Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 09:14
Tabular Output Report in Format: HTML
Building: ApartmentMidRise
Environment: RUNPERIOD 1 ** El Paso International Ap Ut TX USA TMY3 WMO#=722700
Simulation Timestamp: 2023-10-16 09:14:34
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 09:14:34
Values gathered over 8760.00 hours| Total Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
| Total Site Energy | 1418.11 | 452.40 | 502.17 |
| Net Site Energy | 1418.11 | 452.40 | 502.17 |
| Total Source Energy | 4281.47 | 1365.87 | 1516.11 |
| Net Source Energy | 4281.47 | 1365.87 | 1516.11 |
| Site=>Source Conversion Factor | |
| Electricity | 3.167 |
| Natural Gas | 1.084 |
| District Cooling | 1.056 |
| District Heating | 3.613 |
| Steam | 1.200 |
| Gasoline | 1.050 |
| Diesel | 1.050 |
| Coal | 1.050 |
| Fuel Oil No 1 | 1.050 |
| Fuel Oil No 2 | 1.050 |
| Propane | 1.050 |
| Other Fuel 1 | 1.000 |
| Other Fuel 2 | 1.000 |
| Area [m2] | |
| Total Building Area | 3134.61 |
| Net Conditioned Building Area | 2823.98 |
| Unconditioned Building Area | 310.64 |
| Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
| Heating | 0.00 | 100.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Cooling | 187.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Lighting | 99.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Lighting | 50.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment | 458.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans | 112.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems | 408.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1875.32 |
| Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Total End Uses | 1317.45 | 100.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1875.32 |
| Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
| Heating | General | 0.00 | 100.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Cooling | General | 187.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Lighting | LightsWired | 94.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LightsPlugIn | 4.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Exterior Lighting | General | 50.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment | MiscPlug | 388.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| ElevatorLift | 65.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| ElevatorLightsFan | 5.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| General | 112.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems | Water Heater | 408.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1875.32 |
| Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
| Heating | Unassigned | 0.00 | 100.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Cooling | Unassigned | 187.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Lighting | GENERAL | 99.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Lighting | Unassigned | 50.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment | GENERAL | 458.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans | Unassigned | 112.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Pumps | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems | Unassigned | 408.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1875.32 |
| Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
| Lighting | 52.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| HVAC | 251.24 | 35.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.66 |
| Other | 162.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Total | 466.52 | 35.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.66 |
| Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
| Lighting | 47.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| HVAC | 226.34 | 32.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.60 |
| Other | 146.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Total | 420.29 | 32.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.60 |
| Electricity [GJ] | Percent Electricity [%] | |
| Fuel-Fired Power Generation | 0.000 | 0.00 |
| High Temperature Geothermal* | 0.000 | 0.00 |
| Photovoltaic Power | 0.000 | 0.00 |
| Wind Power | 0.000 | 0.00 |
| Power Conversion | 0.000 | 0.00 |
| Net Decrease in On-Site Storage | 0.000 | 0.00 |
| Total On-Site Electric Sources | 0.000 | 0.00 |
| Electricity Coming From Utility | 1317.445 | 100.00 |
| Surplus Electricity Going To Utility | 0.000 | 0.00 |
| Net Electricity From Utility | 1317.445 | 100.00 |
| Total On-Site and Utility Electric Sources | 1317.445 | 100.00 |
| Total Electricity End Uses | 1317.445 | 100.00 |
| Heat [GJ] | Percent Heat [%] | |
| Water-Side Heat Recovery | 0.00 | 0.00 |
| Air to Air Heat Recovery for Cooling | 0.00 | 50.14 |
| Air to Air Heat Recovery for Heating | 0.00 | 49.86 |
| High-Temperature Geothermal* | 0.00 | 0.00 |
| Solar Water Thermal | 0.00 | 0.00 |
| Solar Air Thermal | 0.00 | 0.00 |
| Total On-Site Thermal Sources | 0.00 | 100.00 |
| Water [m3] | Percent Water [%] | |
| Rainwater Collection | 0.00 | 0.00 |
| Condensate Collection | 0.00 | 0.00 |
| Groundwater Well | 0.00 | 0.00 |
| Total On Site Water Sources | 0.00 | 0.00 |
| - | - | - |
| Initial Storage | 0.00 | 0.00 |
| Final Storage | 0.00 | 0.00 |
| Change in Storage | 0.00 | 0.00 |
| - | - | - |
| Water Supplied by Utility | 1875.32 | 100.00 |
| - | - | - |
| Total On Site, Change in Storage, and Utility Water Sources | 1875.32 | 100.00 |
| Total Water End Uses | 1875.32 | 100.00 |
| Degrees [deltaC] | |
| Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
| Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
| Facility [Hours] | |
| Time Setpoint Not Met During Occupied Heating | 0.00 |
| Time Setpoint Not Met During Occupied Cooling | 0.00 |
| Time Not Comfortable Based on Simple ASHRAE 55-2004 | 8109.33 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2012
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME APARTMENTMIDRISE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3B
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_TX_ELPASO
| Environment |ZoneCoolingSummaryMonthly
| G SW APARTMENT | G NW APARTMENT | OFFICE | G NE APARTMENT | G N1 APARTMENT | G N2 APARTMENT | G S1 APARTMENT | G S2 APARTMENT | M SW APARTMENT | M NW APARTMENT | M SE APARTMENT | M NE APARTMENT | M N1 APARTMENT | M N2 APARTMENT | M S1 APARTMENT | M S2 APARTMENT | T SW APARTMENT | T NW APARTMENT | T SE APARTMENT | T NE APARTMENT | T N1 APARTMENT | T N2 APARTMENT | T S1 APARTMENT | T S2 APARTMENT | T CORRIDOR | G CORRIDOR | M CORRIDOR |ZoneHeatingSummaryMonthly
| G SW APARTMENT | G NW APARTMENT | OFFICE | G NE APARTMENT | G N1 APARTMENT | G N2 APARTMENT | G S1 APARTMENT | G S2 APARTMENT | M SW APARTMENT | M NW APARTMENT | M SE APARTMENT | M NE APARTMENT | M N1 APARTMENT | M N2 APARTMENT | M S1 APARTMENT | M S2 APARTMENT | T SW APARTMENT | T NW APARTMENT | T SE APARTMENT | T NE APARTMENT | T N1 APARTMENT | T N2 APARTMENT | T S1 APARTMENT | T S2 APARTMENT | T CORRIDOR | G CORRIDOR | M CORRIDOR |ZoneElectricSummaryMonthly
| G SW APARTMENT | G NW APARTMENT | OFFICE | G NE APARTMENT | G N1 APARTMENT | G N2 APARTMENT | G S1 APARTMENT | G S2 APARTMENT | M SW APARTMENT | M NW APARTMENT | M SE APARTMENT | M NE APARTMENT | M N1 APARTMENT | M N2 APARTMENT | M S1 APARTMENT | M S2 APARTMENT | T SW APARTMENT | T NW APARTMENT | T SE APARTMENT | T NE APARTMENT | T N1 APARTMENT | T N2 APARTMENT | T S1 APARTMENT | T S2 APARTMENT | T CORRIDOR | G CORRIDOR | M CORRIDOR |SpaceGainsMonthly
| G SW APARTMENT | G NW APARTMENT | OFFICE | G NE APARTMENT | G N1 APARTMENT | G N2 APARTMENT | G S1 APARTMENT | G S2 APARTMENT | M SW APARTMENT | M NW APARTMENT | M SE APARTMENT | M NE APARTMENT | M N1 APARTMENT | M N2 APARTMENT | M S1 APARTMENT | M S2 APARTMENT | T SW APARTMENT | T NW APARTMENT | T SE APARTMENT | T NE APARTMENT | T N1 APARTMENT | T N2 APARTMENT | T S1 APARTMENT | T S2 APARTMENT | T CORRIDOR | G CORRIDOR | M CORRIDOR |PeakSpaceGainsMonthly
| G SW APARTMENT | G NW APARTMENT | OFFICE | G NE APARTMENT | G N1 APARTMENT | G N2 APARTMENT | G S1 APARTMENT | G S2 APARTMENT | M SW APARTMENT | M NW APARTMENT | M SE APARTMENT | M NE APARTMENT | M N1 APARTMENT | M N2 APARTMENT | M S1 APARTMENT | M S2 APARTMENT | T SW APARTMENT | T NW APARTMENT | T SE APARTMENT | T NE APARTMENT | T N1 APARTMENT | T N2 APARTMENT | T S1 APARTMENT | T S2 APARTMENT | T CORRIDOR | G CORRIDOR | M CORRIDOR |SpaceGainComponentsAtCoolingPeakMonthly
| G SW APARTMENT | G NW APARTMENT | OFFICE | G NE APARTMENT | G N1 APARTMENT | G N2 APARTMENT | G S1 APARTMENT | G S2 APARTMENT | M SW APARTMENT | M NW APARTMENT | M SE APARTMENT | M NE APARTMENT | M N1 APARTMENT | M N2 APARTMENT | M S1 APARTMENT | M S2 APARTMENT | T SW APARTMENT | T NW APARTMENT | T SE APARTMENT | T NE APARTMENT | T N1 APARTMENT | T N2 APARTMENT | T S1 APARTMENT | T S2 APARTMENT | T CORRIDOR | G CORRIDOR | M CORRIDOR |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| G SW APARTMENT | G NW APARTMENT | OFFICE | G NE APARTMENT | G N1 APARTMENT | G N2 APARTMENT | G S1 APARTMENT | G S2 APARTMENT | M SW APARTMENT | M NW APARTMENT | M SE APARTMENT | M NE APARTMENT | M N1 APARTMENT | M N2 APARTMENT | M S1 APARTMENT | M S2 APARTMENT | T SW APARTMENT | T NW APARTMENT | T SE APARTMENT | T NE APARTMENT | T N1 APARTMENT | T N2 APARTMENT | T S1 APARTMENT | T S2 APARTMENT | T CORRIDOR | G CORRIDOR | M CORRIDOR |ComfortReportSimple55Monthly
| G SW APARTMENT | G NW APARTMENT | OFFICE | G NE APARTMENT | G N1 APARTMENT | G N2 APARTMENT | G S1 APARTMENT | G S2 APARTMENT | M SW APARTMENT | M NW APARTMENT | M SE APARTMENT | M NE APARTMENT | M N1 APARTMENT | M N2 APARTMENT | M S1 APARTMENT | M S2 APARTMENT | T SW APARTMENT | T NW APARTMENT | T SE APARTMENT | T NE APARTMENT | T N1 APARTMENT | T N2 APARTMENT | T S1 APARTMENT | T S2 APARTMENT | T CORRIDOR | G CORRIDOR | M CORRIDOR |OccupantComfortDataSummaryMonthly
| OCCUP_GSW | OCCUP_GNW | OCCUP_OFFICE | OCCUP_GNE | OCCUP_GN1 | OCCUP_GN2 | OCCUP_GS1 | OCCUP_GS2 | OCCUP_MSW | OCCUP_MNW | OCCUP_MSE | OCCUP_MNE | OCCUP_MN1 | OCCUP_MN2 | OCCUP_MS1 | OCCUP_MS2 | OCCUP_TSW | OCCUP_TNW | OCCUP_TSE | OCCUP_TNE | OCCUP_TN1 | OCCUP_TN2 | OCCUP_TS1 | OCCUP_TS2 | OCCUP_T CORRIDOR | OCCUP_G CORRIDOR | OCCUP_M CORRIDOR |DXReportMonthly
| SPLIT GSW COOLING COIL | SPLIT GNW COOLING COIL | SPLIT OFFICE COOLING COIL | SPLIT GNE COOLING COIL | SPLIT GN1 COOLING COIL | SPLIT GN2 COOLING COIL | SPLIT GS1 COOLING COIL | SPLIT GS2 COOLING COIL | SPLIT MSW COOLING COIL | SPLIT MNW COOLING COIL | SPLIT MSE COOLING COIL | SPLIT MNE COOLING COIL | SPLIT MN1 COOLING COIL | SPLIT MN2 COOLING COIL | SPLIT MS1 COOLING COIL | SPLIT MS2 COOLING COIL | SPLIT TSW COOLING COIL | SPLIT TNW COOLING COIL | SPLIT TSE COOLING COIL | SPLIT TNE COOLING COIL | SPLIT TN1 COOLING COIL | SPLIT TN2 COOLING COIL | SPLIT TS1 COOLING COIL | SPLIT TS2 COOLING COIL |WindowReportMonthly
| GWINDOW1 S SWA | GWINDOW1 W SWA | GWINDOW1 W NWA | GWINDOW1 N NWA | GWINDOW1 S SEA | GWINDOW1 E SEA | GWINDOW1 E NEA | GWINDOW1 N NEA | GWINDOW1 N N1A | GWINDOW1 N N2A | GWINDOW1 S S1A | GWINDOW1 S S2A | MWINDOW1 S SWA | MWINDOW1 W SWA | MWINDOW1 W NWA | MWINDOW1 N NWA | MWINDOW1 S SEA | MWINDOW1 E SEA | MWINDOW1 E NEA | MWINDOW1 N NEA | MWINDOW1 N N1A | MWINDOW1 N N2A | MWINDOW1 S S1A | MWINDOW1 S S2A | TWINDOW1 S SWA | TWINDOW1 W SWA | TWINDOW1 W NWA | TWINDOW1 N NWA | TWINDOW1 S SEA | TWINDOW1 E SEA | TWINDOW1 E NEA | TWINDOW1 N NEA | TWINDOW1 N N1A | TWINDOW1 N N2A | TWINDOW1 S S1A | TWINDOW1 S S2A | TWINDOW14 | ENTRANCE DOOR | MWINDOW14 |WindowEnergyReportMonthly
| GWINDOW1 S SWA | GWINDOW1 W SWA | GWINDOW1 W NWA | GWINDOW1 N NWA | GWINDOW1 S SEA | GWINDOW1 E SEA | GWINDOW1 E NEA | GWINDOW1 N NEA | GWINDOW1 N N1A | GWINDOW1 N N2A | GWINDOW1 S S1A | GWINDOW1 S S2A | MWINDOW1 S SWA | MWINDOW1 W SWA | MWINDOW1 W NWA | MWINDOW1 N NWA | MWINDOW1 S SEA | MWINDOW1 E SEA | MWINDOW1 E NEA | MWINDOW1 N NEA | MWINDOW1 N N1A | MWINDOW1 N N2A | MWINDOW1 S S1A | MWINDOW1 S S2A | TWINDOW1 S SWA | TWINDOW1 W SWA | TWINDOW1 W NWA | TWINDOW1 N NWA | TWINDOW1 S SEA | TWINDOW1 E SEA | TWINDOW1 E NEA | TWINDOW1 N NEA | TWINDOW1 N N1A | TWINDOW1 N N2A | TWINDOW1 S S1A | TWINDOW1 S S2A | TWINDOW14 | ENTRANCE DOOR | MWINDOW14 |WindowZoneSummaryMonthly
| G SW APARTMENT | G NW APARTMENT | OFFICE | G NE APARTMENT | G N1 APARTMENT | G N2 APARTMENT | G S1 APARTMENT | G S2 APARTMENT | M SW APARTMENT | M NW APARTMENT | M SE APARTMENT | M NE APARTMENT | M N1 APARTMENT | M N2 APARTMENT | M S1 APARTMENT | M S2 APARTMENT | T SW APARTMENT | T NW APARTMENT | T SE APARTMENT | T NE APARTMENT | T N1 APARTMENT | T N2 APARTMENT | T S1 APARTMENT | T S2 APARTMENT | T CORRIDOR | G CORRIDOR | M CORRIDOR |WindowEnergyZoneSummaryMonthly
| G SW APARTMENT | G NW APARTMENT | OFFICE | G NE APARTMENT | G N1 APARTMENT | G N2 APARTMENT | G S1 APARTMENT | G S2 APARTMENT | M SW APARTMENT | M NW APARTMENT | M SE APARTMENT | M NE APARTMENT | M N1 APARTMENT | M N2 APARTMENT | M S1 APARTMENT | M S2 APARTMENT | T SW APARTMENT | T NW APARTMENT | T SE APARTMENT | T NE APARTMENT | T N1 APARTMENT | T N2 APARTMENT | T S1 APARTMENT | T S2 APARTMENT | T CORRIDOR | G CORRIDOR | M CORRIDOR |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| G SW APARTMENT WATER HEATER | G NW APARTMENT WATER HEATER | G NE APARTMENT WATER HEATER | G N1 APARTMENT WATER HEATER | G N2 APARTMENT WATER HEATER | G S1 APARTMENT WATER HEATER | G S2 APARTMENT WATER HEATER | M SW APARTMENT WATER HEATER | M NW APARTMENT WATER HEATER | M SE APARTMENT WATER HEATER | M NE APARTMENT WATER HEATER | M N1 APARTMENT WATER HEATER | M N2 APARTMENT WATER HEATER | M S1 APARTMENT WATER HEATER | M S2 APARTMENT WATER HEATER | T SW APARTMENT WATER HEATER | T NW APARTMENT WATER HEATER | T SE APARTMENT WATER HEATER | T NE APARTMENT WATER HEATER | T N1 APARTMENT WATER HEATER | T N2 APARTMENT WATER HEATER | T S1 APARTMENT WATER HEATER | T S2 APARTMENT WATER HEATER |DaylightingReportMonthly
| Environment |CoilReportMonthly
| SPLIT GSW HEATING COIL | SPLIT GNW HEATING COIL | SPLIT OFFICE HEATING COIL | SPLIT GNE HEATING COIL | SPLIT GN1 HEATING COIL | SPLIT GN2 HEATING COIL | SPLIT GS1 HEATING COIL | SPLIT GS2 HEATING COIL | SPLIT MSW HEATING COIL | SPLIT MNW HEATING COIL | SPLIT MSE HEATING COIL | SPLIT MNE HEATING COIL | SPLIT MN1 HEATING COIL | SPLIT MN2 HEATING COIL | SPLIT MS1 HEATING COIL | SPLIT MS2 HEATING COIL | SPLIT TSW HEATING COIL | SPLIT TNW HEATING COIL | SPLIT TSE HEATING COIL | SPLIT TNE HEATING COIL | SPLIT TN1 HEATING COIL | SPLIT TN2 HEATING COIL | SPLIT TS1 HEATING COIL | SPLIT TS2 HEATING COIL | SPLIT GSW COOLING COIL | SPLIT GNW COOLING COIL | SPLIT OFFICE COOLING COIL | SPLIT GNE COOLING COIL | SPLIT GN1 COOLING COIL | SPLIT GN2 COOLING COIL | SPLIT GS1 COOLING COIL | SPLIT GS2 COOLING COIL | SPLIT MSW COOLING COIL | SPLIT MNW COOLING COIL | SPLIT MSE COOLING COIL | SPLIT MNE COOLING COIL | SPLIT MN1 COOLING COIL | SPLIT MN2 COOLING COIL | SPLIT MS1 COOLING COIL | SPLIT MS2 COOLING COIL | SPLIT TSW COOLING COIL | SPLIT TNW COOLING COIL | SPLIT TSE COOLING COIL | SPLIT TNE COOLING COIL | SPLIT TN1 COOLING COIL | SPLIT TN2 COOLING COIL | SPLIT TS1 COOLING COIL | SPLIT TS2 COOLING COIL |FanReportMonthly
| SPLIT GSW SUPPLY FAN | G SW APARTMENT ERV SUP FAN | G SW APARTMENT ERV EXH FAN | SPLIT GNW SUPPLY FAN | G NW APARTMENT ERV SUP FAN | G NW APARTMENT ERV EXH FAN | SPLIT OFFICE SUPPLY FAN | SPLIT GNE SUPPLY FAN | G NE APARTMENT ERV SUP FAN | G NE APARTMENT ERV EXH FAN | SPLIT GN1 SUPPLY FAN | G N1 APARTMENT ERV SUP FAN | G N1 APARTMENT ERV EXH FAN | SPLIT GN2 SUPPLY FAN | G N2 APARTMENT ERV SUP FAN | G N2 APARTMENT ERV EXH FAN | SPLIT GS1 SUPPLY FAN | G S1 APARTMENT ERV SUP FAN | G S1 APARTMENT ERV EXH FAN | SPLIT GS2 SUPPLY FAN | G S2 APARTMENT ERV SUP FAN | G S2 APARTMENT ERV EXH FAN | SPLIT MSW SUPPLY FAN | M SW APARTMENT ERV SUP FAN | M SW APARTMENT ERV EXH FAN | SPLIT MNW SUPPLY FAN | M NW APARTMENT ERV SUP FAN | M NW APARTMENT ERV EXH FAN | SPLIT MSE SUPPLY FAN | M SE APARTMENT ERV SUP FAN | M SE APARTMENT ERV EXH FAN | SPLIT MNE SUPPLY FAN | M NE APARTMENT ERV SUP FAN | M NE APARTMENT ERV EXH FAN | SPLIT MN1 SUPPLY FAN | M N1 APARTMENT ERV SUP FAN | M N1 APARTMENT ERV EXH FAN | SPLIT MN2 SUPPLY FAN | M N2 APARTMENT ERV SUP FAN | M N2 APARTMENT ERV EXH FAN | SPLIT MS1 SUPPLY FAN | M S1 APARTMENT ERV SUP FAN | M S1 APARTMENT ERV EXH FAN | SPLIT MS2 SUPPLY FAN | M S2 APARTMENT ERV SUP FAN | M S2 APARTMENT ERV EXH FAN | SPLIT TSW SUPPLY FAN | T SW APARTMENT ERV SUP FAN | T SW APARTMENT ERV EXH FAN | SPLIT TNW SUPPLY FAN | T NW APARTMENT ERV SUP FAN | T NW APARTMENT ERV EXH FAN | SPLIT TSE SUPPLY FAN | T SE APARTMENT ERV SUP FAN | T SE APARTMENT ERV EXH FAN | SPLIT TNE SUPPLY FAN | T NE APARTMENT ERV SUP FAN | T NE APARTMENT ERV EXH FAN | SPLIT TN1 SUPPLY FAN | T N1 APARTMENT ERV SUP FAN | T N1 APARTMENT ERV EXH FAN | SPLIT TN2 SUPPLY FAN | T N2 APARTMENT ERV SUP FAN | T N2 APARTMENT ERV EXH FAN | SPLIT TS1 SUPPLY FAN | T S1 APARTMENT ERV SUP FAN | T S1 APARTMENT ERV EXH FAN | SPLIT TS2 SUPPLY FAN | T S2 APARTMENT ERV SUP FAN | T S2 APARTMENT ERV EXH FAN |ZoneTemperatureOscillationReportMonthly
| G SW APARTMENT | G NW APARTMENT | OFFICE | G NE APARTMENT | G N1 APARTMENT | G N2 APARTMENT | G S1 APARTMENT | G S2 APARTMENT | M SW APARTMENT | M NW APARTMENT | M SE APARTMENT | M NE APARTMENT | M N1 APARTMENT | M N2 APARTMENT | M S1 APARTMENT | M S2 APARTMENT | T SW APARTMENT | T NW APARTMENT | T SE APARTMENT | T NE APARTMENT | T N1 APARTMENT | T N2 APARTMENT | T S1 APARTMENT | T S2 APARTMENT | T CORRIDOR | G CORRIDOR | M CORRIDOR |AirLoopSystemEnergyAndWaterUseMonthly
| SPLIT GSW | SPLIT GNW | SPLIT OFFICE | SPLIT GNE | SPLIT GN1 | SPLIT GN2 | SPLIT GS1 | SPLIT GS2 | SPLIT MSW | SPLIT MNW | SPLIT MSE | SPLIT MNE | SPLIT MN1 | SPLIT MN2 | SPLIT MS1 | SPLIT MS2 | SPLIT TSW | SPLIT TNW | SPLIT TSE | SPLIT TNE | SPLIT TN1 | SPLIT TN2 | SPLIT TS1 | SPLIT TS2 |AirLoopSystemComponentLoadsMonthly
| SPLIT GSW | SPLIT GNW | SPLIT OFFICE | SPLIT GNE | SPLIT GN1 | SPLIT GN2 | SPLIT GS1 | SPLIT GS2 | SPLIT MSW | SPLIT MNW | SPLIT MSE | SPLIT MNE | SPLIT MN1 | SPLIT MN2 | SPLIT MS1 | SPLIT MS2 | SPLIT TSW | SPLIT TNW | SPLIT TSE | SPLIT TNE | SPLIT TN1 | SPLIT TN2 | SPLIT TS1 | SPLIT TS2 |AirLoopSystemComponentEnergyUseMonthly
| SPLIT GSW | SPLIT GNW | SPLIT OFFICE | SPLIT GNE | SPLIT GN1 | SPLIT GN2 | SPLIT GS1 | SPLIT GS2 | SPLIT MSW | SPLIT MNW | SPLIT MSE | SPLIT MNE | SPLIT MN1 | SPLIT MN2 | SPLIT MS1 | SPLIT MS2 | SPLIT TSW | SPLIT TNW | SPLIT TSE | SPLIT TNE | SPLIT TN1 | SPLIT TN2 | SPLIT TS1 | SPLIT TS2 |MechanicalVentilationLoadsMonthly
| G SW APARTMENT | G NW APARTMENT | OFFICE | G NE APARTMENT | G N1 APARTMENT | G N2 APARTMENT | G S1 APARTMENT | G S2 APARTMENT | M SW APARTMENT | M NW APARTMENT | M SE APARTMENT | M NE APARTMENT | M N1 APARTMENT | M N2 APARTMENT | M S1 APARTMENT | M S2 APARTMENT | T SW APARTMENT | T NW APARTMENT | T SE APARTMENT | T NE APARTMENT | T N1 APARTMENT | T N2 APARTMENT | T S1 APARTMENT | T S2 APARTMENT |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 09:14:34
General| Value | |
| Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 09:14 |
| RunPeriod | RUNPERIOD 1 |
| Weather File | El Paso International Ap Ut TX USA TMY3 WMO#=722700 |
| Latitude [deg] | 31.77 |
| Longitude [deg] | -106.5 |
| Elevation [m] | 1186.00 |
| Time Zone | -7.0 |
| North Axis Angle [deg] | 0.00 |
| Rotation for Appendix G [deg] | 0.00 |
| Hours Simulated [hrs] | 8760.00 |
| Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
| Gross Wall Area [m2] | 1542.04 | 564.80 | 206.22 | 564.80 | 206.22 |
| Above Ground Wall Area [m2] | 1542.04 | 564.80 | 206.22 | 564.80 | 206.22 |
| Window Opening Area [m2] | 306.92 | 112.97 | 43.82 | 112.97 | 37.16 |
| Gross Window-Wall Ratio [%] | 19.90 | 20.00 | 21.25 | 20.00 | 18.02 |
| Above Ground Window-Wall Ratio [%] | 19.90 | 20.00 | 21.25 | 20.00 | 18.02 |
| Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
| Gross Wall Area [m2] | 1501.17 | 564.80 | 185.79 | 564.80 | 185.79 |
| Above Ground Wall Area [m2] | 1501.17 | 564.80 | 185.79 | 564.80 | 185.79 |
| Window Opening Area [m2] | 300.26 | 112.97 | 37.16 | 112.97 | 37.16 |
| Gross Window-Wall Ratio [%] | 20.00 | 20.00 | 20.00 | 20.00 | 20.00 |
| Above Ground Window-Wall Ratio [%] | 20.00 | 20.00 | 20.00 | 20.00 | 20.00 |
| Total | |
| Gross Roof Area [m2] | 783.65 |
| Skylight Area [m2] | 0.00 |
| Skylight-Roof Ratio [%] | 0.00 |
| Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
| G SW APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 0.00 | 11.71 | 11.71 | 8.6918 | 35.30 | 6.6700 |
| G NW APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 0.00 | 11.71 | 11.71 | 8.6918 | 35.30 | 6.6700 |
| OFFICE | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 0.00 | 11.71 | 11.71 | 9.7532 | 18.58 | 6.6700 |
| G NE APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 0.00 | 11.71 | 11.71 | 8.6918 | 35.30 | 6.6700 |
| G N1 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 0.00 | 7.06 | 7.06 | 8.6918 | 35.30 | 6.6700 |
| G N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 0.00 | 7.06 | 7.06 | 8.6918 | 35.30 | 6.6700 |
| G S1 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 0.00 | 7.06 | 7.06 | 8.6918 | 35.30 | 6.6700 |
| G S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 0.00 | 7.06 | 7.06 | 8.6918 | 35.30 | 6.6700 |
| M SW APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 58.52 | 0.00 | 11.71 | 11.71 | 8.6918 | 35.30 | 6.6700 |
| M NW APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 58.52 | 0.00 | 11.71 | 11.71 | 8.6918 | 35.30 | 6.6700 |
| M SE APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 58.52 | 0.00 | 11.71 | 11.71 | 8.6918 | 35.30 | 6.6700 |
| M NE APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 58.52 | 0.00 | 11.71 | 11.71 | 8.6918 | 35.30 | 6.6700 |
| M N1 APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 35.30 | 0.00 | 7.06 | 7.06 | 8.6918 | 35.30 | 6.6700 |
| M N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 35.30 | 0.00 | 7.06 | 7.06 | 8.6918 | 35.30 | 6.6700 |
| M S1 APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 35.30 | 0.00 | 7.06 | 7.06 | 8.6918 | 35.30 | 6.6700 |
| M S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 35.30 | 0.00 | 7.06 | 7.06 | 8.6918 | 35.30 | 6.6700 |
| T SW APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 0.00 | 11.71 | 11.71 | 8.6918 | 35.30 | 6.6700 |
| T NW APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 0.00 | 11.71 | 11.71 | 8.6918 | 35.30 | 6.6700 |
| T SE APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 0.00 | 11.71 | 11.71 | 8.6918 | 35.30 | 6.6700 |
| T NE APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 0.00 | 11.71 | 11.71 | 8.6918 | 35.30 | 6.6700 |
| T N1 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 0.00 | 7.06 | 7.06 | 8.6918 | 35.30 | 6.6700 |
| T N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 0.00 | 7.06 | 7.06 | 8.6918 | 35.30 | 6.6700 |
| T S1 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 0.00 | 7.06 | 7.06 | 8.6918 | 35.30 | 6.6700 |
| T S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 0.00 | 7.06 | 7.06 | 8.6918 | 35.30 | 6.6700 |
| T CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 0.00 | 1.11 | 1.11 | 4.7725 | 18.58 | 0.0000 |
| G CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 0.00 | 3.32 | 3.32 | 4.7725 | 18.58 | 105.2565 |
| M CORRIDOR | 77.66 | No | Yes | 236.69 | 2.00 | 10.22 | 0.00 | 1.11 | 1.11 | 4.7725 | 18.58 | 0.0000 |
| Total | 3134.61 | 9553.84 | 1542.04 | 0.00 | 306.92 | 306.92 | 8.3333 | 31.67 | 8.6167 | |||
| Conditioned Total | 2823.98 | 8607.06 | 1501.17 | 0.00 | 300.26 | 300.26 | 8.7250 | 34.33 | 6.6700 | |||
| Unconditioned Total | 310.64 | 946.78 | 40.87 | 0.00 | 6.66 | 6.66 | 4.7725 | 18.58 | 26.3141 | |||
| Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
| G SW APARTMENT | 88.25 | Yes | Yes | 1.00 | G SW APARTMENT | GENERAL | G SW APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| G NW APARTMENT | 88.25 | Yes | Yes | 1.00 | G NW APARTMENT | GENERAL | G NW APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| OFFICE | 88.25 | Yes | Yes | 1.00 | OFFICE | GENERAL | OFFICE | 9.7532 | 18.58 | 6.6700 | |
| G NE APARTMENT | 88.25 | Yes | Yes | 1.00 | G NE APARTMENT | GENERAL | G NE APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| G N1 APARTMENT | 88.25 | Yes | Yes | 1.00 | G N1 APARTMENT | GENERAL | G N1 APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| G N2 APARTMENT | 88.25 | Yes | Yes | 1.00 | G N2 APARTMENT | GENERAL | G N2 APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| G S1 APARTMENT | 88.25 | Yes | Yes | 1.00 | G S1 APARTMENT | GENERAL | G S1 APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| G S2 APARTMENT | 88.25 | Yes | Yes | 1.00 | G S2 APARTMENT | GENERAL | G S2 APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| M SW APARTMENT | 88.25 | Yes | Yes | 2.00 | M SW APARTMENT | GENERAL | M SW APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| M NW APARTMENT | 88.25 | Yes | Yes | 2.00 | M NW APARTMENT | GENERAL | M NW APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| M SE APARTMENT | 88.25 | Yes | Yes | 2.00 | M SE APARTMENT | GENERAL | M SE APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| M NE APARTMENT | 88.25 | Yes | Yes | 2.00 | M NE APARTMENT | GENERAL | M NE APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| M N1 APARTMENT | 88.25 | Yes | Yes | 2.00 | M N1 APARTMENT | GENERAL | M N1 APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| M N2 APARTMENT | 88.25 | Yes | Yes | 2.00 | M N2 APARTMENT | GENERAL | M N2 APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| M S1 APARTMENT | 88.25 | Yes | Yes | 2.00 | M S1 APARTMENT | GENERAL | M S1 APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| M S2 APARTMENT | 88.25 | Yes | Yes | 2.00 | M S2 APARTMENT | GENERAL | M S2 APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| T SW APARTMENT | 88.25 | Yes | Yes | 1.00 | T SW APARTMENT | GENERAL | T SW APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| T NW APARTMENT | 88.25 | Yes | Yes | 1.00 | T NW APARTMENT | GENERAL | T NW APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| T SE APARTMENT | 88.25 | Yes | Yes | 1.00 | T SE APARTMENT | GENERAL | T SE APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| T NE APARTMENT | 88.25 | Yes | Yes | 1.00 | T NE APARTMENT | GENERAL | T NE APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| T N1 APARTMENT | 88.25 | Yes | Yes | 1.00 | T N1 APARTMENT | GENERAL | T N1 APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| T N2 APARTMENT | 88.25 | Yes | Yes | 1.00 | T N2 APARTMENT | GENERAL | T N2 APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| T S1 APARTMENT | 88.25 | Yes | Yes | 1.00 | T S1 APARTMENT | GENERAL | T S1 APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| T S2 APARTMENT | 88.25 | Yes | Yes | 1.00 | T S2 APARTMENT | GENERAL | T S2 APARTMENT | 8.6918 | 35.30 | 6.6700 | |
| T CORRIDOR | 77.66 | No | Yes | 1.00 | T CORRIDOR | GENERAL | T CORRIDOR | 4.7725 | 18.58 | 0.0000 | |
| G CORRIDOR | 77.66 | No | Yes | 1.00 | G CORRIDOR | GENERAL | G CORRIDOR | 4.7725 | 18.58 | 105.2565 | |
| M CORRIDOR | 77.66 | No | Yes | 2.00 | M CORRIDOR | GENERAL | M CORRIDOR | 4.7725 | 18.58 | 0.0000 | |
| Total | 3134.61 | 8.3333 | 15.84 | 8.6167 | |||||||
| Conditioned Total | 2823.98 | 8.7250 | 17.17 | 6.6700 | |||||||
| Unconditioned Total | 310.64 | 4.7725 | 9.29 | 26.3141 | |||||||
| Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
| Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
| GENERAL | 3134.61 | 2823.98 | 310.64 | 0.00 | 6.2575 | 41.91 | 7.1145 |
| Total | 3134.61 | 2823.98 | 310.64 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 09:14:34
End Uses| Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
| Time of Peak | 26-JUL-17:30 | 28-JAN-05:00 | - | - | - | - | - | - | - | - | - | - | 01-JAN-07:10 |
| Heating | 0.00 | 52342.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Cooling | 26117.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Lighting | 5231.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment | 22609.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans | 8995.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems | 27042.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Total End Uses | 89997.38 | 52342.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
| Heating | General | 0.00 | 52342.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Cooling | General | 26117.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Lighting | LightsWired | 4887.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LightsPlugIn | 344.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment | MiscPlug | 18441.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| ElevatorLift | 4006.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| ElevatorLightsFan | 162.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| General | 8995.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems | Water Heater | 27042.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 09:14:34
Values gathered over 8760.00 hours| Source Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
| Heating | 0.00 | 109.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Cooling | 594.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Lighting | 314.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Lighting | 158.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment | 1452.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans | 357.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems | 1295.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Total Source Energy End Use Components | 4172.35 | 109.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
| Heating | 0.00 | 38.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Cooling | 210.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Lighting | 111.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Lighting | 56.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment | 514.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans | 126.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems | 458.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Total Source Energy End Use Components | 1477.47 | 38.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
| Heating | 0.00 | 34.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Cooling | 189.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Lighting | 100.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Lighting | 50.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment | 463.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans | 114.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems | 413.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Total Source Energy End Use Components | 1331.06 | 34.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 09:14:34
ZoneHVAC:EnergyRecoveryVentilator| User-Specified Supply Air Flow Rate [m3/s] | User-Specified Exhaust Air Flow Rate [m3/s] | |
| G SW APARTMENT ERV | 0.025955 | 0.025955 |
| G NW APARTMENT ERV | 0.025955 | 0.025955 |
| G NE APARTMENT ERV | 0.025955 | 0.025955 |
| G N1 APARTMENT ERV | 0.025955 | 0.025955 |
| G N2 APARTMENT ERV | 0.025955 | 0.025955 |
| G S1 APARTMENT ERV | 0.025955 | 0.025955 |
| G S2 APARTMENT ERV | 0.025955 | 0.025955 |
| M SW APARTMENT ERV | 0.051909 | 0.051909 |
| M NW APARTMENT ERV | 0.051909 | 0.051909 |
| M SE APARTMENT ERV | 0.051909 | 0.051909 |
| M NE APARTMENT ERV | 0.051909 | 0.051909 |
| M N1 APARTMENT ERV | 0.051909 | 0.051909 |
| M N2 APARTMENT ERV | 0.051909 | 0.051909 |
| M S1 APARTMENT ERV | 0.051909 | 0.051909 |
| M S2 APARTMENT ERV | 0.051909 | 0.051909 |
| T SW APARTMENT ERV | 0.025955 | 0.025955 |
| T NW APARTMENT ERV | 0.025955 | 0.025955 |
| T SE APARTMENT ERV | 0.025955 | 0.025955 |
| T NE APARTMENT ERV | 0.025955 | 0.025955 |
| T N1 APARTMENT ERV | 0.025955 | 0.025955 |
| T N2 APARTMENT ERV | 0.025955 | 0.025955 |
| T S1 APARTMENT ERV | 0.025955 | 0.025955 |
| T S2 APARTMENT ERV | 0.025955 | 0.025955 |
| Design Size Maximum Flow Rate [m3/s] | |
| G SW APARTMENT ERV SUP FAN | 0.025955 |
| G SW APARTMENT ERV EXH FAN | 0.025955 |
| G NW APARTMENT ERV SUP FAN | 0.025955 |
| G NW APARTMENT ERV EXH FAN | 0.025955 |
| G NE APARTMENT ERV SUP FAN | 0.025955 |
| G NE APARTMENT ERV EXH FAN | 0.025955 |
| G N1 APARTMENT ERV SUP FAN | 0.025955 |
| G N1 APARTMENT ERV EXH FAN | 0.025955 |
| G N2 APARTMENT ERV SUP FAN | 0.025955 |
| G N2 APARTMENT ERV EXH FAN | 0.025955 |
| G S1 APARTMENT ERV SUP FAN | 0.025955 |
| G S1 APARTMENT ERV EXH FAN | 0.025955 |
| G S2 APARTMENT ERV SUP FAN | 0.025955 |
| G S2 APARTMENT ERV EXH FAN | 0.025955 |
| M SW APARTMENT ERV SUP FAN | 0.051909 |
| M SW APARTMENT ERV EXH FAN | 0.051909 |
| M NW APARTMENT ERV SUP FAN | 0.051909 |
| M NW APARTMENT ERV EXH FAN | 0.051909 |
| M SE APARTMENT ERV SUP FAN | 0.051909 |
| M SE APARTMENT ERV EXH FAN | 0.051909 |
| M NE APARTMENT ERV SUP FAN | 0.051909 |
| M NE APARTMENT ERV EXH FAN | 0.051909 |
| M N1 APARTMENT ERV SUP FAN | 0.051909 |
| M N1 APARTMENT ERV EXH FAN | 0.051909 |
| M N2 APARTMENT ERV SUP FAN | 0.051909 |
| M N2 APARTMENT ERV EXH FAN | 0.051909 |
| M S1 APARTMENT ERV SUP FAN | 0.051909 |
| M S1 APARTMENT ERV EXH FAN | 0.051909 |
| M S2 APARTMENT ERV SUP FAN | 0.051909 |
| M S2 APARTMENT ERV EXH FAN | 0.051909 |
| T SW APARTMENT ERV SUP FAN | 0.025955 |
| T SW APARTMENT ERV EXH FAN | 0.025955 |
| T NW APARTMENT ERV SUP FAN | 0.025955 |
| T NW APARTMENT ERV EXH FAN | 0.025955 |
| T SE APARTMENT ERV SUP FAN | 0.025955 |
| T SE APARTMENT ERV EXH FAN | 0.025955 |
| T NE APARTMENT ERV SUP FAN | 0.025955 |
| T NE APARTMENT ERV EXH FAN | 0.025955 |
| T N1 APARTMENT ERV SUP FAN | 0.025955 |
| T N1 APARTMENT ERV EXH FAN | 0.025955 |
| T N2 APARTMENT ERV SUP FAN | 0.025955 |
| T N2 APARTMENT ERV EXH FAN | 0.025955 |
| T S1 APARTMENT ERV SUP FAN | 0.025955 |
| T S1 APARTMENT ERV EXH FAN | 0.025955 |
| T S2 APARTMENT ERV SUP FAN | 0.025955 |
| T S2 APARTMENT ERV EXH FAN | 0.025955 |
| SPLIT GSW SUPPLY FAN | 0.390163 |
| SPLIT GNW SUPPLY FAN | 0.383303 |
| SPLIT OFFICE SUPPLY FAN | 0.431523 |
| SPLIT GNE SUPPLY FAN | 0.363114 |
| SPLIT GN1 SUPPLY FAN | 0.327118 |
| SPLIT GN2 SUPPLY FAN | 0.326741 |
| SPLIT GS1 SUPPLY FAN | 0.335310 |
| SPLIT GS2 SUPPLY FAN | 0.338014 |
| SPLIT MSW SUPPLY FAN | 0.920617 |
| SPLIT MNW SUPPLY FAN | 0.907626 |
| SPLIT MSE SUPPLY FAN | 0.867439 |
| SPLIT MNE SUPPLY FAN | 0.854606 |
| SPLIT MN1 SUPPLY FAN | 0.759236 |
| SPLIT MN2 SUPPLY FAN | 0.758247 |
| SPLIT MS1 SUPPLY FAN | 0.774339 |
| SPLIT MS2 SUPPLY FAN | 0.773324 |
| SPLIT TSW SUPPLY FAN | 0.517132 |
| SPLIT TNW SUPPLY FAN | 0.514905 |
| SPLIT TSE SUPPLY FAN | 0.476123 |
| SPLIT TNE SUPPLY FAN | 0.473850 |
| SPLIT TN1 SUPPLY FAN | 0.432416 |
| SPLIT TN2 SUPPLY FAN | 0.431010 |
| SPLIT TS1 SUPPLY FAN | 0.435216 |
| SPLIT TS2 SUPPLY FAN | 0.433815 |
| Design Size Nominal Supply Air Flow Rate [m3/s] | |
| G SW APARTMENT OA HEAT EXCHANGER | 0.025955 |
| G NW APARTMENT OA HEAT EXCHANGER | 0.025955 |
| G NE APARTMENT OA HEAT EXCHANGER | 0.025955 |
| G N1 APARTMENT OA HEAT EXCHANGER | 0.025955 |
| G N2 APARTMENT OA HEAT EXCHANGER | 0.025955 |
| G S1 APARTMENT OA HEAT EXCHANGER | 0.025955 |
| G S2 APARTMENT OA HEAT EXCHANGER | 0.025955 |
| M SW APARTMENT OA HEAT EXCHANGER | 0.051909 |
| M NW APARTMENT OA HEAT EXCHANGER | 0.051909 |
| M SE APARTMENT OA HEAT EXCHANGER | 0.051909 |
| M NE APARTMENT OA HEAT EXCHANGER | 0.051909 |
| M N1 APARTMENT OA HEAT EXCHANGER | 0.051909 |
| M N2 APARTMENT OA HEAT EXCHANGER | 0.051909 |
| M S1 APARTMENT OA HEAT EXCHANGER | 0.051909 |
| M S2 APARTMENT OA HEAT EXCHANGER | 0.051909 |
| T SW APARTMENT OA HEAT EXCHANGER | 0.025955 |
| T NW APARTMENT OA HEAT EXCHANGER | 0.025955 |
| T SE APARTMENT OA HEAT EXCHANGER | 0.025955 |
| T NE APARTMENT OA HEAT EXCHANGER | 0.025955 |
| T N1 APARTMENT OA HEAT EXCHANGER | 0.025955 |
| T N2 APARTMENT OA HEAT EXCHANGER | 0.025955 |
| T S1 APARTMENT OA HEAT EXCHANGER | 0.025955 |
| T S2 APARTMENT OA HEAT EXCHANGER | 0.025955 |
| Design Size Maximum Air Flow Rate [m3/s] | |
| G SW APARTMENT DIRECT AIR | 0.390163 |
| G NW APARTMENT DIRECT AIR | 0.383303 |
| OFFICE DIRECT AIR | 0.431523 |
| G NE APARTMENT DIRECT AIR | 0.363114 |
| G N1 APARTMENT DIRECT AIR | 0.327118 |
| G N2 APARTMENT DIRECT AIR | 0.326741 |
| G S1 APARTMENT DIRECT AIR | 0.335310 |
| G S2 APARTMENT DIRECT AIR | 0.338014 |
| M SW APARTMENT DIRECT AIR | 0.920617 |
| M NW APARTMENT DIRECT AIR | 0.907626 |
| M SE APARTMENT DIRECT AIR | 0.867439 |
| M NE APARTMENT DIRECT AIR | 0.854606 |
| M N1 APARTMENT DIRECT AIR | 0.759236 |
| M N2 APARTMENT DIRECT AIR | 0.758247 |
| M S1 APARTMENT DIRECT AIR | 0.774339 |
| M S2 APARTMENT DIRECT AIR | 0.773324 |
| T SW APARTMENT DIRECT AIR | 0.517132 |
| T NW APARTMENT DIRECT AIR | 0.514905 |
| T SE APARTMENT DIRECT AIR | 0.476123 |
| T NE APARTMENT DIRECT AIR | 0.473850 |
| T N1 APARTMENT DIRECT AIR | 0.432416 |
| T N2 APARTMENT DIRECT AIR | 0.431010 |
| T S1 APARTMENT DIRECT AIR | 0.435216 |
| T S2 APARTMENT DIRECT AIR | 0.433815 |
| Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
| SPLIT GSW | 0.390163 | 0.390163 | 0.390163 | 0.390163 | 0.390163 | 0.390163 | 1.00 | 1.00 | 0.390163 |
| SPLIT GNW | 0.383303 | 0.383303 | 0.383303 | 0.383303 | 0.383303 | 0.383303 | 1.00 | 1.00 | 0.383303 |
| SPLIT OFFICE | 0.431523 | 0.431523 | 0.431523 | 0.431523 | 0.431523 | 0.431523 | 1.00 | 1.000000 | 0.431523 |
| SPLIT GNE | 0.363114 | 0.363114 | 0.363114 | 0.363114 | 0.363114 | 0.363114 | 1.00 | 1.00 | 0.363114 |
| SPLIT GN1 | 0.327118 | 0.327118 | 0.327118 | 0.327118 | 0.327118 | 0.327118 | 1.00 | 1.00 | 0.327118 |
| SPLIT GN2 | 0.326741 | 0.326741 | 0.326741 | 0.326741 | 0.326741 | 0.326741 | 1.00 | 1.000000 | 0.326741 |
| SPLIT GS1 | 0.335310 | 0.335310 | 0.335310 | 0.335310 | 0.335310 | 0.335310 | 1.00 | 1.00 | 0.335310 |
| SPLIT GS2 | 0.338014 | 0.338014 | 0.338014 | 0.338014 | 0.338014 | 0.338014 | 1.00 | 1.000000 | 0.338014 |
| SPLIT MSW | 0.920617 | 0.920617 | 0.920617 | 0.920617 | 0.920617 | 0.920617 | 1.00 | 1.00 | 0.920617 |
| SPLIT MNW | 0.907626 | 0.907626 | 0.907626 | 0.907626 | 0.907626 | 0.907626 | 1.00 | 1.00 | 0.907626 |
| SPLIT MSE | 0.867439 | 0.867439 | 0.867439 | 0.867439 | 0.867439 | 0.867439 | 1.00 | 1.00 | 0.867439 |
| SPLIT MNE | 0.854606 | 0.854606 | 0.854606 | 0.854606 | 0.854606 | 0.854606 | 1.00 | 1.00 | 0.854606 |
| SPLIT MN1 | 0.759236 | 0.759236 | 0.759236 | 0.759236 | 0.759236 | 0.759236 | 1.00 | 1.00 | 0.759236 |
| SPLIT MN2 | 0.758247 | 0.758247 | 0.758247 | 0.758247 | 0.758247 | 0.758247 | 1.00 | 1.00 | 0.758247 |
| SPLIT MS1 | 0.774339 | 0.774339 | 0.774339 | 0.774339 | 0.774339 | 0.774339 | 1.00 | 1.00 | 0.774339 |
| SPLIT MS2 | 0.773324 | 0.773324 | 0.773324 | 0.773324 | 0.773324 | 0.773324 | 1.00 | 1.00 | 0.773324 |
| SPLIT TSW | 0.517132 | 0.517132 | 0.517132 | 0.517132 | 0.517132 | 0.517132 | 1.00 | 1.00 | 0.517132 |
| SPLIT TNW | 0.514905 | 0.514905 | 0.514905 | 0.514905 | 0.514905 | 0.514905 | 1.00 | 1.00 | 0.514905 |
| SPLIT TSE | 0.476123 | 0.476123 | 0.476123 | 0.476123 | 0.476123 | 0.476123 | 1.00 | 1.00 | 0.476123 |
| SPLIT TNE | 0.473850 | 0.473850 | 0.473850 | 0.473850 | 0.473850 | 0.473850 | 1.00 | 1.00 | 0.473850 |
| SPLIT TN1 | 0.432416 | 0.432416 | 0.432416 | 0.432416 | 0.432416 | 0.432416 | 1.00 | 1.00 | 0.432416 |
| SPLIT TN2 | 0.431010 | 0.431010 | 0.431010 | 0.431010 | 0.431010 | 0.431010 | 1.00 | 1.00 | 0.431010 |
| SPLIT TS1 | 0.435216 | 0.435216 | 0.435216 | 0.435216 | 0.435216 | 0.435216 | 1.00 | 1.00 | 0.435216 |
| SPLIT TS2 | 0.433815 | 0.433815 | 0.433815 | 0.433815 | 0.433815 | 0.433815 | 1.00 | 1.00 | 0.433815 |
| Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
| SPLIT GSW_OA_CONTROLLER | 0.390163 | 0.025955 |
| SPLIT GNW_OA_CONTROLLER | 0.383303 | 0.025955 |
| SPLIT OFFICE_OA_CONTROLLER | 0.431523 | 0.038106 |
| SPLIT GNE_OA_CONTROLLER | 0.363114 | 0.025955 |
| SPLIT GN1_OA_CONTROLLER | 0.327118 | 0.025955 |
| SPLIT GN2_OA_CONTROLLER | 0.326741 | 0.025955 |
| SPLIT GS1_OA_CONTROLLER | 0.335310 | 0.025955 |
| SPLIT GS2_OA_CONTROLLER | 0.338014 | 0.025955 |
| SPLIT MSW_OA_CONTROLLER | 0.920617 | 0.051909 |
| SPLIT MNW_OA_CONTROLLER | 0.907626 | 0.051909 |
| SPLIT MSE_OA_CONTROLLER | 0.867439 | 0.051909 |
| SPLIT MNE_OA_CONTROLLER | 0.854606 | 0.051909 |
| SPLIT MN1_OA_CONTROLLER | 0.759236 | 0.051909 |
| SPLIT MN2_OA_CONTROLLER | 0.758247 | 0.051909 |
| SPLIT MS1_OA_CONTROLLER | 0.774339 | 0.051909 |
| SPLIT MS2_OA_CONTROLLER | 0.773324 | 0.051909 |
| SPLIT TSW_OA_CONTROLLER | 0.517132 | 0.025955 |
| SPLIT TNW_OA_CONTROLLER | 0.514905 | 0.025955 |
| SPLIT TSE_OA_CONTROLLER | 0.476123 | 0.025955 |
| SPLIT TNE_OA_CONTROLLER | 0.473850 | 0.025955 |
| SPLIT TN1_OA_CONTROLLER | 0.432416 | 0.025955 |
| SPLIT TN2_OA_CONTROLLER | 0.431010 | 0.025955 |
| SPLIT TS1_OA_CONTROLLER | 0.435216 | 0.025955 |
| SPLIT TS2_OA_CONTROLLER | 0.433815 | 0.025955 |
| Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | Design Size Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
| SPLIT GSW_UNITARY_PACKAGE_DX | 0.390163 | 0.390163 | 0.390163 | 0.390163 | 6458.59 | 8454.92 | 40.00 | 1.00 |
| SPLIT GNW_UNITARY_PACKAGE_DX | 0.383303 | 0.383303 | 0.383303 | 0.383303 | 6345.03 | 8318.79 | 40.00 | 1.00 |
| SPLIT OFFICE_UNITARY_PACKAGE_DX | 0.431523 | 0.431523 | 0.431523 | 0.431523 | 7143.23 | 9610.62 | 40.00 | 1.00 |
| SPLIT GNE_UNITARY_PACKAGE_DX | 0.363114 | 0.363114 | 0.363114 | 0.363114 | 6010.82 | 7918.36 | 40.00 | 1.00 |
| SPLIT GN1_UNITARY_PACKAGE_DX | 0.327118 | 0.327118 | 0.327118 | 0.327118 | 5414.96 | 7204.35 | 40.00 | 1.00 |
| SPLIT GN2_UNITARY_PACKAGE_DX | 0.326741 | 0.326741 | 0.326741 | 0.326741 | 5408.73 | 7196.88 | 40.00 | 1.00 |
| SPLIT GS1_UNITARY_PACKAGE_DX | 0.335310 | 0.335310 | 0.335310 | 0.335310 | 5550.57 | 7366.89 | 40.00 | 1.00 |
| SPLIT GS2_UNITARY_PACKAGE_DX | 0.338014 | 0.338014 | 0.338014 | 0.338014 | 5595.34 | 7420.52 | 40.00 | 1.00 |
| SPLIT MSW_UNITARY_PACKAGE_DX | 0.920617 | 0.920617 | 0.920617 | 0.920617 | 15239.47 | 19693.04 | 40.00 | 1.00 |
| SPLIT MNW_UNITARY_PACKAGE_DX | 0.907626 | 0.907626 | 0.907626 | 0.907626 | 15024.43 | 19435.08 | 40.00 | 1.00 |
| SPLIT MSE_UNITARY_PACKAGE_DX | 0.867439 | 0.867439 | 0.867439 | 0.867439 | 14359.20 | 18638.27 | 40.00 | 1.00 |
| SPLIT MNE_UNITARY_PACKAGE_DX | 0.854606 | 0.854606 | 0.854606 | 0.854606 | 14146.76 | 18383.44 | 40.00 | 1.00 |
| SPLIT MN1_UNITARY_PACKAGE_DX | 0.759236 | 0.759236 | 0.759236 | 0.759236 | 12568.06 | 16491.49 | 40.00 | 1.00 |
| SPLIT MN2_UNITARY_PACKAGE_DX | 0.758247 | 0.758247 | 0.758247 | 0.758247 | 12551.67 | 16471.86 | 40.00 | 1.00 |
| SPLIT MS1_UNITARY_PACKAGE_DX | 0.774339 | 0.774339 | 0.774339 | 0.774339 | 12818.06 | 16791.30 | 40.00 | 1.00 |
| SPLIT MS2_UNITARY_PACKAGE_DX | 0.773324 | 0.773324 | 0.773324 | 0.773324 | 12801.27 | 16771.18 | 40.00 | 1.00 |
| SPLIT TSW_UNITARY_PACKAGE_DX | 0.517132 | 0.517132 | 0.517132 | 0.517132 | 8560.37 | 10973.83 | 40.00 | 1.00 |
| SPLIT TNW_UNITARY_PACKAGE_DX | 0.514905 | 0.514905 | 0.514905 | 0.514905 | 8523.51 | 10929.50 | 40.00 | 1.00 |
| SPLIT TSE_UNITARY_PACKAGE_DX | 0.476123 | 0.476123 | 0.476123 | 0.476123 | 7881.53 | 10160.41 | 40.00 | 1.00 |
| SPLIT TNE_UNITARY_PACKAGE_DX | 0.473850 | 0.473850 | 0.473850 | 0.473850 | 7843.91 | 10115.17 | 40.00 | 1.00 |
| SPLIT TN1_UNITARY_PACKAGE_DX | 0.432416 | 0.432416 | 0.432416 | 0.432416 | 7158.02 | 9293.05 | 40.00 | 1.00 |
| SPLIT TN2_UNITARY_PACKAGE_DX | 0.431010 | 0.431010 | 0.431010 | 0.431010 | 7134.74 | 9265.17 | 40.00 | 1.00 |
| SPLIT TS1_UNITARY_PACKAGE_DX | 0.435216 | 0.435216 | 0.435216 | 0.435216 | 7204.37 | 9348.74 | 40.00 | 1.00 |
| SPLIT TS2_UNITARY_PACKAGE_DX | 0.433815 | 0.433815 | 0.433815 | 0.433815 | 7181.18 | 9320.96 | 40.00 | 1.00 |
| Design Size Rated Air Flow Rate [m3/s] | Design Size Gross Rated Total Cooling Capacity [W] | Design Size Gross Rated Sensible Heat Ratio | |
| SPLIT GSW COOLING COIL | 0.390163 | 6458.59 | 0.800655 |
| SPLIT GNW COOLING COIL | 0.383303 | 6345.03 | 0.800655 |
| SPLIT OFFICE COOLING COIL | 0.431523 | 7143.23 | 0.800655 |
| SPLIT GNE COOLING COIL | 0.363114 | 6010.82 | 0.800655 |
| SPLIT GN1 COOLING COIL | 0.327118 | 5414.96 | 0.800655 |
| SPLIT GN2 COOLING COIL | 0.326741 | 5408.73 | 0.800655 |
| SPLIT GS1 COOLING COIL | 0.335310 | 5550.57 | 0.800655 |
| SPLIT GS2 COOLING COIL | 0.338014 | 5595.34 | 0.800655 |
| SPLIT MSW COOLING COIL | 0.920617 | 15239.47 | 0.800655 |
| SPLIT MNW COOLING COIL | 0.907626 | 15024.43 | 0.800655 |
| SPLIT MSE COOLING COIL | 0.867439 | 14359.20 | 0.800655 |
| SPLIT MNE COOLING COIL | 0.854606 | 14146.76 | 0.800655 |
| SPLIT MN1 COOLING COIL | 0.759236 | 12568.06 | 0.800655 |
| SPLIT MN2 COOLING COIL | 0.758247 | 12551.67 | 0.800655 |
| SPLIT MS1 COOLING COIL | 0.774339 | 12818.06 | 0.800655 |
| SPLIT MS2 COOLING COIL | 0.773324 | 12801.27 | 0.800655 |
| SPLIT TSW COOLING COIL | 0.517132 | 8560.37 | 0.800655 |
| SPLIT TNW COOLING COIL | 0.514905 | 8523.51 | 0.800655 |
| SPLIT TSE COOLING COIL | 0.476123 | 7881.53 | 0.800655 |
| SPLIT TNE COOLING COIL | 0.473850 | 7843.91 | 0.800655 |
| SPLIT TN1 COOLING COIL | 0.432416 | 7158.02 | 0.800655 |
| SPLIT TN2 COOLING COIL | 0.431010 | 7134.74 | 0.800655 |
| SPLIT TS1 COOLING COIL | 0.435216 | 7204.37 | 0.800655 |
| SPLIT TS2 COOLING COIL | 0.433815 | 7181.18 | 0.800655 |
| Design Size Nominal Capacity [W] | |
| SPLIT GSW HEATING COIL | 8454.92 |
| SPLIT GNW HEATING COIL | 8318.79 |
| SPLIT OFFICE HEATING COIL | 9610.62 |
| SPLIT GNE HEATING COIL | 7918.36 |
| SPLIT GN1 HEATING COIL | 7204.35 |
| SPLIT GN2 HEATING COIL | 7196.88 |
| SPLIT GS1 HEATING COIL | 7366.89 |
| SPLIT GS2 HEATING COIL | 7420.52 |
| SPLIT MSW HEATING COIL | 19693.04 |
| SPLIT MNW HEATING COIL | 19435.08 |
| SPLIT MSE HEATING COIL | 18638.27 |
| SPLIT MNE HEATING COIL | 18383.44 |
| SPLIT MN1 HEATING COIL | 16491.49 |
| SPLIT MN2 HEATING COIL | 16471.86 |
| SPLIT MS1 HEATING COIL | 16791.30 |
| SPLIT MS2 HEATING COIL | 16771.18 |
| SPLIT TSW HEATING COIL | 10973.83 |
| SPLIT TNW HEATING COIL | 10929.50 |
| SPLIT TSE HEATING COIL | 10160.41 |
| SPLIT TNE HEATING COIL | 10115.17 |
| SPLIT TN1 HEATING COIL | 9293.05 |
| SPLIT TN2 HEATING COIL | 9265.17 |
| SPLIT TS1 HEATING COIL | 9348.74 |
| SPLIT TS2 HEATING COIL | 9320.96 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 09:14:34
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other Surfaces| None |
| Possible Shadow Receivers | |
| G SWALL SWA | GWINDOW1 S SWA | |
| G WWALL SWA | GWINDOW1 W SWA | |
| G NWALL NWA | GWINDOW1 N NWA | |
| G WWALL NWA | GWINDOW1 W NWA | |
| G SWALL SEA | GWINDOW1 S SEA | |
| G EWALL SEA | GWINDOW1 E SEA | |
| G NWALL NEA | GWINDOW1 N NEA | |
| G EWALL NEA | GWINDOW1 E NEA | |
| G NWALL N1A | GWINDOW1 N N1A | |
| G NWALL N2A | GWINDOW1 N N2A | |
| G SWALL S1A | GWINDOW1 S S1A | |
| G SWALL S2A | GWINDOW1 S S2A | |
| M WWALL SWA | MWINDOW1 W SWA | |
| M SWALL SWA | MWINDOW1 S SWA | |
| M NWALL NWA | MWINDOW1 N NWA | |
| M WWALL NWA | MWINDOW1 W NWA | |
| M EWALL SEA | MWINDOW1 E SEA | |
| M SWALL SEA | MWINDOW1 S SEA | |
| M NWALL NEA | MWINDOW1 N NEA | |
| M EWALL NEA | MWINDOW1 E NEA | |
| M NWALL N1A | MWINDOW1 N N1A | |
| M NWALL N2A | MWINDOW1 N N2A | |
| M SWALL S1A | MWINDOW1 S S1A | |
| M SWALL S2A | MWINDOW1 S S2A | |
| T WWALL SWA | TWINDOW1 W SWA | |
| T SWALL SWA | TWINDOW1 S SWA | |
| T NWALL NWA | TWINDOW1 N NWA | |
| T WWALL NWA | TWINDOW1 W NWA | |
| T EWALL SEA | TWINDOW1 E SEA | |
| T SWALL SEA | TWINDOW1 S SEA | |
| T NWALL NEA | TWINDOW1 N NEA | |
| T EWALL NEA | TWINDOW1 E NEA | |
| T NWALL N1A | TWINDOW1 N N1A | |
| T NWALL N2A | TWINDOW1 N N2A | |
| T SWALL S1A | TWINDOW1 S S1A | |
| T SWALL S2A | TWINDOW1 S S2A | |
| T EWALL C | TWINDOW14 | |
| G EWALL C | ENTRANCE DOOR | |
| M EWALL C | MWINDOW14 | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 09:14:34
Time Not Meeting the Adaptive Comfort Models during Occupied Hours| ASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 09:14:34
Version| Version ID | |
| 1 | 22.1 |
| #TimeSteps | Minutes per TimeStep {minutes} | |
| 1 | 6 | 10 |
| Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
| 1 | 1 | 20 | 2 | 8 |
| Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
| 1 | Yes | Yes | No | No | Yes | No |
| Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
| 1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
| Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
| 1 | 0.556 | 0.556 |
| Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
| 1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
| Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
| 1 | 18.30 | 11.20 | 6.80 | 8.10 | 10.30 | 12.50 | 19.20 | 23.80 | 27.90 | 27.50 | 26.30 | 23.40 |
| Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
| 1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
| Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
| 1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
| Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
| 1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
| Normal | Daylighting {dimensionless} | |
| 1 | 1.000 | 1.000 |
| Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
| 1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
| Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
| 1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
| Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
| 1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
| Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
| 1 | El Paso International Ap Ut TX USA TMY3 WMO#=722700 | 31.77 | -106.50 | -7.00 | 1186.00 | 87865 | 1.0443 |
| Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
| 1 | Correlation | NA | 17.94 | 21.10 | NA |
| Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
| 1 | ApartmentMidRise | 0.000 | City | 4.00000E-002 | 0.40000 | FullExterior | 25 | 6 |
| Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
| 1 | TARP |
| Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
| 1 | TARP |
| Value {Anisotropic} | |
| 1 | Anisotropic |
| Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
| 1 | ThirdOrderBackwardDifference |
| Simulation {Yes/No} | Carbon Dioxide Concentration | |
| 1 | No | N/A |
| Simulation {Yes/No} | Generic Contaminant Concentration | |
| 1 | No | N/A |
| Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
| 1 | No | N/A | N/A | N/A |
| Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
| 1 | RegulaFalsi |
| Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
| 1 | 0.330 | 460.000 | 6.500000E-003 |
| Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
| 1 | LowerLeftCorner | Clockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
| Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
| 1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
| Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
| 1 | 0 | 0 | 0 |
| Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
| 1 | 27 | 243 | 39 |
| Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
| 1 | G SW APARTMENT | 0.0 | 0.00 | 0.00 | 0.00 | 5.79 | 3.81 | 1.52 | 1 | 1 | 1 | 0.00 | 11.58 | 0.00 | 7.62 | 0.00 | 3.05 | 3.05 | 268.97 | TARP | TARP | 88.25 | 58.52 | 46.82 | 11.71 | 6 | 2 | 0 | Yes |
| 2 | G NW APARTMENT | 0.0 | 0.00 | 9.30 | 0.00 | 5.79 | 13.11 | 1.52 | 1 | 1 | 1 | 0.00 | 11.58 | 9.30 | 16.92 | 0.00 | 3.05 | 3.05 | 268.97 | TARP | TARP | 88.25 | 58.52 | 46.82 | 11.71 | 6 | 2 | 0 | Yes |
| 3 | OFFICE | 0.0 | 34.75 | 0.00 | 0.00 | 40.54 | 3.81 | 1.52 | 1 | 1 | 1 | 34.75 | 46.33 | 0.00 | 7.62 | 0.00 | 3.05 | 3.05 | 268.97 | TARP | TARP | 88.25 | 58.52 | 46.82 | 11.71 | 6 | 2 | 0 | Yes |
| 4 | G NE APARTMENT | 0.0 | 34.75 | 9.30 | 0.00 | 40.54 | 13.11 | 1.52 | 1 | 1 | 1 | 34.75 | 46.33 | 9.30 | 16.92 | 0.00 | 3.05 | 3.05 | 268.97 | TARP | TARP | 88.25 | 58.52 | 46.82 | 11.71 | 6 | 2 | 0 | Yes |
| 5 | G N1 APARTMENT | 0.0 | 11.58 | 9.30 | 0.00 | 17.37 | 13.11 | 1.52 | 1 | 1 | 1 | 11.58 | 23.16 | 9.30 | 16.92 | 0.00 | 3.05 | 3.05 | 268.97 | TARP | TARP | 88.25 | 35.30 | 28.24 | 7.06 | 6 | 1 | 0 | Yes |
| 6 | G N2 APARTMENT | 0.0 | 23.16 | 9.30 | 0.00 | 28.95 | 13.11 | 1.52 | 1 | 1 | 1 | 23.16 | 34.75 | 9.30 | 16.92 | 0.00 | 3.05 | 3.05 | 268.97 | TARP | TARP | 88.25 | 35.30 | 28.24 | 7.06 | 6 | 1 | 0 | Yes |
| 7 | G S1 APARTMENT | 0.0 | 11.58 | 0.00 | 0.00 | 17.37 | 3.81 | 1.52 | 1 | 1 | 1 | 11.58 | 23.16 | 0.00 | 7.62 | 0.00 | 3.05 | 3.05 | 268.97 | TARP | TARP | 88.25 | 35.30 | 28.24 | 7.06 | 6 | 1 | 0 | Yes |
| 8 | G S2 APARTMENT | 0.0 | 23.16 | 0.00 | 0.00 | 28.95 | 3.81 | 1.52 | 1 | 1 | 1 | 23.16 | 34.75 | 0.00 | 7.62 | 0.00 | 3.05 | 3.05 | 268.97 | TARP | TARP | 88.25 | 35.30 | 28.24 | 7.06 | 6 | 1 | 0 | Yes |
| 9 | M SW APARTMENT | 0.0 | 0.00 | 0.00 | 3.05 | 5.79 | 3.81 | 4.57 | 1 | 1 | 2 | 0.00 | 11.58 | 0.00 | 7.62 | 3.05 | 6.10 | 3.05 | 268.97 | TARP | TARP | 88.25 | 58.52 | 46.82 | 11.71 | 6 | 2 | 0 | Yes |
| 10 | M NW APARTMENT | 0.0 | 0.00 | 9.30 | 3.05 | 5.79 | 13.11 | 4.57 | 1 | 1 | 2 | 0.00 | 11.58 | 9.30 | 16.92 | 3.05 | 6.10 | 3.05 | 268.97 | TARP | TARP | 88.25 | 58.52 | 46.82 | 11.71 | 6 | 2 | 0 | Yes |
| 11 | M SE APARTMENT | 0.0 | 34.75 | 0.00 | 3.05 | 40.54 | 3.81 | 4.57 | 1 | 1 | 2 | 34.75 | 46.33 | 0.00 | 7.62 | 3.05 | 6.10 | 3.05 | 268.97 | TARP | TARP | 88.25 | 58.52 | 46.82 | 11.71 | 6 | 2 | 0 | Yes |
| 12 | M NE APARTMENT | 0.0 | 34.75 | 9.30 | 3.05 | 40.54 | 13.11 | 4.57 | 1 | 1 | 2 | 34.75 | 46.33 | 9.30 | 16.92 | 3.05 | 6.10 | 3.05 | 268.97 | TARP | TARP | 88.25 | 58.52 | 46.82 | 11.71 | 6 | 2 | 0 | Yes |
| 13 | M N1 APARTMENT | 0.0 | 11.58 | 9.30 | 3.05 | 17.37 | 13.11 | 4.57 | 1 | 1 | 2 | 11.58 | 23.16 | 9.30 | 16.92 | 3.05 | 6.10 | 3.05 | 268.97 | TARP | TARP | 88.25 | 35.30 | 28.24 | 7.06 | 6 | 1 | 0 | Yes |
| 14 | M N2 APARTMENT | 0.0 | 23.16 | 9.30 | 3.05 | 28.95 | 13.11 | 4.57 | 1 | 1 | 2 | 23.16 | 34.75 | 9.30 | 16.92 | 3.05 | 6.10 | 3.05 | 268.97 | TARP | TARP | 88.25 | 35.30 | 28.24 | 7.06 | 6 | 1 | 0 | Yes |
| 15 | M S1 APARTMENT | 0.0 | 11.58 | 0.00 | 3.05 | 17.37 | 3.81 | 4.57 | 1 | 1 | 2 | 11.58 | 23.16 | 0.00 | 7.62 | 3.05 | 6.10 | 3.05 | 268.97 | TARP | TARP | 88.25 | 35.30 | 28.24 | 7.06 | 6 | 1 | 0 | Yes |
| 16 | M S2 APARTMENT | 0.0 | 23.16 | 0.00 | 3.05 | 28.95 | 3.81 | 4.57 | 1 | 1 | 2 | 23.16 | 34.75 | 0.00 | 7.62 | 3.05 | 6.10 | 3.05 | 268.97 | TARP | TARP | 88.25 | 35.30 | 28.24 | 7.06 | 6 | 1 | 0 | Yes |
| 17 | T SW APARTMENT | 0.0 | 0.00 | 0.00 | 9.14 | 5.79 | 3.81 | 10.67 | 1 | 1 | 1 | 0.00 | 11.58 | 0.00 | 7.62 | 9.14 | 12.19 | 3.05 | 268.97 | TARP | TARP | 88.25 | 58.52 | 46.82 | 11.71 | 6 | 2 | 0 | Yes |
| 18 | T NW APARTMENT | 0.0 | 0.00 | 9.30 | 9.14 | 5.79 | 13.11 | 10.67 | 1 | 1 | 1 | 0.00 | 11.58 | 9.30 | 16.92 | 9.14 | 12.19 | 3.05 | 268.97 | TARP | TARP | 88.25 | 58.52 | 46.82 | 11.71 | 6 | 2 | 0 | Yes |
| 19 | T SE APARTMENT | 0.0 | 34.75 | 0.00 | 9.14 | 40.54 | 3.81 | 10.67 | 1 | 1 | 1 | 34.75 | 46.33 | 0.00 | 7.62 | 9.14 | 12.19 | 3.05 | 268.97 | TARP | TARP | 88.25 | 58.52 | 46.82 | 11.71 | 6 | 2 | 0 | Yes |
| 20 | T NE APARTMENT | 0.0 | 34.75 | 9.30 | 9.14 | 40.54 | 13.11 | 10.67 | 1 | 1 | 1 | 34.75 | 46.33 | 9.30 | 16.92 | 9.14 | 12.19 | 3.05 | 268.97 | TARP | TARP | 88.25 | 58.52 | 46.82 | 11.71 | 6 | 2 | 0 | Yes |
| 21 | T N1 APARTMENT | 0.0 | 11.58 | 9.30 | 9.14 | 17.37 | 13.11 | 10.67 | 1 | 1 | 1 | 11.58 | 23.16 | 9.30 | 16.92 | 9.14 | 12.19 | 3.05 | 268.97 | TARP | TARP | 88.25 | 35.30 | 28.24 | 7.06 | 6 | 1 | 0 | Yes |
| 22 | T N2 APARTMENT | 0.0 | 23.16 | 9.30 | 9.14 | 28.95 | 13.11 | 10.67 | 1 | 1 | 1 | 23.16 | 34.75 | 9.30 | 16.92 | 9.14 | 12.19 | 3.05 | 268.97 | TARP | TARP | 88.25 | 35.30 | 28.24 | 7.06 | 6 | 1 | 0 | Yes |
| 23 | T S1 APARTMENT | 0.0 | 11.58 | 0.00 | 9.14 | 17.37 | 3.81 | 10.67 | 1 | 1 | 1 | 11.58 | 23.16 | 0.00 | 7.62 | 9.14 | 12.19 | 3.05 | 268.97 | TARP | TARP | 88.25 | 35.30 | 28.24 | 7.06 | 6 | 1 | 0 | Yes |
| 24 | T S2 APARTMENT | 0.0 | 23.16 | 0.00 | 9.14 | 28.95 | 3.81 | 10.67 | 1 | 1 | 1 | 23.16 | 34.75 | 0.00 | 7.62 | 9.14 | 12.19 | 3.05 | 268.97 | TARP | TARP | 88.25 | 35.30 | 28.24 | 7.06 | 6 | 1 | 0 | Yes |
| 25 | T CORRIDOR | 0.0 | 0.00 | 7.62 | 9.14 | 23.16 | 8.46 | 10.67 | 1 | 1 | 1 | 0.00 | 46.33 | 7.62 | 9.30 | 9.14 | 12.19 | 3.05 | 236.69 | TARP | TARP | 77.66 | 10.22 | 9.10 | 1.11 | 12 | 1 | 0 | Yes |
| 26 | G CORRIDOR | 0.0 | 0.00 | 7.62 | 0.00 | 23.16 | 8.46 | 1.52 | 1 | 1 | 1 | 0.00 | 46.33 | 7.62 | 9.30 | 0.00 | 3.05 | 3.05 | 236.69 | TARP | TARP | 77.66 | 10.22 | 6.90 | 3.32 | 12 | 1 | 0 | Yes |
| 27 | M CORRIDOR | 0.0 | 0.00 | 7.62 | 3.05 | 23.16 | 8.46 | 4.57 | 1 | 1 | 2 | 0.00 | 46.33 | 7.62 | 9.30 | 3.05 | 6.10 | 3.05 | 236.69 | TARP | TARP | 77.66 | 10.22 | 9.10 | 1.11 | 12 | 1 | 0 | Yes |
| Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
| 1 | G SW APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 2 | G NW APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 3 | OFFICE | 88.25 | 4.7 | 18.581 | 5.382E-002 | 9.753 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 16.423 | No |
| 4 | G NE APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 5 | G N1 APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 6 | G N2 APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 7 | G S1 APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 8 | G S2 APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 9 | M SW APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 10 | M NW APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 11 | M SE APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 12 | M NE APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 13 | M N1 APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 14 | M N2 APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 15 | M S1 APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 16 | M S2 APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 17 | T SW APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 18 | T NW APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 19 | T SE APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 20 | T NE APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 21 | T N1 APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 22 | T N2 APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 23 | T S1 APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 24 | T S2 APARTMENT | 88.25 | 2.5 | 35.300 | 2.833E-002 | 8.692 | 6.670 | 0.000 | 0.000 | 0.000 | 0.000 | 15.362 | No |
| 25 | T CORRIDOR | 77.66 | 4.2 | 18.579 | 5.382E-002 | 4.772 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 4.772 | No |
| 26 | G CORRIDOR | 77.66 | 4.2 | 18.579 | 5.382E-002 | 4.772 | 105.256 | 0.000 | 0.000 | 0.000 | 0.000 | 110.029 | No |
| 27 | M CORRIDOR | 77.66 | 4.2 | 18.579 | 5.382E-002 | 4.772 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 4.772 | No |
| Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | |
| 1 | OCCUP_GSW | OCC_APT_SCH_WORKING_FAMILY | G SW APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 3 |
| 2 | OCCUP_GNW | OCC_APT_SCH_STAY_HOME_FAMILY | G NW APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 1 | 3 |
| 3 | OCCUP_OFFICE | OCC_OFF_W_SB_SCH | OFFICE | 88.25 | 4.7 | 4.7 | 5.382E-002 | 18.581 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 5 |
| 4 | OCCUP_GNE | OCC_APT_SCH_STAY_HOME_FAMILY | G NE APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 1 | 3 |
| 5 | OCCUP_GN1 | OCC_APT_SCH_STAY_HOME_FAMILY | G N1 APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 1 | 3 |
| 6 | OCCUP_GN2 | OCC_APT_SCH_STAY_HOME_FAMILY | G N2 APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 1 | 3 |
| 7 | OCCUP_GS1 | OCC_APT_SCH_WORKING_FAMILY | G S1 APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 3 |
| 8 | OCCUP_GS2 | OCC_APT_SCH_WORKING_FAMILY | G S2 APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 3 |
| 9 | OCCUP_MSW | OCC_APT_SCH_WORKING_FAMILY | M SW APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 3 |
| 10 | OCCUP_MNW | OCC_APT_SCH_STAY_HOME_FAMILY | M NW APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 1 | 3 |
| 11 | OCCUP_MSE | OCC_APT_SCH_WORKING_FAMILY | M SE APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 3 |
| 12 | OCCUP_MNE | OCC_APT_SCH_STAY_HOME_FAMILY | M NE APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 1 | 3 |
| 13 | OCCUP_MN1 | OCC_APT_SCH_STAY_HOME_FAMILY | M N1 APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 1 | 3 |
| 14 | OCCUP_MN2 | OCC_APT_SCH_STAY_HOME_FAMILY | M N2 APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 1 | 3 |
| 15 | OCCUP_MS1 | OCC_APT_SCH_WORKING_FAMILY | M S1 APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 3 |
| 16 | OCCUP_MS2 | OCC_APT_SCH_WORKING_FAMILY | M S2 APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 3 |
| 17 | OCCUP_TSW | OCC_APT_SCH_WORKING_FAMILY | T SW APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 3 |
| 18 | OCCUP_TNW | OCC_APT_SCH_STAY_HOME_FAMILY | T NW APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 1 | 3 |
| 19 | OCCUP_TSE | OCC_APT_SCH_WORKING_FAMILY | T SE APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 3 |
| 20 | OCCUP_TNE | OCC_APT_SCH_STAY_HOME_FAMILY | T NE APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 1 | 3 |
| 21 | OCCUP_TN1 | OCC_APT_SCH_STAY_HOME_FAMILY | T N1 APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 1 | 3 |
| 22 | OCCUP_TN2 | OCC_APT_SCH_STAY_HOME_FAMILY | T N2 APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 1 | 3 |
| 23 | OCCUP_TS1 | OCC_APT_SCH_WORKING_FAMILY | T S1 APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 3 |
| 24 | OCCUP_TS2 | OCC_APT_SCH_WORKING_FAMILY | T S2 APARTMENT | 88.25 | 2.5 | 2.5 | 2.833E-002 | 35.300 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 3 |
| 25 | OCCUP_T CORRIDOR | OCC_APT_SCH_CORRIDOR | T CORRIDOR | 77.66 | 4.2 | 4.2 | 5.382E-002 | 18.579 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 1 | 4 |
| 26 | OCCUP_G CORRIDOR | OCC_APT_SCH_CORRIDOR | G CORRIDOR | 77.66 | 4.2 | 4.2 | 5.382E-002 | 18.579 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 1 | 4 |
| 27 | OCCUP_M CORRIDOR | OCC_APT_SCH_CORRIDOR | M CORRIDOR | 77.66 | 4.2 | 4.2 | 5.382E-002 | 18.579 | 1.000 | 0.000 | AutoCalculate | ACTIVITY SCHEDULE | No | 3.8200E-008 | 1 | 4 |
| Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
| 1 | LIGHTING_HARDWIRED_GSW | LTG_SCH_APARTMENT_HARDWIRED | G SW APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 2 | LIGHTING_HARDWIRED_GNW | LTG_SCH_APARTMENT_HARDWIRED | G NW APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 3 | LIGHTING_HARDWIRED_OFFICE | LTG_SCH_OFFICE | OFFICE | 88.25 | 4.7 | 860.710 | 9.753 | 181.220 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 860.710 |
| 4 | LIGHTING_HARDWIRED_GNE | LTG_SCH_APARTMENT_HARDWIRED | G NE APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 5 | LIGHTING_HARDWIRED_GN1 | LTG_SCH_APARTMENT_HARDWIRED | G N1 APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 6 | LIGHTING_HARDWIRED_GN2 | LTG_SCH_APARTMENT_HARDWIRED | G N2 APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 7 | LIGHTING_HARDWIRED_GS1 | LTG_SCH_APARTMENT_HARDWIRED | G S1 APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 8 | LIGHTING_HARDWIRED_GS2 | LTG_SCH_APARTMENT_HARDWIRED | G S2 APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 9 | LIGHTING_HARDWIRED_MSW | LTG_SCH_APARTMENT_HARDWIRED | M SW APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 10 | LIGHTING_HARDWIRED_MNW | LTG_SCH_APARTMENT_HARDWIRED | M NW APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 11 | LIGHTING_HARDWIRED_MSE | LTG_SCH_APARTMENT_HARDWIRED | M SE APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 12 | LIGHTING_HARDWIRED_MNE | LTG_SCH_APARTMENT_HARDWIRED | M NE APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 13 | LIGHTING_HARDWIRED_MN1 | LTG_SCH_APARTMENT_HARDWIRED | M N1 APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 14 | LIGHTING_HARDWIRED_MN2 | LTG_SCH_APARTMENT_HARDWIRED | M N2 APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 15 | LIGHTING_HARDWIRED_MS1 | LTG_SCH_APARTMENT_HARDWIRED | M S1 APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 16 | LIGHTING_HARDWIRED_MS2 | LTG_SCH_APARTMENT_HARDWIRED | M S2 APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 17 | LIGHTING_HARDWIRED_TSW | LTG_SCH_APARTMENT_HARDWIRED | T SW APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 18 | LIGHTING_HARDWIRED_TNW | LTG_SCH_APARTMENT_HARDWIRED | T NW APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 19 | LIGHTING_HARDWIRED_TSE | LTG_SCH_APARTMENT_HARDWIRED | T SE APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 20 | LIGHTING_HARDWIRED_TNE | LTG_SCH_APARTMENT_HARDWIRED | T NE APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 21 | LIGHTING_HARDWIRED_TN1 | LTG_SCH_APARTMENT_HARDWIRED | T N1 APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 22 | LIGHTING_HARDWIRED_TN2 | LTG_SCH_APARTMENT_HARDWIRED | T N2 APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 23 | LIGHTING_HARDWIRED_TS1 | LTG_SCH_APARTMENT_HARDWIRED | T S1 APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 24 | LIGHTING_HARDWIRED_TS2 | LTG_SCH_APARTMENT_HARDWIRED | T S2 APARTMENT | 88.25 | 2.5 | 694.381 | 7.868 | 277.753 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 694.381 |
| 25 | LIGHTING_HARDWIRED_GC | LTG_SCH_CORRIDOR | G CORRIDOR | 77.66 | 4.2 | 370.628 | 4.772 | 88.667 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 370.628 |
| 26 | LIGHTING_HARDWIRED_MC | LTG_SCH_CORRIDOR | M CORRIDOR | 77.66 | 4.2 | 370.628 | 4.772 | 88.667 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 370.628 |
| 27 | LIGHTING_HARDWIRED_TC | LTG_SCH_CORRIDOR | T CORRIDOR | 77.66 | 4.2 | 370.628 | 4.772 | 88.667 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsWired | 0.000 | 370.628 |
| 28 | LIGHTING_PLUGIN_GSW | LTG_SCH_APARTMENT_PLUGIN | G SW APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| 29 | LIGHTING_PLUGIN_GNW | LTG_SCH_APARTMENT_PLUGIN | G NW APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| 30 | LIGHTING_PLUGIN_GNE | LTG_SCH_APARTMENT_PLUGIN | G NE APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| 31 | LIGHTING_PLUGIN_GN1 | LTG_SCH_APARTMENT_PLUGIN | G N1 APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| 32 | LIGHTING_PLUGIN_GN2 | LTG_SCH_APARTMENT_PLUGIN | G N2 APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| 33 | LIGHTING_PLUGIN_GS1 | LTG_SCH_APARTMENT_PLUGIN | G S1 APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| 34 | LIGHTING_PLUGIN_GS2 | LTG_SCH_APARTMENT_PLUGIN | G S2 APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| 35 | LIGHTING_PLUGIN_MSW | LTG_SCH_APARTMENT_PLUGIN | M SW APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| 36 | LIGHTING_PLUGIN_MNW | LTG_SCH_APARTMENT_PLUGIN | M NW APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| 37 | LIGHTING_PLUGIN_MSE | LTG_SCH_APARTMENT_PLUGIN | M SE APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| 38 | LIGHTING_PLUGIN_MNE | LTG_SCH_APARTMENT_PLUGIN | M NE APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| 39 | LIGHTING_PLUGIN_MN1 | LTG_SCH_APARTMENT_PLUGIN | M N1 APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| 40 | LIGHTING_PLUGIN_MN2 | LTG_SCH_APARTMENT_PLUGIN | M N2 APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| 41 | LIGHTING_PLUGIN_MS1 | LTG_SCH_APARTMENT_PLUGIN | M S1 APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| 42 | LIGHTING_PLUGIN_MS2 | LTG_SCH_APARTMENT_PLUGIN | M S2 APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| 43 | LIGHTING_PLUGIN_TSW | LTG_SCH_APARTMENT_PLUGIN | T SW APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| 44 | LIGHTING_PLUGIN_TNW | LTG_SCH_APARTMENT_PLUGIN | T NW APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| 45 | LIGHTING_PLUGIN_TSE | LTG_SCH_APARTMENT_PLUGIN | T SE APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| 46 | LIGHTING_PLUGIN_TNE | LTG_SCH_APARTMENT_PLUGIN | T NE APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| 47 | LIGHTING_PLUGIN_TN1 | LTG_SCH_APARTMENT_PLUGIN | T N1 APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| 48 | LIGHTING_PLUGIN_TN2 | LTG_SCH_APARTMENT_PLUGIN | T N2 APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| 49 | LIGHTING_PLUGIN_TS1 | LTG_SCH_APARTMENT_PLUGIN | T S1 APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| 50 | LIGHTING_PLUGIN_TS2 | LTG_SCH_APARTMENT_PLUGIN | T S2 APARTMENT | 88.25 | 2.5 | 72.668 | 0.823 | 29.067 | 0.000 | 0.600 | 0.200 | 0.200 | 1.000 | LightsPlugIn | 0.000 | 72.668 |
| Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
| 1 | PLUG_GSW | EQP_APT_SCH | G SW APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 2 | PLUG_GNW | EQP_APT_SCH | G NW APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 3 | PLUG_OFFICE | EQP_OFF_SCH | OFFICE | 88.25 | 4.7 | 588.623 | 6.670 | 123.933 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 588.623 |
| 4 | PLUG_GNE | EQP_APT_SCH | G NE APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 5 | PLUG_GN1 | EQP_APT_SCH | G N1 APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 6 | PLUG_GN2 | EQP_APT_SCH | G N2 APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 7 | PLUG_GS1 | EQP_APT_SCH | G S1 APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 8 | PLUG_GS2 | EQP_APT_SCH | G S2 APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 9 | PLUG_MSW | EQP_APT_SCH | M SW APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 10 | PLUG_MNW | EQP_APT_SCH | M NW APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 11 | PLUG_MSE | EQP_APT_SCH | M SE APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 12 | PLUG_MNE | EQP_APT_SCH | M NE APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 13 | PLUG_MN1 | EQP_APT_SCH | M N1 APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 14 | PLUG_MN2 | EQP_APT_SCH | M N2 APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 15 | PLUG_MS1 | EQP_APT_SCH | M S1 APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 16 | PLUG_MS2 | EQP_APT_SCH | M S2 APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 17 | PLUG_TSW | EQP_APT_SCH | T SW APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 18 | PLUG_TNW | EQP_APT_SCH | T NW APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 19 | PLUG_TSE | EQP_APT_SCH | T SE APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 20 | PLUG_TNE | EQP_APT_SCH | T NE APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 21 | PLUG_TN1 | EQP_APT_SCH | T N1 APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 22 | PLUG_TN2 | EQP_APT_SCH | T N2 APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 23 | PLUG_TS1 | EQP_APT_SCH | T S1 APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 24 | PLUG_TS2 | EQP_APT_SCH | T S2 APARTMENT | 88.25 | 2.5 | 588.623 | 6.670 | 235.449 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 223.677 | 588.623 |
| 25 | G CORRIDOR_ELEVATORS_EQUIP | BLDG_ELEVATORS | G CORRIDOR | 77.66 | 4.2 | 8012.150 | 103.170 | 1916.782 | 0.000 | 0.000 | 0.950 | 5.000E-002 | ElevatorLift | 961.458 | 4006.075 |
| 26 | ELEVATORS_LIGHTS_FAN | ELEV_LIGHT_FAN_SCH_24_7 | G CORRIDOR | 77.66 | 4.2 | 162.000 | 2.086 | 38.756 | 0.000 | 0.000 | 0.950 | 5.000E-002 | ElevatorLightsFan | 162.000 | 162.000 |
| Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
| 1 | PolygonClipping | Periodic | 20 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
| Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
| 1 | WaterHeater:Mixed | G SW APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.496 | 0.7729 |
| 2 | WaterHeater:Mixed | G NW APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.496 | 0.7729 |
| 3 | WaterHeater:Mixed | G NE APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.496 | 0.7729 |
| 4 | WaterHeater:Mixed | G N1 APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.496 | 0.7729 |
| 5 | WaterHeater:Mixed | G N2 APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.496 | 0.7729 |
| 6 | WaterHeater:Mixed | G S1 APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.496 | 0.7729 |
| 7 | WaterHeater:Mixed | G S2 APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.496 | 0.7729 |
| 8 | WaterHeater:Mixed | M SW APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.498 | 0.7911 |
| 9 | WaterHeater:Mixed | M NW APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.498 | 0.7911 |
| 10 | WaterHeater:Mixed | M SE APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.498 | 0.7911 |
| 11 | WaterHeater:Mixed | M NE APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.498 | 0.7911 |
| 12 | WaterHeater:Mixed | M N1 APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.498 | 0.7911 |
| 13 | WaterHeater:Mixed | M N2 APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.498 | 0.7911 |
| 14 | WaterHeater:Mixed | M S1 APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.498 | 0.7911 |
| 15 | WaterHeater:Mixed | M S2 APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.498 | 0.7911 |
| 16 | WaterHeater:Mixed | T SW APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.496 | 0.7729 |
| 17 | WaterHeater:Mixed | T NW APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.496 | 0.7729 |
| 18 | WaterHeater:Mixed | T SE APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.496 | 0.7729 |
| 19 | WaterHeater:Mixed | T NE APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.496 | 0.7729 |
| 20 | WaterHeater:Mixed | T N1 APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.496 | 0.7729 |
| 21 | WaterHeater:Mixed | T N2 APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.496 | 0.7729 |
| 22 | WaterHeater:Mixed | T S1 APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.496 | 0.7729 |
| 23 | WaterHeater:Mixed | T S2 APARTMENT WATER HEATER | 0.1892 | 14653.5 | 1.496 | 0.7729 |
| Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
| 1 | G SWALL SWA | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 2 | GWINDOW1 S SWA | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 3 | G WWALL SWA | 0 | 154.67 | 58.21 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 4 | GWINDOW1 W SWA | 0 | 154.67 | 58.21 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 5 | G NIWALL SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 6 | G EIWALL SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 7 | G GFLOOR SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 8 | G CEILIN SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 9 | G INTERNALMASS SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 10 | G NWALL NWA | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 11 | GWINDOW1 N NWA | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 12 | G WWALL NWA | 0 | 154.67 | 58.21 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 13 | GWINDOW1 W NWA | 0 | 154.67 | 58.21 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 14 | G SIWALL NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 15 | G EIWALL NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 16 | G GFLOOR NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 17 | G CEILIN NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 18 | G INTERNALMASS NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 19 | G SWALL SEA | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 20 | GWINDOW1 S SEA | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 21 | G EWALL SEA | 0 | 154.67 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 22 | GWINDOW1 E SEA | 0 | 154.67 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 23 | G NIWALL SEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 24 | iz-G EIWALL S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 25 | G GFLOOR SEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 26 | G CEILIN SEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 27 | G INTERNALMASS SEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 28 | G NWALL NEA | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 29 | GWINDOW1 N NEA | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 30 | G EWALL NEA | 0 | 154.67 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 31 | GWINDOW1 E NEA | 0 | 154.67 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 32 | G SIWALL NEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 33 | iz-G EIWALL N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 34 | G GFLOOR NEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 35 | G CEILIN NEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 36 | G INTERNALMASS NEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 37 | G NWALL N1A | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 3 | No | No |
| 38 | GWINDOW1 N N1A | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 2 | No | No |
| 39 | G SIWALL N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 40 | G EIWALL N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 41 | iz-G EIWALL NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 42 | G GFLOOR N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 43 | G CEILIN N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 44 | G INTERNALMASS N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 45 | G NWALL N2A | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 3 | No | No |
| 46 | GWINDOW1 N N2A | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 2 | No | No |
| 47 | G SIWALL N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 48 | G EIWALL N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 49 | iz-G EIWALL N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 50 | G GFLOOR N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 51 | G CEILIN N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 52 | G INTERNALMASS N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 53 | G SWALL S1A | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 3 | No | No |
| 54 | GWINDOW1 S S1A | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 2 | No | No |
| 55 | G NIWALL S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 56 | G EIWALL S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 57 | iz-G EIWALL SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 58 | G GFLOOR S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 59 | G CEILIN S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 60 | G INTERNALMASS S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 61 | G SWALL S2A | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 3 | No | No |
| 62 | GWINDOW1 S S2A | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 2 | No | No |
| 63 | G NIWALL S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 64 | G EIWALL S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 65 | iz-G EIWALL S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 66 | G GFLOOR S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 67 | G CEILIN S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 68 | G INTERNALMASS S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 69 | M WWALL SWA | 0 | 154.67 | 58.21 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 70 | MWINDOW1 W SWA | 0 | 154.67 | 58.21 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 71 | M SWALL SWA | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 72 | MWINDOW1 S SWA | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 73 | M NIWALL SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 74 | M EIWALL SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 75 | M GFLOOR SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 76 | M CEILIN SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 77 | M INTERNALMASS SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 78 | M NWALL NWA | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 79 | MWINDOW1 N NWA | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 80 | M WWALL NWA | 0 | 154.67 | 58.21 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 81 | MWINDOW1 W NWA | 0 | 154.67 | 58.21 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 82 | M SIWALL NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 83 | M EIWALL NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 84 | M GFLOOR NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 85 | M CEILIN NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 86 | M INTERNALMASS NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 87 | M EWALL SEA | 0 | 154.67 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 88 | MWINDOW1 E SEA | 0 | 154.67 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 89 | M SWALL SEA | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 90 | MWINDOW1 S SEA | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 91 | M NIWALL SEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 92 | iz-M EIWALL S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 93 | M GFLOOR SEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 94 | M CEILIN SEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 95 | M INTERNALMASS SEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 96 | M NWALL NEA | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 97 | MWINDOW1 N NEA | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 98 | M EWALL NEA | 0 | 154.67 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 99 | MWINDOW1 E NEA | 0 | 154.67 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 100 | M SIWALL NEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 101 | iz-M EIWALL N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 102 | M GFLOOR NEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 103 | M CEILIN NEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 104 | M INTERNALMASS NEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 105 | M NWALL N1A | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 3 | No | No |
| 106 | MWINDOW1 N N1A | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 2 | No | No |
| 107 | M SIWALL N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 108 | M EIWALL N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 109 | iz-M EIWALL NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 110 | M GFLOOR N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 111 | M CEILIN N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 112 | M INTERNALMASS N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 113 | M NWALL N2A | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 3 | No | No |
| 114 | MWINDOW1 N N2A | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 2 | No | No |
| 115 | M SIWALL N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 116 | M EIWALL N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 117 | iz-M EIWALL N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 118 | M GFLOOR N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 119 | M CEILIN N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 120 | M INTERNALMASS N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 121 | M SWALL S1A | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 3 | No | No |
| 122 | MWINDOW1 S S1A | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 2 | No | No |
| 123 | M NIWALL S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 124 | M EIWALL S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 125 | iz-M EIWALL SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 126 | M GFLOOR S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 127 | M CEILIN S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 128 | M INTERNALMASS S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 129 | M SWALL S2A | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 3 | No | No |
| 130 | MWINDOW1 S S2A | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 2 | No | No |
| 131 | M NIWALL S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 132 | M EIWALL S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 133 | iz-M EIWALL S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 134 | M GFLOOR S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 135 | M CEILIN S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 136 | M INTERNALMASS S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 137 | T WWALL SWA | 0 | 154.67 | 58.21 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 138 | TWINDOW1 W SWA | 0 | 154.67 | 58.21 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 139 | T SWALL SWA | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 140 | TWINDOW1 S SWA | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 141 | T NIWALL SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 142 | T EIWALL SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 143 | T GFLOOR SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 144 | T ROOF SWA | 0 | 783.65 | 155.90 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 145 | T INTERNALMASS SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 146 | T NWALL NWA | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 147 | TWINDOW1 N NWA | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 148 | T WWALL NWA | 0 | 154.67 | 58.21 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 149 | TWINDOW1 W NWA | 0 | 154.67 | 58.21 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 150 | T SIWALL NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 151 | T EIWALL NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 152 | T GFLOOR NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 153 | T ROOF NWA | 0 | 783.65 | 155.90 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 154 | T INTERNALMASS NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 155 | T EWALL SEA | 0 | 154.67 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 156 | TWINDOW1 E SEA | 0 | 154.67 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 157 | T SWALL SEA | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 158 | TWINDOW1 S SEA | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 159 | T NIWALL SEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 160 | iz-T EIWALL S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 161 | T GFLOOR SEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 162 | T ROOF SEA | 0 | 783.65 | 155.90 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 163 | T INTERNALMASS SEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 164 | T NWALL NEA | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 165 | TWINDOW1 N NEA | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 166 | T EWALL NEA | 0 | 154.67 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 3 | No | No |
| 167 | TWINDOW1 E NEA | 0 | 154.67 | 123.02 | 12.19 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 2 | No | No |
| 168 | T SIWALL NEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 169 | iz-T EIWALL N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 170 | T GFLOOR NEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 171 | T ROOF NEA | 0 | 783.65 | 155.90 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 172 | T INTERNALMASS NEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 19.20 | 9.19 | 0.20 | 0 | No | No |
| 173 | T NWALL N1A | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 3 | No | No |
| 174 | TWINDOW1 N N1A | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 2 | No | No |
| 175 | T SIWALL N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 176 | T EIWALL N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 177 | iz-T EIWALL NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 178 | T GFLOOR N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 179 | T ROOF N1A | 0 | 783.65 | 155.90 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 180 | T INTERNALMASS N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 181 | T NWALL N2A | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 3 | No | No |
| 182 | TWINDOW1 N N2A | 0 | 423.60 | 123.02 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 2 | No | No |
| 183 | T SIWALL N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 184 | T EIWALL N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 185 | iz-T EIWALL N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 186 | T GFLOOR N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 187 | T ROOF N2A | 0 | 783.65 | 155.90 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 188 | T INTERNALMASS N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 189 | T SWALL S1A | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 3 | No | No |
| 190 | TWINDOW1 S S1A | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 2 | No | No |
| 191 | T NIWALL S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 192 | T EIWALL S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 193 | iz-T EIWALL SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 194 | T GFLOOR S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 195 | T ROOF S1A | 0 | 783.65 | 155.90 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 196 | T INTERNALMASS S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 197 | T SWALL S2A | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 3 | No | No |
