN-16:00 | 462.68 | 13-JUN-03:00 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 93.60 | 23-JUL-16:00 | 239.83 | 02-JUL-04:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 116.32 | 08-AUG-17:00 | 315.88 | 11-AUG-04:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.26 | 14-SEP-17:00 | 257.69 | 30-SEP-07:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 436.36 | 31-OCT-20:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 560.49 | 29-NOV-21:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 477.59 | 26-DEC-14:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 239.83 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 116.32 | 566.73 |
Report: PeakSpaceGainsMonthly
For: M N1 APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 341.84 | 28-JAN-08:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 307.78 | 16-FEB-04:00 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 268.21 | 29-MAR-05:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 46.04 | 01-APR-16:00 | 287.01 | 07-APR-24:00 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.68 | 05-MAY-16:00 | 282.87 | 17-MAY-19:00 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.53 | 28-JUN-16:00 | 290.55 | 13-JUN-03:00 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 56.46 | 23-JUL-16:00 | 149.78 | 02-JUL-04:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 70.16 | 08-AUG-17:00 | 193.44 | 11-AUG-04:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.59 | 14-SEP-17:00 | 164.69 | 30-SEP-07:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 263.20 | 31-OCT-20:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 338.07 | 29-NOV-21:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 288.07 | 26-DEC-14:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 149.78 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 70.16 | 341.84 |
Report: PeakSpaceGainsMonthly
For: M N2 APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 341.84 | 28-JAN-08:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 307.78 | 16-FEB-04:00 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 268.21 | 29-MAR-05:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 45.92 | 01-APR-16:00 | 288.26 | 07-APR-24:00 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.68 | 05-MAY-16:00 | 282.80 | 17-MAY-19:00 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.53 | 28-JUN-16:00 | 290.66 | 13-JUN-03:00 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 56.46 | 23-JUL-16:00 | 149.70 | 02-JUL-04:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 70.16 | 08-AUG-17:00 | 193.44 | 11-AUG-04:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.59 | 14-SEP-17:00 | 164.46 | 30-SEP-07:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 263.20 | 31-OCT-20:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 338.07 | 29-NOV-21:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 288.07 | 26-DEC-14:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 149.70 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 70.16 | 341.84 |
Report: PeakSpaceGainsMonthly
For: M S1 APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 341.84 | 28-JAN-08:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 307.78 | 16-FEB-04:00 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 287.03 | 28-MAR-24:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 41.55 | 01-APR-16:00 | 302.47 | 07-APR-24:00 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.68 | 05-MAY-16:00 | 282.62 | 17-MAY-19:00 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.53 | 28-JUN-16:00 | 290.84 | 13-JUN-03:00 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 56.46 | 23-JUL-16:00 | 151.01 | 02-JUL-04:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 70.16 | 08-AUG-17:00 | 193.44 | 11-AUG-04:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.59 | 14-SEP-17:00 | 169.45 | 30-SEP-07:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 277.68 | 31-OCT-20:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 338.07 | 29-NOV-21:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 288.07 | 26-DEC-14:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 151.01 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 70.16 | 341.84 |
Report: PeakSpaceGainsMonthly
For: M S2 APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 341.84 | 28-JAN-08:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 307.78 | 16-FEB-04:00 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 287.49 | 28-MAR-24:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 41.55 | 01-APR-16:00 | 303.11 | 07-APR-24:00 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.68 | 05-MAY-16:00 | 282.55 | 17-MAY-19:00 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.53 | 28-JUN-16:00 | 290.94 | 13-JUN-03:00 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 56.46 | 23-JUL-16:00 | 150.95 | 02-JUL-04:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 70.16 | 08-AUG-17:00 | 193.44 | 11-AUG-04:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.59 | 14-SEP-17:00 | 169.32 | 30-SEP-07:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 277.59 | 31-OCT-20:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 338.07 | 29-NOV-21:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 288.07 | 26-DEC-14:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 150.95 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 70.16 | 341.84 |
Report: PeakSpaceGainsMonthly
For: T SW APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 751.64 | 28-JAN-08:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 676.53 | 16-FEB-04:00 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 589.59 | 29-MAR-05:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 89.99 | 01-APR-16:00 | 586.70 | 10-APR-21:00 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.84 | 05-MAY-16:00 | 526.13 | 17-MAY-19:00 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 37.71 | 28-JUN-16:00 | 507.27 | 13-JUN-03:00 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 122.51 | 23-JUL-16:00 | 274.45 | 02-JUL-04:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 152.81 | 08-AUG-17:00 | 386.40 | 11-AUG-04:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.76 | 14-SEP-17:00 | 288.68 | 30-SEP-07:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 578.86 | 31-OCT-20:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 743.24 | 29-NOV-21:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 633.01 | 26-DEC-14:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 274.45 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 152.81 | 751.64 |
Report: PeakSpaceGainsMonthly
For: T NW APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 751.64 | 28-JAN-08:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 676.53 | 16-FEB-04:00 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 589.59 | 29-MAR-05:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 89.99 | 01-APR-16:00 | 586.70 | 10-APR-21:00 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.84 | 05-MAY-16:00 | 526.13 | 17-MAY-19:00 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 37.71 | 28-JUN-16:00 | 508.53 | 13-JUN-03:00 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 122.51 | 23-JUL-16:00 | 271.48 | 02-JUL-04:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 152.81 | 08-AUG-17:00 | 381.38 | 11-AUG-04:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.76 | 14-SEP-17:00 | 288.68 | 30-SEP-07:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 578.86 | 31-OCT-20:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 743.24 | 29-NOV-21:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 633.01 | 26-DEC-14:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.48 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 152.81 | 751.64 |
Report: PeakSpaceGainsMonthly
For: T SE APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 751.64 | 28-JAN-08:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 676.53 | 16-FEB-04:00 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 589.59 | 29-MAR-05:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 89.99 | 01-APR-16:00 | 586.70 | 10-APR-21:00 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.84 | 05-MAY-16:00 | 526.13 | 17-MAY-19:00 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 37.71 | 28-JUN-16:00 | 509.41 | 13-JUN-03:00 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 122.51 | 23-JUL-16:00 | 272.24 | 02-JUL-04:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 152.81 | 08-AUG-17:00 | 381.62 | 11-AUG-04:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.76 | 14-SEP-17:00 | 288.68 | 30-SEP-07:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 578.86 | 31-OCT-20:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 743.24 | 29-NOV-21:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 633.01 | 26-DEC-14:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 272.24 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 152.81 | 751.64 |
Report: PeakSpaceGainsMonthly
For: T NE APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 751.64 | 28-JAN-08:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 676.53 | 16-FEB-04:00 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 589.59 | 29-MAR-05:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 89.99 | 01-APR-16:00 | 586.70 | 10-APR-21:00 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.84 | 05-MAY-16:00 | 526.13 | 17-MAY-19:00 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 37.71 | 28-JUN-16:00 | 510.56 | 13-JUN-03:00 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 122.51 | 23-JUL-16:00 | 268.64 | 02-JUL-04:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 152.81 | 08-AUG-17:00 | 376.16 | 11-AUG-04:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.76 | 14-SEP-17:00 | 288.68 | 30-SEP-07:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 578.86 | 31-OCT-20:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 743.24 | 29-NOV-21:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 633.01 | 26-DEC-14:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 268.64 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 152.81 | 751.64 |
Report: PeakSpaceGainsMonthly
For: T N1 APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 453.37 | 28-JAN-08:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 408.06 | 16-FEB-04:00 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 355.63 | 29-MAR-05:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 54.28 | 01-APR-16:00 | 353.88 | 10-APR-21:00 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.94 | 05-MAY-16:00 | 318.05 | 17-MAY-19:00 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.75 | 28-JUN-16:00 | 336.23 | 13-JUN-03:00 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 73.90 | 23-JUL-16:00 | 175.14 | 02-JUL-04:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 92.17 | 08-AUG-17:00 | 239.58 | 11-AUG-04:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.09 | 14-SEP-17:00 | 178.82 | 30-SEP-07:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 349.15 | 31-OCT-20:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 448.30 | 29-NOV-21:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 381.82 | 26-DEC-14:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 175.14 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 92.17 | 453.37 |
Report: PeakSpaceGainsMonthly
For: T N2 APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 453.37 | 28-JAN-08:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 408.06 | 16-FEB-04:00 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 355.63 | 29-MAR-05:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 54.28 | 01-APR-16:00 | 353.88 | 10-APR-21:00 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.94 | 05-MAY-16:00 | 317.96 | 17-MAY-19:00 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.75 | 28-JUN-16:00 | 336.43 | 13-JUN-03:00 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 73.90 | 23-JUL-16:00 | 174.90 | 02-JUL-04:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 92.17 | 08-AUG-17:00 | 239.29 | 11-AUG-04:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.09 | 14-SEP-17:00 | 178.38 | 30-SEP-07:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 349.15 | 31-OCT-20:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 448.30 | 29-NOV-21:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 381.82 | 26-DEC-14:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 174.90 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 92.17 | 453.37 |
Report: PeakSpaceGainsMonthly
For: T S1 APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 453.37 | 28-JAN-08:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 408.06 | 16-FEB-04:00 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 355.63 | 29-MAR-05:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 54.28 | 01-APR-16:00 | 353.88 | 10-APR-21:00 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.94 | 05-MAY-16:00 | 317.35 | 17-MAY-19:00 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.75 | 28-JUN-16:00 | 335.44 | 13-JUN-03:00 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 73.90 | 23-JUL-16:00 | 177.12 | 02-JUL-04:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 92.17 | 08-AUG-17:00 | 243.09 | 11-AUG-04:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.09 | 14-SEP-17:00 | 186.63 | 30-SEP-07:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 349.15 | 31-OCT-20:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 448.30 | 29-NOV-21:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 381.82 | 26-DEC-14:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 177.12 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 92.17 | 453.37 |
Report: PeakSpaceGainsMonthly
For: T S2 APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 453.37 | 28-JAN-08:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 408.06 | 16-FEB-04:00 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 355.63 | 29-MAR-05:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 54.28 | 01-APR-16:00 | 354.55 | 07-APR-24:00 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.94 | 05-MAY-16:00 | 317.35 | 17-MAY-19:00 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.75 | 28-JUN-16:00 | 335.66 | 13-JUN-03:00 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 73.90 | 23-JUL-16:00 | 176.96 | 02-JUL-04:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 92.17 | 08-AUG-17:00 | 242.83 | 11-AUG-04:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.09 | 14-SEP-17:00 | 186.34 | 30-SEP-07:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 349.15 | 31-OCT-20:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 448.30 | 29-NOV-21:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 381.82 | 26-DEC-14:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 176.96 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 92.17 | 453.37 |
Report: PeakSpaceGainsMonthly
For: T CORRIDOR
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 397.10 | 01-JAN-00:10 | 370.63 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 124.33 | 28-JAN-08:00 |
| February | 397.10 | 01-FEB-00:10 | 370.63 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 112.75 | 16-FEB-04:00 |
| March | 397.10 | 01-MAR-00:10 | 370.63 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 105.34 | 28-MAR-24:00 |
| April | 397.10 | 01-APR-00:10 | 370.63 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.88 | 01-APR-16:00 | 112.15 | 07-APR-24:00 |
| May | 397.10 | 01-MAY-00:10 | 370.63 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 98.51 | 17-MAY-19:00 |
| June | 397.10 | 01-JUN-00:10 | 370.63 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 110.98 | 13-JUN-03:00 |
| July | 397.10 | 01-JUL-00:10 | 370.63 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.61 | 24-JUL-14:20 | 57.22 | 02-JUL-04:00 |
| August | 397.10 | 01-AUG-00:10 | 370.63 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.93 | 08-AUG-17:00 | 79.84 | 11-AUG-04:00 |
| September | 397.10 | 01-SEP-00:10 | 370.63 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 57.90 | 30-SEP-07:00 |
| October | 397.10 | 01-OCT-00:10 | 370.63 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 100.12 | 31-OCT-20:00 |
| November | 397.10 | 01-NOV-00:10 | 370.63 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 122.51 | 29-NOV-21:00 |
| December | 397.10 | 01-DEC-00:10 | 370.63 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 104.67 | 14-DEC-13:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
| Minimum of Months | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.22 | ||||
| Maximum of Months | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.93 | 124.33 |
Report: PeakSpaceGainsMonthly
For: G CORRIDOR
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 397.10 | 01-JAN-00:10 | 370.63 | 01-JAN-00:10 | 208.40 | 01-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 13288.84 | 08-JAN-07:01 |
| February | 397.10 | 01-FEB-00:10 | 370.63 | 01-FEB-00:10 | 208.40 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 13729.27 | 19-FEB-07:01 |
| March | 397.10 | 01-MAR-00:10 | 370.63 | 01-MAR-00:10 | 208.40 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 12055.06 | 01-MAR-07:01 |
| April | 397.10 | 01-APR-00:10 | 370.63 | 01-APR-00:10 | 208.40 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2150.27 | 01-APR-16:03 | 10233.76 | 19-APR-06:01 |
| May | 397.10 | 01-MAY-00:10 | 370.63 | 01-MAY-00:10 | 208.40 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 9394.34 | 11-MAY-06:01 |
| June | 397.10 | 01-JUN-00:10 | 370.63 | 01-JUN-00:10 | 208.40 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 119.26 | 28-JUN-17:00 | 7512.39 | 15-JUN-06:01 |
| July | 397.10 | 01-JUL-00:10 | 370.63 | 01-JUL-00:10 | 208.40 | 01-JUL-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1022.07 | 31-JUL-16:02 | 6875.10 | 04-JUL-06:01 |
| August | 397.10 | 01-AUG-00:10 | 370.63 | 01-AUG-00:10 | 208.40 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2316.03 | 29-AUG-16:02 | 7786.74 | 01-AUG-06:01 |
| September | 397.10 | 01-SEP-00:10 | 370.63 | 01-SEP-00:10 | 208.40 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 8262.59 | 27-SEP-06:01 |
| October | 397.10 | 01-OCT-00:10 | 370.63 | 01-OCT-00:10 | 208.40 | 01-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 9028.76 | 13-OCT-06:01 |
| November | 397.10 | 01-NOV-00:10 | 370.63 | 01-NOV-00:10 | 208.40 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 11774.68 | 11-NOV-07:01 |
| December | 397.10 | 01-DEC-00:10 | 370.63 | 01-DEC-00:10 | 208.40 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 11997.67 | 26-DEC-07:01 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 397.10 | 370.63 | 208.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6875.10 | |||||
| Maximum of Months | 397.10 | 370.63 | 208.40 | 0.00 | 0.00 | 0.00 | 0.00 | 2316.03 | 13729.27 |
Report: PeakSpaceGainsMonthly
For: M CORRIDOR
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 397.10 | 01-JAN-00:10 | 370.63 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 102.95 | 28-JAN-08:00 |
| February | 397.10 | 01-FEB-00:10 | 370.63 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 92.15 | 16-FEB-04:00 |
| March | 397.10 | 01-MAR-00:10 | 370.63 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 87.14 | 28-MAR-24:00 |
| April | 397.10 | 01-APR-00:10 | 370.63 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.26 | 01-APR-16:00 | 93.83 | 07-APR-24:00 |
| May | 397.10 | 01-MAY-00:10 | 370.63 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 88.22 | 17-MAY-19:00 |
| June | 397.10 | 01-JUN-00:10 | 370.63 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.68 | 28-JUN-17:00 | 95.32 | 13-JUN-03:00 |
| July | 397.10 | 01-JUL-00:10 | 370.63 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.31 | 24-JUL-14:10 | 48.89 | 02-JUL-04:00 |
| August | 397.10 | 01-AUG-00:10 | 370.63 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.80 | 08-AUG-17:00 | 64.55 | 11-AUG-04:00 |
| September | 397.10 | 01-SEP-00:10 | 370.63 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 53.08 | 30-SEP-07:00 |
| October | 397.10 | 01-OCT-00:10 | 370.63 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 83.93 | 31-OCT-20:00 |
| November | 397.10 | 01-NOV-00:10 | 370.63 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 101.22 | 29-NOV-21:00 |
| December | 397.10 | 01-DEC-00:10 | 370.63 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 88.40 | 14-DEC-13:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
| Minimum of Months | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.89 | ||||
| Maximum of Months | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.26 | 102.95 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: G SW APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 475.36 | 08-JAN-14:20 | 118.75 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 100.41 |
| February | 517.96 | 09-FEB-17:25 | 0.00 | 173.60 | 1177.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 141.48 |
| March | 505.63 | 01-MAR-22:50 | 237.50 | 52.08 | 417.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.05 |
| April | 1068.98 | 27-APR-16:07 | 0.00 | 260.40 | 1765.87 | 0.00 | 0.00 | 0.00 | 0.00 | 24.35 | 0.00 |
| May | 1400.35 | 15-MAY-16:03 | 0.00 | 347.20 | 2354.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.10 |
| June | 1550.67 | 28-JUN-16:27 | 0.00 | 260.40 | 1765.87 | 0.00 | 0.00 | 0.00 | 0.00 | 19.51 | 0.00 |
| July | 1912.96 | 31-JUL-17:17 | 712.50 | 351.55 | 1765.87 | 0.00 | 0.00 | 0.00 | 0.00 | 45.15 | 0.00 |
| August | 2213.89 | 10-AUG-17:20 | 712.50 | 351.55 | 1765.87 | 0.00 | 0.00 | 0.00 | 0.00 | 39.78 | 0.00 |
| September | 1978.44 | 11-SEP-16:04 | 0.00 | 434.00 | 2943.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.89 |
| October | 1556.78 | 04-OCT-16:08 | 0.00 | 347.20 | 2354.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.84 |
| November | 521.02 | 11-NOV-19:10 | 237.50 | 138.88 | 547.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.51 |
| December | 558.59 | 06-DEC-16:20 | 0.00 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94.82 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 475.36 | 0.00 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 2213.89 | 712.50 | 434.00 | 2943.11 | 0.00 | 0.00 | 0.00 | 0.00 | 45.15 | 141.48 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: G NW APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 4.35 | 11-JAN-20:00 | 206.62 | 138.88 | 547.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 95.07 |
| February | 321.71 | 25-FEB-19:50 | 206.62 | 138.88 | 547.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94.01 |
| March | 371.53 | 30-MAR-19:50 | 206.62 | 138.88 | 523.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.94 |
| April | 393.29 | 29-APR-05:00 | 237.50 | 56.42 | 253.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.71 |
| May | 786.61 | 15-MAY-16:30 | 247.00 | 173.60 | 1177.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.98 | 0.00 |
| June | 1300.55 | 28-JUN-18:00 | 206.62 | 117.18 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 12.18 | 0.00 |
| July | 1580.84 | 24-JUL-18:00 | 206.62 | 117.18 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 47.02 | 0.00 |
| August | 1723.41 | 10-AUG-18:00 | 206.62 | 117.18 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 35.95 | 0.00 |
| September | 1159.27 | 14-SEP-16:30 | 247.00 | 173.60 | 1177.25 | 0.00 | 0.00 | 0.00 | 0.00 | 4.23 | 0.00 |
| October | 449.02 | 12-OCT-07:00 | 201.88 | 56.42 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.22 |
| November | 324.11 | 05-NOV-20:00 | 206.62 | 138.88 | 523.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 224.83 |
| December | 76.29 | 10-DEC-15:10 | 59.38 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.41 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 4.35 | 59.38 | 30.38 | 253.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 1723.41 | 247.00 | 173.60 | 1177.25 | 0.00 | 0.00 | 0.00 | 0.00 | 47.02 | 224.83 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: OFFICE
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 802.20 | 06-JAN-08:03 | 4512.06 | 5829.16 | 5886.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 742.72 | 09-FEB-08:02 | 4512.06 | 5829.16 | 5886.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 113.92 |
| March | 606.50 | 24-MAR-07:02 | 4512.06 | 5829.16 | 5886.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 262.43 |
| April | 2832.82 | 27-APR-08:63 | 1353.62 | 1748.75 | 1765.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.86 |
| May | 5933.83 | 15-MAY-08:62 | 1804.82 | 2331.66 | 2354.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.78 |
| June | 5981.62 | 09-JUN-08:62 | 1804.82 | 2331.66 | 2354.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86.33 |
| July | 6308.36 | 24-JUL-07:02 | 2707.23 | 3497.50 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.92 |
| August | 6380.28 | 15-AUG-07:01 | 3158.44 | 4080.41 | 4120.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.92 |
| September | 6035.48 | 11-SEP-08:62 | 2256.03 | 2914.58 | 2943.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.72 |
| October | 5934.98 | 04-OCT-08:62 | 1804.82 | 2331.66 | 2354.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.90 |
| November | 576.60 | 22-NOV-08:02 | 4512.06 | 5829.16 | 5886.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 165.40 |
| December | 717.98 | 26-DEC-08:03 | 4512.06 | 5829.16 | 5886.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 156.14 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 576.60 | 1353.62 | 1748.75 | 1765.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 6380.28 | 4512.06 | 5829.16 | 5886.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 262.43 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: G NE APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 6.87 | 11-JAN-20:00 | 206.62 | 138.88 | 547.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 95.07 |
| February | 321.68 | 25-FEB-19:50 | 206.62 | 138.88 | 547.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94.00 |
| March | 371.73 | 30-MAR-19:50 | 206.62 | 138.88 | 523.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.96 |
| April | 390.45 | 29-APR-05:00 | 237.50 | 56.42 | 253.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.18 |
| May | 531.19 | 15-MAY-16:15 | 494.00 | 347.20 | 2354.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.41 | 0.00 |
| June | 1007.66 | 28-JUN-18:00 | 206.62 | 117.18 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 12.18 | 0.00 |
| July | 1353.37 | 24-JUL-18:00 | 206.62 | 117.18 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 47.02 | 0.00 |
| August | 1297.24 | 10-AUG-17:07 | 619.87 | 351.55 | 1765.87 | 0.00 | 0.00 | 0.00 | 0.00 | 40.74 | 0.00 |
| September | 912.08 | 14-SEP-16:30 | 247.00 | 173.60 | 1177.25 | 0.00 | 0.00 | 0.00 | 0.00 | 4.23 | 0.00 |
| October | 443.07 | 12-OCT-06:50 | 201.88 | 56.42 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.84 |
| November | 322.74 | 19-NOV-19:10 | 206.62 | 138.88 | 547.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.66 |
| December | 13.55 | 30-DEC-13:00 | 59.38 | 17.36 | 406.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 6.87 | 59.38 | 17.36 | 253.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 1353.37 | 619.87 | 351.55 | 2354.49 | 0.00 | 0.00 | 0.00 | 0.00 | 47.02 | 95.07 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: G N1 APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 196.28 | 11-JAN-20:00 | 206.62 | 138.88 | 547.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.34 |
| February | 346.32 | 28-FEB-20:00 | 206.62 | 138.88 | 547.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.80 |
| March | 373.77 | 30-MAR-19:50 | 206.62 | 138.88 | 523.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.26 |
| April | 402.98 | 29-APR-05:00 | 237.50 | 56.42 | 253.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.35 |
| May | 521.32 | 11-MAY-03:00 | 237.50 | 8.68 | 223.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.78 |
| June | 858.01 | 28-JUN-18:00 | 206.62 | 117.18 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 7.35 | 0.00 |
| July | 1066.92 | 24-JUL-18:00 | 206.62 | 117.18 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 28.36 | 0.00 |
| August | 1044.43 | 10-AUG-18:50 | 206.62 | 138.88 | 547.42 | 0.00 | 0.00 | 0.00 | 0.00 | 22.70 | 0.00 |
| September | 755.18 | 14-SEP-17:10 | 413.25 | 234.36 | 1177.25 | 0.00 | 0.00 | 0.00 | 0.00 | 1.49 | 0.00 |
| October | 477.47 | 13-OCT-05:00 | 237.50 | 56.42 | 253.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.68 |
| November | 383.66 | 08-NOV-23:10 | 237.50 | 21.70 | 341.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.78 |
| December | 190.71 | 29-DEC-19:00 | 206.62 | 117.18 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.30 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 190.71 | 206.62 | 8.68 | 223.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 1066.92 | 413.25 | 234.36 | 1177.25 | 0.00 | 0.00 | 0.00 | 0.00 | 28.36 | 73.78 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: G N2 APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 196.54 | 11-JAN-20:00 | 206.62 | 138.88 | 547.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.34 |
| February | 343.32 | 28-FEB-19:50 | 206.62 | 138.88 | 547.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.68 |
| March | 373.77 | 30-MAR-19:50 | 206.62 | 138.88 | 523.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.26 |
| April | 402.80 | 29-APR-05:00 | 237.50 | 56.42 | 253.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.33 |
| May | 520.38 | 11-MAY-03:00 | 237.50 | 8.68 | 223.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.65 |
| June | 853.54 | 28-JUN-18:00 | 206.62 | 117.18 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 7.35 | 0.00 |
| July | 1063.37 | 24-JUL-18:00 | 206.62 | 117.18 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 28.36 | 0.00 |
| August | 1036.83 | 10-AUG-18:50 | 206.62 | 138.88 | 547.42 | 0.00 | 0.00 | 0.00 | 0.00 | 22.70 | 0.00 |
| September | 752.81 | 14-SEP-17:10 | 413.25 | 234.36 | 1177.25 | 0.00 | 0.00 | 0.00 | 0.00 | 1.49 | 0.00 |
| October | 477.37 | 13-OCT-05:00 | 237.50 | 56.42 | 253.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.67 |
| November | 383.59 | 08-NOV-23:10 | 237.50 | 21.70 | 341.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.77 |
| December | 190.90 | 29-DEC-19:00 | 206.62 | 117.18 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.30 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 190.90 | 206.62 | 8.68 | 223.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 1063.37 | 413.25 | 234.36 | 1177.25 | 0.00 | 0.00 | 0.00 | 0.00 | 28.36 | 73.65 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: G S1 APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 547.50 | 07-JAN-14:10 | 118.75 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.26 |
| February | 560.27 | 09-FEB-18:00 | 0.00 | 86.80 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92.46 |
| March | 544.29 | 02-MAR-02:70 | 237.50 | 8.68 | 229.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81.51 |
| April | 742.02 | 27-APR-15:10 | 0.00 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 16.58 | 0.00 |
| May | 1001.94 | 15-MAY-15:10 | 0.00 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 |
| June | 1095.72 | 28-JUN-15:10 | 0.00 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 12.31 | 0.00 |
| July | 1400.22 | 24-JUL-15:10 | 0.00 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 26.50 | 0.00 |
| August | 1616.35 | 10-AUG-15:10 | 0.00 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 22.50 | 0.00 |
| September | 1565.55 | 14-SEP-15:10 | 0.00 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.06 |
| October | 1350.20 | 04-OCT-15:10 | 0.00 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.03 |
| November | 604.47 | 11-NOV-23:00 | 237.50 | 52.08 | 417.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 611.54 | 06-DEC-17:10 | 0.00 | 867.99 | 5886.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74.30 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 544.29 | 0.00 | 8.68 | 229.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 1616.35 | 237.50 | 867.99 | 5886.23 | 0.00 | 0.00 | 0.00 | 0.00 | 26.50 | 92.46 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: G S2 APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 514.41 | 08-JAN-12:50 | 118.75 | 17.36 | 406.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.67 |
| February | 559.11 | 09-FEB-18:00 | 0.00 | 86.80 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92.28 |
| March | 544.48 | 02-MAR-02:70 | 237.50 | 8.68 | 229.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81.54 |
| April | 792.11 | 29-APR-15:10 | 237.50 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.04 |
| May | 1054.76 | 15-MAY-15:10 | 0.00 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 |
| June | 1142.68 | 28-JUN-15:10 | 0.00 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 12.31 | 0.00 |
| July | 1476.40 | 24-JUL-15:10 | 0.00 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 26.50 | 0.00 |
| August | 1692.06 | 13-AUG-15:10 | 237.50 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 23.51 | 0.00 |
| September | 1623.73 | 14-SEP-15:10 | 0.00 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.06 |
| October | 1382.59 | 04-OCT-14:10 | 0.00 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.43 |
| November | 604.83 | 11-NOV-23:00 | 237.50 | 52.08 | 417.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 611.04 | 06-DEC-17:10 | 0.00 | 867.99 | 5886.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74.24 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 514.41 | 0.00 | 8.68 | 229.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 1692.06 | 237.50 | 867.99 | 5886.23 | 0.00 | 0.00 | 0.00 | 0.00 | 26.50 | 92.28 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: M SW APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 625.37 | 07-JAN-12:50 | 118.75 | 17.36 | 406.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 167.49 |
| February | 872.69 | 27-FEB-15:30 | 0.00 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.81 |
| March | 1263.50 | 02-MAR-16:10 | 0.00 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.34 |
| April | 2360.47 | 27-APR-16:03 | 0.00 | 260.40 | 1765.87 | 0.00 | 0.00 | 0.00 | 0.00 | 34.76 | 0.00 |
| May | 2366.93 | 15-MAY-16:05 | 0.00 | 347.20 | 2354.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.31 |
| June | 2260.88 | 28-JUN-16:30 | 0.00 | 260.40 | 1765.87 | 0.00 | 0.00 | 0.00 | 0.00 | 27.81 | 0.00 |
| July | 2558.13 | 23-JUL-16:20 | 237.50 | 86.80 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 79.43 | 0.00 |
| August | 2835.58 | 10-AUG-16:17 | 0.00 | 260.40 | 1765.87 | 0.00 | 0.00 | 0.00 | 0.00 | 40.78 | 0.00 |
| September | 2593.64 | 11-SEP-16:04 | 0.00 | 434.00 | 2943.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.18 |
| October | 2314.96 | 04-OCT-15:10 | 0.00 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.50 |
| November | 1314.93 | 04-NOV-15:20 | 237.50 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.24 |
| December | 641.32 | 06-DEC-21:00 | 237.50 | 138.88 | 523.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 625.37 | 0.00 | 17.36 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 2835.58 | 237.50 | 434.00 | 2943.11 | 0.00 | 0.00 | 0.00 | 0.00 | 79.43 | 167.49 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: M NW APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 259.56 | 11-JAN-19:00 | 206.62 | 117.18 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 147.53 |
| February | 457.55 | 28-FEB-24:00 | 237.50 | 21.70 | 341.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 178.31 |
| March | 518.50 | 01-MAR-23:00 | 237.50 | 52.08 | 417.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85.55 |
| April | 1503.86 | 27-APR-17:20 | 206.62 | 117.18 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 17.37 | 0.00 |
| May | 1825.73 | 15-MAY-16:25 | 247.00 | 173.60 | 1177.25 | 0.00 | 0.00 | 0.00 | 0.00 | 1.23 | 0.00 |
| June | 1980.12 | 22-JUN-18:30 | 206.62 | 138.88 | 547.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.90 |
| July | 2150.56 | 31-JUL-18:00 | 206.62 | 117.18 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 46.33 | 0.00 |
| August | 2277.30 | 10-AUG-17:25 | 413.25 | 234.36 | 1177.25 | 0.00 | 0.00 | 0.00 | 0.00 | 55.65 | 0.00 |
| September | 1671.24 | 12-SEP-16:25 | 247.00 | 173.60 | 1177.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.74 |
| October | 895.23 | 04-OCT-16:30 | 247.00 | 173.60 | 1177.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.32 |
| November | 370.10 | 08-NOV-20:00 | 206.62 | 138.88 | 547.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 144.09 |
| December | 321.79 | 10-DEC-15:40 | 59.38 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.91 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 259.56 | 59.38 | 21.70 | 341.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 2277.30 | 413.25 | 234.36 | 1177.25 | 0.00 | 0.00 | 0.00 | 0.00 | 55.65 | 178.31 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: M SE APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 631.65 | 07-JAN-12:40 | 118.75 | 17.36 | 406.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 156.43 |
| February | 636.06 | 19-FEB-12:00 | 118.75 | 17.36 | 412.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 431.20 |
| March | 1090.30 | 02-MAR-13:50 | 0.00 | 17.36 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.08 |
| April | 2157.36 | 27-APR-13:30 | 0.00 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 19.51 | 0.00 |
| May | 2038.79 | 15-MAY-13:30 | 0.00 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.16 |
| June | 1913.82 | 28-JUN-13:00 | 0.00 | 17.36 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 5.35 | 0.00 |
| July | 2314.40 | 24-JUL-13:30 | 0.00 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 63.03 | 0.00 |
| August | 2463.73 | 10-AUG-13:30 | 0.00 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 32.70 | 0.00 |
| September | 2314.03 | 23-SEP-13:30 | 118.75 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.99 |
| October | 2036.14 | 04-OCT-13:30 | 0.00 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.89 |
| November | 1087.93 | 04-NOV-14:00 | 118.75 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 638.78 | 06-DEC-21:00 | 237.50 | 138.88 | 523.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 631.65 | 0.00 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 2463.73 | 237.50 | 138.88 | 523.87 | 0.00 | 0.00 | 0.00 | 0.00 | 63.03 | 431.20 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: M NE APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 259.67 | 11-JAN-19:00 | 206.62 | 117.18 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 147.58 |
| February | 453.68 | 28-FEB-24:00 | 237.50 | 21.70 | 341.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 176.87 |
| March | 524.45 | 01-MAR-08:45 | 185.25 | 52.08 | 776.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 116.06 |
| April | 1105.34 | 27-APR-16:20 | 494.00 | 347.20 | 2354.49 | 0.00 | 0.00 | 0.00 | 0.00 | 30.53 | 0.00 |
| May | 1283.18 | 15-MAY-16:20 | 494.00 | 347.20 | 2354.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.42 | 0.00 |
| June | 1479.52 | 28-JUN-18:00 | 206.62 | 117.18 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 17.29 | 0.00 |
| July | 1735.68 | 24-JUL-18:00 | 206.62 | 117.18 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 67.30 | 0.00 |
| August | 1614.67 | 10-AUG-10:10 | 59.38 | 17.36 | 412.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.21 |
| September | 1188.07 | 14-SEP-16:30 | 247.00 | 173.60 | 1177.25 | 0.00 | 0.00 | 0.00 | 0.00 | 5.91 | 0.00 |
| October | 497.92 | 07-OCT-17:20 | 826.50 | 468.73 | 2354.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.42 |
| November | 368.58 | 08-NOV-20:00 | 206.62 | 138.88 | 547.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 143.53 |
| December | 246.48 | 30-DEC-13:00 | 59.38 | 17.36 | 406.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 246.48 | 59.38 | 17.36 | 341.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 1735.68 | 826.50 | 468.73 | 2354.49 | 0.00 | 0.00 | 0.00 | 0.00 | 67.30 | 176.87 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: M N1 APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 369.81 | 11-JAN-23:40 | 237.50 | 21.70 | 341.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83.41 |
| February | 476.50 | 28-FEB-24:00 | 237.50 | 21.70 | 341.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 111.79 |
| March | 629.66 | 01-MAR-06:10 | 1425.00 | 364.55 | 1907.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.48 |
| April | 806.12 | 27-APR-18:00 | 206.62 | 117.18 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 11.73 | 0.00 |
| May | 1008.07 | 15-MAY-17:10 | 206.62 | 117.18 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.12 |
| June | 1209.23 | 28-JUN-18:40 | 206.62 | 138.88 | 547.42 | 0.00 | 0.00 | 0.00 | 0.00 | 6.70 | 0.00 |
| July | 1340.04 | 24-JUL-18:00 | 206.62 | 117.18 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 40.59 | 0.00 |
| August | 1268.10 | 10-AUG-18:50 | 206.62 | 138.88 | 547.42 | 0.00 | 0.00 | 0.00 | 0.00 | 32.52 | 0.00 |
| September | 965.91 | 14-SEP-17:10 | 413.25 | 234.36 | 1177.25 | 0.00 | 0.00 | 0.00 | 0.00 | 2.05 | 0.00 |
| October | 600.17 | 01-OCT-18:20 | 206.62 | 138.88 | 547.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.30 |
| November | 472.11 | 09-NOV-23:10 | 237.50 | 21.70 | 341.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93.58 |
| December | 406.03 | 10-DEC-18:25 | 413.25 | 234.36 | 1177.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.01 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 369.81 | 206.62 | 21.70 | 341.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 1340.04 | 1425.00 | 364.55 | 1907.14 | 0.00 | 0.00 | 0.00 | 0.00 | 40.59 | 111.79 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: M N2 APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 369.81 | 11-JAN-23:40 | 237.50 | 21.70 | 341.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83.41 |
| February | 476.01 | 28-FEB-24:00 | 237.50 | 21.70 | 341.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 111.68 |
| March | 627.23 | 01-MAR-07:16 | 1009.38 | 282.08 | 1913.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.08 |
| April | 805.43 | 27-APR-18:00 | 206.62 | 117.18 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 11.73 | 0.00 |
| May | 1001.90 | 15-MAY-17:10 | 206.62 | 117.18 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.12 |
| June | 1201.25 | 28-JUN-18:40 | 206.62 | 138.88 | 547.42 | 0.00 | 0.00 | 0.00 | 0.00 | 6.70 | 0.00 |
| July | 1335.82 | 24-JUL-18:00 | 206.62 | 117.18 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 40.59 | 0.00 |
| August | 1257.24 | 10-AUG-18:50 | 206.62 | 138.88 | 547.42 | 0.00 | 0.00 | 0.00 | 0.00 | 32.52 | 0.00 |
| September | 960.91 | 14-SEP-17:10 | 413.25 | 234.36 | 1177.25 | 0.00 | 0.00 | 0.00 | 0.00 | 2.05 | 0.00 |
| October | 576.25 | 09-OCT-18:30 | 206.62 | 138.88 | 547.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.12 |
| November | 472.04 | 09-NOV-23:10 | 237.50 | 21.70 | 341.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93.57 |
| December | 405.59 | 05-DEC-21:00 | 206.62 | 138.88 | 523.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 369.81 | 206.62 | 21.70 | 341.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 1335.82 | 1009.38 | 282.08 | 1913.02 | 0.00 | 0.00 | 0.00 | 0.00 | 40.59 | 111.68 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: M S1 APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 679.93 | 07-JAN-11:20 | 118.75 | 17.36 | 412.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86.76 |
| February | 780.53 | 27-FEB-15:10 | 0.00 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.01 |
| March | 1249.82 | 02-MAR-14:00 | 0.00 | 17.36 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.31 |
| April | 1793.35 | 27-APR-14:10 | 0.00 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 11.76 | 0.00 |
| May | 1654.93 | 15-MAY-14:10 | 0.00 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.10 |
| June | 1496.13 | 28-JUN-14:10 | 0.00 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 8.06 | 0.00 |
| July | 1770.29 | 24-JUL-13:30 | 0.00 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 38.02 | 0.00 |
| August | 1987.40 | 10-AUG-14:10 | 0.00 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 17.53 | 0.00 |
| September | 2082.93 | 23-SEP-13:30 | 118.75 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.22 |
| October | 1921.72 | 04-OCT-14:10 | 0.00 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.32 |
| November | 1258.60 | 04-NOV-14:00 | 118.75 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 670.41 | 06-DEC-21:00 | 237.50 | 138.88 | 523.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 670.41 | 0.00 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 2082.93 | 237.50 | 138.88 | 523.87 | 0.00 | 0.00 | 0.00 | 0.00 | 38.02 | 86.76 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: M S2 APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 679.97 | 07-JAN-11:20 | 118.75 | 17.36 | 412.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86.77 |
| February | 777.41 | 27-FEB-15:10 | 0.00 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.01 |
| March | 1259.15 | 02-MAR-14:00 | 0.00 | 17.36 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.31 |
| April | 1799.18 | 27-APR-14:10 | 0.00 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 11.76 | 0.00 |
| May | 1659.66 | 15-MAY-14:10 | 0.00 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.10 |
| June | 1501.31 | 28-JUN-14:10 | 0.00 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 8.06 | 0.00 |
| July | 1778.17 | 24-JUL-13:30 | 0.00 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 38.02 | 0.00 |
| August | 1993.51 | 10-AUG-14:10 | 0.00 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 17.53 | 0.00 |
| September | 2086.93 | 23-SEP-13:30 | 118.75 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.22 |
| October | 1923.34 | 04-OCT-14:10 | 0.00 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.32 |
| November | 1264.47 | 04-NOV-14:00 | 118.75 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 670.27 | 06-DEC-21:00 | 237.50 | 138.88 | 523.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 670.27 | 0.00 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 2086.93 | 237.50 | 138.88 | 523.87 | 0.00 | 0.00 | 0.00 | 0.00 | 38.02 | 86.77 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: T SW APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 595.98 | 07-JAN-13:20 | 118.75 | 17.36 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 212.59 |
| February | 1794.61 | 27-FEB-15:30 | 0.00 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.47 |
| March | 2036.09 | 14-MAR-16:05 | 0.00 | 347.20 | 2354.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.82 |
| April | 3172.87 | 27-APR-15:10 | 0.00 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 51.29 | 0.00 |
| May | 3079.35 | 15-MAY-16:05 | 0.00 | 347.20 | 2354.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.85 |
| June | 3045.63 | 28-JUN-16:14 | 0.00 | 434.00 | 2943.11 | 0.00 | 0.00 | 0.00 | 0.00 | 36.88 | 0.00 |
| July | 3456.42 | 31-JUL-16:15 | 0.00 | 347.20 | 2354.49 | 0.00 | 0.00 | 0.00 | 0.00 | 85.75 | 0.00 |
| August | 3871.00 | 10-AUG-16:03 | 0.00 | 520.80 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 47.75 | 0.00 |
| September | 3302.77 | 14-SEP-15:20 | 0.00 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.07 | 0.00 |
| October | 2730.31 | 04-OCT-15:10 | 0.00 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.76 |
| November | 2249.01 | 04-NOV-15:20 | 237.50 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.06 |
| December | 668.25 | 05-DEC-14:30 | 0.00 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 133.01 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 595.98 | 0.00 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 3871.00 | 237.50 | 520.80 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 85.75 | 212.59 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: T NW APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 31.77 | 11-JAN-16:10 | 71.25 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 179.24 |
| February | 351.20 | 28-FEB-20:00 | 206.62 | 138.88 | 547.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 156.66 |
| March | 421.47 | 01-MAR-19:10 | 206.62 | 138.88 | 547.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92.08 |
| April | 2216.97 | 27-APR-16:35 | 247.00 | 173.60 | 1177.25 | 0.00 | 0.00 | 0.00 | 0.00 | 29.78 | 0.00 |
| May | 2420.01 | 15-MAY-16:25 | 247.00 | 173.60 | 1177.25 | 0.00 | 0.00 | 0.00 | 0.00 | 1.13 | 0.00 |
| June | 2635.03 | 28-JUN-16:35 | 247.00 | 173.60 | 1177.25 | 0.00 | 0.00 | 0.00 | 0.00 | 35.25 | 0.00 |
| July | 2902.86 | 31-JUL-17:17 | 619.87 | 351.55 | 1765.87 | 0.00 | 0.00 | 0.00 | 0.00 | 84.47 | 0.00 |
| August | 3119.01 | 10-AUG-17:17 | 619.87 | 351.55 | 1765.87 | 0.00 | 0.00 | 0.00 | 0.00 | 75.02 | 0.00 |
| September | 2107.40 | 12-SEP-16:25 | 247.00 | 173.60 | 1177.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 |
| October | 993.93 | 04-OCT-16:30 | 247.00 | 173.60 | 1177.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.00 |
| November | 430.99 | 04-NOV-16:03 | 370.50 | 260.40 | 1765.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 264.08 | 10-DEC-15:00 | 59.38 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 31.77 | 59.38 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 3119.01 | 619.87 | 351.55 | 1765.87 | 0.00 | 0.00 | 0.00 | 0.00 | 84.47 | 179.24 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: T SE APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 596.16 | 07-JAN-13:20 | 118.75 | 17.36 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 212.65 |
| February | 1344.89 | 27-FEB-15:00 | 0.00 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.23 |
| March | 1912.27 | 14-MAR-13:40 | 0.00 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.57 |
| April | 2925.50 | 27-APR-13:40 | 0.00 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 23.95 | 0.00 |
| May | 2712.12 | 15-MAY-13:50 | 0.00 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.94 |
| June | 2635.57 | 28-JUN-13:20 | 0.00 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 9.32 | 0.00 |
| July | 3225.89 | 24-JUL-13:30 | 0.00 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 82.70 | 0.00 |
| August | 3388.44 | 10-AUG-13:30 | 0.00 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 42.85 | 0.00 |
| September | 2969.55 | 14-SEP-13:50 | 0.00 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.31 |
| October | 2388.60 | 04-OCT-13:40 | 0.00 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.02 |
| November | 1971.04 | 04-NOV-14:00 | 118.75 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 560.59 | 06-DEC-16:20 | 0.00 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 181.44 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 560.59 | 0.00 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 3388.44 | 118.75 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 82.70 | 212.65 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: T NE APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 9.90 | 11-JAN-20:00 | 206.62 | 138.88 | 547.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 182.01 |
| February | 344.18 | 28-FEB-19:50 | 206.62 | 138.88 | 547.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 157.79 |
| March | 385.57 | 25-MAR-10:10 | 59.38 | 17.36 | 412.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 189.65 |
| April | 1616.36 | 27-APR-16:07 | 370.50 | 260.40 | 1765.87 | 0.00 | 0.00 | 0.00 | 0.00 | 45.37 | 0.00 |
| May | 1654.63 | 15-MAY-16:03 | 494.00 | 347.20 | 2354.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.85 |
| June | 1889.53 | 28-JUN-16:05 | 494.00 | 347.20 | 2354.49 | 0.00 | 0.00 | 0.00 | 0.00 | 37.40 | 0.00 |
| July | 2295.13 | 24-JUL-16:03 | 741.00 | 520.80 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 84.95 | 0.00 |
| August | 2169.12 | 08-AUG-16:15 | 494.00 | 347.20 | 2354.49 | 0.00 | 0.00 | 0.00 | 0.00 | 123.64 | 0.00 |
| September | 1443.89 | 14-SEP-16:15 | 494.00 | 347.20 | 2354.49 | 0.00 | 0.00 | 0.00 | 0.00 | 6.03 | 0.00 |
| October | 421.94 | 04-OCT-16:15 | 494.00 | 347.20 | 2354.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.02 |
| November | 321.73 | 05-NOV-20:00 | 206.62 | 138.88 | 523.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 426.83 |
| December | 31.33 | 10-DEC-15:00 | 59.38 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 9.90 | 59.38 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 2295.13 | 741.00 | 520.80 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 123.64 | 426.83 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: T N1 APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 208.97 | 11-JAN-20:00 | 206.62 | 138.88 | 547.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 109.78 |
| February | 386.68 | 28-FEB-22:03 | 712.50 | 156.25 | 1253.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 120.62 |
| March | 417.51 | 19-MAR-20:00 | 206.62 | 138.88 | 523.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 131.12 |
| April | 1253.37 | 27-APR-16:27 | 370.50 | 260.40 | 1765.87 | 0.00 | 0.00 | 0.00 | 0.00 | 20.88 | 0.00 |
| May | 1346.22 | 15-MAY-16:15 | 494.00 | 347.20 | 2354.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 | 0.00 |
| June | 1590.89 | 28-JUN-17:40 | 206.62 | 117.18 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 15.87 | 0.00 |
| July | 1843.07 | 24-JUL-18:00 | 206.62 | 117.18 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 53.26 | 0.00 |
| August | 1759.47 | 08-AUG-16:30 | 247.00 | 173.60 | 1177.25 | 0.00 | 0.00 | 0.00 | 0.00 | 79.06 | 0.00 |
| September | 1204.39 | 14-SEP-16:25 | 247.00 | 173.60 | 1177.25 | 0.00 | 0.00 | 0.00 | 0.00 | 4.44 | 0.00 |
| October | 383.86 | 11-OCT-22:00 | 237.50 | 52.08 | 417.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.12 |
| November | 346.62 | 05-NOV-20:00 | 206.62 | 138.88 | 523.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 276.04 |
| December | 156.61 | 10-DEC-15:00 | 59.38 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 156.61 | 59.38 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 1843.07 | 712.50 | 347.20 | 2354.49 | 0.00 | 0.00 | 0.00 | 0.00 | 79.06 | 276.04 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: T N2 APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 208.56 | 11-JAN-20:00 | 206.62 | 138.88 | 547.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 109.78 |
| February | 381.16 | 28-FEB-22:00 | 237.50 | 95.48 | 500.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 118.91 |
| March | 416.44 | 19-MAR-20:00 | 206.62 | 138.88 | 523.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 130.81 |
| April | 1248.13 | 27-APR-16:27 | 370.50 | 260.40 | 1765.87 | 0.00 | 0.00 | 0.00 | 0.00 | 20.88 | 0.00 |
| May | 1336.98 | 15-MAY-16:15 | 494.00 | 347.20 | 2354.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 | 0.00 |
| June | 1571.58 | 28-JUN-17:40 | 206.62 | 117.18 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 15.87 | 0.00 |
| July | 1830.18 | 24-JUL-18:00 | 206.62 | 117.18 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 53.26 | 0.00 |
| August | 1746.35 | 08-AUG-16:15 | 494.00 | 347.20 | 2354.49 | 0.00 | 0.00 | 0.00 | 0.00 | 74.58 | 0.00 |
| September | 1194.39 | 14-SEP-16:15 | 494.00 | 347.20 | 2354.49 | 0.00 | 0.00 | 0.00 | 0.00 | 3.64 | 0.00 |
| October | 382.55 | 11-OCT-22:00 | 237.50 | 52.08 | 417.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.89 |
| November | 346.01 | 05-NOV-20:00 | 206.62 | 138.88 | 523.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 275.58 |
| December | 150.97 | 10-DEC-15:00 | 59.38 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 150.97 | 59.38 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 1830.18 | 494.00 | 347.20 | 2354.49 | 0.00 | 0.00 | 0.00 | 0.00 | 74.58 | 275.58 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: T S1 APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 669.07 | 20-JAN-13:30 | 0.00 | 17.36 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.04 |
| February | 1348.18 | 27-FEB-15:10 | 0.00 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.73 |
| March | 1735.29 | 14-MAR-14:00 | 0.00 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.04 |
| April | 2494.09 | 27-APR-14:20 | 0.00 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 17.99 | 0.00 |
| May | 2265.30 | 15-MAY-14:10 | 0.00 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.12 |
| June | 2179.20 | 28-JUN-14:10 | 0.00 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 10.30 | 0.00 |
| July | 2605.39 | 24-JUL-13:40 | 0.00 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 52.74 | 0.00 |
| August | 2886.61 | 10-AUG-14:20 | 0.00 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 27.12 | 0.00 |
| September | 2710.71 | 23-SEP-13:40 | 118.75 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.22 |
| October | 2246.08 | 04-OCT-14:10 | 0.00 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.95 |
| November | 1919.59 | 04-NOV-14:00 | 118.75 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 727.85 | 05-DEC-14:30 | 0.00 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80.23 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 669.07 | 0.00 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 2886.61 | 118.75 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 52.74 | 80.23 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: T S2 APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 667.25 | 20-JAN-13:30 | 0.00 | 17.36 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.04 |
| February | 1344.19 | 27-FEB-15:10 | 0.00 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.73 |
| March | 1752.82 | 14-MAR-14:00 | 0.00 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.04 |
| April | 2504.68 | 27-APR-14:10 | 0.00 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 15.29 | 0.00 |
| May | 2278.07 | 15-MAY-14:10 | 0.00 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.12 |
| June | 2189.18 | 28-JUN-14:10 | 0.00 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 10.30 | 0.00 |
| July | 2619.00 | 24-JUL-13:40 | 0.00 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 52.74 | 0.00 |
| August | 2894.23 | 10-AUG-14:20 | 0.00 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 27.12 | 0.00 |
| September | 2718.37 | 23-SEP-13:40 | 118.75 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.22 |
| October | 2253.49 | 04-OCT-14:10 | 0.00 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.95 |
| November | 1924.16 | 04-NOV-14:00 | 118.75 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 732.82 | 05-DEC-14:30 | 0.00 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80.23 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 667.25 | 0.00 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 2894.23 | 118.75 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 52.74 | 80.23 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: T CORRIDOR
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 0.00 | 01-JAN-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80.17 |
| February | 0.00 | 01-FEB-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.57 |
| March | 0.00 | 01-MAR-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.42 |
| April | 0.00 | 01-APR-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.20 |
| May | 0.00 | 01-MAY-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.19 |
| June | 0.00 | 01-JUN-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.81 |
| July | 0.00 | 01-JUL-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.91 |
| August | 0.00 | 01-AUG-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.94 |
| September | 0.00 | 01-SEP-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.28 |
| October | 0.00 | 01-OCT-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.45 |
| November | 0.00 | 01-NOV-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.16 |
| December | 0.00 | 01-DEC-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.51 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
| Minimum of Months | 0.00 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.91 | |
| Maximum of Months | 0.00 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80.17 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: G CORRIDOR
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 0.00 | 01-JAN-00:10 | 397.10 | 370.63 | 56.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.53 |
| February | 0.00 | 01-FEB-00:10 | 397.10 | 370.63 | 56.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.28 |
| March | 0.00 | 01-MAR-00:10 | 397.10 | 370.63 | 56.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.53 |
| April | 0.00 | 01-APR-00:10 | 397.10 | 370.63 | 56.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.04 |
| May | 0.00 | 01-MAY-00:10 | 397.10 | 370.63 | 56.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.01 |
| June | 0.00 | 01-JUN-00:10 | 397.10 | 370.63 | 56.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.82 |
| July | 0.00 | 01-JUL-00:10 | 397.10 | 370.63 | 56.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.04 |
| August | 0.00 | 01-AUG-00:10 | 397.10 | 370.63 | 56.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.09 |
| September | 0.00 | 01-SEP-00:10 | 397.10 | 370.63 | 56.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.27 |
| October | 0.00 | 01-OCT-00:10 | 397.10 | 370.63 | 56.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.33 |
| November | 0.00 | 01-NOV-00:10 | 397.10 | 370.63 | 56.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.35 |
| December | 0.00 | 01-DEC-00:10 | 397.10 | 370.63 | 56.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.96 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 0.00 | 397.10 | 370.63 | 56.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.82 | |
| Maximum of Months | 0.00 | 397.10 | 370.63 | 56.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.53 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: M CORRIDOR
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 0.00 | 01-JAN-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.02 |
| February | 0.00 | 01-FEB-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.82 |
| March | 0.00 | 01-MAR-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.60 |
| April | 0.00 | 01-APR-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.00 |
| May | 0.00 | 01-MAY-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.30 |
| June | 0.00 | 01-JUN-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.58 |
| July | 0.00 | 01-JUL-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.01 |
| August | 0.00 | 01-AUG-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.59 |
| September | 0.00 | 01-SEP-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.25 |
| October | 0.00 | 01-OCT-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.85 |
| November | 0.00 | 01-NOV-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.79 |
| December | 0.00 | 01-DEC-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.95 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
| Minimum of Months | 0.00 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.01 | |
| Maximum of Months | 0.00 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.02 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
| January | 0.101225E+12 | 71196.44 | 13-JAN-18:10 | 0.681314E+11 | 52316.47 | 15-JAN-04:00 |
| February | 0.907010E+11 | 69699.36 | 02-FEB-18:10 | 0.454943E+11 | 63056.36 | 19-FEB-05:00 |
| March | 0.988077E+11 | 65896.46 | 27-MAR-18:40 | 0.223988E+11 | 33336.97 | 24-MAR-05:00 |
| April | 0.954604E+11 | 76036.65 | 27-APR-17:49 | 0.885763E+10 | 26014.53 | 19-APR-04:00 |
| May | 0.999845E+11 | 73189.55 | 15-MAY-16:10 | 0.167592E+10 | 11442.83 | 18-MAY-04:00 |
| June | 0.993786E+11 | 72511.25 | 20-JUN-17:30 | 0.173745E+09 | 3855.70 | 14-JUN-02:00 |
| July | 0.109015E+12 | 79608.17 | 24-JUL-17:30 | 0.00 | 0.00 | 01-JUL-00:10 |
| August | 0.111915E+12 | 82678.05 | 10-AUG-17:19 | 0.00 | 0.00 | 01-AUG-00:10 |
| September | 0.998555E+11 | 73851.11 | 14-SEP-17:10 | 0.335981E+09 | 6117.27 | 27-SEP-03:00 |
| October | 0.971219E+11 | 66905.88 | 04-OCT-16:19 | 0.712301E+10 | 16686.10 | 28-OCT-03:00 |
| November | 0.949581E+11 | 60655.60 | 23-NOV-18:40 | 0.327713E+11 | 35308.05 | 30-NOV-00:00 |
| December | 0.100249E+12 | 63269.71 | 27-DEC-18:30 | 0.583984E+11 | 49872.55 | 26-DEC-09:09 |
| Annual Sum or Average | 0.119867E+13 | 0.245361E+12 | ||||
| Minimum of Months | 0.907010E+11 | 60655.60 | 0.00 | 0.00 | ||
| Maximum of Months | 0.111915E+12 | 82678.05 | 0.681314E+11 | 63056.36 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| INTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [J] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
| January | 0.840929E+10 | 0.542821E+10 | 0.389380E+11 | 0.00 | 0.696561E+10 | 0.00 | 0.00 | 239055.16 | 0.00 | 0.00 | 0.00 | 0.414838E+11 | 0.00 |
| February | 0.760941E+10 | 0.447513E+10 | 0.351823E+11 | 0.00 | 0.573484E+10 | 0.00 | 0.00 | 47480035.07 | 0.00 | 0.00 | 0.00 | 0.376518E+11 | 0.00 |
| March | 0.845392E+10 | 0.436817E+10 | 0.389781E+11 | 0.00 | 0.542364E+10 | 0.00 | 0.00 | 0.283446E+09 | 0.00 | 0.00 | 0.00 | 0.413004E+11 | 0.00 |
| April | 0.814762E+10 | 0.363855E+10 | 0.376905E+11 | 0.00 | 0.521737E+10 | 0.00 | 0.00 | 0.171738E+10 | 0.00 | 0.00 | 0.00 | 0.390489E+11 | 0.00 |
| May | 0.843904E+10 | 0.323172E+10 | 0.389647E+11 | 0.00 | 0.588974E+10 | 0.00 | 0.00 | 0.435109E+10 | 0.00 | 0.00 | 0.00 | 0.391082E+11 | 0.00 |
| June | 0.817737E+10 | 0.284399E+10 | 0.377173E+11 | 0.00 | 0.657759E+10 | 0.00 | 0.00 | 0.736200E+10 | 0.00 | 0.00 | 0.00 | 0.367003E+11 | 0.00 |
| July | 0.840929E+10 | 0.306937E+10 | 0.389380E+11 | 0.00 | 0.839690E+10 | 0.00 | 0.00 | 0.130958E+11 | 0.00 | 0.00 | 0.00 | 0.371055E+11 | 0.00 |
| August | 0.845392E+10 | 0.352395E+10 | 0.389781E+11 | 0.00 | 0.893629E+10 | 0.00 | 0.00 | 0.151564E+11 | 0.00 | 0.00 | 0.00 | 0.368667E+11 | 0.00 |
| September | 0.814762E+10 | 0.397089E+10 | 0.376905E+11 | 0.00 | 0.657277E+10 | 0.00 | 0.00 | 0.740118E+10 | 0.00 | 0.00 | 0.00 | 0.360725E+11 | 0.00 |
| October | 0.842417E+10 | 0.471197E+10 | 0.389514E+11 | 0.00 | 0.522647E+10 | 0.00 | 0.00 | 0.150542E+10 | 0.00 | 0.00 | 0.00 | 0.383025E+11 | 0.00 |
| November | 0.814762E+10 | 0.509396E+10 | 0.376905E+11 | 0.00 | 0.560590E+10 | 0.00 | 0.00 | 0.135475E+09 | 0.00 | 0.00 | 0.00 | 0.382845E+11 | 0.00 |
| December | 0.840929E+10 | 0.556764E+10 | 0.389380E+11 | 0.00 | 0.662619E+10 | 0.00 | 0.00 | 6510085.54 | 0.00 | 0.00 | 0.00 | 0.407010E+11 | 0.00 |
| Annual Sum or Average | 0.992286E+11 | 0.499235E+11 | 0.458657E+12 | 0.00 | 0.771733E+11 | 0.00 | 0.00 | 0.510624E+11 | 0.00 | 0.00 | 0.00 | 0.462626E+12 | 0.00 |
| Minimum of Months | 0.760941E+10 | 0.284399E+10 | 0.351823E+11 | 0.00 | 0.521737E+10 | 0.00 | 0.00 | 239055.16 | 0.00 | 0.00 | 0.00 | 0.360725E+11 | 0.00 |
| Maximum of Months | 0.845392E+10 | 0.556764E+10 | 0.389781E+11 | 0.00 | 0.893629E+10 | 0.00 | 0.00 | 0.151564E+11 | 0.00 | 0.00 | 0.00 | 0.414838E+11 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| INTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
| January | 0.00 | 0.00 | 0.681314E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.454943E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.223988E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.885763E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.167592E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.173745E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.335981E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.712301E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.327713E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.583984E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.245361E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.681314E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| INTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
| January | 5904.43 | 01-JAN-19:10 | 3183.33 | 01-JAN-00:10 | 22709.69 | 03-JAN-17:10 | 0.00 | 3582.66 | 15-JAN-04:00 | 0.00 | 0.00 | 01-JAN-00:10 |
| February | 5904.43 | 01-FEB-19:10 | 3183.33 | 01-FEB-00:10 | 22709.69 | 01-FEB-17:10 | 0.00 | 3965.23 | 19-FEB-05:00 | 0.00 | 0.00 | 01-FEB-00:10 |
| March | 5904.43 | 01-MAR-19:10 | 3183.33 | 01-MAR-00:10 | 22709.69 | 01-MAR-17:10 | 0.00 | 2896.51 | 24-MAR-05:00 | 0.00 | 0.00 | 01-MAR-00:10 |
| April | 5904.43 | 01-APR-18:10 | 3183.33 | 01-APR-00:10 | 22709.69 | 03-APR-16:10 | 0.00 | 5594.98 | 27-APR-16:10 | 0.00 | 0.00 | 01-APR-00:10 |
| May | 5904.43 | 01-MAY-18:10 | 3183.33 | 01-MAY-00:10 | 22709.69 | 01-MAY-16:10 | 0.00 | 5649.71 | 15-MAY-16:10 | 0.00 | 0.00 | 01-MAY-00:10 |
| June | 5904.43 | 01-JUN-18:10 | 3183.33 | 01-JUN-00:10 | 22709.69 | 01-JUN-16:10 | 0.00 | 6049.41 | 28-JUN-17:10 | 0.00 | 0.00 | 01-JUN-00:10 |
| July | 5904.43 | 01-JUL-18:10 | 3183.33 | 01-JUL-00:10 | 22709.69 | 03-JUL-16:10 | 0.00 | 7110.40 | 24-JUL-15:09 | 0.00 | 0.00 | 01-JUL-00:10 |
| August | 5904.43 | 01-AUG-18:10 | 3183.33 | 01-AUG-00:10 | 22709.69 | 01-AUG-16:10 | 0.00 | 7599.85 | 10-AUG-16:19 | 0.00 | 0.00 | 01-AUG-00:10 |
| September | 5904.43 | 01-SEP-18:10 | 3183.33 | 01-SEP-00:10 | 22709.69 | 01-SEP-16:10 | 0.00 | 6196.09 | 14-SEP-16:10 | 0.00 | 0.00 | 01-SEP-00:10 |
| October | 5904.43 | 01-OCT-18:10 | 3183.33 | 01-OCT-00:10 | 22709.69 | 02-OCT-16:10 | 0.00 | 4535.05 | 04-OCT-15:09 | 0.00 | 0.00 | 01-OCT-00:10 |
| November | 5904.43 | 01-NOV-18:10 | 3183.33 | 01-NOV-00:10 | 22709.69 | 01-NOV-16:10 | 0.00 | 3325.46 | 04-NOV-14:20 | 0.00 | 0.00 | 01-NOV-00:10 |
| December | 5904.43 | 01-DEC-19:10 | 3183.33 | 01-DEC-00:10 | 22709.69 | 01-DEC-17:10 | 0.00 | 3377.97 | 26-DEC-03:00 | 0.00 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 5904.43 | 3183.33 | 22709.69 | 0.00 | 2896.51 | 0.00 | 0.00 | |||||
| Maximum of Months | 5904.43 | 3183.33 | 22709.69 | 0.00 | 7599.85 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| COOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY {Maximum} [W] | HEATRECOVERY:ELECTRICITY {TIMESTAMP} | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
| January | 86.01 | 20-JAN-13:30 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 37760.19 | 28-JAN-07:10 | 0.00 |
| February | 2939.14 | 27-FEB-15:09 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 37762.84 | 01-FEB-07:00 | 0.00 |
| March | 3371.32 | 18-MAR-16:10 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 36668.16 | 19-MAR-06:40 | 0.00 |
| April | 13587.97 | 27-APR-15:09 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 33665.98 | 03-APR-06:19 | 0.00 |
| May | 12931.24 | 15-MAY-15:20 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 31214.05 | 22-MAY-07:00 | 0.00 |
| June | 14752.87 | 28-JUN-16:49 | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 31233.61 | 11-JUN-06:00 | 0.00 |
| July | 19995.49 | 24-JUL-15:09 | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 33441.81 | 26-JUL-06:40 | 0.00 |
| August | 21407.18 | 10-AUG-15:30 | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 30534.99 | 02-AUG-17:00 | 0.00 |
| September | 15648.08 | 14-SEP-15:09 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 31952.10 | 22-SEP-07:49 | 0.00 |
| October | 9736.35 | 04-OCT-15:09 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 35960.81 | 14-OCT-06:00 | 0.00 |
| November | 5376.21 | 04-NOV-14:20 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 29345.16 | 01-NOV-06:19 | 0.00 |
| December | 425.96 | 05-DEC-14:30 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 31465.92 | 30-DEC-08:00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
| Minimum of Months | 86.01 | 0.00 | 0.00 | 0.00 | 29345.16 | 0.00 | |||
| Maximum of Months | 21407.18 | 0.00 | 0.00 | 0.00 | 37762.84 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
| January | 71196.44 | 13-JAN-18:10 | 5231.74 | 22609.62 | 3183.33 | 0.00 | 2797.85 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 69699.36 | 02-FEB-18:10 | 5231.74 | 22609.62 | 3183.33 | 0.00 | 1867.20 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 65896.46 | 27-MAR-18:40 | 5904.43 | 20531.10 | 3183.33 | 0.00 | 1802.47 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 76036.65 | 27-APR-17:49 | 5231.74 | 22609.62 | 0.00 | 0.00 | 5241.88 | 0.00 | 0.00 | 11902.01 | 0.00 |
| May | 73189.55 | 15-MAY-16:10 | 4289.87 | 22709.69 | 0.00 | 0.00 | 5649.71 | 0.00 | 0.00 | 12800.98 | 0.00 |
| June | 72511.25 | 20-JUN-17:30 | 5231.74 | 22609.62 | 0.00 | 0.00 | 5627.08 | 0.00 | 0.00 | 12933.29 | 0.00 |
| July | 79608.17 | 24-JUL-17:30 | 5231.74 | 22609.62 | 0.00 | 0.00 | 7011.53 | 0.00 | 0.00 | 18345.87 | 0.00 |
| August | 82678.05 | 10-AUG-17:19 | 5231.74 | 22609.62 | 0.00 | 0.00 | 7513.58 | 0.00 | 0.00 | 20570.82 | 0.00 |
| September | 73851.11 | 14-SEP-17:10 | 5231.74 | 22609.62 | 0.00 | 0.00 | 5823.57 | 0.00 | 0.00 | 13642.48 | 0.00 |
| October | 66905.88 | 04-OCT-16:19 | 4289.87 | 22709.69 | 0.00 | 0.00 | 4333.97 | 0.00 | 0.00 | 8500.19 | 0.00 |
| November | 60655.60 | 23-NOV-18:40 | 5231.74 | 22609.62 | 3183.33 | 0.00 | 2206.57 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 63269.71 | 27-DEC-18:30 | 5231.74 | 22609.62 | 3183.33 | 0.00 | 2348.83 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
| Minimum of Months | 60655.60 | 4289.87 | 20531.10 | 0.00 | 0.00 | 1802.47 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 82678.05 | 5904.43 | 22709.69 | 3183.33 | 0.00 | 7513.58 | 0.00 | 0.00 | 20570.82 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| INTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | |
| January | 0.00 | 0.00 | 52316.47 | 15-JAN-04:00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 63056.36 | 19-FEB-05:00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 33336.97 | 24-MAR-05:00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 26014.53 | 19-APR-04:00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 11442.83 | 18-MAY-04:00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 3855.70 | 14-JUN-02:00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 6117.27 | 27-SEP-03:00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 16686.10 | 28-OCT-03:00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 35308.05 | 30-NOV-00:00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 49872.55 | 26-DEC-09:09 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 63056.36 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: G SW APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: G NW APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: OFFICE
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: G NE APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: G N1 APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: G N2 APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: G S1 APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: G S2 APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: M SW APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: M NW APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: M SE APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: M NE APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: M N1 APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: M N2 APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: M S1 APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: M S2 APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: T SW APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: T NW APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: T SE APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: T NE APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: T N1 APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: T N2 APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: T S1 APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: T S2 APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: T CORRIDOR
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: G CORRIDOR
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: M CORRIDOR
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: G SW APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 533.00 | 21.10 | 492.50 | 21.10 | 492.50 | 21.10 |
| February | 473.00 | 21.12 | 253.83 | 21.12 | 253.83 | 21.11 |
| March | 506.00 | 21.23 | 91.33 | 21.21 | 91.33 | 21.20 |
| April | 496.67 | 21.70 | 13.00 | 21.68 | 13.00 | 21.67 |
| May | 448.50 | 22.46 | 9.67 | 22.49 | 0.00 | 22.49 |
| June | 297.17 | 23.20 | 9.83 | 23.23 | 0.00 | 23.23 |
| July | 87.67 | 23.64 | 138.33 | 23.86 | 0.00 | 23.86 |
| August | 57.00 | 23.58 | 201.17 | 23.91 | 0.00 | 23.91 |
| September | 158.83 | 23.31 | 100.33 | 23.58 | 0.00 | 23.58 |
| October | 456.17 | 22.18 | 1.17 | 22.18 | 0.00 | 22.18 |
| November | 508.00 | 21.30 | 81.17 | 21.27 | 81.17 | 21.25 |
| December | 533.00 | 21.12 | 310.33 | 21.11 | 310.33 | 21.11 |
| Annual Sum or Average | 4555.00 | 21.74 | 1702.67 | 21.78 | 1242.17 | 21.67 |
| Minimum of Months | 57.00 | 21.10 | 1.17 | 21.10 | 0.00 | 21.10 |
| Maximum of Months | 533.00 | 23.64 | 492.50 | 23.91 | 492.50 | 23.91 |
Report: ComfortReportSimple55Monthly
For: G NW APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 744.00 | 21.10 | 705.83 | 21.10 | 705.83 | 21.10 |
| February | 672.00 | 21.11 | 479.67 | 21.10 | 479.67 | 21.10 |
| March | 744.00 | 21.11 | 386.33 | 21.11 | 386.33 | 21.10 |
| April | 720.00 | 21.42 | 78.17 | 21.39 | 78.17 | 21.36 |
| May | 712.67 | 22.19 | 0.00 | 22.19 | 0.00 | 22.19 |
| June | 527.33 | 23.08 | 3.67 | 23.09 | 0.00 | 23.09 |
| July | 183.67 | 23.65 | 116.83 | 23.78 | 0.00 | 23.78 |
| August | 120.67 | 23.54 | 185.33 | 23.82 | 0.00 | 23.82 |
| September | 456.50 | 23.20 | 20.00 | 23.23 | 0.00 | 23.23 |
| October | 744.00 | 21.69 | 0.00 | 21.69 | 0.00 | 21.69 |
| November | 720.00 | 21.15 | 301.00 | 21.14 | 301.00 | 21.13 |
| December | 744.00 | 21.10 | 640.67 | 21.10 | 640.67 | 21.10 |
| Annual Sum or Average | 7088.83 | 21.70 | 2917.50 | 21.62 | 2591.67 | 21.51 |
| Minimum of Months | 120.67 | 21.10 | 0.00 | 21.10 | 0.00 | 21.10 |
| Maximum of Months | 744.00 | 23.65 | 705.83 | 23.82 | 705.83 | 23.82 |
Report: ComfortReportSimple55Monthly
For: OFFICE
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 140.00 | 20.96 | 129.00 | 20.94 | 129.00 | 20.94 |
| February | 133.00 | 21.30 | 74.50 | 21.14 | 74.50 | 21.07 |
| March | 161.00 | 21.86 | 29.33 | 21.67 | 29.33 | 21.54 |
| April | 124.50 | 22.76 | 10.83 | 22.67 | 7.33 | 22.56 |
| May | 81.17 | 23.70 | 17.33 | 23.78 | 0.00 | 23.78 |
| June | 14.33 | 23.93 | 71.50 | 24.18 | 0.00 | 24.18 |
| July | 0.00 | 0.00 | 119.67 | 24.23 | 0.00 | 24.23 |
| August | 0.00 | 0.00 | 158.17 | 24.22 | 0.00 | 24.22 |
| September | 8.00 | 23.90 | 81.83 | 24.18 | 0.00 | 24.18 |
| October | 96.17 | 23.31 | 8.67 | 23.38 | 0.00 | 23.38 |
| November | 140.00 | 21.90 | 37.50 | 21.67 | 37.50 | 21.52 |
| December | 140.00 | 21.06 | 96.17 | 20.99 | 96.17 | 20.96 |
| Annual Sum or Average | 1038.17 | 21.99 | 834.50 | 22.31 | 373.83 | 22.07 |
| Minimum of Months | 0.00 | 0.00 | 8.67 | 20.94 | 0.00 | 20.94 |
| Maximum of Months | 161.00 | 23.93 | 158.17 | 24.23 | 129.00 | 24.23 |
Report: ComfortReportSimple55Monthly
For: G NE APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 744.00 | 21.10 | 705.17 | 21.10 | 705.17 | 21.10 |
| February | 672.00 | 21.10 | 475.17 | 21.10 | 475.17 | 21.10 |
| March | 744.00 | 21.10 | 385.00 | 21.10 | 385.00 | 21.10 |
| April | 720.00 | 21.42 | 65.50 | 21.39 | 65.50 | 21.37 |
| May | 719.33 | 22.18 | 0.00 | 22.18 | 0.00 | 22.18 |
| June | 512.50 | 23.17 | 0.50 | 23.17 | 0.00 | 23.17 |
| July | 222.67 | 23.62 | 90.67 | 23.73 | 0.00 | 23.73 |
| August | 112.50 | 23.51 | 197.00 | 23.82 | 0.00 | 23.82 |
| September | 470.17 | 23.14 | 23.50 | 23.18 | 0.00 | 23.18 |
| October | 744.00 | 21.67 | 0.00 | 21.67 | 0.00 | 21.67 |
| November | 720.00 | 21.15 | 305.67 | 21.14 | 305.67 | 21.13 |
| December | 744.00 | 21.10 | 641.00 | 21.10 | 641.00 | 21.10 |
| Annual Sum or Average | 7125.17 | 21.71 | 2889.17 | 21.62 | 2577.50 | 21.52 |
| Minimum of Months | 112.50 | 21.10 | 0.00 | 21.10 | 0.00 | 21.10 |
| Maximum of Months | 744.00 | 23.62 | 705.17 | 23.82 | 705.17 | 23.82 |
Report: ComfortReportSimple55Monthly
For: G N1 APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 744.00 | 21.10 | 440.83 | 21.10 | 440.83 | 21.10 |
| February | 672.00 | 21.11 | 395.33 | 21.11 | 395.33 | 21.11 |
| March | 744.00 | 21.12 | 159.17 | 21.11 | 159.17 | 21.11 |
| April | 720.00 | 21.45 | 5.33 | 21.45 | 5.33 | 21.44 |
| May | 710.83 | 22.45 | 0.00 | 22.45 | 0.00 | 22.45 |
| June | 484.50 | 23.32 | 0.00 | 23.32 | 0.00 | 23.32 |
