Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 09:14
Tabular Output Report in Format: HTML
Building: ApartmentMidRise
Environment: RUNPERIOD 1 ** New Delhi-Safdarjung AP Delhi IND IWEC2 WMO#=421820
Simulation Timestamp: 2023-10-16 09:14:53
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 09:14:53
Values gathered over 8760.00 hours| Total Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
| Total Site Energy | 1530.81 | 488.36 | 542.08 |
| Net Site Energy | 1530.81 | 488.36 | 542.08 |
| Total Source Energy | 4832.43 | 1541.64 | 1711.22 |
| Net Source Energy | 4832.43 | 1541.64 | 1711.22 |
| Site=>Source Conversion Factor | |
| Electricity | 3.167 |
| Natural Gas | 1.084 |
| District Cooling | 1.056 |
| District Heating | 3.613 |
| Steam | 1.200 |
| Gasoline | 1.050 |
| Diesel | 1.050 |
| Coal | 1.050 |
| Fuel Oil No 1 | 1.050 |
| Fuel Oil No 2 | 1.050 |
| Propane | 1.050 |
| Other Fuel 1 | 1.000 |
| Other Fuel 2 | 1.000 |
| Area [m2] | |
| Total Building Area | 3134.61 |
| Net Conditioned Building Area | 2823.98 |
| Unconditioned Building Area | 310.64 |
| Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
| Heating | 0.00 | 7.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Cooling | 403.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Lighting | 99.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Lighting | 50.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment | 458.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans | 157.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems | 353.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1875.32 |
| Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Total End Uses | 1523.30 | 7.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1875.32 |
| Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
| Heating | General | 0.00 | 7.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Cooling | General | 403.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Lighting | LightsWired | 94.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LightsPlugIn | 4.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Exterior Lighting | General | 50.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment | MiscPlug | 388.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| ElevatorLift | 65.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| ElevatorLightsFan | 5.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| General | 157.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems | Water Heater | 353.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1875.32 |
| Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
| Heating | Unassigned | 0.00 | 7.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Cooling | Unassigned | 403.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Lighting | GENERAL | 99.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Lighting | Unassigned | 50.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment | GENERAL | 458.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans | Unassigned | 157.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Pumps | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems | Unassigned | 353.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1875.32 |
| Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
| Lighting | 52.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| HVAC | 324.14 | 2.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.66 |
| Other | 162.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Total | 539.42 | 2.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.66 |
| Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
| Lighting | 47.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| HVAC | 292.02 | 2.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.60 |
| Other | 146.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Total | 485.96 | 2.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.60 |
| Electricity [GJ] | Percent Electricity [%] | |
| Fuel-Fired Power Generation | 0.000 | 0.00 |
| High Temperature Geothermal* | 0.000 | 0.00 |
| Photovoltaic Power | 0.000 | 0.00 |
| Wind Power | 0.000 | 0.00 |
| Power Conversion | 0.000 | 0.00 |
| Net Decrease in On-Site Storage | 0.000 | 0.00 |
| Total On-Site Electric Sources | 0.000 | 0.00 |
| Electricity Coming From Utility | 1523.301 | 100.00 |
| Surplus Electricity Going To Utility | 0.000 | 0.00 |
| Net Electricity From Utility | 1523.301 | 100.00 |
| Total On-Site and Utility Electric Sources | 1523.301 | 100.00 |
| Total Electricity End Uses | 1523.301 | 100.00 |
| Heat [GJ] | Percent Heat [%] | |
| Water-Side Heat Recovery | 0.00 | 0.00 |
| Air to Air Heat Recovery for Cooling | 0.00 | 48.89 |
| Air to Air Heat Recovery for Heating | 0.00 | 51.11 |
| High-Temperature Geothermal* | 0.00 | 0.00 |
| Solar Water Thermal | 0.00 | 0.00 |
| Solar Air Thermal | 0.00 | 0.00 |
| Total On-Site Thermal Sources | 0.00 | 100.00 |
| Water [m3] | Percent Water [%] | |
| Rainwater Collection | 0.00 | 0.00 |
| Condensate Collection | 0.00 | 0.00 |
| Groundwater Well | 0.00 | 0.00 |
| Total On Site Water Sources | 0.00 | 0.00 |
| - | - | - |
| Initial Storage | 0.00 | 0.00 |
| Final Storage | 0.00 | 0.00 |
| Change in Storage | 0.00 | 0.00 |
| - | - | - |
| Water Supplied by Utility | 1875.32 | 100.00 |
| - | - | - |
| Total On Site, Change in Storage, and Utility Water Sources | 1875.32 | 100.00 |
| Total Water End Uses | 1875.32 | 100.00 |
| Degrees [deltaC] | |
| Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
| Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
| Facility [Hours] | |
| Time Setpoint Not Met During Occupied Heating | 0.00 |
| Time Setpoint Not Met During Occupied Cooling | 0.50 |
| Time Not Comfortable Based on Simple ASHRAE 55-2004 | 8760.00 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2012
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME APARTMENTMIDRISE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 1B
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY IND_DELHI_NEWDELHI
| Environment |ZoneCoolingSummaryMonthly
| G SW APARTMENT | G NW APARTMENT | OFFICE | G NE APARTMENT | G N1 APARTMENT | G N2 APARTMENT | G S1 APARTMENT | G S2 APARTMENT | M SW APARTMENT | M NW APARTMENT | M SE APARTMENT | M NE APARTMENT | M N1 APARTMENT | M N2 APARTMENT | M S1 APARTMENT | M S2 APARTMENT | T SW APARTMENT | T NW APARTMENT | T SE APARTMENT | T NE APARTMENT | T N1 APARTMENT | T N2 APARTMENT | T S1 APARTMENT | T S2 APARTMENT | T CORRIDOR | G CORRIDOR | M CORRIDOR |ZoneHeatingSummaryMonthly
| G SW APARTMENT | G NW APARTMENT | OFFICE | G NE APARTMENT | G N1 APARTMENT | G N2 APARTMENT | G S1 APARTMENT | G S2 APARTMENT | M SW APARTMENT | M NW APARTMENT | M SE APARTMENT | M NE APARTMENT | M N1 APARTMENT | M N2 APARTMENT | M S1 APARTMENT | M S2 APARTMENT | T SW APARTMENT | T NW APARTMENT | T SE APARTMENT | T NE APARTMENT | T N1 APARTMENT | T N2 APARTMENT | T S1 APARTMENT | T S2 APARTMENT | T CORRIDOR | G CORRIDOR | M CORRIDOR |ZoneElectricSummaryMonthly
| G SW APARTMENT | G NW APARTMENT | OFFICE | G NE APARTMENT | G N1 APARTMENT | G N2 APARTMENT | G S1 APARTMENT | G S2 APARTMENT | M SW APARTMENT | M NW APARTMENT | M SE APARTMENT | M NE APARTMENT | M N1 APARTMENT | M N2 APARTMENT | M S1 APARTMENT | M S2 APARTMENT | T SW APARTMENT | T NW APARTMENT | T SE APARTMENT | T NE APARTMENT | T N1 APARTMENT | T N2 APARTMENT | T S1 APARTMENT | T S2 APARTMENT | T CORRIDOR | G CORRIDOR | M CORRIDOR |SpaceGainsMonthly
| G SW APARTMENT | G NW APARTMENT | OFFICE | G NE APARTMENT | G N1 APARTMENT | G N2 APARTMENT | G S1 APARTMENT | G S2 APARTMENT | M SW APARTMENT | M NW APARTMENT | M SE APARTMENT | M NE APARTMENT | M N1 APARTMENT | M N2 APARTMENT | M S1 APARTMENT | M S2 APARTMENT | T SW APARTMENT | T NW APARTMENT | T SE APARTMENT | T NE APARTMENT | T N1 APARTMENT | T N2 APARTMENT | T S1 APARTMENT | T S2 APARTMENT | T CORRIDOR | G CORRIDOR | M CORRIDOR |PeakSpaceGainsMonthly
| G SW APARTMENT | G NW APARTMENT | OFFICE | G NE APARTMENT | G N1 APARTMENT | G N2 APARTMENT | G S1 APARTMENT | G S2 APARTMENT | M SW APARTMENT | M NW APARTMENT | M SE APARTMENT | M NE APARTMENT | M N1 APARTMENT | M N2 APARTMENT | M S1 APARTMENT | M S2 APARTMENT | T SW APARTMENT | T NW APARTMENT | T SE APARTMENT | T NE APARTMENT | T N1 APARTMENT | T N2 APARTMENT | T S1 APARTMENT | T S2 APARTMENT | T CORRIDOR | G CORRIDOR | M CORRIDOR |SpaceGainComponentsAtCoolingPeakMonthly
| G SW APARTMENT | G NW APARTMENT | OFFICE | G NE APARTMENT | G N1 APARTMENT | G N2 APARTMENT | G S1 APARTMENT | G S2 APARTMENT | M SW APARTMENT | M NW APARTMENT | M SE APARTMENT | M NE APARTMENT | M N1 APARTMENT | M N2 APARTMENT | M S1 APARTMENT | M S2 APARTMENT | T SW APARTMENT | T NW APARTMENT | T SE APARTMENT | T NE APARTMENT | T N1 APARTMENT | T N2 APARTMENT | T S1 APARTMENT | T S2 APARTMENT | T CORRIDOR | G CORRIDOR | M CORRIDOR |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| G SW APARTMENT | G NW APARTMENT | OFFICE | G NE APARTMENT | G N1 APARTMENT | G N2 APARTMENT | G S1 APARTMENT | G S2 APARTMENT | M SW APARTMENT | M NW APARTMENT | M SE APARTMENT | M NE APARTMENT | M N1 APARTMENT | M N2 APARTMENT | M S1 APARTMENT | M S2 APARTMENT | T SW APARTMENT | T NW APARTMENT | T SE APARTMENT | T NE APARTMENT | T N1 APARTMENT | T N2 APARTMENT | T S1 APARTMENT | T S2 APARTMENT | T CORRIDOR | G CORRIDOR | M CORRIDOR |ComfortReportSimple55Monthly
| G SW APARTMENT | G NW APARTMENT | OFFICE | G NE APARTMENT | G N1 APARTMENT | G N2 APARTMENT | G S1 APARTMENT | G S2 APARTMENT | M SW APARTMENT | M NW APARTMENT | M SE APARTMENT | M NE APARTMENT | M N1 APARTMENT | M N2 APARTMENT | M S1 APARTMENT | M S2 APARTMENT | T SW APARTMENT | T NW APARTMENT | T SE APARTMENT | T NE APARTMENT | T N1 APARTMENT | T N2 APARTMENT | T S1 APARTMENT | T S2 APARTMENT | T CORRIDOR | G CORRIDOR | M CORRIDOR |OccupantComfortDataSummaryMonthly
| OCCUP_GSW | OCCUP_GNW | OCCUP_OFFICE | OCCUP_GNE | OCCUP_GN1 | OCCUP_GN2 | OCCUP_GS1 | OCCUP_GS2 | OCCUP_MSW | OCCUP_MNW | OCCUP_MSE | OCCUP_MNE | OCCUP_MN1 | OCCUP_MN2 | OCCUP_MS1 | OCCUP_MS2 | OCCUP_TSW | OCCUP_TNW | OCCUP_TSE | OCCUP_TNE | OCCUP_TN1 | OCCUP_TN2 | OCCUP_TS1 | OCCUP_TS2 | OCCUP_T CORRIDOR | OCCUP_G CORRIDOR | OCCUP_M CORRIDOR |DXReportMonthly
| SPLIT GSW COOLING COIL | SPLIT GNW COOLING COIL | SPLIT OFFICE COOLING COIL | SPLIT GNE COOLING COIL | SPLIT GN1 COOLING COIL | SPLIT GN2 COOLING COIL | SPLIT GS1 COOLING COIL | SPLIT GS2 COOLING COIL | SPLIT MSW COOLING COIL | SPLIT MNW COOLING COIL | SPLIT MSE COOLING COIL | SPLIT MNE COOLING COIL | SPLIT MN1 COOLING COIL | SPLIT MN2 COOLING COIL | SPLIT MS1 COOLING COIL | SPLIT MS2 COOLING COIL | SPLIT TSW COOLING COIL | SPLIT TNW COOLING COIL | SPLIT TSE COOLING COIL | SPLIT TNE COOLING COIL | SPLIT TN1 COOLING COIL | SPLIT TN2 COOLING COIL | SPLIT TS1 COOLING COIL | SPLIT TS2 COOLING COIL |WindowReportMonthly
| GWINDOW1 S SWA | GWINDOW1 W SWA | GWINDOW1 W NWA | GWINDOW1 N NWA | GWINDOW1 S SEA | GWINDOW1 E SEA | GWINDOW1 E NEA | GWINDOW1 N NEA | GWINDOW1 N N1A | GWINDOW1 N N2A | GWINDOW1 S S1A | GWINDOW1 S S2A | MWINDOW1 S SWA | MWINDOW1 W SWA | MWINDOW1 W NWA | MWINDOW1 N NWA | MWINDOW1 S SEA | MWINDOW1 E SEA | MWINDOW1 E NEA | MWINDOW1 N NEA | MWINDOW1 N N1A | MWINDOW1 N N2A | MWINDOW1 S S1A | MWINDOW1 S S2A | TWINDOW1 S SWA | TWINDOW1 W SWA | TWINDOW1 W NWA | TWINDOW1 N NWA | TWINDOW1 S SEA | TWINDOW1 E SEA | TWINDOW1 E NEA | TWINDOW1 N NEA | TWINDOW1 N N1A | TWINDOW1 N N2A | TWINDOW1 S S1A | TWINDOW1 S S2A | TWINDOW14 | ENTRANCE DOOR | MWINDOW14 |WindowEnergyReportMonthly
| GWINDOW1 S SWA | GWINDOW1 W SWA | GWINDOW1 W NWA | GWINDOW1 N NWA | GWINDOW1 S SEA | GWINDOW1 E SEA | GWINDOW1 E NEA | GWINDOW1 N NEA | GWINDOW1 N N1A | GWINDOW1 N N2A | GWINDOW1 S S1A | GWINDOW1 S S2A | MWINDOW1 S SWA | MWINDOW1 W SWA | MWINDOW1 W NWA | MWINDOW1 N NWA | MWINDOW1 S SEA | MWINDOW1 E SEA | MWINDOW1 E NEA | MWINDOW1 N NEA | MWINDOW1 N N1A | MWINDOW1 N N2A | MWINDOW1 S S1A | MWINDOW1 S S2A | TWINDOW1 S SWA | TWINDOW1 W SWA | TWINDOW1 W NWA | TWINDOW1 N NWA | TWINDOW1 S SEA | TWINDOW1 E SEA | TWINDOW1 E NEA | TWINDOW1 N NEA | TWINDOW1 N N1A | TWINDOW1 N N2A | TWINDOW1 S S1A | TWINDOW1 S S2A | TWINDOW14 | ENTRANCE DOOR | MWINDOW14 |WindowZoneSummaryMonthly
| G SW APARTMENT | G NW APARTMENT | OFFICE | G NE APARTMENT | G N1 APARTMENT | G N2 APARTMENT | G S1 APARTMENT | G S2 APARTMENT | M SW APARTMENT | M NW APARTMENT | M SE APARTMENT | M NE APARTMENT | M N1 APARTMENT | M N2 APARTMENT | M S1 APARTMENT | M S2 APARTMENT | T SW APARTMENT | T NW APARTMENT | T SE APARTMENT | T NE APARTMENT | T N1 APARTMENT | T N2 APARTMENT | T S1 APARTMENT | T S2 APARTMENT | T CORRIDOR | G CORRIDOR | M CORRIDOR |WindowEnergyZoneSummaryMonthly
| G SW APARTMENT | G NW APARTMENT | OFFICE | G NE APARTMENT | G N1 APARTMENT | G N2 APARTMENT | G S1 APARTMENT | G S2 APARTMENT | M SW APARTMENT | M NW APARTMENT | M SE APARTMENT | M NE APARTMENT | M N1 APARTMENT | M N2 APARTMENT | M S1 APARTMENT | M S2 APARTMENT | T SW APARTMENT | T NW APARTMENT | T SE APARTMENT | T NE APARTMENT | T N1 APARTMENT | T N2 APARTMENT | T S1 APARTMENT | T S2 APARTMENT | T CORRIDOR | G CORRIDOR | M CORRIDOR |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| G SW APARTMENT WATER HEATER | G NW APARTMENT WATER HEATER | G NE APARTMENT WATER HEATER | G N1 APARTMENT WATER HEATER | G N2 APARTMENT WATER HEATER | G S1 APARTMENT WATER HEATER | G S2 APARTMENT WATER HEATER | M SW APARTMENT WATER HEATER | M NW APARTMENT WATER HEATER | M SE APARTMENT WATER HEATER | M NE APARTMENT WATER HEATER | M N1 APARTMENT WATER HEATER | M N2 APARTMENT WATER HEATER | M S1 APARTMENT WATER HEATER | M S2 APARTMENT WATER HEATER | T SW APARTMENT WATER HEATER | T NW APARTMENT WATER HEATER | T SE APARTMENT WATER HEATER | T NE APARTMENT WATER HEATER | T N1 APARTMENT WATER HEATER | T N2 APARTMENT WATER HEATER | T S1 APARTMENT WATER HEATER | T S2 APARTMENT WATER HEATER |DaylightingReportMonthly
| Environment |CoilReportMonthly
| SPLIT GSW HEATING COIL | SPLIT GNW HEATING COIL | SPLIT OFFICE HEATING COIL | SPLIT GNE HEATING COIL | SPLIT GN1 HEATING COIL | SPLIT GN2 HEATING COIL | SPLIT GS1 HEATING COIL | SPLIT GS2 HEATING COIL | SPLIT MSW HEATING COIL | SPLIT MNW HEATING COIL | SPLIT MSE HEATING COIL | SPLIT MNE HEATING COIL | SPLIT MN1 HEATING COIL | SPLIT MN2 HEATING COIL | SPLIT MS1 HEATING COIL | SPLIT MS2 HEATING COIL | SPLIT TSW HEATING COIL | SPLIT TNW HEATING COIL | SPLIT TSE HEATING COIL | SPLIT TNE HEATING COIL | SPLIT TN1 HEATING COIL | SPLIT TN2 HEATING COIL | SPLIT TS1 HEATING COIL | SPLIT TS2 HEATING COIL | SPLIT GSW COOLING COIL | SPLIT GNW COOLING COIL | SPLIT OFFICE COOLING COIL | SPLIT GNE COOLING COIL | SPLIT GN1 COOLING COIL | SPLIT GN2 COOLING COIL | SPLIT GS1 COOLING COIL | SPLIT GS2 COOLING COIL | SPLIT MSW COOLING COIL | SPLIT MNW COOLING COIL | SPLIT MSE COOLING COIL | SPLIT MNE COOLING COIL | SPLIT MN1 COOLING COIL | SPLIT MN2 COOLING COIL | SPLIT MS1 COOLING COIL | SPLIT MS2 COOLING COIL | SPLIT TSW COOLING COIL | SPLIT TNW COOLING COIL | SPLIT TSE COOLING COIL | SPLIT TNE COOLING COIL | SPLIT TN1 COOLING COIL | SPLIT TN2 COOLING COIL | SPLIT TS1 COOLING COIL | SPLIT TS2 COOLING COIL |FanReportMonthly
| SPLIT GSW SUPPLY FAN | G SW APARTMENT ERV SUP FAN | G SW APARTMENT ERV EXH FAN | SPLIT GNW SUPPLY FAN | G NW APARTMENT ERV SUP FAN | G NW APARTMENT ERV EXH FAN | SPLIT OFFICE SUPPLY FAN | SPLIT GNE SUPPLY FAN | G NE APARTMENT ERV SUP FAN | G NE APARTMENT ERV EXH FAN | SPLIT GN1 SUPPLY FAN | G N1 APARTMENT ERV SUP FAN | G N1 APARTMENT ERV EXH FAN | SPLIT GN2 SUPPLY FAN | G N2 APARTMENT ERV SUP FAN | G N2 APARTMENT ERV EXH FAN | SPLIT GS1 SUPPLY FAN | G S1 APARTMENT ERV SUP FAN | G S1 APARTMENT ERV EXH FAN | SPLIT GS2 SUPPLY FAN | G S2 APARTMENT ERV SUP FAN | G S2 APARTMENT ERV EXH FAN | SPLIT MSW SUPPLY FAN | M SW APARTMENT ERV SUP FAN | M SW APARTMENT ERV EXH FAN | SPLIT MNW SUPPLY FAN | M NW APARTMENT ERV SUP FAN | M NW APARTMENT ERV EXH FAN | SPLIT MSE SUPPLY FAN | M SE APARTMENT ERV SUP FAN | M SE APARTMENT ERV EXH FAN | SPLIT MNE SUPPLY FAN | M NE APARTMENT ERV SUP FAN | M NE APARTMENT ERV EXH FAN | SPLIT MN1 SUPPLY FAN | M N1 APARTMENT ERV SUP FAN | M N1 APARTMENT ERV EXH FAN | SPLIT MN2 SUPPLY FAN | M N2 APARTMENT ERV SUP FAN | M N2 APARTMENT ERV EXH FAN | SPLIT MS1 SUPPLY FAN | M S1 APARTMENT ERV SUP FAN | M S1 APARTMENT ERV EXH FAN | SPLIT MS2 SUPPLY FAN | M S2 APARTMENT ERV SUP FAN | M S2 APARTMENT ERV EXH FAN | SPLIT TSW SUPPLY FAN | T SW APARTMENT ERV SUP FAN | T SW APARTMENT ERV EXH FAN | SPLIT TNW SUPPLY FAN | T NW APARTMENT ERV SUP FAN | T NW APARTMENT ERV EXH FAN | SPLIT TSE SUPPLY FAN | T SE APARTMENT ERV SUP FAN | T SE APARTMENT ERV EXH FAN | SPLIT TNE SUPPLY FAN | T NE APARTMENT ERV SUP FAN | T NE APARTMENT ERV EXH FAN | SPLIT TN1 SUPPLY FAN | T N1 APARTMENT ERV SUP FAN | T N1 APARTMENT ERV EXH FAN | SPLIT TN2 SUPPLY FAN | T N2 APARTMENT ERV SUP FAN | T N2 APARTMENT ERV EXH FAN | SPLIT TS1 SUPPLY FAN | T S1 APARTMENT ERV SUP FAN | T S1 APARTMENT ERV EXH FAN | SPLIT TS2 SUPPLY FAN | T S2 APARTMENT ERV SUP FAN | T S2 APARTMENT ERV EXH FAN |ZoneTemperatureOscillationReportMonthly
| G SW APARTMENT | G NW APARTMENT | OFFICE | G NE APARTMENT | G N1 APARTMENT | G N2 APARTMENT | G S1 APARTMENT | G S2 APARTMENT | M SW APARTMENT | M NW APARTMENT | M SE APARTMENT | M NE APARTMENT | M N1 APARTMENT | M N2 APARTMENT | M S1 APARTMENT | M S2 APARTMENT | T SW APARTMENT | T NW APARTMENT | T SE APARTMENT | T NE APARTMENT | T N1 APARTMENT | T N2 APARTMENT | T S1 APARTMENT | T S2 APARTMENT | T CORRIDOR | G CORRIDOR | M CORRIDOR |AirLoopSystemEnergyAndWaterUseMonthly
| SPLIT GSW | SPLIT GNW | SPLIT OFFICE | SPLIT GNE | SPLIT GN1 | SPLIT GN2 | SPLIT GS1 | SPLIT GS2 | SPLIT MSW | SPLIT MNW | SPLIT MSE | SPLIT MNE | SPLIT MN1 | SPLIT MN2 | SPLIT MS1 | SPLIT MS2 | SPLIT TSW | SPLIT TNW | SPLIT TSE | SPLIT TNE | SPLIT TN1 | SPLIT TN2 | SPLIT TS1 | SPLIT TS2 |AirLoopSystemComponentLoadsMonthly
| SPLIT GSW | SPLIT GNW | SPLIT OFFICE | SPLIT GNE | SPLIT GN1 | SPLIT GN2 | SPLIT GS1 | SPLIT GS2 | SPLIT MSW | SPLIT MNW | SPLIT MSE | SPLIT MNE | SPLIT MN1 | SPLIT MN2 | SPLIT MS1 | SPLIT MS2 | SPLIT TSW | SPLIT TNW | SPLIT TSE | SPLIT TNE | SPLIT TN1 | SPLIT TN2 | SPLIT TS1 | SPLIT TS2 |AirLoopSystemComponentEnergyUseMonthly
| SPLIT GSW | SPLIT GNW | SPLIT OFFICE | SPLIT GNE | SPLIT GN1 | SPLIT GN2 | SPLIT GS1 | SPLIT GS2 | SPLIT MSW | SPLIT MNW | SPLIT MSE | SPLIT MNE | SPLIT MN1 | SPLIT MN2 | SPLIT MS1 | SPLIT MS2 | SPLIT TSW | SPLIT TNW | SPLIT TSE | SPLIT TNE | SPLIT TN1 | SPLIT TN2 | SPLIT TS1 | SPLIT TS2 |MechanicalVentilationLoadsMonthly
| G SW APARTMENT | G NW APARTMENT | OFFICE | G NE APARTMENT | G N1 APARTMENT | G N2 APARTMENT | G S1 APARTMENT | G S2 APARTMENT | M SW APARTMENT | M NW APARTMENT | M SE APARTMENT | M NE APARTMENT | M N1 APARTMENT | M N2 APARTMENT | M S1 APARTMENT | M S2 APARTMENT | T SW APARTMENT | T NW APARTMENT | T SE APARTMENT | T NE APARTMENT | T N1 APARTMENT | T N2 APARTMENT | T S1 APARTMENT | T S2 APARTMENT |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 09:14:53
General| Value | |
| Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 09:14 |
| RunPeriod | RUNPERIOD 1 |
| Weather File | New Delhi-Safdarjung AP Delhi IND IWEC2 WMO#=421820 |
| Latitude [deg] | 28.58 |
| Longitude [deg] | 77.20 |
| Elevation [m] | 216.00 |
| Time Zone | 5.50 |
| North Axis Angle [deg] | 0.00 |
| Rotation for Appendix G [deg] | 0.00 |
| Hours Simulated [hrs] | 8760.00 |
| Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
| Gross Wall Area [m2] | 1542.04 | 564.80 | 206.22 | 564.80 | 206.22 |
| Above Ground Wall Area [m2] | 1542.04 | 564.80 | 206.22 | 564.80 | 206.22 |
| Window Opening Area [m2] | 306.92 | 112.97 | 43.82 | 112.97 | 37.16 |
| Gross Window-Wall Ratio [%] | 19.90 | 20.00 | 21.25 | 20.00 | 18.02 |
| Above Ground Window-Wall Ratio [%] | 19.90 | 20.00 | 21.25 | 20.00 | 18.02 |
| Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
| Gross Wall Area [m2] | 1501.17 | 564.80 | 185.79 | 564.80 | 185.79 |
| Above Ground Wall Area [m2] | 1501.17 | 564.80 | 185.79 | 564.80 | 185.79 |
| Window Opening Area [m2] | 300.26 | 112.97 | 37.16 | 112.97 | 37.16 |
| Gross Window-Wall Ratio [%] | 20.00 | 20.00 | 20.00 | 20.00 | 20.00 |
| Above Ground Window-Wall Ratio [%] | 20.00 | 20.00 | 20.00 | 20.00 | 20.00 |
| Total | |
| Gross Roof Area [m2] | 783.65 |
| Skylight Area [m2] | 0.00 |
| Skylight-Roof Ratio [%] | 0.00 |
| Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
| G SW APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 0.00 | 11.71 | 11.71 | 8.6918 | 35.30 | 6.6700 |
| G NW APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 0.00 | 11.71 | 11.71 | 8.6918 | 35.30 | 6.6700 |
| OFFICE | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 0.00 | 11.71 | 11.71 | 9.7532 | 18.58 | 6.6700 |
| G NE APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 0.00 | 11.71 | 11.71 | 8.6918 | 35.30 | 6.6700 |
| G N1 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 0.00 | 7.06 | 7.06 | 8.6918 | 35.30 | 6.6700 |
| G N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 0.00 | 7.06 | 7.06 | 8.6918 | 35.30 | 6.6700 |
| G S1 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 0.00 | 7.06 | 7.06 | 8.6918 | 35.30 | 6.6700 |
| G S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 0.00 | 7.06 | 7.06 | 8.6918 | 35.30 | 6.6700 |
| M SW APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 58.52 | 0.00 | 11.71 | 11.71 | 8.6918 | 35.30 | 6.6700 |
| M NW APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 58.52 | 0.00 | 11.71 | 11.71 | 8.6918 | 35.30 | 6.6700 |
| M SE APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 58.52 | 0.00 | 11.71 | 11.71 | 8.6918 | 35.30 | 6.6700 |
| M NE APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 58.52 | 0.00 | 11.71 | 11.71 | 8.6918 | 35.30 | 6.6700 |
| M N1 APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 35.30 | 0.00 | 7.06 | 7.06 | 8.6918 | 35.30 | 6.6700 |
| M N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 35.30 | 0.00 | 7.06 | 7.06 | 8.6918 | 35.30 | 6.6700 |
| M S1 APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 35.30 | 0.00 | 7.06 | 7.06 | 8.6918 | 35.30 | 6.6700 |
| M S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 35.30 | 0.00 | 7.06 | 7.06 | 8.6918 | 35.30 | 6.6700 |
| T SW APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 0.00 | 11.71 | 11.71 | 8.6918 | 35.30 | 6.6700 |
| T NW APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 0.00 | 11.71 | 11.71 | 8.6918 | 35.30 | 6.6700 |
| T SE APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 0.00 | 11.71 | 11.71 | 8.6918 | 35.30 | 6.6700 |
| T NE APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 0.00 | 11.71 | 11.71 | 8.6918 | 35.30 | 6.6700 |
| T N1 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 0.00 | 7.06 | 7.06 | 8.6918 | 35.30 | 6.6700 |
| T N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 0.00 | 7.06 | 7.06 | 8.6918 | 35.30 | 6.6700 |
| T S1 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 0.00 | 7.06 | 7.06 | 8.6918 | 35.30 | 6.6700 |
| T S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 0.00 | 7.06 | 7.06 | 8.6918 | 35.30 | 6.6700 |
| T CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 0.00 | 1.11 | 1.11 | 4.7725 | 18.58 | 0.0000 |
| G CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 0.00 | 3.32 | 3.32 | 4.7725 | 18.58 | 105.2565 |
| M CORRIDOR | 77.66 | No | Yes | 236.69 | 2.00 | 10.22 | 0.00 | 1.11 | 1.11 | 4.7725 | 18.58 | 0.0000 |
| Total | 3134.61 | 9553.84 | 1542.04 | 0.00 | 306.92 | 306.92 | 8.3333 | 31.67 | 8.6167 | |||
| Conditioned Total | 2823.98 | 8607.06 | 1501.17 | 0.00 | 300.26 | 300.26 | 8.7250 | 34.33 | 6.6700 | |||
| Unconditioned Total | 310.64 | 946.78 | 40.87 | 0.00 | 6.66 | 6.66 | 4.7725 | 18.58 | 26.3141 | |||
| Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
| G SW APARTMENT | 88.25 | Yes | Yes | 1.00 | G SW APARTMENT | GENERAL | G SW APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| G NW APARTMENT | 88.25 | Yes | Yes | 1.00 | G NW APARTMENT | GENERAL | G NW APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| OFFICE | 88.25 | Yes | Yes | 1.00 | OFFICE | GENERAL | OFFICE | 9.7532 | 18.58 | 6.6700 | |
| G NE APARTMENT | 88.25 | Yes | Yes | 1.00 | G NE APARTMENT | GENERAL | G NE APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| G N1 APARTMENT | 88.25 | Yes | Yes | 1.00 | G N1 APARTMENT | GENERAL | G N1 APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| G N2 APARTMENT | 88.25 | Yes | Yes | 1.00 | G N2 APARTMENT | GENERAL | G N2 APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| G S1 APARTMENT | 88.25 | Yes | Yes | 1.00 | G S1 APARTMENT | GENERAL | G S1 APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| G S2 APARTMENT | 88.25 | Yes | Yes | 1.00 | G S2 APARTMENT | GENERAL | G S2 APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| M SW APARTMENT | 88.25 | Yes | Yes | 2.00 | M SW APARTMENT | GENERAL | M SW APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| M NW APARTMENT | 88.25 | Yes | Yes | 2.00 | M NW APARTMENT | GENERAL | M NW APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| M SE APARTMENT | 88.25 | Yes | Yes | 2.00 | M SE APARTMENT | GENERAL | M SE APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| M NE APARTMENT | 88.25 | Yes | Yes | 2.00 | M NE APARTMENT | GENERAL | M NE APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| M N1 APARTMENT | 88.25 | Yes | Yes | 2.00 | M N1 APARTMENT | GENERAL | M N1 APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| M N2 APARTMENT | 88.25 | Yes | Yes | 2.00 | M N2 APARTMENT | GENERAL | M N2 APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| M S1 APARTMENT | 88.25 | Yes | Yes | 2.00 | M S1 APARTMENT | GENERAL | M S1 APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| M S2 APARTMENT | 88.25 | Yes | Yes | 2.00 | M S2 APARTMENT | GENERAL | M S2 APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| T SW APARTMENT | 88.25 | Yes | Yes | 1.00 | T SW APARTMENT | GENERAL | T SW APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| T NW APARTMENT | 88.25 | Yes | Yes | 1.00 | T NW APARTMENT | GENERAL | T NW APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| T SE APARTMENT | 88.25 | Yes | Yes | 1.00 | T SE APARTMENT | GENERAL | T SE APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| T NE APARTMENT | 88.25 | Yes | Yes | 1.00 | T NE APARTMENT | GENERAL | T NE APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| T N1 APARTMENT | 88.25 | Yes | Yes | 1.00 | T N1 APARTMENT | GENERAL | T N1 APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| T N2 APARTMENT | 88.25 | Yes | Yes | 1.00 | T N2 APARTMENT | GENERAL | T N2 APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| T S1 APARTMENT | 88.25 | Yes | Yes | 1.00 | T S1 APARTMENT | GENERAL | T S1 APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| T S2 APARTMENT | 88.25 | Yes | Yes | 1.00 | T S2 APARTMENT | GENERAL | T S2 APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| T CORRIDOR | 77.66 | No | Yes | 1.00 | T CORRIDOR | GENERAL | T CORRIDOR | 4.7725 | 18.58 | 0.0000 | |
| G CORRIDOR | 77.66 | No | Yes | 1.00 | G CORRIDOR | GENERAL | G CORRIDOR | 4.7725 | 18.58 | 105.2565 | |
| M CORRIDOR | 77.66 | No | Yes | 2.00 | M CORRIDOR | GENERAL | M CORRIDOR | 4.7725 | 18.58 | 0.0000 | |
| Total | 3134.61 | 8.3333 | 15.84 | 8.6167 | |||||||
| Conditioned Total | 2823.98 | 8.7250 | 17.17 | 6.6700 | |||||||
| Unconditioned Total | 310.64 | 4.7725 | 9.29 | 26.3141 | |||||||
| Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
| Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
| GENERAL | 3134.61 | 2823.98 | 310.64 | 0.00 | 6.2575 | 41.91 | 7.1145 |
| Total | 3134.61 | 2823.98 | 310.64 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 09:14:53
End Uses| Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
| Time of Peak | 10-JUN-17:10 | 03-JAN-06:00 | - | - | - | - | - | - | - | - | - | - | 01-JAN-07:10 |
| Heating | 0.00 | 12112.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Cooling | 36852.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Lighting | 5231.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment | 22609.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans | 10490.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems | 21545.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Total End Uses | 96729.73 | 12112.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
| Heating | General | 0.00 | 12112.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Cooling | General | 36852.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Lighting | LightsWired | 4887.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LightsPlugIn | 344.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment | MiscPlug | 18441.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| ElevatorLift | 4006.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| ElevatorLightsFan | 162.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| General | 10490.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems | Water Heater | 21545.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 09:14:53
Values gathered over 8760.00 hours| Source Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
| Heating | 0.00 | 8.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Cooling | 1278.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Lighting | 314.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Lighting | 158.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment | 1452.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans | 499.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems | 1120.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Total Source Energy End Use Components | 4824.29 | 8.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
| Heating | 0.00 | 2.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Cooling | 452.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Lighting | 111.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Lighting | 56.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment | 514.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans | 176.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems | 396.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Total Source Energy End Use Components | 1708.33 | 2.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
| Heating | 0.00 | 2.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Cooling | 407.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Lighting | 100.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Lighting | 50.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment | 463.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans | 159.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems | 357.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Total Source Energy End Use Components | 1539.04 | 2.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 09:14:53
ZoneHVAC:EnergyRecoveryVentilator| User-Specified Supply Air Flow Rate [m3/s] | User-Specified Exhaust Air Flow Rate [m3/s] | |
| G SW APARTMENT ERV | 0.025955 | 0.025955 |
| G NW APARTMENT ERV | 0.025955 | 0.025955 |
| G NE APARTMENT ERV | 0.025955 | 0.025955 |
| G N1 APARTMENT ERV | 0.025955 | 0.025955 |
| G N2 APARTMENT ERV | 0.025955 | 0.025955 |
| G S1 APARTMENT ERV | 0.025955 | 0.025955 |
| G S2 APARTMENT ERV | 0.025955 | 0.025955 |
| M SW APARTMENT ERV | 0.051909 | 0.051909 |
| M NW APARTMENT ERV | 0.051909 | 0.051909 |
| M SE APARTMENT ERV | 0.051909 | 0.051909 |
| M NE APARTMENT ERV | 0.051909 | 0.051909 |
| M N1 APARTMENT ERV | 0.051909 | 0.051909 |
| M N2 APARTMENT ERV | 0.051909 | 0.051909 |
| M S1 APARTMENT ERV | 0.051909 | 0.051909 |
| M S2 APARTMENT ERV | 0.051909 | 0.051909 |
| T SW APARTMENT ERV | 0.025955 | 0.025955 |
| T NW APARTMENT ERV | 0.025955 | 0.025955 |
| T SE APARTMENT ERV | 0.025955 | 0.025955 |
| T NE APARTMENT ERV | 0.025955 | 0.025955 |
| T N1 APARTMENT ERV | 0.025955 | 0.025955 |
| T N2 APARTMENT ERV | 0.025955 | 0.025955 |
| T S1 APARTMENT ERV | 0.025955 | 0.025955 |
| T S2 APARTMENT ERV | 0.025955 | 0.025955 |
| Design Size Maximum Flow Rate [m3/s] | |
| G SW APARTMENT ERV SUP FAN | 0.025955 |
| G SW APARTMENT ERV EXH FAN | 0.025955 |
| G NW APARTMENT ERV SUP FAN | 0.025955 |
| G NW APARTMENT ERV EXH FAN | 0.025955 |
| G NE APARTMENT ERV SUP FAN | 0.025955 |
| G NE APARTMENT ERV EXH FAN | 0.025955 |
| G N1 APARTMENT ERV SUP FAN | 0.025955 |
| G N1 APARTMENT ERV EXH FAN | 0.025955 |
| G N2 APARTMENT ERV SUP FAN | 0.025955 |
| G N2 APARTMENT ERV EXH FAN | 0.025955 |
| G S1 APARTMENT ERV SUP FAN | 0.025955 |
| G S1 APARTMENT ERV EXH FAN | 0.025955 |
| G S2 APARTMENT ERV SUP FAN | 0.025955 |
| G S2 APARTMENT ERV EXH FAN | 0.025955 |
| M SW APARTMENT ERV SUP FAN | 0.051909 |
| M SW APARTMENT ERV EXH FAN | 0.051909 |
| M NW APARTMENT ERV SUP FAN | 0.051909 |
| M NW APARTMENT ERV EXH FAN | 0.051909 |
| M SE APARTMENT ERV SUP FAN | 0.051909 |
| M SE APARTMENT ERV EXH FAN | 0.051909 |
| M NE APARTMENT ERV SUP FAN | 0.051909 |
| M NE APARTMENT ERV EXH FAN | 0.051909 |
| M N1 APARTMENT ERV SUP FAN | 0.051909 |
| M N1 APARTMENT ERV EXH FAN | 0.051909 |
| M N2 APARTMENT ERV SUP FAN | 0.051909 |
| M N2 APARTMENT ERV EXH FAN | 0.051909 |
| M S1 APARTMENT ERV SUP FAN | 0.051909 |
| M S1 APARTMENT ERV EXH FAN | 0.051909 |
| M S2 APARTMENT ERV SUP FAN | 0.051909 |
| M S2 APARTMENT ERV EXH FAN | 0.051909 |
| T SW APARTMENT ERV SUP FAN | 0.025955 |
| T SW APARTMENT ERV EXH FAN | 0.025955 |
| T NW APARTMENT ERV SUP FAN | 0.025955 |
| T NW APARTMENT ERV EXH FAN | 0.025955 |
| T SE APARTMENT ERV SUP FAN | 0.025955 |
| T SE APARTMENT ERV EXH FAN | 0.025955 |
| T NE APARTMENT ERV SUP FAN | 0.025955 |
| T NE APARTMENT ERV EXH FAN | 0.025955 |
| T N1 APARTMENT ERV SUP FAN | 0.025955 |
| T N1 APARTMENT ERV EXH FAN | 0.025955 |
| T N2 APARTMENT ERV SUP FAN | 0.025955 |
| T N2 APARTMENT ERV EXH FAN | 0.025955 |
| T S1 APARTMENT ERV SUP FAN | 0.025955 |
| T S1 APARTMENT ERV EXH FAN | 0.025955 |
| T S2 APARTMENT ERV SUP FAN | 0.025955 |
| T S2 APARTMENT ERV EXH FAN | 0.025955 |
| SPLIT GSW SUPPLY FAN | 0.391642 |
| SPLIT GNW SUPPLY FAN | 0.390454 |
| SPLIT OFFICE SUPPLY FAN | 0.448822 |
| SPLIT GNE SUPPLY FAN | 0.378963 |
| SPLIT GN1 SUPPLY FAN | 0.335744 |
| SPLIT GN2 SUPPLY FAN | 0.335511 |
| SPLIT GS1 SUPPLY FAN | 0.337360 |
| SPLIT GS2 SUPPLY FAN | 0.339932 |
| SPLIT MSW SUPPLY FAN | 0.880143 |
| SPLIT MNW SUPPLY FAN | 0.877648 |
| SPLIT MSE SUPPLY FAN | 0.851182 |
| SPLIT MNE SUPPLY FAN | 0.848711 |
| SPLIT MN1 SUPPLY FAN | 0.741082 |
| SPLIT MN2 SUPPLY FAN | 0.740520 |
| SPLIT MS1 SUPPLY FAN | 0.744260 |
| SPLIT MS2 SUPPLY FAN | 0.743694 |
| SPLIT TSW SUPPLY FAN | 0.497758 |
| SPLIT TNW SUPPLY FAN | 0.498833 |
| SPLIT TSE SUPPLY FAN | 0.475714 |
| SPLIT TNE SUPPLY FAN | 0.476777 |
| SPLIT TN1 SUPPLY FAN | 0.425755 |
| SPLIT TN2 SUPPLY FAN | 0.424990 |
| SPLIT TS1 SUPPLY FAN | 0.424862 |
| SPLIT TS2 SUPPLY FAN | 0.424098 |
| Design Size Nominal Supply Air Flow Rate [m3/s] | |
| G SW APARTMENT OA HEAT EXCHANGER | 0.025955 |
| G NW APARTMENT OA HEAT EXCHANGER | 0.025955 |
| G NE APARTMENT OA HEAT EXCHANGER | 0.025955 |
| G N1 APARTMENT OA HEAT EXCHANGER | 0.025955 |
| G N2 APARTMENT OA HEAT EXCHANGER | 0.025955 |
| G S1 APARTMENT OA HEAT EXCHANGER | 0.025955 |
| G S2 APARTMENT OA HEAT EXCHANGER | 0.025955 |
| M SW APARTMENT OA HEAT EXCHANGER | 0.051909 |
| M NW APARTMENT OA HEAT EXCHANGER | 0.051909 |
| M SE APARTMENT OA HEAT EXCHANGER | 0.051909 |
| M NE APARTMENT OA HEAT EXCHANGER | 0.051909 |
| M N1 APARTMENT OA HEAT EXCHANGER | 0.051909 |
| M N2 APARTMENT OA HEAT EXCHANGER | 0.051909 |
| M S1 APARTMENT OA HEAT EXCHANGER | 0.051909 |
| M S2 APARTMENT OA HEAT EXCHANGER | 0.051909 |
| T SW APARTMENT OA HEAT EXCHANGER | 0.025955 |
| T NW APARTMENT OA HEAT EXCHANGER | 0.025955 |
| T SE APARTMENT OA HEAT EXCHANGER | 0.025955 |
| T NE APARTMENT OA HEAT EXCHANGER | 0.025955 |
| T N1 APARTMENT OA HEAT EXCHANGER | 0.025955 |
| T N2 APARTMENT OA HEAT EXCHANGER | 0.025955 |
| T S1 APARTMENT OA HEAT EXCHANGER | 0.025955 |
| T S2 APARTMENT OA HEAT EXCHANGER | 0.025955 |
| Design Size Maximum Air Flow Rate [m3/s] | |
| G SW APARTMENT DIRECT AIR | 0.391642 |
| G NW APARTMENT DIRECT AIR | 0.390454 |
| OFFICE DIRECT AIR | 0.448822 |
| G NE APARTMENT DIRECT AIR | 0.378963 |
| G N1 APARTMENT DIRECT AIR | 0.335744 |
| G N2 APARTMENT DIRECT AIR | 0.335511 |
| G S1 APARTMENT DIRECT AIR | 0.337360 |
| G S2 APARTMENT DIRECT AIR | 0.339932 |
| M SW APARTMENT DIRECT AIR | 0.880143 |
| M NW APARTMENT DIRECT AIR | 0.877648 |
| M SE APARTMENT DIRECT AIR | 0.851182 |
| M NE APARTMENT DIRECT AIR | 0.848711 |
| M N1 APARTMENT DIRECT AIR | 0.741082 |
| M N2 APARTMENT DIRECT AIR | 0.740520 |
| M S1 APARTMENT DIRECT AIR | 0.744260 |
| M S2 APARTMENT DIRECT AIR | 0.743694 |
| T SW APARTMENT DIRECT AIR | 0.497758 |
| T NW APARTMENT DIRECT AIR | 0.498833 |
| T SE APARTMENT DIRECT AIR | 0.475714 |
| T NE APARTMENT DIRECT AIR | 0.476777 |
| T N1 APARTMENT DIRECT AIR | 0.425755 |
| T N2 APARTMENT DIRECT AIR | 0.424990 |
| T S1 APARTMENT DIRECT AIR | 0.424862 |
| T S2 APARTMENT DIRECT AIR | 0.424098 |
| Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
| SPLIT GSW | 0.391642 | 0.391642 | 0.391642 | 0.391642 | 0.391642 | 0.391642 | 1.00 | 1.00 | 0.391642 |
| SPLIT GNW | 0.390454 | 0.390454 | 0.390454 | 0.390454 | 0.390454 | 0.390454 | 1.00 | 1.00 | 0.390454 |
| SPLIT OFFICE | 0.448822 | 0.448822 | 0.448822 | 0.448822 | 0.448822 | 0.448822 | 1.00 | 1.00 | 0.448822 |
| SPLIT GNE | 0.378963 | 0.378963 | 0.378963 | 0.378963 | 0.378963 | 0.378963 | 1.00 | 1.000000 | 0.378963 |
| SPLIT GN1 | 0.335744 | 0.335744 | 0.335744 | 0.335744 | 0.335744 | 0.335744 | 1.00 | 1.00 | 0.335744 |
| SPLIT GN2 | 0.335511 | 0.335511 | 0.335511 | 0.335511 | 0.335511 | 0.335511 | 1.00 | 1.00 | 0.335511 |
| SPLIT GS1 | 0.337360 | 0.337360 | 0.337360 | 0.337360 | 0.337360 | 0.337360 | 1.00 | 1.000000 | 0.337360 |
| SPLIT GS2 | 0.339932 | 0.339932 | 0.339932 | 0.339932 | 0.339932 | 0.339932 | 1.00 | 1.00 | 0.339932 |
| SPLIT MSW | 0.880143 | 0.880143 | 0.880143 | 0.880143 | 0.880143 | 0.880143 | 1.00 | 1.00 | 0.880143 |
| SPLIT MNW | 0.877648 | 0.877648 | 0.877648 | 0.877648 | 0.877648 | 0.877648 | 1.00 | 1.00 | 0.877648 |
| SPLIT MSE | 0.851182 | 0.851182 | 0.851182 | 0.851182 | 0.851182 | 0.851182 | 1.00 | 1.00 | 0.851182 |
| SPLIT MNE | 0.848711 | 0.848711 | 0.848711 | 0.848711 | 0.848711 | 0.848711 | 1.00 | 1.00 | 0.848711 |
| SPLIT MN1 | 0.741082 | 0.741082 | 0.741082 | 0.741082 | 0.741082 | 0.741082 | 1.00 | 1.00 | 0.741082 |
| SPLIT MN2 | 0.740520 | 0.740520 | 0.740520 | 0.740520 | 0.740520 | 0.740520 | 1.00 | 1.00 | 0.740520 |
| SPLIT MS1 | 0.744260 | 0.744260 | 0.744260 | 0.744260 | 0.744260 | 0.744260 | 1.00 | 1.00 | 0.744260 |
| SPLIT MS2 | 0.743694 | 0.743694 | 0.743694 | 0.743694 | 0.743694 | 0.743694 | 1.00 | 1.00 | 0.743694 |
| SPLIT TSW | 0.497758 | 0.497758 | 0.497758 | 0.497758 | 0.497758 | 0.497758 | 1.00 | 1.00 | 0.497758 |
| SPLIT TNW | 0.498833 | 0.498833 | 0.498833 | 0.498833 | 0.498833 | 0.498833 | 1.00 | 1.00 | 0.498833 |
| SPLIT TSE | 0.475714 | 0.475714 | 0.475714 | 0.475714 | 0.475714 | 0.475714 | 1.00 | 1.00 | 0.475714 |
| SPLIT TNE | 0.476777 | 0.476777 | 0.476777 | 0.476777 | 0.476777 | 0.476777 | 1.00 | 1.00 | 0.476777 |
| SPLIT TN1 | 0.425755 | 0.425755 | 0.425755 | 0.425755 | 0.425755 | 0.425755 | 1.00 | 1.00 | 0.425755 |
| SPLIT TN2 | 0.424990 | 0.424990 | 0.424990 | 0.424990 | 0.424990 | 0.424990 | 1.00 | 1.00 | 0.424990 |
| SPLIT TS1 | 0.424862 | 0.424862 | 0.424862 | 0.424862 | 0.424862 | 0.424862 | 1.00 | 1.000000 | 0.424862 |
| SPLIT TS2 | 0.424098 | 0.424098 | 0.424098 | 0.424098 | 0.424098 | 0.424098 | 1.00 | 1.00 | 0.424098 |
| Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
| SPLIT GSW_OA_CONTROLLER | 0.391642 | 0.025955 |
| SPLIT GNW_OA_CONTROLLER | 0.390454 | 0.025955 |
| SPLIT OFFICE_OA_CONTROLLER | 0.448822 | 0.038106 |
| SPLIT GNE_OA_CONTROLLER | 0.378963 | 0.025955 |
| SPLIT GN1_OA_CONTROLLER | 0.335744 | 0.025955 |
| SPLIT GN2_OA_CONTROLLER | 0.335511 | 0.025955 |
| SPLIT GS1_OA_CONTROLLER | 0.337360 | 0.025955 |
| SPLIT GS2_OA_CONTROLLER | 0.339932 | 0.025955 |
| SPLIT MSW_OA_CONTROLLER | 0.880143 | 0.051909 |
| SPLIT MNW_OA_CONTROLLER | 0.877648 | 0.051909 |
| SPLIT MSE_OA_CONTROLLER | 0.851182 | 0.051909 |
| SPLIT MNE_OA_CONTROLLER | 0.848711 | 0.051909 |
| SPLIT MN1_OA_CONTROLLER | 0.741082 | 0.051909 |
| SPLIT MN2_OA_CONTROLLER | 0.740520 | 0.051909 |
| SPLIT MS1_OA_CONTROLLER | 0.744260 | 0.051909 |
| SPLIT MS2_OA_CONTROLLER | 0.743694 | 0.051909 |
| SPLIT TSW_OA_CONTROLLER | 0.497758 | 0.025955 |
| SPLIT TNW_OA_CONTROLLER | 0.498833 | 0.025955 |
| SPLIT TSE_OA_CONTROLLER | 0.475714 | 0.025955 |
| SPLIT TNE_OA_CONTROLLER | 0.476777 | 0.025955 |
| SPLIT TN1_OA_CONTROLLER | 0.425755 | 0.025955 |
| SPLIT TN2_OA_CONTROLLER | 0.424990 | 0.025955 |
| SPLIT TS1_OA_CONTROLLER | 0.424862 | 0.025955 |
| SPLIT TS2_OA_CONTROLLER | 0.424098 | 0.025955 |
| Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | Design Size Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
| SPLIT GSW_UNITARY_PACKAGE_DX | 0.391642 | 0.391642 | 0.391642 | 0.391642 | 6971.54 | 9183.72 | 40.00 | 1.00 |
| SPLIT GNW_UNITARY_PACKAGE_DX | 0.390454 | 0.390454 | 0.390454 | 0.390454 | 6918.18 | 9157.08 | 40.00 | 1.00 |
| SPLIT OFFICE_UNITARY_PACKAGE_DX | 0.448822 | 0.448822 | 0.448822 | 0.448822 | 7760.12 | 10670.50 | 40.00 | 1.00 |
| SPLIT GNE_UNITARY_PACKAGE_DX | 0.378963 | 0.378963 | 0.378963 | 0.378963 | 6733.38 | 8900.92 | 40.00 | 1.00 |
| SPLIT GN1_UNITARY_PACKAGE_DX | 0.335744 | 0.335744 | 0.335744 | 0.335744 | 6022.49 | 7937.48 | 40.00 | 1.00 |
| SPLIT GN2_UNITARY_PACKAGE_DX | 0.335511 | 0.335511 | 0.335511 | 0.335511 | 6018.72 | 7932.27 | 40.00 | 1.00 |
| SPLIT GS1_UNITARY_PACKAGE_DX | 0.337360 | 0.337360 | 0.337360 | 0.337360 | 6098.60 | 7973.63 | 40.00 | 1.00 |
| SPLIT GS2_UNITARY_PACKAGE_DX | 0.339932 | 0.339932 | 0.339932 | 0.339932 | 6140.62 | 8030.97 | 40.00 | 1.00 |
| SPLIT MSW_UNITARY_PACKAGE_DX | 0.880143 | 0.880143 | 0.880143 | 0.880143 | 15535.94 | 20526.71 | 40.00 | 1.00 |
| SPLIT MNW_UNITARY_PACKAGE_DX | 0.877648 | 0.877648 | 0.877648 | 0.877648 | 15438.65 | 20470.73 | 40.00 | 1.00 |
| SPLIT MSE_UNITARY_PACKAGE_DX | 0.851182 | 0.851182 | 0.851182 | 0.851182 | 15073.48 | 19881.10 | 40.00 | 1.00 |
| SPLIT MNE_UNITARY_PACKAGE_DX | 0.848711 | 0.848711 | 0.848711 | 0.848711 | 14972.01 | 19825.67 | 40.00 | 1.00 |
| SPLIT MN1_UNITARY_PACKAGE_DX | 0.741082 | 0.741082 | 0.741082 | 0.741082 | 13194.89 | 17426.36 | 40.00 | 1.00 |
| SPLIT MN2_UNITARY_PACKAGE_DX | 0.740520 | 0.740520 | 0.740520 | 0.740520 | 13185.83 | 17413.82 | 40.00 | 1.00 |
| SPLIT MS1_UNITARY_PACKAGE_DX | 0.744260 | 0.744260 | 0.744260 | 0.744260 | 13332.44 | 17497.52 | 40.00 | 1.00 |
| SPLIT MS2_UNITARY_PACKAGE_DX | 0.743694 | 0.743694 | 0.743694 | 0.743694 | 13323.46 | 17484.91 | 40.00 | 1.00 |
| SPLIT TSW_UNITARY_PACKAGE_DX | 0.497758 | 0.497758 | 0.497758 | 0.497758 | 8706.75 | 11549.36 | 40.00 | 1.00 |
| SPLIT TNW_UNITARY_PACKAGE_DX | 0.498833 | 0.498833 | 0.498833 | 0.498833 | 8704.26 | 11573.12 | 40.00 | 1.00 |
| SPLIT TSE_UNITARY_PACKAGE_DX | 0.475714 | 0.475714 | 0.475714 | 0.475714 | 8351.00 | 11057.92 | 40.00 | 1.00 |
| SPLIT TNE_UNITARY_PACKAGE_DX | 0.476777 | 0.476777 | 0.476777 | 0.476777 | 8347.04 | 11081.43 | 40.00 | 1.00 |
| SPLIT TN1_UNITARY_PACKAGE_DX | 0.425755 | 0.425755 | 0.425755 | 0.425755 | 7494.05 | 9944.01 | 40.00 | 1.00 |
| SPLIT TN2_UNITARY_PACKAGE_DX | 0.424990 | 0.424990 | 0.424990 | 0.424990 | 7481.64 | 9926.97 | 40.00 | 1.00 |
| SPLIT TS1_UNITARY_PACKAGE_DX | 0.424862 | 0.424862 | 0.424862 | 0.424862 | 7505.33 | 9924.27 | 40.00 | 1.00 |
| SPLIT TS2_UNITARY_PACKAGE_DX | 0.424098 | 0.424098 | 0.424098 | 0.424098 | 7493.00 | 9907.24 | 40.00 | 1.00 |
| Design Size Rated Air Flow Rate [m3/s] | Design Size Gross Rated Total Cooling Capacity [W] | Design Size Gross Rated Sensible Heat Ratio | |
| SPLIT GSW COOLING COIL | 0.391642 | 6971.54 | 0.800895 |
| SPLIT GNW COOLING COIL | 0.390454 | 6918.18 | 0.800487 |
| SPLIT OFFICE COOLING COIL | 0.448822 | 7760.12 | 0.800996 |
| SPLIT GNE COOLING COIL | 0.378963 | 6733.38 | 0.800527 |
| SPLIT GN1 COOLING COIL | 0.335744 | 6022.49 | 0.800285 |
| SPLIT GN2 COOLING COIL | 0.335511 | 6018.72 | 0.800262 |
| SPLIT GS1 COOLING COIL | 0.337360 | 6098.60 | 0.800663 |
| SPLIT GS2 COOLING COIL | 0.339932 | 6140.62 | 0.800908 |
| SPLIT MSW COOLING COIL | 0.880143 | 15535.94 | 0.800785 |
| SPLIT MNW COOLING COIL | 0.877648 | 15438.65 | 0.800973 |
| SPLIT MSE COOLING COIL | 0.851182 | 15073.48 | 0.800669 |
| SPLIT MNE COOLING COIL | 0.848711 | 14972.01 | 0.800994 |
| SPLIT MN1 COOLING COIL | 0.741082 | 13194.89 | 0.800816 |
| SPLIT MN2 COOLING COIL | 0.740520 | 13185.83 | 0.800792 |
| SPLIT MS1 COOLING COIL | 0.744260 | 13332.44 | 0.800740 |
| SPLIT MS2 COOLING COIL | 0.743694 | 13323.46 | 0.800711 |
| SPLIT TSW COOLING COIL | 0.497758 | 8706.75 | 0.800932 |
| SPLIT TNW COOLING COIL | 0.498833 | 8704.26 | 0.800783 |
| SPLIT TSE COOLING COIL | 0.475714 | 8351.00 | 0.800688 |
| SPLIT TNE COOLING COIL | 0.476777 | 8347.04 | 0.800628 |
| SPLIT TN1 COOLING COIL | 0.425755 | 7494.05 | 0.800760 |
| SPLIT TN2 COOLING COIL | 0.424990 | 7481.64 | 0.800712 |
| SPLIT TS1 COOLING COIL | 0.424862 | 7505.33 | 0.800516 |
| SPLIT TS2 COOLING COIL | 0.424098 | 7493.00 | 0.800462 |
| Design Size Nominal Capacity [W] | |
| SPLIT GSW HEATING COIL | 9183.72 |
| SPLIT GNW HEATING COIL | 9157.08 |
| SPLIT OFFICE HEATING COIL | 10670.50 |
| SPLIT GNE HEATING COIL | 8900.92 |
| SPLIT GN1 HEATING COIL | 7937.48 |
| SPLIT GN2 HEATING COIL | 7932.27 |
| SPLIT GS1 HEATING COIL | 7973.63 |
| SPLIT GS2 HEATING COIL | 8030.97 |
| SPLIT MSW HEATING COIL | 20526.71 |
| SPLIT MNW HEATING COIL | 20470.73 |
| SPLIT MSE HEATING COIL | 19881.10 |
| SPLIT MNE HEATING COIL | 19825.67 |
| SPLIT MN1 HEATING COIL | 17426.36 |
| SPLIT MN2 HEATING COIL | 17413.82 |
| SPLIT MS1 HEATING COIL | 17497.52 |
| SPLIT MS2 HEATING COIL | 17484.91 |
| SPLIT TSW HEATING COIL | 11549.36 |
| SPLIT TNW HEATING COIL | 11573.12 |
| SPLIT TSE HEATING COIL | 11057.92 |
| SPLIT TNE HEATING COIL | 11081.43 |
| SPLIT TN1 HEATING COIL | 9944.01 |
| SPLIT TN2 HEATING COIL | 9926.97 |
| SPLIT TS1 HEATING COIL | 9924.27 |
| SPLIT TS2 HEATING COIL | 9907.24 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 09:14:53
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other Surfaces| None |
| Possible Shadow Receivers | |
| G SWALL SWA | GWINDOW1 S SWA | |
| G WWALL SWA | GWINDOW1 W SWA | |
| G NWALL NWA | GWINDOW1 N NWA | |
| G WWALL NWA | GWINDOW1 W NWA | |
| G SWALL SEA | GWINDOW1 S SEA | |
| G EWALL SEA | GWINDOW1 E SEA | |
| G NWALL NEA | GWINDOW1 N NEA | |
| G EWALL NEA | GWINDOW1 E NEA | |
| G NWALL N1A | GWINDOW1 N N1A | |
| G NWALL N2A | GWINDOW1 N N2A | |
| G SWALL S1A | GWINDOW1 S S1A | |
| G SWALL S2A | GWINDOW1 S S2A | |
| M WWALL SWA | MWINDOW1 W SWA | |
| M SWALL SWA | MWINDOW1 S SWA | |
| M NWALL NWA | MWINDOW1 N NWA | |
| M WWALL NWA | MWINDOW1 W NWA | |
| M EWALL SEA | MWINDOW1 E SEA | |
| M SWALL SEA | MWINDOW1 S SEA | |
| M NWALL NEA | MWINDOW1 N NEA | |
| M EWALL NEA | MWINDOW1 E NEA | |
| M NWALL N1A | MWINDOW1 N N1A | |
| M NWALL N2A | MWINDOW1 N N2A | |
| M SWALL S1A | MWINDOW1 S S1A | |
| M SWALL S2A | MWINDOW1 S S2A | |
| T WWALL SWA | TWINDOW1 W SWA | |
| T SWALL SWA | TWINDOW1 S SWA | |
| T NWALL NWA | TWINDOW1 N NWA | |
| T WWALL NWA | TWINDOW1 W NWA | |
| T EWALL SEA | TWINDOW1 E SEA | |
| T SWALL SEA | TWINDOW1 S SEA | |
| T NWALL NEA | TWINDOW1 N NEA | |
| T EWALL NEA | TWINDOW1 E NEA | |
| T NWALL N1A | TWINDOW1 N N1A | |
| T NWALL N2A | TWINDOW1 N N2A | |
| T SWALL S1A | TWINDOW1 S S1A | |
| T SWALL S2A | TWINDOW1 S S2A | |
| T EWALL C | TWINDOW14 | |
| G EWALL C | ENTRANCE DOOR | |
| M EWALL C | MWINDOW14 | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 09:14:53
Time Not Meeting the Adaptive Comfort Models during Occupied Hours| ASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 09:14:53
Version| Version ID | |
| 1 | 22.1 |
| #TimeSteps | Minutes per TimeStep {minutes} | |
| 1 | 6 | 10 |
| Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
| 1 | 1 | 20 | 2 | 8 |
| Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
| 1 | Yes | Yes | No | No | Yes | No |
| Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
| 1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
| Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
| 1 | 0.556 | 0.556 |
| Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
| 1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
| Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
| 1 | 25.10 | 19.60 | 14.50 | 13.40 | 17.00 | 22.40 | 29.10 | 33.00 | 33.60 | 31.70 | 30.00 | 28.70 |
| Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
| 1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
| Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
| 1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
| Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
| 1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
| Normal | Daylighting {dimensionless} | |
| 1 | 1.000 | 1.000 |
| Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
| 1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
| Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
| 1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
| Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
| 1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
| Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
| 1 | New Delhi-Safdarjung AP Delhi IND IWEC2 WMO#=421820 | 28.58 | 77.20 | 5.50 | 216.00 | 98757 | 1.1738 |
| Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
| 1 | Correlation | NA | 24.84 | 20.20 | NA |
| Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
| 1 | ApartmentMidRise | 0.000 | City | 4.00000E-002 | 0.40000 | FullExterior | 25 | 6 |
| Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
| 1 | TARP |
| Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
| 1 | TARP |
| Value {Anisotropic} | |
| 1 | Anisotropic |
| Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
| 1 | ThirdOrderBackwardDifference |
| Simulation {Yes/No} | Carbon Dioxide Concentration | |
| 1 | No | N/A |
| Simulation {Yes/No} | Generic Contaminant Concentration | |
| 1 | No | N/A |
| Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
| 1 | No | N/A | N/A | N/A |
| Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
| 1 | RegulaFalsi |
| Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
| 1 | 0.330 | 460.000 | 6.500000E-003 |
| Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
| 1 | LowerLeftCorner | Clockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
| Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
| 1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
| Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
| 1 | 0 | 0 | 0 |
| Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
| 1 | 27 | 243 | 39 |
| Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
| 1 | G SW APARTMENT | 0.0 | 0.00 | 0.00 | 0.00 | 5.79 | 3.81 | 1.52 | 1 | 1 | 1 | 0.00 | 11.58 | 0.00 | 7.62 | 0.00 | 3.05 | 3.05 | 268.97 | TARP | TARP | 88.25 | 58.52 | 46.82 | 11.71 | 6 | 2 | 0 | Yes |
| 2 | G NW APARTMENT | 0.0 | 0.00 | 9.30 | 0.00 | 5.79 | 13.11 | 1.52 | 1 | 1 | 1 | 0.00 | 11.58 | 9.30 | 16.92 | 0.00 | 3.05 | 3.05 | 268.97 | TARP | TARP | 88.25 | 58.52 | 46.82 | 11.71 | 6 | 2 | 0 | Yes |
| 3 | OFFICE | 0.0 | 34.75 | 0.00 | 0.00 | 40.54 | 3.81 | 1.52 | 1 | 1 | 1 | 34.75 | 46.33 | 0.00 | 7.62 | 0.00 | 3.05 | 3.05 | 268.97 | TARP | TARP | 88.25 | 58.52 | 46.82 | 11.71 | 6 | 2 | 0 | Yes |
| 4 | G NE APARTMENT | 0.0 | 34.75 | 9.30 | 0.00 | 40.54 | 13.11 | 1.52 | 1 | 1 | 1 | 34.75 | 46.33 | 9.30 | 16.92 | 0.00 | 3.05 | 3.05 | 268.97 | TARP | TARP | 88.25 | 58.52 | 46.82 | 11.71 | 6 | 2 | 0 | Yes |
| 5 | G N1 APARTMENT | 0.0 | 11.58 | 9.30 | 0.00 | 17.37 | 13.11 | 1.52 | 1 | 1 | 1 | 11.58 | 23.16 | 9.30 | 16.92 | 0.00 | 3.05 | 3.05 | 268.97 | TARP | TARP | 88.25 | 35.30 | 28.24 | 7.06 | 6 | 1 | 0 | Yes |
| 6 | G N2 APARTMENT | 0.0 | 23.16 | 9.30 | 0.00 | 28.95 | 13.11 | 1.52 | 1 | 1 | 1 | 23.16 | 34.75 | 9.30 | 16.92 | 0.00 | 3.05 | 3.05 | 268.97 | TARP | TARP | 88.25 | 35.30 | 28.24 | 7.06 | 6 | 1 | 0 | Yes |
| 7 | G S1 APARTMENT | 0.0 | 11.58 | 0.00 | 0.00 | 17.37 | 3.81 | 1.52 | 1 | 1 | 1 | 11.58 | 23.16 | 0.00 | 7.62 | 0.00 | 3.05 | 3.05 | 268.97 | TARP | TARP | 88.25 | 35.30 | 28.24 | 7.06 | 6 | 1 | 0 | Yes |
| 8 | G S2 APARTMENT | 0.0 | 23.16 | 0.00 | 0.00 | 28.95 | 3.81 | 1.52 | 1 | 1 | 1 | 23.16 | 34.75 | 0.00 | 7.62 | 0.00 | 3.05 | 3.05 | 268.97 | TARP | TARP | 88.25 | 35.30 | 28.24 | 7.06 | 6 | 1 | 0 | Yes |
| 9 | M SW APARTMENT | 0.0 | 0.00 | 0.00 | 3.05 | 5.79 | 3.81 | 4.57 | 1 | 1 | 2 | 0.00 | 11.58 | 0.00 | 7.62 | 3.05 | 6.10 | 3.05 | 268.97 | TARP | TARP | 88.25 | 58.52 | 46.82 | 11.71 | 6 | 2 | 0 | Yes |
| 10 | M NW APARTMENT | 0.0 | 0.00 | 9.30 | 3.05 | 5.79 | 13.11 | 4.57 | 1 | 1 | 2 | 0.00 | 11.58 | 9.30 | 16.92 | 3.05 | 6.10 | 3.05 | 268.97 | TARP | TARP | 88.25 | 58.52 | 46.82 | 11.71 | 6 | 2 | 0 | Yes |
| 11 | M SE APARTMENT | 0.0 | 34.75 | 0.00 | 3.05 | 40.54 | 3.81 | 4.57 | 1 | 1 | 2 | 34.75 | 46.33 | 0.00 | 7.62 | 3.05 | 6.10 | 3.05 | 268.97 | TARP | TARP | 88.25 | 58.52 | 46.82 | 11.71 | 6 | 2 | 0 | Yes |
| 12 | M NE APARTMENT | 0.0 | 34.75 | 9.30 | 3.05 | 40.54 | 13.11 | 4.57 | 1 | 1 | 2 | 34.75 | 46.33 | 9.30 | 16.92 | 3.05 | 6.10 | 3.05 | 268.97 | TARP | TARP | 88.25 | 58.52 | 46.82 | 11.71 | 6 | 2 | 0 | Yes |
| 13 | M N1 APARTMENT | 0.0 | 11.58 | 9.30 | 3.05 | 17.37 | 13.11 | 4.57 | 1 | 1 | 2 | 11.58 | 23.16 | 9.30 | 16.92 | 3.05 | 6.10 | 3.05 | 268.97 | TARP | TARP | 88.25 | 35.30 | 28.24 | 7.06 | 6 | 1 | 0 | Yes |
| 14 | M N2 APARTMENT | 0.0 | 23.16 | 9.30 | 3.05 | 28.95 | 13.11 | 4.57 | 1 | 1 | 2 | 23.16 | 34.75 | 9.30 | 16.92 | 3.05 | 6.10 | 3.05 | 268.97 | TARP | TARP | 88.25 | 35.30 | 28.24 | 7.06 | 6 | 1 | 0 | Yes |
| 15 | M S1 APARTMENT | 0.0 | 11.58 | 0.00 | 3.05 | 17.37 | 3.81 | 4.57 | 1 | 1 | 2 | 11.58 | 23.16 | 0.00 | 7.62 | 3.05 | 6.10 | 3.05 | 268.97 | TARP | TARP | 88.25 | 35.30 | 28.24 | 7.06 | 6 | 1 | 0 | Yes |
| 16 | M S2 APARTMENT | 0.0 | 23.16 | 0.00 | 3.05 | 28.95 | 3.81 | 4.57 | 1 | 1 | 2 | 23.16 | 34.75 | 0.00 | 7.62 | 3.05 | 6.10 | 3.05 | 268.97 | TARP | TARP | 88.25 | 35.30 | 28.24 | 7.06 | 6 | 1 | 0 | Yes |
| 17 | T SW APARTMENT | 0.0 | 0.00 | 0.00 | 9.14 | 5.79 | 3.81 | 10.67 | 1 | 1 | 1 | 0.00 | 11.58 | 0.00 | 7.62 | 9.14 | 12.19 | 3.05 | 268.97 | TARP | TARP | 88.25 | 58.52 | 46.82 | 11.71 | 6 | 2 | 0 | Yes |
| 18 | T NW APARTMENT | 0.0 | 0.00 | 9.30 | 9.14 | 5.79 | 13.11 | 10.67 | 1 | 1 | 1 | 0.00 | 11.58 | 9.30 | 16.92 | 9.14 | 12.19 | 3.05 | 268.97 | TARP | TARP | 88.25 | 58.52 | 46.82 | 11.71 | 6 | 2 | 0 | Yes |
| 19 | T SE APARTMENT | 0.0 | 34.75 | 0.00 | 9.14 | 40.54 | 3.81 | 10.67 | 1 | 1 | 1 | 34.75 | 46.33 | 0.00 | 7.62 | 9.14 | 12.19 | 3.05 | 268.97 | TARP | TARP | 88.25 | 58.52 | 46.82 | 11.71 | 6 | 2 | 0 | Yes |
| 20 | T NE APARTMENT | 0.0 | 34.75 | 9.30 | 9.14 | 40.54 | 13.11 | 10.67 | 1 | 1 | 1 | 34.75 | 46.33 | 9.30 | 16.92 | 9.14 | 12.19 | 3.05 | 268.97 | TARP | TARP | 88.25 | 58.52 | 46.82 | 11.71 | 6 | 2 | 0 | Yes |
| 21 | T N1 APARTMENT | 0.0 | 11.58 | 9.30 | 9.14 | 17.37 | 13.11 | 10.67 | 1 | 1 | 1 | 11.58 | 23.16 | 9.30 | 16.92 | 9.14 | 12.19 | 3.05 | 268.97 | TARP | TARP | 88.25 | 35.30 | 28.24 | 7.06 | 6 | 1 | 0 | Yes |
| 22 | T N2 APARTMENT | 0.0 | 23.16 | 9.30 | 9.14 | 28.95 | 13.11 | 10.67 | 1 | 1 | 1 | 23.16 | 34.75 | 9.30 | 16.92 | 9.14 | 12.19 | 3.05 | 268.97 | TARP | TARP | 88.25 | 35.30 | 28.24 | 7.06 | 6 | 1 | 0 | Yes |
| 23 | T S1 APARTMENT | 0.0 | 11.58 | 0.00 | 9.14 | 17.37 | 3.81 | 10.67 | 1 | 1 | 1 | 11.58 | 23.16 | 0.00 | 7.62 | 9.14 | 12.19 | 3.05 | 268.97 | TARP | TARP | 88.25 | 35.30 | 28.24 | 7.06 | 6 | 1 | 0 | Yes |
| 24 | T S2 APARTMENT | 0.0 | 23.16 | 0.00 | 9.14 | 28.95 | 3.81 | 10.67 | 1 | 1 | 1 | 23.16 | 34.75 | 0.00 | 7.62 | 9.14 | 12.19 | 3.05 | 268.97 | TARP | TARP | 88.25 | 35.30 | 28.24 | 7.06 | 6 | 1 | 0 | Yes |
| 25 | T CORRIDOR | 0.0 | 0.00 | 7.62 | 9.14 | 23.16 | 8.46 | 10.67 | 1 | 1 | 1 | 0.00 | 46.33 | 7.62 | 9.30 | 9.14 | 12.19 | 3.05 | 236.69 | TARP | TARP | 77.66 | 10.22 | 9.10 | 1.11 | 12 | 1 | 0 | Yes |
| 26 | G CORRIDOR | 0.0 | 0.00 | 7.62 | 0.00 | 23.16 | 8.46 | 1.52 | 1 | 1 | 1 | 0.00 | 46.33 | 7.62 | 9.30 | 0.00 | 3.05 | 3.05 | 236.69 | TARP | TARP | 77.66 | 10.22 | 6.90 | 3.32 | 12 | 1 | 0 | Yes |
| 27 | M CORRIDOR | 0.0 | 0.00 | 7.62 | 3.05 | 23.16 | 8.46 | 4.57 | 1 | 1 | 2 | 0.00 | 46.33 | 7.62 | 9.30 | 3.05 | 6.10 | 3.05 | 236.69 | TARP | TARP | 77.66 | 10.22 | 9.10 | 1.11 | 12 | 1 | 0 | Yes |
| Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
| 1 | G SW APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 2 | G NW APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 3 | OFFICE | 88.25 | 4.7 | 18.581 | 5.382E-002 | 9.753 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 16.423 | No |
| 4 | G NE APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 5 | G N1 APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 6 | G N2 APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 7 | G S1 APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 8 | G S2 APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 9 | M SW APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 10 | M NW APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 11 | M SE APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 12 | M NE APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 13 | M N1 APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 14 | M N2 APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 15 | M S1 APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 16 | M S2 APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 17 | T SW APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 18 | T NW APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 19 | T SE APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 20 | T NE APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 21 | T N1 APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 22 | T N2 APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 23 | T S1 APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 24 | T S2 APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 25 | T CORRIDOR | 77.66 | 4.2 | 18.579 | 5.382E-002 | 4.772 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 4.772 | No |
| 26 | G CORRIDOR | 77.66 | 4.2 | 18.579 | 5.382E-002 | 4.772 | 105.256 | 0.000 | 0.000 | 0.000 | 0.000 | 110.029 | No |
| 27 | M CORRIDOR | 77.66 | 4.2 | 18.579 | 5.382E-002 | 4.772 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 4.772 | No |
| Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | |
| 1 | OCCUP_GSW | OCC_APT_SCH_WORKING_FAMILY | G SW APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 3 |
| 2 | OCCUP_GNW | OCC_APT_SCH_STAY_HOME_FAMILY | G NW APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 1 | 3 |
| 3 | OCCUP_OFFICE | OCC_OFF_W_SB_SCH | OFFICE | 88.25 | 4.7 | 4.7 | 5.382E-002 | 18.581 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 5 |
| 4 | OCCUP_GNE | OCC_APT_SCH_STAY_HOME_FAMILY | G NE APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 1 | 3 |
| 5 | OCCUP_GN1 | OCC_APT_SCH_STAY_HOME_FAMILY | G N1 APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 1 | 3 |
| 6 | OCCUP_GN2 | OCC_APT_SCH_STAY_HOME_FAMILY | G N2 APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 1 | 3 |
| 7 | OCCUP_GS1 | OCC_APT_SCH_WORKING_FAMILY | G S1 APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 3 |
| 8 | OCCUP_GS2 | OCC_APT_SCH_WORKING_FAMILY | G S2 APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 3 |
| 9 | OCCUP_MSW | OCC_APT_SCH_WORKING_FAMILY | M SW APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 3 |
| 10 | OCCUP_MNW | OCC_APT_SCH_STAY_HOME_FAMILY | M NW APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 1 | 3 |
| 11 | OCCUP_MSE | OCC_APT_SCH_WORKING_FAMILY | M SE APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 3 |
| 12 | OCCUP_MNE | OCC_APT_SCH_STAY_HOME_FAMILY | M NE APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 1 | 3 |
| 13 | OCCUP_MN1 | OCC_APT_SCH_STAY_HOME_FAMILY | M N1 APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 1 | 3 |
| 14 | OCCUP_MN2 | OCC_APT_SCH_STAY_HOME_FAMILY | M N2 APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 1 | 3 |
| 15 | OCCUP_MS1 | OCC_APT_SCH_WORKING_FAMILY | M S1 APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 3 |
| 16 | OCCUP_MS2 | OCC_APT_SCH_WORKING_FAMILY | M S2 APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 3 |
| 17 | OCCUP_TSW | OCC_APT_SCH_WORKING_FAMILY | T SW APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 3 |
| 18 | OCCUP_TNW | OCC_APT_SCH_STAY_HOME_FAMILY | T NW APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 1 | 3 |
| 19 | OCCUP_TSE | OCC_APT_SCH_WORKING_FAMILY | T SE APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 3 |
| 20 | OCCUP_TNE | OCC_APT_SCH_STAY_HOME_FAMILY | T NE APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 1 | 3 |
| 21 | OCCUP_TN1 | OCC_APT_SCH_STAY_HOME_FAMILY | T N1 APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 1 | 3 |
| 22 | OCCUP_TN2 | OCC_APT_SCH_STAY_HOME_FAMILY | T N2 APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 1 | 3 |
| 23 | OCCUP_TS1 | OCC_APT_SCH_WORKING_FAMILY | T S1 APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 3 |
| 24 | OCCUP_TS2 | OCC_APT_SCH_WORKING_FAMILY | T S2 APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 3 |
| 25 | OCCUP_T CORRIDOR | OCC_APT_SCH_CORRIDOR | T CORRIDOR | 77.66 | 4.2 | 4.2 | 5.382E-002 | 18.579 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 1 | 4 |
| 26 | OCCUP_G CORRIDOR | OCC_APT_SCH_CORRIDOR | G CORRIDOR | 77.66 | 4.2 | 4.2 | 5.382E-002 | 18.579 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 1 | 4 |
| 27 | OCCUP_M CORRIDOR | OCC_APT_SCH_CORRIDOR | M CORRIDOR | 77.66 | 4.2 | 4.2 | 5.382E-002 | 18.579 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 1 | 4 |
| Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
| 1 | LIGHTING_HARDWIRED_GSW | LTG_SCH_APARTMENT_HARDWIRED | G SW APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 2 | LIGHTING_HARDWIRED_GNW | LTG_SCH_APARTMENT_HARDWIRED | G NW APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 3 | LIGHTING_HARDWIRED_OFFICE | LTG_SCH_OFFICE | OFFICE | 88.25 | 4.7 | 860.710 | 9.753 | 181.220 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 860.710 |
| 4 | LIGHTING_HARDWIRED_GNE | LTG_SCH_APARTMENT_HARDWIRED | G NE APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 5 | LIGHTING_HARDWIRED_GN1 | LTG_SCH_APARTMENT_HARDWIRED | G N1 APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 6 | LIGHTING_HARDWIRED_GN2 | LTG_SCH_APARTMENT_HARDWIRED | G N2 APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 7 | LIGHTING_HARDWIRED_GS1 | LTG_SCH_APARTMENT_HARDWIRED | G S1 APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 8 | LIGHTING_HARDWIRED_GS2 | LTG_SCH_APARTMENT_HARDWIRED | G S2 APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 9 | LIGHTING_HARDWIRED_MSW | LTG_SCH_APARTMENT_HARDWIRED | M SW APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 10 | LIGHTING_HARDWIRED_MNW | LTG_SCH_APARTMENT_HARDWIRED | M NW APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 11 | LIGHTING_HARDWIRED_MSE | LTG_SCH_APARTMENT_HARDWIRED | M SE APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 12 | LIGHTING_HARDWIRED_MNE | LTG_SCH_APARTMENT_HARDWIRED | M NE APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 13 | LIGHTING_HARDWIRED_MN1 | LTG_SCH_APARTMENT_HARDWIRED | M N1 APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 14 | LIGHTING_HARDWIRED_MN2 | LTG_SCH_APARTMENT_HARDWIRED | M N2 APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 15 | LIGHTING_HARDWIRED_MS1 | LTG_SCH_APARTMENT_HARDWIRED | M S1 APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 16 | LIGHTING_HARDWIRED_MS2 | LTG_SCH_APARTMENT_HARDWIRED | M S2 APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 17 | LIGHTING_HARDWIRED_TSW | LTG_SCH_APARTMENT_HARDWIRED | T SW APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 18 | LIGHTING_HARDWIRED_TNW | LTG_SCH_APARTMENT_HARDWIRED | T NW APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 19 | LIGHTING_HARDWIRED_TSE | LTG_SCH_APARTMENT_HARDWIRED | T SE APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 20 | LIGHTING_HARDWIRED_TNE | LTG_SCH_APARTMENT_HARDWIRED | T NE APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 21 | LIGHTING_HARDWIRED_TN1 | LTG_SCH_APARTMENT_HARDWIRED | T N1 APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 22 | LIGHTING_HARDWIRED_TN2 | LTG_SCH_APARTMENT_HARDWIRED | T N2 APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 23 | LIGHTING_HARDWIRED_TS1 | LTG_SCH_APARTMENT_HARDWIRED | T S1 APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 24 | LIGHTING_HARDWIRED_TS2 | LTG_SCH_APARTMENT_HARDWIRED | T S2 APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 25 | LIGHTING_HARDWIRED_GC | LTG_SCH_CORRIDOR | G CORRIDOR | 77.66 | 4.2 | 370.628 | 4.772 | 88.667 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 370.628 |
| 26 | LIGHTING_HARDWIRED_MC | LTG_SCH_CORRIDOR | M CORRIDOR | 77.66 | 4.2 | 370.628 | 4.772 | 88.667 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 370.628 |
| 27 | LIGHTING_HARDWIRED_TC | LTG_SCH_CORRIDOR | T CORRIDOR | 77.66 | 4.2 | 370.628 | 4.772 | 88.667 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 370.628 |
| 28 | LIGHTING_PLUGIN_GSW | LTG_SCH_APARTMENT_PLUGIN | G SW APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| 29 | LIGHTING_PLUGIN_GNW | LTG_SCH_APARTMENT_PLUGIN | G NW APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| 30 | LIGHTING_PLUGIN_GNE | LTG_SCH_APARTMENT_PLUGIN | G NE APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| 31 | LIGHTING_PLUGIN_GN1 | LTG_SCH_APARTMENT_PLUGIN | G N1 APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| 32 | LIGHTING_PLUGIN_GN2 | LTG_SCH_APARTMENT_PLUGIN | G N2 APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| 33 | LIGHTING_PLUGIN_GS1 | LTG_SCH_APARTMENT_PLUGIN | G S1 APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| 34 | LIGHTING_PLUGIN_GS2 | LTG_SCH_APARTMENT_PLUGIN | G S2 APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| 35 | LIGHTING_PLUGIN_MSW | LTG_SCH_APARTMENT_PLUGIN | M SW APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| 36 | LIGHTING_PLUGIN_MNW | LTG_SCH_APARTMENT_PLUGIN | M NW APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| 37 | LIGHTING_PLUGIN_MSE | LTG_SCH_APARTMENT_PLUGIN | M SE APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| 38 | LIGHTING_PLUGIN_MNE | LTG_SCH_APARTMENT_PLUGIN | M NE APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| 39 | LIGHTING_PLUGIN_MN1 | LTG_SCH_APARTMENT_PLUGIN | M N1 APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| 40 | LIGHTING_PLUGIN_MN2 | LTG_SCH_APARTMENT_PLUGIN | M N2 APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| 41 | LIGHTING_PLUGIN_MS1 | LTG_SCH_APARTMENT_PLUGIN | M S1 APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| 42 | LIGHTING_PLUGIN_MS2 | LTG_SCH_APARTMENT_PLUGIN | M S2 APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| 43 | LIGHTING_PLUGIN_TSW | LTG_SCH_APARTMENT_PLUGIN | T SW APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| 44 | LIGHTING_PLUGIN_TNW | LTG_SCH_APARTMENT_PLUGIN | T NW APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| 45 | LIGHTING_PLUGIN_TSE | LTG_SCH_APARTMENT_PLUGIN | T SE APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| 46 | LIGHTING_PLUGIN_TNE | LTG_SCH_APARTMENT_PLUGIN | T NE APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| 47 | LIGHTING_PLUGIN_TN1 | LTG_SCH_APARTMENT_PLUGIN | T N1 APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| 48 | LIGHTING_PLUGIN_TN2 | LTG_SCH_APARTMENT_PLUGIN | T N2 APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| 49 | LIGHTING_PLUGIN_TS1 | LTG_SCH_APARTMENT_PLUGIN | T S1 APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| 50 | LIGHTING_PLUGIN_TS2 | LTG_SCH_APARTMENT_PLUGIN | T S2 APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
| 1 | PLUG_GSW | EQP_APT_SCH | G SW APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 2 | PLUG_GNW | EQP_APT_SCH | G NW APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 3 | PLUG_OFFICE | EQP_OFF_SCH | OFFICE | 88.25 | 4.7 | 588.623 | 6.670 | 123.933 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 588.623 |
| 4 | PLUG_GNE | EQP_APT_SCH | G NE APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 5 | PLUG_GN1 | EQP_APT_SCH | G N1 APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 6 | PLUG_GN2 | EQP_APT_SCH | G N2 APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 7 | PLUG_GS1 | EQP_APT_SCH | G S1 APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 8 | PLUG_GS2 | EQP_APT_SCH | G S2 APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 9 | PLUG_MSW | EQP_APT_SCH | M SW APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 10 | PLUG_MNW | EQP_APT_SCH | M NW APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 11 | PLUG_MSE | EQP_APT_SCH | M SE APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 12 | PLUG_MNE | EQP_APT_SCH | M NE APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 13 | PLUG_MN1 | EQP_APT_SCH | M N1 APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 14 | PLUG_MN2 | EQP_APT_SCH | M N2 APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 15 | PLUG_MS1 | EQP_APT_SCH | M S1 APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 16 | PLUG_MS2 | EQP_APT_SCH | M S2 APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 17 | PLUG_TSW | EQP_APT_SCH | T SW APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 18 | PLUG_TNW | EQP_APT_SCH | T NW APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 19 | PLUG_TSE | EQP_APT_SCH | T SE APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 20 | PLUG_TNE | EQP_APT_SCH | T NE APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 21 | PLUG_TN1 | EQP_APT_SCH | T N1 APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 22 | PLUG_TN2 | EQP_APT_SCH | T N2 APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 23 | PLUG_TS1 | EQP_APT_SCH | T S1 APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 24 | PLUG_TS2 | EQP_APT_SCH | T S2 APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 25 | G CORRIDOR_ELEVATORS_EQUIP | BLDG_ELEVATORS | G CORRIDOR | 77.66 | 4.2 | 8012.150 | 103.170 | 1916.782 | 0.000 | 0.000 | 0.950 | 5.000E-002 | ElevatorLift | 961.458 | 4006.075 |
| 26 | ELEVATORS_LIGHTS_FAN | ELEV_LIGHT_FAN_SCH_24_7 | G CORRIDOR | 77.66 | 4.2 | 162.000 | 2.086 | 38.756 | 0.000 | 0.000 | 0.950 | 5.000E-002 | ElevatorLightsFan | 162.000 | 162.000 |
| Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
| 1 | PolygonClipping | Periodic | 20 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
| Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
| 1 | WaterHeater:Mixed | G SW APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.496 | 0.7729 |
| 2 | WaterHeater:Mixed | G NW APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.496 | 0.7729 |
| 3 | WaterHeater:Mixed | G NE APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.496 | 0.7729 |
| 4 | WaterHeater:Mixed | G N1 APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.496 | 0.7729 |
| 5 | WaterHeater:Mixed | G N2 APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.496 | 0.7729 |
| 6 | WaterHeater:Mixed | G S1 APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.496 | 0.7729 |
| 7 | WaterHeater:Mixed | G S2 APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.496 | 0.7729 |
| 8 | WaterHeater:Mixed | M SW APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.498 | 0.7911 |
| 9 | WaterHeater:Mixed | M NW APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.498 | 0.7911 |
| 10 | WaterHeater:Mixed | M SE APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.498 | 0.7911 |
| 11 | WaterHeater:Mixed | M NE APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.498 | 0.7911 |
| 12 | WaterHeater:Mixed | M N1 APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.498 | 0.7911 |
| 13 | WaterHeater:Mixed | M N2 APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.498 | 0.7911 |
| 14 | WaterHeater:Mixed | M S1 APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.498 | 0.7911 |
| 15 | WaterHeater:Mixed | M S2 APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.498 | 0.7911 |
| 16 | WaterHeater:Mixed | T SW APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.496 | 0.7729 |
| 17 | WaterHeater:Mixed | T NW APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.496 | 0.7729 |
| 18 | WaterHeater:Mixed | T SE APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.496 | 0.7729 |
| 19 | WaterHeater:Mixed | T NE APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.496 | 0.7729 |
| 20 | WaterHeater:Mixed | T N1 APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.496 | 0.7729 |
| 21 | WaterHeater:Mixed | T N2 APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.496 | 0.7729 |
| 22 | WaterHeater:Mixed | T S1 APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.496 | 0.7729 |
| 23 | WaterHeater:Mixed | T S2 APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.496 | 0.7729 |
| Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
| 1 | G SWALL SWA | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 2 | GWINDOW1 S SWA | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 3 | G WWALL SWA | 0 | 154.67 | 58.21 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 4 | GWINDOW1 W SWA | 0 | 154.67 | 58.21 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 5 | G NIWALL SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 6 | G EIWALL SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 7 | G GFLOOR SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 8 | G CEILIN SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 9 | G INTERNALMASS SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 10 | G NWALL NWA | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 11 | GWINDOW1 N NWA | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 12 | G WWALL NWA | 0 | 154.67 | 58.21 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 13 | GWINDOW1 W NWA | 0 | 154.67 | 58.21 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 14 | G SIWALL NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 15 | G EIWALL NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 16 | G GFLOOR NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 17 | G CEILIN NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 18 | G INTERNALMASS NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 19 | G SWALL SEA | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 20 | GWINDOW1 S SEA | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 21 | G EWALL SEA | 0 | 154.67 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 22 | GWINDOW1 E SEA | 0 | 154.67 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 23 | G NIWALL SEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 24 | iz-G EIWALL S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 25 | G GFLOOR SEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 26 | G CEILIN SEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 27 | G INTERNALMASS SEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 28 | G NWALL NEA | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 29 | GWINDOW1 N NEA | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 30 | G EWALL NEA | 0 | 154.67 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 31 | GWINDOW1 E NEA | 0 | 154.67 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 32 | G SIWALL NEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 33 | iz-G EIWALL N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 34 | G GFLOOR NEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 35 | G CEILIN NEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 36 | G INTERNALMASS NEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 37 | G NWALL N1A | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 3 | No | No |
| 38 | GWINDOW1 N N1A | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 2 | No | No |
| 39 | G SIWALL N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 40 | G EIWALL N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 41 | iz-G EIWALL NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 42 | G GFLOOR N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 43 | G CEILIN N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 44 | G INTERNALMASS N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 45 | G NWALL N2A | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 3 | No | No |
| 46 | GWINDOW1 N N2A | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 2 | No | No |
| 47 | G SIWALL N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 48 | G EIWALL N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 49 | iz-G EIWALL N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 50 | G GFLOOR N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 51 | G CEILIN N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 52 | G INTERNALMASS N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 53 | G SWALL S1A | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 3 | No | No |
| 54 | GWINDOW1 S S1A | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 2 | No | No |
| 55 | G NIWALL S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 56 | G EIWALL S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 57 | iz-G EIWALL SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 58 | G GFLOOR S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 59 | G CEILIN S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 60 | G INTERNALMASS S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 61 | G SWALL S2A | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 3 | No | No |
| 62 | GWINDOW1 S S2A | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 2 | No | No |
| 63 | G NIWALL S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 64 | G EIWALL S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 65 | iz-G EIWALL S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 66 | G GFLOOR S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 67 | G CEILIN S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 68 | G INTERNALMASS S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 69 | M WWALL SWA | 0 | 154.67 | 58.21 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 70 | MWINDOW1 W SWA | 0 | 154.67 | 58.21 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 71 | M SWALL SWA | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 72 | MWINDOW1 S SWA | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 73 | M NIWALL SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 74 | M EIWALL SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 75 | M GFLOOR SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 76 | M CEILIN SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 77 | M INTERNALMASS SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 78 | M NWALL NWA | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 79 | MWINDOW1 N NWA | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 80 | M WWALL NWA | 0 | 154.67 | 58.21 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 81 | MWINDOW1 W NWA | 0 | 154.67 | 58.21 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 82 | M SIWALL NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 83 | M EIWALL NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 84 | M GFLOOR NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 85 | M CEILIN NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 86 | M INTERNALMASS NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 87 | M EWALL SEA | 0 | 154.67 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 88 | MWINDOW1 E SEA | 0 | 154.67 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 89 | M SWALL SEA | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 90 | MWINDOW1 S SEA | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 91 | M NIWALL SEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 92 | iz-M EIWALL S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 93 | M GFLOOR SEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 94 | M CEILIN SEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 95 | M INTERNALMASS SEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 96 | M NWALL NEA | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 97 | MWINDOW1 N NEA | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 98 | M EWALL NEA | 0 | 154.67 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 99 | MWINDOW1 E NEA | 0 | 154.67 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 100 | M SIWALL NEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 101 | iz-M EIWALL N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 102 | M GFLOOR NEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 103 | M CEILIN NEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 104 | M INTERNALMASS NEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 105 | M NWALL N1A | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 3 | No | No |
| 106 | MWINDOW1 N N1A | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 2 | No | No |
| 107 | M SIWALL N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 108 | M EIWALL N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 109 | iz-M EIWALL NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 110 | M GFLOOR N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 111 | M CEILIN N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 112 | M INTERNALMASS N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 113 | M NWALL N2A | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 3 | No | No |
| 114 | MWINDOW1 N N2A | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 2 | No | No |
| 115 | M SIWALL N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 116 | M EIWALL N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 117 | iz-M EIWALL N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 118 | M GFLOOR N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 119 | M CEILIN N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 120 | M INTERNALMASS N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 121 | M SWALL S1A | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 3 | No | No |
| 122 | MWINDOW1 S S1A | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 2 | No | No |
| 123 | M NIWALL S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 124 | M EIWALL S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 125 | iz-M EIWALL SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 126 | M GFLOOR S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 127 | M CEILIN S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 128 | M INTERNALMASS S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 129 | M SWALL S2A | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 3 | No | No |
| 130 | MWINDOW1 S S2A | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 2 | No | No |
| 131 | M NIWALL S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 132 | M EIWALL S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 133 | iz-M EIWALL S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 134 | M GFLOOR S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 135 | M CEILIN S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 136 | M INTERNALMASS S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 137 | T WWALL SWA | 0 | 154.67 | 58.21 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 138 | TWINDOW1 W SWA | 0 | 154.67 | 58.21 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 139 | T SWALL SWA | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 140 | TWINDOW1 S SWA | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 141 | T NIWALL SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 142 | T EIWALL SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 143 | T GFLOOR SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 144 | T ROOF SWA | 0 | 783.65 | 155.90 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 145 | T INTERNALMASS SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 146 | T NWALL NWA | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 147 | TWINDOW1 N NWA | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 148 | T WWALL NWA | 0 | 154.67 | 58.21 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 149 | TWINDOW1 W NWA | 0 | 154.67 | 58.21 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 150 | T SIWALL NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 151 | T EIWALL NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 152 | T GFLOOR NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 153 | T ROOF NWA | 0 | 783.65 | 155.90 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 154 | T INTERNALMASS NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 155 | T EWALL SEA | 0 | 154.67 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 156 | TWINDOW1 E SEA | 0 | 154.67 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 157 | T SWALL SEA | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 158 | TWINDOW1 S SEA | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 159 | T NIWALL SEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 160 | iz-T EIWALL S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 161 | T GFLOOR SEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 162 | T ROOF SEA | 0 | 783.65 | 155.90 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 163 | T INTERNALMASS SEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 164 | T NWALL NEA | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 165 | TWINDOW1 N NEA | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 166 | T EWALL NEA | 0 | 154.67 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 167 | TWINDOW1 E NEA | 0 | 154.67 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 168 | T SIWALL NEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 169 | iz-T EIWALL N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 170 | T GFLOOR NEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 171 | T ROOF NEA | 0 | 783.65 | 155.90 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 172 | T INTERNALMASS NEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 173 | T NWALL N1A | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 3 | No | No |
| 174 | TWINDOW1 N N1A | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 2 | No | No |
| 175 | T SIWALL N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 176 | T EIWALL N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 177 | iz-T EIWALL NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 178 | T GFLOOR N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 179 | T ROOF N1A | 0 | 783.65 | 155.90 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 180 | T INTERNALMASS N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 181 | T NWALL N2A | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 3 | No | No |
| 182 | TWINDOW1 N N2A | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 2 | No | No |
| 183 | T SIWALL N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 184 | T EIWALL N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 185 | iz-T EIWALL N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 186 | T GFLOOR N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 187 | T ROOF N2A | 0 | 783.65 | 155.90 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 188 | T INTERNALMASS N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 189 | T SWALL S1A | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 3 | No | No |
| 190 | TWINDOW1 S S1A | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 2 | No | No |
| 191 | T NIWALL S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 192 | T EIWALL S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 193 | iz-T EIWALL SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 194 | T GFLOOR S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 195 | T ROOF S1A | 0 | 783.65 | 155.90 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 196 | T INTERNALMASS S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 197 | T SWALL S2A | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 3 | No | No |
| 198 | TWINDOW1 S S2A | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 2 | No | No |
| 199 | T NIWALL S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 200 | T EIWALL S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 201 | iz-T EIWALL S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 202 | T GFLOOR S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 203 | T ROOF S2A | 0 | 783.65 | 155.90 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 204 | T INTERNALMASS S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 205 | T WWALL C | 0 | 154.67 | 58.21 | 12.19 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 3 | No | No |
| 206 | T EWALL C | 0 | 154.67 | 123.02 | 12.19 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 3 | No | No |
| 207 | TWINDOW14 | 0 | 154.67 | 123.02 | 12.19 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 2 | No | No |
| 208 | iz-T NIWALL SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 209 | iz-T NIWALL S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 210 | iz-T NIWALL S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 211 | iz-T NIWALL SEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 212 | iz-T SIWALL NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 213 | iz-T SIWALL N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 214 | iz-T SIWALL N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 215 | iz-T SIWALL NEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 216 | T FLOOR C | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 217 | T ROOF C | 0 | 783.65 | 155.90 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 218 | G WWALL C | 0 | 154.67 | 58.21 | 12.19 | 0 | 3.05 | 3.35 | 3.24 | 0.32 | 4 | No | No |
| 219 | G EWALL C | 0 | 154.67 | 123.02 | 12.19 | 0 | 3.05 | 3.35 | 3.24 | 0.32 | 4 | No | No |
| 220 | ENTRANCE DOOR | 0 | 154.67 | 123.02 | 12.19 | 0 | 3.05 | 3.35 | 3.24 | 0.32 | 1 | No | No |
| 221 | iz-G NIWALL SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.32 | 0 | No | No |
| 222 | iz-G NIWALL S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.32 | 0 | No | No |
| 223 | iz-G NIWALL S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.32 | 0 | No | No |
| 224 | iz-G NIWALL SEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.32 | 0 | No | No |
| 225 | iz-G SIWALL NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.32 | 0 | No | No |
| 226 | iz-G SIWALL N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.32 | 0 | No | No |
| 227 | iz-G SIWALL N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.32 | 0 | No | No |
| 228 | iz-G SIWALL NEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.32 | 0 | No | No |
| 229 | G FLOOR C | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.32 | 0 | No | No |
| 230 | G CEILING C | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.32 | 0 | No | No |
| 231 | M WWALL C | 0 | 154.67 | 58.21 | 12.19 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 4 | No | No |
| 232 | M EWALL C | 0 | 154.67 | 123.02 | 12.19 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 3 | No | No |
| 233 | MWINDOW14 | 0 | 154.67 | 123.02 | 12.19 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 2 | No | No |
| 234 | iz-M NIWALL SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 235 | iz-M NIWALL S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 236 | iz-M NIWALL S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 237 | iz-M NIWALL SEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 238 | iz-M SIWALL NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 239 | iz-M SIWALL N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 240 | iz-M SIWALL N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 241 | iz-M SIWALL NEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 242 | M FLOOR C | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 243 | M CEILING C | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
| 1 | INFIL_GSW | INF_APT_SCH | G SW APARTMENT | 88.25 | 2.5 | 6.000E-002 | 6.799E-004 | 1.025E-003 | 0.803 | 0.000 | 0.000 | 0.224 | 0.000 |
| 2 | INFIL_GNW | INF_APT_SCH | G NW APARTMENT | 88.25 | 2.5 | 6.000E-002 | 6.799E-004 | 1.025E-003 | 0.803 | 0.000 | 0.000 | 0.224 | 0.000 |
| 3 | INFIL_OFFICE | INF_OFF_SCH | OFFICE | 88.25 | 4.7 | 6.000E-002 | 6.799E-004 | 1.025E-003 | 0.803 | 0.000 | 0.000 | 0.224 | 0.000 |
| 4 | INFIL_GNE | INF_APT_SCH | G NE APARTMENT | 88.25 | 2.5 | 6.000E-002 | 6.799E-004 | 1.025E-003 | 0.803 | 0.000 | 0.000 | 0.224 | 0.000 |
| 5 | INFIL_GN1 | INF_APT_SCH | G N1 APARTMENT | 88.25 | 2.5 | 3.619E-002 | 4.101E-004 | 1.025E-003 | 0.484 | 0.000 | 0.000 | 0.224 | 0.000 |
| 6 | INFIL_GN2 | INF_APT_SCH | G N2 APARTMENT | 88.25 | 2.5 | 3.619E-002 | 4.101E-004 | 1.025E-003 | 0.484 | 0.000 | 0.000 | 0.224 | 0.000 |
| 7 | INFIL_GS1 | INF_APT_SCH | G S1 APARTMENT | 88.25 | 2.5 | 3.619E-002 | 4.101E-004 | 1.025E-003 | 0.484 | 0.000 | 0.000 | 0.224 | 0.000 |
| 8 | INFIL_GS2 | INF_APT_SCH | G S2 APARTMENT | 88.25 | 2.5 | 3.619E-002 | 4.101E-004 | 1.025E-003 | 0.484 | 0.000 | 0.000 | 0.224 | 0.000 |
| 9 | INFIL_MSW | INF_APT_SCH | M SW APARTMENT | 88.25 | 2.5 | 6.000E-002 | 6.799E-004 | 1.025E-003 | 0.803 | 0.000 | 0.000 | 0.224 | 0.000 |
| 10 | INFIL_MNW | INF_APT_SCH | M NW APARTMENT | 88.25 | 2.5 | 6.000E-002 | 6.799E-004 | 1.025E-003 | 0.803 | 0.000 | 0.000 | 0.224 | 0.000 |
| 11 | INFIL_MSE | INF_APT_SCH | M SE APARTMENT | 88.25 | 2.5 | 6.000E-002 | 6.799E-004 | 1.025E-003 | 0.803 | 0.000 | 0.000 | 0.224 | 0.000 |
| 12 | INFIL_MNE | INF_APT_SCH | M NE APARTMENT | 88.25 | 2.5 | 6.000E-002 | 6.799E-004 | 1.025E-003 | 0.803 | 0.000 | 0.000 | 0.224 | 0.000 |
| 13 | INFIL_MN1 | INF_APT_SCH | M N1 APARTMENT | 88.25 | 2.5 | 3.619E-002 | 4.101E-004 | 1.025E-003 | 0.484 | 0.000 | 0.000 | 0.224 | 0.000 |
| 14 | INFIL_MN2 | INF_APT_SCH | M N2 APARTMENT | 88.25 | 2.5 | 3.619E-002 | 4.101E-004 | 1.025E-003 | 0.484 | 0.000 | 0.000 | 0.224 | 0.000 |
| 15 | INFIL_MS1 | INF_APT_SCH | M S1 APARTMENT | 88.25 | 2.5 | 3.619E-002 | 4.101E-004 | 1.025E-003 | 0.484 | 0.000 | 0.000 | 0.224 | 0.000 |
| 16 | INFIL_MS2 | INF_APT_SCH | M S2 APARTMENT | 88.25 | 2.5 | 3.619E-002 | 4.101E-004 | 1.025E-003 | 0.484 | 0.000 | 0.000 | 0.224 | 0.000 |
| 17 | INFIL_SW | INF_APT_SCH | T SW APARTMENT | 88.25 | 2.5 | 6.000E-002 | 6.799E-004 | 4.088E-004 | 0.803 | 0.000 | 0.000 | 0.224 | 0.000 |
| 18 | INFIL_NW | INF_APT_SCH | T NW APARTMENT | 88.25 | 2.5 | 6.000E-002 | 6.799E-004 | 4.088E-004 | 0.803 | 0.000 | 0.000 | 0.224 | 0.000 |
| 19 | INFIL_SE | INF_APT_SCH | T SE APARTMENT | 88.25 | 2.5 | 6.000E-002 | 6.799E-004 | 4.088E-004 | 0.803 | 0.000 | 0.000 | 0.224 | 0.000 |
| 20 | INFIL_NE | INF_APT_SCH | T NE APARTMENT | 88.25 | 2.5 | 6.000E-002 | 6.799E-004 | 4.088E-004 | 0.803 | 0.000 | 0.000 | 0.224 | 0.000 |
| 21 | INFIL_TN1 | INF_APT_SCH | T N1 APARTMENT | 88.25 | 2.5 | 3.619E-002 | 4.101E-004 | 2.929E-004 | 0.484 | 0.000 | 0.000 | 0.224 | 0.000 |
| 22 | INFIL_TN2 | INF_APT_SCH | T N2 APARTMENT | 88.25 | 2.5 | 3.619E-002 | 4.101E-004 | 2.929E-004 | 0.484 | 0.000 | 0.000 | 0.224 | 0.000 |
| 23 | INFIL_TS1 | INF_APT_SCH | T S1 APARTMENT | 88.25 | 2.5 | 3.619E-002 | 4.101E-004 | 2.929E-004 | 0.484 | 0.000 | 0.000 | 0.224 | 0.000 |
| 24 | INFIL_TS2 | INF_APT_SCH | T S2 APARTMENT | 88.25 | 2.5 | 3.619E-002 | 4.101E-004 | 2.929E-004 | 0.484 | 0.000 | 0.000 | 0.224 | 0.000 |
| 25 | INFIL_GC | INF_COR_SCH | G CORRIDOR | 77.66 | 4.2 | 1.048E-002 | 1.349E-004 | 1.025E-003 | 0.159 | 0.000 | 0.000 | 0.224 | 0.000 |
| 26 | DOOR_INFIL_GC | INFIL_DOOR_OPENING_SCH | G CORRIDOR | 77.66 | 4.2 | 0.521 | 6.703E-003 | 5.094E-002 | 7.917 | 1.000 | 0.000 | 0.000 | 0.000 |
| 27 | INFIL_MC | INF_COR_SCH | M CORRIDOR | 77.66 | 4.2 | 1.048E-002 | 1.349E-004 | 1.025E-003 | 0.159 | 0.000 | 0.000 | 0.224 | 0.000 |
| 28 | INFIL_TC | INF_COR_SCH | T CORRIDOR | 77.66 | 4.2 | 1.048E-002 | 1.349E-004 | 1.192E-004 | 0.159 | 0.000 | 0.000 | 0.224 | 0.000 |
| Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
| 1 | G SW APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | G SW APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 2 | G NW APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | G NW APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 3 | G NE APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | G NE APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 4 | G N1 APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | G N1 APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 5 | G N2 APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | G N2 APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 6 | G S1 APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | G S1 APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 7 | G S2 APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | G S2 APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 8 | M SW APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | M SW APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 9 | M NW APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | M NW APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 10 | M SE APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | M SE APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 11 | M NE APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | M NE APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 12 | M N1 APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | M N1 APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 13 | M N2 APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | M N2 APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 14 | M S1 APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | M S1 APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 15 | M S2 APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | M S2 APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 16 | T SW APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | T SW APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 17 | T NW APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | T NW APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 18 | T SE APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | T SE APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 19 | T NE APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | T NE APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 20 | T N1 APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | T N1 APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 21 | T N2 APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | T N2 APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 22 | T S1 APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | T S1 APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 23 | T S2 APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | T S2 APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| Simple | |
| 1 | Simple |
| Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
| 1 | G SW APARTMENT | Mixing/Well-Stirred |
| 2 | G NW APARTMENT | Mixing/Well-Stirred |
| 3 | OFFICE | Mixing/Well-Stirred |
| 4 | G NE APARTMENT | Mixing/Well-Stirred |
| 5 | G N1 APARTMENT | Mixing/Well-Stirred |
| 6 | G N2 APARTMENT | Mixing/Well-Stirred |
| 7 | G S1 APARTMENT | Mixing/Well-Stirred |
| 8 | G S2 APARTMENT | Mixing/Well-Stirred |
| 9 | M SW APARTMENT | Mixing/Well-Stirred |
| 10 | M NW APARTMENT | Mixing/Well-Stirred |
| 11 | M SE APARTMENT | Mixing/Well-Stirred |
| 12 | M NE APARTMENT | Mixing/Well-Stirred |
| 13 | M N1 APARTMENT | Mixing/Well-Stirred |
| 14 | M N2 APARTMENT | Mixing/Well-Stirred |
| 15 | M S1 APARTMENT | Mixing/Well-Stirred |
| 16 | M S2 APARTMENT | Mixing/Well-Stirred |
| 17 | T SW APARTMENT | Mixing/Well-Stirred |
| 18 | T NW APARTMENT | Mixing/Well-Stirred |
| 19 | T SE APARTMENT | Mixing/Well-Stirred |
| 20 | T NE APARTMENT | Mixing/Well-Stirred |
| 21 | T N1 APARTMENT | Mixing/Well-Stirred |
| 22 | T N2 APARTMENT | Mixing/Well-Stirred |
| 23 | T S1 APARTMENT | Mixing/Well-Stirred |
| 24 | T S2 APARTMENT | Mixing/Well-Stirred |
| 25 | T CORRIDOR | Mixing/Well-Stirred |
| 26 | G CORRIDOR | Mixing/Well-Stirred |
| 27 | M CORRIDOR | Mixing/Well-Stirred |
| No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
| 1 | NoMultizoneOrDistribution |
| Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
| 1 | 1.000 | 1.000 | 1.000 | 1.000 |
| Value | |
| 1 | 6 |
| Sizing Factor ID | Value | |
| 1 | Global | 1.2000 |
| 2 | Zone G SW APARTMENT | 1.2000 |
| 3 | Zone G NW APARTMENT | 1.2000 |
| 4 | Zone OFFICE | 1.2000 |
| 5 | Zone G NE APARTMENT | 1.2000 |
| 6 | Zone G N1 APARTMENT | 1.2000 |
| 7 | Zone G N2 APARTMENT | 1.2000 |
| 8 | Zone G S1 APARTMENT | 1.2000 |
| 9 | Zone G S2 APARTMENT | 1.2000 |
| 10 | Zone M SW APARTMENT | 1.2000 |
| 11 | Zone M NW APARTMENT | 1.2000 |
| 12 | Zone M SE APARTMENT | 1.2000 |
| 13 | Zone M NE APARTMENT | 1.2000 |
| 14 | Zone M N1 APARTMENT | 1.2000 |
| 15 | Zone M N2 APARTMENT | 1.2000 |
| 16 | Zone M S1 APARTMENT | 1.2000 |
| 17 | Zone M S2 APARTMENT | 1.2000 |
| 18 | Zone T SW APARTMENT | 1.2000 |
| 19 | Zone T NW APARTMENT | 1.2000 |
| 20 | Zone T SE APARTMENT | 1.2000 |
| 21 | Zone T NE APARTMENT | 1.2000 |
| 22 | Zone T N1 APARTMENT | 1.2000 |
| 23 | Zone T N2 APARTMENT | 1.2000 |
| 24 | Zone T S1 APARTMENT | 1.2000 |
| 25 | Zone T S2 APARTMENT | 1.2000 |
| Sizing Factor ID | Value | |
| 1 | Global | 1.2000 |
| 2 | Zone G SW APARTMENT | 1.2000 |
| 3 | Zone G NW APARTMENT | 1.2000 |
| 4 | Zone OFFICE | 1.2000 |
| 5 | Zone G NE APARTMENT | 1.2000 |
| 6 | Zone G N1 APARTMENT | 1.2000 |
| 7 | Zone G N2 APARTMENT | 1.2000 |
| 8 | Zone G S1 APARTMENT | 1.2000 |
| 9 | Zone G S2 APARTMENT | 1.2000 |
| 10 | Zone M SW APARTMENT | 1.2000 |
| 11 | Zone M NW APARTMENT | 1.2000 |
| 12 | Zone M SE APARTMENT | 1.2000 |
| 13 | Zone M NE APARTMENT | 1.2000 |
| 14 | Zone M N1 APARTMENT | 1.2000 |
| 15 | Zone M N2 APARTMENT | 1.2000 |
| 16 | Zone M S1 APARTMENT | 1.2000 |
| 17 | Zone M S2 APARTMENT | 1.2000 |
| 18 | Zone T SW APARTMENT | 1.2000 |
| 19 | Zone T NW APARTMENT | 1.2000 |
| 20 | Zone T SE APARTMENT | 1.2000 |
| 21 | Zone T NE APARTMENT | 1.2000 |
| 22 | Zone T N1 APARTMENT | 1.2000 |
| 23 | Zone T N2 APARTMENT | 1.2000 |
| 24 | Zone T S1 APARTMENT | 1.2000 |
| 25 | Zone T S2 APARTMENT | 1.2000 |
| Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
| 1 | G SW APARTMENT | Cooling | 4492.97652 | 5391.57182 | 0.32637 | 0.39164 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 19:00:00 | 38.21700 | 9.15158E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 2 | G SW APARTMENT | Heating | 584.92251 | 701.90701 | 2.58564E-002 | 3.10277E-002 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 6.30000 | 6.07234E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 3 | G NW APARTMENT | Cooling | 4479.71826 | 5375.66191 | 0.32538 | 0.39045 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 19:00:00 | 38.21700 | 9.15158E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 4 | G NW APARTMENT | Heating | 463.60168 | 556.32202 | 2.04939E-002 | 2.59546E-002 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | 6.30000 | 6.07234E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 5 | OFFICE | Cooling | 5076.72426 | 6092.06911 | 0.37402 | 0.44882 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 09:00:00 | 36.66500 | 9.14901E-003 | 88.24927 | 4.74953 | 3.81060E-002 | 0.00000 |
| 6 | OFFICE | Heating | 965.16433 | 1158.19719 | 4.26651E-002 | 5.11981E-002 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 18:50:00 | 6.30000 | 6.07234E-003 | 88.24927 | 4.74953 | 3.81060E-002 | 0.00000 |
| 7 | G NE APARTMENT | Cooling | 4350.80287 | 5220.96344 | 0.31580 | 0.37896 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 19:00:00 | 38.21700 | 9.15158E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 8 | G NE APARTMENT | Heating | 463.22841 | 555.87409 | 2.04774E-002 | 2.59546E-002 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | 6.30000 | 6.07234E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 9 | G N1 APARTMENT | Cooling | 3867.28299 | 4640.73959 | 0.27979 | 0.33574 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 19:00:00 | 38.21700 | 9.15158E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 10 | G N1 APARTMENT | Heating | 177.00475 | 212.40570 | 7.82464E-003 | 2.59546E-002 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | 6.30000 | 6.07234E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 11 | G N2 APARTMENT | Cooling | 3864.63726 | 4637.56471 | 0.27959 | 0.33551 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 19:00:00 | 38.21700 | 9.15158E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 12 | G N2 APARTMENT | Heating | 176.99521 | 212.39425 | 7.82422E-003 | 2.59546E-002 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | 6.30000 | 6.07234E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 13 | G S1 APARTMENT | Cooling | 3885.34832 | 4662.41799 | 0.28113 | 0.33736 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 19:00:00 | 38.21700 | 9.15158E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 14 | G S1 APARTMENT | Heating | 298.04579 | 357.65495 | 1.31751E-002 | 2.59546E-002 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 6.30000 | 6.07234E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 15 | G S2 APARTMENT | Cooling | 3914.07367 | 4696.88840 | 0.28328 | 0.33993 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 19:00:00 | 38.21700 | 9.15158E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 16 | G S2 APARTMENT | Heating | 306.47537 | 367.77045 | 1.35477E-002 | 2.59546E-002 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 04:40:00 | 6.30000 | 6.07234E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 17 | M SW APARTMENT | Cooling | 10076.44053 | 12091.72864 | 0.73345 | 0.88014 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 19:00:00 | 38.21700 | 9.15158E-003 | 88.24927 | 2.50000 | 5.19091E-002 | 0.00000 |
| 18 | M SW APARTMENT | Heating | 1225.66821 | 1470.80185 | 5.41804E-002 | 6.50165E-002 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 6.30000 | 6.07234E-003 | 88.24927 | 2.50000 | 5.19091E-002 | 0.00000 |
| 19 | M NW APARTMENT | Cooling | 10048.47335 | 12058.16802 | 0.73137 | 0.87765 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 19:00:00 | 38.21700 | 9.15158E-003 | 88.24927 | 2.50000 | 5.19091E-002 | 0.00000 |
| 20 | M NW APARTMENT | Heating | 949.02616 | 1138.83139 | 4.19523E-002 | 5.19091E-002 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 6.30000 | 6.07234E-003 | 88.24927 | 2.50000 | 5.19091E-002 | 0.00000 |
| 21 | M SE APARTMENT | Cooling | 9749.79021 | 11699.74825 | 0.70932 | 0.85118 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 19:00:00 | 38.21700 | 9.15158E-003 | 88.24927 | 2.50000 | 5.19091E-002 | 0.00000 |
| 22 | M SE APARTMENT | Heating | 1224.74029 | 1469.68835 | 5.41394E-002 | 6.49673E-002 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 6.30000 | 6.07234E-003 | 88.24927 | 2.50000 | 5.19091E-002 | 0.00000 |
| 23 | M NE APARTMENT | Cooling | 9722.12423 | 11666.54908 | 0.70726 | 0.84871 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 19:00:00 | 38.21700 | 9.15158E-003 | 88.24927 | 2.50000 | 5.19091E-002 | 0.00000 |
| 24 | M NE APARTMENT | Heating | 948.01753 | 1137.62103 | 4.19077E-002 | 5.19091E-002 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 6.30000 | 6.07234E-003 | 88.24927 | 2.50000 | 5.19091E-002 | 0.00000 |
| 25 | M N1 APARTMENT | Cooling | 8513.29454 | 10215.95345 | 0.61757 | 0.74108 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 19:00:00 | 38.21700 | 9.15158E-003 | 88.24927 | 2.50000 | 5.19091E-002 | 0.00000 |
| 26 | M N1 APARTMENT | Heating | 244.06532 | 292.87838 | 1.07891E-002 | 5.19091E-002 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 6.30000 | 6.07234E-003 | 88.24927 | 2.50000 | 5.19091E-002 | 0.00000 |
| 27 | M N2 APARTMENT | Cooling | 8506.98911 | 10208.38694 | 0.61710 | 0.74052 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 19:00:00 | 38.21700 | 9.15158E-003 | 88.24927 | 2.50000 | 5.19091E-002 | 0.00000 |
| 28 | M N2 APARTMENT | Heating | 244.03802 | 292.84562 | 1.07879E-002 | 5.19091E-002 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 6.30000 | 6.07234E-003 | 88.24927 | 2.50000 | 5.19091E-002 | 0.00000 |
| 29 | M S1 APARTMENT | Cooling | 8548.77038 | 10258.52445 | 0.62022 | 0.74426 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 19:00:00 | 38.21700 | 9.15158E-003 | 88.24927 | 2.50000 | 5.19091E-002 | 0.00000 |
| 30 | M S1 APARTMENT | Heating | 524.08498 | 628.90198 | 2.31671E-002 | 5.19091E-002 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 6.30000 | 6.07234E-003 | 88.24927 | 2.50000 | 5.19091E-002 | 0.00000 |
| 31 | M S2 APARTMENT | Cooling | 8542.42396 | 10250.90875 | 0.61975 | 0.74369 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 19:00:00 | 38.21700 | 9.15158E-003 | 88.24927 | 2.50000 | 5.19091E-002 | 0.00000 |
| 32 | M S2 APARTMENT | Heating | 524.06383 | 628.87659 | 2.31662E-002 | 5.19091E-002 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 6.30000 | 6.07234E-003 | 88.24927 | 2.50000 | 5.19091E-002 | 0.00000 |
| 33 | T SW APARTMENT | Cooling | 5688.94990 | 6826.73988 | 0.41480 | 0.49776 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 19:00:00 | 38.21700 | 9.15158E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 34 | T SW APARTMENT | Heating | 1331.05062 | 1597.26074 | 5.88387E-002 | 7.06065E-002 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 6.30000 | 6.07234E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 35 | T NW APARTMENT | Cooling | 5701.05306 | 6841.26367 | 0.41569 | 0.49883 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 19:00:00 | 38.21700 | 9.15158E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 36 | T NW APARTMENT | Heating | 1183.16435 | 1419.79722 | 5.23024E-002 | 6.27629E-002 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 6.30000 | 6.07234E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 37 | T SE APARTMENT | Cooling | 5441.62039 | 6529.94447 | 0.39643 | 0.47571 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 19:00:00 | 38.21700 | 9.15158E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 38 | T SE APARTMENT | Heating | 1330.57463 | 1596.68956 | 5.88177E-002 | 7.05812E-002 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 6.30000 | 6.07234E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 39 | T NE APARTMENT | Cooling | 5453.58520 | 6544.30224 | 0.39731 | 0.47678 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 19:00:00 | 38.21700 | 9.15158E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 40 | T NE APARTMENT | Heating | 1182.62586 | 1419.15103 | 5.22786E-002 | 6.27343E-002 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 6.30000 | 6.07234E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 41 | T N1 APARTMENT | Cooling | 4880.24137 | 5856.28964 | 0.35480 | 0.42575 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 19:00:00 | 38.21700 | 9.15158E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 42 | T N1 APARTMENT | Heating | 792.78565 | 951.34278 | 3.50457E-002 | 4.20548E-002 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 6.30000 | 6.07234E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 43 | T N2 APARTMENT | Cooling | 4871.60953 | 5845.93144 | 0.35416 | 0.42499 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 19:00:00 | 38.21700 | 9.15158E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 44 | T N2 APARTMENT | Heating | 792.77070 | 951.32484 | 3.50450E-002 | 4.20540E-002 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 6.30000 | 6.07234E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 45 | T S1 APARTMENT | Cooling | 4870.12284 | 5844.14741 | 0.35405 | 0.42486 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 19:00:00 | 38.21700 | 9.15158E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 46 | T S1 APARTMENT | Heating | 941.62680 | 1129.95216 | 4.16245E-002 | 4.99494E-002 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 6.30000 | 6.07234E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 47 | T S2 APARTMENT | Cooling | 4861.49705 | 5833.79647 | 0.35341 | 0.42410 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 19:00:00 | 38.21700 | 9.15158E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 48 | T S2 APARTMENT | Heating | 941.61374 | 1129.93649 | 4.16239E-002 | 4.99487E-002 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 6.30000 | 6.07234E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
| 1 | SPLIT GSW | Cooling | Sensible | 5629.96 | 0.39164 | 0.39164 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:00:00 |
| 2 | SPLIT GSW | Heating | Sensible | 1144.75 | 3.10277E-002 | 3.10277E-002 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 |
| 3 | SPLIT GNW | Cooling | Sensible | 5614.21 | 0.39045 | 0.39045 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:00:00 |
| 4 | SPLIT GNW | Heating | Sensible | 1031.66 | 2.59546E-002 | 2.59546E-002 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
| 5 | SPLIT OFFICE | Cooling | Sensible | 6480.33 | 0.44882 | 0.44882 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:00:00 |
| 6 | SPLIT OFFICE | Heating | Sensible | 1806.52 | 5.11981E-002 | 5.11981E-002 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 18:50:00 |
| 7 | SPLIT GNE | Cooling | Sensible | 5461.04 | 0.37896 | 0.37896 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:00:00 |
| 8 | SPLIT GNE | Heating | Sensible | 1031.66 | 2.59546E-002 | 2.59546E-002 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
| 9 | SPLIT GN1 | Cooling | Sensible | 4885.67 | 0.33574 | 0.33574 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:00:00 |
| 10 | SPLIT GN1 | Heating | Sensible | 1031.66 | 2.59546E-002 | 2.59546E-002 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
| 11 | SPLIT GN2 | Cooling | Sensible | 4882.55 | 0.33551 | 0.33551 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:00:00 |
| 12 | SPLIT GN2 | Heating | Sensible | 1031.66 | 2.59546E-002 | 2.59546E-002 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
| 13 | SPLIT GS1 | Cooling | Sensible | 4907.12 | 0.33736 | 0.33736 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:00:00 |
| 14 | SPLIT GS1 | Heating | Sensible | 1031.66 | 2.59546E-002 | 2.59546E-002 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
| 15 | SPLIT GS2 | Cooling | Sensible | 4941.26 | 0.33993 | 0.33993 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:00:00 |
| 16 | SPLIT GS2 | Heating | Sensible | 1031.66 | 2.59546E-002 | 2.59546E-002 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
| 17 | SPLIT MSW | Cooling | Sensible | 12552.37 | 0.88014 | 0.88014 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:00:00 |
| 18 | SPLIT MSW | Heating | Sensible | 2355.52 | 6.50165E-002 | 6.50165E-002 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 |
| 19 | SPLIT MNW | Cooling | Sensible | 12519.23 | 0.87765 | 0.87765 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:00:00 |
| 20 | SPLIT MNW | Heating | Sensible | 2063.32 | 5.19091E-002 | 5.19091E-002 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
| 21 | SPLIT MSE | Cooling | Sensible | 12165.69 | 0.85118 | 0.85118 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:00:00 |
| 22 | SPLIT MSE | Heating | Sensible | 2354.42 | 6.49673E-002 | 6.49673E-002 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 |
| 23 | SPLIT MNE | Cooling | Sensible | 12132.90 | 0.84871 | 0.84871 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:00:00 |
| 24 | SPLIT MNE | Heating | Sensible | 2063.32 | 5.19091E-002 | 5.19091E-002 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
| 25 | SPLIT MN1 | Cooling | Sensible | 10698.47 | 0.74108 | 0.74108 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:00:00 |
| 26 | SPLIT MN1 | Heating | Sensible | 2063.32 | 5.19091E-002 | 5.19091E-002 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
| 27 | SPLIT MN2 | Cooling | Sensible | 10690.98 | 0.74052 | 0.74052 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:00:00 |
| 28 | SPLIT MN2 | Heating | Sensible | 2063.32 | 5.19091E-002 | 5.19091E-002 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
| 29 | SPLIT MS1 | Cooling | Sensible | 10740.62 | 0.74426 | 0.74426 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:00:00 |
| 30 | SPLIT MS1 | Heating | Sensible | 2063.32 | 5.19091E-002 | 5.19091E-002 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
| 31 | SPLIT MS2 | Cooling | Sensible | 10733.08 | 0.74369 | 0.74369 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:00:00 |
| 32 | SPLIT MS2 | Heating | Sensible | 2063.32 | 5.19091E-002 | 5.19091E-002 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
| 33 | SPLIT TSW | Cooling | Sensible | 7046.20 | 0.49776 | 0.49776 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:00:00 |
| 34 | SPLIT TSW | Heating | Sensible | 2027.06 | 7.06065E-002 | 7.06065E-002 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 |
| 35 | SPLIT TNW | Cooling | Sensible | 7060.56 | 0.49883 | 0.49883 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:00:00 |
| 36 | SPLIT TNW | Heating | Sensible | 1852.20 | 6.27629E-002 | 6.27629E-002 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 |
| 37 | SPLIT TSE | Cooling | Sensible | 6752.78 | 0.47571 | 0.47571 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:00:00 |
| 38 | SPLIT TSE | Heating | Sensible | 2026.50 | 7.05812E-002 | 7.05812E-002 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 |
| 39 | SPLIT TNE | Cooling | Sensible | 6766.98 | 0.47678 | 0.47678 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:00:00 |
| 40 | SPLIT TNE | Heating | Sensible | 1851.56 | 6.27343E-002 | 6.27343E-002 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 |
| 41 | SPLIT TN1 | Cooling | Sensible | 6087.39 | 0.42575 | 0.42575 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:00:00 |
| 42 | SPLIT TN1 | Heating | Sensible | 1390.57 | 4.20548E-002 | 4.20548E-002 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 |
| 43 | SPLIT TN2 | Cooling | Sensible | 6077.18 | 0.42499 | 0.42499 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:00:00 |
| 44 | SPLIT TN2 | Heating | Sensible | 1390.55 | 4.20540E-002 | 4.20540E-002 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 |
| 45 | SPLIT TS1 | Cooling | Sensible | 6075.42 | 0.42486 | 0.42486 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:00:00 |
| 46 | SPLIT TS1 | Heating | Sensible | 1566.56 | 4.99494E-002 | 4.99494E-002 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 |
| 47 | SPLIT TS2 | Cooling | Sensible | 6065.22 | 0.42410 | 0.42410 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:00:00 |
| 48 | SPLIT TS2 | Heating | Sensible | 1566.55 | 4.99487E-002 | 4.99487E-002 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 |
| Component Type | Component Name | Input Field Description | Value | |
| 1 | ZoneHVAC:EnergyRecoveryVentilator | G SW APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 2 | ZoneHVAC:EnergyRecoveryVentilator | G SW APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 2.59546E-002 |
| 3 | Fan:OnOff | G SW APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 4 | Fan:OnOff | G SW APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 5 | HeatExchanger:AirToAir:SensibleAndLatent | G SW APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 6 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | G SW APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.39164 |
| 7 | ZoneHVAC:EnergyRecoveryVentilator | G NW APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 8 | ZoneHVAC:EnergyRecoveryVentilator | G NW APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 2.59546E-002 |
| 9 | Fan:OnOff | G NW APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 10 | Fan:OnOff | G NW APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 11 | HeatExchanger:AirToAir:SensibleAndLatent | G NW APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 12 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | G NW APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.39045 |
| 13 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | OFFICE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.44882 |
| 14 | ZoneHVAC:EnergyRecoveryVentilator | G NE APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 15 | ZoneHVAC:EnergyRecoveryVentilator | G NE APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 2.59546E-002 |
| 16 | Fan:OnOff | G NE APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 17 | Fan:OnOff | G NE APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 18 | HeatExchanger:AirToAir:SensibleAndLatent | G NE APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 19 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | G NE APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.37896 |
| 20 | ZoneHVAC:EnergyRecoveryVentilator | G N1 APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 21 | ZoneHVAC:EnergyRecoveryVentilator | G N1 APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 2.59546E-002 |
| 22 | Fan:OnOff | G N1 APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 23 | Fan:OnOff | G N1 APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 24 | HeatExchanger:AirToAir:SensibleAndLatent | G N1 APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 25 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | G N1 APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.33574 |
| 26 | ZoneHVAC:EnergyRecoveryVentilator | G N2 APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 27 | ZoneHVAC:EnergyRecoveryVentilator | G N2 APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 2.59546E-002 |
| 28 | Fan:OnOff | G N2 APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 29 | Fan:OnOff | G N2 APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 30 | HeatExchanger:AirToAir:SensibleAndLatent | G N2 APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 31 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | G N2 APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.33551 |
| 32 | ZoneHVAC:EnergyRecoveryVentilator | G S1 APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 33 | ZoneHVAC:EnergyRecoveryVentilator | G S1 APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 2.59546E-002 |
| 34 | Fan:OnOff | G S1 APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 35 | Fan:OnOff | G S1 APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 36 | HeatExchanger:AirToAir:SensibleAndLatent | G S1 APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 37 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | G S1 APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.33736 |
| 38 | ZoneHVAC:EnergyRecoveryVentilator | G S2 APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 39 | ZoneHVAC:EnergyRecoveryVentilator | G S2 APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 2.59546E-002 |
| 40 | Fan:OnOff | G S2 APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 41 | Fan:OnOff | G S2 APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 42 | HeatExchanger:AirToAir:SensibleAndLatent | G S2 APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 43 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | G S2 APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.33993 |
| 44 | ZoneHVAC:EnergyRecoveryVentilator | M SW APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 5.19091E-002 |
| 45 | ZoneHVAC:EnergyRecoveryVentilator | M SW APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 5.19091E-002 |
| 46 | Fan:OnOff | M SW APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 5.19091E-002 |
| 47 | Fan:OnOff | M SW APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 5.19091E-002 |
| 48 | HeatExchanger:AirToAir:SensibleAndLatent | M SW APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 5.19091E-002 |
| 49 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | M SW APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.88014 |
| 50 | ZoneHVAC:EnergyRecoveryVentilator | M NW APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 5.19091E-002 |
| 51 | ZoneHVAC:EnergyRecoveryVentilator | M NW APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 5.19091E-002 |
| 52 | Fan:OnOff | M NW APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 5.19091E-002 |
| 53 | Fan:OnOff | M NW APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 5.19091E-002 |
| 54 | HeatExchanger:AirToAir:SensibleAndLatent | M NW APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 5.19091E-002 |
| 55 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | M NW APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.87765 |
| 56 | ZoneHVAC:EnergyRecoveryVentilator | M SE APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 5.19091E-002 |
| 57 | ZoneHVAC:EnergyRecoveryVentilator | M SE APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 5.19091E-002 |
| 58 | Fan:OnOff | M SE APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 5.19091E-002 |
| 59 | Fan:OnOff | M SE APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 5.19091E-002 |
| 60 | HeatExchanger:AirToAir:SensibleAndLatent | M SE APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 5.19091E-002 |
| 61 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | M SE APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.85118 |
| 62 | ZoneHVAC:EnergyRecoveryVentilator | M NE APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 5.19091E-002 |
| 63 | ZoneHVAC:EnergyRecoveryVentilator | M NE APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 5.19091E-002 |
| 64 | Fan:OnOff | M NE APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 5.19091E-002 |
| 65 | Fan:OnOff | M NE APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 5.19091E-002 |
| 66 | HeatExchanger:AirToAir:SensibleAndLatent | M NE APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 5.19091E-002 |
| 67 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | M NE APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.84871 |
| 68 | ZoneHVAC:EnergyRecoveryVentilator | M N1 APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 5.19091E-002 |
| 69 | ZoneHVAC:EnergyRecoveryVentilator | M N1 APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 5.19091E-002 |
| 70 | Fan:OnOff | M N1 APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 5.19091E-002 |
| 71 | Fan:OnOff | M N1 APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 5.19091E-002 |
| 72 | HeatExchanger:AirToAir:SensibleAndLatent | M N1 APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 5.19091E-002 |
| 73 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | M N1 APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.74108 |
| 74 | ZoneHVAC:EnergyRecoveryVentilator | M N2 APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 5.19091E-002 |
| 75 | ZoneHVAC:EnergyRecoveryVentilator | M N2 APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 5.19091E-002 |
| 76 | Fan:OnOff | M N2 APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 5.19091E-002 |
| 77 | Fan:OnOff | M N2 APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 5.19091E-002 |
| 78 | HeatExchanger:AirToAir:SensibleAndLatent | M N2 APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 5.19091E-002 |
| 79 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | M N2 APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.74052 |
| 80 | ZoneHVAC:EnergyRecoveryVentilator | M S1 APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 5.19091E-002 |
| 81 | ZoneHVAC:EnergyRecoveryVentilator | M S1 APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 5.19091E-002 |
| 82 | Fan:OnOff | M S1 APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 5.19091E-002 |
| 83 | Fan:OnOff | M S1 APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 5.19091E-002 |
| 84 | HeatExchanger:AirToAir:SensibleAndLatent | M S1 APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 5.19091E-002 |
| 85 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | M S1 APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.74426 |
| 86 | ZoneHVAC:EnergyRecoveryVentilator | M S2 APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 5.19091E-002 |
| 87 | ZoneHVAC:EnergyRecoveryVentilator | M S2 APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 5.19091E-002 |
| 88 | Fan:OnOff | M S2 APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 5.19091E-002 |
| 89 | Fan:OnOff | M S2 APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 5.19091E-002 |
| 90 | HeatExchanger:AirToAir:SensibleAndLatent | M S2 APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 5.19091E-002 |
| 91 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | M S2 APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.74369 |
| 92 | ZoneHVAC:EnergyRecoveryVentilator | T SW APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 93 | ZoneHVAC:EnergyRecoveryVentilator | T SW APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 2.59546E-002 |
| 94 | Fan:OnOff | T SW APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 95 | Fan:OnOff | T SW APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 96 | HeatExchanger:AirToAir:SensibleAndLatent | T SW APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 97 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | T SW APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.49776 |
| 98 | ZoneHVAC:EnergyRecoveryVentilator | T NW APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 99 | ZoneHVAC:EnergyRecoveryVentilator | T NW APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 2.59546E-002 |
| 100 | Fan:OnOff | T NW APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 101 | Fan:OnOff | T NW APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 102 | HeatExchanger:AirToAir:SensibleAndLatent | T NW APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 103 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | T NW APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.49883 |
| 104 | ZoneHVAC:EnergyRecoveryVentilator | T SE APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 105 | ZoneHVAC:EnergyRecoveryVentilator | T SE APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 2.59546E-002 |
| 106 | Fan:OnOff | T SE APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 107 | Fan:OnOff | T SE APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 108 | HeatExchanger:AirToAir:SensibleAndLatent | T SE APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 109 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | T SE APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.47571 |
| 110 | ZoneHVAC:EnergyRecoveryVentilator | T NE APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 111 | ZoneHVAC:EnergyRecoveryVentilator | T NE APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 2.59546E-002 |
| 112 | Fan:OnOff | T NE APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 113 | Fan:OnOff | T NE APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 114 | HeatExchanger:AirToAir:SensibleAndLatent | T NE APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 115 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | T NE APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.47678 |
| 116 | ZoneHVAC:EnergyRecoveryVentilator | T N1 APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 117 | ZoneHVAC:EnergyRecoveryVentilator | T N1 APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 2.59546E-002 |
| 118 | Fan:OnOff | T N1 APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 119 | Fan:OnOff | T N1 APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 120 | HeatExchanger:AirToAir:SensibleAndLatent | T N1 APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 121 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | T N1 APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.42575 |
| 122 | ZoneHVAC:EnergyRecoveryVentilator | T N2 APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 123 | ZoneHVAC:EnergyRecoveryVentilator | T N2 APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 2.59546E-002 |
| 124 | Fan:OnOff | T N2 APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 125 | Fan:OnOff | T N2 APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 126 | HeatExchanger:AirToAir:SensibleAndLatent | T N2 APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 127 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | T N2 APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.42499 |
| 128 | ZoneHVAC:EnergyRecoveryVentilator | T S1 APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 129 | ZoneHVAC:EnergyRecoveryVentilator | T S1 APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 2.59546E-002 |
| 130 | Fan:OnOff | T S1 APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 131 | Fan:OnOff | T S1 APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 132 | HeatExchanger:AirToAir:SensibleAndLatent | T S1 APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 133 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | T S1 APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.42486 |
| 134 | ZoneHVAC:EnergyRecoveryVentilator | T S2 APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 135 | ZoneHVAC:EnergyRecoveryVentilator | T S2 APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 2.59546E-002 |
| 136 | Fan:OnOff | T S2 APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 137 | Fan:OnOff | T S2 APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 138 | HeatExchanger:AirToAir:SensibleAndLatent | T S2 APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 139 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | T S2 APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.42410 |
| 140 | AirLoopHVAC | SPLIT GSW | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.39164 |
| 141 | AirLoopHVAC | SPLIT GSW | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.39164 |
| 142 | AirLoopHVAC | SPLIT GSW | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.39164 |
| 143 | AirLoopHVAC | SPLIT GSW | Adjusted Heating Design Air Flow Rate [m3/s] | 0.39164 |
| 144 | AirLoopHVAC | SPLIT GSW | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.39164 |
| 145 | AirLoopHVAC | SPLIT GSW | Adjusted Main Design Air Flow Rate [m3/s] | 0.39164 |
| 146 | AirLoopHVAC | SPLIT GSW | User Heating Air Flow Ratio [] | 1.00000 |
| 147 | AirLoopHVAC | SPLIT GSW | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 148 | AirLoopHVAC | SPLIT GNW | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.39045 |
| 149 | AirLoopHVAC | SPLIT GNW | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.39045 |
| 150 | AirLoopHVAC | SPLIT GNW | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.39045 |
| 151 | AirLoopHVAC | SPLIT GNW | Adjusted Heating Design Air Flow Rate [m3/s] | 0.39045 |
| 152 | AirLoopHVAC | SPLIT GNW | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.39045 |
| 153 | AirLoopHVAC | SPLIT GNW | Adjusted Main Design Air Flow Rate [m3/s] | 0.39045 |
| 154 | AirLoopHVAC | SPLIT GNW | User Heating Air Flow Ratio [] | 1.00000 |
| 155 | AirLoopHVAC | SPLIT GNW | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 156 | AirLoopHVAC | SPLIT OFFICE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.44882 |
| 157 | AirLoopHVAC | SPLIT OFFICE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.44882 |
| 158 | AirLoopHVAC | SPLIT OFFICE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.44882 |
| 159 | AirLoopHVAC | SPLIT OFFICE | Adjusted Heating Design Air Flow Rate [m3/s] | 0.44882 |
| 160 | AirLoopHVAC | SPLIT OFFICE | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.44882 |
| 161 | AirLoopHVAC | SPLIT OFFICE | Adjusted Main Design Air Flow Rate [m3/s] | 0.44882 |
| 162 | AirLoopHVAC | SPLIT OFFICE | User Heating Air Flow Ratio [] | 1.00000 |
| 163 | AirLoopHVAC | SPLIT OFFICE | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 164 | AirLoopHVAC | SPLIT GNE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.37896 |
| 165 | AirLoopHVAC | SPLIT GNE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.37896 |
| 166 | AirLoopHVAC | SPLIT GNE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.37896 |
| 167 | AirLoopHVAC | SPLIT GNE | Adjusted Heating Design Air Flow Rate [m3/s] | 0.37896 |
| 168 | AirLoopHVAC | SPLIT GNE | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.37896 |
| 169 | AirLoopHVAC | SPLIT GNE | Adjusted Main Design Air Flow Rate [m3/s] | 0.37896 |
| 170 | AirLoopHVAC | SPLIT GNE | User Heating Air Flow Ratio [] | 1.00000 |
| 171 | AirLoopHVAC | SPLIT GNE | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 172 | AirLoopHVAC | SPLIT GN1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.33574 |
| 173 | AirLoopHVAC | SPLIT GN1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.33574 |
| 174 | AirLoopHVAC | SPLIT GN1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.33574 |
| 175 | AirLoopHVAC | SPLIT GN1 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.33574 |
| 176 | AirLoopHVAC | SPLIT GN1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.33574 |
| 177 | AirLoopHVAC | SPLIT GN1 | Adjusted Main Design Air Flow Rate [m3/s] | 0.33574 |
| 178 | AirLoopHVAC | SPLIT GN1 | User Heating Air Flow Ratio [] | 1.00000 |
| 179 | AirLoopHVAC | SPLIT GN1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 180 | AirLoopHVAC | SPLIT GN2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.33551 |
| 181 | AirLoopHVAC | SPLIT GN2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.33551 |
| 182 | AirLoopHVAC | SPLIT GN2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.33551 |
| 183 | AirLoopHVAC | SPLIT GN2 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.33551 |
| 184 | AirLoopHVAC | SPLIT GN2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.33551 |
| 185 | AirLoopHVAC | SPLIT GN2 | Adjusted Main Design Air Flow Rate [m3/s] | 0.33551 |
| 186 | AirLoopHVAC | SPLIT GN2 | User Heating Air Flow Ratio [] | 1.00000 |
| 187 | AirLoopHVAC | SPLIT GN2 | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 188 | AirLoopHVAC | SPLIT GS1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.33736 |
| 189 | AirLoopHVAC | SPLIT GS1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.33736 |
| 190 | AirLoopHVAC | SPLIT GS1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.33736 |
| 191 | AirLoopHVAC | SPLIT GS1 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.33736 |
| 192 | AirLoopHVAC | SPLIT GS1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.33736 |
| 193 | AirLoopHVAC | SPLIT GS1 | Adjusted Main Design Air Flow Rate [m3/s] | 0.33736 |
| 194 | AirLoopHVAC | SPLIT GS1 | User Heating Air Flow Ratio [] | 1.00000 |
| 195 | AirLoopHVAC | SPLIT GS1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 196 | AirLoopHVAC | SPLIT GS2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.33993 |
| 197 | AirLoopHVAC | SPLIT GS2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.33993 |
| 198 | AirLoopHVAC | SPLIT GS2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.33993 |
| 199 | AirLoopHVAC | SPLIT GS2 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.33993 |
| 200 | AirLoopHVAC | SPLIT GS2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.33993 |
| 201 | AirLoopHVAC | SPLIT GS2 | Adjusted Main Design Air Flow Rate [m3/s] | 0.33993 |
| 202 | AirLoopHVAC | SPLIT GS2 | User Heating Air Flow Ratio [] | 1.00000 |
| 203 | AirLoopHVAC | SPLIT GS2 | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 204 | AirLoopHVAC | SPLIT MSW | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.88014 |
| 205 | AirLoopHVAC | SPLIT MSW | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.88014 |
| 206 | AirLoopHVAC | SPLIT MSW | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.88014 |
| 207 | AirLoopHVAC | SPLIT MSW | Adjusted Heating Design Air Flow Rate [m3/s] | 0.88014 |
| 208 | AirLoopHVAC | SPLIT MSW | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.88014 |
| 209 | AirLoopHVAC | SPLIT MSW | Adjusted Main Design Air Flow Rate [m3/s] | 0.88014 |
| 210 | AirLoopHVAC | SPLIT MSW | User Heating Air Flow Ratio [] | 1.00000 |
| 211 | AirLoopHVAC | SPLIT MSW | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 212 | AirLoopHVAC | SPLIT MNW | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.87765 |
| 213 | AirLoopHVAC | SPLIT MNW | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.87765 |
| 214 | AirLoopHVAC | SPLIT MNW | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.87765 |
| 215 | AirLoopHVAC | SPLIT MNW | Adjusted Heating Design Air Flow Rate [m3/s] | 0.87765 |
| 216 | AirLoopHVAC | SPLIT MNW | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.87765 |
| 217 | AirLoopHVAC | SPLIT MNW | Adjusted Main Design Air Flow Rate [m3/s] | 0.87765 |
| 218 | AirLoopHVAC | SPLIT MNW | User Heating Air Flow Ratio [] | 1.00000 |
| 219 | AirLoopHVAC | SPLIT MNW | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 220 | AirLoopHVAC | SPLIT MSE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.85118 |
| 221 | AirLoopHVAC | SPLIT MSE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.85118 |
| 222 | AirLoopHVAC | SPLIT MSE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.85118 |
| 223 | AirLoopHVAC | SPLIT MSE | Adjusted Heating Design Air Flow Rate [m3/s] | 0.85118 |
| 224 | AirLoopHVAC | SPLIT MSE | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.85118 |
| 225 | AirLoopHVAC | SPLIT MSE | Adjusted Main Design Air Flow Rate [m3/s] | 0.85118 |
| 226 | AirLoopHVAC | SPLIT MSE | User Heating Air Flow Ratio [] | 1.00000 |
| 227 | AirLoopHVAC | SPLIT MSE | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 228 | AirLoopHVAC | SPLIT MNE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.84871 |
| 229 | AirLoopHVAC | SPLIT MNE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.84871 |
| 230 | AirLoopHVAC | SPLIT MNE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.84871 |
| 231 | AirLoopHVAC | SPLIT MNE | Adjusted Heating Design Air Flow Rate [m3/s] | 0.84871 |
| 232 | AirLoopHVAC | SPLIT MNE | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.84871 |
| 233 | AirLoopHVAC | SPLIT MNE | Adjusted Main Design Air Flow Rate [m3/s] | 0.84871 |
| 234 | AirLoopHVAC | SPLIT MNE | User Heating Air Flow Ratio [] | 1.00000 |
| 235 | AirLoopHVAC | SPLIT MNE | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 236 | AirLoopHVAC | SPLIT MN1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.74108 |
| 237 | AirLoopHVAC | SPLIT MN1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.74108 |
| 238 | AirLoopHVAC | SPLIT MN1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.74108 |
| 239 | AirLoopHVAC | SPLIT MN1 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.74108 |
| 240 | AirLoopHVAC | SPLIT MN1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.74108 |
| 241 | AirLoopHVAC | SPLIT MN1 | Adjusted Main Design Air Flow Rate [m3/s] | 0.74108 |
| 242 | AirLoopHVAC | SPLIT MN1 | User Heating Air Flow Ratio [] | 1.00000 |
| 243 | AirLoopHVAC | SPLIT MN1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 244 | AirLoopHVAC | SPLIT MN2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.74052 |
| 245 | AirLoopHVAC | SPLIT MN2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.74052 |
| 246 | AirLoopHVAC | SPLIT MN2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.74052 |
| 247 | AirLoopHVAC | SPLIT MN2 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.74052 |
| 248 | AirLoopHVAC | SPLIT MN2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.74052 |
| 249 | AirLoopHVAC | SPLIT MN2 | Adjusted Main Design Air Flow Rate [m3/s] | 0.74052 |
| 250 | AirLoopHVAC | SPLIT MN2 | User Heating Air Flow Ratio [] | 1.00000 |
| 251 | AirLoopHVAC | SPLIT MN2 | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 252 | AirLoopHVAC | SPLIT MS1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.74426 |
| 253 | AirLoopHVAC | SPLIT MS1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.74426 |
| 254 | AirLoopHVAC | SPLIT MS1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.74426 |
| 255 | AirLoopHVAC | SPLIT MS1 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.74426 |
| 256 | AirLoopHVAC | SPLIT MS1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.74426 |
| 257 | AirLoopHVAC | SPLIT MS1 | Adjusted Main Design Air Flow Rate [m3/s] | 0.74426 |
| 258 | AirLoopHVAC | SPLIT MS1 | User Heating Air Flow Ratio [] | 1.00000 |
| 259 | AirLoopHVAC | SPLIT MS1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 260 | AirLoopHVAC | SPLIT MS2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.74369 |
| 261 | AirLoopHVAC | SPLIT MS2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.74369 |
| 262 | AirLoopHVAC | SPLIT MS2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.74369 |
| 263 | AirLoopHVAC | SPLIT MS2 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.74369 |
| 264 | AirLoopHVAC | SPLIT MS2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.74369 |
| 265 | AirLoopHVAC | SPLIT MS2 | Adjusted Main Design Air Flow Rate [m3/s] | 0.74369 |
| 266 | AirLoopHVAC | SPLIT MS2 | User Heating Air Flow Ratio [] | 1.00000 |
| 267 | AirLoopHVAC | SPLIT MS2 | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 268 | AirLoopHVAC | SPLIT TSW | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.49776 |
| 269 | AirLoopHVAC | SPLIT TSW | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.49776 |
| 270 | AirLoopHVAC | SPLIT TSW | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.49776 |
| 271 | AirLoopHVAC | SPLIT TSW | Adjusted Heating Design Air Flow Rate [m3/s] | 0.49776 |
| 272 | AirLoopHVAC | SPLIT TSW | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.49776 |
| 273 | AirLoopHVAC | SPLIT TSW | Adjusted Main Design Air Flow Rate [m3/s] | 0.49776 |
| 274 | AirLoopHVAC | SPLIT TSW | User Heating Air Flow Ratio [] | 1.00000 |
| 275 | AirLoopHVAC | SPLIT TSW | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 276 | AirLoopHVAC | SPLIT TNW | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.49883 |
| 277 | AirLoopHVAC | SPLIT TNW | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.49883 |
| 278 | AirLoopHVAC | SPLIT TNW | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.49883 |
| 279 | AirLoopHVAC | SPLIT TNW | Adjusted Heating Design Air Flow Rate [m3/s] | 0.49883 |
| 280 | AirLoopHVAC | SPLIT TNW | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.49883 |
| 281 | AirLoopHVAC | SPLIT TNW | Adjusted Main Design Air Flow Rate [m3/s] | 0.49883 |
| 282 | AirLoopHVAC | SPLIT TNW | User Heating Air Flow Ratio [] | 1.00000 |
| 283 | AirLoopHVAC | SPLIT TNW | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 284 | AirLoopHVAC | SPLIT TSE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.47571 |
| 285 | AirLoopHVAC | SPLIT TSE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.47571 |
| 286 | AirLoopHVAC | SPLIT TSE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.47571 |
| 287 | AirLoopHVAC | SPLIT TSE | Adjusted Heating Design Air Flow Rate [m3/s] | 0.47571 |
| 288 | AirLoopHVAC | SPLIT TSE | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.47571 |
| 289 | AirLoopHVAC | SPLIT TSE | Adjusted Main Design Air Flow Rate [m3/s] | 0.47571 |
| 290 | AirLoopHVAC | SPLIT TSE | User Heating Air Flow Ratio [] | 1.00000 |
| 291 | AirLoopHVAC | SPLIT TSE | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 292 | AirLoopHVAC | SPLIT TNE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.47678 |
| 293 | AirLoopHVAC | SPLIT TNE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.47678 |
| 294 | AirLoopHVAC | SPLIT TNE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.47678 |
| 295 | AirLoopHVAC | SPLIT TNE | Adjusted Heating Design Air Flow Rate [m3/s] | 0.47678 |
| 296 | AirLoopHVAC | SPLIT TNE | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.47678 |
| 297 | AirLoopHVAC | SPLIT TNE | Adjusted Main Design Air Flow Rate [m3/s] | 0.47678 |
| 298 | AirLoopHVAC | SPLIT TNE | User Heating Air Flow Ratio [] | 1.00000 |
| 299 | AirLoopHVAC | SPLIT TNE | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 300 | AirLoopHVAC | SPLIT TN1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.42575 |
| 301 | AirLoopHVAC | SPLIT TN1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.42575 |
| 302 | AirLoopHVAC | SPLIT TN1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.42575 |
| 303 | AirLoopHVAC | SPLIT TN1 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.42575 |
| 304 | AirLoopHVAC | SPLIT TN1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.42575 |
| 305 | AirLoopHVAC | SPLIT TN1 | Adjusted Main Design Air Flow Rate [m3/s] | 0.42575 |
| 306 | AirLoopHVAC | SPLIT TN1 | User Heating Air Flow Ratio [] | 1.00000 |
| 307 | AirLoopHVAC | SPLIT TN1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 308 | AirLoopHVAC | SPLIT TN2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.42499 |
| 309 | AirLoopHVAC | SPLIT TN2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.42499 |
| 310 | AirLoopHVAC | SPLIT TN2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.42499 |
| 311 | AirLoopHVAC | SPLIT TN2 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.42499 |
| 312 | AirLoopHVAC | SPLIT TN2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.42499 |
| 313 | AirLoopHVAC | SPLIT TN2 | Adjusted Main Design Air Flow Rate [m3/s] | 0.42499 |
| 314 | AirLoopHVAC | SPLIT TN2 | User Heating Air Flow Ratio [] | 1.00000 |
| 315 | AirLoopHVAC | SPLIT TN2 | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 316 | AirLoopHVAC | SPLIT TS1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.42486 |
| 317 | AirLoopHVAC | SPLIT TS1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.42486 |
| 318 | AirLoopHVAC | SPLIT TS1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.42486 |
| 319 | AirLoopHVAC | SPLIT TS1 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.42486 |
| 320 | AirLoopHVAC | SPLIT TS1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.42486 |
| 321 | AirLoopHVAC | SPLIT TS1 | Adjusted Main Design Air Flow Rate [m3/s] | 0.42486 |
| 322 | AirLoopHVAC | SPLIT TS1 | User Heating Air Flow Ratio [] | 1.00000 |
| 323 | AirLoopHVAC | SPLIT TS1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 324 | AirLoopHVAC | SPLIT TS2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.42410 |
| 325 | AirLoopHVAC | SPLIT TS2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.42410 |
| 326 | AirLoopHVAC | SPLIT TS2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.42410 |
| 327 | AirLoopHVAC | SPLIT TS2 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.42410 |
| 328 | AirLoopHVAC | SPLIT TS2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.42410 |
| 329 | AirLoopHVAC | SPLIT TS2 | Adjusted Main Design Air Flow Rate [m3/s] | 0.42410 |
| 330 | AirLoopHVAC | SPLIT TS2 | User Heating Air Flow Ratio [] | 1.00000 |
| 331 | AirLoopHVAC | SPLIT TS2 | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 332 | AirLoopHVAC | SPLIT GSW | Design Supply Air Flow Rate [m3/s] | 0.39164 |
| 333 | AirLoopHVAC | SPLIT GNW | Design Supply Air Flow Rate [m3/s] | 0.39045 |
| 334 | AirLoopHVAC | SPLIT OFFICE | Design Supply Air Flow Rate [m3/s] | 0.44882 |
| 335 | AirLoopHVAC | SPLIT GNE | Design Supply Air Flow Rate [m3/s] | 0.37896 |
| 336 | AirLoopHVAC | SPLIT GN1 | Design Supply Air Flow Rate [m3/s] | 0.33574 |
| 337 | AirLoopHVAC | SPLIT GN2 | Design Supply Air Flow Rate [m3/s] | 0.33551 |
| 338 | AirLoopHVAC | SPLIT GS1 | Design Supply Air Flow Rate [m3/s] | 0.33736 |
| 339 | AirLoopHVAC | SPLIT GS2 | Design Supply Air Flow Rate [m3/s] | 0.33993 |
| 340 | AirLoopHVAC | SPLIT MSW | Design Supply Air Flow Rate [m3/s] | 0.88014 |
| 341 | AirLoopHVAC | SPLIT MNW | Design Supply Air Flow Rate [m3/s] | 0.87765 |
| 342 | AirLoopHVAC | SPLIT MSE | Design Supply Air Flow Rate [m3/s] | 0.85118 |
| 343 | AirLoopHVAC | SPLIT MNE | Design Supply Air Flow Rate [m3/s] | 0.84871 |
| 344 | AirLoopHVAC | SPLIT MN1 | Design Supply Air Flow Rate [m3/s] | 0.74108 |
| 345 | AirLoopHVAC | SPLIT MN2 | Design Supply Air Flow Rate [m3/s] | 0.74052 |
| 346 | AirLoopHVAC | SPLIT MS1 | Design Supply Air Flow Rate [m3/s] | 0.74426 |
| 347 | AirLoopHVAC | SPLIT MS2 | Design Supply Air Flow Rate [m3/s] | 0.74369 |
| 348 | AirLoopHVAC | SPLIT TSW | Design Supply Air Flow Rate [m3/s] | 0.49776 |
| 349 | AirLoopHVAC | SPLIT TNW | Design Supply Air Flow Rate [m3/s] | 0.49883 |
| 350 | AirLoopHVAC | SPLIT TSE | Design Supply Air Flow Rate [m3/s] | 0.47571 |
| 351 | AirLoopHVAC | SPLIT TNE | Design Supply Air Flow Rate [m3/s] | 0.47678 |
| 352 | AirLoopHVAC | SPLIT TN1 | Design Supply Air Flow Rate [m3/s] | 0.42575 |
| 353 | AirLoopHVAC | SPLIT TN2 | Design Supply Air Flow Rate [m3/s] | 0.42499 |
| 354 | AirLoopHVAC | SPLIT TS1 | Design Supply Air Flow Rate [m3/s] | 0.42486 |
| 355 | AirLoopHVAC | SPLIT TS2 | Design Supply Air Flow Rate [m3/s] | 0.42410 |
| 356 | Controller:OutdoorAir | SPLIT GSW_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.39164 |
| 357 | Controller:OutdoorAir | SPLIT GSW_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.59546E-002 |
| 358 | AirLoopHVAC:UnitarySystem | SPLIT GSW_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.39164 |
| 359 | AirLoopHVAC:UnitarySystem | SPLIT GSW_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.39164 |
| 360 | AirLoopHVAC:UnitarySystem | SPLIT GSW_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.39164 |
| 361 | AirLoopHVAC:UnitarySystem | SPLIT GSW_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.39164 |
| 362 | AirLoopHVAC:UnitarySystem | SPLIT GSW_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 6971.54454 |
| 363 | AirLoopHVAC:UnitarySystem | SPLIT GSW_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 9183.72440 |
| 364 | AirLoopHVAC:UnitarySystem | SPLIT GSW_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 365 | AirLoopHVAC:UnitarySystem | SPLIT GSW_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 366 | Fan:OnOff | SPLIT GSW SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.39164 |
| 367 | Coil:Cooling:DX:SingleSpeed | SPLIT GSW COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.39164 |
| 368 | Coil:Cooling:DX:SingleSpeed | SPLIT GSW COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 6971.54454 |
| 369 | Coil:Cooling:DX:SingleSpeed | SPLIT GSW COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80089 |
| 370 | Coil:Heating:Fuel | SPLIT GSW HEATING COIL | Design Size Nominal Capacity [W] | 9183.72440 |
| 371 | Controller:OutdoorAir | SPLIT GNW_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.39045 |
| 372 | Controller:OutdoorAir | SPLIT GNW_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.59546E-002 |
| 373 | AirLoopHVAC:UnitarySystem | SPLIT GNW_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.39045 |
| 374 | AirLoopHVAC:UnitarySystem | SPLIT GNW_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.39045 |
| 375 | AirLoopHVAC:UnitarySystem | SPLIT GNW_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.39045 |
| 376 | AirLoopHVAC:UnitarySystem | SPLIT GNW_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.39045 |
| 377 | AirLoopHVAC:UnitarySystem | SPLIT GNW_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 6918.17926 |
| 378 | AirLoopHVAC:UnitarySystem | SPLIT GNW_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 9157.07766 |
| 379 | AirLoopHVAC:UnitarySystem | SPLIT GNW_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 380 | AirLoopHVAC:UnitarySystem | SPLIT GNW_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 381 | Fan:OnOff | SPLIT GNW SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.39045 |
| 382 | Coil:Cooling:DX:SingleSpeed | SPLIT GNW COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.39045 |
| 383 | Coil:Cooling:DX:SingleSpeed | SPLIT GNW COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 6918.17926 |
| 384 | Coil:Cooling:DX:SingleSpeed | SPLIT GNW COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80049 |
| 385 | Coil:Heating:Fuel | SPLIT GNW HEATING COIL | Design Size Nominal Capacity [W] | 9157.07766 |
| 386 | Controller:OutdoorAir | SPLIT OFFICE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.44882 |
| 387 | Controller:OutdoorAir | SPLIT OFFICE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 3.81060E-002 |
| 388 | AirLoopHVAC:UnitarySystem | SPLIT OFFICE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.44882 |
| 389 | AirLoopHVAC:UnitarySystem | SPLIT OFFICE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.44882 |
| 390 | AirLoopHVAC:UnitarySystem | SPLIT OFFICE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.44882 |
| 391 | AirLoopHVAC:UnitarySystem | SPLIT OFFICE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.44882 |
| 392 | AirLoopHVAC:UnitarySystem | SPLIT OFFICE_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 7760.11724 |
| 393 | AirLoopHVAC:UnitarySystem | SPLIT OFFICE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 10670.50260 |
| 394 | AirLoopHVAC:UnitarySystem | SPLIT OFFICE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 395 | AirLoopHVAC:UnitarySystem | SPLIT OFFICE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 396 | Fan:OnOff | SPLIT OFFICE SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.44882 |
| 397 | Coil:Cooling:DX:SingleSpeed | SPLIT OFFICE COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.44882 |
| 398 | Coil:Cooling:DX:SingleSpeed | SPLIT OFFICE COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 7760.11724 |
| 399 | Coil:Cooling:DX:SingleSpeed | SPLIT OFFICE COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80100 |
| 400 | Coil:Heating:Fuel | SPLIT OFFICE HEATING COIL | Design Size Nominal Capacity [W] | 10670.50260 |
| 401 | Controller:OutdoorAir | SPLIT GNE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.37896 |
| 402 | Controller:OutdoorAir | SPLIT GNE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.59546E-002 |
| 403 | AirLoopHVAC:UnitarySystem | SPLIT GNE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.37896 |
| 404 | AirLoopHVAC:UnitarySystem | SPLIT GNE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.37896 |
| 405 | AirLoopHVAC:UnitarySystem | SPLIT GNE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.37896 |
| 406 | AirLoopHVAC:UnitarySystem | SPLIT GNE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.37896 |
| 407 | AirLoopHVAC:UnitarySystem | SPLIT GNE_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 6733.37948 |
| 408 | AirLoopHVAC:UnitarySystem | SPLIT GNE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 8900.91807 |
| 409 | AirLoopHVAC:UnitarySystem | SPLIT GNE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 410 | AirLoopHVAC:UnitarySystem | SPLIT GNE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 411 | Fan:OnOff | SPLIT GNE SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.37896 |
| 412 | Coil:Cooling:DX:SingleSpeed | SPLIT GNE COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.37896 |
| 413 | Coil:Cooling:DX:SingleSpeed | SPLIT GNE COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 6733.37948 |