| 198 | TWINDOW1 S S2A | 0 | 423.60 | 117.04 | 12.19 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 2 | No | No |
| 199 | T NIWALL S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 200 | T EIWALL S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 201 | iz-T EIWALL S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 202 | T GFLOOR S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 203 | T ROOF S2A | 0 | 783.65 | 155.90 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 204 | T INTERNALMASS S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 11.58 | 9.19 | 0.20 | 0 | No | No |
| 205 | T WWALL C | 0 | 154.67 | 58.21 | 12.19 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 3 | No | No |
| 206 | T EWALL C | 0 | 154.67 | 123.02 | 12.19 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 3 | No | No |
| 207 | TWINDOW14 | 0 | 154.67 | 123.02 | 12.19 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 2 | No | No |
| 208 | iz-T NIWALL SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 209 | iz-T NIWALL S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 210 | iz-T NIWALL S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 211 | iz-T NIWALL SEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 212 | iz-T SIWALL NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 213 | iz-T SIWALL N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 214 | iz-T SIWALL N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 215 | iz-T SIWALL NEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 216 | T FLOOR C | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 217 | T ROOF C | 0 | 783.65 | 155.90 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 218 | G WWALL C | 0 | 154.67 | 58.21 | 12.19 | 0 | 3.05 | 3.35 | 3.24 | 0.32 | 4 | No | No |
| 219 | G EWALL C | 0 | 154.67 | 123.02 | 12.19 | 0 | 3.05 | 3.35 | 3.24 | 0.32 | 4 | No | No |
| 220 | ENTRANCE DOOR | 0 | 154.67 | 123.02 | 12.19 | 0 | 3.05 | 3.35 | 3.24 | 0.32 | 1 | No | No |
| 221 | iz-G NIWALL SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.32 | 0 | No | No |
| 222 | iz-G NIWALL S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.32 | 0 | No | No |
| 223 | iz-G NIWALL S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.32 | 0 | No | No |
| 224 | iz-G NIWALL SEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.32 | 0 | No | No |
| 225 | iz-G SIWALL NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.32 | 0 | No | No |
| 226 | iz-G SIWALL N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.32 | 0 | No | No |
| 227 | iz-G SIWALL N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.32 | 0 | No | No |
| 228 | iz-G SIWALL NEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.32 | 0 | No | No |
| 229 | G FLOOR C | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.32 | 0 | No | No |
| 230 | G CEILING C | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.32 | 0 | No | No |
| 231 | M WWALL C | 0 | 154.67 | 58.21 | 12.19 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 4 | No | No |
| 232 | M EWALL C | 0 | 154.67 | 123.02 | 12.19 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 3 | No | No |
| 233 | MWINDOW14 | 0 | 154.67 | 123.02 | 12.19 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 2 | No | No |
| 234 | iz-M NIWALL SWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 235 | iz-M NIWALL S1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 236 | iz-M NIWALL S2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 237 | iz-M NIWALL SEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 238 | iz-M SIWALL NWA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 239 | iz-M SIWALL N1A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 240 | iz-M SIWALL N2A | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 241 | iz-M SIWALL NEA | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 242 | M FLOOR C | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| 243 | M CEILING C | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.35 | 3.24 | 0.11 | 0 | No | No |
| Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
| 1 | INFIL_GSW | INF_APT_SCH | G SW APARTMENT | 88.25 | 2.5 | 6.000E-002 | 6.799E-004 | 1.025E-003 | 0.803 | 0.000 | 0.000 | 0.224 | 0.000 |
| 2 | INFIL_GNW | INF_APT_SCH | G NW APARTMENT | 88.25 | 2.5 | 6.000E-002 | 6.799E-004 | 1.025E-003 | 0.803 | 0.000 | 0.000 | 0.224 | 0.000 |
| 3 | INFIL_OFFICE | INF_OFF_SCH | OFFICE | 88.25 | 4.7 | 6.000E-002 | 6.799E-004 | 1.025E-003 | 0.803 | 0.000 | 0.000 | 0.224 | 0.000 |
| 4 | INFIL_GNE | INF_APT_SCH | G NE APARTMENT | 88.25 | 2.5 | 6.000E-002 | 6.799E-004 | 1.025E-003 | 0.803 | 0.000 | 0.000 | 0.224 | 0.000 |
| 5 | INFIL_GN1 | INF_APT_SCH | G N1 APARTMENT | 88.25 | 2.5 | 3.619E-002 | 4.101E-004 | 1.025E-003 | 0.484 | 0.000 | 0.000 | 0.224 | 0.000 |
| 6 | INFIL_GN2 | INF_APT_SCH | G N2 APARTMENT | 88.25 | 2.5 | 3.619E-002 | 4.101E-004 | 1.025E-003 | 0.484 | 0.000 | 0.000 | 0.224 | 0.000 |
| 7 | INFIL_GS1 | INF_APT_SCH | G S1 APARTMENT | 88.25 | 2.5 | 3.619E-002 | 4.101E-004 | 1.025E-003 | 0.484 | 0.000 | 0.000 | 0.224 | 0.000 |
| 8 | INFIL_GS2 | INF_APT_SCH | G S2 APARTMENT | 88.25 | 2.5 | 3.619E-002 | 4.101E-004 | 1.025E-003 | 0.484 | 0.000 | 0.000 | 0.224 | 0.000 |
| 9 | INFIL_MSW | INF_APT_SCH | M SW APARTMENT | 88.25 | 2.5 | 6.000E-002 | 6.799E-004 | 1.025E-003 | 0.803 | 0.000 | 0.000 | 0.224 | 0.000 |
| 10 | INFIL_MNW | INF_APT_SCH | M NW APARTMENT | 88.25 | 2.5 | 6.000E-002 | 6.799E-004 | 1.025E-003 | 0.803 | 0.000 | 0.000 | 0.224 | 0.000 |
| 11 | INFIL_MSE | INF_APT_SCH | M SE APARTMENT | 88.25 | 2.5 | 6.000E-002 | 6.799E-004 | 1.025E-003 | 0.803 | 0.000 | 0.000 | 0.224 | 0.000 |
| 12 | INFIL_MNE | INF_APT_SCH | M NE APARTMENT | 88.25 | 2.5 | 6.000E-002 | 6.799E-004 | 1.025E-003 | 0.803 | 0.000 | 0.000 | 0.224 | 0.000 |
| 13 | INFIL_MN1 | INF_APT_SCH | M N1 APARTMENT | 88.25 | 2.5 | 3.619E-002 | 4.101E-004 | 1.025E-003 | 0.484 | 0.000 | 0.000 | 0.224 | 0.000 |
| 14 | INFIL_MN2 | INF_APT_SCH | M N2 APARTMENT | 88.25 | 2.5 | 3.619E-002 | 4.101E-004 | 1.025E-003 | 0.484 | 0.000 | 0.000 | 0.224 | 0.000 |
| 15 | INFIL_MS1 | INF_APT_SCH | M S1 APARTMENT | 88.25 | 2.5 | 3.619E-002 | 4.101E-004 | 1.025E-003 | 0.484 | 0.000 | 0.000 | 0.224 | 0.000 |
| 16 | INFIL_MS2 | INF_APT_SCH | M S2 APARTMENT | 88.25 | 2.5 | 3.619E-002 | 4.101E-004 | 1.025E-003 | 0.484 | 0.000 | 0.000 | 0.224 | 0.000 |
| 17 | INFIL_SW | INF_APT_SCH | T SW APARTMENT | 88.25 | 2.5 | 6.000E-002 | 6.799E-004 | 4.088E-004 | 0.803 | 0.000 | 0.000 | 0.224 | 0.000 |
| 18 | INFIL_NW | INF_APT_SCH | T NW APARTMENT | 88.25 | 2.5 | 6.000E-002 | 6.799E-004 | 4.088E-004 | 0.803 | 0.000 | 0.000 | 0.224 | 0.000 |
| 19 | INFIL_SE | INF_APT_SCH | T SE APARTMENT | 88.25 | 2.5 | 6.000E-002 | 6.799E-004 | 4.088E-004 | 0.803 | 0.000 | 0.000 | 0.224 | 0.000 |
| 20 | INFIL_NE | INF_APT_SCH | T NE APARTMENT | 88.25 | 2.5 | 6.000E-002 | 6.799E-004 | 4.088E-004 | 0.803 | 0.000 | 0.000 | 0.224 | 0.000 |
| 21 | INFIL_TN1 | INF_APT_SCH | T N1 APARTMENT | 88.25 | 2.5 | 3.619E-002 | 4.101E-004 | 2.929E-004 | 0.484 | 0.000 | 0.000 | 0.224 | 0.000 |
| 22 | INFIL_TN2 | INF_APT_SCH | T N2 APARTMENT | 88.25 | 2.5 | 3.619E-002 | 4.101E-004 | 2.929E-004 | 0.484 | 0.000 | 0.000 | 0.224 | 0.000 |
| 23 | INFIL_TS1 | INF_APT_SCH | T S1 APARTMENT | 88.25 | 2.5 | 3.619E-002 | 4.101E-004 | 2.929E-004 | 0.484 | 0.000 | 0.000 | 0.224 | 0.000 |
| 24 | INFIL_TS2 | INF_APT_SCH | T S2 APARTMENT | 88.25 | 2.5 | 3.619E-002 | 4.101E-004 | 2.929E-004 | 0.484 | 0.000 | 0.000 | 0.224 | 0.000 |
| 25 | INFIL_GC | INF_COR_SCH | G CORRIDOR | 77.66 | 4.2 | 1.048E-002 | 1.349E-004 | 1.025E-003 | 0.159 | 0.000 | 0.000 | 0.224 | 0.000 |
| 26 | DOOR_INFIL_GC | INFIL_DOOR_OPENING_SCH | G CORRIDOR | 77.66 | 4.2 | 0.521 | 6.703E-003 | 5.094E-002 | 7.917 | 1.000 | 0.000 | 0.000 | 0.000 |
| 27 | INFIL_MC | INF_COR_SCH | M CORRIDOR | 77.66 | 4.2 | 1.048E-002 | 1.349E-004 | 1.025E-003 | 0.159 | 0.000 | 0.000 | 0.224 | 0.000 |
| 28 | INFIL_TC | INF_COR_SCH | T CORRIDOR | 77.66 | 4.2 | 1.048E-002 | 1.349E-004 | 1.192E-004 | 0.159 | 0.000 | 0.000 | 0.224 | 0.000 |
| Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
| 1 | G SW APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | G SW APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 2 | G NW APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | G NW APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 3 | G NE APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | G NE APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 4 | G N1 APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | G N1 APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 5 | G N2 APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | G N2 APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 6 | G S1 APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | G S1 APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 7 | G S2 APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | G S2 APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 8 | M SW APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | M SW APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 9 | M NW APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | M NW APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 10 | M SE APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | M SE APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 11 | M NE APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | M NE APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 12 | M N1 APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | M N1 APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 13 | M N2 APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | M N2 APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 14 | M S1 APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | M S1 APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 15 | M S2 APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | M S2 APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 16 | T SW APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | T SW APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 17 | T NW APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | T NW APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 18 | T SE APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | T SE APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 19 | T NE APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | T NE APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 20 | T N1 APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | T N1 APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 21 | T N2 APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | T N2 APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 22 | T S1 APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | T S1 APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 23 | T S2 APARTMENT SLIDING DOOR VENTILATION | Constant-0.0 | T S2 APARTMENT | 88.25 | 2.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| Simple | |
| 1 | Simple |
| Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
| 1 | G SW APARTMENT | Mixing/Well-Stirred |
| 2 | G NW APARTMENT | Mixing/Well-Stirred |
| 3 | OFFICE | Mixing/Well-Stirred |
| 4 | G NE APARTMENT | Mixing/Well-Stirred |
| 5 | G N1 APARTMENT | Mixing/Well-Stirred |
| 6 | G N2 APARTMENT | Mixing/Well-Stirred |
| 7 | G S1 APARTMENT | Mixing/Well-Stirred |
| 8 | G S2 APARTMENT | Mixing/Well-Stirred |
| 9 | M SW APARTMENT | Mixing/Well-Stirred |
| 10 | M NW APARTMENT | Mixing/Well-Stirred |
| 11 | M SE APARTMENT | Mixing/Well-Stirred |
| 12 | M NE APARTMENT | Mixing/Well-Stirred |
| 13 | M N1 APARTMENT | Mixing/Well-Stirred |
| 14 | M N2 APARTMENT | Mixing/Well-Stirred |
| 15 | M S1 APARTMENT | Mixing/Well-Stirred |
| 16 | M S2 APARTMENT | Mixing/Well-Stirred |
| 17 | T SW APARTMENT | Mixing/Well-Stirred |
| 18 | T NW APARTMENT | Mixing/Well-Stirred |
| 19 | T SE APARTMENT | Mixing/Well-Stirred |
| 20 | T NE APARTMENT | Mixing/Well-Stirred |
| 21 | T N1 APARTMENT | Mixing/Well-Stirred |
| 22 | T N2 APARTMENT | Mixing/Well-Stirred |
| 23 | T S1 APARTMENT | Mixing/Well-Stirred |
| 24 | T S2 APARTMENT | Mixing/Well-Stirred |
| 25 | T CORRIDOR | Mixing/Well-Stirred |
| 26 | G CORRIDOR | Mixing/Well-Stirred |
| 27 | M CORRIDOR | Mixing/Well-Stirred |
| No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
| 1 | NoMultizoneOrDistribution |
| Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
| 1 | 1.000 | 1.000 | 1.000 | 1.000 |
| Value | |
| 1 | 6 |
| Sizing Factor ID | Value | |
| 1 | Global | 1.2000 |
| 2 | Zone G SW APARTMENT | 1.2000 |
| 3 | Zone G NW APARTMENT | 1.2000 |
| 4 | Zone OFFICE | 1.2000 |
| 5 | Zone G NE APARTMENT | 1.2000 |
| 6 | Zone G N1 APARTMENT | 1.2000 |
| 7 | Zone G N2 APARTMENT | 1.2000 |
| 8 | Zone G S1 APARTMENT | 1.2000 |
| 9 | Zone G S2 APARTMENT | 1.2000 |
| 10 | Zone M SW APARTMENT | 1.2000 |
| 11 | Zone M NW APARTMENT | 1.2000 |
| 12 | Zone M SE APARTMENT | 1.2000 |
| 13 | Zone M NE APARTMENT | 1.2000 |
| 14 | Zone M N1 APARTMENT | 1.2000 |
| 15 | Zone M N2 APARTMENT | 1.2000 |
| 16 | Zone M S1 APARTMENT | 1.2000 |
| 17 | Zone M S2 APARTMENT | 1.2000 |
| 18 | Zone T SW APARTMENT | 1.2000 |
| 19 | Zone T NW APARTMENT | 1.2000 |
| 20 | Zone T SE APARTMENT | 1.2000 |
| 21 | Zone T NE APARTMENT | 1.2000 |
| 22 | Zone T N1 APARTMENT | 1.2000 |
| 23 | Zone T N2 APARTMENT | 1.2000 |
| 24 | Zone T S1 APARTMENT | 1.2000 |
| 25 | Zone T S2 APARTMENT | 1.2000 |
| Sizing Factor ID | Value | |
| 1 | Global | 1.2000 |
| 2 | Zone G SW APARTMENT | 1.2000 |
| 3 | Zone G NW APARTMENT | 1.2000 |
| 4 | Zone OFFICE | 1.2000 |
| 5 | Zone G NE APARTMENT | 1.2000 |
| 6 | Zone G N1 APARTMENT | 1.2000 |
| 7 | Zone G N2 APARTMENT | 1.2000 |
| 8 | Zone G S1 APARTMENT | 1.2000 |
| 9 | Zone G S2 APARTMENT | 1.2000 |
| 10 | Zone M SW APARTMENT | 1.2000 |
| 11 | Zone M NW APARTMENT | 1.2000 |
| 12 | Zone M SE APARTMENT | 1.2000 |
| 13 | Zone M NE APARTMENT | 1.2000 |
| 14 | Zone M N1 APARTMENT | 1.2000 |
| 15 | Zone M N2 APARTMENT | 1.2000 |
| 16 | Zone M S1 APARTMENT | 1.2000 |
| 17 | Zone M S2 APARTMENT | 1.2000 |
| 18 | Zone T SW APARTMENT | 1.2000 |
| 19 | Zone T NW APARTMENT | 1.2000 |
| 20 | Zone T SE APARTMENT | 1.2000 |
| 21 | Zone T NE APARTMENT | 1.2000 |
| 22 | Zone T N1 APARTMENT | 1.2000 |
| 23 | Zone T N2 APARTMENT | 1.2000 |
| 24 | Zone T S1 APARTMENT | 1.2000 |
| 25 | Zone T S2 APARTMENT | 1.2000 |
| Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
| 1 | G SW APARTMENT | Cooling | 3982.52086 | 4779.02503 | 0.32514 | 0.39016 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 33.03000 | 6.86340E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 2 | G SW APARTMENT | Heating | 1400.90202 | 1681.08242 | 6.96016E-002 | 8.35219E-002 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:50:00 | -5.20000 | 2.80840E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 3 | G NW APARTMENT | Cooling | 3914.14491 | 4696.97389 | 0.31942 | 0.38330 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 33.03000 | 6.86340E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 4 | G NW APARTMENT | Heating | 1290.28352 | 1548.34023 | 6.41062E-002 | 7.69274E-002 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | -5.20000 | 2.80840E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 5 | OFFICE | Cooling | 4250.78148 | 5100.93777 | 0.35960 | 0.43152 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:20:00 | 31.68667 | 6.86128E-003 | 88.24927 | 4.74953 | 3.81060E-002 | 0.00000 |
| 6 | OFFICE | Heating | 1841.50039 | 2209.80047 | 9.14920E-002 | 0.10979 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 18:50:00 | -5.20000 | 2.80840E-003 | 88.24927 | 4.74953 | 3.81060E-002 | 0.00000 |
| 7 | G NE APARTMENT | Cooling | 3712.96225 | 4455.55471 | 0.30259 | 0.36311 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 33.03000 | 6.86340E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 8 | G NE APARTMENT | Heating | 1294.72022 | 1553.66426 | 6.43266E-002 | 7.71919E-002 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | -5.20000 | 2.80840E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 9 | G N1 APARTMENT | Cooling | 3352.80247 | 4023.36296 | 0.27260 | 0.32712 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 33.03000 | 6.86340E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 10 | G N1 APARTMENT | Heating | 736.73477 | 884.08172 | 3.66042E-002 | 4.39250E-002 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | -5.20000 | 2.80840E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 11 | G N2 APARTMENT | Cooling | 3349.02251 | 4018.82701 | 0.27228 | 0.32674 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 33.03000 | 6.86340E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 12 | G N2 APARTMENT | Heating | 736.87548 | 884.25058 | 3.66112E-002 | 4.39334E-002 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | -5.20000 | 2.80840E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 13 | G S1 APARTMENT | Cooling | 3435.17323 | 4122.20788 | 0.27942 | 0.33531 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 33.03000 | 6.86340E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 14 | G S1 APARTMENT | Heating | 849.10496 | 1018.92595 | 4.21868E-002 | 5.06242E-002 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:50:00 | -5.20000 | 2.80840E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 15 | G S2 APARTMENT | Cooling | 3462.17636 | 4154.61163 | 0.28168 | 0.33801 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 33.03000 | 6.86340E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 16 | G S2 APARTMENT | Heating | 857.74199 | 1029.29039 | 4.26159E-002 | 5.11391E-002 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:50:00 | -5.20000 | 2.80840E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 17 | M SW APARTMENT | Cooling | 9370.61672 | 11244.74007 | 0.76718 | 0.92062 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 33.03000 | 6.86340E-003 | 88.24927 | 2.50000 | 5.19091E-002 | 0.00000 |
| 18 | M SW APARTMENT | Heating | 2845.13371 | 3414.16046 | 0.14135 | 0.16962 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | -5.20000 | 2.80840E-003 | 88.24927 | 2.50000 | 5.19091E-002 | 0.00000 |
| 19 | M NW APARTMENT | Cooling | 9240.34658 | 11088.41589 | 0.75635 | 0.90763 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 33.03000 | 6.86340E-003 | 88.24927 | 2.50000 | 5.19091E-002 | 0.00000 |
| 20 | M NW APARTMENT | Heating | 2575.66675 | 3090.80010 | 0.12797 | 0.15356 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | -5.20000 | 2.80840E-003 | 88.24927 | 2.50000 | 5.19091E-002 | 0.00000 |
| 21 | M SE APARTMENT | Cooling | 8836.48808 | 10603.78570 | 0.72287 | 0.86744 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 33.03000 | 6.86340E-003 | 88.24927 | 2.50000 | 5.19091E-002 | 0.00000 |
| 22 | M SE APARTMENT | Heating | 2855.99979 | 3427.19975 | 0.14189 | 0.17027 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | -5.20000 | 2.80840E-003 | 88.24927 | 2.50000 | 5.19091E-002 | 0.00000 |
| 23 | M NE APARTMENT | Cooling | 8708.07343 | 10449.68811 | 0.71217 | 0.85461 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 33.03000 | 6.86340E-003 | 88.24927 | 2.50000 | 5.19091E-002 | 0.00000 |
| 24 | M NE APARTMENT | Heating | 2586.58489 | 3103.90187 | 0.12851 | 0.15421 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | -5.20000 | 2.80840E-003 | 88.24927 | 2.50000 | 5.19091E-002 | 0.00000 |
| 25 | M N1 APARTMENT | Cooling | 7754.83691 | 9305.80429 | 0.63270 | 0.75924 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 33.03000 | 6.86340E-003 | 88.24927 | 2.50000 | 5.19091E-002 | 0.00000 |
| 26 | M N1 APARTMENT | Heating | 1287.45593 | 1544.94711 | 6.39654E-002 | 7.67585E-002 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | -5.20000 | 2.80840E-003 | 88.24927 | 2.50000 | 5.19091E-002 | 0.00000 |
| 27 | M N2 APARTMENT | Cooling | 7744.96449 | 9293.95739 | 0.63187 | 0.75825 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 33.03000 | 6.86340E-003 | 88.24927 | 2.50000 | 5.19091E-002 | 0.00000 |
| 28 | M N2 APARTMENT | Heating | 1287.75443 | 1545.30532 | 6.39802E-002 | 7.67763E-002 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | -5.20000 | 2.80840E-003 | 88.24927 | 2.50000 | 5.19091E-002 | 0.00000 |
| 29 | M S1 APARTMENT | Cooling | 7905.40271 | 9486.48325 | 0.64528 | 0.77434 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 33.03000 | 6.86340E-003 | 88.24927 | 2.50000 | 5.19091E-002 | 0.00000 |
| 30 | M S1 APARTMENT | Heating | 1550.03627 | 1860.04352 | 7.70099E-002 | 9.24119E-002 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | -5.20000 | 2.80840E-003 | 88.24927 | 2.50000 | 5.19091E-002 | 0.00000 |
| 31 | M S2 APARTMENT | Cooling | 7895.27567 | 9474.33081 | 0.64444 | 0.77332 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 33.03000 | 6.86340E-003 | 88.24927 | 2.50000 | 5.19091E-002 | 0.00000 |
| 32 | M S2 APARTMENT | Heating | 1550.33062 | 1860.39674 | 7.70245E-002 | 9.24294E-002 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | -5.20000 | 2.80840E-003 | 88.24927 | 2.50000 | 5.19091E-002 | 0.00000 |
| 33 | T SW APARTMENT | Cooling | 5255.17475 | 6306.20970 | 0.43094 | 0.51713 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 33.03000 | 6.86340E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 34 | T SW APARTMENT | Heating | 2586.68204 | 3104.01845 | 0.12851 | 0.15421 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | -5.20000 | 2.80840E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 35 | T NW APARTMENT | Cooling | 5232.96517 | 6279.55820 | 0.42909 | 0.51491 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 33.03000 | 6.86340E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 36 | T NW APARTMENT | Heating | 2445.22590 | 2934.27108 | 0.12148 | 0.14578 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | -5.20000 | 2.80840E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 37 | T SE APARTMENT | Cooling | 4845.70657 | 5814.84788 | 0.39677 | 0.47612 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 33.03000 | 6.86340E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 38 | T SE APARTMENT | Heating | 2594.00083 | 3112.80100 | 0.12887 | 0.15465 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | -5.20000 | 2.80840E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 39 | T NE APARTMENT | Cooling | 4823.06057 | 5787.67268 | 0.39488 | 0.47385 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 33.03000 | 6.86340E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 40 | T NE APARTMENT | Heating | 2452.61095 | 2943.13314 | 0.12185 | 0.14622 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | -5.20000 | 2.80840E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 41 | T N1 APARTMENT | Cooling | 4408.69445 | 5290.43334 | 0.36035 | 0.43242 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 33.03000 | 6.86340E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 42 | T N1 APARTMENT | Heating | 1693.38387 | 2032.06065 | 8.41322E-002 | 0.10096 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | -5.20000 | 2.80840E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 43 | T N2 APARTMENT | Cooling | 4394.56830 | 5273.48196 | 0.35917 | 0.43101 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 33.03000 | 6.86340E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 44 | T N2 APARTMENT | Heating | 1693.59832 | 2032.31798 | 8.41429E-002 | 0.10097 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | -5.20000 | 2.80840E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 45 | T S1 APARTMENT | Cooling | 4436.85264 | 5324.22317 | 0.36268 | 0.43522 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 33.03000 | 6.86340E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 46 | T S1 APARTMENT | Heating | 1835.24172 | 2202.29007 | 9.11784E-002 | 0.10941 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | -5.20000 | 2.80840E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 47 | T S2 APARTMENT | Cooling | 4422.77635 | 5307.33162 | 0.36151 | 0.43382 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 33.03000 | 6.86340E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| 48 | T S2 APARTMENT | Heating | 1835.45263 | 2202.54315 | 9.11889E-002 | 0.10943 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | -5.20000 | 2.80840E-003 | 88.24927 | 2.50000 | 2.59546E-002 | 0.00000 |
| System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
| 1 | SPLIT GSW | Cooling | Sensible | 4850.04 | 0.39016 | 0.39016 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 2 | SPLIT GSW | Heating | Sensible | 2372.91 | 8.35219E-002 | 8.35219E-002 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:50:00 |
| 3 | SPLIT GNW | Cooling | Sensible | 4768.78 | 0.38330 | 0.38330 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 4 | SPLIT GNW | Heating | Sensible | 2242.11 | 7.69274E-002 | 7.69274E-002 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 |
| 5 | SPLIT OFFICE | Cooling | Sensible | 5338.01 | 0.43152 | 0.43152 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 6 | SPLIT OFFICE | Heating | Sensible | 3229.30 | 0.10979 | 0.10979 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 18:50:00 |
| 7 | SPLIT GNE | Cooling | Sensible | 4529.42 | 0.36311 | 0.36311 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 8 | SPLIT GNE | Heating | Sensible | 2247.35 | 7.71919E-002 | 7.71919E-002 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 |
| 9 | SPLIT GN1 | Cooling | Sensible | 4101.94 | 0.32712 | 0.32712 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 10 | SPLIT GN1 | Heating | Sensible | 1587.53 | 4.39250E-002 | 4.39250E-002 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 |
| 11 | SPLIT GN2 | Cooling | Sensible | 4097.46 | 0.32674 | 0.32674 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 12 | SPLIT GN2 | Heating | Sensible | 1587.70 | 4.39334E-002 | 4.39334E-002 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 |
| 13 | SPLIT GS1 | Cooling | Sensible | 4199.41 | 0.33531 | 0.33531 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 14 | SPLIT GS1 | Heating | Sensible | 1720.41 | 5.06242E-002 | 5.06242E-002 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:50:00 |
| 15 | SPLIT GS2 | Cooling | Sensible | 4231.41 | 0.33801 | 0.33801 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 16 | SPLIT GS2 | Heating | Sensible | 1730.62 | 5.11391E-002 | 5.11391E-002 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:50:00 |
| 17 | SPLIT MSW | Cooling | Sensible | 11365.71 | 0.92062 | 0.92062 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 18 | SPLIT MSW | Heating | Sensible | 4797.02 | 0.16962 | 0.16962 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 |
| 19 | SPLIT MNW | Cooling | Sensible | 11211.58 | 0.90763 | 0.90763 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 20 | SPLIT MNW | Heating | Sensible | 4478.39 | 0.15356 | 0.15356 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 |
| 21 | SPLIT MSE | Cooling | Sensible | 10733.78 | 0.86744 | 0.86744 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 22 | SPLIT MSE | Heating | Sensible | 4809.87 | 0.17027 | 0.17027 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 |
| 23 | SPLIT MNE | Cooling | Sensible | 10581.62 | 0.85461 | 0.85461 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 24 | SPLIT MNE | Heating | Sensible | 4491.30 | 0.15421 | 0.15421 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 |
| 25 | SPLIT MN1 | Cooling | Sensible | 9450.37 | 0.75924 | 0.75924 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 26 | SPLIT MN1 | Heating | Sensible | 2955.08 | 7.67585E-002 | 7.67585E-002 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 |
| 27 | SPLIT MN2 | Cooling | Sensible | 9438.63 | 0.75825 | 0.75825 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 28 | SPLIT MN2 | Heating | Sensible | 2955.43 | 7.67763E-002 | 7.67763E-002 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 |
| 29 | SPLIT MS1 | Cooling | Sensible | 9629.27 | 0.77434 | 0.77434 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 30 | SPLIT MS1 | Heating | Sensible | 3265.57 | 9.24119E-002 | 9.24119E-002 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 |
| 31 | SPLIT MS2 | Cooling | Sensible | 9617.24 | 0.77332 | 0.77332 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 32 | SPLIT MS2 | Heating | Sensible | 3265.92 | 9.24294E-002 | 9.24294E-002 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 |
| 33 | SPLIT TSW | Cooling | Sensible | 6357.39 | 0.51713 | 0.51713 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 34 | SPLIT TSW | Heating | Sensible | 3775.09 | 0.15421 | 0.15421 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 |
| 35 | SPLIT TNW | Cooling | Sensible | 6331.06 | 0.51491 | 0.51491 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 36 | SPLIT TNW | Heating | Sensible | 3607.83 | 0.14578 | 0.14578 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 |
| 37 | SPLIT TSE | Cooling | Sensible | 5871.72 | 0.47612 | 0.47612 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 38 | SPLIT TSE | Heating | Sensible | 3783.75 | 0.15465 | 0.15465 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 |
| 39 | SPLIT TNE | Cooling | Sensible | 5844.86 | 0.47385 | 0.47385 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 40 | SPLIT TNE | Heating | Sensible | 3616.56 | 0.14622 | 0.14622 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 |
| 41 | SPLIT TN1 | Cooling | Sensible | 5353.74 | 0.43242 | 0.43242 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 42 | SPLIT TN1 | Heating | Sensible | 2718.77 | 0.10096 | 0.10096 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 |
| 43 | SPLIT TN2 | Cooling | Sensible | 5337.04 | 0.43101 | 0.43101 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 44 | SPLIT TN2 | Heating | Sensible | 2719.03 | 0.10097 | 0.10097 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 |
| 45 | SPLIT TS1 | Cooling | Sensible | 5386.99 | 0.43522 | 0.43522 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 46 | SPLIT TS1 | Heating | Sensible | 2886.51 | 0.10941 | 0.10941 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 |
| 47 | SPLIT TS2 | Cooling | Sensible | 5370.35 | 0.43382 | 0.43382 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 48 | SPLIT TS2 | Heating | Sensible | 2886.76 | 0.10943 | 0.10943 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 |
| Component Type | Component Name | Input Field Description | Value | |
| 1 | ZoneHVAC:EnergyRecoveryVentilator | G SW APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 2 | ZoneHVAC:EnergyRecoveryVentilator | G SW APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 2.59546E-002 |
| 3 | Fan:OnOff | G SW APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 4 | Fan:OnOff | G SW APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 5 | HeatExchanger:AirToAir:SensibleAndLatent | G SW APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 6 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | G SW APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.39016 |
| 7 | ZoneHVAC:EnergyRecoveryVentilator | G NW APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 8 | ZoneHVAC:EnergyRecoveryVentilator | G NW APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 2.59546E-002 |
| 9 | Fan:OnOff | G NW APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 10 | Fan:OnOff | G NW APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 11 | HeatExchanger:AirToAir:SensibleAndLatent | G NW APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 12 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | G NW APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.38330 |
| 13 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | OFFICE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.43152 |
| 14 | ZoneHVAC:EnergyRecoveryVentilator | G NE APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 15 | ZoneHVAC:EnergyRecoveryVentilator | G NE APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 2.59546E-002 |
| 16 | Fan:OnOff | G NE APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 17 | Fan:OnOff | G NE APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 18 | HeatExchanger:AirToAir:SensibleAndLatent | G NE APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 19 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | G NE APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.36311 |
| 20 | ZoneHVAC:EnergyRecoveryVentilator | G N1 APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 21 | ZoneHVAC:EnergyRecoveryVentilator | G N1 APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 2.59546E-002 |
| 22 | Fan:OnOff | G N1 APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 23 | Fan:OnOff | G N1 APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 24 | HeatExchanger:AirToAir:SensibleAndLatent | G N1 APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 25 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | G N1 APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.32712 |
| 26 | ZoneHVAC:EnergyRecoveryVentilator | G N2 APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 27 | ZoneHVAC:EnergyRecoveryVentilator | G N2 APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 2.59546E-002 |
| 28 | Fan:OnOff | G N2 APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 29 | Fan:OnOff | G N2 APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 30 | HeatExchanger:AirToAir:SensibleAndLatent | G N2 APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 31 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | G N2 APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.32674 |
| 32 | ZoneHVAC:EnergyRecoveryVentilator | G S1 APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 33 | ZoneHVAC:EnergyRecoveryVentilator | G S1 APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 2.59546E-002 |
| 34 | Fan:OnOff | G S1 APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 35 | Fan:OnOff | G S1 APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 36 | HeatExchanger:AirToAir:SensibleAndLatent | G S1 APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 37 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | G S1 APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.33531 |
| 38 | ZoneHVAC:EnergyRecoveryVentilator | G S2 APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 39 | ZoneHVAC:EnergyRecoveryVentilator | G S2 APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 2.59546E-002 |
| 40 | Fan:OnOff | G S2 APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 41 | Fan:OnOff | G S2 APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 42 | HeatExchanger:AirToAir:SensibleAndLatent | G S2 APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 43 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | G S2 APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.33801 |
| 44 | ZoneHVAC:EnergyRecoveryVentilator | M SW APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 5.19091E-002 |
| 45 | ZoneHVAC:EnergyRecoveryVentilator | M SW APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 5.19091E-002 |
| 46 | Fan:OnOff | M SW APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 5.19091E-002 |
| 47 | Fan:OnOff | M SW APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 5.19091E-002 |
| 48 | HeatExchanger:AirToAir:SensibleAndLatent | M SW APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 5.19091E-002 |
| 49 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | M SW APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.92062 |
| 50 | ZoneHVAC:EnergyRecoveryVentilator | M NW APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 5.19091E-002 |
| 51 | ZoneHVAC:EnergyRecoveryVentilator | M NW APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 5.19091E-002 |
| 52 | Fan:OnOff | M NW APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 5.19091E-002 |
| 53 | Fan:OnOff | M NW APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 5.19091E-002 |
| 54 | HeatExchanger:AirToAir:SensibleAndLatent | M NW APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 5.19091E-002 |
| 55 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | M NW APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.90763 |
| 56 | ZoneHVAC:EnergyRecoveryVentilator | M SE APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 5.19091E-002 |
| 57 | ZoneHVAC:EnergyRecoveryVentilator | M SE APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 5.19091E-002 |
| 58 | Fan:OnOff | M SE APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 5.19091E-002 |
| 59 | Fan:OnOff | M SE APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 5.19091E-002 |
| 60 | HeatExchanger:AirToAir:SensibleAndLatent | M SE APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 5.19091E-002 |
| 61 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | M SE APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.86744 |
| 62 | ZoneHVAC:EnergyRecoveryVentilator | M NE APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 5.19091E-002 |
| 63 | ZoneHVAC:EnergyRecoveryVentilator | M NE APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 5.19091E-002 |
| 64 | Fan:OnOff | M NE APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 5.19091E-002 |
| 65 | Fan:OnOff | M NE APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 5.19091E-002 |
| 66 | HeatExchanger:AirToAir:SensibleAndLatent | M NE APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 5.19091E-002 |
| 67 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | M NE APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.85461 |
| 68 | ZoneHVAC:EnergyRecoveryVentilator | M N1 APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 5.19091E-002 |
| 69 | ZoneHVAC:EnergyRecoveryVentilator | M N1 APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 5.19091E-002 |
| 70 | Fan:OnOff | M N1 APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 5.19091E-002 |
| 71 | Fan:OnOff | M N1 APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 5.19091E-002 |
| 72 | HeatExchanger:AirToAir:SensibleAndLatent | M N1 APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 5.19091E-002 |
| 73 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | M N1 APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.75924 |
| 74 | ZoneHVAC:EnergyRecoveryVentilator | M N2 APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 5.19091E-002 |
| 75 | ZoneHVAC:EnergyRecoveryVentilator | M N2 APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 5.19091E-002 |
| 76 | Fan:OnOff | M N2 APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 5.19091E-002 |
| 77 | Fan:OnOff | M N2 APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 5.19091E-002 |
| 78 | HeatExchanger:AirToAir:SensibleAndLatent | M N2 APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 5.19091E-002 |
| 79 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | M N2 APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.75825 |
| 80 | ZoneHVAC:EnergyRecoveryVentilator | M S1 APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 5.19091E-002 |
| 81 | ZoneHVAC:EnergyRecoveryVentilator | M S1 APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 5.19091E-002 |
| 82 | Fan:OnOff | M S1 APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 5.19091E-002 |
| 83 | Fan:OnOff | M S1 APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 5.19091E-002 |
| 84 | HeatExchanger:AirToAir:SensibleAndLatent | M S1 APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 5.19091E-002 |
| 85 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | M S1 APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.77434 |
| 86 | ZoneHVAC:EnergyRecoveryVentilator | M S2 APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 5.19091E-002 |
| 87 | ZoneHVAC:EnergyRecoveryVentilator | M S2 APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 5.19091E-002 |
| 88 | Fan:OnOff | M S2 APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 5.19091E-002 |
| 89 | Fan:OnOff | M S2 APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 5.19091E-002 |
| 90 | HeatExchanger:AirToAir:SensibleAndLatent | M S2 APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 5.19091E-002 |
| 91 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | M S2 APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.77332 |
| 92 | ZoneHVAC:EnergyRecoveryVentilator | T SW APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 93 | ZoneHVAC:EnergyRecoveryVentilator | T SW APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 2.59546E-002 |
| 94 | Fan:OnOff | T SW APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 95 | Fan:OnOff | T SW APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 96 | HeatExchanger:AirToAir:SensibleAndLatent | T SW APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 97 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | T SW APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.51713 |
| 98 | ZoneHVAC:EnergyRecoveryVentilator | T NW APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 99 | ZoneHVAC:EnergyRecoveryVentilator | T NW APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 2.59546E-002 |
| 100 | Fan:OnOff | T NW APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 101 | Fan:OnOff | T NW APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 102 | HeatExchanger:AirToAir:SensibleAndLatent | T NW APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 103 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | T NW APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.51491 |
| 104 | ZoneHVAC:EnergyRecoveryVentilator | T SE APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 105 | ZoneHVAC:EnergyRecoveryVentilator | T SE APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 2.59546E-002 |
| 106 | Fan:OnOff | T SE APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 107 | Fan:OnOff | T SE APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 108 | HeatExchanger:AirToAir:SensibleAndLatent | T SE APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 109 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | T SE APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.47612 |
| 110 | ZoneHVAC:EnergyRecoveryVentilator | T NE APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 111 | ZoneHVAC:EnergyRecoveryVentilator | T NE APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 2.59546E-002 |
| 112 | Fan:OnOff | T NE APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 113 | Fan:OnOff | T NE APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 114 | HeatExchanger:AirToAir:SensibleAndLatent | T NE APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 115 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | T NE APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.47385 |
| 116 | ZoneHVAC:EnergyRecoveryVentilator | T N1 APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 117 | ZoneHVAC:EnergyRecoveryVentilator | T N1 APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 2.59546E-002 |
| 118 | Fan:OnOff | T N1 APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 119 | Fan:OnOff | T N1 APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 120 | HeatExchanger:AirToAir:SensibleAndLatent | T N1 APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 121 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | T N1 APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.43242 |
| 122 | ZoneHVAC:EnergyRecoveryVentilator | T N2 APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 123 | ZoneHVAC:EnergyRecoveryVentilator | T N2 APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 2.59546E-002 |
| 124 | Fan:OnOff | T N2 APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 125 | Fan:OnOff | T N2 APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 126 | HeatExchanger:AirToAir:SensibleAndLatent | T N2 APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 127 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | T N2 APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.43101 |
| 128 | ZoneHVAC:EnergyRecoveryVentilator | T S1 APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 129 | ZoneHVAC:EnergyRecoveryVentilator | T S1 APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 2.59546E-002 |
| 130 | Fan:OnOff | T S1 APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 131 | Fan:OnOff | T S1 APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 132 | HeatExchanger:AirToAir:SensibleAndLatent | T S1 APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 133 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | T S1 APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.43522 |
| 134 | ZoneHVAC:EnergyRecoveryVentilator | T S2 APARTMENT ERV | User-Specified Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 135 | ZoneHVAC:EnergyRecoveryVentilator | T S2 APARTMENT ERV | User-Specified Exhaust Air Flow Rate [m3/s] | 2.59546E-002 |
| 136 | Fan:OnOff | T S2 APARTMENT ERV SUP FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 137 | Fan:OnOff | T S2 APARTMENT ERV EXH FAN | Design Size Maximum Flow Rate [m3/s] | 2.59546E-002 |
| 138 | HeatExchanger:AirToAir:SensibleAndLatent | T S2 APARTMENT OA HEAT EXCHANGER | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.59546E-002 |
| 139 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | T S2 APARTMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.43382 |
| 140 | AirLoopHVAC | SPLIT GSW | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.39016 |
| 141 | AirLoopHVAC | SPLIT GSW | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.39016 |
| 142 | AirLoopHVAC | SPLIT GSW | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.39016 |
| 143 | AirLoopHVAC | SPLIT GSW | Adjusted Heating Design Air Flow Rate [m3/s] | 0.39016 |
| 144 | AirLoopHVAC | SPLIT GSW | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.39016 |
| 145 | AirLoopHVAC | SPLIT GSW | Adjusted Main Design Air Flow Rate [m3/s] | 0.39016 |
| 146 | AirLoopHVAC | SPLIT GSW | User Heating Air Flow Ratio [] | 1.00000 |
| 147 | AirLoopHVAC | SPLIT GSW | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 148 | AirLoopHVAC | SPLIT GNW | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.38330 |
| 149 | AirLoopHVAC | SPLIT GNW | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.38330 |
| 150 | AirLoopHVAC | SPLIT GNW | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.38330 |
| 151 | AirLoopHVAC | SPLIT GNW | Adjusted Heating Design Air Flow Rate [m3/s] | 0.38330 |
| 152 | AirLoopHVAC | SPLIT GNW | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.38330 |
| 153 | AirLoopHVAC | SPLIT GNW | Adjusted Main Design Air Flow Rate [m3/s] | 0.38330 |
| 154 | AirLoopHVAC | SPLIT GNW | User Heating Air Flow Ratio [] | 1.00000 |
| 155 | AirLoopHVAC | SPLIT GNW | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 156 | AirLoopHVAC | SPLIT OFFICE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.43152 |
| 157 | AirLoopHVAC | SPLIT OFFICE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.43152 |
| 158 | AirLoopHVAC | SPLIT OFFICE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.43152 |
| 159 | AirLoopHVAC | SPLIT OFFICE | Adjusted Heating Design Air Flow Rate [m3/s] | 0.43152 |
| 160 | AirLoopHVAC | SPLIT OFFICE | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.43152 |
| 161 | AirLoopHVAC | SPLIT OFFICE | Adjusted Main Design Air Flow Rate [m3/s] | 0.43152 |
| 162 | AirLoopHVAC | SPLIT OFFICE | User Heating Air Flow Ratio [] | 1.00000 |
| 163 | AirLoopHVAC | SPLIT OFFICE | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 164 | AirLoopHVAC | SPLIT GNE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.36311 |
| 165 | AirLoopHVAC | SPLIT GNE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.36311 |
| 166 | AirLoopHVAC | SPLIT GNE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.36311 |
| 167 | AirLoopHVAC | SPLIT GNE | Adjusted Heating Design Air Flow Rate [m3/s] | 0.36311 |
| 168 | AirLoopHVAC | SPLIT GNE | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.36311 |
| 169 | AirLoopHVAC | SPLIT GNE | Adjusted Main Design Air Flow Rate [m3/s] | 0.36311 |
| 170 | AirLoopHVAC | SPLIT GNE | User Heating Air Flow Ratio [] | 1.00000 |
| 171 | AirLoopHVAC | SPLIT GNE | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 172 | AirLoopHVAC | SPLIT GN1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.32712 |
| 173 | AirLoopHVAC | SPLIT GN1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.32712 |
| 174 | AirLoopHVAC | SPLIT GN1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.32712 |
| 175 | AirLoopHVAC | SPLIT GN1 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.32712 |
| 176 | AirLoopHVAC | SPLIT GN1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.32712 |
| 177 | AirLoopHVAC | SPLIT GN1 | Adjusted Main Design Air Flow Rate [m3/s] | 0.32712 |
| 178 | AirLoopHVAC | SPLIT GN1 | User Heating Air Flow Ratio [] | 1.00000 |
| 179 | AirLoopHVAC | SPLIT GN1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 180 | AirLoopHVAC | SPLIT GN2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.32674 |
| 181 | AirLoopHVAC | SPLIT GN2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.32674 |
| 182 | AirLoopHVAC | SPLIT GN2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.32674 |
| 183 | AirLoopHVAC | SPLIT GN2 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.32674 |
| 184 | AirLoopHVAC | SPLIT GN2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.32674 |
| 185 | AirLoopHVAC | SPLIT GN2 | Adjusted Main Design Air Flow Rate [m3/s] | 0.32674 |
| 186 | AirLoopHVAC | SPLIT GN2 | User Heating Air Flow Ratio [] | 1.00000 |
| 187 | AirLoopHVAC | SPLIT GN2 | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 188 | AirLoopHVAC | SPLIT GS1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.33531 |
| 189 | AirLoopHVAC | SPLIT GS1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.33531 |
| 190 | AirLoopHVAC | SPLIT GS1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.33531 |
| 191 | AirLoopHVAC | SPLIT GS1 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.33531 |
| 192 | AirLoopHVAC | SPLIT GS1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.33531 |
| 193 | AirLoopHVAC | SPLIT GS1 | Adjusted Main Design Air Flow Rate [m3/s] | 0.33531 |
| 194 | AirLoopHVAC | SPLIT GS1 | User Heating Air Flow Ratio [] | 1.00000 |
| 195 | AirLoopHVAC | SPLIT GS1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 196 | AirLoopHVAC | SPLIT GS2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.33801 |
| 197 | AirLoopHVAC | SPLIT GS2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.33801 |
| 198 | AirLoopHVAC | SPLIT GS2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.33801 |
| 199 | AirLoopHVAC | SPLIT GS2 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.33801 |
| 200 | AirLoopHVAC | SPLIT GS2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.33801 |
| 201 | AirLoopHVAC | SPLIT GS2 | Adjusted Main Design Air Flow Rate [m3/s] | 0.33801 |
| 202 | AirLoopHVAC | SPLIT GS2 | User Heating Air Flow Ratio [] | 1.00000 |
| 203 | AirLoopHVAC | SPLIT GS2 | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 204 | AirLoopHVAC | SPLIT MSW | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.92062 |
| 205 | AirLoopHVAC | SPLIT MSW | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.92062 |
| 206 | AirLoopHVAC | SPLIT MSW | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.92062 |
| 207 | AirLoopHVAC | SPLIT MSW | Adjusted Heating Design Air Flow Rate [m3/s] | 0.92062 |
| 208 | AirLoopHVAC | SPLIT MSW | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.92062 |
| 209 | AirLoopHVAC | SPLIT MSW | Adjusted Main Design Air Flow Rate [m3/s] | 0.92062 |
| 210 | AirLoopHVAC | SPLIT MSW | User Heating Air Flow Ratio [] | 1.00000 |
| 211 | AirLoopHVAC | SPLIT MSW | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 212 | AirLoopHVAC | SPLIT MNW | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.90763 |
| 213 | AirLoopHVAC | SPLIT MNW | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.90763 |
| 214 | AirLoopHVAC | SPLIT MNW | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.90763 |
| 215 | AirLoopHVAC | SPLIT MNW | Adjusted Heating Design Air Flow Rate [m3/s] | 0.90763 |
| 216 | AirLoopHVAC | SPLIT MNW | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.90763 |
| 217 | AirLoopHVAC | SPLIT MNW | Adjusted Main Design Air Flow Rate [m3/s] | 0.90763 |
| 218 | AirLoopHVAC | SPLIT MNW | User Heating Air Flow Ratio [] | 1.00000 |
| 219 | AirLoopHVAC | SPLIT MNW | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 220 | AirLoopHVAC | SPLIT MSE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.86744 |
| 221 | AirLoopHVAC | SPLIT MSE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.86744 |
| 222 | AirLoopHVAC | SPLIT MSE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.86744 |
| 223 | AirLoopHVAC | SPLIT MSE | Adjusted Heating Design Air Flow Rate [m3/s] | 0.86744 |
| 224 | AirLoopHVAC | SPLIT MSE | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.86744 |
| 225 | AirLoopHVAC | SPLIT MSE | Adjusted Main Design Air Flow Rate [m3/s] | 0.86744 |
| 226 | AirLoopHVAC | SPLIT MSE | User Heating Air Flow Ratio [] | 1.00000 |
| 227 | AirLoopHVAC | SPLIT MSE | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 228 | AirLoopHVAC | SPLIT MNE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.85461 |
| 229 | AirLoopHVAC | SPLIT MNE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.85461 |
| 230 | AirLoopHVAC | SPLIT MNE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.85461 |
| 231 | AirLoopHVAC | SPLIT MNE | Adjusted Heating Design Air Flow Rate [m3/s] | 0.85461 |
| 232 | AirLoopHVAC | SPLIT MNE | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.85461 |
| 233 | AirLoopHVAC | SPLIT MNE | Adjusted Main Design Air Flow Rate [m3/s] | 0.85461 |
| 234 | AirLoopHVAC | SPLIT MNE | User Heating Air Flow Ratio [] | 1.00000 |
| 235 | AirLoopHVAC | SPLIT MNE | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 236 | AirLoopHVAC | SPLIT MN1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.75924 |
| 237 | AirLoopHVAC | SPLIT MN1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.75924 |
| 238 | AirLoopHVAC | SPLIT MN1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.75924 |
| 239 | AirLoopHVAC | SPLIT MN1 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.75924 |
| 240 | AirLoopHVAC | SPLIT MN1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.75924 |
| 241 | AirLoopHVAC | SPLIT MN1 | Adjusted Main Design Air Flow Rate [m3/s] | 0.75924 |
| 242 | AirLoopHVAC | SPLIT MN1 | User Heating Air Flow Ratio [] | 1.00000 |
| 243 | AirLoopHVAC | SPLIT MN1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 244 | AirLoopHVAC | SPLIT MN2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.75825 |
| 245 | AirLoopHVAC | SPLIT MN2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.75825 |
| 246 | AirLoopHVAC | SPLIT MN2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.75825 |
| 247 | AirLoopHVAC | SPLIT MN2 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.75825 |
| 248 | AirLoopHVAC | SPLIT MN2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.75825 |
| 249 | AirLoopHVAC | SPLIT MN2 | Adjusted Main Design Air Flow Rate [m3/s] | 0.75825 |
| 250 | AirLoopHVAC | SPLIT MN2 | User Heating Air Flow Ratio [] | 1.00000 |
| 251 | AirLoopHVAC | SPLIT MN2 | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 252 | AirLoopHVAC | SPLIT MS1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.77434 |
| 253 | AirLoopHVAC | SPLIT MS1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.77434 |
| 254 | AirLoopHVAC | SPLIT MS1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.77434 |
| 255 | AirLoopHVAC | SPLIT MS1 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.77434 |
| 256 | AirLoopHVAC | SPLIT MS1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.77434 |
| 257 | AirLoopHVAC | SPLIT MS1 | Adjusted Main Design Air Flow Rate [m3/s] | 0.77434 |
| 258 | AirLoopHVAC | SPLIT MS1 | User Heating Air Flow Ratio [] | 1.00000 |
| 259 | AirLoopHVAC | SPLIT MS1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 260 | AirLoopHVAC | SPLIT MS2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.77332 |
| 261 | AirLoopHVAC | SPLIT MS2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.77332 |
| 262 | AirLoopHVAC | SPLIT MS2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.77332 |
| 263 | AirLoopHVAC | SPLIT MS2 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.77332 |
| 264 | AirLoopHVAC | SPLIT MS2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.77332 |
| 265 | AirLoopHVAC | SPLIT MS2 | Adjusted Main Design Air Flow Rate [m3/s] | 0.77332 |
| 266 | AirLoopHVAC | SPLIT MS2 | User Heating Air Flow Ratio [] | 1.00000 |
| 267 | AirLoopHVAC | SPLIT MS2 | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 268 | AirLoopHVAC | SPLIT TSW | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.51713 |
| 269 | AirLoopHVAC | SPLIT TSW | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.51713 |
| 270 | AirLoopHVAC | SPLIT TSW | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.51713 |
| 271 | AirLoopHVAC | SPLIT TSW | Adjusted Heating Design Air Flow Rate [m3/s] | 0.51713 |
| 272 | AirLoopHVAC | SPLIT TSW | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.51713 |
| 273 | AirLoopHVAC | SPLIT TSW | Adjusted Main Design Air Flow Rate [m3/s] | 0.51713 |
| 274 | AirLoopHVAC | SPLIT TSW | User Heating Air Flow Ratio [] | 1.00000 |
| 275 | AirLoopHVAC | SPLIT TSW | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 276 | AirLoopHVAC | SPLIT TNW | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.51491 |
| 277 | AirLoopHVAC | SPLIT TNW | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.51491 |
| 278 | AirLoopHVAC | SPLIT TNW | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.51491 |
| 279 | AirLoopHVAC | SPLIT TNW | Adjusted Heating Design Air Flow Rate [m3/s] | 0.51491 |
| 280 | AirLoopHVAC | SPLIT TNW | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.51491 |
| 281 | AirLoopHVAC | SPLIT TNW | Adjusted Main Design Air Flow Rate [m3/s] | 0.51491 |
| 282 | AirLoopHVAC | SPLIT TNW | User Heating Air Flow Ratio [] | 1.00000 |
| 283 | AirLoopHVAC | SPLIT TNW | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 284 | AirLoopHVAC | SPLIT TSE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.47612 |
| 285 | AirLoopHVAC | SPLIT TSE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.47612 |
| 286 | AirLoopHVAC | SPLIT TSE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.47612 |
| 287 | AirLoopHVAC | SPLIT TSE | Adjusted Heating Design Air Flow Rate [m3/s] | 0.47612 |
| 288 | AirLoopHVAC | SPLIT TSE | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.47612 |
| 289 | AirLoopHVAC | SPLIT TSE | Adjusted Main Design Air Flow Rate [m3/s] | 0.47612 |
| 290 | AirLoopHVAC | SPLIT TSE | User Heating Air Flow Ratio [] | 1.00000 |
| 291 | AirLoopHVAC | SPLIT TSE | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 292 | AirLoopHVAC | SPLIT TNE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.47385 |
| 293 | AirLoopHVAC | SPLIT TNE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.47385 |
| 294 | AirLoopHVAC | SPLIT TNE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.47385 |
| 295 | AirLoopHVAC | SPLIT TNE | Adjusted Heating Design Air Flow Rate [m3/s] | 0.47385 |
| 296 | AirLoopHVAC | SPLIT TNE | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.47385 |
| 297 | AirLoopHVAC | SPLIT TNE | Adjusted Main Design Air Flow Rate [m3/s] | 0.47385 |
| 298 | AirLoopHVAC | SPLIT TNE | User Heating Air Flow Ratio [] | 1.00000 |
| 299 | AirLoopHVAC | SPLIT TNE | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 300 | AirLoopHVAC | SPLIT TN1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.43242 |
| 301 | AirLoopHVAC | SPLIT TN1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.43242 |
| 302 | AirLoopHVAC | SPLIT TN1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.43242 |
| 303 | AirLoopHVAC | SPLIT TN1 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.43242 |
| 304 | AirLoopHVAC | SPLIT TN1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.43242 |
| 305 | AirLoopHVAC | SPLIT TN1 | Adjusted Main Design Air Flow Rate [m3/s] | 0.43242 |
| 306 | AirLoopHVAC | SPLIT TN1 | User Heating Air Flow Ratio [] | 1.00000 |
| 307 | AirLoopHVAC | SPLIT TN1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 308 | AirLoopHVAC | SPLIT TN2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.43101 |
| 309 | AirLoopHVAC | SPLIT TN2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.43101 |
| 310 | AirLoopHVAC | SPLIT TN2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.43101 |
| 311 | AirLoopHVAC | SPLIT TN2 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.43101 |
| 312 | AirLoopHVAC | SPLIT TN2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.43101 |
| 313 | AirLoopHVAC | SPLIT TN2 | Adjusted Main Design Air Flow Rate [m3/s] | 0.43101 |
| 314 | AirLoopHVAC | SPLIT TN2 | User Heating Air Flow Ratio [] | 1.00000 |
| 315 | AirLoopHVAC | SPLIT TN2 | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 316 | AirLoopHVAC | SPLIT TS1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.43522 |
| 317 | AirLoopHVAC | SPLIT TS1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.43522 |
| 318 | AirLoopHVAC | SPLIT TS1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.43522 |
| 319 | AirLoopHVAC | SPLIT TS1 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.43522 |
| 320 | AirLoopHVAC | SPLIT TS1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.43522 |
| 321 | AirLoopHVAC | SPLIT TS1 | Adjusted Main Design Air Flow Rate [m3/s] | 0.43522 |
| 322 | AirLoopHVAC | SPLIT TS1 | User Heating Air Flow Ratio [] | 1.00000 |
| 323 | AirLoopHVAC | SPLIT TS1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 324 | AirLoopHVAC | SPLIT TS2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.43382 |
| 325 | AirLoopHVAC | SPLIT TS2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.43382 |
| 326 | AirLoopHVAC | SPLIT TS2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.43382 |
| 327 | AirLoopHVAC | SPLIT TS2 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.43382 |
| 328 | AirLoopHVAC | SPLIT TS2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.43382 |
| 329 | AirLoopHVAC | SPLIT TS2 | Adjusted Main Design Air Flow Rate [m3/s] | 0.43382 |
| 330 | AirLoopHVAC | SPLIT TS2 | User Heating Air Flow Ratio [] | 1.00000 |
| 331 | AirLoopHVAC | SPLIT TS2 | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 332 | AirLoopHVAC | SPLIT GSW | Design Supply Air Flow Rate [m3/s] | 0.39016 |
| 333 | AirLoopHVAC | SPLIT GNW | Design Supply Air Flow Rate [m3/s] | 0.38330 |
| 334 | AirLoopHVAC | SPLIT OFFICE | Design Supply Air Flow Rate [m3/s] | 0.43152 |
| 335 | AirLoopHVAC | SPLIT GNE | Design Supply Air Flow Rate [m3/s] | 0.36311 |
| 336 | AirLoopHVAC | SPLIT GN1 | Design Supply Air Flow Rate [m3/s] | 0.32712 |
| 337 | AirLoopHVAC | SPLIT GN2 | Design Supply Air Flow Rate [m3/s] | 0.32674 |
| 338 | AirLoopHVAC | SPLIT GS1 | Design Supply Air Flow Rate [m3/s] | 0.33531 |
| 339 | AirLoopHVAC | SPLIT GS2 | Design Supply Air Flow Rate [m3/s] | 0.33801 |
| 340 | AirLoopHVAC | SPLIT MSW | Design Supply Air Flow Rate [m3/s] | 0.92062 |
| 341 | AirLoopHVAC | SPLIT MNW | Design Supply Air Flow Rate [m3/s] | 0.90763 |
| 342 | AirLoopHVAC | SPLIT MSE | Design Supply Air Flow Rate [m3/s] | 0.86744 |
| 343 | AirLoopHVAC | SPLIT MNE | Design Supply Air Flow Rate [m3/s] | 0.85461 |
| 344 | AirLoopHVAC | SPLIT MN1 | Design Supply Air Flow Rate [m3/s] | 0.75924 |
| 345 | AirLoopHVAC | SPLIT MN2 | Design Supply Air Flow Rate [m3/s] | 0.75825 |
| 346 | AirLoopHVAC | SPLIT MS1 | Design Supply Air Flow Rate [m3/s] | 0.77434 |
| 347 | AirLoopHVAC | SPLIT MS2 | Design Supply Air Flow Rate [m3/s] | 0.77332 |
| 348 | AirLoopHVAC | SPLIT TSW | Design Supply Air Flow Rate [m3/s] | 0.51713 |
| 349 | AirLoopHVAC | SPLIT TNW | Design Supply Air Flow Rate [m3/s] | 0.51491 |
| 350 | AirLoopHVAC | SPLIT TSE | Design Supply Air Flow Rate [m3/s] | 0.47612 |
| 351 | AirLoopHVAC | SPLIT TNE | Design Supply Air Flow Rate [m3/s] | 0.47385 |
| 352 | AirLoopHVAC | SPLIT TN1 | Design Supply Air Flow Rate [m3/s] | 0.43242 |
| 353 | AirLoopHVAC | SPLIT TN2 | Design Supply Air Flow Rate [m3/s] | 0.43101 |
| 354 | AirLoopHVAC | SPLIT TS1 | Design Supply Air Flow Rate [m3/s] | 0.43522 |
| 355 | AirLoopHVAC | SPLIT TS2 | Design Supply Air Flow Rate [m3/s] | 0.43382 |
| 356 | Controller:OutdoorAir | SPLIT GSW_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.39016 |
| 357 | Controller:OutdoorAir | SPLIT GSW_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.59546E-002 |
| 358 | AirLoopHVAC:UnitarySystem | SPLIT GSW_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.39016 |
| 359 | AirLoopHVAC:UnitarySystem | SPLIT GSW_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.39016 |
| 360 | AirLoopHVAC:UnitarySystem | SPLIT GSW_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.39016 |
| 361 | AirLoopHVAC:UnitarySystem | SPLIT GSW_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.39016 |
| 362 | AirLoopHVAC:UnitarySystem | SPLIT GSW_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 6458.58980 |
| 363 | AirLoopHVAC:UnitarySystem | SPLIT GSW_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 8454.92449 |
| 364 | AirLoopHVAC:UnitarySystem | SPLIT GSW_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 365 | AirLoopHVAC:UnitarySystem | SPLIT GSW_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 366 | Fan:OnOff | SPLIT GSW SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.39016 |
| 367 | Coil:Cooling:DX:SingleSpeed | SPLIT GSW COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.39016 |
| 368 | Coil:Cooling:DX:SingleSpeed | SPLIT GSW COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 6458.58980 |
| 369 | Coil:Cooling:DX:SingleSpeed | SPLIT GSW COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
| 370 | Coil:Heating:Fuel | SPLIT GSW HEATING COIL | Design Size Nominal Capacity [W] | 8454.92449 |
| 371 | Controller:OutdoorAir | SPLIT GNW_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.38330 |
| 372 | Controller:OutdoorAir | SPLIT GNW_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.59546E-002 |
| 373 | AirLoopHVAC:UnitarySystem | SPLIT GNW_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.38330 |
| 374 | AirLoopHVAC:UnitarySystem | SPLIT GNW_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.38330 |
| 375 | AirLoopHVAC:UnitarySystem | SPLIT GNW_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.38330 |
| 376 | AirLoopHVAC:UnitarySystem | SPLIT GNW_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.38330 |
| 377 | AirLoopHVAC:UnitarySystem | SPLIT GNW_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 6345.02502 |
| 378 | AirLoopHVAC:UnitarySystem | SPLIT GNW_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 8318.79483 |
| 379 | AirLoopHVAC:UnitarySystem | SPLIT GNW_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 380 | AirLoopHVAC:UnitarySystem | SPLIT GNW_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 381 | Fan:OnOff | SPLIT GNW SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.38330 |
| 382 | Coil:Cooling:DX:SingleSpeed | SPLIT GNW COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.38330 |
| 383 | Coil:Cooling:DX:SingleSpeed | SPLIT GNW COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 6345.02502 |
| 384 | Coil:Cooling:DX:SingleSpeed | SPLIT GNW COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
| 385 | Coil:Heating:Fuel | SPLIT GNW HEATING COIL | Design Size Nominal Capacity [W] | 8318.79483 |
| 386 | Controller:OutdoorAir | SPLIT OFFICE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.43152 |
| 387 | Controller:OutdoorAir | SPLIT OFFICE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 3.81060E-002 |
| 388 | AirLoopHVAC:UnitarySystem | SPLIT OFFICE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.43152 |
| 389 | AirLoopHVAC:UnitarySystem | SPLIT OFFICE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.43152 |
| 390 | AirLoopHVAC:UnitarySystem | SPLIT OFFICE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.43152 |
| 391 | AirLoopHVAC:UnitarySystem | SPLIT OFFICE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.43152 |
| 392 | AirLoopHVAC:UnitarySystem | SPLIT OFFICE_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 7143.22987 |
| 393 | AirLoopHVAC:UnitarySystem | SPLIT OFFICE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 9610.62211 |
| 394 | AirLoopHVAC:UnitarySystem | SPLIT OFFICE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 395 | AirLoopHVAC:UnitarySystem | SPLIT OFFICE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 396 | Fan:OnOff | SPLIT OFFICE SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.43152 |
| 397 | Coil:Cooling:DX:SingleSpeed | SPLIT OFFICE COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.43152 |
| 398 | Coil:Cooling:DX:SingleSpeed | SPLIT OFFICE COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 7143.22987 |
| 399 | Coil:Cooling:DX:SingleSpeed | SPLIT OFFICE COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
| 400 | Coil:Heating:Fuel | SPLIT OFFICE HEATING COIL | Design Size Nominal Capacity [W] | 9610.62211 |
| 401 | Controller:OutdoorAir | SPLIT GNE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.36311 |
| 402 | Controller:OutdoorAir | SPLIT GNE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.59546E-002 |
| 403 | AirLoopHVAC:UnitarySystem | SPLIT GNE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.36311 |
| 404 | AirLoopHVAC:UnitarySystem | SPLIT GNE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.36311 |
| 405 | AirLoopHVAC:UnitarySystem | SPLIT GNE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.36311 |
| 406 | AirLoopHVAC:UnitarySystem | SPLIT GNE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.36311 |
| 407 | AirLoopHVAC:UnitarySystem | SPLIT GNE_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 6010.82268 |
| 408 | AirLoopHVAC:UnitarySystem | SPLIT GNE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 7918.36071 |
| 409 | AirLoopHVAC:UnitarySystem | SPLIT GNE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 410 | AirLoopHVAC:UnitarySystem | SPLIT GNE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 411 | Fan:OnOff | SPLIT GNE SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.36311 |
| 412 | Coil:Cooling:DX:SingleSpeed | SPLIT GNE COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.36311 |
| 413 | Coil:Cooling:DX:SingleSpeed | SPLIT GNE COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 6010.82268 |
| 414 | Coil:Cooling:DX:SingleSpeed | SPLIT GNE COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
| 415 | Coil:Heating:Fuel | SPLIT GNE HEATING COIL | Design Size Nominal Capacity [W] | 7918.36071 |
| 416 | Controller:OutdoorAir | SPLIT GN1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.32712 |
| 417 | Controller:OutdoorAir | SPLIT GN1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.59546E-002 |
| 418 | AirLoopHVAC:UnitarySystem | SPLIT GN1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.32712 |
| 419 | AirLoopHVAC:UnitarySystem | SPLIT GN1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.32712 |
| 420 | AirLoopHVAC:UnitarySystem | SPLIT GN1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.32712 |
| 421 | AirLoopHVAC:UnitarySystem | SPLIT GN1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.32712 |
| 422 | AirLoopHVAC:UnitarySystem | SPLIT GN1_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 5414.96342 |
| 423 | AirLoopHVAC:UnitarySystem | SPLIT GN1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 7204.35162 |
| 424 | AirLoopHVAC:UnitarySystem | SPLIT GN1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 425 | AirLoopHVAC:UnitarySystem | SPLIT GN1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 426 | Fan:OnOff | SPLIT GN1 SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.32712 |
| 427 | Coil:Cooling:DX:SingleSpeed | SPLIT GN1 COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.32712 |
| 428 | Coil:Cooling:DX:SingleSpeed | SPLIT GN1 COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 5414.96342 |
| 429 | Coil:Cooling:DX:SingleSpeed | SPLIT GN1 COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
| 430 | Coil:Heating:Fuel | SPLIT GN1 HEATING COIL | Design Size Nominal Capacity [W] | 7204.35162 |
| 431 | Controller:OutdoorAir | SPLIT GN2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.32674 |
| 432 | Controller:OutdoorAir | SPLIT GN2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.59546E-002 |
| 433 | AirLoopHVAC:UnitarySystem | SPLIT GN2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.32674 |
| 434 | AirLoopHVAC:UnitarySystem | SPLIT GN2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.32674 |
| 435 | AirLoopHVAC:UnitarySystem | SPLIT GN2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.32674 |
| 436 | AirLoopHVAC:UnitarySystem | SPLIT GN2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.32674 |
| 437 | AirLoopHVAC:UnitarySystem | SPLIT GN2_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 5408.72918 |
| 438 | AirLoopHVAC:UnitarySystem | SPLIT GN2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 7196.88196 |
| 439 | AirLoopHVAC:UnitarySystem | SPLIT GN2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 440 | AirLoopHVAC:UnitarySystem | SPLIT GN2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 441 | Fan:OnOff | SPLIT GN2 SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.32674 |
| 442 | Coil:Cooling:DX:SingleSpeed | SPLIT GN2 COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.32674 |
| 443 | Coil:Cooling:DX:SingleSpeed | SPLIT GN2 COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 5408.72918 |
| 444 | Coil:Cooling:DX:SingleSpeed | SPLIT GN2 COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
| 445 | Coil:Heating:Fuel | SPLIT GN2 HEATING COIL | Design Size Nominal Capacity [W] | 7196.88196 |
| 446 | Controller:OutdoorAir | SPLIT GS1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.33531 |
| 447 | Controller:OutdoorAir | SPLIT GS1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.59546E-002 |
| 448 | AirLoopHVAC:UnitarySystem | SPLIT GS1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.33531 |
| 449 | AirLoopHVAC:UnitarySystem | SPLIT GS1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.33531 |
| 450 | AirLoopHVAC:UnitarySystem | SPLIT GS1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.33531 |
| 451 | AirLoopHVAC:UnitarySystem | SPLIT GS1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.33531 |
| 452 | AirLoopHVAC:UnitarySystem | SPLIT GS1_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 5550.57005 |
| 453 | AirLoopHVAC:UnitarySystem | SPLIT GS1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 7366.88755 |
| 454 | AirLoopHVAC:UnitarySystem | SPLIT GS1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 455 | AirLoopHVAC:UnitarySystem | SPLIT GS1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 456 | Fan:OnOff | SPLIT GS1 SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.33531 |
| 457 | Coil:Cooling:DX:SingleSpeed | SPLIT GS1 COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.33531 |
| 458 | Coil:Cooling:DX:SingleSpeed | SPLIT GS1 COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 5550.57005 |
| 459 | Coil:Cooling:DX:SingleSpeed | SPLIT GS1 COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
| 460 | Coil:Heating:Fuel | SPLIT GS1 HEATING COIL | Design Size Nominal Capacity [W] | 7366.88755 |
| 461 | Controller:OutdoorAir | SPLIT GS2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.33801 |
| 462 | Controller:OutdoorAir | SPLIT GS2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.59546E-002 |
| 463 | AirLoopHVAC:UnitarySystem | SPLIT GS2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.33801 |
| 464 | AirLoopHVAC:UnitarySystem | SPLIT GS2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.33801 |
| 465 | AirLoopHVAC:UnitarySystem | SPLIT GS2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.33801 |
| 466 | AirLoopHVAC:UnitarySystem | SPLIT GS2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.33801 |
| 467 | AirLoopHVAC:UnitarySystem | SPLIT GS2_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 5595.33553 |
| 468 | AirLoopHVAC:UnitarySystem | SPLIT GS2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 7420.52456 |
| 469 | AirLoopHVAC:UnitarySystem | SPLIT GS2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 470 | AirLoopHVAC:UnitarySystem | SPLIT GS2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 471 | Fan:OnOff | SPLIT GS2 SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.33801 |
| 472 | Coil:Cooling:DX:SingleSpeed | SPLIT GS2 COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.33801 |
| 473 | Coil:Cooling:DX:SingleSpeed | SPLIT GS2 COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 5595.33553 |
| 474 | Coil:Cooling:DX:SingleSpeed | SPLIT GS2 COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
| 475 | Coil:Heating:Fuel | SPLIT GS2 HEATING COIL | Design Size Nominal Capacity [W] | 7420.52456 |
| 476 | Controller:OutdoorAir | SPLIT MSW_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.92062 |
| 477 | Controller:OutdoorAir | SPLIT MSW_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 5.19091E-002 |
| 478 | AirLoopHVAC:UnitarySystem | SPLIT MSW_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.92062 |
| 479 | AirLoopHVAC:UnitarySystem | SPLIT MSW_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.92062 |
| 480 | AirLoopHVAC:UnitarySystem | SPLIT MSW_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.92062 |
| 481 | AirLoopHVAC:UnitarySystem | SPLIT MSW_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.92062 |
| 482 | AirLoopHVAC:UnitarySystem | SPLIT MSW_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 15239.47350 |
| 483 | AirLoopHVAC:UnitarySystem | SPLIT MSW_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 19693.04272 |
| 484 | AirLoopHVAC:UnitarySystem | SPLIT MSW_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 485 | AirLoopHVAC:UnitarySystem | SPLIT MSW_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 486 | Fan:OnOff | SPLIT MSW SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.92062 |
| 487 | Coil:Cooling:DX:SingleSpeed | SPLIT MSW COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.92062 |
| 488 | Coil:Cooling:DX:SingleSpeed | SPLIT MSW COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 15239.47350 |
| 489 | Coil:Cooling:DX:SingleSpeed | SPLIT MSW COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
| 490 | Coil:Heating:Fuel | SPLIT MSW HEATING COIL | Design Size Nominal Capacity [W] | 19693.04272 |
| 491 | Controller:OutdoorAir | SPLIT MNW_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.90763 |
| 492 | Controller:OutdoorAir | SPLIT MNW_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 5.19091E-002 |
| 493 | AirLoopHVAC:UnitarySystem | SPLIT MNW_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.90763 |
| 494 | AirLoopHVAC:UnitarySystem | SPLIT MNW_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.90763 |
| 495 | AirLoopHVAC:UnitarySystem | SPLIT MNW_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.90763 |
| 496 | AirLoopHVAC:UnitarySystem | SPLIT MNW_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.90763 |
| 497 | AirLoopHVAC:UnitarySystem | SPLIT MNW_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 15024.43268 |
| 498 | AirLoopHVAC:UnitarySystem | SPLIT MNW_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 19435.07848 |
| 499 | AirLoopHVAC:UnitarySystem | SPLIT MNW_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 500 | AirLoopHVAC:UnitarySystem | SPLIT MNW_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 501 | Fan:OnOff | SPLIT MNW SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.90763 |
| 502 | Coil:Cooling:DX:SingleSpeed | SPLIT MNW COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.90763 |
| 503 | Coil:Cooling:DX:SingleSpeed | SPLIT MNW COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 15024.43268 |
| 504 | Coil:Cooling:DX:SingleSpeed | SPLIT MNW COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
| 505 | Coil:Heating:Fuel | SPLIT MNW HEATING COIL | Design Size Nominal Capacity [W] | 19435.07848 |
| 506 | Controller:OutdoorAir | SPLIT MSE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.86744 |
| 507 | Controller:OutdoorAir | SPLIT MSE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 5.19091E-002 |
| 508 | AirLoopHVAC:UnitarySystem | SPLIT MSE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.86744 |
| 509 | AirLoopHVAC:UnitarySystem | SPLIT MSE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.86744 |
| 510 | AirLoopHVAC:UnitarySystem | SPLIT MSE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.86744 |
| 511 | AirLoopHVAC:UnitarySystem | SPLIT MSE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.86744 |
| 512 | AirLoopHVAC:UnitarySystem | SPLIT MSE_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 14359.19714 |
| 513 | AirLoopHVAC:UnitarySystem | SPLIT MSE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 18638.26613 |
| 514 | AirLoopHVAC:UnitarySystem | SPLIT MSE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 515 | AirLoopHVAC:UnitarySystem | SPLIT MSE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 516 | Fan:OnOff | SPLIT MSE SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.86744 |
| 517 | Coil:Cooling:DX:SingleSpeed | SPLIT MSE COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.86744 |
| 518 | Coil:Cooling:DX:SingleSpeed | SPLIT MSE COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 14359.19714 |
| 519 | Coil:Cooling:DX:SingleSpeed | SPLIT MSE COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
| 520 | Coil:Heating:Fuel | SPLIT MSE HEATING COIL | Design Size Nominal Capacity [W] | 18638.26613 |
| 521 | Controller:OutdoorAir | SPLIT MNE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.85461 |
| 522 | Controller:OutdoorAir | SPLIT MNE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 5.19091E-002 |
| 523 | AirLoopHVAC:UnitarySystem | SPLIT MNE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.85461 |
| 524 | AirLoopHVAC:UnitarySystem | SPLIT MNE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.85461 |
| 525 | AirLoopHVAC:UnitarySystem | SPLIT MNE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.85461 |
| 526 | AirLoopHVAC:UnitarySystem | SPLIT MNE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.85461 |
| 527 | AirLoopHVAC:UnitarySystem | SPLIT MNE_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 14146.76226 |
| 528 | AirLoopHVAC:UnitarySystem | SPLIT MNE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 18383.44270 |
| 529 | AirLoopHVAC:UnitarySystem | SPLIT MNE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 530 | AirLoopHVAC:UnitarySystem | SPLIT MNE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 531 | Fan:OnOff | SPLIT MNE SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.85461 |
| 532 | Coil:Cooling:DX:SingleSpeed | SPLIT MNE COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.85461 |
| 533 | Coil:Cooling:DX:SingleSpeed | SPLIT MNE COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 14146.76226 |
| 534 | Coil:Cooling:DX:SingleSpeed | SPLIT MNE COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
| 535 | Coil:Heating:Fuel | SPLIT MNE HEATING COIL | Design Size Nominal Capacity [W] | 18383.44270 |
| 536 | Controller:OutdoorAir | SPLIT MN1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.75924 |
| 537 | Controller:OutdoorAir | SPLIT MN1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 5.19091E-002 |
| 538 | AirLoopHVAC:UnitarySystem | SPLIT MN1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.75924 |
| 539 | AirLoopHVAC:UnitarySystem | SPLIT MN1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.75924 |
| 540 | AirLoopHVAC:UnitarySystem | SPLIT MN1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.75924 |
| 541 | AirLoopHVAC:UnitarySystem | SPLIT MN1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.75924 |
| 542 | AirLoopHVAC:UnitarySystem | SPLIT MN1_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 12568.05613 |
| 543 | AirLoopHVAC:UnitarySystem | SPLIT MN1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 16491.48792 |
| 544 | AirLoopHVAC:UnitarySystem | SPLIT MN1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 545 | AirLoopHVAC:UnitarySystem | SPLIT MN1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 546 | Fan:OnOff | SPLIT MN1 SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.75924 |
| 547 | Coil:Cooling:DX:SingleSpeed | SPLIT MN1 COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.75924 |
| 548 | Coil:Cooling:DX:SingleSpeed | SPLIT MN1 COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 12568.05613 |
| 549 | Coil:Cooling:DX:SingleSpeed | SPLIT MN1 COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
| 550 | Coil:Heating:Fuel | SPLIT MN1 HEATING COIL | Design Size Nominal Capacity [W] | 16491.48792 |
| 551 | Controller:OutdoorAir | SPLIT MN2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.75825 |
| 552 | Controller:OutdoorAir | SPLIT MN2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 5.19091E-002 |
| 553 | AirLoopHVAC:UnitarySystem | SPLIT MN2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.75825 |
| 554 | AirLoopHVAC:UnitarySystem | SPLIT MN2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.75825 |
| 555 | AirLoopHVAC:UnitarySystem | SPLIT MN2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.75825 |
| 556 | AirLoopHVAC:UnitarySystem | SPLIT MN2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.75825 |
| 557 | AirLoopHVAC:UnitarySystem | SPLIT MN2_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 12551.67438 |
| 558 | AirLoopHVAC:UnitarySystem | SPLIT MN2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 16471.85955 |
| 559 | AirLoopHVAC:UnitarySystem | SPLIT MN2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 560 | AirLoopHVAC:UnitarySystem | SPLIT MN2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 561 | Fan:OnOff | SPLIT MN2 SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.75825 |
| 562 | Coil:Cooling:DX:SingleSpeed | SPLIT MN2 COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.75825 |
| 563 | Coil:Cooling:DX:SingleSpeed | SPLIT MN2 COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 12551.67438 |
| 564 | Coil:Cooling:DX:SingleSpeed | SPLIT MN2 COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
| 565 | Coil:Heating:Fuel | SPLIT MN2 HEATING COIL | Design Size Nominal Capacity [W] | 16471.85955 |
| 566 | Controller:OutdoorAir | SPLIT MS1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.77434 |
| 567 | Controller:OutdoorAir | SPLIT MS1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 5.19091E-002 |
| 568 | AirLoopHVAC:UnitarySystem | SPLIT MS1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.77434 |
| 569 | AirLoopHVAC:UnitarySystem | SPLIT MS1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.77434 |
| 570 | AirLoopHVAC:UnitarySystem | SPLIT MS1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.77434 |
| 571 | AirLoopHVAC:UnitarySystem | SPLIT MS1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.77434 |
| 572 | AirLoopHVAC:UnitarySystem | SPLIT MS1_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 12818.05663 |
| 573 | AirLoopHVAC:UnitarySystem | SPLIT MS1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 16791.29843 |
| 574 | AirLoopHVAC:UnitarySystem | SPLIT MS1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 575 | AirLoopHVAC:UnitarySystem | SPLIT MS1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 576 | Fan:OnOff | SPLIT MS1 SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.77434 |
| 577 | Coil:Cooling:DX:SingleSpeed | SPLIT MS1 COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.77434 |
| 578 | Coil:Cooling:DX:SingleSpeed | SPLIT MS1 COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 12818.05663 |
| 579 | Coil:Cooling:DX:SingleSpeed | SPLIT MS1 COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
| 580 | Coil:Heating:Fuel | SPLIT MS1 HEATING COIL | Design Size Nominal Capacity [W] | 16791.29843 |