| July | 144.17 | 23.82 | 50.00 | 23.87 | 0.00 | 23.87 |
| August | 45.33 | 23.70 | 106.83 | 23.91 | 0.00 | 23.91 |
| September | 371.50 | 23.43 | 5.67 | 23.43 | 0.00 | 23.43 |
| October | 744.00 | 21.93 | 0.00 | 21.93 | 0.00 | 21.93 |
| November | 720.00 | 21.23 | 64.17 | 21.22 | 64.17 | 21.21 |
| December | 744.00 | 21.10 | 429.17 | 21.10 | 429.17 | 21.10 |
| Annual Sum or Average | 6844.33 | 21.74 | 1656.50 | 21.67 | 1494.00 | 21.59 |
| Minimum of Months | 45.33 | 21.10 | 0.00 | 21.10 | 0.00 | 21.10 |
| Maximum of Months | 744.00 | 23.82 | 440.83 | 23.91 | 440.83 | 23.91 |
Report: ComfortReportSimple55Monthly
For: G N2 APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 744.00 | 21.10 | 441.17 | 21.10 | 441.17 | 21.10 |
| February | 672.00 | 21.11 | 395.33 | 21.11 | 395.33 | 21.11 |
| March | 744.00 | 21.12 | 157.50 | 21.11 | 157.50 | 21.11 |
| April | 720.00 | 21.45 | 4.83 | 21.45 | 4.83 | 21.44 |
| May | 711.33 | 22.44 | 0.00 | 22.44 | 0.00 | 22.44 |
| June | 480.83 | 23.33 | 0.00 | 23.33 | 0.00 | 23.33 |
| July | 147.00 | 23.82 | 48.33 | 23.86 | 0.00 | 23.86 |
| August | 46.00 | 23.70 | 109.50 | 23.91 | 0.00 | 23.91 |
| September | 378.33 | 23.42 | 6.00 | 23.43 | 0.00 | 23.43 |
| October | 744.00 | 21.92 | 0.00 | 21.92 | 0.00 | 21.92 |
| November | 720.00 | 21.23 | 64.17 | 21.22 | 64.17 | 21.21 |
| December | 744.00 | 21.10 | 430.17 | 21.10 | 430.17 | 21.10 |
| Annual Sum or Average | 6851.50 | 21.74 | 1657.00 | 21.67 | 1493.17 | 21.59 |
| Minimum of Months | 46.00 | 21.10 | 0.00 | 21.10 | 0.00 | 21.10 |
| Maximum of Months | 744.00 | 23.82 | 441.17 | 23.91 | 441.17 | 23.91 |
Report: ComfortReportSimple55Monthly
For: G S1 APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 533.00 | 21.10 | 231.67 | 21.10 | 231.67 | 21.10 |
| February | 473.00 | 21.17 | 138.67 | 21.15 | 138.67 | 21.14 |
| March | 506.00 | 21.36 | 13.00 | 21.35 | 13.00 | 21.35 |
| April | 483.33 | 21.87 | 0.00 | 21.87 | 0.00 | 21.87 |
| May | 436.83 | 22.89 | 11.00 | 22.92 | 0.00 | 22.92 |
| June | 236.50 | 23.47 | 1.17 | 23.47 | 0.00 | 23.47 |
| July | 53.83 | 23.83 | 105.17 | 23.94 | 0.00 | 23.94 |
| August | 1.17 | 23.84 | 190.50 | 24.00 | 0.00 | 24.00 |
| September | 77.83 | 23.48 | 111.33 | 23.79 | 0.00 | 23.79 |
| October | 402.50 | 22.61 | 2.50 | 22.62 | 0.00 | 22.62 |
| November | 506.50 | 21.46 | 0.00 | 21.46 | 0.00 | 21.46 |
| December | 533.00 | 21.14 | 111.00 | 21.14 | 111.00 | 21.13 |
| Annual Sum or Average | 4243.50 | 21.81 | 916.00 | 21.92 | 494.33 | 21.85 |
| Minimum of Months | 1.17 | 21.10 | 0.00 | 21.10 | 0.00 | 21.10 |
| Maximum of Months | 533.00 | 23.84 | 231.67 | 24.00 | 231.67 | 24.00 |
Report: ComfortReportSimple55Monthly
For: G S2 APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 533.00 | 21.10 | 317.17 | 21.10 | 317.17 | 21.10 |
| February | 473.00 | 21.16 | 162.83 | 21.14 | 162.83 | 21.14 |
| March | 506.00 | 21.36 | 13.33 | 21.35 | 13.33 | 21.34 |
| April | 477.50 | 21.88 | 0.00 | 21.88 | 0.00 | 21.88 |
| May | 422.67 | 22.94 | 16.17 | 22.98 | 0.00 | 22.98 |
| June | 208.50 | 23.50 | 4.83 | 23.51 | 0.00 | 23.51 |
| July | 44.50 | 23.86 | 127.00 | 23.96 | 0.00 | 23.96 |
| August | 0.00 | 0.00 | 224.33 | 24.00 | 0.00 | 24.00 |
| September | 66.00 | 23.50 | 130.67 | 23.83 | 0.00 | 23.83 |
| October | 389.50 | 22.65 | 2.83 | 22.66 | 0.00 | 22.66 |
| November | 503.67 | 21.47 | 1.17 | 21.47 | 1.17 | 21.47 |
| December | 533.00 | 21.14 | 166.83 | 21.13 | 166.83 | 21.12 |
| Annual Sum or Average | 4157.33 | 21.80 | 1167.17 | 21.92 | 661.33 | 21.83 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 21.10 | 0.00 | 21.10 |
| Maximum of Months | 533.00 | 23.86 | 317.17 | 24.00 | 317.17 | 24.00 |
Report: ComfortReportSimple55Monthly
For: M SW APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 533.00 | 21.11 | 163.50 | 21.11 | 163.50 | 21.11 |
| February | 473.00 | 21.34 | 94.17 | 21.30 | 94.17 | 21.27 |
| March | 502.83 | 21.89 | 6.00 | 21.88 | 6.00 | 21.87 |
| April | 424.00 | 22.65 | 10.50 | 22.69 | 0.00 | 22.69 |
| May | 272.67 | 23.24 | 36.67 | 23.33 | 0.00 | 23.33 |
| June | 105.00 | 23.51 | 45.67 | 23.66 | 0.00 | 23.66 |
| July | 31.33 | 23.87 | 175.00 | 23.98 | 0.00 | 23.98 |
| August | 9.00 | 23.72 | 215.33 | 23.99 | 0.00 | 23.99 |
| September | 84.83 | 23.47 | 112.67 | 23.77 | 0.00 | 23.77 |
| October | 419.83 | 22.58 | 8.17 | 22.61 | 0.00 | 22.61 |
| November | 490.67 | 21.41 | 7.67 | 21.41 | 5.50 | 21.41 |
| December | 533.00 | 21.19 | 96.67 | 21.17 | 96.67 | 21.16 |
| Annual Sum or Average | 3879.17 | 21.91 | 972.00 | 22.11 | 365.83 | 22.04 |
| Minimum of Months | 9.00 | 21.11 | 6.00 | 21.11 | 0.00 | 21.11 |
| Maximum of Months | 533.00 | 23.87 | 215.33 | 23.99 | 163.50 | 23.99 |
Report: ComfortReportSimple55Monthly
For: M NW APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 744.00 | 21.10 | 370.67 | 21.10 | 370.67 | 21.10 |
| February | 672.00 | 21.19 | 264.00 | 21.16 | 264.00 | 21.15 |
| March | 744.00 | 21.34 | 34.17 | 21.32 | 34.17 | 21.32 |
| April | 654.67 | 22.12 | 1.67 | 22.12 | 0.00 | 22.12 |
| May | 462.83 | 23.25 | 36.67 | 23.30 | 0.00 | 23.30 |
| June | 174.33 | 23.54 | 38.67 | 23.62 | 0.00 | 23.62 |
| July | 50.50 | 23.85 | 196.17 | 23.97 | 0.00 | 23.97 |
| August | 25.17 | 23.70 | 267.00 | 23.97 | 0.00 | 23.97 |
| September | 220.17 | 23.47 | 61.33 | 23.59 | 0.00 | 23.59 |
| October | 733.17 | 22.17 | 0.00 | 22.17 | 0.00 | 22.17 |
| November | 720.00 | 21.28 | 71.50 | 21.26 | 71.50 | 21.25 |
| December | 744.00 | 21.10 | 297.83 | 21.10 | 297.83 | 21.10 |
| Annual Sum or Average | 5944.83 | 21.77 | 1639.67 | 21.85 | 1038.17 | 21.76 |
| Minimum of Months | 25.17 | 21.10 | 0.00 | 21.10 | 0.00 | 21.10 |
| Maximum of Months | 744.00 | 23.85 | 370.67 | 23.97 | 370.67 | 23.97 |
Report: ComfortReportSimple55Monthly
For: M SE APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 533.00 | 21.11 | 165.00 | 21.11 | 165.00 | 21.11 |
| February | 473.00 | 21.32 | 93.83 | 21.28 | 93.83 | 21.26 |
| March | 504.83 | 21.88 | 4.50 | 21.88 | 4.50 | 21.87 |
| April | 428.83 | 22.74 | 12.17 | 22.78 | 0.00 | 22.78 |
| May | 289.50 | 23.23 | 32.67 | 23.31 | 0.00 | 23.31 |
| June | 96.83 | 23.46 | 47.33 | 23.64 | 0.00 | 23.64 |
| July | 36.00 | 23.83 | 150.83 | 23.97 | 0.00 | 23.97 |
| August | 18.83 | 23.67 | 200.17 | 23.97 | 0.00 | 23.97 |
| September | 96.00 | 23.44 | 100.00 | 23.73 | 0.00 | 23.73 |
| October | 420.67 | 22.58 | 8.83 | 22.61 | 0.00 | 22.61 |
| November | 490.33 | 21.40 | 6.67 | 21.41 | 5.83 | 21.40 |
| December | 533.00 | 21.18 | 101.17 | 21.17 | 101.17 | 21.16 |
| Annual Sum or Average | 3920.83 | 21.93 | 923.17 | 22.10 | 370.33 | 22.03 |
| Minimum of Months | 18.83 | 21.11 | 4.50 | 21.11 | 0.00 | 21.11 |
| Maximum of Months | 533.00 | 23.83 | 200.17 | 23.97 | 165.00 | 23.97 |
Report: ComfortReportSimple55Monthly
For: M NE APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 744.00 | 21.10 | 371.67 | 21.10 | 371.67 | 21.10 |
| February | 672.00 | 21.18 | 261.33 | 21.16 | 261.33 | 21.14 |
| March | 744.00 | 21.32 | 22.83 | 21.31 | 22.83 | 21.31 |
| April | 649.17 | 22.22 | 0.00 | 22.22 | 0.00 | 22.22 |
| May | 469.67 | 23.26 | 26.83 | 23.30 | 0.00 | 23.30 |
| June | 160.67 | 23.54 | 33.50 | 23.62 | 0.00 | 23.62 |
| July | 49.17 | 23.80 | 176.00 | 23.95 | 0.00 | 23.95 |
| August | 32.33 | 23.65 | 282.67 | 23.96 | 0.00 | 23.96 |
| September | 238.17 | 23.44 | 55.50 | 23.55 | 0.00 | 23.55 |
| October | 740.00 | 22.20 | 0.00 | 22.20 | 0.00 | 22.20 |
| November | 720.00 | 21.28 | 69.00 | 21.26 | 69.00 | 21.25 |
| December | 744.00 | 21.10 | 288.33 | 21.10 | 288.33 | 21.10 |
| Annual Sum or Average | 5963.17 | 21.78 | 1587.67 | 21.86 | 1013.17 | 21.77 |
| Minimum of Months | 32.33 | 21.10 | 0.00 | 21.10 | 0.00 | 21.10 |
| Maximum of Months | 744.00 | 23.80 | 371.67 | 23.96 | 371.67 | 23.96 |
Report: ComfortReportSimple55Monthly
For: M N1 APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 744.00 | 21.10 | 168.83 | 21.10 | 168.83 | 21.10 |
| February | 672.00 | 21.26 | 122.83 | 21.23 | 122.83 | 21.22 |
| March | 744.00 | 21.50 | 14.83 | 21.50 | 14.83 | 21.49 |
| April | 651.67 | 22.45 | 0.00 | 22.45 | 0.00 | 22.45 |
| May | 456.00 | 23.59 | 13.50 | 23.60 | 0.00 | 23.60 |
| June | 89.50 | 23.73 | 11.50 | 23.76 | 0.00 | 23.76 |
| July | 24.67 | 23.97 | 87.50 | 23.99 | 0.00 | 23.99 |
| August | 0.00 | 0.00 | 165.17 | 24.00 | 0.00 | 24.00 |
| September | 107.00 | 23.65 | 19.67 | 23.70 | 0.00 | 23.70 |
| October | 716.33 | 22.63 | 0.00 | 22.63 | 0.00 | 22.63 |
| November | 720.00 | 21.45 | 0.83 | 21.45 | 0.83 | 21.45 |
| December | 744.00 | 21.10 | 32.83 | 21.10 | 32.83 | 21.10 |
| Annual Sum or Average | 5669.17 | 21.87 | 637.50 | 21.93 | 340.17 | 21.88 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 21.10 | 0.00 | 21.10 |
| Maximum of Months | 744.00 | 23.97 | 168.83 | 24.00 | 168.83 | 24.00 |
Report: ComfortReportSimple55Monthly
For: M N2 APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 744.00 | 21.10 | 168.83 | 21.10 | 168.83 | 21.10 |
| February | 672.00 | 21.26 | 123.50 | 21.23 | 123.50 | 21.22 |
| March | 744.00 | 21.50 | 14.33 | 21.49 | 14.33 | 21.49 |
| April | 651.50 | 22.47 | 0.00 | 22.47 | 0.00 | 22.47 |
| May | 456.83 | 23.59 | 13.33 | 23.60 | 0.00 | 23.60 |
| June | 86.83 | 23.73 | 11.50 | 23.76 | 0.00 | 23.76 |
| July | 25.33 | 23.96 | 88.00 | 23.99 | 0.00 | 23.99 |
| August | 0.00 | 0.00 | 163.00 | 24.00 | 0.00 | 24.00 |
| September | 108.00 | 23.64 | 19.50 | 23.70 | 0.00 | 23.70 |
| October | 715.83 | 22.63 | 0.00 | 22.63 | 0.00 | 22.63 |
| November | 720.00 | 21.45 | 0.83 | 21.45 | 0.83 | 21.45 |
| December | 744.00 | 21.10 | 32.83 | 21.10 | 32.83 | 21.10 |
| Annual Sum or Average | 5668.33 | 21.87 | 635.67 | 21.93 | 340.33 | 21.89 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 21.10 | 0.00 | 21.10 |
| Maximum of Months | 744.00 | 23.96 | 168.83 | 24.00 | 168.83 | 24.00 |
Report: ComfortReportSimple55Monthly
For: M S1 APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 533.00 | 21.16 | 31.67 | 21.16 | 31.67 | 21.15 |
| February | 473.00 | 21.61 | 30.17 | 21.58 | 30.17 | 21.55 |
| March | 502.17 | 22.45 | 0.00 | 22.45 | 0.00 | 22.45 |
| April | 402.67 | 23.16 | 8.33 | 23.18 | 0.00 | 23.18 |
| May | 226.83 | 23.56 | 27.17 | 23.61 | 0.00 | 23.61 |
| June | 37.17 | 23.60 | 11.17 | 23.69 | 0.00 | 23.69 |
| July | 4.33 | 23.99 | 115.83 | 24.00 | 0.00 | 24.00 |
| August | 0.00 | 0.00 | 174.00 | 24.00 | 0.00 | 24.00 |
| September | 28.00 | 23.62 | 97.67 | 23.92 | 0.00 | 23.92 |
| October | 345.67 | 23.09 | 9.67 | 23.12 | 0.00 | 23.12 |
| November | 471.83 | 21.65 | 3.17 | 21.67 | 0.00 | 21.67 |
| December | 533.00 | 21.33 | 0.00 | 21.33 | 0.00 | 21.33 |
| Annual Sum or Average | 3557.67 | 22.11 | 508.83 | 22.30 | 61.83 | 22.28 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 21.16 | 0.00 | 21.15 |
| Maximum of Months | 533.00 | 23.99 | 174.00 | 24.00 | 31.67 | 24.00 |
Report: ComfortReportSimple55Monthly
For: M S2 APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 533.00 | 21.16 | 31.67 | 21.16 | 31.67 | 21.15 |
| February | 473.00 | 21.61 | 30.00 | 21.57 | 30.00 | 21.55 |
| March | 502.50 | 22.45 | 0.00 | 22.45 | 0.00 | 22.45 |
| April | 402.17 | 23.17 | 8.33 | 23.19 | 0.00 | 23.19 |
| May | 227.83 | 23.56 | 27.17 | 23.61 | 0.00 | 23.61 |
| June | 37.00 | 23.59 | 11.67 | 23.69 | 0.00 | 23.69 |
| July | 4.50 | 23.99 | 114.50 | 24.00 | 0.00 | 24.00 |
| August | 0.00 | 0.00 | 173.17 | 24.00 | 0.00 | 24.00 |
| September | 28.50 | 23.61 | 97.00 | 23.91 | 0.00 | 23.91 |
| October | 346.00 | 23.10 | 9.67 | 23.12 | 0.00 | 23.12 |
| November | 471.83 | 21.65 | 3.17 | 21.67 | 0.00 | 21.67 |
| December | 533.00 | 21.33 | 0.00 | 21.33 | 0.00 | 21.33 |
| Annual Sum or Average | 3559.33 | 22.11 | 506.33 | 22.30 | 61.67 | 22.28 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 21.16 | 0.00 | 21.15 |
| Maximum of Months | 533.00 | 23.99 | 173.17 | 24.00 | 31.67 | 24.00 |
Report: ComfortReportSimple55Monthly
For: T SW APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 533.00 | 21.11 | 490.50 | 21.10 | 490.50 | 21.10 |
| February | 471.67 | 21.23 | 280.67 | 21.18 | 280.67 | 21.16 |
| March | 495.33 | 21.43 | 186.17 | 21.34 | 185.33 | 21.29 |
| April | 444.17 | 21.77 | 71.50 | 21.79 | 51.50 | 21.73 |
| May | 378.00 | 22.02 | 64.17 | 22.26 | 7.50 | 22.24 |
| June | 289.50 | 22.59 | 83.17 | 22.91 | 0.00 | 22.91 |
| July | 240.67 | 23.06 | 161.17 | 23.44 | 0.00 | 23.44 |
| August | 196.67 | 22.98 | 160.83 | 23.44 | 0.00 | 23.44 |
| September | 322.67 | 22.46 | 89.17 | 22.79 | 0.00 | 22.79 |
| October | 485.00 | 21.69 | 24.50 | 21.72 | 14.00 | 21.70 |
| November | 496.50 | 21.22 | 267.50 | 21.20 | 261.00 | 21.18 |
| December | 533.00 | 21.16 | 429.50 | 21.13 | 429.50 | 21.12 |
| Annual Sum or Average | 4886.17 | 21.71 | 2308.83 | 21.75 | 1720.00 | 21.62 |
| Minimum of Months | 196.67 | 21.11 | 24.50 | 21.10 | 0.00 | 21.10 |
| Maximum of Months | 533.00 | 23.06 | 490.50 | 23.44 | 490.50 | 23.44 |
Report: ComfortReportSimple55Monthly
For: T NW APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 744.00 | 21.10 | 709.17 | 21.10 | 709.17 | 21.10 |
| February | 672.00 | 21.15 | 470.17 | 21.13 | 470.17 | 21.12 |
| March | 744.00 | 21.26 | 323.83 | 21.21 | 323.83 | 21.19 |
| April | 670.50 | 21.72 | 98.67 | 21.70 | 84.33 | 21.64 |
| May | 565.17 | 22.10 | 68.50 | 22.27 | 9.17 | 22.25 |
| June | 419.67 | 22.65 | 109.50 | 22.93 | 0.00 | 22.93 |
| July | 307.83 | 23.07 | 251.67 | 23.49 | 0.00 | 23.49 |
| August | 280.83 | 22.97 | 261.50 | 23.47 | 0.00 | 23.47 |
| September | 514.00 | 22.35 | 87.83 | 22.59 | 0.00 | 22.59 |
| October | 741.33 | 21.46 | 56.33 | 21.43 | 56.33 | 21.41 |
| November | 717.00 | 21.15 | 395.83 | 21.13 | 395.83 | 21.12 |
| December | 744.00 | 21.10 | 669.17 | 21.10 | 669.17 | 21.10 |
| Annual Sum or Average | 7120.33 | 21.64 | 3502.17 | 21.68 | 2718.00 | 21.56 |
| Minimum of Months | 280.83 | 21.10 | 56.33 | 21.10 | 0.00 | 21.10 |
| Maximum of Months | 744.00 | 23.07 | 709.17 | 23.49 | 709.17 | 23.49 |
Report: ComfortReportSimple55Monthly
For: T SE APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 533.00 | 21.11 | 491.33 | 21.10 | 491.33 | 21.10 |
| February | 472.67 | 21.22 | 284.17 | 21.17 | 284.17 | 21.15 |
| March | 496.33 | 21.41 | 184.83 | 21.33 | 184.00 | 21.28 |
| April | 448.50 | 21.80 | 70.33 | 21.82 | 51.17 | 21.75 |
| May | 385.17 | 22.02 | 51.50 | 22.21 | 7.50 | 22.19 |
| June | 287.83 | 22.60 | 83.50 | 22.92 | 0.00 | 22.92 |
| July | 244.00 | 23.04 | 147.00 | 23.40 | 0.00 | 23.40 |
| August | 186.67 | 22.97 | 153.83 | 23.44 | 0.00 | 23.44 |
| September | 333.17 | 22.44 | 80.00 | 22.74 | 0.00 | 22.74 |
| October | 484.67 | 21.68 | 24.17 | 21.70 | 15.50 | 21.69 |
| November | 497.17 | 21.22 | 268.83 | 21.20 | 263.33 | 21.17 |
| December | 533.00 | 21.16 | 431.33 | 21.13 | 431.33 | 21.12 |
| Annual Sum or Average | 4902.17 | 21.70 | 2270.83 | 21.73 | 1728.33 | 21.61 |
| Minimum of Months | 186.67 | 21.11 | 24.17 | 21.10 | 0.00 | 21.10 |
| Maximum of Months | 533.00 | 23.04 | 491.33 | 23.44 | 491.33 | 23.44 |
Report: ComfortReportSimple55Monthly
For: T NE APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 744.00 | 21.10 | 706.00 | 21.10 | 706.00 | 21.10 |
| February | 672.00 | 21.14 | 479.67 | 21.12 | 479.67 | 21.12 |
| March | 744.00 | 21.23 | 316.00 | 21.19 | 316.00 | 21.17 |
| April | 671.00 | 21.79 | 88.17 | 21.76 | 75.33 | 21.70 |
| May | 560.67 | 22.16 | 60.83 | 22.30 | 9.33 | 22.28 |
| June | 378.00 | 22.65 | 121.67 | 22.98 | 0.00 | 22.98 |
| July | 293.33 | 23.04 | 264.00 | 23.49 | 0.00 | 23.49 |
| August | 253.00 | 22.98 | 275.67 | 23.51 | 0.00 | 23.51 |
| September | 506.33 | 22.34 | 85.00 | 22.58 | 0.00 | 22.58 |
| October | 744.00 | 21.45 | 56.67 | 21.43 | 56.67 | 21.41 |
| November | 720.00 | 21.16 | 399.50 | 21.14 | 399.50 | 21.13 |
| December | 744.00 | 21.10 | 676.83 | 21.10 | 676.83 | 21.10 |
| Annual Sum or Average | 7030.33 | 21.63 | 3530.00 | 21.68 | 2719.33 | 21.56 |
| Minimum of Months | 253.00 | 21.10 | 56.67 | 21.10 | 0.00 | 21.10 |
| Maximum of Months | 744.00 | 23.04 | 706.00 | 23.51 | 706.00 | 23.51 |
Report: ComfortReportSimple55Monthly
For: T N1 APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 744.00 | 21.10 | 585.33 | 21.10 | 585.33 | 21.10 |
| February | 672.00 | 21.16 | 403.50 | 21.14 | 403.50 | 21.13 |
| March | 744.00 | 21.25 | 211.67 | 21.22 | 211.67 | 21.20 |
| April | 678.33 | 21.82 | 44.67 | 21.79 | 40.67 | 21.76 |
| May | 604.67 | 22.44 | 36.83 | 22.53 | 0.00 | 22.53 |
| June | 393.17 | 22.99 | 65.83 | 23.13 | 0.00 | 23.13 |
| July | 268.67 | 23.37 | 206.50 | 23.64 | 0.00 | 23.64 |
| August | 218.00 | 23.23 | 225.17 | 23.62 | 0.00 | 23.62 |
| September | 519.33 | 22.69 | 44.83 | 22.79 | 0.00 | 22.79 |
| October | 744.00 | 21.51 | 0.00 | 21.51 | 0.00 | 21.51 |
| November | 720.00 | 21.19 | 334.00 | 21.16 | 334.00 | 21.15 |
| December | 744.00 | 21.10 | 618.17 | 21.10 | 618.17 | 21.10 |
| Annual Sum or Average | 7050.17 | 21.73 | 2776.50 | 21.73 | 2193.33 | 21.61 |
| Minimum of Months | 218.00 | 21.10 | 0.00 | 21.10 | 0.00 | 21.10 |
| Maximum of Months | 744.00 | 23.37 | 618.17 | 23.64 | 618.17 | 23.64 |
Report: ComfortReportSimple55Monthly
For: T N2 APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 744.00 | 21.10 | 584.50 | 21.10 | 584.50 | 21.10 |
| February | 672.00 | 21.16 | 403.83 | 21.14 | 403.83 | 21.13 |
| March | 744.00 | 21.25 | 211.83 | 21.22 | 211.83 | 21.19 |
| April | 677.83 | 21.83 | 44.67 | 21.80 | 40.50 | 21.76 |
| May | 605.17 | 22.44 | 37.33 | 22.53 | 0.00 | 22.53 |
| June | 387.67 | 22.98 | 67.00 | 23.13 | 0.00 | 23.13 |
| July | 269.00 | 23.37 | 207.83 | 23.64 | 0.00 | 23.64 |
| August | 216.67 | 23.23 | 225.50 | 23.62 | 0.00 | 23.62 |
| September | 520.33 | 22.68 | 45.33 | 22.79 | 0.00 | 22.79 |
| October | 744.00 | 21.51 | 0.00 | 21.51 | 0.00 | 21.51 |
| November | 720.00 | 21.19 | 335.00 | 21.16 | 335.00 | 21.15 |
| December | 744.00 | 21.10 | 618.50 | 21.10 | 618.50 | 21.10 |
| Annual Sum or Average | 7044.67 | 21.73 | 2781.33 | 21.73 | 2194.17 | 21.61 |
| Minimum of Months | 216.67 | 21.10 | 0.00 | 21.10 | 0.00 | 21.10 |
| Maximum of Months | 744.00 | 23.37 | 618.50 | 23.64 | 618.50 | 23.64 |
Report: ComfortReportSimple55Monthly
For: T S1 APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 533.00 | 21.12 | 369.00 | 21.11 | 369.00 | 21.11 |
| February | 471.33 | 21.31 | 210.33 | 21.24 | 210.33 | 21.21 |
| March | 498.33 | 21.57 | 83.83 | 21.50 | 83.83 | 21.45 |
| April | 446.17 | 22.01 | 32.67 | 22.04 | 18.00 | 22.01 |
| May | 378.17 | 22.33 | 35.00 | 22.47 | 0.00 | 22.47 |
| June | 267.17 | 22.94 | 59.50 | 23.13 | 0.00 | 23.13 |
| July | 202.67 | 23.36 | 136.50 | 23.62 | 0.00 | 23.62 |
| August | 142.33 | 23.23 | 147.67 | 23.62 | 0.00 | 23.62 |
| September | 290.33 | 22.80 | 79.00 | 23.05 | 0.00 | 23.05 |
| October | 475.50 | 21.92 | 9.00 | 21.96 | 0.00 | 21.96 |
| November | 492.33 | 21.28 | 181.00 | 21.26 | 174.17 | 21.23 |
| December | 533.00 | 21.19 | 330.00 | 21.16 | 330.00 | 21.14 |
| Annual Sum or Average | 4730.33 | 21.84 | 1673.50 | 21.87 | 1185.33 | 21.75 |
| Minimum of Months | 142.33 | 21.12 | 9.00 | 21.11 | 0.00 | 21.11 |
| Maximum of Months | 533.00 | 23.36 | 369.00 | 23.62 | 369.00 | 23.62 |
Report: ComfortReportSimple55Monthly
For: T S2 APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 533.00 | 21.12 | 368.50 | 21.11 | 368.50 | 21.11 |
| February | 471.50 | 21.31 | 211.17 | 21.24 | 211.17 | 21.21 |
| March | 498.50 | 21.56 | 83.67 | 21.50 | 83.67 | 21.45 |
| April | 446.67 | 22.02 | 33.67 | 22.04 | 18.83 | 22.01 |
| May | 379.00 | 22.33 | 35.33 | 22.47 | 0.00 | 22.47 |
| June | 266.50 | 22.94 | 60.17 | 23.13 | 0.00 | 23.13 |
| July | 204.67 | 23.36 | 135.17 | 23.61 | 0.00 | 23.61 |
| August | 142.67 | 23.23 | 147.50 | 23.62 | 0.00 | 23.62 |
| September | 292.50 | 22.79 | 78.50 | 23.05 | 0.00 | 23.05 |
| October | 475.50 | 21.92 | 9.17 | 21.96 | 0.00 | 21.96 |
| November | 492.50 | 21.28 | 181.17 | 21.26 | 174.17 | 21.23 |
| December | 533.00 | 21.19 | 330.17 | 21.16 | 330.17 | 21.14 |
| Annual Sum or Average | 4736.00 | 21.84 | 1674.17 | 21.87 | 1186.50 | 21.75 |
| Minimum of Months | 142.67 | 21.12 | 9.17 | 21.11 | 0.00 | 21.11 |
| Maximum of Months | 533.00 | 23.36 | 368.50 | 23.62 | 368.50 | 23.62 |
Report: ComfortReportSimple55Monthly
For: T CORRIDOR
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 744.00 | 20.40 | 195.83 | 20.33 | 195.83 | 20.27 |
| February | 672.00 | 20.94 | 358.83 | 20.96 | 358.83 | 20.97 |
| March | 744.00 | 21.68 | 472.33 | 21.71 | 472.33 | 21.72 |
| April | 699.17 | 22.79 | 571.67 | 22.92 | 558.33 | 22.95 |
| May | 736.17 | 23.81 | 723.50 | 23.83 | 716.50 | 23.83 |
| June | 716.17 | 24.72 | 716.33 | 24.72 | 714.17 | 24.72 |
| July | 744.00 | 25.28 | 744.00 | 25.28 | 744.00 | 25.28 |
| August | 744.00 | 25.31 | 744.00 | 25.31 | 744.00 | 25.31 |
| September | 720.00 | 24.22 | 720.00 | 24.22 | 720.00 | 24.22 |
| October | 739.33 | 22.32 | 685.33 | 22.36 | 680.67 | 22.37 |
| November | 720.00 | 21.10 | 519.17 | 21.14 | 519.17 | 21.15 |
| December | 744.00 | 20.54 | 310.33 | 20.52 | 310.33 | 20.51 |
| Annual Sum or Average | 8722.83 | 22.77 | 6761.33 | 23.01 | 6734.17 | 23.10 |
| Minimum of Months | 672.00 | 20.40 | 195.83 | 20.33 | 195.83 | 20.27 |
| Maximum of Months | 744.00 | 25.31 | 744.00 | 25.31 | 744.00 | 25.31 |
Report: ComfortReportSimple55Monthly
For: G CORRIDOR
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 744.00 | 18.19 | 731.67 | 18.17 | 731.67 | 18.16 |
| February | 672.00 | 18.75 | 567.67 | 18.57 | 567.67 | 18.50 |
| March | 744.00 | 19.74 | 463.33 | 19.42 | 463.33 | 19.27 |
| April | 699.33 | 20.80 | 187.33 | 20.40 | 184.50 | 20.13 |
| May | 633.83 | 22.08 | 100.33 | 22.17 | 43.17 | 22.04 |
| June | 366.50 | 22.90 | 260.33 | 23.73 | 52.33 | 23.79 |
| July | 213.33 | 23.95 | 526.50 | 24.92 | 106.50 | 24.99 |
| August | 213.17 | 24.66 | 590.83 | 25.31 | 154.00 | 25.37 |
| September | 383.67 | 23.11 | 337.17 | 23.97 | 102.83 | 24.08 |
| October | 687.17 | 21.47 | 94.33 | 21.27 | 76.33 | 21.05 |
| November | 720.00 | 19.69 | 443.00 | 19.31 | 443.00 | 19.13 |
| December | 744.00 | 18.59 | 693.67 | 18.51 | 693.67 | 18.49 |
| Annual Sum or Average | 6821.00 | 20.49 | 4996.17 | 20.67 | 3619.00 | 20.35 |
| Minimum of Months | 213.17 | 18.19 | 94.33 | 18.17 | 43.17 | 18.16 |
| Maximum of Months | 744.00 | 24.66 | 731.67 | 25.31 | 731.67 | 25.37 |
Report: ComfortReportSimple55Monthly
For: M CORRIDOR
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 744.00 | 21.85 | 666.00 | 21.86 | 666.00 | 21.86 |
| February | 672.00 | 22.30 | 590.17 | 22.34 | 590.17 | 22.35 |
| March | 744.00 | 23.07 | 739.50 | 23.07 | 739.50 | 23.07 |
| April | 720.00 | 24.18 | 720.00 | 24.18 | 720.00 | 24.18 |
| May | 744.00 | 25.24 | 744.00 | 25.24 | 744.00 | 25.24 |
| June | 720.00 | 25.63 | 720.00 | 25.63 | 720.00 | 25.63 |
| July | 744.00 | 25.82 | 744.00 | 25.82 | 744.00 | 25.82 |
| August | 744.00 | 25.83 | 744.00 | 25.83 | 744.00 | 25.83 |
| September | 720.00 | 25.52 | 720.00 | 25.52 | 720.00 | 25.52 |
| October | 744.00 | 24.14 | 744.00 | 24.14 | 744.00 | 24.14 |
| November | 720.00 | 22.53 | 686.83 | 22.55 | 686.83 | 22.56 |
| December | 744.00 | 21.98 | 688.00 | 21.97 | 688.00 | 21.97 |
| Annual Sum or Average | 8760.00 | 24.02 | 8506.50 | 24.05 | 8506.50 | 24.06 |
| Minimum of Months | 672.00 | 21.85 | 590.17 | 21.86 | 590.17 | 21.86 |
| Maximum of Months | 744.00 | 25.83 | 744.00 | 25.83 | 744.00 | 25.83 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_GSW
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 515.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 492.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 524.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 6145.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_GNW
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 8760.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_OFFICE
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 140.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 133.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 161.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 140.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 154.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 154.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 140.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 161.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 140.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 147.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 140.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 140.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 1750.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 133.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 161.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_GNE
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 8760.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_GN1
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 8760.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_GN2
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 8760.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_GS1
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 515.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 492.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 524.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 6145.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_GS2
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 515.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 492.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 524.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 6145.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_MSW
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 515.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 492.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 524.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 6145.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_MNW
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 8760.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_MSE
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 515.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 492.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 524.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 6145.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_MNE
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 8760.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_MN1
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 8760.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_MN2
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 8760.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_MS1
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 515.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 492.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 524.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 6145.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_MS2
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 515.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 492.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 524.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 6145.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_TSW
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 515.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 492.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 524.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 6145.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_TNW
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 8760.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_TSE
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 515.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 492.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 524.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 6145.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_TNE
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 8760.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_TN1
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 8760.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_TN2
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 8760.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_TS1
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 515.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 492.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 524.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 6145.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_TS2
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 515.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 492.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 524.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 6145.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_T CORRIDOR
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 8760.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_G CORRIDOR
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 8760.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_M CORRIDOR
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 8760.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: DXReportMonthly
For: SPLIT GSW COOLING COIL
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
| April | 69879514.27 | 18229713.71 | 38.67 | 68323616.03 | 1555898.24 | 0.00 | 0.25 | 27-APR-16:07 | 0.00 | 01-APR-00:10 | 1311.08 | 27-APR-16:07 | 1285.94 | 27-APR-16:07 | 53.46 | 29-APR-14:10 | 346.47 | 27-APR-16:07 | 0.00 | 01-APR-00:10 |
| May | 0.237133E+09 | 60538804.61 | 116.31 | 0.224544E+09 | 12588984.16 | 0.00 | 0.30 | 15-MAY-16:15 | 0.00 | 01-MAY-00:10 | 1542.78 | 15-MAY-16:15 | 1542.78 | 15-MAY-16:15 | 173.32 | 07-MAY-16:03 | 392.42 | 15-MAY-16:15 | 0.00 | 01-MAY-00:10 |
| June | 0.504005E+09 | 0.129155E+09 | 271.37 | 0.493423E+09 | 10582628.23 | 0.00 | 0.34 | 28-JUN-16:40 | 0.00 | 01-JUN-00:10 | 1786.47 | 28-JUN-16:40 | 1786.47 | 28-JUN-16:40 | 76.87 | 22-JUN-19:00 | 463.91 | 28-JUN-16:50 | 0.00 | 01-JUN-00:10 |
| July | 0.146726E+10 | 0.372785E+09 | 564.94 | 0.136721E+10 | 0.100049E+09 | 0.00 | 0.45 | 31-JUL-16:04 | 0.00 | 01-JUL-00:10 | 2411.89 | 31-JUL-16:15 | 2246.72 | 31-JUL-16:15 | 247.94 | 15-JUL-18:00 | 631.49 | 31-JUL-16:04 | 0.00 | 01-JUL-00:10 |
| August | 0.185796E+10 | 0.473457E+09 | 594.59 | 0.170976E+10 | 0.148205E+09 | 0.00 | 0.52 | 10-AUG-17:20 | 0.00 | 01-AUG-12:35 | 2753.73 | 10-AUG-17:20 | 2682.27 | 10-AUG-17:07 | 297.91 | 30-AUG-13:20 | 747.20 | 10-AUG-16:40 | 0.00 | 01-AUG-00:10 |
| September | 0.985892E+09 | 0.247882E+09 | 432.57 | 0.913826E+09 | 72065078.27 | 0.00 | 0.42 | 14-SEP-16:04 | 0.00 | 01-SEP-07:35 | 2292.84 | 14-SEP-16:02 | 2160.43 | 14-SEP-16:04 | 267.01 | 14-SEP-13:20 | 565.09 | 14-SEP-16:04 | 0.00 | 01-SEP-00:10 |
| October | 0.164378E+09 | 42617033.07 | 118.83 | 0.163324E+09 | 1053817.64 | 0.00 | 0.31 | 04-OCT-15:10 | 0.00 | 01-OCT-00:10 | 1628.75 | 04-OCT-15:10 | 1628.75 | 04-OCT-15:10 | 41.76 | 08-OCT-13:40 | 413.59 | 04-OCT-15:10 | 0.00 | 01-OCT-00:10 |
| November | 4295030.60 | 1092120.85 | 4.00 | 3662336.03 | 632694.58 | 0.00 | 0.08 | 04-NOV-15:10 | 0.00 | 01-NOV-00:10 | 441.34 | 04-NOV-15:10 | 380.77 | 04-NOV-15:10 | 60.56 | 04-NOV-15:10 | 112.10 | 04-NOV-15:10 | 0.00 | 01-NOV-00:10 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.529080E+10 | 0.134576E+10 | 2141.28 | 0.494407E+10 | 0.346733E+09 | 0.00 | ||||||||||||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Maximum of Months | 0.185796E+10 | 0.473457E+09 | 594.59 | 0.170976E+10 | 0.148205E+09 | 0.00 | 0.52 | 0.00 | 2753.73 | 2682.27 | 297.91 | 747.20 | 0.00 |
Report: DXReportMonthly
For: SPLIT GNW COOLING COIL
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
| April | 7561143.85 | 2005689.99 | 7.08 | 7226750.72 | 334393.12 | 0.00 | 0.12 | 27-APR-17:30 | 0.00 | 01-APR-00:10 | 542.00 | 27-APR-17:30 | 515.22 | 27-APR-17:30 | 26.84 | 27-APR-17:40 | 143.46 | 27-APR-17:30 | 0.00 | 01-APR-00:10 |
| May | 75952890.74 | 19468483.89 | 56.03 | 70325279.77 | 5627610.97 | 0.00 | 0.20 | 15-MAY-16:30 | 0.00 | 01-MAY-00:10 | 881.56 | 15-MAY-16:30 | 881.56 | 15-MAY-16:30 | 115.69 | 07-MAY-16:15 | 227.61 | 15-MAY-16:30 | 0.00 | 01-MAY-00:10 |
| June | 0.292256E+09 | 74928460.67 | 181.84 | 0.285381E+09 | 6875236.33 | 0.00 | 0.34 | 28-JUN-17:40 | 0.00 | 01-JUN-00:10 | 1531.18 | 28-JUN-18:00 | 1498.57 | 28-JUN-17:15 | 74.40 | 22-JUN-19:00 | 392.27 | 28-JUN-17:20 | 0.00 | 01-JUN-00:10 |
| July | 0.998129E+09 | 0.253817E+09 | 469.38 | 0.920926E+09 | 77202906.40 | 0.00 | 0.45 | 24-JUL-18:00 | 0.00 | 01-JUL-00:10 | 2013.97 | 24-JUL-18:00 | 1906.75 | 24-JUL-18:00 | 235.69 | 15-JUL-18:30 | 529.28 | 24-JUL-18:00 | 0.00 | 01-JUL-00:10 |
| August | 0.120395E+10 | 0.308309E+09 | 517.47 | 0.109396E+10 | 0.109990E+09 | 0.00 | 0.50 | 10-AUG-17:30 | 0.00 | 01-AUG-04:00 | 2236.38 | 10-AUG-18:00 | 2136.22 | 10-AUG-17:30 | 211.07 | 30-AUG-13:30 | 604.25 | 10-AUG-17:20 | 0.00 | 01-AUG-00:10 |
| September | 0.307762E+09 | 77887049.39 | 202.20 | 0.279338E+09 | 28424436.23 | 0.00 | 0.32 | 14-SEP-16:25 | 0.00 | 01-SEP-03:00 | 1447.84 | 14-SEP-16:25 | 1308.86 | 14-SEP-16:30 | 174.81 | 14-SEP-13:50 | 361.65 | 14-SEP-16:25 | 0.00 | 01-SEP-00:10 |
| October | 2173522.56 | 574498.75 | 3.33 | 2173522.56 | -0.0 | 0.00 | 0.07 | 04-OCT-16:30 | 0.00 | 01-OCT-00:10 | 288.49 | 04-OCT-16:30 | 288.49 | 04-OCT-16:30 | 0.00 | 04-OCT-16:05 | 76.07 | 04-OCT-16:30 | 0.00 | 01-OCT-00:10 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.288779E+10 | 0.736990E+09 | 1437.32 | 0.265933E+10 | 0.228454E+09 | 0.00 | ||||||||||||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | -0.0 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Maximum of Months | 0.120395E+10 | 0.308309E+09 | 517.47 | 0.109396E+10 | 0.109990E+09 | 0.00 | 0.50 | 0.00 | 2236.38 | 2136.22 | 235.69 | 604.25 | 0.00 |
Report: DXReportMonthly
For: SPLIT OFFICE COOLING COIL
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| February | 549171.29 | 145281.40 | 2.00 | 549171.29 | -0.0 | 0.00 | 0.02 | 27-FEB-15:30 | 0.00 | 01-FEB-00:10 | 135.55 | 27-FEB-15:30 | 135.55 | 27-FEB-15:30 | 0.00 | 27-FEB-16:30 | 35.83 | 27-FEB-15:30 | 0.00 | 01-FEB-00:10 |
| March | 7371459.68 | 1959237.59 | 9.67 | 7371459.68 | 0.00 | 0.00 | 0.06 | 02-MAR-14:00 | 0.00 | 01-MAR-00:10 | 352.85 | 02-MAR-14:00 | 352.85 | 02-MAR-14:00 | 0.00 | 02-MAR-13:20 | 93.52 | 02-MAR-14:00 | 0.00 | 01-MAR-00:10 |
| April | 0.131514E+09 | 33915788.89 | 58.86 | 0.128287E+09 | 3227088.42 | 0.00 | 0.54 | 27-APR-08:63 | 0.00 | 01-APR-00:10 | 3293.00 | 27-APR-08:63 | 3293.00 | 27-APR-08:63 | 161.66 | 28-APR-13:10 | 797.35 | 27-APR-08:63 | 0.00 | 01-APR-00:10 |
| May | 0.444120E+09 | 0.113323E+09 | 158.64 | 0.427000E+09 | 17119489.62 | 0.00 | 1.00 | 15-MAY-08:62 | 0.00 | 01-MAY-00:10 | 6618.38 | 05-MAY-08:62 | 6573.06 | 05-MAY-08:62 | 183.00 | 05-MAY-16:00 | 1470.57 | 05-MAY-08:62 | 0.00 | 01-MAY-00:10 |
| June | 0.858888E+09 | 0.216107E+09 | 181.18 | 0.824048E+09 | 34840236.30 | 0.00 | 1.00 | 09-JUN-08:62 | 0.00 | 01-JUN-00:10 | 6849.32 | 12-JUN-08:62 | 6654.28 | 20-JUN-08:62 | 959.18 | 12-JUN-08:62 | 1489.78 | 12-JUN-08:62 | 0.00 | 01-JUN-00:10 |
| July | 0.130980E+10 | 0.323988E+09 | 178.58 | 0.122040E+10 | 89401905.23 | 0.00 | 1.00 | 05-JUL-08:62 | 0.00 | 01-JUL-00:10 | 6939.97 | 31-JUL-07:02 | 6854.75 | 24-JUL-07:02 | 1081.20 | 11-JUL-08:62 | 1494.10 | 31-JUL-07:02 | 0.00 | 01-JUL-00:10 |
| August | 0.187310E+10 | 0.461486E+09 | 217.39 | 0.171073E+10 | 0.162370E+09 | 0.00 | 1.00 | 01-AUG-08:62 | 0.00 | 01-AUG-00:10 | 6979.71 | 30-AUG-08:62 | 6688.64 | 15-AUG-07:01 | 1438.36 | 30-AUG-08:62 | 1495.58 | 30-AUG-08:62 | 0.00 | 01-AUG-00:10 |
| September | 0.104129E+10 | 0.256178E+09 | 168.41 | 0.960334E+09 | 80955661.50 | 0.00 | 1.00 | 01-SEP-08:62 | 0.00 | 01-SEP-00:10 | 6896.49 | 25-SEP-08:62 | 6452.76 | 11-SEP-08:62 | 1224.78 | 25-SEP-08:62 | 1492.19 | 25-SEP-08:62 | 0.00 | 01-SEP-00:10 |
| October | 0.324380E+09 | 83058714.21 | 99.31 | 0.322191E+09 | 2188829.59 | 0.00 | 1.00 | 04-OCT-08:62 | 0.00 | 01-OCT-00:10 | 6525.76 | 04-OCT-08:62 | 6525.76 | 04-OCT-08:62 | 220.00 | 06-OCT-08:63 | 1463.94 | 04-OCT-08:62 | 0.00 | 01-OCT-00:10 |
| November | 2375242.27 | 626370.44 | 7.50 | 2311167.89 | 64074.38 | 0.00 | 0.03 | 06-NOV-12:00 | 0.00 | 01-NOV-00:10 | 168.89 | 06-NOV-12:00 | 168.89 | 06-NOV-12:00 | 8.24 | 02-NOV-13:30 | 44.65 | 06-NOV-12:00 | 0.00 | 01-NOV-00:10 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.599338E+10 | 0.149079E+10 | 1081.53 | 0.560321E+10 | 0.390167E+09 | 0.00 | ||||||||||||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | -0.0 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Maximum of Months | 0.187310E+10 | 0.461486E+09 | 217.39 | 0.171073E+10 | 0.162370E+09 | 0.00 | 1.00 | 0.00 | 6979.71 | 6854.75 | 1438.36 | 1495.58 | 0.00 |
Report: DXReportMonthly
For: SPLIT GNE COOLING COIL
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
| April | 3976557.35 | 1065211.42 | 5.50 | 3805261.68 | 171295.68 | 0.00 | 0.08 | 27-APR-18:00 | 0.00 | 01-APR-00:10 | 307.76 | 27-APR-18:00 | 292.97 | 27-APR-16:03 | 16.24 | 27-APR-17:50 | 82.57 | 27-APR-16:03 | 0.00 | 01-APR-00:10 |
| May | 55994218.90 | 14369006.99 | 50.58 | 51518487.38 | 4475731.52 | 0.00 | 0.16 | 15-MAY-17:00 | 0.00 | 01-MAY-00:10 | 631.79 | 06-MAY-13:30 | 609.01 | 15-MAY-17:00 | 88.43 | 06-MAY-13:30 | 158.87 | 15-MAY-17:00 | 0.00 | 01-MAY-00:10 |
| June | 0.302252E+09 | 77500968.71 | 209.18 | 0.293888E+09 | 8364100.39 | 0.00 | 0.31 | 28-JUN-17:40 | 0.00 | 01-JUN-00:10 | 1206.26 | 28-JUN-18:00 | 1180.03 | 28-JUN-17:20 | 100.06 | 12-JUN-17:08 | 310.66 | 28-JUN-17:20 | 0.00 | 01-JUN-00:10 |
| July | 0.881836E+09 | 0.224393E+09 | 438.07 | 0.812714E+09 | 69121223.78 | 0.00 | 0.44 | 24-JUL-18:00 | 0.00 | 01-JUL-00:10 | 1758.00 | 24-JUL-18:00 | 1659.91 | 24-JUL-18:00 | 211.80 | 31-JUL-10:20 | 462.07 | 24-JUL-18:00 | 0.00 | 01-JUL-00:10 |
| August | 0.120621E+10 | 0.307477E+09 | 524.67 | 0.109164E+10 | 0.114573E+09 | 0.00 | 0.45 | 10-AUG-17:07 | 0.00 | 01-AUG-03:20 | 1769.83 | 10-AUG-17:07 | 1692.81 | 10-AUG-17:07 | 218.98 | 25-AUG-11:20 | 485.77 | 10-AUG-17:00 | 0.00 | 01-AUG-00:10 |
| September | 0.284029E+09 | 71751064.41 | 194.61 | 0.255026E+09 | 29002656.49 | 0.00 | 0.29 | 14-SEP-16:40 | 0.00 | 01-SEP-00:10 | 1155.65 | 14-SEP-16:40 | 1044.95 | 14-SEP-17:00 | 171.88 | 14-SEP-13:20 | 290.50 | 14-SEP-17:00 | 0.00 | 01-SEP-00:10 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.273430E+10 | 0.696556E+09 | 1422.62 | 0.250859E+10 | 0.225708E+09 | 0.00 | ||||||||||||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Maximum of Months | 0.120621E+10 | 0.307477E+09 | 524.67 | 0.109164E+10 | 0.114573E+09 | 0.00 | 0.45 | 0.00 | 1769.83 | 1692.81 | 218.98 | 485.77 | 0.00 |
Report: DXReportMonthly
For: SPLIT GN1 COOLING COIL
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
| April | 220658.80 | 59211.62 | 1.33 | 208264.20 | 12394.60 | 0.00 | 0.02 | 27-APR-18:00 | 0.00 | 01-APR-00:10 | 72.49 | 27-APR-18:00 | 68.34 | 27-APR-18:00 | 4.15 | 27-APR-18:00 | 19.47 | 27-APR-18:00 | 0.00 | 01-APR-00:10 |
| May | 43432503.66 | 11123972.61 | 48.75 | 39281579.11 | 4150924.55 | 0.00 | 0.15 | 05-MAY-16:07 | 0.00 | 01-MAY-00:10 | 523.85 | 05-MAY-16:10 | 465.79 | 15-MAY-17:00 | 74.89 | 07-MAY-16:07 | 133.89 | 05-MAY-16:07 | 0.00 | 01-MAY-00:10 |
| June | 0.237707E+09 | 61093956.25 | 212.97 | 0.230332E+09 | 7375299.37 | 0.00 | 0.29 | 28-JUN-18:00 | 0.00 | 01-JUN-00:10 | 1040.39 | 28-JUN-18:00 | 1008.51 | 28-JUN-17:50 | 91.74 | 12-JUN-17:15 | 266.95 | 28-JUN-18:00 | 0.00 | 01-JUN-00:10 |
| July | 0.786698E+09 | 0.200687E+09 | 547.34 | 0.719460E+09 | 67238195.82 | 0.00 | 0.40 | 24-JUL-18:00 | 0.00 | 01-JUL-01:20 | 1439.20 | 24-JUL-18:00 | 1349.96 | 24-JUL-18:00 | 169.93 | 15-JUL-18:40 | 380.62 | 24-JUL-18:00 | 0.00 | 01-JUL-00:10 |
| August | 0.103043E+10 | 0.263680E+09 | 587.12 | 0.925664E+09 | 0.104768E+09 | 0.00 | 0.42 | 10-AUG-17:07 | 0.00 | 01-AUG-04:00 | 1478.76 | 10-AUG-18:40 | 1392.10 | 10-AUG-17:07 | 185.17 | 30-AUG-13:20 | 404.79 | 10-AUG-17:07 | 0.00 | 01-AUG-00:10 |
| September | 0.240743E+09 | 61052371.36 | 239.74 | 0.215515E+09 | 25227980.05 | 0.00 | 0.27 | 14-SEP-17:00 | 0.00 | 01-SEP-07:35 | 977.41 | 14-SEP-16:50 | 874.74 | 14-SEP-17:00 | 140.61 | 14-SEP-13:30 | 246.74 | 14-SEP-17:00 | 0.00 | 01-SEP-00:10 |
| October | 135154.54 | 35930.86 | 0.93 | 135154.54 | 0.00 | 0.00 | 0.03 | 04-OCT-16:10 | 0.00 | 01-OCT-00:10 | 89.57 | 04-OCT-16:10 | 89.57 | 04-OCT-16:10 | 0.00 | 04-OCT-16:50 | 23.77 | 04-OCT-16:10 | 0.00 | 01-OCT-00:10 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.233937E+10 | 0.597732E+09 | 1638.19 | 0.213060E+10 | 0.208773E+09 | 0.00 | ||||||||||||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Maximum of Months | 0.103043E+10 | 0.263680E+09 | 587.12 | 0.925664E+09 | 0.104768E+09 | 0.00 | 0.42 | 0.00 | 1478.76 | 1392.10 | 185.17 | 404.79 | 0.00 |
Report: DXReportMonthly
For: SPLIT GN2 COOLING COIL
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
| April | 218776.80 | 58710.43 | 1.33 | 206491.76 | 12285.03 | 0.00 | 0.02 | 27-APR-18:00 | 0.00 | 01-APR-00:10 | 71.59 | 27-APR-18:00 | 67.49 | 27-APR-18:00 | 4.10 | 27-APR-18:00 | 19.23 | 27-APR-18:00 | 0.00 | 01-APR-00:10 |
| May | 43192833.43 | 11063508.70 | 48.30 | 39074059.75 | 4118773.68 | 0.00 | 0.15 | 06-MAY-15:10 | 0.00 | 01-MAY-00:10 | 523.09 | 06-MAY-15:10 | 464.97 | 15-MAY-17:00 | 74.28 | 07-MAY-16:07 | 132.73 | 05-MAY-16:07 | 0.00 | 01-MAY-00:10 |
| June | 0.241267E+09 | 61998817.80 | 214.94 | 0.233680E+09 | 7586410.70 | 0.00 | 0.29 | 28-JUN-18:00 | 0.00 | 01-JUN-00:10 | 1035.40 | 28-JUN-18:00 | 1003.80 | 28-JUN-17:50 | 100.55 | 12-JUN-17:15 | 265.69 | 28-JUN-18:00 | 0.00 | 01-JUN-00:10 |
| July | 0.778772E+09 | 0.198682E+09 | 541.56 | 0.712294E+09 | 66478520.78 | 0.00 | 0.40 | 24-JUL-18:00 | 0.00 | 01-JUL-01:10 | 1435.10 | 24-JUL-18:00 | 1346.10 | 24-JUL-18:00 | 166.75 | 15-JUL-18:40 | 379.53 | 24-JUL-18:00 | 0.00 | 01-JUL-00:10 |
| August | 0.103182E+10 | 0.263999E+09 | 586.95 | 0.926834E+09 | 0.104985E+09 | 0.00 | 0.41 | 10-AUG-17:07 | 0.00 | 01-AUG-03:50 | 1470.04 | 10-AUG-18:40 | 1386.37 | 10-AUG-17:07 | 185.83 | 30-AUG-13:20 | 403.15 | 10-AUG-17:07 | 0.00 | 01-AUG-00:10 |
| September | 0.239339E+09 | 60684752.45 | 236.82 | 0.214141E+09 | 25197754.67 | 0.00 | 0.27 | 14-SEP-17:00 | 0.00 | 01-SEP-07:35 | 974.37 | 14-SEP-16:50 | 872.14 | 14-SEP-17:00 | 141.57 | 14-SEP-13:30 | 245.97 | 14-SEP-17:00 | 0.00 | 01-SEP-00:10 |
| October | 39992.01 | 10638.53 | 0.38 | 39992.01 | 0.00 | 0.00 | 0.01 | 04-OCT-16:30 | 0.00 | 01-OCT-00:10 | 34.91 | 04-OCT-16:30 | 34.91 | 04-OCT-16:30 | 0.00 | 04-OCT-16:15 | 9.28 | 04-OCT-16:30 | 0.00 | 01-OCT-00:10 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.233465E+10 | 0.596498E+09 | 1630.27 | 0.212627E+10 | 0.208379E+09 | 0.00 | ||||||||||||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Maximum of Months | 0.103182E+10 | 0.263999E+09 | 586.95 | 0.926834E+09 | 0.104985E+09 | 0.00 | 0.41 | 0.00 | 1470.04 | 1386.37 | 185.83 | 403.15 | 0.00 |
Report: DXReportMonthly
For: SPLIT GS1 COOLING COIL
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
| April | 54497159.81 | 14221078.26 | 41.74 | 53076599.09 | 1420560.72 | 0.00 | 0.22 | 27-APR-15:10 | 0.00 | 01-APR-00:10 | 945.95 | 27-APR-15:10 | 936.95 | 27-APR-15:10 | 48.90 | 29-APR-14:10 | 252.31 | 27-APR-15:10 | 0.00 | 01-APR-00:10 |
| May | 0.217304E+09 | 55507717.06 | 140.57 | 0.204717E+09 | 12586752.14 | 0.00 | 0.25 | 15-MAY-16:05 | 0.00 | 01-MAY-00:10 | 1118.95 | 07-MAY-16:07 | 1094.44 | 15-MAY-16:05 | 139.41 | 06-MAY-13:30 | 279.99 | 15-MAY-16:05 | 0.00 | 01-MAY-00:10 |
| June | 0.488920E+09 | 0.125460E+09 | 365.01 | 0.475276E+09 | 13643723.97 | 0.00 | 0.29 | 28-JUN-16:05 | 0.00 | 01-JUN-00:10 | 1282.40 | 28-JUN-16:05 | 1282.40 | 28-JUN-16:05 | 121.60 | 12-JUN-17:04 | 333.78 | 28-JUN-16:05 | 0.00 | 01-JUN-00:10 |
| July | 0.128797E+10 | 0.327898E+09 | 636.13 | 0.119361E+10 | 94362532.12 | 0.00 | 0.41 | 24-JUL-15:10 | 0.00 | 01-JUL-02:30 | 1822.89 | 24-JUL-15:10 | 1759.13 | 24-JUL-15:10 | 192.15 | 31-JUL-11:00 | 493.73 | 24-JUL-15:10 | 0.00 | 01-JUL-00:10 |
| August | 0.172700E+10 | 0.439596E+09 | 670.80 | 0.157783E+10 | 0.149170E+09 | 0.00 | 0.47 | 10-AUG-15:10 | 0.00 | 01-AUG-12:35 | 2112.91 | 10-AUG-15:10 | 1997.42 | 10-AUG-16:02 | 274.33 | 30-AUG-13:20 | 566.29 | 10-AUG-15:10 | 0.00 | 01-AUG-00:10 |
| September | 0.101435E+10 | 0.255304E+09 | 532.29 | 0.935334E+09 | 79011215.15 | 0.00 | 0.41 | 14-SEP-14:10 | 0.00 | 01-SEP-07:35 | 1923.21 | 14-SEP-14:10 | 1722.58 | 14-SEP-15:10 | 249.10 | 14-SEP-13:00 | 466.76 | 14-SEP-14:10 | 0.00 | 01-SEP-00:10 |
| October | 0.233480E+09 | 60379287.51 | 171.58 | 0.231315E+09 | 2165200.57 | 0.00 | 0.32 | 04-OCT-15:10 | 0.00 | 01-OCT-00:10 | 1406.11 | 04-OCT-15:10 | 1406.11 | 04-OCT-15:10 | 43.21 | 08-OCT-13:40 | 356.67 | 04-OCT-15:10 | 0.00 | 01-OCT-00:10 |
| November | 5692363.14 | 1444800.59 | 5.08 | 4870754.99 | 821608.15 | 0.00 | 0.10 | 04-NOV-14:10 | 0.00 | 01-NOV-00:10 | 448.38 | 04-NOV-14:10 | 382.58 | 04-NOV-14:20 | 66.63 | 04-NOV-14:10 | 113.40 | 04-NOV-14:10 | 0.00 | 01-NOV-00:10 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.502921E+10 | 0.127981E+10 | 2563.22 | 0.467603E+10 | 0.353182E+09 | 0.00 | ||||||||||||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Maximum of Months | 0.172700E+10 | 0.439596E+09 | 670.80 | 0.157783E+10 | 0.149170E+09 | 0.00 | 0.47 | 0.00 | 2112.91 | 1997.42 | 274.33 | 566.29 | 0.00 |
Report: DXReportMonthly
For: SPLIT GS2 COOLING COIL
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
| April | 60561368.41 | 15775899.39 | 46.07 | 58933593.61 | 1627774.79 | 0.00 | 0.22 | 27-APR-15:10 | 0.00 | 01-APR-00:10 | 984.33 | 27-APR-15:10 | 975.11 | 27-APR-15:10 | 51.95 | 29-APR-13:50 | 262.26 | 27-APR-15:10 | 0.00 | 01-APR-00:10 |
| May | 0.247275E+09 | 63128897.97 | 161.56 | 0.233353E+09 | 13921852.31 | 0.00 | 0.26 | 15-MAY-16:05 | 0.00 | 01-MAY-00:10 | 1185.91 | 07-MAY-16:07 | 1147.46 | 15-MAY-15:10 | 144.96 | 06-MAY-13:30 | 294.38 | 07-MAY-16:07 | 0.00 | 01-MAY-00:10 |
| June | 0.567087E+09 | 0.145412E+09 | 409.36 | 0.550708E+09 | 16379401.25 | 0.00 | 0.30 | 28-JUN-15:10 | 0.00 | 01-JUN-00:10 | 1332.15 | 28-JUN-15:10 | 1332.15 | 28-JUN-15:10 | 89.12 | 12-JUN-17:15 | 345.62 | 28-JUN-15:10 | 0.00 | 01-JUN-00:10 |
| July | 0.142065E+10 | 0.361172E+09 | 660.64 | 0.131816E+10 | 0.102487E+09 | 0.00 | 0.42 | 24-JUL-15:10 | 0.00 | 01-JUL-03:40 | 1905.63 | 24-JUL-15:10 | 1841.39 | 24-JUL-15:10 | 197.04 | 31-JUL-10:50 | 514.94 | 24-JUL-15:10 | 0.00 | 01-JUL-00:10 |
| August | 0.190341E+10 | 0.483495E+09 | 691.81 | 0.174125E+10 | 0.162163E+09 | 0.00 | 0.48 | 10-AUG-15:10 | 0.00 | 01-AUG-12:35 | 2186.46 | 13-AUG-16:05 | 2066.66 | 10-AUG-15:10 | 282.06 | 30-AUG-13:20 | 584.07 | 10-AUG-15:10 | 0.00 | 01-AUG-00:10 |
| September | 0.112392E+10 | 0.282732E+09 | 556.97 | 0.103815E+10 | 85773995.56 | 0.00 | 0.42 | 14-SEP-14:10 | 0.00 | 01-SEP-07:35 | 1990.60 | 14-SEP-14:10 | 1785.30 | 14-SEP-15:10 | 253.38 | 14-SEP-13:00 | 482.41 | 14-SEP-14:10 | 0.00 | 01-SEP-00:10 |
| October | 0.257942E+09 | 66655896.26 | 185.28 | 0.255452E+09 | 2490358.49 | 0.00 | 0.33 | 04-OCT-15:10 | 0.00 | 01-OCT-00:10 | 1440.64 | 04-OCT-15:10 | 1440.64 | 04-OCT-15:10 | 44.73 | 08-OCT-13:40 | 365.09 | 04-OCT-15:10 | 0.00 | 01-OCT-00:10 |
| November | 7294199.41 | 1849875.38 | 7.17 | 6265940.82 | 1028258.58 | 0.00 | 0.11 | 04-NOV-14:10 | 0.00 | 01-NOV-00:10 | 519.69 | 04-NOV-14:10 | 444.39 | 04-NOV-14:10 | 75.30 | 04-NOV-14:10 | 131.21 | 04-NOV-14:10 | 0.00 | 01-NOV-00:10 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.558814E+10 | 0.142022E+10 | 2718.85 | 0.520227E+10 | 0.385872E+09 | 0.00 | ||||||||||||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Maximum of Months | 0.190341E+10 | 0.483495E+09 | 691.81 | 0.174125E+10 | 0.162163E+09 | 0.00 | 0.48 | 0.00 | 2186.46 | 2066.66 | 282.06 | 584.07 | 0.00 |
Report: DXReportMonthly
For: SPLIT MSW COOLING COIL
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| February | 14787658.46 | 3863034.97 | 6.88 | 14786806.85 | 851.61 | 0.00 | 0.13 | 27-FEB-15:30 | 0.00 | 01-FEB-00:10 | 1648.60 | 27-FEB-15:30 | 1648.60 | 27-FEB-15:30 | 0.58 | 28-FEB-14:30 | 428.11 | 27-FEB-15:30 | 0.00 | 01-FEB-00:10 |
| March | 0.121205E+09 | 31749126.20 | 42.53 | 0.121205E+09 | -0.0 | 0.00 | 0.18 | 18-MAR-16:10 | 0.00 | 01-MAR-00:10 | 2181.93 | 18-MAR-16:10 | 2181.93 | 18-MAR-16:10 | 0.00 | 02-MAR-15:30 | 566.62 | 18-MAR-16:10 | 0.00 | 01-MAR-00:10 |
| April | 0.805810E+09 | 0.207444E+09 | 176.00 | 0.792004E+09 | 13806864.07 | 0.00 | 0.42 | 27-APR-16:03 | 0.00 | 01-APR-00:10 | 5444.37 | 27-APR-16:03 | 5364.62 | 27-APR-16:03 | 197.12 | 29-APR-13:40 | 1402.17 | 27-APR-16:03 | 0.00 | 01-APR-00:10 |
| May | 0.192927E+10 | 0.491843E+09 | 393.66 | 0.186872E+10 | 60551246.66 | 0.00 | 0.40 | 15-MAY-16:05 | 0.00 | 01-MAY-00:10 | 5172.49 | 15-MAY-16:05 | 5172.49 | 15-MAY-16:05 | 475.88 | 07-MAY-16:03 | 1292.82 | 15-MAY-16:17 | 0.00 | 01-MAY-00:10 |
| June | 0.264948E+10 | 0.677082E+09 | 539.58 | 0.259629E+10 | 53191240.78 | 0.00 | 0.39 | 28-JUN-16:23 | 0.00 | 01-JUN-02:70 | 5103.90 | 28-JUN-16:30 | 5103.90 | 28-JUN-16:30 | 250.05 | 12-JUN-17:12 | 1310.42 | 28-JUN-16:30 | 0.00 | 01-JUN-00:10 |
| July | 0.463136E+10 | 0.117378E+10 | 688.08 | 0.435355E+10 | 0.277809E+09 | 0.00 | 0.48 | 31-JUL-16:15 | 0.00 | 01-JUL-09:00 | 6259.88 | 31-JUL-16:25 | 5877.05 | 31-JUL-16:30 | 641.70 | 11-JUL-16:03 | 1630.18 | 31-JUL-16:02 | 0.00 | 01-JUL-00:10 |
| August | 0.511713E+10 | 0.130167E+10 | 666.39 | 0.473815E+10 | 0.378978E+09 | 0.00 | 0.53 | 10-AUG-16:13 | 0.00 | 01-AUG-12:35 | 6872.06 | 10-AUG-16:13 | 6703.49 | 10-AUG-16:30 | 777.23 | 30-AUG-13:20 | 1858.35 | 10-AUG-16:13 | 0.00 | 01-AUG-00:10 |
| September | 0.318528E+10 | 0.800635E+09 | 544.96 | 0.298438E+10 | 0.200898E+09 | 0.00 | 0.44 | 23-SEP-16:07 | 0.00 | 01-SEP-07:35 | 5973.36 | 23-SEP-16:07 | 5602.31 | 11-SEP-16:04 | 636.85 | 14-SEP-13:20 | 1447.99 | 23-SEP-16:07 | 0.00 | 01-SEP-00:10 |
| October | 0.784401E+09 | 0.202250E+09 | 185.29 | 0.776948E+09 | 7453100.05 | 0.00 | 0.39 | 04-OCT-15:10 | 0.00 | 01-OCT-02:70 | 4902.75 | 04-OCT-15:10 | 4902.75 | 04-OCT-15:10 | 264.05 | 01-OCT-13:30 | 1231.13 | 04-OCT-15:10 | 0.00 | 01-OCT-00:10 |
| November | 64682619.03 | 16344648.06 | 15.42 | 57424876.97 | 7257742.06 | 0.00 | 0.23 | 04-NOV-15:20 | 0.00 | 01-NOV-00:10 | 2968.88 | 04-NOV-15:20 | 2688.02 | 04-NOV-15:10 | 331.08 | 04-NOV-14:00 | 742.76 | 04-NOV-15:20 | 0.00 | 01-NOV-00:10 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.193034E+11 | 0.490667E+10 | 3258.79 | 0.183035E+11 | 0.999947E+09 | 0.00 | ||||||||||||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | -0.0 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Maximum of Months | 0.511713E+10 | 0.130167E+10 | 688.08 | 0.473815E+10 | 0.378978E+09 | 0.00 | 0.53 | 0.00 | 6872.06 | 6703.49 | 777.23 | 1858.35 | 0.00 |
Report: DXReportMonthly
For: SPLIT MNW COOLING COIL
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
| April | 0.237921E+09 | 61588718.82 | 66.42 | 0.231105E+09 | 6815776.67 | 0.00 | 0.32 | 27-APR-17:20 | 0.00 | 01-APR-00:10 | 3572.76 | 27-APR-17:20 | 3452.86 | 27-APR-17:20 | 121.43 | 27-APR-17:30 | 921.55 | 27-APR-16:30 | 0.00 | 01-APR-00:10 |
| May | 0.108206E+10 | 0.276133E+09 | 287.60 | 0.103559E+10 | 46475368.28 | 0.00 | 0.36 | 15-MAY-16:25 | 0.00 | 01-MAY-00:10 | 4013.15 | 15-MAY-16:25 | 4013.15 | 15-MAY-16:25 | 395.30 | 07-MAY-16:15 | 1011.65 | 15-MAY-16:25 | 0.00 | 01-MAY-00:10 |
| June | 0.196011E+10 | 0.501461E+09 | 495.90 | 0.191498E+10 | 45128001.65 | 0.00 | 0.40 | 28-JUN-17:20 | 0.00 | 01-JUN-01:30 | 4526.86 | 28-JUN-18:00 | 4456.60 | 28-JUN-17:10 | 254.22 | 12-JUN-17:15 | 1153.62 | 28-JUN-17:10 | 0.00 | 01-JUN-00:10 |
| July | 0.356969E+10 | 0.906349E+09 | 665.84 | 0.333119E+10 | 0.238504E+09 | 0.00 | 0.46 | 31-JUL-17:20 | 0.00 | 01-JUL-09:00 | 5377.02 | 31-JUL-17:25 | 4968.32 | 24-JUL-18:00 | 631.49 | 11-JUL-16:03 | 1380.69 | 31-JUL-17:10 | 0.00 | 01-JUL-00:10 |
| August | 0.368768E+10 | 0.942558E+09 | 639.88 | 0.337666E+10 | 0.311020E+09 | 0.00 | 0.50 | 10-AUG-17:30 | 0.00 | 01-AUG-12:35 | 5688.56 | 10-AUG-17:30 | 5484.67 | 10-AUG-17:30 | 569.81 | 30-AUG-13:20 | 1541.91 | 10-AUG-17:20 | 0.00 | 01-AUG-00:10 |
| September | 0.140931E+10 | 0.357208E+09 | 399.59 | 0.129677E+10 | 0.112535E+09 | 0.00 | 0.34 | 14-SEP-16:25 | 0.00 | 01-SEP-07:35 | 3926.96 | 14-SEP-16:25 | 3665.35 | 12-SEP-16:25 | 444.71 | 14-SEP-13:50 | 979.68 | 14-SEP-16:25 | 0.00 | 01-SEP-00:10 |
| October | 38146561.78 | 9973896.93 | 27.74 | 37718606.61 | 427955.17 | 0.00 | 0.17 | 04-OCT-16:30 | 0.00 | 01-OCT-00:10 | 1777.30 | 04-OCT-16:30 | 1777.30 | 04-OCT-16:30 | 89.09 | 01-OCT-18:20 | 461.87 | 04-OCT-16:30 | 0.00 | 01-OCT-00:10 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.119849E+11 | 0.305527E+10 | 2582.97 | 0.112240E+11 | 0.760905E+09 | 0.00 | ||||||||||||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Maximum of Months | 0.368768E+10 | 0.942558E+09 | 665.84 | 0.337666E+10 | 0.311020E+09 | 0.00 | 0.50 | 0.00 | 5688.56 | 5484.67 | 631.49 | 1541.91 | 0.00 |
Report: DXReportMonthly
For: SPLIT MSE COOLING COIL
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| February | 8223309.59 | 2156958.50 | 4.33 | 8223309.59 | 0.00 | 0.00 | 0.09 | 27-FEB-15:10 | 0.00 | 01-FEB-00:10 | 990.15 | 27-FEB-15:10 | 990.15 | 27-FEB-15:10 | 0.00 | 27-FEB-15:30 | 258.76 | 27-FEB-15:10 | 0.00 | 01-FEB-00:10 |
| March | 91457688.62 | 23993092.97 | 32.81 | 91457688.62 | 0.00 | 0.00 | 0.16 | 02-MAR-14:00 | 0.00 | 01-MAR-00:10 | 1687.41 | 02-MAR-14:00 | 1687.41 | 02-MAR-14:00 | 0.00 | 18-MAR-15:10 | 439.16 | 02-MAR-14:00 | 0.00 | 01-MAR-00:10 |
| April | 0.810275E+09 | 0.208388E+09 | 194.57 | 0.796653E+09 | 13622522.95 | 0.00 | 0.43 | 27-APR-13:20 | 0.00 | 01-APR-00:10 | 4857.33 | 27-APR-13:30 | 4857.33 | 27-APR-13:30 | 190.88 | 29-APR-13:20 | 1241.82 | 27-APR-14:30 | 0.00 | 01-APR-00:10 |
| May | 0.180874E+10 | 0.460744E+09 | 396.45 | 0.175109E+10 | 57658879.12 | 0.00 | 0.39 | 15-MAY-13:40 | 0.00 | 01-MAY-00:10 | 4398.93 | 15-MAY-13:40 | 4398.93 | 15-MAY-13:40 | 458.82 | 06-MAY-13:30 | 1095.39 | 15-MAY-13:40 | 0.00 | 01-MAY-00:10 |
| June | 0.282075E+10 | 0.718896E+09 | 560.57 | 0.276041E+10 | 60337962.44 | 0.00 | 0.38 | 28-JUN-13:20 | 0.00 | 01-JUN-01:20 | 4282.09 | 28-JUN-13:00 | 4228.89 | 28-JUN-13:30 | 268.77 | 12-JUN-17:15 | 1074.69 | 28-JUN-15:10 | 0.00 | 01-JUN-00:10 |
| July | 0.434752E+10 | 0.109980E+10 | 672.28 | 0.408409E+10 | 0.263435E+09 | 0.00 | 0.49 | 24-JUL-13:30 | 0.00 | 01-JUL-09:00 | 5627.81 | 24-JUL-13:30 | 5396.77 | 24-JUL-13:30 | 579.77 | 31-JUL-10:20 | 1469.24 | 24-JUL-13:30 | 0.00 | 01-JUL-00:10 |
| August | 0.513460E+10 | 0.129872E+10 | 674.79 | 0.474190E+10 | 0.392695E+09 | 0.00 | 0.53 | 29-AUG-14:30 | 0.00 | 01-AUG-12:35 | 6132.82 | 29-AUG-14:30 | 5743.76 | 10-AUG-14:10 | 757.78 | 30-AUG-13:10 | 1621.10 | 29-AUG-14:30 | 0.00 | 01-AUG-00:10 |
| September | 0.306073E+10 | 0.766529E+09 | 523.86 | 0.286242E+10 | 0.198309E+09 | 0.00 | 0.47 | 23-SEP-13:30 | 0.00 | 01-SEP-07:35 | 5563.19 | 23-SEP-13:30 | 4992.53 | 23-SEP-13:40 | 620.60 | 14-SEP-13:10 | 1338.67 | 23-SEP-13:30 | 0.00 | 01-SEP-00:10 |
| October | 0.789319E+09 | 0.203155E+09 | 188.27 | 0.783062E+09 | 6257187.98 | 0.00 | 0.38 | 04-OCT-13:40 | 0.00 | 01-OCT-00:10 | 4246.43 | 04-OCT-13:40 | 4246.43 | 04-OCT-13:40 | 180.32 | 01-OCT-13:30 | 1065.71 | 04-OCT-13:40 | 0.00 | 01-OCT-00:10 |
| November | 57377965.58 | 14499064.91 | 15.25 | 50726357.97 | 6651607.61 | 0.00 | 0.22 | 04-NOV-14:00 | 0.00 | 01-NOV-00:10 | 2509.33 | 04-NOV-14:00 | 2220.97 | 04-NOV-14:00 | 296.65 | 04-NOV-13:30 | 626.57 | 04-NOV-14:00 | 0.00 | 01-NOV-00:10 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.189290E+11 | 0.479688E+10 | 3263.19 | 0.179300E+11 | 0.998967E+09 | 0.00 | ||||||||||||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Maximum of Months | 0.513460E+10 | 0.129872E+10 | 674.79 | 0.474190E+10 | 0.392695E+09 | 0.00 | 0.53 | 0.00 | 6132.82 | 5743.76 | 757.78 | 1621.10 | 0.00 |
Report: DXReportMonthly
For: SPLIT MNE COOLING COIL
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
| April | 0.211473E+09 | 54720485.37 | 68.70 | 0.204926E+09 | 6547220.56 | 0.00 | 0.28 | 27-APR-16:10 | 0.00 | 01-APR-00:10 | 2730.22 | 27-APR-16:10 | 2648.86 | 27-APR-16:10 | 99.52 | 27-APR-17:30 | 716.91 | 27-APR-16:10 | 0.00 | 01-APR-00:10 |
| May | 0.946196E+09 | 0.241574E+09 | 291.81 | 0.902805E+09 | 43390335.27 | 0.00 | 0.31 | 06-MAY-13:30 | 0.00 | 01-MAY-00:10 | 3068.76 | 06-MAY-13:30 | 2833.09 | 15-MAY-16:20 | 356.54 | 06-MAY-13:30 | 755.93 | 06-MAY-13:30 | 0.00 | 01-MAY-00:10 |
| June | 0.211998E+10 | 0.541583E+09 | 528.38 | 0.206806E+10 | 51924648.45 | 0.00 | 0.35 | 28-JUN-17:50 | 0.00 | 01-JUN-00:30 | 3457.41 | 28-JUN-18:00 | 3378.72 | 28-JUN-17:30 | 273.97 | 12-JUN-17:15 | 881.57 | 28-JUN-17:30 | 0.00 | 01-JUN-00:10 |
| July | 0.328682E+10 | 0.834278E+09 | 648.91 | 0.306388E+10 | 0.222934E+09 | 0.00 | 0.44 | 24-JUL-18:00 | 0.00 | 01-JUL-09:00 | 4369.22 | 24-JUL-18:00 | 4149.31 | 24-JUL-18:00 | 548.03 | 31-JUL-10:20 | 1148.82 | 24-JUL-18:00 | 0.00 | 01-JUL-00:10 |
| August | 0.370600E+10 | 0.942584E+09 | 651.19 | 0.337900E+10 | 0.326997E+09 | 0.00 | 0.43 | 10-AUG-17:10 | 0.00 | 01-AUG-12:35 | 4172.66 | 10-AUG-17:10 | 4013.99 | 10-AUG-17:03 | 556.72 | 25-AUG-11:20 | 1150.28 | 10-AUG-17:00 | 0.00 | 01-AUG-00:10 |
| September | 0.131345E+10 | 0.332607E+09 | 388.09 | 0.120028E+10 | 0.113176E+09 | 0.00 | 0.30 | 14-SEP-16:25 | 0.00 | 01-SEP-04:50 | 2941.58 | 14-SEP-16:25 | 2681.88 | 14-SEP-16:40 | 423.10 | 14-SEP-13:20 | 738.22 | 14-SEP-16:40 | 0.00 | 01-SEP-00:10 |
| October | 28223446.15 | 7422330.64 | 28.71 | 28166911.21 | 56534.94 | 0.00 | 0.09 | 04-OCT-16:30 | 0.00 | 01-OCT-00:10 | 806.84 | 04-OCT-16:30 | 806.84 | 04-OCT-16:30 | 9.00 | 09-OCT-16:10 | 212.14 | 04-OCT-16:30 | 0.00 | 01-OCT-00:10 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.116121E+11 | 0.295477E+10 | 2605.79 | 0.108471E+11 | 0.765026E+09 | 0.00 | ||||||||||||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Maximum of Months | 0.370600E+10 | 0.942584E+09 | 651.19 | 0.337900E+10 | 0.326997E+09 | 0.00 | 0.44 | 0.00 | 4369.22 | 4149.31 | 556.72 | 1150.28 | 0.00 |
Report: DXReportMonthly
For: SPLIT MN1 COOLING COIL
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
| April | 0.154697E+09 | 40068236.08 | 64.86 | 0.147992E+09 | 6704402.56 | 0.00 | 0.23 | 27-APR-18:00 | 0.00 | 01-APR-00:10 | 2019.24 | 27-APR-18:00 | 1940.38 | 27-APR-18:00 | 83.35 | 30-APR-17:35 | 526.44 | 27-APR-18:00 | 0.00 | 01-APR-00:10 |
| May | 0.837510E+09 | 0.214653E+09 | 347.01 | 0.796406E+09 | 41104321.45 | 0.00 | 0.28 | 05-MAY-16:10 | 0.00 | 01-MAY-00:10 | 2452.68 | 05-MAY-16:10 | 2253.63 | 05-MAY-16:10 | 305.64 | 05-MAY-18:00 | 617.39 | 05-MAY-16:10 | 0.00 | 01-MAY-00:10 |
| June | 0.167977E+10 | 0.431157E+09 | 584.35 | 0.163153E+10 | 48230872.65 | 0.00 | 0.32 | 28-JUN-18:00 | 0.00 | 01-JUN-01:50 | 2847.17 | 28-JUN-18:00 | 2764.88 | 28-JUN-18:00 | 267.95 | 12-JUN-17:12 | 727.17 | 28-JUN-18:00 | 0.00 | 01-JUN-00:10 |
| July | 0.273551E+10 | 0.697408E+09 | 710.08 | 0.253064E+10 | 0.204864E+09 | 0.00 | 0.40 | 24-JUL-18:00 | 0.00 | 01-JUL-09:00 | 3490.49 | 24-JUL-18:00 | 3293.19 | 24-JUL-18:00 | 443.29 | 15-JUL-18:50 | 924.38 | 24-JUL-18:00 | 0.00 | 01-JUL-00:10 |
| August | 0.302005E+10 | 0.771977E+09 | 701.52 | 0.273269E+10 | 0.287353E+09 | 0.00 | 0.39 | 10-AUG-18:40 | 0.00 | 01-AUG-12:35 | 3462.56 | 10-AUG-18:40 | 3221.06 | 10-AUG-18:40 | 470.53 | 30-AUG-13:20 | 934.40 | 10-AUG-18:40 | 0.00 | 01-AUG-00:10 |
| September | 0.120174E+10 | 0.305700E+09 | 519.76 | 0.109098E+10 | 0.110763E+09 | 0.00 | 0.27 | 14-SEP-17:00 | 0.00 | 01-SEP-07:35 | 2432.06 | 14-SEP-16:50 | 2203.53 | 14-SEP-17:00 | 344.38 | 14-SEP-13:30 | 614.46 | 14-SEP-17:00 | 0.00 | 01-SEP-00:10 |
| October | 45492790.30 | 11902608.66 | 50.48 | 44826753.33 | 666036.96 | 0.00 | 0.10 | 01-OCT-18:20 | 0.00 | 01-OCT-00:10 | 855.50 | 01-OCT-18:20 | 785.70 | 04-OCT-17:00 | 92.13 | 01-OCT-18:20 | 217.92 | 01-OCT-18:20 | 0.00 | 01-OCT-00:10 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.967476E+10 | 0.247287E+10 | 2978.07 | 0.897507E+10 | 0.699686E+09 | 0.00 | ||||||||||||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Maximum of Months | 0.302005E+10 | 0.771977E+09 | 710.08 | 0.273269E+10 | 0.287353E+09 | 0.00 | 0.40 | 0.00 | 3490.49 | 3293.19 | 470.53 | 934.40 | 0.00 |
Report: DXReportMonthly
For: SPLIT MN2 COOLING COIL
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
| April | 0.156018E+09 | 40409195.94 | 65.36 | 0.149294E+09 | 6723983.22 | 0.00 | 0.23 | 27-APR-18:00 | 0.00 | 01-APR-00:10 | 2017.58 | 27-APR-18:00 | 1938.86 | 27-APR-18:00 | 83.16 | 30-APR-17:35 | 525.97 | 27-APR-18:00 | 0.00 | 01-APR-00:10 |
| May | 0.835180E+09 | 0.214060E+09 | 345.91 | 0.794238E+09 | 40941939.95 | 0.00 | 0.28 | 05-MAY-16:10 | 0.00 | 01-MAY-00:10 | 2447.21 | 05-MAY-16:10 | 2248.44 | 05-MAY-16:10 | 305.11 | 05-MAY-18:00 | 615.98 | 05-MAY-16:10 | 0.00 | 01-MAY-00:10 |
| June | 0.168859E+10 | 0.433395E+09 | 586.49 | 0.164016E+10 | 48432204.44 | 0.00 | 0.32 | 28-JUN-18:00 | 0.00 | 01-JUN-01:50 | 2830.11 | 28-JUN-18:00 | 2748.25 | 28-JUN-18:00 | 269.14 | 12-JUN-17:12 | 722.91 | 28-JUN-18:00 | 0.00 | 01-JUN-00:10 |
| July | 0.272390E+10 | 0.694464E+09 | 709.94 | 0.252000E+10 | 0.203899E+09 | 0.00 | 0.40 | 24-JUL-18:00 | 0.00 | 01-JUL-09:00 | 3480.77 | 24-JUL-18:00 | 3284.01 | 24-JUL-18:00 | 438.01 | 15-JUL-18:50 | 921.79 | 24-JUL-18:00 | 0.00 | 01-JUL-00:10 |
| August | 0.302174E+10 | 0.772323E+09 | 701.80 | 0.273407E+10 | 0.287666E+09 | 0.00 | 0.39 | 10-AUG-18:40 | 0.00 | 01-AUG-12:35 | 3437.78 | 10-AUG-18:40 | 3197.46 | 10-AUG-18:40 | 471.18 | 30-AUG-13:20 | 928.56 | 10-AUG-17:07 | 0.00 | 01-AUG-00:10 |
| September | 0.119523E+10 | 0.304016E+09 | 517.19 | 0.108488E+10 | 0.110352E+09 | 0.00 | 0.27 | 14-SEP-17:00 | 0.00 | 01-SEP-07:35 | 2419.98 | 14-SEP-16:50 | 2192.57 | 14-SEP-17:00 | 346.25 | 14-SEP-13:20 | 611.42 | 14-SEP-17:00 | 0.00 | 01-SEP-00:10 |
| October | 45620543.57 | 11936803.60 | 50.31 | 45011424.62 | 609118.95 | 0.00 | 0.09 | 04-OCT-17:00 | 0.00 | 01-OCT-00:10 | 755.54 | 04-OCT-17:00 | 755.54 | 04-OCT-17:00 | 75.05 | 01-OCT-18:20 | 198.51 | 04-OCT-17:00 | 0.00 | 01-OCT-00:10 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.966628E+10 | 0.247060E+10 | 2977.00 | 0.896766E+10 | 0.698624E+09 | 0.00 | ||||||||||||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Maximum of Months | 0.302174E+10 | 0.772323E+09 | 709.94 | 0.273407E+10 | 0.287666E+09 | 0.00 | 0.40 | 0.00 | 3480.77 | 3284.01 | 471.18 | 928.56 | 0.00 |
Report: DXReportMonthly
For: SPLIT MS1 COOLING COIL
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| February | 27081806.38 | 7081547.61 | 16.85 | 27057835.44 | 23970.94 | 0.00 | 0.14 | 27-FEB-15:10 | 0.00 | 01-FEB-00:10 | 1461.63 | 27-FEB-15:10 | 1461.63 | 27-FEB-15:10 | 3.91 | 28-FEB-13:50 | 378.94 | 27-FEB-15:10 | 0.00 | 01-FEB-00:10 |
| March | 0.175811E+09 | 46005490.34 | 71.67 | 0.175811E+09 | -0.0 | 0.00 | 0.20 | 02-MAR-14:00 | 0.00 | 01-MAR-00:10 | 2035.18 | 02-MAR-14:00 | 2035.18 | 02-MAR-14:00 | 0.00 | 18-MAR-15:40 | 526.06 | 02-MAR-14:00 | 0.00 | 01-MAR-00:10 |
| April | 0.801853E+09 | 0.206883E+09 | 235.89 | 0.786387E+09 | 15466732.61 | 0.00 | 0.39 | 27-APR-14:30 | 0.00 | 01-APR-00:10 | 4093.24 | 27-APR-14:30 | 4093.24 | 27-APR-14:30 | 176.85 | 29-APR-13:20 | 1055.69 | 27-APR-14:30 | 0.00 | 01-APR-00:10 |
| May | 0.174559E+10 | 0.446683E+09 | 469.36 | 0.168882E+10 | 56768269.66 | 0.00 | 0.34 | 15-MAY-14:10 | 0.00 | 01-MAY-00:10 | 3622.67 | 04-MAY-14:10 | 3579.65 | 15-MAY-14:10 | 401.50 | 06-MAY-13:30 | 902.09 | 04-MAY-14:10 | 0.00 | 01-MAY-00:10 |
| June | 0.239621E+10 | 0.613850E+09 | 630.62 | 0.233836E+10 | 57849874.31 | 0.00 | 0.32 | 28-JUN-15:10 | 0.00 | 01-JUN-02:50 | 3397.34 | 28-JUN-15:10 | 3397.34 | 28-JUN-15:10 | 262.97 | 12-JUN-17:12 | 877.88 | 28-JUN-15:10 | 0.00 | 01-JUN-00:10 |
| July | 0.381255E+10 | 0.969048E+09 | 730.87 | 0.356265E+10 | 0.249901E+09 | 0.00 | 0.42 | 24-JUL-13:40 | 0.00 | 01-JUL-09:00 | 4431.76 | 31-JUL-14:10 | 4230.87 | 24-JUL-14:10 | 474.76 | 15-JUL-14:10 | 1174.91 | 24-JUL-15:10 | 0.00 | 01-JUL-00:10 |
| August | 0.447339E+10 | 0.113752E+10 | 727.92 | 0.411037E+10 | 0.363020E+09 | 0.00 | 0.49 | 29-AUG-14:30 | 0.00 | 01-AUG-12:35 | 5211.12 | 29-AUG-14:30 | 4796.07 | 29-AUG-15:10 | 688.86 | 30-AUG-13:20 | 1388.47 | 29-AUG-15:10 | 0.00 | 01-AUG-00:10 |
| September | 0.307467E+10 | 0.773821E+09 | 642.25 | 0.286493E+10 | 0.209743E+09 | 0.00 | 0.46 | 23-SEP-13:40 | 0.00 | 01-SEP-07:35 | 5046.91 | 23-SEP-13:40 | 4499.54 | 23-SEP-13:40 | 580.12 | 14-SEP-13:00 | 1216.00 | 23-SEP-13:40 | 0.00 | 01-SEP-00:10 |
| October | 0.101206E+10 | 0.260479E+09 | 273.98 | 0.100134E+10 | 10713686.79 | 0.00 | 0.39 | 04-OCT-14:10 | 0.00 | 01-OCT-05:05 | 4021.85 | 04-OCT-14:10 | 4021.85 | 04-OCT-14:10 | 242.76 | 01-OCT-13:30 | 1008.90 | 04-OCT-14:10 | 0.00 | 01-OCT-00:10 |
| November | 93758554.26 | 23654210.09 | 25.67 | 83492181.60 | 10266372.66 | 0.00 | 0.27 | 04-NOV-14:00 | 0.00 | 01-NOV-00:10 | 2901.49 | 04-NOV-14:00 | 2590.55 | 04-NOV-14:00 | 324.12 | 04-NOV-13:30 | 719.77 | 04-NOV-14:00 | 0.00 | 01-NOV-00:10 |
| December | 1540837.55 | 409793.37 | 2.83 | 1540837.55 | 0.00 | 0.00 | 0.03 | 05-DEC-14:30 | 0.00 | 01-DEC-00:10 | 245.03 | 05-DEC-14:30 | 245.03 | 05-DEC-14:30 | 0.00 | 05-DEC-14:10 | 65.12 | 05-DEC-14:30 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.176145E+11 | 0.448543E+10 | 3827.92 | 0.166408E+11 | 0.973753E+09 | 0.00 | ||||||||||||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | -0.0 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Maximum of Months | 0.447339E+10 | 0.113752E+10 | 730.87 | 0.411037E+10 | 0.363020E+09 | 0.00 | 0.49 | 0.00 | 5211.12 | 4796.07 | 688.86 | 1388.47 | 0.00 |
Report: DXReportMonthly
For: SPLIT MS2 COOLING COIL
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| February | 26717375.47 | 6986427.69 | 16.31 | 26694171.85 | 23203.62 | 0.00 | 0.14 | 27-FEB-15:00 | 0.00 | 01-FEB-00:10 | 1455.14 | 27-FEB-15:00 | 1455.14 | 27-FEB-15:00 | 3.83 | 28-FEB-13:50 | 377.27 | 27-FEB-15:00 | 0.00 | 01-FEB-00:10 |
| March | 0.175142E+09 | 45829489.64 | 72.78 | 0.175142E+09 | -0.0 | 0.00 | 0.20 | 02-MAR-14:00 | 0.00 | 01-MAR-00:10 | 2055.40 | 02-MAR-14:00 | 2055.40 | 02-MAR-14:00 | 0.00 | 02-MAR-12:30 | 531.08 | 02-MAR-14:00 | 0.00 | 01-MAR-00:10 |
| April | 0.813822E+09 | 0.209986E+09 | 240.23 | 0.798377E+09 | 15444747.88 | 0.00 | 0.39 | 27-APR-14:20 | 0.00 | 01-APR-00:10 | 4103.76 | 27-APR-14:20 | 4103.76 | 27-APR-14:20 | 177.09 | 29-APR-13:20 | 1057.69 | 27-APR-14:30 | 0.00 | 01-APR-00:10 |
| May | 0.174191E+10 | 0.445701E+09 | 467.87 | 0.168530E+10 | 56607263.14 | 0.00 | 0.34 | 15-MAY-14:10 | 0.00 | 01-MAY-00:10 | 3629.84 | 04-MAY-14:10 | 3589.81 | 15-MAY-14:10 | 401.96 | 06-MAY-13:30 | 903.66 | 04-MAY-14:10 | 0.00 | 01-MAY-00:10 |
| June | 0.240442E+10 | 0.615878E+09 | 630.40 | 0.234638E+10 | 58041211.75 | 0.00 | 0.33 | 28-JUN-15:10 | 0.00 | 01-JUN-02:50 | 3398.60 | 28-JUN-14:10 | 3398.59 | 28-JUN-15:10 | 264.08 | 12-JUN-17:12 | 878.06 | 28-JUN-15:10 | 0.00 | 01-JUN-00:10 |
| July | 0.380125E+10 | 0.966118E+09 | 729.56 | 0.355223E+10 | 0.249015E+09 | 0.00 | 0.42 | 24-JUL-13:40 | 0.00 | 01-JUL-09:00 | 4445.65 | 24-JUL-13:30 | 4245.20 | 24-JUL-13:40 | 473.26 | 15-JUL-14:10 | 1177.52 | 24-JUL-14:10 | 0.00 | 01-JUL-00:10 |
| August | 0.447452E+10 | 0.113762E+10 | 726.66 | 0.411133E+10 | 0.363188E+09 | 0.00 | 0.49 | 29-AUG-14:30 | 0.00 | 01-AUG-12:35 | 5223.33 | 29-AUG-14:30 | 4801.75 | 29-AUG-14:30 | 689.14 | 30-AUG-13:20 | 1389.55 | 29-AUG-14:30 | 0.00 | 01-AUG-00:10 |
| September | 0.306758E+10 | 0.771917E+09 | 641.00 | 0.285823E+10 | 0.209340E+09 | 0.00 | 0.46 | 23-SEP-13:40 | 0.00 | 01-SEP-07:35 | 5053.80 | 23-SEP-13:40 | 4506.63 | 23-SEP-13:40 | 580.71 | 14-SEP-13:00 | 1217.33 | 23-SEP-13:40 | 0.00 | 01-SEP-00:10 |
| October | 0.101369E+10 | 0.260875E+09 | 273.74 | 0.100306E+10 | 10628366.17 | 0.00 | 0.39 | 04-OCT-14:10 | 0.00 | 01-OCT-05:05 | 4025.30 | 04-OCT-14:10 | 4025.30 | 04-OCT-14:10 | 239.37 | 01-OCT-13:30 | 1009.54 | 04-OCT-14:10 | 0.00 | 01-OCT-00:10 |
| November | 94095253.01 | 23735546.94 | 25.67 | 83799891.93 | 10295361.08 | 0.00 | 0.27 | 04-NOV-14:00 | 0.00 | 01-NOV-00:10 | 2914.35 | 04-NOV-14:00 | 2603.22 | 04-NOV-14:00 | 324.59 | 04-NOV-13:30 | 722.79 | 04-NOV-14:00 | 0.00 | 01-NOV-00:10 |
| December | 1627329.03 | 432736.66 | 2.83 | 1627329.03 | 0.00 | 0.00 | 0.03 | 05-DEC-14:30 | 0.00 | 01-DEC-00:10 | 250.58 | 05-DEC-14:30 | 250.58 | 05-DEC-14:30 | 0.00 | 05-DEC-13:10 | 66.59 | 05-DEC-14:30 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.176148E+11 | 0.448508E+10 | 3827.04 | 0.166422E+11 | 0.972584E+09 | 0.00 | ||||||||||||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | -0.0 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Maximum of Months | 0.447452E+10 | 0.113762E+10 | 729.56 | 0.411133E+10 | 0.363188E+09 | 0.00 | 0.49 | 0.00 | 5223.33 | 4801.75 | 689.14 | 1389.55 | 0.00 |
Report: DXReportMonthly
For: SPLIT TSW COOLING COIL
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| February | 28244668.29 | 7321639.99 | 15.83 | 28244668.29 | -0.0 | 0.00 | 0.27 | 27-FEB-15:30 | 0.00 | 01-FEB-00:10 | 1823.37 | 27-FEB-15:30 | 1823.37 | 27-FEB-15:30 | 0.00 | 27-FEB-15:10 | 463.68 | 27-FEB-15:30 | 0.00 | 01-FEB-00:10 |
| March | 0.144054E+09 | 37345673.90 | 51.35 | 0.144054E+09 | 0.00 | 0.00 | 0.29 | 14-MAR-16:05 | 0.00 | 01-MAR-00:10 | 1997.32 | 14-MAR-16:05 | 1997.32 | 14-MAR-16:05 | 0.00 | 14-MAR-16:08 | 506.21 | 14-MAR-16:05 | 0.00 | 01-MAR-00:10 |
| April | 0.519277E+09 | 0.133000E+09 | 143.50 | 0.515093E+09 | 4183293.46 | 0.00 | 0.51 | 27-APR-15:10 | 0.00 | 01-APR-00:10 | 3596.00 | 27-APR-15:10 | 3563.80 | 27-APR-15:10 | 117.41 | 29-APR-13:40 | 915.88 | 27-APR-15:10 | 0.00 | 01-APR-00:10 |
| May | 0.937059E+09 | 0.236546E+09 | 236.80 | 0.908852E+09 | 28207257.13 | 0.00 | 0.48 | 15-MAY-16:10 | 0.00 | 01-MAY-00:10 | 3354.90 | 15-MAY-16:05 | 3354.90 | 15-MAY-16:05 | 289.76 | 07-MAY-15:40 | 827.74 | 15-MAY-16:08 | 0.00 | 01-MAY-00:10 |
| June | 0.121896E+10 | 0.308756E+09 | 305.97 | 0.120191E+10 | 17046211.12 | 0.00 | 0.48 | 28-JUN-16:16 | 0.00 | 01-JUN-00:10 | 3394.44 | 28-JUN-16:14 | 3394.44 | 28-JUN-16:14 | 139.39 | 11-JUN-12:00 | 858.75 | 28-JUN-16:27 | 0.00 | 01-JUN-00:10 |
| July | 0.228990E+10 | 0.575222E+09 | 419.14 | 0.216841E+10 | 0.121490E+09 | 0.00 | 0.58 | 31-JUL-16:02 | 0.00 | 01-JUL-00:10 | 4151.61 | 31-JUL-16:02 | 3931.10 | 31-JUL-16:04 | 404.17 | 11-JUL-15:40 | 1065.90 | 31-JUL-16:02 | 0.00 | 01-JUL-00:10 |
| August | 0.246265E+10 | 0.622828E+09 | 439.50 | 0.230481E+10 | 0.157847E+09 | 0.00 | 0.65 | 10-AUG-16:03 | 0.00 | 01-AUG-02:00 | 4555.68 | 10-AUG-16:02 | 4462.41 | 10-AUG-16:03 | 483.70 | 30-AUG-13:20 | 1208.06 | 10-AUG-16:13 | 0.00 | 01-AUG-00:10 |
| September | 0.136577E+10 | 0.339465E+09 | 272.75 | 0.129089E+10 | 74887866.15 | 0.00 | 0.53 | 14-SEP-15:10 | 0.00 | 01-SEP-00:10 | 3838.04 | 14-SEP-15:10 | 3602.93 | 14-SEP-15:20 | 382.85 | 14-SEP-13:20 | 921.61 | 14-SEP-15:10 | 0.00 | 01-SEP-00:10 |
| October | 0.274709E+09 | 70672827.88 | 104.83 | 0.273300E+09 | 1408998.12 | 0.00 | 0.42 | 04-OCT-15:10 | 0.00 | 01-OCT-00:10 | 2900.49 | 04-OCT-15:10 | 2900.49 | 04-OCT-15:10 | 71.09 | 01-OCT-15:30 | 724.08 | 04-OCT-15:10 | 0.00 | 01-OCT-00:10 |
| November | 53099725.60 | 13267497.75 | 16.83 | 48481529.34 | 4618196.26 | 0.00 | 0.36 | 04-NOV-14:30 | 0.00 | 01-NOV-00:10 | 2565.80 | 04-NOV-14:30 | 2367.13 | 04-NOV-14:30 | 230.59 | 04-NOV-13:30 | 630.38 | 04-NOV-14:30 | 0.00 | 01-NOV-00:10 |
| December | 3216402.04 | 855381.08 | 5.33 | 3216402.04 | -0.0 | 0.00 | 0.04 | 05-DEC-14:30 | 0.00 | 01-DEC-00:10 | 284.11 | 05-DEC-14:30 | 284.11 | 05-DEC-14:30 | 0.00 | 05-DEC-14:20 | 75.30 | 05-DEC-14:30 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.929695E+10 | 0.234528E+10 | 2011.85 | 0.888726E+10 | 0.409689E+09 | 0.00 | ||||||||||||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | -0.0 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Maximum of Months | 0.246265E+10 | 0.622828E+09 | 439.50 | 0.230481E+10 | 0.157847E+09 | 0.00 | 0.65 | 0.00 | 4555.68 | 4462.41 | 483.70 | 1208.06 | 0.00 |
Report: DXReportMonthly
For: SPLIT TNW COOLING COIL
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
| March | 1160867.69 | 308510.32 | 1.83 | 1160867.69 | -0.0 | 0.00 | 0.05 | 18-MAR-16:30 | 0.00 | 01-MAR-00:10 | 264.68 | 18-MAR-16:30 | 264.68 | 18-MAR-16:30 | 0.00 | 18-MAR-16:10 | 70.22 | 18-MAR-16:30 | 0.00 | 01-MAR-00:10 |
| April | 0.181819E+09 | 47005356.10 | 65.42 | 0.179420E+09 | 2398273.24 | 0.00 | 0.41 | 27-APR-16:27 | 0.00 | 01-APR-00:10 | 2576.10 | 27-APR-16:30 | 2511.30 | 27-APR-16:27 | 72.66 | 27-APR-17:20 | 660.14 | 27-APR-16:30 | 0.00 | 01-APR-00:10 |
| May | 0.535811E+09 | 0.135817E+09 | 173.83 | 0.514245E+09 | 21566034.02 | 0.00 | 0.42 | 15-MAY-16:30 | 0.00 | 01-MAY-00:10 | 2648.84 | 15-MAY-16:25 | 2648.84 | 15-MAY-16:25 | 238.74 | 07-MAY-16:15 | 661.09 | 15-MAY-16:30 | 0.00 | 01-MAY-00:10 |
| June | 0.878424E+09 | 0.223142E+09 | 274.18 | 0.864034E+09 | 14390715.72 | 0.00 | 0.47 | 28-JUN-17:10 | 0.00 | 01-JUN-00:10 | 2972.57 | 28-JUN-17:10 | 2960.14 | 28-JUN-16:50 | 128.74 | 22-JUN-18:50 | 754.47 | 28-JUN-17:10 | 0.00 | 01-JUN-00:10 |
| July | 0.173657E+10 | 0.438058E+09 | 394.75 | 0.163161E+10 | 0.104953E+09 | 0.00 | 0.55 | 31-JUL-17:10 | 0.00 | 01-JUL-00:10 | 3548.14 | 31-JUL-17:10 | 3308.35 | 31-JUL-17:10 | 394.47 | 11-JUL-16:03 | 905.92 | 31-JUL-16:50 | 0.00 | 01-JUL-00:10 |
| August | 0.174121E+10 | 0.444345E+09 | 401.02 | 0.161194E+10 | 0.129270E+09 | 0.00 | 0.59 | 10-AUG-17:10 | 0.00 | 01-AUG-01:40 | 3761.08 | 10-AUG-17:20 | 3660.03 | 10-AUG-17:07 | 348.50 | 30-AUG-13:20 | 1008.63 | 10-AUG-17:10 | 0.00 | 01-AUG-00:10 |
| September | 0.550248E+09 | 0.138608E+09 | 187.12 | 0.509730E+09 | 40517879.03 | 0.00 | 0.39 | 14-SEP-16:25 | 0.00 | 01-SEP-00:10 | 2476.70 | 14-SEP-16:25 | 2304.64 | 12-SEP-16:25 | 271.93 | 14-SEP-13:50 | 614.40 | 14-SEP-16:25 | 0.00 | 01-SEP-00:10 |
| October | 10622191.34 | 2776173.39 | 4.98 | 10622191.34 | 0.00 | 0.00 | 0.17 | 04-OCT-16:30 | 0.00 | 01-OCT-00:10 | 996.02 | 04-OCT-16:30 | 996.02 | 04-OCT-16:30 | 0.00 | 04-OCT-16:20 | 258.79 | 04-OCT-16:30 | 0.00 | 01-OCT-00:10 |
| November | 3041360.10 | 775492.84 | 3.17 | 2603037.32 | 438322.78 | 0.00 | 0.07 | 04-NOV-16:03 | 0.00 | 01-NOV-00:10 | 409.32 | 04-NOV-16:03 | 350.28 | 04-NOV-16:03 | 59.03 | 04-NOV-16:03 | 104.13 | 04-NOV-16:03 | 0.00 | 01-NOV-00:10 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.563890E+10 | 0.143084E+10 | 1506.30 | 0.532537E+10 | 0.313534E+09 | 0.00 | ||||||||||||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | -0.0 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Maximum of Months | 0.174121E+10 | 0.444345E+09 | 401.02 | 0.163161E+10 | 0.129270E+09 | 0.00 | 0.59 | 0.00 | 3761.08 | 3660.03 | 394.47 | 1008.63 | 0.00 |
Report: DXReportMonthly
For: SPLIT TSE COOLING COIL
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| February | 18961766.77 | 4903908.35 | 9.50 | 18961766.77 | -0.0 | 0.00 | 0.24 | 27-FEB-15:00 | 0.00 | 01-FEB-00:10 | 1346.02 | 27-FEB-15:00 | 1346.02 | 27-FEB-15:00 | 0.00 | 27-FEB-12:50 | 343.84 | 27-FEB-15:00 | 0.00 | 01-FEB-00:10 |
| March | 0.125851E+09 | 32631477.04 | 49.72 | 0.125851E+09 | 0.00 | 0.00 | 0.32 | 14-MAR-13:40 | 0.00 | 01-MAR-00:10 | 1797.42 | 14-MAR-13:40 | 1797.42 | 14-MAR-13:40 | 0.00 | 14-MAR-13:10 | 453.94 | 14-MAR-13:40 | 0.00 | 01-MAR-00:10 |
| April | 0.491740E+09 | 0.125561E+09 | 157.22 | 0.487567E+09 | 4172733.06 | 0.00 | 0.55 | 27-APR-14:10 | 0.00 | 01-APR-00:10 | 3258.07 | 27-APR-14:10 | 3258.07 | 27-APR-14:10 | 113.86 | 29-APR-13:20 | 816.00 | 27-APR-14:30 | 0.00 | 01-APR-00:10 |
| May | 0.852374E+09 | 0.214539E+09 | 244.23 | 0.825930E+09 | 26444391.87 | 0.00 | 0.50 | 15-MAY-13:50 | 0.00 | 01-MAY-00:10 | 2924.79 | 15-MAY-13:40 | 2924.79 | 15-MAY-13:40 | 284.50 | 06-MAY-13:30 | 715.58 | 15-MAY-13:40 | 0.00 | 01-MAY-00:10 |
| June | 0.128085E+10 | 0.322968E+09 | 339.26 | 0.126037E+10 | 20473110.88 | 0.00 | 0.49 | 28-JUN-13:30 | 0.00 | 01-JUN-00:10 | 2925.14 | 28-JUN-13:20 | 2894.90 | 28-JUN-13:30 | 146.43 | 11-JUN-12:00 | 718.67 | 28-JUN-13:40 | 0.00 | 01-JUN-00:10 |
| July | 0.213659E+10 | 0.534135E+09 | 426.21 | 0.201999E+10 | 0.116596E+09 | 0.00 | 0.64 | 24-JUL-13:40 | 0.00 | 01-JUL-00:10 | 3812.55 | 24-JUL-13:30 | 3680.07 | 24-JUL-13:40 | 360.08 | 31-JUL-10:20 | 973.81 | 24-JUL-13:40 | 0.00 | 01-JUL-00:10 |
| August | 0.244835E+10 | 0.613098E+09 | 452.25 | 0.228286E+10 | 0.165496E+09 | 0.00 | 0.68 | 29-AUG-14:30 | 0.00 | 01-AUG-01:30 | 4095.69 | 29-AUG-12:30 | 3874.48 | 10-AUG-14:10 | 472.23 | 30-AUG-13:10 | 1049.45 | 29-AUG-14:30 | 0.00 | 01-AUG-00:10 |
| September | 0.130439E+10 | 0.322166E+09 | 275.05 | 0.122910E+10 | 75284340.69 | 0.00 | 0.58 | 14-SEP-13:40 | 0.00 | 01-SEP-00:10 | 3573.05 | 14-SEP-13:40 | 3236.81 | 14-SEP-14:00 | 368.67 | 14-SEP-13:10 | 844.74 | 14-SEP-13:40 | 0.00 | 01-SEP-00:10 |
| October | 0.262879E+09 | 67477837.79 | 111.08 | 0.262310E+09 | 569321.31 | 0.00 | 0.44 | 04-OCT-13:50 | 0.00 | 01-OCT-00:10 | 2506.39 | 04-OCT-13:40 | 2506.39 | 04-OCT-13:40 | 57.19 | 08-OCT-13:40 | 623.42 | 04-OCT-13:40 | 0.00 | 01-OCT-00:10 |
| November | 46383826.66 | 11549667.70 | 14.75 | 42133248.26 | 4250578.40 | 0.00 | 0.38 | 04-NOV-14:00 | 0.00 | 01-NOV-00:10 | 2263.45 | 04-NOV-14:00 | 2066.42 | 04-NOV-14:00 | 210.20 | 04-NOV-13:20 | 553.46 | 04-NOV-14:00 | 0.00 | 01-NOV-00:10 |
| December | 1492350.25 | 397214.49 | 4.67 | 1492350.25 | 0.00 | 0.00 | 0.03 | 05-DEC-12:50 | 0.00 | 01-DEC-00:10 | 158.27 | 05-DEC-12:50 | 158.27 | 05-DEC-12:50 | 0.00 | 05-DEC-14:30 | 42.02 | 05-DEC-12:50 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.896986E+10 | 0.224943E+10 | 2083.94 | 0.855657E+10 | 0.413287E+09 | 0.00 | ||||||||||||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | -0.0 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Maximum of Months | 0.244835E+10 | 0.613098E+09 | 452.25 | 0.228286E+10 | 0.165496E+09 | 0.00 | 0.68 | 0.00 | 4095.69 | 3874.48 | 472.23 | 1049.45 | 0.00 |
Report: DXReportMonthly
For: SPLIT TNE COOLING COIL
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
| April | 0.141162E+09 | 36478505.27 | 57.17 | 0.139068E+09 | 2094608.78 | 0.00 | 0.38 | 27-APR-16:07 | 0.00 | 01-APR-00:10 | 1928.90 | 27-APR-16:07 | 1878.20 | 27-APR-16:07 | 59.31 | 27-APR-17:30 | 499.35 | 27-APR-16:07 | 0.00 | 01-APR-00:10 |
| May | 0.434947E+09 | 0.110193E+09 | 176.89 | 0.415330E+09 | 19616871.10 | 0.00 | 0.37 | 06-MAY-13:40 | 0.00 | 01-MAY-00:10 | 1962.36 | 06-MAY-13:40 | 1815.32 | 15-MAY-16:03 | 223.33 | 06-MAY-13:30 | 478.88 | 06-MAY-13:40 | 0.00 | 01-MAY-00:10 |
| June | 0.923437E+09 | 0.234240E+09 | 319.85 | 0.905599E+09 | 17837911.09 | 0.00 | 0.42 | 28-JUN-16:14 | 0.00 | 01-JUN-00:10 | 2146.16 | 28-JUN-17:20 | 2144.07 | 28-JUN-16:14 | 98.90 | 12-JUN-17:04 | 547.65 | 28-JUN-17:10 | 0.00 | 01-JUN-00:10 |
| July | 0.158566E+10 | 0.399447E+09 | 409.75 | 0.148529E+10 | 0.100364E+09 | 0.00 | 0.54 | 24-JUL-15:10 | 0.00 | 01-JUL-00:10 | 2810.48 | 24-JUL-16:10 | 2709.09 | 24-JUL-15:10 | 345.68 | 31-JUL-10:20 | 743.53 | 24-JUL-15:10 | 0.00 | 01-JUL-00:10 |
| August | 0.172148E+10 | 0.435988E+09 | 416.84 | 0.158377E+10 | 0.137707E+09 | 0.00 | 0.53 | 10-AUG-16:30 | 0.00 | 01-AUG-01:10 | 2689.36 | 10-AUG-16:13 | 2591.70 | 10-AUG-16:30 | 337.97 | 25-AUG-11:30 | 727.92 | 10-AUG-16:30 | 0.00 | 01-AUG-00:10 |
| September | 0.482914E+09 | 0.121433E+09 | 188.28 | 0.441615E+09 | 41299549.66 | 0.00 | 0.34 | 14-SEP-16:12 | 0.00 | 01-SEP-00:10 | 1757.28 | 14-SEP-16:12 | 1613.56 | 14-SEP-16:15 | 256.52 | 14-SEP-13:20 | 437.82 | 14-SEP-16:12 | 0.00 | 01-SEP-00:10 |
| October | 5345861.99 | 1410390.89 | 5.83 | 5345861.99 | -0.0 | 0.00 | 0.08 | 04-OCT-15:10 | 0.00 | 01-OCT-00:10 | 395.71 | 04-OCT-15:10 | 395.71 | 04-OCT-15:10 | 0.00 | 04-OCT-15:50 | 104.15 | 04-OCT-15:10 | 0.00 | 01-OCT-00:10 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.529495E+10 | 0.133919E+10 | 1574.62 | 0.497603E+10 | 0.318920E+09 | 0.00 | ||||||||||||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | -0.0 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Maximum of Months | 0.172148E+10 | 0.435988E+09 | 416.84 | 0.158377E+10 | 0.137707E+09 | 0.00 | 0.54 | 0.00 | 2810.48 | 2709.09 | 345.68 | 743.53 | 0.00 |
Report: DXReportMonthly
For: SPLIT TN1 COOLING COIL
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
| April | 96130464.58 | 25026588.82 | 53.42 | 94443232.17 | 1687232.41 | 0.00 | 0.31 | 27-APR-16:07 | 0.00 | 01-APR-00:10 | 1520.89 | 27-APR-16:20 | 1477.60 | 27-APR-16:15 | 52.45 | 27-APR-17:30 | 397.14 | 27-APR-16:07 | 0.00 | 01-APR-00:10 |
| May | 0.309241E+09 | 78588240.90 | 151.80 | 0.292378E+09 | 16863274.02 | 0.00 | 0.31 | 15-MAY-16:15 | 0.00 | 01-MAY-00:10 | 1504.75 | 06-MAY-13:40 | 1484.71 | 15-MAY-16:15 | 184.46 | 06-MAY-13:30 | 376.67 | 15-MAY-16:15 | 0.00 | 01-MAY-00:10 |
| June | 0.653714E+09 | 0.166740E+09 | 298.55 | 0.639409E+09 | 14304280.33 | 0.00 | 0.38 | 28-JUN-17:20 | 0.00 | 01-JUN-00:10 | 1850.52 | 28-JUN-17:50 | 1820.90 | 28-JUN-17:20 | 110.33 | 12-JUN-17:00 | 473.44 | 28-JUN-17:20 | 0.00 | 01-JUN-00:10 |
| July | 0.124883E+10 | 0.316714E+09 | 418.42 | 0.116269E+10 | 86135638.43 | 0.00 | 0.47 | 24-JUL-18:00 | 0.00 | 01-JUL-00:10 | 2300.58 | 24-JUL-18:00 | 2190.32 | 24-JUL-18:00 | 262.35 | 11-JUL-16:03 | 602.87 | 24-JUL-18:00 | 0.00 | 01-JUL-00:10 |