| 414 | Coil:Cooling:DX:SingleSpeed | SPLIT GNE COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80053 |
| 415 | Coil:Heating:Fuel | SPLIT GNE HEATING COIL | Design Size Nominal Capacity [W] | 8900.91807 |
| 416 | Controller:OutdoorAir | SPLIT GN1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.33574 |
| 417 | Controller:OutdoorAir | SPLIT GN1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.59546E-002 |
| 418 | AirLoopHVAC:UnitarySystem | SPLIT GN1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.33574 |
| 419 | AirLoopHVAC:UnitarySystem | SPLIT GN1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.33574 |
| 420 | AirLoopHVAC:UnitarySystem | SPLIT GN1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.33574 |
| 421 | AirLoopHVAC:UnitarySystem | SPLIT GN1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.33574 |
| 422 | AirLoopHVAC:UnitarySystem | SPLIT GN1_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 6022.48854 |
| 423 | AirLoopHVAC:UnitarySystem | SPLIT GN1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 7937.48085 |
| 424 | AirLoopHVAC:UnitarySystem | SPLIT GN1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 425 | AirLoopHVAC:UnitarySystem | SPLIT GN1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 426 | Fan:OnOff | SPLIT GN1 SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.33574 |
| 427 | Coil:Cooling:DX:SingleSpeed | SPLIT GN1 COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.33574 |
| 428 | Coil:Cooling:DX:SingleSpeed | SPLIT GN1 COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 6022.48854 |
| 429 | Coil:Cooling:DX:SingleSpeed | SPLIT GN1 COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80029 |
| 430 | Coil:Heating:Fuel | SPLIT GN1 HEATING COIL | Design Size Nominal Capacity [W] | 7937.48085 |
| 431 | Controller:OutdoorAir | SPLIT GN2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.33551 |
| 432 | Controller:OutdoorAir | SPLIT GN2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.59546E-002 |
| 433 | AirLoopHVAC:UnitarySystem | SPLIT GN2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.33551 |
| 434 | AirLoopHVAC:UnitarySystem | SPLIT GN2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.33551 |
| 435 | AirLoopHVAC:UnitarySystem | SPLIT GN2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.33551 |
| 436 | AirLoopHVAC:UnitarySystem | SPLIT GN2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.33551 |
| 437 | AirLoopHVAC:UnitarySystem | SPLIT GN2_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 6018.71689 |
| 438 | AirLoopHVAC:UnitarySystem | SPLIT GN2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 7932.27442 |
| 439 | AirLoopHVAC:UnitarySystem | SPLIT GN2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 440 | AirLoopHVAC:UnitarySystem | SPLIT GN2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 441 | Fan:OnOff | SPLIT GN2 SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.33551 |
| 442 | Coil:Cooling:DX:SingleSpeed | SPLIT GN2 COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.33551 |
| 443 | Coil:Cooling:DX:SingleSpeed | SPLIT GN2 COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 6018.71689 |
| 444 | Coil:Cooling:DX:SingleSpeed | SPLIT GN2 COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80026 |
| 445 | Coil:Heating:Fuel | SPLIT GN2 HEATING COIL | Design Size Nominal Capacity [W] | 7932.27442 |
| 446 | Controller:OutdoorAir | SPLIT GS1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.33736 |
| 447 | Controller:OutdoorAir | SPLIT GS1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.59546E-002 |
| 448 | AirLoopHVAC:UnitarySystem | SPLIT GS1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.33736 |
| 449 | AirLoopHVAC:UnitarySystem | SPLIT GS1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.33736 |
| 450 | AirLoopHVAC:UnitarySystem | SPLIT GS1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.33736 |
| 451 | AirLoopHVAC:UnitarySystem | SPLIT GS1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.33736 |
| 452 | AirLoopHVAC:UnitarySystem | SPLIT GS1_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 6098.60194 |
| 453 | AirLoopHVAC:UnitarySystem | SPLIT GS1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 7973.63028 |
| 454 | AirLoopHVAC:UnitarySystem | SPLIT GS1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 455 | AirLoopHVAC:UnitarySystem | SPLIT GS1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 456 | Fan:OnOff | SPLIT GS1 SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.33736 |
| 457 | Coil:Cooling:DX:SingleSpeed | SPLIT GS1 COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.33736 |
| 458 | Coil:Cooling:DX:SingleSpeed | SPLIT GS1 COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 6098.60194 |
| 459 | Coil:Cooling:DX:SingleSpeed | SPLIT GS1 COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
| 460 | Coil:Heating:Fuel | SPLIT GS1 HEATING COIL | Design Size Nominal Capacity [W] | 7973.63028 |
| 461 | Controller:OutdoorAir | SPLIT GS2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.33993 |
| 462 | Controller:OutdoorAir | SPLIT GS2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.59546E-002 |
| 463 | AirLoopHVAC:UnitarySystem | SPLIT GS2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.33993 |
| 464 | AirLoopHVAC:UnitarySystem | SPLIT GS2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.33993 |
| 465 | AirLoopHVAC:UnitarySystem | SPLIT GS2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.33993 |
| 466 | AirLoopHVAC:UnitarySystem | SPLIT GS2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.33993 |
| 467 | AirLoopHVAC:UnitarySystem | SPLIT GS2_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 6140.62294 |
| 468 | AirLoopHVAC:UnitarySystem | SPLIT GS2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 8030.96994 |
| 469 | AirLoopHVAC:UnitarySystem | SPLIT GS2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 470 | AirLoopHVAC:UnitarySystem | SPLIT GS2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 471 | Fan:OnOff | SPLIT GS2 SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.33993 |
| 472 | Coil:Cooling:DX:SingleSpeed | SPLIT GS2 COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.33993 |
| 473 | Coil:Cooling:DX:SingleSpeed | SPLIT GS2 COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 6140.62294 |
| 474 | Coil:Cooling:DX:SingleSpeed | SPLIT GS2 COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80091 |
| 475 | Coil:Heating:Fuel | SPLIT GS2 HEATING COIL | Design Size Nominal Capacity [W] | 8030.96994 |
| 476 | Controller:OutdoorAir | SPLIT MSW_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.88014 |
| 477 | Controller:OutdoorAir | SPLIT MSW_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 5.19091E-002 |
| 478 | AirLoopHVAC:UnitarySystem | SPLIT MSW_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.88014 |
| 479 | AirLoopHVAC:UnitarySystem | SPLIT MSW_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.88014 |
| 480 | AirLoopHVAC:UnitarySystem | SPLIT MSW_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.88014 |
| 481 | AirLoopHVAC:UnitarySystem | SPLIT MSW_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.88014 |
| 482 | AirLoopHVAC:UnitarySystem | SPLIT MSW_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 15535.93536 |
| 483 | AirLoopHVAC:UnitarySystem | SPLIT MSW_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 20526.71051 |
| 484 | AirLoopHVAC:UnitarySystem | SPLIT MSW_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 485 | AirLoopHVAC:UnitarySystem | SPLIT MSW_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 486 | Fan:OnOff | SPLIT MSW SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.88014 |
| 487 | Coil:Cooling:DX:SingleSpeed | SPLIT MSW COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.88014 |
| 488 | Coil:Cooling:DX:SingleSpeed | SPLIT MSW COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 15535.93536 |
| 489 | Coil:Cooling:DX:SingleSpeed | SPLIT MSW COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80078 |
| 490 | Coil:Heating:Fuel | SPLIT MSW HEATING COIL | Design Size Nominal Capacity [W] | 20526.71051 |
| 491 | Controller:OutdoorAir | SPLIT MNW_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.87765 |
| 492 | Controller:OutdoorAir | SPLIT MNW_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 5.19091E-002 |
| 493 | AirLoopHVAC:UnitarySystem | SPLIT MNW_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.87765 |
| 494 | AirLoopHVAC:UnitarySystem | SPLIT MNW_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.87765 |
| 495 | AirLoopHVAC:UnitarySystem | SPLIT MNW_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.87765 |
| 496 | AirLoopHVAC:UnitarySystem | SPLIT MNW_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.87765 |
| 497 | AirLoopHVAC:UnitarySystem | SPLIT MNW_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 15438.65288 |
| 498 | AirLoopHVAC:UnitarySystem | SPLIT MNW_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 20470.73395 |
| 499 | AirLoopHVAC:UnitarySystem | SPLIT MNW_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 500 | AirLoopHVAC:UnitarySystem | SPLIT MNW_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 501 | Fan:OnOff | SPLIT MNW SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.87765 |
| 502 | Coil:Cooling:DX:SingleSpeed | SPLIT MNW COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.87765 |
| 503 | Coil:Cooling:DX:SingleSpeed | SPLIT MNW COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 15438.65288 |
| 504 | Coil:Cooling:DX:SingleSpeed | SPLIT MNW COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80097 |
| 505 | Coil:Heating:Fuel | SPLIT MNW HEATING COIL | Design Size Nominal Capacity [W] | 20470.73395 |
| 506 | Controller:OutdoorAir | SPLIT MSE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.85118 |
| 507 | Controller:OutdoorAir | SPLIT MSE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 5.19091E-002 |
| 508 | AirLoopHVAC:UnitarySystem | SPLIT MSE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.85118 |
| 509 | AirLoopHVAC:UnitarySystem | SPLIT MSE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.85118 |
| 510 | AirLoopHVAC:UnitarySystem | SPLIT MSE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.85118 |
| 511 | AirLoopHVAC:UnitarySystem | SPLIT MSE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.85118 |
| 512 | AirLoopHVAC:UnitarySystem | SPLIT MSE_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 15073.48140 |
| 513 | AirLoopHVAC:UnitarySystem | SPLIT MSE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 19881.09760 |
| 514 | AirLoopHVAC:UnitarySystem | SPLIT MSE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 515 | AirLoopHVAC:UnitarySystem | SPLIT MSE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 516 | Fan:OnOff | SPLIT MSE SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.85118 |
| 517 | Coil:Cooling:DX:SingleSpeed | SPLIT MSE COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.85118 |
| 518 | Coil:Cooling:DX:SingleSpeed | SPLIT MSE COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 15073.48140 |
| 519 | Coil:Cooling:DX:SingleSpeed | SPLIT MSE COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80067 |
| 520 | Coil:Heating:Fuel | SPLIT MSE HEATING COIL | Design Size Nominal Capacity [W] | 19881.09760 |
| 521 | Controller:OutdoorAir | SPLIT MNE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.84871 |
| 522 | Controller:OutdoorAir | SPLIT MNE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 5.19091E-002 |
| 523 | AirLoopHVAC:UnitarySystem | SPLIT MNE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.84871 |
| 524 | AirLoopHVAC:UnitarySystem | SPLIT MNE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.84871 |
| 525 | AirLoopHVAC:UnitarySystem | SPLIT MNE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.84871 |
| 526 | AirLoopHVAC:UnitarySystem | SPLIT MNE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.84871 |
| 527 | AirLoopHVAC:UnitarySystem | SPLIT MNE_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 14972.01435 |
| 528 | AirLoopHVAC:UnitarySystem | SPLIT MNE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 19825.67171 |
| 529 | AirLoopHVAC:UnitarySystem | SPLIT MNE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 530 | AirLoopHVAC:UnitarySystem | SPLIT MNE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 531 | Fan:OnOff | SPLIT MNE SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.84871 |
| 532 | Coil:Cooling:DX:SingleSpeed | SPLIT MNE COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.84871 |
| 533 | Coil:Cooling:DX:SingleSpeed | SPLIT MNE COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 14972.01435 |
| 534 | Coil:Cooling:DX:SingleSpeed | SPLIT MNE COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80099 |
| 535 | Coil:Heating:Fuel | SPLIT MNE HEATING COIL | Design Size Nominal Capacity [W] | 19825.67171 |
| 536 | Controller:OutdoorAir | SPLIT MN1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.74108 |
| 537 | Controller:OutdoorAir | SPLIT MN1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 5.19091E-002 |
| 538 | AirLoopHVAC:UnitarySystem | SPLIT MN1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.74108 |
| 539 | AirLoopHVAC:UnitarySystem | SPLIT MN1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.74108 |
| 540 | AirLoopHVAC:UnitarySystem | SPLIT MN1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.74108 |
| 541 | AirLoopHVAC:UnitarySystem | SPLIT MN1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.74108 |
| 542 | AirLoopHVAC:UnitarySystem | SPLIT MN1_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 13194.88991 |
| 543 | AirLoopHVAC:UnitarySystem | SPLIT MN1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 17426.35937 |
| 544 | AirLoopHVAC:UnitarySystem | SPLIT MN1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 545 | AirLoopHVAC:UnitarySystem | SPLIT MN1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 546 | Fan:OnOff | SPLIT MN1 SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.74108 |
| 547 | Coil:Cooling:DX:SingleSpeed | SPLIT MN1 COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.74108 |
| 548 | Coil:Cooling:DX:SingleSpeed | SPLIT MN1 COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 13194.88991 |
| 549 | Coil:Cooling:DX:SingleSpeed | SPLIT MN1 COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80082 |
| 550 | Coil:Heating:Fuel | SPLIT MN1 HEATING COIL | Design Size Nominal Capacity [W] | 17426.35937 |
| 551 | Controller:OutdoorAir | SPLIT MN2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.74052 |
| 552 | Controller:OutdoorAir | SPLIT MN2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 5.19091E-002 |
| 553 | AirLoopHVAC:UnitarySystem | SPLIT MN2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.74052 |
| 554 | AirLoopHVAC:UnitarySystem | SPLIT MN2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.74052 |
| 555 | AirLoopHVAC:UnitarySystem | SPLIT MN2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.74052 |
| 556 | AirLoopHVAC:UnitarySystem | SPLIT MN2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.74052 |
| 557 | AirLoopHVAC:UnitarySystem | SPLIT MN2_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 13185.83256 |
| 558 | AirLoopHVAC:UnitarySystem | SPLIT MN2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 17413.82409 |
| 559 | AirLoopHVAC:UnitarySystem | SPLIT MN2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 560 | AirLoopHVAC:UnitarySystem | SPLIT MN2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 561 | Fan:OnOff | SPLIT MN2 SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.74052 |
| 562 | Coil:Cooling:DX:SingleSpeed | SPLIT MN2 COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.74052 |
| 563 | Coil:Cooling:DX:SingleSpeed | SPLIT MN2 COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 13185.83256 |
| 564 | Coil:Cooling:DX:SingleSpeed | SPLIT MN2 COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80079 |
| 565 | Coil:Heating:Fuel | SPLIT MN2 HEATING COIL | Design Size Nominal Capacity [W] | 17413.82409 |
| 566 | Controller:OutdoorAir | SPLIT MS1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.74426 |
| 567 | Controller:OutdoorAir | SPLIT MS1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 5.19091E-002 |
| 568 | AirLoopHVAC:UnitarySystem | SPLIT MS1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.74426 |
| 569 | AirLoopHVAC:UnitarySystem | SPLIT MS1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.74426 |
| 570 | AirLoopHVAC:UnitarySystem | SPLIT MS1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.74426 |
| 571 | AirLoopHVAC:UnitarySystem | SPLIT MS1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.74426 |
| 572 | AirLoopHVAC:UnitarySystem | SPLIT MS1_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 13332.44076 |
| 573 | AirLoopHVAC:UnitarySystem | SPLIT MS1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 17497.52114 |
| 574 | AirLoopHVAC:UnitarySystem | SPLIT MS1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 575 | AirLoopHVAC:UnitarySystem | SPLIT MS1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 576 | Fan:OnOff | SPLIT MS1 SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.74426 |
| 577 | Coil:Cooling:DX:SingleSpeed | SPLIT MS1 COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.74426 |
| 578 | Coil:Cooling:DX:SingleSpeed | SPLIT MS1 COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 13332.44076 |
| 579 | Coil:Cooling:DX:SingleSpeed | SPLIT MS1 COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80074 |
| 580 | Coil:Heating:Fuel | SPLIT MS1 HEATING COIL | Design Size Nominal Capacity [W] | 17497.52114 |
| 581 | Controller:OutdoorAir | SPLIT MS2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.74369 |
| 582 | Controller:OutdoorAir | SPLIT MS2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 5.19091E-002 |
| 583 | AirLoopHVAC:UnitarySystem | SPLIT MS2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.74369 |
| 584 | AirLoopHVAC:UnitarySystem | SPLIT MS2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.74369 |
| 585 | AirLoopHVAC:UnitarySystem | SPLIT MS2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.74369 |
| 586 | AirLoopHVAC:UnitarySystem | SPLIT MS2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.74369 |
| 587 | AirLoopHVAC:UnitarySystem | SPLIT MS2_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 13323.45603 |
| 588 | AirLoopHVAC:UnitarySystem | SPLIT MS2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 17484.90598 |
| 589 | AirLoopHVAC:UnitarySystem | SPLIT MS2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 590 | AirLoopHVAC:UnitarySystem | SPLIT MS2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 591 | Fan:OnOff | SPLIT MS2 SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.74369 |
| 592 | Coil:Cooling:DX:SingleSpeed | SPLIT MS2 COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.74369 |
| 593 | Coil:Cooling:DX:SingleSpeed | SPLIT MS2 COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 13323.45603 |
| 594 | Coil:Cooling:DX:SingleSpeed | SPLIT MS2 COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80071 |
| 595 | Coil:Heating:Fuel | SPLIT MS2 HEATING COIL | Design Size Nominal Capacity [W] | 17484.90598 |
| 596 | Controller:OutdoorAir | SPLIT TSW_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.49776 |
| 597 | Controller:OutdoorAir | SPLIT TSW_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.59546E-002 |
| 598 | AirLoopHVAC:UnitarySystem | SPLIT TSW_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.49776 |
| 599 | AirLoopHVAC:UnitarySystem | SPLIT TSW_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.49776 |
| 600 | AirLoopHVAC:UnitarySystem | SPLIT TSW_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.49776 |
| 601 | AirLoopHVAC:UnitarySystem | SPLIT TSW_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.49776 |
| 602 | AirLoopHVAC:UnitarySystem | SPLIT TSW_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 8706.75162 |
| 603 | AirLoopHVAC:UnitarySystem | SPLIT TSW_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 11549.35546 |
| 604 | AirLoopHVAC:UnitarySystem | SPLIT TSW_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 605 | AirLoopHVAC:UnitarySystem | SPLIT TSW_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 606 | Fan:OnOff | SPLIT TSW SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.49776 |
| 607 | Coil:Cooling:DX:SingleSpeed | SPLIT TSW COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.49776 |
| 608 | Coil:Cooling:DX:SingleSpeed | SPLIT TSW COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 8706.75162 |
| 609 | Coil:Cooling:DX:SingleSpeed | SPLIT TSW COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80093 |
| 610 | Coil:Heating:Fuel | SPLIT TSW HEATING COIL | Design Size Nominal Capacity [W] | 11549.35546 |
| 611 | Controller:OutdoorAir | SPLIT TNW_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.49883 |
| 612 | Controller:OutdoorAir | SPLIT TNW_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.59546E-002 |
| 613 | AirLoopHVAC:UnitarySystem | SPLIT TNW_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.49883 |
| 614 | AirLoopHVAC:UnitarySystem | SPLIT TNW_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.49883 |
| 615 | AirLoopHVAC:UnitarySystem | SPLIT TNW_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.49883 |
| 616 | AirLoopHVAC:UnitarySystem | SPLIT TNW_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.49883 |
| 617 | AirLoopHVAC:UnitarySystem | SPLIT TNW_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 8704.25510 |
| 618 | AirLoopHVAC:UnitarySystem | SPLIT TNW_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 11573.12009 |
| 619 | AirLoopHVAC:UnitarySystem | SPLIT TNW_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 620 | AirLoopHVAC:UnitarySystem | SPLIT TNW_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 621 | Fan:OnOff | SPLIT TNW SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.49883 |
| 622 | Coil:Cooling:DX:SingleSpeed | SPLIT TNW COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.49883 |
| 623 | Coil:Cooling:DX:SingleSpeed | SPLIT TNW COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 8704.25510 |
| 624 | Coil:Cooling:DX:SingleSpeed | SPLIT TNW COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80078 |
| 625 | Coil:Heating:Fuel | SPLIT TNW HEATING COIL | Design Size Nominal Capacity [W] | 11573.12009 |
| 626 | Controller:OutdoorAir | SPLIT TSE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.47571 |
| 627 | Controller:OutdoorAir | SPLIT TSE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.59546E-002 |
| 628 | AirLoopHVAC:UnitarySystem | SPLIT TSE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.47571 |
| 629 | AirLoopHVAC:UnitarySystem | SPLIT TSE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.47571 |
| 630 | AirLoopHVAC:UnitarySystem | SPLIT TSE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.47571 |
| 631 | AirLoopHVAC:UnitarySystem | SPLIT TSE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.47571 |
| 632 | AirLoopHVAC:UnitarySystem | SPLIT TSE_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 8350.99941 |
| 633 | AirLoopHVAC:UnitarySystem | SPLIT TSE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 11057.92034 |
| 634 | AirLoopHVAC:UnitarySystem | SPLIT TSE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 635 | AirLoopHVAC:UnitarySystem | SPLIT TSE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 636 | Fan:OnOff | SPLIT TSE SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.47571 |
| 637 | Coil:Cooling:DX:SingleSpeed | SPLIT TSE COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.47571 |
| 638 | Coil:Cooling:DX:SingleSpeed | SPLIT TSE COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 8350.99941 |
| 639 | Coil:Cooling:DX:SingleSpeed | SPLIT TSE COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80069 |
| 640 | Coil:Heating:Fuel | SPLIT TSE HEATING COIL | Design Size Nominal Capacity [W] | 11057.92034 |
| 641 | Controller:OutdoorAir | SPLIT TNE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.47678 |
| 642 | Controller:OutdoorAir | SPLIT TNE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.59546E-002 |
| 643 | AirLoopHVAC:UnitarySystem | SPLIT TNE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.47678 |
| 644 | AirLoopHVAC:UnitarySystem | SPLIT TNE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.47678 |
| 645 | AirLoopHVAC:UnitarySystem | SPLIT TNE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.47678 |
| 646 | AirLoopHVAC:UnitarySystem | SPLIT TNE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.47678 |
| 647 | AirLoopHVAC:UnitarySystem | SPLIT TNE_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 8347.04091 |
| 648 | AirLoopHVAC:UnitarySystem | SPLIT TNE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 11081.43338 |
| 649 | AirLoopHVAC:UnitarySystem | SPLIT TNE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 650 | AirLoopHVAC:UnitarySystem | SPLIT TNE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 651 | Fan:OnOff | SPLIT TNE SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.47678 |
| 652 | Coil:Cooling:DX:SingleSpeed | SPLIT TNE COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.47678 |
| 653 | Coil:Cooling:DX:SingleSpeed | SPLIT TNE COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 8347.04091 |
| 654 | Coil:Cooling:DX:SingleSpeed | SPLIT TNE COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80063 |
| 655 | Coil:Heating:Fuel | SPLIT TNE HEATING COIL | Design Size Nominal Capacity [W] | 11081.43338 |
| 656 | Controller:OutdoorAir | SPLIT TN1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.42575 |
| 657 | Controller:OutdoorAir | SPLIT TN1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.59546E-002 |
| 658 | AirLoopHVAC:UnitarySystem | SPLIT TN1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.42575 |
| 659 | AirLoopHVAC:UnitarySystem | SPLIT TN1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.42575 |
| 660 | AirLoopHVAC:UnitarySystem | SPLIT TN1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.42575 |
| 661 | AirLoopHVAC:UnitarySystem | SPLIT TN1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.42575 |
| 662 | AirLoopHVAC:UnitarySystem | SPLIT TN1_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 7494.04706 |
| 663 | AirLoopHVAC:UnitarySystem | SPLIT TN1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 9944.01113 |
| 664 | AirLoopHVAC:UnitarySystem | SPLIT TN1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 665 | AirLoopHVAC:UnitarySystem | SPLIT TN1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 666 | Fan:OnOff | SPLIT TN1 SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.42575 |
| 667 | Coil:Cooling:DX:SingleSpeed | SPLIT TN1 COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.42575 |
| 668 | Coil:Cooling:DX:SingleSpeed | SPLIT TN1 COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 7494.04706 |
| 669 | Coil:Cooling:DX:SingleSpeed | SPLIT TN1 COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80076 |
| 670 | Coil:Heating:Fuel | SPLIT TN1 HEATING COIL | Design Size Nominal Capacity [W] | 9944.01113 |
| 671 | Controller:OutdoorAir | SPLIT TN2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.42499 |
| 672 | Controller:OutdoorAir | SPLIT TN2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.59546E-002 |
| 673 | AirLoopHVAC:UnitarySystem | SPLIT TN2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.42499 |
| 674 | AirLoopHVAC:UnitarySystem | SPLIT TN2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.42499 |
| 675 | AirLoopHVAC:UnitarySystem | SPLIT TN2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.42499 |
| 676 | AirLoopHVAC:UnitarySystem | SPLIT TN2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.42499 |
| 677 | AirLoopHVAC:UnitarySystem | SPLIT TN2_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 7481.64494 |
| 678 | AirLoopHVAC:UnitarySystem | SPLIT TN2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 9926.97018 |
| 679 | AirLoopHVAC:UnitarySystem | SPLIT TN2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 680 | AirLoopHVAC:UnitarySystem | SPLIT TN2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 681 | Fan:OnOff | SPLIT TN2 SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.42499 |
| 682 | Coil:Cooling:DX:SingleSpeed | SPLIT TN2 COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.42499 |
| 683 | Coil:Cooling:DX:SingleSpeed | SPLIT TN2 COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 7481.64494 |
| 684 | Coil:Cooling:DX:SingleSpeed | SPLIT TN2 COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80071 |
| 685 | Coil:Heating:Fuel | SPLIT TN2 HEATING COIL | Design Size Nominal Capacity [W] | 9926.97018 |
| 686 | Controller:OutdoorAir | SPLIT TS1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.42486 |
| 687 | Controller:OutdoorAir | SPLIT TS1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.59546E-002 |
| 688 | AirLoopHVAC:UnitarySystem | SPLIT TS1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.42486 |
| 689 | AirLoopHVAC:UnitarySystem | SPLIT TS1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.42486 |
| 690 | AirLoopHVAC:UnitarySystem | SPLIT TS1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.42486 |
| 691 | AirLoopHVAC:UnitarySystem | SPLIT TS1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.42486 |
| 692 | AirLoopHVAC:UnitarySystem | SPLIT TS1_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 7505.33394 |
| 693 | AirLoopHVAC:UnitarySystem | SPLIT TS1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 9924.27445 |
| 694 | AirLoopHVAC:UnitarySystem | SPLIT TS1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 695 | AirLoopHVAC:UnitarySystem | SPLIT TS1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 696 | Fan:OnOff | SPLIT TS1 SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.42486 |
| 697 | Coil:Cooling:DX:SingleSpeed | SPLIT TS1 COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.42486 |
| 698 | Coil:Cooling:DX:SingleSpeed | SPLIT TS1 COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 7505.33394 |
| 699 | Coil:Cooling:DX:SingleSpeed | SPLIT TS1 COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80052 |
| 700 | Coil:Heating:Fuel | SPLIT TS1 HEATING COIL | Design Size Nominal Capacity [W] | 9924.27445 |
| 701 | Controller:OutdoorAir | SPLIT TS2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.42410 |
| 702 | Controller:OutdoorAir | SPLIT TS2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.59546E-002 |
| 703 | AirLoopHVAC:UnitarySystem | SPLIT TS2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.42410 |
| 704 | AirLoopHVAC:UnitarySystem | SPLIT TS2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.42410 |
| 705 | AirLoopHVAC:UnitarySystem | SPLIT TS2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.42410 |
| 706 | AirLoopHVAC:UnitarySystem | SPLIT TS2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.42410 |
| 707 | AirLoopHVAC:UnitarySystem | SPLIT TS2_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 7493.00497 |
| 708 | AirLoopHVAC:UnitarySystem | SPLIT TS2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 9907.24387 |
| 709 | AirLoopHVAC:UnitarySystem | SPLIT TS2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 710 | AirLoopHVAC:UnitarySystem | SPLIT TS2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 711 | Fan:OnOff | SPLIT TS2 SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.42410 |
| 712 | Coil:Cooling:DX:SingleSpeed | SPLIT TS2 COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.42410 |
| 713 | Coil:Cooling:DX:SingleSpeed | SPLIT TS2 COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 7493.00497 |
| 714 | Coil:Cooling:DX:SingleSpeed | SPLIT TS2 COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80046 |
| 715 | Coil:Heating:Fuel | SPLIT TS2 HEATING COIL | Design Size Nominal Capacity [W] | 9907.24387 |
| Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
| 1 | Coil:Cooling:DX:SingleSpeed | SPLIT GSW COOLING COIL | 6664.3 | 3.17 | 10.82 | 11.25 | 10.65 | 10.60 |
| 2 | Coil:Cooling:DX:SingleSpeed | SPLIT GNW COOLING COIL | 6611.9 | 3.17 | 10.81 | 11.24 | 10.64 | 10.58 |
| 3 | Coil:Cooling:DX:SingleSpeed | SPLIT OFFICE COOLING COIL | 7408.2 | 3.15 | 10.76 | 11.19 | 10.58 | 10.51 |
| 4 | Coil:Cooling:DX:SingleSpeed | SPLIT GNE COOLING COIL | 6436.1 | 3.17 | 10.82 | 11.25 | 10.64 | 10.59 |
| 5 | Coil:Cooling:DX:SingleSpeed | SPLIT GN1 COOLING COIL | 5759.1 | 3.18 | 10.84 | 11.27 | 10.66 | 10.62 |
| 6 | Coil:Cooling:DX:SingleSpeed | SPLIT GN2 COOLING COIL | 5755.5 | 3.18 | 10.84 | 11.27 | 10.66 | 10.62 |
| 7 | Coil:Cooling:DX:SingleSpeed | SPLIT GS1 COOLING COIL | 5833.9 | 3.18 | 10.86 | 11.29 | 10.68 | 10.64 |
| 8 | Coil:Cooling:DX:SingleSpeed | SPLIT GS2 COOLING COIL | 5873.9 | 3.18 | 10.85 | 11.29 | 10.68 | 10.64 |
| 9 | Coil:Cooling:DX:SingleSpeed | SPLIT MSW COOLING COIL | 14845.6 | 3.17 | 10.81 | 11.24 | 10.63 | 10.57 |
| 10 | Coil:Cooling:DX:SingleSpeed | SPLIT MNW COOLING COIL | 14750.3 | 3.17 | 10.80 | 11.23 | 10.62 | 10.56 |
| 11 | Coil:Cooling:DX:SingleSpeed | SPLIT MSE COOLING COIL | 14405.8 | 3.17 | 10.81 | 11.24 | 10.64 | 10.58 |
| 12 | Coil:Cooling:DX:SingleSpeed | SPLIT MNE COOLING COIL | 14306.3 | 3.17 | 10.81 | 11.23 | 10.63 | 10.57 |
| 13 | Coil:Cooling:DX:SingleSpeed | SPLIT MN1 COOLING COIL | 12613.5 | 3.17 | 10.82 | 11.25 | 10.65 | 10.60 |
| 14 | Coil:Cooling:DX:SingleSpeed | SPLIT MN2 COOLING COIL | 12604.9 | 3.17 | 10.82 | 11.26 | 10.65 | 10.60 |
| 15 | Coil:Cooling:DX:SingleSpeed | SPLIT MS1 COOLING COIL | 12748.5 | 3.18 | 10.84 | 11.27 | 10.66 | 10.62 |
| 16 | Coil:Cooling:DX:SingleSpeed | SPLIT MS2 COOLING COIL | 12740.0 | 3.18 | 10.84 | 11.27 | 10.66 | 10.62 |
| 17 | Coil:Cooling:DX:SingleSpeed | SPLIT TSW COOLING COIL | 8316.4 | 3.16 | 10.79 | 11.22 | 10.61 | 10.55 |
| 18 | Coil:Cooling:DX:SingleSpeed | SPLIT TNW COOLING COIL | 8313.0 | 3.16 | 10.78 | 11.21 | 10.60 | 10.54 |
| 19 | Coil:Cooling:DX:SingleSpeed | SPLIT TSE COOLING COIL | 7977.9 | 3.16 | 10.80 | 11.22 | 10.62 | 10.56 |
| 20 | Coil:Cooling:DX:SingleSpeed | SPLIT TNE COOLING COIL | 7973.1 | 3.16 | 10.79 | 11.22 | 10.61 | 10.55 |
| 21 | Coil:Cooling:DX:SingleSpeed | SPLIT TN1 COOLING COIL | 7160.1 | 3.17 | 10.80 | 11.23 | 10.62 | 10.56 |
| 22 | Coil:Cooling:DX:SingleSpeed | SPLIT TN2 COOLING COIL | 7148.3 | 3.17 | 10.80 | 11.23 | 10.62 | 10.57 |
| 23 | Coil:Cooling:DX:SingleSpeed | SPLIT TS1 COOLING COIL | 7172.1 | 3.17 | 10.81 | 11.24 | 10.63 | 10.58 |
| 24 | Coil:Cooling:DX:SingleSpeed | SPLIT TS2 COOLING COIL | 7160.3 | 3.17 | 10.81 | 11.24 | 10.63 | 10.58 |
| Zone Name | # Surfaces | |
| 1 | G SW APARTMENT | 9 |
| 2 | G NW APARTMENT | 9 |
| 3 | OFFICE | 9 |
| 4 | G NE APARTMENT | 9 |
| 5 | G N1 APARTMENT | 8 |
| 6 | G N2 APARTMENT | 8 |
| 7 | G S1 APARTMENT | 8 |
| 8 | G S2 APARTMENT | 8 |
| 9 | M SW APARTMENT | 9 |
| 10 | M NW APARTMENT | 9 |
| 11 | M SE APARTMENT | 9 |
| 12 | M NE APARTMENT | 9 |
| 13 | M N1 APARTMENT | 8 |
| 14 | M N2 APARTMENT | 8 |
| 15 | M S1 APARTMENT | 8 |
| 16 | M S2 APARTMENT | 8 |
| 17 | T SW APARTMENT | 9 |
| 18 | T NW APARTMENT | 9 |
| 19 | T SE APARTMENT | 9 |
| 20 | T NE APARTMENT | 9 |
| 21 | T N1 APARTMENT | 8 |
| 22 | T N2 APARTMENT | 8 |
| 23 | T S1 APARTMENT | 8 |
| 24 | T S2 APARTMENT | 8 |
| 25 | T CORRIDOR | 13 |
| 26 | G CORRIDOR | 13 |
| 27 | M CORRIDOR | 13 |
| Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
| 1 | G SWALL SWA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_GRD | 0.844 | 0.750 | 28.24 | 35.30 | 28.24 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 2 | GWINDOW1 S SWA | Window | G SWALL SWA | Window5 Detailed Fenestration | RESWINDOW_U_0.5369_SHGC_0.25 | N/A | 3.053 | No | 7.06 | 7.06 | 7.06 | 180.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 3 | G WWALL SWA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_GRD | 0.844 | 0.750 | 18.58 | 23.22 | 18.58 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 4 | GWINDOW1 W SWA | Window | G WWALL SWA | Window5 Detailed Fenestration | RESWINDOW_U_0.5369_SHGC_0.25 | N/A | 3.053 | No | 4.65 | 4.65 | 4.65 | 270.00 | 90.00 | 3.81 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 5 | G NIWALL SWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-G NIWALL SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 6 | G EIWALL SWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | iz-G EIWALL SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 7 | G GFLOOR SWA | Floor | CTF - ConductionTransferFunction | GGFLOORSWA_FFACTOR | 0.287 | 0.268 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 8 | G CEILIN SWA | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | G CEILIN SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 9 | G INTERNALMASS SWA | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 88.25 | 88.25 | 88.25 | 0.00 | 90.00 | 88.25 | 1.00 | 0.00 | G INTERNALMASS SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 10 | G NWALL NWA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_GRD | 0.844 | 0.750 | 28.24 | 35.30 | 28.24 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 11 | GWINDOW1 N NWA | Window | G NWALL NWA | Window5 Detailed Fenestration | RESWINDOW_U_0.5369_SHGC_0.25 | N/A | 3.053 | No | 7.06 | 7.06 | 7.06 | 0.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 12 | G WWALL NWA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_GRD | 0.844 | 0.750 | 18.58 | 23.22 | 18.58 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 13 | GWINDOW1 W NWA | Window | G WWALL NWA | Window5 Detailed Fenestration | RESWINDOW_U_0.5369_SHGC_0.25 | N/A | 3.053 | No | 4.65 | 4.65 | 4.65 | 270.00 | 90.00 | 3.81 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 14 | G SIWALL NWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-G SIWALL NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 15 | G EIWALL NWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | iz-G EIWALL NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 16 | G GFLOOR NWA | Floor | CTF - ConductionTransferFunction | GGFLOORNWA_FFACTOR | 0.287 | 0.268 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 17 | G CEILIN NWA | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | G CEILIN NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 18 | G INTERNALMASS NWA | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 88.25 | 88.25 | 88.25 | 0.00 | 90.00 | 88.25 | 1.00 | 0.00 | G INTERNALMASS NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 19 | G SWALL SEA | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.844 | 0.750 | 28.24 | 35.30 | 28.24 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 20 | GWINDOW1 S SEA | Window | G SWALL SEA | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5369_SHGC_0.25 | N/A | 3.053 | No | 7.06 | 7.06 | 7.06 | 180.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 21 | G EWALL SEA | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.844 | 0.750 | 18.58 | 23.22 | 18.58 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 22 | GWINDOW1 E SEA | Window | G EWALL SEA | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5369_SHGC_0.25 | N/A | 3.053 | No | 4.65 | 4.65 | 4.65 | 90.00 | 90.00 | 3.81 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 23 | G NIWALL SEA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-G NIWALL SEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 24 | iz-G EIWALL S2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | G EIWALL S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 25 | G GFLOOR SEA | Floor | CTF - ConductionTransferFunction | GGFLOORSEA_FFACTOR | 0.287 | 0.268 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 26 | G CEILIN SEA | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | G CEILIN SEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 27 | G INTERNALMASS SEA | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 88.25 | 88.25 | 88.25 | 0.00 | 90.00 | 88.25 | 1.00 | 0.00 | G INTERNALMASS SEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 28 | G NWALL NEA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_GRD | 0.844 | 0.750 | 28.24 | 35.30 | 28.24 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 29 | GWINDOW1 N NEA | Window | G NWALL NEA | Window5 Detailed Fenestration | RESWINDOW_U_0.5369_SHGC_0.25 | N/A | 3.053 | No | 7.06 | 7.06 | 7.06 | 0.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 30 | G EWALL NEA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_GRD | 0.844 | 0.750 | 18.58 | 23.22 | 18.58 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 31 | GWINDOW1 E NEA | Window | G EWALL NEA | Window5 Detailed Fenestration | RESWINDOW_U_0.5369_SHGC_0.25 | N/A | 3.053 | No | 4.65 | 4.65 | 4.65 | 90.00 | 90.00 | 3.81 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 32 | G SIWALL NEA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-G SIWALL NEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 33 | iz-G EIWALL N2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | G EIWALL N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 34 | G GFLOOR NEA | Floor | CTF - ConductionTransferFunction | GGFLOORNEA_FFACTOR | 0.287 | 0.268 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 35 | G CEILIN NEA | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | G CEILIN NEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 36 | G INTERNALMASS NEA | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 88.25 | 88.25 | 88.25 | 0.00 | 90.00 | 88.25 | 1.00 | 0.00 | G INTERNALMASS NEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 37 | G NWALL N1A | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_GRD | 0.844 | 0.750 | 28.24 | 35.30 | 28.24 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 38 | GWINDOW1 N N1A | Window | G NWALL N1A | Window5 Detailed Fenestration | RESWINDOW_U_0.5369_SHGC_0.25 | N/A | 3.053 | No | 7.06 | 7.06 | 7.06 | 0.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 39 | G SIWALL N1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-G SIWALL N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 40 | G EIWALL N1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | iz-G EIWALL N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 41 | iz-G EIWALL NWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | G EIWALL NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 42 | G GFLOOR N1A | Floor | CTF - ConductionTransferFunction | GGFLOORN1A_FFACTOR | 0.170 | 0.163 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 43 | G CEILIN N1A | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | G CEILIN N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 44 | G INTERNALMASS N1A | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 88.25 | 88.25 | 88.25 | 0.00 | 90.00 | 88.25 | 1.00 | 0.00 | G INTERNALMASS N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 45 | G NWALL N2A | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_GRD | 0.844 | 0.750 | 28.24 | 35.30 | 28.24 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 46 | GWINDOW1 N N2A | Window | G NWALL N2A | Window5 Detailed Fenestration | RESWINDOW_U_0.5369_SHGC_0.25 | N/A | 3.053 | No | 7.06 | 7.06 | 7.06 | 0.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 47 | G SIWALL N2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-G SIWALL N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 48 | G EIWALL N2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | iz-G EIWALL N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 49 | iz-G EIWALL N1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | G EIWALL N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 50 | G GFLOOR N2A | Floor | CTF - ConductionTransferFunction | GGFLOORN2A_FFACTOR | 0.170 | 0.163 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 51 | G CEILIN N2A | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | G CEILIN N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 52 | G INTERNALMASS N2A | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 88.25 | 88.25 | 88.25 | 0.00 | 90.00 | 88.25 | 1.00 | 0.00 | G INTERNALMASS N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 53 | G SWALL S1A | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_GRD | 0.844 | 0.750 | 28.24 | 35.30 | 28.24 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 54 | GWINDOW1 S S1A | Window | G SWALL S1A | Window5 Detailed Fenestration | RESWINDOW_U_0.5369_SHGC_0.25 | N/A | 3.053 | No | 7.06 | 7.06 | 7.06 | 180.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 55 | G NIWALL S1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-G NIWALL S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 56 | G EIWALL S1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | iz-G EIWALL S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 57 | iz-G EIWALL SWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | G EIWALL SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 58 | G GFLOOR S1A | Floor | CTF - ConductionTransferFunction | GGFLOORS1A_FFACTOR | 0.170 | 0.163 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 59 | G CEILIN S1A | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | G CEILIN S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 60 | G INTERNALMASS S1A | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 88.25 | 88.25 | 88.25 | 0.00 | 90.00 | 88.25 | 1.00 | 0.00 | G INTERNALMASS S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 61 | G SWALL S2A | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_GRD | 0.844 | 0.750 | 28.24 | 35.30 | 28.24 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 62 | GWINDOW1 S S2A | Window | G SWALL S2A | Window5 Detailed Fenestration | RESWINDOW_U_0.5369_SHGC_0.25 | N/A | 3.053 | No | 7.06 | 7.06 | 7.06 | 180.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 63 | G NIWALL S2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-G NIWALL S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 64 | G EIWALL S2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | iz-G EIWALL S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 65 | iz-G EIWALL S1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | G EIWALL S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 66 | G GFLOOR S2A | Floor | CTF - ConductionTransferFunction | GGFLOORS2A_FFACTOR | 0.170 | 0.163 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 67 | G CEILIN S2A | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | G CEILIN S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 68 | G INTERNALMASS S2A | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 88.25 | 88.25 | 88.25 | 0.00 | 90.00 | 88.25 | 1.00 | 0.00 | G INTERNALMASS S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 69 | M WWALL SWA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.854 | 0.757 | 18.58 | 23.22 | 18.58 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 70 | MWINDOW1 W SWA | Window | M WWALL SWA | Window5 Detailed Fenestration | RESWINDOW_U_0.5369_SHGC_0.25 | N/A | 3.053 | No | 4.65 | 4.65 | 4.65 | 270.00 | 90.00 | 3.81 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 71 | M SWALL SWA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.854 | 0.757 | 28.24 | 35.30 | 28.24 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 72 | MWINDOW1 S SWA | Window | M SWALL SWA | Window5 Detailed Fenestration | RESWINDOW_U_0.5369_SHGC_0.25 | N/A | 3.053 | No | 7.06 | 7.06 | 7.06 | 180.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 73 | M NIWALL SWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-M NIWALL SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 74 | M EIWALL SWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 90.00 | 90.00 | 3.05 | 7.62 | 0.00 | iz-M EIWALL SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 75 | M GFLOOR SWA | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | M GFLOOR SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 76 | M CEILIN SWA | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | M CEILIN SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 77 | M INTERNALMASS SWA | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 176.50 | 176.50 | 176.50 | 0.00 | 90.00 | 176.50 | 1.00 | 0.00 | M INTERNALMASS SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 78 | M NWALL NWA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.854 | 0.757 | 28.24 | 35.30 | 28.24 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 79 | MWINDOW1 N NWA | Window | M NWALL NWA | Window5 Detailed Fenestration | RESWINDOW_U_0.5369_SHGC_0.25 | N/A | 3.053 | No | 7.06 | 7.06 | 7.06 | 0.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 80 | M WWALL NWA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.854 | 0.757 | 18.58 | 23.22 | 18.58 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 81 | MWINDOW1 W NWA | Window | M WWALL NWA | Window5 Detailed Fenestration | RESWINDOW_U_0.5369_SHGC_0.25 | N/A | 3.053 | No | 4.65 | 4.65 | 4.65 | 270.00 | 90.00 | 3.81 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 82 | M SIWALL NWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-M SIWALL NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 83 | M EIWALL NWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | iz-M EIWALL NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 84 | M GFLOOR NWA | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | M GFLOOR NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 85 | M CEILIN NWA | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | M CEILIN NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 86 | M INTERNALMASS NWA | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 176.50 | 176.50 | 176.50 | 0.00 | 90.00 | 176.50 | 1.00 | 0.00 | M INTERNALMASS NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 87 | M EWALL SEA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.854 | 0.757 | 18.58 | 23.22 | 18.58 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 88 | MWINDOW1 E SEA | Window | M EWALL SEA | Window5 Detailed Fenestration | RESWINDOW_U_0.5369_SHGC_0.25 | N/A | 3.053 | No | 4.65 | 4.65 | 4.65 | 90.00 | 90.00 | 3.81 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 89 | M SWALL SEA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.854 | 0.757 | 28.24 | 35.30 | 28.24 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 90 | MWINDOW1 S SEA | Window | M SWALL SEA | Window5 Detailed Fenestration | RESWINDOW_U_0.5369_SHGC_0.25 | N/A | 3.053 | No | 7.06 | 7.06 | 7.06 | 180.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 91 | M NIWALL SEA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-M NIWALL SEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 92 | iz-M EIWALL S2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | M EIWALL S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 93 | M GFLOOR SEA | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | M GFLOOR SEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 94 | M CEILIN SEA | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | M CEILIN SEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 95 | M INTERNALMASS SEA | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 176.50 | 176.50 | 176.50 | 0.00 | 90.00 | 176.50 | 1.00 | 0.00 | M INTERNALMASS SEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 96 | M NWALL NEA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.854 | 0.757 | 28.24 | 35.30 | 28.24 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 97 | MWINDOW1 N NEA | Window | M NWALL NEA | Window5 Detailed Fenestration | RESWINDOW_U_0.5369_SHGC_0.25 | N/A | 3.053 | No | 7.06 | 7.06 | 7.06 | 0.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 98 | M EWALL NEA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.854 | 0.757 | 18.58 | 23.22 | 18.58 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 99 | MWINDOW1 E NEA | Window | M EWALL NEA | Window5 Detailed Fenestration | RESWINDOW_U_0.5369_SHGC_0.25 | N/A | 3.053 | No | 4.65 | 4.65 | 4.65 | 90.00 | 90.00 | 3.81 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 100 | M SIWALL NEA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-M SIWALL NEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 101 | iz-M EIWALL N2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | M EIWALL N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 102 | M GFLOOR NEA | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | M GFLOOR NEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 103 | M CEILIN NEA | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | M CEILIN NEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 104 | M INTERNALMASS NEA | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 176.50 | 176.50 | 176.50 | 0.00 | 90.00 | 176.50 | 1.00 | 0.00 | M INTERNALMASS NEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 105 | M NWALL N1A | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.854 | 0.757 | 28.24 | 35.30 | 28.24 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 106 | MWINDOW1 N N1A | Window | M NWALL N1A | Window5 Detailed Fenestration | RESWINDOW_U_0.5369_SHGC_0.25 | N/A | 3.053 | No | 7.06 | 7.06 | 7.06 | 0.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 107 | M SIWALL N1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-M SIWALL N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 108 | M EIWALL N1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | iz-M EIWALL N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 109 | iz-M EIWALL NWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | M EIWALL NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 110 | M GFLOOR N1A | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | M GFLOOR N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 111 | M CEILIN N1A | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | M CEILIN N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 112 | M INTERNALMASS N1A | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 176.50 | 176.50 | 176.50 | 0.00 | 90.00 | 176.50 | 1.00 | 0.00 | M INTERNALMASS N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 113 | M NWALL N2A | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.854 | 0.757 | 28.24 | 35.30 | 28.24 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 114 | MWINDOW1 N N2A | Window | M NWALL N2A | Window5 Detailed Fenestration | RESWINDOW_U_0.5369_SHGC_0.25 | N/A | 3.053 | No | 7.06 | 7.06 | 7.06 | 0.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 115 | M SIWALL N2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-M SIWALL N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 116 | M EIWALL N2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | iz-M EIWALL N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 117 | iz-M EIWALL N1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | M EIWALL N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 118 | M GFLOOR N2A | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | M GFLOOR N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 119 | M CEILIN N2A | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | M CEILIN N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 120 | M INTERNALMASS N2A | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 176.50 | 176.50 | 176.50 | 0.00 | 90.00 | 176.50 | 1.00 | 0.00 | M INTERNALMASS N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 121 | M SWALL S1A | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.854 | 0.757 | 28.24 | 35.30 | 28.24 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 122 | MWINDOW1 S S1A | Window | M SWALL S1A | Window5 Detailed Fenestration | RESWINDOW_U_0.5369_SHGC_0.25 | N/A | 3.053 | No | 7.06 | 7.06 | 7.06 | 180.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 123 | M NIWALL S1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-M NIWALL S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 124 | M EIWALL S1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | iz-M EIWALL S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 125 | iz-M EIWALL SWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 270.00 | 90.00 | 3.05 | 7.62 | 0.00 | M EIWALL SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 126 | M GFLOOR S1A | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | M GFLOOR S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 127 | M CEILIN S1A | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | M CEILIN S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 128 | M INTERNALMASS S1A | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 176.50 | 176.50 | 176.50 | 0.00 | 90.00 | 176.50 | 1.00 | 0.00 | M INTERNALMASS S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 129 | M SWALL S2A | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.854 | 0.757 | 28.24 | 35.30 | 28.24 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 130 | MWINDOW1 S S2A | Window | M SWALL S2A | Window5 Detailed Fenestration | RESWINDOW_U_0.5369_SHGC_0.25 | N/A | 3.053 | No | 7.06 | 7.06 | 7.06 | 180.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 131 | M NIWALL S2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-M NIWALL S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 132 | M EIWALL S2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | iz-M EIWALL S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 133 | iz-M EIWALL S1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | M EIWALL S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 134 | M GFLOOR S2A | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | M GFLOOR S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 135 | M CEILIN S2A | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | M CEILIN S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 136 | M INTERNALMASS S2A | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 176.50 | 176.50 | 176.50 | 0.00 | 90.00 | 176.50 | 1.00 | 0.00 | M INTERNALMASS S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 137 | T WWALL SWA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.200 | 1.017 | 18.58 | 23.22 | 18.58 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 138 | TWINDOW1 W SWA | Window | T WWALL SWA | Window5 Detailed Fenestration | RESWINDOW_U_0.5369_SHGC_0.25 | N/A | 3.053 | No | 4.65 | 4.65 | 4.65 | 270.00 | 90.00 | 3.81 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 139 | T SWALL SWA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.200 | 1.017 | 28.24 | 35.30 | 28.24 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 140 | TWINDOW1 S SWA | Window | T SWALL SWA | Window5 Detailed Fenestration | RESWINDOW_U_0.5369_SHGC_0.25 | N/A | 3.053 | No | 7.06 | 7.06 | 7.06 | 180.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 141 | T NIWALL SWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-T NIWALL SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 142 | T EIWALL SWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | iz-T EIWALL SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 143 | T GFLOOR SWA | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | T GFLOOR SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 144 | T ROOF SWA | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.283 | 0.269 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 145 | T INTERNALMASS SWA | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 88.25 | 88.25 | 88.25 | 0.00 | 90.00 | 88.25 | 1.00 | 0.00 | T INTERNALMASS SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 146 | T NWALL NWA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.200 | 1.017 | 28.24 | 35.30 | 28.24 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 147 | TWINDOW1 N NWA | Window | T NWALL NWA | Window5 Detailed Fenestration | RESWINDOW_U_0.5369_SHGC_0.25 | N/A | 3.053 | No | 7.06 | 7.06 | 7.06 | 0.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 148 | T WWALL NWA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.200 | 1.017 | 18.58 | 23.22 | 18.58 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 149 | TWINDOW1 W NWA | Window | T WWALL NWA | Window5 Detailed Fenestration | RESWINDOW_U_0.5369_SHGC_0.25 | N/A | 3.053 | No | 4.65 | 4.65 | 4.65 | 270.00 | 90.00 | 3.81 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 150 | T SIWALL NWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-T SIWALL NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 151 | T EIWALL NWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | iz-T EIWALL NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 152 | T GFLOOR NWA | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | T GFLOOR NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 153 | T ROOF NWA | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.283 | 0.269 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 154 | T INTERNALMASS NWA | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 88.25 | 88.25 | 88.25 | 0.00 | 90.00 | 88.25 | 1.00 | 0.00 | T INTERNALMASS NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 155 | T EWALL SEA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.200 | 1.017 | 18.58 | 23.22 | 18.58 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 156 | TWINDOW1 E SEA | Window | T EWALL SEA | Window5 Detailed Fenestration | RESWINDOW_U_0.5369_SHGC_0.25 | N/A | 3.053 | No | 4.65 | 4.65 | 4.65 | 90.00 | 90.00 | 3.81 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 157 | T SWALL SEA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.200 | 1.017 | 28.24 | 35.30 | 28.24 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 158 | TWINDOW1 S SEA | Window | T SWALL SEA | Window5 Detailed Fenestration | RESWINDOW_U_0.5369_SHGC_0.25 | N/A | 3.053 | No | 7.06 | 7.06 | 7.06 | 180.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 159 | T NIWALL SEA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-T NIWALL SEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 160 | iz-T EIWALL S2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | T EIWALL S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 161 | T GFLOOR SEA | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | T GFLOOR SEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 162 | T ROOF SEA | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.283 | 0.269 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 163 | T INTERNALMASS SEA | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 88.25 | 88.25 | 88.25 | 0.00 | 90.00 | 88.25 | 1.00 | 0.00 | T INTERNALMASS SEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 164 | T NWALL NEA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.200 | 1.017 | 28.24 | 35.30 | 28.24 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 165 | TWINDOW1 N NEA | Window | T NWALL NEA | Window5 Detailed Fenestration | RESWINDOW_U_0.5369_SHGC_0.25 | N/A | 3.053 | No | 7.06 | 7.06 | 7.06 | 0.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 166 | T EWALL NEA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.200 | 1.017 | 18.58 | 23.22 | 18.58 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 167 | TWINDOW1 E NEA | Window | T EWALL NEA | Window5 Detailed Fenestration | RESWINDOW_U_0.5369_SHGC_0.25 | N/A | 3.053 | No | 4.65 | 4.65 | 4.65 | 90.00 | 90.00 | 3.81 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 168 | T SIWALL NEA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-T SIWALL NEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 169 | iz-T EIWALL N2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | T EIWALL N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 170 | T GFLOOR NEA | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | T GFLOOR NEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 171 | T ROOF NEA | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.283 | 0.269 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 172 | T INTERNALMASS NEA | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 88.25 | 88.25 | 88.25 | 0.00 | 90.00 | 88.25 | 1.00 | 0.00 | T INTERNALMASS NEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 173 | T NWALL N1A | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.200 | 1.017 | 28.24 | 35.30 | 28.24 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 174 | TWINDOW1 N N1A | Window | T NWALL N1A | Window5 Detailed Fenestration | RESWINDOW_U_0.5369_SHGC_0.25 | N/A | 3.053 | No | 7.06 | 7.06 | 7.06 | 0.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 175 | T SIWALL N1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-T SIWALL N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 176 | T EIWALL N1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | iz-T EIWALL N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 177 | iz-T EIWALL NWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | T EIWALL NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 178 | T GFLOOR N1A | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | T GFLOOR N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 179 | T ROOF N1A | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.283 | 0.269 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 180 | T INTERNALMASS N1A | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 88.25 | 88.25 | 88.25 | 0.00 | 90.00 | 88.25 | 1.00 | 0.00 | T INTERNALMASS N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 181 | T NWALL N2A | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.200 | 1.017 | 28.24 | 35.30 | 28.24 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 182 | TWINDOW1 N N2A | Window | T NWALL N2A | Window5 Detailed Fenestration | RESWINDOW_U_0.5369_SHGC_0.25 | N/A | 3.053 | No | 7.06 | 7.06 | 7.06 | 0.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 183 | T SIWALL N2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-T SIWALL N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 184 | T EIWALL N2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | iz-T EIWALL N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 185 | iz-T EIWALL N1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | T EIWALL N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 186 | T GFLOOR N2A | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | T GFLOOR N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 187 | T ROOF N2A | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.283 | 0.269 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 188 | T INTERNALMASS N2A | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 88.25 | 88.25 | 88.25 | 0.00 | 90.00 | 88.25 | 1.00 | 0.00 | T INTERNALMASS N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 189 | T SWALL S1A | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.200 | 1.017 | 28.24 | 35.30 | 28.24 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 190 | TWINDOW1 S S1A | Window | T SWALL S1A | Window5 Detailed Fenestration | RESWINDOW_U_0.5369_SHGC_0.25 | N/A | 3.053 | No | 7.06 | 7.06 | 7.06 | 180.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 191 | T NIWALL S1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-T NIWALL S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 192 | T EIWALL S1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | iz-T EIWALL S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 193 | iz-T EIWALL SWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | T EIWALL SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 194 | T GFLOOR S1A | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | T GFLOOR S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 195 | T ROOF S1A | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.283 | 0.269 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 196 | T INTERNALMASS S1A | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 88.25 | 88.25 | 88.25 | 0.00 | 90.00 | 88.25 | 1.00 | 0.00 | T INTERNALMASS S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 197 | T SWALL S2A | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.200 | 1.017 | 28.24 | 35.30 | 28.24 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 198 | TWINDOW1 S S2A | Window | T SWALL S2A | Window5 Detailed Fenestration | RESWINDOW_U_0.5369_SHGC_0.25 | N/A | 3.053 | No | 7.06 | 7.06 | 7.06 | 180.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 199 | T NIWALL S2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-T NIWALL S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 200 | T EIWALL S2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | iz-T EIWALL S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 201 | iz-T EIWALL S1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | T EIWALL S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 202 | T GFLOOR S2A | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | T GFLOOR S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 203 | T ROOF S2A | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.283 | 0.269 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 204 | T INTERNALMASS S2A | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 88.25 | 88.25 | 88.25 | 0.00 | 90.00 | 88.25 | 1.00 | 0.00 | T INTERNALMASS S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 205 | T WWALL C | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.200 | 1.017 | 5.11 | 5.11 | 5.11 | 270.00 | 90.00 | 1.68 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 206 | T EWALL C | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.200 | 1.017 | 3.99 | 5.11 | 3.99 | 90.00 | 90.00 | 1.68 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 207 | TWINDOW14 | Window | T EWALL C | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5369_SHGC_0.25 | N/A | 3.053 | No | 1.11 | 1.11 | 1.11 | 90.00 | 90.00 | 0.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 208 | iz-T NIWALL SWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | T NIWALL SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 209 | iz-T NIWALL S1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | T NIWALL S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 210 | iz-T NIWALL S2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | T NIWALL S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 211 | iz-T NIWALL SEA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | T NIWALL SEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 212 | iz-T SIWALL NWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | T SIWALL NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 213 | iz-T SIWALL N1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | T SIWALL N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 214 | iz-T SIWALL N2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | T SIWALL N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 215 | iz-T SIWALL NEA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | T SIWALL NEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 216 | T FLOOR C | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 77.66 | 77.66 | 77.66 | 90.00 | 180.00 | 1.68 | 46.33 | 0.00 | T FLOOR C | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 217 | T ROOF C | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 77.66 | 77.66 | 77.66 | 180.00 | 0.00 | 46.33 | 1.68 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 218 | G WWALL C | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.844 | 0.750 | 5.11 | 5.11 | 5.11 | 270.00 | 90.00 | 1.68 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 219 | G EWALL C | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.844 | 0.750 | 1.79 | 5.11 | 1.79 | 90.00 | 90.00 | 1.68 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 220 | ENTRANCE DOOR | Window | G EWALL C | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5369_SHGC_0.25 | N/A | 3.053 | No | 3.32 | 3.32 | 3.32 | 90.00 | 90.00 | 1.57 | 2.11 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 221 | iz-G NIWALL SWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | G NIWALL SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 222 | iz-G NIWALL S1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | G NIWALL S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 223 | iz-G NIWALL S2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | G NIWALL S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 224 | iz-G NIWALL SEA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | G NIWALL SEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 225 | iz-G SIWALL NWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | G SIWALL NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 226 | iz-G SIWALL N1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | G SIWALL N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 227 | iz-G SIWALL N2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | G SIWALL N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 228 | iz-G SIWALL NEA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | G SIWALL NEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 229 | G FLOOR C | Floor | CTF - ConductionTransferFunction | GFLOORC_FFACTOR | 5.502E-002 | 5.429E-002 | 77.66 | 77.66 | 77.66 | 90.00 | 180.00 | 1.68 | 46.33 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 230 | G CEILING C | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 77.66 | 77.66 | 77.66 | 180.00 | 0.00 | 46.33 | 1.68 | 0.00 | G CEILING C | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 231 | M WWALL C | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.854 | 0.757 | 5.11 | 5.11 | 5.11 | 270.00 | 90.00 | 1.68 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 232 | M EWALL C | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.854 | 0.757 | 3.99 | 5.11 | 3.99 | 90.00 | 90.00 | 1.68 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 233 | MWINDOW14 | Window | M EWALL C | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5369_SHGC_0.25 | N/A | 3.053 | No | 1.11 | 1.11 | 1.11 | 90.00 | 90.00 | 0.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 234 | iz-M NIWALL SWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | M NIWALL SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 235 | iz-M NIWALL S1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | M NIWALL S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 236 | iz-M NIWALL S2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | M NIWALL S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 237 | iz-M NIWALL SEA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | M NIWALL SEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 238 | iz-M SIWALL NWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | M SIWALL NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 239 | iz-M SIWALL N1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | M SIWALL N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 240 | iz-M SIWALL N2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | M SIWALL N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 241 | iz-M SIWALL NEA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | M SIWALL NEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 242 | M FLOOR C | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 77.66 | 77.66 | 77.66 | 90.00 | 180.00 | 1.68 | 46.33 | 0.00 | M FLOOR C | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 243 | M CEILING C | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 77.66 | 77.66 | 77.66 | 180.00 | 0.00 | 46.33 | 1.68 | 0.00 | M CEILING C | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
| Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
| 1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | Yes | Yes | Yes | Clark and Allen |
| Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
| 1 | NEW YEAR'S DAY | Holiday | InputFile | 01/02 | 1Environment:Special Days |
| Daylight Saving Indicator | Source | Start Date | End Date | |
| 1 | Yes | InputFile | 03/12 | 11/05 |
| Style | Unit Conversion | |
| 1 | Commaandhtml | commaandhtml |
| Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
| 1 | G SW APARTMENT | RunPeriod: RUNPERIOD 1 | 3.7566872147E-002 | 3.3824378857E-002 | Pass | Pass | 1.2392830676E-002 | 1.1174798476E-002 | Pass | Pass |
| 2 | G NW APARTMENT | RunPeriod: RUNPERIOD 1 | 2.0625908950E-002 | 2.9839793678E-002 | Pass | Pass | 2.9696262264E-002 | 3.1406899514E-002 | Pass | Pass |
| 3 | OFFICE | RunPeriod: RUNPERIOD 1 | 3.3105980721E-002 | 2.1990436340E-002 | Pass | Pass | 0.1529055585 | 0.5938681978 | Pass | Pass |
| 4 | G NE APARTMENT | RunPeriod: RUNPERIOD 1 | 2.0048306818E-002 | 2.9252179036E-002 | Pass | Pass | 3.1491868342E-002 | 3.7195845754E-002 | Pass | Pass |
| 5 | G N1 APARTMENT | RunPeriod: RUNPERIOD 1 | 2.4414369069E-002 | 2.9662903605E-002 | Pass | Pass | 2.0052447714E-002 | 1.9725197153E-002 | Pass | Pass |
| 6 | G N2 APARTMENT | RunPeriod: RUNPERIOD 1 | 2.4442553860E-002 | 2.9691172464E-002 | Pass | Pass | 2.0103533155E-002 | 1.9869170826E-002 | Pass | Pass |
| 7 | G S1 APARTMENT | RunPeriod: RUNPERIOD 1 | 3.4485048192E-002 | 3.6779833442E-002 | Pass | Pass | 1.2192216829E-002 | 1.1267139180E-002 | Pass | Pass |
| 8 | G S2 APARTMENT | RunPeriod: RUNPERIOD 1 | 3.4537950746E-002 | 3.6765045032E-002 | Pass | Pass | 1.2193015949E-002 | 1.1264874160E-002 | Pass | Pass |
| 9 | M SW APARTMENT | RunPeriod: RUNPERIOD 1 | 3.7992459799E-002 | 3.1348099999E-002 | Pass | Pass | 1.2053587595E-002 | 1.1063741527E-002 | Pass | Pass |
| 10 | M NW APARTMENT | RunPeriod: RUNPERIOD 1 | 2.1862214742E-002 | 2.7999491352E-002 | Pass | Pass | 2.5449355930E-002 | 2.2941198687E-002 | Pass | Pass |
| 11 | M SE APARTMENT | RunPeriod: RUNPERIOD 1 | 3.8109358154E-002 | 3.1308320296E-002 | Pass | Pass | 1.1744034748E-002 | 1.0603234149E-002 | Pass | Pass |
| 12 | M NE APARTMENT | RunPeriod: RUNPERIOD 1 | 2.1316319435E-002 | 2.7311939828E-002 | Pass | Pass | 2.7736885810E-002 | 2.6122429457E-002 | Pass | Pass |
| 13 | M N1 APARTMENT | RunPeriod: RUNPERIOD 1 | 2.4516091167E-002 | 2.7879036126E-002 | Pass | Pass | 1.4617814707E-002 | 1.3252272118E-002 | Pass | Pass |
| 14 | M N2 APARTMENT | RunPeriod: RUNPERIOD 1 | 2.4551171390E-002 | 2.7874774069E-002 | Pass | Pass | 1.4605400941E-002 | 1.3239964986E-002 | Pass | Pass |
| 15 | M S1 APARTMENT | RunPeriod: RUNPERIOD 1 | 2.2159734633E-002 | 2.0277089722E-002 | Pass | Pass | 2.5679509948E-002 | 8.6872390799E-002 | Pass | Pass |
| 16 | M S2 APARTMENT | RunPeriod: RUNPERIOD 1 | 2.2098126482E-002 | 2.0215499428E-002 | Pass | Pass | 2.5730907362E-002 | 8.7764676159E-002 | Pass | Pass |
| 17 | T SW APARTMENT | RunPeriod: RUNPERIOD 1 | 4.3149788352E-002 | 5.5959498583E-002 | Pass | Pass | 0.1827414991 | 0.7369225162 | Pass | Pass |
| 18 | T NW APARTMENT | RunPeriod: RUNPERIOD 1 | 1.6911796612E-002 | 3.3957057263E-002 | Pass | Pass | 0.1486136008 | 0.4090737281 | Pass | Pass |
| 19 | T SE APARTMENT | RunPeriod: RUNPERIOD 1 | 4.1950043141E-002 | 5.2504407513E-002 | Pass | Pass | 0.2113912536 | 1.1458623168 | Pass | Pass |
| 20 | T NE APARTMENT | RunPeriod: RUNPERIOD 1 | 1.4156216059E-002 | 2.9083945639E-002 | Pass | Pass | 0.1530450946 | 0.4736884908 | Pass | Pass |
| 21 | T N1 APARTMENT | RunPeriod: RUNPERIOD 1 | 1.5581553230E-002 | 3.0614620985E-002 | Pass | Pass | 0.3988862155 | 3.0229718673 | Pass | Pass |
| 22 | T N2 APARTMENT | RunPeriod: RUNPERIOD 1 | 1.5607972000E-002 | 3.0593090105E-002 | Pass | Pass | 0.1866590623 | 0.7089472510 | Pass | Pass |
| 23 | T S1 APARTMENT | RunPeriod: RUNPERIOD 1 | 4.4997615516E-002 | 5.2484262821E-002 | Pass | Pass | 0.1935720241 | 0.8142685607 | Pass | Pass |
| 24 | T S2 APARTMENT | RunPeriod: RUNPERIOD 1 | 4.5074649809E-002 | 5.2495360174E-002 | Pass | Pass | 0.1567618761 | 0.5255204475 | Pass | Pass |
| 25 | T CORRIDOR | RunPeriod: RUNPERIOD 1 | 2.9571239703E-002 | 1.8491917442E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
| 26 | G CORRIDOR | RunPeriod: RUNPERIOD 1 | 0.1474942002 | 0.4453725298 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
| 27 | M CORRIDOR | RunPeriod: RUNPERIOD 1 | 8.8020147650E-003 | 4.6967019153E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 09:14:53
Heat Emission by Components| Envelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
| Heat Emissions [GJ] | 1216.44 | -30.3 | 0.00 | -2.6 | 1900.13 | 3083.61 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 09:14:53
SizingPeriod:DesignDay| Maximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
| NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 6.30 | 0.00 | 6.30 | Wetbulb [C] | 0.50 | 270.00 |
| NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 42.00 | 9.70 | 22.20 | Wetbulb [C] | 3.20 | 320.00 |
| Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
| Jan | 0.60 | 4 | |||
| Feb | 21.40 | 43 | |||
| Mar | 12.00 | 35 | |||
| Apr | 29.10 | 12 | |||
| May | 29.10 | 57 | |||
| Jun | 197.10 | 59 | |||
| Jul | 47.90 | 83 | |||
| Aug | 0.00 | 0 | |||
| Sep | 171.60 | 106 | |||
| Oct | 4.80 | 31 | |||
| Nov | 1.20 | 7 | |||
| Dec | 33.00 | 13 |
| Value | |
| None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 09:14:53
Opaque Exterior| Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
| G SWALL SWA | RES_EXT_WALL_GRD | 0.30 | 0.750 | 0.844 | 35.30 | 28.24 | 180.00 | 90.00 | S |
| G WWALL SWA | RES_EXT_WALL_GRD | 0.30 | 0.750 | 0.844 | 23.22 | 18.58 | 270.00 | 90.00 | W |
| G GFLOOR SWA | GGFLOORSWA_FFACTOR | 1.00 | 0.274 | 0.287 | 88.25 | 88.25 | 90.00 | 180.00 | |
| G NWALL NWA | RES_EXT_WALL_GRD | 0.30 | 0.750 | 0.844 | 35.30 | 28.24 | 0.00 | 90.00 | N |
| G WWALL NWA | RES_EXT_WALL_GRD | 0.30 | 0.750 | 0.844 | 23.22 | 18.58 | 270.00 | 90.00 | W |
| G GFLOOR NWA | GGFLOORNWA_FFACTOR | 1.00 | 0.274 | 0.287 | 88.25 | 88.25 | 90.00 | 180.00 | |
| G SWALL SEA | NONRES_EXT_WALL_GRD | 0.30 | 0.750 | 0.844 | 35.30 | 28.24 | 180.00 | 90.00 | S |
| G EWALL SEA | NONRES_EXT_WALL_GRD | 0.30 | 0.750 | 0.844 | 23.22 | 18.58 | 90.00 | 90.00 | E |
| G GFLOOR SEA | GGFLOORSEA_FFACTOR | 1.00 | 0.274 | 0.287 | 88.25 | 88.25 | 90.00 | 180.00 | |
| G NWALL NEA | RES_EXT_WALL_GRD | 0.30 | 0.750 | 0.844 | 35.30 | 28.24 | 0.00 | 90.00 | N |
| G EWALL NEA | RES_EXT_WALL_GRD | 0.30 | 0.750 | 0.844 | 23.22 | 18.58 | 90.00 | 90.00 | E |
| G GFLOOR NEA | GGFLOORNEA_FFACTOR | 1.00 | 0.274 | 0.287 | 88.25 | 88.25 | 90.00 | 180.00 | |
| G NWALL N1A | RES_EXT_WALL_GRD | 0.30 | 0.750 | 0.844 | 35.30 | 28.24 | 0.00 | 90.00 | N |
| G GFLOOR N1A | GGFLOORN1A_FFACTOR | 1.00 | 0.166 | 0.170 | 88.25 | 88.25 | 90.00 | 180.00 | |
| G NWALL N2A | RES_EXT_WALL_GRD | 0.30 | 0.750 | 0.844 | 35.30 | 28.24 | 0.00 | 90.00 | N |
| G GFLOOR N2A | GGFLOORN2A_FFACTOR | 1.00 | 0.166 | 0.170 | 88.25 | 88.25 | 90.00 | 180.00 | |
| G SWALL S1A | RES_EXT_WALL_GRD | 0.30 | 0.750 | 0.844 | 35.30 | 28.24 | 180.00 | 90.00 | S |
| G GFLOOR S1A | GGFLOORS1A_FFACTOR | 1.00 | 0.166 | 0.170 | 88.25 | 88.25 | 90.00 | 180.00 | |
| G SWALL S2A | RES_EXT_WALL_GRD | 0.30 | 0.750 | 0.844 | 35.30 | 28.24 | 180.00 | 90.00 | S |
| G GFLOOR S2A | GGFLOORS2A_FFACTOR | 1.00 | 0.166 | 0.170 | 88.25 | 88.25 | 90.00 | 180.00 | |
| M WWALL SWA | RES_EXT_WALL_MID | 0.30 | 0.757 | 0.854 | 46.45 | 37.16 | 270.00 | 90.00 | W |
| M SWALL SWA | RES_EXT_WALL_MID | 0.30 | 0.757 | 0.854 | 70.60 | 56.48 | 180.00 | 90.00 | S |
| M NWALL NWA | RES_EXT_WALL_MID | 0.30 | 0.757 | 0.854 | 70.60 | 56.48 | 0.00 | 90.00 | N |
| M WWALL NWA | RES_EXT_WALL_MID | 0.30 | 0.757 | 0.854 | 46.45 | 37.16 | 270.00 | 90.00 | W |
| M EWALL SEA | RES_EXT_WALL_MID | 0.30 | 0.757 | 0.854 | 46.45 | 37.16 | 90.00 | 90.00 | E |
| M SWALL SEA | RES_EXT_WALL_MID | 0.30 | 0.757 | 0.854 | 70.60 | 56.48 | 180.00 | 90.00 | S |
| M NWALL NEA | RES_EXT_WALL_MID | 0.30 | 0.757 | 0.854 | 70.60 | 56.48 | 0.00 | 90.00 | N |
| M EWALL NEA | RES_EXT_WALL_MID | 0.30 | 0.757 | 0.854 | 46.45 | 37.16 | 90.00 | 90.00 | E |
| M NWALL N1A | RES_EXT_WALL_MID | 0.30 | 0.757 | 0.854 | 70.60 | 56.48 | 0.00 | 90.00 | N |
| M NWALL N2A | RES_EXT_WALL_MID | 0.30 | 0.757 | 0.854 | 70.60 | 56.48 | 0.00 | 90.00 | N |
| M SWALL S1A | RES_EXT_WALL_MID | 0.30 | 0.757 | 0.854 | 70.60 | 56.48 | 180.00 | 90.00 | S |
| M SWALL S2A | RES_EXT_WALL_MID | 0.30 | 0.757 | 0.854 | 70.60 | 56.48 | 180.00 | 90.00 | S |
| T WWALL SWA | RES_EXT_WALL_TOP | 0.30 | 1.017 | 1.200 | 23.22 | 18.58 | 270.00 | 90.00 | W |
| T SWALL SWA | RES_EXT_WALL_TOP | 0.30 | 1.017 | 1.200 | 35.30 | 28.24 | 180.00 | 90.00 | S |
| T ROOF SWA | RES_ROOF | 0.55 | 0.273 | 0.283 | 88.25 | 88.25 | 180.00 | 0.00 | |
| T NWALL NWA | RES_EXT_WALL_TOP | 0.30 | 1.017 | 1.200 | 35.30 | 28.24 | 0.00 | 90.00 | N |
| T WWALL NWA | RES_EXT_WALL_TOP | 0.30 | 1.017 | 1.200 | 23.22 | 18.58 | 270.00 | 90.00 | W |
| T ROOF NWA | RES_ROOF | 0.55 | 0.273 | 0.283 | 88.25 | 88.25 | 180.00 | 0.00 | |
| T EWALL SEA | RES_EXT_WALL_TOP | 0.30 | 1.017 | 1.200 | 23.22 | 18.58 | 90.00 | 90.00 | E |
| T SWALL SEA | RES_EXT_WALL_TOP | 0.30 | 1.017 | 1.200 | 35.30 | 28.24 | 180.00 | 90.00 | S |
| T ROOF SEA | RES_ROOF | 0.55 | 0.273 | 0.283 | 88.25 | 88.25 | 180.00 | 0.00 | |
| T NWALL NEA | RES_EXT_WALL_TOP | 0.30 | 1.017 | 1.200 | 35.30 | 28.24 | 0.00 | 90.00 | N |
| T EWALL NEA | RES_EXT_WALL_TOP | 0.30 | 1.017 | 1.200 | 23.22 | 18.58 | 90.00 | 90.00 | E |
| T ROOF NEA | RES_ROOF | 0.55 | 0.273 | 0.283 | 88.25 | 88.25 | 180.00 | 0.00 | |
| T NWALL N1A | RES_EXT_WALL_TOP | 0.30 | 1.017 | 1.200 | 35.30 | 28.24 | 0.00 | 90.00 | N |
| T ROOF N1A | RES_ROOF | 0.55 | 0.273 | 0.283 | 88.25 | 88.25 | 180.00 | 0.00 | |
| T NWALL N2A | RES_EXT_WALL_TOP | 0.30 | 1.017 | 1.200 | 35.30 | 28.24 | 0.00 | 90.00 | N |
| T ROOF N2A | RES_ROOF | 0.55 | 0.273 | 0.283 | 88.25 | 88.25 | 180.00 | 0.00 | |
| T SWALL S1A | RES_EXT_WALL_TOP | 0.30 | 1.017 | 1.200 | 35.30 | 28.24 | 180.00 | 90.00 | S |
| T ROOF S1A | RES_ROOF | 0.55 | 0.273 | 0.283 | 88.25 | 88.25 | 180.00 | 0.00 | |
| T SWALL S2A | RES_EXT_WALL_TOP | 0.30 | 1.017 | 1.200 | 35.30 | 28.24 | 180.00 | 90.00 | S |
| T ROOF S2A | RES_ROOF | 0.55 | 0.273 | 0.283 | 88.25 | 88.25 | 180.00 | 0.00 | |
| T WWALL C | NONRES_EXT_WALL_TOP | 0.30 | 1.017 | 1.200 | 5.11 | 5.11 | 270.00 | 90.00 | W |
| T EWALL C | NONRES_EXT_WALL_TOP | 0.30 | 1.017 | 1.200 | 5.11 | 3.99 | 90.00 | 90.00 | E |
| T ROOF C | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 77.66 | 77.66 | 180.00 | 0.00 | |
| G WWALL C | NONRES_EXT_WALL_GRD | 0.30 | 0.750 | 0.844 | 5.11 | 5.11 | 270.00 | 90.00 | W |
| G EWALL C | NONRES_EXT_WALL_GRD | 0.30 | 0.750 | 0.844 | 5.11 | 1.79 | 90.00 | 90.00 | E |
| G FLOOR C | GFLOORC_FFACTOR | 1.00 | 0.055 | 0.055 | 77.66 | 77.66 | 90.00 | 180.00 | |
| M WWALL C | NONRES_EXT_WALL_MID | 0.30 | 0.757 | 0.854 | 10.22 | 10.22 | 270.00 | 90.00 | W |
| M EWALL C | NONRES_EXT_WALL_MID | 0.30 | 0.757 | 0.854 | 10.22 | 7.99 | 90.00 | 90.00 | E |
| Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
| G NIWALL SWA | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 0.00 | 90.00 | N |
| G EIWALL SWA | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 90.00 | 90.00 | E |
| G CEILIN SWA | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 88.25 | 88.25 | 180.00 | 0.00 | |
| G SIWALL NWA | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 180.00 | 90.00 | S |
| G EIWALL NWA | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 90.00 | 90.00 | E |
| G CEILIN NWA | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 88.25 | 88.25 | 180.00 | 0.00 | |
| G NIWALL SEA | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 0.00 | 90.00 | N |
| iz-G EIWALL S2A | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 270.00 | 90.00 | W |
| G CEILIN SEA | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 88.25 | 88.25 | 180.00 | 0.00 | |
| G SIWALL NEA | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 180.00 | 90.00 | S |
| iz-G EIWALL N2A | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 270.00 | 90.00 | W |
| G CEILIN NEA | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 88.25 | 88.25 | 180.00 | 0.00 | |
| G SIWALL N1A | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 180.00 | 90.00 | S |
| G EIWALL N1A | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 90.00 | 90.00 | E |
| iz-G EIWALL NWA | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 270.00 | 90.00 | W |
| G CEILIN N1A | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 88.25 | 88.25 | 180.00 | 0.00 | |
| G SIWALL N2A | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 180.00 | 90.00 | S |
| G EIWALL N2A | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 90.00 | 90.00 | E |
| iz-G EIWALL N1A | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 270.00 | 90.00 | W |
| G CEILIN N2A | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 88.25 | 88.25 | 180.00 | 0.00 | |
| G NIWALL S1A | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 0.00 | 90.00 | N |
| G EIWALL S1A | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 90.00 | 90.00 | E |
| iz-G EIWALL SWA | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 270.00 | 90.00 | W |
| G CEILIN S1A | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 88.25 | 88.25 | 180.00 | 0.00 | |
| G NIWALL S2A | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 0.00 | 90.00 | N |
| G EIWALL S2A | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 90.00 | 90.00 | E |
| iz-G EIWALL S1A | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 270.00 | 90.00 | W |
| G CEILIN S2A | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 88.25 | 88.25 | 180.00 | 0.00 | |
| M NIWALL SWA | INT_WALL | 0.30 | 2.511 | 6.299 | 70.60 | 70.60 | 0.00 | 90.00 | N |
| M EIWALL SWA | INT_WALL | 0.30 | 2.511 | 6.299 | 46.45 | 46.45 | 90.00 | 90.00 | E |
| M GFLOOR SWA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 176.50 | 176.50 | 90.00 | 180.00 | |
| M CEILIN SWA | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 176.50 | 176.50 | 180.00 | 0.00 | |
| M SIWALL NWA | INT_WALL | 0.30 | 2.511 | 6.299 | 70.60 | 70.60 | 180.00 | 90.00 | S |
| M EIWALL NWA | INT_WALL | 0.30 | 2.511 | 6.299 | 46.45 | 46.45 | 90.00 | 90.00 | E |
| M GFLOOR NWA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 176.50 | 176.50 | 90.00 | 180.00 | |
| M CEILIN NWA | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 176.50 | 176.50 | 180.00 | 0.00 | |
| M NIWALL SEA | INT_WALL | 0.30 | 2.511 | 6.299 | 70.60 | 70.60 | 0.00 | 90.00 | N |
| iz-M EIWALL S2A | INT_WALL | 0.30 | 2.511 | 6.299 | 46.45 | 46.45 | 270.00 | 90.00 | W |
| M GFLOOR SEA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 176.50 | 176.50 | 90.00 | 180.00 | |
| M CEILIN SEA | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 176.50 | 176.50 | 180.00 | 0.00 | |
| M SIWALL NEA | INT_WALL | 0.30 | 2.511 | 6.299 | 70.60 | 70.60 | 180.00 | 90.00 | S |
| iz-M EIWALL N2A | INT_WALL | 0.30 | 2.511 | 6.299 | 46.45 | 46.45 | 270.00 | 90.00 | W |
| M GFLOOR NEA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 176.50 | 176.50 | 90.00 | 180.00 | |
| M CEILIN NEA | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 176.50 | 176.50 | 180.00 | 0.00 | |
| M SIWALL N1A | INT_WALL | 0.30 | 2.511 | 6.299 | 70.60 | 70.60 | 180.00 | 90.00 | S |
| M EIWALL N1A | INT_WALL | 0.30 | 2.511 | 6.299 | 46.45 | 46.45 | 90.00 | 90.00 | E |
| iz-M EIWALL NWA | INT_WALL | 0.30 | 2.511 | 6.299 | 46.45 | 46.45 | 270.00 | 90.00 | W |
| M GFLOOR N1A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 176.50 | 176.50 | 90.00 | 180.00 | |
| M CEILIN N1A | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 176.50 | 176.50 | 180.00 | 0.00 | |
| M SIWALL N2A | INT_WALL | 0.30 | 2.511 | 6.299 | 70.60 | 70.60 | 180.00 | 90.00 | S |
| M EIWALL N2A | INT_WALL | 0.30 | 2.511 | 6.299 | 46.45 | 46.45 | 90.00 | 90.00 | E |
| iz-M EIWALL N1A | INT_WALL | 0.30 | 2.511 | 6.299 | 46.45 | 46.45 | 270.00 | 90.00 | W |
| M GFLOOR N2A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 176.50 | 176.50 | 90.00 | 180.00 | |
| M CEILIN N2A | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 176.50 | 176.50 | 180.00 | 0.00 | |
| M NIWALL S1A | INT_WALL | 0.30 | 2.511 | 6.299 | 70.60 | 70.60 | 0.00 | 90.00 | N |
| M EIWALL S1A | INT_WALL | 0.30 | 2.511 | 6.299 | 46.45 | 46.45 | 90.00 | 90.00 | E |
| iz-M EIWALL SWA | INT_WALL | 0.30 | 2.511 | 6.299 | 46.45 | 46.45 | 270.00 | 90.00 | W |
| M GFLOOR S1A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 176.50 | 176.50 | 90.00 | 180.00 | |
| M CEILIN S1A | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 176.50 | 176.50 | 180.00 | 0.00 | |
| M NIWALL S2A | INT_WALL | 0.30 | 2.511 | 6.299 | 70.60 | 70.60 | 0.00 | 90.00 | N |
| M EIWALL S2A | INT_WALL | 0.30 | 2.511 | 6.299 | 46.45 | 46.45 | 90.00 | 90.00 | E |
| iz-M EIWALL S1A | INT_WALL | 0.30 | 2.511 | 6.299 | 46.45 | 46.45 | 270.00 | 90.00 | W |
| M GFLOOR S2A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 176.50 | 176.50 | 90.00 | 180.00 | |
| M CEILIN S2A | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 176.50 | 176.50 | 180.00 | 0.00 | |
| T NIWALL SWA | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 0.00 | 90.00 | N |
| T EIWALL SWA | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 90.00 | 90.00 | E |
| T GFLOOR SWA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 88.25 | 88.25 | 90.00 | 180.00 | |
| T SIWALL NWA | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 180.00 | 90.00 | S |
| T EIWALL NWA | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 90.00 | 90.00 | E |
| T GFLOOR NWA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 88.25 | 88.25 | 90.00 | 180.00 | |
| T NIWALL SEA | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 0.00 | 90.00 | N |
| iz-T EIWALL S2A | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 270.00 | 90.00 | W |
| T GFLOOR SEA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 88.25 | 88.25 | 90.00 | 180.00 | |
| T SIWALL NEA | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 180.00 | 90.00 | S |
| iz-T EIWALL N2A | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 270.00 | 90.00 | W |
| T GFLOOR NEA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 88.25 | 88.25 | 90.00 | 180.00 | |
| T SIWALL N1A | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 180.00 | 90.00 | S |
| T EIWALL N1A | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 90.00 | 90.00 | E |
| iz-T EIWALL NWA | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 270.00 | 90.00 | W |
| T GFLOOR N1A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 88.25 | 88.25 | 90.00 | 180.00 | |
| T SIWALL N2A | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 180.00 | 90.00 | S |
| T EIWALL N2A | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 90.00 | 90.00 | E |
| iz-T EIWALL N1A | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 270.00 | 90.00 | W |
| T GFLOOR N2A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 88.25 | 88.25 | 90.00 | 180.00 | |
| T NIWALL S1A | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 0.00 | 90.00 | N |
| T EIWALL S1A | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 90.00 | 90.00 | E |
| iz-T EIWALL SWA | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 270.00 | 90.00 | W |
| T GFLOOR S1A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 88.25 | 88.25 | 90.00 | 180.00 | |
| T NIWALL S2A | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 0.00 | 90.00 | N |
| T EIWALL S2A | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 90.00 | 90.00 | E |
| iz-T EIWALL S1A | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 270.00 | 90.00 | W |
| T GFLOOR S2A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 88.25 | 88.25 | 90.00 | 180.00 | |
| iz-T NIWALL SWA | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 180.00 | 90.00 | S |
| iz-T NIWALL S1A | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 180.00 | 90.00 | S |
| iz-T NIWALL S2A | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 180.00 | 90.00 | S |
| iz-T NIWALL SEA | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 180.00 | 90.00 | S |
| iz-T SIWALL NWA | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 0.00 | 90.00 | N |
| iz-T SIWALL N1A | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 0.00 | 90.00 | N |
| iz-T SIWALL N2A | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 0.00 | 90.00 | N |
| iz-T SIWALL NEA | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 0.00 | 90.00 | N |
| T FLOOR C | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 77.66 | 77.66 | 90.00 | 180.00 | |
| iz-G NIWALL SWA | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 180.00 | 90.00 | S |
| iz-G NIWALL S1A | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 180.00 | 90.00 | S |
| iz-G NIWALL S2A | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 180.00 | 90.00 | S |
| iz-G NIWALL SEA | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 180.00 | 90.00 | S |
| iz-G SIWALL NWA | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 0.00 | 90.00 | N |
| iz-G SIWALL N1A | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 0.00 | 90.00 | N |
| iz-G SIWALL N2A | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 0.00 | 90.00 | N |
| iz-G SIWALL NEA | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 0.00 | 90.00 | N |
| G CEILING C | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 77.66 | 77.66 | 180.00 | 0.00 | |
| iz-M NIWALL SWA | INT_WALL | 0.30 | 2.511 | 6.299 | 70.60 | 70.60 | 180.00 | 90.00 | S |
| iz-M NIWALL S1A | INT_WALL | 0.30 | 2.511 | 6.299 | 70.60 | 70.60 | 180.00 | 90.00 | S |
| iz-M NIWALL S2A | INT_WALL | 0.30 | 2.511 | 6.299 | 70.60 | 70.60 | 180.00 | 90.00 | S |
| iz-M NIWALL SEA | INT_WALL | 0.30 | 2.511 | 6.299 | 70.60 | 70.60 | 180.00 | 90.00 | S |
| iz-M SIWALL NWA | INT_WALL | 0.30 | 2.511 | 6.299 | 70.60 | 70.60 | 0.00 | 90.00 | N |
| iz-M SIWALL N1A | INT_WALL | 0.30 | 2.511 | 6.299 | 70.60 | 70.60 | 0.00 | 90.00 | N |
| iz-M SIWALL N2A | INT_WALL | 0.30 | 2.511 | 6.299 | 70.60 | 70.60 | 0.00 | 90.00 | N |
| iz-M SIWALL NEA | INT_WALL | 0.30 | 2.511 | 6.299 | 70.60 | 70.60 | 0.00 | 90.00 | N |
| M FLOOR C | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 155.32 | 155.32 | 90.00 | 180.00 | |
| M CEILING C | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 155.32 | 155.32 | 180.00 | 0.00 | |
| G INTERNALMASS SWA | INTERIORFURNISHINGS | 0.30 | 0.800 | 88.25 | 0.00 | 90.00 | N | ||
| G INTERNALMASS NWA | INTERIORFURNISHINGS | 0.30 | 0.800 | 88.25 | 0.00 | 90.00 | N | ||
| G INTERNALMASS SEA | INTERIORFURNISHINGS | 0.30 | 0.800 | 88.25 | 0.00 | 90.00 | N | ||
| G INTERNALMASS NEA | INTERIORFURNISHINGS | 0.30 | 0.800 | 88.25 | 0.00 | 90.00 | N | ||
| G INTERNALMASS N1A | INTERIORFURNISHINGS | 0.30 | 0.800 | 88.25 | 0.00 | 90.00 | N | ||
| G INTERNALMASS N2A | INTERIORFURNISHINGS | 0.30 | 0.800 | 88.25 | 0.00 | 90.00 | N | ||
| G INTERNALMASS S1A | INTERIORFURNISHINGS | 0.30 | 0.800 | 88.25 | 0.00 | 90.00 | N | ||
| G INTERNALMASS S2A | INTERIORFURNISHINGS | 0.30 | 0.800 | 88.25 | 0.00 | 90.00 | N | ||
| M INTERNALMASS SWA | INTERIORFURNISHINGS | 0.30 | 0.800 | 353.00 | 0.00 | 90.00 | N | ||
| M INTERNALMASS NWA | INTERIORFURNISHINGS | 0.30 | 0.800 | 353.00 | 0.00 | 90.00 | N | ||
| M INTERNALMASS SEA | INTERIORFURNISHINGS | 0.30 | 0.800 | 353.00 | 0.00 | 90.00 | N | ||
| M INTERNALMASS NEA | INTERIORFURNISHINGS | 0.30 | 0.800 | 353.00 | 0.00 | 90.00 | N | ||
| M INTERNALMASS N1A | INTERIORFURNISHINGS | 0.30 | 0.800 | 353.00 | 0.00 | 90.00 | N | ||
| M INTERNALMASS N2A | INTERIORFURNISHINGS | 0.30 | 0.800 | 353.00 | 0.00 | 90.00 | N | ||
| M INTERNALMASS S1A | INTERIORFURNISHINGS | 0.30 | 0.800 | 353.00 | 0.00 | 90.00 | N | ||
| M INTERNALMASS S2A | INTERIORFURNISHINGS | 0.30 | 0.800 | 353.00 | 0.00 | 90.00 | N | ||
| T INTERNALMASS SWA | INTERIORFURNISHINGS | 0.30 | 0.800 | 88.25 | 0.00 | 90.00 | N | ||
| T INTERNALMASS NWA | INTERIORFURNISHINGS | 0.30 | 0.800 | 88.25 | 0.00 | 90.00 | N | ||
| T INTERNALMASS SEA | INTERIORFURNISHINGS | 0.30 | 0.800 | 88.25 | 0.00 | 90.00 | N | ||
| T INTERNALMASS NEA | INTERIORFURNISHINGS | 0.30 | 0.800 | 88.25 | 0.00 | 90.00 | N | ||
| T INTERNALMASS N1A | INTERIORFURNISHINGS | 0.30 | 0.800 | 88.25 | 0.00 | 90.00 | N | ||
| T INTERNALMASS N2A | INTERIORFURNISHINGS | 0.30 | 0.800 | 88.25 | 0.00 | 90.00 | N | ||
| T INTERNALMASS S1A | INTERIORFURNISHINGS | 0.30 | 0.800 | 88.25 | 0.00 | 90.00 | N | ||
| T INTERNALMASS S2A | INTERIORFURNISHINGS | 0.30 | 0.800 | 88.25 | 0.00 | 90.00 | N |
| Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
| GWINDOW1 S SWA | RESWINDOW_U_0.5369_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 3.053 | 0.251 | 0.251 | No | G SWALL SWA | 180.00 | 90.00 | S | |||||||
| GWINDOW1 W SWA | RESWINDOW_U_0.5369_SHGC_0.25 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 3.053 | 0.251 | 0.251 | No | G WWALL SWA | 270.00 | 90.00 | W | |||||||
| GWINDOW1 N NWA | RESWINDOW_U_0.5369_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 3.053 | 0.251 | 0.251 | No | G NWALL NWA | 0.00 | 90.00 | N | |||||||
| GWINDOW1 W NWA | RESWINDOW_U_0.5369_SHGC_0.25 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 3.053 | 0.251 | 0.251 | No | G WWALL NWA | 270.00 | 90.00 | W | |||||||
| GWINDOW1 S SEA | NONRESWINDOW_U_0.5369_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 3.053 | 0.251 | 0.251 | No | G SWALL SEA | 180.00 | 90.00 | S | |||||||
| GWINDOW1 E SEA | NONRESWINDOW_U_0.5369_SHGC_0.25 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 3.053 | 0.251 | 0.251 | No | G EWALL SEA | 90.00 | 90.00 | E | |||||||
| GWINDOW1 N NEA | RESWINDOW_U_0.5369_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 3.053 | 0.251 | 0.251 | No | G NWALL NEA | 0.00 | 90.00 | N | |||||||
| GWINDOW1 E NEA | RESWINDOW_U_0.5369_SHGC_0.25 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 3.053 | 0.251 | 0.251 | No | G EWALL NEA | 90.00 | 90.00 | E | |||||||
| GWINDOW1 N N1A | RESWINDOW_U_0.5369_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 3.053 | 0.251 | 0.251 | No | G NWALL N1A | 0.00 | 90.00 | N | |||||||
| GWINDOW1 N N2A | RESWINDOW_U_0.5369_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 3.053 | 0.251 | 0.251 | No | G NWALL N2A | 0.00 | 90.00 | N | |||||||
| GWINDOW1 S S1A | RESWINDOW_U_0.5369_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 3.053 | 0.251 | 0.251 | No | G SWALL S1A | 180.00 | 90.00 | S | |||||||
| GWINDOW1 S S2A | RESWINDOW_U_0.5369_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 3.053 | 0.251 | 0.251 | No | G SWALL S2A | 180.00 | 90.00 | S | |||||||
| MWINDOW1 W SWA | RESWINDOW_U_0.5369_SHGC_0.25 | 4.65 | 0.00 | 0.00 | 4.65 | 9.29 | 3.053 | 0.251 | 0.251 | No | M WWALL SWA | 270.00 | 90.00 | W | |||||||
| MWINDOW1 S SWA | RESWINDOW_U_0.5369_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 3.053 | 0.251 | 0.251 | No | M SWALL SWA | 180.00 | 90.00 | S | |||||||
| MWINDOW1 N NWA | RESWINDOW_U_0.5369_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 3.053 | 0.251 | 0.251 | No | M NWALL NWA | 0.00 | 90.00 | N | |||||||
| MWINDOW1 W NWA | RESWINDOW_U_0.5369_SHGC_0.25 | 4.65 | 0.00 | 0.00 | 4.65 | 9.29 | 3.053 | 0.251 | 0.251 | No | M WWALL NWA | 270.00 | 90.00 | W | |||||||
| MWINDOW1 E SEA | RESWINDOW_U_0.5369_SHGC_0.25 | 4.65 | 0.00 | 0.00 | 4.65 | 9.29 | 3.053 | 0.251 | 0.251 | No | M EWALL SEA | 90.00 | 90.00 | E | |||||||
| MWINDOW1 S SEA | RESWINDOW_U_0.5369_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 3.053 | 0.251 | 0.251 | No | M SWALL SEA | 180.00 | 90.00 | S | |||||||
| MWINDOW1 N NEA | RESWINDOW_U_0.5369_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 3.053 | 0.251 | 0.251 | No | M NWALL NEA | 0.00 | 90.00 | N | |||||||
| MWINDOW1 E NEA | RESWINDOW_U_0.5369_SHGC_0.25 | 4.65 | 0.00 | 0.00 | 4.65 | 9.29 | 3.053 | 0.251 | 0.251 | No | M EWALL NEA | 90.00 | 90.00 | E | |||||||
| MWINDOW1 N N1A | RESWINDOW_U_0.5369_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 3.053 | 0.251 | 0.251 | No | M NWALL N1A | 0.00 | 90.00 | N | |||||||
| MWINDOW1 N N2A | RESWINDOW_U_0.5369_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 3.053 | 0.251 | 0.251 | No | M NWALL N2A | 0.00 | 90.00 | N | |||||||
| MWINDOW1 S S1A | RESWINDOW_U_0.5369_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 3.053 | 0.251 | 0.251 | No | M SWALL S1A | 180.00 | 90.00 | S | |||||||
| MWINDOW1 S S2A | RESWINDOW_U_0.5369_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 3.053 | 0.251 | 0.251 | No | M SWALL S2A | 180.00 | 90.00 | S | |||||||
| TWINDOW1 W SWA | RESWINDOW_U_0.5369_SHGC_0.25 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 3.053 | 0.251 | 0.251 | No | T WWALL SWA | 270.00 | 90.00 | W | |||||||
| TWINDOW1 S SWA | RESWINDOW_U_0.5369_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 3.053 | 0.251 | 0.251 | No | T SWALL SWA | 180.00 | 90.00 | S | |||||||
| TWINDOW1 N NWA | RESWINDOW_U_0.5369_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 3.053 | 0.251 | 0.251 | No | T NWALL NWA | 0.00 | 90.00 | N | |||||||
| TWINDOW1 W NWA | RESWINDOW_U_0.5369_SHGC_0.25 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 3.053 | 0.251 | 0.251 | No | T WWALL NWA | 270.00 | 90.00 | W | |||||||
| TWINDOW1 E SEA | RESWINDOW_U_0.5369_SHGC_0.25 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 3.053 | 0.251 | 0.251 | No | T EWALL SEA | 90.00 | 90.00 | E | |||||||
| TWINDOW1 S SEA | RESWINDOW_U_0.5369_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 3.053 | 0.251 | 0.251 | No | T SWALL SEA | 180.00 | 90.00 | S | |||||||
| TWINDOW1 N NEA | RESWINDOW_U_0.5369_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 3.053 | 0.251 | 0.251 | No | T NWALL NEA | 0.00 | 90.00 | N | |||||||
| TWINDOW1 E NEA | RESWINDOW_U_0.5369_SHGC_0.25 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 3.053 | 0.251 | 0.251 | No | T EWALL NEA | 90.00 | 90.00 | E | |||||||
| TWINDOW1 N N1A | RESWINDOW_U_0.5369_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 3.053 | 0.251 | 0.251 | No | T NWALL N1A | 0.00 | 90.00 | N | |||||||
| TWINDOW1 N N2A | RESWINDOW_U_0.5369_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 3.053 | 0.251 | 0.251 | No | T NWALL N2A | 0.00 | 90.00 | N | |||||||
| TWINDOW1 S S1A | RESWINDOW_U_0.5369_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 3.053 | 0.251 | 0.251 | No | T SWALL S1A | 180.00 | 90.00 | S | |||||||
| TWINDOW1 S S2A | RESWINDOW_U_0.5369_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 3.053 | 0.251 | 0.251 | No | T SWALL S2A | 180.00 | 90.00 | S | |||||||
| TWINDOW14 | NONRESWINDOW_U_0.5369_SHGC_0.25 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 3.053 | 0.251 | 0.251 | No | T EWALL C | 90.00 | 90.00 | E | |||||||
| ENTRANCE DOOR | NONRESWINDOW_U_0.5369_SHGC_0.25 | 3.32 | 0.00 | 0.00 | 3.32 | 3.32 | 3.053 | 0.251 | 0.251 | No | G EWALL C | 90.00 | 90.00 | E | |||||||
| MWINDOW14 | NONRESWINDOW_U_0.5369_SHGC_0.25 | 1.11 | 0.00 | 0.00 | 1.11 | 2.23 | 3.053 | 0.251 | 0.251 | No | M EWALL C | 90.00 | 90.00 | E | |||||||
| Total or Average | 306.92 | 3.053 | 0.251 | 0.251 | |||||||||||||||||
| North Total or Average | 112.97 | 3.053 | 0.251 | 0.251 | |||||||||||||||||
| Non-North Total or Average | 193.95 | 3.053 | 0.251 | 0.251 |
| Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
| None |
| Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
| Total or Average | 0.00 | - | - | - |
| Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
| None |
| Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
| None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 09:14:53
Sunlit Fraction| March 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
| GWINDOW1 S SWA | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| GWINDOW1 W SWA | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
| GWINDOW1 N NWA | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| GWINDOW1 W NWA | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
| GWINDOW1 S SEA | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| GWINDOW1 E SEA | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
| GWINDOW1 N NEA | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| GWINDOW1 E NEA | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
| GWINDOW1 N N1A | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| GWINDOW1 N N2A | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| GWINDOW1 S S1A | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| GWINDOW1 S S2A | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| MWINDOW1 W SWA | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
| MWINDOW1 S SWA | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| MWINDOW1 N NWA | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| MWINDOW1 W NWA | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
| MWINDOW1 E SEA | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
| MWINDOW1 S SEA | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| MWINDOW1 N NEA | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| MWINDOW1 E NEA | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
| MWINDOW1 N N1A | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| MWINDOW1 N N2A | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| MWINDOW1 S S1A | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| MWINDOW1 S S2A | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| TWINDOW1 W SWA | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
| TWINDOW1 S SWA | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| TWINDOW1 N NWA | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| TWINDOW1 W NWA | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
| TWINDOW1 E SEA | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
| TWINDOW1 S SEA | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| TWINDOW1 N NEA | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| TWINDOW1 E NEA | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
| TWINDOW1 N N1A | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| TWINDOW1 N N2A | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| TWINDOW1 S S1A | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| TWINDOW1 S S2A | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| TWINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
| ENTRANCE DOOR | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
| MWINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
| Name | Type | Shaded Construction | Control | Glare Control | |
| None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 09:14:53
Interior Lighting| Zone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
| LIGHTING_HARDWIRED_GSW | G SW APARTMENT | G SW APARTMENT | GENERAL | 7.8684 | 88.25 | 694.38 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.32 |
| LIGHTING_HARDWIRED_GNW | G NW APARTMENT | G NW APARTMENT | GENERAL | 7.8684 | 88.25 | 694.38 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.32 |
| LIGHTING_HARDWIRED_OFFICE | OFFICE | OFFICE | GENERAL | 9.7532 | 88.25 | 860.71 | LightsWired | LTG_SCH_OFFICE | 46.69 | 168.00 | 45.77 | 0.0000 | Y | 7.40 |
| LIGHTING_HARDWIRED_GNE | G NE APARTMENT | G NE APARTMENT | GENERAL | 7.8684 | 88.25 | 694.38 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.32 |
| LIGHTING_HARDWIRED_GN1 | G N1 APARTMENT | G N1 APARTMENT | GENERAL | 7.8684 | 88.25 | 694.38 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.32 |
| LIGHTING_HARDWIRED_GN2 | G N2 APARTMENT | G N2 APARTMENT | GENERAL | 7.8684 | 88.25 | 694.38 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.32 |
| LIGHTING_HARDWIRED_GS1 | G S1 APARTMENT | G S1 APARTMENT | GENERAL | 7.8684 | 88.25 | 694.38 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.32 |
| LIGHTING_HARDWIRED_GS2 | G S2 APARTMENT | G S2 APARTMENT | GENERAL | 7.8684 | 88.25 | 694.38 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.32 |
| LIGHTING_HARDWIRED_MSW | M SW APARTMENT | M SW APARTMENT | GENERAL | 7.8684 | 176.50 | 1388.76 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 2.63 |
| LIGHTING_HARDWIRED_MNW | M NW APARTMENT | M NW APARTMENT | GENERAL | 7.8684 | 176.50 | 1388.76 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 2.63 |
| LIGHTING_HARDWIRED_MSE | M SE APARTMENT | M SE APARTMENT | GENERAL | 7.8684 | 176.50 | 1388.76 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 2.63 |
| LIGHTING_HARDWIRED_MNE | M NE APARTMENT | M NE APARTMENT | GENERAL | 7.8684 | 176.50 | 1388.76 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 2.63 |
| LIGHTING_HARDWIRED_MN1 | M N1 APARTMENT | M N1 APARTMENT | GENERAL | 7.8684 | 176.50 | 1388.76 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 2.63 |
| LIGHTING_HARDWIRED_MN2 | M N2 APARTMENT | M N2 APARTMENT | GENERAL | 7.8684 | 176.50 | 1388.76 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 2.63 |
| LIGHTING_HARDWIRED_MS1 | M S1 APARTMENT | M S1 APARTMENT | GENERAL | 7.8684 | 176.50 | 1388.76 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 2.63 |
| LIGHTING_HARDWIRED_MS2 | M S2 APARTMENT | M S2 APARTMENT | GENERAL | 7.8684 | 176.50 | 1388.76 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 2.63 |
| LIGHTING_HARDWIRED_TSW | T SW APARTMENT | T SW APARTMENT | GENERAL | 7.8684 | 88.25 | 694.38 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.32 |
| LIGHTING_HARDWIRED_TNW | T NW APARTMENT | T NW APARTMENT | GENERAL | 7.8684 | 88.25 | 694.38 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.32 |
| LIGHTING_HARDWIRED_TSE | T SE APARTMENT | T SE APARTMENT | GENERAL | 7.8684 | 88.25 | 694.38 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.32 |
| LIGHTING_HARDWIRED_TNE | T NE APARTMENT | T NE APARTMENT | GENERAL | 7.8684 | 88.25 | 694.38 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.32 |
| LIGHTING_HARDWIRED_TN1 | T N1 APARTMENT | T N1 APARTMENT | GENERAL | 7.8684 | 88.25 | 694.38 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.32 |
| LIGHTING_HARDWIRED_TN2 | T N2 APARTMENT | T N2 APARTMENT | GENERAL | 7.8684 | 88.25 | 694.38 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.32 |
| LIGHTING_HARDWIRED_TS1 | T S1 APARTMENT | T S1 APARTMENT | GENERAL | 7.8684 | 88.25 | 694.38 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.32 |
| LIGHTING_HARDWIRED_TS2 | T S2 APARTMENT | T S2 APARTMENT | GENERAL | 7.8684 | 88.25 | 694.38 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.32 |
| LIGHTING_HARDWIRED_GC | G CORRIDOR | G CORRIDOR | GENERAL | 4.7725 | 77.66 | 370.63 | LightsWired | LTG_SCH_CORRIDOR | 168.00 | 168.00 | 168.00 | 0.0000 | N | 11.69 |
| LIGHTING_HARDWIRED_MC | M CORRIDOR | M CORRIDOR | GENERAL | 4.7725 | 155.32 | 741.26 | LightsWired | LTG_SCH_CORRIDOR | 168.00 | 168.00 | 168.00 | 0.0000 | N | 23.38 |
| LIGHTING_HARDWIRED_TC | T CORRIDOR | T CORRIDOR | GENERAL | 4.7725 | 77.66 | 370.63 | LightsWired | LTG_SCH_CORRIDOR | 168.00 | 168.00 | 168.00 | 0.0000 | N | 11.69 |
| LIGHTING_PLUGIN_GSW | G SW APARTMENT | G SW APARTMENT | GENERAL | 0.8234 | 88.25 | 72.67 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.14 |
| LIGHTING_PLUGIN_GNW | G NW APARTMENT | G NW APARTMENT | GENERAL | 0.8234 | 88.25 | 72.67 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.14 |
| LIGHTING_PLUGIN_GNE | G NE APARTMENT | G NE APARTMENT | GENERAL | 0.8234 | 88.25 | 72.67 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.14 |
| LIGHTING_PLUGIN_GN1 | G N1 APARTMENT | G N1 APARTMENT | GENERAL | 0.8234 | 88.25 | 72.67 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.14 |
| LIGHTING_PLUGIN_GN2 | G N2 APARTMENT | G N2 APARTMENT | GENERAL | 0.8234 | 88.25 | 72.67 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.14 |
| LIGHTING_PLUGIN_GS1 | G S1 APARTMENT | G S1 APARTMENT | GENERAL | 0.8234 | 88.25 | 72.67 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.14 |
| LIGHTING_PLUGIN_GS2 | G S2 APARTMENT | G S2 APARTMENT | GENERAL | 0.8234 | 88.25 | 72.67 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.14 |
| LIGHTING_PLUGIN_MSW | M SW APARTMENT | M SW APARTMENT | GENERAL | 0.8234 | 176.50 | 145.34 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.28 |
| LIGHTING_PLUGIN_MNW | M NW APARTMENT | M NW APARTMENT | GENERAL | 0.8234 | 176.50 | 145.34 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.28 |
| LIGHTING_PLUGIN_MSE | M SE APARTMENT | M SE APARTMENT | GENERAL | 0.8234 | 176.50 | 145.34 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.28 |
| LIGHTING_PLUGIN_MNE | M NE APARTMENT | M NE APARTMENT | GENERAL | 0.8234 | 176.50 | 145.34 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.28 |
| LIGHTING_PLUGIN_MN1 | M N1 APARTMENT | M N1 APARTMENT | GENERAL | 0.8234 | 176.50 | 145.34 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.28 |
| LIGHTING_PLUGIN_MN2 | M N2 APARTMENT | M N2 APARTMENT | GENERAL | 0.8234 | 176.50 | 145.34 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.28 |
| LIGHTING_PLUGIN_MS1 | M S1 APARTMENT | M S1 APARTMENT | GENERAL | 0.8234 | 176.50 | 145.34 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.28 |
| LIGHTING_PLUGIN_MS2 | M S2 APARTMENT | M S2 APARTMENT | GENERAL | 0.8234 | 176.50 | 145.34 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.28 |
| LIGHTING_PLUGIN_TSW | T SW APARTMENT | T SW APARTMENT | GENERAL | 0.8234 | 88.25 | 72.67 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.14 |
| LIGHTING_PLUGIN_TNW | T NW APARTMENT | T NW APARTMENT | GENERAL | 0.8234 | 88.25 | 72.67 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.14 |
| LIGHTING_PLUGIN_TSE | T SE APARTMENT | T SE APARTMENT | GENERAL | 0.8234 | 88.25 | 72.67 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.14 |
| LIGHTING_PLUGIN_TNE | T NE APARTMENT | T NE APARTMENT | GENERAL | 0.8234 | 88.25 | 72.67 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.14 |
| LIGHTING_PLUGIN_TN1 | T N1 APARTMENT | T N1 APARTMENT | GENERAL | 0.8234 | 88.25 | 72.67 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.14 |
| LIGHTING_PLUGIN_TN2 | T N2 APARTMENT | T N2 APARTMENT | GENERAL | 0.8234 | 88.25 | 72.67 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.14 |
| LIGHTING_PLUGIN_TS1 | T S1 APARTMENT | T S1 APARTMENT | GENERAL | 0.8234 | 88.25 | 72.67 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.14 |
| LIGHTING_PLUGIN_TS2 | T S2 APARTMENT | T S2 APARTMENT | GENERAL | 0.8234 | 88.25 | 72.67 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.14 |
| Interior Lighting Total | 4.4498 | 5870.34 | 26121.74 | 75.91 |
| Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
| None |
| Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
| FACADE LIGHTING | 3183.33 | AstronomicalClock | - | 83.75 | 83.75 | 50.05 | |
| Exterior Lighting Total | 3183.33 | 50.05 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 09:14:53
Central Plant| Type | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
| None |
| Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
| SPLIT GSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 6971.54 | 5583.47 | 1388.07 | 0.80 | 3.91 | |||
| SPLIT GNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 6918.18 | 5537.91 | 1380.27 | 0.80 | 3.91 | |||
| SPLIT OFFICE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7760.12 | 6215.82 | 1544.30 | 0.80 | 3.91 | |||
| SPLIT GNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 6733.38 | 5390.25 | 1343.12 | 0.80 | 3.91 | |||
| SPLIT GN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 6022.49 | 4819.71 | 1202.78 | 0.80 | 3.91 | |||
| SPLIT GN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 6018.72 | 4816.55 | 1202.17 | 0.80 | 3.91 | |||
| SPLIT GS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 6098.60 | 4882.92 | 1215.68 | 0.80 | 3.91 | |||
| SPLIT GS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 6140.62 | 4918.07 | 1222.55 | 0.80 | 3.91 | |||
| SPLIT MSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 15535.94 | 12440.94 | 3095.00 | 0.80 | 3.91 | |||
| SPLIT MNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 15438.65 | 12365.95 | 3072.70 | 0.80 | 3.91 | |||
| SPLIT MSE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 15073.48 | 12068.88 | 3004.61 | 0.80 | 3.91 | |||
| SPLIT MNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 14972.01 | 11992.49 | 2979.52 | 0.80 | 3.91 | |||
| SPLIT MN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 13194.89 | 10566.68 | 2628.21 | 0.80 | 3.91 | |||
| SPLIT MN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 13185.83 | 10559.10 | 2626.73 | 0.80 | 3.91 | |||
| SPLIT MS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 13332.44 | 10675.82 | 2656.62 | 0.80 | 3.91 | |||
| SPLIT MS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 13323.46 | 10668.24 | 2655.22 | 0.80 | 3.91 | |||
| SPLIT TSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 8706.75 | 6973.52 | 1733.24 | 0.80 | 3.91 | |||
| SPLIT TNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 8704.26 | 6970.22 | 1734.03 | 0.80 | 3.91 | |||
| SPLIT TSE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 8351.00 | 6686.55 | 1664.45 | 0.80 | 3.91 | |||
| SPLIT TNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 8347.04 | 6682.87 | 1664.17 | 0.80 | 3.91 | |||
| SPLIT TN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7494.05 | 6000.94 | 1493.11 | 0.80 | 3.91 | |||
| SPLIT TN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7481.64 | 5990.64 | 1491.00 | 0.80 | 3.91 | |||
| SPLIT TS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7505.33 | 6008.14 | 1497.19 | 0.80 | 3.91 | |||
| SPLIT TS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7493.00 | 5997.87 | 1495.14 | 0.80 | 3.91 |
| DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
| SPLIT GSW COOLING COIL | 6664.3 | 3.17 | 10.82 | 11.25 | 10.65 | 10.60 | |
| SPLIT GNW COOLING COIL | 6611.9 | 3.17 | 10.81 | 11.24 | 10.64 | 10.58 | |
| SPLIT OFFICE COOLING COIL | 7408.2 | 3.15 | 10.76 | 11.19 | 10.58 | 10.51 | |
| SPLIT GNE COOLING COIL | 6436.1 | 3.17 | 10.82 | 11.25 | 10.64 | 10.59 | |
| SPLIT GN1 COOLING COIL | 5759.1 | 3.18 | 10.84 | 11.27 | 10.66 | 10.62 | |
| SPLIT GN2 COOLING COIL | 5755.5 | 3.18 | 10.84 | 11.27 | 10.66 | 10.62 | |
| SPLIT GS1 COOLING COIL | 5833.9 | 3.18 | 10.86 | 11.29 | 10.68 | 10.64 | |
| SPLIT GS2 COOLING COIL | 5873.9 | 3.18 | 10.85 | 11.29 | 10.68 | 10.64 | |
| SPLIT MSW COOLING COIL | 14845.6 | 3.17 | 10.81 | 11.24 | 10.63 | 10.57 | |
| SPLIT MNW COOLING COIL | 14750.3 | 3.17 | 10.80 | 11.23 | 10.62 | 10.56 | |
| SPLIT MSE COOLING COIL | 14405.8 | 3.17 | 10.81 | 11.24 | 10.64 | 10.58 | |
| SPLIT MNE COOLING COIL | 14306.3 | 3.17 | 10.81 | 11.23 | 10.63 | 10.57 | |
| SPLIT MN1 COOLING COIL | 12613.5 | 3.17 | 10.82 | 11.25 | 10.65 | 10.60 | |
| SPLIT MN2 COOLING COIL | 12604.9 | 3.17 | 10.82 | 11.26 | 10.65 | 10.60 | |
| SPLIT MS1 COOLING COIL | 12748.5 | 3.18 | 10.84 | 11.27 | 10.66 | 10.62 | |
| SPLIT MS2 COOLING COIL | 12740.0 | 3.18 | 10.84 | 11.27 | 10.66 | 10.62 | |
| SPLIT TSW COOLING COIL | 8316.4 | 3.16 | 10.79 | 11.22 | 10.61 | 10.55 | |
| SPLIT TNW COOLING COIL | 8313.0 | 3.16 | 10.78 | 11.21 | 10.60 | 10.54 | |
| SPLIT TSE COOLING COIL | 7977.9 | 3.16 | 10.80 | 11.22 | 10.62 | 10.56 | |
| SPLIT TNE COOLING COIL | 7973.1 | 3.16 | 10.79 | 11.22 | 10.61 | 10.55 | |
| SPLIT TN1 COOLING COIL | 7160.1 | 3.17 | 10.80 | 11.23 | 10.62 | 10.56 | |
| SPLIT TN2 COOLING COIL | 7148.3 | 3.17 | 10.80 | 11.23 | 10.62 | 10.57 | |
| SPLIT TS1 COOLING COIL | 7172.1 | 3.17 | 10.81 | 11.24 | 10.63 | 10.58 | |
| SPLIT TS2 COOLING COIL | 7160.3 | 3.17 | 10.81 | 11.24 | 10.63 | 10.58 |
| DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
| SPLIT GSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT GNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT OFFICE COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT GNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT GN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT GN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT GS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT GS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT MSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT MNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT MSE COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT MNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT MN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT MN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT MS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT MS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT TSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT TNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT TSE COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT TNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT TN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT TN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT TS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT TS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed |
| DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
| None |
| Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
| SPLIT GSW HEATING COIL | Coil:Heating:Fuel | 9183.72 | 0.80 | |
| SPLIT GNW HEATING COIL | Coil:Heating:Fuel | 9157.08 | 0.80 | |
| SPLIT OFFICE HEATING COIL | Coil:Heating:Fuel | 10670.50 | 0.80 | |
| SPLIT GNE HEATING COIL | Coil:Heating:Fuel | 8900.92 | 0.80 | |
| SPLIT GN1 HEATING COIL | Coil:Heating:Fuel | 7937.48 | 0.80 | |
| SPLIT GN2 HEATING COIL | Coil:Heating:Fuel | 7932.27 | 0.80 | |
| SPLIT GS1 HEATING COIL | Coil:Heating:Fuel | 7973.63 | 0.80 | |
| SPLIT GS2 HEATING COIL | Coil:Heating:Fuel | 8030.97 | 0.80 | |
| SPLIT MSW HEATING COIL | Coil:Heating:Fuel | 20526.71 | 0.80 | |
| SPLIT MNW HEATING COIL | Coil:Heating:Fuel | 20470.73 | 0.80 | |
| SPLIT MSE HEATING COIL | Coil:Heating:Fuel | 19881.10 | 0.80 | |
| SPLIT MNE HEATING COIL | Coil:Heating:Fuel | 19825.67 | 0.80 | |
| SPLIT MN1 HEATING COIL | Coil:Heating:Fuel | 17426.36 | 0.80 | |
| SPLIT MN2 HEATING COIL | Coil:Heating:Fuel | 17413.82 | 0.80 | |
| SPLIT MS1 HEATING COIL | Coil:Heating:Fuel | 17497.52 | 0.80 | |
| SPLIT MS2 HEATING COIL | Coil:Heating:Fuel | 17484.91 | 0.80 | |
| SPLIT TSW HEATING COIL | Coil:Heating:Fuel | 11549.36 | 0.80 | |
| SPLIT TNW HEATING COIL | Coil:Heating:Fuel | 11573.12 | 0.80 | |
| SPLIT TSE HEATING COIL | Coil:Heating:Fuel | 11057.92 | 0.80 | |
| SPLIT TNE HEATING COIL | Coil:Heating:Fuel | 11081.43 | 0.80 | |
| SPLIT TN1 HEATING COIL | Coil:Heating:Fuel | 9944.01 | 0.80 | |
| SPLIT TN2 HEATING COIL | Coil:Heating:Fuel | 9926.97 | 0.80 | |
| SPLIT TS1 HEATING COIL | Coil:Heating:Fuel | 9924.27 | 0.80 | |
| SPLIT TS2 HEATING COIL | Coil:Heating:Fuel | 9907.24 | 0.80 |
| Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
| G SW APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| G SW APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| G NW APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| G NW APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| G NE APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| G NE APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| G N1 APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| G N1 APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| G N2 APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| G N2 APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| G S1 APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| G S1 APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| G S2 APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| G S2 APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| M SW APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.05 | 40.01 | 770.84 | 1.00 | 4.13 | General | ||
| M SW APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.05 | 40.01 | 770.84 | 1.00 | 4.13 | General | ||
| M NW APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.05 | 40.01 | 770.84 | 1.00 | 4.13 | General | ||
| M NW APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.05 | 40.01 | 770.84 | 1.00 | 4.13 | General | ||
| M SE APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.05 | 40.01 | 770.84 | 1.00 | 4.13 | General | ||
| M SE APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.05 | 40.01 | 770.84 | 1.00 | 4.13 | General | ||
| M NE APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.05 | 40.01 | 770.84 | 1.00 | 4.13 | General | ||
| M NE APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.05 | 40.01 | 770.84 | 1.00 | 4.13 | General | ||
| M N1 APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.05 | 40.01 | 770.84 | 1.00 | 4.13 | General | ||
| M N1 APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.05 | 40.01 | 770.84 | 1.00 | 4.13 | General | ||
| M N2 APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.05 | 40.01 | 770.84 | 1.00 | 4.13 | General | ||
| M N2 APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.05 | 40.01 | 770.84 | 1.00 | 4.13 | General | ||
| M S1 APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.05 | 40.01 | 770.84 | 1.00 | 4.13 | General | ||
| M S1 APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.05 | 40.01 | 770.84 | 1.00 | 4.13 | General | ||
| M S2 APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.05 | 40.01 | 770.84 | 1.00 | 4.13 | General | ||
| M S2 APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.05 | 40.01 | 770.84 | 1.00 | 4.13 | General | ||
| T SW APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| T SW APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| T NW APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| T NW APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| T SE APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| T SE APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| T NE APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| T NE APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| T N1 APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| T N1 APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| T N2 APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| T N2 APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| T S1 APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| T S1 APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| T S2 APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| T S2 APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| SPLIT GSW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.39 | 438.68 | 1120.11 | 1.00 | 1.73 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 19:00:00 |
| SPLIT GNW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.39 | 437.35 | 1120.11 | 1.00 | 1.73 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 19:00:00 |
| SPLIT OFFICE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.45 | 502.73 | 1120.11 | 1.00 | 1.66 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 09:00:00 |
| SPLIT GNE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.38 | 424.48 | 1120.11 | 1.00 | 1.75 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 19:00:00 |
| SPLIT GN1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.34 | 376.07 | 1120.11 | 1.00 | 1.82 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 19:00:00 |
| SPLIT GN2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.34 | 375.81 | 1120.11 | 1.00 | 1.82 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 19:00:00 |
| SPLIT GS1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.34 | 377.88 | 1120.11 | 1.00 | 1.82 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 19:00:00 |
| SPLIT GS2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.34 | 380.76 | 1120.11 | 1.00 | 1.81 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 19:00:00 |
| SPLIT MSW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.88 | 985.86 | 1120.11 | 1.00 | 1.41 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 19:00:00 |
| SPLIT MNW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.88 | 983.06 | 1120.11 | 1.00 | 1.41 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 19:00:00 |
| SPLIT MSE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.85 | 953.42 | 1120.11 | 1.00 | 1.42 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 19:00:00 |
| SPLIT MNE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.85 | 950.65 | 1120.11 | 1.00 | 1.42 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 19:00:00 |
| SPLIT MN1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.74 | 830.09 | 1120.11 | 1.00 | 1.46 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 19:00:00 |
| SPLIT MN2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.74 | 829.46 | 1120.11 | 1.00 | 1.46 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 19:00:00 |
| SPLIT MS1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.74 | 833.65 | 1120.11 | 1.00 | 1.46 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 19:00:00 |
| SPLIT MS2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.74 | 833.02 | 1120.11 | 1.00 | 1.46 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 19:00:00 |
| SPLIT TSW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.50 | 557.54 | 1120.11 | 1.00 | 1.61 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 19:00:00 |
| SPLIT TNW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.50 | 558.75 | 1120.11 | 1.00 | 1.61 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 19:00:00 |
| SPLIT TSE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.48 | 532.85 | 1120.11 | 1.00 | 1.63 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 19:00:00 |
| SPLIT TNE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.48 | 534.04 | 1120.11 | 1.00 | 1.63 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 19:00:00 |
| SPLIT TN1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.43 | 476.89 | 1120.11 | 1.00 | 1.68 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 19:00:00 |
| SPLIT TN2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.42 | 476.04 | 1120.11 | 1.00 | 1.68 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 19:00:00 |
| SPLIT TS1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.42 | 475.89 | 1120.11 | 1.00 | 1.68 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 19:00:00 |
| SPLIT TS2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.42 | 475.04 | 1120.11 | 1.00 | 1.69 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 19:00:00 |
| Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
| None |
| Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
| G SW APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.77 |
| G NW APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.77 |
| G NE APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.77 |
| G N1 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.77 |
| G N2 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.77 |
| G S1 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.77 |
| G S2 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.77 |
| M SW APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.79 |
| M NW APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.79 |
| M SE APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.79 |
| M NE APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.79 |
| M N1 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.79 |
| M N2 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.79 |
| M S1 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.79 |
| M S2 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.79 |
| T SW APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.77 |
| T NW APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.77 |
| T SE APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.77 |
| T NE APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.77 |
| T N1 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.77 |
| T N2 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.77 |
| T S1 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.77 |
| T S2 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.77 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 09:14:53
Zone Sensible Cooling| Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
| G SW APARTMENT | 4492.98 | 5391.57 | 61.09 | 0.326 | 0.392 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 19:00:00 | 24.00 | 24.00 | 0.00815 | 38.22 | 0.00915 | 0.026 | 0.00 |
| G NW APARTMENT | 4479.72 | 5375.66 | 60.91 | 0.325 | 0.390 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 19:00:00 | 24.00 | 24.00 | 0.00812 | 38.22 | 0.00915 | 0.026 | 0.00 |
| OFFICE | 5076.72 | 6092.07 | 69.03 | 0.374 | 0.449 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 09:00:00 | 23.90 | 23.90 | 0.00803 | 36.66 | 0.00915 | 0.038 | 0.00 |
| G NE APARTMENT | 4350.80 | 5220.96 | 59.16 | 0.316 | 0.379 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 19:00:00 | 24.00 | 24.00 | 0.00812 | 38.22 | 0.00915 | 0.026 | 0.00 |
| G N1 APARTMENT | 3867.28 | 4640.74 | 52.59 | 0.280 | 0.336 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 19:00:00 | 24.00 | 24.00 | 0.00813 | 38.22 | 0.00915 | 0.026 | 0.00 |
| G N2 APARTMENT | 3864.64 | 4637.56 | 52.55 | 0.280 | 0.336 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 19:00:00 | 24.00 | 24.00 | 0.00813 | 38.22 | 0.00915 | 0.026 | 0.00 |
| G S1 APARTMENT | 3885.35 | 4662.42 | 52.83 | 0.281 | 0.337 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 19:00:00 | 24.00 | 24.00 | 0.00819 | 38.22 | 0.00915 | 0.026 | 0.00 |
| G S2 APARTMENT | 3914.07 | 4696.89 | 53.22 | 0.283 | 0.340 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 19:00:00 | 24.00 | 24.00 | 0.00819 | 38.22 | 0.00915 | 0.026 | 0.00 |
| M SW APARTMENT | 10076.44 | 12091.73 | 137.02 | 0.733 | 0.880 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 19:00:00 | 24.00 | 24.00 | 0.00814 | 38.22 | 0.00915 | 0.052 | 0.00 |
| M NW APARTMENT | 10048.47 | 12058.17 | 136.64 | 0.731 | 0.878 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 19:00:00 | 24.00 | 24.00 | 0.00812 | 38.22 | 0.00915 | 0.052 | 0.00 |
| M SE APARTMENT | 9749.79 | 11699.75 | 132.58 | 0.709 | 0.851 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 19:00:00 | 24.00 | 24.00 | 0.00815 | 38.22 | 0.00915 | 0.052 | 0.00 |
| M NE APARTMENT | 9722.12 | 11666.55 | 132.20 | 0.707 | 0.849 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 19:00:00 | 24.00 | 24.00 | 0.00812 | 38.22 | 0.00915 | 0.052 | 0.00 |
| M N1 APARTMENT | 8513.29 | 10215.95 | 115.76 | 0.618 | 0.741 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 19:00:00 | 24.00 | 24.00 | 0.00813 | 38.22 | 0.00915 | 0.052 | 0.00 |
| M N2 APARTMENT | 8506.99 | 10208.39 | 115.68 | 0.617 | 0.741 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 19:00:00 | 24.00 | 24.00 | 0.00813 | 38.22 | 0.00915 | 0.052 | 0.00 |
| M S1 APARTMENT | 8548.77 | 10258.52 | 116.24 | 0.620 | 0.744 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 19:00:00 | 24.00 | 24.00 | 0.00817 | 38.22 | 0.00915 | 0.052 | 0.00 |
| M S2 APARTMENT | 8542.42 | 10250.91 | 116.16 | 0.620 | 0.744 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 19:00:00 | 24.00 | 24.00 | 0.00817 | 38.22 | 0.00915 | 0.052 | 0.00 |
| T SW APARTMENT | 5688.95 | 6826.74 | 77.36 | 0.415 | 0.498 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 19:00:00 | 24.00 | 24.00 | 0.00812 | 38.22 | 0.00915 | 0.026 | 0.00 |
| T NW APARTMENT | 5701.05 | 6841.26 | 77.52 | 0.416 | 0.499 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 19:00:00 | 24.00 | 24.00 | 0.00811 | 38.22 | 0.00915 | 0.026 | 0.00 |
| T SE APARTMENT | 5441.62 | 6529.94 | 73.99 | 0.396 | 0.476 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 19:00:00 | 24.00 | 24.00 | 0.00813 | 38.22 | 0.00915 | 0.026 | 0.00 |
| T NE APARTMENT | 5453.59 | 6544.30 | 74.16 | 0.397 | 0.477 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 19:00:00 | 24.00 | 24.00 | 0.00811 | 38.22 | 0.00915 | 0.026 | 0.00 |
| T N1 APARTMENT | 4880.24 | 5856.29 | 66.36 | 0.355 | 0.426 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 19:00:00 | 24.00 | 24.00 | 0.00811 | 38.22 | 0.00915 | 0.026 | 0.00 |
| T N2 APARTMENT | 4871.61 | 5845.93 | 66.24 | 0.354 | 0.425 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 19:00:00 | 24.00 | 24.00 | 0.00811 | 38.22 | 0.00915 | 0.026 | 0.00 |
| T S1 APARTMENT | 4870.12 | 5844.15 | 66.22 | 0.354 | 0.425 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 19:00:00 | 24.00 | 24.00 | 0.00813 | 38.22 | 0.00915 | 0.026 | 0.00 |
| T S2 APARTMENT | 4861.50 | 5833.80 | 66.11 | 0.353 | 0.424 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 19:00:00 | 24.00 | 24.00 | 0.00813 | 38.22 | 0.00915 | 0.026 | 0.00 |
| Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
| G SW APARTMENT | 584.92 | 701.91 | 7.95 | 0.026 | 0.031 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 21.10 | 21.10 | 0.00788 | 6.30 | 0.00607 | 0.026 | 0.00 |
| G NW APARTMENT | 463.60 | 556.32 | 6.30 | 0.020 | 0.026 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | 21.10 | 21.10 | 0.00849 | 6.30 | 0.00607 | 0.026 | 0.00 |
| OFFICE | 965.16 | 1158.20 | 13.12 | 0.043 | 0.051 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 18:50:00 | 21.10 | 21.10 | 0.00792 | 6.30 | 0.00607 | 0.038 | 0.00 |
| G NE APARTMENT | 463.23 | 555.87 | 6.30 | 0.020 | 0.026 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | 21.10 | 21.10 | 0.00849 | 6.30 | 0.00607 | 0.026 | 0.00 |
| G N1 APARTMENT | 177.00 | 212.41 | 2.41 | 0.008 | 0.026 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | 21.10 | 21.10 | 0.00938 | 6.30 | 0.00607 | 0.026 | 0.00 |
| G N2 APARTMENT | 177.00 | 212.39 | 2.41 | 0.008 | 0.026 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | 21.10 | 21.10 | 0.00938 | 6.30 | 0.00607 | 0.026 | 0.00 |
| G S1 APARTMENT | 298.05 | 357.65 | 4.05 | 0.013 | 0.026 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 21.10 | 21.10 | 0.00784 | 6.30 | 0.00607 | 0.026 | 0.00 |
| G S2 APARTMENT | 306.48 | 367.77 | 4.17 | 0.014 | 0.026 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 04:40:00 | 21.10 | 21.10 | 0.00784 | 6.30 | 0.00607 | 0.026 | 0.00 |
| M SW APARTMENT | 1225.67 | 1470.80 | 16.67 | 0.054 | 0.065 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 21.10 | 21.10 | 0.00783 | 6.30 | 0.00607 | 0.052 | 0.00 |
| M NW APARTMENT | 949.03 | 1138.83 | 12.90 | 0.042 | 0.052 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 21.10 | 21.10 | 0.00841 | 6.30 | 0.00607 | 0.052 | 0.00 |
| M SE APARTMENT | 1224.74 | 1469.69 | 16.65 | 0.054 | 0.065 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 21.10 | 21.10 | 0.00783 | 6.30 | 0.00607 | 0.052 | 0.00 |
| M NE APARTMENT | 948.02 | 1137.62 | 12.89 | 0.042 | 0.052 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 21.10 | 21.10 | 0.00841 | 6.30 | 0.00607 | 0.052 | 0.00 |
| M N1 APARTMENT | 244.07 | 292.88 | 3.32 | 0.011 | 0.052 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 21.10 | 21.10 | 0.00986 | 6.30 | 0.00607 | 0.052 | 0.00 |
| M N2 APARTMENT | 244.04 | 292.85 | 3.32 | 0.011 | 0.052 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 21.10 | 21.10 | 0.00986 | 6.30 | 0.00607 | 0.052 | 0.00 |
| M S1 APARTMENT | 524.08 | 628.90 | 7.13 | 0.023 | 0.052 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 21.10 | 21.10 | 0.00770 | 6.30 | 0.00607 | 0.052 | 0.00 |
| M S2 APARTMENT | 524.06 | 628.88 | 7.13 | 0.023 | 0.052 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 21.10 | 21.10 | 0.00770 | 6.30 | 0.00607 | 0.052 | 0.00 |
| T SW APARTMENT | 1331.05 | 1597.26 | 18.10 | 0.059 | 0.071 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 21.10 | 21.10 | 0.00790 | 6.30 | 0.00607 | 0.026 | 0.00 |
| T NW APARTMENT | 1183.16 | 1419.80 | 16.09 | 0.052 | 0.063 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 21.10 | 21.10 | 0.00815 | 6.30 | 0.00607 | 0.026 | 0.00 |
| T SE APARTMENT | 1330.57 | 1596.69 | 18.09 | 0.059 | 0.071 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 21.10 | 21.10 | 0.00790 | 6.30 | 0.00607 | 0.026 | 0.00 |
| T NE APARTMENT | 1182.63 | 1419.15 | 16.08 | 0.052 | 0.063 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 21.10 | 21.10 | 0.00815 | 6.30 | 0.00607 | 0.026 | 0.00 |
| T N1 APARTMENT | 792.79 | 951.34 | 10.78 | 0.035 | 0.042 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 21.10 | 21.10 | 0.00829 | 6.30 | 0.00607 | 0.026 | 0.00 |
| T N2 APARTMENT | 792.77 | 951.32 | 10.78 | 0.035 | 0.042 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 21.10 | 21.10 | 0.00829 | 6.30 | 0.00607 | 0.026 | 0.00 |
| T S1 APARTMENT | 941.63 | 1129.95 | 12.80 | 0.042 | 0.050 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 21.10 | 21.10 | 0.00791 | 6.30 | 0.00607 | 0.026 | 0.00 |
| T S2 APARTMENT | 941.61 | 1129.94 | 12.80 | 0.042 | 0.050 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 21.10 | 21.10 | 0.00791 | 6.30 | 0.00607 | 0.026 | 0.00 |
| Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
| SPLIT GSW | 0.39 | 0.39 | 0.03 | 0.03 | 0.3916 | 0.3916 | 0.3916 | 1.0000 | 1.0000 |
| SPLIT GNW | 0.39 | 0.39 | 0.03 | 0.03 | 0.3905 | 0.3905 | 0.3905 | 1.0000 | 1.0000 |
| SPLIT OFFICE | 0.45 | 0.45 | 0.05 | 0.05 | 0.4488 | 0.4488 | 0.4488 | 1.0000 | 1.0000 |
| SPLIT GNE | 0.38 | 0.38 | 0.03 | 0.03 | 0.3790 | 0.3790 | 0.3790 | 1.0000 | 1.0000 |
| SPLIT GN1 | 0.34 | 0.34 | 0.03 | 0.03 | 0.3357 | 0.3357 | 0.3357 | 1.0000 | 1.0000 |
| SPLIT GN2 | 0.34 | 0.34 | 0.03 | 0.03 | 0.3355 | 0.3355 | 0.3355 | 1.0000 | 1.0000 |
| SPLIT GS1 | 0.34 | 0.34 | 0.03 | 0.03 | 0.3374 | 0.3374 | 0.3374 | 1.0000 | 1.0000 |
| SPLIT GS2 | 0.34 | 0.34 | 0.03 | 0.03 | 0.3399 | 0.3399 | 0.3399 | 1.0000 | 1.0000 |
| SPLIT MSW | 0.88 | 0.88 | 0.07 | 0.07 | 0.8801 | 0.8801 | 0.8801 | 1.0000 | 1.0000 |
| SPLIT MNW | 0.88 | 0.88 | 0.05 | 0.05 | 0.8776 | 0.8776 | 0.8776 | 1.0000 | 1.0000 |
| SPLIT MSE | 0.85 | 0.85 | 0.06 | 0.06 | 0.8512 | 0.8512 | 0.8512 | 1.0000 | 1.0000 |
| SPLIT MNE | 0.85 | 0.85 | 0.05 | 0.05 | 0.8487 | 0.8487 | 0.8487 | 1.0000 | 1.0000 |
| SPLIT MN1 | 0.74 | 0.74 | 0.05 | 0.05 | 0.7411 | 0.7411 | 0.7411 | 1.0000 | 1.0000 |
| SPLIT MN2 | 0.74 | 0.74 | 0.05 | 0.05 | 0.7405 | 0.7405 | 0.7405 | 1.0000 | 1.0000 |
| SPLIT MS1 | 0.74 | 0.74 | 0.05 | 0.05 | 0.7443 | 0.7443 | 0.7443 | 1.0000 | 1.0000 |
| SPLIT MS2 | 0.74 | 0.74 | 0.05 | 0.05 | 0.7437 | 0.7437 | 0.7437 | 1.0000 | 1.0000 |
| SPLIT TSW | 0.50 | 0.50 | 0.07 | 0.07 | 0.4978 | 0.4978 | 0.4978 | 1.0000 | 1.0000 |
| SPLIT TNW | 0.50 | 0.50 | 0.06 | 0.06 | 0.4988 | 0.4988 | 0.4988 | 1.0000 | 1.0000 |
| SPLIT TSE | 0.48 | 0.48 | 0.07 | 0.07 | 0.4757 | 0.4757 | 0.4757 | 1.0000 | 1.0000 |
| SPLIT TNE | 0.48 | 0.48 | 0.06 | 0.06 | 0.4768 | 0.4768 | 0.4768 | 1.0000 | 1.0000 |
| SPLIT TN1 | 0.43 | 0.43 | 0.04 | 0.04 | 0.4258 | 0.4258 | 0.4258 | 1.0000 | 1.0000 |
| SPLIT TN2 | 0.42 | 0.42 | 0.04 | 0.04 | 0.4250 | 0.4250 | 0.4250 | 1.0000 | 1.0000 |
| SPLIT TS1 | 0.42 | 0.42 | 0.05 | 0.05 | 0.4249 | 0.4249 | 0.4249 | 1.0000 | 1.0000 |
| SPLIT TS2 | 0.42 | 0.42 | 0.05 | 0.05 | 0.4241 | 0.4241 | 0.4241 | 1.0000 | 1.0000 |
| Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
| None |
| Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
| SPLIT GSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT GSW | 6971.545 | 5583.472 | 0.391642 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 19:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 19:00:00 | 6230.88 | 6020.66 | 0.391642 | 25.92 | 16.56 | 0.00821801 | 12.80 | 11.37 | 0.00800000 | 38.22 | 0.00915158 | 21.18 | 6.6271 | 24.00 | 0.00815175 | 42.7998 | 4492.98 | 0.00 | 6970.36 | 5504.86 |
| SPLIT GSW HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT GSW | 9183.724 | 9183.724 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 9183.72 | 9183.72 | 0.391642 | 20.12 | 14.05 | 0.00775762 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 6.6271 | 21.10 | 0.00787724 | 49.3447 | 584.92 | 0.00 | -999.00 | -999.00 |
| SPLIT GNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT GNW | 6918.179 | 5537.910 | 0.390454 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 19:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 19:00:00 | 6178.53 | 5998.77 | 0.390454 | 25.93 | 16.54 | 0.00818714 | 12.80 | 11.37 | 0.00800000 | 38.22 | 0.00915158 | 21.18 | 6.6473 | 24.00 | 0.00811847 | 42.6268 | 4479.72 | 0.00 | 6917.00 | 5460.38 |
| SPLIT GNW HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT GNW | 9157.078 | 9157.078 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 9157.08 | 9157.08 | 0.390454 | 20.12 | 14.57 | 0.00832509 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 6.6473 | 21.10 | 0.00844867 | 52.8753 | 413.24 | 0.00 | -999.00 | -999.00 |
| SPLIT OFFICE COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT OFFICE | 7760.117 | 6215.822 | 0.448822 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 09:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 09:00:00 | 7052.20 | 6910.07 | 0.448822 | 25.98 | 16.50 | 0.00812887 | 12.80 | 11.37 | 0.00800000 | 36.66 | 0.00914901 | 20.73 | 8.4902 | 23.90 | 0.00803422 | 42.4437 | 5076.72 | 0.00 | 7758.80 | 6127.26 |
| SPLIT OFFICE HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT OFFICE | 10670.503 | 10670.503 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 18:50:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 18:50:00 | 10670.50 | 10670.50 | 0.448822 | 19.84 | 13.95 | 0.00776769 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 8.4902 | 21.10 | 0.00792498 | 49.6399 | 965.16 | 0.00 | -999.00 | -999.00 |
| SPLIT GNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT GNE | 6733.379 | 5390.255 | 0.378963 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 19:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 19:00:00 | 6016.34 | 5834.72 | 0.378963 | 25.95 | 16.55 | 0.00819472 | 12.80 | 11.37 | 0.00800000 | 38.22 | 0.00915158 | 21.18 | 6.8488 | 24.00 | 0.00812437 | 42.6575 | 4350.80 | 0.00 | 6732.23 | 5314.59 |
| SPLIT GNE HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT GNE | 8900.918 | 8900.918 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 8900.92 | 8900.92 | 0.378963 | 20.09 | 14.55 | 0.00832053 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 6.8488 | 21.10 | 0.00844893 | 52.8770 | 412.86 | 0.00 | -999.00 | -999.00 |
| SPLIT GN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT GN1 | 6022.489 | 4819.708 | 0.335744 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 19:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 19:00:00 | 5390.00 | 5215.95 | 0.335744 | 26.07 | 16.61 | 0.00821032 | 12.80 | 11.37 | 0.00800000 | 38.22 | 0.00915158 | 21.18 | 7.7304 | 24.00 | 0.00813146 | 42.6942 | 3867.28 | 0.00 | 6021.46 | 4751.45 |
| SPLIT GN1 HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT GN1 | 7937.481 | 7937.481 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 7937.48 | 7937.48 | 0.335744 | 19.96 | 15.22 | 0.00912316 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 7.7304 | 21.10 | 0.00934049 | 58.3742 | 127.36 | 0.00 | -999.00 | -999.00 |
| SPLIT GN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT GN2 | 6018.717 | 4816.548 | 0.335511 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 19:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 19:00:00 | 5386.69 | 5212.60 | 0.335511 | 26.07 | 16.61 | 0.00821051 | 12.80 | 11.37 | 0.00800000 | 38.22 | 0.00915158 | 21.18 | 7.7358 | 24.00 | 0.00813161 | 42.6949 | 3864.64 | 0.00 | 6017.69 | 4748.33 |
| SPLIT GN2 HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT GN2 | 7932.274 | 7932.274 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 7932.27 | 7932.27 | 0.335511 | 19.96 | 15.22 | 0.00912306 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 7.7358 | 21.10 | 0.00934058 | 58.3747 | 127.35 | 0.00 | -999.00 | -999.00 |
| SPLIT GS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT GS1 | 6098.602 | 4882.922 | 0.337360 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 19:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 19:00:00 | 5465.06 | 5246.13 | 0.337360 | 26.07 | 16.65 | 0.00826295 | 12.80 | 11.37 | 0.00800000 | 38.22 | 0.00915158 | 21.18 | 7.6934 | 24.00 | 0.00818889 | 42.9925 | 3885.35 | 0.00 | 6097.56 | 4813.05 |
| SPLIT GS1 HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT GS1 | 7973.630 | 7973.630 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 10:50:00 | 7973.63 | 7973.63 | 0.337360 | 19.96 | 13.93 | 0.00769945 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 7.6934 | 21.10 | 0.00779958 | 48.8642 | 241.26 | 0.00 | -999.00 | -999.00 |
| SPLIT GS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT GS2 | 6140.623 | 4918.074 | 0.339932 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 19:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 19:00:00 | 5502.02 | 5282.84 | 0.339932 | 26.06 | 16.64 | 0.00826129 | 12.80 | 11.37 | 0.00800000 | 38.22 | 0.00915158 | 21.18 | 7.6352 | 24.00 | 0.00818770 | 42.9863 | 3914.07 | 0.00 | 6139.58 | 4847.72 |
| SPLIT GS2 HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT GS2 | 8030.970 | 8030.970 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 8030.97 | 8030.97 | 0.339932 | 19.97 | 13.94 | 0.00770445 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 7.6352 | 21.10 | 0.00780732 | 48.9121 | 250.75 | 0.00 | -999.00 | -999.00 |
| SPLIT MSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT MSW | 15535.935 | 12440.938 | 0.880143 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 19:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 19:00:00 | 13865.44 | 13430.37 | 0.880143 | 25.83 | 16.51 | 0.00820104 | 12.80 | 11.37 | 0.00800000 | 38.22 | 0.00915158 | 21.18 | 5.8978 | 24.00 | 0.00814146 | 42.7463 | 20152.88 | 0.00 | 15533.29 | 12267.08 |
| SPLIT MSW HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT MSW | 20526.711 | 20526.711 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 20526.71 | 20526.71 | 0.880143 | 20.23 | 14.06 | 0.00772922 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 5.8978 | 21.10 | 0.00783307 | 49.0716 | 2451.34 | 0.00 | -999.00 | -999.00 |
| SPLIT MNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT MNW | 15438.653 | 12365.951 | 0.877648 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 19:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 19:00:00 | 13771.00 | 13386.45 | 0.877648 | 25.83 | 16.50 | 0.00817830 | 12.80 | 11.37 | 0.00800000 | 38.22 | 0.00915158 | 21.18 | 5.9146 | 24.00 | 0.00811712 | 42.6199 | 20096.95 | 0.00 | 15436.03 | 12190.89 |
| SPLIT MNW HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT MNW | 20470.734 | 20470.734 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 20470.73 | 20470.73 | 0.877648 | 20.22 | 14.56 | 0.00826850 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 5.9146 | 21.10 | 0.00837199 | 52.4020 | 1616.83 | 0.00 | -999.00 | -999.00 |
| SPLIT MSE COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT MSE | 15073.481 | 12068.876 | 0.851182 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 19:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 19:00:00 | 13460.02 | 13016.88 | 0.851182 | 25.85 | 16.53 | 0.00821162 | 12.80 | 11.37 | 0.00800000 | 38.22 | 0.00915158 | 21.18 | 6.0985 | 24.00 | 0.00815058 | 42.7937 | 19499.58 | 0.00 | 15070.92 | 11899.86 |
| SPLIT MSE HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT MSE | 19881.098 | 19881.098 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 19881.10 | 19881.10 | 0.851182 | 20.20 | 14.05 | 0.00772556 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 6.0985 | 21.10 | 0.00783293 | 49.0708 | 2449.48 | 0.00 | -999.00 | -999.00 |
| SPLIT MNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT MNE | 14972.014 | 11992.492 | 0.848711 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 19:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 19:00:00 | 13361.13 | 12972.68 | 0.848711 | 25.86 | 16.51 | 0.00818617 | 12.80 | 11.37 | 0.00800000 | 38.22 | 0.00915158 | 21.18 | 6.1162 | 24.00 | 0.00812328 | 42.6518 | 19444.25 | 0.00 | 14969.47 | 11824.84 |
| SPLIT MNE HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT MNE | 19825.672 | 19825.672 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 19825.67 | 19825.67 | 0.848711 | 20.20 | 14.54 | 0.00826413 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 6.1162 | 21.10 | 0.00837225 | 52.4036 | 1614.81 | 0.00 | -999.00 | -999.00 |
| SPLIT MN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT MN1 | 13194.890 | 10566.682 | 0.741082 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 19:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 19:00:00 | 11793.94 | 11429.56 | 0.741082 | 25.97 | 16.56 | 0.00819971 | 12.80 | 11.37 | 0.00800000 | 38.22 | 0.00915158 | 21.18 | 7.0045 | 24.00 | 0.00812802 | 42.6763 | 17026.59 | 0.00 | 13192.64 | 10417.92 |
| SPLIT MN1 HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT MN1 | 17426.359 | 17426.359 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 17426.36 | 17426.36 | 0.741082 | 20.06 | 15.67 | 0.00959587 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 7.0045 | 21.10 | 0.00989059 | 61.7586 | 208.45 | 0.00 | -999.00 | -999.00 |
| SPLIT MN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT MN2 | 13185.833 | 10559.103 | 0.740520 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 19:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 19:00:00 | 11785.99 | 11421.53 | 0.740520 | 25.98 | 16.56 | 0.00819990 | 12.80 | 11.37 | 0.00800000 | 38.22 | 0.00915158 | 21.18 | 7.0098 | 24.00 | 0.00812816 | 42.6771 | 17013.98 | 0.00 | 13183.59 | 10410.45 |
| SPLIT MN2 HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT MN2 | 17413.824 | 17413.824 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 17413.82 | 17413.82 | 0.740520 | 20.06 | 15.67 | 0.00959586 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 7.0098 | 21.10 | 0.00989081 | 61.7600 | 208.40 | 0.00 | -999.00 | -999.00 |
| SPLIT MS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT MS1 | 13332.441 | 10675.822 | 0.744260 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 19:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 19:00:00 | 11928.70 | 11487.28 | 0.744260 | 25.97 | 16.60 | 0.00824066 | 12.80 | 11.37 | 0.00800000 | 38.22 | 0.00915158 | 21.18 | 6.9746 | 24.00 | 0.00817236 | 42.9066 | 17097.54 | 0.00 | 13330.17 | 10524.63 |
| SPLIT MS1 HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT MS1 | 17497.521 | 17497.521 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 17497.52 | 17497.52 | 0.744260 | 20.07 | 13.87 | 0.00759004 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 6.9746 | 21.10 | 0.00761663 | 47.7320 | 728.77 | 0.00 | -999.00 | -999.00 |
| SPLIT MS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT MS2 | 13323.456 | 10668.236 | 0.743694 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 19:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 19:00:00 | 11920.84 | 11479.21 | 0.743694 | 25.97 | 16.60 | 0.00824095 | 12.80 | 11.37 | 0.00800000 | 38.22 | 0.00915158 | 21.18 | 6.9799 | 24.00 | 0.00817262 | 42.9079 | 17084.85 | 0.00 | 13321.19 | 10517.15 |
| SPLIT MS2 HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT MS2 | 17484.906 | 17484.906 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 17484.91 | 17484.91 | 0.743694 | 20.07 | 13.87 | 0.00758993 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 6.9799 | 21.10 | 0.00761661 | 47.7318 | 728.73 | 0.00 | -999.00 | -999.00 |
| SPLIT TSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT TSW | 8706.752 | 6973.516 | 0.497758 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 19:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 19:00:00 | 7758.70 | 7541.17 | 0.497758 | 25.74 | 16.46 | 0.00817799 | 12.80 | 11.37 | 0.00800000 | 38.22 | 0.00915158 | 21.18 | 5.2143 | 24.00 | 0.00812443 | 42.6580 | 5688.95 | 0.00 | 8705.27 | 6873.71 |
| SPLIT TSW HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT TSW | 11549.355 | 11549.355 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 11549.36 | 11549.36 | 0.497758 | 20.33 | 14.17 | 0.00780469 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 5.2143 | 21.10 | 0.00789999 | 49.4857 | 1331.05 | 0.00 | -999.00 | -999.00 |