| 581 | Controller:OutdoorAir | SPLIT MS2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.77332 |
| 582 | Controller:OutdoorAir | SPLIT MS2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 5.19091E-002 |
| 583 | AirLoopHVAC:UnitarySystem | SPLIT MS2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.77332 |
| 584 | AirLoopHVAC:UnitarySystem | SPLIT MS2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.77332 |
| 585 | AirLoopHVAC:UnitarySystem | SPLIT MS2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.77332 |
| 586 | AirLoopHVAC:UnitarySystem | SPLIT MS2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.77332 |
| 587 | AirLoopHVAC:UnitarySystem | SPLIT MS2_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 12801.26551 |
| 588 | AirLoopHVAC:UnitarySystem | SPLIT MS2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 16771.17920 |
| 589 | AirLoopHVAC:UnitarySystem | SPLIT MS2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 590 | AirLoopHVAC:UnitarySystem | SPLIT MS2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 591 | Fan:OnOff | SPLIT MS2 SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.77332 |
| 592 | Coil:Cooling:DX:SingleSpeed | SPLIT MS2 COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.77332 |
| 593 | Coil:Cooling:DX:SingleSpeed | SPLIT MS2 COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 12801.26551 |
| 594 | Coil:Cooling:DX:SingleSpeed | SPLIT MS2 COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
| 595 | Coil:Heating:Fuel | SPLIT MS2 HEATING COIL | Design Size Nominal Capacity [W] | 16771.17920 |
| 596 | Controller:OutdoorAir | SPLIT TSW_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.51713 |
| 597 | Controller:OutdoorAir | SPLIT TSW_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.59546E-002 |
| 598 | AirLoopHVAC:UnitarySystem | SPLIT TSW_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.51713 |
| 599 | AirLoopHVAC:UnitarySystem | SPLIT TSW_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.51713 |
| 600 | AirLoopHVAC:UnitarySystem | SPLIT TSW_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.51713 |
| 601 | AirLoopHVAC:UnitarySystem | SPLIT TSW_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.51713 |
| 602 | AirLoopHVAC:UnitarySystem | SPLIT TSW_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 8560.36538 |
| 603 | AirLoopHVAC:UnitarySystem | SPLIT TSW_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 10973.83305 |
| 604 | AirLoopHVAC:UnitarySystem | SPLIT TSW_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 605 | AirLoopHVAC:UnitarySystem | SPLIT TSW_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 606 | Fan:OnOff | SPLIT TSW SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.51713 |
| 607 | Coil:Cooling:DX:SingleSpeed | SPLIT TSW COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.51713 |
| 608 | Coil:Cooling:DX:SingleSpeed | SPLIT TSW COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 8560.36538 |
| 609 | Coil:Cooling:DX:SingleSpeed | SPLIT TSW COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
| 610 | Coil:Heating:Fuel | SPLIT TSW HEATING COIL | Design Size Nominal Capacity [W] | 10973.83305 |
| 611 | Controller:OutdoorAir | SPLIT TNW_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.51491 |
| 612 | Controller:OutdoorAir | SPLIT TNW_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.59546E-002 |
| 613 | AirLoopHVAC:UnitarySystem | SPLIT TNW_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.51491 |
| 614 | AirLoopHVAC:UnitarySystem | SPLIT TNW_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.51491 |
| 615 | AirLoopHVAC:UnitarySystem | SPLIT TNW_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.51491 |
| 616 | AirLoopHVAC:UnitarySystem | SPLIT TNW_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.51491 |
| 617 | AirLoopHVAC:UnitarySystem | SPLIT TNW_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 8523.51311 |
| 618 | AirLoopHVAC:UnitarySystem | SPLIT TNW_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 10929.50195 |
| 619 | AirLoopHVAC:UnitarySystem | SPLIT TNW_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 620 | AirLoopHVAC:UnitarySystem | SPLIT TNW_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 621 | Fan:OnOff | SPLIT TNW SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.51491 |
| 622 | Coil:Cooling:DX:SingleSpeed | SPLIT TNW COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.51491 |
| 623 | Coil:Cooling:DX:SingleSpeed | SPLIT TNW COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 8523.51311 |
| 624 | Coil:Cooling:DX:SingleSpeed | SPLIT TNW COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
| 625 | Coil:Heating:Fuel | SPLIT TNW HEATING COIL | Design Size Nominal Capacity [W] | 10929.50195 |
| 626 | Controller:OutdoorAir | SPLIT TSE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.47612 |
| 627 | Controller:OutdoorAir | SPLIT TSE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.59546E-002 |
| 628 | AirLoopHVAC:UnitarySystem | SPLIT TSE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.47612 |
| 629 | AirLoopHVAC:UnitarySystem | SPLIT TSE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.47612 |
| 630 | AirLoopHVAC:UnitarySystem | SPLIT TSE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.47612 |
| 631 | AirLoopHVAC:UnitarySystem | SPLIT TSE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.47612 |
| 632 | AirLoopHVAC:UnitarySystem | SPLIT TSE_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 7881.52927 |
| 633 | AirLoopHVAC:UnitarySystem | SPLIT TSE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 10160.41056 |
| 634 | AirLoopHVAC:UnitarySystem | SPLIT TSE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 635 | AirLoopHVAC:UnitarySystem | SPLIT TSE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 636 | Fan:OnOff | SPLIT TSE SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.47612 |
| 637 | Coil:Cooling:DX:SingleSpeed | SPLIT TSE COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.47612 |
| 638 | Coil:Cooling:DX:SingleSpeed | SPLIT TSE COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 7881.52927 |
| 639 | Coil:Cooling:DX:SingleSpeed | SPLIT TSE COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
| 640 | Coil:Heating:Fuel | SPLIT TSE HEATING COIL | Design Size Nominal Capacity [W] | 10160.41056 |
| 641 | Controller:OutdoorAir | SPLIT TNE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.47385 |
| 642 | Controller:OutdoorAir | SPLIT TNE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.59546E-002 |
| 643 | AirLoopHVAC:UnitarySystem | SPLIT TNE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.47385 |
| 644 | AirLoopHVAC:UnitarySystem | SPLIT TNE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.47385 |
| 645 | AirLoopHVAC:UnitarySystem | SPLIT TNE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.47385 |
| 646 | AirLoopHVAC:UnitarySystem | SPLIT TNE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.47385 |
| 647 | AirLoopHVAC:UnitarySystem | SPLIT TNE_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 7843.90804 |
| 648 | AirLoopHVAC:UnitarySystem | SPLIT TNE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 10115.17255 |
| 649 | AirLoopHVAC:UnitarySystem | SPLIT TNE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 650 | AirLoopHVAC:UnitarySystem | SPLIT TNE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 651 | Fan:OnOff | SPLIT TNE SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.47385 |
| 652 | Coil:Cooling:DX:SingleSpeed | SPLIT TNE COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.47385 |
| 653 | Coil:Cooling:DX:SingleSpeed | SPLIT TNE COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 7843.90804 |
| 654 | Coil:Cooling:DX:SingleSpeed | SPLIT TNE COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
| 655 | Coil:Heating:Fuel | SPLIT TNE HEATING COIL | Design Size Nominal Capacity [W] | 10115.17255 |
| 656 | Controller:OutdoorAir | SPLIT TN1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.43242 |
| 657 | Controller:OutdoorAir | SPLIT TN1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.59546E-002 |
| 658 | AirLoopHVAC:UnitarySystem | SPLIT TN1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.43242 |
| 659 | AirLoopHVAC:UnitarySystem | SPLIT TN1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.43242 |
| 660 | AirLoopHVAC:UnitarySystem | SPLIT TN1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.43242 |
| 661 | AirLoopHVAC:UnitarySystem | SPLIT TN1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.43242 |
| 662 | AirLoopHVAC:UnitarySystem | SPLIT TN1_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 7158.01971 |
| 663 | AirLoopHVAC:UnitarySystem | SPLIT TN1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 9293.05437 |
| 664 | AirLoopHVAC:UnitarySystem | SPLIT TN1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 665 | AirLoopHVAC:UnitarySystem | SPLIT TN1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 666 | Fan:OnOff | SPLIT TN1 SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.43242 |
| 667 | Coil:Cooling:DX:SingleSpeed | SPLIT TN1 COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.43242 |
| 668 | Coil:Cooling:DX:SingleSpeed | SPLIT TN1 COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 7158.01971 |
| 669 | Coil:Cooling:DX:SingleSpeed | SPLIT TN1 COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
| 670 | Coil:Heating:Fuel | SPLIT TN1 HEATING COIL | Design Size Nominal Capacity [W] | 9293.05437 |
| 671 | Controller:OutdoorAir | SPLIT TN2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.43101 |
| 672 | Controller:OutdoorAir | SPLIT TN2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.59546E-002 |
| 673 | AirLoopHVAC:UnitarySystem | SPLIT TN2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.43101 |
| 674 | AirLoopHVAC:UnitarySystem | SPLIT TN2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.43101 |
| 675 | AirLoopHVAC:UnitarySystem | SPLIT TN2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.43101 |
| 676 | AirLoopHVAC:UnitarySystem | SPLIT TN2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.43101 |
| 677 | AirLoopHVAC:UnitarySystem | SPLIT TN2_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 7134.74481 |
| 678 | AirLoopHVAC:UnitarySystem | SPLIT TN2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 9265.16637 |
| 679 | AirLoopHVAC:UnitarySystem | SPLIT TN2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 680 | AirLoopHVAC:UnitarySystem | SPLIT TN2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 681 | Fan:OnOff | SPLIT TN2 SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.43101 |
| 682 | Coil:Cooling:DX:SingleSpeed | SPLIT TN2 COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.43101 |
| 683 | Coil:Cooling:DX:SingleSpeed | SPLIT TN2 COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 7134.74481 |
| 684 | Coil:Cooling:DX:SingleSpeed | SPLIT TN2 COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
| 685 | Coil:Heating:Fuel | SPLIT TN2 HEATING COIL | Design Size Nominal Capacity [W] | 9265.16637 |
| 686 | Controller:OutdoorAir | SPLIT TS1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.43522 |
| 687 | Controller:OutdoorAir | SPLIT TS1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.59546E-002 |
| 688 | AirLoopHVAC:UnitarySystem | SPLIT TS1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.43522 |
| 689 | AirLoopHVAC:UnitarySystem | SPLIT TS1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.43522 |
| 690 | AirLoopHVAC:UnitarySystem | SPLIT TS1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.43522 |
| 691 | AirLoopHVAC:UnitarySystem | SPLIT TS1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.43522 |
| 692 | AirLoopHVAC:UnitarySystem | SPLIT TS1_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 7204.37096 |
| 693 | AirLoopHVAC:UnitarySystem | SPLIT TS1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 9348.74467 |
| 694 | AirLoopHVAC:UnitarySystem | SPLIT TS1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 695 | AirLoopHVAC:UnitarySystem | SPLIT TS1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 696 | Fan:OnOff | SPLIT TS1 SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.43522 |
| 697 | Coil:Cooling:DX:SingleSpeed | SPLIT TS1 COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.43522 |
| 698 | Coil:Cooling:DX:SingleSpeed | SPLIT TS1 COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 7204.37096 |
| 699 | Coil:Cooling:DX:SingleSpeed | SPLIT TS1 COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
| 700 | Coil:Heating:Fuel | SPLIT TS1 HEATING COIL | Design Size Nominal Capacity [W] | 9348.74467 |
| 701 | Controller:OutdoorAir | SPLIT TS2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.43382 |
| 702 | Controller:OutdoorAir | SPLIT TS2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.59546E-002 |
| 703 | AirLoopHVAC:UnitarySystem | SPLIT TS2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.43382 |
| 704 | AirLoopHVAC:UnitarySystem | SPLIT TS2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.43382 |
| 705 | AirLoopHVAC:UnitarySystem | SPLIT TS2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.43382 |
| 706 | AirLoopHVAC:UnitarySystem | SPLIT TS2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.43382 |
| 707 | AirLoopHVAC:UnitarySystem | SPLIT TS2_UNITARY_PACKAGE_DX | Design Size Nominal Cooling Capacity [W] | 7181.18334 |
| 708 | AirLoopHVAC:UnitarySystem | SPLIT TS2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 9320.96073 |
| 709 | AirLoopHVAC:UnitarySystem | SPLIT TS2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
| 710 | AirLoopHVAC:UnitarySystem | SPLIT TS2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 711 | Fan:OnOff | SPLIT TS2 SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.43382 |
| 712 | Coil:Cooling:DX:SingleSpeed | SPLIT TS2 COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.43382 |
| 713 | Coil:Cooling:DX:SingleSpeed | SPLIT TS2 COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 7181.18334 |
| 714 | Coil:Cooling:DX:SingleSpeed | SPLIT TS2 COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
| 715 | Coil:Heating:Fuel | SPLIT TS2 HEATING COIL | Design Size Nominal Capacity [W] | 9320.96073 |
| Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
| 1 | Coil:Cooling:DX:SingleSpeed | SPLIT GSW COOLING COIL | 6152.8 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 |
| 2 | Coil:Cooling:DX:SingleSpeed | SPLIT GNW COOLING COIL | 6044.6 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 |
| 3 | Coil:Cooling:DX:SingleSpeed | SPLIT OFFICE COOLING COIL | 6805.1 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 |
| 4 | Coil:Cooling:DX:SingleSpeed | SPLIT GNE COOLING COIL | 5726.3 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 |
| 5 | Coil:Cooling:DX:SingleSpeed | SPLIT GN1 COOLING COIL | 5158.6 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 |
| 6 | Coil:Cooling:DX:SingleSpeed | SPLIT GN2 COOLING COIL | 5152.7 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 |
| 7 | Coil:Cooling:DX:SingleSpeed | SPLIT GS1 COOLING COIL | 5287.8 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 |
| 8 | Coil:Cooling:DX:SingleSpeed | SPLIT GS2 COOLING COIL | 5330.4 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 |
| 9 | Coil:Cooling:DX:SingleSpeed | SPLIT MSW COOLING COIL | 14518.0 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 |
| 10 | Coil:Cooling:DX:SingleSpeed | SPLIT MNW COOLING COIL | 14313.1 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 |
| 11 | Coil:Cooling:DX:SingleSpeed | SPLIT MSE COOLING COIL | 13679.4 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 |
| 12 | Coil:Cooling:DX:SingleSpeed | SPLIT MNE COOLING COIL | 13477.0 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 |
| 13 | Coil:Cooling:DX:SingleSpeed | SPLIT MN1 COOLING COIL | 11973.1 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 |
| 14 | Coil:Cooling:DX:SingleSpeed | SPLIT MN2 COOLING COIL | 11957.4 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 |
| 15 | Coil:Cooling:DX:SingleSpeed | SPLIT MS1 COOLING COIL | 12211.2 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 |
| 16 | Coil:Cooling:DX:SingleSpeed | SPLIT MS2 COOLING COIL | 12195.2 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 |
| 17 | Coil:Cooling:DX:SingleSpeed | SPLIT TSW COOLING COIL | 8155.1 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 |
| 18 | Coil:Cooling:DX:SingleSpeed | SPLIT TNW COOLING COIL | 8120.0 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 |
| 19 | Coil:Cooling:DX:SingleSpeed | SPLIT TSE COOLING COIL | 7508.4 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 |
| 20 | Coil:Cooling:DX:SingleSpeed | SPLIT TNE COOLING COIL | 7472.6 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 |
| 21 | Coil:Cooling:DX:SingleSpeed | SPLIT TN1 COOLING COIL | 6819.1 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 |
| 22 | Coil:Cooling:DX:SingleSpeed | SPLIT TN2 COOLING COIL | 6797.0 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 |
| 23 | Coil:Cooling:DX:SingleSpeed | SPLIT TS1 COOLING COIL | 6863.3 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 |
| 24 | Coil:Cooling:DX:SingleSpeed | SPLIT TS2 COOLING COIL | 6841.2 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 |
| Zone Name | # Surfaces | |
| 1 | G SW APARTMENT | 9 |
| 2 | G NW APARTMENT | 9 |
| 3 | OFFICE | 9 |
| 4 | G NE APARTMENT | 9 |
| 5 | G N1 APARTMENT | 8 |
| 6 | G N2 APARTMENT | 8 |
| 7 | G S1 APARTMENT | 8 |
| 8 | G S2 APARTMENT | 8 |
| 9 | M SW APARTMENT | 9 |
| 10 | M NW APARTMENT | 9 |
| 11 | M SE APARTMENT | 9 |
| 12 | M NE APARTMENT | 9 |
| 13 | M N1 APARTMENT | 8 |
| 14 | M N2 APARTMENT | 8 |
| 15 | M S1 APARTMENT | 8 |
| 16 | M S2 APARTMENT | 8 |
| 17 | T SW APARTMENT | 9 |
| 18 | T NW APARTMENT | 9 |
| 19 | T SE APARTMENT | 9 |
| 20 | T NE APARTMENT | 9 |
| 21 | T N1 APARTMENT | 8 |
| 22 | T N2 APARTMENT | 8 |
| 23 | T S1 APARTMENT | 8 |
| 24 | T S2 APARTMENT | 8 |
| 25 | T CORRIDOR | 13 |
| 26 | G CORRIDOR | 13 |
| 27 | M CORRIDOR | 13 |
| Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
| 1 | G SWALL SWA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_GRD | 0.752 | 0.676 | 28.24 | 35.30 | 28.24 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 2 | GWINDOW1 S SWA | Window | G SWALL SWA | Window5 Detailed Fenestration | RESWINDOW_U_0.4945_SHGC_0.25 | N/A | 2.811 | No | 7.06 | 7.06 | 7.06 | 180.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 3 | G WWALL SWA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_GRD | 0.752 | 0.676 | 18.58 | 23.22 | 18.58 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 4 | GWINDOW1 W SWA | Window | G WWALL SWA | Window5 Detailed Fenestration | RESWINDOW_U_0.4945_SHGC_0.25 | N/A | 2.811 | No | 4.65 | 4.65 | 4.65 | 270.00 | 90.00 | 3.81 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 5 | G NIWALL SWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-G NIWALL SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 6 | G EIWALL SWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | iz-G EIWALL SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 7 | G GFLOOR SWA | Floor | CTF - ConductionTransferFunction | GGFLOORSWA_FFACTOR | 0.287 | 0.268 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 8 | G CEILIN SWA | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | G CEILIN SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 9 | G INTERNALMASS SWA | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 88.25 | 88.25 | 88.25 | 0.00 | 90.00 | 88.25 | 1.00 | 0.00 | G INTERNALMASS SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 10 | G NWALL NWA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_GRD | 0.752 | 0.676 | 28.24 | 35.30 | 28.24 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 11 | GWINDOW1 N NWA | Window | G NWALL NWA | Window5 Detailed Fenestration | RESWINDOW_U_0.4945_SHGC_0.25 | N/A | 2.811 | No | 7.06 | 7.06 | 7.06 | 0.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 12 | G WWALL NWA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_GRD | 0.752 | 0.676 | 18.58 | 23.22 | 18.58 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 13 | GWINDOW1 W NWA | Window | G WWALL NWA | Window5 Detailed Fenestration | RESWINDOW_U_0.4945_SHGC_0.25 | N/A | 2.811 | No | 4.65 | 4.65 | 4.65 | 270.00 | 90.00 | 3.81 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 14 | G SIWALL NWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-G SIWALL NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 15 | G EIWALL NWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | iz-G EIWALL NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 16 | G GFLOOR NWA | Floor | CTF - ConductionTransferFunction | GGFLOORNWA_FFACTOR | 0.287 | 0.268 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 17 | G CEILIN NWA | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | G CEILIN NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 18 | G INTERNALMASS NWA | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 88.25 | 88.25 | 88.25 | 0.00 | 90.00 | 88.25 | 1.00 | 0.00 | G INTERNALMASS NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 19 | G SWALL SEA | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.752 | 0.676 | 28.24 | 35.30 | 28.24 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 20 | GWINDOW1 S SEA | Window | G SWALL SEA | Window5 Detailed Fenestration | NONRESWINDOW_U_0.4945_SHGC_0.25 | N/A | 2.811 | No | 7.06 | 7.06 | 7.06 | 180.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 21 | G EWALL SEA | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.752 | 0.676 | 18.58 | 23.22 | 18.58 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 22 | GWINDOW1 E SEA | Window | G EWALL SEA | Window5 Detailed Fenestration | NONRESWINDOW_U_0.4945_SHGC_0.25 | N/A | 2.811 | No | 4.65 | 4.65 | 4.65 | 90.00 | 90.00 | 3.81 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 23 | G NIWALL SEA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-G NIWALL SEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 24 | iz-G EIWALL S2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | G EIWALL S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 25 | G GFLOOR SEA | Floor | CTF - ConductionTransferFunction | GGFLOORSEA_FFACTOR | 0.287 | 0.268 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 26 | G CEILIN SEA | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | G CEILIN SEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 27 | G INTERNALMASS SEA | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 88.25 | 88.25 | 88.25 | 0.00 | 90.00 | 88.25 | 1.00 | 0.00 | G INTERNALMASS SEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 28 | G NWALL NEA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_GRD | 0.752 | 0.676 | 28.24 | 35.30 | 28.24 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 29 | GWINDOW1 N NEA | Window | G NWALL NEA | Window5 Detailed Fenestration | RESWINDOW_U_0.4945_SHGC_0.25 | N/A | 2.811 | No | 7.06 | 7.06 | 7.06 | 0.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 30 | G EWALL NEA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_GRD | 0.752 | 0.676 | 18.58 | 23.22 | 18.58 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 31 | GWINDOW1 E NEA | Window | G EWALL NEA | Window5 Detailed Fenestration | RESWINDOW_U_0.4945_SHGC_0.25 | N/A | 2.811 | No | 4.65 | 4.65 | 4.65 | 90.00 | 90.00 | 3.81 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 32 | G SIWALL NEA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-G SIWALL NEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 33 | iz-G EIWALL N2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | G EIWALL N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 34 | G GFLOOR NEA | Floor | CTF - ConductionTransferFunction | GGFLOORNEA_FFACTOR | 0.287 | 0.268 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 35 | G CEILIN NEA | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | G CEILIN NEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 36 | G INTERNALMASS NEA | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 88.25 | 88.25 | 88.25 | 0.00 | 90.00 | 88.25 | 1.00 | 0.00 | G INTERNALMASS NEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 37 | G NWALL N1A | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_GRD | 0.752 | 0.676 | 28.24 | 35.30 | 28.24 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 38 | GWINDOW1 N N1A | Window | G NWALL N1A | Window5 Detailed Fenestration | RESWINDOW_U_0.4945_SHGC_0.25 | N/A | 2.811 | No | 7.06 | 7.06 | 7.06 | 0.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 39 | G SIWALL N1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-G SIWALL N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 40 | G EIWALL N1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | iz-G EIWALL N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 41 | iz-G EIWALL NWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | G EIWALL NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 42 | G GFLOOR N1A | Floor | CTF - ConductionTransferFunction | GGFLOORN1A_FFACTOR | 0.170 | 0.163 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 43 | G CEILIN N1A | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | G CEILIN N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 44 | G INTERNALMASS N1A | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 88.25 | 88.25 | 88.25 | 0.00 | 90.00 | 88.25 | 1.00 | 0.00 | G INTERNALMASS N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 45 | G NWALL N2A | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_GRD | 0.752 | 0.676 | 28.24 | 35.30 | 28.24 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 46 | GWINDOW1 N N2A | Window | G NWALL N2A | Window5 Detailed Fenestration | RESWINDOW_U_0.4945_SHGC_0.25 | N/A | 2.811 | No | 7.06 | 7.06 | 7.06 | 0.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 47 | G SIWALL N2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-G SIWALL N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 48 | G EIWALL N2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | iz-G EIWALL N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 49 | iz-G EIWALL N1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | G EIWALL N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 50 | G GFLOOR N2A | Floor | CTF - ConductionTransferFunction | GGFLOORN2A_FFACTOR | 0.170 | 0.163 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 51 | G CEILIN N2A | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | G CEILIN N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 52 | G INTERNALMASS N2A | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 88.25 | 88.25 | 88.25 | 0.00 | 90.00 | 88.25 | 1.00 | 0.00 | G INTERNALMASS N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 53 | G SWALL S1A | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_GRD | 0.752 | 0.676 | 28.24 | 35.30 | 28.24 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 54 | GWINDOW1 S S1A | Window | G SWALL S1A | Window5 Detailed Fenestration | RESWINDOW_U_0.4945_SHGC_0.25 | N/A | 2.811 | No | 7.06 | 7.06 | 7.06 | 180.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 55 | G NIWALL S1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-G NIWALL S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 56 | G EIWALL S1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | iz-G EIWALL S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 57 | iz-G EIWALL SWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | G EIWALL SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 58 | G GFLOOR S1A | Floor | CTF - ConductionTransferFunction | GGFLOORS1A_FFACTOR | 0.170 | 0.163 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 59 | G CEILIN S1A | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | G CEILIN S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 60 | G INTERNALMASS S1A | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 88.25 | 88.25 | 88.25 | 0.00 | 90.00 | 88.25 | 1.00 | 0.00 | G INTERNALMASS S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 61 | G SWALL S2A | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_GRD | 0.752 | 0.676 | 28.24 | 35.30 | 28.24 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 62 | GWINDOW1 S S2A | Window | G SWALL S2A | Window5 Detailed Fenestration | RESWINDOW_U_0.4945_SHGC_0.25 | N/A | 2.811 | No | 7.06 | 7.06 | 7.06 | 180.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 63 | G NIWALL S2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-G NIWALL S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 64 | G EIWALL S2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | iz-G EIWALL S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 65 | iz-G EIWALL S1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | G EIWALL S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 66 | G GFLOOR S2A | Floor | CTF - ConductionTransferFunction | GGFLOORS2A_FFACTOR | 0.170 | 0.163 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 67 | G CEILIN S2A | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | G CEILIN S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 68 | G INTERNALMASS S2A | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 88.25 | 88.25 | 88.25 | 0.00 | 90.00 | 88.25 | 1.00 | 0.00 | G INTERNALMASS S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 69 | M WWALL SWA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.761 | 0.683 | 18.58 | 23.22 | 18.58 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 70 | MWINDOW1 W SWA | Window | M WWALL SWA | Window5 Detailed Fenestration | RESWINDOW_U_0.4945_SHGC_0.25 | N/A | 2.811 | No | 4.65 | 4.65 | 4.65 | 270.00 | 90.00 | 3.81 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 71 | M SWALL SWA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.761 | 0.683 | 28.24 | 35.30 | 28.24 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 72 | MWINDOW1 S SWA | Window | M SWALL SWA | Window5 Detailed Fenestration | RESWINDOW_U_0.4945_SHGC_0.25 | N/A | 2.811 | No | 7.06 | 7.06 | 7.06 | 180.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 73 | M NIWALL SWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-M NIWALL SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 74 | M EIWALL SWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 90.00 | 90.00 | 3.05 | 7.62 | 0.00 | iz-M EIWALL SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 75 | M GFLOOR SWA | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | M GFLOOR SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 76 | M CEILIN SWA | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | M CEILIN SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 77 | M INTERNALMASS SWA | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 176.50 | 176.50 | 176.50 | 0.00 | 90.00 | 176.50 | 1.00 | 0.00 | M INTERNALMASS SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 78 | M NWALL NWA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.761 | 0.683 | 28.24 | 35.30 | 28.24 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 79 | MWINDOW1 N NWA | Window | M NWALL NWA | Window5 Detailed Fenestration | RESWINDOW_U_0.4945_SHGC_0.25 | N/A | 2.811 | No | 7.06 | 7.06 | 7.06 | 0.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 80 | M WWALL NWA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.761 | 0.683 | 18.58 | 23.22 | 18.58 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 81 | MWINDOW1 W NWA | Window | M WWALL NWA | Window5 Detailed Fenestration | RESWINDOW_U_0.4945_SHGC_0.25 | N/A | 2.811 | No | 4.65 | 4.65 | 4.65 | 270.00 | 90.00 | 3.81 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 82 | M SIWALL NWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-M SIWALL NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 83 | M EIWALL NWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | iz-M EIWALL NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 84 | M GFLOOR NWA | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | M GFLOOR NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 85 | M CEILIN NWA | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | M CEILIN NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 86 | M INTERNALMASS NWA | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 176.50 | 176.50 | 176.50 | 0.00 | 90.00 | 176.50 | 1.00 | 0.00 | M INTERNALMASS NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 87 | M EWALL SEA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.761 | 0.683 | 18.58 | 23.22 | 18.58 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 88 | MWINDOW1 E SEA | Window | M EWALL SEA | Window5 Detailed Fenestration | RESWINDOW_U_0.4945_SHGC_0.25 | N/A | 2.811 | No | 4.65 | 4.65 | 4.65 | 90.00 | 90.00 | 3.81 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 89 | M SWALL SEA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.761 | 0.683 | 28.24 | 35.30 | 28.24 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 90 | MWINDOW1 S SEA | Window | M SWALL SEA | Window5 Detailed Fenestration | RESWINDOW_U_0.4945_SHGC_0.25 | N/A | 2.811 | No | 7.06 | 7.06 | 7.06 | 180.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 91 | M NIWALL SEA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-M NIWALL SEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 92 | iz-M EIWALL S2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | M EIWALL S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 93 | M GFLOOR SEA | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | M GFLOOR SEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 94 | M CEILIN SEA | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | M CEILIN SEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 95 | M INTERNALMASS SEA | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 176.50 | 176.50 | 176.50 | 0.00 | 90.00 | 176.50 | 1.00 | 0.00 | M INTERNALMASS SEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 96 | M NWALL NEA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.761 | 0.683 | 28.24 | 35.30 | 28.24 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 97 | MWINDOW1 N NEA | Window | M NWALL NEA | Window5 Detailed Fenestration | RESWINDOW_U_0.4945_SHGC_0.25 | N/A | 2.811 | No | 7.06 | 7.06 | 7.06 | 0.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 98 | M EWALL NEA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.761 | 0.683 | 18.58 | 23.22 | 18.58 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 99 | MWINDOW1 E NEA | Window | M EWALL NEA | Window5 Detailed Fenestration | RESWINDOW_U_0.4945_SHGC_0.25 | N/A | 2.811 | No | 4.65 | 4.65 | 4.65 | 90.00 | 90.00 | 3.81 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 100 | M SIWALL NEA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-M SIWALL NEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 101 | iz-M EIWALL N2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | M EIWALL N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 102 | M GFLOOR NEA | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | M GFLOOR NEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 103 | M CEILIN NEA | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | M CEILIN NEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 104 | M INTERNALMASS NEA | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 176.50 | 176.50 | 176.50 | 0.00 | 90.00 | 176.50 | 1.00 | 0.00 | M INTERNALMASS NEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 105 | M NWALL N1A | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.761 | 0.683 | 28.24 | 35.30 | 28.24 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 106 | MWINDOW1 N N1A | Window | M NWALL N1A | Window5 Detailed Fenestration | RESWINDOW_U_0.4945_SHGC_0.25 | N/A | 2.811 | No | 7.06 | 7.06 | 7.06 | 0.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 107 | M SIWALL N1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-M SIWALL N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 108 | M EIWALL N1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | iz-M EIWALL N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 109 | iz-M EIWALL NWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | M EIWALL NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 110 | M GFLOOR N1A | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | M GFLOOR N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 111 | M CEILIN N1A | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | M CEILIN N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 112 | M INTERNALMASS N1A | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 176.50 | 176.50 | 176.50 | 0.00 | 90.00 | 176.50 | 1.00 | 0.00 | M INTERNALMASS N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 113 | M NWALL N2A | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.761 | 0.683 | 28.24 | 35.30 | 28.24 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 114 | MWINDOW1 N N2A | Window | M NWALL N2A | Window5 Detailed Fenestration | RESWINDOW_U_0.4945_SHGC_0.25 | N/A | 2.811 | No | 7.06 | 7.06 | 7.06 | 0.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 115 | M SIWALL N2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-M SIWALL N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 116 | M EIWALL N2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | iz-M EIWALL N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 117 | iz-M EIWALL N1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | M EIWALL N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 118 | M GFLOOR N2A | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | M GFLOOR N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 119 | M CEILIN N2A | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | M CEILIN N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 120 | M INTERNALMASS N2A | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 176.50 | 176.50 | 176.50 | 0.00 | 90.00 | 176.50 | 1.00 | 0.00 | M INTERNALMASS N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 121 | M SWALL S1A | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.761 | 0.683 | 28.24 | 35.30 | 28.24 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 122 | MWINDOW1 S S1A | Window | M SWALL S1A | Window5 Detailed Fenestration | RESWINDOW_U_0.4945_SHGC_0.25 | N/A | 2.811 | No | 7.06 | 7.06 | 7.06 | 180.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 123 | M NIWALL S1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-M NIWALL S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 124 | M EIWALL S1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | iz-M EIWALL S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 125 | iz-M EIWALL SWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 270.00 | 90.00 | 3.05 | 7.62 | 0.00 | M EIWALL SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 126 | M GFLOOR S1A | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | M GFLOOR S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 127 | M CEILIN S1A | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | M CEILIN S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 128 | M INTERNALMASS S1A | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 176.50 | 176.50 | 176.50 | 0.00 | 90.00 | 176.50 | 1.00 | 0.00 | M INTERNALMASS S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 129 | M SWALL S2A | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.761 | 0.683 | 28.24 | 35.30 | 28.24 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 130 | MWINDOW1 S S2A | Window | M SWALL S2A | Window5 Detailed Fenestration | RESWINDOW_U_0.4945_SHGC_0.25 | N/A | 2.811 | No | 7.06 | 7.06 | 7.06 | 180.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 131 | M NIWALL S2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-M NIWALL S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 132 | M EIWALL S2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | iz-M EIWALL S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 133 | iz-M EIWALL S1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | M EIWALL S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 134 | M GFLOOR S2A | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | M GFLOOR S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 135 | M CEILIN S2A | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | M CEILIN S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 136 | M INTERNALMASS S2A | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 176.50 | 176.50 | 176.50 | 0.00 | 90.00 | 176.50 | 1.00 | 0.00 | M INTERNALMASS S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 137 | T WWALL SWA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.098 | 0.943 | 18.58 | 23.22 | 18.58 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 138 | TWINDOW1 W SWA | Window | T WWALL SWA | Window5 Detailed Fenestration | RESWINDOW_U_0.4945_SHGC_0.25 | N/A | 2.811 | No | 4.65 | 4.65 | 4.65 | 270.00 | 90.00 | 3.81 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 139 | T SWALL SWA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.098 | 0.943 | 28.24 | 35.30 | 28.24 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 140 | TWINDOW1 S SWA | Window | T SWALL SWA | Window5 Detailed Fenestration | RESWINDOW_U_0.4945_SHGC_0.25 | N/A | 2.811 | No | 7.06 | 7.06 | 7.06 | 180.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 141 | T NIWALL SWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-T NIWALL SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 142 | T EIWALL SWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | iz-T EIWALL SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 143 | T GFLOOR SWA | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | T GFLOOR SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 144 | T ROOF SWA | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.283 | 0.269 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 145 | T INTERNALMASS SWA | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 88.25 | 88.25 | 88.25 | 0.00 | 90.00 | 88.25 | 1.00 | 0.00 | T INTERNALMASS SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 146 | T NWALL NWA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.098 | 0.943 | 28.24 | 35.30 | 28.24 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 147 | TWINDOW1 N NWA | Window | T NWALL NWA | Window5 Detailed Fenestration | RESWINDOW_U_0.4945_SHGC_0.25 | N/A | 2.811 | No | 7.06 | 7.06 | 7.06 | 0.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 148 | T WWALL NWA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.098 | 0.943 | 18.58 | 23.22 | 18.58 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 149 | TWINDOW1 W NWA | Window | T WWALL NWA | Window5 Detailed Fenestration | RESWINDOW_U_0.4945_SHGC_0.25 | N/A | 2.811 | No | 4.65 | 4.65 | 4.65 | 270.00 | 90.00 | 3.81 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 150 | T SIWALL NWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-T SIWALL NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 151 | T EIWALL NWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | iz-T EIWALL NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 152 | T GFLOOR NWA | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | T GFLOOR NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 153 | T ROOF NWA | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.283 | 0.269 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 154 | T INTERNALMASS NWA | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 88.25 | 88.25 | 88.25 | 0.00 | 90.00 | 88.25 | 1.00 | 0.00 | T INTERNALMASS NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 155 | T EWALL SEA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.098 | 0.943 | 18.58 | 23.22 | 18.58 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 156 | TWINDOW1 E SEA | Window | T EWALL SEA | Window5 Detailed Fenestration | RESWINDOW_U_0.4945_SHGC_0.25 | N/A | 2.811 | No | 4.65 | 4.65 | 4.65 | 90.00 | 90.00 | 3.81 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 157 | T SWALL SEA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.098 | 0.943 | 28.24 | 35.30 | 28.24 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 158 | TWINDOW1 S SEA | Window | T SWALL SEA | Window5 Detailed Fenestration | RESWINDOW_U_0.4945_SHGC_0.25 | N/A | 2.811 | No | 7.06 | 7.06 | 7.06 | 180.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 159 | T NIWALL SEA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-T NIWALL SEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 160 | iz-T EIWALL S2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | T EIWALL S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 161 | T GFLOOR SEA | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | T GFLOOR SEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 162 | T ROOF SEA | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.283 | 0.269 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 163 | T INTERNALMASS SEA | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 88.25 | 88.25 | 88.25 | 0.00 | 90.00 | 88.25 | 1.00 | 0.00 | T INTERNALMASS SEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 164 | T NWALL NEA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.098 | 0.943 | 28.24 | 35.30 | 28.24 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 165 | TWINDOW1 N NEA | Window | T NWALL NEA | Window5 Detailed Fenestration | RESWINDOW_U_0.4945_SHGC_0.25 | N/A | 2.811 | No | 7.06 | 7.06 | 7.06 | 0.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 166 | T EWALL NEA | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.098 | 0.943 | 18.58 | 23.22 | 18.58 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 167 | TWINDOW1 E NEA | Window | T EWALL NEA | Window5 Detailed Fenestration | RESWINDOW_U_0.4945_SHGC_0.25 | N/A | 2.811 | No | 4.65 | 4.65 | 4.65 | 90.00 | 90.00 | 3.81 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 168 | T SIWALL NEA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-T SIWALL NEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 169 | iz-T EIWALL N2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | T EIWALL N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 170 | T GFLOOR NEA | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | T GFLOOR NEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 171 | T ROOF NEA | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.283 | 0.269 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 172 | T INTERNALMASS NEA | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 88.25 | 88.25 | 88.25 | 0.00 | 90.00 | 88.25 | 1.00 | 0.00 | T INTERNALMASS NEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 173 | T NWALL N1A | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.098 | 0.943 | 28.24 | 35.30 | 28.24 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 174 | TWINDOW1 N N1A | Window | T NWALL N1A | Window5 Detailed Fenestration | RESWINDOW_U_0.4945_SHGC_0.25 | N/A | 2.811 | No | 7.06 | 7.06 | 7.06 | 0.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 175 | T SIWALL N1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-T SIWALL N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 176 | T EIWALL N1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | iz-T EIWALL N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 177 | iz-T EIWALL NWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | T EIWALL NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 178 | T GFLOOR N1A | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | T GFLOOR N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 179 | T ROOF N1A | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.283 | 0.269 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 180 | T INTERNALMASS N1A | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 88.25 | 88.25 | 88.25 | 0.00 | 90.00 | 88.25 | 1.00 | 0.00 | T INTERNALMASS N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 181 | T NWALL N2A | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.098 | 0.943 | 28.24 | 35.30 | 28.24 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 182 | TWINDOW1 N N2A | Window | T NWALL N2A | Window5 Detailed Fenestration | RESWINDOW_U_0.4945_SHGC_0.25 | N/A | 2.811 | No | 7.06 | 7.06 | 7.06 | 0.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 183 | T SIWALL N2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-T SIWALL N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 184 | T EIWALL N2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | iz-T EIWALL N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 185 | iz-T EIWALL N1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | T EIWALL N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 186 | T GFLOOR N2A | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | T GFLOOR N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 187 | T ROOF N2A | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.283 | 0.269 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 188 | T INTERNALMASS N2A | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 88.25 | 88.25 | 88.25 | 0.00 | 90.00 | 88.25 | 1.00 | 0.00 | T INTERNALMASS N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 189 | T SWALL S1A | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.098 | 0.943 | 28.24 | 35.30 | 28.24 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 190 | TWINDOW1 S S1A | Window | T SWALL S1A | Window5 Detailed Fenestration | RESWINDOW_U_0.4945_SHGC_0.25 | N/A | 2.811 | No | 7.06 | 7.06 | 7.06 | 180.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 191 | T NIWALL S1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-T NIWALL S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 192 | T EIWALL S1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | iz-T EIWALL S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 193 | iz-T EIWALL SWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | T EIWALL SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 194 | T GFLOOR S1A | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | T GFLOOR S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 195 | T ROOF S1A | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.283 | 0.269 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 196 | T INTERNALMASS S1A | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 88.25 | 88.25 | 88.25 | 0.00 | 90.00 | 88.25 | 1.00 | 0.00 | T INTERNALMASS S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 197 | T SWALL S2A | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.098 | 0.943 | 28.24 | 35.30 | 28.24 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 198 | TWINDOW1 S S2A | Window | T SWALL S2A | Window5 Detailed Fenestration | RESWINDOW_U_0.4945_SHGC_0.25 | N/A | 2.811 | No | 7.06 | 7.06 | 7.06 | 180.00 | 90.00 | 5.79 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 199 | T NIWALL S2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | iz-T NIWALL S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 200 | T EIWALL S2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | iz-T EIWALL S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 201 | iz-T EIWALL S1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 23.22 | 23.22 | 23.22 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | T EIWALL S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 202 | T GFLOOR S2A | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 88.25 | 88.25 | 88.25 | 90.00 | 180.00 | 7.62 | 11.58 | 0.00 | T GFLOOR S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 203 | T ROOF S2A | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.283 | 0.269 | 88.25 | 88.25 | 88.25 | 180.00 | 0.00 | 11.58 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 204 | T INTERNALMASS S2A | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 88.25 | 88.25 | 88.25 | 0.00 | 90.00 | 88.25 | 1.00 | 0.00 | T INTERNALMASS S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 205 | T WWALL C | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.098 | 0.943 | 5.11 | 5.11 | 5.11 | 270.00 | 90.00 | 1.68 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 206 | T EWALL C | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.098 | 0.943 | 3.99 | 5.11 | 3.99 | 90.00 | 90.00 | 1.68 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 207 | TWINDOW14 | Window | T EWALL C | Window5 Detailed Fenestration | NONRESWINDOW_U_0.4945_SHGC_0.25 | N/A | 2.811 | No | 1.11 | 1.11 | 1.11 | 90.00 | 90.00 | 0.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 208 | iz-T NIWALL SWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | T NIWALL SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 209 | iz-T NIWALL S1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | T NIWALL S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 210 | iz-T NIWALL S2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | T NIWALL S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 211 | iz-T NIWALL SEA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | T NIWALL SEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 212 | iz-T SIWALL NWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | T SIWALL NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 213 | iz-T SIWALL N1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | T SIWALL N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 214 | iz-T SIWALL N2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | T SIWALL N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 215 | iz-T SIWALL NEA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | T SIWALL NEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 216 | T FLOOR C | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 77.66 | 77.66 | 77.66 | 90.00 | 180.00 | 1.68 | 46.33 | 0.00 | T FLOOR C | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 217 | T ROOF C | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 77.66 | 77.66 | 77.66 | 180.00 | 0.00 | 46.33 | 1.68 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 218 | G WWALL C | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.752 | 0.676 | 5.11 | 5.11 | 5.11 | 270.00 | 90.00 | 1.68 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 219 | G EWALL C | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.752 | 0.676 | 1.79 | 5.11 | 1.79 | 90.00 | 90.00 | 1.68 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 220 | ENTRANCE DOOR | Window | G EWALL C | Window5 Detailed Fenestration | NONRESWINDOW_U_0.4945_SHGC_0.25 | N/A | 2.811 | No | 3.32 | 3.32 | 3.32 | 90.00 | 90.00 | 1.57 | 2.11 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 221 | iz-G NIWALL SWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | G NIWALL SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 222 | iz-G NIWALL S1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | G NIWALL S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 223 | iz-G NIWALL S2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | G NIWALL S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 224 | iz-G NIWALL SEA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | G NIWALL SEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 225 | iz-G SIWALL NWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | G SIWALL NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 226 | iz-G SIWALL N1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | G SIWALL N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 227 | iz-G SIWALL N2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | G SIWALL N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 228 | iz-G SIWALL NEA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | G SIWALL NEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 229 | G FLOOR C | Floor | CTF - ConductionTransferFunction | GFLOORC_FFACTOR | 5.502E-002 | 5.429E-002 | 77.66 | 77.66 | 77.66 | 90.00 | 180.00 | 1.68 | 46.33 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 230 | G CEILING C | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 77.66 | 77.66 | 77.66 | 180.00 | 0.00 | 46.33 | 1.68 | 0.00 | G CEILING C | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 231 | M WWALL C | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.761 | 0.683 | 5.11 | 5.11 | 5.11 | 270.00 | 90.00 | 1.68 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 232 | M EWALL C | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.761 | 0.683 | 3.99 | 5.11 | 3.99 | 90.00 | 90.00 | 1.68 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 233 | MWINDOW14 | Window | M EWALL C | Window5 Detailed Fenestration | NONRESWINDOW_U_0.4945_SHGC_0.25 | N/A | 2.811 | No | 1.11 | 1.11 | 1.11 | 90.00 | 90.00 | 0.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 234 | iz-M NIWALL SWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | M NIWALL SWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 235 | iz-M NIWALL S1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | M NIWALL S1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 236 | iz-M NIWALL S2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | M NIWALL S2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 237 | iz-M NIWALL SEA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 180.00 | 90.00 | 11.58 | 3.05 | 0.00 | M NIWALL SEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 238 | iz-M SIWALL NWA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | M SIWALL NWA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 239 | iz-M SIWALL N1A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | M SIWALL N1A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 240 | iz-M SIWALL N2A | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | M SIWALL N2A | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 241 | iz-M SIWALL NEA | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.30 | 35.30 | 35.30 | 0.00 | 90.00 | 11.58 | 3.05 | 0.00 | M SIWALL NEA | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 242 | M FLOOR C | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 77.66 | 77.66 | 77.66 | 90.00 | 180.00 | 1.68 | 46.33 | 0.00 | M FLOOR C | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 243 | M CEILING C | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 77.66 | 77.66 | 77.66 | 180.00 | 0.00 | 46.33 | 1.68 | 0.00 | M CEILING C | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
| Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
| 1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | Yes | Yes | Yes | Clark and Allen |
| Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
| 1 | NEW YEAR'S DAY | Holiday | InputFile | 01/02 | 1Environment:Special Days |
| Daylight Saving Indicator | Source | Start Date | End Date | |
| 1 | Yes | InputFile | 03/12 | 11/05 |
| Style | Unit Conversion | |
| 1 | Commaandhtml | commaandhtml |
| Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
| 1 | G SW APARTMENT | RunPeriod: RUNPERIOD 1 | 4.2264338741E-002 | 3.7499155747E-002 | Pass | Pass | 3.8405072849E-002 | 0.1138481476 | Pass | Pass |
| 2 | G NW APARTMENT | RunPeriod: RUNPERIOD 1 | 1.6365604273E-002 | 3.5439621932E-002 | Pass | Pass | 0.1650772609 | 0.3789551374 | Pass | Pass |
| 3 | OFFICE | RunPeriod: RUNPERIOD 1 | 4.8911857753E-002 | 3.4251729834E-002 | Pass | Pass | 0.9280336716 | 8.9193165701 | Pass | Pass |
| 4 | G NE APARTMENT | RunPeriod: RUNPERIOD 1 | 9.1250819714E-003 | 2.4831329352E-002 | Pass | Pass | 0.3285356640 | 1.1741959323 | Pass | Pass |
| 5 | G N1 APARTMENT | RunPeriod: RUNPERIOD 1 | 2.1018817297E-002 | 3.7181327839E-002 | Pass | Pass | 4.1887005511E-002 | 4.1006353830E-002 | Pass | Pass |
| 6 | G N2 APARTMENT | RunPeriod: RUNPERIOD 1 | 2.0682741449E-002 | 3.7067965000E-002 | Pass | Pass | 4.1850129472E-002 | 4.1092363655E-002 | Pass | Pass |
| 7 | G S1 APARTMENT | RunPeriod: RUNPERIOD 1 | 2.4229109139E-002 | 2.9335832513E-002 | Pass | Pass | 3.4713823962E-002 | 9.2293217352E-002 | Pass | Pass |
| 8 | G S2 APARTMENT | RunPeriod: RUNPERIOD 1 | 2.5009022082E-002 | 2.9900608350E-002 | Pass | Pass | 3.6651445048E-002 | 9.5597321133E-002 | Pass | Pass |
| 9 | M SW APARTMENT | RunPeriod: RUNPERIOD 1 | 3.2572710877E-002 | 3.7566669354E-002 | Pass | Pass | 3.5217709936E-002 | 7.0186985691E-002 | Pass | Pass |
| 10 | M NW APARTMENT | RunPeriod: RUNPERIOD 1 | 2.5253622678E-002 | 3.9433448036E-002 | Pass | Pass | 9.1774545169E-002 | 0.2016745531 | Pass | Pass |
| 11 | M SE APARTMENT | RunPeriod: RUNPERIOD 1 | 3.4895374864E-002 | 4.1818822273E-002 | Pass | Pass | 3.8582360488E-002 | 8.7133359329E-002 | Pass | Pass |
| 12 | M NE APARTMENT | RunPeriod: RUNPERIOD 1 | 2.3724957041E-002 | 3.6660095007E-002 | Pass | Pass | 0.3043671671 | 1.1966753465 | Pass | Pass |
| 13 | M N1 APARTMENT | RunPeriod: RUNPERIOD 1 | 3.2721118731E-002 | 3.8726663443E-002 | Pass | Pass | 2.2860312988E-002 | 1.5679864130E-002 | Pass | Pass |
| 14 | M N2 APARTMENT | RunPeriod: RUNPERIOD 1 | 3.2852241246E-002 | 3.8597075403E-002 | Pass | Pass | 2.2887703392E-002 | 1.5700613617E-002 | Pass | Pass |
| 15 | M S1 APARTMENT | RunPeriod: RUNPERIOD 1 | 1.6776374967E-002 | 2.8015946237E-002 | Pass | Pass | 3.2588013687E-002 | 5.8931435840E-002 | Pass | Pass |
| 16 | M S2 APARTMENT | RunPeriod: RUNPERIOD 1 | 1.6914554401E-002 | 2.8232160079E-002 | Pass | Pass | 3.2681076679E-002 | 5.9366476045E-002 | Pass | Pass |
| 17 | T SW APARTMENT | RunPeriod: RUNPERIOD 1 | 4.1721654201E-002 | 7.1903661437E-002 | Pass | Pass | 0.1727613658 | 0.6814386176 | Pass | Pass |
| 18 | T NW APARTMENT | RunPeriod: RUNPERIOD 1 | 1.9315186781E-002 | 4.4921178631E-002 | Pass | Pass | 1.2671690667 | 12.3210626706 | Pass | Pass |
| 19 | T SE APARTMENT | RunPeriod: RUNPERIOD 1 | 4.4569271099E-002 | 7.0771059254E-002 | Pass | Pass | 0.1501680713 | 0.4553925473 | Pass | Pass |
| 20 | T NE APARTMENT | RunPeriod: RUNPERIOD 1 | 8.0808783924E-003 | 2.8135183753E-002 | Pass | Pass | 0.2282719261 | 0.5874389759 | Pass | Pass |
| 21 | T N1 APARTMENT | RunPeriod: RUNPERIOD 1 | 1.5058389679E-002 | 3.8356421290E-002 | Pass | Pass | 0.2279870103 | 0.6871587698 | Pass | Pass |
| 22 | T N2 APARTMENT | RunPeriod: RUNPERIOD 1 | 1.4767518372E-002 | 3.7969541025E-002 | Pass | Pass | 0.2539084739 | 1.1171777872 | Pass | Pass |
| 23 | T S1 APARTMENT | RunPeriod: RUNPERIOD 1 | 4.1040802460E-002 | 6.8279091789E-002 | Pass | Pass | 0.1979339914 | 0.8976807135 | Pass | Pass |
| 24 | T S2 APARTMENT | RunPeriod: RUNPERIOD 1 | 4.0983965330E-002 | 6.8534499650E-002 | Pass | Pass | 0.1563060121 | 0.4548286519 | Pass | Pass |
| 25 | T CORRIDOR | RunPeriod: RUNPERIOD 1 | 3.4907970149E-002 | 2.4799728947E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
| 26 | G CORRIDOR | RunPeriod: RUNPERIOD 1 | 0.1577865335 | 0.4856565227 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
| 27 | M CORRIDOR | RunPeriod: RUNPERIOD 1 | 1.0222341013E-002 | 7.0683265066E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 09:14:34
Heat Emission by Components| Envelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
| Heat Emissions [GJ] | 1581.59 | 86.82 | 0.00 | 8.79 | 905.18 | 2582.39 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 09:14:34
SizingPeriod:DesignDay| Maximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
| EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | -5.20 | 0.00 | -5.20 | Wetbulb [C] | 2.20 | 20.00 |
| EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 38.10 | 13.00 | 18.10 | Wetbulb [C] | 3.90 | 280.00 |
| Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
| Jan | 3.00 | 6 | |||
| Feb | 3.00 | 4 | |||
| Mar | 0.00 | 0 | |||
| Apr | 0.00 | 0 | |||
| May | 0.00 | 0 | |||
| Jun | 18.00 | 7 | |||
| Jul | 27.00 | 16 | |||
| Aug | 41.00 | 15 | |||
| Sep | 0.00 | 0 | |||
| Oct | 23.00 | 18 | |||
| Nov | 0.00 | 0 | |||
| Dec | 7.00 | 7 |
| Value | |
| None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 09:14:34
Opaque Exterior| Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
| G SWALL SWA | RES_EXT_WALL_GRD | 0.30 | 0.676 | 0.752 | 35.30 | 28.24 | 180.00 | 90.00 | S |
| G WWALL SWA | RES_EXT_WALL_GRD | 0.30 | 0.676 | 0.752 | 23.22 | 18.58 | 270.00 | 90.00 | W |
| G GFLOOR SWA | GGFLOORSWA_FFACTOR | 1.00 | 0.274 | 0.287 | 88.25 | 88.25 | 90.00 | 180.00 | |
| G NWALL NWA | RES_EXT_WALL_GRD | 0.30 | 0.676 | 0.752 | 35.30 | 28.24 | 0.00 | 90.00 | N |
| G WWALL NWA | RES_EXT_WALL_GRD | 0.30 | 0.676 | 0.752 | 23.22 | 18.58 | 270.00 | 90.00 | W |
| G GFLOOR NWA | GGFLOORNWA_FFACTOR | 1.00 | 0.274 | 0.287 | 88.25 | 88.25 | 90.00 | 180.00 | |
| G SWALL SEA | NONRES_EXT_WALL_GRD | 0.30 | 0.676 | 0.752 | 35.30 | 28.24 | 180.00 | 90.00 | S |
| G EWALL SEA | NONRES_EXT_WALL_GRD | 0.30 | 0.676 | 0.752 | 23.22 | 18.58 | 90.00 | 90.00 | E |
| G GFLOOR SEA | GGFLOORSEA_FFACTOR | 1.00 | 0.274 | 0.287 | 88.25 | 88.25 | 90.00 | 180.00 | |
| G NWALL NEA | RES_EXT_WALL_GRD | 0.30 | 0.676 | 0.752 | 35.30 | 28.24 | 0.00 | 90.00 | N |
| G EWALL NEA | RES_EXT_WALL_GRD | 0.30 | 0.676 | 0.752 | 23.22 | 18.58 | 90.00 | 90.00 | E |
| G GFLOOR NEA | GGFLOORNEA_FFACTOR | 1.00 | 0.274 | 0.287 | 88.25 | 88.25 | 90.00 | 180.00 | |
| G NWALL N1A | RES_EXT_WALL_GRD | 0.30 | 0.676 | 0.752 | 35.30 | 28.24 | 0.00 | 90.00 | N |
| G GFLOOR N1A | GGFLOORN1A_FFACTOR | 1.00 | 0.166 | 0.170 | 88.25 | 88.25 | 90.00 | 180.00 | |
| G NWALL N2A | RES_EXT_WALL_GRD | 0.30 | 0.676 | 0.752 | 35.30 | 28.24 | 0.00 | 90.00 | N |
| G GFLOOR N2A | GGFLOORN2A_FFACTOR | 1.00 | 0.166 | 0.170 | 88.25 | 88.25 | 90.00 | 180.00 | |
| G SWALL S1A | RES_EXT_WALL_GRD | 0.30 | 0.676 | 0.752 | 35.30 | 28.24 | 180.00 | 90.00 | S |
| G GFLOOR S1A | GGFLOORS1A_FFACTOR | 1.00 | 0.166 | 0.170 | 88.25 | 88.25 | 90.00 | 180.00 | |
| G SWALL S2A | RES_EXT_WALL_GRD | 0.30 | 0.676 | 0.752 | 35.30 | 28.24 | 180.00 | 90.00 | S |
| G GFLOOR S2A | GGFLOORS2A_FFACTOR | 1.00 | 0.166 | 0.170 | 88.25 | 88.25 | 90.00 | 180.00 | |
| M WWALL SWA | RES_EXT_WALL_MID | 0.30 | 0.683 | 0.761 | 46.45 | 37.16 | 270.00 | 90.00 | W |
| M SWALL SWA | RES_EXT_WALL_MID | 0.30 | 0.683 | 0.761 | 70.60 | 56.48 | 180.00 | 90.00 | S |
| M NWALL NWA | RES_EXT_WALL_MID | 0.30 | 0.683 | 0.761 | 70.60 | 56.48 | 0.00 | 90.00 | N |
| M WWALL NWA | RES_EXT_WALL_MID | 0.30 | 0.683 | 0.761 | 46.45 | 37.16 | 270.00 | 90.00 | W |
| M EWALL SEA | RES_EXT_WALL_MID | 0.30 | 0.683 | 0.761 | 46.45 | 37.16 | 90.00 | 90.00 | E |
| M SWALL SEA | RES_EXT_WALL_MID | 0.30 | 0.683 | 0.761 | 70.60 | 56.48 | 180.00 | 90.00 | S |
| M NWALL NEA | RES_EXT_WALL_MID | 0.30 | 0.683 | 0.761 | 70.60 | 56.48 | 0.00 | 90.00 | N |
| M EWALL NEA | RES_EXT_WALL_MID | 0.30 | 0.683 | 0.761 | 46.45 | 37.16 | 90.00 | 90.00 | E |
| M NWALL N1A | RES_EXT_WALL_MID | 0.30 | 0.683 | 0.761 | 70.60 | 56.48 | 0.00 | 90.00 | N |
| M NWALL N2A | RES_EXT_WALL_MID | 0.30 | 0.683 | 0.761 | 70.60 | 56.48 | 0.00 | 90.00 | N |
| M SWALL S1A | RES_EXT_WALL_MID | 0.30 | 0.683 | 0.761 | 70.60 | 56.48 | 180.00 | 90.00 | S |
| M SWALL S2A | RES_EXT_WALL_MID | 0.30 | 0.683 | 0.761 | 70.60 | 56.48 | 180.00 | 90.00 | S |
| T WWALL SWA | RES_EXT_WALL_TOP | 0.30 | 0.943 | 1.098 | 23.22 | 18.58 | 270.00 | 90.00 | W |
| T SWALL SWA | RES_EXT_WALL_TOP | 0.30 | 0.943 | 1.098 | 35.30 | 28.24 | 180.00 | 90.00 | S |
| T ROOF SWA | RES_ROOF | 0.55 | 0.273 | 0.283 | 88.25 | 88.25 | 180.00 | 0.00 | |
| T NWALL NWA | RES_EXT_WALL_TOP | 0.30 | 0.943 | 1.098 | 35.30 | 28.24 | 0.00 | 90.00 | N |
| T WWALL NWA | RES_EXT_WALL_TOP | 0.30 | 0.943 | 1.098 | 23.22 | 18.58 | 270.00 | 90.00 | W |
| T ROOF NWA | RES_ROOF | 0.55 | 0.273 | 0.283 | 88.25 | 88.25 | 180.00 | 0.00 | |
| T EWALL SEA | RES_EXT_WALL_TOP | 0.30 | 0.943 | 1.098 | 23.22 | 18.58 | 90.00 | 90.00 | E |
| T SWALL SEA | RES_EXT_WALL_TOP | 0.30 | 0.943 | 1.098 | 35.30 | 28.24 | 180.00 | 90.00 | S |
| T ROOF SEA | RES_ROOF | 0.55 | 0.273 | 0.283 | 88.25 | 88.25 | 180.00 | 0.00 | |
| T NWALL NEA | RES_EXT_WALL_TOP | 0.30 | 0.943 | 1.098 | 35.30 | 28.24 | 0.00 | 90.00 | N |
| T EWALL NEA | RES_EXT_WALL_TOP | 0.30 | 0.943 | 1.098 | 23.22 | 18.58 | 90.00 | 90.00 | E |
| T ROOF NEA | RES_ROOF | 0.55 | 0.273 | 0.283 | 88.25 | 88.25 | 180.00 | 0.00 | |
| T NWALL N1A | RES_EXT_WALL_TOP | 0.30 | 0.943 | 1.098 | 35.30 | 28.24 | 0.00 | 90.00 | N |
| T ROOF N1A | RES_ROOF | 0.55 | 0.273 | 0.283 | 88.25 | 88.25 | 180.00 | 0.00 | |
| T NWALL N2A | RES_EXT_WALL_TOP | 0.30 | 0.943 | 1.098 | 35.30 | 28.24 | 0.00 | 90.00 | N |
| T ROOF N2A | RES_ROOF | 0.55 | 0.273 | 0.283 | 88.25 | 88.25 | 180.00 | 0.00 | |
| T SWALL S1A | RES_EXT_WALL_TOP | 0.30 | 0.943 | 1.098 | 35.30 | 28.24 | 180.00 | 90.00 | S |
| T ROOF S1A | RES_ROOF | 0.55 | 0.273 | 0.283 | 88.25 | 88.25 | 180.00 | 0.00 | |
| T SWALL S2A | RES_EXT_WALL_TOP | 0.30 | 0.943 | 1.098 | 35.30 | 28.24 | 180.00 | 90.00 | S |
| T ROOF S2A | RES_ROOF | 0.55 | 0.273 | 0.283 | 88.25 | 88.25 | 180.00 | 0.00 | |
| T WWALL C | NONRES_EXT_WALL_TOP | 0.30 | 0.943 | 1.098 | 5.11 | 5.11 | 270.00 | 90.00 | W |
| T EWALL C | NONRES_EXT_WALL_TOP | 0.30 | 0.943 | 1.098 | 5.11 | 3.99 | 90.00 | 90.00 | E |
| T ROOF C | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 77.66 | 77.66 | 180.00 | 0.00 | |
| G WWALL C | NONRES_EXT_WALL_GRD | 0.30 | 0.676 | 0.752 | 5.11 | 5.11 | 270.00 | 90.00 | W |
| G EWALL C | NONRES_EXT_WALL_GRD | 0.30 | 0.676 | 0.752 | 5.11 | 1.79 | 90.00 | 90.00 | E |
| G FLOOR C | GFLOORC_FFACTOR | 1.00 | 0.055 | 0.055 | 77.66 | 77.66 | 90.00 | 180.00 | |
| M WWALL C | NONRES_EXT_WALL_MID | 0.30 | 0.683 | 0.761 | 10.22 | 10.22 | 270.00 | 90.00 | W |
| M EWALL C | NONRES_EXT_WALL_MID | 0.30 | 0.683 | 0.761 | 10.22 | 7.99 | 90.00 | 90.00 | E |
| Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
| G NIWALL SWA | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 0.00 | 90.00 | N |
| G EIWALL SWA | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 90.00 | 90.00 | E |
| G CEILIN SWA | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 88.25 | 88.25 | 180.00 | 0.00 | |
| G SIWALL NWA | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 180.00 | 90.00 | S |
| G EIWALL NWA | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 90.00 | 90.00 | E |
| G CEILIN NWA | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 88.25 | 88.25 | 180.00 | 0.00 | |
| G NIWALL SEA | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 0.00 | 90.00 | N |
| iz-G EIWALL S2A | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 270.00 | 90.00 | W |
| G CEILIN SEA | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 88.25 | 88.25 | 180.00 | 0.00 | |
| G SIWALL NEA | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 180.00 | 90.00 | S |
| iz-G EIWALL N2A | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 270.00 | 90.00 | W |
| G CEILIN NEA | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 88.25 | 88.25 | 180.00 | 0.00 | |
| G SIWALL N1A | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 180.00 | 90.00 | S |
| G EIWALL N1A | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 90.00 | 90.00 | E |
| iz-G EIWALL NWA | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 270.00 | 90.00 | W |
| G CEILIN N1A | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 88.25 | 88.25 | 180.00 | 0.00 | |
| G SIWALL N2A | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 180.00 | 90.00 | S |
| G EIWALL N2A | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 90.00 | 90.00 | E |
| iz-G EIWALL N1A | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 270.00 | 90.00 | W |
| G CEILIN N2A | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 88.25 | 88.25 | 180.00 | 0.00 | |
| G NIWALL S1A | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 0.00 | 90.00 | N |
| G EIWALL S1A | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 90.00 | 90.00 | E |
| iz-G EIWALL SWA | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 270.00 | 90.00 | W |
| G CEILIN S1A | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 88.25 | 88.25 | 180.00 | 0.00 | |
| G NIWALL S2A | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 0.00 | 90.00 | N |
| G EIWALL S2A | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 90.00 | 90.00 | E |
| iz-G EIWALL S1A | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 270.00 | 90.00 | W |
| G CEILIN S2A | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 88.25 | 88.25 | 180.00 | 0.00 | |
| M NIWALL SWA | INT_WALL | 0.30 | 2.511 | 6.299 | 70.60 | 70.60 | 0.00 | 90.00 | N |
| M EIWALL SWA | INT_WALL | 0.30 | 2.511 | 6.299 | 46.45 | 46.45 | 90.00 | 90.00 | E |
| M GFLOOR SWA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 176.50 | 176.50 | 90.00 | 180.00 | |
| M CEILIN SWA | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 176.50 | 176.50 | 180.00 | 0.00 | |
| M SIWALL NWA | INT_WALL | 0.30 | 2.511 | 6.299 | 70.60 | 70.60 | 180.00 | 90.00 | S |
| M EIWALL NWA | INT_WALL | 0.30 | 2.511 | 6.299 | 46.45 | 46.45 | 90.00 | 90.00 | E |
| M GFLOOR NWA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 176.50 | 176.50 | 90.00 | 180.00 | |
| M CEILIN NWA | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 176.50 | 176.50 | 180.00 | 0.00 | |
| M NIWALL SEA | INT_WALL | 0.30 | 2.511 | 6.299 | 70.60 | 70.60 | 0.00 | 90.00 | N |
| iz-M EIWALL S2A | INT_WALL | 0.30 | 2.511 | 6.299 | 46.45 | 46.45 | 270.00 | 90.00 | W |
| M GFLOOR SEA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 176.50 | 176.50 | 90.00 | 180.00 | |
| M CEILIN SEA | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 176.50 | 176.50 | 180.00 | 0.00 | |
| M SIWALL NEA | INT_WALL | 0.30 | 2.511 | 6.299 | 70.60 | 70.60 | 180.00 | 90.00 | S |
| iz-M EIWALL N2A | INT_WALL | 0.30 | 2.511 | 6.299 | 46.45 | 46.45 | 270.00 | 90.00 | W |
| M GFLOOR NEA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 176.50 | 176.50 | 90.00 | 180.00 | |
| M CEILIN NEA | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 176.50 | 176.50 | 180.00 | 0.00 | |
| M SIWALL N1A | INT_WALL | 0.30 | 2.511 | 6.299 | 70.60 | 70.60 | 180.00 | 90.00 | S |
| M EIWALL N1A | INT_WALL | 0.30 | 2.511 | 6.299 | 46.45 | 46.45 | 90.00 | 90.00 | E |
| iz-M EIWALL NWA | INT_WALL | 0.30 | 2.511 | 6.299 | 46.45 | 46.45 | 270.00 | 90.00 | W |
| M GFLOOR N1A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 176.50 | 176.50 | 90.00 | 180.00 | |
| M CEILIN N1A | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 176.50 | 176.50 | 180.00 | 0.00 | |
| M SIWALL N2A | INT_WALL | 0.30 | 2.511 | 6.299 | 70.60 | 70.60 | 180.00 | 90.00 | S |
| M EIWALL N2A | INT_WALL | 0.30 | 2.511 | 6.299 | 46.45 | 46.45 | 90.00 | 90.00 | E |
| iz-M EIWALL N1A | INT_WALL | 0.30 | 2.511 | 6.299 | 46.45 | 46.45 | 270.00 | 90.00 | W |
| M GFLOOR N2A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 176.50 | 176.50 | 90.00 | 180.00 | |
| M CEILIN N2A | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 176.50 | 176.50 | 180.00 | 0.00 | |
| M NIWALL S1A | INT_WALL | 0.30 | 2.511 | 6.299 | 70.60 | 70.60 | 0.00 | 90.00 | N |
| M EIWALL S1A | INT_WALL | 0.30 | 2.511 | 6.299 | 46.45 | 46.45 | 90.00 | 90.00 | E |
| iz-M EIWALL SWA | INT_WALL | 0.30 | 2.511 | 6.299 | 46.45 | 46.45 | 270.00 | 90.00 | W |
| M GFLOOR S1A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 176.50 | 176.50 | 90.00 | 180.00 | |
| M CEILIN S1A | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 176.50 | 176.50 | 180.00 | 0.00 | |
| M NIWALL S2A | INT_WALL | 0.30 | 2.511 | 6.299 | 70.60 | 70.60 | 0.00 | 90.00 | N |
| M EIWALL S2A | INT_WALL | 0.30 | 2.511 | 6.299 | 46.45 | 46.45 | 90.00 | 90.00 | E |
| iz-M EIWALL S1A | INT_WALL | 0.30 | 2.511 | 6.299 | 46.45 | 46.45 | 270.00 | 90.00 | W |
| M GFLOOR S2A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 176.50 | 176.50 | 90.00 | 180.00 | |
| M CEILIN S2A | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 176.50 | 176.50 | 180.00 | 0.00 | |
| T NIWALL SWA | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 0.00 | 90.00 | N |
| T EIWALL SWA | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 90.00 | 90.00 | E |
| T GFLOOR SWA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 88.25 | 88.25 | 90.00 | 180.00 | |
| T SIWALL NWA | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 180.00 | 90.00 | S |
| T EIWALL NWA | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 90.00 | 90.00 | E |
| T GFLOOR NWA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 88.25 | 88.25 | 90.00 | 180.00 | |
| T NIWALL SEA | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 0.00 | 90.00 | N |
| iz-T EIWALL S2A | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 270.00 | 90.00 | W |
| T GFLOOR SEA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 88.25 | 88.25 | 90.00 | 180.00 | |
| T SIWALL NEA | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 180.00 | 90.00 | S |
| iz-T EIWALL N2A | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 270.00 | 90.00 | W |
| T GFLOOR NEA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 88.25 | 88.25 | 90.00 | 180.00 | |
| T SIWALL N1A | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 180.00 | 90.00 | S |
| T EIWALL N1A | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 90.00 | 90.00 | E |
| iz-T EIWALL NWA | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 270.00 | 90.00 | W |
| T GFLOOR N1A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 88.25 | 88.25 | 90.00 | 180.00 | |
| T SIWALL N2A | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 180.00 | 90.00 | S |
| T EIWALL N2A | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 90.00 | 90.00 | E |
| iz-T EIWALL N1A | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 270.00 | 90.00 | W |
| T GFLOOR N2A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 88.25 | 88.25 | 90.00 | 180.00 | |
| T NIWALL S1A | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 0.00 | 90.00 | N |
| T EIWALL S1A | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 90.00 | 90.00 | E |
| iz-T EIWALL SWA | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 270.00 | 90.00 | W |
| T GFLOOR S1A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 88.25 | 88.25 | 90.00 | 180.00 | |
| T NIWALL S2A | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 0.00 | 90.00 | N |
| T EIWALL S2A | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 90.00 | 90.00 | E |
| iz-T EIWALL S1A | INT_WALL | 0.30 | 2.511 | 6.299 | 23.22 | 23.22 | 270.00 | 90.00 | W |
| T GFLOOR S2A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 88.25 | 88.25 | 90.00 | 180.00 | |
| iz-T NIWALL SWA | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 180.00 | 90.00 | S |
| iz-T NIWALL S1A | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 180.00 | 90.00 | S |
| iz-T NIWALL S2A | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 180.00 | 90.00 | S |
| iz-T NIWALL SEA | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 180.00 | 90.00 | S |
| iz-T SIWALL NWA | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 0.00 | 90.00 | N |
| iz-T SIWALL N1A | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 0.00 | 90.00 | N |
| iz-T SIWALL N2A | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 0.00 | 90.00 | N |
| iz-T SIWALL NEA | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 0.00 | 90.00 | N |
| T FLOOR C | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 77.66 | 77.66 | 90.00 | 180.00 | |
| iz-G NIWALL SWA | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 180.00 | 90.00 | S |
| iz-G NIWALL S1A | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 180.00 | 90.00 | S |
| iz-G NIWALL S2A | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 180.00 | 90.00 | S |
| iz-G NIWALL SEA | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 180.00 | 90.00 | S |
| iz-G SIWALL NWA | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 0.00 | 90.00 | N |
| iz-G SIWALL N1A | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 0.00 | 90.00 | N |
| iz-G SIWALL N2A | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 0.00 | 90.00 | N |
| iz-G SIWALL NEA | INT_WALL | 0.30 | 2.511 | 6.299 | 35.30 | 35.30 | 0.00 | 90.00 | N |
| G CEILING C | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 77.66 | 77.66 | 180.00 | 0.00 | |
| iz-M NIWALL SWA | INT_WALL | 0.30 | 2.511 | 6.299 | 70.60 | 70.60 | 180.00 | 90.00 | S |
| iz-M NIWALL S1A | INT_WALL | 0.30 | 2.511 | 6.299 | 70.60 | 70.60 | 180.00 | 90.00 | S |
| iz-M NIWALL S2A | INT_WALL | 0.30 | 2.511 | 6.299 | 70.60 | 70.60 | 180.00 | 90.00 | S |
| iz-M NIWALL SEA | INT_WALL | 0.30 | 2.511 | 6.299 | 70.60 | 70.60 | 180.00 | 90.00 | S |
| iz-M SIWALL NWA | INT_WALL | 0.30 | 2.511 | 6.299 | 70.60 | 70.60 | 0.00 | 90.00 | N |
| iz-M SIWALL N1A | INT_WALL | 0.30 | 2.511 | 6.299 | 70.60 | 70.60 | 0.00 | 90.00 | N |
| iz-M SIWALL N2A | INT_WALL | 0.30 | 2.511 | 6.299 | 70.60 | 70.60 | 0.00 | 90.00 | N |
| iz-M SIWALL NEA | INT_WALL | 0.30 | 2.511 | 6.299 | 70.60 | 70.60 | 0.00 | 90.00 | N |
| M FLOOR C | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 155.32 | 155.32 | 90.00 | 180.00 | |
| M CEILING C | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 155.32 | 155.32 | 180.00 | 0.00 | |
| G INTERNALMASS SWA | INTERIORFURNISHINGS | 0.30 | 0.800 | 88.25 | 0.00 | 90.00 | N | ||
| G INTERNALMASS NWA | INTERIORFURNISHINGS | 0.30 | 0.800 | 88.25 | 0.00 | 90.00 | N | ||
| G INTERNALMASS SEA | INTERIORFURNISHINGS | 0.30 | 0.800 | 88.25 | 0.00 | 90.00 | N | ||
| G INTERNALMASS NEA | INTERIORFURNISHINGS | 0.30 | 0.800 | 88.25 | 0.00 | 90.00 | N | ||
| G INTERNALMASS N1A | INTERIORFURNISHINGS | 0.30 | 0.800 | 88.25 | 0.00 | 90.00 | N | ||
| G INTERNALMASS N2A | INTERIORFURNISHINGS | 0.30 | 0.800 | 88.25 | 0.00 | 90.00 | N | ||
| G INTERNALMASS S1A | INTERIORFURNISHINGS | 0.30 | 0.800 | 88.25 | 0.00 | 90.00 | N | ||
| G INTERNALMASS S2A | INTERIORFURNISHINGS | 0.30 | 0.800 | 88.25 | 0.00 | 90.00 | N | ||
| M INTERNALMASS SWA | INTERIORFURNISHINGS | 0.30 | 0.800 | 353.00 | 0.00 | 90.00 | N | ||
| M INTERNALMASS NWA | INTERIORFURNISHINGS | 0.30 | 0.800 | 353.00 | 0.00 | 90.00 | N | ||
| M INTERNALMASS SEA | INTERIORFURNISHINGS | 0.30 | 0.800 | 353.00 | 0.00 | 90.00 | N | ||
| M INTERNALMASS NEA | INTERIORFURNISHINGS | 0.30 | 0.800 | 353.00 | 0.00 | 90.00 | N | ||
| M INTERNALMASS N1A | INTERIORFURNISHINGS | 0.30 | 0.800 | 353.00 | 0.00 | 90.00 | N | ||
| M INTERNALMASS N2A | INTERIORFURNISHINGS | 0.30 | 0.800 | 353.00 | 0.00 | 90.00 | N | ||
| M INTERNALMASS S1A | INTERIORFURNISHINGS | 0.30 | 0.800 | 353.00 | 0.00 | 90.00 | N | ||
| M INTERNALMASS S2A | INTERIORFURNISHINGS | 0.30 | 0.800 | 353.00 | 0.00 | 90.00 | N | ||
| T INTERNALMASS SWA | INTERIORFURNISHINGS | 0.30 | 0.800 | 88.25 | 0.00 | 90.00 | N | ||
| T INTERNALMASS NWA | INTERIORFURNISHINGS | 0.30 | 0.800 | 88.25 | 0.00 | 90.00 | N | ||
| T INTERNALMASS SEA | INTERIORFURNISHINGS | 0.30 | 0.800 | 88.25 | 0.00 | 90.00 | N | ||
| T INTERNALMASS NEA | INTERIORFURNISHINGS | 0.30 | 0.800 | 88.25 | 0.00 | 90.00 | N | ||
| T INTERNALMASS N1A | INTERIORFURNISHINGS | 0.30 | 0.800 | 88.25 | 0.00 | 90.00 | N | ||
| T INTERNALMASS N2A | INTERIORFURNISHINGS | 0.30 | 0.800 | 88.25 | 0.00 | 90.00 | N | ||
| T INTERNALMASS S1A | INTERIORFURNISHINGS | 0.30 | 0.800 | 88.25 | 0.00 | 90.00 | N | ||
| T INTERNALMASS S2A | INTERIORFURNISHINGS | 0.30 | 0.800 | 88.25 | 0.00 | 90.00 | N |
| Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
| GWINDOW1 S SWA | RESWINDOW_U_0.4945_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.811 | 0.251 | 0.251 | No | G SWALL SWA | 180.00 | 90.00 | S | |||||||
| GWINDOW1 W SWA | RESWINDOW_U_0.4945_SHGC_0.25 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 2.811 | 0.251 | 0.251 | No | G WWALL SWA | 270.00 | 90.00 | W | |||||||
| GWINDOW1 N NWA | RESWINDOW_U_0.4945_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.811 | 0.251 | 0.251 | No | G NWALL NWA | 0.00 | 90.00 | N | |||||||
| GWINDOW1 W NWA | RESWINDOW_U_0.4945_SHGC_0.25 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 2.811 | 0.251 | 0.251 | No | G WWALL NWA | 270.00 | 90.00 | W | |||||||
| GWINDOW1 S SEA | NONRESWINDOW_U_0.4945_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.811 | 0.251 | 0.251 | No | G SWALL SEA | 180.00 | 90.00 | S | |||||||
| GWINDOW1 E SEA | NONRESWINDOW_U_0.4945_SHGC_0.25 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 2.811 | 0.251 | 0.251 | No | G EWALL SEA | 90.00 | 90.00 | E | |||||||
| GWINDOW1 N NEA | RESWINDOW_U_0.4945_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.811 | 0.251 | 0.251 | No | G NWALL NEA | 0.00 | 90.00 | N | |||||||
| GWINDOW1 E NEA | RESWINDOW_U_0.4945_SHGC_0.25 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 2.811 | 0.251 | 0.251 | No | G EWALL NEA | 90.00 | 90.00 | E | |||||||
| GWINDOW1 N N1A | RESWINDOW_U_0.4945_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.811 | 0.251 | 0.251 | No | G NWALL N1A | 0.00 | 90.00 | N | |||||||
| GWINDOW1 N N2A | RESWINDOW_U_0.4945_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.811 | 0.251 | 0.251 | No | G NWALL N2A | 0.00 | 90.00 | N | |||||||
| GWINDOW1 S S1A | RESWINDOW_U_0.4945_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.811 | 0.251 | 0.251 | No | G SWALL S1A | 180.00 | 90.00 | S | |||||||
| GWINDOW1 S S2A | RESWINDOW_U_0.4945_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.811 | 0.251 | 0.251 | No | G SWALL S2A | 180.00 | 90.00 | S | |||||||
| MWINDOW1 W SWA | RESWINDOW_U_0.4945_SHGC_0.25 | 4.65 | 0.00 | 0.00 | 4.65 | 9.29 | 2.811 | 0.251 | 0.251 | No | M WWALL SWA | 270.00 | 90.00 | W | |||||||
| MWINDOW1 S SWA | RESWINDOW_U_0.4945_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 2.811 | 0.251 | 0.251 | No | M SWALL SWA | 180.00 | 90.00 | S | |||||||
| MWINDOW1 N NWA | RESWINDOW_U_0.4945_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 2.811 | 0.251 | 0.251 | No | M NWALL NWA | 0.00 | 90.00 | N | |||||||
| MWINDOW1 W NWA | RESWINDOW_U_0.4945_SHGC_0.25 | 4.65 | 0.00 | 0.00 | 4.65 | 9.29 | 2.811 | 0.251 | 0.251 | No | M WWALL NWA | 270.00 | 90.00 | W | |||||||
| MWINDOW1 E SEA | RESWINDOW_U_0.4945_SHGC_0.25 | 4.65 | 0.00 | 0.00 | 4.65 | 9.29 | 2.811 | 0.251 | 0.251 | No | M EWALL SEA | 90.00 | 90.00 | E | |||||||
| MWINDOW1 S SEA | RESWINDOW_U_0.4945_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 2.811 | 0.251 | 0.251 | No | M SWALL SEA | 180.00 | 90.00 | S | |||||||
| MWINDOW1 N NEA | RESWINDOW_U_0.4945_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 2.811 | 0.251 | 0.251 | No | M NWALL NEA | 0.00 | 90.00 | N | |||||||
| MWINDOW1 E NEA | RESWINDOW_U_0.4945_SHGC_0.25 | 4.65 | 0.00 | 0.00 | 4.65 | 9.29 | 2.811 | 0.251 | 0.251 | No | M EWALL NEA | 90.00 | 90.00 | E | |||||||
| MWINDOW1 N N1A | RESWINDOW_U_0.4945_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 2.811 | 0.251 | 0.251 | No | M NWALL N1A | 0.00 | 90.00 | N | |||||||
| MWINDOW1 N N2A | RESWINDOW_U_0.4945_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 2.811 | 0.251 | 0.251 | No | M NWALL N2A | 0.00 | 90.00 | N | |||||||
| MWINDOW1 S S1A | RESWINDOW_U_0.4945_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 2.811 | 0.251 | 0.251 | No | M SWALL S1A | 180.00 | 90.00 | S | |||||||
| MWINDOW1 S S2A | RESWINDOW_U_0.4945_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 2.811 | 0.251 | 0.251 | No | M SWALL S2A | 180.00 | 90.00 | S | |||||||
| TWINDOW1 W SWA | RESWINDOW_U_0.4945_SHGC_0.25 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 2.811 | 0.251 | 0.251 | No | T WWALL SWA | 270.00 | 90.00 | W | |||||||
| TWINDOW1 S SWA | RESWINDOW_U_0.4945_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.811 | 0.251 | 0.251 | No | T SWALL SWA | 180.00 | 90.00 | S | |||||||
| TWINDOW1 N NWA | RESWINDOW_U_0.4945_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.811 | 0.251 | 0.251 | No | T NWALL NWA | 0.00 | 90.00 | N | |||||||
| TWINDOW1 W NWA | RESWINDOW_U_0.4945_SHGC_0.25 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 2.811 | 0.251 | 0.251 | No | T WWALL NWA | 270.00 | 90.00 | W | |||||||
| TWINDOW1 E SEA | RESWINDOW_U_0.4945_SHGC_0.25 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 2.811 | 0.251 | 0.251 | No | T EWALL SEA | 90.00 | 90.00 | E | |||||||
| TWINDOW1 S SEA | RESWINDOW_U_0.4945_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.811 | 0.251 | 0.251 | No | T SWALL SEA | 180.00 | 90.00 | S | |||||||
| TWINDOW1 N NEA | RESWINDOW_U_0.4945_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.811 | 0.251 | 0.251 | No | T NWALL NEA | 0.00 | 90.00 | N | |||||||
| TWINDOW1 E NEA | RESWINDOW_U_0.4945_SHGC_0.25 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 2.811 | 0.251 | 0.251 | No | T EWALL NEA | 90.00 | 90.00 | E | |||||||
| TWINDOW1 N N1A | RESWINDOW_U_0.4945_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.811 | 0.251 | 0.251 | No | T NWALL N1A | 0.00 | 90.00 | N | |||||||
| TWINDOW1 N N2A | RESWINDOW_U_0.4945_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.811 | 0.251 | 0.251 | No | T NWALL N2A | 0.00 | 90.00 | N | |||||||
| TWINDOW1 S S1A | RESWINDOW_U_0.4945_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.811 | 0.251 | 0.251 | No | T SWALL S1A | 180.00 | 90.00 | S | |||||||