| August | 0.133599E+10 | 0.341580E+09 | 438.57 | 0.122231E+10 | 0.113674E+09 | 0.00 | 0.47 | 10-AUG-16:40 | 0.00 | 01-AUG-02:00 | 2271.58 | 10-AUG-16:40 | 2181.05 | 10-AUG-17:07 | 292.76 | 30-AUG-13:20 | 621.35 | 10-AUG-16:40 | 0.00 | 01-AUG-00:10 |
| September | 0.339453E+09 | 85784903.87 | 178.02 | 0.308337E+09 | 31116479.23 | 0.00 | 0.30 | 14-SEP-16:25 | 0.00 | 01-SEP-00:10 | 1492.75 | 14-SEP-16:25 | 1357.84 | 14-SEP-16:25 | 215.74 | 14-SEP-13:30 | 374.07 | 14-SEP-16:25 | 0.00 | 01-SEP-00:10 |
| October | 2199755.07 | 582348.91 | 3.50 | 2199755.07 | -0.0 | 0.00 | 0.05 | 04-OCT-16:40 | 0.00 | 01-OCT-00:10 | 246.04 | 04-OCT-16:40 | 246.04 | 04-OCT-16:40 | 0.00 | 04-OCT-16:15 | 65.03 | 04-OCT-16:40 | 0.00 | 01-OCT-00:10 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.398555E+10 | 0.101502E+10 | 1542.28 | 0.372177E+10 | 0.263781E+09 | 0.00 | ||||||||||||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | -0.0 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Maximum of Months | 0.133599E+10 | 0.341580E+09 | 438.57 | 0.122231E+10 | 0.113674E+09 | 0.00 | 0.47 | 0.00 | 2300.58 | 2190.32 | 292.76 | 621.35 | 0.00 |
Report: DXReportMonthly
For: SPLIT TN2 COOLING COIL
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
| April | 96899828.24 | 25220510.38 | 54.08 | 95203425.54 | 1696402.71 | 0.00 | 0.32 | 27-APR-16:07 | 0.00 | 01-APR-00:10 | 1516.59 | 27-APR-16:07 | 1474.68 | 27-APR-16:07 | 52.03 | 27-APR-17:30 | 396.29 | 27-APR-16:07 | 0.00 | 01-APR-00:10 |
| May | 0.309935E+09 | 78753676.70 | 152.23 | 0.293105E+09 | 16829918.46 | 0.00 | 0.31 | 15-MAY-16:15 | 0.00 | 01-MAY-00:10 | 1517.06 | 06-MAY-13:40 | 1474.68 | 15-MAY-16:15 | 185.24 | 06-MAY-13:30 | 374.11 | 15-MAY-16:15 | 0.00 | 01-MAY-00:10 |
| June | 0.661934E+09 | 0.168808E+09 | 302.91 | 0.647429E+09 | 14505309.00 | 0.00 | 0.38 | 28-JUN-17:20 | 0.00 | 01-JUN-00:10 | 1828.80 | 28-JUN-17:50 | 1800.64 | 28-JUN-17:20 | 112.61 | 12-JUN-17:00 | 468.25 | 28-JUN-17:20 | 0.00 | 01-JUN-00:10 |
| July | 0.124629E+10 | 0.316035E+09 | 418.98 | 0.116043E+10 | 85865371.56 | 0.00 | 0.47 | 24-JUL-18:00 | 0.00 | 01-JUL-00:10 | 2286.07 | 24-JUL-18:00 | 2176.31 | 24-JUL-18:00 | 259.18 | 11-JUL-16:03 | 598.99 | 24-JUL-18:00 | 0.00 | 01-JUL-00:10 |
| August | 0.134045E+10 | 0.342585E+09 | 439.03 | 0.122627E+10 | 0.114178E+09 | 0.00 | 0.47 | 10-AUG-16:40 | 0.00 | 01-AUG-01:50 | 2252.33 | 10-AUG-16:30 | 2161.04 | 10-AUG-16:40 | 293.21 | 30-AUG-13:20 | 616.01 | 10-AUG-16:40 | 0.00 | 01-AUG-00:10 |
| September | 0.341280E+09 | 86223321.91 | 178.50 | 0.309932E+09 | 31347752.80 | 0.00 | 0.30 | 14-SEP-16:25 | 0.00 | 01-SEP-00:10 | 1480.26 | 14-SEP-16:25 | 1346.79 | 14-SEP-16:25 | 217.43 | 14-SEP-13:30 | 370.97 | 14-SEP-16:25 | 0.00 | 01-SEP-00:10 |
| October | 2239139.34 | 592817.93 | 3.67 | 2239139.34 | 0.00 | 0.00 | 0.05 | 04-OCT-16:30 | 0.00 | 01-OCT-00:10 | 238.90 | 04-OCT-16:30 | 238.90 | 04-OCT-16:30 | 0.00 | 04-OCT-15:30 | 63.15 | 04-OCT-16:30 | 0.00 | 01-OCT-00:10 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.399902E+10 | 0.101822E+10 | 1549.40 | 0.373460E+10 | 0.264423E+09 | 0.00 | ||||||||||||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Maximum of Months | 0.134045E+10 | 0.342585E+09 | 439.03 | 0.122627E+10 | 0.114178E+09 | 0.00 | 0.47 | 0.00 | 2286.07 | 2176.31 | 293.21 | 616.01 | 0.00 |
Report: DXReportMonthly
For: SPLIT TS1 COOLING COIL
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 418191.36 | 111195.65 | 1.17 | 418191.36 | -0.0 | 0.00 | 0.03 | 20-JAN-13:30 | 0.00 | 01-JAN-00:10 | 162.90 | 20-JAN-13:30 | 162.90 | 20-JAN-13:30 | 0.00 | 20-JAN-14:20 | 43.27 | 20-JAN-13:30 | 0.00 | 01-JAN-00:10 |
| February | 28659083.40 | 7461809.58 | 21.17 | 28658577.56 | 505.84 | 0.00 | 0.25 | 27-FEB-15:10 | 0.00 | 01-FEB-00:10 | 1346.05 | 27-FEB-15:10 | 1346.05 | 27-FEB-15:10 | 0.42 | 28-FEB-14:30 | 343.42 | 27-FEB-15:10 | 0.00 | 01-FEB-00:10 |
| March | 0.121803E+09 | 31616744.57 | 55.17 | 0.121803E+09 | -0.0 | 0.00 | 0.30 | 14-MAR-14:00 | 0.00 | 01-MAR-00:10 | 1619.43 | 14-MAR-14:00 | 1619.43 | 14-MAR-14:00 | 0.00 | 14-MAR-12:50 | 410.28 | 14-MAR-14:00 | 0.00 | 01-MAR-00:10 |
| April | 0.407686E+09 | 0.104560E+09 | 157.33 | 0.403544E+09 | 4142756.57 | 0.00 | 0.50 | 27-APR-14:30 | 0.00 | 01-APR-00:10 | 2803.47 | 27-APR-14:30 | 2803.47 | 27-APR-14:30 | 105.50 | 29-APR-13:30 | 710.64 | 27-APR-14:30 | 0.00 | 01-APR-00:10 |
| May | 0.703934E+09 | 0.178077E+09 | 246.33 | 0.679533E+09 | 24401432.32 | 0.00 | 0.44 | 15-MAY-14:10 | 0.00 | 01-MAY-00:10 | 2463.72 | 04-MAY-14:10 | 2448.38 | 15-MAY-14:10 | 251.50 | 06-MAY-13:30 | 605.30 | 15-MAY-14:10 | 0.00 | 01-MAY-00:10 |
| June | 0.100532E+10 | 0.255077E+09 | 339.79 | 0.987835E+09 | 17481565.61 | 0.00 | 0.43 | 28-JUN-14:10 | 0.00 | 01-JUN-00:10 | 2431.04 | 28-JUN-14:10 | 2420.65 | 28-JUN-14:20 | 135.90 | 11-JUN-12:00 | 610.84 | 28-JUN-15:10 | 0.00 | 01-JUN-00:10 |
| July | 0.181201E+10 | 0.456130E+09 | 443.92 | 0.170680E+10 | 0.105209E+09 | 0.00 | 0.55 | 24-JUL-13:50 | 0.00 | 01-JUL-00:20 | 3131.54 | 24-JUL-13:40 | 3021.02 | 24-JUL-13:50 | 305.31 | 15-JUL-14:00 | 813.88 | 24-JUL-13:50 | 0.00 | 01-JUL-00:10 |
| August | 0.207511E+10 | 0.524325E+09 | 482.52 | 0.192895E+10 | 0.146162E+09 | 0.00 | 0.62 | 29-AUG-14:30 | 0.00 | 01-AUG-02:20 | 3546.16 | 29-AUG-14:30 | 3344.07 | 10-AUG-14:20 | 433.65 | 30-AUG-13:10 | 925.20 | 29-AUG-14:30 | 0.00 | 01-AUG-00:10 |
| September | 0.117135E+10 | 0.290812E+09 | 300.50 | 0.110049E+10 | 70856510.17 | 0.00 | 0.55 | 23-SEP-13:50 | 0.00 | 01-SEP-00:10 | 3248.20 | 23-SEP-13:50 | 2932.86 | 23-SEP-13:50 | 349.50 | 14-SEP-13:00 | 772.11 | 23-SEP-13:50 | 0.00 | 01-SEP-00:10 |
| October | 0.271984E+09 | 69921552.17 | 129.08 | 0.270699E+09 | 1285518.83 | 0.00 | 0.43 | 04-OCT-14:10 | 0.00 | 01-OCT-00:10 | 2361.43 | 04-OCT-14:10 | 2361.43 | 04-OCT-14:10 | 59.34 | 08-OCT-13:40 | 588.50 | 04-OCT-14:10 | 0.00 | 01-OCT-00:10 |
| November | 53131999.15 | 13292018.38 | 21.92 | 48390871.50 | 4741127.65 | 0.00 | 0.39 | 04-NOV-14:00 | 0.00 | 01-NOV-00:10 | 2209.73 | 04-NOV-14:00 | 2010.76 | 04-NOV-14:00 | 211.21 | 04-NOV-13:30 | 539.79 | 04-NOV-14:00 | 0.00 | 01-NOV-00:10 |
| December | 8207628.71 | 2174370.77 | 8.67 | 8207628.71 | 0.00 | 0.00 | 0.07 | 03-DEC-14:00 | 0.00 | 01-DEC-00:10 | 383.18 | 03-DEC-14:00 | 383.18 | 03-DEC-14:00 | 0.00 | 05-DEC-14:00 | 101.31 | 03-DEC-14:00 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.765961E+10 | 0.193356E+10 | 2207.55 | 0.728533E+10 | 0.374280E+09 | 0.00 | ||||||||||||||
| Minimum of Months | 418191.36 | 111195.65 | 1.17 | 418191.36 | -0.0 | 0.00 | 0.03 | 0.00 | 162.90 | 162.90 | 0.00 | 43.27 | 0.00 | |||||||
| Maximum of Months | 0.207511E+10 | 0.524325E+09 | 482.52 | 0.192895E+10 | 0.146162E+09 | 0.00 | 0.62 | 0.00 | 3546.16 | 3344.07 | 433.65 | 925.20 | 0.00 |
Report: DXReportMonthly
For: SPLIT TS2 COOLING COIL
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 480979.62 | 127859.50 | 1.17 | 480979.62 | -0.0 | 0.00 | 0.03 | 20-JAN-13:30 | 0.00 | 01-JAN-00:10 | 160.93 | 20-JAN-13:30 | 160.93 | 20-JAN-13:30 | 0.00 | 20-JAN-14:20 | 42.74 | 20-JAN-13:30 | 0.00 | 01-JAN-00:10 |
| February | 29031751.19 | 7559426.99 | 21.17 | 29031270.90 | 480.29 | 0.00 | 0.25 | 27-FEB-15:00 | 0.00 | 01-FEB-00:10 | 1343.35 | 27-FEB-15:00 | 1343.35 | 27-FEB-15:00 | 0.40 | 28-FEB-14:30 | 342.67 | 27-FEB-15:00 | 0.00 | 01-FEB-00:10 |
| March | 0.123345E+09 | 32007621.40 | 55.75 | 0.123345E+09 | 0.00 | 0.00 | 0.30 | 14-MAR-14:00 | 0.00 | 01-MAR-00:10 | 1638.33 | 14-MAR-14:00 | 1638.33 | 14-MAR-14:00 | 0.00 | 18-MAR-13:50 | 414.73 | 14-MAR-14:00 | 0.00 | 01-MAR-00:10 |
| April | 0.412243E+09 | 0.105703E+09 | 159.17 | 0.408080E+09 | 4162609.64 | 0.00 | 0.50 | 27-APR-14:20 | 0.00 | 01-APR-00:10 | 2813.20 | 27-APR-14:20 | 2813.20 | 27-APR-14:20 | 105.75 | 29-APR-13:30 | 712.13 | 27-APR-14:30 | 0.00 | 01-APR-00:10 |
| May | 0.706436E+09 | 0.178657E+09 | 246.33 | 0.682077E+09 | 24358448.97 | 0.00 | 0.44 | 15-MAY-14:10 | 0.00 | 01-MAY-00:10 | 2476.72 | 04-MAY-14:10 | 2462.03 | 15-MAY-14:10 | 251.87 | 06-MAY-13:30 | 608.18 | 15-MAY-14:10 | 0.00 | 01-MAY-00:10 |
| June | 0.101450E+10 | 0.257314E+09 | 341.44 | 0.996818E+09 | 17677250.71 | 0.00 | 0.44 | 28-JUN-14:10 | 0.00 | 01-JUN-00:10 | 2441.59 | 28-JUN-14:10 | 2430.68 | 28-JUN-14:10 | 136.40 | 11-JUN-12:00 | 610.90 | 28-JUN-14:20 | 0.00 | 01-JUN-00:10 |
| July | 0.180955E+10 | 0.455368E+09 | 444.78 | 0.170465E+10 | 0.104893E+09 | 0.00 | 0.56 | 24-JUL-13:50 | 0.00 | 01-JUL-00:20 | 3145.76 | 24-JUL-13:40 | 3033.89 | 24-JUL-13:50 | 304.44 | 15-JUL-14:00 | 816.44 | 24-JUL-13:50 | 0.00 | 01-JUL-00:10 |
| August | 0.207943E+10 | 0.525148E+09 | 482.54 | 0.193287E+10 | 0.146554E+09 | 0.00 | 0.62 | 29-AUG-14:30 | 0.00 | 01-AUG-02:20 | 3552.11 | 29-AUG-14:30 | 3352.04 | 10-AUG-14:20 | 433.93 | 30-AUG-13:10 | 926.04 | 29-AUG-14:30 | 0.00 | 01-AUG-00:10 |
| September | 0.117174E+10 | 0.290782E+09 | 299.75 | 0.110089E+10 | 70853595.40 | 0.00 | 0.56 | 23-SEP-13:50 | 0.00 | 01-SEP-00:10 | 3254.15 | 23-SEP-13:50 | 2939.24 | 23-SEP-13:50 | 349.60 | 14-SEP-13:00 | 773.00 | 23-SEP-13:50 | 0.00 | 01-SEP-00:10 |
| October | 0.274944E+09 | 70662485.29 | 129.50 | 0.273710E+09 | 1234228.08 | 0.00 | 0.43 | 04-OCT-14:10 | 0.00 | 01-OCT-00:10 | 2369.33 | 04-OCT-14:10 | 2369.33 | 04-OCT-14:10 | 59.40 | 08-OCT-13:30 | 590.07 | 04-OCT-14:10 | 0.00 | 01-OCT-00:10 |
| November | 53343415.04 | 13343565.42 | 22.25 | 48609251.59 | 4734163.45 | 0.00 | 0.39 | 04-NOV-14:00 | 0.00 | 01-NOV-00:10 | 2214.06 | 04-NOV-14:00 | 2015.58 | 04-NOV-14:00 | 211.05 | 04-NOV-13:30 | 540.60 | 04-NOV-14:00 | 0.00 | 01-NOV-00:10 |
| December | 8459861.56 | 2240589.18 | 8.83 | 8459861.56 | -0.0 | 0.00 | 0.08 | 03-DEC-14:00 | 0.00 | 01-DEC-00:10 | 385.88 | 03-DEC-14:00 | 385.88 | 03-DEC-14:00 | 0.00 | 02-DEC-13:20 | 102.01 | 03-DEC-14:00 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.768349E+10 | 0.193891E+10 | 2212.67 | 0.730903E+10 | 0.374467E+09 | 0.00 | ||||||||||||||
| Minimum of Months | 480979.62 | 127859.50 | 1.17 | 480979.62 | -0.0 | 0.00 | 0.03 | 0.00 | 160.93 | 160.93 | 0.00 | 42.74 | 0.00 | |||||||
| Maximum of Months | 0.207943E+10 | 0.525148E+09 | 482.54 | 0.193287E+10 | 0.146554E+09 | 0.00 | 0.62 | 0.00 | 3552.11 | 3352.04 | 433.93 | 926.04 | 0.00 |
Report: WindowReportMonthly
For: GWINDOW1 S SWA
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 132.96 | 79.07 | 53.89 | 119.39 | 160.10 | 0.00 | 0.00 | 0.00 |
| February | 206.86 | 129.16 | 77.70 | 213.70 | 139.15 | 0.00 | 0.00 | 0.00 |
| March | 216.23 | 113.83 | 102.40 | 234.37 | 115.65 | 0.00 | 0.00 | 0.00 |
| April | 232.13 | 101.06 | 131.07 | 267.47 | 95.37 | 0.00 | 0.00 | 0.00 |
| May | 213.31 | 64.60 | 148.71 | 246.29 | 82.51 | 0.00 | 0.00 | 0.00 |
| June | 194.60 | 52.84 | 141.76 | 227.04 | 66.71 | 0.00 | 0.00 | 0.00 |
| July | 212.64 | 78.70 | 133.94 | 269.78 | 61.78 | 0.00 | 0.00 | 0.00 |
| August | 224.67 | 103.49 | 121.18 | 292.91 | 60.11 | 0.00 | 0.00 | 0.00 |
| September | 249.27 | 136.61 | 112.66 | 304.83 | 85.66 | 0.00 | 0.00 | 0.00 |
| October | 222.42 | 135.22 | 87.20 | 251.29 | 109.20 | 0.00 | 0.00 | 0.00 |
| November | 134.27 | 76.73 | 57.54 | 129.92 | 129.26 | 0.00 | 0.00 | 0.00 |
| December | 140.24 | 90.47 | 49.77 | 137.96 | 162.19 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 198.18 | 96.60 | 101.58 | 224.58 | 105.49 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 132.96 | 52.84 | 49.77 | 119.39 | 60.11 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 249.27 | 136.61 | 148.71 | 304.83 | 162.19 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: GWINDOW1 W SWA
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 33.62 | 9.98 | 23.64 | 14.72 | 112.78 | 0.00 | 0.00 | 0.00 |
| February | 59.73 | 22.25 | 37.48 | 43.12 | 96.59 | 0.00 | 0.00 | 0.00 |
| March | 84.14 | 28.43 | 55.71 | 73.93 | 76.75 | 0.00 | 0.00 | 0.00 |
| April | 127.73 | 48.74 | 78.99 | 133.46 | 61.40 | 0.00 | 0.00 | 0.00 |
| May | 164.75 | 67.00 | 97.75 | 184.65 | 52.64 | 0.00 | 0.00 | 0.00 |
| June | 158.40 | 61.51 | 96.89 | 179.46 | 42.18 | 0.00 | 0.00 | 0.00 |
| July | 196.02 | 103.19 | 92.83 | 240.32 | 38.95 | 0.00 | 0.00 | 0.00 |
| August | 161.81 | 82.54 | 79.28 | 200.14 | 38.65 | 0.00 | 0.00 | 0.00 |
| September | 132.26 | 63.63 | 68.63 | 150.14 | 56.14 | 0.00 | 0.00 | 0.00 |
| October | 75.32 | 30.81 | 44.51 | 69.24 | 73.56 | 0.00 | 0.00 | 0.00 |
| November | 37.48 | 10.68 | 26.80 | 21.71 | 88.82 | 0.00 | 0.00 | 0.00 |
| December | 31.80 | 11.15 | 20.64 | 17.66 | 113.17 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 105.53 | 45.17 | 60.37 | 111.15 | 70.85 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 31.80 | 9.98 | 20.64 | 14.72 | 38.65 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 196.02 | 103.19 | 97.75 | 240.32 | 113.17 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: GWINDOW1 W NWA
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 33.62 | 9.98 | 23.64 | 15.19 | 111.45 | 0.00 | 0.00 | 0.00 |
| February | 59.73 | 22.25 | 37.48 | 44.43 | 94.49 | 0.00 | 0.00 | 0.00 |
| March | 84.14 | 28.43 | 55.71 | 76.21 | 74.25 | 0.00 | 0.00 | 0.00 |
| April | 127.73 | 48.74 | 78.99 | 136.73 | 58.66 | 0.00 | 0.00 | 0.00 |
| May | 164.75 | 67.00 | 97.75 | 187.78 | 50.05 | 0.00 | 0.00 | 0.00 |
| June | 158.40 | 61.51 | 96.89 | 181.33 | 40.89 | 0.00 | 0.00 | 0.00 |
| July | 196.02 | 103.19 | 92.83 | 241.56 | 38.32 | 0.00 | 0.00 | 0.00 |
| August | 161.81 | 82.54 | 79.28 | 201.68 | 37.76 | 0.00 | 0.00 | 0.00 |
| September | 132.26 | 63.63 | 68.63 | 152.66 | 53.54 | 0.00 | 0.00 | 0.00 |
| October | 75.32 | 30.81 | 44.51 | 72.86 | 67.89 | 0.00 | 0.00 | 0.00 |
| November | 37.48 | 10.68 | 26.80 | 22.72 | 86.50 | 0.00 | 0.00 | 0.00 |
| December | 31.80 | 11.15 | 20.64 | 18.32 | 111.40 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 105.53 | 45.17 | 60.37 | 113.07 | 68.65 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 31.80 | 9.98 | 20.64 | 15.19 | 37.76 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 196.02 | 103.19 | 97.75 | 241.56 | 111.45 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: GWINDOW1 N NWA
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 30.02 | 0.00 | 30.02 | 1.44 | 177.20 | 0.00 | 0.00 | 0.00 |
| February | 46.71 | 0.00 | 46.71 | 11.62 | 150.88 | 0.00 | 0.00 | 0.00 |
| March | 68.83 | 0.00 | 68.83 | 36.16 | 115.98 | 0.00 | 0.00 | 0.00 |
| April | 97.54 | 0.47 | 97.07 | 74.99 | 88.53 | 0.00 | 0.00 | 0.00 |
| May | 125.25 | 3.66 | 121.59 | 112.50 | 73.66 | 0.00 | 0.00 | 0.00 |
| June | 131.76 | 8.67 | 123.09 | 124.59 | 58.91 | 0.00 | 0.00 | 0.00 |
| July | 125.33 | 9.86 | 115.47 | 128.67 | 54.99 | 0.00 | 0.00 | 0.00 |
| August | 101.81 | 3.10 | 98.71 | 105.93 | 54.44 | 0.00 | 0.00 | 0.00 |
| September | 78.78 | 0.05 | 78.73 | 62.45 | 82.76 | 0.00 | 0.00 | 0.00 |
| October | 53.95 | 0.00 | 53.95 | 28.89 | 105.48 | 0.00 | 0.00 | 0.00 |
| November | 33.98 | 0.00 | 33.98 | 6.61 | 136.11 | 0.00 | 0.00 | 0.00 |
| December | 25.51 | 0.00 | 25.51 | 0.77 | 175.06 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 76.77 | 2.17 | 74.60 | 58.16 | 105.96 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 25.51 | 0.00 | 25.51 | 0.77 | 54.44 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 131.76 | 9.86 | 123.09 | 128.67 | 177.20 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: GWINDOW1 S SEA
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 132.96 | 79.07 | 53.89 | 124.43 | 138.70 | 0.00 | 0.00 | 0.00 |
| February | 206.86 | 129.16 | 77.70 | 218.50 | 126.52 | 0.00 | 0.00 | 0.00 |
| March | 216.23 | 113.83 | 102.40 | 235.15 | 113.54 | 0.00 | 0.00 | 0.00 |
| April | 232.13 | 101.06 | 131.07 | 265.05 | 98.18 | 0.00 | 0.00 | 0.00 |
| May | 213.31 | 64.60 | 148.71 | 242.36 | 88.65 | 0.00 | 0.00 | 0.00 |
| June | 194.60 | 52.84 | 141.76 | 221.47 | 74.46 | 0.00 | 0.00 | 0.00 |
| July | 212.64 | 78.70 | 133.94 | 263.49 | 71.12 | 0.00 | 0.00 | 0.00 |
| August | 224.67 | 103.49 | 121.18 | 286.39 | 72.42 | 0.00 | 0.00 | 0.00 |
| September | 249.27 | 136.61 | 112.66 | 300.65 | 95.44 | 0.00 | 0.00 | 0.00 |
| October | 222.42 | 135.22 | 87.20 | 248.81 | 116.08 | 0.00 | 0.00 | 0.00 |
| November | 134.27 | 76.73 | 57.54 | 130.59 | 125.99 | 0.00 | 0.00 | 0.00 |
| December | 140.24 | 90.47 | 49.77 | 141.07 | 146.78 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 198.18 | 96.60 | 101.58 | 223.13 | 105.56 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 132.96 | 52.84 | 49.77 | 124.43 | 71.12 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 249.27 | 136.61 | 148.71 | 300.65 | 146.78 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: GWINDOW1 E SEA
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 31.58 | 7.91 | 23.67 | 13.11 | 96.60 | 0.00 | 0.00 | 0.00 |
| February | 57.90 | 20.33 | 37.57 | 41.41 | 86.47 | 0.00 | 0.00 | 0.00 |
| March | 87.01 | 31.41 | 55.60 | 76.82 | 73.81 | 0.00 | 0.00 | 0.00 |
| April | 134.95 | 56.13 | 78.82 | 140.67 | 60.42 | 0.00 | 0.00 | 0.00 |
| May | 143.51 | 49.97 | 93.54 | 153.38 | 54.97 | 0.00 | 0.00 | 0.00 |
| June | 171.81 | 74.80 | 97.01 | 193.86 | 45.35 | 0.00 | 0.00 | 0.00 |
| July | 160.37 | 72.20 | 88.16 | 185.81 | 42.39 | 0.00 | 0.00 | 0.00 |
| August | 156.92 | 78.36 | 78.56 | 186.75 | 43.78 | 0.00 | 0.00 | 0.00 |
| September | 116.31 | 53.67 | 62.64 | 123.31 | 60.90 | 0.00 | 0.00 | 0.00 |
| October | 76.35 | 32.76 | 43.60 | 68.31 | 76.70 | 0.00 | 0.00 | 0.00 |
| November | 37.24 | 10.55 | 26.70 | 20.80 | 86.04 | 0.00 | 0.00 | 0.00 |
| December | 30.44 | 9.75 | 20.68 | 15.35 | 101.15 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 100.55 | 41.58 | 58.97 | 101.93 | 68.97 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 30.44 | 7.91 | 20.68 | 13.11 | 42.39 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 171.81 | 78.36 | 97.01 | 193.86 | 101.15 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: GWINDOW1 E NEA
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 31.58 | 7.91 | 23.67 | 11.58 | 110.63 | 0.00 | 0.00 | 0.00 |
| February | 57.90 | 20.33 | 37.57 | 39.74 | 92.88 | 0.00 | 0.00 | 0.00 |
| March | 87.01 | 31.41 | 55.60 | 78.00 | 72.19 | 0.00 | 0.00 | 0.00 |
| April | 134.95 | 56.13 | 78.82 | 144.96 | 55.75 | 0.00 | 0.00 | 0.00 |
| May | 143.51 | 49.97 | 93.54 | 159.18 | 48.14 | 0.00 | 0.00 | 0.00 |
| June | 171.81 | 74.80 | 97.01 | 198.92 | 39.53 | 0.00 | 0.00 | 0.00 |
| July | 160.37 | 72.20 | 88.16 | 191.83 | 35.66 | 0.00 | 0.00 | 0.00 |
| August | 156.92 | 78.36 | 78.56 | 193.06 | 35.34 | 0.00 | 0.00 | 0.00 |
| September | 116.31 | 53.67 | 62.64 | 128.76 | 51.45 | 0.00 | 0.00 | 0.00 |
| October | 76.35 | 32.76 | 43.60 | 73.17 | 66.02 | 0.00 | 0.00 | 0.00 |
| November | 37.24 | 10.55 | 26.70 | 21.40 | 85.90 | 0.00 | 0.00 | 0.00 |
| December | 30.44 | 9.75 | 20.68 | 14.53 | 110.05 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 100.55 | 41.58 | 58.97 | 104.92 | 66.84 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 30.44 | 7.91 | 20.68 | 11.58 | 35.34 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 171.81 | 78.36 | 97.01 | 198.92 | 110.63 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: GWINDOW1 N NEA
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 30.02 | 0.00 | 30.02 | 1.43 | 177.15 | 0.00 | 0.00 | 0.00 |
| February | 46.71 | 0.00 | 46.71 | 11.58 | 150.78 | 0.00 | 0.00 | 0.00 |
| March | 68.83 | 0.00 | 68.83 | 35.97 | 115.76 | 0.00 | 0.00 | 0.00 |
| April | 97.54 | 0.47 | 97.07 | 74.42 | 88.38 | 0.00 | 0.00 | 0.00 |
| May | 125.25 | 3.66 | 121.59 | 112.40 | 72.87 | 0.00 | 0.00 | 0.00 |
| June | 131.76 | 8.67 | 123.09 | 123.30 | 59.00 | 0.00 | 0.00 | 0.00 |
| July | 125.33 | 9.86 | 115.47 | 128.84 | 54.15 | 0.00 | 0.00 | 0.00 |
| August | 101.81 | 3.10 | 98.71 | 105.49 | 54.09 | 0.00 | 0.00 | 0.00 |
| September | 78.78 | 0.05 | 78.73 | 62.35 | 81.80 | 0.00 | 0.00 | 0.00 |
| October | 53.95 | 0.00 | 53.95 | 28.66 | 105.02 | 0.00 | 0.00 | 0.00 |
| November | 33.98 | 0.00 | 33.98 | 6.56 | 136.03 | 0.00 | 0.00 | 0.00 |
| December | 25.51 | 0.00 | 25.51 | 0.75 | 175.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 76.77 | 2.17 | 74.60 | 57.93 | 105.63 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 25.51 | 0.00 | 25.51 | 0.75 | 54.09 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 131.76 | 9.86 | 123.09 | 128.84 | 177.15 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: GWINDOW1 N N1A
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 30.02 | 0.00 | 30.02 | 1.29 | 180.95 | 0.00 | 0.00 | 0.00 |
| February | 46.71 | 0.00 | 46.71 | 11.11 | 153.96 | 0.00 | 0.00 | 0.00 |
| March | 68.83 | 0.00 | 68.83 | 35.39 | 118.44 | 0.00 | 0.00 | 0.00 |
| April | 97.54 | 0.47 | 97.07 | 74.35 | 90.17 | 0.00 | 0.00 | 0.00 |
| May | 125.25 | 3.66 | 121.59 | 111.40 | 75.67 | 0.00 | 0.00 | 0.00 |
| June | 131.76 | 8.67 | 123.09 | 123.62 | 60.38 | 0.00 | 0.00 | 0.00 |
| July | 125.33 | 9.86 | 115.47 | 129.28 | 55.15 | 0.00 | 0.00 | 0.00 |
| August | 101.81 | 3.10 | 98.71 | 106.35 | 54.68 | 0.00 | 0.00 | 0.00 |
| September | 78.78 | 0.05 | 78.73 | 61.93 | 84.51 | 0.00 | 0.00 | 0.00 |
| October | 53.95 | 0.00 | 53.95 | 27.88 | 108.69 | 0.00 | 0.00 | 0.00 |
| November | 33.98 | 0.00 | 33.98 | 6.17 | 139.45 | 0.00 | 0.00 | 0.00 |
| December | 25.51 | 0.00 | 25.51 | 0.67 | 178.60 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 76.77 | 2.17 | 74.60 | 57.74 | 108.18 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 25.51 | 0.00 | 25.51 | 0.67 | 54.68 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 131.76 | 9.86 | 123.09 | 129.28 | 180.95 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: GWINDOW1 N N2A
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 30.02 | 0.00 | 30.02 | 1.29 | 180.95 | 0.00 | 0.00 | 0.00 |
| February | 46.71 | 0.00 | 46.71 | 11.11 | 153.96 | 0.00 | 0.00 | 0.00 |
| March | 68.83 | 0.00 | 68.83 | 35.38 | 118.43 | 0.00 | 0.00 | 0.00 |
| April | 97.54 | 0.47 | 97.07 | 74.31 | 90.17 | 0.00 | 0.00 | 0.00 |
| May | 125.25 | 3.66 | 121.59 | 111.42 | 75.60 | 0.00 | 0.00 | 0.00 |
| June | 131.76 | 8.67 | 123.09 | 123.52 | 60.43 | 0.00 | 0.00 | 0.00 |
| July | 125.33 | 9.86 | 115.47 | 129.30 | 55.10 | 0.00 | 0.00 | 0.00 |
| August | 101.81 | 3.10 | 98.71 | 106.34 | 54.67 | 0.00 | 0.00 | 0.00 |
| September | 78.78 | 0.05 | 78.73 | 61.94 | 84.43 | 0.00 | 0.00 | 0.00 |
| October | 53.95 | 0.00 | 53.95 | 27.89 | 108.64 | 0.00 | 0.00 | 0.00 |
| November | 33.98 | 0.00 | 33.98 | 6.17 | 139.45 | 0.00 | 0.00 | 0.00 |
| December | 25.51 | 0.00 | 25.51 | 0.67 | 178.60 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 76.77 | 2.17 | 74.60 | 57.73 | 108.16 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 25.51 | 0.00 | 25.51 | 0.67 | 54.67 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 131.76 | 9.86 | 123.09 | 129.30 | 180.95 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: GWINDOW1 S S1A
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 132.96 | 79.07 | 53.89 | 118.40 | 163.65 | 0.00 | 0.00 | 0.00 |
| February | 206.86 | 129.16 | 77.70 | 212.21 | 142.53 | 0.00 | 0.00 | 0.00 |
| March | 216.23 | 113.83 | 102.40 | 232.73 | 119.18 | 0.00 | 0.00 | 0.00 |
| April | 232.13 | 101.06 | 131.07 | 265.81 | 98.24 | 0.00 | 0.00 | 0.00 |
| May | 213.31 | 64.60 | 148.71 | 244.41 | 85.77 | 0.00 | 0.00 | 0.00 |
| June | 194.60 | 52.84 | 141.76 | 226.05 | 68.49 | 0.00 | 0.00 | 0.00 |
| July | 212.64 | 78.70 | 133.94 | 270.28 | 61.87 | 0.00 | 0.00 | 0.00 |
| August | 224.67 | 103.49 | 121.18 | 293.24 | 60.36 | 0.00 | 0.00 | 0.00 |
| September | 249.27 | 136.61 | 112.66 | 304.35 | 87.10 | 0.00 | 0.00 | 0.00 |
| October | 222.42 | 135.22 | 87.20 | 249.15 | 114.57 | 0.00 | 0.00 | 0.00 |
| November | 134.27 | 76.73 | 57.54 | 128.55 | 133.40 | 0.00 | 0.00 | 0.00 |
| December | 140.24 | 90.47 | 49.77 | 137.01 | 165.83 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 198.18 | 96.60 | 101.58 | 223.53 | 108.26 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 132.96 | 52.84 | 49.77 | 118.40 | 60.36 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 249.27 | 136.61 | 148.71 | 304.35 | 165.83 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: GWINDOW1 S S2A
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 132.96 | 79.07 | 53.89 | 118.67 | 162.61 | 0.00 | 0.00 | 0.00 |
| February | 206.86 | 129.16 | 77.70 | 212.49 | 141.84 | 0.00 | 0.00 | 0.00 |
| March | 216.23 | 113.83 | 102.40 | 232.73 | 119.08 | 0.00 | 0.00 | 0.00 |
| April | 232.13 | 101.06 | 131.07 | 265.49 | 98.56 | 0.00 | 0.00 | 0.00 |
| May | 213.31 | 64.60 | 148.71 | 243.83 | 86.42 | 0.00 | 0.00 | 0.00 |
| June | 194.60 | 52.84 | 141.76 | 225.50 | 69.03 | 0.00 | 0.00 | 0.00 |
| July | 212.64 | 78.70 | 133.94 | 269.91 | 62.23 | 0.00 | 0.00 | 0.00 |
| August | 224.67 | 103.49 | 121.18 | 292.83 | 60.83 | 0.00 | 0.00 | 0.00 |
| September | 249.27 | 136.61 | 112.66 | 304.03 | 87.55 | 0.00 | 0.00 | 0.00 |
| October | 222.42 | 135.22 | 87.20 | 248.78 | 115.34 | 0.00 | 0.00 | 0.00 |
| November | 134.27 | 76.73 | 57.54 | 128.47 | 133.44 | 0.00 | 0.00 | 0.00 |
| December | 140.24 | 90.47 | 49.77 | 137.19 | 165.08 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 198.18 | 96.60 | 101.58 | 223.33 | 108.35 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 132.96 | 52.84 | 49.77 | 118.67 | 60.83 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 249.27 | 136.61 | 148.71 | 304.03 | 165.08 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MWINDOW1 S SWA
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 132.96 | 79.07 | 53.89 | 116.78 | 167.41 | 0.00 | 0.00 | 0.00 |
| February | 206.86 | 129.16 | 77.70 | 208.71 | 147.58 | 0.00 | 0.00 | 0.00 |
| March | 216.23 | 113.83 | 102.40 | 227.53 | 127.45 | 0.00 | 0.00 | 0.00 |
| April | 232.13 | 101.06 | 131.07 | 257.50 | 108.98 | 0.00 | 0.00 | 0.00 |
| May | 213.31 | 64.60 | 148.71 | 237.73 | 92.36 | 0.00 | 0.00 | 0.00 |
| June | 194.60 | 52.84 | 141.76 | 221.48 | 71.88 | 0.00 | 0.00 | 0.00 |
| July | 212.64 | 78.70 | 133.94 | 266.89 | 63.75 | 0.00 | 0.00 | 0.00 |
| August | 224.67 | 103.49 | 121.18 | 290.70 | 61.50 | 0.00 | 0.00 | 0.00 |
| September | 249.27 | 136.61 | 112.66 | 302.35 | 88.17 | 0.00 | 0.00 | 0.00 |
| October | 222.42 | 135.22 | 87.20 | 247.49 | 115.49 | 0.00 | 0.00 | 0.00 |
| November | 134.27 | 76.73 | 57.54 | 127.40 | 135.01 | 0.00 | 0.00 | 0.00 |
| December | 140.24 | 90.47 | 49.77 | 135.56 | 168.72 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 198.18 | 96.60 | 101.58 | 220.02 | 112.19 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 132.96 | 52.84 | 49.77 | 116.78 | 61.50 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 249.27 | 136.61 | 148.71 | 302.35 | 168.72 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MWINDOW1 W SWA
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 33.62 | 9.98 | 23.64 | 13.86 | 118.29 | 0.00 | 0.00 | 0.00 |
| February | 59.73 | 22.25 | 37.48 | 40.64 | 102.73 | 0.00 | 0.00 | 0.00 |
| March | 84.14 | 28.43 | 55.71 | 69.59 | 84.43 | 0.00 | 0.00 | 0.00 |
| April | 127.73 | 48.74 | 78.99 | 126.58 | 70.05 | 0.00 | 0.00 | 0.00 |
| May | 164.75 | 67.00 | 97.75 | 178.51 | 58.80 | 0.00 | 0.00 | 0.00 |
| June | 158.40 | 61.51 | 96.89 | 175.48 | 45.39 | 0.00 | 0.00 | 0.00 |
| July | 196.02 | 103.19 | 92.83 | 238.14 | 40.15 | 0.00 | 0.00 | 0.00 |
| August | 161.81 | 82.54 | 79.28 | 198.58 | 39.54 | 0.00 | 0.00 | 0.00 |
| September | 132.26 | 63.63 | 68.63 | 148.51 | 57.83 | 0.00 | 0.00 | 0.00 |
| October | 75.32 | 30.81 | 44.51 | 67.13 | 77.90 | 0.00 | 0.00 | 0.00 |
| November | 37.48 | 10.68 | 26.80 | 20.59 | 92.93 | 0.00 | 0.00 | 0.00 |
| December | 31.80 | 11.15 | 20.64 | 16.90 | 118.02 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 105.53 | 45.17 | 60.37 | 108.32 | 75.38 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 31.80 | 9.98 | 20.64 | 13.86 | 39.54 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 196.02 | 103.19 | 97.75 | 238.14 | 118.29 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MWINDOW1 W NWA
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 33.62 | 9.98 | 23.64 | 14.46 | 116.73 | 0.00 | 0.00 | 0.00 |
| February | 59.73 | 22.25 | 37.48 | 42.50 | 99.78 | 0.00 | 0.00 | 0.00 |
| March | 84.14 | 28.43 | 55.71 | 72.97 | 80.00 | 0.00 | 0.00 | 0.00 |
| April | 127.73 | 48.74 | 78.99 | 130.41 | 66.25 | 0.00 | 0.00 | 0.00 |
| May | 164.75 | 67.00 | 97.75 | 179.97 | 57.92 | 0.00 | 0.00 | 0.00 |
| June | 158.40 | 61.51 | 96.89 | 176.34 | 45.09 | 0.00 | 0.00 | 0.00 |
| July | 196.02 | 103.19 | 92.83 | 239.10 | 39.86 | 0.00 | 0.00 | 0.00 |
| August | 161.81 | 82.54 | 79.28 | 199.82 | 39.05 | 0.00 | 0.00 | 0.00 |
| September | 132.26 | 63.63 | 68.63 | 150.28 | 56.59 | 0.00 | 0.00 | 0.00 |
| October | 75.32 | 30.81 | 44.51 | 70.37 | 72.71 | 0.00 | 0.00 | 0.00 |
| November | 37.48 | 10.68 | 26.80 | 21.76 | 90.39 | 0.00 | 0.00 | 0.00 |
| December | 31.80 | 11.15 | 20.64 | 17.79 | 115.84 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 105.53 | 45.17 | 60.37 | 110.09 | 73.23 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 31.80 | 9.98 | 20.64 | 14.46 | 39.05 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 196.02 | 103.19 | 97.75 | 239.10 | 116.73 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MWINDOW1 N NWA
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 30.02 | 0.00 | 30.02 | 1.10 | 185.50 | 0.00 | 0.00 | 0.00 |
| February | 46.71 | 0.00 | 46.71 | 9.85 | 159.71 | 0.00 | 0.00 | 0.00 |
| March | 68.83 | 0.00 | 68.83 | 32.38 | 125.39 | 0.00 | 0.00 | 0.00 |
| April | 97.54 | 0.47 | 97.07 | 66.81 | 100.35 | 0.00 | 0.00 | 0.00 |
| May | 125.25 | 3.66 | 121.59 | 101.23 | 85.15 | 0.00 | 0.00 | 0.00 |
| June | 131.76 | 8.67 | 123.09 | 117.21 | 64.66 | 0.00 | 0.00 | 0.00 |
| July | 125.33 | 9.86 | 115.47 | 125.59 | 57.12 | 0.00 | 0.00 | 0.00 |
| August | 101.81 | 3.10 | 98.71 | 103.72 | 56.22 | 0.00 | 0.00 | 0.00 |
| September | 78.78 | 0.05 | 78.73 | 59.48 | 87.53 | 0.00 | 0.00 | 0.00 |
| October | 53.95 | 0.00 | 53.95 | 26.02 | 113.08 | 0.00 | 0.00 | 0.00 |
| November | 33.98 | 0.00 | 33.98 | 5.68 | 142.19 | 0.00 | 0.00 | 0.00 |
| December | 25.51 | 0.00 | 25.51 | 0.56 | 182.04 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 76.77 | 2.17 | 74.60 | 54.41 | 113.02 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 25.51 | 0.00 | 25.51 | 0.56 | 56.22 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 131.76 | 9.86 | 123.09 | 125.59 | 185.50 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MWINDOW1 S SEA
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 132.96 | 79.07 | 53.89 | 116.74 | 167.28 | 0.00 | 0.00 | 0.00 |
| February | 206.86 | 129.16 | 77.70 | 208.50 | 147.26 | 0.00 | 0.00 | 0.00 |
| March | 216.23 | 113.83 | 102.40 | 226.93 | 127.16 | 0.00 | 0.00 | 0.00 |
| April | 232.13 | 101.06 | 131.07 | 256.26 | 109.19 | 0.00 | 0.00 | 0.00 |
| May | 213.31 | 64.60 | 148.71 | 237.50 | 91.77 | 0.00 | 0.00 | 0.00 |
| June | 194.60 | 52.84 | 141.76 | 220.84 | 71.66 | 0.00 | 0.00 | 0.00 |
| July | 212.64 | 78.70 | 133.94 | 266.82 | 63.12 | 0.00 | 0.00 | 0.00 |
| August | 224.67 | 103.49 | 121.18 | 290.36 | 61.14 | 0.00 | 0.00 | 0.00 |
| September | 249.27 | 136.61 | 112.66 | 302.21 | 87.59 | 0.00 | 0.00 | 0.00 |
| October | 222.42 | 135.22 | 87.20 | 247.09 | 115.29 | 0.00 | 0.00 | 0.00 |
| November | 134.27 | 76.73 | 57.54 | 127.23 | 134.92 | 0.00 | 0.00 | 0.00 |
| December | 140.24 | 90.47 | 49.77 | 135.46 | 168.53 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 198.18 | 96.60 | 101.58 | 219.68 | 111.91 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 132.96 | 52.84 | 49.77 | 116.74 | 61.14 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 249.27 | 136.61 | 148.71 | 302.21 | 168.53 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MWINDOW1 E SEA
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 31.58 | 7.91 | 23.67 | 10.61 | 117.76 | 0.00 | 0.00 | 0.00 |
| February | 57.90 | 20.33 | 37.57 | 36.52 | 101.77 | 0.00 | 0.00 | 0.00 |
| March | 87.01 | 31.41 | 55.60 | 71.52 | 82.76 | 0.00 | 0.00 | 0.00 |
| April | 134.95 | 56.13 | 78.82 | 134.58 | 66.98 | 0.00 | 0.00 | 0.00 |
| May | 143.51 | 49.97 | 93.54 | 150.08 | 56.75 | 0.00 | 0.00 | 0.00 |
| June | 171.81 | 74.80 | 97.01 | 193.47 | 43.53 | 0.00 | 0.00 | 0.00 |
| July | 160.37 | 72.20 | 88.16 | 188.52 | 37.61 | 0.00 | 0.00 | 0.00 |
| August | 156.92 | 78.36 | 78.56 | 190.07 | 37.00 | 0.00 | 0.00 | 0.00 |
| September | 116.31 | 53.67 | 62.64 | 124.54 | 55.89 | 0.00 | 0.00 | 0.00 |
| October | 76.35 | 32.76 | 43.60 | 67.42 | 76.17 | 0.00 | 0.00 | 0.00 |
| November | 37.24 | 10.55 | 26.70 | 19.43 | 92.71 | 0.00 | 0.00 | 0.00 |
| December | 30.44 | 9.75 | 20.68 | 13.45 | 117.14 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 100.55 | 41.58 | 58.97 | 100.34 | 73.71 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 30.44 | 7.91 | 20.68 | 10.61 | 37.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 171.81 | 78.36 | 97.01 | 193.47 | 117.76 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MWINDOW1 E NEA
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 31.58 | 7.91 | 23.67 | 10.90 | 115.94 | 0.00 | 0.00 | 0.00 |
| February | 57.90 | 20.33 | 37.57 | 37.81 | 98.23 | 0.00 | 0.00 | 0.00 |
| March | 87.01 | 31.41 | 55.60 | 74.74 | 77.92 | 0.00 | 0.00 | 0.00 |
| April | 134.95 | 56.13 | 78.82 | 138.28 | 63.19 | 0.00 | 0.00 | 0.00 |
| May | 143.51 | 49.97 | 93.54 | 151.44 | 55.87 | 0.00 | 0.00 | 0.00 |
| June | 171.81 | 74.80 | 97.01 | 194.25 | 43.23 | 0.00 | 0.00 | 0.00 |
| July | 160.37 | 72.20 | 88.16 | 189.47 | 37.29 | 0.00 | 0.00 | 0.00 |
| August | 156.92 | 78.36 | 78.56 | 191.29 | 36.49 | 0.00 | 0.00 | 0.00 |
| September | 116.31 | 53.67 | 62.64 | 126.31 | 54.55 | 0.00 | 0.00 | 0.00 |
| October | 76.35 | 32.76 | 43.60 | 70.50 | 70.83 | 0.00 | 0.00 | 0.00 |
| November | 37.24 | 10.55 | 26.70 | 20.39 | 89.85 | 0.00 | 0.00 | 0.00 |
| December | 30.44 | 9.75 | 20.68 | 13.94 | 114.53 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 100.55 | 41.58 | 58.97 | 101.93 | 71.37 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 30.44 | 7.91 | 20.68 | 10.90 | 36.49 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 171.81 | 78.36 | 97.01 | 194.25 | 115.94 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MWINDOW1 N NEA
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 30.02 | 0.00 | 30.02 | 1.09 | 185.45 | 0.00 | 0.00 | 0.00 |
| February | 46.71 | 0.00 | 46.71 | 9.79 | 159.57 | 0.00 | 0.00 | 0.00 |
| March | 68.83 | 0.00 | 68.83 | 32.05 | 124.96 | 0.00 | 0.00 | 0.00 |
| April | 97.54 | 0.47 | 97.07 | 65.55 | 100.55 | 0.00 | 0.00 | 0.00 |
| May | 125.25 | 3.66 | 121.59 | 100.87 | 84.59 | 0.00 | 0.00 | 0.00 |
| June | 131.76 | 8.67 | 123.09 | 116.44 | 64.44 | 0.00 | 0.00 | 0.00 |
| July | 125.33 | 9.86 | 115.47 | 125.57 | 56.56 | 0.00 | 0.00 | 0.00 |
| August | 101.81 | 3.10 | 98.71 | 103.32 | 55.87 | 0.00 | 0.00 | 0.00 |
| September | 78.78 | 0.05 | 78.73 | 59.30 | 86.82 | 0.00 | 0.00 | 0.00 |
| October | 53.95 | 0.00 | 53.95 | 25.56 | 112.79 | 0.00 | 0.00 | 0.00 |
| November | 33.98 | 0.00 | 33.98 | 5.61 | 142.09 | 0.00 | 0.00 | 0.00 |
| December | 25.51 | 0.00 | 25.51 | 0.55 | 181.98 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 76.77 | 2.17 | 74.60 | 54.08 | 112.75 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 25.51 | 0.00 | 25.51 | 0.55 | 55.87 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 131.76 | 9.86 | 123.09 | 125.57 | 185.45 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MWINDOW1 N N1A
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 30.02 | 0.00 | 30.02 | 1.00 | 189.15 | 0.00 | 0.00 | 0.00 |
| February | 46.71 | 0.00 | 46.71 | 9.35 | 162.79 | 0.00 | 0.00 | 0.00 |
| March | 68.83 | 0.00 | 68.83 | 31.69 | 128.06 | 0.00 | 0.00 | 0.00 |
| April | 97.54 | 0.47 | 97.07 | 65.82 | 103.10 | 0.00 | 0.00 | 0.00 |
| May | 125.25 | 3.66 | 121.59 | 100.88 | 86.73 | 0.00 | 0.00 | 0.00 |
| June | 131.76 | 8.67 | 123.09 | 117.60 | 65.09 | 0.00 | 0.00 | 0.00 |
| July | 125.33 | 9.86 | 115.47 | 126.96 | 56.79 | 0.00 | 0.00 | 0.00 |
| August | 101.81 | 3.10 | 98.71 | 104.76 | 56.01 | 0.00 | 0.00 | 0.00 |
| September | 78.78 | 0.05 | 78.73 | 59.55 | 88.48 | 0.00 | 0.00 | 0.00 |
| October | 53.95 | 0.00 | 53.95 | 24.56 | 118.24 | 0.00 | 0.00 | 0.00 |
| November | 33.98 | 0.00 | 33.98 | 5.15 | 146.34 | 0.00 | 0.00 | 0.00 |
| December | 25.51 | 0.00 | 25.51 | 0.49 | 185.67 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 76.77 | 2.17 | 74.60 | 54.26 | 115.31 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 25.51 | 0.00 | 25.51 | 0.49 | 56.01 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 131.76 | 9.86 | 123.09 | 126.96 | 189.15 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MWINDOW1 N N2A
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 30.02 | 0.00 | 30.02 | 0.99 | 189.15 | 0.00 | 0.00 | 0.00 |
| February | 46.71 | 0.00 | 46.71 | 9.35 | 162.78 | 0.00 | 0.00 | 0.00 |
| March | 68.83 | 0.00 | 68.83 | 31.67 | 128.02 | 0.00 | 0.00 | 0.00 |
| April | 97.54 | 0.47 | 97.07 | 65.70 | 103.22 | 0.00 | 0.00 | 0.00 |
| May | 125.25 | 3.66 | 121.59 | 100.87 | 86.69 | 0.00 | 0.00 | 0.00 |
| June | 131.76 | 8.67 | 123.09 | 117.58 | 65.09 | 0.00 | 0.00 | 0.00 |
| July | 125.33 | 9.86 | 115.47 | 126.96 | 56.77 | 0.00 | 0.00 | 0.00 |
| August | 101.81 | 3.10 | 98.71 | 104.75 | 56.00 | 0.00 | 0.00 | 0.00 |
| September | 78.78 | 0.05 | 78.73 | 59.55 | 88.44 | 0.00 | 0.00 | 0.00 |
| October | 53.95 | 0.00 | 53.95 | 24.54 | 118.24 | 0.00 | 0.00 | 0.00 |
| November | 33.98 | 0.00 | 33.98 | 5.14 | 146.33 | 0.00 | 0.00 | 0.00 |
| December | 25.51 | 0.00 | 25.51 | 0.49 | 185.67 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 76.77 | 2.17 | 74.60 | 54.24 | 115.31 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 25.51 | 0.00 | 25.51 | 0.49 | 56.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 131.76 | 9.86 | 123.09 | 126.96 | 189.15 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MWINDOW1 S S1A
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 132.96 | 79.07 | 53.89 | 115.81 | 170.88 | 0.00 | 0.00 | 0.00 |
| February | 206.86 | 129.16 | 77.70 | 207.06 | 151.62 | 0.00 | 0.00 | 0.00 |
| March | 216.23 | 113.83 | 102.40 | 225.33 | 133.21 | 0.00 | 0.00 | 0.00 |
| April | 232.13 | 101.06 | 131.07 | 255.76 | 112.83 | 0.00 | 0.00 | 0.00 |
| May | 213.31 | 64.60 | 148.71 | 237.47 | 93.88 | 0.00 | 0.00 | 0.00 |
| June | 194.60 | 52.84 | 141.76 | 221.88 | 72.29 | 0.00 | 0.00 | 0.00 |
| July | 212.64 | 78.70 | 133.94 | 268.02 | 63.29 | 0.00 | 0.00 | 0.00 |
| August | 224.67 | 103.49 | 121.18 | 291.57 | 61.26 | 0.00 | 0.00 | 0.00 |
| September | 249.27 | 136.61 | 112.66 | 302.46 | 88.87 | 0.00 | 0.00 | 0.00 |
| October | 222.42 | 135.22 | 87.20 | 245.56 | 120.99 | 0.00 | 0.00 | 0.00 |
| November | 134.27 | 76.73 | 57.54 | 125.81 | 140.14 | 0.00 | 0.00 | 0.00 |
| December | 140.24 | 90.47 | 49.77 | 134.41 | 173.01 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 198.18 | 96.60 | 101.58 | 219.28 | 115.02 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 132.96 | 52.84 | 49.77 | 115.81 | 61.26 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 249.27 | 136.61 | 148.71 | 302.46 | 173.01 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MWINDOW1 S S2A
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 132.96 | 79.07 | 53.89 | 115.80 | 170.87 | 0.00 | 0.00 | 0.00 |
| February | 206.86 | 129.16 | 77.70 | 207.05 | 151.60 | 0.00 | 0.00 | 0.00 |
| March | 216.23 | 113.83 | 102.40 | 225.29 | 133.22 | 0.00 | 0.00 | 0.00 |
| April | 232.13 | 101.06 | 131.07 | 255.67 | 112.91 | 0.00 | 0.00 | 0.00 |
| May | 213.31 | 64.60 | 148.71 | 237.47 | 93.84 | 0.00 | 0.00 | 0.00 |
| June | 194.60 | 52.84 | 141.76 | 221.86 | 72.28 | 0.00 | 0.00 | 0.00 |
| July | 212.64 | 78.70 | 133.94 | 268.02 | 63.27 | 0.00 | 0.00 | 0.00 |
| August | 224.67 | 103.49 | 121.18 | 291.56 | 61.24 | 0.00 | 0.00 | 0.00 |
| September | 249.27 | 136.61 | 112.66 | 302.45 | 88.84 | 0.00 | 0.00 | 0.00 |
| October | 222.42 | 135.22 | 87.20 | 245.55 | 120.99 | 0.00 | 0.00 | 0.00 |
| November | 134.27 | 76.73 | 57.54 | 125.80 | 140.14 | 0.00 | 0.00 | 0.00 |
| December | 140.24 | 90.47 | 49.77 | 134.41 | 172.99 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 198.18 | 96.60 | 101.58 | 219.27 | 115.01 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 132.96 | 52.84 | 49.77 | 115.80 | 61.24 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 249.27 | 136.61 | 148.71 | 302.45 | 172.99 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: TWINDOW1 S SWA
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 132.96 | 79.07 | 53.89 | 117.44 | 160.78 | 0.00 | 0.00 | 0.00 |
| February | 206.86 | 129.16 | 77.70 | 209.01 | 141.07 | 0.00 | 0.00 | 0.00 |
| March | 216.23 | 113.83 | 102.40 | 228.12 | 118.60 | 0.00 | 0.00 | 0.00 |
| April | 232.13 | 101.06 | 131.07 | 258.97 | 99.29 | 0.00 | 0.00 | 0.00 |
| May | 213.31 | 64.60 | 148.71 | 239.98 | 82.24 | 0.00 | 0.00 | 0.00 |
| June | 194.60 | 52.84 | 141.76 | 222.10 | 65.19 | 0.00 | 0.00 | 0.00 |
| July | 212.64 | 78.70 | 133.94 | 265.33 | 59.53 | 0.00 | 0.00 | 0.00 |
| August | 224.67 | 103.49 | 121.18 | 289.48 | 57.30 | 0.00 | 0.00 | 0.00 |
| September | 249.27 | 136.61 | 112.66 | 304.25 | 78.76 | 0.00 | 0.00 | 0.00 |
| October | 222.42 | 135.22 | 87.20 | 250.54 | 102.31 | 0.00 | 0.00 | 0.00 |
| November | 134.27 | 76.73 | 57.54 | 128.53 | 127.00 | 0.00 | 0.00 | 0.00 |
| December | 140.24 | 90.47 | 49.77 | 136.03 | 161.58 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 198.18 | 96.60 | 101.58 | 220.83 | 104.30 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 132.96 | 52.84 | 49.77 | 117.44 | 57.30 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 249.27 | 136.61 | 148.71 | 304.25 | 161.58 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: TWINDOW1 W SWA
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 33.62 | 9.98 | 23.64 | 13.87 | 113.36 | 0.00 | 0.00 | 0.00 |
| February | 59.73 | 22.25 | 37.48 | 40.43 | 97.91 | 0.00 | 0.00 | 0.00 |
| March | 84.14 | 28.43 | 55.71 | 69.67 | 78.21 | 0.00 | 0.00 | 0.00 |
| April | 127.73 | 48.74 | 78.99 | 127.29 | 63.38 | 0.00 | 0.00 | 0.00 |
| May | 164.75 | 67.00 | 97.75 | 179.89 | 52.04 | 0.00 | 0.00 | 0.00 |
| June | 158.40 | 61.51 | 96.89 | 175.75 | 40.89 | 0.00 | 0.00 | 0.00 |
| July | 196.02 | 103.19 | 92.83 | 236.85 | 37.19 | 0.00 | 0.00 | 0.00 |
| August | 161.81 | 82.54 | 79.28 | 197.61 | 36.64 | 0.00 | 0.00 | 0.00 |
| September | 132.26 | 63.63 | 68.63 | 149.36 | 51.28 | 0.00 | 0.00 | 0.00 |
| October | 75.32 | 30.81 | 44.51 | 68.46 | 68.45 | 0.00 | 0.00 | 0.00 |
| November | 37.48 | 10.68 | 26.80 | 20.91 | 87.12 | 0.00 | 0.00 | 0.00 |
| December | 31.80 | 11.15 | 20.64 | 16.75 | 112.68 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 105.53 | 45.17 | 60.37 | 108.51 | 69.80 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 31.80 | 9.98 | 20.64 | 13.87 | 36.64 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 196.02 | 103.19 | 97.75 | 236.85 | 113.36 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: TWINDOW1 W NWA
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 33.62 | 9.98 | 23.64 | 14.75 | 112.11 | 0.00 | 0.00 | 0.00 |
| February | 59.73 | 22.25 | 37.48 | 42.94 | 95.60 | 0.00 | 0.00 | 0.00 |
| March | 84.14 | 28.43 | 55.71 | 73.30 | 75.97 | 0.00 | 0.00 | 0.00 |
| April | 127.73 | 48.74 | 78.99 | 130.87 | 61.71 | 0.00 | 0.00 | 0.00 |
| May | 164.75 | 67.00 | 97.75 | 181.99 | 51.35 | 0.00 | 0.00 | 0.00 |
| June | 158.40 | 61.51 | 96.89 | 177.05 | 40.63 | 0.00 | 0.00 | 0.00 |
| July | 196.02 | 103.19 | 92.83 | 238.26 | 36.96 | 0.00 | 0.00 | 0.00 |
| August | 161.81 | 82.54 | 79.28 | 199.50 | 36.15 | 0.00 | 0.00 | 0.00 |
| September | 132.26 | 63.63 | 68.63 | 152.54 | 49.57 | 0.00 | 0.00 | 0.00 |
| October | 75.32 | 30.81 | 44.51 | 72.58 | 65.24 | 0.00 | 0.00 | 0.00 |
| November | 37.48 | 10.68 | 26.80 | 22.37 | 85.51 | 0.00 | 0.00 | 0.00 |
| December | 31.80 | 11.15 | 20.64 | 18.03 | 111.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 105.53 | 45.17 | 60.37 | 110.79 | 68.36 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 31.80 | 9.98 | 20.64 | 14.75 | 36.15 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 196.02 | 103.19 | 97.75 | 238.26 | 112.11 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: TWINDOW1 N NWA
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 30.02 | 0.00 | 30.02 | 1.28 | 178.24 | 0.00 | 0.00 | 0.00 |
| February | 46.71 | 0.00 | 46.71 | 10.42 | 153.32 | 0.00 | 0.00 | 0.00 |
| March | 68.83 | 0.00 | 68.83 | 33.07 | 119.40 | 0.00 | 0.00 | 0.00 |
| April | 97.54 | 0.47 | 97.07 | 67.94 | 93.71 | 0.00 | 0.00 | 0.00 |
| May | 125.25 | 3.66 | 121.59 | 105.09 | 75.86 | 0.00 | 0.00 | 0.00 |
| June | 131.76 | 8.67 | 123.09 | 119.42 | 58.84 | 0.00 | 0.00 | 0.00 |
| July | 125.33 | 9.86 | 115.47 | 125.25 | 53.32 | 0.00 | 0.00 | 0.00 |
| August | 101.81 | 3.10 | 98.71 | 104.01 | 52.35 | 0.00 | 0.00 | 0.00 |
| September | 78.78 | 0.05 | 78.73 | 63.02 | 76.88 | 0.00 | 0.00 | 0.00 |
| October | 53.95 | 0.00 | 53.95 | 29.27 | 101.59 | 0.00 | 0.00 | 0.00 |
| November | 33.98 | 0.00 | 33.98 | 6.43 | 134.69 | 0.00 | 0.00 | 0.00 |
| December | 25.51 | 0.00 | 25.51 | 0.69 | 174.54 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 76.77 | 2.17 | 74.60 | 55.76 | 105.84 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 25.51 | 0.00 | 25.51 | 0.69 | 52.35 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 131.76 | 9.86 | 123.09 | 125.25 | 178.24 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: TWINDOW1 S SEA
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 132.96 | 79.07 | 53.89 | 117.36 | 160.61 | 0.00 | 0.00 | 0.00 |
| February | 206.86 | 129.16 | 77.70 | 208.66 | 140.59 | 0.00 | 0.00 | 0.00 |
| March | 216.23 | 113.83 | 102.40 | 227.25 | 118.01 | 0.00 | 0.00 | 0.00 |
| April | 232.13 | 101.06 | 131.07 | 257.25 | 98.83 | 0.00 | 0.00 | 0.00 |
| May | 213.31 | 64.60 | 148.71 | 238.98 | 81.29 | 0.00 | 0.00 | 0.00 |
| June | 194.60 | 52.84 | 141.76 | 220.33 | 64.61 | 0.00 | 0.00 | 0.00 |
| July | 212.64 | 78.70 | 133.94 | 264.70 | 58.43 | 0.00 | 0.00 | 0.00 |
| August | 224.67 | 103.49 | 121.18 | 288.45 | 56.69 | 0.00 | 0.00 | 0.00 |
| September | 249.27 | 136.61 | 112.66 | 303.60 | 77.68 | 0.00 | 0.00 | 0.00 |
| October | 222.42 | 135.22 | 87.20 | 249.64 | 101.81 | 0.00 | 0.00 | 0.00 |
| November | 134.27 | 76.73 | 57.54 | 128.27 | 126.79 | 0.00 | 0.00 | 0.00 |
| December | 140.24 | 90.47 | 49.77 | 135.87 | 161.32 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 198.18 | 96.60 | 101.58 | 220.04 | 103.72 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 132.96 | 52.84 | 49.77 | 117.36 | 56.69 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 249.27 | 136.61 | 148.71 | 303.60 | 161.32 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: TWINDOW1 E SEA
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 31.58 | 7.91 | 23.67 | 10.97 | 113.14 | 0.00 | 0.00 | 0.00 |
| February | 57.90 | 20.33 | 37.57 | 37.04 | 97.65 | 0.00 | 0.00 | 0.00 |
| March | 87.01 | 31.41 | 55.60 | 72.13 | 77.00 | 0.00 | 0.00 | 0.00 |
| April | 134.95 | 56.13 | 78.82 | 136.03 | 60.79 | 0.00 | 0.00 | 0.00 |
| May | 143.51 | 49.97 | 93.54 | 151.93 | 50.58 | 0.00 | 0.00 | 0.00 |
| June | 171.81 | 74.80 | 97.01 | 193.96 | 39.61 | 0.00 | 0.00 | 0.00 |
| July | 160.37 | 72.20 | 88.16 | 187.81 | 35.07 | 0.00 | 0.00 | 0.00 |
| August | 156.92 | 78.36 | 78.56 | 189.40 | 34.56 | 0.00 | 0.00 | 0.00 |
| September | 116.31 | 53.67 | 62.64 | 125.89 | 49.75 | 0.00 | 0.00 | 0.00 |
| October | 76.35 | 32.76 | 43.60 | 69.46 | 67.50 | 0.00 | 0.00 | 0.00 |
| November | 37.24 | 10.55 | 26.70 | 20.16 | 87.29 | 0.00 | 0.00 | 0.00 |
| December | 30.44 | 9.75 | 20.68 | 13.83 | 112.34 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 100.55 | 41.58 | 58.97 | 101.04 | 68.64 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 30.44 | 7.91 | 20.68 | 10.97 | 34.56 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 171.81 | 78.36 | 97.01 | 193.96 | 113.14 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: TWINDOW1 E NEA
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 31.58 | 7.91 | 23.67 | 11.32 | 111.42 | 0.00 | 0.00 | 0.00 |
| February | 57.90 | 20.33 | 37.57 | 38.53 | 94.27 | 0.00 | 0.00 | 0.00 |
| March | 87.01 | 31.41 | 55.60 | 75.41 | 74.09 | 0.00 | 0.00 | 0.00 |
| April | 134.95 | 56.13 | 78.82 | 139.30 | 58.85 | 0.00 | 0.00 | 0.00 |
| May | 143.51 | 49.97 | 93.54 | 153.77 | 49.81 | 0.00 | 0.00 | 0.00 |
| June | 171.81 | 74.80 | 97.01 | 195.07 | 39.34 | 0.00 | 0.00 | 0.00 |
| July | 160.37 | 72.20 | 88.16 | 189.18 | 34.78 | 0.00 | 0.00 | 0.00 |
| August | 156.92 | 78.36 | 78.56 | 191.18 | 34.02 | 0.00 | 0.00 | 0.00 |
| September | 116.31 | 53.67 | 62.64 | 128.80 | 47.83 | 0.00 | 0.00 | 0.00 |
| October | 76.35 | 32.76 | 43.60 | 73.15 | 63.60 | 0.00 | 0.00 | 0.00 |
| November | 37.24 | 10.55 | 26.70 | 21.16 | 85.15 | 0.00 | 0.00 | 0.00 |
| December | 30.44 | 9.75 | 20.68 | 14.38 | 109.90 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 100.55 | 41.58 | 58.97 | 102.93 | 66.80 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 30.44 | 7.91 | 20.68 | 11.32 | 34.02 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 171.81 | 78.36 | 97.01 | 195.07 | 111.42 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: TWINDOW1 N NEA
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 30.02 | 0.00 | 30.02 | 1.26 | 178.18 | 0.00 | 0.00 | 0.00 |
| February | 46.71 | 0.00 | 46.71 | 10.32 | 153.05 | 0.00 | 0.00 | 0.00 |
| March | 68.83 | 0.00 | 68.83 | 32.55 | 118.66 | 0.00 | 0.00 | 0.00 |
| April | 97.54 | 0.47 | 97.07 | 66.22 | 93.17 | 0.00 | 0.00 | 0.00 |
| May | 125.25 | 3.66 | 121.59 | 103.88 | 74.97 | 0.00 | 0.00 | 0.00 |
| June | 131.76 | 8.67 | 123.09 | 117.43 | 58.33 | 0.00 | 0.00 | 0.00 |
| July | 125.33 | 9.86 | 115.47 | 124.70 | 52.33 | 0.00 | 0.00 | 0.00 |
| August | 101.81 | 3.10 | 98.71 | 102.78 | 51.69 | 0.00 | 0.00 | 0.00 |
| September | 78.78 | 0.05 | 78.73 | 61.99 | 75.62 | 0.00 | 0.00 | 0.00 |
| October | 53.95 | 0.00 | 53.95 | 28.48 | 100.77 | 0.00 | 0.00 | 0.00 |
| November | 33.98 | 0.00 | 33.98 | 6.30 | 134.54 | 0.00 | 0.00 | 0.00 |
| December | 25.51 | 0.00 | 25.51 | 0.66 | 174.44 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 76.77 | 2.17 | 74.60 | 54.99 | 105.25 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 25.51 | 0.00 | 25.51 | 0.66 | 51.69 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 131.76 | 9.86 | 123.09 | 124.70 | 178.18 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: TWINDOW1 N N1A
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 30.02 | 0.00 | 30.02 | 1.18 | 181.65 | 0.00 | 0.00 | 0.00 |
| February | 46.71 | 0.00 | 46.71 | 10.14 | 155.91 | 0.00 | 0.00 | 0.00 |
| March | 68.83 | 0.00 | 68.83 | 32.91 | 121.07 | 0.00 | 0.00 | 0.00 |
| April | 97.54 | 0.47 | 97.07 | 68.12 | 95.14 | 0.00 | 0.00 | 0.00 |
| May | 125.25 | 3.66 | 121.59 | 105.48 | 77.51 | 0.00 | 0.00 | 0.00 |
| June | 131.76 | 8.67 | 123.09 | 119.35 | 60.40 | 0.00 | 0.00 | 0.00 |
| July | 125.33 | 9.86 | 115.47 | 126.34 | 54.08 | 0.00 | 0.00 | 0.00 |
| August | 101.81 | 3.10 | 98.71 | 104.73 | 53.20 | 0.00 | 0.00 | 0.00 |
| September | 78.78 | 0.05 | 78.73 | 62.97 | 78.75 | 0.00 | 0.00 | 0.00 |
| October | 53.95 | 0.00 | 53.95 | 29.05 | 103.38 | 0.00 | 0.00 | 0.00 |
| November | 33.98 | 0.00 | 33.98 | 6.15 | 137.56 | 0.00 | 0.00 | 0.00 |
| December | 25.51 | 0.00 | 25.51 | 0.62 | 177.84 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 76.77 | 2.17 | 74.60 | 55.87 | 107.81 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 25.51 | 0.00 | 25.51 | 0.62 | 53.20 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 131.76 | 9.86 | 123.09 | 126.34 | 181.65 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: TWINDOW1 N N2A
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 30.02 | 0.00 | 30.02 | 1.18 | 181.65 | 0.00 | 0.00 | 0.00 |
| February | 46.71 | 0.00 | 46.71 | 10.13 | 155.89 | 0.00 | 0.00 | 0.00 |
| March | 68.83 | 0.00 | 68.83 | 32.87 | 121.00 | 0.00 | 0.00 | 0.00 |
| April | 97.54 | 0.47 | 97.07 | 67.96 | 95.13 | 0.00 | 0.00 | 0.00 |
| May | 125.25 | 3.66 | 121.59 | 105.36 | 77.44 | 0.00 | 0.00 | 0.00 |
| June | 131.76 | 8.67 | 123.09 | 119.20 | 60.37 | 0.00 | 0.00 | 0.00 |
| July | 125.33 | 9.86 | 115.47 | 126.30 | 54.01 | 0.00 | 0.00 | 0.00 |
| August | 101.81 | 3.10 | 98.71 | 104.65 | 53.15 | 0.00 | 0.00 | 0.00 |
| September | 78.78 | 0.05 | 78.73 | 62.89 | 78.62 | 0.00 | 0.00 | 0.00 |
| October | 53.95 | 0.00 | 53.95 | 28.99 | 103.31 | 0.00 | 0.00 | 0.00 |
| November | 33.98 | 0.00 | 33.98 | 6.14 | 137.55 | 0.00 | 0.00 | 0.00 |
| December | 25.51 | 0.00 | 25.51 | 0.62 | 177.84 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 76.77 | 2.17 | 74.60 | 55.80 | 107.77 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 25.51 | 0.00 | 25.51 | 0.62 | 53.15 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 131.76 | 9.86 | 123.09 | 126.30 | 181.65 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: TWINDOW1 S S1A
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 132.96 | 79.07 | 53.89 | 116.59 | 164.01 | 0.00 | 0.00 | 0.00 |
| February | 206.86 | 129.16 | 77.70 | 207.87 | 144.17 | 0.00 | 0.00 | 0.00 |
| March | 216.23 | 113.83 | 102.40 | 227.26 | 121.46 | 0.00 | 0.00 | 0.00 |
| April | 232.13 | 101.06 | 131.07 | 258.39 | 101.73 | 0.00 | 0.00 | 0.00 |
| May | 213.31 | 64.60 | 148.71 | 239.91 | 84.20 | 0.00 | 0.00 | 0.00 |
| June | 194.60 | 52.84 | 141.76 | 222.04 | 66.92 | 0.00 | 0.00 | 0.00 |
| July | 212.64 | 78.70 | 133.94 | 266.19 | 60.25 | 0.00 | 0.00 | 0.00 |
| August | 224.67 | 103.49 | 121.18 | 290.07 | 58.23 | 0.00 | 0.00 | 0.00 |
| September | 249.27 | 136.61 | 112.66 | 303.82 | 81.02 | 0.00 | 0.00 | 0.00 |
| October | 222.42 | 135.22 | 87.20 | 249.47 | 105.69 | 0.00 | 0.00 | 0.00 |
| November | 134.27 | 76.73 | 57.54 | 127.64 | 130.17 | 0.00 | 0.00 | 0.00 |
| December | 140.24 | 90.47 | 49.77 | 135.17 | 164.98 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 198.18 | 96.60 | 101.58 | 220.39 | 106.73 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 132.96 | 52.84 | 49.77 | 116.59 | 58.23 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 249.27 | 136.61 | 148.71 | 303.82 | 164.98 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: TWINDOW1 S S2A
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 132.96 | 79.07 | 53.89 | 116.58 | 164.00 | 0.00 | 0.00 | 0.00 |
| February | 206.86 | 129.16 | 77.70 | 207.84 | 144.12 | 0.00 | 0.00 | 0.00 |
| March | 216.23 | 113.83 | 102.40 | 227.19 | 121.41 | 0.00 | 0.00 | 0.00 |
| April | 232.13 | 101.06 | 131.07 | 258.25 | 101.71 | 0.00 | 0.00 | 0.00 |
| May | 213.31 | 64.60 | 148.71 | 239.85 | 84.12 | 0.00 | 0.00 | 0.00 |
| June | 194.60 | 52.84 | 141.76 | 221.92 | 66.87 | 0.00 | 0.00 | 0.00 |
| July | 212.64 | 78.70 | 133.94 | 266.15 | 60.16 | 0.00 | 0.00 | 0.00 |
| August | 224.67 | 103.49 | 121.18 | 290.01 | 58.18 | 0.00 | 0.00 | 0.00 |
| September | 249.27 | 136.61 | 112.66 | 303.79 | 80.92 | 0.00 | 0.00 | 0.00 |
| October | 222.42 | 135.22 | 87.20 | 249.42 | 105.65 | 0.00 | 0.00 | 0.00 |
| November | 134.27 | 76.73 | 57.54 | 127.62 | 130.16 | 0.00 | 0.00 | 0.00 |
| December | 140.24 | 90.47 | 49.77 | 135.15 | 164.96 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 198.18 | 96.60 | 101.58 | 220.33 | 106.68 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 132.96 | 52.84 | 49.77 | 116.58 | 58.18 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 249.27 | 136.61 | 148.71 | 303.79 | 164.96 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: TWINDOW14
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 7.58 | 1.90 | 5.68 | 2.56 | 28.32 | 151.00 | 0.00 | 0.00 |
| February | 13.89 | 4.88 | 9.01 | 8.78 | 24.51 | 153.17 | 0.00 | 0.00 |
| March | 20.88 | 7.54 | 13.34 | 17.33 | 19.87 | 258.50 | 0.00 | 0.00 |
| April | 32.38 | 13.47 | 18.91 | 32.50 | 16.05 | 230.33 | 0.00 | 0.00 |
| May | 34.44 | 11.99 | 22.44 | 35.93 | 13.82 | 320.00 | 0.00 | 0.00 |
| June | 41.23 | 17.95 | 23.28 | 45.66 | 11.07 | 288.17 | 0.00 | 0.00 |
| July | 38.48 | 17.33 | 21.16 | 44.07 | 9.94 | 337.00 | 0.00 | 0.00 |
| August | 37.65 | 18.80 | 18.85 | 44.55 | 9.77 | 325.50 | 0.00 | 0.00 |
| September | 27.91 | 12.88 | 15.03 | 29.87 | 13.57 | 452.67 | 0.00 | 0.00 |
| October | 18.32 | 7.86 | 10.46 | 16.69 | 17.60 | 352.83 | 0.00 | 0.00 |
| November | 8.94 | 2.53 | 6.41 | 4.70 | 22.35 | 327.33 | 0.00 | 0.00 |
| December | 7.30 | 2.34 | 4.96 | 3.27 | 28.05 | 306.33 | 0.00 | 0.00 |
| Annual Sum or Average | 24.13 | 9.98 | 14.15 | 23.90 | 17.88 | 3502.83 | 0.00 | 0.00 |
| Minimum of Months | 7.30 | 1.90 | 4.96 | 2.56 | 9.77 | 151.00 | 0.00 | 0.00 |
| Maximum of Months | 41.23 | 18.80 | 23.28 | 45.66 | 28.32 | 452.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ENTRANCE DOOR
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 22.57 | 5.65 | 16.92 | 8.82 | 74.51 | 0.00 | 0.00 | 0.00 |
| February | 41.38 | 14.53 | 26.85 | 28.92 | 64.51 | 0.00 | 0.00 | 0.00 |
| March | 62.18 | 22.45 | 39.73 | 55.24 | 53.00 | 0.00 | 0.00 | 0.00 |
| April | 96.44 | 40.11 | 56.32 | 101.82 | 42.66 | 0.00 | 0.00 | 0.00 |
| May | 102.56 | 35.71 | 66.85 | 110.84 | 38.44 | 0.00 | 0.00 | 0.00 |
| June | 122.78 | 53.46 | 69.33 | 139.08 | 31.66 | 0.00 | 0.00 | 0.00 |
| July | 114.61 | 51.60 | 63.01 | 133.18 | 29.23 | 0.00 | 0.00 | 0.00 |
| August | 112.14 | 56.00 | 56.14 | 133.58 | 29.44 | 0.00 | 0.00 | 0.00 |
| September | 83.12 | 38.36 | 44.76 | 89.40 | 41.04 | 0.00 | 0.00 | 0.00 |
| October | 54.57 | 23.41 | 31.16 | 50.22 | 51.76 | 0.00 | 0.00 | 0.00 |
| November | 26.62 | 7.54 | 19.08 | 15.07 | 61.61 | 0.00 | 0.00 | 0.00 |
| December | 21.75 | 6.97 | 14.78 | 10.74 | 75.32 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 71.86 | 29.71 | 42.14 | 73.29 | 49.36 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 21.75 | 5.65 | 14.78 | 8.82 | 29.23 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 122.78 | 56.00 | 69.33 | 139.08 | 75.32 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MWINDOW14
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 7.58 | 1.90 | 5.68 | 2.31 | 30.87 | 569.83 | 0.00 | 0.00 |
| February | 13.89 | 4.88 | 9.01 | 8.24 | 26.58 | 462.50 | 0.00 | 0.00 |
| March | 20.88 | 7.54 | 13.34 | 16.55 | 21.84 | 555.50 | 0.00 | 0.00 |
| April | 32.38 | 13.47 | 18.91 | 31.48 | 17.63 | 444.50 | 0.00 | 0.00 |
| May | 34.44 | 11.99 | 22.44 | 34.69 | 15.38 | 468.50 | 0.00 | 0.00 |
| June | 41.23 | 17.95 | 23.28 | 44.85 | 11.96 | 391.17 | 0.00 | 0.00 |
| July | 38.48 | 17.33 | 21.16 | 43.67 | 10.48 | 404.83 | 0.00 | 0.00 |
| August | 37.65 | 18.80 | 18.85 | 44.15 | 10.32 | 402.17 | 0.00 | 0.00 |
| September | 27.91 | 12.88 | 15.03 | 28.88 | 15.16 | 533.17 | 0.00 | 0.00 |
| October | 18.32 | 7.86 | 10.46 | 15.56 | 20.22 | 590.00 | 0.00 | 0.00 |
| November | 8.94 | 2.53 | 6.41 | 4.29 | 24.76 | 633.50 | 0.00 | 0.00 |
| December | 7.30 | 2.34 | 4.96 | 3.00 | 30.62 | 579.33 | 0.00 | 0.00 |
| Annual Sum or Average | 24.13 | 9.98 | 14.15 | 23.21 | 19.62 | 6035.00 | 0.00 | 0.00 |
| Minimum of Months | 7.30 | 1.90 | 4.96 | 2.31 | 10.32 | 391.17 | 0.00 | 0.00 |
| Maximum of Months | 41.23 | 18.80 | 23.28 | 44.85 | 30.87 | 633.50 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: GWINDOW1 S SWA
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.356115E+09 | 0.211787E+09 | 0.144327E+09 | 0.319774E+09 | 0.428804E+09 |
| February | 0.500446E+09 | 0.312463E+09 | 0.187983E+09 | 0.516982E+09 | 0.336633E+09 |
| March | 0.579159E+09 | 0.304880E+09 | 0.274279E+09 | 0.627733E+09 | 0.309767E+09 |
| April | 0.601691E+09 | 0.261958E+09 | 0.339733E+09 | 0.693286E+09 | 0.247204E+09 |
| May | 0.571336E+09 | 0.173034E+09 | 0.398303E+09 | 0.659662E+09 | 0.221005E+09 |
| June | 0.504391E+09 | 0.136950E+09 | 0.367441E+09 | 0.588484E+09 | 0.172905E+09 |
| July | 0.569545E+09 | 0.210801E+09 | 0.358744E+09 | 0.722589E+09 | 0.165480E+09 |
| August | 0.601744E+09 | 0.277187E+09 | 0.324557E+09 | 0.784532E+09 | 0.161004E+09 |
| September | 0.646105E+09 | 0.354088E+09 | 0.292017E+09 | 0.790115E+09 | 0.222028E+09 |
| October | 0.595727E+09 | 0.362163E+09 | 0.233564E+09 | 0.673066E+09 | 0.292488E+09 |
| November | 0.348015E+09 | 0.198875E+09 | 0.149140E+09 | 0.336740E+09 | 0.335054E+09 |
| December | 0.375617E+09 | 0.242303E+09 | 0.133314E+09 | 0.369505E+09 | 0.434397E+09 |
| Annual Sum or Average | 0.624989E+10 | 0.304649E+10 | 0.320340E+10 | 0.708247E+10 | 0.332677E+10 |
| Minimum of Months | 0.348015E+09 | 0.136950E+09 | 0.133314E+09 | 0.319774E+09 | 0.161004E+09 |
| Maximum of Months | 0.646105E+09 | 0.362163E+09 | 0.398303E+09 | 0.790115E+09 | 0.434397E+09 |
Report: WindowEnergyReportMonthly
For: GWINDOW1 W SWA
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 90052656.22 | 26738428.29 | 63314227.93 | 39427433.34 | 0.302061E+09 |
| February | 0.144505E+09 | 53823828.75 | 90681094.50 | 0.104320E+09 | 0.233666E+09 |
| March | 0.225360E+09 | 76140086.25 | 0.149220E+09 | 0.198004E+09 | 0.205559E+09 |
| April | 0.331066E+09 | 0.126322E+09 | 0.204744E+09 | 0.345941E+09 | 0.159155E+09 |
| May | 0.441268E+09 | 0.179466E+09 | 0.261802E+09 | 0.494556E+09 | 0.140986E+09 |
| June | 0.410564E+09 | 0.159434E+09 | 0.251130E+09 | 0.465169E+09 | 0.109326E+09 |
| July | 0.525018E+09 | 0.276382E+09 | 0.248636E+09 | 0.643671E+09 | 0.104315E+09 |
| August | 0.433403E+09 | 0.221070E+09 | 0.212333E+09 | 0.536063E+09 | 0.103521E+09 |
| September | 0.342828E+09 | 0.164932E+09 | 0.177895E+09 | 0.389174E+09 | 0.145523E+09 |
| October | 0.201743E+09 | 82533136.91 | 0.119209E+09 | 0.185447E+09 | 0.197015E+09 |
| November | 97144609.54 | 27672977.77 | 69471631.78 | 56282475.77 | 0.230232E+09 |
| December | 85164584.22 | 29873663.51 | 55290920.71 | 47313118.32 | 0.303119E+09 |
| Annual Sum or Average | 0.332812E+10 | 0.142439E+10 | 0.190373E+10 | 0.350537E+10 | 0.223448E+10 |
| Minimum of Months | 85164584.22 | 26738428.29 | 55290920.71 | 39427433.34 | 0.103521E+09 |
| Maximum of Months | 0.525018E+09 | 0.276382E+09 | 0.261802E+09 | 0.643671E+09 | 0.303119E+09 |
Report: WindowEnergyReportMonthly
For: GWINDOW1 W NWA
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 90052656.22 | 26738428.29 | 63314227.93 | 40686993.04 | 0.298505E+09 |
| February | 0.144505E+09 | 53823828.75 | 90681094.50 | 0.107485E+09 | 0.228581E+09 |
| March | 0.225360E+09 | 76140086.25 | 0.149220E+09 | 0.204111E+09 | 0.198861E+09 |
| April | 0.331066E+09 | 0.126322E+09 | 0.204744E+09 | 0.354414E+09 | 0.152052E+09 |
| May | 0.441268E+09 | 0.179466E+09 | 0.261802E+09 | 0.502940E+09 | 0.134056E+09 |
| June | 0.410564E+09 | 0.159434E+09 | 0.251130E+09 | 0.470017E+09 | 0.106000E+09 |
| July | 0.525018E+09 | 0.276382E+09 | 0.248636E+09 | 0.647002E+09 | 0.102627E+09 |
| August | 0.433403E+09 | 0.221070E+09 | 0.212333E+09 | 0.540189E+09 | 0.101130E+09 |
| September | 0.342828E+09 | 0.164932E+09 | 0.177895E+09 | 0.395691E+09 | 0.138779E+09 |
| October | 0.201743E+09 | 82533136.91 | 0.119209E+09 | 0.195154E+09 | 0.181846E+09 |
| November | 97144609.54 | 27672977.77 | 69471631.78 | 58898762.55 | 0.224211E+09 |
| December | 85164584.22 | 29873663.51 | 55290920.71 | 49055836.53 | 0.298380E+09 |
| Annual Sum or Average | 0.332812E+10 | 0.142439E+10 | 0.190373E+10 | 0.356565E+10 | 0.216503E+10 |
| Minimum of Months | 85164584.22 | 26738428.29 | 55290920.71 | 40686993.04 | 0.101130E+09 |
| Maximum of Months | 0.525018E+09 | 0.276382E+09 | 0.261802E+09 | 0.647002E+09 | 0.298505E+09 |
Report: WindowEnergyReportMonthly
For: GWINDOW1 N NWA
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 80398594.49 | 0.00 | 80398594.49 | 3854531.71 | 0.474617E+09 |
| February | 0.112996E+09 | 0.00 | 0.112996E+09 | 28109796.20 | 0.365013E+09 |
| March | 0.184345E+09 | 3676.65 | 0.184341E+09 | 96837611.81 | 0.310638E+09 |
| April | 0.252834E+09 | 1224735.97 | 0.251609E+09 | 0.194370E+09 | 0.229460E+09 |
| May | 0.335468E+09 | 9808992.16 | 0.325659E+09 | 0.301320E+09 | 0.197289E+09 |
| June | 0.341516E+09 | 22472037.20 | 0.319044E+09 | 0.322929E+09 | 0.152687E+09 |
| July | 0.335695E+09 | 26421681.49 | 0.309274E+09 | 0.344624E+09 | 0.147281E+09 |
| August | 0.272693E+09 | 8316268.31 | 0.264376E+09 | 0.283724E+09 | 0.145806E+09 |
| September | 0.204209E+09 | 132190.44 | 0.204077E+09 | 0.161863E+09 | 0.214507E+09 |
| October | 0.144505E+09 | 0.00 | 0.144505E+09 | 77367236.50 | 0.282531E+09 |
| November | 88087644.44 | 0.00 | 88087644.44 | 17139298.13 | 0.352804E+09 |
| December | 68318055.64 | 0.00 | 68318055.64 | 2049971.02 | 0.468884E+09 |
| Annual Sum or Average | 0.242106E+10 | 68379582.23 | 0.235269E+10 | 0.183419E+10 | 0.334152E+10 |
| Minimum of Months | 68318055.64 | 0.00 | 68318055.64 | 2049971.02 | 0.145806E+09 |
| Maximum of Months | 0.341516E+09 | 26421681.49 | 0.325659E+09 | 0.344624E+09 | 0.474617E+09 |
Report: WindowEnergyReportMonthly
For: GWINDOW1 S SEA
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.356115E+09 | 0.211787E+09 | 0.144327E+09 | 0.333284E+09 | 0.371481E+09 |
| February | 0.500446E+09 | 0.312463E+09 | 0.187983E+09 | 0.528589E+09 | 0.306082E+09 |
| March | 0.579159E+09 | 0.304880E+09 | 0.274279E+09 | 0.629829E+09 | 0.304100E+09 |
| April | 0.601691E+09 | 0.261958E+09 | 0.339733E+09 | 0.687017E+09 | 0.254489E+09 |
| May | 0.571336E+09 | 0.173034E+09 | 0.398303E+09 | 0.649128E+09 | 0.237440E+09 |
| June | 0.504391E+09 | 0.136950E+09 | 0.367441E+09 | 0.574054E+09 | 0.193010E+09 |
| July | 0.569545E+09 | 0.210801E+09 | 0.358744E+09 | 0.705722E+09 | 0.190498E+09 |
| August | 0.601744E+09 | 0.277187E+09 | 0.324557E+09 | 0.767074E+09 | 0.193957E+09 |
| September | 0.646105E+09 | 0.354088E+09 | 0.292017E+09 | 0.779285E+09 | 0.247381E+09 |
| October | 0.595727E+09 | 0.362163E+09 | 0.233564E+09 | 0.666410E+09 | 0.310922E+09 |
| November | 0.348015E+09 | 0.198875E+09 | 0.149140E+09 | 0.338498E+09 | 0.326558E+09 |
| December | 0.375617E+09 | 0.242303E+09 | 0.133314E+09 | 0.377851E+09 | 0.393142E+09 |
| Annual Sum or Average | 0.624989E+10 | 0.304649E+10 | 0.320340E+10 | 0.703674E+10 | 0.332906E+10 |
| Minimum of Months | 0.348015E+09 | 0.136950E+09 | 0.133314E+09 | 0.333284E+09 | 0.190498E+09 |
| Maximum of Months | 0.646105E+09 | 0.362163E+09 | 0.398303E+09 | 0.779285E+09 | 0.393142E+09 |
Report: WindowEnergyReportMonthly
For: GWINDOW1 E SEA
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 84573088.28 | 21176855.29 | 63396233.00 | 35108268.37 | 0.258743E+09 |
| February | 0.140068E+09 | 49179775.95 | 90887815.83 | 0.100171E+09 | 0.209195E+09 |
| March | 0.233043E+09 | 84128155.90 | 0.148915E+09 | 0.205756E+09 | 0.197701E+09 |
| April | 0.349779E+09 | 0.145490E+09 | 0.204289E+09 | 0.364622E+09 | 0.156604E+09 |
| May | 0.384372E+09 | 0.133839E+09 | 0.250533E+09 | 0.410816E+09 | 0.147244E+09 |
| June | 0.445336E+09 | 0.193882E+09 | 0.251454E+09 | 0.502479E+09 | 0.117545E+09 |
| July | 0.429534E+09 | 0.193393E+09 | 0.236141E+09 | 0.497676E+09 | 0.113537E+09 |
| August | 0.420291E+09 | 0.209870E+09 | 0.210421E+09 | 0.500204E+09 | 0.117256E+09 |
| September | 0.301475E+09 | 0.139116E+09 | 0.162359E+09 | 0.319627E+09 | 0.157840E+09 |
| October | 0.204507E+09 | 87733384.55 | 0.116774E+09 | 0.182971E+09 | 0.205428E+09 |
| November | 96532611.88 | 27335106.39 | 69197505.49 | 53918305.24 | 0.223011E+09 |
| December | 81522159.70 | 26125280.48 | 55396879.22 | 41112984.87 | 0.270931E+09 |
| Annual Sum or Average | 0.317103E+10 | 0.131127E+10 | 0.185977E+10 | 0.321446E+10 | 0.217503E+10 |
| Minimum of Months | 81522159.70 | 21176855.29 | 55396879.22 | 35108268.37 | 0.113537E+09 |
| Maximum of Months | 0.445336E+09 | 0.209870E+09 | 0.251454E+09 | 0.502479E+09 | 0.270931E+09 |
Report: WindowEnergyReportMonthly
For: GWINDOW1 E NEA
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 84573088.28 | 21176855.29 | 63396233.00 | 31006011.85 | 0.296305E+09 |
| February | 0.140068E+09 | 49179775.95 | 90887815.83 | 96146582.85 | 0.224697E+09 |
| March | 0.233043E+09 | 84128155.90 | 0.148915E+09 | 0.208921E+09 | 0.193350E+09 |
| April | 0.349779E+09 | 0.145490E+09 | 0.204289E+09 | 0.375731E+09 | 0.144517E+09 |
| May | 0.384372E+09 | 0.133839E+09 | 0.250533E+09 | 0.426349E+09 | 0.128934E+09 |
| June | 0.445336E+09 | 0.193882E+09 | 0.251454E+09 | 0.515605E+09 | 0.102461E+09 |
| July | 0.429534E+09 | 0.193393E+09 | 0.236141E+09 | 0.513800E+09 | 95501200.37 |
| August | 0.420291E+09 | 0.209870E+09 | 0.210421E+09 | 0.517099E+09 | 94649138.37 |
| September | 0.301475E+09 | 0.139116E+09 | 0.162359E+09 | 0.333746E+09 | 0.133359E+09 |
| October | 0.204507E+09 | 87733384.55 | 0.116774E+09 | 0.195974E+09 | 0.176825E+09 |
| November | 96532611.88 | 27335106.39 | 69197505.49 | 55456163.18 | 0.222642E+09 |
| December | 81522159.70 | 26125280.48 | 55396879.22 | 38918716.49 | 0.294749E+09 |
| Annual Sum or Average | 0.317103E+10 | 0.131127E+10 | 0.185977E+10 | 0.330875E+10 | 0.210799E+10 |
| Minimum of Months | 81522159.70 | 21176855.29 | 55396879.22 | 31006011.85 | 94649138.37 |
| Maximum of Months | 0.445336E+09 | 0.209870E+09 | 0.251454E+09 | 0.517099E+09 | 0.296305E+09 |
Report: WindowEnergyReportMonthly
For: GWINDOW1 N NEA
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 80398594.49 | 0.00 | 80398594.49 | 3825381.96 | 0.474481E+09 |
| February | 0.112996E+09 | 0.00 | 0.112996E+09 | 28020011.05 | 0.364766E+09 |
| March | 0.184345E+09 | 3676.65 | 0.184341E+09 | 96343954.02 | 0.310061E+09 |
| April | 0.252834E+09 | 1224735.97 | 0.251609E+09 | 0.192887E+09 | 0.229087E+09 |
| May | 0.335468E+09 | 9808992.16 | 0.325659E+09 | 0.301041E+09 | 0.195162E+09 |
| June | 0.341516E+09 | 22472037.20 | 0.319044E+09 | 0.319592E+09 | 0.152926E+09 |
| July | 0.335695E+09 | 26421681.49 | 0.309274E+09 | 0.345085E+09 | 0.145034E+09 |
| August | 0.272693E+09 | 8316268.31 | 0.264376E+09 | 0.282558E+09 | 0.144864E+09 |
| September | 0.204209E+09 | 132190.44 | 0.204077E+09 | 0.161607E+09 | 0.212032E+09 |
| October | 0.144505E+09 | 0.00 | 0.144505E+09 | 76774864.33 | 0.281295E+09 |
| November | 88087644.44 | 0.00 | 88087644.44 | 17005251.15 | 0.352589E+09 |
| December | 68318055.64 | 0.00 | 68318055.64 | 2015582.90 | 0.468726E+09 |
| Annual Sum or Average | 0.242106E+10 | 68379582.23 | 0.235269E+10 | 0.182676E+10 | 0.333102E+10 |
| Minimum of Months | 68318055.64 | 0.00 | 68318055.64 | 2015582.90 | 0.144864E+09 |
| Maximum of Months | 0.341516E+09 | 26421681.49 | 0.325659E+09 | 0.345085E+09 | 0.474481E+09 |
Report: WindowEnergyReportMonthly
For: GWINDOW1 N N1A
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 80398594.49 | 0.00 | 80398594.49 | 3459660.93 | 0.484662E+09 |
| February | 0.112996E+09 | 0.00 | 0.112996E+09 | 26886260.52 | 0.372470E+09 |
| March | 0.184345E+09 | 3676.65 | 0.184341E+09 | 94784922.47 | 0.317239E+09 |
| April | 0.252834E+09 | 1224735.97 | 0.251609E+09 | 0.192726E+09 | 0.233713E+09 |
| May | 0.335468E+09 | 9808992.16 | 0.325659E+09 | 0.298367E+09 | 0.202687E+09 |
| June | 0.341516E+09 | 22472037.20 | 0.319044E+09 | 0.320436E+09 | 0.156510E+09 |
| July | 0.335695E+09 | 26421681.49 | 0.309274E+09 | 0.346256E+09 | 0.147708E+09 |
| August | 0.272693E+09 | 8316268.31 | 0.264376E+09 | 0.284853E+09 | 0.146453E+09 |
| September | 0.204209E+09 | 132190.44 | 0.204077E+09 | 0.160520E+09 | 0.219044E+09 |
| October | 0.144505E+09 | 0.00 | 0.144505E+09 | 74674586.91 | 0.291121E+09 |
| November | 88087644.44 | 0.00 | 88087644.44 | 15992418.15 | 0.361459E+09 |
| December | 68318055.64 | 0.00 | 68318055.64 | 1803309.37 | 0.478371E+09 |
| Annual Sum or Average | 0.242106E+10 | 68379582.23 | 0.235269E+10 | 0.182076E+10 | 0.341144E+10 |
| Minimum of Months | 68318055.64 | 0.00 | 68318055.64 | 1803309.37 | 0.146453E+09 |
| Maximum of Months | 0.341516E+09 | 26421681.49 | 0.325659E+09 | 0.346256E+09 | 0.484662E+09 |
Report: WindowEnergyReportMonthly
For: GWINDOW1 N N2A
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 80398594.49 | 0.00 | 80398594.49 | 3458743.57 | 0.484656E+09 |
| February | 0.112996E+09 | 0.00 | 0.112996E+09 | 26882861.08 | 0.372458E+09 |
| March | 0.184345E+09 | 3676.65 | 0.184341E+09 | 94768822.00 | 0.317197E+09 |
| April | 0.252834E+09 | 1224735.97 | 0.251609E+09 | 0.192624E+09 | 0.233733E+09 |
| May | 0.335468E+09 | 9808992.16 | 0.325659E+09 | 0.298432E+09 | 0.202498E+09 |
| June | 0.341516E+09 | 22472037.20 | 0.319044E+09 | 0.320167E+09 | 0.156643E+09 |
| July | 0.335695E+09 | 26421681.49 | 0.309274E+09 | 0.346326E+09 | 0.147576E+09 |
| August | 0.272693E+09 | 8316268.31 | 0.264376E+09 | 0.284811E+09 | 0.146415E+09 |
| September | 0.204209E+09 | 132190.44 | 0.204077E+09 | 0.160559E+09 | 0.218834E+09 |
| October | 0.144505E+09 | 0.00 | 0.144505E+09 | 74699640.47 | 0.290969E+09 |
| November | 88087644.44 | 0.00 | 88087644.44 | 15987595.37 | 0.361443E+09 |
| December | 68318055.64 | 0.00 | 68318055.64 | 1802281.83 | 0.478362E+09 |
| Annual Sum or Average | 0.242106E+10 | 68379582.23 | 0.235269E+10 | 0.182052E+10 | 0.341078E+10 |
| Minimum of Months | 68318055.64 | 0.00 | 68318055.64 | 1802281.83 | 0.146415E+09 |
| Maximum of Months | 0.341516E+09 | 26421681.49 | 0.325659E+09 | 0.346326E+09 | 0.484656E+09 |
Report: WindowEnergyReportMonthly
For: GWINDOW1 S S1A
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.356115E+09 | 0.211787E+09 | 0.144327E+09 | 0.317132E+09 | 0.438314E+09 |
| February | 0.500446E+09 | 0.312463E+09 | 0.187983E+09 | 0.513375E+09 | 0.344796E+09 |
| March | 0.579159E+09 | 0.304880E+09 | 0.274279E+09 | 0.623332E+09 | 0.319213E+09 |
| April | 0.601691E+09 | 0.261958E+09 | 0.339733E+09 | 0.688972E+09 | 0.254642E+09 |
| May | 0.571336E+09 | 0.173034E+09 | 0.398303E+09 | 0.654625E+09 | 0.229721E+09 |
| June | 0.504391E+09 | 0.136950E+09 | 0.367441E+09 | 0.585931E+09 | 0.177525E+09 |
| July | 0.569545E+09 | 0.210801E+09 | 0.358744E+09 | 0.723914E+09 | 0.165717E+09 |
| August | 0.601744E+09 | 0.277187E+09 | 0.324557E+09 | 0.785427E+09 | 0.161664E+09 |
| September | 0.646105E+09 | 0.354088E+09 | 0.292017E+09 | 0.788869E+09 | 0.225759E+09 |
| October | 0.595727E+09 | 0.362163E+09 | 0.233564E+09 | 0.667336E+09 | 0.306861E+09 |
| November | 0.348015E+09 | 0.198875E+09 | 0.149140E+09 | 0.333206E+09 | 0.345764E+09 |
| December | 0.375617E+09 | 0.242303E+09 | 0.133314E+09 | 0.366972E+09 | 0.444172E+09 |
| Annual Sum or Average | 0.624989E+10 | 0.304649E+10 | 0.320340E+10 | 0.704909E+10 | 0.341415E+10 |
| Minimum of Months | 0.348015E+09 | 0.136950E+09 | 0.133314E+09 | 0.317132E+09 | 0.161664E+09 |
| Maximum of Months | 0.646105E+09 | 0.362163E+09 | 0.398303E+09 | 0.788869E+09 | 0.444172E+09 |
Report: WindowEnergyReportMonthly
For: GWINDOW1 S S2A
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.356115E+09 | 0.211787E+09 | 0.144327E+09 | 0.317844E+09 | 0.435547E+09 |
| February | 0.500446E+09 | 0.312463E+09 | 0.187983E+09 | 0.514068E+09 | 0.343143E+09 |
| March | 0.579159E+09 | 0.304880E+09 | 0.274279E+09 | 0.623332E+09 | 0.318943E+09 |
| April | 0.601691E+09 | 0.261958E+09 | 0.339733E+09 | 0.688144E+09 | 0.255470E+09 |
| May | 0.571336E+09 | 0.173034E+09 | 0.398303E+09 | 0.653072E+09 | 0.231479E+09 |
| June | 0.504391E+09 | 0.136950E+09 | 0.367441E+09 | 0.584506E+09 | 0.178926E+09 |
| July | 0.569545E+09 | 0.210801E+09 | 0.358744E+09 | 0.722932E+09 | 0.166680E+09 |
| August | 0.601744E+09 | 0.277187E+09 | 0.324557E+09 | 0.784311E+09 | 0.162923E+09 |
| September | 0.646105E+09 | 0.354088E+09 | 0.292017E+09 | 0.788039E+09 | 0.226941E+09 |
| October | 0.595727E+09 | 0.362163E+09 | 0.233564E+09 | 0.666324E+09 | 0.308919E+09 |
| November | 0.348015E+09 | 0.198875E+09 | 0.149140E+09 | 0.333002E+09 | 0.345879E+09 |
| December | 0.375617E+09 | 0.242303E+09 | 0.133314E+09 | 0.367453E+09 | 0.442141E+09 |
| Annual Sum or Average | 0.624989E+10 | 0.304649E+10 | 0.320340E+10 | 0.704303E+10 | 0.341699E+10 |
| Minimum of Months | 0.348015E+09 | 0.136950E+09 | 0.133314E+09 | 0.317844E+09 | 0.162923E+09 |
| Maximum of Months | 0.646105E+09 | 0.362163E+09 | 0.398303E+09 | 0.788039E+09 | 0.442141E+09 |
Report: WindowEnergyReportMonthly
For: MWINDOW1 S SWA
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.356115E+09 | 0.211787E+09 | 0.144327E+09 | 0.312782E+09 | 0.448383E+09 |
| February | 0.500446E+09 | 0.312463E+09 | 0.187983E+09 | 0.504906E+09 | 0.357025E+09 |
| March | 0.579159E+09 | 0.304880E+09 | 0.274279E+09 | 0.609423E+09 | 0.341357E+09 |
| April | 0.601691E+09 | 0.261958E+09 | 0.339733E+09 | 0.667442E+09 | 0.282471E+09 |
| May | 0.571336E+09 | 0.173034E+09 | 0.398303E+09 | 0.636739E+09 | 0.247384E+09 |
| June | 0.504391E+09 | 0.136950E+09 | 0.367441E+09 | 0.574070E+09 | 0.186316E+09 |
| July | 0.569545E+09 | 0.210801E+09 | 0.358744E+09 | 0.714845E+09 | 0.170757E+09 |
| August | 0.601744E+09 | 0.277187E+09 | 0.324557E+09 | 0.778618E+09 | 0.164716E+09 |
| September | 0.646105E+09 | 0.354088E+09 | 0.292017E+09 | 0.783695E+09 | 0.228531E+09 |
| October | 0.595727E+09 | 0.362163E+09 | 0.233564E+09 | 0.662872E+09 | 0.309340E+09 |
| November | 0.348015E+09 | 0.198875E+09 | 0.149140E+09 | 0.330217E+09 | 0.349958E+09 |
| December | 0.375617E+09 | 0.242303E+09 | 0.133314E+09 | 0.363074E+09 | 0.451900E+09 |
| Annual Sum or Average | 0.624989E+10 | 0.304649E+10 | 0.320340E+10 | 0.693868E+10 | 0.353814E+10 |
| Minimum of Months | 0.348015E+09 | 0.136950E+09 | 0.133314E+09 | 0.312782E+09 | 0.164716E+09 |
| Maximum of Months | 0.646105E+09 | 0.362163E+09 | 0.398303E+09 | 0.783695E+09 | 0.451900E+09 |
Report: WindowEnergyReportMonthly
For: MWINDOW1 W SWA
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 90052656.22 | 26738428.29 | 63314227.93 | 37112279.28 | 0.316817E+09 |
| February | 0.144505E+09 | 53823828.75 | 90681094.50 | 98305637.06 | 0.248518E+09 |
| March | 0.225360E+09 | 76140086.25 | 0.149220E+09 | 0.186392E+09 | 0.226143E+09 |
| April | 0.331066E+09 | 0.126322E+09 | 0.204744E+09 | 0.328088E+09 | 0.181557E+09 |
| May | 0.441268E+09 | 0.179466E+09 | 0.261802E+09 | 0.478132E+09 | 0.157483E+09 |
| June | 0.410564E+09 | 0.159434E+09 | 0.251130E+09 | 0.454844E+09 | 0.117656E+09 |
| July | 0.525018E+09 | 0.276382E+09 | 0.248636E+09 | 0.637832E+09 | 0.107551E+09 |
| August | 0.433403E+09 | 0.221070E+09 | 0.212333E+09 | 0.531886E+09 | 0.105895E+09 |
| September | 0.342828E+09 | 0.164932E+09 | 0.177895E+09 | 0.384941E+09 | 0.149893E+09 |
| October | 0.201743E+09 | 82533136.91 | 0.119209E+09 | 0.179792E+09 | 0.208649E+09 |
| November | 97144609.54 | 27672977.77 | 69471631.78 | 53359195.40 | 0.240868E+09 |
| December | 85164584.22 | 29873663.51 | 55290920.71 | 45258050.85 | 0.316099E+09 |
| Annual Sum or Average | 0.332812E+10 | 0.142439E+10 | 0.190373E+10 | 0.341594E+10 | 0.237713E+10 |
| Minimum of Months | 85164584.22 | 26738428.29 | 55290920.71 | 37112279.28 | 0.105895E+09 |
| Maximum of Months | 0.525018E+09 | 0.276382E+09 | 0.261802E+09 | 0.637832E+09 | 0.316817E+09 |
Report: WindowEnergyReportMonthly
For: MWINDOW1 W NWA
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 90052656.22 | 26738428.29 | 63314227.93 | 38716512.26 | 0.312661E+09 |
| February | 0.144505E+09 | 53823828.75 | 90681094.50 | 0.102820E+09 | 0.241393E+09 |
| March | 0.225360E+09 | 76140086.25 | 0.149220E+09 | 0.195435E+09 | 0.214280E+09 |
| April | 0.331066E+09 | 0.126322E+09 | 0.204744E+09 | 0.338022E+09 | 0.171723E+09 |
| May | 0.441268E+09 | 0.179466E+09 | 0.261802E+09 | 0.482032E+09 | 0.155124E+09 |
| June | 0.410564E+09 | 0.159434E+09 | 0.251130E+09 | 0.457062E+09 | 0.116876E+09 |
| July | 0.525018E+09 | 0.276382E+09 | 0.248636E+09 | 0.640412E+09 | 0.106768E+09 |
| August | 0.433403E+09 | 0.221070E+09 | 0.212333E+09 | 0.535208E+09 | 0.104581E+09 |
| September | 0.342828E+09 | 0.164932E+09 | 0.177895E+09 | 0.389521E+09 | 0.146673E+09 |
| October | 0.201743E+09 | 82533136.91 | 0.119209E+09 | 0.188468E+09 | 0.194737E+09 |
| November | 97144609.54 | 27672977.77 | 69471631.78 | 56407936.97 | 0.234279E+09 |
| December | 85164584.22 | 29873663.51 | 55290920.71 | 47650908.36 | 0.310275E+09 |
| Annual Sum or Average | 0.332812E+10 | 0.142439E+10 | 0.190373E+10 | 0.347176E+10 | 0.230937E+10 |
| Minimum of Months | 85164584.22 | 26738428.29 | 55290920.71 | 38716512.26 | 0.104581E+09 |
| Maximum of Months | 0.525018E+09 | 0.276382E+09 | 0.261802E+09 | 0.640412E+09 | 0.312661E+09 |
Report: WindowEnergyReportMonthly
For: MWINDOW1 N NWA
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 80398594.49 | 0.00 | 80398594.49 | 2951706.50 | 0.496838E+09 |
| February | 0.112996E+09 | 0.00 | 0.112996E+09 | 23827680.10 | 0.386369E+09 |
| March | 0.184345E+09 | 3676.65 | 0.184341E+09 | 86729895.95 | 0.335835E+09 |
| April | 0.252834E+09 | 1224735.97 | 0.251609E+09 | 0.173169E+09 | 0.260104E+09 |
| May | 0.335468E+09 | 9808992.16 | 0.325659E+09 | 0.271132E+09 | 0.228078E+09 |
| June | 0.341516E+09 | 22472037.20 | 0.319044E+09 | 0.303800E+09 | 0.167595E+09 |
| July | 0.335695E+09 | 26421681.49 | 0.309274E+09 | 0.336389E+09 | 0.152986E+09 |
| August | 0.272693E+09 | 8316268.31 | 0.264376E+09 | 0.277810E+09 | 0.150590E+09 |
| September | 0.204209E+09 | 132190.44 | 0.204077E+09 | 0.154172E+09 | 0.226878E+09 |
| October | 0.144505E+09 | 0.00 | 0.144505E+09 | 69692734.63 | 0.302872E+09 |
| November | 88087644.44 | 0.00 | 88087644.44 | 14725448.28 | 0.368544E+09 |
| December | 68318055.64 | 0.00 | 68318055.64 | 1513092.35 | 0.487576E+09 |
| Annual Sum or Average | 0.242106E+10 | 68379582.23 | 0.235269E+10 | 0.171591E+10 | 0.356426E+10 |
| Minimum of Months | 68318055.64 | 0.00 | 68318055.64 | 1513092.35 | 0.150590E+09 |
| Maximum of Months | 0.341516E+09 | 26421681.49 | 0.325659E+09 | 0.336389E+09 | 0.496838E+09 |
Report: WindowEnergyReportMonthly
For: MWINDOW1 S SEA
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.356115E+09 | 0.211787E+09 | 0.144327E+09 | 0.312668E+09 | 0.448044E+09 |