| SPLIT TNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT TNW | 8704.255 | 6970.223 | 0.498833 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 19:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 19:00:00 | 7753.44 | 7553.60 | 0.498833 | 25.74 | 16.45 | 0.00816323 | 12.80 | 11.37 | 0.00800000 | 38.22 | 0.00915158 | 21.18 | 5.2031 | 24.00 | 0.00810898 | 42.5777 | 5701.05 | 0.00 | 8702.77 | 6870.66 |
| SPLIT TNW HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT TNW | 11573.120 | 11573.120 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 11573.12 | 11573.12 | 0.498833 | 20.33 | 14.39 | 0.00803864 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 5.2031 | 21.10 | 0.00814656 | 51.0091 | 1183.16 | 0.00 | -999.00 | -999.00 |
| SPLIT TSE COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT TSE | 8350.999 | 6686.547 | 0.475714 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 19:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 19:00:00 | 7446.14 | 7226.65 | 0.475714 | 25.77 | 16.48 | 0.00818781 | 12.80 | 11.37 | 0.00800000 | 38.22 | 0.00915158 | 21.18 | 5.4559 | 24.00 | 0.00813219 | 42.6983 | 5441.62 | 0.00 | 8349.58 | 6590.75 |
| SPLIT TSE HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT TSE | 11057.920 | 11057.920 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 11057.92 | 11057.92 | 0.475714 | 20.29 | 14.15 | 0.00780024 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 5.4559 | 21.10 | 0.00789995 | 49.4854 | 1330.57 | 0.00 | -999.00 | -999.00 |
| SPLIT TNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT TNE | 8347.041 | 6682.874 | 0.476777 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 19:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 19:00:00 | 7439.37 | 7238.74 | 0.476777 | 25.77 | 16.47 | 0.00817137 | 12.80 | 11.37 | 0.00800000 | 38.22 | 0.00915158 | 21.18 | 5.4438 | 24.00 | 0.00811494 | 42.6086 | 5453.59 | 0.00 | 8345.62 | 6587.31 |
| SPLIT TNE HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT TNE | 11081.433 | 11081.433 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 11081.43 | 11081.43 | 0.476777 | 20.29 | 14.37 | 0.00803370 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 5.4438 | 21.10 | 0.00814662 | 51.0095 | 1182.63 | 0.00 | -999.00 | -999.00 |
| SPLIT TN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT TN1 | 7494.047 | 6000.935 | 0.425755 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 19:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 19:00:00 | 6685.36 | 6506.03 | 0.425755 | 25.86 | 16.50 | 0.00817139 | 12.80 | 11.37 | 0.00800000 | 38.22 | 0.00915158 | 21.18 | 6.0961 | 24.00 | 0.00810776 | 42.5712 | 4880.24 | 0.00 | 7492.77 | 5916.02 |
| SPLIT TN1 HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT TN1 | 9944.011 | 9944.011 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 9944.01 | 9944.01 | 0.425755 | 20.20 | 14.44 | 0.00815360 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 6.0961 | 21.10 | 0.00828871 | 51.8873 | 792.79 | 0.00 | -999.00 | -999.00 |
| SPLIT TN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT TN2 | 7481.645 | 5990.640 | 0.424990 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 19:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 19:00:00 | 6674.45 | 6495.09 | 0.424990 | 25.86 | 16.50 | 0.00817173 | 12.80 | 11.37 | 0.00800000 | 38.22 | 0.00915158 | 21.18 | 6.1071 | 24.00 | 0.00810799 | 42.5724 | 4871.61 | 0.00 | 7480.37 | 5905.88 |
| SPLIT TN2 HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT TN2 | 9926.970 | 9926.970 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 9926.97 | 9926.97 | 0.424990 | 20.20 | 14.44 | 0.00815336 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 6.1071 | 21.10 | 0.00828872 | 51.8873 | 792.77 | 0.00 | -999.00 | -999.00 |
| SPLIT TS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT TS1 | 7505.334 | 6008.140 | 0.424862 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 19:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 19:00:00 | 6699.33 | 6497.00 | 0.424862 | 25.86 | 16.52 | 0.00819366 | 12.80 | 11.37 | 0.00800000 | 38.22 | 0.00915158 | 21.18 | 6.1089 | 24.00 | 0.00813133 | 42.6937 | 4870.12 | 0.00 | 7504.06 | 5924.22 |
| SPLIT TS1 HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT TS1 | 9924.274 | 9924.274 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 9924.27 | 9924.27 | 0.424862 | 20.20 | 14.12 | 0.00780038 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 6.1089 | 21.10 | 0.00791281 | 49.5648 | 941.63 | 0.00 | -999.00 | -999.00 |
| SPLIT TS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT TS2 | 7493.005 | 5997.868 | 0.424098 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 19:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 19:00:00 | 6688.50 | 6486.08 | 0.424098 | 25.86 | 16.52 | 0.00819409 | 12.80 | 11.37 | 0.00800000 | 38.22 | 0.00915158 | 21.18 | 6.1199 | 24.00 | 0.00813167 | 42.6955 | 4861.50 | 0.00 | 7491.73 | 5914.10 |
| SPLIT TS2 HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT TS2 | 9907.244 | 9907.244 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 9907.24 | 9907.24 | 0.424098 | 20.19 | 14.12 | 0.00780017 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 6.1199 | 21.10 | 0.00791281 | 49.5648 | 941.61 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 09:14:53
Coils| Coil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
| SPLIT GSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT GSW | G SW APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 6971.545 | 5583.472 | 0.391642 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.1169 | 1004.8586 | 1.1738 | SPLIT GSW SUPPLY FAN | Fan:OnOff | 0.391642 | 0.45970362 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 19:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 19:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 19:00:00 | Sensible | 6230.88 | 6020.66 | 0.8938 | 0.45970362 | 0.391642 | 25.92 | 16.56 | 0.00821801 | 46997.4 | 12.80 | 11.37 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 438.681 | 5792.19 | 38.22 | 0.00915158 | 21.18 | 0.02595455 | 6.6271 | 24.05 | 0.00815175 | 24.00 | 0.00815175 | 42.7998 | 4492.98 | 0.00 | 6970.36 | 5504.86 | 0.44154880 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.48 | 14.11 | 0.00988336 | 39536.2 | |
| SPLIT GSW HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT GSW | G SW APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 9183.724 | 9183.724 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | SPLIT GSW SUPPLY FAN | Fan:OnOff | 0.391642 | 0.45970362 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | Sensible | 9183.72 | 9183.72 | 1.0000 | 0.45970362 | 0.391642 | 20.12 | 14.05 | 0.00775762 | 39908.0 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9183.72 | 6.30 | 0.00607234 | 6.30 | 0.02595455 | 6.6271 | 21.10 | 0.00787724 | 21.10 | 0.00787724 | 49.3447 | 584.92 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT GNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT GNW | G NW APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 6918.179 | 5537.910 | 0.390454 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.0595 | 1004.8586 | 1.1738 | SPLIT GNW SUPPLY FAN | Fan:OnOff | 0.390454 | 0.45830904 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 19:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 19:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 19:00:00 | Sensible | 6178.53 | 5998.77 | 0.8931 | 0.45830904 | 0.390454 | 25.93 | 16.54 | 0.00818714 | 46921.7 | 12.80 | 11.37 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 437.350 | 5741.18 | 38.22 | 0.00915158 | 21.18 | 0.02595455 | 6.6473 | 24.05 | 0.00811847 | 24.00 | 0.00811847 | 42.6268 | 4479.72 | 0.00 | 6917.00 | 5460.38 | 0.44020929 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.54 | 14.13 | 0.00988730 | 39609.4 | |
| SPLIT GNW HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT GNW | G NW APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 9157.078 | 9157.078 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | SPLIT GNW SUPPLY FAN | Fan:OnOff | 0.390454 | 0.45830904 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 9157.08 | 9157.08 | 1.0000 | 0.45830904 | 0.390454 | 20.12 | 14.57 | 0.00832509 | 41345.7 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9157.08 | 6.30 | 0.00607234 | 6.30 | 0.02595455 | 6.6473 | 21.10 | 0.00848550 | 21.10 | 0.00844867 | 52.8753 | 413.24 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT OFFICE COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT OFFICE | OFFICE | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 7760.117 | 6215.822 | 0.448822 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.9512 | 1004.8586 | 1.1738 | SPLIT OFFICE SUPPLY FAN | Fan:OnOff | 0.448822 | 0.52682051 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 09:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 09:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 09:00:00 | Sensible | 7052.20 | 6910.07 | 0.9088 | 0.52682051 | 0.448822 | 25.98 | 16.50 | 0.00812887 | 46825.0 | 12.80 | 11.37 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 502.729 | 6549.48 | 36.66 | 0.00914901 | 20.73 | 0.03810604 | 8.4902 | 23.96 | 0.00803422 | 23.90 | 0.00803422 | 42.4437 | 5076.72 | 0.00 | 7758.80 | 6127.26 | 0.50601509 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.83 | 14.27 | 0.00992049 | 39989.3 | |
| SPLIT OFFICE HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT OFFICE | OFFICE | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 10670.503 | 10670.503 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | SPLIT OFFICE SUPPLY FAN | Fan:OnOff | 0.448822 | 0.52682051 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 18:50:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 18:50:00 | Sensible | 10670.50 | 10670.50 | 1.0000 | 0.52682051 | 0.448822 | 19.84 | 13.95 | 0.00776769 | 39652.5 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10670.50 | 6.30 | 0.00607234 | 6.30 | 0.03810604 | 8.4902 | 21.10 | 0.00792498 | 21.10 | 0.00792498 | 49.6399 | 965.16 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT GNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT GNE | G NE APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 6733.379 | 5390.255 | 0.378963 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.0736 | 1004.8586 | 1.1738 | SPLIT GNE SUPPLY FAN | Fan:OnOff | 0.378963 | 0.44482095 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 19:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 19:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 19:00:00 | Sensible | 6016.34 | 5834.72 | 0.8935 | 0.44482095 | 0.378963 | 25.95 | 16.55 | 0.00819472 | 46968.6 | 12.80 | 11.37 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 424.479 | 5591.86 | 38.22 | 0.00915158 | 21.18 | 0.02595455 | 6.8488 | 24.05 | 0.00812437 | 24.00 | 0.00812437 | 42.6575 | 4350.80 | 0.00 | 6732.23 | 5314.59 | 0.42725388 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.51 | 14.12 | 0.00988373 | 39565.4 | |
| SPLIT GNE HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT GNE | G NE APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 8900.918 | 8900.918 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | SPLIT GNE SUPPLY FAN | Fan:OnOff | 0.378963 | 0.44482095 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 8900.92 | 8900.92 | 1.0000 | 0.44482095 | 0.378963 | 20.09 | 14.55 | 0.00832053 | 41303.7 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8900.92 | 6.30 | 0.00607234 | 6.30 | 0.02595455 | 6.8488 | 21.10 | 0.00848583 | 21.10 | 0.00844893 | 52.8770 | 412.86 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT GN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT GN1 | G N1 APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 6022.489 | 4819.708 | 0.335744 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.1026 | 1004.8586 | 1.1738 | SPLIT GN1 SUPPLY FAN | Fan:OnOff | 0.335744 | 0.39409194 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 19:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 19:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 19:00:00 | Sensible | 5390.00 | 5215.95 | 0.8950 | 0.39409194 | 0.335744 | 26.07 | 16.61 | 0.00821032 | 47130.5 | 12.80 | 11.37 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 376.070 | 5013.93 | 38.22 | 0.00915158 | 21.18 | 0.02595455 | 7.7304 | 24.04 | 0.00813146 | 24.00 | 0.00813146 | 42.6942 | 3867.28 | 0.00 | 6021.46 | 4751.45 | 0.37852829 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.40 | 14.06 | 0.00986919 | 39414.8 | |
| SPLIT GN1 HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT GN1 | G N1 APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 7937.481 | 7937.481 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | SPLIT GN1 SUPPLY FAN | Fan:OnOff | 0.335744 | 0.39409194 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 7937.48 | 7937.48 | 1.0000 | 0.39409194 | 0.335744 | 19.96 | 15.22 | 0.00912316 | 43207.7 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 7937.48 | 6.30 | 0.00607234 | 6.30 | 0.02595455 | 7.7304 | 21.10 | 0.00937876 | 21.10 | 0.00934049 | 58.3742 | 127.36 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT GN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT GN2 | G N2 APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 6018.717 | 4816.548 | 0.335511 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.1029 | 1004.8586 | 1.1738 | SPLIT GN2 SUPPLY FAN | Fan:OnOff | 0.335511 | 0.39381780 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 19:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 19:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 19:00:00 | Sensible | 5386.69 | 5212.60 | 0.8950 | 0.39381780 | 0.335511 | 26.07 | 16.61 | 0.00821051 | 47131.7 | 12.80 | 11.37 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 375.808 | 5010.88 | 38.22 | 0.00915158 | 21.18 | 0.02595455 | 7.7358 | 24.04 | 0.00813161 | 24.00 | 0.00813161 | 42.6949 | 3864.64 | 0.00 | 6017.69 | 4748.33 | 0.37826497 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.40 | 14.06 | 0.00986895 | 39413.7 | |
| SPLIT GN2 HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT GN2 | G N2 APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 7932.274 | 7932.274 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | SPLIT GN2 SUPPLY FAN | Fan:OnOff | 0.335511 | 0.39381780 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 7932.27 | 7932.27 | 1.0000 | 0.39381780 | 0.335511 | 19.96 | 15.22 | 0.00912306 | 43206.6 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 7932.27 | 6.30 | 0.00607234 | 6.30 | 0.02595455 | 7.7358 | 21.10 | 0.00937884 | 21.10 | 0.00934058 | 58.3747 | 127.35 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT GS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT GS1 | G S1 APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 6098.602 | 4882.922 | 0.337360 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.2004 | 1004.8586 | 1.1738 | SPLIT GS1 SUPPLY FAN | Fan:OnOff | 0.337360 | 0.39598784 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 19:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 19:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 19:00:00 | Sensible | 5465.06 | 5246.13 | 0.8961 | 0.39598784 | 0.337360 | 26.07 | 16.65 | 0.00826295 | 47259.3 | 12.80 | 11.37 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 377.879 | 5087.19 | 38.22 | 0.00915158 | 21.18 | 0.02595455 | 7.6934 | 24.04 | 0.00818889 | 24.00 | 0.00818889 | 42.9925 | 3885.35 | 0.00 | 6097.56 | 4813.05 | 0.38034931 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.30 | 14.01 | 0.00986054 | 39290.9 | |
| SPLIT GS1 HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT GS1 | G S1 APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 7973.630 | 7973.630 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | SPLIT GS1 SUPPLY FAN | Fan:OnOff | 0.337360 | 0.39598784 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 10:50:00 | Sensible | 7973.63 | 7973.63 | 1.0000 | 0.39598784 | 0.337360 | 19.96 | 13.93 | 0.00769945 | 39599.5 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 7973.63 | 6.30 | 0.00607234 | 6.30 | 0.02595455 | 7.6934 | 21.10 | 0.00783507 | 21.10 | 0.00779958 | 48.8642 | 241.26 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT GS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT GS2 | G S2 APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 6140.623 | 4918.074 | 0.339932 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.1973 | 1004.8586 | 1.1738 | SPLIT GS2 SUPPLY FAN | Fan:OnOff | 0.339932 | 0.39900700 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 19:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 19:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 19:00:00 | Sensible | 5502.02 | 5282.84 | 0.8960 | 0.39900700 | 0.339932 | 26.06 | 16.64 | 0.00826129 | 47246.7 | 12.80 | 11.37 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 380.760 | 5121.26 | 38.22 | 0.00915158 | 21.18 | 0.02595455 | 7.6352 | 24.04 | 0.00818770 | 24.00 | 0.00818770 | 42.9863 | 3914.07 | 0.00 | 6139.58 | 4847.72 | 0.38324924 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.30 | 14.02 | 0.00986304 | 39302.6 | |
| SPLIT GS2 HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT GS2 | G S2 APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 8030.970 | 8030.970 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | SPLIT GS2 SUPPLY FAN | Fan:OnOff | 0.339932 | 0.39900700 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 8030.97 | 8030.97 | 1.0000 | 0.39900700 | 0.339932 | 19.97 | 13.94 | 0.00770445 | 39621.0 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8030.97 | 6.30 | 0.00607234 | 6.30 | 0.02595455 | 7.6352 | 21.10 | 0.00783936 | 21.10 | 0.00780732 | 48.9121 | 250.75 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT MSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT MSW | M SW APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 15535.935 | 12440.938 | 0.880143 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.0853 | 1004.8586 | 1.1738 | SPLIT MSW SUPPLY FAN | Fan:OnOff | 0.880143 | 1.03309934 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 19:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 19:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 19:00:00 | Sensible | 13865.44 | 13430.37 | 0.8925 | 1.03309934 | 0.880143 | 25.83 | 16.51 | 0.00820104 | 46856.0 | 12.80 | 11.37 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 985.855 | 12879.59 | 38.22 | 0.00915158 | 21.18 | 0.05190911 | 5.8978 | 24.06 | 0.00814146 | 24.00 | 0.00814146 | 42.7463 | 20152.88 | 0.00 | 15533.29 | 12267.08 | 0.99229972 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.59 | 14.15 | 0.00989412 | 39668.6 | |
| SPLIT MSW HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT MSW | M SW APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 20526.711 | 20526.711 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | SPLIT MSW SUPPLY FAN | Fan:OnOff | 0.880143 | 1.03309934 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | Sensible | 20526.71 | 20526.71 | 1.0000 | 1.03309934 | 0.880143 | 20.23 | 14.06 | 0.00772922 | 39945.9 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 20526.71 | 6.30 | 0.00607234 | 6.30 | 0.05190911 | 5.8978 | 21.10 | 0.00783307 | 21.10 | 0.00783307 | 49.0716 | 2451.34 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT MNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT MNW | M NW APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 15438.653 | 12365.951 | 0.877648 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.0431 | 1004.8586 | 1.1738 | SPLIT MNW SUPPLY FAN | Fan:OnOff | 0.877648 | 1.03017007 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 19:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 19:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 19:00:00 | Sensible | 13771.00 | 13386.45 | 0.8920 | 1.03017007 | 0.877648 | 25.83 | 16.50 | 0.00817830 | 46800.5 | 12.80 | 11.37 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 983.060 | 12787.94 | 38.22 | 0.00915158 | 21.18 | 0.05190911 | 5.9146 | 24.06 | 0.00811712 | 24.00 | 0.00811712 | 42.6199 | 20096.95 | 0.00 | 15436.03 | 12190.89 | 0.98948614 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.63 | 14.17 | 0.00989880 | 39722.3 | |
| SPLIT MNW HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT MNW | M NW APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 20470.734 | 20470.734 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | SPLIT MNW SUPPLY FAN | Fan:OnOff | 0.877648 | 1.03017007 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 20470.73 | 20470.73 | 1.0000 | 1.03017007 | 0.877648 | 20.22 | 14.56 | 0.00826850 | 41312.6 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 20470.73 | 6.30 | 0.00607234 | 6.30 | 0.05190911 | 5.9146 | 21.10 | 0.00840656 | 21.10 | 0.00837199 | 52.4020 | 1616.83 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT MSE COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT MSE | M SE APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 15073.481 | 12068.876 | 0.851182 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.1050 | 1004.8586 | 1.1738 | SPLIT MSE SUPPLY FAN | Fan:OnOff | 0.851182 | 0.99910530 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 19:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 19:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 19:00:00 | Sensible | 13460.02 | 13016.88 | 0.8930 | 0.99910530 | 0.851182 | 25.85 | 16.53 | 0.00821162 | 46909.7 | 12.80 | 11.37 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 953.416 | 12506.61 | 38.22 | 0.00915158 | 21.18 | 0.05190911 | 6.0985 | 24.05 | 0.00815058 | 24.00 | 0.00815058 | 42.7937 | 19499.58 | 0.00 | 15070.92 | 11899.86 | 0.95964820 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.55 | 14.14 | 0.00988908 | 39617.8 | |
| SPLIT MSE HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT MSE | M SE APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 19881.098 | 19881.098 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | SPLIT MSE SUPPLY FAN | Fan:OnOff | 0.851182 | 0.99910530 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | Sensible | 19881.10 | 19881.10 | 1.0000 | 0.99910530 | 0.851182 | 20.20 | 14.05 | 0.00772556 | 39906.3 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 19881.10 | 6.30 | 0.00607234 | 6.30 | 0.05190911 | 6.0985 | 21.10 | 0.00783293 | 21.10 | 0.00783293 | 49.0708 | 2449.48 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT MNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT MNE | M NE APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 14972.014 | 11992.492 | 0.848711 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.0577 | 1004.8586 | 1.1738 | SPLIT MNE SUPPLY FAN | Fan:OnOff | 0.848711 | 0.99620439 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 19:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 19:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 19:00:00 | Sensible | 13361.13 | 12972.68 | 0.8924 | 0.99620439 | 0.848711 | 25.86 | 16.51 | 0.00818617 | 46847.5 | 12.80 | 11.37 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 950.648 | 12410.49 | 38.22 | 0.00915158 | 21.18 | 0.05190911 | 6.1162 | 24.05 | 0.00812328 | 24.00 | 0.00812328 | 42.6518 | 19444.25 | 0.00 | 14969.47 | 11824.84 | 0.95686185 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.59 | 14.16 | 0.00989614 | 39678.1 | |
| SPLIT MNE HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT MNE | M NE APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 19825.672 | 19825.672 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | SPLIT MNE SUPPLY FAN | Fan:OnOff | 0.848711 | 0.99620439 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 19825.67 | 19825.67 | 1.0000 | 0.99620439 | 0.848711 | 20.20 | 14.54 | 0.00826413 | 41271.1 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 19825.67 | 6.30 | 0.00607234 | 6.30 | 0.05190911 | 6.1162 | 21.10 | 0.00840692 | 21.10 | 0.00837225 | 52.4036 | 1614.81 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT MN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT MN1 | M N1 APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 13194.890 | 10566.682 | 0.741082 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.0829 | 1004.8586 | 1.1738 | SPLIT MN1 SUPPLY FAN | Fan:OnOff | 0.741082 | 0.86987183 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 19:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 19:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 19:00:00 | Sensible | 11793.94 | 11429.56 | 0.8938 | 0.86987183 | 0.741082 | 25.97 | 16.56 | 0.00819971 | 47003.6 | 12.80 | 11.37 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 830.092 | 10963.85 | 38.22 | 0.00915158 | 21.18 | 0.05190911 | 7.0045 | 24.05 | 0.00812802 | 24.00 | 0.00812802 | 42.6763 | 17026.59 | 0.00 | 13192.64 | 10417.92 | 0.83551847 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.48 | 14.10 | 0.00988259 | 39532.6 | |
| SPLIT MN1 HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT MN1 | M N1 APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 17426.359 | 17426.359 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | SPLIT MN1 SUPPLY FAN | Fan:OnOff | 0.741082 | 0.86987183 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 17426.36 | 17426.36 | 1.0000 | 0.86987183 | 0.741082 | 20.06 | 15.67 | 0.00959587 | 44517.3 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 17426.36 | 6.30 | 0.00607234 | 6.30 | 0.05190911 | 7.0045 | 21.10 | 0.00986127 | 21.10 | 0.00989059 | 61.7586 | 208.45 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT MN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT MN2 | M N2 APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 13185.833 | 10559.103 | 0.740520 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.0832 | 1004.8586 | 1.1738 | SPLIT MN2 SUPPLY FAN | Fan:OnOff | 0.740520 | 0.86921179 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 19:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 19:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 19:00:00 | Sensible | 11785.99 | 11421.53 | 0.8938 | 0.86921179 | 0.740520 | 25.98 | 16.56 | 0.00819990 | 47004.8 | 12.80 | 11.37 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 829.463 | 10956.53 | 38.22 | 0.00915158 | 21.18 | 0.05190911 | 7.0098 | 24.05 | 0.00812816 | 24.00 | 0.00812816 | 42.6771 | 17013.98 | 0.00 | 13183.59 | 10410.45 | 0.83488449 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.48 | 14.10 | 0.00988234 | 39531.5 | |
| SPLIT MN2 HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT MN2 | M N2 APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 17413.824 | 17413.824 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | SPLIT MN2 SUPPLY FAN | Fan:OnOff | 0.740520 | 0.86921179 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 17413.82 | 17413.82 | 1.0000 | 0.86921179 | 0.740520 | 20.06 | 15.67 | 0.00959586 | 44516.5 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 17413.82 | 6.30 | 0.00607234 | 6.30 | 0.05190911 | 7.0098 | 21.10 | 0.00986148 | 21.10 | 0.00989081 | 61.7600 | 208.40 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT MS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT MS1 | M S1 APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 13332.441 | 10675.822 | 0.744260 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.1590 | 1004.8586 | 1.1738 | SPLIT MS1 SUPPLY FAN | Fan:OnOff | 0.744260 | 0.87360169 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 19:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 19:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 19:00:00 | Sensible | 11928.70 | 11487.28 | 0.8947 | 0.87360169 | 0.744260 | 25.97 | 16.60 | 0.00824066 | 47103.5 | 12.80 | 11.37 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 833.652 | 11095.05 | 38.22 | 0.00915158 | 21.18 | 0.05190911 | 6.9746 | 24.05 | 0.00817236 | 24.00 | 0.00817236 | 42.9066 | 17097.54 | 0.00 | 13330.17 | 10524.63 | 0.83910103 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.41 | 14.07 | 0.00987375 | 39436.1 | |
| SPLIT MS1 HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT MS1 | M S1 APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 17497.521 | 17497.521 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | SPLIT MS1 SUPPLY FAN | Fan:OnOff | 0.744260 | 0.87360169 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 17497.52 | 17497.52 | 1.0000 | 0.87360169 | 0.744260 | 20.07 | 13.87 | 0.00759004 | 39430.2 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 17497.52 | 6.30 | 0.00607234 | 6.30 | 0.05190911 | 6.9746 | 21.10 | 0.00770383 | 21.10 | 0.00761663 | 47.7320 | 728.77 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT MS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT MS2 | M S2 APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 13323.456 | 10668.236 | 0.743694 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.1595 | 1004.8586 | 1.1738 | SPLIT MS2 SUPPLY FAN | Fan:OnOff | 0.743694 | 0.87293745 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 19:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 19:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 19:00:00 | Sensible | 11920.84 | 11479.21 | 0.8947 | 0.87293745 | 0.743694 | 25.97 | 16.60 | 0.00824095 | 47105.0 | 12.80 | 11.37 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 833.018 | 11087.82 | 38.22 | 0.00915158 | 21.18 | 0.05190911 | 6.9799 | 24.05 | 0.00817262 | 24.00 | 0.00817262 | 42.9079 | 17084.85 | 0.00 | 13321.19 | 10517.15 | 0.83846302 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.41 | 14.07 | 0.00987345 | 39434.8 | |
| SPLIT MS2 HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT MS2 | M S2 APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 17484.906 | 17484.906 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | SPLIT MS2 SUPPLY FAN | Fan:OnOff | 0.743694 | 0.87293745 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 17484.91 | 17484.91 | 1.0000 | 0.87293745 | 0.743694 | 20.07 | 13.87 | 0.00758993 | 39429.1 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 17484.91 | 6.30 | 0.00607234 | 6.30 | 0.05190911 | 6.9799 | 21.10 | 0.00770381 | 21.10 | 0.00761661 | 47.7318 | 728.73 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT TSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT TSW | T SW APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 8706.752 | 6973.516 | 0.497758 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.0425 | 1004.8586 | 1.1738 | SPLIT TSW SUPPLY FAN | Fan:OnOff | 0.497758 | 0.58426162 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 19:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 19:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 19:00:00 | Sensible | 7758.70 | 7541.17 | 0.8911 | 0.58426162 | 0.497758 | 25.74 | 16.46 | 0.00817799 | 46705.7 | 12.80 | 11.37 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 557.543 | 7201.16 | 38.22 | 0.00915158 | 21.18 | 0.02595455 | 5.2143 | 24.06 | 0.00812443 | 24.00 | 0.00812443 | 42.6580 | 5688.95 | 0.00 | 8705.27 | 6873.71 | 0.56118770 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.70 | 14.21 | 0.00990503 | 39810.2 | |
| SPLIT TSW HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT TSW | T SW APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 11549.355 | 11549.355 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | SPLIT TSW SUPPLY FAN | Fan:OnOff | 0.497758 | 0.58426162 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | Sensible | 11549.36 | 11549.36 | 1.0000 | 0.58426162 | 0.497758 | 20.33 | 14.17 | 0.00780469 | 40240.5 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 11549.36 | 6.30 | 0.00607234 | 6.30 | 0.02595455 | 5.2143 | 21.10 | 0.00789999 | 21.10 | 0.00789999 | 49.4857 | 1331.05 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT TNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT TNW | T NW APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 8704.255 | 6970.223 | 0.498833 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.0150 | 1004.8586 | 1.1738 | SPLIT TNW SUPPLY FAN | Fan:OnOff | 0.498833 | 0.58552341 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 19:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 19:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 19:00:00 | Sensible | 7753.44 | 7553.60 | 0.8908 | 0.58552341 | 0.498833 | 25.74 | 16.45 | 0.00816323 | 46666.6 | 12.80 | 11.37 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 558.747 | 7194.69 | 38.22 | 0.00915158 | 21.18 | 0.02595455 | 5.2031 | 24.06 | 0.00810898 | 24.00 | 0.00810898 | 42.5777 | 5701.05 | 0.00 | 8702.77 | 6870.66 | 0.56239966 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.73 | 14.22 | 0.00990740 | 39848.0 | |
| SPLIT TNW HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT TNW | T NW APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 11573.120 | 11573.120 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | SPLIT TNW SUPPLY FAN | Fan:OnOff | 0.498833 | 0.58552341 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | Sensible | 11573.12 | 11573.12 | 1.0000 | 0.58552341 | 0.498833 | 20.33 | 14.39 | 0.00803864 | 40836.5 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 11573.12 | 6.30 | 0.00607234 | 6.30 | 0.02595455 | 5.2031 | 21.10 | 0.00814656 | 21.10 | 0.00814656 | 51.0091 | 1183.16 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT TSE COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT TSE | T SE APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 8350.999 | 6686.547 | 0.475714 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.0607 | 1004.8586 | 1.1738 | SPLIT TSE SUPPLY FAN | Fan:OnOff | 0.475714 | 0.55838570 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 19:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 19:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 19:00:00 | Sensible | 7446.14 | 7226.65 | 0.8916 | 0.55838570 | 0.475714 | 25.77 | 16.48 | 0.00818781 | 46764.6 | 12.80 | 11.37 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 532.851 | 6913.29 | 38.22 | 0.00915158 | 21.18 | 0.02595455 | 5.4559 | 24.06 | 0.00813219 | 24.00 | 0.00813219 | 42.6983 | 5441.62 | 0.00 | 8349.58 | 6590.75 | 0.53633368 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.66 | 14.19 | 0.00989890 | 39754.5 | |
| SPLIT TSE HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT TSE | T SE APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 11057.920 | 11057.920 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | SPLIT TSE SUPPLY FAN | Fan:OnOff | 0.475714 | 0.55838570 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | Sensible | 11057.92 | 11057.92 | 1.0000 | 0.55838570 | 0.475714 | 20.29 | 14.15 | 0.00780024 | 40192.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 11057.92 | 6.30 | 0.00607234 | 6.30 | 0.02595455 | 5.4559 | 21.10 | 0.00789995 | 21.10 | 0.00789995 | 49.4854 | 1330.57 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT TNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT TNE | T NE APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 8347.041 | 6682.874 | 0.476777 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.0302 | 1004.8586 | 1.1738 | SPLIT TNE SUPPLY FAN | Fan:OnOff | 0.476777 | 0.55963375 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 19:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 19:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 19:00:00 | Sensible | 7439.37 | 7238.74 | 0.8913 | 0.55963375 | 0.476777 | 25.77 | 16.47 | 0.00817137 | 46721.1 | 12.80 | 11.37 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 534.042 | 6905.33 | 38.22 | 0.00915158 | 21.18 | 0.02595455 | 5.4438 | 24.06 | 0.00811494 | 24.00 | 0.00811494 | 42.6086 | 5453.59 | 0.00 | 8345.62 | 6587.31 | 0.53753245 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.69 | 14.20 | 0.00990215 | 39796.6 | |
| SPLIT TNE HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT TNE | T NE APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 11081.433 | 11081.433 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | SPLIT TNE SUPPLY FAN | Fan:OnOff | 0.476777 | 0.55963375 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | Sensible | 11081.43 | 11081.43 | 1.0000 | 0.55963375 | 0.476777 | 20.29 | 14.37 | 0.00803370 | 40787.6 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 11081.43 | 6.30 | 0.00607234 | 6.30 | 0.02595455 | 5.4438 | 21.10 | 0.00814662 | 21.10 | 0.00814662 | 51.0095 | 1182.63 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT TN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT TN1 | T N1 APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 7494.047 | 6000.935 | 0.425755 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.0302 | 1004.8586 | 1.1738 | SPLIT TN1 SUPPLY FAN | Fan:OnOff | 0.425755 | 0.49974485 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 19:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 19:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 19:00:00 | Sensible | 6685.36 | 6506.03 | 0.8921 | 0.49974485 | 0.425755 | 25.86 | 16.50 | 0.00817139 | 46811.7 | 12.80 | 11.37 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 476.891 | 6208.47 | 38.22 | 0.00915158 | 21.18 | 0.02595455 | 6.0961 | 24.06 | 0.00810776 | 24.00 | 0.00810776 | 42.5712 | 4880.24 | 0.00 | 7492.77 | 5916.02 | 0.48000871 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.62 | 14.17 | 0.00989675 | 39712.7 | |
| SPLIT TN1 HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT TN1 | T N1 APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 9944.011 | 9944.011 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | SPLIT TN1 SUPPLY FAN | Fan:OnOff | 0.425755 | 0.49974485 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | Sensible | 9944.01 | 9944.01 | 1.0000 | 0.49974485 | 0.425755 | 20.20 | 14.44 | 0.00815360 | 40993.6 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9944.01 | 6.30 | 0.00607234 | 6.30 | 0.02595455 | 6.0961 | 21.10 | 0.00828871 | 21.10 | 0.00828871 | 51.8873 | 792.79 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT TN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT TN2 | T N2 APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 7481.645 | 5990.640 | 0.424990 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.0308 | 1004.8586 | 1.1738 | SPLIT TN2 SUPPLY FAN | Fan:OnOff | 0.424990 | 0.49884756 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 19:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 19:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 19:00:00 | Sensible | 6674.45 | 6495.09 | 0.8921 | 0.49884756 | 0.424990 | 25.86 | 16.50 | 0.00817173 | 46814.1 | 12.80 | 11.37 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 476.035 | 6198.42 | 38.22 | 0.00915158 | 21.18 | 0.02595455 | 6.1071 | 24.06 | 0.00810799 | 24.00 | 0.00810799 | 42.5724 | 4871.61 | 0.00 | 7480.37 | 5905.88 | 0.47914685 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.62 | 14.17 | 0.00989628 | 39710.5 | |
| SPLIT TN2 HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT TN2 | T N2 APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 9926.970 | 9926.970 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | SPLIT TN2 SUPPLY FAN | Fan:OnOff | 0.424990 | 0.49884756 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | Sensible | 9926.97 | 9926.97 | 1.0000 | 0.49884756 | 0.424990 | 20.20 | 14.44 | 0.00815336 | 40991.3 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9926.97 | 6.30 | 0.00607234 | 6.30 | 0.02595455 | 6.1071 | 21.10 | 0.00828872 | 21.10 | 0.00828872 | 51.8873 | 792.77 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT TS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT TS1 | T S1 APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 7505.334 | 6008.140 | 0.424862 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.0716 | 1004.8586 | 1.1738 | SPLIT TS1 SUPPLY FAN | Fan:OnOff | 0.424862 | 0.49869632 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 19:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 19:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 19:00:00 | Sensible | 6699.33 | 6497.00 | 0.8926 | 0.49869632 | 0.424862 | 25.86 | 16.52 | 0.00819366 | 46870.1 | 12.80 | 11.37 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 475.891 | 6223.44 | 38.22 | 0.00915158 | 21.18 | 0.02595455 | 6.1089 | 24.06 | 0.00813133 | 24.00 | 0.00813133 | 42.6937 | 4870.12 | 0.00 | 7504.06 | 5924.22 | 0.47900159 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.58 | 14.15 | 0.00989152 | 39656.3 | |
| SPLIT TS1 HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT TS1 | T S1 APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 9924.274 | 9924.274 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | SPLIT TS1 SUPPLY FAN | Fan:OnOff | 0.424862 | 0.49869632 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | Sensible | 9924.27 | 9924.27 | 1.0000 | 0.49869632 | 0.424862 | 20.20 | 14.12 | 0.00780038 | 40094.7 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9924.27 | 6.30 | 0.00607234 | 6.30 | 0.02595455 | 6.1089 | 21.10 | 0.00791281 | 21.10 | 0.00791281 | 49.5648 | 941.63 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT TS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT TS2 | T S2 APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 7493.005 | 5997.868 | 0.424098 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.0724 | 1004.8586 | 1.1738 | SPLIT TS2 SUPPLY FAN | Fan:OnOff | 0.424098 | 0.49779959 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 19:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 19:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 19:00:00 | Sensible | 6688.50 | 6486.08 | 0.8926 | 0.49779959 | 0.424098 | 25.86 | 16.52 | 0.00819409 | 46872.7 | 12.80 | 11.37 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 475.035 | 6213.47 | 38.22 | 0.00915158 | 21.18 | 0.02595455 | 6.1199 | 24.06 | 0.00813167 | 24.00 | 0.00813167 | 42.6955 | 4861.50 | 0.00 | 7491.73 | 5914.10 | 0.47814027 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.58 | 14.15 | 0.00989100 | 39653.9 | |
| SPLIT TS2 HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT TS2 | T S2 APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 9907.244 | 9907.244 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | SPLIT TS2 SUPPLY FAN | Fan:OnOff | 0.424098 | 0.49779959 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | Sensible | 9907.24 | 9907.24 | 1.0000 | 0.49779959 | 0.424098 | 20.19 | 14.12 | 0.00780017 | 40092.5 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9907.24 | 6.30 | 0.00607234 | 6.30 | 0.02595455 | 6.1199 | 21.10 | 0.00791281 | 21.10 | 0.00791281 | 49.5648 | 941.61 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 09:14:53
Economizer| High Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
| None |
| Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
| None |
| Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
| G SW APARTMENT | 4068.00 | 1973.83 | 1136.33 |
| G NW APARTMENT | 5301.00 | 3544.33 | 1551.50 |
| OFFICE | 1583.17 | 171.67 | 149.33 |
| G NE APARTMENT | 5329.00 | 3521.00 | 1568.17 |
| G N1 APARTMENT | 5142.33 | 3608.50 | 1845.50 |
| G N2 APARTMENT | 5144.50 | 3603.83 | 1845.33 |
| G S1 APARTMENT | 4065.33 | 1829.17 | 1353.83 |
| G S2 APARTMENT | 4220.50 | 1608.33 | 1184.00 |
| M SW APARTMENT | 3938.50 | 2148.00 | 1329.83 |
| M NW APARTMENT | 5173.17 | 3688.67 | 1816.00 |
| M SE APARTMENT | 3932.50 | 2162.67 | 1350.00 |
| M NE APARTMENT | 5196.83 | 3680.50 | 1833.33 |
| M N1 APARTMENT | 4885.00 | 3544.50 | 2050.67 |
| M N2 APARTMENT | 4885.67 | 3538.67 | 2050.17 |
| M S1 APARTMENT | 3892.00 | 1942.67 | 1490.50 |
| M S2 APARTMENT | 3890.83 | 1942.50 | 1490.83 |
| T SW APARTMENT | 3793.17 | 2989.50 | 1361.33 |
| T NW APARTMENT | 5380.67 | 4377.00 | 1893.67 |
| T SE APARTMENT | 3767.67 | 3020.67 | 1378.83 |
| T NE APARTMENT | 5390.17 | 4352.33 | 1867.33 |
| T N1 APARTMENT | 5149.17 | 4455.00 | 1899.17 |
| T N2 APARTMENT | 5151.17 | 4449.50 | 1897.83 |
| T S1 APARTMENT | 3740.00 | 2908.67 | 1402.50 |
| T S2 APARTMENT | 3737.67 | 2908.83 | 1403.00 |
| T CORRIDOR | 8759.17 | 8744.17 | 8744.17 |
| G CORRIDOR | 7201.83 | 6415.50 | 5337.50 |
| M CORRIDOR | 8760.00 | 8760.00 | 8760.00 |
| Facility | 8760.00 | 8760.00 | 8760.00 |
| During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
| G SW APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| G NW APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| OFFICE | 0.00 | 0.50 | 0.00 | 0.50 |
| G NE APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| G N1 APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| G N2 APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| G S1 APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| G S2 APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| M SW APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| M NW APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| M SE APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| M NE APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| M N1 APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| M N2 APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| M S1 APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| M S2 APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| T SW APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| T NW APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| T SE APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| T NE APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| T N1 APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| T N2 APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| T S1 APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| T S2 APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| T CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
| G CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
| M CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
| Facility | 0.00 | 0.50 | 0.00 | 0.50 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 09:14:53
Average Outdoor Air During Occupied Hours| Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
| G SW APARTMENT | 2.41 | 2.50 | 268.97 | 0.359 | 0.052 | 0.000 | 0.037 |
| G NW APARTMENT | 1.71 | 2.50 | 268.97 | 0.359 | 0.064 | 0.000 | 0.046 |
| OFFICE | 4.75 | 4.75 | 268.97 | 0.527 | 0.090 | 0.000 | 0.000 |
| G NE APARTMENT | 1.71 | 2.50 | 268.97 | 0.359 | 0.064 | 0.000 | 0.046 |
| G N1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.359 | 0.039 | 0.000 | 0.046 |
| G N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.359 | 0.039 | 0.000 | 0.046 |
| G S1 APARTMENT | 2.41 | 2.50 | 268.97 | 0.359 | 0.031 | 0.000 | 0.038 |
| G S2 APARTMENT | 2.41 | 2.50 | 268.97 | 0.359 | 0.031 | 0.000 | 0.038 |
| M SW APARTMENT | 2.41 | 2.50 | 268.97 | 0.359 | 0.074 | 0.000 | 0.039 |
| M NW APARTMENT | 1.71 | 2.50 | 268.97 | 0.359 | 0.092 | 0.000 | 0.049 |
| M SE APARTMENT | 2.41 | 2.50 | 268.97 | 0.359 | 0.074 | 0.000 | 0.039 |
| M NE APARTMENT | 1.71 | 2.50 | 268.97 | 0.359 | 0.092 | 0.000 | 0.049 |
| M N1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.359 | 0.055 | 0.000 | 0.050 |
| M N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.359 | 0.055 | 0.000 | 0.050 |
| M S1 APARTMENT | 2.41 | 2.50 | 268.97 | 0.360 | 0.045 | 0.000 | 0.039 |
| M S2 APARTMENT | 2.41 | 2.50 | 268.97 | 0.360 | 0.045 | 0.000 | 0.039 |
| T SW APARTMENT | 2.41 | 2.50 | 268.97 | 0.359 | 0.098 | 0.000 | 0.040 |
| T NW APARTMENT | 1.71 | 2.50 | 268.97 | 0.359 | 0.121 | 0.000 | 0.050 |
| T SE APARTMENT | 2.41 | 2.50 | 268.97 | 0.359 | 0.098 | 0.000 | 0.041 |
| T NE APARTMENT | 1.71 | 2.50 | 268.97 | 0.359 | 0.121 | 0.000 | 0.051 |
| T N1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.359 | 0.073 | 0.000 | 0.051 |
| T N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.359 | 0.073 | 0.000 | 0.051 |
| T S1 APARTMENT | 2.41 | 2.50 | 268.97 | 0.359 | 0.059 | 0.000 | 0.041 |
| T S2 APARTMENT | 2.41 | 2.50 | 268.97 | 0.359 | 0.059 | 0.000 | 0.041 |
| Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
| G SW APARTMENT | 2.41 | 2.50 | 268.97 | 0.331 | 0.000 | 0.000 | 0.000 |
| G NW APARTMENT | 1.71 | 2.50 | 268.97 | 0.328 | 0.000 | 0.000 | 0.000 |
| OFFICE | 4.75 | 4.75 | 268.97 | 0.485 | 0.000 | 0.000 | 0.000 |
| G NE APARTMENT | 1.71 | 2.50 | 268.97 | 0.329 | 0.000 | 0.000 | 0.000 |
| G N1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.329 | 0.000 | 0.000 | 0.000 |
| G N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.329 | 0.000 | 0.000 | 0.000 |
| G S1 APARTMENT | 2.41 | 2.50 | 268.97 | 0.332 | 0.000 | 0.000 | 0.000 |
| G S2 APARTMENT | 2.41 | 2.50 | 268.97 | 0.332 | 0.000 | 0.000 | 0.000 |
| M SW APARTMENT | 2.41 | 2.50 | 268.97 | 0.330 | 0.000 | 0.000 | 0.000 |
| M NW APARTMENT | 1.71 | 2.50 | 268.97 | 0.328 | 0.000 | 0.000 | 0.000 |
| M SE APARTMENT | 2.41 | 2.50 | 268.97 | 0.330 | 0.000 | 0.000 | 0.000 |
| M NE APARTMENT | 1.71 | 2.50 | 268.97 | 0.328 | 0.000 | 0.000 | 0.000 |
| M N1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.328 | 0.000 | 0.000 | 0.000 |
| M N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.328 | 0.000 | 0.000 | 0.000 |
| M S1 APARTMENT | 2.41 | 2.50 | 268.97 | 0.331 | 0.000 | 0.000 | 0.000 |
| M S2 APARTMENT | 2.41 | 2.50 | 268.97 | 0.331 | 0.000 | 0.000 | 0.000 |
| T SW APARTMENT | 2.41 | 2.50 | 268.97 | 0.329 | 0.000 | 0.000 | 0.000 |
| T NW APARTMENT | 1.71 | 2.50 | 268.97 | 0.327 | 0.000 | 0.000 | 0.000 |
| T SE APARTMENT | 2.41 | 2.50 | 268.97 | 0.329 | 0.000 | 0.000 | 0.000 |
| T NE APARTMENT | 1.71 | 2.50 | 268.97 | 0.327 | 0.000 | 0.000 | 0.000 |
| T N1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.327 | 0.000 | 0.000 | 0.000 |
| T N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.327 | 0.000 | 0.000 | 0.000 |
| T S1 APARTMENT | 2.41 | 2.50 | 268.97 | 0.329 | 0.000 | 0.000 | 0.000 |
| T S2 APARTMENT | 2.41 | 2.50 | 268.97 | 0.329 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 09:14:53
Mechanical Ventilation Parameters by Zone| AirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
| G SW APARTMENT | SPLIT GSW | 2.41 | 2.50 | 268.97 | 88.25 | 0.0260 | 0.026 |
| G NW APARTMENT | SPLIT GNW | 1.71 | 2.50 | 268.97 | 88.25 | 0.0260 | 0.026 |
| OFFICE | SPLIT OFFICE | 4.75 | 4.75 | 268.97 | 88.25 | 0.0381 | 0.038 |
| G NE APARTMENT | SPLIT GNE | 1.71 | 2.50 | 268.97 | 88.25 | 0.0260 | 0.026 |
| G N1 APARTMENT | SPLIT GN1 | 1.71 | 2.50 | 268.97 | 88.25 | 0.0260 | 0.026 |
| G N2 APARTMENT | SPLIT GN2 | 1.71 | 2.50 | 268.97 | 88.25 | 0.0260 | 0.026 |
| G S1 APARTMENT | SPLIT GS1 | 2.41 | 2.50 | 268.97 | 88.25 | 0.0260 | 0.026 |
| G S2 APARTMENT | SPLIT GS2 | 2.41 | 2.50 | 268.97 | 88.25 | 0.0260 | 0.026 |
| M SW APARTMENT | SPLIT MSW | 2.41 | 2.50 | 268.97 | 88.25 | 0.0519 | 0.052 |
| M NW APARTMENT | SPLIT MNW | 1.71 | 2.50 | 268.97 | 88.25 | 0.0519 | 0.052 |
| M SE APARTMENT | SPLIT MSE | 2.41 | 2.50 | 268.97 | 88.25 | 0.0519 | 0.052 |
| M NE APARTMENT | SPLIT MNE | 1.71 | 2.50 | 268.97 | 88.25 | 0.0519 | 0.052 |
| M N1 APARTMENT | SPLIT MN1 | 1.71 | 2.50 | 268.97 | 88.25 | 0.0519 | 0.052 |
| M N2 APARTMENT | SPLIT MN2 | 1.71 | 2.50 | 268.97 | 88.25 | 0.0519 | 0.052 |
| M S1 APARTMENT | SPLIT MS1 | 2.41 | 2.50 | 268.97 | 88.25 | 0.0519 | 0.052 |
| M S2 APARTMENT | SPLIT MS2 | 2.41 | 2.50 | 268.97 | 88.25 | 0.0519 | 0.052 |
| T SW APARTMENT | SPLIT TSW | 2.41 | 2.50 | 268.97 | 88.25 | 0.0260 | 0.026 |
| T NW APARTMENT | SPLIT TNW | 1.71 | 2.50 | 268.97 | 88.25 | 0.0260 | 0.026 |
| T SE APARTMENT | SPLIT TSE | 2.41 | 2.50 | 268.97 | 88.25 | 0.0260 | 0.026 |
| T NE APARTMENT | SPLIT TNE | 1.71 | 2.50 | 268.97 | 88.25 | 0.0260 | 0.026 |
| T N1 APARTMENT | SPLIT TN1 | 1.71 | 2.50 | 268.97 | 88.25 | 0.0260 | 0.026 |
| T N2 APARTMENT | SPLIT TN2 | 1.71 | 2.50 | 268.97 | 88.25 | 0.0260 | 0.026 |
| T S1 APARTMENT | SPLIT TS1 | 2.41 | 2.50 | 268.97 | 88.25 | 0.0260 | 0.026 |
| T S2 APARTMENT | SPLIT TS2 | 2.41 | 2.50 | 268.97 | 88.25 | 0.0260 | 0.026 |
| Total Facility | 68.21 | 82.25 | 8607.06 | 2823.98 | 0.8427 | 1.258 |
| Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
| G SW APARTMENT | 818502.78 | 108797.19 | 927299.97 | 145346.05 | 1072646.02 | 818502.78 | 0.00 | 7305.50 | 1454.50 | 2615.00 |
| G NW APARTMENT | 818502.78 | 105665.27 | 924168.05 | 145346.05 | 1069514.10 | 818502.78 | 0.00 | 7305.50 | 1454.50 | 0.00 |
| OFFICE | 1201711.97 | 0.00 | 1201711.97 | 145346.05 | 1347058.02 | 1201711.97 | 0.00 | 8760.00 | 0.00 | 7010.00 |
| G NE APARTMENT | 818502.78 | 106104.76 | 924607.53 | 145346.05 | 1069953.59 | 818502.78 | 0.00 | 7305.50 | 1454.50 | 0.00 |
| G N1 APARTMENT | 818502.78 | 106616.67 | 925119.45 | 87669.05 | 1012788.49 | 818502.78 | 0.00 | 7305.50 | 1454.50 | 0.00 |
| G N2 APARTMENT | 818502.78 | 106643.09 | 925145.87 | 87669.05 | 1012814.92 | 818502.78 | 0.00 | 7305.50 | 1454.50 | 0.00 |
| G S1 APARTMENT | 818502.78 | 109088.86 | 927591.63 | 87669.05 | 1015260.68 | 818502.78 | 0.00 | 7305.50 | 1454.50 | 2615.00 |
| G S2 APARTMENT | 818502.78 | 109119.61 | 927622.39 | 87669.05 | 1015291.44 | 818502.78 | 0.00 | 7305.50 | 1454.50 | 2615.00 |
| M SW APARTMENT | 1637005.55 | 115977.03 | 1752982.59 | 208872.82 | 1961855.41 | 1637005.55 | 0.00 | 7302.67 | 1457.33 | 2615.00 |
| M NW APARTMENT | 1637005.55 | 113048.21 | 1750053.77 | 208872.82 | 1958926.59 | 1637005.55 | 0.00 | 7302.67 | 1457.33 | 0.00 |
| M SE APARTMENT | 1637005.55 | 116047.04 | 1753052.59 | 208872.82 | 1961925.41 | 1637005.55 | 0.00 | 7302.67 | 1457.33 | 2615.00 |
| M NE APARTMENT | 1637005.55 | 113523.41 | 1750528.96 | 208872.82 | 1959401.78 | 1637005.55 | 0.00 | 7302.67 | 1457.33 | 0.00 |
| M N1 APARTMENT | 1637005.55 | 114189.12 | 1751194.67 | 125986.78 | 1877181.45 | 1637005.55 | 0.00 | 7302.67 | 1457.33 | 0.00 |
| M N2 APARTMENT | 1637005.55 | 114214.49 | 1751220.05 | 125986.78 | 1877206.83 | 1637005.55 | 0.00 | 7302.67 | 1457.33 | 0.00 |
| M S1 APARTMENT | 1637005.55 | 116171.84 | 1753177.40 | 125986.78 | 1879164.18 | 1637005.55 | 0.00 | 7302.67 | 1457.33 | 2615.00 |
| M S2 APARTMENT | 1637005.55 | 116172.00 | 1753177.55 | 125986.78 | 1879164.34 | 1637005.55 | 0.00 | 7302.67 | 1457.33 | 2615.00 |
| T SW APARTMENT | 818502.78 | 121314.19 | 939816.97 | 276294.09 | 1216111.06 | 818502.78 | 0.00 | 7306.17 | 1453.83 | 2615.00 |
| T NW APARTMENT | 818502.78 | 115744.20 | 934246.98 | 276294.09 | 1210541.07 | 818502.78 | 0.00 | 7306.17 | 1453.83 | 0.00 |
| T SE APARTMENT | 818502.78 | 122150.55 | 940653.33 | 276294.09 | 1216947.42 | 818502.78 | 0.00 | 7306.17 | 1453.83 | 2615.00 |
| T NE APARTMENT | 818502.78 | 117032.05 | 935534.83 | 276294.09 | 1211828.91 | 818502.78 | 0.00 | 7306.17 | 1453.83 | 0.00 |
| T N1 APARTMENT | 818502.78 | 116524.95 | 935027.73 | 166653.58 | 1101681.31 | 818502.78 | 0.00 | 7306.17 | 1453.83 | 0.00 |
| T N2 APARTMENT | 818502.78 | 116607.60 | 935110.37 | 166653.58 | 1101763.95 | 818502.78 | 0.00 | 7306.17 | 1453.83 | 0.00 |
| T S1 APARTMENT | 818502.78 | 122514.88 | 941017.65 | 166653.58 | 1107671.23 | 818502.78 | 0.00 | 7306.17 | 1453.83 | 2615.00 |
| T S2 APARTMENT | 818502.78 | 122540.28 | 941043.06 | 166653.58 | 1107696.64 | 818502.78 | 0.00 | 7306.17 | 1453.83 | 2615.00 |
| Total Facility | 39671342.50 | 3545150.42 | 43216492.93 | 5382727.88 | 48599220.80 | 39671342.50 | 0.00 | 8760.00 | 1464.83 | 8760.00 |
| Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
| G SW APARTMENT | 0.0260 | 0.0027 | 0.0287 | 0.0037 | 0.0324 | 0.0260 | 0.00 | 5345.00 | 800.00 |
| G NW APARTMENT | 0.0260 | 0.0034 | 0.0293 | 0.0046 | 0.0339 | 0.0260 | 0.00 | 7305.50 | 1454.50 |
| OFFICE | 0.0381 | 0.0000 | 0.0381 | 0.0065 | 0.0446 | 0.0381 | 0.00 | 1750.00 | 0.00 |
| G NE APARTMENT | 0.0260 | 0.0034 | 0.0293 | 0.0046 | 0.0339 | 0.0260 | 0.00 | 7305.50 | 1454.50 |
| G N1 APARTMENT | 0.0260 | 0.0034 | 0.0293 | 0.0028 | 0.0321 | 0.0260 | 0.00 | 7305.50 | 1454.50 |
| G N2 APARTMENT | 0.0260 | 0.0034 | 0.0293 | 0.0028 | 0.0321 | 0.0260 | 0.00 | 7305.50 | 1454.50 |
| G S1 APARTMENT | 0.0260 | 0.0027 | 0.0287 | 0.0022 | 0.0309 | 0.0260 | 0.00 | 5345.00 | 800.00 |
| G S2 APARTMENT | 0.0260 | 0.0027 | 0.0287 | 0.0022 | 0.0309 | 0.0260 | 0.00 | 5345.00 | 800.00 |
| M SW APARTMENT | 0.0519 | 0.0029 | 0.0548 | 0.0053 | 0.0601 | 0.0519 | 0.00 | 5343.67 | 801.33 |
| M NW APARTMENT | 0.0519 | 0.0036 | 0.0555 | 0.0066 | 0.0621 | 0.0519 | 0.00 | 7302.67 | 1457.33 |
| M SE APARTMENT | 0.0519 | 0.0029 | 0.0548 | 0.0053 | 0.0601 | 0.0519 | 0.00 | 5343.67 | 801.33 |
| M NE APARTMENT | 0.0519 | 0.0036 | 0.0555 | 0.0066 | 0.0621 | 0.0519 | 0.00 | 7302.67 | 1457.33 |
| M N1 APARTMENT | 0.0519 | 0.0036 | 0.0555 | 0.0040 | 0.0595 | 0.0519 | 0.00 | 7302.67 | 1457.33 |
| M N2 APARTMENT | 0.0519 | 0.0036 | 0.0555 | 0.0040 | 0.0595 | 0.0519 | 0.00 | 7302.67 | 1457.33 |
| M S1 APARTMENT | 0.0519 | 0.0029 | 0.0548 | 0.0032 | 0.0580 | 0.0519 | 0.00 | 5343.67 | 801.33 |
| M S2 APARTMENT | 0.0519 | 0.0029 | 0.0548 | 0.0032 | 0.0580 | 0.0519 | 0.00 | 5343.67 | 801.33 |
| T SW APARTMENT | 0.0260 | 0.0029 | 0.0289 | 0.0071 | 0.0360 | 0.0260 | 0.00 | 5346.33 | 798.67 |
| T NW APARTMENT | 0.0260 | 0.0037 | 0.0296 | 0.0088 | 0.0384 | 0.0260 | 0.00 | 7306.17 | 1453.83 |
| T SE APARTMENT | 0.0260 | 0.0030 | 0.0289 | 0.0071 | 0.0360 | 0.0260 | 0.00 | 5346.33 | 798.67 |
| T NE APARTMENT | 0.0260 | 0.0037 | 0.0297 | 0.0088 | 0.0384 | 0.0260 | 0.00 | 7306.17 | 1453.83 |
| T N1 APARTMENT | 0.0260 | 0.0037 | 0.0296 | 0.0053 | 0.0349 | 0.0260 | 0.00 | 7306.17 | 1453.83 |
| T N2 APARTMENT | 0.0260 | 0.0037 | 0.0297 | 0.0053 | 0.0349 | 0.0260 | 0.00 | 7306.17 | 1453.83 |
| T S1 APARTMENT | 0.0260 | 0.0030 | 0.0289 | 0.0043 | 0.0332 | 0.0260 | 0.00 | 5346.33 | 798.67 |
| T S2 APARTMENT | 0.0260 | 0.0030 | 0.0289 | 0.0043 | 0.0332 | 0.0260 | 0.00 | 5346.33 | 798.67 |
| Total Facility | 1.2580 | 0.1000 | 1.3580 | 0.1570 | 1.5150 | 1.2580 | 0.00 | 8760.00 | 1464.83 |
| Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
| SPLIT GSW | 0.00 | 108797.19 | 108797.19 | 818502.78 | 8377.42 | 43.58 | 339.00 | 654.50 |
| SPLIT GNW | 0.00 | 105665.27 | 105665.27 | 818502.78 | 8449.78 | 46.00 | 264.22 | 0.00 |
| SPLIT OFFICE | 1655685.47 | 0.00 | 1655685.47 | 1201711.97 | 0.00 | 0.00 | 8760.00 | 7010.00 |
| SPLIT GNE | 0.00 | 106104.76 | 106104.76 | 818502.78 | 8439.60 | 45.86 | 274.54 | 0.00 |
| SPLIT GN1 | 0.00 | 106616.67 | 106616.67 | 818502.78 | 8420.05 | 48.28 | 291.67 | 0.00 |
| SPLIT GN2 | 0.00 | 106643.09 | 106643.09 | 818502.78 | 8419.72 | 48.06 | 292.22 | 0.00 |
| SPLIT GS1 | 0.00 | 109088.86 | 109088.86 | 818502.78 | 8370.83 | 42.38 | 346.79 | 654.50 |
| SPLIT GS2 | 0.00 | 109119.61 | 109119.61 | 818502.78 | 8370.83 | 42.17 | 347.00 | 654.50 |
| SPLIT MSW | 0.00 | 115977.03 | 115977.03 | 1637005.55 | 8759.67 | 0.33 | 0.00 | 656.00 |
| SPLIT MNW | 0.00 | 113048.21 | 113048.21 | 1637005.55 | 8759.83 | 0.17 | 0.00 | 0.00 |
| SPLIT MSE | 0.00 | 116047.04 | 116047.04 | 1637005.55 | 8759.67 | 0.33 | 0.00 | 656.00 |
| SPLIT MNE | 0.00 | 113523.41 | 113523.41 | 1637005.55 | 8759.83 | 0.17 | 0.00 | 0.00 |
| SPLIT MN1 | 0.00 | 114189.12 | 114189.12 | 1637005.55 | 8759.50 | 0.50 | 0.00 | 0.00 |
| SPLIT MN2 | 0.00 | 114214.49 | 114214.49 | 1637005.55 | 8759.50 | 0.50 | 0.00 | 0.00 |
| SPLIT MS1 | 0.00 | 116171.84 | 116171.84 | 1637005.55 | 8759.33 | 0.67 | 0.00 | 656.00 |
| SPLIT MS2 | 0.00 | 116172.00 | 116172.00 | 1637005.55 | 8759.33 | 0.67 | 0.00 | 656.00 |
| SPLIT TSW | 0.00 | 121314.19 | 121314.19 | 818502.78 | 8242.79 | 54.63 | 462.58 | 655.17 |
| SPLIT TNW | 0.00 | 115744.20 | 115744.20 | 818502.78 | 8341.03 | 51.47 | 367.50 | 0.00 |
| SPLIT TSE | 0.00 | 122150.55 | 122150.55 | 818502.78 | 8223.68 | 54.07 | 482.25 | 655.17 |
| SPLIT TNE | 0.00 | 117032.05 | 117032.05 | 818502.78 | 8334.08 | 50.22 | 375.69 | 0.00 |
| SPLIT TN1 | 0.00 | 116524.95 | 116524.95 | 818502.78 | 8322.19 | 46.91 | 390.90 | 0.00 |
| SPLIT TN2 | 0.00 | 116607.60 | 116607.60 | 818502.78 | 8322.25 | 46.72 | 391.03 | 0.00 |
| SPLIT TS1 | 0.00 | 122514.88 | 122514.88 | 818502.78 | 8205.50 | 56.05 | 498.45 | 655.17 |
| SPLIT TS2 | 0.00 | 122540.28 | 122540.28 | 818502.78 | 8204.89 | 56.19 | 498.92 | 655.17 |
| Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
| SPLIT GSW | 0.0000 | 0.0027 | 0.0027 | 0.0260 | 5912.67 | 23.33 | 209.00 |
| SPLIT GNW | 0.0000 | 0.0034 | 0.0034 | 0.0260 | 8449.78 | 46.00 | 264.22 |
| SPLIT OFFICE | 0.0525 | 0.0000 | 0.0525 | 0.0381 | 0.00 | 0.00 | 1750.00 |
| SPLIT GNE | 0.0000 | 0.0034 | 0.0034 | 0.0260 | 8439.60 | 45.86 | 274.54 |
| SPLIT GN1 | 0.0000 | 0.0034 | 0.0034 | 0.0260 | 8420.05 | 48.28 | 291.67 |
| SPLIT GN2 | 0.0000 | 0.0034 | 0.0034 | 0.0260 | 8419.72 | 48.06 | 292.22 |
| SPLIT GS1 | 0.0000 | 0.0027 | 0.0027 | 0.0260 | 5909.33 | 23.00 | 212.67 |
| SPLIT GS2 | 0.0000 | 0.0027 | 0.0027 | 0.0260 | 5909.33 | 23.00 | 212.67 |
| SPLIT MSW | 0.0000 | 0.0029 | 0.0029 | 0.0519 | 6145.00 | 0.00 | 0.00 |
| SPLIT MNW | 0.0000 | 0.0036 | 0.0036 | 0.0519 | 8759.83 | 0.17 | 0.00 |
| SPLIT MSE | 0.0000 | 0.0029 | 0.0029 | 0.0519 | 6145.00 | 0.00 | 0.00 |
| SPLIT MNE | 0.0000 | 0.0036 | 0.0036 | 0.0519 | 8759.83 | 0.17 | 0.00 |
| SPLIT MN1 | 0.0000 | 0.0036 | 0.0036 | 0.0519 | 8759.50 | 0.50 | 0.00 |
| SPLIT MN2 | 0.0000 | 0.0036 | 0.0036 | 0.0519 | 8759.50 | 0.50 | 0.00 |
| SPLIT MS1 | 0.0000 | 0.0029 | 0.0029 | 0.0519 | 6145.00 | 0.00 | 0.00 |
| SPLIT MS2 | 0.0000 | 0.0029 | 0.0029 | 0.0519 | 6145.00 | 0.00 | 0.00 |
| SPLIT TSW | 0.0000 | 0.0029 | 0.0029 | 0.0260 | 5871.63 | 31.25 | 242.12 |
| SPLIT TNW | 0.0000 | 0.0037 | 0.0037 | 0.0260 | 8341.03 | 51.47 | 367.50 |
| SPLIT TSE | 0.0000 | 0.0030 | 0.0030 | 0.0260 | 5864.11 | 31.50 | 249.40 |
| SPLIT TNE | 0.0000 | 0.0037 | 0.0037 | 0.0260 | 8334.08 | 50.22 | 375.69 |
| SPLIT TN1 | 0.0000 | 0.0037 | 0.0037 | 0.0260 | 8322.19 | 46.91 | 390.90 |
| SPLIT TN2 | 0.0000 | 0.0037 | 0.0037 | 0.0260 | 8322.25 | 46.72 | 391.03 |
| SPLIT TS1 | 0.0000 | 0.0030 | 0.0030 | 0.0260 | 5848.53 | 31.38 | 265.10 |
| SPLIT TS2 | 0.0000 | 0.0030 | 0.0030 | 0.0260 | 5848.25 | 31.51 | 265.24 |
| No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
| SPLIT GSW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT GNW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT OFFICE | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT GNE | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT GN1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT GN2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT GS1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT GS2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT MSW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT MNW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT MSE | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT MNE | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT MN1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT MN2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT MS1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT MS2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT TSW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT TNW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT TSE | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT TNE | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT TN1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT TN2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT TS1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT TS2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
| SPLIT GSW | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT GNW | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT OFFICE | 0.0525 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT GNE | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT GN1 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT GN2 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT GS1 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT GS2 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT MSW | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT MNW | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT MSE | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT MNE | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT MN1 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT MN2 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT MS1 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT MS2 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT TSW | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT TNW | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT TSE | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT TNE | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT TN1 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT TN2 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT TS1 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT TS2 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 09:14:53
Surfaces by Class| Total | Outdoors | |
| Wall | 126 | 42 |
| Floor | 27 | 9 |
| Roof | 27 | 9 |
| Internal Mass | 24 | 0 |
| Building Detached Shading | 0 | 0 |
| Fixed Detached Shading | 0 | 0 |
| Window | 39 | 39 |
| Door | 0 | 0 |
| Glass Door | 0 | 0 |
| Shading | 0 | 0 |
| Overhang | 0 | 0 |
| Fin | 0 | 0 |
| Tubular Daylighting Device Dome | 0 | 0 |
| Tubular Daylighting Device Diffuser | 0 | 0 |
| Count | |
| HVAC Air Loops | 24 |
| Conditioned Zones | 24 |
| Unconditioned Zones | 3 |
| Supply Plenums | 0 |
| Return Plenums | 0 |
| Count | |
| IDF Objects | 1536 |
| Defaulted Fields | 1816 |
| Fields with Defaults | 5921 |
| Autosized Fields | 617 |
| Autosizable Fields | 759 |
| Autocalculated Fields | 331 |
| Autocalculatable Fields | 508 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 09:14:53
Annual and Peak Values - Electricity| Electricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
| Electricity:Facility | 1523.30 | 16996.43 | 27-JAN-03:30 | 96729.73 | 10-JUN-17:10 |
| Electricity:Building | 557.89 | 10119.94 | 01-JAN-03:10 | 27841.36 | 01-JAN-18:10 |
| Electricity:Zone:G SW APARTMENT | 13.67 | 232.36 | 01-JAN-03:10 | 705.80 | 01-JAN-18:10 |
| Electricity:SpaceType:GENERAL | 557.89 | 10119.94 | 01-JAN-03:10 | 27841.36 | 01-JAN-18:10 |
| InteriorLights:Electricity | 99.23 | 1868.27 | 01-JAN-00:10 | 5904.43 | 01-JAN-19:10 |
| InteriorLights:Electricity:Zone:G SW APARTMENT | 1.45 | 8.68 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 |
| InteriorLights:Electricity:SpaceType:GENERAL | 99.23 | 1868.27 | 01-JAN-00:10 | 5904.43 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity | 94.96 | 1842.77 | 01-JAN-00:10 | 5496.56 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:G SW APARTMENT | 1.32 | 7.86 | 01-JAN-00:10 | 125.72 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 94.96 | 1842.77 | 01-JAN-00:10 | 5496.56 | 01-JAN-19:10 |
| Electricity:Zone:G NW APARTMENT | 13.67 | 232.36 | 01-JAN-03:10 | 705.80 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:G NW APARTMENT | 1.45 | 8.68 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:G NW APARTMENT | 1.32 | 7.86 | 01-JAN-00:10 | 125.72 | 01-JAN-19:10 |
| Electricity:Zone:OFFICE | 16.86 | 310.83 | 01-JAN-00:10 | 1171.54 | 03-JAN-08:10 |
| InteriorLights:Electricity:Zone:OFFICE | 7.40 | 116.58 | 01-JAN-00:10 | 582.92 | 03-JAN-08:10 |
| LightsWired:InteriorLights:Electricity:Zone:OFFICE | 7.40 | 116.58 | 01-JAN-00:10 | 582.92 | 03-JAN-08:10 |
| Electricity:Zone:G NE APARTMENT | 13.67 | 232.36 | 01-JAN-03:10 | 705.80 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:G NE APARTMENT | 1.45 | 8.68 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:G NE APARTMENT | 1.32 | 7.86 | 01-JAN-00:10 | 125.72 | 01-JAN-19:10 |
| Electricity:Zone:G N1 APARTMENT | 13.67 | 232.36 | 01-JAN-03:10 | 705.80 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:G N1 APARTMENT | 1.45 | 8.68 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:G N1 APARTMENT | 1.32 | 7.86 | 01-JAN-00:10 | 125.72 | 01-JAN-19:10 |
| Electricity:Zone:G N2 APARTMENT | 13.67 | 232.36 | 01-JAN-03:10 | 705.80 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:G N2 APARTMENT | 1.45 | 8.68 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:G N2 APARTMENT | 1.32 | 7.86 | 01-JAN-00:10 | 125.72 | 01-JAN-19:10 |
| Electricity:Zone:G S1 APARTMENT | 13.67 | 232.36 | 01-JAN-03:10 | 705.80 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:G S1 APARTMENT | 1.45 | 8.68 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:G S1 APARTMENT | 1.32 | 7.86 | 01-JAN-00:10 | 125.72 | 01-JAN-19:10 |
| Electricity:Zone:G S2 APARTMENT | 13.67 | 232.36 | 01-JAN-03:10 | 705.80 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:G S2 APARTMENT | 1.45 | 8.68 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:G S2 APARTMENT | 1.32 | 7.86 | 01-JAN-00:10 | 125.72 | 01-JAN-19:10 |
| Electricity:Zone:M SW APARTMENT | 27.33 | 464.72 | 01-JAN-03:10 | 1411.61 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:M SW APARTMENT | 2.91 | 17.37 | 01-JAN-00:10 | 277.76 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:M SW APARTMENT | 2.63 | 15.72 | 01-JAN-00:10 | 251.45 | 01-JAN-19:10 |
| Electricity:Zone:M NW APARTMENT | 27.33 | 464.72 | 01-JAN-03:10 | 1411.61 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:M NW APARTMENT | 2.91 | 17.37 | 01-JAN-00:10 | 277.76 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:M NW APARTMENT | 2.63 | 15.72 | 01-JAN-00:10 | 251.45 | 01-JAN-19:10 |
| Electricity:Zone:M SE APARTMENT | 27.33 | 464.72 | 01-JAN-03:10 | 1411.61 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:M SE APARTMENT | 2.91 | 17.37 | 01-JAN-00:10 | 277.76 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:M SE APARTMENT | 2.63 | 15.72 | 01-JAN-00:10 | 251.45 | 01-JAN-19:10 |
| Electricity:Zone:M NE APARTMENT | 27.33 | 464.72 | 01-JAN-03:10 | 1411.61 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:M NE APARTMENT | 2.91 | 17.37 | 01-JAN-00:10 | 277.76 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:M NE APARTMENT | 2.63 | 15.72 | 01-JAN-00:10 | 251.45 | 01-JAN-19:10 |
| Electricity:Zone:M N1 APARTMENT | 27.33 | 464.72 | 01-JAN-03:10 | 1411.61 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:M N1 APARTMENT | 2.91 | 17.37 | 01-JAN-00:10 | 277.76 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:M N1 APARTMENT | 2.63 | 15.72 | 01-JAN-00:10 | 251.45 | 01-JAN-19:10 |
| Electricity:Zone:M N2 APARTMENT | 27.33 | 464.72 | 01-JAN-03:10 | 1411.61 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:M N2 APARTMENT | 2.91 | 17.37 | 01-JAN-00:10 | 277.76 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:M N2 APARTMENT | 2.63 | 15.72 | 01-JAN-00:10 | 251.45 | 01-JAN-19:10 |
| Electricity:Zone:M S1 APARTMENT | 27.33 | 464.72 | 01-JAN-03:10 | 1411.61 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:M S1 APARTMENT | 2.91 | 17.37 | 01-JAN-00:10 | 277.76 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:M S1 APARTMENT | 2.63 | 15.72 | 01-JAN-00:10 | 251.45 | 01-JAN-19:10 |
| Electricity:Zone:M S2 APARTMENT | 27.33 | 464.72 | 01-JAN-03:10 | 1411.61 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:M S2 APARTMENT | 2.91 | 17.37 | 01-JAN-00:10 | 277.76 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:M S2 APARTMENT | 2.63 | 15.72 | 01-JAN-00:10 | 251.45 | 01-JAN-19:10 |
| Electricity:Zone:T SW APARTMENT | 13.67 | 232.36 | 01-JAN-03:10 | 705.80 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:T SW APARTMENT | 1.45 | 8.68 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:T SW APARTMENT | 1.32 | 7.86 | 01-JAN-00:10 | 125.72 | 01-JAN-19:10 |
| Electricity:Zone:T NW APARTMENT | 13.67 | 232.36 | 01-JAN-03:10 | 705.80 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:T NW APARTMENT | 1.45 | 8.68 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:T NW APARTMENT | 1.32 | 7.86 | 01-JAN-00:10 | 125.72 | 01-JAN-19:10 |
| Electricity:Zone:T SE APARTMENT | 13.67 | 232.36 | 01-JAN-03:10 | 705.80 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:T SE APARTMENT | 1.45 | 8.68 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:T SE APARTMENT | 1.32 | 7.86 | 01-JAN-00:10 | 125.72 | 01-JAN-19:10 |
| Electricity:Zone:T NE APARTMENT | 13.67 | 232.36 | 01-JAN-03:10 | 705.80 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:T NE APARTMENT | 1.45 | 8.68 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:T NE APARTMENT | 1.32 | 7.86 | 01-JAN-00:10 | 125.72 | 01-JAN-19:10 |
| Electricity:Zone:T N1 APARTMENT | 13.67 | 232.36 | 01-JAN-03:10 | 705.80 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:T N1 APARTMENT | 1.45 | 8.68 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:T N1 APARTMENT | 1.32 | 7.86 | 01-JAN-00:10 | 125.72 | 01-JAN-19:10 |
| Electricity:Zone:T N2 APARTMENT | 13.67 | 232.36 | 01-JAN-03:10 | 705.80 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:T N2 APARTMENT | 1.45 | 8.68 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:T N2 APARTMENT | 1.32 | 7.86 | 01-JAN-00:10 | 125.72 | 01-JAN-19:10 |
| Electricity:Zone:T S1 APARTMENT | 13.67 | 232.36 | 01-JAN-03:10 | 705.80 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:T S1 APARTMENT | 1.45 | 8.68 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:T S1 APARTMENT | 1.32 | 7.86 | 01-JAN-00:10 | 125.72 | 01-JAN-19:10 |
| Electricity:Zone:T S2 APARTMENT | 13.67 | 232.36 | 01-JAN-03:10 | 705.80 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:T S2 APARTMENT | 1.45 | 8.68 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:T S2 APARTMENT | 1.32 | 7.86 | 01-JAN-00:10 | 125.72 | 01-JAN-19:10 |
| Electricity:Zone:G CORRIDOR | 82.28 | 1494.09 | 01-JAN-00:10 | 4538.70 | 01-JAN-07:10 |
| InteriorLights:Electricity:Zone:G CORRIDOR | 11.69 | 370.63 | 01-JAN-00:10 | 370.63 | 01-JAN-00:10 |
| LightsWired:InteriorLights:Electricity:Zone:G CORRIDOR | 11.69 | 370.63 | 01-JAN-00:10 | 370.63 | 01-JAN-00:10 |
| Electricity:Zone:M CORRIDOR | 23.38 | 741.26 | 01-JAN-00:10 | 741.26 | 01-JAN-00:10 |
| InteriorLights:Electricity:Zone:M CORRIDOR | 23.38 | 741.26 | 01-JAN-00:10 | 741.26 | 01-JAN-00:10 |
| LightsWired:InteriorLights:Electricity:Zone:M CORRIDOR | 23.38 | 741.26 | 01-JAN-00:10 | 741.26 | 01-JAN-00:10 |
| Electricity:Zone:T CORRIDOR | 11.69 | 370.63 | 01-JAN-00:10 | 370.63 | 01-JAN-00:10 |
| InteriorLights:Electricity:Zone:T CORRIDOR | 11.69 | 370.63 | 01-JAN-00:10 | 370.63 | 01-JAN-00:10 |
| LightsWired:InteriorLights:Electricity:Zone:T CORRIDOR | 11.69 | 370.63 | 01-JAN-00:10 | 370.63 | 01-JAN-00:10 |
| LightsPlugIn:InteriorLights:Electricity | 4.27 | 25.50 | 01-JAN-00:10 | 407.87 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:G SW APARTMENT | 0.14 | 0.82 | 01-JAN-00:10 | 13.16 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:SpaceType:GENERAL | 4.27 | 25.50 | 01-JAN-00:10 | 407.87 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:G NW APARTMENT | 0.14 | 0.82 | 01-JAN-00:10 | 13.16 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:G NE APARTMENT | 0.14 | 0.82 | 01-JAN-00:10 | 13.16 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:G N1 APARTMENT | 0.14 | 0.82 | 01-JAN-00:10 | 13.16 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:G N2 APARTMENT | 0.14 | 0.82 | 01-JAN-00:10 | 13.16 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:G S1 APARTMENT | 0.14 | 0.82 | 01-JAN-00:10 | 13.16 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:G S2 APARTMENT | 0.14 | 0.82 | 01-JAN-00:10 | 13.16 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:M SW APARTMENT | 0.28 | 1.65 | 01-JAN-00:10 | 26.31 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:M NW APARTMENT | 0.28 | 1.65 | 01-JAN-00:10 | 26.31 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:M SE APARTMENT | 0.28 | 1.65 | 01-JAN-00:10 | 26.31 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:M NE APARTMENT | 0.28 | 1.65 | 01-JAN-00:10 | 26.31 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:M N1 APARTMENT | 0.28 | 1.65 | 01-JAN-00:10 | 26.31 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:M N2 APARTMENT | 0.28 | 1.65 | 01-JAN-00:10 | 26.31 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:M S1 APARTMENT | 0.28 | 1.65 | 01-JAN-00:10 | 26.31 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:M S2 APARTMENT | 0.28 | 1.65 | 01-JAN-00:10 | 26.31 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:T SW APARTMENT | 0.14 | 0.82 | 01-JAN-00:10 | 13.16 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:T NW APARTMENT | 0.14 | 0.82 | 01-JAN-00:10 | 13.16 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:T SE APARTMENT | 0.14 | 0.82 | 01-JAN-00:10 | 13.16 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:T NE APARTMENT | 0.14 | 0.82 | 01-JAN-00:10 | 13.16 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:T N1 APARTMENT | 0.14 | 0.82 | 01-JAN-00:10 | 13.16 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:T N2 APARTMENT | 0.14 | 0.82 | 01-JAN-00:10 | 13.16 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:T S1 APARTMENT | 0.14 | 0.82 | 01-JAN-00:10 | 13.16 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:T S2 APARTMENT | 0.14 | 0.82 | 01-JAN-00:10 | 13.16 | 01-JAN-19:10 |
| InteriorEquipment:Electricity | 458.66 | 8251.68 | 01-JAN-03:10 | 22709.69 | 03-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:G SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:SpaceType:GENERAL | 458.66 | 8251.68 | 01-JAN-03:10 | 22709.69 | 03-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity | 388.06 | 7128.22 | 01-JAN-03:10 | 18541.61 | 03-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:G SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 388.06 | 7128.22 | 01-JAN-03:10 | 18541.61 | 03-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:G NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:G NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:OFFICE | 9.47 | 194.25 | 01-JAN-00:10 | 588.62 | 03-JAN-08:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:OFFICE | 9.47 | 194.25 | 01-JAN-00:10 | 588.62 | 03-JAN-08:10 |
| InteriorEquipment:Electricity:Zone:G NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:G NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:G N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:G N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:G N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:G N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:G S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:G S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:G S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:G S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:M SW APARTMENT | 24.43 | 447.35 | 01-JAN-03:10 | 1177.25 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:M SW APARTMENT | 24.43 | 447.35 | 01-JAN-03:10 | 1177.25 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:M NW APARTMENT | 24.43 | 447.35 | 01-JAN-03:10 | 1177.25 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:M NW APARTMENT | 24.43 | 447.35 | 01-JAN-03:10 | 1177.25 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:M SE APARTMENT | 24.43 | 447.35 | 01-JAN-03:10 | 1177.25 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:M SE APARTMENT | 24.43 | 447.35 | 01-JAN-03:10 | 1177.25 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:M NE APARTMENT | 24.43 | 447.35 | 01-JAN-03:10 | 1177.25 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:M NE APARTMENT | 24.43 | 447.35 | 01-JAN-03:10 | 1177.25 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:M N1 APARTMENT | 24.43 | 447.35 | 01-JAN-03:10 | 1177.25 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:M N1 APARTMENT | 24.43 | 447.35 | 01-JAN-03:10 | 1177.25 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:M N2 APARTMENT | 24.43 | 447.35 | 01-JAN-03:10 | 1177.25 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:M N2 APARTMENT | 24.43 | 447.35 | 01-JAN-03:10 | 1177.25 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:M S1 APARTMENT | 24.43 | 447.35 | 01-JAN-03:10 | 1177.25 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:M S1 APARTMENT | 24.43 | 447.35 | 01-JAN-03:10 | 1177.25 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:M S2 APARTMENT | 24.43 | 447.35 | 01-JAN-03:10 | 1177.25 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:M S2 APARTMENT | 24.43 | 447.35 | 01-JAN-03:10 | 1177.25 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:T SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:T SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:T NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:T NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:T SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:T SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:T NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:T NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:T N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:T N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:T N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:T N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:T S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:T S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:T S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:T S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:G CORRIDOR | 70.59 | 1123.46 | 01-JAN-00:10 | 4168.07 | 01-JAN-07:10 |
| ElevatorLift:InteriorEquipment:Electricity | 65.48 | 961.46 | 01-JAN-00:10 | 4006.07 | 01-JAN-07:10 |
| ElevatorLift:InteriorEquipment:Electricity:Zone:G CORRIDOR | 65.48 | 961.46 | 01-JAN-00:10 | 4006.07 | 01-JAN-07:10 |
| ElevatorLift:InteriorEquipment:Electricity:SpaceType:GENERAL | 65.48 | 961.46 | 01-JAN-00:10 | 4006.07 | 01-JAN-07:10 |
| ElevatorLightsFan:InteriorEquipment:Electricity | 5.11 | 162.00 | 01-JAN-00:10 | 162.00 | 01-JAN-00:10 |
| ElevatorLightsFan:InteriorEquipment:Electricity:Zone:G CORRIDOR | 5.11 | 162.00 | 01-JAN-00:10 | 162.00 | 01-JAN-00:10 |
| ElevatorLightsFan:InteriorEquipment:Electricity:SpaceType:GENERAL | 5.11 | 162.00 | 01-JAN-00:10 | 162.00 | 01-JAN-00:10 |
| Fans:Electricity | 157.80 | 1743.16 | 01-JAN-13:30 | 10921.37 | 06-JUN-16:10 |
| Fans:Electricity:Zone:G SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:G SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:G NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:G NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:G NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:G NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:G N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:G N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:G N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:G N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:G S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:G S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:G S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:G S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:M SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:M SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:M NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:M NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:M SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:M SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:M NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:M NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:M N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:M N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:M N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:M N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:M S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:M S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:M S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:M S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:T SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:T SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:T NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:T NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:T SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:T SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:T NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:T NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:T N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:T N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:T N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:T N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:T S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:T S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:T S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:T S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| ElectricityPurchased:Facility | 1523.30 | 16996.43 | 27-JAN-03:30 | 96729.73 | 10-JUN-17:10 |
| ElectricityPurchased:Plant | 1523.30 | 16996.43 | 27-JAN-03:30 | 96729.73 | 10-JUN-17:10 |
| Cogeneration:ElectricityPurchased | 1523.30 | 16996.43 | 27-JAN-03:30 | 96729.73 | 10-JUN-17:10 |
| General:Cogeneration:ElectricityPurchased | 1523.30 | 16996.43 | 27-JAN-03:30 | 96729.73 | 10-JUN-17:10 |
| ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| ElectricityNet:Facility | 1523.30 | 16996.43 | 27-JAN-03:30 | 96729.73 | 10-JUN-17:10 |
| ElectricityNet:Plant | 1523.30 | 16996.43 | 27-JAN-03:30 | 96729.73 | 10-JUN-17:10 |
| Cogeneration:ElectricityNet | 1523.30 | 16996.43 | 27-JAN-03:30 | 96729.73 | 10-JUN-17:10 |
| General:Cogeneration:ElectricityNet | 1523.30 | 16996.43 | 27-JAN-03:30 | 96729.73 | 10-JUN-17:10 |
| Electricity:HVAC | 561.48 | 1743.16 | 01-JAN-13:30 | 49400.43 | 06-JUN-15:10 |
| HeatRecovery:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:HeatRecovery:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:Fans:Electricity | 157.80 | 1743.16 | 01-JAN-13:30 | 10921.37 | 06-JUN-16:10 |
| Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Cooling:Electricity | 403.68 | 0.00 | 01-JAN-00:10 | 38499.90 | 06-JUN-15:10 |
| General:Cooling:Electricity | 403.68 | 0.00 | 01-JAN-00:10 | 38499.90 | 06-JUN-15:10 |
| ExteriorLights:Electricity | 50.05 | 0.00 | 01-JAN-07:20 | 3183.33 | 01-JAN-00:10 |
| General:ExteriorLights:Electricity | 50.05 | 0.00 | 01-JAN-07:20 | 3183.33 | 01-JAN-00:10 |
| Electricity:Plant | 353.88 | 1950.00 | 01-JAN-00:10 | 37136.47 | 01-JAN-08:30 |
| WaterSystems:Electricity | 353.88 | 1950.00 | 01-JAN-00:10 | 37136.47 | 01-JAN-08:30 |
| Water Heater:WaterSystems:Electricity | 353.88 | 1950.00 | 01-JAN-00:10 | 37136.47 | 01-JAN-08:30 |
| Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
| NaturalGas:Facility | 7.51 | 0.00 | 01-JAN-12:40 | 12112.07 | 03-JAN-07:00 |
| NaturalGas:HVAC | 7.51 | 0.00 | 01-JAN-12:40 | 12112.07 | 03-JAN-07:00 |
| Heating:NaturalGas | 7.51 | 0.00 | 01-JAN-12:40 | 12112.07 | 03-JAN-07:00 |
| General:Heating:NaturalGas | 7.51 | 0.00 | 01-JAN-12:40 | 12112.07 | 03-JAN-07:00 |
| Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
| None |
| Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
| Water:Facility | 1875.32 | 0.00 | 01-JAN-02:10 | 0.00 | 01-JAN-07:10 |
| Water:Plant | 1875.32 | 0.00 | 01-JAN-02:10 | 0.00 | 01-JAN-07:10 |
| WaterSystems:Water | 1875.32 | 0.00 | 01-JAN-02:10 | 0.00 | 01-JAN-07:10 |
| Water Heater:WaterSystems:Water | 1875.32 | 0.00 | 01-JAN-02:10 | 0.00 | 01-JAN-07:10 |
| MainsWater:Facility | 1875.32 | 0.00 | 01-JAN-02:10 | 0.00 | 01-JAN-07:10 |
| MainsWater:Plant | 1875.32 | 0.00 | 01-JAN-02:10 | 0.00 | 01-JAN-07:10 |
| WaterSystems:MainsWater | 1875.32 | 0.00 | 01-JAN-02:10 | 0.00 | 01-JAN-07:10 |
| Water Heater:WaterSystems:MainsWater | 1875.32 | 0.00 | 01-JAN-02:10 | 0.00 | 01-JAN-07:10 |
| Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
| Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
| CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
| Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
| None |
| Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
| None |
| Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
| EnergyTransfer:Facility | 2530.78 | 4992.06 | 09-FEB-17:40 | 205872.70 | 06-JUN-15:10 |
| EnergyTransfer:Building | 1029.83 | 4480.80 | 22-DEC-09:00 | 87604.07 | 06-JUN-15:10 |
| EnergyTransfer:Zone:G SW APARTMENT | 36.08 | 122.10 | 03-JAN-13:30 | 2790.49 | 06-JUN-16:10 |
| Heating:EnergyTransfer | 5.55 | 0.00 | 01-JAN-19:10 | 4139.13 | 03-JAN-07:00 |
| Heating:EnergyTransfer:Zone:G SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:Heating:EnergyTransfer | 5.55 | 0.00 | 01-JAN-19:10 | 4139.13 | 03-JAN-07:00 |
| General:Heating:EnergyTransfer:Zone:G SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Cooling:EnergyTransfer | 1024.28 | 4217.90 | 22-DEC-09:20 | 87604.07 | 06-JUN-15:10 |
| Cooling:EnergyTransfer:Zone:G SW APARTMENT | 36.08 | 122.10 | 03-JAN-13:30 | 2790.49 | 06-JUN-16:10 |
| General:Cooling:EnergyTransfer | 1024.28 | 4217.90 | 22-DEC-09:20 | 87604.07 | 06-JUN-15:10 |
| General:Cooling:EnergyTransfer:Zone:G SW APARTMENT | 36.08 | 122.10 | 03-JAN-13:30 | 2790.49 | 06-JUN-16:10 |
| EnergyTransfer:Zone:G NW APARTMENT | 30.97 | 0.38 | 08-JAN-14:40 | 2807.97 | 06-JUN-16:40 |
| Heating:EnergyTransfer:Zone:G NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 18.83 | 06-FEB-13:10 |
| General:Heating:EnergyTransfer:Zone:G NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 18.83 | 06-FEB-13:10 |
| Cooling:EnergyTransfer:Zone:G NW APARTMENT | 30.97 | 0.00 | 08-JAN-14:50 | 2807.97 | 06-JUN-16:40 |
| General:Cooling:EnergyTransfer:Zone:G NW APARTMENT | 30.97 | 0.00 | 08-JAN-14:50 | 2807.97 | 06-JUN-16:40 |
| EnergyTransfer:Zone:OFFICE | 27.93 | 0.01 | 22-DEC-06:30 | 5194.23 | 12-JUN-08:10 |
| Heating:EnergyTransfer:Zone:OFFICE | 3.62 | 0.00 | 01-JAN-00:10 | 1035.02 | 08-JUN-17:10 |
| General:Heating:EnergyTransfer:Zone:OFFICE | 3.62 | 0.00 | 01-JAN-00:10 | 1035.02 | 08-JUN-17:10 |
| Cooling:EnergyTransfer:Zone:OFFICE | 24.31 | 0.00 | 01-JAN-11:40 | 5194.23 | 12-JUN-08:10 |
| General:Cooling:EnergyTransfer:Zone:OFFICE | 24.31 | 0.00 | 01-JAN-11:40 | 5194.23 | 12-JUN-08:10 |
| EnergyTransfer:Zone:G NE APARTMENT | 31.00 | 0.69 | 03-FEB-14:50 | 2510.98 | 06-JUN-16:10 |
| Heating:EnergyTransfer:Zone:G NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 3.67 | 08-JAN-15:00 |
| General:Heating:EnergyTransfer:Zone:G NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 3.67 | 08-JAN-15:00 |
| Cooling:EnergyTransfer:Zone:G NE APARTMENT | 31.00 | 0.00 | 08-JAN-14:50 | 2510.98 | 06-JUN-16:10 |
| General:Cooling:EnergyTransfer:Zone:G NE APARTMENT | 31.00 | 0.00 | 08-JAN-14:50 | 2510.98 | 06-JUN-16:10 |
| EnergyTransfer:Zone:G N1 APARTMENT | 26.21 | 1.07 | 08-JAN-14:50 | 1929.85 | 07-JUN-17:20 |
| Heating:EnergyTransfer:Zone:G N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 3.36 | 08-JAN-15:00 |
| General:Heating:EnergyTransfer:Zone:G N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 3.36 | 08-JAN-15:00 |
| Cooling:EnergyTransfer:Zone:G N1 APARTMENT | 26.21 | 0.00 | 08-JAN-14:50 | 1929.85 | 07-JUN-17:20 |
| General:Cooling:EnergyTransfer:Zone:G N1 APARTMENT | 26.21 | 0.00 | 08-JAN-14:50 | 1929.85 | 07-JUN-17:20 |
| EnergyTransfer:Zone:G N2 APARTMENT | 26.22 | 0.67 | 08-JAN-14:50 | 1925.14 | 07-JUN-17:20 |
| Heating:EnergyTransfer:Zone:G N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 2.98 | 08-JAN-15:00 |
| General:Heating:EnergyTransfer:Zone:G N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 2.98 | 08-JAN-15:00 |
| Cooling:EnergyTransfer:Zone:G N2 APARTMENT | 26.22 | 0.00 | 08-JAN-14:50 | 1925.14 | 07-JUN-17:20 |
| General:Cooling:EnergyTransfer:Zone:G N2 APARTMENT | 26.22 | 0.00 | 08-JAN-14:50 | 1925.14 | 07-JUN-17:20 |
| EnergyTransfer:Zone:G S1 APARTMENT | 31.87 | 158.70 | 02-JAN-15:00 | 1986.50 | 01-OCT-15:10 |
| Heating:EnergyTransfer:Zone:G S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:Heating:EnergyTransfer:Zone:G S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Cooling:EnergyTransfer:Zone:G S1 APARTMENT | 31.87 | 158.70 | 02-JAN-15:00 | 1986.50 | 01-OCT-15:10 |
| General:Cooling:EnergyTransfer:Zone:G S1 APARTMENT | 31.87 | 158.70 | 02-JAN-15:00 | 1986.50 | 01-OCT-15:10 |
| EnergyTransfer:Zone:G S2 APARTMENT | 34.76 | 158.45 | 02-JAN-15:00 | 2159.43 | 01-OCT-15:10 |
| Heating:EnergyTransfer:Zone:G S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:Heating:EnergyTransfer:Zone:G S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Cooling:EnergyTransfer:Zone:G S2 APARTMENT | 34.76 | 158.45 | 02-JAN-15:00 | 2159.43 | 01-OCT-15:10 |
| General:Cooling:EnergyTransfer:Zone:G S2 APARTMENT | 34.76 | 158.45 | 02-JAN-15:00 | 2159.43 | 01-OCT-15:10 |
| EnergyTransfer:Zone:M SW APARTMENT | 74.44 | 235.77 | 06-DEC-09:20 | 6401.81 | 05-MAY-16:10 |
| Heating:EnergyTransfer:Zone:M SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:Heating:EnergyTransfer:Zone:M SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Cooling:EnergyTransfer:Zone:M SW APARTMENT | 74.44 | 235.77 | 06-DEC-09:20 | 6401.81 | 05-MAY-16:10 |
| General:Cooling:EnergyTransfer:Zone:M SW APARTMENT | 74.44 | 235.77 | 06-DEC-09:20 | 6401.81 | 05-MAY-16:10 |
| EnergyTransfer:Zone:M NW APARTMENT | 63.02 | 4.86 | 24-DEC-13:00 | 6264.24 | 05-MAY-16:30 |
| Heating:EnergyTransfer:Zone:M NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 76.56 | 24-DEC-14:00 |
| General:Heating:EnergyTransfer:Zone:M NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 76.56 | 24-DEC-14:00 |
| Cooling:EnergyTransfer:Zone:M NW APARTMENT | 63.02 | 0.00 | 24-DEC-13:10 | 6264.24 | 05-MAY-16:30 |
| General:Cooling:EnergyTransfer:Zone:M NW APARTMENT | 63.02 | 0.00 | 24-DEC-13:10 | 6264.24 | 05-MAY-16:30 |
| EnergyTransfer:Zone:M SE APARTMENT | 74.63 | 285.74 | 06-DEC-09:00 | 5645.84 | 05-MAY-15:10 |
| Heating:EnergyTransfer:Zone:M SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:Heating:EnergyTransfer:Zone:M SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Cooling:EnergyTransfer:Zone:M SE APARTMENT | 74.63 | 285.74 | 06-DEC-09:00 | 5645.84 | 05-MAY-15:10 |
| General:Cooling:EnergyTransfer:Zone:M SE APARTMENT | 74.63 | 285.74 | 06-DEC-09:00 | 5645.84 | 05-MAY-15:10 |
| EnergyTransfer:Zone:M NE APARTMENT | 63.12 | 6.92 | 24-DEC-13:10 | 5536.97 | 06-JUN-15:10 |
| Heating:EnergyTransfer:Zone:M NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 69.32 | 24-DEC-14:00 |
| General:Heating:EnergyTransfer:Zone:M NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 69.32 | 24-DEC-14:00 |
| Cooling:EnergyTransfer:Zone:M NE APARTMENT | 63.12 | 0.00 | 24-DEC-13:20 | 5536.97 | 06-JUN-15:10 |
| General:Cooling:EnergyTransfer:Zone:M NE APARTMENT | 63.12 | 0.00 | 24-DEC-13:20 | 5536.97 | 06-JUN-15:10 |
| EnergyTransfer:Zone:M N1 APARTMENT | 52.51 | 3.90 | 24-DEC-13:20 | 3959.79 | 06-JUN-16:10 |
| Heating:EnergyTransfer:Zone:M N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 41.65 | 24-DEC-13:50 |
| General:Heating:EnergyTransfer:Zone:M N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 41.65 | 24-DEC-13:50 |
| Cooling:EnergyTransfer:Zone:M N1 APARTMENT | 52.51 | 0.00 | 24-DEC-13:30 | 3959.79 | 06-JUN-16:10 |
| General:Cooling:EnergyTransfer:Zone:M N1 APARTMENT | 52.51 | 0.00 | 24-DEC-13:30 | 3959.79 | 06-JUN-16:10 |
| EnergyTransfer:Zone:M N2 APARTMENT | 52.53 | 5.28 | 24-DEC-13:20 | 3952.26 | 06-JUN-16:10 |
| Heating:EnergyTransfer:Zone:M N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 40.30 | 24-DEC-13:50 |
| General:Heating:EnergyTransfer:Zone:M N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 40.30 | 24-DEC-13:50 |
| Cooling:EnergyTransfer:Zone:M N2 APARTMENT | 52.53 | 0.00 | 24-DEC-13:30 | 3952.26 | 06-JUN-16:10 |
| General:Cooling:EnergyTransfer:Zone:M N2 APARTMENT | 52.53 | 0.00 | 24-DEC-13:30 | 3952.26 | 06-JUN-16:10 |
| EnergyTransfer:Zone:M S1 APARTMENT | 64.76 | 314.02 | 29-DEC-17:00 | 4139.93 | 15-APR-15:10 |
| Heating:EnergyTransfer:Zone:M S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:Heating:EnergyTransfer:Zone:M S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Cooling:EnergyTransfer:Zone:M S1 APARTMENT | 64.76 | 314.02 | 29-DEC-17:00 | 4139.93 | 15-APR-15:10 |
| General:Cooling:EnergyTransfer:Zone:M S1 APARTMENT | 64.76 | 314.02 | 29-DEC-17:00 | 4139.93 | 15-APR-15:10 |
| EnergyTransfer:Zone:M S2 APARTMENT | 64.79 | 314.00 | 29-DEC-17:00 | 4140.91 | 15-APR-15:10 |
| Heating:EnergyTransfer:Zone:M S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:Heating:EnergyTransfer:Zone:M S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Cooling:EnergyTransfer:Zone:M S2 APARTMENT | 64.79 | 314.00 | 29-DEC-17:00 | 4140.91 | 15-APR-15:10 |
| General:Cooling:EnergyTransfer:Zone:M S2 APARTMENT | 64.79 | 314.00 | 29-DEC-17:00 | 4140.91 | 15-APR-15:10 |
| EnergyTransfer:Zone:T SW APARTMENT | 40.17 | 0.19 | 03-DEC-07:10 | 4521.06 | 05-MAY-16:10 |
| Heating:EnergyTransfer:Zone:T SW APARTMENT | 0.23 | 0.00 | 01-JAN-09:50 | 608.97 | 03-JAN-07:00 |
| General:Heating:EnergyTransfer:Zone:T SW APARTMENT | 0.23 | 0.00 | 01-JAN-09:50 | 608.97 | 03-JAN-07:00 |
| Cooling:EnergyTransfer:Zone:T SW APARTMENT | 39.94 | 0.00 | 01-JAN-00:10 | 4521.06 | 05-MAY-16:10 |
| General:Cooling:EnergyTransfer:Zone:T SW APARTMENT | 39.94 | 0.00 | 01-JAN-00:10 | 4521.06 | 05-MAY-16:10 |
| EnergyTransfer:Zone:T NW APARTMENT | 34.76 | 0.02 | 15-DEC-06:50 | 4461.33 | 06-JUN-16:10 |
| Heating:EnergyTransfer:Zone:T NW APARTMENT | 0.56 | 0.00 | 01-JAN-11:40 | 784.59 | 03-JAN-07:00 |
| General:Heating:EnergyTransfer:Zone:T NW APARTMENT | 0.56 | 0.00 | 01-JAN-11:40 | 784.59 | 03-JAN-07:00 |
| Cooling:EnergyTransfer:Zone:T NW APARTMENT | 34.20 | 0.00 | 01-JAN-00:10 | 4461.33 | 06-JUN-16:10 |
| General:Cooling:EnergyTransfer:Zone:T NW APARTMENT | 34.20 | 0.00 | 01-JAN-00:10 | 4461.33 | 06-JUN-16:10 |
| EnergyTransfer:Zone:T SE APARTMENT | 40.18 | 0.11 | 11-DEC-07:40 | 4057.43 | 06-JUN-15:10 |
| Heating:EnergyTransfer:Zone:T SE APARTMENT | 0.22 | 0.00 | 01-JAN-09:20 | 618.20 | 03-JAN-07:00 |
| General:Heating:EnergyTransfer:Zone:T SE APARTMENT | 0.22 | 0.00 | 01-JAN-09:20 | 618.20 | 03-JAN-07:00 |
| Cooling:EnergyTransfer:Zone:T SE APARTMENT | 39.96 | 0.00 | 01-JAN-00:10 | 4057.43 | 06-JUN-15:10 |
| General:Cooling:EnergyTransfer:Zone:T SE APARTMENT | 39.96 | 0.00 | 01-JAN-00:10 | 4057.43 | 06-JUN-15:10 |
| EnergyTransfer:Zone:T NE APARTMENT | 34.71 | 0.50 | 13-JAN-08:20 | 3985.08 | 06-JUN-15:10 |
| Heating:EnergyTransfer:Zone:T NE APARTMENT | 0.51 | 0.00 | 01-JAN-10:50 | 798.70 | 03-JAN-07:00 |
| General:Heating:EnergyTransfer:Zone:T NE APARTMENT | 0.51 | 0.00 | 01-JAN-10:50 | 798.70 | 03-JAN-07:00 |
| Cooling:EnergyTransfer:Zone:T NE APARTMENT | 34.20 | 0.00 | 01-JAN-00:10 | 3985.08 | 06-JUN-15:10 |
| General:Cooling:EnergyTransfer:Zone:T NE APARTMENT | 34.20 | 0.00 | 01-JAN-00:10 | 3985.08 | 06-JUN-15:10 |
| EnergyTransfer:Zone:T N1 APARTMENT | 28.41 | 0.07 | 31-JAN-01:50 | 3003.53 | 06-JUN-15:10 |
| Heating:EnergyTransfer:Zone:T N1 APARTMENT | 0.17 | 0.00 | 01-JAN-10:50 | 437.84 | 02-JAN-05:00 |
| General:Heating:EnergyTransfer:Zone:T N1 APARTMENT | 0.17 | 0.00 | 01-JAN-10:50 | 437.84 | 02-JAN-05:00 |
| Cooling:EnergyTransfer:Zone:T N1 APARTMENT | 28.23 | 0.00 | 01-JAN-00:10 | 3003.53 | 06-JUN-15:10 |
| General:Cooling:EnergyTransfer:Zone:T N1 APARTMENT | 28.23 | 0.00 | 01-JAN-00:10 | 3003.53 | 06-JUN-15:10 |
| EnergyTransfer:Zone:T N2 APARTMENT | 28.42 | 0.09 | 11-JAN-01:30 | 3000.16 | 06-JUN-15:10 |
| Heating:EnergyTransfer:Zone:T N2 APARTMENT | 0.18 | 0.00 | 01-JAN-10:40 | 439.65 | 02-JAN-05:00 |
| General:Heating:EnergyTransfer:Zone:T N2 APARTMENT | 0.18 | 0.00 | 01-JAN-10:40 | 439.65 | 02-JAN-05:00 |
| Cooling:EnergyTransfer:Zone:T N2 APARTMENT | 28.25 | 0.00 | 01-JAN-00:10 | 3000.16 | 06-JUN-15:10 |
| General:Cooling:EnergyTransfer:Zone:T N2 APARTMENT | 28.25 | 0.00 | 01-JAN-00:10 | 3000.16 | 06-JUN-15:10 |
| EnergyTransfer:Zone:T S1 APARTMENT | 34.16 | 0.03 | 07-JAN-05:40 | 3111.89 | 15-APR-15:10 |
| Heating:EnergyTransfer:Zone:T S1 APARTMENT | 0.03 | 0.00 | 01-JAN-00:10 | 257.04 | 02-JAN-06:00 |
| General:Heating:EnergyTransfer:Zone:T S1 APARTMENT | 0.03 | 0.00 | 01-JAN-00:10 | 257.04 | 02-JAN-06:00 |
| Cooling:EnergyTransfer:Zone:T S1 APARTMENT | 34.13 | 0.00 | 01-JAN-01:30 | 3111.89 | 15-APR-15:10 |
| General:Cooling:EnergyTransfer:Zone:T S1 APARTMENT | 34.13 | 0.00 | 01-JAN-01:30 | 3111.89 | 15-APR-15:10 |
| EnergyTransfer:Zone:T S2 APARTMENT | 34.18 | 0.12 | 07-JAN-05:40 | 3110.03 | 15-APR-15:10 |
| Heating:EnergyTransfer:Zone:T S2 APARTMENT | 0.03 | 0.00 | 01-JAN-00:10 | 258.50 | 02-JAN-06:00 |
| General:Heating:EnergyTransfer:Zone:T S2 APARTMENT | 0.03 | 0.00 | 01-JAN-00:10 | 258.50 | 02-JAN-06:00 |
| Cooling:EnergyTransfer:Zone:T S2 APARTMENT | 34.15 | 0.00 | 01-JAN-01:30 | 3110.03 | 15-APR-15:10 |
| General:Cooling:EnergyTransfer:Zone:T S2 APARTMENT | 34.15 | 0.00 | 01-JAN-01:30 | 3110.03 | 15-APR-15:10 |
| EnergyTransfer:Zone:T CORRIDOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Heating:EnergyTransfer:Zone:T CORRIDOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:Heating:EnergyTransfer:Zone:T CORRIDOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Cooling:EnergyTransfer:Zone:T CORRIDOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:Cooling:EnergyTransfer:Zone:T CORRIDOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| EnergyTransfer:Zone:G CORRIDOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Heating:EnergyTransfer:Zone:G CORRIDOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:Heating:EnergyTransfer:Zone:G CORRIDOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Cooling:EnergyTransfer:Zone:G CORRIDOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:Cooling:EnergyTransfer:Zone:G CORRIDOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| EnergyTransfer:Zone:M CORRIDOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Heating:EnergyTransfer:Zone:M CORRIDOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:Heating:EnergyTransfer:Zone:M CORRIDOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Cooling:EnergyTransfer:Zone:M CORRIDOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:Cooling:EnergyTransfer:Zone:M CORRIDOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| EnergyTransfer:HVAC | 1500.95 | 0.00 | 01-JAN-13:40 | 131437.10 | 01-JUL-16:20 |
| HeatRecoveryForHeating:EnergyTransfer | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 30-JUN-01:00 |
| HeatRecoveryForCooling:EnergyTransfer | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 26-JUN-09:40 |
| HeatingCoils:EnergyTransfer | 6.01 | 0.00 | 01-JAN-12:40 | 9689.65 | 03-JAN-07:00 |
| CoolingCoils:EnergyTransfer | 1494.94 | 0.00 | 01-JAN-00:10 | 131437.10 | 01-JUL-16:20 |
| PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 09:14:53
Annual Building Sensible Heat Gain Components| HVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
| G SW APARTMENT | 4.258 | -2.676 | 0.000 | -37.663 | 0.000 | 0.000 | 3.583 | 1.454 | 12.213 | 11.843 | 0.000 | 0.893 | 9.730 | 0.000 | -2.698 | 0.000 | -0.937 | -0.000 |
| G NW APARTMENT | 4.259 | -2.535 | 0.037 | -32.725 | 0.000 | 0.000 | 3.661 | 1.454 | 12.213 | 7.945 | 0.000 | 0.893 | 8.348 | 0.000 | -2.684 | 0.000 | -0.865 | -0.000 |
| OFFICE | 0.000 | 0.000 | 3.623 | -24.311 | 0.000 | 0.000 | 1.965 | 7.396 | 9.469 | 10.677 | 0.000 | 0.577 | 0.000 | 0.000 | -3.456 | 0.000 | -0.450 | -5.490 |
| G NE APARTMENT | 4.259 | -2.544 | 0.034 | -32.750 | 0.000 | 0.000 | 3.661 | 1.454 | 12.213 | 7.827 | 0.000 | 0.893 | 8.381 | 0.000 | -2.553 | 0.000 | -0.874 | -0.000 |
| G N1 APARTMENT | 4.260 | -2.602 | 0.004 | -27.870 | 0.000 | 0.000 | 3.645 | 1.454 | 12.213 | 3.740 | 0.000 | 0.539 | 7.059 | 0.000 | -1.668 | 0.000 | -0.775 | -0.000 |
| G N2 APARTMENT | 4.260 | -2.603 | 0.004 | -27.879 | 0.000 | 0.000 | 3.645 | 1.454 | 12.213 | 3.740 | 0.000 | 0.539 | 7.070 | 0.000 | -1.668 | 0.000 | -0.775 | -0.000 |
| G S1 APARTMENT | 4.260 | -2.722 | 0.000 | -33.410 | 0.000 | 0.000 | 3.570 | 1.454 | 12.213 | 7.698 | 0.000 | 0.539 | 8.856 | 0.000 | -1.633 | 0.000 | -0.825 | -0.000 |
| G S2 APARTMENT | 4.259 | -2.726 | 0.000 | -36.288 | 0.000 | 0.000 | 3.569 | 1.454 | 12.213 | 7.665 | 0.000 | 0.539 | 11.790 | 0.000 | -1.648 | 0.000 | -0.827 | -0.000 |
| M SW APARTMENT | 8.518 | -5.361 | 0.000 | -77.600 | 0.000 | 0.000 | 7.164 | 2.908 | 24.426 | 23.792 | 0.000 | 2.561 | 21.175 | 0.000 | -5.374 | 0.000 | -2.210 | -0.000 |
| M NW APARTMENT | 8.519 | -5.113 | 0.041 | -66.470 | 0.000 | 0.000 | 7.312 | 2.908 | 24.426 | 16.020 | 0.000 | 2.561 | 17.260 | 0.000 | -5.398 | 0.000 | -2.066 | -0.000 |
| M SE APARTMENT | 8.518 | -5.369 | 0.000 | -77.783 | 0.000 | 0.000 | 7.163 | 2.908 | 24.426 | 23.698 | 0.000 | 2.561 | 21.333 | 0.000 | -5.241 | 0.000 | -2.215 | -0.000 |
| M NE APARTMENT | 8.519 | -5.134 | 0.039 | -66.541 | 0.000 | 0.000 | 7.311 | 2.908 | 24.426 | 15.781 | 0.000 | 2.561 | 17.351 | 0.000 | -5.131 | 0.000 | -2.090 | -0.000 |
| M N1 APARTMENT | 8.522 | -5.284 | 0.000 | -55.743 | 0.000 | 0.000 | 7.271 | 2.908 | 24.426 | 7.558 | 0.000 | 1.545 | 13.969 | 0.000 | -3.373 | 0.000 | -1.799 | -0.000 |
| M N2 APARTMENT | 8.522 | -5.285 | 0.000 | -55.766 | 0.000 | 0.000 | 7.271 | 2.908 | 24.426 | 7.557 | 0.000 | 1.545 | 13.997 | 0.000 | -3.374 | 0.000 | -1.801 | -0.000 |
| M S1 APARTMENT | 8.521 | -5.459 | 0.000 | -67.824 | 0.000 | 0.000 | 7.137 | 2.908 | 24.426 | 15.454 | 0.000 | 1.545 | 18.426 | 0.000 | -3.254 | 0.000 | -1.878 | -0.000 |
| M S2 APARTMENT | 8.521 | -5.459 | 0.000 | -67.847 | 0.000 | 0.000 | 7.137 | 2.908 | 24.426 | 15.453 | 0.000 | 1.545 | 18.450 | 0.000 | -3.254 | 0.000 | -1.878 | -0.000 |
| T SW APARTMENT | 4.258 | -2.377 | 0.755 | -42.341 | 0.000 | 0.000 | 3.658 | 1.454 | 12.213 | 11.749 | 0.000 | 1.685 | 12.496 | 0.000 | -2.405 | 0.000 | -1.145 | -0.001 |
| T NW APARTMENT | 4.259 | -2.244 | 1.344 | -37.006 | 0.000 | 0.000 | 3.728 | 1.454 | 12.213 | 7.888 | 0.000 | 1.685 | 10.092 | 0.000 | -2.397 | 0.000 | -1.016 | -0.001 |
| T SE APARTMENT | 4.258 | -2.389 | 0.722 | -42.330 | 0.000 | 0.000 | 3.658 | 1.454 | 12.213 | 11.704 | 0.000 | 1.685 | 12.542 | 0.000 | -2.350 | 0.000 | -1.168 | -0.001 |
| T NE APARTMENT | 4.259 | -2.253 | 1.269 | -36.962 | 0.000 | 0.000 | 3.730 | 1.454 | 12.213 | 7.790 | 0.000 | 1.685 | 10.141 | 0.000 | -2.286 | 0.000 | -1.039 | -0.000 |
| T N1 APARTMENT | 4.260 | -2.293 | 0.730 | -30.752 | 0.000 | 0.000 | 3.716 | 1.454 | 12.213 | 3.728 | 0.000 | 1.016 | 8.268 | 0.000 | -1.494 | 0.000 | -0.846 | -0.000 |
| T N2 APARTMENT | 4.260 | -2.293 | 0.731 | -30.768 | 0.000 | 0.000 | 3.716 | 1.454 | 12.213 | 3.726 | 0.000 | 1.016 | 8.285 | 0.000 | -1.493 | 0.000 | -0.848 | -0.000 |
| T S1 APARTMENT | 4.259 | -2.455 | 0.290 | -36.201 | 0.000 | 0.000 | 3.639 | 1.454 | 12.213 | 7.656 | 0.000 | 1.016 | 10.581 | 0.000 | -1.476 | 0.000 | -0.977 | -0.000 |
| T S2 APARTMENT | 4.259 | -2.455 | 0.291 | -36.222 | 0.000 | 0.000 | 3.639 | 1.454 | 12.213 | 7.655 | 0.000 | 1.016 | 10.603 | 0.000 | -1.476 | 0.000 | -0.977 | -0.001 |
| T CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 5.433 | 11.688 | 0.000 | 0.940 | 0.000 | 0.187 | 0.000 | 0.000 | -0.261 | 0.000 | -0.106 | -17.881 |
| G CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 5.043 | 11.688 | 3.530 | 2.671 | 0.000 | 5.806 | 0.000 | 0.000 | -0.860 | 0.000 | -7.394 | -20.484 |
| M CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 10.571 | 23.376 | 0.000 | 1.879 | 0.000 | 0.312 | 0.000 | 0.000 | -0.581 | 0.000 | -0.199 | -35.359 |
| Total Facility | 132.047 | -79.631 | 9.913 | -1081.051 | 0.000 | 0.000 | 135.598 | 99.229 | 391.594 | 253.834 | 0.000 | 38.943 | 286.204 | 0.000 | -69.487 | 0.000 | -37.981 | -79.218 |
| Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
| G SW APARTMENT | 06-JUN-16:01 | 0.00 | 641.83 | 0.00 | -3432.53 | 0.00 | 0.00 | 0.00 | 86.80 | 588.62 | 1527.16 | 0.00 | 310.72 | 277.40 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| G NW APARTMENT | 06-JUN-16:40 | 0.00 | 632.55 | 0.00 | -3440.54 | 0.00 | 0.00 | 86.96 | 86.80 | 588.62 | 1486.94 | 0.00 | 258.22 | 300.46 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| OFFICE | 20-NOV-08:62 | 0.00 | 0.00 | 0.00 | -7292.06 | 0.00 | 0.00 | 252.36 | 582.92 | 588.62 | 430.45 | 0.00 | 0.00 | 5493.07 | 0.00 | -0.00 | 0.00 | -55.36 | 0.00 |
| G NE APARTMENT | 06-JUN-16:01 | 0.00 | 641.93 | 0.00 | -3153.10 | 0.00 | 0.00 | 86.96 | 86.80 | 588.62 | 875.53 | 0.00 | 310.72 | 562.54 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| G N1 APARTMENT | 07-JUN-17:14 | 0.00 | 628.98 | 0.00 | -2559.06 | 0.00 | 0.00 | 145.49 | 117.18 | 588.62 | 529.62 | 0.00 | 90.51 | 458.65 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| G N2 APARTMENT | 07-JUN-17:14 | 0.00 | 628.98 | 0.00 | -2554.35 | 0.00 | 0.00 | 145.49 | 117.18 | 588.62 | 529.68 | 0.00 | 90.51 | 453.88 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| G S1 APARTMENT | 01-OCT-15:10 | 0.00 | 390.39 | 0.00 | -2376.96 | 0.00 | 0.00 | 167.23 | 60.76 | 470.90 | 764.86 | 0.00 | 32.48 | 490.34 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| G S2 APARTMENT | 01-OCT-15:10 | 0.00 | 390.39 | 0.00 | -2549.89 | 0.00 | 0.00 | 167.23 | 60.76 | 470.90 | 762.77 | 0.00 | 32.48 | 665.38 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| M SW APARTMENT | 05-MAY-16:03 | 0.00 | 1217.79 | 0.00 | -7620.20 | 0.00 | 0.00 | 0.00 | 173.60 | 1177.25 | 3013.78 | 0.00 | 1077.38 | 960.39 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| M NW APARTMENT | 05-MAY-16:30 | 0.00 | 1205.56 | 0.00 | -7469.74 | 0.00 | 0.00 | 173.92 | 173.60 | 1177.25 | 2948.47 | 0.00 | 1041.13 | 749.82 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| M SE APARTMENT | 05-MAY-15:10 | 0.00 | 1234.86 | 0.00 | -6880.12 | 0.00 | 0.00 | 0.00 | 121.52 | 941.80 | 1734.28 | 0.00 | 1153.16 | 1694.50 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| M NE APARTMENT | 06-JUN-15:10 | 0.00 | 1295.68 | 0.00 | -6832.03 | 0.00 | 0.00 | 100.34 | 121.52 | 941.80 | 1765.69 | 0.00 | 1165.27 | 1441.74 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| M N1 APARTMENT | 06-JUN-16:08 | 0.00 | 1283.84 | 0.00 | -5245.69 | 0.00 | 0.00 | 173.91 | 173.60 | 1177.25 | 1129.13 | 0.00 | 538.13 | 769.83 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| M N2 APARTMENT | 06-JUN-16:08 | 0.00 | 1283.84 | 0.00 | -5238.17 | 0.00 | 0.00 | 173.91 | 173.60 | 1177.25 | 1129.20 | 0.00 | 538.13 | 762.24 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| M S1 APARTMENT | 15-APR-15:10 | 0.00 | 1046.73 | 0.00 | -5186.99 | 0.00 | 0.00 | 334.45 | 121.52 | 941.80 | 1246.27 | 0.00 | 650.55 | 845.66 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| M S2 APARTMENT | 15-APR-15:10 | 0.00 | 1046.73 | 0.00 | -5187.96 | 0.00 | 0.00 | 334.45 | 121.52 | 941.80 | 1246.24 | 0.00 | 650.55 | 846.67 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| T SW APARTMENT | 05-MAY-16:03 | 0.00 | 608.89 | 0.00 | -5130.07 | 0.00 | 0.00 | 0.00 | 86.80 | 588.62 | 1473.36 | 0.00 | 711.08 | 1661.33 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| T NW APARTMENT | 06-JUN-16:03 | 0.00 | 641.83 | 0.00 | -5103.29 | 0.00 | 0.00 | 86.96 | 86.80 | 588.62 | 1561.23 | 0.00 | 588.90 | 1548.96 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| T SE APARTMENT | 06-JUN-15:10 | 0.00 | 647.74 | 0.00 | -4704.69 | 0.00 | 0.00 | 0.00 | 60.76 | 470.90 | 838.95 | 0.00 | 769.19 | 1917.16 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| T NE APARTMENT | 06-JUN-15:10 | 0.00 | 647.80 | 0.00 | -4632.43 | 0.00 | 0.00 | 50.17 | 60.76 | 470.90 | 855.04 | 0.00 | 769.18 | 1778.59 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| T N1 APARTMENT | 06-JUN-15:10 | 0.00 | 647.87 | 0.00 | -3651.10 | 0.00 | 0.00 | 50.17 | 60.76 | 470.90 | 529.70 | 0.00 | 463.95 | 1427.75 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| T N2 APARTMENT | 06-JUN-15:10 | 0.00 | 647.87 | 0.00 | -3647.74 | 0.00 | 0.00 | 50.17 | 60.76 | 470.90 | 529.74 | 0.00 | 463.95 | 1424.35 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| T S1 APARTMENT | 15-APR-15:10 | 0.00 | 523.35 | 0.00 | -3635.48 | 0.00 | 0.00 | 167.23 | 60.76 | 470.90 | 607.93 | 0.00 | 429.22 | 1376.11 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| T S2 APARTMENT | 15-APR-15:10 | 0.00 | 523.35 | 0.00 | -3633.62 | 0.00 | 0.00 | 167.23 | 60.76 | 470.90 | 607.94 | 0.00 | 429.22 | 1374.23 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| T CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| G CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Total Facility | 06-JUN-15:10 | 0.00 | 20083.12 | 0.00 | -107677.72 | 0.00 | 0.00 | 1360.39 | 3948.92 | 15334.78 | 28203.33 | 0.00 | 16475.76 | 22271.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
| G SW APARTMENT | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| G NW APARTMENT | 06-FEB-13:10 | 18.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.94 | 17.36 | 388.49 | 411.04 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -0.35 | -877.31 |
| OFFICE | 08-JUN-16:01 | 0.00 | 0.00 | 1198.97 | 0.00 | 0.00 | 0.00 | 0.00 | 116.58 | 294.31 | 778.85 | 0.00 | 22.03 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -2410.74 |
| G NE APARTMENT | 08-JAN-15:00 | 3.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.34 | 17.36 | 382.60 | 204.13 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -7.55 | -643.55 |
| G N1 APARTMENT | 08-JAN-15:00 | 3.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.32 | 17.36 | 382.60 | 122.46 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -6.67 | -562.42 |
| G N2 APARTMENT | 08-JAN-15:00 | 2.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.29 | 17.36 | 382.60 | 122.26 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -6.87 | -561.61 |
| G S1 APARTMENT | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| G S2 APARTMENT | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M SW APARTMENT | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M NW APARTMENT | 24-DEC-14:00 | 76.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85.51 | 34.72 | 776.98 | 1205.27 | 0.00 | 19.29 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -2198.34 |
| M SE APARTMENT | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M NE APARTMENT | 24-DEC-14:00 | 69.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.77 | 34.72 | 776.98 | 536.11 | 0.00 | 15.34 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -1517.24 |
| M N1 APARTMENT | 24-DEC-13:50 | 41.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.03 | 34.72 | 776.98 | 315.85 | 0.00 | 0.14 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -1253.38 |
| M N2 APARTMENT | 24-DEC-13:50 | 40.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83.92 | 34.72 | 776.98 | 315.10 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -0.31 | -1250.71 |
| M S1 APARTMENT | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M S2 APARTMENT | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T SW APARTMENT | 03-JAN-07:00 | -466.33 | 0.00 | 1075.27 | 0.00 | 0.00 | 0.00 | 194.99 | 60.76 | 317.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -464.57 | 0.00 | -60.83 | -657.14 |
| T NW APARTMENT | 03-JAN-07:00 | -466.33 | 0.00 | 1250.87 | 0.00 | 0.00 | 0.00 | 194.99 | 60.76 | 317.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -459.03 | 0.00 | -60.83 | -838.30 |
| T SE APARTMENT | 03-JAN-07:00 | -466.33 | 0.00 | 1084.50 | 0.00 | 0.00 | 0.00 | 194.99 | 60.76 | 317.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -461.80 | 0.00 | -60.83 | -669.14 |
| T NE APARTMENT | 03-JAN-07:00 | -466.33 | 0.00 | 1264.98 | 0.00 | 0.00 | 0.00 | 194.99 | 60.76 | 317.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -456.19 | 0.00 | -60.83 | -855.24 |
| T N1 APARTMENT | 02-JAN-05:00 | -432.55 | 0.00 | 870.38 | 0.00 | 0.00 | 0.00 | 194.99 | 26.04 | 223.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -257.56 | 0.00 | 0.00 | -624.97 |
| T N2 APARTMENT | 02-JAN-05:00 | -432.55 | 0.00 | 872.18 | 0.00 | 0.00 | 0.00 | 194.99 | 26.04 | 223.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -257.53 | 0.00 | 0.00 | -626.81 |
| T S1 APARTMENT | 02-JAN-06:00 | -435.57 | 0.00 | 692.61 | 0.00 | 0.00 | 0.00 | 194.99 | 56.42 | 253.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -262.44 | 0.00 | 0.00 | -499.11 |
| T S2 APARTMENT | 02-JAN-06:00 | -435.57 | 0.00 | 694.07 | 0.00 | 0.00 | 0.00 | 194.99 | 56.42 | 253.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -262.41 | 0.00 | 0.00 | -500.60 |
| T CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| G CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Total Facility | 03-JAN-07:00 | -15026.37 | 214.71 | 10154.70 | -214.71 | 0.00 | 0.00 | 7189.98 | 3482.59 | 10216.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -13001.66 | 0.00 | -2644.93 | -370.45 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 09:14:53
System Ventilation Requirements for Cooling| Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
| SPLIT GSW | 0.3916 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.3916 | 0.0663 | 1.0000 | Not calculated | 0.0260 | 0.0663 | ||
| SPLIT GNW | 0.3905 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.3905 | 0.0665 | 1.0000 | Not calculated | 0.0260 | 0.0665 | ||
| SPLIT OFFICE | 0.4488 | 0.0000 | 4.7495 | 1.0000 | Calculated from schedules | 0.0381 | 0.4488 | 0.0849 | 1.0000 | Not calculated | 0.0381 | 0.0849 | ||
| SPLIT GNE | 0.3790 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.3790 | 0.0685 | 1.0000 | Not calculated | 0.0260 | 0.0685 | ||
| SPLIT GN1 | 0.3357 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.3357 | 0.0773 | 1.0000 | Not calculated | 0.0260 | 0.0773 | ||
| SPLIT GN2 | 0.3355 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.3355 | 0.0774 | 1.0000 | Not calculated | 0.0260 | 0.0774 | ||
| SPLIT GS1 | 0.3374 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.3374 | 0.0769 | 1.0000 | Not calculated | 0.0260 | 0.0769 | ||
| SPLIT GS2 | 0.3399 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.3399 | 0.0764 | 1.0000 | Not calculated | 0.0260 | 0.0764 | ||
| SPLIT MSW | 0.8801 | 0.0000 | 5.0000 | 1.0000 | Calculated from schedules | 0.0519 | 0.8801 | 0.0590 | 1.0000 | Not calculated | 0.0519 | 0.0590 | ||
| SPLIT MNW | 0.8776 | 0.0000 | 5.0000 | 1.0000 | Calculated from schedules | 0.0519 | 0.8776 | 0.0591 | 1.0000 | Not calculated | 0.0519 | 0.0591 | ||
| SPLIT MSE | 0.8512 | 0.0000 | 5.0000 | 1.0000 | Calculated from schedules | 0.0519 | 0.8512 | 0.0610 | 1.0000 | Not calculated | 0.0519 | 0.0610 | ||
| SPLIT MNE | 0.8487 | 0.0000 | 5.0000 | 1.0000 | Calculated from schedules | 0.0519 | 0.8487 | 0.0612 | 1.0000 | Not calculated | 0.0519 | 0.0612 | ||
| SPLIT MN1 | 0.7411 | 0.0000 | 5.0000 | 1.0000 | Calculated from schedules | 0.0519 | 0.7411 | 0.0700 | 1.0000 | Not calculated | 0.0519 | 0.0700 | ||
| SPLIT MN2 | 0.7405 | 0.0000 | 5.0000 | 1.0000 | Calculated from schedules | 0.0519 | 0.7405 | 0.0701 | 1.0000 | Not calculated | 0.0519 | 0.0701 | ||
| SPLIT MS1 | 0.7443 | 0.0000 | 5.0000 | 1.0000 | Calculated from schedules | 0.0519 | 0.7443 | 0.0697 | 1.0000 | Not calculated | 0.0519 | 0.0697 | ||
| SPLIT MS2 | 0.7437 | 0.0000 | 5.0000 | 1.0000 | Calculated from schedules | 0.0519 | 0.7437 | 0.0698 | 1.0000 | Not calculated | 0.0519 | 0.0698 | ||
| SPLIT TSW | 0.4978 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.4978 | 0.0521 | 1.0000 | Not calculated | 0.0260 | 0.0521 | ||
| SPLIT TNW | 0.4988 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.4988 | 0.0520 | 1.0000 | Not calculated | 0.0260 | 0.0520 | ||
| SPLIT TSE | 0.4757 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.4757 | 0.0546 | 1.0000 | Not calculated | 0.0260 | 0.0546 | ||
| SPLIT TNE | 0.4768 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.4768 | 0.0544 | 1.0000 | Not calculated | 0.0260 | 0.0544 | ||
| SPLIT TN1 | 0.4258 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.4258 | 0.0610 | 1.0000 | Not calculated | 0.0260 | 0.0610 | ||
| SPLIT TN2 | 0.4250 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.4250 | 0.0611 | 1.0000 | Not calculated | 0.0260 | 0.0611 | ||
| SPLIT TS1 | 0.4249 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.4249 | 0.0611 | 1.0000 | Not calculated | 0.0260 | 0.0611 | ||
| SPLIT TS2 | 0.4241 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.4241 | 0.0612 | 1.0000 | Not calculated | 0.0260 | 0.0612 |
| Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
| SPLIT GSW | 0.3916 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.3916 | 1.0000 | 1.0000 | Not calculated | 0.0260 | 0.0663 | ||
| SPLIT GNW | 0.3905 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.3905 | 1.0000 | 1.0000 | Not calculated | 0.0260 | 0.0665 | ||
| SPLIT OFFICE | 0.4488 | 0.0000 | 4.7495 | 1.0000 | Calculated from schedules | 0.0381 | 0.4488 | 1.0000 | 1.0000 | Not calculated | 0.0381 | 0.0849 | ||
| SPLIT GNE | 0.3790 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.3790 | 1.0000 | 1.0000 | Not calculated | 0.0260 | 0.0685 | ||
| SPLIT GN1 | 0.3357 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.3357 | 1.0000 | 1.0000 | Not calculated | 0.0260 | 0.0773 | ||
| SPLIT GN2 | 0.3355 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.3355 | 1.0000 | 1.0000 | Not calculated | 0.0260 | 0.0774 | ||
| SPLIT GS1 | 0.3374 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.3374 | 1.0000 | 1.0000 | Not calculated | 0.0260 | 0.0769 | ||
| SPLIT GS2 | 0.3399 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.3399 | 1.0000 | 1.0000 | Not calculated | 0.0260 | 0.0764 | ||
| SPLIT MSW | 0.8801 | 0.0000 | 5.0000 | 1.0000 | Calculated from schedules | 0.0519 | 0.8801 | 1.0000 | 1.0000 | Not calculated | 0.0519 | 0.0590 | ||
| SPLIT MNW | 0.8776 | 0.0000 | 5.0000 | 1.0000 | Calculated from schedules | 0.0519 | 0.8776 | 1.0000 | 1.0000 | Not calculated | 0.0519 | 0.0591 | ||
| SPLIT MSE | 0.8512 | 0.0000 | 5.0000 | 1.0000 | Calculated from schedules | 0.0519 | 0.8512 | 1.0000 | 1.0000 | Not calculated | 0.0519 | 0.0610 | ||
| SPLIT MNE | 0.8487 | 0.0000 | 5.0000 | 1.0000 | Calculated from schedules | 0.0519 | 0.8487 | 1.0000 | 1.0000 | Not calculated | 0.0519 | 0.0612 | ||
| SPLIT MN1 | 0.7411 | 0.0000 | 5.0000 | 1.0000 | Calculated from schedules | 0.0519 | 0.7411 | 1.0000 | 1.0000 | Not calculated | 0.0519 | 0.0700 | ||
| SPLIT MN2 | 0.7405 | 0.0000 | 5.0000 | 1.0000 | Calculated from schedules | 0.0519 | 0.7405 | 1.0000 | 1.0000 | Not calculated | 0.0519 | 0.0701 | ||
| SPLIT MS1 | 0.7443 | 0.0000 | 5.0000 | 1.0000 | Calculated from schedules | 0.0519 | 0.7443 | 1.0000 | 1.0000 | Not calculated | 0.0519 | 0.0697 | ||
| SPLIT MS2 | 0.7437 | 0.0000 | 5.0000 | 1.0000 | Calculated from schedules | 0.0519 | 0.7437 | 1.0000 | 1.0000 | Not calculated | 0.0519 | 0.0698 | ||
| SPLIT TSW | 0.4978 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.4978 | 1.0000 | 1.0000 | Not calculated | 0.0260 | 0.0521 | ||
| SPLIT TNW | 0.4988 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.4988 | 1.0000 | 1.0000 | Not calculated | 0.0260 | 0.0520 | ||
| SPLIT TSE | 0.4757 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.4757 | 1.0000 | 1.0000 | Not calculated | 0.0260 | 0.0546 | ||
| SPLIT TNE | 0.4768 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.4768 | 1.0000 | 1.0000 | Not calculated | 0.0260 | 0.0544 | ||
| SPLIT TN1 | 0.4258 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.4258 | 1.0000 | 1.0000 | Not calculated | 0.0260 | 0.0610 | ||
| SPLIT TN2 | 0.4250 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.4250 | 1.0000 | 1.0000 | Not calculated | 0.0260 | 0.0611 | ||
| SPLIT TS1 | 0.4249 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.4249 | 1.0000 | 1.0000 | Not calculated | 0.0260 | 0.0611 | ||
| SPLIT TS2 | 0.4241 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.4241 | 1.0000 | 1.0000 | Not calculated | 0.0260 | 0.0612 |
| AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
| G SW APARTMENT | SPLIT GSW | 0.000000 | 2.5000 | 0.000294 | 88.25 | 0.0260 | 1.0000 | 0.0260 | 1.000 | 0.0260 |
| G NW APARTMENT | SPLIT GNW | 0.000000 | 2.5000 | 0.000294 | 88.25 | 0.0260 | 1.0000 | 0.0260 | 1.000 | 0.0260 |
| OFFICE | SPLIT OFFICE | 0.000000 | 4.7495 | 0.000432 | 88.25 | 0.0381 | 1.0000 | 0.0381 | 1.000 | 0.0381 |
| G NE APARTMENT | SPLIT GNE | 0.000000 | 2.5000 | 0.000294 | 88.25 | 0.0260 | 1.0000 | 0.0260 | 1.000 | 0.0260 |
| G N1 APARTMENT | SPLIT GN1 | 0.000000 | 2.5000 | 0.000294 | 88.25 | 0.0260 | 1.0000 | 0.0260 | 1.000 | 0.0260 |
| G N2 APARTMENT | SPLIT GN2 | 0.000000 | 2.5000 | 0.000294 | 88.25 | 0.0260 | 1.0000 | 0.0260 | 1.000 | 0.0260 |
| G S1 APARTMENT | SPLIT GS1 | 0.000000 | 2.5000 | 0.000294 | 88.25 | 0.0260 | 1.0000 | 0.0260 | 1.000 | 0.0260 |
| G S2 APARTMENT | SPLIT GS2 | 0.000000 | 2.5000 | 0.000294 | 88.25 | 0.0260 | 1.0000 | 0.0260 | 1.000 | 0.0260 |
| M SW APARTMENT | SPLIT MSW | 0.000000 | 5.0000 | 0.000294 | 176.50 | 0.0519 | 1.0000 | 0.0519 | 1.000 | 0.0519 |
| M NW APARTMENT | SPLIT MNW | 0.000000 | 5.0000 | 0.000294 | 176.50 | 0.0519 | 1.0000 | 0.0519 | 1.000 | 0.0519 |
| M SE APARTMENT | SPLIT MSE | 0.000000 | 5.0000 | 0.000294 | 176.50 | 0.0519 | 1.0000 | 0.0519 | 1.000 | 0.0519 |
| M NE APARTMENT | SPLIT MNE | 0.000000 | 5.0000 | 0.000294 | 176.50 | 0.0519 | 1.0000 | 0.0519 | 1.000 | 0.0519 |
| M N1 APARTMENT | SPLIT MN1 | 0.000000 | 5.0000 | 0.000294 | 176.50 | 0.0519 | 1.0000 | 0.0519 | 1.000 | 0.0519 |
| M N2 APARTMENT | SPLIT MN2 | 0.000000 | 5.0000 | 0.000294 | 176.50 | 0.0519 | 1.0000 | 0.0519 | 1.000 | 0.0519 |
| M S1 APARTMENT | SPLIT MS1 | 0.000000 | 5.0000 | 0.000294 | 176.50 | 0.0519 | 1.0000 | 0.0519 | 1.000 | 0.0519 |
| M S2 APARTMENT | SPLIT MS2 | 0.000000 | 5.0000 | 0.000294 | 176.50 | 0.0519 | 1.0000 | 0.0519 | 1.000 | 0.0519 |
| T SW APARTMENT | SPLIT TSW | 0.000000 | 2.5000 | 0.000294 | 88.25 | 0.0260 | 1.0000 | 0.0260 | 1.000 | 0.0260 |
| T NW APARTMENT | SPLIT TNW | 0.000000 | 2.5000 | 0.000294 | 88.25 | 0.0260 | 1.0000 | 0.0260 | 1.000 | 0.0260 |
| T SE APARTMENT | SPLIT TSE | 0.000000 | 2.5000 | 0.000294 | 88.25 | 0.0260 | 1.0000 | 0.0260 | 1.000 | 0.0260 |
| T NE APARTMENT | SPLIT TNE | 0.000000 | 2.5000 | 0.000294 | 88.25 | 0.0260 | 1.0000 | 0.0260 | 1.000 | 0.0260 |
| T N1 APARTMENT | SPLIT TN1 | 0.000000 | 2.5000 | 0.000294 | 88.25 | 0.0260 | 1.0000 | 0.0260 | 1.000 | 0.0260 |
| T N2 APARTMENT | SPLIT TN2 | 0.000000 | 2.5000 | 0.000294 | 88.25 | 0.0260 | 1.0000 | 0.0260 | 1.000 | 0.0260 |
| T S1 APARTMENT | SPLIT TS1 | 0.000000 | 2.5000 | 0.000294 | 88.25 | 0.0260 | 1.0000 | 0.0260 | 1.000 | 0.0260 |
| T S2 APARTMENT | SPLIT TS2 | 0.000000 | 2.5000 | 0.000294 | 88.25 | 0.0260 | 1.0000 | 0.0260 | 1.000 | 0.0260 |
| People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
| SPLIT GSW | 0.000000 | 2.50 | 0.000294 | 88.2493 | 0.0260 | 0.0260 | 0.0260 |
| SPLIT GNW | 0.000000 | 2.50 | 0.000294 | 88.2493 | 0.0260 | 0.0260 | 0.0260 |
| SPLIT OFFICE | 0.000000 | 4.75 | 0.000432 | 88.2493 | 0.0381 | 0.0381 | 0.0381 |
| SPLIT GNE | 0.000000 | 2.50 | 0.000294 | 88.2493 | 0.0260 | 0.0260 | 0.0260 |
| SPLIT GN1 | 0.000000 | 2.50 | 0.000294 | 88.2493 | 0.0260 | 0.0260 | 0.0260 |
| SPLIT GN2 | 0.000000 | 2.50 | 0.000294 | 88.2493 | 0.0260 | 0.0260 | 0.0260 |
| SPLIT GS1 | 0.000000 | 2.50 | 0.000294 | 88.2493 | 0.0260 | 0.0260 | 0.0260 |
| SPLIT GS2 | 0.000000 | 2.50 | 0.000294 | 88.2493 | 0.0260 | 0.0260 | 0.0260 |
| SPLIT MSW | 0.000000 | 5.00 | 0.000294 | 176.4985 | 0.0519 | 0.0519 | 0.0519 |
| SPLIT MNW | 0.000000 | 5.00 | 0.000294 | 176.4985 | 0.0519 | 0.0519 | 0.0519 |
| SPLIT MSE | 0.000000 | 5.00 | 0.000294 | 176.4985 | 0.0519 | 0.0519 | 0.0519 |
| SPLIT MNE | 0.000000 | 5.00 | 0.000294 | 176.4985 | 0.0519 | 0.0519 | 0.0519 |
| SPLIT MN1 | 0.000000 | 5.00 | 0.000294 | 176.4985 | 0.0519 | 0.0519 | 0.0519 |
| SPLIT MN2 | 0.000000 | 5.00 | 0.000294 | 176.4985 | 0.0519 | 0.0519 | 0.0519 |
| SPLIT MS1 | 0.000000 | 5.00 | 0.000294 | 176.4985 | 0.0519 | 0.0519 | 0.0519 |
| SPLIT MS2 | 0.000000 | 5.00 | 0.000294 | 176.4985 | 0.0519 | 0.0519 | 0.0519 |
| SPLIT TSW | 0.000000 | 2.50 | 0.000294 | 88.2493 | 0.0260 | 0.0260 | 0.0260 |
| SPLIT TNW | 0.000000 | 2.50 | 0.000294 | 88.2493 | 0.0260 | 0.0260 | 0.0260 |
| SPLIT TSE | 0.000000 | 2.50 | 0.000294 | 88.2493 | 0.0260 | 0.0260 | 0.0260 |
| SPLIT TNE | 0.000000 | 2.50 | 0.000294 | 88.2493 | 0.0260 | 0.0260 | 0.0260 |
| SPLIT TN1 | 0.000000 | 2.50 | 0.000294 | 88.2493 | 0.0260 | 0.0260 | 0.0260 |
| SPLIT TN2 | 0.000000 | 2.50 | 0.000294 | 88.2493 | 0.0260 | 0.0260 | 0.0260 |
| SPLIT TS1 | 0.000000 | 2.50 | 0.000294 | 88.2493 | 0.0260 | 0.0260 | 0.0260 |
| SPLIT TS2 | 0.000000 | 2.50 | 0.000294 | 88.2493 | 0.0260 | 0.0260 | 0.0260 |
| AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
| G SW APARTMENT | SPLIT GSW | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.3916 | 0.3916 | 0.3916 | No | 0.0260 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| G NW APARTMENT | SPLIT GNW | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.3905 | 0.3905 | 0.3905 | No | 0.0260 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| OFFICE | SPLIT OFFICE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4488 | 0.4488 | 0.4488 | No | 0.0381 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| G NE APARTMENT | SPLIT GNE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.3790 | 0.3790 | 0.3790 | No | 0.0260 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| G N1 APARTMENT | SPLIT GN1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.3357 | 0.3357 | 0.3357 | No | 0.0260 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| G N2 APARTMENT | SPLIT GN2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.3355 | 0.3355 | 0.3355 | No | 0.0260 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| G S1 APARTMENT | SPLIT GS1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.3374 | 0.3374 | 0.3374 | No | 0.0260 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| G S2 APARTMENT | SPLIT GS2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.3399 | 0.3399 | 0.3399 | No | 0.0260 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| M SW APARTMENT | SPLIT MSW | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8801 | 0.8801 | 0.8801 | No | 0.0519 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| M NW APARTMENT | SPLIT MNW | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8776 | 0.8776 | 0.8776 | No | 0.0519 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| M SE APARTMENT | SPLIT MSE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8512 | 0.8512 | 0.8512 | No | 0.0519 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| M NE APARTMENT | SPLIT MNE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8487 | 0.8487 | 0.8487 | No | 0.0519 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| M N1 APARTMENT | SPLIT MN1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.7411 | 0.7411 | 0.7411 | No | 0.0519 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| M N2 APARTMENT | SPLIT MN2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.7405 | 0.7405 | 0.7405 | No | 0.0519 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| M S1 APARTMENT | SPLIT MS1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.7443 | 0.7443 | 0.7443 | No | 0.0519 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| M S2 APARTMENT | SPLIT MS2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.7437 | 0.7437 | 0.7437 | No | 0.0519 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| T SW APARTMENT | SPLIT TSW | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4978 | 0.4978 | 0.4978 | No | 0.0260 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| T NW APARTMENT | SPLIT TNW | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4988 | 0.4988 | 0.4988 | No | 0.0260 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| T SE APARTMENT | SPLIT TSE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4757 | 0.4757 | 0.4757 | No | 0.0260 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| T NE APARTMENT | SPLIT TNE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4768 | 0.4768 | 0.4768 | No | 0.0260 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| T N1 APARTMENT | SPLIT TN1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4258 | 0.4258 | 0.4258 | No | 0.0260 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| T N2 APARTMENT | SPLIT TN2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4250 | 0.4250 | 0.4250 | No | 0.0260 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| T S1 APARTMENT | SPLIT TS1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4249 | 0.4249 | 0.4249 | No | 0.0260 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| T S2 APARTMENT | SPLIT TS2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4241 | 0.4241 | 0.4241 | No | 0.0260 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
| SPLIT GSW | 0.3916 | 0.3916 | 0.3916 | 0.3916 | 0.0260 | 1.0000 |
| SPLIT GNW | 0.3905 | 0.3905 | 0.3905 | 0.3905 | 0.0260 | 1.0000 |
| SPLIT OFFICE | 0.4488 | 0.4488 | 0.4488 | 0.4488 | 0.0381 | 1.0000 |
| SPLIT GNE | 0.3790 | 0.3790 | 0.3790 | 0.3790 | 0.0260 | 1.0000 |
| SPLIT GN1 | 0.3357 | 0.3357 | 0.3357 | 0.3357 | 0.0260 | 1.0000 |
| SPLIT GN2 | 0.3355 | 0.3355 | 0.3355 | 0.3355 | 0.0260 | 1.0000 |
| SPLIT GS1 | 0.3374 | 0.3374 | 0.3374 | 0.3374 | 0.0260 | 1.0000 |
| SPLIT GS2 | 0.3399 | 0.3399 | 0.3399 | 0.3399 | 0.0260 | 1.0000 |
| SPLIT MSW | 0.8801 | 0.8801 | 0.8801 | 0.8801 | 0.0519 | 1.0000 |
| SPLIT MNW | 0.8776 | 0.8776 | 0.8776 | 0.8776 | 0.0519 | 1.0000 |
| SPLIT MSE | 0.8512 | 0.8512 | 0.8512 | 0.8512 | 0.0519 | 1.0000 |
| SPLIT MNE | 0.8487 | 0.8487 | 0.8487 | 0.8487 | 0.0519 | 1.0000 |
| SPLIT MN1 | 0.7411 | 0.7411 | 0.7411 | 0.7411 | 0.0519 | 1.0000 |
| SPLIT MN2 | 0.7405 | 0.7405 | 0.7405 | 0.7405 | 0.0519 | 1.0000 |
| SPLIT MS1 | 0.7443 | 0.7443 | 0.7443 | 0.7443 | 0.0519 | 1.0000 |
| SPLIT MS2 | 0.7437 | 0.7437 | 0.7437 | 0.7437 | 0.0519 | 1.0000 |
| SPLIT TSW | 0.4978 | 0.4978 | 0.4978 | 0.4978 | 0.0260 | 1.0000 |
| SPLIT TNW | 0.4988 | 0.4988 | 0.4988 | 0.4988 | 0.0260 | 1.0000 |
| SPLIT TSE | 0.4757 | 0.4757 | 0.4757 | 0.4757 | 0.0260 | 1.0000 |
| SPLIT TNE | 0.4768 | 0.4768 | 0.4768 | 0.4768 | 0.0260 | 1.0000 |
| SPLIT TN1 | 0.4258 | 0.4258 | 0.4258 | 0.4258 | 0.0260 | 1.0000 |
| SPLIT TN2 | 0.4250 | 0.4250 | 0.4250 | 0.4250 | 0.0260 | 1.0000 |
| SPLIT TS1 | 0.4249 | 0.4249 | 0.4249 | 0.4249 | 0.0260 | 1.0000 |
| SPLIT TS2 | 0.4241 | 0.4241 | 0.4241 | 0.4241 | 0.0260 | 1.0000 |
| AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
| G SW APARTMENT | SPLIT GSW | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.3916 | 0.3916 | 0.3916 | No | 0.0260 | 0.8365 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| G NW APARTMENT | SPLIT GNW | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.3905 | 0.3905 | 0.3905 | No | 0.0260 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| OFFICE | SPLIT OFFICE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4488 | 0.4488 | 0.4488 | No | 0.0381 | 0.7443 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| G NE APARTMENT | SPLIT GNE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.3790 | 0.3790 | 0.3790 | No | 0.0260 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| G N1 APARTMENT | SPLIT GN1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.3357 | 0.3357 | 0.3357 | No | 0.0260 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| G N2 APARTMENT | SPLIT GN2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.3355 | 0.3355 | 0.3355 | No | 0.0260 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| G S1 APARTMENT | SPLIT GS1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.3374 | 0.3374 | 0.3374 | No | 0.0260 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| G S2 APARTMENT | SPLIT GS2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.3399 | 0.3399 | 0.3399 | No | 0.0260 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| M SW APARTMENT | SPLIT MSW | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8801 | 0.8801 | 0.8801 | No | 0.0519 | 0.7984 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| M NW APARTMENT | SPLIT MNW | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8776 | 0.8776 | 0.8776 | No | 0.0519 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| M SE APARTMENT | SPLIT MSE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8512 | 0.8512 | 0.8512 | No | 0.0519 | 0.7990 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| M NE APARTMENT | SPLIT MNE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8487 | 0.8487 | 0.8487 | No | 0.0519 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| M N1 APARTMENT | SPLIT MN1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.7411 | 0.7411 | 0.7411 | No | 0.0519 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| M N2 APARTMENT | SPLIT MN2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.7405 | 0.7405 | 0.7405 | No | 0.0519 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| M S1 APARTMENT | SPLIT MS1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.7443 | 0.7443 | 0.7443 | No | 0.0519 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| M S2 APARTMENT | SPLIT MS2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.7437 | 0.7437 | 0.7437 | No | 0.0519 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| T SW APARTMENT | SPLIT TSW | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4978 | 0.4978 | 0.4978 | No | 0.0260 | 0.3676 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| T NW APARTMENT | SPLIT TNW | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4988 | 0.4988 | 0.4988 | No | 0.0260 | 0.4135 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| T SE APARTMENT | SPLIT TSE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4757 | 0.4757 | 0.4757 | No | 0.0260 | 0.3677 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| T NE APARTMENT | SPLIT TNE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4768 | 0.4768 | 0.4768 | No | 0.0260 | 0.4137 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| T N1 APARTMENT | SPLIT TN1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4258 | 0.4258 | 0.4258 | No | 0.0260 | 0.6172 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| T N2 APARTMENT | SPLIT TN2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4250 | 0.4250 | 0.4250 | No | 0.0260 | 0.6172 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| T S1 APARTMENT | SPLIT TS1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4249 | 0.4249 | 0.4249 | No | 0.0260 | 0.5196 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| T S2 APARTMENT | SPLIT TS2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4241 | 0.4241 | 0.4241 | No | 0.0260 | 0.5196 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
| SPLIT GSW | 0.3916 | 0.3916 | 0.3916 | 0.3916 | 0.0260 | 1.0000 |
| SPLIT GNW | 0.3905 | 0.3905 | 0.3905 | 0.3905 | 0.0260 | 1.0000 |
| SPLIT OFFICE | 0.4488 | 0.4488 | 0.4488 | 0.4488 | 0.0381 | 1.0000 |
| SPLIT GNE | 0.3790 | 0.3790 | 0.3790 | 0.3790 | 0.0260 | 1.0000 |
| SPLIT GN1 | 0.3357 | 0.3357 | 0.3357 | 0.3357 | 0.0260 | 1.0000 |
| SPLIT GN2 | 0.3355 | 0.3355 | 0.3355 | 0.3355 | 0.0260 | 1.0000 |
| SPLIT GS1 | 0.3374 | 0.3374 | 0.3374 | 0.3374 | 0.0260 | 1.0000 |
| SPLIT GS2 | 0.3399 | 0.3399 | 0.3399 | 0.3399 | 0.0260 | 1.0000 |
| SPLIT MSW | 0.8801 | 0.8801 | 0.8801 | 0.8801 | 0.0519 | 1.0000 |
| SPLIT MNW | 0.8776 | 0.8776 | 0.8776 | 0.8776 | 0.0519 | 1.0000 |
| SPLIT MSE | 0.8512 | 0.8512 | 0.8512 | 0.8512 | 0.0519 | 1.0000 |
| SPLIT MNE | 0.8487 | 0.8487 | 0.8487 | 0.8487 | 0.0519 | 1.0000 |
| SPLIT MN1 | 0.7411 | 0.7411 | 0.7411 | 0.7411 | 0.0519 | 1.0000 |
| SPLIT MN2 | 0.7405 | 0.7405 | 0.7405 | 0.7405 | 0.0519 | 1.0000 |
| SPLIT MS1 | 0.7443 | 0.7443 | 0.7443 | 0.7443 | 0.0519 | 1.0000 |
| SPLIT MS2 | 0.7437 | 0.7437 | 0.7437 | 0.7437 | 0.0519 | 1.0000 |
| SPLIT TSW | 0.4978 | 0.4978 | 0.4978 | 0.4978 | 0.0260 | 1.0000 |
| SPLIT TNW | 0.4988 | 0.4988 | 0.4988 | 0.4988 | 0.0260 | 1.0000 |
| SPLIT TSE | 0.4757 | 0.4757 | 0.4757 | 0.4757 | 0.0260 | 1.0000 |
| SPLIT TNE | 0.4768 | 0.4768 | 0.4768 | 0.4768 | 0.0260 | 1.0000 |
| SPLIT TN1 | 0.4258 | 0.4258 | 0.4258 | 0.4258 | 0.0260 | 1.0000 |
| SPLIT TN2 | 0.4250 | 0.4250 | 0.4250 | 0.4250 | 0.0260 | 1.0000 |
| SPLIT TS1 | 0.4249 | 0.4249 | 0.4249 | 0.4249 | 0.0260 | 1.0000 |
| SPLIT TS2 | 0.4241 | 0.4241 | 0.4241 | 0.4241 | 0.0260 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 09:14:53
Sec1.1A-General Information| Data | |
| Weather File | RUNPERIOD 1 ** New Delhi-Safdarjung AP Delhi IND IWEC2 WMO#=421820 |
| Total gross floor area [m2] | 3134.61 |
| Principal Heating Source | Natural Gas |
| Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
| G SW APARTMENT | 88.25 | 88.25 | 0.00 | 117.85 |
| G NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
| OFFICE | 88.25 | 88.25 | 0.00 | 33.56 |
| G NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
| G N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
| G N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
| G S1 APARTMENT | 88.25 | 88.25 | 0.00 | 117.85 |
| G S2 APARTMENT | 88.25 | 88.25 | 0.00 | 117.85 |
| M SW APARTMENT | 88.25 | 88.25 | 0.00 | 117.85 |
| M NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
| M SE APARTMENT | 88.25 | 88.25 | 0.00 | 117.85 |
| M NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
| M N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
| M N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
| M S1 APARTMENT | 88.25 | 88.25 | 0.00 | 117.85 |
| M S2 APARTMENT | 88.25 | 88.25 | 0.00 | 117.85 |
| T SW APARTMENT | 88.25 | 88.25 | 0.00 | 117.85 |
| T NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
| T SE APARTMENT | 88.25 | 88.25 | 0.00 | 117.85 |
| T NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
| T N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
| T N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
| T S1 APARTMENT | 88.25 | 88.25 | 0.00 | 117.85 |
| T S2 APARTMENT | 88.25 | 88.25 | 0.00 | 117.85 |
| T CORRIDOR | 77.66 | 0.00 | 77.66 | 168.00 |
| G CORRIDOR | 77.66 | 0.00 | 77.66 | 168.00 |
| M CORRIDOR | 77.66 | 0.00 | 77.66 | 168.00 |
| Totals | 3134.61 | 2823.98 | 310.64 |
| Data | |
| Number of hours heating loads not met | 0.00 |
| Number of hours cooling loads not met | 0.50 |
| Number of hours not met | 0.50 |
| Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
| None |
| Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
| Heating -- General | 0.00 | 0.00 | 7.51 | 12112.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Cooling -- General | 403.68 | 38499.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Lighting -- LightsWired | 94.96 | 5496.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Lighting -- LightsPlugIn | 4.27 | 407.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Lighting -- General | 50.05 | 3183.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment -- MiscPlug | 388.06 | 18541.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment -- ElevatorLift | 65.48 | 4006.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment -- ElevatorLightsFan | 5.11 | 162.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans -- Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans -- General | 157.80 | 10921.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Recovery -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems -- Water Heater | 353.88 | 37136.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Process Subtotal [GJ] | Total Energy Use [GJ] | |
| Electricity | 458.66 | 1523.30 |
| Natural Gas | 0.00 | 7.51 |
| Additional | 0.00 | 0.00 |
| Total | 458.66 | 1530.81 |
| Process Subtotal [$] | Total Energy Cost [$] | |
| Electricity | 0.00 | |
| Natural Gas | 0.00 | |
| Additional | 0.00 | |
| Total | 0.00 |
| Rated Capacity [kW] | Annual Energy Generated [GJ] | |
| Photovoltaic | 0.00 | 0.00 |
| Wind | 0.00 | 0.00 |
| Electricty [MJ/m2] | |
| Interior Lighting (All) | 31.66 |
| Space Heating | 0.00 |
| Space Cooling | 128.78 |
| Fans (All) | 50.34 |
| Service Water Heating | 112.90 |
| Receptacle Equipment | 146.32 |
| Miscellaneous (All) | 485.96 |
| Subtotal | 485.96 |
| Natural Gas [MJ/m2] | |
| Space Heating | 2.40 |
| Service Water Heating | 0.00 |
| Miscellaneous (All) | 2.40 |
| Subtotal | 2.40 |
| Additional [MJ/m2] | |
| Subtotal | 0.00 |
| Miscellaneous | 0.00 |
| Percent [%] | |
| Interior Lighting (All) | 6.48 |
| Space Heating | 0.49 |
| Space Cooling | 26.37 |
| Fans (All) | 10.31 |
| Service Water Heating | 23.12 |
| Receptacle Equipment | 29.96 |
| Miscellaneous | 3.27 |
| Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
| OCC_APT_SCH_STAY_HOME_FAMILY | 5993. | 8760. |
| OCC_APT_SCH_CORRIDOR | 5993. | 8760. |
| OCC_APT_SCH_WORKING_FAMILY | 5845. | 6055. |
| OCC_OFF_SCH | 2210. | 2340. |
| OCC_OFF_W_SB_SCH | 1820. | 1820. |
| LTG_SCH_OFFICE | 2435. | 8760. |
| LTG_SCH_CORRIDOR | 8760. | 8760. |
| LTG_SCH_APARTMENT_HARDWIRED | 527. | 8760. |
| LTG_SCH_APARTMENT_PLUGIN | 527. | 8760. |
| EQP_APT_SCH | 5763. | 8760. |
| EQP_OFF_SCH | 4531. | 8760. |
| INF_APT_SCH | 8760. | 8760. |
| INF_OFF_SCH | 8760. | 8760. |
| INF_COR_SCH | 8760. | 8760. |
| INFIL_DOOR_OPENING_SCH | 1466. | 5840. |
| ALL OFF | 0. | 0. |
| ALL ON | 8760. | 8760. |
| ALWAYS_ON | 8760. | 8760. |
| ALLON_EXCEPT_DD | 8760. | 8760. |
| EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
| FAN_OFF_W_SB_SCH | 8240. | 8240. |
| APT_DHW_SCH | 4592. | 8760. |
| EXTERIOR_LTG_SCH | 4380. | 4380. |
| BLDG_ELEVATORS | 2270. | 8760. |
| ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
| ELEV_LIGHT_FAN_SCH_ADD_DF | 2154. | 8760. |
| SLIDING_DOORS_VENTILATION_AVAILABILITY_SCH | 5840. | 5840. |
| First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
| HTGSETP_APT_SCH | APTHEATINGSETPOINT | January | 21.10 | 365 | 21.10 | 365 |
| HTGSETP_DESIGN_OFF_SCH | OFFHEATINGSETPOINT | January | 21.10 | 365 | 21.10 | 365 |
| CLGSETP_APT_SCH | APTCOOLINGSETPOINT | July | 24.00 | 365 | 24.00 | 365 |
| CLGSETP_DESIGN_OFF_SCH | OFFCOOLINGSETPOINT | July | 23.90 | 365 | 23.90 | 365 |
| S HTGSETP_APT_SCH | S APARTMENT DUAL SP CONTROL | January | 21.10 | 365 | 21.10 | 365 |
| S CLGSETP_APT_SCH | S APARTMENT DUAL SP CONTROL | July | 24.00 | 365 | 24.00 | 365 |
| N HTGSETP_APT_SCH | N APARTMENT DUAL SP CONTROL | January | 21.10 | 365 | 21.10 | 365 |
| N CLGSETP_APT_SCH | N APARTMENT DUAL SP CONTROL | July | 24.00 | 365 | 24.00 | 365 |
| HTGSETP_OFF_SCH_YES_OPTIMUM | OFFICE DUAL SP CONTROL | January | 21.10 | 365 | 15.60 | 365 |
| CLGSETP_OFF_SCH_YES_OPTIMUM | OFFICE DUAL SP CONTROL | July | 24.00 | 365 | 29.40 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 09:14:53
Heat Index Hours| Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
| G SW APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| G NW APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| OFFICE | 4316.67 | 3299.83 | 1143.50 | 0.00 | 0.00 |
| G NE APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| G N1 APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| G N2 APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| G S1 APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| G S2 APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M SW APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M NW APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M SE APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M NE APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M N1 APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M N2 APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M S1 APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M S2 APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T SW APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T NW APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T SE APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T NE APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T N1 APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T N2 APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T S1 APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T S2 APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T CORRIDOR | 3545.17 | 3818.67 | 1396.17 | 0.00 | 0.00 |
| G CORRIDOR | 3768.33 | 3117.33 | 1869.83 | 4.50 | 0.00 |
| M CORRIDOR | 2161.83 | 6557.50 | 40.67 | 0.00 | 0.00 |
| Min | 2161.83 | 0.00 | 0.00 | 0.00 | 0.00 |
| Max | 8760.00 | 6557.50 | 1869.83 | 4.50 | 0.00 |
| Average | 7973.04 | 621.98 | 164.82 | 0.17 | 0.00 |
| Sum | 215272.00 | 16793.33 | 4450.17 | 4.50 | 0.00 |
| Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
| G SW APARTMENT | 11830.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| G NW APARTMENT | 10585.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| OFFICE | 6984.67 | 15.33 | 0.00 | 0.00 | 0.00 |
| G NE APARTMENT | 10585.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| G N1 APARTMENT | 10585.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| G N2 APARTMENT | 10585.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| G S1 APARTMENT | 11830.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| G S2 APARTMENT | 11830.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M SW APARTMENT | 11830.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M NW APARTMENT | 10585.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M SE APARTMENT | 11830.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M NE APARTMENT | 10585.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M N1 APARTMENT | 10585.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M N2 APARTMENT | 10585.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M S1 APARTMENT | 11830.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M S2 APARTMENT | 11830.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T SW APARTMENT | 11830.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T NW APARTMENT | 10585.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T SE APARTMENT | 11830.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T NE APARTMENT | 10585.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T N1 APARTMENT | 10585.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T N2 APARTMENT | 10585.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T S1 APARTMENT | 11830.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T S2 APARTMENT | 11830.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T CORRIDOR | 9536.17 | 9951.67 | 3507.17 | 0.00 | 0.00 |
| G CORRIDOR | 9807.50 | 7713.33 | 5464.83 | 9.33 | 0.00 |
| M CORRIDOR | 5733.83 | 17143.50 | 117.67 | 0.00 | 0.00 |
| Min | 5733.83 | 0.00 | 0.00 | 0.00 | 0.00 |
| Max | 11830.00 | 17143.50 | 5464.83 | 9.33 | 0.00 |
| Average | 10711.56 | 1289.77 | 336.65 | 0.35 | 0.00 |
| Sum | 289212.17 | 34823.83 | 9089.67 | 9.33 | 0.00 |
| Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
| G SW APARTMENT | 7572.67 | 1187.33 | 0.00 | 0.00 | 0.00 |
| G NW APARTMENT | 7541.17 | 1218.83 | 0.00 | 0.00 | 0.00 |
| OFFICE | 4243.50 | 3996.67 | 519.83 | 0.00 | 0.00 |
| G NE APARTMENT | 7544.17 | 1215.83 | 0.00 | 0.00 | 0.00 |
| G N1 APARTMENT | 7210.33 | 1549.67 | 0.00 | 0.00 | 0.00 |
| G N2 APARTMENT | 7210.50 | 1549.50 | 0.00 | 0.00 | 0.00 |
| G S1 APARTMENT | 7279.67 | 1480.33 | 0.00 | 0.00 | 0.00 |
| G S2 APARTMENT | 7534.33 | 1225.67 | 0.00 | 0.00 | 0.00 |
| M SW APARTMENT | 7240.00 | 1520.00 | 0.00 | 0.00 | 0.00 |
| M NW APARTMENT | 7187.83 | 1572.17 | 0.00 | 0.00 | 0.00 |
| M SE APARTMENT | 7232.00 | 1528.00 | 0.00 | 0.00 | 0.00 |
| M NE APARTMENT | 7181.67 | 1578.33 | 0.00 | 0.00 | 0.00 |
| M N1 APARTMENT | 6971.33 | 1788.67 | 0.00 | 0.00 | 0.00 |
| M N2 APARTMENT | 6971.50 | 1788.50 | 0.00 | 0.00 | 0.00 |
| M S1 APARTMENT | 7035.17 | 1724.83 | 0.00 | 0.00 | 0.00 |
| M S2 APARTMENT | 7034.83 | 1725.17 | 0.00 | 0.00 | 0.00 |
| T SW APARTMENT | 7281.50 | 1478.50 | 0.00 | 0.00 | 0.00 |
| T NW APARTMENT | 7237.67 | 1522.33 | 0.00 | 0.00 | 0.00 |
| T SE APARTMENT | 7298.50 | 1461.50 | 0.00 | 0.00 | 0.00 |
| T NE APARTMENT | 7256.33 | 1503.67 | 0.00 | 0.00 | 0.00 |
| T N1 APARTMENT | 7161.83 | 1598.17 | 0.00 | 0.00 | 0.00 |
| T N2 APARTMENT | 7161.33 | 1598.67 | 0.00 | 0.00 | 0.00 |
| T S1 APARTMENT | 7213.83 | 1546.17 | 0.00 | 0.00 | 0.00 |
| T S2 APARTMENT | 7213.50 | 1546.50 | 0.00 | 0.00 | 0.00 |
| T CORRIDOR | 68.33 | 5936.00 | 2755.67 | 0.00 | 0.00 |
| G CORRIDOR | 2876.67 | 4095.67 | 1784.17 | 3.50 | 0.00 |
| M CORRIDOR | 0.00 | 6603.00 | 2157.00 | 0.00 | 0.00 |
| Min | 0.00 | 1187.33 | 0.00 | 0.00 | 0.00 |
| Max | 7572.67 | 6603.00 | 2755.67 | 3.50 | 0.00 |
| Average | 6435.56 | 2057.02 | 267.28 | 0.13 | 0.00 |
| Sum | 173760.17 | 55539.67 | 7216.67 | 3.50 | 0.00 |
| Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
| G SW APARTMENT | 10065.83 | 1764.17 | 0.00 | 0.00 | 0.00 |
| G NW APARTMENT | 8970.50 | 1614.50 | 0.00 | 0.00 | 0.00 |
| OFFICE | 6380.67 | 619.33 | 0.00 | 0.00 | 0.00 |
| G NE APARTMENT | 8923.00 | 1662.00 | 0.00 | 0.00 | 0.00 |
| G N1 APARTMENT | 8560.67 | 2024.33 | 0.00 | 0.00 | 0.00 |
| G N2 APARTMENT | 8559.50 | 2025.50 | 0.00 | 0.00 | 0.00 |
| G S1 APARTMENT | 9652.00 | 2178.00 | 0.00 | 0.00 | 0.00 |
| G S2 APARTMENT | 10017.50 | 1812.50 | 0.00 | 0.00 | 0.00 |
| M SW APARTMENT | 9602.83 | 2227.17 | 0.00 | 0.00 | 0.00 |
| M NW APARTMENT | 8538.33 | 2046.67 | 0.00 | 0.00 | 0.00 |
| M SE APARTMENT | 9548.50 | 2281.50 | 0.00 | 0.00 | 0.00 |
| M NE APARTMENT | 8473.00 | 2112.00 | 0.00 | 0.00 | 0.00 |
| M N1 APARTMENT | 8262.83 | 2322.17 | 0.00 | 0.00 | 0.00 |
| M N2 APARTMENT | 8261.17 | 2323.83 | 0.00 | 0.00 | 0.00 |
| M S1 APARTMENT | 9306.33 | 2523.67 | 0.00 | 0.00 | 0.00 |
| M S2 APARTMENT | 9305.00 | 2525.00 | 0.00 | 0.00 | 0.00 |
| T SW APARTMENT | 9555.17 | 2274.83 | 0.00 | 0.00 | 0.00 |
| T NW APARTMENT | 8477.67 | 2107.33 | 0.00 | 0.00 | 0.00 |
| T SE APARTMENT | 9532.67 | 2297.33 | 0.00 | 0.00 | 0.00 |
| T NE APARTMENT | 8429.50 | 2155.50 | 0.00 | 0.00 | 0.00 |
| T N1 APARTMENT | 8379.50 | 2205.50 | 0.00 | 0.00 | 0.00 |
| T N2 APARTMENT | 8376.17 | 2208.83 | 0.00 | 0.00 | 0.00 |
| T S1 APARTMENT | 9456.67 | 2373.33 | 0.00 | 0.00 | 0.00 |
| T S2 APARTMENT | 9454.50 | 2375.50 | 0.00 | 0.00 | 0.00 |
| T CORRIDOR | 138.33 | 15523.00 | 7333.67 | 0.00 | 0.00 |
| G CORRIDOR | 6462.33 | 11036.50 | 5488.67 | 7.50 | 0.00 |
| M CORRIDOR | 0.00 | 17276.33 | 5718.67 | 0.00 | 0.00 |
| Min | 0.00 | 619.33 | 0.00 | 0.00 | 0.00 |
| Max | 10065.83 | 17276.33 | 7333.67 | 7.50 | 0.00 |
| Average | 8173.71 | 3477.64 | 686.70 | 0.28 | 0.00 |
| Sum | 220690.17 | 93896.33 | 18541.00 | 7.50 | 0.00 |
| SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
| None |
| SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
| None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 09:14:53
CO2 Level Hours| Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
| None |
| Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
| None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 09:14:53
Illuminance Level Hours| A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
| None |
| A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
| None |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
| January | 13.392 |
| February | 16.974 |
| March | 22.368 |
| April | 29.134 |
| May | 32.978 |
| June | 33.595 |
| July | 31.671 |
| August | 30.033 |
| September | 28.750 |
| October | 25.087 |
| November | 19.629 |
| December | 14.516 |
| Annual Sum or Average | 24.876 |
| Minimum of Months | 13.392 |
| Maximum of Months | 33.595 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Environment
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
| January | 13.392 |
| February | 16.974 |
| March | 22.368 |
| April | 29.134 |
| May | 32.978 |
| June | 33.595 |
| July | 31.671 |
| August | 30.033 |
| September | 28.750 |
| October | 25.087 |
| November | 19.629 |
| December | 14.516 |
| Annual Sum or Average | 24.876 |
| Minimum of Months | 13.392 |
| Maximum of Months | 33.595 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2012
For: Environment
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
| January | 13.392 |
| February | 16.974 |
| March | 22.368 |
| April | 29.134 |
| May | 32.978 |
| June | 33.595 |
| July | 31.671 |
| August | 30.033 |
| September | 28.750 |
| October | 25.087 |
| November | 19.629 |
| December | 14.516 |
| Annual Sum or Average | 24.876 |
| Minimum of Months | 13.392 |
| Maximum of Months | 33.595 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
| January | 13.392 |
| February | 16.974 |
| March | 22.368 |
| April | 29.134 |
| May | 32.978 |
| June | 33.595 |
| July | 31.671 |
| August | 30.033 |
| September | 28.750 |
| October | 25.087 |
| November | 19.629 |
| December | 14.516 |
| Annual Sum or Average | 24.876 |
| Minimum of Months | 13.392 |
| Maximum of Months | 33.595 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME APARTMENTMIDRISE
For: Environment
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
| January | 13.392 |
| February | 16.974 |
| March | 22.368 |
| April | 29.134 |
| May | 32.978 |
| June | 33.595 |
| July | 31.671 |
| August | 30.033 |
| September | 28.750 |
| October | 25.087 |
| November | 19.629 |
| December | 14.516 |
| Annual Sum or Average | 24.876 |
| Minimum of Months | 13.392 |
| Maximum of Months | 33.595 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
| January | 13.392 |
| February | 16.974 |
| March | 22.368 |
| April | 29.134 |
| May | 32.978 |
| June | 33.595 |
| July | 31.671 |
| August | 30.033 |
| September | 28.750 |
| October | 25.087 |
| November | 19.629 |
| December | 14.516 |
| Annual Sum or Average | 24.876 |
| Minimum of Months | 13.392 |
| Maximum of Months | 33.595 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
| January | 13.392 |
| February | 16.974 |
| March | 22.368 |
| April | 29.134 |
| May | 32.978 |
| June | 33.595 |
| July | 31.671 |
| August | 30.033 |
| September | 28.750 |
| October | 25.087 |
| November | 19.629 |
| December | 14.516 |
| Annual Sum or Average | 24.876 |
| Minimum of Months | 13.392 |
| Maximum of Months | 33.595 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 1B
For: Environment
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
| January | 13.392 |
| February | 16.974 |
| March | 22.368 |
| April | 29.134 |
| May | 32.978 |
| June | 33.595 |
| July | 31.671 |
| August | 30.033 |
| September | 28.750 |
| October | 25.087 |
| November | 19.629 |
| December | 14.516 |
| Annual Sum or Average | 24.876 |
| Minimum of Months | 13.392 |
| Maximum of Months | 33.595 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY IND_DELHI_NEWDELHI
For: Environment
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
| January | 13.392 |
| February | 16.974 |
| March | 22.368 |
| April | 29.134 |
| May | 32.978 |
| June | 33.595 |
| July | 31.671 |
| August | 30.033 |
| September | 28.750 |
| October | 25.087 |
| November | 19.629 |
| December | 14.516 |
| Annual Sum or Average | 24.876 |
| Minimum of Months | 13.392 |
| Maximum of Months | 33.595 |
Report: ZoneCoolingSummaryMonthly
For: G SW APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.114143E+10 | 1189.73 | 12-JAN-15:20 | 23.50 | 14.30 | 0.116727E+09 | 70.36 | 30-JAN-21:40 | 10.83 | 8.69 |
| February | 0.130932E+10 | 1630.29 | 20-FEB-16:10 | 25.43 | 14.23 | 0.109843E+09 | 70.38 | 01-FEB-20:49 | 25.43 | 14.23 |
| March | 0.209328E+10 | 1961.18 | 29-MAR-16:03 | 32.78 | 18.63 | 0.123583E+09 | 70.36 | 01-MAR-02:09 | 32.78 | 18.63 |
| April | 0.310218E+10 | 2457.90 | 27-APR-16:09 | 39.70 | 18.93 | 0.123964E+09 | 70.32 | 06-APR-02:20 | 39.70 | 18.93 |
| May | 0.389293E+10 | 2731.97 | 05-MAY-16:40 | 42.70 | 20.38 | 0.125734E+09 | 70.30 | 13-MAY-01:30 | 23.40 | 19.68 |