| TWINDOW1 S S2A | RESWINDOW_U_0.4945_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.811 | 0.251 | 0.251 | No | T SWALL S2A | 180.00 | 90.00 | S | |||||||
| TWINDOW14 | NONRESWINDOW_U_0.4945_SHGC_0.25 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.811 | 0.251 | 0.251 | No | T EWALL C | 90.00 | 90.00 | E | |||||||
| ENTRANCE DOOR | NONRESWINDOW_U_0.4945_SHGC_0.25 | 3.32 | 0.00 | 0.00 | 3.32 | 3.32 | 2.811 | 0.251 | 0.251 | No | G EWALL C | 90.00 | 90.00 | E | |||||||
| MWINDOW14 | NONRESWINDOW_U_0.4945_SHGC_0.25 | 1.11 | 0.00 | 0.00 | 1.11 | 2.23 | 2.811 | 0.251 | 0.251 | No | M EWALL C | 90.00 | 90.00 | E | |||||||
| Total or Average | 306.92 | 2.811 | 0.251 | 0.251 | |||||||||||||||||
| North Total or Average | 112.97 | 2.811 | 0.251 | 0.251 | |||||||||||||||||
| Non-North Total or Average | 193.95 | 2.811 | 0.251 | 0.251 |
| Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
| None |
| Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
| Total or Average | 0.00 | - | - | - |
| Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
| None |
| Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
| None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 09:14:34
Sunlit Fraction| March 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
| GWINDOW1 S SWA | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| GWINDOW1 W SWA | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
| GWINDOW1 N NWA | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| GWINDOW1 W NWA | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
| GWINDOW1 S SEA | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| GWINDOW1 E SEA | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
| GWINDOW1 N NEA | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| GWINDOW1 E NEA | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
| GWINDOW1 N N1A | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| GWINDOW1 N N2A | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| GWINDOW1 S S1A | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| GWINDOW1 S S2A | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| MWINDOW1 W SWA | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
| MWINDOW1 S SWA | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| MWINDOW1 N NWA | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| MWINDOW1 W NWA | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
| MWINDOW1 E SEA | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
| MWINDOW1 S SEA | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| MWINDOW1 N NEA | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| MWINDOW1 E NEA | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
| MWINDOW1 N N1A | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| MWINDOW1 N N2A | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| MWINDOW1 S S1A | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| MWINDOW1 S S2A | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| TWINDOW1 W SWA | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
| TWINDOW1 S SWA | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| TWINDOW1 N NWA | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| TWINDOW1 W NWA | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
| TWINDOW1 E SEA | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
| TWINDOW1 S SEA | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| TWINDOW1 N NEA | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| TWINDOW1 E NEA | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
| TWINDOW1 N N1A | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| TWINDOW1 N N2A | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| TWINDOW1 S S1A | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| TWINDOW1 S S2A | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| TWINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
| ENTRANCE DOOR | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
| MWINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
| Name | Type | Shaded Construction | Control | Glare Control | |
| None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 09:14:34
Interior Lighting| Zone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
| LIGHTING_HARDWIRED_GSW | G SW APARTMENT | G SW APARTMENT | GENERAL | 7.8684 | 88.25 | 694.38 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.32 |
| LIGHTING_HARDWIRED_GNW | G NW APARTMENT | G NW APARTMENT | GENERAL | 7.8684 | 88.25 | 694.38 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.32 |
| LIGHTING_HARDWIRED_OFFICE | OFFICE | OFFICE | GENERAL | 9.7532 | 88.25 | 860.71 | LightsWired | LTG_SCH_OFFICE | 46.69 | 168.00 | 45.77 | 0.0000 | Y | 7.40 |
| LIGHTING_HARDWIRED_GNE | G NE APARTMENT | G NE APARTMENT | GENERAL | 7.8684 | 88.25 | 694.38 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.32 |
| LIGHTING_HARDWIRED_GN1 | G N1 APARTMENT | G N1 APARTMENT | GENERAL | 7.8684 | 88.25 | 694.38 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.32 |
| LIGHTING_HARDWIRED_GN2 | G N2 APARTMENT | G N2 APARTMENT | GENERAL | 7.8684 | 88.25 | 694.38 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.32 |
| LIGHTING_HARDWIRED_GS1 | G S1 APARTMENT | G S1 APARTMENT | GENERAL | 7.8684 | 88.25 | 694.38 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.32 |
| LIGHTING_HARDWIRED_GS2 | G S2 APARTMENT | G S2 APARTMENT | GENERAL | 7.8684 | 88.25 | 694.38 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.32 |
| LIGHTING_HARDWIRED_MSW | M SW APARTMENT | M SW APARTMENT | GENERAL | 7.8684 | 176.50 | 1388.76 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 2.63 |
| LIGHTING_HARDWIRED_MNW | M NW APARTMENT | M NW APARTMENT | GENERAL | 7.8684 | 176.50 | 1388.76 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 2.63 |
| LIGHTING_HARDWIRED_MSE | M SE APARTMENT | M SE APARTMENT | GENERAL | 7.8684 | 176.50 | 1388.76 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 2.63 |
| LIGHTING_HARDWIRED_MNE | M NE APARTMENT | M NE APARTMENT | GENERAL | 7.8684 | 176.50 | 1388.76 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 2.63 |
| LIGHTING_HARDWIRED_MN1 | M N1 APARTMENT | M N1 APARTMENT | GENERAL | 7.8684 | 176.50 | 1388.76 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 2.63 |
| LIGHTING_HARDWIRED_MN2 | M N2 APARTMENT | M N2 APARTMENT | GENERAL | 7.8684 | 176.50 | 1388.76 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 2.63 |
| LIGHTING_HARDWIRED_MS1 | M S1 APARTMENT | M S1 APARTMENT | GENERAL | 7.8684 | 176.50 | 1388.76 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 2.63 |
| LIGHTING_HARDWIRED_MS2 | M S2 APARTMENT | M S2 APARTMENT | GENERAL | 7.8684 | 176.50 | 1388.76 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 2.63 |
| LIGHTING_HARDWIRED_TSW | T SW APARTMENT | T SW APARTMENT | GENERAL | 7.8684 | 88.25 | 694.38 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.32 |
| LIGHTING_HARDWIRED_TNW | T NW APARTMENT | T NW APARTMENT | GENERAL | 7.8684 | 88.25 | 694.38 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.32 |
| LIGHTING_HARDWIRED_TSE | T SE APARTMENT | T SE APARTMENT | GENERAL | 7.8684 | 88.25 | 694.38 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.32 |
| LIGHTING_HARDWIRED_TNE | T NE APARTMENT | T NE APARTMENT | GENERAL | 7.8684 | 88.25 | 694.38 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.32 |
| LIGHTING_HARDWIRED_TN1 | T N1 APARTMENT | T N1 APARTMENT | GENERAL | 7.8684 | 88.25 | 694.38 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.32 |
| LIGHTING_HARDWIRED_TN2 | T N2 APARTMENT | T N2 APARTMENT | GENERAL | 7.8684 | 88.25 | 694.38 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.32 |
| LIGHTING_HARDWIRED_TS1 | T S1 APARTMENT | T S1 APARTMENT | GENERAL | 7.8684 | 88.25 | 694.38 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.32 |
| LIGHTING_HARDWIRED_TS2 | T S2 APARTMENT | T S2 APARTMENT | GENERAL | 7.8684 | 88.25 | 694.38 | LightsWired | LTG_SCH_APARTMENT_HARDWIRED | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 1.32 |
| LIGHTING_HARDWIRED_GC | G CORRIDOR | G CORRIDOR | GENERAL | 4.7725 | 77.66 | 370.63 | LightsWired | LTG_SCH_CORRIDOR | 168.00 | 168.00 | 168.00 | 0.0000 | N | 11.69 |
| LIGHTING_HARDWIRED_MC | M CORRIDOR | M CORRIDOR | GENERAL | 4.7725 | 155.32 | 741.26 | LightsWired | LTG_SCH_CORRIDOR | 168.00 | 168.00 | 168.00 | 0.0000 | N | 23.38 |
| LIGHTING_HARDWIRED_TC | T CORRIDOR | T CORRIDOR | GENERAL | 4.7725 | 77.66 | 370.63 | LightsWired | LTG_SCH_CORRIDOR | 168.00 | 168.00 | 168.00 | 0.0000 | N | 11.69 |
| LIGHTING_PLUGIN_GSW | G SW APARTMENT | G SW APARTMENT | GENERAL | 0.8234 | 88.25 | 72.67 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.14 |
| LIGHTING_PLUGIN_GNW | G NW APARTMENT | G NW APARTMENT | GENERAL | 0.8234 | 88.25 | 72.67 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.14 |
| LIGHTING_PLUGIN_GNE | G NE APARTMENT | G NE APARTMENT | GENERAL | 0.8234 | 88.25 | 72.67 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.14 |
| LIGHTING_PLUGIN_GN1 | G N1 APARTMENT | G N1 APARTMENT | GENERAL | 0.8234 | 88.25 | 72.67 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.14 |
| LIGHTING_PLUGIN_GN2 | G N2 APARTMENT | G N2 APARTMENT | GENERAL | 0.8234 | 88.25 | 72.67 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.14 |
| LIGHTING_PLUGIN_GS1 | G S1 APARTMENT | G S1 APARTMENT | GENERAL | 0.8234 | 88.25 | 72.67 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.14 |
| LIGHTING_PLUGIN_GS2 | G S2 APARTMENT | G S2 APARTMENT | GENERAL | 0.8234 | 88.25 | 72.67 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.14 |
| LIGHTING_PLUGIN_MSW | M SW APARTMENT | M SW APARTMENT | GENERAL | 0.8234 | 176.50 | 145.34 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.28 |
| LIGHTING_PLUGIN_MNW | M NW APARTMENT | M NW APARTMENT | GENERAL | 0.8234 | 176.50 | 145.34 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.28 |
| LIGHTING_PLUGIN_MSE | M SE APARTMENT | M SE APARTMENT | GENERAL | 0.8234 | 176.50 | 145.34 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.28 |
| LIGHTING_PLUGIN_MNE | M NE APARTMENT | M NE APARTMENT | GENERAL | 0.8234 | 176.50 | 145.34 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.28 |
| LIGHTING_PLUGIN_MN1 | M N1 APARTMENT | M N1 APARTMENT | GENERAL | 0.8234 | 176.50 | 145.34 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.28 |
| LIGHTING_PLUGIN_MN2 | M N2 APARTMENT | M N2 APARTMENT | GENERAL | 0.8234 | 176.50 | 145.34 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.28 |
| LIGHTING_PLUGIN_MS1 | M S1 APARTMENT | M S1 APARTMENT | GENERAL | 0.8234 | 176.50 | 145.34 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.28 |
| LIGHTING_PLUGIN_MS2 | M S2 APARTMENT | M S2 APARTMENT | GENERAL | 0.8234 | 176.50 | 145.34 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.28 |
| LIGHTING_PLUGIN_TSW | T SW APARTMENT | T SW APARTMENT | GENERAL | 0.8234 | 88.25 | 72.67 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.14 |
| LIGHTING_PLUGIN_TNW | T NW APARTMENT | T NW APARTMENT | GENERAL | 0.8234 | 88.25 | 72.67 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.14 |
| LIGHTING_PLUGIN_TSE | T SE APARTMENT | T SE APARTMENT | GENERAL | 0.8234 | 88.25 | 72.67 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.14 |
| LIGHTING_PLUGIN_TNE | T NE APARTMENT | T NE APARTMENT | GENERAL | 0.8234 | 88.25 | 72.67 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.14 |
| LIGHTING_PLUGIN_TN1 | T N1 APARTMENT | T N1 APARTMENT | GENERAL | 0.8234 | 88.25 | 72.67 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.14 |
| LIGHTING_PLUGIN_TN2 | T N2 APARTMENT | T N2 APARTMENT | GENERAL | 0.8234 | 88.25 | 72.67 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.14 |
| LIGHTING_PLUGIN_TS1 | T S1 APARTMENT | T S1 APARTMENT | GENERAL | 0.8234 | 88.25 | 72.67 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.14 |
| LIGHTING_PLUGIN_TS2 | T S2 APARTMENT | T S2 APARTMENT | GENERAL | 0.8234 | 88.25 | 72.67 | LightsPlugIn | LTG_SCH_APARTMENT_PLUGIN | 10.10 | 168.00 | 10.10 | 0.0000 | Y | 0.14 |
| Interior Lighting Total | 4.4498 | 5870.34 | 26121.74 | 75.91 |
| Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
| None |
| Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
| FACADE LIGHTING | 3183.33 | AstronomicalClock | - | 83.77 | 83.77 | 50.06 | |
| Exterior Lighting Total | 3183.33 | 50.06 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 09:14:34
Central Plant| Type | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
| None |
| Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
| SPLIT GSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 6458.59 | 5171.10 | 1287.49 | 0.80 | 3.91 | |||
| SPLIT GNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 6345.03 | 5080.18 | 1264.85 | 0.80 | 3.91 | |||
| SPLIT OFFICE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7143.23 | 5719.26 | 1423.97 | 0.80 | 3.91 | |||
| SPLIT GNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 6010.82 | 4812.60 | 1198.23 | 0.80 | 3.91 | |||
| SPLIT GN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5414.96 | 4335.52 | 1079.44 | 0.80 | 3.91 | |||
| SPLIT GN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5408.73 | 4330.53 | 1078.20 | 0.80 | 3.91 | |||
| SPLIT GS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5550.57 | 4444.09 | 1106.48 | 0.80 | 3.91 | |||
| SPLIT GS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5595.34 | 4479.93 | 1115.40 | 0.80 | 3.91 | |||
| SPLIT MSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 15239.47 | 12201.56 | 3037.91 | 0.80 | 3.91 | |||
| SPLIT MNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 15024.43 | 12029.39 | 2995.04 | 0.80 | 3.91 | |||
| SPLIT MSE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 14359.20 | 11496.77 | 2862.43 | 0.80 | 3.91 | |||
| SPLIT MNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 14146.76 | 11326.68 | 2820.08 | 0.80 | 3.91 | |||
| SPLIT MN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 12568.06 | 10062.68 | 2505.38 | 0.80 | 3.91 | |||
| SPLIT MN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 12551.67 | 10049.56 | 2502.11 | 0.80 | 3.91 | |||
| SPLIT MS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 12818.06 | 10262.84 | 2555.21 | 0.80 | 3.91 | |||
| SPLIT MS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 12801.27 | 10249.40 | 2551.86 | 0.80 | 3.91 | |||
| SPLIT TSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 8560.37 | 6853.90 | 1706.46 | 0.80 | 3.91 | |||
| SPLIT TNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 8523.51 | 6824.40 | 1699.12 | 0.80 | 3.91 | |||
| SPLIT TSE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7881.53 | 6310.39 | 1571.14 | 0.80 | 3.91 | |||
| SPLIT TNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7843.91 | 6280.27 | 1563.64 | 0.80 | 3.91 | |||
| SPLIT TN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7158.02 | 5731.11 | 1426.91 | 0.80 | 3.91 | |||
| SPLIT TN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7134.74 | 5712.47 | 1422.27 | 0.80 | 3.91 | |||
| SPLIT TS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7204.37 | 5768.22 | 1436.15 | 0.80 | 3.91 | |||
| SPLIT TS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7181.18 | 5749.65 | 1431.53 | 0.80 | 3.91 |
| DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
| SPLIT GSW COOLING COIL | 6152.8 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 | |
| SPLIT GNW COOLING COIL | 6044.6 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 | |
| SPLIT OFFICE COOLING COIL | 6805.1 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 | |
| SPLIT GNE COOLING COIL | 5726.3 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 | |
| SPLIT GN1 COOLING COIL | 5158.6 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 | |
| SPLIT GN2 COOLING COIL | 5152.7 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 | |
| SPLIT GS1 COOLING COIL | 5287.8 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 | |
| SPLIT GS2 COOLING COIL | 5330.4 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 | |
| SPLIT MSW COOLING COIL | 14518.0 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 | |
| SPLIT MNW COOLING COIL | 14313.1 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 | |
| SPLIT MSE COOLING COIL | 13679.4 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 | |
| SPLIT MNE COOLING COIL | 13477.0 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 | |
| SPLIT MN1 COOLING COIL | 11973.1 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 | |
| SPLIT MN2 COOLING COIL | 11957.4 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 | |
| SPLIT MS1 COOLING COIL | 12211.2 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 | |
| SPLIT MS2 COOLING COIL | 12195.2 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 | |
| SPLIT TSW COOLING COIL | 8155.1 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 | |
| SPLIT TNW COOLING COIL | 8120.0 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 | |
| SPLIT TSE COOLING COIL | 7508.4 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 | |
| SPLIT TNE COOLING COIL | 7472.6 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 | |
| SPLIT TN1 COOLING COIL | 6819.1 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 | |
| SPLIT TN2 COOLING COIL | 6797.0 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 | |
| SPLIT TS1 COOLING COIL | 6863.3 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 | |
| SPLIT TS2 COOLING COIL | 6841.2 | 3.13 | 10.67 | 11.09 | 10.49 | 10.38 |
| DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
| SPLIT GSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT GNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT OFFICE COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT GNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT GN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT GN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT GS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT GS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT MSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT MNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT MSE COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT MNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT MN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT MN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT MS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT MS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT TSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT TNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT TSE COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT TNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT TN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT TN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT TS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SPLIT TS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed |
| DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
| None |
| Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
| SPLIT GSW HEATING COIL | Coil:Heating:Fuel | 8454.92 | 0.80 | |
| SPLIT GNW HEATING COIL | Coil:Heating:Fuel | 8318.79 | 0.80 | |
| SPLIT OFFICE HEATING COIL | Coil:Heating:Fuel | 9610.62 | 0.80 | |
| SPLIT GNE HEATING COIL | Coil:Heating:Fuel | 7918.36 | 0.80 | |
| SPLIT GN1 HEATING COIL | Coil:Heating:Fuel | 7204.35 | 0.80 | |
| SPLIT GN2 HEATING COIL | Coil:Heating:Fuel | 7196.88 | 0.80 | |
| SPLIT GS1 HEATING COIL | Coil:Heating:Fuel | 7366.89 | 0.80 | |
| SPLIT GS2 HEATING COIL | Coil:Heating:Fuel | 7420.52 | 0.80 | |
| SPLIT MSW HEATING COIL | Coil:Heating:Fuel | 19693.04 | 0.80 | |
| SPLIT MNW HEATING COIL | Coil:Heating:Fuel | 19435.08 | 0.80 | |
| SPLIT MSE HEATING COIL | Coil:Heating:Fuel | 18638.27 | 0.80 | |
| SPLIT MNE HEATING COIL | Coil:Heating:Fuel | 18383.44 | 0.80 | |
| SPLIT MN1 HEATING COIL | Coil:Heating:Fuel | 16491.49 | 0.80 | |
| SPLIT MN2 HEATING COIL | Coil:Heating:Fuel | 16471.86 | 0.80 | |
| SPLIT MS1 HEATING COIL | Coil:Heating:Fuel | 16791.30 | 0.80 | |
| SPLIT MS2 HEATING COIL | Coil:Heating:Fuel | 16771.18 | 0.80 | |
| SPLIT TSW HEATING COIL | Coil:Heating:Fuel | 10973.83 | 0.80 | |
| SPLIT TNW HEATING COIL | Coil:Heating:Fuel | 10929.50 | 0.80 | |
| SPLIT TSE HEATING COIL | Coil:Heating:Fuel | 10160.41 | 0.80 | |
| SPLIT TNE HEATING COIL | Coil:Heating:Fuel | 10115.17 | 0.80 | |
| SPLIT TN1 HEATING COIL | Coil:Heating:Fuel | 9293.05 | 0.80 | |
| SPLIT TN2 HEATING COIL | Coil:Heating:Fuel | 9265.17 | 0.80 | |
| SPLIT TS1 HEATING COIL | Coil:Heating:Fuel | 9348.74 | 0.80 | |
| SPLIT TS2 HEATING COIL | Coil:Heating:Fuel | 9320.96 | 0.80 |
| Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
| G SW APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| G SW APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| G NW APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| G NW APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| G NE APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| G NE APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| G N1 APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| G N1 APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| G N2 APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| G N2 APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| G S1 APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| G S1 APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| G S2 APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| G S2 APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| M SW APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.05 | 40.01 | 770.84 | 1.00 | 4.13 | General | ||
| M SW APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.05 | 40.01 | 770.84 | 1.00 | 4.13 | General | ||
| M NW APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.05 | 40.01 | 770.84 | 1.00 | 4.13 | General | ||
| M NW APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.05 | 40.01 | 770.84 | 1.00 | 4.13 | General | ||
| M SE APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.05 | 40.01 | 770.84 | 1.00 | 4.13 | General | ||
| M SE APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.05 | 40.01 | 770.84 | 1.00 | 4.13 | General | ||
| M NE APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.05 | 40.01 | 770.84 | 1.00 | 4.13 | General | ||
| M NE APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.05 | 40.01 | 770.84 | 1.00 | 4.13 | General | ||
| M N1 APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.05 | 40.01 | 770.84 | 1.00 | 4.13 | General | ||
| M N1 APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.05 | 40.01 | 770.84 | 1.00 | 4.13 | General | ||
| M N2 APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.05 | 40.01 | 770.84 | 1.00 | 4.13 | General | ||
| M N2 APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.05 | 40.01 | 770.84 | 1.00 | 4.13 | General | ||
| M S1 APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.05 | 40.01 | 770.84 | 1.00 | 4.13 | General | ||
| M S1 APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.05 | 40.01 | 770.84 | 1.00 | 4.13 | General | ||
| M S2 APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.05 | 40.01 | 770.84 | 1.00 | 4.13 | General | ||
| M S2 APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.05 | 40.01 | 770.84 | 1.00 | 4.13 | General | ||
| T SW APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| T SW APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| T NW APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| T NW APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| T SE APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| T SE APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| T NE APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| T NE APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| T N1 APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| T N1 APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| T N2 APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| T N2 APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| T S1 APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| T S1 APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| T S2 APARTMENT ERV SUP FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| T S2 APARTMENT ERV EXH FAN | Fan:OnOff | 0.30 | 233.69 | 0.03 | 20.01 | 770.84 | 1.00 | 7.36 | General | ||
| SPLIT GSW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.39 | 437.03 | 1120.11 | 1.00 | 1.73 | General | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 |
| SPLIT GNW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.38 | 429.34 | 1120.11 | 1.00 | 1.74 | General | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 |
| SPLIT OFFICE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.43 | 483.35 | 1120.11 | 1.00 | 1.68 | General | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:20:00 |
| SPLIT GNE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.36 | 406.73 | 1120.11 | 1.00 | 1.77 | General | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 |
| SPLIT GN1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.33 | 366.41 | 1120.11 | 1.00 | 1.84 | General | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 |
| SPLIT GN2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.33 | 365.99 | 1120.11 | 1.00 | 1.84 | General | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 |
| SPLIT GS1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.34 | 375.58 | 1120.11 | 1.00 | 1.82 | General | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 |
| SPLIT GS2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.34 | 378.61 | 1120.11 | 1.00 | 1.82 | General | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 |
| SPLIT MSW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.92 | 1031.19 | 1120.11 | 1.00 | 1.39 | General | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 |
| SPLIT MNW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.91 | 1016.64 | 1120.11 | 1.00 | 1.40 | General | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 |
| SPLIT MSE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.87 | 971.63 | 1120.11 | 1.00 | 1.41 | General | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 |
| SPLIT MNE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.85 | 957.25 | 1120.11 | 1.00 | 1.41 | General | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 |
| SPLIT MN1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.76 | 850.43 | 1120.11 | 1.00 | 1.45 | General | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 |
| SPLIT MN2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.76 | 849.32 | 1120.11 | 1.00 | 1.45 | General | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 |
| SPLIT MS1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.77 | 867.34 | 1120.11 | 1.00 | 1.44 | General | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 |
| SPLIT MS2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.77 | 866.21 | 1120.11 | 1.00 | 1.44 | General | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 |
| SPLIT TSW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.52 | 579.24 | 1120.11 | 1.00 | 1.59 | General | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 |
| SPLIT TNW SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.51 | 576.75 | 1120.11 | 1.00 | 1.59 | General | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 |
| SPLIT TSE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.48 | 533.31 | 1120.11 | 1.00 | 1.63 | General | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 |
| SPLIT TNE SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.47 | 530.76 | 1120.11 | 1.00 | 1.63 | General | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 |
| SPLIT TN1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.43 | 484.35 | 1120.11 | 1.00 | 1.68 | General | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 |
| SPLIT TN2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.43 | 482.78 | 1120.11 | 1.00 | 1.68 | General | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 |
| SPLIT TS1 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.44 | 487.49 | 1120.11 | 1.00 | 1.67 | General | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 |
| SPLIT TS2 SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.43 | 485.92 | 1120.11 | 1.00 | 1.67 | General | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 |
| Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
| None |
| Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
| G SW APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.77 |
| G NW APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.77 |
| G NE APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.77 |
| G N1 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.77 |
| G N2 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.77 |
| G S1 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.77 |
| G S2 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.77 |
| M SW APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.79 |
| M NW APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.79 |
| M SE APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.79 |
| M NE APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.79 |
| M N1 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.79 |
| M N2 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.79 |
| M S1 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.79 |
| M S2 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.79 |
| T SW APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.77 |
| T NW APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.77 |
| T SE APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.77 |
| T NE APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.77 |
| T N1 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.77 |
| T N2 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.77 |
| T S1 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.77 |
| T S2 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 1.50 | 0.77 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 09:14:34
Zone Sensible Cooling| Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
| G SW APARTMENT | 3982.52 | 4779.03 | 54.15 | 0.325 | 0.390 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 24.00 | 24.00 | 0.00807 | 33.03 | 0.00686 | 0.026 | 0.00 |
| G NW APARTMENT | 3914.14 | 4696.97 | 53.22 | 0.319 | 0.383 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 24.00 | 24.00 | 0.00803 | 33.03 | 0.00686 | 0.026 | 0.00 |
| OFFICE | 4250.78 | 5100.94 | 57.80 | 0.360 | 0.432 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:20:00 | 23.90 | 23.90 | 0.00796 | 31.69 | 0.00686 | 0.038 | 0.00 |
| G NE APARTMENT | 3712.96 | 4455.55 | 50.49 | 0.303 | 0.363 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 24.00 | 24.00 | 0.00803 | 33.03 | 0.00686 | 0.026 | 0.00 |
| G N1 APARTMENT | 3352.80 | 4023.36 | 45.59 | 0.273 | 0.327 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 24.00 | 24.00 | 0.00807 | 33.03 | 0.00686 | 0.026 | 0.00 |
| G N2 APARTMENT | 3349.02 | 4018.83 | 45.54 | 0.272 | 0.327 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 24.00 | 24.00 | 0.00807 | 33.03 | 0.00686 | 0.026 | 0.00 |
| G S1 APARTMENT | 3435.17 | 4122.21 | 46.71 | 0.279 | 0.335 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 24.00 | 24.00 | 0.00814 | 33.03 | 0.00686 | 0.026 | 0.00 |
| G S2 APARTMENT | 3462.18 | 4154.61 | 47.08 | 0.282 | 0.338 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 24.00 | 24.00 | 0.00814 | 33.03 | 0.00686 | 0.026 | 0.00 |
| M SW APARTMENT | 9370.62 | 11244.74 | 127.42 | 0.767 | 0.921 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 24.00 | 24.00 | 0.00803 | 33.03 | 0.00686 | 0.052 | 0.00 |
| M NW APARTMENT | 9240.35 | 11088.42 | 125.65 | 0.756 | 0.908 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 24.00 | 24.00 | 0.00801 | 33.03 | 0.00686 | 0.052 | 0.00 |
| M SE APARTMENT | 8836.49 | 10603.79 | 120.16 | 0.723 | 0.867 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 24.00 | 24.00 | 0.00804 | 33.03 | 0.00686 | 0.052 | 0.00 |
| M NE APARTMENT | 8708.07 | 10449.69 | 118.41 | 0.712 | 0.855 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 24.00 | 24.00 | 0.00801 | 33.03 | 0.00686 | 0.052 | 0.00 |
| M N1 APARTMENT | 7754.84 | 9305.80 | 105.45 | 0.633 | 0.759 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 24.00 | 24.00 | 0.00804 | 33.03 | 0.00686 | 0.052 | 0.00 |
| M N2 APARTMENT | 7744.96 | 9293.96 | 105.31 | 0.632 | 0.758 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 24.00 | 24.00 | 0.00804 | 33.03 | 0.00686 | 0.052 | 0.00 |
| M S1 APARTMENT | 7905.40 | 9486.48 | 107.50 | 0.645 | 0.774 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 24.00 | 24.00 | 0.00809 | 33.03 | 0.00686 | 0.052 | 0.00 |
| M S2 APARTMENT | 7895.28 | 9474.33 | 107.36 | 0.644 | 0.773 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 24.00 | 24.00 | 0.00809 | 33.03 | 0.00686 | 0.052 | 0.00 |
| T SW APARTMENT | 5255.17 | 6306.21 | 71.46 | 0.431 | 0.517 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 24.00 | 24.00 | 0.00801 | 33.03 | 0.00686 | 0.026 | 0.00 |
| T NW APARTMENT | 5232.97 | 6279.56 | 71.16 | 0.429 | 0.515 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 24.00 | 24.00 | 0.00799 | 33.03 | 0.00686 | 0.026 | 0.00 |
| T SE APARTMENT | 4845.71 | 5814.85 | 65.89 | 0.397 | 0.476 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 24.00 | 24.00 | 0.00801 | 33.03 | 0.00686 | 0.026 | 0.00 |
| T NE APARTMENT | 4823.06 | 5787.67 | 65.58 | 0.395 | 0.474 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 24.00 | 24.00 | 0.00799 | 33.03 | 0.00686 | 0.026 | 0.00 |
| T N1 APARTMENT | 4408.69 | 5290.43 | 59.95 | 0.360 | 0.432 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 24.00 | 24.00 | 0.00802 | 33.03 | 0.00686 | 0.026 | 0.00 |
| T N2 APARTMENT | 4394.57 | 5273.48 | 59.76 | 0.359 | 0.431 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 24.00 | 24.00 | 0.00802 | 33.03 | 0.00686 | 0.026 | 0.00 |
| T S1 APARTMENT | 4436.85 | 5324.22 | 60.33 | 0.363 | 0.435 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 24.00 | 24.00 | 0.00805 | 33.03 | 0.00686 | 0.026 | 0.00 |
| T S2 APARTMENT | 4422.78 | 5307.33 | 60.14 | 0.362 | 0.434 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 24.00 | 24.00 | 0.00805 | 33.03 | 0.00686 | 0.026 | 0.00 |
| Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
| G SW APARTMENT | 1400.90 | 1681.08 | 19.05 | 0.070 | 0.084 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:50:00 | 21.10 | 21.10 | 0.00747 | -5.20 | 0.00281 | 0.026 | 0.00 |
| G NW APARTMENT | 1290.28 | 1548.34 | 17.55 | 0.064 | 0.077 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | 21.10 | 21.10 | 0.00759 | -5.20 | 0.00281 | 0.026 | 0.00 |
| OFFICE | 1841.50 | 2209.80 | 25.04 | 0.091 | 0.110 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 18:50:00 | 21.10 | 21.10 | 0.00759 | -5.20 | 0.00281 | 0.038 | 0.00 |
| G NE APARTMENT | 1294.72 | 1553.66 | 17.61 | 0.064 | 0.077 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | 21.10 | 21.10 | 0.00759 | -5.20 | 0.00281 | 0.026 | 0.00 |
| G N1 APARTMENT | 736.73 | 884.08 | 10.02 | 0.037 | 0.044 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | 21.10 | 21.10 | 0.00771 | -5.20 | 0.00281 | 0.026 | 0.00 |
| G N2 APARTMENT | 736.88 | 884.25 | 10.02 | 0.037 | 0.044 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | 21.10 | 21.10 | 0.00771 | -5.20 | 0.00281 | 0.026 | 0.00 |
| G S1 APARTMENT | 849.10 | 1018.93 | 11.55 | 0.042 | 0.051 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:50:00 | 21.10 | 21.10 | 0.00746 | -5.20 | 0.00281 | 0.026 | 0.00 |
| G S2 APARTMENT | 857.74 | 1029.29 | 11.66 | 0.043 | 0.051 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:50:00 | 21.10 | 21.10 | 0.00747 | -5.20 | 0.00281 | 0.026 | 0.00 |
| M SW APARTMENT | 2845.13 | 3414.16 | 38.69 | 0.141 | 0.170 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | 21.10 | 21.10 | 0.00729 | -5.20 | 0.00281 | 0.052 | 0.00 |
| M NW APARTMENT | 2575.67 | 3090.80 | 35.02 | 0.128 | 0.154 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | 21.10 | 21.10 | 0.00744 | -5.20 | 0.00281 | 0.052 | 0.00 |
| M SE APARTMENT | 2856.00 | 3427.20 | 38.84 | 0.142 | 0.170 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | 21.10 | 21.10 | 0.00729 | -5.20 | 0.00281 | 0.052 | 0.00 |
| M NE APARTMENT | 2586.58 | 3103.90 | 35.17 | 0.129 | 0.154 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | 21.10 | 21.10 | 0.00744 | -5.20 | 0.00281 | 0.052 | 0.00 |
| M N1 APARTMENT | 1287.46 | 1544.95 | 17.51 | 0.064 | 0.077 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | 21.10 | 21.10 | 0.00750 | -5.20 | 0.00281 | 0.052 | 0.00 |
| M N2 APARTMENT | 1287.75 | 1545.31 | 17.51 | 0.064 | 0.077 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | 21.10 | 21.10 | 0.00750 | -5.20 | 0.00281 | 0.052 | 0.00 |
| M S1 APARTMENT | 1550.04 | 1860.04 | 21.08 | 0.077 | 0.092 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | 21.10 | 21.10 | 0.00721 | -5.20 | 0.00281 | 0.052 | 0.00 |
| M S2 APARTMENT | 1550.33 | 1860.40 | 21.08 | 0.077 | 0.092 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | 21.10 | 21.10 | 0.00721 | -5.20 | 0.00281 | 0.052 | 0.00 |
| T SW APARTMENT | 2586.68 | 3104.02 | 35.17 | 0.129 | 0.154 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | 21.10 | 21.10 | 0.00747 | -5.20 | 0.00281 | 0.026 | 0.00 |
| T NW APARTMENT | 2445.23 | 2934.27 | 33.25 | 0.121 | 0.146 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | 21.10 | 21.10 | 0.00756 | -5.20 | 0.00281 | 0.026 | 0.00 |
| T SE APARTMENT | 2594.00 | 3112.80 | 35.27 | 0.129 | 0.155 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | 21.10 | 21.10 | 0.00747 | -5.20 | 0.00281 | 0.026 | 0.00 |
| T NE APARTMENT | 2452.61 | 2943.13 | 33.35 | 0.122 | 0.146 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | 21.10 | 21.10 | 0.00756 | -5.20 | 0.00281 | 0.026 | 0.00 |
| T N1 APARTMENT | 1693.38 | 2032.06 | 23.03 | 0.084 | 0.101 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | 21.10 | 21.10 | 0.00768 | -5.20 | 0.00281 | 0.026 | 0.00 |
| T N2 APARTMENT | 1693.60 | 2032.32 | 23.03 | 0.084 | 0.101 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | 21.10 | 21.10 | 0.00768 | -5.20 | 0.00281 | 0.026 | 0.00 |
| T S1 APARTMENT | 1835.24 | 2202.29 | 24.96 | 0.091 | 0.109 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | 21.10 | 21.10 | 0.00754 | -5.20 | 0.00281 | 0.026 | 0.00 |
| T S2 APARTMENT | 1835.45 | 2202.54 | 24.96 | 0.091 | 0.109 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | 21.10 | 21.10 | 0.00754 | -5.20 | 0.00281 | 0.026 | 0.00 |
| Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
| SPLIT GSW | 0.39 | 0.39 | 0.08 | 0.08 | 0.3902 | 0.3902 | 0.3902 | 1.0000 | 1.0000 |
| SPLIT GNW | 0.38 | 0.38 | 0.08 | 0.08 | 0.3833 | 0.3833 | 0.3833 | 1.0000 | 1.0000 |
| SPLIT OFFICE | 0.43 | 0.43 | 0.11 | 0.11 | 0.4315 | 0.4315 | 0.4315 | 1.0000 | 1.0000 |
| SPLIT GNE | 0.36 | 0.36 | 0.08 | 0.08 | 0.3631 | 0.3631 | 0.3631 | 1.0000 | 1.0000 |
| SPLIT GN1 | 0.33 | 0.33 | 0.04 | 0.04 | 0.3271 | 0.3271 | 0.3271 | 1.0000 | 1.0000 |
| SPLIT GN2 | 0.33 | 0.33 | 0.04 | 0.04 | 0.3267 | 0.3267 | 0.3267 | 1.0000 | 1.0000 |
| SPLIT GS1 | 0.34 | 0.34 | 0.05 | 0.05 | 0.3353 | 0.3353 | 0.3353 | 1.0000 | 1.0000 |
| SPLIT GS2 | 0.34 | 0.34 | 0.05 | 0.05 | 0.3380 | 0.3380 | 0.3380 | 1.0000 | 1.0000 |
| SPLIT MSW | 0.92 | 0.92 | 0.17 | 0.17 | 0.9206 | 0.9206 | 0.9206 | 1.0000 | 1.0000 |
| SPLIT MNW | 0.91 | 0.91 | 0.15 | 0.15 | 0.9076 | 0.9076 | 0.9076 | 1.0000 | 1.0000 |
| SPLIT MSE | 0.87 | 0.87 | 0.17 | 0.17 | 0.8674 | 0.8674 | 0.8674 | 1.0000 | 1.0000 |
| SPLIT MNE | 0.85 | 0.85 | 0.15 | 0.15 | 0.8546 | 0.8546 | 0.8546 | 1.0000 | 1.0000 |
| SPLIT MN1 | 0.76 | 0.76 | 0.08 | 0.08 | 0.7592 | 0.7592 | 0.7592 | 1.0000 | 1.0000 |
| SPLIT MN2 | 0.76 | 0.76 | 0.08 | 0.08 | 0.7582 | 0.7582 | 0.7582 | 1.0000 | 1.0000 |
| SPLIT MS1 | 0.77 | 0.77 | 0.09 | 0.09 | 0.7743 | 0.7743 | 0.7743 | 1.0000 | 1.0000 |
| SPLIT MS2 | 0.77 | 0.77 | 0.09 | 0.09 | 0.7733 | 0.7733 | 0.7733 | 1.0000 | 1.0000 |
| SPLIT TSW | 0.52 | 0.52 | 0.15 | 0.15 | 0.5171 | 0.5171 | 0.5171 | 1.0000 | 1.0000 |
| SPLIT TNW | 0.51 | 0.51 | 0.15 | 0.15 | 0.5149 | 0.5149 | 0.5149 | 1.0000 | 1.0000 |
| SPLIT TSE | 0.48 | 0.48 | 0.15 | 0.15 | 0.4761 | 0.4761 | 0.4761 | 1.0000 | 1.0000 |
| SPLIT TNE | 0.47 | 0.47 | 0.15 | 0.15 | 0.4739 | 0.4739 | 0.4739 | 1.0000 | 1.0000 |
| SPLIT TN1 | 0.43 | 0.43 | 0.10 | 0.10 | 0.4324 | 0.4324 | 0.4324 | 1.0000 | 1.0000 |
| SPLIT TN2 | 0.43 | 0.43 | 0.10 | 0.10 | 0.4310 | 0.4310 | 0.4310 | 1.0000 | 1.0000 |
| SPLIT TS1 | 0.44 | 0.44 | 0.11 | 0.11 | 0.4352 | 0.4352 | 0.4352 | 1.0000 | 1.0000 |
| SPLIT TS2 | 0.43 | 0.43 | 0.11 | 0.11 | 0.4338 | 0.4338 | 0.4338 | 1.0000 | 1.0000 |
| Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
| None |
| Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
| SPLIT GSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT GSW | 6458.590 | 5171.104 | 0.390163 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 5863.04 | 5863.04 | 0.390163 | 25.70 | 15.09 | 0.00799182 | 12.80 | 10.32 | 0.00799182 | 33.03 | 0.00686340 | 16.59 | 6.6522 | 24.00 | 0.00807223 | 37.7120 | 3982.52 | 0.00 | 6457.49 | 4808.56 |
| SPLIT GSW HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT GSW | 8454.924 | 8454.924 | -999.0 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:50:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:50:00 | 8454.92 | 8454.92 | 0.390163 | 19.35 | 12.09 | 0.00715954 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 6.6522 | 21.10 | 0.00746962 | 41.6591 | 1400.90 | 0.00 | -999.00 | -999.00 |
| SPLIT GNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT GNW | 6345.025 | 5080.178 | 0.383303 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 5755.58 | 5755.58 | 0.383303 | 25.71 | 15.06 | 0.00795384 | 12.80 | 10.29 | 0.00795384 | 33.03 | 0.00686340 | 16.59 | 6.7713 | 24.00 | 0.00803304 | 37.5308 | 3914.14 | 0.00 | 6343.95 | 4724.00 |
| SPLIT GNW HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT GNW | 8318.795 | 8318.795 | -999.0 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | 8318.79 | 8318.79 | 0.383303 | 19.32 | 12.18 | 0.00726418 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 6.7713 | 21.10 | 0.00758781 | 42.3104 | 1290.28 | 0.00 | -999.00 | -999.00 |
| SPLIT OFFICE COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT OFFICE | 7143.230 | 5719.265 | 0.431523 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 12:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:20:00 | 6546.12 | 6546.12 | 0.431523 | 25.64 | 14.96 | 0.00786450 | 12.80 | 10.20 | 0.00786450 | 31.69 | 0.00686128 | 16.16 | 8.8306 | 23.90 | 0.00796329 | 37.4327 | 4182.21 | 0.00 | 7142.01 | 5318.28 |
| SPLIT OFFICE HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT OFFICE | 9610.622 | 9610.622 | -999.0 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 18:50:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 18:50:00 | 9610.62 | 9610.62 | 0.431523 | 18.78 | 11.88 | 0.00716542 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 8.8306 | 21.10 | 0.00758743 | 42.3082 | 1841.50 | 0.00 | -999.00 | -999.00 |
| SPLIT GNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT GNE | 6010.823 | 4812.597 | 0.363114 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 5453.62 | 5453.62 | 0.363114 | 25.74 | 15.07 | 0.00795088 | 12.80 | 10.28 | 0.00795088 | 33.03 | 0.00686340 | 16.59 | 7.1478 | 24.00 | 0.00803459 | 37.5380 | 3712.96 | 0.00 | 6009.80 | 4475.18 |
| SPLIT GNE HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT GNE | 7918.361 | 7918.361 | -999.0 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | 7918.36 | 7918.36 | 0.363114 | 19.22 | 12.12 | 0.00724726 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 7.1478 | 21.10 | 0.00758896 | 42.3168 | 1294.72 | 0.00 | -999.00 | -999.00 |
| SPLIT GN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT GN1 | 5414.963 | 4335.519 | 0.327118 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 4918.22 | 4918.22 | 0.327118 | 25.80 | 15.11 | 0.00797260 | 12.80 | 10.31 | 0.00797260 | 33.03 | 0.00686340 | 16.59 | 7.9343 | 24.00 | 0.00806819 | 37.6932 | 3352.80 | 0.00 | 5414.04 | 4031.55 |
| SPLIT GN1 HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT GN1 | 7204.352 | 7204.352 | -999.0 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | 7204.35 | 7204.35 | 0.327118 | 19.01 | 12.12 | 0.00732392 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 7.9343 | 21.10 | 0.00771307 | 42.9994 | 736.73 | 0.00 | -999.00 | -999.00 |
| SPLIT GN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT GN2 | 5408.729 | 4330.527 | 0.326741 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 4912.59 | 4912.59 | 0.326741 | 25.80 | 15.11 | 0.00797258 | 12.80 | 10.31 | 0.00797258 | 33.03 | 0.00686340 | 16.59 | 7.9435 | 24.00 | 0.00806829 | 37.6937 | 3349.02 | 0.00 | 5407.81 | 4026.91 |
| SPLIT GN2 HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT GN2 | 7196.882 | 7196.882 | -999.0 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | 7196.88 | 7196.88 | 0.326741 | 19.01 | 12.11 | 0.00732351 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 7.9435 | 21.10 | 0.00771311 | 42.9996 | 736.88 | 0.00 | -999.00 | -999.00 |
| SPLIT GS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT GS1 | 5550.570 | 4444.093 | 0.335310 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 5048.20 | 5019.52 | 0.335310 | 25.79 | 15.16 | 0.00803932 | 12.80 | 10.33 | 0.00800000 | 33.03 | 0.00686340 | 16.59 | 7.7405 | 24.00 | 0.00813798 | 38.0157 | 3435.17 | 0.00 | 5549.63 | 4132.52 |
| SPLIT GS1 HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT GS1 | 7366.888 | 7366.888 | -999.0 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:50:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:50:00 | 7366.89 | 7366.89 | 0.335310 | 19.06 | 11.93 | 0.00710428 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 7.7405 | 21.10 | 0.00746470 | 41.6314 | 849.10 | 0.00 | -999.00 | -999.00 |
| SPLIT GS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT GS2 | 5595.336 | 4479.935 | 0.338014 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 5088.67 | 5059.74 | 0.338014 | 25.78 | 15.16 | 0.00803935 | 12.80 | 10.33 | 0.00800000 | 33.03 | 0.00686340 | 16.59 | 7.6785 | 24.00 | 0.00813716 | 38.0120 | 3462.18 | 0.00 | 5594.38 | 4165.85 |
| SPLIT GS2 HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT GS2 | 7420.525 | 7420.525 | -999.0 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:50:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:50:00 | 7420.52 | 7420.52 | 0.338014 | 19.08 | 11.94 | 0.00711165 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 7.6785 | 21.10 | 0.00746956 | 41.6582 | 857.74 | 0.00 | -999.00 | -999.00 |
| SPLIT MSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT MSW | 15239.473 | 12201.565 | 0.920617 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 13816.84 | 13816.84 | 0.920617 | 25.62 | 15.04 | 0.00796892 | 12.80 | 10.30 | 0.00796892 | 33.03 | 0.00686340 | 16.59 | 5.6385 | 24.00 | 0.00803498 | 37.5398 | 18741.23 | 0.00 | 15236.88 | 11346.11 |
| SPLIT MSW HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT MSW | 19693.043 | 19693.043 | -999.0 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | 19693.04 | 19693.04 | 0.920617 | 19.62 | 12.08 | 0.00703783 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 5.6385 | 21.10 | 0.00729056 | 40.6735 | 5690.27 | 0.00 | -999.00 | -999.00 |
| SPLIT MNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT MNW | 15024.433 | 12029.391 | 0.907626 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 13615.05 | 13615.05 | 0.907626 | 25.62 | 15.02 | 0.00794390 | 12.80 | 10.28 | 0.00794390 | 33.03 | 0.00686340 | 16.59 | 5.7192 | 24.00 | 0.00800945 | 37.4218 | 18480.69 | 0.00 | 15021.88 | 11186.01 |
| SPLIT MNW HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT MNW | 19435.078 | 19435.078 | -999.0 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | 19435.08 | 19435.08 | 0.907626 | 19.60 | 12.20 | 0.00717633 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 5.7192 | 21.10 | 0.00744129 | 41.5037 | 5151.33 | 0.00 | -999.00 | -999.00 |
| SPLIT MSE COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT MSE | 14359.197 | 11496.767 | 0.867439 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 13022.30 | 13022.30 | 0.867439 | 25.64 | 15.05 | 0.00797002 | 12.80 | 10.30 | 0.00797002 | 33.03 | 0.00686340 | 16.59 | 5.9842 | 24.00 | 0.00804046 | 37.5652 | 17672.98 | 0.00 | 14356.75 | 10690.72 |
| SPLIT MSE HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT MSE | 18638.266 | 18638.266 | -999.0 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | 18638.27 | 18638.27 | 0.867439 | 19.53 | 12.03 | 0.00702455 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 5.9842 | 21.10 | 0.00729291 | 40.6865 | 5712.00 | 0.00 | -999.00 | -999.00 |
| SPLIT MNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT MNE | 14146.762 | 11326.680 | 0.854606 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 12821.76 | 12821.76 | 0.854606 | 25.65 | 15.03 | 0.00793956 | 12.80 | 10.27 | 0.00793956 | 33.03 | 0.00686340 | 16.59 | 6.0740 | 24.00 | 0.00800916 | 37.4205 | 17416.15 | 0.00 | 14144.35 | 10532.56 |
| SPLIT MNE HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT MNE | 18383.443 | 18383.443 | -999.0 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | 18383.44 | 18383.44 | 0.854606 | 19.50 | 12.15 | 0.00716179 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 6.0740 | 21.10 | 0.00744332 | 41.5148 | 5173.17 | 0.00 | -999.00 | -999.00 |
| SPLIT MN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT MN1 | 12568.056 | 10062.680 | 0.759236 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 11402.92 | 11402.92 | 0.759236 | 25.71 | 15.07 | 0.00796095 | 12.80 | 10.29 | 0.00796095 | 33.03 | 0.00686340 | 16.59 | 6.8370 | 24.00 | 0.00804150 | 37.5699 | 15509.67 | 0.00 | 12565.92 | 9357.18 |
| SPLIT MN1 HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT MN1 | 16491.488 | 16491.488 | -999.0 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | 16491.49 | 16491.49 | 0.759236 | 19.30 | 12.09 | 0.00717660 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 6.8370 | 21.10 | 0.00749717 | 41.8105 | 2574.91 | 0.00 | -999.00 | -999.00 |
| SPLIT MN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT MN2 | 12551.674 | 10049.564 | 0.758247 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 11388.12 | 11388.12 | 0.758247 | 25.71 | 15.07 | 0.00796090 | 12.80 | 10.29 | 0.00796090 | 33.03 | 0.00686340 | 16.59 | 6.8459 | 24.00 | 0.00804156 | 37.5702 | 15489.93 | 0.00 | 12549.54 | 9344.99 |
| SPLIT MN2 HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT MN2 | 16471.860 | 16471.860 | -999.0 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | 16471.86 | 16471.86 | 0.758247 | 19.30 | 12.09 | 0.00717628 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 6.8459 | 21.10 | 0.00749728 | 41.8111 | 2575.51 | 0.00 | -999.00 | -999.00 |
| SPLIT MS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT MS1 | 12818.057 | 10262.844 | 0.774339 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 11640.64 | 11627.99 | 0.774339 | 25.70 | 15.10 | 0.00800746 | 12.80 | 10.33 | 0.00800000 | 33.03 | 0.00686340 | 16.59 | 6.7037 | 24.00 | 0.00808966 | 37.7925 | 15810.81 | 0.00 | 12815.88 | 9543.31 |
| SPLIT MS1 HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT MS1 | 16791.298 | 16791.298 | -999.0 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | 16791.30 | 16791.30 | 0.774339 | 19.34 | 11.86 | 0.00691879 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 6.7037 | 21.10 | 0.00721413 | 40.2510 | 3100.07 | 0.00 | -999.00 | -999.00 |
| SPLIT MS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT MS2 | 12801.266 | 10249.401 | 0.773324 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 11625.50 | 11612.66 | 0.773324 | 25.70 | 15.10 | 0.00800757 | 12.80 | 10.33 | 0.00800000 | 33.03 | 0.00686340 | 16.59 | 6.7125 | 24.00 | 0.00808990 | 37.7936 | 15790.55 | 0.00 | 12799.09 | 9530.81 |
| SPLIT MS2 HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT MS2 | 16771.179 | 16771.179 | -999.0 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | 16771.18 | 16771.18 | 0.773324 | 19.33 | 11.86 | 0.00691853 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 6.7125 | 21.10 | 0.00721427 | 40.2517 | 3100.66 | 0.00 | -999.00 | -999.00 |
| SPLIT TSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT TSW | 8560.365 | 6853.902 | 0.517132 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 7754.70 | 7754.70 | 0.517132 | 25.57 | 15.01 | 0.00795185 | 12.80 | 10.29 | 0.00795185 | 33.03 | 0.00686340 | 16.59 | 5.0189 | 24.00 | 0.00800937 | 37.4215 | 5255.17 | 0.00 | 8558.91 | 6373.37 |
| SPLIT TSW HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT TSW | 10973.833 | 10973.833 | -999.0 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | 10973.83 | 10973.83 | 0.517132 | 19.78 | 12.32 | 0.00723136 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 5.0189 | 21.10 | 0.00746508 | 41.6367 | 2586.68 | 0.00 | -999.00 | -999.00 |
| SPLIT TNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT TNW | 8523.513 | 6824.396 | 0.514905 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 7718.80 | 7718.80 | 0.514905 | 25.57 | 15.00 | 0.00793655 | 12.80 | 10.27 | 0.00793655 | 33.03 | 0.00686340 | 16.59 | 5.0406 | 24.00 | 0.00799352 | 37.3482 | 5232.97 | 0.00 | 8522.06 | 6345.93 |
| SPLIT TNW HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT TNW | 10929.502 | 10929.502 | -999.0 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | 10929.50 | 10929.50 | 0.514905 | 19.77 | 12.39 | 0.00731590 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 5.0406 | 21.10 | 0.00755517 | 42.1323 | 2445.23 | 0.00 | -999.00 | -999.00 |
| SPLIT TSE COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT TSE | 7881.529 | 6310.388 | 0.476123 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 7141.76 | 7141.76 | 0.476123 | 25.60 | 15.02 | 0.00794912 | 12.80 | 10.28 | 0.00794912 | 33.03 | 0.00686340 | 16.59 | 5.4512 | 24.00 | 0.00801172 | 37.4324 | 4845.71 | 0.00 | 7880.19 | 5867.96 |
| SPLIT TSE HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT TSE | 10160.411 | 10160.411 | -999.0 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | 10160.41 | 10160.41 | 0.476123 | 19.66 | 12.26 | 0.00721252 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 5.4512 | 21.10 | 0.00746644 | 41.6442 | 2594.00 | 0.00 | -999.00 | -999.00 |
| SPLIT TNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT TNE | 7843.908 | 6280.266 | 0.473850 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 7104.86 | 7104.86 | 0.473850 | 25.61 | 15.01 | 0.00793056 | 12.80 | 10.26 | 0.00793056 | 33.03 | 0.00686340 | 16.59 | 5.4774 | 24.00 | 0.00799240 | 37.3430 | 4823.06 | 0.00 | 7842.57 | 5839.95 |
| SPLIT TNE HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT TNE | 10115.173 | 10115.173 | -999.0 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | 10115.17 | 10115.17 | 0.473850 | 19.66 | 12.33 | 0.00729630 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 5.4774 | 21.10 | 0.00755636 | 42.1389 | 2452.61 | 0.00 | -999.00 | -999.00 |
| SPLIT TN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT TN1 | 7158.020 | 5731.106 | 0.432416 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 6489.57 | 6489.57 | 0.432416 | 25.65 | 15.04 | 0.00795353 | 12.80 | 10.29 | 0.00795353 | 33.03 | 0.00686340 | 16.59 | 6.0022 | 24.00 | 0.00802314 | 37.4851 | 4408.69 | 0.00 | 7156.80 | 5329.30 |
| SPLIT TN1 HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT TN1 | 9293.054 | 9293.054 | -999.0 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | 9293.05 | 9293.05 | 0.432416 | 19.52 | 12.36 | 0.00738303 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 6.0022 | 21.10 | 0.00767514 | 42.7916 | 1693.38 | 0.00 | -999.00 | -999.00 |
| SPLIT TN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT TN2 | 7134.745 | 5712.471 | 0.431010 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 6468.54 | 6468.54 | 0.431010 | 25.65 | 15.04 | 0.00795337 | 12.80 | 10.29 | 0.00795337 | 33.03 | 0.00686340 | 16.59 | 6.0218 | 24.00 | 0.00802321 | 37.4854 | 4394.57 | 0.00 | 7133.53 | 5311.97 |
| SPLIT TN2 HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT TN2 | 9265.166 | 9265.166 | -999.0 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | 9265.17 | 9265.17 | 0.431010 | 19.52 | 12.36 | 0.00738211 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 6.0218 | 21.10 | 0.00767518 | 42.7918 | 1693.60 | 0.00 | -999.00 | -999.00 |
| SPLIT TS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT TS1 | 7204.371 | 5768.218 | 0.435216 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 6534.95 | 6534.95 | 0.435216 | 25.65 | 15.06 | 0.00797775 | 12.80 | 10.31 | 0.00797775 | 33.03 | 0.00686340 | 16.59 | 5.9636 | 24.00 | 0.00804842 | 37.6020 | 4436.85 | 0.00 | 7203.14 | 5363.81 |
| SPLIT TS1 HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT TS1 | 9348.745 | 9348.745 | -999.0 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | 9348.74 | 9348.74 | 0.435216 | 19.53 | 12.25 | 0.00725564 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 5.9636 | 21.10 | 0.00753767 | 42.0352 | 1835.24 | 0.00 | -999.00 | -999.00 |
| SPLIT TS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | SPLIT TS2 | 7181.183 | 5749.652 | 0.433815 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 6514.02 | 6514.02 | 0.433815 | 25.65 | 15.06 | 0.00797777 | 12.80 | 10.31 | 0.00797777 | 33.03 | 0.00686340 | 16.59 | 5.9829 | 24.00 | 0.00804868 | 37.6032 | 4422.78 | 0.00 | 7179.96 | 5346.54 |
| SPLIT TS2 HEATING COIL | COIL:HEATING:FUEL | AirLoopHVAC | SPLIT TS2 | 9320.961 | 9320.961 | -999.0 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | 9320.96 | 9320.96 | 0.433815 | 19.53 | 12.25 | 0.00725477 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 5.9829 | 21.10 | 0.00753772 | 42.0355 | 1835.45 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 09:14:34
Coils| Coil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
| SPLIT GSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT GSW | G SW APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 6458.590 | 5171.104 | 0.390163 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.6964 | 1004.8586 | 1.0443 | SPLIT GSW SUPPLY FAN | Fan:OnOff | 0.390163 | 0.40746003 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | Sensible | 5863.04 | 5863.04 | 0.9078 | 0.40746003 | 0.390163 | 25.70 | 15.09 | 0.00799182 | 46190.6 | 12.80 | 10.32 | 0.00799182 | 33039.2 | -999.0 | -999.00 | -999.00 | -999.00 | 437.025 | 5426.01 | 33.03 | 0.00686340 | 16.59 | 0.02595455 | 6.6522 | 24.05 | 0.00807223 | 24.00 | 0.00807223 | 37.7120 | 3982.52 | 0.00 | 6457.49 | 4808.56 | 0.39136844 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.65 | 13.84 | 0.00953274 | 38822.6 | |
| SPLIT GSW HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT GSW | G SW APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 8454.924 | 8454.924 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | SPLIT GSW SUPPLY FAN | Fan:OnOff | 0.390163 | 0.40746003 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:50:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:50:00 | Sensible | 8454.92 | 8454.92 | 1.0000 | 0.40746003 | 0.390163 | 19.35 | 12.09 | 0.00715954 | 37606.8 | 40.00 | 19.53 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8454.92 | -5.20 | 0.00280840 | -5.20 | 0.02595455 | 6.6522 | 21.10 | 0.00746962 | 21.10 | 0.00746962 | 41.6591 | 1400.90 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT GNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT GNW | G NW APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 6345.025 | 5080.178 | 0.383303 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.6258 | 1004.8586 | 1.0443 | SPLIT GNW SUPPLY FAN | Fan:OnOff | 0.383303 | 0.40029545 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | Sensible | 5755.58 | 5755.58 | 0.9071 | 0.40029545 | 0.383303 | 25.71 | 15.06 | 0.00795384 | 46104.1 | 12.80 | 10.29 | 0.00795384 | 32943.3 | -999.0 | -999.00 | -999.00 | -999.00 | 429.341 | 5326.24 | 33.03 | 0.00686340 | 16.59 | 0.02595455 | 6.7713 | 24.05 | 0.00803304 | 24.00 | 0.00803304 | 37.5308 | 3914.14 | 0.00 | 6343.95 | 4724.00 | 0.38448680 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.65 | 13.84 | 0.00953274 | 38822.6 | |
| SPLIT GNW HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT GNW | G NW APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 8318.795 | 8318.795 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | SPLIT GNW SUPPLY FAN | Fan:OnOff | 0.383303 | 0.40029545 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | Sensible | 8318.79 | 8318.79 | 1.0000 | 0.40029545 | 0.383303 | 19.32 | 12.18 | 0.00726418 | 37840.5 | 40.00 | 19.53 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8318.79 | -5.20 | 0.00280840 | -5.20 | 0.02595455 | 6.7713 | 21.10 | 0.00758781 | 21.10 | 0.00758781 | 42.3104 | 1290.28 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT OFFICE COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT OFFICE | OFFICE | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 7143.230 | 5719.265 | 0.431523 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.4597 | 1004.8586 | 1.0443 | SPLIT OFFICE SUPPLY FAN | Fan:OnOff | 0.431523 | 0.45065266 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 12:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 12:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:20:00 | Sensible | 6546.12 | 6546.12 | 0.9164 | 0.45065266 | 0.431523 | 25.64 | 14.96 | 0.00786450 | 45807.5 | 12.80 | 10.20 | 0.00786450 | 32717.7 | -999.0 | -999.00 | -999.00 | -999.00 | 483.352 | 6062.77 | 31.69 | 0.00686128 | 16.16 | 0.03810604 | 8.8306 | 23.90 | 0.00796167 | 23.90 | 0.00796329 | 37.4327 | 4182.21 | 0.00 | 7142.01 | 5318.28 | 0.43285528 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.65 | 13.84 | 0.00953274 | 38822.6 | |
| SPLIT OFFICE HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT OFFICE | OFFICE | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 9610.622 | 9610.622 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | SPLIT OFFICE SUPPLY FAN | Fan:OnOff | 0.431523 | 0.45065266 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 18:50:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 18:50:00 | Sensible | 9610.62 | 9610.62 | 1.0000 | 0.45065266 | 0.431523 | 18.78 | 11.88 | 0.00716542 | 37038.4 | 40.00 | 19.53 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9610.62 | -5.20 | 0.00280840 | -5.20 | 0.03810604 | 8.8306 | 21.10 | 0.00758743 | 21.10 | 0.00758743 | 42.3082 | 1841.50 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT GNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT GNE | G NE APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 6010.823 | 4812.597 | 0.363114 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.6203 | 1004.8586 | 1.0443 | SPLIT GNE SUPPLY FAN | Fan:OnOff | 0.363114 | 0.37921126 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | Sensible | 5453.62 | 5453.62 | 0.9073 | 0.37921126 | 0.363114 | 25.74 | 15.07 | 0.00795088 | 46128.2 | 12.80 | 10.28 | 0.00795088 | 32935.8 | -999.0 | -999.00 | -999.00 | -999.00 | 406.727 | 5046.90 | 33.03 | 0.00686340 | 16.59 | 0.02595455 | 7.1478 | 24.04 | 0.00803459 | 24.00 | 0.00803459 | 37.5380 | 3712.96 | 0.00 | 6009.80 | 4475.18 | 0.36423528 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.65 | 13.84 | 0.00953274 | 38822.6 | |
| SPLIT GNE HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT GNE | G NE APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 7918.361 | 7918.361 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | SPLIT GNE SUPPLY FAN | Fan:OnOff | 0.363114 | 0.37921126 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | Sensible | 7918.36 | 7918.36 | 1.0000 | 0.37921126 | 0.363114 | 19.22 | 12.12 | 0.00724726 | 37696.8 | 40.00 | 19.53 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 7918.36 | -5.20 | 0.00280840 | -5.20 | 0.02595455 | 7.1478 | 21.10 | 0.00758896 | 21.10 | 0.00758896 | 42.3168 | 1294.72 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT GN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT GN1 | G N1 APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 5414.963 | 4335.519 | 0.327118 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.6607 | 1004.8586 | 1.0443 | SPLIT GN1 SUPPLY FAN | Fan:OnOff | 0.327118 | 0.34161965 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | Sensible | 4918.22 | 4918.22 | 0.9083 | 0.34161965 | 0.327118 | 25.80 | 15.11 | 0.00797260 | 46247.4 | 12.80 | 10.31 | 0.00797260 | 32990.7 | -999.0 | -999.00 | -999.00 | -999.00 | 366.407 | 4551.81 | 33.03 | 0.00686340 | 16.59 | 0.02595455 | 7.9343 | 24.04 | 0.00806819 | 24.00 | 0.00806819 | 37.6932 | 3352.80 | 0.00 | 5414.04 | 4031.55 | 0.32812825 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.65 | 13.84 | 0.00953274 | 38822.6 | |
| SPLIT GN1 HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT GN1 | G N1 APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 7204.352 | 7204.352 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | SPLIT GN1 SUPPLY FAN | Fan:OnOff | 0.327118 | 0.34161965 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | Sensible | 7204.35 | 7204.35 | 1.0000 | 0.34161965 | 0.327118 | 19.01 | 12.12 | 0.00732392 | 37680.7 | 40.00 | 19.53 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 7204.35 | -5.20 | 0.00280840 | -5.20 | 0.02595455 | 7.9343 | 21.10 | 0.00771307 | 21.10 | 0.00771307 | 42.9994 | 736.73 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT GN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT GN2 | G N2 APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 5408.729 | 4330.527 | 0.326741 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.6606 | 1004.8586 | 1.0443 | SPLIT GN2 SUPPLY FAN | Fan:OnOff | 0.326741 | 0.34122634 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | Sensible | 4912.59 | 4912.59 | 0.9083 | 0.34122634 | 0.326741 | 25.80 | 15.11 | 0.00797258 | 46248.1 | 12.80 | 10.31 | 0.00797258 | 32990.6 | -999.0 | -999.00 | -999.00 | -999.00 | 365.986 | 4546.60 | 33.03 | 0.00686340 | 16.59 | 0.02595455 | 7.9435 | 24.04 | 0.00806829 | 24.00 | 0.00806829 | 37.6937 | 3349.02 | 0.00 | 5407.81 | 4026.91 | 0.32775048 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.65 | 13.84 | 0.00953274 | 38822.6 | |
| SPLIT GN2 HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT GN2 | G N2 APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 7196.882 | 7196.882 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | SPLIT GN2 SUPPLY FAN | Fan:OnOff | 0.326741 | 0.34122634 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | Sensible | 7196.88 | 7196.88 | 1.0000 | 0.34122634 | 0.326741 | 19.01 | 12.11 | 0.00732351 | 37677.2 | 40.00 | 19.53 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 7196.88 | -5.20 | 0.00280840 | -5.20 | 0.02595455 | 7.9435 | 21.10 | 0.00771311 | 21.10 | 0.00771311 | 42.9996 | 736.88 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT GS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT GS1 | G S1 APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 5550.570 | 4444.093 | 0.335310 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7847 | 1004.8586 | 1.0443 | SPLIT GS1 SUPPLY FAN | Fan:OnOff | 0.335310 | 0.35017481 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | Sensible | 5048.20 | 5019.52 | 0.9095 | 0.35017481 | 0.335310 | 25.79 | 15.16 | 0.00803932 | 46402.1 | 12.80 | 10.33 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 375.583 | 4672.61 | 33.03 | 0.00686340 | 16.59 | 0.02595455 | 7.7405 | 24.04 | 0.00813798 | 24.00 | 0.00813798 | 38.0157 | 3435.17 | 0.00 | 5549.63 | 4132.52 | 0.33634555 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.65 | 13.84 | 0.00953274 | 38822.6 | |
| SPLIT GS1 HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT GS1 | G S1 APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 7366.888 | 7366.888 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | SPLIT GS1 SUPPLY FAN | Fan:OnOff | 0.335310 | 0.35017481 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:50:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:50:00 | Sensible | 7366.89 | 7366.89 | 1.0000 | 0.35017481 | 0.335310 | 19.06 | 11.93 | 0.00710428 | 37175.4 | 40.00 | 19.53 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 7366.89 | -5.20 | 0.00280840 | -5.20 | 0.02595455 | 7.7405 | 21.10 | 0.00746470 | 21.10 | 0.00746470 | 41.6314 | 849.10 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT GS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT GS2 | G S2 APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 5595.336 | 4479.935 | 0.338014 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7848 | 1004.8586 | 1.0443 | SPLIT GS2 SUPPLY FAN | Fan:OnOff | 0.338014 | 0.35299898 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | Sensible | 5088.67 | 5059.74 | 0.9094 | 0.35299898 | 0.338014 | 25.78 | 15.16 | 0.00803935 | 46396.8 | 12.80 | 10.33 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 378.612 | 4710.06 | 33.03 | 0.00686340 | 16.59 | 0.02595455 | 7.6785 | 24.04 | 0.00813716 | 24.00 | 0.00813716 | 38.0120 | 3462.18 | 0.00 | 5594.38 | 4165.85 | 0.33905818 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.65 | 13.84 | 0.00953274 | 38822.6 | |
| SPLIT GS2 HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT GS2 | G S2 APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 7420.525 | 7420.525 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | SPLIT GS2 SUPPLY FAN | Fan:OnOff | 0.338014 | 0.35299898 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:50:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:50:00 | Sensible | 7420.52 | 7420.52 | 1.0000 | 0.35299898 | 0.338014 | 19.08 | 11.94 | 0.00711165 | 37210.7 | 40.00 | 19.53 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 7420.52 | -5.20 | 0.00280840 | -5.20 | 0.02595455 | 7.6785 | 21.10 | 0.00746956 | 21.10 | 0.00746956 | 41.6582 | 857.74 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT MSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT MSW | M SW APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 15239.473 | 12201.565 | 0.920617 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.6538 | 1004.8586 | 1.0443 | SPLIT MSW SUPPLY FAN | Fan:OnOff | 0.920617 | 0.96142912 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | Sensible | 13816.84 | 13816.84 | 0.9066 | 0.96142912 | 0.920617 | 25.62 | 15.04 | 0.00796892 | 46049.7 | 12.80 | 10.30 | 0.00796892 | 32981.4 | -999.0 | -999.00 | -999.00 | -999.00 | 1031.190 | 12785.65 | 33.03 | 0.00686340 | 16.59 | 0.05190911 | 5.6385 | 24.06 | 0.00803498 | 24.00 | 0.00803498 | 37.5398 | 18741.23 | 0.00 | 15236.88 | 11346.11 | 0.92345994 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.65 | 13.84 | 0.00953274 | 38822.6 | |
| SPLIT MSW HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT MSW | M SW APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 19693.043 | 19693.043 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | SPLIT MSW SUPPLY FAN | Fan:OnOff | 0.920617 | 0.96142912 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | Sensible | 19693.04 | 19693.04 | 1.0000 | 0.96142912 | 0.920617 | 19.62 | 12.08 | 0.00703783 | 37568.7 | 40.00 | 19.53 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 19693.04 | -5.20 | 0.00280840 | -5.20 | 0.05190911 | 5.6385 | 21.10 | 0.00729056 | 21.10 | 0.00729056 | 40.6735 | 5690.27 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT MNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT MNW | M NW APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 15024.433 | 12029.391 | 0.907626 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.6073 | 1004.8586 | 1.0443 | SPLIT MNW SUPPLY FAN | Fan:OnOff | 0.907626 | 0.94786261 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | Sensible | 13615.05 | 13615.05 | 0.9062 | 0.94786261 | 0.907626 | 25.62 | 15.02 | 0.00794390 | 45992.6 | 12.80 | 10.28 | 0.00794390 | 32918.2 | -999.0 | -999.00 | -999.00 | -999.00 | 1016.639 | 12598.41 | 33.03 | 0.00686340 | 16.59 | 0.05190911 | 5.7192 | 24.06 | 0.00800945 | 24.00 | 0.00800945 | 37.4218 | 18480.69 | 0.00 | 15021.88 | 11186.01 | 0.91042920 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.65 | 13.84 | 0.00953274 | 38822.6 | |
| SPLIT MNW HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT MNW | M NW APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 19435.078 | 19435.078 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | SPLIT MNW SUPPLY FAN | Fan:OnOff | 0.907626 | 0.94786261 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | Sensible | 19435.08 | 19435.08 | 1.0000 | 0.94786261 | 0.907626 | 19.60 | 12.20 | 0.00717633 | 37898.8 | 40.00 | 19.53 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 19435.08 | -5.20 | 0.00280840 | -5.20 | 0.05190911 | 5.7192 | 21.10 | 0.00744129 | 21.10 | 0.00744129 | 41.5037 | 5151.33 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT MSE COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT MSE | M SE APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 14359.197 | 11496.767 | 0.867439 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.6559 | 1004.8586 | 1.0443 | SPLIT MSE SUPPLY FAN | Fan:OnOff | 0.867439 | 0.90589418 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | Sensible | 13022.30 | 13022.30 | 0.9069 | 0.90589418 | 0.867439 | 25.64 | 15.05 | 0.00797002 | 46080.0 | 12.80 | 10.30 | 0.00797002 | 32984.1 | -999.0 | -999.00 | -999.00 | -999.00 | 971.625 | 12050.67 | 33.03 | 0.00686340 | 16.59 | 0.05190911 | 5.9842 | 24.05 | 0.00804046 | 24.00 | 0.00804046 | 37.5652 | 17672.98 | 0.00 | 14356.75 | 10690.72 | 0.87011820 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.65 | 13.84 | 0.00953274 | 38822.6 | |
| SPLIT MSE HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT MSE | M SE APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 18638.266 | 18638.266 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | SPLIT MSE SUPPLY FAN | Fan:OnOff | 0.867439 | 0.90589418 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | Sensible | 18638.27 | 18638.27 | 1.0000 | 0.90589418 | 0.867439 | 19.53 | 12.03 | 0.00702455 | 37442.5 | 40.00 | 19.53 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 18638.27 | -5.20 | 0.00280840 | -5.20 | 0.05190911 | 5.9842 | 21.10 | 0.00729291 | 21.10 | 0.00729291 | 40.6865 | 5712.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT MNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT MNE | M NE APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 14146.762 | 11326.680 | 0.854606 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.5993 | 1004.8586 | 1.0443 | SPLIT MNE SUPPLY FAN | Fan:OnOff | 0.854606 | 0.89249207 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | Sensible | 12821.76 | 12821.76 | 0.9063 | 0.89249207 | 0.854606 | 25.65 | 15.03 | 0.00793956 | 46010.0 | 12.80 | 10.27 | 0.00793956 | 32907.2 | -999.0 | -999.00 | -999.00 | -999.00 | 957.251 | 11864.51 | 33.03 | 0.00686340 | 16.59 | 0.05190911 | 6.0740 | 24.05 | 0.00800916 | 24.00 | 0.00800916 | 37.4205 | 17416.15 | 0.00 | 14144.35 | 10532.56 | 0.85724538 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.65 | 13.84 | 0.00953274 | 38822.6 | |
| SPLIT MNE HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT MNE | M NE APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 18383.443 | 18383.443 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | SPLIT MNE SUPPLY FAN | Fan:OnOff | 0.854606 | 0.89249207 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | Sensible | 18383.44 | 18383.44 | 1.0000 | 0.89249207 | 0.854606 | 19.50 | 12.15 | 0.00716179 | 37766.9 | 40.00 | 19.53 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 18383.44 | -5.20 | 0.00280840 | -5.20 | 0.05190911 | 6.0740 | 21.10 | 0.00744332 | 21.10 | 0.00744332 | 41.5148 | 5173.17 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT MN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT MN1 | M N1 APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 12568.056 | 10062.680 | 0.759236 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.6390 | 1004.8586 | 1.0443 | SPLIT MN1 SUPPLY FAN | Fan:OnOff | 0.759236 | 0.79289453 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | Sensible | 11402.92 | 11402.92 | 0.9073 | 0.79289453 | 0.759236 | 25.71 | 15.07 | 0.00796095 | 46127.9 | 12.80 | 10.29 | 0.00796095 | 32961.2 | -999.0 | -999.00 | -999.00 | -999.00 | 850.427 | 10552.49 | 33.03 | 0.00686340 | 16.59 | 0.05190911 | 6.8370 | 24.05 | 0.00804150 | 24.00 | 0.00804150 | 37.5699 | 15509.67 | 0.00 | 12565.92 | 9357.18 | 0.76158119 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.65 | 13.84 | 0.00953274 | 38822.6 | |
| SPLIT MN1 HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT MN1 | M N1 APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 16491.488 | 16491.488 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | SPLIT MN1 SUPPLY FAN | Fan:OnOff | 0.759236 | 0.79289453 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | Sensible | 16491.49 | 16491.49 | 1.0000 | 0.79289453 | 0.759236 | 19.30 | 12.09 | 0.00717660 | 37600.6 | 40.00 | 19.53 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 16491.49 | -5.20 | 0.00280840 | -5.20 | 0.05190911 | 6.8370 | 21.10 | 0.00749717 | 21.10 | 0.00749717 | 41.8105 | 2574.91 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT MN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT MN2 | M N2 APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 12551.674 | 10049.564 | 0.758247 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.6389 | 1004.8586 | 1.0443 | SPLIT MN2 SUPPLY FAN | Fan:OnOff | 0.758247 | 0.79186104 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | Sensible | 11388.12 | 11388.12 | 0.9073 | 0.79186104 | 0.758247 | 25.71 | 15.07 | 0.00796090 | 46128.6 | 12.80 | 10.29 | 0.00796090 | 32961.1 | -999.0 | -999.00 | -999.00 | -999.00 | 849.318 | 10538.80 | 33.03 | 0.00686340 | 16.59 | 0.05190911 | 6.8459 | 24.05 | 0.00804156 | 24.00 | 0.00804156 | 37.5702 | 15489.93 | 0.00 | 12549.54 | 9344.99 | 0.76058851 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.65 | 13.84 | 0.00953274 | 38822.6 | |
| SPLIT MN2 HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT MN2 | M N2 APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 16471.860 | 16471.860 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | SPLIT MN2 SUPPLY FAN | Fan:OnOff | 0.758247 | 0.79186104 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | Sensible | 16471.86 | 16471.86 | 1.0000 | 0.79186104 | 0.758247 | 19.30 | 12.09 | 0.00717628 | 37597.4 | 40.00 | 19.53 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 16471.86 | -5.20 | 0.00280840 | -5.20 | 0.05190911 | 6.8459 | 21.10 | 0.00749728 | 21.10 | 0.00749728 | 41.8111 | 2575.51 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT MS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT MS1 | M S1 APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 12818.057 | 10262.844 | 0.774339 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7255 | 1004.8586 | 1.0443 | SPLIT MS1 SUPPLY FAN | Fan:OnOff | 0.774339 | 0.80866658 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | Sensible | 11640.64 | 11627.99 | 0.9081 | 0.80866658 | 0.774339 | 25.70 | 15.10 | 0.00800746 | 46235.0 | 12.80 | 10.33 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 867.343 | 10773.30 | 33.03 | 0.00686340 | 16.59 | 0.05190911 | 6.7037 | 24.05 | 0.00808966 | 24.00 | 0.00808966 | 37.7925 | 15810.81 | 0.00 | 12815.88 | 9543.31 | 0.77673036 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.65 | 13.84 | 0.00953274 | 38822.6 | |
| SPLIT MS1 HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT MS1 | M S1 APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 16791.298 | 16791.298 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | SPLIT MS1 SUPPLY FAN | Fan:OnOff | 0.774339 | 0.80866658 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | Sensible | 16791.30 | 16791.30 | 1.0000 | 0.80866658 | 0.774339 | 19.34 | 11.86 | 0.00691879 | 36982.0 | 40.00 | 19.53 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 16791.30 | -5.20 | 0.00280840 | -5.20 | 0.05190911 | 6.7037 | 21.10 | 0.00721413 | 21.10 | 0.00721413 | 40.2510 | 3100.07 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT MS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT MS2 | M S2 APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 12801.266 | 10249.401 | 0.773324 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7257 | 1004.8586 | 1.0443 | SPLIT MS2 SUPPLY FAN | Fan:OnOff | 0.773324 | 0.80760726 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | Sensible | 11625.50 | 11612.66 | 0.9082 | 0.80760726 | 0.773324 | 25.70 | 15.10 | 0.00800757 | 46236.0 | 12.80 | 10.33 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 866.207 | 10759.29 | 33.03 | 0.00686340 | 16.59 | 0.05190911 | 6.7125 | 24.05 | 0.00808990 | 24.00 | 0.00808990 | 37.7936 | 15790.55 | 0.00 | 12799.09 | 9530.81 | 0.77571288 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.65 | 13.84 | 0.00953274 | 38822.6 | |
| SPLIT MS2 HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT MS2 | M S2 APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 16771.179 | 16771.179 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | SPLIT MS2 SUPPLY FAN | Fan:OnOff | 0.773324 | 0.80760726 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | Sensible | 16771.18 | 16771.18 | 1.0000 | 0.80760726 | 0.773324 | 19.33 | 11.86 | 0.00691853 | 36979.0 | 40.00 | 19.53 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 16771.18 | -5.20 | 0.00280840 | -5.20 | 0.05190911 | 6.7125 | 21.10 | 0.00721427 | 21.10 | 0.00721427 | 40.2517 | 3100.66 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT TSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT TSW | T SW APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 8560.365 | 6853.902 | 0.517132 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.6221 | 1004.8586 | 1.0443 | SPLIT TSW SUPPLY FAN | Fan:OnOff | 0.517132 | 0.54005702 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | Sensible | 7754.70 | 7754.70 | 0.9059 | 0.54005702 | 0.517132 | 25.57 | 15.01 | 0.00795185 | 45955.5 | 12.80 | 10.29 | 0.00795185 | 32938.3 | -999.0 | -999.00 | -999.00 | -999.00 | 579.243 | 7175.46 | 33.03 | 0.00686340 | 16.59 | 0.02595455 | 5.0189 | 24.06 | 0.00800937 | 24.00 | 0.00800937 | 37.4215 | 5255.17 | 0.00 | 8558.91 | 6373.37 | 0.51872885 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.65 | 13.84 | 0.00953274 | 38822.6 | |
| SPLIT TSW HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT TSW | T SW APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 10973.833 | 10973.833 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | SPLIT TSW SUPPLY FAN | Fan:OnOff | 0.517132 | 0.54005702 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | Sensible | 10973.83 | 10973.83 | 1.0000 | 0.54005702 | 0.517132 | 19.78 | 12.32 | 0.00723136 | 38225.3 | 40.00 | 19.53 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10973.83 | -5.20 | 0.00280840 | -5.20 | 0.02595455 | 5.0189 | 21.10 | 0.00746508 | 21.10 | 0.00746508 | 41.6367 | 2586.68 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT TNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT TNW | T NW APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 8523.513 | 6824.396 | 0.514905 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.5937 | 1004.8586 | 1.0443 | SPLIT TNW SUPPLY FAN | Fan:OnOff | 0.514905 | 0.53773208 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | Sensible | 7718.80 | 7718.80 | 0.9056 | 0.53773208 | 0.514905 | 25.57 | 15.00 | 0.00793655 | 45918.5 | 12.80 | 10.27 | 0.00793655 | 32899.6 | -999.0 | -999.00 | -999.00 | -999.00 | 576.750 | 7142.05 | 33.03 | 0.00686340 | 16.59 | 0.02595455 | 5.0406 | 24.06 | 0.00799352 | 24.00 | 0.00799352 | 37.3482 | 5232.97 | 0.00 | 8522.06 | 6345.93 | 0.51649572 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.65 | 13.84 | 0.00953274 | 38822.6 | |
| SPLIT TNW HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT TNW | T NW APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 10929.502 | 10929.502 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | SPLIT TNW SUPPLY FAN | Fan:OnOff | 0.514905 | 0.53773208 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | Sensible | 10929.50 | 10929.50 | 1.0000 | 0.53773208 | 0.514905 | 19.77 | 12.39 | 0.00731590 | 38434.3 | 40.00 | 19.53 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10929.50 | -5.20 | 0.00280840 | -5.20 | 0.02595455 | 5.0406 | 21.10 | 0.00755517 | 21.10 | 0.00755517 | 42.1323 | 2445.23 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT TSE COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT TSE | T SE APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 7881.529 | 6310.388 | 0.476123 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.6170 | 1004.8586 | 1.0443 | SPLIT TSE SUPPLY FAN | Fan:OnOff | 0.476123 | 0.49723055 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | Sensible | 7141.76 | 7141.76 | 0.9061 | 0.49723055 | 0.476123 | 25.60 | 15.02 | 0.00794912 | 45986.2 | 12.80 | 10.28 | 0.00794912 | 32931.4 | -999.0 | -999.00 | -999.00 | -999.00 | 533.309 | 6608.45 | 33.03 | 0.00686340 | 16.59 | 0.02595455 | 5.4512 | 24.06 | 0.00801172 | 24.00 | 0.00801172 | 37.4324 | 4845.71 | 0.00 | 7880.19 | 5867.96 | 0.47759370 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.65 | 13.84 | 0.00953274 | 38822.6 | |
| SPLIT TSE HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT TSE | T SE APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 10160.411 | 10160.411 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | SPLIT TSE SUPPLY FAN | Fan:OnOff | 0.476123 | 0.49723055 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | Sensible | 10160.41 | 10160.41 | 1.0000 | 0.49723055 | 0.476123 | 19.66 | 12.26 | 0.00721252 | 38061.7 | 40.00 | 19.53 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10160.41 | -5.20 | 0.00280840 | -5.20 | 0.02595455 | 5.4512 | 21.10 | 0.00746644 | 21.10 | 0.00746644 | 41.6442 | 2594.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT TNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT TNE | T NE APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 7843.908 | 6280.266 | 0.473850 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.5825 | 1004.8586 | 1.0443 | SPLIT TNE SUPPLY FAN | Fan:OnOff | 0.473850 | 0.49485710 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | Sensible | 7104.86 | 7104.86 | 0.9058 | 0.49485710 | 0.473850 | 25.61 | 15.01 | 0.00793056 | 45941.3 | 12.80 | 10.26 | 0.00793056 | 32884.5 | -999.0 | -999.00 | -999.00 | -999.00 | 530.764 | 6574.09 | 33.03 | 0.00686340 | 16.59 | 0.02595455 | 5.4774 | 24.06 | 0.00799240 | 24.00 | 0.00799240 | 37.3430 | 4823.06 | 0.00 | 7842.57 | 5839.95 | 0.47531398 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.65 | 13.84 | 0.00953274 | 38822.6 | |
| SPLIT TNE HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT TNE | T NE APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 10115.173 | 10115.173 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | SPLIT TNE SUPPLY FAN | Fan:OnOff | 0.473850 | 0.49485710 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | Sensible | 10115.17 | 10115.17 | 1.0000 | 0.49485710 | 0.473850 | 19.66 | 12.33 | 0.00729630 | 38267.6 | 40.00 | 19.53 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10115.17 | -5.20 | 0.00280840 | -5.20 | 0.02595455 | 5.4774 | 21.10 | 0.00755636 | 21.10 | 0.00755636 | 42.1389 | 2452.61 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT TN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT TN1 | T N1 APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 7158.020 | 5731.106 | 0.432416 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.6252 | 1004.8586 | 1.0443 | SPLIT TN1 SUPPLY FAN | Fan:OnOff | 0.432416 | 0.45158572 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | Sensible | 6489.57 | 6489.57 | 0.9066 | 0.45158572 | 0.432416 | 25.65 | 15.04 | 0.00795353 | 46044.7 | 12.80 | 10.29 | 0.00795353 | 32942.5 | -999.0 | -999.00 | -999.00 | -999.00 | 484.353 | 6005.22 | 33.03 | 0.00686340 | 16.59 | 0.02595455 | 6.0022 | 24.06 | 0.00802314 | 24.00 | 0.00802314 | 37.4851 | 4408.69 | 0.00 | 7156.80 | 5329.30 | 0.43375150 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.65 | 13.84 | 0.00953274 | 38822.6 | |