| February | 0.500446E+09 | 0.312463E+09 | 0.187983E+09 | 0.504393E+09 | 0.356249E+09 |
| March | 0.579159E+09 | 0.304880E+09 | 0.274279E+09 | 0.607800E+09 | 0.340582E+09 |
| April | 0.601691E+09 | 0.261958E+09 | 0.339733E+09 | 0.664215E+09 | 0.283014E+09 |
| May | 0.571336E+09 | 0.173034E+09 | 0.398303E+09 | 0.636114E+09 | 0.245799E+09 |
| June | 0.504391E+09 | 0.136950E+09 | 0.367441E+09 | 0.572429E+09 | 0.185733E+09 |
| July | 0.569545E+09 | 0.210801E+09 | 0.358744E+09 | 0.714660E+09 | 0.169064E+09 |
| August | 0.601744E+09 | 0.277187E+09 | 0.324557E+09 | 0.777701E+09 | 0.163760E+09 |
| September | 0.646105E+09 | 0.354088E+09 | 0.292017E+09 | 0.783332E+09 | 0.227044E+09 |
| October | 0.595727E+09 | 0.362163E+09 | 0.233564E+09 | 0.661811E+09 | 0.308784E+09 |
| November | 0.348015E+09 | 0.198875E+09 | 0.149140E+09 | 0.329787E+09 | 0.349702E+09 |
| December | 0.375617E+09 | 0.242303E+09 | 0.133314E+09 | 0.362829E+09 | 0.451396E+09 |
| Annual Sum or Average | 0.624989E+10 | 0.304649E+10 | 0.320340E+10 | 0.692774E+10 | 0.352917E+10 |
| Minimum of Months | 0.348015E+09 | 0.136950E+09 | 0.133314E+09 | 0.312668E+09 | 0.163760E+09 |
| Maximum of Months | 0.646105E+09 | 0.362163E+09 | 0.398303E+09 | 0.783332E+09 | 0.451396E+09 |
Report: WindowEnergyReportMonthly
For: MWINDOW1 E SEA
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 84573088.28 | 21176855.29 | 63396233.00 | 28414208.18 | 0.315402E+09 |
| February | 0.140068E+09 | 49179775.95 | 90887815.83 | 88343426.79 | 0.246208E+09 |
| March | 0.233043E+09 | 84128155.90 | 0.148915E+09 | 0.191556E+09 | 0.221677E+09 |
| April | 0.349779E+09 | 0.145490E+09 | 0.204289E+09 | 0.348834E+09 | 0.173613E+09 |
| May | 0.384372E+09 | 0.133839E+09 | 0.250533E+09 | 0.401970E+09 | 0.151986E+09 |
| June | 0.445336E+09 | 0.193882E+09 | 0.251454E+09 | 0.501461E+09 | 0.112823E+09 |
| July | 0.429534E+09 | 0.193393E+09 | 0.236141E+09 | 0.504925E+09 | 0.100737E+09 |
| August | 0.420291E+09 | 0.209870E+09 | 0.210421E+09 | 0.509091E+09 | 99089657.22 |
| September | 0.301475E+09 | 0.139116E+09 | 0.162359E+09 | 0.322804E+09 | 0.144864E+09 |
| October | 0.204507E+09 | 87733384.55 | 0.116774E+09 | 0.180579E+09 | 0.204023E+09 |
| November | 96532611.88 | 27335106.39 | 69197505.49 | 50369198.28 | 0.240296E+09 |
| December | 81522159.70 | 26125280.48 | 55396879.22 | 36018597.55 | 0.313738E+09 |
| Annual Sum or Average | 0.317103E+10 | 0.131127E+10 | 0.185977E+10 | 0.316437E+10 | 0.232446E+10 |
| Minimum of Months | 81522159.70 | 21176855.29 | 55396879.22 | 28414208.18 | 99089657.22 |
| Maximum of Months | 0.445336E+09 | 0.209870E+09 | 0.251454E+09 | 0.509091E+09 | 0.315402E+09 |
Report: WindowEnergyReportMonthly
For: MWINDOW1 E NEA
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 84573088.28 | 21176855.29 | 63396233.00 | 29199593.49 | 0.310546E+09 |
| February | 0.140068E+09 | 49179775.95 | 90887815.83 | 91466777.35 | 0.237647E+09 |
| March | 0.233043E+09 | 84128155.90 | 0.148915E+09 | 0.200192E+09 | 0.208714E+09 |
| April | 0.349779E+09 | 0.145490E+09 | 0.204289E+09 | 0.358419E+09 | 0.163778E+09 |
| May | 0.384372E+09 | 0.133839E+09 | 0.250533E+09 | 0.405621E+09 | 0.149640E+09 |
| June | 0.445336E+09 | 0.193882E+09 | 0.251454E+09 | 0.503495E+09 | 0.112040E+09 |
| July | 0.429534E+09 | 0.193393E+09 | 0.236141E+09 | 0.507464E+09 | 99867361.59 |
| August | 0.420291E+09 | 0.209870E+09 | 0.210421E+09 | 0.512339E+09 | 97742344.03 |
| September | 0.301475E+09 | 0.139116E+09 | 0.162359E+09 | 0.327397E+09 | 0.141382E+09 |
| October | 0.204507E+09 | 87733384.55 | 0.116774E+09 | 0.188840E+09 | 0.189709E+09 |
| November | 96532611.88 | 27335106.39 | 69197505.49 | 52849736.23 | 0.232900E+09 |
| December | 81522159.70 | 26125280.48 | 55396879.22 | 37337070.86 | 0.306766E+09 |
| Annual Sum or Average | 0.317103E+10 | 0.131127E+10 | 0.185977E+10 | 0.321462E+10 | 0.225073E+10 |
| Minimum of Months | 81522159.70 | 21176855.29 | 55396879.22 | 29199593.49 | 97742344.03 |
| Maximum of Months | 0.445336E+09 | 0.209870E+09 | 0.251454E+09 | 0.512339E+09 | 0.310546E+09 |
Report: WindowEnergyReportMonthly
For: MWINDOW1 N NEA
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 80398594.49 | 0.00 | 80398594.49 | 2921327.15 | 0.496704E+09 |
| February | 0.112996E+09 | 0.00 | 0.112996E+09 | 23686772.41 | 0.386021E+09 |
| March | 0.184345E+09 | 3676.65 | 0.184341E+09 | 85854084.93 | 0.334688E+09 |
| April | 0.252834E+09 | 1224735.97 | 0.251609E+09 | 0.169896E+09 | 0.260622E+09 |
| May | 0.335468E+09 | 9808992.16 | 0.325659E+09 | 0.270176E+09 | 0.226576E+09 |
| June | 0.341516E+09 | 22472037.20 | 0.319044E+09 | 0.301825E+09 | 0.167027E+09 |
| July | 0.335695E+09 | 26421681.49 | 0.309274E+09 | 0.336317E+09 | 0.151483E+09 |
| August | 0.272693E+09 | 8316268.31 | 0.264376E+09 | 0.276741E+09 | 0.149651E+09 |
| September | 0.204209E+09 | 132190.44 | 0.204077E+09 | 0.153702E+09 | 0.225039E+09 |
| October | 0.144505E+09 | 0.00 | 0.144505E+09 | 68473086.80 | 0.302105E+09 |
| November | 88087644.44 | 0.00 | 88087644.44 | 14540431.98 | 0.368292E+09 |
| December | 68318055.64 | 0.00 | 68318055.64 | 1478874.55 | 0.487407E+09 |
| Annual Sum or Average | 0.242106E+10 | 68379582.23 | 0.235269E+10 | 0.170561E+10 | 0.355561E+10 |
| Minimum of Months | 68318055.64 | 0.00 | 68318055.64 | 1478874.55 | 0.149651E+09 |
| Maximum of Months | 0.341516E+09 | 26421681.49 | 0.325659E+09 | 0.336317E+09 | 0.496704E+09 |
Report: WindowEnergyReportMonthly
For: MWINDOW1 N N1A
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 80398594.49 | 0.00 | 80398594.49 | 2666214.41 | 0.506631E+09 |
| February | 0.112996E+09 | 0.00 | 0.112996E+09 | 22620242.61 | 0.393811E+09 |
| March | 0.184345E+09 | 3676.65 | 0.184341E+09 | 84865496.98 | 0.342999E+09 |
| April | 0.252834E+09 | 1224735.97 | 0.251609E+09 | 0.170607E+09 | 0.267244E+09 |
| May | 0.335468E+09 | 9808992.16 | 0.325659E+09 | 0.270199E+09 | 0.232287E+09 |
| June | 0.341516E+09 | 22472037.20 | 0.319044E+09 | 0.304832E+09 | 0.168714E+09 |
| July | 0.335695E+09 | 26421681.49 | 0.309274E+09 | 0.340043E+09 | 0.152113E+09 |
| August | 0.272693E+09 | 8316268.31 | 0.264376E+09 | 0.280595E+09 | 0.150012E+09 |
| September | 0.204209E+09 | 132190.44 | 0.204077E+09 | 0.154353E+09 | 0.229342E+09 |
| October | 0.144505E+09 | 0.00 | 0.144505E+09 | 65778158.58 | 0.316697E+09 |
| November | 88087644.44 | 0.00 | 88087644.44 | 13344361.21 | 0.379300E+09 |
| December | 68318055.64 | 0.00 | 68318055.64 | 1318131.38 | 0.497310E+09 |
| Annual Sum or Average | 0.242106E+10 | 68379582.23 | 0.235269E+10 | 0.171122E+10 | 0.363646E+10 |
| Minimum of Months | 68318055.64 | 0.00 | 68318055.64 | 1318131.38 | 0.150012E+09 |
| Maximum of Months | 0.341516E+09 | 26421681.49 | 0.325659E+09 | 0.340043E+09 | 0.506631E+09 |
Report: WindowEnergyReportMonthly
For: MWINDOW1 N N2A
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 80398594.49 | 0.00 | 80398594.49 | 2664984.95 | 0.506621E+09 |
| February | 0.112996E+09 | 0.00 | 0.112996E+09 | 22613631.72 | 0.393793E+09 |
| March | 0.184345E+09 | 3676.65 | 0.184341E+09 | 84830125.85 | 0.342895E+09 |
| April | 0.252834E+09 | 1224735.97 | 0.251609E+09 | 0.170285E+09 | 0.267533E+09 |
| May | 0.335468E+09 | 9808992.16 | 0.325659E+09 | 0.270164E+09 | 0.232200E+09 |
| June | 0.341516E+09 | 22472037.20 | 0.319044E+09 | 0.304758E+09 | 0.168703E+09 |
| July | 0.335695E+09 | 26421681.49 | 0.309274E+09 | 0.340044E+09 | 0.152051E+09 |
| August | 0.272693E+09 | 8316268.31 | 0.264376E+09 | 0.280555E+09 | 0.149977E+09 |
| September | 0.204209E+09 | 132190.44 | 0.204077E+09 | 0.154347E+09 | 0.229235E+09 |
| October | 0.144505E+09 | 0.00 | 0.144505E+09 | 65724277.25 | 0.316692E+09 |
| November | 88087644.44 | 0.00 | 88087644.44 | 13335295.03 | 0.379284E+09 |
| December | 68318055.64 | 0.00 | 68318055.64 | 1316992.01 | 0.497300E+09 |
| Annual Sum or Average | 0.242106E+10 | 68379582.23 | 0.235269E+10 | 0.171064E+10 | 0.363629E+10 |
| Minimum of Months | 68318055.64 | 0.00 | 68318055.64 | 1316992.01 | 0.149977E+09 |
| Maximum of Months | 0.341516E+09 | 26421681.49 | 0.325659E+09 | 0.340044E+09 | 0.506621E+09 |
Report: WindowEnergyReportMonthly
For: MWINDOW1 S S1A
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.356115E+09 | 0.211787E+09 | 0.144327E+09 | 0.310177E+09 | 0.457692E+09 |
| February | 0.500446E+09 | 0.312463E+09 | 0.187983E+09 | 0.500917E+09 | 0.366807E+09 |
| March | 0.579159E+09 | 0.304880E+09 | 0.274279E+09 | 0.603515E+09 | 0.356801E+09 |
| April | 0.601691E+09 | 0.261958E+09 | 0.339733E+09 | 0.662940E+09 | 0.292464E+09 |
| May | 0.571336E+09 | 0.173034E+09 | 0.398303E+09 | 0.636050E+09 | 0.251443E+09 |
| June | 0.504391E+09 | 0.136950E+09 | 0.367441E+09 | 0.575117E+09 | 0.187374E+09 |
| July | 0.569545E+09 | 0.210801E+09 | 0.358744E+09 | 0.717874E+09 | 0.169527E+09 |
| August | 0.601744E+09 | 0.277187E+09 | 0.324557E+09 | 0.780942E+09 | 0.164068E+09 |
| September | 0.646105E+09 | 0.354088E+09 | 0.292017E+09 | 0.783966E+09 | 0.230346E+09 |
| October | 0.595727E+09 | 0.362163E+09 | 0.233564E+09 | 0.657710E+09 | 0.324048E+09 |
| November | 0.348015E+09 | 0.198875E+09 | 0.149140E+09 | 0.326087E+09 | 0.363244E+09 |
| December | 0.375617E+09 | 0.242303E+09 | 0.133314E+09 | 0.360002E+09 | 0.463388E+09 |
| Annual Sum or Average | 0.624989E+10 | 0.304649E+10 | 0.320340E+10 | 0.691530E+10 | 0.362720E+10 |
| Minimum of Months | 0.348015E+09 | 0.136950E+09 | 0.133314E+09 | 0.310177E+09 | 0.164068E+09 |
| Maximum of Months | 0.646105E+09 | 0.362163E+09 | 0.398303E+09 | 0.783966E+09 | 0.463388E+09 |
Report: WindowEnergyReportMonthly
For: MWINDOW1 S S2A
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.356115E+09 | 0.211787E+09 | 0.144327E+09 | 0.310171E+09 | 0.457671E+09 |
| February | 0.500446E+09 | 0.312463E+09 | 0.187983E+09 | 0.500896E+09 | 0.366757E+09 |
| March | 0.579159E+09 | 0.304880E+09 | 0.274279E+09 | 0.603425E+09 | 0.356821E+09 |
| April | 0.601691E+09 | 0.261958E+09 | 0.339733E+09 | 0.662706E+09 | 0.292655E+09 |
| May | 0.571336E+09 | 0.173034E+09 | 0.398303E+09 | 0.636045E+09 | 0.251347E+09 |
| June | 0.504391E+09 | 0.136950E+09 | 0.367441E+09 | 0.575061E+09 | 0.187354E+09 |
| July | 0.569545E+09 | 0.210801E+09 | 0.358744E+09 | 0.717867E+09 | 0.169459E+09 |
| August | 0.601744E+09 | 0.277187E+09 | 0.324557E+09 | 0.780909E+09 | 0.164033E+09 |
| September | 0.646105E+09 | 0.354088E+09 | 0.292017E+09 | 0.783962E+09 | 0.230275E+09 |
| October | 0.595727E+09 | 0.362163E+09 | 0.233564E+09 | 0.657672E+09 | 0.324055E+09 |
| November | 0.348015E+09 | 0.198875E+09 | 0.149140E+09 | 0.326066E+09 | 0.363240E+09 |
| December | 0.375617E+09 | 0.242303E+09 | 0.133314E+09 | 0.359995E+09 | 0.463348E+09 |
| Annual Sum or Average | 0.624989E+10 | 0.304649E+10 | 0.320340E+10 | 0.691478E+10 | 0.362701E+10 |
| Minimum of Months | 0.348015E+09 | 0.136950E+09 | 0.133314E+09 | 0.310171E+09 | 0.164033E+09 |
| Maximum of Months | 0.646105E+09 | 0.362163E+09 | 0.398303E+09 | 0.783962E+09 | 0.463348E+09 |
Report: WindowEnergyReportMonthly
For: TWINDOW1 S SWA
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.356115E+09 | 0.211787E+09 | 0.144327E+09 | 0.314564E+09 | 0.430638E+09 |
| February | 0.500446E+09 | 0.312463E+09 | 0.187983E+09 | 0.505647E+09 | 0.341277E+09 |
| March | 0.579159E+09 | 0.304880E+09 | 0.274279E+09 | 0.610992E+09 | 0.317654E+09 |
| April | 0.601691E+09 | 0.261958E+09 | 0.339733E+09 | 0.671252E+09 | 0.257370E+09 |
| May | 0.571336E+09 | 0.173034E+09 | 0.398303E+09 | 0.642751E+09 | 0.220274E+09 |
| June | 0.504391E+09 | 0.136950E+09 | 0.367441E+09 | 0.575673E+09 | 0.168983E+09 |
| July | 0.569545E+09 | 0.210801E+09 | 0.358744E+09 | 0.710647E+09 | 0.159444E+09 |
| August | 0.601744E+09 | 0.277187E+09 | 0.324557E+09 | 0.775345E+09 | 0.153472E+09 |
| September | 0.646105E+09 | 0.354088E+09 | 0.292017E+09 | 0.788613E+09 | 0.204142E+09 |
| October | 0.595727E+09 | 0.362163E+09 | 0.233564E+09 | 0.671051E+09 | 0.274016E+09 |
| November | 0.348015E+09 | 0.198875E+09 | 0.149140E+09 | 0.333160E+09 | 0.329178E+09 |
| December | 0.375617E+09 | 0.242303E+09 | 0.133314E+09 | 0.364349E+09 | 0.432776E+09 |
| Annual Sum or Average | 0.624989E+10 | 0.304649E+10 | 0.320340E+10 | 0.696404E+10 | 0.328922E+10 |
| Minimum of Months | 0.348015E+09 | 0.136950E+09 | 0.133314E+09 | 0.314564E+09 | 0.153472E+09 |
| Maximum of Months | 0.646105E+09 | 0.362163E+09 | 0.398303E+09 | 0.788613E+09 | 0.432776E+09 |
Report: WindowEnergyReportMonthly
For: TWINDOW1 W SWA
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 90052656.22 | 26738428.29 | 63314227.93 | 37149365.92 | 0.303619E+09 |
| February | 0.144505E+09 | 53823828.75 | 90681094.50 | 97805899.41 | 0.236865E+09 |
| March | 0.225360E+09 | 76140086.25 | 0.149220E+09 | 0.186603E+09 | 0.209479E+09 |
| April | 0.331066E+09 | 0.126322E+09 | 0.204744E+09 | 0.329940E+09 | 0.164270E+09 |
| May | 0.441268E+09 | 0.179466E+09 | 0.261802E+09 | 0.481812E+09 | 0.139386E+09 |
| June | 0.410564E+09 | 0.159434E+09 | 0.251130E+09 | 0.455538E+09 | 0.105992E+09 |
| July | 0.525018E+09 | 0.276382E+09 | 0.248636E+09 | 0.634373E+09 | 99620942.44 |
| August | 0.433403E+09 | 0.221070E+09 | 0.212333E+09 | 0.529272E+09 | 98136095.66 |
| September | 0.342828E+09 | 0.164932E+09 | 0.177895E+09 | 0.387137E+09 | 0.132922E+09 |
| October | 0.201743E+09 | 82533136.91 | 0.119209E+09 | 0.183352E+09 | 0.183349E+09 |
| November | 97144609.54 | 27672977.77 | 69471631.78 | 54200211.17 | 0.225810E+09 |
| December | 85164584.22 | 29873663.51 | 55290920.71 | 44850390.88 | 0.301790E+09 |
| Annual Sum or Average | 0.332812E+10 | 0.142439E+10 | 0.190373E+10 | 0.342203E+10 | 0.220124E+10 |
| Minimum of Months | 85164584.22 | 26738428.29 | 55290920.71 | 37149365.92 | 98136095.66 |
| Maximum of Months | 0.525018E+09 | 0.276382E+09 | 0.261802E+09 | 0.634373E+09 | 0.303619E+09 |
Report: WindowEnergyReportMonthly
For: TWINDOW1 W NWA
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 90052656.22 | 26738428.29 | 63314227.93 | 39518975.46 | 0.300274E+09 |
| February | 0.144505E+09 | 53823828.75 | 90681094.50 | 0.103885E+09 | 0.231273E+09 |
| March | 0.225360E+09 | 76140086.25 | 0.149220E+09 | 0.196321E+09 | 0.203467E+09 |
| April | 0.331066E+09 | 0.126322E+09 | 0.204744E+09 | 0.339214E+09 | 0.159956E+09 |
| May | 0.441268E+09 | 0.179466E+09 | 0.261802E+09 | 0.487451E+09 | 0.137535E+09 |
| June | 0.410564E+09 | 0.159434E+09 | 0.251130E+09 | 0.458921E+09 | 0.105305E+09 |
| July | 0.525018E+09 | 0.276382E+09 | 0.248636E+09 | 0.638158E+09 | 98990622.80 |
| August | 0.433403E+09 | 0.221070E+09 | 0.212333E+09 | 0.534347E+09 | 96814030.69 |
| September | 0.342828E+09 | 0.164932E+09 | 0.177895E+09 | 0.395395E+09 | 0.128476E+09 |
| October | 0.201743E+09 | 82533136.91 | 0.119209E+09 | 0.194391E+09 | 0.174741E+09 |
| November | 97144609.54 | 27672977.77 | 69471631.78 | 57973006.55 | 0.221636E+09 |
| December | 85164584.22 | 29873663.51 | 55290920.71 | 48300019.81 | 0.297298E+09 |
| Annual Sum or Average | 0.332812E+10 | 0.142439E+10 | 0.190373E+10 | 0.349387E+10 | 0.215576E+10 |
| Minimum of Months | 85164584.22 | 26738428.29 | 55290920.71 | 39518975.46 | 96814030.69 |
| Maximum of Months | 0.525018E+09 | 0.276382E+09 | 0.261802E+09 | 0.638158E+09 | 0.300274E+09 |
Report: WindowEnergyReportMonthly
For: TWINDOW1 N NWA
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 80398594.49 | 0.00 | 80398594.49 | 3423863.62 | 0.477407E+09 |
| February | 0.112996E+09 | 0.00 | 0.112996E+09 | 25200925.91 | 0.370906E+09 |
| March | 0.184345E+09 | 3676.65 | 0.184341E+09 | 88581254.75 | 0.319811E+09 |
| April | 0.252834E+09 | 1224735.97 | 0.251609E+09 | 0.176093E+09 | 0.242902E+09 |
| May | 0.335468E+09 | 9808992.16 | 0.325659E+09 | 0.281466E+09 | 0.203175E+09 |
| June | 0.341516E+09 | 22472037.20 | 0.319044E+09 | 0.309547E+09 | 0.152509E+09 |
| July | 0.335695E+09 | 26421681.49 | 0.309274E+09 | 0.335458E+09 | 0.142805E+09 |
| August | 0.272693E+09 | 8316268.31 | 0.264376E+09 | 0.278593E+09 | 0.140217E+09 |
| September | 0.204209E+09 | 132190.44 | 0.204077E+09 | 0.163339E+09 | 0.199280E+09 |
| October | 0.144505E+09 | 0.00 | 0.144505E+09 | 78384750.53 | 0.272091E+09 |
| November | 88087644.44 | 0.00 | 88087644.44 | 16661597.74 | 0.349129E+09 |
| December | 68318055.64 | 0.00 | 68318055.64 | 1855547.44 | 0.467477E+09 |
| Annual Sum or Average | 0.242106E+10 | 68379582.23 | 0.235269E+10 | 0.175860E+10 | 0.333771E+10 |
| Minimum of Months | 68318055.64 | 0.00 | 68318055.64 | 1855547.44 | 0.140217E+09 |
| Maximum of Months | 0.341516E+09 | 26421681.49 | 0.325659E+09 | 0.335458E+09 | 0.477407E+09 |
Report: WindowEnergyReportMonthly
For: TWINDOW1 S SEA
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.356115E+09 | 0.211787E+09 | 0.144327E+09 | 0.314344E+09 | 0.430175E+09 |
| February | 0.500446E+09 | 0.312463E+09 | 0.187983E+09 | 0.504797E+09 | 0.340118E+09 |
| March | 0.579159E+09 | 0.304880E+09 | 0.274279E+09 | 0.608670E+09 | 0.316090E+09 |
| April | 0.601691E+09 | 0.261958E+09 | 0.339733E+09 | 0.666790E+09 | 0.256166E+09 |
| May | 0.571336E+09 | 0.173034E+09 | 0.398303E+09 | 0.640085E+09 | 0.217719E+09 |
| June | 0.504391E+09 | 0.136950E+09 | 0.367441E+09 | 0.571103E+09 | 0.167471E+09 |
| July | 0.569545E+09 | 0.210801E+09 | 0.358744E+09 | 0.708969E+09 | 0.156491E+09 |
| August | 0.601744E+09 | 0.277187E+09 | 0.324557E+09 | 0.772596E+09 | 0.151835E+09 |
| September | 0.646105E+09 | 0.354088E+09 | 0.292017E+09 | 0.786923E+09 | 0.201339E+09 |
| October | 0.595727E+09 | 0.362163E+09 | 0.233564E+09 | 0.668633E+09 | 0.272701E+09 |
| November | 0.348015E+09 | 0.198875E+09 | 0.149140E+09 | 0.332487E+09 | 0.328650E+09 |
| December | 0.375617E+09 | 0.242303E+09 | 0.133314E+09 | 0.363925E+09 | 0.432073E+09 |
| Annual Sum or Average | 0.624989E+10 | 0.304649E+10 | 0.320340E+10 | 0.693932E+10 | 0.327083E+10 |
| Minimum of Months | 0.348015E+09 | 0.136950E+09 | 0.133314E+09 | 0.314344E+09 | 0.151835E+09 |
| Maximum of Months | 0.646105E+09 | 0.362163E+09 | 0.398303E+09 | 0.786923E+09 | 0.432073E+09 |
Report: WindowEnergyReportMonthly
For: TWINDOW1 E SEA
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 84573088.28 | 21176855.29 | 63396233.00 | 29381994.51 | 0.303021E+09 |
| February | 0.140068E+09 | 49179775.95 | 90887815.83 | 89606073.04 | 0.236241E+09 |
| March | 0.233043E+09 | 84128155.90 | 0.148915E+09 | 0.193199E+09 | 0.206230E+09 |
| April | 0.349779E+09 | 0.145490E+09 | 0.204289E+09 | 0.352581E+09 | 0.157561E+09 |
| May | 0.384372E+09 | 0.133839E+09 | 0.250533E+09 | 0.406934E+09 | 0.135464E+09 |
| June | 0.445336E+09 | 0.193882E+09 | 0.251454E+09 | 0.502751E+09 | 0.102674E+09 |
| July | 0.429534E+09 | 0.193393E+09 | 0.236141E+09 | 0.503027E+09 | 93943745.15 |
| August | 0.420291E+09 | 0.209870E+09 | 0.210421E+09 | 0.507299E+09 | 92574631.90 |
| September | 0.301475E+09 | 0.139116E+09 | 0.162359E+09 | 0.326300E+09 | 0.128942E+09 |
| October | 0.204507E+09 | 87733384.55 | 0.116774E+09 | 0.186054E+09 | 0.180802E+09 |
| November | 96532611.88 | 27335106.39 | 69197505.49 | 52256008.00 | 0.226254E+09 |
| December | 81522159.70 | 26125280.48 | 55396879.22 | 37045472.72 | 0.300901E+09 |
| Annual Sum or Average | 0.317103E+10 | 0.131127E+10 | 0.185977E+10 | 0.318644E+10 | 0.216461E+10 |
| Minimum of Months | 81522159.70 | 21176855.29 | 55396879.22 | 29381994.51 | 92574631.90 |
| Maximum of Months | 0.445336E+09 | 0.209870E+09 | 0.251454E+09 | 0.507299E+09 | 0.303021E+09 |
Report: WindowEnergyReportMonthly
For: TWINDOW1 E NEA
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 84573088.28 | 21176855.29 | 63396233.00 | 30322711.58 | 0.298432E+09 |
| February | 0.140068E+09 | 49179775.95 | 90887815.83 | 93207689.46 | 0.228050E+09 |
| March | 0.233043E+09 | 84128155.90 | 0.148915E+09 | 0.201980E+09 | 0.198442E+09 |
| April | 0.349779E+09 | 0.145490E+09 | 0.204289E+09 | 0.361063E+09 | 0.152530E+09 |
| May | 0.384372E+09 | 0.133839E+09 | 0.250533E+09 | 0.411870E+09 | 0.133406E+09 |
| June | 0.445336E+09 | 0.193882E+09 | 0.251454E+09 | 0.505628E+09 | 0.101980E+09 |
| July | 0.429534E+09 | 0.193393E+09 | 0.236141E+09 | 0.506705E+09 | 93157058.23 |
| August | 0.420291E+09 | 0.209870E+09 | 0.210421E+09 | 0.512047E+09 | 91123319.87 |
| September | 0.301475E+09 | 0.139116E+09 | 0.162359E+09 | 0.333852E+09 | 0.123972E+09 |
| October | 0.204507E+09 | 87733384.55 | 0.116774E+09 | 0.195919E+09 | 0.170350E+09 |
| November | 96532611.88 | 27335106.39 | 69197505.49 | 54857577.12 | 0.220699E+09 |
| December | 81522159.70 | 26125280.48 | 55396879.22 | 38524704.80 | 0.294364E+09 |
| Annual Sum or Average | 0.317103E+10 | 0.131127E+10 | 0.185977E+10 | 0.324598E+10 | 0.210650E+10 |
| Minimum of Months | 81522159.70 | 21176855.29 | 55396879.22 | 30322711.58 | 91123319.87 |
| Maximum of Months | 0.445336E+09 | 0.209870E+09 | 0.251454E+09 | 0.512047E+09 | 0.298432E+09 |
Report: WindowEnergyReportMonthly
For: TWINDOW1 N NEA
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 80398594.49 | 0.00 | 80398594.49 | 3374264.46 | 0.477240E+09 |
| February | 0.112996E+09 | 0.00 | 0.112996E+09 | 24975543.06 | 0.370261E+09 |
| March | 0.184345E+09 | 3676.65 | 0.184341E+09 | 87169504.92 | 0.317808E+09 |
| April | 0.252834E+09 | 1224735.97 | 0.251609E+09 | 0.171635E+09 | 0.241487E+09 |
| May | 0.335468E+09 | 9808992.16 | 0.325659E+09 | 0.278245E+09 | 0.200801E+09 |
| June | 0.341516E+09 | 22472037.20 | 0.319044E+09 | 0.304372E+09 | 0.151181E+09 |
| July | 0.335695E+09 | 26421681.49 | 0.309274E+09 | 0.333998E+09 | 0.140172E+09 |
| August | 0.272693E+09 | 8316268.31 | 0.264376E+09 | 0.275292E+09 | 0.138457E+09 |
| September | 0.204209E+09 | 132190.44 | 0.204077E+09 | 0.160666E+09 | 0.196012E+09 |
| October | 0.144505E+09 | 0.00 | 0.144505E+09 | 76280663.23 | 0.269916E+09 |
| November | 88087644.44 | 0.00 | 88087644.44 | 16336735.82 | 0.348717E+09 |
| December | 68318055.64 | 0.00 | 68318055.64 | 1777747.14 | 0.467223E+09 |
| Annual Sum or Average | 0.242106E+10 | 68379582.23 | 0.235269E+10 | 0.173412E+10 | 0.331927E+10 |
| Minimum of Months | 68318055.64 | 0.00 | 68318055.64 | 1777747.14 | 0.138457E+09 |
| Maximum of Months | 0.341516E+09 | 26421681.49 | 0.325659E+09 | 0.333998E+09 | 0.477240E+09 |
Report: WindowEnergyReportMonthly
For: TWINDOW1 N N1A
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 80398594.49 | 0.00 | 80398594.49 | 3153945.28 | 0.486533E+09 |
| February | 0.112996E+09 | 0.00 | 0.112996E+09 | 24523409.10 | 0.377178E+09 |
| March | 0.184345E+09 | 3676.65 | 0.184341E+09 | 88157713.86 | 0.324264E+09 |
| April | 0.252834E+09 | 1224735.97 | 0.251609E+09 | 0.176559E+09 | 0.246611E+09 |
| May | 0.335468E+09 | 9808992.16 | 0.325659E+09 | 0.282509E+09 | 0.207604E+09 |
| June | 0.341516E+09 | 22472037.20 | 0.319044E+09 | 0.309365E+09 | 0.156550E+09 |
| July | 0.335695E+09 | 26421681.49 | 0.309274E+09 | 0.338378E+09 | 0.144857E+09 |
| August | 0.272693E+09 | 8316268.31 | 0.264376E+09 | 0.280506E+09 | 0.142485E+09 |
| September | 0.204209E+09 | 132190.44 | 0.204077E+09 | 0.163209E+09 | 0.204109E+09 |
| October | 0.144505E+09 | 0.00 | 0.144505E+09 | 77803324.01 | 0.276885E+09 |
| November | 88087644.44 | 0.00 | 88087644.44 | 15935730.91 | 0.356563E+09 |
| December | 68318055.64 | 0.00 | 68318055.64 | 1666411.70 | 0.476340E+09 |
| Annual Sum or Average | 0.242106E+10 | 68379582.23 | 0.235269E+10 | 0.176177E+10 | 0.339998E+10 |
| Minimum of Months | 68318055.64 | 0.00 | 68318055.64 | 1666411.70 | 0.142485E+09 |
| Maximum of Months | 0.341516E+09 | 26421681.49 | 0.325659E+09 | 0.338378E+09 | 0.486533E+09 |
Report: WindowEnergyReportMonthly
For: TWINDOW1 N N2A
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 80398594.49 | 0.00 | 80398594.49 | 3151489.11 | 0.486526E+09 |
| February | 0.112996E+09 | 0.00 | 0.112996E+09 | 24505304.04 | 0.377122E+09 |
| March | 0.184345E+09 | 3676.65 | 0.184341E+09 | 88039763.38 | 0.324090E+09 |
| April | 0.252834E+09 | 1224735.97 | 0.251609E+09 | 0.176144E+09 | 0.246570E+09 |
| May | 0.335468E+09 | 9808992.16 | 0.325659E+09 | 0.282198E+09 | 0.207417E+09 |
| June | 0.341516E+09 | 22472037.20 | 0.319044E+09 | 0.308974E+09 | 0.156473E+09 |
| July | 0.335695E+09 | 26421681.49 | 0.309274E+09 | 0.338294E+09 | 0.144648E+09 |
| August | 0.272693E+09 | 8316268.31 | 0.264376E+09 | 0.280284E+09 | 0.142368E+09 |
| September | 0.204209E+09 | 132190.44 | 0.204077E+09 | 0.163004E+09 | 0.203773E+09 |
| October | 0.144505E+09 | 0.00 | 0.144505E+09 | 77634968.19 | 0.276700E+09 |
| November | 88087644.44 | 0.00 | 88087644.44 | 15914011.08 | 0.356531E+09 |
| December | 68318055.64 | 0.00 | 68318055.64 | 1662113.32 | 0.476325E+09 |
| Annual Sum or Average | 0.242106E+10 | 68379582.23 | 0.235269E+10 | 0.175981E+10 | 0.339854E+10 |
| Minimum of Months | 68318055.64 | 0.00 | 68318055.64 | 1662113.32 | 0.142368E+09 |
| Maximum of Months | 0.341516E+09 | 26421681.49 | 0.325659E+09 | 0.338294E+09 | 0.486526E+09 |
Report: WindowEnergyReportMonthly
For: TWINDOW1 S S1A
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.356115E+09 | 0.211787E+09 | 0.144327E+09 | 0.312279E+09 | 0.439290E+09 |
| February | 0.500446E+09 | 0.312463E+09 | 0.187983E+09 | 0.502873E+09 | 0.348764E+09 |
| March | 0.579159E+09 | 0.304880E+09 | 0.274279E+09 | 0.608698E+09 | 0.325308E+09 |
| April | 0.601691E+09 | 0.261958E+09 | 0.339733E+09 | 0.669736E+09 | 0.263677E+09 |
| May | 0.571336E+09 | 0.173034E+09 | 0.398303E+09 | 0.642584E+09 | 0.225528E+09 |
| June | 0.504391E+09 | 0.136950E+09 | 0.367441E+09 | 0.575517E+09 | 0.173452E+09 |
| July | 0.569545E+09 | 0.210801E+09 | 0.358744E+09 | 0.712964E+09 | 0.161362E+09 |
| August | 0.601744E+09 | 0.277187E+09 | 0.324557E+09 | 0.776936E+09 | 0.155957E+09 |
| September | 0.646105E+09 | 0.354088E+09 | 0.292017E+09 | 0.787498E+09 | 0.209995E+09 |
| October | 0.595727E+09 | 0.362163E+09 | 0.233564E+09 | 0.668191E+09 | 0.283077E+09 |
| November | 0.348015E+09 | 0.198875E+09 | 0.149140E+09 | 0.330855E+09 | 0.337397E+09 |
| December | 0.375617E+09 | 0.242303E+09 | 0.133314E+09 | 0.362037E+09 | 0.441893E+09 |
| Annual Sum or Average | 0.624989E+10 | 0.304649E+10 | 0.320340E+10 | 0.695017E+10 | 0.336570E+10 |
| Minimum of Months | 0.348015E+09 | 0.136950E+09 | 0.133314E+09 | 0.312279E+09 | 0.155957E+09 |
| Maximum of Months | 0.646105E+09 | 0.362163E+09 | 0.398303E+09 | 0.787498E+09 | 0.441893E+09 |
Report: WindowEnergyReportMonthly
For: TWINDOW1 S S2A
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.356115E+09 | 0.211787E+09 | 0.144327E+09 | 0.312258E+09 | 0.439254E+09 |
| February | 0.500446E+09 | 0.312463E+09 | 0.187983E+09 | 0.502796E+09 | 0.348666E+09 |
| March | 0.579159E+09 | 0.304880E+09 | 0.274279E+09 | 0.608519E+09 | 0.325196E+09 |
| April | 0.601691E+09 | 0.261958E+09 | 0.339733E+09 | 0.669391E+09 | 0.263637E+09 |
| May | 0.571336E+09 | 0.173034E+09 | 0.398303E+09 | 0.642409E+09 | 0.225299E+09 |
| June | 0.504391E+09 | 0.136950E+09 | 0.367441E+09 | 0.575219E+09 | 0.173332E+09 |
| July | 0.569545E+09 | 0.210801E+09 | 0.358744E+09 | 0.712861E+09 | 0.161131E+09 |
| August | 0.601744E+09 | 0.277187E+09 | 0.324557E+09 | 0.776761E+09 | 0.155837E+09 |
| September | 0.646105E+09 | 0.354088E+09 | 0.292017E+09 | 0.787425E+09 | 0.209742E+09 |
| October | 0.595727E+09 | 0.362163E+09 | 0.233564E+09 | 0.668037E+09 | 0.282985E+09 |
| November | 0.348015E+09 | 0.198875E+09 | 0.149140E+09 | 0.330803E+09 | 0.337368E+09 |
| December | 0.375617E+09 | 0.242303E+09 | 0.133314E+09 | 0.361998E+09 | 0.441835E+09 |
| Annual Sum or Average | 0.624989E+10 | 0.304649E+10 | 0.320340E+10 | 0.694848E+10 | 0.336428E+10 |
| Minimum of Months | 0.348015E+09 | 0.136950E+09 | 0.133314E+09 | 0.312258E+09 | 0.155837E+09 |
| Maximum of Months | 0.646105E+09 | 0.362163E+09 | 0.398303E+09 | 0.787425E+09 | 0.441835E+09 |
Report: WindowEnergyReportMonthly
For: TWINDOW14
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 20293656.78 | 5081472.62 | 15212184.16 | 6863072.70 | 75853545.22 |
| February | 33609788.78 | 11800887.42 | 21808901.36 | 21236034.89 | 59287996.49 |
| March | 55919693.26 | 20186893.44 | 35732799.82 | 46418148.40 | 53215006.52 |
| April | 83930981.03 | 34910973.71 | 49020007.32 | 84241763.44 | 41603426.51 |
| May | 92231689.51 | 32115176.81 | 60116512.69 | 96232339.61 | 37012829.61 |
| June | 0.106860E+09 | 46522726.36 | 60337344.53 | 0.118361E+09 | 28702092.82 |
| July | 0.103068E+09 | 46405470.61 | 56662916.82 | 0.118038E+09 | 26631176.24 |
| August | 0.100851E+09 | 50359159.92 | 50491468.84 | 0.119318E+09 | 26167653.21 |
| September | 72340185.12 | 33381365.85 | 38958819.27 | 77432536.91 | 35178129.65 |
| October | 49072406.16 | 21051982.73 | 28020423.43 | 44704286.60 | 47139735.17 |
| November | 23163393.15 | 6559170.04 | 16604223.10 | 12192464.77 | 57935893.23 |
| December | 19561574.05 | 6268867.39 | 13292706.66 | 8748961.50 | 75138814.19 |
| Annual Sum or Average | 0.760902E+09 | 0.314644E+09 | 0.446258E+09 | 0.753787E+09 | 0.563866E+09 |
| Minimum of Months | 19561574.05 | 5081472.62 | 13292706.66 | 6863072.70 | 26167653.21 |
| Maximum of Months | 0.106860E+09 | 50359159.92 | 60337344.53 | 0.119318E+09 | 75853545.22 |
Report: WindowEnergyReportMonthly
For: ENTRANCE DOOR
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 60439560.24 | 15133890.07 | 45305670.17 | 23613050.30 | 0.199563E+09 |
| February | 0.100098E+09 | 35145979.55 | 64952335.68 | 69962470.10 | 0.156051E+09 |
| March | 0.166543E+09 | 60121592.45 | 0.106421E+09 | 0.147959E+09 | 0.141948E+09 |
| April | 0.249967E+09 | 0.103974E+09 | 0.145994E+09 | 0.263929E+09 | 0.110578E+09 |
| May | 0.274689E+09 | 95646988.84 | 0.179042E+09 | 0.296869E+09 | 0.102966E+09 |
| June | 0.318256E+09 | 0.138556E+09 | 0.179700E+09 | 0.360487E+09 | 82061044.14 |
| July | 0.306963E+09 | 0.138207E+09 | 0.168756E+09 | 0.356700E+09 | 78298931.01 |
| August | 0.300358E+09 | 0.149982E+09 | 0.150376E+09 | 0.357786E+09 | 78857997.08 |
| September | 0.215447E+09 | 99418014.91 | 0.116029E+09 | 0.231737E+09 | 0.106375E+09 |
| October | 0.146150E+09 | 62698043.65 | 83451794.24 | 0.134505E+09 | 0.138629E+09 |
| November | 68986349.31 | 19534840.72 | 49451508.59 | 39064999.42 | 0.159681E+09 |
| December | 58259235.67 | 18670247.19 | 39588988.49 | 28754004.95 | 0.201736E+09 |
| Annual Sum or Average | 0.226616E+10 | 0.937089E+09 | 0.132907E+10 | 0.231137E+10 | 0.155674E+10 |
| Minimum of Months | 58259235.67 | 15133890.07 | 39588988.49 | 23613050.30 | 78298931.01 |
| Maximum of Months | 0.318256E+09 | 0.149982E+09 | 0.179700E+09 | 0.360487E+09 | 0.201736E+09 |
Report: WindowEnergyReportMonthly
For: MWINDOW14
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 20293656.78 | 5081472.62 | 15212184.16 | 6178981.45 | 82669087.77 |
| February | 33609788.78 | 11800887.42 | 21808901.36 | 19923525.25 | 64294847.65 |
| March | 55919693.26 | 20186893.44 | 35732799.82 | 44328305.06 | 58484668.26 |
| April | 83930981.03 | 34910973.71 | 49020007.32 | 81587863.24 | 45699773.42 |
| May | 92231689.51 | 32115176.81 | 60116512.69 | 92908190.88 | 41191390.37 |
| June | 0.106860E+09 | 46522726.36 | 60337344.53 | 0.116240E+09 | 31008334.06 |
| July | 0.103068E+09 | 46405470.61 | 56662916.82 | 0.116968E+09 | 28056779.55 |
| August | 0.100851E+09 | 50359159.92 | 50491468.84 | 0.118247E+09 | 27632216.18 |
| September | 72340185.12 | 33381365.85 | 38958819.27 | 74854999.78 | 39300838.50 |
| October | 49072406.16 | 21051982.73 | 28020423.43 | 41668875.45 | 54167016.30 |
| November | 23163393.15 | 6559170.04 | 16604223.10 | 11107846.12 | 64189106.63 |
| December | 19561574.05 | 6268867.39 | 13292706.66 | 8045460.97 | 82022325.79 |
| Annual Sum or Average | 0.760902E+09 | 0.314644E+09 | 0.446258E+09 | 0.732059E+09 | 0.618716E+09 |
| Minimum of Months | 19561574.05 | 5081472.62 | 13292706.66 | 6178981.45 | 27632216.18 |
| Maximum of Months | 0.106860E+09 | 50359159.92 | 60337344.53 | 0.118247E+09 | 82669087.77 |
Report: WindowZoneSummaryMonthly
For: G SW APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 128.91 | 267.68 | 166.58 | 89.06 | 77.52 | 0.00 | 0.00 |
| February | 252.51 | 231.43 | 266.60 | 151.41 | 115.19 | 0.00 | 0.00 |
| March | 306.09 | 190.20 | 300.37 | 142.26 | 158.12 | 0.00 | 0.00 |
| April | 399.32 | 155.15 | 359.86 | 149.80 | 210.06 | 0.00 | 0.00 |
| May | 429.41 | 133.63 | 378.06 | 131.61 | 246.45 | 0.00 | 0.00 |
| June | 405.24 | 107.62 | 352.99 | 114.35 | 238.65 | 0.00 | 0.00 |
| July | 508.53 | 99.15 | 408.66 | 181.89 | 226.77 | 0.00 | 0.00 |
| August | 492.23 | 97.94 | 386.48 | 186.03 | 200.45 | 0.00 | 0.00 |
| September | 453.67 | 140.50 | 381.53 | 200.24 | 181.29 | 0.00 | 0.00 |
| October | 318.49 | 180.71 | 297.74 | 166.03 | 131.71 | 0.00 | 0.00 |
| November | 148.85 | 215.31 | 171.74 | 87.40 | 84.34 | 0.00 | 0.00 |
| December | 150.65 | 270.38 | 172.04 | 101.62 | 70.42 | 0.00 | 0.00 |
| Annual Sum or Average | 333.28 | 173.88 | 303.72 | 141.77 | 161.95 | 0.00 | 0.00 |
| Minimum of Months | 128.91 | 97.94 | 166.58 | 87.40 | 70.42 | 0.00 | 0.00 |
| Maximum of Months | 508.53 | 270.38 | 408.66 | 200.24 | 246.45 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: G NW APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 11.94 | 283.96 | 63.64 | 9.98 | 53.66 | 0.00 | 0.00 |
| February | 51.84 | 241.16 | 106.44 | 22.25 | 84.19 | 0.00 | 0.00 |
| March | 110.40 | 188.26 | 152.97 | 28.43 | 124.54 | 0.00 | 0.00 |
| April | 210.94 | 146.40 | 225.27 | 49.21 | 176.06 | 0.00 | 0.00 |
| May | 299.27 | 122.70 | 290.00 | 70.67 | 219.33 | 0.00 | 0.00 |
| June | 304.52 | 98.40 | 290.15 | 70.18 | 219.97 | 0.00 | 0.00 |
| July | 368.92 | 92.00 | 321.35 | 113.05 | 208.30 | 0.00 | 0.00 |
| August | 306.74 | 91.32 | 263.63 | 85.64 | 177.98 | 0.00 | 0.00 |
| September | 214.06 | 135.25 | 211.05 | 63.68 | 147.37 | 0.00 | 0.00 |
| October | 99.84 | 171.47 | 129.27 | 30.81 | 98.46 | 0.00 | 0.00 |
| November | 26.71 | 219.99 | 71.46 | 10.68 | 60.79 | 0.00 | 0.00 |
| December | 14.75 | 282.14 | 57.30 | 11.15 | 46.15 | 0.00 | 0.00 |
| Annual Sum or Average | 169.06 | 172.44 | 182.31 | 47.34 | 134.97 | 0.00 | 0.00 |
| Minimum of Months | 11.94 | 91.32 | 57.30 | 9.98 | 46.15 | 0.00 | 0.00 |
| Maximum of Months | 368.92 | 283.96 | 321.35 | 113.05 | 219.97 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: OFFICE
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 133.63 | 231.38 | 164.53 | 86.98 | 77.56 | 0.00 | 0.00 |
| February | 257.23 | 210.32 | 264.76 | 149.49 | 115.27 | 0.00 | 0.00 |
| March | 309.94 | 185.32 | 303.24 | 145.24 | 158.00 | 0.00 | 0.00 |
| April | 402.10 | 154.98 | 367.08 | 157.19 | 209.89 | 0.00 | 0.00 |
| May | 392.95 | 140.84 | 356.82 | 114.57 | 242.25 | 0.00 | 0.00 |
| June | 412.24 | 116.72 | 366.41 | 127.64 | 238.77 | 0.00 | 0.00 |
| July | 445.95 | 110.16 | 373.01 | 150.91 | 222.10 | 0.00 | 0.00 |
| August | 468.86 | 111.90 | 381.58 | 181.85 | 199.74 | 0.00 | 0.00 |
| September | 420.96 | 153.34 | 365.58 | 190.28 | 175.30 | 0.00 | 0.00 |
| October | 315.16 | 190.82 | 298.77 | 167.97 | 130.80 | 0.00 | 0.00 |
| November | 149.19 | 209.82 | 171.51 | 87.27 | 84.24 | 0.00 | 0.00 |
| December | 153.05 | 244.56 | 170.68 | 100.22 | 70.46 | 0.00 | 0.00 |
| Annual Sum or Average | 322.04 | 171.51 | 298.74 | 138.18 | 160.55 | 0.00 | 0.00 |
| Minimum of Months | 133.63 | 110.16 | 164.53 | 86.98 | 70.46 | 0.00 | 0.00 |
| Maximum of Months | 468.86 | 244.56 | 381.58 | 190.28 | 242.25 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: G NE APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 8.00 | 282.77 | 61.59 | 7.91 | 53.69 | 0.00 | 0.00 |
| February | 44.77 | 237.11 | 104.61 | 20.33 | 84.28 | 0.00 | 0.00 |
| March | 109.36 | 183.34 | 155.83 | 31.41 | 124.42 | 0.00 | 0.00 |
| April | 216.37 | 141.14 | 232.49 | 56.60 | 175.89 | 0.00 | 0.00 |
| May | 270.82 | 120.24 | 268.76 | 53.63 | 215.13 | 0.00 | 0.00 |
| June | 321.52 | 97.83 | 303.57 | 83.47 | 220.10 | 0.00 | 0.00 |
| July | 319.50 | 88.63 | 285.70 | 82.07 | 203.63 | 0.00 | 0.00 |
| August | 297.67 | 88.54 | 258.73 | 81.46 | 177.27 | 0.00 | 0.00 |
| September | 187.78 | 129.92 | 195.09 | 53.72 | 141.37 | 0.00 | 0.00 |
| October | 97.89 | 167.10 | 130.31 | 32.76 | 97.55 | 0.00 | 0.00 |
| November | 24.38 | 218.35 | 71.23 | 10.55 | 60.68 | 0.00 | 0.00 |
| December | 10.15 | 279.91 | 55.94 | 9.75 | 46.19 | 0.00 | 0.00 |
| Annual Sum or Average | 159.64 | 169.27 | 177.32 | 43.75 | 133.58 | 0.00 | 0.00 |
| Minimum of Months | 8.00 | 88.54 | 55.94 | 7.91 | 46.19 | 0.00 | 0.00 |
| Maximum of Months | 321.52 | 282.77 | 303.57 | 83.47 | 220.10 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: G N1 APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 1.29 | 180.95 | 30.02 | 0.00 | 30.02 | 0.00 | 0.00 |
| February | 11.11 | 153.96 | 46.71 | 0.00 | 46.71 | 0.00 | 0.00 |
| March | 35.39 | 118.44 | 68.83 | 0.00 | 68.83 | 0.00 | 0.00 |
| April | 74.35 | 90.17 | 97.54 | 0.47 | 97.07 | 0.00 | 0.00 |
| May | 111.40 | 75.67 | 125.25 | 3.66 | 121.59 | 0.00 | 0.00 |
| June | 123.62 | 60.38 | 131.76 | 8.67 | 123.09 | 0.00 | 0.00 |
| July | 129.28 | 55.15 | 125.33 | 9.86 | 115.47 | 0.00 | 0.00 |
| August | 106.35 | 54.68 | 101.81 | 3.10 | 98.71 | 0.00 | 0.00 |
| September | 61.93 | 84.51 | 78.78 | 0.05 | 78.73 | 0.00 | 0.00 |
| October | 27.88 | 108.69 | 53.95 | 0.00 | 53.95 | 0.00 | 0.00 |
| November | 6.17 | 139.45 | 33.98 | 0.00 | 33.98 | 0.00 | 0.00 |
| December | 0.67 | 178.60 | 25.51 | 0.00 | 25.51 | 0.00 | 0.00 |
| Annual Sum or Average | 57.74 | 108.18 | 76.77 | 2.17 | 74.60 | 0.00 | 0.00 |
| Minimum of Months | 0.67 | 54.68 | 25.51 | 0.00 | 25.51 | 0.00 | 0.00 |
| Maximum of Months | 129.28 | 180.95 | 131.76 | 9.86 | 123.09 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: G N2 APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 1.29 | 180.95 | 30.02 | 0.00 | 30.02 | 0.00 | 0.00 |
| February | 11.11 | 153.96 | 46.71 | 0.00 | 46.71 | 0.00 | 0.00 |
| March | 35.38 | 118.43 | 68.83 | 0.00 | 68.83 | 0.00 | 0.00 |
| April | 74.31 | 90.17 | 97.54 | 0.47 | 97.07 | 0.00 | 0.00 |
| May | 111.42 | 75.60 | 125.25 | 3.66 | 121.59 | 0.00 | 0.00 |
| June | 123.52 | 60.43 | 131.76 | 8.67 | 123.09 | 0.00 | 0.00 |
| July | 129.30 | 55.10 | 125.33 | 9.86 | 115.47 | 0.00 | 0.00 |
| August | 106.34 | 54.67 | 101.81 | 3.10 | 98.71 | 0.00 | 0.00 |
| September | 61.94 | 84.43 | 78.78 | 0.05 | 78.73 | 0.00 | 0.00 |
| October | 27.89 | 108.64 | 53.95 | 0.00 | 53.95 | 0.00 | 0.00 |
| November | 6.17 | 139.45 | 33.98 | 0.00 | 33.98 | 0.00 | 0.00 |
| December | 0.67 | 178.60 | 25.51 | 0.00 | 25.51 | 0.00 | 0.00 |
| Annual Sum or Average | 57.73 | 108.16 | 76.77 | 2.17 | 74.60 | 0.00 | 0.00 |
| Minimum of Months | 0.67 | 54.67 | 25.51 | 0.00 | 25.51 | 0.00 | 0.00 |
| Maximum of Months | 129.30 | 180.95 | 131.76 | 9.86 | 123.09 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: G S1 APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 118.40 | 163.65 | 132.96 | 79.07 | 53.89 | 0.00 | 0.00 |
| February | 212.21 | 142.53 | 206.86 | 129.16 | 77.70 | 0.00 | 0.00 |
| March | 232.73 | 119.18 | 216.23 | 113.83 | 102.40 | 0.00 | 0.00 |
| April | 265.81 | 98.24 | 232.13 | 101.06 | 131.07 | 0.00 | 0.00 |
| May | 244.41 | 85.77 | 213.31 | 64.60 | 148.71 | 0.00 | 0.00 |
| June | 226.05 | 68.49 | 194.60 | 52.84 | 141.76 | 0.00 | 0.00 |
| July | 270.28 | 61.87 | 212.64 | 78.70 | 133.94 | 0.00 | 0.00 |
| August | 293.24 | 60.36 | 224.67 | 103.49 | 121.18 | 0.00 | 0.00 |
| September | 304.35 | 87.10 | 249.27 | 136.61 | 112.66 | 0.00 | 0.00 |
| October | 249.15 | 114.57 | 222.42 | 135.22 | 87.20 | 0.00 | 0.00 |
| November | 128.55 | 133.40 | 134.27 | 76.73 | 57.54 | 0.00 | 0.00 |
| December | 137.01 | 165.83 | 140.24 | 90.47 | 49.77 | 0.00 | 0.00 |
| Annual Sum or Average | 223.53 | 108.26 | 198.18 | 96.60 | 101.58 | 0.00 | 0.00 |
| Minimum of Months | 118.40 | 60.36 | 132.96 | 52.84 | 49.77 | 0.00 | 0.00 |
| Maximum of Months | 304.35 | 165.83 | 249.27 | 136.61 | 148.71 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: G S2 APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 118.67 | 162.61 | 132.96 | 79.07 | 53.89 | 0.00 | 0.00 |
| February | 212.49 | 141.84 | 206.86 | 129.16 | 77.70 | 0.00 | 0.00 |
| March | 232.73 | 119.08 | 216.23 | 113.83 | 102.40 | 0.00 | 0.00 |
| April | 265.49 | 98.56 | 232.13 | 101.06 | 131.07 | 0.00 | 0.00 |
| May | 243.83 | 86.42 | 213.31 | 64.60 | 148.71 | 0.00 | 0.00 |
| June | 225.50 | 69.03 | 194.60 | 52.84 | 141.76 | 0.00 | 0.00 |
| July | 269.91 | 62.23 | 212.64 | 78.70 | 133.94 | 0.00 | 0.00 |
| August | 292.83 | 60.83 | 224.67 | 103.49 | 121.18 | 0.00 | 0.00 |
| September | 304.03 | 87.55 | 249.27 | 136.61 | 112.66 | 0.00 | 0.00 |
| October | 248.78 | 115.34 | 222.42 | 135.22 | 87.20 | 0.00 | 0.00 |
| November | 128.47 | 133.44 | 134.27 | 76.73 | 57.54 | 0.00 | 0.00 |
| December | 137.19 | 165.08 | 140.24 | 90.47 | 49.77 | 0.00 | 0.00 |
| Annual Sum or Average | 223.33 | 108.35 | 198.18 | 96.60 | 101.58 | 0.00 | 0.00 |
| Minimum of Months | 118.67 | 60.83 | 132.96 | 52.84 | 49.77 | 0.00 | 0.00 |
| Maximum of Months | 304.03 | 165.08 | 249.27 | 136.61 | 148.71 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: M SW APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 125.01 | 280.07 | 166.58 | 89.06 | 77.52 | 0.00 | 0.00 |
| February | 244.56 | 245.52 | 266.60 | 151.41 | 115.19 | 0.00 | 0.00 |
| March | 294.60 | 209.36 | 300.37 | 142.26 | 158.12 | 0.00 | 0.00 |
| April | 381.98 | 176.92 | 359.86 | 149.80 | 210.06 | 0.00 | 0.00 |
| May | 414.45 | 149.37 | 378.06 | 131.61 | 246.45 | 0.00 | 0.00 |
| June | 395.55 | 115.87 | 352.99 | 114.35 | 238.65 | 0.00 | 0.00 |
| July | 503.32 | 102.20 | 408.66 | 181.89 | 226.77 | 0.00 | 0.00 |
| August | 488.39 | 100.14 | 386.48 | 186.03 | 200.45 | 0.00 | 0.00 |
| September | 449.46 | 144.59 | 381.53 | 200.24 | 181.29 | 0.00 | 0.00 |
| October | 312.35 | 191.13 | 297.74 | 166.03 | 131.71 | 0.00 | 0.00 |
| November | 144.96 | 224.92 | 171.74 | 87.40 | 84.34 | 0.00 | 0.00 |
| December | 147.07 | 281.36 | 172.04 | 101.62 | 70.42 | 0.00 | 0.00 |
| Annual Sum or Average | 325.61 | 184.84 | 303.72 | 141.77 | 161.95 | 0.00 | 0.00 |
| Minimum of Months | 125.01 | 100.14 | 166.58 | 87.40 | 70.42 | 0.00 | 0.00 |
| Maximum of Months | 503.32 | 281.36 | 408.66 | 200.24 | 246.45 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: M NW APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 10.68 | 297.36 | 63.64 | 9.98 | 53.66 | 0.00 | 0.00 |
| February | 47.62 | 254.76 | 106.44 | 22.25 | 84.19 | 0.00 | 0.00 |
| March | 102.99 | 203.03 | 152.97 | 28.43 | 124.54 | 0.00 | 0.00 |
| April | 196.05 | 165.43 | 225.27 | 49.21 | 176.06 | 0.00 | 0.00 |
| May | 280.03 | 141.90 | 290.00 | 70.67 | 219.33 | 0.00 | 0.00 |
| June | 291.89 | 108.10 | 290.15 | 70.18 | 219.97 | 0.00 | 0.00 |
| July | 363.34 | 95.62 | 321.35 | 113.05 | 208.30 | 0.00 | 0.00 |
| August | 302.66 | 94.38 | 263.63 | 85.64 | 177.98 | 0.00 | 0.00 |
| September | 208.55 | 142.91 | 211.05 | 63.68 | 147.37 | 0.00 | 0.00 |
| October | 94.12 | 183.52 | 129.27 | 30.81 | 98.46 | 0.00 | 0.00 |
| November | 24.64 | 229.77 | 71.46 | 10.68 | 60.79 | 0.00 | 0.00 |
| December | 13.71 | 293.24 | 57.30 | 11.15 | 46.15 | 0.00 | 0.00 |
| Annual Sum or Average | 162.08 | 183.84 | 182.31 | 47.34 | 134.97 | 0.00 | 0.00 |
| Minimum of Months | 10.68 | 94.38 | 57.30 | 9.98 | 46.15 | 0.00 | 0.00 |
| Maximum of Months | 363.34 | 297.36 | 321.35 | 113.05 | 219.97 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: M SE APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 122.07 | 279.76 | 164.53 | 86.98 | 77.56 | 0.00 | 0.00 |
| February | 241.12 | 245.13 | 264.76 | 149.49 | 115.27 | 0.00 | 0.00 |
| March | 295.98 | 207.46 | 303.24 | 145.24 | 158.00 | 0.00 | 0.00 |
| April | 386.71 | 172.04 | 367.08 | 157.19 | 209.89 | 0.00 | 0.00 |
| May | 384.58 | 145.52 | 356.82 | 114.57 | 242.25 | 0.00 | 0.00 |
| June | 411.20 | 112.08 | 366.41 | 127.64 | 238.77 | 0.00 | 0.00 |
| July | 452.39 | 97.78 | 373.01 | 150.91 | 222.10 | 0.00 | 0.00 |
| August | 476.90 | 94.61 | 381.58 | 181.85 | 199.74 | 0.00 | 0.00 |
| September | 424.02 | 140.76 | 365.58 | 190.28 | 175.30 | 0.00 | 0.00 |
| October | 312.52 | 189.46 | 298.77 | 167.97 | 130.80 | 0.00 | 0.00 |
| November | 144.01 | 224.97 | 171.51 | 87.27 | 84.24 | 0.00 | 0.00 |
| December | 144.25 | 281.01 | 170.68 | 100.22 | 70.46 | 0.00 | 0.00 |
| Annual Sum or Average | 316.65 | 182.25 | 298.74 | 138.18 | 160.55 | 0.00 | 0.00 |
| Minimum of Months | 122.07 | 94.61 | 164.53 | 86.98 | 70.46 | 0.00 | 0.00 |
| Maximum of Months | 476.90 | 281.01 | 381.58 | 190.28 | 242.25 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: M NE APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 6.85 | 296.25 | 61.59 | 7.91 | 53.69 | 0.00 | 0.00 |
| February | 40.55 | 250.75 | 104.61 | 20.33 | 84.28 | 0.00 | 0.00 |
| March | 101.76 | 197.85 | 155.83 | 31.41 | 124.42 | 0.00 | 0.00 |
| April | 200.18 | 160.09 | 232.49 | 56.60 | 175.89 | 0.00 | 0.00 |
| May | 251.20 | 139.35 | 268.76 | 53.63 | 215.13 | 0.00 | 0.00 |
| June | 309.86 | 106.83 | 303.57 | 83.47 | 220.10 | 0.00 | 0.00 |
| July | 313.78 | 92.59 | 285.70 | 82.07 | 203.63 | 0.00 | 0.00 |
| August | 293.61 | 91.37 | 258.73 | 81.46 | 177.27 | 0.00 | 0.00 |
| September | 181.98 | 137.74 | 195.09 | 53.72 | 141.37 | 0.00 | 0.00 |
| October | 91.68 | 179.24 | 130.31 | 32.76 | 97.55 | 0.00 | 0.00 |
| November | 22.20 | 228.14 | 71.23 | 10.55 | 60.68 | 0.00 | 0.00 |
| December | 9.18 | 291.20 | 55.94 | 9.75 | 46.19 | 0.00 | 0.00 |
| Annual Sum or Average | 152.53 | 180.63 | 177.32 | 43.75 | 133.58 | 0.00 | 0.00 |
| Minimum of Months | 6.85 | 91.37 | 55.94 | 7.91 | 46.19 | 0.00 | 0.00 |
| Maximum of Months | 313.78 | 296.25 | 303.57 | 83.47 | 220.10 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: M N1 APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 1.00 | 189.15 | 30.02 | 0.00 | 30.02 | 0.00 | 0.00 |
| February | 9.35 | 162.79 | 46.71 | 0.00 | 46.71 | 0.00 | 0.00 |
| March | 31.69 | 128.06 | 68.83 | 0.00 | 68.83 | 0.00 | 0.00 |
| April | 65.82 | 103.10 | 97.54 | 0.47 | 97.07 | 0.00 | 0.00 |
| May | 100.88 | 86.73 | 125.25 | 3.66 | 121.59 | 0.00 | 0.00 |
| June | 117.60 | 65.09 | 131.76 | 8.67 | 123.09 | 0.00 | 0.00 |
| July | 126.96 | 56.79 | 125.33 | 9.86 | 115.47 | 0.00 | 0.00 |
| August | 104.76 | 56.01 | 101.81 | 3.10 | 98.71 | 0.00 | 0.00 |
| September | 59.55 | 88.48 | 78.78 | 0.05 | 78.73 | 0.00 | 0.00 |
| October | 24.56 | 118.24 | 53.95 | 0.00 | 53.95 | 0.00 | 0.00 |
| November | 5.15 | 146.34 | 33.98 | 0.00 | 33.98 | 0.00 | 0.00 |
| December | 0.49 | 185.67 | 25.51 | 0.00 | 25.51 | 0.00 | 0.00 |
| Annual Sum or Average | 54.26 | 115.31 | 76.77 | 2.17 | 74.60 | 0.00 | 0.00 |
| Minimum of Months | 0.49 | 56.01 | 25.51 | 0.00 | 25.51 | 0.00 | 0.00 |
| Maximum of Months | 126.96 | 189.15 | 131.76 | 9.86 | 123.09 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: M N2 APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 0.99 | 189.15 | 30.02 | 0.00 | 30.02 | 0.00 | 0.00 |
| February | 9.35 | 162.78 | 46.71 | 0.00 | 46.71 | 0.00 | 0.00 |
| March | 31.67 | 128.02 | 68.83 | 0.00 | 68.83 | 0.00 | 0.00 |
| April | 65.70 | 103.22 | 97.54 | 0.47 | 97.07 | 0.00 | 0.00 |
| May | 100.87 | 86.69 | 125.25 | 3.66 | 121.59 | 0.00 | 0.00 |
| June | 117.58 | 65.09 | 131.76 | 8.67 | 123.09 | 0.00 | 0.00 |
| July | 126.96 | 56.77 | 125.33 | 9.86 | 115.47 | 0.00 | 0.00 |
| August | 104.75 | 56.00 | 101.81 | 3.10 | 98.71 | 0.00 | 0.00 |
| September | 59.55 | 88.44 | 78.78 | 0.05 | 78.73 | 0.00 | 0.00 |
| October | 24.54 | 118.24 | 53.95 | 0.00 | 53.95 | 0.00 | 0.00 |
| November | 5.14 | 146.33 | 33.98 | 0.00 | 33.98 | 0.00 | 0.00 |
| December | 0.49 | 185.67 | 25.51 | 0.00 | 25.51 | 0.00 | 0.00 |
| Annual Sum or Average | 54.24 | 115.31 | 76.77 | 2.17 | 74.60 | 0.00 | 0.00 |
| Minimum of Months | 0.49 | 56.00 | 25.51 | 0.00 | 25.51 | 0.00 | 0.00 |
| Maximum of Months | 126.96 | 189.15 | 131.76 | 9.86 | 123.09 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: M S1 APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 115.81 | 170.88 | 132.96 | 79.07 | 53.89 | 0.00 | 0.00 |
| February | 207.06 | 151.62 | 206.86 | 129.16 | 77.70 | 0.00 | 0.00 |
| March | 225.33 | 133.21 | 216.23 | 113.83 | 102.40 | 0.00 | 0.00 |
| April | 255.76 | 112.83 | 232.13 | 101.06 | 131.07 | 0.00 | 0.00 |
| May | 237.47 | 93.88 | 213.31 | 64.60 | 148.71 | 0.00 | 0.00 |
| June | 221.88 | 72.29 | 194.60 | 52.84 | 141.76 | 0.00 | 0.00 |
| July | 268.02 | 63.29 | 212.64 | 78.70 | 133.94 | 0.00 | 0.00 |
| August | 291.57 | 61.26 | 224.67 | 103.49 | 121.18 | 0.00 | 0.00 |
| September | 302.46 | 88.87 | 249.27 | 136.61 | 112.66 | 0.00 | 0.00 |
| October | 245.56 | 120.99 | 222.42 | 135.22 | 87.20 | 0.00 | 0.00 |
| November | 125.81 | 140.14 | 134.27 | 76.73 | 57.54 | 0.00 | 0.00 |
| December | 134.41 | 173.01 | 140.24 | 90.47 | 49.77 | 0.00 | 0.00 |
| Annual Sum or Average | 219.28 | 115.02 | 198.18 | 96.60 | 101.58 | 0.00 | 0.00 |
| Minimum of Months | 115.81 | 61.26 | 132.96 | 52.84 | 49.77 | 0.00 | 0.00 |
| Maximum of Months | 302.46 | 173.01 | 249.27 | 136.61 | 148.71 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: M S2 APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 115.80 | 170.87 | 132.96 | 79.07 | 53.89 | 0.00 | 0.00 |
| February | 207.05 | 151.60 | 206.86 | 129.16 | 77.70 | 0.00 | 0.00 |
| March | 225.29 | 133.22 | 216.23 | 113.83 | 102.40 | 0.00 | 0.00 |
| April | 255.67 | 112.91 | 232.13 | 101.06 | 131.07 | 0.00 | 0.00 |
| May | 237.47 | 93.84 | 213.31 | 64.60 | 148.71 | 0.00 | 0.00 |
| June | 221.86 | 72.28 | 194.60 | 52.84 | 141.76 | 0.00 | 0.00 |
| July | 268.02 | 63.27 | 212.64 | 78.70 | 133.94 | 0.00 | 0.00 |
| August | 291.56 | 61.24 | 224.67 | 103.49 | 121.18 | 0.00 | 0.00 |
| September | 302.45 | 88.84 | 249.27 | 136.61 | 112.66 | 0.00 | 0.00 |
| October | 245.55 | 120.99 | 222.42 | 135.22 | 87.20 | 0.00 | 0.00 |
| November | 125.80 | 140.14 | 134.27 | 76.73 | 57.54 | 0.00 | 0.00 |
| December | 134.41 | 172.99 | 140.24 | 90.47 | 49.77 | 0.00 | 0.00 |
| Annual Sum or Average | 219.27 | 115.01 | 198.18 | 96.60 | 101.58 | 0.00 | 0.00 |
| Minimum of Months | 115.80 | 61.24 | 132.96 | 52.84 | 49.77 | 0.00 | 0.00 |
| Maximum of Months | 302.45 | 172.99 | 249.27 | 136.61 | 148.71 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: T SW APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 125.91 | 268.73 | 166.58 | 89.06 | 77.52 | 0.00 | 0.00 |
| February | 244.90 | 234.43 | 266.60 | 151.41 | 115.19 | 0.00 | 0.00 |
| March | 295.35 | 194.37 | 300.37 | 142.26 | 158.12 | 0.00 | 0.00 |
| April | 384.12 | 160.53 | 359.86 | 149.80 | 210.06 | 0.00 | 0.00 |
| May | 417.99 | 132.41 | 378.06 | 131.61 | 246.45 | 0.00 | 0.00 |
| June | 396.35 | 104.59 | 352.99 | 114.35 | 238.65 | 0.00 | 0.00 |
| July | 500.30 | 94.85 | 408.66 | 181.89 | 226.77 | 0.00 | 0.00 |
| August | 486.10 | 92.95 | 386.48 | 186.03 | 200.45 | 0.00 | 0.00 |
| September | 452.29 | 128.73 | 381.53 | 200.24 | 181.29 | 0.00 | 0.00 |
| October | 317.15 | 168.91 | 297.74 | 166.03 | 131.71 | 0.00 | 0.00 |
| November | 146.66 | 211.33 | 171.74 | 87.40 | 84.34 | 0.00 | 0.00 |
| December | 147.67 | 269.15 | 172.04 | 101.62 | 70.42 | 0.00 | 0.00 |
| Annual Sum or Average | 326.70 | 171.46 | 303.72 | 141.77 | 161.95 | 0.00 | 0.00 |
| Minimum of Months | 125.91 | 92.95 | 166.58 | 87.40 | 70.42 | 0.00 | 0.00 |
| Maximum of Months | 500.30 | 269.15 | 408.66 | 200.24 | 246.45 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: T NW APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 11.24 | 285.56 | 63.64 | 9.98 | 53.66 | 0.00 | 0.00 |
| February | 48.70 | 244.26 | 106.44 | 22.25 | 84.19 | 0.00 | 0.00 |
| March | 103.86 | 192.85 | 152.97 | 28.43 | 124.54 | 0.00 | 0.00 |
| April | 197.47 | 154.08 | 225.27 | 49.21 | 176.06 | 0.00 | 0.00 |
| May | 286.02 | 126.14 | 290.00 | 70.67 | 219.33 | 0.00 | 0.00 |
| June | 295.13 | 98.12 | 290.15 | 70.18 | 219.97 | 0.00 | 0.00 |
| July | 362.29 | 89.06 | 321.35 | 113.05 | 208.30 | 0.00 | 0.00 |
| August | 302.58 | 87.56 | 263.63 | 85.64 | 177.98 | 0.00 | 0.00 |
| September | 214.37 | 125.26 | 211.05 | 63.68 | 147.37 | 0.00 | 0.00 |
| October | 99.71 | 164.70 | 129.27 | 30.81 | 98.46 | 0.00 | 0.00 |
| November | 26.06 | 217.47 | 71.46 | 10.68 | 60.79 | 0.00 | 0.00 |
| December | 14.24 | 281.04 | 57.30 | 11.15 | 46.15 | 0.00 | 0.00 |
| Annual Sum or Average | 164.20 | 171.84 | 182.31 | 47.34 | 134.97 | 0.00 | 0.00 |
| Minimum of Months | 11.24 | 87.56 | 57.30 | 9.98 | 46.15 | 0.00 | 0.00 |
| Maximum of Months | 362.29 | 285.56 | 321.35 | 113.05 | 219.97 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: T SE APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 123.05 | 268.46 | 164.53 | 86.98 | 77.56 | 0.00 | 0.00 |
| February | 241.52 | 234.06 | 264.76 | 149.49 | 115.27 | 0.00 | 0.00 |
| March | 296.98 | 192.61 | 303.24 | 145.24 | 158.00 | 0.00 | 0.00 |
| April | 389.65 | 155.99 | 367.08 | 157.19 | 209.89 | 0.00 | 0.00 |
| May | 388.58 | 129.53 | 356.82 | 114.57 | 242.25 | 0.00 | 0.00 |
| June | 411.89 | 101.82 | 366.41 | 127.64 | 238.77 | 0.00 | 0.00 |
| July | 449.96 | 90.95 | 373.01 | 150.91 | 222.10 | 0.00 | 0.00 |
| August | 474.86 | 88.26 | 381.58 | 181.85 | 199.74 | 0.00 | 0.00 |
| September | 427.28 | 125.22 | 365.58 | 190.28 | 175.30 | 0.00 | 0.00 |
| October | 317.36 | 167.58 | 298.77 | 167.97 | 130.80 | 0.00 | 0.00 |
| November | 145.72 | 211.37 | 171.51 | 87.27 | 84.24 | 0.00 | 0.00 |
| December | 144.96 | 268.91 | 170.68 | 100.22 | 70.46 | 0.00 | 0.00 |
| Annual Sum or Average | 317.99 | 169.26 | 298.74 | 138.18 | 160.55 | 0.00 | 0.00 |
| Minimum of Months | 123.05 | 88.26 | 164.53 | 86.98 | 70.46 | 0.00 | 0.00 |
| Maximum of Months | 474.86 | 268.91 | 381.58 | 190.28 | 242.25 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: T NE APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 7.54 | 284.56 | 61.59 | 7.91 | 53.69 | 0.00 | 0.00 |
| February | 42.09 | 240.56 | 104.61 | 20.33 | 84.28 | 0.00 | 0.00 |
| March | 103.23 | 188.02 | 155.83 | 31.41 | 124.42 | 0.00 | 0.00 |
| April | 202.40 | 148.90 | 232.49 | 56.60 | 175.89 | 0.00 | 0.00 |
| May | 256.78 | 123.90 | 268.76 | 53.63 | 215.13 | 0.00 | 0.00 |
| June | 311.73 | 96.89 | 303.57 | 83.47 | 220.10 | 0.00 | 0.00 |
| July | 312.67 | 85.90 | 285.70 | 82.07 | 203.63 | 0.00 | 0.00 |
| August | 293.22 | 84.97 | 258.73 | 81.46 | 177.27 | 0.00 | 0.00 |
| September | 188.02 | 120.68 | 195.09 | 53.72 | 141.37 | 0.00 | 0.00 |
| October | 98.01 | 160.76 | 130.31 | 32.76 | 97.55 | 0.00 | 0.00 |
| November | 23.91 | 216.13 | 71.23 | 10.55 | 60.68 | 0.00 | 0.00 |
| December | 9.93 | 279.22 | 55.94 | 9.75 | 46.19 | 0.00 | 0.00 |
| Annual Sum or Average | 154.75 | 168.88 | 177.32 | 43.75 | 133.58 | 0.00 | 0.00 |
| Minimum of Months | 7.54 | 84.97 | 55.94 | 7.91 | 46.19 | 0.00 | 0.00 |
| Maximum of Months | 312.67 | 284.56 | 303.57 | 83.47 | 220.10 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: T N1 APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 1.18 | 181.65 | 30.02 | 0.00 | 30.02 | 0.00 | 0.00 |
| February | 10.14 | 155.91 | 46.71 | 0.00 | 46.71 | 0.00 | 0.00 |
| March | 32.91 | 121.07 | 68.83 | 0.00 | 68.83 | 0.00 | 0.00 |
| April | 68.12 | 95.14 | 97.54 | 0.47 | 97.07 | 0.00 | 0.00 |
| May | 105.48 | 77.51 | 125.25 | 3.66 | 121.59 | 0.00 | 0.00 |
| June | 119.35 | 60.40 | 131.76 | 8.67 | 123.09 | 0.00 | 0.00 |
| July | 126.34 | 54.08 | 125.33 | 9.86 | 115.47 | 0.00 | 0.00 |
| August | 104.73 | 53.20 | 101.81 | 3.10 | 98.71 | 0.00 | 0.00 |
| September | 62.97 | 78.75 | 78.78 | 0.05 | 78.73 | 0.00 | 0.00 |
| October | 29.05 | 103.38 | 53.95 | 0.00 | 53.95 | 0.00 | 0.00 |
| November | 6.15 | 137.56 | 33.98 | 0.00 | 33.98 | 0.00 | 0.00 |
| December | 0.62 | 177.84 | 25.51 | 0.00 | 25.51 | 0.00 | 0.00 |
| Annual Sum or Average | 55.87 | 107.81 | 76.77 | 2.17 | 74.60 | 0.00 | 0.00 |
| Minimum of Months | 0.62 | 53.20 | 25.51 | 0.00 | 25.51 | 0.00 | 0.00 |
| Maximum of Months | 126.34 | 181.65 | 131.76 | 9.86 | 123.09 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: T N2 APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 1.18 | 181.65 | 30.02 | 0.00 | 30.02 | 0.00 | 0.00 |
| February | 10.13 | 155.89 | 46.71 | 0.00 | 46.71 | 0.00 | 0.00 |
| March | 32.87 | 121.00 | 68.83 | 0.00 | 68.83 | 0.00 | 0.00 |
| April | 67.96 | 95.13 | 97.54 | 0.47 | 97.07 | 0.00 | 0.00 |
| May | 105.36 | 77.44 | 125.25 | 3.66 | 121.59 | 0.00 | 0.00 |
| June | 119.20 | 60.37 | 131.76 | 8.67 | 123.09 | 0.00 | 0.00 |
| July | 126.30 | 54.01 | 125.33 | 9.86 | 115.47 | 0.00 | 0.00 |
| August | 104.65 | 53.15 | 101.81 | 3.10 | 98.71 | 0.00 | 0.00 |
| September | 62.89 | 78.62 | 78.78 | 0.05 | 78.73 | 0.00 | 0.00 |
| October | 28.99 | 103.31 | 53.95 | 0.00 | 53.95 | 0.00 | 0.00 |
| November | 6.14 | 137.55 | 33.98 | 0.00 | 33.98 | 0.00 | 0.00 |
| December | 0.62 | 177.84 | 25.51 | 0.00 | 25.51 | 0.00 | 0.00 |
| Annual Sum or Average | 55.80 | 107.77 | 76.77 | 2.17 | 74.60 | 0.00 | 0.00 |
| Minimum of Months | 0.62 | 53.15 | 25.51 | 0.00 | 25.51 | 0.00 | 0.00 |
| Maximum of Months | 126.30 | 181.65 | 131.76 | 9.86 | 123.09 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: T S1 APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 116.59 | 164.01 | 132.96 | 79.07 | 53.89 | 0.00 | 0.00 |
| February | 207.87 | 144.17 | 206.86 | 129.16 | 77.70 | 0.00 | 0.00 |
| March | 227.26 | 121.46 | 216.23 | 113.83 | 102.40 | 0.00 | 0.00 |
| April | 258.39 | 101.73 | 232.13 | 101.06 | 131.07 | 0.00 | 0.00 |
| May | 239.91 | 84.20 | 213.31 | 64.60 | 148.71 | 0.00 | 0.00 |
| June | 222.04 | 66.92 | 194.60 | 52.84 | 141.76 | 0.00 | 0.00 |
| July | 266.19 | 60.25 | 212.64 | 78.70 | 133.94 | 0.00 | 0.00 |
| August | 290.07 | 58.23 | 224.67 | 103.49 | 121.18 | 0.00 | 0.00 |
| September | 303.82 | 81.02 | 249.27 | 136.61 | 112.66 | 0.00 | 0.00 |
| October | 249.47 | 105.69 | 222.42 | 135.22 | 87.20 | 0.00 | 0.00 |
| November | 127.64 | 130.17 | 134.27 | 76.73 | 57.54 | 0.00 | 0.00 |
| December | 135.17 | 164.98 | 140.24 | 90.47 | 49.77 | 0.00 | 0.00 |
| Annual Sum or Average | 220.39 | 106.73 | 198.18 | 96.60 | 101.58 | 0.00 | 0.00 |
| Minimum of Months | 116.59 | 58.23 | 132.96 | 52.84 | 49.77 | 0.00 | 0.00 |
| Maximum of Months | 303.82 | 164.98 | 249.27 | 136.61 | 148.71 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: T S2 APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 116.58 | 164.00 | 132.96 | 79.07 | 53.89 | 0.00 | 0.00 |
| February | 207.84 | 144.12 | 206.86 | 129.16 | 77.70 | 0.00 | 0.00 |
| March | 227.19 | 121.41 | 216.23 | 113.83 | 102.40 | 0.00 | 0.00 |
| April | 258.25 | 101.71 | 232.13 | 101.06 | 131.07 | 0.00 | 0.00 |
| May | 239.85 | 84.12 | 213.31 | 64.60 | 148.71 | 0.00 | 0.00 |
| June | 221.92 | 66.87 | 194.60 | 52.84 | 141.76 | 0.00 | 0.00 |
| July | 266.15 | 60.16 | 212.64 | 78.70 | 133.94 | 0.00 | 0.00 |
| August | 290.01 | 58.18 | 224.67 | 103.49 | 121.18 | 0.00 | 0.00 |
| September | 303.79 | 80.92 | 249.27 | 136.61 | 112.66 | 0.00 | 0.00 |
| October | 249.42 | 105.65 | 222.42 | 135.22 | 87.20 | 0.00 | 0.00 |
| November | 127.62 | 130.16 | 134.27 | 76.73 | 57.54 | 0.00 | 0.00 |
| December | 135.15 | 164.96 | 140.24 | 90.47 | 49.77 | 0.00 | 0.00 |
| Annual Sum or Average | 220.33 | 106.68 | 198.18 | 96.60 | 101.58 | 0.00 | 0.00 |
| Minimum of Months | 116.58 | 58.18 | 132.96 | 52.84 | 49.77 | 0.00 | 0.00 |
| Maximum of Months | 303.79 | 164.96 | 249.27 | 136.61 | 148.71 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: T CORRIDOR
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 2.56 | 28.32 | 7.58 | 1.90 | 5.68 | 0.00 | 0.00 |
| February | 8.78 | 24.51 | 13.89 | 4.88 | 9.01 | 0.00 | 0.00 |
| March | 17.33 | 19.87 | 20.88 | 7.54 | 13.34 | 0.00 | 0.00 |
| April | 32.50 | 16.05 | 32.38 | 13.47 | 18.91 | 0.00 | 0.00 |
| May | 35.93 | 13.82 | 34.44 | 11.99 | 22.44 | 0.00 | 0.00 |
| June | 45.66 | 11.07 | 41.23 | 17.95 | 23.28 | 0.00 | 0.00 |
| July | 44.07 | 9.94 | 38.48 | 17.33 | 21.16 | 0.00 | 0.00 |
| August | 44.55 | 9.77 | 37.65 | 18.80 | 18.85 | 0.00 | 0.00 |
| September | 29.87 | 13.57 | 27.91 | 12.88 | 15.03 | 0.00 | 0.00 |
| October | 16.69 | 17.60 | 18.32 | 7.86 | 10.46 | 0.00 | 0.00 |
| November | 4.70 | 22.35 | 8.94 | 2.53 | 6.41 | 0.00 | 0.00 |
| December | 3.27 | 28.05 | 7.30 | 2.34 | 4.96 | 0.00 | 0.00 |
| Annual Sum or Average | 23.90 | 17.88 | 24.13 | 9.98 | 14.15 | 0.00 | 0.00 |
| Minimum of Months | 2.56 | 9.77 | 7.30 | 1.90 | 4.96 | 0.00 | 0.00 |
| Maximum of Months | 45.66 | 28.32 | 41.23 | 18.80 | 23.28 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: G CORRIDOR
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 8.82 | 74.51 | 22.57 | 5.65 | 16.92 | 0.00 | 0.00 |
| February | 28.92 | 64.51 | 41.38 | 14.53 | 26.85 | 0.00 | 0.00 |
| March | 55.24 | 53.00 | 62.18 | 22.45 | 39.73 | 0.00 | 0.00 |
| April | 101.82 | 42.66 | 96.44 | 40.11 | 56.32 | 0.00 | 0.00 |
| May | 110.84 | 38.44 | 102.56 | 35.71 | 66.85 | 0.00 | 0.00 |
| June | 139.08 | 31.66 | 122.78 | 53.46 | 69.33 | 0.00 | 0.00 |
| July | 133.18 | 29.23 | 114.61 | 51.60 | 63.01 | 0.00 | 0.00 |
| August | 133.58 | 29.44 | 112.14 | 56.00 | 56.14 | 0.00 | 0.00 |
| September | 89.40 | 41.04 | 83.12 | 38.36 | 44.76 | 0.00 | 0.00 |
| October | 50.22 | 51.76 | 54.57 | 23.41 | 31.16 | 0.00 | 0.00 |
| November | 15.07 | 61.61 | 26.62 | 7.54 | 19.08 | 0.00 | 0.00 |
| December | 10.74 | 75.32 | 21.75 | 6.97 | 14.78 | 0.00 | 0.00 |
| Annual Sum or Average | 73.29 | 49.36 | 71.86 | 29.71 | 42.14 | 0.00 | 0.00 |
| Minimum of Months | 8.82 | 29.23 | 21.75 | 5.65 | 14.78 | 0.00 | 0.00 |
| Maximum of Months | 139.08 | 75.32 | 122.78 | 56.00 | 69.33 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: M CORRIDOR
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 2.31 | 30.87 | 7.58 | 1.90 | 5.68 | 0.00 | 0.00 |
| February | 8.24 | 26.58 | 13.89 | 4.88 | 9.01 | 0.00 | 0.00 |
| March | 16.55 | 21.84 | 20.88 | 7.54 | 13.34 | 0.00 | 0.00 |
| April | 31.48 | 17.63 | 32.38 | 13.47 | 18.91 | 0.00 | 0.00 |
| May | 34.69 | 15.38 | 34.44 | 11.99 | 22.44 | 0.00 | 0.00 |
| June | 44.85 | 11.96 | 41.23 | 17.95 | 23.28 | 0.00 | 0.00 |
| July | 43.67 | 10.48 | 38.48 | 17.33 | 21.16 | 0.00 | 0.00 |
| August | 44.15 | 10.32 | 37.65 | 18.80 | 18.85 | 0.00 | 0.00 |
| September | 28.88 | 15.16 | 27.91 | 12.88 | 15.03 | 0.00 | 0.00 |
| October | 15.56 | 20.22 | 18.32 | 7.86 | 10.46 | 0.00 | 0.00 |
| November | 4.29 | 24.76 | 8.94 | 2.53 | 6.41 | 0.00 | 0.00 |
| December | 3.00 | 30.62 | 7.30 | 2.34 | 4.96 | 0.00 | 0.00 |
| Annual Sum or Average | 23.21 | 19.62 | 24.13 | 9.98 | 14.15 | 0.00 | 0.00 |
| Minimum of Months | 2.31 | 10.32 | 7.30 | 1.90 | 4.96 | 0.00 | 0.00 |
| Maximum of Months | 44.85 | 30.87 | 41.23 | 18.80 | 23.28 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: G SW APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.345282E+09 | 0.716945E+09 | 0.446167E+09 | 0.238526E+09 | 0.207642E+09 | 0.00 | 0.00 |
| February | 0.610875E+09 | 0.559871E+09 | 0.644951E+09 | 0.366286E+09 | 0.278664E+09 | 0.00 | 0.00 |
| March | 0.819841E+09 | 0.509430E+09 | 0.804519E+09 | 0.381020E+09 | 0.423499E+09 | 0.00 | 0.00 |
| April | 0.103503E+10 | 0.402161E+09 | 0.932758E+09 | 0.388280E+09 | 0.544477E+09 | 0.00 | 0.00 |
| May | 0.115014E+10 | 0.357913E+09 | 0.101260E+10 | 0.352500E+09 | 0.660105E+09 | 0.00 | 0.00 |
| June | 0.105038E+10 | 0.278964E+09 | 0.914955E+09 | 0.296385E+09 | 0.618571E+09 | 0.00 | 0.00 |
| July | 0.136203E+10 | 0.265569E+09 | 0.109456E+10 | 0.487183E+09 | 0.607380E+09 | 0.00 | 0.00 |
| August | 0.131838E+10 | 0.262315E+09 | 0.103515E+10 | 0.498257E+09 | 0.536890E+09 | 0.00 | 0.00 |
| September | 0.117590E+10 | 0.364167E+09 | 0.988933E+09 | 0.519020E+09 | 0.469913E+09 | 0.00 | 0.00 |
| October | 0.853032E+09 | 0.484022E+09 | 0.797470E+09 | 0.444696E+09 | 0.352774E+09 | 0.00 | 0.00 |
| November | 0.385815E+09 | 0.558078E+09 | 0.445160E+09 | 0.226548E+09 | 0.218612E+09 | 0.00 | 0.00 |
| December | 0.403500E+09 | 0.724198E+09 | 0.460782E+09 | 0.272177E+09 | 0.188605E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.105102E+11 | 0.548363E+10 | 0.957801E+10 | 0.447088E+10 | 0.510713E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.345282E+09 | 0.262315E+09 | 0.445160E+09 | 0.226548E+09 | 0.188605E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.136203E+10 | 0.724198E+09 | 0.109456E+10 | 0.519020E+09 | 0.660105E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: G NW APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 31969334.60 | 0.760550E+09 | 0.170451E+09 | 26738428.29 | 0.143713E+09 | 0.00 | 0.00 |
| February | 0.125404E+09 | 0.583403E+09 | 0.257501E+09 | 53823828.75 | 0.203677E+09 | 0.00 | 0.00 |
| March | 0.295697E+09 | 0.504247E+09 | 0.409705E+09 | 76143762.90 | 0.333561E+09 | 0.00 | 0.00 |
| April | 0.546753E+09 | 0.379481E+09 | 0.583900E+09 | 0.127547E+09 | 0.456353E+09 | 0.00 | 0.00 |
| May | 0.801551E+09 | 0.328636E+09 | 0.776736E+09 | 0.189275E+09 | 0.587461E+09 | 0.00 | 0.00 |
| June | 0.789306E+09 | 0.255047E+09 | 0.752080E+09 | 0.181906E+09 | 0.570174E+09 | 0.00 | 0.00 |
| July | 0.988128E+09 | 0.246411E+09 | 0.860713E+09 | 0.302804E+09 | 0.557909E+09 | 0.00 | 0.00 |
| August | 0.821573E+09 | 0.244595E+09 | 0.706095E+09 | 0.229386E+09 | 0.476709E+09 | 0.00 | 0.00 |
| September | 0.554837E+09 | 0.350570E+09 | 0.547037E+09 | 0.165064E+09 | 0.381972E+09 | 0.00 | 0.00 |
| October | 0.267402E+09 | 0.459258E+09 | 0.346247E+09 | 82533136.91 | 0.263714E+09 | 0.00 | 0.00 |
| November | 69230400.64 | 0.570208E+09 | 0.185232E+09 | 27672977.77 | 0.157559E+09 | 0.00 | 0.00 |
| December | 39515810.37 | 0.755674E+09 | 0.153483E+09 | 29873663.51 | 0.123609E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.533137E+10 | 0.543808E+10 | 0.574918E+10 | 0.149277E+10 | 0.425641E+10 | 0.00 | 0.00 |
| Minimum of Months | 31969334.60 | 0.244595E+09 | 0.153483E+09 | 26738428.29 | 0.123609E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.988128E+09 | 0.760550E+09 | 0.860713E+09 | 0.302804E+09 | 0.587461E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: OFFICE
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.357910E+09 | 0.619741E+09 | 0.440688E+09 | 0.232964E+09 | 0.207724E+09 | 0.00 | 0.00 |
| February | 0.622300E+09 | 0.508817E+09 | 0.640513E+09 | 0.361642E+09 | 0.278871E+09 | 0.00 | 0.00 |
| March | 0.830140E+09 | 0.496356E+09 | 0.812202E+09 | 0.389008E+09 | 0.423194E+09 | 0.00 | 0.00 |
| April | 0.104225E+10 | 0.401708E+09 | 0.951471E+09 | 0.407449E+09 | 0.544022E+09 | 0.00 | 0.00 |
| May | 0.105249E+10 | 0.377229E+09 | 0.955709E+09 | 0.306873E+09 | 0.648836E+09 | 0.00 | 0.00 |
| June | 0.106852E+10 | 0.302544E+09 | 0.949727E+09 | 0.330832E+09 | 0.618895E+09 | 0.00 | 0.00 |
| July | 0.119442E+10 | 0.295056E+09 | 0.999079E+09 | 0.404194E+09 | 0.594885E+09 | 0.00 | 0.00 |
| August | 0.125579E+10 | 0.299726E+09 | 0.102204E+10 | 0.487057E+09 | 0.534979E+09 | 0.00 | 0.00 |
| September | 0.109114E+10 | 0.397448E+09 | 0.947580E+09 | 0.493204E+09 | 0.454377E+09 | 0.00 | 0.00 |
| October | 0.844135E+09 | 0.511103E+09 | 0.800234E+09 | 0.449896E+09 | 0.350338E+09 | 0.00 | 0.00 |
| November | 0.386706E+09 | 0.543859E+09 | 0.444548E+09 | 0.226210E+09 | 0.218338E+09 | 0.00 | 0.00 |
| December | 0.409924E+09 | 0.655033E+09 | 0.457139E+09 | 0.268429E+09 | 0.188711E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.101557E+11 | 0.540862E+10 | 0.942093E+10 | 0.435776E+10 | 0.506317E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.357910E+09 | 0.295056E+09 | 0.440688E+09 | 0.226210E+09 | 0.188711E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.125579E+10 | 0.655033E+09 | 0.102204E+10 | 0.493204E+09 | 0.648836E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: G NE APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 21414117.66 | 0.757369E+09 | 0.164972E+09 | 21176855.29 | 0.143795E+09 | 0.00 | 0.00 |
| February | 0.108316E+09 | 0.573612E+09 | 0.253063E+09 | 49179775.95 | 0.203883E+09 | 0.00 | 0.00 |
| March | 0.292901E+09 | 0.491047E+09 | 0.417388E+09 | 84131832.55 | 0.333256E+09 | 0.00 | 0.00 |
| April | 0.560844E+09 | 0.365830E+09 | 0.602613E+09 | 0.146715E+09 | 0.455898E+09 | 0.00 | 0.00 |
| May | 0.725352E+09 | 0.322057E+09 | 0.719840E+09 | 0.143648E+09 | 0.576192E+09 | 0.00 | 0.00 |
| June | 0.833389E+09 | 0.253578E+09 | 0.786852E+09 | 0.216354E+09 | 0.570498E+09 | 0.00 | 0.00 |
| July | 0.855742E+09 | 0.237392E+09 | 0.765229E+09 | 0.219815E+09 | 0.545414E+09 | 0.00 | 0.00 |
| August | 0.797284E+09 | 0.237140E+09 | 0.692984E+09 | 0.218186E+09 | 0.474798E+09 | 0.00 | 0.00 |
| September | 0.486726E+09 | 0.336764E+09 | 0.505684E+09 | 0.139248E+09 | 0.366436E+09 | 0.00 | 0.00 |
| October | 0.262195E+09 | 0.447566E+09 | 0.349012E+09 | 87733384.55 | 0.261279E+09 | 0.00 | 0.00 |
| November | 63195781.76 | 0.565965E+09 | 0.184620E+09 | 27335106.39 | 0.157285E+09 | 0.00 | 0.00 |
| December | 27183792.93 | 0.749724E+09 | 0.149840E+09 | 26125280.48 | 0.123715E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.503454E+10 | 0.533804E+10 | 0.559210E+10 | 0.137965E+10 | 0.421245E+10 | 0.00 | 0.00 |
| Minimum of Months | 21414117.66 | 0.237140E+09 | 0.149840E+09 | 21176855.29 | 0.123715E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.855742E+09 | 0.757369E+09 | 0.786852E+09 | 0.219815E+09 | 0.576192E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: G N1 APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 3459660.93 | 0.484662E+09 | 80398594.49 | 0.00 | 80398594.49 | 0.00 | 0.00 |
| February | 26886260.52 | 0.372470E+09 | 0.112996E+09 | 0.00 | 0.112996E+09 | 0.00 | 0.00 |
| March | 94784922.47 | 0.317239E+09 | 0.184345E+09 | 3676.65 | 0.184341E+09 | 0.00 | 0.00 |
| April | 0.192726E+09 | 0.233713E+09 | 0.252834E+09 | 1224735.97 | 0.251609E+09 | 0.00 | 0.00 |
| May | 0.298367E+09 | 0.202687E+09 | 0.335468E+09 | 9808992.16 | 0.325659E+09 | 0.00 | 0.00 |
| June | 0.320436E+09 | 0.156510E+09 | 0.341516E+09 | 22472037.20 | 0.319044E+09 | 0.00 | 0.00 |
| July | 0.346256E+09 | 0.147708E+09 | 0.335695E+09 | 26421681.49 | 0.309274E+09 | 0.00 | 0.00 |
| August | 0.284853E+09 | 0.146453E+09 | 0.272693E+09 | 8316268.31 | 0.264376E+09 | 0.00 | 0.00 |
| September | 0.160520E+09 | 0.219044E+09 | 0.204209E+09 | 132190.44 | 0.204077E+09 | 0.00 | 0.00 |
| October | 74674586.91 | 0.291121E+09 | 0.144505E+09 | 0.00 | 0.144505E+09 | 0.00 | 0.00 |
| November | 15992418.15 | 0.361459E+09 | 88087644.44 | 0.00 | 88087644.44 | 0.00 | 0.00 |
| December | 1803309.37 | 0.478371E+09 | 68318055.64 | 0.00 | 68318055.64 | 0.00 | 0.00 |
| Annual Sum or Average | 0.182076E+10 | 0.341144E+10 | 0.242106E+10 | 68379582.23 | 0.235269E+10 | 0.00 | 0.00 |
| Minimum of Months | 1803309.37 | 0.146453E+09 | 68318055.64 | 0.00 | 68318055.64 | 0.00 | 0.00 |
| Maximum of Months | 0.346256E+09 | 0.484662E+09 | 0.341516E+09 | 26421681.49 | 0.325659E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: G N2 APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 3458743.57 | 0.484656E+09 | 80398594.49 | 0.00 | 80398594.49 | 0.00 | 0.00 |
| February | 26882861.08 | 0.372458E+09 | 0.112996E+09 | 0.00 | 0.112996E+09 | 0.00 | 0.00 |
| March | 94768822.00 | 0.317197E+09 | 0.184345E+09 | 3676.65 | 0.184341E+09 | 0.00 | 0.00 |
| April | 0.192624E+09 | 0.233733E+09 | 0.252834E+09 | 1224735.97 | 0.251609E+09 | 0.00 | 0.00 |
| May | 0.298432E+09 | 0.202498E+09 | 0.335468E+09 | 9808992.16 | 0.325659E+09 | 0.00 | 0.00 |
| June | 0.320167E+09 | 0.156643E+09 | 0.341516E+09 | 22472037.20 | 0.319044E+09 | 0.00 | 0.00 |
| July | 0.346326E+09 | 0.147576E+09 | 0.335695E+09 | 26421681.49 | 0.309274E+09 | 0.00 | 0.00 |
| August | 0.284811E+09 | 0.146415E+09 | 0.272693E+09 | 8316268.31 | 0.264376E+09 | 0.00 | 0.00 |
| September | 0.160559E+09 | 0.218834E+09 | 0.204209E+09 | 132190.44 | 0.204077E+09 | 0.00 | 0.00 |
| October | 74699640.47 | 0.290969E+09 | 0.144505E+09 | 0.00 | 0.144505E+09 | 0.00 | 0.00 |
| November | 15987595.37 | 0.361443E+09 | 88087644.44 | 0.00 | 88087644.44 | 0.00 | 0.00 |
| December | 1802281.83 | 0.478362E+09 | 68318055.64 | 0.00 | 68318055.64 | 0.00 | 0.00 |
| Annual Sum or Average | 0.182052E+10 | 0.341078E+10 | 0.242106E+10 | 68379582.23 | 0.235269E+10 | 0.00 | 0.00 |
| Minimum of Months | 1802281.83 | 0.146415E+09 | 68318055.64 | 0.00 | 68318055.64 | 0.00 | 0.00 |
| Maximum of Months | 0.346326E+09 | 0.484656E+09 | 0.341516E+09 | 26421681.49 | 0.325659E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: G S1 APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.317132E+09 | 0.438314E+09 | 0.356115E+09 | 0.211787E+09 | 0.144327E+09 | 0.00 | 0.00 |
| February | 0.513375E+09 | 0.344796E+09 | 0.500446E+09 | 0.312463E+09 | 0.187983E+09 | 0.00 | 0.00 |
| March | 0.623332E+09 | 0.319213E+09 | 0.579159E+09 | 0.304880E+09 | 0.274279E+09 | 0.00 | 0.00 |
| April | 0.688972E+09 | 0.254642E+09 | 0.601691E+09 | 0.261958E+09 | 0.339733E+09 | 0.00 | 0.00 |
| May | 0.654625E+09 | 0.229721E+09 | 0.571336E+09 | 0.173034E+09 | 0.398303E+09 | 0.00 | 0.00 |
| June | 0.585931E+09 | 0.177525E+09 | 0.504391E+09 | 0.136950E+09 | 0.367441E+09 | 0.00 | 0.00 |
| July | 0.723914E+09 | 0.165717E+09 | 0.569545E+09 | 0.210801E+09 | 0.358744E+09 | 0.00 | 0.00 |
| August | 0.785427E+09 | 0.161664E+09 | 0.601744E+09 | 0.277187E+09 | 0.324557E+09 | 0.00 | 0.00 |
| September | 0.788869E+09 | 0.225759E+09 | 0.646105E+09 | 0.354088E+09 | 0.292017E+09 | 0.00 | 0.00 |
| October | 0.667336E+09 | 0.306861E+09 | 0.595727E+09 | 0.362163E+09 | 0.233564E+09 | 0.00 | 0.00 |
| November | 0.333206E+09 | 0.345764E+09 | 0.348015E+09 | 0.198875E+09 | 0.149140E+09 | 0.00 | 0.00 |
| December | 0.366972E+09 | 0.444172E+09 | 0.375617E+09 | 0.242303E+09 | 0.133314E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.704909E+10 | 0.341415E+10 | 0.624989E+10 | 0.304649E+10 | 0.320340E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.317132E+09 | 0.161664E+09 | 0.348015E+09 | 0.136950E+09 | 0.133314E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.788869E+09 | 0.444172E+09 | 0.646105E+09 | 0.362163E+09 | 0.398303E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: G S2 APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.317844E+09 | 0.435547E+09 | 0.356115E+09 | 0.211787E+09 | 0.144327E+09 | 0.00 | 0.00 |
| February | 0.514068E+09 | 0.343143E+09 | 0.500446E+09 | 0.312463E+09 | 0.187983E+09 | 0.00 | 0.00 |
| March | 0.623332E+09 | 0.318943E+09 | 0.579159E+09 | 0.304880E+09 | 0.274279E+09 | 0.00 | 0.00 |
| April | 0.688144E+09 | 0.255470E+09 | 0.601691E+09 | 0.261958E+09 | 0.339733E+09 | 0.00 | 0.00 |
| May | 0.653072E+09 | 0.231479E+09 | 0.571336E+09 | 0.173034E+09 | 0.398303E+09 | 0.00 | 0.00 |
| June | 0.584506E+09 | 0.178926E+09 | 0.504391E+09 | 0.136950E+09 | 0.367441E+09 | 0.00 | 0.00 |
| July | 0.722932E+09 | 0.166680E+09 | 0.569545E+09 | 0.210801E+09 | 0.358744E+09 | 0.00 | 0.00 |
| August | 0.784311E+09 | 0.162923E+09 | 0.601744E+09 | 0.277187E+09 | 0.324557E+09 | 0.00 | 0.00 |
| September | 0.788039E+09 | 0.226941E+09 | 0.646105E+09 | 0.354088E+09 | 0.292017E+09 | 0.00 | 0.00 |
| October | 0.666324E+09 | 0.308919E+09 | 0.595727E+09 | 0.362163E+09 | 0.233564E+09 | 0.00 | 0.00 |
| November | 0.333002E+09 | 0.345879E+09 | 0.348015E+09 | 0.198875E+09 | 0.149140E+09 | 0.00 | 0.00 |
| December | 0.367453E+09 | 0.442141E+09 | 0.375617E+09 | 0.242303E+09 | 0.133314E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.704303E+10 | 0.341699E+10 | 0.624989E+10 | 0.304649E+10 | 0.320340E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.317844E+09 | 0.162923E+09 | 0.348015E+09 | 0.136950E+09 | 0.133314E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.788039E+09 | 0.442141E+09 | 0.646105E+09 | 0.362163E+09 | 0.398303E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: M SW APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.334821E+09 | 0.750126E+09 | 0.446167E+09 | 0.238526E+09 | 0.207642E+09 | 0.00 | 0.00 |
| February | 0.591629E+09 | 0.593961E+09 | 0.644951E+09 | 0.366286E+09 | 0.278664E+09 | 0.00 | 0.00 |
| March | 0.789060E+09 | 0.560745E+09 | 0.804519E+09 | 0.381020E+09 | 0.423499E+09 | 0.00 | 0.00 |
| April | 0.990086E+09 | 0.458584E+09 | 0.932758E+09 | 0.388280E+09 | 0.544477E+09 | 0.00 | 0.00 |
| May | 0.111007E+10 | 0.400063E+09 | 0.101260E+10 | 0.352500E+09 | 0.660105E+09 | 0.00 | 0.00 |
| June | 0.102527E+10 | 0.300330E+09 | 0.914955E+09 | 0.296385E+09 | 0.618571E+09 | 0.00 | 0.00 |
| July | 0.134810E+10 | 0.273732E+09 | 0.109456E+10 | 0.487183E+09 | 0.607380E+09 | 0.00 | 0.00 |
| August | 0.130812E+10 | 0.268224E+09 | 0.103515E+10 | 0.498257E+09 | 0.536890E+09 | 0.00 | 0.00 |
| September | 0.116500E+10 | 0.374786E+09 | 0.988933E+09 | 0.519020E+09 | 0.469913E+09 | 0.00 | 0.00 |
| October | 0.836604E+09 | 0.511929E+09 | 0.797470E+09 | 0.444696E+09 | 0.352774E+09 | 0.00 | 0.00 |
| November | 0.375746E+09 | 0.582995E+09 | 0.445160E+09 | 0.226548E+09 | 0.218612E+09 | 0.00 | 0.00 |
| December | 0.393919E+09 | 0.753586E+09 | 0.460782E+09 | 0.272177E+09 | 0.188605E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.102684E+11 | 0.582906E+10 | 0.957801E+10 | 0.447088E+10 | 0.510713E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.334821E+09 | 0.268224E+09 | 0.445160E+09 | 0.226548E+09 | 0.188605E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.134810E+10 | 0.753586E+09 | 0.109456E+10 | 0.519020E+09 | 0.660105E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: M NW APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 28611934.59 | 0.796442E+09 | 0.170451E+09 | 26738428.29 | 0.143713E+09 | 0.00 | 0.00 |
| February | 0.115192E+09 | 0.616306E+09 | 0.257501E+09 | 53823828.75 | 0.203677E+09 | 0.00 | 0.00 |
| March | 0.275852E+09 | 0.543802E+09 | 0.409705E+09 | 76143762.90 | 0.333561E+09 | 0.00 | 0.00 |
| April | 0.508162E+09 | 0.428797E+09 | 0.583900E+09 | 0.127547E+09 | 0.456353E+09 | 0.00 | 0.00 |
| May | 0.750021E+09 | 0.380058E+09 | 0.776736E+09 | 0.189275E+09 | 0.587461E+09 | 0.00 | 0.00 |
| June | 0.756575E+09 | 0.280184E+09 | 0.752080E+09 | 0.181906E+09 | 0.570174E+09 | 0.00 | 0.00 |
| July | 0.973167E+09 | 0.256120E+09 | 0.860713E+09 | 0.302804E+09 | 0.557909E+09 | 0.00 | 0.00 |
| August | 0.810640E+09 | 0.252792E+09 | 0.706095E+09 | 0.229386E+09 | 0.476709E+09 | 0.00 | 0.00 |
| September | 0.540556E+09 | 0.370414E+09 | 0.547037E+09 | 0.165064E+09 | 0.381972E+09 | 0.00 | 0.00 |
| October | 0.252099E+09 | 0.491547E+09 | 0.346247E+09 | 82533136.91 | 0.263714E+09 | 0.00 | 0.00 |
| November | 63871939.61 | 0.595561E+09 | 0.185232E+09 | 27672977.77 | 0.157559E+09 | 0.00 | 0.00 |
| December | 36730273.74 | 0.785417E+09 | 0.153483E+09 | 29873663.51 | 0.123609E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.511148E+10 | 0.579744E+10 | 0.574918E+10 | 0.149277E+10 | 0.425641E+10 | 0.00 | 0.00 |
| Minimum of Months | 28611934.59 | 0.252792E+09 | 0.153483E+09 | 26738428.29 | 0.123609E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.973167E+09 | 0.796442E+09 | 0.860713E+09 | 0.302804E+09 | 0.587461E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: M SE APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.326943E+09 | 0.749308E+09 | 0.440688E+09 | 0.232964E+09 | 0.207724E+09 | 0.00 | 0.00 |
| February | 0.583309E+09 | 0.593030E+09 | 0.640513E+09 | 0.361642E+09 | 0.278871E+09 | 0.00 | 0.00 |
| March | 0.792747E+09 | 0.555650E+09 | 0.812202E+09 | 0.389008E+09 | 0.423194E+09 | 0.00 | 0.00 |
| April | 0.100234E+10 | 0.445920E+09 | 0.951471E+09 | 0.407449E+09 | 0.544022E+09 | 0.00 | 0.00 |
| May | 0.103006E+10 | 0.389760E+09 | 0.955709E+09 | 0.306873E+09 | 0.648836E+09 | 0.00 | 0.00 |
| June | 0.106583E+10 | 0.290500E+09 | 0.949727E+09 | 0.330832E+09 | 0.618895E+09 | 0.00 | 0.00 |
| July | 0.121167E+10 | 0.261887E+09 | 0.999079E+09 | 0.404194E+09 | 0.594885E+09 | 0.00 | 0.00 |
| August | 0.127733E+10 | 0.253392E+09 | 0.102204E+10 | 0.487057E+09 | 0.534979E+09 | 0.00 | 0.00 |
| September | 0.109907E+10 | 0.364842E+09 | 0.947580E+09 | 0.493204E+09 | 0.454377E+09 | 0.00 | 0.00 |
| October | 0.837042E+09 | 0.507458E+09 | 0.800234E+09 | 0.449896E+09 | 0.350338E+09 | 0.00 | 0.00 |
| November | 0.373285E+09 | 0.583126E+09 | 0.444548E+09 | 0.226210E+09 | 0.218338E+09 | 0.00 | 0.00 |
| December | 0.386365E+09 | 0.752652E+09 | 0.457139E+09 | 0.268429E+09 | 0.188711E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.998600E+10 | 0.574753E+10 | 0.942093E+10 | 0.435776E+10 | 0.506317E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.326943E+09 | 0.253392E+09 | 0.440688E+09 | 0.226210E+09 | 0.188711E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.127733E+10 | 0.752652E+09 | 0.102204E+10 | 0.493204E+09 | 0.648836E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: M NE APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 18352349.10 | 0.793482E+09 | 0.164972E+09 | 21176855.29 | 0.143795E+09 | 0.00 | 0.00 |
| February | 98090260.23 | 0.606605E+09 | 0.253063E+09 | 49179775.95 | 0.203883E+09 | 0.00 | 0.00 |
| March | 0.272558E+09 | 0.529914E+09 | 0.417388E+09 | 84131832.55 | 0.333256E+09 | 0.00 | 0.00 |
| April | 0.518875E+09 | 0.414959E+09 | 0.602613E+09 | 0.146715E+09 | 0.455898E+09 | 0.00 | 0.00 |
| May | 0.672823E+09 | 0.373242E+09 | 0.719840E+09 | 0.143648E+09 | 0.576192E+09 | 0.00 | 0.00 |
| June | 0.803157E+09 | 0.276903E+09 | 0.786852E+09 | 0.216354E+09 | 0.570498E+09 | 0.00 | 0.00 |
| July | 0.840417E+09 | 0.247986E+09 | 0.765229E+09 | 0.219815E+09 | 0.545414E+09 | 0.00 | 0.00 |
| August | 0.786418E+09 | 0.244732E+09 | 0.692984E+09 | 0.218186E+09 | 0.474798E+09 | 0.00 | 0.00 |
| September | 0.471701E+09 | 0.357023E+09 | 0.505684E+09 | 0.139248E+09 | 0.366436E+09 | 0.00 | 0.00 |
| October | 0.245565E+09 | 0.480066E+09 | 0.349012E+09 | 87733384.55 | 0.261279E+09 | 0.00 | 0.00 |
| November | 57545247.49 | 0.591347E+09 | 0.184620E+09 | 27335106.39 | 0.157285E+09 | 0.00 | 0.00 |