| June | 0.400716E+10 | 2790.70 | 06-JUN-16:01 | 44.00 | 21.68 | 0.120422E+09 | 70.29 | 18-JUN-05:30 | 23.55 | 21.85 |
| July | 0.423962E+10 | 2634.73 | 02-JUL-17:03 | 40.18 | 26.57 | 0.129276E+09 | 70.28 | 19-JUL-03:20 | 23.63 | 23.63 |
| August | 0.415775E+10 | 2485.47 | 06-AUG-16:40 | 36.10 | 26.38 | 0.123963E+09 | 70.29 | 16-AUG-00:20 | 23.53 | 23.04 |
| September | 0.396999E+10 | 2634.48 | 24-SEP-16:04 | 34.68 | 25.31 | 0.123963E+09 | 70.29 | 27-SEP-04:40 | 23.30 | 20.89 |
| October | 0.378552E+10 | 2626.57 | 01-OCT-16:03 | 35.32 | 20.17 | 0.127505E+09 | 70.30 | 24-OCT-19:00 | 23.10 | 16.11 |
| November | 0.275162E+10 | 2192.52 | 04-NOV-15:20 | 29.93 | 17.59 | 0.123962E+09 | 70.37 | 26-NOV-06:40 | 11.13 | 8.80 |
| December | 0.162995E+10 | 1631.07 | 02-DEC-15:10 | 23.70 | 13.26 | 0.125589E+09 | 70.37 | 22-DEC-21:10 | 10.33 | 8.37 |
| Annual Sum or Average | 0.360808E+11 | 0.147453E+10 | ||||||||
| Minimum of Months | 0.114143E+10 | 1189.73 | 23.50 | 13.26 | 0.109843E+09 | 70.28 | 10.33 | 8.37 | ||
| Maximum of Months | 0.423962E+10 | 2790.70 | 44.00 | 26.57 | 0.129276E+09 | 70.38 | 39.70 | 23.63 |
Report: ZoneCoolingSummaryMonthly
For: G NW APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.682302E+09 | 489.44 | 21-JAN-06:10 | 5.50 | 5.15 | 0.100756E+09 | 69.52 | 14-JAN-22:49 | 5.50 | 5.15 |
| February | 0.727348E+09 | 938.28 | 22-FEB-17:10 | 25.53 | 15.68 | 0.104222E+09 | 70.36 | 24-FEB-01:49 | 15.95 | 12.88 |
| March | 0.149161E+10 | 1630.17 | 29-MAR-16:40 | 32.43 | 18.52 | 0.127573E+09 | 70.38 | 04-MAR-00:00 | 32.43 | 18.52 |
| April | 0.271767E+10 | 2265.66 | 27-APR-16:30 | 39.50 | 18.94 | 0.124621E+09 | 70.32 | 06-APR-02:20 | 39.50 | 18.94 |
| May | 0.382258E+10 | 2693.83 | 05-MAY-17:04 | 42.27 | 20.34 | 0.128775E+09 | 70.30 | 13-MAY-01:30 | 23.40 | 19.68 |
| June | 0.403474E+10 | 2808.03 | 06-JUN-16:40 | 43.70 | 21.71 | 0.124621E+09 | 70.29 | 18-JUN-05:30 | 23.55 | 21.85 |
| July | 0.424715E+10 | 2634.39 | 02-JUL-17:15 | 40.07 | 26.58 | 0.128775E+09 | 70.28 | 19-JUL-03:20 | 23.63 | 23.63 |
| August | 0.409385E+10 | 2442.09 | 07-AUG-17:04 | 36.48 | 26.95 | 0.128775E+09 | 70.29 | 16-AUG-00:20 | 23.53 | 23.04 |
| September | 0.364226E+10 | 2212.37 | 22-SEP-16:03 | 34.38 | 24.77 | 0.124621E+09 | 70.29 | 27-SEP-04:40 | 23.30 | 20.89 |
| October | 0.294783E+10 | 2082.11 | 01-OCT-16:17 | 35.13 | 20.18 | 0.128775E+09 | 70.30 | 18-OCT-21:49 | 23.40 | 19.13 |
| November | 0.167902E+10 | 1381.28 | 04-NOV-16:10 | 29.18 | 17.67 | 0.124188E+09 | 70.36 | 22-NOV-01:00 | 12.30 | 11.66 |
| December | 0.878706E+09 | 804.22 | 01-DEC-16:10 | 22.12 | 13.82 | 0.117245E+09 | 70.37 | 26-DEC-21:10 | 14.18 | 11.96 |
| Annual Sum or Average | 0.309651E+11 | 0.146295E+10 | ||||||||
| Minimum of Months | 0.682302E+09 | 489.44 | 5.50 | 5.15 | 0.100756E+09 | 69.52 | 5.50 | 5.15 | ||
| Maximum of Months | 0.424715E+10 | 2808.03 | 43.70 | 26.95 | 0.128775E+09 | 70.38 | 39.50 | 23.63 |
Report: ZoneCoolingSummaryMonthly
For: OFFICE
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.842965E+09 | 6154.63 | 26-JAN-09:02 | 15.47 | 12.49 | 67692503.76 | 166.81 | 26-JAN-09:09 | 15.47 | 12.49 |
| February | 0.950034E+09 | 6732.14 | 21-FEB-09:02 | 16.45 | 12.54 | 65813542.50 | 179.71 | 23-FEB-08:09 | 16.57 | 14.43 |
| March | 0.157022E+10 | 6774.91 | 14-MAR-07:02 | 20.97 | 15.53 | 80882135.32 | 217.47 | 13-MAR-07:10 | 20.97 | 15.53 |
| April | 0.203713E+10 | 7143.23 | 10-APR-07:02 | 19.87 | 14.05 | 70689088.17 | 217.85 | 04-APR-07:10 | 19.87 | 14.05 |
| May | 0.267337E+10 | 6629.07 | 05-MAY-07:02 | 31.33 | 17.31 | 77772595.10 | 217.48 | 04-MAY-07:10 | 31.33 | 17.31 |
| June | 0.270568E+10 | 6600.10 | 12-JUN-06:02 | 34.87 | 19.39 | 77779862.11 | 217.51 | 06-JUN-07:10 | 34.87 | 19.39 |
| July | 0.260393E+10 | 5094.89 | 05-JUL-07:02 | 33.75 | 24.52 | 70726267.84 | 217.47 | 17-JUL-07:10 | 30.72 | 26.85 |
| August | 0.284479E+10 | 5096.84 | 07-AUG-08:62 | 31.17 | 24.55 | 81328128.15 | 217.47 | 17-AUG-07:10 | 27.82 | 25.52 |
| September | 0.253230E+10 | 5617.88 | 26-SEP-08:62 | 26.97 | 20.03 | 70711798.36 | 217.47 | 01-SEP-07:10 | 26.97 | 20.03 |
| October | 0.252241E+10 | 7232.50 | 24-OCT-07:02 | 19.53 | 14.18 | 74222218.46 | 217.48 | 16-OCT-07:10 | 19.53 | 14.18 |
| November | 0.183447E+10 | 7291.91 | 20-NOV-08:62 | 15.48 | 12.44 | 70427126.54 | 217.21 | 06-NOV-08:09 | 15.48 | 12.44 |
| December | 0.119496E+10 | 6747.57 | 01-DEC-09:02 | 16.72 | 10.87 | 69623245.63 | 170.52 | 01-DEC-08:09 | 16.72 | 10.87 |
| Annual Sum or Average | 0.243123E+11 | 0.877669E+09 | ||||||||
| Minimum of Months | 0.842965E+09 | 5094.89 | 15.47 | 10.87 | 65813542.50 | 166.81 | 15.47 | 10.87 | ||
| Maximum of Months | 0.284479E+10 | 7291.91 | 34.87 | 24.55 | 81328128.15 | 217.85 | 34.87 | 26.85 |
Report: ZoneCoolingSummaryMonthly
For: G NE APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.683685E+09 | 488.51 | 21-JAN-06:10 | 5.50 | 5.15 | 0.100645E+09 | 69.31 | 14-JAN-22:49 | 5.50 | 5.15 |
| February | 0.737218E+09 | 857.91 | 24-FEB-17:10 | 25.33 | 17.24 | 0.104660E+09 | 70.36 | 20-FEB-01:10 | 25.33 | 17.24 |
| March | 0.150726E+10 | 1386.87 | 29-MAR-16:30 | 32.55 | 18.55 | 0.127611E+09 | 70.36 | 20-MAR-00:40 | 32.55 | 18.55 |
| April | 0.273372E+10 | 1954.73 | 15-APR-16:01 | 39.58 | 21.03 | 0.124621E+09 | 70.32 | 06-APR-02:20 | 39.58 | 21.03 |
| May | 0.384682E+10 | 2401.69 | 05-MAY-17:04 | 42.27 | 20.34 | 0.128775E+09 | 70.30 | 13-MAY-01:30 | 23.40 | 19.68 |
| June | 0.398925E+10 | 2511.17 | 06-JUN-16:01 | 44.00 | 21.68 | 0.124621E+09 | 70.29 | 18-JUN-05:30 | 23.55 | 21.85 |
| July | 0.425289E+10 | 2377.12 | 04-JUL-17:15 | 40.00 | 24.23 | 0.128775E+09 | 70.28 | 19-JUL-03:20 | 23.63 | 23.63 |
| August | 0.409874E+10 | 2278.67 | 07-AUG-17:04 | 36.48 | 26.95 | 0.128775E+09 | 70.29 | 16-AUG-00:20 | 23.53 | 23.04 |
| September | 0.363014E+10 | 2015.18 | 22-SEP-16:03 | 34.38 | 24.77 | 0.124621E+09 | 70.29 | 27-SEP-04:40 | 23.30 | 20.89 |
| October | 0.296610E+10 | 1896.81 | 03-OCT-15:10 | 35.22 | 22.44 | 0.128775E+09 | 70.30 | 18-OCT-21:49 | 23.40 | 19.13 |
| November | 0.168260E+10 | 1203.04 | 01-NOV-16:02 | 27.60 | 15.88 | 0.124202E+09 | 70.37 | 25-NOV-23:40 | 12.47 | 9.86 |
| December | 0.872924E+09 | 675.75 | 01-DEC-15:10 | 23.22 | 13.42 | 0.117432E+09 | 70.37 | 03-DEC-21:40 | 11.70 | 10.19 |
| Annual Sum or Average | 0.310013E+11 | 0.146351E+10 | ||||||||
| Minimum of Months | 0.683685E+09 | 488.51 | 5.50 | 5.15 | 0.100645E+09 | 69.31 | 5.50 | 5.15 | ||
| Maximum of Months | 0.425289E+10 | 2511.17 | 44.00 | 26.95 | 0.128775E+09 | 70.37 | 39.58 | 23.63 |
Report: ZoneCoolingSummaryMonthly
For: G N1 APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.740376E+09 | 507.80 | 21-JAN-06:10 | 5.50 | 5.15 | 0.106390E+09 | 70.38 | 19-JAN-21:10 | 5.50 | 5.15 |
| February | 0.759401E+09 | 772.59 | 24-FEB-17:05 | 25.33 | 17.24 | 0.108735E+09 | 70.38 | 19-FEB-00:10 | 25.33 | 17.24 |
| March | 0.141060E+10 | 1138.08 | 29-MAR-17:07 | 32.00 | 18.46 | 0.128422E+09 | 70.37 | 21-MAR-01:30 | 32.00 | 18.46 |
| April | 0.226376E+10 | 1524.91 | 27-APR-17:05 | 39.00 | 18.90 | 0.124621E+09 | 70.32 | 06-APR-02:20 | 39.00 | 18.90 |
| May | 0.307993E+10 | 1839.59 | 05-MAY-17:14 | 42.03 | 20.28 | 0.128775E+09 | 70.30 | 13-MAY-01:30 | 23.40 | 19.68 |
| June | 0.323052E+10 | 1930.04 | 07-JUN-17:14 | 43.60 | 21.92 | 0.124621E+09 | 70.29 | 18-JUN-05:30 | 23.55 | 21.85 |
| July | 0.345223E+10 | 1868.54 | 04-JUL-17:30 | 40.05 | 24.21 | 0.128775E+09 | 70.28 | 19-JUL-03:20 | 23.63 | 23.63 |
| August | 0.334726E+10 | 1776.17 | 07-AUG-17:15 | 36.37 | 26.97 | 0.128775E+09 | 70.29 | 16-AUG-00:20 | 23.53 | 23.04 |
| September | 0.298389E+10 | 1564.25 | 22-SEP-16:03 | 34.38 | 24.77 | 0.124621E+09 | 70.29 | 27-SEP-04:40 | 23.30 | 20.89 |
| October | 0.248196E+10 | 1466.33 | 03-OCT-16:03 | 34.05 | 22.34 | 0.128775E+09 | 70.30 | 18-OCT-21:49 | 23.40 | 19.13 |
| November | 0.154718E+10 | 1014.69 | 01-NOV-16:13 | 27.40 | 15.88 | 0.124504E+09 | 70.37 | 26-NOV-00:00 | 12.00 | 9.96 |
| December | 0.910743E+09 | 623.94 | 01-DEC-17:04 | 20.88 | 14.25 | 0.121944E+09 | 70.38 | 25-DEC-21:40 | 14.03 | 11.23 |
| Annual Sum or Average | 0.262078E+11 | 0.147896E+10 | ||||||||
| Minimum of Months | 0.740376E+09 | 507.80 | 5.50 | 5.15 | 0.106390E+09 | 70.28 | 5.50 | 5.15 | ||
| Maximum of Months | 0.345223E+10 | 1930.04 | 43.60 | 26.97 | 0.128775E+09 | 70.38 | 39.00 | 23.63 |
Report: ZoneCoolingSummaryMonthly
For: G N2 APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.740748E+09 | 507.74 | 21-JAN-06:10 | 5.50 | 5.15 | 0.106427E+09 | 70.37 | 19-JAN-21:10 | 5.50 | 5.15 |
| February | 0.762750E+09 | 774.67 | 24-FEB-17:05 | 25.33 | 17.24 | 0.108798E+09 | 70.38 | 20-FEB-01:39 | 25.33 | 17.24 |
| March | 0.141256E+10 | 1134.27 | 29-MAR-17:07 | 32.00 | 18.46 | 0.128424E+09 | 70.37 | 21-MAR-01:30 | 32.00 | 18.46 |
| April | 0.226488E+10 | 1519.52 | 27-APR-17:05 | 39.00 | 18.90 | 0.124621E+09 | 70.32 | 06-APR-02:20 | 39.00 | 18.90 |
| May | 0.308103E+10 | 1835.81 | 05-MAY-17:14 | 42.03 | 20.28 | 0.128775E+09 | 70.30 | 13-MAY-01:30 | 23.40 | 19.68 |
| June | 0.322894E+10 | 1925.33 | 07-JUN-17:14 | 43.60 | 21.92 | 0.124621E+09 | 70.29 | 18-JUN-05:30 | 23.55 | 21.85 |
| July | 0.345247E+10 | 1864.91 | 04-JUL-17:25 | 40.05 | 24.21 | 0.128775E+09 | 70.28 | 19-JUL-03:20 | 23.63 | 23.63 |
| August | 0.334754E+10 | 1773.79 | 07-AUG-17:15 | 36.37 | 26.97 | 0.128775E+09 | 70.29 | 16-AUG-00:20 | 23.53 | 23.04 |
| September | 0.298350E+10 | 1561.58 | 22-SEP-16:04 | 34.38 | 24.77 | 0.124621E+09 | 70.29 | 27-SEP-04:40 | 23.30 | 20.89 |
| October | 0.248298E+10 | 1464.46 | 03-OCT-16:03 | 34.05 | 22.34 | 0.128775E+09 | 70.30 | 18-OCT-21:49 | 23.40 | 19.13 |
| November | 0.154802E+10 | 1011.96 | 01-NOV-16:13 | 27.40 | 15.88 | 0.124504E+09 | 70.36 | 22-NOV-05:49 | 11.75 | 10.68 |
| December | 0.912400E+09 | 622.10 | 01-DEC-17:04 | 20.88 | 14.25 | 0.121976E+09 | 70.37 | 25-DEC-21:19 | 14.47 | 11.41 |
| Annual Sum or Average | 0.262178E+11 | 0.147909E+10 | ||||||||
| Minimum of Months | 0.740748E+09 | 507.74 | 5.50 | 5.15 | 0.106427E+09 | 70.28 | 5.50 | 5.15 | ||
| Maximum of Months | 0.345247E+10 | 1925.33 | 43.60 | 26.97 | 0.128775E+09 | 70.38 | 39.00 | 23.63 |
Report: ZoneCoolingSummaryMonthly
For: G S1 APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.130841E+10 | 1135.77 | 12-JAN-14:30 | 23.45 | 14.09 | 0.122750E+09 | 70.38 | 06-JAN-21:49 | 23.45 | 14.09 |
| February | 0.143736E+10 | 1392.91 | 20-FEB-14:40 | 26.33 | 13.84 | 0.113188E+09 | 70.37 | 06-FEB-01:10 | 26.33 | 13.84 |
| March | 0.205670E+10 | 1570.24 | 12-MAR-16:05 | 31.18 | 19.88 | 0.123909E+09 | 70.36 | 26-MAR-06:40 | 17.57 | 12.50 |
| April | 0.266837E+10 | 1747.47 | 15-APR-16:01 | 39.58 | 21.03 | 0.123964E+09 | 70.32 | 06-APR-02:20 | 39.58 | 21.03 |
| May | 0.316569E+10 | 1873.05 | 05-MAY-17:14 | 42.03 | 20.28 | 0.125734E+09 | 70.30 | 13-MAY-01:30 | 23.40 | 19.68 |
| June | 0.321586E+10 | 1885.03 | 06-JUN-16:01 | 44.00 | 21.68 | 0.120422E+09 | 70.29 | 18-JUN-05:30 | 23.55 | 21.85 |
| July | 0.345881E+10 | 1858.06 | 04-JUL-17:15 | 40.00 | 24.23 | 0.129276E+09 | 70.28 | 19-JUL-03:20 | 23.63 | 23.63 |
| August | 0.342565E+10 | 1816.18 | 07-AUG-17:15 | 36.37 | 26.97 | 0.123963E+09 | 70.29 | 16-AUG-00:20 | 23.53 | 23.04 |
| September | 0.332917E+10 | 1983.19 | 24-SEP-16:04 | 34.68 | 25.31 | 0.123963E+09 | 70.29 | 27-SEP-04:40 | 23.30 | 20.89 |
| October | 0.334827E+10 | 1986.50 | 01-OCT-15:10 | 35.92 | 19.96 | 0.127505E+09 | 70.31 | 24-OCT-19:00 | 23.10 | 16.11 |
| November | 0.266618E+10 | 1805.86 | 04-NOV-14:10 | 30.28 | 17.23 | 0.123963E+09 | 70.31 | 23-NOV-16:40 | 23.33 | 14.35 |
| December | 0.179194E+10 | 1494.78 | 02-DEC-14:00 | 24.10 | 13.15 | 0.128286E+09 | 70.37 | 07-DEC-04:30 | 11.15 | 8.46 |
| Annual Sum or Average | 0.318724E+11 | 0.148692E+10 | ||||||||
| Minimum of Months | 0.130841E+10 | 1135.77 | 23.45 | 13.15 | 0.113188E+09 | 70.28 | 11.15 | 8.46 | ||
| Maximum of Months | 0.345881E+10 | 1986.50 | 44.00 | 26.97 | 0.129276E+09 | 70.38 | 39.58 | 23.63 |
Report: ZoneCoolingSummaryMonthly
For: G S2 APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.136256E+10 | 1178.68 | 12-JAN-14:30 | 23.45 | 14.09 | 0.123180E+09 | 70.38 | 10-JAN-22:00 | 23.45 | 14.09 |
| February | 0.153379E+10 | 1484.74 | 20-FEB-14:50 | 26.32 | 13.93 | 0.113560E+09 | 70.38 | 18-FEB-04:30 | 26.32 | 13.93 |
| March | 0.223955E+10 | 1705.63 | 12-MAR-16:05 | 31.18 | 19.88 | 0.123940E+09 | 70.31 | 17-MAR-06:00 | 16.00 | 12.10 |
| April | 0.295071E+10 | 1881.76 | 15-APR-16:01 | 39.58 | 21.03 | 0.123964E+09 | 70.31 | 06-APR-02:20 | 39.58 | 21.03 |
| May | 0.349201E+10 | 1961.13 | 05-MAY-17:20 | 42.03 | 20.28 | 0.125734E+09 | 70.30 | 13-MAY-01:30 | 23.40 | 19.68 |
| June | 0.352932E+10 | 1986.72 | 11-JUN-17:14 | 42.67 | 23.12 | 0.120422E+09 | 70.29 | 18-JUN-05:30 | 23.55 | 21.85 |
| July | 0.380235E+10 | 2021.24 | 02-JUL-17:20 | 40.07 | 26.58 | 0.129276E+09 | 70.28 | 19-JUL-03:20 | 23.63 | 23.63 |
| August | 0.375531E+10 | 1969.71 | 06-AUG-17:04 | 35.87 | 26.48 | 0.123963E+09 | 70.29 | 16-AUG-00:20 | 23.53 | 23.04 |
| September | 0.365162E+10 | 2152.95 | 24-SEP-16:04 | 34.68 | 25.31 | 0.123963E+09 | 70.29 | 27-SEP-04:40 | 23.30 | 20.89 |
| October | 0.366027E+10 | 2159.43 | 01-OCT-15:10 | 35.92 | 19.96 | 0.127505E+09 | 70.30 | 24-OCT-19:00 | 23.10 | 16.11 |
| November | 0.288372E+10 | 1922.12 | 13-NOV-14:00 | 28.20 | 15.96 | 0.123963E+09 | 70.31 | 23-NOV-16:40 | 23.33 | 14.35 |
| December | 0.189436E+10 | 1567.33 | 02-DEC-14:00 | 24.10 | 13.15 | 0.128512E+09 | 70.38 | 13-DEC-04:40 | 10.93 | 8.84 |
| Annual Sum or Average | 0.347556E+11 | 0.148798E+10 | ||||||||
| Minimum of Months | 0.136256E+10 | 1178.68 | 23.45 | 13.15 | 0.113560E+09 | 70.28 | 10.93 | 8.84 | ||
| Maximum of Months | 0.380235E+10 | 2159.43 | 42.67 | 26.58 | 0.129276E+09 | 70.38 | 39.58 | 23.63 |
Report: ZoneCoolingSummaryMonthly
For: M SW APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.133200E+10 | 1523.67 | 12-JAN-15:20 | 23.50 | 14.30 | 0.118633E+09 | 70.32 | 27-JAN-00:20 | 13.70 | 11.68 |
| February | 0.170088E+10 | 2114.12 | 20-FEB-16:10 | 25.43 | 14.23 | 0.111502E+09 | 70.32 | 07-FEB-01:00 | 25.43 | 14.23 |
| March | 0.281668E+10 | 2481.99 | 12-MAR-16:08 | 31.18 | 19.88 | 0.123895E+09 | 70.31 | 03-MAR-04:49 | 31.18 | 19.88 |
| April | 0.383874E+10 | 3059.27 | 27-APR-16:03 | 39.70 | 18.93 | 0.123964E+09 | 70.31 | 06-APR-02:20 | 39.70 | 18.93 |
| May | 0.440410E+10 | 3201.23 | 05-MAY-16:03 | 43.00 | 20.35 | 0.125734E+09 | 70.29 | 13-MAY-01:30 | 23.40 | 19.68 |
| June | 0.416856E+10 | 3120.00 | 06-JUN-16:08 | 44.00 | 21.68 | 0.120422E+09 | 70.29 | 18-JUN-05:30 | 23.55 | 21.85 |
| July | 0.404144E+10 | 2728.95 | 02-JUL-16:40 | 40.33 | 26.50 | 0.129276E+09 | 70.28 | 19-JUL-03:20 | 23.63 | 23.63 |
| August | 0.372116E+10 | 2467.85 | 06-AUG-16:20 | 36.20 | 26.31 | 0.123963E+09 | 70.29 | 16-AUG-00:20 | 23.53 | 23.04 |
| September | 0.351368E+10 | 2655.24 | 24-SEP-15:30 | 34.95 | 25.05 | 0.123963E+09 | 70.29 | 27-SEP-04:40 | 23.30 | 20.89 |
| October | 0.345578E+10 | 2704.87 | 03-OCT-15:10 | 35.22 | 22.44 | 0.127504E+09 | 70.30 | 24-OCT-19:00 | 23.10 | 16.11 |
| November | 0.260574E+10 | 2395.85 | 04-NOV-15:20 | 29.93 | 17.59 | 0.123680E+09 | 70.31 | 21-NOV-04:19 | 13.57 | 10.97 |
| December | 0.162255E+10 | 1801.04 | 02-DEC-14:30 | 24.00 | 13.17 | 0.122918E+09 | 70.32 | 01-DEC-01:10 | 24.00 | 13.17 |
| Annual Sum or Average | 0.372213E+11 | 0.147545E+10 | ||||||||
| Minimum of Months | 0.133200E+10 | 1523.67 | 23.50 | 13.17 | 0.111502E+09 | 70.28 | 13.57 | 10.97 | ||
| Maximum of Months | 0.440410E+10 | 3201.23 | 44.00 | 26.50 | 0.129276E+09 | 70.32 | 39.70 | 23.63 |
Report: ZoneCoolingSummaryMonthly
For: M NW APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.730901E+09 | 565.26 | 14-JAN-17:10 | 20.55 | 14.69 | 0.104731E+09 | 70.32 | 14-JAN-21:10 | 17.67 | 13.83 |
| February | 0.988715E+09 | 1286.69 | 22-FEB-17:10 | 25.53 | 15.68 | 0.109156E+09 | 70.32 | 12-FEB-21:00 | 25.53 | 15.68 |
| March | 0.215078E+10 | 2102.07 | 29-MAR-16:30 | 32.55 | 18.55 | 0.128503E+09 | 70.31 | 03-MAR-03:09 | 32.55 | 18.55 |
| April | 0.342286E+10 | 2840.37 | 27-APR-16:17 | 39.60 | 18.94 | 0.124621E+09 | 70.31 | 06-APR-02:20 | 39.60 | 18.94 |
| May | 0.432100E+10 | 3132.12 | 05-MAY-16:30 | 42.80 | 20.37 | 0.128775E+09 | 70.29 | 13-MAY-01:30 | 23.40 | 19.68 |
| June | 0.418490E+10 | 3131.19 | 06-JUN-16:04 | 44.00 | 21.68 | 0.124621E+09 | 70.29 | 18-JUN-05:30 | 23.55 | 21.85 |
| July | 0.403482E+10 | 2696.91 | 02-JUL-16:50 | 40.32 | 26.53 | 0.128775E+09 | 70.28 | 19-JUL-03:20 | 23.63 | 23.63 |
| August | 0.364045E+10 | 2390.61 | 07-AUG-16:17 | 36.93 | 26.75 | 0.128775E+09 | 70.29 | 16-AUG-00:20 | 23.53 | 23.04 |
| September | 0.315653E+10 | 2180.36 | 22-SEP-16:09 | 34.38 | 24.77 | 0.124621E+09 | 70.29 | 27-SEP-04:40 | 23.30 | 20.89 |
| October | 0.256497E+10 | 2072.30 | 03-OCT-15:20 | 35.03 | 22.43 | 0.128750E+09 | 70.30 | 18-OCT-21:49 | 23.40 | 19.13 |
| November | 0.148351E+10 | 1405.32 | 04-NOV-16:10 | 29.18 | 17.67 | 0.123245E+09 | 70.31 | 07-NOV-05:00 | 14.40 | 13.42 |
| December | 0.831808E+09 | 771.31 | 01-DEC-16:10 | 22.12 | 13.82 | 0.113939E+09 | 70.30 | 04-DEC-21:10 | 12.82 | 11.25 |
| Annual Sum or Average | 0.315113E+11 | 0.146851E+10 | ||||||||
| Minimum of Months | 0.730901E+09 | 565.26 | 20.55 | 13.82 | 0.104731E+09 | 70.28 | 12.82 | 11.25 | ||
| Maximum of Months | 0.432100E+10 | 3132.12 | 44.00 | 26.75 | 0.128775E+09 | 70.32 | 39.60 | 23.63 |
Report: ZoneCoolingSummaryMonthly
For: M SE APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.133647E+10 | 1424.74 | 12-JAN-14:30 | 23.45 | 14.09 | 0.118769E+09 | 70.31 | 18-JAN-18:40 | 15.87 | 13.81 |
| February | 0.173545E+10 | 1923.22 | 20-FEB-14:30 | 26.35 | 13.75 | 0.111604E+09 | 70.31 | 03-FEB-23:19 | 26.35 | 13.75 |
| March | 0.284150E+10 | 2206.88 | 12-MAR-16:10 | 31.18 | 19.88 | 0.123895E+09 | 70.32 | 02-MAR-04:19 | 31.18 | 19.88 |
| April | 0.385736E+10 | 2816.07 | 15-APR-15:10 | 40.22 | 20.73 | 0.123964E+09 | 70.31 | 06-APR-02:20 | 40.22 | 20.73 |
| May | 0.443082E+10 | 2822.92 | 05-MAY-15:10 | 43.27 | 20.42 | 0.125734E+09 | 70.29 | 13-MAY-01:30 | 23.40 | 19.68 |
| June | 0.411935E+10 | 2803.30 | 06-JUN-15:10 | 44.18 | 21.72 | 0.120422E+09 | 70.29 | 18-JUN-05:30 | 23.55 | 21.85 |
| July | 0.404756E+10 | 2359.36 | 02-JUL-16:30 | 40.35 | 26.46 | 0.129276E+09 | 70.28 | 19-JUL-03:20 | 23.63 | 23.63 |
| August | 0.372625E+10 | 2247.81 | 07-AUG-16:01 | 37.02 | 26.70 | 0.123963E+09 | 70.29 | 16-AUG-00:20 | 23.53 | 23.04 |
| September | 0.350138E+10 | 2434.37 | 28-SEP-14:10 | 35.50 | 22.76 | 0.123963E+09 | 70.29 | 27-SEP-04:40 | 35.50 | 22.76 |
| October | 0.347652E+10 | 2542.74 | 03-OCT-14:10 | 35.73 | 22.27 | 0.127504E+09 | 70.30 | 24-OCT-19:00 | 23.10 | 16.11 |
| November | 0.261261E+10 | 2197.01 | 04-NOV-13:40 | 30.23 | 17.20 | 0.123669E+09 | 70.31 | 23-NOV-16:40 | 23.33 | 14.35 |
| December | 0.163138E+10 | 1687.31 | 02-DEC-14:00 | 24.10 | 13.15 | 0.122966E+09 | 70.31 | 19-DEC-21:00 | 11.10 | 7.98 |
| Annual Sum or Average | 0.373167E+11 | 0.147573E+10 | ||||||||
| Minimum of Months | 0.133647E+10 | 1424.74 | 23.45 | 13.15 | 0.111604E+09 | 70.28 | 11.10 | 7.98 | ||
| Maximum of Months | 0.443082E+10 | 2822.92 | 44.18 | 26.70 | 0.129276E+09 | 70.32 | 40.22 | 23.63 |
Report: ZoneCoolingSummaryMonthly
For: M NE APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.729744E+09 | 492.20 | 21-JAN-06:10 | 5.50 | 5.15 | 0.104662E+09 | 70.29 | 14-JAN-23:49 | 5.50 | 5.15 |
| February | 0.100546E+10 | 1100.82 | 22-FEB-17:05 | 25.53 | 15.68 | 0.109494E+09 | 70.32 | 05-FEB-21:40 | 25.53 | 15.68 |
| March | 0.217337E+10 | 1776.90 | 29-MAR-16:13 | 32.67 | 18.59 | 0.128532E+09 | 70.30 | 31-MAR-23:40 | 23.57 | 16.59 |
| April | 0.344126E+10 | 2451.34 | 15-APR-15:10 | 40.22 | 20.73 | 0.124621E+09 | 70.31 | 06-APR-02:20 | 40.22 | 20.73 |
| May | 0.434780E+10 | 2743.53 | 05-MAY-16:09 | 43.00 | 20.35 | 0.128775E+09 | 70.29 | 13-MAY-01:30 | 23.40 | 19.68 |
| June | 0.413572E+10 | 2768.48 | 06-JUN-15:10 | 44.18 | 21.72 | 0.124621E+09 | 70.29 | 18-JUN-05:30 | 23.55 | 21.85 |
| July | 0.404096E+10 | 2395.11 | 07-JUL-10:10 | 37.08 | 24.60 | 0.128775E+09 | 70.28 | 19-JUL-03:20 | 23.63 | 23.63 |
| August | 0.364553E+10 | 2182.13 | 07-AUG-16:17 | 36.93 | 26.75 | 0.128775E+09 | 70.29 | 16-AUG-00:20 | 23.53 | 23.04 |
| September | 0.314421E+10 | 1925.22 | 22-SEP-16:03 | 34.38 | 24.77 | 0.124621E+09 | 70.29 | 27-SEP-04:40 | 23.30 | 20.89 |
| October | 0.258496E+10 | 1864.03 | 03-OCT-15:10 | 35.22 | 22.44 | 0.128748E+09 | 70.30 | 18-OCT-21:49 | 23.40 | 19.13 |
| November | 0.148472E+10 | 1155.31 | 04-NOV-16:10 | 29.18 | 17.67 | 0.123281E+09 | 70.32 | 29-NOV-02:20 | 15.93 | 13.03 |
| December | 0.824525E+09 | 610.28 | 01-DEC-15:10 | 23.22 | 13.42 | 0.114101E+09 | 70.30 | 16-DEC-22:30 | 13.20 | 12.06 |
| Annual Sum or Average | 0.315583E+11 | 0.146901E+10 | ||||||||
| Minimum of Months | 0.729744E+09 | 492.20 | 5.50 | 5.15 | 0.104662E+09 | 70.28 | 5.50 | 5.15 | ||
| Maximum of Months | 0.434780E+10 | 2768.48 | 44.18 | 26.75 | 0.128775E+09 | 70.32 | 40.22 | 23.63 |
Report: ZoneCoolingSummaryMonthly
For: M N1 APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.809578E+09 | 552.70 | 27-JAN-18:20 | 15.37 | 11.88 | 0.112735E+09 | 70.32 | 27-JAN-21:49 | 11.42 | 9.46 |
| February | 0.101210E+10 | 944.69 | 24-FEB-17:05 | 25.33 | 17.24 | 0.112899E+09 | 70.31 | 27-FEB-02:20 | 12.77 | 12.05 |
| March | 0.187903E+10 | 1370.79 | 29-MAR-16:30 | 32.55 | 18.55 | 0.128737E+09 | 70.31 | 03-MAR-06:10 | 32.55 | 18.55 |
| April | 0.267012E+10 | 1770.02 | 27-APR-16:20 | 39.60 | 18.94 | 0.124621E+09 | 70.31 | 06-APR-02:20 | 39.60 | 18.94 |
| May | 0.330583E+10 | 1973.03 | 05-MAY-17:04 | 42.27 | 20.34 | 0.128775E+09 | 70.29 | 13-MAY-01:30 | 23.40 | 19.68 |
| June | 0.322705E+10 | 1980.94 | 06-JUN-16:08 | 44.00 | 21.68 | 0.124621E+09 | 70.29 | 18-JUN-05:30 | 23.55 | 21.85 |
| July | 0.322985E+10 | 1793.25 | 02-JUL-17:25 | 39.95 | 26.58 | 0.128775E+09 | 70.28 | 19-JUL-03:20 | 23.63 | 23.63 |
| August | 0.298214E+10 | 1651.95 | 07-AUG-17:17 | 36.37 | 26.97 | 0.128775E+09 | 70.29 | 16-AUG-00:20 | 23.53 | 23.04 |
| September | 0.260747E+10 | 1475.28 | 22-SEP-16:10 | 34.38 | 24.77 | 0.124621E+09 | 70.29 | 27-SEP-04:40 | 23.30 | 20.89 |
| October | 0.219602E+10 | 1399.64 | 03-OCT-16:03 | 34.05 | 22.34 | 0.128772E+09 | 70.30 | 18-OCT-21:49 | 23.40 | 19.13 |
| November | 0.142638E+10 | 980.28 | 04-NOV-16:20 | 28.97 | 17.69 | 0.124269E+09 | 70.32 | 21-NOV-03:00 | 13.60 | 11.24 |
| December | 0.906939E+09 | 630.65 | 28-DEC-17:05 | 22.60 | 14.86 | 0.120976E+09 | 70.32 | 27-DEC-23:00 | 22.60 | 14.86 |
| Annual Sum or Average | 0.262525E+11 | 0.148858E+10 | ||||||||
| Minimum of Months | 0.809578E+09 | 552.70 | 15.37 | 11.88 | 0.112735E+09 | 70.28 | 11.42 | 9.46 | ||
| Maximum of Months | 0.330583E+10 | 1980.94 | 44.00 | 26.97 | 0.128775E+09 | 70.32 | 39.60 | 23.63 |
Report: ZoneCoolingSummaryMonthly
For: M N2 APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.810370E+09 | 531.32 | 27-JAN-18:20 | 15.37 | 11.88 | 0.112784E+09 | 70.32 | 19-JAN-22:00 | 15.37 | 11.88 |
| February | 0.101621E+10 | 945.91 | 24-FEB-17:05 | 25.33 | 17.24 | 0.112931E+09 | 70.32 | 03-FEB-21:49 | 25.33 | 17.24 |
| March | 0.188079E+10 | 1366.82 | 29-MAR-16:30 | 32.55 | 18.55 | 0.128738E+09 | 70.32 | 01-MAR-03:20 | 32.55 | 18.55 |
| April | 0.267118E+10 | 1764.53 | 27-APR-16:03 | 39.70 | 18.93 | 0.124621E+09 | 70.31 | 06-APR-02:20 | 39.70 | 18.93 |
| May | 0.330691E+10 | 1968.14 | 05-MAY-17:04 | 42.27 | 20.34 | 0.128775E+09 | 70.29 | 13-MAY-01:30 | 23.40 | 19.68 |
| June | 0.322564E+10 | 1977.18 | 06-JUN-16:08 | 44.00 | 21.68 | 0.124621E+09 | 70.29 | 18-JUN-05:30 | 23.55 | 21.85 |
| July | 0.323011E+10 | 1788.14 | 02-JUL-17:25 | 39.95 | 26.58 | 0.128775E+09 | 70.28 | 19-JUL-03:20 | 23.63 | 23.63 |
| August | 0.298242E+10 | 1649.06 | 07-AUG-17:17 | 36.37 | 26.97 | 0.128775E+09 | 70.29 | 16-AUG-00:20 | 23.53 | 23.04 |
| September | 0.260719E+10 | 1472.32 | 22-SEP-16:10 | 34.38 | 24.77 | 0.124621E+09 | 70.29 | 27-SEP-04:40 | 23.30 | 20.89 |
| October | 0.219711E+10 | 1397.40 | 03-OCT-16:03 | 34.05 | 22.34 | 0.128772E+09 | 70.30 | 18-OCT-21:49 | 23.40 | 19.13 |
| November | 0.142769E+10 | 977.29 | 04-NOV-16:20 | 28.97 | 17.69 | 0.124269E+09 | 70.31 | 21-NOV-03:00 | 13.60 | 11.24 |
| December | 0.909259E+09 | 629.95 | 28-DEC-17:05 | 22.60 | 14.86 | 0.121010E+09 | 70.31 | 26-DEC-23:10 | 22.60 | 14.86 |
| Annual Sum or Average | 0.262649E+11 | 0.148869E+10 | ||||||||
| Minimum of Months | 0.810370E+09 | 531.32 | 15.37 | 11.88 | 0.112784E+09 | 70.28 | 13.60 | 11.24 | ||
| Maximum of Months | 0.330691E+10 | 1977.18 | 44.00 | 26.97 | 0.128775E+09 | 70.32 | 39.70 | 23.63 |
Report: ZoneCoolingSummaryMonthly
For: M S1 APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.156104E+10 | 1423.61 | 12-JAN-14:30 | 23.45 | 14.09 | 0.124741E+09 | 70.32 | 22-JAN-23:19 | 8.60 | 7.18 |
| February | 0.178607E+10 | 1734.17 | 20-FEB-14:30 | 26.35 | 13.75 | 0.114004E+09 | 70.32 | 05-FEB-01:39 | 26.35 | 13.75 |
| March | 0.255621E+10 | 1870.05 | 12-MAR-16:05 | 31.18 | 19.88 | 0.123962E+09 | 70.31 | 25-MAR-06:40 | 15.73 | 11.44 |
| April | 0.308780E+10 | 2069.96 | 15-APR-15:10 | 40.22 | 20.73 | 0.123964E+09 | 70.31 | 06-APR-02:20 | 40.22 | 20.73 |
| May | 0.338936E+10 | 2037.70 | 05-MAY-16:03 | 43.00 | 20.35 | 0.125734E+09 | 70.29 | 13-MAY-01:30 | 23.40 | 19.68 |
| June | 0.321060E+10 | 1971.92 | 06-JUN-15:10 | 44.18 | 21.72 | 0.120422E+09 | 70.29 | 18-JUN-05:30 | 23.55 | 21.85 |
| July | 0.323651E+10 | 1793.89 | 02-JUL-17:03 | 40.18 | 26.57 | 0.129276E+09 | 70.28 | 19-JUL-03:20 | 23.63 | 23.63 |
| August | 0.306311E+10 | 1712.58 | 06-AUG-16:20 | 36.20 | 26.31 | 0.123963E+09 | 70.29 | 16-AUG-00:20 | 23.53 | 23.04 |
| September | 0.296640E+10 | 1939.81 | 24-SEP-15:20 | 35.00 | 24.98 | 0.123963E+09 | 70.29 | 27-SEP-04:40 | 23.30 | 20.89 |
| October | 0.309586E+10 | 2057.12 | 17-OCT-14:10 | 32.88 | 18.40 | 0.127505E+09 | 70.30 | 24-OCT-19:00 | 23.10 | 16.11 |
| November | 0.258828E+10 | 1954.93 | 04-NOV-14:00 | 30.30 | 17.17 | 0.123962E+09 | 70.31 | 27-NOV-04:00 | 9.90 | 8.79 |
| December | 0.183996E+10 | 1669.16 | 02-DEC-14:00 | 24.10 | 13.15 | 0.127336E+09 | 70.32 | 03-DEC-02:09 | 9.33 | 8.16 |
| Annual Sum or Average | 0.323812E+11 | 0.148883E+10 | ||||||||
| Minimum of Months | 0.156104E+10 | 1423.61 | 23.45 | 13.15 | 0.114004E+09 | 70.28 | 8.60 | 7.18 | ||
| Maximum of Months | 0.338936E+10 | 2069.96 | 44.18 | 26.57 | 0.129276E+09 | 70.32 | 40.22 | 23.63 |
Report: ZoneCoolingSummaryMonthly
For: M S2 APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.156407E+10 | 1426.19 | 12-JAN-14:30 | 23.45 | 14.09 | 0.124745E+09 | 70.32 | 22-JAN-23:19 | 8.60 | 7.18 |
| February | 0.178887E+10 | 1737.21 | 20-FEB-14:30 | 26.35 | 13.75 | 0.114005E+09 | 70.32 | 05-FEB-01:39 | 26.35 | 13.75 |
| March | 0.255763E+10 | 1867.91 | 12-MAR-16:05 | 31.18 | 19.88 | 0.123962E+09 | 70.31 | 25-MAR-18:30 | 23.30 | 13.98 |
| April | 0.308885E+10 | 2070.45 | 15-APR-15:10 | 40.22 | 20.73 | 0.123964E+09 | 70.31 | 06-APR-02:20 | 40.22 | 20.73 |
| May | 0.339044E+10 | 2034.71 | 05-MAY-16:03 | 43.00 | 20.35 | 0.125734E+09 | 70.29 | 13-MAY-01:30 | 23.40 | 19.68 |
| June | 0.320920E+10 | 1971.31 | 06-JUN-15:10 | 44.18 | 21.72 | 0.120422E+09 | 70.29 | 18-JUN-05:30 | 23.55 | 21.85 |
| July | 0.323678E+10 | 1788.97 | 02-JUL-17:03 | 40.18 | 26.57 | 0.129276E+09 | 70.28 | 19-JUL-03:20 | 23.63 | 23.63 |
| August | 0.306340E+10 | 1710.02 | 06-AUG-16:20 | 36.20 | 26.31 | 0.123963E+09 | 70.29 | 16-AUG-00:20 | 23.53 | 23.04 |
| September | 0.296612E+10 | 1938.04 | 24-SEP-15:10 | 35.05 | 24.91 | 0.123963E+09 | 70.29 | 27-SEP-04:40 | 23.30 | 20.89 |
| October | 0.309686E+10 | 2058.78 | 17-OCT-14:10 | 32.88 | 18.40 | 0.127505E+09 | 70.30 | 24-OCT-19:00 | 23.10 | 16.11 |
| November | 0.258889E+10 | 1956.89 | 04-NOV-14:00 | 30.30 | 17.17 | 0.123962E+09 | 70.32 | 27-NOV-04:00 | 9.90 | 8.79 |
| December | 0.184178E+10 | 1671.21 | 02-DEC-14:00 | 24.10 | 13.15 | 0.127334E+09 | 70.32 | 16-DEC-05:10 | 13.35 | 10.64 |
| Annual Sum or Average | 0.323929E+11 | 0.148884E+10 | ||||||||
| Minimum of Months | 0.156407E+10 | 1426.19 | 23.45 | 13.15 | 0.114005E+09 | 70.28 | 8.60 | 7.18 | ||
| Maximum of Months | 0.339044E+10 | 2070.45 | 44.18 | 26.57 | 0.129276E+09 | 70.32 | 40.22 | 23.63 |
Report: ZoneCoolingSummaryMonthly
For: T SW APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.826112E+09 | 1713.48 | 12-JAN-15:20 | 23.50 | 14.30 | 96360382.22 | 70.36 | 30-JAN-18:49 | 15.63 | 9.96 |
| February | 0.138045E+10 | 2641.63 | 20-FEB-16:10 | 25.43 | 14.23 | 96479504.93 | 70.37 | 14-FEB-23:40 | 25.43 | 14.23 |
| March | 0.280845E+10 | 3508.94 | 28-MAR-16:01 | 35.40 | 18.76 | 0.119747E+09 | 70.37 | 16-MAR-01:10 | 35.40 | 18.76 |
| April | 0.438791E+10 | 4334.42 | 15-APR-15:20 | 40.13 | 20.80 | 0.123890E+09 | 70.35 | 11-APR-04:30 | 40.13 | 20.80 |
| May | 0.533407E+10 | 4521.24 | 05-MAY-16:03 | 43.00 | 20.35 | 0.125734E+09 | 70.30 | 13-MAY-01:30 | 23.40 | 19.68 |
| June | 0.510645E+10 | 4462.24 | 06-JUN-16:03 | 44.00 | 21.68 | 0.120422E+09 | 70.30 | 18-JUN-05:30 | 23.55 | 21.85 |
| July | 0.484475E+10 | 3865.76 | 02-JUL-16:30 | 40.35 | 26.46 | 0.129276E+09 | 70.28 | 19-JUL-03:20 | 23.63 | 23.63 |
| August | 0.435759E+10 | 3452.76 | 06-AUG-16:03 | 36.25 | 26.27 | 0.123964E+09 | 70.29 | 16-AUG-00:20 | 23.53 | 23.04 |
| September | 0.392129E+10 | 3675.67 | 24-SEP-15:30 | 34.95 | 25.05 | 0.123963E+09 | 70.29 | 27-SEP-04:40 | 23.30 | 20.89 |
| October | 0.357049E+10 | 3762.54 | 03-OCT-15:10 | 35.22 | 22.44 | 0.126659E+09 | 70.35 | 28-OCT-01:19 | 17.27 | 15.73 |
| November | 0.232367E+10 | 3136.56 | 04-NOV-15:20 | 29.93 | 17.59 | 0.113086E+09 | 70.35 | 25-NOV-21:40 | 13.87 | 10.44 |
| December | 0.107695E+10 | 2052.77 | 02-DEC-15:00 | 23.90 | 13.19 | 99541198.46 | 70.37 | 30-DEC-18:10 | 12.98 | 7.93 |
| Annual Sum or Average | 0.399382E+11 | 0.139912E+10 | ||||||||
| Minimum of Months | 0.826112E+09 | 1713.48 | 23.50 | 13.19 | 96360382.22 | 70.28 | 12.98 | 7.93 | ||
| Maximum of Months | 0.533407E+10 | 4521.24 | 44.00 | 26.46 | 0.129276E+09 | 70.37 | 40.13 | 23.63 |
Report: ZoneCoolingSummaryMonthly
For: T NW APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.301185E+09 | 540.43 | 12-JAN-17:07 | 22.03 | 14.45 | 88736284.81 | 64.81 | 12-JAN-21:10 | 14.33 | 11.55 |
| February | 0.697277E+09 | 1548.72 | 22-FEB-16:20 | 26.23 | 15.89 | 93917454.97 | 70.38 | 20-FEB-00:30 | 26.23 | 15.89 |
| March | 0.210993E+10 | 2932.03 | 28-MAR-16:30 | 35.20 | 18.83 | 0.123537E+09 | 70.37 | 04-MAR-00:20 | 35.20 | 18.83 |
| April | 0.392625E+10 | 4010.49 | 27-APR-16:03 | 39.70 | 18.93 | 0.124533E+09 | 70.33 | 23-APR-04:19 | 39.70 | 18.93 |
| May | 0.524015E+10 | 4409.72 | 05-MAY-16:15 | 42.90 | 20.36 | 0.128775E+09 | 70.30 | 13-MAY-01:30 | 23.40 | 19.68 |
| June | 0.512096E+10 | 4461.50 | 06-JUN-16:03 | 44.00 | 21.68 | 0.124621E+09 | 70.30 | 18-JUN-05:30 | 23.55 | 21.85 |
| July | 0.483802E+10 | 3805.51 | 02-JUL-16:50 | 40.32 | 26.53 | 0.128775E+09 | 70.28 | 19-JUL-03:20 | 23.63 | 23.63 |
| August | 0.426424E+10 | 3342.27 | 07-AUG-16:20 | 36.93 | 26.75 | 0.128775E+09 | 70.29 | 16-AUG-00:20 | 23.53 | 23.04 |
| September | 0.352563E+10 | 2975.76 | 22-SEP-16:01 | 34.38 | 24.77 | 0.124621E+09 | 70.29 | 27-SEP-04:40 | 23.30 | 20.89 |
| October | 0.260688E+10 | 2930.53 | 03-OCT-15:10 | 35.22 | 22.44 | 0.127628E+09 | 70.34 | 28-OCT-00:30 | 17.60 | 15.86 |
| November | 0.119769E+10 | 1770.79 | 04-NOV-16:10 | 29.18 | 17.67 | 0.110266E+09 | 70.35 | 01-NOV-23:30 | 29.18 | 17.67 |
| December | 0.376152E+09 | 738.97 | 28-DEC-16:10 | 23.63 | 15.15 | 91639876.91 | 70.27 | 28-DEC-21:10 | 18.85 | 14.08 |
| Annual Sum or Average | 0.342044E+11 | 0.139583E+10 | ||||||||
| Minimum of Months | 0.301185E+09 | 540.43 | 22.03 | 14.45 | 88736284.81 | 64.81 | 14.33 | 11.55 | ||
| Maximum of Months | 0.524015E+10 | 4461.50 | 44.00 | 26.75 | 0.128775E+09 | 70.38 | 39.70 | 23.63 |
Report: ZoneCoolingSummaryMonthly
For: T SE APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.810134E+09 | 1568.82 | 12-JAN-14:40 | 23.50 | 14.13 | 96134822.09 | 70.37 | 28-JAN-19:10 | 13.87 | 10.57 |
| February | 0.139402E+10 | 2412.45 | 20-FEB-14:30 | 26.35 | 13.75 | 96640120.56 | 70.37 | 18-FEB-21:49 | 26.35 | 13.75 |
| March | 0.282703E+10 | 3041.43 | 13-MAR-14:10 | 32.48 | 18.81 | 0.119743E+09 | 70.35 | 26-MAR-00:10 | 17.32 | 13.21 |
| April | 0.440922E+10 | 4046.73 | 15-APR-14:00 | 40.20 | 20.61 | 0.123887E+09 | 70.37 | 10-APR-02:49 | 40.20 | 20.61 |
| May | 0.536421E+10 | 4027.34 | 05-MAY-15:10 | 43.27 | 20.42 | 0.125734E+09 | 70.30 | 13-MAY-01:30 | 23.40 | 19.68 |
| June | 0.505230E+10 | 4057.43 | 06-JUN-15:10 | 44.18 | 21.72 | 0.120422E+09 | 70.30 | 18-JUN-05:30 | 23.55 | 21.85 |
| July | 0.485004E+10 | 3359.40 | 07-JUL-14:10 | 40.32 | 24.56 | 0.129276E+09 | 70.28 | 19-JUL-03:20 | 23.63 | 23.63 |
| August | 0.436334E+10 | 3163.93 | 07-AUG-15:10 | 37.27 | 26.59 | 0.123964E+09 | 70.29 | 16-AUG-00:20 | 23.53 | 23.04 |
| September | 0.390779E+10 | 3386.53 | 28-SEP-14:10 | 35.50 | 22.76 | 0.123963E+09 | 70.29 | 27-SEP-04:40 | 35.50 | 22.76 |
| October | 0.359350E+10 | 3565.29 | 03-OCT-14:10 | 35.73 | 22.27 | 0.126642E+09 | 70.35 | 17-OCT-05:40 | 19.83 | 15.95 |
| November | 0.231947E+10 | 2876.22 | 04-NOV-14:00 | 30.30 | 17.17 | 0.113061E+09 | 70.36 | 30-NOV-21:40 | 14.63 | 9.89 |
| December | 0.106819E+10 | 1878.28 | 02-DEC-14:10 | 24.07 | 13.15 | 99473409.31 | 70.37 | 08-DEC-18:49 | 15.32 | 12.80 |
| Annual Sum or Average | 0.399592E+11 | 0.139894E+10 | ||||||||
| Minimum of Months | 0.810134E+09 | 1568.82 | 23.50 | 13.15 | 96134822.09 | 70.28 | 13.87 | 9.89 | ||
| Maximum of Months | 0.536421E+10 | 4057.43 | 44.18 | 26.59 | 0.129276E+09 | 70.37 | 40.20 | 23.63 |
Report: ZoneCoolingSummaryMonthly
For: T NE APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.302680E+09 | 465.71 | 26-JAN-14:00 | 22.50 | 13.87 | 87740642.20 | 64.01 | 14-JAN-22:40 | 22.50 | 13.87 |
| February | 0.691921E+09 | 1327.16 | 23-FEB-14:30 | 26.10 | 14.00 | 94064576.43 | 70.35 | 14-FEB-21:49 | 26.10 | 14.00 |
| March | 0.212136E+10 | 2431.66 | 29-MAR-16:05 | 32.78 | 18.63 | 0.123594E+09 | 70.36 | 15-MAR-04:10 | 32.78 | 18.63 |
| April | 0.394713E+10 | 3507.70 | 15-APR-15:10 | 40.22 | 20.73 | 0.124532E+09 | 70.36 | 10-APR-02:30 | 40.22 | 20.73 |
| May | 0.527051E+10 | 3837.29 | 05-MAY-15:10 | 43.27 | 20.42 | 0.128775E+09 | 70.30 | 13-MAY-01:30 | 23.40 | 19.68 |
| June | 0.506690E+10 | 3985.08 | 06-JUN-15:10 | 44.18 | 21.72 | 0.124621E+09 | 70.30 | 18-JUN-05:30 | 23.55 | 21.85 |
| July | 0.484336E+10 | 3282.43 | 07-JUL-14:10 | 40.32 | 24.56 | 0.128775E+09 | 70.28 | 19-JUL-03:20 | 23.63 | 23.63 |
| August | 0.426999E+10 | 3030.01 | 07-AUG-16:03 | 37.02 | 26.70 | 0.128775E+09 | 70.29 | 16-AUG-00:20 | 23.53 | 23.04 |
| September | 0.351199E+10 | 2654.05 | 22-SEP-15:10 | 34.75 | 25.00 | 0.124621E+09 | 70.29 | 27-SEP-04:40 | 23.30 | 20.89 |
| October | 0.262696E+10 | 2617.01 | 03-OCT-15:10 | 35.22 | 22.44 | 0.127605E+09 | 70.34 | 10-OCT-05:49 | 20.20 | 18.25 |
| November | 0.117945E+10 | 1529.05 | 09-NOV-14:00 | 29.40 | 17.86 | 0.110260E+09 | 70.35 | 15-NOV-22:40 | 16.83 | 14.23 |
| December | 0.368115E+09 | 496.12 | 01-DEC-15:10 | 23.22 | 13.42 | 91102664.09 | 70.07 | 28-DEC-21:10 | 18.85 | 14.08 |
| Annual Sum or Average | 0.342004E+11 | 0.139447E+10 | ||||||||
| Minimum of Months | 0.302680E+09 | 465.71 | 22.50 | 13.42 | 87740642.20 | 64.01 | 16.83 | 13.87 | ||
| Maximum of Months | 0.527051E+10 | 3985.08 | 44.18 | 26.70 | 0.128775E+09 | 70.36 | 40.22 | 23.63 |
Report: ZoneCoolingSummaryMonthly
For: T N1 APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.354264E+09 | 363.60 | 04-JAN-23:00 | 9.00 | 8.18 | 89916603.56 | 68.11 | 14-JAN-22:49 | 17.33 | 13.74 |
| February | 0.652079E+09 | 1042.75 | 22-FEB-17:08 | 25.53 | 15.68 | 97090167.57 | 70.37 | 20-FEB-00:49 | 25.53 | 15.68 |
| March | 0.176512E+10 | 1943.84 | 29-MAR-16:13 | 32.67 | 18.59 | 0.125495E+09 | 70.36 | 25-MAR-02:39 | 32.67 | 18.59 |
| April | 0.310778E+10 | 2637.23 | 27-APR-16:01 | 39.70 | 18.93 | 0.124589E+09 | 70.35 | 10-APR-04:49 | 39.70 | 18.93 |
| May | 0.413436E+10 | 2925.67 | 05-MAY-16:01 | 43.00 | 20.35 | 0.128775E+09 | 70.30 | 13-MAY-01:30 | 23.40 | 19.68 |
| June | 0.407893E+10 | 3003.53 | 06-JUN-15:10 | 44.18 | 21.72 | 0.124621E+09 | 70.30 | 18-JUN-05:30 | 23.55 | 21.85 |
| July | 0.396435E+10 | 2622.02 | 02-JUL-17:06 | 40.18 | 26.57 | 0.128775E+09 | 70.28 | 19-JUL-03:20 | 23.63 | 23.63 |
| August | 0.355480E+10 | 2401.48 | 07-AUG-16:17 | 36.93 | 26.75 | 0.128775E+09 | 70.29 | 16-AUG-00:20 | 23.53 | 23.04 |
| September | 0.293927E+10 | 2073.39 | 22-SEP-16:03 | 34.38 | 24.77 | 0.124621E+09 | 70.29 | 27-SEP-04:40 | 23.30 | 20.89 |
| October | 0.219507E+10 | 2014.21 | 03-OCT-15:10 | 35.22 | 22.44 | 0.128138E+09 | 70.35 | 23-OCT-05:40 | 18.83 | 14.21 |
| November | 0.104018E+10 | 1214.22 | 09-NOV-14:30 | 29.30 | 17.79 | 0.113899E+09 | 70.36 | 04-NOV-23:49 | 29.30 | 17.79 |
| December | 0.444060E+09 | 428.27 | 28-DEC-17:08 | 22.60 | 14.86 | 93398397.88 | 70.33 | 28-DEC-21:19 | 18.70 | 14.05 |
| Annual Sum or Average | 0.282302E+11 | 0.140809E+10 | ||||||||
| Minimum of Months | 0.354264E+09 | 363.60 | 9.00 | 8.18 | 89916603.56 | 68.11 | 17.33 | 13.74 | ||
| Maximum of Months | 0.413436E+10 | 3003.53 | 44.18 | 26.75 | 0.128775E+09 | 70.37 | 39.70 | 23.63 |
Report: ZoneCoolingSummaryMonthly
For: T N2 APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.354276E+09 | 362.97 | 04-JAN-23:00 | 9.00 | 8.18 | 89856425.51 | 68.07 | 14-JAN-22:49 | 17.33 | 13.74 |
| February | 0.655919E+09 | 1041.49 | 22-FEB-16:10 | 26.37 | 15.92 | 97103158.58 | 70.37 | 20-FEB-00:49 | 26.37 | 15.92 |
| March | 0.176864E+10 | 1935.10 | 29-MAR-16:03 | 32.78 | 18.63 | 0.125489E+09 | 70.38 | 25-MAR-02:00 | 32.78 | 18.63 |
| April | 0.310948E+10 | 2625.15 | 27-APR-16:01 | 39.70 | 18.93 | 0.124588E+09 | 70.36 | 10-APR-04:30 | 39.70 | 18.93 |
| May | 0.413593E+10 | 2916.07 | 05-MAY-16:01 | 43.00 | 20.35 | 0.128775E+09 | 70.30 | 13-MAY-01:30 | 23.40 | 19.68 |
| June | 0.407734E+10 | 3000.16 | 06-JUN-15:10 | 44.18 | 21.72 | 0.124621E+09 | 70.30 | 18-JUN-05:30 | 23.55 | 21.85 |
| July | 0.396469E+10 | 2609.02 | 02-JUL-17:07 | 40.18 | 26.57 | 0.128775E+09 | 70.28 | 19-JUL-03:20 | 23.63 | 23.63 |
| August | 0.355520E+10 | 2395.56 | 07-AUG-16:07 | 37.02 | 26.70 | 0.128775E+09 | 70.29 | 16-AUG-00:20 | 23.53 | 23.04 |
| September | 0.293907E+10 | 2065.92 | 22-SEP-16:04 | 34.38 | 24.77 | 0.124621E+09 | 70.29 | 27-SEP-04:40 | 23.30 | 20.89 |
| October | 0.219701E+10 | 2011.46 | 03-OCT-15:10 | 35.22 | 22.44 | 0.128135E+09 | 70.36 | 21-OCT-03:00 | 18.00 | 15.07 |
| November | 0.104337E+10 | 1215.76 | 09-NOV-14:20 | 29.33 | 17.81 | 0.113883E+09 | 70.36 | 02-NOV-00:10 | 29.33 | 17.81 |
| December | 0.444840E+09 | 422.82 | 28-DEC-17:10 | 22.60 | 14.86 | 93366713.71 | 70.34 | 28-DEC-22:40 | 17.50 | 13.83 |
| Annual Sum or Average | 0.282458E+11 | 0.140799E+10 | ||||||||
| Minimum of Months | 0.354276E+09 | 362.97 | 9.00 | 8.18 | 89856425.51 | 68.07 | 17.33 | 13.74 | ||
| Maximum of Months | 0.413593E+10 | 3000.16 | 44.18 | 26.70 | 0.128775E+09 | 70.38 | 39.70 | 23.63 |
Report: ZoneCoolingSummaryMonthly
For: T S1 APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.912101E+09 | 1484.43 | 12-JAN-15:00 | 23.60 | 14.20 | 0.100588E+09 | 70.37 | 08-JAN-20:49 | 23.60 | 14.20 |
| February | 0.136627E+10 | 2170.81 | 20-FEB-14:40 | 26.33 | 13.84 | 0.100491E+09 | 70.37 | 20-FEB-01:30 | 26.33 | 13.84 |
| March | 0.248019E+10 | 2593.01 | 12-MAR-15:20 | 31.43 | 19.70 | 0.121597E+09 | 70.36 | 23-MAR-03:30 | 16.95 | 14.28 |
| April | 0.357306E+10 | 3111.89 | 15-APR-15:10 | 40.22 | 20.73 | 0.123937E+09 | 70.37 | 10-APR-05:10 | 40.22 | 20.73 |
| May | 0.422877E+10 | 3060.80 | 05-MAY-15:10 | 43.27 | 20.42 | 0.125734E+09 | 70.30 | 13-MAY-01:30 | 23.40 | 19.68 |
| June | 0.406421E+10 | 3073.45 | 06-JUN-15:10 | 44.18 | 21.72 | 0.120422E+09 | 70.30 | 18-JUN-05:30 | 23.55 | 21.85 |
| July | 0.397123E+10 | 2679.11 | 02-JUL-16:15 | 40.37 | 26.43 | 0.129276E+09 | 70.28 | 19-JUL-03:20 | 23.63 | 23.63 |
| August | 0.364879E+10 | 2498.58 | 06-AUG-16:03 | 36.25 | 26.27 | 0.123963E+09 | 70.29 | 16-AUG-00:20 | 23.53 | 23.04 |
| September | 0.333839E+10 | 2771.47 | 27-SEP-14:10 | 35.55 | 22.75 | 0.123963E+09 | 70.29 | 27-SEP-04:40 | 35.55 | 22.75 |
| October | 0.317379E+10 | 2915.91 | 03-OCT-14:10 | 35.73 | 22.27 | 0.127082E+09 | 70.34 | 28-OCT-02:20 | 16.90 | 15.56 |
| November | 0.219892E+10 | 2588.12 | 04-NOV-14:10 | 30.28 | 17.23 | 0.116856E+09 | 70.35 | 15-NOV-00:30 | 15.80 | 13.98 |
| December | 0.117688E+10 | 1762.91 | 02-DEC-14:20 | 24.03 | 13.16 | 0.104432E+09 | 70.37 | 18-DEC-20:19 | 16.93 | 13.17 |
| Annual Sum or Average | 0.341326E+11 | 0.141834E+10 | ||||||||
| Minimum of Months | 0.912101E+09 | 1484.43 | 23.60 | 13.16 | 0.100491E+09 | 70.28 | 15.80 | 13.17 | ||
| Maximum of Months | 0.422877E+10 | 3111.89 | 44.18 | 26.43 | 0.129276E+09 | 70.37 | 40.22 | 23.63 |
Report: ZoneCoolingSummaryMonthly
For: T S2 APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.915142E+09 | 1488.41 | 12-JAN-15:00 | 23.60 | 14.20 | 0.100568E+09 | 70.38 | 19-JAN-20:40 | 14.03 | 11.78 |
| February | 0.137096E+10 | 2177.04 | 20-FEB-14:40 | 26.33 | 13.84 | 0.100485E+09 | 70.37 | 20-FEB-01:30 | 26.33 | 13.84 |
| March | 0.248336E+10 | 2590.93 | 12-MAR-15:20 | 31.43 | 19.70 | 0.121588E+09 | 70.36 | 18-MAR-01:49 | 16.85 | 14.88 |
| April | 0.357476E+10 | 3110.03 | 15-APR-15:10 | 40.22 | 20.73 | 0.123936E+09 | 70.36 | 10-APR-05:10 | 40.22 | 20.73 |
| May | 0.423037E+10 | 3058.33 | 05-MAY-15:10 | 43.27 | 20.42 | 0.125734E+09 | 70.30 | 13-MAY-01:30 | 23.40 | 19.68 |
| June | 0.406263E+10 | 3070.10 | 06-JUN-15:10 | 44.18 | 21.72 | 0.120422E+09 | 70.30 | 18-JUN-05:30 | 23.55 | 21.85 |
| July | 0.397158E+10 | 2669.08 | 02-JUL-16:15 | 40.37 | 26.43 | 0.129276E+09 | 70.28 | 19-JUL-03:20 | 23.63 | 23.63 |
| August | 0.364920E+10 | 2493.15 | 07-AUG-15:10 | 37.27 | 26.59 | 0.123963E+09 | 70.29 | 16-AUG-00:20 | 23.53 | 23.04 |
| September | 0.333820E+10 | 2774.55 | 27-SEP-14:10 | 35.55 | 22.75 | 0.123963E+09 | 70.29 | 27-SEP-04:40 | 35.55 | 22.75 |
| October | 0.317551E+10 | 2919.47 | 03-OCT-14:10 | 35.73 | 22.27 | 0.127079E+09 | 70.33 | 28-OCT-02:20 | 16.90 | 15.56 |
| November | 0.220143E+10 | 2590.85 | 04-NOV-14:10 | 30.28 | 17.23 | 0.116834E+09 | 70.36 | 12-NOV-01:10 | 16.40 | 14.15 |
| December | 0.118026E+10 | 1767.63 | 02-DEC-14:20 | 24.03 | 13.16 | 0.104405E+09 | 70.37 | 26-DEC-20:00 | 14.30 | 12.00 |
| Annual Sum or Average | 0.341534E+11 | 0.141826E+10 | ||||||||
| Minimum of Months | 0.915142E+09 | 1488.41 | 23.60 | 13.16 | 0.100485E+09 | 70.28 | 14.03 | 11.78 | ||
| Maximum of Months | 0.423037E+10 | 3110.03 | 44.18 | 26.59 | 0.129276E+09 | 70.38 | 40.22 | 23.63 |
Report: ZoneCoolingSummaryMonthly
For: T CORRIDOR
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 7.83 | 7.49 | 0.173923E+09 | 130.99 | 14-JAN-21:10 | 17.67 | 13.83 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 9.73 | 7.85 | 0.191890E+09 | 148.32 | 22-FEB-21:10 | 20.90 | 14.58 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 | 12.96 | 0.262073E+09 | 174.10 | 28-MAR-20:10 | 28.48 | 18.89 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 23.70 | 16.77 | 0.287969E+09 | 187.99 | 27-APR-20:10 | 36.02 | 17.54 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 30.53 | 18.24 | 0.314990E+09 | 193.83 | 05-MAY-20:10 | 37.98 | 19.06 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 28.05 | 22.58 | 0.307556E+09 | 196.21 | 12-JUN-20:10 | 38.43 | 22.54 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 32.95 | 24.65 | 0.313151E+09 | 194.45 | 04-JUL-20:10 | 39.85 | 24.37 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 29.32 | 26.26 | 0.305680E+09 | 185.88 | 07-AUG-20:10 | 34.07 | 27.23 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 28.43 | 25.91 | 0.286917E+09 | 180.40 | 17-SEP-20:10 | 37.37 | 27.68 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 26.58 | 21.85 | 0.276996E+09 | 172.19 | 02-OCT-20:10 | 27.12 | 20.31 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 | 15.09 | 0.228986E+09 | 153.21 | 04-NOV-20:10 | 20.62 | 16.10 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 12.50 | 9.11 | 0.184664E+09 | 134.46 | 28-DEC-21:10 | 18.85 | 14.08 |
| Annual Sum or Average | 0.00 | 0.313479E+10 | ||||||||
| Minimum of Months | 0.00 | 0.00 | 7.83 | 7.49 | 0.173923E+09 | 130.99 | 17.67 | 13.83 | ||
| Maximum of Months | 0.00 | 0.00 | 32.95 | 26.26 | 0.314990E+09 | 196.21 | 39.85 | 27.68 |
Report: ZoneCoolingSummaryMonthly
For: G CORRIDOR
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 7.83 | 7.49 | 0.186486E+09 | 137.47 | 15-JAN-06:10 | 15.12 | 13.68 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 9.73 | 7.85 | 0.201518E+09 | 151.79 | 24-FEB-22:49 | 19.15 | 16.48 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 | 12.96 | 0.272928E+09 | 219.30 | 28-MAR-17:10 | 34.60 | 18.91 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 23.70 | 16.77 | 0.319501E+09 | 265.60 | 28-APR-17:10 | 39.07 | 19.90 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 30.53 | 18.24 | 0.363931E+09 | 305.43 | 03-MAY-17:10 | 42.68 | 21.29 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 28.05 | 22.58 | 0.358310E+09 | 317.67 | 07-JUN-17:10 | 43.85 | 21.80 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 32.95 | 24.65 | 0.359337E+09 | 283.37 | 02-JUL-17:10 | 40.18 | 26.57 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 29.32 | 26.26 | 0.348084E+09 | 249.05 | 07-AUG-17:10 | 36.48 | 26.95 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 28.43 | 25.91 | 0.328587E+09 | 231.35 | 26-SEP-17:10 | 34.60 | 22.33 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 26.58 | 21.85 | 0.313656E+09 | 230.31 | 02-OCT-17:10 | 34.42 | 21.24 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 | 15.09 | 0.257239E+09 | 164.91 | 04-NOV-21:49 | 18.45 | 15.53 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 12.50 | 9.11 | 0.215299E+09 | 145.81 | 01-DEC-00:20 | 12.40 | 9.10 |
| Annual Sum or Average | 0.00 | 0.352488E+10 | ||||||||
| Minimum of Months | 0.00 | 0.00 | 7.83 | 7.49 | 0.186486E+09 | 137.47 | 12.40 | 9.10 | ||
| Maximum of Months | 0.00 | 0.00 | 32.95 | 26.26 | 0.363931E+09 | 317.67 | 43.85 | 26.95 |
Report: ZoneCoolingSummaryMonthly
For: M CORRIDOR
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 7.83 | 7.49 | 0.235755E+09 | 143.48 | 14-JAN-21:10 | 17.67 | 13.83 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 9.73 | 7.85 | 0.233877E+09 | 152.29 | 22-FEB-21:10 | 20.90 | 14.58 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 | 12.96 | 0.277851E+09 | 161.86 | 28-MAR-20:10 | 28.48 | 18.89 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 23.70 | 16.77 | 0.282663E+09 | 168.56 | 27-APR-20:10 | 36.02 | 17.54 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 30.53 | 18.24 | 0.298837E+09 | 171.71 | 05-MAY-20:10 | 37.98 | 19.06 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 28.05 | 22.58 | 0.288921E+09 | 171.93 | 12-JUN-20:10 | 38.43 | 22.54 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 32.95 | 24.65 | 0.295657E+09 | 170.52 | 04-JUL-20:10 | 39.85 | 24.37 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 29.32 | 26.26 | 0.291860E+09 | 166.86 | 07-AUG-20:10 | 34.07 | 27.23 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 28.43 | 25.91 | 0.279772E+09 | 164.53 | 17-SEP-20:10 | 37.37 | 27.68 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 26.58 | 21.85 | 0.284030E+09 | 162.71 | 01-OCT-20:10 | 27.03 | 21.10 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 | 15.09 | 0.263179E+09 | 155.13 | 04-NOV-20:10 | 20.62 | 16.10 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 12.50 | 9.11 | 0.249748E+09 | 146.06 | 01-DEC-21:10 | 12.15 | 11.68 |
| Annual Sum or Average | 0.00 | 0.328215E+10 | ||||||||
| Minimum of Months | 0.00 | 0.00 | 7.83 | 7.49 | 0.233877E+09 | 143.48 | 12.15 | 11.68 | ||
| Maximum of Months | 0.00 | 0.00 | 32.95 | 26.26 | 0.298837E+09 | 171.93 | 39.85 | 27.68 |
Report: ZoneHeatingSummaryMonthly
For: G SW APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 7.83 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 9.73 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 23.70 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 30.53 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 28.05 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 32.95 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 29.32 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 28.43 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 26.58 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 12.50 |
| Annual Sum or Average | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 7.83 | |
| Maximum of Months | 0.00 | 0.00 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: G NW APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 2482.48 | 2.88 | 08-JAN-15:00 | 22.90 |
| February | 46721.26 | 18.83 | 06-FEB-13:10 | 23.97 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 23.70 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 30.53 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 28.05 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 32.95 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 29.32 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 28.43 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 26.58 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 |
| December | 1795.92 | 2.99 | 24-DEC-13:30 | 23.40 |
| Annual Sum or Average | 50999.66 | |||
| Minimum of Months | 0.00 | 0.00 | 15.55 | |
| Maximum of Months | 46721.26 | 18.83 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: OFFICE
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 76400756.98 | 435.50 | 12-JAN-09:05 | 16.33 |
| February | 0.164043E+09 | 465.52 | 15-FEB-09:05 | 17.25 |
| March | 0.409734E+09 | 826.57 | 28-MAR-16:13 | 35.30 |
| April | 0.589233E+09 | 979.62 | 14-APR-16:01 | 39.28 |
| May | 0.471306E+09 | 1182.28 | 03-MAY-16:01 | 44.12 |
| June | 0.397417E+09 | 1198.98 | 08-JUN-16:01 | 44.47 |
| July | 0.305679E+09 | 979.27 | 07-JUL-16:01 | 39.98 |
| August | 0.358169E+09 | 803.22 | 07-AUG-17:12 | 36.37 |
| September | 0.364076E+09 | 735.16 | 27-SEP-16:13 | 35.30 |
| October | 0.271991E+09 | 713.96 | 02-OCT-16:13 | 35.53 |
| November | 0.138012E+09 | 533.94 | 03-NOV-16:12 | 27.90 |
| December | 76380411.83 | 536.22 | 06-DEC-09:05 | 19.10 |
| Annual Sum or Average | 0.362244E+10 | |||
| Minimum of Months | 76380411.83 | 435.50 | 16.33 | |
| Maximum of Months | 0.589233E+09 | 1198.98 | 44.47 |
Report: ZoneHeatingSummaryMonthly
For: G NE APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 3019.61 | 3.67 | 08-JAN-15:00 | 22.90 |
| February | 412.41 | 0.69 | 03-FEB-14:50 | 23.38 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 23.70 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 30.53 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 28.05 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 32.95 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 29.32 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 28.43 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 26.58 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 12.50 |
| Annual Sum or Average | 3432.02 | |||
| Minimum of Months | 0.00 | 0.00 | 12.50 | |
| Maximum of Months | 3019.61 | 3.67 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: G N1 APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 2657.38 | 3.36 | 08-JAN-15:00 | 22.90 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 9.73 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 23.70 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 30.53 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 28.05 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 32.95 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 29.32 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 28.43 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 26.58 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 12.50 |
| Annual Sum or Average | 2657.38 | |||
| Minimum of Months | 0.00 | 0.00 | 9.73 | |
| Maximum of Months | 2657.38 | 3.36 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: G N2 APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 2189.78 | 2.98 | 08-JAN-15:00 | 22.90 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 9.73 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 23.70 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 30.53 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 28.05 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 32.95 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 29.32 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 28.43 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 26.58 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 12.50 |
| Annual Sum or Average | 2189.78 | |||
| Minimum of Months | 0.00 | 0.00 | 9.73 | |
| Maximum of Months | 2189.78 | 2.98 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: G S1 APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 7.83 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 9.73 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 23.70 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 30.53 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 28.05 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 32.95 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 29.32 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 28.43 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 26.58 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 12.50 |
| Annual Sum or Average | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 7.83 | |
| Maximum of Months | 0.00 | 0.00 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: G S2 APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 7.83 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 9.73 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 23.70 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 30.53 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 28.05 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 32.95 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 29.32 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 28.43 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 26.58 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 12.50 |
| Annual Sum or Average | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 7.83 | |
| Maximum of Months | 0.00 | 0.00 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: M SW APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 7.83 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 9.73 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 23.70 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 30.53 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 28.05 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 32.95 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 29.32 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 28.43 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 26.58 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 12.50 |
| Annual Sum or Average | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 7.83 | |
| Maximum of Months | 0.00 | 0.00 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: M NW APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 7.83 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 9.73 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 23.70 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 30.53 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 28.05 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 32.95 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 29.32 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 28.43 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 26.58 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 |
| December | 186971.44 | 38.28 | 24-DEC-14:00 | 24.30 |
| Annual Sum or Average | 186971.44 | |||
| Minimum of Months | 0.00 | 0.00 | 7.83 | |
| Maximum of Months | 186971.44 | 38.28 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: M SE APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 7.83 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 9.73 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 23.70 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 30.53 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 28.05 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 32.95 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 29.32 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 28.43 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 26.58 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 12.50 |
| Annual Sum or Average | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 7.83 | |
| Maximum of Months | 0.00 | 0.00 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: M NE APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 7.83 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 9.73 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 23.70 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 30.53 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 28.05 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 32.95 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 29.32 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 28.43 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 26.58 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 |
| December | 204905.35 | 34.66 | 24-DEC-14:00 | 24.30 |
| Annual Sum or Average | 204905.35 | |||
| Minimum of Months | 0.00 | 0.00 | 7.83 | |
| Maximum of Months | 204905.35 | 34.66 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: M N1 APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 7.83 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 9.73 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 23.70 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 30.53 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 28.05 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 32.95 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 29.32 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 28.43 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 26.58 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 |
| December | 23822.20 | 20.82 | 24-DEC-13:50 | 24.00 |
| Annual Sum or Average | 23822.20 | |||
| Minimum of Months | 0.00 | 0.00 | 7.83 | |
| Maximum of Months | 23822.20 | 20.82 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: M N2 APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 7.83 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 9.73 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 23.70 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 30.53 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 28.05 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 32.95 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 29.32 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 28.43 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 26.58 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 |
| December | 22601.89 | 20.15 | 24-DEC-13:50 | 24.00 |
| Annual Sum or Average | 22601.89 | |||
| Minimum of Months | 0.00 | 0.00 | 7.83 | |
| Maximum of Months | 22601.89 | 20.15 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: M S1 APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 7.83 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 9.73 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 23.70 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 30.53 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 28.05 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 32.95 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 29.32 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 28.43 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 26.58 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 12.50 |
| Annual Sum or Average | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 7.83 | |
| Maximum of Months | 0.00 | 0.00 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: M S2 APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 7.83 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 9.73 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 23.70 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 30.53 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 28.05 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 32.95 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 29.32 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 28.43 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 26.58 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 12.50 |
| Annual Sum or Average | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 7.83 | |
| Maximum of Months | 0.00 | 0.00 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: T SW APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.144783E+09 | 608.97 | 03-JAN-07:00 | 5.40 |
| February | 27058600.01 | 535.02 | 11-FEB-06:00 | 9.20 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 23.70 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 30.53 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 28.05 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 32.95 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 29.32 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 28.43 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 26.58 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 |
| December | 61882728.15 | 550.06 | 23-DEC-07:00 | 6.10 |
| Annual Sum or Average | 0.233724E+09 | |||
| Minimum of Months | 0.00 | 0.00 | 5.40 | |
| Maximum of Months | 0.144783E+09 | 608.97 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: T NW APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.326211E+09 | 784.59 | 03-JAN-07:00 | 5.40 |
| February | 55167100.67 | 531.84 | 11-FEB-06:00 | 9.20 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 23.70 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 30.53 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 28.05 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 32.95 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 29.32 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 28.43 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 26.58 |
| November | 762564.04 | 62.12 | 26-NOV-06:00 | 10.80 |
| December | 0.174836E+09 | 751.61 | 23-DEC-06:00 | 5.30 |
| Annual Sum or Average | 0.556976E+09 | |||
| Minimum of Months | 0.00 | 0.00 | 5.30 | |
| Maximum of Months | 0.326211E+09 | 784.59 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: T SE APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.135410E+09 | 618.20 | 03-JAN-07:00 | 5.40 |
| February | 25379191.95 | 537.35 | 11-FEB-06:00 | 9.20 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 23.70 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 30.53 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 28.05 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 32.95 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 29.32 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 28.43 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 26.58 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 |
| December | 59882859.57 | 545.72 | 23-DEC-07:00 | 6.10 |
| Annual Sum or Average | 0.220672E+09 | |||
| Minimum of Months | 0.00 | 0.00 | 5.40 | |
| Maximum of Months | 0.135410E+09 | 618.20 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: T NE APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.300723E+09 | 798.70 | 03-JAN-07:00 | 5.40 |
| February | 48129487.29 | 534.67 | 11-FEB-06:00 | 9.20 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 23.70 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 30.53 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 28.05 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 32.95 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 29.32 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 28.43 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 26.58 |
| November | 413016.47 | 72.65 | 26-NOV-06:00 | 10.80 |
| December | 0.163721E+09 | 746.44 | 23-DEC-06:00 | 5.30 |
| Annual Sum or Average | 0.512987E+09 | |||
| Minimum of Months | 0.00 | 0.00 | 5.30 | |
| Maximum of Months | 0.300723E+09 | 798.70 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: T N1 APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.119695E+09 | 437.84 | 02-JAN-05:00 | 6.50 |
| February | 7020226.14 | 205.67 | 11-FEB-06:00 | 9.20 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 23.70 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 30.53 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 28.05 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 32.95 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 29.32 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 28.43 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 26.58 |
| November | 170219.55 | 37.75 | 26-NOV-11:30 | 24.50 |
| December | 48067467.33 | 408.54 | 23-DEC-06:00 | 5.30 |
| Annual Sum or Average | 0.174953E+09 | |||
| Minimum of Months | 0.00 | 0.00 | 5.30 | |
| Maximum of Months | 0.119695E+09 | 437.84 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: T N2 APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.120337E+09 | 439.65 | 02-JAN-05:00 | 6.50 |
| February | 7005682.58 | 206.19 | 11-FEB-06:00 | 9.20 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 23.70 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 30.53 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 28.05 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 32.95 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 29.32 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 28.43 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 26.58 |
| November | 154122.73 | 35.78 | 26-NOV-11:30 | 24.50 |
| December | 48187015.99 | 407.06 | 23-DEC-06:00 | 5.30 |
| Annual Sum or Average | 0.175684E+09 | |||
| Minimum of Months | 0.00 | 0.00 | 5.30 | |
| Maximum of Months | 0.120337E+09 | 439.65 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: T S1 APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 15854066.40 | 257.04 | 02-JAN-06:00 | 6.40 |
| February | 2959708.17 | 206.49 | 11-FEB-06:00 | 9.20 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 23.70 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 30.53 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 28.05 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 32.95 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 29.32 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 28.43 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 26.58 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 |
| December | 6968365.03 | 196.02 | 23-DEC-06:00 | 5.30 |
| Annual Sum or Average | 25782139.60 | |||
| Minimum of Months | 0.00 | 0.00 | 5.30 | |
| Maximum of Months | 15854066.40 | 257.04 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: T S2 APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 15978472.59 | 258.50 | 02-JAN-06:00 | 6.40 |
| February | 2969936.53 | 207.02 | 11-FEB-06:00 | 9.20 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 23.70 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 30.53 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 28.05 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 32.95 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 29.32 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 28.43 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 26.58 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 |
| December | 7006745.94 | 195.04 | 23-DEC-06:00 | 5.30 |
| Annual Sum or Average | 25955155.06 | |||
| Minimum of Months | 0.00 | 0.00 | 5.30 | |
| Maximum of Months | 15978472.59 | 258.50 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: T CORRIDOR
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 7.83 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 9.73 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 23.70 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 30.53 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 28.05 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 32.95 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 29.32 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 28.43 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 26.58 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 12.50 |
| Annual Sum or Average | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 7.83 | |
| Maximum of Months | 0.00 | 0.00 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: G CORRIDOR
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 7.83 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 9.73 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 23.70 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 30.53 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 28.05 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 32.95 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 29.32 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 28.43 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 26.58 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 12.50 |
| Annual Sum or Average | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 7.83 | |
| Maximum of Months | 0.00 | 0.00 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: M CORRIDOR
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 7.83 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 9.73 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 23.70 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 30.53 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 28.05 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 32.95 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 29.32 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 28.43 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 26.58 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 12.50 |
| Annual Sum or Average | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 7.83 | |
| Maximum of Months | 0.00 | 0.00 | 32.95 |
Report: ZoneElectricSummaryMonthly
For: G SW APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: G NW APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: OFFICE
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.609777E+09 | 582.92 | 03-JAN-08:09 | 0.787690E+09 | 588.62 | 03-JAN-08:09 |
| February | 0.564682E+09 | 582.92 | 01-FEB-08:09 | 0.723971E+09 | 588.62 | 01-FEB-08:09 |
| March | 0.654405E+09 | 582.92 | 01-MAR-08:09 | 0.827804E+09 | 588.62 | 01-MAR-08:09 |
| April | 0.599704E+09 | 582.92 | 03-APR-07:10 | 0.770907E+09 | 588.62 | 03-APR-07:10 |
| May | 0.639529E+09 | 582.92 | 01-MAY-07:10 | 0.814432E+09 | 588.62 | 01-MAY-07:10 |
| June | 0.629456E+09 | 582.92 | 01-JUN-07:10 | 0.797650E+09 | 588.62 | 01-JUN-07:10 |
| July | 0.609777E+09 | 582.92 | 03-JUL-07:10 | 0.787690E+09 | 588.62 | 03-JUL-07:10 |
| August | 0.654405E+09 | 582.92 | 01-AUG-07:10 | 0.827804E+09 | 588.62 | 01-AUG-07:10 |
| September | 0.599704E+09 | 582.92 | 01-SEP-07:10 | 0.770907E+09 | 588.62 | 01-SEP-07:10 |
| October | 0.624653E+09 | 582.92 | 02-OCT-07:10 | 0.801061E+09 | 588.62 | 02-OCT-07:10 |
| November | 0.599704E+09 | 582.92 | 01-NOV-07:10 | 0.770907E+09 | 588.62 | 01-NOV-07:10 |
| December | 0.609777E+09 | 582.92 | 01-DEC-08:09 | 0.787690E+09 | 588.62 | 01-DEC-08:09 |
| Annual Sum or Average | 0.739557E+10 | 0.946851E+10 | ||||
| Minimum of Months | 0.564682E+09 | 582.92 | 0.723971E+09 | 588.62 | ||
| Maximum of Months | 0.654405E+09 | 582.92 | 0.827804E+09 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: G NE APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: G N1 APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: G N2 APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: G S1 APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: G S2 APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: M SW APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: M NW APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: M SE APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: M NE APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: M N1 APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: M N2 APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: M S1 APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: M S2 APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: T SW APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: T NW APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: T SE APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: T NE APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: T N1 APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: T N2 APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: T S1 APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: T S2 APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: T CORRIDOR
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
| January | 0.992689E+09 | 370.63 | 01-JAN-00:10 | 0.00 | 0.00 |
| February | 0.896622E+09 | 370.63 | 01-FEB-00:10 | 0.00 | 0.00 |
| March | 0.992689E+09 | 370.63 | 01-MAR-00:10 | 0.00 | 0.00 |
| April | 0.960667E+09 | 370.63 | 01-APR-00:10 | 0.00 | 0.00 |
| May | 0.992689E+09 | 370.63 | 01-MAY-00:10 | 0.00 | 0.00 |
| June | 0.960667E+09 | 370.63 | 01-JUN-00:10 | 0.00 | 0.00 |
| July | 0.992689E+09 | 370.63 | 01-JUL-00:10 | 0.00 | 0.00 |
| August | 0.992689E+09 | 370.63 | 01-AUG-00:10 | 0.00 | 0.00 |
| September | 0.960667E+09 | 370.63 | 01-SEP-00:10 | 0.00 | 0.00 |
| October | 0.992689E+09 | 370.63 | 01-OCT-00:10 | 0.00 | 0.00 |
| November | 0.960667E+09 | 370.63 | 01-NOV-00:10 | 0.00 | 0.00 |
| December | 0.992689E+09 | 370.63 | 01-DEC-00:10 | 0.00 | 0.00 |
| Annual Sum or Average | 0.116881E+11 | 0.00 | 0.00 | ||
| Minimum of Months | 0.896622E+09 | 370.63 | 0.00 | 0.00 | |
| Maximum of Months | 0.992689E+09 | 370.63 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: G CORRIDOR
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.992689E+09 | 370.63 | 01-JAN-00:10 | 0.599555E+10 | 4168.07 | 01-JAN-07:10 |
| February | 0.896622E+09 | 370.63 | 01-FEB-00:10 | 0.541534E+10 | 4168.07 | 01-FEB-07:10 |
| March | 0.992689E+09 | 370.63 | 01-MAR-00:10 | 0.599555E+10 | 4168.07 | 01-MAR-07:10 |
| April | 0.960667E+09 | 370.63 | 01-APR-00:10 | 0.580215E+10 | 4168.07 | 01-APR-06:10 |
| May | 0.992689E+09 | 370.63 | 01-MAY-00:10 | 0.599555E+10 | 4168.07 | 01-MAY-06:10 |
| June | 0.960667E+09 | 370.63 | 01-JUN-00:10 | 0.580215E+10 | 4168.07 | 01-JUN-06:10 |
| July | 0.992689E+09 | 370.63 | 01-JUL-00:10 | 0.599555E+10 | 4168.07 | 01-JUL-06:10 |
| August | 0.992689E+09 | 370.63 | 01-AUG-00:10 | 0.599555E+10 | 4168.07 | 01-AUG-06:10 |
| September | 0.960667E+09 | 370.63 | 01-SEP-00:10 | 0.580215E+10 | 4168.07 | 01-SEP-06:10 |
| October | 0.992689E+09 | 370.63 | 01-OCT-00:10 | 0.599555E+10 | 4168.07 | 01-OCT-06:10 |
| November | 0.960667E+09 | 370.63 | 01-NOV-00:10 | 0.580215E+10 | 4168.07 | 01-NOV-06:10 |
| December | 0.992689E+09 | 370.63 | 01-DEC-00:10 | 0.599555E+10 | 4168.07 | 01-DEC-07:10 |
| Annual Sum or Average | 0.116881E+11 | 0.705928E+11 | ||||
| Minimum of Months | 0.896622E+09 | 370.63 | 0.541534E+10 | 4168.07 | ||
| Maximum of Months | 0.992689E+09 | 370.63 | 0.599555E+10 | 4168.07 |
Report: ZoneElectricSummaryMonthly
For: M CORRIDOR
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
| January | 0.992689E+09 | 370.63 | 01-JAN-00:10 | 0.00 | 0.00 |
| February | 0.896622E+09 | 370.63 | 01-FEB-00:10 | 0.00 | 0.00 |
| March | 0.992689E+09 | 370.63 | 01-MAR-00:10 | 0.00 | 0.00 |
| April | 0.960667E+09 | 370.63 | 01-APR-00:10 | 0.00 | 0.00 |
| May | 0.992689E+09 | 370.63 | 01-MAY-00:10 | 0.00 | 0.00 |
| June | 0.960667E+09 | 370.63 | 01-JUN-00:10 | 0.00 | 0.00 |
| July | 0.992689E+09 | 370.63 | 01-JUL-00:10 | 0.00 | 0.00 |
| August | 0.992689E+09 | 370.63 | 01-AUG-00:10 | 0.00 | 0.00 |
| September | 0.960667E+09 | 370.63 | 01-SEP-00:10 | 0.00 | 0.00 |
| October | 0.992689E+09 | 370.63 | 01-OCT-00:10 | 0.00 | 0.00 |
| November | 0.960667E+09 | 370.63 | 01-NOV-00:10 | 0.00 | 0.00 |
| December | 0.992689E+09 | 370.63 | 01-DEC-00:10 | 0.00 | 0.00 |
| Annual Sum or Average | 0.116881E+11 | 0.00 | 0.00 | ||
| Minimum of Months | 0.896622E+09 | 370.63 | 0.00 | 0.00 | |
| Maximum of Months | 0.992689E+09 | 370.63 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: G SW APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89275814.47 |
| February | 0.389025E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2279551.42 | 83446237.54 |
| March | 0.418950E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30404687.19 | 38049122.74 |
| April | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115354E+09 | 1845331.55 |
| May | 0.424935E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.202254E+09 | 173219.13 |
| June | 0.406980E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.145173E+09 | 47917.00 |
| July | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.169182E+09 | 34886.01 |
| August | 0.418950E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110871E+09 | 21096.98 |
| September | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 73560499.44 | 5380.17 |
| October | 0.430920E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 35790845.07 | 2991202.08 |
| November | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8494394.85 | 17437227.84 |
| December | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 63059.45 | 74578570.42 |
| Annual Sum or Average | 0.505732E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.893426E+09 | 0.307906E+09 |
| Minimum of Months | 0.389025E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5380.17 |
| Maximum of Months | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.202254E+09 | 89275814.47 |
Report: SpaceGainsMonthly
For: G NW APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79610535.81 |
| February | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2279577.88 | 78746423.99 |
| March | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30404718.47 | 37498569.41 |
| April | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115354E+09 | 1845331.68 |
| May | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.202254E+09 | 173219.24 |
| June | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.145173E+09 | 47917.05 |
| July | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.169182E+09 | 34886.03 |
| August | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110871E+09 | 21097.02 |
| September | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 73560485.87 | 5380.17 |
| October | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 35790839.87 | 2991199.87 |
| November | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8494414.60 | 17365230.81 |
| December | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 63064.07 | 70946958.57 |
| Annual Sum or Average | 0.512427E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.893426E+09 | 0.289287E+09 |
| Minimum of Months | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5380.17 |
| Maximum of Months | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.202254E+09 | 79610535.81 |
Report: SpaceGainsMonthly
For: OFFICE
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.227408E+09 | 0.609777E+09 | 0.787690E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100766E+09 |
| February | 0.216037E+09 | 0.564682E+09 | 0.723971E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1724857.59 | 0.107611E+09 |
| March | 0.261519E+09 | 0.654405E+09 | 0.827804E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17728562.61 | 67775119.99 |
| April | 0.227408E+09 | 0.599704E+09 | 0.770907E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 79413739.60 | 13139015.80 |
| May | 0.250148E+09 | 0.639529E+09 | 0.814432E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138424E+09 | 8022221.04 |
| June | 0.250148E+09 | 0.629456E+09 | 0.797650E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102501E+09 | 5313154.88 |
| July | 0.227408E+09 | 0.609777E+09 | 0.787690E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 97060177.62 | 5451383.22 |
| August | 0.261519E+09 | 0.654405E+09 | 0.827804E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 64305803.14 | 7300332.20 |
| September | 0.227408E+09 | 0.599704E+09 | 0.770907E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 46489922.80 | 10843447.36 |
| October | 0.238778E+09 | 0.624653E+09 | 0.801061E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 24251891.30 | 10855492.87 |
| November | 0.227408E+09 | 0.599704E+09 | 0.770907E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5359863.93 | 27318778.77 |
| December | 0.227408E+09 | 0.609777E+09 | 0.787690E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 37156.21 | 85803681.20 |
| Annual Sum or Average | 0.284259E+10 | 0.739557E+10 | 0.946851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.577297E+09 | 0.450199E+09 |
| Minimum of Months | 0.216037E+09 | 0.564682E+09 | 0.723971E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5313154.88 |
| Maximum of Months | 0.261519E+09 | 0.654405E+09 | 0.827804E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138424E+09 | 0.107611E+09 |
Report: SpaceGainsMonthly
For: G NE APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80144235.71 |
| February | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2279580.53 | 79659497.38 |
| March | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30404725.54 | 37636152.31 |
| April | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115354E+09 | 1845331.35 |
| May | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.202254E+09 | 173219.16 |
| June | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.145173E+09 | 47917.04 |
| July | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.169182E+09 | 34886.00 |
| August | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110871E+09 | 21096.98 |
| September | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 73560495.06 | 5380.16 |
| October | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 35790841.91 | 2991200.53 |
| November | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8494415.70 | 17386955.65 |
| December | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 63064.27 | 71376753.72 |
| Annual Sum or Average | 0.512427E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.893426E+09 | 0.291323E+09 |
| Minimum of Months | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5380.16 |
| Maximum of Months | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.202254E+09 | 80144235.71 |
Report: SpaceGainsMonthly
For: G N1 APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49984431.18 |
| February | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1374989.50 | 49531462.81 |
| March | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18339377.42 | 22951844.87 |
| April | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 69578447.84 | 1113056.71 |
| May | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121994E+09 | 104481.24 |
| June | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 87564521.70 | 28902.31 |
| July | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102046E+09 | 21042.27 |
| August | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 66874845.32 | 12725.24 |
| September | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 44369832.39 | 3245.15 |
| October | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21588133.94 | 1804214.18 |
| November | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5123624.59 | 10504150.27 |
| December | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 38038.95 | 44125641.27 |
| Annual Sum or Average | 0.512427E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.538892E+09 | 0.180185E+09 |
| Minimum of Months | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3245.15 |
| Maximum of Months | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121994E+09 | 49984431.18 |
Report: SpaceGainsMonthly
For: G N2 APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50016253.83 |
| February | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1374989.39 | 49566169.40 |
| March | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18339375.17 | 22953304.84 |
| April | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 69578447.21 | 1113056.70 |
| May | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121994E+09 | 104481.24 |
| June | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 87564521.85 | 28902.31 |
| July | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102046E+09 | 21042.27 |
| August | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 66874845.39 | 12725.24 |
| September | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 44369832.65 | 3245.15 |
| October | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21588133.97 | 1804214.18 |
| November | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5123624.58 | 10504306.67 |
| December | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 38038.93 | 44139842.03 |
| Annual Sum or Average | 0.512427E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.538892E+09 | 0.180268E+09 |
| Minimum of Months | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3245.15 |
| Maximum of Months | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121994E+09 | 50016253.83 |
Report: SpaceGainsMonthly
For: G S1 APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54895427.72 |
| February | 0.389025E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1374974.12 | 51651075.19 |
| March | 0.418950E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18339357.97 | 23094948.04 |
| April | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 69578448.80 | 1113056.46 |
| May | 0.424935E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121994E+09 | 104481.16 |
| June | 0.406980E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 87564522.74 | 28902.26 |
| July | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102046E+09 | 21042.25 |
| August | 0.418950E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 66874850.61 | 12725.20 |
| September | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 44369840.99 | 3245.15 |
| October | 0.430920E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21588137.29 | 1804215.49 |
| November | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5123617.84 | 10517751.59 |
| December | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 38036.67 | 45541173.25 |
| Annual Sum or Average | 0.505732E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.538892E+09 | 0.188788E+09 |
| Minimum of Months | 0.389025E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3245.15 |
| Maximum of Months | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121994E+09 | 54895427.72 |
Report: SpaceGainsMonthly
For: G S2 APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54974309.50 |
| February | 0.389025E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1374973.55 | 51808456.46 |
| March | 0.418950E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18339355.97 | 23110953.68 |
| April | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 69578448.51 | 1113056.56 |
| May | 0.424935E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121994E+09 | 104481.24 |
| June | 0.406980E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 87564525.96 | 28902.09 |
| July | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102046E+09 | 21042.25 |
| August | 0.418950E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 66874854.91 | 12725.10 |
| September | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 44369843.46 | 3245.15 |
| October | 0.430920E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21588137.68 | 1804216.20 |
| November | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5123617.48 | 10517752.90 |
| December | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 38036.58 | 45584798.71 |
| Annual Sum or Average | 0.505732E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.538892E+09 | 0.189084E+09 |
| Minimum of Months | 0.389025E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3245.15 |
| Maximum of Months | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121994E+09 | 54974309.50 |
Report: SpaceGainsMonthly
For: M SW APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128831E+09 |
| February | 0.389025E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3219356.66 | 0.121386E+09 |
| March | 0.418950E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 43439519.81 | 55283199.41 |
| April | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.165362E+09 | 2685585.46 |
| May | 0.424935E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.290059E+09 | 255002.82 |
| June | 0.406980E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.208213E+09 | 72454.44 |
| July | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.242498E+09 | 51844.81 |
| August | 0.418950E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.158845E+09 | 32325.85 |
| September | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105351E+09 | 8337.83 |
| October | 0.430920E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 51257599.16 | 4338882.15 |
| November | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12121048.42 | 25106106.04 |
| December | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 85294.50 | 0.105702E+09 |
| Annual Sum or Average | 0.505732E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128045E+10 | 0.443753E+09 |
| Minimum of Months | 0.389025E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8337.83 |
| Maximum of Months | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.290059E+09 | 0.128831E+09 |
Report: SpaceGainsMonthly
For: M NW APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.117451E+09 |
| February | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3219384.60 | 0.118007E+09 |
| March | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 43439546.13 | 55014219.41 |
| April | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.165362E+09 | 2685585.32 |
| May | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.290059E+09 | 255002.94 |
| June | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.208213E+09 | 72454.52 |
| July | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.242498E+09 | 51844.85 |
| August | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.158845E+09 | 32325.90 |
| September | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105351E+09 | 8337.81 |
| October | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 51257596.26 | 4337909.78 |
| November | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12121071.95 | 24715993.47 |
| December | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 99406.68 | 99007237.26 |
| Annual Sum or Average | 0.512427E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128046E+10 | 0.421638E+09 |
| Minimum of Months | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8337.81 |
| Maximum of Months | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.290059E+09 | 0.118007E+09 |
Report: SpaceGainsMonthly
For: M SE APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129349E+09 |
| February | 0.389025E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3219360.59 | 0.121611E+09 |
| March | 0.418950E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 43439530.10 | 55319142.83 |
| April | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.165362E+09 | 2685584.82 |
| May | 0.424935E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.290059E+09 | 255002.72 |
| June | 0.406980E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.208213E+09 | 72454.42 |
| July | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.242498E+09 | 51844.77 |
| August | 0.418950E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.158845E+09 | 32325.79 |
| September | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105351E+09 | 8337.81 |
| October | 0.430920E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 51257604.10 | 4338883.86 |
| November | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12121052.46 | 25107919.61 |
| December | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 85295.05 | 0.105971E+09 |
| Annual Sum or Average | 0.505732E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128045E+10 | 0.444802E+09 |
| Minimum of Months | 0.389025E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8337.81 |
| Maximum of Months | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.290059E+09 | 0.129349E+09 |
Report: SpaceGainsMonthly
For: M NE APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118520E+09 |
| February | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3219387.63 | 0.119095E+09 |
| March | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 43439560.32 | 55152980.92 |
| April | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.165362E+09 | 2685584.68 |
| May | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.290059E+09 | 255002.84 |
| June | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.208213E+09 | 72454.50 |
| July | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.242498E+09 | 51844.80 |
| August | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.158845E+09 | 32325.84 |
| September | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105351E+09 | 8337.80 |
| October | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 51257597.90 | 4337853.06 |
| November | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12121075.67 | 24821360.33 |
| December | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 94523.72 | 99811704.67 |
| Annual Sum or Average | 0.512427E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128046E+10 | 0.424845E+09 |
| Minimum of Months | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8337.80 |
| Maximum of Months | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.290059E+09 | 0.119095E+09 |
Report: SpaceGainsMonthly
For: M N1 APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74693207.28 |
| February | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1941861.66 | 73591130.81 |
| March | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26201673.03 | 33360706.11 |
| April | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 99742218.37 | 1619875.88 |
| May | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.174957E+09 | 153810.95 |
| June | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125589E+09 | 43702.68 |
| July | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.146268E+09 | 31271.34 |
| August | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 95811138.83 | 19498.19 |
| September | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 63544886.11 | 5029.12 |
| October | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30917294.27 | 2617064.33 |
| November | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7311138.40 | 15124155.36 |
| December | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 51497.95 | 62820835.27 |
| Annual Sum or Average | 0.512427E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.772336E+09 | 0.264080E+09 |
| Minimum of Months | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5029.12 |
| Maximum of Months | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.174957E+09 | 74693207.28 |
Report: SpaceGainsMonthly
For: M N2 APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74750022.06 |
| February | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1941861.57 | 73614253.47 |
| March | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26201671.35 | 33361596.49 |
| April | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 99742218.57 | 1619875.87 |
| May | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.174957E+09 | 153810.95 |
| June | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125589E+09 | 43702.68 |
| July | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.146268E+09 | 31271.34 |
| August | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 95811139.10 | 19498.19 |
| September | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 63544886.15 | 5029.12 |
| October | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30917294.30 | 2617063.40 |
| November | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7311138.35 | 15124779.61 |
| December | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 51453.38 | 62845762.67 |
| Annual Sum or Average | 0.512427E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.772335E+09 | 0.264187E+09 |
| Minimum of Months | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5029.12 |
| Maximum of Months | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.174957E+09 | 74750022.06 |
Report: SpaceGainsMonthly
For: M S1 APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79281177.84 |
| February | 0.389025E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1941845.62 | 74687337.29 |
| March | 0.418950E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26201652.52 | 33397621.51 |
| April | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 99742224.08 | 1619875.73 |
| May | 0.424935E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.174957E+09 | 153810.85 |
| June | 0.406980E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125589E+09 | 43702.62 |
| July | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.146268E+09 | 31271.31 |
| August | 0.418950E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 95811145.78 | 19498.15 |
| September | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 63544896.98 | 5029.12 |
| October | 0.430920E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30917295.94 | 2617102.06 |
| November | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7311124.72 | 15174077.80 |
| December | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 51448.74 | 65265263.12 |
| Annual Sum or Average | 0.505732E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.772335E+09 | 0.272296E+09 |
| Minimum of Months | 0.389025E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5029.12 |
| Maximum of Months | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.174957E+09 | 79281177.84 |
Report: SpaceGainsMonthly
For: M S2 APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79283375.77 |
| February | 0.389025E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1941845.68 | 74686511.01 |
| March | 0.418950E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26201652.71 | 33397668.17 |
| April | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 99742224.25 | 1619875.72 |
| May | 0.424935E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.174957E+09 | 153810.85 |
| June | 0.406980E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125589E+09 | 43702.62 |
| July | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.146268E+09 | 31271.31 |
| August | 0.418950E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 95811146.17 | 19498.15 |
| September | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 63544897.05 | 5029.12 |
| October | 0.430920E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30917296.02 | 2617102.07 |
| November | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7311124.79 | 15174063.25 |
| December | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 51448.75 | 65265212.12 |
| Annual Sum or Average | 0.505732E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.772335E+09 | 0.272297E+09 |
| Minimum of Months | 0.389025E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5029.12 |
| Maximum of Months | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.174957E+09 | 79283375.77 |
Report: SpaceGainsMonthly
For: T SW APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.152034E+09 |
| February | 0.389025E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4111431.62 | 0.140745E+09 |
| March | 0.418950E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 56791910.44 | 68783969.01 |
| April | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.217656E+09 | 3575534.84 |
| May | 0.424935E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.382117E+09 | 353470.15 |
| June | 0.406980E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.274335E+09 | 105743.65 |
| July | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.319108E+09 | 73191.94 |
| August | 0.418950E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.208833E+09 | 48076.42 |
| September | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138402E+09 | 12919.39 |
| October | 0.430920E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 67336599.98 | 5722628.04 |
| November | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15806758.52 | 29708651.63 |
| December | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 99233.80 | 0.122619E+09 |
| Annual Sum or Average | 0.505732E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.168460E+10 | 0.523782E+09 |
| Minimum of Months | 0.389025E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12919.39 |
| Maximum of Months | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.382117E+09 | 0.152034E+09 |
Report: SpaceGainsMonthly
For: T NW APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.135639E+09 |
| February | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4111482.43 | 0.133097E+09 |
| March | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 56791952.43 | 67066687.23 |
| April | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.217656E+09 | 3566437.77 |
| May | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.382116E+09 | 353470.30 |
| June | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.274335E+09 | 105743.77 |
| July | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.319108E+09 | 73191.98 |
| August | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.208833E+09 | 48076.47 |
| September | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138402E+09 | 12919.37 |
| October | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 67336588.44 | 5643393.52 |
| November | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15825950.27 | 27376018.14 |
| December | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 104250.18 | 0.110282E+09 |
| Annual Sum or Average | 0.512427E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.168462E+10 | 0.483265E+09 |
| Minimum of Months | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12919.37 |
| Maximum of Months | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.382116E+09 | 0.135639E+09 |
Report: SpaceGainsMonthly
For: T SE APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.153990E+09 |
| February | 0.389025E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4111439.83 | 0.142464E+09 |
| March | 0.418950E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 56791916.98 | 69359716.05 |
| April | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.217656E+09 | 3585474.77 |
| May | 0.424935E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.382117E+09 | 353469.98 |
| June | 0.406980E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.274335E+09 | 105743.59 |
| July | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.319108E+09 | 73191.87 |
| August | 0.418950E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.208833E+09 | 48076.33 |
| September | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138402E+09 | 12919.36 |
| October | 0.430920E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 67336609.77 | 5733634.00 |
| November | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15806754.68 | 30067663.92 |
| December | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 99234.78 | 0.123854E+09 |
| Annual Sum or Average | 0.505732E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.168460E+10 | 0.529648E+09 |
| Minimum of Months | 0.389025E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12919.36 |
| Maximum of Months | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.382117E+09 | 0.153990E+09 |
Report: SpaceGainsMonthly
For: T NE APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136057E+09 |
| February | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4111487.06 | 0.136174E+09 |
| March | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 56791966.42 | 68047811.68 |
| April | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.217656E+09 | 3576960.11 |
| May | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.382117E+09 | 353470.13 |
| June | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.274335E+09 | 105743.71 |
| July | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.319108E+09 | 73191.91 |
| August | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.208833E+09 | 48076.38 |
| September | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138402E+09 | 12919.34 |
| October | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 67336592.82 | 5672124.05 |
| November | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15806806.23 | 28298700.10 |
| December | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 99259.46 | 0.111472E+09 |
| Annual Sum or Average | 0.512427E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.168460E+10 | 0.489892E+09 |
| Minimum of Months | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12919.34 |
| Maximum of Months | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.382117E+09 | 0.136174E+09 |
Report: SpaceGainsMonthly
For: T N1 APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82609994.32 |
| February | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2479961.31 | 83734926.93 |
| March | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34255519.90 | 42038507.39 |
| April | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131284E+09 | 2181000.89 |
| May | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.230483E+09 | 213203.98 |
| June | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.165472E+09 | 63781.73 |
| July | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.192478E+09 | 44147.36 |
| August | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125963E+09 | 28998.47 |
| September | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 83480319.69 | 7792.60 |
| October | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 40615737.26 | 3470949.54 |
| November | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9539785.12 | 17530869.74 |
| December | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 73213.47 | 67957778.34 |
| Annual Sum or Average | 0.512427E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101613E+10 | 0.299882E+09 |
| Minimum of Months | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7792.60 |
| Maximum of Months | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.230483E+09 | 83734926.93 |
Report: SpaceGainsMonthly
For: T N2 APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82679138.61 |
| February | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2479960.87 | 83842387.36 |
| March | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34255519.58 | 42053858.55 |
| April | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131284E+09 | 2180757.67 |
| May | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.230483E+09 | 213203.98 |
| June | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.165472E+09 | 63781.74 |
| July | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.192478E+09 | 44147.35 |
| August | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125963E+09 | 28998.46 |
| September | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 83480320.08 | 7792.60 |
| October | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 40615737.35 | 3470804.39 |
| November | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9538524.69 | 17548168.49 |
| December | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 70988.09 | 68015924.57 |
| Annual Sum or Average | 0.512427E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101612E+10 | 0.300149E+09 |
| Minimum of Months | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7792.60 |
| Maximum of Months | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.230483E+09 | 83842387.36 |
Report: SpaceGainsMonthly
For: T S1 APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94986796.72 |
| February | 0.389025E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2479927.54 | 88725227.45 |
| March | 0.418950E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34255486.70 | 42904859.18 |
| April | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131285E+09 | 2184412.39 |
| May | 0.424935E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.230483E+09 | 213203.88 |
| June | 0.406980E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.165472E+09 | 63781.66 |
| July | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.192478E+09 | 44147.33 |
| August | 0.418950E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125963E+09 | 28998.43 |
| September | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 83480339.33 | 7792.61 |
| October | 0.430920E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 40615743.90 | 3497092.43 |
| November | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9534252.29 | 18801393.29 |
| December | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 59857.07 | 76842677.05 |
| Annual Sum or Average | 0.505732E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101611E+10 | 0.328300E+09 |
| Minimum of Months | 0.389025E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7792.61 |
| Maximum of Months | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.230483E+09 | 94986796.72 |
Report: SpaceGainsMonthly
For: T S2 APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 95041095.08 |
| February | 0.389025E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2479927.70 | 88750865.45 |
| March | 0.418950E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34255488.84 | 42908799.48 |
| April | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131285E+09 | 2184296.59 |
| May | 0.424935E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.230483E+09 | 213203.87 |
| June | 0.406980E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.165472E+09 | 63781.66 |
| July | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.192478E+09 | 44147.33 |
| August | 0.418950E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125963E+09 | 28998.43 |
| September | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 83480340.05 | 7792.61 |
| October | 0.430920E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 40615744.20 | 3496939.70 |
| November | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9534258.98 | 18801854.46 |
| December | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 59857.08 | 76860135.74 |
| Annual Sum or Average | 0.505732E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101611E+10 | 0.328402E+09 |
| Minimum of Months | 0.389025E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7792.61 |
| Maximum of Months | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.230483E+09 | 95041095.08 |
Report: SpaceGainsMonthly
For: T CORRIDOR
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.727675E+09 | 0.992689E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26833029.64 |
| February | 0.657255E+09 | 0.896622E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 95868.67 | 28834122.54 |
| March | 0.727675E+09 | 0.992689E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4566381.68 | 17380051.38 |
| April | 0.704201E+09 | 0.960667E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24865172.49 | 1484480.43 |
| May | 0.727675E+09 | 0.992689E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46198558.70 | 512246.31 |
| June | 0.704201E+09 | 0.960667E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33535836.19 | 330855.11 |
| July | 0.727675E+09 | 0.992689E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34756127.45 | 105286.58 |
| August | 0.727675E+09 | 0.992689E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21257426.41 | 228178.22 |
| September | 0.704201E+09 | 0.960667E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13883914.97 | 438820.70 |
| October | 0.727675E+09 | 0.992689E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6986979.49 | 1892189.60 |
| November | 0.704201E+09 | 0.960667E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1300077.77 | 6121457.20 |
| December | 0.727675E+09 | 0.992689E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7328.03 | 22212290.36 |
| Annual Sum or Average | 0.856778E+10 | 0.116881E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.187454E+09 | 0.106373E+09 |
| Minimum of Months | 0.657255E+09 | 0.896622E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 105286.58 |
| Maximum of Months | 0.727675E+09 | 0.992689E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46198558.70 | 28834122.54 |
Report: SpaceGainsMonthly
For: G CORRIDOR
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.727675E+09 | 0.992689E+09 | 0.299778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.194192E+10 |
| February | 0.657255E+09 | 0.896622E+09 | 0.270767E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2373422.28 | 0.123218E+10 |
| March | 0.727675E+09 | 0.992689E+09 | 0.299778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.173326E+09 | 0.653246E+09 |
| April | 0.704201E+09 | 0.960667E+09 | 0.290107E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.778701E+09 | 0.151937E+09 |
| May | 0.727675E+09 | 0.992689E+09 | 0.299778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129924E+10 | 20097619.36 |
| June | 0.704201E+09 | 0.960667E+09 | 0.290107E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127312E+10 | 15628931.45 |
| July | 0.727675E+09 | 0.992689E+09 | 0.299778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.866140E+09 | 5584993.70 |
| August | 0.727675E+09 | 0.992689E+09 | 0.299778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.601218E+09 | 24936177.11 |
| September | 0.704201E+09 | 0.960667E+09 | 0.290107E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.454213E+09 | 72105147.00 |
| October | 0.727675E+09 | 0.992689E+09 | 0.299778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.316687E+09 | 0.424223E+09 |
| November | 0.704201E+09 | 0.960667E+09 | 0.290107E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 40992467.12 | 0.100467E+10 |
| December | 0.727675E+09 | 0.992689E+09 | 0.299778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.184758E+10 |
| Annual Sum or Average | 0.856778E+10 | 0.116881E+11 | 0.352964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.580601E+10 | 0.739412E+10 |
| Minimum of Months | 0.657255E+09 | 0.896622E+09 | 0.270767E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5584993.70 |
| Maximum of Months | 0.727675E+09 | 0.992689E+09 | 0.299778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129924E+10 | 0.194192E+10 |
Report: SpaceGainsMonthly
For: M CORRIDOR
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.727675E+09 | 0.992689E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25644976.41 |
| February | 0.657255E+09 | 0.896622E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35079.07 | 27104849.90 |
| March | 0.727675E+09 | 0.992689E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3861022.85 | 14892614.29 |
| April | 0.704201E+09 | 0.960667E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20600597.53 | 1315058.23 |
| May | 0.727675E+09 | 0.992689E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37912891.96 | 405740.94 |
| June | 0.704201E+09 | 0.960667E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27638861.93 | 250043.32 |
| July | 0.727675E+09 | 0.992689E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29387822.30 | 80210.85 |
| August | 0.727675E+09 | 0.992689E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18098122.21 | 130162.37 |
| September | 0.704201E+09 | 0.960667E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11670420.98 | 322658.11 |
| October | 0.727675E+09 | 0.992689E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5751834.80 | 1616678.17 |
| November | 0.704201E+09 | 0.960667E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 862609.88 | 5952615.94 |
| December | 0.727675E+09 | 0.992689E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21607294.42 |
| Annual Sum or Average | 0.856778E+10 | 0.116881E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.155819E+09 | 99322902.95 |
| Minimum of Months | 0.657255E+09 | 0.896622E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80210.85 |
| Maximum of Months | 0.727675E+09 | 0.992689E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37912891.96 | 27104849.90 |
Report: PeakSpaceGainsMonthly
For: G SW APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 181.31 | 31-JAN-08:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 30.72 | 19-FEB-15:00 | 219.33 | 18-FEB-08:00 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 152.98 | 27-MAR-15:00 | 306.73 | 24-MAR-24:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 391.06 | 15-APR-14:00 | 34.55 | 10-APR-06:00 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 405.67 | 05-MAY-15:00 | 10.30 | 13-MAY-05:00 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 421.36 | 06-JUN-15:00 | 7.04 | 18-JUN-05:00 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 245.86 | 19-JUL-12:00 | 6.88 | 19-JUL-03:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 177.54 | 31-AUG-11:00 | 5.41 | 15-AUG-24:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 180.26 | 19-SEP-13:00 | 0.94 | 27-SEP-06:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 194.16 | 03-OCT-15:00 | 31.89 | 12-OCT-03:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 70.39 | 13-NOV-14:00 | 82.25 | 28-NOV-06:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 28-DEC-14:00 | 191.23 | 29-DEC-24:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.94 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 421.36 | 306.73 |
Report: PeakSpaceGainsMonthly
For: G NW APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 167.88 | 31-JAN-08:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 30.72 | 19-FEB-15:00 | 207.67 | 18-FEB-08:00 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 152.98 | 27-MAR-15:00 | 300.67 | 24-MAR-24:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 391.06 | 15-APR-14:00 | 34.55 | 10-APR-06:00 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 405.67 | 05-MAY-15:00 | 10.30 | 13-MAY-05:00 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 421.36 | 06-JUN-15:00 | 7.04 | 18-JUN-05:00 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 245.86 | 19-JUL-12:00 | 6.88 | 19-JUL-03:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 177.54 | 31-AUG-11:00 | 5.41 | 15-AUG-24:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 180.26 | 19-SEP-13:00 | 0.94 | 27-SEP-06:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 194.16 | 03-OCT-15:00 | 31.89 | 12-OCT-03:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 70.39 | 13-NOV-14:00 | 82.13 | 28-NOV-05:40 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 28-DEC-14:00 | 184.24 | 29-DEC-24:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.94 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 421.36 | 300.67 |
Report: PeakSpaceGainsMonthly
For: OFFICE
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 451.21 | 03-JAN-08:09 | 582.92 | 03-JAN-08:09 | 588.62 | 03-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 193.91 | 31-JAN-08:10 |
| February | 451.21 | 01-FEB-08:09 | 582.92 | 01-FEB-08:09 | 588.62 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 27.47 | 21-FEB-15:00 | 238.56 | 18-FEB-08:00 |
| March | 451.21 | 01-MAR-08:09 | 582.92 | 01-MAR-08:09 | 588.62 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 152.98 | 27-MAR-15:00 | 414.68 | 24-MAR-24:00 |
| April | 451.21 | 03-APR-07:10 | 582.92 | 03-APR-07:10 | 588.62 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 356.84 | 27-APR-15:00 | 116.98 | 22-APR-18:00 |
| May | 451.21 | 01-MAY-07:10 | 582.92 | 01-MAY-07:10 | 588.62 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 405.67 | 05-MAY-15:00 | 69.08 | 15-MAY-03:00 |
| June | 451.21 | 01-JUN-07:10 | 582.92 | 01-JUN-07:10 | 588.62 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 421.36 | 06-JUN-15:00 | 94.38 | 24-JUN-11:00 |
| July | 451.21 | 03-JUL-07:10 | 582.92 | 03-JUL-07:10 | 588.62 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 245.80 | 19-JUL-12:00 | 54.66 | 26-JUL-06:00 |
| August | 451.21 | 01-AUG-07:10 | 582.92 | 01-AUG-07:10 | 588.62 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 177.50 | 31-AUG-11:00 | 52.81 | 15-AUG-23:00 |
| September | 451.21 | 01-SEP-07:10 | 582.92 | 01-SEP-07:10 | 588.62 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 180.23 | 19-SEP-13:00 | 40.85 | 08-SEP-21:00 |
| October | 451.21 | 02-OCT-07:10 | 582.92 | 02-OCT-07:10 | 588.62 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 194.15 | 03-OCT-15:00 | 74.86 | 12-OCT-03:00 |
| November | 451.21 | 01-NOV-07:10 | 582.92 | 01-NOV-07:10 | 588.62 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 47.62 | 10-NOV-14:00 | 103.60 | 28-NOV-05:00 |
| December | 451.21 | 01-DEC-08:09 | 582.92 | 01-DEC-08:09 | 588.62 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 28-DEC-14:00 | 217.79 | 29-DEC-18:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 451.21 | 582.92 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.85 | |||||
| Maximum of Months | 451.21 | 582.92 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 421.36 | 414.68 |
Report: PeakSpaceGainsMonthly
For: G NE APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 169.51 | 31-JAN-08:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 30.72 | 19-FEB-15:00 | 210.25 | 18-FEB-08:00 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 152.98 | 27-MAR-15:00 | 297.90 | 24-MAR-24:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 391.06 | 15-APR-14:00 | 34.55 | 10-APR-06:00 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 405.67 | 05-MAY-15:00 | 10.30 | 13-MAY-05:00 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 421.36 | 06-JUN-15:00 | 7.04 | 18-JUN-05:00 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 245.86 | 19-JUL-12:00 | 6.88 | 19-JUL-03:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 177.54 | 31-AUG-11:00 | 5.41 | 15-AUG-24:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 180.26 | 19-SEP-13:00 | 0.94 | 27-SEP-06:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 194.16 | 03-OCT-15:00 | 31.89 | 12-OCT-03:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 70.39 | 13-NOV-14:00 | 82.13 | 28-NOV-05:50 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 28-DEC-14:00 | 184.31 | 29-DEC-24:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.94 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 421.36 | 297.90 |
Report: PeakSpaceGainsMonthly
For: G N1 APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 106.16 | 31-JAN-08:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.53 | 19-FEB-15:00 | 131.96 | 18-FEB-08:00 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 92.27 | 27-MAR-15:00 | 185.01 | 24-MAR-24:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 235.88 | 15-APR-14:00 | 20.84 | 10-APR-06:00 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 244.69 | 05-MAY-15:00 | 6.21 | 13-MAY-05:00 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 254.16 | 06-JUN-15:00 | 4.25 | 18-JUN-05:00 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 148.29 | 19-JUL-12:00 | 4.15 | 19-JUL-03:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 107.09 | 31-AUG-11:00 | 3.26 | 15-AUG-24:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 108.73 | 19-SEP-13:00 | 0.57 | 27-SEP-06:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 117.11 | 03-OCT-15:00 | 19.23 | 12-OCT-03:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 42.45 | 13-NOV-14:00 | 49.61 | 28-NOV-06:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.82 | 28-DEC-14:00 | 116.07 | 29-DEC-24:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.57 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 254.16 | 185.01 |
Report: PeakSpaceGainsMonthly
For: G N2 APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 106.21 | 31-JAN-08:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.53 | 19-FEB-15:00 | 132.04 | 18-FEB-08:00 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 92.27 | 27-MAR-15:00 | 185.01 | 24-MAR-24:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 235.88 | 15-APR-14:00 | 20.84 | 10-APR-06:00 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 244.69 | 05-MAY-15:00 | 6.21 | 13-MAY-05:00 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 254.16 | 06-JUN-15:00 | 4.25 | 18-JUN-05:00 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 148.29 | 19-JUL-12:00 | 4.15 | 19-JUL-03:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 107.09 | 31-AUG-11:00 | 3.26 | 15-AUG-24:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 108.73 | 19-SEP-13:00 | 0.57 | 27-SEP-06:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 117.11 | 03-OCT-15:00 | 19.23 | 12-OCT-03:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 42.45 | 13-NOV-14:00 | 49.61 | 28-NOV-06:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.82 | 28-DEC-14:00 | 116.09 | 29-DEC-24:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.57 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 254.16 | 185.01 |
Report: PeakSpaceGainsMonthly
For: G S1 APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 114.36 | 31-JAN-08:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.53 | 19-FEB-15:00 | 138.66 | 18-FEB-08:00 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 92.27 | 27-MAR-15:00 | 185.01 | 24-MAR-24:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 235.88 | 15-APR-14:00 | 20.84 | 10-APR-06:00 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 244.69 | 05-MAY-15:00 | 6.21 | 13-MAY-05:00 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 254.16 | 06-JUN-15:00 | 4.25 | 18-JUN-05:00 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 148.29 | 19-JUL-12:00 | 4.15 | 19-JUL-03:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 107.09 | 31-AUG-11:00 | 3.26 | 15-AUG-24:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 108.73 | 19-SEP-13:00 | 0.57 | 27-SEP-06:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 117.11 | 03-OCT-15:00 | 19.23 | 12-OCT-03:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 42.45 | 13-NOV-14:00 | 49.61 | 28-NOV-06:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.82 | 28-DEC-14:00 | 116.92 | 29-DEC-24:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.57 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 254.16 | 185.01 |
Report: PeakSpaceGainsMonthly
For: G S2 APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 114.77 | 31-JAN-08:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.53 | 19-FEB-15:00 | 139.42 | 18-FEB-08:00 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 92.27 | 27-MAR-15:00 | 185.01 | 24-MAR-24:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 235.88 | 15-APR-14:00 | 20.84 | 10-APR-06:00 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 244.69 | 05-MAY-15:00 | 6.21 | 13-MAY-05:00 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 254.16 | 06-JUN-15:00 | 4.25 | 18-JUN-05:00 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 148.29 | 19-JUL-12:00 | 4.15 | 19-JUL-03:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 107.09 | 31-AUG-11:00 | 3.26 | 15-AUG-24:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 108.73 | 19-SEP-13:00 | 0.57 | 27-SEP-06:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 117.11 | 03-OCT-15:00 | 19.23 | 12-OCT-03:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 42.45 | 13-NOV-14:00 | 49.61 | 28-NOV-06:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.82 | 28-DEC-14:00 | 116.92 | 29-DEC-24:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.57 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 254.16 | 185.01 |
Report: PeakSpaceGainsMonthly
For: M SW APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 259.31 | 31-JAN-08:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 43.71 | 19-FEB-15:00 | 317.80 | 18-FEB-08:00 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 219.37 | 27-MAR-15:00 | 442.69 | 24-MAR-24:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 561.29 | 15-APR-14:00 | 49.84 | 10-APR-06:02 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 582.37 | 05-MAY-15:00 | 15.03 | 13-MAY-05:00 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 604.93 | 06-JUN-15:00 | 10.41 | 18-JUN-05:00 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 352.52 | 19-JUL-12:00 | 10.14 | 19-JUL-03:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 254.46 | 31-AUG-11:00 | 8.03 | 15-AUG-24:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 258.43 | 19-SEP-13:00 | 1.40 | 27-SEP-06:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 278.54 | 03-OCT-15:00 | 46.13 | 12-OCT-03:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 100.67 | 13-NOV-14:00 | 118.46 | 28-NOV-06:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.80 | 28-DEC-14:00 | 263.22 | 29-DEC-24:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.40 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 604.93 | 442.69 |
Report: PeakSpaceGainsMonthly
For: M NW APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 242.28 | 31-JAN-08:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 43.71 | 19-FEB-15:00 | 306.97 | 18-FEB-08:00 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 219.37 | 27-MAR-15:00 | 442.69 | 24-MAR-24:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 561.29 | 15-APR-14:00 | 49.84 | 10-APR-06:02 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 582.37 | 05-MAY-15:00 | 15.03 | 13-MAY-05:00 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 604.93 | 06-JUN-15:00 | 10.41 | 18-JUN-05:00 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 352.52 | 19-JUL-12:00 | 10.14 | 19-JUL-03:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 254.46 | 31-AUG-11:00 | 8.03 | 15-AUG-24:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 258.43 | 19-SEP-13:00 | 1.40 | 27-SEP-06:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 278.54 | 03-OCT-15:00 | 46.13 | 12-OCT-03:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 100.67 | 13-NOV-14:00 | 113.95 | 28-NOV-05:30 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.65 | 24-DEC-14:00 | 255.76 | 29-DEC-24:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.40 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 604.93 | 442.69 |
Report: PeakSpaceGainsMonthly
For: M SE APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 262.19 | 31-JAN-08:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 43.71 | 19-FEB-15:00 | 321.43 | 18-FEB-08:00 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 219.37 | 27-MAR-15:00 | 442.69 | 24-MAR-24:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 561.29 | 15-APR-14:00 | 49.84 | 10-APR-06:02 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 582.37 | 05-MAY-15:00 | 15.03 | 13-MAY-05:00 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 604.93 | 06-JUN-15:00 | 10.41 | 18-JUN-05:00 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 352.52 | 19-JUL-12:00 | 10.14 | 19-JUL-03:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 254.46 | 31-AUG-11:00 | 8.03 | 15-AUG-24:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 258.43 | 19-SEP-13:00 | 1.40 | 27-SEP-06:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 278.54 | 03-OCT-15:00 | 46.13 | 12-OCT-03:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 100.67 | 13-NOV-14:00 | 118.51 | 28-NOV-06:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.80 | 28-DEC-14:00 | 263.06 | 29-DEC-24:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.40 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 604.93 | 442.69 |
Report: PeakSpaceGainsMonthly
For: M NE APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 245.17 | 31-JAN-08:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 43.71 | 19-FEB-15:00 | 310.89 | 18-FEB-08:00 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 219.37 | 27-MAR-15:00 | 442.69 | 24-MAR-24:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 561.29 | 15-APR-14:00 | 49.84 | 10-APR-06:02 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 582.37 | 05-MAY-15:00 | 15.03 | 13-MAY-05:00 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 604.93 | 06-JUN-15:00 | 10.41 | 18-JUN-05:00 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 352.52 | 19-JUL-12:00 | 10.14 | 19-JUL-03:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 254.46 | 31-AUG-11:00 | 8.03 | 15-AUG-24:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 258.43 | 19-SEP-13:00 | 1.40 | 27-SEP-06:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 278.54 | 03-OCT-15:00 | 46.13 | 12-OCT-03:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 100.67 | 13-NOV-14:00 | 113.94 | 28-NOV-05:30 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.80 | 28-DEC-14:00 | 255.73 | 29-DEC-24:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.40 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 604.93 | 442.69 |
Report: PeakSpaceGainsMonthly
For: M N1 APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 155.30 | 31-JAN-08:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 26.37 | 19-FEB-15:00 | 194.89 | 18-FEB-08:00 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 132.32 | 27-MAR-15:00 | 267.02 | 24-MAR-24:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 338.56 | 15-APR-14:00 | 30.06 | 10-APR-06:02 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 351.27 | 05-MAY-15:00 | 9.07 | 13-MAY-05:00 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 364.88 | 06-JUN-15:00 | 6.28 | 18-JUN-05:00 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 212.63 | 19-JUL-12:00 | 6.11 | 19-JUL-03:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 153.48 | 31-AUG-11:00 | 4.84 | 15-AUG-24:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 155.88 | 19-SEP-13:00 | 0.85 | 27-SEP-06:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 168.01 | 03-OCT-15:00 | 27.82 | 12-OCT-03:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 60.72 | 13-NOV-14:00 | 71.45 | 28-NOV-06:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.31 | 28-DEC-14:00 | 164.72 | 29-DEC-24:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.85 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 364.88 | 267.02 |
Report: PeakSpaceGainsMonthly
For: M N2 APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 155.37 | 31-JAN-08:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 26.37 | 19-FEB-15:00 | 194.93 | 18-FEB-08:00 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 132.32 | 27-MAR-15:00 | 267.02 | 24-MAR-24:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 338.56 | 15-APR-14:00 | 30.06 | 10-APR-06:02 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 351.27 | 05-MAY-15:00 | 9.07 | 13-MAY-05:00 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 364.88 | 06-JUN-15:00 | 6.28 | 18-JUN-05:00 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 212.63 | 19-JUL-12:00 | 6.11 | 19-JUL-03:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 153.48 | 31-AUG-11:00 | 4.84 | 15-AUG-24:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 155.88 | 19-SEP-13:00 | 0.85 | 27-SEP-06:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 168.01 | 03-OCT-15:00 | 27.82 | 12-OCT-03:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 60.72 | 13-NOV-14:00 | 71.45 | 28-NOV-06:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.31 | 28-DEC-14:00 | 164.73 | 29-DEC-24:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.85 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 364.88 | 267.02 |
Report: PeakSpaceGainsMonthly
For: M S1 APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 164.71 | 31-JAN-08:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 26.37 | 19-FEB-15:00 | 200.88 | 18-FEB-08:00 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 132.32 | 27-MAR-15:00 | 267.02 | 24-MAR-24:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 338.56 | 15-APR-14:00 | 30.06 | 10-APR-06:02 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 351.27 | 05-MAY-15:00 | 9.07 | 13-MAY-05:00 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 364.88 | 06-JUN-15:00 | 6.28 | 18-JUN-05:00 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 212.63 | 19-JUL-12:00 | 6.11 | 19-JUL-03:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 153.48 | 31-AUG-11:00 | 4.84 | 15-AUG-24:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 155.88 | 19-SEP-13:00 | 0.85 | 27-SEP-06:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 168.01 | 03-OCT-15:00 | 27.82 | 12-OCT-03:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 60.72 | 13-NOV-14:00 | 71.45 | 28-NOV-06:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.31 | 28-DEC-14:00 | 168.24 | 29-DEC-24:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.85 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 364.88 | 267.02 |
Report: PeakSpaceGainsMonthly
For: M S2 APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 164.73 | 31-JAN-08:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 26.37 | 19-FEB-15:00 | 200.89 | 18-FEB-08:00 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 132.32 | 27-MAR-15:00 | 267.02 | 24-MAR-24:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 338.56 | 15-APR-14:00 | 30.06 | 10-APR-06:02 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 351.27 | 05-MAY-15:00 | 9.07 | 13-MAY-05:00 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 364.88 | 06-JUN-15:00 | 6.28 | 18-JUN-05:00 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 212.63 | 19-JUL-12:00 | 6.11 | 19-JUL-03:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 153.48 | 31-AUG-11:00 | 4.84 | 15-AUG-24:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 155.88 | 19-SEP-13:00 | 0.85 | 27-SEP-06:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 168.01 | 03-OCT-15:00 | 27.82 | 12-OCT-03:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 60.72 | 13-NOV-14:00 | 71.45 | 28-NOV-06:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.31 | 28-DEC-14:00 | 168.23 | 29-DEC-24:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.85 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 364.88 | 267.02 |
Report: PeakSpaceGainsMonthly
For: T SW APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 313.63 | 31-JAN-08:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 56.66 | 19-FEB-15:00 | 340.75 | 18-FEB-08:00 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 288.94 | 27-MAR-15:00 | 535.01 | 24-MAR-23:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 740.64 | 15-APR-14:00 | 59.44 | 10-APR-06:10 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 768.76 | 05-MAY-15:00 | 20.48 | 13-MAY-05:00 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 798.62 | 06-JUN-15:00 | 14.53 | 18-JUN-05:00 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 464.20 | 19-JUL-12:00 | 14.06 | 19-JUL-03:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 334.81 | 31-AUG-11:00 | 11.30 | 15-AUG-24:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 340.23 | 19-SEP-13:00 | 2.00 | 27-SEP-06:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 367.16 | 03-OCT-15:00 | 61.82 | 12-OCT-03:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 131.90 | 13-NOV-14:00 | 138.09 | 29-NOV-24:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.84 | 28-DEC-14:00 | 308.15 | 31-DEC-15:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 798.62 | 535.01 |
Report: PeakSpaceGainsMonthly
For: T NW APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 313.63 | 31-JAN-08:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 56.66 | 19-FEB-15:00 | 340.75 | 18-FEB-08:00 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 288.94 | 27-MAR-15:00 | 520.27 | 24-MAR-23:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 740.64 | 15-APR-14:00 | 58.78 | 10-APR-06:10 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 768.76 | 05-MAY-15:00 | 20.48 | 13-MAY-05:00 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 798.62 | 06-JUN-15:00 | 14.53 | 18-JUN-05:00 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 464.20 | 19-JUL-12:00 | 14.06 | 19-JUL-03:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 334.81 | 31-AUG-11:00 | 11.30 | 15-AUG-24:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 340.23 | 19-SEP-13:00 | 2.00 | 27-SEP-06:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 367.16 | 03-OCT-15:00 | 61.82 | 12-OCT-03:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 131.90 | 13-NOV-14:00 | 129.89 | 29-NOV-24:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.84 | 28-DEC-14:00 | 266.55 | 29-DEC-24:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 798.62 | 520.27 |
Report: PeakSpaceGainsMonthly
For: T SE APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 313.63 | 31-JAN-08:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 56.66 | 19-FEB-15:00 | 340.75 | 18-FEB-08:00 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 288.94 | 27-MAR-15:00 | 527.22 | 24-MAR-23:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 740.64 | 15-APR-14:00 | 61.42 | 10-APR-07:00 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 768.76 | 05-MAY-15:00 | 20.48 | 13-MAY-05:00 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 798.62 | 06-JUN-15:00 | 14.53 | 18-JUN-05:00 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 464.20 | 19-JUL-12:00 | 14.06 | 19-JUL-03:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 334.81 | 31-AUG-11:00 | 11.30 | 15-AUG-24:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 340.23 | 19-SEP-13:00 | 2.00 | 27-SEP-06:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 367.16 | 03-OCT-15:00 | 61.82 | 12-OCT-03:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 131.90 | 13-NOV-14:00 | 137.06 | 29-NOV-24:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.84 | 28-DEC-14:00 | 308.15 | 31-DEC-15:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 798.62 | 527.22 |
Report: PeakSpaceGainsMonthly
For: T NE APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 313.63 | 31-JAN-08:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 56.66 | 19-FEB-15:00 | 340.75 | 18-FEB-08:00 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 288.94 | 27-MAR-15:00 | 510.28 | 24-MAR-23:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 740.64 | 15-APR-14:00 | 60.61 | 10-APR-07:00 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 768.76 | 05-MAY-15:00 | 20.48 | 13-MAY-05:00 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 798.62 | 06-JUN-15:00 | 14.53 | 18-JUN-05:00 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 464.20 | 19-JUL-12:00 | 14.06 | 19-JUL-03:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 334.81 | 31-AUG-11:00 | 11.30 | 15-AUG-24:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 340.23 | 19-SEP-13:00 | 2.00 | 27-SEP-06:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 367.16 | 03-OCT-15:00 | 61.82 | 12-OCT-03:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 131.90 | 13-NOV-14:00 | 128.59 | 29-NOV-24:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.84 | 28-DEC-14:00 | 266.26 | 29-DEC-24:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 798.62 | 510.28 |
Report: PeakSpaceGainsMonthly
For: T N1 APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 189.18 | 31-JAN-08:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 34.18 | 19-FEB-15:00 | 205.91 | 18-FEB-08:00 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 174.28 | 27-MAR-15:00 | 343.04 | 24-MAR-24:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 446.74 | 15-APR-14:00 | 37.88 | 10-APR-06:50 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 463.70 | 05-MAY-15:00 | 12.35 | 13-MAY-05:00 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 481.71 | 06-JUN-15:00 | 8.76 | 18-JUN-05:00 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 279.99 | 19-JUL-12:00 | 8.48 | 19-JUL-03:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 201.95 | 31-AUG-11:00 | 6.82 | 15-AUG-24:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 205.22 | 19-SEP-13:00 | 1.21 | 27-SEP-06:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 221.46 | 03-OCT-15:00 | 37.29 | 12-OCT-03:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 79.56 | 13-NOV-14:00 | 82.91 | 29-NOV-24:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.06 | 24-DEC-14:00 | 178.74 | 29-DEC-24:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.21 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 481.71 | 343.04 |
Report: PeakSpaceGainsMonthly
For: T N2 APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 189.18 | 31-JAN-08:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 34.18 | 19-FEB-15:00 | 205.96 | 18-FEB-08:00 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 174.28 | 27-MAR-15:00 | 342.61 | 24-MAR-24:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 446.74 | 15-APR-14:00 | 37.86 | 10-APR-06:50 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 463.70 | 05-MAY-15:00 | 12.35 | 13-MAY-05:00 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 481.71 | 06-JUN-15:00 | 8.76 | 18-JUN-05:00 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 279.99 | 19-JUL-12:00 | 8.48 | 19-JUL-03:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 201.95 | 31-AUG-11:00 | 6.82 | 15-AUG-24:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 205.22 | 19-SEP-13:00 | 1.21 | 27-SEP-06:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 221.46 | 03-OCT-15:00 | 37.29 | 12-OCT-03:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 79.56 | 13-NOV-14:00 | 82.85 | 29-NOV-24:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.57 | 24-DEC-14:00 | 178.70 | 29-DEC-24:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.21 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 481.71 | 342.61 |
Report: PeakSpaceGainsMonthly
For: T S1 APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 189.18 | 31-JAN-08:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 34.18 | 19-FEB-15:00 | 216.78 | 18-FEB-08:00 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 174.28 | 27-MAR-15:00 | 353.91 | 24-MAR-24:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 446.74 | 15-APR-14:00 | 38.34 | 10-APR-07:00 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 463.70 | 05-MAY-15:00 | 12.35 | 13-MAY-05:00 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 481.71 | 06-JUN-15:00 | 8.76 | 18-JUN-05:00 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 279.99 | 19-JUL-12:00 | 8.48 | 19-JUL-03:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 201.95 | 31-AUG-11:00 | 6.82 | 15-AUG-24:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 205.22 | 19-SEP-13:00 | 1.21 | 27-SEP-06:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 221.46 | 03-OCT-15:00 | 37.29 | 12-OCT-03:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 79.56 | 13-NOV-14:00 | 85.52 | 29-NOV-24:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.54 | 28-DEC-14:00 | 185.87 | 31-DEC-15:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.21 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 481.71 | 353.91 |
Report: PeakSpaceGainsMonthly
For: T S2 APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 189.18 | 31-JAN-08:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 34.18 | 19-FEB-15:00 | 216.78 | 18-FEB-08:00 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 174.28 | 27-MAR-15:00 | 353.53 | 24-MAR-24:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 446.74 | 15-APR-14:00 | 38.34 | 10-APR-07:00 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 463.70 | 05-MAY-15:00 | 12.35 | 13-MAY-05:00 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 481.71 | 06-JUN-15:00 | 8.76 | 18-JUN-05:00 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 279.99 | 19-JUL-12:00 | 8.48 | 19-JUL-03:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 201.95 | 31-AUG-11:00 | 6.82 | 15-AUG-24:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 205.22 | 19-SEP-13:00 | 1.21 | 27-SEP-06:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 221.46 | 03-OCT-15:00 | 37.29 | 12-OCT-03:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 79.56 | 13-NOV-14:00 | 85.52 | 29-NOV-24:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.54 | 28-DEC-14:00 | 185.87 | 31-DEC-15:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.21 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 481.71 | 353.53 |
Report: PeakSpaceGainsMonthly
For: T CORRIDOR
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 397.10 | 01-JAN-00:10 | 370.63 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 54.01 | 31-JAN-08:00 |
| February | 397.10 | 01-FEB-00:10 | 370.63 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.72 | 19-FEB-15:00 | 66.78 | 18-FEB-08:00 |
| March | 397.10 | 01-MAR-00:10 | 370.63 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.67 | 27-MAR-15:00 | 123.43 | 24-MAR-24:00 |
| April | 397.10 | 01-APR-00:10 | 370.63 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99.44 | 15-APR-14:00 | 21.13 | 22-APR-18:00 |
| May | 397.10 | 01-MAY-00:10 | 370.63 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 105.32 | 05-MAY-15:00 | 8.06 | 13-MAY-05:00 |
| June | 397.10 | 01-JUN-00:10 | 370.63 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 109.73 | 06-JUN-15:00 | 8.78 | 18-JUN-05:00 |
| July | 397.10 | 01-JUL-00:10 | 370.63 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.56 | 19-JUL-11:00 | 7.30 | 19-JUL-03:00 |
| August | 397.10 | 01-AUG-00:10 | 370.63 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.38 | 31-AUG-11:00 | 9.16 | 15-AUG-24:00 |
| September | 397.10 | 01-SEP-00:10 | 370.63 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.68 | 19-SEP-13:00 | 6.26 | 08-SEP-21:00 |
| October | 397.10 | 01-OCT-00:10 | 370.63 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.13 | 03-OCT-14:00 | 15.86 | 12-OCT-03:00 |
| November | 397.10 | 01-NOV-00:10 | 370.63 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.40 | 13-NOV-14:00 | 27.25 | 29-NOV-24:00 |
| December | 397.10 | 01-DEC-00:10 | 370.63 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.28 | 24-DEC-14:00 | 58.19 | 29-DEC-24:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
| Minimum of Months | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.26 | ||||
| Maximum of Months | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 109.73 | 123.43 |
Report: PeakSpaceGainsMonthly
For: G CORRIDOR
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 397.10 | 01-JAN-00:10 | 370.63 | 01-JAN-00:10 | 208.40 | 01-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 9893.12 | 21-JAN-07:01 |
| February | 397.10 | 01-FEB-00:10 | 370.63 | 01-FEB-00:10 | 208.40 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 89.12 | 22-FEB-15:00 | 8923.12 | 02-FEB-07:01 |
| March | 397.10 | 01-MAR-00:10 | 370.63 | 01-MAR-00:10 | 208.40 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4046.58 | 28-MAR-16:01 | 5666.18 | 01-MAR-07:01 |
| April | 397.10 | 01-APR-00:10 | 370.63 | 01-APR-00:10 | 208.40 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5744.49 | 27-APR-16:01 | 3699.81 | 11-APR-06:02 |
| May | 397.10 | 01-MAY-00:10 | 370.63 | 01-MAY-00:10 | 208.40 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7610.01 | 03-MAY-16:01 | 1655.10 | 13-MAY-06:03 |
| June | 397.10 | 01-JUN-00:10 | 370.63 | 01-JUN-00:10 | 208.40 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7618.43 | 08-JUN-16:01 | 1507.01 | 18-JUN-06:03 |
| July | 397.10 | 01-JUL-00:10 | 370.63 | 01-JUL-00:10 | 208.40 | 01-JUL-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5710.95 | 02-JUL-16:01 | 563.61 | 26-JUL-06:03 |
| August | 397.10 | 01-AUG-00:10 | 370.63 | 01-AUG-00:10 | 208.40 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4207.27 | 07-AUG-16:01 | 1298.70 | 16-AUG-06:03 |
| September | 397.10 | 01-SEP-00:10 | 370.63 | 01-SEP-00:10 | 208.40 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3686.28 | 26-SEP-16:01 | 1667.38 | 27-SEP-06:03 |
| October | 397.10 | 01-OCT-00:10 | 370.63 | 01-OCT-00:10 | 208.40 | 01-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3755.24 | 02-OCT-16:01 | 5281.94 | 31-OCT-06:01 |
| November | 397.10 | 01-NOV-00:10 | 370.63 | 01-NOV-00:10 | 208.40 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 968.46 | 04-NOV-16:05 | 8127.14 | 27-NOV-07:01 |
| December | 397.10 | 01-DEC-00:10 | 370.63 | 01-DEC-00:10 | 208.40 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 10133.13 | 31-DEC-07:01 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 397.10 | 370.63 | 208.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 563.61 | |||||
| Maximum of Months | 397.10 | 370.63 | 208.40 | 0.00 | 0.00 | 0.00 | 0.00 | 7618.43 | 10133.13 |
Report: PeakSpaceGainsMonthly
For: M CORRIDOR
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 397.10 | 01-JAN-00:10 | 370.63 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 50.48 | 31-JAN-08:00 |
| February | 397.10 | 01-FEB-00:10 | 370.63 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.58 | 22-FEB-15:10 | 63.46 | 18-FEB-08:00 |
| March | 397.10 | 01-MAR-00:10 | 370.63 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.06 | 27-MAR-15:00 | 103.02 | 24-MAR-24:00 |
| April | 397.10 | 01-APR-00:10 | 370.63 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81.74 | 15-APR-14:00 | 16.71 | 22-APR-18:00 |
| May | 397.10 | 01-MAY-00:10 | 370.63 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86.36 | 05-MAY-15:00 | 6.48 | 13-MAY-05:00 |
| June | 397.10 | 01-JUN-00:10 | 370.63 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90.30 | 06-JUN-15:00 | 7.07 | 18-JUN-05:00 |
| July | 397.10 | 01-JUL-00:10 | 370.63 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.38 | 20-JUL-15:00 | 5.88 | 19-JUL-03:00 |
| August | 397.10 | 01-AUG-00:10 | 370.63 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.35 | 31-AUG-11:00 | 6.28 | 15-AUG-24:00 |
| September | 397.10 | 01-SEP-00:10 | 370.63 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.36 | 19-SEP-13:00 | 4.44 | 08-SEP-21:00 |
| October | 397.10 | 01-OCT-00:10 | 370.63 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.15 | 03-OCT-14:00 | 12.71 | 12-OCT-03:00 |
| November | 397.10 | 01-NOV-00:10 | 370.63 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.17 | 13-NOV-14:00 | 23.81 | 28-NOV-05:00 |
| December | 397.10 | 01-DEC-00:10 | 370.63 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 53.74 | 29-DEC-24:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
| Minimum of Months | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.44 | ||||
| Maximum of Months | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90.30 | 103.02 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: G SW APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 1189.73 | 12-JAN-15:20 | 0.00 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.79 |
| February | 1630.29 | 20-FEB-16:10 | 237.50 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 5.63 | 0.00 |
| March | 1961.18 | 29-MAR-16:03 | 0.00 | 520.80 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 138.68 | 0.00 |
| April | 2457.90 | 27-APR-16:09 | 0.00 | 781.19 | 5297.60 | 0.00 | 0.00 | 0.00 | 0.00 | 309.28 | 0.00 |
| May | 2731.97 | 05-MAY-16:40 | 0.00 | 86.80 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 356.38 | 0.00 |
| June | 2790.70 | 06-JUN-16:01 | 0.00 | 867.99 | 5886.23 | 0.00 | 0.00 | 0.00 | 0.00 | 310.72 | 0.00 |
| July | 2634.73 | 02-JUL-17:03 | 1662.50 | 820.27 | 4120.36 | 0.00 | 0.00 | 0.00 | 0.00 | 116.48 | 0.00 |
| August | 2485.47 | 06-AUG-16:40 | 237.50 | 86.80 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 104.29 | 0.00 |
| September | 2634.48 | 24-SEP-16:04 | 1187.50 | 434.00 | 2943.11 | 0.00 | 0.00 | 0.00 | 0.00 | 85.94 | 0.00 |
| October | 2626.57 | 01-OCT-16:03 | 1425.00 | 520.80 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 38.93 | 0.00 |
| November | 2192.52 | 04-NOV-15:20 | 237.50 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 15.34 | 0.00 |
| December | 1631.07 | 02-DEC-15:10 | 0.00 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.78 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 1189.73 | 0.00 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 2790.70 | 1662.50 | 867.99 | 5886.23 | 0.00 | 0.00 | 0.00 | 0.00 | 356.38 | 6.79 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: G NW APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 489.44 | 21-JAN-06:10 | 1187.50 | 303.79 | 1589.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 938.28 | 22-FEB-17:10 | 494.00 | 347.20 | 2354.49 | 0.00 | 0.00 | 0.00 | 0.00 | 20.87 | 0.00 |
| March | 1630.17 | 29-MAR-16:40 | 123.50 | 86.80 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 136.38 | 0.00 |
| April | 2265.66 | 27-APR-16:30 | 123.50 | 86.80 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 290.80 | 0.00 |
| May | 2693.83 | 05-MAY-17:04 | 1653.00 | 937.46 | 4708.98 | 0.00 | 0.00 | 0.00 | 0.00 | 332.46 | 0.00 |
| June | 2808.03 | 06-JUN-16:40 | 247.00 | 173.60 | 1177.25 | 0.00 | 0.00 | 0.00 | 0.00 | 258.22 | 0.00 |
| July | 2634.39 | 02-JUL-17:15 | 826.50 | 468.73 | 2354.49 | 0.00 | 0.00 | 0.00 | 0.00 | 112.86 | 0.00 |
| August | 2442.09 | 07-AUG-17:04 | 1033.12 | 585.91 | 2943.11 | 0.00 | 0.00 | 0.00 | 0.00 | 117.81 | 0.00 |
| September | 2212.37 | 22-SEP-16:03 | 864.50 | 607.59 | 4120.36 | 0.00 | 0.00 | 0.00 | 0.00 | 131.22 | 0.00 |
| October | 2082.11 | 01-OCT-16:17 | 370.50 | 260.40 | 1765.87 | 0.00 | 0.00 | 0.00 | 0.00 | 36.30 | 0.00 |
| November | 1381.28 | 04-NOV-16:10 | 247.00 | 173.60 | 1177.25 | 0.00 | 0.00 | 0.00 | 0.00 | 8.64 | 0.00 |
| December | 804.22 | 01-DEC-16:10 | 71.25 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.15 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 489.44 | 71.25 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 2808.03 | 1653.00 | 937.46 | 4708.98 | 0.00 | 0.00 | 0.00 | 0.00 | 332.46 | 7.15 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: OFFICE
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 6154.63 | 26-JAN-09:02 | 1804.82 | 2331.66 | 2354.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.10 |
| February | 6732.14 | 21-FEB-09:02 | 1804.82 | 2331.66 | 2354.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.52 |
| March | 6774.91 | 14-MAR-07:02 | 2707.23 | 3497.50 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.94 |
| April | 7143.23 | 10-APR-07:02 | 2707.23 | 3497.50 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.46 |
| May | 6629.07 | 05-MAY-07:02 | 2707.23 | 3497.50 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 64.92 | 0.00 |
| June | 6600.10 | 12-JUN-06:02 | 0.00 | 699.50 | 1765.87 | 0.00 | 0.00 | 0.00 | 0.00 | 64.78 | 0.00 |
| July | 5094.89 | 05-JUL-07:02 | 2707.23 | 3497.50 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 63.90 | 0.00 |
| August | 5096.84 | 07-AUG-08:62 | 1804.82 | 2331.66 | 2354.49 | 0.00 | 0.00 | 0.00 | 0.00 | 53.63 | 0.00 |