| SPLIT TN1 HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT TN1 | T N1 APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 9293.054 | 9293.054 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | SPLIT TN1 SUPPLY FAN | Fan:OnOff | 0.432416 | 0.45158572 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | Sensible | 9293.05 | 9293.05 | 1.0000 | 0.45158572 | 0.432416 | 19.52 | 12.36 | 0.00738303 | 38347.7 | 40.00 | 19.53 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9293.05 | -5.20 | 0.00280840 | -5.20 | 0.02595455 | 6.0022 | 21.10 | 0.00767514 | 21.10 | 0.00767514 | 42.7916 | 1693.38 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT TN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT TN2 | T N2 APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 7134.745 | 5712.471 | 0.431010 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.6249 | 1004.8586 | 1.0443 | SPLIT TN2 SUPPLY FAN | Fan:OnOff | 0.431010 | 0.45011735 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | Sensible | 6468.54 | 6468.54 | 0.9066 | 0.45011735 | 0.431010 | 25.65 | 15.04 | 0.00795337 | 46045.9 | 12.80 | 10.29 | 0.00795337 | 32942.1 | -999.0 | -999.00 | -999.00 | -999.00 | 482.778 | 5985.76 | 33.03 | 0.00686340 | 16.59 | 0.02595455 | 6.0218 | 24.06 | 0.00802321 | 24.00 | 0.00802321 | 37.4854 | 4394.57 | 0.00 | 7133.53 | 5311.97 | 0.43234112 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.65 | 13.84 | 0.00953274 | 38822.6 | |
| SPLIT TN2 HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT TN2 | T N2 APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 9265.166 | 9265.166 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | SPLIT TN2 SUPPLY FAN | Fan:OnOff | 0.431010 | 0.45011735 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | Sensible | 9265.17 | 9265.17 | 1.0000 | 0.45011735 | 0.431010 | 19.52 | 12.36 | 0.00738211 | 38340.1 | 40.00 | 19.53 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9265.17 | -5.20 | 0.00280840 | -5.20 | 0.02595455 | 6.0218 | 21.10 | 0.00767518 | 21.10 | 0.00767518 | 42.7918 | 1693.60 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT TS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT TS1 | T S1 APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 7204.371 | 5768.218 | 0.435216 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.6702 | 1004.8586 | 1.0443 | SPLIT TS1 SUPPLY FAN | Fan:OnOff | 0.435216 | 0.45450993 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | Sensible | 6534.95 | 6534.95 | 0.9071 | 0.45450993 | 0.435216 | 25.65 | 15.06 | 0.00797775 | 46103.2 | 12.80 | 10.31 | 0.00797775 | 33003.6 | -999.0 | -999.00 | -999.00 | -999.00 | 487.489 | 6047.47 | 33.03 | 0.00686340 | 16.59 | 0.02595455 | 5.9636 | 24.06 | 0.00804842 | 24.00 | 0.00804842 | 37.6020 | 4436.85 | 0.00 | 7203.14 | 5363.81 | 0.43656022 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.65 | 13.84 | 0.00953274 | 38822.6 | |
| SPLIT TS1 HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT TS1 | T S1 APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 9348.745 | 9348.745 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | SPLIT TS1 SUPPLY FAN | Fan:OnOff | 0.435216 | 0.45450993 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | Sensible | 9348.74 | 9348.74 | 1.0000 | 0.45450993 | 0.435216 | 19.53 | 12.25 | 0.00725564 | 38034.5 | 40.00 | 19.53 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9348.74 | -5.20 | 0.00280840 | -5.20 | 0.02595455 | 5.9636 | 21.10 | 0.00753767 | 21.10 | 0.00753767 | 42.0352 | 1835.24 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| SPLIT TS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | SPLIT TS2 | T S2 APARTMENT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 7181.183 | 5749.652 | 0.433815 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.6703 | 1004.8586 | 1.0443 | SPLIT TS2 SUPPLY FAN | Fan:OnOff | 0.433815 | 0.45304707 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | Sensible | 6514.02 | 6514.02 | 0.9071 | 0.45304707 | 0.433815 | 25.65 | 15.06 | 0.00797777 | 46104.8 | 12.80 | 10.31 | 0.00797777 | 33003.7 | -999.0 | -999.00 | -999.00 | -999.00 | 485.920 | 6028.10 | 33.03 | 0.00686340 | 16.59 | 0.02595455 | 5.9829 | 24.06 | 0.00804868 | 24.00 | 0.00804868 | 37.6032 | 4422.78 | 0.00 | 7179.96 | 5346.54 | 0.43515513 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.65 | 13.84 | 0.00953274 | 38822.6 | |
| SPLIT TS2 HEATING COIL | COIL:HEATING:FUEL | AirLoop | AirLoopHVAC | SPLIT TS2 | T S2 APARTMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 9320.961 | 9320.961 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | SPLIT TS2 SUPPLY FAN | Fan:OnOff | 0.433815 | 0.45304707 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 05:00:00 | Sensible | 9320.96 | 9320.96 | 1.0000 | 0.45304707 | 0.433815 | 19.53 | 12.25 | 0.00725477 | 38027.1 | 40.00 | 19.53 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9320.96 | -5.20 | 0.00280840 | -5.20 | 0.02595455 | 5.9829 | 21.10 | 0.00753772 | 21.10 | 0.00753772 | 42.0355 | 1835.45 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 09:14:34
Economizer| High Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
| None |
| Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
| None |
| Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
| G SW APARTMENT | 2084.17 | 3395.17 | 354.50 |
| G NW APARTMENT | 4114.67 | 5144.83 | 1760.67 |
| OFFICE | 899.17 | 681.17 | 54.83 |
| G NE APARTMENT | 4080.17 | 5133.83 | 1752.67 |
| G N1 APARTMENT | 3349.33 | 5179.33 | 1207.50 |
| G N2 APARTMENT | 3348.67 | 5176.67 | 1205.17 |
| G S1 APARTMENT | 1756.67 | 3329.83 | 147.50 |
| G S2 APARTMENT | 1891.83 | 3211.67 | 118.00 |
| M SW APARTMENT | 1868.50 | 3348.50 | 243.83 |
| M NW APARTMENT | 3287.33 | 5059.67 | 1035.67 |
| M SE APARTMENT | 1846.00 | 3393.00 | 256.50 |
| M NE APARTMENT | 3271.00 | 5048.33 | 1055.00 |
| M N1 APARTMENT | 2633.17 | 5114.00 | 649.67 |
| M N2 APARTMENT | 2634.67 | 5113.67 | 654.00 |
| M S1 APARTMENT | 1631.83 | 3294.50 | 144.00 |
| M S2 APARTMENT | 1631.83 | 3294.17 | 144.00 |
| T SW APARTMENT | 3010.50 | 3774.33 | 1457.00 |
| T NW APARTMENT | 4899.17 | 5442.00 | 2547.00 |
| T SE APARTMENT | 2964.50 | 3809.17 | 1468.83 |
| T NE APARTMENT | 4846.67 | 5405.50 | 2506.17 |
| T N1 APARTMENT | 4470.83 | 5510.50 | 2331.17 |
| T N2 APARTMENT | 4471.67 | 5508.00 | 2331.67 |
| T S1 APARTMENT | 2554.83 | 3774.67 | 1108.67 |
| T S2 APARTMENT | 2552.83 | 3776.33 | 1110.17 |
| T CORRIDOR | 5733.33 | 7952.67 | 5135.50 |
| G CORRIDOR | 5398.50 | 6029.17 | 3168.00 |
| M CORRIDOR | 7823.50 | 8002.00 | 7218.00 |
| Facility | 8649.33 | 8736.67 | 8109.33 |
| During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
| G SW APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| G NW APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| OFFICE | 0.00 | 0.00 | 0.00 | 0.00 |
| G NE APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| G N1 APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| G N2 APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| G S1 APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| G S2 APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| M SW APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| M NW APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| M SE APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| M NE APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| M N1 APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| M N2 APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| M S1 APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| M S2 APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| T SW APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| T NW APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| T SE APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| T NE APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| T N1 APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| T N2 APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| T S1 APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| T S2 APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
| T CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
| G CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
| M CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
| Facility | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 09:14:34
Average Outdoor Air During Occupied Hours| Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
| G SW APARTMENT | 2.40 | 2.50 | 268.97 | 0.353 | 0.156 | 0.000 | 0.048 |
| G NW APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.163 | 0.000 | 0.063 |
| OFFICE | 4.75 | 4.75 | 268.97 | 0.519 | 0.175 | 0.000 | 0.000 |
| G NE APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.163 | 0.000 | 0.063 |
| G N1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.098 | 0.000 | 0.063 |
| G N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.098 | 0.000 | 0.063 |
| G S1 APARTMENT | 2.40 | 2.50 | 268.97 | 0.353 | 0.094 | 0.000 | 0.048 |
| G S2 APARTMENT | 2.40 | 2.50 | 268.97 | 0.353 | 0.094 | 0.000 | 0.048 |
| M SW APARTMENT | 2.40 | 2.50 | 268.97 | 0.353 | 0.224 | 0.000 | 0.058 |
| M NW APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.235 | 0.000 | 0.079 |
| M SE APARTMENT | 2.40 | 2.50 | 268.97 | 0.353 | 0.224 | 0.000 | 0.058 |
| M NE APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.235 | 0.000 | 0.079 |
| M N1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.142 | 0.000 | 0.079 |
| M N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.142 | 0.000 | 0.079 |
| M S1 APARTMENT | 2.40 | 2.50 | 268.97 | 0.354 | 0.135 | 0.000 | 0.058 |
| M S2 APARTMENT | 2.40 | 2.50 | 268.97 | 0.354 | 0.135 | 0.000 | 0.058 |
| T SW APARTMENT | 2.40 | 2.50 | 268.97 | 0.353 | 0.295 | 0.000 | 0.067 |
| T NW APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.310 | 0.000 | 0.092 |
| T SE APARTMENT | 2.40 | 2.50 | 268.97 | 0.353 | 0.295 | 0.000 | 0.067 |
| T NE APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.310 | 0.000 | 0.092 |
| T N1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.187 | 0.000 | 0.092 |
| T N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.187 | 0.000 | 0.092 |
| T S1 APARTMENT | 2.40 | 2.50 | 268.97 | 0.353 | 0.178 | 0.000 | 0.067 |
| T S2 APARTMENT | 2.40 | 2.50 | 268.97 | 0.353 | 0.178 | 0.000 | 0.067 |
| Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
| G SW APARTMENT | 2.40 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
| G NW APARTMENT | 1.71 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
| OFFICE | 4.75 | 4.75 | 268.97 | 0.503 | 0.000 | 0.000 | 0.000 |
| G NE APARTMENT | 1.71 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
| G N1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
| G N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
| G S1 APARTMENT | 2.40 | 2.50 | 268.97 | 0.344 | 0.000 | 0.000 | 0.000 |
| G S2 APARTMENT | 2.40 | 2.50 | 268.97 | 0.344 | 0.000 | 0.000 | 0.000 |
| M SW APARTMENT | 2.40 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
| M NW APARTMENT | 1.71 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
| M SE APARTMENT | 2.40 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
| M NE APARTMENT | 1.71 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
| M N1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
| M N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
| M S1 APARTMENT | 2.40 | 2.50 | 268.97 | 0.344 | 0.000 | 0.000 | 0.000 |
| M S2 APARTMENT | 2.40 | 2.50 | 268.97 | 0.344 | 0.000 | 0.000 | 0.000 |
| T SW APARTMENT | 2.40 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
| T NW APARTMENT | 1.71 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
| T SE APARTMENT | 2.40 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
| T NE APARTMENT | 1.71 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
| T N1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
| T N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
| T S1 APARTMENT | 2.40 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
| T S2 APARTMENT | 2.40 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 09:14:34
Mechanical Ventilation Parameters by Zone| AirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
| G SW APARTMENT | SPLIT GSW | 2.40 | 2.50 | 268.97 | 88.25 | 0.0260 | 0.026 |
| G NW APARTMENT | SPLIT GNW | 1.71 | 2.50 | 268.97 | 88.25 | 0.0260 | 0.026 |
| OFFICE | SPLIT OFFICE | 4.75 | 4.75 | 268.97 | 88.25 | 0.0381 | 0.038 |
| G NE APARTMENT | SPLIT GNE | 1.71 | 2.50 | 268.97 | 88.25 | 0.0260 | 0.026 |
| G N1 APARTMENT | SPLIT GN1 | 1.71 | 2.50 | 268.97 | 88.25 | 0.0260 | 0.026 |
| G N2 APARTMENT | SPLIT GN2 | 1.71 | 2.50 | 268.97 | 88.25 | 0.0260 | 0.026 |
| G S1 APARTMENT | SPLIT GS1 | 2.40 | 2.50 | 268.97 | 88.25 | 0.0260 | 0.026 |
| G S2 APARTMENT | SPLIT GS2 | 2.40 | 2.50 | 268.97 | 88.25 | 0.0260 | 0.026 |
| M SW APARTMENT | SPLIT MSW | 2.40 | 2.50 | 268.97 | 88.25 | 0.0519 | 0.052 |
| M NW APARTMENT | SPLIT MNW | 1.71 | 2.50 | 268.97 | 88.25 | 0.0519 | 0.052 |
| M SE APARTMENT | SPLIT MSE | 2.40 | 2.50 | 268.97 | 88.25 | 0.0519 | 0.052 |
| M NE APARTMENT | SPLIT MNE | 1.71 | 2.50 | 268.97 | 88.25 | 0.0519 | 0.052 |
| M N1 APARTMENT | SPLIT MN1 | 1.71 | 2.50 | 268.97 | 88.25 | 0.0519 | 0.052 |
| M N2 APARTMENT | SPLIT MN2 | 1.71 | 2.50 | 268.97 | 88.25 | 0.0519 | 0.052 |
| M S1 APARTMENT | SPLIT MS1 | 2.40 | 2.50 | 268.97 | 88.25 | 0.0519 | 0.052 |
| M S2 APARTMENT | SPLIT MS2 | 2.40 | 2.50 | 268.97 | 88.25 | 0.0519 | 0.052 |
| T SW APARTMENT | SPLIT TSW | 2.40 | 2.50 | 268.97 | 88.25 | 0.0260 | 0.026 |
| T NW APARTMENT | SPLIT TNW | 1.71 | 2.50 | 268.97 | 88.25 | 0.0260 | 0.026 |
| T SE APARTMENT | SPLIT TSE | 2.40 | 2.50 | 268.97 | 88.25 | 0.0260 | 0.026 |
| T NE APARTMENT | SPLIT TNE | 1.71 | 2.50 | 268.97 | 88.25 | 0.0260 | 0.026 |
| T N1 APARTMENT | SPLIT TN1 | 1.71 | 2.50 | 268.97 | 88.25 | 0.0260 | 0.026 |
| T N2 APARTMENT | SPLIT TN2 | 1.71 | 2.50 | 268.97 | 88.25 | 0.0260 | 0.026 |
| T S1 APARTMENT | SPLIT TS1 | 2.40 | 2.50 | 268.97 | 88.25 | 0.0260 | 0.026 |
| T S2 APARTMENT | SPLIT TS2 | 2.40 | 2.50 | 268.97 | 88.25 | 0.0260 | 0.026 |
| Total Facility | 68.19 | 82.25 | 8607.06 | 2823.98 | 0.8427 | 1.258 |
| Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
| G SW APARTMENT | 818502.78 | 150278.96 | 968781.74 | 378370.14 | 1347151.88 | 818502.78 | 0.00 | 7157.00 | 1603.00 | 2615.00 |
| G NW APARTMENT | 818502.78 | 145132.85 | 963635.63 | 378370.14 | 1342005.77 | 818502.78 | 0.00 | 7157.00 | 1603.00 | 0.00 |
| OFFICE | 1201711.97 | 0.00 | 1201711.97 | 378370.14 | 1580082.11 | 1201711.97 | 0.00 | 8760.00 | 0.00 | 7010.00 |
| G NE APARTMENT | 818502.78 | 145358.21 | 963860.99 | 378370.14 | 1342231.13 | 818502.78 | 0.00 | 7157.00 | 1603.00 | 0.00 |
| G N1 APARTMENT | 818502.78 | 145686.33 | 964189.11 | 228223.26 | 1192412.37 | 818502.78 | 0.00 | 7157.00 | 1603.00 | 0.00 |
| G N2 APARTMENT | 818502.78 | 145707.77 | 964210.55 | 228223.26 | 1192433.81 | 818502.78 | 0.00 | 7157.00 | 1603.00 | 0.00 |
| G S1 APARTMENT | 818502.78 | 151377.08 | 969879.86 | 228223.26 | 1198103.13 | 818502.78 | 0.00 | 7157.00 | 1603.00 | 2615.00 |
| G S2 APARTMENT | 818502.78 | 151569.10 | 970071.88 | 228223.26 | 1198295.14 | 818502.78 | 0.00 | 7157.00 | 1603.00 | 2615.00 |
| M SW APARTMENT | 1637005.55 | 186226.61 | 1823232.16 | 543746.39 | 2366978.55 | 1637005.55 | 0.00 | 7117.33 | 1642.67 | 2615.00 |
| M NW APARTMENT | 1637005.55 | 182464.28 | 1819469.84 | 543746.39 | 2363216.22 | 1637005.55 | 0.00 | 7117.33 | 1642.67 | 0.00 |
| M SE APARTMENT | 1637005.55 | 186334.85 | 1823340.40 | 543746.39 | 2367086.79 | 1637005.55 | 0.00 | 7117.33 | 1642.67 | 2615.00 |
| M NE APARTMENT | 1637005.55 | 182693.07 | 1819698.62 | 543746.39 | 2363445.01 | 1637005.55 | 0.00 | 7117.33 | 1642.67 | 0.00 |
| M N1 APARTMENT | 1637005.55 | 182927.93 | 1819933.49 | 327974.02 | 2147907.50 | 1637005.55 | 0.00 | 7117.33 | 1642.67 | 0.00 |
| M N2 APARTMENT | 1637005.55 | 182952.22 | 1819957.77 | 327974.02 | 2147931.79 | 1637005.55 | 0.00 | 7117.33 | 1642.67 | 0.00 |
| M S1 APARTMENT | 1637005.55 | 186568.19 | 1823573.74 | 327974.02 | 2151547.76 | 1637005.55 | 0.00 | 7117.33 | 1642.67 | 2615.00 |
| M S2 APARTMENT | 1637005.55 | 186573.05 | 1823578.61 | 327974.02 | 2151552.62 | 1637005.55 | 0.00 | 7117.33 | 1642.67 | 2615.00 |
| T SW APARTMENT | 818502.78 | 216447.81 | 1034950.59 | 719263.02 | 1754213.61 | 818502.78 | 0.00 | 7142.00 | 1618.00 | 2615.00 |
| T NW APARTMENT | 818502.78 | 212345.24 | 1030848.01 | 719263.02 | 1750111.03 | 818502.78 | 0.00 | 7142.00 | 1618.00 | 0.00 |
| T SE APARTMENT | 818502.78 | 217235.59 | 1035738.36 | 719263.02 | 1755001.38 | 818502.78 | 0.00 | 7142.00 | 1618.00 | 2615.00 |
| T NE APARTMENT | 818502.78 | 213148.92 | 1031651.70 | 719263.02 | 1750914.72 | 818502.78 | 0.00 | 7142.00 | 1618.00 | 0.00 |
| T N1 APARTMENT | 818502.78 | 212364.83 | 1030867.61 | 433841.19 | 1464708.80 | 818502.78 | 0.00 | 7142.00 | 1618.00 | 0.00 |
| T N2 APARTMENT | 818502.78 | 212432.03 | 1030934.81 | 433841.19 | 1464776.00 | 818502.78 | 0.00 | 7142.00 | 1618.00 | 0.00 |
| T S1 APARTMENT | 818502.78 | 217178.42 | 1035681.19 | 433841.19 | 1469522.39 | 818502.78 | 0.00 | 7142.00 | 1618.00 | 2615.00 |
| T S2 APARTMENT | 818502.78 | 217213.03 | 1035715.81 | 433841.19 | 1469557.00 | 818502.78 | 0.00 | 7142.00 | 1618.00 | 2615.00 |
| Total Facility | 39671342.50 | 5706956.58 | 45378299.08 | 14012553.67 | 59390852.75 | 39671342.50 | 0.00 | 8760.00 | 1645.67 | 8760.00 |
| Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
| G SW APARTMENT | 0.0260 | 0.0035 | 0.0294 | 0.0114 | 0.0409 | 0.0260 | 0.00 | 5289.50 | 855.50 |
| G NW APARTMENT | 0.0260 | 0.0046 | 0.0306 | 0.0120 | 0.0426 | 0.0260 | 0.00 | 7157.00 | 1603.00 |
| OFFICE | 0.0381 | 0.0000 | 0.0381 | 0.0129 | 0.0510 | 0.0381 | 0.00 | 1750.00 | 0.00 |
| G NE APARTMENT | 0.0260 | 0.0046 | 0.0306 | 0.0120 | 0.0426 | 0.0260 | 0.00 | 7157.00 | 1603.00 |
| G N1 APARTMENT | 0.0260 | 0.0046 | 0.0306 | 0.0072 | 0.0378 | 0.0260 | 0.00 | 7157.00 | 1603.00 |
| G N2 APARTMENT | 0.0260 | 0.0046 | 0.0306 | 0.0072 | 0.0378 | 0.0260 | 0.00 | 7157.00 | 1603.00 |
| G S1 APARTMENT | 0.0260 | 0.0035 | 0.0295 | 0.0069 | 0.0363 | 0.0260 | 0.00 | 5289.50 | 855.50 |
| G S2 APARTMENT | 0.0260 | 0.0035 | 0.0295 | 0.0069 | 0.0364 | 0.0260 | 0.00 | 5289.50 | 855.50 |
| M SW APARTMENT | 0.0519 | 0.0042 | 0.0562 | 0.0164 | 0.0726 | 0.0519 | 0.00 | 5266.17 | 878.83 |
| M NW APARTMENT | 0.0519 | 0.0058 | 0.0577 | 0.0172 | 0.0749 | 0.0519 | 0.00 | 7117.33 | 1642.67 |
| M SE APARTMENT | 0.0519 | 0.0042 | 0.0562 | 0.0164 | 0.0726 | 0.0519 | 0.00 | 5266.17 | 878.83 |
| M NE APARTMENT | 0.0519 | 0.0058 | 0.0577 | 0.0172 | 0.0749 | 0.0519 | 0.00 | 7117.33 | 1642.67 |
| M N1 APARTMENT | 0.0519 | 0.0058 | 0.0577 | 0.0104 | 0.0681 | 0.0519 | 0.00 | 7117.33 | 1642.67 |
| M N2 APARTMENT | 0.0519 | 0.0058 | 0.0577 | 0.0104 | 0.0681 | 0.0519 | 0.00 | 7117.33 | 1642.67 |
| M S1 APARTMENT | 0.0519 | 0.0042 | 0.0562 | 0.0099 | 0.0661 | 0.0519 | 0.00 | 5266.17 | 878.83 |
| M S2 APARTMENT | 0.0519 | 0.0042 | 0.0562 | 0.0099 | 0.0661 | 0.0519 | 0.00 | 5266.17 | 878.83 |
| T SW APARTMENT | 0.0260 | 0.0049 | 0.0308 | 0.0217 | 0.0526 | 0.0260 | 0.00 | 5276.67 | 868.33 |
| T NW APARTMENT | 0.0260 | 0.0067 | 0.0327 | 0.0228 | 0.0555 | 0.0260 | 0.00 | 7142.00 | 1618.00 |
| T SE APARTMENT | 0.0260 | 0.0049 | 0.0309 | 0.0217 | 0.0526 | 0.0260 | 0.00 | 5276.67 | 868.33 |
| T NE APARTMENT | 0.0260 | 0.0068 | 0.0327 | 0.0228 | 0.0555 | 0.0260 | 0.00 | 7142.00 | 1618.00 |
| T N1 APARTMENT | 0.0260 | 0.0067 | 0.0327 | 0.0138 | 0.0464 | 0.0260 | 0.00 | 7142.00 | 1618.00 |
| T N2 APARTMENT | 0.0260 | 0.0067 | 0.0327 | 0.0138 | 0.0464 | 0.0260 | 0.00 | 7142.00 | 1618.00 |
| T S1 APARTMENT | 0.0260 | 0.0049 | 0.0309 | 0.0131 | 0.0440 | 0.0260 | 0.00 | 5276.67 | 868.33 |
| T S2 APARTMENT | 0.0260 | 0.0049 | 0.0309 | 0.0131 | 0.0440 | 0.0260 | 0.00 | 5276.67 | 868.33 |
| Total Facility | 1.2580 | 0.1558 | 1.4138 | 0.4351 | 1.8490 | 1.2580 | 0.00 | 8760.00 | 1645.67 |
| Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
| SPLIT GSW | 0.00 | 150278.96 | 150278.96 | 818502.78 | 7964.17 | 45.42 | 750.42 | 747.50 |
| SPLIT GNW | 0.00 | 145132.85 | 145132.85 | 818502.78 | 8093.26 | 46.31 | 620.43 | 0.00 |
| SPLIT OFFICE | 1310621.64 | 0.00 | 1310621.64 | 1201711.97 | 0.00 | 0.00 | 8760.00 | 7010.00 |
| SPLIT GNE | 0.00 | 145358.21 | 145358.21 | 818502.78 | 8084.08 | 42.92 | 633.00 | 0.00 |
| SPLIT GN1 | 0.00 | 145686.33 | 145686.33 | 818502.78 | 8078.17 | 43.93 | 637.90 | 0.00 |
| SPLIT GN2 | 0.00 | 145707.77 | 145707.77 | 818502.78 | 8077.58 | 44.38 | 638.04 | 0.00 |
| SPLIT GS1 | 0.00 | 151377.08 | 151377.08 | 818502.78 | 7942.58 | 43.08 | 774.33 | 747.50 |
| SPLIT GS2 | 0.00 | 151569.10 | 151569.10 | 818502.78 | 7939.25 | 43.42 | 777.33 | 747.50 |
| SPLIT MSW | 0.00 | 186226.61 | 186226.61 | 1637005.55 | 8606.67 | 13.00 | 140.33 | 763.83 |
| SPLIT MNW | 0.00 | 182464.28 | 182464.28 | 1637005.55 | 8606.00 | 8.83 | 145.17 | 0.00 |
| SPLIT MSE | 0.00 | 186334.85 | 186334.85 | 1637005.55 | 8605.67 | 13.53 | 140.81 | 763.83 |
| SPLIT MNE | 0.00 | 182693.07 | 182693.07 | 1637005.55 | 8604.50 | 9.03 | 146.47 | 0.00 |
| SPLIT MN1 | 0.00 | 182927.93 | 182927.93 | 1637005.55 | 8604.17 | 9.31 | 146.53 | 0.00 |
| SPLIT MN2 | 0.00 | 182952.22 | 182952.22 | 1637005.55 | 8604.17 | 9.31 | 146.53 | 0.00 |
| SPLIT MS1 | 0.00 | 186568.19 | 186568.19 | 1637005.55 | 8605.00 | 13.67 | 141.33 | 763.83 |
| SPLIT MS2 | 0.00 | 186573.05 | 186573.05 | 1637005.55 | 8604.83 | 13.83 | 141.33 | 763.83 |
| SPLIT TSW | 0.00 | 216447.81 | 216447.81 | 818502.78 | 7588.10 | 26.23 | 1145.67 | 749.67 |
| SPLIT TNW | 0.00 | 212345.24 | 212345.24 | 818502.78 | 7656.88 | 32.35 | 1070.77 | 0.00 |
| SPLIT TSE | 0.00 | 217235.59 | 217235.59 | 818502.78 | 7580.43 | 24.87 | 1154.70 | 749.67 |
| SPLIT TNE | 0.00 | 213148.92 | 213148.92 | 818502.78 | 7647.83 | 28.97 | 1083.19 | 0.00 |
| SPLIT TN1 | 0.00 | 212364.83 | 212364.83 | 818502.78 | 7660.01 | 29.75 | 1070.24 | 0.00 |
| SPLIT TN2 | 0.00 | 212432.03 | 212432.03 | 818502.78 | 7658.79 | 30.89 | 1070.32 | 0.00 |
| SPLIT TS1 | 0.00 | 217178.42 | 217178.42 | 818502.78 | 7581.60 | 24.39 | 1154.01 | 749.67 |
| SPLIT TS2 | 0.00 | 217213.03 | 217213.03 | 818502.78 | 7581.04 | 25.16 | 1153.80 | 749.67 |
| Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
| SPLIT GSW | 0.0000 | 0.0035 | 0.0035 | 0.0260 | 5744.42 | 23.88 | 376.71 |
| SPLIT GNW | 0.0000 | 0.0046 | 0.0046 | 0.0260 | 8093.26 | 46.31 | 620.43 |
| SPLIT OFFICE | 0.0416 | 0.0000 | 0.0416 | 0.0381 | 0.00 | 0.00 | 1750.00 |
| SPLIT GNE | 0.0000 | 0.0046 | 0.0046 | 0.0260 | 8084.08 | 42.92 | 633.00 |
| SPLIT GN1 | 0.0000 | 0.0046 | 0.0046 | 0.0260 | 8078.17 | 43.93 | 637.90 |
| SPLIT GN2 | 0.0000 | 0.0046 | 0.0046 | 0.0260 | 8077.58 | 44.38 | 638.04 |
| SPLIT GS1 | 0.0000 | 0.0035 | 0.0035 | 0.0260 | 5737.00 | 22.83 | 385.17 |
| SPLIT GS2 | 0.0000 | 0.0035 | 0.0035 | 0.0260 | 5735.50 | 23.17 | 386.33 |
| SPLIT MSW | 0.0000 | 0.0042 | 0.0042 | 0.0519 | 6090.33 | 2.67 | 52.00 |
| SPLIT MNW | 0.0000 | 0.0058 | 0.0058 | 0.0519 | 8606.00 | 8.83 | 145.17 |
| SPLIT MSE | 0.0000 | 0.0042 | 0.0042 | 0.0519 | 6090.17 | 2.83 | 52.00 |
| SPLIT MNE | 0.0000 | 0.0058 | 0.0058 | 0.0519 | 8604.50 | 9.03 | 146.47 |
| SPLIT MN1 | 0.0000 | 0.0058 | 0.0058 | 0.0519 | 8604.17 | 9.31 | 146.53 |
| SPLIT MN2 | 0.0000 | 0.0058 | 0.0058 | 0.0519 | 8604.17 | 9.31 | 146.53 |
| SPLIT MS1 | 0.0000 | 0.0042 | 0.0042 | 0.0519 | 6090.17 | 2.50 | 52.33 |
| SPLIT MS2 | 0.0000 | 0.0042 | 0.0042 | 0.0519 | 6090.17 | 2.50 | 52.33 |
| SPLIT TSW | 0.0000 | 0.0049 | 0.0049 | 0.0260 | 5537.19 | 16.26 | 591.56 |
| SPLIT TNW | 0.0000 | 0.0067 | 0.0067 | 0.0260 | 7656.88 | 32.35 | 1070.77 |
| SPLIT TSE | 0.0000 | 0.0049 | 0.0049 | 0.0260 | 5533.43 | 15.95 | 595.62 |
| SPLIT TNE | 0.0000 | 0.0068 | 0.0068 | 0.0260 | 7647.83 | 28.97 | 1083.19 |
| SPLIT TN1 | 0.0000 | 0.0067 | 0.0067 | 0.0260 | 7660.01 | 29.75 | 1070.24 |
| SPLIT TN2 | 0.0000 | 0.0067 | 0.0067 | 0.0260 | 7658.79 | 30.89 | 1070.32 |
| SPLIT TS1 | 0.0000 | 0.0049 | 0.0049 | 0.0260 | 5533.54 | 14.78 | 596.68 |
| SPLIT TS2 | 0.0000 | 0.0049 | 0.0049 | 0.0260 | 5533.37 | 15.20 | 596.43 |
| No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
| SPLIT GSW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT GNW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT OFFICE | 0.00 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT GNE | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT GN1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT GN2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT GS1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT GS2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT MSW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT MNW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT MSE | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT MNE | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT MN1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT MN2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT MS1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT MS2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT TSW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT TNW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT TSE | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT TNE | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT TN1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT TN2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT TS1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SPLIT TS2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
| SPLIT GSW | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT GNW | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT OFFICE | 0.0000 | 0.0416 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT GNE | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT GN1 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT GN2 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT GS1 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT GS2 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT MSW | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT MNW | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT MSE | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT MNE | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT MN1 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT MN2 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT MS1 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT MS2 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT TSW | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT TNW | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT TSE | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT TNE | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT TN1 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT TN2 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT TS1 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| SPLIT TS2 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 09:14:34
Surfaces by Class| Total | Outdoors | |
| Wall | 126 | 42 |
| Floor | 27 | 9 |
| Roof | 27 | 9 |
| Internal Mass | 24 | 0 |
| Building Detached Shading | 0 | 0 |
| Fixed Detached Shading | 0 | 0 |
| Window | 39 | 39 |
| Door | 0 | 0 |
| Glass Door | 0 | 0 |
| Shading | 0 | 0 |
| Overhang | 0 | 0 |
| Fin | 0 | 0 |
| Tubular Daylighting Device Dome | 0 | 0 |
| Tubular Daylighting Device Diffuser | 0 | 0 |
| Count | |
| HVAC Air Loops | 24 |
| Conditioned Zones | 24 |
| Unconditioned Zones | 3 |
| Supply Plenums | 0 |
| Return Plenums | 0 |
| Count | |
| IDF Objects | 1536 |
| Defaulted Fields | 1816 |
| Fields with Defaults | 5921 |
| Autosized Fields | 617 |
| Autosizable Fields | 759 |
| Autocalculated Fields | 331 |
| Autocalculatable Fields | 508 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 09:14:34
Annual and Peak Values - Electricity| Electricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
| Electricity:Facility | 1317.45 | 16977.05 | 16-APR-03:00 | 89997.38 | 26-JUL-17:30 |
| Electricity:Building | 557.89 | 10119.94 | 01-JAN-03:10 | 27841.36 | 01-JAN-18:10 |
| Electricity:Zone:G SW APARTMENT | 13.67 | 232.36 | 01-JAN-03:10 | 705.80 | 01-JAN-18:10 |
| Electricity:SpaceType:GENERAL | 557.89 | 10119.94 | 01-JAN-03:10 | 27841.36 | 01-JAN-18:10 |
| InteriorLights:Electricity | 99.23 | 1868.27 | 01-JAN-00:10 | 5904.43 | 01-JAN-19:10 |
| InteriorLights:Electricity:Zone:G SW APARTMENT | 1.45 | 8.68 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 |
| InteriorLights:Electricity:SpaceType:GENERAL | 99.23 | 1868.27 | 01-JAN-00:10 | 5904.43 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity | 94.96 | 1842.77 | 01-JAN-00:10 | 5496.56 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:G SW APARTMENT | 1.32 | 7.86 | 01-JAN-00:10 | 125.72 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 94.96 | 1842.77 | 01-JAN-00:10 | 5496.56 | 01-JAN-19:10 |
| Electricity:Zone:G NW APARTMENT | 13.67 | 232.36 | 01-JAN-03:10 | 705.80 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:G NW APARTMENT | 1.45 | 8.68 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:G NW APARTMENT | 1.32 | 7.86 | 01-JAN-00:10 | 125.72 | 01-JAN-19:10 |
| Electricity:Zone:OFFICE | 16.86 | 310.83 | 01-JAN-00:10 | 1171.54 | 03-JAN-08:10 |
| InteriorLights:Electricity:Zone:OFFICE | 7.40 | 116.58 | 01-JAN-00:10 | 582.92 | 03-JAN-08:10 |
| LightsWired:InteriorLights:Electricity:Zone:OFFICE | 7.40 | 116.58 | 01-JAN-00:10 | 582.92 | 03-JAN-08:10 |
| Electricity:Zone:G NE APARTMENT | 13.67 | 232.36 | 01-JAN-03:10 | 705.80 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:G NE APARTMENT | 1.45 | 8.68 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:G NE APARTMENT | 1.32 | 7.86 | 01-JAN-00:10 | 125.72 | 01-JAN-19:10 |
| Electricity:Zone:G N1 APARTMENT | 13.67 | 232.36 | 01-JAN-03:10 | 705.80 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:G N1 APARTMENT | 1.45 | 8.68 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:G N1 APARTMENT | 1.32 | 7.86 | 01-JAN-00:10 | 125.72 | 01-JAN-19:10 |
| Electricity:Zone:G N2 APARTMENT | 13.67 | 232.36 | 01-JAN-03:10 | 705.80 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:G N2 APARTMENT | 1.45 | 8.68 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:G N2 APARTMENT | 1.32 | 7.86 | 01-JAN-00:10 | 125.72 | 01-JAN-19:10 |
| Electricity:Zone:G S1 APARTMENT | 13.67 | 232.36 | 01-JAN-03:10 | 705.80 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:G S1 APARTMENT | 1.45 | 8.68 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:G S1 APARTMENT | 1.32 | 7.86 | 01-JAN-00:10 | 125.72 | 01-JAN-19:10 |
| Electricity:Zone:G S2 APARTMENT | 13.67 | 232.36 | 01-JAN-03:10 | 705.80 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:G S2 APARTMENT | 1.45 | 8.68 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:G S2 APARTMENT | 1.32 | 7.86 | 01-JAN-00:10 | 125.72 | 01-JAN-19:10 |
| Electricity:Zone:M SW APARTMENT | 27.33 | 464.72 | 01-JAN-03:10 | 1411.61 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:M SW APARTMENT | 2.91 | 17.37 | 01-JAN-00:10 | 277.76 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:M SW APARTMENT | 2.63 | 15.72 | 01-JAN-00:10 | 251.45 | 01-JAN-19:10 |
| Electricity:Zone:M NW APARTMENT | 27.33 | 464.72 | 01-JAN-03:10 | 1411.61 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:M NW APARTMENT | 2.91 | 17.37 | 01-JAN-00:10 | 277.76 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:M NW APARTMENT | 2.63 | 15.72 | 01-JAN-00:10 | 251.45 | 01-JAN-19:10 |
| Electricity:Zone:M SE APARTMENT | 27.33 | 464.72 | 01-JAN-03:10 | 1411.61 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:M SE APARTMENT | 2.91 | 17.37 | 01-JAN-00:10 | 277.76 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:M SE APARTMENT | 2.63 | 15.72 | 01-JAN-00:10 | 251.45 | 01-JAN-19:10 |
| Electricity:Zone:M NE APARTMENT | 27.33 | 464.72 | 01-JAN-03:10 | 1411.61 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:M NE APARTMENT | 2.91 | 17.37 | 01-JAN-00:10 | 277.76 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:M NE APARTMENT | 2.63 | 15.72 | 01-JAN-00:10 | 251.45 | 01-JAN-19:10 |
| Electricity:Zone:M N1 APARTMENT | 27.33 | 464.72 | 01-JAN-03:10 | 1411.61 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:M N1 APARTMENT | 2.91 | 17.37 | 01-JAN-00:10 | 277.76 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:M N1 APARTMENT | 2.63 | 15.72 | 01-JAN-00:10 | 251.45 | 01-JAN-19:10 |
| Electricity:Zone:M N2 APARTMENT | 27.33 | 464.72 | 01-JAN-03:10 | 1411.61 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:M N2 APARTMENT | 2.91 | 17.37 | 01-JAN-00:10 | 277.76 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:M N2 APARTMENT | 2.63 | 15.72 | 01-JAN-00:10 | 251.45 | 01-JAN-19:10 |
| Electricity:Zone:M S1 APARTMENT | 27.33 | 464.72 | 01-JAN-03:10 | 1411.61 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:M S1 APARTMENT | 2.91 | 17.37 | 01-JAN-00:10 | 277.76 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:M S1 APARTMENT | 2.63 | 15.72 | 01-JAN-00:10 | 251.45 | 01-JAN-19:10 |
| Electricity:Zone:M S2 APARTMENT | 27.33 | 464.72 | 01-JAN-03:10 | 1411.61 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:M S2 APARTMENT | 2.91 | 17.37 | 01-JAN-00:10 | 277.76 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:M S2 APARTMENT | 2.63 | 15.72 | 01-JAN-00:10 | 251.45 | 01-JAN-19:10 |
| Electricity:Zone:T SW APARTMENT | 13.67 | 232.36 | 01-JAN-03:10 | 705.80 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:T SW APARTMENT | 1.45 | 8.68 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:T SW APARTMENT | 1.32 | 7.86 | 01-JAN-00:10 | 125.72 | 01-JAN-19:10 |
| Electricity:Zone:T NW APARTMENT | 13.67 | 232.36 | 01-JAN-03:10 | 705.80 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:T NW APARTMENT | 1.45 | 8.68 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:T NW APARTMENT | 1.32 | 7.86 | 01-JAN-00:10 | 125.72 | 01-JAN-19:10 |
| Electricity:Zone:T SE APARTMENT | 13.67 | 232.36 | 01-JAN-03:10 | 705.80 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:T SE APARTMENT | 1.45 | 8.68 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:T SE APARTMENT | 1.32 | 7.86 | 01-JAN-00:10 | 125.72 | 01-JAN-19:10 |
| Electricity:Zone:T NE APARTMENT | 13.67 | 232.36 | 01-JAN-03:10 | 705.80 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:T NE APARTMENT | 1.45 | 8.68 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:T NE APARTMENT | 1.32 | 7.86 | 01-JAN-00:10 | 125.72 | 01-JAN-19:10 |
| Electricity:Zone:T N1 APARTMENT | 13.67 | 232.36 | 01-JAN-03:10 | 705.80 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:T N1 APARTMENT | 1.45 | 8.68 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:T N1 APARTMENT | 1.32 | 7.86 | 01-JAN-00:10 | 125.72 | 01-JAN-19:10 |
| Electricity:Zone:T N2 APARTMENT | 13.67 | 232.36 | 01-JAN-03:10 | 705.80 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:T N2 APARTMENT | 1.45 | 8.68 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:T N2 APARTMENT | 1.32 | 7.86 | 01-JAN-00:10 | 125.72 | 01-JAN-19:10 |
| Electricity:Zone:T S1 APARTMENT | 13.67 | 232.36 | 01-JAN-03:10 | 705.80 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:T S1 APARTMENT | 1.45 | 8.68 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:T S1 APARTMENT | 1.32 | 7.86 | 01-JAN-00:10 | 125.72 | 01-JAN-19:10 |
| Electricity:Zone:T S2 APARTMENT | 13.67 | 232.36 | 01-JAN-03:10 | 705.80 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:T S2 APARTMENT | 1.45 | 8.68 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:T S2 APARTMENT | 1.32 | 7.86 | 01-JAN-00:10 | 125.72 | 01-JAN-19:10 |
| Electricity:Zone:G CORRIDOR | 82.28 | 1494.09 | 01-JAN-00:10 | 4538.70 | 01-JAN-07:10 |
| InteriorLights:Electricity:Zone:G CORRIDOR | 11.69 | 370.63 | 01-JAN-00:10 | 370.63 | 01-JAN-00:10 |
| LightsWired:InteriorLights:Electricity:Zone:G CORRIDOR | 11.69 | 370.63 | 01-JAN-00:10 | 370.63 | 01-JAN-00:10 |
| Electricity:Zone:M CORRIDOR | 23.38 | 741.26 | 01-JAN-00:10 | 741.26 | 01-JAN-00:10 |
| InteriorLights:Electricity:Zone:M CORRIDOR | 23.38 | 741.26 | 01-JAN-00:10 | 741.26 | 01-JAN-00:10 |
| LightsWired:InteriorLights:Electricity:Zone:M CORRIDOR | 23.38 | 741.26 | 01-JAN-00:10 | 741.26 | 01-JAN-00:10 |
| Electricity:Zone:T CORRIDOR | 11.69 | 370.63 | 01-JAN-00:10 | 370.63 | 01-JAN-00:10 |
| InteriorLights:Electricity:Zone:T CORRIDOR | 11.69 | 370.63 | 01-JAN-00:10 | 370.63 | 01-JAN-00:10 |
| LightsWired:InteriorLights:Electricity:Zone:T CORRIDOR | 11.69 | 370.63 | 01-JAN-00:10 | 370.63 | 01-JAN-00:10 |
| LightsPlugIn:InteriorLights:Electricity | 4.27 | 25.50 | 01-JAN-00:10 | 407.87 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:G SW APARTMENT | 0.14 | 0.82 | 01-JAN-00:10 | 13.16 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:SpaceType:GENERAL | 4.27 | 25.50 | 01-JAN-00:10 | 407.87 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:G NW APARTMENT | 0.14 | 0.82 | 01-JAN-00:10 | 13.16 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:G NE APARTMENT | 0.14 | 0.82 | 01-JAN-00:10 | 13.16 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:G N1 APARTMENT | 0.14 | 0.82 | 01-JAN-00:10 | 13.16 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:G N2 APARTMENT | 0.14 | 0.82 | 01-JAN-00:10 | 13.16 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:G S1 APARTMENT | 0.14 | 0.82 | 01-JAN-00:10 | 13.16 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:G S2 APARTMENT | 0.14 | 0.82 | 01-JAN-00:10 | 13.16 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:M SW APARTMENT | 0.28 | 1.65 | 01-JAN-00:10 | 26.31 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:M NW APARTMENT | 0.28 | 1.65 | 01-JAN-00:10 | 26.31 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:M SE APARTMENT | 0.28 | 1.65 | 01-JAN-00:10 | 26.31 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:M NE APARTMENT | 0.28 | 1.65 | 01-JAN-00:10 | 26.31 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:M N1 APARTMENT | 0.28 | 1.65 | 01-JAN-00:10 | 26.31 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:M N2 APARTMENT | 0.28 | 1.65 | 01-JAN-00:10 | 26.31 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:M S1 APARTMENT | 0.28 | 1.65 | 01-JAN-00:10 | 26.31 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:M S2 APARTMENT | 0.28 | 1.65 | 01-JAN-00:10 | 26.31 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:T SW APARTMENT | 0.14 | 0.82 | 01-JAN-00:10 | 13.16 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:T NW APARTMENT | 0.14 | 0.82 | 01-JAN-00:10 | 13.16 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:T SE APARTMENT | 0.14 | 0.82 | 01-JAN-00:10 | 13.16 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:T NE APARTMENT | 0.14 | 0.82 | 01-JAN-00:10 | 13.16 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:T N1 APARTMENT | 0.14 | 0.82 | 01-JAN-00:10 | 13.16 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:T N2 APARTMENT | 0.14 | 0.82 | 01-JAN-00:10 | 13.16 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:T S1 APARTMENT | 0.14 | 0.82 | 01-JAN-00:10 | 13.16 | 01-JAN-19:10 |
| LightsPlugIn:InteriorLights:Electricity:Zone:T S2 APARTMENT | 0.14 | 0.82 | 01-JAN-00:10 | 13.16 | 01-JAN-19:10 |
| InteriorEquipment:Electricity | 458.66 | 8251.68 | 01-JAN-03:10 | 22709.69 | 03-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:G SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:SpaceType:GENERAL | 458.66 | 8251.68 | 01-JAN-03:10 | 22709.69 | 03-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity | 388.06 | 7128.22 | 01-JAN-03:10 | 18541.61 | 03-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:G SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 388.06 | 7128.22 | 01-JAN-03:10 | 18541.61 | 03-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:G NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:G NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:OFFICE | 9.47 | 194.25 | 01-JAN-00:10 | 588.62 | 03-JAN-08:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:OFFICE | 9.47 | 194.25 | 01-JAN-00:10 | 588.62 | 03-JAN-08:10 |
| InteriorEquipment:Electricity:Zone:G NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:G NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:G N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:G N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:G N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:G N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:G S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:G S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:G S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:G S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:M SW APARTMENT | 24.43 | 447.35 | 01-JAN-03:10 | 1177.25 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:M SW APARTMENT | 24.43 | 447.35 | 01-JAN-03:10 | 1177.25 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:M NW APARTMENT | 24.43 | 447.35 | 01-JAN-03:10 | 1177.25 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:M NW APARTMENT | 24.43 | 447.35 | 01-JAN-03:10 | 1177.25 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:M SE APARTMENT | 24.43 | 447.35 | 01-JAN-03:10 | 1177.25 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:M SE APARTMENT | 24.43 | 447.35 | 01-JAN-03:10 | 1177.25 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:M NE APARTMENT | 24.43 | 447.35 | 01-JAN-03:10 | 1177.25 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:M NE APARTMENT | 24.43 | 447.35 | 01-JAN-03:10 | 1177.25 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:M N1 APARTMENT | 24.43 | 447.35 | 01-JAN-03:10 | 1177.25 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:M N1 APARTMENT | 24.43 | 447.35 | 01-JAN-03:10 | 1177.25 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:M N2 APARTMENT | 24.43 | 447.35 | 01-JAN-03:10 | 1177.25 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:M N2 APARTMENT | 24.43 | 447.35 | 01-JAN-03:10 | 1177.25 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:M S1 APARTMENT | 24.43 | 447.35 | 01-JAN-03:10 | 1177.25 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:M S1 APARTMENT | 24.43 | 447.35 | 01-JAN-03:10 | 1177.25 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:M S2 APARTMENT | 24.43 | 447.35 | 01-JAN-03:10 | 1177.25 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:M S2 APARTMENT | 24.43 | 447.35 | 01-JAN-03:10 | 1177.25 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:T SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:T SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:T NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:T NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:T SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:T SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:T NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:T NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:T N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:T N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:T N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:T N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:T S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:T S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:T S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:T S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:10 | 588.62 | 01-JAN-17:10 |
| InteriorEquipment:Electricity:Zone:G CORRIDOR | 70.59 | 1123.46 | 01-JAN-00:10 | 4168.07 | 01-JAN-07:10 |
| ElevatorLift:InteriorEquipment:Electricity | 65.48 | 961.46 | 01-JAN-00:10 | 4006.07 | 01-JAN-07:10 |
| ElevatorLift:InteriorEquipment:Electricity:Zone:G CORRIDOR | 65.48 | 961.46 | 01-JAN-00:10 | 4006.07 | 01-JAN-07:10 |
| ElevatorLift:InteriorEquipment:Electricity:SpaceType:GENERAL | 65.48 | 961.46 | 01-JAN-00:10 | 4006.07 | 01-JAN-07:10 |
| ElevatorLightsFan:InteriorEquipment:Electricity | 5.11 | 162.00 | 01-JAN-00:10 | 162.00 | 01-JAN-00:10 |
| ElevatorLightsFan:InteriorEquipment:Electricity:Zone:G CORRIDOR | 5.11 | 162.00 | 01-JAN-00:10 | 162.00 | 01-JAN-00:10 |
| ElevatorLightsFan:InteriorEquipment:Electricity:SpaceType:GENERAL | 5.11 | 162.00 | 01-JAN-00:10 | 162.00 | 01-JAN-00:10 |
| Fans:Electricity | 112.97 | 1723.78 | 14-FEB-16:00 | 9845.83 | 15-JUN-17:00 |
| Fans:Electricity:Zone:G SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:G SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:G NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:G NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:G NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:G NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:G N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:G N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:G N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:G N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:G S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:G S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:G S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:G S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:M SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:M SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:M NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:M NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:M SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:M SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:M NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:M NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:M N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:M N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:M N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:M N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:M S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:M S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:M S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:M S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:T SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:T SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:T NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:T NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:T SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:T SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:T NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:T NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:T N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:T N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:T N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:T N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:T S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:T S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:T S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:T S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| ElectricityPurchased:Facility | 1317.45 | 16977.05 | 16-APR-03:00 | 89997.38 | 26-JUL-17:30 |
| ElectricityPurchased:Plant | 1317.45 | 16977.05 | 16-APR-03:00 | 89997.38 | 26-JUL-17:30 |
| Cogeneration:ElectricityPurchased | 1317.45 | 16977.05 | 16-APR-03:00 | 89997.38 | 26-JUL-17:30 |
| General:Cogeneration:ElectricityPurchased | 1317.45 | 16977.05 | 16-APR-03:00 | 89997.38 | 26-JUL-17:30 |
| ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| ElectricityNet:Facility | 1317.45 | 16977.05 | 16-APR-03:00 | 89997.38 | 26-JUL-17:30 |
| ElectricityNet:Plant | 1317.45 | 16977.05 | 16-APR-03:00 | 89997.38 | 26-JUL-17:30 |
| Cogeneration:ElectricityNet | 1317.45 | 16977.05 | 16-APR-03:00 | 89997.38 | 26-JUL-17:30 |
| General:Cogeneration:ElectricityNet | 1317.45 | 16977.05 | 16-APR-03:00 | 89997.38 | 26-JUL-17:30 |
| Electricity:HVAC | 300.59 | 1723.78 | 03-JAN-18:50 | 37887.92 | 15-JUN-17:00 |
| HeatRecovery:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:HeatRecovery:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:Fans:Electricity | 112.97 | 1723.78 | 14-FEB-16:00 | 9845.83 | 15-JUN-17:00 |
| Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Cooling:Electricity | 187.62 | 0.00 | 01-JAN-00:10 | 28167.44 | 05-JUN-17:00 |
| General:Cooling:Electricity | 187.62 | 0.00 | 01-JAN-00:10 | 28167.44 | 05-JUN-17:00 |
| ExteriorLights:Electricity | 50.06 | 0.00 | 01-JAN-07:20 | 3183.33 | 01-JAN-00:10 |
| General:ExteriorLights:Electricity | 50.06 | 0.00 | 01-JAN-07:20 | 3183.33 | 01-JAN-00:10 |
| Electricity:Plant | 408.91 | 1950.00 | 01-JAN-00:10 | 37509.09 | 01-JAN-07:50 |
| WaterSystems:Electricity | 408.91 | 1950.00 | 01-JAN-00:10 | 37509.09 | 01-JAN-07:50 |
| Water Heater:WaterSystems:Electricity | 408.91 | 1950.00 | 01-JAN-00:10 | 37509.09 | 01-JAN-07:50 |
| Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
| NaturalGas:Facility | 100.67 | 0.00 | 01-JAN-12:50 | 52342.16 | 28-JAN-06:00 |
| NaturalGas:HVAC | 100.67 | 0.00 | 01-JAN-12:50 | 52342.16 | 28-JAN-06:00 |
| Heating:NaturalGas | 100.67 | 0.00 | 01-JAN-12:50 | 52342.16 | 28-JAN-06:00 |
| General:Heating:NaturalGas | 100.67 | 0.00 | 01-JAN-12:50 | 52342.16 | 28-JAN-06:00 |
| Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
| None |
| Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
| Water:Facility | 1875.32 | 0.00 | 01-JAN-02:10 | 0.00 | 01-JAN-07:10 |
| Water:Plant | 1875.32 | 0.00 | 01-JAN-02:10 | 0.00 | 01-JAN-07:10 |
| WaterSystems:Water | 1875.32 | 0.00 | 01-JAN-02:10 | 0.00 | 01-JAN-07:10 |
| Water Heater:WaterSystems:Water | 1875.32 | 0.00 | 01-JAN-02:10 | 0.00 | 01-JAN-07:10 |
| MainsWater:Facility | 1875.32 | 0.00 | 01-JAN-02:10 | 0.00 | 01-JAN-07:10 |
| MainsWater:Plant | 1875.32 | 0.00 | 01-JAN-02:10 | 0.00 | 01-JAN-07:10 |
| WaterSystems:MainsWater | 1875.32 | 0.00 | 01-JAN-02:10 | 0.00 | 01-JAN-07:10 |
| Water Heater:WaterSystems:MainsWater | 1875.32 | 0.00 | 01-JAN-02:10 | 0.00 | 01-JAN-07:10 |
| Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
| Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
| CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
| Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
| None |
| Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
| None |
| Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
| EnergyTransfer:Facility | 1474.65 | 1465.36 | 03-MAR-14:30 | 166054.04 | 15-JUN-17:00 |
| EnergyTransfer:Building | 696.70 | 1303.27 | 03-MAR-17:00 | 72591.85 | 15-JUN-17:00 |
| EnergyTransfer:Zone:G SW APARTMENT | 21.28 | 0.08 | 06-MAR-14:30 | 2384.45 | 19-SEP-16:10 |
| Heating:EnergyTransfer | 39.14 | 0.00 | 01-JAN-19:20 | 24666.76 | 28-JAN-06:00 |
| Heating:EnergyTransfer:Zone:G SW APARTMENT | 0.20 | 0.00 | 01-JAN-00:10 | 660.20 | 26-JAN-00:10 |
| General:Heating:EnergyTransfer | 39.14 | 0.00 | 01-JAN-19:20 | 24666.76 | 28-JAN-06:00 |
| General:Heating:EnergyTransfer:Zone:G SW APARTMENT | 0.20 | 0.00 | 01-JAN-00:10 | 660.20 | 26-JAN-00:10 |
| Cooling:EnergyTransfer | 657.56 | 166.56 | 26-JAN-01:00 | 72591.85 | 15-JUN-17:00 |
| Cooling:EnergyTransfer:Zone:G SW APARTMENT | 21.07 | 0.00 | 06-JAN-07:00 | 2384.45 | 19-SEP-16:10 |
| General:Cooling:EnergyTransfer | 657.56 | 166.56 | 26-JAN-01:00 | 72591.85 | 15-JUN-17:00 |
| General:Cooling:EnergyTransfer:Zone:G SW APARTMENT | 21.07 | 0.00 | 06-JAN-07:00 | 2384.45 | 19-SEP-16:10 |
| EnergyTransfer:Zone:G NW APARTMENT | 17.79 | 0.00 | 25-MAR-16:50 | 2287.65 | 15-JUN-17:10 |
| Heating:EnergyTransfer:Zone:G NW APARTMENT | 1.31 | 0.00 | 01-JAN-08:30 | 1019.29 | 09-FEB-01:00 |
| General:Heating:EnergyTransfer:Zone:G NW APARTMENT | 1.31 | 0.00 | 01-JAN-08:30 | 1019.29 | 09-FEB-01:00 |
| Cooling:EnergyTransfer:Zone:G NW APARTMENT | 16.48 | 0.00 | 01-JAN-00:10 | 2287.65 | 15-JUN-17:10 |
| General:Cooling:EnergyTransfer:Zone:G NW APARTMENT | 16.48 | 0.00 | 01-JAN-00:10 | 2287.65 | 15-JUN-17:10 |
| EnergyTransfer:Zone:OFFICE | 18.03 | 0.00 | 02-MAR-14:40 | 4328.81 | 07-AUG-08:10 |
| Heating:EnergyTransfer:Zone:OFFICE | 3.62 | 0.00 | 01-JAN-00:10 | 895.77 | 02-MAR-08:10 |
| General:Heating:EnergyTransfer:Zone:OFFICE | 3.62 | 0.00 | 01-JAN-00:10 | 895.77 | 02-MAR-08:10 |
| Cooling:EnergyTransfer:Zone:OFFICE | 14.41 | 0.00 | 01-JAN-11:00 | 4328.81 | 07-AUG-08:10 |
| General:Cooling:EnergyTransfer:Zone:OFFICE | 14.41 | 0.00 | 01-JAN-11:00 | 4328.81 | 07-AUG-08:10 |
| EnergyTransfer:Zone:G NE APARTMENT | 17.82 | 0.00 | 16-MAR-15:30 | 1984.57 | 03-JUL-17:00 |
| Heating:EnergyTransfer:Zone:G NE APARTMENT | 1.24 | 0.00 | 01-JAN-08:30 | 1014.35 | 09-FEB-01:00 |
| General:Heating:EnergyTransfer:Zone:G NE APARTMENT | 1.24 | 0.00 | 01-JAN-08:30 | 1014.35 | 09-FEB-01:00 |
| Cooling:EnergyTransfer:Zone:G NE APARTMENT | 16.58 | 0.00 | 01-JAN-00:10 | 1984.57 | 03-JUL-17:00 |
| General:Cooling:EnergyTransfer:Zone:G NE APARTMENT | 16.58 | 0.00 | 01-JAN-00:10 | 1984.57 | 03-JUL-17:00 |
| EnergyTransfer:Zone:G N1 APARTMENT | 15.12 | 0.01 | 23-FEB-13:40 | 1578.65 | 07-AUG-18:00 |
| Heating:EnergyTransfer:Zone:G N1 APARTMENT | 0.22 | 0.00 | 01-JAN-00:10 | 421.60 | 09-FEB-01:10 |
| General:Heating:EnergyTransfer:Zone:G N1 APARTMENT | 0.22 | 0.00 | 01-JAN-00:10 | 421.60 | 09-FEB-01:10 |
| Cooling:EnergyTransfer:Zone:G N1 APARTMENT | 14.90 | 0.00 | 03-JAN-07:00 | 1578.65 | 07-AUG-18:00 |
| General:Cooling:EnergyTransfer:Zone:G N1 APARTMENT | 14.90 | 0.00 | 03-JAN-07:00 | 1578.65 | 07-AUG-18:00 |
| EnergyTransfer:Zone:G N2 APARTMENT | 15.13 | 0.02 | 03-FEB-15:40 | 1572.89 | 07-AUG-18:00 |
| Heating:EnergyTransfer:Zone:G N2 APARTMENT | 0.22 | 0.00 | 01-JAN-00:10 | 420.96 | 09-FEB-01:00 |
| General:Heating:EnergyTransfer:Zone:G N2 APARTMENT | 0.22 | 0.00 | 01-JAN-00:10 | 420.96 | 09-FEB-01:00 |
| Cooling:EnergyTransfer:Zone:G N2 APARTMENT | 14.91 | 0.00 | 02-JAN-06:00 | 1572.89 | 07-AUG-18:00 |
| General:Cooling:EnergyTransfer:Zone:G N2 APARTMENT | 14.91 | 0.00 | 02-JAN-06:00 | 1572.89 | 07-AUG-18:00 |
| EnergyTransfer:Zone:G S1 APARTMENT | 20.17 | 0.22 | 02-MAR-05:30 | 1754.34 | 19-SEP-14:10 |
| Heating:EnergyTransfer:Zone:G S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 78.72 | 26-JAN-00:10 |
| General:Heating:EnergyTransfer:Zone:G S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 78.72 | 26-JAN-00:10 |
| Cooling:EnergyTransfer:Zone:G S1 APARTMENT | 20.17 | 0.00 | 25-JAN-23:10 | 1754.34 | 19-SEP-14:10 |
| General:Cooling:EnergyTransfer:Zone:G S1 APARTMENT | 20.17 | 0.00 | 25-JAN-23:10 | 1754.34 | 19-SEP-14:10 |
| EnergyTransfer:Zone:G S2 APARTMENT | 21.84 | 0.10 | 02-MAR-05:40 | 1844.85 | 19-SEP-14:10 |
| Heating:EnergyTransfer:Zone:G S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 58.41 | 26-JAN-00:20 |
| General:Heating:EnergyTransfer:Zone:G S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 58.41 | 26-JAN-00:20 |
| Cooling:EnergyTransfer:Zone:G S2 APARTMENT | 21.84 | 0.00 | 25-JAN-23:20 | 1844.85 | 19-SEP-14:10 |
| General:Cooling:EnergyTransfer:Zone:G S2 APARTMENT | 21.84 | 0.00 | 25-JAN-23:20 | 1844.85 | 19-SEP-14:10 |
| EnergyTransfer:Zone:M SW APARTMENT | 51.44 | 0.02 | 27-NOV-01:20 | 5612.42 | 15-JUN-17:00 |
| Heating:EnergyTransfer:Zone:M SW APARTMENT | 0.25 | 0.00 | 01-JAN-00:10 | 1681.57 | 26-JAN-00:10 |
| General:Heating:EnergyTransfer:Zone:M SW APARTMENT | 0.25 | 0.00 | 01-JAN-00:10 | 1681.57 | 26-JAN-00:10 |
| Cooling:EnergyTransfer:Zone:M SW APARTMENT | 51.18 | 0.00 | 06-JAN-06:50 | 5612.42 | 15-JUN-17:00 |
| General:Cooling:EnergyTransfer:Zone:M SW APARTMENT | 51.18 | 0.00 | 06-JAN-06:50 | 5612.42 | 15-JUN-17:00 |
| EnergyTransfer:Zone:M NW APARTMENT | 42.27 | 0.11 | 14-JAN-14:00 | 5818.41 | 15-JUN-17:00 |
| Heating:EnergyTransfer:Zone:M NW APARTMENT | 1.77 | 0.00 | 01-JAN-00:10 | 1942.54 | 26-JAN-00:10 |
| General:Heating:EnergyTransfer:Zone:M NW APARTMENT | 1.77 | 0.00 | 01-JAN-00:10 | 1942.54 | 26-JAN-00:10 |
| Cooling:EnergyTransfer:Zone:M NW APARTMENT | 40.49 | 0.00 | 02-JAN-05:30 | 5818.41 | 15-JUN-17:00 |
| General:Cooling:EnergyTransfer:Zone:M NW APARTMENT | 40.49 | 0.00 | 02-JAN-05:30 | 5818.41 | 15-JUN-17:00 |
| EnergyTransfer:Zone:M SE APARTMENT | 51.69 | 0.01 | 30-NOV-03:10 | 4653.26 | 05-JUN-17:00 |
| Heating:EnergyTransfer:Zone:M SE APARTMENT | 0.26 | 0.00 | 01-JAN-00:10 | 1656.67 | 26-JAN-00:10 |
| General:Heating:EnergyTransfer:Zone:M SE APARTMENT | 0.26 | 0.00 | 01-JAN-00:10 | 1656.67 | 26-JAN-00:10 |
| Cooling:EnergyTransfer:Zone:M SE APARTMENT | 51.43 | 0.00 | 06-JAN-06:50 | 4653.26 | 05-JUN-17:00 |
| General:Cooling:EnergyTransfer:Zone:M SE APARTMENT | 51.43 | 0.00 | 06-JAN-06:50 | 4653.26 | 05-JUN-17:00 |
| EnergyTransfer:Zone:M NE APARTMENT | 42.45 | 0.05 | 04-JAN-05:50 | 4817.15 | 15-JUN-17:00 |
| Heating:EnergyTransfer:Zone:M NE APARTMENT | 1.70 | 0.00 | 01-JAN-00:10 | 1982.65 | 28-JAN-06:00 |
| General:Heating:EnergyTransfer:Zone:M NE APARTMENT | 1.70 | 0.00 | 01-JAN-00:10 | 1982.65 | 28-JAN-06:00 |
| Cooling:EnergyTransfer:Zone:M NE APARTMENT | 40.75 | 0.00 | 01-JAN-03:50 | 4817.15 | 15-JUN-17:00 |
| General:Cooling:EnergyTransfer:Zone:M NE APARTMENT | 40.75 | 0.00 | 01-JAN-03:50 | 4817.15 | 15-JUN-17:00 |
| EnergyTransfer:Zone:M N1 APARTMENT | 35.76 | 0.25 | 31-MAR-12:20 | 3612.46 | 15-JUN-17:10 |
| Heating:EnergyTransfer:Zone:M N1 APARTMENT | 0.17 | 0.00 | 01-JAN-00:10 | 777.12 | 28-JAN-06:00 |
| General:Heating:EnergyTransfer:Zone:M N1 APARTMENT | 0.17 | 0.00 | 01-JAN-00:10 | 777.12 | 28-JAN-06:00 |
| Cooling:EnergyTransfer:Zone:M N1 APARTMENT | 35.59 | 0.00 | 05-JAN-04:30 | 3612.46 | 15-JUN-17:10 |
| General:Cooling:EnergyTransfer:Zone:M N1 APARTMENT | 35.59 | 0.00 | 05-JAN-04:30 | 3612.46 | 15-JUN-17:10 |
| EnergyTransfer:Zone:M N2 APARTMENT | 35.78 | 0.01 | 26-DEC-00:30 | 3599.68 | 15-JUN-17:10 |
| Heating:EnergyTransfer:Zone:M N2 APARTMENT | 0.17 | 0.00 | 01-JAN-00:10 | 781.09 | 28-JAN-06:00 |
| General:Heating:EnergyTransfer:Zone:M N2 APARTMENT | 0.17 | 0.00 | 01-JAN-00:10 | 781.09 | 28-JAN-06:00 |
| Cooling:EnergyTransfer:Zone:M N2 APARTMENT | 35.62 | 0.00 | 05-JAN-04:30 | 3599.68 | 15-JUN-17:10 |
| General:Cooling:EnergyTransfer:Zone:M N2 APARTMENT | 35.62 | 0.00 | 05-JAN-04:30 | 3599.68 | 15-JUN-17:10 |
| EnergyTransfer:Zone:M S1 APARTMENT | 47.07 | 5.85 | 27-DEC-01:10 | 3740.11 | 19-SEP-14:10 |
| Heating:EnergyTransfer:Zone:M S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 173.95 | 27-DEC-06:00 |
| General:Heating:EnergyTransfer:Zone:M S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 173.95 | 27-DEC-06:00 |
| Cooling:EnergyTransfer:Zone:M S1 APARTMENT | 47.07 | 0.00 | 26-JAN-07:00 | 3740.11 | 19-SEP-14:10 |
| General:Cooling:EnergyTransfer:Zone:M S1 APARTMENT | 47.07 | 0.00 | 26-JAN-07:00 | 3740.11 | 19-SEP-14:10 |
| EnergyTransfer:Zone:M S2 APARTMENT | 47.12 | 6.09 | 27-DEC-02:10 | 3744.75 | 19-SEP-14:10 |
| Heating:EnergyTransfer:Zone:M S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 173.37 | 27-DEC-06:00 |
| General:Heating:EnergyTransfer:Zone:M S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:10 | 173.37 | 27-DEC-06:00 |
| Cooling:EnergyTransfer:Zone:M S2 APARTMENT | 47.12 | 0.00 | 26-JAN-07:00 | 3744.75 | 19-SEP-14:10 |
| General:Cooling:EnergyTransfer:Zone:M S2 APARTMENT | 47.12 | 0.00 | 26-JAN-07:00 | 3744.75 | 19-SEP-14:10 |
| EnergyTransfer:Zone:T SW APARTMENT | 28.88 | 0.02 | 26-FEB-12:20 | 3902.41 | 15-JUN-16:40 |
| Heating:EnergyTransfer:Zone:T SW APARTMENT | 3.71 | 0.00 | 01-JAN-09:00 | 2256.88 | 09-FEB-01:00 |
| General:Heating:EnergyTransfer:Zone:T SW APARTMENT | 3.71 | 0.00 | 01-JAN-09:00 | 2256.88 | 09-FEB-01:00 |
| Cooling:EnergyTransfer:Zone:T SW APARTMENT | 25.16 | 0.00 | 01-JAN-00:10 | 3902.41 | 15-JUN-16:40 |
| General:Cooling:EnergyTransfer:Zone:T SW APARTMENT | 25.16 | 0.00 | 01-JAN-00:10 | 3902.41 | 15-JUN-16:40 |
| EnergyTransfer:Zone:T NW APARTMENT | 26.38 | 0.04 | 13-APR-01:50 | 4026.40 | 15-JUN-17:00 |
| Heating:EnergyTransfer:Zone:T NW APARTMENT | 5.91 | 0.00 | 01-JAN-11:40 | 2472.27 | 09-FEB-01:00 |
| General:Heating:EnergyTransfer:Zone:T NW APARTMENT | 5.91 | 0.00 | 01-JAN-11:40 | 2472.27 | 09-FEB-01:00 |
| Cooling:EnergyTransfer:Zone:T NW APARTMENT | 20.47 | 0.00 | 01-JAN-00:10 | 4026.40 | 15-JUN-17:00 |
| General:Cooling:EnergyTransfer:Zone:T NW APARTMENT | 20.47 | 0.00 | 01-JAN-00:10 | 4026.40 | 15-JUN-17:00 |
| EnergyTransfer:Zone:T SE APARTMENT | 28.74 | 0.28 | 24-JAN-12:20 | 3263.95 | 21-JUN-13:00 |
| Heating:EnergyTransfer:Zone:T SE APARTMENT | 3.63 | 0.00 | 01-JAN-09:00 | 2253.66 | 09-FEB-01:00 |
| General:Heating:EnergyTransfer:Zone:T SE APARTMENT | 3.63 | 0.00 | 01-JAN-09:00 | 2253.66 | 09-FEB-01:00 |
| Cooling:EnergyTransfer:Zone:T SE APARTMENT | 25.11 | 0.00 | 01-JAN-00:10 | 3263.95 | 21-JUN-13:00 |
| General:Cooling:EnergyTransfer:Zone:T SE APARTMENT | 25.11 | 0.00 | 01-JAN-00:10 | 3263.95 | 21-JUN-13:00 |
| EnergyTransfer:Zone:T NE APARTMENT | 26.12 | 0.06 | 11-NOV-02:00 | 3288.32 | 15-JUN-17:00 |
| Heating:EnergyTransfer:Zone:T NE APARTMENT | 5.69 | 0.00 | 01-JAN-10:30 | 2477.77 | 09-FEB-01:00 |
| General:Heating:EnergyTransfer:Zone:T NE APARTMENT | 5.69 | 0.00 | 01-JAN-10:30 | 2477.77 | 09-FEB-01:00 |
| Cooling:EnergyTransfer:Zone:T NE APARTMENT | 20.43 | 0.00 | 01-JAN-00:10 | 3288.32 | 15-JUN-17:00 |
| General:Cooling:EnergyTransfer:Zone:T NE APARTMENT | 20.43 | 0.00 | 01-JAN-00:10 | 3288.32 | 15-JUN-17:00 |
| EnergyTransfer:Zone:T N1 APARTMENT | 19.74 | 0.04 | 28-NOV-13:30 | 2596.01 | 15-JUN-17:00 |
| Heating:EnergyTransfer:Zone:T N1 APARTMENT | 3.08 | 0.00 | 01-JAN-10:30 | 1455.98 | 28-JAN-06:00 |
| General:Heating:EnergyTransfer:Zone:T N1 APARTMENT | 3.08 | 0.00 | 01-JAN-10:30 | 1455.98 | 28-JAN-06:00 |
| Cooling:EnergyTransfer:Zone:T N1 APARTMENT | 16.67 | 0.00 | 01-JAN-00:10 | 2596.01 | 15-JUN-17:00 |
| General:Cooling:EnergyTransfer:Zone:T N1 APARTMENT | 16.67 | 0.00 | 01-JAN-00:10 | 2596.01 | 15-JUN-17:00 |
| EnergyTransfer:Zone:T N2 APARTMENT | 19.77 | 0.00 | 30-MAR-23:30 | 2580.37 | 15-JUN-17:00 |
| Heating:EnergyTransfer:Zone:T N2 APARTMENT | 3.08 | 0.00 | 01-JAN-10:30 | 1458.98 | 28-JAN-06:00 |
| General:Heating:EnergyTransfer:Zone:T N2 APARTMENT | 3.08 | 0.00 | 01-JAN-10:30 | 1458.98 | 28-JAN-06:00 |
| Cooling:EnergyTransfer:Zone:T N2 APARTMENT | 16.69 | 0.00 | 01-JAN-00:10 | 2580.37 | 15-JUN-17:00 |
| General:Cooling:EnergyTransfer:Zone:T N2 APARTMENT | 16.69 | 0.00 | 01-JAN-00:10 | 2580.37 | 15-JUN-17:00 |
| EnergyTransfer:Zone:T S1 APARTMENT | 23.14 | 0.01 | 13-MAR-07:50 | 2673.66 | 19-SEP-14:10 |
| Heating:EnergyTransfer:Zone:T S1 APARTMENT | 1.45 | 0.00 | 01-JAN-00:10 | 1268.26 | 27-DEC-06:00 |
| General:Heating:EnergyTransfer:Zone:T S1 APARTMENT | 1.45 | 0.00 | 01-JAN-00:10 | 1268.26 | 27-DEC-06:00 |
| Cooling:EnergyTransfer:Zone:T S1 APARTMENT | 21.69 | 0.00 | 01-JAN-03:40 | 2673.66 | 19-SEP-14:10 |
| General:Cooling:EnergyTransfer:Zone:T S1 APARTMENT | 21.69 | 0.00 | 01-JAN-03:40 | 2673.66 | 19-SEP-14:10 |
| EnergyTransfer:Zone:T S2 APARTMENT | 23.18 | 0.05 | 21-FEB-05:30 | 2677.09 | 19-SEP-14:10 |
| Heating:EnergyTransfer:Zone:T S2 APARTMENT | 1.46 | 0.00 | 01-JAN-00:10 | 1268.65 | 27-DEC-06:00 |
| General:Heating:EnergyTransfer:Zone:T S2 APARTMENT | 1.46 | 0.00 | 01-JAN-00:10 | 1268.65 | 27-DEC-06:00 |
| Cooling:EnergyTransfer:Zone:T S2 APARTMENT | 21.73 | 0.00 | 01-JAN-03:40 | 2677.09 | 19-SEP-14:10 |
| General:Cooling:EnergyTransfer:Zone:T S2 APARTMENT | 21.73 | 0.00 | 01-JAN-03:40 | 2677.09 | 19-SEP-14:10 |
| EnergyTransfer:Zone:T CORRIDOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Heating:EnergyTransfer:Zone:T CORRIDOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:Heating:EnergyTransfer:Zone:T CORRIDOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Cooling:EnergyTransfer:Zone:T CORRIDOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:Cooling:EnergyTransfer:Zone:T CORRIDOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| EnergyTransfer:Zone:G CORRIDOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Heating:EnergyTransfer:Zone:G CORRIDOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:Heating:EnergyTransfer:Zone:G CORRIDOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Cooling:EnergyTransfer:Zone:G CORRIDOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:Cooling:EnergyTransfer:Zone:G CORRIDOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| EnergyTransfer:Zone:M CORRIDOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Heating:EnergyTransfer:Zone:M CORRIDOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:Heating:EnergyTransfer:Zone:M CORRIDOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Cooling:EnergyTransfer:Zone:M CORRIDOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:Cooling:EnergyTransfer:Zone:M CORRIDOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| EnergyTransfer:HVAC | 777.96 | 0.00 | 03-JAN-19:10 | 93462.19 | 15-JUN-17:00 |
| HeatRecoveryForHeating:EnergyTransfer | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 08-JUL-09:20 |
| HeatRecoveryForCooling:EnergyTransfer | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 08-JUL-19:10 |
| HeatingCoils:EnergyTransfer | 80.53 | 0.00 | 01-JAN-12:50 | 41873.73 | 28-JAN-06:00 |
| CoolingCoils:EnergyTransfer | 697.43 | 0.00 | 01-JAN-00:10 | 93462.19 | 15-JUN-17:00 |
| PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 09:14:34
Annual Building Sensible Heat Gain Components| HVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
| G SW APARTMENT | 1.439 | -5.330 | 1.368 | -18.347 | 0.000 | 0.000 | 3.742 | 1.454 | 12.213 | 11.420 | 0.000 | 0.634 | 0.000 | 0.000 | -4.772 | 0.000 | -3.080 | -0.740 |
| G NW APARTMENT | 1.444 | -5.051 | 4.034 | -15.597 | 0.000 | 0.000 | 3.846 | 1.454 | 12.213 | 6.402 | 0.000 | 0.637 | 0.000 | 0.000 | -4.824 | 0.000 | -2.846 | -1.711 |
| OFFICE | 0.000 | 0.000 | 3.619 | -14.414 | 0.000 | 0.000 | 2.011 | 7.396 | 9.469 | 10.834 | 0.000 | 0.342 | 0.001 | 0.000 | -5.310 | 0.000 | -2.866 | -11.080 |
| G NE APARTMENT | 1.444 | -5.051 | 3.942 | -15.673 | 0.000 | 0.000 | 3.848 | 1.454 | 12.213 | 6.211 | 0.000 | 0.636 | 0.000 | 0.000 | -4.557 | 0.000 | -2.852 | -1.614 |
| G N1 APARTMENT | 1.445 | -5.106 | 2.173 | -13.192 | 0.000 | 0.000 | 3.832 | 1.454 | 12.213 | 2.193 | 0.000 | 0.385 | 0.000 | 0.000 | -3.039 | 0.000 | -1.975 | -0.381 |
| G N2 APARTMENT | 1.445 | -5.107 | 2.175 | -13.203 | 0.000 | 0.000 | 3.832 | 1.454 | 12.213 | 2.192 | 0.000 | 0.385 | 0.000 | 0.000 | -3.039 | 0.000 | -1.976 | -0.371 |
| G S1 APARTMENT | 1.439 | -5.512 | 0.248 | -16.340 | 0.000 | 0.000 | 3.698 | 1.454 | 12.213 | 7.291 | 0.000 | 0.382 | 0.283 | 0.000 | -2.948 | 0.000 | -2.208 | -0.000 |
| G S2 APARTMENT | 1.439 | -5.532 | 0.237 | -17.986 | 0.000 | 0.000 | 3.693 | 1.454 | 12.213 | 7.271 | 0.000 | 0.382 | 2.016 | 0.000 | -2.968 | 0.000 | -2.219 | -0.000 |
| M SW APARTMENT | 2.878 | -11.028 | 1.601 | -44.378 | 0.000 | 0.000 | 7.395 | 2.908 | 24.426 | 22.505 | 0.000 | 1.813 | 10.670 | 0.000 | -9.908 | 0.000 | -8.883 | -0.000 |
| M NW APARTMENT | 2.878 | -10.347 | 5.831 | -37.083 | 0.000 | 0.000 | 7.631 | 2.908 | 24.426 | 12.571 | 0.000 | 1.813 | 7.641 | 0.000 | -10.027 | 0.000 | -8.243 | -0.000 |
| M SE APARTMENT | 2.878 | -11.053 | 1.584 | -44.572 | 0.000 | 0.000 | 7.397 | 2.908 | 24.426 | 22.372 | 0.000 | 1.813 | 10.801 | 0.000 | -9.642 | 0.000 | -8.912 | -0.000 |
| M NE APARTMENT | 2.878 | -10.355 | 5.726 | -37.298 | 0.000 | 0.000 | 7.636 | 2.908 | 24.426 | 12.164 | 0.000 | 1.813 | 7.842 | 0.000 | -9.470 | 0.000 | -8.271 | -0.000 |
| M N1 APARTMENT | 2.879 | -10.538 | 2.443 | -30.208 | 0.000 | 0.000 | 7.584 | 2.908 | 24.426 | 4.292 | 0.000 | 1.094 | 7.145 | 0.000 | -6.339 | 0.000 | -5.685 | -0.000 |
| M N2 APARTMENT | 2.879 | -10.539 | 2.449 | -30.238 | 0.000 | 0.000 | 7.584 | 2.908 | 24.426 | 4.290 | 0.000 | 1.094 | 7.172 | 0.000 | -6.338 | 0.000 | -5.687 | -0.000 |
| M S1 APARTMENT | 2.878 | -11.423 | 0.168 | -38.694 | 0.000 | 0.000 | 7.295 | 2.908 | 24.426 | 14.397 | 0.000 | 1.094 | 9.287 | 0.000 | -6.113 | 0.000 | -6.223 | -0.000 |
| M S2 APARTMENT | 2.878 | -11.424 | 0.169 | -38.738 | 0.000 | 0.000 | 7.295 | 2.908 | 24.426 | 14.395 | 0.000 | 1.094 | 9.334 | 0.000 | -6.113 | 0.000 | -6.224 | -0.000 |
| T SW APARTMENT | 1.439 | -5.177 | 6.340 | -24.055 | 0.000 | 0.000 | 3.788 | 1.454 | 12.213 | 11.195 | 0.000 | 1.190 | 1.548 | 0.000 | -4.547 | 0.000 | -5.387 | -0.000 |
| T NW APARTMENT | 1.439 | -4.945 | 9.307 | -20.363 | 0.000 | 0.000 | 3.873 | 1.454 | 12.213 | 6.235 | 0.000 | 1.190 | 0.000 | 0.000 | -4.658 | 0.000 | -5.054 | -0.691 |
| T SE APARTMENT | 1.439 | -5.197 | 6.195 | -23.923 | 0.000 | 0.000 | 3.791 | 1.454 | 12.213 | 11.129 | 0.000 | 1.190 | 1.567 | 0.000 | -4.424 | 0.000 | -5.434 | -0.000 |
| T NE APARTMENT | 1.439 | -4.945 | 9.110 | -20.338 | 0.000 | 0.000 | 3.877 | 1.454 | 12.213 | 6.059 | 0.000 | 1.190 | 0.000 | 0.000 | -4.406 | 0.000 | -5.082 | -0.570 |
| T N1 APARTMENT | 1.439 | -4.971 | 6.223 | -16.285 | 0.000 | 0.000 | 3.864 | 1.454 | 12.213 | 2.137 | 0.000 | 0.718 | 0.000 | 0.000 | -2.931 | 0.000 | -3.372 | -0.489 |
| T N2 APARTMENT | 1.439 | -4.971 | 6.234 | -16.310 | 0.000 | 0.000 | 3.865 | 1.454 | 12.213 | 2.135 | 0.000 | 0.718 | 0.000 | 0.000 | -2.929 | 0.000 | -3.375 | -0.472 |
| T S1 APARTMENT | 1.439 | -5.279 | 3.555 | -19.954 | 0.000 | 0.000 | 3.764 | 1.454 | 12.213 | 7.197 | 0.000 | 0.718 | 1.376 | 0.000 | -2.792 | 0.000 | -3.691 | -0.000 |
| T S2 APARTMENT | 1.439 | -5.280 | 3.562 | -19.993 | 0.000 | 0.000 | 3.765 | 1.454 | 12.213 | 7.195 | 0.000 | 0.718 | 1.411 | 0.000 | -2.790 | 0.000 | -3.693 | -0.000 |
| T CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 5.990 | 11.688 | 0.000 | 0.966 | 0.000 | 0.112 | 0.000 | 0.000 | -0.478 | 0.000 | -0.828 | -17.450 |
| G CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 5.877 | 11.688 | 3.530 | 2.864 | 0.000 | 2.212 | 0.000 | 0.000 | -1.448 | 0.000 | -15.267 | -9.456 |
| M CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 11.298 | 23.376 | 0.000 | 1.895 | 0.000 | 0.190 | 0.000 | 0.000 | -1.060 | 0.000 | -1.439 | -34.260 |
| Total Facility | 44.633 | -164.161 | 88.293 | -587.183 | 0.000 | 0.000 | 142.069 | 99.229 | 391.594 | 219.805 | 0.000 | 25.553 | 78.096 | 0.000 | -127.869 | 0.000 | -130.773 | -79.286 |
| Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
| G SW APARTMENT | 19-SEP-16:01 | 0.00 | 290.39 | 0.00 | -2674.99 | 0.00 | 0.00 | 0.00 | 86.80 | 588.62 | 1478.12 | 0.00 | 51.05 | 180.01 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| G NW APARTMENT | 15-JUN-17:03 | 0.00 | 377.06 | 0.00 | -2664.86 | 0.00 | 0.00 | 145.49 | 117.18 | 588.62 | 1478.98 | 0.00 | 324.73 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -367.20 |
| OFFICE | 23-OCT-07:01 | 0.00 | 0.00 | 0.00 | -6630.65 | 0.00 | 0.00 | 253.03 | 582.92 | 588.62 | 648.72 | 0.00 | 0.00 | 4740.16 | 0.00 | -0.00 | 0.00 | -182.79 | 0.00 |
| G NE APARTMENT | 03-JUL-17:00 | 0.00 | 415.42 | 0.00 | -2399.95 | 0.00 | 0.00 | 86.96 | 86.80 | 588.62 | 396.84 | 0.00 | 306.19 | 519.11 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| G N1 APARTMENT | 07-AUG-18:00 | 0.00 | 307.60 | 0.00 | -1886.47 | 0.00 | 0.00 | 145.49 | 117.18 | 588.62 | 299.52 | 0.00 | 167.66 | 260.40 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| G N2 APARTMENT | 07-AUG-18:00 | 0.00 | 307.60 | 0.00 | -1880.71 | 0.00 | 0.00 | 145.49 | 117.18 | 588.62 | 299.59 | 0.00 | 167.66 | 254.57 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| G S1 APARTMENT | 19-SEP-14:10 | 0.00 | 290.63 | 0.00 | -2044.84 | 0.00 | 0.00 | 0.00 | 30.38 | 400.26 | 1038.23 | 0.00 | 56.52 | 228.81 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| G S2 APARTMENT | 19-SEP-14:10 | 0.00 | 290.62 | 0.00 | -2135.35 | 0.00 | 0.00 | 0.00 | 30.38 | 400.26 | 1037.00 | 0.00 | 56.52 | 320.56 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| M SW APARTMENT | 15-JUN-17:00 | 0.00 | 763.89 | 0.00 | -6376.31 | 0.00 | 0.00 | 0.00 | 173.60 | 1177.25 | 2675.99 | 0.00 | 994.13 | 591.45 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| M NW APARTMENT | 15-JUN-17:00 | 0.00 | 764.12 | 0.00 | -6582.59 | 0.00 | 0.00 | 173.91 | 173.60 | 1177.25 | 2981.46 | 0.00 | 994.13 | 318.11 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| M SE APARTMENT | 05-JUN-17:00 | 0.00 | 800.01 | 0.00 | -5453.01 | 0.00 | 0.00 | 0.00 | 173.60 | 1177.25 | 1050.17 | 0.00 | 1113.82 | 1138.16 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| M NE APARTMENT | 15-JUN-17:00 | 0.00 | 764.13 | 0.00 | -5581.32 | 0.00 | 0.00 | 173.91 | 173.60 | 1177.25 | 1272.72 | 0.00 | 994.13 | 1025.58 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| M N1 APARTMENT | 15-JUN-17:03 | 0.00 | 754.13 | 0.00 | -4367.29 | 0.00 | 0.00 | 290.97 | 234.36 | 1177.25 | 922.64 | 0.00 | 562.10 | 425.83 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| M N2 APARTMENT | 15-JUN-17:03 | 0.00 | 754.13 | 0.00 | -4354.50 | 0.00 | 0.00 | 290.97 | 234.36 | 1177.25 | 922.75 | 0.00 | 562.10 | 412.93 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| M S1 APARTMENT | 19-SEP-14:10 | 0.00 | 581.23 | 0.00 | -4321.08 | 0.00 | 0.00 | 0.00 | 60.77 | 800.53 | 2074.97 | 0.00 | 162.13 | 641.46 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| M S2 APARTMENT | 19-SEP-14:10 | 0.00 | 581.23 | 0.00 | -4325.72 | 0.00 | 0.00 | 0.00 | 60.77 | 800.53 | 2074.91 | 0.00 | 162.13 | 646.17 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| T SW APARTMENT | 15-JUN-16:40 | 0.00 | 387.43 | 0.00 | -4289.86 | 0.00 | 0.00 | 0.00 | 86.80 | 588.62 | 1370.41 | 0.00 | 639.27 | 1217.33 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| T NW APARTMENT | 15-JUN-17:00 | 0.00 | 382.05 | 0.00 | -4408.48 | 0.00 | 0.00 | 86.96 | 86.80 | 588.62 | 1461.15 | 0.00 | 655.53 | 1147.37 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| T SE APARTMENT | 21-JUN-13:00 | 0.00 | 339.44 | 0.00 | -3603.56 | 0.00 | 0.00 | 0.00 | 17.36 | 388.49 | 726.94 | 0.00 | 803.44 | 1327.89 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| T NE APARTMENT | 15-JUN-17:00 | 0.00 | 382.05 | 0.00 | -3670.40 | 0.00 | 0.00 | 86.96 | 86.80 | 588.62 | 615.85 | 0.00 | 655.53 | 1254.58 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| T N1 APARTMENT | 15-JUN-17:00 | 0.00 | 382.07 | 0.00 | -2978.11 | 0.00 | 0.00 | 86.96 | 86.80 | 588.62 | 441.62 | 0.00 | 395.40 | 996.64 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| T N2 APARTMENT | 15-JUN-17:00 | 0.00 | 382.07 | 0.00 | -2962.47 | 0.00 | 0.00 | 86.96 | 86.80 | 588.62 | 441.80 | 0.00 | 395.40 | 980.82 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| T S1 APARTMENT | 19-SEP-14:10 | 0.00 | 290.61 | 0.00 | -2964.10 | 0.00 | 0.00 | 0.00 | 30.38 | 400.26 | 1021.79 | 0.00 | 106.79 | 1114.26 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| T S2 APARTMENT | 19-SEP-14:10 | 0.00 | 290.61 | 0.00 | -2967.52 | 0.00 | 0.00 | 0.00 | 30.38 | 400.26 | 1021.73 | 0.00 | 106.79 | 1117.73 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| T CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| G CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Total Facility | 15-JUN-17:00 | 0.00 | 11842.42 | 0.00 | -84434.59 | 0.00 | 0.00 | 1799.55 | 4289.87 | 18750.02 | 21861.97 | 0.00 | 15944.06 | 9946.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
| G SW APARTMENT | 26-JAN-00:10 | -392.29 | 0.00 | 1052.51 | 0.00 | 0.00 | 0.00 | 194.99 | 8.68 | 264.88 | 0.00 | 0.00 | 0.00 | 8.26 | 0.00 | -432.27 | 0.00 | -704.77 | 0.00 |
| G NW APARTMENT | 09-FEB-01:00 | -528.35 | 0.00 | 1547.59 | 0.00 | 0.00 | 0.00 | 194.99 | 8.68 | 264.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -568.33 | 0.00 | -901.17 | -18.30 |
| OFFICE | 02-MAR-08:61 | 0.00 | 0.00 | 8837.35 | 0.00 | 0.00 | 0.00 | 404.31 | 582.92 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -252.22 | 0.00 | -199.65 | -9961.32 |
| G NE APARTMENT | 16-FEB-17:01 | -239.91 | 0.00 | 1255.74 | 0.00 | 0.00 | 0.00 | 102.22 | 86.80 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -204.05 | 0.00 | -67.30 | -1522.12 |
| G N1 APARTMENT | 09-FEB-01:10 | -528.36 | 0.00 | 949.95 | 0.00 | 0.00 | 0.00 | 194.99 | 8.68 | 241.34 | 0.00 | 0.00 | 0.00 | 4.69 | 0.00 | -342.97 | 0.00 | -528.32 | 0.00 |
| G N2 APARTMENT | 09-FEB-01:00 | -528.38 | 0.00 | 949.33 | 0.00 | 0.00 | 0.00 | 194.99 | 8.68 | 264.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -343.28 | 0.00 | -543.56 | -2.66 |
| G S1 APARTMENT | 26-JAN-00:10 | -392.28 | 0.00 | 471.00 | 0.00 | 0.00 | 0.00 | 194.99 | 8.68 | 264.88 | 0.00 | 0.00 | 0.00 | 145.20 | 0.00 | -267.38 | 0.00 | -425.10 | 0.00 |
| G S2 APARTMENT | 26-JAN-00:20 | -392.29 | 0.00 | 450.70 | 0.00 | 0.00 | 0.00 | 194.99 | 8.68 | 264.88 | 0.00 | 0.00 | 0.00 | 161.06 | 0.00 | -268.21 | 0.00 | -419.82 | 0.00 |
| M SW APARTMENT | 26-JAN-00:10 | -784.60 | 0.00 | 2466.22 | 0.00 | 0.00 | 0.00 | 389.98 | 17.37 | 529.76 | 0.00 | 0.00 | 0.00 | 296.28 | 0.00 | -886.72 | 0.00 | -2028.29 | 0.00 |
| M NW APARTMENT | 26-JAN-00:10 | -784.59 | 0.00 | 2727.19 | 0.00 | 0.00 | 0.00 | 389.98 | 17.37 | 529.76 | 0.00 | 0.00 | 0.00 | 4.56 | 0.00 | -855.97 | 0.00 | -2028.29 | 0.00 |
| M SE APARTMENT | 26-JAN-00:10 | -784.60 | 0.00 | 2441.32 | 0.00 | 0.00 | 0.00 | 389.98 | 17.37 | 529.76 | 0.00 | 0.00 | 0.00 | 307.91 | 0.00 | -873.44 | 0.00 | -2028.29 | 0.00 |
| M NE APARTMENT | 28-JAN-06:00 | -1293.68 | 0.00 | 3276.29 | 0.00 | 0.00 | 0.00 | 389.98 | 112.83 | 506.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1390.37 | 0.00 | -1193.18 | -408.09 |
| M N1 APARTMENT | 28-JAN-06:00 | -1293.86 | 0.00 | 2070.96 | 0.00 | 0.00 | 0.00 | 389.98 | 112.83 | 506.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -850.27 | 0.00 | -719.69 | -216.18 |
| M N2 APARTMENT | 28-JAN-06:00 | -1293.86 | 0.00 | 2074.94 | 0.00 | 0.00 | 0.00 | 389.98 | 112.83 | 506.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -850.15 | 0.00 | -719.69 | -220.26 |
| M S1 APARTMENT | 27-DEC-06:00 | -1296.96 | 0.00 | 1470.91 | 0.00 | 0.00 | 0.00 | 389.98 | 112.83 | 506.22 | 0.00 | 0.00 | 0.00 | 66.26 | 0.00 | -839.56 | 0.00 | -409.68 | 0.00 |
| M S2 APARTMENT | 27-DEC-06:00 | -1296.96 | 0.00 | 1470.32 | 0.00 | 0.00 | 0.00 | 389.98 | 112.83 | 506.22 | 0.00 | 0.00 | 0.00 | 66.87 | 0.00 | -839.58 | 0.00 | -409.68 | 0.00 |
| T SW APARTMENT | 09-FEB-01:00 | -528.29 | 0.00 | 2784.99 | 0.00 | 0.00 | 0.00 | 194.99 | 8.68 | 264.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -581.11 | 0.00 | -1718.19 | -425.95 |
| T NW APARTMENT | 09-FEB-01:00 | -528.29 | 0.00 | 3000.37 | 0.00 | 0.00 | 0.00 | 194.99 | 8.68 | 264.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -559.70 | 0.00 | -1718.19 | -662.75 |
| T SE APARTMENT | 09-FEB-01:00 | -528.29 | 0.00 | 2781.77 | 0.00 | 0.00 | 0.00 | 194.99 | 8.68 | 264.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -571.87 | 0.00 | -1718.19 | -431.97 |
| T NE APARTMENT | 09-FEB-01:00 | -528.29 | 0.00 | 3005.86 | 0.00 | 0.00 | 0.00 | 194.99 | 8.68 | 264.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -550.39 | 0.00 | -1718.19 | -677.54 |
| T N1 APARTMENT | 28-JAN-06:00 | -646.89 | 0.00 | 2102.84 | 0.00 | 0.00 | 0.00 | 194.99 | 56.42 | 253.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -410.71 | 0.00 | -476.78 | -1072.98 |
| T N2 APARTMENT | 28-JAN-06:00 | -646.89 | 0.00 | 2105.84 | 0.00 | 0.00 | 0.00 | 194.99 | 56.42 | 253.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -410.66 | 0.00 | -476.78 | -1076.03 |
| T S1 APARTMENT | 27-DEC-06:00 | -648.46 | 0.00 | 1916.71 | 0.00 | 0.00 | 0.00 | 194.99 | 56.42 | 253.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -401.17 | 0.00 | -271.40 | -1100.19 |
| T S2 APARTMENT | 27-DEC-06:00 | -648.46 | 0.00 | 1917.10 | 0.00 | 0.00 | 0.00 | 194.99 | 56.42 | 253.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -401.16 | 0.00 | -271.40 | -1100.59 |
| T CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| G CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Total Facility | 27-JAN-08:61 | -20253.99 | 0.00 | 46039.89 | 0.00 | 0.00 | 0.00 | 2156.65 | 2872.71 | 12840.25 | 4590.00 | 0.00 | 0.00 | 0.00 | 0.00 | -5269.50 | 0.00 | -13831.28 | -29144.73 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 09:14:34
System Ventilation Requirements for Cooling| Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
| SPLIT GSW | 0.3902 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.3902 | 0.0665 | 1.0000 | Not calculated | 0.0260 | 0.0665 | ||
| SPLIT GNW | 0.3833 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.3833 | 0.0677 | 1.0000 | Not calculated | 0.0260 | 0.0677 | ||
| SPLIT OFFICE | 0.4315 | 0.0000 | 4.7495 | 1.0000 | Calculated from schedules | 0.0381 | 0.4315 | 0.0883 | 1.0000 | Not calculated | 0.0381 | 0.0883 | ||
| SPLIT GNE | 0.3631 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.3631 | 0.0715 | 1.0000 | Not calculated | 0.0260 | 0.0715 | ||
| SPLIT GN1 | 0.3271 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.3271 | 0.0793 | 1.0000 | Not calculated | 0.0260 | 0.0793 | ||
| SPLIT GN2 | 0.3267 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.3267 | 0.0794 | 1.0000 | Not calculated | 0.0260 | 0.0794 | ||
| SPLIT GS1 | 0.3353 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.3353 | 0.0774 | 1.0000 | Not calculated | 0.0260 | 0.0774 | ||
| SPLIT GS2 | 0.3380 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.3380 | 0.0768 | 1.0000 | Not calculated | 0.0260 | 0.0768 | ||
| SPLIT MSW | 0.9206 | 0.0000 | 5.0000 | 1.0000 | Calculated from schedules | 0.0519 | 0.9206 | 0.0564 | 1.0000 | Not calculated | 0.0519 | 0.0564 | ||
| SPLIT MNW | 0.9076 | 0.0000 | 5.0000 | 1.0000 | Calculated from schedules | 0.0519 | 0.9076 | 0.0572 | 1.0000 | Not calculated | 0.0519 | 0.0572 | ||
| SPLIT MSE | 0.8674 | 0.0000 | 5.0000 | 1.0000 | Calculated from schedules | 0.0519 | 0.8674 | 0.0598 | 1.0000 | Not calculated | 0.0519 | 0.0598 | ||
| SPLIT MNE | 0.8546 | 0.0000 | 5.0000 | 1.0000 | Calculated from schedules | 0.0519 | 0.8546 | 0.0607 | 1.0000 | Not calculated | 0.0519 | 0.0607 | ||
| SPLIT MN1 | 0.7592 | 0.0000 | 5.0000 | 1.0000 | Calculated from schedules | 0.0519 | 0.7592 | 0.0684 | 1.0000 | Not calculated | 0.0519 | 0.0684 | ||
| SPLIT MN2 | 0.7582 | 0.0000 | 5.0000 | 1.0000 | Calculated from schedules | 0.0519 | 0.7582 | 0.0685 | 1.0000 | Not calculated | 0.0519 | 0.0685 | ||
| SPLIT MS1 | 0.7743 | 0.0000 | 5.0000 | 1.0000 | Calculated from schedules | 0.0519 | 0.7743 | 0.0670 | 1.0000 | Not calculated | 0.0519 | 0.0670 | ||
| SPLIT MS2 | 0.7733 | 0.0000 | 5.0000 | 1.0000 | Calculated from schedules | 0.0519 | 0.7733 | 0.0671 | 1.0000 | Not calculated | 0.0519 | 0.0671 | ||
| SPLIT TSW | 0.5171 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.5171 | 0.0502 | 1.0000 | Not calculated | 0.0260 | 0.0502 | ||
| SPLIT TNW | 0.5149 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.5149 | 0.0504 | 1.0000 | Not calculated | 0.0260 | 0.0504 | ||
| SPLIT TSE | 0.4761 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.4761 | 0.0545 | 1.0000 | Not calculated | 0.0260 | 0.0545 | ||
| SPLIT TNE | 0.4739 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.4739 | 0.0548 | 1.0000 | Not calculated | 0.0260 | 0.0548 | ||
| SPLIT TN1 | 0.4324 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.4324 | 0.0600 | 1.0000 | Not calculated | 0.0260 | 0.0600 | ||
| SPLIT TN2 | 0.4310 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.4310 | 0.0602 | 1.0000 | Not calculated | 0.0260 | 0.0602 | ||
| SPLIT TS1 | 0.4352 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.4352 | 0.0596 | 1.0000 | Not calculated | 0.0260 | 0.0596 | ||
| SPLIT TS2 | 0.4338 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.4338 | 0.0598 | 1.0000 | Not calculated | 0.0260 | 0.0598 |
| Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
| SPLIT GSW | 0.3902 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.3902 | 1.0000 | 1.0000 | Not calculated | 0.0260 | 0.0665 | ||
| SPLIT GNW | 0.3833 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.3833 | 1.0000 | 1.0000 | Not calculated | 0.0260 | 0.0677 | ||
| SPLIT OFFICE | 0.4315 | 0.0000 | 4.7495 | 1.0000 | Calculated from schedules | 0.0381 | 0.4315 | 1.0000 | 1.0000 | Not calculated | 0.0381 | 0.0883 | ||
| SPLIT GNE | 0.3631 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.3631 | 1.0000 | 1.0000 | Not calculated | 0.0260 | 0.0715 | ||
| SPLIT GN1 | 0.3271 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.3271 | 1.0000 | 1.0000 | Not calculated | 0.0260 | 0.0793 | ||
| SPLIT GN2 | 0.3267 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.3267 | 1.0000 | 1.0000 | Not calculated | 0.0260 | 0.0794 | ||
| SPLIT GS1 | 0.3353 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.3353 | 1.0000 | 1.0000 | Not calculated | 0.0260 | 0.0774 | ||
| SPLIT GS2 | 0.3380 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.3380 | 1.0000 | 1.0000 | Not calculated | 0.0260 | 0.0768 | ||
| SPLIT MSW | 0.9206 | 0.0000 | 5.0000 | 1.0000 | Calculated from schedules | 0.0519 | 0.9206 | 1.0000 | 1.0000 | Not calculated | 0.0519 | 0.0564 | ||
| SPLIT MNW | 0.9076 | 0.0000 | 5.0000 | 1.0000 | Calculated from schedules | 0.0519 | 0.9076 | 1.0000 | 1.0000 | Not calculated | 0.0519 | 0.0572 | ||
| SPLIT MSE | 0.8674 | 0.0000 | 5.0000 | 1.0000 | Calculated from schedules | 0.0519 | 0.8674 | 1.0000 | 1.0000 | Not calculated | 0.0519 | 0.0598 | ||
| SPLIT MNE | 0.8546 | 0.0000 | 5.0000 | 1.0000 | Calculated from schedules | 0.0519 | 0.8546 | 1.0000 | 1.0000 | Not calculated | 0.0519 | 0.0607 | ||
| SPLIT MN1 | 0.7592 | 0.0000 | 5.0000 | 1.0000 | Calculated from schedules | 0.0519 | 0.7592 | 1.0000 | 1.0000 | Not calculated | 0.0519 | 0.0684 | ||
| SPLIT MN2 | 0.7582 | 0.0000 | 5.0000 | 1.0000 | Calculated from schedules | 0.0519 | 0.7582 | 1.0000 | 1.0000 | Not calculated | 0.0519 | 0.0685 | ||
| SPLIT MS1 | 0.7743 | 0.0000 | 5.0000 | 1.0000 | Calculated from schedules | 0.0519 | 0.7743 | 1.0000 | 1.0000 | Not calculated | 0.0519 | 0.0670 | ||
| SPLIT MS2 | 0.7733 | 0.0000 | 5.0000 | 1.0000 | Calculated from schedules | 0.0519 | 0.7733 | 1.0000 | 1.0000 | Not calculated | 0.0519 | 0.0671 | ||
| SPLIT TSW | 0.5171 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.5171 | 1.0000 | 1.0000 | Not calculated | 0.0260 | 0.0502 | ||
| SPLIT TNW | 0.5149 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.5149 | 1.0000 | 1.0000 | Not calculated | 0.0260 | 0.0504 | ||
| SPLIT TSE | 0.4761 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.4761 | 1.0000 | 1.0000 | Not calculated | 0.0260 | 0.0545 | ||
| SPLIT TNE | 0.4739 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.4739 | 1.0000 | 1.0000 | Not calculated | 0.0260 | 0.0548 | ||
| SPLIT TN1 | 0.4324 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.4324 | 1.0000 | 1.0000 | Not calculated | 0.0260 | 0.0600 | ||
| SPLIT TN2 | 0.4310 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.4310 | 1.0000 | 1.0000 | Not calculated | 0.0260 | 0.0602 | ||
| SPLIT TS1 | 0.4352 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.4352 | 1.0000 | 1.0000 | Not calculated | 0.0260 | 0.0596 | ||
| SPLIT TS2 | 0.4338 | 0.0000 | 2.5000 | 1.0000 | Calculated from schedules | 0.0260 | 0.4338 | 1.0000 | 1.0000 | Not calculated | 0.0260 | 0.0598 |
| AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
| G SW APARTMENT | SPLIT GSW | 0.000000 | 2.5000 | 0.000294 | 88.25 | 0.0260 | 1.0000 | 0.0260 | 1.000 | 0.0260 |
| G NW APARTMENT | SPLIT GNW | 0.000000 | 2.5000 | 0.000294 | 88.25 | 0.0260 | 1.0000 | 0.0260 | 1.000 | 0.0260 |
| OFFICE | SPLIT OFFICE | 0.000000 | 4.7495 | 0.000432 | 88.25 | 0.0381 | 1.0000 | 0.0381 | 1.000 | 0.0381 |
| G NE APARTMENT | SPLIT GNE | 0.000000 | 2.5000 | 0.000294 | 88.25 | 0.0260 | 1.0000 | 0.0260 | 1.000 | 0.0260 |
| G N1 APARTMENT | SPLIT GN1 | 0.000000 | 2.5000 | 0.000294 | 88.25 | 0.0260 | 1.0000 | 0.0260 | 1.000 | 0.0260 |
| G N2 APARTMENT | SPLIT GN2 | 0.000000 | 2.5000 | 0.000294 | 88.25 | 0.0260 | 1.0000 | 0.0260 | 1.000 | 0.0260 |
| G S1 APARTMENT | SPLIT GS1 | 0.000000 | 2.5000 | 0.000294 | 88.25 | 0.0260 | 1.0000 | 0.0260 | 1.000 | 0.0260 |
| G S2 APARTMENT | SPLIT GS2 | 0.000000 | 2.5000 | 0.000294 | 88.25 | 0.0260 | 1.0000 | 0.0260 | 1.000 | 0.0260 |
| M SW APARTMENT | SPLIT MSW | 0.000000 | 5.0000 | 0.000294 | 176.50 | 0.0519 | 1.0000 | 0.0519 | 1.000 | 0.0519 |
| M NW APARTMENT | SPLIT MNW | 0.000000 | 5.0000 | 0.000294 | 176.50 | 0.0519 | 1.0000 | 0.0519 | 1.000 | 0.0519 |
| M SE APARTMENT | SPLIT MSE | 0.000000 | 5.0000 | 0.000294 | 176.50 | 0.0519 | 1.0000 | 0.0519 | 1.000 | 0.0519 |
| M NE APARTMENT | SPLIT MNE | 0.000000 | 5.0000 | 0.000294 | 176.50 | 0.0519 | 1.0000 | 0.0519 | 1.000 | 0.0519 |
| M N1 APARTMENT | SPLIT MN1 | 0.000000 | 5.0000 | 0.000294 | 176.50 | 0.0519 | 1.0000 | 0.0519 | 1.000 | 0.0519 |
| M N2 APARTMENT | SPLIT MN2 | 0.000000 | 5.0000 | 0.000294 | 176.50 | 0.0519 | 1.0000 | 0.0519 | 1.000 | 0.0519 |
| M S1 APARTMENT | SPLIT MS1 | 0.000000 | 5.0000 | 0.000294 | 176.50 | 0.0519 | 1.0000 | 0.0519 | 1.000 | 0.0519 |
| M S2 APARTMENT | SPLIT MS2 | 0.000000 | 5.0000 | 0.000294 | 176.50 | 0.0519 | 1.0000 | 0.0519 | 1.000 | 0.0519 |
| T SW APARTMENT | SPLIT TSW | 0.000000 | 2.5000 | 0.000294 | 88.25 | 0.0260 | 1.0000 | 0.0260 | 1.000 | 0.0260 |