| December | 24582229.13 | 0.779940E+09 | 0.149840E+09 | 26125280.48 | 0.123715E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.481008E+10 | 0.569620E+10 | 0.559210E+10 | 0.137965E+10 | 0.421245E+10 | 0.00 | 0.00 |
| Minimum of Months | 18352349.10 | 0.244732E+09 | 0.149840E+09 | 21176855.29 | 0.123715E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.840417E+09 | 0.793482E+09 | 0.786852E+09 | 0.219815E+09 | 0.576192E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: M N1 APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 2666214.41 | 0.506631E+09 | 80398594.49 | 0.00 | 80398594.49 | 0.00 | 0.00 |
| February | 22620242.61 | 0.393811E+09 | 0.112996E+09 | 0.00 | 0.112996E+09 | 0.00 | 0.00 |
| March | 84865496.98 | 0.342999E+09 | 0.184345E+09 | 3676.65 | 0.184341E+09 | 0.00 | 0.00 |
| April | 0.170607E+09 | 0.267244E+09 | 0.252834E+09 | 1224735.97 | 0.251609E+09 | 0.00 | 0.00 |
| May | 0.270199E+09 | 0.232287E+09 | 0.335468E+09 | 9808992.16 | 0.325659E+09 | 0.00 | 0.00 |
| June | 0.304832E+09 | 0.168714E+09 | 0.341516E+09 | 22472037.20 | 0.319044E+09 | 0.00 | 0.00 |
| July | 0.340043E+09 | 0.152113E+09 | 0.335695E+09 | 26421681.49 | 0.309274E+09 | 0.00 | 0.00 |
| August | 0.280595E+09 | 0.150012E+09 | 0.272693E+09 | 8316268.31 | 0.264376E+09 | 0.00 | 0.00 |
| September | 0.154353E+09 | 0.229342E+09 | 0.204209E+09 | 132190.44 | 0.204077E+09 | 0.00 | 0.00 |
| October | 65778158.58 | 0.316697E+09 | 0.144505E+09 | 0.00 | 0.144505E+09 | 0.00 | 0.00 |
| November | 13344361.21 | 0.379300E+09 | 88087644.44 | 0.00 | 88087644.44 | 0.00 | 0.00 |
| December | 1318131.38 | 0.497310E+09 | 68318055.64 | 0.00 | 68318055.64 | 0.00 | 0.00 |
| Annual Sum or Average | 0.171122E+10 | 0.363646E+10 | 0.242106E+10 | 68379582.23 | 0.235269E+10 | 0.00 | 0.00 |
| Minimum of Months | 1318131.38 | 0.150012E+09 | 68318055.64 | 0.00 | 68318055.64 | 0.00 | 0.00 |
| Maximum of Months | 0.340043E+09 | 0.506631E+09 | 0.341516E+09 | 26421681.49 | 0.325659E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: M N2 APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 2664984.95 | 0.506621E+09 | 80398594.49 | 0.00 | 80398594.49 | 0.00 | 0.00 |
| February | 22613631.72 | 0.393793E+09 | 0.112996E+09 | 0.00 | 0.112996E+09 | 0.00 | 0.00 |
| March | 84830125.85 | 0.342895E+09 | 0.184345E+09 | 3676.65 | 0.184341E+09 | 0.00 | 0.00 |
| April | 0.170285E+09 | 0.267533E+09 | 0.252834E+09 | 1224735.97 | 0.251609E+09 | 0.00 | 0.00 |
| May | 0.270164E+09 | 0.232200E+09 | 0.335468E+09 | 9808992.16 | 0.325659E+09 | 0.00 | 0.00 |
| June | 0.304758E+09 | 0.168703E+09 | 0.341516E+09 | 22472037.20 | 0.319044E+09 | 0.00 | 0.00 |
| July | 0.340044E+09 | 0.152051E+09 | 0.335695E+09 | 26421681.49 | 0.309274E+09 | 0.00 | 0.00 |
| August | 0.280555E+09 | 0.149977E+09 | 0.272693E+09 | 8316268.31 | 0.264376E+09 | 0.00 | 0.00 |
| September | 0.154347E+09 | 0.229235E+09 | 0.204209E+09 | 132190.44 | 0.204077E+09 | 0.00 | 0.00 |
| October | 65724277.25 | 0.316692E+09 | 0.144505E+09 | 0.00 | 0.144505E+09 | 0.00 | 0.00 |
| November | 13335295.03 | 0.379284E+09 | 88087644.44 | 0.00 | 88087644.44 | 0.00 | 0.00 |
| December | 1316992.01 | 0.497300E+09 | 68318055.64 | 0.00 | 68318055.64 | 0.00 | 0.00 |
| Annual Sum or Average | 0.171064E+10 | 0.363629E+10 | 0.242106E+10 | 68379582.23 | 0.235269E+10 | 0.00 | 0.00 |
| Minimum of Months | 1316992.01 | 0.149977E+09 | 68318055.64 | 0.00 | 68318055.64 | 0.00 | 0.00 |
| Maximum of Months | 0.340044E+09 | 0.506621E+09 | 0.341516E+09 | 26421681.49 | 0.325659E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: M S1 APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.310177E+09 | 0.457692E+09 | 0.356115E+09 | 0.211787E+09 | 0.144327E+09 | 0.00 | 0.00 |
| February | 0.500917E+09 | 0.366807E+09 | 0.500446E+09 | 0.312463E+09 | 0.187983E+09 | 0.00 | 0.00 |
| March | 0.603515E+09 | 0.356801E+09 | 0.579159E+09 | 0.304880E+09 | 0.274279E+09 | 0.00 | 0.00 |
| April | 0.662940E+09 | 0.292464E+09 | 0.601691E+09 | 0.261958E+09 | 0.339733E+09 | 0.00 | 0.00 |
| May | 0.636050E+09 | 0.251443E+09 | 0.571336E+09 | 0.173034E+09 | 0.398303E+09 | 0.00 | 0.00 |
| June | 0.575117E+09 | 0.187374E+09 | 0.504391E+09 | 0.136950E+09 | 0.367441E+09 | 0.00 | 0.00 |
| July | 0.717874E+09 | 0.169527E+09 | 0.569545E+09 | 0.210801E+09 | 0.358744E+09 | 0.00 | 0.00 |
| August | 0.780942E+09 | 0.164068E+09 | 0.601744E+09 | 0.277187E+09 | 0.324557E+09 | 0.00 | 0.00 |
| September | 0.783966E+09 | 0.230346E+09 | 0.646105E+09 | 0.354088E+09 | 0.292017E+09 | 0.00 | 0.00 |
| October | 0.657710E+09 | 0.324048E+09 | 0.595727E+09 | 0.362163E+09 | 0.233564E+09 | 0.00 | 0.00 |
| November | 0.326087E+09 | 0.363244E+09 | 0.348015E+09 | 0.198875E+09 | 0.149140E+09 | 0.00 | 0.00 |
| December | 0.360002E+09 | 0.463388E+09 | 0.375617E+09 | 0.242303E+09 | 0.133314E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.691530E+10 | 0.362720E+10 | 0.624989E+10 | 0.304649E+10 | 0.320340E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.310177E+09 | 0.164068E+09 | 0.348015E+09 | 0.136950E+09 | 0.133314E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.783966E+09 | 0.463388E+09 | 0.646105E+09 | 0.362163E+09 | 0.398303E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: M S2 APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.310171E+09 | 0.457671E+09 | 0.356115E+09 | 0.211787E+09 | 0.144327E+09 | 0.00 | 0.00 |
| February | 0.500896E+09 | 0.366757E+09 | 0.500446E+09 | 0.312463E+09 | 0.187983E+09 | 0.00 | 0.00 |
| March | 0.603425E+09 | 0.356821E+09 | 0.579159E+09 | 0.304880E+09 | 0.274279E+09 | 0.00 | 0.00 |
| April | 0.662706E+09 | 0.292655E+09 | 0.601691E+09 | 0.261958E+09 | 0.339733E+09 | 0.00 | 0.00 |
| May | 0.636045E+09 | 0.251347E+09 | 0.571336E+09 | 0.173034E+09 | 0.398303E+09 | 0.00 | 0.00 |
| June | 0.575061E+09 | 0.187354E+09 | 0.504391E+09 | 0.136950E+09 | 0.367441E+09 | 0.00 | 0.00 |
| July | 0.717867E+09 | 0.169459E+09 | 0.569545E+09 | 0.210801E+09 | 0.358744E+09 | 0.00 | 0.00 |
| August | 0.780909E+09 | 0.164033E+09 | 0.601744E+09 | 0.277187E+09 | 0.324557E+09 | 0.00 | 0.00 |
| September | 0.783962E+09 | 0.230275E+09 | 0.646105E+09 | 0.354088E+09 | 0.292017E+09 | 0.00 | 0.00 |
| October | 0.657672E+09 | 0.324055E+09 | 0.595727E+09 | 0.362163E+09 | 0.233564E+09 | 0.00 | 0.00 |
| November | 0.326066E+09 | 0.363240E+09 | 0.348015E+09 | 0.198875E+09 | 0.149140E+09 | 0.00 | 0.00 |
| December | 0.359995E+09 | 0.463348E+09 | 0.375617E+09 | 0.242303E+09 | 0.133314E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.691478E+10 | 0.362701E+10 | 0.624989E+10 | 0.304649E+10 | 0.320340E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.310171E+09 | 0.164033E+09 | 0.348015E+09 | 0.136950E+09 | 0.133314E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.783962E+09 | 0.463348E+09 | 0.646105E+09 | 0.362163E+09 | 0.398303E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: T SW APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.337234E+09 | 0.719778E+09 | 0.446167E+09 | 0.238526E+09 | 0.207642E+09 | 0.00 | 0.00 |
| February | 0.592453E+09 | 0.567142E+09 | 0.644951E+09 | 0.366286E+09 | 0.278664E+09 | 0.00 | 0.00 |
| March | 0.791068E+09 | 0.520606E+09 | 0.804519E+09 | 0.381020E+09 | 0.423499E+09 | 0.00 | 0.00 |
| April | 0.995638E+09 | 0.416087E+09 | 0.932758E+09 | 0.388280E+09 | 0.544477E+09 | 0.00 | 0.00 |
| May | 0.111954E+10 | 0.354635E+09 | 0.101260E+10 | 0.352500E+09 | 0.660105E+09 | 0.00 | 0.00 |
| June | 0.102734E+10 | 0.271108E+09 | 0.914955E+09 | 0.296385E+09 | 0.618571E+09 | 0.00 | 0.00 |
| July | 0.133999E+10 | 0.254036E+09 | 0.109456E+10 | 0.487183E+09 | 0.607380E+09 | 0.00 | 0.00 |
| August | 0.130196E+10 | 0.248949E+09 | 0.103515E+10 | 0.498257E+09 | 0.536890E+09 | 0.00 | 0.00 |
| September | 0.117234E+10 | 0.333659E+09 | 0.988933E+09 | 0.519020E+09 | 0.469913E+09 | 0.00 | 0.00 |
| October | 0.849442E+09 | 0.452404E+09 | 0.797470E+09 | 0.444696E+09 | 0.352774E+09 | 0.00 | 0.00 |
| November | 0.380143E+09 | 0.547772E+09 | 0.445160E+09 | 0.226548E+09 | 0.218612E+09 | 0.00 | 0.00 |
| December | 0.395518E+09 | 0.720884E+09 | 0.460782E+09 | 0.272177E+09 | 0.188605E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.103027E+11 | 0.540706E+10 | 0.957801E+10 | 0.447088E+10 | 0.510713E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.337234E+09 | 0.248949E+09 | 0.445160E+09 | 0.226548E+09 | 0.188605E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.133999E+10 | 0.720884E+09 | 0.109456E+10 | 0.519020E+09 | 0.660105E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: T NW APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 30103536.89 | 0.764841E+09 | 0.170451E+09 | 26738428.29 | 0.143713E+09 | 0.00 | 0.00 |
| February | 0.117827E+09 | 0.590920E+09 | 0.257501E+09 | 53823828.75 | 0.203677E+09 | 0.00 | 0.00 |
| March | 0.278167E+09 | 0.516542E+09 | 0.409705E+09 | 76143762.90 | 0.333561E+09 | 0.00 | 0.00 |
| April | 0.511832E+09 | 0.399382E+09 | 0.583900E+09 | 0.127547E+09 | 0.456353E+09 | 0.00 | 0.00 |
| May | 0.766065E+09 | 0.337858E+09 | 0.776736E+09 | 0.189275E+09 | 0.587461E+09 | 0.00 | 0.00 |
| June | 0.764982E+09 | 0.254328E+09 | 0.752080E+09 | 0.181906E+09 | 0.570174E+09 | 0.00 | 0.00 |
| July | 0.970359E+09 | 0.238538E+09 | 0.860713E+09 | 0.302804E+09 | 0.557909E+09 | 0.00 | 0.00 |
| August | 0.810422E+09 | 0.234514E+09 | 0.706095E+09 | 0.229386E+09 | 0.476709E+09 | 0.00 | 0.00 |
| September | 0.555658E+09 | 0.324680E+09 | 0.547037E+09 | 0.165064E+09 | 0.381972E+09 | 0.00 | 0.00 |
| October | 0.267065E+09 | 0.441121E+09 | 0.346247E+09 | 82533136.91 | 0.263714E+09 | 0.00 | 0.00 |
| November | 67539153.56 | 0.563670E+09 | 0.185232E+09 | 27672977.77 | 0.157559E+09 | 0.00 | 0.00 |
| December | 38127613.23 | 0.752747E+09 | 0.153483E+09 | 29873663.51 | 0.123609E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.517815E+10 | 0.541914E+10 | 0.574918E+10 | 0.149277E+10 | 0.425641E+10 | 0.00 | 0.00 |
| Minimum of Months | 30103536.89 | 0.234514E+09 | 0.153483E+09 | 26738428.29 | 0.123609E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.970359E+09 | 0.764841E+09 | 0.860713E+09 | 0.302804E+09 | 0.587461E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: T SE APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.329565E+09 | 0.719035E+09 | 0.440688E+09 | 0.232964E+09 | 0.207724E+09 | 0.00 | 0.00 |
| February | 0.584286E+09 | 0.566242E+09 | 0.640513E+09 | 0.361642E+09 | 0.278871E+09 | 0.00 | 0.00 |
| March | 0.795429E+09 | 0.515881E+09 | 0.812202E+09 | 0.389008E+09 | 0.423194E+09 | 0.00 | 0.00 |
| April | 0.100997E+10 | 0.404325E+09 | 0.951471E+09 | 0.407449E+09 | 0.544022E+09 | 0.00 | 0.00 |
| May | 0.104078E+10 | 0.346943E+09 | 0.955709E+09 | 0.306873E+09 | 0.648836E+09 | 0.00 | 0.00 |
| June | 0.106762E+10 | 0.263907E+09 | 0.949727E+09 | 0.330832E+09 | 0.618895E+09 | 0.00 | 0.00 |
| July | 0.120517E+10 | 0.243612E+09 | 0.999079E+09 | 0.404194E+09 | 0.594885E+09 | 0.00 | 0.00 |
| August | 0.127187E+10 | 0.236388E+09 | 0.102204E+10 | 0.487057E+09 | 0.534979E+09 | 0.00 | 0.00 |
| September | 0.110751E+10 | 0.324565E+09 | 0.947580E+09 | 0.493204E+09 | 0.454377E+09 | 0.00 | 0.00 |
| October | 0.850026E+09 | 0.448842E+09 | 0.800234E+09 | 0.449896E+09 | 0.350338E+09 | 0.00 | 0.00 |
| November | 0.377718E+09 | 0.547878E+09 | 0.444548E+09 | 0.226210E+09 | 0.218338E+09 | 0.00 | 0.00 |
| December | 0.388252E+09 | 0.720256E+09 | 0.457139E+09 | 0.268429E+09 | 0.188711E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.100282E+11 | 0.533787E+10 | 0.942093E+10 | 0.435776E+10 | 0.506317E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.329565E+09 | 0.236388E+09 | 0.440688E+09 | 0.226210E+09 | 0.188711E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.127187E+10 | 0.720256E+09 | 0.102204E+10 | 0.493204E+09 | 0.648836E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: T NE APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 20203368.66 | 0.762178E+09 | 0.164972E+09 | 21176855.29 | 0.143795E+09 | 0.00 | 0.00 |
| February | 0.101834E+09 | 0.581962E+09 | 0.253063E+09 | 49179775.95 | 0.203883E+09 | 0.00 | 0.00 |
| March | 0.276486E+09 | 0.503586E+09 | 0.417388E+09 | 84131832.55 | 0.333256E+09 | 0.00 | 0.00 |
| April | 0.524625E+09 | 0.385943E+09 | 0.602613E+09 | 0.146715E+09 | 0.455898E+09 | 0.00 | 0.00 |
| May | 0.687752E+09 | 0.331845E+09 | 0.719840E+09 | 0.143648E+09 | 0.576192E+09 | 0.00 | 0.00 |
| June | 0.807992E+09 | 0.251152E+09 | 0.786852E+09 | 0.216354E+09 | 0.570498E+09 | 0.00 | 0.00 |
| July | 0.837458E+09 | 0.230083E+09 | 0.765229E+09 | 0.219815E+09 | 0.545414E+09 | 0.00 | 0.00 |
| August | 0.785350E+09 | 0.227591E+09 | 0.692984E+09 | 0.218186E+09 | 0.474798E+09 | 0.00 | 0.00 |
| September | 0.487338E+09 | 0.312803E+09 | 0.505684E+09 | 0.139248E+09 | 0.366436E+09 | 0.00 | 0.00 |
| October | 0.262523E+09 | 0.430588E+09 | 0.349012E+09 | 87733384.55 | 0.261279E+09 | 0.00 | 0.00 |
| November | 61978154.95 | 0.560200E+09 | 0.184620E+09 | 27335106.39 | 0.157285E+09 | 0.00 | 0.00 |
| December | 26586531.87 | 0.747871E+09 | 0.149840E+09 | 26125280.48 | 0.123715E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.488012E+10 | 0.532580E+10 | 0.559210E+10 | 0.137965E+10 | 0.421245E+10 | 0.00 | 0.00 |
| Minimum of Months | 20203368.66 | 0.227591E+09 | 0.149840E+09 | 21176855.29 | 0.123715E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.837458E+09 | 0.762178E+09 | 0.786852E+09 | 0.219815E+09 | 0.576192E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: T N1 APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 3153945.28 | 0.486533E+09 | 80398594.49 | 0.00 | 80398594.49 | 0.00 | 0.00 |
| February | 24523409.10 | 0.377178E+09 | 0.112996E+09 | 0.00 | 0.112996E+09 | 0.00 | 0.00 |
| March | 88157713.86 | 0.324264E+09 | 0.184345E+09 | 3676.65 | 0.184341E+09 | 0.00 | 0.00 |
| April | 0.176559E+09 | 0.246611E+09 | 0.252834E+09 | 1224735.97 | 0.251609E+09 | 0.00 | 0.00 |
| May | 0.282509E+09 | 0.207604E+09 | 0.335468E+09 | 9808992.16 | 0.325659E+09 | 0.00 | 0.00 |
| June | 0.309365E+09 | 0.156550E+09 | 0.341516E+09 | 22472037.20 | 0.319044E+09 | 0.00 | 0.00 |
| July | 0.338378E+09 | 0.144857E+09 | 0.335695E+09 | 26421681.49 | 0.309274E+09 | 0.00 | 0.00 |
| August | 0.280506E+09 | 0.142485E+09 | 0.272693E+09 | 8316268.31 | 0.264376E+09 | 0.00 | 0.00 |
| September | 0.163209E+09 | 0.204109E+09 | 0.204209E+09 | 132190.44 | 0.204077E+09 | 0.00 | 0.00 |
| October | 77803324.01 | 0.276885E+09 | 0.144505E+09 | 0.00 | 0.144505E+09 | 0.00 | 0.00 |
| November | 15935730.91 | 0.356563E+09 | 88087644.44 | 0.00 | 88087644.44 | 0.00 | 0.00 |
| December | 1666411.70 | 0.476340E+09 | 68318055.64 | 0.00 | 68318055.64 | 0.00 | 0.00 |
| Annual Sum or Average | 0.176177E+10 | 0.339998E+10 | 0.242106E+10 | 68379582.23 | 0.235269E+10 | 0.00 | 0.00 |
| Minimum of Months | 1666411.70 | 0.142485E+09 | 68318055.64 | 0.00 | 68318055.64 | 0.00 | 0.00 |
| Maximum of Months | 0.338378E+09 | 0.486533E+09 | 0.341516E+09 | 26421681.49 | 0.325659E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: T N2 APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 3151489.11 | 0.486526E+09 | 80398594.49 | 0.00 | 80398594.49 | 0.00 | 0.00 |
| February | 24505304.04 | 0.377122E+09 | 0.112996E+09 | 0.00 | 0.112996E+09 | 0.00 | 0.00 |
| March | 88039763.38 | 0.324090E+09 | 0.184345E+09 | 3676.65 | 0.184341E+09 | 0.00 | 0.00 |
| April | 0.176144E+09 | 0.246570E+09 | 0.252834E+09 | 1224735.97 | 0.251609E+09 | 0.00 | 0.00 |
| May | 0.282198E+09 | 0.207417E+09 | 0.335468E+09 | 9808992.16 | 0.325659E+09 | 0.00 | 0.00 |
| June | 0.308974E+09 | 0.156473E+09 | 0.341516E+09 | 22472037.20 | 0.319044E+09 | 0.00 | 0.00 |
| July | 0.338294E+09 | 0.144648E+09 | 0.335695E+09 | 26421681.49 | 0.309274E+09 | 0.00 | 0.00 |
| August | 0.280284E+09 | 0.142368E+09 | 0.272693E+09 | 8316268.31 | 0.264376E+09 | 0.00 | 0.00 |
| September | 0.163004E+09 | 0.203773E+09 | 0.204209E+09 | 132190.44 | 0.204077E+09 | 0.00 | 0.00 |
| October | 77634968.19 | 0.276700E+09 | 0.144505E+09 | 0.00 | 0.144505E+09 | 0.00 | 0.00 |
| November | 15914011.08 | 0.356531E+09 | 88087644.44 | 0.00 | 88087644.44 | 0.00 | 0.00 |
| December | 1662113.32 | 0.476325E+09 | 68318055.64 | 0.00 | 68318055.64 | 0.00 | 0.00 |
| Annual Sum or Average | 0.175981E+10 | 0.339854E+10 | 0.242106E+10 | 68379582.23 | 0.235269E+10 | 0.00 | 0.00 |
| Minimum of Months | 1662113.32 | 0.142368E+09 | 68318055.64 | 0.00 | 68318055.64 | 0.00 | 0.00 |
| Maximum of Months | 0.338294E+09 | 0.486526E+09 | 0.341516E+09 | 26421681.49 | 0.325659E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: T S1 APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.312279E+09 | 0.439290E+09 | 0.356115E+09 | 0.211787E+09 | 0.144327E+09 | 0.00 | 0.00 |
| February | 0.502873E+09 | 0.348764E+09 | 0.500446E+09 | 0.312463E+09 | 0.187983E+09 | 0.00 | 0.00 |
| March | 0.608698E+09 | 0.325308E+09 | 0.579159E+09 | 0.304880E+09 | 0.274279E+09 | 0.00 | 0.00 |
| April | 0.669736E+09 | 0.263677E+09 | 0.601691E+09 | 0.261958E+09 | 0.339733E+09 | 0.00 | 0.00 |
| May | 0.642584E+09 | 0.225528E+09 | 0.571336E+09 | 0.173034E+09 | 0.398303E+09 | 0.00 | 0.00 |
| June | 0.575517E+09 | 0.173452E+09 | 0.504391E+09 | 0.136950E+09 | 0.367441E+09 | 0.00 | 0.00 |
| July | 0.712964E+09 | 0.161362E+09 | 0.569545E+09 | 0.210801E+09 | 0.358744E+09 | 0.00 | 0.00 |
| August | 0.776936E+09 | 0.155957E+09 | 0.601744E+09 | 0.277187E+09 | 0.324557E+09 | 0.00 | 0.00 |
| September | 0.787498E+09 | 0.209995E+09 | 0.646105E+09 | 0.354088E+09 | 0.292017E+09 | 0.00 | 0.00 |
| October | 0.668191E+09 | 0.283077E+09 | 0.595727E+09 | 0.362163E+09 | 0.233564E+09 | 0.00 | 0.00 |
| November | 0.330855E+09 | 0.337397E+09 | 0.348015E+09 | 0.198875E+09 | 0.149140E+09 | 0.00 | 0.00 |
| December | 0.362037E+09 | 0.441893E+09 | 0.375617E+09 | 0.242303E+09 | 0.133314E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.695017E+10 | 0.336570E+10 | 0.624989E+10 | 0.304649E+10 | 0.320340E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.312279E+09 | 0.155957E+09 | 0.348015E+09 | 0.136950E+09 | 0.133314E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.787498E+09 | 0.441893E+09 | 0.646105E+09 | 0.362163E+09 | 0.398303E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: T S2 APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.312258E+09 | 0.439254E+09 | 0.356115E+09 | 0.211787E+09 | 0.144327E+09 | 0.00 | 0.00 |
| February | 0.502796E+09 | 0.348666E+09 | 0.500446E+09 | 0.312463E+09 | 0.187983E+09 | 0.00 | 0.00 |
| March | 0.608519E+09 | 0.325196E+09 | 0.579159E+09 | 0.304880E+09 | 0.274279E+09 | 0.00 | 0.00 |
| April | 0.669391E+09 | 0.263637E+09 | 0.601691E+09 | 0.261958E+09 | 0.339733E+09 | 0.00 | 0.00 |
| May | 0.642409E+09 | 0.225299E+09 | 0.571336E+09 | 0.173034E+09 | 0.398303E+09 | 0.00 | 0.00 |
| June | 0.575219E+09 | 0.173332E+09 | 0.504391E+09 | 0.136950E+09 | 0.367441E+09 | 0.00 | 0.00 |
| July | 0.712861E+09 | 0.161131E+09 | 0.569545E+09 | 0.210801E+09 | 0.358744E+09 | 0.00 | 0.00 |
| August | 0.776761E+09 | 0.155837E+09 | 0.601744E+09 | 0.277187E+09 | 0.324557E+09 | 0.00 | 0.00 |
| September | 0.787425E+09 | 0.209742E+09 | 0.646105E+09 | 0.354088E+09 | 0.292017E+09 | 0.00 | 0.00 |
| October | 0.668037E+09 | 0.282985E+09 | 0.595727E+09 | 0.362163E+09 | 0.233564E+09 | 0.00 | 0.00 |
| November | 0.330803E+09 | 0.337368E+09 | 0.348015E+09 | 0.198875E+09 | 0.149140E+09 | 0.00 | 0.00 |
| December | 0.361998E+09 | 0.441835E+09 | 0.375617E+09 | 0.242303E+09 | 0.133314E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.694848E+10 | 0.336428E+10 | 0.624989E+10 | 0.304649E+10 | 0.320340E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.312258E+09 | 0.155837E+09 | 0.348015E+09 | 0.136950E+09 | 0.133314E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.787425E+09 | 0.441835E+09 | 0.646105E+09 | 0.362163E+09 | 0.398303E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: T CORRIDOR
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 6863072.70 | 75853545.22 | 20293656.78 | 5081472.62 | 15212184.16 | 0.00 | 0.00 |
| February | 21236034.89 | 59287996.49 | 33609788.78 | 11800887.42 | 21808901.36 | 0.00 | 0.00 |
| March | 46418148.40 | 53215006.52 | 55919693.26 | 20186893.44 | 35732799.82 | 0.00 | 0.00 |
| April | 84241763.44 | 41603426.51 | 83930981.03 | 34910973.71 | 49020007.32 | 0.00 | 0.00 |
| May | 96232339.61 | 37012829.61 | 92231689.51 | 32115176.81 | 60116512.69 | 0.00 | 0.00 |
| June | 0.118361E+09 | 28702092.82 | 0.106860E+09 | 46522726.36 | 60337344.53 | 0.00 | 0.00 |
| July | 0.118038E+09 | 26631176.24 | 0.103068E+09 | 46405470.61 | 56662916.82 | 0.00 | 0.00 |
| August | 0.119318E+09 | 26167653.21 | 0.100851E+09 | 50359159.92 | 50491468.84 | 0.00 | 0.00 |
| September | 77432536.91 | 35178129.65 | 72340185.12 | 33381365.85 | 38958819.27 | 0.00 | 0.00 |
| October | 44704286.60 | 47139735.17 | 49072406.16 | 21051982.73 | 28020423.43 | 0.00 | 0.00 |
| November | 12192464.77 | 57935893.23 | 23163393.15 | 6559170.04 | 16604223.10 | 0.00 | 0.00 |
| December | 8748961.50 | 75138814.19 | 19561574.05 | 6268867.39 | 13292706.66 | 0.00 | 0.00 |
| Annual Sum or Average | 0.753787E+09 | 0.563866E+09 | 0.760902E+09 | 0.314644E+09 | 0.446258E+09 | 0.00 | 0.00 |
| Minimum of Months | 6863072.70 | 26167653.21 | 19561574.05 | 5081472.62 | 13292706.66 | 0.00 | 0.00 |
| Maximum of Months | 0.119318E+09 | 75853545.22 | 0.106860E+09 | 50359159.92 | 60337344.53 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: G CORRIDOR
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 23613050.30 | 0.199563E+09 | 60439560.24 | 15133890.07 | 45305670.17 | 0.00 | 0.00 |
| February | 69962470.10 | 0.156051E+09 | 0.100098E+09 | 35145979.55 | 64952335.68 | 0.00 | 0.00 |
| March | 0.147959E+09 | 0.141948E+09 | 0.166543E+09 | 60121592.45 | 0.106421E+09 | 0.00 | 0.00 |
| April | 0.263929E+09 | 0.110578E+09 | 0.249967E+09 | 0.103974E+09 | 0.145994E+09 | 0.00 | 0.00 |
| May | 0.296869E+09 | 0.102966E+09 | 0.274689E+09 | 95646988.84 | 0.179042E+09 | 0.00 | 0.00 |
| June | 0.360487E+09 | 82061044.14 | 0.318256E+09 | 0.138556E+09 | 0.179700E+09 | 0.00 | 0.00 |
| July | 0.356700E+09 | 78298931.01 | 0.306963E+09 | 0.138207E+09 | 0.168756E+09 | 0.00 | 0.00 |
| August | 0.357786E+09 | 78857997.08 | 0.300358E+09 | 0.149982E+09 | 0.150376E+09 | 0.00 | 0.00 |
| September | 0.231737E+09 | 0.106375E+09 | 0.215447E+09 | 99418014.91 | 0.116029E+09 | 0.00 | 0.00 |
| October | 0.134505E+09 | 0.138629E+09 | 0.146150E+09 | 62698043.65 | 83451794.24 | 0.00 | 0.00 |
| November | 39064999.42 | 0.159681E+09 | 68986349.31 | 19534840.72 | 49451508.59 | 0.00 | 0.00 |
| December | 28754004.95 | 0.201736E+09 | 58259235.67 | 18670247.19 | 39588988.49 | 0.00 | 0.00 |
| Annual Sum or Average | 0.231137E+10 | 0.155674E+10 | 0.226616E+10 | 0.937089E+09 | 0.132907E+10 | 0.00 | 0.00 |
| Minimum of Months | 23613050.30 | 78298931.01 | 58259235.67 | 15133890.07 | 39588988.49 | 0.00 | 0.00 |
| Maximum of Months | 0.360487E+09 | 0.201736E+09 | 0.318256E+09 | 0.149982E+09 | 0.179700E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: M CORRIDOR
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 6178981.45 | 82669087.77 | 20293656.78 | 5081472.62 | 15212184.16 | 0.00 | 0.00 |
| February | 19923525.25 | 64294847.65 | 33609788.78 | 11800887.42 | 21808901.36 | 0.00 | 0.00 |
| March | 44328305.06 | 58484668.26 | 55919693.26 | 20186893.44 | 35732799.82 | 0.00 | 0.00 |
| April | 81587863.24 | 45699773.42 | 83930981.03 | 34910973.71 | 49020007.32 | 0.00 | 0.00 |
| May | 92908190.88 | 41191390.37 | 92231689.51 | 32115176.81 | 60116512.69 | 0.00 | 0.00 |
| June | 0.116240E+09 | 31008334.06 | 0.106860E+09 | 46522726.36 | 60337344.53 | 0.00 | 0.00 |
| July | 0.116968E+09 | 28056779.55 | 0.103068E+09 | 46405470.61 | 56662916.82 | 0.00 | 0.00 |
| August | 0.118247E+09 | 27632216.18 | 0.100851E+09 | 50359159.92 | 50491468.84 | 0.00 | 0.00 |
| September | 74854999.78 | 39300838.50 | 72340185.12 | 33381365.85 | 38958819.27 | 0.00 | 0.00 |
| October | 41668875.45 | 54167016.30 | 49072406.16 | 21051982.73 | 28020423.43 | 0.00 | 0.00 |
| November | 11107846.12 | 64189106.63 | 23163393.15 | 6559170.04 | 16604223.10 | 0.00 | 0.00 |
| December | 8045460.97 | 82022325.79 | 19561574.05 | 6268867.39 | 13292706.66 | 0.00 | 0.00 |
| Annual Sum or Average | 0.732059E+09 | 0.618716E+09 | 0.760902E+09 | 0.314644E+09 | 0.446258E+09 | 0.00 | 0.00 |
| Minimum of Months | 6178981.45 | 27632216.18 | 19561574.05 | 5081472.62 | 13292706.66 | 0.00 | 0.00 |
| Maximum of Months | 0.118247E+09 | 82669087.77 | 0.106860E+09 | 50359159.92 | 60337344.53 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
| January | 4.50 | 3.10 | 1.22 | 3.91 | -4.2 | 29.50 | 44.23 | 0.00 |
| February | 5.82 | 4.07 | 1.77 | 3.94 | -3.8 | 43.80 | 82.64 | 0.00 |
| March | 8.33 | 5.86 | 2.94 | 3.85 | -1.4 | 65.55 | 100.60 | 0.02 |
| April | 10.85 | 8.04 | 5.25 | 4.23 | 1.22 | 89.73 | 150.02 | 0.00 |
| May | 12.97 | 10.02 | 7.49 | 3.85 | 3.75 | 114.98 | 168.60 | 0.00 |
| June | 15.59 | 11.80 | 8.88 | 4.02 | 5.93 | 107.53 | 199.74 | 0.01 |
| July | 17.66 | 13.41 | 10.38 | 3.76 | 8.02 | 92.25 | 247.81 | 0.00 |
| August | 18.80 | 14.57 | 11.86 | 3.84 | 8.90 | 79.20 | 215.47 | 0.01 |
| September | 15.09 | 12.55 | 10.74 | 2.23 | 5.47 | 68.06 | 162.11 | 0.01 |
| October | 11.43 | 9.19 | 7.19 | 4.02 | 2.10 | 48.18 | 106.36 | 0.04 |
| November | 8.07 | 6.72 | 5.29 | 3.86 | 0.13 | 33.26 | 46.10 | 0.00 |
| December | 5.42 | 4.09 | 2.46 | 3.51 | -3.8 | 24.03 | 50.49 | 0.04 |
| Annual Sum or Average | 11.24 | 8.64 | 6.31 | 3.75 | 1.89 | 66.43 | 131.49 | 0.01 |
| Minimum of Months | 4.50 | 3.10 | 1.22 | 2.23 | -4.2 | 24.03 | 44.23 | 0.00 |
| Maximum of Months | 18.80 | 14.57 | 11.86 | 4.23 | 8.90 | 114.98 | 247.81 | 0.04 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
| January | 14.40 | 11-JAN-14:20 | 10.49 | 7.20 | 8.40 | 3.89 | 99.17 | 130.33 |
| February | 20.00 | 27-FEB-14:00 | 12.17 | 5.60 | 2.60 | 5.54 | 87.00 | 691.00 |
| March | 20.60 | 18-MAR-15:00 | 10.43 | 0.00 | 6.20 | 6.55 | 111.50 | 465.50 |
| April | 27.20 | 27-APR-15:09 | 17.22 | 11.02 | 4.10 | 12.63 | 151.33 | 598.33 |
| May | 25.00 | 05-MAY-15:00 | 17.36 | 12.80 | 2.60 | 18.99 | 208.50 | 29.50 |
| June | 26.70 | 28-JUN-16:00 | 16.74 | 10.60 | 3.10 | 11.84 | 131.50 | 527.00 |
| July | 30.60 | 24-JUL-14:00 | 18.78 | 12.20 | 3.10 | 20.75 | 267.00 | 383.50 |
| August | 31.80 | 10-AUG-16:00 | 18.70 | 11.10 | 2.60 | 16.85 | 50.50 | 750.50 |
| September | 25.00 | 14-SEP-16:00 | 16.69 | 11.70 | 3.10 | 13.54 | 100.50 | 235.00 |
| October | 21.70 | 04-OCT-14:00 | 11.49 | 1.70 | 5.20 | 4.92 | 56.50 | 783.50 |
| November | 21.10 | 04-NOV-13:00 | 15.94 | 12.80 | 0.00 | 6.95 | 52.50 | 729.00 |
| December | 13.30 | 14-DEC-11:00 | 8.44 | 3.60 | 13.90 | 5.33 | 127.50 | 85.00 |
| Annual Sum or Average | ||||||||
| Minimum of Months | 13.30 | 8.44 | 0.00 | 0.00 | 3.89 | 50.50 | 29.50 | |
| Maximum of Months | 31.80 | 18.78 | 12.80 | 13.90 | 20.75 | 267.00 | 783.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
| January | -3.9 | 07-JAN-07:00 | -3.9 | -3.9 | 2.10 | -14.4 | 0.00 | 0.00 |
| February | -5.6 | 19-FEB-05:10 | -6.1 | -7.3 | 3.77 | -22.8 | 0.00 | 0.00 |
| March | -0.6 | 01-MAR-06:00 | -2.0 | -3.9 | 1.50 | -17.3 | 16.50 | 102.00 |
| April | 1.70 | 19-APR-04:00 | 1.21 | 0.60 | 3.10 | -11.9 | 0.00 | 0.00 |
| May | 4.40 | 11-MAY-02:00 | 3.92 | 3.30 | 3.10 | -10.9 | 0.00 | 0.00 |
| June | 8.30 | 15-JUN-02:00 | 7.50 | 6.70 | 3.10 | -3.2 | 0.00 | 0.00 |
| July | 11.10 | 03-JUL-03:00 | 8.19 | 5.00 | 2.60 | 5.54 | 0.00 | 0.00 |
| August | 11.00 | 06-AUG-04:00 | 10.57 | 10.20 | 2.60 | -3.2 | 11.00 | 135.50 |
| September | 7.20 | 27-SEP-04:49 | 6.72 | 6.20 | 0.25 | -4.0 | 0.00 | 0.00 |
| October | 5.60 | 13-OCT-04:00 | 4.51 | 3.30 | 2.10 | -8.5 | 0.00 | 0.00 |
| November | 0.00 | 11-NOV-06:00 | -0.2 | -0.6 | 2.10 | -16.0 | 0.00 | 0.00 |
| December | -1.7 | 26-DEC-06:00 | -1.7 | -1.7 | 2.10 | -15.7 | 0.00 | 0.00 |
| Annual Sum or Average | ||||||||
| Minimum of Months | -5.6 | -6.1 | -7.3 | 0.25 | -22.8 | 0.00 | 0.00 | |
| Maximum of Months | 11.10 | 10.57 | 10.20 | 3.77 | 5.54 | 16.50 | 135.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| SITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
| January | 10.49 | 11-JAN-13:00 | 14.40 | 7.20 | 8.20 | 2.85 | 105.50 | 249.00 |
| February | 12.42 | 27-FEB-15:00 | 19.40 | 6.70 | 2.60 | 6.35 | 88.00 | 342.50 |
| March | 12.45 | 09-MAR-11:00 | 17.20 | 8.90 | 2.10 | 12.41 | 178.00 | 40.00 |
| April | 17.29 | 27-APR-14:00 | 27.20 | 11.10 | 4.10 | 12.41 | 147.50 | 646.00 |
| May | 17.58 | 06-MAY-12:00 | 23.90 | 13.90 | 5.20 | 15.57 | 365.50 | 282.50 |
| June | 16.74 | 28-JUN-16:00 | 26.70 | 10.60 | 3.10 | 11.84 | 131.50 | 527.00 |
| July | 19.18 | 31-JUL-15:00 | 28.90 | 13.90 | 4.10 | 14.65 | 45.00 | 848.50 |
| August | 20.13 | 29-AUG-12:00 | 28.90 | 15.70 | 2.60 | 17.39 | 136.50 | 655.00 |
| September | 17.97 | 23-SEP-13:00 | 23.30 | 15.00 | 2.10 | 9.72 | 148.00 | 670.50 |
| October | 15.15 | 01-OCT-11:00 | 17.20 | 13.90 | 4.60 | 13.73 | 236.50 | 63.50 |
| November | 16.05 | 04-NOV-12:00 | 20.60 | 13.30 | 0.00 | 7.95 | 62.00 | 746.50 |
| December | 10.71 | 16-DEC-11:00 | 11.70 | 10.00 | 6.70 | 7.35 | 89.50 | 0.00 |
| Annual Sum or Average | ||||||||
| Minimum of Months | 10.49 | 11.70 | 6.70 | 0.00 | 2.85 | 45.00 | 0.00 | |
| Maximum of Months | 20.13 | 28.90 | 15.70 | 8.20 | 17.39 | 365.50 | 848.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| SITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
| January | 10.00 | 11-JAN-21:00 | 11.10 | 10.49 | 4.60 | 6.75 | 0.00 | 0.00 |
| February | 11.70 | 24-FEB-00:00 | 12.80 | 12.15 | 4.10 | 8.74 | 0.00 | 0.00 |
| March | 11.70 | 09-MAR-16:00 | 12.80 | 12.15 | 2.10 | 8.74 | 37.50 | 0.00 |
| April | 12.80 | 28-APR-12:00 | 16.70 | 14.35 | 4.10 | 8.35 | 265.50 | 596.00 |
| May | 13.90 | 05-MAY-16:00 | 22.80 | 17.10 | 2.60 | 19.17 | 111.50 | 27.50 |
| June | 13.90 | 12-JUN-12:00 | 16.70 | 15.00 | 3.60 | 13.16 | 263.50 | 0.00 |
| July | 15.00 | 11-JUL-09:20 | 16.13 | 15.49 | 4.60 | 12.91 | 204.17 | 28.17 |
| August | 16.40 | 30-AUG-07:00 | 17.40 | 16.77 | 5.20 | 12.41 | 168.50 | 34.50 |
| September | 15.00 | 14-SEP-11:20 | 20.37 | 16.93 | 2.10 | 6.89 | 152.83 | 748.17 |
| October | 13.90 | 01-OCT-10:00 | 16.70 | 15.01 | 4.10 | 13.16 | 184.50 | 0.00 |
| November | 13.90 | 03-NOV-19:00 | 15.00 | 14.31 | 4.60 | 11.46 | 0.00 | 0.00 |
| December | 10.00 | 16-DEC-10:00 | 11.10 | 10.48 | 7.70 | 6.75 | 81.00 | 0.00 |
| Annual Sum or Average | ||||||||
| Minimum of Months | 10.00 | 11.10 | 10.48 | 2.10 | 6.75 | 0.00 | 0.00 | |
| Maximum of Months | 16.40 | 22.80 | 17.10 | 7.70 | 19.17 | 265.50 | 748.17 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| SITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
| January | 18.00 | 13.00 | 16.00 | 11.48 | 8.35 | 0.00 |
| February | 18.00 | 13.00 | 16.00 | 11.14 | 14.81 | 0.00 |
| March | 18.00 | 13.00 | 16.00 | 11.69 | 23.26 | 0.00 |
| April | 18.00 | 13.00 | 16.00 | 12.99 | 36.00 | 0.00 |
| May | 18.00 | 13.00 | 16.00 | 14.72 | 45.46 | 0.00 |
| June | 18.00 | 13.00 | 16.00 | 16.40 | 49.26 | 0.00 |
| July | 18.00 | 13.00 | 16.00 | 17.58 | 51.50 | 0.00 |
| August | 18.00 | 13.00 | 16.00 | 17.95 | 42.11 | 0.00 |
| September | 18.00 | 13.00 | 16.00 | 17.39 | 30.76 | 0.00 |
| October | 18.00 | 13.00 | 16.00 | 16.06 | 18.91 | 0.00 |
| November | 18.00 | 13.00 | 16.00 | 14.32 | 9.65 | 0.00 |
| December | 18.00 | 13.00 | 16.00 | 12.65 | 7.39 | 0.00 |
| Annual Sum or Average | 18.00 | 13.00 | 16.00 | 14.55 | 28.19 | 0.00 |
| Minimum of Months | 18.00 | 13.00 | 16.00 | 11.14 | 7.39 | 0.00 |
| Maximum of Months | 18.00 | 13.00 | 16.00 | 17.95 | 51.50 | 0.00 |
Report: WaterHeaterReportMonthly
For: G SW APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.121792E+10 | -0.103132E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186600610.8 | 59.44 | 0.00 | 0.00 |
| February | 0.110620E+10 | -937945237.3 | 0.00 | 0.00 | 672.00 | 0.00 | -168253612.9 | 59.44 | 0.00 | 0.00 |
| March | 0.121247E+10 | -0.102681E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -185664970.7 | 59.44 | 0.00 | 0.00 |
| April | 0.114364E+10 | -966491652.7 | 0.00 | 0.00 | 720.00 | 0.00 | -177149816.6 | 59.44 | 0.00 | 0.00 |
| May | 0.113999E+10 | -961547954.7 | 0.00 | 0.00 | 744.00 | 0.00 | -178441555.6 | 59.44 | 0.00 | 0.00 |
| June | 0.106455E+10 | -895524001.4 | 0.00 | 0.00 | 720.00 | 0.00 | -169028246.3 | 59.44 | 0.00 | 0.00 |
| July | 0.107276E+10 | -899972718.5 | 0.00 | 0.00 | 744.00 | 0.00 | -172783675.0 | 59.44 | 0.00 | 0.00 |
| August | 0.106489E+10 | -892145406.6 | 0.00 | 0.00 | 744.00 | 0.00 | -172745808.4 | 59.44 | 0.00 | 0.00 |
| September | 0.104301E+10 | -875059637.6 | 0.00 | 0.00 | 720.00 | 0.00 | -167952479.7 | 59.44 | 0.00 | 0.00 |
| October | 0.111268E+10 | -932810191.6 | 0.00 | 0.00 | 744.00 | 0.00 | -179868387.3 | 59.44 | 0.00 | 0.00 |
| November | 0.111839E+10 | -938782872.4 | 0.00 | 0.00 | 720.00 | 0.00 | -179605315.3 | 59.44 | 0.00 | 0.00 |
| December | 0.119248E+10 | -0.100602E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186459105.7 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.134890E+11 | -0.113644E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.212455E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.104301E+10 | -0.103132E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -186600610.8 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.121792E+10 | -875059637.6 | 0.00 | 0.00 | 744.00 | 0.00 | -167952479.7 | 59.44 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: G NW APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.121793E+10 | -0.103132E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186602669.1 | 59.44 | 0.00 | 0.00 |
| February | 0.110647E+10 | -937946794.7 | 0.00 | 0.00 | 672.00 | 0.00 | -168519357.9 | 59.44 | 0.00 | 0.00 |
| March | 0.121336E+10 | -0.102681E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186557982.8 | 59.44 | 0.00 | 0.00 |
| April | 0.114558E+10 | -966492152.1 | 0.00 | 0.00 | 720.00 | 0.00 | -179086274.3 | 59.44 | 0.00 | 0.00 |
| May | 0.114245E+10 | -961547297.0 | 0.00 | 0.00 | 744.00 | 0.00 | -180906958.1 | 59.44 | 0.00 | 0.00 |
| June | 0.106566E+10 | -895517505.6 | 0.00 | 0.00 | 720.00 | 0.00 | -170140965.3 | 59.44 | 0.00 | 0.00 |
| July | 0.107297E+10 | -899970422.9 | 0.00 | 0.00 | 744.00 | 0.00 | -172998264.2 | 59.44 | 0.00 | 0.00 |
| August | 0.106509E+10 | -892146493.0 | 0.00 | 0.00 | 744.00 | 0.00 | -172938517.3 | 59.44 | 0.00 | 0.00 |
| September | 0.104443E+10 | -875062026.3 | 0.00 | 0.00 | 720.00 | 0.00 | -169371828.6 | 59.44 | 0.00 | 0.00 |
| October | 0.111652E+10 | -932810012.5 | 0.00 | 0.00 | 744.00 | 0.00 | -183712206.7 | 59.44 | 0.00 | 0.00 |
| November | 0.111911E+10 | -938782972.0 | 0.00 | 0.00 | 720.00 | 0.00 | -180327210.0 | 59.44 | 0.00 | 0.00 |
| December | 0.119262E+10 | -0.100602E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186600097.3 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.135022E+11 | -0.113644E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.213776E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.104443E+10 | -0.103132E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -186602669.1 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.121793E+10 | -875062026.3 | 0.00 | 0.00 | 744.00 | 0.00 | -168519357.9 | 59.44 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: G NE APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.121793E+10 | -0.103132E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186602669.1 | 59.44 | 0.00 | 0.00 |
| February | 0.110648E+10 | -937946844.3 | 0.00 | 0.00 | 672.00 | 0.00 | -168532996.1 | 59.44 | 0.00 | 0.00 |
| March | 0.121340E+10 | -0.102681E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186596986.8 | 59.44 | 0.00 | 0.00 |
| April | 0.114557E+10 | -966491862.2 | 0.00 | 0.00 | 720.00 | 0.00 | -179080317.5 | 59.44 | 0.00 | 0.00 |
| May | 0.114260E+10 | -961548472.8 | 0.00 | 0.00 | 744.00 | 0.00 | -181053293.7 | 59.44 | 0.00 | 0.00 |
| June | 0.106525E+10 | -895518810.9 | 0.00 | 0.00 | 720.00 | 0.00 | -169733405.3 | 59.44 | 0.00 | 0.00 |
| July | 0.107312E+10 | -899971060.4 | 0.00 | 0.00 | 744.00 | 0.00 | -173145706.8 | 59.44 | 0.00 | 0.00 |
| August | 0.106507E+10 | -892147083.7 | 0.00 | 0.00 | 744.00 | 0.00 | -172919710.4 | 59.44 | 0.00 | 0.00 |
| September | 0.104467E+10 | -875063136.1 | 0.00 | 0.00 | 720.00 | 0.00 | -169604253.3 | 59.44 | 0.00 | 0.00 |
| October | 0.111661E+10 | -932811705.0 | 0.00 | 0.00 | 744.00 | 0.00 | -183802709.1 | 59.44 | 0.00 | 0.00 |
| November | 0.111912E+10 | -938780139.8 | 0.00 | 0.00 | 720.00 | 0.00 | -180336753.4 | 59.44 | 0.00 | 0.00 |
| December | 0.119263E+10 | -0.100602E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186603097.7 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.135024E+11 | -0.113644E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.213801E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.104467E+10 | -0.103132E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -186603097.7 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.121793E+10 | -875063136.1 | 0.00 | 0.00 | 744.00 | 0.00 | -168532996.1 | 59.44 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: G N1 APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.121793E+10 | -0.103132E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186602669.0 | 59.44 | 0.00 | 0.00 |
| February | 0.110644E+10 | -937946743.4 | 0.00 | 0.00 | 672.00 | 0.00 | -168489194.8 | 59.44 | 0.00 | 0.00 |
| March | 0.121333E+10 | -0.102681E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186523166.3 | 59.44 | 0.00 | 0.00 |
| April | 0.114543E+10 | -966491975.6 | 0.00 | 0.00 | 720.00 | 0.00 | -178940357.9 | 59.44 | 0.00 | 0.00 |
| May | 0.114126E+10 | -961548333.7 | 0.00 | 0.00 | 744.00 | 0.00 | -179714997.2 | 59.44 | 0.00 | 0.00 |
| June | 0.106463E+10 | -895521292.0 | 0.00 | 0.00 | 720.00 | 0.00 | -169105920.8 | 59.44 | 0.00 | 0.00 |
| July | 0.107269E+10 | -899974499.1 | 0.00 | 0.00 | 744.00 | 0.00 | -172711593.7 | 59.44 | 0.00 | 0.00 |
| August | 0.106480E+10 | -892146575.4 | 0.00 | 0.00 | 744.00 | 0.00 | -172650739.1 | 59.44 | 0.00 | 0.00 |
| September | 0.104348E+10 | -875061759.2 | 0.00 | 0.00 | 720.00 | 0.00 | -168420199.2 | 59.44 | 0.00 | 0.00 |
| October | 0.111538E+10 | -932809628.2 | 0.00 | 0.00 | 744.00 | 0.00 | -182566154.2 | 59.44 | 0.00 | 0.00 |
| November | 0.111877E+10 | -938781571.2 | 0.00 | 0.00 | 720.00 | 0.00 | -179983657.0 | 59.44 | 0.00 | 0.00 |
| December | 0.119262E+10 | -0.100602E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186600528.0 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.134967E+11 | -0.113644E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.213231E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.104348E+10 | -0.103132E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -186602669.0 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.121793E+10 | -875061759.2 | 0.00 | 0.00 | 744.00 | 0.00 | -168420199.2 | 59.44 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: G N2 APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.121793E+10 | -0.103132E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186602669.0 | 59.44 | 0.00 | 0.00 |
| February | 0.110644E+10 | -937946745.7 | 0.00 | 0.00 | 672.00 | 0.00 | -168489909.8 | 59.44 | 0.00 | 0.00 |
| March | 0.121333E+10 | -0.102681E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186524727.9 | 59.44 | 0.00 | 0.00 |
| April | 0.114543E+10 | -966491878.3 | 0.00 | 0.00 | 720.00 | 0.00 | -178933137.4 | 59.44 | 0.00 | 0.00 |
| May | 0.114129E+10 | -961548137.3 | 0.00 | 0.00 | 744.00 | 0.00 | -179746099.4 | 59.44 | 0.00 | 0.00 |
| June | 0.106459E+10 | -895521158.1 | 0.00 | 0.00 | 720.00 | 0.00 | -169064588.3 | 59.44 | 0.00 | 0.00 |
| July | 0.107270E+10 | -899974452.5 | 0.00 | 0.00 | 744.00 | 0.00 | -172722713.4 | 59.44 | 0.00 | 0.00 |
| August | 0.106480E+10 | -892146680.8 | 0.00 | 0.00 | 744.00 | 0.00 | -172652595.5 | 59.44 | 0.00 | 0.00 |
| September | 0.104351E+10 | -875061635.9 | 0.00 | 0.00 | 720.00 | 0.00 | -168448411.0 | 59.44 | 0.00 | 0.00 |
| October | 0.111540E+10 | -932810604.6 | 0.00 | 0.00 | 744.00 | 0.00 | -182587333.5 | 59.44 | 0.00 | 0.00 |
| November | 0.111877E+10 | -938781415.9 | 0.00 | 0.00 | 720.00 | 0.00 | -179984351.6 | 59.44 | 0.00 | 0.00 |
| December | 0.119262E+10 | -0.100602E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186600302.7 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.134968E+11 | -0.113644E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.213236E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.104351E+10 | -0.103132E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -186602669.0 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.121793E+10 | -875061635.9 | 0.00 | 0.00 | 744.00 | 0.00 | -168448411.0 | 59.44 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: G S1 APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.121789E+10 | -0.103132E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186568614.6 | 59.44 | 0.00 | 0.00 |
| February | 0.110590E+10 | -937947226.8 | 0.00 | 0.00 | 672.00 | 0.00 | -167950993.0 | 59.44 | 0.00 | 0.00 |
| March | 0.121177E+10 | -0.102681E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -184964402.9 | 59.44 | 0.00 | 0.00 |
| April | 0.114254E+10 | -966492208.4 | 0.00 | 0.00 | 720.00 | 0.00 | -176050385.8 | 59.44 | 0.00 | 0.00 |
| May | 0.113810E+10 | -961549376.3 | 0.00 | 0.00 | 744.00 | 0.00 | -176549851.6 | 59.44 | 0.00 | 0.00 |
| June | 0.106354E+10 | -895518477.2 | 0.00 | 0.00 | 720.00 | 0.00 | -168020842.4 | 59.44 | 0.00 | 0.00 |
| July | 0.107255E+10 | -899972977.4 | 0.00 | 0.00 | 744.00 | 0.00 | -172581806.1 | 59.44 | 0.00 | 0.00 |
| August | 0.106468E+10 | -892146041.3 | 0.00 | 0.00 | 744.00 | 0.00 | -172537378.5 | 59.44 | 0.00 | 0.00 |
| September | 0.104239E+10 | -875061799.2 | 0.00 | 0.00 | 720.00 | 0.00 | -167323861.0 | 59.44 | 0.00 | 0.00 |
| October | 0.111025E+10 | -932812838.6 | 0.00 | 0.00 | 744.00 | 0.00 | -177441921.6 | 59.44 | 0.00 | 0.00 |
| November | 0.111748E+10 | -938781537.7 | 0.00 | 0.00 | 720.00 | 0.00 | -178699406.0 | 59.44 | 0.00 | 0.00 |
| December | 0.119229E+10 | -0.100602E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186267917.4 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.134794E+11 | -0.113644E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.211496E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.104239E+10 | -0.103132E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -186568614.6 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.121789E+10 | -875061799.2 | 0.00 | 0.00 | 744.00 | 0.00 | -167323861.0 | 59.44 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: G S2 APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.121790E+10 | -0.103132E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186580425.7 | 59.44 | 0.00 | 0.00 |
| February | 0.110594E+10 | -937946746.8 | 0.00 | 0.00 | 672.00 | 0.00 | -167995553.3 | 59.44 | 0.00 | 0.00 |
| March | 0.121176E+10 | -0.102681E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -184957352.3 | 59.44 | 0.00 | 0.00 |
| April | 0.114235E+10 | -966492391.6 | 0.00 | 0.00 | 720.00 | 0.00 | -175861612.5 | 59.44 | 0.00 | 0.00 |
| May | 0.113774E+10 | -961548443.6 | 0.00 | 0.00 | 744.00 | 0.00 | -176194964.3 | 59.44 | 0.00 | 0.00 |
| June | 0.106334E+10 | -895521803.9 | 0.00 | 0.00 | 720.00 | 0.00 | -167815624.3 | 59.44 | 0.00 | 0.00 |
| July | 0.107252E+10 | -899973368.5 | 0.00 | 0.00 | 744.00 | 0.00 | -172547449.4 | 59.44 | 0.00 | 0.00 |
| August | 0.106466E+10 | -892146722.4 | 0.00 | 0.00 | 744.00 | 0.00 | -172513026.2 | 59.44 | 0.00 | 0.00 |
| September | 0.104230E+10 | -875058323.9 | 0.00 | 0.00 | 720.00 | 0.00 | -167245210.2 | 59.44 | 0.00 | 0.00 |
| October | 0.110993E+10 | -932812067.2 | 0.00 | 0.00 | 744.00 | 0.00 | -177113009.4 | 59.44 | 0.00 | 0.00 |
| November | 0.111733E+10 | -938781297.1 | 0.00 | 0.00 | 720.00 | 0.00 | -178551523.7 | 59.44 | 0.00 | 0.00 |
| December | 0.119233E+10 | -0.100602E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186305341.9 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.134781E+11 | -0.113644E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.211368E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.104230E+10 | -0.103132E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -186580425.7 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.121790E+10 | -875058323.9 | 0.00 | 0.00 | 744.00 | 0.00 | -167245210.2 | 59.44 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: M SW APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.224911E+10 | -0.206265E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186452425.7 | 59.44 | 0.00 | 0.00 |
| February | 0.204286E+10 | -0.187589E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -166973796.0 | 59.44 | 0.00 | 0.00 |
| March | 0.223582E+10 | -0.205362E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -182197241.5 | 59.44 | 0.00 | 0.00 |
| April | 0.210476E+10 | -0.193299E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -171773518.3 | 59.44 | 0.00 | 0.00 |
| May | 0.209726E+10 | -0.192310E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -174155170.5 | 59.44 | 0.00 | 0.00 |
| June | 0.195841E+10 | -0.179105E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -167360314.2 | 59.44 | 0.00 | 0.00 |
| July | 0.197248E+10 | -0.179995E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172527306.9 | 59.44 | 0.00 | 0.00 |
| August | 0.195685E+10 | -0.178430E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172553187.8 | 59.44 | 0.00 | 0.00 |
| September | 0.191747E+10 | -0.175013E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -167343468.1 | 59.44 | 0.00 | 0.00 |
| October | 0.204333E+10 | -0.186563E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -177705916.7 | 59.44 | 0.00 | 0.00 |
| November | 0.205618E+10 | -0.187757E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -178605847.7 | 59.44 | 0.00 | 0.00 |
| December | 0.219801E+10 | -0.201205E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -185960776.1 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.248325E+11 | -0.227289E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.210361E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.191747E+10 | -0.206265E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -186452425.7 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.224911E+10 | -0.175013E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -166973796.0 | 59.44 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: M NW APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.224926E+10 | -0.206265E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186604783.8 | 59.44 | 0.00 | 0.00 |
| February | 0.204407E+10 | -0.187589E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -168174996.2 | 59.44 | 0.00 | 0.00 |
| March | 0.223908E+10 | -0.205362E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -185460214.4 | 59.44 | 0.00 | 0.00 |
| April | 0.210798E+10 | -0.193299E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -174994222.4 | 59.44 | 0.00 | 0.00 |
| May | 0.209788E+10 | -0.192310E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -174779048.0 | 59.44 | 0.00 | 0.00 |
| June | 0.195852E+10 | -0.179104E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -167480201.2 | 59.44 | 0.00 | 0.00 |
| July | 0.197251E+10 | -0.179995E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172557667.6 | 59.44 | 0.00 | 0.00 |
| August | 0.195689E+10 | -0.178430E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172593115.2 | 59.44 | 0.00 | 0.00 |
| September | 0.191788E+10 | -0.175013E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -167750422.0 | 59.44 | 0.00 | 0.00 |
| October | 0.204690E+10 | -0.186563E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -181268346.1 | 59.44 | 0.00 | 0.00 |
| November | 0.205731E+10 | -0.187757E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -179741617.7 | 59.44 | 0.00 | 0.00 |
| December | 0.219865E+10 | -0.201205E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186601603.8 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.248469E+11 | -0.227289E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.211801E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.191788E+10 | -0.206265E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -186604783.8 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.224926E+10 | -0.175013E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -167480201.2 | 59.44 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: M SE APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.224913E+10 | -0.206265E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186472719.3 | 59.44 | 0.00 | 0.00 |
| February | 0.204290E+10 | -0.187589E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -167010539.4 | 59.44 | 0.00 | 0.00 |
| March | 0.223572E+10 | -0.205362E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -182095241.8 | 59.44 | 0.00 | 0.00 |
| April | 0.210430E+10 | -0.193299E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -171312896.9 | 59.44 | 0.00 | 0.00 |
| May | 0.209730E+10 | -0.192310E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -174196638.0 | 59.44 | 0.00 | 0.00 |
| June | 0.195839E+10 | -0.179104E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -167347244.3 | 59.44 | 0.00 | 0.00 |
| July | 0.197250E+10 | -0.179995E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172549264.6 | 59.44 | 0.00 | 0.00 |
| August | 0.195686E+10 | -0.178430E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172565250.9 | 59.44 | 0.00 | 0.00 |
| September | 0.191753E+10 | -0.175013E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -167400729.7 | 59.44 | 0.00 | 0.00 |
| October | 0.204327E+10 | -0.186563E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -177642331.7 | 59.44 | 0.00 | 0.00 |
| November | 0.205615E+10 | -0.187757E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -178576239.9 | 59.44 | 0.00 | 0.00 |
| December | 0.219804E+10 | -0.201205E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -185985300.6 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.248321E+11 | -0.227289E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.210315E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.191753E+10 | -0.206265E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -186472719.3 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.224913E+10 | -0.175013E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -167010539.4 | 59.44 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: M NE APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.224926E+10 | -0.206265E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186604750.0 | 59.44 | 0.00 | 0.00 |
| February | 0.204410E+10 | -0.187589E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -168202809.4 | 59.44 | 0.00 | 0.00 |
| March | 0.223916E+10 | -0.205362E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -185538757.2 | 59.44 | 0.00 | 0.00 |
| April | 0.210749E+10 | -0.193299E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -174505593.8 | 59.44 | 0.00 | 0.00 |
| May | 0.209786E+10 | -0.192310E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -174757671.4 | 59.44 | 0.00 | 0.00 |
| June | 0.195848E+10 | -0.179105E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -167432646.1 | 59.44 | 0.00 | 0.00 |
| July | 0.197253E+10 | -0.179995E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172581293.0 | 59.44 | 0.00 | 0.00 |
| August | 0.195690E+10 | -0.178430E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172599466.0 | 59.44 | 0.00 | 0.00 |
| September | 0.191799E+10 | -0.175013E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -167863540.9 | 59.44 | 0.00 | 0.00 |
| October | 0.204683E+10 | -0.186562E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -181204202.1 | 59.44 | 0.00 | 0.00 |
| November | 0.205731E+10 | -0.187757E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -179746503.4 | 59.44 | 0.00 | 0.00 |
| December | 0.219865E+10 | -0.201205E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186602598.5 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.248466E+11 | -0.227289E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.211764E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.191799E+10 | -0.206265E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -186604750.0 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.224926E+10 | -0.175013E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -167432646.1 | 59.44 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: M N1 APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.224924E+10 | -0.206265E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186580908.0 | 59.44 | 0.00 | 0.00 |
| February | 0.204375E+10 | -0.187590E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -167846588.5 | 59.44 | 0.00 | 0.00 |
| March | 0.223826E+10 | -0.205362E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -184639784.4 | 59.44 | 0.00 | 0.00 |
| April | 0.210652E+10 | -0.193299E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -173535361.3 | 59.44 | 0.00 | 0.00 |
| May | 0.209683E+10 | -0.192310E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -173732143.9 | 59.44 | 0.00 | 0.00 |
| June | 0.195816E+10 | -0.179105E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -167111684.7 | 59.44 | 0.00 | 0.00 |
| July | 0.197245E+10 | -0.179995E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172500917.5 | 59.44 | 0.00 | 0.00 |
| August | 0.195680E+10 | -0.178430E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172505529.7 | 59.44 | 0.00 | 0.00 |
| September | 0.191735E+10 | -0.175013E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -167220268.9 | 59.44 | 0.00 | 0.00 |
| October | 0.204457E+10 | -0.186563E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -178940430.9 | 59.44 | 0.00 | 0.00 |
| November | 0.205648E+10 | -0.187757E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -178912194.3 | 59.44 | 0.00 | 0.00 |
| December | 0.219865E+10 | -0.201205E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186594816.8 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.248390E+11 | -0.227289E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.211012E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.191735E+10 | -0.206265E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -186594816.8 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.224924E+10 | -0.175013E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -167111684.7 | 59.44 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: M N2 APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.224924E+10 | -0.206265E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186580778.5 | 59.44 | 0.00 | 0.00 |
| February | 0.204375E+10 | -0.187590E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -167848359.3 | 59.44 | 0.00 | 0.00 |
| March | 0.223827E+10 | -0.205362E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -184648818.3 | 59.44 | 0.00 | 0.00 |
| April | 0.210644E+10 | -0.193299E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -173458527.2 | 59.44 | 0.00 | 0.00 |
| May | 0.209684E+10 | -0.192310E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -173737540.5 | 59.44 | 0.00 | 0.00 |
| June | 0.195816E+10 | -0.179105E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -167110642.8 | 59.44 | 0.00 | 0.00 |
| July | 0.197245E+10 | -0.179995E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172501314.6 | 59.44 | 0.00 | 0.00 |
| August | 0.195680E+10 | -0.178430E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172505953.5 | 59.44 | 0.00 | 0.00 |
| September | 0.191736E+10 | -0.175013E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -167228359.2 | 59.44 | 0.00 | 0.00 |
| October | 0.204456E+10 | -0.186563E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -178933912.0 | 59.44 | 0.00 | 0.00 |
| November | 0.205648E+10 | -0.187757E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -178913674.6 | 59.44 | 0.00 | 0.00 |
| December | 0.219865E+10 | -0.201205E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186595723.8 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.248390E+11 | -0.227289E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.211006E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.191736E+10 | -0.206265E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -186595723.8 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.224924E+10 | -0.175013E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -167110642.8 | 59.44 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: M S1 APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.224879E+10 | -0.206265E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186141786.9 | 59.44 | 0.00 | 0.00 |
| February | 0.204169E+10 | -0.187589E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -165796196.0 | 59.44 | 0.00 | 0.00 |
| March | 0.223315E+10 | -0.205362E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -179536032.9 | 59.44 | 0.00 | 0.00 |
| April | 0.210275E+10 | -0.193299E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -169764765.6 | 59.44 | 0.00 | 0.00 |
| May | 0.209636E+10 | -0.192310E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -173259847.3 | 59.44 | 0.00 | 0.00 |
| June | 0.195811E+10 | -0.179105E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -167059726.5 | 59.44 | 0.00 | 0.00 |
| July | 0.197245E+10 | -0.179995E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172494542.9 | 59.44 | 0.00 | 0.00 |
| August | 0.195679E+10 | -0.178430E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172493366.9 | 59.44 | 0.00 | 0.00 |
| September | 0.191716E+10 | -0.175013E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -167030446.3 | 59.44 | 0.00 | 0.00 |
| October | 0.204083E+10 | -0.186563E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -175196920.4 | 59.44 | 0.00 | 0.00 |
| November | 0.205453E+10 | -0.187757E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -176962934.1 | 59.44 | 0.00 | 0.00 |
| December | 0.219723E+10 | -0.201205E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -185178004.5 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.248198E+11 | -0.227289E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.209091E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.191716E+10 | -0.206265E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -186141786.9 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.224879E+10 | -0.175013E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -165796196.0 | 59.44 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: M S2 APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.224880E+10 | -0.206265E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186142511.2 | 59.44 | 0.00 | 0.00 |
| February | 0.204169E+10 | -0.187589E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -165799959.7 | 59.44 | 0.00 | 0.00 |
| March | 0.223314E+10 | -0.205362E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -179522046.4 | 59.44 | 0.00 | 0.00 |
| April | 0.210271E+10 | -0.193299E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -169722306.2 | 59.44 | 0.00 | 0.00 |
| May | 0.209637E+10 | -0.192310E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -173268408.3 | 59.44 | 0.00 | 0.00 |
| June | 0.195811E+10 | -0.179105E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -167060476.6 | 59.44 | 0.00 | 0.00 |
| July | 0.197245E+10 | -0.179995E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172494598.4 | 59.44 | 0.00 | 0.00 |
| August | 0.195679E+10 | -0.178430E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172493551.1 | 59.44 | 0.00 | 0.00 |
| September | 0.191716E+10 | -0.175013E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -167033759.8 | 59.44 | 0.00 | 0.00 |
| October | 0.204082E+10 | -0.186563E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -175192687.1 | 59.44 | 0.00 | 0.00 |
| November | 0.205453E+10 | -0.187757E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -176961159.6 | 59.44 | 0.00 | 0.00 |
| December | 0.219723E+10 | -0.201205E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -185181744.7 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.248198E+11 | -0.227289E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.209087E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.191716E+10 | -0.206265E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -186142511.2 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.224880E+10 | -0.175013E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -165799959.7 | 59.44 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: T SW APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.121779E+10 | -0.103132E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186469555.9 | 59.44 | 0.00 | 0.00 |
| February | 0.110530E+10 | -937945807.6 | 0.00 | 0.00 | 672.00 | 0.00 | -167351314.3 | 59.44 | 0.00 | 0.00 |
| March | 0.121078E+10 | -0.102681E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -183975467.3 | 59.44 | 0.00 | 0.00 |
| April | 0.114180E+10 | -966491372.6 | 0.00 | 0.00 | 720.00 | 0.00 | -175311866.2 | 59.44 | 0.00 | 0.00 |
| May | 0.114031E+10 | -961547325.9 | 0.00 | 0.00 | 744.00 | 0.00 | -178764425.4 | 59.44 | 0.00 | 0.00 |
| June | 0.106591E+10 | -895519527.7 | 0.00 | 0.00 | 720.00 | 0.00 | -170386686.8 | 59.44 | 0.00 | 0.00 |
| July | 0.107427E+10 | -899976297.8 | 0.00 | 0.00 | 744.00 | 0.00 | -174288810.7 | 59.44 | 0.00 | 0.00 |
| August | 0.106635E+10 | -892146200.8 | 0.00 | 0.00 | 744.00 | 0.00 | -174207961.9 | 59.44 | 0.00 | 0.00 |
| September | 0.104630E+10 | -875058969.6 | 0.00 | 0.00 | 720.00 | 0.00 | -171236177.7 | 59.44 | 0.00 | 0.00 |
| October | 0.111508E+10 | -932811371.4 | 0.00 | 0.00 | 744.00 | 0.00 | -182271184.7 | 59.44 | 0.00 | 0.00 |
| November | 0.111840E+10 | -938782627.8 | 0.00 | 0.00 | 720.00 | 0.00 | -179614235.9 | 59.44 | 0.00 | 0.00 |
| December | 0.119213E+10 | -0.100602E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186108490.7 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.134944E+11 | -0.113644E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.212999E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.104630E+10 | -0.103132E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -186469555.9 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.121779E+10 | -875058969.6 | 0.00 | 0.00 | 744.00 | 0.00 | -167351314.3 | 59.44 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: T NW APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.121793E+10 | -0.103132E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186602669.2 | 59.44 | 0.00 | 0.00 |
| February | 0.110628E+10 | -937946064.5 | 0.00 | 0.00 | 672.00 | 0.00 | -168330291.7 | 59.44 | 0.00 | 0.00 |
| March | 0.121262E+10 | -0.102681E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -185812491.9 | 59.44 | 0.00 | 0.00 |
| April | 0.114341E+10 | -966491810.8 | 0.00 | 0.00 | 720.00 | 0.00 | -176922296.3 | 59.44 | 0.00 | 0.00 |
| May | 0.114107E+10 | -961548767.9 | 0.00 | 0.00 | 744.00 | 0.00 | -179522926.3 | 59.44 | 0.00 | 0.00 |
| June | 0.106616E+10 | -895519154.4 | 0.00 | 0.00 | 720.00 | 0.00 | -170640069.8 | 59.44 | 0.00 | 0.00 |
| July | 0.107437E+10 | -899969399.5 | 0.00 | 0.00 | 744.00 | 0.00 | -174403590.1 | 59.44 | 0.00 | 0.00 |
| August | 0.106659E+10 | -892148238.1 | 0.00 | 0.00 | 744.00 | 0.00 | -174443647.6 | 59.44 | 0.00 | 0.00 |
| September | 0.104753E+10 | -875060833.9 | 0.00 | 0.00 | 720.00 | 0.00 | -172471244.3 | 59.44 | 0.00 | 0.00 |
| October | 0.111764E+10 | -932812143.5 | 0.00 | 0.00 | 744.00 | 0.00 | -184824558.8 | 59.44 | 0.00 | 0.00 |
| November | 0.111907E+10 | -938781895.8 | 0.00 | 0.00 | 720.00 | 0.00 | -180292893.2 | 59.44 | 0.00 | 0.00 |
| December | 0.119263E+10 | -0.100602E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186602218.8 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.135053E+11 | -0.113644E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.214087E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.104753E+10 | -0.103132E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -186602669.2 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.121793E+10 | -875060833.9 | 0.00 | 0.00 | 744.00 | 0.00 | -168330291.7 | 59.44 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: T SE APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.121782E+10 | -0.103132E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186494969.2 | 59.44 | 0.00 | 0.00 |
| February | 0.110534E+10 | -937945580.1 | 0.00 | 0.00 | 672.00 | 0.00 | -167393876.5 | 59.44 | 0.00 | 0.00 |
| March | 0.121072E+10 | -0.102681E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -183916723.0 | 59.44 | 0.00 | 0.00 |
| April | 0.114146E+10 | -966491970.1 | 0.00 | 0.00 | 720.00 | 0.00 | -174966459.5 | 59.44 | 0.00 | 0.00 |
| May | 0.114018E+10 | -961547517.9 | 0.00 | 0.00 | 744.00 | 0.00 | -178628875.7 | 59.44 | 0.00 | 0.00 |
| June | 0.106562E+10 | -895521584.7 | 0.00 | 0.00 | 720.00 | 0.00 | -170095073.2 | 59.44 | 0.00 | 0.00 |
| July | 0.107421E+10 | -899969736.0 | 0.00 | 0.00 | 744.00 | 0.00 | -174236274.2 | 59.44 | 0.00 | 0.00 |
| August | 0.106619E+10 | -892146163.3 | 0.00 | 0.00 | 744.00 | 0.00 | -174044112.1 | 59.44 | 0.00 | 0.00 |
| September | 0.104633E+10 | -875062809.8 | 0.00 | 0.00 | 720.00 | 0.00 | -171270209.1 | 59.44 | 0.00 | 0.00 |
| October | 0.111495E+10 | -932811133.4 | 0.00 | 0.00 | 744.00 | 0.00 | -182139172.4 | 59.44 | 0.00 | 0.00 |
| November | 0.111838E+10 | -938781216.8 | 0.00 | 0.00 | 720.00 | 0.00 | -179598753.4 | 59.44 | 0.00 | 0.00 |
| December | 0.119215E+10 | -0.100602E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186131080.9 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.134933E+11 | -0.113644E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.212892E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.104633E+10 | -0.103132E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -186494969.2 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.121782E+10 | -875062809.8 | 0.00 | 0.00 | 744.00 | 0.00 | -167393876.5 | 59.44 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: T NE APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.121793E+10 | -0.103132E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186602669.2 | 59.44 | 0.00 | 0.00 |
| February | 0.110632E+10 | -937946264.8 | 0.00 | 0.00 | 672.00 | 0.00 | -168371958.8 | 59.44 | 0.00 | 0.00 |
| March | 0.121280E+10 | -0.102681E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -185990718.4 | 59.44 | 0.00 | 0.00 |
| April | 0.114310E+10 | -966492349.6 | 0.00 | 0.00 | 720.00 | 0.00 | -176607212.7 | 59.44 | 0.00 | 0.00 |
| May | 0.114080E+10 | -961548747.5 | 0.00 | 0.00 | 744.00 | 0.00 | -179252447.0 | 59.44 | 0.00 | 0.00 |
| June | 0.106577E+10 | -895521276.8 | 0.00 | 0.00 | 720.00 | 0.00 | -170253064.8 | 59.44 | 0.00 | 0.00 |
| July | 0.107434E+10 | -899974783.2 | 0.00 | 0.00 | 744.00 | 0.00 | -174363421.9 | 59.44 | 0.00 | 0.00 |
| August | 0.106639E+10 | -892148232.3 | 0.00 | 0.00 | 744.00 | 0.00 | -174242475.5 | 59.44 | 0.00 | 0.00 |
| September | 0.104748E+10 | -875060345.2 | 0.00 | 0.00 | 720.00 | 0.00 | -172422820.2 | 59.44 | 0.00 | 0.00 |
| October | 0.111769E+10 | -932813066.4 | 0.00 | 0.00 | 744.00 | 0.00 | -184877660.2 | 59.44 | 0.00 | 0.00 |
| November | 0.111908E+10 | -938782197.5 | 0.00 | 0.00 | 720.00 | 0.00 | -180302488.6 | 59.44 | 0.00 | 0.00 |
| December | 0.119262E+10 | -0.100602E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186601233.4 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.135043E+11 | -0.113644E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.213989E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.104748E+10 | -0.103132E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -186602669.2 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.121793E+10 | -875060345.2 | 0.00 | 0.00 | 744.00 | 0.00 | -168371958.8 | 59.44 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: T N1 APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.121793E+10 | -0.103132E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186602669.1 | 59.44 | 0.00 | 0.00 |
| February | 0.110623E+10 | -937945610.8 | 0.00 | 0.00 | 672.00 | 0.00 | -168280631.4 | 59.44 | 0.00 | 0.00 |
| March | 0.121268E+10 | -0.102681E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -185869612.2 | 59.44 | 0.00 | 0.00 |
| April | 0.114308E+10 | -966491671.7 | 0.00 | 0.00 | 720.00 | 0.00 | -176592450.9 | 59.44 | 0.00 | 0.00 |
| May | 0.114023E+10 | -961548111.1 | 0.00 | 0.00 | 744.00 | 0.00 | -178681175.9 | 59.44 | 0.00 | 0.00 |
| June | 0.106507E+10 | -895523021.6 | 0.00 | 0.00 | 720.00 | 0.00 | -169544971.4 | 59.44 | 0.00 | 0.00 |
| July | 0.107362E+10 | -899974715.8 | 0.00 | 0.00 | 744.00 | 0.00 | -173643192.1 | 59.44 | 0.00 | 0.00 |
| August | 0.106583E+10 | -892147206.9 | 0.00 | 0.00 | 744.00 | 0.00 | -173685138.5 | 59.44 | 0.00 | 0.00 |
| September | 0.104646E+10 | -875057875.3 | 0.00 | 0.00 | 720.00 | 0.00 | -171399263.7 | 59.44 | 0.00 | 0.00 |
| October | 0.111742E+10 | -932811272.9 | 0.00 | 0.00 | 744.00 | 0.00 | -184609116.3 | 59.44 | 0.00 | 0.00 |
| November | 0.111894E+10 | -938784492.7 | 0.00 | 0.00 | 720.00 | 0.00 | -180157271.0 | 59.44 | 0.00 | 0.00 |
| December | 0.119262E+10 | -0.100602E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186601558.7 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.135001E+11 | -0.113644E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.213567E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.104646E+10 | -0.103132E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -186602669.1 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.121793E+10 | -875057875.3 | 0.00 | 0.00 | 744.00 | 0.00 | -168280631.4 | 59.44 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: T N2 APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.121793E+10 | -0.103132E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186602669.1 | 59.44 | 0.00 | 0.00 |
| February | 0.110623E+10 | -937945615.4 | 0.00 | 0.00 | 672.00 | 0.00 | -168283871.5 | 59.44 | 0.00 | 0.00 |
| March | 0.121268E+10 | -0.102681E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -185876796.4 | 59.44 | 0.00 | 0.00 |
| April | 0.114304E+10 | -966491613.8 | 0.00 | 0.00 | 720.00 | 0.00 | -176553355.3 | 59.44 | 0.00 | 0.00 |
| May | 0.114021E+10 | -961548337.2 | 0.00 | 0.00 | 744.00 | 0.00 | -178664924.3 | 59.44 | 0.00 | 0.00 |
| June | 0.106504E+10 | -895523335.8 | 0.00 | 0.00 | 720.00 | 0.00 | -169520138.7 | 59.44 | 0.00 | 0.00 |
| July | 0.107363E+10 | -899975096.4 | 0.00 | 0.00 | 744.00 | 0.00 | -173655179.4 | 59.44 | 0.00 | 0.00 |
| August | 0.106583E+10 | -892148161.0 | 0.00 | 0.00 | 744.00 | 0.00 | -173677850.7 | 59.44 | 0.00 | 0.00 |
| September | 0.104648E+10 | -875059350.0 | 0.00 | 0.00 | 720.00 | 0.00 | -171417426.2 | 59.44 | 0.00 | 0.00 |
| October | 0.111742E+10 | -932810590.3 | 0.00 | 0.00 | 744.00 | 0.00 | -184610773.0 | 59.44 | 0.00 | 0.00 |
| November | 0.111894E+10 | -938783719.5 | 0.00 | 0.00 | 720.00 | 0.00 | -180159565.9 | 59.44 | 0.00 | 0.00 |
| December | 0.119262E+10 | -0.100602E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186601358.5 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.135001E+11 | -0.113644E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.213562E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.104648E+10 | -0.103132E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -186602669.1 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.121793E+10 | -875059350.0 | 0.00 | 0.00 | 744.00 | 0.00 | -168283871.5 | 59.44 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: T S1 APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.121770E+10 | -0.103132E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186371677.5 | 59.44 | 0.00 | 0.00 |
| February | 0.110487E+10 | -937947645.0 | 0.00 | 0.00 | 672.00 | 0.00 | -166917356.2 | 59.44 | 0.00 | 0.00 |
| March | 0.121017E+10 | -0.102681E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -183360540.6 | 59.44 | 0.00 | 0.00 |
| April | 0.114089E+10 | -966490876.5 | 0.00 | 0.00 | 720.00 | 0.00 | -174399947.3 | 59.44 | 0.00 | 0.00 |
| May | 0.113927E+10 | -961549479.6 | 0.00 | 0.00 | 744.00 | 0.00 | -177718499.2 | 59.44 | 0.00 | 0.00 |
| June | 0.106484E+10 | -895520938.1 | 0.00 | 0.00 | 720.00 | 0.00 | -169315471.4 | 59.44 | 0.00 | 0.00 |
| July | 0.107352E+10 | -899974916.9 | 0.00 | 0.00 | 744.00 | 0.00 | -173543997.8 | 59.44 | 0.00 | 0.00 |
| August | 0.106563E+10 | -892146914.8 | 0.00 | 0.00 | 744.00 | 0.00 | -173479701.6 | 59.44 | 0.00 | 0.00 |
| September | 0.104506E+10 | -875059471.5 | 0.00 | 0.00 | 720.00 | 0.00 | -169999676.6 | 59.44 | 0.00 | 0.00 |
| October | 0.111397E+10 | -932810875.3 | 0.00 | 0.00 | 744.00 | 0.00 | -181156877.5 | 59.44 | 0.00 | 0.00 |
| November | 0.111802E+10 | -938781893.0 | 0.00 | 0.00 | 720.00 | 0.00 | -179233355.7 | 59.44 | 0.00 | 0.00 |
| December | 0.119190E+10 | -0.100602E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -185876200.0 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.134858E+11 | -0.113644E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.212137E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.104506E+10 | -0.103132E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -186371677.5 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.121770E+10 | -875059471.5 | 0.00 | 0.00 | 744.00 | 0.00 | -166917356.2 | 59.44 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: T S2 APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.121770E+10 | -0.103132E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186372584.0 | 59.44 | 0.00 | 0.00 |
| February | 0.110487E+10 | -937947645.9 | 0.00 | 0.00 | 672.00 | 0.00 | -166919084.7 | 59.44 | 0.00 | 0.00 |
| March | 0.121016E+10 | -0.102681E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -183354681.0 | 59.44 | 0.00 | 0.00 |
| April | 0.114086E+10 | -966491100.9 | 0.00 | 0.00 | 720.00 | 0.00 | -174373367.1 | 59.44 | 0.00 | 0.00 |
| May | 0.113928E+10 | -961549458.3 | 0.00 | 0.00 | 744.00 | 0.00 | -177727359.2 | 59.44 | 0.00 | 0.00 |
| June | 0.106483E+10 | -895520797.1 | 0.00 | 0.00 | 720.00 | 0.00 | -169306583.3 | 59.44 | 0.00 | 0.00 |
| July | 0.107353E+10 | -899974481.2 | 0.00 | 0.00 | 744.00 | 0.00 | -173555308.8 | 59.44 | 0.00 | 0.00 |
| August | 0.106562E+10 | -892146747.1 | 0.00 | 0.00 | 744.00 | 0.00 | -173477696.5 | 59.44 | 0.00 | 0.00 |
| September | 0.104508E+10 | -875059592.2 | 0.00 | 0.00 | 720.00 | 0.00 | -170020495.9 | 59.44 | 0.00 | 0.00 |
| October | 0.111396E+10 | -932810728.3 | 0.00 | 0.00 | 744.00 | 0.00 | -181153788.9 | 59.44 | 0.00 | 0.00 |
| November | 0.111801E+10 | -938781736.4 | 0.00 | 0.00 | 720.00 | 0.00 | -179230776.9 | 59.44 | 0.00 | 0.00 |
| December | 0.119190E+10 | -0.100602E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -185877085.4 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.134858E+11 | -0.113644E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.212137E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.104508E+10 | -0.103132E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -186372584.0 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.121770E+10 | -875059592.2 | 0.00 | 0.00 | 744.00 | 0.00 | -166919084.7 | 59.44 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
| January | 237.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 259.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 247.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 379.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 427.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 375.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 471.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 366.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 301.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 245.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 242.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 160.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 3714.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 160.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 471.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT GSW HEATING COIL
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.206796E+10 | 1404.01 | 15-JAN-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.138995E+10 | 1731.65 | 19-FEB-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.811924E+09 | 993.28 | 24-MAR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.363366E+09 | 869.73 | 19-APR-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 5905483.32 | 168.38 | 29-MAY-03:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 70205233.40 | 458.76 | 28-OCT-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.833405E+09 | 927.81 | 30-NOV-01:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.166104E+10 | 1349.65 | 26-DEC-08:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.720376E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.206796E+10 | 1731.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT GNW HEATING COIL
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.249148E+10 | 1580.35 | 15-JAN-08:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.192418E+10 | 1888.91 | 19-FEB-08:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.133125E+10 | 1169.47 | 25-MAR-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.649418E+09 | 1090.81 | 02-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 51318181.60 | 362.05 | 24-MAY-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.279547E+09 | 622.93 | 30-OCT-02:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.115656E+10 | 972.10 | 24-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.209783E+10 | 1406.80 | 26-DEC-08:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.998158E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.249148E+10 | 1888.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT OFFICE HEATING COIL
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.563950E+09 | 10221.22 | 03-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.291928E+09 | 10221.22 | 06-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 30071550.10 | 10221.22 | 06-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 6005064.54 | 7940.49 | 18-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 88899762.24 | 10221.22 | 14-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.351232E+09 | 10221.22 | 01-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.133209E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.563950E+09 | 10221.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT GNE HEATING COIL
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.249933E+10 | 1577.79 | 15-JAN-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.192507E+10 | 1840.99 | 19-FEB-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.131497E+10 | 1166.94 | 27-MAR-17:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.603978E+09 | 1043.64 | 02-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 64550224.61 | 355.52 | 24-MAY-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.272120E+09 | 632.63 | 30-OCT-02:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.115744E+10 | 1005.72 | 13-NOV-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.210520E+10 | 1409.36 | 26-DEC-08:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.994266E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.249933E+10 | 1840.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT GN1 HEATING COIL
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.165911E+10 | 1131.95 | 15-JAN-08:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.127068E+10 | 1340.00 | 19-FEB-08:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.789062E+09 | 776.23 | 25-MAR-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.344096E+09 | 648.00 | 19-APR-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 208440.63 | 42.99 | 29-MAY-02:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 76775606.40 | 377.76 | 30-OCT-02:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.677280E+09 | 681.51 | 13-NOV-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.136597E+10 | 995.09 | 26-DEC-08:19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.618319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.165911E+10 | 1340.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT GN2 HEATING COIL
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.165949E+10 | 1132.50 | 15-JAN-08:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.127083E+10 | 1338.10 | 19-FEB-08:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.789168E+09 | 774.26 | 25-MAR-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.341847E+09 | 648.19 | 19-APR-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 275790.80 | 47.91 | 29-MAY-02:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 76539482.83 | 377.88 | 30-OCT-02:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.677452E+09 | 683.88 | 13-NOV-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.136640E+10 | 995.09 | 26-DEC-08:19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.618200E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.165949E+10 | 1338.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT GS1 HEATING COIL