| September | 5617.88 | 26-SEP-08:62 | 2256.03 | 2914.58 | 2943.11 | 0.00 | 0.00 | 0.00 | 0.00 | 10.34 | 0.00 |
| October | 7232.50 | 24-OCT-07:02 | 2707.23 | 3497.50 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.98 |
| November | 7291.91 | 20-NOV-08:62 | 2707.23 | 3497.50 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.36 |
| December | 6747.57 | 01-DEC-09:02 | 1804.82 | 2331.66 | 2354.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.87 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 5094.89 | 0.00 | 699.50 | 1765.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 7291.91 | 2707.23 | 3497.50 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 64.92 | 55.36 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: G NE APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 488.51 | 21-JAN-06:10 | 1187.50 | 303.79 | 1589.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 857.91 | 24-FEB-17:10 | 494.00 | 347.20 | 2354.49 | 0.00 | 0.00 | 0.00 | 0.00 | 12.64 | 0.00 |
| March | 1386.87 | 29-MAR-16:30 | 123.50 | 86.80 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 137.18 | 0.00 |
| April | 1954.73 | 15-APR-16:01 | 1111.50 | 781.19 | 5297.60 | 0.00 | 0.00 | 0.00 | 0.00 | 305.48 | 0.00 |
| May | 2401.69 | 05-MAY-17:04 | 1653.00 | 937.46 | 4708.98 | 0.00 | 0.00 | 0.00 | 0.00 | 332.46 | 0.00 |
| June | 2511.17 | 06-JUN-16:01 | 1235.00 | 867.99 | 5886.23 | 0.00 | 0.00 | 0.00 | 0.00 | 310.72 | 0.00 |
| July | 2377.12 | 04-JUL-17:15 | 826.50 | 468.73 | 2354.49 | 0.00 | 0.00 | 0.00 | 0.00 | 84.58 | 0.00 |
| August | 2278.67 | 07-AUG-17:04 | 1033.12 | 585.91 | 2943.11 | 0.00 | 0.00 | 0.00 | 0.00 | 117.81 | 0.00 |
| September | 2015.18 | 22-SEP-16:03 | 864.50 | 607.59 | 4120.36 | 0.00 | 0.00 | 0.00 | 0.00 | 131.22 | 0.00 |
| October | 1896.81 | 03-OCT-15:10 | 71.25 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 185.05 | 0.00 |
| November | 1203.04 | 01-NOV-16:02 | 741.00 | 520.80 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 12.73 | 0.00 |
| December | 675.75 | 01-DEC-15:10 | 59.38 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.95 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 488.51 | 59.38 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 2511.17 | 1653.00 | 937.46 | 5886.23 | 0.00 | 0.00 | 0.00 | 0.00 | 332.46 | 2.95 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: G N1 APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 507.80 | 21-JAN-06:10 | 1187.50 | 303.79 | 1589.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 772.59 | 24-FEB-17:05 | 494.00 | 347.20 | 2354.49 | 0.00 | 0.00 | 0.00 | 0.00 | 7.63 | 0.00 |
| March | 1138.08 | 29-MAR-17:07 | 619.87 | 351.55 | 1765.87 | 0.00 | 0.00 | 0.00 | 0.00 | 78.74 | 0.00 |
| April | 1524.91 | 27-APR-17:05 | 1239.75 | 703.09 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 153.37 | 0.00 |
| May | 1839.59 | 05-MAY-17:14 | 1033.12 | 585.91 | 2943.11 | 0.00 | 0.00 | 0.00 | 0.00 | 193.66 | 0.00 |
| June | 1930.04 | 07-JUN-17:14 | 1033.12 | 585.91 | 2943.11 | 0.00 | 0.00 | 0.00 | 0.00 | 90.51 | 0.00 |
| July | 1868.54 | 04-JUL-17:30 | 413.25 | 234.36 | 1177.25 | 0.00 | 0.00 | 0.00 | 0.00 | 51.17 | 0.00 |
| August | 1776.17 | 07-AUG-17:15 | 826.50 | 468.73 | 2354.49 | 0.00 | 0.00 | 0.00 | 0.00 | 68.64 | 0.00 |
| September | 1564.25 | 22-SEP-16:03 | 864.50 | 607.59 | 4120.36 | 0.00 | 0.00 | 0.00 | 0.00 | 79.15 | 0.00 |
| October | 1466.33 | 03-OCT-16:03 | 864.50 | 607.59 | 4120.36 | 0.00 | 0.00 | 0.00 | 0.00 | 80.91 | 0.00 |
| November | 1014.69 | 01-NOV-16:13 | 370.50 | 260.40 | 1765.87 | 0.00 | 0.00 | 0.00 | 0.00 | 6.88 | 0.00 |
| December | 623.94 | 01-DEC-17:04 | 617.50 | 434.00 | 2943.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.16 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 507.80 | 370.50 | 234.36 | 1177.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 1930.04 | 1239.75 | 703.09 | 4120.36 | 0.00 | 0.00 | 0.00 | 0.00 | 193.66 | 7.16 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: G N2 APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 507.74 | 21-JAN-06:10 | 1187.50 | 303.79 | 1589.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 774.67 | 24-FEB-17:05 | 494.00 | 347.20 | 2354.49 | 0.00 | 0.00 | 0.00 | 0.00 | 7.63 | 0.00 |
| March | 1134.27 | 29-MAR-17:07 | 619.87 | 351.55 | 1765.87 | 0.00 | 0.00 | 0.00 | 0.00 | 78.74 | 0.00 |
| April | 1519.52 | 27-APR-17:05 | 1239.75 | 703.09 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 153.37 | 0.00 |
| May | 1835.81 | 05-MAY-17:14 | 1033.12 | 585.91 | 2943.11 | 0.00 | 0.00 | 0.00 | 0.00 | 193.66 | 0.00 |
| June | 1925.33 | 07-JUN-17:14 | 1033.12 | 585.91 | 2943.11 | 0.00 | 0.00 | 0.00 | 0.00 | 90.51 | 0.00 |
| July | 1864.91 | 04-JUL-17:25 | 413.25 | 234.36 | 1177.25 | 0.00 | 0.00 | 0.00 | 0.00 | 51.17 | 0.00 |
| August | 1773.79 | 07-AUG-17:15 | 826.50 | 468.73 | 2354.49 | 0.00 | 0.00 | 0.00 | 0.00 | 68.64 | 0.00 |
| September | 1561.58 | 22-SEP-16:04 | 864.50 | 607.59 | 4120.36 | 0.00 | 0.00 | 0.00 | 0.00 | 79.15 | 0.00 |
| October | 1464.46 | 03-OCT-16:03 | 864.50 | 607.59 | 4120.36 | 0.00 | 0.00 | 0.00 | 0.00 | 80.91 | 0.00 |
| November | 1011.96 | 01-NOV-16:13 | 370.50 | 260.40 | 1765.87 | 0.00 | 0.00 | 0.00 | 0.00 | 6.88 | 0.00 |
| December | 622.10 | 01-DEC-17:04 | 617.50 | 434.00 | 2943.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.16 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 507.74 | 370.50 | 234.36 | 1177.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 1925.33 | 1239.75 | 703.09 | 4120.36 | 0.00 | 0.00 | 0.00 | 0.00 | 193.66 | 7.16 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: G S1 APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 1135.77 | 12-JAN-14:30 | 0.00 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.85 |
| February | 1392.91 | 20-FEB-14:40 | 118.75 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 3.68 | 0.00 |
| March | 1570.24 | 12-MAR-16:05 | 950.00 | 347.20 | 2354.49 | 0.00 | 0.00 | 0.00 | 0.00 | 31.03 | 0.00 |
| April | 1747.47 | 15-APR-16:01 | 2137.50 | 781.19 | 5297.60 | 0.00 | 0.00 | 0.00 | 0.00 | 184.26 | 0.00 |
| May | 1873.05 | 05-MAY-17:14 | 1187.50 | 585.91 | 2943.11 | 0.00 | 0.00 | 0.00 | 0.00 | 193.66 | 0.00 |
| June | 1885.03 | 06-JUN-16:01 | 0.00 | 867.99 | 5886.23 | 0.00 | 0.00 | 0.00 | 0.00 | 187.42 | 0.00 |
| July | 1858.06 | 04-JUL-17:15 | 950.00 | 468.73 | 2354.49 | 0.00 | 0.00 | 0.00 | 0.00 | 51.02 | 0.00 |
| August | 1816.18 | 07-AUG-17:15 | 950.00 | 468.73 | 2354.49 | 0.00 | 0.00 | 0.00 | 0.00 | 68.64 | 0.00 |
| September | 1983.19 | 24-SEP-16:04 | 1187.50 | 434.00 | 2943.11 | 0.00 | 0.00 | 0.00 | 0.00 | 51.84 | 0.00 |
| October | 1986.50 | 01-OCT-15:10 | 237.50 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 32.48 | 0.00 |
| November | 1805.86 | 04-NOV-14:10 | 0.00 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 14.69 | 0.00 |
| December | 1494.78 | 02-DEC-14:00 | 118.75 | 17.36 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.18 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 1135.77 | 0.00 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 1986.50 | 2137.50 | 867.99 | 5886.23 | 0.00 | 0.00 | 0.00 | 0.00 | 193.66 | 4.85 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: G S2 APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 1178.68 | 12-JAN-14:30 | 0.00 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.85 |
| February | 1484.74 | 20-FEB-14:50 | 118.75 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 3.65 | 0.00 |
| March | 1705.63 | 12-MAR-16:05 | 950.00 | 347.20 | 2354.49 | 0.00 | 0.00 | 0.00 | 0.00 | 31.03 | 0.00 |
| April | 1881.76 | 15-APR-16:01 | 2137.50 | 781.19 | 5297.60 | 0.00 | 0.00 | 0.00 | 0.00 | 184.26 | 0.00 |
| May | 1961.13 | 05-MAY-17:20 | 1187.50 | 585.91 | 2943.11 | 0.00 | 0.00 | 0.00 | 0.00 | 193.66 | 0.00 |
| June | 1986.72 | 11-JUN-17:14 | 1187.50 | 585.91 | 2943.11 | 0.00 | 0.00 | 0.00 | 0.00 | 36.62 | 0.00 |
| July | 2021.24 | 02-JUL-17:20 | 950.00 | 468.73 | 2354.49 | 0.00 | 0.00 | 0.00 | 0.00 | 68.07 | 0.00 |
| August | 1969.71 | 06-AUG-17:04 | 1187.50 | 585.91 | 2943.11 | 0.00 | 0.00 | 0.00 | 0.00 | 57.02 | 0.00 |
| September | 2152.95 | 24-SEP-16:04 | 1187.50 | 434.00 | 2943.11 | 0.00 | 0.00 | 0.00 | 0.00 | 51.84 | 0.00 |
| October | 2159.43 | 01-OCT-15:10 | 237.50 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 32.48 | 0.00 |
| November | 1922.12 | 13-NOV-14:00 | 118.75 | 17.36 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 42.45 | 0.00 |
| December | 1567.33 | 02-DEC-14:00 | 118.75 | 17.36 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.18 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 1178.68 | 0.00 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 2159.43 | 2137.50 | 781.19 | 5297.60 | 0.00 | 0.00 | 0.00 | 0.00 | 193.66 | 4.85 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: M SW APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 1523.67 | 12-JAN-15:20 | 0.00 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.14 |
| February | 2114.12 | 20-FEB-16:10 | 237.50 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 7.98 | 0.00 |
| March | 2481.99 | 12-MAR-16:08 | 950.00 | 347.20 | 2354.49 | 0.00 | 0.00 | 0.00 | 0.00 | 73.72 | 0.00 |
| April | 3059.27 | 27-APR-16:03 | 0.00 | 781.19 | 5297.60 | 0.00 | 0.00 | 0.00 | 0.00 | 443.89 | 0.00 |
| May | 3201.23 | 05-MAY-16:03 | 0.00 | 867.99 | 5886.23 | 0.00 | 0.00 | 0.00 | 0.00 | 538.69 | 0.00 |
| June | 3120.00 | 06-JUN-16:08 | 0.00 | 867.99 | 5886.23 | 0.00 | 0.00 | 0.00 | 0.00 | 446.08 | 0.00 |
| July | 2728.95 | 02-JUL-16:40 | 237.50 | 86.80 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 172.82 | 0.00 |
| August | 2467.85 | 06-AUG-16:20 | 712.50 | 260.40 | 1765.87 | 0.00 | 0.00 | 0.00 | 0.00 | 157.10 | 0.00 |
| September | 2655.24 | 24-SEP-15:30 | 237.50 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 145.21 | 0.00 |
| October | 2704.87 | 03-OCT-15:10 | 0.00 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 265.46 | 0.00 |
| November | 2395.85 | 04-NOV-15:20 | 237.50 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 21.97 | 0.00 |
| December | 1801.04 | 02-DEC-14:30 | 118.75 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.08 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 1523.67 | 0.00 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 3201.23 | 950.00 | 867.99 | 5886.23 | 0.00 | 0.00 | 0.00 | 0.00 | 538.69 | 10.14 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: M NW APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 565.26 | 14-JAN-17:10 | 494.00 | 347.20 | 2354.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.83 |
| February | 1286.69 | 22-FEB-17:10 | 494.00 | 347.20 | 2354.49 | 0.00 | 0.00 | 0.00 | 0.00 | 29.61 | 0.00 |
| March | 2102.07 | 29-MAR-16:30 | 123.50 | 86.80 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 196.68 | 0.00 |
| April | 2840.37 | 27-APR-16:17 | 370.50 | 260.40 | 1765.87 | 0.00 | 0.00 | 0.00 | 0.00 | 430.57 | 0.00 |
| May | 3132.12 | 05-MAY-16:30 | 123.50 | 86.80 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 520.57 | 0.00 |
| June | 3131.19 | 06-JUN-16:04 | 1235.00 | 867.99 | 5886.23 | 0.00 | 0.00 | 0.00 | 0.00 | 446.08 | 0.00 |
| July | 2696.91 | 02-JUL-16:50 | 123.50 | 86.80 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 172.62 | 0.00 |
| August | 2390.61 | 07-AUG-16:17 | 370.50 | 260.40 | 1765.87 | 0.00 | 0.00 | 0.00 | 0.00 | 188.27 | 0.00 |
| September | 2180.36 | 22-SEP-16:09 | 864.50 | 607.59 | 4120.36 | 0.00 | 0.00 | 0.00 | 0.00 | 188.22 | 0.00 |
| October | 2072.30 | 03-OCT-15:20 | 71.25 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 252.66 | 0.00 |
| November | 1405.32 | 04-NOV-16:10 | 247.00 | 173.60 | 1177.25 | 0.00 | 0.00 | 0.00 | 0.00 | 12.36 | 0.00 |
| December | 771.31 | 01-DEC-16:10 | 71.25 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.38 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 565.26 | 71.25 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 3132.12 | 1235.00 | 867.99 | 5886.23 | 0.00 | 0.00 | 0.00 | 0.00 | 520.57 | 46.83 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: M SE APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 1424.74 | 12-JAN-14:30 | 0.00 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.97 |
| February | 1923.22 | 20-FEB-14:30 | 118.75 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 8.74 | 0.00 |
| March | 2206.88 | 12-MAR-16:10 | 950.00 | 347.20 | 2354.49 | 0.00 | 0.00 | 0.00 | 0.00 | 73.72 | 0.00 |
| April | 2816.07 | 15-APR-15:10 | 237.50 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 539.28 | 0.00 |
| May | 2822.92 | 05-MAY-15:10 | 0.00 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 576.58 | 0.00 |
| June | 2803.30 | 06-JUN-15:10 | 0.00 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 582.64 | 0.00 |
| July | 2359.36 | 02-JUL-16:30 | 237.50 | 86.80 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 173.01 | 0.00 |
| August | 2247.81 | 07-AUG-16:01 | 0.00 | 607.59 | 4120.36 | 0.00 | 0.00 | 0.00 | 0.00 | 191.69 | 0.00 |
| September | 2434.37 | 28-SEP-14:10 | 0.00 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 230.41 | 0.00 |
| October | 2542.74 | 03-OCT-14:10 | 0.00 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 276.44 | 0.00 |
| November | 2197.01 | 04-NOV-13:40 | 118.75 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 38.46 | 0.00 |
| December | 1687.31 | 02-DEC-14:00 | 118.75 | 17.36 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 1424.74 | 0.00 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 2822.92 | 950.00 | 607.59 | 4120.36 | 0.00 | 0.00 | 0.00 | 0.00 | 582.64 | 11.97 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: M NE APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 492.20 | 21-JAN-06:10 | 1187.50 | 303.79 | 1589.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 1100.82 | 22-FEB-17:05 | 494.00 | 347.20 | 2354.49 | 0.00 | 0.00 | 0.00 | 0.00 | 29.61 | 0.00 |
| March | 1776.90 | 29-MAR-16:13 | 370.50 | 260.40 | 1765.87 | 0.00 | 0.00 | 0.00 | 0.00 | 197.78 | 0.00 |
| April | 2451.34 | 15-APR-15:10 | 71.25 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 539.28 | 0.00 |
| May | 2743.53 | 05-MAY-16:09 | 1235.00 | 867.99 | 5886.23 | 0.00 | 0.00 | 0.00 | 0.00 | 538.69 | 0.00 |
| June | 2768.48 | 06-JUN-15:10 | 71.25 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 582.64 | 0.00 |
| July | 2395.11 | 07-JUL-10:10 | 59.38 | 17.36 | 412.04 | 0.00 | 0.00 | 0.00 | 0.00 | 269.18 | 0.00 |
| August | 2182.13 | 07-AUG-16:17 | 370.50 | 260.40 | 1765.87 | 0.00 | 0.00 | 0.00 | 0.00 | 188.27 | 0.00 |
| September | 1925.22 | 22-SEP-16:03 | 864.50 | 607.59 | 4120.36 | 0.00 | 0.00 | 0.00 | 0.00 | 188.22 | 0.00 |
| October | 1864.03 | 03-OCT-15:10 | 71.25 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 265.46 | 0.00 |
| November | 1155.31 | 04-NOV-16:10 | 247.00 | 173.60 | 1177.25 | 0.00 | 0.00 | 0.00 | 0.00 | 12.36 | 0.00 |
| December | 610.28 | 01-DEC-15:10 | 59.38 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.35 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 492.20 | 59.38 | 17.36 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 2768.48 | 1235.00 | 867.99 | 5886.23 | 0.00 | 0.00 | 0.00 | 0.00 | 582.64 | 4.35 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: M N1 APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 552.70 | 27-JAN-18:20 | 826.50 | 468.73 | 2354.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.41 |
| February | 944.69 | 24-FEB-17:05 | 494.00 | 347.20 | 2354.49 | 0.00 | 0.00 | 0.00 | 0.00 | 10.80 | 0.00 |
| March | 1370.79 | 29-MAR-16:30 | 123.50 | 86.80 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 118.63 | 0.00 |
| April | 1770.02 | 27-APR-16:20 | 370.50 | 260.40 | 1765.87 | 0.00 | 0.00 | 0.00 | 0.00 | 259.71 | 0.00 |
| May | 1973.03 | 05-MAY-17:04 | 1653.00 | 937.46 | 4708.98 | 0.00 | 0.00 | 0.00 | 0.00 | 287.86 | 0.00 |
| June | 1980.94 | 06-JUN-16:08 | 1235.00 | 867.99 | 5886.23 | 0.00 | 0.00 | 0.00 | 0.00 | 269.07 | 0.00 |
| July | 1793.25 | 02-JUL-17:25 | 413.25 | 234.36 | 1177.25 | 0.00 | 0.00 | 0.00 | 0.00 | 94.61 | 0.00 |
| August | 1651.95 | 07-AUG-17:17 | 826.50 | 468.73 | 2354.49 | 0.00 | 0.00 | 0.00 | 0.00 | 98.49 | 0.00 |
| September | 1475.28 | 22-SEP-16:10 | 864.50 | 607.59 | 4120.36 | 0.00 | 0.00 | 0.00 | 0.00 | 113.53 | 0.00 |
| October | 1399.64 | 03-OCT-16:03 | 864.50 | 607.59 | 4120.36 | 0.00 | 0.00 | 0.00 | 0.00 | 116.04 | 0.00 |
| November | 980.28 | 04-NOV-16:20 | 123.50 | 86.80 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 6.35 | 0.00 |
| December | 630.65 | 28-DEC-17:05 | 494.00 | 347.20 | 2354.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.69 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 552.70 | 123.50 | 86.80 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 1980.94 | 1653.00 | 937.46 | 5886.23 | 0.00 | 0.00 | 0.00 | 0.00 | 287.86 | 55.41 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: M N2 APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 531.32 | 27-JAN-18:20 | 826.50 | 468.73 | 2354.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.41 |
| February | 945.91 | 24-FEB-17:05 | 494.00 | 347.20 | 2354.49 | 0.00 | 0.00 | 0.00 | 0.00 | 10.80 | 0.00 |
| March | 1366.82 | 29-MAR-16:30 | 123.50 | 86.80 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 118.63 | 0.00 |
| April | 1764.53 | 27-APR-16:03 | 1111.50 | 781.19 | 5297.60 | 0.00 | 0.00 | 0.00 | 0.00 | 267.74 | 0.00 |
| May | 1968.14 | 05-MAY-17:04 | 1653.00 | 937.46 | 4708.98 | 0.00 | 0.00 | 0.00 | 0.00 | 287.86 | 0.00 |
| June | 1977.18 | 06-JUN-16:08 | 1235.00 | 867.99 | 5886.23 | 0.00 | 0.00 | 0.00 | 0.00 | 269.07 | 0.00 |
| July | 1788.14 | 02-JUL-17:25 | 413.25 | 234.36 | 1177.25 | 0.00 | 0.00 | 0.00 | 0.00 | 94.61 | 0.00 |
| August | 1649.06 | 07-AUG-17:17 | 826.50 | 468.73 | 2354.49 | 0.00 | 0.00 | 0.00 | 0.00 | 98.49 | 0.00 |
| September | 1472.32 | 22-SEP-16:10 | 864.50 | 607.59 | 4120.36 | 0.00 | 0.00 | 0.00 | 0.00 | 113.53 | 0.00 |
| October | 1397.40 | 03-OCT-16:03 | 864.50 | 607.59 | 4120.36 | 0.00 | 0.00 | 0.00 | 0.00 | 116.04 | 0.00 |
| November | 977.29 | 04-NOV-16:20 | 123.50 | 86.80 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 6.35 | 0.00 |
| December | 629.95 | 28-DEC-17:05 | 494.00 | 347.20 | 2354.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.69 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 531.32 | 123.50 | 86.80 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 1977.18 | 1653.00 | 937.46 | 5886.23 | 0.00 | 0.00 | 0.00 | 0.00 | 287.86 | 55.41 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: M S1 APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 1423.61 | 12-JAN-14:30 | 0.00 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.22 |
| February | 1734.17 | 20-FEB-14:30 | 118.75 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 5.27 | 0.00 |
| March | 1870.05 | 12-MAR-16:05 | 950.00 | 347.20 | 2354.49 | 0.00 | 0.00 | 0.00 | 0.00 | 44.46 | 0.00 |
| April | 2069.96 | 15-APR-15:10 | 237.50 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 325.28 | 0.00 |
| May | 2037.70 | 05-MAY-16:03 | 0.00 | 867.99 | 5886.23 | 0.00 | 0.00 | 0.00 | 0.00 | 324.93 | 0.00 |
| June | 1971.92 | 06-JUN-15:10 | 0.00 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 351.43 | 0.00 |
| July | 1793.89 | 02-JUL-17:03 | 1662.50 | 820.27 | 4120.36 | 0.00 | 0.00 | 0.00 | 0.00 | 100.84 | 0.00 |
| August | 1712.58 | 06-AUG-16:20 | 712.50 | 260.40 | 1765.87 | 0.00 | 0.00 | 0.00 | 0.00 | 94.76 | 0.00 |
| September | 1939.81 | 24-SEP-15:20 | 237.50 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 90.84 | 0.00 |
| October | 2057.12 | 17-OCT-14:10 | 0.00 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 141.43 | 0.00 |
| November | 1954.93 | 04-NOV-14:00 | 118.75 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 22.10 | 0.00 |
| December | 1669.16 | 02-DEC-14:00 | 118.75 | 17.36 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.21 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 1423.61 | 0.00 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 2069.96 | 1662.50 | 867.99 | 5886.23 | 0.00 | 0.00 | 0.00 | 0.00 | 351.43 | 7.22 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: M S2 APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 1426.19 | 12-JAN-14:30 | 0.00 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.22 |
| February | 1737.21 | 20-FEB-14:30 | 118.75 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 5.27 | 0.00 |
| March | 1867.91 | 12-MAR-16:05 | 950.00 | 347.20 | 2354.49 | 0.00 | 0.00 | 0.00 | 0.00 | 44.46 | 0.00 |
| April | 2070.45 | 15-APR-15:10 | 237.50 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 325.28 | 0.00 |
| May | 2034.71 | 05-MAY-16:03 | 0.00 | 867.99 | 5886.23 | 0.00 | 0.00 | 0.00 | 0.00 | 324.93 | 0.00 |
| June | 1971.31 | 06-JUN-15:10 | 0.00 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 351.43 | 0.00 |
| July | 1788.97 | 02-JUL-17:03 | 1662.50 | 820.27 | 4120.36 | 0.00 | 0.00 | 0.00 | 0.00 | 100.84 | 0.00 |
| August | 1710.02 | 06-AUG-16:20 | 712.50 | 260.40 | 1765.87 | 0.00 | 0.00 | 0.00 | 0.00 | 94.76 | 0.00 |
| September | 1938.04 | 24-SEP-15:10 | 237.50 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 94.13 | 0.00 |
| October | 2058.78 | 17-OCT-14:10 | 0.00 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 141.43 | 0.00 |
| November | 1956.89 | 04-NOV-14:00 | 118.75 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 22.10 | 0.00 |
| December | 1671.21 | 02-DEC-14:00 | 118.75 | 17.36 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.21 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 1426.19 | 0.00 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 2070.45 | 1662.50 | 867.99 | 5886.23 | 0.00 | 0.00 | 0.00 | 0.00 | 351.43 | 7.22 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: T SW APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 1713.48 | 12-JAN-15:20 | 0.00 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.43 |
| February | 2641.63 | 20-FEB-16:10 | 237.50 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 10.26 | 0.00 |
| March | 3508.94 | 28-MAR-16:01 | 0.00 | 607.59 | 4120.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 4334.42 | 15-APR-15:20 | 237.50 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 690.07 | 0.00 |
| May | 4521.24 | 05-MAY-16:03 | 0.00 | 867.99 | 5886.23 | 0.00 | 0.00 | 0.00 | 0.00 | 711.08 | 0.00 |
| June | 4462.24 | 06-JUN-16:03 | 0.00 | 867.99 | 5886.23 | 0.00 | 0.00 | 0.00 | 0.00 | 588.90 | 0.00 |
| July | 3865.76 | 02-JUL-16:30 | 237.50 | 86.80 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 228.30 | 0.00 |
| August | 3452.76 | 06-AUG-16:03 | 1425.00 | 520.80 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 212.10 | 0.00 |
| September | 3675.67 | 24-SEP-15:30 | 237.50 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 191.38 | 0.00 |
| October | 3762.54 | 03-OCT-15:10 | 0.00 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 349.91 | 0.00 |
| November | 3136.56 | 04-NOV-15:20 | 237.50 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 28.86 | 0.00 |
| December | 2052.77 | 02-DEC-15:00 | 118.75 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.81 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 1713.48 | 0.00 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 4521.24 | 1425.00 | 867.99 | 5886.23 | 0.00 | 0.00 | 0.00 | 0.00 | 711.08 | 14.43 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: T NW APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 540.43 | 12-JAN-17:07 | 370.50 | 260.40 | 1765.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.69 |
| February | 1548.72 | 22-FEB-16:20 | 71.25 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 44.28 | 0.00 |
| March | 2932.03 | 28-MAR-16:30 | 123.50 | 86.80 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 4010.49 | 27-APR-16:03 | 1111.50 | 781.19 | 5297.60 | 0.00 | 0.00 | 0.00 | 0.00 | 585.69 | 0.00 |
| May | 4409.72 | 05-MAY-16:15 | 494.00 | 347.20 | 2354.49 | 0.00 | 0.00 | 0.00 | 0.00 | 699.07 | 0.00 |
| June | 4461.50 | 06-JUN-16:03 | 1235.00 | 867.99 | 5886.23 | 0.00 | 0.00 | 0.00 | 0.00 | 588.90 | 0.00 |
| July | 3805.51 | 02-JUL-16:50 | 123.50 | 86.80 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 227.79 | 0.00 |
| August | 3342.27 | 07-AUG-16:20 | 370.50 | 260.40 | 1765.87 | 0.00 | 0.00 | 0.00 | 0.00 | 248.28 | 0.00 |
| September | 2975.76 | 22-SEP-16:01 | 864.50 | 607.59 | 4120.36 | 0.00 | 0.00 | 0.00 | 0.00 | 248.02 | 0.00 |
| October | 2930.53 | 03-OCT-15:10 | 71.25 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 349.91 | 0.00 |
| November | 1770.79 | 04-NOV-16:10 | 247.00 | 173.60 | 1177.25 | 0.00 | 0.00 | 0.00 | 0.00 | 16.23 | 0.00 |
| December | 738.97 | 28-DEC-16:10 | 71.25 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.97 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 540.43 | 71.25 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 4461.50 | 1235.00 | 867.99 | 5886.23 | 0.00 | 0.00 | 0.00 | 0.00 | 699.07 | 33.69 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: T SE APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 1568.82 | 12-JAN-14:40 | 0.00 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.51 |
| February | 2412.45 | 20-FEB-14:30 | 118.75 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 11.37 | 0.00 |
| March | 3041.43 | 13-MAR-14:10 | 0.00 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 59.61 | 0.00 |
| April | 4046.73 | 15-APR-14:00 | 118.75 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 740.64 | 0.00 |
| May | 4027.34 | 05-MAY-15:10 | 0.00 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 761.11 | 0.00 |
| June | 4057.43 | 06-JUN-15:10 | 0.00 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 769.19 | 0.00 |
| July | 3359.40 | 07-JUL-14:10 | 0.00 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 275.94 | 0.00 |
| August | 3163.93 | 07-AUG-15:10 | 0.00 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 267.97 | 0.00 |
| September | 3386.53 | 28-SEP-14:10 | 0.00 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 303.73 | 0.00 |
| October | 3565.29 | 03-OCT-14:10 | 0.00 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 364.43 | 0.00 |
| November | 2876.22 | 04-NOV-14:00 | 118.75 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 48.17 | 0.00 |
| December | 1878.28 | 02-DEC-14:10 | 118.75 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 1568.82 | 0.00 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 4057.43 | 118.75 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 769.19 | 15.51 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: T NE APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 465.71 | 26-JAN-14:00 | 59.38 | 17.36 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.94 |
| February | 1327.16 | 23-FEB-14:30 | 59.38 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 23.22 | 0.00 |
| March | 2431.66 | 29-MAR-16:05 | 741.00 | 520.80 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 261.84 | 0.00 |
| April | 3507.70 | 15-APR-15:10 | 71.25 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 711.60 | 0.00 |
| May | 3837.29 | 05-MAY-15:10 | 71.25 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 761.11 | 0.00 |
| June | 3985.08 | 06-JUN-15:10 | 71.25 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 769.18 | 0.00 |
| July | 3282.43 | 07-JUL-14:10 | 59.38 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 275.94 | 0.00 |
| August | 3030.01 | 07-AUG-16:03 | 864.50 | 607.59 | 4120.36 | 0.00 | 0.00 | 0.00 | 0.00 | 252.80 | 0.00 |
| September | 2654.05 | 22-SEP-15:10 | 71.25 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 308.35 | 0.00 |
| October | 2617.01 | 03-OCT-15:10 | 71.25 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 349.91 | 0.00 |
| November | 1529.05 | 09-NOV-14:00 | 59.38 | 17.36 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 33.80 | 0.00 |
| December | 496.12 | 01-DEC-15:10 | 59.38 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.04 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 465.71 | 59.38 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 3985.08 | 864.50 | 607.59 | 4120.36 | 0.00 | 0.00 | 0.00 | 0.00 | 769.18 | 35.94 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: T N1 APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 363.60 | 04-JAN-23:00 | 237.50 | 52.08 | 417.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 1042.75 | 22-FEB-17:08 | 494.00 | 347.20 | 2354.49 | 0.00 | 0.00 | 0.00 | 0.00 | 23.00 | 0.00 |
| March | 1943.84 | 29-MAR-16:13 | 370.50 | 260.40 | 1765.87 | 0.00 | 0.00 | 0.00 | 0.00 | 157.08 | 0.00 |
| April | 2637.23 | 27-APR-16:01 | 1111.50 | 781.19 | 5297.60 | 0.00 | 0.00 | 0.00 | 0.00 | 353.27 | 0.00 |
| May | 2925.67 | 05-MAY-16:01 | 1235.00 | 867.99 | 5886.23 | 0.00 | 0.00 | 0.00 | 0.00 | 428.91 | 0.00 |
| June | 3003.53 | 06-JUN-15:10 | 71.25 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 463.95 | 0.00 |
| July | 2622.02 | 02-JUL-17:06 | 1446.38 | 820.27 | 4120.36 | 0.00 | 0.00 | 0.00 | 0.00 | 133.06 | 0.00 |
| August | 2401.48 | 07-AUG-16:17 | 370.50 | 260.40 | 1765.87 | 0.00 | 0.00 | 0.00 | 0.00 | 149.76 | 0.00 |
| September | 2073.39 | 22-SEP-16:03 | 864.50 | 607.59 | 4120.36 | 0.00 | 0.00 | 0.00 | 0.00 | 149.60 | 0.00 |
| October | 2014.21 | 03-OCT-15:10 | 71.25 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 211.06 | 0.00 |
| November | 1214.22 | 09-NOV-14:30 | 59.38 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 18.89 | 0.00 |
| December | 428.27 | 28-DEC-17:08 | 494.00 | 347.20 | 2354.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.46 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 363.60 | 59.38 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 3003.53 | 1446.38 | 867.99 | 5886.23 | 0.00 | 0.00 | 0.00 | 0.00 | 463.95 | 10.46 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: T N2 APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 362.97 | 04-JAN-23:00 | 237.50 | 52.08 | 417.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 1041.49 | 22-FEB-16:10 | 71.25 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 26.52 | 0.00 |
| March | 1935.10 | 29-MAR-16:03 | 741.00 | 520.80 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 157.94 | 0.00 |
| April | 2625.15 | 27-APR-16:01 | 1111.50 | 781.19 | 5297.60 | 0.00 | 0.00 | 0.00 | 0.00 | 353.27 | 0.00 |
| May | 2916.07 | 05-MAY-16:01 | 1235.00 | 867.99 | 5886.23 | 0.00 | 0.00 | 0.00 | 0.00 | 428.91 | 0.00 |
| June | 3000.16 | 06-JUN-15:10 | 71.25 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 463.95 | 0.00 |
| July | 2609.02 | 02-JUL-17:07 | 1446.38 | 820.27 | 4120.36 | 0.00 | 0.00 | 0.00 | 0.00 | 133.06 | 0.00 |
| August | 2395.56 | 07-AUG-16:07 | 864.50 | 607.59 | 4120.36 | 0.00 | 0.00 | 0.00 | 0.00 | 152.48 | 0.00 |
| September | 2065.92 | 22-SEP-16:04 | 864.50 | 607.59 | 4120.36 | 0.00 | 0.00 | 0.00 | 0.00 | 149.60 | 0.00 |
| October | 2011.46 | 03-OCT-15:10 | 71.25 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 211.06 | 0.00 |
| November | 1215.76 | 09-NOV-14:20 | 59.38 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 19.39 | 0.00 |
| December | 422.82 | 28-DEC-17:10 | 494.00 | 347.20 | 2354.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.46 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 362.97 | 59.38 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 3000.16 | 1446.38 | 867.99 | 5886.23 | 0.00 | 0.00 | 0.00 | 0.00 | 463.95 | 10.46 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: T S1 APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 1484.43 | 12-JAN-15:00 | 0.00 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.58 |
| February | 2170.81 | 20-FEB-14:40 | 118.75 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 6.81 | 0.00 |
| March | 2593.01 | 12-MAR-15:20 | 237.50 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 37.25 | 0.00 |
| April | 3111.89 | 15-APR-15:10 | 237.50 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 429.22 | 0.00 |
| May | 3060.80 | 05-MAY-15:10 | 0.00 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 459.08 | 0.00 |
| June | 3073.45 | 06-JUN-15:10 | 0.00 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 463.95 | 0.00 |
| July | 2679.11 | 02-JUL-16:15 | 950.00 | 347.20 | 2354.49 | 0.00 | 0.00 | 0.00 | 0.00 | 137.86 | 0.00 |
| August | 2498.58 | 06-AUG-16:03 | 1425.00 | 520.80 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 127.94 | 0.00 |
| September | 2771.47 | 27-SEP-14:10 | 0.00 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 171.73 | 0.00 |
| October | 2915.91 | 03-OCT-14:10 | 0.00 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 219.81 | 0.00 |
| November | 2588.12 | 04-NOV-14:10 | 0.00 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 27.66 | 0.00 |
| December | 1762.91 | 02-DEC-14:20 | 118.75 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.09 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 1484.43 | 0.00 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 3111.89 | 1425.00 | 520.80 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 463.95 | 7.58 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: T S2 APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 1488.41 | 12-JAN-15:00 | 0.00 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.58 |
| February | 2177.04 | 20-FEB-14:40 | 118.75 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 6.81 | 0.00 |
| March | 2590.93 | 12-MAR-15:20 | 237.50 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 37.25 | 0.00 |
| April | 3110.03 | 15-APR-15:10 | 237.50 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 429.22 | 0.00 |
| May | 3058.33 | 05-MAY-15:10 | 0.00 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 459.08 | 0.00 |
| June | 3070.10 | 06-JUN-15:10 | 0.00 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 463.95 | 0.00 |
| July | 2669.08 | 02-JUL-16:15 | 950.00 | 347.20 | 2354.49 | 0.00 | 0.00 | 0.00 | 0.00 | 137.86 | 0.00 |
| August | 2493.15 | 07-AUG-15:10 | 0.00 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 161.63 | 0.00 |
| September | 2774.55 | 27-SEP-14:10 | 0.00 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 171.73 | 0.00 |
| October | 2919.47 | 03-OCT-14:10 | 0.00 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 219.81 | 0.00 |
| November | 2590.85 | 04-NOV-14:10 | 0.00 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 27.66 | 0.00 |
| December | 1767.63 | 02-DEC-14:20 | 118.75 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.09 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 1488.41 | 0.00 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 3110.03 | 950.00 | 347.20 | 2354.49 | 0.00 | 0.00 | 0.00 | 0.00 | 463.95 | 7.58 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: T CORRIDOR
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 0.00 | 01-JAN-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 01-FEB-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 01-MAR-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 01-APR-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 01-MAY-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.89 | 0.00 |
| June | 0.00 | 01-JUN-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 01-JUL-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.23 | 0.00 |
| August | 0.00 | 01-AUG-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.61 | 0.00 |
| September | 0.00 | 01-SEP-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.37 | 0.00 |
| October | 0.00 | 01-OCT-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 01-NOV-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 01-DEC-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.32 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
| Minimum of Months | 0.00 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.23 | 6.32 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: G CORRIDOR
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 0.00 | 01-JAN-00:10 | 397.10 | 370.63 | 56.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 01-FEB-00:10 | 397.10 | 370.63 | 56.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 01-MAR-00:10 | 397.10 | 370.63 | 56.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 01-APR-00:10 | 397.10 | 370.63 | 56.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 01-MAY-00:10 | 397.10 | 370.63 | 56.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.81 | 0.00 |
| June | 0.00 | 01-JUN-00:10 | 397.10 | 370.63 | 56.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 01-JUL-00:10 | 397.10 | 370.63 | 56.17 | 0.00 | 0.00 | 0.00 | 0.00 | 8.89 | 0.00 |
| August | 0.00 | 01-AUG-00:10 | 397.10 | 370.63 | 56.17 | 0.00 | 0.00 | 0.00 | 0.00 | 2.93 | 0.00 |
| September | 0.00 | 01-SEP-00:10 | 397.10 | 370.63 | 56.17 | 0.00 | 0.00 | 0.00 | 0.00 | 1.62 | 0.00 |
| October | 0.00 | 01-OCT-00:10 | 397.10 | 370.63 | 56.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 01-NOV-00:10 | 397.10 | 370.63 | 56.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 01-DEC-00:10 | 397.10 | 370.63 | 56.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.74 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 0.00 | 397.10 | 370.63 | 56.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 397.10 | 370.63 | 56.17 | 0.00 | 0.00 | 0.00 | 0.00 | 8.89 | 3.74 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: M CORRIDOR
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 0.00 | 01-JAN-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 01-FEB-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 01-MAR-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 01-APR-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 01-MAY-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.47 | 0.00 |
| June | 0.00 | 01-JUN-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 01-JUL-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.11 | 0.00 |
| August | 0.00 | 01-AUG-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.50 | 0.00 |
| September | 0.00 | 01-SEP-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.65 | 0.00 |
| October | 0.00 | 01-OCT-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 01-NOV-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 01-DEC-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.35 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
| Minimum of Months | 0.00 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.11 | 5.35 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
| January | 0.953025E+11 | 68740.73 | 01-JAN-17:49 | 0.427387E+10 | 12112.07 | 03-JAN-06:00 |
| February | 0.915974E+11 | 73392.45 | 23-FEB-18:30 | 0.869936E+09 | 6869.12 | 11-FEB-05:00 |
| March | 0.115277E+12 | 77711.86 | 10-MAR-19:30 | 0.00 | 0.00 | 01-MAR-00:10 |
| April | 0.131682E+12 | 88243.05 | 26-APR-17:40 | 0.00 | 0.00 | 01-APR-00:10 |
| May | 0.152936E+12 | 95009.67 | 05-MAY-17:19 | 0.00 | 0.00 | 01-MAY-00:10 |
| June | 0.152809E+12 | 96729.73 | 10-JUN-17:10 | 0.00 | 0.00 | 01-JUN-00:10 |
| July | 0.158983E+12 | 95884.91 | 01-JUL-16:49 | 0.00 | 0.00 | 01-JUL-00:10 |
| August | 0.153282E+12 | 91163.62 | 07-AUG-17:40 | 0.00 | 0.00 | 01-AUG-00:10 |
| September | 0.140618E+12 | 94112.27 | 17-SEP-17:30 | 0.00 | 0.00 | 01-SEP-00:10 |
| October | 0.126969E+12 | 88401.49 | 03-OCT-17:19 | 0.00 | 0.00 | 01-OCT-00:10 |
| November | 0.106453E+12 | 73964.65 | 03-NOV-17:19 | 46762359.75 | 1478.48 | 26-NOV-05:00 |
| December | 0.973910E+11 | 66728.63 | 28-DEC-18:30 | 0.231735E+10 | 9004.66 | 23-DEC-05:00 |
| Annual Sum or Average | 0.152330E+13 | 0.750793E+10 | ||||
| Minimum of Months | 0.915974E+11 | 66728.63 | 0.00 | 0.00 | ||
| Maximum of Months | 0.158983E+12 | 96729.73 | 0.427387E+10 | 12112.07 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| INTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [J] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
| January | 0.840929E+10 | 0.480937E+10 | 0.389380E+11 | 0.00 | 0.552857E+10 | 0.00 | 0.00 | 0.263338E+10 | 0.00 | 0.00 | 0.00 | 0.349839E+11 | 0.00 |
| February | 0.760941E+10 | 0.416189E+10 | 0.351823E+11 | 0.00 | 0.625463E+10 | 0.00 | 0.00 | 0.733192E+10 | 0.00 | 0.00 | 0.00 | 0.310572E+11 | 0.00 |
| March | 0.845392E+10 | 0.431278E+10 | 0.389781E+11 | 0.00 | 0.102266E+11 | 0.00 | 0.00 | 0.206258E+11 | 0.00 | 0.00 | 0.00 | 0.326802E+11 | 0.00 |
| April | 0.814762E+10 | 0.388494E+10 | 0.376905E+11 | 0.00 | 0.144404E+11 | 0.00 | 0.00 | 0.382014E+11 | 0.00 | 0.00 | 0.00 | 0.293171E+11 | 0.00 |
| May | 0.843904E+10 | 0.376079E+10 | 0.389647E+11 | 0.00 | 0.185232E+11 | 0.00 | 0.00 | 0.554209E+11 | 0.00 | 0.00 | 0.00 | 0.278279E+11 | 0.00 |
| June | 0.817737E+10 | 0.350294E+10 | 0.377173E+11 | 0.00 | 0.190723E+11 | 0.00 | 0.00 | 0.592084E+11 | 0.00 | 0.00 | 0.00 | 0.251306E+11 | 0.00 |
| July | 0.840929E+10 | 0.369394E+10 | 0.389380E+11 | 0.00 | 0.201285E+11 | 0.00 | 0.00 | 0.626155E+11 | 0.00 | 0.00 | 0.00 | 0.251980E+11 | 0.00 |
| August | 0.845392E+10 | 0.389831E+10 | 0.389781E+11 | 0.00 | 0.189853E+11 | 0.00 | 0.00 | 0.572150E+11 | 0.00 | 0.00 | 0.00 | 0.257514E+11 | 0.00 |
| September | 0.814762E+10 | 0.404920E+10 | 0.376905E+11 | 0.00 | 0.166362E+11 | 0.00 | 0.00 | 0.475194E+11 | 0.00 | 0.00 | 0.00 | 0.265753E+11 | 0.00 |
| October | 0.842417E+10 | 0.448468E+10 | 0.389514E+11 | 0.00 | 0.131245E+11 | 0.00 | 0.00 | 0.321239E+11 | 0.00 | 0.00 | 0.00 | 0.298599E+11 | 0.00 |
| November | 0.814762E+10 | 0.458973E+10 | 0.376905E+11 | 0.00 | 0.881941E+10 | 0.00 | 0.00 | 0.159270E+11 | 0.00 | 0.00 | 0.00 | 0.312791E+11 | 0.00 |
| December | 0.840929E+10 | 0.489914E+10 | 0.389380E+11 | 0.00 | 0.606072E+10 | 0.00 | 0.00 | 0.486116E+10 | 0.00 | 0.00 | 0.00 | 0.342227E+11 | 0.00 |
| Annual Sum or Average | 0.992286E+11 | 0.500477E+11 | 0.458657E+12 | 0.00 | 0.157800E+12 | 0.00 | 0.00 | 0.403684E+12 | 0.00 | 0.00 | 0.00 | 0.353883E+12 | 0.00 |
| Minimum of Months | 0.760941E+10 | 0.350294E+10 | 0.351823E+11 | 0.00 | 0.552857E+10 | 0.00 | 0.00 | 0.263338E+10 | 0.00 | 0.00 | 0.00 | 0.251306E+11 | 0.00 |
| Maximum of Months | 0.845392E+10 | 0.489914E+10 | 0.389781E+11 | 0.00 | 0.201285E+11 | 0.00 | 0.00 | 0.626155E+11 | 0.00 | 0.00 | 0.00 | 0.349839E+11 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| INTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
| January | 0.00 | 0.00 | 0.427387E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.869936E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 46762359.75 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.231735E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.750793E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.427387E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| INTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
| January | 5904.43 | 01-JAN-19:10 | 3183.33 | 01-JAN-00:10 | 22709.69 | 03-JAN-17:10 | 0.00 | 3772.64 | 12-JAN-15:20 | 0.00 | 0.00 | 01-JAN-00:10 |
| February | 5904.43 | 01-FEB-19:10 | 3183.33 | 01-FEB-00:10 | 22709.69 | 01-FEB-17:10 | 0.00 | 5358.22 | 22-FEB-15:09 | 0.00 | 0.00 | 01-FEB-00:10 |
| March | 5904.43 | 01-MAR-19:10 | 3183.33 | 01-MAR-00:10 | 22709.69 | 01-MAR-17:10 | 0.00 | 7531.66 | 28-MAR-16:10 | 0.00 | 0.00 | 01-MAR-00:10 |
| April | 5904.43 | 01-APR-18:10 | 3183.33 | 01-APR-00:10 | 22709.69 | 03-APR-16:10 | 0.00 | 9757.54 | 15-APR-15:09 | 0.00 | 0.00 | 01-APR-00:10 |
| May | 5904.43 | 01-MAY-18:10 | 3183.33 | 01-MAY-00:10 | 22709.69 | 01-MAY-16:10 | 0.00 | 10910.71 | 05-MAY-16:10 | 0.00 | 0.00 | 01-MAY-00:10 |
| June | 5904.43 | 01-JUN-18:10 | 3183.33 | 01-JUN-00:10 | 22709.69 | 01-JUN-16:10 | 0.00 | 10921.37 | 06-JUN-16:10 | 0.00 | 0.00 | 01-JUN-00:10 |
| July | 5904.43 | 01-JUL-18:10 | 3183.33 | 01-JUL-00:10 | 22709.69 | 03-JUL-16:10 | 0.00 | 10608.65 | 01-JUL-16:19 | 0.00 | 0.00 | 01-JUL-00:10 |
| August | 5904.43 | 01-AUG-18:10 | 3183.33 | 01-AUG-00:10 | 22709.69 | 01-AUG-16:10 | 0.00 | 9894.87 | 07-AUG-16:10 | 0.00 | 0.00 | 01-AUG-00:10 |
| September | 5904.43 | 01-SEP-18:10 | 3183.33 | 01-SEP-00:10 | 22709.69 | 01-SEP-16:10 | 0.00 | 9284.06 | 22-SEP-15:09 | 0.00 | 0.00 | 01-SEP-00:10 |
| October | 5904.43 | 01-OCT-18:10 | 3183.33 | 01-OCT-00:10 | 22709.69 | 02-OCT-16:10 | 0.00 | 8724.35 | 03-OCT-15:09 | 0.00 | 0.00 | 01-OCT-00:10 |
| November | 5904.43 | 01-NOV-18:10 | 3183.33 | 01-NOV-00:10 | 22709.69 | 01-NOV-16:10 | 0.00 | 6376.64 | 04-NOV-15:09 | 0.00 | 0.00 | 01-NOV-00:10 |
| December | 5904.43 | 01-DEC-19:10 | 3183.33 | 01-DEC-00:10 | 22709.69 | 01-DEC-17:10 | 0.00 | 4466.77 | 01-DEC-14:30 | 0.00 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 5904.43 | 3183.33 | 22709.69 | 0.00 | 3772.64 | 0.00 | 0.00 | |||||
| Maximum of Months | 5904.43 | 3183.33 | 22709.69 | 0.00 | 10921.37 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| COOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY {Maximum} [W] | HEATRECOVERY:ELECTRICITY {TIMESTAMP} | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
| January | 7625.95 | 12-JAN-15:20 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 37136.47 | 01-JAN-08:30 | 0.00 |
| February | 13810.78 | 22-FEB-15:09 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 32539.37 | 26-FEB-08:50 | 0.00 |
| March | 22836.49 | 28-MAR-15:30 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 27837.01 | 12-MAR-05:49 | 0.00 |
| April | 32318.41 | 27-APR-15:09 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 25823.10 | 18-APR-05:49 | 0.00 |
| May | 37062.12 | 05-MAY-15:20 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 25231.35 | 09-MAY-07:00 | 0.00 |
| June | 38499.90 | 06-JUN-15:09 | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 24263.40 | 21-JUN-07:40 | 0.00 |
| July | 37529.47 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 26322.99 | 30-JUL-07:49 | 0.00 |
| August | 34684.22 | 07-AUG-15:20 | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 26855.79 | 21-AUG-06:19 | 0.00 |
| September | 31865.62 | 22-SEP-15:09 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 30536.89 | 30-SEP-06:30 | 0.00 |
| October | 29147.15 | 03-OCT-15:09 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 31752.40 | 27-OCT-07:30 | 0.00 |
| November | 18023.47 | 09-NOV-13:50 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 30114.33 | 14-NOV-07:40 | 0.00 |
| December | 10155.43 | 01-DEC-14:30 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 31026.97 | 18-DEC-07:10 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
| Minimum of Months | 7625.95 | 0.00 | 0.00 | 0.00 | 24263.40 | 0.00 | |||
| Maximum of Months | 38499.90 | 0.00 | 0.00 | 0.00 | 37136.47 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
| January | 68740.73 | 01-JAN-17:49 | 4289.87 | 22609.62 | 3183.33 | 0.00 | 1797.85 | 0.00 | 0.00 | 194.70 | 0.00 |
| February | 73392.45 | 23-FEB-18:30 | 5231.74 | 22609.62 | 3183.33 | 0.00 | 4015.39 | 0.00 | 0.00 | 7918.50 | 0.00 |
| March | 77711.86 | 10-MAR-19:30 | 5904.43 | 20531.10 | 3183.33 | 0.00 | 5980.99 | 0.00 | 0.00 | 15843.38 | 0.00 |
| April | 88243.05 | 26-APR-17:40 | 5231.74 | 22609.62 | 0.00 | 0.00 | 8708.37 | 0.00 | 0.00 | 27837.32 | 0.00 |
| May | 95009.67 | 05-MAY-17:19 | 5231.74 | 22609.62 | 0.00 | 0.00 | 10565.35 | 0.00 | 0.00 | 34560.20 | 0.00 |
| June | 96729.73 | 10-JUN-17:10 | 5231.74 | 22609.62 | 0.00 | 0.00 | 10490.68 | 0.00 | 0.00 | 36852.21 | 0.00 |
| July | 95884.91 | 01-JUL-16:49 | 4289.87 | 22609.62 | 0.00 | 0.00 | 10529.73 | 0.00 | 0.00 | 37138.80 | 0.00 |
| August | 91163.62 | 07-AUG-17:40 | 5231.74 | 22609.62 | 0.00 | 0.00 | 9669.58 | 0.00 | 0.00 | 32641.15 | 0.00 |
| September | 94112.27 | 17-SEP-17:30 | 5231.74 | 22609.62 | 0.00 | 0.00 | 8899.70 | 0.00 | 0.00 | 29386.56 | 0.00 |
| October | 88401.49 | 03-OCT-17:19 | 5231.74 | 22609.62 | 0.00 | 0.00 | 7739.28 | 0.00 | 0.00 | 23263.34 | 0.00 |
| November | 73964.65 | 03-NOV-17:19 | 5231.74 | 22609.62 | 0.00 | 0.00 | 5298.69 | 0.00 | 0.00 | 12781.43 | 0.00 |
| December | 66728.63 | 28-DEC-18:30 | 5231.74 | 22609.62 | 3183.33 | 0.00 | 3485.00 | 0.00 | 0.00 | 6098.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
| Minimum of Months | 66728.63 | 4289.87 | 20531.10 | 0.00 | 0.00 | 1797.85 | 0.00 | 0.00 | 194.70 | 0.00 | |
| Maximum of Months | 96729.73 | 5904.43 | 22609.62 | 3183.33 | 0.00 | 10565.35 | 0.00 | 0.00 | 37138.80 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| INTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | |
| January | 0.00 | 0.00 | 12112.07 | 03-JAN-06:00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 6869.12 | 11-FEB-05:00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 1478.48 | 26-NOV-05:00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 9004.66 | 23-DEC-05:00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 12112.07 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: G SW APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: G NW APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: OFFICE
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 24.58 | 0.50 | 24.58 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.50 | 24.58 | 0.50 | 24.58 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 24.58 | 0.50 | 24.58 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: G NE APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: G N1 APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: G N2 APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: G S1 APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: G S2 APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: M SW APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: M NW APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: M SE APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: M NE APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: M N1 APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: M N2 APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: M S1 APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: M S2 APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: T SW APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: T NW APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: T SE APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: T NE APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: T N1 APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: T N2 APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: T S1 APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: T S2 APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: T CORRIDOR
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: G CORRIDOR
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: M CORRIDOR
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: G SW APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 391.67 | 23.11 | 2.00 | 23.11 | 0.00 | 23.11 |
| February | 201.67 | 23.30 | 55.33 | 23.45 | 0.00 | 23.45 |
| March | 26.50 | 23.77 | 219.83 | 23.97 | 0.00 | 23.97 |
| April | 0.00 | 0.00 | 354.33 | 24.00 | 0.00 | 24.00 |
| May | 31.50 | 24.00 | 515.00 | 24.00 | 31.50 | 24.00 |
| June | 126.50 | 24.00 | 492.00 | 24.00 | 126.50 | 24.00 |
| July | 354.17 | 24.00 | 533.00 | 24.00 | 354.17 | 24.00 |
| August | 378.50 | 24.00 | 506.00 | 24.00 | 378.50 | 24.00 |
| September | 239.50 | 24.00 | 510.00 | 24.00 | 239.50 | 24.00 |
| October | 6.17 | 24.00 | 523.00 | 24.00 | 6.17 | 24.00 |
| November | 0.00 | 0.00 | 329.33 | 24.00 | 0.00 | 24.00 |
| December | 217.67 | 23.57 | 28.17 | 23.62 | 0.00 | 23.62 |
| Annual Sum or Average | 1973.83 | 23.70 | 4068.00 | 23.90 | 1136.33 | 23.92 |
| Minimum of Months | 0.00 | 0.00 | 2.00 | 23.11 | 0.00 | 23.11 |
| Maximum of Months | 391.67 | 24.00 | 533.00 | 24.00 | 378.50 | 24.00 |
Report: ComfortReportSimple55Monthly
For: G NW APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 738.00 | 22.54 | 0.00 | 22.54 | 0.00 | 22.54 |
| February | 493.17 | 23.12 | 29.50 | 23.17 | 0.00 | 23.17 |
| March | 134.33 | 23.72 | 191.00 | 23.88 | 0.00 | 23.88 |
| April | 0.00 | 0.00 | 458.50 | 24.00 | 0.00 | 24.00 |
| May | 39.83 | 24.00 | 744.00 | 24.00 | 39.83 | 24.00 |
| June | 168.50 | 24.00 | 720.00 | 24.00 | 168.50 | 24.00 |
| July | 469.83 | 24.00 | 744.00 | 24.00 | 469.83 | 24.00 |
| August | 530.33 | 24.00 | 744.00 | 24.00 | 530.33 | 24.00 |
| September | 331.00 | 24.00 | 720.00 | 24.00 | 331.00 | 24.00 |
| October | 12.00 | 24.00 | 728.00 | 24.00 | 12.00 | 24.00 |
| November | 41.50 | 23.75 | 222.00 | 23.96 | 0.00 | 23.96 |
| December | 585.83 | 23.33 | 0.00 | 23.33 | 0.00 | 23.33 |
| Annual Sum or Average | 3544.33 | 23.45 | 5301.00 | 23.78 | 1551.50 | 23.81 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 22.54 | 0.00 | 22.54 |
| Maximum of Months | 738.00 | 24.00 | 744.00 | 24.00 | 530.33 | 24.00 |
Report: ComfortReportSimple55Monthly
For: OFFICE
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 19.83 | 23.75 | 34.33 | 24.03 | 0.00 | 24.03 |
| February | 2.00 | 24.05 | 99.83 | 24.19 | 0.00 | 24.19 |
| March | 0.00 | 0.00 | 161.00 | 24.23 | 0.00 | 24.23 |
| April | 3.67 | 25.67 | 140.00 | 24.27 | 3.67 | 24.31 |
| May | 21.00 | 25.52 | 154.00 | 24.40 | 21.00 | 24.52 |
| June | 26.67 | 25.36 | 154.00 | 24.41 | 26.67 | 24.53 |
| July | 29.83 | 25.19 | 140.00 | 24.42 | 29.83 | 24.54 |
| August | 33.00 | 25.23 | 161.00 | 24.42 | 33.00 | 24.54 |
| September | 25.83 | 25.34 | 140.00 | 24.42 | 25.83 | 24.54 |
| October | 9.33 | 25.58 | 147.00 | 24.32 | 9.33 | 24.39 |
| November | 0.00 | 0.00 | 140.00 | 24.23 | 0.00 | 24.23 |
| December | 0.50 | 24.11 | 112.00 | 24.23 | 0.00 | 24.23 |
| Annual Sum or Average | 171.67 | 25.14 | 1583.17 | 24.33 | 149.33 | 24.41 |
| Minimum of Months | 0.00 | 0.00 | 34.33 | 24.03 | 0.00 | 24.03 |
| Maximum of Months | 33.00 | 25.67 | 161.00 | 24.42 | 33.00 | 24.54 |
Report: ComfortReportSimple55Monthly
For: G NE APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 738.33 | 22.56 | 0.00 | 22.56 | 0.00 | 22.56 |
| February | 484.17 | 23.18 | 30.33 | 23.23 | 0.00 | 23.23 |
| March | 114.17 | 23.71 | 204.00 | 23.90 | 0.00 | 23.90 |
| April | 0.00 | 0.00 | 458.83 | 24.00 | 0.00 | 24.00 |
| May | 39.00 | 24.00 | 744.00 | 24.00 | 39.00 | 24.00 |
| June | 177.33 | 24.00 | 720.00 | 24.00 | 177.33 | 24.00 |
| July | 471.83 | 24.00 | 744.00 | 24.00 | 471.83 | 24.00 |
| August | 534.50 | 24.00 | 744.00 | 24.00 | 534.50 | 24.00 |
| September | 333.83 | 24.00 | 720.00 | 24.00 | 333.83 | 24.00 |
| October | 11.67 | 24.00 | 735.83 | 24.00 | 11.67 | 24.00 |
| November | 33.83 | 23.73 | 228.00 | 23.96 | 0.00 | 23.96 |
| December | 582.33 | 23.36 | 0.00 | 23.36 | 0.00 | 23.36 |
| Annual Sum or Average | 3521.00 | 23.47 | 5329.00 | 23.79 | 1568.17 | 23.82 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 22.56 | 0.00 | 22.56 |
| Maximum of Months | 738.33 | 24.00 | 744.00 | 24.00 | 534.50 | 24.00 |
Report: ComfortReportSimple55Monthly
For: G N1 APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 703.00 | 22.79 | 0.00 | 22.79 | 0.00 | 22.79 |
| February | 451.83 | 23.42 | 35.67 | 23.46 | 0.00 | 23.46 |
| March | 67.00 | 23.87 | 178.17 | 23.96 | 0.00 | 23.96 |
| April | 0.00 | 0.00 | 395.67 | 24.00 | 0.00 | 24.00 |
| May | 47.83 | 24.00 | 734.67 | 24.00 | 47.83 | 24.00 |
| June | 223.33 | 24.00 | 720.00 | 24.00 | 223.33 | 24.00 |
| July | 559.17 | 24.00 | 744.00 | 24.00 | 559.17 | 24.00 |
| August | 586.67 | 24.00 | 744.00 | 24.00 | 586.67 | 24.00 |
| September | 416.17 | 24.00 | 720.00 | 24.00 | 416.17 | 24.00 |
| October | 12.33 | 24.00 | 693.83 | 24.00 | 12.33 | 24.00 |
| November | 19.50 | 23.89 | 175.00 | 23.99 | 0.00 | 23.99 |
| December | 521.67 | 23.57 | 1.33 | 23.57 | 0.00 | 23.57 |
| Annual Sum or Average | 3608.50 | 23.63 | 5142.33 | 23.85 | 1845.50 | 23.87 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 22.79 | 0.00 | 22.79 |
| Maximum of Months | 703.00 | 24.00 | 744.00 | 24.00 | 586.67 | 24.00 |
Report: ComfortReportSimple55Monthly
For: G N2 APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 703.00 | 22.79 | 0.00 | 22.79 | 0.00 | 22.79 |
| February | 450.33 | 23.42 | 35.67 | 23.46 | 0.00 | 23.46 |
| March | 66.17 | 23.87 | 178.67 | 23.96 | 0.00 | 23.96 |
| April | 0.00 | 0.00 | 396.83 | 24.00 | 0.00 | 24.00 |
| May | 47.83 | 24.00 | 734.67 | 24.00 | 47.83 | 24.00 |
| June | 223.67 | 24.00 | 720.00 | 24.00 | 223.67 | 24.00 |
| July | 559.33 | 24.00 | 744.00 | 24.00 | 559.33 | 24.00 |
| August | 586.50 | 24.00 | 744.00 | 24.00 | 586.50 | 24.00 |
| September | 415.67 | 24.00 | 720.00 | 24.00 | 415.67 | 24.00 |
| October | 12.33 | 24.00 | 694.17 | 24.00 | 12.33 | 24.00 |
| November | 18.83 | 23.89 | 175.17 | 23.99 | 0.00 | 23.99 |
| December | 520.17 | 23.57 | 1.33 | 23.57 | 0.00 | 23.57 |
| Annual Sum or Average | 3603.83 | 23.63 | 5144.50 | 23.85 | 1845.33 | 23.87 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 22.79 | 0.00 | 22.79 |
| Maximum of Months | 703.00 | 24.00 | 744.00 | 24.00 | 586.50 | 24.00 |
Report: ComfortReportSimple55Monthly
For: G S1 APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 290.83 | 23.40 | 1.33 | 23.40 | 0.00 | 23.40 |
| February | 94.67 | 23.50 | 65.50 | 23.71 | 0.00 | 23.71 |
| March | 0.83 | 23.83 | 225.17 | 24.00 | 0.00 | 24.00 |
| April | 0.00 | 0.00 | 319.50 | 24.00 | 0.00 | 24.00 |
| May | 37.00 | 24.00 | 511.50 | 24.00 | 37.00 | 24.00 |
| June | 171.17 | 24.00 | 492.00 | 24.00 | 171.17 | 24.00 |
| July | 415.67 | 24.00 | 533.00 | 24.00 | 415.67 | 24.00 |
| August | 425.67 | 24.00 | 506.00 | 24.00 | 425.67 | 24.00 |
| September | 298.50 | 24.00 | 510.00 | 24.00 | 298.50 | 24.00 |
| October | 5.83 | 24.00 | 523.50 | 24.00 | 5.83 | 24.00 |
| November | 0.00 | 0.00 | 342.33 | 24.00 | 0.00 | 24.00 |
| December | 89.00 | 23.73 | 35.50 | 23.81 | 0.00 | 23.81 |
| Annual Sum or Average | 1829.17 | 23.87 | 4065.33 | 23.96 | 1353.83 | 23.97 |
| Minimum of Months | 0.00 | 0.00 | 1.33 | 23.40 | 0.00 | 23.40 |
| Maximum of Months | 425.67 | 24.00 | 533.00 | 24.00 | 425.67 | 24.00 |
Report: ComfortReportSimple55Monthly
For: G S2 APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 265.33 | 23.38 | 9.17 | 23.40 | 0.00 | 23.40 |
| February | 81.83 | 23.54 | 73.50 | 23.76 | 0.00 | 23.76 |
| March | 0.00 | 0.00 | 257.50 | 24.00 | 0.00 | 24.00 |
| April | 0.00 | 0.00 | 368.83 | 24.00 | 0.00 | 24.00 |
| May | 27.00 | 24.00 | 513.67 | 24.00 | 27.00 | 24.00 |
| June | 129.33 | 24.00 | 492.00 | 24.00 | 129.33 | 24.00 |
| July | 372.17 | 24.00 | 533.00 | 24.00 | 372.17 | 24.00 |
| August | 403.17 | 24.00 | 506.00 | 24.00 | 403.17 | 24.00 |
| September | 249.33 | 24.00 | 510.00 | 24.00 | 249.33 | 24.00 |
| October | 3.00 | 24.00 | 524.00 | 24.00 | 3.00 | 24.00 |
| November | 0.00 | 0.00 | 391.33 | 24.00 | 0.00 | 24.00 |
| December | 77.17 | 23.74 | 41.50 | 23.83 | 0.00 | 23.83 |
| Annual Sum or Average | 1608.33 | 23.86 | 4220.50 | 23.96 | 1184.00 | 23.97 |
| Minimum of Months | 0.00 | 0.00 | 9.17 | 23.40 | 0.00 | 23.40 |
| Maximum of Months | 403.17 | 24.00 | 533.00 | 24.00 | 403.17 | 24.00 |
Report: ComfortReportSimple55Monthly
For: M SW APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 360.50 | 23.18 | 2.33 | 23.19 | 0.00 | 23.19 |
| February | 142.17 | 23.34 | 59.33 | 23.53 | 0.00 | 23.53 |
| March | 2.83 | 23.85 | 245.50 | 24.00 | 0.00 | 24.00 |
| April | 0.00 | 0.00 | 358.00 | 24.00 | 0.00 | 24.00 |
| May | 28.50 | 24.00 | 515.00 | 24.00 | 28.50 | 24.00 |
| June | 137.67 | 24.00 | 492.00 | 24.00 | 137.67 | 24.00 |
| July | 404.50 | 24.00 | 533.00 | 24.00 | 404.50 | 24.00 |
| August | 431.67 | 24.00 | 506.00 | 24.00 | 431.67 | 24.00 |
| September | 315.00 | 24.00 | 510.00 | 24.00 | 315.00 | 24.00 |
| October | 12.50 | 24.00 | 503.50 | 24.00 | 12.50 | 24.00 |
| November | 19.33 | 23.71 | 199.67 | 23.97 | 0.00 | 23.97 |
| December | 293.33 | 23.42 | 14.17 | 23.45 | 0.00 | 23.45 |
| Annual Sum or Average | 2148.00 | 23.74 | 3938.50 | 23.91 | 1329.83 | 23.92 |
| Minimum of Months | 0.00 | 0.00 | 2.33 | 23.19 | 0.00 | 23.19 |
| Maximum of Months | 431.67 | 24.00 | 533.00 | 24.00 | 431.67 | 24.00 |
Report: ComfortReportSimple55Monthly
For: M NW APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 715.00 | 22.70 | 0.00 | 22.70 | 0.00 | 22.70 |
| February | 367.00 | 23.30 | 41.33 | 23.37 | 0.00 | 23.37 |
| March | 35.33 | 23.78 | 277.83 | 23.98 | 0.00 | 23.98 |
| April | 0.00 | 0.00 | 467.83 | 24.00 | 0.00 | 24.00 |
| May | 35.33 | 24.00 | 744.00 | 24.00 | 35.33 | 24.00 |
| June | 181.83 | 24.00 | 720.00 | 24.00 | 181.83 | 24.00 |
| July | 542.83 | 24.00 | 744.00 | 24.00 | 542.83 | 24.00 |
| August | 598.33 | 24.00 | 744.00 | 24.00 | 598.33 | 24.00 |
| September | 431.33 | 24.00 | 720.00 | 24.00 | 431.33 | 24.00 |
| October | 26.33 | 24.00 | 633.17 | 24.00 | 26.33 | 24.00 |
| November | 118.00 | 23.68 | 81.00 | 23.81 | 0.00 | 23.81 |
| December | 637.33 | 23.17 | 0.00 | 23.17 | 0.00 | 23.17 |
| Annual Sum or Average | 3688.67 | 23.52 | 5173.17 | 23.80 | 1816.00 | 23.84 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 22.70 | 0.00 | 22.70 |
| Maximum of Months | 715.00 | 24.00 | 744.00 | 24.00 | 598.33 | 24.00 |
Report: ComfortReportSimple55Monthly
For: M SE APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 362.83 | 23.20 | 1.83 | 23.21 | 0.00 | 23.21 |
| February | 137.00 | 23.33 | 58.33 | 23.53 | 0.00 | 23.53 |
| March | 2.50 | 23.83 | 246.50 | 24.00 | 0.00 | 24.00 |
| April | 0.00 | 0.00 | 351.33 | 24.00 | 0.00 | 24.00 |
| May | 30.50 | 24.00 | 514.50 | 24.00 | 30.50 | 24.00 |
| June | 149.50 | 24.00 | 492.00 | 24.00 | 149.50 | 24.00 |
| July | 406.00 | 24.00 | 533.00 | 24.00 | 406.00 | 24.00 |
| August | 433.17 | 24.00 | 506.00 | 24.00 | 433.17 | 24.00 |
| September | 317.83 | 24.00 | 510.00 | 24.00 | 317.83 | 24.00 |
| October | 13.00 | 24.00 | 504.50 | 24.00 | 13.00 | 24.00 |
| November | 19.83 | 23.71 | 199.83 | 23.97 | 0.00 | 23.97 |
| December | 290.50 | 23.42 | 14.67 | 23.45 | 0.00 | 23.45 |
| Annual Sum or Average | 2162.67 | 23.74 | 3932.50 | 23.91 | 1350.00 | 23.93 |
| Minimum of Months | 0.00 | 0.00 | 1.83 | 23.21 | 0.00 | 23.21 |
| Maximum of Months | 433.17 | 24.00 | 533.00 | 24.00 | 433.17 | 24.00 |
Report: ComfortReportSimple55Monthly
For: M NE APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 721.50 | 22.75 | 0.00 | 22.75 | 0.00 | 22.75 |
| February | 344.17 | 23.34 | 39.17 | 23.41 | 0.00 | 23.41 |
| March | 23.67 | 23.79 | 290.67 | 23.98 | 0.00 | 23.98 |
| April | 0.00 | 0.00 | 481.33 | 24.00 | 0.00 | 24.00 |
| May | 35.50 | 24.00 | 741.00 | 24.00 | 35.50 | 24.00 |
| June | 193.50 | 24.00 | 720.00 | 24.00 | 193.50 | 24.00 |
| July | 547.50 | 24.00 | 744.00 | 24.00 | 547.50 | 24.00 |
| August | 599.67 | 24.00 | 744.00 | 24.00 | 599.67 | 24.00 |
| September | 430.83 | 24.00 | 720.00 | 24.00 | 430.83 | 24.00 |
| October | 26.33 | 24.00 | 637.50 | 24.00 | 26.33 | 24.00 |
| November | 106.17 | 23.69 | 79.17 | 23.82 | 0.00 | 23.82 |
| December | 651.67 | 23.23 | 0.00 | 23.23 | 0.00 | 23.23 |
| Annual Sum or Average | 3680.50 | 23.55 | 5196.83 | 23.81 | 1833.33 | 23.84 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 22.75 | 0.00 | 22.75 |
| Maximum of Months | 721.50 | 24.00 | 744.00 | 24.00 | 599.67 | 24.00 |
Report: ComfortReportSimple55Monthly
For: M N1 APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 612.33 | 23.02 | 0.00 | 23.02 | 0.00 | 23.02 |
| February | 278.83 | 23.60 | 42.83 | 23.65 | 0.00 | 23.65 |
| March | 3.17 | 23.84 | 199.33 | 24.00 | 0.00 | 24.00 |
| April | 0.00 | 0.00 | 394.67 | 24.00 | 0.00 | 24.00 |
| May | 46.67 | 24.00 | 691.50 | 24.00 | 46.67 | 24.00 |
| June | 242.17 | 24.00 | 720.00 | 24.00 | 242.17 | 24.00 |
| July | 617.17 | 24.00 | 744.00 | 24.00 | 617.17 | 24.00 |
| August | 632.83 | 24.00 | 744.00 | 24.00 | 632.83 | 24.00 |
| September | 489.00 | 24.00 | 720.00 | 24.00 | 489.00 | 24.00 |
| October | 22.83 | 24.00 | 560.50 | 24.00 | 22.83 | 24.00 |
| November | 59.67 | 23.87 | 68.17 | 23.94 | 0.00 | 23.94 |
| December | 539.83 | 23.51 | 0.00 | 23.51 | 0.00 | 23.51 |
| Annual Sum or Average | 3544.50 | 23.72 | 4885.00 | 23.88 | 2050.67 | 23.91 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 23.02 | 0.00 | 23.02 |
| Maximum of Months | 632.83 | 24.00 | 744.00 | 24.00 | 632.83 | 24.00 |
Report: ComfortReportSimple55Monthly
For: M N2 APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 611.83 | 23.02 | 0.00 | 23.02 | 0.00 | 23.02 |
| February | 276.33 | 23.60 | 43.17 | 23.65 | 0.00 | 23.65 |
| March | 2.83 | 23.84 | 199.83 | 24.00 | 0.00 | 24.00 |
| April | 0.00 | 0.00 | 394.50 | 24.00 | 0.00 | 24.00 |
| May | 46.67 | 24.00 | 692.17 | 24.00 | 46.67 | 24.00 |
| June | 242.17 | 24.00 | 720.00 | 24.00 | 242.17 | 24.00 |
| July | 617.17 | 24.00 | 744.00 | 24.00 | 617.17 | 24.00 |
| August | 632.17 | 24.00 | 744.00 | 24.00 | 632.17 | 24.00 |
| September | 489.17 | 24.00 | 720.00 | 24.00 | 489.17 | 24.00 |
| October | 22.83 | 24.00 | 560.33 | 24.00 | 22.83 | 24.00 |
| November | 60.00 | 23.87 | 67.67 | 23.94 | 0.00 | 23.94 |
| December | 537.50 | 23.51 | 0.00 | 23.51 | 0.00 | 23.51 |
| Annual Sum or Average | 3538.67 | 23.72 | 4885.67 | 23.88 | 2050.17 | 23.91 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 23.02 | 0.00 | 23.02 |
| Maximum of Months | 632.17 | 24.00 | 744.00 | 24.00 | 632.17 | 24.00 |
Report: ComfortReportSimple55Monthly
For: M S1 APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 226.33 | 23.47 | 1.17 | 23.47 | 0.00 | 23.47 |
| February | 63.17 | 23.59 | 64.00 | 23.80 | 0.00 | 23.80 |
| March | 0.00 | 0.00 | 235.17 | 24.00 | 0.00 | 24.00 |
| April | 0.00 | 0.00 | 310.67 | 24.00 | 0.00 | 24.00 |
| May | 34.50 | 24.00 | 490.17 | 24.00 | 34.50 | 24.00 |
| June | 185.50 | 24.00 | 492.00 | 24.00 | 185.50 | 24.00 |
| July | 458.33 | 24.00 | 533.00 | 24.00 | 458.33 | 24.00 |
| August | 453.33 | 24.00 | 506.00 | 24.00 | 453.33 | 24.00 |
| September | 348.83 | 24.00 | 510.00 | 24.00 | 348.83 | 24.00 |
| October | 10.00 | 24.00 | 506.67 | 24.00 | 10.00 | 24.00 |
| November | 0.00 | 0.00 | 219.33 | 24.00 | 0.00 | 24.00 |
| December | 162.67 | 23.71 | 23.83 | 23.75 | 0.00 | 23.75 |
| Annual Sum or Average | 1942.67 | 23.90 | 3892.00 | 23.97 | 1490.50 | 23.97 |
| Minimum of Months | 0.00 | 0.00 | 1.17 | 23.47 | 0.00 | 23.47 |
| Maximum of Months | 458.33 | 24.00 | 533.00 | 24.00 | 458.33 | 24.00 |
Report: ComfortReportSimple55Monthly
For: M S2 APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 226.00 | 23.47 | 1.17 | 23.47 | 0.00 | 23.47 |
| February | 62.83 | 23.59 | 63.83 | 23.80 | 0.00 | 23.80 |
| March | 0.00 | 0.00 | 234.83 | 24.00 | 0.00 | 24.00 |
| April | 0.00 | 0.00 | 310.67 | 24.00 | 0.00 | 24.00 |
| May | 34.67 | 24.00 | 489.67 | 24.00 | 34.67 | 24.00 |
| June | 185.67 | 24.00 | 492.00 | 24.00 | 185.67 | 24.00 |
| July | 458.33 | 24.00 | 533.00 | 24.00 | 458.33 | 24.00 |
| August | 453.33 | 24.00 | 506.00 | 24.00 | 453.33 | 24.00 |
| September | 348.83 | 24.00 | 510.00 | 24.00 | 348.83 | 24.00 |
| October | 10.00 | 24.00 | 506.50 | 24.00 | 10.00 | 24.00 |
| November | 0.00 | 0.00 | 219.17 | 24.00 | 0.00 | 24.00 |
| December | 162.83 | 23.71 | 24.00 | 23.75 | 0.00 | 23.75 |
| Annual Sum or Average | 1942.50 | 23.90 | 3890.83 | 23.97 | 1490.83 | 23.97 |
| Minimum of Months | 0.00 | 0.00 | 1.17 | 23.47 | 0.00 | 23.47 |
| Maximum of Months | 458.33 | 24.00 | 533.00 | 24.00 | 458.33 | 24.00 |
Report: ComfortReportSimple55Monthly
For: T SW APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 482.33 | 21.99 | 19.67 | 21.98 | 14.67 | 21.95 |
| February | 307.67 | 22.26 | 51.67 | 22.51 | 0.00 | 22.51 |
| March | 144.67 | 23.20 | 198.50 | 23.66 | 0.00 | 23.66 |
| April | 14.50 | 23.86 | 382.67 | 23.99 | 5.00 | 23.99 |
| May | 36.83 | 24.00 | 512.00 | 24.00 | 36.83 | 24.00 |
| June | 141.33 | 24.00 | 492.00 | 24.00 | 141.33 | 24.00 |
| July | 366.83 | 24.00 | 533.00 | 24.00 | 366.83 | 24.00 |
| August | 400.83 | 24.00 | 506.00 | 24.00 | 400.83 | 24.00 |
| September | 323.33 | 24.00 | 510.00 | 24.00 | 323.33 | 24.00 |
| October | 84.83 | 23.74 | 427.50 | 23.95 | 55.50 | 23.96 |
| November | 248.67 | 22.77 | 126.50 | 23.18 | 0.00 | 23.18 |
| December | 437.67 | 22.02 | 33.67 | 22.06 | 17.00 | 22.03 |
| Annual Sum or Average | 2989.50 | 23.06 | 3793.17 | 23.57 | 1361.33 | 23.63 |
| Minimum of Months | 14.50 | 21.99 | 19.67 | 21.98 | 0.00 | 21.95 |
| Maximum of Months | 482.33 | 24.00 | 533.00 | 24.00 | 400.83 | 24.00 |
Report: ComfortReportSimple55Monthly
For: T NW APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 730.50 | 21.83 | 81.17 | 21.76 | 81.17 | 21.70 |
| February | 505.00 | 22.32 | 33.67 | 22.42 | 0.00 | 22.42 |
| March | 210.83 | 23.12 | 288.33 | 23.63 | 0.00 | 23.63 |
| April | 18.67 | 23.85 | 552.00 | 23.99 | 6.00 | 23.99 |
| May | 43.00 | 24.00 | 741.17 | 24.00 | 43.00 | 24.00 |
| June | 178.83 | 24.00 | 720.00 | 24.00 | 178.83 | 24.00 |
| July | 475.67 | 24.00 | 744.00 | 24.00 | 475.67 | 24.00 |
| August | 546.50 | 24.00 | 744.00 | 24.00 | 546.50 | 24.00 |
| September | 424.33 | 24.00 | 720.00 | 24.00 | 424.33 | 24.00 |
| October | 133.50 | 23.71 | 594.50 | 23.94 | 85.00 | 23.95 |
| November | 391.67 | 22.73 | 108.67 | 23.01 | 0.00 | 23.01 |
| December | 718.50 | 22.04 | 53.17 | 21.98 | 53.17 | 21.92 |
| Annual Sum or Average | 4377.00 | 22.96 | 5380.67 | 23.49 | 1893.67 | 23.54 |
| Minimum of Months | 18.67 | 21.83 | 33.67 | 21.76 | 0.00 | 21.70 |
| Maximum of Months | 730.50 | 24.00 | 744.00 | 24.00 | 546.50 | 24.00 |
Report: ComfortReportSimple55Monthly
For: T SE APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 484.50 | 21.99 | 17.33 | 21.98 | 13.67 | 21.96 |
| February | 308.50 | 22.28 | 43.83 | 22.50 | 0.00 | 22.50 |
| March | 145.67 | 23.20 | 194.50 | 23.66 | 0.00 | 23.66 |
| April | 15.50 | 23.87 | 375.67 | 23.99 | 5.50 | 23.99 |
| May | 37.83 | 24.00 | 512.00 | 24.00 | 37.83 | 24.00 |
| June | 145.00 | 24.00 | 492.00 | 24.00 | 145.00 | 24.00 |
| July | 367.17 | 24.00 | 533.00 | 24.00 | 367.17 | 24.00 |
| August | 408.67 | 24.00 | 506.00 | 24.00 | 408.67 | 24.00 |
| September | 327.17 | 24.00 | 510.00 | 24.00 | 327.17 | 24.00 |
| October | 87.00 | 23.74 | 427.00 | 23.95 | 57.50 | 23.95 |
| November | 250.50 | 22.77 | 123.50 | 23.18 | 0.00 | 23.18 |
| December | 443.17 | 22.05 | 32.83 | 22.08 | 16.33 | 22.05 |
| Annual Sum or Average | 3020.67 | 23.07 | 3767.67 | 23.57 | 1378.83 | 23.63 |
| Minimum of Months | 15.50 | 21.99 | 17.33 | 21.98 | 0.00 | 21.96 |
| Maximum of Months | 484.50 | 24.00 | 533.00 | 24.00 | 408.67 | 24.00 |
Report: ComfortReportSimple55Monthly
For: T NE APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 734.33 | 21.82 | 70.83 | 21.76 | 70.83 | 21.71 |
| February | 504.00 | 22.40 | 32.83 | 22.50 | 0.00 | 22.50 |
| March | 196.00 | 23.14 | 303.00 | 23.66 | 0.00 | 23.66 |
| April | 17.83 | 23.85 | 557.83 | 24.00 | 6.00 | 24.00 |
| May | 42.50 | 24.00 | 741.17 | 24.00 | 42.50 | 24.00 |
| June | 177.00 | 24.00 | 720.00 | 24.00 | 177.00 | 24.00 |
| July | 472.83 | 24.00 | 744.00 | 24.00 | 472.83 | 24.00 |
| August | 544.83 | 24.00 | 744.00 | 24.00 | 544.83 | 24.00 |
| September | 419.50 | 24.00 | 720.00 | 24.00 | 419.50 | 24.00 |
| October | 129.50 | 23.71 | 605.67 | 23.95 | 84.17 | 23.95 |
| November | 382.67 | 22.77 | 101.17 | 23.02 | 0.00 | 23.02 |
| December | 731.33 | 22.09 | 49.67 | 22.03 | 49.67 | 21.97 |
| Annual Sum or Average | 4352.33 | 22.97 | 5390.17 | 23.50 | 1867.33 | 23.55 |
| Minimum of Months | 17.83 | 21.82 | 32.83 | 21.76 | 0.00 | 21.71 |
| Maximum of Months | 734.33 | 24.00 | 744.00 | 24.00 | 544.83 | 24.00 |
Report: ComfortReportSimple55Monthly
For: T N1 APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 738.17 | 21.90 | 8.83 | 21.89 | 8.83 | 21.88 |
| February | 516.00 | 22.59 | 24.83 | 22.65 | 0.00 | 22.65 |
| March | 168.83 | 23.33 | 261.83 | 23.74 | 0.00 | 23.74 |
| April | 12.83 | 23.92 | 516.00 | 24.00 | 3.33 | 24.00 |
| May | 45.50 | 24.00 | 739.67 | 24.00 | 45.50 | 24.00 |
| June | 200.17 | 24.00 | 720.00 | 24.00 | 200.17 | 24.00 |
| July | 514.67 | 24.00 | 744.00 | 24.00 | 514.67 | 24.00 |
| August | 583.67 | 24.00 | 744.00 | 24.00 | 583.67 | 24.00 |
| September | 447.50 | 24.00 | 720.00 | 24.00 | 447.50 | 24.00 |
| October | 106.50 | 23.80 | 595.83 | 23.97 | 74.17 | 23.97 |
| November | 379.50 | 23.03 | 52.83 | 23.15 | 0.00 | 23.15 |
| December | 741.67 | 22.18 | 21.33 | 22.15 | 21.33 | 22.12 |
| Annual Sum or Average | 4455.00 | 23.07 | 5149.17 | 23.56 | 1899.17 | 23.63 |
| Minimum of Months | 12.83 | 21.90 | 8.83 | 21.89 | 0.00 | 21.88 |
| Maximum of Months | 741.67 | 24.00 | 744.00 | 24.00 | 583.67 | 24.00 |
Report: ComfortReportSimple55Monthly
For: T N2 APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 738.00 | 21.90 | 9.00 | 21.89 | 9.00 | 21.88 |
| February | 514.17 | 22.59 | 25.17 | 22.65 | 0.00 | 22.65 |
| March | 167.33 | 23.32 | 262.17 | 23.74 | 0.00 | 23.74 |
| April | 12.83 | 23.92 | 515.50 | 24.00 | 3.33 | 24.00 |
| May | 45.50 | 24.00 | 739.67 | 24.00 | 45.50 | 24.00 |
| June | 200.17 | 24.00 | 720.00 | 24.00 | 200.17 | 24.00 |
| July | 513.83 | 24.00 | 744.00 | 24.00 | 513.83 | 24.00 |
| August | 583.17 | 24.00 | 744.00 | 24.00 | 583.17 | 24.00 |
| September | 447.67 | 24.00 | 720.00 | 24.00 | 447.67 | 24.00 |
| October | 106.17 | 23.80 | 597.00 | 23.97 | 73.83 | 23.97 |
| November | 378.83 | 23.03 | 53.33 | 23.15 | 0.00 | 23.15 |
| December | 741.83 | 22.18 | 21.33 | 22.15 | 21.33 | 22.12 |
| Annual Sum or Average | 4449.50 | 23.07 | 5151.17 | 23.56 | 1897.83 | 23.63 |
| Minimum of Months | 12.83 | 21.90 | 9.00 | 21.89 | 0.00 | 21.88 |
| Maximum of Months | 741.83 | 24.00 | 744.00 | 24.00 | 583.17 | 24.00 |
Report: ComfortReportSimple55Monthly
For: T S1 APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 472.67 | 22.22 | 3.50 | 22.23 | 0.00 | 22.23 |
| February | 277.83 | 22.50 | 45.50 | 22.71 | 0.00 | 22.71 |
| March | 104.50 | 23.40 | 195.00 | 23.79 | 0.00 | 23.79 |
| April | 8.83 | 23.92 | 356.17 | 24.00 | 2.83 | 24.00 |
| May | 38.33 | 24.00 | 511.17 | 24.00 | 38.33 | 24.00 |
| June | 157.83 | 24.00 | 492.00 | 24.00 | 157.83 | 24.00 |
| July | 395.17 | 24.00 | 533.00 | 24.00 | 395.17 | 24.00 |
| August | 421.67 | 24.00 | 506.00 | 24.00 | 421.67 | 24.00 |
| September | 340.33 | 24.00 | 510.00 | 24.00 | 340.33 | 24.00 |
| October | 63.33 | 23.84 | 438.67 | 23.98 | 46.33 | 23.98 |
| November | 208.50 | 23.06 | 135.33 | 23.43 | 0.00 | 23.43 |
| December | 419.67 | 22.29 | 13.67 | 22.34 | 0.00 | 22.34 |
| Annual Sum or Average | 2908.67 | 23.23 | 3740.00 | 23.66 | 1402.50 | 23.72 |
| Minimum of Months | 8.83 | 22.22 | 3.50 | 22.23 | 0.00 | 22.23 |
| Maximum of Months | 472.67 | 24.00 | 533.00 | 24.00 | 421.67 | 24.00 |
Report: ComfortReportSimple55Monthly
For: T S2 APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 472.33 | 22.22 | 3.50 | 22.23 | 0.00 | 22.23 |
| February | 278.00 | 22.50 | 45.67 | 22.71 | 0.00 | 22.71 |
| March | 104.67 | 23.40 | 194.67 | 23.79 | 0.00 | 23.79 |
| April | 8.67 | 23.91 | 355.67 | 24.00 | 2.50 | 24.00 |
| May | 38.33 | 24.00 | 511.17 | 24.00 | 38.33 | 24.00 |
| June | 158.00 | 24.00 | 492.00 | 24.00 | 158.00 | 24.00 |
| July | 395.17 | 24.00 | 533.00 | 24.00 | 395.17 | 24.00 |
| August | 421.83 | 24.00 | 506.00 | 24.00 | 421.83 | 24.00 |
| September | 340.67 | 24.00 | 510.00 | 24.00 | 340.67 | 24.00 |
| October | 63.50 | 23.84 | 438.33 | 23.98 | 46.50 | 23.98 |
| November | 208.33 | 23.05 | 134.00 | 23.42 | 0.00 | 23.42 |
| December | 419.33 | 22.29 | 13.67 | 22.34 | 0.00 | 22.34 |
| Annual Sum or Average | 2908.83 | 23.23 | 3737.67 | 23.66 | 1403.00 | 23.72 |
| Minimum of Months | 8.67 | 22.22 | 3.50 | 22.23 | 0.00 | 22.23 |
| Maximum of Months | 472.33 | 24.00 | 533.00 | 24.00 | 421.83 | 24.00 |
Report: ComfortReportSimple55Monthly
For: T CORRIDOR
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 737.67 | 22.61 | 743.83 | 22.62 | 737.67 | 22.62 |
| February | 662.50 | 23.86 | 671.33 | 23.87 | 662.50 | 23.87 |
| March | 744.00 | 25.42 | 744.00 | 25.42 | 744.00 | 25.42 |
| April | 720.00 | 26.45 | 720.00 | 26.45 | 720.00 | 26.45 |
| May | 744.00 | 26.93 | 744.00 | 26.93 | 744.00 | 26.93 |
| June | 720.00 | 26.98 | 720.00 | 26.98 | 720.00 | 26.98 |
| July | 744.00 | 26.85 | 744.00 | 26.85 | 744.00 | 26.85 |
| August | 744.00 | 26.65 | 744.00 | 26.65 | 744.00 | 26.65 |
| September | 720.00 | 26.40 | 720.00 | 26.40 | 720.00 | 26.40 |
| October | 744.00 | 25.87 | 744.00 | 25.87 | 744.00 | 25.87 |
| November | 720.00 | 24.70 | 720.00 | 24.70 | 720.00 | 24.70 |
| December | 744.00 | 23.03 | 744.00 | 23.03 | 744.00 | 23.03 |
| Annual Sum or Average | 8744.17 | 25.49 | 8759.17 | 25.49 | 8744.17 | 25.49 |
| Minimum of Months | 662.50 | 22.61 | 671.33 | 22.62 | 662.50 | 22.62 |
| Maximum of Months | 744.00 | 26.98 | 744.00 | 26.98 | 744.00 | 26.98 |
Report: ComfortReportSimple55Monthly
For: G CORRIDOR
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 622.33 | 22.57 | 107.67 | 22.64 | 62.83 | 22.58 |
| February | 301.17 | 23.36 | 336.50 | 24.17 | 105.33 | 24.23 |
| March | 226.17 | 25.56 | 692.00 | 25.82 | 201.33 | 25.85 |
| April | 463.67 | 27.70 | 718.33 | 27.51 | 463.67 | 27.57 |
| May | 744.00 | 28.31 | 744.00 | 28.31 | 744.00 | 28.31 |
| June | 720.00 | 28.43 | 720.00 | 28.43 | 720.00 | 28.43 |
| July | 744.00 | 28.13 | 744.00 | 28.13 | 744.00 | 28.13 |
| August | 744.00 | 27.83 | 744.00 | 27.83 | 744.00 | 27.83 |
| September | 720.00 | 27.59 | 720.00 | 27.59 | 720.00 | 27.59 |
| October | 561.83 | 27.05 | 739.00 | 26.98 | 560.17 | 27.01 |
| November | 219.50 | 25.22 | 655.50 | 25.65 | 186.67 | 25.69 |
| December | 348.83 | 23.07 | 280.83 | 23.84 | 85.50 | 23.92 |
| Annual Sum or Average | 6415.50 | 26.74 | 7201.83 | 26.93 | 5337.50 | 27.11 |
| Minimum of Months | 219.50 | 22.57 | 107.67 | 22.64 | 62.83 | 22.58 |
| Maximum of Months | 744.00 | 28.43 | 744.00 | 28.43 | 744.00 | 28.43 |
Report: ComfortReportSimple55Monthly
For: M CORRIDOR
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 744.00 | 24.61 | 744.00 | 24.61 | 744.00 | 24.61 |
| February | 672.00 | 25.32 | 672.00 | 25.32 | 672.00 | 25.32 |
| March | 744.00 | 25.86 | 744.00 | 25.86 | 744.00 | 25.86 |
| April | 720.00 | 26.26 | 720.00 | 26.26 | 720.00 | 26.26 |
| May | 744.00 | 26.45 | 744.00 | 26.45 | 744.00 | 26.45 |
| June | 720.00 | 26.43 | 720.00 | 26.43 | 720.00 | 26.43 |
| July | 744.00 | 26.35 | 744.00 | 26.35 | 744.00 | 26.35 |
| August | 744.00 | 26.25 | 744.00 | 26.25 | 744.00 | 26.25 |
| September | 720.00 | 26.17 | 720.00 | 26.17 | 720.00 | 26.17 |
| October | 744.00 | 26.04 | 744.00 | 26.04 | 744.00 | 26.04 |
| November | 720.00 | 25.71 | 720.00 | 25.71 | 720.00 | 25.71 |
| December | 744.00 | 25.05 | 744.00 | 25.05 | 744.00 | 25.05 |
| Annual Sum or Average | 8760.00 | 25.88 | 8760.00 | 25.88 | 8760.00 | 25.88 |
| Minimum of Months | 672.00 | 24.61 | 672.00 | 24.61 | 672.00 | 24.61 |
| Maximum of Months | 744.00 | 26.45 | 744.00 | 26.45 | 744.00 | 26.45 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_GSW
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 515.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 492.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 524.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 6145.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_GNW
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 8760.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_OFFICE
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 140.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 133.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 161.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 140.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 154.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 154.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 140.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 161.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 140.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 147.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 140.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 140.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 1750.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 133.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 161.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_GNE
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 8760.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_GN1
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 8760.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_GN2
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 8760.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_GS1
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 515.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 492.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 524.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 6145.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_GS2
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 515.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 492.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 524.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 6145.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_MSW
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 515.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 492.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 524.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 6145.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_MNW
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 8760.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_MSE
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 515.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 492.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 524.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 6145.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_MNE
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 8760.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_MN1
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 8760.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_MN2
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 8760.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_MS1
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 515.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 492.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 524.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 6145.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_MS2
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 515.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 492.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 524.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 6145.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_TSW
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 515.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 492.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 524.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 6145.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_TNW
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 8760.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_TSE
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 515.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 492.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 524.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 6145.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_TNE
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 8760.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_TN1
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 8760.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_TN2
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 8760.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_TS1
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 515.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 492.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 524.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 6145.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_TS2
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 515.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 492.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 524.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 6145.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_T CORRIDOR
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 8760.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_G CORRIDOR
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 8760.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_M CORRIDOR
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 8760.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: DXReportMonthly
For: SPLIT GSW COOLING COIL
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.394333E+09 | 0.102400E+09 | 266.91 | 0.388453E+09 | 5880062.35 | 0.00 | 0.22 | 12-JAN-15:20 | 0.00 | 01-JAN-00:10 | 1293.43 | 12-JAN-15:20 | 1293.43 | 12-JAN-15:20 | 61.50 | 13-JAN-14:40 | 330.77 | 12-JAN-15:20 | 0.00 | 01-JAN-00:10 |
| February | 0.956837E+09 | 0.246079E+09 | 389.49 | 0.918561E+09 | 38275596.72 | 0.00 | 0.31 | 20-FEB-16:10 | 0.00 | 01-FEB-00:10 | 1828.98 | 20-FEB-16:10 | 1828.98 | 20-FEB-16:10 | 298.74 | 25-FEB-17:10 | 473.83 | 20-FEB-16:10 | 0.00 | 01-FEB-00:10 |
| March | 0.233626E+10 | 0.614549E+09 | 671.10 | 0.218002E+10 | 0.156234E+09 | 0.00 | 0.43 | 28-MAR-16:01 | 0.00 | 01-MAR-02:00 | 2562.95 | 12-MAR-16:10 | 2487.21 | 28-MAR-16:01 | 338.10 | 10-MAR-21:00 | 732.10 | 28-MAR-16:01 | 0.00 | 01-MAR-00:10 |
| April | 0.415323E+10 | 0.115766E+10 | 720.00 | 0.387106E+10 | 0.282176E+09 | 0.00 | 0.58 | 27-APR-16:10 | 0.02 | 11-APR-05:05 | 3218.91 | 18-APR-16:01 | 3218.59 | 27-APR-16:09 | 421.12 | 18-APR-14:10 | 992.60 | 27-APR-16:10 | 0.00 | 01-APR-00:10 |
| May | 0.596184E+10 | 0.170296E+10 | 744.00 | 0.512248E+10 | 0.839361E+09 | 0.00 | 0.67 | 05-MAY-16:10 | 0.16 | 13-MAY-04:00 | 3627.21 | 05-MAY-16:30 | 3627.21 | 05-MAY-16:30 | 824.42 | 24-MAY-15:10 | 1161.22 | 05-MAY-16:03 | 0.00 | 01-MAY-00:10 |
| June | 0.667686E+10 | 0.188839E+10 | 720.00 | 0.529793E+10 | 0.137893E+10 | 0.00 | 0.69 | 06-JUN-16:10 | 0.22 | 01-JUN-04:00 | 3951.84 | 22-JUN-17:10 | 3733.55 | 06-JUN-16:01 | 1112.47 | 23-JUN-14:10 | 1241.64 | 10-JUN-16:35 | 0.00 | 01-JUN-00:10 |
| July | 0.770743E+10 | 0.206860E+10 | 744.00 | 0.544002E+10 | 0.226741E+10 | 0.00 | 0.69 | 02-JUL-16:50 | 0.24 | 19-JUL-03:00 | 4289.69 | 01-JUL-16:30 | 3456.50 | 02-JUL-16:50 | 1263.60 | 17-JUL-17:20 | 1252.60 | 02-JUL-16:50 | 0.00 | 01-JUL-00:10 |
| August | 0.750818E+10 | 0.195905E+10 | 744.00 | 0.520115E+10 | 0.230703E+10 | 0.00 | 0.64 | 07-AUG-16:03 | 0.27 | 24-AUG-04:00 | 4108.46 | 13-AUG-16:02 | 3183.41 | 07-AUG-16:03 | 1362.94 | 12-AUG-09:30 | 1146.00 | 07-AUG-16:03 | 0.00 | 01-AUG-00:10 |
| September | 0.660439E+10 | 0.170843E+10 | 720.00 | 0.483855E+10 | 0.176584E+10 | 0.00 | 0.62 | 24-SEP-16:10 | 0.25 | 09-SEP-03:00 | 3960.69 | 24-SEP-16:10 | 3254.82 | 24-SEP-16:04 | 1000.97 | 14-SEP-17:20 | 1095.96 | 24-SEP-16:10 | 0.00 | 01-SEP-00:10 |
| October | 0.485413E+10 | 0.126231E+10 | 744.00 | 0.426621E+10 | 0.587919E+09 | 0.00 | 0.58 | 03-OCT-15:10 | 0.05 | 31-OCT-06:00 | 3559.79 | 03-OCT-15:10 | 3241.31 | 01-OCT-16:03 | 536.54 | 06-OCT-11:30 | 1008.98 | 03-OCT-15:10 | 0.00 | 01-OCT-00:10 |
| November | 0.280896E+10 | 0.720706E+09 | 714.00 | 0.265110E+10 | 0.157863E+09 | 0.00 | 0.43 | 04-NOV-15:10 | 0.00 | 25-NOV-04:30 | 2584.09 | 04-NOV-15:10 | 2584.09 | 04-NOV-15:10 | 265.74 | 08-NOV-22:05 | 698.25 | 04-NOV-15:10 | 0.00 | 01-NOV-00:10 |
| December | 0.100061E+10 | 0.257202E+09 | 454.18 | 0.980671E+09 | 19934628.62 | 0.00 | 0.29 | 02-DEC-14:30 | 0.00 | 01-DEC-02:50 | 1778.16 | 02-DEC-14:30 | 1778.16 | 02-DEC-14:30 | 102.75 | 10-DEC-18:40 | 450.95 | 02-DEC-14:30 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.509630E+11 | 0.136883E+11 | 7631.67 | 0.411562E+11 | 0.980684E+10 | 0.00 | ||||||||||||||
| Minimum of Months | 0.394333E+09 | 0.102400E+09 | 266.91 | 0.388453E+09 | 5880062.35 | 0.00 | 0.22 | 0.00 | 1293.43 | 1293.43 | 61.50 | 330.77 | 0.00 | |||||||
| Maximum of Months | 0.770743E+10 | 0.206860E+10 | 744.00 | 0.544002E+10 | 0.230703E+10 | 0.00 | 0.69 | 0.27 | 4289.69 | 3733.55 | 1362.94 | 1252.60 | 0.00 |
Report: DXReportMonthly
For: SPLIT GNW COOLING COIL
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 13036873.96 | 3399480.10 | 25.06 | 12563553.54 | 473320.42 | 0.00 | 0.06 | 14-JAN-17:10 | 0.00 | 01-JAN-00:10 | 338.52 | 14-JAN-17:10 | 315.89 | 14-JAN-17:10 | 22.65 | 14-JAN-16:10 | 87.37 | 14-JAN-17:10 | 0.00 | 01-JAN-00:10 |
| February | 0.338543E+09 | 88014005.90 | 228.33 | 0.321117E+09 | 17425966.65 | 0.00 | 0.18 | 24-FEB-16:10 | 0.00 | 01-FEB-00:10 | 1105.86 | 24-FEB-17:10 | 1085.98 | 22-FEB-17:10 | 218.50 | 25-FEB-17:10 | 289.47 | 24-FEB-16:10 | 0.00 | 01-FEB-00:10 |
| March | 0.166191E+10 | 0.440962E+09 | 606.29 | 0.153420E+10 | 0.127702E+09 | 0.00 | 0.37 | 28-MAR-16:40 | 0.00 | 01-MAR-00:10 | 2120.38 | 29-MAR-16:30 | 2077.65 | 28-MAR-16:50 | 308.67 | 10-MAR-21:00 | 614.28 | 28-MAR-16:40 | 0.00 | 01-MAR-00:10 |
| April | 0.372910E+10 | 0.104351E+10 | 720.00 | 0.345762E+10 | 0.271479E+09 | 0.00 | 0.55 | 27-APR-16:03 | 0.01 | 11-APR-05:05 | 3023.15 | 18-APR-16:01 | 3006.77 | 27-APR-16:17 | 420.43 | 18-APR-14:10 | 930.97 | 27-APR-16:01 | 0.00 | 01-APR-00:10 |
| May | 0.588991E+10 | 0.168193E+10 | 744.00 | 0.504881E+10 | 0.841098E+09 | 0.00 | 0.67 | 05-MAY-16:40 | 0.16 | 13-MAY-04:00 | 3576.49 | 05-MAY-16:50 | 3576.49 | 05-MAY-16:50 | 837.65 | 24-MAY-15:10 | 1140.51 | 05-MAY-16:40 | 0.00 | 01-MAY-00:10 |
| June | 0.671575E+10 | 0.189774E+10 | 720.00 | 0.533008E+10 | 0.138567E+10 | 0.00 | 0.70 | 07-JUN-16:50 | 0.23 | 25-JUN-04:00 | 4035.52 | 22-JUN-17:00 | 3744.06 | 06-JUN-16:30 | 1127.10 | 23-JUN-14:10 | 1232.74 | 10-JUN-16:50 | 0.00 | 01-JUN-00:10 |
| July | 0.772056E+10 | 0.207084E+10 | 744.00 | 0.545067E+10 | 0.226989E+10 | 0.00 | 0.69 | 02-JUL-17:10 | 0.24 | 19-JUL-03:00 | 4240.05 | 01-JUL-16:40 | 3453.03 | 02-JUL-17:03 | 1286.04 | 17-JUL-17:10 | 1244.54 | 02-JUL-17:10 | 0.00 | 01-JUL-00:10 |
| August | 0.743997E+10 | 0.194060E+10 | 744.00 | 0.513498E+10 | 0.230500E+10 | 0.00 | 0.63 | 07-AUG-17:10 | 0.28 | 24-AUG-04:00 | 3993.54 | 07-AUG-17:10 | 3122.64 | 07-AUG-16:17 | 1315.84 | 12-AUG-09:30 | 1133.14 | 07-AUG-16:20 | 0.00 | 01-AUG-00:10 |
| September | 0.622598E+10 | 0.161161E+10 | 720.00 | 0.448787E+10 | 0.173811E+10 | 0.00 | 0.56 | 17-SEP-17:30 | 0.24 | 29-SEP-04:00 | 3565.97 | 14-SEP-16:30 | 2793.71 | 22-SEP-16:03 | 1007.36 | 14-SEP-17:20 | 989.78 | 17-SEP-18:00 | 0.00 | 01-SEP-00:10 |
| October | 0.390795E+10 | 0.102208E+10 | 744.00 | 0.336499E+10 | 0.542958E+09 | 0.00 | 0.49 | 03-OCT-15:10 | 0.01 | 31-OCT-05:50 | 2971.73 | 03-OCT-16:10 | 2667.93 | 02-OCT-16:03 | 506.96 | 06-OCT-11:20 | 849.66 | 03-OCT-15:10 | 0.00 | 01-OCT-00:10 |
| November | 0.160630E+10 | 0.417501E+09 | 640.66 | 0.149582E+10 | 0.110477E+09 | 0.00 | 0.29 | 04-NOV-16:10 | 0.00 | 03-NOV-05:03 | 1704.54 | 04-NOV-16:10 | 1687.76 | 04-NOV-16:10 | 216.85 | 08-NOV-22:05 | 463.81 | 04-NOV-16:10 | 0.00 | 01-NOV-00:10 |
| December | 0.208443E+09 | 54205412.89 | 209.11 | 0.204042E+09 | 4401312.74 | 0.00 | 0.14 | 01-DEC-15:10 | 0.00 | 01-DEC-00:10 | 833.59 | 01-DEC-15:10 | 833.59 | 01-DEC-15:10 | 44.42 | 16-DEC-17:10 | 216.44 | 01-DEC-15:10 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.454574E+11 | 0.122724E+11 | 6845.45 | 0.358428E+11 | 0.961468E+10 | 0.00 | ||||||||||||||
| Minimum of Months | 13036873.96 | 3399480.10 | 25.06 | 12563553.54 | 473320.42 | 0.00 | 0.06 | 0.00 | 338.52 | 315.89 | 22.65 | 87.37 | 0.00 | |||||||
| Maximum of Months | 0.772056E+10 | 0.207084E+10 | 744.00 | 0.545067E+10 | 0.230500E+10 | 0.00 | 0.70 | 0.28 | 4240.05 | 3744.06 | 1315.84 | 1244.54 | 0.00 |
Report: DXReportMonthly
For: SPLIT OFFICE COOLING COIL
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.805304E+09 | 0.204925E+09 | 157.56 | 0.785334E+09 | 19969257.84 | 0.00 | 0.96 | 26-JAN-09:02 | 0.00 | 01-JAN-00:10 | 7515.79 | 26-JAN-09:02 | 6980.96 | 12-JAN-09:02 | 669.68 | 18-JAN-09:03 | 1662.71 | 26-JAN-09:02 | 0.00 | 01-JAN-00:10 |
| February | 0.114285E+10 | 0.286681E+09 | 163.06 | 0.109422E+10 | 48634948.71 | 0.00 | 1.00 | 21-FEB-09:02 | 0.00 | 01-FEB-00:10 | 7947.29 | 23-FEB-09:02 | 7562.03 | 21-FEB-09:02 | 812.17 | 23-FEB-09:02 | 1733.78 | 23-FEB-09:02 | 0.00 | 01-FEB-00:10 |
| March | 0.213897E+10 | 0.548196E+09 | 236.59 | 0.202631E+10 | 0.112664E+09 | 0.00 | 1.00 | 06-MAR-09:02 | 0.00 | 01-MAR-00:10 | 8322.65 | 29-MAR-07:02 | 7773.88 | 27-MAR-08:62 | 1671.30 | 29-MAR-08:62 | 1746.27 | 29-MAR-07:02 | 0.00 | 01-MAR-00:10 |
| April | 0.308726E+10 | 0.843260E+09 | 392.11 | 0.292921E+10 | 0.158054E+09 | 0.00 | 1.00 | 03-APR-07:02 | 0.00 | 01-APR-00:10 | 8536.11 | 26-APR-07:02 | 7994.82 | 04-APR-07:02 | 2488.14 | 26-APR-07:03 | 1912.30 | 27-APR-07:02 | 0.00 | 01-APR-00:10 |
| May | 0.472300E+10 | 0.132586E+10 | 605.44 | 0.418104E+10 | 0.541956E+09 | 0.00 | 1.00 | 01-MAY-06:02 | 0.00 | 01-MAY-06:04 | 8897.45 | 23-MAY-06:03 | 7852.23 | 01-MAY-06:02 | 3940.78 | 23-MAY-06:03 | 2001.81 | 04-MAY-08:62 | 0.00 | 01-MAY-00:10 |
| June | 0.527863E+10 | 0.145402E+10 | 631.43 | 0.430266E+10 | 0.975967E+09 | 0.00 | 1.00 | 01-JUN-07:02 | 0.00 | 01-JUN-00:10 | 8922.79 | 26-JUN-06:03 | 7929.94 | 12-JUN-06:02 | 4843.63 | 29-JUN-06:03 | 2018.10 | 12-JUN-06:02 | 0.00 | 01-JUN-00:10 |
| July | 0.579710E+10 | 0.149640E+10 | 665.65 | 0.409939E+10 | 0.169770E+10 | 0.00 | 1.00 | 03-JUL-06:03 | 0.00 | 03-JUL-16:01 | 8945.83 | 26-JUL-06:03 | 6208.85 | 05-JUL-08:62 | 5018.75 | 13-JUL-06:03 | 2030.77 | 05-JUL-07:02 | 0.00 | 01-JUL-00:10 |
| August | 0.590897E+10 | 0.148325E+10 | 636.51 | 0.410973E+10 | 0.179924E+10 | 0.00 | 1.00 | 01-AUG-06:03 | 0.00 | 01-AUG-16:01 | 8956.94 | 16-AUG-07:02 | 6072.73 | 07-AUG-08:62 | 4861.34 | 30-AUG-06:03 | 1945.00 | 08-AUG-07:02 | 0.00 | 01-AUG-00:10 |
| September | 0.479593E+10 | 0.119903E+10 | 577.36 | 0.356785E+10 | 0.122808E+10 | 0.00 | 1.00 | 01-SEP-06:03 | 0.00 | 01-SEP-06:08 | 8957.40 | 07-SEP-07:02 | 6480.71 | 26-SEP-08:62 | 4941.09 | 13-SEP-06:03 | 1898.00 | 22-SEP-08:62 | 0.00 | 01-SEP-00:10 |
| October | 0.363445E+10 | 0.925174E+09 | 405.82 | 0.328822E+10 | 0.346229E+09 | 0.00 | 1.00 | 02-OCT-07:02 | 0.00 | 01-OCT-00:30 | 8782.03 | 04-OCT-06:03 | 7973.91 | 24-OCT-07:02 | 3288.32 | 12-OCT-07:03 | 1841.08 | 04-OCT-08:62 | 0.00 | 01-OCT-00:10 |
| November | 0.225652E+10 | 0.562975E+09 | 234.64 | 0.217142E+10 | 85091718.12 | 0.00 | 1.00 | 01-NOV-07:02 | 0.00 | 01-NOV-00:10 | 8266.28 | 09-NOV-08:62 | 7909.93 | 01-NOV-07:02 | 1414.47 | 09-NOV-09:02 | 1745.67 | 09-NOV-08:62 | 0.00 | 01-NOV-00:10 |
| December | 0.119362E+10 | 0.299477E+09 | 170.44 | 0.117187E+10 | 21746777.37 | 0.00 | 1.00 | 01-DEC-09:02 | 0.00 | 01-DEC-00:10 | 7606.50 | 01-DEC-09:02 | 7606.50 | 01-DEC-09:02 | 242.87 | 15-DEC-09:02 | 1702.70 | 01-DEC-09:02 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.407626E+11 | 0.106292E+11 | 4876.58 | 0.337273E+11 | 0.703534E+10 | 0.00 | ||||||||||||||
| Minimum of Months | 0.805304E+09 | 0.204925E+09 | 157.56 | 0.785334E+09 | 19969257.84 | 0.00 | 0.96 | 0.00 | 7515.79 | 6072.73 | 242.87 | 1662.71 | 0.00 | |||||||
| Maximum of Months | 0.590897E+10 | 0.149640E+10 | 665.65 | 0.430266E+10 | 0.179924E+10 | 0.00 | 1.00 | 0.00 | 8957.40 | 7994.82 | 5018.75 | 2030.77 | 0.00 |
Report: DXReportMonthly
For: SPLIT GNE COOLING COIL
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 9649134.94 | 2516662.44 | 21.58 | 9312160.25 | 336974.69 | 0.00 | 0.04 | 26-JAN-14:00 | 0.00 | 01-JAN-00:10 | 252.73 | 26-JAN-14:00 | 252.73 | 26-JAN-14:00 | 17.56 | 14-JAN-16:10 | 66.17 | 26-JAN-14:00 | 0.00 | 01-JAN-00:10 |
| February | 0.346156E+09 | 89951088.32 | 238.66 | 0.327776E+09 | 18379745.17 | 0.00 | 0.18 | 24-FEB-16:10 | 0.00 | 01-FEB-00:10 | 1079.29 | 24-FEB-17:10 | 1000.49 | 24-FEB-16:10 | 188.60 | 25-FEB-17:10 | 281.47 | 24-FEB-16:10 | 0.00 | 01-FEB-00:10 |
| March | 0.168203E+10 | 0.445656E+09 | 613.28 | 0.155032E+10 | 0.131708E+09 | 0.00 | 0.33 | 29-MAR-16:03 | 0.00 | 01-MAR-00:10 | 1866.23 | 29-MAR-16:03 | 1818.13 | 29-MAR-16:03 | 309.62 | 10-MAR-21:00 | 533.02 | 29-MAR-16:03 | 0.00 | 01-MAR-00:10 |
| April | 0.374985E+10 | 0.104697E+10 | 720.00 | 0.347388E+10 | 0.275974E+09 | 0.00 | 0.51 | 15-APR-15:10 | 0.01 | 11-APR-05:10 | 2771.27 | 18-APR-15:10 | 2687.83 | 15-APR-15:10 | 408.50 | 26-APR-08:30 | 844.68 | 15-APR-15:10 | 0.00 | 01-APR-00:10 |
| May | 0.591733E+10 | 0.168599E+10 | 744.00 | 0.507293E+10 | 0.844405E+09 | 0.00 | 0.63 | 05-MAY-16:10 | 0.16 | 13-MAY-04:00 | 3257.51 | 05-MAY-16:40 | 3257.51 | 05-MAY-16:40 | 812.89 | 24-MAY-14:20 | 1050.34 | 05-MAY-16:05 | 0.00 | 01-MAY-00:10 |
| June | 0.666232E+10 | 0.187935E+10 | 720.00 | 0.527866E+10 | 0.138366E+10 | 0.00 | 0.66 | 06-JUN-16:10 | 0.23 | 25-JUN-04:00 | 3817.80 | 23-JUN-15:10 | 3432.87 | 06-JUN-15:10 | 1112.77 | 23-JUN-14:10 | 1120.10 | 06-JUN-15:10 | 0.00 | 01-JUN-00:10 |
| July | 0.772497E+10 | 0.206800E+10 | 744.00 | 0.545421E+10 | 0.227076E+10 | 0.00 | 0.66 | 02-JUL-17:20 | 0.25 | 19-JUL-03:00 | 4039.33 | 01-JUL-16:40 | 3161.02 | 02-JUL-17:20 | 1267.37 | 17-JUL-17:10 | 1156.57 | 02-JUL-17:10 | 0.00 | 01-JUL-00:10 |
| August | 0.744380E+10 | 0.193790E+10 | 744.00 | 0.513778E+10 | 0.230602E+10 | 0.00 | 0.62 | 07-AUG-17:10 | 0.28 | 24-AUG-04:00 | 3801.17 | 07-AUG-17:10 | 2949.43 | 07-AUG-16:30 | 1321.65 | 12-AUG-09:30 | 1080.42 | 07-AUG-16:10 | 0.00 | 01-AUG-00:10 |
| September | 0.621060E+10 | 0.160499E+10 | 720.00 | 0.447287E+10 | 0.173773E+10 | 0.00 | 0.54 | 14-SEP-17:10 | 0.24 | 27-SEP-05:00 | 3425.92 | 14-SEP-17:10 | 2580.00 | 22-SEP-16:03 | 996.48 | 14-SEP-17:20 | 937.43 | 17-SEP-20:00 | 0.00 | 01-SEP-00:10 |
| October | 0.392967E+10 | 0.102623E+10 | 744.00 | 0.338364E+10 | 0.546032E+09 | 0.00 | 0.48 | 03-OCT-15:10 | 0.01 | 31-OCT-06:00 | 2781.63 | 03-OCT-15:10 | 2464.89 | 03-OCT-15:10 | 532.96 | 13-OCT-09:30 | 800.61 | 03-OCT-15:10 | 0.00 | 01-OCT-00:10 |
| November | 0.161122E+10 | 0.418431E+09 | 647.73 | 0.149916E+10 | 0.112057E+09 | 0.00 | 0.26 | 09-NOV-13:00 | 0.00 | 03-NOV-05:03 | 1535.03 | 09-NOV-13:00 | 1477.20 | 04-NOV-16:10 | 230.94 | 09-NOV-09:40 | 417.22 | 09-NOV-13:00 | 0.00 | 01-NOV-00:10 |
| December | 0.198813E+09 | 51735375.67 | 210.80 | 0.194944E+09 | 3869137.50 | 0.00 | 0.13 | 01-DEC-14:00 | 0.00 | 01-DEC-00:10 | 730.97 | 01-DEC-14:00 | 730.97 | 01-DEC-14:00 | 37.50 | 16-DEC-17:10 | 190.16 | 01-DEC-14:00 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.454864E+11 | 0.122577E+11 | 6868.05 | 0.358555E+11 | 0.963094E+10 | 0.00 | ||||||||||||||
| Minimum of Months | 9649134.94 | 2516662.44 | 21.58 | 9312160.25 | 336974.69 | 0.00 | 0.04 | 0.00 | 252.73 | 252.73 | 17.56 | 66.17 | 0.00 | |||||||
| Maximum of Months | 0.772497E+10 | 0.206800E+10 | 744.00 | 0.545421E+10 | 0.230602E+10 | 0.00 | 0.66 | 0.28 | 4039.33 | 3432.87 | 1321.65 | 1156.57 | 0.00 |
Report: DXReportMonthly
For: SPLIT GN1 COOLING COIL
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 13369525.54 | 3480627.45 | 35.67 | 12741243.55 | 628281.99 | 0.00 | 0.05 | 14-JAN-17:05 | 0.00 | 01-JAN-00:10 | 278.20 | 14-JAN-17:05 | 259.17 | 14-JAN-17:05 | 22.03 | 18-JAN-19:20 | 71.82 | 14-JAN-17:05 | 0.00 | 01-JAN-00:10 |
| February | 0.357205E+09 | 92603627.43 | 290.37 | 0.335231E+09 | 21973776.36 | 0.00 | 0.19 | 24-FEB-17:10 | 0.00 | 01-FEB-00:10 | 979.34 | 24-FEB-17:10 | 903.17 | 24-FEB-17:05 | 189.27 | 25-FEB-17:10 | 253.02 | 24-FEB-17:10 | 0.00 | 01-FEB-00:10 |
| March | 0.157396E+10 | 0.415536E+09 | 669.21 | 0.144180E+10 | 0.132153E+09 | 0.00 | 0.31 | 29-MAR-16:03 | 0.00 | 01-MAR-01:10 | 1575.78 | 29-MAR-16:13 | 1528.96 | 29-MAR-16:30 | 289.58 | 10-MAR-21:00 | 452.57 | 28-MAR-16:40 | 0.00 | 01-MAR-00:10 |
| April | 0.321982E+10 | 0.897752E+09 | 720.00 | 0.296270E+10 | 0.257129E+09 | 0.00 | 0.46 | 27-APR-16:10 | 0.02 | 11-APR-05:05 | 2290.97 | 18-APR-16:02 | 2182.76 | 27-APR-16:01 | 341.83 | 18-APR-14:10 | 685.65 | 27-APR-16:01 | 0.00 | 01-APR-00:10 |
| May | 0.500514E+10 | 0.142636E+10 | 744.00 | 0.423693E+10 | 0.768214E+09 | 0.00 | 0.57 | 05-MAY-17:00 | 0.18 | 13-MAY-03:00 | 2705.47 | 25-MAY-17:10 | 2640.37 | 05-MAY-17:08 | 763.61 | 22-MAY-23:00 | 850.60 | 05-MAY-17:00 | 0.00 | 01-MAY-00:10 |
| June | 0.572639E+10 | 0.161432E+10 | 720.00 | 0.445010E+10 | 0.127629E+10 | 0.00 | 0.61 | 10-JUN-17:10 | 0.24 | 18-JUN-04:00 | 3234.12 | 22-JUN-17:14 | 2791.42 | 07-JUN-17:02 | 958.63 | 23-JUN-14:10 | 963.27 | 10-JUN-17:10 | 0.00 | 01-JUN-00:10 |
| July | 0.662592E+10 | 0.177398E+10 | 744.00 | 0.457648E+10 | 0.204944E+10 | 0.00 | 0.62 | 02-JUL-17:20 | 0.26 | 19-JUL-03:00 | 3419.73 | 01-JUL-17:12 | 2605.52 | 04-JUL-17:35 | 1068.88 | 17-JUL-17:10 | 975.68 | 02-JUL-17:20 | 0.00 | 01-JUL-00:10 |
| August | 0.641995E+10 | 0.166980E+10 | 744.00 | 0.431485E+10 | 0.210510E+10 | 0.00 | 0.58 | 07-AUG-17:10 | 0.29 | 24-AUG-04:00 | 3211.44 | 27-AUG-16:02 | 2395.18 | 07-AUG-17:06 | 1160.93 | 12-AUG-09:30 | 901.03 | 07-AUG-17:10 | 0.00 | 01-AUG-00:10 |
| September | 0.536812E+10 | 0.138461E+10 | 720.00 | 0.376664E+10 | 0.160148E+10 | 0.00 | 0.52 | 17-SEP-20:00 | 0.24 | 29-SEP-04:00 | 2935.38 | 14-SEP-17:20 | 2104.25 | 17-SEP-18:00 | 921.14 | 14-SEP-17:20 | 824.50 | 17-SEP-20:00 | 0.00 | 01-SEP-00:10 |
| October | 0.336506E+10 | 0.877576E+09 | 744.00 | 0.285738E+10 | 0.507674E+09 | 0.00 | 0.43 | 03-OCT-16:10 | 0.02 | 31-OCT-05:20 | 2259.46 | 03-OCT-16:10 | 1976.45 | 02-OCT-16:09 | 466.65 | 13-OCT-09:30 | 644.07 | 03-OCT-15:10 | 0.00 | 01-OCT-00:10 |
| November | 0.146173E+10 | 0.379228E+09 | 677.63 | 0.135091E+10 | 0.110821E+09 | 0.00 | 0.25 | 04-NOV-16:05 | 0.00 | 03-NOV-05:03 | 1287.94 | 04-NOV-16:05 | 1274.49 | 04-NOV-16:05 | 205.05 | 08-NOV-22:05 | 352.42 | 04-NOV-16:05 | 0.00 | 01-NOV-00:10 |
| December | 0.224228E+09 | 58286184.83 | 270.41 | 0.218257E+09 | 5970941.82 | 0.00 | 0.13 | 01-DEC-15:10 | 0.00 | 01-DEC-01:10 | 639.21 | 01-DEC-15:10 | 639.21 | 01-DEC-15:10 | 63.89 | 10-DEC-18:50 | 166.38 | 01-DEC-15:10 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.393609E+11 | 0.105935E+11 | 7079.28 | 0.305240E+11 | 0.883687E+10 | 0.00 | ||||||||||||||
| Minimum of Months | 13369525.54 | 3480627.45 | 35.67 | 12741243.55 | 628281.99 | 0.00 | 0.05 | 0.00 | 278.20 | 259.17 | 22.03 | 71.82 | 0.00 | |||||||
| Maximum of Months | 0.662592E+10 | 0.177398E+10 | 744.00 | 0.457648E+10 | 0.210510E+10 | 0.00 | 0.62 | 0.29 | 3419.73 | 2791.42 | 1160.93 | 975.68 | 0.00 |
Report: DXReportMonthly
For: SPLIT GN2 COOLING COIL
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 13491702.83 | 3512669.12 | 35.83 | 12862607.59 | 629095.24 | 0.00 | 0.05 | 14-JAN-17:05 | 0.00 | 01-JAN-00:10 | 277.26 | 14-JAN-17:05 | 258.29 | 14-JAN-17:05 | 21.09 | 17-JAN-20:10 | 71.58 | 14-JAN-17:05 | 0.00 | 01-JAN-00:10 |
| February | 0.360664E+09 | 93496490.32 | 292.11 | 0.338525E+09 | 22138545.04 | 0.00 | 0.19 | 24-FEB-17:10 | 0.00 | 01-FEB-00:10 | 981.68 | 24-FEB-17:10 | 905.41 | 24-FEB-17:05 | 189.10 | 25-FEB-17:10 | 253.60 | 24-FEB-17:10 | 0.00 | 01-FEB-00:10 |
| March | 0.157623E+10 | 0.416122E+09 | 669.54 | 0.144390E+10 | 0.132322E+09 | 0.00 | 0.31 | 29-MAR-16:03 | 0.00 | 01-MAR-01:10 | 1572.59 | 29-MAR-16:03 | 1525.61 | 29-MAR-16:30 | 289.73 | 10-MAR-21:00 | 451.68 | 28-MAR-16:40 | 0.00 | 01-MAR-00:10 |
| April | 0.322116E+10 | 0.898096E+09 | 720.00 | 0.296389E+10 | 0.257269E+09 | 0.00 | 0.46 | 27-APR-16:10 | 0.02 | 11-APR-05:05 | 2288.94 | 18-APR-16:02 | 2178.59 | 27-APR-16:01 | 341.79 | 18-APR-14:10 | 684.80 | 18-APR-16:02 | 0.00 | 01-APR-00:10 |
| May | 0.500640E+10 | 0.142667E+10 | 744.00 | 0.423808E+10 | 0.768320E+09 | 0.00 | 0.57 | 05-MAY-17:00 | 0.18 | 13-MAY-03:40 | 2701.19 | 25-MAY-17:10 | 2636.29 | 05-MAY-17:09 | 763.70 | 22-MAY-23:00 | 849.43 | 05-MAY-17:00 | 0.00 | 01-MAY-00:10 |
| June | 0.572452E+10 | 0.161376E+10 | 720.00 | 0.444835E+10 | 0.127617E+10 | 0.00 | 0.61 | 10-JUN-17:10 | 0.24 | 18-JUN-04:00 | 3229.27 | 22-JUN-17:14 | 2786.43 | 07-JUN-17:02 | 958.41 | 23-JUN-14:10 | 961.09 | 10-JUN-17:10 | 0.00 | 01-JUN-00:10 |
| July | 0.662620E+10 | 0.177398E+10 | 744.00 | 0.457670E+10 | 0.204950E+10 | 0.00 | 0.62 | 02-JUL-17:20 | 0.26 | 19-JUL-03:00 | 3416.80 | 01-JUL-17:12 | 2601.74 | 04-JUL-17:35 | 1068.48 | 17-JUL-17:10 | 974.31 | 02-JUL-17:20 | 0.00 | 01-JUL-00:10 |
| August | 0.642027E+10 | 0.166982E+10 | 744.00 | 0.431510E+10 | 0.210517E+10 | 0.00 | 0.58 | 07-AUG-17:10 | 0.29 | 24-AUG-04:00 | 3209.96 | 27-AUG-16:02 | 2392.66 | 07-AUG-17:06 | 1160.93 | 12-AUG-09:30 | 900.22 | 07-AUG-17:10 | 0.00 | 01-AUG-00:10 |
| September | 0.536764E+10 | 0.138445E+10 | 720.00 | 0.376619E+10 | 0.160146E+10 | 0.00 | 0.52 | 17-SEP-20:00 | 0.24 | 29-SEP-04:00 | 2933.89 | 14-SEP-17:20 | 2100.12 | 17-SEP-18:00 | 920.87 | 14-SEP-17:20 | 823.64 | 17-SEP-20:00 | 0.00 | 01-SEP-00:10 |
| October | 0.336626E+10 | 0.877873E+09 | 744.00 | 0.285847E+10 | 0.507795E+09 | 0.00 | 0.43 | 03-OCT-16:10 | 0.02 | 31-OCT-05:20 | 2257.19 | 03-OCT-16:10 | 1973.65 | 02-OCT-16:10 | 467.41 | 13-OCT-09:30 | 643.87 | 03-OCT-15:10 | 0.00 | 01-OCT-00:10 |
| November | 0.146266E+10 | 0.379465E+09 | 677.80 | 0.135180E+10 | 0.110862E+09 | 0.00 | 0.25 | 04-NOV-16:05 | 0.00 | 03-NOV-05:03 | 1284.95 | 04-NOV-16:05 | 1271.53 | 04-NOV-16:05 | 204.97 | 08-NOV-22:05 | 351.63 | 04-NOV-16:05 | 0.00 | 01-NOV-00:10 |
| December | 0.225851E+09 | 58707266.10 | 271.11 | 0.219852E+09 | 5998613.60 | 0.00 | 0.13 | 01-DEC-15:10 | 0.00 | 01-DEC-01:10 | 639.46 | 01-DEC-15:10 | 639.46 | 01-DEC-15:10 | 64.12 | 10-DEC-18:50 | 166.44 | 01-DEC-15:10 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.393714E+11 | 0.105960E+11 | 7082.39 | 0.305337E+11 | 0.883763E+10 | 0.00 | ||||||||||||||
| Minimum of Months | 13491702.83 | 3512669.12 | 35.83 | 12862607.59 | 629095.24 | 0.00 | 0.05 | 0.00 | 277.26 | 258.29 | 21.09 | 71.58 | 0.00 | |||||||
| Maximum of Months | 0.662620E+10 | 0.177398E+10 | 744.00 | 0.457670E+10 | 0.210517E+10 | 0.00 | 0.62 | 0.29 | 3416.80 | 2786.43 | 1160.93 | 974.31 | 0.00 |
Report: DXReportMonthly
For: SPLIT GS1 COOLING COIL
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.556076E+09 | 0.143955E+09 | 393.81 | 0.543361E+09 | 12714867.85 | 0.00 | 0.23 | 12-JAN-14:50 | 0.00 | 01-JAN-00:10 | 1232.23 | 12-JAN-14:50 | 1232.23 | 12-JAN-14:50 | 88.76 | 16-JAN-20:30 | 314.20 | 12-JAN-14:50 | 0.00 | 01-JAN-00:10 |
| February | 0.109056E+10 | 0.279611E+09 | 486.91 | 0.104195E+10 | 48603109.21 | 0.00 | 0.31 | 20-FEB-14:40 | 0.00 | 01-FEB-00:10 | 1601.31 | 20-FEB-14:40 | 1601.31 | 20-FEB-14:40 | 269.67 | 25-FEB-17:10 | 420.04 | 20-FEB-14:40 | 0.00 | 01-FEB-00:10 |
| March | 0.230028E+10 | 0.602084E+09 | 723.26 | 0.213654E+10 | 0.163741E+09 | 0.00 | 0.40 | 12-MAR-16:10 | 0.00 | 01-MAR-08:50 | 2118.53 | 12-MAR-16:10 | 1961.87 | 12-MAR-16:05 | 319.72 | 10-MAR-21:00 | 580.74 | 12-MAR-16:10 | 0.00 | 01-MAR-00:10 |
| April | 0.366636E+10 | 0.101818E+10 | 720.00 | 0.339686E+10 | 0.269500E+09 | 0.00 | 0.51 | 15-APR-15:10 | 0.04 | 11-APR-05:05 | 2516.22 | 18-APR-15:10 | 2453.00 | 15-APR-15:10 | 346.08 | 18-APR-13:30 | 770.33 | 15-APR-15:10 | 0.00 | 01-APR-00:10 |
| May | 0.509455E+10 | 0.145251E+10 | 744.00 | 0.432640E+10 | 0.768155E+09 | 0.00 | 0.58 | 05-MAY-16:10 | 0.18 | 13-MAY-04:00 | 2801.44 | 20-MAY-16:10 | 2681.42 | 05-MAY-16:01 | 764.19 | 22-MAY-23:00 | 872.43 | 05-MAY-16:01 | 0.00 | 01-MAY-00:10 |
| June | 0.570153E+10 | 0.160901E+10 | 720.00 | 0.443101E+10 | 0.127052E+10 | 0.00 | 0.60 | 10-JUN-17:10 | 0.24 | 18-JUN-04:00 | 3159.10 | 22-JUN-17:20 | 2748.75 | 06-JUN-16:01 | 944.90 | 23-JUN-14:10 | 966.15 | 10-JUN-17:10 | 0.00 | 01-JUN-00:10 |
| July | 0.662887E+10 | 0.177625E+10 | 744.00 | 0.458004E+10 | 0.204883E+10 | 0.00 | 0.61 | 02-JUL-17:10 | 0.25 | 19-JUL-03:00 | 3448.85 | 01-JUL-17:02 | 2608.06 | 02-JUL-17:10 | 1086.42 | 01-JUL-16:01 | 984.14 | 01-JUL-16:01 | 0.00 | 01-JUL-00:10 |
| August | 0.650605E+10 | 0.169322E+10 | 744.00 | 0.439563E+10 | 0.211043E+10 | 0.00 | 0.59 | 27-AUG-16:02 | 0.29 | 24-AUG-04:00 | 3383.26 | 27-AUG-16:02 | 2440.87 | 07-AUG-16:10 | 1209.08 | 12-AUG-09:30 | 930.04 | 27-AUG-16:02 | 0.00 | 01-AUG-00:10 |
| September | 0.577164E+10 | 0.148843E+10 | 720.00 | 0.413531E+10 | 0.163634E+10 | 0.00 | 0.57 | 24-SEP-16:10 | 0.26 | 09-SEP-03:00 | 3164.82 | 24-SEP-16:10 | 2551.78 | 24-SEP-15:10 | 914.35 | 14-SEP-17:20 | 881.57 | 24-SEP-16:10 | 0.00 | 01-SEP-00:10 |
| October | 0.434847E+10 | 0.112741E+10 | 744.00 | 0.378816E+10 | 0.560310E+09 | 0.00 | 0.53 | 03-OCT-14:10 | 0.06 | 31-OCT-05:15 | 2824.89 | 03-OCT-15:10 | 2568.78 | 03-OCT-14:10 | 502.27 | 13-OCT-09:40 | 812.20 | 03-OCT-14:10 | 0.00 | 01-OCT-00:10 |
| November | 0.271677E+10 | 0.695102E+09 | 720.00 | 0.255565E+10 | 0.161120E+09 | 0.00 | 0.41 | 04-NOV-14:10 | 0.02 | 28-NOV-07:40 | 2180.04 | 04-NOV-14:10 | 2176.83 | 04-NOV-14:10 | 259.65 | 08-NOV-22:05 | 592.04 | 04-NOV-14:10 | 0.00 | 01-NOV-00:10 |
| December | 0.117112E+10 | 0.300602E+09 | 606.91 | 0.114466E+10 | 26462709.90 | 0.00 | 0.31 | 02-DEC-14:00 | 0.00 | 02-DEC-03:10 | 1634.73 | 02-DEC-14:00 | 1634.73 | 02-DEC-14:00 | 116.14 | 10-DEC-18:40 | 414.06 | 02-DEC-14:00 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.455523E+11 | 0.121864E+11 | 8066.90 | 0.364756E+11 | 0.907672E+10 | 0.00 | ||||||||||||||
| Minimum of Months | 0.556076E+09 | 0.143955E+09 | 393.81 | 0.543361E+09 | 12714867.85 | 0.00 | 0.23 | 0.00 | 1232.23 | 1232.23 | 88.76 | 314.20 | 0.00 | |||||||
| Maximum of Months | 0.662887E+10 | 0.177625E+10 | 744.00 | 0.458004E+10 | 0.211043E+10 | 0.00 | 0.61 | 0.29 | 3448.85 | 2748.75 | 1209.08 | 984.14 | 0.00 |
Report: DXReportMonthly
For: SPLIT GS2 COOLING COIL
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.614942E+09 | 0.159050E+09 | 408.55 | 0.600181E+09 | 14760893.73 | 0.00 | 0.24 | 12-JAN-14:40 | 0.00 | 01-JAN-00:10 | 1277.35 | 12-JAN-14:40 | 1277.35 | 12-JAN-14:40 | 87.61 | 16-JAN-20:30 | 325.35 | 12-JAN-14:40 | 0.00 | 01-JAN-00:10 |
| February | 0.119896E+10 | 0.307008E+09 | 516.40 | 0.114463E+10 | 54326297.13 | 0.00 | 0.32 | 20-FEB-14:50 | 0.00 | 01-FEB-00:10 | 1699.53 | 20-FEB-14:50 | 1699.53 | 20-FEB-14:50 | 284.37 | 25-FEB-17:10 | 444.67 | 20-FEB-14:30 | 0.00 | 01-FEB-00:10 |
| March | 0.250921E+10 | 0.654986E+09 | 729.10 | 0.233383E+10 | 0.175386E+09 | 0.00 | 0.42 | 12-MAR-16:10 | 0.00 | 01-MAR-08:50 | 2268.45 | 12-MAR-16:10 | 2107.43 | 12-MAR-16:05 | 329.51 | 10-MAR-21:00 | 619.66 | 12-MAR-16:10 | 0.00 | 01-MAR-00:10 |
| April | 0.398343E+10 | 0.110130E+10 | 720.00 | 0.370134E+10 | 0.282084E+09 | 0.00 | 0.53 | 15-APR-15:10 | 0.06 | 11-APR-05:10 | 2644.03 | 16-APR-16:10 | 2598.09 | 15-APR-15:10 | 349.64 | 18-APR-13:30 | 812.68 | 15-APR-15:10 | 0.00 | 01-APR-00:10 |
| May | 0.547057E+10 | 0.155364E+10 | 744.00 | 0.467859E+10 | 0.791977E+09 | 0.00 | 0.59 | 05-MAY-16:10 | 0.20 | 13-MAY-04:00 | 2963.74 | 20-MAY-16:10 | 2770.57 | 05-MAY-17:04 | 791.17 | 22-MAY-23:00 | 898.96 | 05-MAY-16:06 | 0.00 | 01-MAY-00:10 |
| June | 0.607130E+10 | 0.170793E+10 | 720.00 | 0.476936E+10 | 0.130195E+10 | 0.00 | 0.63 | 10-JUN-17:10 | 0.26 | 02-JUN-05:00 | 3264.40 | 22-JUN-17:20 | 2845.46 | 06-JUN-16:01 | 953.76 | 28-JUN-13:00 | 1012.47 | 10-JUN-17:10 | 0.00 | 01-JUN-00:10 |
| July | 0.704668E+10 | 0.188380E+10 | 744.00 | 0.495057E+10 | 0.209611E+10 | 0.00 | 0.64 | 02-JUL-17:10 | 0.28 | 19-JUL-03:00 | 3619.54 | 01-JUL-17:02 | 2783.29 | 02-JUL-17:03 | 1100.25 | 01-JUL-16:01 | 1034.14 | 02-JUL-17:10 | 0.00 | 01-JUL-00:10 |
| August | 0.690947E+10 | 0.179471E+10 | 744.00 | 0.475112E+10 | 0.215835E+10 | 0.00 | 0.62 | 27-AUG-16:02 | 0.31 | 24-AUG-04:00 | 3575.79 | 27-AUG-16:02 | 2586.44 | 06-AUG-16:03 | 1232.56 | 12-AUG-09:30 | 980.03 | 27-AUG-16:02 | 0.00 | 01-AUG-00:10 |
| September | 0.616218E+10 | 0.158548E+10 | 720.00 | 0.448295E+10 | 0.167923E+10 | 0.00 | 0.60 | 24-SEP-16:10 | 0.28 | 09-SEP-03:00 | 3358.19 | 24-SEP-16:10 | 2736.97 | 24-SEP-15:10 | 927.95 | 14-SEP-18:00 | 931.76 | 24-SEP-16:10 | 0.00 | 01-SEP-00:10 |
| October | 0.470791E+10 | 0.121637E+10 | 744.00 | 0.412433E+10 | 0.583580E+09 | 0.00 | 0.55 | 03-OCT-14:10 | 0.08 | 31-OCT-05:15 | 2932.26 | 03-OCT-15:10 | 2752.92 | 01-OCT-15:10 | 514.41 | 13-OCT-09:30 | 841.86 | 03-OCT-14:10 | 0.00 | 01-OCT-00:10 |
| November | 0.296216E+10 | 0.756111E+09 | 720.00 | 0.279021E+10 | 0.171944E+09 | 0.00 | 0.43 | 04-NOV-14:10 | 0.04 | 25-NOV-05:00 | 2302.27 | 04-NOV-14:10 | 2300.15 | 04-NOV-14:10 | 272.08 | 08-NOV-22:05 | 623.38 | 04-NOV-14:10 | 0.00 | 01-NOV-00:10 |
| December | 0.128377E+10 | 0.329256E+09 | 644.63 | 0.125445E+10 | 29326934.36 | 0.00 | 0.32 | 02-DEC-14:00 | 0.00 | 02-DEC-04:00 | 1712.71 | 02-DEC-14:00 | 1712.71 | 02-DEC-14:00 | 122.40 | 10-DEC-18:40 | 432.99 | 02-DEC-14:00 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.489206E+11 | 0.130497E+11 | 8154.68 | 0.395816E+11 | 0.933902E+10 | 0.00 | ||||||||||||||
| Minimum of Months | 0.614942E+09 | 0.159050E+09 | 408.55 | 0.600181E+09 | 14760893.73 | 0.00 | 0.24 | 0.00 | 1277.35 | 1277.35 | 87.61 | 325.35 | 0.00 | |||||||
| Maximum of Months | 0.704668E+10 | 0.188380E+10 | 744.00 | 0.495057E+10 | 0.215835E+10 | 0.00 | 0.64 | 0.31 | 3619.54 | 2845.46 | 1232.56 | 1034.14 | 0.00 |
Report: DXReportMonthly
For: SPLIT MSW COOLING COIL
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.119014E+10 | 0.308287E+09 | 310.44 | 0.117373E+10 | 16406518.21 | 0.00 | 0.25 | 12-JAN-15:20 | 0.00 | 01-JAN-00:10 | 3308.65 | 12-JAN-15:20 | 3308.65 | 12-JAN-15:20 | 150.25 | 13-JAN-14:40 | 842.19 | 12-JAN-15:20 | 0.00 | 01-JAN-00:10 |
| February | 0.278052E+10 | 0.711968E+09 | 444.11 | 0.267188E+10 | 0.108638E+09 | 0.00 | 0.35 | 20-FEB-16:10 | 0.00 | 01-FEB-00:10 | 4702.95 | 20-FEB-16:10 | 4702.95 | 20-FEB-16:10 | 733.80 | 25-FEB-17:10 | 1212.25 | 20-FEB-15:20 | 0.00 | 01-FEB-00:10 |
| March | 0.631409E+10 | 0.165077E+10 | 714.41 | 0.592492E+10 | 0.389172E+09 | 0.00 | 0.47 | 28-MAR-16:07 | 0.00 | 01-MAR-03:20 | 6297.82 | 12-MAR-16:10 | 6102.37 | 28-MAR-16:07 | 784.15 | 10-MAR-21:00 | 1784.57 | 28-MAR-16:07 | 0.00 | 01-MAR-00:10 |
| April | 0.996700E+10 | 0.276857E+10 | 720.00 | 0.934158E+10 | 0.625422E+09 | 0.00 | 0.62 | 27-APR-16:10 | 0.04 | 10-APR-05:10 | 7744.35 | 27-APR-16:03 | 7744.35 | 27-APR-16:03 | 991.52 | 18-APR-14:10 | 2376.85 | 15-APR-15:10 | 0.00 | 01-APR-00:10 |
| May | 0.131844E+11 | 0.377008E+10 | 744.00 | 0.113673E+11 | 0.181706E+10 | 0.00 | 0.69 | 05-MAY-16:10 | 0.16 | 13-MAY-04:00 | 8302.31 | 05-MAY-16:03 | 8302.31 | 05-MAY-16:03 | 1929.33 | 24-MAY-15:10 | 2651.77 | 05-MAY-16:03 | 0.00 | 01-MAY-00:10 |
| June | 0.138534E+11 | 0.393675E+10 | 720.00 | 0.109658E+11 | 0.288756E+10 | 0.00 | 0.68 | 06-JUN-16:10 | 0.19 | 18-JUN-05:00 | 8506.18 | 22-JUN-16:30 | 8191.52 | 06-JUN-16:08 | 2502.57 | 23-JUN-14:10 | 2657.22 | 06-JUN-16:08 | 0.00 | 01-JUN-00:10 |
| July | 0.152153E+11 | 0.410777E+10 | 744.00 | 0.104825E+11 | 0.473286E+10 | 0.00 | 0.64 | 02-JUL-16:40 | 0.18 | 19-JUL-03:00 | 9137.82 | 01-JUL-16:01 | 7138.59 | 02-JUL-16:40 | 2851.58 | 17-JUL-17:20 | 2619.29 | 02-JUL-16:30 | 0.00 | 01-JUL-00:10 |
| August | 0.141725E+11 | 0.372471E+10 | 744.00 | 0.948582E+10 | 0.468672E+10 | 0.00 | 0.58 | 07-AUG-16:01 | 0.21 | 24-AUG-04:00 | 8380.74 | 13-AUG-16:02 | 6316.91 | 07-AUG-16:04 | 2900.75 | 12-AUG-09:30 | 2334.19 | 07-AUG-16:01 | 0.00 | 01-AUG-00:10 |
| September | 0.122253E+11 | 0.318930E+10 | 720.00 | 0.871062E+10 | 0.351470E+10 | 0.00 | 0.57 | 22-SEP-15:10 | 0.18 | 27-SEP-05:00 | 8105.18 | 22-SEP-15:10 | 6585.01 | 24-SEP-15:30 | 2067.60 | 14-SEP-17:20 | 2258.03 | 22-SEP-15:10 | 0.00 | 01-SEP-00:10 |
| October | 0.894037E+10 | 0.234772E+10 | 743.13 | 0.782879E+10 | 0.111158E+10 | 0.00 | 0.55 | 03-OCT-15:10 | 0.00 | 31-OCT-05:30 | 7432.84 | 03-OCT-15:10 | 6679.47 | 03-OCT-15:10 | 1141.85 | 13-OCT-13:30 | 2117.42 | 03-OCT-15:10 | 0.00 | 01-OCT-00:10 |
| November | 0.526569E+10 | 0.135683E+10 | 665.00 | 0.499147E+10 | 0.274215E+09 | 0.00 | 0.42 | 04-NOV-15:10 | 0.00 | 01-NOV-05:03 | 5612.45 | 04-NOV-15:10 | 5612.45 | 04-NOV-15:10 | 524.17 | 18-NOV-10:50 | 1519.10 | 04-NOV-15:10 | 0.00 | 01-NOV-00:10 |
| December | 0.200406E+10 | 0.515211E+09 | 400.56 | 0.196684E+10 | 37226781.20 | 0.00 | 0.29 | 02-DEC-14:30 | 0.00 | 01-DEC-01:00 | 3930.82 | 02-DEC-14:30 | 3930.82 | 02-DEC-14:30 | 208.86 | 10-DEC-18:40 | 997.42 | 02-DEC-14:30 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.105113E+12 | 0.283880E+11 | 7669.66 | 0.849113E+11 | 0.202016E+11 | 0.00 | ||||||||||||||
| Minimum of Months | 0.119014E+10 | 0.308287E+09 | 310.44 | 0.117373E+10 | 16406518.21 | 0.00 | 0.25 | 0.00 | 3308.65 | 3308.65 | 150.25 | 842.19 | 0.00 | |||||||
| Maximum of Months | 0.152153E+11 | 0.410777E+10 | 744.00 | 0.113673E+11 | 0.473286E+10 | 0.00 | 0.69 | 0.21 | 9137.82 | 8302.31 | 2900.75 | 2657.22 | 0.00 |
Report: DXReportMonthly
For: SPLIT MNW COOLING COIL
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 61903258.79 | 16107639.35 | 43.00 | 59593925.21 | 2309333.59 | 0.00 | 0.08 | 14-JAN-17:10 | 0.00 | 01-JAN-00:10 | 1105.36 | 14-JAN-17:10 | 1036.98 | 14-JAN-17:10 | 69.71 | 14-JAN-16:10 | 284.38 | 14-JAN-17:10 | 0.00 | 01-JAN-00:10 |
| February | 0.123030E+10 | 0.318348E+09 | 326.56 | 0.116634E+10 | 63955786.18 | 0.00 | 0.22 | 22-FEB-17:10 | 0.00 | 01-FEB-00:10 | 2924.74 | 22-FEB-17:10 | 2924.74 | 22-FEB-17:10 | 562.60 | 25-FEB-17:10 | 764.66 | 22-FEB-16:10 | 0.00 | 01-FEB-00:10 |
| March | 0.483276E+10 | 0.127242E+10 | 690.40 | 0.449058E+10 | 0.342179E+09 | 0.00 | 0.41 | 28-MAR-16:30 | 0.00 | 01-MAR-01:30 | 5271.97 | 29-MAR-16:13 | 5166.96 | 29-MAR-16:30 | 738.17 | 10-MAR-21:00 | 1520.11 | 28-MAR-16:30 | 0.00 | 01-MAR-00:10 |
| April | 0.905293E+10 | 0.252342E+10 | 720.00 | 0.844679E+10 | 0.606141E+09 | 0.00 | 0.59 | 27-APR-16:10 | 0.03 | 10-APR-05:05 | 7270.18 | 27-APR-16:10 | 7270.18 | 27-APR-16:10 | 987.44 | 18-APR-14:20 | 2238.30 | 27-APR-16:10 | 0.00 | 01-APR-00:10 |
| May | 0.130092E+11 | 0.371934E+10 | 744.00 | 0.111915E+11 | 0.181769E+10 | 0.00 | 0.68 | 05-MAY-16:10 | 0.16 | 13-MAY-04:00 | 8138.98 | 05-MAY-16:30 | 8138.98 | 05-MAY-16:30 | 1953.39 | 24-MAY-15:10 | 2600.79 | 05-MAY-16:03 | 0.00 | 01-MAY-00:10 |
| June | 0.139012E+11 | 0.394790E+10 | 720.00 | 0.110047E+11 | 0.289651E+10 | 0.00 | 0.68 | 06-JUN-16:08 | 0.19 | 18-JUN-05:00 | 8677.75 | 22-JUN-16:40 | 8217.27 | 06-JUN-16:04 | 2530.70 | 23-JUN-14:10 | 2662.82 | 06-JUN-16:04 | 0.00 | 01-JUN-00:10 |
| July | 0.152039E+11 | 0.410299E+10 | 744.00 | 0.104718E+11 | 0.473207E+10 | 0.00 | 0.64 | 02-JUL-16:50 | 0.19 | 19-JUL-03:00 | 8961.54 | 01-JUL-16:13 | 7068.02 | 02-JUL-16:50 | 2900.83 | 17-JUL-17:10 | 2583.61 | 02-JUL-16:50 | 0.00 | 01-JUL-00:10 |
| August | 0.139879E+11 | 0.367522E+10 | 744.00 | 0.931522E+10 | 0.467269E+10 | 0.00 | 0.58 | 07-AUG-16:17 | 0.21 | 24-AUG-04:00 | 7991.56 | 07-AUG-16:20 | 6180.24 | 07-AUG-16:17 | 2792.64 | 12-AUG-09:30 | 2304.00 | 07-AUG-16:03 | 0.00 | 01-AUG-00:10 |
| September | 0.113809E+11 | 0.296954E+10 | 720.00 | 0.794231E+10 | 0.343857E+10 | 0.00 | 0.51 | 22-SEP-16:01 | 0.17 | 27-SEP-05:00 | 7088.83 | 14-SEP-16:20 | 5532.45 | 22-SEP-16:09 | 2073.04 | 14-SEP-17:20 | 1974.83 | 22-SEP-16:01 | 0.00 | 01-SEP-00:10 |
| October | 0.691226E+10 | 0.182504E+10 | 736.32 | 0.590745E+10 | 0.100481E+10 | 0.00 | 0.45 | 03-OCT-15:10 | 0.00 | 28-OCT-05:03 | 6054.39 | 03-OCT-15:20 | 5317.59 | 03-OCT-15:10 | 1050.40 | 13-OCT-14:10 | 1747.11 | 03-OCT-15:10 | 0.00 | 01-OCT-00:10 |
| November | 0.275414E+10 | 0.720175E+09 | 559.01 | 0.257677E+10 | 0.177368E+09 | 0.00 | 0.26 | 04-NOV-16:10 | 0.00 | 01-NOV-05:03 | 3463.54 | 04-NOV-16:10 | 3430.46 | 04-NOV-16:10 | 406.11 | 08-NOV-22:05 | 946.07 | 04-NOV-16:10 | 0.00 | 01-NOV-00:10 |
| December | 0.346653E+09 | 90192721.66 | 173.78 | 0.338852E+09 | 7801261.06 | 0.00 | 0.12 | 28-DEC-16:10 | 0.00 | 01-DEC-00:10 | 1632.54 | 28-DEC-16:10 | 1632.54 | 28-DEC-16:10 | 93.57 | 16-DEC-17:10 | 421.37 | 28-DEC-16:10 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.926740E+11 | 0.251807E+11 | 6921.07 | 0.729119E+11 | 0.197621E+11 | 0.00 | ||||||||||||||
| Minimum of Months | 61903258.79 | 16107639.35 | 43.00 | 59593925.21 | 2309333.59 | 0.00 | 0.08 | 0.00 | 1105.36 | 1036.98 | 69.71 | 284.38 | 0.00 | |||||||
| Maximum of Months | 0.152039E+11 | 0.410299E+10 | 744.00 | 0.111915E+11 | 0.473207E+10 | 0.00 | 0.68 | 0.21 | 8961.54 | 8217.27 | 2900.83 | 2662.82 | 0.00 |
Report: DXReportMonthly
For: SPLIT MSE COOLING COIL
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.119461E+10 | 0.309612E+09 | 329.71 | 0.117848E+10 | 16133279.10 | 0.00 | 0.24 | 12-JAN-14:30 | 0.00 | 01-JAN-00:10 | 3087.84 | 12-JAN-14:30 | 3087.84 | 12-JAN-14:30 | 143.17 | 13-JAN-14:20 | 787.11 | 12-JAN-14:30 | 0.00 | 01-JAN-00:10 |
| February | 0.285618E+10 | 0.730984E+09 | 462.52 | 0.274418E+10 | 0.112005E+09 | 0.00 | 0.34 | 20-FEB-14:30 | 0.00 | 01-FEB-00:10 | 4353.18 | 20-FEB-14:20 | 4353.18 | 20-FEB-14:20 | 651.73 | 25-FEB-17:10 | 1137.26 | 20-FEB-14:20 | 0.00 | 01-FEB-00:10 |
| March | 0.637366E+10 | 0.166356E+10 | 720.37 | 0.597664E+10 | 0.397019E+09 | 0.00 | 0.43 | 12-MAR-16:10 | 0.00 | 01-MAR-03:10 | 5680.82 | 12-MAR-16:10 | 5360.22 | 29-MAR-15:10 | 783.64 | 10-MAR-21:00 | 1572.23 | 28-MAR-15:10 | 0.00 | 01-MAR-00:10 |
| April | 0.100132E+11 | 0.277421E+10 | 720.00 | 0.937823E+10 | 0.634999E+09 | 0.00 | 0.60 | 15-APR-14:00 | 0.04 | 10-APR-05:10 | 7250.35 | 15-APR-15:10 | 7250.35 | 15-APR-15:10 | 952.51 | 18-APR-14:10 | 2243.57 | 15-APR-15:10 | 0.00 | 01-APR-00:10 |
| May | 0.132468E+11 | 0.377816E+10 | 744.00 | 0.114199E+11 | 0.182689E+10 | 0.00 | 0.65 | 05-MAY-15:10 | 0.16 | 13-MAY-04:00 | 7498.79 | 05-MAY-15:10 | 7498.79 | 05-MAY-15:10 | 1869.83 | 24-MAY-14:20 | 2421.62 | 05-MAY-15:10 | 0.00 | 01-MAY-00:10 |
| June | 0.137402E+11 | 0.389677E+10 | 720.00 | 0.108542E+11 | 0.288598E+10 | 0.00 | 0.64 | 06-JUN-15:10 | 0.19 | 18-JUN-05:00 | 8256.02 | 23-JUN-14:10 | 7514.82 | 06-JUN-15:10 | 2466.57 | 23-JUN-14:10 | 2457.49 | 06-JUN-15:10 | 0.00 | 01-JUN-00:10 |
| July | 0.152270E+11 | 0.410283E+10 | 744.00 | 0.104900E+11 | 0.473697E+10 | 0.00 | 0.62 | 01-JUL-16:01 | 0.19 | 19-JUL-03:00 | 8648.50 | 01-JUL-16:01 | 6338.75 | 02-JUL-16:15 | 2809.72 | 19-JUL-12:00 | 2472.05 | 01-JUL-16:01 | 0.00 | 01-JUL-00:10 |
| August | 0.141833E+11 | 0.372045E+10 | 744.00 | 0.949180E+10 | 0.469152E+10 | 0.00 | 0.56 | 07-AUG-16:10 | 0.21 | 24-AUG-04:00 | 7806.76 | 27-AUG-16:02 | 5869.84 | 07-AUG-16:01 | 2919.52 | 12-AUG-09:30 | 2194.61 | 07-AUG-16:10 | 0.00 | 01-AUG-00:10 |
| September | 0.121961E+11 | 0.317601E+10 | 720.00 | 0.867995E+10 | 0.351620E+10 | 0.00 | 0.56 | 22-SEP-15:10 | 0.18 | 27-SEP-05:00 | 7600.32 | 22-SEP-15:10 | 6119.09 | 28-SEP-14:10 | 2037.02 | 14-SEP-17:20 | 2122.70 | 22-SEP-15:10 | 0.00 | 01-SEP-00:10 |
| October | 0.899013E+10 | 0.235634E+10 | 743.00 | 0.787072E+10 | 0.111942E+10 | 0.00 | 0.53 | 03-OCT-14:10 | 0.00 | 31-OCT-05:30 | 6998.02 | 03-OCT-14:10 | 6359.77 | 03-OCT-14:10 | 1160.10 | 13-OCT-09:40 | 2015.89 | 03-OCT-14:10 | 0.00 | 01-OCT-00:10 |
| November | 0.528324E+10 | 0.135957E+10 | 668.68 | 0.500486E+10 | 0.278386E+09 | 0.00 | 0.40 | 04-NOV-13:40 | 0.00 | 01-NOV-05:03 | 5217.74 | 04-NOV-13:30 | 5202.29 | 04-NOV-13:40 | 601.63 | 09-NOV-09:30 | 1417.97 | 04-NOV-13:40 | 0.00 | 01-NOV-00:10 |
| December | 0.201923E+10 | 0.519224E+09 | 418.20 | 0.198340E+10 | 35832319.99 | 0.00 | 0.28 | 02-DEC-14:00 | 0.00 | 01-DEC-00:50 | 3691.40 | 02-DEC-14:00 | 3691.40 | 02-DEC-14:00 | 190.05 | 10-DEC-18:40 | 939.00 | 02-DEC-14:00 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.105324E+12 | 0.283877E+11 | 7734.48 | 0.850724E+11 | 0.202513E+11 | 0.00 | ||||||||||||||
| Minimum of Months | 0.119461E+10 | 0.309612E+09 | 329.71 | 0.117848E+10 | 16133279.10 | 0.00 | 0.24 | 0.00 | 3087.84 | 3087.84 | 143.17 | 787.11 | 0.00 | |||||||
| Maximum of Months | 0.152270E+11 | 0.410283E+10 | 744.00 | 0.114199E+11 | 0.473697E+10 | 0.00 | 0.65 | 0.21 | 8648.50 | 7514.82 | 2919.52 | 2472.05 | 0.00 |
Report: DXReportMonthly
For: SPLIT MNE COOLING COIL
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 50455050.03 | 13130826.24 | 37.47 | 48594408.71 | 1860641.32 | 0.00 | 0.07 | 14-JAN-17:10 | 0.00 | 01-JAN-00:10 | 852.40 | 14-JAN-17:10 | 824.81 | 26-JAN-14:00 | 56.42 | 14-JAN-16:10 | 219.80 | 14-JAN-17:10 | 0.00 | 01-JAN-00:10 |
| February | 0.126183E+10 | 0.326458E+09 | 347.56 | 0.119549E+10 | 66335271.37 | 0.00 | 0.21 | 24-FEB-16:10 | 0.00 | 01-FEB-00:10 | 2707.35 | 24-FEB-16:10 | 2536.46 | 22-FEB-16:10 | 473.80 | 25-FEB-17:10 | 707.63 | 24-FEB-16:10 | 0.00 | 01-FEB-00:10 |
| March | 0.488874E+10 | 0.128520E+10 | 697.34 | 0.453787E+10 | 0.350866E+09 | 0.00 | 0.36 | 29-MAR-16:03 | 0.00 | 01-MAR-01:20 | 4578.62 | 29-MAR-16:03 | 4481.07 | 29-MAR-16:03 | 737.36 | 10-MAR-21:00 | 1301.52 | 29-MAR-16:03 | 0.00 | 01-MAR-00:10 |
| April | 0.909918E+10 | 0.252974E+10 | 720.00 | 0.848364E+10 | 0.615545E+09 | 0.00 | 0.54 | 15-APR-15:10 | 0.03 | 10-APR-05:10 | 6577.49 | 18-APR-15:10 | 6465.90 | 15-APR-15:10 | 942.16 | 18-APR-14:10 | 2019.45 | 15-APR-15:10 | 0.00 | 01-APR-00:10 |
| May | 0.130702E+11 | 0.372700E+10 | 744.00 | 0.112445E+11 | 0.182579E+10 | 0.00 | 0.64 | 05-MAY-16:10 | 0.16 | 13-MAY-04:00 | 7314.69 | 25-MAY-16:17 | 7310.49 | 05-MAY-16:09 | 1885.91 | 24-MAY-15:10 | 2355.98 | 05-MAY-16:09 | 0.00 | 01-MAY-00:10 |
| June | 0.137867E+11 | 0.390731E+10 | 720.00 | 0.108933E+11 | 0.289337E+10 | 0.00 | 0.64 | 06-JUN-15:10 | 0.20 | 18-JUN-05:00 | 8274.64 | 23-JUN-15:10 | 7441.64 | 06-JUN-15:10 | 2493.23 | 23-JUN-14:10 | 2434.14 | 06-JUN-15:10 | 0.00 | 01-JUN-00:10 |
| July | 0.152142E+11 | 0.409746E+10 | 744.00 | 0.104797E+11 | 0.473455E+10 | 0.00 | 0.61 | 01-JUL-16:01 | 0.19 | 19-JUL-03:00 | 8453.45 | 01-JUL-16:01 | 6278.77 | 02-JUL-17:10 | 2848.41 | 17-JUL-17:10 | 2420.07 | 01-JUL-16:01 | 0.00 | 01-JUL-00:10 |
| August | 0.139977E+11 | 0.367065E+10 | 744.00 | 0.932154E+10 | 0.467611E+10 | 0.00 | 0.56 | 07-AUG-16:10 | 0.22 | 24-AUG-04:00 | 7483.11 | 07-AUG-16:20 | 5728.78 | 07-AUG-16:01 | 2811.29 | 12-AUG-09:30 | 2164.26 | 07-AUG-16:10 | 0.00 | 01-AUG-00:10 |
| September | 0.113515E+11 | 0.295672E+10 | 720.00 | 0.791220E+10 | 0.343929E+10 | 0.00 | 0.48 | 22-SEP-15:10 | 0.17 | 27-SEP-05:00 | 6660.46 | 14-SEP-16:20 | 4994.00 | 22-SEP-15:10 | 2040.78 | 14-SEP-17:20 | 1833.45 | 22-SEP-15:10 | 0.00 | 01-SEP-00:10 |
| October | 0.696293E+10 | 0.183534E+10 | 736.51 | 0.594895E+10 | 0.101399E+10 | 0.00 | 0.43 | 03-OCT-15:10 | 0.00 | 28-OCT-05:03 | 5555.64 | 03-OCT-15:10 | 4868.15 | 03-OCT-15:10 | 1060.19 | 13-OCT-09:40 | 1609.41 | 03-OCT-15:10 | 0.00 | 01-OCT-00:10 |
| November | 0.275914E+10 | 0.720780E+09 | 566.13 | 0.257767E+10 | 0.181469E+09 | 0.00 | 0.23 | 09-NOV-13:00 | 0.00 | 01-NOV-05:03 | 3031.29 | 09-NOV-13:00 | 2890.17 | 04-NOV-16:10 | 471.98 | 09-NOV-09:40 | 827.32 | 09-NOV-13:00 | 0.00 | 01-NOV-00:10 |
| December | 0.322535E+09 | 84013788.31 | 174.27 | 0.315945E+09 | 6589738.62 | 0.00 | 0.10 | 01-DEC-14:00 | 0.00 | 01-DEC-00:10 | 1316.30 | 01-DEC-14:00 | 1316.30 | 01-DEC-14:00 | 75.56 | 16-DEC-17:10 | 343.73 | 01-DEC-14:00 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.927651E+11 | 0.251538E+11 | 6951.27 | 0.729594E+11 | 0.198058E+11 | 0.00 | ||||||||||||||
| Minimum of Months | 50455050.03 | 13130826.24 | 37.47 | 48594408.71 | 1860641.32 | 0.00 | 0.07 | 0.00 | 852.40 | 824.81 | 56.42 | 219.80 | 0.00 | |||||||
| Maximum of Months | 0.152142E+11 | 0.409746E+10 | 744.00 | 0.112445E+11 | 0.473455E+10 | 0.00 | 0.64 | 0.22 | 8453.45 | 7441.64 | 2848.41 | 2434.14 | 0.00 |
Report: DXReportMonthly
For: SPLIT MN1 COOLING COIL
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.115841E+09 | 29991897.63 | 106.01 | 0.108033E+09 | 7807936.41 | 0.00 | 0.09 | 14-JAN-17:10 | 0.00 | 01-JAN-00:10 | 1008.07 | 14-JAN-17:10 | 945.30 | 14-JAN-17:10 | 148.84 | 16-JAN-20:20 | 259.11 | 14-JAN-17:10 | 0.00 | 01-JAN-00:10 |
| February | 0.125783E+10 | 0.324928E+09 | 403.38 | 0.118257E+10 | 75262702.83 | 0.00 | 0.20 | 24-FEB-17:10 | 0.00 | 01-FEB-00:10 | 2352.14 | 24-FEB-17:10 | 2179.41 | 24-FEB-17:05 | 454.24 | 25-FEB-17:10 | 606.36 | 24-FEB-17:10 | 0.00 | 01-FEB-00:10 |
| March | 0.422621E+10 | 0.110962E+10 | 721.23 | 0.389680E+10 | 0.329412E+09 | 0.00 | 0.33 | 29-MAR-16:03 | 0.00 | 01-MAR-03:20 | 3686.62 | 29-MAR-16:13 | 3590.95 | 29-MAR-16:20 | 661.30 | 10-MAR-21:00 | 1051.90 | 29-MAR-16:03 | 0.00 | 01-MAR-00:10 |
| April | 0.736336E+10 | 0.204899E+10 | 720.00 | 0.680899E+10 | 0.554371E+09 | 0.00 | 0.48 | 27-APR-16:06 | 0.04 | 11-APR-05:05 | 5138.96 | 18-APR-16:02 | 4949.10 | 27-APR-16:03 | 762.05 | 18-APR-14:10 | 1551.13 | 27-APR-16:03 | 0.00 | 01-APR-00:10 |
| May | 0.105850E+11 | 0.302316E+10 | 744.00 | 0.897394E+10 | 0.161106E+10 | 0.00 | 0.56 | 05-MAY-16:10 | 0.17 | 13-MAY-04:00 | 5861.77 | 25-MAY-17:10 | 5603.59 | 05-MAY-16:03 | 1544.20 | 22-MAY-23:00 | 1828.49 | 05-MAY-16:03 | 0.00 | 01-MAY-00:10 |
| June | 0.115175E+11 | 0.326308E+10 | 720.00 | 0.890716E+10 | 0.261035E+10 | 0.00 | 0.57 | 06-JUN-16:10 | 0.21 | 18-JUN-04:00 | 6634.08 | 23-JUN-15:10 | 5715.27 | 06-JUN-16:08 | 2070.51 | 23-JUN-14:10 | 1972.49 | 22-JUN-17:10 | 0.00 | 01-JUN-00:10 |
| July | 0.128722E+11 | 0.346596E+10 | 744.00 | 0.869301E+10 | 0.417920E+10 | 0.00 | 0.57 | 01-JUL-16:13 | 0.21 | 19-JUL-03:00 | 6910.84 | 01-JUL-16:13 | 5076.30 | 02-JUL-17:15 | 2313.49 | 17-JUL-17:10 | 1986.86 | 01-JUL-16:13 | 0.00 | 01-JUL-00:10 |
| August | 0.120631E+11 | 0.315758E+10 | 744.00 | 0.785873E+10 | 0.420433E+10 | 0.00 | 0.51 | 07-AUG-17:10 | 0.24 | 24-AUG-04:00 | 6254.97 | 27-AUG-16:02 | 4546.93 | 07-AUG-16:17 | 2403.22 | 12-AUG-09:30 | 1759.94 | 07-AUG-16:20 | 0.00 | 01-AUG-00:10 |
| September | 0.987380E+10 | 0.256351E+10 | 720.00 | 0.673206E+10 | 0.314174E+10 | 0.00 | 0.46 | 14-SEP-17:10 | 0.18 | 29-SEP-04:00 | 5660.18 | 14-SEP-17:20 | 3993.91 | 22-SEP-16:09 | 1857.75 | 14-SEP-17:20 | 1573.63 | 17-SEP-20:00 | 0.00 | 01-SEP-00:10 |
| October | 0.605467E+10 | 0.159042E+10 | 741.79 | 0.510147E+10 | 0.953192E+09 | 0.00 | 0.38 | 03-OCT-15:10 | 0.00 | 29-OCT-05:03 | 4404.62 | 03-OCT-16:10 | 3791.12 | 03-OCT-15:10 | 927.21 | 06-OCT-11:20 | 1269.59 | 03-OCT-15:10 | 0.00 | 01-OCT-00:10 |
| November | 0.263919E+10 | 0.687462E+09 | 643.12 | 0.244358E+10 | 0.195609E+09 | 0.00 | 0.23 | 04-NOV-16:10 | 0.00 | 01-NOV-05:03 | 2532.25 | 04-NOV-16:10 | 2505.81 | 04-NOV-16:10 | 397.29 | 08-NOV-22:05 | 695.54 | 04-NOV-16:10 | 0.00 | 01-NOV-00:10 |
| December | 0.452071E+09 | 0.117469E+09 | 263.37 | 0.438522E+09 | 13548617.45 | 0.00 | 0.12 | 28-DEC-17:10 | 0.00 | 01-DEC-00:20 | 1314.37 | 28-DEC-17:10 | 1311.03 | 28-DEC-17:05 | 127.28 | 10-DEC-18:50 | 339.15 | 28-DEC-17:10 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.790207E+11 | 0.213822E+11 | 7270.91 | 0.611449E+11 | 0.178759E+11 | 0.00 | ||||||||||||||
| Minimum of Months | 0.115841E+09 | 29991897.63 | 106.01 | 0.108033E+09 | 7807936.41 | 0.00 | 0.09 | 0.00 | 1008.07 | 945.30 | 127.28 | 259.11 | 0.00 | |||||||
| Maximum of Months | 0.128722E+11 | 0.346596E+10 | 744.00 | 0.897394E+10 | 0.420433E+10 | 0.00 | 0.57 | 0.24 | 6910.84 | 5715.27 | 2403.22 | 1986.86 | 0.00 |
Report: DXReportMonthly
For: SPLIT MN2 COOLING COIL
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.116814E+09 | 30246258.82 | 106.51 | 0.108996E+09 | 7817750.00 | 0.00 | 0.09 | 14-JAN-17:10 | 0.00 | 01-JAN-00:10 | 1006.98 | 14-JAN-17:10 | 944.28 | 14-JAN-17:10 | 147.92 | 16-JAN-20:20 | 258.83 | 14-JAN-17:10 | 0.00 | 01-JAN-00:10 |
| February | 0.126670E+10 | 0.327209E+09 | 404.86 | 0.119110E+10 | 75592260.94 | 0.00 | 0.20 | 24-FEB-17:10 | 0.00 | 01-FEB-00:10 | 2354.83 | 24-FEB-17:10 | 2182.02 | 24-FEB-17:05 | 453.02 | 25-FEB-17:10 | 607.03 | 24-FEB-17:10 | 0.00 | 01-FEB-00:10 |
| March | 0.423019E+10 | 0.111064E+10 | 721.21 | 0.390056E+10 | 0.329633E+09 | 0.00 | 0.33 | 29-MAR-16:03 | 0.00 | 01-MAR-03:10 | 3678.56 | 29-MAR-16:13 | 3583.08 | 29-MAR-16:20 | 661.43 | 10-MAR-21:00 | 1049.88 | 29-MAR-16:03 | 0.00 | 01-MAR-00:10 |
| April | 0.736587E+10 | 0.204964E+10 | 720.00 | 0.681125E+10 | 0.554620E+09 | 0.00 | 0.48 | 27-APR-16:06 | 0.04 | 11-APR-05:05 | 5132.72 | 18-APR-16:02 | 4938.08 | 27-APR-16:03 | 761.89 | 18-APR-14:10 | 1547.85 | 27-APR-16:03 | 0.00 | 01-APR-00:10 |
| May | 0.105875E+11 | 0.302378E+10 | 744.00 | 0.897618E+10 | 0.161128E+10 | 0.00 | 0.56 | 05-MAY-16:10 | 0.17 | 13-MAY-04:00 | 5850.97 | 25-MAY-17:10 | 5597.12 | 05-MAY-16:03 | 1544.29 | 22-MAY-23:00 | 1826.45 | 05-MAY-16:03 | 0.00 | 01-MAY-00:10 |
| June | 0.115142E+11 | 0.326207E+10 | 720.00 | 0.890403E+10 | 0.261015E+10 | 0.00 | 0.57 | 06-JUN-16:10 | 0.21 | 18-JUN-04:00 | 6632.31 | 23-JUN-15:10 | 5707.08 | 06-JUN-16:08 | 2070.03 | 23-JUN-14:10 | 1969.13 | 22-JUN-17:10 | 0.00 | 01-JUN-00:10 |
| July | 0.128728E+11 | 0.346599E+10 | 744.00 | 0.869347E+10 | 0.417933E+10 | 0.00 | 0.57 | 01-JUL-16:13 | 0.21 | 19-JUL-03:00 | 6906.83 | 01-JUL-16:13 | 5065.34 | 02-JUL-17:15 | 2312.40 | 17-JUL-17:10 | 1985.70 | 01-JUL-16:13 | 0.00 | 01-JUL-00:10 |
| August | 0.120637E+11 | 0.315764E+10 | 744.00 | 0.785925E+10 | 0.420450E+10 | 0.00 | 0.51 | 07-AUG-17:10 | 0.24 | 24-AUG-04:00 | 6251.54 | 27-AUG-16:02 | 4542.31 | 07-AUG-16:17 | 2403.58 | 12-AUG-09:30 | 1758.35 | 07-AUG-16:04 | 0.00 | 01-AUG-00:10 |
| September | 0.987308E+10 | 0.256326E+10 | 720.00 | 0.673137E+10 | 0.314170E+10 | 0.00 | 0.46 | 14-SEP-17:10 | 0.18 | 29-SEP-04:00 | 5655.49 | 14-SEP-17:20 | 3987.45 | 22-SEP-16:09 | 1856.84 | 14-SEP-17:20 | 1571.75 | 17-SEP-20:00 | 0.00 | 01-SEP-00:10 |
| October | 0.605721E+10 | 0.159107E+10 | 741.79 | 0.510378E+10 | 0.953423E+09 | 0.00 | 0.38 | 03-OCT-15:10 | 0.00 | 29-OCT-05:03 | 4399.12 | 03-OCT-16:10 | 3790.08 | 03-OCT-15:10 | 928.37 | 06-OCT-11:20 | 1269.12 | 03-OCT-15:10 | 0.00 | 01-OCT-00:10 |
| November | 0.264208E+10 | 0.688207E+09 | 643.36 | 0.244640E+10 | 0.195686E+09 | 0.00 | 0.23 | 04-NOV-16:10 | 0.00 | 01-NOV-05:03 | 2526.01 | 04-NOV-16:10 | 2499.64 | 04-NOV-16:10 | 396.94 | 08-NOV-22:05 | 693.87 | 04-NOV-16:10 | 0.00 | 01-NOV-00:10 |
| December | 0.456698E+09 | 0.118670E+09 | 264.53 | 0.443078E+09 | 13619233.51 | 0.00 | 0.12 | 28-DEC-17:10 | 0.00 | 01-DEC-00:20 | 1312.87 | 28-DEC-17:10 | 1309.51 | 28-DEC-17:05 | 127.35 | 10-DEC-18:50 | 338.76 | 28-DEC-17:10 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.790468E+11 | 0.213884E+11 | 7274.26 | 0.611695E+11 | 0.178773E+11 | 0.00 | ||||||||||||||
| Minimum of Months | 0.116814E+09 | 30246258.82 | 106.51 | 0.108996E+09 | 7817750.00 | 0.00 | 0.09 | 0.00 | 1006.98 | 944.28 | 127.35 | 258.83 | 0.00 | |||||||
| Maximum of Months | 0.128728E+11 | 0.346599E+10 | 744.00 | 0.897618E+10 | 0.420450E+10 | 0.00 | 0.57 | 0.24 | 6906.83 | 5707.08 | 2403.58 | 1985.70 | 0.00 |
Report: DXReportMonthly
For: SPLIT MS1 COOLING COIL
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.165255E+10 | 0.426585E+09 | 453.01 | 0.161741E+10 | 35139127.16 | 0.00 | 0.27 | 12-JAN-14:30 | 0.00 | 01-JAN-00:10 | 3081.47 | 12-JAN-14:30 | 3081.47 | 12-JAN-14:30 | 168.45 | 16-JAN-20:20 | 781.82 | 12-JAN-14:30 | 0.00 | 01-JAN-00:10 |
| February | 0.295931E+10 | 0.756157E+09 | 543.75 | 0.283264E+10 | 0.126671E+09 | 0.00 | 0.34 | 20-FEB-14:30 | 0.00 | 01-FEB-00:10 | 3940.71 | 20-FEB-14:30 | 3940.71 | 20-FEB-14:30 | 626.45 | 25-FEB-17:10 | 1027.97 | 20-FEB-14:30 | 0.00 | 01-FEB-00:10 |
| March | 0.573442E+10 | 0.149510E+10 | 739.45 | 0.535477E+10 | 0.379655E+09 | 0.00 | 0.42 | 12-MAR-16:10 | 0.00 | 01-MAR-08:50 | 4912.08 | 12-MAR-16:10 | 4573.19 | 12-MAR-16:05 | 708.49 | 10-MAR-21:00 | 1342.32 | 12-MAR-16:10 | 0.00 | 01-MAR-00:10 |
| April | 0.828257E+10 | 0.229730E+10 | 720.00 | 0.770621E+10 | 0.576364E+09 | 0.00 | 0.53 | 15-APR-15:10 | 0.06 | 11-APR-05:10 | 5676.28 | 18-APR-15:10 | 5629.95 | 15-APR-15:10 | 774.02 | 18-APR-14:10 | 1761.39 | 15-APR-15:10 | 0.00 | 01-APR-00:10 |
| May | 0.107611E+11 | 0.307507E+10 | 744.00 | 0.914932E+10 | 0.161176E+10 | 0.00 | 0.57 | 05-MAY-16:10 | 0.17 | 13-MAY-04:00 | 5981.49 | 20-MAY-16:04 | 5769.12 | 05-MAY-16:03 | 1544.37 | 22-MAY-23:00 | 1879.69 | 05-MAY-16:03 | 0.00 | 01-MAY-00:10 |
| June | 0.114673E+11 | 0.325168E+10 | 720.00 | 0.886647E+10 | 0.260083E+10 | 0.00 | 0.56 | 06-JUN-15:10 | 0.21 | 18-JUN-04:00 | 6594.75 | 23-JUN-15:10 | 5705.57 | 06-JUN-15:10 | 2043.66 | 23-JUN-14:10 | 1952.85 | 10-JUN-16:20 | 0.00 | 01-JUN-00:10 |
| July | 0.128821E+11 | 0.347094E+10 | 744.00 | 0.870203E+10 | 0.418008E+10 | 0.00 | 0.58 | 01-JUL-16:01 | 0.21 | 19-JUL-03:00 | 7085.21 | 01-JUL-16:01 | 5096.12 | 02-JUL-16:50 | 2290.94 | 01-JUL-16:01 | 2035.33 | 01-JUL-16:01 | 0.00 | 01-JUL-00:10 |
| August | 0.122491E+11 | 0.320814E+10 | 744.00 | 0.802814E+10 | 0.422096E+10 | 0.00 | 0.53 | 27-AUG-16:02 | 0.23 | 24-AUG-04:00 | 6650.28 | 27-AUG-16:02 | 4683.13 | 07-AUG-16:03 | 2510.52 | 12-AUG-09:30 | 1841.92 | 27-AUG-16:02 | 0.00 | 01-AUG-00:10 |
| September | 0.107297E+11 | 0.278723E+10 | 720.00 | 0.750242E+10 | 0.322729E+10 | 0.00 | 0.52 | 24-SEP-16:10 | 0.20 | 27-SEP-05:00 | 6250.93 | 24-SEP-16:10 | 5030.67 | 24-SEP-15:10 | 1851.08 | 14-SEP-17:20 | 1755.28 | 22-SEP-15:10 | 0.00 | 01-SEP-00:10 |
| October | 0.810863E+10 | 0.211950E+10 | 744.00 | 0.703959E+10 | 0.106904E+10 | 0.00 | 0.50 | 03-OCT-14:10 | 0.02 | 31-OCT-05:40 | 5745.63 | 03-OCT-14:10 | 5210.39 | 03-OCT-14:10 | 1030.66 | 06-OCT-11:30 | 1664.39 | 03-OCT-14:10 | 0.00 | 01-OCT-00:10 |
| November | 0.524371E+10 | 0.134590E+10 | 715.78 | 0.494650E+10 | 0.297212E+09 | 0.00 | 0.41 | 04-NOV-14:00 | 0.00 | 25-NOV-04:30 | 4689.91 | 04-NOV-13:50 | 4679.72 | 04-NOV-14:00 | 512.84 | 18-NOV-10:50 | 1274.79 | 04-NOV-14:00 | 0.00 | 01-NOV-00:10 |
| December | 0.245140E+10 | 0.628803E+09 | 535.85 | 0.240095E+10 | 50448788.63 | 0.00 | 0.32 | 02-DEC-14:00 | 0.00 | 01-DEC-03:10 | 3647.42 | 02-DEC-14:00 | 3647.42 | 02-DEC-14:00 | 251.48 | 10-DEC-18:40 | 923.07 | 02-DEC-14:00 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.925219E+11 | 0.248624E+11 | 8123.84 | 0.741464E+11 | 0.183755E+11 | 0.00 | ||||||||||||||
| Minimum of Months | 0.165255E+10 | 0.426585E+09 | 453.01 | 0.161741E+10 | 35139127.16 | 0.00 | 0.27 | 0.00 | 3081.47 | 3081.47 | 168.45 | 781.82 | 0.00 | |||||||
| Maximum of Months | 0.128821E+11 | 0.347094E+10 | 744.00 | 0.914932E+10 | 0.422096E+10 | 0.00 | 0.58 | 0.23 | 7085.21 | 5769.12 | 2510.52 | 2035.33 | 0.00 |
Report: DXReportMonthly
For: SPLIT MS2 COOLING COIL
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.165903E+10 | 0.428240E+09 | 453.38 | 0.162386E+10 | 35169848.68 | 0.00 | 0.27 | 12-JAN-14:30 | 0.00 | 01-JAN-00:10 | 3086.98 | 12-JAN-14:30 | 3086.98 | 12-JAN-14:30 | 168.44 | 16-JAN-20:20 | 783.14 | 12-JAN-14:30 | 0.00 | 01-JAN-00:10 |
| February | 0.296548E+10 | 0.757690E+09 | 544.20 | 0.283864E+10 | 0.126837E+09 | 0.00 | 0.34 | 20-FEB-14:30 | 0.00 | 01-FEB-00:10 | 3947.21 | 20-FEB-14:30 | 3947.21 | 20-FEB-14:30 | 625.24 | 25-FEB-17:10 | 1029.54 | 20-FEB-14:30 | 0.00 | 01-FEB-00:10 |
| March | 0.573760E+10 | 0.149588E+10 | 739.45 | 0.535778E+10 | 0.379820E+09 | 0.00 | 0.42 | 12-MAR-16:10 | 0.00 | 01-MAR-08:50 | 4907.13 | 12-MAR-16:10 | 4568.54 | 12-MAR-16:05 | 708.60 | 10-MAR-21:00 | 1341.00 | 12-MAR-16:10 | 0.00 | 01-MAR-00:10 |
| April | 0.828500E+10 | 0.229789E+10 | 720.00 | 0.770840E+10 | 0.576599E+09 | 0.00 | 0.53 | 15-APR-15:10 | 0.06 | 11-APR-05:10 | 5675.90 | 18-APR-15:10 | 5630.94 | 15-APR-15:10 | 773.85 | 18-APR-14:10 | 1761.58 | 15-APR-15:10 | 0.00 | 01-APR-00:10 |
| May | 0.107636E+11 | 0.307569E+10 | 744.00 | 0.915157E+10 | 0.161200E+10 | 0.00 | 0.57 | 05-MAY-16:10 | 0.17 | 13-MAY-04:00 | 5977.04 | 20-MAY-16:04 | 5762.60 | 05-MAY-16:03 | 1544.47 | 22-MAY-23:00 | 1877.64 | 05-MAY-16:03 | 0.00 | 01-MAY-00:10 |
| June | 0.114640E+11 | 0.325067E+10 | 720.00 | 0.886335E+10 | 0.260064E+10 | 0.00 | 0.56 | 06-JUN-15:10 | 0.21 | 18-JUN-04:00 | 6593.00 | 23-JUN-15:10 | 5704.18 | 06-JUN-15:10 | 2043.20 | 23-JUN-14:10 | 1948.45 | 10-JUN-16:10 | 0.00 | 01-JUN-00:10 |
| July | 0.128827E+11 | 0.347098E+10 | 744.00 | 0.870249E+10 | 0.418023E+10 | 0.00 | 0.58 | 01-JUL-16:01 | 0.21 | 19-JUL-03:00 | 7081.92 | 01-JUL-16:01 | 5086.25 | 02-JUL-16:50 | 2289.59 | 01-JUL-16:01 | 2034.36 | 01-JUL-16:01 | 0.00 | 01-JUL-00:10 |
| August | 0.122498E+11 | 0.320821E+10 | 744.00 | 0.802866E+10 | 0.422114E+10 | 0.00 | 0.53 | 27-AUG-16:02 | 0.23 | 24-AUG-04:00 | 6646.83 | 27-AUG-16:02 | 4679.00 | 07-AUG-16:03 | 2510.89 | 12-AUG-09:30 | 1840.94 | 27-AUG-16:02 | 0.00 | 01-AUG-00:10 |
| September | 0.107290E+11 | 0.278697E+10 | 720.00 | 0.750172E+10 | 0.322725E+10 | 0.00 | 0.52 | 22-SEP-15:10 | 0.20 | 27-SEP-05:00 | 6246.79 | 22-SEP-15:10 | 5032.62 | 27-SEP-14:10 | 1850.27 | 14-SEP-17:20 | 1754.33 | 22-SEP-15:10 | 0.00 | 01-SEP-00:10 |
| October | 0.811090E+10 | 0.212003E+10 | 744.00 | 0.704168E+10 | 0.106923E+10 | 0.00 | 0.50 | 03-OCT-14:10 | 0.02 | 31-OCT-05:40 | 5750.23 | 03-OCT-14:10 | 5215.16 | 03-OCT-14:10 | 1031.42 | 06-OCT-11:30 | 1665.56 | 03-OCT-14:10 | 0.00 | 01-OCT-00:10 |
| November | 0.524499E+10 | 0.134617E+10 | 715.78 | 0.494774E+10 | 0.297247E+09 | 0.00 | 0.41 | 04-NOV-13:50 | 0.00 | 25-NOV-04:30 | 4695.07 | 04-NOV-13:50 | 4683.87 | 04-NOV-14:00 | 513.92 | 18-NOV-10:50 | 1275.79 | 04-NOV-14:00 | 0.00 | 01-NOV-00:10 |
| December | 0.245528E+10 | 0.629776E+09 | 535.66 | 0.240485E+10 | 50427542.82 | 0.00 | 0.32 | 02-DEC-14:00 | 0.00 | 01-DEC-03:10 | 3651.79 | 02-DEC-14:00 | 3651.79 | 02-DEC-14:00 | 250.95 | 10-DEC-18:40 | 924.10 | 02-DEC-14:00 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.925473E+11 | 0.248682E+11 | 8124.48 | 0.741707E+11 | 0.183766E+11 | 0.00 | ||||||||||||||
| Minimum of Months | 0.165903E+10 | 0.428240E+09 | 453.38 | 0.162386E+10 | 35169848.68 | 0.00 | 0.27 | 0.00 | 3086.98 | 3086.98 | 168.44 | 783.14 | 0.00 | |||||||
| Maximum of Months | 0.128827E+11 | 0.347098E+10 | 744.00 | 0.915157E+10 | 0.422114E+10 | 0.00 | 0.58 | 0.23 | 7081.92 | 5762.60 | 2510.89 | 2034.36 | 0.00 |
Report: DXReportMonthly
For: SPLIT TSW COOLING COIL
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.438949E+09 | 0.113753E+09 | 173.56 | 0.435622E+09 | 3326507.05 | 0.00 | 0.25 | 12-JAN-15:20 | 0.00 | 01-JAN-00:10 | 1860.57 | 12-JAN-15:20 | 1860.57 | 12-JAN-15:20 | 76.23 | 13-JAN-14:50 | 473.57 | 12-JAN-15:20 | 0.00 | 01-JAN-00:10 |
| February | 0.117173E+10 | 0.300319E+09 | 285.67 | 0.113782E+10 | 33914168.05 | 0.00 | 0.39 | 20-FEB-15:20 | 0.00 | 01-FEB-00:10 | 2928.75 | 20-FEB-15:20 | 2928.75 | 20-FEB-15:20 | 398.87 | 25-FEB-17:10 | 756.09 | 20-FEB-15:20 | 0.00 | 01-FEB-00:10 |
| March | 0.313031E+10 | 0.822303E+09 | 549.97 | 0.297048E+10 | 0.159834E+09 | 0.00 | 0.57 | 28-MAR-16:04 | 0.00 | 01-MAR-00:10 | 4201.72 | 28-MAR-16:01 | 4201.72 | 28-MAR-16:01 | 411.68 | 10-MAR-20:50 | 1209.09 | 28-MAR-16:01 | 0.00 | 01-MAR-00:10 |
| April | 0.557629E+10 | 0.155659E+10 | 710.49 | 0.526758E+10 | 0.308706E+09 | 0.00 | 0.74 | 15-APR-15:10 | 0.00 | 10-APR-03:00 | 5265.53 | 15-APR-15:20 | 5265.53 | 15-APR-15:20 | 600.10 | 18-APR-14:10 | 1592.16 | 15-APR-15:10 | 0.00 | 01-APR-00:10 |
| May | 0.767072E+10 | 0.219821E+10 | 744.00 | 0.669755E+10 | 0.973166E+09 | 0.00 | 0.81 | 05-MAY-16:10 | 0.10 | 13-MAY-04:00 | 5583.85 | 05-MAY-16:03 | 5583.85 | 05-MAY-16:03 | 1160.66 | 24-MAY-15:10 | 1747.21 | 05-MAY-16:03 | 0.00 | 01-MAY-00:10 |
| June | 0.805044E+10 | 0.229228E+10 | 720.00 | 0.650683E+10 | 0.154362E+10 | 0.00 | 0.80 | 06-JUN-16:10 | 0.13 | 18-JUN-05:00 | 5573.03 | 10-JUN-16:03 | 5555.88 | 06-JUN-15:30 | 1471.47 | 23-JUN-13:40 | 1768.32 | 06-JUN-15:20 | 0.00 | 01-JUN-00:10 |
| July | 0.871109E+10 | 0.235481E+10 | 744.00 | 0.612453E+10 | 0.258656E+10 | 0.00 | 0.74 | 02-JUL-16:30 | 0.13 | 19-JUL-03:00 | 5804.85 | 01-JUL-16:01 | 4802.69 | 02-JUL-16:30 | 1727.68 | 19-JUL-12:00 | 1685.26 | 02-JUL-16:30 | 0.00 | 01-JUL-00:10 |
| August | 0.796572E+10 | 0.209867E+10 | 744.00 | 0.544329E+10 | 0.252242E+10 | 0.00 | 0.67 | 07-AUG-16:03 | 0.15 | 24-AUG-04:00 | 5333.78 | 13-AUG-16:02 | 4224.27 | 07-AUG-16:03 | 1668.48 | 12-AUG-09:40 | 1494.26 | 07-AUG-16:03 | 0.00 | 01-AUG-00:10 |
| September | 0.664071E+10 | 0.173951E+10 | 720.00 | 0.480342E+10 | 0.183729E+10 | 0.00 | 0.66 | 22-SEP-15:10 | 0.10 | 27-SEP-05:00 | 5264.99 | 22-SEP-15:10 | 4397.40 | 24-SEP-15:30 | 1165.50 | 05-SEP-17:20 | 1449.31 | 22-SEP-15:10 | 0.00 | 01-SEP-00:10 |
| October | 0.453927E+10 | 0.120142E+10 | 686.08 | 0.404060E+10 | 0.498674E+09 | 0.00 | 0.64 | 03-OCT-15:10 | 0.00 | 09-OCT-05:05 | 4937.30 | 03-OCT-15:10 | 4485.50 | 03-OCT-14:40 | 682.40 | 13-OCT-11:00 | 1386.57 | 03-OCT-14:40 | 0.00 | 01-OCT-00:10 |
| November | 0.231958E+10 | 0.600377E+09 | 415.66 | 0.223425E+10 | 85334228.63 | 0.00 | 0.47 | 04-NOV-15:10 | 0.00 | 01-NOV-01:00 | 3607.38 | 04-NOV-15:10 | 3607.38 | 04-NOV-15:10 | 318.62 | 09-NOV-10:20 | 967.60 | 04-NOV-15:10 | 0.00 | 01-NOV-00:10 |
| December | 0.683761E+09 | 0.175866E+09 | 233.49 | 0.675765E+09 | 7995865.37 | 0.00 | 0.30 | 02-DEC-15:00 | 0.00 | 01-DEC-00:10 | 2235.38 | 02-DEC-15:00 | 2235.38 | 02-DEC-15:00 | 87.73 | 16-DEC-17:10 | 566.35 | 02-DEC-15:00 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.568986E+11 | 0.154541E+11 | 6726.91 | 0.463377E+11 | 0.105608E+11 | 0.00 | ||||||||||||||
| Minimum of Months | 0.438949E+09 | 0.113753E+09 | 173.56 | 0.435622E+09 | 3326507.05 | 0.00 | 0.25 | 0.00 | 1860.57 | 1860.57 | 76.23 | 473.57 | 0.00 | |||||||
| Maximum of Months | 0.871109E+10 | 0.235481E+10 | 744.00 | 0.669755E+10 | 0.258656E+10 | 0.00 | 0.81 | 0.15 | 5804.85 | 5583.85 | 1727.68 | 1768.32 | 0.00 |
Report: DXReportMonthly
For: SPLIT TNW COOLING COIL
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 29183432.45 | 7628187.42 | 30.72 | 28629820.54 | 553611.91 | 0.00 | 0.08 | 12-JAN-16:10 | 0.00 | 01-JAN-00:10 | 561.27 | 12-JAN-16:10 | 561.27 | 12-JAN-16:10 | 30.38 | 14-JAN-16:10 | 146.45 | 12-JAN-16:10 | 0.00 | 01-JAN-00:10 |
| February | 0.480254E+09 | 0.124804E+09 | 206.50 | 0.461078E+09 | 19176119.84 | 0.00 | 0.24 | 22-FEB-16:10 | 0.00 | 01-FEB-00:10 | 1773.62 | 22-FEB-16:10 | 1773.62 | 22-FEB-16:10 | 287.89 | 25-FEB-17:10 | 466.83 | 22-FEB-16:10 | 0.00 | 01-FEB-00:10 |
| March | 0.236364E+10 | 0.627175E+09 | 523.36 | 0.222226E+10 | 0.141377E+09 | 0.00 | 0.49 | 28-MAR-16:30 | 0.00 | 01-MAR-00:10 | 3574.24 | 28-MAR-16:30 | 3574.24 | 28-MAR-16:30 | 394.19 | 10-MAR-20:50 | 1038.51 | 28-MAR-16:20 | 0.00 | 01-MAR-00:10 |
| April | 0.507197E+10 | 0.142286E+10 | 708.15 | 0.477113E+10 | 0.300839E+09 | 0.00 | 0.69 | 27-APR-16:10 | 0.00 | 05-APR-06:00 | 4904.84 | 27-APR-16:03 | 4904.84 | 27-APR-16:03 | 597.32 | 18-APR-14:20 | 1484.36 | 27-APR-16:10 | 0.00 | 01-APR-00:10 |
| May | 0.757312E+10 | 0.217116E+10 | 744.00 | 0.659806E+10 | 0.975066E+09 | 0.00 | 0.80 | 05-MAY-16:10 | 0.11 | 13-MAY-04:00 | 5462.27 | 05-MAY-16:05 | 5462.27 | 05-MAY-16:05 | 1172.33 | 24-MAY-15:10 | 1713.66 | 05-MAY-16:05 | 0.00 | 01-MAY-00:10 |
| June | 0.807275E+10 | 0.229817E+10 | 720.00 | 0.652423E+10 | 0.154851E+10 | 0.00 | 0.80 | 06-JUN-16:04 | 0.13 | 18-JUN-05:00 | 5642.02 | 22-JUN-16:30 | 5551.72 | 06-JUN-16:03 | 1484.23 | 23-JUN-14:10 | 1763.25 | 06-JUN-16:03 | 0.00 | 01-JUN-00:10 |
| July | 0.870610E+10 | 0.235345E+10 | 744.00 | 0.611901E+10 | 0.258709E+10 | 0.00 | 0.73 | 02-JUL-16:40 | 0.13 | 19-JUL-03:00 | 5677.86 | 01-JUL-16:13 | 4736.63 | 02-JUL-16:50 | 1735.09 | 19-JUL-12:00 | 1660.00 | 02-JUL-16:40 | 0.00 | 01-JUL-00:10 |
| August | 0.786120E+10 | 0.207170E+10 | 744.00 | 0.534438E+10 | 0.251683E+10 | 0.00 | 0.66 | 07-AUG-16:10 | 0.16 | 24-AUG-04:00 | 5160.78 | 07-AUG-16:20 | 4124.11 | 07-AUG-16:03 | 1608.36 | 12-AUG-09:40 | 1473.20 | 07-AUG-16:10 | 0.00 | 01-AUG-00:10 |
| September | 0.617989E+10 | 0.162087E+10 | 720.00 | 0.437788E+10 | 0.180201E+10 | 0.00 | 0.58 | 22-SEP-15:20 | 0.10 | 27-SEP-05:00 | 4560.36 | 22-SEP-15:20 | 3631.22 | 22-SEP-16:01 | 1170.71 | 05-SEP-17:20 | 1268.50 | 22-SEP-15:20 | 0.00 | 01-SEP-00:10 |
| October | 0.345336E+10 | 0.922229E+09 | 667.47 | 0.300312E+10 | 0.450245E+09 | 0.00 | 0.53 | 03-OCT-15:10 | 0.00 | 09-OCT-04:50 | 4035.31 | 03-OCT-15:10 | 3591.53 | 03-OCT-15:10 | 622.93 | 13-OCT-14:10 | 1151.84 | 03-OCT-15:10 | 0.00 | 01-OCT-00:10 |
| November | 0.110407E+10 | 0.291670E+09 | 337.50 | 0.105046E+10 | 53618735.73 | 0.00 | 0.29 | 09-NOV-15:10 | 0.00 | 01-NOV-00:10 | 2170.04 | 09-NOV-15:10 | 2127.14 | 04-NOV-15:30 | 215.13 | 09-NOV-11:00 | 587.89 | 09-NOV-15:10 | 0.00 | 01-NOV-00:10 |
| December | 89525827.62 | 23373533.97 | 81.42 | 88268652.93 | 1257174.70 | 0.00 | 0.11 | 28-DEC-16:10 | 0.00 | 01-DEC-00:10 | 808.50 | 28-DEC-16:10 | 808.50 | 28-DEC-16:10 | 38.34 | 16-DEC-16:10 | 209.14 | 28-DEC-16:10 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.509851E+11 | 0.139351E+11 | 6227.12 | 0.405885E+11 | 0.103966E+11 | 0.00 | ||||||||||||||
| Minimum of Months | 29183432.45 | 7628187.42 | 30.72 | 28629820.54 | 553611.91 | 0.00 | 0.08 | 0.00 | 561.27 | 561.27 | 30.38 | 146.45 | 0.00 | |||||||
| Maximum of Months | 0.870610E+10 | 0.235345E+10 | 744.00 | 0.659806E+10 | 0.258709E+10 | 0.00 | 0.80 | 0.16 | 5677.86 | 5551.72 | 1735.09 | 1763.25 | 0.00 |
Report: DXReportMonthly
For: SPLIT TSE COOLING COIL
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.406419E+09 | 0.105390E+09 | 171.11 | 0.403369E+09 | 3049988.52 | 0.00 | 0.24 | 12-JAN-14:40 | 0.00 | 01-JAN-00:10 | 1703.93 | 12-JAN-14:40 | 1703.93 | 12-JAN-14:40 | 70.33 | 13-JAN-14:20 | 434.48 | 12-JAN-14:40 | 0.00 | 01-JAN-00:10 |
| February | 0.117779E+10 | 0.301762E+09 | 294.67 | 0.114359E+10 | 34191751.28 | 0.00 | 0.38 | 20-FEB-14:30 | 0.00 | 01-FEB-00:10 | 2705.41 | 20-FEB-14:30 | 2705.41 | 20-FEB-14:30 | 330.08 | 25-FEB-17:10 | 702.58 | 20-FEB-14:30 | 0.00 | 01-FEB-00:10 |
| March | 0.315352E+10 | 0.826615E+09 | 558.58 | 0.298841E+10 | 0.165110E+09 | 0.00 | 0.53 | 28-MAR-15:10 | 0.00 | 01-MAR-00:10 | 3722.44 | 29-MAR-14:10 | 3681.07 | 28-MAR-15:10 | 409.91 | 10-MAR-20:50 | 1070.02 | 28-MAR-15:10 | 0.00 | 01-MAR-00:10 |
| April | 0.560420E+10 | 0.155896E+10 | 710.92 | 0.528829E+10 | 0.315911E+09 | 0.00 | 0.73 | 15-APR-14:00 | 0.00 | 05-APR-06:00 | 4956.63 | 15-APR-14:00 | 4956.63 | 15-APR-14:00 | 576.29 | 18-APR-14:10 | 1502.12 | 15-APR-14:00 | 0.00 | 01-APR-00:10 |
| May | 0.770693E+10 | 0.220070E+10 | 744.00 | 0.672646E+10 | 0.980469E+09 | 0.00 | 0.77 | 05-MAY-15:10 | 0.11 | 13-MAY-04:00 | 5056.75 | 05-MAY-15:10 | 5056.75 | 05-MAY-15:10 | 1131.59 | 24-MAY-14:20 | 1599.24 | 05-MAY-15:10 | 0.00 | 01-MAY-00:10 |
| June | 0.798971E+10 | 0.226839E+10 | 720.00 | 0.644462E+10 | 0.154509E+10 | 0.00 | 0.77 | 06-JUN-15:10 | 0.14 | 18-JUN-05:00 | 5339.43 | 23-JUN-14:10 | 5117.29 | 06-JUN-15:10 | 1453.15 | 23-JUN-13:00 | 1637.32 | 06-JUN-15:10 | 0.00 | 01-JUN-00:10 |
| July | 0.871612E+10 | 0.234942E+10 | 744.00 | 0.612629E+10 | 0.258983E+10 | 0.00 | 0.71 | 01-JUL-13:00 | 0.13 | 19-JUL-03:00 | 5445.14 | 01-JUL-13:00 | 4239.09 | 07-JUL-14:10 | 1740.75 | 19-JUL-11:50 | 1556.45 | 01-JUL-13:00 | 0.00 | 01-JUL-00:10 |
| August | 0.797270E+10 | 0.209480E+10 | 744.00 | 0.544611E+10 | 0.252659E+10 | 0.00 | 0.65 | 07-AUG-15:10 | 0.16 | 24-AUG-04:00 | 4902.38 | 13-AUG-16:02 | 3937.56 | 07-AUG-15:10 | 1680.98 | 12-AUG-09:40 | 1407.00 | 07-AUG-15:10 | 0.00 | 01-AUG-00:10 |
| September | 0.662676E+10 | 0.173148E+10 | 720.00 | 0.478625E+10 | 0.184051E+10 | 0.00 | 0.65 | 22-SEP-14:20 | 0.10 | 27-SEP-05:00 | 4934.49 | 22-SEP-14:20 | 4089.80 | 28-SEP-14:10 | 1150.29 | 05-SEP-17:20 | 1360.88 | 22-SEP-14:20 | 0.00 | 01-SEP-00:10 |
| October | 0.456853E+10 | 0.120595E+10 | 686.93 | 0.406375E+10 | 0.504783E+09 | 0.00 | 0.64 | 03-OCT-14:10 | 0.00 | 09-OCT-05:05 | 4667.89 | 03-OCT-14:10 | 4285.33 | 03-OCT-14:10 | 707.57 | 13-OCT-10:20 | 1323.88 | 03-OCT-14:10 | 0.00 | 01-OCT-00:10 |
| November | 0.231526E+10 | 0.598336E+09 | 421.04 | 0.222776E+10 | 87497287.61 | 0.00 | 0.46 | 09-NOV-13:30 | 0.00 | 01-NOV-00:50 | 3385.61 | 09-NOV-13:30 | 3335.97 | 04-NOV-14:00 | 372.05 | 09-NOV-09:50 | 899.92 | 04-NOV-14:00 | 0.00 | 01-NOV-00:10 |
| December | 0.664572E+09 | 0.170976E+09 | 237.83 | 0.657315E+09 | 7256795.55 | 0.00 | 0.28 | 02-DEC-14:00 | 0.00 | 01-DEC-00:10 | 2059.40 | 03-DEC-14:00 | 2059.40 | 03-DEC-14:00 | 76.51 | 16-DEC-14:30 | 524.03 | 03-DEC-14:00 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.569025E+11 | 0.154128E+11 | 6753.08 | 0.463022E+11 | 0.106003E+11 | 0.00 | ||||||||||||||
| Minimum of Months | 0.406419E+09 | 0.105390E+09 | 171.11 | 0.403369E+09 | 3049988.52 | 0.00 | 0.24 | 0.00 | 1703.93 | 1703.93 | 70.33 | 434.48 | 0.00 | |||||||
| Maximum of Months | 0.871612E+10 | 0.234942E+10 | 744.00 | 0.672646E+10 | 0.258983E+10 | 0.00 | 0.77 | 0.16 | 5445.14 | 5117.29 | 1740.75 | 1637.32 | 0.00 |
Report: DXReportMonthly
For: SPLIT TNE COOLING COIL
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 18873467.15 | 4936631.59 | 24.30 | 18561450.52 | 312016.63 | 0.00 | 0.07 | 26-JAN-14:00 | 0.00 | 01-JAN-00:10 | 475.33 | 26-JAN-14:00 | 475.33 | 26-JAN-14:00 | 20.59 | 14-JAN-16:10 | 124.09 | 26-JAN-14:00 | 0.00 | 01-JAN-00:10 |
| February | 0.459556E+09 | 0.119533E+09 | 217.55 | 0.440901E+09 | 18655448.37 | 0.00 | 0.22 | 23-FEB-14:00 | 0.00 | 01-FEB-00:10 | 1552.65 | 24-FEB-16:10 | 1537.62 | 23-FEB-14:00 | 212.99 | 25-FEB-17:10 | 409.35 | 22-FEB-15:10 | 0.00 | 01-FEB-00:10 |
| March | 0.237978E+10 | 0.630466E+09 | 534.32 | 0.223232E+10 | 0.147453E+09 | 0.00 | 0.43 | 28-MAR-16:01 | 0.00 | 01-MAR-00:10 | 3020.84 | 29-MAR-15:10 | 2948.43 | 29-MAR-16:05 | 392.07 | 10-MAR-20:50 | 866.26 | 28-MAR-16:01 | 0.00 | 01-MAR-00:10 |
| April | 0.510031E+10 | 0.142603E+10 | 709.24 | 0.479183E+10 | 0.308475E+09 | 0.00 | 0.65 | 15-APR-15:10 | 0.00 | 05-APR-05:50 | 4377.56 | 15-APR-15:10 | 4377.56 | 15-APR-15:10 | 569.93 | 18-APR-14:10 | 1343.79 | 15-APR-15:10 | 0.00 | 01-APR-00:10 |
| May | 0.760934E+10 | 0.217371E+10 | 744.00 | 0.662737E+10 | 0.981973E+09 | 0.00 | 0.74 | 05-MAY-15:10 | 0.11 | 13-MAY-04:00 | 4852.50 | 05-MAY-15:10 | 4852.50 | 05-MAY-15:10 | 1137.66 | 24-MAY-14:20 | 1541.76 | 05-MAY-15:10 | 0.00 | 01-MAY-00:10 |
| June | 0.801190E+10 | 0.227415E+10 | 720.00 | 0.646221E+10 | 0.154969E+10 | 0.00 | 0.76 | 06-JUN-15:10 | 0.14 | 18-JUN-05:00 | 5327.10 | 23-JUN-14:10 | 5040.56 | 06-JUN-15:10 | 1463.15 | 23-JUN-13:40 | 1615.42 | 06-JUN-15:10 | 0.00 | 01-JUN-00:10 |
| July | 0.871100E+10 | 0.234798E+10 | 744.00 | 0.612095E+10 | 0.259005E+10 | 0.00 | 0.69 | 01-JUL-12:50 | 0.14 | 19-JUL-03:00 | 5293.92 | 01-JUL-13:00 | 4157.94 | 07-JUL-14:10 | 1748.98 | 19-JUL-11:50 | 1517.46 | 01-JUL-13:00 | 0.00 | 01-JUL-00:10 |
| August | 0.786817E+10 | 0.206795E+10 | 744.00 | 0.534738E+10 | 0.252079E+10 | 0.00 | 0.64 | 07-AUG-16:10 | 0.16 | 24-AUG-04:00 | 4791.56 | 07-AUG-16:10 | 3787.58 | 07-AUG-16:04 | 1621.67 | 12-AUG-09:40 | 1371.91 | 07-AUG-16:10 | 0.00 | 01-AUG-00:10 |
| September | 0.616660E+10 | 0.161358E+10 | 720.00 | 0.436098E+10 | 0.180562E+10 | 0.00 | 0.55 | 22-SEP-15:10 | 0.10 | 27-SEP-05:00 | 4191.71 | 22-SEP-15:10 | 3297.23 | 22-SEP-15:10 | 1156.10 | 05-SEP-17:20 | 1170.34 | 22-SEP-15:10 | 0.00 | 01-SEP-00:10 |
| October | 0.348183E+10 | 0.927874E+09 | 668.26 | 0.302383E+10 | 0.458000E+09 | 0.00 | 0.50 | 03-OCT-15:10 | 0.00 | 09-OCT-04:40 | 3666.96 | 03-OCT-15:10 | 3264.93 | 03-OCT-14:10 | 630.44 | 13-OCT-10:20 | 1051.10 | 03-OCT-14:20 | 0.00 | 01-OCT-00:10 |
| November | 0.108197E+10 | 0.285843E+09 | 349.96 | 0.102653E+10 | 55435783.51 | 0.00 | 0.27 | 09-NOV-13:50 | 0.00 | 01-NOV-00:10 | 1955.98 | 09-NOV-13:40 | 1860.79 | 09-NOV-14:00 | 271.23 | 09-NOV-10:10 | 532.66 | 09-NOV-13:40 | 0.00 | 01-NOV-00:10 |
| December | 68964274.24 | 18041033.67 | 73.67 | 68082015.59 | 882258.65 | 0.00 | 0.08 | 28-DEC-15:10 | 0.00 | 01-DEC-00:10 | 548.46 | 28-DEC-15:10 | 548.46 | 28-DEC-15:10 | 26.31 | 16-DEC-16:10 | 143.72 | 28-DEC-15:10 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.509583E+11 | 0.138901E+11 | 6249.30 | 0.405209E+11 | 0.104373E+11 | 0.00 | ||||||||||||||
| Minimum of Months | 18873467.15 | 4936631.59 | 24.30 | 18561450.52 | 312016.63 | 0.00 | 0.07 | 0.00 | 475.33 | 475.33 | 20.59 | 124.09 | 0.00 | |||||||
| Maximum of Months | 0.871100E+10 | 0.234798E+10 | 744.00 | 0.662737E+10 | 0.259005E+10 | 0.00 | 0.76 | 0.16 | 5327.10 | 5040.56 | 1748.98 | 1615.42 | 0.00 |
Report: DXReportMonthly
For: SPLIT TN1 COOLING COIL
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 12736446.59 | 3330262.64 | 19.53 | 12460760.08 | 275686.52 | 0.00 | 0.05 | 26-JAN-14:00 | 0.00 | 01-JAN-00:10 | 321.01 | 26-JAN-14:00 | 321.01 | 26-JAN-14:00 | 19.13 | 14-JAN-16:10 | 83.99 | 26-JAN-14:00 | 0.00 | 01-JAN-00:10 |
| February | 0.362838E+09 | 94377650.62 | 207.97 | 0.345472E+09 | 17366406.54 | 0.00 | 0.20 | 24-FEB-16:10 | 0.00 | 01-FEB-00:10 | 1295.34 | 24-FEB-16:10 | 1226.14 | 22-FEB-16:10 | 212.31 | 25-FEB-17:10 | 339.01 | 24-FEB-16:10 | 0.00 | 01-FEB-00:10 |
| March | 0.197391E+10 | 0.523591E+09 | 556.71 | 0.183971E+10 | 0.134196E+09 | 0.00 | 0.40 | 28-MAR-16:06 | 0.00 | 01-MAR-00:10 | 2470.72 | 29-MAR-16:03 | 2468.15 | 28-MAR-16:06 | 350.67 | 10-MAR-21:00 | 729.84 | 28-MAR-16:06 | 0.00 | 01-MAR-00:10 |
| April | 0.415847E+10 | 0.116676E+10 | 714.50 | 0.388167E+10 | 0.276796E+09 | 0.00 | 0.57 | 27-APR-16:10 | 0.00 | 10-APR-04:00 | 3421.62 | 18-APR-15:10 | 3416.47 | 27-APR-16:01 | 455.22 | 18-APR-14:10 | 1061.86 | 15-APR-15:10 | 0.00 | 01-APR-00:10 |
| May | 0.625179E+10 | 0.179308E+10 | 744.00 | 0.539115E+10 | 0.860634E+09 | 0.00 | 0.67 | 05-MAY-16:10 | 0.12 | 13-MAY-04:00 | 3899.75 | 25-MAY-16:17 | 3852.48 | 05-MAY-16:01 | 904.88 | 24-MAY-14:20 | 1235.28 | 05-MAY-16:03 | 0.00 | 01-MAY-00:10 |
| June | 0.677417E+10 | 0.192690E+10 | 720.00 | 0.538406E+10 | 0.139011E+10 | 0.00 | 0.68 | 06-JUN-16:10 | 0.16 | 18-JUN-05:00 | 4312.66 | 22-JUN-16:30 | 3975.23 | 06-JUN-15:10 | 1193.98 | 23-JUN-14:10 | 1291.94 | 06-JUN-15:10 | 0.00 | 01-JUN-00:10 |
| July | 0.741149E+10 | 0.200249E+10 | 744.00 | 0.515320E+10 | 0.225829E+10 | 0.00 | 0.64 | 02-JUL-17:10 | 0.15 | 19-JUL-03:00 | 4397.30 | 01-JUL-16:13 | 3446.05 | 02-JUL-17:06 | 1338.63 | 17-JUL-17:10 | 1256.03 | 01-JUL-16:13 | 0.00 | 01-JUL-00:10 |
| August | 0.680218E+10 | 0.178889E+10 | 744.00 | 0.455943E+10 | 0.224275E+10 | 0.00 | 0.59 | 07-AUG-16:10 | 0.18 | 24-AUG-04:00 | 3951.51 | 07-AUG-16:10 | 3100.67 | 07-AUG-16:06 | 1359.88 | 12-AUG-09:40 | 1139.67 | 07-AUG-16:10 | 0.00 | 01-AUG-00:10 |
| September | 0.536794E+10 | 0.140311E+10 | 720.00 | 0.373227E+10 | 0.163567E+10 | 0.00 | 0.51 | 14-SEP-16:10 | 0.11 | 27-SEP-05:00 | 3557.87 | 14-SEP-16:10 | 2648.22 | 22-SEP-15:10 | 1004.53 | 14-SEP-17:20 | 977.43 | 14-SEP-16:10 | 0.00 | 01-SEP-00:10 |
| October | 0.298303E+10 | 0.793743E+09 | 688.93 | 0.255298E+10 | 0.430058E+09 | 0.00 | 0.45 | 03-OCT-15:10 | 0.00 | 09-OCT-05:05 | 2931.38 | 03-OCT-15:10 | 2595.80 | 03-OCT-15:10 | 551.37 | 06-OCT-11:20 | 846.88 | 03-OCT-15:10 | 0.00 | 01-OCT-00:10 |
| November | 0.899148E+09 | 0.237535E+09 | 360.79 | 0.847165E+09 | 51983191.79 | 0.00 | 0.25 | 09-NOV-14:00 | 0.00 | 01-NOV-00:40 | 1607.03 | 09-NOV-14:00 | 1516.47 | 09-NOV-14:20 | 203.89 | 09-NOV-10:50 | 439.15 | 09-NOV-14:00 | 0.00 | 01-NOV-00:10 |
| December | 41707553.44 | 10916713.70 | 56.11 | 41116186.25 | 591367.19 | 0.00 | 0.07 | 28-DEC-16:10 | 0.00 | 01-DEC-00:10 | 458.43 | 28-DEC-16:10 | 458.43 | 28-DEC-16:10 | 22.02 | 16-DEC-17:10 | 119.25 | 28-DEC-16:10 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.430394E+11 | 0.117447E+11 | 6276.54 | 0.337407E+11 | 0.929872E+10 | 0.00 | ||||||||||||||
| Minimum of Months | 12736446.59 | 3330262.64 | 19.53 | 12460760.08 | 275686.52 | 0.00 | 0.05 | 0.00 | 321.01 | 321.01 | 19.13 | 83.99 | 0.00 | |||||||
| Maximum of Months | 0.741149E+10 | 0.200249E+10 | 744.00 | 0.539115E+10 | 0.225829E+10 | 0.00 | 0.68 | 0.18 | 4397.30 | 3975.23 | 1359.88 | 1291.94 | 0.00 |
Report: DXReportMonthly
For: SPLIT TN2 COOLING COIL
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 12972401.11 | 3391812.26 | 19.90 | 12692651.39 | 279749.72 | 0.00 | 0.05 | 26-JAN-14:00 | 0.00 | 01-JAN-00:10 | 329.95 | 26-JAN-14:00 | 329.95 | 26-JAN-14:00 | 19.17 | 14-JAN-16:10 | 86.31 | 26-JAN-14:00 | 0.00 | 01-JAN-00:10 |
| February | 0.366651E+09 | 95365634.01 | 209.38 | 0.349179E+09 | 17471799.01 | 0.00 | 0.20 | 24-FEB-16:10 | 0.00 | 01-FEB-00:10 | 1297.92 | 24-FEB-16:10 | 1226.29 | 22-FEB-16:10 | 210.49 | 25-FEB-17:10 | 339.66 | 24-FEB-16:10 | 0.00 | 01-FEB-00:10 |
| March | 0.197787E+10 | 0.524604E+09 | 556.04 | 0.184347E+10 | 0.134408E+09 | 0.00 | 0.40 | 28-MAR-16:06 | 0.00 | 01-MAR-00:10 | 2461.70 | 29-MAR-16:03 | 2458.84 | 28-MAR-16:06 | 350.64 | 10-MAR-21:00 | 727.18 | 28-MAR-16:06 | 0.00 | 01-MAR-00:10 |