| T NW APARTMENT | SPLIT TNW | 0.000000 | 2.5000 | 0.000294 | 88.25 | 0.0260 | 1.0000 | 0.0260 | 1.000 | 0.0260 |
| T SE APARTMENT | SPLIT TSE | 0.000000 | 2.5000 | 0.000294 | 88.25 | 0.0260 | 1.0000 | 0.0260 | 1.000 | 0.0260 |
| T NE APARTMENT | SPLIT TNE | 0.000000 | 2.5000 | 0.000294 | 88.25 | 0.0260 | 1.0000 | 0.0260 | 1.000 | 0.0260 |
| T N1 APARTMENT | SPLIT TN1 | 0.000000 | 2.5000 | 0.000294 | 88.25 | 0.0260 | 1.0000 | 0.0260 | 1.000 | 0.0260 |
| T N2 APARTMENT | SPLIT TN2 | 0.000000 | 2.5000 | 0.000294 | 88.25 | 0.0260 | 1.0000 | 0.0260 | 1.000 | 0.0260 |
| T S1 APARTMENT | SPLIT TS1 | 0.000000 | 2.5000 | 0.000294 | 88.25 | 0.0260 | 1.0000 | 0.0260 | 1.000 | 0.0260 |
| T S2 APARTMENT | SPLIT TS2 | 0.000000 | 2.5000 | 0.000294 | 88.25 | 0.0260 | 1.0000 | 0.0260 | 1.000 | 0.0260 |
| People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
| SPLIT GSW | 0.000000 | 2.50 | 0.000294 | 88.2493 | 0.0260 | 0.0260 | 0.0260 |
| SPLIT GNW | 0.000000 | 2.50 | 0.000294 | 88.2493 | 0.0260 | 0.0260 | 0.0260 |
| SPLIT OFFICE | 0.000000 | 4.75 | 0.000432 | 88.2493 | 0.0381 | 0.0381 | 0.0381 |
| SPLIT GNE | 0.000000 | 2.50 | 0.000294 | 88.2493 | 0.0260 | 0.0260 | 0.0260 |
| SPLIT GN1 | 0.000000 | 2.50 | 0.000294 | 88.2493 | 0.0260 | 0.0260 | 0.0260 |
| SPLIT GN2 | 0.000000 | 2.50 | 0.000294 | 88.2493 | 0.0260 | 0.0260 | 0.0260 |
| SPLIT GS1 | 0.000000 | 2.50 | 0.000294 | 88.2493 | 0.0260 | 0.0260 | 0.0260 |
| SPLIT GS2 | 0.000000 | 2.50 | 0.000294 | 88.2493 | 0.0260 | 0.0260 | 0.0260 |
| SPLIT MSW | 0.000000 | 5.00 | 0.000294 | 176.4985 | 0.0519 | 0.0519 | 0.0519 |
| SPLIT MNW | 0.000000 | 5.00 | 0.000294 | 176.4985 | 0.0519 | 0.0519 | 0.0519 |
| SPLIT MSE | 0.000000 | 5.00 | 0.000294 | 176.4985 | 0.0519 | 0.0519 | 0.0519 |
| SPLIT MNE | 0.000000 | 5.00 | 0.000294 | 176.4985 | 0.0519 | 0.0519 | 0.0519 |
| SPLIT MN1 | 0.000000 | 5.00 | 0.000294 | 176.4985 | 0.0519 | 0.0519 | 0.0519 |
| SPLIT MN2 | 0.000000 | 5.00 | 0.000294 | 176.4985 | 0.0519 | 0.0519 | 0.0519 |
| SPLIT MS1 | 0.000000 | 5.00 | 0.000294 | 176.4985 | 0.0519 | 0.0519 | 0.0519 |
| SPLIT MS2 | 0.000000 | 5.00 | 0.000294 | 176.4985 | 0.0519 | 0.0519 | 0.0519 |
| SPLIT TSW | 0.000000 | 2.50 | 0.000294 | 88.2493 | 0.0260 | 0.0260 | 0.0260 |
| SPLIT TNW | 0.000000 | 2.50 | 0.000294 | 88.2493 | 0.0260 | 0.0260 | 0.0260 |
| SPLIT TSE | 0.000000 | 2.50 | 0.000294 | 88.2493 | 0.0260 | 0.0260 | 0.0260 |
| SPLIT TNE | 0.000000 | 2.50 | 0.000294 | 88.2493 | 0.0260 | 0.0260 | 0.0260 |
| SPLIT TN1 | 0.000000 | 2.50 | 0.000294 | 88.2493 | 0.0260 | 0.0260 | 0.0260 |
| SPLIT TN2 | 0.000000 | 2.50 | 0.000294 | 88.2493 | 0.0260 | 0.0260 | 0.0260 |
| SPLIT TS1 | 0.000000 | 2.50 | 0.000294 | 88.2493 | 0.0260 | 0.0260 | 0.0260 |
| SPLIT TS2 | 0.000000 | 2.50 | 0.000294 | 88.2493 | 0.0260 | 0.0260 | 0.0260 |
| AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
| G SW APARTMENT | SPLIT GSW | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.3902 | 0.3902 | 0.3902 | No | 0.0260 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| G NW APARTMENT | SPLIT GNW | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.3833 | 0.3833 | 0.3833 | No | 0.0260 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| OFFICE | SPLIT OFFICE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4315 | 0.4315 | 0.4315 | No | 0.0381 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| G NE APARTMENT | SPLIT GNE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.3631 | 0.3631 | 0.3631 | No | 0.0260 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| G N1 APARTMENT | SPLIT GN1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.3271 | 0.3271 | 0.3271 | No | 0.0260 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| G N2 APARTMENT | SPLIT GN2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.3267 | 0.3267 | 0.3267 | No | 0.0260 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| G S1 APARTMENT | SPLIT GS1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.3353 | 0.3353 | 0.3353 | No | 0.0260 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| G S2 APARTMENT | SPLIT GS2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.3380 | 0.3380 | 0.3380 | No | 0.0260 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| M SW APARTMENT | SPLIT MSW | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9206 | 0.9206 | 0.9206 | No | 0.0519 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| M NW APARTMENT | SPLIT MNW | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9076 | 0.9076 | 0.9076 | No | 0.0519 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| M SE APARTMENT | SPLIT MSE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8674 | 0.8674 | 0.8674 | No | 0.0519 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| M NE APARTMENT | SPLIT MNE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8546 | 0.8546 | 0.8546 | No | 0.0519 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| M N1 APARTMENT | SPLIT MN1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.7592 | 0.7592 | 0.7592 | No | 0.0519 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| M N2 APARTMENT | SPLIT MN2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.7582 | 0.7582 | 0.7582 | No | 0.0519 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| M S1 APARTMENT | SPLIT MS1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.7743 | 0.7743 | 0.7743 | No | 0.0519 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| M S2 APARTMENT | SPLIT MS2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.7733 | 0.7733 | 0.7733 | No | 0.0519 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| T SW APARTMENT | SPLIT TSW | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.5171 | 0.5171 | 0.5171 | No | 0.0260 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| T NW APARTMENT | SPLIT TNW | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.5149 | 0.5149 | 0.5149 | No | 0.0260 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| T SE APARTMENT | SPLIT TSE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4761 | 0.4761 | 0.4761 | No | 0.0260 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| T NE APARTMENT | SPLIT TNE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4739 | 0.4739 | 0.4739 | No | 0.0260 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| T N1 APARTMENT | SPLIT TN1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4324 | 0.4324 | 0.4324 | No | 0.0260 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| T N2 APARTMENT | SPLIT TN2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4310 | 0.4310 | 0.4310 | No | 0.0260 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| T S1 APARTMENT | SPLIT TS1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4352 | 0.4352 | 0.4352 | No | 0.0260 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| T S2 APARTMENT | SPLIT TS2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4338 | 0.4338 | 0.4338 | No | 0.0260 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
| SPLIT GSW | 0.3902 | 0.3902 | 0.3902 | 0.3902 | 0.0260 | 1.0000 |
| SPLIT GNW | 0.3833 | 0.3833 | 0.3833 | 0.3833 | 0.0260 | 1.0000 |
| SPLIT OFFICE | 0.4315 | 0.4315 | 0.4315 | 0.4315 | 0.0381 | 1.0000 |
| SPLIT GNE | 0.3631 | 0.3631 | 0.3631 | 0.3631 | 0.0260 | 1.0000 |
| SPLIT GN1 | 0.3271 | 0.3271 | 0.3271 | 0.3271 | 0.0260 | 1.0000 |
| SPLIT GN2 | 0.3267 | 0.3267 | 0.3267 | 0.3267 | 0.0260 | 1.0000 |
| SPLIT GS1 | 0.3353 | 0.3353 | 0.3353 | 0.3353 | 0.0260 | 1.0000 |
| SPLIT GS2 | 0.3380 | 0.3380 | 0.3380 | 0.3380 | 0.0260 | 1.0000 |
| SPLIT MSW | 0.9206 | 0.9206 | 0.9206 | 0.9206 | 0.0519 | 1.0000 |
| SPLIT MNW | 0.9076 | 0.9076 | 0.9076 | 0.9076 | 0.0519 | 1.0000 |
| SPLIT MSE | 0.8674 | 0.8674 | 0.8674 | 0.8674 | 0.0519 | 1.0000 |
| SPLIT MNE | 0.8546 | 0.8546 | 0.8546 | 0.8546 | 0.0519 | 1.0000 |
| SPLIT MN1 | 0.7592 | 0.7592 | 0.7592 | 0.7592 | 0.0519 | 1.0000 |
| SPLIT MN2 | 0.7582 | 0.7582 | 0.7582 | 0.7582 | 0.0519 | 1.0000 |
| SPLIT MS1 | 0.7743 | 0.7743 | 0.7743 | 0.7743 | 0.0519 | 1.0000 |
| SPLIT MS2 | 0.7733 | 0.7733 | 0.7733 | 0.7733 | 0.0519 | 1.0000 |
| SPLIT TSW | 0.5171 | 0.5171 | 0.5171 | 0.5171 | 0.0260 | 1.0000 |
| SPLIT TNW | 0.5149 | 0.5149 | 0.5149 | 0.5149 | 0.0260 | 1.0000 |
| SPLIT TSE | 0.4761 | 0.4761 | 0.4761 | 0.4761 | 0.0260 | 1.0000 |
| SPLIT TNE | 0.4739 | 0.4739 | 0.4739 | 0.4739 | 0.0260 | 1.0000 |
| SPLIT TN1 | 0.4324 | 0.4324 | 0.4324 | 0.4324 | 0.0260 | 1.0000 |
| SPLIT TN2 | 0.4310 | 0.4310 | 0.4310 | 0.4310 | 0.0260 | 1.0000 |
| SPLIT TS1 | 0.4352 | 0.4352 | 0.4352 | 0.4352 | 0.0260 | 1.0000 |
| SPLIT TS2 | 0.4338 | 0.4338 | 0.4338 | 0.4338 | 0.0260 | 1.0000 |
| AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
| G SW APARTMENT | SPLIT GSW | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.3902 | 0.3902 | 0.3902 | No | 0.0260 | 0.3108 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| G NW APARTMENT | SPLIT GNW | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.3833 | 0.3833 | 0.3833 | No | 0.0260 | 0.3374 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| OFFICE | SPLIT OFFICE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4315 | 0.4315 | 0.4315 | No | 0.0381 | 0.3471 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| G NE APARTMENT | SPLIT GNE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.3631 | 0.3631 | 0.3631 | No | 0.0260 | 0.3362 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| G N1 APARTMENT | SPLIT GN1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.3271 | 0.3271 | 0.3271 | No | 0.0260 | 0.5909 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| G N2 APARTMENT | SPLIT GN2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.3267 | 0.3267 | 0.3267 | No | 0.0260 | 0.5908 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| G S1 APARTMENT | SPLIT GS1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.3353 | 0.3353 | 0.3353 | No | 0.0260 | 0.5127 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| G S2 APARTMENT | SPLIT GS2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.3380 | 0.3380 | 0.3380 | No | 0.0260 | 0.5075 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| M SW APARTMENT | SPLIT MSW | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9206 | 0.9206 | 0.9206 | No | 0.0519 | 0.3060 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| M NW APARTMENT | SPLIT MNW | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9076 | 0.9076 | 0.9076 | No | 0.0519 | 0.3380 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| M SE APARTMENT | SPLIT MSE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8674 | 0.8674 | 0.8674 | No | 0.0519 | 0.3049 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| M NE APARTMENT | SPLIT MNE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8546 | 0.8546 | 0.8546 | No | 0.0519 | 0.3366 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| M N1 APARTMENT | SPLIT MN1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.7592 | 0.7592 | 0.7592 | No | 0.0519 | 0.6763 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| M N2 APARTMENT | SPLIT MN2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.7582 | 0.7582 | 0.7582 | No | 0.0519 | 0.6761 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| M S1 APARTMENT | SPLIT MS1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.7743 | 0.7743 | 0.7743 | No | 0.0519 | 0.5617 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| M S2 APARTMENT | SPLIT MS2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.7733 | 0.7733 | 0.7733 | No | 0.0519 | 0.5616 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| T SW APARTMENT | SPLIT TSW | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.5171 | 0.5171 | 0.5171 | No | 0.0260 | 0.1683 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| T NW APARTMENT | SPLIT TNW | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.5149 | 0.5149 | 0.5149 | No | 0.0260 | 0.1780 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| T SE APARTMENT | SPLIT TSE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4761 | 0.4761 | 0.4761 | No | 0.0260 | 0.1678 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| T NE APARTMENT | SPLIT TNE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4739 | 0.4739 | 0.4739 | No | 0.0260 | 0.1775 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| T N1 APARTMENT | SPLIT TN1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4324 | 0.4324 | 0.4324 | No | 0.0260 | 0.2571 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| T N2 APARTMENT | SPLIT TN2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4310 | 0.4310 | 0.4310 | No | 0.0260 | 0.2570 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| T S1 APARTMENT | SPLIT TS1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4352 | 0.4352 | 0.4352 | No | 0.0260 | 0.2372 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| T S2 APARTMENT | SPLIT TS2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4338 | 0.4338 | 0.4338 | No | 0.0260 | 0.2372 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
| SPLIT GSW | 0.3902 | 0.3902 | 0.3902 | 0.3902 | 0.0260 | 1.0000 |
| SPLIT GNW | 0.3833 | 0.3833 | 0.3833 | 0.3833 | 0.0260 | 1.0000 |
| SPLIT OFFICE | 0.4315 | 0.4315 | 0.4315 | 0.4315 | 0.0381 | 1.0000 |
| SPLIT GNE | 0.3631 | 0.3631 | 0.3631 | 0.3631 | 0.0260 | 1.0000 |
| SPLIT GN1 | 0.3271 | 0.3271 | 0.3271 | 0.3271 | 0.0260 | 1.0000 |
| SPLIT GN2 | 0.3267 | 0.3267 | 0.3267 | 0.3267 | 0.0260 | 1.0000 |
| SPLIT GS1 | 0.3353 | 0.3353 | 0.3353 | 0.3353 | 0.0260 | 1.0000 |
| SPLIT GS2 | 0.3380 | 0.3380 | 0.3380 | 0.3380 | 0.0260 | 1.0000 |
| SPLIT MSW | 0.9206 | 0.9206 | 0.9206 | 0.9206 | 0.0519 | 1.0000 |
| SPLIT MNW | 0.9076 | 0.9076 | 0.9076 | 0.9076 | 0.0519 | 1.0000 |
| SPLIT MSE | 0.8674 | 0.8674 | 0.8674 | 0.8674 | 0.0519 | 1.0000 |
| SPLIT MNE | 0.8546 | 0.8546 | 0.8546 | 0.8546 | 0.0519 | 1.0000 |
| SPLIT MN1 | 0.7592 | 0.7592 | 0.7592 | 0.7592 | 0.0519 | 1.0000 |
| SPLIT MN2 | 0.7582 | 0.7582 | 0.7582 | 0.7582 | 0.0519 | 1.0000 |
| SPLIT MS1 | 0.7743 | 0.7743 | 0.7743 | 0.7743 | 0.0519 | 1.0000 |
| SPLIT MS2 | 0.7733 | 0.7733 | 0.7733 | 0.7733 | 0.0519 | 1.0000 |
| SPLIT TSW | 0.5171 | 0.5171 | 0.5171 | 0.5171 | 0.0260 | 1.0000 |
| SPLIT TNW | 0.5149 | 0.5149 | 0.5149 | 0.5149 | 0.0260 | 1.0000 |
| SPLIT TSE | 0.4761 | 0.4761 | 0.4761 | 0.4761 | 0.0260 | 1.0000 |
| SPLIT TNE | 0.4739 | 0.4739 | 0.4739 | 0.4739 | 0.0260 | 1.0000 |
| SPLIT TN1 | 0.4324 | 0.4324 | 0.4324 | 0.4324 | 0.0260 | 1.0000 |
| SPLIT TN2 | 0.4310 | 0.4310 | 0.4310 | 0.4310 | 0.0260 | 1.0000 |
| SPLIT TS1 | 0.4352 | 0.4352 | 0.4352 | 0.4352 | 0.0260 | 1.0000 |
| SPLIT TS2 | 0.4338 | 0.4338 | 0.4338 | 0.4338 | 0.0260 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 09:14:34
Sec1.1A-General Information| Data | |
| Weather File | RUNPERIOD 1 ** El Paso International Ap Ut TX USA TMY3 WMO#=722700 |
| Total gross floor area [m2] | 3134.61 |
| Principal Heating Source | Natural Gas |
| Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
| G SW APARTMENT | 88.25 | 88.25 | 0.00 | 117.85 |
| G NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
| OFFICE | 88.25 | 88.25 | 0.00 | 33.56 |
| G NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
| G N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
| G N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
| G S1 APARTMENT | 88.25 | 88.25 | 0.00 | 117.85 |
| G S2 APARTMENT | 88.25 | 88.25 | 0.00 | 117.85 |
| M SW APARTMENT | 88.25 | 88.25 | 0.00 | 117.85 |
| M NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
| M SE APARTMENT | 88.25 | 88.25 | 0.00 | 117.85 |
| M NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
| M N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
| M N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
| M S1 APARTMENT | 88.25 | 88.25 | 0.00 | 117.85 |
| M S2 APARTMENT | 88.25 | 88.25 | 0.00 | 117.85 |
| T SW APARTMENT | 88.25 | 88.25 | 0.00 | 117.85 |
| T NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
| T SE APARTMENT | 88.25 | 88.25 | 0.00 | 117.85 |
| T NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
| T N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
| T N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
| T S1 APARTMENT | 88.25 | 88.25 | 0.00 | 117.85 |
| T S2 APARTMENT | 88.25 | 88.25 | 0.00 | 117.85 |
| T CORRIDOR | 77.66 | 0.00 | 77.66 | 168.00 |
| G CORRIDOR | 77.66 | 0.00 | 77.66 | 168.00 |
| M CORRIDOR | 77.66 | 0.00 | 77.66 | 168.00 |
| Totals | 3134.61 | 2823.98 | 310.64 |
| Data | |
| Number of hours heating loads not met | 0.00 |
| Number of hours cooling loads not met | 0.00 |
| Number of hours not met | 0.00 |
| Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
| None |
| Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
| Heating -- General | 0.00 | 0.00 | 100.67 | 52342.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Cooling -- General | 187.62 | 28167.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Lighting -- LightsWired | 94.96 | 5496.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Lighting -- LightsPlugIn | 4.27 | 407.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Lighting -- General | 50.06 | 3183.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment -- MiscPlug | 388.06 | 18541.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment -- ElevatorLift | 65.48 | 4006.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment -- ElevatorLightsFan | 5.11 | 162.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans -- Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans -- General | 112.97 | 9845.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Recovery -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems -- Water Heater | 408.91 | 37509.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Process Subtotal [GJ] | Total Energy Use [GJ] | |
| Electricity | 458.66 | 1317.45 |
| Natural Gas | 0.00 | 100.67 |
| Additional | 0.00 | 0.00 |
| Total | 458.66 | 1418.11 |
| Process Subtotal [$] | Total Energy Cost [$] | |
| Electricity | 0.00 | |
| Natural Gas | 0.00 | |
| Additional | 0.00 | |
| Total | 0.00 |
| Rated Capacity [kW] | Annual Energy Generated [GJ] | |
| Photovoltaic | 0.00 | 0.00 |
| Wind | 0.00 | 0.00 |
| Electricty [MJ/m2] | |
| Interior Lighting (All) | 31.66 |
| Space Heating | 0.00 |
| Space Cooling | 59.86 |
| Fans (All) | 36.04 |
| Service Water Heating | 130.45 |
| Receptacle Equipment | 146.32 |
| Miscellaneous (All) | 420.29 |
| Subtotal | 420.29 |
| Natural Gas [MJ/m2] | |
| Space Heating | 32.11 |
| Service Water Heating | 0.00 |
| Miscellaneous (All) | 32.11 |
| Subtotal | 32.11 |
| Additional [MJ/m2] | |
| Subtotal | 0.00 |
| Miscellaneous | 0.00 |
| Percent [%] | |
| Interior Lighting (All) | 7.00 |
| Space Heating | 7.10 |
| Space Cooling | 13.23 |
| Fans (All) | 7.97 |
| Service Water Heating | 28.83 |
| Receptacle Equipment | 32.34 |
| Miscellaneous | 3.53 |
| Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
| OCC_APT_SCH_STAY_HOME_FAMILY | 5993. | 8760. |
| OCC_APT_SCH_CORRIDOR | 5993. | 8760. |
| OCC_APT_SCH_WORKING_FAMILY | 5845. | 6055. |
| OCC_OFF_SCH | 2210. | 2340. |
| OCC_OFF_W_SB_SCH | 1820. | 1820. |
| LTG_SCH_OFFICE | 2435. | 8760. |
| LTG_SCH_CORRIDOR | 8760. | 8760. |
| LTG_SCH_APARTMENT_HARDWIRED | 527. | 8760. |
| LTG_SCH_APARTMENT_PLUGIN | 527. | 8760. |
| EQP_APT_SCH | 5763. | 8760. |
| EQP_OFF_SCH | 4531. | 8760. |
| INF_APT_SCH | 8760. | 8760. |
| INF_OFF_SCH | 8760. | 8760. |
| INF_COR_SCH | 8760. | 8760. |
| INFIL_DOOR_OPENING_SCH | 1466. | 5840. |
| ALL OFF | 0. | 0. |
| ALL ON | 8760. | 8760. |
| ALWAYS_ON | 8760. | 8760. |
| ALLON_EXCEPT_DD | 8760. | 8760. |
| EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
| FAN_OFF_W_SB_SCH | 8240. | 8240. |
| APT_DHW_SCH | 4592. | 8760. |
| EXTERIOR_LTG_SCH | 4380. | 4380. |
| BLDG_ELEVATORS | 2270. | 8760. |
| ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
| ELEV_LIGHT_FAN_SCH_ADD_DF | 2154. | 8760. |
| SLIDING_DOORS_VENTILATION_AVAILABILITY_SCH | 5840. | 5840. |
| First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
| HTGSETP_APT_SCH | APTHEATINGSETPOINT | January | 21.10 | 365 | 21.10 | 365 |
| HTGSETP_DESIGN_OFF_SCH | OFFHEATINGSETPOINT | January | 21.10 | 365 | 21.10 | 365 |
| CLGSETP_APT_SCH | APTCOOLINGSETPOINT | July | 24.00 | 365 | 24.00 | 365 |
| CLGSETP_DESIGN_OFF_SCH | OFFCOOLINGSETPOINT | July | 23.90 | 365 | 23.90 | 365 |
| S HTGSETP_APT_SCH | S APARTMENT DUAL SP CONTROL | January | 21.10 | 365 | 21.10 | 365 |
| S CLGSETP_APT_SCH | S APARTMENT DUAL SP CONTROL | July | 24.00 | 365 | 24.00 | 365 |
| N HTGSETP_APT_SCH | N APARTMENT DUAL SP CONTROL | January | 21.10 | 365 | 21.10 | 365 |
| N CLGSETP_APT_SCH | N APARTMENT DUAL SP CONTROL | July | 24.00 | 365 | 24.00 | 365 |
| HTGSETP_OFF_SCH_YES_OPTIMUM | OFFICE DUAL SP CONTROL | January | 21.10 | 365 | 15.60 | 365 |
| CLGSETP_OFF_SCH_YES_OPTIMUM | OFFICE DUAL SP CONTROL | July | 24.00 | 365 | 29.40 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 09:14:34
Heat Index Hours| Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
| G SW APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| G NW APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| OFFICE | 6405.67 | 2354.33 | 0.00 | 0.00 | 0.00 |
| G NE APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| G N1 APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| G N2 APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| G S1 APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| G S2 APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M SW APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M NW APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M SE APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M NE APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M N1 APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M N2 APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M S1 APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M S2 APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T SW APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T NW APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T SE APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T NE APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T N1 APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T N2 APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T S1 APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T S2 APARTMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T CORRIDOR | 6425.33 | 2334.17 | 0.50 | 0.00 | 0.00 |
| G CORRIDOR | 6837.00 | 1923.00 | 0.00 | 0.00 | 0.00 |
| M CORRIDOR | 5334.00 | 3426.00 | 0.00 | 0.00 | 0.00 |
| Min | 5334.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Max | 8760.00 | 3426.00 | 0.50 | 0.00 | 0.00 |
| Average | 8388.22 | 371.76 | 0.02 | 0.00 | 0.00 |
| Sum | 226482.00 | 10037.50 | 0.50 | 0.00 | 0.00 |
| Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
| G SW APARTMENT | 11830.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| G NW APARTMENT | 10585.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| OFFICE | 7000.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| G NE APARTMENT | 10585.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| G N1 APARTMENT | 10585.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| G N2 APARTMENT | 10585.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| G S1 APARTMENT | 11830.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| G S2 APARTMENT | 11830.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M SW APARTMENT | 11830.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M NW APARTMENT | 10585.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M SE APARTMENT | 11830.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M NE APARTMENT | 10585.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M N1 APARTMENT | 10585.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M N2 APARTMENT | 10585.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M S1 APARTMENT | 11830.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| M S2 APARTMENT | 11830.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T SW APARTMENT | 11830.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T NW APARTMENT | 10585.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T SE APARTMENT | 11830.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T NE APARTMENT | 10585.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T N1 APARTMENT | 10585.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T N2 APARTMENT | 10585.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T S1 APARTMENT | 11830.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T S2 APARTMENT | 11830.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| T CORRIDOR | 17295.00 | 5698.50 | 1.50 | 0.00 | 0.00 |
| G CORRIDOR | 17863.67 | 5131.33 | 0.00 | 0.00 | 0.00 |
| M CORRIDOR | 14107.67 | 8887.33 | 0.00 | 0.00 | 0.00 |
| Min | 7000.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Max | 17863.67 | 8887.33 | 1.50 | 0.00 | 0.00 |
| Average | 11608.01 | 730.27 | 0.06 | 0.00 | 0.00 |
| Sum | 313416.33 | 19717.17 | 1.50 | 0.00 | 0.00 |
| Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
| G SW APARTMENT | 8728.33 | 31.67 | 0.00 | 0.00 | 0.00 |
| G NW APARTMENT | 8729.50 | 30.50 | 0.00 | 0.00 | 0.00 |
| OFFICE | 6917.50 | 1842.50 | 0.00 | 0.00 | 0.00 |
| G NE APARTMENT | 8728.83 | 31.17 | 0.00 | 0.00 | 0.00 |
| G N1 APARTMENT | 8732.83 | 27.17 | 0.00 | 0.00 | 0.00 |
| G N2 APARTMENT | 8732.50 | 27.50 | 0.00 | 0.00 | 0.00 |
| G S1 APARTMENT | 8732.50 | 27.50 | 0.00 | 0.00 | 0.00 |
| G S2 APARTMENT | 8745.17 | 14.83 | 0.00 | 0.00 | 0.00 |
| M SW APARTMENT | 8729.50 | 30.50 | 0.00 | 0.00 | 0.00 |
| M NW APARTMENT | 8730.83 | 29.17 | 0.00 | 0.00 | 0.00 |
| M SE APARTMENT | 8729.50 | 30.50 | 0.00 | 0.00 | 0.00 |
| M NE APARTMENT | 8730.00 | 30.00 | 0.00 | 0.00 | 0.00 |
| M N1 APARTMENT | 8734.33 | 25.67 | 0.00 | 0.00 | 0.00 |
| M N2 APARTMENT | 8733.67 | 26.33 | 0.00 | 0.00 | 0.00 |
| M S1 APARTMENT | 8732.17 | 27.83 | 0.00 | 0.00 | 0.00 |
| M S2 APARTMENT | 8731.67 | 28.33 | 0.00 | 0.00 | 0.00 |
| T SW APARTMENT | 8696.67 | 63.33 | 0.00 | 0.00 | 0.00 |
| T NW APARTMENT | 8695.00 | 65.00 | 0.00 | 0.00 | 0.00 |
| T SE APARTMENT | 8698.83 | 61.17 | 0.00 | 0.00 | 0.00 |
| T NE APARTMENT | 8696.50 | 63.50 | 0.00 | 0.00 | 0.00 |
| T N1 APARTMENT | 8709.50 | 50.50 | 0.00 | 0.00 | 0.00 |
| T N2 APARTMENT | 8709.00 | 51.00 | 0.00 | 0.00 | 0.00 |
| T S1 APARTMENT | 8710.33 | 49.67 | 0.00 | 0.00 | 0.00 |
| T S2 APARTMENT | 8710.17 | 49.83 | 0.00 | 0.00 | 0.00 |
| T CORRIDOR | 4469.17 | 4256.50 | 34.33 | 0.00 | 0.00 |
| G CORRIDOR | 6388.67 | 2371.33 | 0.00 | 0.00 | 0.00 |
| M CORRIDOR | 2376.33 | 6348.17 | 35.50 | 0.00 | 0.00 |
| Min | 2376.33 | 14.83 | 0.00 | 0.00 | 0.00 |
| Max | 8745.17 | 6348.17 | 35.50 | 0.00 | 0.00 |
| Average | 8176.26 | 581.15 | 2.59 | 0.00 | 0.00 |
| Sum | 220759.00 | 15691.17 | 69.83 | 0.00 | 0.00 |
| Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
| G SW APARTMENT | 11783.67 | 46.33 | 0.00 | 0.00 | 0.00 |
| G NW APARTMENT | 10540.00 | 45.00 | 0.00 | 0.00 | 0.00 |
| OFFICE | 6888.67 | 111.33 | 0.00 | 0.00 | 0.00 |
| G NE APARTMENT | 10535.00 | 50.00 | 0.00 | 0.00 | 0.00 |
| G N1 APARTMENT | 10547.00 | 38.00 | 0.00 | 0.00 | 0.00 |
| G N2 APARTMENT | 10546.33 | 38.67 | 0.00 | 0.00 | 0.00 |
| G S1 APARTMENT | 11792.00 | 38.00 | 0.00 | 0.00 | 0.00 |
| G S2 APARTMENT | 11813.00 | 17.00 | 0.00 | 0.00 | 0.00 |
| M SW APARTMENT | 11784.33 | 45.67 | 0.00 | 0.00 | 0.00 |
| M NW APARTMENT | 10540.33 | 44.67 | 0.00 | 0.00 | 0.00 |
| M SE APARTMENT | 11778.33 | 51.67 | 0.00 | 0.00 | 0.00 |
| M NE APARTMENT | 10533.33 | 51.67 | 0.00 | 0.00 | 0.00 |
| M N1 APARTMENT | 10548.00 | 37.00 | 0.00 | 0.00 | 0.00 |
| M N2 APARTMENT | 10546.67 | 38.33 | 0.00 | 0.00 | 0.00 |
| M S1 APARTMENT | 11790.33 | 39.67 | 0.00 | 0.00 | 0.00 |
| M S2 APARTMENT | 11789.33 | 40.67 | 0.00 | 0.00 | 0.00 |
| T SW APARTMENT | 11727.00 | 103.00 | 0.00 | 0.00 | 0.00 |
| T NW APARTMENT | 10483.00 | 102.00 | 0.00 | 0.00 | 0.00 |
| T SE APARTMENT | 11726.00 | 104.00 | 0.00 | 0.00 | 0.00 |
| T NE APARTMENT | 10476.00 | 109.00 | 0.00 | 0.00 | 0.00 |
| T N1 APARTMENT | 10508.33 | 76.67 | 0.00 | 0.00 | 0.00 |
| T N2 APARTMENT | 10507.33 | 77.67 | 0.00 | 0.00 | 0.00 |
| T S1 APARTMENT | 11752.67 | 77.33 | 0.00 | 0.00 | 0.00 |
| T S2 APARTMENT | 11752.33 | 77.67 | 0.00 | 0.00 | 0.00 |
| T CORRIDOR | 11678.00 | 11200.17 | 116.83 | 0.00 | 0.00 |
| G CORRIDOR | 16245.33 | 6749.67 | 0.00 | 0.00 | 0.00 |
| M CORRIDOR | 6199.33 | 16677.17 | 118.50 | 0.00 | 0.00 |
| Min | 6199.33 | 17.00 | 0.00 | 0.00 | 0.00 |
| Max | 16245.33 | 16677.17 | 118.50 | 0.00 | 0.00 |
| Average | 10993.02 | 1336.59 | 8.72 | 0.00 | 0.00 |
| Sum | 296811.67 | 36088.00 | 235.33 | 0.00 | 0.00 |
| SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
| None |
| SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
| None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 09:14:34
CO2 Level Hours| Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
| None |
| Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
| None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 09:14:34
Illuminance Level Hours| A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
| None |
| A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
| None |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
| January | 8.136 |
| February | 10.272 |
| March | 12.546 |
| April | 19.230 |
| May | 23.842 |
| June | 27.856 |
| July | 27.543 |
| August | 26.276 |
| September | 23.380 |
| October | 18.301 |
| November | 11.185 |
| December | 6.787 |
| Annual Sum or Average | 17.982 |
| Minimum of Months | 6.787 |
| Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Environment
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
| January | 8.136 |
| February | 10.272 |
| March | 12.546 |
| April | 19.230 |
| May | 23.842 |
| June | 27.856 |
| July | 27.543 |
| August | 26.276 |
| September | 23.380 |
| October | 18.301 |
| November | 11.185 |
| December | 6.787 |
| Annual Sum or Average | 17.982 |
| Minimum of Months | 6.787 |
| Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2012
For: Environment
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
| January | 8.136 |
| February | 10.272 |
| March | 12.546 |
| April | 19.230 |
| May | 23.842 |
| June | 27.856 |
| July | 27.543 |
| August | 26.276 |
| September | 23.380 |
| October | 18.301 |
| November | 11.185 |
| December | 6.787 |
| Annual Sum or Average | 17.982 |
| Minimum of Months | 6.787 |
| Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
| January | 8.136 |
| February | 10.272 |
| March | 12.546 |
| April | 19.230 |
| May | 23.842 |
| June | 27.856 |
| July | 27.543 |
| August | 26.276 |
| September | 23.380 |
| October | 18.301 |
| November | 11.185 |
| December | 6.787 |
| Annual Sum or Average | 17.982 |
| Minimum of Months | 6.787 |
| Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME APARTMENTMIDRISE
For: Environment
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
| January | 8.136 |
| February | 10.272 |
| March | 12.546 |
| April | 19.230 |
| May | 23.842 |
| June | 27.856 |
| July | 27.543 |
| August | 26.276 |
| September | 23.380 |
| October | 18.301 |
| November | 11.185 |
| December | 6.787 |
| Annual Sum or Average | 17.982 |
| Minimum of Months | 6.787 |
| Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
| January | 8.136 |
| February | 10.272 |
| March | 12.546 |
| April | 19.230 |
| May | 23.842 |
| June | 27.856 |
| July | 27.543 |
| August | 26.276 |
| September | 23.380 |
| October | 18.301 |
| November | 11.185 |
| December | 6.787 |
| Annual Sum or Average | 17.982 |
| Minimum of Months | 6.787 |
| Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
| January | 8.136 |
| February | 10.272 |
| March | 12.546 |
| April | 19.230 |
| May | 23.842 |
| June | 27.856 |
| July | 27.543 |
| August | 26.276 |
| September | 23.380 |
| October | 18.301 |
| November | 11.185 |
| December | 6.787 |
| Annual Sum or Average | 17.982 |
| Minimum of Months | 6.787 |
| Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3B
For: Environment
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
| January | 8.136 |
| February | 10.272 |
| March | 12.546 |
| April | 19.230 |
| May | 23.842 |
| June | 27.856 |
| July | 27.543 |
| August | 26.276 |
| September | 23.380 |
| October | 18.301 |
| November | 11.185 |
| December | 6.787 |
| Annual Sum or Average | 17.982 |
| Minimum of Months | 6.787 |
| Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_TX_ELPASO
For: Environment
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
| January | 8.136 |
| February | 10.272 |
| March | 12.546 |
| April | 19.230 |
| May | 23.842 |
| June | 27.856 |
| July | 27.543 |
| August | 26.276 |
| September | 23.380 |
| October | 18.301 |
| November | 11.185 |
| December | 6.787 |
| Annual Sum or Average | 17.982 |
| Minimum of Months | 6.787 |
| Maximum of Months | 27.856 |
Report: ZoneCoolingSummaryMonthly
For: G SW APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.653670E+09 | 589.28 | 01-JAN-16:20 | 15.20 | 8.88 | 87691360.60 | 70.36 | 02-JAN-17:10 | 16.23 | 8.47 |
| February | 0.474066E+09 | 651.98 | 20-FEB-16:10 | 23.12 | 8.59 | 79468865.98 | 70.38 | 20-FEB-19:10 | 17.52 | 6.26 |
| March | 0.463678E+09 | 588.19 | 21-MAR-16:17 | 24.80 | 9.49 | 87111506.54 | 70.36 | 26-MAR-17:00 | 21.10 | 8.29 |
| April | 0.103031E+10 | 1513.15 | 30-APR-16:10 | 30.50 | 12.87 | 0.114140E+09 | 70.40 | 05-APR-23:00 | 30.50 | 12.87 |
| May | 0.188655E+10 | 1882.57 | 19-MAY-17:17 | 34.03 | 16.20 | 0.124620E+09 | 70.38 | 01-MAY-03:20 | 34.03 | 16.20 |
| June | 0.266008E+10 | 2197.41 | 15-JUN-17:05 | 37.02 | 15.17 | 0.120421E+09 | 70.32 | 14-JUN-04:30 | 37.02 | 15.17 |
| July | 0.306934E+10 | 2210.68 | 26-JUL-17:23 | 35.00 | 19.87 | 0.129276E+09 | 70.30 | 11-JUL-03:00 | 35.00 | 19.87 |
| August | 0.320170E+10 | 2303.02 | 06-AUG-17:08 | 36.02 | 18.72 | 0.123963E+09 | 70.32 | 20-AUG-02:20 | 23.67 | 15.56 |
| September | 0.316969E+10 | 2384.61 | 19-SEP-16:01 | 33.80 | 16.09 | 0.123964E+09 | 70.32 | 26-SEP-19:49 | 23.40 | 12.15 |
| October | 0.238012E+10 | 2287.81 | 05-OCT-16:03 | 30.63 | 17.38 | 0.127183E+09 | 70.38 | 10-OCT-03:09 | 12.30 | 8.79 |
| November | 0.134276E+10 | 1644.73 | 09-NOV-15:10 | 23.30 | 12.70 | 0.110029E+09 | 70.38 | 01-NOV-02:20 | 23.30 | 12.70 |
| December | 0.741369E+09 | 556.32 | 18-DEC-23:30 | 0.00 | -5.2 | 87800571.63 | 70.27 | 16-DEC-16:19 | 0.00 | -5.2 |
| Annual Sum or Average | 0.210733E+11 | 0.131567E+10 | ||||||||
| Minimum of Months | 0.463678E+09 | 556.32 | 0.00 | -5.2 | 79468865.98 | 70.27 | 0.00 | -5.2 | ||
| Maximum of Months | 0.320170E+10 | 2384.61 | 37.02 | 19.87 | 0.129276E+09 | 70.40 | 37.02 | 19.87 |
Report: ZoneCoolingSummaryMonthly
For: G NW APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.137081E+09 | 321.14 | 04-JAN-19:10 | 8.62 | 1.36 | 78519690.02 | 46.51 | 03-JAN-21:10 | 8.62 | 1.36 |
| February | 0.111434E+09 | 303.99 | 20-FEB-23:00 | 9.40 | 2.31 | 72310806.47 | 54.62 | 21-FEB-21:19 | 14.80 | 4.41 |
| March | 0.168644E+09 | 380.72 | 16-MAR-06:03 | 6.47 | 1.47 | 83094939.72 | 57.42 | 15-MAR-20:10 | 6.47 | 1.47 |
| April | 0.717839E+09 | 1296.30 | 21-APR-16:30 | 30.85 | 14.66 | 0.110835E+09 | 70.40 | 28-APR-02:09 | 18.22 | 10.24 |
| May | 0.180359E+10 | 1864.79 | 19-MAY-17:30 | 33.85 | 16.05 | 0.127405E+09 | 70.39 | 04-MAY-23:10 | 33.85 | 16.05 |
| June | 0.270751E+10 | 2287.79 | 15-JUN-17:03 | 37.02 | 15.17 | 0.124621E+09 | 70.32 | 14-JUN-04:30 | 37.02 | 15.17 |
| July | 0.305513E+10 | 2220.98 | 26-JUL-17:50 | 34.60 | 19.79 | 0.128775E+09 | 70.30 | 11-JUL-03:00 | 34.60 | 19.79 |
| August | 0.295702E+10 | 2267.72 | 07-AUG-18:00 | 34.40 | 18.63 | 0.128775E+09 | 70.32 | 20-AUG-02:20 | 23.67 | 15.56 |
| September | 0.252613E+10 | 1890.46 | 20-SEP-17:00 | 32.80 | 17.01 | 0.124602E+09 | 70.35 | 25-SEP-02:30 | 11.40 | 9.34 |
| October | 0.146937E+10 | 1814.53 | 05-OCT-16:30 | 29.70 | 17.65 | 0.127040E+09 | 70.38 | 31-OCT-02:20 | 15.07 | 7.01 |
| November | 0.626606E+09 | 706.54 | 03-NOV-16:10 | 23.35 | 13.45 | 93994915.61 | 70.36 | 09-NOV-22:00 | 16.70 | 10.18 |
| December | 0.199319E+09 | 351.06 | 03-DEC-17:17 | 7.60 | 4.76 | 78645419.63 | 48.60 | 10-DEC-21:10 | 12.80 | 5.50 |
| Annual Sum or Average | 0.164797E+11 | 0.127862E+10 | ||||||||
| Minimum of Months | 0.111434E+09 | 303.99 | 6.47 | 1.36 | 72310806.47 | 46.51 | 6.47 | 1.36 | ||
| Maximum of Months | 0.305513E+10 | 2287.79 | 37.02 | 19.79 | 0.128775E+09 | 70.40 | 37.02 | 19.79 |
Report: ZoneCoolingSummaryMonthly
For: OFFICE
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.373880E+09 | 915.85 | 12-JAN-15:00 | 18.90 | 10.02 | 57627805.95 | 135.27 | 31-JAN-16:49 | 15.60 | 5.17 |
| February | 0.313059E+09 | 1080.23 | 22-FEB-13:50 | 21.52 | 7.85 | 57250433.38 | 141.59 | 08-FEB-09:09 | 21.52 | 7.85 |
| March | 0.319351E+09 | 1030.46 | 16-MAR-14:40 | 22.80 | 8.93 | 70978894.24 | 138.51 | 16-MAR-08:09 | 22.80 | 8.93 |
| April | 0.726681E+09 | 5786.99 | 27-APR-08:62 | 18.27 | 10.12 | 68860852.48 | 178.11 | 20-APR-07:10 | 18.27 | 10.12 |
| May | 0.139599E+10 | 6167.48 | 19-MAY-07:02 | 22.07 | 14.09 | 77384811.10 | 222.76 | 31-MAY-07:10 | 25.37 | 12.75 |
| June | 0.192853E+10 | 6455.85 | 22-JUN-07:02 | 21.20 | 15.49 | 77721048.75 | 218.75 | 09-JUN-07:10 | 21.20 | 15.49 |
| July | 0.193821E+10 | 6201.31 | 03-JUL-07:02 | 27.98 | 16.41 | 70693107.64 | 217.82 | 18-JUL-07:10 | 23.40 | 20.09 |
| August | 0.225186E+10 | 6436.83 | 28-AUG-07:02 | 22.38 | 15.17 | 81259142.16 | 217.47 | 07-AUG-07:10 | 22.38 | 15.17 |
| September | 0.203685E+10 | 6593.89 | 25-SEP-07:01 | 13.77 | 9.50 | 70627363.98 | 218.70 | 15-SEP-07:10 | 13.77 | 9.50 |
| October | 0.162496E+10 | 6630.52 | 23-OCT-07:01 | 13.27 | 9.81 | 73723791.30 | 220.26 | 05-OCT-07:10 | 13.27 | 9.81 |
| November | 0.986059E+09 | 6122.95 | 10-NOV-09:02 | 18.48 | 11.84 | 66803819.06 | 175.06 | 10-NOV-08:09 | 18.48 | 11.84 |
| December | 0.518971E+09 | 702.13 | 27-DEC-08:02 | -3.4 | -4.3 | 58867619.51 | 134.34 | 11-DEC-10:50 | -3.4 | -4.3 |
| Annual Sum or Average | 0.144144E+11 | 0.831799E+09 | ||||||||
| Minimum of Months | 0.313059E+09 | 702.13 | -3.4 | -4.3 | 57250433.38 | 134.34 | -3.4 | -4.3 | ||
| Maximum of Months | 0.225186E+10 | 6630.52 | 27.98 | 16.41 | 81259142.16 | 222.76 | 25.37 | 20.09 |
Report: ZoneCoolingSummaryMonthly
For: G NE APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.119089E+09 | 275.46 | 04-JAN-17:50 | 10.28 | 2.28 | 78242162.77 | 45.81 | 03-JAN-21:10 | 10.28 | 2.28 |
| February | 0.124472E+09 | 329.60 | 21-FEB-08:15 | 8.33 | 2.46 | 72144421.23 | 54.05 | 21-FEB-21:30 | 14.70 | 4.40 |
| March | 0.195419E+09 | 380.71 | 16-MAR-06:03 | 6.47 | 1.47 | 82461876.89 | 56.90 | 15-MAR-20:10 | 6.47 | 1.47 |
| April | 0.729020E+09 | 1153.48 | 21-APR-15:10 | 32.02 | 15.38 | 0.111198E+09 | 70.40 | 09-APR-22:49 | 32.02 | 15.38 |
| May | 0.182402E+10 | 1514.88 | 19-MAY-17:17 | 34.03 | 16.20 | 0.127579E+09 | 70.39 | 07-MAY-00:20 | 34.03 | 16.20 |
| June | 0.275077E+10 | 1932.19 | 15-JUN-17:00 | 37.20 | 15.32 | 0.124621E+09 | 70.32 | 14-JUN-04:30 | 37.20 | 15.32 |
| July | 0.308703E+10 | 1984.57 | 03-JUL-17:00 | 38.30 | 18.83 | 0.128775E+09 | 70.30 | 11-JUL-03:00 | 23.30 | 15.50 |
| August | 0.298808E+10 | 1983.41 | 07-AUG-18:00 | 34.40 | 18.63 | 0.128775E+09 | 70.32 | 20-AUG-02:20 | 23.67 | 15.56 |
| September | 0.253418E+10 | 1575.77 | 02-SEP-16:40 | 30.53 | 18.16 | 0.124591E+09 | 70.32 | 28-SEP-23:00 | 23.30 | 12.43 |
| October | 0.141540E+10 | 1458.82 | 05-OCT-16:03 | 30.63 | 17.38 | 0.126781E+09 | 70.38 | 27-OCT-22:00 | 13.90 | 10.08 |
| November | 0.617372E+09 | 518.04 | 16-NOV-07:00 | 1.70 | -0.1 | 93119323.29 | 70.40 | 08-NOV-21:10 | 1.70 | -0.1 |
| December | 0.193621E+09 | 341.00 | 14-DEC-18:40 | 8.00 | 5.92 | 78464170.20 | 49.12 | 10-DEC-21:19 | 8.00 | 5.92 |
| Annual Sum or Average | 0.165785E+11 | 0.127675E+10 | ||||||||
| Minimum of Months | 0.119089E+09 | 275.46 | 1.70 | -0.1 | 72144421.23 | 45.81 | 1.70 | -0.1 | ||
| Maximum of Months | 0.308703E+10 | 1984.57 | 38.30 | 18.83 | 0.128775E+09 | 70.40 | 37.20 | 16.20 |
Report: ZoneCoolingSummaryMonthly
For: G N1 APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.313452E+09 | 375.49 | 08-JAN-20:00 | 6.70 | 1.85 | 78896501.38 | 50.13 | 03-JAN-21:10 | 6.70 | 1.85 |
| February | 0.250924E+09 | 374.44 | 22-FEB-01:30 | 6.70 | 0.71 | 73214402.15 | 55.59 | 21-FEB-21:19 | 6.70 | 0.71 |
| March | 0.341407E+09 | 421.56 | 17-MAR-21:00 | 5.00 | -1.0 | 84641375.42 | 59.07 | 15-MAR-21:30 | 5.00 | -1.0 |
| April | 0.686017E+09 | 932.12 | 21-APR-17:07 | 30.60 | 14.09 | 0.114789E+09 | 70.39 | 03-APR-23:40 | 30.60 | 14.09 |
| May | 0.157532E+10 | 1225.27 | 19-MAY-17:30 | 33.85 | 16.05 | 0.128297E+09 | 70.38 | 05-MAY-00:00 | 33.85 | 16.05 |
| June | 0.225427E+10 | 1525.58 | 15-JUN-17:05 | 37.02 | 15.17 | 0.124621E+09 | 70.32 | 14-JUN-04:30 | 37.02 | 15.17 |
| July | 0.252167E+10 | 1529.36 | 03-JUL-17:00 | 38.30 | 18.83 | 0.128775E+09 | 70.30 | 11-JUL-03:00 | 23.30 | 15.50 |
| August | 0.242927E+10 | 1578.65 | 07-AUG-18:00 | 34.40 | 18.63 | 0.128775E+09 | 70.32 | 20-AUG-02:20 | 23.67 | 15.56 |
| September | 0.207647E+10 | 1253.01 | 20-SEP-17:17 | 32.43 | 16.78 | 0.124621E+09 | 70.37 | 25-SEP-04:10 | 10.32 | 8.96 |
| October | 0.132920E+10 | 1173.42 | 05-OCT-16:17 | 30.17 | 17.52 | 0.128102E+09 | 70.37 | 31-OCT-22:10 | 10.60 | 4.91 |
| November | 0.734287E+09 | 580.39 | 17-NOV-06:00 | -0.6 | -2.9 | 98422910.88 | 70.38 | 09-NOV-23:30 | -0.6 | -2.9 |
| December | 0.385447E+09 | 404.22 | 09-DEC-22:50 | 5.65 | 1.30 | 79308690.06 | 51.65 | 10-DEC-21:10 | 12.80 | 5.50 |
| Annual Sum or Average | 0.148977E+11 | 0.129247E+10 | ||||||||
| Minimum of Months | 0.250924E+09 | 374.44 | -0.6 | -2.9 | 73214402.15 | 50.13 | -0.6 | -2.9 | ||
| Maximum of Months | 0.252167E+10 | 1578.65 | 38.30 | 18.83 | 0.128775E+09 | 70.39 | 37.02 | 16.05 |
Report: ZoneCoolingSummaryMonthly
For: G N2 APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.311658E+09 | 375.23 | 08-JAN-20:00 | 6.70 | 1.85 | 78874991.35 | 50.05 | 03-JAN-21:10 | 6.70 | 1.85 |
| February | 0.251932E+09 | 374.51 | 22-FEB-01:30 | 6.70 | 0.71 | 73221748.82 | 55.61 | 21-FEB-21:19 | 6.70 | 0.71 |
| March | 0.341192E+09 | 421.22 | 17-MAR-21:00 | 5.00 | -1.0 | 84645189.27 | 59.01 | 15-MAR-21:30 | 5.00 | -1.0 |
| April | 0.690206E+09 | 931.69 | 21-APR-17:10 | 30.60 | 14.09 | 0.114859E+09 | 70.38 | 05-APR-23:19 | 30.60 | 14.09 |
| May | 0.157858E+10 | 1221.06 | 19-MAY-17:30 | 33.85 | 16.05 | 0.128308E+09 | 70.39 | 03-MAY-01:00 | 33.85 | 16.05 |
| June | 0.225677E+10 | 1521.07 | 15-JUN-17:08 | 37.02 | 15.17 | 0.124621E+09 | 70.32 | 14-JUN-04:30 | 37.02 | 15.17 |
| July | 0.252322E+10 | 1530.17 | 03-JUL-17:00 | 38.30 | 18.83 | 0.128775E+09 | 70.30 | 11-JUL-03:00 | 23.30 | 15.50 |
| August | 0.243097E+10 | 1572.89 | 07-AUG-18:00 | 34.40 | 18.63 | 0.128775E+09 | 70.32 | 20-AUG-02:20 | 23.67 | 15.56 |
| September | 0.207728E+10 | 1248.88 | 20-SEP-17:05 | 32.62 | 16.90 | 0.124621E+09 | 70.37 | 30-SEP-05:00 | 8.30 | 5.77 |
| October | 0.132699E+10 | 1169.12 | 05-OCT-16:17 | 30.17 | 17.52 | 0.128087E+09 | 70.38 | 31-OCT-21:00 | 10.60 | 4.98 |
| November | 0.733658E+09 | 580.26 | 17-NOV-06:00 | -0.6 | -2.9 | 98349760.96 | 70.39 | 08-NOV-21:19 | -0.6 | -2.9 |
| December | 0.385465E+09 | 404.27 | 09-DEC-22:50 | 5.65 | 1.30 | 79309401.73 | 51.72 | 10-DEC-21:10 | 12.80 | 5.50 |
| Annual Sum or Average | 0.149079E+11 | 0.129245E+10 | ||||||||
| Minimum of Months | 0.251932E+09 | 374.51 | -0.6 | -2.9 | 73221748.82 | 50.05 | -0.6 | -2.9 | ||
| Maximum of Months | 0.252322E+10 | 1572.89 | 38.30 | 18.83 | 0.128775E+09 | 70.39 | 37.02 | 16.05 |
Report: ZoneCoolingSummaryMonthly
For: G S1 APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.966069E+09 | 711.93 | 04-JAN-14:00 | 11.70 | 3.46 | 96382548.43 | 70.34 | 07-JAN-17:49 | 13.07 | 5.64 |
| February | 0.754241E+09 | 608.31 | 22-FEB-13:50 | 21.52 | 7.85 | 86801089.78 | 70.38 | 21-FEB-19:49 | 21.52 | 7.85 |
| March | 0.673081E+09 | 563.45 | 18-MAR-06:00 | 0.00 | -3.7 | 94523989.20 | 70.38 | 15-MAR-21:30 | 0.00 | -3.7 |
| April | 0.102765E+10 | 1130.00 | 21-APR-15:10 | 32.02 | 15.38 | 0.118540E+09 | 70.40 | 03-APR-04:10 | 32.02 | 15.38 |
| May | 0.167411E+10 | 1242.99 | 19-MAY-17:17 | 34.03 | 16.20 | 0.125413E+09 | 70.37 | 01-MAY-23:30 | 34.03 | 16.20 |
| June | 0.221783E+10 | 1441.49 | 15-JUN-17:05 | 37.02 | 15.17 | 0.120422E+09 | 70.32 | 14-JUN-04:30 | 37.02 | 15.17 |
| July | 0.254865E+10 | 1533.11 | 03-JUL-17:00 | 38.30 | 18.83 | 0.129276E+09 | 70.30 | 11-JUL-03:00 | 23.30 | 15.50 |
| August | 0.268970E+10 | 1613.27 | 07-AUG-18:00 | 34.40 | 18.63 | 0.123963E+09 | 70.32 | 20-AUG-02:20 | 23.67 | 15.56 |
| September | 0.274271E+10 | 1754.34 | 19-SEP-14:10 | 33.80 | 16.79 | 0.123963E+09 | 70.32 | 26-SEP-19:49 | 23.40 | 12.15 |
| October | 0.229809E+10 | 1701.63 | 01-OCT-15:10 | 32.62 | 15.84 | 0.127474E+09 | 70.37 | 07-OCT-03:09 | 10.40 | 8.57 |
| November | 0.153813E+10 | 1413.10 | 09-NOV-14:00 | 23.30 | 12.45 | 0.115889E+09 | 70.38 | 13-NOV-00:30 | 7.75 | 3.84 |
| December | 0.103597E+10 | 675.87 | 19-DEC-04:10 | -3.9 | -7.3 | 96834024.77 | 70.31 | 23-DEC-17:40 | 13.67 | 4.93 |
| Annual Sum or Average | 0.201662E+11 | 0.135948E+10 | ||||||||
| Minimum of Months | 0.673081E+09 | 563.45 | -3.9 | -7.3 | 86801089.78 | 70.30 | 0.00 | -3.7 | ||
| Maximum of Months | 0.274271E+10 | 1754.34 | 38.30 | 18.83 | 0.129276E+09 | 70.40 | 37.02 | 16.20 |
Report: ZoneCoolingSummaryMonthly
For: G S2 APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.970066E+09 | 734.65 | 04-JAN-14:00 | 11.70 | 3.46 | 96669842.58 | 70.39 | 07-JAN-17:00 | 12.80 | 5.50 |
| February | 0.768236E+09 | 641.01 | 22-FEB-13:50 | 21.52 | 7.85 | 87496804.11 | 70.37 | 21-FEB-19:00 | 21.52 | 7.85 |
| March | 0.696699E+09 | 577.74 | 16-MAR-15:10 | 22.70 | 8.66 | 95642493.72 | 70.37 | 26-MAR-17:40 | 21.67 | 8.63 |
| April | 0.112117E+10 | 1192.78 | 29-APR-16:05 | 31.02 | 13.95 | 0.119343E+09 | 70.39 | 01-APR-23:10 | 31.02 | 13.95 |
| May | 0.186635E+10 | 1366.69 | 21-MAY-16:20 | 32.73 | 18.75 | 0.125550E+09 | 70.37 | 08-MAY-05:10 | 32.73 | 18.75 |
| June | 0.247742E+10 | 1533.86 | 05-JUN-17:00 | 37.80 | 17.11 | 0.120422E+09 | 70.32 | 14-JUN-04:30 | 23.60 | 9.85 |
| July | 0.284079E+10 | 1658.28 | 02-JUL-18:00 | 36.10 | 18.22 | 0.129276E+09 | 70.30 | 11-JUL-03:00 | 23.30 | 15.50 |
| August | 0.297299E+10 | 1729.67 | 07-AUG-18:00 | 34.40 | 18.63 | 0.123963E+09 | 70.31 | 11-AUG-03:20 | 23.67 | 14.51 |
| September | 0.301008E+10 | 1844.85 | 19-SEP-14:10 | 33.80 | 16.79 | 0.123963E+09 | 70.32 | 26-SEP-19:49 | 23.40 | 12.15 |
| October | 0.247924E+10 | 1834.12 | 01-OCT-15:10 | 32.62 | 15.84 | 0.127488E+09 | 70.31 | 29-OCT-15:50 | 23.40 | 11.36 |
| November | 0.159764E+10 | 1455.77 | 09-NOV-14:00 | 23.30 | 12.45 | 0.116367E+09 | 70.38 | 16-NOV-21:40 | 6.83 | 1.96 |
| December | 0.104253E+10 | 677.40 | 19-DEC-04:10 | -3.9 | -7.3 | 97728382.10 | 70.35 | 17-DEC-20:10 | -3.9 | -7.3 |
| Annual Sum or Average | 0.218432E+11 | 0.136391E+10 | ||||||||
| Minimum of Months | 0.696699E+09 | 577.74 | -3.9 | -7.3 | 87496804.11 | 70.30 | -3.9 | -7.3 | ||
| Maximum of Months | 0.301008E+10 | 1844.85 | 37.80 | 18.75 | 0.129276E+09 | 70.39 | 32.73 | 18.75 |
Report: ZoneCoolingSummaryMonthly
For: M SW APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.883149E+09 | 1150.00 | 12-JAN-15:00 | 18.90 | 10.02 | 95008615.26 | 70.33 | 28-JAN-17:00 | 11.70 | 4.19 |
| February | 0.912396E+09 | 1690.79 | 20-FEB-16:10 | 23.12 | 8.59 | 90987175.43 | 70.32 | 12-FEB-19:30 | 23.12 | 8.59 |
| March | 0.109594E+10 | 1676.01 | 14-MAR-16:15 | 24.40 | 10.25 | 0.105948E+09 | 70.31 | 14-MAR-17:00 | 23.30 | 9.45 |
| April | 0.199853E+10 | 2349.42 | 21-APR-15:10 | 32.02 | 15.38 | 0.120376E+09 | 70.32 | 15-APR-03:00 | 32.02 | 15.38 |
| May | 0.281365E+10 | 2579.04 | 19-MAY-17:05 | 34.22 | 16.36 | 0.125485E+09 | 70.32 | 10-MAY-23:49 | 34.22 | 16.36 |
| June | 0.346406E+10 | 2806.21 | 15-JUN-17:00 | 37.20 | 15.32 | 0.120422E+09 | 70.32 | 14-JUN-04:30 | 37.20 | 15.32 |
| July | 0.350812E+10 | 2610.30 | 26-JUL-17:23 | 35.00 | 19.87 | 0.129276E+09 | 70.30 | 11-JUL-03:00 | 35.00 | 19.87 |
| August | 0.335348E+10 | 2553.73 | 07-AUG-16:10 | 37.12 | 17.89 | 0.123963E+09 | 70.31 | 20-AUG-02:20 | 23.67 | 15.56 |
| September | 0.309158E+10 | 2608.14 | 18-SEP-16:15 | 33.13 | 15.97 | 0.123908E+09 | 70.31 | 11-SEP-05:00 | 33.13 | 15.97 |
| October | 0.233590E+10 | 2552.57 | 05-OCT-16:03 | 30.63 | 17.38 | 0.126042E+09 | 70.31 | 07-OCT-23:30 | 13.60 | 11.40 |
| November | 0.133370E+10 | 1984.50 | 09-NOV-15:10 | 23.30 | 12.70 | 0.106650E+09 | 70.30 | 20-NOV-19:40 | 10.17 | 2.78 |
| December | 0.799988E+09 | 907.81 | 16-DEC-15:30 | 15.00 | 4.18 | 91704746.01 | 70.31 | 23-DEC-17:49 | 13.48 | 4.89 |
| Annual Sum or Average | 0.255905E+11 | 0.135977E+10 | ||||||||
| Minimum of Months | 0.799988E+09 | 907.81 | 15.00 | 4.18 | 90987175.43 | 70.30 | 10.17 | 2.78 | ||
| Maximum of Months | 0.350812E+10 | 2806.21 | 37.20 | 19.87 | 0.129276E+09 | 70.33 | 37.20 | 19.87 |
Report: ZoneCoolingSummaryMonthly
For: M NW APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.280832E+09 | 415.00 | 08-JAN-20:50 | 5.28 | 0.78 | 79984870.78 | 51.99 | 12-JAN-21:10 | 12.43 | 7.05 |
| February | 0.380223E+09 | 531.91 | 22-FEB-07:00 | 1.10 | -3.0 | 78736596.87 | 70.11 | 21-FEB-21:30 | 1.10 | -3.0 |
| March | 0.641311E+09 | 845.04 | 16-MAR-16:05 | 22.02 | 8.30 | 99810257.46 | 70.31 | 15-MAR-23:10 | 22.02 | 8.30 |
| April | 0.157186E+10 | 2107.68 | 21-APR-16:17 | 30.93 | 14.71 | 0.119419E+09 | 70.33 | 06-APR-02:49 | 30.93 | 14.71 |
| May | 0.271872E+10 | 2560.79 | 19-MAY-17:25 | 33.85 | 16.05 | 0.128460E+09 | 70.32 | 10-MAY-23:49 | 33.85 | 16.05 |
| June | 0.350495E+10 | 2909.20 | 15-JUN-17:00 | 37.20 | 15.32 | 0.124622E+09 | 70.32 | 14-JUN-04:30 | 37.20 | 15.32 |
| July | 0.348000E+10 | 2627.89 | 26-JUL-17:50 | 34.60 | 19.79 | 0.128775E+09 | 70.30 | 11-JUL-03:00 | 34.60 | 19.79 |
| August | 0.308333E+10 | 2514.21 | 07-AUG-18:00 | 34.40 | 18.63 | 0.128774E+09 | 70.31 | 20-AUG-02:20 | 23.67 | 15.56 |
| September | 0.240725E+10 | 2037.12 | 18-SEP-16:50 | 32.88 | 15.68 | 0.124484E+09 | 70.31 | 28-SEP-23:00 | 23.30 | 12.43 |
| October | 0.138336E+10 | 2018.78 | 05-OCT-16:30 | 29.70 | 17.65 | 0.125266E+09 | 70.32 | 20-OCT-01:49 | 13.27 | 8.20 |
| November | 0.547621E+09 | 720.32 | 03-NOV-16:05 | 23.35 | 13.45 | 91270880.45 | 70.31 | 09-NOV-21:00 | 18.90 | 11.06 |
| December | 0.247000E+09 | 387.54 | 09-DEC-22:40 | 6.30 | 1.69 | 79189842.93 | 51.06 | 10-DEC-21:19 | 12.80 | 5.53 |
| Annual Sum or Average | 0.202465E+11 | 0.130879E+10 | ||||||||
| Minimum of Months | 0.247000E+09 | 387.54 | 1.10 | -3.0 | 78736596.87 | 51.06 | 1.10 | -3.0 | ||
| Maximum of Months | 0.350495E+10 | 2909.20 | 37.20 | 19.79 | 0.128775E+09 | 70.33 | 37.20 | 19.79 |
Report: ZoneCoolingSummaryMonthly
For: M SE APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.864025E+09 | 952.83 | 12-JAN-15:00 | 18.90 | 10.02 | 94401331.81 | 70.31 | 13-JAN-18:00 | 13.30 | 6.51 |
| February | 0.932207E+09 | 1444.37 | 20-FEB-14:50 | 23.12 | 8.81 | 91493249.62 | 70.28 | 10-FEB-18:30 | 23.12 | 8.81 |
| March | 0.110334E+10 | 1384.04 | 16-MAR-15:10 | 22.70 | 8.66 | 0.105759E+09 | 70.32 | 08-MAR-22:40 | 22.70 | 8.66 |
| April | 0.204274E+10 | 2185.09 | 21-APR-15:10 | 32.02 | 15.38 | 0.120471E+09 | 70.32 | 01-APR-21:49 | 32.02 | 15.38 |
| May | 0.284649E+10 | 2194.87 | 19-MAY-14:00 | 35.00 | 17.23 | 0.125485E+09 | 70.32 | 08-MAY-03:49 | 35.00 | 17.23 |
| June | 0.350923E+10 | 2326.63 | 05-JUN-17:00 | 37.80 | 17.11 | 0.120422E+09 | 70.32 | 14-JUN-04:30 | 23.60 | 9.85 |
| July | 0.354267E+10 | 2259.34 | 03-JUL-17:00 | 38.30 | 18.83 | 0.129276E+09 | 70.30 | 11-JUL-03:00 | 23.30 | 15.50 |
| August | 0.338693E+10 | 2210.71 | 27-AUG-13:00 | 34.40 | 16.88 | 0.123962E+09 | 70.31 | 11-AUG-04:00 | 34.40 | 16.88 |
| September | 0.310073E+10 | 2308.08 | 19-SEP-13:30 | 33.35 | 16.80 | 0.123901E+09 | 70.31 | 26-SEP-19:49 | 23.40 | 12.15 |
| October | 0.228010E+10 | 2214.94 | 01-OCT-15:10 | 32.62 | 15.84 | 0.125769E+09 | 70.32 | 10-OCT-01:19 | 13.90 | 9.17 |
| November | 0.131008E+10 | 1767.19 | 09-NOV-14:00 | 23.30 | 12.45 | 0.106440E+09 | 70.32 | 09-NOV-02:20 | 23.30 | 12.45 |
| December | 0.796056E+09 | 680.37 | 16-DEC-15:10 | 15.00 | 4.18 | 91570481.45 | 70.27 | 16-DEC-16:19 | 14.43 | 3.97 |
| Annual Sum or Average | 0.257146E+11 | 0.135895E+10 | ||||||||
| Minimum of Months | 0.796056E+09 | 680.37 | 15.00 | 4.18 | 91493249.62 | 70.27 | 13.30 | 3.97 | ||
| Maximum of Months | 0.354267E+10 | 2326.63 | 38.30 | 18.83 | 0.129276E+09 | 70.32 | 35.00 | 17.23 |
Report: ZoneCoolingSummaryMonthly
For: M NE APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.276715E+09 | 399.56 | 08-JAN-20:30 | 5.85 | 1.21 | 79334988.88 | 50.86 | 12-JAN-21:10 | 12.43 | 7.05 |
| February | 0.405265E+09 | 535.57 | 22-FEB-07:00 | 1.10 | -3.0 | 78690562.50 | 70.03 | 21-FEB-21:30 | 1.10 | -3.0 |
| March | 0.632721E+09 | 573.02 | 22-MAR-16:10 | 23.80 | 8.77 | 99662398.31 | 70.30 | 09-MAR-22:49 | 23.80 | 8.77 |
| April | 0.160777E+10 | 1914.65 | 21-APR-15:10 | 32.02 | 15.38 | 0.119580E+09 | 70.32 | 01-APR-21:49 | 32.02 | 15.38 |
| May | 0.275149E+10 | 2049.67 | 19-MAY-17:20 | 34.03 | 16.20 | 0.128494E+09 | 70.32 | 08-MAY-03:39 | 34.03 | 16.20 |
| June | 0.355035E+10 | 2408.57 | 15-JUN-17:00 | 37.20 | 15.32 | 0.124622E+09 | 70.32 | 14-JUN-04:30 | 37.20 | 15.32 |
| July | 0.351468E+10 | 2261.34 | 03-JUL-17:00 | 38.30 | 18.83 | 0.128775E+09 | 70.30 | 11-JUL-03:00 | 23.30 | 15.50 |
| August | 0.311661E+10 | 2147.63 | 07-AUG-18:00 | 34.40 | 18.63 | 0.128774E+09 | 70.31 | 11-AUG-04:00 | 23.30 | 14.99 |
| September | 0.241534E+10 | 1623.52 | 02-SEP-16:40 | 30.53 | 18.16 | 0.124469E+09 | 70.32 | 30-SEP-02:30 | 11.95 | 7.15 |
| October | 0.132091E+10 | 1532.75 | 05-OCT-16:03 | 30.63 | 17.38 | 0.124893E+09 | 70.32 | 01-OCT-02:00 | 30.63 | 17.38 |
| November | 0.539438E+09 | 494.68 | 25-NOV-07:10 | 2.38 | 1.06 | 90247675.73 | 70.31 | 09-NOV-21:00 | 2.38 | 1.06 |
| December | 0.242281E+09 | 387.23 | 09-DEC-22:40 | 6.30 | 1.69 | 78937142.67 | 51.82 | 10-DEC-21:19 | 12.80 | 5.53 |
| Annual Sum or Average | 0.203736E+11 | 0.130648E+10 | ||||||||
| Minimum of Months | 0.242281E+09 | 387.23 | 1.10 | -3.0 | 78690562.50 | 50.86 | 1.10 | -3.0 | ||
| Maximum of Months | 0.355035E+10 | 2408.57 | 38.30 | 18.83 | 0.128775E+09 | 70.32 | 37.20 | 17.38 |
Report: ZoneCoolingSummaryMonthly
For: M N1 APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.575466E+09 | 485.04 | 02-JAN-02:40 | 2.77 | 1.33 | 81617727.63 | 54.48 | 12-JAN-21:10 | 12.43 | 7.05 |
| February | 0.557200E+09 | 551.97 | 22-FEB-07:00 | 1.10 | -3.0 | 82688354.58 | 70.33 | 21-FEB-21:30 | 1.10 | -3.0 |
| March | 0.715317E+09 | 568.93 | 18-MAR-06:00 | 0.00 | -3.7 | 0.105800E+09 | 70.30 | 16-MAR-02:20 | 0.00 | -3.7 |
| April | 0.135544E+10 | 1411.77 | 21-APR-17:07 | 30.60 | 14.09 | 0.121502E+09 | 70.33 | 01-APR-21:49 | 30.60 | 14.09 |
| May | 0.218884E+10 | 1571.90 | 19-MAY-17:40 | 33.67 | 15.89 | 0.128692E+09 | 70.32 | 10-MAY-23:49 | 33.67 | 15.89 |
| June | 0.272622E+10 | 1806.57 | 15-JUN-17:03 | 37.02 | 15.17 | 0.124622E+09 | 70.32 | 14-JUN-04:30 | 37.02 | 15.17 |
| July | 0.275100E+10 | 1706.33 | 02-JUL-18:00 | 36.10 | 18.22 | 0.128775E+09 | 70.30 | 11-JUL-03:00 | 23.30 | 15.50 |
| August | 0.246956E+10 | 1660.36 | 07-AUG-18:00 | 34.40 | 18.63 | 0.128775E+09 | 70.31 | 11-AUG-03:20 | 23.67 | 14.51 |
| September | 0.197503E+10 | 1261.99 | 02-SEP-16:40 | 30.53 | 18.16 | 0.124591E+09 | 70.32 | 28-SEP-23:00 | 23.30 | 12.43 |
| October | 0.127634E+10 | 1212.66 | 05-OCT-16:17 | 30.17 | 17.52 | 0.127506E+09 | 70.31 | 22-OCT-05:00 | 11.70 | 8.86 |
| November | 0.706522E+09 | 563.47 | 17-NOV-05:20 | -0.2 | -2.7 | 97054296.99 | 70.27 | 09-NOV-21:10 | -0.2 | -2.7 |
| December | 0.498571E+09 | 481.98 | 12-DEC-03:00 | 2.80 | -0.7 | 80589686.40 | 54.91 | 10-DEC-21:19 | 2.80 | -0.7 |
| Annual Sum or Average | 0.177955E+11 | 0.133221E+10 | ||||||||
| Minimum of Months | 0.498571E+09 | 481.98 | -0.2 | -3.7 | 80589686.40 | 54.48 | -0.2 | -3.7 | ||
| Maximum of Months | 0.275100E+10 | 1806.57 | 37.02 | 18.63 | 0.128775E+09 | 70.33 | 37.02 | 15.89 |
Report: ZoneCoolingSummaryMonthly
For: M N2 APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.572727E+09 | 484.44 | 02-JAN-02:40 | 2.77 | 1.33 | 81552890.72 | 54.40 | 12-JAN-21:10 | 12.43 | 7.05 |
| February | 0.558809E+09 | 552.24 | 22-FEB-07:00 | 1.10 | -3.0 | 82727588.92 | 70.32 | 21-FEB-21:30 | 1.10 | -3.0 |
| March | 0.717756E+09 | 568.86 | 18-MAR-06:00 | 0.00 | -3.7 | 0.105863E+09 | 70.32 | 09-MAR-21:30 | 0.00 | -3.7 |
| April | 0.136087E+10 | 1410.10 | 21-APR-17:07 | 30.60 | 14.09 | 0.121523E+09 | 70.32 | 01-APR-21:49 | 30.60 | 14.09 |
| May | 0.219125E+10 | 1564.82 | 19-MAY-17:40 | 33.67 | 15.89 | 0.128693E+09 | 70.32 | 02-MAY-02:09 | 33.67 | 15.89 |
| June | 0.272832E+10 | 1800.18 | 15-JUN-17:03 | 37.02 | 15.17 | 0.124622E+09 | 70.32 | 14-JUN-04:30 | 37.02 | 15.17 |
| July | 0.275256E+10 | 1703.54 | 02-JUL-18:00 | 36.10 | 18.22 | 0.128775E+09 | 70.30 | 11-JUL-03:00 | 23.30 | 15.50 |
| August | 0.247122E+10 | 1653.73 | 07-AUG-18:00 | 34.40 | 18.63 | 0.128775E+09 | 70.31 | 11-AUG-03:20 | 23.67 | 14.51 |
| September | 0.197601E+10 | 1258.79 | 02-SEP-16:40 | 30.53 | 18.16 | 0.124590E+09 | 70.32 | 28-SEP-23:00 | 23.30 | 12.43 |
| October | 0.127484E+10 | 1206.80 | 05-OCT-16:17 | 30.17 | 17.52 | 0.127484E+09 | 70.31 | 23-OCT-20:30 | 11.40 | 6.60 |
| November | 0.705812E+09 | 560.87 | 17-NOV-05:10 | -0.1 | -2.6 | 96959299.57 | 70.29 | 02-NOV-21:19 | -0.1 | -2.6 |
| December | 0.497959E+09 | 482.13 | 12-DEC-03:00 | 2.80 | -0.7 | 80586294.45 | 55.01 | 10-DEC-21:19 | 2.80 | -0.7 |
| Annual Sum or Average | 0.178081E+11 | 0.133215E+10 | ||||||||
| Minimum of Months | 0.497959E+09 | 482.13 | -0.1 | -3.7 | 80586294.45 | 54.40 | -0.1 | -3.7 | ||
| Maximum of Months | 0.275256E+10 | 1800.18 | 37.02 | 18.63 | 0.128775E+09 | 70.32 | 37.02 | 15.89 |
Report: ZoneCoolingSummaryMonthly
For: M S1 APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.118559E+10 | 1187.20 | 04-JAN-14:00 | 11.70 | 3.46 | 0.106598E+09 | 70.33 | 22-JAN-19:10 | 9.22 | 5.24 |
| February | 0.113100E+10 | 1412.33 | 20-FEB-14:50 | 23.12 | 8.81 | 0.100681E+09 | 70.31 | 21-FEB-00:30 | 9.75 | 2.94 |
| March | 0.122503E+10 | 1319.84 | 16-MAR-15:10 | 22.70 | 8.66 | 0.113365E+09 | 70.33 | 29-MAR-19:30 | 11.40 | 2.88 |
| April | 0.180484E+10 | 1637.37 | 21-APR-15:10 | 32.02 | 15.38 | 0.122266E+09 | 70.32 | 01-APR-21:49 | 32.02 | 15.38 |
| May | 0.228504E+10 | 1599.66 | 14-MAY-16:10 | 32.12 | 13.71 | 0.125677E+09 | 70.32 | 10-MAY-23:49 | 32.12 | 13.71 |
| June | 0.268515E+10 | 1712.63 | 05-JUN-17:00 | 37.80 | 17.11 | 0.120422E+09 | 70.32 | 14-JUN-04:30 | 23.60 | 9.85 |
| July | 0.277897E+10 | 1706.01 | 02-JUL-18:00 | 36.10 | 18.22 | 0.129276E+09 | 70.30 | 11-JUL-03:00 | 23.30 | 15.50 |
| August | 0.274052E+10 | 1687.94 | 07-AUG-18:00 | 34.40 | 18.63 | 0.123963E+09 | 70.31 | 11-AUG-03:20 | 23.67 | 14.51 |
| September | 0.266558E+10 | 1870.05 | 19-SEP-14:10 | 33.80 | 16.79 | 0.123963E+09 | 70.32 | 30-SEP-06:10 | 8.95 | 6.15 |
| October | 0.228426E+10 | 1854.34 | 01-OCT-15:10 | 32.62 | 15.84 | 0.127279E+09 | 70.32 | 25-OCT-00:20 | 10.20 | 7.12 |
| November | 0.158767E+10 | 1673.24 | 09-NOV-14:00 | 23.30 | 12.45 | 0.113931E+09 | 70.32 | 03-NOV-01:30 | 23.30 | 12.45 |
| December | 0.116212E+10 | 1009.77 | 16-DEC-14:40 | 15.00 | 4.23 | 0.102571E+09 | 70.33 | 23-DEC-20:19 | 9.83 | 3.14 |
| Annual Sum or Average | 0.235358E+11 | 0.140999E+10 | ||||||||
| Minimum of Months | 0.113100E+10 | 1009.77 | 11.70 | 3.46 | 0.100681E+09 | 70.30 | 8.95 | 2.88 | ||
| Maximum of Months | 0.277897E+10 | 1870.05 | 37.80 | 18.63 | 0.129276E+09 | 70.33 | 32.12 | 15.50 |
Report: ZoneCoolingSummaryMonthly
For: M S2 APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.118562E+10 | 1194.22 | 04-JAN-14:00 | 11.70 | 3.46 | 0.106538E+09 | 70.33 | 11-JAN-21:19 | 11.83 | 6.14 |
| February | 0.113560E+10 | 1418.61 | 20-FEB-14:50 | 23.12 | 8.81 | 0.100760E+09 | 70.32 | 08-FEB-03:09 | 23.12 | 8.81 |
| March | 0.122948E+10 | 1319.98 | 16-MAR-15:10 | 22.70 | 8.66 | 0.113372E+09 | 70.32 | 08-MAR-00:30 | 22.70 | 8.66 |
| April | 0.180992E+10 | 1639.54 | 21-APR-15:10 | 32.02 | 15.38 | 0.122272E+09 | 70.32 | 14-APR-05:10 | 32.02 | 15.38 |
| May | 0.228748E+10 | 1595.79 | 14-MAY-16:05 | 32.12 | 13.71 | 0.125676E+09 | 70.32 | 06-MAY-03:20 | 32.12 | 13.71 |
| June | 0.268730E+10 | 1707.86 | 05-JUN-17:00 | 37.80 | 17.11 | 0.120422E+09 | 70.32 | 14-JUN-04:30 | 23.60 | 9.85 |
| July | 0.278057E+10 | 1703.49 | 02-JUL-18:00 | 36.10 | 18.22 | 0.129276E+09 | 70.30 | 11-JUL-03:00 | 23.30 | 15.50 |
| August | 0.274218E+10 | 1680.47 | 07-AUG-18:00 | 34.40 | 18.63 | 0.123963E+09 | 70.31 | 11-AUG-03:20 | 23.67 | 14.51 |
| September | 0.266643E+10 | 1872.37 | 19-SEP-14:10 | 33.80 | 16.79 | 0.123963E+09 | 70.32 | 25-SEP-05:00 | 10.00 | 8.46 |
| October | 0.228194E+10 | 1852.95 | 01-OCT-15:10 | 32.62 | 15.84 | 0.127272E+09 | 70.32 | 07-OCT-00:30 | 11.70 | 9.48 |
| November | 0.158839E+10 | 1677.31 | 09-NOV-14:00 | 23.30 | 12.45 | 0.113895E+09 | 70.32 | 01-NOV-02:00 | 23.30 | 12.45 |
| December | 0.116335E+10 | 1016.62 | 16-DEC-14:50 | 15.00 | 4.20 | 0.102565E+09 | 70.32 | 08-DEC-20:19 | 15.00 | 4.20 |
| Annual Sum or Average | 0.235583E+11 | 0.140997E+10 | ||||||||
| Minimum of Months | 0.113560E+10 | 1016.62 | 11.70 | 3.46 | 0.100760E+09 | 70.30 | 10.00 | 4.20 | ||
| Maximum of Months | 0.278057E+10 | 1872.37 | 37.80 | 18.63 | 0.129276E+09 | 70.33 | 32.12 | 15.50 |
Report: ZoneCoolingSummaryMonthly
For: T SW APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.461835E+09 | 1711.96 | 12-JAN-15:10 | 18.90 | 10.04 | 85978545.62 | 70.35 | 11-JAN-18:00 | 18.90 | 10.04 |
| February | 0.562960E+09 | 2083.79 | 20-FEB-16:10 | 23.12 | 8.59 | 79953528.59 | 70.37 | 04-FEB-19:10 | 23.12 | 8.59 |
| March | 0.752871E+09 | 2177.57 | 14-MAR-16:15 | 24.40 | 10.25 | 90811648.81 | 70.32 | 07-MAR-21:30 | 24.40 | 10.25 |
| April | 0.190754E+10 | 3229.24 | 21-APR-15:10 | 32.02 | 15.38 | 0.109917E+09 | 70.39 | 02-APR-04:40 | 32.02 | 15.38 |
| May | 0.299834E+10 | 3523.05 | 19-MAY-17:05 | 34.22 | 16.36 | 0.121734E+09 | 70.37 | 13-MAY-02:30 | 34.22 | 16.36 |
| June | 0.403296E+10 | 3902.41 | 15-JUN-16:40 | 37.40 | 15.43 | 0.120206E+09 | 70.38 | 13-JUN-04:40 | 37.40 | 15.43 |
| July | 0.408402E+10 | 3574.85 | 06-JUL-17:00 | 35.00 | 19.59 | 0.129255E+09 | 70.30 | 11-JUL-03:00 | 23.30 | 15.50 |
| August | 0.377224E+10 | 3592.53 | 07-AUG-16:01 | 37.12 | 17.89 | 0.123717E+09 | 70.33 | 14-AUG-02:49 | 17.30 | 16.84 |
| September | 0.324111E+10 | 3521.14 | 19-SEP-15:30 | 33.60 | 16.22 | 0.121408E+09 | 70.35 | 02-SEP-05:49 | 33.60 | 16.22 |
| October | 0.207961E+10 | 3433.80 | 05-OCT-16:03 | 30.63 | 17.38 | 0.112365E+09 | 70.38 | 30-OCT-23:40 | 19.23 | 8.84 |
| November | 0.852315E+09 | 2387.75 | 09-NOV-15:10 | 23.30 | 12.70 | 89004001.86 | 70.38 | 09-NOV-22:10 | 18.53 | 10.92 |
| December | 0.419054E+09 | 1360.87 | 16-DEC-15:30 | 15.00 | 4.18 | 84524285.97 | 70.27 | 16-DEC-16:19 | 14.43 | 3.97 |
| Annual Sum or Average | 0.251649E+11 | 0.126887E+10 | ||||||||
| Minimum of Months | 0.419054E+09 | 1360.87 | 15.00 | 4.18 | 79953528.59 | 70.27 | 14.43 | 3.97 | ||
| Maximum of Months | 0.408402E+10 | 3902.41 | 37.40 | 19.59 | 0.129255E+09 | 70.39 | 37.40 | 16.84 |
Report: ZoneCoolingSummaryMonthly
For: T NW APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 96125545.08 | 327.26 | 27-JAN-17:35 | 8.53 | 0.47 | 78934250.61 | 50.10 | 12-JAN-18:10 | 8.53 | 0.47 |
| February | 0.145637E+09 | 728.57 | 19-FEB-17:10 | 22.02 | 8.11 | 75089776.32 | 64.90 | 20-FEB-21:10 | 14.72 | 5.21 |
| March | 0.319193E+09 | 1153.12 | 14-MAR-16:40 | 24.40 | 10.18 | 89973760.24 | 70.27 | 15-MAR-20:10 | 19.08 | 7.09 |
| April | 0.149728E+10 | 2856.66 | 21-APR-15:10 | 32.02 | 15.38 | 0.109274E+09 | 70.38 | 10-APR-00:20 | 32.02 | 15.38 |
| May | 0.289603E+10 | 3498.72 | 19-MAY-17:05 | 34.22 | 16.36 | 0.124709E+09 | 70.38 | 21-MAY-02:00 | 17.80 | 7.29 |
| June | 0.407385E+10 | 4026.40 | 15-JUN-17:00 | 37.20 | 15.32 | 0.124436E+09 | 70.38 | 01-JUN-05:40 | 37.20 | 15.32 |
| July | 0.404994E+10 | 3632.73 | 06-JUL-17:00 | 35.00 | 19.59 | 0.128755E+09 | 70.33 | 05-JUL-02:00 | 35.00 | 19.59 |
| August | 0.346647E+10 | 3428.44 | 07-AUG-16:01 | 37.12 | 17.89 | 0.128497E+09 | 70.37 | 30-AUG-02:49 | 17.88 | 13.67 |
| September | 0.250464E+10 | 2777.07 | 18-SEP-16:30 | 33.05 | 15.87 | 0.121613E+09 | 70.37 | 29-SEP-03:00 | 18.90 | 12.67 |
| October | 0.114922E+10 | 2756.14 | 05-OCT-16:17 | 30.17 | 17.52 | 0.109990E+09 | 70.39 | 22-OCT-00:10 | 17.70 | 11.10 |
| November | 0.192020E+09 | 886.21 | 09-NOV-16:10 | 23.22 | 12.98 | 81976869.33 | 69.04 | 09-NOV-21:10 | 19.82 | 11.24 |
| December | 78757694.90 | 308.26 | 16-DEC-18:25 | 9.15 | 1.93 | 78233169.51 | 42.51 | 18-DEC-22:49 | 0.87 | -4.6 |
| Annual Sum or Average | 0.204692E+11 | 0.125148E+10 | ||||||||
| Minimum of Months | 78757694.90 | 308.26 | 8.53 | 0.47 | 75089776.32 | 42.51 | 0.87 | -4.6 | ||
| Maximum of Months | 0.407385E+10 | 4026.40 | 37.20 | 19.59 | 0.128755E+09 | 70.39 | 37.20 | 19.59 |
Report: ZoneCoolingSummaryMonthly
For: T SE APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.427858E+09 | 1427.18 | 12-JAN-15:00 | 18.90 | 10.02 | 85394046.37 | 70.31 | 12-JAN-18:40 | 15.77 | 8.63 |
| February | 0.562477E+09 | 1758.35 | 20-FEB-14:50 | 23.12 | 8.81 | 79927242.37 | 70.35 | 19-FEB-19:00 | 23.12 | 8.81 |
| March | 0.734095E+09 | 1657.00 | 16-MAR-14:10 | 22.80 | 9.24 | 90102936.17 | 70.37 | 07-MAR-21:40 | 22.80 | 9.24 |
| April | 0.191265E+10 | 3004.49 | 21-APR-14:10 | 32.20 | 15.26 | 0.110083E+09 | 70.38 | 03-APR-04:40 | 32.20 | 15.26 |
| May | 0.301391E+10 | 3144.89 | 19-MAY-14:00 | 35.00 | 17.23 | 0.121919E+09 | 70.38 | 12-MAY-01:19 | 35.00 | 17.23 |
| June | 0.408078E+10 | 3263.95 | 21-JUN-13:00 | 35.60 | 16.94 | 0.120169E+09 | 70.34 | 28-JUN-01:39 | 17.57 | 15.99 |
| July | 0.411711E+10 | 3137.46 | 26-JUL-14:00 | 36.70 | 20.76 | 0.129263E+09 | 70.30 | 11-JUL-03:00 | 36.70 | 20.76 |
| August | 0.380660E+10 | 3085.65 | 27-AUG-13:00 | 34.40 | 16.88 | 0.123714E+09 | 70.36 | 30-AUG-03:20 | 17.97 | 13.79 |
| September | 0.324123E+10 | 3193.73 | 19-SEP-13:30 | 33.35 | 16.80 | 0.121477E+09 | 70.37 | 12-SEP-01:30 | 33.35 | 16.80 |
| October | 0.200810E+10 | 2924.40 | 03-OCT-13:40 | 32.07 | 19.44 | 0.111662E+09 | 70.32 | 04-OCT-02:49 | 18.98 | 17.35 |
| November | 0.812148E+09 | 2080.43 | 09-NOV-14:00 | 23.30 | 12.45 | 88633374.34 | 70.38 | 23-NOV-18:10 | 16.32 | 6.88 |
| December | 0.397079E+09 | 1022.49 | 16-DEC-14:40 | 15.00 | 4.23 | 84136750.51 | 70.38 | 31-DEC-16:49 | 13.07 | 4.38 |
| Annual Sum or Average | 0.251140E+11 | 0.126648E+10 | ||||||||
| Minimum of Months | 0.397079E+09 | 1022.49 | 15.00 | 4.23 | 79927242.37 | 70.30 | 13.07 | 4.38 | ||
| Maximum of Months | 0.411711E+10 | 3263.95 | 36.70 | 20.76 | 0.129263E+09 | 70.38 | 36.70 | 20.76 |
Report: ZoneCoolingSummaryMonthly
For: T NE APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 66792515.01 | 255.42 | 17-JAN-16:10 | 10.92 | 5.28 | 78304036.79 | 45.81 | 12-JAN-19:19 | 10.92 | 5.28 |
| February | 0.142578E+09 | 342.09 | 22-FEB-15:10 | 22.30 | 8.09 | 74603791.90 | 62.95 | 21-FEB-21:19 | 22.30 | 8.09 |
| March | 0.303170E+09 | 719.42 | 22-MAR-16:05 | 23.80 | 8.77 | 88940594.54 | 70.27 | 15-MAR-20:10 | 23.80 | 8.77 |
| April | 0.149920E+10 | 2600.84 | 21-APR-15:10 | 32.02 | 15.38 | 0.109262E+09 | 70.38 | 28-APR-02:20 | 18.13 | 10.33 |
| May | 0.291112E+10 | 2862.98 | 19-MAY-14:00 | 35.00 | 17.23 | 0.124943E+09 | 70.37 | 17-MAY-03:20 | 35.00 | 17.23 |
| June | 0.412267E+10 | 3288.32 | 15-JUN-17:00 | 37.20 | 15.32 | 0.124395E+09 | 70.33 | 12-JUN-03:09 | 37.20 | 15.32 |
| July | 0.408364E+10 | 2978.84 | 02-JUL-18:00 | 36.10 | 18.22 | 0.128762E+09 | 70.30 | 11-JUL-03:00 | 23.30 | 15.50 |
| August | 0.350059E+10 | 2846.13 | 07-AUG-16:10 | 37.12 | 17.89 | 0.128498E+09 | 70.36 | 19-AUG-05:40 | 19.80 | 15.50 |
| September | 0.249949E+10 | 2233.50 | 15-SEP-15:10 | 30.00 | 18.95 | 0.121667E+09 | 70.39 | 11-SEP-03:30 | 30.00 | 18.95 |
| October | 0.106933E+10 | 2055.71 | 05-OCT-16:03 | 30.63 | 17.38 | 0.109062E+09 | 70.37 | 17-OCT-23:19 | 17.80 | 14.53 |
| November | 0.175967E+09 | 526.02 | 09-NOV-15:10 | 23.30 | 12.70 | 80689017.86 | 68.90 | 08-NOV-21:10 | 23.30 | 12.70 |
| December | 51364777.81 | 254.58 | 09-DEC-19:00 | 11.10 | 4.10 | 77964621.75 | 42.51 | 18-DEC-22:49 | 0.87 | -4.6 |
| Annual Sum or Average | 0.204259E+11 | 0.124709E+10 | ||||||||
| Minimum of Months | 51364777.81 | 254.58 | 10.92 | 4.10 | 74603791.90 | 42.51 | 0.87 | -4.6 | ||
| Maximum of Months | 0.412267E+10 | 3288.32 | 37.20 | 18.95 | 0.128762E+09 | 70.39 | 37.20 | 18.95 |
Report: ZoneCoolingSummaryMonthly
For: T N1 APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.113990E+09 | 331.37 | 12-JAN-22:40 | 8.33 | 4.30 | 78637640.72 | 49.69 | 12-JAN-21:10 | 8.33 | 4.30 |
| February | 0.168495E+09 | 354.81 | 22-FEB-01:10 | 7.43 | 1.13 | 75254467.05 | 64.38 | 20-FEB-21:10 | 7.43 | 1.13 |
| March | 0.312458E+09 | 559.09 | 22-MAR-16:10 | 23.80 | 8.77 | 90442958.33 | 70.28 | 15-MAR-20:40 | 23.80 | 8.77 |
| April | 0.120186E+10 | 1921.60 | 21-APR-15:10 | 32.02 | 15.38 | 0.111406E+09 | 70.38 | 25-APR-22:40 | 16.10 | 10.56 |
| May | 0.229158E+10 | 2183.75 | 19-MAY-17:17 | 34.03 | 16.20 | 0.126212E+09 | 70.38 | 07-MAY-00:30 | 34.03 | 16.20 |
| June | 0.322219E+10 | 2596.01 | 15-JUN-17:00 | 37.20 | 15.32 | 0.124572E+09 | 70.35 | 13-JUN-05:10 | 37.20 | 15.32 |
| July | 0.325923E+10 | 2382.45 | 02-JUL-18:00 | 36.10 | 18.22 | 0.128769E+09 | 70.30 | 11-JUL-03:00 | 23.30 | 15.50 |
| August | 0.280218E+10 | 2293.70 | 07-AUG-18:00 | 34.40 | 18.63 | 0.128678E+09 | 70.32 | 11-AUG-04:00 | 23.30 | 14.99 |
| September | 0.201539E+10 | 1795.05 | 02-SEP-16:20 | 31.67 | 18.16 | 0.122697E+09 | 70.39 | 11-SEP-04:10 | 16.52 | 11.03 |
| October | 0.971290E+09 | 1683.74 | 05-OCT-16:03 | 30.63 | 17.38 | 0.113261E+09 | 70.38 | 26-OCT-22:10 | 17.47 | 8.53 |
| November | 0.224521E+09 | 389.13 | 09-NOV-15:10 | 23.30 | 12.70 | 81891289.49 | 70.27 | 09-NOV-22:40 | 17.43 | 10.49 |
| December | 86309749.07 | 291.01 | 16-DEC-18:01 | 9.72 | 2.11 | 78096378.40 | 44.98 | 10-DEC-21:10 | 9.72 | 2.11 |
| Annual Sum or Average | 0.166695E+11 | 0.125992E+10 | ||||||||
| Minimum of Months | 86309749.07 | 291.01 | 7.43 | 1.13 | 75254467.05 | 44.98 | 7.43 | 1.13 | ||
| Maximum of Months | 0.325923E+10 | 2596.01 | 37.20 | 18.63 | 0.128769E+09 | 70.39 | 37.20 | 16.20 |
Report: ZoneCoolingSummaryMonthly
For: T N2 APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.112522E+09 | 330.74 | 12-JAN-22:40 | 8.33 | 4.30 | 78600994.84 | 49.45 | 12-JAN-21:10 | 8.33 | 4.30 |
| February | 0.169599E+09 | 354.82 | 22-FEB-01:10 | 7.43 | 1.13 | 75235360.55 | 64.30 | 20-FEB-21:10 | 7.43 | 1.13 |
| March | 0.313849E+09 | 561.03 | 22-MAR-16:10 | 23.80 | 8.77 | 90397200.39 | 70.29 | 15-MAR-20:40 | 23.80 | 8.77 |
| April | 0.120792E+10 | 1922.85 | 21-APR-15:10 | 32.02 | 15.38 | 0.111394E+09 | 70.38 | 27-APR-01:10 | 17.62 | 7.41 |
| May | 0.229626E+10 | 2166.47 | 19-MAY-17:17 | 34.03 | 16.20 | 0.126211E+09 | 70.38 | 26-MAY-03:39 | 17.80 | 11.31 |
| June | 0.322506E+10 | 2580.37 | 15-JUN-17:00 | 37.20 | 15.32 | 0.124571E+09 | 70.34 | 28-JUN-02:39 | 17.20 | 15.87 |
| July | 0.326141E+10 | 2372.92 | 02-JUL-18:00 | 36.10 | 18.22 | 0.128769E+09 | 70.30 | 11-JUL-03:00 | 23.30 | 15.50 |
| August | 0.280467E+10 | 2278.36 | 07-AUG-18:00 | 34.40 | 18.63 | 0.128677E+09 | 70.32 | 11-AUG-04:00 | 23.30 | 14.99 |
| September | 0.201826E+10 | 1786.19 | 02-SEP-16:20 | 31.67 | 18.16 | 0.122685E+09 | 70.38 | 25-SEP-23:30 | 18.35 | 11.01 |
| October | 0.972353E+09 | 1670.76 | 05-OCT-16:03 | 30.63 | 17.38 | 0.113120E+09 | 70.39 | 22-OCT-00:20 | 17.60 | 11.11 |
| November | 0.223226E+09 | 397.47 | 09-NOV-15:10 | 23.30 | 12.70 | 81793398.32 | 70.30 | 09-NOV-22:40 | 17.43 | 10.49 |
| December | 85581382.75 | 268.80 | 16-DEC-17:50 | 10.55 | 2.45 | 78086990.08 | 45.02 | 10-DEC-21:10 | 10.55 | 2.45 |
| Annual Sum or Average | 0.166907E+11 | 0.125954E+10 | ||||||||
| Minimum of Months | 85581382.75 | 268.80 | 7.43 | 1.13 | 75235360.55 | 45.02 | 7.43 | 1.13 | ||
| Maximum of Months | 0.326141E+10 | 2580.37 | 37.20 | 18.63 | 0.128769E+09 | 70.39 | 23.80 | 15.87 |
Report: ZoneCoolingSummaryMonthly
For: T S1 APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.572213E+09 | 1425.47 | 12-JAN-15:00 | 18.90 | 10.02 | 88576448.84 | 70.36 | 13-JAN-18:40 | 14.07 | 6.93 |
| February | 0.634657E+09 | 1613.20 | 20-FEB-15:00 | 23.30 | 8.88 | 82705592.94 | 70.37 | 05-FEB-20:30 | 23.30 | 8.88 |
| March | 0.743275E+09 | 1553.87 | 16-MAR-15:10 | 22.70 | 8.66 | 93756243.52 | 70.37 | 06-MAR-19:19 | 22.70 | 8.66 |
| April | 0.161932E+10 | 2298.06 | 21-APR-14:30 | 32.20 | 15.35 | 0.112575E+09 | 70.38 | 06-APR-18:10 | 32.20 | 15.35 |
| May | 0.239448E+10 | 2376.85 | 19-MAY-14:00 | 35.00 | 17.23 | 0.123236E+09 | 70.37 | 13-MAY-02:00 | 35.00 | 17.23 |
| June | 0.318014E+10 | 2517.94 | 15-JUN-16:01 | 37.70 | 15.60 | 0.120360E+09 | 70.38 | 12-JUN-04:40 | 37.70 | 15.60 |
| July | 0.329322E+10 | 2462.16 | 02-JUL-16:01 | 38.22 | 18.82 | 0.129270E+09 | 70.30 | 11-JUL-03:00 | 23.30 | 15.50 |
| August | 0.311006E+10 | 2430.61 | 07-AUG-16:04 | 37.12 | 17.89 | 0.123885E+09 | 70.34 | 17-AUG-04:40 | 17.40 | 16.18 |
| September | 0.276259E+10 | 2673.66 | 19-SEP-14:10 | 33.80 | 16.79 | 0.122490E+09 | 70.38 | 11-SEP-04:40 | 33.80 | 16.79 |
| October | 0.191988E+10 | 2509.00 | 03-OCT-13:40 | 32.07 | 19.44 | 0.116703E+09 | 70.37 | 29-OCT-00:20 | 16.10 | 12.01 |
| November | 0.925628E+09 | 1967.94 | 09-NOV-14:20 | 23.30 | 12.51 | 92693808.22 | 70.38 | 08-NOV-23:10 | 23.30 | 12.51 |
| December | 0.534772E+09 | 1152.16 | 16-DEC-14:50 | 15.00 | 4.20 | 86858831.19 | 70.33 | 30-DEC-17:49 | 9.27 | 3.18 |
| Annual Sum or Average | 0.216902E+11 | 0.129311E+10 | ||||||||
| Minimum of Months | 0.534772E+09 | 1152.16 | 15.00 | 4.20 | 82705592.94 | 70.30 | 9.27 | 3.18 | ||
| Maximum of Months | 0.329322E+10 | 2673.66 | 38.22 | 19.44 | 0.129270E+09 | 70.38 | 37.70 | 17.23 |
Report: ZoneCoolingSummaryMonthly
For: T S2 APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.573433E+09 | 1427.10 | 12-JAN-15:00 | 18.90 | 10.02 | 88512655.20 | 70.35 | 13-JAN-18:40 | 14.07 | 6.93 |
| February | 0.638667E+09 | 1620.12 | 20-FEB-15:00 | 23.30 | 8.88 | 82696840.23 | 70.34 | 05-FEB-20:30 | 23.30 | 8.88 |
| March | 0.748095E+09 | 1554.47 | 16-MAR-15:10 | 22.70 | 8.66 | 93692952.09 | 70.37 | 07-MAR-20:10 | 22.70 | 8.66 |
| April | 0.162606E+10 | 2304.32 | 21-APR-14:20 | 32.20 | 15.31 | 0.112556E+09 | 70.38 | 30-APR-02:49 | 16.10 | 11.72 |
| May | 0.239939E+10 | 2383.12 | 19-MAY-14:00 | 35.00 | 17.23 | 0.123228E+09 | 70.38 | 01-MAY-02:39 | 35.00 | 17.23 |
| June | 0.318314E+10 | 2507.50 | 15-JUN-16:01 | 37.70 | 15.60 | 0.120358E+09 | 70.36 | 12-JUN-04:40 | 37.70 | 15.60 |
| July | 0.329548E+10 | 2453.78 | 02-JUL-16:01 | 38.22 | 18.82 | 0.129270E+09 | 70.30 | 11-JUL-03:00 | 23.30 | 15.50 |
| August | 0.311257E+10 | 2426.10 | 26-AUG-15:10 | 34.32 | 16.57 | 0.123884E+09 | 70.32 | 17-AUG-04:40 | 34.32 | 16.57 |
| September | 0.276516E+10 | 2677.09 | 19-SEP-14:10 | 33.80 | 16.79 | 0.122480E+09 | 70.37 | 11-SEP-04:40 | 33.80 | 16.79 |
| October | 0.192056E+10 | 2512.48 | 03-OCT-13:40 | 32.07 | 19.44 | 0.116592E+09 | 70.37 | 13-OCT-00:10 | 17.20 | 10.92 |
| November | 0.928681E+09 | 1974.18 | 09-NOV-14:10 | 23.30 | 12.48 | 92627777.98 | 70.37 | 23-NOV-20:00 | 13.30 | 5.73 |
| December | 0.536472E+09 | 1157.02 | 16-DEC-14:40 | 15.00 | 4.23 | 86814556.10 | 70.27 | 16-DEC-16:19 | 14.43 | 3.97 |
| Annual Sum or Average | 0.217277E+11 | 0.129271E+10 | ||||||||
| Minimum of Months | 0.536472E+09 | 1157.02 | 15.00 | 4.23 | 82696840.23 | 70.27 | 13.30 | 3.97 | ||
| Maximum of Months | 0.329548E+10 | 2677.09 | 38.22 | 19.44 | 0.129270E+09 | 70.38 | 37.70 | 17.23 |
Report: ZoneCoolingSummaryMonthly
For: T CORRIDOR
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 6.70 | 3.92 | 0.134385E+09 | 106.60 | 12-JAN-21:10 | 12.43 | 7.05 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 6.42 | 1.84 | 0.135296E+09 | 124.23 | 20-FEB-21:10 | 14.72 | 5.21 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 7.32 | 2.40 | 0.171323E+09 | 134.31 | 15-MAR-20:10 | 19.08 | 7.09 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 11.18 | 2.41 | 0.225298E+09 | 164.06 | 19-APR-20:10 | 28.30 | 12.40 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 20.40 | 8.41 | 0.269117E+09 | 174.75 | 19-MAY-20:10 | 30.92 | 14.42 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 25.03 | 11.56 | 0.284881E+09 | 182.56 | 15-JUN-20:10 | 33.80 | 13.95 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 | 17.07 | 0.295969E+09 | 183.56 | 02-JUL-20:10 | 33.72 | 16.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 27.32 | 18.12 | 0.288476E+09 | 181.81 | 06-AUG-20:10 | 32.43 | 18.80 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 22.63 | 17.18 | 0.263475E+09 | 169.22 | 01-SEP-20:10 | 26.83 | 18.01 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 16.02 | 8.67 | 0.230097E+09 | 164.09 | 04-OCT-20:10 | 26.02 | 17.88 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 10.60 | 5.64 | 0.153553E+09 | 134.14 | 09-NOV-21:10 | 19.82 | 11.24 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 8.95 | 5.46 | 0.125576E+09 | 91.31 | 09-DEC-21:10 | 10.32 | 4.02 |
| Annual Sum or Average | 0.00 | 0.257745E+10 | ||||||||
| Minimum of Months | 0.00 | 0.00 | 6.42 | 1.84 | 0.125576E+09 | 91.31 | 10.32 | 4.02 | ||
| Maximum of Months | 0.00 | 0.00 | 27.63 | 18.12 | 0.295969E+09 | 183.56 | 33.80 | 18.80 |
Report: ZoneCoolingSummaryMonthly
For: G CORRIDOR
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 6.70 | 3.92 | 0.123562E+09 | 101.16 | 03-JAN-22:49 | 10.97 | 5.44 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 6.42 | 1.84 | 0.121289E+09 | 109.48 | 22-FEB-22:49 | 14.40 | 4.99 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 7.32 | 2.40 | 0.148851E+09 | 113.29 | 16-MAR-21:49 | 16.28 | 6.02 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 11.18 | 2.41 | 0.222129E+09 | 175.16 | 29-APR-17:10 | 30.22 | 13.21 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 20.40 | 8.41 | 0.283601E+09 | 209.88 | 19-MAY-17:10 | 34.22 | 16.36 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 25.03 | 11.56 | 0.309383E+09 | 248.55 | 02-JUN-17:10 | 38.62 | 16.10 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 | 17.07 | 0.322328E+09 | 250.26 | 03-JUL-17:10 | 38.12 | 18.79 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 27.32 | 18.12 | 0.315819E+09 | 238.94 | 07-AUG-17:10 | 36.32 | 18.05 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 22.63 | 17.18 | 0.289726E+09 | 207.72 | 19-SEP-17:10 | 33.03 | 16.74 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 16.02 | 8.67 | 0.256023E+09 | 185.94 | 01-OCT-17:10 | 30.92 | 15.01 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 10.60 | 5.64 | 0.175884E+09 | 144.66 | 01-NOV-04:49 | 11.02 | 9.76 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 8.95 | 5.46 | 0.121994E+09 | 100.59 | 10-DEC-22:49 | 10.97 | 4.80 |
| Annual Sum or Average | 0.00 | 0.269059E+10 | ||||||||
| Minimum of Months | 0.00 | 0.00 | 6.42 | 1.84 | 0.121289E+09 | 100.59 | 10.97 | 4.80 | ||
| Maximum of Months | 0.00 | 0.00 | 27.63 | 18.12 | 0.322328E+09 | 250.26 | 38.62 | 18.79 |
Report: ZoneCoolingSummaryMonthly
For: M CORRIDOR
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 6.70 | 3.92 | 0.185372E+09 | 118.04 | 12-JAN-21:10 | 12.43 | 7.05 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 6.42 | 1.84 | 0.182999E+09 | 138.52 | 21-FEB-21:10 | 14.90 | 4.43 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 7.32 | 2.40 | 0.224155E+09 | 143.64 | 16-MAR-20:10 | 17.20 | 5.94 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 11.18 | 2.41 | 0.256080E+09 | 158.46 | 30-APR-20:10 | 26.32 | 11.07 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 20.40 | 8.41 | 0.280901E+09 | 162.79 | 19-MAY-20:10 | 30.92 | 14.42 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 25.03 | 11.56 | 0.280922E+09 | 166.72 | 15-JUN-20:10 | 33.80 | 13.95 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 | 17.07 | 0.289364E+09 | 166.71 | 02-JUL-21:10 | 33.17 | 17.50 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 27.32 | 18.12 | 0.286491E+09 | 165.49 | 06-AUG-20:10 | 32.43 | 18.80 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 22.63 | 17.18 | 0.272952E+09 | 160.88 | 20-SEP-20:10 | 25.40 | 15.25 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 16.02 | 8.67 | 0.267774E+09 | 158.08 | 05-OCT-20:10 | 23.80 | 16.56 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 10.60 | 5.64 | 0.212213E+09 | 144.02 | 09-NOV-21:19 | 19.63 | 11.21 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 8.95 | 5.46 | 0.179583E+09 | 115.80 | 10-DEC-22:30 | 11.70 | 5.14 |
| Annual Sum or Average | 0.00 | 0.291881E+10 | ||||||||
| Minimum of Months | 0.00 | 0.00 | 6.42 | 1.84 | 0.179583E+09 | 115.80 | 11.70 | 4.43 | ||
| Maximum of Months | 0.00 | 0.00 | 27.63 | 18.12 | 0.289364E+09 | 166.72 | 33.80 | 18.80 |
Report: ZoneHeatingSummaryMonthly
For: G SW APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 57263705.91 | 660.20 | 26-JAN-00:10 | 6.10 |
| February | 58733794.31 | 458.89 | 09-FEB-04:00 | 1.10 |
| March | 51683891.31 | 612.22 | 01-MAR-05:00 | 1.10 |
| April | 517826.21 | 108.44 | 01-APR-12:40 | 27.23 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 20.40 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 25.03 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 27.32 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 22.63 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 16.02 |
| November | 1615306.51 | 195.07 | 28-NOV-05:00 | -0.6 |
| December | 33405737.85 | 454.94 | 27-DEC-06:00 | -3.3 |
| Annual Sum or Average | 0.203220E+09 | |||
| Minimum of Months | 0.00 | 0.00 | -3.3 | |
| Maximum of Months | 58733794.31 | 660.20 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: G NW APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.381241E+09 | 897.13 | 28-JAN-06:00 | -3.3 |
| February | 0.361174E+09 | 1019.29 | 09-FEB-01:00 | 1.10 |
| March | 0.211509E+09 | 821.21 | 01-MAR-23:00 | 0.60 |
| April | 5508956.94 | 205.68 | 01-APR-01:00 | 11.10 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 20.40 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 25.03 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 27.32 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 22.63 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 16.02 |
| November | 18984565.00 | 507.69 | 28-NOV-05:00 | -0.6 |
| December | 0.332119E+09 | 759.28 | 31-DEC-07:00 | -2.8 |
| Annual Sum or Average | 0.131054E+10 | |||
| Minimum of Months | 0.00 | 0.00 | -3.3 | |
| Maximum of Months | 0.381241E+09 | 1019.29 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: OFFICE
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 41640278.38 | 8145.19 | 27-JAN-08:61 | -3.5 |
| February | 0.126424E+09 | 4362.22 | 03-FEB-08:61 | -2.0 |
| March | 0.198448E+09 | 8837.31 | 02-MAR-08:61 | -0.9 |
| April | 0.428227E+09 | 647.82 | 19-APR-16:12 | 31.10 |
| May | 0.582248E+09 | 745.99 | 19-MAY-16:13 | 34.80 |
| June | 0.617088E+09 | 901.34 | 02-JUN-16:01 | 38.90 |
| July | 0.572301E+09 | 823.51 | 03-JUL-16:01 | 38.30 |
| August | 0.449121E+09 | 764.39 | 07-AUG-16:01 | 37.12 |
| September | 0.309840E+09 | 652.29 | 01-SEP-16:13 | 32.60 |
| October | 0.203715E+09 | 586.09 | 04-OCT-16:13 | 30.60 |
| November | 56889486.33 | 408.01 | 08-NOV-09:05 | 17.38 |
| December | 33496298.93 | 8741.73 | 27-DEC-08:61 | -3.4 |
| Annual Sum or Average | 0.361944E+10 | |||
| Minimum of Months | 33496298.93 | 408.01 | -3.5 | |
| Maximum of Months | 0.617088E+09 | 8837.31 | 38.90 |
Report: ZoneHeatingSummaryMonthly
For: G NE APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.368057E+09 | 925.92 | 28-JAN-06:00 | -3.3 |
| February | 0.325730E+09 | 1015.83 | 16-FEB-17:01 | 11.60 |
| March | 0.204122E+09 | 848.78 | 01-MAR-23:00 | 0.60 |
| April | 5078044.88 | 206.68 | 01-APR-01:00 | 11.10 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 20.40 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 25.03 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 27.32 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 22.63 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 16.02 |
| November | 19111847.21 | 536.65 | 28-NOV-05:00 | -0.6 |
| December | 0.318359E+09 | 788.70 | 31-DEC-07:00 | -2.8 |
| Annual Sum or Average | 0.124046E+10 | |||
| Minimum of Months | 0.00 | 0.00 | -3.3 | |
| Maximum of Months | 0.368057E+09 | 1015.83 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: G N1 APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 62966661.32 | 405.68 | 28-JAN-06:00 | -3.3 |
| February | 68179392.69 | 421.60 | 09-FEB-01:10 | 1.10 |
| March | 30068427.42 | 312.30 | 01-MAR-23:10 | 0.50 |
| April | 6027398.76 | 172.94 | 01-APR-15:00 | 28.90 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 20.40 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 25.03 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 27.32 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 22.63 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 16.02 |
| November | 945341.26 | 120.15 | 28-NOV-05:00 | -0.6 |
| December | 49393866.57 | 312.91 | 31-DEC-07:00 | -2.8 |
| Annual Sum or Average | 0.217581E+09 | |||
| Minimum of Months | 0.00 | 0.00 | -3.3 | |
| Maximum of Months | 68179392.69 | 421.60 | 28.90 |
Report: ZoneHeatingSummaryMonthly
For: G N2 APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 63432075.31 | 406.74 | 28-JAN-06:00 | -3.3 |
| February | 67836279.49 | 420.96 | 09-FEB-01:00 | 1.10 |
| March | 30027098.87 | 311.80 | 01-MAR-23:10 | 0.50 |
| April | 5889749.61 | 172.57 | 01-APR-15:00 | 28.90 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 20.40 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 25.03 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 27.32 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 22.63 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 16.02 |
| November | 972369.04 | 122.92 | 28-NOV-05:00 | -0.6 |
| December | 49936989.22 | 315.50 | 31-DEC-07:00 | -2.8 |
| Annual Sum or Average | 0.218095E+09 | |||
| Minimum of Months | 0.00 | 0.00 | -3.3 | |
| Maximum of Months | 67836279.49 | 420.96 | 28.90 |
Report: ZoneHeatingSummaryMonthly
For: G S1 APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 1063156.56 | 78.72 | 26-JAN-00:10 | 6.10 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 6.42 |
| March | 153173.51 | 28.55 | 02-MAR-06:00 | -3.9 |
| April | 147660.98 | 65.34 | 01-APR-11:50 | 25.63 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 20.40 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 25.03 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 27.32 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 22.63 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 16.02 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 10.60 |
| December | 4980.68 | 8.30 | 27-DEC-06:00 | -3.3 |
| Annual Sum or Average | 1368971.72 | |||
| Minimum of Months | 0.00 | 0.00 | -3.9 | |
| Maximum of Months | 1063156.56 | 78.72 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: G S2 APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 694688.44 | 58.41 | 26-JAN-00:20 | 6.10 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 6.42 |
| March | 97258.40 | 24.43 | 02-MAR-08:00 | -1.1 |
| April | 62953.09 | 40.45 | 01-APR-11:30 | 24.70 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 20.40 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 25.03 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 27.32 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 22.63 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 16.02 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 10.60 |
| December | 18859.10 | 26.36 | 27-DEC-06:00 | -3.3 |
| Annual Sum or Average | 873759.03 | |||
| Minimum of Months | 0.00 | 0.00 | -3.3 | |
| Maximum of Months | 694688.44 | 58.41 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: M SW APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 43775302.88 | 840.79 | 26-JAN-00:10 | 6.10 |
| February | 13095656.40 | 321.91 | 02-FEB-06:00 | -3.3 |
| March | 7275453.50 | 351.89 | 01-MAR-05:00 | 1.10 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 11.18 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 20.40 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 25.03 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 27.32 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 22.63 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 16.02 |
| November | 14093091.15 | 620.73 | 28-NOV-05:00 | -0.6 |
| December | 48819755.42 | 616.35 | 27-DEC-06:00 | -3.3 |