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.126298E+10 | 951.87 | 15-JAN-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.782964E+09 | 1196.68 | 19-FEB-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.324889E+09 | 613.66 | 24-MAR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.110229E+09 | 553.19 | 19-APR-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 129719.86 | 39.41 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.394032E+09 | 577.34 | 30-NOV-01:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.962186E+09 | 936.86 | 26-DEC-08:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.383741E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.126298E+10 | 1196.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT GS2 HEATING COIL
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.142958E+10 | 1047.71 | 15-JAN-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.873595E+09 | 1309.56 | 19-FEB-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.337096E+09 | 625.61 | 24-MAR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.105637E+09 | 564.74 | 19-APR-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.425911E+09 | 614.54 | 24-NOV-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.106645E+10 | 1055.61 | 26-DEC-08:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.423827E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.142958E+10 | 1309.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT MSW HEATING COIL
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.286591E+10 | 2421.95 | 15-JAN-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.156506E+10 | 3058.47 | 19-FEB-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.333916E+09 | 1459.99 | 24-MAR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 67016521.38 | 947.28 | 19-APR-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 24031439.08 | 702.77 | 31-OCT-22:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.122532E+10 | 1866.68 | 29-NOV-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.238100E+10 | 2403.72 | 26-DEC-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.846225E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.286591E+10 | 3058.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT MNW HEATING COIL
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.368149E+10 | 2755.10 | 15-JAN-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.251298E+10 | 3295.77 | 19-FEB-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.101834E+10 | 1839.97 | 24-MAR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.188289E+09 | 1378.64 | 19-APR-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.199193E+09 | 1032.58 | 30-OCT-02:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.180951E+10 | 1915.34 | 30-NOV-01:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.321833E+10 | 2467.85 | 26-DEC-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.126281E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.368149E+10 | 3295.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT MSE HEATING COIL
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.287519E+10 | 2453.73 | 15-JAN-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.155886E+10 | 3049.97 | 19-FEB-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.302262E+09 | 1501.88 | 24-MAR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 65517180.30 | 948.93 | 19-APR-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 24740103.67 | 723.21 | 31-OCT-22:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.122858E+10 | 1863.52 | 30-NOV-01:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.239158E+10 | 2422.97 | 26-DEC-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.844673E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.287519E+10 | 3049.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT MNE HEATING COIL
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.369600E+10 | 2800.62 | 15-JAN-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.251342E+10 | 3286.09 | 19-FEB-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.977063E+09 | 1860.69 | 24-MAR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.166848E+09 | 1383.71 | 19-APR-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.196421E+09 | 1095.64 | 30-OCT-02:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.181097E+10 | 1911.44 | 30-NOV-01:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.323321E+10 | 2488.48 | 26-DEC-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.125939E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.369600E+10 | 3286.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT MN1 HEATING COIL
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.211761E+10 | 1834.97 | 15-JAN-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.143911E+10 | 2182.03 | 19-FEB-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.306978E+09 | 1070.13 | 05-MAR-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 23788607.25 | 580.79 | 19-APR-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 13005162.49 | 342.12 | 31-OCT-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.849784E+09 | 1181.26 | 13-NOV-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.177421E+10 | 1596.04 | 26-DEC-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.652449E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.211761E+10 | 2182.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT MN2 HEATING COIL
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.211823E+10 | 1836.63 | 15-JAN-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.143908E+10 | 2181.08 | 19-FEB-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.306758E+09 | 1066.08 | 05-MAR-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 23582246.08 | 580.49 | 19-APR-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 13261750.40 | 347.84 | 31-OCT-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.850176E+09 | 1186.03 | 13-NOV-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.177509E+10 | 1598.22 | 26-DEC-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.652618E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.211823E+10 | 2181.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT MS1 HEATING COIL
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.132577E+10 | 1552.57 | 15-JAN-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.624552E+09 | 2030.08 | 19-FEB-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 11805882.30 | 398.53 | 06-MAR-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.375080E+09 | 1074.83 | 30-NOV-01:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.105022E+10 | 1478.62 | 26-DEC-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.338743E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.132577E+10 | 2030.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT MS2 HEATING COIL
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.132705E+10 | 1554.41 | 15-JAN-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.624469E+09 | 2029.29 | 19-FEB-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 11439295.35 | 392.50 | 06-MAR-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.375309E+09 | 1074.51 | 30-NOV-01:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.105106E+10 | 1478.49 | 26-DEC-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.338932E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.132705E+10 | 2029.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT TSW HEATING COIL
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.287629E+10 | 2238.69 | 15-JAN-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.189854E+10 | 2663.71 | 19-FEB-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.122258E+10 | 1642.97 | 24-MAR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.592991E+09 | 1472.04 | 11-APR-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.212742E+09 | 1278.68 | 18-MAY-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 28125506.87 | 762.54 | 15-JUN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 37086954.38 | 708.53 | 27-SEP-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.607109E+09 | 1211.53 | 28-OCT-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.171785E+10 | 1650.80 | 30-NOV-01:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.258081E+10 | 1990.41 | 26-DEC-08:45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.117741E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.287629E+10 | 2663.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT TNW HEATING COIL
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.331224E+10 | 2359.99 | 15-JAN-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.240507E+10 | 2724.34 | 19-FEB-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.157175E+10 | 1739.73 | 24-MAR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.750437E+09 | 1511.26 | 11-APR-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.240331E+09 | 1264.98 | 18-MAY-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 28923264.74 | 632.62 | 15-JUN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 55008927.22 | 739.16 | 27-SEP-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.873220E+09 | 1207.10 | 28-OCT-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.203430E+10 | 1730.07 | 11-NOV-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.302652E+10 | 2010.90 | 26-DEC-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.142978E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.331224E+10 | 2724.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT TSE HEATING COIL
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.288046E+10 | 2259.57 | 15-JAN-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.189206E+10 | 2666.61 | 19-FEB-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.119728E+10 | 1653.35 | 24-MAR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.554916E+09 | 1504.95 | 11-APR-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.210729E+09 | 1276.73 | 18-MAY-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 30579690.55 | 611.37 | 14-JUN-03:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 39392472.67 | 769.02 | 27-SEP-03:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.601618E+09 | 1209.07 | 28-OCT-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.171652E+10 | 1648.93 | 30-NOV-00:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.258549E+10 | 1998.31 | 26-DEC-08:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.117090E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.288046E+10 | 2666.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT TNE HEATING COIL
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.332007E+10 | 2380.19 | 15-JAN-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.240548E+10 | 2728.25 | 19-FEB-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.153599E+10 | 1748.04 | 24-MAR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.698628E+09 | 1544.97 | 11-APR-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.239450E+09 | 1265.40 | 18-MAY-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 31878050.42 | 634.26 | 14-JUN-03:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 59615922.04 | 797.86 | 27-SEP-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.856114E+09 | 1205.07 | 28-OCT-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.203176E+10 | 1751.47 | 11-NOV-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.303510E+10 | 2017.18 | 26-DEC-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.142141E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.332007E+10 | 2728.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT TN1 HEATING COIL
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.233134E+10 | 1762.05 | 15-JAN-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.168340E+10 | 2011.11 | 19-FEB-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.100846E+10 | 1206.97 | 02-MAR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.424851E+09 | 1054.34 | 19-APR-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 86995621.62 | 809.21 | 18-MAY-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 5010486.35 | 221.24 | 15-JUN-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 22430173.69 | 482.31 | 27-SEP-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.475918E+09 | 793.12 | 28-OCT-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.134083E+10 | 1269.64 | 11-NOV-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.212064E+10 | 1489.42 | 26-DEC-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.949987E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.233134E+10 | 2011.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT TN2 HEATING COIL
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.233179E+10 | 1763.25 | 15-JAN-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.168403E+10 | 2010.84 | 19-FEB-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.100912E+10 | 1211.06 | 02-MAR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.422856E+09 | 1054.71 | 19-APR-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 87852485.92 | 809.43 | 18-MAY-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 5387204.85 | 234.56 | 15-JUN-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 22828352.88 | 488.70 | 27-SEP-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.476770E+09 | 792.79 | 28-OCT-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.134095E+10 | 1271.10 | 11-NOV-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.212126E+10 | 1489.57 | 26-DEC-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.950284E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.233179E+10 | 2010.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT TS1 HEATING COIL
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.190552E+10 | 1629.77 | 15-JAN-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.120961E+10 | 1937.81 | 19-FEB-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.688317E+09 | 1094.61 | 24-MAR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.291461E+09 | 1007.13 | 18-APR-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 69810133.13 | 824.41 | 18-MAY-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 4376054.60 | 213.24 | 15-JUN-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 16023939.23 | 450.47 | 27-SEP-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.280572E+09 | 794.81 | 28-OCT-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.104943E+10 | 1132.19 | 24-NOV-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.169848E+10 | 1457.58 | 26-DEC-09:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.721360E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.190552E+10 | 1937.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT TS2 HEATING COIL
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.190630E+10 | 1631.15 | 15-JAN-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.121053E+10 | 1937.35 | 19-FEB-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.688568E+09 | 1096.25 | 24-MAR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.290345E+09 | 1007.28 | 18-APR-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 70564461.95 | 824.71 | 18-MAY-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 4715506.19 | 225.97 | 15-JUN-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 16398192.97 | 458.40 | 27-SEP-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.281115E+09 | 794.58 | 28-OCT-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.104975E+10 | 1132.48 | 11-NOV-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.169945E+10 | 1457.44 | 26-DEC-09:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.721773E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.190630E+10 | 1937.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT GSW COOLING COIL
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 69879514.27 | 68323616.03 | 1311.08 | 27-APR-16:07 | 1285.94 | 0.00 |
| May | 0.00 | 0.00 | 0.237133E+09 | 0.224544E+09 | 1542.78 | 15-MAY-16:15 | 1542.78 | 0.00 |
| June | 0.00 | 0.00 | 0.504005E+09 | 0.493423E+09 | 1786.47 | 28-JUN-16:40 | 1786.47 | 0.00 |
| July | 0.00 | 0.00 | 0.146726E+10 | 0.136721E+10 | 2411.89 | 31-JUL-16:15 | 2246.72 | 0.00 |
| August | 0.00 | 0.00 | 0.185796E+10 | 0.170976E+10 | 2753.73 | 10-AUG-17:20 | 2678.19 | 0.00 |
| September | 0.00 | 0.00 | 0.985892E+09 | 0.913826E+09 | 2292.84 | 14-SEP-16:02 | 2160.21 | 0.00 |
| October | 0.00 | 0.00 | 0.164378E+09 | 0.163324E+09 | 1628.75 | 04-OCT-15:10 | 1628.75 | 0.00 |
| November | 0.00 | 0.00 | 4295030.60 | 3662336.03 | 441.34 | 04-NOV-15:10 | 380.77 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.529080E+10 | 0.494407E+10 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.185796E+10 | 0.170976E+10 | 2753.73 | 2678.19 | 0.00 |
Report: CoilReportMonthly
For: SPLIT GNW COOLING COIL
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 7561143.85 | 7226750.72 | 542.00 | 27-APR-17:30 | 515.22 | 0.00 |
| May | 0.00 | 0.00 | 75952890.74 | 70325279.77 | 881.56 | 15-MAY-16:30 | 881.56 | 0.00 |
| June | 0.00 | 0.00 | 0.292256E+09 | 0.285381E+09 | 1531.18 | 28-JUN-18:00 | 1487.33 | 0.00 |
| July | 0.00 | 0.00 | 0.998129E+09 | 0.920926E+09 | 2013.97 | 24-JUL-18:00 | 1906.75 | 0.00 |
| August | 0.00 | 0.00 | 0.120395E+10 | 0.109396E+10 | 2236.38 | 10-AUG-18:00 | 2123.37 | 0.00 |
| September | 0.00 | 0.00 | 0.307762E+09 | 0.279338E+09 | 1447.84 | 14-SEP-16:25 | 1308.71 | 0.00 |
| October | 0.00 | 0.00 | 2173522.56 | 2173522.56 | 288.49 | 04-OCT-16:30 | 288.49 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.288779E+10 | 0.265933E+10 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.120395E+10 | 0.109396E+10 | 2236.38 | 2123.37 | 0.00 |
Report: CoilReportMonthly
For: SPLIT OFFICE COOLING COIL
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 549171.29 | 549171.29 | 135.55 | 27-FEB-15:30 | 135.55 | 0.00 |
| March | 0.00 | 0.00 | 7371459.68 | 7371459.68 | 352.85 | 02-MAR-14:00 | 352.85 | 0.00 |
| April | 0.00 | 0.00 | 0.131514E+09 | 0.128287E+09 | 3293.00 | 27-APR-08:63 | 3293.00 | 0.00 |
| May | 0.00 | 0.00 | 0.444120E+09 | 0.427000E+09 | 6618.38 | 05-MAY-08:62 | 6573.06 | 0.00 |
| June | 0.00 | 0.00 | 0.858888E+09 | 0.824048E+09 | 6849.32 | 12-JUN-08:62 | 5890.14 | 0.00 |
| July | 0.00 | 0.00 | 0.130980E+10 | 0.122040E+10 | 6939.97 | 31-JUL-07:02 | 6493.26 | 0.00 |
| August | 0.00 | 0.00 | 0.187310E+10 | 0.171073E+10 | 6979.71 | 30-AUG-08:62 | 5541.35 | 0.00 |
| September | 0.00 | 0.00 | 0.104129E+10 | 0.960334E+09 | 6896.49 | 25-SEP-08:62 | 5671.72 | 0.00 |
| October | 0.00 | 0.00 | 0.324380E+09 | 0.322191E+09 | 6525.76 | 04-OCT-08:62 | 6525.76 | 0.00 |
| November | 0.00 | 0.00 | 2375242.27 | 2311167.89 | 168.89 | 06-NOV-12:00 | 168.89 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.599338E+10 | 0.560321E+10 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.187310E+10 | 0.171073E+10 | 6979.71 | 6573.06 | 0.00 |
Report: CoilReportMonthly
For: SPLIT GNE COOLING COIL
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 3976557.35 | 3805261.68 | 307.76 | 27-APR-18:00 | 291.71 | 0.00 |
| May | 0.00 | 0.00 | 55994218.90 | 51518487.38 | 631.79 | 06-MAY-13:30 | 543.36 | 0.00 |
| June | 0.00 | 0.00 | 0.302252E+09 | 0.293888E+09 | 1206.26 | 28-JUN-18:00 | 1170.15 | 0.00 |
| July | 0.00 | 0.00 | 0.881836E+09 | 0.812714E+09 | 1758.00 | 24-JUL-18:00 | 1659.91 | 0.00 |
| August | 0.00 | 0.00 | 0.120621E+10 | 0.109164E+10 | 1769.83 | 10-AUG-17:07 | 1692.81 | 0.00 |
| September | 0.00 | 0.00 | 0.284029E+09 | 0.255026E+09 | 1155.65 | 14-SEP-16:40 | 1042.54 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.273430E+10 | 0.250859E+10 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.120621E+10 | 0.109164E+10 | 1769.83 | 1692.81 | 0.00 |
Report: CoilReportMonthly
For: SPLIT GN1 COOLING COIL
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 220658.80 | 208264.20 | 72.49 | 27-APR-18:00 | 68.34 | 0.00 |
| May | 0.00 | 0.00 | 43432503.66 | 39281579.11 | 523.85 | 05-MAY-16:10 | 465.39 | 0.00 |
| June | 0.00 | 0.00 | 0.237707E+09 | 0.230332E+09 | 1040.39 | 28-JUN-18:00 | 1007.98 | 0.00 |
| July | 0.00 | 0.00 | 0.786698E+09 | 0.719460E+09 | 1439.20 | 24-JUL-18:00 | 1349.96 | 0.00 |
| August | 0.00 | 0.00 | 0.103043E+10 | 0.925664E+09 | 1478.76 | 10-AUG-18:40 | 1368.61 | 0.00 |
| September | 0.00 | 0.00 | 0.240743E+09 | 0.215515E+09 | 977.41 | 14-SEP-16:50 | 871.38 | 0.00 |
| October | 0.00 | 0.00 | 135154.54 | 135154.54 | 89.57 | 04-OCT-16:10 | 89.57 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.233937E+10 | 0.213060E+10 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.103043E+10 | 0.925664E+09 | 1478.76 | 1368.61 | 0.00 |
Report: CoilReportMonthly
For: SPLIT GN2 COOLING COIL
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 218776.80 | 206491.76 | 71.59 | 27-APR-18:00 | 67.49 | 0.00 |
| May | 0.00 | 0.00 | 43192833.43 | 39074059.75 | 523.09 | 06-MAY-15:10 | 456.07 | 0.00 |
| June | 0.00 | 0.00 | 0.241267E+09 | 0.233680E+09 | 1035.40 | 28-JUN-18:00 | 1003.14 | 0.00 |
| July | 0.00 | 0.00 | 0.778772E+09 | 0.712294E+09 | 1435.10 | 24-JUL-18:00 | 1346.10 | 0.00 |
| August | 0.00 | 0.00 | 0.103182E+10 | 0.926834E+09 | 1470.04 | 10-AUG-18:40 | 1360.37 | 0.00 |
| September | 0.00 | 0.00 | 0.239339E+09 | 0.214141E+09 | 974.37 | 14-SEP-16:50 | 868.88 | 0.00 |
| October | 0.00 | 0.00 | 39992.01 | 39992.01 | 34.91 | 04-OCT-16:30 | 34.91 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.233465E+10 | 0.212627E+10 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.103182E+10 | 0.926834E+09 | 1470.04 | 1360.37 | 0.00 |
Report: CoilReportMonthly
For: SPLIT GS1 COOLING COIL
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 54497159.81 | 53076599.09 | 945.95 | 27-APR-15:10 | 936.95 | 0.00 |
| May | 0.00 | 0.00 | 0.217304E+09 | 0.204717E+09 | 1118.95 | 07-MAY-16:07 | 980.77 | 0.00 |
| June | 0.00 | 0.00 | 0.488920E+09 | 0.475276E+09 | 1282.40 | 28-JUN-16:05 | 1282.40 | 0.00 |
| July | 0.00 | 0.00 | 0.128797E+10 | 0.119361E+10 | 1822.89 | 24-JUL-15:10 | 1759.13 | 0.00 |
| August | 0.00 | 0.00 | 0.172700E+10 | 0.157783E+10 | 2112.91 | 10-AUG-15:10 | 1996.67 | 0.00 |
| September | 0.00 | 0.00 | 0.101435E+10 | 0.935334E+09 | 1923.21 | 14-SEP-14:10 | 1715.75 | 0.00 |
| October | 0.00 | 0.00 | 0.233480E+09 | 0.231315E+09 | 1406.11 | 04-OCT-15:10 | 1406.11 | 0.00 |
| November | 0.00 | 0.00 | 5692363.14 | 4870754.99 | 448.38 | 04-NOV-14:10 | 381.75 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.502921E+10 | 0.467603E+10 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.172700E+10 | 0.157783E+10 | 2112.91 | 1996.67 | 0.00 |
Report: CoilReportMonthly
For: SPLIT GS2 COOLING COIL
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 60561368.41 | 58933593.61 | 984.33 | 27-APR-15:10 | 975.11 | 0.00 |
| May | 0.00 | 0.00 | 0.247275E+09 | 0.233353E+09 | 1185.91 | 07-MAY-16:07 | 1042.69 | 0.00 |
| June | 0.00 | 0.00 | 0.567087E+09 | 0.550708E+09 | 1332.15 | 28-JUN-15:10 | 1332.15 | 0.00 |
| July | 0.00 | 0.00 | 0.142065E+10 | 0.131816E+10 | 1905.63 | 24-JUL-15:10 | 1841.39 | 0.00 |
| August | 0.00 | 0.00 | 0.190341E+10 | 0.174125E+10 | 2186.46 | 13-AUG-16:05 | 2000.07 | 0.00 |
| September | 0.00 | 0.00 | 0.112392E+10 | 0.103815E+10 | 1990.60 | 14-SEP-14:10 | 1781.04 | 0.00 |
| October | 0.00 | 0.00 | 0.257942E+09 | 0.255452E+09 | 1440.64 | 04-OCT-15:10 | 1440.64 | 0.00 |
| November | 0.00 | 0.00 | 7294199.41 | 6265940.82 | 519.69 | 04-NOV-14:10 | 444.39 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.558814E+10 | 0.520227E+10 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.190341E+10 | 0.174125E+10 | 2186.46 | 2000.07 | 0.00 |
Report: CoilReportMonthly
For: SPLIT MSW COOLING COIL
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 14787658.46 | 14786806.85 | 1648.60 | 27-FEB-15:30 | 1648.60 | 0.00 |
| March | 0.00 | 0.00 | 0.121205E+09 | 0.121205E+09 | 2181.93 | 18-MAR-16:10 | 2181.93 | 0.00 |
| April | 0.00 | 0.00 | 0.805810E+09 | 0.792004E+09 | 5444.37 | 27-APR-16:03 | 5364.62 | 0.00 |
| May | 0.00 | 0.00 | 0.192927E+10 | 0.186872E+10 | 5172.49 | 15-MAY-16:05 | 5172.49 | 0.00 |
| June | 0.00 | 0.00 | 0.264948E+10 | 0.259629E+10 | 5103.90 | 28-JUN-16:30 | 5103.90 | 0.00 |
| July | 0.00 | 0.00 | 0.463136E+10 | 0.435355E+10 | 6259.88 | 31-JUL-16:25 | 5876.70 | 0.00 |
| August | 0.00 | 0.00 | 0.511713E+10 | 0.473815E+10 | 6872.06 | 10-AUG-16:13 | 6700.36 | 0.00 |
| September | 0.00 | 0.00 | 0.318528E+10 | 0.298438E+10 | 5973.36 | 23-SEP-16:07 | 5487.17 | 0.00 |
| October | 0.00 | 0.00 | 0.784401E+09 | 0.776948E+09 | 4902.75 | 04-OCT-15:10 | 4902.75 | 0.00 |
| November | 0.00 | 0.00 | 64682619.03 | 57424876.97 | 2968.88 | 04-NOV-15:20 | 2687.61 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.193034E+11 | 0.183035E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.511713E+10 | 0.473815E+10 | 6872.06 | 6700.36 | 0.00 |
Report: CoilReportMonthly
For: SPLIT MNW COOLING COIL
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.237921E+09 | 0.231105E+09 | 3572.76 | 27-APR-17:20 | 3452.86 | 0.00 |
| May | 0.00 | 0.00 | 0.108206E+10 | 0.103559E+10 | 4013.15 | 15-MAY-16:25 | 4013.15 | 0.00 |
| June | 0.00 | 0.00 | 0.196011E+10 | 0.191498E+10 | 4526.86 | 28-JUN-18:00 | 4411.11 | 0.00 |
| July | 0.00 | 0.00 | 0.356969E+10 | 0.333119E+10 | 5377.02 | 31-JUL-17:25 | 4949.33 | 0.00 |
| August | 0.00 | 0.00 | 0.368768E+10 | 0.337666E+10 | 5688.56 | 10-AUG-17:30 | 5484.67 | 0.00 |
| September | 0.00 | 0.00 | 0.140931E+10 | 0.129677E+10 | 3926.96 | 14-SEP-16:25 | 3609.83 | 0.00 |
| October | 0.00 | 0.00 | 38146561.78 | 37718606.61 | 1777.30 | 04-OCT-16:30 | 1777.30 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.119849E+11 | 0.112240E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.368768E+10 | 0.337666E+10 | 5688.56 | 5484.67 | 0.00 |
Report: CoilReportMonthly
For: SPLIT MSE COOLING COIL
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 8223309.59 | 8223309.59 | 990.15 | 27-FEB-15:10 | 990.15 | 0.00 |
| March | 0.00 | 0.00 | 91457688.62 | 91457688.62 | 1687.41 | 02-MAR-14:00 | 1687.41 | 0.00 |
| April | 0.00 | 0.00 | 0.810275E+09 | 0.796653E+09 | 4857.33 | 27-APR-13:30 | 4857.33 | 0.00 |
| May | 0.00 | 0.00 | 0.180874E+10 | 0.175109E+10 | 4398.93 | 15-MAY-13:40 | 4398.93 | 0.00 |
| June | 0.00 | 0.00 | 0.282075E+10 | 0.276041E+10 | 4282.09 | 28-JUN-13:00 | 4216.96 | 0.00 |
| July | 0.00 | 0.00 | 0.434752E+10 | 0.408409E+10 | 5627.81 | 24-JUL-13:30 | 5396.77 | 0.00 |
| August | 0.00 | 0.00 | 0.513460E+10 | 0.474190E+10 | 6132.82 | 29-AUG-14:30 | 5668.06 | 0.00 |
| September | 0.00 | 0.00 | 0.306073E+10 | 0.286242E+10 | 5563.19 | 23-SEP-13:30 | 4991.01 | 0.00 |
| October | 0.00 | 0.00 | 0.789319E+09 | 0.783062E+09 | 4246.43 | 04-OCT-13:40 | 4246.43 | 0.00 |
| November | 0.00 | 0.00 | 57377965.58 | 50726357.97 | 2509.33 | 04-NOV-14:00 | 2220.97 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.189290E+11 | 0.179300E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.513460E+10 | 0.474190E+10 | 6132.82 | 5668.06 | 0.00 |
Report: CoilReportMonthly
For: SPLIT MNE COOLING COIL
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.211473E+09 | 0.204926E+09 | 2730.22 | 27-APR-16:10 | 2648.86 | 0.00 |
| May | 0.00 | 0.00 | 0.946196E+09 | 0.902805E+09 | 3068.76 | 06-MAY-13:30 | 2712.22 | 0.00 |
| June | 0.00 | 0.00 | 0.211998E+10 | 0.206806E+10 | 3457.41 | 28-JUN-18:00 | 3362.28 | 0.00 |
| July | 0.00 | 0.00 | 0.328682E+10 | 0.306388E+10 | 4369.22 | 24-JUL-18:00 | 4149.31 | 0.00 |
| August | 0.00 | 0.00 | 0.370600E+10 | 0.337900E+10 | 4172.66 | 10-AUG-17:10 | 4013.28 | 0.00 |
| September | 0.00 | 0.00 | 0.131345E+10 | 0.120028E+10 | 2941.58 | 14-SEP-16:25 | 2679.29 | 0.00 |
| October | 0.00 | 0.00 | 28223446.15 | 28166911.21 | 806.84 | 04-OCT-16:30 | 806.84 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.116121E+11 | 0.108471E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.370600E+10 | 0.337900E+10 | 4369.22 | 4149.31 | 0.00 |
Report: CoilReportMonthly
For: SPLIT MN1 COOLING COIL
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.154697E+09 | 0.147992E+09 | 2019.24 | 27-APR-18:00 | 1940.38 | 0.00 |
| May | 0.00 | 0.00 | 0.837510E+09 | 0.796406E+09 | 2452.68 | 05-MAY-16:10 | 2253.63 | 0.00 |
| June | 0.00 | 0.00 | 0.167977E+10 | 0.163153E+10 | 2847.17 | 28-JUN-18:00 | 2764.88 | 0.00 |
| July | 0.00 | 0.00 | 0.273551E+10 | 0.253064E+10 | 3490.49 | 24-JUL-18:00 | 3293.19 | 0.00 |
| August | 0.00 | 0.00 | 0.302005E+10 | 0.273269E+10 | 3462.56 | 10-AUG-18:40 | 3221.06 | 0.00 |
| September | 0.00 | 0.00 | 0.120174E+10 | 0.109098E+10 | 2432.06 | 14-SEP-16:50 | 2196.11 | 0.00 |
| October | 0.00 | 0.00 | 45492790.30 | 44826753.33 | 855.50 | 01-OCT-18:20 | 763.37 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.967476E+10 | 0.897507E+10 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.302005E+10 | 0.273269E+10 | 3490.49 | 3293.19 | 0.00 |
Report: CoilReportMonthly
For: SPLIT MN2 COOLING COIL
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.156018E+09 | 0.149294E+09 | 2017.58 | 27-APR-18:00 | 1938.86 | 0.00 |
| May | 0.00 | 0.00 | 0.835180E+09 | 0.794238E+09 | 2447.21 | 05-MAY-16:10 | 2248.44 | 0.00 |
| June | 0.00 | 0.00 | 0.168859E+10 | 0.164016E+10 | 2830.11 | 28-JUN-18:00 | 2748.25 | 0.00 |
| July | 0.00 | 0.00 | 0.272390E+10 | 0.252000E+10 | 3480.77 | 24-JUL-18:00 | 3284.01 | 0.00 |
| August | 0.00 | 0.00 | 0.302174E+10 | 0.273407E+10 | 3437.78 | 10-AUG-18:40 | 3197.46 | 0.00 |
| September | 0.00 | 0.00 | 0.119523E+10 | 0.108488E+10 | 2419.98 | 14-SEP-16:50 | 2185.36 | 0.00 |
| October | 0.00 | 0.00 | 45620543.57 | 45011424.62 | 755.54 | 04-OCT-17:00 | 755.54 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.966628E+10 | 0.896766E+10 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.302174E+10 | 0.273407E+10 | 3480.77 | 3284.01 | 0.00 |
Report: CoilReportMonthly
For: SPLIT MS1 COOLING COIL
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 27081806.38 | 27057835.44 | 1461.63 | 27-FEB-15:10 | 1461.63 | 0.00 |
| March | 0.00 | 0.00 | 0.175811E+09 | 0.175811E+09 | 2035.18 | 02-MAR-14:00 | 2035.18 | 0.00 |
| April | 0.00 | 0.00 | 0.801853E+09 | 0.786387E+09 | 4093.24 | 27-APR-14:30 | 4093.24 | 0.00 |
| May | 0.00 | 0.00 | 0.174559E+10 | 0.168882E+10 | 3622.67 | 04-MAY-14:10 | 3567.01 | 0.00 |
| June | 0.00 | 0.00 | 0.239621E+10 | 0.233836E+10 | 3397.34 | 28-JUN-15:10 | 3397.34 | 0.00 |
| July | 0.00 | 0.00 | 0.381255E+10 | 0.356265E+10 | 4431.76 | 31-JUL-14:10 | 4130.98 | 0.00 |
| August | 0.00 | 0.00 | 0.447339E+10 | 0.411037E+10 | 5211.12 | 29-AUG-14:30 | 4789.16 | 0.00 |
| September | 0.00 | 0.00 | 0.307467E+10 | 0.286493E+10 | 5046.91 | 23-SEP-13:40 | 4499.54 | 0.00 |
| October | 0.00 | 0.00 | 0.101206E+10 | 0.100134E+10 | 4021.85 | 04-OCT-14:10 | 4021.85 | 0.00 |
| November | 0.00 | 0.00 | 93758554.26 | 83492181.60 | 2901.49 | 04-NOV-14:00 | 2590.55 | 0.00 |
| December | 0.00 | 0.00 | 1540837.55 | 1540837.55 | 245.03 | 05-DEC-14:30 | 245.03 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.176145E+11 | 0.166408E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.447339E+10 | 0.411037E+10 | 5211.12 | 4789.16 | 0.00 |
Report: CoilReportMonthly
For: SPLIT MS2 COOLING COIL
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 26717375.47 | 26694171.85 | 1455.14 | 27-FEB-15:00 | 1455.14 | 0.00 |
| March | 0.00 | 0.00 | 0.175142E+09 | 0.175142E+09 | 2055.40 | 02-MAR-14:00 | 2055.40 | 0.00 |
| April | 0.00 | 0.00 | 0.813822E+09 | 0.798377E+09 | 4103.76 | 27-APR-14:20 | 4103.76 | 0.00 |
| May | 0.00 | 0.00 | 0.174191E+10 | 0.168530E+10 | 3629.84 | 04-MAY-14:10 | 3574.24 | 0.00 |
| June | 0.00 | 0.00 | 0.240442E+10 | 0.234638E+10 | 3398.60 | 28-JUN-14:10 | 3377.95 | 0.00 |
| July | 0.00 | 0.00 | 0.380125E+10 | 0.355223E+10 | 4445.65 | 24-JUL-13:30 | 4238.54 | 0.00 |
| August | 0.00 | 0.00 | 0.447452E+10 | 0.411133E+10 | 5223.33 | 29-AUG-14:30 | 4801.75 | 0.00 |
| September | 0.00 | 0.00 | 0.306758E+10 | 0.285823E+10 | 5053.80 | 23-SEP-13:40 | 4506.63 | 0.00 |
| October | 0.00 | 0.00 | 0.101369E+10 | 0.100306E+10 | 4025.30 | 04-OCT-14:10 | 4025.30 | 0.00 |
| November | 0.00 | 0.00 | 94095253.01 | 83799891.93 | 2914.35 | 04-NOV-14:00 | 2603.22 | 0.00 |
| December | 0.00 | 0.00 | 1627329.03 | 1627329.03 | 250.58 | 05-DEC-14:30 | 250.58 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.176148E+11 | 0.166422E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.447452E+10 | 0.411133E+10 | 5223.33 | 4801.75 | 0.00 |
Report: CoilReportMonthly
For: SPLIT TSW COOLING COIL
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 28244668.29 | 28244668.29 | 1823.37 | 27-FEB-15:30 | 1823.37 | 0.00 |
| March | 0.00 | 0.00 | 0.144054E+09 | 0.144054E+09 | 1997.32 | 14-MAR-16:05 | 1997.32 | 0.00 |
| April | 0.00 | 0.00 | 0.519277E+09 | 0.515093E+09 | 3596.00 | 27-APR-15:10 | 3563.80 | 0.00 |
| May | 0.00 | 0.00 | 0.937059E+09 | 0.908852E+09 | 3354.90 | 15-MAY-16:05 | 3354.90 | 0.00 |
| June | 0.00 | 0.00 | 0.121896E+10 | 0.120191E+10 | 3394.44 | 28-JUN-16:14 | 3394.44 | 0.00 |
| July | 0.00 | 0.00 | 0.228990E+10 | 0.216841E+10 | 4151.61 | 31-JUL-16:02 | 3931.05 | 0.00 |
| August | 0.00 | 0.00 | 0.246265E+10 | 0.230481E+10 | 4555.68 | 10-AUG-16:02 | 4462.17 | 0.00 |
| September | 0.00 | 0.00 | 0.136577E+10 | 0.129089E+10 | 3838.04 | 14-SEP-15:10 | 3598.78 | 0.00 |
| October | 0.00 | 0.00 | 0.274709E+09 | 0.273300E+09 | 2900.49 | 04-OCT-15:10 | 2900.49 | 0.00 |
| November | 0.00 | 0.00 | 53099725.60 | 48481529.34 | 2565.80 | 04-NOV-14:30 | 2367.13 | 0.00 |
| December | 0.00 | 0.00 | 3216402.04 | 3216402.04 | 284.11 | 05-DEC-14:30 | 284.11 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.929695E+10 | 0.888726E+10 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.246265E+10 | 0.230481E+10 | 4555.68 | 4462.17 | 0.00 |
Report: CoilReportMonthly
For: SPLIT TNW COOLING COIL
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 1160867.69 | 1160867.69 | 264.68 | 18-MAR-16:30 | 264.68 | 0.00 |
| April | 0.00 | 0.00 | 0.181819E+09 | 0.179420E+09 | 2576.10 | 27-APR-16:30 | 2511.02 | 0.00 |
| May | 0.00 | 0.00 | 0.535811E+09 | 0.514245E+09 | 2648.84 | 15-MAY-16:25 | 2648.84 | 0.00 |
| June | 0.00 | 0.00 | 0.878424E+09 | 0.864034E+09 | 2972.57 | 28-JUN-17:10 | 2950.23 | 0.00 |
| July | 0.00 | 0.00 | 0.173657E+10 | 0.163161E+10 | 3548.14 | 31-JUL-17:10 | 3308.35 | 0.00 |
| August | 0.00 | 0.00 | 0.174121E+10 | 0.161194E+10 | 3761.08 | 10-AUG-17:20 | 3656.81 | 0.00 |
| September | 0.00 | 0.00 | 0.550248E+09 | 0.509730E+09 | 2476.70 | 14-SEP-16:25 | 2301.64 | 0.00 |
| October | 0.00 | 0.00 | 10622191.34 | 10622191.34 | 996.02 | 04-OCT-16:30 | 996.02 | 0.00 |
| November | 0.00 | 0.00 | 3041360.10 | 2603037.32 | 409.32 | 04-NOV-16:03 | 350.28 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.563890E+10 | 0.532537E+10 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.174121E+10 | 0.163161E+10 | 3761.08 | 3656.81 | 0.00 |
Report: CoilReportMonthly
For: SPLIT TSE COOLING COIL
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 18961766.77 | 18961766.77 | 1346.02 | 27-FEB-15:00 | 1346.02 | 0.00 |
| March | 0.00 | 0.00 | 0.125851E+09 | 0.125851E+09 | 1797.42 | 14-MAR-13:40 | 1797.42 | 0.00 |
| April | 0.00 | 0.00 | 0.491740E+09 | 0.487567E+09 | 3258.07 | 27-APR-14:10 | 3258.07 | 0.00 |
| May | 0.00 | 0.00 | 0.852374E+09 | 0.825930E+09 | 2924.79 | 15-MAY-13:40 | 2924.79 | 0.00 |
| June | 0.00 | 0.00 | 0.128085E+10 | 0.126037E+10 | 2925.14 | 28-JUN-13:20 | 2892.17 | 0.00 |
| July | 0.00 | 0.00 | 0.213659E+10 | 0.201999E+10 | 3812.55 | 24-JUL-13:30 | 3678.76 | 0.00 |
| August | 0.00 | 0.00 | 0.244835E+10 | 0.228286E+10 | 4095.69 | 29-AUG-12:30 | 3823.34 | 0.00 |
| September | 0.00 | 0.00 | 0.130439E+10 | 0.122910E+10 | 3573.05 | 14-SEP-13:40 | 3225.37 | 0.00 |
| October | 0.00 | 0.00 | 0.262879E+09 | 0.262310E+09 | 2506.39 | 04-OCT-13:40 | 2506.39 | 0.00 |
| November | 0.00 | 0.00 | 46383826.66 | 42133248.26 | 2263.45 | 04-NOV-14:00 | 2066.42 | 0.00 |
| December | 0.00 | 0.00 | 1492350.25 | 1492350.25 | 158.27 | 05-DEC-12:50 | 158.27 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.896986E+10 | 0.855657E+10 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.244835E+10 | 0.228286E+10 | 4095.69 | 3823.34 | 0.00 |
Report: CoilReportMonthly
For: SPLIT TNE COOLING COIL
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.141162E+09 | 0.139068E+09 | 1928.90 | 27-APR-16:07 | 1878.20 | 0.00 |
| May | 0.00 | 0.00 | 0.434947E+09 | 0.415330E+09 | 1962.36 | 06-MAY-13:40 | 1742.68 | 0.00 |
| June | 0.00 | 0.00 | 0.923437E+09 | 0.905599E+09 | 2146.16 | 28-JUN-17:20 | 2119.09 | 0.00 |
| July | 0.00 | 0.00 | 0.158566E+10 | 0.148529E+10 | 2810.48 | 24-JUL-16:10 | 2674.64 | 0.00 |
| August | 0.00 | 0.00 | 0.172148E+10 | 0.158377E+10 | 2689.36 | 10-AUG-16:13 | 2587.65 | 0.00 |
| September | 0.00 | 0.00 | 0.482914E+09 | 0.441615E+09 | 1757.28 | 14-SEP-16:12 | 1613.28 | 0.00 |
| October | 0.00 | 0.00 | 5345861.99 | 5345861.99 | 395.71 | 04-OCT-15:10 | 395.71 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.529495E+10 | 0.497603E+10 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.172148E+10 | 0.158377E+10 | 2810.48 | 2674.64 | 0.00 |
Report: CoilReportMonthly
For: SPLIT TN1 COOLING COIL
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 96130464.58 | 94443232.17 | 1520.89 | 27-APR-16:20 | 1477.20 | 0.00 |
| May | 0.00 | 0.00 | 0.309241E+09 | 0.292378E+09 | 1504.75 | 06-MAY-13:40 | 1321.97 | 0.00 |
| June | 0.00 | 0.00 | 0.653714E+09 | 0.639409E+09 | 1850.52 | 28-JUN-17:50 | 1807.06 | 0.00 |
| July | 0.00 | 0.00 | 0.124883E+10 | 0.116269E+10 | 2300.58 | 24-JUL-18:00 | 2190.32 | 0.00 |
| August | 0.00 | 0.00 | 0.133599E+10 | 0.122231E+10 | 2271.58 | 10-AUG-16:40 | 2179.88 | 0.00 |
| September | 0.00 | 0.00 | 0.339453E+09 | 0.308337E+09 | 1492.75 | 14-SEP-16:25 | 1357.84 | 0.00 |
| October | 0.00 | 0.00 | 2199755.07 | 2199755.07 | 246.04 | 04-OCT-16:40 | 246.04 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.398555E+10 | 0.372177E+10 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.133599E+10 | 0.122231E+10 | 2300.58 | 2190.32 | 0.00 |
Report: CoilReportMonthly
For: SPLIT TN2 COOLING COIL
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 96899828.24 | 95203425.54 | 1516.59 | 27-APR-16:07 | 1474.68 | 0.00 |
| May | 0.00 | 0.00 | 0.309935E+09 | 0.293105E+09 | 1517.06 | 06-MAY-13:40 | 1333.63 | 0.00 |
| June | 0.00 | 0.00 | 0.661934E+09 | 0.647429E+09 | 1828.80 | 28-JUN-17:50 | 1785.77 | 0.00 |
| July | 0.00 | 0.00 | 0.124629E+10 | 0.116043E+10 | 2286.07 | 24-JUL-18:00 | 2176.31 | 0.00 |
| August | 0.00 | 0.00 | 0.134045E+10 | 0.122627E+10 | 2252.33 | 10-AUG-16:30 | 2158.25 | 0.00 |
| September | 0.00 | 0.00 | 0.341280E+09 | 0.309932E+09 | 1480.26 | 14-SEP-16:25 | 1346.79 | 0.00 |
| October | 0.00 | 0.00 | 2239139.34 | 2239139.34 | 238.90 | 04-OCT-16:30 | 238.90 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.399902E+10 | 0.373460E+10 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.134045E+10 | 0.122627E+10 | 2286.07 | 2176.31 | 0.00 |
Report: CoilReportMonthly
For: SPLIT TS1 COOLING COIL
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 418191.36 | 418191.36 | 162.90 | 20-JAN-13:30 | 162.90 | 0.00 |
| February | 0.00 | 0.00 | 28659083.40 | 28658577.56 | 1346.05 | 27-FEB-15:10 | 1346.05 | 0.00 |
| March | 0.00 | 0.00 | 0.121803E+09 | 0.121803E+09 | 1619.43 | 14-MAR-14:00 | 1619.43 | 0.00 |
| April | 0.00 | 0.00 | 0.407686E+09 | 0.403544E+09 | 2803.47 | 27-APR-14:30 | 2803.47 | 0.00 |
| May | 0.00 | 0.00 | 0.703934E+09 | 0.679533E+09 | 2463.72 | 04-MAY-14:10 | 2430.73 | 0.00 |
| June | 0.00 | 0.00 | 0.100532E+10 | 0.987835E+09 | 2431.04 | 28-JUN-14:10 | 2420.04 | 0.00 |
| July | 0.00 | 0.00 | 0.181201E+10 | 0.170680E+10 | 3131.54 | 24-JUL-13:40 | 3017.37 | 0.00 |
| August | 0.00 | 0.00 | 0.207511E+10 | 0.192895E+10 | 3546.16 | 29-AUG-14:30 | 3310.71 | 0.00 |
| September | 0.00 | 0.00 | 0.117135E+10 | 0.110049E+10 | 3248.20 | 23-SEP-13:50 | 2932.86 | 0.00 |
| October | 0.00 | 0.00 | 0.271984E+09 | 0.270699E+09 | 2361.43 | 04-OCT-14:10 | 2361.43 | 0.00 |
| November | 0.00 | 0.00 | 53131999.15 | 48390871.50 | 2209.73 | 04-NOV-14:00 | 2010.76 | 0.00 |
| December | 0.00 | 0.00 | 8207628.71 | 8207628.71 | 383.18 | 03-DEC-14:00 | 383.18 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.765961E+10 | 0.728533E+10 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 418191.36 | 418191.36 | 162.90 | 162.90 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.207511E+10 | 0.192895E+10 | 3546.16 | 3310.71 | 0.00 |
Report: CoilReportMonthly
For: SPLIT TS2 COOLING COIL
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 480979.62 | 480979.62 | 160.93 | 20-JAN-13:30 | 160.93 | 0.00 |
| February | 0.00 | 0.00 | 29031751.19 | 29031270.90 | 1343.35 | 27-FEB-15:00 | 1343.35 | 0.00 |
| March | 0.00 | 0.00 | 0.123345E+09 | 0.123345E+09 | 1638.33 | 14-MAR-14:00 | 1638.33 | 0.00 |
| April | 0.00 | 0.00 | 0.412243E+09 | 0.408080E+09 | 2813.20 | 27-APR-14:20 | 2813.20 | 0.00 |
| May | 0.00 | 0.00 | 0.706436E+09 | 0.682077E+09 | 2476.72 | 04-MAY-14:10 | 2443.82 | 0.00 |
| June | 0.00 | 0.00 | 0.101450E+10 | 0.996818E+09 | 2441.59 | 28-JUN-14:10 | 2430.68 | 0.00 |
| July | 0.00 | 0.00 | 0.180955E+10 | 0.170465E+10 | 3145.76 | 24-JUL-13:40 | 3031.84 | 0.00 |
| August | 0.00 | 0.00 | 0.207943E+10 | 0.193287E+10 | 3552.11 | 29-AUG-14:30 | 3317.17 | 0.00 |
| September | 0.00 | 0.00 | 0.117174E+10 | 0.110089E+10 | 3254.15 | 23-SEP-13:50 | 2939.24 | 0.00 |
| October | 0.00 | 0.00 | 0.274944E+09 | 0.273710E+09 | 2369.33 | 04-OCT-14:10 | 2369.33 | 0.00 |
| November | 0.00 | 0.00 | 53343415.04 | 48609251.59 | 2214.06 | 04-NOV-14:00 | 2015.58 | 0.00 |
| December | 0.00 | 0.00 | 8459861.56 | 8459861.56 | 385.88 | 03-DEC-14:00 | 385.88 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.768349E+10 | 0.730903E+10 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 480979.62 | 480979.62 | 160.93 | 160.93 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.207943E+10 | 0.193287E+10 | 3552.11 | 3317.17 | 0.00 |
Report: FanReportMonthly
For: SPLIT GSW SUPPLY FAN
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 93814551.55 | 0.93 | 63.69 | 15-JAN-08:00 | 0.93 |
| February | 63056303.39 | 0.82 | 78.56 | 19-FEB-06:00 | 0.93 |
| March | 36833526.38 | 0.69 | 45.06 | 24-MAR-06:00 | 0.93 |
| April | 22006269.43 | 0.45 | 102.46 | 27-APR-16:07 | 1.05 |
| May | 18799193.00 | 0.20 | 121.26 | 15-MAY-16:15 | 1.05 |
| June | 39497734.35 | 0.40 | 138.30 | 28-JUN-16:40 | 1.03 |
| July | 0.112750E+09 | 0.81 | 182.20 | 31-JUL-16:04 | 1.02 |
| August | 0.141915E+09 | 0.85 | 211.45 | 10-AUG-17:20 | 1.00 |
| September | 75515429.83 | 0.64 | 171.13 | 14-SEP-16:04 | 1.02 |
| October | 16335344.79 | 0.31 | 128.54 | 04-OCT-15:10 | 1.04 |
| November | 38138854.03 | 0.70 | 42.09 | 30-NOV-01:00 | 0.93 |
| December | 75354257.59 | 0.88 | 61.23 | 26-DEC-08:30 | 0.93 |
| Annual Sum or Average | 0.734016E+09 | 0.64 | |||
| Minimum of Months | 16335344.79 | 0.20 | 42.09 | 0.93 | |
| Maximum of Months | 0.141915E+09 | 0.93 | 211.45 | 1.05 |
Report: FanReportMonthly
For: G SW APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.64 | 20.01 | 01-JAN-00:10 | 0.64 |
| February | 48400714.57 | 0.64 | 20.01 | 01-FEB-00:10 | 0.64 |
| March | 53586505.42 | 0.64 | 20.01 | 01-MAR-00:10 | 0.64 |
| April | 51857908.47 | 0.64 | 20.01 | 01-APR-00:10 | 0.64 |
| May | 53586505.42 | 0.64 | 20.01 | 01-MAY-00:10 | 0.64 |
| June | 51857908.47 | 0.64 | 20.01 | 01-JUN-00:10 | 0.64 |
| July | 53586505.42 | 0.64 | 20.01 | 01-JUL-00:10 | 0.64 |
| August | 53586505.42 | 0.64 | 20.01 | 01-AUG-00:10 | 0.64 |
| September | 51857908.47 | 0.64 | 20.01 | 01-SEP-00:10 | 0.64 |
| October | 53586505.42 | 0.64 | 20.01 | 01-OCT-00:10 | 0.64 |
| November | 51857908.47 | 0.64 | 20.01 | 01-NOV-00:10 | 0.64 |
| December | 53586505.42 | 0.64 | 20.01 | 01-DEC-00:10 | 0.64 |
| Annual Sum or Average | 0.630938E+09 | 0.64 | |||
| Minimum of Months | 48400714.57 | 0.64 | 20.01 | 0.64 | |
| Maximum of Months | 53586505.42 | 0.64 | 20.01 | 0.64 |
Report: FanReportMonthly
For: G SW APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.64 | 20.01 | 01-JAN-00:10 | 0.64 |
| February | 48400714.57 | 0.64 | 20.01 | 01-FEB-00:10 | 0.64 |
| March | 53586505.42 | 0.64 | 20.01 | 01-MAR-00:10 | 0.64 |
| April | 51857908.47 | 0.64 | 20.01 | 01-APR-00:10 | 0.64 |
| May | 53586505.42 | 0.64 | 20.01 | 01-MAY-00:10 | 0.64 |
| June | 51857908.47 | 0.64 | 20.01 | 01-JUN-00:10 | 0.64 |
| July | 53586505.42 | 0.64 | 20.01 | 01-JUL-00:10 | 0.64 |
| August | 53586505.42 | 0.64 | 20.01 | 01-AUG-00:10 | 0.64 |
| September | 51857908.47 | 0.64 | 20.01 | 01-SEP-00:10 | 0.64 |
| October | 53586505.42 | 0.64 | 20.01 | 01-OCT-00:10 | 0.64 |
| November | 51857908.47 | 0.64 | 20.01 | 01-NOV-00:10 | 0.64 |
| December | 53586505.42 | 0.64 | 20.01 | 01-DEC-00:10 | 0.64 |
| Annual Sum or Average | 0.630938E+09 | 0.64 | |||
| Minimum of Months | 48400714.57 | 0.64 | 20.01 | 0.64 | |
| Maximum of Months | 53586505.42 | 0.64 | 20.01 | 0.64 |
Report: FanReportMonthly
For: SPLIT GNW SUPPLY FAN
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.111175E+09 | 0.93 | 70.52 | 15-JAN-08:20 | 0.93 |
| February | 85861521.35 | 0.90 | 84.29 | 19-FEB-08:10 | 0.93 |
| March | 59403444.00 | 0.88 | 52.18 | 25-MAR-07:00 | 0.94 |
| April | 29577298.36 | 0.61 | 48.67 | 02-APR-07:01 | 0.93 |
| May | 8235891.86 | 0.19 | 70.23 | 15-MAY-16:30 | 1.06 |
| June | 22884966.13 | 0.27 | 117.08 | 28-JUN-17:40 | 1.03 |
| July | 76629703.26 | 0.67 | 152.89 | 24-JUL-18:00 | 1.02 |
| August | 92162366.44 | 0.74 | 170.96 | 10-AUG-17:30 | 1.01 |
| September | 23685519.13 | 0.30 | 108.88 | 14-SEP-16:25 | 1.04 |
| October | 12652509.71 | 0.42 | 27.80 | 30-OCT-02:00 | 0.93 |
| November | 51608422.12 | 0.81 | 43.38 | 24-NOV-08:09 | 0.93 |
| December | 93610033.39 | 0.93 | 62.77 | 26-DEC-08:20 | 0.93 |
| Annual Sum or Average | 0.667487E+09 | 0.64 | |||
| Minimum of Months | 8235891.86 | 0.19 | 27.80 | 0.93 | |
| Maximum of Months | 0.111175E+09 | 0.93 | 170.96 | 1.06 |
Report: FanReportMonthly
For: G NW APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.64 | 20.01 | 01-JAN-00:10 | 0.64 |
| February | 48400714.57 | 0.64 | 20.01 | 01-FEB-00:10 | 0.64 |
| March | 53586505.42 | 0.64 | 20.01 | 01-MAR-00:10 | 0.64 |
| April | 51857908.47 | 0.64 | 20.01 | 01-APR-00:10 | 0.64 |
| May | 53586505.42 | 0.64 | 20.01 | 01-MAY-00:10 | 0.64 |
| June | 51857908.47 | 0.64 | 20.01 | 01-JUN-00:10 | 0.64 |
| July | 53586505.42 | 0.64 | 20.01 | 01-JUL-00:10 | 0.64 |
| August | 53586505.42 | 0.64 | 20.01 | 01-AUG-00:10 | 0.64 |
| September | 51857908.47 | 0.64 | 20.01 | 01-SEP-00:10 | 0.64 |
| October | 53586505.42 | 0.64 | 20.01 | 01-OCT-00:10 | 0.64 |
| November | 51857908.47 | 0.64 | 20.01 | 01-NOV-00:10 | 0.64 |
| December | 53586505.42 | 0.64 | 20.01 | 01-DEC-00:10 | 0.64 |
| Annual Sum or Average | 0.630938E+09 | 0.64 | |||
| Minimum of Months | 48400714.57 | 0.64 | 20.01 | 0.64 | |
| Maximum of Months | 53586505.42 | 0.64 | 20.01 | 0.64 |
Report: FanReportMonthly
For: G NW APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.64 | 20.01 | 01-JAN-00:10 | 0.64 |
| February | 48400714.57 | 0.64 | 20.01 | 01-FEB-00:10 | 0.64 |
| March | 53586505.42 | 0.64 | 20.01 | 01-MAR-00:10 | 0.64 |
| April | 51857908.47 | 0.64 | 20.01 | 01-APR-00:10 | 0.64 |
| May | 53586505.42 | 0.64 | 20.01 | 01-MAY-00:10 | 0.64 |
| June | 51857908.47 | 0.64 | 20.01 | 01-JUN-00:10 | 0.64 |
| July | 53586505.42 | 0.64 | 20.01 | 01-JUL-00:10 | 0.64 |
| August | 53586505.42 | 0.64 | 20.01 | 01-AUG-00:10 | 0.64 |
| September | 51857908.47 | 0.64 | 20.01 | 01-SEP-00:10 | 0.64 |
| October | 53586505.42 | 0.64 | 20.01 | 01-OCT-00:10 | 0.64 |
| November | 51857908.47 | 0.64 | 20.01 | 01-NOV-00:10 | 0.64 |
| December | 53586505.42 | 0.64 | 20.01 | 01-DEC-00:10 | 0.64 |
| Annual Sum or Average | 0.630938E+09 | 0.64 | |||
| Minimum of Months | 48400714.57 | 0.64 | 20.01 | 0.64 | |
| Maximum of Months | 53586505.42 | 0.64 | 20.01 | 0.64 |
Report: FanReportMonthly
For: SPLIT OFFICE SUPPLY FAN
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.120720E+10 | 0.93 | 450.72 | 01-JAN-00:10 | 0.93 |
| February | 0.109038E+10 | 0.93 | 450.72 | 01-FEB-00:10 | 0.93 |
| March | 0.120720E+10 | 0.93 | 450.72 | 01-MAR-00:10 | 0.93 |
| April | 0.116826E+10 | 0.93 | 450.72 | 01-APR-00:10 | 0.93 |
| May | 0.120720E+10 | 0.93 | 450.72 | 01-MAY-00:10 | 0.93 |
| June | 0.116826E+10 | 0.93 | 450.72 | 01-JUN-00:10 | 0.93 |
| July | 0.120720E+10 | 0.93 | 450.72 | 01-JUL-00:10 | 0.93 |
| August | 0.120720E+10 | 0.92 | 450.72 | 01-AUG-00:10 | 0.92 |
| September | 0.116826E+10 | 0.93 | 450.72 | 01-SEP-00:10 | 0.92 |
| October | 0.120720E+10 | 0.93 | 450.72 | 01-OCT-00:10 | 0.93 |
| November | 0.116826E+10 | 0.93 | 450.72 | 01-NOV-00:10 | 0.93 |
| December | 0.120720E+10 | 0.93 | 450.72 | 01-DEC-00:10 | 0.93 |
| Annual Sum or Average | 0.142138E+11 | 0.93 | |||
| Minimum of Months | 0.109038E+10 | 0.92 | 450.72 | 0.92 | |
| Maximum of Months | 0.120720E+10 | 0.93 | 450.72 | 0.93 |
Report: FanReportMonthly
For: SPLIT GNE SUPPLY FAN
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.109970E+09 | 0.93 | 69.42 | 15-JAN-08:00 | 0.93 |
| February | 84702649.02 | 0.91 | 81.00 | 19-FEB-06:00 | 0.93 |
| March | 57858375.22 | 0.90 | 51.34 | 27-MAR-17:01 | 0.93 |
| April | 26891592.57 | 0.58 | 45.92 | 02-APR-07:01 | 0.93 |
| May | 7225937.44 | 0.20 | 48.91 | 15-MAY-17:00 | 1.07 |
| June | 23673108.23 | 0.31 | 92.78 | 28-JUN-17:40 | 1.04 |
| July | 67715422.21 | 0.63 | 133.43 | 24-JUL-18:00 | 1.02 |
| August | 91997716.13 | 0.75 | 136.86 | 10-AUG-17:07 | 1.01 |
| September | 21802915.99 | 0.29 | 87.27 | 14-SEP-16:40 | 1.04 |
| October | 11973204.81 | 0.40 | 27.84 | 30-OCT-02:00 | 0.93 |
| November | 50926814.35 | 0.81 | 44.25 | 13-NOV-05:00 | 0.93 |
| December | 92628291.31 | 0.93 | 62.01 | 26-DEC-08:23 | 0.93 |
| Annual Sum or Average | 0.647366E+09 | 0.64 | |||
| Minimum of Months | 7225937.44 | 0.20 | 27.84 | 0.93 | |
| Maximum of Months | 0.109970E+09 | 0.93 | 136.86 | 1.07 |
Report: FanReportMonthly
For: G NE APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.64 | 20.01 | 01-JAN-00:10 | 0.64 |
| February | 48400714.57 | 0.64 | 20.01 | 01-FEB-00:10 | 0.64 |
| March | 53586505.42 | 0.64 | 20.01 | 01-MAR-00:10 | 0.64 |
| April | 51857908.47 | 0.64 | 20.01 | 01-APR-00:10 | 0.64 |
| May | 53586505.42 | 0.64 | 20.01 | 01-MAY-00:10 | 0.64 |
| June | 51857908.47 | 0.64 | 20.01 | 01-JUN-00:10 | 0.64 |
| July | 53586505.42 | 0.64 | 20.01 | 01-JUL-00:10 | 0.64 |
| August | 53586505.42 | 0.64 | 20.01 | 01-AUG-00:10 | 0.64 |
| September | 51857908.47 | 0.64 | 20.01 | 01-SEP-00:10 | 0.64 |
| October | 53586505.42 | 0.64 | 20.01 | 01-OCT-00:10 | 0.64 |
| November | 51857908.47 | 0.64 | 20.01 | 01-NOV-00:10 | 0.64 |
| December | 53586505.42 | 0.64 | 20.01 | 01-DEC-00:10 | 0.64 |
| Annual Sum or Average | 0.630938E+09 | 0.64 | |||
| Minimum of Months | 48400714.57 | 0.64 | 20.01 | 0.64 | |
| Maximum of Months | 53586505.42 | 0.64 | 20.01 | 0.64 |
Report: FanReportMonthly
For: G NE APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.64 | 20.01 | 01-JAN-00:10 | 0.64 |
| February | 48400714.57 | 0.64 | 20.01 | 01-FEB-00:10 | 0.64 |
| March | 53586505.42 | 0.64 | 20.01 | 01-MAR-00:10 | 0.64 |
| April | 51857908.47 | 0.64 | 20.01 | 01-APR-00:10 | 0.64 |
| May | 53586505.42 | 0.64 | 20.01 | 01-MAY-00:10 | 0.64 |
| June | 51857908.47 | 0.64 | 20.01 | 01-JUN-00:10 | 0.64 |
| July | 53586505.42 | 0.64 | 20.01 | 01-JUL-00:10 | 0.64 |
| August | 53586505.42 | 0.64 | 20.01 | 01-AUG-00:10 | 0.64 |
| September | 51857908.47 | 0.64 | 20.01 | 01-SEP-00:10 | 0.64 |
| October | 53586505.42 | 0.64 | 20.01 | 01-OCT-00:10 | 0.64 |
| November | 51857908.47 | 0.64 | 20.01 | 01-NOV-00:10 | 0.64 |
| December | 53586505.42 | 0.64 | 20.01 | 01-DEC-00:10 | 0.64 |
| Annual Sum or Average | 0.630938E+09 | 0.64 | |||
| Minimum of Months | 48400714.57 | 0.64 | 20.01 | 0.64 | |
| Maximum of Months | 53586505.42 | 0.64 | 20.01 | 0.64 |
Report: FanReportMonthly
For: SPLIT GN1 SUPPLY FAN
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 72204932.53 | 0.93 | 49.26 | 15-JAN-08:20 | 0.93 |
| February | 55300488.24 | 0.88 | 58.32 | 19-FEB-08:10 | 0.93 |
| March | 34340198.96 | 0.83 | 33.78 | 25-MAR-07:00 | 0.94 |
| April | 14992784.15 | 0.48 | 28.20 | 19-APR-05:00 | 0.93 |
| May | 3397040.48 | 0.07 | 40.29 | 05-MAY-16:07 | 1.06 |
| June | 18652378.55 | 0.32 | 80.04 | 28-JUN-18:00 | 1.04 |
| July | 60590378.10 | 0.79 | 109.81 | 24-JUL-18:00 | 1.02 |
| August | 78930738.11 | 0.84 | 113.99 | 10-AUG-17:07 | 1.02 |
| September | 18549176.43 | 0.36 | 73.96 | 14-SEP-17:00 | 1.04 |
| October | 3352457.66 | 0.21 | 16.44 | 30-OCT-02:00 | 0.93 |
| November | 29475415.42 | 0.71 | 29.66 | 13-NOV-05:00 | 0.93 |
| December | 59447616.01 | 0.93 | 43.31 | 26-DEC-08:19 | 0.93 |
| Annual Sum or Average | 0.449234E+09 | 0.61 | |||
| Minimum of Months | 3352457.66 | 0.07 | 16.44 | 0.93 | |
| Maximum of Months | 78930738.11 | 0.93 | 113.99 | 1.06 |
Report: FanReportMonthly
For: G N1 APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.64 | 20.01 | 01-JAN-00:10 | 0.64 |
| February | 48400714.57 | 0.64 | 20.01 | 01-FEB-00:10 | 0.64 |
| March | 53586505.42 | 0.64 | 20.01 | 01-MAR-00:10 | 0.64 |
| April | 51857908.47 | 0.64 | 20.01 | 01-APR-00:10 | 0.64 |
| May | 53586505.42 | 0.64 | 20.01 | 01-MAY-00:10 | 0.64 |
| June | 51857908.47 | 0.64 | 20.01 | 01-JUN-00:10 | 0.64 |
| July | 53586505.42 | 0.64 | 20.01 | 01-JUL-00:10 | 0.64 |
| August | 53586505.42 | 0.64 | 20.01 | 01-AUG-00:10 | 0.64 |
| September | 51857908.47 | 0.64 | 20.01 | 01-SEP-00:10 | 0.64 |
| October | 53586505.42 | 0.64 | 20.01 | 01-OCT-00:10 | 0.64 |
| November | 51857908.47 | 0.64 | 20.01 | 01-NOV-00:10 | 0.64 |
| December | 53586505.42 | 0.64 | 20.01 | 01-DEC-00:10 | 0.64 |
| Annual Sum or Average | 0.630938E+09 | 0.64 | |||
| Minimum of Months | 48400714.57 | 0.64 | 20.01 | 0.64 | |
| Maximum of Months | 53586505.42 | 0.64 | 20.01 | 0.64 |
Report: FanReportMonthly
For: G N1 APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.64 | 20.01 | 01-JAN-00:10 | 0.64 |
| February | 48400714.57 | 0.64 | 20.01 | 01-FEB-00:10 | 0.64 |
| March | 53586505.42 | 0.64 | 20.01 | 01-MAR-00:10 | 0.64 |
| April | 51857908.47 | 0.64 | 20.01 | 01-APR-00:10 | 0.64 |
| May | 53586505.42 | 0.64 | 20.01 | 01-MAY-00:10 | 0.64 |
| June | 51857908.47 | 0.64 | 20.01 | 01-JUN-00:10 | 0.64 |
| July | 53586505.42 | 0.64 | 20.01 | 01-JUL-00:10 | 0.64 |
| August | 53586505.42 | 0.64 | 20.01 | 01-AUG-00:10 | 0.64 |
| September | 51857908.47 | 0.64 | 20.01 | 01-SEP-00:10 | 0.64 |
| October | 53586505.42 | 0.64 | 20.01 | 01-OCT-00:10 | 0.64 |
| November | 51857908.47 | 0.64 | 20.01 | 01-NOV-00:10 | 0.64 |
| December | 53586505.42 | 0.64 | 20.01 | 01-DEC-00:10 | 0.64 |
| Annual Sum or Average | 0.630938E+09 | 0.64 | |||
| Minimum of Months | 48400714.57 | 0.64 | 20.01 | 0.64 | |
| Maximum of Months | 53586505.42 | 0.64 | 20.01 | 0.64 |
Report: FanReportMonthly
For: SPLIT GN2 SUPPLY FAN
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 72196308.40 | 0.93 | 49.27 | 15-JAN-08:20 | 0.93 |
| February | 55287396.75 | 0.88 | 58.21 | 19-FEB-08:10 | 0.93 |
| March | 34332810.80 | 0.83 | 33.68 | 25-MAR-07:00 | 0.94 |
| April | 14889543.75 | 0.48 | 28.20 | 19-APR-05:00 | 0.93 |
| May | 3381744.42 | 0.07 | 39.98 | 06-MAY-15:10 | 1.06 |
| June | 18928786.63 | 0.32 | 79.66 | 28-JUN-18:00 | 1.04 |
| July | 59980616.31 | 0.78 | 109.50 | 24-JUL-18:00 | 1.02 |
| August | 79025901.55 | 0.84 | 113.52 | 10-AUG-17:07 | 1.02 |
| September | 18436708.42 | 0.35 | 73.73 | 14-SEP-17:00 | 1.04 |
| October | 3333161.18 | 0.20 | 16.44 | 30-OCT-02:00 | 0.93 |
| November | 29472596.96 | 0.71 | 29.75 | 13-NOV-05:00 | 0.93 |
| December | 59445370.39 | 0.93 | 43.29 | 26-DEC-08:19 | 0.93 |
| Annual Sum or Average | 0.448711E+09 | 0.61 | |||
| Minimum of Months | 3333161.18 | 0.07 | 16.44 | 0.93 | |
| Maximum of Months | 79025901.55 | 0.93 | 113.52 | 1.06 |
Report: FanReportMonthly
For: G N2 APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.64 | 20.01 | 01-JAN-00:10 | 0.64 |
| February | 48400714.57 | 0.64 | 20.01 | 01-FEB-00:10 | 0.64 |
| March | 53586505.42 | 0.64 | 20.01 | 01-MAR-00:10 | 0.64 |
| April | 51857908.47 | 0.64 | 20.01 | 01-APR-00:10 | 0.64 |
| May | 53586505.42 | 0.64 | 20.01 | 01-MAY-00:10 | 0.64 |
| June | 51857908.47 | 0.64 | 20.01 | 01-JUN-00:10 | 0.64 |
| July | 53586505.42 | 0.64 | 20.01 | 01-JUL-00:10 | 0.64 |
| August | 53586505.42 | 0.64 | 20.01 | 01-AUG-00:10 | 0.64 |
| September | 51857908.47 | 0.64 | 20.01 | 01-SEP-00:10 | 0.64 |
| October | 53586505.42 | 0.64 | 20.01 | 01-OCT-00:10 | 0.64 |
| November | 51857908.47 | 0.64 | 20.01 | 01-NOV-00:10 | 0.64 |
| December | 53586505.42 | 0.64 | 20.01 | 01-DEC-00:10 | 0.64 |
| Annual Sum or Average | 0.630938E+09 | 0.64 | |||
| Minimum of Months | 48400714.57 | 0.64 | 20.01 | 0.64 | |
| Maximum of Months | 53586505.42 | 0.64 | 20.01 | 0.64 |
Report: FanReportMonthly
For: G N2 APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.64 | 20.01 | 01-JAN-00:10 | 0.64 |
| February | 48400714.57 | 0.64 | 20.01 | 01-FEB-00:10 | 0.64 |
| March | 53586505.42 | 0.64 | 20.01 | 01-MAR-00:10 | 0.64 |
| April | 51857908.47 | 0.64 | 20.01 | 01-APR-00:10 | 0.64 |
| May | 53586505.42 | 0.64 | 20.01 | 01-MAY-00:10 | 0.64 |
| June | 51857908.47 | 0.64 | 20.01 | 01-JUN-00:10 | 0.64 |
| July | 53586505.42 | 0.64 | 20.01 | 01-JUL-00:10 | 0.64 |
| August | 53586505.42 | 0.64 | 20.01 | 01-AUG-00:10 | 0.64 |
| September | 51857908.47 | 0.64 | 20.01 | 01-SEP-00:10 | 0.64 |
| October | 53586505.42 | 0.64 | 20.01 | 01-OCT-00:10 | 0.64 |
| November | 51857908.47 | 0.64 | 20.01 | 01-NOV-00:10 | 0.64 |
| December | 53586505.42 | 0.64 | 20.01 | 01-DEC-00:10 | 0.64 |
| Annual Sum or Average | 0.630938E+09 | 0.64 | |||
| Minimum of Months | 48400714.57 | 0.64 | 20.01 | 0.64 | |
| Maximum of Months | 53586505.42 | 0.64 | 20.01 | 0.64 |
Report: FanReportMonthly
For: SPLIT GS1 SUPPLY FAN
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 56401346.49 | 0.90 | 42.51 | 15-JAN-08:00 | 0.93 |
| February | 34965023.03 | 0.73 | 53.44 | 19-FEB-06:00 | 0.93 |
| March | 14508663.58 | 0.48 | 27.40 | 24-MAR-06:00 | 0.93 |
| April | 9230644.68 | 0.25 | 74.56 | 27-APR-15:10 | 1.05 |
| May | 16977952.42 | 0.20 | 86.57 | 15-MAY-16:05 | 1.05 |
| June | 38358710.97 | 0.55 | 99.95 | 28-JUN-16:05 | 1.04 |
| July | 99209759.68 | 0.91 | 141.04 | 24-JUL-15:10 | 1.02 |
| August | 0.131944E+09 | 0.96 | 161.24 | 10-AUG-15:10 | 1.01 |
| September | 77750349.27 | 0.79 | 141.78 | 14-SEP-14:10 | 1.02 |
| October | 18612054.88 | 0.25 | 110.84 | 04-OCT-15:10 | 1.04 |
| November | 18034133.67 | 0.53 | 34.35 | 04-NOV-14:10 | 1.07 |
| December | 42968594.55 | 0.82 | 41.84 | 26-DEC-08:23 | 0.93 |
| Annual Sum or Average | 0.558961E+09 | 0.61 | |||
| Minimum of Months | 9230644.68 | 0.20 | 27.40 | 0.93 | |
| Maximum of Months | 0.131944E+09 | 0.96 | 161.24 | 1.07 |
Report: FanReportMonthly
For: G S1 APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.64 | 20.01 | 01-JAN-00:10 | 0.64 |
| February | 48400714.57 | 0.64 | 20.01 | 01-FEB-00:10 | 0.64 |
| March | 53586505.42 | 0.64 | 20.01 | 01-MAR-00:10 | 0.64 |
| April | 51857908.47 | 0.64 | 20.01 | 01-APR-00:10 | 0.64 |
| May | 53586505.42 | 0.64 | 20.01 | 01-MAY-00:10 | 0.64 |
| June | 51857908.47 | 0.64 | 20.01 | 01-JUN-00:10 | 0.64 |
| July | 53586505.42 | 0.64 | 20.01 | 01-JUL-00:10 | 0.64 |
| August | 53586505.42 | 0.64 | 20.01 | 01-AUG-00:10 | 0.64 |
| September | 51857908.47 | 0.64 | 20.01 | 01-SEP-00:10 | 0.64 |
| October | 53586505.42 | 0.64 | 20.01 | 01-OCT-00:10 | 0.64 |
| November | 51857908.47 | 0.64 | 20.01 | 01-NOV-00:10 | 0.64 |
| December | 53586505.42 | 0.64 | 20.01 | 01-DEC-00:10 | 0.64 |
| Annual Sum or Average | 0.630938E+09 | 0.64 | |||
| Minimum of Months | 48400714.57 | 0.64 | 20.01 | 0.64 | |
| Maximum of Months | 53586505.42 | 0.64 | 20.01 | 0.64 |
Report: FanReportMonthly
For: G S1 APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.64 | 20.01 | 01-JAN-00:10 | 0.64 |
| February | 48400714.57 | 0.64 | 20.01 | 01-FEB-00:10 | 0.64 |
| March | 53586505.42 | 0.64 | 20.01 | 01-MAR-00:10 | 0.64 |
| April | 51857908.47 | 0.64 | 20.01 | 01-APR-00:10 | 0.64 |
| May | 53586505.42 | 0.64 | 20.01 | 01-MAY-00:10 | 0.64 |
| June | 51857908.47 | 0.64 | 20.01 | 01-JUN-00:10 | 0.64 |
| July | 53586505.42 | 0.64 | 20.01 | 01-JUL-00:10 | 0.64 |
| August | 53586505.42 | 0.64 | 20.01 | 01-AUG-00:10 | 0.64 |
| September | 51857908.47 | 0.64 | 20.01 | 01-SEP-00:10 | 0.64 |
| October | 53586505.42 | 0.64 | 20.01 | 01-OCT-00:10 | 0.64 |
| November | 51857908.47 | 0.64 | 20.01 | 01-NOV-00:10 | 0.64 |
| December | 53586505.42 | 0.64 | 20.01 | 01-DEC-00:10 | 0.64 |
| Annual Sum or Average | 0.630938E+09 | 0.64 | |||
| Minimum of Months | 48400714.57 | 0.64 | 20.01 | 0.64 | |
| Maximum of Months | 53586505.42 | 0.64 | 20.01 | 0.64 |
Report: FanReportMonthly
For: SPLIT GS2 SUPPLY FAN
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 63873660.58 | 0.91 | 46.81 | 15-JAN-08:00 | 0.93 |
| February | 39032289.94 | 0.74 | 58.51 | 19-FEB-06:00 | 0.93 |
| March | 15061465.79 | 0.48 | 27.95 | 24-MAR-06:00 | 0.93 |
| April | 9501803.92 | 0.24 | 77.51 | 27-APR-15:10 | 1.05 |
| May | 19311956.81 | 0.23 | 90.54 | 15-MAY-16:05 | 1.05 |
| June | 44463544.01 | 0.61 | 103.55 | 28-JUN-15:10 | 1.04 |
| July | 0.109328E+09 | 0.95 | 147.13 | 24-JUL-15:10 | 1.02 |
| August | 0.145249E+09 | 0.99 | 166.35 | 10-AUG-15:10 | 1.01 |
| September | 86115019.41 | 0.83 | 146.57 | 14-SEP-14:10 | 1.02 |
| October | 20537060.10 | 0.27 | 113.46 | 04-OCT-15:10 | 1.04 |
| November | 19590322.27 | 0.54 | 39.75 | 04-NOV-14:10 | 1.07 |
| December | 47649259.10 | 0.83 | 47.16 | 26-DEC-08:20 | 0.93 |
| Annual Sum or Average | 0.619713E+09 | 0.63 | |||
| Minimum of Months | 9501803.92 | 0.23 | 27.95 | 0.93 | |
| Maximum of Months | 0.145249E+09 | 0.99 | 166.35 | 1.07 |
Report: FanReportMonthly
For: G S2 APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.64 | 20.01 | 01-JAN-00:10 | 0.64 |
| February | 48400714.57 | 0.64 | 20.01 | 01-FEB-00:10 | 0.64 |
| March | 53586505.42 | 0.64 | 20.01 | 01-MAR-00:10 | 0.64 |
| April | 51857908.47 | 0.64 | 20.01 | 01-APR-00:10 | 0.64 |
| May | 53586505.42 | 0.64 | 20.01 | 01-MAY-00:10 | 0.64 |
| June | 51857908.47 | 0.64 | 20.01 | 01-JUN-00:10 | 0.64 |
| July | 53586505.42 | 0.64 | 20.01 | 01-JUL-00:10 | 0.64 |
| August | 53586505.42 | 0.64 | 20.01 | 01-AUG-00:10 | 0.64 |
| September | 51857908.47 | 0.64 | 20.01 | 01-SEP-00:10 | 0.64 |
| October | 53586505.42 | 0.64 | 20.01 | 01-OCT-00:10 | 0.64 |
| November | 51857908.47 | 0.64 | 20.01 | 01-NOV-00:10 | 0.64 |
| December | 53586505.42 | 0.64 | 20.01 | 01-DEC-00:10 | 0.64 |
| Annual Sum or Average | 0.630938E+09 | 0.64 | |||
| Minimum of Months | 48400714.57 | 0.64 | 20.01 | 0.64 | |
| Maximum of Months | 53586505.42 | 0.64 | 20.01 | 0.64 |
Report: FanReportMonthly
For: G S2 APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.64 | 20.01 | 01-JAN-00:10 | 0.64 |
| February | 48400714.57 | 0.64 | 20.01 | 01-FEB-00:10 | 0.64 |
| March | 53586505.42 | 0.64 | 20.01 | 01-MAR-00:10 | 0.64 |
| April | 51857908.47 | 0.64 | 20.01 | 01-APR-00:10 | 0.64 |
| May | 53586505.42 | 0.64 | 20.01 | 01-MAY-00:10 | 0.64 |
| June | 51857908.47 | 0.64 | 20.01 | 01-JUN-00:10 | 0.64 |
| July | 53586505.42 | 0.64 | 20.01 | 01-JUL-00:10 | 0.64 |
| August | 53586505.42 | 0.64 | 20.01 | 01-AUG-00:10 | 0.64 |
| September | 51857908.47 | 0.64 | 20.01 | 01-SEP-00:10 | 0.64 |
| October | 53586505.42 | 0.64 | 20.01 | 01-OCT-00:10 | 0.64 |
| November | 51857908.47 | 0.64 | 20.01 | 01-NOV-00:10 | 0.64 |
| December | 53586505.42 | 0.64 | 20.01 | 01-DEC-00:10 | 0.64 |
| Annual Sum or Average | 0.630938E+09 | 0.64 | |||
| Minimum of Months | 48400714.57 | 0.64 | 20.01 | 0.64 | |
| Maximum of Months | 53586505.42 | 0.64 | 20.01 | 0.64 |
Report: FanReportMonthly
For: SPLIT MSW SUPPLY FAN
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.132030E+09 | 0.87 | 111.58 | 15-JAN-05:00 | 0.93 |
| February | 73293926.87 | 0.62 | 140.90 | 19-FEB-06:00 | 0.93 |
| March | 25243482.82 | 0.28 | 176.30 | 18-MAR-16:10 | 1.07 |
| April | 66554272.91 | 0.32 | 415.00 | 27-APR-16:03 | 1.02 |
| May | 0.150931E+09 | 0.57 | 399.62 | 15-MAY-16:05 | 1.03 |
| June | 0.207391E+09 | 0.80 | 391.57 | 28-JUN-16:23 | 1.03 |
| July | 0.355829E+09 | 0.98 | 471.26 | 31-JUL-16:15 | 1.01 |
| August | 0.390803E+09 | 0.95 | 526.73 | 10-AUG-16:13 | 1.00 |
| September | 0.244144E+09 | 0.81 | 440.88 | 23-SEP-16:07 | 1.02 |
| October | 63459910.50 | 0.29 | 382.67 | 04-OCT-15:10 | 1.03 |
| November | 61412806.08 | 0.59 | 225.84 | 04-NOV-15:20 | 1.05 |
| December | 0.109691E+09 | 0.78 | 110.74 | 26-DEC-14:00 | 0.93 |
| Annual Sum or Average | 0.188078E+10 | 0.66 | |||
| Minimum of Months | 25243482.82 | 0.28 | 110.74 | 0.93 | |
| Maximum of Months | 0.390803E+09 | 0.98 | 526.73 | 1.07 |
Report: FanReportMonthly
For: M SW APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.107173E+09 | 0.64 | 40.01 | 01-JAN-00:10 | 0.64 |
| February | 96801429.15 | 0.64 | 40.01 | 01-FEB-00:10 | 0.64 |
| March | 0.107173E+09 | 0.64 | 40.01 | 01-MAR-00:10 | 0.64 |
| April | 0.103716E+09 | 0.64 | 40.01 | 01-APR-00:10 | 0.64 |
| May | 0.107173E+09 | 0.64 | 40.01 | 01-MAY-00:10 | 0.64 |
| June | 0.103716E+09 | 0.64 | 40.01 | 01-JUN-00:10 | 0.64 |
| July | 0.107173E+09 | 0.64 | 40.01 | 01-JUL-00:10 | 0.64 |
| August | 0.107173E+09 | 0.64 | 40.01 | 01-AUG-00:10 | 0.64 |
| September | 0.103716E+09 | 0.64 | 40.01 | 01-SEP-00:10 | 0.64 |
| October | 0.107173E+09 | 0.64 | 40.01 | 01-OCT-00:10 | 0.64 |
| November | 0.103716E+09 | 0.64 | 40.01 | 01-NOV-00:10 | 0.64 |
| December | 0.107173E+09 | 0.64 | 40.01 | 01-DEC-00:10 | 0.64 |
| Annual Sum or Average | 0.126188E+10 | 0.64 | |||
| Minimum of Months | 96801429.15 | 0.64 | 40.01 | 0.64 | |
| Maximum of Months | 0.107173E+09 | 0.64 | 40.01 | 0.64 |
Report: FanReportMonthly
For: M SW APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.107173E+09 | 0.64 | 40.01 | 01-JAN-00:10 | 0.64 |
| February | 96801429.15 | 0.64 | 40.01 | 01-FEB-00:10 | 0.64 |
| March | 0.107173E+09 | 0.64 | 40.01 | 01-MAR-00:10 | 0.64 |
| April | 0.103716E+09 | 0.64 | 40.01 | 01-APR-00:10 | 0.64 |
| May | 0.107173E+09 | 0.64 | 40.01 | 01-MAY-00:10 | 0.64 |
| June | 0.103716E+09 | 0.64 | 40.01 | 01-JUN-00:10 | 0.64 |
| July | 0.107173E+09 | 0.64 | 40.01 | 01-JUL-00:10 | 0.64 |
| August | 0.107173E+09 | 0.64 | 40.01 | 01-AUG-00:10 | 0.64 |
| September | 0.103716E+09 | 0.64 | 40.01 | 01-SEP-00:10 | 0.64 |
| October | 0.107173E+09 | 0.64 | 40.01 | 01-OCT-00:10 | 0.64 |
| November | 0.103716E+09 | 0.64 | 40.01 | 01-NOV-00:10 | 0.64 |
| December | 0.107173E+09 | 0.64 | 40.01 | 01-DEC-00:10 | 0.64 |
| Annual Sum or Average | 0.126188E+10 | 0.64 | |||
| Minimum of Months | 96801429.15 | 0.64 | 40.01 | 0.64 | |
| Maximum of Months | 0.107173E+09 | 0.64 | 40.01 | 0.64 |
Report: FanReportMonthly
For: SPLIT MNW SUPPLY FAN
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.167874E+09 | 0.93 | 125.63 | 15-JAN-05:00 | 0.93 |
| February | 0.114590E+09 | 0.80 | 150.29 | 19-FEB-06:00 | 0.93 |
| March | 46435597.80 | 0.53 | 83.90 | 24-MAR-06:00 | 0.93 |
| April | 27288705.09 | 0.21 | 274.34 | 27-APR-17:20 | 1.04 |
| May | 84590853.29 | 0.42 | 312.25 | 15-MAY-16:25 | 1.03 |
| June | 0.153509E+09 | 0.74 | 343.82 | 28-JUN-17:20 | 1.02 |
| July | 0.274565E+09 | 0.95 | 401.51 | 31-JUL-17:20 | 1.01 |
| August | 0.282635E+09 | 0.92 | 436.35 | 10-AUG-17:30 | 1.01 |
| September | 0.108763E+09 | 0.60 | 295.35 | 14-SEP-16:25 | 1.03 |
| October | 12165726.05 | 0.22 | 143.53 | 04-OCT-16:30 | 1.07 |
| November | 82512618.92 | 0.71 | 87.34 | 30-NOV-01:00 | 0.93 |
| December | 0.146753E+09 | 0.93 | 112.53 | 26-DEC-14:00 | 0.93 |
| Annual Sum or Average | 0.150168E+10 | 0.66 | |||
| Minimum of Months | 12165726.05 | 0.21 | 83.90 | 0.93 | |
| Maximum of Months | 0.282635E+09 | 0.95 | 436.35 | 1.07 |
Report: FanReportMonthly
For: M NW APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.107173E+09 | 0.64 | 40.01 | 01-JAN-00:10 | 0.64 |
| February | 96801429.15 | 0.64 | 40.01 | 01-FEB-00:10 | 0.64 |
| March | 0.107173E+09 | 0.64 | 40.01 | 01-MAR-00:10 | 0.64 |
| April | 0.103716E+09 | 0.64 | 40.01 | 01-APR-00:10 | 0.64 |
| May | 0.107173E+09 | 0.64 | 40.01 | 01-MAY-00:10 | 0.64 |
| June | 0.103716E+09 | 0.64 | 40.01 | 01-JUN-00:10 | 0.64 |
| July | 0.107173E+09 | 0.64 | 40.01 | 01-JUL-00:10 | 0.64 |
| August | 0.107173E+09 | 0.64 | 40.01 | 01-AUG-00:10 | 0.64 |
| September | 0.103716E+09 | 0.64 | 40.01 | 01-SEP-00:10 | 0.64 |
| October | 0.107173E+09 | 0.64 | 40.01 | 01-OCT-00:10 | 0.64 |
| November | 0.103716E+09 | 0.64 | 40.01 | 01-NOV-00:10 | 0.64 |
| December | 0.107173E+09 | 0.64 | 40.01 | 01-DEC-00:10 | 0.64 |
| Annual Sum or Average | 0.126188E+10 | 0.64 | |||
| Minimum of Months | 96801429.15 | 0.64 | 40.01 | 0.64 | |
| Maximum of Months | 0.107173E+09 | 0.64 | 40.01 | 0.64 |
Report: FanReportMonthly
For: M NW APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.107173E+09 | 0.64 | 40.01 | 01-JAN-00:10 | 0.64 |
| February | 96801429.15 | 0.64 | 40.01 | 01-FEB-00:10 | 0.64 |
| March | 0.107173E+09 | 0.64 | 40.01 | 01-MAR-00:10 | 0.64 |
| April | 0.103716E+09 | 0.64 | 40.01 | 01-APR-00:10 | 0.64 |
| May | 0.107173E+09 | 0.64 | 40.01 | 01-MAY-00:10 | 0.64 |
| June | 0.103716E+09 | 0.64 | 40.01 | 01-JUN-00:10 | 0.64 |
| July | 0.107173E+09 | 0.64 | 40.01 | 01-JUL-00:10 | 0.64 |
| August | 0.107173E+09 | 0.64 | 40.01 | 01-AUG-00:10 | 0.64 |
| September | 0.103716E+09 | 0.64 | 40.01 | 01-SEP-00:10 | 0.64 |
| October | 0.107173E+09 | 0.64 | 40.01 | 01-OCT-00:10 | 0.64 |
| November | 0.103716E+09 | 0.64 | 40.01 | 01-NOV-00:10 | 0.64 |
| December | 0.107173E+09 | 0.64 | 40.01 | 01-DEC-00:10 | 0.64 |
| Annual Sum or Average | 0.126188E+10 | 0.64 | |||
| Minimum of Months | 96801429.15 | 0.64 | 40.01 | 0.64 | |
| Maximum of Months | 0.107173E+09 | 0.64 | 40.01 | 0.64 |
Report: FanReportMonthly
For: SPLIT MSE SUPPLY FAN
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.131079E+09 | 0.88 | 111.86 | 15-JAN-05:00 | 0.93 |
| February | 71734188.29 | 0.61 | 139.05 | 19-FEB-06:00 | 0.93 |
| March | 21234837.54 | 0.26 | 136.52 | 02-MAR-14:00 | 1.07 |
| April | 66786254.24 | 0.34 | 371.06 | 27-APR-13:20 | 1.02 |
| May | 0.141363E+09 | 0.57 | 337.85 | 15-MAY-13:40 | 1.03 |
| June | 0.220200E+09 | 0.83 | 325.06 | 28-JUN-13:20 | 1.03 |
| July | 0.333448E+09 | 0.96 | 425.37 | 24-JUL-13:30 | 1.01 |
| August | 0.390316E+09 | 0.96 | 460.43 | 29-AUG-14:30 | 1.00 |
| September | 0.233709E+09 | 0.77 | 406.91 | 23-SEP-13:30 | 1.01 |
| October | 63750285.92 | 0.30 | 330.81 | 04-OCT-13:40 | 1.03 |
| November | 60412225.35 | 0.58 | 190.23 | 04-NOV-14:00 | 1.05 |
| December | 0.109031E+09 | 0.78 | 110.46 | 26-DEC-14:00 | 0.93 |
| Annual Sum or Average | 0.184306E+10 | 0.65 | |||
| Minimum of Months | 21234837.54 | 0.26 | 110.46 | 0.93 | |
| Maximum of Months | 0.390316E+09 | 0.96 | 460.43 | 1.07 |
Report: FanReportMonthly
For: M SE APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.107173E+09 | 0.64 | 40.01 | 01-JAN-00:10 | 0.64 |
| February | 96801429.15 | 0.64 | 40.01 | 01-FEB-00:10 | 0.64 |
| March | 0.107173E+09 | 0.64 | 40.01 | 01-MAR-00:10 | 0.64 |
| April | 0.103716E+09 | 0.64 | 40.01 | 01-APR-00:10 | 0.64 |
| May | 0.107173E+09 | 0.64 | 40.01 | 01-MAY-00:10 | 0.64 |
| June | 0.103716E+09 | 0.64 | 40.01 | 01-JUN-00:10 | 0.64 |
| July | 0.107173E+09 | 0.64 | 40.01 | 01-JUL-00:10 | 0.64 |
| August | 0.107173E+09 | 0.64 | 40.01 | 01-AUG-00:10 | 0.64 |
| September | 0.103716E+09 | 0.64 | 40.01 | 01-SEP-00:10 | 0.64 |
| October | 0.107173E+09 | 0.64 | 40.01 | 01-OCT-00:10 | 0.64 |
| November | 0.103716E+09 | 0.64 | 40.01 | 01-NOV-00:10 | 0.64 |
| December | 0.107173E+09 | 0.64 | 40.01 | 01-DEC-00:10 | 0.64 |
| Annual Sum or Average | 0.126188E+10 | 0.64 | |||
| Minimum of Months | 96801429.15 | 0.64 | 40.01 | 0.64 | |
| Maximum of Months | 0.107173E+09 | 0.64 | 40.01 | 0.64 |
Report: FanReportMonthly
For: M SE APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.107173E+09 | 0.64 | 40.01 | 01-JAN-00:10 | 0.64 |
| February | 96801429.15 | 0.64 | 40.01 | 01-FEB-00:10 | 0.64 |
| March | 0.107173E+09 | 0.64 | 40.01 | 01-MAR-00:10 | 0.64 |
| April | 0.103716E+09 | 0.64 | 40.01 | 01-APR-00:10 | 0.64 |
| May | 0.107173E+09 | 0.64 | 40.01 | 01-MAY-00:10 | 0.64 |
| June | 0.103716E+09 | 0.64 | 40.01 | 01-JUN-00:10 | 0.64 |
| July | 0.107173E+09 | 0.64 | 40.01 | 01-JUL-00:10 | 0.64 |
| August | 0.107173E+09 | 0.64 | 40.01 | 01-AUG-00:10 | 0.64 |
| September | 0.103716E+09 | 0.64 | 40.01 | 01-SEP-00:10 | 0.64 |
| October | 0.107173E+09 | 0.64 | 40.01 | 01-OCT-00:10 | 0.64 |
| November | 0.103716E+09 | 0.64 | 40.01 | 01-NOV-00:10 | 0.64 |
| December | 0.107173E+09 | 0.64 | 40.01 | 01-DEC-00:10 | 0.64 |
| Annual Sum or Average | 0.126188E+10 | 0.64 | |||
| Minimum of Months | 96801429.15 | 0.64 | 40.01 | 0.64 | |
| Maximum of Months | 0.107173E+09 | 0.64 | 40.01 | 0.64 |
Report: FanReportMonthly
For: SPLIT MNE SUPPLY FAN
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.166296E+09 | 0.93 | 126.01 | 15-JAN-05:00 | 0.93 |
| February | 0.113087E+09 | 0.81 | 147.85 | 19-FEB-06:00 | 0.93 |
| March | 43961511.72 | 0.52 | 83.72 | 24-MAR-06:00 | 0.93 |
| April | 24125068.05 | 0.19 | 211.75 | 27-APR-16:10 | 1.04 |
| May | 73962896.08 | 0.42 | 229.47 | 06-MAY-13:30 | 1.04 |
| June | 0.165802E+09 | 0.79 | 263.74 | 28-JUN-17:50 | 1.03 |
| July | 0.252764E+09 | 0.93 | 331.99 | 24-JUL-18:00 | 1.02 |
| August | 0.283010E+09 | 0.93 | 324.15 | 10-AUG-17:10 | 1.02 |
| September | 0.101217E+09 | 0.58 | 222.26 | 14-SEP-16:25 | 1.04 |
| October | 11130996.18 | 0.21 | 65.92 | 04-OCT-16:30 | 1.08 |
| November | 81481729.55 | 0.71 | 86.00 | 30-NOV-01:00 | 0.93 |
| December | 0.145474E+09 | 0.93 | 111.97 | 26-DEC-14:00 | 0.93 |
| Annual Sum or Average | 0.146231E+10 | 0.66 | |||
| Minimum of Months | 11130996.18 | 0.19 | 65.92 | 0.93 | |
| Maximum of Months | 0.283010E+09 | 0.93 | 331.99 | 1.08 |
Report: FanReportMonthly
For: M NE APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.107173E+09 | 0.64 | 40.01 | 01-JAN-00:10 | 0.64 |
| February | 96801429.15 | 0.64 | 40.01 | 01-FEB-00:10 | 0.64 |
| March | 0.107173E+09 | 0.64 | 40.01 | 01-MAR-00:10 | 0.64 |
| April | 0.103716E+09 | 0.64 | 40.01 | 01-APR-00:10 | 0.64 |
| May | 0.107173E+09 | 0.64 | 40.01 | 01-MAY-00:10 | 0.64 |
| June | 0.103716E+09 | 0.64 | 40.01 | 01-JUN-00:10 | 0.64 |
| July | 0.107173E+09 | 0.64 | 40.01 | 01-JUL-00:10 | 0.64 |
| August | 0.107173E+09 | 0.64 | 40.01 | 01-AUG-00:10 | 0.64 |
| September | 0.103716E+09 | 0.64 | 40.01 | 01-SEP-00:10 | 0.64 |
| October | 0.107173E+09 | 0.64 | 40.01 | 01-OCT-00:10 | 0.64 |
| November | 0.103716E+09 | 0.64 | 40.01 | 01-NOV-00:10 | 0.64 |
| December | 0.107173E+09 | 0.64 | 40.01 | 01-DEC-00:10 | 0.64 |
| Annual Sum or Average | 0.126188E+10 | 0.64 | |||
| Minimum of Months | 96801429.15 | 0.64 | 40.01 | 0.64 | |
| Maximum of Months | 0.107173E+09 | 0.64 | 40.01 | 0.64 |
Report: FanReportMonthly
For: M NE APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.107173E+09 | 0.64 | 40.01 | 01-JAN-00:10 | 0.64 |
| February | 96801429.15 | 0.64 | 40.01 | 01-FEB-00:10 | 0.64 |
| March | 0.107173E+09 | 0.64 | 40.01 | 01-MAR-00:10 | 0.64 |
| April | 0.103716E+09 | 0.64 | 40.01 | 01-APR-00:10 | 0.64 |
| May | 0.107173E+09 | 0.64 | 40.01 | 01-MAY-00:10 | 0.64 |
| June | 0.103716E+09 | 0.64 | 40.01 | 01-JUN-00:10 | 0.64 |
| July | 0.107173E+09 | 0.64 | 40.01 | 01-JUL-00:10 | 0.64 |
| August | 0.107173E+09 | 0.64 | 40.01 | 01-AUG-00:10 | 0.64 |
| September | 0.103716E+09 | 0.64 | 40.01 | 01-SEP-00:10 | 0.64 |
| October | 0.107173E+09 | 0.64 | 40.01 | 01-OCT-00:10 | 0.64 |
| November | 0.103716E+09 | 0.64 | 40.01 | 01-NOV-00:10 | 0.64 |
| December | 0.107173E+09 | 0.64 | 40.01 | 01-DEC-00:10 | 0.64 |
| Annual Sum or Average | 0.126188E+10 | 0.64 | |||
| Minimum of Months | 96801429.15 | 0.64 | 40.01 | 0.64 | |
| Maximum of Months | 0.107173E+09 | 0.64 | 40.01 | 0.64 |
Report: FanReportMonthly
For: SPLIT MN1 SUPPLY FAN
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 94344270.40 | 0.91 | 81.75 | 15-JAN-05:00 | 0.93 |
| February | 64115414.88 | 0.70 | 97.21 | 19-FEB-06:00 | 0.93 |
| March | 13676521.79 | 0.29 | 47.68 | 05-MAR-04:00 | 0.93 |
| April | 13218052.25 | 0.13 | 156.86 | 27-APR-18:00 | 1.05 |
| May | 65677731.26 | 0.50 | 186.26 | 05-MAY-16:10 | 1.04 |
| June | 0.131929E+09 | 0.87 | 218.09 | 28-JUN-18:00 | 1.04 |
| July | 0.211288E+09 | 1.02 | 266.89 | 24-JUL-18:00 | 1.02 |
| August | 0.231806E+09 | 1.00 | 265.96 | 10-AUG-18:40 | 1.02 |
| September | 92992964.54 | 0.78 | 184.36 | 14-SEP-17:00 | 1.04 |
| October | 4241620.46 | 0.10 | 66.20 | 01-OCT-18:20 | 1.07 |
| November | 37859673.97 | 0.57 | 52.63 | 13-NOV-05:00 | 0.93 |
| December | 79044761.24 | 0.91 | 71.11 | 26-DEC-04:00 | 0.93 |
| Annual Sum or Average | 0.104019E+10 | 0.65 | |||
| Minimum of Months | 4241620.46 | 0.10 | 47.68 | 0.93 | |
| Maximum of Months | 0.231806E+09 | 1.02 | 266.89 | 1.07 |
Report: FanReportMonthly
For: M N1 APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.107173E+09 | 0.64 | 40.01 | 01-JAN-00:10 | 0.64 |
| February | 96801429.15 | 0.64 | 40.01 | 01-FEB-00:10 | 0.64 |
| March | 0.107173E+09 | 0.64 | 40.01 | 01-MAR-00:10 | 0.64 |
| April | 0.103716E+09 | 0.64 | 40.01 | 01-APR-00:10 | 0.64 |
| May | 0.107173E+09 | 0.64 | 40.01 | 01-MAY-00:10 | 0.64 |
| June | 0.103716E+09 | 0.64 | 40.01 | 01-JUN-00:10 | 0.64 |
| July | 0.107173E+09 | 0.64 | 40.01 | 01-JUL-00:10 | 0.64 |
| August | 0.107173E+09 | 0.64 | 40.01 | 01-AUG-00:10 | 0.64 |
| September | 0.103716E+09 | 0.64 | 40.01 | 01-SEP-00:10 | 0.64 |
| October | 0.107173E+09 | 0.64 | 40.01 | 01-OCT-00:10 | 0.64 |
| November | 0.103716E+09 | 0.64 | 40.01 | 01-NOV-00:10 | 0.64 |
| December | 0.107173E+09 | 0.64 | 40.01 | 01-DEC-00:10 | 0.64 |
| Annual Sum or Average | 0.126188E+10 | 0.64 | |||
| Minimum of Months | 96801429.15 | 0.64 | 40.01 | 0.64 | |
| Maximum of Months | 0.107173E+09 | 0.64 | 40.01 | 0.64 |
Report: FanReportMonthly
For: M N1 APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.107173E+09 | 0.64 | 40.01 | 01-JAN-00:10 | 0.64 |
| February | 96801429.15 | 0.64 | 40.01 | 01-FEB-00:10 | 0.64 |
| March | 0.107173E+09 | 0.64 | 40.01 | 01-MAR-00:10 | 0.64 |
| April | 0.103716E+09 | 0.64 | 40.01 | 01-APR-00:10 | 0.64 |
| May | 0.107173E+09 | 0.64 | 40.01 | 01-MAY-00:10 | 0.64 |
| June | 0.103716E+09 | 0.64 | 40.01 | 01-JUN-00:10 | 0.64 |
| July | 0.107173E+09 | 0.64 | 40.01 | 01-JUL-00:10 | 0.64 |
| August | 0.107173E+09 | 0.64 | 40.01 | 01-AUG-00:10 | 0.64 |
| September | 0.103716E+09 | 0.64 | 40.01 | 01-SEP-00:10 | 0.64 |
| October | 0.107173E+09 | 0.64 | 40.01 | 01-OCT-00:10 | 0.64 |
| November | 0.103716E+09 | 0.64 | 40.01 | 01-NOV-00:10 | 0.64 |
| December | 0.107173E+09 | 0.64 | 40.01 | 01-DEC-00:10 | 0.64 |
| Annual Sum or Average | 0.126188E+10 | 0.64 | |||
| Minimum of Months | 96801429.15 | 0.64 | 40.01 | 0.64 | |
| Maximum of Months | 0.107173E+09 | 0.64 | 40.01 | 0.64 |
Report: FanReportMonthly
For: SPLIT MN2 SUPPLY FAN
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 94340771.83 | 0.91 | 81.80 | 15-JAN-05:00 | 0.93 |
| February | 64093108.36 | 0.70 | 97.14 | 19-FEB-06:00 | 0.93 |
| March | 13662253.99 | 0.29 | 47.48 | 05-MAR-04:00 | 0.93 |
| April | 13312267.05 | 0.13 | 156.72 | 27-APR-18:00 | 1.05 |
| May | 65497811.21 | 0.50 | 185.84 | 05-MAY-16:10 | 1.04 |
| June | 0.132615E+09 | 0.88 | 216.81 | 28-JUN-18:00 | 1.04 |
| July | 0.210391E+09 | 1.02 | 266.14 | 24-JUL-18:00 | 1.02 |
| August | 0.231910E+09 | 1.00 | 264.11 | 10-AUG-18:40 | 1.02 |
| September | 92479218.77 | 0.77 | 183.45 | 14-SEP-17:00 | 1.04 |
| October | 4262984.02 | 0.10 | 61.67 | 04-OCT-17:00 | 1.08 |
| November | 37864818.43 | 0.57 | 52.82 | 13-NOV-05:00 | 0.93 |
| December | 79058337.12 | 0.91 | 71.18 | 26-DEC-04:00 | 0.93 |
| Annual Sum or Average | 0.103949E+10 | 0.65 | |||
| Minimum of Months | 4262984.02 | 0.10 | 47.48 | 0.93 | |
| Maximum of Months | 0.231910E+09 | 1.02 | 266.14 | 1.08 |
Report: FanReportMonthly
For: M N2 APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.107173E+09 | 0.64 | 40.01 | 01-JAN-00:10 | 0.64 |
| February | 96801429.15 | 0.64 | 40.01 | 01-FEB-00:10 | 0.64 |
| March | 0.107173E+09 | 0.64 | 40.01 | 01-MAR-00:10 | 0.64 |
| April | 0.103716E+09 | 0.64 | 40.01 | 01-APR-00:10 | 0.64 |
| May | 0.107173E+09 | 0.64 | 40.01 | 01-MAY-00:10 | 0.64 |
| June | 0.103716E+09 | 0.64 | 40.01 | 01-JUN-00:10 | 0.64 |
| July | 0.107173E+09 | 0.64 | 40.01 | 01-JUL-00:10 | 0.64 |
| August | 0.107173E+09 | 0.64 | 40.01 | 01-AUG-00:10 | 0.64 |
| September | 0.103716E+09 | 0.64 | 40.01 | 01-SEP-00:10 | 0.64 |
| October | 0.107173E+09 | 0.64 | 40.01 | 01-OCT-00:10 | 0.64 |
| November | 0.103716E+09 | 0.64 | 40.01 | 01-NOV-00:10 | 0.64 |
| December | 0.107173E+09 | 0.64 | 40.01 | 01-DEC-00:10 | 0.64 |
| Annual Sum or Average | 0.126188E+10 | 0.64 | |||
| Minimum of Months | 96801429.15 | 0.64 | 40.01 | 0.64 | |
| Maximum of Months | 0.107173E+09 | 0.64 | 40.01 | 0.64 |
Report: FanReportMonthly
For: M N2 APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.107173E+09 | 0.64 | 40.01 | 01-JAN-00:10 | 0.64 |
| February | 96801429.15 | 0.64 | 40.01 | 01-FEB-00:10 | 0.64 |
| March | 0.107173E+09 | 0.64 | 40.01 | 01-MAR-00:10 | 0.64 |
| April | 0.103716E+09 | 0.64 | 40.01 | 01-APR-00:10 | 0.64 |
| May | 0.107173E+09 | 0.64 | 40.01 | 01-MAY-00:10 | 0.64 |
| June | 0.103716E+09 | 0.64 | 40.01 | 01-JUN-00:10 | 0.64 |
| July | 0.107173E+09 | 0.64 | 40.01 | 01-JUL-00:10 | 0.64 |