| April | 0.416048E+10 | 0.116721E+10 | 714.50 | 0.388345E+10 | 0.277022E+09 | 0.00 | 0.57 | 15-APR-15:10 | 0.00 | 10-APR-04:00 | 3418.83 | 18-APR-15:10 | 3413.39 | 15-APR-15:10 | 454.88 | 18-APR-14:10 | 1061.23 | 15-APR-15:10 | 0.00 | 01-APR-00:10 |
| May | 0.625358E+10 | 0.179340E+10 | 744.00 | 0.539273E+10 | 0.860845E+09 | 0.00 | 0.67 | 05-MAY-16:10 | 0.12 | 13-MAY-04:00 | 3888.22 | 25-MAY-16:17 | 3842.01 | 05-MAY-16:03 | 904.48 | 24-MAY-14:20 | 1232.06 | 05-MAY-16:03 | 0.00 | 01-MAY-00:10 |
| June | 0.677233E+10 | 0.192619E+10 | 720.00 | 0.538223E+10 | 0.139010E+10 | 0.00 | 0.68 | 06-JUN-15:10 | 0.16 | 18-JUN-05:00 | 4300.33 | 22-JUN-16:30 | 3971.50 | 06-JUN-15:10 | 1193.59 | 23-JUN-14:10 | 1290.64 | 06-JUN-15:10 | 0.00 | 01-JUN-00:10 |
| July | 0.741186E+10 | 0.200238E+10 | 744.00 | 0.515344E+10 | 0.225842E+10 | 0.00 | 0.64 | 02-JUL-17:10 | 0.15 | 19-JUL-03:00 | 4390.42 | 01-JUL-16:13 | 3432.00 | 02-JUL-17:07 | 1337.86 | 19-JUL-12:00 | 1254.20 | 01-JUL-16:01 | 0.00 | 01-JUL-00:10 |
| August | 0.680266E+10 | 0.178884E+10 | 744.00 | 0.455975E+10 | 0.224291E+10 | 0.00 | 0.59 | 07-AUG-16:10 | 0.18 | 24-AUG-04:00 | 3944.75 | 07-AUG-16:10 | 3094.68 | 07-AUG-16:07 | 1360.29 | 12-AUG-09:40 | 1137.72 | 07-AUG-16:10 | 0.00 | 01-AUG-00:10 |
| September | 0.536772E+10 | 0.140295E+10 | 720.00 | 0.373198E+10 | 0.163574E+10 | 0.00 | 0.51 | 14-SEP-16:10 | 0.11 | 27-SEP-05:00 | 3549.01 | 14-SEP-16:10 | 2645.10 | 22-SEP-15:10 | 1003.52 | 14-SEP-17:20 | 975.04 | 14-SEP-16:10 | 0.00 | 01-SEP-00:10 |
| October | 0.298529E+10 | 0.794312E+09 | 688.64 | 0.255504E+10 | 0.430246E+09 | 0.00 | 0.45 | 03-OCT-15:10 | 0.00 | 09-OCT-05:05 | 2927.73 | 03-OCT-15:10 | 2592.75 | 03-OCT-15:10 | 552.48 | 06-OCT-11:20 | 845.81 | 03-OCT-15:10 | 0.00 | 01-OCT-00:10 |
| November | 0.902704E+09 | 0.238467E+09 | 360.46 | 0.850591E+09 | 52112916.09 | 0.00 | 0.25 | 09-NOV-14:00 | 0.00 | 01-NOV-00:40 | 1610.60 | 09-NOV-14:00 | 1519.76 | 09-NOV-14:00 | 205.98 | 09-NOV-10:50 | 440.08 | 09-NOV-14:00 | 0.00 | 01-NOV-00:10 |
| December | 42805703.05 | 11204451.21 | 57.44 | 42206305.48 | 599397.57 | 0.00 | 0.07 | 28-DEC-16:10 | 0.00 | 01-DEC-00:10 | 455.41 | 28-DEC-16:10 | 455.41 | 28-DEC-16:10 | 21.79 | 16-DEC-17:10 | 118.47 | 28-DEC-16:10 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.430569E+11 | 0.117483E+11 | 6278.36 | 0.337568E+11 | 0.930015E+10 | 0.00 | ||||||||||||||
| Minimum of Months | 12972401.11 | 3391812.26 | 19.90 | 12692651.39 | 279749.72 | 0.00 | 0.05 | 0.00 | 329.95 | 329.95 | 19.17 | 86.31 | 0.00 | |||||||
| Maximum of Months | 0.741186E+10 | 0.200238E+10 | 744.00 | 0.539273E+10 | 0.225842E+10 | 0.00 | 0.68 | 0.18 | 4390.42 | 3971.50 | 1360.29 | 1290.64 | 0.00 |
Report: DXReportMonthly
For: SPLIT TS1 COOLING COIL
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.402622E+09 | 0.104338E+09 | 192.83 | 0.399304E+09 | 3318018.09 | 0.00 | 0.25 | 12-JAN-14:50 | 0.00 | 01-JAN-00:10 | 1611.82 | 12-JAN-14:50 | 1611.82 | 12-JAN-14:50 | 65.86 | 13-JAN-14:30 | 410.19 | 12-JAN-14:50 | 0.00 | 01-JAN-00:10 |
| February | 0.108779E+10 | 0.278659E+09 | 314.42 | 0.105321E+10 | 34577103.26 | 0.00 | 0.38 | 20-FEB-14:40 | 0.00 | 01-FEB-00:10 | 2442.54 | 20-FEB-14:40 | 2442.54 | 20-FEB-14:40 | 326.24 | 25-FEB-17:10 | 633.91 | 20-FEB-14:40 | 0.00 | 01-FEB-00:10 |
| March | 0.276104E+10 | 0.724474E+09 | 590.46 | 0.260608E+10 | 0.154967E+09 | 0.00 | 0.51 | 28-MAR-15:10 | 0.00 | 01-MAR-00:10 | 3232.65 | 12-MAR-16:10 | 3164.90 | 28-MAR-15:10 | 367.99 | 10-MAR-21:00 | 923.08 | 28-MAR-15:10 | 0.00 | 01-MAR-00:10 |
| April | 0.466766E+10 | 0.130304E+10 | 715.58 | 0.438189E+10 | 0.285767E+09 | 0.00 | 0.65 | 15-APR-15:10 | 0.00 | 10-APR-04:50 | 3944.37 | 15-APR-15:10 | 3944.37 | 15-APR-15:10 | 461.05 | 18-APR-14:10 | 1210.49 | 15-APR-15:10 | 0.00 | 01-APR-00:10 |
| May | 0.635065E+10 | 0.182104E+10 | 744.00 | 0.549101E+10 | 0.859634E+09 | 0.00 | 0.69 | 05-MAY-15:10 | 0.12 | 13-MAY-04:00 | 4006.77 | 05-MAY-15:10 | 4006.77 | 05-MAY-15:10 | 899.16 | 24-MAY-14:20 | 1284.77 | 05-MAY-15:10 | 0.00 | 01-MAY-00:10 |
| June | 0.675167E+10 | 0.192112E+10 | 720.00 | 0.536616E+10 | 0.138551E+10 | 0.00 | 0.69 | 06-JUN-15:10 | 0.16 | 18-JUN-05:00 | 4285.09 | 23-JUN-14:10 | 4049.82 | 06-JUN-15:10 | 1185.59 | 23-JUN-13:00 | 1313.91 | 06-JUN-15:10 | 0.00 | 01-JUN-00:10 |
| July | 0.741696E+10 | 0.200417E+10 | 744.00 | 0.515859E+10 | 0.225837E+10 | 0.00 | 0.65 | 01-JUL-16:01 | 0.15 | 19-JUL-03:00 | 4530.33 | 01-JUL-16:01 | 3513.65 | 02-JUL-16:15 | 1330.51 | 19-JUL-12:00 | 1291.20 | 01-JUL-16:01 | 0.00 | 01-JUL-00:10 |
| August | 0.690838E+10 | 0.181661E+10 | 744.00 | 0.465873E+10 | 0.224966E+10 | 0.00 | 0.60 | 13-AUG-16:02 | 0.18 | 24-AUG-04:00 | 4194.70 | 13-AUG-16:02 | 3207.14 | 07-AUG-15:10 | 1419.18 | 12-AUG-09:50 | 1163.14 | 07-AUG-15:10 | 0.00 | 01-AUG-00:10 |
| September | 0.583559E+10 | 0.152424E+10 | 720.00 | 0.416123E+10 | 0.167436E+10 | 0.00 | 0.60 | 24-SEP-14:00 | 0.12 | 27-SEP-05:00 | 4095.38 | 22-SEP-15:10 | 3422.98 | 27-SEP-14:20 | 1001.05 | 14-SEP-17:20 | 1140.77 | 24-SEP-14:00 | 0.00 | 01-SEP-00:10 |
| October | 0.409003E+10 | 0.107877E+10 | 706.58 | 0.360663E+10 | 0.483399E+09 | 0.00 | 0.59 | 03-OCT-14:10 | 0.00 | 21-OCT-05:00 | 3896.10 | 03-OCT-14:10 | 3580.76 | 03-OCT-14:10 | 627.36 | 13-OCT-11:00 | 1112.56 | 03-OCT-14:10 | 0.00 | 01-OCT-00:10 |
| November | 0.216867E+10 | 0.559779E+09 | 452.00 | 0.207937E+10 | 89307324.28 | 0.00 | 0.46 | 04-NOV-14:00 | 0.00 | 01-NOV-02:00 | 3027.98 | 09-NOV-13:40 | 3022.88 | 04-NOV-14:10 | 309.26 | 09-NOV-10:10 | 815.63 | 04-NOV-14:00 | 0.00 | 01-NOV-00:10 |
| December | 0.655284E+09 | 0.168499E+09 | 266.00 | 0.646953E+09 | 8330618.32 | 0.00 | 0.30 | 02-DEC-14:20 | 0.00 | 01-DEC-00:10 | 1925.19 | 02-DEC-14:20 | 1925.19 | 02-DEC-14:20 | 77.02 | 16-DEC-17:10 | 488.47 | 02-DEC-14:20 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.490963E+11 | 0.133047E+11 | 6909.87 | 0.396091E+11 | 0.948720E+10 | 0.00 | ||||||||||||||
| Minimum of Months | 0.402622E+09 | 0.104338E+09 | 192.83 | 0.399304E+09 | 3318018.09 | 0.00 | 0.25 | 0.00 | 1611.82 | 1611.82 | 65.86 | 410.19 | 0.00 | |||||||
| Maximum of Months | 0.741696E+10 | 0.200417E+10 | 744.00 | 0.549101E+10 | 0.225837E+10 | 0.00 | 0.69 | 0.18 | 4530.33 | 4049.82 | 1419.18 | 1313.91 | 0.00 |
Report: DXReportMonthly
For: SPLIT TS2 COOLING COIL
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.405897E+09 | 0.105173E+09 | 193.00 | 0.402565E+09 | 3331986.19 | 0.00 | 0.25 | 12-JAN-14:50 | 0.00 | 01-JAN-00:10 | 1617.20 | 12-JAN-14:50 | 1617.20 | 12-JAN-14:50 | 66.21 | 13-JAN-14:30 | 411.48 | 12-JAN-14:50 | 0.00 | 01-JAN-00:10 |
| February | 0.109285E+10 | 0.279915E+09 | 315.08 | 0.105818E+10 | 34672511.18 | 0.00 | 0.38 | 20-FEB-14:40 | 0.00 | 01-FEB-00:10 | 2449.19 | 20-FEB-14:40 | 2449.19 | 20-FEB-14:40 | 324.44 | 25-FEB-17:10 | 635.48 | 20-FEB-14:40 | 0.00 | 01-FEB-00:10 |
| March | 0.276457E+10 | 0.725309E+09 | 589.96 | 0.260945E+10 | 0.155124E+09 | 0.00 | 0.51 | 28-MAR-15:10 | 0.00 | 01-MAR-00:10 | 3224.84 | 12-MAR-16:10 | 3163.20 | 28-MAR-15:10 | 367.95 | 10-MAR-21:00 | 922.51 | 28-MAR-15:10 | 0.00 | 01-MAR-00:10 |
| April | 0.466962E+10 | 0.130344E+10 | 715.58 | 0.438364E+10 | 0.285976E+09 | 0.00 | 0.65 | 15-APR-14:10 | 0.00 | 10-APR-04:50 | 3942.26 | 15-APR-15:10 | 3942.26 | 15-APR-15:10 | 460.74 | 18-APR-14:10 | 1209.71 | 15-APR-15:10 | 0.00 | 01-APR-00:10 |
| May | 0.635248E+10 | 0.182137E+10 | 744.00 | 0.549262E+10 | 0.859859E+09 | 0.00 | 0.69 | 05-MAY-15:10 | 0.12 | 13-MAY-04:00 | 4003.99 | 05-MAY-15:10 | 4003.99 | 05-MAY-15:10 | 898.76 | 24-MAY-14:20 | 1283.75 | 05-MAY-15:10 | 0.00 | 01-MAY-00:10 |
| June | 0.674984E+10 | 0.192042E+10 | 720.00 | 0.536434E+10 | 0.138551E+10 | 0.00 | 0.69 | 06-JUN-15:10 | 0.16 | 18-JUN-05:00 | 4286.01 | 23-JUN-14:10 | 4046.09 | 06-JUN-15:10 | 1185.68 | 23-JUN-13:00 | 1312.60 | 06-JUN-15:10 | 0.00 | 01-JUN-00:10 |
| July | 0.741734E+10 | 0.200407E+10 | 744.00 | 0.515883E+10 | 0.225852E+10 | 0.00 | 0.65 | 01-JUL-16:01 | 0.15 | 19-JUL-03:00 | 4524.16 | 01-JUL-16:01 | 3502.72 | 02-JUL-16:15 | 1331.50 | 19-JUL-12:00 | 1289.41 | 01-JUL-16:01 | 0.00 | 01-JUL-00:10 |
| August | 0.690887E+10 | 0.181656E+10 | 744.00 | 0.465905E+10 | 0.224982E+10 | 0.00 | 0.60 | 07-AUG-15:10 | 0.18 | 24-AUG-04:00 | 4184.98 | 13-AUG-16:02 | 3205.44 | 07-AUG-15:10 | 1419.61 | 12-AUG-09:50 | 1162.31 | 07-AUG-15:10 | 0.00 | 01-AUG-00:10 |
| September | 0.583534E+10 | 0.152404E+10 | 720.00 | 0.416092E+10 | 0.167441E+10 | 0.00 | 0.60 | 24-SEP-14:00 | 0.12 | 27-SEP-05:00 | 4091.08 | 22-SEP-14:20 | 3425.66 | 27-SEP-14:10 | 1000.12 | 14-SEP-17:20 | 1141.08 | 24-SEP-14:00 | 0.00 | 01-SEP-00:10 |
| October | 0.409194E+10 | 0.107917E+10 | 706.75 | 0.360842E+10 | 0.483522E+09 | 0.00 | 0.60 | 03-OCT-14:10 | 0.00 | 21-OCT-05:00 | 3899.58 | 03-OCT-14:10 | 3584.47 | 03-OCT-14:10 | 628.52 | 13-OCT-11:00 | 1113.31 | 03-OCT-14:10 | 0.00 | 01-OCT-00:10 |
| November | 0.217146E+10 | 0.560424E+09 | 452.00 | 0.208208E+10 | 89375859.56 | 0.00 | 0.46 | 04-NOV-14:00 | 0.00 | 01-NOV-02:00 | 3033.27 | 09-NOV-13:40 | 3026.27 | 04-NOV-14:00 | 311.06 | 09-NOV-10:10 | 816.58 | 04-NOV-14:00 | 0.00 | 01-NOV-00:10 |
| December | 0.659070E+09 | 0.169455E+09 | 266.67 | 0.650740E+09 | 8329883.42 | 0.00 | 0.30 | 02-DEC-14:20 | 0.00 | 01-DEC-00:10 | 1930.23 | 02-DEC-14:20 | 1930.23 | 02-DEC-14:20 | 76.71 | 16-DEC-17:10 | 489.65 | 02-DEC-14:20 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.491193E+11 | 0.133093E+11 | 6911.04 | 0.396308E+11 | 0.948845E+10 | 0.00 | ||||||||||||||
| Minimum of Months | 0.405897E+09 | 0.105173E+09 | 193.00 | 0.402565E+09 | 3331986.19 | 0.00 | 0.25 | 0.00 | 1617.20 | 1617.20 | 66.21 | 411.48 | 0.00 | |||||||
| Maximum of Months | 0.741734E+10 | 0.200407E+10 | 744.00 | 0.549262E+10 | 0.225852E+10 | 0.00 | 0.69 | 0.18 | 4524.16 | 4046.09 | 1419.61 | 1312.60 | 0.00 |
Report: WindowReportMonthly
For: GWINDOW1 S SWA
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 167.36 | 101.30 | 66.07 | 234.58 | 137.69 | 0.00 | 0.00 | 0.00 |
| February | 161.53 | 90.35 | 71.18 | 247.96 | 106.84 | 0.00 | 0.00 | 0.00 |
| March | 133.41 | 57.00 | 76.41 | 240.85 | 61.12 | 0.00 | 0.00 | 0.00 |
| April | 99.06 | 30.02 | 69.04 | 240.23 | 17.92 | 0.00 | 0.00 | 0.00 |
| May | 69.44 | 5.39 | 64.05 | 223.65 | 1.65 | 0.00 | 0.00 | 0.00 |
| June | 63.46 | 1.29 | 62.17 | 219.86 | 1.65 | 0.00 | 0.00 | 0.00 |
| July | 65.80 | 0.73 | 65.07 | 204.69 | 0.25 | 0.00 | 0.00 | 0.00 |
| August | 69.14 | 2.90 | 66.24 | 187.16 | 1.00 | 0.00 | 0.00 | 0.00 |
| September | 96.94 | 27.47 | 69.48 | 214.45 | 5.78 | 0.00 | 0.00 | 0.00 |
| October | 160.12 | 88.84 | 71.28 | 305.22 | 47.66 | 0.00 | 0.00 | 0.00 |
| November | 202.35 | 134.00 | 68.35 | 335.32 | 97.47 | 0.00 | 0.00 | 0.00 |
| December | 179.44 | 112.28 | 67.15 | 259.86 | 137.61 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 122.09 | 54.07 | 68.02 | 242.67 | 51.16 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 63.46 | 0.73 | 62.17 | 187.16 | 0.25 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 202.35 | 134.00 | 76.41 | 335.32 | 137.69 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: GWINDOW1 W SWA
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 51.04 | 19.84 | 31.19 | 57.97 | 98.63 | 0.00 | 0.00 | 0.00 |
| February | 58.30 | 21.45 | 36.85 | 79.71 | 74.39 | 0.00 | 0.00 | 0.00 |
| March | 75.99 | 30.54 | 45.46 | 129.10 | 40.81 | 0.00 | 0.00 | 0.00 |
| April | 91.85 | 42.99 | 48.86 | 195.67 | 11.55 | 0.00 | 0.00 | 0.00 |
| May | 87.00 | 36.85 | 50.16 | 219.26 | 1.11 | 0.00 | 0.00 | 0.00 |
| June | 82.07 | 32.04 | 50.03 | 218.24 | 1.06 | 0.00 | 0.00 | 0.00 |
| July | 60.68 | 11.77 | 48.91 | 165.32 | 0.18 | 0.00 | 0.00 | 0.00 |
| August | 55.64 | 9.77 | 45.87 | 140.17 | 0.67 | 0.00 | 0.00 | 0.00 |
| September | 61.46 | 18.18 | 43.27 | 131.97 | 3.76 | 0.00 | 0.00 | 0.00 |
| October | 63.79 | 25.38 | 38.41 | 121.75 | 31.97 | 0.00 | 0.00 | 0.00 |
| November | 57.70 | 24.58 | 33.12 | 89.88 | 67.39 | 0.00 | 0.00 | 0.00 |
| December | 49.44 | 18.88 | 30.56 | 57.29 | 97.25 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 66.23 | 24.32 | 41.91 | 134.03 | 35.58 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 49.44 | 9.77 | 30.56 | 57.29 | 0.18 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 91.85 | 42.99 | 50.16 | 219.26 | 98.63 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: GWINDOW1 W NWA
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 51.04 | 19.84 | 31.19 | 62.52 | 90.47 | 0.00 | 0.00 | 0.00 |
| February | 58.30 | 21.45 | 36.85 | 82.92 | 69.78 | 0.00 | 0.00 | 0.00 |
| March | 75.99 | 30.54 | 45.46 | 130.88 | 39.44 | 0.00 | 0.00 | 0.00 |
| April | 91.85 | 42.99 | 48.86 | 196.83 | 11.20 | 0.00 | 0.00 | 0.00 |
| May | 87.00 | 36.85 | 50.16 | 219.50 | 1.11 | 0.00 | 0.00 | 0.00 |
| June | 82.07 | 32.04 | 50.03 | 218.17 | 1.06 | 0.00 | 0.00 | 0.00 |
| July | 60.68 | 11.77 | 48.91 | 165.29 | 0.18 | 0.00 | 0.00 | 0.00 |
| August | 55.64 | 9.77 | 45.87 | 140.40 | 0.67 | 0.00 | 0.00 | 0.00 |
| September | 61.46 | 18.18 | 43.27 | 132.89 | 3.55 | 0.00 | 0.00 | 0.00 |
| October | 63.79 | 25.38 | 38.41 | 123.59 | 30.84 | 0.00 | 0.00 | 0.00 |
| November | 57.70 | 24.58 | 33.12 | 92.26 | 65.20 | 0.00 | 0.00 | 0.00 |
| December | 49.44 | 18.88 | 30.56 | 60.37 | 92.29 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 66.23 | 24.32 | 41.91 | 135.63 | 33.67 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 49.44 | 9.77 | 30.56 | 60.37 | 0.18 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 91.85 | 42.99 | 50.16 | 219.50 | 92.29 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: GWINDOW1 N NWA
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 37.02 | 0.00 | 37.02 | 23.88 | 141.13 | 0.00 | 0.00 | 0.00 |
| February | 43.90 | 0.00 | 43.90 | 45.13 | 107.46 | 0.00 | 0.00 | 0.00 |
| March | 52.91 | 0.01 | 52.91 | 85.15 | 60.28 | 0.00 | 0.00 | 0.00 |
| April | 57.54 | 0.29 | 57.25 | 149.37 | 16.84 | 0.00 | 0.00 | 0.00 |
| May | 63.80 | 1.97 | 61.82 | 208.98 | 1.68 | 0.00 | 0.00 | 0.00 |
| June | 65.66 | 2.28 | 63.38 | 223.75 | 1.64 | 0.00 | 0.00 | 0.00 |
| July | 65.03 | 1.12 | 63.91 | 202.24 | 0.25 | 0.00 | 0.00 | 0.00 |
| August | 59.80 | 0.33 | 59.47 | 167.76 | 0.98 | 0.00 | 0.00 | 0.00 |
| September | 53.11 | 0.01 | 53.10 | 128.22 | 5.40 | 0.00 | 0.00 | 0.00 |
| October | 46.01 | 0.00 | 46.01 | 92.17 | 47.10 | 0.00 | 0.00 | 0.00 |
| November | 38.97 | 0.00 | 38.97 | 48.85 | 100.15 | 0.00 | 0.00 | 0.00 |
| December | 36.11 | 0.00 | 36.11 | 23.44 | 144.80 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 51.69 | 0.50 | 51.19 | 116.93 | 52.09 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 36.11 | 0.00 | 36.11 | 23.44 | 0.25 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 65.66 | 2.28 | 63.91 | 223.75 | 144.80 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: GWINDOW1 S SEA
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 167.36 | 101.30 | 66.07 | 231.53 | 146.44 | 0.00 | 0.00 | 0.00 |
| February | 161.53 | 90.35 | 71.18 | 241.95 | 120.68 | 0.00 | 0.00 | 0.00 |
| March | 133.41 | 57.00 | 76.41 | 231.10 | 80.07 | 0.00 | 0.00 | 0.00 |
| April | 99.06 | 30.02 | 69.04 | 216.86 | 38.32 | 0.00 | 0.00 | 0.00 |
| May | 69.44 | 5.39 | 64.05 | 186.20 | 12.90 | 0.00 | 0.00 | 0.00 |
| June | 63.46 | 1.29 | 62.17 | 178.97 | 9.84 | 0.00 | 0.00 | 0.00 |
| July | 65.80 | 0.73 | 65.07 | 159.37 | 6.59 | 0.00 | 0.00 | 0.00 |
| August | 69.14 | 2.90 | 66.24 | 153.47 | 13.99 | 0.00 | 0.00 | 0.00 |
| September | 96.94 | 27.47 | 69.48 | 190.67 | 31.01 | 0.00 | 0.00 | 0.00 |
| October | 160.12 | 88.84 | 71.28 | 289.69 | 76.95 | 0.00 | 0.00 | 0.00 |
| November | 202.35 | 134.00 | 68.35 | 324.68 | 121.24 | 0.00 | 0.00 | 0.00 |
| December | 179.44 | 112.28 | 67.15 | 254.57 | 150.18 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 122.09 | 54.07 | 68.02 | 221.35 | 67.10 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 63.46 | 0.73 | 62.17 | 153.47 | 6.59 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 202.35 | 134.00 | 76.41 | 324.68 | 150.18 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: GWINDOW1 E SEA
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 52.34 | 21.11 | 31.23 | 51.58 | 97.46 | 0.00 | 0.00 | 0.00 |
| February | 63.35 | 26.08 | 37.27 | 79.48 | 78.13 | 0.00 | 0.00 | 0.00 |
| March | 77.36 | 31.89 | 45.47 | 122.30 | 50.10 | 0.00 | 0.00 | 0.00 |
| April | 92.32 | 43.12 | 49.19 | 179.48 | 23.78 | 0.00 | 0.00 | 0.00 |
| May | 90.57 | 40.16 | 50.41 | 200.30 | 8.21 | 0.00 | 0.00 | 0.00 |
| June | 73.68 | 24.44 | 49.24 | 175.99 | 6.40 | 0.00 | 0.00 | 0.00 |
| July | 61.85 | 12.99 | 48.86 | 138.27 | 4.27 | 0.00 | 0.00 | 0.00 |
| August | 55.78 | 9.66 | 46.12 | 117.96 | 9.10 | 0.00 | 0.00 | 0.00 |
| September | 59.49 | 16.49 | 43.00 | 111.94 | 19.75 | 0.00 | 0.00 | 0.00 |
| October | 65.29 | 26.40 | 38.89 | 112.25 | 49.36 | 0.00 | 0.00 | 0.00 |
| November | 57.74 | 24.73 | 33.01 | 78.68 | 78.74 | 0.00 | 0.00 | 0.00 |
| December | 50.34 | 19.92 | 30.41 | 51.55 | 100.92 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 66.66 | 24.71 | 41.95 | 118.44 | 43.70 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 50.34 | 9.66 | 30.41 | 51.55 | 4.27 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 92.32 | 43.12 | 50.41 | 200.30 | 100.92 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: GWINDOW1 E NEA
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 52.34 | 21.11 | 31.23 | 58.01 | 83.80 | 0.00 | 0.00 | 0.00 |
| February | 63.35 | 26.08 | 37.27 | 86.25 | 64.86 | 0.00 | 0.00 | 0.00 |
| March | 77.36 | 31.89 | 45.47 | 130.83 | 36.79 | 0.00 | 0.00 | 0.00 |
| April | 92.32 | 43.12 | 49.19 | 197.14 | 10.76 | 0.00 | 0.00 | 0.00 |
| May | 90.57 | 40.16 | 50.41 | 225.38 | 1.04 | 0.00 | 0.00 | 0.00 |
| June | 73.68 | 24.44 | 49.24 | 202.98 | 1.06 | 0.00 | 0.00 | 0.00 |
| July | 61.85 | 12.99 | 48.86 | 168.23 | 0.16 | 0.00 | 0.00 | 0.00 |
| August | 55.78 | 9.66 | 46.12 | 140.43 | 0.63 | 0.00 | 0.00 | 0.00 |
| September | 59.49 | 16.49 | 43.00 | 129.21 | 3.43 | 0.00 | 0.00 | 0.00 |
| October | 65.29 | 26.40 | 38.89 | 124.55 | 29.45 | 0.00 | 0.00 | 0.00 |
| November | 57.74 | 24.73 | 33.01 | 87.52 | 60.84 | 0.00 | 0.00 | 0.00 |
| December | 50.34 | 19.92 | 30.41 | 57.30 | 87.49 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 66.66 | 24.71 | 41.95 | 134.16 | 31.56 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 50.34 | 9.66 | 30.41 | 57.30 | 0.16 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 92.32 | 43.12 | 50.41 | 225.38 | 87.49 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: GWINDOW1 N NEA
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 37.02 | 0.00 | 37.02 | 23.29 | 140.99 | 0.00 | 0.00 | 0.00 |
| February | 43.90 | 0.00 | 43.90 | 44.35 | 107.70 | 0.00 | 0.00 | 0.00 |
| March | 52.91 | 0.01 | 52.91 | 84.68 | 60.11 | 0.00 | 0.00 | 0.00 |
| April | 57.54 | 0.29 | 57.25 | 149.12 | 16.72 | 0.00 | 0.00 | 0.00 |
| May | 63.80 | 1.97 | 61.82 | 208.80 | 1.65 | 0.00 | 0.00 | 0.00 |
| June | 65.66 | 2.28 | 63.38 | 223.97 | 1.62 | 0.00 | 0.00 | 0.00 |
| July | 65.03 | 1.12 | 63.91 | 202.21 | 0.25 | 0.00 | 0.00 | 0.00 |
| August | 59.80 | 0.33 | 59.47 | 167.74 | 0.98 | 0.00 | 0.00 | 0.00 |
| September | 53.11 | 0.01 | 53.10 | 128.21 | 5.33 | 0.00 | 0.00 | 0.00 |
| October | 46.01 | 0.00 | 46.01 | 91.91 | 46.95 | 0.00 | 0.00 | 0.00 |
| November | 38.97 | 0.00 | 38.97 | 48.52 | 99.95 | 0.00 | 0.00 | 0.00 |
| December | 36.11 | 0.00 | 36.11 | 22.89 | 144.81 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 51.69 | 0.50 | 51.19 | 116.67 | 52.03 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 36.11 | 0.00 | 36.11 | 22.89 | 0.25 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 65.66 | 2.28 | 63.91 | 223.97 | 144.81 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: GWINDOW1 N N1A
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 37.02 | 0.00 | 37.02 | 22.85 | 145.40 | 0.00 | 0.00 | 0.00 |
| February | 43.90 | 0.00 | 43.90 | 44.13 | 111.07 | 0.00 | 0.00 | 0.00 |
| March | 52.91 | 0.01 | 52.91 | 85.37 | 61.03 | 0.00 | 0.00 | 0.00 |
| April | 57.54 | 0.29 | 57.25 | 151.46 | 16.62 | 0.00 | 0.00 | 0.00 |
| May | 63.80 | 1.97 | 61.82 | 212.46 | 1.55 | 0.00 | 0.00 | 0.00 |
| June | 65.66 | 2.28 | 63.38 | 227.79 | 1.53 | 0.00 | 0.00 | 0.00 |
| July | 65.03 | 1.12 | 63.91 | 206.14 | 0.23 | 0.00 | 0.00 | 0.00 |
| August | 59.80 | 0.33 | 59.47 | 171.39 | 0.80 | 0.00 | 0.00 | 0.00 |
| September | 53.11 | 0.01 | 53.10 | 131.20 | 4.66 | 0.00 | 0.00 | 0.00 |
| October | 46.01 | 0.00 | 46.01 | 93.79 | 46.12 | 0.00 | 0.00 | 0.00 |
| November | 38.97 | 0.00 | 38.97 | 49.36 | 100.17 | 0.00 | 0.00 | 0.00 |
| December | 36.11 | 0.00 | 36.11 | 22.73 | 148.15 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 51.69 | 0.50 | 51.19 | 118.60 | 52.88 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 36.11 | 0.00 | 36.11 | 22.73 | 0.23 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 65.66 | 2.28 | 63.91 | 227.79 | 148.15 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: GWINDOW1 N N2A
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 37.02 | 0.00 | 37.02 | 22.82 | 145.43 | 0.00 | 0.00 | 0.00 |
| February | 43.90 | 0.00 | 43.90 | 44.08 | 111.13 | 0.00 | 0.00 | 0.00 |
| March | 52.91 | 0.01 | 52.91 | 85.35 | 61.03 | 0.00 | 0.00 | 0.00 |
| April | 57.54 | 0.29 | 57.25 | 151.45 | 16.61 | 0.00 | 0.00 | 0.00 |
| May | 63.80 | 1.97 | 61.82 | 212.45 | 1.55 | 0.00 | 0.00 | 0.00 |
| June | 65.66 | 2.28 | 63.38 | 227.80 | 1.53 | 0.00 | 0.00 | 0.00 |
| July | 65.03 | 1.12 | 63.91 | 206.14 | 0.23 | 0.00 | 0.00 | 0.00 |
| August | 59.80 | 0.33 | 59.47 | 171.39 | 0.80 | 0.00 | 0.00 | 0.00 |
| September | 53.11 | 0.01 | 53.10 | 131.20 | 4.65 | 0.00 | 0.00 | 0.00 |
| October | 46.01 | 0.00 | 46.01 | 93.78 | 46.12 | 0.00 | 0.00 | 0.00 |
| November | 38.97 | 0.00 | 38.97 | 49.35 | 100.17 | 0.00 | 0.00 | 0.00 |
| December | 36.11 | 0.00 | 36.11 | 22.70 | 148.17 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 51.69 | 0.50 | 51.19 | 118.58 | 52.89 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 36.11 | 0.00 | 36.11 | 22.70 | 0.23 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 65.66 | 2.28 | 63.91 | 227.80 | 148.17 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: GWINDOW1 S S1A
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 167.36 | 101.30 | 66.07 | 232.66 | 141.75 | 0.00 | 0.00 | 0.00 |
| February | 161.53 | 90.35 | 71.18 | 246.78 | 109.68 | 0.00 | 0.00 | 0.00 |
| March | 133.41 | 57.00 | 76.41 | 240.99 | 61.70 | 0.00 | 0.00 | 0.00 |
| April | 99.06 | 30.02 | 69.04 | 242.06 | 17.74 | 0.00 | 0.00 | 0.00 |
| May | 69.44 | 5.39 | 64.05 | 227.01 | 1.54 | 0.00 | 0.00 | 0.00 |
| June | 63.46 | 1.29 | 62.17 | 223.84 | 1.54 | 0.00 | 0.00 | 0.00 |
| July | 65.80 | 0.73 | 65.07 | 208.56 | 0.23 | 0.00 | 0.00 | 0.00 |
| August | 69.14 | 2.90 | 66.24 | 190.68 | 0.83 | 0.00 | 0.00 | 0.00 |
| September | 96.94 | 27.47 | 69.48 | 217.18 | 5.07 | 0.00 | 0.00 | 0.00 |
| October | 160.12 | 88.84 | 71.28 | 306.57 | 46.86 | 0.00 | 0.00 | 0.00 |
| November | 202.35 | 134.00 | 68.35 | 335.66 | 97.57 | 0.00 | 0.00 | 0.00 |
| December | 179.44 | 112.28 | 67.15 | 259.04 | 139.74 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 122.09 | 54.07 | 68.02 | 244.12 | 51.78 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 63.46 | 0.73 | 62.17 | 190.68 | 0.23 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 202.35 | 134.00 | 76.41 | 335.66 | 141.75 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: GWINDOW1 S S2A
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 167.36 | 101.30 | 66.07 | 232.38 | 142.20 | 0.00 | 0.00 | 0.00 |
| February | 161.53 | 90.35 | 71.18 | 246.36 | 110.35 | 0.00 | 0.00 | 0.00 |
| March | 133.41 | 57.00 | 76.41 | 240.44 | 62.39 | 0.00 | 0.00 | 0.00 |
| April | 99.06 | 30.02 | 69.04 | 240.92 | 18.39 | 0.00 | 0.00 | 0.00 |
| May | 69.44 | 5.39 | 64.05 | 225.22 | 1.70 | 0.00 | 0.00 | 0.00 |
| June | 63.46 | 1.29 | 62.17 | 222.05 | 1.67 | 0.00 | 0.00 | 0.00 |
| July | 65.80 | 0.73 | 65.07 | 206.62 | 0.25 | 0.00 | 0.00 | 0.00 |
| August | 69.14 | 2.90 | 66.24 | 188.98 | 0.98 | 0.00 | 0.00 | 0.00 |
| September | 96.94 | 27.47 | 69.48 | 215.83 | 5.66 | 0.00 | 0.00 | 0.00 |
| October | 160.12 | 88.84 | 71.28 | 305.79 | 47.84 | 0.00 | 0.00 | 0.00 |
| November | 202.35 | 134.00 | 68.35 | 335.15 | 98.37 | 0.00 | 0.00 | 0.00 |
| December | 179.44 | 112.28 | 67.15 | 258.71 | 140.24 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 122.09 | 54.07 | 68.02 | 243.06 | 52.26 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 63.46 | 0.73 | 62.17 | 188.98 | 0.25 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 202.35 | 134.00 | 76.41 | 335.15 | 142.20 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MWINDOW1 S SWA
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 167.36 | 101.30 | 66.07 | 232.36 | 139.56 | 0.00 | 0.00 | 0.00 |
| February | 161.53 | 90.35 | 71.18 | 245.29 | 109.13 | 0.00 | 0.00 | 0.00 |
| March | 133.41 | 57.00 | 76.41 | 238.60 | 62.69 | 0.00 | 0.00 | 0.00 |
| April | 99.06 | 30.02 | 69.04 | 239.07 | 18.31 | 0.00 | 0.00 | 0.00 |
| May | 69.44 | 5.39 | 64.05 | 225.09 | 1.58 | 0.00 | 0.00 | 0.00 |
| June | 63.46 | 1.29 | 62.17 | 222.95 | 1.49 | 0.00 | 0.00 | 0.00 |
| July | 65.80 | 0.73 | 65.07 | 209.70 | 0.20 | 0.00 | 0.00 | 0.00 |
| August | 69.14 | 2.90 | 66.24 | 192.33 | 0.61 | 0.00 | 0.00 | 0.00 |
| September | 96.94 | 27.47 | 69.48 | 218.29 | 4.11 | 0.00 | 0.00 | 0.00 |
| October | 160.12 | 88.84 | 71.28 | 306.53 | 45.02 | 0.00 | 0.00 | 0.00 |
| November | 202.35 | 134.00 | 68.35 | 335.33 | 95.51 | 0.00 | 0.00 | 0.00 |
| December | 179.44 | 112.28 | 67.15 | 259.66 | 135.91 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 122.09 | 54.07 | 68.02 | 243.64 | 50.93 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 63.46 | 0.73 | 62.17 | 192.33 | 0.20 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 202.35 | 134.00 | 76.41 | 335.33 | 139.56 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MWINDOW1 W SWA
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 51.04 | 19.84 | 31.19 | 56.95 | 100.11 | 0.00 | 0.00 | 0.00 |
| February | 58.30 | 21.45 | 36.85 | 78.40 | 76.12 | 0.00 | 0.00 | 0.00 |
| March | 75.99 | 30.54 | 45.46 | 127.76 | 41.92 | 0.00 | 0.00 | 0.00 |
| April | 91.85 | 42.99 | 48.86 | 194.94 | 11.80 | 0.00 | 0.00 | 0.00 |
| May | 87.00 | 36.85 | 50.16 | 220.03 | 1.07 | 0.00 | 0.00 | 0.00 |
| June | 82.07 | 32.04 | 50.03 | 220.05 | 0.96 | 0.00 | 0.00 | 0.00 |
| July | 60.68 | 11.77 | 48.91 | 168.31 | 0.14 | 0.00 | 0.00 | 0.00 |
| August | 55.64 | 9.77 | 45.87 | 143.51 | 0.41 | 0.00 | 0.00 | 0.00 |
| September | 61.46 | 18.18 | 43.27 | 134.61 | 2.67 | 0.00 | 0.00 | 0.00 |
| October | 63.79 | 25.38 | 38.41 | 122.89 | 30.22 | 0.00 | 0.00 | 0.00 |
| November | 57.70 | 24.58 | 33.12 | 90.25 | 66.08 | 0.00 | 0.00 | 0.00 |
| December | 49.44 | 18.88 | 30.56 | 57.32 | 96.04 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 66.23 | 24.32 | 41.91 | 134.77 | 35.46 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 49.44 | 9.77 | 30.56 | 56.95 | 0.14 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 91.85 | 42.99 | 50.16 | 220.05 | 100.11 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MWINDOW1 W NWA
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 51.04 | 19.84 | 31.19 | 61.32 | 92.97 | 0.00 | 0.00 | 0.00 |
| February | 58.30 | 21.45 | 36.85 | 80.91 | 73.32 | 0.00 | 0.00 | 0.00 |
| March | 75.99 | 30.54 | 45.46 | 129.21 | 41.09 | 0.00 | 0.00 | 0.00 |
| April | 91.85 | 42.99 | 48.86 | 195.93 | 11.55 | 0.00 | 0.00 | 0.00 |
| May | 87.00 | 36.85 | 50.16 | 220.25 | 1.07 | 0.00 | 0.00 | 0.00 |
| June | 82.07 | 32.04 | 50.03 | 220.02 | 0.96 | 0.00 | 0.00 | 0.00 |
| July | 60.68 | 11.77 | 48.91 | 168.33 | 0.14 | 0.00 | 0.00 | 0.00 |
| August | 55.64 | 9.77 | 45.87 | 143.75 | 0.40 | 0.00 | 0.00 | 0.00 |
| September | 61.46 | 18.18 | 43.27 | 135.53 | 2.53 | 0.00 | 0.00 | 0.00 |
| October | 63.79 | 25.38 | 38.41 | 124.67 | 29.34 | 0.00 | 0.00 | 0.00 |
| November | 57.70 | 24.58 | 33.12 | 92.64 | 64.13 | 0.00 | 0.00 | 0.00 |
| December | 49.44 | 18.88 | 30.56 | 60.71 | 91.08 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 66.23 | 24.32 | 41.91 | 136.29 | 33.88 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 49.44 | 9.77 | 30.56 | 60.71 | 0.14 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 91.85 | 42.99 | 50.16 | 220.25 | 92.97 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MWINDOW1 N NWA
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 37.02 | 0.00 | 37.02 | 22.73 | 145.04 | 0.00 | 0.00 | 0.00 |
| February | 43.90 | 0.00 | 43.90 | 42.73 | 112.95 | 0.00 | 0.00 | 0.00 |
| March | 52.91 | 0.01 | 52.91 | 83.20 | 62.76 | 0.00 | 0.00 | 0.00 |
| April | 57.54 | 0.29 | 57.25 | 148.67 | 17.36 | 0.00 | 0.00 | 0.00 |
| May | 63.80 | 1.97 | 61.82 | 210.50 | 1.61 | 0.00 | 0.00 | 0.00 |
| June | 65.66 | 2.28 | 63.38 | 226.92 | 1.48 | 0.00 | 0.00 | 0.00 |
| July | 65.03 | 1.12 | 63.91 | 207.16 | 0.19 | 0.00 | 0.00 | 0.00 |
| August | 59.80 | 0.33 | 59.47 | 173.08 | 0.59 | 0.00 | 0.00 | 0.00 |
| September | 53.11 | 0.01 | 53.10 | 132.67 | 3.83 | 0.00 | 0.00 | 0.00 |
| October | 46.01 | 0.00 | 46.01 | 94.27 | 44.73 | 0.00 | 0.00 | 0.00 |
| November | 38.97 | 0.00 | 38.97 | 49.82 | 98.32 | 0.00 | 0.00 | 0.00 |
| December | 36.11 | 0.00 | 36.11 | 24.16 | 142.67 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 51.69 | 0.50 | 51.19 | 118.38 | 52.38 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 36.11 | 0.00 | 36.11 | 22.73 | 0.19 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 65.66 | 2.28 | 63.91 | 226.92 | 145.04 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MWINDOW1 S SEA
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 167.36 | 101.30 | 66.07 | 231.67 | 139.37 | 0.00 | 0.00 | 0.00 |
| February | 161.53 | 90.35 | 71.18 | 244.71 | 108.97 | 0.00 | 0.00 | 0.00 |
| March | 133.41 | 57.00 | 76.41 | 238.19 | 62.45 | 0.00 | 0.00 | 0.00 |
| April | 99.06 | 30.02 | 69.04 | 238.84 | 18.16 | 0.00 | 0.00 | 0.00 |
| May | 69.44 | 5.39 | 64.05 | 224.93 | 1.55 | 0.00 | 0.00 | 0.00 |
| June | 63.46 | 1.29 | 62.17 | 223.14 | 1.46 | 0.00 | 0.00 | 0.00 |
| July | 65.80 | 0.73 | 65.07 | 209.67 | 0.19 | 0.00 | 0.00 | 0.00 |
| August | 69.14 | 2.90 | 66.24 | 192.31 | 0.61 | 0.00 | 0.00 | 0.00 |
| September | 96.94 | 27.47 | 69.48 | 218.28 | 4.05 | 0.00 | 0.00 | 0.00 |
| October | 160.12 | 88.84 | 71.28 | 306.26 | 44.85 | 0.00 | 0.00 | 0.00 |
| November | 202.35 | 134.00 | 68.35 | 335.01 | 95.26 | 0.00 | 0.00 | 0.00 |
| December | 179.44 | 112.28 | 67.15 | 259.17 | 135.68 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 122.09 | 54.07 | 68.02 | 243.39 | 50.81 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 63.46 | 0.73 | 62.17 | 192.31 | 0.19 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 202.35 | 134.00 | 76.41 | 335.01 | 139.37 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MWINDOW1 E SEA
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 52.34 | 21.11 | 31.23 | 51.92 | 92.77 | 0.00 | 0.00 | 0.00 |
| February | 63.35 | 26.08 | 37.27 | 81.39 | 70.39 | 0.00 | 0.00 | 0.00 |
| March | 77.36 | 31.89 | 45.47 | 127.64 | 38.96 | 0.00 | 0.00 | 0.00 |
| April | 92.32 | 43.12 | 49.19 | 195.24 | 11.33 | 0.00 | 0.00 | 0.00 |
| May | 90.57 | 40.16 | 50.41 | 225.76 | 1.01 | 0.00 | 0.00 | 0.00 |
| June | 73.68 | 24.44 | 49.24 | 204.82 | 0.95 | 0.00 | 0.00 | 0.00 |
| July | 61.85 | 12.99 | 48.86 | 171.43 | 0.13 | 0.00 | 0.00 | 0.00 |
| August | 55.78 | 9.66 | 46.12 | 143.52 | 0.39 | 0.00 | 0.00 | 0.00 |
| September | 59.49 | 16.49 | 43.00 | 131.00 | 2.59 | 0.00 | 0.00 | 0.00 |
| October | 65.29 | 26.40 | 38.89 | 123.92 | 28.88 | 0.00 | 0.00 | 0.00 |
| November | 57.74 | 24.73 | 33.01 | 85.62 | 61.72 | 0.00 | 0.00 | 0.00 |
| December | 50.34 | 19.92 | 30.41 | 54.38 | 91.03 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 66.66 | 24.71 | 41.95 | 133.25 | 33.20 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 50.34 | 9.66 | 30.41 | 51.92 | 0.13 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 92.32 | 43.12 | 50.41 | 225.76 | 92.77 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MWINDOW1 E NEA
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 52.34 | 21.11 | 31.23 | 56.68 | 86.14 | 0.00 | 0.00 | 0.00 |
| February | 63.35 | 26.08 | 37.27 | 83.95 | 67.97 | 0.00 | 0.00 | 0.00 |
| March | 77.36 | 31.89 | 45.47 | 129.11 | 38.19 | 0.00 | 0.00 | 0.00 |
| April | 92.32 | 43.12 | 49.19 | 196.24 | 11.09 | 0.00 | 0.00 | 0.00 |
| May | 90.57 | 40.16 | 50.41 | 226.00 | 1.00 | 0.00 | 0.00 | 0.00 |
| June | 73.68 | 24.44 | 49.24 | 204.80 | 0.95 | 0.00 | 0.00 | 0.00 |
| July | 61.85 | 12.99 | 48.86 | 171.45 | 0.13 | 0.00 | 0.00 | 0.00 |
| August | 55.78 | 9.66 | 46.12 | 143.76 | 0.38 | 0.00 | 0.00 | 0.00 |
| September | 59.49 | 16.49 | 43.00 | 131.93 | 2.46 | 0.00 | 0.00 | 0.00 |
| October | 65.29 | 26.40 | 38.89 | 125.73 | 28.03 | 0.00 | 0.00 | 0.00 |
| November | 57.74 | 24.73 | 33.01 | 88.03 | 59.84 | 0.00 | 0.00 | 0.00 |
| December | 50.34 | 19.92 | 30.41 | 57.76 | 86.38 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 66.66 | 24.71 | 41.95 | 134.81 | 31.73 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 50.34 | 9.66 | 30.41 | 56.68 | 0.13 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 92.32 | 43.12 | 50.41 | 226.00 | 86.38 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MWINDOW1 N NEA
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 37.02 | 0.00 | 37.02 | 22.00 | 144.91 | 0.00 | 0.00 | 0.00 |
| February | 43.90 | 0.00 | 43.90 | 41.96 | 113.10 | 0.00 | 0.00 | 0.00 |
| March | 52.91 | 0.01 | 52.91 | 82.76 | 62.55 | 0.00 | 0.00 | 0.00 |
| April | 57.54 | 0.29 | 57.25 | 148.42 | 17.22 | 0.00 | 0.00 | 0.00 |
| May | 63.80 | 1.97 | 61.82 | 210.34 | 1.58 | 0.00 | 0.00 | 0.00 |
| June | 65.66 | 2.28 | 63.38 | 227.11 | 1.46 | 0.00 | 0.00 | 0.00 |
| July | 65.03 | 1.12 | 63.91 | 207.14 | 0.19 | 0.00 | 0.00 | 0.00 |
| August | 59.80 | 0.33 | 59.47 | 173.05 | 0.59 | 0.00 | 0.00 | 0.00 |
| September | 53.11 | 0.01 | 53.10 | 132.66 | 3.77 | 0.00 | 0.00 | 0.00 |
| October | 46.01 | 0.00 | 46.01 | 93.99 | 44.57 | 0.00 | 0.00 | 0.00 |
| November | 38.97 | 0.00 | 38.97 | 49.43 | 98.13 | 0.00 | 0.00 | 0.00 |
| December | 36.11 | 0.00 | 36.11 | 23.46 | 142.64 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 51.69 | 0.50 | 51.19 | 118.08 | 52.31 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 36.11 | 0.00 | 36.11 | 22.00 | 0.19 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 65.66 | 2.28 | 63.91 | 227.11 | 144.91 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MWINDOW1 N N1A
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 37.02 | 0.00 | 37.02 | 21.16 | 151.06 | 0.00 | 0.00 | 0.00 |
| February | 43.90 | 0.00 | 43.90 | 42.08 | 115.95 | 0.00 | 0.00 | 0.00 |
| March | 52.91 | 0.01 | 52.91 | 84.13 | 62.61 | 0.00 | 0.00 | 0.00 |
| April | 57.54 | 0.29 | 57.25 | 151.43 | 16.83 | 0.00 | 0.00 | 0.00 |
| May | 63.80 | 1.97 | 61.82 | 214.38 | 1.47 | 0.00 | 0.00 | 0.00 |
| June | 65.66 | 2.28 | 63.38 | 230.83 | 1.39 | 0.00 | 0.00 | 0.00 |
| July | 65.03 | 1.12 | 63.91 | 210.35 | 0.19 | 0.00 | 0.00 | 0.00 |
| August | 59.80 | 0.33 | 59.47 | 175.73 | 0.53 | 0.00 | 0.00 | 0.00 |
| September | 53.11 | 0.01 | 53.10 | 134.90 | 3.55 | 0.00 | 0.00 | 0.00 |
| October | 46.01 | 0.00 | 46.01 | 95.50 | 44.36 | 0.00 | 0.00 | 0.00 |
| November | 38.97 | 0.00 | 38.97 | 50.02 | 99.15 | 0.00 | 0.00 | 0.00 |
| December | 36.11 | 0.00 | 36.11 | 22.86 | 147.79 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 51.69 | 0.50 | 51.19 | 119.84 | 53.49 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 36.11 | 0.00 | 36.11 | 21.16 | 0.19 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 65.66 | 2.28 | 63.91 | 230.83 | 151.06 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MWINDOW1 N N2A
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 37.02 | 0.00 | 37.02 | 21.11 | 151.09 | 0.00 | 0.00 | 0.00 |
| February | 43.90 | 0.00 | 43.90 | 42.04 | 115.99 | 0.00 | 0.00 | 0.00 |
| March | 52.91 | 0.01 | 52.91 | 84.11 | 62.61 | 0.00 | 0.00 | 0.00 |
| April | 57.54 | 0.29 | 57.25 | 151.42 | 16.83 | 0.00 | 0.00 | 0.00 |
| May | 63.80 | 1.97 | 61.82 | 214.37 | 1.47 | 0.00 | 0.00 | 0.00 |
| June | 65.66 | 2.28 | 63.38 | 230.83 | 1.39 | 0.00 | 0.00 | 0.00 |
| July | 65.03 | 1.12 | 63.91 | 210.34 | 0.19 | 0.00 | 0.00 | 0.00 |
| August | 59.80 | 0.33 | 59.47 | 175.73 | 0.53 | 0.00 | 0.00 | 0.00 |
| September | 53.11 | 0.01 | 53.10 | 134.90 | 3.54 | 0.00 | 0.00 | 0.00 |
| October | 46.01 | 0.00 | 46.01 | 95.49 | 44.35 | 0.00 | 0.00 | 0.00 |
| November | 38.97 | 0.00 | 38.97 | 50.00 | 99.15 | 0.00 | 0.00 | 0.00 |
| December | 36.11 | 0.00 | 36.11 | 22.82 | 147.82 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 51.69 | 0.50 | 51.19 | 119.82 | 53.49 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 36.11 | 0.00 | 36.11 | 21.11 | 0.19 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 65.66 | 2.28 | 63.91 | 230.83 | 151.09 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MWINDOW1 S S1A
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 167.36 | 101.30 | 66.07 | 230.48 | 143.64 | 0.00 | 0.00 | 0.00 |
| February | 161.53 | 90.35 | 71.18 | 244.68 | 111.17 | 0.00 | 0.00 | 0.00 |
| March | 133.41 | 57.00 | 76.41 | 239.42 | 62.52 | 0.00 | 0.00 | 0.00 |
| April | 99.06 | 30.02 | 69.04 | 241.60 | 17.78 | 0.00 | 0.00 | 0.00 |
| May | 69.44 | 5.39 | 64.05 | 228.92 | 1.44 | 0.00 | 0.00 | 0.00 |
| June | 63.46 | 1.29 | 62.17 | 226.86 | 1.40 | 0.00 | 0.00 | 0.00 |
| July | 65.80 | 0.73 | 65.07 | 212.90 | 0.19 | 0.00 | 0.00 | 0.00 |
| August | 69.14 | 2.90 | 66.24 | 194.94 | 0.55 | 0.00 | 0.00 | 0.00 |
| September | 96.94 | 27.47 | 69.48 | 220.36 | 3.83 | 0.00 | 0.00 | 0.00 |
| October | 160.12 | 88.84 | 71.28 | 307.56 | 44.70 | 0.00 | 0.00 | 0.00 |
| November | 202.35 | 134.00 | 68.35 | 335.48 | 96.02 | 0.00 | 0.00 | 0.00 |
| December | 179.44 | 112.28 | 67.15 | 258.39 | 138.91 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 122.09 | 54.07 | 68.02 | 245.01 | 51.60 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 63.46 | 0.73 | 62.17 | 194.94 | 0.19 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 202.35 | 134.00 | 76.41 | 335.48 | 143.64 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MWINDOW1 S S2A
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 167.36 | 101.30 | 66.07 | 230.45 | 143.64 | 0.00 | 0.00 | 0.00 |
| February | 161.53 | 90.35 | 71.18 | 244.66 | 111.17 | 0.00 | 0.00 | 0.00 |
| March | 133.41 | 57.00 | 76.41 | 239.40 | 62.52 | 0.00 | 0.00 | 0.00 |
| April | 99.06 | 30.02 | 69.04 | 241.59 | 17.78 | 0.00 | 0.00 | 0.00 |
| May | 69.44 | 5.39 | 64.05 | 228.91 | 1.44 | 0.00 | 0.00 | 0.00 |
| June | 63.46 | 1.29 | 62.17 | 226.87 | 1.40 | 0.00 | 0.00 | 0.00 |
| July | 65.80 | 0.73 | 65.07 | 212.90 | 0.19 | 0.00 | 0.00 | 0.00 |
| August | 69.14 | 2.90 | 66.24 | 194.93 | 0.55 | 0.00 | 0.00 | 0.00 |
| September | 96.94 | 27.47 | 69.48 | 220.36 | 3.83 | 0.00 | 0.00 | 0.00 |
| October | 160.12 | 88.84 | 71.28 | 307.55 | 44.69 | 0.00 | 0.00 | 0.00 |
| November | 202.35 | 134.00 | 68.35 | 335.47 | 96.01 | 0.00 | 0.00 | 0.00 |
| December | 179.44 | 112.28 | 67.15 | 258.37 | 138.90 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 122.09 | 54.07 | 68.02 | 245.01 | 51.60 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 63.46 | 0.73 | 62.17 | 194.93 | 0.19 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 202.35 | 134.00 | 76.41 | 335.47 | 143.64 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: TWINDOW1 S SWA
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 167.36 | 101.30 | 66.07 | 237.46 | 122.05 | 0.00 | 0.00 | 0.00 |
| February | 161.53 | 90.35 | 71.18 | 247.97 | 96.57 | 0.00 | 0.00 | 0.00 |
| March | 133.41 | 57.00 | 76.41 | 236.21 | 58.62 | 0.00 | 0.00 | 0.00 |
| April | 99.06 | 30.02 | 69.04 | 233.19 | 17.35 | 0.00 | 0.00 | 0.00 |
| May | 69.44 | 5.39 | 64.05 | 218.06 | 1.48 | 0.00 | 0.00 | 0.00 |
| June | 63.46 | 1.29 | 62.17 | 215.41 | 1.48 | 0.00 | 0.00 | 0.00 |
| July | 65.80 | 0.73 | 65.07 | 203.07 | 0.18 | 0.00 | 0.00 | 0.00 |
| August | 69.14 | 2.90 | 66.24 | 186.54 | 0.60 | 0.00 | 0.00 | 0.00 |
| September | 96.94 | 27.47 | 69.48 | 213.28 | 3.83 | 0.00 | 0.00 | 0.00 |
| October | 160.12 | 88.84 | 71.28 | 302.70 | 42.82 | 0.00 | 0.00 | 0.00 |
| November | 202.35 | 134.00 | 68.35 | 335.37 | 87.18 | 0.00 | 0.00 | 0.00 |
| December | 179.44 | 112.28 | 67.15 | 264.94 | 119.15 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 122.09 | 54.07 | 68.02 | 241.04 | 45.73 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 63.46 | 0.73 | 62.17 | 186.54 | 0.18 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 202.35 | 134.00 | 76.41 | 335.37 | 122.05 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: TWINDOW1 W SWA
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 51.04 | 19.84 | 31.19 | 58.10 | 86.45 | 0.00 | 0.00 | 0.00 |
| February | 58.30 | 21.45 | 36.85 | 78.80 | 66.50 | 0.00 | 0.00 | 0.00 |
| March | 75.99 | 30.54 | 45.46 | 125.79 | 38.87 | 0.00 | 0.00 | 0.00 |
| April | 91.85 | 42.99 | 48.86 | 190.90 | 11.12 | 0.00 | 0.00 | 0.00 |
| May | 87.00 | 36.85 | 50.16 | 215.30 | 1.01 | 0.00 | 0.00 | 0.00 |
| June | 82.07 | 32.04 | 50.03 | 215.01 | 0.95 | 0.00 | 0.00 | 0.00 |
| July | 60.68 | 11.77 | 48.91 | 163.86 | 0.13 | 0.00 | 0.00 | 0.00 |
| August | 55.64 | 9.77 | 45.87 | 139.61 | 0.40 | 0.00 | 0.00 | 0.00 |
| September | 61.46 | 18.18 | 43.27 | 131.28 | 2.48 | 0.00 | 0.00 | 0.00 |
| October | 63.79 | 25.38 | 38.41 | 120.16 | 28.59 | 0.00 | 0.00 | 0.00 |
| November | 57.70 | 24.58 | 33.12 | 89.31 | 59.62 | 0.00 | 0.00 | 0.00 |
| December | 49.44 | 18.88 | 30.56 | 58.56 | 82.78 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 66.23 | 24.32 | 41.91 | 132.39 | 31.43 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 49.44 | 9.77 | 30.56 | 58.10 | 0.13 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 91.85 | 42.99 | 50.16 | 215.30 | 86.45 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: TWINDOW1 W NWA
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 51.04 | 19.84 | 31.19 | 63.60 | 81.77 | 0.00 | 0.00 | 0.00 |
| February | 58.30 | 21.45 | 36.85 | 82.88 | 63.92 | 0.00 | 0.00 | 0.00 |
| March | 75.99 | 30.54 | 45.46 | 128.13 | 37.94 | 0.00 | 0.00 | 0.00 |
| April | 91.85 | 42.99 | 48.86 | 192.27 | 10.95 | 0.00 | 0.00 | 0.00 |
| May | 87.00 | 36.85 | 50.16 | 215.57 | 1.00 | 0.00 | 0.00 | 0.00 |
| June | 82.07 | 32.04 | 50.03 | 214.98 | 0.95 | 0.00 | 0.00 | 0.00 |
| July | 60.68 | 11.77 | 48.91 | 163.87 | 0.13 | 0.00 | 0.00 | 0.00 |
| August | 55.64 | 9.77 | 45.87 | 139.92 | 0.40 | 0.00 | 0.00 | 0.00 |
| September | 61.46 | 18.18 | 43.27 | 132.51 | 2.39 | 0.00 | 0.00 | 0.00 |
| October | 63.79 | 25.38 | 38.41 | 122.83 | 27.76 | 0.00 | 0.00 | 0.00 |
| November | 57.70 | 24.58 | 33.12 | 93.64 | 57.07 | 0.00 | 0.00 | 0.00 |
| December | 49.44 | 18.88 | 30.56 | 64.19 | 78.16 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 66.23 | 24.32 | 41.91 | 134.70 | 30.06 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 49.44 | 9.77 | 30.56 | 63.60 | 0.13 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 91.85 | 42.99 | 50.16 | 215.57 | 81.77 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: TWINDOW1 N NWA
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 37.02 | 0.00 | 37.02 | 26.20 | 127.99 | 0.00 | 0.00 | 0.00 |
| February | 43.90 | 0.00 | 43.90 | 45.96 | 98.80 | 0.00 | 0.00 | 0.00 |
| March | 52.91 | 0.01 | 52.91 | 81.88 | 58.13 | 0.00 | 0.00 | 0.00 |
| April | 57.54 | 0.29 | 57.25 | 143.38 | 16.49 | 0.00 | 0.00 | 0.00 |
| May | 63.80 | 1.97 | 61.82 | 203.50 | 1.53 | 0.00 | 0.00 | 0.00 |
| June | 65.66 | 2.28 | 63.38 | 219.37 | 1.47 | 0.00 | 0.00 | 0.00 |
| July | 65.03 | 1.12 | 63.91 | 200.54 | 0.18 | 0.00 | 0.00 | 0.00 |
| August | 59.80 | 0.33 | 59.47 | 167.35 | 0.57 | 0.00 | 0.00 | 0.00 |
| September | 53.11 | 0.01 | 53.10 | 128.18 | 3.61 | 0.00 | 0.00 | 0.00 |
| October | 46.01 | 0.00 | 46.01 | 91.60 | 42.43 | 0.00 | 0.00 | 0.00 |
| November | 38.97 | 0.00 | 38.97 | 51.52 | 87.76 | 0.00 | 0.00 | 0.00 |
| December | 36.11 | 0.00 | 36.11 | 29.08 | 122.76 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 51.69 | 0.50 | 51.19 | 116.07 | 46.60 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 36.11 | 0.00 | 36.11 | 26.20 | 0.18 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 65.66 | 2.28 | 63.91 | 219.37 | 127.99 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: TWINDOW1 S SEA
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 167.36 | 101.30 | 66.07 | 236.02 | 121.42 | 0.00 | 0.00 | 0.00 |
| February | 161.53 | 90.35 | 71.18 | 246.50 | 96.13 | 0.00 | 0.00 | 0.00 |
| March | 133.41 | 57.00 | 76.41 | 235.28 | 58.13 | 0.00 | 0.00 | 0.00 |
| April | 99.06 | 30.02 | 69.04 | 232.82 | 17.14 | 0.00 | 0.00 | 0.00 |
| May | 69.44 | 5.39 | 64.05 | 217.83 | 1.44 | 0.00 | 0.00 | 0.00 |
| June | 63.46 | 1.29 | 62.17 | 215.63 | 1.46 | 0.00 | 0.00 | 0.00 |
| July | 65.80 | 0.73 | 65.07 | 203.04 | 0.18 | 0.00 | 0.00 | 0.00 |
| August | 69.14 | 2.90 | 66.24 | 186.51 | 0.60 | 0.00 | 0.00 | 0.00 |
| September | 96.94 | 27.47 | 69.48 | 213.26 | 3.76 | 0.00 | 0.00 | 0.00 |
| October | 160.12 | 88.84 | 71.28 | 302.21 | 42.51 | 0.00 | 0.00 | 0.00 |
| November | 202.35 | 134.00 | 68.35 | 334.48 | 86.65 | 0.00 | 0.00 | 0.00 |
| December | 179.44 | 112.28 | 67.15 | 263.64 | 118.54 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 122.09 | 54.07 | 68.02 | 240.46 | 45.45 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 63.46 | 0.73 | 62.17 | 186.51 | 0.18 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 202.35 | 134.00 | 76.41 | 334.48 | 121.42 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: TWINDOW1 E SEA
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 52.34 | 21.11 | 31.23 | 55.42 | 81.49 | 0.00 | 0.00 | 0.00 |
| February | 63.35 | 26.08 | 37.27 | 83.40 | 62.63 | 0.00 | 0.00 | 0.00 |
| March | 77.36 | 31.89 | 45.47 | 126.24 | 36.58 | 0.00 | 0.00 | 0.00 |
| April | 92.32 | 43.12 | 49.19 | 191.21 | 10.73 | 0.00 | 0.00 | 0.00 |
| May | 90.57 | 40.16 | 50.41 | 220.86 | 0.94 | 0.00 | 0.00 | 0.00 |
| June | 73.68 | 24.44 | 49.24 | 199.73 | 0.95 | 0.00 | 0.00 | 0.00 |
| July | 61.85 | 12.99 | 48.86 | 166.94 | 0.12 | 0.00 | 0.00 | 0.00 |
| August | 55.78 | 9.66 | 46.12 | 139.58 | 0.37 | 0.00 | 0.00 | 0.00 |
| September | 59.49 | 16.49 | 43.00 | 127.65 | 2.41 | 0.00 | 0.00 | 0.00 |
| October | 65.29 | 26.40 | 38.89 | 121.37 | 27.47 | 0.00 | 0.00 | 0.00 |
| November | 57.74 | 24.73 | 33.01 | 85.82 | 56.53 | 0.00 | 0.00 | 0.00 |
| December | 50.34 | 19.92 | 30.41 | 57.76 | 80.12 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 66.66 | 24.71 | 41.95 | 131.51 | 29.90 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 50.34 | 9.66 | 30.41 | 55.42 | 0.12 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 92.32 | 43.12 | 50.41 | 220.86 | 81.49 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: TWINDOW1 E NEA
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 52.34 | 21.11 | 31.23 | 60.59 | 75.99 | 0.00 | 0.00 | 0.00 |
| February | 63.35 | 26.08 | 37.27 | 87.27 | 60.02 | 0.00 | 0.00 | 0.00 |
| March | 77.36 | 31.89 | 45.47 | 128.51 | 35.70 | 0.00 | 0.00 | 0.00 |
| April | 92.32 | 43.12 | 49.19 | 192.58 | 10.55 | 0.00 | 0.00 | 0.00 |
| May | 90.57 | 40.16 | 50.41 | 221.14 | 0.94 | 0.00 | 0.00 | 0.00 |
| June | 73.68 | 24.44 | 49.24 | 199.71 | 0.94 | 0.00 | 0.00 | 0.00 |
| July | 61.85 | 12.99 | 48.86 | 166.95 | 0.12 | 0.00 | 0.00 | 0.00 |
| August | 55.78 | 9.66 | 46.12 | 139.89 | 0.37 | 0.00 | 0.00 | 0.00 |
| September | 59.49 | 16.49 | 43.00 | 128.88 | 2.32 | 0.00 | 0.00 | 0.00 |
| October | 65.29 | 26.40 | 38.89 | 124.03 | 26.66 | 0.00 | 0.00 | 0.00 |
| November | 57.74 | 24.73 | 33.01 | 90.01 | 53.97 | 0.00 | 0.00 | 0.00 |
| December | 50.34 | 19.92 | 30.41 | 62.73 | 74.69 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 66.66 | 24.71 | 41.95 | 133.69 | 28.39 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 50.34 | 9.66 | 30.41 | 60.59 | 0.12 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 92.32 | 43.12 | 50.41 | 221.14 | 75.99 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: TWINDOW1 N NEA
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 37.02 | 0.00 | 37.02 | 25.08 | 126.84 | 0.00 | 0.00 | 0.00 |
| February | 43.90 | 0.00 | 43.90 | 44.29 | 98.40 | 0.00 | 0.00 | 0.00 |
| March | 52.91 | 0.01 | 52.91 | 80.84 | 57.68 | 0.00 | 0.00 | 0.00 |
| April | 57.54 | 0.29 | 57.25 | 143.00 | 16.28 | 0.00 | 0.00 | 0.00 |
| May | 63.80 | 1.97 | 61.82 | 203.27 | 1.49 | 0.00 | 0.00 | 0.00 |
| June | 65.66 | 2.28 | 63.38 | 219.59 | 1.44 | 0.00 | 0.00 | 0.00 |
| July | 65.03 | 1.12 | 63.91 | 200.51 | 0.18 | 0.00 | 0.00 | 0.00 |
| August | 59.80 | 0.33 | 59.47 | 167.31 | 0.57 | 0.00 | 0.00 | 0.00 |
| September | 53.11 | 0.01 | 53.10 | 128.16 | 3.54 | 0.00 | 0.00 | 0.00 |
| October | 46.01 | 0.00 | 46.01 | 91.08 | 42.13 | 0.00 | 0.00 | 0.00 |
| November | 38.97 | 0.00 | 38.97 | 50.34 | 87.22 | 0.00 | 0.00 | 0.00 |
| December | 36.11 | 0.00 | 36.11 | 27.73 | 121.79 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 51.69 | 0.50 | 51.19 | 115.46 | 46.25 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 36.11 | 0.00 | 36.11 | 25.08 | 0.18 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 65.66 | 2.28 | 63.91 | 219.59 | 126.84 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: TWINDOW1 N N1A
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 37.02 | 0.00 | 37.02 | 26.16 | 130.05 | 0.00 | 0.00 | 0.00 |
| February | 43.90 | 0.00 | 43.90 | 45.86 | 101.39 | 0.00 | 0.00 | 0.00 |
| March | 52.91 | 0.01 | 52.91 | 83.02 | 58.99 | 0.00 | 0.00 | 0.00 |
| April | 57.54 | 0.29 | 57.25 | 146.96 | 16.23 | 0.00 | 0.00 | 0.00 |
| May | 63.80 | 1.97 | 61.82 | 208.18 | 1.44 | 0.00 | 0.00 | 0.00 |
| June | 65.66 | 2.28 | 63.38 | 224.08 | 1.43 | 0.00 | 0.00 | 0.00 |
| July | 65.03 | 1.12 | 63.91 | 204.33 | 0.18 | 0.00 | 0.00 | 0.00 |
| August | 59.80 | 0.33 | 59.47 | 170.54 | 0.54 | 0.00 | 0.00 | 0.00 |
| September | 53.11 | 0.01 | 53.10 | 130.97 | 3.44 | 0.00 | 0.00 | 0.00 |
| October | 46.01 | 0.00 | 46.01 | 93.30 | 42.56 | 0.00 | 0.00 | 0.00 |
| November | 38.97 | 0.00 | 38.97 | 51.70 | 89.90 | 0.00 | 0.00 | 0.00 |
| December | 36.11 | 0.00 | 36.11 | 28.89 | 124.88 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 51.69 | 0.50 | 51.19 | 118.20 | 47.36 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 36.11 | 0.00 | 36.11 | 26.16 | 0.18 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 65.66 | 2.28 | 63.91 | 224.08 | 130.05 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: TWINDOW1 N N2A
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 37.02 | 0.00 | 37.02 | 26.07 | 129.96 | 0.00 | 0.00 | 0.00 |
| February | 43.90 | 0.00 | 43.90 | 45.74 | 101.38 | 0.00 | 0.00 | 0.00 |
| March | 52.91 | 0.01 | 52.91 | 82.95 | 58.96 | 0.00 | 0.00 | 0.00 |
| April | 57.54 | 0.29 | 57.25 | 146.94 | 16.22 | 0.00 | 0.00 | 0.00 |
| May | 63.80 | 1.97 | 61.82 | 208.17 | 1.43 | 0.00 | 0.00 | 0.00 |
| June | 65.66 | 2.28 | 63.38 | 224.09 | 1.42 | 0.00 | 0.00 | 0.00 |
| July | 65.03 | 1.12 | 63.91 | 204.33 | 0.18 | 0.00 | 0.00 | 0.00 |
| August | 59.80 | 0.33 | 59.47 | 170.54 | 0.54 | 0.00 | 0.00 | 0.00 |
| September | 53.11 | 0.01 | 53.10 | 130.97 | 3.44 | 0.00 | 0.00 | 0.00 |
| October | 46.01 | 0.00 | 46.01 | 93.27 | 42.54 | 0.00 | 0.00 | 0.00 |
| November | 38.97 | 0.00 | 38.97 | 51.62 | 89.87 | 0.00 | 0.00 | 0.00 |
| December | 36.11 | 0.00 | 36.11 | 28.79 | 124.82 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 51.69 | 0.50 | 51.19 | 118.16 | 47.34 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 36.11 | 0.00 | 36.11 | 26.07 | 0.18 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 65.66 | 2.28 | 63.91 | 224.09 | 129.96 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: TWINDOW1 S S1A
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 167.36 | 101.30 | 66.07 | 236.21 | 125.79 | 0.00 | 0.00 | 0.00 |
| February | 161.53 | 90.35 | 71.18 | 247.16 | 99.60 | 0.00 | 0.00 | 0.00 |
| March | 133.41 | 57.00 | 76.41 | 237.08 | 59.42 | 0.00 | 0.00 | 0.00 |
| April | 99.06 | 30.02 | 69.04 | 236.47 | 17.09 | 0.00 | 0.00 | 0.00 |
| May | 69.44 | 5.39 | 64.05 | 222.68 | 1.39 | 0.00 | 0.00 | 0.00 |
| June | 63.46 | 1.29 | 62.17 | 220.12 | 1.44 | 0.00 | 0.00 | 0.00 |
| July | 65.80 | 0.73 | 65.07 | 206.90 | 0.18 | 0.00 | 0.00 | 0.00 |
| August | 69.14 | 2.90 | 66.24 | 189.67 | 0.56 | 0.00 | 0.00 | 0.00 |
| September | 96.94 | 27.47 | 69.48 | 215.87 | 3.67 | 0.00 | 0.00 | 0.00 |
| October | 160.12 | 88.84 | 71.28 | 304.08 | 42.94 | 0.00 | 0.00 | 0.00 |
| November | 202.35 | 134.00 | 68.35 | 335.05 | 89.34 | 0.00 | 0.00 | 0.00 |
| December | 179.44 | 112.28 | 67.15 | 263.65 | 122.91 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 122.09 | 54.07 | 68.02 | 242.78 | 46.81 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 63.46 | 0.73 | 62.17 | 189.67 | 0.18 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 202.35 | 134.00 | 76.41 | 335.05 | 125.79 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: TWINDOW1 S S2A
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 167.36 | 101.30 | 66.07 | 236.12 | 125.76 | 0.00 | 0.00 | 0.00 |
| February | 161.53 | 90.35 | 71.18 | 247.08 | 99.58 | 0.00 | 0.00 | 0.00 |
| March | 133.41 | 57.00 | 76.41 | 237.04 | 59.40 | 0.00 | 0.00 | 0.00 |
| April | 99.06 | 30.02 | 69.04 | 236.45 | 17.08 | 0.00 | 0.00 | 0.00 |
| May | 69.44 | 5.39 | 64.05 | 222.67 | 1.39 | 0.00 | 0.00 | 0.00 |
| June | 63.46 | 1.29 | 62.17 | 220.13 | 1.44 | 0.00 | 0.00 | 0.00 |
| July | 65.80 | 0.73 | 65.07 | 206.90 | 0.18 | 0.00 | 0.00 | 0.00 |
| August | 69.14 | 2.90 | 66.24 | 189.67 | 0.56 | 0.00 | 0.00 | 0.00 |
| September | 96.94 | 27.47 | 69.48 | 215.87 | 3.66 | 0.00 | 0.00 | 0.00 |
| October | 160.12 | 88.84 | 71.28 | 304.06 | 42.92 | 0.00 | 0.00 | 0.00 |
| November | 202.35 | 134.00 | 68.35 | 335.01 | 89.31 | 0.00 | 0.00 | 0.00 |
| December | 179.44 | 112.28 | 67.15 | 263.58 | 122.88 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 122.09 | 54.07 | 68.02 | 242.75 | 46.79 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 63.46 | 0.73 | 62.17 | 189.67 | 0.18 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 202.35 | 134.00 | 76.41 | 335.01 | 125.76 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: TWINDOW14
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 12.56 | 5.07 | 7.49 | 13.70 | 20.93 | 407.67 | 0.00 | 0.00 |
| February | 15.20 | 6.26 | 8.94 | 19.95 | 16.84 | 303.50 | 0.00 | 0.00 |
| March | 18.56 | 7.65 | 10.91 | 29.40 | 10.50 | 291.00 | 0.00 | 0.00 |
| April | 22.15 | 10.35 | 11.80 | 43.69 | 3.77 | 208.00 | 0.00 | 0.00 |
| May | 21.73 | 9.64 | 12.10 | 49.32 | 0.62 | 73.17 | 0.00 | 0.00 |
| June | 17.68 | 5.86 | 11.82 | 43.96 | 0.56 | 52.17 | 0.00 | 0.00 |
| July | 14.84 | 3.12 | 11.72 | 35.93 | 0.12 | 11.83 | 0.00 | 0.00 |
| August | 13.39 | 2.32 | 11.07 | 29.98 | 0.47 | 80.17 | 0.00 | 0.00 |
| September | 14.27 | 3.96 | 10.32 | 28.22 | 1.73 | 227.00 | 0.00 | 0.00 |
| October | 15.67 | 6.34 | 9.33 | 28.19 | 8.30 | 361.17 | 0.00 | 0.00 |
| November | 13.85 | 5.93 | 7.92 | 20.54 | 15.31 | 382.83 | 0.00 | 0.00 |
| December | 12.08 | 4.78 | 7.30 | 14.24 | 20.67 | 412.83 | 0.00 | 0.00 |
| Annual Sum or Average | 15.99 | 5.93 | 10.06 | 29.79 | 8.28 | 2811.33 | 0.00 | 0.00 |
| Minimum of Months | 12.08 | 2.32 | 7.30 | 13.70 | 0.12 | 11.83 | 0.00 | 0.00 |
| Maximum of Months | 22.15 | 10.35 | 12.10 | 49.32 | 20.93 | 412.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ENTRANCE DOOR
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 37.41 | 15.09 | 22.32 | 39.02 | 65.69 | 2.33 | 0.00 | 0.00 |
| February | 45.27 | 18.64 | 26.63 | 58.02 | 52.52 | 4.00 | 0.00 | 0.00 |
| March | 55.29 | 22.79 | 32.49 | 86.80 | 32.61 | 5.00 | 0.00 | 0.00 |
| April | 65.97 | 30.82 | 35.16 | 126.91 | 13.17 | 0.00 | 0.00 | 0.00 |
| May | 64.72 | 28.70 | 36.03 | 140.35 | 3.29 | 15.17 | 0.00 | 0.00 |
| June | 52.65 | 17.46 | 35.19 | 123.47 | 2.63 | 35.50 | 0.00 | 0.00 |
| July | 44.20 | 9.29 | 34.92 | 99.92 | 1.03 | 36.83 | 0.00 | 0.00 |
| August | 39.87 | 6.90 | 32.96 | 83.74 | 2.81 | 95.50 | 0.00 | 0.00 |
| September | 42.51 | 11.78 | 30.73 | 79.75 | 8.38 | 164.00 | 0.00 | 0.00 |
| October | 46.66 | 18.87 | 27.79 | 80.67 | 28.56 | 37.50 | 0.00 | 0.00 |
| November | 41.26 | 17.67 | 23.59 | 58.03 | 50.07 | 17.50 | 0.00 | 0.00 |
| December | 35.97 | 14.24 | 21.73 | 38.70 | 67.61 | 3.00 | 0.00 | 0.00 |
| Annual Sum or Average | 47.64 | 17.66 | 29.98 | 84.70 | 27.26 | 416.33 | 0.00 | 0.00 |
| Minimum of Months | 35.97 | 6.90 | 21.73 | 38.70 | 1.03 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 65.97 | 30.82 | 36.03 | 140.35 | 67.61 | 164.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MWINDOW14
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 12.56 | 5.07 | 7.49 | 11.82 | 24.17 | 539.83 | 0.00 | 0.00 |
| February | 15.20 | 6.26 | 8.94 | 18.43 | 19.03 | 389.17 | 0.00 | 0.00 |
| March | 18.56 | 7.65 | 10.91 | 29.01 | 11.15 | 357.83 | 0.00 | 0.00 |
| April | 22.15 | 10.35 | 11.80 | 44.37 | 3.89 | 226.17 | 0.00 | 0.00 |
| May | 21.73 | 9.64 | 12.10 | 50.63 | 0.62 | 73.33 | 0.00 | 0.00 |
| June | 17.68 | 5.86 | 11.82 | 45.44 | 0.52 | 52.67 | 0.00 | 0.00 |
| July | 14.84 | 3.12 | 11.72 | 37.33 | 0.11 | 9.50 | 0.00 | 0.00 |
| August | 13.39 | 2.32 | 11.07 | 31.08 | 0.43 | 63.50 | 0.00 | 0.00 |
| September | 14.27 | 3.96 | 10.32 | 28.87 | 1.69 | 211.83 | 0.00 | 0.00 |
| October | 15.67 | 6.34 | 9.33 | 28.22 | 8.65 | 386.17 | 0.00 | 0.00 |
| November | 13.85 | 5.93 | 7.92 | 19.50 | 16.79 | 445.50 | 0.00 | 0.00 |
| December | 12.08 | 4.78 | 7.30 | 12.29 | 23.94 | 555.83 | 0.00 | 0.00 |
| Annual Sum or Average | 15.99 | 5.93 | 10.06 | 29.79 | 9.21 | 3311.33 | 0.00 | 0.00 |
| Minimum of Months | 12.08 | 2.32 | 7.30 | 11.82 | 0.11 | 9.50 | 0.00 | 0.00 |
| Maximum of Months | 22.15 | 10.35 | 12.10 | 50.63 | 24.17 | 555.83 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: GWINDOW1 S SWA
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.448261E+09 | 0.271309E+09 | 0.176952E+09 | 0.628287E+09 | 0.368797E+09 |
| February | 0.390780E+09 | 0.218583E+09 | 0.172197E+09 | 0.599871E+09 | 0.258466E+09 |
| March | 0.357330E+09 | 0.152663E+09 | 0.204667E+09 | 0.645080E+09 | 0.163696E+09 |
| April | 0.256767E+09 | 77806700.21 | 0.178961E+09 | 0.622676E+09 | 46445173.31 |
| May | 0.185984E+09 | 14437677.05 | 0.171546E+09 | 0.599018E+09 | 4418239.97 |
| June | 0.164493E+09 | 3353335.34 | 0.161140E+09 | 0.569883E+09 | 4268019.73 |
| July | 0.176248E+09 | 1962822.04 | 0.174285E+09 | 0.548253E+09 | 663670.44 |
| August | 0.185183E+09 | 7763252.03 | 0.177420E+09 | 0.501295E+09 | 2686261.31 |
| September | 0.251278E+09 | 71196446.15 | 0.180081E+09 | 0.555853E+09 | 14987338.18 |
| October | 0.428869E+09 | 0.237960E+09 | 0.190909E+09 | 0.817501E+09 | 0.127655E+09 |
| November | 0.524493E+09 | 0.347337E+09 | 0.177156E+09 | 0.869145E+09 | 0.252651E+09 |
| December | 0.480605E+09 | 0.300743E+09 | 0.179862E+09 | 0.696019E+09 | 0.368572E+09 |
| Annual Sum or Average | 0.385029E+10 | 0.170512E+10 | 0.214517E+10 | 0.765288E+10 | 0.161331E+10 |
| Minimum of Months | 0.164493E+09 | 1962822.04 | 0.161140E+09 | 0.501295E+09 | 663670.44 |
| Maximum of Months | 0.524493E+09 | 0.347337E+09 | 0.204667E+09 | 0.869145E+09 | 0.368797E+09 |
Report: WindowEnergyReportMonthly
For: GWINDOW1 W SWA
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.136699E+09 | 53149103.01 | 83549429.80 | 0.155277E+09 | 0.264170E+09 |
| February | 0.141033E+09 | 51891941.89 | 89140842.82 | 0.192825E+09 | 0.179957E+09 |
| March | 0.203543E+09 | 81795576.77 | 0.121747E+09 | 0.345773E+09 | 0.109312E+09 |
| April | 0.238074E+09 | 0.111439E+09 | 0.126635E+09 | 0.507171E+09 | 29947759.71 |
| May | 0.233028E+09 | 98688978.79 | 0.134339E+09 | 0.587265E+09 | 2986289.58 |
| June | 0.212729E+09 | 83043153.64 | 0.129686E+09 | 0.565688E+09 | 2754511.46 |
| July | 0.162517E+09 | 31519774.07 | 0.130997E+09 | 0.442795E+09 | 469991.34 |
| August | 0.149019E+09 | 26155339.21 | 0.122864E+09 | 0.375443E+09 | 1805546.70 |
| September | 0.159292E+09 | 47133868.37 | 0.112158E+09 | 0.342056E+09 | 9739751.94 |
| October | 0.170857E+09 | 67979562.24 | 0.102878E+09 | 0.326088E+09 | 85631720.78 |
| November | 0.149559E+09 | 63710905.93 | 85848488.14 | 0.232971E+09 | 0.174675E+09 |
| December | 0.132416E+09 | 50570362.82 | 81845224.19 | 0.153452E+09 | 0.260488E+09 |
| Annual Sum or Average | 0.208877E+10 | 0.767078E+09 | 0.132169E+10 | 0.422680E+10 | 0.112194E+10 |
| Minimum of Months | 0.132416E+09 | 26155339.21 | 81845224.19 | 0.153452E+09 | 469991.34 |
| Maximum of Months | 0.238074E+09 | 0.111439E+09 | 0.134339E+09 | 0.587265E+09 | 0.264170E+09 |
Report: WindowEnergyReportMonthly
For: GWINDOW1 W NWA
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.136699E+09 | 53149103.01 | 83549429.80 | 0.167459E+09 | 0.242328E+09 |
| February | 0.141033E+09 | 51891941.89 | 89140842.82 | 0.200596E+09 | 0.168806E+09 |
| March | 0.203543E+09 | 81795576.77 | 0.121747E+09 | 0.350555E+09 | 0.105640E+09 |
| April | 0.238074E+09 | 0.111439E+09 | 0.126635E+09 | 0.510186E+09 | 29022010.34 |
| May | 0.233028E+09 | 98688978.79 | 0.134339E+09 | 0.587912E+09 | 2963884.18 |
| June | 0.212729E+09 | 83043153.64 | 0.129686E+09 | 0.565494E+09 | 2755645.27 |
| July | 0.162517E+09 | 31519774.07 | 0.130997E+09 | 0.442700E+09 | 473294.73 |
| August | 0.149019E+09 | 26155339.21 | 0.122864E+09 | 0.376055E+09 | 1798869.71 |
| September | 0.159292E+09 | 47133868.37 | 0.112158E+09 | 0.344457E+09 | 9189860.65 |
| October | 0.170857E+09 | 67979562.24 | 0.102878E+09 | 0.331020E+09 | 82595703.67 |
| November | 0.149559E+09 | 63710905.93 | 85848488.14 | 0.239146E+09 | 0.169011E+09 |
| December | 0.132416E+09 | 50570362.82 | 81845224.19 | 0.161687E+09 | 0.247181E+09 |
| Annual Sum or Average | 0.208877E+10 | 0.767078E+09 | 0.132169E+10 | 0.427727E+10 | 0.106176E+10 |
| Minimum of Months | 0.132416E+09 | 26155339.21 | 81845224.19 | 0.161687E+09 | 473294.73 |
| Maximum of Months | 0.238074E+09 | 0.111439E+09 | 0.134339E+09 | 0.587912E+09 | 0.247181E+09 |
Report: WindowEnergyReportMonthly
For: GWINDOW1 N NWA
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 99151823.08 | 0.00 | 99151823.08 | 63947058.07 | 0.378014E+09 |
| February | 0.106199E+09 | 0.00 | 0.106199E+09 | 0.109187E+09 | 0.259972E+09 |
| March | 0.141718E+09 | 13520.81 | 0.141704E+09 | 0.228055E+09 | 0.161464E+09 |
| April | 0.149133E+09 | 741838.03 | 0.148392E+09 | 0.387175E+09 | 43661851.96 |
| May | 0.170871E+09 | 5287419.98 | 0.165583E+09 | 0.559725E+09 | 4490325.29 |
| June | 0.170190E+09 | 5905759.23 | 0.164284E+09 | 0.579961E+09 | 4252171.16 |
| July | 0.174176E+09 | 2995006.13 | 0.171181E+09 | 0.541668E+09 | 674038.49 |
| August | 0.160176E+09 | 893198.87 | 0.159283E+09 | 0.449329E+09 | 2624235.22 |
| September | 0.137666E+09 | 17478.26 | 0.137648E+09 | 0.332336E+09 | 13995344.89 |
| October | 0.123225E+09 | 0.00 | 0.123225E+09 | 0.246881E+09 | 0.126140E+09 |
| November | 0.101006E+09 | 0.00 | 0.101006E+09 | 0.126614E+09 | 0.259599E+09 |
| December | 96724368.79 | 0.00 | 96724368.79 | 62778738.12 | 0.387837E+09 |
| Annual Sum or Average | 0.163024E+10 | 15854221.32 | 0.161438E+10 | 0.368766E+10 | 0.164272E+10 |
| Minimum of Months | 96724368.79 | 0.00 | 96724368.79 | 62778738.12 | 674038.49 |
| Maximum of Months | 0.174176E+09 | 5905759.23 | 0.171181E+09 | 0.579961E+09 | 0.387837E+09 |
Report: WindowEnergyReportMonthly
For: GWINDOW1 S SEA
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.448261E+09 | 0.271309E+09 | 0.176952E+09 | 0.620134E+09 | 0.392236E+09 |
| February | 0.390780E+09 | 0.218583E+09 | 0.172197E+09 | 0.585335E+09 | 0.291944E+09 |
| March | 0.357330E+09 | 0.152663E+09 | 0.204667E+09 | 0.618977E+09 | 0.214464E+09 |
| April | 0.256767E+09 | 77806700.21 | 0.178961E+09 | 0.562089E+09 | 99323761.04 |
| May | 0.185984E+09 | 14437677.05 | 0.171546E+09 | 0.498708E+09 | 34557887.02 |
| June | 0.164493E+09 | 3353335.34 | 0.161140E+09 | 0.463893E+09 | 25514185.09 |
| July | 0.176248E+09 | 1962822.04 | 0.174285E+09 | 0.426858E+09 | 17639716.42 |
| August | 0.185183E+09 | 7763252.03 | 0.177420E+09 | 0.411066E+09 | 37482481.68 |
| September | 0.251278E+09 | 71196446.15 | 0.180081E+09 | 0.494220E+09 | 80382917.31 |
| October | 0.428869E+09 | 0.237960E+09 | 0.190909E+09 | 0.775902E+09 | 0.206097E+09 |
| November | 0.524493E+09 | 0.347337E+09 | 0.177156E+09 | 0.841569E+09 | 0.314265E+09 |
| December | 0.480605E+09 | 0.300743E+09 | 0.179862E+09 | 0.681843E+09 | 0.402235E+09 |
| Annual Sum or Average | 0.385029E+10 | 0.170512E+10 | 0.214517E+10 | 0.698059E+10 | 0.211614E+10 |
| Minimum of Months | 0.164493E+09 | 1962822.04 | 0.161140E+09 | 0.411066E+09 | 17639716.42 |
| Maximum of Months | 0.524493E+09 | 0.347337E+09 | 0.204667E+09 | 0.841569E+09 | 0.402235E+09 |
Report: WindowEnergyReportMonthly
For: GWINDOW1 E SEA
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.140190E+09 | 56539698.18 | 83650121.12 | 0.138164E+09 | 0.261045E+09 |
| February | 0.153254E+09 | 63094222.38 | 90159425.42 | 0.192288E+09 | 0.189009E+09 |
| March | 0.207203E+09 | 85422598.17 | 0.121780E+09 | 0.327565E+09 | 0.134178E+09 |
| April | 0.239284E+09 | 0.111771E+09 | 0.127513E+09 | 0.465217E+09 | 61631607.33 |
| May | 0.242579E+09 | 0.107554E+09 | 0.135025E+09 | 0.536488E+09 | 21989381.27 |
| June | 0.190973E+09 | 63337525.82 | 0.127635E+09 | 0.456173E+09 | 16584717.81 |
| July | 0.165663E+09 | 34801893.95 | 0.130861E+09 | 0.370338E+09 | 11435862.26 |
| August | 0.149413E+09 | 25874433.90 | 0.123538E+09 | 0.315946E+09 | 24368306.76 |
| September | 0.154194E+09 | 42735465.13 | 0.111459E+09 | 0.290160E+09 | 51193319.29 |
| October | 0.174871E+09 | 70715302.48 | 0.104156E+09 | 0.300641E+09 | 0.132201E+09 |
| November | 0.149658E+09 | 64104976.85 | 85553081.43 | 0.203926E+09 | 0.204082E+09 |
| December | 0.134821E+09 | 53363630.86 | 81457844.71 | 0.138076E+09 | 0.270304E+09 |
| Annual Sum or Average | 0.210210E+10 | 0.779315E+09 | 0.132279E+10 | 0.373498E+10 | 0.137802E+10 |
| Minimum of Months | 0.134821E+09 | 25874433.90 | 81457844.71 | 0.138076E+09 | 11435862.26 |
| Maximum of Months | 0.242579E+09 | 0.111771E+09 | 0.135025E+09 | 0.536488E+09 | 0.270304E+09 |
Report: WindowEnergyReportMonthly
For: GWINDOW1 E NEA
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.140190E+09 | 56539698.18 | 83650121.12 | 0.155367E+09 | 0.224458E+09 |
| February | 0.153254E+09 | 63094222.38 | 90159425.42 | 0.208655E+09 | 0.156912E+09 |
| March | 0.207203E+09 | 85422598.17 | 0.121780E+09 | 0.350427E+09 | 98538804.70 |
| April | 0.239284E+09 | 0.111771E+09 | 0.127513E+09 | 0.510975E+09 | 27890441.07 |
| May | 0.242579E+09 | 0.107554E+09 | 0.135025E+09 | 0.603656E+09 | 2794962.78 |
| June | 0.190973E+09 | 63337525.82 | 0.127635E+09 | 0.526119E+09 | 2738600.02 |
| July | 0.165663E+09 | 34801893.95 | 0.130861E+09 | 0.450592E+09 | 425964.70 |
| August | 0.149413E+09 | 25874433.90 | 0.123538E+09 | 0.376116E+09 | 1694175.02 |
| September | 0.154194E+09 | 42735465.13 | 0.111459E+09 | 0.334922E+09 | 8889166.61 |
| October | 0.174871E+09 | 70715302.48 | 0.104156E+09 | 0.333606E+09 | 78881224.48 |
| November | 0.149658E+09 | 64104976.85 | 85553081.43 | 0.226839E+09 | 0.157704E+09 |
| December | 0.134821E+09 | 53363630.86 | 81457844.71 | 0.153468E+09 | 0.234330E+09 |
| Annual Sum or Average | 0.210210E+10 | 0.779315E+09 | 0.132279E+10 | 0.423074E+10 | 0.995259E+09 |
| Minimum of Months | 0.134821E+09 | 25874433.90 | 81457844.71 | 0.153468E+09 | 425964.70 |
| Maximum of Months | 0.242579E+09 | 0.111771E+09 | 0.135025E+09 | 0.603656E+09 | 0.234330E+09 |
Report: WindowEnergyReportMonthly
For: GWINDOW1 N NEA
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 99151823.08 | 0.00 | 99151823.08 | 62371389.38 | 0.377637E+09 |
| February | 0.106199E+09 | 0.00 | 0.106199E+09 | 0.107300E+09 | 0.260542E+09 |
| March | 0.141718E+09 | 13520.81 | 0.141704E+09 | 0.226794E+09 | 0.160996E+09 |
| April | 0.149133E+09 | 741838.03 | 0.148392E+09 | 0.386528E+09 | 43342897.88 |
| May | 0.170871E+09 | 5287419.98 | 0.165583E+09 | 0.559257E+09 | 4412472.34 |
| June | 0.170190E+09 | 5905759.23 | 0.164284E+09 | 0.580535E+09 | 4187954.45 |
| July | 0.174176E+09 | 2995006.13 | 0.171181E+09 | 0.541599E+09 | 673290.27 |
| August | 0.160176E+09 | 893198.87 | 0.159283E+09 | 0.449263E+09 | 2631995.52 |
| September | 0.137666E+09 | 17478.26 | 0.137648E+09 | 0.332321E+09 | 13815134.04 |
| October | 0.123225E+09 | 0.00 | 0.123225E+09 | 0.246179E+09 | 0.125754E+09 |
| November | 0.101006E+09 | 0.00 | 0.101006E+09 | 0.125759E+09 | 0.259077E+09 |
| December | 96724368.79 | 0.00 | 96724368.79 | 61320596.55 | 0.387852E+09 |
| Annual Sum or Average | 0.163024E+10 | 15854221.32 | 0.161438E+10 | 0.367923E+10 | 0.164092E+10 |
| Minimum of Months | 96724368.79 | 0.00 | 96724368.79 | 61320596.55 | 673290.27 |
| Maximum of Months | 0.174176E+09 | 5905759.23 | 0.171181E+09 | 0.580535E+09 | 0.387852E+09 |
Report: WindowEnergyReportMonthly
For: GWINDOW1 N N1A
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 99151823.08 | 0.00 | 99151823.08 | 61210902.81 | 0.389451E+09 |
| February | 0.106199E+09 | 0.00 | 0.106199E+09 | 0.106761E+09 | 0.268693E+09 |
| March | 0.141718E+09 | 13520.81 | 0.141704E+09 | 0.228659E+09 | 0.163462E+09 |
| April | 0.149133E+09 | 741838.03 | 0.148392E+09 | 0.392582E+09 | 43073515.24 |
| May | 0.170871E+09 | 5287419.98 | 0.165583E+09 | 0.569051E+09 | 4161076.10 |
| June | 0.170190E+09 | 5905759.23 | 0.164284E+09 | 0.590443E+09 | 3978328.74 |
| July | 0.174176E+09 | 2995006.13 | 0.171181E+09 | 0.552137E+09 | 609138.12 |
| August | 0.160176E+09 | 893198.87 | 0.159283E+09 | 0.459057E+09 | 2141027.86 |
| September | 0.137666E+09 | 17478.26 | 0.137648E+09 | 0.340079E+09 | 12067477.68 |
| October | 0.123225E+09 | 0.00 | 0.123225E+09 | 0.251217E+09 | 0.123540E+09 |
| November | 0.101006E+09 | 0.00 | 0.101006E+09 | 0.127951E+09 | 0.259642E+09 |
| December | 96724368.79 | 0.00 | 96724368.79 | 60876579.37 | 0.396794E+09 |
| Annual Sum or Average | 0.163024E+10 | 15854221.32 | 0.161438E+10 | 0.374002E+10 | 0.166761E+10 |
| Minimum of Months | 96724368.79 | 0.00 | 96724368.79 | 60876579.37 | 609138.12 |
| Maximum of Months | 0.174176E+09 | 5905759.23 | 0.171181E+09 | 0.590443E+09 | 0.396794E+09 |
Report: WindowEnergyReportMonthly
For: GWINDOW1 N N2A
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 99151823.08 | 0.00 | 99151823.08 | 61111789.99 | 0.389515E+09 |
| February | 0.106199E+09 | 0.00 | 0.106199E+09 | 0.106636E+09 | 0.268835E+09 |
| March | 0.141718E+09 | 13520.81 | 0.141704E+09 | 0.228606E+09 | 0.163458E+09 |
| April | 0.149133E+09 | 741838.03 | 0.148392E+09 | 0.392553E+09 | 43065435.99 |
| May | 0.170871E+09 | 5287419.98 | 0.165583E+09 | 0.569030E+09 | 4158735.73 |
| June | 0.170190E+09 | 5905759.23 | 0.164284E+09 | 0.590466E+09 | 3975633.28 |
| July | 0.174176E+09 | 2995006.13 | 0.171181E+09 | 0.552134E+09 | 609044.05 |
| August | 0.160176E+09 | 893198.87 | 0.159283E+09 | 0.459053E+09 | 2141584.56 |
| September | 0.137666E+09 | 17478.26 | 0.137648E+09 | 0.340080E+09 | 12060832.47 |
| October | 0.123225E+09 | 0.00 | 0.123225E+09 | 0.251192E+09 | 0.123532E+09 |
| November | 0.101006E+09 | 0.00 | 0.101006E+09 | 0.127919E+09 | 0.259631E+09 |
| December | 96724368.79 | 0.00 | 96724368.79 | 60798645.92 | 0.396865E+09 |
| Annual Sum or Average | 0.163024E+10 | 15854221.32 | 0.161438E+10 | 0.373958E+10 | 0.166785E+10 |
| Minimum of Months | 96724368.79 | 0.00 | 96724368.79 | 60798645.92 | 609044.05 |
| Maximum of Months | 0.174176E+09 | 5905759.23 | 0.171181E+09 | 0.590466E+09 | 0.396865E+09 |
Report: WindowEnergyReportMonthly
For: GWINDOW1 S S1A
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.448261E+09 | 0.271309E+09 | 0.176952E+09 | 0.623153E+09 | 0.379655E+09 |
| February | 0.390780E+09 | 0.218583E+09 | 0.172197E+09 | 0.596999E+09 | 0.265345E+09 |
| March | 0.357330E+09 | 0.152663E+09 | 0.204667E+09 | 0.645469E+09 | 0.165267E+09 |
| April | 0.256767E+09 | 77806700.21 | 0.178961E+09 | 0.627419E+09 | 45988284.15 |
| May | 0.185984E+09 | 14437677.05 | 0.171546E+09 | 0.608020E+09 | 4125964.20 |
| June | 0.164493E+09 | 3353335.34 | 0.161140E+09 | 0.580182E+09 | 3997571.87 |
| July | 0.176248E+09 | 1962822.04 | 0.174285E+09 | 0.558601E+09 | 611552.70 |
| August | 0.185183E+09 | 7763252.03 | 0.177420E+09 | 0.510714E+09 | 2230983.56 |
| September | 0.251278E+09 | 71196446.15 | 0.180081E+09 | 0.562935E+09 | 13130805.54 |
| October | 0.428869E+09 | 0.237960E+09 | 0.190909E+09 | 0.821109E+09 | 0.125498E+09 |
| November | 0.524493E+09 | 0.347337E+09 | 0.177156E+09 | 0.870040E+09 | 0.252908E+09 |
| December | 0.480605E+09 | 0.300743E+09 | 0.179862E+09 | 0.693811E+09 | 0.374267E+09 |
| Annual Sum or Average | 0.385029E+10 | 0.170512E+10 | 0.214517E+10 | 0.769845E+10 | 0.163303E+10 |
| Minimum of Months | 0.164493E+09 | 1962822.04 | 0.161140E+09 | 0.510714E+09 | 611552.70 |
| Maximum of Months | 0.524493E+09 | 0.347337E+09 | 0.204667E+09 | 0.870040E+09 | 0.379655E+09 |
Report: WindowEnergyReportMonthly
For: GWINDOW1 S S2A
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.448261E+09 | 0.271309E+09 | 0.176952E+09 | 0.622398E+09 | 0.380873E+09 |
| February | 0.390780E+09 | 0.218583E+09 | 0.172197E+09 | 0.595989E+09 | 0.266958E+09 |
| March | 0.357330E+09 | 0.152663E+09 | 0.204667E+09 | 0.643987E+09 | 0.167108E+09 |
| April | 0.256767E+09 | 77806700.21 | 0.178961E+09 | 0.624457E+09 | 47670200.33 |
| May | 0.185984E+09 | 14437677.05 | 0.171546E+09 | 0.603221E+09 | 4550275.94 |
| June | 0.164493E+09 | 3353335.34 | 0.161140E+09 | 0.575543E+09 | 4326286.65 |
| July | 0.176248E+09 | 1962822.04 | 0.174285E+09 | 0.553398E+09 | 673501.16 |
| August | 0.185183E+09 | 7763252.03 | 0.177420E+09 | 0.506163E+09 | 2637277.70 |
| September | 0.251278E+09 | 71196446.15 | 0.180081E+09 | 0.559434E+09 | 14670961.23 |
| October | 0.428869E+09 | 0.237960E+09 | 0.190909E+09 | 0.819032E+09 | 0.128122E+09 |
| November | 0.524493E+09 | 0.347337E+09 | 0.177156E+09 | 0.868697E+09 | 0.254976E+09 |
| December | 0.480605E+09 | 0.300743E+09 | 0.179862E+09 | 0.692938E+09 | 0.375625E+09 |
| Annual Sum or Average | 0.385029E+10 | 0.170512E+10 | 0.214517E+10 | 0.766526E+10 | 0.164819E+10 |
| Minimum of Months | 0.164493E+09 | 1962822.04 | 0.161140E+09 | 0.506163E+09 | 673501.16 |
| Maximum of Months | 0.524493E+09 | 0.347337E+09 | 0.204667E+09 | 0.868697E+09 | 0.380873E+09 |
Report: WindowEnergyReportMonthly
For: MWINDOW1 S SWA
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.448261E+09 | 0.271309E+09 | 0.176952E+09 | 0.622360E+09 | 0.373799E+09 |
| February | 0.390780E+09 | 0.218583E+09 | 0.172197E+09 | 0.593405E+09 | 0.264000E+09 |
| March | 0.357330E+09 | 0.152663E+09 | 0.204667E+09 | 0.639069E+09 | 0.167910E+09 |
| April | 0.256767E+09 | 77806700.21 | 0.178961E+09 | 0.619682E+09 | 47450025.71 |
| May | 0.185984E+09 | 14437677.05 | 0.171546E+09 | 0.602876E+09 | 4231638.43 |
| June | 0.164493E+09 | 3353335.34 | 0.161140E+09 | 0.577889E+09 | 3850325.80 |
| July | 0.176248E+09 | 1962822.04 | 0.174285E+09 | 0.561654E+09 | 522654.08 |
| August | 0.185183E+09 | 7763252.03 | 0.177420E+09 | 0.515137E+09 | 1628155.79 |
| September | 0.251278E+09 | 71196446.15 | 0.180081E+09 | 0.565815E+09 | 10646288.62 |
| October | 0.428869E+09 | 0.237960E+09 | 0.190909E+09 | 0.821011E+09 | 0.120592E+09 |
| November | 0.524493E+09 | 0.347337E+09 | 0.177156E+09 | 0.869175E+09 | 0.247569E+09 |
| December | 0.480605E+09 | 0.300743E+09 | 0.179862E+09 | 0.695486E+09 | 0.364015E+09 |
| Annual Sum or Average | 0.385029E+10 | 0.170512E+10 | 0.214517E+10 | 0.768356E+10 | 0.160621E+10 |
| Minimum of Months | 0.164493E+09 | 1962822.04 | 0.161140E+09 | 0.515137E+09 | 522654.08 |
| Maximum of Months | 0.524493E+09 | 0.347337E+09 | 0.204667E+09 | 0.869175E+09 | 0.373799E+09 |
Report: WindowEnergyReportMonthly
For: MWINDOW1 W SWA
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.136699E+09 | 53149103.01 | 83549429.80 | 0.152545E+09 | 0.268132E+09 |
| February | 0.141033E+09 | 51891941.89 | 89140842.82 | 0.189657E+09 | 0.184161E+09 |
| March | 0.203543E+09 | 81795576.77 | 0.121747E+09 | 0.342185E+09 | 0.112272E+09 |
| April | 0.238074E+09 | 0.111439E+09 | 0.126635E+09 | 0.505272E+09 | 30575081.66 |
| May | 0.233028E+09 | 98688978.79 | 0.134339E+09 | 0.589332E+09 | 2873210.05 |
| June | 0.212729E+09 | 83043153.64 | 0.129686E+09 | 0.570370E+09 | 2500258.45 |
| July | 0.162517E+09 | 31519774.07 | 0.130997E+09 | 0.450814E+09 | 363334.23 |
| August | 0.149019E+09 | 26155339.21 | 0.122864E+09 | 0.384379E+09 | 1090367.04 |
| September | 0.159292E+09 | 47133868.37 | 0.112158E+09 | 0.348902E+09 | 6916907.92 |
| October | 0.170857E+09 | 67979562.24 | 0.102878E+09 | 0.329143E+09 | 80948757.06 |
| November | 0.149559E+09 | 63710905.93 | 85848488.14 | 0.233915E+09 | 0.171286E+09 |
| December | 0.132416E+09 | 50570362.82 | 81845224.19 | 0.153531E+09 | 0.257223E+09 |
| Annual Sum or Average | 0.208877E+10 | 0.767078E+09 | 0.132169E+10 | 0.425005E+10 | 0.111834E+10 |
| Minimum of Months | 0.132416E+09 | 26155339.21 | 81845224.19 | 0.152545E+09 | 363334.23 |
| Maximum of Months | 0.238074E+09 | 0.111439E+09 | 0.134339E+09 | 0.589332E+09 | 0.268132E+09 |
Report: WindowEnergyReportMonthly
For: MWINDOW1 W NWA
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.136699E+09 | 53149103.01 | 83549429.80 | 0.164248E+09 | 0.249008E+09 |
| February | 0.141033E+09 | 51891941.89 | 89140842.82 | 0.195748E+09 | 0.177380E+09 |
| March | 0.203543E+09 | 81795576.77 | 0.121747E+09 | 0.346075E+09 | 0.110056E+09 |
| April | 0.238074E+09 | 0.111439E+09 | 0.126635E+09 | 0.507844E+09 | 29946158.98 |
| May | 0.233028E+09 | 98688978.79 | 0.134339E+09 | 0.589928E+09 | 2852572.98 |
| June | 0.212729E+09 | 83043153.64 | 0.129686E+09 | 0.570290E+09 | 2491203.14 |
| July | 0.162517E+09 | 31519774.07 | 0.130997E+09 | 0.450844E+09 | 364837.27 |
| August | 0.149019E+09 | 26155339.21 | 0.122864E+09 | 0.385021E+09 | 1078789.13 |
| September | 0.159292E+09 | 47133868.37 | 0.112158E+09 | 0.351291E+09 | 6563104.11 |
| October | 0.170857E+09 | 67979562.24 | 0.102878E+09 | 0.333919E+09 | 78572160.20 |
| November | 0.149559E+09 | 63710905.93 | 85848488.14 | 0.240127E+09 | 0.166216E+09 |
| December | 0.132416E+09 | 50570362.82 | 81845224.19 | 0.162613E+09 | 0.243948E+09 |
| Annual Sum or Average | 0.208877E+10 | 0.767078E+09 | 0.132169E+10 | 0.429795E+10 | 0.106848E+10 |
| Minimum of Months | 0.132416E+09 | 26155339.21 | 81845224.19 | 0.162613E+09 | 364837.27 |
| Maximum of Months | 0.238074E+09 | 0.111439E+09 | 0.134339E+09 | 0.589928E+09 | 0.249008E+09 |
Report: WindowEnergyReportMonthly
For: MWINDOW1 N NWA
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 99151823.08 | 0.00 | 99151823.08 | 60890307.24 | 0.388473E+09 |
| February | 0.106199E+09 | 0.00 | 0.106199E+09 | 0.103377E+09 | 0.273246E+09 |
| March | 0.141718E+09 | 13520.81 | 0.141704E+09 | 0.222838E+09 | 0.168089E+09 |
| April | 0.149133E+09 | 741838.03 | 0.148392E+09 | 0.385355E+09 | 44992164.23 |
| May | 0.170871E+09 | 5287419.98 | 0.165583E+09 | 0.563805E+09 | 4313524.76 |
| June | 0.170190E+09 | 5905759.23 | 0.164284E+09 | 0.588176E+09 | 3828633.28 |
| July | 0.174176E+09 | 2995006.13 | 0.171181E+09 | 0.554869E+09 | 517803.16 |
| August | 0.160176E+09 | 893198.87 | 0.159283E+09 | 0.463569E+09 | 1574023.21 |
| September | 0.137666E+09 | 17478.26 | 0.137648E+09 | 0.343881E+09 | 9918528.64 |
| October | 0.123225E+09 | 0.00 | 0.123225E+09 | 0.252501E+09 | 0.119813E+09 |
| November | 0.101006E+09 | 0.00 | 0.101006E+09 | 0.129145E+09 | 0.254855E+09 |
| December | 96724368.79 | 0.00 | 96724368.79 | 64721050.09 | 0.382138E+09 |
| Annual Sum or Average | 0.163024E+10 | 15854221.32 | 0.161438E+10 | 0.373313E+10 | 0.165176E+10 |
| Minimum of Months | 96724368.79 | 0.00 | 96724368.79 | 60890307.24 | 517803.16 |
| Maximum of Months | 0.174176E+09 | 5905759.23 | 0.171181E+09 | 0.588176E+09 | 0.388473E+09 |
Report: WindowEnergyReportMonthly
For: MWINDOW1 S SEA
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.448261E+09 | 0.271309E+09 | 0.176952E+09 | 0.620493E+09 | 0.373288E+09 |
| February | 0.390780E+09 | 0.218583E+09 | 0.172197E+09 | 0.592002E+09 | 0.263621E+09 |
| March | 0.357330E+09 | 0.152663E+09 | 0.204667E+09 | 0.637967E+09 | 0.167256E+09 |
| April | 0.256767E+09 | 77806700.21 | 0.178961E+09 | 0.619084E+09 | 47077471.66 |
| May | 0.185984E+09 | 14437677.05 | 0.171546E+09 | 0.602455E+09 | 4154959.42 |
| June | 0.164493E+09 | 3353335.34 | 0.161140E+09 | 0.578376E+09 | 3792236.89 |
| July | 0.176248E+09 | 1962822.04 | 0.174285E+09 | 0.561589E+09 | 522142.86 |
| August | 0.185183E+09 | 7763252.03 | 0.177420E+09 | 0.515086E+09 | 1632371.83 |
| September | 0.251278E+09 | 71196446.15 | 0.180081E+09 | 0.565794E+09 | 10491439.53 |
| October | 0.428869E+09 | 0.237960E+09 | 0.190909E+09 | 0.820276E+09 | 0.120140E+09 |
| November | 0.524493E+09 | 0.347337E+09 | 0.177156E+09 | 0.868351E+09 | 0.246917E+09 |
| December | 0.480605E+09 | 0.300743E+09 | 0.179862E+09 | 0.694162E+09 | 0.363395E+09 |
| Annual Sum or Average | 0.385029E+10 | 0.170512E+10 | 0.214517E+10 | 0.767563E+10 | 0.160229E+10 |
| Minimum of Months | 0.164493E+09 | 1962822.04 | 0.161140E+09 | 0.515086E+09 | 522142.86 |
| Maximum of Months | 0.524493E+09 | 0.347337E+09 | 0.204667E+09 | 0.868351E+09 | 0.373288E+09 |
Report: WindowEnergyReportMonthly
For: MWINDOW1 E SEA
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.140190E+09 | 56539698.18 | 83650121.12 | 0.139069E+09 | 0.248477E+09 |
| February | 0.153254E+09 | 63094222.38 | 90159425.42 | 0.196896E+09 | 0.170289E+09 |
| March | 0.207203E+09 | 85422598.17 | 0.121780E+09 | 0.341883E+09 | 0.104352E+09 |
| April | 0.239284E+09 | 0.111771E+09 | 0.127513E+09 | 0.506056E+09 | 29369986.51 |
| May | 0.242579E+09 | 0.107554E+09 | 0.135025E+09 | 0.604689E+09 | 2692250.93 |
| June | 0.190973E+09 | 63337525.82 | 0.127635E+09 | 0.530904E+09 | 2474080.13 |
| July | 0.165663E+09 | 34801893.95 | 0.130861E+09 | 0.459164E+09 | 335902.35 |
| August | 0.149413E+09 | 25874433.90 | 0.123538E+09 | 0.384391E+09 | 1034664.80 |
| September | 0.154194E+09 | 42735465.13 | 0.111459E+09 | 0.339550E+09 | 6719550.16 |
| October | 0.174871E+09 | 70715302.48 | 0.104156E+09 | 0.331914E+09 | 77362412.22 |
| November | 0.149658E+09 | 64104976.85 | 85553081.43 | 0.221925E+09 | 0.159974E+09 |
| December | 0.134821E+09 | 53363630.86 | 81457844.71 | 0.145650E+09 | 0.243813E+09 |
| Annual Sum or Average | 0.210210E+10 | 0.779315E+09 | 0.132279E+10 | 0.420209E+10 | 0.104689E+10 |
| Minimum of Months | 0.134821E+09 | 25874433.90 | 81457844.71 | 0.139069E+09 | 335902.35 |
| Maximum of Months | 0.242579E+09 | 0.111771E+09 | 0.135025E+09 | 0.604689E+09 | 0.248477E+09 |
Report: WindowEnergyReportMonthly
For: MWINDOW1 E NEA
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.140190E+09 | 56539698.18 | 83650121.12 | 0.151801E+09 | 0.230705E+09 |
| February | 0.153254E+09 | 63094222.38 | 90159425.42 | 0.203094E+09 | 0.164421E+09 |
| March | 0.207203E+09 | 85422598.17 | 0.121780E+09 | 0.345797E+09 | 0.102293E+09 |
| April | 0.239284E+09 | 0.111771E+09 | 0.127513E+09 | 0.508648E+09 | 28754281.15 |
| May | 0.242579E+09 | 0.107554E+09 | 0.135025E+09 | 0.605309E+09 | 2673760.39 |
| June | 0.190973E+09 | 63337525.82 | 0.127635E+09 | 0.530832E+09 | 2465284.22 |
| July | 0.165663E+09 | 34801893.95 | 0.130861E+09 | 0.459200E+09 | 337470.80 |
| August | 0.149413E+09 | 25874433.90 | 0.123538E+09 | 0.385039E+09 | 1023400.40 |
| September | 0.154194E+09 | 42735465.13 | 0.111459E+09 | 0.341950E+09 | 6367800.81 |
| October | 0.174871E+09 | 70715302.48 | 0.104156E+09 | 0.336754E+09 | 75079684.66 |
| November | 0.149658E+09 | 64104976.85 | 85553081.43 | 0.228164E+09 | 0.155118E+09 |
| December | 0.134821E+09 | 53363630.86 | 81457844.71 | 0.154709E+09 | 0.231361E+09 |
| Annual Sum or Average | 0.210210E+10 | 0.779315E+09 | 0.132279E+10 | 0.425130E+10 | 0.100060E+10 |
| Minimum of Months | 0.134821E+09 | 25874433.90 | 81457844.71 | 0.151801E+09 | 337470.80 |
| Maximum of Months | 0.242579E+09 | 0.111771E+09 | 0.135025E+09 | 0.605309E+09 | 0.231361E+09 |
Report: WindowEnergyReportMonthly
For: MWINDOW1 N NEA
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 99151823.08 | 0.00 | 99151823.08 | 58918457.05 | 0.388119E+09 |
| February | 0.106199E+09 | 0.00 | 0.106199E+09 | 0.101504E+09 | 0.273603E+09 |
| March | 0.141718E+09 | 13520.81 | 0.141704E+09 | 0.221661E+09 | 0.167532E+09 |
| April | 0.149133E+09 | 741838.03 | 0.148392E+09 | 0.384714E+09 | 44634812.27 |
| May | 0.170871E+09 | 5287419.98 | 0.165583E+09 | 0.563372E+09 | 4233968.74 |
| June | 0.170190E+09 | 5905759.23 | 0.164284E+09 | 0.588661E+09 | 3771632.00 |
| July | 0.174176E+09 | 2995006.13 | 0.171181E+09 | 0.554803E+09 | 517314.52 |
| August | 0.160176E+09 | 893198.87 | 0.159283E+09 | 0.463500E+09 | 1577946.90 |
| September | 0.137666E+09 | 17478.26 | 0.137648E+09 | 0.343865E+09 | 9770306.85 |
| October | 0.123225E+09 | 0.00 | 0.123225E+09 | 0.251754E+09 | 0.119390E+09 |
| November | 0.101006E+09 | 0.00 | 0.101006E+09 | 0.128116E+09 | 0.254360E+09 |
| December | 96724368.79 | 0.00 | 96724368.79 | 62836307.60 | 0.382048E+09 |
| Annual Sum or Average | 0.163024E+10 | 15854221.32 | 0.161438E+10 | 0.372370E+10 | 0.164956E+10 |
| Minimum of Months | 96724368.79 | 0.00 | 96724368.79 | 58918457.05 | 517314.52 |
| Maximum of Months | 0.174176E+09 | 5905759.23 | 0.171181E+09 | 0.588661E+09 | 0.388119E+09 |
Report: WindowEnergyReportMonthly
For: MWINDOW1 N N1A
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 99151823.08 | 0.00 | 99151823.08 | 56674972.49 | 0.404601E+09 |
| February | 0.106199E+09 | 0.00 | 0.106199E+09 | 0.101798E+09 | 0.280518E+09 |
| March | 0.141718E+09 | 13520.81 | 0.141704E+09 | 0.225329E+09 | 0.167698E+09 |
| April | 0.149133E+09 | 741838.03 | 0.148392E+09 | 0.392513E+09 | 43630475.41 |
| May | 0.170871E+09 | 5287419.98 | 0.165583E+09 | 0.574184E+09 | 3930698.84 |
| June | 0.170190E+09 | 5905759.23 | 0.164284E+09 | 0.598299E+09 | 3599050.58 |
| July | 0.174176E+09 | 2995006.13 | 0.171181E+09 | 0.563389E+09 | 508227.74 |
| August | 0.160176E+09 | 893198.87 | 0.159283E+09 | 0.470680E+09 | 1424707.09 |
| September | 0.137666E+09 | 17478.26 | 0.137648E+09 | 0.349656E+09 | 9192668.26 |
| October | 0.123225E+09 | 0.00 | 0.123225E+09 | 0.255800E+09 | 0.118802E+09 |
| November | 0.101006E+09 | 0.00 | 0.101006E+09 | 0.129643E+09 | 0.256998E+09 |
| December | 96724368.79 | 0.00 | 96724368.79 | 61230105.19 | 0.395846E+09 |
| Annual Sum or Average | 0.163024E+10 | 15854221.32 | 0.161438E+10 | 0.377920E+10 | 0.168675E+10 |
| Minimum of Months | 96724368.79 | 0.00 | 96724368.79 | 56674972.49 | 508227.74 |
| Maximum of Months | 0.174176E+09 | 5905759.23 | 0.171181E+09 | 0.598299E+09 | 0.404601E+09 |
Report: WindowEnergyReportMonthly
For: MWINDOW1 N N2A
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 99151823.08 | 0.00 | 99151823.08 | 56546401.52 | 0.404690E+09 |
| February | 0.106199E+09 | 0.00 | 0.106199E+09 | 0.101696E+09 | 0.280597E+09 |
| March | 0.141718E+09 | 13520.81 | 0.141704E+09 | 0.225284E+09 | 0.167683E+09 |
| April | 0.149133E+09 | 741838.03 | 0.148392E+09 | 0.392488E+09 | 43619591.18 |
| May | 0.170871E+09 | 5287419.98 | 0.165583E+09 | 0.574167E+09 | 3928033.03 |
| June | 0.170190E+09 | 5905759.23 | 0.164284E+09 | 0.598316E+09 | 3596728.32 |
| July | 0.174176E+09 | 2995006.13 | 0.171181E+09 | 0.563386E+09 | 508176.15 |
| August | 0.160176E+09 | 893198.87 | 0.159283E+09 | 0.470677E+09 | 1425033.11 |
| September | 0.137666E+09 | 17478.26 | 0.137648E+09 | 0.349656E+09 | 9187071.61 |
| October | 0.123225E+09 | 0.00 | 0.123225E+09 | 0.255773E+09 | 0.118790E+09 |
| November | 0.101006E+09 | 0.00 | 0.101006E+09 | 0.129603E+09 | 0.256986E+09 |
| December | 96724368.79 | 0.00 | 96724368.79 | 61128912.50 | 0.395922E+09 |
| Annual Sum or Average | 0.163024E+10 | 15854221.32 | 0.161438E+10 | 0.377872E+10 | 0.168693E+10 |
| Minimum of Months | 96724368.79 | 0.00 | 96724368.79 | 56546401.52 | 508176.15 |
| Maximum of Months | 0.174176E+09 | 5905759.23 | 0.171181E+09 | 0.598316E+09 | 0.404690E+09 |
Report: WindowEnergyReportMonthly
For: MWINDOW1 S S1A
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.448261E+09 | 0.271309E+09 | 0.176952E+09 | 0.617305E+09 | 0.384726E+09 |
| February | 0.390780E+09 | 0.218583E+09 | 0.172197E+09 | 0.591927E+09 | 0.268935E+09 |
| March | 0.357330E+09 | 0.152663E+09 | 0.204667E+09 | 0.641252E+09 | 0.167460E+09 |
| April | 0.256767E+09 | 77806700.21 | 0.178961E+09 | 0.626221E+09 | 46097157.69 |
| May | 0.185984E+09 | 14437677.05 | 0.171546E+09 | 0.613136E+09 | 3853428.15 |
| June | 0.164493E+09 | 3353335.34 | 0.161140E+09 | 0.588026E+09 | 3619921.66 |
| July | 0.176248E+09 | 1962822.04 | 0.174285E+09 | 0.570243E+09 | 512446.78 |
| August | 0.185183E+09 | 7763252.03 | 0.177420E+09 | 0.522116E+09 | 1464248.60 |
| September | 0.251278E+09 | 71196446.15 | 0.180081E+09 | 0.571172E+09 | 9929195.72 |
| October | 0.428869E+09 | 0.237960E+09 | 0.190909E+09 | 0.823758E+09 | 0.119719E+09 |
| November | 0.524493E+09 | 0.347337E+09 | 0.177156E+09 | 0.869564E+09 | 0.248889E+09 |
| December | 0.480605E+09 | 0.300743E+09 | 0.179862E+09 | 0.692065E+09 | 0.372043E+09 |
| Annual Sum or Average | 0.385029E+10 | 0.170512E+10 | 0.214517E+10 | 0.772679E+10 | 0.162725E+10 |
| Minimum of Months | 0.164493E+09 | 1962822.04 | 0.161140E+09 | 0.522116E+09 | 512446.78 |
| Maximum of Months | 0.524493E+09 | 0.347337E+09 | 0.204667E+09 | 0.869564E+09 | 0.384726E+09 |
Report: WindowEnergyReportMonthly
For: MWINDOW1 S S2A
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.448261E+09 | 0.271309E+09 | 0.176952E+09 | 0.617241E+09 | 0.384726E+09 |
| February | 0.390780E+09 | 0.218583E+09 | 0.172197E+09 | 0.591882E+09 | 0.268932E+09 |
| March | 0.357330E+09 | 0.152663E+09 | 0.204667E+09 | 0.641216E+09 | 0.167442E+09 |
| April | 0.256767E+09 | 77806700.21 | 0.178961E+09 | 0.626198E+09 | 46085504.67 |
| May | 0.185984E+09 | 14437677.05 | 0.171546E+09 | 0.613120E+09 | 3850741.01 |
| June | 0.164493E+09 | 3353335.34 | 0.161140E+09 | 0.588044E+09 | 3617556.10 |
| July | 0.176248E+09 | 1962822.04 | 0.174285E+09 | 0.570241E+09 | 512392.97 |
| August | 0.185183E+09 | 7763252.03 | 0.177420E+09 | 0.522113E+09 | 1464589.34 |
| September | 0.251278E+09 | 71196446.15 | 0.180081E+09 | 0.571171E+09 | 9923450.08 |
| October | 0.428869E+09 | 0.237960E+09 | 0.190909E+09 | 0.823736E+09 | 0.119706E+09 |
| November | 0.524493E+09 | 0.347337E+09 | 0.177156E+09 | 0.869540E+09 | 0.248871E+09 |
| December | 0.480605E+09 | 0.300743E+09 | 0.179862E+09 | 0.692026E+09 | 0.372030E+09 |
| Annual Sum or Average | 0.385029E+10 | 0.170512E+10 | 0.214517E+10 | 0.772653E+10 | 0.162716E+10 |
| Minimum of Months | 0.164493E+09 | 1962822.04 | 0.161140E+09 | 0.522113E+09 | 512392.97 |
| Maximum of Months | 0.524493E+09 | 0.347337E+09 | 0.204667E+09 | 0.869540E+09 | 0.384726E+09 |
Report: WindowEnergyReportMonthly
For: TWINDOW1 S SWA
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.448261E+09 | 0.271309E+09 | 0.176952E+09 | 0.636022E+09 | 0.326899E+09 |
| February | 0.390780E+09 | 0.218583E+09 | 0.172197E+09 | 0.599880E+09 | 0.233631E+09 |
| March | 0.357330E+09 | 0.152663E+09 | 0.204667E+09 | 0.632664E+09 | 0.156997E+09 |
| April | 0.256767E+09 | 77806700.21 | 0.178961E+09 | 0.604435E+09 | 44970268.18 |
| May | 0.185984E+09 | 14437677.05 | 0.171546E+09 | 0.584054E+09 | 3964161.56 |
| June | 0.164493E+09 | 3353335.34 | 0.161140E+09 | 0.558337E+09 | 3846205.36 |
| July | 0.176248E+09 | 1962822.04 | 0.174285E+09 | 0.543902E+09 | 490031.77 |
| August | 0.185183E+09 | 7763252.03 | 0.177420E+09 | 0.499629E+09 | 1597329.42 |
| September | 0.251278E+09 | 71196446.15 | 0.180081E+09 | 0.552825E+09 | 9931611.17 |
| October | 0.428869E+09 | 0.237960E+09 | 0.190909E+09 | 0.810765E+09 | 0.114678E+09 |
| November | 0.524493E+09 | 0.347337E+09 | 0.177156E+09 | 0.869267E+09 | 0.225973E+09 |
| December | 0.480605E+09 | 0.300743E+09 | 0.179862E+09 | 0.709621E+09 | 0.319125E+09 |
| Annual Sum or Average | 0.385029E+10 | 0.170512E+10 | 0.214517E+10 | 0.760140E+10 | 0.144210E+10 |
| Minimum of Months | 0.164493E+09 | 1962822.04 | 0.161140E+09 | 0.499629E+09 | 490031.77 |
| Maximum of Months | 0.524493E+09 | 0.347337E+09 | 0.204667E+09 | 0.869267E+09 | 0.326899E+09 |
Report: WindowEnergyReportMonthly
For: TWINDOW1 W SWA
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.136699E+09 | 53149103.01 | 83549429.80 | 0.155612E+09 | 0.231557E+09 |
| February | 0.141033E+09 | 51891941.89 | 89140842.82 | 0.190632E+09 | 0.160873E+09 |
| March | 0.203543E+09 | 81795576.77 | 0.121747E+09 | 0.336928E+09 | 0.104114E+09 |
| April | 0.238074E+09 | 0.111439E+09 | 0.126635E+09 | 0.494820E+09 | 28820435.93 |
| May | 0.233028E+09 | 98688978.79 | 0.134339E+09 | 0.576666E+09 | 2697856.75 |
| June | 0.212729E+09 | 83043153.64 | 0.129686E+09 | 0.557303E+09 | 2472499.90 |
| July | 0.162517E+09 | 31519774.07 | 0.130997E+09 | 0.438885E+09 | 341408.76 |
| August | 0.149019E+09 | 26155339.21 | 0.122864E+09 | 0.373919E+09 | 1070120.51 |
| September | 0.159292E+09 | 47133868.37 | 0.112158E+09 | 0.340274E+09 | 6424221.35 |
| October | 0.170857E+09 | 67979562.24 | 0.102878E+09 | 0.321832E+09 | 76582429.96 |
| November | 0.149559E+09 | 63710905.93 | 85848488.14 | 0.231484E+09 | 0.154540E+09 |
| December | 0.132416E+09 | 50570362.82 | 81845224.19 | 0.156843E+09 | 0.221712E+09 |
| Annual Sum or Average | 0.208877E+10 | 0.767078E+09 | 0.132169E+10 | 0.417520E+10 | 0.991205E+09 |
| Minimum of Months | 0.132416E+09 | 26155339.21 | 81845224.19 | 0.155612E+09 | 341408.76 |
| Maximum of Months | 0.238074E+09 | 0.111439E+09 | 0.134339E+09 | 0.576666E+09 | 0.231557E+09 |
Report: WindowEnergyReportMonthly
For: TWINDOW1 W NWA
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.136699E+09 | 53149103.01 | 83549429.80 | 0.170346E+09 | 0.219009E+09 |
| February | 0.141033E+09 | 51891941.89 | 89140842.82 | 0.200497E+09 | 0.154637E+09 |
| March | 0.203543E+09 | 81795576.77 | 0.121747E+09 | 0.343173E+09 | 0.101631E+09 |
| April | 0.238074E+09 | 0.111439E+09 | 0.126635E+09 | 0.498364E+09 | 28371479.89 |
| May | 0.233028E+09 | 98688978.79 | 0.134339E+09 | 0.577396E+09 | 2686553.04 |
| June | 0.212729E+09 | 83043153.64 | 0.129686E+09 | 0.557227E+09 | 2464976.92 |
| July | 0.162517E+09 | 31519774.07 | 0.130997E+09 | 0.438908E+09 | 342409.69 |
| August | 0.149019E+09 | 26155339.21 | 0.122864E+09 | 0.374749E+09 | 1063782.65 |
| September | 0.159292E+09 | 47133868.37 | 0.112158E+09 | 0.343463E+09 | 6184248.36 |
| October | 0.170857E+09 | 67979562.24 | 0.102878E+09 | 0.328996E+09 | 74363579.35 |
| November | 0.149559E+09 | 63710905.93 | 85848488.14 | 0.242712E+09 | 0.147921E+09 |
| December | 0.132416E+09 | 50570362.82 | 81845224.19 | 0.171917E+09 | 0.209336E+09 |
| Annual Sum or Average | 0.208877E+10 | 0.767078E+09 | 0.132169E+10 | 0.424775E+10 | 0.948011E+09 |
| Minimum of Months | 0.132416E+09 | 26155339.21 | 81845224.19 | 0.170346E+09 | 342409.69 |
| Maximum of Months | 0.238074E+09 | 0.111439E+09 | 0.134339E+09 | 0.577396E+09 | 0.219009E+09 |
Report: WindowEnergyReportMonthly
For: TWINDOW1 N NWA
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 99151823.08 | 0.00 | 99151823.08 | 70164034.69 | 0.342815E+09 |
| February | 0.106199E+09 | 0.00 | 0.106199E+09 | 0.111184E+09 | 0.239015E+09 |
| March | 0.141718E+09 | 13520.81 | 0.141704E+09 | 0.219297E+09 | 0.155704E+09 |
| April | 0.149133E+09 | 741838.03 | 0.148392E+09 | 0.371653E+09 | 42743303.57 |
| May | 0.170871E+09 | 5287419.98 | 0.165583E+09 | 0.545062E+09 | 4086872.69 |
| June | 0.170190E+09 | 5905759.23 | 0.164284E+09 | 0.568596E+09 | 3801785.09 |
| July | 0.174176E+09 | 2995006.13 | 0.171181E+09 | 0.537119E+09 | 483712.51 |
| August | 0.160176E+09 | 893198.87 | 0.159283E+09 | 0.448235E+09 | 1539273.00 |
| September | 0.137666E+09 | 17478.26 | 0.137648E+09 | 0.332244E+09 | 9351679.66 |
| October | 0.123225E+09 | 0.00 | 0.123225E+09 | 0.245341E+09 | 0.113638E+09 |
| November | 0.101006E+09 | 0.00 | 0.101006E+09 | 0.133538E+09 | 0.227484E+09 |
| December | 96724368.79 | 0.00 | 96724368.79 | 77895460.80 | 0.328791E+09 |
| Annual Sum or Average | 0.163024E+10 | 15854221.32 | 0.161438E+10 | 0.366033E+10 | 0.146945E+10 |
| Minimum of Months | 96724368.79 | 0.00 | 96724368.79 | 70164034.69 | 483712.51 |
| Maximum of Months | 0.174176E+09 | 5905759.23 | 0.171181E+09 | 0.568596E+09 | 0.342815E+09 |
Report: WindowEnergyReportMonthly
For: TWINDOW1 S SEA
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.448261E+09 | 0.271309E+09 | 0.176952E+09 | 0.632145E+09 | 0.325204E+09 |
| February | 0.390780E+09 | 0.218583E+09 | 0.172197E+09 | 0.596338E+09 | 0.232555E+09 |
| March | 0.357330E+09 | 0.152663E+09 | 0.204667E+09 | 0.630179E+09 | 0.155700E+09 |
| April | 0.256767E+09 | 77806700.21 | 0.178961E+09 | 0.603471E+09 | 44416622.29 |
| May | 0.185984E+09 | 14437677.05 | 0.171546E+09 | 0.583429E+09 | 3870181.22 |
| June | 0.164493E+09 | 3353335.34 | 0.161140E+09 | 0.558923E+09 | 3775595.47 |
| July | 0.176248E+09 | 1962822.04 | 0.174285E+09 | 0.543825E+09 | 490268.26 |
| August | 0.185183E+09 | 7763252.03 | 0.177420E+09 | 0.499544E+09 | 1597168.60 |
| September | 0.251278E+09 | 71196446.15 | 0.180081E+09 | 0.552763E+09 | 9744400.78 |
| October | 0.428869E+09 | 0.237960E+09 | 0.190909E+09 | 0.809446E+09 | 0.113847E+09 |
| November | 0.524493E+09 | 0.347337E+09 | 0.177156E+09 | 0.866960E+09 | 0.224590E+09 |
| December | 0.480605E+09 | 0.300743E+09 | 0.179862E+09 | 0.706135E+09 | 0.317507E+09 |
| Annual Sum or Average | 0.385029E+10 | 0.170512E+10 | 0.214517E+10 | 0.758316E+10 | 0.143330E+10 |
| Minimum of Months | 0.164493E+09 | 1962822.04 | 0.161140E+09 | 0.499544E+09 | 490268.26 |
| Maximum of Months | 0.524493E+09 | 0.347337E+09 | 0.204667E+09 | 0.866960E+09 | 0.325204E+09 |
Report: WindowEnergyReportMonthly
For: TWINDOW1 E SEA
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.140190E+09 | 56539698.18 | 83650121.12 | 0.148424E+09 | 0.218260E+09 |
| February | 0.153254E+09 | 63094222.38 | 90159425.42 | 0.201757E+09 | 0.151525E+09 |
| March | 0.207203E+09 | 85422598.17 | 0.121780E+09 | 0.338127E+09 | 97977097.41 |
| April | 0.239284E+09 | 0.111771E+09 | 0.127513E+09 | 0.495622E+09 | 27799370.08 |
| May | 0.242579E+09 | 0.107554E+09 | 0.135025E+09 | 0.591544E+09 | 2516314.84 |
| June | 0.190973E+09 | 63337525.82 | 0.127635E+09 | 0.517701E+09 | 2455231.63 |
| July | 0.165663E+09 | 34801893.95 | 0.130861E+09 | 0.447138E+09 | 313781.39 |
| August | 0.149413E+09 | 25874433.90 | 0.123538E+09 | 0.373848E+09 | 996973.77 |
| September | 0.154194E+09 | 42735465.13 | 0.111459E+09 | 0.330871E+09 | 6245056.13 |
| October | 0.174871E+09 | 70715302.48 | 0.104156E+09 | 0.325075E+09 | 73569436.46 |
| November | 0.149658E+09 | 64104976.85 | 85553081.43 | 0.222447E+09 | 0.146531E+09 |
| December | 0.134821E+09 | 53363630.86 | 81457844.71 | 0.154702E+09 | 0.214592E+09 |
| Annual Sum or Average | 0.210210E+10 | 0.779315E+09 | 0.132279E+10 | 0.414726E+10 | 0.942780E+09 |
| Minimum of Months | 0.134821E+09 | 25874433.90 | 81457844.71 | 0.148424E+09 | 313781.39 |
| Maximum of Months | 0.242579E+09 | 0.111771E+09 | 0.135025E+09 | 0.591544E+09 | 0.218260E+09 |
Report: WindowEnergyReportMonthly
For: TWINDOW1 E NEA
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.140190E+09 | 56539698.18 | 83650121.12 | 0.162273E+09 | 0.203526E+09 |
| February | 0.153254E+09 | 63094222.38 | 90159425.42 | 0.211131E+09 | 0.145204E+09 |
| March | 0.207203E+09 | 85422598.17 | 0.121780E+09 | 0.344192E+09 | 95610968.28 |
| April | 0.239284E+09 | 0.111771E+09 | 0.127513E+09 | 0.499173E+09 | 27347799.14 |
| May | 0.242579E+09 | 0.107554E+09 | 0.135025E+09 | 0.592314E+09 | 2506016.30 |
| June | 0.190973E+09 | 63337525.82 | 0.127635E+09 | 0.517640E+09 | 2447766.03 |
| July | 0.165663E+09 | 34801893.95 | 0.130861E+09 | 0.447170E+09 | 315005.64 |
| August | 0.149413E+09 | 25874433.90 | 0.123538E+09 | 0.374682E+09 | 990589.58 |
| September | 0.154194E+09 | 42735465.13 | 0.111459E+09 | 0.334068E+09 | 6006637.35 |
| October | 0.174871E+09 | 70715302.48 | 0.104156E+09 | 0.332200E+09 | 71418707.34 |
| November | 0.149658E+09 | 64104976.85 | 85553081.43 | 0.233299E+09 | 0.139881E+09 |
| December | 0.134821E+09 | 53363630.86 | 81457844.71 | 0.168004E+09 | 0.200063E+09 |
| Annual Sum or Average | 0.210210E+10 | 0.779315E+09 | 0.132279E+10 | 0.421614E+10 | 0.895317E+09 |
| Minimum of Months | 0.134821E+09 | 25874433.90 | 81457844.71 | 0.162273E+09 | 315005.64 |
| Maximum of Months | 0.242579E+09 | 0.111771E+09 | 0.135025E+09 | 0.592314E+09 | 0.203526E+09 |
Report: WindowEnergyReportMonthly
For: TWINDOW1 N NEA
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 99151823.08 | 0.00 | 99151823.08 | 67176224.82 | 0.339734E+09 |
| February | 0.106199E+09 | 0.00 | 0.106199E+09 | 0.107142E+09 | 0.238041E+09 |
| March | 0.141718E+09 | 13520.81 | 0.141704E+09 | 0.216525E+09 | 0.154486E+09 |
| April | 0.149133E+09 | 741838.03 | 0.148392E+09 | 0.370652E+09 | 42210035.65 |
| May | 0.170871E+09 | 5287419.98 | 0.165583E+09 | 0.544447E+09 | 3991843.07 |
| June | 0.170190E+09 | 5905759.23 | 0.164284E+09 | 0.569187E+09 | 3738837.87 |
| July | 0.174176E+09 | 2995006.13 | 0.171181E+09 | 0.537045E+09 | 483947.46 |
| August | 0.160176E+09 | 893198.87 | 0.159283E+09 | 0.448124E+09 | 1538924.40 |
| September | 0.137666E+09 | 17478.26 | 0.137648E+09 | 0.332189E+09 | 9173523.13 |
| October | 0.123225E+09 | 0.00 | 0.123225E+09 | 0.243943E+09 | 0.112837E+09 |
| November | 0.101006E+09 | 0.00 | 0.101006E+09 | 0.130493E+09 | 0.226068E+09 |
| December | 96724368.79 | 0.00 | 96724368.79 | 74276062.42 | 0.326196E+09 |
| Annual Sum or Average | 0.163024E+10 | 15854221.32 | 0.161438E+10 | 0.364120E+10 | 0.145850E+10 |
| Minimum of Months | 96724368.79 | 0.00 | 96724368.79 | 67176224.82 | 483947.46 |
| Maximum of Months | 0.174176E+09 | 5905759.23 | 0.171181E+09 | 0.569187E+09 | 0.339734E+09 |
Report: WindowEnergyReportMonthly
For: TWINDOW1 N N1A
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 99151823.08 | 0.00 | 99151823.08 | 70074720.60 | 0.348319E+09 |
| February | 0.106199E+09 | 0.00 | 0.106199E+09 | 0.110953E+09 | 0.245275E+09 |
| March | 0.141718E+09 | 13520.81 | 0.141704E+09 | 0.222350E+09 | 0.157996E+09 |
| April | 0.149133E+09 | 741838.03 | 0.148392E+09 | 0.380925E+09 | 42074525.73 |
| May | 0.170871E+09 | 5287419.98 | 0.165583E+09 | 0.557590E+09 | 3846949.02 |
| June | 0.170190E+09 | 5905759.23 | 0.164284E+09 | 0.580827E+09 | 3697332.06 |
| July | 0.174176E+09 | 2995006.13 | 0.171181E+09 | 0.547285E+09 | 484526.43 |
| August | 0.160176E+09 | 893198.87 | 0.159283E+09 | 0.456785E+09 | 1451306.47 |
| September | 0.137666E+09 | 17478.26 | 0.137648E+09 | 0.339481E+09 | 8928905.75 |
| October | 0.123225E+09 | 0.00 | 0.123225E+09 | 0.249900E+09 | 0.113985E+09 |
| November | 0.101006E+09 | 0.00 | 0.101006E+09 | 0.134008E+09 | 0.233031E+09 |
| December | 96724368.79 | 0.00 | 96724368.79 | 77389816.54 | 0.334467E+09 |
| Annual Sum or Average | 0.163024E+10 | 15854221.32 | 0.161438E+10 | 0.372757E+10 | 0.149356E+10 |
| Minimum of Months | 96724368.79 | 0.00 | 96724368.79 | 70074720.60 | 484526.43 |
| Maximum of Months | 0.174176E+09 | 5905759.23 | 0.171181E+09 | 0.580827E+09 | 0.348319E+09 |
Report: WindowEnergyReportMonthly
For: TWINDOW1 N N2A
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 99151823.08 | 0.00 | 99151823.08 | 69829068.66 | 0.348096E+09 |
| February | 0.106199E+09 | 0.00 | 0.106199E+09 | 0.110646E+09 | 0.245251E+09 |
| March | 0.141718E+09 | 13520.81 | 0.141704E+09 | 0.222181E+09 | 0.157926E+09 |
| April | 0.149133E+09 | 741838.03 | 0.148392E+09 | 0.380870E+09 | 42043593.82 |
| May | 0.170871E+09 | 5287419.98 | 0.165583E+09 | 0.557563E+09 | 3841200.85 |
| June | 0.170190E+09 | 5905759.23 | 0.164284E+09 | 0.580848E+09 | 3693438.48 |
| July | 0.174176E+09 | 2995006.13 | 0.171181E+09 | 0.547283E+09 | 484513.53 |
| August | 0.160176E+09 | 893198.87 | 0.159283E+09 | 0.456780E+09 | 1451347.50 |
| September | 0.137666E+09 | 17478.26 | 0.137648E+09 | 0.339475E+09 | 8917978.17 |
| October | 0.123225E+09 | 0.00 | 0.123225E+09 | 0.249824E+09 | 0.113940E+09 |
| November | 0.101006E+09 | 0.00 | 0.101006E+09 | 0.133809E+09 | 0.232953E+09 |
| December | 96724368.79 | 0.00 | 96724368.79 | 77110979.11 | 0.334317E+09 |
| Annual Sum or Average | 0.163024E+10 | 15854221.32 | 0.161438E+10 | 0.372622E+10 | 0.149292E+10 |
| Minimum of Months | 96724368.79 | 0.00 | 96724368.79 | 69829068.66 | 484513.53 |
| Maximum of Months | 0.174176E+09 | 5905759.23 | 0.171181E+09 | 0.580848E+09 | 0.348096E+09 |
Report: WindowEnergyReportMonthly
For: TWINDOW1 S S1A
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.448261E+09 | 0.271309E+09 | 0.176952E+09 | 0.632673E+09 | 0.336928E+09 |
| February | 0.390780E+09 | 0.218583E+09 | 0.172197E+09 | 0.597924E+09 | 0.240956E+09 |
| March | 0.357330E+09 | 0.152663E+09 | 0.204667E+09 | 0.635005E+09 | 0.159163E+09 |
| April | 0.256767E+09 | 77806700.21 | 0.178961E+09 | 0.612934E+09 | 44291506.89 |
| May | 0.185984E+09 | 14437677.05 | 0.171546E+09 | 0.596421E+09 | 3727204.46 |
| June | 0.164493E+09 | 3353335.34 | 0.161140E+09 | 0.570561E+09 | 3731368.09 |
| July | 0.176248E+09 | 1962822.04 | 0.174285E+09 | 0.554165E+09 | 490425.30 |
| August | 0.185183E+09 | 7763252.03 | 0.177420E+09 | 0.508025E+09 | 1499406.93 |
| September | 0.251278E+09 | 71196446.15 | 0.180081E+09 | 0.559541E+09 | 9507750.16 |
| October | 0.428869E+09 | 0.237960E+09 | 0.190909E+09 | 0.814456E+09 | 0.115002E+09 |
| November | 0.524493E+09 | 0.347337E+09 | 0.177156E+09 | 0.868437E+09 | 0.231563E+09 |
| December | 0.480605E+09 | 0.300743E+09 | 0.179862E+09 | 0.706167E+09 | 0.329214E+09 |
| Annual Sum or Average | 0.385029E+10 | 0.170512E+10 | 0.214517E+10 | 0.765631E+10 | 0.147607E+10 |
| Minimum of Months | 0.164493E+09 | 1962822.04 | 0.161140E+09 | 0.508025E+09 | 490425.30 |
| Maximum of Months | 0.524493E+09 | 0.347337E+09 | 0.204667E+09 | 0.868437E+09 | 0.336928E+09 |
Report: WindowEnergyReportMonthly
For: TWINDOW1 S S2A
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.448261E+09 | 0.271309E+09 | 0.176952E+09 | 0.632420E+09 | 0.336838E+09 |
| February | 0.390780E+09 | 0.218583E+09 | 0.172197E+09 | 0.597728E+09 | 0.240901E+09 |
| March | 0.357330E+09 | 0.152663E+09 | 0.204667E+09 | 0.634881E+09 | 0.159091E+09 |
| April | 0.256767E+09 | 77806700.21 | 0.178961E+09 | 0.612885E+09 | 44259812.08 |
| May | 0.185984E+09 | 14437677.05 | 0.171546E+09 | 0.596394E+09 | 3721402.07 |
| June | 0.164493E+09 | 3353335.34 | 0.161140E+09 | 0.570583E+09 | 3727114.17 |
| July | 0.176248E+09 | 1962822.04 | 0.174285E+09 | 0.554162E+09 | 490411.25 |
| August | 0.185183E+09 | 7763252.03 | 0.177420E+09 | 0.508021E+09 | 1499461.03 |
| September | 0.251278E+09 | 71196446.15 | 0.180081E+09 | 0.559536E+09 | 9496748.37 |
| October | 0.428869E+09 | 0.237960E+09 | 0.190909E+09 | 0.814397E+09 | 0.114958E+09 |
| November | 0.524493E+09 | 0.347337E+09 | 0.177156E+09 | 0.868333E+09 | 0.231480E+09 |
| December | 0.480605E+09 | 0.300743E+09 | 0.179862E+09 | 0.705970E+09 | 0.329115E+09 |
| Annual Sum or Average | 0.385029E+10 | 0.170512E+10 | 0.214517E+10 | 0.765531E+10 | 0.147558E+10 |
| Minimum of Months | 0.164493E+09 | 1962822.04 | 0.161140E+09 | 0.508021E+09 | 490411.25 |
| Maximum of Months | 0.524493E+09 | 0.347337E+09 | 0.204667E+09 | 0.868333E+09 | 0.336838E+09 |
Report: WindowEnergyReportMonthly
For: TWINDOW14
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 33639117.77 | 13566930.72 | 20072187.05 | 36693158.65 | 56062346.11 |
| February | 36773836.59 | 15139715.48 | 21634121.11 | 48252064.13 | 40750688.74 |
| March | 49719189.67 | 20497500.13 | 29221689.54 | 78732901.62 | 28121378.10 |
| April | 57417101.96 | 26819896.19 | 30597205.77 | 0.113240E+09 | 9782443.09 |
| May | 58207818.60 | 25808017.15 | 32399801.45 | 0.132099E+09 | 1671597.26 |
| June | 45824639.87 | 15198097.13 | 30626542.74 | 0.113957E+09 | 1443598.01 |
| July | 39751489.86 | 8350856.11 | 31400633.75 | 96241970.20 | 322155.85 |
| August | 35852171.33 | 6208675.73 | 29643495.59 | 80293751.62 | 1267335.18 |
| September | 36999575.50 | 10254548.81 | 26745026.69 | 73152819.84 | 4481931.09 |
| October | 41960976.56 | 16968424.67 | 24992551.89 | 75504398.95 | 22220494.88 |
| November | 35911060.25 | 15382250.13 | 20528810.12 | 53230212.19 | 39673256.23 |
| December | 32350961.84 | 12804820.44 | 19546141.40 | 38147336.18 | 55374051.42 |
| Annual Sum or Average | 0.504408E+09 | 0.187000E+09 | 0.317408E+09 | 0.939545E+09 | 0.261171E+09 |
| Minimum of Months | 32350961.84 | 6208675.73 | 19546141.40 | 36693158.65 | 322155.85 |
| Maximum of Months | 58207818.60 | 26819896.19 | 32399801.45 | 0.132099E+09 | 56062346.11 |
Report: WindowEnergyReportMonthly
For: ENTRANCE DOOR
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.100186E+09 | 40405695.99 | 59779968.27 | 0.104522E+09 | 0.175950E+09 |
| February | 0.109522E+09 | 45089840.41 | 64431796.61 | 0.140352E+09 | 0.127066E+09 |
| March | 0.148076E+09 | 61046656.47 | 87029463.66 | 0.232488E+09 | 87332306.59 |
| April | 0.171002E+09 | 79876325.33 | 91126093.31 | 0.328950E+09 | 34142839.78 |
| May | 0.173357E+09 | 76862697.73 | 96494671.85 | 0.375916E+09 | 8820301.73 |
| June | 0.136477E+09 | 45263715.50 | 91213466.10 | 0.320022E+09 | 6826228.95 |
| July | 0.118390E+09 | 24870927.72 | 93518901.77 | 0.267619E+09 | 2758403.92 |
| August | 0.106777E+09 | 18490981.45 | 88285707.06 | 0.224294E+09 | 7515115.81 |
| September | 0.110194E+09 | 30540598.33 | 79653345.35 | 0.206721E+09 | 21728561.96 |
| October | 0.124970E+09 | 50536191.48 | 74434039.26 | 0.216057E+09 | 76499363.29 |
| November | 0.106952E+09 | 45812168.96 | 61139905.42 | 0.150425E+09 | 0.129787E+09 |
| December | 96349215.33 | 38135941.91 | 58213273.42 | 0.103652E+09 | 0.181098E+09 |
| Annual Sum or Average | 0.150225E+10 | 0.556932E+09 | 0.945321E+09 | 0.267102E+10 | 0.859524E+09 |
| Minimum of Months | 96349215.33 | 18490981.45 | 58213273.42 | 0.103652E+09 | 2758403.92 |
| Maximum of Months | 0.173357E+09 | 79876325.33 | 96494671.85 | 0.375916E+09 | 0.181098E+09 |
Report: WindowEnergyReportMonthly
For: MWINDOW14
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 33639117.77 | 13566930.72 | 20072187.05 | 31654072.95 | 64736393.16 |
| February | 36773836.59 | 15139715.48 | 21634121.11 | 44581575.35 | 46027080.51 |
| March | 49719189.67 | 20497500.13 | 29221689.54 | 77689292.81 | 29855603.71 |
| April | 57417101.96 | 26819896.19 | 30597205.77 | 0.115012E+09 | 10073946.82 |
| May | 58207818.60 | 25808017.15 | 32399801.45 | 0.135608E+09 | 1648088.88 |
| June | 45824639.87 | 15198097.13 | 30626542.74 | 0.117791E+09 | 1353401.39 |
| July | 39751489.86 | 8350856.11 | 31400633.75 | 99986618.05 | 300140.80 |
| August | 35852171.33 | 6208675.73 | 29643495.59 | 83241793.15 | 1161603.30 |
| September | 36999575.50 | 10254548.81 | 26745026.69 | 74843939.93 | 4375065.97 |
| October | 41960976.56 | 16968424.67 | 24992551.89 | 75584992.00 | 23178432.65 |
| November | 35911060.25 | 15382250.13 | 20528810.12 | 50533658.70 | 43508668.60 |
| December | 32350961.84 | 12804820.44 | 19546141.40 | 32924839.46 | 64115181.22 |
| Annual Sum or Average | 0.504408E+09 | 0.187000E+09 | 0.317408E+09 | 0.939452E+09 | 0.290334E+09 |
| Minimum of Months | 32350961.84 | 6208675.73 | 19546141.40 | 31654072.95 | 300140.80 |
| Maximum of Months | 58207818.60 | 26819896.19 | 32399801.45 | 0.135608E+09 | 64736393.16 |
Report: WindowZoneSummaryMonthly
For: G SW APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 287.72 | 231.50 | 218.40 | 121.14 | 97.26 | 0.00 | 0.00 |
| February | 325.36 | 178.92 | 219.83 | 111.80 | 108.03 | 0.00 | 0.00 |
| March | 369.51 | 101.50 | 209.41 | 87.54 | 121.87 | 0.00 | 0.00 |
| April | 435.89 | 29.46 | 190.91 | 73.01 | 117.90 | 0.00 | 0.00 |
| May | 442.90 | 2.76 | 156.44 | 42.24 | 114.20 | 0.00 | 0.00 |
| June | 438.09 | 2.69 | 145.53 | 33.33 | 112.20 | 0.00 | 0.00 |
| July | 370.01 | 0.42 | 126.48 | 12.50 | 113.98 | 0.00 | 0.00 |
| August | 327.34 | 1.68 | 124.78 | 12.66 | 112.11 | 0.00 | 0.00 |
| September | 346.41 | 9.54 | 158.40 | 45.65 | 112.75 | 0.00 | 0.00 |
| October | 426.72 | 79.39 | 223.91 | 114.22 | 109.69 | 0.00 | 0.00 |
| November | 423.40 | 163.07 | 260.05 | 158.58 | 101.47 | 0.00 | 0.00 |
| December | 312.66 | 230.37 | 228.88 | 131.17 | 97.71 | 0.00 | 0.00 |
| Annual Sum or Average | 375.53 | 85.56 | 188.33 | 78.39 | 109.93 | 0.00 | 0.00 |
| Minimum of Months | 287.72 | 0.42 | 124.78 | 12.50 | 97.26 | 0.00 | 0.00 |
| Maximum of Months | 442.90 | 231.50 | 260.05 | 158.58 | 121.87 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: G NW APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 83.80 | 229.02 | 88.06 | 19.84 | 68.21 | 0.00 | 0.00 |
| February | 127.13 | 176.32 | 102.20 | 21.45 | 80.75 | 0.00 | 0.00 |
| March | 215.85 | 99.54 | 128.91 | 30.54 | 98.36 | 0.00 | 0.00 |
| April | 346.16 | 28.00 | 149.39 | 43.28 | 106.11 | 0.00 | 0.00 |
| May | 428.47 | 2.77 | 150.80 | 38.82 | 111.98 | 0.00 | 0.00 |
| June | 441.92 | 2.70 | 147.73 | 34.32 | 113.41 | 0.00 | 0.00 |
| July | 367.52 | 0.43 | 125.71 | 12.89 | 112.82 | 0.00 | 0.00 |
| August | 308.16 | 1.65 | 115.44 | 10.10 | 105.34 | 0.00 | 0.00 |
| September | 261.11 | 8.94 | 114.57 | 18.19 | 96.38 | 0.00 | 0.00 |
| October | 215.76 | 77.93 | 109.80 | 25.38 | 84.42 | 0.00 | 0.00 |
| November | 140.53 | 164.77 | 96.67 | 24.58 | 72.09 | 0.00 | 0.00 |
| December | 80.44 | 233.72 | 85.55 | 18.88 | 66.67 | 0.00 | 0.00 |
| Annual Sum or Average | 251.92 | 85.11 | 117.93 | 24.83 | 93.10 | 0.00 | 0.00 |
| Minimum of Months | 80.44 | 0.43 | 85.55 | 10.10 | 66.67 | 0.00 | 0.00 |
| Maximum of Months | 441.92 | 233.72 | 150.80 | 43.28 | 113.41 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: OFFICE
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 280.25 | 241.04 | 219.70 | 122.40 | 97.30 | 0.00 | 0.00 |
| February | 319.49 | 196.86 | 224.88 | 116.43 | 108.45 | 0.00 | 0.00 |
| March | 350.80 | 127.57 | 210.77 | 88.89 | 121.88 | 0.00 | 0.00 |
| April | 394.74 | 60.50 | 191.38 | 73.14 | 118.24 | 0.00 | 0.00 |
| May | 386.18 | 20.79 | 160.01 | 45.55 | 114.46 | 0.00 | 0.00 |
| June | 354.94 | 16.22 | 137.14 | 25.73 | 111.41 | 0.00 | 0.00 |
| July | 297.62 | 10.84 | 127.65 | 13.73 | 113.93 | 0.00 | 0.00 |
| August | 271.30 | 22.96 | 124.92 | 12.56 | 112.36 | 0.00 | 0.00 |
| September | 302.05 | 50.20 | 156.43 | 43.96 | 112.48 | 0.00 | 0.00 |
| October | 401.11 | 125.48 | 225.41 | 115.25 | 110.16 | 0.00 | 0.00 |
| November | 402.35 | 198.98 | 260.09 | 158.74 | 101.35 | 0.00 | 0.00 |
| December | 303.45 | 248.43 | 229.77 | 132.21 | 97.57 | 0.00 | 0.00 |
| Annual Sum or Average | 338.58 | 109.59 | 188.75 | 78.78 | 109.97 | 0.00 | 0.00 |
| Minimum of Months | 271.30 | 10.84 | 124.92 | 12.56 | 97.30 | 0.00 | 0.00 |
| Maximum of Months | 402.35 | 248.43 | 260.09 | 158.74 | 121.88 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: G NE APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 71.66 | 215.17 | 89.36 | 21.11 | 68.25 | 0.00 | 0.00 |
| February | 124.43 | 166.39 | 107.25 | 26.08 | 81.17 | 0.00 | 0.00 |
| March | 212.35 | 93.74 | 130.27 | 31.90 | 98.37 | 0.00 | 0.00 |
| April | 345.89 | 27.11 | 149.85 | 43.41 | 106.44 | 0.00 | 0.00 |
| May | 434.17 | 2.68 | 154.36 | 42.13 | 112.23 | 0.00 | 0.00 |
| June | 426.95 | 2.67 | 139.34 | 26.71 | 112.62 | 0.00 | 0.00 |
| July | 370.44 | 0.41 | 126.88 | 14.11 | 112.77 | 0.00 | 0.00 |
| August | 308.16 | 1.61 | 115.59 | 9.99 | 105.59 | 0.00 | 0.00 |
| September | 257.33 | 8.67 | 112.60 | 16.49 | 96.11 | 0.00 | 0.00 |
| October | 215.19 | 75.13 | 111.30 | 26.40 | 84.89 | 0.00 | 0.00 |
| November | 132.35 | 157.11 | 96.71 | 24.73 | 71.97 | 0.00 | 0.00 |
| December | 72.83 | 224.93 | 86.45 | 19.92 | 66.53 | 0.00 | 0.00 |
| Annual Sum or Average | 248.19 | 80.96 | 118.35 | 25.21 | 93.14 | 0.00 | 0.00 |
| Minimum of Months | 71.66 | 0.41 | 86.45 | 9.99 | 66.53 | 0.00 | 0.00 |
| Maximum of Months | 434.17 | 224.93 | 154.36 | 43.41 | 112.77 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: G N1 APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 22.85 | 145.40 | 37.02 | 0.00 | 37.02 | 0.00 | 0.00 |
| February | 44.13 | 111.07 | 43.90 | 0.00 | 43.90 | 0.00 | 0.00 |
| March | 85.37 | 61.03 | 52.91 | 0.01 | 52.91 | 0.00 | 0.00 |
| April | 151.46 | 16.62 | 57.54 | 0.29 | 57.25 | 0.00 | 0.00 |
| May | 212.46 | 1.55 | 63.80 | 1.97 | 61.82 | 0.00 | 0.00 |
| June | 227.79 | 1.53 | 65.66 | 2.28 | 63.38 | 0.00 | 0.00 |
| July | 206.14 | 0.23 | 65.03 | 1.12 | 63.91 | 0.00 | 0.00 |
| August | 171.39 | 0.80 | 59.80 | 0.33 | 59.47 | 0.00 | 0.00 |
| September | 131.20 | 4.66 | 53.11 | 0.01 | 53.10 | 0.00 | 0.00 |
| October | 93.79 | 46.12 | 46.01 | 0.00 | 46.01 | 0.00 | 0.00 |
| November | 49.36 | 100.17 | 38.97 | 0.00 | 38.97 | 0.00 | 0.00 |
| December | 22.73 | 148.15 | 36.11 | 0.00 | 36.11 | 0.00 | 0.00 |
| Annual Sum or Average | 118.60 | 52.88 | 51.69 | 0.50 | 51.19 | 0.00 | 0.00 |
| Minimum of Months | 22.73 | 0.23 | 36.11 | 0.00 | 36.11 | 0.00 | 0.00 |
| Maximum of Months | 227.79 | 148.15 | 65.66 | 2.28 | 63.91 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: G N2 APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 22.82 | 145.43 | 37.02 | 0.00 | 37.02 | 0.00 | 0.00 |
| February | 44.08 | 111.13 | 43.90 | 0.00 | 43.90 | 0.00 | 0.00 |
| March | 85.35 | 61.03 | 52.91 | 0.01 | 52.91 | 0.00 | 0.00 |
| April | 151.45 | 16.61 | 57.54 | 0.29 | 57.25 | 0.00 | 0.00 |
| May | 212.45 | 1.55 | 63.80 | 1.97 | 61.82 | 0.00 | 0.00 |
| June | 227.80 | 1.53 | 65.66 | 2.28 | 63.38 | 0.00 | 0.00 |
| July | 206.14 | 0.23 | 65.03 | 1.12 | 63.91 | 0.00 | 0.00 |
| August | 171.39 | 0.80 | 59.80 | 0.33 | 59.47 | 0.00 | 0.00 |
| September | 131.20 | 4.65 | 53.11 | 0.01 | 53.10 | 0.00 | 0.00 |
| October | 93.78 | 46.12 | 46.01 | 0.00 | 46.01 | 0.00 | 0.00 |
| November | 49.35 | 100.17 | 38.97 | 0.00 | 38.97 | 0.00 | 0.00 |
| December | 22.70 | 148.17 | 36.11 | 0.00 | 36.11 | 0.00 | 0.00 |
| Annual Sum or Average | 118.58 | 52.89 | 51.69 | 0.50 | 51.19 | 0.00 | 0.00 |
| Minimum of Months | 22.70 | 0.23 | 36.11 | 0.00 | 36.11 | 0.00 | 0.00 |
| Maximum of Months | 227.80 | 148.17 | 65.66 | 2.28 | 63.91 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: G S1 APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 232.66 | 141.75 | 167.36 | 101.30 | 66.07 | 0.00 | 0.00 |
| February | 246.78 | 109.68 | 161.53 | 90.35 | 71.18 | 0.00 | 0.00 |
| March | 240.99 | 61.70 | 133.41 | 57.00 | 76.41 | 0.00 | 0.00 |
| April | 242.06 | 17.74 | 99.06 | 30.02 | 69.04 | 0.00 | 0.00 |
| May | 227.01 | 1.54 | 69.44 | 5.39 | 64.05 | 0.00 | 0.00 |
| June | 223.84 | 1.54 | 63.46 | 1.29 | 62.17 | 0.00 | 0.00 |
| July | 208.56 | 0.23 | 65.80 | 0.73 | 65.07 | 0.00 | 0.00 |
| August | 190.68 | 0.83 | 69.14 | 2.90 | 66.24 | 0.00 | 0.00 |
| September | 217.18 | 5.07 | 96.94 | 27.47 | 69.48 | 0.00 | 0.00 |
| October | 306.57 | 46.86 | 160.12 | 88.84 | 71.28 | 0.00 | 0.00 |
| November | 335.66 | 97.57 | 202.35 | 134.00 | 68.35 | 0.00 | 0.00 |
| December | 259.04 | 139.74 | 179.44 | 112.28 | 67.15 | 0.00 | 0.00 |
| Annual Sum or Average | 244.12 | 51.78 | 122.09 | 54.07 | 68.02 | 0.00 | 0.00 |
| Minimum of Months | 190.68 | 0.23 | 63.46 | 0.73 | 62.17 | 0.00 | 0.00 |
| Maximum of Months | 335.66 | 141.75 | 202.35 | 134.00 | 76.41 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: G S2 APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 232.38 | 142.20 | 167.36 | 101.30 | 66.07 | 0.00 | 0.00 |
| February | 246.36 | 110.35 | 161.53 | 90.35 | 71.18 | 0.00 | 0.00 |
| March | 240.44 | 62.39 | 133.41 | 57.00 | 76.41 | 0.00 | 0.00 |
| April | 240.92 | 18.39 | 99.06 | 30.02 | 69.04 | 0.00 | 0.00 |
| May | 225.22 | 1.70 | 69.44 | 5.39 | 64.05 | 0.00 | 0.00 |
| June | 222.05 | 1.67 | 63.46 | 1.29 | 62.17 | 0.00 | 0.00 |
| July | 206.62 | 0.25 | 65.80 | 0.73 | 65.07 | 0.00 | 0.00 |
| August | 188.98 | 0.98 | 69.14 | 2.90 | 66.24 | 0.00 | 0.00 |
| September | 215.83 | 5.66 | 96.94 | 27.47 | 69.48 | 0.00 | 0.00 |
| October | 305.79 | 47.84 | 160.12 | 88.84 | 71.28 | 0.00 | 0.00 |
| November | 335.15 | 98.37 | 202.35 | 134.00 | 68.35 | 0.00 | 0.00 |
| December | 258.71 | 140.24 | 179.44 | 112.28 | 67.15 | 0.00 | 0.00 |
| Annual Sum or Average | 243.06 | 52.26 | 122.09 | 54.07 | 68.02 | 0.00 | 0.00 |
| Minimum of Months | 188.98 | 0.25 | 63.46 | 0.73 | 62.17 | 0.00 | 0.00 |
| Maximum of Months | 335.15 | 142.20 | 202.35 | 134.00 | 76.41 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: M SW APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 284.36 | 234.72 | 218.40 | 121.14 | 97.26 | 0.00 | 0.00 |
| February | 321.24 | 182.81 | 219.83 | 111.80 | 108.03 | 0.00 | 0.00 |
| March | 365.87 | 104.12 | 209.41 | 87.54 | 121.87 | 0.00 | 0.00 |
| April | 434.00 | 30.09 | 190.91 | 73.01 | 117.90 | 0.00 | 0.00 |
| May | 445.12 | 2.65 | 156.44 | 42.24 | 114.20 | 0.00 | 0.00 |
| June | 442.99 | 2.44 | 145.53 | 33.33 | 112.20 | 0.00 | 0.00 |
| July | 378.01 | 0.33 | 126.48 | 12.50 | 113.98 | 0.00 | 0.00 |
| August | 335.84 | 1.01 | 124.78 | 12.66 | 112.11 | 0.00 | 0.00 |
| September | 352.90 | 6.77 | 158.40 | 45.65 | 112.75 | 0.00 | 0.00 |
| October | 429.19 | 75.02 | 223.91 | 114.22 | 109.69 | 0.00 | 0.00 |
| November | 423.84 | 159.86 | 260.05 | 158.58 | 101.47 | 0.00 | 0.00 |
| December | 312.60 | 227.56 | 228.88 | 131.17 | 97.71 | 0.00 | 0.00 |
| Annual Sum or Average | 377.23 | 85.21 | 188.33 | 78.39 | 109.93 | 0.00 | 0.00 |
| Minimum of Months | 284.36 | 0.33 | 124.78 | 12.50 | 97.26 | 0.00 | 0.00 |
| Maximum of Months | 445.12 | 234.72 | 260.05 | 158.58 | 121.87 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: M NW APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 81.27 | 235.22 | 88.06 | 19.84 | 68.21 | 0.00 | 0.00 |
| February | 122.57 | 185.20 | 102.20 | 21.45 | 80.75 | 0.00 | 0.00 |
| March | 212.18 | 103.62 | 128.91 | 30.54 | 98.36 | 0.00 | 0.00 |
| April | 344.56 | 28.87 | 149.39 | 43.28 | 106.11 | 0.00 | 0.00 |
| May | 430.74 | 2.66 | 150.80 | 38.82 | 111.98 | 0.00 | 0.00 |
| June | 446.93 | 2.43 | 147.73 | 34.32 | 113.41 | 0.00 | 0.00 |
| July | 375.49 | 0.33 | 125.71 | 12.89 | 112.82 | 0.00 | 0.00 |
| August | 316.82 | 0.99 | 115.44 | 10.10 | 105.34 | 0.00 | 0.00 |
| September | 268.20 | 6.36 | 114.57 | 18.19 | 96.38 | 0.00 | 0.00 |
| October | 218.94 | 74.07 | 109.80 | 25.38 | 84.42 | 0.00 | 0.00 |
| November | 141.92 | 161.91 | 96.67 | 24.58 | 72.09 | 0.00 | 0.00 |
| December | 81.60 | 230.47 | 85.55 | 18.88 | 66.67 | 0.00 | 0.00 |
| Annual Sum or Average | 254.00 | 85.59 | 117.93 | 24.83 | 93.10 | 0.00 | 0.00 |
| Minimum of Months | 81.27 | 0.33 | 85.55 | 10.10 | 66.67 | 0.00 | 0.00 |
| Maximum of Months | 446.93 | 235.22 | 150.80 | 43.28 | 113.41 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: M SE APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 280.86 | 229.41 | 219.70 | 122.40 | 97.30 | 0.00 | 0.00 |
| February | 324.34 | 177.60 | 224.88 | 116.43 | 108.45 | 0.00 | 0.00 |
| March | 363.66 | 99.23 | 210.77 | 88.89 | 121.88 | 0.00 | 0.00 |
| April | 433.43 | 28.84 | 191.38 | 73.14 | 118.24 | 0.00 | 0.00 |
| May | 450.67 | 2.53 | 160.01 | 45.55 | 114.46 | 0.00 | 0.00 |
| June | 427.96 | 2.41 | 137.14 | 25.73 | 111.41 | 0.00 | 0.00 |
| July | 381.11 | 0.32 | 127.65 | 13.73 | 113.93 | 0.00 | 0.00 |
| August | 335.82 | 0.99 | 124.92 | 12.56 | 112.36 | 0.00 | 0.00 |
| September | 349.22 | 6.57 | 156.43 | 43.96 | 112.48 | 0.00 | 0.00 |
| October | 429.79 | 73.35 | 225.41 | 115.25 | 110.16 | 0.00 | 0.00 |
| November | 419.86 | 156.21 | 260.09 | 158.74 | 101.35 | 0.00 | 0.00 |
| December | 311.23 | 224.39 | 229.77 | 132.21 | 97.57 | 0.00 | 0.00 |
| Annual Sum or Average | 375.73 | 83.10 | 188.75 | 78.78 | 109.97 | 0.00 | 0.00 |
| Minimum of Months | 280.86 | 0.32 | 124.92 | 12.56 | 97.30 | 0.00 | 0.00 |
| Maximum of Months | 450.67 | 229.41 | 260.09 | 158.74 | 121.88 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: M NE APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 68.75 | 221.12 | 89.36 | 21.11 | 68.25 | 0.00 | 0.00 |
| February | 119.30 | 174.45 | 107.25 | 26.08 | 81.17 | 0.00 | 0.00 |
| March | 208.49 | 97.37 | 130.27 | 31.90 | 98.37 | 0.00 | 0.00 |
| April | 344.27 | 27.92 | 149.85 | 43.41 | 106.44 | 0.00 | 0.00 |
| May | 436.33 | 2.57 | 154.36 | 42.13 | 112.23 | 0.00 | 0.00 |
| June | 431.90 | 2.40 | 139.34 | 26.71 | 112.62 | 0.00 | 0.00 |
| July | 378.59 | 0.32 | 126.88 | 14.11 | 112.77 | 0.00 | 0.00 |
| August | 316.81 | 0.97 | 115.59 | 9.99 | 105.59 | 0.00 | 0.00 |
| September | 264.51 | 6.15 | 112.60 | 16.49 | 96.11 | 0.00 | 0.00 |
| October | 218.53 | 71.42 | 111.30 | 26.40 | 84.89 | 0.00 | 0.00 |
| November | 133.85 | 154.38 | 96.71 | 24.73 | 71.97 | 0.00 | 0.00 |
| December | 74.07 | 221.87 | 86.45 | 19.92 | 66.53 | 0.00 | 0.00 |
| Annual Sum or Average | 250.21 | 81.36 | 118.35 | 25.21 | 93.14 | 0.00 | 0.00 |
| Minimum of Months | 68.75 | 0.32 | 86.45 | 9.99 | 66.53 | 0.00 | 0.00 |
| Maximum of Months | 436.33 | 221.87 | 154.36 | 43.41 | 112.77 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: M N1 APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 21.16 | 151.06 | 37.02 | 0.00 | 37.02 | 0.00 | 0.00 |
| February | 42.08 | 115.95 | 43.90 | 0.00 | 43.90 | 0.00 | 0.00 |
| March | 84.13 | 62.61 | 52.91 | 0.01 | 52.91 | 0.00 | 0.00 |
| April | 151.43 | 16.83 | 57.54 | 0.29 | 57.25 | 0.00 | 0.00 |
| May | 214.38 | 1.47 | 63.80 | 1.97 | 61.82 | 0.00 | 0.00 |
| June | 230.83 | 1.39 | 65.66 | 2.28 | 63.38 | 0.00 | 0.00 |
| July | 210.35 | 0.19 | 65.03 | 1.12 | 63.91 | 0.00 | 0.00 |
| August | 175.73 | 0.53 | 59.80 | 0.33 | 59.47 | 0.00 | 0.00 |
| September | 134.90 | 3.55 | 53.11 | 0.01 | 53.10 | 0.00 | 0.00 |
| October | 95.50 | 44.36 | 46.01 | 0.00 | 46.01 | 0.00 | 0.00 |
| November | 50.02 | 99.15 | 38.97 | 0.00 | 38.97 | 0.00 | 0.00 |
| December | 22.86 | 147.79 | 36.11 | 0.00 | 36.11 | 0.00 | 0.00 |
| Annual Sum or Average | 119.84 | 53.49 | 51.69 | 0.50 | 51.19 | 0.00 | 0.00 |
| Minimum of Months | 21.16 | 0.19 | 36.11 | 0.00 | 36.11 | 0.00 | 0.00 |
| Maximum of Months | 230.83 | 151.06 | 65.66 | 2.28 | 63.91 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: M N2 APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 21.11 | 151.09 | 37.02 | 0.00 | 37.02 | 0.00 | 0.00 |
| February | 42.04 | 115.99 | 43.90 | 0.00 | 43.90 | 0.00 | 0.00 |
| March | 84.11 | 62.61 | 52.91 | 0.01 | 52.91 | 0.00 | 0.00 |
| April | 151.42 | 16.83 | 57.54 | 0.29 | 57.25 | 0.00 | 0.00 |
| May | 214.37 | 1.47 | 63.80 | 1.97 | 61.82 | 0.00 | 0.00 |
| June | 230.83 | 1.39 | 65.66 | 2.28 | 63.38 | 0.00 | 0.00 |
| July | 210.34 | 0.19 | 65.03 | 1.12 | 63.91 | 0.00 | 0.00 |
| August | 175.73 | 0.53 | 59.80 | 0.33 | 59.47 | 0.00 | 0.00 |
| September | 134.90 | 3.54 | 53.11 | 0.01 | 53.10 | 0.00 | 0.00 |
| October | 95.49 | 44.35 | 46.01 | 0.00 | 46.01 | 0.00 | 0.00 |
| November | 50.00 | 99.15 | 38.97 | 0.00 | 38.97 | 0.00 | 0.00 |
| December | 22.82 | 147.82 | 36.11 | 0.00 | 36.11 | 0.00 | 0.00 |
| Annual Sum or Average | 119.82 | 53.49 | 51.69 | 0.50 | 51.19 | 0.00 | 0.00 |
| Minimum of Months | 21.11 | 0.19 | 36.11 | 0.00 | 36.11 | 0.00 | 0.00 |
| Maximum of Months | 230.83 | 151.09 | 65.66 | 2.28 | 63.91 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: M S1 APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 230.48 | 143.64 | 167.36 | 101.30 | 66.07 | 0.00 | 0.00 |
| February | 244.68 | 111.17 | 161.53 | 90.35 | 71.18 | 0.00 | 0.00 |
| March | 239.42 | 62.52 | 133.41 | 57.00 | 76.41 | 0.00 | 0.00 |
| April | 241.60 | 17.78 | 99.06 | 30.02 | 69.04 | 0.00 | 0.00 |
| May | 228.92 | 1.44 | 69.44 | 5.39 | 64.05 | 0.00 | 0.00 |
| June | 226.86 | 1.40 | 63.46 | 1.29 | 62.17 | 0.00 | 0.00 |
| July | 212.90 | 0.19 | 65.80 | 0.73 | 65.07 | 0.00 | 0.00 |
| August | 194.94 | 0.55 | 69.14 | 2.90 | 66.24 | 0.00 | 0.00 |
| September | 220.36 | 3.83 | 96.94 | 27.47 | 69.48 | 0.00 | 0.00 |
| October | 307.56 | 44.70 | 160.12 | 88.84 | 71.28 | 0.00 | 0.00 |
| November | 335.48 | 96.02 | 202.35 | 134.00 | 68.35 | 0.00 | 0.00 |
| December | 258.39 | 138.91 | 179.44 | 112.28 | 67.15 | 0.00 | 0.00 |
| Annual Sum or Average | 245.01 | 51.60 | 122.09 | 54.07 | 68.02 | 0.00 | 0.00 |
| Minimum of Months | 194.94 | 0.19 | 63.46 | 0.73 | 62.17 | 0.00 | 0.00 |
| Maximum of Months | 335.48 | 143.64 | 202.35 | 134.00 | 76.41 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: M S2 APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 230.45 | 143.64 | 167.36 | 101.30 | 66.07 | 0.00 | 0.00 |
| February | 244.66 | 111.17 | 161.53 | 90.35 | 71.18 | 0.00 | 0.00 |
| March | 239.40 | 62.52 | 133.41 | 57.00 | 76.41 | 0.00 | 0.00 |
| April | 241.59 | 17.78 | 99.06 | 30.02 | 69.04 | 0.00 | 0.00 |
| May | 228.91 | 1.44 | 69.44 | 5.39 | 64.05 | 0.00 | 0.00 |
| June | 226.87 | 1.40 | 63.46 | 1.29 | 62.17 | 0.00 | 0.00 |
| July | 212.90 | 0.19 | 65.80 | 0.73 | 65.07 | 0.00 | 0.00 |
| August | 194.93 | 0.55 | 69.14 | 2.90 | 66.24 | 0.00 | 0.00 |
| September | 220.36 | 3.83 | 96.94 | 27.47 | 69.48 | 0.00 | 0.00 |
| October | 307.55 | 44.69 | 160.12 | 88.84 | 71.28 | 0.00 | 0.00 |
| November | 335.47 | 96.01 | 202.35 | 134.00 | 68.35 | 0.00 | 0.00 |
| December | 258.37 | 138.90 | 179.44 | 112.28 | 67.15 | 0.00 | 0.00 |
| Annual Sum or Average | 245.01 | 51.60 | 122.09 | 54.07 | 68.02 | 0.00 | 0.00 |
| Minimum of Months | 194.93 | 0.19 | 63.46 | 0.73 | 62.17 | 0.00 | 0.00 |
| Maximum of Months | 335.47 | 143.64 | 202.35 | 134.00 | 76.41 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: T SW APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 291.63 | 204.58 | 218.40 | 121.14 | 97.26 | 0.00 | 0.00 |
| February | 324.97 | 161.28 | 219.83 | 111.80 | 108.03 | 0.00 | 0.00 |
| March | 361.56 | 97.04 | 209.41 | 87.54 | 121.87 | 0.00 | 0.00 |
| April | 424.08 | 28.45 | 190.91 | 73.01 | 117.90 | 0.00 | 0.00 |
| May | 433.36 | 2.48 | 156.44 | 42.24 | 114.20 | 0.00 | 0.00 |
| June | 430.39 | 2.42 | 145.53 | 33.33 | 112.20 | 0.00 | 0.00 |
| July | 366.93 | 0.31 | 126.48 | 12.50 | 113.98 | 0.00 | 0.00 |
| August | 326.14 | 1.00 | 124.78 | 12.66 | 112.11 | 0.00 | 0.00 |
| September | 344.56 | 6.31 | 158.40 | 45.65 | 112.75 | 0.00 | 0.00 |
| October | 422.67 | 71.21 | 223.91 | 114.22 | 109.69 | 0.00 | 0.00 |
| November | 423.48 | 145.61 | 260.05 | 158.58 | 101.47 | 0.00 | 0.00 |
| December | 320.42 | 198.84 | 228.88 | 131.17 | 97.71 | 0.00 | 0.00 |
| Annual Sum or Average | 372.54 | 76.27 | 188.33 | 78.39 | 109.93 | 0.00 | 0.00 |
| Minimum of Months | 291.63 | 0.31 | 124.78 | 12.50 | 97.26 | 0.00 | 0.00 |
| Maximum of Months | 433.36 | 204.58 | 260.05 | 158.58 | 121.87 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: T NW APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 87.08 | 207.05 | 88.06 | 19.84 | 68.21 | 0.00 | 0.00 |
| February | 127.72 | 161.61 | 102.20 | 21.45 | 80.75 | 0.00 | 0.00 |
| March | 209.73 | 95.80 | 128.91 | 30.54 | 98.36 | 0.00 | 0.00 |
| April | 335.61 | 27.39 | 149.39 | 43.28 | 106.11 | 0.00 | 0.00 |
| May | 419.07 | 2.52 | 150.80 | 38.82 | 111.98 | 0.00 | 0.00 |
| June | 434.34 | 2.41 | 147.73 | 34.32 | 113.41 | 0.00 | 0.00 |
| July | 364.41 | 0.31 | 125.71 | 12.89 | 112.82 | 0.00 | 0.00 |
| August | 307.26 | 0.97 | 115.44 | 10.10 | 105.34 | 0.00 | 0.00 |
| September | 260.69 | 5.99 | 114.57 | 18.19 | 96.38 | 0.00 | 0.00 |
| October | 214.43 | 70.19 | 109.80 | 25.38 | 84.42 | 0.00 | 0.00 |
| November | 144.58 | 144.26 | 96.67 | 24.58 | 72.09 | 0.00 | 0.00 |
| December | 90.25 | 197.90 | 85.55 | 18.88 | 66.67 | 0.00 | 0.00 |
| Annual Sum or Average | 250.12 | 76.01 | 117.93 | 24.83 | 93.10 | 0.00 | 0.00 |
| Minimum of Months | 87.08 | 0.31 | 85.55 | 10.10 | 66.67 | 0.00 | 0.00 |
| Maximum of Months | 434.34 | 207.05 | 150.80 | 43.28 | 113.41 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: T SE APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 288.95 | 200.42 | 219.70 | 122.40 | 97.30 | 0.00 | 0.00 |
| February | 328.37 | 157.23 | 224.88 | 116.43 | 108.45 | 0.00 | 0.00 |
| March | 359.69 | 92.88 | 210.77 | 88.89 | 121.88 | 0.00 | 0.00 |
| April | 423.49 | 27.31 | 191.38 | 73.14 | 118.24 | 0.00 | 0.00 |
| May | 438.66 | 2.36 | 160.01 | 45.55 | 114.46 | 0.00 | 0.00 |
| June | 415.36 | 2.40 | 137.14 | 25.73 | 111.41 | 0.00 | 0.00 |
| July | 369.98 | 0.30 | 127.65 | 13.73 | 113.93 | 0.00 | 0.00 |
| August | 326.08 | 0.96 | 124.92 | 12.56 | 112.36 | 0.00 | 0.00 |
| September | 340.85 | 6.11 | 156.43 | 43.96 | 112.48 | 0.00 | 0.00 |
| October | 423.25 | 69.64 | 225.41 | 115.25 | 110.16 | 0.00 | 0.00 |
| November | 419.46 | 142.34 | 260.09 | 158.74 | 101.35 | 0.00 | 0.00 |
| December | 319.09 | 196.35 | 229.77 | 132.21 | 97.57 | 0.00 | 0.00 |
| Annual Sum or Average | 371.14 | 74.52 | 188.75 | 78.78 | 109.97 | 0.00 | 0.00 |
| Minimum of Months | 288.95 | 0.30 | 124.92 | 12.56 | 97.30 | 0.00 | 0.00 |
| Maximum of Months | 438.66 | 200.42 | 260.09 | 158.74 | 121.88 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: T NE APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 77.23 | 194.39 | 89.36 | 21.11 | 68.25 | 0.00 | 0.00 |
| February | 126.39 | 153.24 | 107.25 | 26.08 | 81.17 | 0.00 | 0.00 |
| March | 206.63 | 90.65 | 130.27 | 31.90 | 98.37 | 0.00 | 0.00 |
| April | 335.26 | 26.52 | 149.85 | 43.41 | 106.44 | 0.00 | 0.00 |
| May | 424.41 | 2.42 | 154.36 | 42.13 | 112.23 | 0.00 | 0.00 |
| June | 419.30 | 2.38 | 139.34 | 26.71 | 112.62 | 0.00 | 0.00 |
| July | 367.46 | 0.30 | 126.88 | 14.11 | 112.77 | 0.00 | 0.00 |
| August | 307.20 | 0.94 | 115.59 | 9.99 | 105.59 | 0.00 | 0.00 |
| September | 256.97 | 5.79 | 112.60 | 16.49 | 96.11 | 0.00 | 0.00 |
| October | 214.11 | 67.79 | 111.30 | 26.40 | 84.89 | 0.00 | 0.00 |
| November | 137.57 | 138.40 | 96.71 | 24.73 | 71.97 | 0.00 | 0.00 |
| December | 85.13 | 191.15 | 86.45 | 19.92 | 66.53 | 0.00 | 0.00 |
| Annual Sum or Average | 247.01 | 72.49 | 118.35 | 25.21 | 93.14 | 0.00 | 0.00 |
| Minimum of Months | 77.23 | 0.30 | 86.45 | 9.99 | 66.53 | 0.00 | 0.00 |
| Maximum of Months | 424.41 | 194.39 | 154.36 | 43.41 | 112.77 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: T N1 APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 26.16 | 130.05 | 37.02 | 0.00 | 37.02 | 0.00 | 0.00 |
| February | 45.86 | 101.39 | 43.90 | 0.00 | 43.90 | 0.00 | 0.00 |
| March | 83.02 | 58.99 | 52.91 | 0.01 | 52.91 | 0.00 | 0.00 |
| April | 146.96 | 16.23 | 57.54 | 0.29 | 57.25 | 0.00 | 0.00 |
| May | 208.18 | 1.44 | 63.80 | 1.97 | 61.82 | 0.00 | 0.00 |
| June | 224.08 | 1.43 | 65.66 | 2.28 | 63.38 | 0.00 | 0.00 |
| July | 204.33 | 0.18 | 65.03 | 1.12 | 63.91 | 0.00 | 0.00 |
| August | 170.54 | 0.54 | 59.80 | 0.33 | 59.47 | 0.00 | 0.00 |
| September | 130.97 | 3.44 | 53.11 | 0.01 | 53.10 | 0.00 | 0.00 |
| October | 93.30 | 42.56 | 46.01 | 0.00 | 46.01 | 0.00 | 0.00 |
| November | 51.70 | 89.90 | 38.97 | 0.00 | 38.97 | 0.00 | 0.00 |
| December | 28.89 | 124.88 | 36.11 | 0.00 | 36.11 | 0.00 | 0.00 |
| Annual Sum or Average | 118.20 | 47.36 | 51.69 | 0.50 | 51.19 | 0.00 | 0.00 |
| Minimum of Months | 26.16 | 0.18 | 36.11 | 0.00 | 36.11 | 0.00 | 0.00 |
| Maximum of Months | 224.08 | 130.05 | 65.66 | 2.28 | 63.91 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: T N2 APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 26.07 | 129.96 | 37.02 | 0.00 | 37.02 | 0.00 | 0.00 |
| February | 45.74 | 101.38 | 43.90 | 0.00 | 43.90 | 0.00 | 0.00 |
| March | 82.95 | 58.96 | 52.91 | 0.01 | 52.91 | 0.00 | 0.00 |
| April | 146.94 | 16.22 | 57.54 | 0.29 | 57.25 | 0.00 | 0.00 |
| May | 208.17 | 1.43 | 63.80 | 1.97 | 61.82 | 0.00 | 0.00 |
| June | 224.09 | 1.42 | 65.66 | 2.28 | 63.38 | 0.00 | 0.00 |
| July | 204.33 | 0.18 | 65.03 | 1.12 | 63.91 | 0.00 | 0.00 |
| August | 170.54 | 0.54 | 59.80 | 0.33 | 59.47 | 0.00 | 0.00 |
| September | 130.97 | 3.44 | 53.11 | 0.01 | 53.10 | 0.00 | 0.00 |
| October | 93.27 | 42.54 | 46.01 | 0.00 | 46.01 | 0.00 | 0.00 |
| November | 51.62 | 89.87 | 38.97 | 0.00 | 38.97 | 0.00 | 0.00 |
| December | 28.79 | 124.82 | 36.11 | 0.00 | 36.11 | 0.00 | 0.00 |
| Annual Sum or Average | 118.16 | 47.34 | 51.69 | 0.50 | 51.19 | 0.00 | 0.00 |
| Minimum of Months | 26.07 | 0.18 | 36.11 | 0.00 | 36.11 | 0.00 | 0.00 |
| Maximum of Months | 224.09 | 129.96 | 65.66 | 2.28 | 63.91 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: T S1 APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 236.21 | 125.79 | 167.36 | 101.30 | 66.07 | 0.00 | 0.00 |
| February | 247.16 | 99.60 | 161.53 | 90.35 | 71.18 | 0.00 | 0.00 |
| March | 237.08 | 59.42 | 133.41 | 57.00 | 76.41 | 0.00 | 0.00 |
| April | 236.47 | 17.09 | 99.06 | 30.02 | 69.04 | 0.00 | 0.00 |
| May | 222.68 | 1.39 | 69.44 | 5.39 | 64.05 | 0.00 | 0.00 |
| June | 220.12 | 1.44 | 63.46 | 1.29 | 62.17 | 0.00 | 0.00 |
| July | 206.90 | 0.18 | 65.80 | 0.73 | 65.07 | 0.00 | 0.00 |
| August | 189.67 | 0.56 | 69.14 | 2.90 | 66.24 | 0.00 | 0.00 |
| September | 215.87 | 3.67 | 96.94 | 27.47 | 69.48 | 0.00 | 0.00 |
| October | 304.08 | 42.94 | 160.12 | 88.84 | 71.28 | 0.00 | 0.00 |
| November | 335.05 | 89.34 | 202.35 | 134.00 | 68.35 | 0.00 | 0.00 |
| December | 263.65 | 122.91 | 179.44 | 112.28 | 67.15 | 0.00 | 0.00 |
| Annual Sum or Average | 242.78 | 46.81 | 122.09 | 54.07 | 68.02 | 0.00 | 0.00 |
| Minimum of Months | 189.67 | 0.18 | 63.46 | 0.73 | 62.17 | 0.00 | 0.00 |
| Maximum of Months | 335.05 | 125.79 | 202.35 | 134.00 | 76.41 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: T S2 APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 236.12 | 125.76 | 167.36 | 101.30 | 66.07 | 0.00 | 0.00 |
| February | 247.08 | 99.58 | 161.53 | 90.35 | 71.18 | 0.00 | 0.00 |
| March | 237.04 | 59.40 | 133.41 | 57.00 | 76.41 | 0.00 | 0.00 |
| April | 236.45 | 17.08 | 99.06 | 30.02 | 69.04 | 0.00 | 0.00 |
| May | 222.67 | 1.39 | 69.44 | 5.39 | 64.05 | 0.00 | 0.00 |
| June | 220.13 | 1.44 | 63.46 | 1.29 | 62.17 | 0.00 | 0.00 |
| July | 206.90 | 0.18 | 65.80 | 0.73 | 65.07 | 0.00 | 0.00 |
| August | 189.67 | 0.56 | 69.14 | 2.90 | 66.24 | 0.00 | 0.00 |
| September | 215.87 | 3.66 | 96.94 | 27.47 | 69.48 | 0.00 | 0.00 |
| October | 304.06 | 42.92 | 160.12 | 88.84 | 71.28 | 0.00 | 0.00 |
| November | 335.01 | 89.31 | 202.35 | 134.00 | 68.35 | 0.00 | 0.00 |
| December | 263.58 | 122.88 | 179.44 | 112.28 | 67.15 | 0.00 | 0.00 |
| Annual Sum or Average | 242.75 | 46.79 | 122.09 | 54.07 | 68.02 | 0.00 | 0.00 |
| Minimum of Months | 189.67 | 0.18 | 63.46 | 0.73 | 62.17 | 0.00 | 0.00 |
| Maximum of Months | 335.01 | 125.76 | 202.35 | 134.00 | 76.41 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: T CORRIDOR
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 13.70 | 20.93 | 12.56 | 5.07 | 7.49 | 0.00 | 0.00 |
| February | 19.95 | 16.84 | 15.20 | 6.26 | 8.94 | 0.00 | 0.00 |
| March | 29.40 | 10.50 | 18.56 | 7.65 | 10.91 | 0.00 | 0.00 |
| April | 43.69 | 3.77 | 22.15 | 10.35 | 11.80 | 0.00 | 0.00 |
| May | 49.32 | 0.62 | 21.73 | 9.64 | 12.10 | 0.00 | 0.00 |
| June | 43.96 | 0.56 | 17.68 | 5.86 | 11.82 | 0.00 | 0.00 |
| July | 35.93 | 0.12 | 14.84 | 3.12 | 11.72 | 0.00 | 0.00 |
| August | 29.98 | 0.47 | 13.39 | 2.32 | 11.07 | 0.00 | 0.00 |
| September | 28.22 | 1.73 | 14.27 | 3.96 | 10.32 | 0.00 | 0.00 |
| October | 28.19 | 8.30 | 15.67 | 6.34 | 9.33 | 0.00 | 0.00 |
| November | 20.54 | 15.31 | 13.85 | 5.93 | 7.92 | 0.00 | 0.00 |
| December | 14.24 | 20.67 | 12.08 | 4.78 | 7.30 | 0.00 | 0.00 |
| Annual Sum or Average | 29.79 | 8.28 | 15.99 | 5.93 | 10.06 | 0.00 | 0.00 |
| Minimum of Months | 13.70 | 0.12 | 12.08 | 2.32 | 7.30 | 0.00 | 0.00 |
| Maximum of Months | 49.32 | 20.93 | 22.15 | 10.35 | 12.10 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: G CORRIDOR
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 39.02 | 65.69 | 37.41 | 15.09 | 22.32 | 0.00 | 0.00 |
| February | 58.02 | 52.52 | 45.27 | 18.64 | 26.63 | 0.00 | 0.00 |
| March | 86.80 | 32.61 | 55.29 | 22.79 | 32.49 | 0.00 | 0.00 |
| April | 126.91 | 13.17 | 65.97 | 30.82 | 35.16 | 0.00 | 0.00 |
| May | 140.35 | 3.29 | 64.72 | 28.70 | 36.03 | 0.00 | 0.00 |
| June | 123.47 | 2.63 | 52.65 | 17.46 | 35.19 | 0.00 | 0.00 |
| July | 99.92 | 1.03 | 44.20 | 9.29 | 34.92 | 0.00 | 0.00 |
| August | 83.74 | 2.81 | 39.87 | 6.90 | 32.96 | 0.00 | 0.00 |
| September | 79.75 | 8.38 | 42.51 | 11.78 | 30.73 | 0.00 | 0.00 |
| October | 80.67 | 28.56 | 46.66 | 18.87 | 27.79 | 0.00 | 0.00 |
| November | 58.03 | 50.07 | 41.26 | 17.67 | 23.59 | 0.00 | 0.00 |
| December | 38.70 | 67.61 | 35.97 | 14.24 | 21.73 | 0.00 | 0.00 |
| Annual Sum or Average | 84.70 | 27.26 | 47.64 | 17.66 | 29.98 | 0.00 | 0.00 |
| Minimum of Months | 38.70 | 1.03 | 35.97 | 6.90 | 21.73 | 0.00 | 0.00 |
| Maximum of Months | 140.35 | 67.61 | 65.97 | 30.82 | 36.03 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: M CORRIDOR
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 11.82 | 24.17 | 12.56 | 5.07 | 7.49 | 0.00 | 0.00 |
| February | 18.43 | 19.03 | 15.20 | 6.26 | 8.94 | 0.00 | 0.00 |
| March | 29.01 | 11.15 | 18.56 | 7.65 | 10.91 | 0.00 | 0.00 |
| April | 44.37 | 3.89 | 22.15 | 10.35 | 11.80 | 0.00 | 0.00 |
| May | 50.63 | 0.62 | 21.73 | 9.64 | 12.10 | 0.00 | 0.00 |
| June | 45.44 | 0.52 | 17.68 | 5.86 | 11.82 | 0.00 | 0.00 |
| July | 37.33 | 0.11 | 14.84 | 3.12 | 11.72 | 0.00 | 0.00 |
| August | 31.08 | 0.43 | 13.39 | 2.32 | 11.07 | 0.00 | 0.00 |
| September | 28.87 | 1.69 | 14.27 | 3.96 | 10.32 | 0.00 | 0.00 |
| October | 28.22 | 8.65 | 15.67 | 6.34 | 9.33 | 0.00 | 0.00 |
| November | 19.50 | 16.79 | 13.85 | 5.93 | 7.92 | 0.00 | 0.00 |
| December | 12.29 | 23.94 | 12.08 | 4.78 | 7.30 | 0.00 | 0.00 |
| Annual Sum or Average | 29.79 | 9.21 | 15.99 | 5.93 | 10.06 | 0.00 | 0.00 |
| Minimum of Months | 11.82 | 0.11 | 12.08 | 2.32 | 7.30 | 0.00 | 0.00 |
| Maximum of Months | 50.63 | 24.17 | 22.15 | 10.35 | 12.10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: G SW APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.770636E+09 | 0.620038E+09 | 0.584960E+09 | 0.324458E+09 | 0.260502E+09 | 0.00 | 0.00 |
| February | 0.787120E+09 | 0.432846E+09 | 0.531813E+09 | 0.270475E+09 | 0.261338E+09 | 0.00 | 0.00 |
| March | 0.989690E+09 | 0.271846E+09 | 0.560873E+09 | 0.234458E+09 | 0.326414E+09 | 0.00 | 0.00 |
| April | 0.112981E+10 | 76360816.88 | 0.494841E+09 | 0.189246E+09 | 0.305596E+09 | 0.00 | 0.00 |
| May | 0.118627E+10 | 7392127.74 | 0.419011E+09 | 0.113127E+09 | 0.305885E+09 | 0.00 | 0.00 |
| June | 0.113553E+10 | 6981383.11 | 0.377222E+09 | 86396488.98 | 0.290826E+09 | 0.00 | 0.00 |
| July | 0.991046E+09 | 1131718.10 | 0.338765E+09 | 33482596.11 | 0.305282E+09 | 0.00 | 0.00 |
| August | 0.876735E+09 | 4488970.78 | 0.334202E+09 | 33918591.24 | 0.300284E+09 | 0.00 | 0.00 |
| September | 0.897898E+09 | 24716023.13 | 0.410569E+09 | 0.118330E+09 | 0.292239E+09 | 0.00 | 0.00 |
| October | 0.114293E+10 | 0.212631E+09 | 0.599726E+09 | 0.305940E+09 | 0.293787E+09 | 0.00 | 0.00 |
| November | 0.109746E+10 | 0.422670E+09 | 0.674052E+09 | 0.411048E+09 | 0.263004E+09 | 0.00 | 0.00 |
| December | 0.837434E+09 | 0.617022E+09 | 0.613021E+09 | 0.351314E+09 | 0.261707E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.118426E+11 | 0.269813E+10 | 0.593906E+10 | 0.247219E+10 | 0.346686E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.770636E+09 | 1131718.10 | 0.334202E+09 | 33482596.11 | 0.260502E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.118627E+10 | 0.620038E+09 | 0.674052E+09 | 0.411048E+09 | 0.326414E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: G NW APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.224462E+09 | 0.613397E+09 | 0.235850E+09 | 53149103.01 | 0.182701E+09 | 0.00 | 0.00 |
| February | 0.307555E+09 | 0.426550E+09 | 0.247232E+09 | 51891941.89 | 0.195340E+09 | 0.00 | 0.00 |
| March | 0.578119E+09 | 0.266614E+09 | 0.345261E+09 | 81809097.59 | 0.263451E+09 | 0.00 | 0.00 |
| April | 0.897257E+09 | 72579539.72 | 0.387208E+09 | 0.112181E+09 | 0.275027E+09 | 0.00 | 0.00 |
| May | 0.114760E+10 | 7421032.18 | 0.403899E+09 | 0.103976E+09 | 0.299922E+09 | 0.00 | 0.00 |
| June | 0.114545E+10 | 7003715.23 | 0.382919E+09 | 88948912.87 | 0.293970E+09 | 0.00 | 0.00 |
| July | 0.984367E+09 | 1146928.45 | 0.336693E+09 | 34514780.20 | 0.302178E+09 | 0.00 | 0.00 |
| August | 0.825383E+09 | 4421515.01 | 0.309195E+09 | 27048538.08 | 0.282147E+09 | 0.00 | 0.00 |
| September | 0.676787E+09 | 23179370.53 | 0.296957E+09 | 47151346.63 | 0.249806E+09 | 0.00 | 0.00 |
| October | 0.577896E+09 | 0.208731E+09 | 0.294082E+09 | 67979562.24 | 0.226103E+09 | 0.00 | 0.00 |
| November | 0.364243E+09 | 0.427093E+09 | 0.250565E+09 | 63710905.93 | 0.186854E+09 | 0.00 | 0.00 |
| December | 0.215457E+09 | 0.626008E+09 | 0.229140E+09 | 50570362.82 | 0.178570E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.794458E+10 | 0.268415E+10 | 0.371900E+10 | 0.782932E+09 | 0.293607E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.215457E+09 | 1146928.45 | 0.229140E+09 | 27048538.08 | 0.178570E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.114760E+10 | 0.626008E+09 | 0.403899E+09 | 0.112181E+09 | 0.302178E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: OFFICE
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.750629E+09 | 0.645612E+09 | 0.588451E+09 | 0.327849E+09 | 0.260602E+09 | 0.00 | 0.00 |
| February | 0.772915E+09 | 0.476244E+09 | 0.544034E+09 | 0.281677E+09 | 0.262356E+09 | 0.00 | 0.00 |
| March | 0.939578E+09 | 0.341679E+09 | 0.564533E+09 | 0.238085E+09 | 0.326447E+09 | 0.00 | 0.00 |
| April | 0.102317E+10 | 0.156821E+09 | 0.496051E+09 | 0.189578E+09 | 0.306473E+09 | 0.00 | 0.00 |
| May | 0.103434E+10 | 55693795.32 | 0.428563E+09 | 0.121992E+09 | 0.306571E+09 | 0.00 | 0.00 |
| June | 0.920008E+09 | 42041625.17 | 0.355466E+09 | 66690861.17 | 0.288775E+09 | 0.00 | 0.00 |
| July | 0.797147E+09 | 29026625.75 | 0.341911E+09 | 36764715.99 | 0.305146E+09 | 0.00 | 0.00 |
| August | 0.726654E+09 | 61492851.62 | 0.334596E+09 | 33637685.93 | 0.300958E+09 | 0.00 | 0.00 |
| September | 0.782923E+09 | 0.130119E+09 | 0.405472E+09 | 0.113932E+09 | 0.291540E+09 | 0.00 | 0.00 |
| October | 0.107433E+10 | 0.336082E+09 | 0.603740E+09 | 0.308675E+09 | 0.295064E+09 | 0.00 | 0.00 |
| November | 0.104290E+10 | 0.515748E+09 | 0.674151E+09 | 0.411442E+09 | 0.262709E+09 | 0.00 | 0.00 |
| December | 0.812774E+09 | 0.665393E+09 | 0.615426E+09 | 0.354107E+09 | 0.261319E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.106774E+11 | 0.345595E+10 | 0.595239E+10 | 0.248443E+10 | 0.346796E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.726654E+09 | 29026625.75 | 0.334596E+09 | 33637685.93 | 0.260602E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.107433E+10 | 0.665393E+09 | 0.674151E+09 | 0.411442E+09 | 0.326447E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: G NE APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.191942E+09 | 0.576299E+09 | 0.239342E+09 | 56539698.18 | 0.182802E+09 | 0.00 | 0.00 |
| February | 0.301025E+09 | 0.402525E+09 | 0.259452E+09 | 63094222.38 | 0.196358E+09 | 0.00 | 0.00 |
| March | 0.568756E+09 | 0.251070E+09 | 0.348921E+09 | 85436118.98 | 0.263484E+09 | 0.00 | 0.00 |
| April | 0.896550E+09 | 70279789.71 | 0.388417E+09 | 0.112513E+09 | 0.275904E+09 | 0.00 | 0.00 |
| May | 0.116288E+10 | 7177875.53 | 0.413450E+09 | 0.112841E+09 | 0.300608E+09 | 0.00 | 0.00 |
| June | 0.110664E+10 | 6914558.05 | 0.361163E+09 | 69243285.06 | 0.291919E+09 | 0.00 | 0.00 |
| July | 0.992188E+09 | 1096333.16 | 0.339839E+09 | 37796900.09 | 0.302042E+09 | 0.00 | 0.00 |
| August | 0.825369E+09 | 4315810.30 | 0.309589E+09 | 26767632.77 | 0.282821E+09 | 0.00 | 0.00 |
| September | 0.667003E+09 | 22463923.41 | 0.291860E+09 | 42752943.39 | 0.249107E+09 | 0.00 | 0.00 |
| October | 0.576376E+09 | 0.201225E+09 | 0.298096E+09 | 70715302.48 | 0.227380E+09 | 0.00 | 0.00 |
| November | 0.343046E+09 | 0.407228E+09 | 0.250664E+09 | 64104976.85 | 0.186559E+09 | 0.00 | 0.00 |
| December | 0.195056E+09 | 0.602450E+09 | 0.231546E+09 | 53363630.86 | 0.178182E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.782684E+10 | 0.255305E+10 | 0.373234E+10 | 0.795169E+09 | 0.293717E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.191942E+09 | 1096333.16 | 0.231546E+09 | 26767632.77 | 0.178182E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.116288E+10 | 0.602450E+09 | 0.413450E+09 | 0.112841E+09 | 0.302042E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: G N1 APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 61210902.81 | 0.389451E+09 | 99151823.08 | 0.00 | 99151823.08 | 0.00 | 0.00 |
| February | 0.106761E+09 | 0.268693E+09 | 0.106199E+09 | 0.00 | 0.106199E+09 | 0.00 | 0.00 |
| March | 0.228659E+09 | 0.163462E+09 | 0.141718E+09 | 13520.81 | 0.141704E+09 | 0.00 | 0.00 |
| April | 0.392582E+09 | 43073515.24 | 0.149133E+09 | 741838.03 | 0.148392E+09 | 0.00 | 0.00 |
| May | 0.569051E+09 | 4161076.10 | 0.170871E+09 | 5287419.98 | 0.165583E+09 | 0.00 | 0.00 |
| June | 0.590443E+09 | 3978328.74 | 0.170190E+09 | 5905759.23 | 0.164284E+09 | 0.00 | 0.00 |
| July | 0.552137E+09 | 609138.12 | 0.174176E+09 | 2995006.13 | 0.171181E+09 | 0.00 | 0.00 |
| August | 0.459057E+09 | 2141027.86 | 0.160176E+09 | 893198.87 | 0.159283E+09 | 0.00 | 0.00 |
| September | 0.340079E+09 | 12067477.68 | 0.137666E+09 | 17478.26 | 0.137648E+09 | 0.00 | 0.00 |
| October | 0.251217E+09 | 0.123540E+09 | 0.123225E+09 | 0.00 | 0.123225E+09 | 0.00 | 0.00 |
| November | 0.127951E+09 | 0.259642E+09 | 0.101006E+09 | 0.00 | 0.101006E+09 | 0.00 | 0.00 |
| December | 60876579.37 | 0.396794E+09 | 96724368.79 | 0.00 | 96724368.79 | 0.00 | 0.00 |
| Annual Sum or Average | 0.374002E+10 | 0.166761E+10 | 0.163024E+10 | 15854221.32 | 0.161438E+10 | 0.00 | 0.00 |
| Minimum of Months | 60876579.37 | 609138.12 | 96724368.79 | 0.00 | 96724368.79 | 0.00 | 0.00 |
| Maximum of Months | 0.590443E+09 | 0.396794E+09 | 0.174176E+09 | 5905759.23 | 0.171181E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: G N2 APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 61111789.99 | 0.389515E+09 | 99151823.08 | 0.00 | 99151823.08 | 0.00 | 0.00 |
| February | 0.106636E+09 | 0.268835E+09 | 0.106199E+09 | 0.00 | 0.106199E+09 | 0.00 | 0.00 |
| March | 0.228606E+09 | 0.163458E+09 | 0.141718E+09 | 13520.81 | 0.141704E+09 | 0.00 | 0.00 |
| April | 0.392553E+09 | 43065435.99 | 0.149133E+09 | 741838.03 | 0.148392E+09 | 0.00 | 0.00 |
| May | 0.569030E+09 | 4158735.73 | 0.170871E+09 | 5287419.98 | 0.165583E+09 | 0.00 | 0.00 |
| June | 0.590466E+09 | 3975633.28 | 0.170190E+09 | 5905759.23 | 0.164284E+09 | 0.00 | 0.00 |
| July | 0.552134E+09 | 609044.05 | 0.174176E+09 | 2995006.13 | 0.171181E+09 | 0.00 | 0.00 |
| August | 0.459053E+09 | 2141584.56 | 0.160176E+09 | 893198.87 | 0.159283E+09 | 0.00 | 0.00 |
| September | 0.340080E+09 | 12060832.47 | 0.137666E+09 | 17478.26 | 0.137648E+09 | 0.00 | 0.00 |
| October | 0.251192E+09 | 0.123532E+09 | 0.123225E+09 | 0.00 | 0.123225E+09 | 0.00 | 0.00 |
| November | 0.127919E+09 | 0.259631E+09 | 0.101006E+09 | 0.00 | 0.101006E+09 | 0.00 | 0.00 |
| December | 60798645.92 | 0.396865E+09 | 96724368.79 | 0.00 | 96724368.79 | 0.00 | 0.00 |
| Annual Sum or Average | 0.373958E+10 | 0.166785E+10 | 0.163024E+10 | 15854221.32 | 0.161438E+10 | 0.00 | 0.00 |
| Minimum of Months | 60798645.92 | 609044.05 | 96724368.79 | 0.00 | 96724368.79 | 0.00 | 0.00 |
| Maximum of Months | 0.590466E+09 | 0.396865E+09 | 0.174176E+09 | 5905759.23 | 0.171181E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: G S1 APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.623153E+09 | 0.379655E+09 | 0.448261E+09 | 0.271309E+09 | 0.176952E+09 | 0.00 | 0.00 |
| February | 0.596999E+09 | 0.265345E+09 | 0.390780E+09 | 0.218583E+09 | 0.172197E+09 | 0.00 | 0.00 |
| March | 0.645469E+09 | 0.165267E+09 | 0.357330E+09 | 0.152663E+09 | 0.204667E+09 | 0.00 | 0.00 |
| April | 0.627419E+09 | 45988284.15 | 0.256767E+09 | 77806700.21 | 0.178961E+09 | 0.00 | 0.00 |
| May | 0.608020E+09 | 4125964.20 | 0.185984E+09 | 14437677.05 | 0.171546E+09 | 0.00 | 0.00 |
| June | 0.580182E+09 | 3997571.87 | 0.164493E+09 | 3353335.34 | 0.161140E+09 | 0.00 | 0.00 |
| July | 0.558601E+09 | 611552.70 | 0.176248E+09 | 1962822.04 | 0.174285E+09 | 0.00 | 0.00 |
| August | 0.510714E+09 | 2230983.56 | 0.185183E+09 | 7763252.03 | 0.177420E+09 | 0.00 | 0.00 |
| September | 0.562935E+09 | 13130805.54 | 0.251278E+09 | 71196446.15 | 0.180081E+09 | 0.00 | 0.00 |
| October | 0.821109E+09 | 0.125498E+09 | 0.428869E+09 | 0.237960E+09 | 0.190909E+09 | 0.00 | 0.00 |
| November | 0.870040E+09 | 0.252908E+09 | 0.524493E+09 | 0.347337E+09 | 0.177156E+09 | 0.00 | 0.00 |
| December | 0.693811E+09 | 0.374267E+09 | 0.480605E+09 | 0.300743E+09 | 0.179862E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.769845E+10 | 0.163303E+10 | 0.385029E+10 | 0.170512E+10 | 0.214517E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.510714E+09 | 611552.70 | 0.164493E+09 | 1962822.04 | 0.161140E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.870040E+09 | 0.379655E+09 | 0.524493E+09 | 0.347337E+09 | 0.204667E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: G S2 APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.622398E+09 | 0.380873E+09 | 0.448261E+09 | 0.271309E+09 | 0.176952E+09 | 0.00 | 0.00 |
| February | 0.595989E+09 | 0.266958E+09 | 0.390780E+09 | 0.218583E+09 | 0.172197E+09 | 0.00 | 0.00 |
| March | 0.643987E+09 | 0.167108E+09 | 0.357330E+09 | 0.152663E+09 | 0.204667E+09 | 0.00 | 0.00 |
| April | 0.624457E+09 | 47670200.33 | 0.256767E+09 | 77806700.21 | 0.178961E+09 | 0.00 | 0.00 |
| May | 0.603221E+09 | 4550275.94 | 0.185984E+09 | 14437677.05 | 0.171546E+09 | 0.00 | 0.00 |
| June | 0.575543E+09 | 4326286.65 | 0.164493E+09 | 3353335.34 | 0.161140E+09 | 0.00 | 0.00 |
| July | 0.553398E+09 | 673501.16 | 0.176248E+09 | 1962822.04 | 0.174285E+09 | 0.00 | 0.00 |
| August | 0.506163E+09 | 2637277.70 | 0.185183E+09 | 7763252.03 | 0.177420E+09 | 0.00 | 0.00 |
| September | 0.559434E+09 | 14670961.23 | 0.251278E+09 | 71196446.15 | 0.180081E+09 | 0.00 | 0.00 |
| October | 0.819032E+09 | 0.128122E+09 | 0.428869E+09 | 0.237960E+09 | 0.190909E+09 | 0.00 | 0.00 |
| November | 0.868697E+09 | 0.254976E+09 | 0.524493E+09 | 0.347337E+09 | 0.177156E+09 | 0.00 | 0.00 |
| December | 0.692938E+09 | 0.375625E+09 | 0.480605E+09 | 0.300743E+09 | 0.179862E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.766526E+10 | 0.164819E+10 | 0.385029E+10 | 0.170512E+10 | 0.214517E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.506163E+09 | 673501.16 | 0.164493E+09 | 1962822.04 | 0.161140E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.868697E+09 | 0.380873E+09 | 0.524493E+09 | 0.347337E+09 | 0.204667E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: M SW APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.761642E+09 | 0.628667E+09 | 0.584960E+09 | 0.324458E+09 | 0.260502E+09 | 0.00 | 0.00 |
| February | 0.777145E+09 | 0.442244E+09 | 0.531813E+09 | 0.270475E+09 | 0.261338E+09 | 0.00 | 0.00 |
| March | 0.979958E+09 | 0.278887E+09 | 0.560873E+09 | 0.234458E+09 | 0.326414E+09 | 0.00 | 0.00 |
| April | 0.112492E+10 | 77986762.81 | 0.494841E+09 | 0.189246E+09 | 0.305596E+09 | 0.00 | 0.00 |
| May | 0.119220E+10 | 7096085.96 | 0.419011E+09 | 0.113127E+09 | 0.305885E+09 | 0.00 | 0.00 |
| June | 0.114823E+10 | 6316986.08 | 0.377222E+09 | 86396488.98 | 0.290826E+09 | 0.00 | 0.00 |
| July | 0.101246E+10 | 882249.27 | 0.338765E+09 | 33482596.11 | 0.305282E+09 | 0.00 | 0.00 |
| August | 0.899515E+09 | 2718003.68 | 0.334202E+09 | 33918591.24 | 0.300284E+09 | 0.00 | 0.00 |
| September | 0.914708E+09 | 17553925.69 | 0.410569E+09 | 0.118330E+09 | 0.292239E+09 | 0.00 | 0.00 |
| October | 0.114954E+10 | 0.200923E+09 | 0.599726E+09 | 0.305940E+09 | 0.293787E+09 | 0.00 | 0.00 |
| November | 0.109859E+10 | 0.414350E+09 | 0.674052E+09 | 0.411048E+09 | 0.263004E+09 | 0.00 | 0.00 |
| December | 0.837277E+09 | 0.609498E+09 | 0.613021E+09 | 0.351314E+09 | 0.261707E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.118962E+11 | 0.268712E+10 | 0.593906E+10 | 0.247219E+10 | 0.346686E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.761642E+09 | 882249.27 | 0.334202E+09 | 33482596.11 | 0.260502E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.119220E+10 | 0.628667E+09 | 0.674052E+09 | 0.411048E+09 | 0.326414E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: M NW APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.217663E+09 | 0.630006E+09 | 0.235850E+09 | 53149103.01 | 0.182701E+09 | 0.00 | 0.00 |
| February | 0.296530E+09 | 0.448030E+09 | 0.247232E+09 | 51891941.89 | 0.195340E+09 | 0.00 | 0.00 |
| March | 0.568316E+09 | 0.277547E+09 | 0.345261E+09 | 81809097.59 | 0.263451E+09 | 0.00 | 0.00 |
| April | 0.893096E+09 | 74835024.21 | 0.387208E+09 | 0.112181E+09 | 0.275027E+09 | 0.00 | 0.00 |
| May | 0.115370E+10 | 7137561.22 | 0.403899E+09 | 0.103976E+09 | 0.299922E+09 | 0.00 | 0.00 |
| June | 0.115845E+10 | 6306179.58 | 0.382919E+09 | 88948912.87 | 0.293970E+09 | 0.00 | 0.00 |
| July | 0.100571E+10 | 878655.46 | 0.336693E+09 | 34514780.20 | 0.302178E+09 | 0.00 | 0.00 |
| August | 0.848583E+09 | 2645914.99 | 0.309195E+09 | 27048538.08 | 0.282147E+09 | 0.00 | 0.00 |
| September | 0.695169E+09 | 16478428.83 | 0.296957E+09 | 47151346.63 | 0.249806E+09 | 0.00 | 0.00 |
| October | 0.586419E+09 | 0.198385E+09 | 0.294082E+09 | 67979562.24 | 0.226103E+09 | 0.00 | 0.00 |
| November | 0.367864E+09 | 0.419663E+09 | 0.250565E+09 | 63710905.93 | 0.186854E+09 | 0.00 | 0.00 |
| December | 0.218545E+09 | 0.617297E+09 | 0.229140E+09 | 50570362.82 | 0.178570E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.801005E+10 | 0.269921E+10 | 0.371900E+10 | 0.782932E+09 | 0.293607E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.217663E+09 | 878655.46 | 0.229140E+09 | 27048538.08 | 0.178570E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.115845E+10 | 0.630006E+09 | 0.403899E+09 | 0.112181E+09 | 0.302178E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: M SE APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.752244E+09 | 0.614447E+09 | 0.588451E+09 | 0.327849E+09 | 0.260602E+09 | 0.00 | 0.00 |
| February | 0.784646E+09 | 0.429658E+09 | 0.544034E+09 | 0.281677E+09 | 0.262356E+09 | 0.00 | 0.00 |
| March | 0.974015E+09 | 0.265773E+09 | 0.564533E+09 | 0.238085E+09 | 0.326447E+09 | 0.00 | 0.00 |
| April | 0.112346E+10 | 74763432.74 | 0.496051E+09 | 0.189578E+09 | 0.306473E+09 | 0.00 | 0.00 |
| May | 0.120707E+10 | 6768855.84 | 0.428563E+09 | 0.121992E+09 | 0.306571E+09 | 0.00 | 0.00 |
| June | 0.110927E+10 | 6257482.24 | 0.355466E+09 | 66690861.17 | 0.288775E+09 | 0.00 | 0.00 |
| July | 0.102075E+10 | 857403.34 | 0.341911E+09 | 36764715.99 | 0.305146E+09 | 0.00 | 0.00 |
| August | 0.899461E+09 | 2650195.01 | 0.334596E+09 | 33637685.93 | 0.300958E+09 | 0.00 | 0.00 |
| September | 0.905166E+09 | 17033403.67 | 0.405472E+09 | 0.113932E+09 | 0.291540E+09 | 0.00 | 0.00 |
| October | 0.115115E+10 | 0.196458E+09 | 0.603740E+09 | 0.308675E+09 | 0.295064E+09 | 0.00 | 0.00 |
| November | 0.108828E+10 | 0.404897E+09 | 0.674151E+09 | 0.411442E+09 | 0.262709E+09 | 0.00 | 0.00 |
| December | 0.833598E+09 | 0.600994E+09 | 0.615426E+09 | 0.354107E+09 | 0.261319E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.118491E+11 | 0.262056E+10 | 0.595239E+10 | 0.248443E+10 | 0.346796E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.752244E+09 | 857403.34 | 0.334596E+09 | 33637685.93 | 0.260602E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.120707E+10 | 0.614447E+09 | 0.674151E+09 | 0.411442E+09 | 0.326447E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: M NE APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.184153E+09 | 0.592257E+09 | 0.239342E+09 | 56539698.18 | 0.182802E+09 | 0.00 | 0.00 |
| February | 0.288612E+09 | 0.422037E+09 | 0.259452E+09 | 63094222.38 | 0.196358E+09 | 0.00 | 0.00 |
| March | 0.558432E+09 | 0.260799E+09 | 0.348921E+09 | 85436118.98 | 0.263484E+09 | 0.00 | 0.00 |
| April | 0.892343E+09 | 72370628.58 | 0.388417E+09 | 0.112513E+09 | 0.275904E+09 | 0.00 | 0.00 |