| Annual Sum or Average | 0.127059E+09 | |||
| Minimum of Months | 0.00 | 0.00 | -3.3 | |
| Maximum of Months | 48819755.42 | 840.79 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: M NW APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.271250E+09 | 971.27 | 26-JAN-00:10 | 6.10 |
| February | 0.145531E+09 | 955.65 | 09-FEB-01:00 | 1.10 |
| March | 38961184.75 | 698.97 | 01-MAR-23:00 | 0.60 |
| April | 98926.53 | 52.85 | 01-APR-11:40 | 25.17 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 20.40 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 25.03 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 27.32 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 22.63 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 16.02 |
| November | 55046603.04 | 780.01 | 28-NOV-05:00 | -0.6 |
| December | 0.375376E+09 | 882.17 | 31-DEC-07:00 | -2.8 |
| Annual Sum or Average | 0.886264E+09 | |||
| Minimum of Months | 0.00 | 0.00 | -2.8 | |
| Maximum of Months | 0.375376E+09 | 971.27 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: M SE APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 44048717.96 | 828.33 | 26-JAN-00:10 | 6.10 |
| February | 12481336.19 | 351.11 | 02-FEB-06:00 | -3.3 |
| March | 7002260.70 | 280.63 | 02-MAR-06:00 | -3.9 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 11.18 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 20.40 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 25.03 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 27.32 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 22.63 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 16.02 |
| November | 15264193.41 | 669.87 | 28-NOV-05:00 | -0.6 |
| December | 53626040.67 | 621.28 | 27-DEC-06:00 | -3.3 |
| Annual Sum or Average | 0.132423E+09 | |||
| Minimum of Months | 0.00 | 0.00 | -3.9 | |
| Maximum of Months | 53626040.67 | 828.33 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: M NE APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.265504E+09 | 991.32 | 28-JAN-06:00 | -3.3 |
| February | 0.132147E+09 | 938.61 | 09-FEB-01:00 | 1.10 |
| March | 33205355.58 | 750.69 | 01-MAR-23:00 | 0.60 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 11.18 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 20.40 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 25.03 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 27.32 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 22.63 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 16.02 |
| November | 56153608.87 | 823.51 | 28-NOV-05:00 | -0.6 |
| December | 0.362401E+09 | 927.90 | 31-DEC-07:00 | -2.8 |
| Annual Sum or Average | 0.849411E+09 | |||
| Minimum of Months | 0.00 | 0.00 | -3.3 | |
| Maximum of Months | 0.362401E+09 | 991.32 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: M N1 APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 27058697.61 | 388.56 | 28-JAN-06:00 | -3.3 |
| February | 11300850.25 | 253.34 | 02-FEB-03:00 | -2.2 |
| March | 1737733.91 | 128.86 | 01-MAR-23:10 | 0.50 |
| April | 55156.54 | 39.38 | 01-APR-11:30 | 24.70 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 20.40 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 25.03 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 27.32 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 22.63 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 16.02 |
| November | 4153666.71 | 282.72 | 28-NOV-05:00 | -0.6 |
| December | 38595171.50 | 337.85 | 20-DEC-04:00 | 7.80 |
| Annual Sum or Average | 82901276.53 | |||
| Minimum of Months | 0.00 | 0.00 | -3.3 | |
| Maximum of Months | 38595171.50 | 388.56 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: M N2 APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 27363853.77 | 390.54 | 28-JAN-06:00 | -3.3 |
| February | 11236377.32 | 254.23 | 02-FEB-03:00 | -2.2 |
| March | 1725349.08 | 128.79 | 01-MAR-23:10 | 0.50 |
| April | 29437.26 | 27.22 | 01-APR-11:20 | 24.23 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 20.40 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 25.03 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 27.32 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 22.63 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 16.02 |
| November | 4202928.63 | 284.96 | 28-NOV-05:00 | -0.6 |
| December | 39221870.69 | 339.99 | 20-DEC-04:00 | 7.80 |
| Annual Sum or Average | 83779816.75 | |||
| Minimum of Months | 0.00 | 0.00 | -3.3 | |
| Maximum of Months | 39221870.69 | 390.54 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: M S1 APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 10052.80 | 16.75 | 26-JAN-07:00 | 0.60 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 6.42 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 7.32 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 11.18 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 20.40 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 25.03 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 27.32 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 22.63 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 16.02 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 10.60 |
| December | 374223.75 | 86.98 | 27-DEC-06:00 | -3.3 |
| Annual Sum or Average | 384276.55 | |||
| Minimum of Months | 0.00 | 0.00 | -3.3 | |
| Maximum of Months | 374223.75 | 86.98 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: M S2 APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 8567.82 | 14.28 | 26-JAN-07:00 | 0.60 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 6.42 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 7.32 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 11.18 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 20.40 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 25.03 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 27.32 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 22.63 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 16.02 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 10.60 |
| December | 370173.55 | 86.68 | 27-DEC-06:00 | -3.3 |
| Annual Sum or Average | 378741.37 | |||
| Minimum of Months | 0.00 | 0.00 | -3.3 | |
| Maximum of Months | 370173.55 | 86.68 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: T SW APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.946138E+09 | 1965.79 | 28-JAN-06:00 | -3.3 |
| February | 0.657966E+09 | 2256.88 | 09-FEB-01:00 | 1.10 |
| March | 0.425972E+09 | 1688.56 | 01-MAR-05:00 | 1.10 |
| April | 69190783.82 | 1411.86 | 11-APR-02:00 | 6.10 |
| May | 84341.13 | 230.98 | 02-MAY-07:20 | 12.93 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 25.03 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 27.32 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 22.63 |
| October | 5472515.30 | 440.63 | 25-OCT-06:00 | 6.70 |
| November | 0.480950E+09 | 1905.72 | 28-NOV-05:00 | -0.6 |
| December | 0.112541E+10 | 1953.93 | 27-DEC-06:00 | -3.3 |
| Annual Sum or Average | 0.371118E+10 | |||
| Minimum of Months | 0.00 | 0.00 | -3.3 | |
| Maximum of Months | 0.112541E+10 | 2256.88 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: T NW APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.153254E+10 | 2237.20 | 28-JAN-06:00 | -3.3 |
| February | 0.103461E+10 | 2472.27 | 09-FEB-01:00 | 1.10 |
| March | 0.615616E+09 | 1827.67 | 02-MAR-06:00 | -3.9 |
| April | 85819385.06 | 1466.90 | 11-APR-02:00 | 6.10 |
| May | 8873.26 | 45.12 | 02-MAY-07:03 | 12.57 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 25.03 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 27.32 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 22.63 |
| October | 18390812.78 | 556.79 | 25-OCT-06:00 | 6.70 |
| November | 0.818527E+09 | 1978.70 | 28-NOV-05:00 | -0.6 |
| December | 0.180135E+10 | 2158.56 | 31-DEC-07:00 | -2.8 |
| Annual Sum or Average | 0.590685E+10 | |||
| Minimum of Months | 0.00 | 0.00 | -3.9 | |
| Maximum of Months | 0.180135E+10 | 2472.27 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: T SE APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.933525E+09 | 2015.00 | 28-JAN-06:00 | -3.3 |
| February | 0.629019E+09 | 2253.66 | 09-FEB-01:00 | 1.10 |
| March | 0.404652E+09 | 1700.61 | 02-MAR-06:00 | -3.9 |
| April | 60676632.53 | 1418.28 | 11-APR-02:00 | 6.10 |
| May | 13182.57 | 62.63 | 02-MAY-05:20 | 9.80 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 25.03 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 27.32 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 22.63 |
| October | 6819360.51 | 492.25 | 25-OCT-06:00 | 6.70 |
| November | 0.479256E+09 | 1950.24 | 28-NOV-05:00 | -0.6 |
| December | 0.111307E+10 | 1964.88 | 27-DEC-06:00 | -3.3 |
| Annual Sum or Average | 0.362703E+10 | |||
| Minimum of Months | 0.00 | 0.00 | -3.9 | |
| Maximum of Months | 0.111307E+10 | 2253.66 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: T NE APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.148921E+10 | 2279.85 | 28-JAN-06:00 | -3.3 |
| February | 0.972813E+09 | 2477.77 | 09-FEB-01:00 | 1.10 |
| March | 0.575666E+09 | 1882.29 | 01-MAR-23:00 | 0.60 |
| April | 76225106.10 | 1471.03 | 11-APR-02:00 | 6.10 |
| May | 18831.88 | 79.12 | 02-MAY-05:20 | 9.80 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 25.03 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 27.32 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 22.63 |
| October | 21117284.47 | 644.84 | 25-OCT-06:00 | 6.70 |
| November | 0.795409E+09 | 2016.45 | 28-NOV-05:00 | -0.6 |
| December | 0.176115E+10 | 2193.36 | 31-DEC-07:00 | -2.8 |
| Annual Sum or Average | 0.569161E+10 | |||
| Minimum of Months | 0.00 | 0.00 | -3.3 | |
| Maximum of Months | 0.176115E+10 | 2477.77 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: T N1 APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.815912E+09 | 1455.98 | 28-JAN-06:00 | -3.3 |
| February | 0.527817E+09 | 1430.59 | 09-FEB-01:00 | 1.10 |
| March | 0.272332E+09 | 1203.20 | 02-MAR-06:00 | -3.9 |
| April | 23847004.36 | 660.52 | 11-APR-02:00 | 6.10 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 20.40 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 25.03 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 27.32 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 22.63 |
| October | 2244184.69 | 214.48 | 25-OCT-06:00 | 6.70 |
| November | 0.401064E+09 | 1274.84 | 28-NOV-05:00 | -0.6 |
| December | 0.103210E+10 | 1377.70 | 31-DEC-07:00 | -2.8 |
| Annual Sum or Average | 0.307531E+10 | |||
| Minimum of Months | 0.00 | 0.00 | -3.9 | |
| Maximum of Months | 0.103210E+10 | 1455.98 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: T N2 APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.817880E+09 | 1458.98 | 28-JAN-06:00 | -3.3 |
| February | 0.527612E+09 | 1430.11 | 09-FEB-01:00 | 1.10 |
| March | 0.273526E+09 | 1205.36 | 02-MAR-06:00 | -3.9 |
| April | 23930192.97 | 661.08 | 11-APR-02:00 | 6.10 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 20.40 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 25.03 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 27.32 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 22.63 |
| October | 2478498.47 | 226.50 | 25-OCT-06:00 | 6.70 |
| November | 0.403485E+09 | 1277.12 | 28-NOV-05:00 | -0.6 |
| December | 0.103348E+10 | 1380.35 | 31-DEC-07:00 | -2.8 |
| Annual Sum or Average | 0.308239E+10 | |||
| Minimum of Months | 0.00 | 0.00 | -3.9 | |
| Maximum of Months | 0.103348E+10 | 1458.98 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: T S1 APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.369395E+09 | 1154.99 | 28-JAN-06:00 | -3.3 |
| February | 0.252694E+09 | 1214.61 | 09-FEB-04:00 | 1.10 |
| March | 0.137934E+09 | 1006.76 | 02-MAR-06:00 | -3.9 |
| April | 17200604.30 | 585.46 | 11-APR-02:00 | 6.10 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 20.40 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 25.03 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 27.32 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 22.63 |
| October | 25254.98 | 30.58 | 25-OCT-06:00 | 6.70 |
| November | 0.170440E+09 | 1199.74 | 28-NOV-05:00 | -0.6 |
| December | 0.502780E+09 | 1268.26 | 27-DEC-06:00 | -3.3 |
| Annual Sum or Average | 0.145047E+10 | |||
| Minimum of Months | 0.00 | 0.00 | -3.9 | |
| Maximum of Months | 0.502780E+09 | 1268.26 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: T S2 APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.370939E+09 | 1159.31 | 28-JAN-06:00 | -3.3 |
| February | 0.252569E+09 | 1213.74 | 09-FEB-04:00 | 1.10 |
| March | 0.138702E+09 | 1010.11 | 02-MAR-06:00 | -3.9 |
| April | 17266485.72 | 586.75 | 11-APR-02:00 | 6.10 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 20.40 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 25.03 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 27.32 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 22.63 |
| October | 44085.16 | 38.76 | 25-OCT-06:00 | 6.70 |
| November | 0.171536E+09 | 1203.64 | 28-NOV-05:00 | -0.6 |
| December | 0.504449E+09 | 1268.65 | 27-DEC-06:00 | -3.3 |
| Annual Sum or Average | 0.145551E+10 | |||
| Minimum of Months | 0.00 | 0.00 | -3.9 | |
| Maximum of Months | 0.504449E+09 | 1268.65 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: T CORRIDOR
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 6.70 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 6.42 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 7.32 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 11.18 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 20.40 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 25.03 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 27.32 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 22.63 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 16.02 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 10.60 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 8.95 |
| Annual Sum or Average | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 6.42 | |
| Maximum of Months | 0.00 | 0.00 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: G CORRIDOR
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 6.70 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 6.42 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 7.32 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 11.18 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 20.40 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 25.03 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 27.32 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 22.63 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 16.02 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 10.60 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 8.95 |
| Annual Sum or Average | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 6.42 | |
| Maximum of Months | 0.00 | 0.00 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: M CORRIDOR
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 6.70 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 6.42 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 7.32 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 11.18 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 20.40 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 25.03 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 27.32 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 22.63 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 16.02 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 10.60 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 8.95 |
| Annual Sum or Average | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 6.42 | |
| Maximum of Months | 0.00 | 0.00 | 27.63 |
Report: ZoneElectricSummaryMonthly
For: G SW APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: G NW APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: OFFICE
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.609777E+09 | 582.92 | 03-JAN-08:09 | 0.787690E+09 | 588.62 | 03-JAN-08:09 |
| February | 0.564682E+09 | 582.92 | 01-FEB-08:09 | 0.723971E+09 | 588.62 | 01-FEB-08:09 |
| March | 0.654405E+09 | 582.92 | 01-MAR-08:09 | 0.827804E+09 | 588.62 | 01-MAR-08:09 |
| April | 0.599704E+09 | 582.92 | 03-APR-07:10 | 0.770907E+09 | 588.62 | 03-APR-07:10 |
| May | 0.639529E+09 | 582.92 | 01-MAY-07:10 | 0.814432E+09 | 588.62 | 01-MAY-07:10 |
| June | 0.629456E+09 | 582.92 | 01-JUN-07:10 | 0.797650E+09 | 588.62 | 01-JUN-07:10 |
| July | 0.609777E+09 | 582.92 | 03-JUL-07:10 | 0.787690E+09 | 588.62 | 03-JUL-07:10 |
| August | 0.654405E+09 | 582.92 | 01-AUG-07:10 | 0.827804E+09 | 588.62 | 01-AUG-07:10 |
| September | 0.599704E+09 | 582.92 | 01-SEP-07:10 | 0.770907E+09 | 588.62 | 01-SEP-07:10 |
| October | 0.624653E+09 | 582.92 | 02-OCT-07:10 | 0.801061E+09 | 588.62 | 02-OCT-07:10 |
| November | 0.599704E+09 | 582.92 | 01-NOV-07:10 | 0.770907E+09 | 588.62 | 01-NOV-07:10 |
| December | 0.609777E+09 | 582.92 | 01-DEC-08:09 | 0.787690E+09 | 588.62 | 01-DEC-08:09 |
| Annual Sum or Average | 0.739557E+10 | 0.946851E+10 | ||||
| Minimum of Months | 0.564682E+09 | 582.92 | 0.723971E+09 | 588.62 | ||
| Maximum of Months | 0.654405E+09 | 582.92 | 0.827804E+09 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: G NE APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: G N1 APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: G N2 APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: G S1 APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: G S2 APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: M SW APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: M NW APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: M SE APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: M NE APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: M N1 APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: M N2 APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: M S1 APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: M S2 APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: T SW APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: T NW APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: T SE APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: T NE APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: T N1 APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: T N2 APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: T S1 APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: T S2 APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.123508E+09 | 138.88 | 01-JAN-19:10 | 0.103725E+10 | 588.62 | 01-JAN-17:10 |
| February | 0.111556E+09 | 138.88 | 01-FEB-19:10 | 0.936871E+09 | 588.62 | 01-FEB-17:10 |
| March | 0.123508E+09 | 138.88 | 01-MAR-19:10 | 0.103725E+10 | 588.62 | 01-MAR-17:10 |
| April | 0.119524E+09 | 138.88 | 01-APR-18:10 | 0.100379E+10 | 588.62 | 01-APR-16:10 |
| May | 0.123508E+09 | 138.88 | 01-MAY-18:10 | 0.103725E+10 | 588.62 | 01-MAY-16:10 |
| June | 0.119524E+09 | 138.88 | 01-JUN-18:10 | 0.100379E+10 | 588.62 | 01-JUN-16:10 |
| July | 0.123508E+09 | 138.88 | 01-JUL-18:10 | 0.103725E+10 | 588.62 | 01-JUL-16:10 |
| August | 0.123508E+09 | 138.88 | 01-AUG-18:10 | 0.103725E+10 | 588.62 | 01-AUG-16:10 |
| September | 0.119524E+09 | 138.88 | 01-SEP-18:10 | 0.100379E+10 | 588.62 | 01-SEP-16:10 |
| October | 0.123508E+09 | 138.88 | 01-OCT-18:10 | 0.103725E+10 | 588.62 | 01-OCT-16:10 |
| November | 0.119524E+09 | 138.88 | 01-NOV-18:10 | 0.100379E+10 | 588.62 | 01-NOV-16:10 |
| December | 0.123508E+09 | 138.88 | 01-DEC-19:10 | 0.103725E+10 | 588.62 | 01-DEC-17:10 |
| Annual Sum or Average | 0.145421E+10 | 0.122128E+11 | ||||
| Minimum of Months | 0.111556E+09 | 138.88 | 0.936871E+09 | 588.62 | ||
| Maximum of Months | 0.123508E+09 | 138.88 | 0.103725E+10 | 588.62 |
Report: ZoneElectricSummaryMonthly
For: T CORRIDOR
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
| January | 0.992689E+09 | 370.63 | 01-JAN-00:10 | 0.00 | 0.00 |
| February | 0.896622E+09 | 370.63 | 01-FEB-00:10 | 0.00 | 0.00 |
| March | 0.992689E+09 | 370.63 | 01-MAR-00:10 | 0.00 | 0.00 |
| April | 0.960667E+09 | 370.63 | 01-APR-00:10 | 0.00 | 0.00 |
| May | 0.992689E+09 | 370.63 | 01-MAY-00:10 | 0.00 | 0.00 |
| June | 0.960667E+09 | 370.63 | 01-JUN-00:10 | 0.00 | 0.00 |
| July | 0.992689E+09 | 370.63 | 01-JUL-00:10 | 0.00 | 0.00 |
| August | 0.992689E+09 | 370.63 | 01-AUG-00:10 | 0.00 | 0.00 |
| September | 0.960667E+09 | 370.63 | 01-SEP-00:10 | 0.00 | 0.00 |
| October | 0.992689E+09 | 370.63 | 01-OCT-00:10 | 0.00 | 0.00 |
| November | 0.960667E+09 | 370.63 | 01-NOV-00:10 | 0.00 | 0.00 |
| December | 0.992689E+09 | 370.63 | 01-DEC-00:10 | 0.00 | 0.00 |
| Annual Sum or Average | 0.116881E+11 | 0.00 | 0.00 | ||
| Minimum of Months | 0.896622E+09 | 370.63 | 0.00 | 0.00 | |
| Maximum of Months | 0.992689E+09 | 370.63 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: G CORRIDOR
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.992689E+09 | 370.63 | 01-JAN-00:10 | 0.599555E+10 | 4168.07 | 01-JAN-07:10 |
| February | 0.896622E+09 | 370.63 | 01-FEB-00:10 | 0.541534E+10 | 4168.07 | 01-FEB-07:10 |
| March | 0.992689E+09 | 370.63 | 01-MAR-00:10 | 0.599555E+10 | 4168.07 | 01-MAR-07:10 |
| April | 0.960667E+09 | 370.63 | 01-APR-00:10 | 0.580215E+10 | 4168.07 | 01-APR-06:10 |
| May | 0.992689E+09 | 370.63 | 01-MAY-00:10 | 0.599555E+10 | 4168.07 | 01-MAY-06:10 |
| June | 0.960667E+09 | 370.63 | 01-JUN-00:10 | 0.580215E+10 | 4168.07 | 01-JUN-06:10 |
| July | 0.992689E+09 | 370.63 | 01-JUL-00:10 | 0.599555E+10 | 4168.07 | 01-JUL-06:10 |
| August | 0.992689E+09 | 370.63 | 01-AUG-00:10 | 0.599555E+10 | 4168.07 | 01-AUG-06:10 |
| September | 0.960667E+09 | 370.63 | 01-SEP-00:10 | 0.580215E+10 | 4168.07 | 01-SEP-06:10 |
| October | 0.992689E+09 | 370.63 | 01-OCT-00:10 | 0.599555E+10 | 4168.07 | 01-OCT-06:10 |
| November | 0.960667E+09 | 370.63 | 01-NOV-00:10 | 0.580215E+10 | 4168.07 | 01-NOV-06:10 |
| December | 0.992689E+09 | 370.63 | 01-DEC-00:10 | 0.599555E+10 | 4168.07 | 01-DEC-07:10 |
| Annual Sum or Average | 0.116881E+11 | 0.705928E+11 | ||||
| Minimum of Months | 0.896622E+09 | 370.63 | 0.541534E+10 | 4168.07 | ||
| Maximum of Months | 0.992689E+09 | 370.63 | 0.599555E+10 | 4168.07 |
Report: ZoneElectricSummaryMonthly
For: M CORRIDOR
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
| January | 0.992689E+09 | 370.63 | 01-JAN-00:10 | 0.00 | 0.00 |
| February | 0.896622E+09 | 370.63 | 01-FEB-00:10 | 0.00 | 0.00 |
| March | 0.992689E+09 | 370.63 | 01-MAR-00:10 | 0.00 | 0.00 |
| April | 0.960667E+09 | 370.63 | 01-APR-00:10 | 0.00 | 0.00 |
| May | 0.992689E+09 | 370.63 | 01-MAY-00:10 | 0.00 | 0.00 |
| June | 0.960667E+09 | 370.63 | 01-JUN-00:10 | 0.00 | 0.00 |
| July | 0.992689E+09 | 370.63 | 01-JUL-00:10 | 0.00 | 0.00 |
| August | 0.992689E+09 | 370.63 | 01-AUG-00:10 | 0.00 | 0.00 |
| September | 0.960667E+09 | 370.63 | 01-SEP-00:10 | 0.00 | 0.00 |
| October | 0.992689E+09 | 370.63 | 01-OCT-00:10 | 0.00 | 0.00 |
| November | 0.960667E+09 | 370.63 | 01-NOV-00:10 | 0.00 | 0.00 |
| December | 0.992689E+09 | 370.63 | 01-DEC-00:10 | 0.00 | 0.00 |
| Annual Sum or Average | 0.116881E+11 | 0.00 | 0.00 | ||
| Minimum of Months | 0.896622E+09 | 370.63 | 0.00 | 0.00 | |
| Maximum of Months | 0.992689E+09 | 370.63 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: G SW APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.431192E+09 |
| February | 0.389025E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.363851E+09 |
| March | 0.418950E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 305261.27 | 0.348131E+09 |
| April | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 42413424.93 | 0.189939E+09 |
| May | 0.424935E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111737E+09 | 83181782.29 |
| June | 0.406980E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.180952E+09 | 18994618.20 |
| July | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.137700E+09 | 10735434.88 |
| August | 0.418950E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108760E+09 | 23061742.83 |
| September | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 39422430.42 | 36041451.49 |
| October | 0.430920E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12214854.48 | 0.174027E+09 |
| November | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.345438E+09 |
| December | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.376543E+09 |
| Annual Sum or Average | 0.505732E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.633505E+09 | 0.240114E+10 |
| Minimum of Months | 0.389025E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10735434.88 |
| Maximum of Months | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.180952E+09 | 0.431192E+09 |
Report: SpaceGainsMonthly
For: G NW APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.408272E+09 |
| February | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 95751.55 | 0.341492E+09 |
| March | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1704914.33 | 0.322283E+09 |
| April | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 42838943.13 | 0.180840E+09 |
| May | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111737E+09 | 82617064.53 |
| June | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.180952E+09 | 18995613.96 |
| July | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.137700E+09 | 10735433.76 |
| August | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108760E+09 | 23061737.12 |
| September | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 39422431.04 | 36027842.26 |
| October | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12214854.78 | 0.171896E+09 |
| November | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.317263E+09 |
| December | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.356146E+09 |
| Annual Sum or Average | 0.512427E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.635426E+09 | 0.226963E+10 |
| Minimum of Months | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10735433.76 |
| Maximum of Months | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.180952E+09 | 0.408272E+09 |
Report: SpaceGainsMonthly
For: OFFICE
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.227408E+09 | 0.609777E+09 | 0.787690E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.441586E+09 |
| February | 0.216037E+09 | 0.564682E+09 | 0.723971E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.385153E+09 |
| March | 0.261519E+09 | 0.654405E+09 | 0.827804E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 250566.16 | 0.384929E+09 |
| April | 0.227408E+09 | 0.599704E+09 | 0.770907E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 24111678.83 | 0.237263E+09 |
| May | 0.250148E+09 | 0.639529E+09 | 0.814432E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 59437507.09 | 0.141744E+09 |
| June | 0.250148E+09 | 0.629456E+09 | 0.797650E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107663E+09 | 64617804.38 |
| July | 0.227408E+09 | 0.609777E+09 | 0.787690E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 68963814.08 | 60199241.45 |
| August | 0.261519E+09 | 0.654405E+09 | 0.827804E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 54625172.80 | 73323380.76 |
| September | 0.227408E+09 | 0.599704E+09 | 0.770907E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 20208267.64 | 81556061.65 |
| October | 0.238778E+09 | 0.624653E+09 | 0.801061E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6379381.13 | 0.231705E+09 |
| November | 0.227408E+09 | 0.599704E+09 | 0.770907E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.374295E+09 |
| December | 0.227408E+09 | 0.609777E+09 | 0.787690E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.389794E+09 |
| Annual Sum or Average | 0.284259E+10 | 0.739557E+10 | 0.946851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.341640E+09 | 0.286617E+10 |
| Minimum of Months | 0.216037E+09 | 0.564682E+09 | 0.723971E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60199241.45 |
| Maximum of Months | 0.261519E+09 | 0.654405E+09 | 0.827804E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107663E+09 | 0.441586E+09 |
Report: SpaceGainsMonthly
For: G NE APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.407532E+09 |
| February | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 131483.27 | 0.341346E+09 |
| March | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1636940.54 | 0.321595E+09 |
| April | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 42686804.93 | 0.183185E+09 |
| May | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111737E+09 | 83599168.75 |
| June | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.180952E+09 | 18994956.69 |
| July | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.137700E+09 | 10735431.24 |
| August | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108760E+09 | 23061731.55 |
| September | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 39422443.29 | 36023629.10 |
| October | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12214863.10 | 0.171966E+09 |
| November | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.316937E+09 |
| December | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.355801E+09 |
| Annual Sum or Average | 0.512427E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.635242E+09 | 0.227078E+10 |
| Minimum of Months | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10735431.24 |
| Maximum of Months | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.180952E+09 | 0.407532E+09 |
Report: SpaceGainsMonthly
For: G N1 APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.246706E+09 |
| February | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 94015.05 | 0.207448E+09 |
| March | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1053406.34 | 0.196783E+09 |
| April | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25940162.18 | 0.114298E+09 |
| May | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 67397250.61 | 51227059.18 |
| June | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109146E+09 | 11457746.66 |
| July | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 83057366.88 | 6475336.43 |
| August | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 65601029.51 | 13910244.35 |
| September | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23778633.98 | 21739065.84 |
| October | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7367703.15 | 0.104601E+09 |
| November | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.195873E+09 |
| December | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.215731E+09 |
| Annual Sum or Average | 0.512427E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.383435E+09 | 0.138625E+10 |
| Minimum of Months | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6475336.43 |
| Maximum of Months | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109146E+09 | 0.246706E+09 |
Report: SpaceGainsMonthly
For: G N2 APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.246681E+09 |
| February | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 92276.91 | 0.207472E+09 |
| March | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1045941.61 | 0.196823E+09 |
| April | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25927827.03 | 0.114424E+09 |
| May | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 67397250.79 | 51251070.66 |
| June | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109146E+09 | 11457746.60 |
| July | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 83057367.22 | 6475336.40 |
| August | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 65601029.57 | 13910244.25 |
| September | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23778634.08 | 21739115.29 |
| October | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7367703.20 | 0.104595E+09 |
| November | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.195843E+09 |
| December | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.215745E+09 |
| Annual Sum or Average | 0.512427E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.383414E+09 | 0.138642E+10 |
| Minimum of Months | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6475336.40 |
| Maximum of Months | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109146E+09 | 0.246681E+09 |
Report: SpaceGainsMonthly
For: G S1 APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.270066E+09 |
| February | 0.389025E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.229910E+09 |
| March | 0.418950E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 184106.16 | 0.221287E+09 |
| April | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25567821.27 | 0.120214E+09 |
| May | 0.424935E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 67397224.98 | 51418907.69 |
| June | 0.406980E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109146E+09 | 11457745.48 |
| July | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 83057363.40 | 6475337.53 |
| August | 0.418950E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 65601031.55 | 13910248.48 |
| September | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23778630.46 | 21739278.05 |
| October | 0.430920E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7367700.24 | 0.105170E+09 |
| November | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.213278E+09 |
| December | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.236606E+09 |
| Annual Sum or Average | 0.505732E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.382100E+09 | 0.150153E+10 |
| Minimum of Months | 0.389025E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6475337.53 |
| Maximum of Months | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109146E+09 | 0.270066E+09 |
Report: SpaceGainsMonthly
For: G S2 APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.270568E+09 |
| February | 0.389025E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.231022E+09 |
| March | 0.418950E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 184104.63 | 0.223098E+09 |
| April | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25564785.82 | 0.121233E+09 |
| May | 0.424935E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 67397211.34 | 51649312.32 |
| June | 0.406980E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109146E+09 | 11457755.37 |
| July | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 83057365.16 | 6475338.04 |
| August | 0.418950E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 65601021.34 | 13910254.51 |
| September | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23778632.21 | 21739283.52 |
| October | 0.430920E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7367700.71 | 0.105179E+09 |
| November | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.213666E+09 |
| December | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.237675E+09 |
| Annual Sum or Average | 0.505732E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.382097E+09 | 0.150767E+10 |
| Minimum of Months | 0.389025E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6475338.04 |
| Maximum of Months | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109146E+09 | 0.270568E+09 |
Report: SpaceGainsMonthly
For: M SW APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.638797E+09 |
| February | 0.389025E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.556707E+09 |
| March | 0.418950E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 420988.57 | 0.563174E+09 |
| April | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 60529436.12 | 0.288856E+09 |
| May | 0.424935E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.159804E+09 | 0.123047E+09 |
| June | 0.406980E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.259236E+09 | 27508980.61 |
| July | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.197175E+09 | 15617226.61 |
| August | 0.418950E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.155709E+09 | 33390991.45 |
| September | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 56361915.49 | 52004064.99 |
| October | 0.430920E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17433496.52 | 0.248794E+09 |
| November | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.489627E+09 |
| December | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.549153E+09 |
| Annual Sum or Average | 0.505732E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.906670E+09 | 0.358668E+10 |
| Minimum of Months | 0.389025E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15617226.61 |
| Maximum of Months | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.259236E+09 | 0.638797E+09 |
Report: SpaceGainsMonthly
For: M NW APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.592165E+09 |
| February | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.512680E+09 |
| March | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 421031.61 | 0.523069E+09 |
| April | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 60534790.64 | 0.283150E+09 |
| May | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.159804E+09 | 0.122976E+09 |
| June | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.259236E+09 | 27508983.79 |
| July | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.197175E+09 | 15617225.41 |
| August | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.155709E+09 | 33391033.53 |
| September | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 56361936.64 | 51916160.34 |
| October | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17433505.77 | 0.243645E+09 |
| November | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.448505E+09 |
| December | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.513745E+09 |
| Annual Sum or Average | 0.512427E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.906676E+09 | 0.336837E+10 |
| Minimum of Months | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15617225.41 |
| Maximum of Months | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.259236E+09 | 0.592165E+09 |
Report: SpaceGainsMonthly
For: M SE APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.639548E+09 |
| February | 0.389025E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.559464E+09 |
| March | 0.418950E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 420992.25 | 0.565890E+09 |
| April | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 60529508.10 | 0.290724E+09 |
| May | 0.424935E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.159804E+09 | 0.123629E+09 |
| June | 0.406980E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.259236E+09 | 27508976.61 |
| July | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.197175E+09 | 15617223.26 |
| August | 0.418950E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.155709E+09 | 33390319.86 |
| September | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 56361944.28 | 52004368.57 |
| October | 0.430920E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17433501.30 | 0.248592E+09 |
| November | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.490232E+09 |
| December | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.550266E+09 |
| Annual Sum or Average | 0.505732E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.906670E+09 | 0.359687E+10 |
| Minimum of Months | 0.389025E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15617223.26 |
| Maximum of Months | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.259236E+09 | 0.639548E+09 |
Report: SpaceGainsMonthly
For: M NE APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.590366E+09 |
| February | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.513942E+09 |
| March | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 421028.74 | 0.526972E+09 |
| April | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 60529553.95 | 0.285749E+09 |
| May | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.159804E+09 | 0.123562E+09 |
| June | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.259236E+09 | 27508978.98 |
| July | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.197175E+09 | 15617221.63 |
| August | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.155709E+09 | 33390656.81 |
| September | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 56361953.89 | 51930661.95 |
| October | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17433518.28 | 0.244175E+09 |
| November | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.448144E+09 |
| December | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.513129E+09 |
| Annual Sum or Average | 0.512427E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.906671E+09 | 0.337449E+10 |
| Minimum of Months | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15617221.63 |
| Maximum of Months | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.259236E+09 | 0.590366E+09 |
Report: SpaceGainsMonthly
For: M N1 APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.360118E+09 |
| February | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.317459E+09 |
| March | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 253958.00 | 0.327210E+09 |
| April | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36510724.41 | 0.175318E+09 |
| May | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 96389875.98 | 74790412.52 |
| June | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.156365E+09 | 16592703.96 |
| July | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118931E+09 | 9419906.31 |
| August | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 93919809.40 | 20141455.67 |
| September | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33996128.81 | 31381683.30 |
| October | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10515468.08 | 0.149974E+09 |
| November | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.279336E+09 |
| December | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.312236E+09 |
| Annual Sum or Average | 0.512427E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.546882E+09 | 0.207398E+10 |
| Minimum of Months | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9419906.31 |
| Maximum of Months | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.156365E+09 | 0.360118E+09 |
Report: SpaceGainsMonthly
For: M N2 APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.360046E+09 |
| February | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.317618E+09 |
| March | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 253957.46 | 0.327473E+09 |
| April | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36510277.67 | 0.175414E+09 |
| May | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 96389880.79 | 74800154.50 |
| June | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.156365E+09 | 16592703.80 |
| July | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118931E+09 | 9419906.26 |
| August | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 93919809.90 | 20141455.48 |
| September | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33996128.92 | 31381327.41 |
| October | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10515468.15 | 0.149965E+09 |
| November | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.279289E+09 |
| December | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.312260E+09 |
| Annual Sum or Average | 0.512427E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.546881E+09 | 0.207440E+10 |
| Minimum of Months | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9419906.26 |
| Maximum of Months | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.156365E+09 | 0.360046E+09 |
Report: SpaceGainsMonthly
For: M S1 APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.403663E+09 |
| February | 0.389025E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.352861E+09 |
| March | 0.418950E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 253935.35 | 0.353539E+09 |
| April | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36509940.39 | 0.178205E+09 |
| May | 0.424935E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 96389853.91 | 74802622.90 |
| June | 0.406980E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.156365E+09 | 16592702.22 |
| July | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118931E+09 | 9419907.44 |
| August | 0.418950E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 93919809.93 | 20141460.62 |
| September | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33996115.22 | 31399056.77 |
| October | 0.430920E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10515460.32 | 0.151381E+09 |
| November | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.304473E+09 |
| December | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.346464E+09 |
| Annual Sum or Average | 0.505732E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.546881E+09 | 0.224294E+10 |
| Minimum of Months | 0.389025E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9419907.44 |
| Maximum of Months | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.156365E+09 | 0.403663E+09 |
Report: SpaceGainsMonthly
For: M S2 APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.403657E+09 |
| February | 0.389025E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.353021E+09 |
| March | 0.418950E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 253935.36 | 0.353636E+09 |
| April | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36509941.03 | 0.178247E+09 |
| May | 0.424935E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 96389856.06 | 74811777.82 |
| June | 0.406980E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.156365E+09 | 16592702.05 |
| July | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118931E+09 | 9419907.38 |
| August | 0.418950E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 93919807.88 | 20141460.43 |
| September | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33996115.55 | 31399119.25 |
| October | 0.430920E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10515460.48 | 0.151375E+09 |
| November | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.304447E+09 |
| December | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.346526E+09 |
| Annual Sum or Average | 0.505732E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.546881E+09 | 0.224327E+10 |
| Minimum of Months | 0.389025E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9419907.38 |
| Maximum of Months | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.156365E+09 | 0.403657E+09 |
Report: SpaceGainsMonthly
For: T SW APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.821469E+09 |
| February | 0.389025E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.699369E+09 |
| March | 0.418950E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 511758.93 | 0.691501E+09 |
| April | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 79075663.19 | 0.346976E+09 |
| May | 0.424935E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.209355E+09 | 0.148697E+09 |
| June | 0.406980E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.340786E+09 | 36342941.48 |
| July | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.258944E+09 | 21111866.29 |
| August | 0.418950E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.204423E+09 | 44347482.87 |
| September | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 73787874.54 | 66369285.81 |
| October | 0.430920E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22746689.86 | 0.295069E+09 |
| November | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.598289E+09 |
| December | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.711426E+09 |
| Annual Sum or Average | 0.505732E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118963E+10 | 0.448097E+10 |
| Minimum of Months | 0.389025E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21111866.29 |
| Maximum of Months | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.340786E+09 | 0.821469E+09 |
Report: SpaceGainsMonthly
For: T NW APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.781787E+09 |
| February | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.665013E+09 |
| March | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 514968.13 | 0.656473E+09 |
| April | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 79078915.69 | 0.337083E+09 |
| May | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.209355E+09 | 0.148625E+09 |
| June | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.340786E+09 | 36409583.80 |
| July | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.258944E+09 | 21111632.14 |
| August | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.204423E+09 | 44307844.84 |
| September | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 73787867.92 | 65493521.46 |
| October | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22746693.11 | 0.279560E+09 |
| November | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.561382E+09 |
| December | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.678419E+09 |
| Annual Sum or Average | 0.512427E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118964E+10 | 0.427566E+10 |
| Minimum of Months | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21111632.14 |
| Maximum of Months | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.340786E+09 | 0.781787E+09 |
Report: SpaceGainsMonthly
For: T SE APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.822791E+09 |
| February | 0.389025E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.701881E+09 |
| March | 0.418950E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 511764.35 | 0.695426E+09 |
| April | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 79075801.16 | 0.352087E+09 |
| May | 0.424935E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.209355E+09 | 0.152085E+09 |
| June | 0.406980E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.340786E+09 | 36205972.74 |
| July | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.258945E+09 | 21132769.71 |
| August | 0.418950E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.204423E+09 | 44366391.04 |
| September | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 73787927.60 | 66803563.19 |
| October | 0.430920E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22746710.46 | 0.296283E+09 |
| November | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.600557E+09 |
| December | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.711842E+09 |
| Annual Sum or Average | 0.505732E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118963E+10 | 0.450146E+10 |
| Minimum of Months | 0.389025E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21132769.71 |
| Maximum of Months | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.340786E+09 | 0.822791E+09 |
Report: SpaceGainsMonthly
For: T NE APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.778639E+09 |
| February | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.664998E+09 |
| March | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 511799.51 | 0.656903E+09 |
| April | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 79075800.55 | 0.341626E+09 |
| May | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.209355E+09 | 0.152208E+09 |
| June | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.340786E+09 | 36264531.58 |
| July | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.258945E+09 | 21129345.39 |
| August | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.204423E+09 | 44330433.07 |
| September | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 73787910.76 | 66104611.82 |
| October | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22746717.42 | 0.282155E+09 |
| November | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.558728E+09 |
| December | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.676905E+09 |
| Annual Sum or Average | 0.512427E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118963E+10 | 0.427999E+10 |
| Minimum of Months | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21129345.39 |
| Maximum of Months | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.340786E+09 | 0.778639E+09 |
Report: SpaceGainsMonthly
For: T N1 APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.470479E+09 |
| February | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.401561E+09 |
| March | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 309309.46 | 0.395833E+09 |
| April | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 47698536.75 | 0.208281E+09 |
| May | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126278E+09 | 93550635.53 |
| June | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.205554E+09 | 22231105.64 |
| July | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.156189E+09 | 12752865.70 |
| August | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123303E+09 | 26923640.86 |
| September | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 44507031.91 | 40456835.30 |
| October | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13720259.12 | 0.175350E+09 |
| November | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.338636E+09 |
| December | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.408568E+09 |
| Annual Sum or Average | 0.512427E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.717558E+09 | 0.259462E+10 |
| Minimum of Months | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12752865.70 |
| Maximum of Months | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.205554E+09 | 0.470479E+09 |
Report: SpaceGainsMonthly
For: T N2 APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.470419E+09 |
| February | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.401650E+09 |
| March | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 309073.21 | 0.396060E+09 |
| April | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 47697275.38 | 0.208528E+09 |
| May | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126278E+09 | 93655497.42 |
| June | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.205554E+09 | 22228566.54 |
| July | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.156189E+09 | 12752932.06 |
| August | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123303E+09 | 26923042.16 |
| September | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 44507032.25 | 40459761.51 |
| October | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13720259.27 | 0.175326E+09 |
| November | 0.421173E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.338610E+09 |
| December | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.408558E+09 |
| Annual Sum or Average | 0.512427E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.717557E+09 | 0.259517E+10 |
| Minimum of Months | 0.393095E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12752932.06 |
| Maximum of Months | 0.435212E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.205554E+09 | 0.470419E+09 |
Report: SpaceGainsMonthly
For: T S1 APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.502234E+09 |
| February | 0.389025E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.430410E+09 |
| March | 0.418950E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 308688.53 | 0.425584E+09 |
| April | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 47696600.24 | 0.215885E+09 |
| May | 0.424935E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126278E+09 | 93541835.19 |
| June | 0.406980E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.205554E+09 | 22218454.70 |
| July | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.156189E+09 | 12754354.60 |
| August | 0.418950E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123303E+09 | 26948226.80 |
| September | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 44507025.25 | 40909188.31 |
| October | 0.430920E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13720249.69 | 0.185634E+09 |
| November | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.369121E+09 |
| December | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.434520E+09 |
| Annual Sum or Average | 0.505732E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.717555E+09 | 0.275976E+10 |
| Minimum of Months | 0.389025E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12754354.60 |
| Maximum of Months | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.205554E+09 | 0.502234E+09 |
Report: SpaceGainsMonthly
For: T S2 APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.502291E+09 |
| February | 0.389025E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.430593E+09 |
| March | 0.418950E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 308688.59 | 0.425800E+09 |
| April | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 47696613.50 | 0.216104E+09 |
| May | 0.424935E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126278E+09 | 93626336.82 |
| June | 0.406980E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.205554E+09 | 22215559.26 |
| July | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.156189E+09 | 12754418.99 |
| August | 0.418950E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123303E+09 | 26947533.56 |
| September | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 44507026.73 | 40907738.59 |
| October | 0.430920E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13720250.30 | 0.185557E+09 |
| November | 0.418950E+09 | 0.119524E+09 | 0.100379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.369114E+09 |
| December | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.434551E+09 |
| Annual Sum or Average | 0.505732E+10 | 0.145421E+10 | 0.122128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.717555E+09 | 0.276046E+10 |
| Minimum of Months | 0.389025E+09 | 0.111556E+09 | 0.936871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12754418.99 |
| Maximum of Months | 0.436905E+09 | 0.123508E+09 | 0.103725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.205554E+09 | 0.502291E+09 |
Report: SpaceGainsMonthly
For: T CORRIDOR
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.727675E+09 | 0.992689E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.137320E+09 |
| February | 0.657255E+09 | 0.896622E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120791E+09 |
| March | 0.727675E+09 | 0.992689E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60863.10 | 0.124365E+09 |
| April | 0.704201E+09 | 0.960667E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6424608.29 | 71235626.68 |
| May | 0.727675E+09 | 0.992689E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18089218.85 | 37277370.32 |
| June | 0.704201E+09 | 0.960667E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35675948.78 | 12208339.49 |
| July | 0.727675E+09 | 0.992689E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24627908.77 | 9548638.69 |
| August | 0.727675E+09 | 0.992689E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19307037.96 | 14206503.33 |
| September | 0.704201E+09 | 0.960667E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5888257.06 | 17149473.48 |
| October | 0.727675E+09 | 0.992689E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1666643.98 | 60961229.71 |
| November | 0.704201E+09 | 0.960667E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105160E+09 |
| December | 0.727675E+09 | 0.992689E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.117728E+09 |
| Annual Sum or Average | 0.856778E+10 | 0.116881E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111740E+09 | 0.827952E+09 |
| Minimum of Months | 0.657255E+09 | 0.896622E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9548638.69 |
| Maximum of Months | 0.727675E+09 | 0.992689E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35675948.78 | 0.137320E+09 |
Report: SpaceGainsMonthly
For: G CORRIDOR
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.727675E+09 | 0.992689E+09 | 0.299778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.251535E+10 |
| February | 0.657255E+09 | 0.896622E+09 | 0.270767E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 34049.78 | 0.191176E+10 |
| March | 0.727675E+09 | 0.992689E+09 | 0.299778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4505930.91 | 0.170869E+10 |
| April | 0.704201E+09 | 0.960667E+09 | 0.290107E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127056E+09 | 0.982794E+09 |
| May | 0.727675E+09 | 0.992689E+09 | 0.299778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.290849E+09 | 0.521962E+09 |
| June | 0.704201E+09 | 0.960667E+09 | 0.290107E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.621085E+09 | 0.244799E+09 |
| July | 0.727675E+09 | 0.992689E+09 | 0.299778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.514528E+09 | 0.217119E+09 |
| August | 0.727675E+09 | 0.992689E+09 | 0.299778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.406191E+09 | 0.351548E+09 |
| September | 0.704201E+09 | 0.960667E+09 | 0.290107E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.210555E+09 | 0.579445E+09 |
| October | 0.727675E+09 | 0.992689E+09 | 0.299778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 37317186.81 | 0.127660E+10 |
| November | 0.704201E+09 | 0.960667E+09 | 0.290107E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.218673E+10 |
| December | 0.727675E+09 | 0.992689E+09 | 0.299778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.276971E+10 |
| Annual Sum or Average | 0.856778E+10 | 0.116881E+11 | 0.352964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.221212E+10 | 0.152665E+11 |
| Minimum of Months | 0.657255E+09 | 0.896622E+09 | 0.270767E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.217119E+09 |
| Maximum of Months | 0.727675E+09 | 0.992689E+09 | 0.299778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.621085E+09 | 0.276971E+10 |
Report: SpaceGainsMonthly
For: M CORRIDOR
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.727675E+09 | 0.992689E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.117872E+09 |
| February | 0.657255E+09 | 0.896622E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105262E+09 |
| March | 0.727675E+09 | 0.992689E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 128.43 | 0.110144E+09 |
| April | 0.704201E+09 | 0.960667E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5236743.49 | 62874952.99 |
| May | 0.727675E+09 | 0.992689E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15295797.99 | 32249470.90 |
| June | 0.704201E+09 | 0.960667E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29989452.88 | 9731565.28 |
| July | 0.727675E+09 | 0.992689E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21396540.15 | 7316137.79 |
| August | 0.727675E+09 | 0.992689E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16723233.55 | 11215028.54 |
| September | 0.704201E+09 | 0.960667E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5136798.86 | 14190374.63 |
| October | 0.727675E+09 | 0.992689E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1442920.55 | 54171240.41 |
| November | 0.704201E+09 | 0.960667E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93611260.06 |
| December | 0.727675E+09 | 0.992689E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101058E+09 |
| Annual Sum or Average | 0.856778E+10 | 0.116881E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 95221615.89 | 0.719695E+09 |
| Minimum of Months | 0.657255E+09 | 0.896622E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7316137.79 |
| Maximum of Months | 0.727675E+09 | 0.992689E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29989452.88 | 0.117872E+09 |
Report: PeakSpaceGainsMonthly
For: G SW APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 713.52 | 25-JAN-24:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 901.17 | 09-FEB-01:00 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.18 | 22-MAR-13:00 | 644.41 | 19-MAR-24:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 398.09 | 21-APR-15:00 | 674.77 | 10-APR-24:00 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 368.39 | 19-MAY-14:00 | 290.19 | 04-MAY-02:00 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 424.83 | 21-JUN-13:00 | 219.77 | 28-JUN-02:00 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 357.87 | 02-JUL-21:00 | 112.63 | 18-JUL-21:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 315.76 | 26-AUG-15:00 | 165.59 | 14-AUG-01:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 132.85 | 15-SEP-15:00 | 118.57 | 24-SEP-07:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 164.42 | 01-OCT-15:00 | 350.77 | 23-OCT-21:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 484.90 | 15-NOV-09:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 622.66 | 18-DEC-08:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 112.63 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 424.83 | 901.17 |
Report: PeakSpaceGainsMonthly
For: G NW APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 713.52 | 25-JAN-24:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.62 | 06-FEB-14:00 | 901.17 | 09-FEB-01:00 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 55.71 | 22-MAR-12:20 | 644.41 | 19-MAR-24:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 398.09 | 21-APR-15:00 | 660.62 | 11-APR-02:00 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 368.39 | 19-MAY-14:00 | 285.54 | 04-MAY-02:00 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 424.83 | 21-JUN-13:00 | 219.77 | 28-JUN-02:00 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 357.87 | 02-JUL-21:00 | 112.63 | 18-JUL-21:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 315.76 | 26-AUG-15:00 | 165.59 | 14-AUG-01:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 132.85 | 15-SEP-15:00 | 118.18 | 24-SEP-07:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 164.42 | 01-OCT-15:00 | 346.91 | 23-OCT-21:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 430.65 | 26-NOV-09:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 622.66 | 18-DEC-08:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 112.63 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 424.83 | 901.17 |
Report: PeakSpaceGainsMonthly
For: OFFICE
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 451.21 | 03-JAN-08:09 | 582.92 | 03-JAN-08:09 | 588.62 | 03-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 664.18 | 25-JAN-23:00 |
| February | 451.21 | 01-FEB-08:09 | 582.92 | 01-FEB-08:09 | 588.62 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 934.97 | 08-FEB-18:00 |
| March | 451.21 | 01-MAR-08:09 | 582.92 | 01-MAR-08:09 | 588.62 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 27.18 | 22-MAR-13:00 | 649.71 | 19-MAR-24:00 |
| April | 451.21 | 03-APR-07:10 | 582.92 | 03-APR-07:10 | 588.62 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 398.09 | 21-APR-15:00 | 724.23 | 10-APR-24:00 |
| May | 451.21 | 01-MAY-07:10 | 582.92 | 01-MAY-07:10 | 588.62 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 368.39 | 19-MAY-14:00 | 373.74 | 04-MAY-02:00 |
| June | 451.21 | 01-JUN-07:10 | 582.92 | 01-JUN-07:10 | 588.62 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 424.83 | 21-JUN-13:00 | 300.62 | 28-JUN-02:00 |
| July | 451.21 | 03-JUL-07:10 | 582.92 | 03-JUL-07:10 | 588.62 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 258.33 | 27-JUL-15:00 | 216.43 | 18-JUL-21:00 |
| August | 451.21 | 01-AUG-07:10 | 582.92 | 01-AUG-07:10 | 588.62 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 243.18 | 07-AUG-16:00 | 275.34 | 14-AUG-01:00 |
| September | 451.21 | 01-SEP-07:10 | 582.92 | 01-SEP-07:10 | 588.62 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 132.84 | 15-SEP-15:00 | 194.17 | 23-SEP-17:00 |
| October | 451.21 | 02-OCT-07:10 | 582.92 | 02-OCT-07:10 | 588.62 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 121.62 | 05-OCT-16:00 | 422.07 | 23-OCT-18:00 |
| November | 451.21 | 01-NOV-07:10 | 582.92 | 01-NOV-07:10 | 588.62 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 568.83 | 15-NOV-09:00 |
| December | 451.21 | 01-DEC-08:09 | 582.92 | 01-DEC-08:09 | 588.62 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 617.03 | 18-DEC-08:10 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 451.21 | 582.92 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 194.17 | |||||
| Maximum of Months | 451.21 | 582.92 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 424.83 | 934.97 |
Report: PeakSpaceGainsMonthly
For: G NE APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 713.52 | 25-JAN-24:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.77 | 06-FEB-14:00 | 901.17 | 09-FEB-01:00 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 50.94 | 22-MAR-12:50 | 644.41 | 19-MAR-24:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 398.09 | 21-APR-15:00 | 660.62 | 11-APR-02:00 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 368.39 | 19-MAY-14:00 | 284.99 | 04-MAY-02:00 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 424.83 | 21-JUN-13:00 | 219.77 | 28-JUN-02:00 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 357.87 | 02-JUL-21:00 | 112.63 | 18-JUL-21:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 315.76 | 26-AUG-15:00 | 165.59 | 14-AUG-01:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 132.85 | 15-SEP-15:00 | 118.57 | 24-SEP-07:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 164.42 | 01-OCT-15:00 | 345.68 | 23-OCT-18:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 436.18 | 15-NOV-09:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 622.66 | 18-DEC-08:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 112.63 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 424.83 | 901.17 |
Report: PeakSpaceGainsMonthly
For: G N1 APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 430.38 | 25-JAN-24:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.92 | 20-FEB-16:00 | 543.56 | 09-FEB-01:00 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.67 | 22-MAR-12:50 | 388.69 | 19-MAR-24:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 240.12 | 21-APR-15:00 | 420.27 | 10-APR-24:00 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 222.20 | 19-MAY-14:00 | 188.33 | 04-MAY-02:00 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 256.25 | 21-JUN-13:00 | 132.56 | 28-JUN-02:00 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 215.86 | 02-JUL-21:00 | 67.94 | 18-JUL-21:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 190.46 | 26-AUG-15:00 | 99.88 | 14-AUG-01:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 80.13 | 15-SEP-15:00 | 71.52 | 24-SEP-07:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 99.17 | 01-OCT-15:00 | 211.57 | 23-OCT-21:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 270.27 | 15-NOV-09:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 375.57 | 18-DEC-08:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.94 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 256.25 | 543.56 |
Report: PeakSpaceGainsMonthly
For: G N2 APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 430.38 | 25-JAN-24:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.87 | 20-FEB-16:00 | 543.56 | 09-FEB-01:00 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.53 | 22-MAR-12:50 | 388.69 | 19-MAR-24:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 240.12 | 21-APR-15:00 | 420.53 | 10-APR-24:00 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 222.20 | 19-MAY-14:00 | 188.41 | 04-MAY-02:00 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 256.25 | 21-JUN-13:00 | 132.56 | 28-JUN-02:00 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 215.86 | 02-JUL-21:00 | 67.94 | 18-JUL-21:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 190.46 | 26-AUG-15:00 | 99.88 | 14-AUG-01:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 80.13 | 15-SEP-15:00 | 71.52 | 24-SEP-07:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 99.17 | 01-OCT-15:00 | 211.57 | 23-OCT-21:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 270.46 | 15-NOV-09:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 375.57 | 18-DEC-08:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.94 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 256.25 | 543.56 |
Report: PeakSpaceGainsMonthly
For: G S1 APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 430.38 | 25-JAN-24:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 571.03 | 08-FEB-18:00 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.39 | 22-MAR-13:00 | 408.04 | 19-MAR-24:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 240.12 | 21-APR-15:00 | 434.93 | 10-APR-24:00 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 222.20 | 19-MAY-14:00 | 191.02 | 04-MAY-02:00 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 256.25 | 21-JUN-13:00 | 132.56 | 28-JUN-02:00 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 215.86 | 02-JUL-21:00 | 67.94 | 18-JUL-21:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 190.46 | 26-AUG-15:00 | 99.88 | 14-AUG-01:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 80.13 | 15-SEP-15:00 | 71.52 | 24-SEP-07:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 99.17 | 01-OCT-15:00 | 211.57 | 23-OCT-21:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 309.96 | 15-NOV-09:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 389.16 | 18-DEC-08:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.94 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 256.25 | 571.03 |
Report: PeakSpaceGainsMonthly
For: G S2 APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 430.38 | 25-JAN-24:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 574.33 | 08-FEB-18:00 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.39 | 22-MAR-13:00 | 409.72 | 19-MAR-24:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 240.12 | 21-APR-15:00 | 437.69 | 10-APR-24:00 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 222.20 | 19-MAY-14:00 | 192.39 | 04-MAY-02:70 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 256.25 | 21-JUN-13:00 | 132.56 | 28-JUN-02:00 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 215.86 | 02-JUL-21:00 | 67.94 | 18-JUL-21:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 190.46 | 26-AUG-15:00 | 99.88 | 14-AUG-01:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 80.13 | 15-SEP-15:00 | 71.52 | 24-SEP-07:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 99.17 | 01-OCT-15:00 | 211.57 | 23-OCT-21:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 309.96 | 15-NOV-09:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 390.20 | 18-DEC-08:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.94 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 256.25 | 574.33 |
Report: PeakSpaceGainsMonthly
For: M SW APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 1026.74 | 25-JAN-24:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1359.26 | 08-FEB-18:00 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.28 | 22-MAR-13:00 | 972.64 | 19-MAR-24:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 570.70 | 21-APR-15:00 | 998.54 | 10-APR-24:00 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 528.45 | 19-MAY-14:00 | 450.67 | 04-MAY-02:00 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 609.47 | 21-JUN-13:00 | 316.75 | 28-JUN-02:00 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 513.12 | 02-JUL-21:00 | 162.66 | 18-JUL-21:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 452.91 | 26-AUG-15:00 | 238.72 | 14-AUG-01:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 190.29 | 15-SEP-15:00 | 167.82 | 24-SEP-07:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 235.75 | 01-OCT-15:00 | 504.85 | 23-OCT-21:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 676.75 | 15-NOV-09:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 895.78 | 18-DEC-08:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 162.66 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 609.47 | 1359.26 |
Report: PeakSpaceGainsMonthly
For: M NW APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 1026.74 | 25-JAN-24:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1296.33 | 09-FEB-01:00 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.28 | 22-MAR-13:00 | 927.57 | 19-MAR-24:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 570.70 | 21-APR-15:00 | 983.48 | 10-APR-24:00 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 528.45 | 19-MAY-14:00 | 448.83 | 04-MAY-02:00 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 609.47 | 21-JUN-13:00 | 316.75 | 28-JUN-02:00 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 513.12 | 02-JUL-21:00 | 162.66 | 18-JUL-21:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 452.91 | 26-AUG-15:00 | 238.72 | 14-AUG-01:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 190.29 | 15-SEP-15:00 | 167.54 | 24-SEP-07:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 235.75 | 01-OCT-15:00 | 497.65 | 23-OCT-18:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 619.67 | 26-NOV-09:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 895.78 | 18-DEC-08:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 162.66 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 609.47 | 1296.33 |
Report: PeakSpaceGainsMonthly
For: M SE APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 1026.74 | 25-JAN-24:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1344.44 | 08-FEB-18:00 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.28 | 22-MAR-13:00 | 974.57 | 19-MAR-24:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 570.70 | 21-APR-15:00 | 997.62 | 10-APR-24:00 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 528.45 | 19-MAY-14:00 | 447.86 | 04-MAY-02:00 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 609.47 | 21-JUN-13:00 | 316.75 | 28-JUN-02:00 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 513.12 | 02-JUL-21:00 | 162.66 | 18-JUL-21:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 452.91 | 26-AUG-15:00 | 238.72 | 14-AUG-01:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 190.29 | 15-SEP-15:00 | 168.99 | 24-SEP-07:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 235.75 | 01-OCT-15:00 | 503.57 | 23-OCT-21:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 709.38 | 15-NOV-09:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 895.78 | 18-DEC-08:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 162.66 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 609.47 | 1344.44 |
Report: PeakSpaceGainsMonthly
For: M NE APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 1026.74 | 25-JAN-24:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1296.33 | 09-FEB-01:00 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.28 | 22-MAR-13:00 | 927.57 | 19-MAR-24:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 570.70 | 21-APR-15:00 | 982.93 | 10-APR-24:00 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 528.45 | 19-MAY-14:00 | 445.82 | 04-MAY-02:00 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 609.47 | 21-JUN-13:00 | 316.75 | 28-JUN-02:00 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 513.12 | 02-JUL-21:00 | 162.66 | 18-JUL-21:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 452.91 | 26-AUG-15:00 | 238.72 | 14-AUG-01:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 190.29 | 15-SEP-15:00 | 168.73 | 24-SEP-07:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 235.75 | 01-OCT-15:00 | 493.09 | 23-OCT-18:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 619.67 | 26-NOV-09:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 895.78 | 18-DEC-08:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 162.66 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 609.47 | 1296.33 |
Report: PeakSpaceGainsMonthly
For: M N1 APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 619.31 | 25-JAN-24:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 781.91 | 09-FEB-01:00 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.09 | 22-MAR-13:00 | 590.25 | 19-MAR-24:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 344.23 | 21-APR-15:00 | 628.42 | 10-APR-24:00 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 318.75 | 19-MAY-14:00 | 277.20 | 04-MAY-02:70 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 367.62 | 21-JUN-13:00 | 191.06 | 28-JUN-02:00 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 309.50 | 02-JUL-21:00 | 98.11 | 18-JUL-21:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 273.18 | 26-AUG-15:00 | 143.99 | 14-AUG-01:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 114.78 | 15-SEP-15:00 | 102.45 | 24-SEP-07:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 142.20 | 01-OCT-15:00 | 302.54 | 23-OCT-21:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 382.10 | 15-NOV-09:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 540.31 | 18-DEC-08:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.11 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 367.62 | 781.91 |
Report: PeakSpaceGainsMonthly
For: M N2 APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 619.31 | 25-JAN-24:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 781.91 | 09-FEB-01:00 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.09 | 22-MAR-13:00 | 590.33 | 19-MAR-24:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 344.23 | 21-APR-15:00 | 628.43 | 10-APR-24:00 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 318.75 | 19-MAY-14:00 | 277.20 | 04-MAY-02:70 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 367.62 | 21-JUN-13:00 | 191.06 | 28-JUN-02:00 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 309.50 | 02-JUL-21:00 | 98.11 | 18-JUL-21:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 273.18 | 26-AUG-15:00 | 143.99 | 14-AUG-01:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 114.78 | 15-SEP-15:00 | 102.46 | 24-SEP-07:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 142.20 | 01-OCT-15:00 | 302.42 | 23-OCT-21:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 382.32 | 15-NOV-09:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 540.31 | 18-DEC-08:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.11 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 367.62 | 781.91 |
Report: PeakSpaceGainsMonthly
For: M S1 APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 619.31 | 25-JAN-24:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 865.45 | 08-FEB-18:00 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.09 | 22-MAR-13:00 | 632.85 | 19-MAR-24:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 344.23 | 21-APR-15:00 | 637.78 | 10-APR-24:00 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 318.75 | 19-MAY-14:00 | 277.20 | 04-MAY-02:70 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 367.62 | 21-JUN-13:00 | 191.06 | 28-JUN-02:00 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 309.50 | 02-JUL-21:00 | 98.11 | 18-JUL-21:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 273.18 | 26-AUG-15:00 | 143.99 | 14-AUG-01:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 114.78 | 15-SEP-15:00 | 102.64 | 24-SEP-07:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 142.20 | 01-OCT-15:00 | 304.51 | 23-OCT-21:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 442.00 | 15-NOV-09:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 560.68 | 18-DEC-08:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.11 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 367.62 | 865.45 |
Report: PeakSpaceGainsMonthly
For: M S2 APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 619.31 | 25-JAN-24:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 865.12 | 08-FEB-18:00 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.09 | 22-MAR-13:00 | 632.96 | 19-MAR-24:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 344.23 | 21-APR-15:00 | 637.71 | 10-APR-24:00 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 318.75 | 19-MAY-14:00 | 277.20 | 04-MAY-02:70 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 367.62 | 21-JUN-13:00 | 191.06 | 28-JUN-02:00 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 309.50 | 02-JUL-21:00 | 98.11 | 18-JUL-21:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 273.18 | 26-AUG-15:00 | 143.99 | 14-AUG-01:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 114.78 | 15-SEP-15:00 | 102.65 | 24-SEP-07:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 142.20 | 01-OCT-15:00 | 304.51 | 23-OCT-21:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 442.42 | 15-NOV-09:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 560.65 | 18-DEC-08:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.11 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 367.62 | 865.12 |
Report: PeakSpaceGainsMonthly
For: T SW APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 1361.76 | 25-JAN-24:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1718.19 | 09-FEB-01:00 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 48.59 | 22-MAR-13:00 | 1230.96 | 19-MAR-24:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 751.25 | 21-APR-15:00 | 1260.80 | 11-APR-02:00 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 696.50 | 19-MAY-14:00 | 498.59 | 04-MAY-02:00 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 803.44 | 21-JUN-13:00 | 411.04 | 28-JUN-02:00 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 675.69 | 02-JUL-21:00 | 217.29 | 18-JUL-21:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 596.81 | 26-AUG-15:00 | 317.79 | 14-AUG-01:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 250.04 | 15-SEP-15:00 | 212.25 | 23-SEP-17:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 310.44 | 01-OCT-15:00 | 660.61 | 23-OCT-18:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 821.80 | 26-NOV-09:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1187.50 | 18-DEC-08:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 212.25 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 803.44 | 1718.19 |
Report: PeakSpaceGainsMonthly
For: T NW APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 1361.76 | 25-JAN-24:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1718.19 | 09-FEB-01:00 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 48.59 | 22-MAR-13:00 | 1230.96 | 19-MAR-24:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 751.25 | 21-APR-15:00 | 1260.80 | 11-APR-02:00 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 696.50 | 19-MAY-14:00 | 497.01 | 04-MAY-02:00 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 803.44 | 21-JUN-13:00 | 412.59 | 28-JUN-02:00 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 675.69 | 02-JUL-21:00 | 217.29 | 18-JUL-21:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 596.81 | 26-AUG-15:00 | 317.79 | 14-AUG-01:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 250.04 | 15-SEP-15:00 | 212.25 | 23-SEP-17:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 310.44 | 01-OCT-15:00 | 638.47 | 23-OCT-18:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 821.80 | 26-NOV-09:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1187.50 | 18-DEC-08:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 212.25 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 803.44 | 1718.19 |
Report: PeakSpaceGainsMonthly
For: T SE APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 1361.76 | 25-JAN-24:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1718.19 | 09-FEB-01:00 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 48.59 | 22-MAR-13:00 | 1230.96 | 19-MAR-24:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 751.25 | 21-APR-15:00 | 1260.80 | 11-APR-02:00 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 696.50 | 19-MAY-14:00 | 492.88 | 04-MAY-02:00 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 803.44 | 21-JUN-13:00 | 405.75 | 28-JUN-02:00 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 675.69 | 02-JUL-21:00 | 217.29 | 18-JUL-21:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 596.81 | 26-AUG-15:00 | 317.79 | 14-AUG-01:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 250.04 | 15-SEP-15:00 | 212.25 | 23-SEP-17:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 310.44 | 01-OCT-15:00 | 657.80 | 23-OCT-18:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 821.80 | 26-NOV-09:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1187.50 | 18-DEC-08:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 212.25 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 803.44 | 1718.19 |
Report: PeakSpaceGainsMonthly