| August | 0.107173E+09 | 0.64 | 40.01 | 01-AUG-00:10 | 0.64 |
| September | 0.103716E+09 | 0.64 | 40.01 | 01-SEP-00:10 | 0.64 |
| October | 0.107173E+09 | 0.64 | 40.01 | 01-OCT-00:10 | 0.64 |
| November | 0.103716E+09 | 0.64 | 40.01 | 01-NOV-00:10 | 0.64 |
| December | 0.107173E+09 | 0.64 | 40.01 | 01-DEC-00:10 | 0.64 |
| Annual Sum or Average | 0.126188E+10 | 0.64 | |||
| Minimum of Months | 96801429.15 | 0.64 | 40.01 | 0.64 | |
| Maximum of Months | 0.107173E+09 | 0.64 | 40.01 | 0.64 |
Report: FanReportMonthly
For: SPLIT MS1 SUPPLY FAN
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 60097192.77 | 0.73 | 70.38 | 15-JAN-05:00 | 0.93 |
| February | 30496264.42 | 0.40 | 117.10 | 27-FEB-15:10 | 1.07 |
| March | 14821372.46 | 0.13 | 163.54 | 02-MAR-14:00 | 1.06 |
| April | 63360819.59 | 0.35 | 314.45 | 27-APR-14:30 | 1.03 |
| May | 0.137020E+09 | 0.68 | 277.22 | 15-MAY-14:10 | 1.04 |
| June | 0.187967E+09 | 0.94 | 263.07 | 28-JUN-15:10 | 1.04 |
| July | 0.293806E+09 | 1.05 | 338.56 | 24-JUL-13:40 | 1.02 |
| August | 0.341902E+09 | 1.04 | 393.55 | 29-AUG-14:30 | 1.01 |
| September | 0.235876E+09 | 0.95 | 369.46 | 23-SEP-13:40 | 1.01 |
| October | 80231833.68 | 0.40 | 313.29 | 04-OCT-14:10 | 1.03 |
| November | 24187060.41 | 0.34 | 218.65 | 04-NOV-14:00 | 1.04 |
| December | 47734077.98 | 0.61 | 67.03 | 26-DEC-04:00 | 0.93 |
| Annual Sum or Average | 0.151750E+10 | 0.64 | |||
| Minimum of Months | 14821372.46 | 0.13 | 67.03 | 0.93 | |
| Maximum of Months | 0.341902E+09 | 1.05 | 393.55 | 1.07 |
Report: FanReportMonthly
For: M S1 APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.107173E+09 | 0.64 | 40.01 | 01-JAN-00:10 | 0.64 |
| February | 96801429.15 | 0.64 | 40.01 | 01-FEB-00:10 | 0.64 |
| March | 0.107173E+09 | 0.64 | 40.01 | 01-MAR-00:10 | 0.64 |
| April | 0.103716E+09 | 0.64 | 40.01 | 01-APR-00:10 | 0.64 |
| May | 0.107173E+09 | 0.64 | 40.01 | 01-MAY-00:10 | 0.64 |
| June | 0.103716E+09 | 0.64 | 40.01 | 01-JUN-00:10 | 0.64 |
| July | 0.107173E+09 | 0.64 | 40.01 | 01-JUL-00:10 | 0.64 |
| August | 0.107173E+09 | 0.64 | 40.01 | 01-AUG-00:10 | 0.64 |
| September | 0.103716E+09 | 0.64 | 40.01 | 01-SEP-00:10 | 0.64 |
| October | 0.107173E+09 | 0.64 | 40.01 | 01-OCT-00:10 | 0.64 |
| November | 0.103716E+09 | 0.64 | 40.01 | 01-NOV-00:10 | 0.64 |
| December | 0.107173E+09 | 0.64 | 40.01 | 01-DEC-00:10 | 0.64 |
| Annual Sum or Average | 0.126188E+10 | 0.64 | |||
| Minimum of Months | 96801429.15 | 0.64 | 40.01 | 0.64 | |
| Maximum of Months | 0.107173E+09 | 0.64 | 40.01 | 0.64 |
Report: FanReportMonthly
For: M S1 APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.107173E+09 | 0.64 | 40.01 | 01-JAN-00:10 | 0.64 |
| February | 96801429.15 | 0.64 | 40.01 | 01-FEB-00:10 | 0.64 |
| March | 0.107173E+09 | 0.64 | 40.01 | 01-MAR-00:10 | 0.64 |
| April | 0.103716E+09 | 0.64 | 40.01 | 01-APR-00:10 | 0.64 |
| May | 0.107173E+09 | 0.64 | 40.01 | 01-MAY-00:10 | 0.64 |
| June | 0.103716E+09 | 0.64 | 40.01 | 01-JUN-00:10 | 0.64 |
| July | 0.107173E+09 | 0.64 | 40.01 | 01-JUL-00:10 | 0.64 |
| August | 0.107173E+09 | 0.64 | 40.01 | 01-AUG-00:10 | 0.64 |
| September | 0.103716E+09 | 0.64 | 40.01 | 01-SEP-00:10 | 0.64 |
| October | 0.107173E+09 | 0.64 | 40.01 | 01-OCT-00:10 | 0.64 |
| November | 0.103716E+09 | 0.64 | 40.01 | 01-NOV-00:10 | 0.64 |
| December | 0.107173E+09 | 0.64 | 40.01 | 01-DEC-00:10 | 0.64 |
| Annual Sum or Average | 0.126188E+10 | 0.64 | |||
| Minimum of Months | 96801429.15 | 0.64 | 40.01 | 0.64 | |
| Maximum of Months | 0.107173E+09 | 0.64 | 40.01 | 0.64 |
Report: FanReportMonthly
For: SPLIT MS2 SUPPLY FAN
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 60139450.80 | 0.74 | 70.44 | 15-JAN-05:00 | 0.93 |
| February | 30455828.51 | 0.40 | 116.59 | 27-FEB-15:00 | 1.07 |
| March | 14750988.02 | 0.13 | 165.10 | 02-MAR-14:00 | 1.06 |
| April | 64320842.23 | 0.36 | 315.14 | 27-APR-14:20 | 1.03 |
| May | 0.136720E+09 | 0.68 | 277.93 | 15-MAY-14:10 | 1.04 |
| June | 0.188589E+09 | 0.94 | 263.12 | 28-JUN-15:10 | 1.04 |
| July | 0.292913E+09 | 1.05 | 339.63 | 24-JUL-13:40 | 1.02 |
| August | 0.341934E+09 | 1.04 | 394.35 | 29-AUG-14:30 | 1.01 |
| September | 0.235294E+09 | 0.95 | 369.87 | 23-SEP-13:40 | 1.01 |
| October | 80353791.33 | 0.40 | 313.49 | 04-OCT-14:10 | 1.03 |
| November | 24217723.21 | 0.34 | 219.58 | 04-NOV-14:00 | 1.04 |
| December | 47766492.84 | 0.61 | 67.00 | 26-DEC-04:00 | 0.93 |
| Annual Sum or Average | 0.151746E+10 | 0.64 | |||
| Minimum of Months | 14750988.02 | 0.13 | 67.00 | 0.93 | |
| Maximum of Months | 0.341934E+09 | 1.05 | 394.35 | 1.07 |
Report: FanReportMonthly
For: M S2 APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.107173E+09 | 0.64 | 40.01 | 01-JAN-00:10 | 0.64 |
| February | 96801429.15 | 0.64 | 40.01 | 01-FEB-00:10 | 0.64 |
| March | 0.107173E+09 | 0.64 | 40.01 | 01-MAR-00:10 | 0.64 |
| April | 0.103716E+09 | 0.64 | 40.01 | 01-APR-00:10 | 0.64 |
| May | 0.107173E+09 | 0.64 | 40.01 | 01-MAY-00:10 | 0.64 |
| June | 0.103716E+09 | 0.64 | 40.01 | 01-JUN-00:10 | 0.64 |
| July | 0.107173E+09 | 0.64 | 40.01 | 01-JUL-00:10 | 0.64 |
| August | 0.107173E+09 | 0.64 | 40.01 | 01-AUG-00:10 | 0.64 |
| September | 0.103716E+09 | 0.64 | 40.01 | 01-SEP-00:10 | 0.64 |
| October | 0.107173E+09 | 0.64 | 40.01 | 01-OCT-00:10 | 0.64 |
| November | 0.103716E+09 | 0.64 | 40.01 | 01-NOV-00:10 | 0.64 |
| December | 0.107173E+09 | 0.64 | 40.01 | 01-DEC-00:10 | 0.64 |
| Annual Sum or Average | 0.126188E+10 | 0.64 | |||
| Minimum of Months | 96801429.15 | 0.64 | 40.01 | 0.64 | |
| Maximum of Months | 0.107173E+09 | 0.64 | 40.01 | 0.64 |
Report: FanReportMonthly
For: M S2 APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.107173E+09 | 0.64 | 40.01 | 01-JAN-00:10 | 0.64 |
| February | 96801429.15 | 0.64 | 40.01 | 01-FEB-00:10 | 0.64 |
| March | 0.107173E+09 | 0.64 | 40.01 | 01-MAR-00:10 | 0.64 |
| April | 0.103716E+09 | 0.64 | 40.01 | 01-APR-00:10 | 0.64 |
| May | 0.107173E+09 | 0.64 | 40.01 | 01-MAY-00:10 | 0.64 |
| June | 0.103716E+09 | 0.64 | 40.01 | 01-JUN-00:10 | 0.64 |
| July | 0.107173E+09 | 0.64 | 40.01 | 01-JUL-00:10 | 0.64 |
| August | 0.107173E+09 | 0.64 | 40.01 | 01-AUG-00:10 | 0.64 |
| September | 0.103716E+09 | 0.64 | 40.01 | 01-SEP-00:10 | 0.64 |
| October | 0.107173E+09 | 0.64 | 40.01 | 01-OCT-00:10 | 0.64 |
| November | 0.103716E+09 | 0.64 | 40.01 | 01-NOV-00:10 | 0.64 |
| December | 0.107173E+09 | 0.64 | 40.01 | 01-DEC-00:10 | 0.64 |
| Annual Sum or Average | 0.126188E+10 | 0.64 | |||
| Minimum of Months | 96801429.15 | 0.64 | 40.01 | 0.64 | |
| Maximum of Months | 0.107173E+09 | 0.64 | 40.01 | 0.64 |
Report: FanReportMonthly
For: SPLIT TSW SUPPLY FAN
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.133152E+09 | 0.90 | 103.64 | 15-JAN-05:00 | 0.93 |
| February | 90155606.64 | 0.77 | 143.29 | 27-FEB-15:30 | 1.05 |
| March | 68203493.83 | 0.68 | 156.52 | 14-MAR-16:05 | 1.05 |
| April | 68236420.50 | 0.58 | 270.79 | 27-APR-15:10 | 1.01 |
| May | 82483406.40 | 0.53 | 256.07 | 15-MAY-16:10 | 1.01 |
| June | 95915091.57 | 0.49 | 256.75 | 28-JUN-16:16 | 1.01 |
| July | 0.174110E+09 | 0.59 | 308.23 | 31-JUL-16:02 | 0.99 |
| August | 0.186231E+09 | 0.62 | 342.95 | 10-AUG-16:03 | 0.98 |
| September | 0.105305E+09 | 0.45 | 280.70 | 14-SEP-15:10 | 1.00 |
| October | 49927410.40 | 0.59 | 225.11 | 04-OCT-15:10 | 1.03 |
| November | 83564399.37 | 0.81 | 191.95 | 04-NOV-14:30 | 1.03 |
| December | 0.119740E+09 | 0.86 | 92.14 | 26-DEC-08:45 | 0.93 |
| Annual Sum or Average | 0.125702E+10 | 0.66 | |||
| Minimum of Months | 49927410.40 | 0.45 | 92.14 | 0.93 | |
| Maximum of Months | 0.186231E+09 | 0.90 | 342.95 | 1.05 |
Report: FanReportMonthly
For: T SW APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.64 | 20.01 | 01-JAN-00:10 | 0.64 |
| February | 48400714.57 | 0.64 | 20.01 | 01-FEB-00:10 | 0.64 |
| March | 53586505.42 | 0.64 | 20.01 | 01-MAR-00:10 | 0.64 |
| April | 51857908.47 | 0.64 | 20.01 | 01-APR-00:10 | 0.64 |
| May | 53586505.42 | 0.64 | 20.01 | 01-MAY-00:10 | 0.64 |
| June | 51857908.47 | 0.64 | 20.01 | 01-JUN-00:10 | 0.64 |
| July | 53586505.42 | 0.64 | 20.01 | 01-JUL-00:10 | 0.64 |
| August | 53586505.42 | 0.64 | 20.01 | 01-AUG-00:10 | 0.64 |
| September | 51857908.47 | 0.64 | 20.01 | 01-SEP-00:10 | 0.64 |
| October | 53586505.42 | 0.64 | 20.01 | 01-OCT-00:10 | 0.64 |
| November | 51857908.47 | 0.64 | 20.01 | 01-NOV-00:10 | 0.64 |
| December | 53586505.42 | 0.64 | 20.01 | 01-DEC-00:10 | 0.64 |
| Annual Sum or Average | 0.630938E+09 | 0.64 | |||
| Minimum of Months | 48400714.57 | 0.64 | 20.01 | 0.64 | |
| Maximum of Months | 53586505.42 | 0.64 | 20.01 | 0.64 |
Report: FanReportMonthly
For: T SW APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.64 | 20.01 | 01-JAN-00:10 | 0.64 |
| February | 48400714.57 | 0.64 | 20.01 | 01-FEB-00:10 | 0.64 |
| March | 53586505.42 | 0.64 | 20.01 | 01-MAR-00:10 | 0.64 |
| April | 51857908.47 | 0.64 | 20.01 | 01-APR-00:10 | 0.64 |
| May | 53586505.42 | 0.64 | 20.01 | 01-MAY-00:10 | 0.64 |
| June | 51857908.47 | 0.64 | 20.01 | 01-JUN-00:10 | 0.64 |
| July | 53586505.42 | 0.64 | 20.01 | 01-JUL-00:10 | 0.64 |
| August | 53586505.42 | 0.64 | 20.01 | 01-AUG-00:10 | 0.64 |
| September | 51857908.47 | 0.64 | 20.01 | 01-SEP-00:10 | 0.64 |
| October | 53586505.42 | 0.64 | 20.01 | 01-OCT-00:10 | 0.64 |
| November | 51857908.47 | 0.64 | 20.01 | 01-NOV-00:10 | 0.64 |
| December | 53586505.42 | 0.64 | 20.01 | 01-DEC-00:10 | 0.64 |
| Annual Sum or Average | 0.630938E+09 | 0.64 | |||
| Minimum of Months | 48400714.57 | 0.64 | 20.01 | 0.64 | |
| Maximum of Months | 53586505.42 | 0.64 | 20.01 | 0.64 |
Report: FanReportMonthly
For: SPLIT TNW SUPPLY FAN
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.152256E+09 | 0.93 | 108.48 | 15-JAN-05:00 | 0.93 |
| February | 0.110555E+09 | 0.87 | 125.23 | 19-FEB-06:00 | 0.93 |
| March | 72345462.02 | 0.74 | 79.97 | 24-MAR-06:00 | 0.93 |
| April | 48808714.39 | 0.55 | 195.88 | 27-APR-16:27 | 1.02 |
| May | 52690499.60 | 0.45 | 204.11 | 15-MAY-16:30 | 1.02 |
| June | 69659221.61 | 0.44 | 224.64 | 28-JUN-17:10 | 1.01 |
| July | 0.132455E+09 | 0.56 | 262.85 | 31-JUL-17:10 | 1.00 |
| August | 0.132603E+09 | 0.57 | 285.37 | 10-AUG-17:10 | 0.99 |
| September | 44747667.25 | 0.36 | 185.40 | 14-SEP-16:25 | 1.03 |
| October | 41002394.92 | 0.61 | 80.43 | 04-OCT-16:30 | 1.07 |
| November | 93746465.91 | 0.86 | 79.53 | 11-NOV-06:00 | 0.93 |
| December | 0.139122E+09 | 0.93 | 92.44 | 26-DEC-04:00 | 0.93 |
| Annual Sum or Average | 0.108999E+10 | 0.66 | |||
| Minimum of Months | 41002394.92 | 0.36 | 79.53 | 0.93 | |
| Maximum of Months | 0.152256E+09 | 0.93 | 285.37 | 1.07 |
Report: FanReportMonthly
For: T NW APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.64 | 20.01 | 01-JAN-00:10 | 0.64 |
| February | 48400714.57 | 0.64 | 20.01 | 01-FEB-00:10 | 0.64 |
| March | 53586505.42 | 0.64 | 20.01 | 01-MAR-00:10 | 0.64 |
| April | 51857908.47 | 0.64 | 20.01 | 01-APR-00:10 | 0.64 |
| May | 53586505.42 | 0.64 | 20.01 | 01-MAY-00:10 | 0.64 |
| June | 51857908.47 | 0.64 | 20.01 | 01-JUN-00:10 | 0.64 |
| July | 53586505.42 | 0.64 | 20.01 | 01-JUL-00:10 | 0.64 |
| August | 53586505.42 | 0.64 | 20.01 | 01-AUG-00:10 | 0.64 |
| September | 51857908.47 | 0.64 | 20.01 | 01-SEP-00:10 | 0.64 |
| October | 53586505.42 | 0.64 | 20.01 | 01-OCT-00:10 | 0.64 |
| November | 51857908.47 | 0.64 | 20.01 | 01-NOV-00:10 | 0.64 |
| December | 53586505.42 | 0.64 | 20.01 | 01-DEC-00:10 | 0.64 |
| Annual Sum or Average | 0.630938E+09 | 0.64 | |||
| Minimum of Months | 48400714.57 | 0.64 | 20.01 | 0.64 | |
| Maximum of Months | 53586505.42 | 0.64 | 20.01 | 0.64 |
Report: FanReportMonthly
For: T NW APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.64 | 20.01 | 01-JAN-00:10 | 0.64 |
| February | 48400714.57 | 0.64 | 20.01 | 01-FEB-00:10 | 0.64 |
| March | 53586505.42 | 0.64 | 20.01 | 01-MAR-00:10 | 0.64 |
| April | 51857908.47 | 0.64 | 20.01 | 01-APR-00:10 | 0.64 |
| May | 53586505.42 | 0.64 | 20.01 | 01-MAY-00:10 | 0.64 |
| June | 51857908.47 | 0.64 | 20.01 | 01-JUN-00:10 | 0.64 |
| July | 53586505.42 | 0.64 | 20.01 | 01-JUL-00:10 | 0.64 |
| August | 53586505.42 | 0.64 | 20.01 | 01-AUG-00:10 | 0.64 |
| September | 51857908.47 | 0.64 | 20.01 | 01-SEP-00:10 | 0.64 |
| October | 53586505.42 | 0.64 | 20.01 | 01-OCT-00:10 | 0.64 |
| November | 51857908.47 | 0.64 | 20.01 | 01-NOV-00:10 | 0.64 |
| December | 53586505.42 | 0.64 | 20.01 | 01-DEC-00:10 | 0.64 |
| Annual Sum or Average | 0.630938E+09 | 0.64 | |||
| Minimum of Months | 48400714.57 | 0.64 | 20.01 | 0.64 | |
| Maximum of Months | 53586505.42 | 0.64 | 20.01 | 0.64 |
Report: FanReportMonthly
For: SPLIT TSE SUPPLY FAN
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.131501E+09 | 0.90 | 103.15 | 15-JAN-05:00 | 0.93 |
| February | 87893893.81 | 0.75 | 121.74 | 19-FEB-07:00 | 0.93 |
| March | 64807064.99 | 0.67 | 140.39 | 14-MAR-13:40 | 1.04 |
| April | 63847522.60 | 0.58 | 243.72 | 27-APR-14:10 | 1.00 |
| May | 75479492.73 | 0.53 | 220.76 | 15-MAY-13:50 | 1.01 |
| June | 0.100371E+09 | 0.53 | 218.11 | 28-JUN-13:30 | 1.01 |
| July | 0.161706E+09 | 0.60 | 281.79 | 24-JUL-13:40 | 0.98 |
| August | 0.183599E+09 | 0.64 | 298.64 | 29-AUG-14:30 | 0.98 |
| September | 0.100083E+09 | 0.45 | 256.87 | 14-SEP-13:40 | 0.99 |
| October | 48301281.65 | 0.58 | 193.57 | 04-OCT-13:50 | 1.02 |
| November | 81878354.06 | 0.80 | 168.40 | 04-NOV-14:00 | 1.03 |
| December | 0.118158E+09 | 0.85 | 91.23 | 26-DEC-08:50 | 0.93 |
| Annual Sum or Average | 0.121763E+10 | 0.66 | |||
| Minimum of Months | 48301281.65 | 0.45 | 91.23 | 0.93 | |
| Maximum of Months | 0.183599E+09 | 0.90 | 298.64 | 1.04 |
Report: FanReportMonthly
For: T SE APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.64 | 20.01 | 01-JAN-00:10 | 0.64 |
| February | 48400714.57 | 0.64 | 20.01 | 01-FEB-00:10 | 0.64 |
| March | 53586505.42 | 0.64 | 20.01 | 01-MAR-00:10 | 0.64 |
| April | 51857908.47 | 0.64 | 20.01 | 01-APR-00:10 | 0.64 |
| May | 53586505.42 | 0.64 | 20.01 | 01-MAY-00:10 | 0.64 |
| June | 51857908.47 | 0.64 | 20.01 | 01-JUN-00:10 | 0.64 |
| July | 53586505.42 | 0.64 | 20.01 | 01-JUL-00:10 | 0.64 |
| August | 53586505.42 | 0.64 | 20.01 | 01-AUG-00:10 | 0.64 |
| September | 51857908.47 | 0.64 | 20.01 | 01-SEP-00:10 | 0.64 |
| October | 53586505.42 | 0.64 | 20.01 | 01-OCT-00:10 | 0.64 |
| November | 51857908.47 | 0.64 | 20.01 | 01-NOV-00:10 | 0.64 |
| December | 53586505.42 | 0.64 | 20.01 | 01-DEC-00:10 | 0.64 |
| Annual Sum or Average | 0.630938E+09 | 0.64 | |||
| Minimum of Months | 48400714.57 | 0.64 | 20.01 | 0.64 | |
| Maximum of Months | 53586505.42 | 0.64 | 20.01 | 0.64 |
Report: FanReportMonthly
For: T SE APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.64 | 20.01 | 01-JAN-00:10 | 0.64 |
| February | 48400714.57 | 0.64 | 20.01 | 01-FEB-00:10 | 0.64 |
| March | 53586505.42 | 0.64 | 20.01 | 01-MAR-00:10 | 0.64 |
| April | 51857908.47 | 0.64 | 20.01 | 01-APR-00:10 | 0.64 |
| May | 53586505.42 | 0.64 | 20.01 | 01-MAY-00:10 | 0.64 |
| June | 51857908.47 | 0.64 | 20.01 | 01-JUN-00:10 | 0.64 |
| July | 53586505.42 | 0.64 | 20.01 | 01-JUL-00:10 | 0.64 |
| August | 53586505.42 | 0.64 | 20.01 | 01-AUG-00:10 | 0.64 |
| September | 51857908.47 | 0.64 | 20.01 | 01-SEP-00:10 | 0.64 |
| October | 53586505.42 | 0.64 | 20.01 | 01-OCT-00:10 | 0.64 |
| November | 51857908.47 | 0.64 | 20.01 | 01-NOV-00:10 | 0.64 |
| December | 53586505.42 | 0.64 | 20.01 | 01-DEC-00:10 | 0.64 |
| Annual Sum or Average | 0.630938E+09 | 0.64 | |||
| Minimum of Months | 48400714.57 | 0.64 | 20.01 | 0.64 | |
| Maximum of Months | 53586505.42 | 0.64 | 20.01 | 0.64 |
Report: FanReportMonthly
For: SPLIT TNE SUPPLY FAN
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.150035E+09 | 0.93 | 107.56 | 15-JAN-05:00 | 0.93 |
| February | 0.108704E+09 | 0.87 | 123.29 | 19-FEB-07:00 | 0.93 |
| March | 69411855.44 | 0.74 | 78.99 | 24-MAR-06:00 | 0.93 |
| April | 42662574.52 | 0.51 | 147.57 | 27-APR-16:07 | 1.03 |
| May | 44576076.49 | 0.46 | 145.42 | 06-MAY-13:40 | 1.03 |
| June | 73176220.84 | 0.51 | 163.55 | 28-JUN-16:14 | 1.02 |
| July | 0.120795E+09 | 0.58 | 212.48 | 24-JUL-15:10 | 1.00 |
| August | 0.130351E+09 | 0.59 | 205.76 | 10-AUG-16:30 | 1.00 |
| September | 39644222.21 | 0.37 | 132.14 | 14-SEP-16:12 | 1.03 |
| October | 39126145.21 | 0.60 | 54.46 | 28-OCT-04:00 | 0.93 |
| November | 91815548.20 | 0.86 | 79.15 | 11-NOV-06:00 | 0.93 |
| December | 0.137157E+09 | 0.93 | 91.16 | 26-DEC-04:00 | 0.93 |
| Annual Sum or Average | 0.104746E+10 | 0.66 | |||
| Minimum of Months | 39126145.21 | 0.37 | 54.46 | 0.93 | |
| Maximum of Months | 0.150035E+09 | 0.93 | 212.48 | 1.03 |
Report: FanReportMonthly
For: T NE APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.64 | 20.01 | 01-JAN-00:10 | 0.64 |
| February | 48400714.57 | 0.64 | 20.01 | 01-FEB-00:10 | 0.64 |
| March | 53586505.42 | 0.64 | 20.01 | 01-MAR-00:10 | 0.64 |
| April | 51857908.47 | 0.64 | 20.01 | 01-APR-00:10 | 0.64 |
| May | 53586505.42 | 0.64 | 20.01 | 01-MAY-00:10 | 0.64 |
| June | 51857908.47 | 0.64 | 20.01 | 01-JUN-00:10 | 0.64 |
| July | 53586505.42 | 0.64 | 20.01 | 01-JUL-00:10 | 0.64 |
| August | 53586505.42 | 0.64 | 20.01 | 01-AUG-00:10 | 0.64 |
| September | 51857908.47 | 0.64 | 20.01 | 01-SEP-00:10 | 0.64 |
| October | 53586505.42 | 0.64 | 20.01 | 01-OCT-00:10 | 0.64 |
| November | 51857908.47 | 0.64 | 20.01 | 01-NOV-00:10 | 0.64 |
| December | 53586505.42 | 0.64 | 20.01 | 01-DEC-00:10 | 0.64 |
| Annual Sum or Average | 0.630938E+09 | 0.64 | |||
| Minimum of Months | 48400714.57 | 0.64 | 20.01 | 0.64 | |
| Maximum of Months | 53586505.42 | 0.64 | 20.01 | 0.64 |
Report: FanReportMonthly
For: T NE APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.64 | 20.01 | 01-JAN-00:10 | 0.64 |
| February | 48400714.57 | 0.64 | 20.01 | 01-FEB-00:10 | 0.64 |
| March | 53586505.42 | 0.64 | 20.01 | 01-MAR-00:10 | 0.64 |
| April | 51857908.47 | 0.64 | 20.01 | 01-APR-00:10 | 0.64 |
| May | 53586505.42 | 0.64 | 20.01 | 01-MAY-00:10 | 0.64 |
| June | 51857908.47 | 0.64 | 20.01 | 01-JUN-00:10 | 0.64 |
| July | 53586505.42 | 0.64 | 20.01 | 01-JUL-00:10 | 0.64 |
| August | 53586505.42 | 0.64 | 20.01 | 01-AUG-00:10 | 0.64 |
| September | 51857908.47 | 0.64 | 20.01 | 01-SEP-00:10 | 0.64 |
| October | 53586505.42 | 0.64 | 20.01 | 01-OCT-00:10 | 0.64 |
| November | 51857908.47 | 0.64 | 20.01 | 01-NOV-00:10 | 0.64 |
| December | 53586505.42 | 0.64 | 20.01 | 01-DEC-00:10 | 0.64 |
| Annual Sum or Average | 0.630938E+09 | 0.64 | |||
| Minimum of Months | 48400714.57 | 0.64 | 20.01 | 0.64 | |
| Maximum of Months | 53586505.42 | 0.64 | 20.01 | 0.64 |
Report: FanReportMonthly
For: SPLIT TN1 SUPPLY FAN
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.104883E+09 | 0.93 | 79.27 | 15-JAN-05:00 | 0.93 |
| February | 75733417.55 | 0.85 | 90.48 | 19-FEB-06:00 | 0.93 |
| March | 45368718.07 | 0.70 | 54.30 | 02-MAR-06:00 | 0.93 |
| April | 26711896.99 | 0.45 | 117.34 | 27-APR-16:07 | 1.04 |
| May | 27956935.93 | 0.33 | 116.38 | 15-MAY-16:15 | 1.04 |
| June | 51257872.63 | 0.46 | 141.12 | 28-JUN-17:20 | 1.03 |
| July | 95709102.90 | 0.60 | 174.28 | 24-JUL-18:00 | 1.01 |
| August | 0.102005E+09 | 0.62 | 175.34 | 10-AUG-16:40 | 1.01 |
| September | 27098336.13 | 0.29 | 112.68 | 14-SEP-16:25 | 1.04 |
| October | 21591675.19 | 0.51 | 35.68 | 28-OCT-04:00 | 0.93 |
| November | 60321517.57 | 0.82 | 57.12 | 11-NOV-06:00 | 0.93 |
| December | 95403824.78 | 0.93 | 67.01 | 26-DEC-04:00 | 0.93 |
| Annual Sum or Average | 0.734041E+09 | 0.62 | |||
| Minimum of Months | 21591675.19 | 0.29 | 35.68 | 0.93 | |
| Maximum of Months | 0.104883E+09 | 0.93 | 175.34 | 1.04 |
Report: FanReportMonthly
For: T N1 APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.64 | 20.01 | 01-JAN-00:10 | 0.64 |
| February | 48400714.57 | 0.64 | 20.01 | 01-FEB-00:10 | 0.64 |
| March | 53586505.42 | 0.64 | 20.01 | 01-MAR-00:10 | 0.64 |
| April | 51857908.47 | 0.64 | 20.01 | 01-APR-00:10 | 0.64 |
| May | 53586505.42 | 0.64 | 20.01 | 01-MAY-00:10 | 0.64 |
| June | 51857908.47 | 0.64 | 20.01 | 01-JUN-00:10 | 0.64 |
| July | 53586505.42 | 0.64 | 20.01 | 01-JUL-00:10 | 0.64 |
| August | 53586505.42 | 0.64 | 20.01 | 01-AUG-00:10 | 0.64 |
| September | 51857908.47 | 0.64 | 20.01 | 01-SEP-00:10 | 0.64 |
| October | 53586505.42 | 0.64 | 20.01 | 01-OCT-00:10 | 0.64 |
| November | 51857908.47 | 0.64 | 20.01 | 01-NOV-00:10 | 0.64 |
| December | 53586505.42 | 0.64 | 20.01 | 01-DEC-00:10 | 0.64 |
| Annual Sum or Average | 0.630938E+09 | 0.64 | |||
| Minimum of Months | 48400714.57 | 0.64 | 20.01 | 0.64 | |
| Maximum of Months | 53586505.42 | 0.64 | 20.01 | 0.64 |
Report: FanReportMonthly
For: T N1 APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.64 | 20.01 | 01-JAN-00:10 | 0.64 |
| February | 48400714.57 | 0.64 | 20.01 | 01-FEB-00:10 | 0.64 |
| March | 53586505.42 | 0.64 | 20.01 | 01-MAR-00:10 | 0.64 |
| April | 51857908.47 | 0.64 | 20.01 | 01-APR-00:10 | 0.64 |
| May | 53586505.42 | 0.64 | 20.01 | 01-MAY-00:10 | 0.64 |
| June | 51857908.47 | 0.64 | 20.01 | 01-JUN-00:10 | 0.64 |
| July | 53586505.42 | 0.64 | 20.01 | 01-JUL-00:10 | 0.64 |
| August | 53586505.42 | 0.64 | 20.01 | 01-AUG-00:10 | 0.64 |
| September | 51857908.47 | 0.64 | 20.01 | 01-SEP-00:10 | 0.64 |
| October | 53586505.42 | 0.64 | 20.01 | 01-OCT-00:10 | 0.64 |
| November | 51857908.47 | 0.64 | 20.01 | 01-NOV-00:10 | 0.64 |
| December | 53586505.42 | 0.64 | 20.01 | 01-DEC-00:10 | 0.64 |
| Annual Sum or Average | 0.630938E+09 | 0.64 | |||
| Minimum of Months | 48400714.57 | 0.64 | 20.01 | 0.64 | |
| Maximum of Months | 53586505.42 | 0.64 | 20.01 | 0.64 |
Report: FanReportMonthly
For: SPLIT TN2 SUPPLY FAN
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.104825E+09 | 0.93 | 79.27 | 15-JAN-05:00 | 0.93 |
| February | 75705152.19 | 0.85 | 90.40 | 19-FEB-06:00 | 0.93 |
| March | 45364670.63 | 0.70 | 54.44 | 02-MAR-06:00 | 0.93 |
| April | 26667208.38 | 0.45 | 117.09 | 27-APR-16:07 | 1.04 |
| May | 28044043.56 | 0.33 | 115.58 | 15-MAY-16:15 | 1.04 |
| June | 51909608.52 | 0.46 | 139.58 | 28-JUN-17:20 | 1.03 |
| July | 95503567.16 | 0.60 | 173.16 | 24-JUL-18:00 | 1.01 |
| August | 0.102312E+09 | 0.62 | 173.83 | 10-AUG-16:40 | 1.01 |
| September | 27248494.88 | 0.29 | 111.74 | 14-SEP-16:25 | 1.04 |
| October | 21617262.87 | 0.51 | 35.64 | 28-OCT-04:00 | 0.93 |
| November | 60281886.89 | 0.82 | 57.14 | 11-NOV-06:00 | 0.93 |
| December | 95360770.47 | 0.93 | 66.96 | 26-DEC-04:00 | 0.93 |
| Annual Sum or Average | 0.734840E+09 | 0.62 | |||
| Minimum of Months | 21617262.87 | 0.29 | 35.64 | 0.93 | |
| Maximum of Months | 0.104825E+09 | 0.93 | 173.83 | 1.04 |
Report: FanReportMonthly
For: T N2 APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.64 | 20.01 | 01-JAN-00:10 | 0.64 |
| February | 48400714.57 | 0.64 | 20.01 | 01-FEB-00:10 | 0.64 |
| March | 53586505.42 | 0.64 | 20.01 | 01-MAR-00:10 | 0.64 |
| April | 51857908.47 | 0.64 | 20.01 | 01-APR-00:10 | 0.64 |
| May | 53586505.42 | 0.64 | 20.01 | 01-MAY-00:10 | 0.64 |
| June | 51857908.47 | 0.64 | 20.01 | 01-JUN-00:10 | 0.64 |
| July | 53586505.42 | 0.64 | 20.01 | 01-JUL-00:10 | 0.64 |
| August | 53586505.42 | 0.64 | 20.01 | 01-AUG-00:10 | 0.64 |
| September | 51857908.47 | 0.64 | 20.01 | 01-SEP-00:10 | 0.64 |
| October | 53586505.42 | 0.64 | 20.01 | 01-OCT-00:10 | 0.64 |
| November | 51857908.47 | 0.64 | 20.01 | 01-NOV-00:10 | 0.64 |
| December | 53586505.42 | 0.64 | 20.01 | 01-DEC-00:10 | 0.64 |
| Annual Sum or Average | 0.630938E+09 | 0.64 | |||
| Minimum of Months | 48400714.57 | 0.64 | 20.01 | 0.64 | |
| Maximum of Months | 53586505.42 | 0.64 | 20.01 | 0.64 |
Report: FanReportMonthly
For: T N2 APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.64 | 20.01 | 01-JAN-00:10 | 0.64 |
| February | 48400714.57 | 0.64 | 20.01 | 01-FEB-00:10 | 0.64 |
| March | 53586505.42 | 0.64 | 20.01 | 01-MAR-00:10 | 0.64 |
| April | 51857908.47 | 0.64 | 20.01 | 01-APR-00:10 | 0.64 |
| May | 53586505.42 | 0.64 | 20.01 | 01-MAY-00:10 | 0.64 |
| June | 51857908.47 | 0.64 | 20.01 | 01-JUN-00:10 | 0.64 |
| July | 53586505.42 | 0.64 | 20.01 | 01-JUL-00:10 | 0.64 |
| August | 53586505.42 | 0.64 | 20.01 | 01-AUG-00:10 | 0.64 |
| September | 51857908.47 | 0.64 | 20.01 | 01-SEP-00:10 | 0.64 |
| October | 53586505.42 | 0.64 | 20.01 | 01-OCT-00:10 | 0.64 |
| November | 51857908.47 | 0.64 | 20.01 | 01-NOV-00:10 | 0.64 |
| December | 53586505.42 | 0.64 | 20.01 | 01-DEC-00:10 | 0.64 |
| Annual Sum or Average | 0.630938E+09 | 0.64 | |||
| Minimum of Months | 48400714.57 | 0.64 | 20.01 | 0.64 | |
| Maximum of Months | 53586505.42 | 0.64 | 20.01 | 0.64 |
Report: FanReportMonthly
For: SPLIT TS1 SUPPLY FAN
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 86784515.00 | 0.88 | 74.20 | 15-JAN-05:00 | 0.93 |
| February | 57381042.08 | 0.72 | 106.14 | 27-FEB-15:10 | 1.05 |
| March | 41165255.07 | 0.60 | 126.87 | 14-MAR-14:00 | 1.04 |
| April | 45316795.67 | 0.50 | 211.72 | 27-APR-14:30 | 1.01 |
| May | 57819217.83 | 0.44 | 186.79 | 15-MAY-14:10 | 1.02 |
| June | 78343046.50 | 0.52 | 183.79 | 28-JUN-14:10 | 1.02 |
| July | 0.138040E+09 | 0.63 | 235.03 | 24-JUL-13:50 | 1.00 |
| August | 0.156916E+09 | 0.68 | 263.18 | 29-AUG-14:30 | 0.99 |
| September | 89428133.99 | 0.46 | 234.81 | 23-SEP-13:50 | 1.00 |
| October | 34352143.90 | 0.50 | 182.79 | 04-OCT-14:10 | 1.02 |
| November | 51823836.34 | 0.73 | 164.20 | 04-NOV-14:00 | 1.02 |
| December | 78001909.26 | 0.83 | 66.36 | 26-DEC-09:00 | 0.93 |
| Annual Sum or Average | 0.915372E+09 | 0.62 | |||
| Minimum of Months | 34352143.90 | 0.44 | 66.36 | 0.93 | |
| Maximum of Months | 0.156916E+09 | 0.88 | 263.18 | 1.05 |
Report: FanReportMonthly
For: T S1 APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.64 | 20.01 | 01-JAN-00:10 | 0.64 |
| February | 48400714.57 | 0.64 | 20.01 | 01-FEB-00:10 | 0.64 |
| March | 53586505.42 | 0.64 | 20.01 | 01-MAR-00:10 | 0.64 |
| April | 51857908.47 | 0.64 | 20.01 | 01-APR-00:10 | 0.64 |
| May | 53586505.42 | 0.64 | 20.01 | 01-MAY-00:10 | 0.64 |
| June | 51857908.47 | 0.64 | 20.01 | 01-JUN-00:10 | 0.64 |
| July | 53586505.42 | 0.64 | 20.01 | 01-JUL-00:10 | 0.64 |
| August | 53586505.42 | 0.64 | 20.01 | 01-AUG-00:10 | 0.64 |
| September | 51857908.47 | 0.64 | 20.01 | 01-SEP-00:10 | 0.64 |
| October | 53586505.42 | 0.64 | 20.01 | 01-OCT-00:10 | 0.64 |
| November | 51857908.47 | 0.64 | 20.01 | 01-NOV-00:10 | 0.64 |
| December | 53586505.42 | 0.64 | 20.01 | 01-DEC-00:10 | 0.64 |
| Annual Sum or Average | 0.630938E+09 | 0.64 | |||
| Minimum of Months | 48400714.57 | 0.64 | 20.01 | 0.64 | |
| Maximum of Months | 53586505.42 | 0.64 | 20.01 | 0.64 |
Report: FanReportMonthly
For: T S1 APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.64 | 20.01 | 01-JAN-00:10 | 0.64 |
| February | 48400714.57 | 0.64 | 20.01 | 01-FEB-00:10 | 0.64 |
| March | 53586505.42 | 0.64 | 20.01 | 01-MAR-00:10 | 0.64 |
| April | 51857908.47 | 0.64 | 20.01 | 01-APR-00:10 | 0.64 |
| May | 53586505.42 | 0.64 | 20.01 | 01-MAY-00:10 | 0.64 |
| June | 51857908.47 | 0.64 | 20.01 | 01-JUN-00:10 | 0.64 |
| July | 53586505.42 | 0.64 | 20.01 | 01-JUL-00:10 | 0.64 |
| August | 53586505.42 | 0.64 | 20.01 | 01-AUG-00:10 | 0.64 |
| September | 51857908.47 | 0.64 | 20.01 | 01-SEP-00:10 | 0.64 |
| October | 53586505.42 | 0.64 | 20.01 | 01-OCT-00:10 | 0.64 |
| November | 51857908.47 | 0.64 | 20.01 | 01-NOV-00:10 | 0.64 |
| December | 53586505.42 | 0.64 | 20.01 | 01-DEC-00:10 | 0.64 |
| Annual Sum or Average | 0.630938E+09 | 0.64 | |||
| Minimum of Months | 48400714.57 | 0.64 | 20.01 | 0.64 | |
| Maximum of Months | 53586505.42 | 0.64 | 20.01 | 0.64 |
Report: FanReportMonthly
For: SPLIT TS2 SUPPLY FAN
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 86774589.85 | 0.88 | 74.22 | 15-JAN-05:00 | 0.93 |
| February | 57421733.80 | 0.72 | 105.90 | 27-FEB-15:00 | 1.05 |
| March | 41280820.54 | 0.60 | 128.25 | 14-MAR-14:00 | 1.04 |
| April | 45612199.18 | 0.51 | 212.27 | 27-APR-14:20 | 1.01 |
| May | 58030998.12 | 0.44 | 187.68 | 15-MAY-14:10 | 1.02 |
| June | 79045490.30 | 0.52 | 184.45 | 28-JUN-14:10 | 1.02 |
| July | 0.137810E+09 | 0.63 | 235.78 | 24-JUL-13:50 | 1.00 |
| August | 0.157171E+09 | 0.68 | 263.43 | 29-AUG-14:30 | 0.99 |
| September | 89435830.55 | 0.46 | 235.09 | 23-SEP-13:50 | 1.00 |
| October | 34598130.61 | 0.50 | 183.28 | 04-OCT-14:10 | 1.02 |
| November | 51826989.79 | 0.73 | 164.46 | 04-NOV-14:00 | 1.02 |
| December | 78021717.86 | 0.83 | 66.31 | 26-DEC-09:00 | 0.93 |
| Annual Sum or Average | 0.917029E+09 | 0.62 | |||
| Minimum of Months | 34598130.61 | 0.44 | 66.31 | 0.93 | |
| Maximum of Months | 0.157171E+09 | 0.88 | 263.43 | 1.05 |
Report: FanReportMonthly
For: T S2 APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.64 | 20.01 | 01-JAN-00:10 | 0.64 |
| February | 48400714.57 | 0.64 | 20.01 | 01-FEB-00:10 | 0.64 |
| March | 53586505.42 | 0.64 | 20.01 | 01-MAR-00:10 | 0.64 |
| April | 51857908.47 | 0.64 | 20.01 | 01-APR-00:10 | 0.64 |
| May | 53586505.42 | 0.64 | 20.01 | 01-MAY-00:10 | 0.64 |
| June | 51857908.47 | 0.64 | 20.01 | 01-JUN-00:10 | 0.64 |
| July | 53586505.42 | 0.64 | 20.01 | 01-JUL-00:10 | 0.64 |
| August | 53586505.42 | 0.64 | 20.01 | 01-AUG-00:10 | 0.64 |
| September | 51857908.47 | 0.64 | 20.01 | 01-SEP-00:10 | 0.64 |
| October | 53586505.42 | 0.64 | 20.01 | 01-OCT-00:10 | 0.64 |
| November | 51857908.47 | 0.64 | 20.01 | 01-NOV-00:10 | 0.64 |
| December | 53586505.42 | 0.64 | 20.01 | 01-DEC-00:10 | 0.64 |
| Annual Sum or Average | 0.630938E+09 | 0.64 | |||
| Minimum of Months | 48400714.57 | 0.64 | 20.01 | 0.64 | |
| Maximum of Months | 53586505.42 | 0.64 | 20.01 | 0.64 |
Report: FanReportMonthly
For: T S2 APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.64 | 20.01 | 01-JAN-00:10 | 0.64 |
| February | 48400714.57 | 0.64 | 20.01 | 01-FEB-00:10 | 0.64 |
| March | 53586505.42 | 0.64 | 20.01 | 01-MAR-00:10 | 0.64 |
| April | 51857908.47 | 0.64 | 20.01 | 01-APR-00:10 | 0.64 |
| May | 53586505.42 | 0.64 | 20.01 | 01-MAY-00:10 | 0.64 |
| June | 51857908.47 | 0.64 | 20.01 | 01-JUN-00:10 | 0.64 |
| July | 53586505.42 | 0.64 | 20.01 | 01-JUL-00:10 | 0.64 |
| August | 53586505.42 | 0.64 | 20.01 | 01-AUG-00:10 | 0.64 |
| September | 51857908.47 | 0.64 | 20.01 | 01-SEP-00:10 | 0.64 |
| October | 53586505.42 | 0.64 | 20.01 | 01-OCT-00:10 | 0.64 |
| November | 51857908.47 | 0.64 | 20.01 | 01-NOV-00:10 | 0.64 |
| December | 53586505.42 | 0.64 | 20.01 | 01-DEC-00:10 | 0.64 |
| Annual Sum or Average | 0.630938E+09 | 0.64 | |||
| Minimum of Months | 48400714.57 | 0.64 | 20.01 | 0.64 | |
| Maximum of Months | 53586505.42 | 0.64 | 20.01 | 0.64 |
Report: ZoneTemperatureOscillationReportMonthly
For: G SW APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: G NW APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: OFFICE
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: G NE APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: G N1 APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: G N2 APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: G S1 APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: G S2 APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: M SW APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: M NW APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: M SE APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: M NE APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: M N1 APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: M N2 APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: M S1 APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: M S2 APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: T SW APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: T NW APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: T SE APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: T NE APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: T N1 APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: T N2 APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: T S1 APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: T S2 APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: T CORRIDOR
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: G CORRIDOR
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: M CORRIDOR
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT GSW
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 93814551.55 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 63056303.39 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 36833526.38 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 40235983.14 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 79337997.61 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.168653E+09 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.485535E+09 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.615372E+09 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.323398E+09 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 58952377.87 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 39230974.88 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 75354257.59 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.207977E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 36833526.38 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.615372E+09 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT GNW
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.111175E+09 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 85861521.35 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 59403444.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 31582988.35 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 27704375.74 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 97813426.80 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.330447E+09 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.400471E+09 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.101573E+09 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 13227008.46 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 51608422.12 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 93610033.39 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.140448E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 13227008.46 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.400471E+09 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT OFFICE
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.120720E+10 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.109052E+10 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.120916E+10 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.120218E+10 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.132053E+10 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.138437E+10 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.153119E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.166869E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.142444E+10 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.129026E+10 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.116889E+10 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.120720E+10 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.157046E+11 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.109052E+10 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.166869E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT GNE
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.109970E+09 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 84702649.02 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 57858375.22 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 27956803.99 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 21594944.43 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.101174E+09 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.292109E+09 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.399475E+09 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 93553980.40 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 11973204.81 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 50926814.35 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 92628291.31 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.134392E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 11973204.81 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.399475E+09 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT GN1
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 72204932.53 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 55300488.24 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 34340198.96 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 15051995.77 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 14521013.09 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 79746334.80 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.261277E+09 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.342611E+09 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 79601547.79 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 3388388.52 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 29475415.42 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 59447616.01 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.104697E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 3388388.52 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.342611E+09 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT GN2
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 72196308.40 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 55287396.75 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 34332810.80 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 14948254.19 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 14445253.12 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 80927604.43 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.258663E+09 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.343025E+09 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 79121460.87 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 3343799.71 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 29472596.96 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 59445370.39 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.104521E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 3343799.71 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.343025E+09 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT GS1
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 56401346.49 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 34965023.03 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 14508663.58 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 23451722.94 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 72485669.48 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.163819E+09 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.427107E+09 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.571540E+09 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.333055E+09 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 78991342.39 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 19478934.26 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 42968594.55 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.183877E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 14508663.58 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.571540E+09 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT GS2
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 63873660.58 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 39032289.94 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 15061465.79 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 25277703.31 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 82440854.78 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.189876E+09 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.470500E+09 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.628744E+09 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.368847E+09 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 87192956.36 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 21440197.66 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 47649259.10 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.203993E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 15061465.79 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.628744E+09 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT MSW
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.132030E+09 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 77156961.83 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 56992609.02 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.273998E+09 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.642773E+09 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.884473E+09 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.152961E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.169248E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.104478E+10 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.265710E+09 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 77757454.15 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.109691E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.678745E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 56992609.02 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.169248E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT MNW
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.167874E+09 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.114590E+09 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 46435597.80 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 88877423.90 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.360724E+09 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.654970E+09 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.118091E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.122519E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.465972E+09 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 22139622.98 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 82512618.92 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.146753E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.455696E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 22139622.98 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.122519E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT MSE
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.131079E+09 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 73891146.79 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 45227930.51 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.275174E+09 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.602107E+09 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.939096E+09 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.143324E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.168904E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.100024E+10 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.266906E+09 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 74911290.26 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.109031E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.663995E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 45227930.51 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.168904E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT MNE
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.166296E+09 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.113087E+09 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 43961511.72 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 78845553.41 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.315537E+09 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.707385E+09 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.108704E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.122559E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.433824E+09 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 18553326.82 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 81481729.55 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.145474E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.441708E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 18553326.82 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.122559E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT MN1
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 94344270.40 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 64115414.88 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 13676521.79 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 53286288.33 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.280331E+09 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.563086E+09 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.908696E+09 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.100378E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.398693E+09 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 16144229.13 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 37859673.97 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 79044761.24 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.351306E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 13676521.79 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.100378E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT MN2
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 94340771.83 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 64093108.36 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 13662253.99 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 53721462.99 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.279558E+09 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.566010E+09 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.904855E+09 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.100423E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.396495E+09 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 16199787.62 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 37864818.43 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 79058337.12 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.351009E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 13662253.99 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.100423E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT MS1
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 60097192.77 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 37577812.03 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 60826862.80 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.270244E+09 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.583703E+09 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.801817E+09 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.126285E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.147942E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.100970E+10 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.340711E+09 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 47841270.50 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 48143871.35 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.600293E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 37577812.03 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.147942E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT MS2
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 60139450.80 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 37442256.19 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 60580477.67 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.274307E+09 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.582422E+09 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.804468E+09 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.125903E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.147956E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.100721E+10 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.341229E+09 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 47953270.16 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 48199229.50 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.600254E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 37442256.19 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.147956E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT TSW
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.133152E+09 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 97477246.64 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.105549E+09 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.201236E+09 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.319029E+09 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.404672E+09 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.749332E+09 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.809058E+09 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.444770E+09 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.120600E+09 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 96831897.12 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.120596E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.360230E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 96831897.12 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.809058E+09 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT TNW
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.152256E+09 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.110555E+09 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 72653972.34 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 95814070.49 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.188507E+09 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.292801E+09 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.570513E+09 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.576948E+09 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.183355E+09 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 43778568.31 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 94521958.75 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.139122E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.252083E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 43778568.31 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.576948E+09 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT TSE
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.131501E+09 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 92797802.16 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 97438542.02 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.189409E+09 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.290019E+09 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.423339E+09 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.695841E+09 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.796697E+09 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.422249E+09 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.115779E+09 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 93428021.76 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.118555E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.346705E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 92797802.16 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.796697E+09 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT TNE
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.150035E+09 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.108704E+09 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 69411855.44 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 79141079.79 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.154769E+09 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.307416E+09 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.520242E+09 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.566339E+09 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.161077E+09 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 40536536.11 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 91815548.20 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.137157E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.238664E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 40536536.11 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.566339E+09 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT TN1
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.104883E+09 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 75733417.55 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 45368718.07 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 51738485.80 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.106545E+09 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.217998E+09 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.412423E+09 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.443585E+09 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.112883E+09 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 22174024.10 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 60321517.57 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 95403824.78 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.174906E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 22174024.10 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.443585E+09 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT TN2
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.104825E+09 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 75705152.19 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 45364670.63 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 51887718.76 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.106798E+09 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.220717E+09 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.411539E+09 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.444897E+09 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.113472E+09 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 22210080.80 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 60281886.89 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 95360770.47 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.175306E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 22210080.80 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.444897E+09 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT TS1
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 86895710.66 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 64842851.66 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 72781999.64 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.149877E+09 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.235896E+09 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.333420E+09 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.594170E+09 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.681242E+09 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.380240E+09 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.104274E+09 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 65115854.73 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 80176280.03 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.284893E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 64842851.66 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.681242E+09 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT TS2
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 86902449.35 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 64981160.79 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 73288441.94 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.151315E+09 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.236688E+09 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.336360E+09 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.593178E+09 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.682319E+09 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.380218E+09 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.105261E+09 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 65170555.21 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 80262307.03 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.285594E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 64981160.79 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.682319E+09 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT GSW
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 93814551.55 | 0.00 | 0.206796E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 63056303.39 | 0.00 | 0.138995E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 36833526.38 | 0.00 | 0.811924E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 22006269.43 | 69879514.27 | 0.363366E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 18799193.00 | 0.237133E+09 | 5905483.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 39497734.35 | 0.504005E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.112750E+09 | 0.146726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.141915E+09 | 0.185796E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 75515429.83 | 0.985892E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 16335344.79 | 0.164378E+09 | 70205233.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 38138854.03 | 4295030.60 | 0.833405E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 75354257.59 | 0.00 | 0.166104E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.734016E+09 | 0.529080E+10 | 0.720376E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 16335344.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.141915E+09 | 0.185796E+10 | 0.206796E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT GNW
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 0.111175E+09 | 0.00 | 0.249148E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 85861521.35 | 0.00 | 0.192418E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 59403444.00 | 0.00 | 0.133125E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 29577298.36 | 7561143.85 | 0.649418E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 8235891.86 | 75952890.74 | 51318181.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 22884966.13 | 0.292256E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 76629703.26 | 0.998129E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 92162366.44 | 0.120395E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 23685519.13 | 0.307762E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 12652509.71 | 2173522.56 | 0.279547E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 51608422.12 | 0.00 | 0.115656E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 93610033.39 | 0.00 | 0.209783E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.667487E+09 | 0.288779E+10 | 0.998158E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 8235891.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.111175E+09 | 0.120395E+10 | 0.249148E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT OFFICE
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 0.120720E+10 | 0.00 | 0.563950E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.109038E+10 | 549171.29 | 0.291928E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.120720E+10 | 7371459.68 | 30071550.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.116826E+10 | 0.131514E+09 | 6005064.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.120720E+10 | 0.444120E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.116826E+10 | 0.858888E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.120720E+10 | 0.130980E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.120720E+10 | 0.187310E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.116826E+10 | 0.104129E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.120720E+10 | 0.324380E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.116826E+10 | 2375242.27 | 88899762.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.120720E+10 | 0.00 | 0.351232E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.142138E+11 | 0.599338E+10 | 0.133209E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 0.109038E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.120720E+10 | 0.187310E+10 | 0.563950E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT GNE
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 0.109970E+09 | 0.00 | 0.249933E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 84702649.02 | 0.00 | 0.192507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 57858375.22 | 0.00 | 0.131497E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 26891592.57 | 3976557.35 | 0.603978E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 7225937.44 | 55994218.90 | 64550224.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 23673108.23 | 0.302252E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 67715422.21 | 0.881836E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 91997716.13 | 0.120621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 21802915.99 | 0.284029E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 11973204.81 | 0.00 | 0.272120E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 50926814.35 | 0.00 | 0.115744E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 92628291.31 | 0.00 | 0.210520E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.647366E+09 | 0.273430E+10 | 0.994266E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 7225937.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.109970E+09 | 0.120621E+10 | 0.249933E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT GN1
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 72204932.53 | 0.00 | 0.165911E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 55300488.24 | 0.00 | 0.127068E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 34340198.96 | 0.00 | 0.789062E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 14992784.15 | 220658.80 | 0.344096E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 3397040.48 | 43432503.66 | 208440.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 18652378.55 | 0.237707E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 60590378.10 | 0.786698E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 78930738.11 | 0.103043E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 18549176.43 | 0.240743E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 3352457.66 | 135154.54 | 76775606.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 29475415.42 | 0.00 | 0.677280E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 59447616.01 | 0.00 | 0.136597E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.449234E+09 | 0.233937E+10 | 0.618319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 3352457.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 78930738.11 | 0.103043E+10 | 0.165911E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT GN2
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 72196308.40 | 0.00 | 0.165949E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 55287396.75 | 0.00 | 0.127083E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 34332810.80 | 0.00 | 0.789168E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 14889543.75 | 218776.80 | 0.341847E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 3381744.42 | 43192833.43 | 275790.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 18928786.63 | 0.241267E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 59980616.31 | 0.778772E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 79025901.55 | 0.103182E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 18436708.42 | 0.239339E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 3333161.18 | 39992.01 | 76539482.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 29472596.96 | 0.00 | 0.677452E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 59445370.39 | 0.00 | 0.136640E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.448711E+09 | 0.233465E+10 | 0.618200E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 3333161.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 79025901.55 | 0.103182E+10 | 0.165949E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT GS1
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 56401346.49 | 0.00 | 0.126298E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 34965023.03 | 0.00 | 0.782964E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 14508663.58 | 0.00 | 0.324889E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 9230644.68 | 54497159.81 | 0.110229E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 16977952.42 | 0.217304E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 38358710.97 | 0.488920E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 99209759.68 | 0.128797E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.131944E+09 | 0.172700E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 77750349.27 | 0.101435E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 18612054.88 | 0.233480E+09 | 129719.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 18034133.67 | 5692363.14 | 0.394032E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 42968594.55 | 0.00 | 0.962186E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.558961E+09 | 0.502921E+10 | 0.383741E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 9230644.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.131944E+09 | 0.172700E+10 | 0.126298E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT GS2
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 63873660.58 | 0.00 | 0.142958E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 39032289.94 | 0.00 | 0.873595E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 15061465.79 | 0.00 | 0.337096E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 9501803.92 | 60561368.41 | 0.105637E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 19311956.81 | 0.247275E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 44463544.01 | 0.567087E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.109328E+09 | 0.142065E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.145249E+09 | 0.190341E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 86115019.41 | 0.112392E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 20537060.10 | 0.257942E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 19590322.27 | 7294199.41 | 0.425911E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 47649259.10 | 0.00 | 0.106645E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.619713E+09 | 0.558814E+10 | 0.423827E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 9501803.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.145249E+09 | 0.190341E+10 | 0.142958E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT MSW
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 0.132030E+09 | 0.00 | 0.286591E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 73293926.87 | 14787658.46 | 0.156506E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 25243482.82 | 0.121205E+09 | 0.333916E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 66554272.91 | 0.805810E+09 | 67016521.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.150931E+09 | 0.192927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.207391E+09 | 0.264948E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.355829E+09 | 0.463136E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.390803E+09 | 0.511713E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.244144E+09 | 0.318528E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 63459910.50 | 0.784401E+09 | 24031439.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 61412806.08 | 64682619.03 | 0.122532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.109691E+09 | 0.00 | 0.238100E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.188078E+10 | 0.193034E+11 | 0.846225E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 25243482.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.390803E+09 | 0.511713E+10 | 0.286591E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT MNW
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 0.167874E+09 | 0.00 | 0.368149E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.114590E+09 | 0.00 | 0.251298E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 46435597.80 | 0.00 | 0.101834E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 27288705.09 | 0.237921E+09 | 0.188289E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 84590853.29 | 0.108206E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.153509E+09 | 0.196011E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.274565E+09 | 0.356969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.282635E+09 | 0.368768E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.108763E+09 | 0.140931E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 12165726.05 | 38146561.78 | 0.199193E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 82512618.92 | 0.00 | 0.180951E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.146753E+09 | 0.00 | 0.321833E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.150168E+10 | 0.119849E+11 | 0.126281E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 12165726.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.282635E+09 | 0.368768E+10 | 0.368149E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT MSE
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 0.131079E+09 | 0.00 | 0.287519E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 71734188.29 | 8223309.59 | 0.155886E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 21234837.54 | 91457688.62 | 0.302262E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 66786254.24 | 0.810275E+09 | 65517180.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.141363E+09 | 0.180874E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.220200E+09 | 0.282075E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.333448E+09 | 0.434752E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.390316E+09 | 0.513460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.233709E+09 | 0.306073E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 63750285.92 | 0.789319E+09 | 24740103.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 60412225.35 | 57377965.58 | 0.122858E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.109031E+09 | 0.00 | 0.239158E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.184306E+10 | 0.189290E+11 | 0.844673E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 21234837.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.390316E+09 | 0.513460E+10 | 0.287519E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT MNE
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 0.166296E+09 | 0.00 | 0.369600E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.113087E+09 | 0.00 | 0.251342E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 43961511.72 | 0.00 | 0.977063E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 24125068.05 | 0.211473E+09 | 0.166848E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 73962896.08 | 0.946196E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.165802E+09 | 0.211998E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.252764E+09 | 0.328682E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.283010E+09 | 0.370600E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.101217E+09 | 0.131345E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 11130996.18 | 28223446.15 | 0.196421E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 81481729.55 | 0.00 | 0.181097E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.145474E+09 | 0.00 | 0.323321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.146231E+10 | 0.116121E+11 | 0.125939E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 11130996.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.283010E+09 | 0.370600E+10 | 0.369600E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT MN1
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 94344270.40 | 0.00 | 0.211761E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 64115414.88 | 0.00 | 0.143911E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 13676521.79 | 0.00 | 0.306978E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 13218052.25 | 0.154697E+09 | 23788607.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 65677731.26 | 0.837510E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.131929E+09 | 0.167977E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.211288E+09 | 0.273551E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.231806E+09 | 0.302005E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 92992964.54 | 0.120174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 4241620.46 | 45492790.30 | 13005162.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 37859673.97 | 0.00 | 0.849784E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 79044761.24 | 0.00 | 0.177421E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.104019E+10 | 0.967476E+10 | 0.652449E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 4241620.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.231806E+09 | 0.302005E+10 | 0.211761E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT MN2
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 94340771.83 | 0.00 | 0.211823E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 64093108.36 | 0.00 | 0.143908E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 13662253.99 | 0.00 | 0.306758E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 13312267.05 | 0.156018E+09 | 23582246.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 65497811.21 | 0.835180E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.132615E+09 | 0.168859E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.210391E+09 | 0.272390E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.231910E+09 | 0.302174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 92479218.77 | 0.119523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 4262984.02 | 45620543.57 | 13261750.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 37864818.43 | 0.00 | 0.850176E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 79058337.12 | 0.00 | 0.177509E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.103949E+10 | 0.966628E+10 | 0.652618E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 4262984.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.231910E+09 | 0.302174E+10 | 0.211823E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT MS1
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 60097192.77 | 0.00 | 0.132577E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 30496264.42 | 27081806.38 | 0.624552E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 14821372.46 | 0.175811E+09 | 11805882.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 63360819.59 | 0.801853E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.137020E+09 | 0.174559E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.187967E+09 | 0.239621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.293806E+09 | 0.381255E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.341902E+09 | 0.447339E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.235876E+09 | 0.307467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 80231833.68 | 0.101206E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 24187060.41 | 93758554.26 | 0.375080E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 47734077.98 | 1540837.55 | 0.105022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.151750E+10 | 0.176145E+11 | 0.338743E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 14821372.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.341902E+09 | 0.447339E+10 | 0.132577E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT MS2
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 60139450.80 | 0.00 | 0.132705E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 30455828.51 | 26717375.47 | 0.624469E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 14750988.02 | 0.175142E+09 | 11439295.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 64320842.23 | 0.813822E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.136720E+09 | 0.174191E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.188589E+09 | 0.240442E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.292913E+09 | 0.380125E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.341934E+09 | 0.447452E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.235294E+09 | 0.306758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 80353791.33 | 0.101369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 24217723.21 | 94095253.01 | 0.375309E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 47766492.84 | 1627329.03 | 0.105106E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.151746E+10 | 0.176148E+11 | 0.338932E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 14750988.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.341934E+09 | 0.447452E+10 | 0.132705E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT TSW
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 0.133152E+09 | 0.00 | 0.287629E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 90155606.64 | 28244668.29 | 0.189854E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 68203493.83 | 0.144054E+09 | 0.122258E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 68236420.50 | 0.519277E+09 | 0.592991E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 82483406.40 | 0.937059E+09 | 0.212742E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 95915091.57 | 0.121896E+10 | 28125506.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.174110E+09 | 0.228990E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.186231E+09 | 0.246265E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.105305E+09 | 0.136577E+10 | 37086954.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 49927410.40 | 0.274709E+09 | 0.607109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 83564399.37 | 53099725.60 | 0.171785E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.119740E+09 | 3216402.04 | 0.258081E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.125702E+10 | 0.929695E+10 | 0.117741E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 49927410.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.186231E+09 | 0.246265E+10 | 0.287629E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT TNW
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 0.152256E+09 | 0.00 | 0.331224E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.110555E+09 | 0.00 | 0.240507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 72345462.02 | 1160867.69 | 0.157175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 48808714.39 | 0.181819E+09 | 0.750437E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 52690499.60 | 0.535811E+09 | 0.240331E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 69659221.61 | 0.878424E+09 | 28923264.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.132455E+09 | 0.173657E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.132603E+09 | 0.174121E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 44747667.25 | 0.550248E+09 | 55008927.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 41002394.92 | 10622191.34 | 0.873220E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 93746465.91 | 3041360.10 | 0.203430E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.139122E+09 | 0.00 | 0.302652E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.108999E+10 | 0.563890E+10 | 0.142978E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 41002394.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.152256E+09 | 0.174121E+10 | 0.331224E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT TSE
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 0.131501E+09 | 0.00 | 0.288046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 87893893.81 | 18961766.77 | 0.189206E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 64807064.99 | 0.125851E+09 | 0.119728E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 63847522.60 | 0.491740E+09 | 0.554916E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 75479492.73 | 0.852374E+09 | 0.210729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.100371E+09 | 0.128085E+10 | 30579690.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.161706E+09 | 0.213659E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.183599E+09 | 0.244835E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.100083E+09 | 0.130439E+10 | 39392472.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 48301281.65 | 0.262879E+09 | 0.601618E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 81878354.06 | 46383826.66 | 0.171652E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.118158E+09 | 1492350.25 | 0.258549E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.121763E+10 | 0.896986E+10 | 0.117090E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 48301281.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.183599E+09 | 0.244835E+10 | 0.288046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT TNE