| May | 0.116866E+10 | 6887923.05 | 0.413450E+09 | 0.112841E+09 | 0.300608E+09 | 0.00 | 0.00 |
| June | 0.111948E+10 | 6226667.57 | 0.361163E+09 | 69243285.06 | 0.291919E+09 | 0.00 | 0.00 |
| July | 0.101400E+10 | 854785.32 | 0.339839E+09 | 37796900.09 | 0.302042E+09 | 0.00 | 0.00 |
| August | 0.848534E+09 | 2595830.47 | 0.309589E+09 | 26767632.77 | 0.282821E+09 | 0.00 | 0.00 |
| September | 0.685619E+09 | 15942391.38 | 0.291860E+09 | 42752943.39 | 0.249107E+09 | 0.00 | 0.00 |
| October | 0.585322E+09 | 0.191284E+09 | 0.298096E+09 | 70715302.48 | 0.227380E+09 | 0.00 | 0.00 |
| November | 0.346947E+09 | 0.400146E+09 | 0.250664E+09 | 64104976.85 | 0.186559E+09 | 0.00 | 0.00 |
| December | 0.198382E+09 | 0.594245E+09 | 0.231546E+09 | 53363630.86 | 0.178182E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.789049E+10 | 0.256565E+10 | 0.373234E+10 | 0.795169E+09 | 0.293717E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.184153E+09 | 854785.32 | 0.231546E+09 | 26767632.77 | 0.178182E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.116866E+10 | 0.594245E+09 | 0.413450E+09 | 0.112841E+09 | 0.302042E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: M N1 APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 56674972.49 | 0.404601E+09 | 99151823.08 | 0.00 | 99151823.08 | 0.00 | 0.00 |
| February | 0.101798E+09 | 0.280518E+09 | 0.106199E+09 | 0.00 | 0.106199E+09 | 0.00 | 0.00 |
| March | 0.225329E+09 | 0.167698E+09 | 0.141718E+09 | 13520.81 | 0.141704E+09 | 0.00 | 0.00 |
| April | 0.392513E+09 | 43630475.41 | 0.149133E+09 | 741838.03 | 0.148392E+09 | 0.00 | 0.00 |
| May | 0.574184E+09 | 3930698.84 | 0.170871E+09 | 5287419.98 | 0.165583E+09 | 0.00 | 0.00 |
| June | 0.598299E+09 | 3599050.58 | 0.170190E+09 | 5905759.23 | 0.164284E+09 | 0.00 | 0.00 |
| July | 0.563389E+09 | 508227.74 | 0.174176E+09 | 2995006.13 | 0.171181E+09 | 0.00 | 0.00 |
| August | 0.470680E+09 | 1424707.09 | 0.160176E+09 | 893198.87 | 0.159283E+09 | 0.00 | 0.00 |
| September | 0.349656E+09 | 9192668.26 | 0.137666E+09 | 17478.26 | 0.137648E+09 | 0.00 | 0.00 |
| October | 0.255800E+09 | 0.118802E+09 | 0.123225E+09 | 0.00 | 0.123225E+09 | 0.00 | 0.00 |
| November | 0.129643E+09 | 0.256998E+09 | 0.101006E+09 | 0.00 | 0.101006E+09 | 0.00 | 0.00 |
| December | 61230105.19 | 0.395846E+09 | 96724368.79 | 0.00 | 96724368.79 | 0.00 | 0.00 |
| Annual Sum or Average | 0.377920E+10 | 0.168675E+10 | 0.163024E+10 | 15854221.32 | 0.161438E+10 | 0.00 | 0.00 |
| Minimum of Months | 56674972.49 | 508227.74 | 96724368.79 | 0.00 | 96724368.79 | 0.00 | 0.00 |
| Maximum of Months | 0.598299E+09 | 0.404601E+09 | 0.174176E+09 | 5905759.23 | 0.171181E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: M N2 APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 56546401.52 | 0.404690E+09 | 99151823.08 | 0.00 | 99151823.08 | 0.00 | 0.00 |
| February | 0.101696E+09 | 0.280597E+09 | 0.106199E+09 | 0.00 | 0.106199E+09 | 0.00 | 0.00 |
| March | 0.225284E+09 | 0.167683E+09 | 0.141718E+09 | 13520.81 | 0.141704E+09 | 0.00 | 0.00 |
| April | 0.392488E+09 | 43619591.18 | 0.149133E+09 | 741838.03 | 0.148392E+09 | 0.00 | 0.00 |
| May | 0.574167E+09 | 3928033.03 | 0.170871E+09 | 5287419.98 | 0.165583E+09 | 0.00 | 0.00 |
| June | 0.598316E+09 | 3596728.32 | 0.170190E+09 | 5905759.23 | 0.164284E+09 | 0.00 | 0.00 |
| July | 0.563386E+09 | 508176.15 | 0.174176E+09 | 2995006.13 | 0.171181E+09 | 0.00 | 0.00 |
| August | 0.470677E+09 | 1425033.11 | 0.160176E+09 | 893198.87 | 0.159283E+09 | 0.00 | 0.00 |
| September | 0.349656E+09 | 9187071.61 | 0.137666E+09 | 17478.26 | 0.137648E+09 | 0.00 | 0.00 |
| October | 0.255773E+09 | 0.118790E+09 | 0.123225E+09 | 0.00 | 0.123225E+09 | 0.00 | 0.00 |
| November | 0.129603E+09 | 0.256986E+09 | 0.101006E+09 | 0.00 | 0.101006E+09 | 0.00 | 0.00 |
| December | 61128912.50 | 0.395922E+09 | 96724368.79 | 0.00 | 96724368.79 | 0.00 | 0.00 |
| Annual Sum or Average | 0.377872E+10 | 0.168693E+10 | 0.163024E+10 | 15854221.32 | 0.161438E+10 | 0.00 | 0.00 |
| Minimum of Months | 56546401.52 | 508176.15 | 96724368.79 | 0.00 | 96724368.79 | 0.00 | 0.00 |
| Maximum of Months | 0.598316E+09 | 0.404690E+09 | 0.174176E+09 | 5905759.23 | 0.171181E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: M S1 APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.617305E+09 | 0.384726E+09 | 0.448261E+09 | 0.271309E+09 | 0.176952E+09 | 0.00 | 0.00 |
| February | 0.591927E+09 | 0.268935E+09 | 0.390780E+09 | 0.218583E+09 | 0.172197E+09 | 0.00 | 0.00 |
| March | 0.641252E+09 | 0.167460E+09 | 0.357330E+09 | 0.152663E+09 | 0.204667E+09 | 0.00 | 0.00 |
| April | 0.626221E+09 | 46097157.69 | 0.256767E+09 | 77806700.21 | 0.178961E+09 | 0.00 | 0.00 |
| May | 0.613136E+09 | 3853428.15 | 0.185984E+09 | 14437677.05 | 0.171546E+09 | 0.00 | 0.00 |
| June | 0.588026E+09 | 3619921.66 | 0.164493E+09 | 3353335.34 | 0.161140E+09 | 0.00 | 0.00 |
| July | 0.570243E+09 | 512446.78 | 0.176248E+09 | 1962822.04 | 0.174285E+09 | 0.00 | 0.00 |
| August | 0.522116E+09 | 1464248.60 | 0.185183E+09 | 7763252.03 | 0.177420E+09 | 0.00 | 0.00 |
| September | 0.571172E+09 | 9929195.72 | 0.251278E+09 | 71196446.15 | 0.180081E+09 | 0.00 | 0.00 |
| October | 0.823758E+09 | 0.119719E+09 | 0.428869E+09 | 0.237960E+09 | 0.190909E+09 | 0.00 | 0.00 |
| November | 0.869564E+09 | 0.248889E+09 | 0.524493E+09 | 0.347337E+09 | 0.177156E+09 | 0.00 | 0.00 |
| December | 0.692065E+09 | 0.372043E+09 | 0.480605E+09 | 0.300743E+09 | 0.179862E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.772679E+10 | 0.162725E+10 | 0.385029E+10 | 0.170512E+10 | 0.214517E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.522116E+09 | 512446.78 | 0.164493E+09 | 1962822.04 | 0.161140E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.869564E+09 | 0.384726E+09 | 0.524493E+09 | 0.347337E+09 | 0.204667E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: M S2 APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.617241E+09 | 0.384726E+09 | 0.448261E+09 | 0.271309E+09 | 0.176952E+09 | 0.00 | 0.00 |
| February | 0.591882E+09 | 0.268932E+09 | 0.390780E+09 | 0.218583E+09 | 0.172197E+09 | 0.00 | 0.00 |
| March | 0.641216E+09 | 0.167442E+09 | 0.357330E+09 | 0.152663E+09 | 0.204667E+09 | 0.00 | 0.00 |
| April | 0.626198E+09 | 46085504.67 | 0.256767E+09 | 77806700.21 | 0.178961E+09 | 0.00 | 0.00 |
| May | 0.613120E+09 | 3850741.01 | 0.185984E+09 | 14437677.05 | 0.171546E+09 | 0.00 | 0.00 |
| June | 0.588044E+09 | 3617556.10 | 0.164493E+09 | 3353335.34 | 0.161140E+09 | 0.00 | 0.00 |
| July | 0.570241E+09 | 512392.97 | 0.176248E+09 | 1962822.04 | 0.174285E+09 | 0.00 | 0.00 |
| August | 0.522113E+09 | 1464589.34 | 0.185183E+09 | 7763252.03 | 0.177420E+09 | 0.00 | 0.00 |
| September | 0.571171E+09 | 9923450.08 | 0.251278E+09 | 71196446.15 | 0.180081E+09 | 0.00 | 0.00 |
| October | 0.823736E+09 | 0.119706E+09 | 0.428869E+09 | 0.237960E+09 | 0.190909E+09 | 0.00 | 0.00 |
| November | 0.869540E+09 | 0.248871E+09 | 0.524493E+09 | 0.347337E+09 | 0.177156E+09 | 0.00 | 0.00 |
| December | 0.692026E+09 | 0.372030E+09 | 0.480605E+09 | 0.300743E+09 | 0.179862E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.772653E+10 | 0.162716E+10 | 0.385029E+10 | 0.170512E+10 | 0.214517E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.522113E+09 | 512392.97 | 0.164493E+09 | 1962822.04 | 0.161140E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.869540E+09 | 0.384726E+09 | 0.524493E+09 | 0.347337E+09 | 0.204667E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: T SW APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.781114E+09 | 0.547936E+09 | 0.584960E+09 | 0.324458E+09 | 0.260502E+09 | 0.00 | 0.00 |
| February | 0.786167E+09 | 0.390160E+09 | 0.531813E+09 | 0.270475E+09 | 0.261338E+09 | 0.00 | 0.00 |
| March | 0.968400E+09 | 0.259919E+09 | 0.560873E+09 | 0.234458E+09 | 0.326414E+09 | 0.00 | 0.00 |
| April | 0.109921E+10 | 73745574.99 | 0.494841E+09 | 0.189246E+09 | 0.305596E+09 | 0.00 | 0.00 |
| May | 0.116071E+10 | 6654679.57 | 0.419011E+09 | 0.113127E+09 | 0.305885E+09 | 0.00 | 0.00 |
| June | 0.111558E+10 | 6262284.35 | 0.377222E+09 | 86396488.98 | 0.290826E+09 | 0.00 | 0.00 |
| July | 0.982785E+09 | 829270.38 | 0.338765E+09 | 33482596.11 | 0.305282E+09 | 0.00 | 0.00 |
| August | 0.873546E+09 | 2666350.39 | 0.334202E+09 | 33918591.24 | 0.300284E+09 | 0.00 | 0.00 |
| September | 0.893089E+09 | 16345846.76 | 0.410569E+09 | 0.118330E+09 | 0.292239E+09 | 0.00 | 0.00 |
| October | 0.113207E+10 | 0.190730E+09 | 0.599726E+09 | 0.305940E+09 | 0.293787E+09 | 0.00 | 0.00 |
| November | 0.109766E+10 | 0.377419E+09 | 0.674052E+09 | 0.411048E+09 | 0.263004E+09 | 0.00 | 0.00 |
| December | 0.858214E+09 | 0.532586E+09 | 0.613021E+09 | 0.351314E+09 | 0.261707E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.117485E+11 | 0.240525E+10 | 0.593906E+10 | 0.247219E+10 | 0.346686E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.781114E+09 | 829270.38 | 0.334202E+09 | 33482596.11 | 0.260502E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.116071E+10 | 0.547936E+09 | 0.674052E+09 | 0.411048E+09 | 0.326414E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: T NW APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.233238E+09 | 0.554552E+09 | 0.235850E+09 | 53149103.01 | 0.182701E+09 | 0.00 | 0.00 |
| February | 0.308986E+09 | 0.390956E+09 | 0.247232E+09 | 51891941.89 | 0.195340E+09 | 0.00 | 0.00 |
| March | 0.561733E+09 | 0.256597E+09 | 0.345261E+09 | 81809097.59 | 0.263451E+09 | 0.00 | 0.00 |
| April | 0.869909E+09 | 71006406.86 | 0.387208E+09 | 0.112181E+09 | 0.275027E+09 | 0.00 | 0.00 |
| May | 0.112243E+10 | 6748505.19 | 0.403899E+09 | 0.103976E+09 | 0.299922E+09 | 0.00 | 0.00 |
| June | 0.112581E+10 | 6254424.44 | 0.382919E+09 | 88948912.87 | 0.293970E+09 | 0.00 | 0.00 |
| July | 0.976025E+09 | 823722.83 | 0.336693E+09 | 34514780.20 | 0.302178E+09 | 0.00 | 0.00 |
| August | 0.822978E+09 | 2597841.62 | 0.309195E+09 | 27048538.08 | 0.282147E+09 | 0.00 | 0.00 |
| September | 0.675703E+09 | 15531553.38 | 0.296957E+09 | 47151346.63 | 0.249806E+09 | 0.00 | 0.00 |
| October | 0.574330E+09 | 0.187994E+09 | 0.294082E+09 | 67979562.24 | 0.226103E+09 | 0.00 | 0.00 |
| November | 0.374759E+09 | 0.373914E+09 | 0.250565E+09 | 63710905.93 | 0.186854E+09 | 0.00 | 0.00 |
| December | 0.241730E+09 | 0.530044E+09 | 0.229140E+09 | 50570362.82 | 0.178570E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.788763E+10 | 0.239702E+10 | 0.371900E+10 | 0.782932E+09 | 0.293607E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.233238E+09 | 823722.83 | 0.229140E+09 | 27048538.08 | 0.178570E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.112581E+10 | 0.554552E+09 | 0.403899E+09 | 0.112181E+09 | 0.302178E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: T SE APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.773921E+09 | 0.536816E+09 | 0.588451E+09 | 0.327849E+09 | 0.260602E+09 | 0.00 | 0.00 |
| February | 0.794397E+09 | 0.380381E+09 | 0.544034E+09 | 0.281677E+09 | 0.262356E+09 | 0.00 | 0.00 |
| March | 0.963398E+09 | 0.248770E+09 | 0.564533E+09 | 0.238085E+09 | 0.326447E+09 | 0.00 | 0.00 |
| April | 0.109767E+10 | 70796517.35 | 0.496051E+09 | 0.189578E+09 | 0.306473E+09 | 0.00 | 0.00 |
| May | 0.117491E+10 | 6321537.73 | 0.428563E+09 | 0.121992E+09 | 0.306571E+09 | 0.00 | 0.00 |
| June | 0.107662E+10 | 6225135.14 | 0.355466E+09 | 66690861.17 | 0.288775E+09 | 0.00 | 0.00 |
| July | 0.990962E+09 | 803444.19 | 0.341911E+09 | 36764715.99 | 0.305146E+09 | 0.00 | 0.00 |
| August | 0.873379E+09 | 2581073.51 | 0.334596E+09 | 33637685.93 | 0.300958E+09 | 0.00 | 0.00 |
| September | 0.883471E+09 | 15826737.39 | 0.405472E+09 | 0.113932E+09 | 0.291540E+09 | 0.00 | 0.00 |
| October | 0.113364E+10 | 0.186537E+09 | 0.603740E+09 | 0.308675E+09 | 0.295064E+09 | 0.00 | 0.00 |
| November | 0.108724E+10 | 0.368949E+09 | 0.674151E+09 | 0.411442E+09 | 0.262709E+09 | 0.00 | 0.00 |
| December | 0.854647E+09 | 0.525908E+09 | 0.615426E+09 | 0.354107E+09 | 0.261319E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.117043E+11 | 0.234991E+10 | 0.595239E+10 | 0.248443E+10 | 0.346796E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.773921E+09 | 803444.19 | 0.334596E+09 | 33637685.93 | 0.260602E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.117491E+10 | 0.536816E+09 | 0.674151E+09 | 0.411442E+09 | 0.326447E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: T NE APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.206847E+09 | 0.520657E+09 | 0.239342E+09 | 56539698.18 | 0.182802E+09 | 0.00 | 0.00 |
| February | 0.305756E+09 | 0.370728E+09 | 0.259452E+09 | 63094222.38 | 0.196358E+09 | 0.00 | 0.00 |
| March | 0.553429E+09 | 0.242810E+09 | 0.348921E+09 | 85436118.98 | 0.263484E+09 | 0.00 | 0.00 |
| April | 0.868994E+09 | 68727294.98 | 0.388417E+09 | 0.112513E+09 | 0.275904E+09 | 0.00 | 0.00 |
| May | 0.113674E+10 | 6482563.01 | 0.413450E+09 | 0.112841E+09 | 0.300608E+09 | 0.00 | 0.00 |
| June | 0.108681E+10 | 6172487.62 | 0.361163E+09 | 69243285.06 | 0.291919E+09 | 0.00 | 0.00 |
| July | 0.984215E+09 | 798953.11 | 0.339839E+09 | 37796900.09 | 0.302042E+09 | 0.00 | 0.00 |
| August | 0.822801E+09 | 2524213.64 | 0.309589E+09 | 26767632.77 | 0.282821E+09 | 0.00 | 0.00 |
| September | 0.666079E+09 | 15001636.23 | 0.291860E+09 | 42752943.39 | 0.249107E+09 | 0.00 | 0.00 |
| October | 0.573462E+09 | 0.181574E+09 | 0.298096E+09 | 70715302.48 | 0.227380E+09 | 0.00 | 0.00 |
| November | 0.356573E+09 | 0.358730E+09 | 0.250664E+09 | 64104976.85 | 0.186559E+09 | 0.00 | 0.00 |
| December | 0.228004E+09 | 0.511983E+09 | 0.231546E+09 | 53363630.86 | 0.178182E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.778972E+10 | 0.228619E+10 | 0.373234E+10 | 0.795169E+09 | 0.293717E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.206847E+09 | 798953.11 | 0.231546E+09 | 26767632.77 | 0.178182E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.113674E+10 | 0.520657E+09 | 0.413450E+09 | 0.112841E+09 | 0.302042E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: T N1 APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 70074720.60 | 0.348319E+09 | 99151823.08 | 0.00 | 99151823.08 | 0.00 | 0.00 |
| February | 0.110953E+09 | 0.245275E+09 | 0.106199E+09 | 0.00 | 0.106199E+09 | 0.00 | 0.00 |
| March | 0.222350E+09 | 0.157996E+09 | 0.141718E+09 | 13520.81 | 0.141704E+09 | 0.00 | 0.00 |
| April | 0.380925E+09 | 42074525.73 | 0.149133E+09 | 741838.03 | 0.148392E+09 | 0.00 | 0.00 |
| May | 0.557590E+09 | 3846949.02 | 0.170871E+09 | 5287419.98 | 0.165583E+09 | 0.00 | 0.00 |
| June | 0.580827E+09 | 3697332.06 | 0.170190E+09 | 5905759.23 | 0.164284E+09 | 0.00 | 0.00 |
| July | 0.547285E+09 | 484526.43 | 0.174176E+09 | 2995006.13 | 0.171181E+09 | 0.00 | 0.00 |
| August | 0.456785E+09 | 1451306.47 | 0.160176E+09 | 893198.87 | 0.159283E+09 | 0.00 | 0.00 |
| September | 0.339481E+09 | 8928905.75 | 0.137666E+09 | 17478.26 | 0.137648E+09 | 0.00 | 0.00 |
| October | 0.249900E+09 | 0.113985E+09 | 0.123225E+09 | 0.00 | 0.123225E+09 | 0.00 | 0.00 |
| November | 0.134008E+09 | 0.233031E+09 | 0.101006E+09 | 0.00 | 0.101006E+09 | 0.00 | 0.00 |
| December | 77389816.54 | 0.334467E+09 | 96724368.79 | 0.00 | 96724368.79 | 0.00 | 0.00 |
| Annual Sum or Average | 0.372757E+10 | 0.149356E+10 | 0.163024E+10 | 15854221.32 | 0.161438E+10 | 0.00 | 0.00 |
| Minimum of Months | 70074720.60 | 484526.43 | 96724368.79 | 0.00 | 96724368.79 | 0.00 | 0.00 |
| Maximum of Months | 0.580827E+09 | 0.348319E+09 | 0.174176E+09 | 5905759.23 | 0.171181E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: T N2 APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 69829068.66 | 0.348096E+09 | 99151823.08 | 0.00 | 99151823.08 | 0.00 | 0.00 |
| February | 0.110646E+09 | 0.245251E+09 | 0.106199E+09 | 0.00 | 0.106199E+09 | 0.00 | 0.00 |
| March | 0.222181E+09 | 0.157926E+09 | 0.141718E+09 | 13520.81 | 0.141704E+09 | 0.00 | 0.00 |
| April | 0.380870E+09 | 42043593.82 | 0.149133E+09 | 741838.03 | 0.148392E+09 | 0.00 | 0.00 |
| May | 0.557563E+09 | 3841200.85 | 0.170871E+09 | 5287419.98 | 0.165583E+09 | 0.00 | 0.00 |
| June | 0.580848E+09 | 3693438.48 | 0.170190E+09 | 5905759.23 | 0.164284E+09 | 0.00 | 0.00 |
| July | 0.547283E+09 | 484513.53 | 0.174176E+09 | 2995006.13 | 0.171181E+09 | 0.00 | 0.00 |
| August | 0.456780E+09 | 1451347.50 | 0.160176E+09 | 893198.87 | 0.159283E+09 | 0.00 | 0.00 |
| September | 0.339475E+09 | 8917978.17 | 0.137666E+09 | 17478.26 | 0.137648E+09 | 0.00 | 0.00 |
| October | 0.249824E+09 | 0.113940E+09 | 0.123225E+09 | 0.00 | 0.123225E+09 | 0.00 | 0.00 |
| November | 0.133809E+09 | 0.232953E+09 | 0.101006E+09 | 0.00 | 0.101006E+09 | 0.00 | 0.00 |
| December | 77110979.11 | 0.334317E+09 | 96724368.79 | 0.00 | 96724368.79 | 0.00 | 0.00 |
| Annual Sum or Average | 0.372622E+10 | 0.149292E+10 | 0.163024E+10 | 15854221.32 | 0.161438E+10 | 0.00 | 0.00 |
| Minimum of Months | 69829068.66 | 484513.53 | 96724368.79 | 0.00 | 96724368.79 | 0.00 | 0.00 |
| Maximum of Months | 0.580848E+09 | 0.348096E+09 | 0.174176E+09 | 5905759.23 | 0.171181E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: T S1 APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.632673E+09 | 0.336928E+09 | 0.448261E+09 | 0.271309E+09 | 0.176952E+09 | 0.00 | 0.00 |
| February | 0.597924E+09 | 0.240956E+09 | 0.390780E+09 | 0.218583E+09 | 0.172197E+09 | 0.00 | 0.00 |
| March | 0.635005E+09 | 0.159163E+09 | 0.357330E+09 | 0.152663E+09 | 0.204667E+09 | 0.00 | 0.00 |
| April | 0.612934E+09 | 44291506.89 | 0.256767E+09 | 77806700.21 | 0.178961E+09 | 0.00 | 0.00 |
| May | 0.596421E+09 | 3727204.46 | 0.185984E+09 | 14437677.05 | 0.171546E+09 | 0.00 | 0.00 |
| June | 0.570561E+09 | 3731368.09 | 0.164493E+09 | 3353335.34 | 0.161140E+09 | 0.00 | 0.00 |
| July | 0.554165E+09 | 490425.30 | 0.176248E+09 | 1962822.04 | 0.174285E+09 | 0.00 | 0.00 |
| August | 0.508025E+09 | 1499406.93 | 0.185183E+09 | 7763252.03 | 0.177420E+09 | 0.00 | 0.00 |
| September | 0.559541E+09 | 9507750.16 | 0.251278E+09 | 71196446.15 | 0.180081E+09 | 0.00 | 0.00 |
| October | 0.814456E+09 | 0.115002E+09 | 0.428869E+09 | 0.237960E+09 | 0.190909E+09 | 0.00 | 0.00 |
| November | 0.868437E+09 | 0.231563E+09 | 0.524493E+09 | 0.347337E+09 | 0.177156E+09 | 0.00 | 0.00 |
| December | 0.706167E+09 | 0.329214E+09 | 0.480605E+09 | 0.300743E+09 | 0.179862E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.765631E+10 | 0.147607E+10 | 0.385029E+10 | 0.170512E+10 | 0.214517E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.508025E+09 | 490425.30 | 0.164493E+09 | 1962822.04 | 0.161140E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.868437E+09 | 0.336928E+09 | 0.524493E+09 | 0.347337E+09 | 0.204667E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: T S2 APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.632420E+09 | 0.336838E+09 | 0.448261E+09 | 0.271309E+09 | 0.176952E+09 | 0.00 | 0.00 |
| February | 0.597728E+09 | 0.240901E+09 | 0.390780E+09 | 0.218583E+09 | 0.172197E+09 | 0.00 | 0.00 |
| March | 0.634881E+09 | 0.159091E+09 | 0.357330E+09 | 0.152663E+09 | 0.204667E+09 | 0.00 | 0.00 |
| April | 0.612885E+09 | 44259812.08 | 0.256767E+09 | 77806700.21 | 0.178961E+09 | 0.00 | 0.00 |
| May | 0.596394E+09 | 3721402.07 | 0.185984E+09 | 14437677.05 | 0.171546E+09 | 0.00 | 0.00 |
| June | 0.570583E+09 | 3727114.17 | 0.164493E+09 | 3353335.34 | 0.161140E+09 | 0.00 | 0.00 |
| July | 0.554162E+09 | 490411.25 | 0.176248E+09 | 1962822.04 | 0.174285E+09 | 0.00 | 0.00 |
| August | 0.508021E+09 | 1499461.03 | 0.185183E+09 | 7763252.03 | 0.177420E+09 | 0.00 | 0.00 |
| September | 0.559536E+09 | 9496748.37 | 0.251278E+09 | 71196446.15 | 0.180081E+09 | 0.00 | 0.00 |
| October | 0.814397E+09 | 0.114958E+09 | 0.428869E+09 | 0.237960E+09 | 0.190909E+09 | 0.00 | 0.00 |
| November | 0.868333E+09 | 0.231480E+09 | 0.524493E+09 | 0.347337E+09 | 0.177156E+09 | 0.00 | 0.00 |
| December | 0.705970E+09 | 0.329115E+09 | 0.480605E+09 | 0.300743E+09 | 0.179862E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.765531E+10 | 0.147558E+10 | 0.385029E+10 | 0.170512E+10 | 0.214517E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.508021E+09 | 490411.25 | 0.164493E+09 | 1962822.04 | 0.161140E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.868333E+09 | 0.336838E+09 | 0.524493E+09 | 0.347337E+09 | 0.204667E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: T CORRIDOR
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 36693158.65 | 56062346.11 | 33639117.77 | 13566930.72 | 20072187.05 | 0.00 | 0.00 |
| February | 48252064.13 | 40750688.74 | 36773836.59 | 15139715.48 | 21634121.11 | 0.00 | 0.00 |
| March | 78732901.62 | 28121378.10 | 49719189.67 | 20497500.13 | 29221689.54 | 0.00 | 0.00 |
| April | 0.113240E+09 | 9782443.09 | 57417101.96 | 26819896.19 | 30597205.77 | 0.00 | 0.00 |
| May | 0.132099E+09 | 1671597.26 | 58207818.60 | 25808017.15 | 32399801.45 | 0.00 | 0.00 |
| June | 0.113957E+09 | 1443598.01 | 45824639.87 | 15198097.13 | 30626542.74 | 0.00 | 0.00 |
| July | 96241970.20 | 322155.85 | 39751489.86 | 8350856.11 | 31400633.75 | 0.00 | 0.00 |
| August | 80293751.62 | 1267335.18 | 35852171.33 | 6208675.73 | 29643495.59 | 0.00 | 0.00 |
| September | 73152819.84 | 4481931.09 | 36999575.50 | 10254548.81 | 26745026.69 | 0.00 | 0.00 |
| October | 75504398.95 | 22220494.88 | 41960976.56 | 16968424.67 | 24992551.89 | 0.00 | 0.00 |
| November | 53230212.19 | 39673256.23 | 35911060.25 | 15382250.13 | 20528810.12 | 0.00 | 0.00 |
| December | 38147336.18 | 55374051.42 | 32350961.84 | 12804820.44 | 19546141.40 | 0.00 | 0.00 |
| Annual Sum or Average | 0.939545E+09 | 0.261171E+09 | 0.504408E+09 | 0.187000E+09 | 0.317408E+09 | 0.00 | 0.00 |
| Minimum of Months | 36693158.65 | 322155.85 | 32350961.84 | 6208675.73 | 19546141.40 | 0.00 | 0.00 |
| Maximum of Months | 0.132099E+09 | 56062346.11 | 58207818.60 | 26819896.19 | 32399801.45 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: G CORRIDOR
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.104522E+09 | 0.175950E+09 | 0.100186E+09 | 40405695.99 | 59779968.27 | 0.00 | 0.00 |
| February | 0.140352E+09 | 0.127066E+09 | 0.109522E+09 | 45089840.41 | 64431796.61 | 0.00 | 0.00 |
| March | 0.232488E+09 | 87332306.59 | 0.148076E+09 | 61046656.47 | 87029463.66 | 0.00 | 0.00 |
| April | 0.328950E+09 | 34142839.78 | 0.171002E+09 | 79876325.33 | 91126093.31 | 0.00 | 0.00 |
| May | 0.375916E+09 | 8820301.73 | 0.173357E+09 | 76862697.73 | 96494671.85 | 0.00 | 0.00 |
| June | 0.320022E+09 | 6826228.95 | 0.136477E+09 | 45263715.50 | 91213466.10 | 0.00 | 0.00 |
| July | 0.267619E+09 | 2758403.92 | 0.118390E+09 | 24870927.72 | 93518901.77 | 0.00 | 0.00 |
| August | 0.224294E+09 | 7515115.81 | 0.106777E+09 | 18490981.45 | 88285707.06 | 0.00 | 0.00 |
| September | 0.206721E+09 | 21728561.96 | 0.110194E+09 | 30540598.33 | 79653345.35 | 0.00 | 0.00 |
| October | 0.216057E+09 | 76499363.29 | 0.124970E+09 | 50536191.48 | 74434039.26 | 0.00 | 0.00 |
| November | 0.150425E+09 | 0.129787E+09 | 0.106952E+09 | 45812168.96 | 61139905.42 | 0.00 | 0.00 |
| December | 0.103652E+09 | 0.181098E+09 | 96349215.33 | 38135941.91 | 58213273.42 | 0.00 | 0.00 |
| Annual Sum or Average | 0.267102E+10 | 0.859524E+09 | 0.150225E+10 | 0.556932E+09 | 0.945321E+09 | 0.00 | 0.00 |
| Minimum of Months | 0.103652E+09 | 2758403.92 | 96349215.33 | 18490981.45 | 58213273.42 | 0.00 | 0.00 |
| Maximum of Months | 0.375916E+09 | 0.181098E+09 | 0.173357E+09 | 79876325.33 | 96494671.85 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: M CORRIDOR
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 31654072.95 | 64736393.16 | 33639117.77 | 13566930.72 | 20072187.05 | 0.00 | 0.00 |
| February | 44581575.35 | 46027080.51 | 36773836.59 | 15139715.48 | 21634121.11 | 0.00 | 0.00 |
| March | 77689292.81 | 29855603.71 | 49719189.67 | 20497500.13 | 29221689.54 | 0.00 | 0.00 |
| April | 0.115012E+09 | 10073946.82 | 57417101.96 | 26819896.19 | 30597205.77 | 0.00 | 0.00 |
| May | 0.135608E+09 | 1648088.88 | 58207818.60 | 25808017.15 | 32399801.45 | 0.00 | 0.00 |
| June | 0.117791E+09 | 1353401.39 | 45824639.87 | 15198097.13 | 30626542.74 | 0.00 | 0.00 |
| July | 99986618.05 | 300140.80 | 39751489.86 | 8350856.11 | 31400633.75 | 0.00 | 0.00 |
| August | 83241793.15 | 1161603.30 | 35852171.33 | 6208675.73 | 29643495.59 | 0.00 | 0.00 |
| September | 74843939.93 | 4375065.97 | 36999575.50 | 10254548.81 | 26745026.69 | 0.00 | 0.00 |
| October | 75584992.00 | 23178432.65 | 41960976.56 | 16968424.67 | 24992551.89 | 0.00 | 0.00 |
| November | 50533658.70 | 43508668.60 | 35911060.25 | 15382250.13 | 20528810.12 | 0.00 | 0.00 |
| December | 32924839.46 | 64115181.22 | 32350961.84 | 12804820.44 | 19546141.40 | 0.00 | 0.00 |
| Annual Sum or Average | 0.939452E+09 | 0.290334E+09 | 0.504408E+09 | 0.187000E+09 | 0.317408E+09 | 0.00 | 0.00 |
| Minimum of Months | 31654072.95 | 300140.80 | 32350961.84 | 6208675.73 | 19546141.40 | 0.00 | 0.00 |
| Maximum of Months | 0.135608E+09 | 64736393.16 | 58207818.60 | 26819896.19 | 32399801.45 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
| January | 13.39 | 10.38 | 7.87 | 1.20 | 0.38 | 63.33 | 149.51 | 0.00 |
| February | 16.97 | 12.78 | 9.69 | 1.81 | 4.63 | 75.94 | 163.32 | 0.01 |
| March | 22.37 | 15.60 | 11.23 | 1.86 | 10.07 | 92.70 | 193.23 | 0.00 |
| April | 29.13 | 18.33 | 11.93 | 1.64 | 16.17 | 89.20 | 259.84 | 0.01 |
| May | 32.98 | 21.97 | 16.72 | 2.17 | 21.14 | 97.31 | 248.85 | 0.02 |
| June | 33.59 | 24.39 | 20.62 | 1.55 | 23.45 | 107.22 | 203.36 | 0.06 |
| July | 31.67 | 26.29 | 24.51 | 2.27 | 24.88 | 132.35 | 83.14 | 0.02 |
| August | 30.03 | 26.31 | 25.11 | 1.75 | 23.81 | 127.44 | 60.46 | 0.00 |
| September | 28.75 | 24.70 | 23.21 | 1.33 | 20.22 | 105.62 | 105.60 | 0.08 |
| October | 25.09 | 18.74 | 15.36 | 0.77 | 12.83 | 75.09 | 190.08 | 0.00 |
| November | 19.63 | 14.46 | 10.99 | 0.66 | 5.78 | 58.54 | 201.10 | 0.00 |
| December | 14.52 | 10.88 | 7.89 | 0.97 | 0.94 | 60.91 | 153.60 | 0.01 |
| Annual Sum or Average | 24.88 | 18.77 | 15.46 | 1.50 | 13.74 | 90.59 | 167.44 | 0.02 |
| Minimum of Months | 13.39 | 10.38 | 7.87 | 0.66 | 0.38 | 58.54 | 60.46 | 0.00 |
| Maximum of Months | 33.59 | 26.31 | 25.11 | 2.27 | 24.88 | 132.35 | 259.84 | 0.08 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
| January | 23.60 | 12-JAN-14:00 | 14.20 | 7.40 | 3.80 | 8.15 | 163.00 | 476.00 |
| February | 27.10 | 22-FEB-14:00 | 16.20 | 9.10 | 1.50 | 15.39 | 225.00 | 451.00 |
| March | 35.60 | 28-MAR-14:00 | 18.50 | 7.70 | 0.00 | 19.52 | 182.00 | 699.00 |
| April | 40.30 | 15-APR-14:00 | 20.67 | 10.00 | 6.70 | 28.43 | 201.00 | 649.50 |
| May | 44.50 | 03-MAY-14:00 | 20.64 | 5.30 | 2.80 | 28.91 | 150.00 | 809.00 |
| June | 44.60 | 07-JUN-15:00 | 21.53 | 9.10 | 3.10 | 28.43 | 167.00 | 640.50 |
| July | 40.40 | 02-JUL-15:00 | 26.36 | 21.60 | 2.10 | 29.87 | 200.00 | 545.50 |
| August | 37.30 | 07-AUG-14:00 | 26.58 | 22.90 | 3.00 | 29.87 | 311.00 | 370.00 |
| September | 37.50 | 17-SEP-19:00 | 27.68 | 24.60 | 0.20 | 28.59 | 0.00 | 0.00 |
| October | 36.40 | 02-OCT-14:20 | 21.05 | 13.00 | 1.80 | 21.61 | 187.33 | 678.83 |
| November | 30.30 | 04-NOV-13:00 | 17.17 | 8.90 | 1.10 | 14.84 | 155.00 | 710.00 |
| December | 24.60 | 28-DEC-13:00 | 15.30 | 8.90 | 2.80 | 10.88 | 181.50 | 535.00 |
| Annual Sum or Average | ||||||||
| Minimum of Months | 23.60 | 14.20 | 5.30 | 0.00 | 8.15 | 0.00 | 0.00 | |
| Maximum of Months | 44.60 | 27.68 | 24.60 | 6.70 | 29.87 | 311.00 | 809.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
| January | 4.80 | 05-JAN-06:00 | 4.73 | 4.60 | 0.00 | -10.2 | 0.00 | 0.00 |
| February | 6.90 | 02-FEB-05:00 | 6.67 | 6.50 | 0.00 | -7.8 | 0.00 | 0.00 |
| March | 13.30 | 01-MAR-03:00 | 10.56 | 8.30 | 0.80 | -1.4 | 0.00 | 0.00 |
| April | 17.40 | 11-APR-04:00 | 13.58 | 10.90 | 0.00 | 3.06 | 0.00 | 0.00 |
| May | 22.70 | 13-MAY-04:00 | 20.32 | 19.30 | 2.10 | 20.40 | 0.00 | 0.00 |
| June | 23.30 | 18-JUN-04:00 | 21.80 | 21.20 | 2.70 | 17.75 | 0.00 | 0.00 |
| July | 23.20 | 19-JUL-02:00 | 23.20 | 23.20 | 2.30 | 15.39 | 0.00 | 0.00 |
| August | 23.40 | 15-AUG-23:00 | 22.91 | 22.80 | 2.40 | 21.78 | 0.00 | 0.00 |
| September | 23.00 | 27-SEP-04:00 | 20.74 | 19.70 | 0.00 | 10.30 | 0.00 | 0.00 |
| October | 15.50 | 31-OCT-04:00 | 14.07 | 13.20 | 0.00 | 1.80 | 0.00 | 0.00 |
| November | 9.50 | 27-NOV-05:00 | 8.75 | 8.10 | 0.00 | -5.0 | 0.00 | 0.00 |
| December | 5.00 | 21-DEC-04:00 | 4.08 | 3.00 | 0.00 | -10.5 | 0.00 | 0.00 |
| Annual Sum or Average | ||||||||
| Minimum of Months | 4.80 | 4.08 | 3.00 | 0.00 | -10.5 | 0.00 | 0.00 | |
| Maximum of Months | 23.40 | 23.20 | 23.20 | 2.70 | 21.78 | 0.00 | 0.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| SITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
| January | 15.62 | 17-JAN-14:00 | 18.20 | 14.10 | 1.00 | 11.07 | 198.00 | 56.50 |
| February | 18.14 | 25-FEB-16:00 | 21.20 | 16.60 | 5.90 | 10.88 | 107.50 | 156.50 |
| March | 21.38 | 10-MAR-18:49 | 29.25 | 17.73 | 2.10 | 21.44 | 0.00 | 0.00 |
| April | 23.42 | 18-APR-13:00 | 37.10 | 17.80 | 5.70 | 23.49 | 233.50 | 671.50 |
| May | 27.40 | 22-MAY-22:00 | 29.40 | 26.80 | 0.00 | 20.40 | 0.00 | 0.00 |
| June | 28.92 | 28-JUN-12:00 | 34.40 | 27.50 | 1.00 | 25.49 | 332.50 | 501.50 |
| July | 29.18 | 01-JUL-16:00 | 37.20 | 26.80 | 2.30 | 25.66 | 196.00 | 196.00 |
| August | 29.17 | 27-AUG-15:00 | 35.10 | 27.40 | 1.30 | 29.55 | 256.00 | 129.00 |
| September | 28.10 | 14-SEP-16:00 | 33.70 | 26.40 | 1.40 | 26.48 | 122.50 | 108.50 |
| October | 23.06 | 06-OCT-10:00 | 28.60 | 20.80 | 1.30 | 20.22 | 327.00 | 348.50 |
| November | 18.93 | 08-NOV-17:10 | 27.55 | 14.47 | 0.17 | 16.67 | 28.00 | 65.33 |
| December | 15.64 | 29-DEC-19:00 | 16.80 | 14.90 | 4.80 | 13.54 | 0.00 | 0.00 |
| Annual Sum or Average | ||||||||
| Minimum of Months | 15.62 | 16.80 | 14.10 | 0.00 | 10.88 | 0.00 | 0.00 | |
| Maximum of Months | 29.18 | 37.20 | 27.50 | 5.90 | 29.55 | 332.50 | 671.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| SITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
| January | 14.10 | 17-JAN-13:00 | 17.80 | 15.48 | 0.90 | 9.72 | 260.50 | 81.50 |
| February | 16.60 | 25-FEB-16:00 | 21.20 | 18.14 | 5.90 | 10.88 | 107.50 | 156.50 |
| March | 18.30 | 10-MAR-19:00 | 27.70 | 21.26 | 2.10 | 21.44 | 0.00 | 0.00 |
| April | 19.30 | 26-APR-23:10 | 28.53 | 22.04 | 0.00 | 15.61 | 0.00 | 0.00 |
| May | 26.80 | 22-MAY-22:00 | 29.40 | 27.40 | 0.00 | 20.40 | 0.00 | 0.00 |
| June | 27.50 | 28-JUN-12:00 | 34.40 | 28.92 | 1.00 | 25.49 | 332.50 | 501.50 |
| July | 27.30 | 18-JUL-06:19 | 29.10 | 27.70 | 1.17 | 26.48 | 20.00 | 0.00 |
| August | 28.80 | 12-AUG-07:00 | 29.10 | 28.83 | 2.90 | 26.81 | 113.00 | 6.50 |
| September | 26.50 | 12-SEP-14:00 | 30.50 | 27.38 | 0.90 | 25.99 | 260.00 | 20.00 |
| October | 21.10 | 06-OCT-08:00 | 25.50 | 22.41 | 0.30 | 17.21 | 239.00 | 159.00 |
| November | 16.30 | 08-NOV-21:19 | 20.10 | 17.59 | 0.00 | 10.95 | 0.00 | 0.00 |
| December | 14.90 | 29-DEC-20:10 | 16.72 | 15.59 | 4.73 | 13.13 | 0.00 | 0.00 |
| Annual Sum or Average | ||||||||
| Minimum of Months | 14.10 | 16.72 | 15.48 | 0.00 | 9.72 | 0.00 | 0.00 | |
| Maximum of Months | 28.80 | 34.40 | 28.92 | 5.90 | 26.81 | 332.50 | 501.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| SITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
| January | 18.00 | 13.00 | 16.00 | 20.92 | 27.26 | 0.00 |
| February | 18.00 | 13.00 | 16.00 | 21.74 | 33.91 | 0.00 |
| March | 18.00 | 13.00 | 16.00 | 24.21 | 44.04 | 0.00 |
| April | 18.00 | 13.00 | 16.00 | 27.79 | 55.91 | 0.00 |
| May | 18.00 | 13.00 | 16.00 | 31.48 | 58.43 | 0.00 |
| June | 18.00 | 13.00 | 16.00 | 34.27 | 54.82 | 0.00 |
| July | 18.00 | 13.00 | 16.00 | 35.42 | 39.75 | 0.00 |
| August | 18.00 | 13.00 | 16.00 | 34.60 | 34.68 | 0.00 |
| September | 18.00 | 13.00 | 16.00 | 32.04 | 35.55 | 0.00 |
| October | 18.00 | 13.00 | 16.00 | 28.44 | 39.44 | 0.00 |
| November | 18.00 | 13.00 | 16.00 | 24.77 | 33.85 | 0.00 |
| December | 18.00 | 13.00 | 16.00 | 22.02 | 26.79 | 0.00 |
| Annual Sum or Average | 18.00 | 13.00 | 16.00 | 28.18 | 40.37 | 0.00 |
| Minimum of Months | 18.00 | 13.00 | 16.00 | 20.92 | 26.79 | 0.00 |
| Maximum of Months | 18.00 | 13.00 | 16.00 | 35.42 | 58.43 | 0.00 |
Report: WaterHeaterReportMonthly
For: G SW APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.100343E+10 | -828266578.1 | 0.00 | 0.00 | 744.00 | 0.00 | -175162708.0 | 59.44 | 0.00 | 0.00 |
| February | 0.889072E+09 | -732128556.5 | 0.00 | 0.00 | 672.00 | 0.00 | -156943362.9 | 59.44 | 0.00 | 0.00 |
| March | 0.930032E+09 | -757455520.6 | 0.00 | 0.00 | 744.00 | 0.00 | -172576374.7 | 59.44 | 0.00 | 0.00 |
| April | 0.825446E+09 | -658532524.7 | 0.00 | 0.00 | 720.00 | 0.00 | -166913866.1 | 59.44 | 0.00 | 0.00 |
| May | 0.773755E+09 | -601276070.4 | 0.00 | 0.00 | 744.00 | 0.00 | -172478674.6 | 59.44 | 0.00 | 0.00 |
| June | 0.690546E+09 | -523628778.3 | 0.00 | 0.00 | 720.00 | 0.00 | -166917510.5 | 59.44 | 0.00 | 0.00 |
| July | 0.688856E+09 | -516374842.4 | 0.00 | 0.00 | 744.00 | 0.00 | -172481544.1 | 59.44 | 0.00 | 0.00 |
| August | 0.706641E+09 | -534163379.3 | 0.00 | 0.00 | 744.00 | 0.00 | -172477409.9 | 59.44 | 0.00 | 0.00 |
| September | 0.737028E+09 | -570108779.5 | 0.00 | 0.00 | 720.00 | 0.00 | -166919291.8 | 59.44 | 0.00 | 0.00 |
| October | 0.839044E+09 | -666557973.3 | 0.00 | 0.00 | 744.00 | 0.00 | -172486296.0 | 59.44 | 0.00 | 0.00 |
| November | 0.888401E+09 | -721486470.0 | 0.00 | 0.00 | 720.00 | 0.00 | -166914226.3 | 59.44 | 0.00 | 0.00 |
| December | 0.977861E+09 | -804668042.6 | 0.00 | 0.00 | 744.00 | 0.00 | -173193276.4 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.995011E+10 | -0.791465E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.203546E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.688856E+09 | -828266578.1 | 0.00 | 0.00 | 672.00 | 0.00 | -175162708.0 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.100343E+10 | -516374842.4 | 0.00 | 0.00 | 744.00 | 0.00 | -156943362.9 | 59.44 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: G NW APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.100781E+10 | -828265793.1 | 0.00 | 0.00 | 744.00 | 0.00 | -179542917.1 | 59.44 | 0.00 | 0.00 |
| February | 0.890781E+09 | -732127706.2 | 0.00 | 0.00 | 672.00 | 0.00 | -158653716.8 | 59.44 | 0.00 | 0.00 |
| March | 0.930219E+09 | -757454211.0 | 0.00 | 0.00 | 744.00 | 0.00 | -172765205.1 | 59.44 | 0.00 | 0.00 |
| April | 0.825447E+09 | -658533378.7 | 0.00 | 0.00 | 720.00 | 0.00 | -166913511.6 | 59.44 | 0.00 | 0.00 |
| May | 0.773754E+09 | -601280367.5 | 0.00 | 0.00 | 744.00 | 0.00 | -172473157.8 | 59.44 | 0.00 | 0.00 |
| June | 0.690549E+09 | -523634350.5 | 0.00 | 0.00 | 720.00 | 0.00 | -166914868.6 | 59.44 | 0.00 | 0.00 |
| July | 0.688858E+09 | -516376877.6 | 0.00 | 0.00 | 744.00 | 0.00 | -172480896.3 | 59.44 | 0.00 | 0.00 |
| August | 0.706636E+09 | -534155497.5 | 0.00 | 0.00 | 744.00 | 0.00 | -172480559.1 | 59.44 | 0.00 | 0.00 |
| September | 0.737034E+09 | -570117668.7 | 0.00 | 0.00 | 720.00 | 0.00 | -166915985.7 | 59.44 | 0.00 | 0.00 |
| October | 0.839044E+09 | -666561309.9 | 0.00 | 0.00 | 744.00 | 0.00 | -172482743.1 | 59.44 | 0.00 | 0.00 |
| November | 0.888488E+09 | -721470693.5 | 0.00 | 0.00 | 720.00 | 0.00 | -167017624.2 | 59.44 | 0.00 | 0.00 |
| December | 0.979762E+09 | -804669710.3 | 0.00 | 0.00 | 744.00 | 0.00 | -175092030.0 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.995838E+10 | -0.791465E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.204373E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.688858E+09 | -828265793.1 | 0.00 | 0.00 | 672.00 | 0.00 | -179542917.1 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.100781E+10 | -516376877.6 | 0.00 | 0.00 | 744.00 | 0.00 | -158653716.8 | 59.44 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: G NE APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.100769E+10 | -828265856.0 | 0.00 | 0.00 | 744.00 | 0.00 | -179423006.4 | 59.44 | 0.00 | 0.00 |
| February | 0.890561E+09 | -732121816.8 | 0.00 | 0.00 | 672.00 | 0.00 | -158438938.8 | 59.44 | 0.00 | 0.00 |
| March | 0.930187E+09 | -757451928.5 | 0.00 | 0.00 | 744.00 | 0.00 | -172734999.0 | 59.44 | 0.00 | 0.00 |
| April | 0.825447E+09 | -658522343.2 | 0.00 | 0.00 | 720.00 | 0.00 | -166924388.7 | 59.44 | 0.00 | 0.00 |
| May | 0.773754E+09 | -601261158.5 | 0.00 | 0.00 | 744.00 | 0.00 | -172493172.3 | 59.44 | 0.00 | 0.00 |
| June | 0.690542E+09 | -523622005.0 | 0.00 | 0.00 | 720.00 | 0.00 | -166920118.9 | 59.44 | 0.00 | 0.00 |
| July | 0.688856E+09 | -516375841.9 | 0.00 | 0.00 | 744.00 | 0.00 | -172480466.8 | 59.44 | 0.00 | 0.00 |
| August | 0.706643E+09 | -534162999.8 | 0.00 | 0.00 | 744.00 | 0.00 | -172479681.2 | 59.44 | 0.00 | 0.00 |
| September | 0.737025E+09 | -570106492.7 | 0.00 | 0.00 | 720.00 | 0.00 | -166918372.2 | 59.44 | 0.00 | 0.00 |
| October | 0.839045E+09 | -666559632.7 | 0.00 | 0.00 | 744.00 | 0.00 | -172485125.5 | 59.44 | 0.00 | 0.00 |
| November | 0.888481E+09 | -721480065.6 | 0.00 | 0.00 | 720.00 | 0.00 | -167000538.4 | 59.44 | 0.00 | 0.00 |
| December | 0.979609E+09 | -804671360.9 | 0.00 | 0.00 | 744.00 | 0.00 | -174937961.5 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.995784E+10 | -0.791460E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.204324E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.688856E+09 | -828265856.0 | 0.00 | 0.00 | 672.00 | 0.00 | -179423006.4 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.100769E+10 | -516375841.9 | 0.00 | 0.00 | 744.00 | 0.00 | -158438938.8 | 59.44 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: G N1 APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.100636E+10 | -828266744.0 | 0.00 | 0.00 | 744.00 | 0.00 | -178092958.5 | 59.44 | 0.00 | 0.00 |
| February | 0.889677E+09 | -732124948.0 | 0.00 | 0.00 | 672.00 | 0.00 | -157552143.5 | 59.44 | 0.00 | 0.00 |
| March | 0.930026E+09 | -757453282.2 | 0.00 | 0.00 | 744.00 | 0.00 | -172573214.2 | 59.44 | 0.00 | 0.00 |
| April | 0.825447E+09 | -658533553.7 | 0.00 | 0.00 | 720.00 | 0.00 | -166913711.3 | 59.44 | 0.00 | 0.00 |
| May | 0.773755E+09 | -601281497.0 | 0.00 | 0.00 | 744.00 | 0.00 | -172473315.2 | 59.44 | 0.00 | 0.00 |
| June | 0.690545E+09 | -523629121.9 | 0.00 | 0.00 | 720.00 | 0.00 | -166915740.1 | 59.44 | 0.00 | 0.00 |
| July | 0.688859E+09 | -516378600.2 | 0.00 | 0.00 | 744.00 | 0.00 | -172480065.4 | 59.44 | 0.00 | 0.00 |
| August | 0.706636E+09 | -534151289.7 | 0.00 | 0.00 | 744.00 | 0.00 | -172484954.1 | 59.44 | 0.00 | 0.00 |
| September | 0.737032E+09 | -570114438.5 | 0.00 | 0.00 | 720.00 | 0.00 | -166917409.9 | 59.44 | 0.00 | 0.00 |
| October | 0.839044E+09 | -666564941.6 | 0.00 | 0.00 | 744.00 | 0.00 | -172478908.5 | 59.44 | 0.00 | 0.00 |
| November | 0.888423E+09 | -721470698.6 | 0.00 | 0.00 | 720.00 | 0.00 | -166952012.9 | 59.44 | 0.00 | 0.00 |
| December | 0.978667E+09 | -804671543.2 | 0.00 | 0.00 | 744.00 | 0.00 | -173995735.6 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.995447E+10 | -0.791464E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.203983E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.688859E+09 | -828266744.0 | 0.00 | 0.00 | 672.00 | 0.00 | -178092958.5 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.100636E+10 | -516378600.2 | 0.00 | 0.00 | 744.00 | 0.00 | -157552143.5 | 59.44 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: G N2 APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.100634E+10 | -828266899.6 | 0.00 | 0.00 | 744.00 | 0.00 | -178077165.5 | 59.44 | 0.00 | 0.00 |
| February | 0.889659E+09 | -732124637.1 | 0.00 | 0.00 | 672.00 | 0.00 | -157534383.6 | 59.44 | 0.00 | 0.00 |
| March | 0.930026E+09 | -757452831.2 | 0.00 | 0.00 | 744.00 | 0.00 | -172572994.2 | 59.44 | 0.00 | 0.00 |
| April | 0.825447E+09 | -658530852.6 | 0.00 | 0.00 | 720.00 | 0.00 | -166916045.7 | 59.44 | 0.00 | 0.00 |
| May | 0.773755E+09 | -601281017.9 | 0.00 | 0.00 | 744.00 | 0.00 | -172474056.2 | 59.44 | 0.00 | 0.00 |
| June | 0.690544E+09 | -523628542.8 | 0.00 | 0.00 | 720.00 | 0.00 | -166915750.1 | 59.44 | 0.00 | 0.00 |
| July | 0.688858E+09 | -516378297.1 | 0.00 | 0.00 | 744.00 | 0.00 | -172479919.6 | 59.44 | 0.00 | 0.00 |
| August | 0.706637E+09 | -534151891.4 | 0.00 | 0.00 | 744.00 | 0.00 | -172485256.9 | 59.44 | 0.00 | 0.00 |
| September | 0.737031E+09 | -570113179.0 | 0.00 | 0.00 | 720.00 | 0.00 | -166917659.4 | 59.44 | 0.00 | 0.00 |
| October | 0.839043E+09 | -666564574.1 | 0.00 | 0.00 | 744.00 | 0.00 | -172478795.2 | 59.44 | 0.00 | 0.00 |
| November | 0.888425E+09 | -721475139.8 | 0.00 | 0.00 | 720.00 | 0.00 | -166949437.8 | 59.44 | 0.00 | 0.00 |
| December | 0.978656E+09 | -804671875.1 | 0.00 | 0.00 | 744.00 | 0.00 | -173984003.0 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.995443E+10 | -0.791464E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.203979E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.688858E+09 | -828266899.6 | 0.00 | 0.00 | 672.00 | 0.00 | -178077165.5 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.100634E+10 | -516378297.1 | 0.00 | 0.00 | 744.00 | 0.00 | -157534383.6 | 59.44 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: G S1 APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.100207E+10 | -828265465.6 | 0.00 | 0.00 | 744.00 | 0.00 | -173801500.4 | 59.44 | 0.00 | 0.00 |
| February | 0.888322E+09 | -732125403.6 | 0.00 | 0.00 | 672.00 | 0.00 | -156196130.1 | 59.44 | 0.00 | 0.00 |
| March | 0.929954E+09 | -757452710.5 | 0.00 | 0.00 | 744.00 | 0.00 | -172500813.2 | 59.44 | 0.00 | 0.00 |
| April | 0.825447E+09 | -658526749.2 | 0.00 | 0.00 | 720.00 | 0.00 | -166920079.4 | 59.44 | 0.00 | 0.00 |
| May | 0.773756E+09 | -601276698.2 | 0.00 | 0.00 | 744.00 | 0.00 | -172478998.5 | 59.44 | 0.00 | 0.00 |
| June | 0.690542E+09 | -523624784.0 | 0.00 | 0.00 | 720.00 | 0.00 | -166916900.9 | 59.44 | 0.00 | 0.00 |
| July | 0.688859E+09 | -516378087.3 | 0.00 | 0.00 | 744.00 | 0.00 | -172480641.2 | 59.44 | 0.00 | 0.00 |
| August | 0.706640E+09 | -534156087.5 | 0.00 | 0.00 | 744.00 | 0.00 | -172483994.3 | 59.44 | 0.00 | 0.00 |
| September | 0.737029E+09 | -570110706.8 | 0.00 | 0.00 | 720.00 | 0.00 | -166918295.8 | 59.44 | 0.00 | 0.00 |
| October | 0.839043E+09 | -666563976.9 | 0.00 | 0.00 | 744.00 | 0.00 | -172479166.6 | 59.44 | 0.00 | 0.00 |
| November | 0.888402E+09 | -721477960.0 | 0.00 | 0.00 | 720.00 | 0.00 | -166924229.5 | 59.44 | 0.00 | 0.00 |
| December | 0.977339E+09 | -804676003.1 | 0.00 | 0.00 | 744.00 | 0.00 | -172663409.9 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.994740E+10 | -0.791463E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.203276E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.688859E+09 | -828265465.6 | 0.00 | 0.00 | 672.00 | 0.00 | -173801500.4 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.100207E+10 | -516378087.3 | 0.00 | 0.00 | 744.00 | 0.00 | -156196130.1 | 59.44 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: G S2 APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.100197E+10 | -828266828.0 | 0.00 | 0.00 | 744.00 | 0.00 | -173707695.0 | 59.44 | 0.00 | 0.00 |
| February | 0.888235E+09 | -732127922.8 | 0.00 | 0.00 | 672.00 | 0.00 | -156106577.5 | 59.44 | 0.00 | 0.00 |
| March | 0.929946E+09 | -757453482.2 | 0.00 | 0.00 | 744.00 | 0.00 | -172492983.3 | 59.44 | 0.00 | 0.00 |
| April | 0.825445E+09 | -658520382.7 | 0.00 | 0.00 | 720.00 | 0.00 | -166924812.2 | 59.44 | 0.00 | 0.00 |
| May | 0.773755E+09 | -601260531.8 | 0.00 | 0.00 | 744.00 | 0.00 | -172494066.0 | 59.44 | 0.00 | 0.00 |
| June | 0.690542E+09 | -523621295.6 | 0.00 | 0.00 | 720.00 | 0.00 | -166920802.8 | 59.44 | 0.00 | 0.00 |
| July | 0.688856E+09 | -516375858.1 | 0.00 | 0.00 | 744.00 | 0.00 | -172480386.1 | 59.44 | 0.00 | 0.00 |
| August | 0.706643E+09 | -534163119.3 | 0.00 | 0.00 | 744.00 | 0.00 | -172479546.6 | 59.44 | 0.00 | 0.00 |
| September | 0.737025E+09 | -570106524.6 | 0.00 | 0.00 | 720.00 | 0.00 | -166918374.2 | 59.44 | 0.00 | 0.00 |
| October | 0.839045E+09 | -666559608.1 | 0.00 | 0.00 | 744.00 | 0.00 | -172485172.4 | 59.44 | 0.00 | 0.00 |
| November | 0.888403E+09 | -721481256.1 | 0.00 | 0.00 | 720.00 | 0.00 | -166921345.6 | 59.44 | 0.00 | 0.00 |
| December | 0.977297E+09 | -804672525.7 | 0.00 | 0.00 | 744.00 | 0.00 | -172624561.7 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.994717E+10 | -0.791461E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.203256E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.688856E+09 | -828266828.0 | 0.00 | 0.00 | 672.00 | 0.00 | -173707695.0 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.100197E+10 | -516375858.1 | 0.00 | 0.00 | 744.00 | 0.00 | -156106577.5 | 59.44 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: M SW APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.183127E+10 | -0.165653E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -174732485.7 | 59.44 | 0.00 | 0.00 |
| February | 0.162084E+10 | -0.146426E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -156583064.8 | 59.44 | 0.00 | 0.00 |
| March | 0.168742E+10 | -0.151491E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172504195.5 | 59.44 | 0.00 | 0.00 |
| April | 0.148397E+10 | -0.131706E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -166917134.3 | 59.44 | 0.00 | 0.00 |
| May | 0.137503E+10 | -0.120255E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172484874.9 | 59.44 | 0.00 | 0.00 |
| June | 0.121417E+10 | -0.104725E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -166917049.9 | 59.44 | 0.00 | 0.00 |
| July | 0.120523E+10 | -0.103275E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172481686.7 | 59.44 | 0.00 | 0.00 |
| August | 0.124080E+10 | -0.106832E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172479821.2 | 59.44 | 0.00 | 0.00 |
| September | 0.130714E+10 | -0.114022E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -166919954.4 | 59.44 | 0.00 | 0.00 |
| October | 0.150561E+10 | -0.133312E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172483680.0 | 59.44 | 0.00 | 0.00 |
| November | 0.160994E+10 | -0.144296E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -166972046.5 | 59.44 | 0.00 | 0.00 |
| December | 0.178309E+10 | -0.160935E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -173736159.3 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.178645E+11 | -0.158293E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.203521E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.120523E+10 | -0.165653E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -174732485.7 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.183127E+10 | -0.103275E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -156583064.8 | 59.44 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: M NW APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.183511E+10 | -0.165654E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -178571012.0 | 59.44 | 0.00 | 0.00 |
| February | 0.162175E+10 | -0.146426E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -157493046.1 | 59.44 | 0.00 | 0.00 |
| March | 0.168746E+10 | -0.151491E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172549785.6 | 59.44 | 0.00 | 0.00 |
| April | 0.148398E+10 | -0.131705E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -166922539.2 | 59.44 | 0.00 | 0.00 |
| May | 0.137503E+10 | -0.120255E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172481209.8 | 59.44 | 0.00 | 0.00 |
| June | 0.121417E+10 | -0.104726E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -166917204.5 | 59.44 | 0.00 | 0.00 |
| July | 0.120523E+10 | -0.103275E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172481446.4 | 59.44 | 0.00 | 0.00 |
| August | 0.124080E+10 | -0.106831E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172481563.2 | 59.44 | 0.00 | 0.00 |
| September | 0.130714E+10 | -0.114022E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -166919975.8 | 59.44 | 0.00 | 0.00 |
| October | 0.150561E+10 | -0.133312E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172488350.8 | 59.44 | 0.00 | 0.00 |
| November | 0.161017E+10 | -0.144296E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -167213200.0 | 59.44 | 0.00 | 0.00 |
| December | 0.178531E+10 | -0.160935E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -175964629.2 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.178718E+11 | -0.158293E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.204248E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.120523E+10 | -0.165654E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -178571012.0 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.183511E+10 | -0.103275E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -157493046.1 | 59.44 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: M SE APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.183114E+10 | -0.165653E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -174605148.1 | 59.44 | 0.00 | 0.00 |
| February | 0.162079E+10 | -0.146426E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -156534764.2 | 59.44 | 0.00 | 0.00 |
| March | 0.168741E+10 | -0.151491E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172498437.4 | 59.44 | 0.00 | 0.00 |
| April | 0.148397E+10 | -0.131706E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -166917052.9 | 59.44 | 0.00 | 0.00 |
| May | 0.137503E+10 | -0.120255E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172482775.0 | 59.44 | 0.00 | 0.00 |
| June | 0.121417E+10 | -0.104725E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -166917331.0 | 59.44 | 0.00 | 0.00 |
| July | 0.120524E+10 | -0.103275E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172481643.5 | 59.44 | 0.00 | 0.00 |
| August | 0.124080E+10 | -0.106832E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172480546.4 | 59.44 | 0.00 | 0.00 |
| September | 0.130714E+10 | -0.114022E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -166918382.9 | 59.44 | 0.00 | 0.00 |
| October | 0.150561E+10 | -0.133312E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172484761.5 | 59.44 | 0.00 | 0.00 |
| November | 0.160994E+10 | -0.144297E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -166971166.7 | 59.44 | 0.00 | 0.00 |
| December | 0.178303E+10 | -0.160935E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -173679172.1 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.178643E+11 | -0.158293E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.203497E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.120524E+10 | -0.165653E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -174605148.1 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.183114E+10 | -0.103275E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -156534764.2 | 59.44 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: M NE APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.183493E+10 | -0.165653E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -178396919.4 | 59.44 | 0.00 | 0.00 |
| February | 0.162156E+10 | -0.146426E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -157303080.6 | 59.44 | 0.00 | 0.00 |
| March | 0.168745E+10 | -0.151491E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172535747.9 | 59.44 | 0.00 | 0.00 |
| April | 0.148397E+10 | -0.131706E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -166917049.7 | 59.44 | 0.00 | 0.00 |
| May | 0.137503E+10 | -0.120255E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172482761.8 | 59.44 | 0.00 | 0.00 |
| June | 0.121417E+10 | -0.104725E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -166917331.0 | 59.44 | 0.00 | 0.00 |
| July | 0.120524E+10 | -0.103275E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172481642.6 | 59.44 | 0.00 | 0.00 |
| August | 0.124080E+10 | -0.106832E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172480545.0 | 59.44 | 0.00 | 0.00 |
| September | 0.130714E+10 | -0.114022E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -166918379.9 | 59.44 | 0.00 | 0.00 |
| October | 0.150561E+10 | -0.133312E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172489791.1 | 59.44 | 0.00 | 0.00 |
| November | 0.161014E+10 | -0.144296E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -167179040.6 | 59.44 | 0.00 | 0.00 |
| December | 0.178512E+10 | -0.160935E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -175771317.4 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.178712E+11 | -0.158293E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.204187E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.120524E+10 | -0.165653E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -178396919.4 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.183493E+10 | -0.103275E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -157303080.6 | 59.44 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: M N1 APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.183301E+10 | -0.165654E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -176477169.6 | 59.44 | 0.00 | 0.00 |
| February | 0.162084E+10 | -0.146426E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -156584380.7 | 59.44 | 0.00 | 0.00 |
| March | 0.168741E+10 | -0.151491E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172497282.3 | 59.44 | 0.00 | 0.00 |
| April | 0.148397E+10 | -0.131706E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -166917144.0 | 59.44 | 0.00 | 0.00 |
| May | 0.137503E+10 | -0.120255E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172484885.8 | 59.44 | 0.00 | 0.00 |
| June | 0.121417E+10 | -0.104725E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -166917059.1 | 59.44 | 0.00 | 0.00 |
| July | 0.120523E+10 | -0.103275E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172481697.6 | 59.44 | 0.00 | 0.00 |
| August | 0.124080E+10 | -0.106832E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172479832.5 | 59.44 | 0.00 | 0.00 |
| September | 0.130714E+10 | -0.114022E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -166919963.4 | 59.44 | 0.00 | 0.00 |
| October | 0.150561E+10 | -0.133312E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172484100.5 | 59.44 | 0.00 | 0.00 |
| November | 0.160996E+10 | -0.144296E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -166992657.4 | 59.44 | 0.00 | 0.00 |
| December | 0.178361E+10 | -0.160935E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -174260186.0 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.178668E+11 | -0.158293E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.203750E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.120523E+10 | -0.165654E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -176477169.6 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.183301E+10 | -0.103275E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -156584380.7 | 59.44 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: M N2 APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.183299E+10 | -0.165654E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -176456947.8 | 59.44 | 0.00 | 0.00 |
| February | 0.162083E+10 | -0.146426E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -156574754.3 | 59.44 | 0.00 | 0.00 |
| March | 0.168741E+10 | -0.151491E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172497044.3 | 59.44 | 0.00 | 0.00 |
| April | 0.148397E+10 | -0.131706E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -166917143.7 | 59.44 | 0.00 | 0.00 |
| May | 0.137503E+10 | -0.120255E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172484887.3 | 59.44 | 0.00 | 0.00 |
| June | 0.121417E+10 | -0.104725E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -166917059.1 | 59.44 | 0.00 | 0.00 |
| July | 0.120523E+10 | -0.103275E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172481697.6 | 59.44 | 0.00 | 0.00 |
| August | 0.124080E+10 | -0.106832E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172479832.5 | 59.44 | 0.00 | 0.00 |
| September | 0.130714E+10 | -0.114022E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -166919963.5 | 59.44 | 0.00 | 0.00 |
| October | 0.150561E+10 | -0.133312E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172484109.5 | 59.44 | 0.00 | 0.00 |
| November | 0.160996E+10 | -0.144296E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -166992356.6 | 59.44 | 0.00 | 0.00 |
| December | 0.178360E+10 | -0.160935E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -174247433.9 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.178667E+11 | -0.158293E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.203745E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.120523E+10 | -0.165654E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -176456947.8 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.183299E+10 | -0.103275E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -156574754.3 | 59.44 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: M S1 APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.182991E+10 | -0.165654E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -173370606.8 | 59.44 | 0.00 | 0.00 |
| February | 0.162029E+10 | -0.146426E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -156029869.2 | 59.44 | 0.00 | 0.00 |
| March | 0.168740E+10 | -0.151491E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172484350.3 | 59.44 | 0.00 | 0.00 |
| April | 0.148398E+10 | -0.131705E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -166923026.3 | 59.44 | 0.00 | 0.00 |
| May | 0.137503E+10 | -0.120255E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172480831.8 | 59.44 | 0.00 | 0.00 |
| June | 0.121417E+10 | -0.104726E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -166917384.1 | 59.44 | 0.00 | 0.00 |
| July | 0.120523E+10 | -0.103275E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172481703.4 | 59.44 | 0.00 | 0.00 |
| August | 0.124080E+10 | -0.106831E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172481788.4 | 59.44 | 0.00 | 0.00 |
| September | 0.130714E+10 | -0.114022E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -166919935.5 | 59.44 | 0.00 | 0.00 |
| October | 0.150561E+10 | -0.133312E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172483742.2 | 59.44 | 0.00 | 0.00 |
| November | 0.160988E+10 | -0.144296E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -166921463.6 | 59.44 | 0.00 | 0.00 |
| December | 0.178219E+10 | -0.160935E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172847310.5 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.178616E+11 | -0.158293E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.203234E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.120523E+10 | -0.165654E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -173370606.8 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.182991E+10 | -0.103275E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -156029869.2 | 59.44 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: M S2 APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.182991E+10 | -0.165654E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -173368955.0 | 59.44 | 0.00 | 0.00 |
| February | 0.162029E+10 | -0.146426E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -156029574.4 | 59.44 | 0.00 | 0.00 |
| March | 0.168740E+10 | -0.151491E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172484342.6 | 59.44 | 0.00 | 0.00 |
| April | 0.148398E+10 | -0.131705E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -166923026.2 | 59.44 | 0.00 | 0.00 |
| May | 0.137503E+10 | -0.120255E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172480832.0 | 59.44 | 0.00 | 0.00 |
| June | 0.121417E+10 | -0.104726E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -166917383.8 | 59.44 | 0.00 | 0.00 |
| July | 0.120523E+10 | -0.103275E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172481703.4 | 59.44 | 0.00 | 0.00 |
| August | 0.124080E+10 | -0.106831E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172481788.3 | 59.44 | 0.00 | 0.00 |
| September | 0.130714E+10 | -0.114022E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -166919935.6 | 59.44 | 0.00 | 0.00 |
| October | 0.150561E+10 | -0.133312E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172483742.1 | 59.44 | 0.00 | 0.00 |
| November | 0.160988E+10 | -0.144296E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -166921475.3 | 59.44 | 0.00 | 0.00 |
| December | 0.178219E+10 | -0.160935E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172847386.3 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.178616E+11 | -0.158293E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.203234E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.120523E+10 | -0.165654E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -173368955.0 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.182991E+10 | -0.103275E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -156029574.4 | 59.44 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: T SW APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.100841E+10 | -828263560.7 | 0.00 | 0.00 | 744.00 | 0.00 | -180149674.1 | 59.44 | 0.00 | 0.00 |
| February | 0.892337E+09 | -732127275.4 | 0.00 | 0.00 | 672.00 | 0.00 | -160210132.4 | 59.44 | 0.00 | 0.00 |
| March | 0.930903E+09 | -757456241.8 | 0.00 | 0.00 | 744.00 | 0.00 | -173446763.7 | 59.44 | 0.00 | 0.00 |
| April | 0.825461E+09 | -658532397.7 | 0.00 | 0.00 | 720.00 | 0.00 | -166929001.9 | 59.44 | 0.00 | 0.00 |
| May | 0.773755E+09 | -601275328.6 | 0.00 | 0.00 | 744.00 | 0.00 | -172479265.9 | 59.44 | 0.00 | 0.00 |
| June | 0.690546E+09 | -523628173.2 | 0.00 | 0.00 | 720.00 | 0.00 | -166917861.2 | 59.44 | 0.00 | 0.00 |
| July | 0.688856E+09 | -516374838.5 | 0.00 | 0.00 | 744.00 | 0.00 | -172481512.6 | 59.44 | 0.00 | 0.00 |
| August | 0.706641E+09 | -534163342.7 | 0.00 | 0.00 | 744.00 | 0.00 | -172477420.5 | 59.44 | 0.00 | 0.00 |
| September | 0.737028E+09 | -570108769.0 | 0.00 | 0.00 | 720.00 | 0.00 | -166919275.5 | 59.44 | 0.00 | 0.00 |
| October | 0.839224E+09 | -666556273.0 | 0.00 | 0.00 | 744.00 | 0.00 | -172667578.5 | 59.44 | 0.00 | 0.00 |
| November | 0.890673E+09 | -721477385.2 | 0.00 | 0.00 | 720.00 | 0.00 | -169195446.0 | 59.44 | 0.00 | 0.00 |
| December | 0.983768E+09 | -804670852.4 | 0.00 | 0.00 | 744.00 | 0.00 | -179097193.7 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.996761E+10 | -0.791463E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.205297E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.688856E+09 | -828263560.7 | 0.00 | 0.00 | 672.00 | 0.00 | -180149674.1 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.100841E+10 | -516374838.5 | 0.00 | 0.00 | 744.00 | 0.00 | -160210132.4 | 59.44 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: T NW APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.101112E+10 | -828265382.5 | 0.00 | 0.00 | 744.00 | 0.00 | -182855881.6 | 59.44 | 0.00 | 0.00 |
| February | 0.893486E+09 | -732131318.7 | 0.00 | 0.00 | 672.00 | 0.00 | -161354432.3 | 59.44 | 0.00 | 0.00 |
| March | 0.931166E+09 | -757452665.1 | 0.00 | 0.00 | 744.00 | 0.00 | -173713602.7 | 59.44 | 0.00 | 0.00 |
| April | 0.825465E+09 | -658522162.0 | 0.00 | 0.00 | 720.00 | 0.00 | -166942708.4 | 59.44 | 0.00 | 0.00 |
| May | 0.773754E+09 | -601261544.6 | 0.00 | 0.00 | 744.00 | 0.00 | -172492696.7 | 59.44 | 0.00 | 0.00 |
| June | 0.690542E+09 | -523622121.3 | 0.00 | 0.00 | 720.00 | 0.00 | -166919688.6 | 59.44 | 0.00 | 0.00 |
| July | 0.688856E+09 | -516376382.3 | 0.00 | 0.00 | 744.00 | 0.00 | -172480067.9 | 59.44 | 0.00 | 0.00 |
| August | 0.706643E+09 | -534162901.2 | 0.00 | 0.00 | 744.00 | 0.00 | -172480049.3 | 59.44 | 0.00 | 0.00 |
| September | 0.737026E+09 | -570106802.1 | 0.00 | 0.00 | 720.00 | 0.00 | -166918826.3 | 59.44 | 0.00 | 0.00 |
| October | 0.839312E+09 | -666561190.0 | 0.00 | 0.00 | 744.00 | 0.00 | -172750776.0 | 59.44 | 0.00 | 0.00 |
| November | 0.891660E+09 | -721478290.5 | 0.00 | 0.00 | 720.00 | 0.00 | -170181914.7 | 59.44 | 0.00 | 0.00 |
| December | 0.986372E+09 | -804672193.3 | 0.00 | 0.00 | 744.00 | 0.00 | -181699748.6 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.997540E+10 | -0.791461E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.206079E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.688856E+09 | -828265382.5 | 0.00 | 0.00 | 672.00 | 0.00 | -182855881.6 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.101112E+10 | -516376382.3 | 0.00 | 0.00 | 744.00 | 0.00 | -161354432.3 | 59.44 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: T SE APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.100821E+10 | -828266518.3 | 0.00 | 0.00 | 744.00 | 0.00 | -179944451.9 | 59.44 | 0.00 | 0.00 |
| February | 0.892138E+09 | -732125687.0 | 0.00 | 0.00 | 672.00 | 0.00 | -160011954.7 | 59.44 | 0.00 | 0.00 |
| March | 0.930831E+09 | -757452588.7 | 0.00 | 0.00 | 744.00 | 0.00 | -173378832.0 | 59.44 | 0.00 | 0.00 |
| April | 0.825460E+09 | -658521662.4 | 0.00 | 0.00 | 720.00 | 0.00 | -166938628.5 | 59.44 | 0.00 | 0.00 |
| May | 0.773754E+09 | -601261082.9 | 0.00 | 0.00 | 744.00 | 0.00 | -172493267.6 | 59.44 | 0.00 | 0.00 |
| June | 0.690542E+09 | -523621842.4 | 0.00 | 0.00 | 720.00 | 0.00 | -166920262.8 | 59.44 | 0.00 | 0.00 |
| July | 0.688856E+09 | -516375760.2 | 0.00 | 0.00 | 744.00 | 0.00 | -172480483.0 | 59.44 | 0.00 | 0.00 |
| August | 0.706643E+09 | -534163044.0 | 0.00 | 0.00 | 744.00 | 0.00 | -172479602.3 | 59.44 | 0.00 | 0.00 |
| September | 0.737025E+09 | -570106500.0 | 0.00 | 0.00 | 720.00 | 0.00 | -166918352.1 | 59.44 | 0.00 | 0.00 |
| October | 0.839223E+09 | -666559294.0 | 0.00 | 0.00 | 744.00 | 0.00 | -172663264.5 | 59.44 | 0.00 | 0.00 |
| November | 0.890601E+09 | -721486268.0 | 0.00 | 0.00 | 720.00 | 0.00 | -169114494.4 | 59.44 | 0.00 | 0.00 |
| December | 0.983589E+09 | -804673919.9 | 0.00 | 0.00 | 744.00 | 0.00 | -178915501.7 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.996687E+10 | -0.791461E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.205226E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.688856E+09 | -828266518.3 | 0.00 | 0.00 | 672.00 | 0.00 | -179944451.9 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.100821E+10 | -516375760.2 | 0.00 | 0.00 | 744.00 | 0.00 | -160011954.7 | 59.44 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: T NE APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.101121E+10 | -828265150.6 | 0.00 | 0.00 | 744.00 | 0.00 | -182949805.8 | 59.44 | 0.00 | 0.00 |
| February | 0.893197E+09 | -732132285.8 | 0.00 | 0.00 | 672.00 | 0.00 | -161065115.4 | 59.44 | 0.00 | 0.00 |
| March | 0.931061E+09 | -757460498.8 | 0.00 | 0.00 | 744.00 | 0.00 | -173600545.3 | 59.44 | 0.00 | 0.00 |
| April | 0.825460E+09 | -658519119.4 | 0.00 | 0.00 | 720.00 | 0.00 | -166940773.2 | 59.44 | 0.00 | 0.00 |
| May | 0.773755E+09 | -601260371.7 | 0.00 | 0.00 | 744.00 | 0.00 | -172494891.2 | 59.44 | 0.00 | 0.00 |
| June | 0.690542E+09 | -523620656.7 | 0.00 | 0.00 | 720.00 | 0.00 | -166921305.8 | 59.44 | 0.00 | 0.00 |
| July | 0.688857E+09 | -516376277.5 | 0.00 | 0.00 | 744.00 | 0.00 | -172480616.4 | 59.44 | 0.00 | 0.00 |
| August | 0.706642E+09 | -534162339.1 | 0.00 | 0.00 | 744.00 | 0.00 | -172479607.4 | 59.44 | 0.00 | 0.00 |
| September | 0.737026E+09 | -570106120.8 | 0.00 | 0.00 | 720.00 | 0.00 | -166919608.2 | 59.44 | 0.00 | 0.00 |
| October | 0.839300E+09 | -666554489.8 | 0.00 | 0.00 | 744.00 | 0.00 | -172745206.0 | 59.44 | 0.00 | 0.00 |
| November | 0.891488E+09 | -721478690.3 | 0.00 | 0.00 | 720.00 | 0.00 | -170009784.3 | 59.44 | 0.00 | 0.00 |
| December | 0.986280E+09 | -804673374.0 | 0.00 | 0.00 | 744.00 | 0.00 | -181606842.9 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.997482E+10 | -0.791461E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.206021E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.688857E+09 | -828265150.6 | 0.00 | 0.00 | 672.00 | 0.00 | -182949805.8 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.101121E+10 | -516376277.5 | 0.00 | 0.00 | 744.00 | 0.00 | -161065115.4 | 59.44 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: T N1 APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.101089E+10 | -828267661.4 | 0.00 | 0.00 | 744.00 | 0.00 | -182623005.1 | 59.44 | 0.00 | 0.00 |
| February | 0.892702E+09 | -732124272.4 | 0.00 | 0.00 | 672.00 | 0.00 | -160577922.7 | 59.44 | 0.00 | 0.00 |
| March | 0.930715E+09 | -757453706.0 | 0.00 | 0.00 | 744.00 | 0.00 | -173260847.3 | 59.44 | 0.00 | 0.00 |
| April | 0.825454E+09 | -658532883.6 | 0.00 | 0.00 | 720.00 | 0.00 | -166920801.8 | 59.44 | 0.00 | 0.00 |
| May | 0.773755E+09 | -601281597.1 | 0.00 | 0.00 | 744.00 | 0.00 | -172473409.9 | 59.44 | 0.00 | 0.00 |
| June | 0.690545E+09 | -523628988.7 | 0.00 | 0.00 | 720.00 | 0.00 | -166915720.0 | 59.44 | 0.00 | 0.00 |
| July | 0.688859E+09 | -516378601.6 | 0.00 | 0.00 | 744.00 | 0.00 | -172480047.8 | 59.44 | 0.00 | 0.00 |
| August | 0.706636E+09 | -534151296.2 | 0.00 | 0.00 | 744.00 | 0.00 | -172484934.8 | 59.44 | 0.00 | 0.00 |
| September | 0.737032E+09 | -570114435.9 | 0.00 | 0.00 | 720.00 | 0.00 | -166917390.3 | 59.44 | 0.00 | 0.00 |
| October | 0.839194E+09 | -666564998.5 | 0.00 | 0.00 | 744.00 | 0.00 | -172629173.0 | 59.44 | 0.00 | 0.00 |
| November | 0.890816E+09 | -721478361.4 | 0.00 | 0.00 | 720.00 | 0.00 | -169337654.7 | 59.44 | 0.00 | 0.00 |
| December | 0.985982E+09 | -804673080.5 | 0.00 | 0.00 | 744.00 | 0.00 | -181308851.1 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.997258E+10 | -0.791465E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.205793E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.688859E+09 | -828267661.4 | 0.00 | 0.00 | 672.00 | 0.00 | -182623005.1 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.101089E+10 | -516378601.6 | 0.00 | 0.00 | 744.00 | 0.00 | -160577922.7 | 59.44 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: T N2 APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.101089E+10 | -828267668.4 | 0.00 | 0.00 | 744.00 | 0.00 | -182621603.6 | 59.44 | 0.00 | 0.00 |
| February | 0.892686E+09 | -732124311.7 | 0.00 | 0.00 | 672.00 | 0.00 | -160561474.8 | 59.44 | 0.00 | 0.00 |
| March | 0.930713E+09 | -757453526.9 | 0.00 | 0.00 | 744.00 | 0.00 | -173259244.3 | 59.44 | 0.00 | 0.00 |
| April | 0.825453E+09 | -658531022.9 | 0.00 | 0.00 | 720.00 | 0.00 | -166922387.5 | 59.44 | 0.00 | 0.00 |
| May | 0.773755E+09 | -601281207.9 | 0.00 | 0.00 | 744.00 | 0.00 | -172473896.1 | 59.44 | 0.00 | 0.00 |
| June | 0.690544E+09 | -523628588.0 | 0.00 | 0.00 | 720.00 | 0.00 | -166915713.4 | 59.44 | 0.00 | 0.00 |
| July | 0.688858E+09 | -516378347.0 | 0.00 | 0.00 | 744.00 | 0.00 | -172479873.2 | 59.44 | 0.00 | 0.00 |
| August | 0.706637E+09 | -534151871.7 | 0.00 | 0.00 | 744.00 | 0.00 | -172485231.6 | 59.44 | 0.00 | 0.00 |
| September | 0.737031E+09 | -570113202.6 | 0.00 | 0.00 | 720.00 | 0.00 | -166917634.6 | 59.44 | 0.00 | 0.00 |
| October | 0.839195E+09 | -666565031.2 | 0.00 | 0.00 | 744.00 | 0.00 | -172629603.6 | 59.44 | 0.00 | 0.00 |
| November | 0.890815E+09 | -721483646.1 | 0.00 | 0.00 | 720.00 | 0.00 | -169331530.5 | 59.44 | 0.00 | 0.00 |
| December | 0.985972E+09 | -804673179.5 | 0.00 | 0.00 | 744.00 | 0.00 | -181298650.1 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.997255E+10 | -0.791465E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.205790E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.688858E+09 | -828267668.4 | 0.00 | 0.00 | 672.00 | 0.00 | -182621603.6 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.101089E+10 | -516378347.0 | 0.00 | 0.00 | 744.00 | 0.00 | -160561474.8 | 59.44 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: T S1 APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.100733E+10 | -828268139.1 | 0.00 | 0.00 | 744.00 | 0.00 | -179064212.6 | 59.44 | 0.00 | 0.00 |
| February | 0.891362E+09 | -732133099.4 | 0.00 | 0.00 | 672.00 | 0.00 | -159229368.0 | 59.44 | 0.00 | 0.00 |
| March | 0.930485E+09 | -757456138.5 | 0.00 | 0.00 | 744.00 | 0.00 | -173028386.1 | 59.44 | 0.00 | 0.00 |
| April | 0.825449E+09 | -658518700.5 | 0.00 | 0.00 | 720.00 | 0.00 | -166930065.4 | 59.44 | 0.00 | 0.00 |
| May | 0.773755E+09 | -601260405.0 | 0.00 | 0.00 | 744.00 | 0.00 | -172494517.0 | 59.44 | 0.00 | 0.00 |
| June | 0.690542E+09 | -523620853.3 | 0.00 | 0.00 | 720.00 | 0.00 | -166921128.7 | 59.44 | 0.00 | 0.00 |
| July | 0.688856E+09 | -516376030.7 | 0.00 | 0.00 | 744.00 | 0.00 | -172480222.0 | 59.44 | 0.00 | 0.00 |
| August | 0.706643E+09 | -534163164.0 | 0.00 | 0.00 | 744.00 | 0.00 | -172479452.4 | 59.44 | 0.00 | 0.00 |
| September | 0.737025E+09 | -570106540.7 | 0.00 | 0.00 | 720.00 | 0.00 | -166918349.7 | 59.44 | 0.00 | 0.00 |
| October | 0.839134E+09 | -666558984.2 | 0.00 | 0.00 | 744.00 | 0.00 | -172575496.2 | 59.44 | 0.00 | 0.00 |
| November | 0.889860E+09 | -721477439.5 | 0.00 | 0.00 | 720.00 | 0.00 | -168382141.8 | 59.44 | 0.00 | 0.00 |
| December | 0.982587E+09 | -804669748.9 | 0.00 | 0.00 | 744.00 | 0.00 | -177917211.0 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.996303E+10 | -0.791461E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.204842E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.688856E+09 | -828268139.1 | 0.00 | 0.00 | 672.00 | 0.00 | -179064212.6 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.100733E+10 | -516376030.7 | 0.00 | 0.00 | 744.00 | 0.00 | -159229368.0 | 59.44 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: T S2 APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.100732E+10 | -828268195.7 | 0.00 | 0.00 | 744.00 | 0.00 | -179056422.1 | 59.44 | 0.00 | 0.00 |
| February | 0.891358E+09 | -732133221.1 | 0.00 | 0.00 | 672.00 | 0.00 | -159225268.2 | 59.44 | 0.00 | 0.00 |
| March | 0.930485E+09 | -757456081.8 | 0.00 | 0.00 | 744.00 | 0.00 | -173028689.2 | 59.44 | 0.00 | 0.00 |
| April | 0.825449E+09 | -658518531.7 | 0.00 | 0.00 | 720.00 | 0.00 | -166930164.2 | 59.44 | 0.00 | 0.00 |
| May | 0.773755E+09 | -601260410.8 | 0.00 | 0.00 | 744.00 | 0.00 | -172494547.7 | 59.44 | 0.00 | 0.00 |
| June | 0.690542E+09 | -523620833.9 | 0.00 | 0.00 | 720.00 | 0.00 | -166921135.2 | 59.44 | 0.00 | 0.00 |
| July | 0.688856E+09 | -516376057.5 | 0.00 | 0.00 | 744.00 | 0.00 | -172480213.1 | 59.44 | 0.00 | 0.00 |
| August | 0.706643E+09 | -534163167.0 | 0.00 | 0.00 | 744.00 | 0.00 | -172479447.8 | 59.44 | 0.00 | 0.00 |
| September | 0.737025E+09 | -570106541.9 | 0.00 | 0.00 | 720.00 | 0.00 | -166918349.6 | 59.44 | 0.00 | 0.00 |
| October | 0.839135E+09 | -666558984.0 | 0.00 | 0.00 | 744.00 | 0.00 | -172575942.9 | 59.44 | 0.00 | 0.00 |
| November | 0.889863E+09 | -721477478.8 | 0.00 | 0.00 | 720.00 | 0.00 | -168385038.7 | 59.44 | 0.00 | 0.00 |
| December | 0.982586E+09 | -804669874.1 | 0.00 | 0.00 | 744.00 | 0.00 | -177916066.1 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.996302E+10 | -0.791461E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.204841E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.688856E+09 | -828268195.7 | 0.00 | 0.00 | 672.00 | 0.00 | -179056422.1 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.100732E+10 | -516376057.5 | 0.00 | 0.00 | 744.00 | 0.00 | -159225268.2 | 59.44 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
| January | 319.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 303.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 364.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 379.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 406.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 386.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 379.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 372.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 344.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 347.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 317.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 315.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 4237.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 303.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 406.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT GSW HEATING COIL
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT GNW HEATING COIL
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 35037375.14 | 346.26 | 03-JAN-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 35037375.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 35037375.14 | 346.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT OFFICE HEATING COIL
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT GNE HEATING COIL
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 32748307.78 | 351.76 | 03-JAN-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 32748307.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 32748307.78 | 351.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT GN1 HEATING COIL
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 3428930.05 | 108.73 | 03-JAN-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 3428930.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 3428930.05 | 108.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT GN2 HEATING COIL
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 3435711.89 | 108.94 | 03-JAN-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 3435711.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 3435711.89 | 108.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT GS1 HEATING COIL
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT GS2 HEATING COIL
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT MSW HEATING COIL
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT MNW HEATING COIL
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 39305771.23 | 623.57 | 03-JAN-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 39305771.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 39305771.23 | 623.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT MSE HEATING COIL
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT MNE HEATING COIL
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 37427126.38 | 641.70 | 03-JAN-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 37427126.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 37427126.38 | 641.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT MN1 HEATING COIL
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT MN2 HEATING COIL
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT MS1 HEATING COIL
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT MS2 HEATING COIL
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT TSW HEATING COIL
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.398921E+09 | 1025.81 | 03-JAN-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 98538235.84 | 843.72 | 11-FEB-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 2976724.22 | 166.73 | 26-NOV-06:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.220611E+09 | 971.26 | 23-DEC-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.721046E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.398921E+09 | 1025.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT TNW HEATING COIL
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.670000E+09 | 1193.34 | 03-JAN-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.161254E+09 | 840.67 | 11-FEB-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 15808896.61 | 345.00 | 26-NOV-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.436345E+09 | 1164.41 | 23-DEC-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.128341E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.670000E+09 | 1193.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT TSE HEATING COIL
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.380214E+09 | 1034.71 | 03-JAN-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 92612560.85 | 846.01 | 11-FEB-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 3040643.15 | 177.47 | 26-NOV-06:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.213821E+09 | 966.84 | 23-DEC-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.689688E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.380214E+09 | 1034.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT TNE HEATING COIL
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.633933E+09 | 1206.90 | 03-JAN-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.146574E+09 | 843.45 | 11-FEB-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 14586099.41 | 355.07 | 26-NOV-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.417126E+09 | 1159.57 | 23-DEC-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.121222E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.633933E+09 | 1206.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT TN1 HEATING COIL
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.411936E+09 | 852.94 | 03-JAN-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 68490986.75 | 529.72 | 11-FEB-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 496553.38 | 82.29 | 26-NOV-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.215543E+09 | 837.38 | 23-DEC-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.696467E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.411936E+09 | 852.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT TN2 HEATING COIL
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.412766E+09 | 854.45 | 03-JAN-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 68359027.15 | 530.21 | 11-FEB-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 500971.03 | 82.81 | 26-NOV-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.216033E+09 | 835.98 | 23-DEC-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.697659E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.412766E+09 | 854.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT TS1 HEATING COIL
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.179859E+09 | 669.86 | 03-JAN-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 30056054.38 | 530.51 | 11-FEB-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 67107479.70 | 634.61 | 23-DEC-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.277023E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.179859E+09 | 669.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT TS2 HEATING COIL
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.180087E+09 | 670.69 | 03-JAN-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 30064647.10 | 531.01 | 11-FEB-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 67297553.10 | 633.68 | 23-DEC-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.277449E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.180087E+09 | 670.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT GSW COOLING COIL
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.394333E+09 | 0.388453E+09 | 1293.43 | 12-JAN-15:20 | 1293.43 | 0.00 |
| February | 0.00 | 0.00 | 0.956837E+09 | 0.918561E+09 | 1828.98 | 20-FEB-16:10 | 1828.98 | 0.00 |
| March | 0.00 | 0.00 | 0.233626E+10 | 0.218002E+10 | 2562.95 | 12-MAR-16:10 | 2385.02 | 0.00 |
| April | 0.00 | 0.00 | 0.415323E+10 | 0.387106E+10 | 3218.91 | 18-APR-16:01 | 2844.69 | 0.00 |
| May | 0.00 | 0.00 | 0.596184E+10 | 0.512248E+10 | 3627.21 | 05-MAY-16:30 | 3627.21 | 0.00 |
| June | 0.00 | 0.00 | 0.667686E+10 | 0.529793E+10 | 3951.84 | 22-JUN-17:10 | 3030.05 | 0.00 |
| July | 0.00 | 0.00 | 0.770743E+10 | 0.544002E+10 | 4289.69 | 01-JUL-16:30 | 3054.83 | 0.00 |
| August | 0.00 | 0.00 | 0.750818E+10 | 0.520115E+10 | 4108.46 | 13-AUG-16:02 | 2956.43 | 0.00 |
| September | 0.00 | 0.00 | 0.660439E+10 | 0.483855E+10 | 3960.69 | 24-SEP-16:10 | 3254.72 | 0.00 |
| October | 0.00 | 0.00 | 0.485413E+10 | 0.426621E+10 | 3559.79 | 03-OCT-15:10 | 3222.94 | 0.00 |
| November | 0.00 | 0.00 | 0.280896E+10 | 0.265110E+10 | 2584.09 | 04-NOV-15:10 | 2584.09 | 0.00 |
| December | 0.00 | 0.00 | 0.100061E+10 | 0.980671E+09 | 1778.16 | 02-DEC-14:30 | 1778.16 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.509630E+11 | 0.411562E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.394333E+09 | 0.388453E+09 | 1293.43 | 1293.43 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.770743E+10 | 0.544002E+10 | 4289.69 | 3627.21 | 0.00 |
Report: CoilReportMonthly
For: SPLIT GNW COOLING COIL
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 13036873.96 | 12563553.54 | 338.52 | 14-JAN-17:10 | 315.89 | 0.00 |
| February | 0.00 | 0.00 | 0.338543E+09 | 0.321117E+09 | 1105.86 | 24-FEB-17:10 | 1020.99 | 0.00 |
| March | 0.00 | 0.00 | 0.166191E+10 | 0.153420E+10 | 2120.38 | 29-MAR-16:30 | 2070.60 | 0.00 |
| April | 0.00 | 0.00 | 0.372910E+10 | 0.345762E+10 | 3023.15 | 18-APR-16:01 | 2636.80 | 0.00 |
| May | 0.00 | 0.00 | 0.588991E+10 | 0.504881E+10 | 3576.49 | 05-MAY-16:50 | 3576.49 | 0.00 |
| June | 0.00 | 0.00 | 0.671575E+10 | 0.533008E+10 | 4035.52 | 22-JUN-17:00 | 3090.89 | 0.00 |
| July | 0.00 | 0.00 | 0.772056E+10 | 0.545067E+10 | 4240.05 | 01-JUL-16:40 | 3032.49 | 0.00 |
| August | 0.00 | 0.00 | 0.743997E+10 | 0.513498E+10 | 3993.54 | 07-AUG-17:10 | 3122.03 | 0.00 |
| September | 0.00 | 0.00 | 0.622598E+10 | 0.448787E+10 | 3565.97 | 14-SEP-16:30 | 2584.43 | 0.00 |
| October | 0.00 | 0.00 | 0.390795E+10 | 0.336499E+10 | 2971.73 | 03-OCT-16:10 | 2607.02 | 0.00 |
| November | 0.00 | 0.00 | 0.160630E+10 | 0.149582E+10 | 1704.54 | 04-NOV-16:10 | 1687.76 | 0.00 |
| December | 0.00 | 0.00 | 0.208443E+09 | 0.204042E+09 | 833.59 | 01-DEC-15:10 | 833.59 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.454574E+11 | 0.358428E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 13036873.96 | 12563553.54 | 338.52 | 315.89 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.772056E+10 | 0.545067E+10 | 4240.05 | 3576.49 | 0.00 |
Report: CoilReportMonthly
For: SPLIT OFFICE COOLING COIL
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.805304E+09 | 0.785334E+09 | 7515.79 | 26-JAN-09:02 | 6950.11 | 0.00 |
| February | 0.00 | 0.00 | 0.114285E+10 | 0.109422E+10 | 7947.29 | 23-FEB-09:02 | 7135.13 | 0.00 |
| March | 0.00 | 0.00 | 0.213897E+10 | 0.202631E+10 | 8322.65 | 29-MAR-07:02 | 6890.72 | 0.00 |
| April | 0.00 | 0.00 | 0.308726E+10 | 0.292921E+10 | 8536.11 | 26-APR-07:02 | 6214.32 | 0.00 |
| May | 0.00 | 0.00 | 0.472300E+10 | 0.418104E+10 | 8897.45 | 23-MAY-06:03 | 4956.67 | 0.00 |
| June | 0.00 | 0.00 | 0.527863E+10 | 0.430266E+10 | 8922.79 | 26-JUN-06:03 | 4616.13 | 0.00 |
| July | 0.00 | 0.00 | 0.579710E+10 | 0.409939E+10 | 8945.83 | 26-JUL-06:03 | 4603.76 | 0.00 |
| August | 0.00 | 0.00 | 0.590897E+10 | 0.410973E+10 | 8956.94 | 16-AUG-07:02 | 4745.85 | 0.00 |
| September | 0.00 | 0.00 | 0.479593E+10 | 0.356785E+10 | 8957.40 | 07-SEP-07:02 | 4678.17 | 0.00 |
| October | 0.00 | 0.00 | 0.363445E+10 | 0.328822E+10 | 8782.03 | 04-OCT-06:03 | 6100.32 | 0.00 |
| November | 0.00 | 0.00 | 0.225652E+10 | 0.217142E+10 | 8266.28 | 09-NOV-08:62 | 6962.22 | 0.00 |
| December | 0.00 | 0.00 | 0.119362E+10 | 0.117187E+10 | 7606.50 | 01-DEC-09:02 | 7606.50 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.407626E+11 | 0.337273E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.805304E+09 | 0.785334E+09 | 7515.79 | 4603.76 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.590897E+10 | 0.430266E+10 | 8957.40 | 7606.50 | 0.00 |
Report: CoilReportMonthly
For: SPLIT GNE COOLING COIL
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 9649134.94 | 9312160.25 | 252.73 | 26-JAN-14:00 | 252.73 | 0.00 |
| February | 0.00 | 0.00 | 0.346156E+09 | 0.327776E+09 | 1079.29 | 24-FEB-17:10 | 996.37 | 0.00 |
| March | 0.00 | 0.00 | 0.168203E+10 | 0.155032E+10 | 1866.23 | 29-MAR-16:03 | 1818.13 | 0.00 |
| April | 0.00 | 0.00 | 0.374985E+10 | 0.347388E+10 | 2771.27 | 18-APR-15:10 | 2383.28 | 0.00 |
| May | 0.00 | 0.00 | 0.591733E+10 | 0.507293E+10 | 3257.51 | 05-MAY-16:40 | 3257.51 | 0.00 |
| June | 0.00 | 0.00 | 0.666232E+10 | 0.527866E+10 | 3817.80 | 23-JUN-15:10 | 2735.71 | 0.00 |
| July | 0.00 | 0.00 | 0.772497E+10 | 0.545421E+10 | 4039.33 | 01-JUL-16:40 | 2861.66 | 0.00 |
| August | 0.00 | 0.00 | 0.744380E+10 | 0.513778E+10 | 3801.17 | 07-AUG-17:10 | 2944.75 | 0.00 |
| September | 0.00 | 0.00 | 0.621060E+10 | 0.447287E+10 | 3425.92 | 14-SEP-17:10 | 2436.60 | 0.00 |
| October | 0.00 | 0.00 | 0.392967E+10 | 0.338364E+10 | 2781.63 | 03-OCT-15:10 | 2464.89 | 0.00 |
| November | 0.00 | 0.00 | 0.161122E+10 | 0.149916E+10 | 1535.03 | 09-NOV-13:00 | 1426.31 | 0.00 |
| December | 0.00 | 0.00 | 0.198813E+09 | 0.194944E+09 | 730.97 | 01-DEC-14:00 | 730.97 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.454864E+11 | 0.358555E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 9649134.94 | 9312160.25 | 252.73 | 252.73 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.772497E+10 | 0.545421E+10 | 4039.33 | 3257.51 | 0.00 |
Report: CoilReportMonthly
For: SPLIT GN1 COOLING COIL
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 13369525.54 | 12741243.55 | 278.20 | 14-JAN-17:05 | 259.17 | 0.00 |
| February | 0.00 | 0.00 | 0.357205E+09 | 0.335231E+09 | 979.34 | 24-FEB-17:10 | 902.87 | 0.00 |
| March | 0.00 | 0.00 | 0.157396E+10 | 0.144180E+10 | 1575.78 | 29-MAR-16:13 | 1527.58 | 0.00 |
| April | 0.00 | 0.00 | 0.321982E+10 | 0.296270E+10 | 2290.97 | 18-APR-16:02 | 1973.94 | 0.00 |
| May | 0.00 | 0.00 | 0.500514E+10 | 0.423693E+10 | 2705.47 | 25-MAY-17:10 | 2205.85 | 0.00 |
| June | 0.00 | 0.00 | 0.572639E+10 | 0.445010E+10 | 3234.12 | 22-JUN-17:14 | 2378.42 | 0.00 |
| July | 0.00 | 0.00 | 0.662592E+10 | 0.457648E+10 | 3419.73 | 01-JUL-17:12 | 2357.85 | 0.00 |
| August | 0.00 | 0.00 | 0.641995E+10 | 0.431485E+10 | 3211.44 | 27-AUG-16:02 | 2164.02 | 0.00 |
| September | 0.00 | 0.00 | 0.536812E+10 | 0.376664E+10 | 2935.38 | 14-SEP-17:20 | 2014.24 | 0.00 |
| October | 0.00 | 0.00 | 0.336506E+10 | 0.285738E+10 | 2259.46 | 03-OCT-16:10 | 1957.32 | 0.00 |
| November | 0.00 | 0.00 | 0.146173E+10 | 0.135091E+10 | 1287.94 | 04-NOV-16:05 | 1274.49 | 0.00 |
| December | 0.00 | 0.00 | 0.224228E+09 | 0.218257E+09 | 639.21 | 01-DEC-15:10 | 639.21 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.393609E+11 | 0.305240E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 13369525.54 | 12741243.55 | 278.20 | 259.17 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.662592E+10 | 0.457648E+10 | 3419.73 | 2378.42 | 0.00 |
Report: CoilReportMonthly
For: SPLIT GN2 COOLING COIL
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 13491702.83 | 12862607.59 | 277.26 | 14-JAN-17:05 | 258.29 | 0.00 |
| February | 0.00 | 0.00 | 0.360664E+09 | 0.338525E+09 | 981.68 | 24-FEB-17:10 | 905.11 | 0.00 |
| March | 0.00 | 0.00 | 0.157623E+10 | 0.144390E+10 | 1572.59 | 29-MAR-16:03 | 1523.75 | 0.00 |
| April | 0.00 | 0.00 | 0.322116E+10 | 0.296389E+10 | 2288.94 | 18-APR-16:02 | 1972.23 | 0.00 |
| May | 0.00 | 0.00 | 0.500640E+10 | 0.423808E+10 | 2701.19 | 25-MAY-17:10 | 2201.99 | 0.00 |
| June | 0.00 | 0.00 | 0.572452E+10 | 0.444835E+10 | 3229.27 | 22-JUN-17:14 | 2374.14 | 0.00 |
| July | 0.00 | 0.00 | 0.662620E+10 | 0.457670E+10 | 3416.80 | 01-JUL-17:12 | 2355.51 | 0.00 |
| August | 0.00 | 0.00 | 0.642027E+10 | 0.431510E+10 | 3209.96 | 27-AUG-16:02 | 2162.91 | 0.00 |
| September | 0.00 | 0.00 | 0.536764E+10 | 0.376619E+10 | 2933.89 | 14-SEP-17:20 | 2013.02 | 0.00 |
| October | 0.00 | 0.00 | 0.336626E+10 | 0.285847E+10 | 2257.19 | 03-OCT-16:10 | 1955.28 | 0.00 |
| November | 0.00 | 0.00 | 0.146266E+10 | 0.135180E+10 | 1284.95 | 04-NOV-16:05 | 1271.53 | 0.00 |
| December | 0.00 | 0.00 | 0.225851E+09 | 0.219852E+09 | 639.46 | 01-DEC-15:10 | 639.46 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.393714E+11 | 0.305337E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 13491702.83 | 12862607.59 | 277.26 | 258.29 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.662620E+10 | 0.457670E+10 | 3416.80 | 2374.14 | 0.00 |
Report: CoilReportMonthly
For: SPLIT GS1 COOLING COIL
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.556076E+09 | 0.543361E+09 | 1232.23 | 12-JAN-14:50 | 1232.23 | 0.00 |
| February | 0.00 | 0.00 | 0.109056E+10 | 0.104195E+10 | 1601.31 | 20-FEB-14:40 | 1601.31 | 0.00 |
| March | 0.00 | 0.00 | 0.230028E+10 | 0.213654E+10 | 2118.53 | 12-MAR-16:10 | 1961.70 | 0.00 |
| April | 0.00 | 0.00 | 0.366636E+10 | 0.339686E+10 | 2516.22 | 18-APR-15:10 | 2188.91 | 0.00 |
| May | 0.00 | 0.00 | 0.509455E+10 | 0.432640E+10 | 2801.44 | 20-MAY-16:10 | 2283.13 | 0.00 |
| June | 0.00 | 0.00 | 0.570153E+10 | 0.443101E+10 | 3159.10 | 22-JUN-17:20 | 2328.94 | 0.00 |
| July | 0.00 | 0.00 | 0.662887E+10 | 0.458004E+10 | 3448.85 | 01-JUL-17:02 | 2368.61 | 0.00 |
| August | 0.00 | 0.00 | 0.650605E+10 | 0.439563E+10 | 3383.26 | 27-AUG-16:02 | 2298.40 | 0.00 |
| September | 0.00 | 0.00 | 0.577164E+10 | 0.413531E+10 | 3164.82 | 24-SEP-16:10 | 2546.79 | 0.00 |
| October | 0.00 | 0.00 | 0.434847E+10 | 0.378816E+10 | 2824.89 | 03-OCT-15:10 | 2548.47 | 0.00 |
| November | 0.00 | 0.00 | 0.271677E+10 | 0.255565E+10 | 2180.04 | 04-NOV-14:10 | 2176.83 | 0.00 |
| December | 0.00 | 0.00 | 0.117112E+10 | 0.114466E+10 | 1634.73 | 02-DEC-14:00 | 1634.73 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.455523E+11 | 0.364756E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.556076E+09 | 0.543361E+09 | 1232.23 | 1232.23 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.662887E+10 | 0.458004E+10 | 3448.85 | 2548.47 | 0.00 |
Report: CoilReportMonthly
For: SPLIT GS2 COOLING COIL
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.614942E+09 | 0.600181E+09 | 1277.35 | 12-JAN-14:40 | 1277.35 | 0.00 |
| February | 0.00 | 0.00 | 0.119896E+10 | 0.114463E+10 | 1699.53 | 20-FEB-14:50 | 1699.53 | 0.00 |
| March | 0.00 | 0.00 | 0.250921E+10 | 0.233383E+10 | 2268.45 | 12-MAR-16:10 | 2107.26 | 0.00 |
| April | 0.00 | 0.00 | 0.398343E+10 | 0.370134E+10 | 2644.03 | 16-APR-16:10 | 2467.13 | 0.00 |
| May | 0.00 | 0.00 | 0.547057E+10 | 0.467859E+10 | 2963.74 | 20-MAY-16:10 | 2437.12 | 0.00 |
| June | 0.00 | 0.00 | 0.607130E+10 | 0.476936E+10 | 3264.40 | 22-JUN-17:20 | 2425.44 | 0.00 |
| July | 0.00 | 0.00 | 0.704668E+10 | 0.495057E+10 | 3619.54 | 01-JUL-17:02 | 2524.88 | 0.00 |
| August | 0.00 | 0.00 | 0.690947E+10 | 0.475112E+10 | 3575.79 | 27-AUG-16:02 | 2474.98 | 0.00 |
| September | 0.00 | 0.00 | 0.616218E+10 | 0.448295E+10 | 3358.19 | 24-SEP-16:10 | 2729.13 | 0.00 |
| October | 0.00 | 0.00 | 0.470791E+10 | 0.412433E+10 | 2932.26 | 03-OCT-15:10 | 2652.73 | 0.00 |
| November | 0.00 | 0.00 | 0.296216E+10 | 0.279021E+10 | 2302.27 | 04-NOV-14:10 | 2300.15 | 0.00 |
| December | 0.00 | 0.00 | 0.128377E+10 | 0.125445E+10 | 1712.71 | 02-DEC-14:00 | 1712.71 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.489206E+11 | 0.395816E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.614942E+09 | 0.600181E+09 | 1277.35 | 1277.35 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.704668E+10 | 0.495057E+10 | 3619.54 | 2729.13 | 0.00 |
Report: CoilReportMonthly
For: SPLIT MSW COOLING COIL
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.119014E+10 | 0.117373E+10 | 3308.65 | 12-JAN-15:20 | 3308.65 | 0.00 |
| February | 0.00 | 0.00 | 0.278052E+10 | 0.267188E+10 | 4702.95 | 20-FEB-16:10 | 4702.95 | 0.00 |
| March | 0.00 | 0.00 | 0.631409E+10 | 0.592492E+10 | 6297.82 | 12-MAR-16:10 | 5899.42 | 0.00 |
| April | 0.00 | 0.00 | 0.996700E+10 | 0.934158E+10 | 7744.35 | 27-APR-16:03 | 7744.35 | 0.00 |
| May | 0.00 | 0.00 | 0.131844E+11 | 0.113673E+11 | 8302.31 | 05-MAY-16:03 | 8302.31 | 0.00 |
| June | 0.00 | 0.00 | 0.138534E+11 | 0.109658E+11 | 8506.18 | 22-JUN-16:30 | 6556.04 | 0.00 |
| July | 0.00 | 0.00 | 0.152153E+11 | 0.104825E+11 | 9137.82 | 01-JUL-16:01 | 6432.46 | 0.00 |
| August | 0.00 | 0.00 | 0.141725E+11 | 0.948582E+10 | 8380.74 | 13-AUG-16:02 | 5925.61 | 0.00 |
| September | 0.00 | 0.00 | 0.122253E+11 | 0.871062E+10 | 8105.18 | 22-SEP-15:10 | 6473.40 | 0.00 |
| October | 0.00 | 0.00 | 0.894037E+10 | 0.782879E+10 | 7432.84 | 03-OCT-15:10 | 6679.47 | 0.00 |
| November | 0.00 | 0.00 | 0.526569E+10 | 0.499147E+10 | 5612.45 | 04-NOV-15:10 | 5612.45 | 0.00 |
| December | 0.00 | 0.00 | 0.200406E+10 | 0.196684E+10 | 3930.82 | 02-DEC-14:30 | 3930.82 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.105113E+12 | 0.849113E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.119014E+10 | 0.117373E+10 | 3308.65 | 3308.65 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.152153E+11 | 0.113673E+11 | 9137.82 | 8302.31 | 0.00 |
Report: CoilReportMonthly
For: SPLIT MNW COOLING COIL
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 61903258.79 | 59593925.21 | 1105.36 | 14-JAN-17:10 | 1036.98 | 0.00 |
| February | 0.00 | 0.00 | 0.123030E+10 | 0.116634E+10 | 2924.74 | 22-FEB-17:10 | 2924.74 | 0.00 |
| March | 0.00 | 0.00 | 0.483276E+10 | 0.449058E+10 | 5271.97 | 29-MAR-16:13 | 5166.02 | 0.00 |
| April | 0.00 | 0.00 | 0.905293E+10 | 0.844679E+10 | 7270.18 | 27-APR-16:10 | 7270.18 | 0.00 |
| May | 0.00 | 0.00 | 0.130092E+11 | 0.111915E+11 | 8138.98 | 05-MAY-16:30 | 8138.98 | 0.00 |
| June | 0.00 | 0.00 | 0.139012E+11 | 0.110047E+11 | 8677.75 | 22-JUN-16:40 | 6658.55 | 0.00 |
| July | 0.00 | 0.00 | 0.152039E+11 | 0.104718E+11 | 8961.54 | 01-JUL-16:13 | 6327.40 | 0.00 |
| August | 0.00 | 0.00 | 0.139879E+11 | 0.931522E+10 | 7991.56 | 07-AUG-16:20 | 6179.67 | 0.00 |
| September | 0.00 | 0.00 | 0.113809E+11 | 0.794231E+10 | 7088.83 | 14-SEP-16:20 | 5055.07 | 0.00 |
| October | 0.00 | 0.00 | 0.691226E+10 | 0.590745E+10 | 6054.39 | 03-OCT-15:20 | 5308.43 | 0.00 |
| November | 0.00 | 0.00 | 0.275414E+10 | 0.257677E+10 | 3463.54 | 04-NOV-16:10 | 3430.46 | 0.00 |
| December | 0.00 | 0.00 | 0.346653E+09 | 0.338852E+09 | 1632.54 | 28-DEC-16:10 | 1632.54 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.926740E+11 | 0.729119E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 61903258.79 | 59593925.21 | 1105.36 | 1036.98 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.152039E+11 | 0.111915E+11 | 8961.54 | 8138.98 | 0.00 |
Report: CoilReportMonthly
For: SPLIT MSE COOLING COIL
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.119461E+10 | 0.117848E+10 | 3087.84 | 12-JAN-14:30 | 3087.84 | 0.00 |
| February | 0.00 | 0.00 | 0.285618E+10 | 0.274418E+10 | 4353.18 | 20-FEB-14:20 | 4353.18 | 0.00 |
| March | 0.00 | 0.00 | 0.637366E+10 | 0.597664E+10 | 5680.82 | 12-MAR-16:10 | 5306.03 | 0.00 |
| April | 0.00 | 0.00 | 0.100132E+11 | 0.937823E+10 | 7250.35 | 15-APR-15:10 | 7250.35 | 0.00 |
| May | 0.00 | 0.00 | 0.132468E+11 | 0.114199E+11 | 7498.79 | 05-MAY-15:10 | 7498.79 | 0.00 |
| June | 0.00 | 0.00 | 0.137402E+11 | 0.108542E+11 | 8256.02 | 23-JUN-14:10 | 5789.46 | 0.00 |
| July | 0.00 | 0.00 | 0.152270E+11 | 0.104900E+11 | 8648.50 | 01-JUL-16:01 | 6023.49 | 0.00 |
| August | 0.00 | 0.00 | 0.141833E+11 | 0.949180E+10 | 7806.76 | 27-AUG-16:02 | 5387.40 | 0.00 |
| September | 0.00 | 0.00 | 0.121961E+11 | 0.867995E+10 | 7600.32 | 22-SEP-15:10 | 6038.64 | 0.00 |
| October | 0.00 | 0.00 | 0.899013E+10 | 0.787072E+10 | 6998.02 | 03-OCT-14:10 | 6359.77 | 0.00 |
| November | 0.00 | 0.00 | 0.528324E+10 | 0.500486E+10 | 5217.74 | 04-NOV-13:30 | 5198.19 | 0.00 |
| December | 0.00 | 0.00 | 0.201923E+10 | 0.198340E+10 | 3691.40 | 02-DEC-14:00 | 3691.40 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.105324E+12 | 0.850724E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.119461E+10 | 0.117848E+10 | 3087.84 | 3087.84 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.152270E+11 | 0.114199E+11 | 8648.50 | 7498.79 | 0.00 |
Report: CoilReportMonthly
For: SPLIT MNE COOLING COIL
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 50455050.03 | 48594408.71 | 852.40 | 14-JAN-17:10 | 798.26 | 0.00 |
| February | 0.00 | 0.00 | 0.126183E+10 | 0.119549E+10 | 2707.35 | 24-FEB-16:10 | 2534.47 | 0.00 |
| March | 0.00 | 0.00 | 0.488874E+10 | 0.453787E+10 | 4578.62 | 29-MAR-16:03 | 4481.07 | 0.00 |
| April | 0.00 | 0.00 | 0.909918E+10 | 0.848364E+10 | 6577.49 | 18-APR-15:10 | 5674.27 | 0.00 |
| May | 0.00 | 0.00 | 0.130702E+11 | 0.112445E+11 | 7314.69 | 25-MAY-16:17 | 6045.57 | 0.00 |
| June | 0.00 | 0.00 | 0.137867E+11 | 0.108933E+11 | 8274.64 | 23-JUN-15:10 | 5869.11 | 0.00 |
| July | 0.00 | 0.00 | 0.152142E+11 | 0.104797E+11 | 8453.45 | 01-JUL-16:01 | 5897.00 | 0.00 |
| August | 0.00 | 0.00 | 0.139977E+11 | 0.932154E+10 | 7483.11 | 07-AUG-16:20 | 5726.25 | 0.00 |
| September | 0.00 | 0.00 | 0.113515E+11 | 0.791220E+10 | 6660.46 | 14-SEP-16:20 | 4685.61 | 0.00 |
| October | 0.00 | 0.00 | 0.696293E+10 | 0.594895E+10 | 5555.64 | 03-OCT-15:10 | 4868.15 | 0.00 |
| November | 0.00 | 0.00 | 0.275914E+10 | 0.257767E+10 | 3031.29 | 09-NOV-13:00 | 2810.73 | 0.00 |
| December | 0.00 | 0.00 | 0.322535E+09 | 0.315945E+09 | 1316.30 | 01-DEC-14:00 | 1316.30 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.927651E+11 | 0.729594E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 50455050.03 | 48594408.71 | 852.40 | 798.26 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.152142E+11 | 0.112445E+11 | 8453.45 | 6045.57 | 0.00 |
Report: CoilReportMonthly
For: SPLIT MN1 COOLING COIL
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.115841E+09 | 0.108033E+09 | 1008.07 | 14-JAN-17:10 | 945.30 | 0.00 |
| February | 0.00 | 0.00 | 0.125783E+10 | 0.118257E+10 | 2352.14 | 24-FEB-17:10 | 2178.19 | 0.00 |
| March | 0.00 | 0.00 | 0.422621E+10 | 0.389680E+10 | 3686.62 | 29-MAR-16:13 | 3590.25 | 0.00 |
| April | 0.00 | 0.00 | 0.736336E+10 | 0.680899E+10 | 5138.96 | 18-APR-16:02 | 4439.37 | 0.00 |
| May | 0.00 | 0.00 | 0.105850E+11 | 0.897394E+10 | 5861.77 | 25-MAY-17:10 | 4779.37 | 0.00 |
| June | 0.00 | 0.00 | 0.115175E+11 | 0.890716E+10 | 6634.08 | 23-JUN-15:10 | 4608.62 | 0.00 |
| July | 0.00 | 0.00 | 0.128722E+11 | 0.869301E+10 | 6910.84 | 01-JUL-16:13 | 4685.15 | 0.00 |
| August | 0.00 | 0.00 | 0.120631E+11 | 0.785873E+10 | 6254.97 | 27-AUG-16:02 | 4122.15 | 0.00 |
| September | 0.00 | 0.00 | 0.987380E+10 | 0.673206E+10 | 5660.18 | 14-SEP-17:20 | 3802.42 | 0.00 |
| October | 0.00 | 0.00 | 0.605467E+10 | 0.510147E+10 | 4404.62 | 03-OCT-16:10 | 3776.27 | 0.00 |
| November | 0.00 | 0.00 | 0.263919E+10 | 0.244358E+10 | 2532.25 | 04-NOV-16:10 | 2505.81 | 0.00 |
| December | 0.00 | 0.00 | 0.452071E+09 | 0.438522E+09 | 1314.37 | 28-DEC-17:10 | 1309.76 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.790207E+11 | 0.611449E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.115841E+09 | 0.108033E+09 | 1008.07 | 945.30 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.128722E+11 | 0.897394E+10 | 6910.84 | 4779.37 | 0.00 |
Report: CoilReportMonthly
For: SPLIT MN2 COOLING COIL
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.116814E+09 | 0.108996E+09 | 1006.98 | 14-JAN-17:10 | 944.28 | 0.00 |
| February | 0.00 | 0.00 | 0.126670E+10 | 0.119110E+10 | 2354.83 | 24-FEB-17:10 | 2180.80 | 0.00 |
| March | 0.00 | 0.00 | 0.423019E+10 | 0.390056E+10 | 3678.56 | 29-MAR-16:13 | 3582.38 | 0.00 |
| April | 0.00 | 0.00 | 0.736587E+10 | 0.681125E+10 | 5132.72 | 18-APR-16:02 | 4433.96 | 0.00 |
| May | 0.00 | 0.00 | 0.105875E+11 | 0.897618E+10 | 5850.97 | 25-MAY-17:10 | 4769.60 | 0.00 |
| June | 0.00 | 0.00 | 0.115142E+11 | 0.890403E+10 | 6632.31 | 23-JUN-15:10 | 4607.37 | 0.00 |
| July | 0.00 | 0.00 | 0.128728E+11 | 0.869347E+10 | 6906.83 | 01-JUL-16:13 | 4682.64 | 0.00 |
| August | 0.00 | 0.00 | 0.120637E+11 | 0.785925E+10 | 6251.54 | 27-AUG-16:02 | 4119.75 | 0.00 |
| September | 0.00 | 0.00 | 0.987308E+10 | 0.673137E+10 | 5655.49 | 14-SEP-17:20 | 3798.65 | 0.00 |
| October | 0.00 | 0.00 | 0.605721E+10 | 0.510378E+10 | 4399.12 | 03-OCT-16:10 | 3771.39 | 0.00 |
| November | 0.00 | 0.00 | 0.264208E+10 | 0.244640E+10 | 2526.01 | 04-NOV-16:10 | 2499.64 | 0.00 |
| December | 0.00 | 0.00 | 0.456698E+09 | 0.443078E+09 | 1312.87 | 28-DEC-17:10 | 1308.24 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.790468E+11 | 0.611695E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.116814E+09 | 0.108996E+09 | 1006.98 | 944.28 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.128728E+11 | 0.897618E+10 | 6906.83 | 4769.60 | 0.00 |
Report: CoilReportMonthly
For: SPLIT MS1 COOLING COIL
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.165255E+10 | 0.161741E+10 | 3081.47 | 12-JAN-14:30 | 3081.47 | 0.00 |
| February | 0.00 | 0.00 | 0.295931E+10 | 0.283264E+10 | 3940.71 | 20-FEB-14:30 | 3940.71 | 0.00 |
| March | 0.00 | 0.00 | 0.573442E+10 | 0.535477E+10 | 4912.08 | 12-MAR-16:10 | 4572.31 | 0.00 |
| April | 0.00 | 0.00 | 0.828257E+10 | 0.770621E+10 | 5676.28 | 18-APR-15:10 | 4944.41 | 0.00 |
| May | 0.00 | 0.00 | 0.107611E+11 | 0.914932E+10 | 5981.49 | 20-MAY-16:04 | 4888.70 | 0.00 |
| June | 0.00 | 0.00 | 0.114673E+11 | 0.886647E+10 | 6594.75 | 23-JUN-15:10 | 4602.17 | 0.00 |
| July | 0.00 | 0.00 | 0.128821E+11 | 0.870203E+10 | 7085.21 | 01-JUL-16:01 | 4794.26 | 0.00 |
| August | 0.00 | 0.00 | 0.122491E+11 | 0.802814E+10 | 6650.28 | 27-AUG-16:02 | 4437.29 | 0.00 |
| September | 0.00 | 0.00 | 0.107297E+11 | 0.750242E+10 | 6250.93 | 24-SEP-16:10 | 4974.14 | 0.00 |
| October | 0.00 | 0.00 | 0.810863E+10 | 0.703959E+10 | 5745.63 | 03-OCT-14:10 | 5210.39 | 0.00 |
| November | 0.00 | 0.00 | 0.524371E+10 | 0.494650E+10 | 4689.91 | 04-NOV-13:50 | 4675.17 | 0.00 |
| December | 0.00 | 0.00 | 0.245140E+10 | 0.240095E+10 | 3647.42 | 02-DEC-14:00 | 3647.42 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.925219E+11 | 0.741464E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.165255E+10 | 0.161741E+10 | 3081.47 | 3081.47 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.128821E+11 | 0.914932E+10 | 7085.21 | 5210.39 | 0.00 |
Report: CoilReportMonthly
For: SPLIT MS2 COOLING COIL
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.165903E+10 | 0.162386E+10 | 3086.98 | 12-JAN-14:30 | 3086.98 | 0.00 |
| February | 0.00 | 0.00 | 0.296548E+10 | 0.283864E+10 | 3947.21 | 20-FEB-14:30 | 3947.21 | 0.00 |
| March | 0.00 | 0.00 | 0.573760E+10 | 0.535778E+10 | 4907.13 | 12-MAR-16:10 | 4567.66 | 0.00 |
| April | 0.00 | 0.00 | 0.828500E+10 | 0.770840E+10 | 5675.90 | 18-APR-15:10 | 4944.57 | 0.00 |
| May | 0.00 | 0.00 | 0.107636E+11 | 0.915157E+10 | 5977.04 | 20-MAY-16:04 | 4884.90 | 0.00 |
| June | 0.00 | 0.00 | 0.114640E+11 | 0.886335E+10 | 6593.00 | 23-JUN-15:10 | 4600.92 | 0.00 |
| July | 0.00 | 0.00 | 0.128827E+11 | 0.870249E+10 | 7081.92 | 01-JUL-16:01 | 4792.33 | 0.00 |
| August | 0.00 | 0.00 | 0.122498E+11 | 0.802866E+10 | 6646.83 | 27-AUG-16:02 | 4434.80 | 0.00 |
| September | 0.00 | 0.00 | 0.107290E+11 | 0.750172E+10 | 6246.79 | 22-SEP-15:10 | 4944.21 | 0.00 |
| October | 0.00 | 0.00 | 0.811090E+10 | 0.704168E+10 | 5750.23 | 03-OCT-14:10 | 5215.16 | 0.00 |
| November | 0.00 | 0.00 | 0.524499E+10 | 0.494774E+10 | 4695.07 | 04-NOV-13:50 | 4680.40 | 0.00 |
| December | 0.00 | 0.00 | 0.245528E+10 | 0.240485E+10 | 3651.79 | 02-DEC-14:00 | 3651.79 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.925473E+11 | 0.741707E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.165903E+10 | 0.162386E+10 | 3086.98 | 3086.98 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.128827E+11 | 0.915157E+10 | 7081.92 | 5215.16 | 0.00 |
Report: CoilReportMonthly
For: SPLIT TSW COOLING COIL
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.438949E+09 | 0.435622E+09 | 1860.57 | 12-JAN-15:20 | 1860.57 | 0.00 |
| February | 0.00 | 0.00 | 0.117173E+10 | 0.113782E+10 | 2928.75 | 20-FEB-15:20 | 2928.75 | 0.00 |
| March | 0.00 | 0.00 | 0.313031E+10 | 0.297048E+10 | 4201.72 | 28-MAR-16:01 | 4201.72 | 0.00 |
| April | 0.00 | 0.00 | 0.557629E+10 | 0.526758E+10 | 5265.53 | 15-APR-15:20 | 5265.53 | 0.00 |
| May | 0.00 | 0.00 | 0.767072E+10 | 0.669755E+10 | 5583.85 | 05-MAY-16:03 | 5583.85 | 0.00 |
| June | 0.00 | 0.00 | 0.805044E+10 | 0.650683E+10 | 5573.03 | 10-JUN-16:03 | 5041.20 | 0.00 |
| July | 0.00 | 0.00 | 0.871109E+10 | 0.612453E+10 | 5804.85 | 01-JUL-16:01 | 4278.94 | 0.00 |
| August | 0.00 | 0.00 | 0.796572E+10 | 0.544329E+10 | 5333.78 | 13-AUG-16:02 | 3963.18 | 0.00 |
| September | 0.00 | 0.00 | 0.664071E+10 | 0.480342E+10 | 5264.99 | 22-SEP-15:10 | 4302.97 | 0.00 |
| October | 0.00 | 0.00 | 0.453927E+10 | 0.404060E+10 | 4937.30 | 03-OCT-15:10 | 4483.91 | 0.00 |
| November | 0.00 | 0.00 | 0.231958E+10 | 0.223425E+10 | 3607.38 | 04-NOV-15:10 | 3607.38 | 0.00 |
| December | 0.00 | 0.00 | 0.683761E+09 | 0.675765E+09 | 2235.38 | 02-DEC-15:00 | 2235.38 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.568986E+11 | 0.463377E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.438949E+09 | 0.435622E+09 | 1860.57 | 1860.57 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.871109E+10 | 0.669755E+10 | 5804.85 | 5583.85 | 0.00 |
Report: CoilReportMonthly
For: SPLIT TNW COOLING COIL
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 29183432.45 | 28629820.54 | 561.27 | 12-JAN-16:10 | 561.27 | 0.00 |
| February | 0.00 | 0.00 | 0.480254E+09 | 0.461078E+09 | 1773.62 | 22-FEB-16:10 | 1773.62 | 0.00 |
| March | 0.00 | 0.00 | 0.236364E+10 | 0.222226E+10 | 3574.24 | 28-MAR-16:30 | 3574.24 | 0.00 |
| April | 0.00 | 0.00 | 0.507197E+10 | 0.477113E+10 | 4904.84 | 27-APR-16:03 | 4904.84 | 0.00 |
| May | 0.00 | 0.00 | 0.757312E+10 | 0.659806E+10 | 5462.27 | 05-MAY-16:05 | 5462.27 | 0.00 |
| June | 0.00 | 0.00 | 0.807275E+10 | 0.652423E+10 | 5642.02 | 22-JUN-16:30 | 4521.47 | 0.00 |
| July | 0.00 | 0.00 | 0.870610E+10 | 0.611901E+10 | 5677.86 | 01-JUL-16:13 | 4191.06 | 0.00 |
| August | 0.00 | 0.00 | 0.786120E+10 | 0.534438E+10 | 5160.78 | 07-AUG-16:20 | 4123.87 | 0.00 |
| September | 0.00 | 0.00 | 0.617989E+10 | 0.437788E+10 | 4560.36 | 22-SEP-15:20 | 3619.06 | 0.00 |
| October | 0.00 | 0.00 | 0.345336E+10 | 0.300312E+10 | 4035.31 | 03-OCT-15:10 | 3591.53 | 0.00 |
| November | 0.00 | 0.00 | 0.110407E+10 | 0.105046E+10 | 2170.04 | 09-NOV-15:10 | 2099.24 | 0.00 |
| December | 0.00 | 0.00 | 89525827.62 | 88268652.93 | 808.50 | 28-DEC-16:10 | 808.50 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.509851E+11 | 0.405885E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 29183432.45 | 28629820.54 | 561.27 | 561.27 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.870610E+10 | 0.659806E+10 | 5677.86 | 5462.27 | 0.00 |
Report: CoilReportMonthly
For: SPLIT TSE COOLING COIL
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.406419E+09 | 0.403369E+09 | 1703.93 | 12-JAN-14:40 | 1703.93 | 0.00 |
| February | 0.00 | 0.00 | 0.117779E+10 | 0.114359E+10 | 2705.41 | 20-FEB-14:30 | 2705.41 | 0.00 |
| March | 0.00 | 0.00 | 0.315352E+10 | 0.298841E+10 | 3722.44 | 29-MAR-14:10 | 3579.09 | 0.00 |
| April | 0.00 | 0.00 | 0.560420E+10 | 0.528829E+10 | 4956.63 | 15-APR-14:00 | 4956.63 | 0.00 |
| May | 0.00 | 0.00 | 0.770693E+10 | 0.672646E+10 | 5056.75 | 05-MAY-15:10 | 5056.75 | 0.00 |
| June | 0.00 | 0.00 | 0.798971E+10 | 0.644462E+10 | 5339.43 | 23-JUN-14:10 | 3890.11 | 0.00 |
| July | 0.00 | 0.00 | 0.871612E+10 | 0.612629E+10 | 5445.14 | 01-JUL-13:00 | 4060.66 | 0.00 |
| August | 0.00 | 0.00 | 0.797270E+10 | 0.544611E+10 | 4902.38 | 13-AUG-16:02 | 3579.52 | 0.00 |
| September | 0.00 | 0.00 | 0.662676E+10 | 0.478625E+10 | 4934.49 | 22-SEP-14:20 | 4025.38 | 0.00 |
| October | 0.00 | 0.00 | 0.456853E+10 | 0.406375E+10 | 4667.89 | 03-OCT-14:10 | 4285.33 | 0.00 |
| November | 0.00 | 0.00 | 0.231526E+10 | 0.222776E+10 | 3385.61 | 09-NOV-13:30 | 3285.78 | 0.00 |
| December | 0.00 | 0.00 | 0.664572E+09 | 0.657315E+09 | 2059.40 | 03-DEC-14:00 | 2059.40 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.569025E+11 | 0.463022E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.406419E+09 | 0.403369E+09 | 1703.93 | 1703.93 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.871612E+10 | 0.672646E+10 | 5445.14 | 5056.75 | 0.00 |
Report: CoilReportMonthly
For: SPLIT TNE COOLING COIL
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 18873467.15 | 18561450.52 | 475.33 | 26-JAN-14:00 | 475.33 | 0.00 |
| February | 0.00 | 0.00 | 0.459556E+09 | 0.440901E+09 | 1552.65 | 24-FEB-16:10 | 1454.53 | 0.00 |
| March | 0.00 | 0.00 | 0.237978E+10 | 0.223232E+10 | 3020.84 | 29-MAR-15:10 | 2929.42 | 0.00 |
| April | 0.00 | 0.00 | 0.510031E+10 | 0.479183E+10 | 4377.56 | 15-APR-15:10 | 4377.56 | 0.00 |
| May | 0.00 | 0.00 | 0.760934E+10 | 0.662737E+10 | 4852.50 | 05-MAY-15:10 | 4852.50 | 0.00 |
| June | 0.00 | 0.00 | 0.801190E+10 | 0.646221E+10 | 5327.10 | 23-JUN-14:10 | 3864.45 | 0.00 |
| July | 0.00 | 0.00 | 0.871100E+10 | 0.612095E+10 | 5293.92 | 01-JUL-13:00 | 3939.66 | 0.00 |
| August | 0.00 | 0.00 | 0.786817E+10 | 0.534738E+10 | 4791.56 | 07-AUG-16:10 | 3787.45 | 0.00 |
| September | 0.00 | 0.00 | 0.616660E+10 | 0.436098E+10 | 4191.71 | 22-SEP-15:10 | 3297.23 | 0.00 |
| October | 0.00 | 0.00 | 0.348183E+10 | 0.302383E+10 | 3666.96 | 03-OCT-15:10 | 3251.27 | 0.00 |
| November | 0.00 | 0.00 | 0.108197E+10 | 0.102653E+10 | 1955.98 | 09-NOV-13:40 | 1853.63 | 0.00 |
| December | 0.00 | 0.00 | 68964274.24 | 68082015.59 | 548.46 | 28-DEC-15:10 | 548.46 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.509583E+11 | 0.405209E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 18873467.15 | 18561450.52 | 475.33 | 475.33 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.871100E+10 | 0.662737E+10 | 5327.10 | 4852.50 | 0.00 |
Report: CoilReportMonthly
For: SPLIT TN1 COOLING COIL
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 12736446.59 | 12460760.08 | 321.01 | 26-JAN-14:00 | 321.01 | 0.00 |
| February | 0.00 | 0.00 | 0.362838E+09 | 0.345472E+09 | 1295.34 | 24-FEB-16:10 | 1211.25 | 0.00 |
| March | 0.00 | 0.00 | 0.197391E+10 | 0.183971E+10 | 2470.72 | 29-MAR-16:03 | 2420.34 | 0.00 |
| April | 0.00 | 0.00 | 0.415847E+10 | 0.388167E+10 | 3421.62 | 18-APR-15:10 | 2987.73 | 0.00 |
| May | 0.00 | 0.00 | 0.625179E+10 | 0.539115E+10 | 3899.75 | 25-MAY-16:17 | 3288.37 | 0.00 |
| June | 0.00 | 0.00 | 0.677417E+10 | 0.538406E+10 | 4312.66 | 22-JUN-16:30 | 3351.54 | 0.00 |
| July | 0.00 | 0.00 | 0.741149E+10 | 0.515320E+10 | 4397.30 | 01-JUL-16:13 | 3160.99 | 0.00 |
| August | 0.00 | 0.00 | 0.680218E+10 | 0.455943E+10 | 3951.51 | 07-AUG-16:10 | 3100.51 | 0.00 |
| September | 0.00 | 0.00 | 0.536794E+10 | 0.373227E+10 | 3557.87 | 14-SEP-16:10 | 2577.43 | 0.00 |
| October | 0.00 | 0.00 | 0.298303E+10 | 0.255298E+10 | 2931.38 | 03-OCT-15:10 | 2595.80 | 0.00 |
| November | 0.00 | 0.00 | 0.899148E+09 | 0.847165E+09 | 1607.03 | 09-NOV-14:00 | 1515.78 | 0.00 |
| December | 0.00 | 0.00 | 41707553.44 | 41116186.25 | 458.43 | 28-DEC-16:10 | 458.43 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.430394E+11 | 0.337407E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 12736446.59 | 12460760.08 | 321.01 | 321.01 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.741149E+10 | 0.539115E+10 | 4397.30 | 3351.54 | 0.00 |
Report: CoilReportMonthly
For: SPLIT TN2 COOLING COIL
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 12972401.11 | 12692651.39 | 329.95 | 26-JAN-14:00 | 329.95 | 0.00 |
| February | 0.00 | 0.00 | 0.366651E+09 | 0.349179E+09 | 1297.92 | 24-FEB-16:10 | 1213.86 | 0.00 |
| March | 0.00 | 0.00 | 0.197787E+10 | 0.184347E+10 | 2461.70 | 29-MAR-16:03 | 2411.46 | 0.00 |
| April | 0.00 | 0.00 | 0.416048E+10 | 0.388345E+10 | 3418.83 | 18-APR-15:10 | 2985.63 | 0.00 |
| May | 0.00 | 0.00 | 0.625358E+10 | 0.539273E+10 | 3888.22 | 25-MAY-16:17 | 3277.90 | 0.00 |
| June | 0.00 | 0.00 | 0.677233E+10 | 0.538223E+10 | 4300.33 | 22-JUN-16:30 | 3340.60 | 0.00 |
| July | 0.00 | 0.00 | 0.741186E+10 | 0.515344E+10 | 4390.42 | 01-JUL-16:13 | 3155.59 | 0.00 |
| August | 0.00 | 0.00 | 0.680266E+10 | 0.455975E+10 | 3944.75 | 07-AUG-16:10 | 3094.58 | 0.00 |
| September | 0.00 | 0.00 | 0.536772E+10 | 0.373198E+10 | 3549.01 | 14-SEP-16:10 | 2570.32 | 0.00 |
| October | 0.00 | 0.00 | 0.298529E+10 | 0.255504E+10 | 2927.73 | 03-OCT-15:10 | 2592.75 | 0.00 |
| November | 0.00 | 0.00 | 0.902704E+09 | 0.850591E+09 | 1610.60 | 09-NOV-14:00 | 1519.76 | 0.00 |
| December | 0.00 | 0.00 | 42805703.05 | 42206305.48 | 455.41 | 28-DEC-16:10 | 455.41 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.430569E+11 | 0.337568E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 12972401.11 | 12692651.39 | 329.95 | 329.95 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.741186E+10 | 0.539273E+10 | 4390.42 | 3340.60 | 0.00 |
Report: CoilReportMonthly
For: SPLIT TS1 COOLING COIL
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.402622E+09 | 0.399304E+09 | 1611.82 | 12-JAN-14:50 | 1611.82 | 0.00 |
| February | 0.00 | 0.00 | 0.108779E+10 | 0.105321E+10 | 2442.54 | 20-FEB-14:40 | 2442.54 | 0.00 |
| March | 0.00 | 0.00 | 0.276104E+10 | 0.260608E+10 | 3232.65 | 12-MAR-16:10 | 3040.45 | 0.00 |
| April | 0.00 | 0.00 | 0.466766E+10 | 0.438189E+10 | 3944.37 | 15-APR-15:10 | 3944.37 | 0.00 |
| May | 0.00 | 0.00 | 0.635065E+10 | 0.549101E+10 | 4006.77 | 05-MAY-15:10 | 4006.77 | 0.00 |
| June | 0.00 | 0.00 | 0.675167E+10 | 0.536616E+10 | 4285.09 | 23-JUN-14:10 | 3103.65 | 0.00 |
| July | 0.00 | 0.00 | 0.741696E+10 | 0.515859E+10 | 4530.33 | 01-JUL-16:01 | 3256.90 | 0.00 |
| August | 0.00 | 0.00 | 0.690838E+10 | 0.465873E+10 | 4194.70 | 13-AUG-16:02 | 3030.19 | 0.00 |
| September | 0.00 | 0.00 | 0.583559E+10 | 0.416123E+10 | 4095.38 | 22-SEP-15:10 | 3341.11 | 0.00 |
| October | 0.00 | 0.00 | 0.409003E+10 | 0.360663E+10 | 3896.10 | 03-OCT-14:10 | 3580.76 | 0.00 |
| November | 0.00 | 0.00 | 0.216867E+10 | 0.207937E+10 | 3027.98 | 09-NOV-13:40 | 2934.79 | 0.00 |
| December | 0.00 | 0.00 | 0.655284E+09 | 0.646953E+09 | 1925.19 | 02-DEC-14:20 | 1925.19 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.490963E+11 | 0.396091E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.402622E+09 | 0.399304E+09 | 1611.82 | 1611.82 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.741696E+10 | 0.549101E+10 | 4530.33 | 4006.77 | 0.00 |
Report: CoilReportMonthly
For: SPLIT TS2 COOLING COIL
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.405897E+09 | 0.402565E+09 | 1617.20 | 12-JAN-14:50 | 1617.20 | 0.00 |
| February | 0.00 | 0.00 | 0.109285E+10 | 0.105818E+10 | 2449.19 | 20-FEB-14:40 | 2449.19 | 0.00 |
| March | 0.00 | 0.00 | 0.276457E+10 | 0.260945E+10 | 3224.84 | 12-MAR-16:10 | 3032.94 | 0.00 |
| April | 0.00 | 0.00 | 0.466962E+10 | 0.438364E+10 | 3942.26 | 15-APR-15:10 | 3942.26 | 0.00 |
| May | 0.00 | 0.00 | 0.635248E+10 | 0.549262E+10 | 4003.99 | 05-MAY-15:10 | 4003.99 | 0.00 |
| June | 0.00 | 0.00 | 0.674984E+10 | 0.536434E+10 | 4286.01 | 23-JUN-14:10 | 3104.98 | 0.00 |
| July | 0.00 | 0.00 | 0.741734E+10 | 0.515883E+10 | 4524.16 | 01-JUL-16:01 | 3252.10 | 0.00 |
| August | 0.00 | 0.00 | 0.690887E+10 | 0.465905E+10 | 4184.98 | 13-AUG-16:02 | 3021.96 | 0.00 |
| September | 0.00 | 0.00 | 0.583534E+10 | 0.416092E+10 | 4091.08 | 22-SEP-14:20 | 3345.13 | 0.00 |
| October | 0.00 | 0.00 | 0.409194E+10 | 0.360842E+10 | 3899.58 | 03-OCT-14:10 | 3584.47 | 0.00 |
| November | 0.00 | 0.00 | 0.217146E+10 | 0.208208E+10 | 3033.27 | 09-NOV-13:40 | 2940.30 | 0.00 |
| December | 0.00 | 0.00 | 0.659070E+09 | 0.650740E+09 | 1930.23 | 02-DEC-14:20 | 1930.23 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.491193E+11 | 0.396308E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.405897E+09 | 0.402565E+09 | 1617.20 | 1617.20 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.741734E+10 | 0.549262E+10 | 4524.16 | 4003.99 | 0.00 |
Report: FanReportMonthly
For: SPLIT GSW SUPPLY FAN
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 29338438.48 | 0.39 | 94.83 | 12-JAN-15:20 | 1.07 |
| February | 69849964.02 | 0.63 | 134.35 | 20-FEB-16:10 | 1.05 |
| March | 0.169295E+09 | 0.97 | 189.86 | 28-MAR-16:01 | 1.03 |
| April | 0.306051E+09 | 1.06 | 253.94 | 27-APR-16:10 | 1.01 |
| May | 0.434264E+09 | 1.04 | 296.01 | 05-MAY-16:10 | 0.99 |
| June | 0.474252E+09 | 1.03 | 301.22 | 06-JUN-16:10 | 0.99 |
| July | 0.522172E+09 | 1.02 | 300.74 | 02-JUL-16:50 | 0.98 |
| August | 0.502679E+09 | 1.02 | 279.21 | 07-AUG-16:03 | 0.99 |
| September | 0.446718E+09 | 1.03 | 273.59 | 24-SEP-16:10 | 0.99 |
| October | 0.342374E+09 | 1.05 | 254.65 | 03-OCT-15:10 | 1.00 |
| November | 0.201709E+09 | 1.06 | 187.29 | 04-NOV-15:10 | 1.03 |
| December | 73446917.92 | 0.66 | 129.39 | 02-DEC-14:30 | 1.06 |
| Annual Sum or Average | 0.357215E+10 | 0.91 | |||
| Minimum of Months | 29338438.48 | 0.39 | 94.83 | 0.98 | |
| Maximum of Months | 0.522172E+09 | 1.06 | 301.22 | 1.07 |
Report: FanReportMonthly
For: G SW APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.65 | 20.01 | 01-JAN-00:10 | 0.65 |
| February | 48400714.57 | 0.64 | 20.01 | 01-FEB-00:10 | 0.65 |
| March | 53586505.42 | 0.64 | 20.01 | 01-MAR-00:10 | 0.64 |
| April | 51857908.47 | 0.64 | 20.01 | 01-APR-00:10 | 0.64 |
| May | 53586505.42 | 0.64 | 20.01 | 01-MAY-00:10 | 0.64 |
| June | 51857908.47 | 0.63 | 20.01 | 01-JUN-00:10 | 0.64 |
| July | 53586505.42 | 0.63 | 20.01 | 01-JUL-00:10 | 0.63 |
| August | 53586505.42 | 0.63 | 20.01 | 01-AUG-00:10 | 0.63 |
| September | 51857908.47 | 0.63 | 20.01 | 01-SEP-00:10 | 0.63 |
| October | 53586505.42 | 0.64 | 20.01 | 01-OCT-00:10 | 0.64 |
| November | 51857908.47 | 0.64 | 20.01 | 01-NOV-00:10 | 0.64 |
| December | 53586505.42 | 0.65 | 20.01 | 01-DEC-00:10 | 0.65 |
| Annual Sum or Average | 0.630938E+09 | 0.64 | |||
| Minimum of Months | 48400714.57 | 0.63 | 20.01 | 0.63 | |
| Maximum of Months | 53586505.42 | 0.65 | 20.01 | 0.65 |
Report: FanReportMonthly
For: G SW APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.64 | 20.01 | 01-JAN-00:10 | 0.64 |
| February | 48400714.57 | 0.64 | 20.01 | 01-FEB-00:10 | 0.65 |
| March | 53586505.42 | 0.64 | 20.01 | 01-MAR-00:10 | 0.64 |
| April | 51857908.47 | 0.64 | 20.01 | 01-APR-00:10 | 0.64 |
| May | 53586505.42 | 0.64 | 20.01 | 01-MAY-00:10 | 0.64 |
| June | 51857908.47 | 0.64 | 20.01 | 01-JUN-00:10 | 0.64 |
| July | 53586505.42 | 0.64 | 20.01 | 01-JUL-00:10 | 0.64 |
| August | 53586505.42 | 0.64 | 20.01 | 01-AUG-00:10 | 0.64 |
| September | 51857908.47 | 0.64 | 20.01 | 01-SEP-00:10 | 0.64 |
| October | 53586505.42 | 0.64 | 20.01 | 01-OCT-00:10 | 0.64 |
| November | 51857908.47 | 0.64 | 20.01 | 01-NOV-00:10 | 0.64 |
| December | 53586505.42 | 0.64 | 20.01 | 01-DEC-00:10 | 0.65 |
| Annual Sum or Average | 0.630938E+09 | 0.64 | |||
| Minimum of Months | 48400714.57 | 0.64 | 20.01 | 0.64 | |
| Maximum of Months | 53586505.42 | 0.64 | 20.01 | 0.65 |
Report: FanReportMonthly
For: SPLIT GNW SUPPLY FAN
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 2646386.71 | 0.11 | 24.89 | 14-JAN-17:10 | 1.09 |
| February | 25018304.78 | 0.37 | 80.29 | 24-FEB-16:10 | 1.07 |
| March | 0.121676E+09 | 0.88 | 160.07 | 28-MAR-16:40 | 1.04 |
| April | 0.276954E+09 | 1.06 | 238.94 | 27-APR-16:03 | 1.01 |
| May | 0.430905E+09 | 1.04 | 291.62 | 05-MAY-16:40 | 0.99 |
| June | 0.478838E+09 | 1.03 | 304.75 | 07-JUN-16:50 | 0.99 |
| July | 0.525250E+09 | 1.02 | 300.66 | 02-JUL-17:10 | 0.98 |
| August | 0.500235E+09 | 1.02 | 277.67 | 07-AUG-17:10 | 0.99 |
| September | 0.423240E+09 | 1.03 | 244.38 | 17-SEP-17:30 | 1.00 |
| October | 0.278305E+09 | 1.06 | 214.69 | 03-OCT-15:10 | 1.02 |
| November | 0.117106E+09 | 0.96 | 125.68 | 04-NOV-16:10 | 1.05 |
| December | 15537137.80 | 0.31 | 62.56 | 01-DEC-15:10 | 1.08 |
| Annual Sum or Average | 0.319571E+10 | 0.82 | |||
| Minimum of Months | 2646386.71 | 0.11 | 24.89 | 0.98 | |
| Maximum of Months | 0.525250E+09 | 1.06 | 304.75 | 1.09 |
Report: FanReportMonthly
For: G NW APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.65 | 20.01 | 01-JAN-00:10 | 0.65 |
| February | 48400714.57 | 0.64 | 20.01 | 01-FEB-00:10 | 0.65 |
| March | 53586505.42 | 0.64 | 20.01 | 01-MAR-00:10 | 0.64 |
| April | 51857908.47 | 0.64 | 20.01 | 01-APR-00:10 | 0.64 |
| May | 53586505.42 | 0.64 | 20.01 | 01-MAY-00:10 | 0.64 |
| June | 51857908.47 | 0.63 | 20.01 | 01-JUN-00:10 | 0.64 |
| July | 53586505.42 | 0.63 | 20.01 | 01-JUL-00:10 | 0.63 |
| August | 53586505.42 | 0.63 | 20.01 | 01-AUG-00:10 | 0.63 |
| September | 51857908.47 | 0.63 | 20.01 | 01-SEP-00:10 | 0.63 |
| October | 53586505.42 | 0.64 | 20.01 | 01-OCT-00:10 | 0.64 |
| November | 51857908.47 | 0.64 | 20.01 | 01-NOV-00:10 | 0.64 |
| December | 53586505.42 | 0.65 | 20.01 | 01-DEC-00:10 | 0.65 |
| Annual Sum or Average | 0.630938E+09 | 0.64 | |||
| Minimum of Months | 48400714.57 | 0.63 | 20.01 | 0.63 | |
| Maximum of Months | 53586505.42 | 0.65 | 20.01 | 0.65 |
Report: FanReportMonthly
For: G NW APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.64 | 20.01 | 01-JAN-00:10 | 0.64 |
| February | 48400714.57 | 0.64 | 20.01 | 01-FEB-00:10 | 0.65 |
| March | 53586505.42 | 0.64 | 20.01 | 01-MAR-00:10 | 0.64 |
| April | 51857908.47 | 0.64 | 20.01 | 01-APR-00:10 | 0.64 |
| May | 53586505.42 | 0.64 | 20.01 | 01-MAY-00:10 | 0.64 |
| June | 51857908.47 | 0.64 | 20.01 | 01-JUN-00:10 | 0.64 |
| July | 53586505.42 | 0.64 | 20.01 | 01-JUL-00:10 | 0.64 |
| August | 53586505.42 | 0.64 | 20.01 | 01-AUG-00:10 | 0.64 |
| September | 51857908.47 | 0.64 | 20.01 | 01-SEP-00:10 | 0.64 |
| October | 53586505.42 | 0.64 | 20.01 | 01-OCT-00:10 | 0.64 |
| November | 51857908.47 | 0.64 | 20.01 | 01-NOV-00:10 | 0.64 |
| December | 53586505.42 | 0.64 | 20.01 | 01-DEC-00:10 | 0.65 |
| Annual Sum or Average | 0.630938E+09 | 0.64 | |||
| Minimum of Months | 48400714.57 | 0.64 | 20.01 | 0.64 | |
| Maximum of Months | 53586505.42 | 0.64 | 20.01 | 0.65 |
Report: FanReportMonthly
For: SPLIT OFFICE SUPPLY FAN
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.134651E+10 | 0.94 | 502.73 | 01-JAN-00:10 | 0.94 |
| February | 0.121620E+10 | 0.94 | 502.73 | 01-FEB-00:10 | 0.94 |
| March | 0.134651E+10 | 0.93 | 502.73 | 01-MAR-00:10 | 0.94 |
| April | 0.130307E+10 | 0.93 | 502.73 | 01-APR-00:10 | 0.94 |
| May | 0.134651E+10 | 0.93 | 502.73 | 01-MAY-00:10 | 0.94 |
| June | 0.130307E+10 | 0.93 | 502.73 | 01-JUN-00:10 | 0.92 |
| July | 0.134651E+10 | 0.92 | 502.73 | 01-JUL-00:10 | 0.92 |
| August | 0.134651E+10 | 0.92 | 502.73 | 01-AUG-00:10 | 0.92 |
| September | 0.130307E+10 | 0.92 | 502.73 | 01-SEP-00:10 | 0.92 |
| October | 0.134651E+10 | 0.93 | 502.73 | 01-OCT-00:10 | 0.93 |
| November | 0.130307E+10 | 0.94 | 502.73 | 01-NOV-00:10 | 0.93 |
| December | 0.134651E+10 | 0.94 | 502.73 | 01-DEC-00:10 | 0.94 |
| Annual Sum or Average | 0.158541E+11 | 0.93 | |||
| Minimum of Months | 0.121620E+10 | 0.92 | 502.73 | 0.92 | |
| Maximum of Months | 0.134651E+10 | 0.94 | 502.73 | 0.94 |
Report: FanReportMonthly
For: SPLIT GNE SUPPLY FAN
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 2279865.33 | 0.10 | 18.96 | 26-JAN-14:00 | 1.10 |
| February | 25491689.41 | 0.39 | 77.86 | 24-FEB-16:10 | 1.07 |
| March | 0.122706E+09 | 0.89 | 139.17 | 29-MAR-16:03 | 1.05 |
| April | 0.277244E+09 | 1.06 | 214.56 | 15-APR-15:10 | 1.02 |
| May | 0.430853E+09 | 1.03 | 267.65 | 05-MAY-16:10 | 1.00 |
| June | 0.472899E+09 | 1.02 | 278.52 | 06-JUN-16:10 | 0.99 |
| July | 0.523100E+09 | 1.02 | 278.09 | 02-JUL-17:20 | 0.99 |
| August | 0.498207E+09 | 1.02 | 263.59 | 07-AUG-17:10 | 0.99 |
| September | 0.420387E+09 | 1.03 | 230.97 | 14-SEP-17:10 | 1.00 |
| October | 0.278748E+09 | 1.06 | 201.66 | 03-OCT-15:10 | 1.02 |
| November | 0.117085E+09 | 0.97 | 111.62 | 09-NOV-13:00 | 1.06 |
| December | 14789194.71 | 0.31 | 54.81 | 01-DEC-14:00 | 1.08 |
| Annual Sum or Average | 0.318379E+10 | 0.83 | |||
| Minimum of Months | 2279865.33 | 0.10 | 18.96 | 0.99 | |
| Maximum of Months | 0.523100E+09 | 1.06 | 278.52 | 1.10 |
Report: FanReportMonthly
For: G NE APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.65 | 20.01 | 01-JAN-00:10 | 0.65 |
| February | 48400714.57 | 0.64 | 20.01 | 01-FEB-00:10 | 0.65 |
| March | 53586505.42 | 0.64 | 20.01 | 01-MAR-00:10 | 0.64 |
| April | 51857908.47 | 0.64 | 20.01 | 01-APR-00:10 | 0.64 |
| May | 53586505.42 | 0.64 | 20.01 | 01-MAY-00:10 | 0.64 |
| June | 51857908.47 | 0.63 | 20.01 | 01-JUN-00:10 | 0.64 |
| July | 53586505.42 | 0.63 | 20.01 | 01-JUL-00:10 | 0.63 |
| August | 53586505.42 | 0.63 | 20.01 | 01-AUG-00:10 | 0.63 |
| September | 51857908.47 | 0.63 | 20.01 | 01-SEP-00:10 | 0.63 |
| October | 53586505.42 | 0.64 | 20.01 | 01-OCT-00:10 | 0.64 |
| November | 51857908.47 | 0.64 | 20.01 | 01-NOV-00:10 | 0.64 |
| December | 53586505.42 | 0.65 | 20.01 | 01-DEC-00:10 | 0.65 |
| Annual Sum or Average | 0.630938E+09 | 0.64 | |||
| Minimum of Months | 48400714.57 | 0.63 | 20.01 | 0.63 | |
| Maximum of Months | 53586505.42 | 0.65 | 20.01 | 0.65 |
Report: FanReportMonthly
For: G NE APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.64 | 20.01 | 01-JAN-00:10 | 0.64 |
| February | 48400714.57 | 0.64 | 20.01 | 01-FEB-00:10 | 0.65 |
| March | 53586505.42 | 0.64 | 20.01 | 01-MAR-00:10 | 0.64 |
| April | 51857908.47 | 0.64 | 20.01 | 01-APR-00:10 | 0.64 |
| May | 53586505.42 | 0.64 | 20.01 | 01-MAY-00:10 | 0.64 |
| June | 51857908.47 | 0.64 | 20.01 | 01-JUN-00:10 | 0.64 |
| July | 53586505.42 | 0.64 | 20.01 | 01-JUL-00:10 | 0.64 |
| August | 53586505.42 | 0.64 | 20.01 | 01-AUG-00:10 | 0.64 |
| September | 51857908.47 | 0.64 | 20.01 | 01-SEP-00:10 | 0.64 |
| October | 53586505.42 | 0.64 | 20.01 | 01-OCT-00:10 | 0.64 |
| November | 51857908.47 | 0.64 | 20.01 | 01-NOV-00:10 | 0.64 |
| December | 53586505.42 | 0.64 | 20.01 | 01-DEC-00:10 | 0.65 |
| Annual Sum or Average | 0.630938E+09 | 0.64 | |||
| Minimum of Months | 48400714.57 | 0.64 | 20.01 | 0.64 | |
| Maximum of Months | 53586505.42 | 0.64 | 20.01 | 0.65 |
Report: FanReportMonthly
For: SPLIT GN1 SUPPLY FAN
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 1145223.53 | 0.07 | 20.20 | 14-JAN-17:05 | 1.09 |
| February | 25999036.08 | 0.47 | 69.93 | 24-FEB-17:10 | 1.07 |
| March | 0.113599E+09 | 0.97 | 116.53 | 29-MAR-16:03 | 1.05 |
| April | 0.235784E+09 | 1.06 | 173.62 | 27-APR-16:10 | 1.03 |
| May | 0.360945E+09 | 1.04 | 214.66 | 05-MAY-17:00 | 1.01 |
| June | 0.401912E+09 | 1.03 | 228.37 | 10-JUN-17:10 | 1.00 |
| July | 0.443955E+09 | 1.02 | 231.59 | 02-JUL-17:20 | 0.99 |
| August | 0.424742E+09 | 1.02 | 217.27 | 07-AUG-17:10 | 1.00 |
| September | 0.359002E+09 | 1.03 | 196.52 | 17-SEP-20:00 | 1.01 |
| October | 0.236233E+09 | 1.06 | 161.03 | 03-OCT-16:10 | 1.03 |
| November | 0.105177E+09 | 1.02 | 94.32 | 04-NOV-16:05 | 1.06 |
| December | 16491155.52 | 0.40 | 47.50 | 01-DEC-15:10 | 1.08 |
| Annual Sum or Average | 0.272498E+10 | 0.85 | |||
| Minimum of Months | 1145223.53 | 0.07 | 20.20 | 0.99 | |
| Maximum of Months | 0.443955E+09 | 1.06 | 231.59 | 1.09 |
Report: FanReportMonthly
For: G N1 APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.65 | 20.01 | 01-JAN-00:10 | 0.65 |
| February | 48400714.57 | 0.64 | 20.01 | 01-FEB-00:10 | 0.65 |
| March | 53586505.42 | 0.64 | 20.01 | 01-MAR-00:10 | 0.64 |
| April | 51857908.47 | 0.64 | 20.01 | 01-APR-00:10 | 0.64 |
| May | 53586505.42 | 0.64 | 20.01 | 01-MAY-00:10 | 0.64 |
| June | 51857908.47 | 0.63 | 20.01 | 01-JUN-00:10 | 0.64 |
| July | 53586505.42 | 0.63 | 20.01 | 01-JUL-00:10 | 0.63 |
| August | 53586505.42 | 0.63 | 20.01 | 01-AUG-00:10 | 0.63 |
| September | 51857908.47 | 0.63 | 20.01 | 01-SEP-00:10 | 0.63 |
| October | 53586505.42 | 0.64 | 20.01 | 01-OCT-00:10 | 0.64 |
| November | 51857908.47 | 0.64 | 20.01 | 01-NOV-00:10 | 0.64 |
| December | 53586505.42 | 0.65 | 20.01 | 01-DEC-00:10 | 0.65 |
| Annual Sum or Average | 0.630938E+09 | 0.64 | |||
| Minimum of Months | 48400714.57 | 0.63 | 20.01 | 0.63 | |
| Maximum of Months | 53586505.42 | 0.65 | 20.01 | 0.65 |
Report: FanReportMonthly
For: G N1 APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.64 | 20.01 | 01-JAN-00:10 | 0.64 |
| February | 48400714.57 | 0.64 | 20.01 | 01-FEB-00:10 | 0.65 |
| March | 53586505.42 | 0.64 | 20.01 | 01-MAR-00:10 | 0.64 |
| April | 51857908.47 | 0.64 | 20.01 | 01-APR-00:10 | 0.64 |
| May | 53586505.42 | 0.64 | 20.01 | 01-MAY-00:10 | 0.64 |
| June | 51857908.47 | 0.64 | 20.01 | 01-JUN-00:10 | 0.64 |
| July | 53586505.42 | 0.64 | 20.01 | 01-JUL-00:10 | 0.64 |
| August | 53586505.42 | 0.64 | 20.01 | 01-AUG-00:10 | 0.64 |
| September | 51857908.47 | 0.64 | 20.01 | 01-SEP-00:10 | 0.64 |
| October | 53586505.42 | 0.64 | 20.01 | 01-OCT-00:10 | 0.64 |
| November | 51857908.47 | 0.64 | 20.01 | 01-NOV-00:10 | 0.64 |
| December | 53586505.42 | 0.64 | 20.01 | 01-DEC-00:10 | 0.65 |
| Annual Sum or Average | 0.630938E+09 | 0.64 | |||
| Minimum of Months | 48400714.57 | 0.64 | 20.01 | 0.64 | |
| Maximum of Months | 53586505.42 | 0.64 | 20.01 | 0.65 |
Report: FanReportMonthly
For: SPLIT GN2 SUPPLY FAN
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 1154573.38 | 0.07 | 20.13 | 14-JAN-17:05 | 1.09 |
| February | 26248849.87 | 0.47 | 70.08 | 24-FEB-17:10 | 1.07 |
| March | 0.113752E+09 | 0.97 | 116.32 | 29-MAR-16:03 | 1.05 |
| April | 0.235856E+09 | 1.06 | 173.29 | 27-APR-16:10 | 1.03 |
| May | 0.360999E+09 | 1.04 | 214.35 | 05-MAY-17:00 | 1.01 |
| June | 0.401743E+09 | 1.03 | 227.83 | 10-JUN-17:10 | 1.00 |
| July | 0.443926E+09 | 1.02 | 231.24 | 02-JUL-17:20 | 0.99 |
| August | 0.424719E+09 | 1.02 | 217.06 | 07-AUG-17:10 | 1.00 |
| September | 0.358935E+09 | 1.03 | 196.30 | 17-SEP-20:00 | 1.01 |
| October | 0.236296E+09 | 1.06 | 160.86 | 03-OCT-16:10 | 1.03 |
| November | 0.105235E+09 | 1.02 | 94.10 | 04-NOV-16:05 | 1.06 |
| December | 16609321.31 | 0.40 | 47.52 | 01-DEC-15:10 | 1.08 |
| Annual Sum or Average | 0.272547E+10 | 0.85 | |||
| Minimum of Months | 1154573.38 | 0.07 | 20.13 | 0.99 | |
| Maximum of Months | 0.443926E+09 | 1.06 | 231.24 | 1.09 |
Report: FanReportMonthly
For: G N2 APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.65 | 20.01 | 01-JAN-00:10 | 0.65 |
| February | 48400714.57 | 0.64 | 20.01 | 01-FEB-00:10 | 0.65 |
| March | 53586505.42 | 0.64 | 20.01 | 01-MAR-00:10 | 0.64 |
| April | 51857908.47 | 0.64 | 20.01 | 01-APR-00:10 | 0.64 |
| May | 53586505.42 | 0.64 | 20.01 | 01-MAY-00:10 | 0.64 |
| June | 51857908.47 | 0.63 | 20.01 | 01-JUN-00:10 | 0.64 |
| July | 53586505.42 | 0.63 | 20.01 | 01-JUL-00:10 | 0.63 |
| August | 53586505.42 | 0.63 | 20.01 | 01-AUG-00:10 | 0.63 |
| September | 51857908.47 | 0.63 | 20.01 | 01-SEP-00:10 | 0.63 |
| October | 53586505.42 | 0.64 | 20.01 | 01-OCT-00:10 | 0.64 |
| November | 51857908.47 | 0.64 | 20.01 | 01-NOV-00:10 | 0.64 |
| December | 53586505.42 | 0.65 | 20.01 | 01-DEC-00:10 | 0.65 |
| Annual Sum or Average | 0.630938E+09 | 0.64 | |||
| Minimum of Months | 48400714.57 | 0.63 | 20.01 | 0.63 | |
| Maximum of Months | 53586505.42 | 0.65 | 20.01 | 0.65 |
Report: FanReportMonthly
For: G N2 APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.64 | 20.01 | 01-JAN-00:10 | 0.64 |
| February | 48400714.57 | 0.64 | 20.01 | 01-FEB-00:10 | 0.65 |
| March | 53586505.42 | 0.64 | 20.01 | 01-MAR-00:10 | 0.64 |
| April | 51857908.47 | 0.64 | 20.01 | 01-APR-00:10 | 0.64 |
| May | 53586505.42 | 0.64 | 20.01 | 01-MAY-00:10 | 0.64 |
| June | 51857908.47 | 0.64 | 20.01 | 01-JUN-00:10 | 0.64 |
| July | 53586505.42 | 0.64 | 20.01 | 01-JUL-00:10 | 0.64 |
| August | 53586505.42 | 0.64 | 20.01 | 01-AUG-00:10 | 0.64 |
| September | 51857908.47 | 0.64 | 20.01 | 01-SEP-00:10 | 0.64 |
| October | 53586505.42 | 0.64 | 20.01 | 01-OCT-00:10 | 0.64 |
| November | 51857908.47 | 0.64 | 20.01 | 01-NOV-00:10 | 0.64 |
| December | 53586505.42 | 0.64 | 20.01 | 01-DEC-00:10 | 0.65 |
| Annual Sum or Average | 0.630938E+09 | 0.64 | |||
| Minimum of Months | 48400714.57 | 0.64 | 20.01 | 0.64 | |
| Maximum of Months | 53586505.42 | 0.64 | 20.01 | 0.65 |
Report: FanReportMonthly
For: SPLIT GS1 SUPPLY FAN
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 40554861.13 | 0.58 | 88.69 | 12-JAN-14:50 | 1.07 |
| February | 78157724.17 | 0.78 | 116.17 | 20-FEB-14:40 | 1.05 |
| March | 0.163770E+09 | 1.04 | 149.91 | 12-MAR-16:10 | 1.03 |
| April | 0.265539E+09 | 1.05 | 192.07 | 15-APR-15:10 | 1.02 |
| May | 0.364738E+09 | 1.04 | 218.75 | 05-MAY-16:10 | 1.01 |
| June | 0.397501E+09 | 1.03 | 226.93 | 10-JUN-17:10 | 1.00 |
| July | 0.441046E+09 | 1.02 | 231.12 | 02-JUL-17:10 | 0.99 |
| August | 0.427419E+09 | 1.02 | 222.63 | 27-AUG-16:02 | 1.00 |
| September | 0.383064E+09 | 1.03 | 216.02 | 24-SEP-16:10 | 1.00 |
| October | 0.301347E+09 | 1.05 | 201.26 | 03-OCT-14:10 | 1.01 |
| November | 0.191732E+09 | 1.07 | 155.86 | 04-NOV-14:10 | 1.03 |
| December | 84499690.49 | 0.89 | 116.81 | 02-DEC-14:00 | 1.05 |
| Annual Sum or Average | 0.313937E+10 | 0.97 | |||
| Minimum of Months | 40554861.13 | 0.58 | 88.69 | 0.99 | |
| Maximum of Months | 0.441046E+09 | 1.07 | 231.12 | 1.07 |
Report: FanReportMonthly
For: G S1 APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.65 | 20.01 | 01-JAN-00:10 | 0.65 |
| February | 48400714.57 | 0.64 | 20.01 | 01-FEB-00:10 | 0.65 |
| March | 53586505.42 | 0.64 | 20.01 | 01-MAR-00:10 | 0.64 |
| April | 51857908.47 | 0.64 | 20.01 | 01-APR-00:10 | 0.64 |
| May | 53586505.42 | 0.64 | 20.01 | 01-MAY-00:10 | 0.64 |
| June | 51857908.47 | 0.63 | 20.01 | 01-JUN-00:10 | 0.64 |
| July | 53586505.42 | 0.63 | 20.01 | 01-JUL-00:10 | 0.63 |
| August | 53586505.42 | 0.63 | 20.01 | 01-AUG-00:10 | 0.63 |
| September | 51857908.47 | 0.63 | 20.01 | 01-SEP-00:10 | 0.63 |
| October | 53586505.42 | 0.64 | 20.01 | 01-OCT-00:10 | 0.64 |
| November | 51857908.47 | 0.64 | 20.01 | 01-NOV-00:10 | 0.64 |
| December | 53586505.42 | 0.65 | 20.01 | 01-DEC-00:10 | 0.65 |
| Annual Sum or Average | 0.630938E+09 | 0.64 | |||
| Minimum of Months | 48400714.57 | 0.63 | 20.01 | 0.63 | |
| Maximum of Months | 53586505.42 | 0.65 | 20.01 | 0.65 |
Report: FanReportMonthly
For: G S1 APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.64 | 20.01 | 01-JAN-00:10 | 0.64 |
| February | 48400714.57 | 0.64 | 20.01 | 01-FEB-00:10 | 0.65 |
| March | 53586505.42 | 0.64 | 20.01 | 01-MAR-00:10 | 0.64 |
| April | 51857908.47 | 0.64 | 20.01 | 01-APR-00:10 | 0.64 |
| May | 53586505.42 | 0.64 | 20.01 | 01-MAY-00:10 | 0.64 |
| June | 51857908.47 | 0.64 | 20.01 | 01-JUN-00:10 | 0.64 |
| July | 53586505.42 | 0.64 | 20.01 | 01-JUL-00:10 | 0.64 |
| August | 53586505.42 | 0.64 | 20.01 | 01-AUG-00:10 | 0.64 |
| September | 51857908.47 | 0.64 | 20.01 | 01-SEP-00:10 | 0.64 |
| October | 53586505.42 | 0.64 | 20.01 | 01-OCT-00:10 | 0.64 |
| November | 51857908.47 | 0.64 | 20.01 | 01-NOV-00:10 | 0.64 |
| December | 53586505.42 | 0.64 | 20.01 | 01-DEC-00:10 | 0.65 |
| Annual Sum or Average | 0.630938E+09 | 0.64 | |||
| Minimum of Months | 48400714.57 | 0.64 | 20.01 | 0.64 | |
| Maximum of Months | 53586505.42 | 0.64 | 20.01 | 0.65 |
Report: FanReportMonthly
For: SPLIT GS2 SUPPLY FAN
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 44829374.55 | 0.60 | 91.90 | 12-JAN-14:40 | 1.06 |
| February | 85877821.08 | 0.83 | 123.09 | 20-FEB-14:50 | 1.05 |
| March | 0.178464E+09 | 1.05 | 160.14 | 12-MAR-16:10 | 1.03 |
| April | 0.287844E+09 | 1.05 | 202.79 | 15-APR-15:10 | 1.01 |
| May | 0.390985E+09 | 1.03 | 225.56 | 05-MAY-16:10 | 1.01 |
| June | 0.422932E+09 | 1.02 | 238.32 | 10-JUN-17:10 | 0.99 |
| July | 0.468857E+09 | 1.02 | 243.82 | 02-JUL-17:10 | 0.99 |
| August | 0.454049E+09 | 1.02 | 235.25 | 27-AUG-16:02 | 0.99 |
| September | 0.408925E+09 | 1.03 | 228.81 | 24-SEP-16:10 | 1.00 |
| October | 0.325779E+09 | 1.05 | 208.87 | 03-OCT-14:10 | 1.01 |
| November | 0.208829E+09 | 1.07 | 164.24 | 04-NOV-14:10 | 1.03 |
| December | 92613194.79 | 0.94 | 122.24 | 02-DEC-14:00 | 1.05 |
| Annual Sum or Average | 0.336998E+10 | 0.98 | |||
| Minimum of Months | 44829374.55 | 0.60 | 91.90 | 0.99 | |
| Maximum of Months | 0.468857E+09 | 1.07 | 243.82 | 1.06 |
Report: FanReportMonthly
For: G S2 APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.65 | 20.01 | 01-JAN-00:10 | 0.65 |
| February | 48400714.57 | 0.64 | 20.01 | 01-FEB-00:10 | 0.65 |
| March | 53586505.42 | 0.64 | 20.01 | 01-MAR-00:10 | 0.64 |
| April | 51857908.47 | 0.64 | 20.01 | 01-APR-00:10 | 0.64 |
| May | 53586505.42 | 0.64 | 20.01 | 01-MAY-00:10 | 0.64 |
| June | 51857908.47 | 0.63 | 20.01 | 01-JUN-00:10 | 0.64 |
| July | 53586505.42 | 0.63 | 20.01 | 01-JUL-00:10 | 0.63 |
| August | 53586505.42 | 0.63 | 20.01 | 01-AUG-00:10 | 0.63 |
| September | 51857908.47 | 0.63 | 20.01 | 01-SEP-00:10 | 0.63 |
| October | 53586505.42 | 0.64 | 20.01 | 01-OCT-00:10 | 0.64 |
| November | 51857908.47 | 0.64 | 20.01 | 01-NOV-00:10 | 0.64 |
| December | 53586505.42 | 0.65 | 20.01 | 01-DEC-00:10 | 0.65 |
| Annual Sum or Average | 0.630938E+09 | 0.64 | |||
| Minimum of Months | 48400714.57 | 0.63 | 20.01 | 0.63 | |
| Maximum of Months | 53586505.42 | 0.65 | 20.01 | 0.65 |
Report: FanReportMonthly
For: G S2 APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.64 | 20.01 | 01-JAN-00:10 | 0.64 |
| February | 48400714.57 | 0.64 | 20.01 | 01-FEB-00:10 | 0.65 |
| March | 53586505.42 | 0.64 | 20.01 | 01-MAR-00:10 | 0.64 |
| April | 51857908.47 | 0.64 | 20.01 | 01-APR-00:10 | 0.64 |
| May | 53586505.42 | 0.64 | 20.01 | 01-MAY-00:10 | 0.64 |
| June | 51857908.47 | 0.64 | 20.01 | 01-JUN-00:10 | 0.64 |
| July | 53586505.42 | 0.64 | 20.01 | 01-JUL-00:10 | 0.64 |
| August | 53586505.42 | 0.64 | 20.01 | 01-AUG-00:10 | 0.64 |
| September | 51857908.47 | 0.64 | 20.01 | 01-SEP-00:10 | 0.64 |
| October | 53586505.42 | 0.64 | 20.01 | 01-OCT-00:10 | 0.64 |
| November | 51857908.47 | 0.64 | 20.01 | 01-NOV-00:10 | 0.64 |
| December | 53586505.42 | 0.64 | 20.01 | 01-DEC-00:10 | 0.65 |
| Annual Sum or Average | 0.630938E+09 | 0.64 | |||
| Minimum of Months | 48400714.57 | 0.64 | 20.01 | 0.64 | |
| Maximum of Months | 53586505.42 | 0.64 | 20.01 | 0.65 |
Report: FanReportMonthly
For: SPLIT MSW SUPPLY FAN
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 89074816.89 | 0.45 | 243.51 | 12-JAN-15:20 | 1.06 |
| February | 0.203928E+09 | 0.71 | 346.03 | 20-FEB-16:10 | 1.05 |
| March | 0.459841E+09 | 1.03 | 466.78 | 28-MAR-16:07 | 1.02 |
| April | 0.739138E+09 | 1.05 | 612.92 | 27-APR-16:10 | 1.00 |
| May | 0.969812E+09 | 1.04 | 682.34 | 05-MAY-16:10 | 0.99 |
| June | 0.996339E+09 | 1.03 | 668.16 | 06-JUN-16:10 | 0.99 |
| July | 0.104287E+10 | 1.03 | 633.36 | 02-JUL-16:40 | 0.99 |
| August | 0.960449E+09 | 1.03 | 571.84 | 07-AUG-16:01 | 1.00 |
| September | 0.837918E+09 | 1.04 | 565.76 | 22-SEP-15:10 | 1.00 |
| October | 0.639857E+09 | 1.06 | 538.22 | 03-OCT-15:10 | 1.01 |
| November | 0.382415E+09 | 0.99 | 410.97 | 04-NOV-15:10 | 1.03 |
| December | 0.148396E+09 | 0.58 | 288.67 | 02-DEC-14:30 | 1.06 |
| Annual Sum or Average | 0.747003E+10 | 0.92 | |||
| Minimum of Months | 89074816.89 | 0.45 | 243.51 | 0.99 | |
| Maximum of Months | 0.104287E+10 | 1.06 | 682.34 | 1.06 |
Report: FanReportMonthly
For: M SW APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.107173E+09 | 0.65 | 40.01 | 01-JAN-00:10 | 0.65 |
| February | 96801429.15 | 0.64 | 40.01 | 01-FEB-00:10 | 0.65 |
| March | 0.107173E+09 | 0.64 | 40.01 | 01-MAR-00:10 | 0.64 |
| April | 0.103716E+09 | 0.64 | 40.01 | 01-APR-00:10 | 0.64 |
| May | 0.107173E+09 | 0.64 | 40.01 | 01-MAY-00:10 | 0.64 |
| June | 0.103716E+09 | 0.63 | 40.01 | 01-JUN-00:10 | 0.64 |
| July | 0.107173E+09 | 0.63 | 40.01 | 01-JUL-00:10 | 0.63 |
| August | 0.107173E+09 | 0.63 | 40.01 | 01-AUG-00:10 | 0.63 |
| September | 0.103716E+09 | 0.63 | 40.01 | 01-SEP-00:10 | 0.63 |
| October | 0.107173E+09 | 0.64 | 40.01 | 01-OCT-00:10 | 0.64 |
| November | 0.103716E+09 | 0.64 | 40.01 | 01-NOV-00:10 | 0.64 |
| December | 0.107173E+09 | 0.65 | 40.01 | 01-DEC-00:10 | 0.65 |
| Annual Sum or Average | 0.126188E+10 | 0.64 | |||
| Minimum of Months | 96801429.15 | 0.63 | 40.01 | 0.63 | |
| Maximum of Months | 0.107173E+09 | 0.65 | 40.01 | 0.65 |
Report: FanReportMonthly
For: M SW APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.107173E+09 | 0.64 | 40.01 | 01-JAN-00:10 | 0.64 |
| February | 96801429.15 | 0.64 | 40.01 | 01-FEB-00:10 | 0.65 |
| March | 0.107173E+09 | 0.64 | 40.01 | 01-MAR-00:10 | 0.64 |
| April | 0.103716E+09 | 0.64 | 40.01 | 01-APR-00:10 | 0.64 |
| May | 0.107173E+09 | 0.64 | 40.01 | 01-MAY-00:10 | 0.64 |
| June | 0.103716E+09 | 0.64 | 40.01 | 01-JUN-00:10 | 0.64 |
| July | 0.107173E+09 | 0.64 | 40.01 | 01-JUL-00:10 | 0.64 |
| August | 0.107173E+09 | 0.64 | 40.01 | 01-AUG-00:10 | 0.64 |
| September | 0.103716E+09 | 0.64 | 40.01 | 01-SEP-00:10 | 0.64 |
| October | 0.107173E+09 | 0.64 | 40.01 | 01-OCT-00:10 | 0.64 |
| November | 0.103716E+09 | 0.64 | 40.01 | 01-NOV-00:10 | 0.64 |
| December | 0.107173E+09 | 0.64 | 40.01 | 01-DEC-00:10 | 0.65 |
| Annual Sum or Average | 0.126188E+10 | 0.64 | |||
| Minimum of Months | 96801429.15 | 0.64 | 40.01 | 0.64 | |
| Maximum of Months | 0.107173E+09 | 0.64 | 40.01 | 0.65 |
Report: FanReportMonthly
For: SPLIT MNW SUPPLY FAN
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 6530890.57 | 0.11 | 81.62 | 14-JAN-17:10 | 1.09 |
| February | 91272456.40 | 0.53 | 216.14 | 22-FEB-17:10 | 1.07 |
| March | 0.355144E+09 | 1.00 | 398.85 | 28-MAR-16:30 | 1.04 |
| April | 0.675814E+09 | 1.06 | 579.66 | 27-APR-16:10 | 1.01 |
| May | 0.960022E+09 | 1.04 | 670.21 | 05-MAY-16:10 | 0.99 |
| June | 0.100253E+10 | 1.03 | 671.30 | 06-JUN-16:08 | 0.99 |
| July | 0.104529E+10 | 1.03 | 627.58 | 02-JUL-16:50 | 0.99 |
| August | 0.950830E+09 | 1.03 | 565.78 | 07-AUG-16:17 | 1.00 |
| September | 0.782613E+09 | 1.04 | 496.79 | 22-SEP-16:01 | 1.01 |
| October | 0.498730E+09 | 1.05 | 443.84 | 03-OCT-15:10 | 1.02 |
| November | 0.203089E+09 | 0.84 | 258.22 | 04-NOV-16:10 | 1.06 |
| December | 26027990.88 | 0.26 | 121.75 | 28-DEC-16:10 | 1.08 |
| Annual Sum or Average | 0.659790E+10 | 0.84 | |||
| Minimum of Months | 6530890.57 | 0.11 | 81.62 | 0.99 | |
| Maximum of Months | 0.104529E+10 | 1.06 | 671.30 | 1.09 |
Report: FanReportMonthly
For: M NW APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.107173E+09 | 0.65 | 40.01 | 01-JAN-00:10 | 0.65 |
| February | 96801429.15 | 0.64 | 40.01 | 01-FEB-00:10 | 0.65 |
| March | 0.107173E+09 | 0.64 | 40.01 | 01-MAR-00:10 | 0.64 |
| April | 0.103716E+09 | 0.64 | 40.01 | 01-APR-00:10 | 0.64 |
| May | 0.107173E+09 | 0.64 | 40.01 | 01-MAY-00:10 | 0.64 |
| June | 0.103716E+09 | 0.63 | 40.01 | 01-JUN-00:10 | 0.64 |
| July | 0.107173E+09 | 0.63 | 40.01 | 01-JUL-00:10 | 0.63 |
| August | 0.107173E+09 | 0.63 | 40.01 | 01-AUG-00:10 | 0.63 |
| September | 0.103716E+09 | 0.63 | 40.01 | 01-SEP-00:10 | 0.63 |
| October | 0.107173E+09 | 0.64 | 40.01 | 01-OCT-00:10 | 0.64 |
| November | 0.103716E+09 | 0.64 | 40.01 | 01-NOV-00:10 | 0.64 |
| December | 0.107173E+09 | 0.65 | 40.01 | 01-DEC-00:10 | 0.65 |
| Annual Sum or Average | 0.126188E+10 | 0.64 | |||
| Minimum of Months | 96801429.15 | 0.63 | 40.01 | 0.63 | |
| Maximum of Months | 0.107173E+09 | 0.65 | 40.01 | 0.65 |
Report: FanReportMonthly
For: M NW APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.107173E+09 | 0.64 | 40.01 | 01-JAN-00:10 | 0.64 |
| February | 96801429.15 | 0.64 | 40.01 | 01-FEB-00:10 | 0.65 |
| March | 0.107173E+09 | 0.64 | 40.01 | 01-MAR-00:10 | 0.64 |
| April | 0.103716E+09 | 0.64 | 40.01 | 01-APR-00:10 | 0.64 |
| May | 0.107173E+09 | 0.64 | 40.01 | 01-MAY-00:10 | 0.64 |
| June | 0.103716E+09 | 0.64 | 40.01 | 01-JUN-00:10 | 0.64 |
| July | 0.107173E+09 | 0.64 | 40.01 | 01-JUL-00:10 | 0.64 |
| August | 0.107173E+09 | 0.64 | 40.01 | 01-AUG-00:10 | 0.64 |
| September | 0.103716E+09 | 0.64 | 40.01 | 01-SEP-00:10 | 0.64 |
| October | 0.107173E+09 | 0.64 | 40.01 | 01-OCT-00:10 | 0.64 |
| November | 0.103716E+09 | 0.64 | 40.01 | 01-NOV-00:10 | 0.64 |
| December | 0.107173E+09 | 0.64 | 40.01 | 01-DEC-00:10 | 0.65 |
| Annual Sum or Average | 0.126188E+10 | 0.64 | |||
| Minimum of Months | 96801429.15 | 0.64 | 40.01 | 0.64 | |
| Maximum of Months | 0.107173E+09 | 0.64 | 40.01 | 0.65 |
Report: FanReportMonthly
For: SPLIT MSE SUPPLY FAN
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 89152060.34 | 0.48 | 226.86 | 12-JAN-14:30 | 1.06 |
| February | 0.208701E+09 | 0.74 | 321.09 | 20-FEB-14:30 | 1.05 |
| March | 0.462188E+09 | 1.04 | 409.18 | 12-MAR-16:10 | 1.03 |
| April | 0.738702E+09 | 1.05 | 572.41 | 15-APR-14:00 | 1.00 |
| May | 0.969087E+09 | 1.03 | 617.96 | 05-MAY-15:10 | 1.00 |
| June | 0.983170E+09 | 1.03 | 612.53 | 06-JUN-15:10 | 0.99 |
| July | 0.103836E+10 | 1.03 | 592.43 | 01-JUL-16:01 | 0.99 |
| August | 0.956420E+09 | 1.03 | 535.11 | 07-AUG-16:10 | 1.00 |
| September | 0.831939E+09 | 1.04 | 529.74 | 22-SEP-15:10 | 1.00 |
| October | 0.640440E+09 | 1.05 | 509.71 | 03-OCT-14:10 | 1.01 |
| November | 0.382103E+09 | 1.00 | 381.21 | 04-NOV-13:40 | 1.04 |
| December | 0.149080E+09 | 0.61 | 270.50 | 02-DEC-14:00 | 1.06 |
| Annual Sum or Average | 0.744934E+10 | 0.93 | |||
| Minimum of Months | 89152060.34 | 0.48 | 226.86 | 0.99 | |
| Maximum of Months | 0.103836E+10 | 1.05 | 617.96 | 1.06 |
Report: FanReportMonthly
For: M SE APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.107173E+09 | 0.65 | 40.01 | 01-JAN-00:10 | 0.65 |
| February | 96801429.15 | 0.64 | 40.01 | 01-FEB-00:10 | 0.65 |
| March | 0.107173E+09 | 0.64 | 40.01 | 01-MAR-00:10 | 0.64 |
| April | 0.103716E+09 | 0.64 | 40.01 | 01-APR-00:10 | 0.64 |
| May | 0.107173E+09 | 0.64 | 40.01 | 01-MAY-00:10 | 0.64 |
| June | 0.103716E+09 | 0.63 | 40.01 | 01-JUN-00:10 | 0.64 |
| July | 0.107173E+09 | 0.63 | 40.01 | 01-JUL-00:10 | 0.63 |
| August | 0.107173E+09 | 0.63 | 40.01 | 01-AUG-00:10 | 0.63 |
| September | 0.103716E+09 | 0.63 | 40.01 | 01-SEP-00:10 | 0.63 |
| October | 0.107173E+09 | 0.64 | 40.01 | 01-OCT-00:10 | 0.64 |
| November | 0.103716E+09 | 0.64 | 40.01 | 01-NOV-00:10 | 0.64 |
| December | 0.107173E+09 | 0.65 | 40.01 | 01-DEC-00:10 | 0.65 |
| Annual Sum or Average | 0.126188E+10 | 0.64 | |||
| Minimum of Months | 96801429.15 | 0.63 | 40.01 | 0.63 | |
| Maximum of Months | 0.107173E+09 | 0.65 | 40.01 | 0.65 |
Report: FanReportMonthly
For: M SE APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.107173E+09 | 0.64 | 40.01 | 01-JAN-00:10 | 0.64 |
| February | 96801429.15 | 0.64 | 40.01 | 01-FEB-00:10 | 0.65 |
| March | 0.107173E+09 | 0.64 | 40.01 | 01-MAR-00:10 | 0.64 |
| April | 0.103716E+09 | 0.64 | 40.01 | 01-APR-00:10 | 0.64 |
| May | 0.107173E+09 | 0.64 | 40.01 | 01-MAY-00:10 | 0.64 |
| June | 0.103716E+09 | 0.64 | 40.01 | 01-JUN-00:10 | 0.64 |
| July | 0.107173E+09 | 0.64 | 40.01 | 01-JUL-00:10 | 0.64 |
| August | 0.107173E+09 | 0.64 | 40.01 | 01-AUG-00:10 | 0.64 |
| September | 0.103716E+09 | 0.64 | 40.01 | 01-SEP-00:10 | 0.64 |
| October | 0.107173E+09 | 0.64 | 40.01 | 01-OCT-00:10 | 0.64 |
| November | 0.103716E+09 | 0.64 | 40.01 | 01-NOV-00:10 | 0.64 |
| December | 0.107173E+09 | 0.64 | 40.01 | 01-DEC-00:10 | 0.65 |
| Annual Sum or Average | 0.126188E+10 | 0.64 | |||
| Minimum of Months | 96801429.15 | 0.64 | 40.01 | 0.64 | |
| Maximum of Months | 0.107173E+09 | 0.64 | 40.01 | 0.65 |
Report: FanReportMonthly
For: SPLIT MNE SUPPLY FAN
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 5567881.54 | 0.10 | 62.89 | 14-JAN-17:10 | 1.09 |
| February | 93326538.13 | 0.56 | 197.23 | 24-FEB-16:10 | 1.07 |
| March | 0.357952E+09 | 1.01 | 342.55 | 29-MAR-16:03 | 1.04 |
| April | 0.676023E+09 | 1.05 | 516.69 | 15-APR-15:10 | 1.01 |
| May | 0.959576E+09 | 1.04 | 605.46 | 05-MAY-16:10 | 1.00 |
| June | 0.989520E+09 | 1.03 | 608.86 | 06-JUN-15:10 | 0.99 |
| July | 0.104102E+10 | 1.03 | 582.30 | 01-JUL-16:01 | 0.99 |
| August | 0.947117E+09 | 1.03 | 528.89 | 07-AUG-16:10 | 1.00 |
| September | 0.777226E+09 | 1.04 | 457.10 | 22-SEP-15:10 | 1.02 |
| October | 0.500399E+09 | 1.05 | 407.46 | 03-OCT-15:10 | 1.03 |
| November | 0.202801E+09 | 0.85 | 222.84 | 09-NOV-13:00 | 1.06 |
| December | 24181483.46 | 0.26 | 99.78 | 01-DEC-14:00 | 1.09 |
| Annual Sum or Average | 0.657471E+10 | 0.84 | |||
| Minimum of Months | 5567881.54 | 0.10 | 62.89 | 0.99 | |
| Maximum of Months | 0.104102E+10 | 1.05 | 608.86 | 1.09 |
Report: FanReportMonthly
For: M NE APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.107173E+09 | 0.65 | 40.01 | 01-JAN-00:10 | 0.65 |
| February | 96801429.15 | 0.64 | 40.01 | 01-FEB-00:10 | 0.65 |
| March | 0.107173E+09 | 0.64 | 40.01 | 01-MAR-00:10 | 0.64 |
| April | 0.103716E+09 | 0.64 | 40.01 | 01-APR-00:10 | 0.64 |
| May | 0.107173E+09 | 0.64 | 40.01 | 01-MAY-00:10 | 0.64 |
| June | 0.103716E+09 | 0.63 | 40.01 | 01-JUN-00:10 | 0.64 |
| July | 0.107173E+09 | 0.63 | 40.01 | 01-JUL-00:10 | 0.63 |
| August | 0.107173E+09 | 0.63 | 40.01 | 01-AUG-00:10 | 0.63 |
| September | 0.103716E+09 | 0.63 | 40.01 | 01-SEP-00:10 | 0.63 |
| October | 0.107173E+09 | 0.64 | 40.01 | 01-OCT-00:10 | 0.64 |
| November | 0.103716E+09 | 0.64 | 40.01 | 01-NOV-00:10 | 0.64 |
| December | 0.107173E+09 | 0.65 | 40.01 | 01-DEC-00:10 | 0.65 |
| Annual Sum or Average | 0.126188E+10 | 0.64 | |||
| Minimum of Months | 96801429.15 | 0.63 | 40.01 | 0.63 | |
| Maximum of Months | 0.107173E+09 | 0.65 | 40.01 | 0.65 |
Report: FanReportMonthly
For: M NE APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.107173E+09 | 0.64 | 40.01 | 01-JAN-00:10 | 0.64 |
| February | 96801429.15 | 0.64 | 40.01 | 01-FEB-00:10 | 0.65 |
| March | 0.107173E+09 | 0.64 | 40.01 | 01-MAR-00:10 | 0.64 |
| April | 0.103716E+09 | 0.64 | 40.01 | 01-APR-00:10 | 0.64 |
| May | 0.107173E+09 | 0.64 | 40.01 | 01-MAY-00:10 | 0.64 |
| June | 0.103716E+09 | 0.64 | 40.01 | 01-JUN-00:10 | 0.64 |
| July | 0.107173E+09 | 0.64 | 40.01 | 01-JUL-00:10 | 0.64 |
| August | 0.107173E+09 | 0.64 | 40.01 | 01-AUG-00:10 | 0.64 |
| September | 0.103716E+09 | 0.64 | 40.01 | 01-SEP-00:10 | 0.64 |
| October | 0.107173E+09 | 0.64 | 40.01 | 01-OCT-00:10 | 0.64 |
| November | 0.103716E+09 | 0.64 | 40.01 | 01-NOV-00:10 | 0.64 |
| December | 0.107173E+09 | 0.64 | 40.01 | 01-DEC-00:10 | 0.65 |
| Annual Sum or Average | 0.126188E+10 | 0.64 | |||
| Minimum of Months | 96801429.15 | 0.64 | 40.01 | 0.64 | |
| Maximum of Months | 0.107173E+09 | 0.64 | 40.01 | 0.65 |
Report: FanReportMonthly
For: SPLIT MN1 SUPPLY FAN
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 8515680.55 | 0.16 | 73.47 | 14-JAN-17:10 | 1.09 |
| February | 92031036.46 | 0.65 | 168.89 | 24-FEB-17:10 | 1.07 |
| March | 0.306646E+09 | 1.04 | 274.02 | 29-MAR-16:03 | 1.05 |
| April | 0.542912E+09 | 1.06 | 396.05 | 27-APR-16:06 | 1.02 |
| May | 0.770761E+09 | 1.04 | 464.71 | 05-MAY-16:10 | 1.01 |
| June | 0.817752E+09 | 1.03 | 469.58 | 06-JUN-16:10 | 1.01 |
| July | 0.871848E+09 | 1.03 | 472.02 | 01-JUL-16:13 | 1.00 |
| August | 0.806950E+09 | 1.03 | 425.48 | 07-AUG-17:10 | 1.01 |
| September | 0.667812E+09 | 1.04 | 381.44 | 14-SEP-17:10 | 1.02 |
| October | 0.430296E+09 | 1.06 | 318.11 | 03-OCT-15:10 | 1.03 |
| November | 0.191910E+09 | 0.97 | 187.51 | 04-NOV-16:10 | 1.06 |
| December | 33459552.19 | 0.39 | 96.67 | 28-DEC-17:10 | 1.08 |
| Annual Sum or Average | 0.554089E+10 | 0.88 | |||
| Minimum of Months | 8515680.55 | 0.16 | 73.47 | 1.00 | |
| Maximum of Months | 0.871848E+09 | 1.06 | 472.02 | 1.09 |
Report: FanReportMonthly
For: M N1 APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.107173E+09 | 0.65 | 40.01 | 01-JAN-00:10 | 0.65 |
| February | 96801429.15 | 0.64 | 40.01 | 01-FEB-00:10 | 0.65 |
| March | 0.107173E+09 | 0.64 | 40.01 | 01-MAR-00:10 | 0.64 |
| April | 0.103716E+09 | 0.64 | 40.01 | 01-APR-00:10 | 0.64 |
| May | 0.107173E+09 | 0.64 | 40.01 | 01-MAY-00:10 | 0.64 |
| June | 0.103716E+09 | 0.63 | 40.01 | 01-JUN-00:10 | 0.64 |
| July | 0.107173E+09 | 0.63 | 40.01 | 01-JUL-00:10 | 0.63 |
| August | 0.107173E+09 | 0.63 | 40.01 | 01-AUG-00:10 | 0.63 |
| September | 0.103716E+09 | 0.63 | 40.01 | 01-SEP-00:10 | 0.63 |
| October | 0.107173E+09 | 0.64 | 40.01 | 01-OCT-00:10 | 0.64 |
| November | 0.103716E+09 | 0.64 | 40.01 | 01-NOV-00:10 | 0.64 |
| December | 0.107173E+09 | 0.65 | 40.01 | 01-DEC-00:10 | 0.65 |
| Annual Sum or Average | 0.126188E+10 | 0.64 | |||
| Minimum of Months | 96801429.15 | 0.63 | 40.01 | 0.63 | |
| Maximum of Months | 0.107173E+09 | 0.65 | 40.01 | 0.65 |
Report: FanReportMonthly
For: M N1 APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.107173E+09 | 0.64 | 40.01 | 01-JAN-00:10 | 0.64 |
| February | 96801429.15 | 0.64 | 40.01 | 01-FEB-00:10 | 0.65 |
| March | 0.107173E+09 | 0.64 | 40.01 | 01-MAR-00:10 | 0.64 |
| April | 0.103716E+09 | 0.64 | 40.01 | 01-APR-00:10 | 0.64 |
| May | 0.107173E+09 | 0.64 | 40.01 | 01-MAY-00:10 | 0.64 |
| June | 0.103716E+09 | 0.64 | 40.01 | 01-JUN-00:10 | 0.64 |
| July | 0.107173E+09 | 0.64 | 40.01 | 01-JUL-00:10 | 0.64 |
| August | 0.107173E+09 | 0.64 | 40.01 | 01-AUG-00:10 | 0.64 |
| September | 0.103716E+09 | 0.64 | 40.01 | 01-SEP-00:10 | 0.64 |
| October | 0.107173E+09 | 0.64 | 40.01 | 01-OCT-00:10 | 0.64 |
| November | 0.103716E+09 | 0.64 | 40.01 | 01-NOV-00:10 | 0.64 |
| December | 0.107173E+09 | 0.64 | 40.01 | 01-DEC-00:10 | 0.65 |
| Annual Sum or Average | 0.126188E+10 | 0.64 | |||
| Minimum of Months | 96801429.15 | 0.64 | 40.01 | 0.64 | |
| Maximum of Months | 0.107173E+09 | 0.64 | 40.01 | 0.65 |
Report: FanReportMonthly
For: SPLIT MN2 SUPPLY FAN
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 8587856.32 | 0.16 | 73.39 | 14-JAN-17:10 | 1.09 |
| February | 92672922.91 | 0.66 | 169.07 | 24-FEB-17:10 | 1.07 |
| March | 0.306906E+09 | 1.04 | 273.48 | 29-MAR-16:03 | 1.05 |
| April | 0.543039E+09 | 1.06 | 395.19 | 27-APR-16:06 | 1.02 |
| May | 0.770859E+09 | 1.04 | 464.16 | 05-MAY-16:10 | 1.01 |
| June | 0.817434E+09 | 1.03 | 468.91 | 06-JUN-16:10 | 1.01 |
| July | 0.871795E+09 | 1.03 | 471.71 | 01-JUL-16:13 | 1.00 |
| August | 0.806910E+09 | 1.03 | 424.96 | 07-AUG-17:10 | 1.01 |
| September | 0.667697E+09 | 1.04 | 381.09 | 14-SEP-17:10 | 1.02 |
| October | 0.430438E+09 | 1.06 | 317.97 | 03-OCT-15:10 | 1.03 |
| November | 0.192104E+09 | 0.97 | 187.05 | 04-NOV-16:10 | 1.06 |
| December | 33799838.69 | 0.39 | 96.56 | 28-DEC-17:10 | 1.08 |
| Annual Sum or Average | 0.554224E+10 | 0.88 | |||
| Minimum of Months | 8587856.32 | 0.16 | 73.39 | 1.00 | |
| Maximum of Months | 0.871795E+09 | 1.06 | 471.71 | 1.09 |
Report: FanReportMonthly
For: M N2 APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.107173E+09 | 0.65 | 40.01 | 01-JAN-00:10 | 0.65 |
| February | 96801429.15 | 0.64 | 40.01 | 01-FEB-00:10 | 0.65 |
| March | 0.107173E+09 | 0.64 | 40.01 | 01-MAR-00:10 | 0.64 |
| April | 0.103716E+09 | 0.64 | 40.01 | 01-APR-00:10 | 0.64 |
| May | 0.107173E+09 | 0.64 | 40.01 | 01-MAY-00:10 | 0.64 |
| June | 0.103716E+09 | 0.63 | 40.01 | 01-JUN-00:10 | 0.64 |
| July | 0.107173E+09 | 0.63 | 40.01 | 01-JUL-00:10 | 0.63 |
| August | 0.107173E+09 | 0.63 | 40.01 | 01-AUG-00:10 | 0.63 |
| September | 0.103716E+09 | 0.63 | 40.01 | 01-SEP-00:10 | 0.63 |
| October | 0.107173E+09 | 0.64 | 40.01 | 01-OCT-00:10 | 0.64 |
| November | 0.103716E+09 | 0.64 | 40.01 | 01-NOV-00:10 | 0.64 |
| December | 0.107173E+09 | 0.65 | 40.01 | 01-DEC-00:10 | 0.65 |
| Annual Sum or Average | 0.126188E+10 | 0.64 | |||
| Minimum of Months | 96801429.15 | 0.63 | 40.01 | 0.63 | |
| Maximum of Months | 0.107173E+09 | 0.65 | 40.01 | 0.65 |
Report: FanReportMonthly
For: M N2 APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.107173E+09 | 0.64 | 40.01 | 01-JAN-00:10 | 0.64 |
| February | 96801429.15 | 0.64 | 40.01 | 01-FEB-00:10 | 0.65 |
| March | 0.107173E+09 | 0.64 | 40.01 | 01-MAR-00:10 | 0.64 |
| April | 0.103716E+09 | 0.64 | 40.01 | 01-APR-00:10 | 0.64 |
| May | 0.107173E+09 | 0.64 | 40.01 | 01-MAY-00:10 | 0.64 |
| June | 0.103716E+09 | 0.64 | 40.01 | 01-JUN-00:10 | 0.64 |
| July | 0.107173E+09 | 0.64 | 40.01 | 01-JUL-00:10 | 0.64 |
| August | 0.107173E+09 | 0.64 | 40.01 | 01-AUG-00:10 | 0.64 |
| September | 0.103716E+09 | 0.64 | 40.01 | 01-SEP-00:10 | 0.64 |
| October | 0.107173E+09 | 0.64 | 40.01 | 01-OCT-00:10 | 0.64 |
| November | 0.103716E+09 | 0.64 | 40.01 | 01-NOV-00:10 | 0.64 |
| December | 0.107173E+09 | 0.64 | 40.01 | 01-DEC-00:10 | 0.65 |
| Annual Sum or Average | 0.126188E+10 | 0.64 | |||
| Minimum of Months | 96801429.15 | 0.64 | 40.01 | 0.64 | |
| Maximum of Months | 0.107173E+09 | 0.64 | 40.01 | 0.65 |
Report: FanReportMonthly
For: SPLIT MS1 SUPPLY FAN
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.121273E+09 | 0.66 | 222.73 | 12-JAN-14:30 | 1.06 |
| February | 0.213404E+09 | 0.87 | 286.88 | 20-FEB-14:30 | 1.05 |
| March | 0.411143E+09 | 1.06 | 349.95 | 12-MAR-16:10 | 1.03 |
| April | 0.605114E+09 | 1.05 | 443.37 | 15-APR-15:10 | 1.01 |
| May | 0.779262E+09 | 1.04 | 475.95 | 05-MAY-16:10 | 1.01 |
| June | 0.810005E+09 | 1.03 | 465.92 | 06-JUN-15:10 | 1.01 |
| July | 0.867743E+09 | 1.03 | 480.34 | 01-JUL-16:01 | 1.00 |
| August | 0.814986E+09 | 1.03 | 444.05 | 27-AUG-16:02 | 1.00 |
| September | 0.721847E+09 | 1.04 | 433.08 | 24-SEP-16:10 | 1.01 |
| October | 0.570163E+09 | 1.06 | 415.79 | 03-OCT-14:10 | 1.02 |
| November | 0.374288E+09 | 1.07 | 338.61 | 04-NOV-14:00 | 1.03 |
| December | 0.178430E+09 | 0.78 | 262.83 | 02-DEC-14:00 | 1.05 |
| Annual Sum or Average | 0.646766E+10 | 0.98 | |||
| Minimum of Months | 0.121273E+09 | 0.66 | 222.73 | 1.00 | |
| Maximum of Months | 0.867743E+09 | 1.07 | 480.34 | 1.06 |
Report: FanReportMonthly
For: M S1 APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.107173E+09 | 0.65 | 40.01 | 01-JAN-00:10 | 0.65 |
| February | 96801429.15 | 0.64 | 40.01 | 01-FEB-00:10 | 0.65 |
| March | 0.107173E+09 | 0.64 | 40.01 | 01-MAR-00:10 | 0.64 |
| April | 0.103716E+09 | 0.64 | 40.01 | 01-APR-00:10 | 0.64 |
| May | 0.107173E+09 | 0.64 | 40.01 | 01-MAY-00:10 | 0.64 |
| June | 0.103716E+09 | 0.63 | 40.01 | 01-JUN-00:10 | 0.64 |
| July | 0.107173E+09 | 0.63 | 40.01 | 01-JUL-00:10 | 0.63 |
| August | 0.107173E+09 | 0.63 | 40.01 | 01-AUG-00:10 | 0.63 |
| September | 0.103716E+09 | 0.63 | 40.01 | 01-SEP-00:10 | 0.63 |
| October | 0.107173E+09 | 0.64 | 40.01 | 01-OCT-00:10 | 0.64 |
| November | 0.103716E+09 | 0.64 | 40.01 | 01-NOV-00:10 | 0.64 |
| December | 0.107173E+09 | 0.65 | 40.01 | 01-DEC-00:10 | 0.65 |
| Annual Sum or Average | 0.126188E+10 | 0.64 | |||
| Minimum of Months | 96801429.15 | 0.63 | 40.01 | 0.63 | |
| Maximum of Months | 0.107173E+09 | 0.65 | 40.01 | 0.65 |
Report: FanReportMonthly
For: M S1 APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.107173E+09 | 0.64 | 40.01 | 01-JAN-00:10 | 0.64 |
| February | 96801429.15 | 0.64 | 40.01 | 01-FEB-00:10 | 0.65 |
| March | 0.107173E+09 | 0.64 | 40.01 | 01-MAR-00:10 | 0.64 |
| April | 0.103716E+09 | 0.64 | 40.01 | 01-APR-00:10 | 0.64 |
| May | 0.107173E+09 | 0.64 | 40.01 | 01-MAY-00:10 | 0.64 |
| June | 0.103716E+09 | 0.64 | 40.01 | 01-JUN-00:10 | 0.64 |
| July | 0.107173E+09 | 0.64 | 40.01 | 01-JUL-00:10 | 0.64 |
| August | 0.107173E+09 | 0.64 | 40.01 | 01-AUG-00:10 | 0.64 |
| September | 0.103716E+09 | 0.64 | 40.01 | 01-SEP-00:10 | 0.64 |
| October | 0.107173E+09 | 0.64 | 40.01 | 01-OCT-00:10 | 0.64 |
| November | 0.103716E+09 | 0.64 | 40.01 | 01-NOV-00:10 | 0.64 |
| December | 0.107173E+09 | 0.64 | 40.01 | 01-DEC-00:10 | 0.65 |
| Annual Sum or Average | 0.126188E+10 | 0.64 | |||
| Minimum of Months | 96801429.15 | 0.64 | 40.01 | 0.64 | |
| Maximum of Months | 0.107173E+09 | 0.64 | 40.01 | 0.65 |
Report: FanReportMonthly
For: SPLIT MS2 SUPPLY FAN
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.121733E+09 | 0.66 | 223.09 | 12-JAN-14:30 | 1.06 |
| February | 0.213819E+09 | 0.87 | 287.29 | 20-FEB-14:30 | 1.05 |
| March | 0.411319E+09 | 1.06 | 349.57 | 12-MAR-16:10 | 1.03 |
| April | 0.605213E+09 | 1.05 | 443.38 | 15-APR-15:10 | 1.01 |
| May | 0.779350E+09 | 1.04 | 475.39 | 05-MAY-16:10 | 1.01 |
| June | 0.809680E+09 | 1.03 | 465.75 | 06-JUN-15:10 | 1.01 |
| July | 0.867680E+09 | 1.03 | 480.07 | 01-JUL-16:01 | 1.00 |
| August | 0.814935E+09 | 1.03 | 443.78 | 27-AUG-16:02 | 1.00 |
| September | 0.721713E+09 | 1.04 | 432.48 | 22-SEP-15:10 | 1.01 |
| October | 0.570253E+09 | 1.06 | 416.06 | 03-OCT-14:10 | 1.02 |
| November | 0.374332E+09 | 1.07 | 338.85 | 04-NOV-13:50 | 1.03 |
| December | 0.178692E+09 | 0.78 | 263.10 | 02-DEC-14:00 | 1.05 |
| Annual Sum or Average | 0.646872E+10 | 0.98 | |||
| Minimum of Months | 0.121733E+09 | 0.66 | 223.09 | 1.00 | |
| Maximum of Months | 0.867680E+09 | 1.07 | 480.07 | 1.06 |
Report: FanReportMonthly
For: M S2 APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.107173E+09 | 0.65 | 40.01 | 01-JAN-00:10 | 0.65 |
| February | 96801429.15 | 0.64 | 40.01 | 01-FEB-00:10 | 0.65 |
| March | 0.107173E+09 | 0.64 | 40.01 | 01-MAR-00:10 | 0.64 |
| April | 0.103716E+09 | 0.64 | 40.01 | 01-APR-00:10 | 0.64 |
| May | 0.107173E+09 | 0.64 | 40.01 | 01-MAY-00:10 | 0.64 |
| June | 0.103716E+09 | 0.63 | 40.01 | 01-JUN-00:10 | 0.64 |
| July | 0.107173E+09 | 0.63 | 40.01 | 01-JUL-00:10 | 0.63 |
| August | 0.107173E+09 | 0.63 | 40.01 | 01-AUG-00:10 | 0.63 |
| September | 0.103716E+09 | 0.63 | 40.01 | 01-SEP-00:10 | 0.63 |
| October | 0.107173E+09 | 0.64 | 40.01 | 01-OCT-00:10 | 0.64 |
| November | 0.103716E+09 | 0.64 | 40.01 | 01-NOV-00:10 | 0.64 |
| December | 0.107173E+09 | 0.65 | 40.01 | 01-DEC-00:10 | 0.65 |
| Annual Sum or Average | 0.126188E+10 | 0.64 | |||
| Minimum of Months | 96801429.15 | 0.63 | 40.01 | 0.63 | |
| Maximum of Months | 0.107173E+09 | 0.65 | 40.01 | 0.65 |
Report: FanReportMonthly
For: M S2 APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.107173E+09 | 0.64 | 40.01 | 01-JAN-00:10 | 0.64 |
| February | 96801429.15 | 0.64 | 40.01 | 01-FEB-00:10 | 0.65 |
| March | 0.107173E+09 | 0.64 | 40.01 | 01-MAR-00:10 | 0.64 |
| April | 0.103716E+09 | 0.64 | 40.01 | 01-APR-00:10 | 0.64 |
| May | 0.107173E+09 | 0.64 | 40.01 | 01-MAY-00:10 | 0.64 |
| June | 0.103716E+09 | 0.64 | 40.01 | 01-JUN-00:10 | 0.64 |
| July | 0.107173E+09 | 0.64 | 40.01 | 01-JUL-00:10 | 0.64 |
| August | 0.107173E+09 | 0.64 | 40.01 | 01-AUG-00:10 | 0.64 |
| September | 0.103716E+09 | 0.64 | 40.01 | 01-SEP-00:10 | 0.64 |
| October | 0.107173E+09 | 0.64 | 40.01 | 01-OCT-00:10 | 0.64 |
| November | 0.103716E+09 | 0.64 | 40.01 | 01-NOV-00:10 | 0.64 |
| December | 0.107173E+09 | 0.64 | 40.01 | 01-DEC-00:10 | 0.65 |
| Annual Sum or Average | 0.126188E+10 | 0.64 | |||
| Minimum of Months | 96801429.15 | 0.64 | 40.01 | 0.64 | |
| Maximum of Months | 0.107173E+09 | 0.64 | 40.01 | 0.65 |
Report: FanReportMonthly
For: SPLIT TSW SUPPLY FAN
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 52474401.57 | 0.55 | 138.19 | 12-JAN-15:20 | 1.06 |
| February | 91563298.02 | 0.57 | 216.94 | 20-FEB-15:20 | 1.04 |
| March | 0.229706E+09 | 0.79 | 319.10 | 28-MAR-16:04 | 1.01 |
| April | 0.416890E+09 | 1.04 | 410.95 | 15-APR-15:10 | 0.98 |
| May | 0.569391E+09 | 1.03 | 453.99 | 05-MAY-16:10 | 0.97 |
| June | 0.585145E+09 | 1.03 | 447.74 | 06-JUN-16:10 | 0.97 |
| July | 0.603251E+09 | 1.03 | 413.86 | 02-JUL-16:30 | 0.97 |
| August | 0.545682E+09 | 1.03 | 371.39 | 07-AUG-16:03 | 0.99 |
| September | 0.460012E+09 | 1.04 | 367.75 | 22-SEP-15:10 | 0.99 |
| October | 0.327858E+09 | 0.98 | 356.40 | 03-OCT-15:10 | 0.99 |
| November | 0.170113E+09 | 0.63 | 264.21 | 04-NOV-15:10 | 1.02 |
| December | 61819594.46 | 0.56 | 165.68 | 02-DEC-15:00 | 1.06 |
| Annual Sum or Average | 0.411390E+10 | 0.86 | |||
| Minimum of Months | 52474401.57 | 0.55 | 138.19 | 0.97 | |
| Maximum of Months | 0.603251E+09 | 1.04 | 453.99 | 1.06 |
Report: FanReportMonthly
For: T SW APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.65 | 20.01 | 01-JAN-00:10 | 0.65 |
| February | 48400714.57 | 0.64 | 20.01 | 01-FEB-00:10 | 0.65 |
| March | 53586505.42 | 0.64 | 20.01 | 01-MAR-00:10 | 0.64 |
| April | 51857908.47 | 0.64 | 20.01 | 01-APR-00:10 | 0.64 |
| May | 53586505.42 | 0.64 | 20.01 | 01-MAY-00:10 | 0.64 |
| June | 51857908.47 | 0.63 | 20.01 | 01-JUN-00:10 | 0.64 |
| July | 53586505.42 | 0.63 | 20.01 | 01-JUL-00:10 | 0.63 |
| August | 53586505.42 | 0.63 | 20.01 | 01-AUG-00:10 | 0.63 |
| September | 51857908.47 | 0.63 | 20.01 | 01-SEP-00:10 | 0.63 |
| October | 53586505.42 | 0.64 | 20.01 | 01-OCT-00:10 | 0.64 |
| November | 51857908.47 | 0.64 | 20.01 | 01-NOV-00:10 | 0.64 |
| December | 53586505.42 | 0.65 | 20.01 | 01-DEC-00:10 | 0.65 |
| Annual Sum or Average | 0.630938E+09 | 0.64 | |||
| Minimum of Months | 48400714.57 | 0.63 | 20.01 | 0.63 | |
| Maximum of Months | 53586505.42 | 0.65 | 20.01 | 0.65 |
Report: FanReportMonthly
For: T SW APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.64 | 20.01 | 01-JAN-00:10 | 0.64 |
| February | 48400714.57 | 0.64 | 20.01 | 01-FEB-00:10 | 0.65 |
| March | 53586505.42 | 0.64 | 20.01 | 01-MAR-00:10 | 0.64 |
| April | 51857908.47 | 0.64 | 20.01 | 01-APR-00:10 | 0.64 |
| May | 53586505.42 | 0.64 | 20.01 | 01-MAY-00:10 | 0.64 |
| June | 51857908.47 | 0.64 | 20.01 | 01-JUN-00:10 | 0.64 |
| July | 53586505.42 | 0.64 | 20.01 | 01-JUL-00:10 | 0.64 |
| August | 53586505.42 | 0.64 | 20.01 | 01-AUG-00:10 | 0.64 |
| September | 51857908.47 | 0.64 | 20.01 | 01-SEP-00:10 | 0.64 |
| October | 53586505.42 | 0.64 | 20.01 | 01-OCT-00:10 | 0.64 |
| November | 51857908.47 | 0.64 | 20.01 | 01-NOV-00:10 | 0.64 |
| December | 53586505.42 | 0.64 | 20.01 | 01-DEC-00:10 | 0.65 |
| Annual Sum or Average | 0.630938E+09 | 0.64 | |||
| Minimum of Months | 48400714.57 | 0.64 | 20.01 | 0.64 | |
| Maximum of Months | 53586505.42 | 0.64 | 20.01 | 0.65 |
Report: FanReportMonthly
For: SPLIT TNW SUPPLY FAN
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 34572052.15 | 0.47 | 57.61 | 03-JAN-07:00 | 0.94 |
| February | 43841206.58 | 0.51 | 132.42 | 22-FEB-16:10 | 1.06 |
| March | 0.175272E+09 | 0.75 | 274.66 | 28-MAR-16:30 | 1.02 |
| April | 0.381927E+09 | 1.04 | 387.99 | 27-APR-16:10 | 0.99 |
| May | 0.563785E+09 | 1.04 | 445.62 | 05-MAY-16:10 | 0.97 |
| June | 0.588055E+09 | 1.03 | 448.42 | 06-JUN-16:04 | 0.97 |
| July | 0.604410E+09 | 1.03 | 408.92 | 02-JUL-16:40 | 0.98 |
| August | 0.539922E+09 | 1.03 | 366.54 | 07-AUG-16:10 | 0.99 |
| September | 0.429557E+09 | 1.04 | 321.41 | 22-SEP-15:20 | 1.00 |
| October | 0.251979E+09 | 0.96 | 295.72 | 03-OCT-15:10 | 1.01 |
| November | 83195836.87 | 0.54 | 161.43 | 09-NOV-15:10 | 1.05 |
| December | 27876197.55 | 0.48 | 60.91 | 28-DEC-16:10 | 1.08 |
| Annual Sum or Average | 0.372439E+10 | 0.83 | |||
| Minimum of Months | 27876197.55 | 0.47 | 57.61 | 0.94 | |
| Maximum of Months | 0.604410E+09 | 1.04 | 448.42 | 1.08 |
Report: FanReportMonthly
For: T NW APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.65 | 20.01 | 01-JAN-00:10 | 0.65 |
| February | 48400714.57 | 0.64 | 20.01 | 01-FEB-00:10 | 0.65 |
| March | 53586505.42 | 0.64 | 20.01 | 01-MAR-00:10 | 0.64 |
| April | 51857908.47 | 0.64 | 20.01 | 01-APR-00:10 | 0.64 |
| May | 53586505.42 | 0.64 | 20.01 | 01-MAY-00:10 | 0.64 |
| June | 51857908.47 | 0.63 | 20.01 | 01-JUN-00:10 | 0.64 |
| July | 53586505.42 | 0.63 | 20.01 | 01-JUL-00:10 | 0.63 |
| August | 53586505.42 | 0.63 | 20.01 | 01-AUG-00:10 | 0.63 |
| September | 51857908.47 | 0.63 | 20.01 | 01-SEP-00:10 | 0.63 |
| October | 53586505.42 | 0.64 | 20.01 | 01-OCT-00:10 | 0.64 |
| November | 51857908.47 | 0.64 | 20.01 | 01-NOV-00:10 | 0.64 |
| December | 53586505.42 | 0.65 | 20.01 | 01-DEC-00:10 | 0.65 |
| Annual Sum or Average | 0.630938E+09 | 0.64 | |||
| Minimum of Months | 48400714.57 | 0.63 | 20.01 | 0.63 | |
| Maximum of Months | 53586505.42 | 0.65 | 20.01 | 0.65 |
Report: FanReportMonthly
For: T NW APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.64 | 20.01 | 01-JAN-00:10 | 0.64 |
| February | 48400714.57 | 0.64 | 20.01 | 01-FEB-00:10 | 0.65 |
| March | 53586505.42 | 0.64 | 20.01 | 01-MAR-00:10 | 0.64 |
| April | 51857908.47 | 0.64 | 20.01 | 01-APR-00:10 | 0.64 |
| May | 53586505.42 | 0.64 | 20.01 | 01-MAY-00:10 | 0.64 |
| June | 51857908.47 | 0.64 | 20.01 | 01-JUN-00:10 | 0.64 |
| July | 53586505.42 | 0.64 | 20.01 | 01-JUL-00:10 | 0.64 |
| August | 53586505.42 | 0.64 | 20.01 | 01-AUG-00:10 | 0.64 |
| September | 51857908.47 | 0.64 | 20.01 | 01-SEP-00:10 | 0.64 |
| October | 53586505.42 | 0.64 | 20.01 | 01-OCT-00:10 | 0.64 |
| November | 51857908.47 | 0.64 | 20.01 | 01-NOV-00:10 | 0.64 |
| December | 53586505.42 | 0.64 | 20.01 | 01-DEC-00:10 | 0.65 |
| Annual Sum or Average | 0.630938E+09 | 0.64 | |||
| Minimum of Months | 48400714.57 | 0.64 | 20.01 | 0.64 | |
| Maximum of Months | 53586505.42 | 0.64 | 20.01 | 0.65 |
Report: FanReportMonthly
For: SPLIT TSE SUPPLY FAN
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 48981552.65 | 0.53 | 126.34 | 12-JAN-14:40 | 1.06 |
| February | 91371580.74 | 0.58 | 200.23 | 20-FEB-14:30 | 1.04 |
| March | 0.230280E+09 | 0.80 | 281.02 | 28-MAR-15:10 | 1.02 |
| April | 0.416407E+09 | 1.04 | 387.32 | 15-APR-14:00 | 0.98 |
| May | 0.568285E+09 | 1.03 | 411.92 | 05-MAY-15:10 | 0.98 |
| June | 0.577135E+09 | 1.03 | 412.03 | 06-JUN-15:10 | 0.97 |
| July | 0.599820E+09 | 1.02 | 378.31 | 01-JUL-13:00 | 0.98 |
| August | 0.542855E+09 | 1.03 | 347.55 | 07-AUG-15:10 | 0.99 |
| September | 0.456423E+09 | 1.04 | 344.03 | 22-SEP-14:20 | 0.99 |
| October | 0.328162E+09 | 0.98 | 338.42 | 03-OCT-14:10 | 0.99 |
| November | 0.169016E+09 | 0.63 | 244.36 | 09-NOV-13:30 | 1.03 |
| December | 59876718.59 | 0.56 | 151.84 | 02-DEC-14:00 | 1.06 |
| Annual Sum or Average | 0.408861E+10 | 0.86 | |||
| Minimum of Months | 48981552.65 | 0.53 | 126.34 | 0.97 | |
| Maximum of Months | 0.599820E+09 | 1.04 | 412.03 | 1.06 |
Report: FanReportMonthly
For: T SE APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.65 | 20.01 | 01-JAN-00:10 | 0.65 |
| February | 48400714.57 | 0.64 | 20.01 | 01-FEB-00:10 | 0.65 |
| March | 53586505.42 | 0.64 | 20.01 | 01-MAR-00:10 | 0.64 |
| April | 51857908.47 | 0.64 | 20.01 | 01-APR-00:10 | 0.64 |
| May | 53586505.42 | 0.64 | 20.01 | 01-MAY-00:10 | 0.64 |
| June | 51857908.47 | 0.63 | 20.01 | 01-JUN-00:10 | 0.64 |
| July | 53586505.42 | 0.63 | 20.01 | 01-JUL-00:10 | 0.63 |
| August | 53586505.42 | 0.63 | 20.01 | 01-AUG-00:10 | 0.63 |
| September | 51857908.47 | 0.63 | 20.01 | 01-SEP-00:10 | 0.63 |
| October | 53586505.42 | 0.64 | 20.01 | 01-OCT-00:10 | 0.64 |
| November | 51857908.47 | 0.64 | 20.01 | 01-NOV-00:10 | 0.64 |
| December | 53586505.42 | 0.65 | 20.01 | 01-DEC-00:10 | 0.65 |
| Annual Sum or Average | 0.630938E+09 | 0.64 | |||
| Minimum of Months | 48400714.57 | 0.63 | 20.01 | 0.63 | |
| Maximum of Months | 53586505.42 | 0.65 | 20.01 | 0.65 |
Report: FanReportMonthly
For: T SE APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.64 | 20.01 | 01-JAN-00:10 | 0.64 |
| February | 48400714.57 | 0.64 | 20.01 | 01-FEB-00:10 | 0.65 |
| March | 53586505.42 | 0.64 | 20.01 | 01-MAR-00:10 | 0.64 |
| April | 51857908.47 | 0.64 | 20.01 | 01-APR-00:10 | 0.64 |
| May | 53586505.42 | 0.64 | 20.01 | 01-MAY-00:10 | 0.64 |
| June | 51857908.47 | 0.64 | 20.01 | 01-JUN-00:10 | 0.64 |
| July | 53586505.42 | 0.64 | 20.01 | 01-JUL-00:10 | 0.64 |
| August | 53586505.42 | 0.64 | 20.01 | 01-AUG-00:10 | 0.64 |
| September | 51857908.47 | 0.64 | 20.01 | 01-SEP-00:10 | 0.64 |
| October | 53586505.42 | 0.64 | 20.01 | 01-OCT-00:10 | 0.64 |
| November | 51857908.47 | 0.64 | 20.01 | 01-NOV-00:10 | 0.64 |
| December | 53586505.42 | 0.64 | 20.01 | 01-DEC-00:10 | 0.65 |
| Annual Sum or Average | 0.630938E+09 | 0.64 | |||
| Minimum of Months | 48400714.57 | 0.64 | 20.01 | 0.64 | |
| Maximum of Months | 53586505.42 | 0.64 | 20.01 | 0.65 |
Report: FanReportMonthly
For: SPLIT TNE SUPPLY FAN
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 31985280.81 | 0.43 | 58.16 | 03-JAN-07:00 | 0.94 |
| February | 41462688.71 | 0.51 | 116.17 | 23-FEB-14:00 | 1.07 |
| March | 0.175764E+09 | 0.77 | 228.21 | 28-MAR-16:01 | 1.03 |
| April | 0.381877E+09 | 1.04 | 346.61 | 15-APR-15:10 | 0.99 |
| May | 0.562861E+09 | 1.03 | 397.62 | 05-MAY-15:10 | 0.98 |
| June | 0.580138E+09 | 1.03 | 407.61 | 06-JUN-15:10 | 0.97 |
| July | 0.601106E+09 | 1.02 | 369.73 | 01-JUL-12:50 | 0.98 |
| August | 0.537280E+09 | 1.03 | 339.58 | 07-AUG-16:10 | 0.99 |
| September | 0.426372E+09 | 1.04 | 295.05 | 22-SEP-15:10 | 1.00 |
| October | 0.252886E+09 | 0.96 | 268.70 | 03-OCT-15:10 | 1.02 |
| November | 81237777.57 | 0.55 | 144.97 | 09-NOV-13:50 | 1.06 |
| December | 25341729.57 | 0.45 | 55.88 | 23-DEC-06:00 | 0.94 |
| Annual Sum or Average | 0.369831E+10 | 0.82 | |||
| Minimum of Months | 25341729.57 | 0.43 | 55.88 | 0.94 | |
| Maximum of Months | 0.601106E+09 | 1.04 | 407.61 | 1.07 |
Report: FanReportMonthly
For: T NE APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.65 | 20.01 | 01-JAN-00:10 | 0.65 |
| February | 48400714.57 | 0.64 | 20.01 | 01-FEB-00:10 | 0.65 |
| March | 53586505.42 | 0.64 | 20.01 | 01-MAR-00:10 | 0.64 |
| April | 51857908.47 | 0.64 | 20.01 | 01-APR-00:10 | 0.64 |
| May | 53586505.42 | 0.64 | 20.01 | 01-MAY-00:10 | 0.64 |
| June | 51857908.47 | 0.63 | 20.01 | 01-JUN-00:10 | 0.64 |
| July | 53586505.42 | 0.63 | 20.01 | 01-JUL-00:10 | 0.63 |
| August | 53586505.42 | 0.63 | 20.01 | 01-AUG-00:10 | 0.63 |
| September | 51857908.47 | 0.63 | 20.01 | 01-SEP-00:10 | 0.63 |
| October | 53586505.42 | 0.64 | 20.01 | 01-OCT-00:10 | 0.64 |
| November | 51857908.47 | 0.64 | 20.01 | 01-NOV-00:10 | 0.64 |
| December | 53586505.42 | 0.65 | 20.01 | 01-DEC-00:10 | 0.65 |
| Annual Sum or Average | 0.630938E+09 | 0.64 | |||
| Minimum of Months | 48400714.57 | 0.63 | 20.01 | 0.63 | |
| Maximum of Months | 53586505.42 | 0.65 | 20.01 | 0.65 |
Report: FanReportMonthly
For: T NE APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.64 | 20.01 | 01-JAN-00:10 | 0.64 |
| February | 48400714.57 | 0.64 | 20.01 | 01-FEB-00:10 | 0.65 |
| March | 53586505.42 | 0.64 | 20.01 | 01-MAR-00:10 | 0.64 |
| April | 51857908.47 | 0.64 | 20.01 | 01-APR-00:10 | 0.64 |
| May | 53586505.42 | 0.64 | 20.01 | 01-MAY-00:10 | 0.64 |
| June | 51857908.47 | 0.64 | 20.01 | 01-JUN-00:10 | 0.64 |
| July | 53586505.42 | 0.64 | 20.01 | 01-JUL-00:10 | 0.64 |
| August | 53586505.42 | 0.64 | 20.01 | 01-AUG-00:10 | 0.64 |
| September | 51857908.47 | 0.64 | 20.01 | 01-SEP-00:10 | 0.64 |
| October | 53586505.42 | 0.64 | 20.01 | 01-OCT-00:10 | 0.64 |
| November | 51857908.47 | 0.64 | 20.01 | 01-NOV-00:10 | 0.64 |
| December | 53586505.42 | 0.64 | 20.01 | 01-DEC-00:10 | 0.65 |
| Annual Sum or Average | 0.630938E+09 | 0.64 | |||
| Minimum of Months | 48400714.57 | 0.64 | 20.01 | 0.64 | |
| Maximum of Months | 53586505.42 | 0.64 | 20.01 | 0.65 |
Report: FanReportMonthly
For: SPLIT TN1 SUPPLY FAN
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 20717009.64 | 0.37 | 40.91 | 03-JAN-07:00 | 0.94 |
| February | 30281347.19 | 0.44 | 94.69 | 24-FEB-16:10 | 1.07 |
| March | 0.145246E+09 | 0.80 | 191.15 | 28-MAR-16:06 | 1.04 |
| April | 0.310876E+09 | 1.05 | 272.59 | 27-APR-16:10 | 1.01 |
| May | 0.461628E+09 | 1.04 | 317.82 | 05-MAY-16:10 | 0.99 |
| June | 0.488479E+09 | 1.03 | 323.85 | 06-JUN-16:10 | 0.99 |
| July | 0.509789E+09 | 1.03 | 304.89 | 02-JUL-17:10 | 0.99 |
| August | 0.462286E+09 | 1.03 | 280.20 | 07-AUG-16:10 | 1.00 |
| September | 0.368925E+09 | 1.04 | 244.72 | 14-SEP-16:10 | 1.01 |
| October | 0.215440E+09 | 0.99 | 215.30 | 03-OCT-15:10 | 1.02 |
| November | 66583185.99 | 0.55 | 118.72 | 09-NOV-14:00 | 1.06 |
| December | 13488932.92 | 0.34 | 40.16 | 23-DEC-06:00 | 0.94 |
| Annual Sum or Average | 0.309374E+10 | 0.81 | |||
| Minimum of Months | 13488932.92 | 0.34 | 40.16 | 0.94 | |
| Maximum of Months | 0.509789E+09 | 1.05 | 323.85 | 1.07 |
Report: FanReportMonthly
For: T N1 APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.65 | 20.01 | 01-JAN-00:10 | 0.65 |
| February | 48400714.57 | 0.64 | 20.01 | 01-FEB-00:10 | 0.65 |
| March | 53586505.42 | 0.64 | 20.01 | 01-MAR-00:10 | 0.64 |
| April | 51857908.47 | 0.64 | 20.01 | 01-APR-00:10 | 0.64 |
| May | 53586505.42 | 0.64 | 20.01 | 01-MAY-00:10 | 0.64 |
| June | 51857908.47 | 0.63 | 20.01 | 01-JUN-00:10 | 0.64 |
| July | 53586505.42 | 0.63 | 20.01 | 01-JUL-00:10 | 0.63 |
| August | 53586505.42 | 0.63 | 20.01 | 01-AUG-00:10 | 0.63 |
| September | 51857908.47 | 0.63 | 20.01 | 01-SEP-00:10 | 0.63 |
| October | 53586505.42 | 0.64 | 20.01 | 01-OCT-00:10 | 0.64 |
| November | 51857908.47 | 0.64 | 20.01 | 01-NOV-00:10 | 0.64 |
| December | 53586505.42 | 0.65 | 20.01 | 01-DEC-00:10 | 0.65 |
| Annual Sum or Average | 0.630938E+09 | 0.64 | |||
| Minimum of Months | 48400714.57 | 0.63 | 20.01 | 0.63 | |
| Maximum of Months | 53586505.42 | 0.65 | 20.01 | 0.65 |
Report: FanReportMonthly
For: T N1 APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.64 | 20.01 | 01-JAN-00:10 | 0.64 |
| February | 48400714.57 | 0.64 | 20.01 | 01-FEB-00:10 | 0.65 |
| March | 53586505.42 | 0.64 | 20.01 | 01-MAR-00:10 | 0.64 |
| April | 51857908.47 | 0.64 | 20.01 | 01-APR-00:10 | 0.64 |
| May | 53586505.42 | 0.64 | 20.01 | 01-MAY-00:10 | 0.64 |
| June | 51857908.47 | 0.64 | 20.01 | 01-JUN-00:10 | 0.64 |
| July | 53586505.42 | 0.64 | 20.01 | 01-JUL-00:10 | 0.64 |
| August | 53586505.42 | 0.64 | 20.01 | 01-AUG-00:10 | 0.64 |
| September | 51857908.47 | 0.64 | 20.01 | 01-SEP-00:10 | 0.64 |
| October | 53586505.42 | 0.64 | 20.01 | 01-OCT-00:10 | 0.64 |
| November | 51857908.47 | 0.64 | 20.01 | 01-NOV-00:10 | 0.64 |
| December | 53586505.42 | 0.64 | 20.01 | 01-DEC-00:10 | 0.65 |
| Annual Sum or Average | 0.630938E+09 | 0.64 | |||
| Minimum of Months | 48400714.57 | 0.64 | 20.01 | 0.64 | |
| Maximum of Months | 53586505.42 | 0.64 | 20.01 | 0.65 |
Report: FanReportMonthly
For: SPLIT TN2 SUPPLY FAN
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 20772812.91 | 0.37 | 40.97 | 03-JAN-07:00 | 0.94 |
| February | 30554227.17 | 0.44 | 94.86 | 24-FEB-16:10 | 1.07 |
| March | 0.145510E+09 | 0.80 | 190.43 | 28-MAR-16:06 | 1.04 |
| April | 0.310953E+09 | 1.05 | 272.16 | 15-APR-15:10 | 1.01 |
| May | 0.461650E+09 | 1.04 | 316.94 | 05-MAY-16:10 | 0.99 |
| June | 0.488233E+09 | 1.03 | 323.40 | 06-JUN-15:10 | 0.99 |
| July | 0.509693E+09 | 1.03 | 303.77 | 02-JUL-17:10 | 0.99 |
| August | 0.462212E+09 | 1.03 | 279.68 | 07-AUG-16:10 | 1.00 |
| September | 0.368831E+09 | 1.04 | 244.08 | 14-SEP-16:10 | 1.01 |
| October | 0.215562E+09 | 0.99 | 215.00 | 03-OCT-15:10 | 1.02 |
| November | 66835972.56 | 0.55 | 118.96 | 09-NOV-14:00 | 1.06 |
| December | 13594343.43 | 0.34 | 40.09 | 23-DEC-06:00 | 0.94 |
| Annual Sum or Average | 0.309440E+10 | 0.81 | |||
| Minimum of Months | 13594343.43 | 0.34 | 40.09 | 0.94 | |
| Maximum of Months | 0.509693E+09 | 1.05 | 323.40 | 1.07 |
Report: FanReportMonthly
For: T N2 APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.65 | 20.01 | 01-JAN-00:10 | 0.65 |
| February | 48400714.57 | 0.64 | 20.01 | 01-FEB-00:10 | 0.65 |
| March | 53586505.42 | 0.64 | 20.01 | 01-MAR-00:10 | 0.64 |
| April | 51857908.47 | 0.64 | 20.01 | 01-APR-00:10 | 0.64 |
| May | 53586505.42 | 0.64 | 20.01 | 01-MAY-00:10 | 0.64 |
| June | 51857908.47 | 0.63 | 20.01 | 01-JUN-00:10 | 0.64 |
| July | 53586505.42 | 0.63 | 20.01 | 01-JUL-00:10 | 0.63 |
| August | 53586505.42 | 0.63 | 20.01 | 01-AUG-00:10 | 0.63 |
| September | 51857908.47 | 0.63 | 20.01 | 01-SEP-00:10 | 0.63 |
| October | 53586505.42 | 0.64 | 20.01 | 01-OCT-00:10 | 0.64 |
| November | 51857908.47 | 0.64 | 20.01 | 01-NOV-00:10 | 0.64 |
| December | 53586505.42 | 0.65 | 20.01 | 01-DEC-00:10 | 0.65 |
| Annual Sum or Average | 0.630938E+09 | 0.64 | |||
| Minimum of Months | 48400714.57 | 0.63 | 20.01 | 0.63 | |
| Maximum of Months | 53586505.42 | 0.65 | 20.01 | 0.65 |
Report: FanReportMonthly
For: T N2 APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.64 | 20.01 | 01-JAN-00:10 | 0.64 |
| February | 48400714.57 | 0.64 | 20.01 | 01-FEB-00:10 | 0.65 |
| March | 53586505.42 | 0.64 | 20.01 | 01-MAR-00:10 | 0.64 |
| April | 51857908.47 | 0.64 | 20.01 | 01-APR-00:10 | 0.64 |
| May | 53586505.42 | 0.64 | 20.01 | 01-MAY-00:10 | 0.64 |
| June | 51857908.47 | 0.64 | 20.01 | 01-JUN-00:10 | 0.64 |
| July | 53586505.42 | 0.64 | 20.01 | 01-JUL-00:10 | 0.64 |
| August | 53586505.42 | 0.64 | 20.01 | 01-AUG-00:10 | 0.64 |
| September | 51857908.47 | 0.64 | 20.01 | 01-SEP-00:10 | 0.64 |
| October | 53586505.42 | 0.64 | 20.01 | 01-OCT-00:10 | 0.64 |
| November | 51857908.47 | 0.64 | 20.01 | 01-NOV-00:10 | 0.64 |
| December | 53586505.42 | 0.64 | 20.01 | 01-DEC-00:10 | 0.65 |
| Annual Sum or Average | 0.630938E+09 | 0.64 | |||
| Minimum of Months | 48400714.57 | 0.64 | 20.01 | 0.64 | |
| Maximum of Months | 53586505.42 | 0.64 | 20.01 | 0.65 |
Report: FanReportMonthly
For: SPLIT TS1 SUPPLY FAN
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 38781634.65 | 0.48 | 118.52 | 12-JAN-14:50 | 1.06 |
| February | 81181358.63 | 0.56 | 179.52 | 20-FEB-14:40 | 1.04 |
| March | 0.200670E+09 | 0.85 | 240.83 | 28-MAR-15:10 | 1.02 |
| April | 0.345977E+09 | 1.05 | 309.18 | 15-APR-15:10 | 0.99 |
| May | 0.467123E+09 | 1.04 | 328.40 | 05-MAY-15:10 | 0.99 |
| June | 0.485298E+09 | 1.03 | 328.50 | 06-JUN-15:10 | 0.99 |
| July | 0.508359E+09 | 1.03 | 311.56 | 01-JUL-16:01 | 0.99 |
| August | 0.467821E+09 | 1.03 | 285.15 | 13-AUG-16:02 | 1.00 |
| September | 0.399422E+09 | 1.04 | 286.69 | 24-SEP-14:00 | 1.00 |
| October | 0.292016E+09 | 1.00 | 282.63 | 03-OCT-14:10 | 1.00 |
| November | 0.157047E+09 | 0.67 | 219.76 | 04-NOV-14:00 | 1.03 |
| December | 51757134.01 | 0.48 | 141.22 | 02-DEC-14:20 | 1.06 |
| Annual Sum or Average | 0.349545E+10 | 0.86 | |||
| Minimum of Months | 38781634.65 | 0.48 | 118.52 | 0.99 | |
| Maximum of Months | 0.508359E+09 | 1.05 | 328.50 | 1.06 |
Report: FanReportMonthly
For: T S1 APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.65 | 20.01 | 01-JAN-00:10 | 0.65 |
| February | 48400714.57 | 0.64 | 20.01 | 01-FEB-00:10 | 0.65 |
| March | 53586505.42 | 0.64 | 20.01 | 01-MAR-00:10 | 0.64 |
| April | 51857908.47 | 0.64 | 20.01 | 01-APR-00:10 | 0.64 |
| May | 53586505.42 | 0.64 | 20.01 | 01-MAY-00:10 | 0.64 |
| June | 51857908.47 | 0.63 | 20.01 | 01-JUN-00:10 | 0.64 |
| July | 53586505.42 | 0.63 | 20.01 | 01-JUL-00:10 | 0.63 |
| August | 53586505.42 | 0.63 | 20.01 | 01-AUG-00:10 | 0.63 |
| September | 51857908.47 | 0.63 | 20.01 | 01-SEP-00:10 | 0.63 |
| October | 53586505.42 | 0.64 | 20.01 | 01-OCT-00:10 | 0.64 |
| November | 51857908.47 | 0.64 | 20.01 | 01-NOV-00:10 | 0.64 |
| December | 53586505.42 | 0.65 | 20.01 | 01-DEC-00:10 | 0.65 |
| Annual Sum or Average | 0.630938E+09 | 0.64 | |||
| Minimum of Months | 48400714.57 | 0.63 | 20.01 | 0.63 | |
| Maximum of Months | 53586505.42 | 0.65 | 20.01 | 0.65 |
Report: FanReportMonthly
For: T S1 APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.64 | 20.01 | 01-JAN-00:10 | 0.64 |
| February | 48400714.57 | 0.64 | 20.01 | 01-FEB-00:10 | 0.65 |
| March | 53586505.42 | 0.64 | 20.01 | 01-MAR-00:10 | 0.64 |
| April | 51857908.47 | 0.64 | 20.01 | 01-APR-00:10 | 0.64 |
| May | 53586505.42 | 0.64 | 20.01 | 01-MAY-00:10 | 0.64 |
| June | 51857908.47 | 0.64 | 20.01 | 01-JUN-00:10 | 0.64 |
| July | 53586505.42 | 0.64 | 20.01 | 01-JUL-00:10 | 0.64 |
| August | 53586505.42 | 0.64 | 20.01 | 01-AUG-00:10 | 0.64 |
| September | 51857908.47 | 0.64 | 20.01 | 01-SEP-00:10 | 0.64 |
| October | 53586505.42 | 0.64 | 20.01 | 01-OCT-00:10 | 0.64 |
| November | 51857908.47 | 0.64 | 20.01 | 01-NOV-00:10 | 0.64 |
| December | 53586505.42 | 0.64 | 20.01 | 01-DEC-00:10 | 0.65 |
| Annual Sum or Average | 0.630938E+09 | 0.64 | |||
| Minimum of Months | 48400714.57 | 0.64 | 20.01 | 0.64 | |
| Maximum of Months | 53586505.42 | 0.64 | 20.01 | 0.65 |
Report: FanReportMonthly
For: SPLIT TS2 SUPPLY FAN
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 39028469.20 | 0.48 | 118.88 | 12-JAN-14:50 | 1.06 |
| February | 81529795.56 | 0.56 | 179.93 | 20-FEB-14:40 | 1.04 |
| March | 0.200874E+09 | 0.85 | 240.65 | 28-MAR-15:10 | 1.02 |
| April | 0.346028E+09 | 1.05 | 309.24 | 15-APR-14:10 | 0.99 |
| May | 0.467137E+09 | 1.04 | 328.09 | 05-MAY-15:10 | 0.99 |
| June | 0.485048E+09 | 1.03 | 328.13 | 06-JUN-15:10 | 0.99 |
| July | 0.508257E+09 | 1.03 | 311.08 | 01-JUL-16:01 | 0.99 |
| August | 0.467739E+09 | 1.03 | 284.91 | 07-AUG-15:10 | 1.00 |
| September | 0.399308E+09 | 1.04 | 286.74 | 24-SEP-14:00 | 1.00 |
| October | 0.292078E+09 | 1.00 | 282.79 | 03-OCT-14:10 | 1.00 |
| November | 0.157206E+09 | 0.67 | 219.98 | 04-NOV-14:00 | 1.02 |
| December | 52035005.97 | 0.48 | 141.54 | 02-DEC-14:20 | 1.06 |
| Annual Sum or Average | 0.349627E+10 | 0.86 | |||
| Minimum of Months | 39028469.20 | 0.48 | 118.88 | 0.99 | |
| Maximum of Months | 0.508257E+09 | 1.05 | 328.13 | 1.06 |
Report: FanReportMonthly
For: T S2 APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.65 | 20.01 | 01-JAN-00:10 | 0.65 |
| February | 48400714.57 | 0.64 | 20.01 | 01-FEB-00:10 | 0.65 |
| March | 53586505.42 | 0.64 | 20.01 | 01-MAR-00:10 | 0.64 |
| April | 51857908.47 | 0.64 | 20.01 | 01-APR-00:10 | 0.64 |
| May | 53586505.42 | 0.64 | 20.01 | 01-MAY-00:10 | 0.64 |
| June | 51857908.47 | 0.63 | 20.01 | 01-JUN-00:10 | 0.64 |
| July | 53586505.42 | 0.63 | 20.01 | 01-JUL-00:10 | 0.63 |
| August | 53586505.42 | 0.63 | 20.01 | 01-AUG-00:10 | 0.63 |
| September | 51857908.47 | 0.63 | 20.01 | 01-SEP-00:10 | 0.63 |
| October | 53586505.42 | 0.64 | 20.01 | 01-OCT-00:10 | 0.64 |
| November | 51857908.47 | 0.64 | 20.01 | 01-NOV-00:10 | 0.64 |
| December | 53586505.42 | 0.65 | 20.01 | 01-DEC-00:10 | 0.65 |
| Annual Sum or Average | 0.630938E+09 | 0.64 | |||
| Minimum of Months | 48400714.57 | 0.63 | 20.01 | 0.63 | |
| Maximum of Months | 53586505.42 | 0.65 | 20.01 | 0.65 |
Report: FanReportMonthly
For: T S2 APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.64 | 20.01 | 01-JAN-00:10 | 0.64 |
| February | 48400714.57 | 0.64 | 20.01 | 01-FEB-00:10 | 0.65 |
| March | 53586505.42 | 0.64 | 20.01 | 01-MAR-00:10 | 0.64 |
| April | 51857908.47 | 0.64 | 20.01 | 01-APR-00:10 | 0.64 |
| May | 53586505.42 | 0.64 | 20.01 | 01-MAY-00:10 | 0.64 |
| June | 51857908.47 | 0.64 | 20.01 | 01-JUN-00:10 | 0.64 |
| July | 53586505.42 | 0.64 | 20.01 | 01-JUL-00:10 | 0.64 |
| August | 53586505.42 | 0.64 | 20.01 | 01-AUG-00:10 | 0.64 |
| September | 51857908.47 | 0.64 | 20.01 | 01-SEP-00:10 | 0.64 |
| October | 53586505.42 | 0.64 | 20.01 | 01-OCT-00:10 | 0.64 |
| November | 51857908.47 | 0.64 | 20.01 | 01-NOV-00:10 | 0.64 |
| December | 53586505.42 | 0.64 | 20.01 | 01-DEC-00:10 | 0.65 |
| Annual Sum or Average | 0.630938E+09 | 0.64 | |||
| Minimum of Months | 48400714.57 | 0.64 | 20.01 | 0.64 | |
| Maximum of Months | 53586505.42 | 0.64 | 20.01 | 0.65 |
Report: ZoneTemperatureOscillationReportMonthly
For: G SW APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: G NW APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: OFFICE
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: G NE APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: G N1 APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: G N2 APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: G S1 APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: G S2 APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: M SW APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: M NW APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: M SE APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: M NE APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: M N1 APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: M N2 APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: M S1 APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: M S2 APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: T SW APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: T NW APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: T SE APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: T NE APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: T N1 APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: T N2 APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: T S1 APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: T S2 APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: T CORRIDOR
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: G CORRIDOR
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: M CORRIDOR
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT GSW
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.131739E+09 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.315929E+09 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.783843E+09 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.146371E+10 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.213722E+10 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.236265E+10 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.259077E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.246173E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.215515E+10 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.160468E+10 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.922415E+09 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.330649E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.172605E+11 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.131739E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.259077E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT GNW
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 6045866.80 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.113032E+09 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.562638E+09 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.132047E+10 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.211284E+10 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.237658E+10 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.259609E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.244084E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.203485E+10 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.130038E+10 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.534607E+09 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 69742550.69 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.154681E+11 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 6045866.80 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.259609E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT OFFICE
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.155143E+10 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.150288E+10 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.189470E+10 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.214633E+10 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.267237E+10 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.275709E+10 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.284290E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.282976E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.250210E+10 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.227168E+10 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.186605E+10 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.164599E+10 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.264833E+11 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.150288E+10 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.284290E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT GNE
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 4796527.77 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.115443E+09 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.568362E+09 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.132421E+10 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.211684E+10 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.235225E+10 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.259110E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.243611E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.202538E+10 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.130497E+10 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.535515E+09 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 66524570.37 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.154415E+11 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 4796527.77 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.259110E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT GN1
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 4625850.98 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.118603E+09 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.529134E+09 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.113354E+10 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.178730E+10 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.201623E+10 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.221793E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.209454E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.174361E+10 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.111381E+10 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.484405E+09 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 74777340.35 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.133185E+11 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 4625850.98 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.221793E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT GN2
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 4667242.50 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.119745E+09 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.529874E+09 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.113395E+10 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.178767E+10 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.201550E+10 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.221791E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.209454E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.174339E+10 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.111417E+10 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.484701E+09 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 75316587.40 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.133214E+11 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 4667242.50 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.221791E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT GS1
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.184510E+09 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.357769E+09 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.765854E+09 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.128372E+10 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.181725E+10 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.200651E+10 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.221730E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.212064E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.187149E+10 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.142876E+10 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.886834E+09 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.385102E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.153257E+11 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.184510E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.221730E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT GS2
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.203879E+09 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.392886E+09 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.833450E+09 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.138915E+10 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.194462E+10 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.213086E+10 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.235266E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.224876E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.199441E+10 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.154215E+10 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.964941E+09 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.421870E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.164196E+11 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.203879E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.235266E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT MSW
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.397362E+09 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.915897E+09 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.211061E+10 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.350771E+10 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.473989E+10 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.493309E+10 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.515064E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.468516E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.402721E+10 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.298757E+10 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.173924E+10 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.663608E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.358580E+11 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.397362E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.515064E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT MNW
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 22638529.92 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.409620E+09 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.162756E+10 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.319923E+10 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.467936E+10 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.495044E+10 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.514828E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.462605E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.375215E+10 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.232377E+10 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.923264E+09 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.116221E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.317786E+11 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 22638529.92 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.514828E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT MSE
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.398764E+09 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.939685E+09 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.212574E+10 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.351291E+10 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.474725E+10 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.487994E+10 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.514119E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.467687E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.400795E+10 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.299678E+10 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.174167E+10 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.668304E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.358371E+11 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.398764E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.514119E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT MNE
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 18698707.78 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.419785E+09 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.164315E+10 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.320576E+10 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.468657E+10 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.489683E+10 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.513848E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.461776E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.373394E+10 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.233574E+10 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.923581E+09 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.108195E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.317285E+11 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 18698707.78 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.513848E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT MN1
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 38507578.19 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.416959E+09 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.141627E+10 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.259190E+10 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.379392E+10 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.408083E+10 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.433781E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.396453E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.323132E+10 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.202071E+10 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.879372E+09 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.150929E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.269231E+11 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 38507578.19 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.433781E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT MN2
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 38834115.14 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.419882E+09 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.141755E+10 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.259268E+10 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.379464E+10 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.407950E+10 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.433779E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.396455E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.323096E+10 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.202151E+10 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.880311E+09 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.152470E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.269307E+11 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 38834115.14 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.433779E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT MS1
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.547858E+09 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.969561E+09 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.190625E+10 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.290241E+10 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.385433E+10 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.406168E+10 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.433868E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.402313E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.350908E+10 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.268967E+10 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.172019E+10 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.807232E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.313301E+11 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.547858E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.433868E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT MS2
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.549973E+09 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.971509E+09 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.190720E+10 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.290310E+10 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.385504E+10 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.406035E+10 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.433866E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.402314E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.350868E+10 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.269028E+10 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.172050E+10 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.808468E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.313369E+11 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.549973E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.433866E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT TSW
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.166228E+09 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.391883E+09 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.105201E+10 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.197348E+10 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.276761E+10 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.287743E+10 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.295806E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.264435E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.219952E+10 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.152927E+10 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.770490E+09 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.237685E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.195680E+11 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.166228E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.295806E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT TNW
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 42200239.58 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.168645E+09 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.802447E+09 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.180478E+10 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.273494E+10 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.288622E+10 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.295786E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.261163E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.205043E+10 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.117421E+10 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.374866E+09 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 51249731.52 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.176595E+11 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 42200239.58 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.295786E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT TSE
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.154371E+09 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.393134E+09 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.105690E+10 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.197537E+10 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.276898E+10 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.284552E+10 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.294924E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.263766E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.218791E+10 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.153411E+10 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.767352E+09 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.230852E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.195014E+11 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.154371E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.294924E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT TNE
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 36921912.40 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.160996E+09 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.806230E+09 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.180790E+10 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.273657E+10 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.285429E+10 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.294909E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.260523E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.203995E+10 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.118076E+10 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.367080E+09 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 43382763.24 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.175884E+11 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 36921912.40 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.294909E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT TN1
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 24047272.28 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.124659E+09 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.668837E+09 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.147763E+10 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.225470E+10 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.241538E+10 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.251228E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.225117E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.177204E+10 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.100918E+10 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.304118E+09 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 24405646.62 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.148385E+11 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 24047272.28 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.251228E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT TN2
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 24164625.16 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.125920E+09 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.670114E+09 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.147817E+10 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.225505E+10 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.241443E+10 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.251208E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.225105E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.177178E+10 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.100987E+10 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.305303E+09 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 24798794.63 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.148427E+11 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 24164625.16 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.251208E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT TS1
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.143120E+09 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.359840E+09 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.925144E+09 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.164902E+10 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.228816E+10 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.240642E+10 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.251253E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.228443E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.192367E+10 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.137079E+10 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.716826E+09 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.220256E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.168002E+11 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.143120E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.251253E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT TS2
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.144201E+09 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.361445E+09 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.926183E+09 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.164947E+10 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.228850E+10 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.240547E+10 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.251233E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.228430E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.192335E+10 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.137125E+10 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.717630E+09 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.221490E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.168056E+11 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.144201E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.251233E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT GSW
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 29338438.48 | 0.394333E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 69849964.02 | 0.956837E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.169295E+09 | 0.233626E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.306051E+09 | 0.415323E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.434264E+09 | 0.596184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.474252E+09 | 0.667686E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.522172E+09 | 0.770743E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.502679E+09 | 0.750818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.446718E+09 | 0.660439E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.342374E+09 | 0.485413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.201709E+09 | 0.280896E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 73446917.92 | 0.100061E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.357215E+10 | 0.509630E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 29338438.48 | 0.394333E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.522172E+09 | 0.770743E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT GNW
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 2646386.71 | 13036873.96 | 35037375.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 25018304.78 | 0.338543E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.121676E+09 | 0.166191E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.276954E+09 | 0.372910E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.430905E+09 | 0.588991E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.478838E+09 | 0.671575E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.525250E+09 | 0.772056E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.500235E+09 | 0.743997E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.423240E+09 | 0.622598E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.278305E+09 | 0.390795E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.117106E+09 | 0.160630E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 15537137.80 | 0.208443E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.319571E+10 | 0.454574E+11 | 35037375.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 2646386.71 | 13036873.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.525250E+09 | 0.772056E+10 | 35037375.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT OFFICE
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 0.134651E+10 | 0.805304E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.121620E+10 | 0.114285E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.134651E+10 | 0.213897E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.130307E+10 | 0.308726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.134651E+10 | 0.472300E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.130307E+10 | 0.527863E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.134651E+10 | 0.579710E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.134651E+10 | 0.590897E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.130307E+10 | 0.479593E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.134651E+10 | 0.363445E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.130307E+10 | 0.225652E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.134651E+10 | 0.119362E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.158541E+11 | 0.407626E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 0.121620E+10 | 0.805304E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.134651E+10 | 0.590897E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT GNE
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 2279865.33 | 9649134.94 | 32748307.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 25491689.41 | 0.346156E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.122706E+09 | 0.168203E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.277244E+09 | 0.374985E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.430853E+09 | 0.591733E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.472899E+09 | 0.666232E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.523100E+09 | 0.772497E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.498207E+09 | 0.744380E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.420387E+09 | 0.621060E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.278748E+09 | 0.392967E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.117085E+09 | 0.161122E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 14789194.71 | 0.198813E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.318379E+10 | 0.454864E+11 | 32748307.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 2279865.33 | 9649134.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.523100E+09 | 0.772497E+10 | 32748307.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT GN1
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 1145223.53 | 13369525.54 | 3428930.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 25999036.08 | 0.357205E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.113599E+09 | 0.157396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.235784E+09 | 0.321982E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.360945E+09 | 0.500514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.401912E+09 | 0.572639E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.443955E+09 | 0.662592E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.424742E+09 | 0.641995E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.359002E+09 | 0.536812E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.236233E+09 | 0.336506E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.105177E+09 | 0.146173E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 16491155.52 | 0.224228E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.272498E+10 | 0.393609E+11 | 3428930.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 1145223.53 | 13369525.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.443955E+09 | 0.662592E+10 | 3428930.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT GN2
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 1154573.38 | 13491702.83 | 3435711.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 26248849.87 | 0.360664E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.113752E+09 | 0.157623E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.235856E+09 | 0.322116E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.360999E+09 | 0.500640E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.401743E+09 | 0.572452E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.443926E+09 | 0.662620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.424719E+09 | 0.642027E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.358935E+09 | 0.536764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.236296E+09 | 0.336626E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.105235E+09 | 0.146266E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 16609321.31 | 0.225851E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.272547E+10 | 0.393714E+11 | 3435711.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 1154573.38 | 13491702.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.443926E+09 | 0.662620E+10 | 3435711.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT GS1
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 40554861.13 | 0.556076E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 78157724.17 | 0.109056E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.163770E+09 | 0.230028E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.265539E+09 | 0.366636E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.364738E+09 | 0.509455E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.397501E+09 | 0.570153E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.441046E+09 | 0.662887E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.427419E+09 | 0.650605E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.383064E+09 | 0.577164E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.301347E+09 | 0.434847E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.191732E+09 | 0.271677E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 84499690.49 | 0.117112E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.313937E+10 | 0.455523E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 40554861.13 | 0.556076E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.441046E+09 | 0.662887E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT GS2
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 44829374.55 | 0.614942E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 85877821.08 | 0.119896E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.178464E+09 | 0.250921E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.287844E+09 | 0.398343E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.390985E+09 | 0.547057E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.422932E+09 | 0.607130E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.468857E+09 | 0.704668E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.454049E+09 | 0.690947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.408925E+09 | 0.616218E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.325779E+09 | 0.470791E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.208829E+09 | 0.296216E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 92613194.79 | 0.128377E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.336998E+10 | 0.489206E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 44829374.55 | 0.614942E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.468857E+09 | 0.704668E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT MSW
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 89074816.89 | 0.119014E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.203928E+09 | 0.278052E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.459841E+09 | 0.631409E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.739138E+09 | 0.996700E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.969812E+09 | 0.131844E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.996339E+09 | 0.138534E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.104287E+10 | 0.152153E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.960449E+09 | 0.141725E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.837918E+09 | 0.122253E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.639857E+09 | 0.894037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.382415E+09 | 0.526569E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.148396E+09 | 0.200406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.747003E+10 | 0.105113E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 89074816.89 | 0.119014E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.104287E+10 | 0.152153E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT MNW
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 6530890.57 | 61903258.79 | 39305771.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 91272456.40 | 0.123030E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.355144E+09 | 0.483276E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.675814E+09 | 0.905293E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.960022E+09 | 0.130092E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.100253E+10 | 0.139012E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.104529E+10 | 0.152039E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.950830E+09 | 0.139879E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.782613E+09 | 0.113809E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.498730E+09 | 0.691226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.203089E+09 | 0.275414E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 26027990.88 | 0.346653E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.659790E+10 | 0.926740E+11 | 39305771.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 6530890.57 | 61903258.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.104529E+10 | 0.152039E+11 | 39305771.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT MSE
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 89152060.34 | 0.119461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.208701E+09 | 0.285618E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.462188E+09 | 0.637366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.738702E+09 | 0.100132E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.969087E+09 | 0.132468E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.983170E+09 | 0.137402E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.103836E+10 | 0.152270E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.956420E+09 | 0.141833E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.831939E+09 | 0.121961E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.640440E+09 | 0.899013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.382103E+09 | 0.528324E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.149080E+09 | 0.201923E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.744934E+10 | 0.105324E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 89152060.34 | 0.119461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.103836E+10 | 0.152270E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT MNE
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 5567881.54 | 50455050.03 | 37427126.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 93326538.13 | 0.126183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.357952E+09 | 0.488874E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.676023E+09 | 0.909918E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.959576E+09 | 0.130702E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.989520E+09 | 0.137867E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.104102E+10 | 0.152142E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.947117E+09 | 0.139977E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.777226E+09 | 0.113515E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.500399E+09 | 0.696293E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.202801E+09 | 0.275914E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 24181483.46 | 0.322535E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.657471E+10 | 0.927651E+11 | 37427126.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 5567881.54 | 50455050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.104102E+10 | 0.152142E+11 | 37427126.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT MN1
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 8515680.55 | 0.115841E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 92031036.46 | 0.125783E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.306646E+09 | 0.422621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.542912E+09 | 0.736336E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.770761E+09 | 0.105850E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.817752E+09 | 0.115175E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.871848E+09 | 0.128722E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.806950E+09 | 0.120631E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.667812E+09 | 0.987380E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.430296E+09 | 0.605467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.191910E+09 | 0.263919E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 33459552.19 | 0.452071E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.554089E+10 | 0.790207E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 8515680.55 | 0.115841E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.871848E+09 | 0.128722E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT MN2
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 8587856.32 | 0.116814E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 92672922.91 | 0.126670E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.306906E+09 | 0.423019E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.543039E+09 | 0.736587E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.770859E+09 | 0.105875E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.817434E+09 | 0.115142E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.871795E+09 | 0.128728E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.806910E+09 | 0.120637E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.667697E+09 | 0.987308E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.430438E+09 | 0.605721E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.192104E+09 | 0.264208E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 33799838.69 | 0.456698E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.554224E+10 | 0.790468E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 8587856.32 | 0.116814E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.871795E+09 | 0.128728E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT MS1
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 0.121273E+09 | 0.165255E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.213404E+09 | 0.295931E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.411143E+09 | 0.573442E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.605114E+09 | 0.828257E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.779262E+09 | 0.107611E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.810005E+09 | 0.114673E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.867743E+09 | 0.128821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.814986E+09 | 0.122491E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.721847E+09 | 0.107297E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.570163E+09 | 0.810863E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.374288E+09 | 0.524371E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.178430E+09 | 0.245140E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.646766E+10 | 0.925219E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 0.121273E+09 | 0.165255E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.867743E+09 | 0.128821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT MS2
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 0.121733E+09 | 0.165903E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.213819E+09 | 0.296548E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.411319E+09 | 0.573760E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.605213E+09 | 0.828500E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.779350E+09 | 0.107636E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.809680E+09 | 0.114640E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.867680E+09 | 0.128827E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.814935E+09 | 0.122498E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.721713E+09 | 0.107290E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.570253E+09 | 0.811090E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.374332E+09 | 0.524499E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.178692E+09 | 0.245528E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.646872E+10 | 0.925473E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 0.121733E+09 | 0.165903E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.867680E+09 | 0.128827E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT TSW
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 52474401.57 | 0.438949E+09 | 0.398921E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 91563298.02 | 0.117173E+10 | 98538235.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.229706E+09 | 0.313031E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.416890E+09 | 0.557629E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.569391E+09 | 0.767072E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.585145E+09 | 0.805044E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.603251E+09 | 0.871109E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.545682E+09 | 0.796572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.460012E+09 | 0.664071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.327858E+09 | 0.453927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.170113E+09 | 0.231958E+10 | 2976724.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 61819594.46 | 0.683761E+09 | 0.220611E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.411390E+10 | 0.568986E+11 | 0.721046E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 52474401.57 | 0.438949E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.603251E+09 | 0.871109E+10 | 0.398921E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT TNW
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 34572052.15 | 29183432.45 | 0.670000E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 43841206.58 | 0.480254E+09 | 0.161254E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.175272E+09 | 0.236364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.381927E+09 | 0.507197E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.563785E+09 | 0.757312E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.588055E+09 | 0.807275E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.604410E+09 | 0.870610E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.539922E+09 | 0.786120E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.429557E+09 | 0.617989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.251979E+09 | 0.345336E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 83195836.87 | 0.110407E+10 | 15808896.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 27876197.55 | 89525827.62 | 0.436345E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.372439E+10 | 0.509851E+11 | 0.128341E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 27876197.55 | 29183432.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.604410E+09 | 0.870610E+10 | 0.670000E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT TSE
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 48981552.65 | 0.406419E+09 | 0.380214E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 91371580.74 | 0.117779E+10 | 92612560.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.230280E+09 | 0.315352E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.416407E+09 | 0.560420E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.568285E+09 | 0.770693E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.577135E+09 | 0.798971E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.599820E+09 | 0.871612E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.542855E+09 | 0.797270E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.456423E+09 | 0.662676E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.328162E+09 | 0.456853E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.169016E+09 | 0.231526E+10 | 3040643.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 59876718.59 | 0.664572E+09 | 0.213821E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.408861E+10 | 0.569025E+11 | 0.689688E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 48981552.65 | 0.406419E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.599820E+09 | 0.871612E+10 | 0.380214E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT TNE
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 31985280.81 | 18873467.15 | 0.633933E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 41462688.71 | 0.459556E+09 | 0.146574E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.175764E+09 | 0.237978E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.381877E+09 | 0.510031E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.562861E+09 | 0.760934E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.580138E+09 | 0.801190E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.601106E+09 | 0.871100E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.537280E+09 | 0.786817E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.426372E+09 | 0.616660E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.252886E+09 | 0.348183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 81237777.57 | 0.108197E+10 | 14586099.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 25341729.57 | 68964274.24 | 0.417126E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.369831E+10 | 0.509583E+11 | 0.121222E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 25341729.57 | 18873467.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.601106E+09 | 0.871100E+10 | 0.633933E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT TN1
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 20717009.64 | 12736446.59 | 0.411936E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 30281347.19 | 0.362838E+09 | 68490986.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.145246E+09 | 0.197391E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.310876E+09 | 0.415847E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.461628E+09 | 0.625179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.488479E+09 | 0.677417E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.509789E+09 | 0.741149E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.462286E+09 | 0.680218E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.368925E+09 | 0.536794E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.215440E+09 | 0.298303E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 66583185.99 | 0.899148E+09 | 496553.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 13488932.92 | 41707553.44 | 0.215543E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.309374E+10 | 0.430394E+11 | 0.696467E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 13488932.92 | 12736446.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.509789E+09 | 0.741149E+10 | 0.411936E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT TN2
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 20772812.91 | 12972401.11 | 0.412766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 30554227.17 | 0.366651E+09 | 68359027.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.145510E+09 | 0.197787E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.310953E+09 | 0.416048E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.461650E+09 | 0.625358E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.488233E+09 | 0.677233E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.509693E+09 | 0.741186E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.462212E+09 | 0.680266E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.368831E+09 | 0.536772E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.215562E+09 | 0.298529E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 66835972.56 | 0.902704E+09 | 500971.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 13594343.43 | 42805703.05 | 0.216033E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.309440E+10 | 0.430569E+11 | 0.697659E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 13594343.43 | 12972401.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.509693E+09 | 0.741186E+10 | 0.412766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT TS1
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 38781634.65 | 0.402622E+09 | 0.179859E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 81181358.63 | 0.108779E+10 | 30056054.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.200670E+09 | 0.276104E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.345977E+09 | 0.466766E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.467123E+09 | 0.635065E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.485298E+09 | 0.675167E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.508359E+09 | 0.741696E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.467821E+09 | 0.690838E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.399422E+09 | 0.583559E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.292016E+09 | 0.409003E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.157047E+09 | 0.216867E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 51757134.01 | 0.655284E+09 | 67107479.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.349545E+10 | 0.490963E+11 | 0.277023E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 38781634.65 | 0.402622E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.508359E+09 | 0.741696E+10 | 0.179859E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT TS2
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 39028469.20 | 0.405897E+09 | 0.180087E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 81529795.56 | 0.109285E+10 | 30064647.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.200874E+09 | 0.276457E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.346028E+09 | 0.466962E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.467137E+09 | 0.635248E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.485048E+09 | 0.674984E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.508257E+09 | 0.741734E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.467739E+09 | 0.690887E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.399308E+09 | 0.583534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.292078E+09 | 0.409194E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.157206E+09 | 0.217146E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 52035005.97 | 0.659070E+09 | 67297553.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.349627E+10 | 0.491193E+11 | 0.277449E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 39028469.20 | 0.405897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.508257E+09 | 0.741734E+10 | 0.180087E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT GSW
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 29338438.48 | 0.00 | 0.00 | 0.00 | 0.102400E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 69849964.02 | 0.00 | 0.00 | 0.00 | 0.246079E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.169295E+09 | 0.00 | 0.00 | 0.00 | 0.614549E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.306051E+09 | 0.00 | 0.00 | 0.00 | 0.115766E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.434264E+09 | 0.00 | 0.00 | 0.00 | 0.170296E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.474252E+09 | 0.00 | 0.00 | 0.00 | 0.188839E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.522172E+09 | 0.00 | 0.00 | 0.00 | 0.206860E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.502679E+09 | 0.00 | 0.00 | 0.00 | 0.195905E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.446718E+09 | 0.00 | 0.00 | 0.00 | 0.170843E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.342374E+09 | 0.00 | 0.00 | 0.00 | 0.126231E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.201709E+09 | 0.00 | 0.00 | 0.00 | 0.720706E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 73446917.92 | 0.00 | 0.00 | 0.00 | 0.257202E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.357215E+10 | 0.00 | 0.00 | 0.00 | 0.136883E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 29338438.48 | 0.00 | 0.00 | 0.00 | 0.102400E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.522172E+09 | 0.00 | 0.00 | 0.00 | 0.206860E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT GNW
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 2646386.71 | 0.00 | 0.00 | 0.00 | 3399480.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 25018304.78 | 0.00 | 0.00 | 0.00 | 88014005.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.121676E+09 | 0.00 | 0.00 | 0.00 | 0.440962E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.276954E+09 | 0.00 | 0.00 | 0.00 | 0.104351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.430905E+09 | 0.00 | 0.00 | 0.00 | 0.168193E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.478838E+09 | 0.00 | 0.00 | 0.00 | 0.189774E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.525250E+09 | 0.00 | 0.00 | 0.00 | 0.207084E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.500235E+09 | 0.00 | 0.00 | 0.00 | 0.194060E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.423240E+09 | 0.00 | 0.00 | 0.00 | 0.161161E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.278305E+09 | 0.00 | 0.00 | 0.00 | 0.102208E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.117106E+09 | 0.00 | 0.00 | 0.00 | 0.417501E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 15537137.80 | 0.00 | 0.00 | 0.00 | 54205412.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.319571E+10 | 0.00 | 0.00 | 0.00 | 0.122724E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 2646386.71 | 0.00 | 0.00 | 0.00 | 3399480.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.525250E+09 | 0.00 | 0.00 | 0.00 | 0.207084E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT OFFICE
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 0.134651E+10 | 0.00 | 0.00 | 0.00 | 0.204925E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.121620E+10 | 0.00 | 0.00 | 0.00 | 0.286681E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.134651E+10 | 0.00 | 0.00 | 0.00 | 0.548196E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.130307E+10 | 0.00 | 0.00 | 0.00 | 0.843260E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.134651E+10 | 0.00 | 0.00 | 0.00 | 0.132586E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.130307E+10 | 0.00 | 0.00 | 0.00 | 0.145402E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.134651E+10 | 0.00 | 0.00 | 0.00 | 0.149640E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.134651E+10 | 0.00 | 0.00 | 0.00 | 0.148325E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.130307E+10 | 0.00 | 0.00 | 0.00 | 0.119903E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.134651E+10 | 0.00 | 0.00 | 0.00 | 0.925174E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.130307E+10 | 0.00 | 0.00 | 0.00 | 0.562975E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.134651E+10 | 0.00 | 0.00 | 0.00 | 0.299477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.158541E+11 | 0.00 | 0.00 | 0.00 | 0.106292E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 0.121620E+10 | 0.00 | 0.00 | 0.00 | 0.204925E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.134651E+10 | 0.00 | 0.00 | 0.00 | 0.149640E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT GNE
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 2279865.33 | 0.00 | 0.00 | 0.00 | 2516662.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 25491689.41 | 0.00 | 0.00 | 0.00 | 89951088.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.122706E+09 | 0.00 | 0.00 | 0.00 | 0.445656E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.277244E+09 | 0.00 | 0.00 | 0.00 | 0.104697E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.430853E+09 | 0.00 | 0.00 | 0.00 | 0.168599E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.472899E+09 | 0.00 | 0.00 | 0.00 | 0.187935E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.523100E+09 | 0.00 | 0.00 | 0.00 | 0.206800E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.498207E+09 | 0.00 | 0.00 | 0.00 | 0.193790E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.420387E+09 | 0.00 | 0.00 | 0.00 | 0.160499E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.278748E+09 | 0.00 | 0.00 | 0.00 | 0.102623E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.117085E+09 | 0.00 | 0.00 | 0.00 | 0.418431E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 14789194.71 | 0.00 | 0.00 | 0.00 | 51735375.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.318379E+10 | 0.00 | 0.00 | 0.00 | 0.122577E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 2279865.33 | 0.00 | 0.00 | 0.00 | 2516662.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.523100E+09 | 0.00 | 0.00 | 0.00 | 0.206800E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT GN1
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 1145223.53 | 0.00 | 0.00 | 0.00 | 3480627.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 25999036.08 | 0.00 | 0.00 | 0.00 | 92603627.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.113599E+09 | 0.00 | 0.00 | 0.00 | 0.415536E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.235784E+09 | 0.00 | 0.00 | 0.00 | 0.897752E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.360945E+09 | 0.00 | 0.00 | 0.00 | 0.142636E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.401912E+09 | 0.00 | 0.00 | 0.00 | 0.161432E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.443955E+09 | 0.00 | 0.00 | 0.00 | 0.177398E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.424742E+09 | 0.00 | 0.00 | 0.00 | 0.166980E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.359002E+09 | 0.00 | 0.00 | 0.00 | 0.138461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.236233E+09 | 0.00 | 0.00 | 0.00 | 0.877576E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.105177E+09 | 0.00 | 0.00 | 0.00 | 0.379228E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 16491155.52 | 0.00 | 0.00 | 0.00 | 58286184.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.272498E+10 | 0.00 | 0.00 | 0.00 | 0.105935E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 1145223.53 | 0.00 | 0.00 | 0.00 | 3480627.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.443955E+09 | 0.00 | 0.00 | 0.00 | 0.177398E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT GN2
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 1154573.38 | 0.00 | 0.00 | 0.00 | 3512669.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 26248849.87 | 0.00 | 0.00 | 0.00 | 93496490.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.113752E+09 | 0.00 | 0.00 | 0.00 | 0.416122E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.235856E+09 | 0.00 | 0.00 | 0.00 | 0.898096E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.360999E+09 | 0.00 | 0.00 | 0.00 | 0.142667E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.401743E+09 | 0.00 | 0.00 | 0.00 | 0.161376E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.443926E+09 | 0.00 | 0.00 | 0.00 | 0.177398E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.424719E+09 | 0.00 | 0.00 | 0.00 | 0.166982E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.358935E+09 | 0.00 | 0.00 | 0.00 | 0.138445E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.236296E+09 | 0.00 | 0.00 | 0.00 | 0.877873E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.105235E+09 | 0.00 | 0.00 | 0.00 | 0.379465E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 16609321.31 | 0.00 | 0.00 | 0.00 | 58707266.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.272547E+10 | 0.00 | 0.00 | 0.00 | 0.105960E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 1154573.38 | 0.00 | 0.00 | 0.00 | 3512669.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.443926E+09 | 0.00 | 0.00 | 0.00 | 0.177398E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT GS1
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 40554861.13 | 0.00 | 0.00 | 0.00 | 0.143955E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 78157724.17 | 0.00 | 0.00 | 0.00 | 0.279611E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.163770E+09 | 0.00 | 0.00 | 0.00 | 0.602084E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.265539E+09 | 0.00 | 0.00 | 0.00 | 0.101818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.364738E+09 | 0.00 | 0.00 | 0.00 | 0.145251E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.397501E+09 | 0.00 | 0.00 | 0.00 | 0.160901E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.441046E+09 | 0.00 | 0.00 | 0.00 | 0.177625E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.427419E+09 | 0.00 | 0.00 | 0.00 | 0.169322E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.383064E+09 | 0.00 | 0.00 | 0.00 | 0.148843E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.301347E+09 | 0.00 | 0.00 | 0.00 | 0.112741E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.191732E+09 | 0.00 | 0.00 | 0.00 | 0.695102E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 84499690.49 | 0.00 | 0.00 | 0.00 | 0.300602E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.313937E+10 | 0.00 | 0.00 | 0.00 | 0.121864E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 40554861.13 | 0.00 | 0.00 | 0.00 | 0.143955E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.441046E+09 | 0.00 | 0.00 | 0.00 | 0.177625E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT GS2
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 44829374.55 | 0.00 | 0.00 | 0.00 | 0.159050E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 85877821.08 | 0.00 | 0.00 | 0.00 | 0.307008E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.178464E+09 | 0.00 | 0.00 | 0.00 | 0.654986E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.287844E+09 | 0.00 | 0.00 | 0.00 | 0.110130E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.390985E+09 | 0.00 | 0.00 | 0.00 | 0.155364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.422932E+09 | 0.00 | 0.00 | 0.00 | 0.170793E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.468857E+09 | 0.00 | 0.00 | 0.00 | 0.188380E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.454049E+09 | 0.00 | 0.00 | 0.00 | 0.179471E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.408925E+09 | 0.00 | 0.00 | 0.00 | 0.158548E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.325779E+09 | 0.00 | 0.00 | 0.00 | 0.121637E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.208829E+09 | 0.00 | 0.00 | 0.00 | 0.756111E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 92613194.79 | 0.00 | 0.00 | 0.00 | 0.329256E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.336998E+10 | 0.00 | 0.00 | 0.00 | 0.130497E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 44829374.55 | 0.00 | 0.00 | 0.00 | 0.159050E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.468857E+09 | 0.00 | 0.00 | 0.00 | 0.188380E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT MSW
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 89074816.89 | 0.00 | 0.00 | 0.00 | 0.308287E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.203928E+09 | 0.00 | 0.00 | 0.00 | 0.711968E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.459841E+09 | 0.00 | 0.00 | 0.00 | 0.165077E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.739138E+09 | 0.00 | 0.00 | 0.00 | 0.276857E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.969812E+09 | 0.00 | 0.00 | 0.00 | 0.377008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.996339E+09 | 0.00 | 0.00 | 0.00 | 0.393675E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.104287E+10 | 0.00 | 0.00 | 0.00 | 0.410777E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.960449E+09 | 0.00 | 0.00 | 0.00 | 0.372471E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.837918E+09 | 0.00 | 0.00 | 0.00 | 0.318930E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.639857E+09 | 0.00 | 0.00 | 0.00 | 0.234772E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.382415E+09 | 0.00 | 0.00 | 0.00 | 0.135683E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.148396E+09 | 0.00 | 0.00 | 0.00 | 0.515211E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.747003E+10 | 0.00 | 0.00 | 0.00 | 0.283880E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 89074816.89 | 0.00 | 0.00 | 0.00 | 0.308287E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.104287E+10 | 0.00 | 0.00 | 0.00 | 0.410777E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT MNW
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 6530890.57 | 0.00 | 0.00 | 0.00 | 16107639.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 91272456.40 | 0.00 | 0.00 | 0.00 | 0.318348E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.355144E+09 | 0.00 | 0.00 | 0.00 | 0.127242E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.675814E+09 | 0.00 | 0.00 | 0.00 | 0.252342E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.960022E+09 | 0.00 | 0.00 | 0.00 | 0.371934E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.100253E+10 | 0.00 | 0.00 | 0.00 | 0.394790E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.104529E+10 | 0.00 | 0.00 | 0.00 | 0.410299E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.950830E+09 | 0.00 | 0.00 | 0.00 | 0.367522E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.782613E+09 | 0.00 | 0.00 | 0.00 | 0.296954E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.498730E+09 | 0.00 | 0.00 | 0.00 | 0.182504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.203089E+09 | 0.00 | 0.00 | 0.00 | 0.720175E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 26027990.88 | 0.00 | 0.00 | 0.00 | 90192721.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.659790E+10 | 0.00 | 0.00 | 0.00 | 0.251807E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 6530890.57 | 0.00 | 0.00 | 0.00 | 16107639.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.104529E+10 | 0.00 | 0.00 | 0.00 | 0.410299E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT MSE
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 89152060.34 | 0.00 | 0.00 | 0.00 | 0.309612E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.208701E+09 | 0.00 | 0.00 | 0.00 | 0.730984E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.462188E+09 | 0.00 | 0.00 | 0.00 | 0.166356E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.738702E+09 | 0.00 | 0.00 | 0.00 | 0.277421E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.969087E+09 | 0.00 | 0.00 | 0.00 | 0.377816E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.983170E+09 | 0.00 | 0.00 | 0.00 | 0.389677E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.103836E+10 | 0.00 | 0.00 | 0.00 | 0.410283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.956420E+09 | 0.00 | 0.00 | 0.00 | 0.372045E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.831939E+09 | 0.00 | 0.00 | 0.00 | 0.317601E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.640440E+09 | 0.00 | 0.00 | 0.00 | 0.235634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.382103E+09 | 0.00 | 0.00 | 0.00 | 0.135957E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.149080E+09 | 0.00 | 0.00 | 0.00 | 0.519224E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.744934E+10 | 0.00 | 0.00 | 0.00 | 0.283877E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 89152060.34 | 0.00 | 0.00 | 0.00 | 0.309612E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.103836E+10 | 0.00 | 0.00 | 0.00 | 0.410283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT MNE
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 5567881.54 | 0.00 | 0.00 | 0.00 | 13130826.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 93326538.13 | 0.00 | 0.00 | 0.00 | 0.326458E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.357952E+09 | 0.00 | 0.00 | 0.00 | 0.128520E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.676023E+09 | 0.00 | 0.00 | 0.00 | 0.252974E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.959576E+09 | 0.00 | 0.00 | 0.00 | 0.372700E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.989520E+09 | 0.00 | 0.00 | 0.00 | 0.390731E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.104102E+10 | 0.00 | 0.00 | 0.00 | 0.409746E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.947117E+09 | 0.00 | 0.00 | 0.00 | 0.367065E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.777226E+09 | 0.00 | 0.00 | 0.00 | 0.295672E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.500399E+09 | 0.00 | 0.00 | 0.00 | 0.183534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.202801E+09 | 0.00 | 0.00 | 0.00 | 0.720780E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 24181483.46 | 0.00 | 0.00 | 0.00 | 84013788.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.657471E+10 | 0.00 | 0.00 | 0.00 | 0.251538E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 5567881.54 | 0.00 | 0.00 | 0.00 | 13130826.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.104102E+10 | 0.00 | 0.00 | 0.00 | 0.409746E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT MN1
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 8515680.55 | 0.00 | 0.00 | 0.00 | 29991897.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 92031036.46 | 0.00 | 0.00 | 0.00 | 0.324928E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.306646E+09 | 0.00 | 0.00 | 0.00 | 0.110962E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.542912E+09 | 0.00 | 0.00 | 0.00 | 0.204899E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.770761E+09 | 0.00 | 0.00 | 0.00 | 0.302316E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.817752E+09 | 0.00 | 0.00 | 0.00 | 0.326308E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.871848E+09 | 0.00 | 0.00 | 0.00 | 0.346596E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.806950E+09 | 0.00 | 0.00 | 0.00 | 0.315758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.667812E+09 | 0.00 | 0.00 | 0.00 | 0.256351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.430296E+09 | 0.00 | 0.00 | 0.00 | 0.159042E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.191910E+09 | 0.00 | 0.00 | 0.00 | 0.687462E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 33459552.19 | 0.00 | 0.00 | 0.00 | 0.117469E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.554089E+10 | 0.00 | 0.00 | 0.00 | 0.213822E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 8515680.55 | 0.00 | 0.00 | 0.00 | 29991897.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.871848E+09 | 0.00 | 0.00 | 0.00 | 0.346596E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT MN2
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 8587856.32 | 0.00 | 0.00 | 0.00 | 30246258.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 92672922.91 | 0.00 | 0.00 | 0.00 | 0.327209E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.306906E+09 | 0.00 | 0.00 | 0.00 | 0.111064E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.543039E+09 | 0.00 | 0.00 | 0.00 | 0.204964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.770859E+09 | 0.00 | 0.00 | 0.00 | 0.302378E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.817434E+09 | 0.00 | 0.00 | 0.00 | 0.326207E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.871795E+09 | 0.00 | 0.00 | 0.00 | 0.346599E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.806910E+09 | 0.00 | 0.00 | 0.00 | 0.315764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.667697E+09 | 0.00 | 0.00 | 0.00 | 0.256326E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.430438E+09 | 0.00 | 0.00 | 0.00 | 0.159107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.192104E+09 | 0.00 | 0.00 | 0.00 | 0.688207E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 33799838.69 | 0.00 | 0.00 | 0.00 | 0.118670E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.554224E+10 | 0.00 | 0.00 | 0.00 | 0.213884E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 8587856.32 | 0.00 | 0.00 | 0.00 | 30246258.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.871795E+09 | 0.00 | 0.00 | 0.00 | 0.346599E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT MS1
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 0.121273E+09 | 0.00 | 0.00 | 0.00 | 0.426585E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.213404E+09 | 0.00 | 0.00 | 0.00 | 0.756157E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.411143E+09 | 0.00 | 0.00 | 0.00 | 0.149510E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.605114E+09 | 0.00 | 0.00 | 0.00 | 0.229730E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.779262E+09 | 0.00 | 0.00 | 0.00 | 0.307507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.810005E+09 | 0.00 | 0.00 | 0.00 | 0.325168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.867743E+09 | 0.00 | 0.00 | 0.00 | 0.347094E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.814986E+09 | 0.00 | 0.00 | 0.00 | 0.320814E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.721847E+09 | 0.00 | 0.00 | 0.00 | 0.278723E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.570163E+09 | 0.00 | 0.00 | 0.00 | 0.211950E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.374288E+09 | 0.00 | 0.00 | 0.00 | 0.134590E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.178430E+09 | 0.00 | 0.00 | 0.00 | 0.628803E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.646766E+10 | 0.00 | 0.00 | 0.00 | 0.248624E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 0.121273E+09 | 0.00 | 0.00 | 0.00 | 0.426585E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.867743E+09 | 0.00 | 0.00 | 0.00 | 0.347094E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT MS2
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 0.121733E+09 | 0.00 | 0.00 | 0.00 | 0.428240E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.213819E+09 | 0.00 | 0.00 | 0.00 | 0.757690E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.411319E+09 | 0.00 | 0.00 | 0.00 | 0.149588E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.605213E+09 | 0.00 | 0.00 | 0.00 | 0.229789E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.779350E+09 | 0.00 | 0.00 | 0.00 | 0.307569E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.809680E+09 | 0.00 | 0.00 | 0.00 | 0.325067E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.867680E+09 | 0.00 | 0.00 | 0.00 | 0.347098E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.814935E+09 | 0.00 | 0.00 | 0.00 | 0.320821E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.721713E+09 | 0.00 | 0.00 | 0.00 | 0.278697E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.570253E+09 | 0.00 | 0.00 | 0.00 | 0.212003E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.374332E+09 | 0.00 | 0.00 | 0.00 | 0.134617E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.178692E+09 | 0.00 | 0.00 | 0.00 | 0.629776E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.646872E+10 | 0.00 | 0.00 | 0.00 | 0.248682E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 0.121733E+09 | 0.00 | 0.00 | 0.00 | 0.428240E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.867680E+09 | 0.00 | 0.00 | 0.00 | 0.347098E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT TSW
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 52474401.57 | 0.00 | 0.00 | 0.00 | 0.113753E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 91563298.02 | 0.00 | 0.00 | 0.00 | 0.300319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.229706E+09 | 0.00 | 0.00 | 0.00 | 0.822303E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.416890E+09 | 0.00 | 0.00 | 0.00 | 0.155659E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.569391E+09 | 0.00 | 0.00 | 0.00 | 0.219821E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.585145E+09 | 0.00 | 0.00 | 0.00 | 0.229228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.603251E+09 | 0.00 | 0.00 | 0.00 | 0.235481E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.545682E+09 | 0.00 | 0.00 | 0.00 | 0.209867E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.460012E+09 | 0.00 | 0.00 | 0.00 | 0.173951E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.327858E+09 | 0.00 | 0.00 | 0.00 | 0.120142E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.170113E+09 | 0.00 | 0.00 | 0.00 | 0.600377E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 61819594.46 | 0.00 | 0.00 | 0.00 | 0.175866E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.411390E+10 | 0.00 | 0.00 | 0.00 | 0.154541E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 52474401.57 | 0.00 | 0.00 | 0.00 | 0.113753E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.603251E+09 | 0.00 | 0.00 | 0.00 | 0.235481E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT TNW
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 34572052.15 | 0.00 | 0.00 | 0.00 | 7628187.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 43841206.58 | 0.00 | 0.00 | 0.00 | 0.124804E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.175272E+09 | 0.00 | 0.00 | 0.00 | 0.627175E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.381927E+09 | 0.00 | 0.00 | 0.00 | 0.142286E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.563785E+09 | 0.00 | 0.00 | 0.00 | 0.217116E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.588055E+09 | 0.00 | 0.00 | 0.00 | 0.229817E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.604410E+09 | 0.00 | 0.00 | 0.00 | 0.235345E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.539922E+09 | 0.00 | 0.00 | 0.00 | 0.207170E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.429557E+09 | 0.00 | 0.00 | 0.00 | 0.162087E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.251979E+09 | 0.00 | 0.00 | 0.00 | 0.922229E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 83195836.87 | 0.00 | 0.00 | 0.00 | 0.291670E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 27876197.55 | 0.00 | 0.00 | 0.00 | 23373533.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.372439E+10 | 0.00 | 0.00 | 0.00 | 0.139351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 27876197.55 | 0.00 | 0.00 | 0.00 | 7628187.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.604410E+09 | 0.00 | 0.00 | 0.00 | 0.235345E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT TSE
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 48981552.65 | 0.00 | 0.00 | 0.00 | 0.105390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 91371580.74 | 0.00 | 0.00 | 0.00 | 0.301762E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.230280E+09 | 0.00 | 0.00 | 0.00 | 0.826615E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.416407E+09 | 0.00 | 0.00 | 0.00 | 0.155896E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.568285E+09 | 0.00 | 0.00 | 0.00 | 0.220070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.577135E+09 | 0.00 | 0.00 | 0.00 | 0.226839E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.599820E+09 | 0.00 | 0.00 | 0.00 | 0.234942E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.542855E+09 | 0.00 | 0.00 | 0.00 | 0.209480E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.456423E+09 | 0.00 | 0.00 | 0.00 | 0.173148E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.328162E+09 | 0.00 | 0.00 | 0.00 | 0.120595E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.169016E+09 | 0.00 | 0.00 | 0.00 | 0.598336E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 59876718.59 | 0.00 | 0.00 | 0.00 | 0.170976E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.408861E+10 | 0.00 | 0.00 | 0.00 | 0.154128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 48981552.65 | 0.00 | 0.00 | 0.00 | 0.105390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.599820E+09 | 0.00 | 0.00 | 0.00 | 0.234942E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT TNE
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 31985280.81 | 0.00 | 0.00 | 0.00 | 4936631.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 41462688.71 | 0.00 | 0.00 | 0.00 | 0.119533E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.175764E+09 | 0.00 | 0.00 | 0.00 | 0.630466E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.381877E+09 | 0.00 | 0.00 | 0.00 | 0.142603E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.562861E+09 | 0.00 | 0.00 | 0.00 | 0.217371E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.580138E+09 | 0.00 | 0.00 | 0.00 | 0.227415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.601106E+09 | 0.00 | 0.00 | 0.00 | 0.234798E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.537280E+09 | 0.00 | 0.00 | 0.00 | 0.206795E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.426372E+09 | 0.00 | 0.00 | 0.00 | 0.161358E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.252886E+09 | 0.00 | 0.00 | 0.00 | 0.927874E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 81237777.57 | 0.00 | 0.00 | 0.00 | 0.285843E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 25341729.57 | 0.00 | 0.00 | 0.00 | 18041033.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.369831E+10 | 0.00 | 0.00 | 0.00 | 0.138901E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 25341729.57 | 0.00 | 0.00 | 0.00 | 4936631.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.601106E+09 | 0.00 | 0.00 | 0.00 | 0.234798E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT TN1
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 20717009.64 | 0.00 | 0.00 | 0.00 | 3330262.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 30281347.19 | 0.00 | 0.00 | 0.00 | 94377650.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.145246E+09 | 0.00 | 0.00 | 0.00 | 0.523591E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.310876E+09 | 0.00 | 0.00 | 0.00 | 0.116676E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.461628E+09 | 0.00 | 0.00 | 0.00 | 0.179308E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.488479E+09 | 0.00 | 0.00 | 0.00 | 0.192690E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.509789E+09 | 0.00 | 0.00 | 0.00 | 0.200249E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.462286E+09 | 0.00 | 0.00 | 0.00 | 0.178889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.368925E+09 | 0.00 | 0.00 | 0.00 | 0.140311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.215440E+09 | 0.00 | 0.00 | 0.00 | 0.793743E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 66583185.99 | 0.00 | 0.00 | 0.00 | 0.237535E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 13488932.92 | 0.00 | 0.00 | 0.00 | 10916713.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.309374E+10 | 0.00 | 0.00 | 0.00 | 0.117447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 13488932.92 | 0.00 | 0.00 | 0.00 | 3330262.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.509789E+09 | 0.00 | 0.00 | 0.00 | 0.200249E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT TN2
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 20772812.91 | 0.00 | 0.00 | 0.00 | 3391812.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 30554227.17 | 0.00 | 0.00 | 0.00 | 95365634.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.145510E+09 | 0.00 | 0.00 | 0.00 | 0.524604E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.310953E+09 | 0.00 | 0.00 | 0.00 | 0.116721E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.461650E+09 | 0.00 | 0.00 | 0.00 | 0.179340E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.488233E+09 | 0.00 | 0.00 | 0.00 | 0.192619E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.509693E+09 | 0.00 | 0.00 | 0.00 | 0.200238E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.462212E+09 | 0.00 | 0.00 | 0.00 | 0.178884E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.368831E+09 | 0.00 | 0.00 | 0.00 | 0.140295E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.215562E+09 | 0.00 | 0.00 | 0.00 | 0.794312E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 66835972.56 | 0.00 | 0.00 | 0.00 | 0.238467E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 13594343.43 | 0.00 | 0.00 | 0.00 | 11204451.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.309440E+10 | 0.00 | 0.00 | 0.00 | 0.117483E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 13594343.43 | 0.00 | 0.00 | 0.00 | 3391812.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.509693E+09 | 0.00 | 0.00 | 0.00 | 0.200238E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT TS1
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 38781634.65 | 0.00 | 0.00 | 0.00 | 0.104338E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 81181358.63 | 0.00 | 0.00 | 0.00 | 0.278659E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.200670E+09 | 0.00 | 0.00 | 0.00 | 0.724474E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.345977E+09 | 0.00 | 0.00 | 0.00 | 0.130304E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.467123E+09 | 0.00 | 0.00 | 0.00 | 0.182104E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.485298E+09 | 0.00 | 0.00 | 0.00 | 0.192112E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.508359E+09 | 0.00 | 0.00 | 0.00 | 0.200417E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.467821E+09 | 0.00 | 0.00 | 0.00 | 0.181661E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.399422E+09 | 0.00 | 0.00 | 0.00 | 0.152424E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.292016E+09 | 0.00 | 0.00 | 0.00 | 0.107877E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.157047E+09 | 0.00 | 0.00 | 0.00 | 0.559779E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 51757134.01 | 0.00 | 0.00 | 0.00 | 0.168499E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.349545E+10 | 0.00 | 0.00 | 0.00 | 0.133047E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 38781634.65 | 0.00 | 0.00 | 0.00 | 0.104338E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.508359E+09 | 0.00 | 0.00 | 0.00 | 0.200417E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT TS2
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 39028469.20 | 0.00 | 0.00 | 0.00 | 0.105173E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 81529795.56 | 0.00 | 0.00 | 0.00 | 0.279915E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.200874E+09 | 0.00 | 0.00 | 0.00 | 0.725309E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.346028E+09 | 0.00 | 0.00 | 0.00 | 0.130344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.467137E+09 | 0.00 | 0.00 | 0.00 | 0.182137E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.485048E+09 | 0.00 | 0.00 | 0.00 | 0.192042E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.508257E+09 | 0.00 | 0.00 | 0.00 | 0.200407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.467739E+09 | 0.00 | 0.00 | 0.00 | 0.181656E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.399308E+09 | 0.00 | 0.00 | 0.00 | 0.152404E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.292078E+09 | 0.00 | 0.00 | 0.00 | 0.107917E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.157206E+09 | 0.00 | 0.00 | 0.00 | 0.560424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 52035005.97 | 0.00 | 0.00 | 0.00 | 0.169455E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.349627E+10 | 0.00 | 0.00 | 0.00 | 0.133093E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 39028469.20 | 0.00 | 0.00 | 0.00 | 0.105173E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.508257E+09 | 0.00 | 0.00 | 0.00 | 0.200407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: G SW APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.619846E+09 | 298489.98 | 0.00 | 1116232.97 | 0.00 | 0.00 | 0.259172E+09 | 0.00 | 0.35 |
| February | 0.311289E+09 | 13821041.95 | 0.00 | 1280961.35 | 0.00 | 0.00 | 0.219748E+09 | 0.00 | 0.36 |
| March | 42330870.02 | 0.174275E+09 | 0.00 | 1242858.90 | 0.00 | 0.00 | 0.181818E+09 | 0.00 | 0.36 |
| April | 0.00 | 0.625322E+09 | 0.00 | 336887.71 | 0.00 | 0.00 | 19130988.69 | 0.00 | 0.36 |
| May | 0.00 | 0.139170E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| June | 0.00 | 0.191305E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| July | 0.00 | 0.241192E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| August | 0.00 | 0.239874E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| September | 0.00 | 0.187142E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| October | 0.00 | 0.588547E+09 | 0.00 | 781662.97 | 0.00 | 0.00 | 41117021.36 | 0.00 | 0.36 |
| November | 0.00 | 90035234.03 | 0.00 | 2959916.45 | 0.00 | 0.00 | 0.364585E+09 | 0.00 | 0.36 |
| December | 0.301815E+09 | 1671817.97 | 0.00 | 2517725.95 | 0.00 | 0.00 | 0.515559E+09 | 0.00 | 0.35 |
| Annual Sum or Average | 0.127528E+10 | 0.114808E+11 | 0.00 | 10236246.30 | 0.00 | 0.00 | 0.160113E+10 | 0.00 | 0.36 |
| Minimum of Months | 0.00 | 298489.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
| Maximum of Months | 0.619846E+09 | 0.241192E+10 | 0.00 | 2959916.45 | 0.00 | 0.00 | 0.515559E+09 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: G NW APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.781801E+09 | 115913.90 | 0.00 | 42012.12 | 219444.25 | 0.00 | 11900033.37 | 0.00 | 0.35 |
| February | 0.419560E+09 | 10758218.80 | 0.00 | 400846.22 | 741.92 | 0.00 | 88165813.15 | 0.00 | 0.36 |
| March | 93133371.95 | 0.162569E+09 | 0.00 | 830393.37 | 0.00 | 0.00 | 0.140870E+09 | 0.00 | 0.36 |
| April | 0.00 | 0.616941E+09 | 0.00 | 303311.23 | 0.00 | 0.00 | 19824041.27 | 0.00 | 0.36 |
| May | 0.00 | 0.139064E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| June | 0.00 | 0.191546E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| July | 0.00 | 0.241442E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| August | 0.00 | 0.239334E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| September | 0.00 | 0.184778E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| October | 0.00 | 0.557602E+09 | 0.00 | 673085.64 | 0.00 | 0.00 | 48984566.90 | 0.00 | 0.36 |
| November | 46925146.09 | 80044511.45 | 0.00 | 1705529.30 | 0.00 | 0.00 | 0.344730E+09 | 0.00 | 0.36 |
| December | 0.630814E+09 | 1490675.49 | 0.00 | 612085.69 | 10879.57 | 0.00 | 0.160475E+09 | 0.00 | 0.35 |
| Annual Sum or Average | 0.197223E+10 | 0.113912E+11 | 0.00 | 4567263.57 | 231065.75 | 0.00 | 0.814950E+09 | 0.00 | 0.36 |
| Minimum of Months | 0.00 | 115913.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
| Maximum of Months | 0.781801E+09 | 0.241442E+10 | 0.00 | 1705529.30 | 219444.25 | 0.00 | 0.344730E+09 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: OFFICE
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.119435E+10 | 0.00 | 0.00 | 1129457.18 | 0.00 | 0.00 | 0.179956E+09 | 0.00 | 0.52 |
| February | 0.815537E+09 | 7212946.41 | 0.00 | 1276755.32 | 181786.28 | 0.00 | 0.108995E+09 | 0.00 | 0.52 |
| March | 0.498619E+09 | 97979699.39 | 0.00 | 1385437.76 | 19066308.26 | 0.00 | 61899340.41 | 0.00 | 0.53 |
| April | 0.155363E+09 | 0.318522E+09 | 0.00 | 521220.88 | 0.114672E+09 | 0.00 | 8604911.17 | 0.00 | 0.53 |
| May | 51077293.87 | 0.829741E+09 | 0.00 | 103642.36 | 0.273768E+09 | 0.00 | 1693620.80 | 0.00 | 0.54 |
| June | 28905061.20 | 0.110073E+10 | 0.00 | 38310.08 | 0.433606E+09 | 0.00 | 1522790.14 | 0.00 | 0.54 |
| July | 11815382.44 | 0.147026E+10 | 0.00 | 30938.86 | 0.378699E+09 | 0.00 | 40586.49 | 0.00 | 0.55 |
| August | 25384413.72 | 0.142308E+10 | 0.00 | 58313.04 | 0.388604E+09 | 0.00 | 253716.10 | 0.00 | 0.54 |
| September | 62000578.62 | 0.966712E+09 | 0.00 | 176790.32 | 0.234401E+09 | 0.00 | 2736569.39 | 0.00 | 0.54 |
| October | 0.369862E+09 | 0.327646E+09 | 0.00 | 1044177.11 | 40094255.64 | 0.00 | 47433194.35 | 0.00 | 0.53 |
| November | 0.792981E+09 | 53310337.14 | 0.00 | 1880060.67 | 2668671.41 | 0.00 | 76360668.89 | 0.00 | 0.53 |
| December | 0.116855E+10 | 35152.36 | 0.00 | 1831620.45 | 0.00 | 0.00 | 0.170465E+09 | 0.00 | 0.52 |
| Annual Sum or Average | 0.517444E+10 | 0.659523E+10 | 0.00 | 9476724.03 | 0.188576E+10 | 0.00 | 0.659962E+09 | 0.00 | 0.53 |
| Minimum of Months | 11815382.44 | 0.00 | 0.00 | 30938.86 | 0.00 | 0.00 | 40586.49 | 0.00 | 0.52 |
| Maximum of Months | 0.119435E+10 | 0.147026E+10 | 0.00 | 1880060.67 | 0.433606E+09 | 0.00 | 0.179956E+09 | 0.00 | 0.55 |
Report: MechanicalVentilationLoadsMonthly
For: G NE APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.787211E+09 | 115166.90 | 0.00 | 27200.63 | 233211.26 | 0.00 | 8342195.16 | 0.00 | 0.35 |
| February | 0.417131E+09 | 10873848.62 | 0.00 | 429349.44 | 0.00 | 0.00 | 94141509.04 | 0.00 | 0.36 |
| March | 88347197.50 | 0.164629E+09 | 0.00 | 877742.10 | 0.00 | 0.00 | 0.145880E+09 | 0.00 | 0.36 |
| April | 0.00 | 0.619540E+09 | 0.00 | 317450.18 | 0.00 | 0.00 | 19821658.86 | 0.00 | 0.36 |
| May | 0.00 | 0.139215E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| June | 0.00 | 0.191308E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| July | 0.00 | 0.241463E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| August | 0.00 | 0.239363E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| September | 0.00 | 0.184666E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| October | 0.00 | 0.559715E+09 | 0.00 | 682247.54 | 0.00 | 0.00 | 49314742.58 | 0.00 | 0.36 |
| November | 39534298.72 | 81273513.29 | 0.00 | 1789861.15 | 0.00 | 0.00 | 0.353223E+09 | 0.00 | 0.36 |
| December | 0.626875E+09 | 1485064.22 | 0.00 | 579342.24 | 0.00 | 0.00 | 0.167552E+09 | 0.00 | 0.35 |
| Annual Sum or Average | 0.195910E+10 | 0.113978E+11 | 0.00 | 4703193.28 | 233211.26 | 0.00 | 0.838275E+09 | 0.00 | 0.36 |
| Minimum of Months | 0.00 | 115166.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
| Maximum of Months | 0.787211E+09 | 0.241463E+10 | 0.00 | 1789861.15 | 233211.26 | 0.00 | 0.353223E+09 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: G N1 APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.778489E+09 | 107495.03 | 0.00 | 72904.26 | 229213.31 | 0.00 | 46537918.12 | 0.00 | 0.35 |
| February | 0.390190E+09 | 10378347.90 | 0.00 | 552020.66 | 0.00 | 0.00 | 0.139417E+09 | 0.00 | 0.36 |
| March | 42434919.97 | 0.160611E+09 | 0.00 | 1065272.21 | 0.00 | 0.00 | 0.190319E+09 | 0.00 | 0.36 |
| April | 0.00 | 0.607995E+09 | 0.00 | 318976.97 | 0.00 | 0.00 | 19519555.71 | 0.00 | 0.36 |
| May | 0.00 | 0.137127E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| June | 0.00 | 0.187958E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| July | 0.00 | 0.237061E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| August | 0.00 | 0.233714E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| September | 0.00 | 0.179540E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| October | 0.00 | 0.537305E+09 | 0.00 | 674064.29 | 0.00 | 0.00 | 51268269.73 | 0.00 | 0.36 |
| November | 7470597.33 | 77666661.75 | 0.00 | 1881365.75 | 0.00 | 0.00 | 0.384415E+09 | 0.00 | 0.36 |
| December | 0.538653E+09 | 1456694.64 | 0.00 | 792594.31 | 0.00 | 0.00 | 0.276246E+09 | 0.00 | 0.35 |
| Annual Sum or Average | 0.175724E+10 | 0.111495E+11 | 0.00 | 5357198.45 | 229213.31 | 0.00 | 0.110772E+10 | 0.00 | 0.36 |
| Minimum of Months | 0.00 | 107495.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
| Maximum of Months | 0.778489E+09 | 0.237061E+10 | 0.00 | 1881365.75 | 229213.31 | 0.00 | 0.384415E+09 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: G N2 APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.778369E+09 | 107516.06 | 0.00 | 73249.60 | 225898.49 | 0.00 | 46945473.82 | 0.00 | 0.35 |
| February | 0.388137E+09 | 10395239.86 | 0.00 | 557530.97 | 0.00 | 0.00 | 0.141725E+09 | 0.00 | 0.36 |
| March | 42438653.89 | 0.160696E+09 | 0.00 | 1066729.34 | 0.00 | 0.00 | 0.190286E+09 | 0.00 | 0.36 |
| April | 0.00 | 0.608093E+09 | 0.00 | 318958.08 | 0.00 | 0.00 | 19518326.56 | 0.00 | 0.36 |
| May | 0.00 | 0.137134E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| June | 0.00 | 0.187946E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| July | 0.00 | 0.237066E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| August | 0.00 | 0.233720E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| September | 0.00 | 0.179537E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| October | 0.00 | 0.537405E+09 | 0.00 | 674188.26 | 0.00 | 0.00 | 51273357.12 | 0.00 | 0.36 |
| November | 7319403.26 | 77710029.23 | 0.00 | 1882636.91 | 0.00 | 0.00 | 0.384596E+09 | 0.00 | 0.36 |
| December | 0.538215E+09 | 1456570.91 | 0.00 | 796848.67 | 0.00 | 0.00 | 0.276865E+09 | 0.00 | 0.35 |
| Annual Sum or Average | 0.175448E+10 | 0.111499E+11 | 0.00 | 5370141.83 | 225898.49 | 0.00 | 0.111121E+10 | 0.00 | 0.36 |
| Minimum of Months | 0.00 | 107516.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
| Maximum of Months | 0.778369E+09 | 0.237066E+10 | 0.00 | 1882636.91 | 225898.49 | 0.00 | 0.384596E+09 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: G S1 APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.441699E+09 | 288644.26 | 0.00 | 1710589.53 | 0.00 | 0.00 | 0.462167E+09 | 0.00 | 0.35 |
| February | 0.168836E+09 | 13757472.67 | 0.00 | 1846554.18 | 0.00 | 0.00 | 0.372211E+09 | 0.00 | 0.36 |
| March | 8915046.46 | 0.173769E+09 | 0.00 | 1561620.54 | 0.00 | 0.00 | 0.209673E+09 | 0.00 | 0.36 |
| April | 0.00 | 0.618314E+09 | 0.00 | 357133.59 | 0.00 | 0.00 | 18734457.84 | 0.00 | 0.36 |
| May | 0.00 | 0.137393E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| June | 0.00 | 0.187799E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| July | 0.00 | 0.236959E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| August | 0.00 | 0.234601E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| September | 0.00 | 0.182717E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| October | 0.00 | 0.574759E+09 | 0.00 | 797419.80 | 0.00 | 0.00 | 41972313.78 | 0.00 | 0.36 |
| November | 0.00 | 88785103.43 | 0.00 | 3138418.87 | 0.00 | 0.00 | 0.361462E+09 | 0.00 | 0.36 |
| December | 87759049.98 | 1646898.17 | 0.00 | 3428209.47 | 0.00 | 0.00 | 0.737210E+09 | 0.00 | 0.35 |
| Annual Sum or Average | 0.707209E+09 | 0.112660E+11 | 0.00 | 12839945.98 | 0.00 | 0.00 | 0.220343E+10 | 0.00 | 0.36 |
| Minimum of Months | 0.00 | 288644.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
| Maximum of Months | 0.441699E+09 | 0.236959E+10 | 0.00 | 3428209.47 | 0.00 | 0.00 | 0.737210E+09 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: G S2 APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.415348E+09 | 288167.97 | 0.00 | 1868397.27 | 0.00 | 0.00 | 0.488802E+09 | 0.00 | 0.35 |
| February | 0.143510E+09 | 13958856.40 | 0.00 | 2068629.43 | 0.00 | 0.00 | 0.395314E+09 | 0.00 | 0.36 |
| March | 2766363.55 | 0.177170E+09 | 0.00 | 1714857.65 | 0.00 | 0.00 | 0.210212E+09 | 0.00 | 0.36 |
| April | 0.00 | 0.628778E+09 | 0.00 | 397730.93 | 0.00 | 0.00 | 17645254.37 | 0.00 | 0.36 |
| May | 0.00 | 0.139493E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| June | 0.00 | 0.190678E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| July | 0.00 | 0.241087E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| August | 0.00 | 0.238945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| September | 0.00 | 0.186704E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| October | 0.00 | 0.590991E+09 | 0.00 | 862823.03 | 0.00 | 0.00 | 38128016.11 | 0.00 | 0.36 |
| November | 0.00 | 89952279.97 | 0.00 | 3440709.92 | 0.00 | 0.00 | 0.353490E+09 | 0.00 | 0.36 |
| December | 74602151.23 | 1650997.29 | 0.00 | 3719900.63 | 0.00 | 0.00 | 0.748634E+09 | 0.00 | 0.35 |
| Annual Sum or Average | 0.636226E+09 | 0.114718E+11 | 0.00 | 14073048.86 | 0.00 | 0.00 | 0.225223E+10 | 0.00 | 0.36 |
| Minimum of Months | 0.00 | 288167.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
| Maximum of Months | 0.415348E+09 | 0.241087E+10 | 0.00 | 3719900.63 | 0.00 | 0.00 | 0.748634E+09 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: M SW APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.114514E+10 | 596578.33 | 0.00 | 3129065.64 | 0.00 | 0.00 | 0.622600E+09 | 0.00 | 0.35 |
| February | 0.483276E+09 | 29552535.71 | 0.00 | 3783273.57 | 0.00 | 0.00 | 0.570086E+09 | 0.00 | 0.36 |
| March | 18548856.75 | 0.367400E+09 | 0.00 | 3535041.96 | 0.00 | 0.00 | 0.398375E+09 | 0.00 | 0.36 |
| April | 0.00 | 0.128734E+10 | 0.00 | 783551.16 | 0.00 | 0.00 | 34652653.63 | 0.00 | 0.36 |
| May | 0.00 | 0.280438E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| June | 0.00 | 0.380840E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| July | 0.00 | 0.469718E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| August | 0.00 | 0.461755E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| September | 0.00 | 0.357860E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| October | 68465.40 | 0.112051E+10 | 0.00 | 1284378.10 | 0.00 | 0.00 | 0.100519E+09 | 0.00 | 0.36 |
| November | 54354207.80 | 0.180028E+09 | 0.00 | 4717125.14 | 0.00 | 0.00 | 0.706413E+09 | 0.00 | 0.36 |
| December | 0.870447E+09 | 3416181.54 | 0.00 | 4592541.69 | 0.00 | 0.00 | 0.739115E+09 | 0.00 | 0.35 |
| Annual Sum or Average | 0.257184E+10 | 0.224950E+11 | 0.00 | 21824977.26 | 0.00 | 0.00 | 0.317176E+10 | 0.00 | 0.36 |
| Minimum of Months | 0.00 | 596578.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
| Maximum of Months | 0.114514E+10 | 0.469718E+10 | 0.00 | 4717125.14 | 0.00 | 0.00 | 0.739115E+09 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: M NW APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.155349E+10 | 256938.60 | 0.00 | 203320.05 | 269341.85 | 0.00 | 68277912.93 | 0.00 | 0.35 |
| February | 0.719955E+09 | 23977810.79 | 0.00 | 1608277.03 | 0.00 | 0.00 | 0.319871E+09 | 0.00 | 0.36 |
| March | 71437446.42 | 0.347422E+09 | 0.00 | 2798186.84 | 0.00 | 0.00 | 0.362672E+09 | 0.00 | 0.36 |
| April | 0.00 | 0.127329E+10 | 0.00 | 728086.63 | 0.00 | 0.00 | 35488077.87 | 0.00 | 0.36 |
| May | 0.00 | 0.280038E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| June | 0.00 | 0.380941E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| July | 0.00 | 0.469736E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| August | 0.00 | 0.459985E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| September | 0.00 | 0.351843E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| October | 5020293.21 | 0.105030E+10 | 0.00 | 1062278.21 | 0.00 | 0.00 | 0.114187E+09 | 0.00 | 0.36 |
| November | 0.255653E+09 | 0.157596E+09 | 0.00 | 2364717.71 | 0.00 | 0.00 | 0.550138E+09 | 0.00 | 0.36 |
| December | 0.130448E+10 | 2583829.28 | 0.00 | 976851.25 | 629598.11 | 0.00 | 0.239269E+09 | 0.00 | 0.35 |
| Annual Sum or Average | 0.391004E+10 | 0.222809E+11 | 0.00 | 9741717.72 | 898939.97 | 0.00 | 0.168990E+10 | 0.00 | 0.36 |
| Minimum of Months | 0.00 | 256938.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
| Maximum of Months | 0.155349E+10 | 0.469736E+10 | 0.00 | 2798186.84 | 629598.11 | 0.00 | 0.550138E+09 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: M SE APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.111502E+10 | 582452.17 | 0.00 | 3122104.86 | 0.00 | 0.00 | 0.658100E+09 | 0.00 | 0.35 |
| February | 0.455439E+09 | 29610631.51 | 0.00 | 4084292.60 | 0.00 | 0.00 | 0.599107E+09 | 0.00 | 0.36 |
| March | 13562784.14 | 0.370628E+09 | 0.00 | 3733343.68 | 0.00 | 0.00 | 0.403531E+09 | 0.00 | 0.36 |
| April | 0.00 | 0.129215E+10 | 0.00 | 819453.81 | 0.00 | 0.00 | 34682997.60 | 0.00 | 0.36 |
| May | 0.00 | 0.280868E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| June | 0.00 | 0.380513E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| July | 0.00 | 0.469864E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| August | 0.00 | 0.461910E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| September | 0.00 | 0.357718E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| October | 137844.37 | 0.112519E+10 | 0.00 | 1319993.08 | 0.00 | 0.00 | 0.101271E+09 | 0.00 | 0.36 |
| November | 54152805.47 | 0.182124E+09 | 0.00 | 4950545.71 | 0.00 | 0.00 | 0.708444E+09 | 0.00 | 0.36 |
| December | 0.847410E+09 | 3388115.61 | 0.00 | 4648198.95 | 0.00 | 0.00 | 0.765809E+09 | 0.00 | 0.35 |
| Annual Sum or Average | 0.248572E+10 | 0.225124E+11 | 0.00 | 22677932.70 | 0.00 | 0.00 | 0.327094E+10 | 0.00 | 0.36 |
| Minimum of Months | 0.00 | 582452.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
| Maximum of Months | 0.111502E+10 | 0.469864E+10 | 0.00 | 4950545.71 | 0.00 | 0.00 | 0.765809E+09 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: M NE APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.156831E+10 | 250131.09 | 0.00 | 157102.18 | 284747.29 | 0.00 | 59186371.51 | 0.00 | 0.35 |
| February | 0.688281E+09 | 24163098.78 | 0.00 | 1763497.60 | 0.00 | 0.00 | 0.357677E+09 | 0.00 | 0.36 |
| March | 59126505.70 | 0.351241E+09 | 0.00 | 2963689.81 | 0.00 | 0.00 | 0.375549E+09 | 0.00 | 0.36 |
| April | 0.00 | 0.127790E+10 | 0.00 | 766745.06 | 0.00 | 0.00 | 35571665.31 | 0.00 | 0.36 |
| May | 0.00 | 0.280343E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| June | 0.00 | 0.380496E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| July | 0.00 | 0.469766E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| August | 0.00 | 0.460032E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| September | 0.00 | 0.351607E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| October | 5644494.22 | 0.105629E+10 | 0.00 | 1105693.53 | 0.00 | 0.00 | 0.114787E+09 | 0.00 | 0.36 |
| November | 0.233776E+09 | 0.160844E+09 | 0.00 | 2542802.86 | 0.00 | 0.00 | 0.575708E+09 | 0.00 | 0.36 |
| December | 0.131790E+10 | 2434470.94 | 0.00 | 892426.10 | 696788.23 | 0.00 | 0.233378E+09 | 0.00 | 0.35 |
| Annual Sum or Average | 0.387303E+10 | 0.222956E+11 | 0.00 | 10191957.15 | 981535.53 | 0.00 | 0.175186E+10 | 0.00 | 0.36 |
| Minimum of Months | 0.00 | 250131.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
| Maximum of Months | 0.156831E+10 | 0.469766E+10 | 0.00 | 2963689.81 | 696788.23 | 0.00 | 0.575708E+09 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: M N1 APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.144205E+10 | 240484.28 | 0.00 | 586194.16 | 207142.67 | 0.00 | 0.264980E+09 | 0.00 | 0.35 |
| February | 0.508978E+09 | 22847726.90 | 0.00 | 2198917.70 | 0.00 | 0.00 | 0.564667E+09 | 0.00 | 0.36 |
| March | 10239039.57 | 0.338138E+09 | 0.00 | 3120062.90 | 0.00 | 0.00 | 0.424078E+09 | 0.00 | 0.36 |
| April | 0.00 | 0.124352E+10 | 0.00 | 727974.73 | 0.00 | 0.00 | 36213018.45 | 0.00 | 0.36 |
| May | 0.00 | 0.275037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| June | 0.00 | 0.373116E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| July | 0.00 | 0.462650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| August | 0.00 | 0.451758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| September | 0.00 | 0.344478E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| October | 285230.66 | 0.102394E+10 | 0.00 | 1171151.85 | 0.00 | 0.00 | 0.116989E+09 | 0.00 | 0.36 |
| November | 77537884.29 | 0.153680E+09 | 0.00 | 3133158.04 | 0.00 | 0.00 | 0.722339E+09 | 0.00 | 0.36 |
| December | 0.111987E+10 | 2908944.58 | 0.00 | 1545305.87 | 95089.20 | 0.00 | 0.494087E+09 | 0.00 | 0.35 |
| Annual Sum or Average | 0.315895E+10 | 0.218557E+11 | 0.00 | 12482765.26 | 302231.86 | 0.00 | 0.262335E+10 | 0.00 | 0.36 |
| Minimum of Months | 0.00 | 240484.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
| Maximum of Months | 0.144205E+10 | 0.462650E+10 | 0.00 | 3133158.04 | 207142.67 | 0.00 | 0.722339E+09 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: M N2 APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.144107E+10 | 252276.54 | 0.00 | 590045.62 | 187504.49 | 0.00 | 0.266702E+09 | 0.00 | 0.35 |
| February | 0.507526E+09 | 22881206.46 | 0.00 | 2214610.93 | 0.00 | 0.00 | 0.566320E+09 | 0.00 | 0.36 |
| March | 10117340.22 | 0.338272E+09 | 0.00 | 3121929.94 | 0.00 | 0.00 | 0.424210E+09 | 0.00 | 0.36 |
| April | 0.00 | 0.124366E+10 | 0.00 | 727592.96 | 0.00 | 0.00 | 36213649.86 | 0.00 | 0.36 |
| May | 0.00 | 0.275049E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| June | 0.00 | 0.373095E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| July | 0.00 | 0.462657E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| August | 0.00 | 0.451769E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| September | 0.00 | 0.344469E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| October | 285270.00 | 0.102414E+10 | 0.00 | 1170974.80 | 0.00 | 0.00 | 0.117032E+09 | 0.00 | 0.36 |
| November | 77403299.92 | 0.153791E+09 | 0.00 | 3137182.88 | 0.00 | 0.00 | 0.722581E+09 | 0.00 | 0.36 |
| December | 0.111592E+10 | 2907780.51 | 0.00 | 1555755.95 | 91682.05 | 0.00 | 0.498453E+09 | 0.00 | 0.35 |
| Annual Sum or Average | 0.315232E+10 | 0.218563E+11 | 0.00 | 12518093.08 | 279186.54 | 0.00 | 0.263151E+10 | 0.00 | 0.36 |
| Minimum of Months | 0.00 | 252276.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
| Maximum of Months | 0.144107E+10 | 0.462657E+10 | 0.00 | 3137182.88 | 187504.49 | 0.00 | 0.722581E+09 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: M S1 APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.731526E+09 | 576296.60 | 0.00 | 4669175.17 | 0.00 | 0.00 | 0.108311E+10 | 0.00 | 0.35 |
| February | 0.218923E+09 | 28919072.65 | 0.00 | 4972565.16 | 0.00 | 0.00 | 0.847857E+09 | 0.00 | 0.36 |
| March | 222500.67 | 0.361202E+09 | 0.00 | 3899253.51 | 0.00 | 0.00 | 0.413317E+09 | 0.00 | 0.36 |
| April | 0.00 | 0.126103E+10 | 0.00 | 779748.83 | 0.00 | 0.00 | 35267303.67 | 0.00 | 0.36 |
| May | 0.00 | 0.275606E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| June | 0.00 | 0.372975E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| July | 0.00 | 0.462651E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| August | 0.00 | 0.453952E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| September | 0.00 | 0.351884E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| October | 0.00 | 0.110483E+10 | 0.00 | 1400960.83 | 0.00 | 0.00 | 97404801.80 | 0.00 | 0.36 |
| November | 0.00 | 0.178036E+09 | 0.00 | 5673606.59 | 0.00 | 0.00 | 0.744380E+09 | 0.00 | 0.36 |
| December | 0.299650E+09 | 3358820.55 | 0.00 | 6413217.99 | 0.00 | 0.00 | 0.134153E+10 | 0.00 | 0.35 |
| Annual Sum or Average | 0.125032E+10 | 0.221086E+11 | 0.00 | 27808528.09 | 0.00 | 0.00 | 0.456287E+10 | 0.00 | 0.36 |
| Minimum of Months | 0.00 | 576296.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
| Maximum of Months | 0.731526E+09 | 0.462651E+10 | 0.00 | 6413217.99 | 0.00 | 0.00 | 0.134153E+10 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: M S2 APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.731295E+09 | 576012.17 | 0.00 | 4680944.87 | 0.00 | 0.00 | 0.108340E+10 | 0.00 | 0.35 |
| February | 0.218876E+09 | 28937661.02 | 0.00 | 4981744.32 | 0.00 | 0.00 | 0.847866E+09 | 0.00 | 0.36 |
| March | 222523.37 | 0.361304E+09 | 0.00 | 3900550.15 | 0.00 | 0.00 | 0.413337E+09 | 0.00 | 0.36 |
| April | 0.00 | 0.126116E+10 | 0.00 | 779605.85 | 0.00 | 0.00 | 35266932.86 | 0.00 | 0.36 |
| May | 0.00 | 0.275619E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| June | 0.00 | 0.372955E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| July | 0.00 | 0.462660E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| August | 0.00 | 0.453964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| September | 0.00 | 0.351876E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| October | 0.00 | 0.110498E+10 | 0.00 | 1401109.44 | 0.00 | 0.00 | 97435015.24 | 0.00 | 0.36 |
| November | 0.00 | 0.178104E+09 | 0.00 | 5674654.05 | 0.00 | 0.00 | 0.744474E+09 | 0.00 | 0.36 |
| December | 0.300338E+09 | 3358552.84 | 0.00 | 6416663.36 | 0.00 | 0.00 | 0.134088E+10 | 0.00 | 0.35 |
| Annual Sum or Average | 0.125073E+10 | 0.221092E+11 | 0.00 | 27835272.04 | 0.00 | 0.00 | 0.456266E+10 | 0.00 | 0.36 |
| Minimum of Months | 0.00 | 576012.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
| Maximum of Months | 0.731295E+09 | 0.462660E+10 | 0.00 | 6416663.36 | 0.00 | 0.00 | 0.134088E+10 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: T SW APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.408041E+09 | 306884.93 | 0.00 | 975847.47 | 0.00 | 0.261837E+09 | 0.105860E+09 | 0.00 | 0.35 |
| February | 0.313420E+09 | 14833044.29 | 0.00 | 1120887.80 | 0.00 | 61663527.22 | 91553946.61 | 0.00 | 0.35 |
| March | 0.136902E+09 | 0.180604E+09 | 0.00 | 936505.08 | 0.00 | 0.00 | 79398634.83 | 0.00 | 0.36 |
| April | 4271958.69 | 0.635076E+09 | 0.00 | 230154.64 | 0.00 | 0.00 | 17444646.51 | 0.00 | 0.36 |
| May | 0.00 | 0.140305E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| June | 0.00 | 0.191711E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| July | 0.00 | 0.236654E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| August | 0.00 | 0.232394E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| September | 0.00 | 0.177491E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| October | 36603094.75 | 0.531035E+09 | 0.00 | 286869.18 | 0.00 | 0.00 | 39930739.99 | 0.00 | 0.36 |
| November | 0.277526E+09 | 89102377.02 | 0.00 | 969312.18 | 0.00 | 0.00 | 0.100355E+09 | 0.00 | 0.36 |
| December | 0.443027E+09 | 1774693.11 | 0.00 | 1315561.04 | 0.00 | 0.132445E+09 | 0.127629E+09 | 0.00 | 0.35 |
| Annual Sum or Average | 0.161979E+10 | 0.112383E+11 | 0.00 | 5835137.39 | 0.00 | 0.455945E+09 | 0.562172E+09 | 0.00 | 0.36 |
| Minimum of Months | 0.00 | 306884.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
| Maximum of Months | 0.443027E+09 | 0.236654E+10 | 0.00 | 1315561.04 | 0.00 | 0.261837E+09 | 0.127629E+09 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: T NW APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.331492E+09 | 213533.61 | 0.00 | 67564.72 | 31403.38 | 0.382618E+09 | 10207691.94 | 0.00 | 0.35 |
| February | 0.303584E+09 | 12170272.11 | 0.00 | 406252.14 | 0.00 | 99988209.51 | 45676107.78 | 0.00 | 0.35 |
| March | 0.148372E+09 | 0.171822E+09 | 0.00 | 690355.32 | 0.00 | 0.00 | 68208177.42 | 0.00 | 0.36 |
| April | 4573368.20 | 0.630312E+09 | 0.00 | 215896.67 | 0.00 | 0.00 | 17367489.98 | 0.00 | 0.36 |
| May | 0.00 | 0.140243E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| June | 0.00 | 0.191795E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| July | 0.00 | 0.236720E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| August | 0.00 | 0.231695E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| September | 0.00 | 0.174986E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| October | 46693122.25 | 0.500830E+09 | 0.00 | 220524.76 | 0.00 | 0.00 | 36488521.50 | 0.00 | 0.36 |
| November | 0.310886E+09 | 76981204.28 | 0.00 | 366744.93 | 53874.64 | 4823129.98 | 54854834.85 | 0.00 | 0.36 |
| December | 0.369478E+09 | 1483314.28 | 0.00 | 177620.74 | 383490.06 | 0.269072E+09 | 18970496.70 | 0.00 | 0.35 |
| Annual Sum or Average | 0.151508E+10 | 0.111482E+11 | 0.00 | 2144959.28 | 468768.08 | 0.756501E+09 | 0.251773E+09 | 0.00 | 0.36 |
| Minimum of Months | 0.00 | 213533.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
| Maximum of Months | 0.369478E+09 | 0.236720E+10 | 0.00 | 690355.32 | 383490.06 | 0.382618E+09 | 68208177.42 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: T SE APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.427031E+09 | 297970.73 | 0.00 | 863447.02 | 0.00 | 0.250194E+09 | 0.102139E+09 | 0.00 | 0.35 |
| February | 0.318657E+09 | 14827201.36 | 0.00 | 1169414.03 | 0.00 | 56912234.04 | 94699861.46 | 0.00 | 0.35 |
| March | 0.135805E+09 | 0.182830E+09 | 0.00 | 1005566.47 | 0.00 | 0.00 | 81760040.39 | 0.00 | 0.36 |
| April | 4052143.44 | 0.638377E+09 | 0.00 | 259189.44 | 0.00 | 0.00 | 17612229.52 | 0.00 | 0.36 |
| May | 0.00 | 0.140620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| June | 0.00 | 0.191690E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| July | 0.00 | 0.236783E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| August | 0.00 | 0.232539E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| September | 0.00 | 0.177537E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| October | 36845029.94 | 0.534835E+09 | 0.00 | 309192.81 | 0.00 | 0.00 | 40705053.48 | 0.00 | 0.36 |
| November | 0.277771E+09 | 90614393.49 | 0.00 | 1037073.37 | 0.00 | 0.00 | 0.102428E+09 | 0.00 | 0.36 |
| December | 0.451339E+09 | 1757125.97 | 0.00 | 1231817.50 | 0.00 | 0.128679E+09 | 0.126735E+09 | 0.00 | 0.35 |
| Annual Sum or Average | 0.165150E+10 | 0.112552E+11 | 0.00 | 5875700.64 | 0.00 | 0.435785E+09 | 0.566079E+09 | 0.00 | 0.36 |
| Minimum of Months | 0.00 | 297970.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
| Maximum of Months | 0.451339E+09 | 0.236783E+10 | 0.00 | 1231817.50 | 0.00 | 0.250194E+09 | 0.126735E+09 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: T NE APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.350121E+09 | 186271.75 | 0.00 | 39696.65 | 49185.67 | 0.365787E+09 | 5939616.23 | 0.00 | 0.35 |
| February | 0.314768E+09 | 12231542.12 | 0.00 | 401681.42 | 0.00 | 91474334.84 | 48126238.00 | 0.00 | 0.35 |
| March | 0.148112E+09 | 0.174567E+09 | 0.00 | 758926.67 | 0.00 | 0.00 | 70187922.98 | 0.00 | 0.36 |
| April | 4454301.06 | 0.633824E+09 | 0.00 | 239057.68 | 0.00 | 0.00 | 17438824.30 | 0.00 | 0.36 |
| May | 0.00 | 0.140532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| June | 0.00 | 0.191755E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| July | 0.00 | 0.236830E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| August | 0.00 | 0.231824E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| September | 0.00 | 0.175037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| October | 48351172.58 | 0.506179E+09 | 0.00 | 243353.43 | 0.00 | 0.00 | 36224534.48 | 0.00 | 0.36 |
| November | 0.314592E+09 | 79204331.58 | 0.00 | 386991.19 | 0.00 | 4748191.75 | 55235639.60 | 0.00 | 0.36 |
| December | 0.386447E+09 | 1508042.35 | 0.00 | 119950.71 | 125590.08 | 0.257920E+09 | 14072971.93 | 0.00 | 0.35 |
| Annual Sum or Average | 0.156685E+10 | 0.111675E+11 | 0.00 | 2189657.74 | 174775.75 | 0.719929E+09 | 0.247226E+09 | 0.00 | 0.36 |
| Minimum of Months | 0.00 | 186271.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
| Maximum of Months | 0.386447E+09 | 0.236830E+10 | 0.00 | 758926.67 | 125590.08 | 0.365787E+09 | 70187922.98 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: T N1 APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.438404E+09 | 126173.97 | 0.00 | 32506.63 | 184543.58 | 0.287360E+09 | 5937328.94 | 0.00 | 0.35 |
| February | 0.370611E+09 | 11345610.56 | 0.00 | 361072.79 | 0.00 | 42000044.10 | 56058805.96 | 0.00 | 0.35 |
| March | 0.129915E+09 | 0.168212E+09 | 0.00 | 758796.93 | 0.00 | 0.00 | 95768587.71 | 0.00 | 0.36 |
| April | 2386663.85 | 0.619600E+09 | 0.00 | 237074.54 | 0.00 | 0.00 | 19212351.76 | 0.00 | 0.36 |
| May | 0.00 | 0.138908E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| June | 0.00 | 0.189527E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| July | 0.00 | 0.235438E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| August | 0.00 | 0.229735E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| September | 0.00 | 0.172979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| October | 32709311.91 | 0.493840E+09 | 0.00 | 292497.20 | 0.00 | 0.00 | 49136286.49 | 0.00 | 0.36 |
| November | 0.309198E+09 | 74183576.03 | 0.00 | 394253.52 | 14954.81 | 0.00 | 79181857.54 | 0.00 | 0.36 |
| December | 0.552013E+09 | 1317880.69 | 0.00 | 82208.15 | 492837.54 | 0.105164E+09 | 11972888.66 | 0.00 | 0.35 |
| Annual Sum or Average | 0.183524E+10 | 0.110345E+11 | 0.00 | 2158409.75 | 692335.93 | 0.434524E+09 | 0.317268E+09 | 0.00 | 0.36 |
| Minimum of Months | 0.00 | 126173.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
| Maximum of Months | 0.552013E+09 | 0.235438E+10 | 0.00 | 758796.93 | 492837.54 | 0.287360E+09 | 95768587.71 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: T N2 APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.437707E+09 | 126173.45 | 0.00 | 32547.59 | 177906.17 | 0.287984E+09 | 5957998.34 | 0.00 | 0.35 |
| February | 0.370445E+09 | 11372524.26 | 0.00 | 363960.77 | 0.00 | 41732948.24 | 56735162.85 | 0.00 | 0.35 |
| March | 0.130183E+09 | 0.168347E+09 | 0.00 | 760873.07 | 0.00 | 0.00 | 95556048.44 | 0.00 | 0.36 |
| April | 2441101.23 | 0.619699E+09 | 0.00 | 237279.82 | 0.00 | 0.00 | 19157036.56 | 0.00 | 0.36 |
| May | 0.00 | 0.138918E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| June | 0.00 | 0.189523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| July | 0.00 | 0.235445E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| August | 0.00 | 0.229744E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| September | 0.00 | 0.172977E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| October | 32840932.27 | 0.494033E+09 | 0.00 | 292357.57 | 0.00 | 0.00 | 49087912.67 | 0.00 | 0.36 |
| November | 0.309397E+09 | 74334981.09 | 0.00 | 395697.21 | 10594.30 | 0.00 | 79069438.99 | 0.00 | 0.36 |
| December | 0.552016E+09 | 1347290.57 | 0.00 | 83169.70 | 441448.16 | 0.105208E+09 | 12016736.56 | 0.00 | 0.35 |
| Annual Sum or Average | 0.183503E+10 | 0.110353E+11 | 0.00 | 2165885.73 | 629948.62 | 0.434925E+09 | 0.317580E+09 | 0.00 | 0.36 |
| Minimum of Months | 0.00 | 126173.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
| Maximum of Months | 0.552016E+09 | 0.235445E+10 | 0.00 | 760873.07 | 441448.16 | 0.287984E+09 | 95556048.44 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: T S1 APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.572042E+09 | 301836.31 | 0.00 | 930318.46 | 0.00 | 92502027.80 | 0.135583E+09 | 0.00 | 0.35 |
| February | 0.356360E+09 | 14411732.38 | 0.00 | 1173316.83 | 0.00 | 10581180.73 | 0.121382E+09 | 0.00 | 0.36 |
| March | 0.111520E+09 | 0.178672E+09 | 0.00 | 1034833.32 | 0.00 | 0.00 | 0.111689E+09 | 0.00 | 0.36 |
| April | 2186102.55 | 0.625808E+09 | 0.00 | 253338.86 | 0.00 | 0.00 | 19121902.99 | 0.00 | 0.36 |
| May | 0.00 | 0.139058E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| June | 0.00 | 0.189469E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| July | 0.00 | 0.235415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| August | 0.00 | 0.230646E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| September | 0.00 | 0.176088E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| October | 24048100.52 | 0.529279E+09 | 0.00 | 351390.90 | 0.00 | 0.00 | 49539654.92 | 0.00 | 0.36 |
| November | 0.254750E+09 | 87995439.59 | 0.00 | 1129622.81 | 0.00 | 0.00 | 0.137050E+09 | 0.00 | 0.36 |
| December | 0.525455E+09 | 1752553.56 | 0.00 | 1327761.82 | 0.00 | 39620668.13 | 0.165001E+09 | 0.00 | 0.35 |
| Annual Sum or Average | 0.184636E+10 | 0.111450E+11 | 0.00 | 6200582.99 | 0.00 | 0.142704E+09 | 0.739367E+09 | 0.00 | 0.36 |
| Minimum of Months | 0.00 | 301836.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
| Maximum of Months | 0.572042E+09 | 0.235415E+10 | 0.00 | 1327761.82 | 0.00 | 92502027.80 | 0.165001E+09 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: T S2 APARTMENT
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.571978E+09 | 301620.05 | 0.00 | 933879.03 | 0.00 | 92818940.01 | 0.135447E+09 | 0.00 | 0.35 |
| February | 0.355984E+09 | 14429039.23 | 0.00 | 1179467.74 | 0.00 | 10581130.34 | 0.121808E+09 | 0.00 | 0.36 |
| March | 0.111683E+09 | 0.178771E+09 | 0.00 | 1035969.21 | 0.00 | 0.00 | 0.111563E+09 | 0.00 | 0.36 |
| April | 2185557.77 | 0.625896E+09 | 0.00 | 253458.30 | 0.00 | 0.00 | 19122080.13 | 0.00 | 0.36 |
| May | 0.00 | 0.139068E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| June | 0.00 | 0.189465E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| July | 0.00 | 0.235423E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| August | 0.00 | 0.230655E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| September | 0.00 | 0.176085E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| October | 24202574.00 | 0.529393E+09 | 0.00 | 351176.79 | 0.00 | 0.00 | 49448242.74 | 0.00 | 0.36 |
| November | 0.254539E+09 | 88079177.10 | 0.00 | 1131311.40 | 0.00 | 0.00 | 0.137282E+09 | 0.00 | 0.36 |
| December | 0.524875E+09 | 1752391.89 | 0.00 | 1331280.21 | 0.00 | 39620183.78 | 0.165591E+09 | 0.00 | 0.35 |
| Annual Sum or Average | 0.184545E+10 | 0.111456E+11 | 0.00 | 6216542.69 | 0.00 | 0.143020E+09 | 0.740261E+09 | 0.00 | 0.36 |
| Minimum of Months | 0.00 | 301620.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
| Maximum of Months | 0.571978E+09 | 0.235423E+10 | 0.00 | 1331280.21 | 0.00 | 92818940.01 | 0.165591E+09 | 0.00 | 0.36 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 09:14:53
Custom Monthly Report| SITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
| January | 0.888684E+11 | 0.820061E+10 | 0.00 | 0.137499E+10 | 0.136767E+11 |
| February | 0.946192E+11 | 0.711789E+10 | 0.00 | 0.918414E+09 | 0.360753E+11 |
| March | 0.119130E+12 | 0.304223E+10 | 0.00 | 0.444858E+09 | 0.992470E+11 |
| April | 0.120842E+12 | -0.337574E+10 | 0.00 | -268704709.9 | 0.175450E+12 |
| May | 0.120785E+12 | -0.982743E+10 | 0.00 | -0.105063E+10 | 0.249466E+12 |
| June | 0.113102E+12 | -0.965954E+10 | 0.00 | -0.150387E+10 | 0.268183E+12 |
| July | 0.100033E+12 | -0.167061E+11 | 0.00 | -0.183707E+10 | 0.295365E+12 |
| August | 0.876119E+11 | -0.125730E+11 | 0.00 | -0.178599E+10 | 0.275829E+12 |
| September | 0.974883E+11 | -0.740960E+10 | 0.00 | -0.113620E+10 | 0.230406E+12 |
| October | 0.994032E+11 | -660899016.6 | 0.00 | 50599631.66 | 0.154568E+12 |
| November | 0.932389E+11 | 0.392201E+10 | 0.00 | 0.815243E+09 | 0.776178E+11 |
| December | 0.813196E+11 | 0.759679E+10 | 0.00 | 0.134081E+10 | 0.242447E+11 |
| Annual Sum or Average | 0.121644E+13 | -0.303328E+11 | 0.00 | -0.263755E+10 | 0.190013E+13 |
| Minimum of Months | 0.813196E+11 | -0.167061E+11 | 0.00 | -0.183707E+10 | 0.136767E+11 |
| Maximum of Months | 0.120842E+12 | 0.820061E+10 | 0.00 | 0.137499E+10 | 0.295365E+12 |