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 0.150035E+09 | 0.00 | 0.332007E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.108704E+09 | 0.00 | 0.240548E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 69411855.44 | 0.00 | 0.153599E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 42662574.52 | 0.141162E+09 | 0.698628E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 44576076.49 | 0.434947E+09 | 0.239450E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 73176220.84 | 0.923437E+09 | 31878050.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.120795E+09 | 0.158566E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.130351E+09 | 0.172148E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 39644222.21 | 0.482914E+09 | 59615922.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 39126145.21 | 5345861.99 | 0.856114E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 91815548.20 | 0.00 | 0.203176E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.137157E+09 | 0.00 | 0.303510E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.104746E+10 | 0.529495E+10 | 0.142141E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 39126145.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.150035E+09 | 0.172148E+10 | 0.332007E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT TN1
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 0.104883E+09 | 0.00 | 0.233134E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 75733417.55 | 0.00 | 0.168340E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 45368718.07 | 0.00 | 0.100846E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 26711896.99 | 96130464.58 | 0.424851E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 27956935.93 | 0.309241E+09 | 86995621.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 51257872.63 | 0.653714E+09 | 5010486.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 95709102.90 | 0.124883E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.102005E+09 | 0.133599E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 27098336.13 | 0.339453E+09 | 22430173.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 21591675.19 | 2199755.07 | 0.475918E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 60321517.57 | 0.00 | 0.134083E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 95403824.78 | 0.00 | 0.212064E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.734041E+09 | 0.398555E+10 | 0.949987E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 21591675.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.104883E+09 | 0.133599E+10 | 0.233134E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT TN2
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 0.104825E+09 | 0.00 | 0.233179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 75705152.19 | 0.00 | 0.168403E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 45364670.63 | 0.00 | 0.100912E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 26667208.38 | 96899828.24 | 0.422856E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 28044043.56 | 0.309935E+09 | 87852485.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 51909608.52 | 0.661934E+09 | 5387204.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 95503567.16 | 0.124629E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.102312E+09 | 0.134045E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 27248494.88 | 0.341280E+09 | 22828352.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 21617262.87 | 2239139.34 | 0.476770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 60281886.89 | 0.00 | 0.134095E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 95360770.47 | 0.00 | 0.212126E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.734840E+09 | 0.399902E+10 | 0.950284E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 21617262.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.104825E+09 | 0.134045E+10 | 0.233179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT TS1
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 86784515.00 | 418191.36 | 0.190552E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 57381042.08 | 28659083.40 | 0.120961E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 41165255.07 | 0.121803E+09 | 0.688317E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 45316795.67 | 0.407686E+09 | 0.291461E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 57819217.83 | 0.703934E+09 | 69810133.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 78343046.50 | 0.100532E+10 | 4376054.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.138040E+09 | 0.181201E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.156916E+09 | 0.207511E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 89428133.99 | 0.117135E+10 | 16023939.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 34352143.90 | 0.271984E+09 | 0.280572E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 51823836.34 | 53131999.15 | 0.104943E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 78001909.26 | 8207628.71 | 0.169848E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.915372E+09 | 0.765961E+10 | 0.721360E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 34352143.90 | 418191.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.156916E+09 | 0.207511E+10 | 0.190552E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT TS2
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 86774589.85 | 480979.62 | 0.190630E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 57421733.80 | 29031751.19 | 0.121053E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 41280820.54 | 0.123345E+09 | 0.688568E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 45612199.18 | 0.412243E+09 | 0.290345E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 58030998.12 | 0.706436E+09 | 70564461.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 79045490.30 | 0.101450E+10 | 4715506.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.137810E+09 | 0.180955E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.157171E+09 | 0.207943E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 89435830.55 | 0.117174E+10 | 16398192.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 34598130.61 | 0.274944E+09 | 0.281115E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 51826989.79 | 53343415.04 | 0.104975E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 78021717.86 | 8459861.56 | 0.169945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.917029E+09 | 0.768349E+10 | 0.721773E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 34598130.61 | 480979.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.157171E+09 | 0.207943E+10 | 0.190630E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT GSW
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 93814551.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 63056303.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 36833526.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 22006269.43 | 0.00 | 0.00 | 0.00 | 18229713.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 18799193.00 | 0.00 | 0.00 | 0.00 | 60538804.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 39497734.35 | 0.00 | 0.00 | 0.00 | 0.129155E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.112750E+09 | 0.00 | 0.00 | 0.00 | 0.372785E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.141915E+09 | 0.00 | 0.00 | 0.00 | 0.473457E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 75515429.83 | 0.00 | 0.00 | 0.00 | 0.247882E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 16335344.79 | 0.00 | 0.00 | 0.00 | 42617033.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 38138854.03 | 0.00 | 0.00 | 0.00 | 1092120.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 75354257.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.734016E+09 | 0.00 | 0.00 | 0.00 | 0.134576E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 16335344.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.141915E+09 | 0.00 | 0.00 | 0.00 | 0.473457E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT GNW
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 0.111175E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 85861521.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 59403444.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 29577298.36 | 0.00 | 0.00 | 0.00 | 2005689.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 8235891.86 | 0.00 | 0.00 | 0.00 | 19468483.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 22884966.13 | 0.00 | 0.00 | 0.00 | 74928460.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 76629703.26 | 0.00 | 0.00 | 0.00 | 0.253817E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 92162366.44 | 0.00 | 0.00 | 0.00 | 0.308309E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 23685519.13 | 0.00 | 0.00 | 0.00 | 77887049.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 12652509.71 | 0.00 | 0.00 | 0.00 | 574498.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 51608422.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 93610033.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.667487E+09 | 0.00 | 0.00 | 0.00 | 0.736990E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 8235891.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.111175E+09 | 0.00 | 0.00 | 0.00 | 0.308309E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT OFFICE
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 0.120720E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.109038E+10 | 0.00 | 0.00 | 0.00 | 145281.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.120720E+10 | 0.00 | 0.00 | 0.00 | 1959237.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.116826E+10 | 0.00 | 0.00 | 0.00 | 33915788.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.120720E+10 | 0.00 | 0.00 | 0.00 | 0.113323E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.116826E+10 | 0.00 | 0.00 | 0.00 | 0.216107E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.120720E+10 | 0.00 | 0.00 | 0.00 | 0.323988E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.120720E+10 | 0.00 | 0.00 | 0.00 | 0.461486E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.116826E+10 | 0.00 | 0.00 | 0.00 | 0.256178E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.120720E+10 | 0.00 | 0.00 | 0.00 | 83058714.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.116826E+10 | 0.00 | 0.00 | 0.00 | 626370.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.120720E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.142138E+11 | 0.00 | 0.00 | 0.00 | 0.149079E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 0.109038E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.120720E+10 | 0.00 | 0.00 | 0.00 | 0.461486E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT GNE
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 0.109970E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 84702649.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 57858375.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 26891592.57 | 0.00 | 0.00 | 0.00 | 1065211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 7225937.44 | 0.00 | 0.00 | 0.00 | 14369006.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 23673108.23 | 0.00 | 0.00 | 0.00 | 77500968.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 67715422.21 | 0.00 | 0.00 | 0.00 | 0.224393E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 91997716.13 | 0.00 | 0.00 | 0.00 | 0.307477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 21802915.99 | 0.00 | 0.00 | 0.00 | 71751064.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 11973204.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 50926814.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 92628291.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.647366E+09 | 0.00 | 0.00 | 0.00 | 0.696556E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 7225937.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.109970E+09 | 0.00 | 0.00 | 0.00 | 0.307477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT GN1
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 72204932.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 55300488.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 34340198.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 14992784.15 | 0.00 | 0.00 | 0.00 | 59211.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 3397040.48 | 0.00 | 0.00 | 0.00 | 11123972.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 18652378.55 | 0.00 | 0.00 | 0.00 | 61093956.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 60590378.10 | 0.00 | 0.00 | 0.00 | 0.200687E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 78930738.11 | 0.00 | 0.00 | 0.00 | 0.263680E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 18549176.43 | 0.00 | 0.00 | 0.00 | 61052371.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 3352457.66 | 0.00 | 0.00 | 0.00 | 35930.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 29475415.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 59447616.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.449234E+09 | 0.00 | 0.00 | 0.00 | 0.597732E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 3352457.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 78930738.11 | 0.00 | 0.00 | 0.00 | 0.263680E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT GN2
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 72196308.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 55287396.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 34332810.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 14889543.75 | 0.00 | 0.00 | 0.00 | 58710.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 3381744.42 | 0.00 | 0.00 | 0.00 | 11063508.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 18928786.63 | 0.00 | 0.00 | 0.00 | 61998817.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 59980616.31 | 0.00 | 0.00 | 0.00 | 0.198682E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 79025901.55 | 0.00 | 0.00 | 0.00 | 0.263999E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 18436708.42 | 0.00 | 0.00 | 0.00 | 60684752.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 3333161.18 | 0.00 | 0.00 | 0.00 | 10638.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 29472596.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 59445370.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.448711E+09 | 0.00 | 0.00 | 0.00 | 0.596498E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 3333161.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 79025901.55 | 0.00 | 0.00 | 0.00 | 0.263999E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT GS1
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 56401346.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 34965023.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 14508663.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 9230644.68 | 0.00 | 0.00 | 0.00 | 14221078.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 16977952.42 | 0.00 | 0.00 | 0.00 | 55507717.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 38358710.97 | 0.00 | 0.00 | 0.00 | 0.125460E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 99209759.68 | 0.00 | 0.00 | 0.00 | 0.327898E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.131944E+09 | 0.00 | 0.00 | 0.00 | 0.439596E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 77750349.27 | 0.00 | 0.00 | 0.00 | 0.255304E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 18612054.88 | 0.00 | 0.00 | 0.00 | 60379287.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 18034133.67 | 0.00 | 0.00 | 0.00 | 1444800.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 42968594.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.558961E+09 | 0.00 | 0.00 | 0.00 | 0.127981E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 9230644.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.131944E+09 | 0.00 | 0.00 | 0.00 | 0.439596E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT GS2
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 63873660.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 39032289.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 15061465.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 9501803.92 | 0.00 | 0.00 | 0.00 | 15775899.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 19311956.81 | 0.00 | 0.00 | 0.00 | 63128897.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 44463544.01 | 0.00 | 0.00 | 0.00 | 0.145412E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.109328E+09 | 0.00 | 0.00 | 0.00 | 0.361172E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.145249E+09 | 0.00 | 0.00 | 0.00 | 0.483495E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 86115019.41 | 0.00 | 0.00 | 0.00 | 0.282732E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 20537060.10 | 0.00 | 0.00 | 0.00 | 66655896.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 19590322.27 | 0.00 | 0.00 | 0.00 | 1849875.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 47649259.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.619713E+09 | 0.00 | 0.00 | 0.00 | 0.142022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 9501803.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.145249E+09 | 0.00 | 0.00 | 0.00 | 0.483495E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT MSW
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 0.132030E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 73293926.87 | 0.00 | 0.00 | 0.00 | 3863034.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 25243482.82 | 0.00 | 0.00 | 0.00 | 31749126.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 66554272.91 | 0.00 | 0.00 | 0.00 | 0.207444E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.150931E+09 | 0.00 | 0.00 | 0.00 | 0.491843E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.207391E+09 | 0.00 | 0.00 | 0.00 | 0.677082E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.355829E+09 | 0.00 | 0.00 | 0.00 | 0.117378E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.390803E+09 | 0.00 | 0.00 | 0.00 | 0.130167E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.244144E+09 | 0.00 | 0.00 | 0.00 | 0.800635E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 63459910.50 | 0.00 | 0.00 | 0.00 | 0.202250E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 61412806.08 | 0.00 | 0.00 | 0.00 | 16344648.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.109691E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.188078E+10 | 0.00 | 0.00 | 0.00 | 0.490667E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 25243482.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.390803E+09 | 0.00 | 0.00 | 0.00 | 0.130167E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT MNW
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 0.167874E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.114590E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 46435597.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 27288705.09 | 0.00 | 0.00 | 0.00 | 61588718.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 84590853.29 | 0.00 | 0.00 | 0.00 | 0.276133E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.153509E+09 | 0.00 | 0.00 | 0.00 | 0.501461E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.274565E+09 | 0.00 | 0.00 | 0.00 | 0.906349E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.282635E+09 | 0.00 | 0.00 | 0.00 | 0.942558E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.108763E+09 | 0.00 | 0.00 | 0.00 | 0.357208E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 12165726.05 | 0.00 | 0.00 | 0.00 | 9973896.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 82512618.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.146753E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.150168E+10 | 0.00 | 0.00 | 0.00 | 0.305527E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 12165726.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.282635E+09 | 0.00 | 0.00 | 0.00 | 0.942558E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT MSE
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 0.131079E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 71734188.29 | 0.00 | 0.00 | 0.00 | 2156958.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 21234837.54 | 0.00 | 0.00 | 0.00 | 23993092.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 66786254.24 | 0.00 | 0.00 | 0.00 | 0.208388E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.141363E+09 | 0.00 | 0.00 | 0.00 | 0.460744E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.220200E+09 | 0.00 | 0.00 | 0.00 | 0.718896E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.333448E+09 | 0.00 | 0.00 | 0.00 | 0.109980E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.390316E+09 | 0.00 | 0.00 | 0.00 | 0.129872E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.233709E+09 | 0.00 | 0.00 | 0.00 | 0.766529E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 63750285.92 | 0.00 | 0.00 | 0.00 | 0.203155E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 60412225.35 | 0.00 | 0.00 | 0.00 | 14499064.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.109031E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.184306E+10 | 0.00 | 0.00 | 0.00 | 0.479688E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 21234837.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.390316E+09 | 0.00 | 0.00 | 0.00 | 0.129872E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT MNE
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 0.166296E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.113087E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 43961511.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 24125068.05 | 0.00 | 0.00 | 0.00 | 54720485.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 73962896.08 | 0.00 | 0.00 | 0.00 | 0.241574E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.165802E+09 | 0.00 | 0.00 | 0.00 | 0.541583E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.252764E+09 | 0.00 | 0.00 | 0.00 | 0.834278E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.283010E+09 | 0.00 | 0.00 | 0.00 | 0.942584E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.101217E+09 | 0.00 | 0.00 | 0.00 | 0.332607E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 11130996.18 | 0.00 | 0.00 | 0.00 | 7422330.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 81481729.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.145474E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.146231E+10 | 0.00 | 0.00 | 0.00 | 0.295477E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 11130996.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.283010E+09 | 0.00 | 0.00 | 0.00 | 0.942584E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT MN1
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 94344270.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 64115414.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 13676521.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 13218052.25 | 0.00 | 0.00 | 0.00 | 40068236.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 65677731.26 | 0.00 | 0.00 | 0.00 | 0.214653E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.131929E+09 | 0.00 | 0.00 | 0.00 | 0.431157E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.211288E+09 | 0.00 | 0.00 | 0.00 | 0.697408E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.231806E+09 | 0.00 | 0.00 | 0.00 | 0.771977E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 92992964.54 | 0.00 | 0.00 | 0.00 | 0.305700E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 4241620.46 | 0.00 | 0.00 | 0.00 | 11902608.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 37859673.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 79044761.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.104019E+10 | 0.00 | 0.00 | 0.00 | 0.247287E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 4241620.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.231806E+09 | 0.00 | 0.00 | 0.00 | 0.771977E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT MN2
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 94340771.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 64093108.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 13662253.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 13312267.05 | 0.00 | 0.00 | 0.00 | 40409195.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 65497811.21 | 0.00 | 0.00 | 0.00 | 0.214060E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.132615E+09 | 0.00 | 0.00 | 0.00 | 0.433395E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.210391E+09 | 0.00 | 0.00 | 0.00 | 0.694464E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.231910E+09 | 0.00 | 0.00 | 0.00 | 0.772323E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 92479218.77 | 0.00 | 0.00 | 0.00 | 0.304016E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 4262984.02 | 0.00 | 0.00 | 0.00 | 11936803.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 37864818.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 79058337.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.103949E+10 | 0.00 | 0.00 | 0.00 | 0.247060E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 4262984.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.231910E+09 | 0.00 | 0.00 | 0.00 | 0.772323E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT MS1
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 60097192.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 30496264.42 | 0.00 | 0.00 | 0.00 | 7081547.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 14821372.46 | 0.00 | 0.00 | 0.00 | 46005490.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 63360819.59 | 0.00 | 0.00 | 0.00 | 0.206883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.137020E+09 | 0.00 | 0.00 | 0.00 | 0.446683E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.187967E+09 | 0.00 | 0.00 | 0.00 | 0.613850E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.293806E+09 | 0.00 | 0.00 | 0.00 | 0.969048E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.341902E+09 | 0.00 | 0.00 | 0.00 | 0.113752E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.235876E+09 | 0.00 | 0.00 | 0.00 | 0.773821E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 80231833.68 | 0.00 | 0.00 | 0.00 | 0.260479E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 24187060.41 | 0.00 | 0.00 | 0.00 | 23654210.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 47734077.98 | 0.00 | 0.00 | 0.00 | 409793.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.151750E+10 | 0.00 | 0.00 | 0.00 | 0.448543E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 14821372.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.341902E+09 | 0.00 | 0.00 | 0.00 | 0.113752E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT MS2
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 60139450.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 30455828.51 | 0.00 | 0.00 | 0.00 | 6986427.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 14750988.02 | 0.00 | 0.00 | 0.00 | 45829489.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 64320842.23 | 0.00 | 0.00 | 0.00 | 0.209986E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.136720E+09 | 0.00 | 0.00 | 0.00 | 0.445701E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.188589E+09 | 0.00 | 0.00 | 0.00 | 0.615878E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.292913E+09 | 0.00 | 0.00 | 0.00 | 0.966118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.341934E+09 | 0.00 | 0.00 | 0.00 | 0.113762E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.235294E+09 | 0.00 | 0.00 | 0.00 | 0.771917E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 80353791.33 | 0.00 | 0.00 | 0.00 | 0.260875E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 24217723.21 | 0.00 | 0.00 | 0.00 | 23735546.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 47766492.84 | 0.00 | 0.00 | 0.00 | 432736.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.151746E+10 | 0.00 | 0.00 | 0.00 | 0.448508E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 14750988.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.341934E+09 | 0.00 | 0.00 | 0.00 | 0.113762E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT TSW
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 0.133152E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 90155606.64 | 0.00 | 0.00 | 0.00 | 7321639.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 68203493.83 | 0.00 | 0.00 | 0.00 | 37345673.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 68236420.50 | 0.00 | 0.00 | 0.00 | 0.133000E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 82483406.40 | 0.00 | 0.00 | 0.00 | 0.236546E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 95915091.57 | 0.00 | 0.00 | 0.00 | 0.308756E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.174110E+09 | 0.00 | 0.00 | 0.00 | 0.575222E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.186231E+09 | 0.00 | 0.00 | 0.00 | 0.622828E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.105305E+09 | 0.00 | 0.00 | 0.00 | 0.339465E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 49927410.40 | 0.00 | 0.00 | 0.00 | 70672827.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 83564399.37 | 0.00 | 0.00 | 0.00 | 13267497.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.119740E+09 | 0.00 | 0.00 | 0.00 | 855381.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.125702E+10 | 0.00 | 0.00 | 0.00 | 0.234528E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 49927410.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.186231E+09 | 0.00 | 0.00 | 0.00 | 0.622828E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT TNW
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 0.152256E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.110555E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 72345462.02 | 0.00 | 0.00 | 0.00 | 308510.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 48808714.39 | 0.00 | 0.00 | 0.00 | 47005356.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 52690499.60 | 0.00 | 0.00 | 0.00 | 0.135817E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 69659221.61 | 0.00 | 0.00 | 0.00 | 0.223142E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.132455E+09 | 0.00 | 0.00 | 0.00 | 0.438058E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.132603E+09 | 0.00 | 0.00 | 0.00 | 0.444345E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 44747667.25 | 0.00 | 0.00 | 0.00 | 0.138608E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 41002394.92 | 0.00 | 0.00 | 0.00 | 2776173.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 93746465.91 | 0.00 | 0.00 | 0.00 | 775492.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.139122E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.108999E+10 | 0.00 | 0.00 | 0.00 | 0.143084E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 41002394.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.152256E+09 | 0.00 | 0.00 | 0.00 | 0.444345E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT TSE
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 0.131501E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 87893893.81 | 0.00 | 0.00 | 0.00 | 4903908.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 64807064.99 | 0.00 | 0.00 | 0.00 | 32631477.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 63847522.60 | 0.00 | 0.00 | 0.00 | 0.125561E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 75479492.73 | 0.00 | 0.00 | 0.00 | 0.214539E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.100371E+09 | 0.00 | 0.00 | 0.00 | 0.322968E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.161706E+09 | 0.00 | 0.00 | 0.00 | 0.534135E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.183599E+09 | 0.00 | 0.00 | 0.00 | 0.613098E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.100083E+09 | 0.00 | 0.00 | 0.00 | 0.322166E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 48301281.65 | 0.00 | 0.00 | 0.00 | 67477837.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 81878354.06 | 0.00 | 0.00 | 0.00 | 11549667.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.118158E+09 | 0.00 | 0.00 | 0.00 | 397214.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.121763E+10 | 0.00 | 0.00 | 0.00 | 0.224943E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 48301281.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.183599E+09 | 0.00 | 0.00 | 0.00 | 0.613098E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT TNE
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 0.150035E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.108704E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 69411855.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 42662574.52 | 0.00 | 0.00 | 0.00 | 36478505.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 44576076.49 | 0.00 | 0.00 | 0.00 | 0.110193E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 73176220.84 | 0.00 | 0.00 | 0.00 | 0.234240E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.120795E+09 | 0.00 | 0.00 | 0.00 | 0.399447E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.130351E+09 | 0.00 | 0.00 | 0.00 | 0.435988E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 39644222.21 | 0.00 | 0.00 | 0.00 | 0.121433E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 39126145.21 | 0.00 | 0.00 | 0.00 | 1410390.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 91815548.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.137157E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.104746E+10 | 0.00 | 0.00 | 0.00 | 0.133919E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 39126145.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.150035E+09 | 0.00 | 0.00 | 0.00 | 0.435988E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT TN1
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 0.104883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 75733417.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 45368718.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 26711896.99 | 0.00 | 0.00 | 0.00 | 25026588.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 27956935.93 | 0.00 | 0.00 | 0.00 | 78588240.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 51257872.63 | 0.00 | 0.00 | 0.00 | 0.166740E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 95709102.90 | 0.00 | 0.00 | 0.00 | 0.316714E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.102005E+09 | 0.00 | 0.00 | 0.00 | 0.341580E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 27098336.13 | 0.00 | 0.00 | 0.00 | 85784903.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 21591675.19 | 0.00 | 0.00 | 0.00 | 582348.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 60321517.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 95403824.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.734041E+09 | 0.00 | 0.00 | 0.00 | 0.101502E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 21591675.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.104883E+09 | 0.00 | 0.00 | 0.00 | 0.341580E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT TN2
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 0.104825E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 75705152.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 45364670.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 26667208.38 | 0.00 | 0.00 | 0.00 | 25220510.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 28044043.56 | 0.00 | 0.00 | 0.00 | 78753676.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 51909608.52 | 0.00 | 0.00 | 0.00 | 0.168808E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 95503567.16 | 0.00 | 0.00 | 0.00 | 0.316035E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.102312E+09 | 0.00 | 0.00 | 0.00 | 0.342585E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 27248494.88 | 0.00 | 0.00 | 0.00 | 86223321.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 21617262.87 | 0.00 | 0.00 | 0.00 | 592817.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 60281886.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 95360770.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.734840E+09 | 0.00 | 0.00 | 0.00 | 0.101822E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 21617262.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.104825E+09 | 0.00 | 0.00 | 0.00 | 0.342585E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT TS1
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 86784515.00 | 0.00 | 0.00 | 0.00 | 111195.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 57381042.08 | 0.00 | 0.00 | 0.00 | 7461809.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 41165255.07 | 0.00 | 0.00 | 0.00 | 31616744.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 45316795.67 | 0.00 | 0.00 | 0.00 | 0.104560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 57819217.83 | 0.00 | 0.00 | 0.00 | 0.178077E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 78343046.50 | 0.00 | 0.00 | 0.00 | 0.255077E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.138040E+09 | 0.00 | 0.00 | 0.00 | 0.456130E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.156916E+09 | 0.00 | 0.00 | 0.00 | 0.524325E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 89428133.99 | 0.00 | 0.00 | 0.00 | 0.290812E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 34352143.90 | 0.00 | 0.00 | 0.00 | 69921552.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 51823836.34 | 0.00 | 0.00 | 0.00 | 13292018.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 78001909.26 | 0.00 | 0.00 | 0.00 | 2174370.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.915372E+09 | 0.00 | 0.00 | 0.00 | 0.193356E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 34352143.90 | 0.00 | 0.00 | 0.00 | 111195.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.156916E+09 | 0.00 | 0.00 | 0.00 | 0.524325E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT TS2
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 86774589.85 | 0.00 | 0.00 | 0.00 | 127859.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 57421733.80 | 0.00 | 0.00 | 0.00 | 7559426.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 41280820.54 | 0.00 | 0.00 | 0.00 | 32007621.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 45612199.18 | 0.00 | 0.00 | 0.00 | 0.105703E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 58030998.12 | 0.00 | 0.00 | 0.00 | 0.178657E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 79045490.30 | 0.00 | 0.00 | 0.00 | 0.257314E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.137810E+09 | 0.00 | 0.00 | 0.00 | 0.455368E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.157171E+09 | 0.00 | 0.00 | 0.00 | 0.525148E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 89435830.55 | 0.00 | 0.00 | 0.00 | 0.290782E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 34598130.61 | 0.00 | 0.00 | 0.00 | 70662485.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 51826989.79 | 0.00 | 0.00 | 0.00 | 13343565.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 78021717.86 | 0.00 | 0.00 | 0.00 | 2240589.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.917029E+09 | 0.00 | 0.00 | 0.00 | 0.193891E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 34598130.61 | 0.00 | 0.00 | 0.00 | 127859.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.157171E+09 | 0.00 | 0.00 | 0.00 | 0.525148E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: G SW APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 92472269.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130240E+10 | 0.00 | 0.00 | 0.35 |
| February | 0.292099E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.873404E+09 | 0.00 | 0.00 | 0.35 |
| March | 0.594497E+09 | 0.00 | 0.00 | 16.74 | 0.00 | 0.496036E+09 | 90891.07 | 0.00 | 0.35 |
| April | 0.707487E+09 | 3522845.50 | 0.00 | 87149.32 | 291060.31 | 0.173529E+09 | 22339661.94 | 0.00 | 0.35 |
| May | 0.754435E+09 | 2311337.99 | 0.00 | 477633.42 | 0.00 | 0.00 | 82946583.27 | 0.00 | 0.35 |
| June | 0.436250E+09 | 3365349.42 | 0.00 | 1054955.89 | 0.00 | 0.00 | 0.230656E+09 | 0.00 | 0.35 |
| July | 0.125582E+09 | 39049398.06 | 0.00 | 2145183.87 | 0.00 | 0.00 | 0.411494E+09 | 0.00 | 0.36 |
| August | 0.111400E+09 | 79553648.54 | 0.00 | 1948019.68 | 0.00 | 0.00 | 0.331469E+09 | 0.00 | 0.36 |
| September | 0.280968E+09 | 9295467.85 | 0.00 | 2040599.59 | 0.00 | 0.00 | 0.429151E+09 | 0.00 | 0.36 |
| October | 0.790044E+09 | 0.00 | 0.00 | 582789.38 | 0.00 | 11160858.71 | 0.148279E+09 | 0.00 | 0.35 |
| November | 0.589590E+09 | 0.00 | 0.00 | 9354.76 | 0.00 | 0.491659E+09 | 1565433.74 | 0.00 | 0.35 |
| December | 0.266716E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105629E+10 | 0.00 | 0.00 | 0.35 |
| Annual Sum or Average | 0.504154E+10 | 0.137098E+09 | 0.00 | 8345702.65 | 291060.31 | 0.440448E+10 | 0.165799E+10 | 0.00 | 0.35 |
| Minimum of Months | 92472269.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
| Maximum of Months | 0.790044E+09 | 79553648.54 | 0.00 | 2145183.87 | 291060.31 | 0.130240E+10 | 0.429151E+09 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: G NW APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 919394.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139361E+10 | 0.00 | 0.00 | 0.35 |
| February | 59396756.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110183E+10 | 0.00 | 0.00 | 0.35 |
| March | 0.199746E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.876319E+09 | 0.00 | 0.00 | 0.35 |
| April | 0.445012E+09 | 1277699.71 | 0.00 | 4089.01 | 3282153.65 | 0.421717E+09 | 1218580.50 | 0.00 | 0.35 |
| May | 0.772062E+09 | 1445521.54 | 0.00 | 139356.31 | 0.00 | 0.00 | 21590456.62 | 0.00 | 0.35 |
| June | 0.513023E+09 | 2891417.56 | 0.00 | 593344.81 | 1307.67 | 0.00 | 0.136268E+09 | 0.00 | 0.35 |
| July | 0.181841E+09 | 34407768.74 | 0.00 | 1478756.00 | 0.00 | 0.00 | 0.360294E+09 | 0.00 | 0.36 |
| August | 0.166649E+09 | 68558690.78 | 0.00 | 1328206.20 | 0.00 | 0.00 | 0.288809E+09 | 0.00 | 0.36 |
| September | 0.518064E+09 | 3470900.70 | 0.00 | 649753.10 | 0.00 | 0.00 | 0.188408E+09 | 0.00 | 0.35 |
| October | 0.777557E+09 | 0.00 | 0.00 | 8238.64 | 0.00 | 96375437.55 | 1308472.18 | 0.00 | 0.35 |
| November | 0.302077E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.767032E+09 | 0.00 | 0.00 | 0.35 |
| December | 11368939.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130876E+10 | 0.00 | 0.00 | 0.35 |
| Annual Sum or Average | 0.394772E+10 | 0.112052E+09 | 0.00 | 4201744.07 | 3283461.32 | 0.596564E+10 | 0.997897E+09 | 0.00 | 0.35 |
| Minimum of Months | 919394.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
| Maximum of Months | 0.777557E+09 | 68558690.78 | 0.00 | 1478756.00 | 3282153.65 | 0.139361E+10 | 0.360294E+09 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: OFFICE
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.132179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.445186E+09 | 0.00 | 0.00 | 0.51 |
| February | 0.134131E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.211170E+09 | 0.00 | 0.00 | 0.51 |
| March | 0.154560E+10 | 0.00 | 0.00 | 14809.20 | 0.00 | 28818733.57 | 18992392.34 | 0.00 | 0.51 |
| April | 0.131373E+10 | 2054070.44 | 0.00 | 136823.89 | 704232.40 | 4260526.45 | 84437970.49 | 0.00 | 0.52 |
| May | 0.111611E+10 | 1158910.16 | 0.00 | 647470.21 | 133202.35 | 0.00 | 0.251569E+09 | 0.00 | 0.52 |
| June | 0.894211E+09 | 363069.02 | 0.00 | 1255538.58 | 91579.99 | 0.00 | 0.229543E+09 | 0.00 | 0.52 |
| July | 0.857461E+09 | 23847170.24 | 0.00 | 1430343.06 | 1970880.24 | 0.00 | 0.119776E+09 | 0.00 | 0.52 |
| August | 0.761056E+09 | 65551022.53 | 0.00 | 1524420.04 | 6117600.76 | 0.00 | 99777209.86 | 0.00 | 0.53 |
| September | 0.100400E+10 | 8730638.18 | 0.00 | 1249580.90 | 396444.66 | 0.00 | 0.189638E+09 | 0.00 | 0.52 |
| October | 0.132653E+10 | 0.00 | 0.00 | 558313.91 | 0.00 | 0.00 | 0.190511E+09 | 0.00 | 0.52 |
| November | 0.144662E+10 | 0.00 | 0.00 | 6244.02 | 0.00 | 0.100227E+09 | 16417568.46 | 0.00 | 0.51 |
| December | 0.146019E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.281668E+09 | 0.00 | 0.00 | 0.51 |
| Annual Sum or Average | 0.143886E+11 | 0.101705E+09 | 0.00 | 6823543.81 | 9413940.41 | 0.107133E+10 | 0.120066E+10 | 0.00 | 0.52 |
| Minimum of Months | 0.761056E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.51 |
| Maximum of Months | 0.154560E+10 | 65551022.53 | 0.00 | 1524420.04 | 6117600.76 | 0.445186E+09 | 0.251569E+09 | 0.00 | 0.53 |
Report: MechanicalVentilationLoadsMonthly
For: G NE APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 856705.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139368E+10 | 0.00 | 0.00 | 0.35 |
| February | 59568293.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110139E+10 | 0.00 | 0.00 | 0.35 |
| March | 0.219636E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.855658E+09 | 0.00 | 0.00 | 0.35 |
| April | 0.488367E+09 | 1147768.57 | 0.00 | 519.79 | 3199519.79 | 0.379079E+09 | 207231.41 | 0.00 | 0.35 |
| May | 0.776119E+09 | 1467672.88 | 0.00 | 86774.24 | 0.00 | 0.00 | 14499097.32 | 0.00 | 0.35 |
| June | 0.505394E+09 | 2896722.96 | 0.00 | 652622.54 | 0.00 | 0.00 | 0.150499E+09 | 0.00 | 0.35 |
| July | 0.230719E+09 | 33787453.61 | 0.00 | 1325971.54 | 0.00 | 0.00 | 0.313172E+09 | 0.00 | 0.35 |
| August | 0.153329E+09 | 71294734.52 | 0.00 | 1386986.07 | 0.00 | 0.00 | 0.302839E+09 | 0.00 | 0.36 |
| September | 0.523767E+09 | 3548152.92 | 0.00 | 593932.43 | 0.00 | 0.00 | 0.177668E+09 | 0.00 | 0.35 |
| October | 0.776749E+09 | 0.00 | 0.00 | 101.52 | 0.00 | 96205285.79 | 148192.56 | 0.00 | 0.35 |
| November | 0.279001E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.789954E+09 | 0.00 | 0.00 | 0.35 |
| December | 407462.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131974E+10 | 0.00 | 0.00 | 0.35 |
| Annual Sum or Average | 0.401391E+10 | 0.114143E+09 | 0.00 | 4046908.13 | 3199519.79 | 0.593571E+10 | 0.959032E+09 | 0.00 | 0.35 |
| Minimum of Months | 407462.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
| Maximum of Months | 0.776749E+09 | 71294734.52 | 0.00 | 1386986.07 | 3199519.79 | 0.139368E+10 | 0.313172E+09 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: G N1 APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.129752E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127053E+10 | 0.00 | 0.00 | 0.35 |
| February | 0.248441E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.918432E+09 | 0.00 | 0.00 | 0.35 |
| March | 0.690405E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.391857E+09 | 0.00 | 0.00 | 0.35 |
| April | 0.793253E+09 | 0.00 | 0.00 | 0.00 | 4851020.46 | 83654559.64 | 0.00 | 0.00 | 0.35 |
| May | 0.801403E+09 | 1363789.20 | 0.00 | 81178.96 | 0.00 | 0.00 | 22759032.72 | 0.00 | 0.35 |
| June | 0.461519E+09 | 2764827.51 | 0.00 | 644060.12 | 0.00 | 0.00 | 0.213912E+09 | 0.00 | 0.35 |
| July | 99687919.56 | 31591940.26 | 0.00 | 1589501.36 | 0.00 | 0.00 | 0.454252E+09 | 0.00 | 0.36 |
| August | 75927880.00 | 65605879.10 | 0.00 | 1507020.25 | 0.00 | 0.00 | 0.386710E+09 | 0.00 | 0.36 |
| September | 0.427460E+09 | 2595530.13 | 0.00 | 747232.89 | 0.00 | 0.00 | 0.302891E+09 | 0.00 | 0.36 |
| October | 0.903435E+09 | 0.00 | 0.00 | 1827.34 | 0.00 | 0.00 | 663043.29 | 0.00 | 0.35 |
| November | 0.779422E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.302158E+09 | 0.00 | 0.00 | 0.35 |
| December | 0.338328E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.986833E+09 | 0.00 | 0.00 | 0.35 |
| Annual Sum or Average | 0.574903E+10 | 0.103922E+09 | 0.00 | 4570820.92 | 4851020.46 | 0.395347E+10 | 0.138119E+10 | 0.00 | 0.35 |
| Minimum of Months | 75927880.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
| Maximum of Months | 0.903435E+09 | 65605879.10 | 0.00 | 1589501.36 | 4851020.46 | 0.127053E+10 | 0.454252E+09 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: G N2 APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.128657E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127163E+10 | 0.00 | 0.00 | 0.35 |
| February | 0.248145E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.918713E+09 | 0.00 | 0.00 | 0.35 |
| March | 0.689342E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.392888E+09 | 0.00 | 0.00 | 0.35 |
| April | 0.794486E+09 | 0.00 | 0.00 | 0.00 | 4826486.79 | 82522979.16 | 0.00 | 0.00 | 0.35 |
| May | 0.801373E+09 | 1361836.86 | 0.00 | 79934.58 | 0.00 | 0.00 | 22149774.57 | 0.00 | 0.35 |
| June | 0.458231E+09 | 2767533.76 | 0.00 | 655893.59 | 0.00 | 0.00 | 0.217861E+09 | 0.00 | 0.35 |
| July | 0.104156E+09 | 31569432.70 | 0.00 | 1563190.02 | 0.00 | 0.00 | 0.450066E+09 | 0.00 | 0.36 |
| August | 77908984.43 | 65744731.78 | 0.00 | 1503821.90 | 0.00 | 0.00 | 0.384699E+09 | 0.00 | 0.36 |
| September | 0.428017E+09 | 2619448.90 | 0.00 | 735371.49 | 0.00 | 0.00 | 0.301814E+09 | 0.00 | 0.36 |
| October | 0.903189E+09 | 0.00 | 0.00 | 1180.88 | 0.00 | 0.00 | 458547.23 | 0.00 | 0.35 |
| November | 0.779213E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.302348E+09 | 0.00 | 0.00 | 0.35 |
| December | 0.337986E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.987176E+09 | 0.00 | 0.00 | 0.35 |
| Annual Sum or Average | 0.575070E+10 | 0.104063E+09 | 0.00 | 4539392.46 | 4826486.79 | 0.395528E+10 | 0.137705E+10 | 0.00 | 0.35 |
| Minimum of Months | 77908984.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
| Maximum of Months | 0.903189E+09 | 65744731.78 | 0.00 | 1563190.02 | 4826486.79 | 0.127163E+10 | 0.450066E+09 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: G S1 APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.610372E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.790824E+09 | 0.00 | 0.00 | 0.35 |
| February | 0.793283E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.383041E+09 | 0.00 | 0.00 | 0.35 |
| March | 0.107613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33522159.11 | 0.00 | 0.00 | 0.35 |
| April | 0.888078E+09 | 3474886.21 | 0.00 | 94455.79 | 252361.73 | 2157565.47 | 40595171.20 | 0.00 | 0.35 |
| May | 0.713618E+09 | 2355567.72 | 0.00 | 527821.60 | 0.00 | 0.00 | 0.167599E+09 | 0.00 | 0.35 |
| June | 0.320906E+09 | 3299350.35 | 0.00 | 1349414.68 | 0.00 | 0.00 | 0.369648E+09 | 0.00 | 0.36 |
| July | 34865027.99 | 37105281.50 | 0.00 | 2287002.19 | 0.00 | 0.00 | 0.509418E+09 | 0.00 | 0.36 |
| August | 12900223.74 | 78267376.01 | 0.00 | 2233839.60 | 0.00 | 0.00 | 0.431000E+09 | 0.00 | 0.36 |
| September | 0.143505E+09 | 8931529.16 | 0.00 | 2446962.25 | 0.00 | 0.00 | 0.575229E+09 | 0.00 | 0.36 |
| October | 0.710029E+09 | 0.00 | 0.00 | 901024.85 | 0.00 | 0.00 | 0.293832E+09 | 0.00 | 0.35 |
| November | 0.101866E+10 | 0.00 | 0.00 | 17009.29 | 0.00 | 81051179.35 | 6406027.28 | 0.00 | 0.35 |
| December | 0.827025E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.504707E+09 | 0.00 | 0.00 | 0.35 |
| Annual Sum or Average | 0.714937E+10 | 0.133434E+09 | 0.00 | 9857530.24 | 252361.73 | 0.179530E+10 | 0.239373E+10 | 0.00 | 0.35 |
| Minimum of Months | 12900223.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
| Maximum of Months | 0.107613E+10 | 78267376.01 | 0.00 | 2446962.25 | 252361.73 | 0.790824E+09 | 0.575229E+09 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: G S2 APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.426986E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.973985E+09 | 0.00 | 0.00 | 0.35 |
| February | 0.694826E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.480619E+09 | 0.00 | 0.00 | 0.35 |
| March | 0.105703E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 52729902.18 | 0.00 | 0.00 | 0.35 |
| April | 0.884256E+09 | 3479895.17 | 0.00 | 114249.33 | 251796.32 | 5484582.97 | 44620629.92 | 0.00 | 0.35 |
| May | 0.681880E+09 | 2456641.46 | 0.00 | 654660.11 | 0.00 | 0.00 | 0.205643E+09 | 0.00 | 0.35 |
| June | 0.281507E+09 | 3321342.95 | 0.00 | 1581667.44 | 0.00 | 0.00 | 0.411039E+09 | 0.00 | 0.36 |
| July | 21476486.61 | 37878090.05 | 0.00 | 2519308.98 | 0.00 | 0.00 | 0.518487E+09 | 0.00 | 0.36 |
| August | 4775324.36 | 79702056.15 | 0.00 | 2501976.34 | 0.00 | 0.00 | 0.432241E+09 | 0.00 | 0.36 |
| September | 0.113629E+09 | 9239021.26 | 0.00 | 2707632.81 | 0.00 | 0.00 | 0.601606E+09 | 0.00 | 0.36 |
| October | 0.700449E+09 | 0.00 | 0.00 | 1004710.94 | 0.00 | 0.00 | 0.309800E+09 | 0.00 | 0.35 |
| November | 0.969388E+09 | 0.00 | 0.00 | 23237.31 | 0.00 | 0.131665E+09 | 7804745.17 | 0.00 | 0.35 |
| December | 0.713199E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.617762E+09 | 0.00 | 0.00 | 0.35 |
| Annual Sum or Average | 0.654940E+10 | 0.136077E+09 | 0.00 | 11107443.27 | 251796.32 | 0.226225E+10 | 0.253124E+10 | 0.00 | 0.35 |
| Minimum of Months | 4775324.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
| Maximum of Months | 0.105703E+10 | 79702056.15 | 0.00 | 2707632.81 | 251796.32 | 0.973985E+09 | 0.601606E+09 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: M SW APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.867735E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.191702E+10 | 0.00 | 0.00 | 0.35 |
| February | 0.143656E+10 | 0.00 | 0.00 | 63575.00 | 0.00 | 0.905600E+09 | 28493074.24 | 0.00 | 0.35 |
| March | 0.206423E+10 | 0.00 | 0.00 | 569023.41 | 0.00 | 94952681.44 | 0.145762E+09 | 0.00 | 0.35 |
| April | 0.158832E+10 | 7495384.79 | 0.00 | 1852687.60 | 0.00 | 0.00 | 0.409298E+09 | 0.00 | 0.35 |
| May | 0.916930E+09 | 6339359.02 | 0.00 | 4795413.06 | 0.00 | 0.00 | 0.899112E+09 | 0.00 | 0.35 |
| June | 0.303209E+09 | 7127278.52 | 0.00 | 6056064.27 | 0.00 | 0.00 | 0.106276E+10 | 0.00 | 0.36 |
| July | 24974410.27 | 84062541.37 | 0.00 | 6933270.19 | 0.00 | 0.00 | 0.101817E+10 | 0.00 | 0.36 |
| August | 58339573.12 | 0.167288E+09 | 0.00 | 5476435.50 | 0.00 | 0.00 | 0.800426E+09 | 0.00 | 0.36 |
| September | 0.304206E+09 | 21997402.58 | 0.00 | 6492641.88 | 0.00 | 0.00 | 0.110175E+10 | 0.00 | 0.36 |
| October | 0.146519E+10 | 0.00 | 0.00 | 2411668.37 | 0.00 | 0.00 | 0.502954E+09 | 0.00 | 0.35 |
| November | 0.148228E+10 | 0.00 | 0.00 | 153572.80 | 0.00 | 0.674934E+09 | 33692781.84 | 0.00 | 0.35 |
| December | 0.115613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.149939E+10 | 0.00 | 0.00 | 0.35 |
| Annual Sum or Average | 0.116681E+11 | 0.294310E+09 | 0.00 | 34804352.09 | 0.00 | 0.509189E+10 | 0.600241E+10 | 0.00 | 0.35 |
| Minimum of Months | 24974410.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
| Maximum of Months | 0.206423E+10 | 0.167288E+09 | 0.00 | 6933270.19 | 0.00 | 0.191702E+10 | 0.110175E+10 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: M NW APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.200537E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.257823E+10 | 0.00 | 0.00 | 0.35 |
| February | 0.657902E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.166883E+10 | 0.00 | 0.00 | 0.35 |
| March | 0.174149E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.442945E+09 | 0.00 | 0.00 | 0.35 |
| April | 0.167502E+10 | 6314654.27 | 0.00 | 474728.48 | 1163698.38 | 64972958.55 | 0.139396E+09 | 0.00 | 0.35 |
| May | 0.113505E+10 | 5072143.01 | 0.00 | 2922707.60 | 0.00 | 0.00 | 0.666403E+09 | 0.00 | 0.35 |
| June | 0.391708E+09 | 6287668.47 | 0.00 | 4963506.84 | 0.00 | 0.00 | 0.978135E+09 | 0.00 | 0.36 |
| July | 56407905.03 | 75799283.06 | 0.00 | 5853959.51 | 0.00 | 0.00 | 0.998121E+09 | 0.00 | 0.36 |
| August | 0.100471E+09 | 0.147453E+09 | 0.00 | 4418145.71 | 0.00 | 0.00 | 0.780550E+09 | 0.00 | 0.36 |
| September | 0.552585E+09 | 11318167.06 | 0.00 | 3412483.98 | 0.00 | 0.00 | 0.884280E+09 | 0.00 | 0.36 |
| October | 0.167012E+10 | 0.00 | 0.00 | 247671.46 | 0.00 | 66297442.86 | 98766769.12 | 0.00 | 0.35 |
| November | 0.104771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110348E+10 | 0.00 | 0.00 | 0.35 |
| December | 0.404037E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.222702E+10 | 0.00 | 0.00 | 0.35 |
| Annual Sum or Average | 0.963304E+10 | 0.252245E+09 | 0.00 | 22293203.57 | 1163698.38 | 0.815178E+10 | 0.454565E+10 | 0.00 | 0.35 |
| Minimum of Months | 56407905.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
| Maximum of Months | 0.174149E+10 | 0.147453E+09 | 0.00 | 5853959.51 | 1163698.38 | 0.257823E+10 | 0.998121E+09 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: M SE APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.879414E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.190461E+10 | 0.00 | 0.00 | 0.35 |
| February | 0.144611E+10 | 0.00 | 0.00 | 28531.63 | 0.00 | 0.906124E+09 | 16740269.29 | 0.00 | 0.35 |
| March | 0.210512E+10 | 0.00 | 0.00 | 366539.67 | 0.00 | 75887086.82 | 0.127092E+09 | 0.00 | 0.35 |
| April | 0.153549E+10 | 7459968.37 | 0.00 | 1936709.96 | 0.00 | 0.00 | 0.479151E+09 | 0.00 | 0.35 |
| May | 0.935467E+09 | 6308375.18 | 0.00 | 4539092.93 | 0.00 | 0.00 | 0.880199E+09 | 0.00 | 0.35 |
| June | 0.292331E+09 | 7116145.95 | 0.00 | 6638206.32 | 0.00 | 0.00 | 0.107194E+10 | 0.00 | 0.36 |
| July | 39922488.74 | 82964034.88 | 0.00 | 6772319.10 | 0.00 | 0.00 | 0.101191E+10 | 0.00 | 0.36 |
| August | 70432057.45 | 0.171204E+09 | 0.00 | 5757781.08 | 0.00 | 0.00 | 0.787123E+09 | 0.00 | 0.36 |
| September | 0.342889E+09 | 22212587.07 | 0.00 | 6198535.23 | 0.00 | 0.00 | 0.106495E+10 | 0.00 | 0.36 |
| October | 0.143942E+10 | 0.00 | 0.00 | 2391938.96 | 0.00 | 0.00 | 0.531364E+09 | 0.00 | 0.35 |
| November | 0.149065E+10 | 0.00 | 0.00 | 138799.17 | 0.00 | 0.669132E+09 | 32353701.00 | 0.00 | 0.35 |
| December | 0.114360E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.151100E+10 | 0.00 | 0.00 | 0.35 |
| Annual Sum or Average | 0.117209E+11 | 0.297265E+09 | 0.00 | 34768454.06 | 0.00 | 0.506676E+10 | 0.600282E+10 | 0.00 | 0.35 |
| Minimum of Months | 39922488.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
| Maximum of Months | 0.210512E+10 | 0.171204E+09 | 0.00 | 6772319.10 | 0.00 | 0.190461E+10 | 0.107194E+10 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: M NE APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.193107E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.258569E+10 | 0.00 | 0.00 | 0.35 |
| February | 0.672243E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.165336E+10 | 0.00 | 0.00 | 0.35 |
| March | 0.174847E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.432438E+09 | 0.00 | 0.00 | 0.35 |
| April | 0.168611E+10 | 6096023.13 | 0.00 | 451552.20 | 1139409.95 | 78629077.81 | 0.132117E+09 | 0.00 | 0.35 |
| May | 0.111946E+10 | 5159430.55 | 0.00 | 2677516.42 | 0.00 | 0.00 | 0.683942E+09 | 0.00 | 0.35 |
| June | 0.359072E+09 | 6247318.29 | 0.00 | 5523513.57 | 0.00 | 0.00 | 0.100999E+10 | 0.00 | 0.36 |
| July | 87293928.04 | 74576803.43 | 0.00 | 5664073.85 | 0.00 | 0.00 | 0.976267E+09 | 0.00 | 0.36 |
| August | 0.107620E+09 | 0.152632E+09 | 0.00 | 4722877.71 | 0.00 | 0.00 | 0.772356E+09 | 0.00 | 0.36 |
| September | 0.607726E+09 | 11168939.51 | 0.00 | 3196125.67 | 0.00 | 0.00 | 0.826616E+09 | 0.00 | 0.36 |
| October | 0.167705E+10 | 0.00 | 0.00 | 195305.82 | 0.00 | 71208706.42 | 89017685.69 | 0.00 | 0.35 |
| November | 0.105838E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109253E+10 | 0.00 | 0.00 | 0.35 |
| December | 0.391089E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.223998E+10 | 0.00 | 0.00 | 0.35 |
| Annual Sum or Average | 0.970763E+10 | 0.255881E+09 | 0.00 | 22430965.24 | 1139409.95 | 0.815383E+10 | 0.449031E+10 | 0.00 | 0.35 |
| Minimum of Months | 87293928.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
| Maximum of Months | 0.174847E+10 | 0.152632E+09 | 0.00 | 5664073.85 | 1139409.95 | 0.258569E+10 | 0.100999E+10 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: M N1 APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.196624E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.827346E+09 | 0.00 | 0.00 | 0.35 |
| February | 0.182301E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.529224E+09 | 0.00 | 0.00 | 0.35 |
| March | 0.222836E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2741589.26 | 0.00 | 0.00 | 0.35 |
| April | 0.179830E+10 | 5994871.90 | 0.00 | 444085.29 | 1452202.08 | 0.00 | 0.154535E+09 | 0.00 | 0.35 |
| May | 0.898956E+09 | 4677412.90 | 0.00 | 2958979.38 | 0.00 | 0.00 | 0.961995E+09 | 0.00 | 0.35 |
| June | 0.153614E+09 | 5947460.75 | 0.00 | 5187985.10 | 0.00 | 0.00 | 0.124148E+10 | 0.00 | 0.36 |
| July | 5929477.08 | 68431584.20 | 0.00 | 5479220.50 | 0.00 | 0.00 | 0.106524E+10 | 0.00 | 0.36 |
| August | 4529436.78 | 0.139476E+09 | 0.00 | 4650107.95 | 0.00 | 0.00 | 0.882708E+09 | 0.00 | 0.36 |
| September | 0.232081E+09 | 8283074.31 | 0.00 | 4016545.79 | 0.00 | 0.00 | 0.122887E+10 | 0.00 | 0.36 |
| October | 0.173306E+10 | 0.00 | 0.00 | 392287.44 | 0.00 | 0.00 | 0.210808E+09 | 0.00 | 0.35 |
| November | 0.213290E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 64941419.75 | 0.00 | 0.00 | 0.35 |
| December | 0.221328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.430501E+09 | 0.00 | 0.00 | 0.35 |
| Annual Sum or Average | 0.151903E+11 | 0.232811E+09 | 0.00 | 23129211.45 | 1452202.08 | 0.185475E+10 | 0.574563E+10 | 0.00 | 0.35 |
| Minimum of Months | 4529436.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
| Maximum of Months | 0.222836E+10 | 0.139476E+09 | 0.00 | 5479220.50 | 1452202.08 | 0.827346E+09 | 0.124148E+10 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: M N2 APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.196708E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.826509E+09 | 0.00 | 0.00 | 0.35 |
| February | 0.182127E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.530891E+09 | 0.00 | 0.00 | 0.35 |
| March | 0.222933E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1370886.50 | 0.00 | 0.00 | 0.35 |
| April | 0.180105E+10 | 5997153.26 | 0.00 | 446188.04 | 1430469.57 | 0.00 | 0.154702E+09 | 0.00 | 0.35 |
| May | 0.907234E+09 | 4683253.30 | 0.00 | 2946192.35 | 0.00 | 0.00 | 0.953598E+09 | 0.00 | 0.35 |
| June | 0.154381E+09 | 5949576.09 | 0.00 | 5208317.41 | 0.00 | 0.00 | 0.124067E+10 | 0.00 | 0.36 |
| July | 6014936.89 | 68438862.96 | 0.00 | 5460678.06 | 0.00 | 0.00 | 0.106584E+10 | 0.00 | 0.36 |
| August | 4590151.19 | 0.139732E+09 | 0.00 | 4644999.58 | 0.00 | 0.00 | 0.882783E+09 | 0.00 | 0.36 |
| September | 0.237439E+09 | 8331694.05 | 0.00 | 3987135.93 | 0.00 | 0.00 | 0.122365E+10 | 0.00 | 0.36 |
| October | 0.174092E+10 | 0.00 | 0.00 | 388693.70 | 0.00 | 0.00 | 0.203226E+09 | 0.00 | 0.35 |
| November | 0.213341E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 64405355.46 | 0.00 | 0.00 | 0.35 |
| December | 0.221192E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.431854E+09 | 0.00 | 0.00 | 0.35 |
| Annual Sum or Average | 0.152147E+11 | 0.233133E+09 | 0.00 | 23082205.06 | 1430469.57 | 0.185503E+10 | 0.572448E+10 | 0.00 | 0.35 |
| Minimum of Months | 4590151.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
| Maximum of Months | 0.222933E+10 | 0.139732E+09 | 0.00 | 5460678.06 | 1430469.57 | 0.826509E+09 | 0.124067E+10 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: M S1 APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.257849E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.232036E+09 | 0.00 | 0.00 | 0.35 |
| February | 0.219150E+10 | 0.00 | 0.00 | 156596.74 | 0.00 | 0.158242E+09 | 80527884.85 | 0.00 | 0.35 |
| March | 0.215163E+10 | 0.00 | 0.00 | 863952.64 | 0.00 | 0.00 | 0.274521E+09 | 0.00 | 0.35 |
| April | 0.138345E+10 | 7450512.96 | 0.00 | 2377612.65 | 0.00 | 0.00 | 0.709744E+09 | 0.00 | 0.35 |
| May | 0.607683E+09 | 5924950.13 | 0.00 | 5090513.58 | 0.00 | 0.00 | 0.126006E+10 | 0.00 | 0.35 |
| June | 0.109527E+09 | 6895787.81 | 0.00 | 6385151.56 | 0.00 | 0.00 | 0.127738E+10 | 0.00 | 0.36 |
| July | 4708759.98 | 78756686.23 | 0.00 | 6600285.65 | 0.00 | 0.00 | 0.105124E+10 | 0.00 | 0.36 |
| August | 2186121.15 | 0.163266E+09 | 0.00 | 5730325.89 | 0.00 | 0.00 | 0.856794E+09 | 0.00 | 0.36 |
| September | 85153840.08 | 20663566.98 | 0.00 | 7113215.59 | 0.00 | 0.00 | 0.132746E+10 | 0.00 | 0.36 |
| October | 0.120566E+10 | 0.00 | 0.00 | 3466736.34 | 0.00 | 0.00 | 0.876904E+09 | 0.00 | 0.35 |
| November | 0.214683E+10 | 0.00 | 0.00 | 265172.08 | 0.00 | 29453905.51 | 91259407.88 | 0.00 | 0.35 |
| December | 0.246056E+10 | 0.00 | 0.00 | 27854.12 | 0.00 | 0.216148E+09 | 22337535.25 | 0.00 | 0.35 |
| Annual Sum or Average | 0.149274E+11 | 0.282958E+09 | 0.00 | 38077416.84 | 0.00 | 0.635881E+09 | 0.782822E+10 | 0.00 | 0.35 |
| Minimum of Months | 2186121.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
| Maximum of Months | 0.257849E+10 | 0.163266E+09 | 0.00 | 7113215.59 | 0.00 | 0.232036E+09 | 0.132746E+10 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: M S2 APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.257846E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.232036E+09 | 0.00 | 0.00 | 0.35 |
| February | 0.219202E+10 | 0.00 | 0.00 | 154829.47 | 0.00 | 0.157308E+09 | 80778075.17 | 0.00 | 0.35 |
| March | 0.215552E+10 | 0.00 | 0.00 | 863282.42 | 0.00 | 0.00 | 0.271137E+09 | 0.00 | 0.35 |
| April | 0.137021E+10 | 7451208.30 | 0.00 | 2423588.91 | 0.00 | 0.00 | 0.724676E+09 | 0.00 | 0.35 |
| May | 0.614927E+09 | 5929937.17 | 0.00 | 5065057.77 | 0.00 | 0.00 | 0.125260E+10 | 0.00 | 0.35 |
| June | 0.109675E+09 | 6897507.35 | 0.00 | 6397450.43 | 0.00 | 0.00 | 0.127715E+10 | 0.00 | 0.36 |
| July | 4710110.76 | 78752329.40 | 0.00 | 6582967.12 | 0.00 | 0.00 | 0.105189E+10 | 0.00 | 0.36 |
| August | 2240949.11 | 0.163426E+09 | 0.00 | 5725333.85 | 0.00 | 0.00 | 0.856898E+09 | 0.00 | 0.36 |
| September | 87325370.50 | 20694505.12 | 0.00 | 7086888.72 | 0.00 | 0.00 | 0.132558E+10 | 0.00 | 0.36 |
| October | 0.120668E+10 | 0.00 | 0.00 | 3470285.13 | 0.00 | 0.00 | 0.876097E+09 | 0.00 | 0.35 |
| November | 0.214688E+10 | 0.00 | 0.00 | 265675.85 | 0.00 | 29453903.40 | 91241253.58 | 0.00 | 0.35 |
| December | 0.245961E+10 | 0.00 | 0.00 | 27958.52 | 0.00 | 0.216946E+09 | 22337741.15 | 0.00 | 0.35 |
| Annual Sum or Average | 0.149282E+11 | 0.283151E+09 | 0.00 | 38063318.18 | 0.00 | 0.635744E+09 | 0.783038E+10 | 0.00 | 0.35 |
| Minimum of Months | 2240949.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
| Maximum of Months | 0.257846E+10 | 0.163426E+09 | 0.00 | 7086888.72 | 0.00 | 0.232036E+09 | 0.132558E+10 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: T SW APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.107565E+09 | 0.00 | 0.00 | 583.18 | 0.00 | 0.127816E+10 | 1732498.29 | 0.00 | 0.35 |
| February | 0.254304E+09 | 0.00 | 0.00 | 91557.07 | 0.00 | 0.887196E+09 | 31797919.36 | 0.00 | 0.35 |
| March | 0.388272E+09 | 0.00 | 0.00 | 455683.06 | 0.00 | 0.648134E+09 | 76047027.62 | 0.00 | 0.35 |
| April | 0.464483E+09 | 3794868.11 | 0.00 | 962768.69 | 0.00 | 0.325235E+09 | 0.136210E+09 | 0.00 | 0.35 |
| May | 0.516179E+09 | 3350033.82 | 0.00 | 1845090.15 | 0.00 | 0.105250E+09 | 0.192933E+09 | 0.00 | 0.35 |
| June | 0.409712E+09 | 3668823.37 | 0.00 | 2109059.15 | 0.00 | 15352155.64 | 0.200427E+09 | 0.00 | 0.35 |
| July | 0.308710E+09 | 43651753.55 | 0.00 | 2304781.03 | 0.00 | 0.00 | 0.193009E+09 | 0.00 | 0.35 |
| August | 0.258905E+09 | 85073326.92 | 0.00 | 1501795.07 | 0.00 | 0.00 | 0.162108E+09 | 0.00 | 0.36 |
| September | 0.448569E+09 | 11854399.26 | 0.00 | 1944426.01 | 0.00 | 24559875.04 | 0.172500E+09 | 0.00 | 0.35 |
| October | 0.435156E+09 | 0.00 | 0.00 | 788870.37 | 0.00 | 0.340579E+09 | 0.114371E+09 | 0.00 | 0.35 |
| November | 0.217129E+09 | 17096.37 | 0.00 | 99648.81 | 0.00 | 0.832988E+09 | 20826379.30 | 0.00 | 0.35 |
| December | 0.159348E+09 | 0.00 | 0.00 | 21337.73 | 0.00 | 0.114901E+10 | 12111328.38 | 0.00 | 0.35 |
| Annual Sum or Average | 0.396833E+10 | 0.151410E+09 | 0.00 | 12125600.32 | 0.00 | 0.560646E+10 | 0.131407E+10 | 0.00 | 0.35 |
| Minimum of Months | 0.107565E+09 | 0.00 | 0.00 | 583.18 | 0.00 | 0.00 | 1732498.29 | 0.00 | 0.35 |
| Maximum of Months | 0.516179E+09 | 85073326.92 | 0.00 | 2304781.03 | 0.00 | 0.127816E+10 | 0.200427E+09 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: T NW APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 3163442.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138166E+10 | 0.00 | 0.00 | 0.35 |
| February | 93860017.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106227E+10 | 0.00 | 0.00 | 0.35 |
| March | 0.280548E+09 | 0.00 | 0.00 | 5715.05 | 0.00 | 0.797613E+09 | 2541742.41 | 0.00 | 0.35 |
| April | 0.446672E+09 | 3483996.04 | 0.00 | 272490.25 | 68492.16 | 0.404466E+09 | 46403287.89 | 0.00 | 0.35 |
| May | 0.547835E+09 | 2656009.74 | 0.00 | 1112062.56 | 0.00 | 0.119585E+09 | 0.136131E+09 | 0.00 | 0.35 |
| June | 0.433532E+09 | 3266652.08 | 0.00 | 1605300.42 | 0.00 | 17444275.29 | 0.172116E+09 | 0.00 | 0.35 |
| July | 0.321760E+09 | 39703931.37 | 0.00 | 1820580.30 | 0.00 | 0.00 | 0.180690E+09 | 0.00 | 0.35 |
| August | 0.281495E+09 | 75723627.87 | 0.00 | 1125924.49 | 0.00 | 0.00 | 0.141315E+09 | 0.00 | 0.36 |
| September | 0.496525E+09 | 6064877.32 | 0.00 | 848463.42 | 0.00 | 29008422.79 | 0.108871E+09 | 0.00 | 0.35 |
| October | 0.359511E+09 | 0.00 | 0.00 | 29434.32 | 0.00 | 0.480967E+09 | 2532326.33 | 0.00 | 0.35 |
| November | 89802002.49 | 0.00 | 0.00 | 7843.63 | 0.00 | 0.969044E+09 | 1432128.64 | 0.00 | 0.35 |
| December | 11433225.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129989E+10 | 0.00 | 0.00 | 0.35 |
| Annual Sum or Average | 0.336614E+10 | 0.130899E+09 | 0.00 | 6827814.46 | 68492.16 | 0.656195E+10 | 0.792034E+09 | 0.00 | 0.35 |
| Minimum of Months | 3163442.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
| Maximum of Months | 0.547835E+09 | 75723627.87 | 0.00 | 1820580.30 | 68492.16 | 0.138166E+10 | 0.180690E+09 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: T SE APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.105160E+09 | 0.00 | 0.00 | 1410.75 | 0.00 | 0.127983E+10 | 2025047.84 | 0.00 | 0.35 |
| February | 0.267894E+09 | 0.00 | 0.00 | 59370.56 | 0.00 | 0.882494E+09 | 22002514.82 | 0.00 | 0.35 |
| March | 0.411504E+09 | 0.00 | 0.00 | 356838.58 | 0.00 | 0.633952E+09 | 67647956.14 | 0.00 | 0.35 |
| April | 0.478677E+09 | 3783247.36 | 0.00 | 913772.99 | 0.00 | 0.298788E+09 | 0.154293E+09 | 0.00 | 0.35 |
| May | 0.513700E+09 | 3325060.97 | 0.00 | 1644170.76 | 0.00 | 0.103528E+09 | 0.200139E+09 | 0.00 | 0.35 |
| June | 0.381596E+09 | 3659412.64 | 0.00 | 2255141.02 | 0.00 | 18715232.06 | 0.229245E+09 | 0.00 | 0.35 |
| July | 0.300307E+09 | 43127784.46 | 0.00 | 2227267.69 | 0.00 | 0.00 | 0.204799E+09 | 0.00 | 0.35 |
| August | 0.246164E+09 | 87348369.09 | 0.00 | 1585496.88 | 0.00 | 0.00 | 0.177619E+09 | 0.00 | 0.36 |
| September | 0.442912E+09 | 12027213.52 | 0.00 | 1786145.33 | 0.00 | 25929529.48 | 0.176433E+09 | 0.00 | 0.35 |
| October | 0.431873E+09 | 0.00 | 0.00 | 722919.98 | 0.00 | 0.335957E+09 | 0.124773E+09 | 0.00 | 0.35 |
| November | 0.220564E+09 | 4024.33 | 0.00 | 90572.26 | 0.00 | 0.832998E+09 | 17809892.98 | 0.00 | 0.35 |
| December | 0.156297E+09 | 0.00 | 0.00 | 17035.44 | 0.00 | 0.115259E+10 | 11168737.37 | 0.00 | 0.35 |
| Annual Sum or Average | 0.395665E+10 | 0.153275E+09 | 0.00 | 11660142.23 | 0.00 | 0.556477E+10 | 0.138795E+10 | 0.00 | 0.35 |
| Minimum of Months | 0.105160E+09 | 0.00 | 0.00 | 1410.75 | 0.00 | 0.00 | 2025047.84 | 0.00 | 0.35 |
| Maximum of Months | 0.513700E+09 | 87348369.09 | 0.00 | 2255141.02 | 0.00 | 0.127983E+10 | 0.229245E+09 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: T NE APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 2123065.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138272E+10 | 0.00 | 0.00 | 0.35 |
| February | 83416698.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107191E+10 | 0.00 | 0.00 | 0.35 |
| March | 0.307187E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.769891E+09 | 0.00 | 0.00 | 0.35 |
| April | 0.496363E+09 | 3455291.86 | 0.00 | 179123.52 | 0.00 | 0.371649E+09 | 34792934.92 | 0.00 | 0.35 |
| May | 0.537412E+09 | 2677041.91 | 0.00 | 889676.67 | 0.00 | 0.131664E+09 | 0.139863E+09 | 0.00 | 0.35 |
| June | 0.393478E+09 | 3239177.06 | 0.00 | 1756307.40 | 0.00 | 20441957.79 | 0.214771E+09 | 0.00 | 0.35 |
| July | 0.314302E+09 | 39113883.23 | 0.00 | 1775134.56 | 0.00 | 0.00 | 0.190843E+09 | 0.00 | 0.35 |
| August | 0.271089E+09 | 78759212.95 | 0.00 | 1191359.11 | 0.00 | 0.00 | 0.155148E+09 | 0.00 | 0.36 |
| September | 0.497602E+09 | 6083262.32 | 0.00 | 685363.16 | 0.00 | 28573264.66 | 0.108423E+09 | 0.00 | 0.35 |
| October | 0.371752E+09 | 0.00 | 0.00 | 15217.84 | 0.00 | 0.467546E+09 | 2288603.29 | 0.00 | 0.35 |
| November | 89329027.12 | 0.00 | 0.00 | 10.55 | 0.00 | 0.970854E+09 | 97207.58 | 0.00 | 0.35 |
| December | 3242321.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130812E+10 | 0.00 | 0.00 | 0.35 |
| Annual Sum or Average | 0.336730E+10 | 0.133328E+09 | 0.00 | 6492192.81 | 0.00 | 0.652337E+10 | 0.846227E+09 | 0.00 | 0.35 |
| Minimum of Months | 2123065.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
| Maximum of Months | 0.537412E+09 | 78759212.95 | 0.00 | 1775134.56 | 0.00 | 0.138272E+10 | 0.214771E+09 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: T N1 APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 27379184.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136535E+10 | 0.00 | 0.00 | 0.35 |
| February | 0.171572E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.992676E+09 | 0.00 | 0.00 | 0.35 |
| March | 0.476069E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.611456E+09 | 0.00 | 0.00 | 0.35 |
| April | 0.628979E+09 | 3384068.17 | 0.00 | 143312.45 | 93768.07 | 0.248448E+09 | 35046531.93 | 0.00 | 0.35 |
| May | 0.667363E+09 | 2446724.59 | 0.00 | 664557.76 | 0.00 | 36865473.52 | 0.125910E+09 | 0.00 | 0.35 |
| June | 0.433323E+09 | 3102977.21 | 0.00 | 1347123.56 | 0.00 | 0.00 | 0.218881E+09 | 0.00 | 0.35 |
| July | 0.295002E+09 | 36606952.52 | 0.00 | 1492615.29 | 0.00 | 0.00 | 0.231915E+09 | 0.00 | 0.35 |
| August | 0.252606E+09 | 72874033.82 | 0.00 | 1063691.46 | 0.00 | 0.00 | 0.190261E+09 | 0.00 | 0.36 |
| September | 0.536779E+09 | 4444280.41 | 0.00 | 557768.65 | 0.00 | 11822162.43 | 0.115854E+09 | 0.00 | 0.35 |
| October | 0.559909E+09 | 0.00 | 0.00 | 8095.84 | 0.00 | 0.294101E+09 | 1312455.41 | 0.00 | 0.35 |
| November | 0.232228E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.838528E+09 | 0.00 | 0.00 | 0.35 |
| December | 42592398.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127593E+10 | 0.00 | 0.00 | 0.35 |
| Annual Sum or Average | 0.432380E+10 | 0.122859E+09 | 0.00 | 5277165.01 | 93768.07 | 0.567519E+10 | 0.919180E+09 | 0.00 | 0.35 |
| Minimum of Months | 27379184.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
| Maximum of Months | 0.667363E+09 | 72874033.82 | 0.00 | 1492615.29 | 93768.07 | 0.136535E+10 | 0.231915E+09 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: T N2 APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 27379226.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136536E+10 | 0.00 | 0.00 | 0.35 |
| February | 0.171911E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.992270E+09 | 0.00 | 0.00 | 0.35 |
| March | 0.475755E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.611605E+09 | 0.00 | 0.00 | 0.35 |
| April | 0.632599E+09 | 3391761.68 | 0.00 | 143690.78 | 74917.30 | 0.246074E+09 | 34466426.07 | 0.00 | 0.35 |
| May | 0.667273E+09 | 2455207.53 | 0.00 | 666939.27 | 0.00 | 37105892.28 | 0.126019E+09 | 0.00 | 0.35 |
| June | 0.431415E+09 | 3104674.49 | 0.00 | 1366013.74 | 0.00 | 0.00 | 0.221123E+09 | 0.00 | 0.35 |
| July | 0.296110E+09 | 36628341.48 | 0.00 | 1488370.79 | 0.00 | 0.00 | 0.230751E+09 | 0.00 | 0.35 |
| August | 0.252225E+09 | 73110742.83 | 0.00 | 1067534.14 | 0.00 | 0.00 | 0.190753E+09 | 0.00 | 0.36 |
| September | 0.537405E+09 | 4513892.17 | 0.00 | 553011.90 | 0.00 | 12254989.84 | 0.114319E+09 | 0.00 | 0.35 |
| October | 0.559540E+09 | 0.00 | 0.00 | 8089.15 | 0.00 | 0.294337E+09 | 1363650.10 | 0.00 | 0.35 |
| November | 0.232074E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.838651E+09 | 0.00 | 0.00 | 0.35 |
| December | 42016929.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127651E+10 | 0.00 | 0.00 | 0.35 |
| Annual Sum or Average | 0.432570E+10 | 0.123205E+09 | 0.00 | 5293649.77 | 74917.30 | 0.567417E+10 | 0.918796E+09 | 0.00 | 0.35 |
| Minimum of Months | 27379226.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
| Maximum of Months | 0.667273E+09 | 73110742.83 | 0.00 | 1488370.79 | 74917.30 | 0.136536E+10 | 0.230751E+09 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: T S1 APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.251814E+09 | 0.00 | 0.00 | 7190.18 | 0.00 | 0.114033E+10 | 4995226.82 | 0.00 | 0.35 |
| February | 0.418866E+09 | 0.00 | 0.00 | 111595.61 | 0.00 | 0.722057E+09 | 47980955.21 | 0.00 | 0.35 |
| March | 0.618891E+09 | 0.00 | 0.00 | 407538.49 | 0.00 | 0.423205E+09 | 90302265.43 | 0.00 | 0.35 |
| April | 0.626869E+09 | 3778063.15 | 0.00 | 837842.14 | 0.00 | 0.159598E+09 | 0.165801E+09 | 0.00 | 0.35 |
| May | 0.597003E+09 | 3168084.77 | 0.00 | 1465670.90 | 0.00 | 24698611.08 | 0.222443E+09 | 0.00 | 0.35 |
| June | 0.399223E+09 | 3560268.75 | 0.00 | 1897109.06 | 0.00 | 0.00 | 0.254555E+09 | 0.00 | 0.35 |
| July | 0.276019E+09 | 41510584.76 | 0.00 | 2004349.55 | 0.00 | 0.00 | 0.249206E+09 | 0.00 | 0.35 |
| August | 0.218112E+09 | 83967621.85 | 0.00 | 1480145.71 | 0.00 | 0.00 | 0.220193E+09 | 0.00 | 0.36 |
| September | 0.451714E+09 | 11365205.96 | 0.00 | 1737461.64 | 0.00 | 4222331.94 | 0.220171E+09 | 0.00 | 0.35 |
| October | 0.618242E+09 | 0.00 | 0.00 | 805324.35 | 0.00 | 0.154551E+09 | 0.147905E+09 | 0.00 | 0.35 |
| November | 0.427385E+09 | 2448.95 | 0.00 | 120498.66 | 0.00 | 0.630418E+09 | 27931196.95 | 0.00 | 0.35 |
| December | 0.289544E+09 | 0.00 | 0.00 | 35950.16 | 0.00 | 0.102654E+10 | 16011390.74 | 0.00 | 0.35 |
| Annual Sum or Average | 0.519368E+10 | 0.147352E+09 | 0.00 | 10910676.45 | 0.00 | 0.428561E+10 | 0.166749E+10 | 0.00 | 0.35 |
| Minimum of Months | 0.218112E+09 | 0.00 | 0.00 | 7190.18 | 0.00 | 0.00 | 4995226.82 | 0.00 | 0.35 |
| Maximum of Months | 0.626869E+09 | 83967621.85 | 0.00 | 2004349.55 | 0.00 | 0.114033E+10 | 0.254555E+09 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: T S2 APARTMENT
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.251292E+09 | 0.00 | 0.00 | 7413.59 | 0.00 | 0.114083E+10 | 4997226.00 | 0.00 | 0.35 |
| February | 0.419124E+09 | 0.00 | 0.00 | 111714.98 | 0.00 | 0.721725E+09 | 48001612.43 | 0.00 | 0.35 |
| March | 0.617333E+09 | 0.00 | 0.00 | 406601.58 | 0.00 | 0.424481E+09 | 90645281.70 | 0.00 | 0.35 |
| April | 0.628750E+09 | 3778938.11 | 0.00 | 846723.44 | 0.00 | 0.157092E+09 | 0.166872E+09 | 0.00 | 0.35 |
| May | 0.594574E+09 | 3173955.53 | 0.00 | 1467119.50 | 0.00 | 25511348.78 | 0.223872E+09 | 0.00 | 0.35 |
| June | 0.398736E+09 | 3561866.48 | 0.00 | 1912716.74 | 0.00 | 0.00 | 0.255102E+09 | 0.00 | 0.35 |
| July | 0.277307E+09 | 41519177.25 | 0.00 | 1996553.17 | 0.00 | 0.00 | 0.247911E+09 | 0.00 | 0.35 |
| August | 0.218240E+09 | 84114736.55 | 0.00 | 1483727.89 | 0.00 | 0.00 | 0.220120E+09 | 0.00 | 0.36 |
| September | 0.452956E+09 | 11395639.35 | 0.00 | 1731740.51 | 0.00 | 4221984.73 | 0.218579E+09 | 0.00 | 0.35 |
| October | 0.616292E+09 | 0.00 | 0.00 | 810263.19 | 0.00 | 0.155580E+09 | 0.148883E+09 | 0.00 | 0.35 |
| November | 0.427365E+09 | 2714.00 | 0.00 | 120876.22 | 0.00 | 0.630435E+09 | 27983592.26 | 0.00 | 0.35 |
| December | 0.290313E+09 | 0.00 | 0.00 | 36405.19 | 0.00 | 0.102574E+10 | 16015374.80 | 0.00 | 0.35 |
| Annual Sum or Average | 0.519228E+10 | 0.147547E+09 | 0.00 | 10931856.00 | 0.00 | 0.428562E+10 | 0.166898E+10 | 0.00 | 0.35 |
| Minimum of Months | 0.218240E+09 | 0.00 | 0.00 | 7413.59 | 0.00 | 0.00 | 4997226.00 | 0.00 | 0.35 |
| Maximum of Months | 0.628750E+09 | 84114736.55 | 0.00 | 1996553.17 | 0.00 | 0.114083E+10 | 0.255102E+09 | 0.00 | 0.36 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 09:15:24
Custom Monthly Report| SITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
| January | 0.395099E+11 | 0.148076E+11 | 0.00 | 0.176667E+10 | 0.136236E+11 |
| February | 0.715168E+11 | 0.128216E+11 | 0.00 | 0.155248E+10 | 0.932860E+10 |
| March | 0.121235E+12 | 0.126404E+11 | 0.00 | 0.159343E+10 | 0.585041E+10 |
| April | 0.180038E+12 | 0.123265E+11 | 0.00 | 0.139981E+10 | 0.101562E+11 |
| May | 0.230534E+12 | 0.122847E+11 | 0.00 | 0.136703E+10 | 0.217669E+11 |
| June | 0.230255E+12 | 0.127608E+11 | 0.00 | 0.112456E+10 | 0.362456E+11 |
| July | 0.243478E+12 | 0.106802E+11 | 0.00 | 0.952850E+09 | 0.648009E+11 |
| August | 0.194592E+12 | 0.918266E+10 | 0.00 | 0.790689E+09 | 0.748300E+11 |
| September | 0.142568E+12 | 0.895176E+10 | 0.00 | 0.118576E+10 | 0.369408E+11 |
| October | 0.970832E+11 | 0.122074E+11 | 0.00 | 0.151760E+10 | 0.877443E+10 |
| November | 0.421569E+11 | 0.118743E+11 | 0.00 | 0.156327E+10 | 0.722832E+10 |
| December | 0.326902E+11 | 0.128745E+11 | 0.00 | 0.174186E+10 | 0.117107E+11 |
| Annual Sum or Average | 0.162566E+13 | 0.143412E+12 | 0.00 | 0.165560E+11 | 0.301256E+12 |
| Minimum of Months | 0.326902E+11 | 0.895176E+10 | 0.00 | 0.790689E+09 | 0.585041E+10 |
| Maximum of Months | 0.243478E+12 | 0.148076E+11 | 0.00 | 0.176667E+10 | 0.748300E+11 |