For: T NE APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 1361.76 | 25-JAN-24:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1718.19 | 09-FEB-01:00 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 48.59 | 22-MAR-13:00 | 1230.96 | 19-MAR-24:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 751.25 | 21-APR-15:00 | 1260.80 | 11-APR-02:00 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 696.50 | 19-MAY-14:00 | 491.33 | 04-MAY-02:00 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 803.44 | 21-JUN-13:00 | 407.46 | 28-JUN-02:00 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 675.69 | 02-JUL-21:00 | 217.29 | 18-JUL-21:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 596.81 | 26-AUG-15:00 | 317.79 | 14-AUG-01:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 250.04 | 15-SEP-15:00 | 212.25 | 23-SEP-17:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 310.44 | 01-OCT-15:00 | 604.66 | 23-OCT-18:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 821.80 | 26-NOV-09:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1187.50 | 18-DEC-08:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 212.25 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 803.44 | 1718.19 |
Report: PeakSpaceGainsMonthly
For: T N1 APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 821.38 | 25-JAN-24:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1036.37 | 09-FEB-01:00 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 29.31 | 22-MAR-13:00 | 742.49 | 19-MAR-24:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 453.13 | 21-APR-15:00 | 760.48 | 11-APR-02:00 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 420.11 | 19-MAY-14:00 | 335.74 | 04-MAY-02:00 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 484.61 | 21-JUN-13:00 | 254.20 | 28-JUN-02:00 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 407.56 | 02-JUL-21:00 | 131.06 | 18-JUL-21:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 359.98 | 26-AUG-15:00 | 191.68 | 14-AUG-01:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 150.82 | 15-SEP-15:00 | 128.02 | 23-SEP-17:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 187.25 | 01-OCT-15:00 | 384.96 | 23-OCT-18:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 495.69 | 26-NOV-09:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 716.27 | 18-DEC-08:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 128.02 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 484.61 | 1036.37 |
Report: PeakSpaceGainsMonthly
For: T N2 APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 821.38 | 25-JAN-24:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1036.37 | 09-FEB-01:00 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 29.31 | 22-MAR-13:00 | 742.49 | 19-MAR-24:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 453.13 | 21-APR-15:00 | 760.48 | 11-APR-02:00 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 420.11 | 19-MAY-14:00 | 335.44 | 04-MAY-02:00 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 484.61 | 21-JUN-13:00 | 254.20 | 28-JUN-02:00 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 407.56 | 02-JUL-21:00 | 131.06 | 18-JUL-21:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 359.98 | 26-AUG-15:00 | 191.68 | 14-AUG-01:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 150.82 | 15-SEP-15:00 | 128.02 | 23-SEP-17:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 187.25 | 01-OCT-15:00 | 383.93 | 23-OCT-18:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 495.69 | 26-NOV-09:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 716.27 | 18-DEC-08:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 128.02 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 484.61 | 1036.37 |
Report: PeakSpaceGainsMonthly
For: T S1 APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 821.38 | 25-JAN-24:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1036.37 | 09-FEB-01:00 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 29.31 | 22-MAR-13:00 | 742.49 | 19-MAR-24:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 453.14 | 21-APR-15:00 | 760.48 | 11-APR-02:00 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 420.11 | 19-MAY-14:00 | 337.03 | 04-MAY-02:00 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 484.61 | 21-JUN-13:00 | 254.20 | 28-JUN-02:00 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 407.56 | 02-JUL-21:00 | 131.06 | 18-JUL-21:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 359.98 | 26-AUG-15:00 | 191.68 | 14-AUG-01:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 150.82 | 15-SEP-15:00 | 128.02 | 23-SEP-17:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 187.25 | 01-OCT-15:00 | 398.46 | 23-OCT-18:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 499.39 | 15-NOV-12:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 716.27 | 18-DEC-08:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 128.02 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 484.61 | 1036.37 |
Report: PeakSpaceGainsMonthly
For: T S2 APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 237.50 | 01-JAN-00:10 | 138.88 | 01-JAN-19:10 | 588.62 | 01-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 821.38 | 25-JAN-24:00 |
| February | 237.50 | 01-FEB-00:10 | 138.88 | 01-FEB-19:10 | 588.62 | 01-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1036.37 | 09-FEB-01:00 |
| March | 237.50 | 01-MAR-00:10 | 138.88 | 01-MAR-19:10 | 588.62 | 01-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 29.31 | 22-MAR-13:00 | 742.49 | 19-MAR-24:00 |
| April | 237.50 | 01-APR-00:10 | 138.88 | 01-APR-18:10 | 588.62 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 453.14 | 21-APR-15:00 | 760.48 | 11-APR-02:00 |
| May | 237.50 | 01-MAY-00:10 | 138.88 | 01-MAY-18:10 | 588.62 | 01-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 420.11 | 19-MAY-14:00 | 336.71 | 04-MAY-02:00 |
| June | 237.50 | 01-JUN-00:10 | 138.88 | 01-JUN-18:10 | 588.62 | 01-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 484.61 | 21-JUN-13:00 | 254.20 | 28-JUN-02:00 |
| July | 237.50 | 01-JUL-00:10 | 138.88 | 01-JUL-18:10 | 588.62 | 01-JUL-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 407.56 | 02-JUL-21:00 | 131.06 | 18-JUL-21:00 |
| August | 237.50 | 01-AUG-00:10 | 138.88 | 01-AUG-18:10 | 588.62 | 01-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 359.98 | 26-AUG-15:00 | 191.68 | 14-AUG-01:00 |
| September | 237.50 | 01-SEP-00:10 | 138.88 | 01-SEP-18:10 | 588.62 | 01-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 150.82 | 15-SEP-15:00 | 128.02 | 23-SEP-17:00 |
| October | 237.50 | 01-OCT-00:10 | 138.88 | 01-OCT-18:10 | 588.62 | 01-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 187.25 | 01-OCT-15:00 | 398.46 | 23-OCT-18:00 |
| November | 237.50 | 01-NOV-00:10 | 138.88 | 01-NOV-18:10 | 588.62 | 01-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 502.38 | 15-NOV-12:00 |
| December | 237.50 | 01-DEC-00:10 | 138.88 | 01-DEC-19:10 | 588.62 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 716.27 | 18-DEC-08:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 128.02 | |||||
| Maximum of Months | 237.50 | 138.88 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 484.61 | 1036.37 |
Report: PeakSpaceGainsMonthly
For: T CORRIDOR
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 397.10 | 01-JAN-00:10 | 370.63 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 225.00 | 25-JAN-23:00 |
| February | 397.10 | 01-FEB-00:10 | 370.63 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 305.78 | 08-FEB-18:00 |
| March | 397.10 | 01-MAR-00:10 | 370.63 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.43 | 22-MAR-12:00 | 224.82 | 19-MAR-24:00 |
| April | 397.10 | 01-APR-00:10 | 370.63 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86.60 | 21-APR-15:00 | 230.53 | 10-APR-24:00 |
| May | 397.10 | 01-MAY-00:10 | 370.63 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88.03 | 19-MAY-14:00 | 115.46 | 04-MAY-02:00 |
| June | 397.10 | 01-JUN-00:10 | 370.63 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 101.92 | 21-JUN-13:00 | 90.85 | 28-JUN-02:00 |
| July | 397.10 | 01-JUL-00:10 | 370.63 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.86 | 03-JUL-17:00 | 60.29 | 18-JUL-21:00 |
| August | 397.10 | 01-AUG-00:10 | 370.63 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.72 | 26-AUG-15:00 | 72.14 | 14-AUG-01:00 |
| September | 397.10 | 01-SEP-00:10 | 370.63 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.26 | 10-SEP-15:00 | 51.03 | 23-SEP-17:00 |
| October | 397.10 | 01-OCT-00:10 | 370.63 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.51 | 01-OCT-15:00 | 126.43 | 23-OCT-18:00 |
| November | 397.10 | 01-NOV-00:10 | 370.63 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 136.38 | 26-NOV-09:00 |
| December | 397.10 | 01-DEC-00:10 | 370.63 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 193.83 | 18-DEC-08:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
| Minimum of Months | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.03 | ||||
| Maximum of Months | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 101.92 | 305.78 |
Report: PeakSpaceGainsMonthly
For: G CORRIDOR
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 397.10 | 01-JAN-00:10 | 370.63 | 01-JAN-00:10 | 208.40 | 01-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 12717.79 | 27-JAN-07:01 |
| February | 397.10 | 01-FEB-00:10 | 370.63 | 01-FEB-00:10 | 208.40 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.51 | 06-FEB-14:00 | 13120.94 | 03-FEB-07:01 |
| March | 397.10 | 01-MAR-00:10 | 370.63 | 01-MAR-00:10 | 208.40 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 562.49 | 21-MAR-16:03 | 11308.06 | 02-MAR-07:01 |
| April | 397.10 | 01-APR-00:10 | 370.63 | 01-APR-00:10 | 208.40 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2337.36 | 19-APR-16:02 | 9362.49 | 12-APR-06:01 |
| May | 397.10 | 01-MAY-00:10 | 370.63 | 01-MAY-00:10 | 208.40 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3488.02 | 19-MAY-16:02 | 7203.43 | 02-MAY-06:01 |
| June | 397.10 | 01-JUN-00:10 | 370.63 | 01-JUN-00:10 | 208.40 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5150.31 | 02-JUN-16:01 | 4170.27 | 13-JUN-06:01 |
| July | 397.10 | 01-JUL-00:10 | 370.63 | 01-JUL-00:10 | 208.40 | 01-JUL-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4654.84 | 03-JUL-16:01 | 3869.19 | 05-JUL-06:01 |
| August | 397.10 | 01-AUG-00:10 | 370.63 | 01-AUG-00:10 | 208.40 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4145.86 | 07-AUG-16:01 | 4323.64 | 31-AUG-06:01 |
| September | 397.10 | 01-SEP-00:10 | 370.63 | 01-SEP-00:10 | 208.40 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2826.53 | 19-SEP-16:01 | 8079.81 | 30-SEP-06:01 |
| October | 397.10 | 01-OCT-00:10 | 370.63 | 01-OCT-00:10 | 208.40 | 01-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1936.63 | 01-OCT-16:03 | 8815.18 | 11-OCT-06:01 |
| November | 397.10 | 01-NOV-00:10 | 370.63 | 01-NOV-00:10 | 208.40 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 11240.77 | 17-NOV-07:01 |
| December | 397.10 | 01-DEC-00:10 | 370.63 | 01-DEC-00:10 | 208.40 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 12708.25 | 27-DEC-07:01 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 397.10 | 370.63 | 208.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3869.19 | |||||
| Maximum of Months | 397.10 | 370.63 | 208.40 | 0.00 | 0.00 | 0.00 | 0.00 | 5150.31 | 13120.94 |
Report: PeakSpaceGainsMonthly
For: M CORRIDOR
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 397.10 | 01-JAN-00:10 | 370.63 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 189.09 | 25-JAN-23:00 |
| February | 397.10 | 01-FEB-00:10 | 370.63 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 259.28 | 08-FEB-18:00 |
| March | 397.10 | 01-MAR-00:10 | 370.63 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.21 | 21-MAR-16:00 | 197.44 | 19-MAR-24:00 |
| April | 397.10 | 01-APR-00:10 | 370.63 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.40 | 21-APR-15:00 | 204.24 | 10-APR-24:00 |
| May | 397.10 | 01-MAY-00:10 | 370.63 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.64 | 19-MAY-14:00 | 99.07 | 04-MAY-02:00 |
| June | 397.10 | 01-JUN-00:10 | 370.63 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83.88 | 21-JUN-13:00 | 70.06 | 28-JUN-02:00 |
| July | 397.10 | 01-JUL-00:10 | 370.63 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.94 | 02-JUL-21:00 | 42.71 | 18-JUL-21:00 |
| August | 397.10 | 01-AUG-00:10 | 370.63 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.97 | 26-AUG-15:00 | 54.48 | 14-AUG-01:00 |
| September | 397.10 | 01-SEP-00:10 | 370.63 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.82 | 10-SEP-15:00 | 37.00 | 23-SEP-17:00 |
| October | 397.10 | 01-OCT-00:10 | 370.63 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.00 | 01-OCT-15:00 | 99.60 | 23-OCT-18:00 |
| November | 397.10 | 01-NOV-00:10 | 370.63 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 131.72 | 15-NOV-09:00 |
| December | 397.10 | 01-DEC-00:10 | 370.63 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 169.04 | 18-DEC-08:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
| Minimum of Months | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.00 | ||||
| Maximum of Months | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83.88 | 259.28 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: G SW APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 589.28 | 01-JAN-16:20 | 237.50 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 210.78 |
| February | 651.98 | 20-FEB-16:10 | 237.50 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.03 |
| March | 588.19 | 21-MAR-16:17 | 0.00 | 260.40 | 1765.87 | 0.00 | 0.00 | 0.00 | 0.00 | 15.65 | 0.00 |
| April | 1513.15 | 30-APR-16:10 | 950.00 | 347.20 | 2354.49 | 0.00 | 0.00 | 0.00 | 0.00 | 106.00 | 0.00 |
| May | 1882.57 | 19-MAY-17:17 | 712.50 | 351.55 | 1765.87 | 0.00 | 0.00 | 0.00 | 0.00 | 286.19 | 0.00 |
| June | 2197.41 | 15-JUN-17:05 | 1425.00 | 703.09 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 324.73 | 0.00 |
| July | 2210.68 | 26-JUL-17:23 | 712.50 | 351.55 | 1765.87 | 0.00 | 0.00 | 0.00 | 0.00 | 239.43 | 0.00 |
| August | 2303.02 | 06-AUG-17:08 | 1187.50 | 585.91 | 2943.11 | 0.00 | 0.00 | 0.00 | 0.00 | 159.49 | 0.00 |
| September | 2384.61 | 19-SEP-16:01 | 0.00 | 607.59 | 4120.36 | 0.00 | 0.00 | 0.00 | 0.00 | 51.05 | 0.00 |
| October | 2287.81 | 05-OCT-16:03 | 0.00 | 520.80 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 124.69 | 0.00 |
| November | 1644.73 | 09-NOV-15:10 | 0.00 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.08 |
| December | 556.32 | 18-DEC-23:30 | 237.50 | 21.70 | 341.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 242.83 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 556.32 | 0.00 | 21.70 | 341.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 2384.61 | 1425.00 | 703.09 | 4120.36 | 0.00 | 0.00 | 0.00 | 0.00 | 324.73 | 242.83 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: G NW APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 321.14 | 04-JAN-19:10 | 206.62 | 138.88 | 547.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96.64 |
| February | 303.99 | 20-FEB-23:00 | 237.50 | 52.08 | 417.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 130.41 |
| March | 380.72 | 16-MAR-06:03 | 2018.75 | 564.16 | 3826.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 134.53 |
| April | 1296.30 | 21-APR-16:30 | 247.00 | 173.60 | 1177.25 | 0.00 | 0.00 | 0.00 | 0.00 | 310.51 | 0.00 |
| May | 1864.79 | 19-MAY-17:30 | 413.25 | 234.36 | 1177.25 | 0.00 | 0.00 | 0.00 | 0.00 | 281.38 | 0.00 |
| June | 2287.79 | 15-JUN-17:03 | 1239.75 | 703.09 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 324.73 | 0.00 |
| July | 2220.98 | 26-JUL-17:50 | 206.62 | 117.18 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 254.50 | 0.00 |
| August | 2267.72 | 07-AUG-18:00 | 206.62 | 117.18 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 277.97 | 0.00 |
| September | 1890.46 | 20-SEP-17:00 | 123.50 | 86.80 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 74.77 | 0.00 |
| October | 1814.53 | 05-OCT-16:30 | 123.50 | 86.80 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 126.21 | 0.00 |
| November | 706.54 | 03-NOV-16:10 | 494.00 | 347.20 | 2354.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.02 |
| December | 351.06 | 03-DEC-17:17 | 494.00 | 347.20 | 2354.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 303.99 | 123.50 | 52.08 | 417.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 2287.79 | 2018.75 | 703.09 | 3826.05 | 0.00 | 0.00 | 0.00 | 0.00 | 324.73 | 134.53 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: OFFICE
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 915.85 | 12-JAN-15:00 | 0.00 | 582.92 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 1080.23 | 22-FEB-13:50 | 451.21 | 582.92 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.11 |
| March | 1030.46 | 16-MAR-14:40 | 451.21 | 582.92 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.64 |
| April | 5786.99 | 27-APR-08:62 | 1804.82 | 2331.66 | 2354.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.83 |
| May | 6167.48 | 19-MAY-07:02 | 2256.03 | 2914.58 | 2943.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.21 |
| June | 6455.85 | 22-JUN-07:02 | 2707.23 | 3497.50 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.40 |
| July | 6201.31 | 03-JUL-07:02 | 2707.23 | 3497.50 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 22.58 | 0.00 |
| August | 6436.83 | 28-AUG-07:02 | 2707.23 | 3497.50 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.62 |
| September | 6593.89 | 25-SEP-07:01 | 3158.44 | 4080.41 | 4120.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92.67 |
| October | 6630.52 | 23-OCT-07:01 | 3158.44 | 4080.41 | 4120.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 182.79 |
| November | 6122.95 | 10-NOV-09:02 | 1804.82 | 2331.66 | 2354.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 187.32 |
| December | 702.13 | 27-DEC-08:02 | 4512.06 | 5829.16 | 5886.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 190.61 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 702.13 | 0.00 | 582.92 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 6630.52 | 4512.06 | 5829.16 | 5886.23 | 0.00 | 0.00 | 0.00 | 0.00 | 22.58 | 190.61 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: G NE APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 275.46 | 04-JAN-17:50 | 123.50 | 86.80 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 102.27 |
| February | 329.60 | 21-FEB-08:15 | 555.75 | 156.25 | 2330.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.77 |
| March | 380.71 | 16-MAR-06:03 | 2018.75 | 564.16 | 3826.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 134.53 |
| April | 1153.48 | 21-APR-15:10 | 71.25 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 382.81 | 0.00 |
| May | 1514.88 | 19-MAY-17:17 | 619.87 | 351.55 | 1765.87 | 0.00 | 0.00 | 0.00 | 0.00 | 286.19 | 0.00 |
| June | 1932.19 | 15-JUN-17:00 | 123.50 | 86.80 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 346.41 | 0.00 |
| July | 1984.57 | 03-JUL-17:00 | 123.50 | 86.80 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 306.19 | 0.00 |
| August | 1983.41 | 07-AUG-18:00 | 206.62 | 117.18 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 277.97 | 0.00 |
| September | 1575.77 | 02-SEP-16:40 | 123.50 | 86.80 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 92.23 | 0.00 |
| October | 1458.82 | 05-OCT-16:03 | 741.00 | 520.80 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 124.69 | 0.00 |
| November | 518.04 | 16-NOV-07:00 | 237.50 | 60.76 | 317.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 341.00 | 14-DEC-18:40 | 206.62 | 117.18 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.61 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 275.46 | 71.25 | 60.76 | 317.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 1984.57 | 2018.75 | 564.16 | 3826.05 | 0.00 | 0.00 | 0.00 | 0.00 | 382.81 | 134.53 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: G N1 APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 375.49 | 08-JAN-20:00 | 206.62 | 138.88 | 547.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 374.44 | 22-FEB-01:30 | 237.50 | 8.68 | 241.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.19 |
| March | 421.56 | 17-MAR-21:00 | 237.50 | 95.48 | 500.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 109.35 |
| April | 932.12 | 21-APR-17:07 | 619.87 | 351.55 | 1765.87 | 0.00 | 0.00 | 0.00 | 0.00 | 184.63 | 0.00 |
| May | 1225.27 | 19-MAY-17:30 | 413.25 | 234.36 | 1177.25 | 0.00 | 0.00 | 0.00 | 0.00 | 169.72 | 0.00 |
| June | 1525.58 | 15-JUN-17:05 | 1239.75 | 703.09 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 195.87 | 0.00 |
| July | 1529.36 | 03-JUL-17:00 | 123.50 | 86.80 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 184.69 | 0.00 |
| August | 1578.65 | 07-AUG-18:00 | 206.62 | 117.18 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 167.66 | 0.00 |
| September | 1253.01 | 20-SEP-17:17 | 826.50 | 468.73 | 2354.49 | 0.00 | 0.00 | 0.00 | 0.00 | 40.50 | 0.00 |
| October | 1173.42 | 05-OCT-16:17 | 370.50 | 260.40 | 1765.87 | 0.00 | 0.00 | 0.00 | 0.00 | 76.13 | 0.00 |
| November | 580.39 | 17-NOV-06:00 | 237.50 | 56.42 | 253.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 404.22 | 09-DEC-22:50 | 237.50 | 52.08 | 417.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80.95 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 374.44 | 123.50 | 8.68 | 241.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 1578.65 | 1239.75 | 703.09 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 195.87 | 109.35 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: G N2 APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 375.23 | 08-JAN-20:00 | 206.62 | 138.88 | 547.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 374.51 | 22-FEB-01:30 | 237.50 | 8.68 | 241.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.21 |
| March | 421.22 | 17-MAR-21:00 | 237.50 | 95.48 | 500.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 109.27 |
| April | 931.69 | 21-APR-17:10 | 619.87 | 351.55 | 1765.87 | 0.00 | 0.00 | 0.00 | 0.00 | 184.63 | 0.00 |
| May | 1221.06 | 19-MAY-17:30 | 413.25 | 234.36 | 1177.25 | 0.00 | 0.00 | 0.00 | 0.00 | 169.72 | 0.00 |
| June | 1521.07 | 15-JUN-17:08 | 1239.75 | 703.09 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 195.87 | 0.00 |
| July | 1530.17 | 03-JUL-17:00 | 123.50 | 86.80 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 184.69 | 0.00 |
| August | 1572.89 | 07-AUG-18:00 | 206.62 | 117.18 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 167.66 | 0.00 |
| September | 1248.88 | 20-SEP-17:05 | 826.50 | 468.73 | 2354.49 | 0.00 | 0.00 | 0.00 | 0.00 | 42.77 | 0.00 |
| October | 1169.12 | 05-OCT-16:17 | 370.50 | 260.40 | 1765.87 | 0.00 | 0.00 | 0.00 | 0.00 | 76.13 | 0.00 |
| November | 580.26 | 17-NOV-06:00 | 237.50 | 56.42 | 253.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 404.27 | 09-DEC-22:50 | 237.50 | 52.08 | 417.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80.96 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 374.51 | 123.50 | 8.68 | 241.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 1572.89 | 1239.75 | 703.09 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 195.87 | 109.27 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: G S1 APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 711.93 | 04-JAN-14:00 | 0.00 | 17.36 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.68 |
| February | 608.31 | 22-FEB-13:50 | 0.00 | 17.36 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.27 |
| March | 563.45 | 18-MAR-06:00 | 237.50 | 60.76 | 317.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 146.45 |
| April | 1130.00 | 21-APR-15:10 | 0.00 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 230.90 | 0.00 |
| May | 1242.99 | 19-MAY-17:17 | 712.50 | 351.55 | 1765.87 | 0.00 | 0.00 | 0.00 | 0.00 | 172.62 | 0.00 |
| June | 1441.49 | 15-JUN-17:05 | 1425.00 | 703.09 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 195.87 | 0.00 |
| July | 1533.11 | 03-JUL-17:00 | 0.00 | 86.80 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 184.69 | 0.00 |
| August | 1613.27 | 07-AUG-18:00 | 237.50 | 117.18 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 167.66 | 0.00 |
| September | 1754.34 | 19-SEP-14:10 | 0.00 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 56.52 | 0.00 |
| October | 1701.63 | 01-OCT-15:10 | 237.50 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 92.62 | 0.00 |
| November | 1413.10 | 09-NOV-14:00 | 0.00 | 17.36 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.25 |
| December | 675.87 | 19-DEC-04:10 | 237.50 | 26.04 | 223.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 563.45 | 0.00 | 17.36 | 223.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 1754.34 | 1425.00 | 703.09 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 230.90 | 146.45 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: G S2 APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 734.65 | 04-JAN-14:00 | 0.00 | 17.36 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.68 |
| February | 641.01 | 22-FEB-13:50 | 0.00 | 17.36 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.27 |
| March | 577.74 | 16-MAR-15:10 | 0.00 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.29 |
| April | 1192.78 | 29-APR-16:05 | 950.00 | 347.20 | 2354.49 | 0.00 | 0.00 | 0.00 | 0.00 | 117.87 | 0.00 |
| May | 1366.69 | 21-MAY-16:20 | 475.00 | 173.60 | 1177.25 | 0.00 | 0.00 | 0.00 | 0.00 | 148.10 | 0.00 |
| June | 1533.86 | 05-JUN-17:00 | 0.00 | 86.80 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 234.09 | 0.00 |
| July | 1658.28 | 02-JUL-18:00 | 237.50 | 117.18 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 158.64 | 0.00 |
| August | 1729.67 | 07-AUG-18:00 | 237.50 | 117.18 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 167.66 | 0.00 |
| September | 1844.85 | 19-SEP-14:10 | 0.00 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 56.52 | 0.00 |
| October | 1834.12 | 01-OCT-15:10 | 237.50 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 92.62 | 0.00 |
| November | 1455.77 | 09-NOV-14:00 | 0.00 | 17.36 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.25 |
| December | 677.40 | 19-DEC-04:10 | 237.50 | 26.04 | 223.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 577.74 | 0.00 | 17.36 | 223.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 1844.85 | 950.00 | 347.20 | 2354.49 | 0.00 | 0.00 | 0.00 | 0.00 | 234.09 | 54.68 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: M SW APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 1150.00 | 12-JAN-15:00 | 0.00 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 1690.79 | 20-FEB-16:10 | 237.50 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.46 |
| March | 1676.01 | 14-MAR-16:15 | 0.00 | 173.60 | 1177.25 | 0.00 | 0.00 | 0.00 | 0.00 | 4.70 | 0.00 |
| April | 2349.42 | 21-APR-15:10 | 0.00 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 548.76 | 0.00 |
| May | 2579.04 | 19-MAY-17:05 | 950.00 | 468.73 | 2354.49 | 0.00 | 0.00 | 0.00 | 0.00 | 417.34 | 0.00 |
| June | 2806.21 | 15-JUN-17:00 | 0.00 | 86.80 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 497.07 | 0.00 |
| July | 2610.30 | 26-JUL-17:23 | 712.50 | 351.55 | 1765.87 | 0.00 | 0.00 | 0.00 | 0.00 | 343.46 | 0.00 |
| August | 2553.73 | 07-AUG-16:10 | 0.00 | 694.39 | 4708.98 | 0.00 | 0.00 | 0.00 | 0.00 | 315.10 | 0.00 |
| September | 2608.14 | 18-SEP-16:15 | 0.00 | 173.60 | 1177.25 | 0.00 | 0.00 | 0.00 | 0.00 | 125.08 | 0.00 |
| October | 2552.57 | 05-OCT-16:03 | 0.00 | 520.80 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 178.66 | 0.00 |
| November | 1984.50 | 09-NOV-15:10 | 0.00 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.81 |
| December | 907.81 | 16-DEC-15:30 | 0.00 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93.01 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 907.81 | 0.00 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 2806.21 | 950.00 | 694.39 | 4708.98 | 0.00 | 0.00 | 0.00 | 0.00 | 548.76 | 93.01 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: M NW APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 415.00 | 08-JAN-20:50 | 206.62 | 138.88 | 523.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 103.07 |
| February | 531.91 | 22-FEB-07:00 | 237.50 | 60.76 | 317.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 274.03 |
| March | 845.04 | 16-MAR-16:05 | 247.00 | 173.60 | 1177.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77.80 |
| April | 2107.68 | 21-APR-16:17 | 494.00 | 347.20 | 2354.49 | 0.00 | 0.00 | 0.00 | 0.00 | 445.18 | 0.00 |
| May | 2560.79 | 19-MAY-17:25 | 413.25 | 234.36 | 1177.25 | 0.00 | 0.00 | 0.00 | 0.00 | 403.56 | 0.00 |
| June | 2909.20 | 15-JUN-17:00 | 123.50 | 86.80 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 497.07 | 0.00 |
| July | 2627.89 | 26-JUL-17:50 | 206.62 | 117.18 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 365.05 | 0.00 |
| August | 2514.21 | 07-AUG-18:00 | 206.62 | 117.18 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 398.69 | 0.00 |
| September | 2037.12 | 18-SEP-16:50 | 123.50 | 86.80 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 142.49 | 0.00 |
| October | 2018.78 | 05-OCT-16:30 | 123.50 | 86.80 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 180.75 | 0.00 |
| November | 720.32 | 03-NOV-16:05 | 494.00 | 347.20 | 2354.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.75 |
| December | 387.54 | 09-DEC-22:40 | 237.50 | 52.08 | 417.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 171.01 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 387.54 | 123.50 | 52.08 | 317.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 2909.20 | 494.00 | 347.20 | 2354.49 | 0.00 | 0.00 | 0.00 | 0.00 | 497.07 | 274.03 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: M SE APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 952.83 | 12-JAN-15:00 | 0.00 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 1444.37 | 20-FEB-14:50 | 118.75 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.84 |
| March | 1384.04 | 16-MAR-15:10 | 0.00 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.00 |
| April | 2185.09 | 21-APR-15:10 | 0.00 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 548.76 | 0.00 |
| May | 2194.87 | 19-MAY-14:00 | 0.00 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 528.45 | 0.00 |
| June | 2326.63 | 05-JUN-17:00 | 0.00 | 86.80 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 556.91 | 0.00 |
| July | 2259.34 | 03-JUL-17:00 | 0.00 | 86.80 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 439.41 | 0.00 |
| August | 2210.71 | 27-AUG-13:00 | 118.75 | 17.36 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 302.31 | 0.00 |
| September | 2308.08 | 19-SEP-13:30 | 0.00 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 146.67 | 0.00 |
| October | 2214.94 | 01-OCT-15:10 | 237.50 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 220.16 | 0.00 |
| November | 1767.19 | 09-NOV-14:00 | 0.00 | 17.36 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.10 |
| December | 680.37 | 16-DEC-15:10 | 0.00 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 109.65 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 680.37 | 0.00 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 2326.63 | 237.50 | 86.80 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 556.91 | 109.65 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: M NE APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 399.56 | 08-JAN-20:30 | 206.62 | 138.88 | 523.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.55 |
| February | 535.57 | 22-FEB-07:00 | 237.50 | 60.76 | 317.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 275.84 |
| March | 573.02 | 22-MAR-16:10 | 247.00 | 173.60 | 1177.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.68 |
| April | 1914.65 | 21-APR-15:10 | 71.25 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 548.76 | 0.00 |
| May | 2049.67 | 19-MAY-17:20 | 619.87 | 351.55 | 1765.87 | 0.00 | 0.00 | 0.00 | 0.00 | 410.46 | 0.00 |
| June | 2408.57 | 15-JUN-17:00 | 123.50 | 86.80 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 497.07 | 0.00 |
| July | 2261.34 | 03-JUL-17:00 | 123.50 | 86.80 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 439.41 | 0.00 |
| August | 2147.63 | 07-AUG-18:00 | 206.62 | 117.18 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 398.69 | 0.00 |
| September | 1623.52 | 02-SEP-16:40 | 123.50 | 86.80 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 132.14 | 0.00 |
| October | 1532.75 | 05-OCT-16:03 | 741.00 | 520.80 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 178.66 | 0.00 |
| November | 494.68 | 25-NOV-07:10 | 2018.75 | 564.16 | 3826.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 164.34 |
| December | 387.23 | 09-DEC-22:40 | 237.50 | 52.08 | 417.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 170.88 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 387.23 | 71.25 | 52.08 | 317.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 2408.57 | 2018.75 | 564.16 | 3826.05 | 0.00 | 0.00 | 0.00 | 0.00 | 548.76 | 275.84 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: M N1 APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 485.04 | 02-JAN-02:40 | 237.50 | 8.68 | 229.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.71 |
| February | 551.97 | 22-FEB-07:00 | 237.50 | 60.76 | 317.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 171.25 |
| March | 568.93 | 18-MAR-06:00 | 237.50 | 60.76 | 317.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 212.64 |
| April | 1411.77 | 21-APR-17:07 | 619.87 | 351.55 | 1765.87 | 0.00 | 0.00 | 0.00 | 0.00 | 264.53 | 0.00 |
| May | 1571.90 | 19-MAY-17:40 | 206.62 | 117.18 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 239.24 | 0.00 |
| June | 1806.57 | 15-JUN-17:03 | 1239.75 | 703.09 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 281.05 | 0.00 |
| July | 1706.33 | 02-JUL-18:00 | 206.62 | 117.18 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 227.60 | 0.00 |
| August | 1660.36 | 07-AUG-18:00 | 206.62 | 117.18 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 240.48 | 0.00 |
| September | 1261.99 | 02-SEP-16:40 | 123.50 | 86.80 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 79.70 | 0.00 |
| October | 1212.66 | 05-OCT-16:17 | 370.50 | 260.40 | 1765.87 | 0.00 | 0.00 | 0.00 | 0.00 | 109.06 | 0.00 |
| November | 563.47 | 17-NOV-05:20 | 237.50 | 56.42 | 253.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 481.98 | 12-DEC-03:00 | 237.50 | 8.68 | 229.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 481.98 | 123.50 | 8.68 | 229.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 1806.57 | 1239.75 | 703.09 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 281.05 | 212.64 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: M N2 APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 484.44 | 02-JAN-02:40 | 237.50 | 8.68 | 229.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.64 |
| February | 552.24 | 22-FEB-07:00 | 237.50 | 60.76 | 317.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 171.33 |
| March | 568.86 | 18-MAR-06:00 | 237.50 | 60.76 | 317.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 212.61 |
| April | 1410.10 | 21-APR-17:07 | 619.87 | 351.55 | 1765.87 | 0.00 | 0.00 | 0.00 | 0.00 | 264.53 | 0.00 |
| May | 1564.82 | 19-MAY-17:40 | 206.62 | 117.18 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 239.24 | 0.00 |
| June | 1800.18 | 15-JUN-17:03 | 1239.75 | 703.09 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 281.05 | 0.00 |
| July | 1703.54 | 02-JUL-18:00 | 206.62 | 117.18 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 227.60 | 0.00 |
| August | 1653.73 | 07-AUG-18:00 | 206.62 | 117.18 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 240.48 | 0.00 |
| September | 1258.79 | 02-SEP-16:40 | 123.50 | 86.80 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 79.70 | 0.00 |
| October | 1206.80 | 05-OCT-16:17 | 370.50 | 260.40 | 1765.87 | 0.00 | 0.00 | 0.00 | 0.00 | 109.06 | 0.00 |
| November | 560.87 | 17-NOV-05:10 | 237.50 | 56.42 | 253.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 482.13 | 12-DEC-03:00 | 237.50 | 8.68 | 229.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 482.13 | 123.50 | 8.68 | 229.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 1800.18 | 1239.75 | 703.09 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 281.05 | 212.61 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: M S1 APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 1187.20 | 04-JAN-14:00 | 0.00 | 17.36 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.71 |
| February | 1412.33 | 20-FEB-14:50 | 118.75 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.36 |
| March | 1319.84 | 16-MAR-15:10 | 0.00 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.81 |
| April | 1637.37 | 21-APR-15:10 | 0.00 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 331.00 | 0.00 |
| May | 1599.66 | 14-MAY-16:10 | 950.00 | 347.20 | 2354.49 | 0.00 | 0.00 | 0.00 | 0.00 | 261.24 | 0.00 |
| June | 1712.63 | 05-JUN-17:00 | 0.00 | 86.80 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 335.91 | 0.00 |
| July | 1706.01 | 02-JUL-18:00 | 237.50 | 117.18 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 227.61 | 0.00 |
| August | 1687.94 | 07-AUG-18:00 | 237.50 | 117.18 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 240.48 | 0.00 |
| September | 1870.05 | 19-SEP-14:10 | 0.00 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 81.06 | 0.00 |
| October | 1854.34 | 01-OCT-15:10 | 237.50 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 132.80 | 0.00 |
| November | 1673.24 | 09-NOV-14:00 | 0.00 | 17.36 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.14 |
| December | 1009.77 | 16-DEC-14:40 | 118.75 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80.28 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 1009.77 | 0.00 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 1870.05 | 950.00 | 347.20 | 2354.49 | 0.00 | 0.00 | 0.00 | 0.00 | 335.91 | 80.28 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: M S2 APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 1194.22 | 04-JAN-14:00 | 0.00 | 17.36 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.71 |
| February | 1418.61 | 20-FEB-14:50 | 118.75 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.36 |
| March | 1319.98 | 16-MAR-15:10 | 0.00 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.81 |
| April | 1639.54 | 21-APR-15:10 | 0.00 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 331.00 | 0.00 |
| May | 1595.79 | 14-MAY-16:05 | 950.00 | 347.20 | 2354.49 | 0.00 | 0.00 | 0.00 | 0.00 | 261.24 | 0.00 |
| June | 1707.86 | 05-JUN-17:00 | 0.00 | 86.80 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 335.91 | 0.00 |
| July | 1703.49 | 02-JUL-18:00 | 237.50 | 117.18 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 227.61 | 0.00 |
| August | 1680.47 | 07-AUG-18:00 | 237.50 | 117.18 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 240.48 | 0.00 |
| September | 1872.37 | 19-SEP-14:10 | 0.00 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 81.06 | 0.00 |
| October | 1852.95 | 01-OCT-15:10 | 237.50 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 132.80 | 0.00 |
| November | 1677.31 | 09-NOV-14:00 | 0.00 | 17.36 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.14 |
| December | 1016.62 | 16-DEC-14:50 | 118.75 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.72 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 1016.62 | 0.00 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 1872.37 | 950.00 | 347.20 | 2354.49 | 0.00 | 0.00 | 0.00 | 0.00 | 335.91 | 78.71 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: T SW APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 1711.96 | 12-JAN-15:10 | 0.00 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.32 |
| February | 2083.79 | 20-FEB-16:10 | 237.50 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.68 |
| March | 2177.57 | 14-MAR-16:15 | 0.00 | 173.60 | 1177.25 | 0.00 | 0.00 | 0.00 | 0.00 | 5.57 | 0.00 |
| April | 3229.24 | 21-APR-15:10 | 0.00 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 722.30 | 0.00 |
| May | 3523.05 | 19-MAY-17:05 | 950.00 | 468.73 | 2354.49 | 0.00 | 0.00 | 0.00 | 0.00 | 549.91 | 0.00 |
| June | 3902.41 | 15-JUN-16:40 | 0.00 | 86.80 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 639.27 | 0.00 |
| July | 3574.85 | 06-JUL-17:00 | 0.00 | 86.80 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 519.91 | 0.00 |
| August | 3592.53 | 07-AUG-16:01 | 0.00 | 694.39 | 4708.98 | 0.00 | 0.00 | 0.00 | 0.00 | 415.54 | 0.00 |
| September | 3521.14 | 19-SEP-15:30 | 0.00 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 106.37 | 0.00 |
| October | 3433.80 | 05-OCT-16:03 | 0.00 | 520.80 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 234.91 | 0.00 |
| November | 2387.75 | 09-NOV-15:10 | 0.00 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.04 |
| December | 1360.87 | 16-DEC-15:30 | 0.00 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 123.58 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 1360.87 | 0.00 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 3902.41 | 950.00 | 694.39 | 4708.98 | 0.00 | 0.00 | 0.00 | 0.00 | 722.30 | 123.58 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: T NW APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 327.26 | 27-JAN-17:35 | 247.00 | 173.60 | 1177.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86.59 |
| February | 728.57 | 19-FEB-17:10 | 123.50 | 86.80 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.92 |
| March | 1153.12 | 14-MAR-16:40 | 123.50 | 86.80 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 4.41 | 0.00 |
| April | 2856.66 | 21-APR-15:10 | 71.25 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 722.30 | 0.00 |
| May | 3498.72 | 19-MAY-17:05 | 826.50 | 468.73 | 2354.49 | 0.00 | 0.00 | 0.00 | 0.00 | 549.91 | 0.00 |
| June | 4026.40 | 15-JUN-17:00 | 123.50 | 86.80 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 655.53 | 0.00 |
| July | 3632.73 | 06-JUL-17:00 | 123.50 | 86.80 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 519.91 | 0.00 |
| August | 3428.44 | 07-AUG-16:01 | 988.00 | 694.39 | 4708.98 | 0.00 | 0.00 | 0.00 | 0.00 | 415.54 | 0.00 |
| September | 2777.07 | 18-SEP-16:30 | 123.50 | 86.80 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 172.54 | 0.00 |
| October | 2756.14 | 05-OCT-16:17 | 370.50 | 260.40 | 1765.87 | 0.00 | 0.00 | 0.00 | 0.00 | 237.63 | 0.00 |
| November | 886.21 | 09-NOV-16:10 | 71.25 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.83 |
| December | 308.26 | 16-DEC-18:25 | 413.25 | 234.36 | 1177.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 233.69 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 308.26 | 71.25 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 4026.40 | 988.00 | 694.39 | 4708.98 | 0.00 | 0.00 | 0.00 | 0.00 | 722.30 | 233.69 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: T SE APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 1427.18 | 12-JAN-15:00 | 0.00 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 1758.35 | 20-FEB-14:50 | 118.75 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.02 |
| March | 1657.00 | 16-MAR-14:10 | 0.00 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97.49 |
| April | 3004.49 | 21-APR-14:10 | 0.00 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 709.86 | 0.00 |
| May | 3144.89 | 19-MAY-14:00 | 0.00 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 696.50 | 0.00 |
| June | 3263.95 | 21-JUN-13:00 | 0.00 | 17.36 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 803.44 | 0.00 |
| July | 3137.46 | 26-JUL-14:00 | 0.00 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 405.82 | 0.00 |
| August | 3085.65 | 27-AUG-13:00 | 118.75 | 17.36 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 398.36 | 0.00 |
| September | 3193.73 | 19-SEP-13:30 | 0.00 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 193.19 | 0.00 |
| October | 2924.40 | 03-OCT-13:40 | 0.00 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 121.52 | 0.00 |
| November | 2080.43 | 09-NOV-14:00 | 0.00 | 17.36 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.03 |
| December | 1022.49 | 16-DEC-14:40 | 118.75 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 176.83 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 1022.49 | 0.00 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 3263.95 | 118.75 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 803.44 | 176.83 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: T NE APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 255.42 | 17-JAN-16:10 | 71.25 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 181.97 |
| February | 342.09 | 22-FEB-15:10 | 59.38 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.84 |
| March | 719.42 | 22-MAR-16:05 | 247.00 | 173.60 | 1177.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.23 |
| April | 2600.84 | 21-APR-15:10 | 71.25 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 722.30 | 0.00 |
| May | 2862.98 | 19-MAY-14:00 | 59.38 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 696.50 | 0.00 |
| June | 3288.32 | 15-JUN-17:00 | 123.50 | 86.80 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 655.53 | 0.00 |
| July | 2978.84 | 02-JUL-18:00 | 206.62 | 117.18 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 497.51 | 0.00 |
| August | 2846.13 | 07-AUG-16:10 | 988.00 | 694.39 | 4708.98 | 0.00 | 0.00 | 0.00 | 0.00 | 415.54 | 0.00 |
| September | 2233.50 | 15-SEP-15:10 | 71.25 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 233.87 | 0.00 |
| October | 2055.71 | 05-OCT-16:03 | 741.00 | 520.80 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 234.91 | 0.00 |
| November | 526.02 | 09-NOV-15:10 | 59.38 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.04 |
| December | 254.58 | 09-DEC-19:00 | 206.62 | 117.18 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 101.02 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 254.58 | 59.38 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 3288.32 | 988.00 | 694.39 | 4708.98 | 0.00 | 0.00 | 0.00 | 0.00 | 722.30 | 181.97 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: T N1 APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 331.37 | 12-JAN-22:40 | 237.50 | 52.08 | 417.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.49 |
| February | 354.81 | 22-FEB-01:10 | 237.50 | 8.68 | 241.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 118.02 |
| March | 559.09 | 22-MAR-16:10 | 247.00 | 173.60 | 1177.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.99 |
| April | 1921.60 | 21-APR-15:10 | 71.25 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 435.67 | 0.00 |
| May | 2183.75 | 19-MAY-17:17 | 619.87 | 351.55 | 1765.87 | 0.00 | 0.00 | 0.00 | 0.00 | 326.20 | 0.00 |
| June | 2596.01 | 15-JUN-17:00 | 123.50 | 86.80 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 395.40 | 0.00 |
| July | 2382.45 | 02-JUL-18:00 | 206.62 | 117.18 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 300.08 | 0.00 |
| August | 2293.70 | 07-AUG-18:00 | 206.62 | 117.18 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 316.89 | 0.00 |
| September | 1795.05 | 02-SEP-16:20 | 123.50 | 86.80 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 82.73 | 0.00 |
| October | 1683.74 | 05-OCT-16:03 | 741.00 | 520.80 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 141.69 | 0.00 |
| November | 389.13 | 09-NOV-15:10 | 59.38 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.52 |
| December | 291.01 | 16-DEC-18:01 | 1446.38 | 820.27 | 4120.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 141.12 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 291.01 | 59.38 | 8.68 | 241.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 2596.01 | 1446.38 | 820.27 | 4120.36 | 0.00 | 0.00 | 0.00 | 0.00 | 435.67 | 141.12 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: T N2 APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 330.74 | 12-JAN-22:40 | 237.50 | 52.08 | 417.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.31 |
| February | 354.82 | 22-FEB-01:10 | 237.50 | 8.68 | 241.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 118.02 |
| March | 561.03 | 22-MAR-16:10 | 247.00 | 173.60 | 1177.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.99 |
| April | 1922.85 | 21-APR-15:10 | 71.25 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 435.67 | 0.00 |
| May | 2166.47 | 19-MAY-17:17 | 619.87 | 351.55 | 1765.87 | 0.00 | 0.00 | 0.00 | 0.00 | 326.20 | 0.00 |
| June | 2580.37 | 15-JUN-17:00 | 123.50 | 86.80 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 395.40 | 0.00 |
| July | 2372.92 | 02-JUL-18:00 | 206.62 | 117.18 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 300.08 | 0.00 |
| August | 2278.36 | 07-AUG-18:00 | 206.62 | 117.18 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 316.89 | 0.00 |
| September | 1786.19 | 02-SEP-16:20 | 123.50 | 86.80 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 82.73 | 0.00 |
| October | 1670.76 | 05-OCT-16:03 | 741.00 | 520.80 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 141.69 | 0.00 |
| November | 397.47 | 09-NOV-15:10 | 59.38 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.52 |
| December | 268.80 | 16-DEC-17:50 | 123.50 | 86.80 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 134.33 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 268.80 | 59.38 | 8.68 | 241.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 2580.37 | 741.00 | 520.80 | 3531.74 | 0.00 | 0.00 | 0.00 | 0.00 | 435.67 | 134.33 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: T S1 APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 1425.47 | 12-JAN-15:00 | 0.00 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 1613.20 | 20-FEB-15:00 | 118.75 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.13 |
| March | 1553.87 | 16-MAR-15:10 | 0.00 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.24 |
| April | 2298.06 | 21-APR-14:30 | 0.00 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 438.16 | 0.00 |
| May | 2376.85 | 19-MAY-14:00 | 0.00 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 420.11 | 0.00 |
| June | 2517.94 | 15-JUN-16:01 | 0.00 | 694.39 | 4708.98 | 0.00 | 0.00 | 0.00 | 0.00 | 369.90 | 0.00 |
| July | 2462.16 | 02-JUL-16:01 | 1900.00 | 694.39 | 4708.98 | 0.00 | 0.00 | 0.00 | 0.00 | 200.31 | 0.00 |
| August | 2430.61 | 07-AUG-16:04 | 0.00 | 694.39 | 4708.98 | 0.00 | 0.00 | 0.00 | 0.00 | 250.65 | 0.00 |
| September | 2673.66 | 19-SEP-14:10 | 0.00 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 106.79 | 0.00 |
| October | 2509.00 | 03-OCT-13:40 | 0.00 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 73.30 | 0.00 |
| November | 1967.94 | 09-NOV-14:20 | 0.00 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.18 |
| December | 1152.16 | 16-DEC-14:50 | 118.75 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 100.60 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 1152.16 | 0.00 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 2673.66 | 1900.00 | 694.39 | 4708.98 | 0.00 | 0.00 | 0.00 | 0.00 | 438.16 | 100.60 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: T S2 APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 1427.10 | 12-JAN-15:00 | 0.00 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 1620.12 | 20-FEB-15:00 | 118.75 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.13 |
| March | 1554.47 | 16-MAR-15:10 | 0.00 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.24 |
| April | 2304.32 | 21-APR-14:20 | 0.00 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 433.17 | 0.00 |
| May | 2383.12 | 19-MAY-14:00 | 0.00 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 420.11 | 0.00 |
| June | 2507.50 | 15-JUN-16:01 | 0.00 | 694.39 | 4708.98 | 0.00 | 0.00 | 0.00 | 0.00 | 369.90 | 0.00 |
| July | 2453.78 | 02-JUL-16:01 | 1900.00 | 694.39 | 4708.98 | 0.00 | 0.00 | 0.00 | 0.00 | 200.31 | 0.00 |
| August | 2426.10 | 26-AUG-15:10 | 237.50 | 60.76 | 470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 334.07 | 0.00 |
| September | 2677.09 | 19-SEP-14:10 | 0.00 | 30.38 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 106.79 | 0.00 |
| October | 2512.48 | 03-OCT-13:40 | 0.00 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 73.30 | 0.00 |
| November | 1974.18 | 09-NOV-14:10 | 0.00 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.15 |
| December | 1157.02 | 16-DEC-14:40 | 118.75 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 106.66 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 1157.02 | 0.00 | 17.36 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 2677.09 | 1900.00 | 694.39 | 4708.98 | 0.00 | 0.00 | 0.00 | 0.00 | 433.17 | 106.66 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: T CORRIDOR
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 0.00 | 01-JAN-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.09 |
| February | 0.00 | 01-FEB-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 120.83 |
| March | 0.00 | 01-MAR-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.49 |
| April | 0.00 | 01-APR-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.29 |
| May | 0.00 | 01-MAY-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.46 |
| June | 0.00 | 01-JUN-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.49 |
| July | 0.00 | 01-JUL-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.38 | 0.00 |
| August | 0.00 | 01-AUG-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.54 | 0.00 |
| September | 0.00 | 01-SEP-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.39 |
| October | 0.00 | 01-OCT-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.58 |
| November | 0.00 | 01-NOV-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.02 |
| December | 0.00 | 01-DEC-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.97 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
| Minimum of Months | 0.00 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.54 | 120.83 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: G CORRIDOR
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 0.00 | 01-JAN-00:10 | 397.10 | 370.63 | 56.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.76 |
| February | 0.00 | 01-FEB-00:10 | 397.10 | 370.63 | 56.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.77 |
| March | 0.00 | 01-MAR-00:10 | 397.10 | 370.63 | 56.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.91 |
| April | 0.00 | 01-APR-00:10 | 397.10 | 370.63 | 56.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.20 |
| May | 0.00 | 01-MAY-00:10 | 397.10 | 370.63 | 56.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.72 |
| June | 0.00 | 01-JUN-00:10 | 397.10 | 370.63 | 56.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.37 |
| July | 0.00 | 01-JUL-00:10 | 397.10 | 370.63 | 56.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.61 | 0.00 |
| August | 0.00 | 01-AUG-00:10 | 397.10 | 370.63 | 56.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 0.00 |
| September | 0.00 | 01-SEP-00:10 | 397.10 | 370.63 | 56.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.96 |
| October | 0.00 | 01-OCT-00:10 | 397.10 | 370.63 | 56.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.85 |
| November | 0.00 | 01-NOV-00:10 | 397.10 | 370.63 | 56.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.63 |
| December | 0.00 | 01-DEC-00:10 | 397.10 | 370.63 | 56.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.62 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 0.00 | 397.10 | 370.63 | 56.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 397.10 | 370.63 | 56.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 66.77 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: M CORRIDOR
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 0.00 | 01-JAN-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.22 |
| February | 0.00 | 01-FEB-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 102.49 |
| March | 0.00 | 01-MAR-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.87 |
| April | 0.00 | 01-APR-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.24 |
| May | 0.00 | 01-MAY-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.05 |
| June | 0.00 | 01-JUN-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.70 |
| July | 0.00 | 01-JUL-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.08 | 0.00 |
| August | 0.00 | 01-AUG-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.10 | 0.00 |
| September | 0.00 | 01-SEP-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.34 |
| October | 0.00 | 01-OCT-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.03 |
| November | 0.00 | 01-NOV-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.71 |
| December | 0.00 | 01-DEC-00:10 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.32 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
| Minimum of Months | 0.00 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 397.10 | 370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.10 | 102.49 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
| January | 0.975908E+11 | 70534.46 | 01-JAN-18:19 | 0.272780E+11 | 52342.16 | 28-JAN-05:00 |
| February | 0.884310E+11 | 70317.70 | 05-FEB-18:19 | 0.177938E+11 | 45009.84 | 02-FEB-06:00 |
| March | 0.969925E+11 | 70423.59 | 21-MAR-16:19 | 0.104569E+11 | 43659.14 | 02-MAR-05:00 |
| April | 0.103724E+12 | 79742.71 | 21-APR-17:49 | 0.107891E+10 | 14236.61 | 11-APR-01:00 |
| May | 0.119404E+12 | 80517.44 | 19-MAY-17:30 | 6283547.59 | 975.53 | 02-MAY-05:19 |
| June | 0.128547E+12 | 89705.97 | 14-JUN-17:40 | 0.00 | 0.00 | 01-JUN-00:10 |
| July | 0.135705E+12 | 89997.38 | 26-JUL-17:30 | 0.00 | 0.00 | 01-JUL-00:10 |
| August | 0.129466E+12 | 84643.87 | 05-AUG-17:10 | 0.00 | 0.00 | 01-AUG-00:10 |
| September | 0.119208E+12 | 82604.21 | 19-SEP-17:40 | 1136462.04 | 545.72 | 25-SEP-05:00 |
| October | 0.107746E+12 | 80479.05 | 05-OCT-17:10 | 0.323771E+09 | 6720.37 | 25-OCT-05:00 |
| November | 0.940916E+11 | 64497.17 | 09-NOV-17:30 | 0.109785E+11 | 44985.90 | 28-NOV-04:00 |
| December | 0.965388E+11 | 64473.36 | 16-DEC-18:40 | 0.327478E+11 | 49792.44 | 27-DEC-05:00 |
| Annual Sum or Average | 0.131745E+13 | 0.100665E+12 | ||||
| Minimum of Months | 0.884310E+11 | 64473.36 | 0.00 | 0.00 | ||
| Maximum of Months | 0.135705E+12 | 89997.38 | 0.327478E+11 | 52342.16 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| INTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [J] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
| January | 0.840929E+10 | 0.491633E+10 | 0.389380E+11 | 0.00 | 0.589491E+10 | 0.00 | 0.00 | 0.478604E+09 | 0.00 | 0.00 | 0.00 | 0.389537E+11 | 0.00 |
| February | 0.760941E+10 | 0.420582E+10 | 0.351823E+11 | 0.00 | 0.523449E+10 | 0.00 | 0.00 | 0.106213E+10 | 0.00 | 0.00 | 0.00 | 0.351368E+11 | 0.00 |
| March | 0.845392E+10 | 0.432233E+10 | 0.389781E+11 | 0.00 | 0.560716E+10 | 0.00 | 0.00 | 0.183266E+10 | 0.00 | 0.00 | 0.00 | 0.377983E+11 | 0.00 |
| April | 0.814762E+10 | 0.384674E+10 | 0.376905E+11 | 0.00 | 0.797288E+10 | 0.00 | 0.00 | 0.114309E+11 | 0.00 | 0.00 | 0.00 | 0.346353E+11 | 0.00 |
| May | 0.843904E+10 | 0.368630E+10 | 0.389647E+11 | 0.00 | 0.114972E+11 | 0.00 | 0.00 | 0.232488E+11 | 0.00 | 0.00 | 0.00 | 0.335683E+11 | 0.00 |
| June | 0.817737E+10 | 0.342272E+10 | 0.377173E+11 | 0.00 | 0.143841E+11 | 0.00 | 0.00 | 0.341935E+11 | 0.00 | 0.00 | 0.00 | 0.306526E+11 | 0.00 |
| July | 0.840929E+10 | 0.360035E+10 | 0.389380E+11 | 0.00 | 0.155721E+11 | 0.00 | 0.00 | 0.385961E+11 | 0.00 | 0.00 | 0.00 | 0.305892E+11 | 0.00 |
| August | 0.845392E+10 | 0.384674E+10 | 0.389781E+11 | 0.00 | 0.141745E+11 | 0.00 | 0.00 | 0.334162E+11 | 0.00 | 0.00 | 0.00 | 0.305969E+11 | 0.00 |
| September | 0.814762E+10 | 0.403392E+10 | 0.376905E+11 | 0.00 | 0.121446E+11 | 0.00 | 0.00 | 0.265110E+11 | 0.00 | 0.00 | 0.00 | 0.306800E+11 | 0.00 |
| October | 0.842417E+10 | 0.451906E+10 | 0.389514E+11 | 0.00 | 0.862859E+10 | 0.00 | 0.00 | 0.135953E+11 | 0.00 | 0.00 | 0.00 | 0.336271E+11 | 0.00 |
| November | 0.814762E+10 | 0.466613E+10 | 0.376905E+11 | 0.00 | 0.580706E+10 | 0.00 | 0.00 | 0.300709E+10 | 0.00 | 0.00 | 0.00 | 0.347731E+11 | 0.00 |
| December | 0.840929E+10 | 0.498891E+10 | 0.389380E+11 | 0.00 | 0.605176E+10 | 0.00 | 0.00 | 0.251048E+09 | 0.00 | 0.00 | 0.00 | 0.378998E+11 | 0.00 |
| Annual Sum or Average | 0.992286E+11 | 0.500553E+11 | 0.458657E+12 | 0.00 | 0.112969E+12 | 0.00 | 0.00 | 0.187623E+12 | 0.00 | 0.00 | 0.00 | 0.408911E+12 | 0.00 |
| Minimum of Months | 0.760941E+10 | 0.342272E+10 | 0.351823E+11 | 0.00 | 0.523449E+10 | 0.00 | 0.00 | 0.251048E+09 | 0.00 | 0.00 | 0.00 | 0.305892E+11 | 0.00 |
| Maximum of Months | 0.845392E+10 | 0.498891E+10 | 0.389781E+11 | 0.00 | 0.155721E+11 | 0.00 | 0.00 | 0.385961E+11 | 0.00 | 0.00 | 0.00 | 0.389537E+11 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| INTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
| January | 0.00 | 0.00 | 0.272780E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.177938E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.104569E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.107891E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 6283547.59 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 1136462.04 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.323771E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.109785E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.327478E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.100665E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.327478E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| INTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
| January | 5904.43 | 01-JAN-19:10 | 3183.33 | 01-JAN-00:10 | 22709.69 | 03-JAN-17:10 | 0.00 | 3903.25 | 28-JAN-05:00 | 0.00 | 0.00 | 01-JAN-00:10 |
| February | 5904.43 | 01-FEB-19:10 | 3183.33 | 01-FEB-00:10 | 22709.69 | 01-FEB-17:10 | 0.00 | 3714.13 | 20-FEB-15:09 | 0.00 | 0.00 | 01-FEB-00:10 |
| March | 5904.43 | 01-MAR-19:10 | 3183.33 | 01-MAR-00:10 | 22709.69 | 01-MAR-17:10 | 0.00 | 4082.74 | 16-MAR-15:09 | 0.00 | 0.00 | 01-MAR-00:10 |
| April | 5904.43 | 01-APR-18:10 | 3183.33 | 01-APR-00:10 | 22709.69 | 03-APR-16:10 | 0.00 | 7626.35 | 21-APR-15:09 | 0.00 | 0.00 | 01-APR-00:10 |
| May | 5904.43 | 01-MAY-18:10 | 3183.33 | 01-MAY-00:10 | 22709.69 | 01-MAY-16:10 | 0.00 | 8272.51 | 19-MAY-17:10 | 0.00 | 0.00 | 01-MAY-00:10 |
| June | 5904.43 | 01-JUN-18:10 | 3183.33 | 01-JUN-00:10 | 22709.69 | 01-JUN-16:10 | 0.00 | 9845.83 | 15-JUN-16:00 | 0.00 | 0.00 | 01-JUN-00:10 |
| July | 5904.43 | 01-JUL-18:10 | 3183.33 | 01-JUL-00:10 | 22709.69 | 03-JUL-16:10 | 0.00 | 8995.66 | 26-JUL-17:30 | 0.00 | 0.00 | 01-JUL-00:10 |
| August | 5904.43 | 01-AUG-18:10 | 3183.33 | 01-AUG-00:10 | 22709.69 | 01-AUG-16:10 | 0.00 | 8866.78 | 07-AUG-16:10 | 0.00 | 0.00 | 01-AUG-00:10 |
| September | 5904.43 | 01-SEP-18:10 | 3183.33 | 01-SEP-00:10 | 22709.69 | 01-SEP-16:10 | 0.00 | 7895.63 | 19-SEP-16:10 | 0.00 | 0.00 | 01-SEP-00:10 |
| October | 5904.43 | 01-OCT-18:10 | 3183.33 | 01-OCT-00:10 | 22709.69 | 02-OCT-16:10 | 0.00 | 7544.44 | 01-OCT-15:09 | 0.00 | 0.00 | 01-OCT-00:10 |
| November | 5904.43 | 01-NOV-18:10 | 3183.33 | 01-NOV-00:10 | 22709.69 | 01-NOV-16:10 | 0.00 | 4657.04 | 09-NOV-15:09 | 0.00 | 0.00 | 01-NOV-00:10 |
| December | 5904.43 | 01-DEC-19:10 | 3183.33 | 01-DEC-00:10 | 22709.69 | 01-DEC-17:10 | 0.00 | 3797.44 | 27-DEC-05:00 | 0.00 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 5904.43 | 3183.33 | 22709.69 | 0.00 | 3714.13 | 0.00 | 0.00 | |||||
| Maximum of Months | 5904.43 | 3183.33 | 22709.69 | 0.00 | 9845.83 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| COOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY {Maximum} [W] | HEATRECOVERY:ELECTRICITY {TIMESTAMP} | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
| January | 4391.56 | 12-JAN-14:00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 37509.09 | 01-JAN-07:49 | 0.00 |
| February | 6277.22 | 20-FEB-15:09 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 37454.85 | 05-FEB-08:20 | 0.00 |
| March | 7818.12 | 16-MAR-15:09 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 35989.80 | 01-MAR-07:40 | 0.00 |
| April | 20806.96 | 21-APR-15:09 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 34494.88 | 12-APR-05:40 | 0.00 |
| May | 23103.00 | 19-MAY-16:00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 27482.31 | 04-MAY-07:00 | 0.00 |
| June | 28167.44 | 05-JUN-16:00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 27858.27 | 26-JUN-07:10 | 0.00 |
| July | 26454.61 | 26-JUL-14:09 | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 27898.99 | 02-JUL-06:19 | 0.00 |
| August | 26451.00 | 07-AUG-15:00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 27869.18 | 11-AUG-06:30 | 0.00 |
| September | 22363.09 | 20-SEP-15:09 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 29320.37 | 21-SEP-06:49 | 0.00 |
| October | 21619.06 | 03-OCT-13:00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 31396.78 | 07-OCT-07:49 | 0.00 |
| November | 10049.16 | 09-NOV-15:09 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 32798.84 | 23-NOV-07:49 | 0.00 |
| December | 2913.16 | 16-DEC-15:09 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 32991.67 | 13-DEC-07:40 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
| Minimum of Months | 2913.16 | 0.00 | 0.00 | 0.00 | 27482.31 | 0.00 | |||
| Maximum of Months | 28167.44 | 0.00 | 0.00 | 0.00 | 37509.09 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
| January | 70534.46 | 01-JAN-18:19 | 5231.74 | 22609.62 | 3183.33 | 0.00 | 2006.68 | 0.00 | 0.00 | 900.25 | 0.00 |
| February | 70317.70 | 05-FEB-18:19 | 5231.74 | 22609.62 | 3183.33 | 0.00 | 2039.38 | 0.00 | 0.00 | 995.35 | 0.00 |
| March | 70423.59 | 21-MAR-16:19 | 4289.87 | 22709.69 | 0.00 | 0.00 | 3998.84 | 0.00 | 0.00 | 7226.30 | 0.00 |
| April | 79742.71 | 21-APR-17:49 | 5231.74 | 22609.62 | 0.00 | 0.00 | 7028.50 | 0.00 | 0.00 | 17754.66 | 0.00 |
| May | 80517.44 | 19-MAY-17:30 | 5231.74 | 22609.62 | 0.00 | 0.00 | 8200.85 | 0.00 | 0.00 | 22427.41 | 0.00 |
| June | 89705.97 | 14-JUN-17:40 | 5231.74 | 22609.62 | 0.00 | 0.00 | 9445.81 | 0.00 | 0.00 | 26163.87 | 0.00 |
| July | 89997.38 | 26-JUL-17:30 | 5231.74 | 22609.62 | 0.00 | 0.00 | 8995.66 | 0.00 | 0.00 | 26117.40 | 0.00 |
| August | 84643.87 | 05-AUG-17:10 | 5231.74 | 22609.62 | 0.00 | 0.00 | 8006.12 | 0.00 | 0.00 | 22435.26 | 0.00 |
| September | 82604.21 | 19-SEP-17:40 | 5231.74 | 22609.62 | 0.00 | 0.00 | 7417.78 | 0.00 | 0.00 | 19588.37 | 0.00 |
| October | 80479.05 | 05-OCT-17:10 | 5231.74 | 22609.62 | 0.00 | 0.00 | 7019.82 | 0.00 | 0.00 | 17995.08 | 0.00 |
| November | 64497.17 | 09-NOV-17:30 | 4289.87 | 22709.69 | 3183.33 | 0.00 | 3742.77 | 0.00 | 0.00 | 6473.34 | 0.00 |
| December | 64473.36 | 16-DEC-18:40 | 5231.74 | 22609.62 | 3183.33 | 0.00 | 1815.49 | 0.00 | 0.00 | 163.21 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
| Minimum of Months | 64473.36 | 4289.87 | 22609.62 | 0.00 | 0.00 | 1815.49 | 0.00 | 0.00 | 163.21 | 0.00 | |
| Maximum of Months | 89997.38 | 5231.74 | 22709.69 | 3183.33 | 0.00 | 9445.81 | 0.00 | 0.00 | 26163.87 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| INTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | |
| January | 0.00 | 0.00 | 52342.16 | 28-JAN-05:00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 45009.84 | 02-FEB-06:00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 43659.14 | 02-MAR-05:00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 14236.61 | 11-APR-01:00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 975.53 | 02-MAY-05:19 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 545.72 | 25-SEP-05:00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 6720.37 | 25-OCT-05:00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 44985.90 | 28-NOV-04:00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 49792.44 | 27-DEC-05:00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 52342.16 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: G SW APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: G NW APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: OFFICE
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: G NE APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: G N1 APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: G N2 APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: G S1 APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: G S2 APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: M SW APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: M NW APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: M SE APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: M NE APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: M N1 APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: M N2 APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: M S1 APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: M S2 APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: T SW APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: T NW APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: T SE APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: T NE APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: T N1 APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: T N2 APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: T S1 APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: T S2 APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: T CORRIDOR
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: G CORRIDOR
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: M CORRIDOR
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: G SW APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 533.00 | 21.69 | 51.00 | 21.64 | 51.00 | 21.59 |
| February | 473.00 | 21.78 | 64.00 | 21.70 | 64.00 | 21.64 |
| March | 506.00 | 21.85 | 65.50 | 21.76 | 65.50 | 21.69 |
| April | 455.50 | 23.39 | 3.33 | 23.37 | 3.33 | 23.35 |
| May | 243.17 | 23.88 | 75.50 | 23.91 | 0.00 | 23.91 |
| June | 55.83 | 24.00 | 201.50 | 24.00 | 4.17 | 24.00 |
| July | 80.33 | 24.00 | 530.50 | 24.00 | 80.33 | 24.00 |
| August | 20.83 | 24.00 | 449.83 | 24.00 | 20.83 | 24.00 |
| September | 17.50 | 24.00 | 386.17 | 24.00 | 17.50 | 24.00 |
| October | 46.00 | 23.87 | 210.17 | 23.98 | 1.17 | 23.98 |
| November | 431.00 | 23.08 | 0.00 | 23.08 | 0.00 | 23.08 |
| December | 533.00 | 21.71 | 46.67 | 21.66 | 46.67 | 21.62 |
| Annual Sum or Average | 3395.17 | 22.44 | 2084.17 | 22.91 | 354.50 | 22.86 |
| Minimum of Months | 17.50 | 21.69 | 0.00 | 21.64 | 0.00 | 21.59 |
| Maximum of Months | 533.00 | 24.00 | 530.50 | 24.00 | 80.33 | 24.00 |
Report: ComfortReportSimple55Monthly
For: G NW APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 744.00 | 21.15 | 373.00 | 21.14 | 373.00 | 21.13 |
| February | 672.00 | 21.27 | 404.50 | 21.21 | 404.50 | 21.18 |
| March | 744.00 | 21.47 | 311.50 | 21.36 | 311.50 | 21.30 |
| April | 686.83 | 23.23 | 10.83 | 23.20 | 10.83 | 23.17 |
| May | 351.00 | 23.86 | 109.67 | 23.90 | 0.00 | 23.90 |
| June | 64.83 | 24.00 | 306.33 | 24.00 | 3.33 | 24.00 |
| July | 103.17 | 24.00 | 741.67 | 24.00 | 103.17 | 24.00 |
| August | 32.83 | 24.00 | 650.67 | 24.00 | 32.83 | 24.00 |
| September | 45.17 | 24.00 | 514.50 | 24.00 | 37.33 | 24.00 |
| October | 250.50 | 23.80 | 219.00 | 23.89 | 11.17 | 23.89 |
| November | 706.50 | 22.30 | 29.83 | 22.25 | 29.83 | 22.20 |
| December | 744.00 | 21.17 | 443.17 | 21.14 | 443.17 | 21.13 |
| Annual Sum or Average | 5144.83 | 22.10 | 4114.67 | 22.45 | 1760.67 | 22.29 |
| Minimum of Months | 32.83 | 21.15 | 10.83 | 21.14 | 0.00 | 21.13 |
| Maximum of Months | 744.00 | 24.00 | 741.67 | 24.00 | 443.17 | 24.00 |
Report: ComfortReportSimple55Monthly
For: OFFICE
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 140.00 | 23.03 | 7.33 | 22.91 | 7.33 | 22.80 |
| February | 133.00 | 23.30 | 4.33 | 23.22 | 4.33 | 23.14 |
| March | 161.00 | 23.45 | 5.67 | 23.36 | 5.67 | 23.28 |
| April | 36.83 | 23.95 | 10.33 | 24.11 | 0.00 | 24.11 |
| May | 0.00 | 0.00 | 98.67 | 24.31 | 0.00 | 24.31 |
| June | 0.17 | 25.80 | 152.00 | 24.24 | 0.17 | 24.24 |
| July | 14.33 | 25.33 | 140.00 | 24.34 | 14.33 | 24.42 |
| August | 8.50 | 25.57 | 161.00 | 24.30 | 8.50 | 24.37 |
| September | 4.50 | 25.54 | 140.00 | 24.28 | 4.50 | 24.32 |
| October | 0.67 | 25.61 | 140.17 | 24.24 | 0.67 | 24.25 |
| November | 42.17 | 23.46 | 30.33 | 23.80 | 0.00 | 23.80 |
| December | 140.00 | 23.15 | 9.33 | 23.00 | 9.33 | 22.87 |
| Annual Sum or Average | 681.17 | 23.38 | 899.17 | 23.82 | 54.83 | 23.80 |
| Minimum of Months | 0.00 | 0.00 | 4.33 | 22.91 | 0.00 | 22.80 |
| Maximum of Months | 161.00 | 25.80 | 161.00 | 24.34 | 14.33 | 24.42 |
Report: ComfortReportSimple55Monthly
For: G NE APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 744.00 | 21.13 | 386.33 | 21.12 | 386.33 | 21.12 |
| February | 672.00 | 21.27 | 400.50 | 21.21 | 400.50 | 21.18 |
| March | 744.00 | 21.46 | 293.67 | 21.36 | 293.67 | 21.30 |
| April | 681.00 | 23.30 | 7.67 | 23.27 | 7.67 | 23.25 |
| May | 319.33 | 23.89 | 113.67 | 23.92 | 0.00 | 23.92 |
| June | 55.83 | 24.00 | 304.67 | 24.00 | 5.17 | 24.00 |
| July | 102.83 | 24.00 | 738.50 | 24.00 | 102.83 | 24.00 |
| August | 33.50 | 24.00 | 643.50 | 24.00 | 33.50 | 24.00 |
| September | 43.17 | 23.99 | 508.00 | 24.00 | 36.33 | 24.00 |
| October | 278.83 | 23.81 | 206.00 | 23.89 | 9.00 | 23.89 |
| November | 715.33 | 22.30 | 27.67 | 22.25 | 27.67 | 22.21 |
| December | 744.00 | 21.15 | 450.00 | 21.13 | 450.00 | 21.13 |
| Annual Sum or Average | 5133.83 | 22.10 | 4080.17 | 22.45 | 1752.67 | 22.28 |
| Minimum of Months | 33.50 | 21.13 | 7.67 | 21.12 | 0.00 | 21.12 |
| Maximum of Months | 744.00 | 24.00 | 738.50 | 24.00 | 450.00 | 24.00 |
Report: ComfortReportSimple55Monthly
For: G N1 APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 744.00 | 21.17 | 263.50 | 21.16 | 263.50 | 21.15 |
| February | 672.00 | 21.33 | 303.17 | 21.27 | 303.17 | 21.23 |
| March | 744.00 | 21.56 | 149.00 | 21.49 | 149.00 | 21.43 |
| April | 684.50 | 23.46 | 8.33 | 23.43 | 8.33 | 23.40 |
| May | 392.17 | 23.96 | 90.33 | 23.96 | 0.00 | 23.96 |
| June | 85.50 | 24.00 | 211.50 | 24.00 | 0.00 | 24.00 |
| July | 101.33 | 24.00 | 722.83 | 24.00 | 101.33 | 24.00 |
| August | 21.33 | 24.00 | 595.83 | 24.00 | 21.33 | 24.00 |
| September | 51.67 | 24.00 | 478.17 | 24.00 | 42.67 | 24.00 |
| October | 243.83 | 23.92 | 210.33 | 23.96 | 1.83 | 23.96 |
| November | 695.00 | 22.52 | 0.00 | 22.52 | 0.00 | 22.52 |
| December | 744.00 | 21.21 | 316.33 | 21.18 | 316.33 | 21.16 |
| Annual Sum or Average | 5179.33 | 22.22 | 3349.33 | 22.57 | 1207.50 | 22.43 |
| Minimum of Months | 21.33 | 21.17 | 0.00 | 21.16 | 0.00 | 21.15 |
| Maximum of Months | 744.00 | 24.00 | 722.83 | 24.00 | 316.33 | 24.00 |
Report: ComfortReportSimple55Monthly
For: G N2 APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 744.00 | 21.17 | 263.50 | 21.15 | 263.50 | 21.14 |
| February | 672.00 | 21.33 | 300.17 | 21.27 | 300.17 | 21.23 |
| March | 744.00 | 21.56 | 149.50 | 21.49 | 149.50 | 21.44 |
| April | 683.50 | 23.46 | 8.33 | 23.43 | 8.33 | 23.40 |
| May | 390.17 | 23.96 | 92.00 | 23.97 | 0.00 | 23.97 |
| June | 84.67 | 24.00 | 211.50 | 24.00 | 0.00 | 24.00 |
| July | 101.17 | 24.00 | 723.00 | 24.00 | 101.17 | 24.00 |
| August | 21.67 | 24.00 | 597.17 | 24.00 | 21.67 | 24.00 |
| September | 51.50 | 24.00 | 478.00 | 24.00 | 42.67 | 24.00 |
| October | 244.50 | 23.92 | 209.17 | 23.96 | 1.83 | 23.96 |
| November | 695.50 | 22.51 | 0.00 | 22.51 | 0.00 | 22.51 |
| December | 744.00 | 21.21 | 316.33 | 21.18 | 316.33 | 21.16 |
| Annual Sum or Average | 5176.67 | 22.22 | 3348.67 | 22.57 | 1205.17 | 22.44 |
| Minimum of Months | 21.67 | 21.17 | 0.00 | 21.15 | 0.00 | 21.14 |
| Maximum of Months | 744.00 | 24.00 | 723.00 | 24.00 | 316.33 | 24.00 |
Report: ComfortReportSimple55Monthly
For: G S1 APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 527.83 | 22.18 | 16.00 | 22.15 | 16.00 | 22.12 |
| February | 473.00 | 22.27 | 5.33 | 22.25 | 5.33 | 22.24 |
| March | 506.00 | 22.31 | 16.83 | 22.27 | 16.83 | 22.23 |
| April | 448.50 | 23.66 | 0.00 | 23.66 | 0.00 | 23.66 |
| May | 249.00 | 23.97 | 72.50 | 23.97 | 0.00 | 23.97 |
| June | 66.67 | 24.00 | 142.00 | 24.00 | 0.00 | 24.00 |
| July | 78.67 | 24.00 | 517.33 | 24.00 | 78.67 | 24.00 |
| August | 11.00 | 24.00 | 406.33 | 24.00 | 11.00 | 24.00 |
| September | 18.17 | 24.00 | 366.33 | 24.00 | 18.17 | 24.00 |
| October | 23.83 | 23.97 | 212.50 | 24.00 | 0.00 | 24.00 |
| November | 394.17 | 23.42 | 0.00 | 23.42 | 0.00 | 23.42 |
| December | 533.00 | 22.24 | 1.50 | 22.23 | 1.50 | 22.23 |
| Annual Sum or Average | 3329.83 | 22.81 | 1756.67 | 23.20 | 147.50 | 23.20 |
| Minimum of Months | 11.00 | 22.18 | 0.00 | 22.15 | 0.00 | 22.12 |
| Maximum of Months | 533.00 | 24.00 | 517.33 | 24.00 | 78.67 | 24.00 |
Report: ComfortReportSimple55Monthly
For: G S2 APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 528.50 | 22.20 | 15.50 | 22.17 | 15.50 | 22.14 |
| February | 473.00 | 22.31 | 5.33 | 22.30 | 5.33 | 22.28 |
| March | 506.00 | 22.37 | 13.00 | 22.34 | 13.00 | 22.31 |
| April | 441.50 | 23.71 | 0.00 | 23.71 | 0.00 | 23.71 |
| May | 213.83 | 23.98 | 90.00 | 23.98 | 0.00 | 23.98 |
| June | 40.67 | 24.00 | 195.83 | 24.00 | 0.00 | 24.00 |
| July | 66.50 | 24.00 | 526.50 | 24.00 | 66.50 | 24.00 |
| August | 7.33 | 24.00 | 438.33 | 24.00 | 7.33 | 24.00 |
| September | 8.00 | 24.00 | 377.00 | 24.00 | 8.00 | 24.00 |
| October | 12.00 | 23.97 | 228.00 | 24.00 | 0.00 | 24.00 |
| November | 381.33 | 23.44 | 0.00 | 23.44 | 0.00 | 23.44 |
| December | 533.00 | 22.29 | 2.33 | 22.28 | 2.33 | 22.27 |
| Annual Sum or Average | 3211.67 | 22.81 | 1891.83 | 23.23 | 118.00 | 23.23 |
| Minimum of Months | 7.33 | 22.20 | 0.00 | 22.17 | 0.00 | 22.14 |
| Maximum of Months | 533.00 | 24.00 | 526.50 | 24.00 | 66.50 | 24.00 |
Report: ComfortReportSimple55Monthly
For: M SW APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 525.00 | 22.08 | 20.50 | 22.04 | 20.50 | 22.01 |
| February | 470.50 | 22.52 | 11.67 | 22.48 | 11.67 | 22.45 |
| March | 501.17 | 22.97 | 7.00 | 22.94 | 7.00 | 22.92 |
| April | 358.00 | 23.72 | 3.67 | 23.72 | 0.00 | 23.72 |
| May | 169.50 | 23.96 | 105.50 | 23.98 | 0.00 | 23.98 |
| June | 38.17 | 24.00 | 225.50 | 24.00 | 1.83 | 24.00 |
| July | 83.50 | 24.00 | 526.17 | 24.00 | 83.50 | 24.00 |
| August | 34.17 | 24.00 | 396.00 | 24.00 | 34.17 | 24.00 |
| September | 53.33 | 23.98 | 362.33 | 24.00 | 42.67 | 24.00 |
| October | 129.00 | 23.73 | 177.83 | 23.88 | 10.17 | 23.89 |
| November | 453.17 | 22.90 | 3.50 | 22.89 | 3.50 | 22.88 |
| December | 533.00 | 21.93 | 28.83 | 21.89 | 28.83 | 21.85 |
| Annual Sum or Average | 3348.50 | 22.82 | 1868.50 | 23.20 | 243.83 | 23.20 |
| Minimum of Months | 34.17 | 21.93 | 3.50 | 21.89 | 0.00 | 21.85 |
| Maximum of Months | 533.00 | 24.00 | 526.17 | 24.00 | 83.50 | 24.00 |
Report: ComfortReportSimple55Monthly
For: M NW APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 744.00 | 21.26 | 193.83 | 21.23 | 193.83 | 21.20 |
| February | 672.00 | 21.72 | 136.50 | 21.62 | 136.50 | 21.54 |
| March | 744.00 | 22.44 | 44.17 | 22.37 | 44.17 | 22.30 |
| April | 551.33 | 23.64 | 0.00 | 23.64 | 0.00 | 23.64 |
| May | 236.67 | 23.95 | 159.00 | 23.97 | 0.00 | 23.97 |
| June | 41.00 | 24.00 | 341.67 | 24.00 | 1.50 | 24.00 |
| July | 107.83 | 24.00 | 737.67 | 24.00 | 107.83 | 24.00 |
| August | 46.17 | 24.00 | 596.83 | 24.00 | 46.17 | 24.00 |
| September | 91.67 | 23.96 | 466.00 | 23.99 | 64.83 | 23.99 |
| October | 367.83 | 23.67 | 192.00 | 23.78 | 21.17 | 23.79 |
| November | 713.17 | 22.13 | 53.00 | 22.06 | 53.00 | 22.00 |
| December | 744.00 | 21.21 | 366.67 | 21.17 | 366.67 | 21.15 |
| Annual Sum or Average | 5059.67 | 22.32 | 3287.33 | 22.71 | 1035.67 | 22.61 |
| Minimum of Months | 41.00 | 21.21 | 0.00 | 21.17 | 0.00 | 21.15 |
| Maximum of Months | 744.00 | 24.00 | 737.67 | 24.00 | 366.67 | 24.00 |
Report: ComfortReportSimple55Monthly
For: M SE APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 525.00 | 22.05 | 23.00 | 22.01 | 23.00 | 21.98 |
| February | 469.33 | 22.55 | 13.17 | 22.51 | 13.17 | 22.48 |
| March | 506.00 | 22.97 | 7.33 | 22.95 | 7.33 | 22.92 |
| April | 362.50 | 23.73 | 10.00 | 23.74 | 0.00 | 23.74 |
| May | 173.83 | 23.96 | 101.33 | 23.98 | 0.00 | 23.98 |
| June | 41.50 | 24.00 | 210.50 | 24.00 | 3.00 | 24.00 |
| July | 83.33 | 24.00 | 522.17 | 24.00 | 83.33 | 24.00 |
| August | 37.50 | 24.00 | 387.50 | 24.00 | 37.50 | 24.00 |
| September | 49.83 | 23.97 | 356.17 | 24.00 | 39.33 | 24.00 |
| October | 151.83 | 23.72 | 175.17 | 23.87 | 10.17 | 23.87 |
| November | 459.33 | 22.91 | 4.50 | 22.89 | 4.50 | 22.87 |
| December | 533.00 | 21.93 | 35.17 | 21.88 | 35.17 | 21.83 |
| Annual Sum or Average | 3393.00 | 22.83 | 1846.00 | 23.20 | 256.50 | 23.19 |
| Minimum of Months | 37.50 | 21.93 | 4.50 | 21.88 | 0.00 | 21.83 |
| Maximum of Months | 533.00 | 24.00 | 522.17 | 24.00 | 83.33 | 24.00 |
Report: ComfortReportSimple55Monthly
For: M NE APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 744.00 | 21.21 | 206.33 | 21.19 | 206.33 | 21.17 |
| February | 672.00 | 21.75 | 128.17 | 21.65 | 128.17 | 21.57 |
| March | 744.00 | 22.51 | 40.00 | 22.44 | 40.00 | 22.37 |
| April | 553.67 | 23.69 | 1.33 | 23.69 | 0.00 | 23.69 |
| May | 221.33 | 23.96 | 155.50 | 23.98 | 0.00 | 23.98 |
| June | 37.67 | 24.00 | 333.17 | 24.00 | 2.67 | 24.00 |
| July | 106.33 | 24.00 | 731.17 | 24.00 | 106.33 | 24.00 |
| August | 46.17 | 24.00 | 599.00 | 24.00 | 46.17 | 24.00 |
| September | 93.67 | 23.96 | 469.50 | 23.99 | 64.83 | 23.99 |
| October | 368.67 | 23.68 | 167.50 | 23.78 | 21.17 | 23.79 |
| November | 716.83 | 22.12 | 51.83 | 22.05 | 51.83 | 21.99 |
| December | 744.00 | 21.19 | 387.50 | 21.16 | 387.50 | 21.15 |
| Annual Sum or Average | 5048.33 | 22.33 | 3271.00 | 22.70 | 1055.00 | 22.60 |
| Minimum of Months | 37.67 | 21.19 | 1.33 | 21.16 | 0.00 | 21.15 |
| Maximum of Months | 744.00 | 24.00 | 731.17 | 24.00 | 387.50 | 24.00 |
Report: ComfortReportSimple55Monthly
For: M N1 APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 744.00 | 21.35 | 134.83 | 21.31 | 134.83 | 21.29 |
| February | 672.00 | 21.97 | 78.83 | 21.88 | 78.83 | 21.81 |
| March | 741.67 | 22.78 | 17.00 | 22.74 | 17.00 | 22.70 |
| April | 582.67 | 23.80 | 0.00 | 23.80 | 0.00 | 23.80 |
| May | 291.17 | 23.99 | 119.67 | 23.99 | 0.00 | 23.99 |
| June | 80.50 | 24.00 | 216.00 | 24.00 | 0.00 | 24.00 |
| July | 104.33 | 24.00 | 715.83 | 24.00 | 104.33 | 24.00 |
| August | 34.00 | 24.00 | 534.83 | 24.00 | 34.00 | 24.00 |
| September | 86.83 | 24.00 | 424.17 | 24.00 | 56.33 | 24.00 |
| October | 321.83 | 23.88 | 184.33 | 23.92 | 16.67 | 23.93 |
| November | 711.00 | 22.45 | 1.33 | 22.45 | 1.33 | 22.45 |
| December | 744.00 | 21.29 | 206.33 | 21.25 | 206.33 | 21.22 |
| Annual Sum or Average | 5114.00 | 22.53 | 2633.17 | 22.87 | 649.67 | 22.80 |
| Minimum of Months | 34.00 | 21.29 | 0.00 | 21.25 | 0.00 | 21.22 |
| Maximum of Months | 744.00 | 24.00 | 715.83 | 24.00 | 206.33 | 24.00 |
Report: ComfortReportSimple55Monthly
For: M N2 APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 744.00 | 21.35 | 136.17 | 21.31 | 136.17 | 21.28 |
| February | 672.00 | 21.97 | 78.67 | 21.88 | 78.67 | 21.81 |
| March | 741.50 | 22.78 | 16.83 | 22.75 | 16.83 | 22.71 |
| April | 581.83 | 23.80 | 0.00 | 23.80 | 0.00 | 23.80 |
| May | 290.33 | 23.99 | 119.17 | 23.99 | 0.00 | 23.99 |
| June | 79.83 | 24.00 | 215.50 | 24.00 | 0.00 | 24.00 |
| July | 104.50 | 24.00 | 715.67 | 24.00 | 104.50 | 24.00 |
| August | 34.33 | 24.00 | 535.17 | 24.00 | 34.33 | 24.00 |
| September | 87.00 | 24.00 | 423.17 | 24.00 | 56.33 | 24.00 |
| October | 322.00 | 23.88 | 183.67 | 23.92 | 16.50 | 23.93 |
| November | 712.33 | 22.45 | 1.33 | 22.45 | 1.33 | 22.45 |
| December | 744.00 | 21.29 | 209.33 | 21.25 | 209.33 | 21.22 |
| Annual Sum or Average | 5113.67 | 22.53 | 2634.67 | 22.87 | 654.00 | 22.80 |
| Minimum of Months | 34.33 | 21.29 | 0.00 | 21.25 | 0.00 | 21.22 |
| Maximum of Months | 744.00 | 24.00 | 715.67 | 24.00 | 209.33 | 24.00 |
Report: ComfortReportSimple55Monthly
For: M S1 APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 518.17 | 22.74 | 0.00 | 22.74 | 0.00 | 22.74 |
| February | 470.67 | 23.13 | 0.00 | 23.13 | 0.00 | 23.13 |
| March | 492.83 | 23.40 | 0.00 | 23.40 | 0.00 | 23.40 |
| April | 388.00 | 23.88 | 0.00 | 23.88 | 0.00 | 23.88 |
| May | 198.67 | 23.99 | 84.67 | 23.99 | 0.00 | 23.99 |
| June | 65.17 | 24.00 | 146.67 | 24.00 | 0.00 | 24.00 |
| July | 81.17 | 24.00 | 511.67 | 24.00 | 81.17 | 24.00 |
| August | 21.83 | 24.00 | 363.83 | 24.00 | 21.83 | 24.00 |
| September | 41.17 | 24.00 | 346.83 | 24.00 | 36.17 | 24.00 |
| October | 68.50 | 23.93 | 177.00 | 23.98 | 3.67 | 23.98 |
| November | 415.33 | 23.31 | 0.00 | 23.31 | 0.00 | 23.31 |
| December | 533.00 | 22.55 | 1.17 | 22.55 | 1.17 | 22.55 |
| Annual Sum or Average | 3294.50 | 23.25 | 1631.83 | 23.50 | 144.00 | 23.51 |
| Minimum of Months | 21.83 | 22.55 | 0.00 | 22.55 | 0.00 | 22.55 |
| Maximum of Months | 533.00 | 24.00 | 511.67 | 24.00 | 81.17 | 24.00 |
Report: ComfortReportSimple55Monthly
For: M S2 APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 518.17 | 22.74 | 0.00 | 22.74 | 0.00 | 22.74 |
| February | 470.50 | 23.14 | 0.00 | 23.14 | 0.00 | 23.14 |
| March | 492.50 | 23.40 | 0.00 | 23.40 | 0.00 | 23.40 |
| April | 387.83 | 23.88 | 0.00 | 23.88 | 0.00 | 23.88 |
| May | 198.83 | 23.99 | 84.33 | 23.99 | 0.00 | 23.99 |
| June | 65.17 | 24.00 | 147.33 | 24.00 | 0.00 | 24.00 |
| July | 81.00 | 24.00 | 511.50 | 24.00 | 81.00 | 24.00 |
| August | 22.17 | 24.00 | 363.67 | 24.00 | 22.17 | 24.00 |
| September | 41.00 | 24.00 | 347.00 | 24.00 | 36.00 | 24.00 |
| October | 68.67 | 23.92 | 176.83 | 23.98 | 3.67 | 23.98 |
| November | 415.33 | 23.31 | 0.00 | 23.31 | 0.00 | 23.31 |
| December | 533.00 | 22.55 | 1.17 | 22.55 | 1.17 | 22.55 |
| Annual Sum or Average | 3294.17 | 23.25 | 1631.83 | 23.50 | 144.00 | 23.51 |
| Minimum of Months | 22.17 | 22.55 | 0.00 | 22.55 | 0.00 | 22.55 |
| Maximum of Months | 533.00 | 24.00 | 511.50 | 24.00 | 81.00 | 24.00 |
Report: ComfortReportSimple55Monthly
For: T SW APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 519.00 | 21.52 | 254.33 | 21.38 | 254.33 | 21.31 |
| February | 452.33 | 21.72 | 199.33 | 21.53 | 199.33 | 21.43 |
| March | 476.17 | 21.94 | 159.33 | 21.73 | 159.33 | 21.60 |
| April | 367.17 | 22.89 | 61.33 | 22.81 | 35.17 | 22.68 |
| May | 232.00 | 23.52 | 129.17 | 23.69 | 0.00 | 23.69 |
| June | 57.67 | 23.91 | 261.00 | 23.98 | 9.17 | 23.97 |
| July | 112.83 | 23.99 | 525.83 | 24.00 | 112.83 | 24.00 |
| August | 60.17 | 23.89 | 409.83 | 23.98 | 54.50 | 23.97 |
| September | 182.17 | 23.61 | 365.67 | 23.84 | 105.33 | 23.84 |
| October | 313.33 | 22.59 | 136.33 | 23.00 | 19.33 | 23.03 |
| November | 470.33 | 21.81 | 167.00 | 21.63 | 166.33 | 21.52 |
| December | 531.17 | 21.51 | 341.33 | 21.35 | 341.33 | 21.28 |
| Annual Sum or Average | 3774.33 | 22.23 | 3010.50 | 22.51 | 1457.00 | 22.37 |
| Minimum of Months | 57.67 | 21.51 | 61.33 | 21.35 | 0.00 | 21.28 |
| Maximum of Months | 531.17 | 23.99 | 525.83 | 24.00 | 341.33 | 24.00 |
Report: ComfortReportSimple55Monthly
For: T NW APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 744.00 | 21.19 | 513.83 | 21.16 | 513.83 | 21.14 |
| February | 672.00 | 21.49 | 372.00 | 21.35 | 372.00 | 21.29 |
| March | 744.00 | 21.90 | 277.50 | 21.68 | 277.50 | 21.56 |
| April | 525.50 | 22.86 | 85.50 | 22.77 | 51.83 | 22.64 |
| May | 280.67 | 23.49 | 226.00 | 23.72 | 0.00 | 23.72 |
| June | 61.67 | 23.93 | 445.17 | 23.99 | 9.67 | 23.98 |
| July | 137.33 | 24.00 | 737.67 | 24.00 | 137.33 | 24.00 |
| August | 79.00 | 23.89 | 632.33 | 23.98 | 72.17 | 23.97 |
| September | 236.17 | 23.56 | 506.83 | 23.83 | 126.83 | 23.83 |
| October | 505.17 | 22.53 | 144.83 | 22.84 | 28.33 | 22.87 |
| November | 712.50 | 21.59 | 327.83 | 21.44 | 327.83 | 21.36 |
| December | 744.00 | 21.14 | 629.67 | 21.12 | 629.67 | 21.11 |
| Annual Sum or Average | 5442.00 | 22.02 | 4899.17 | 22.34 | 2547.00 | 22.18 |
| Minimum of Months | 61.67 | 21.14 | 85.50 | 21.12 | 0.00 | 21.11 |
| Maximum of Months | 744.00 | 24.00 | 737.67 | 24.00 | 629.67 | 24.00 |
Report: ComfortReportSimple55Monthly
For: T SE APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 522.00 | 21.52 | 260.50 | 21.38 | 260.50 | 21.31 |
| February | 450.17 | 21.71 | 197.67 | 21.52 | 197.67 | 21.43 |
| March | 485.50 | 21.96 | 161.83 | 21.74 | 161.83 | 21.61 |
| April | 371.17 | 22.92 | 52.50 | 22.81 | 35.50 | 22.68 |
| May | 231.83 | 23.54 | 112.33 | 23.69 | 0.00 | 23.69 |
| June | 57.50 | 23.90 | 249.67 | 23.97 | 9.50 | 23.96 |
| July | 110.50 | 24.00 | 524.33 | 24.00 | 110.50 | 24.00 |
| August | 59.00 | 23.89 | 408.33 | 23.97 | 54.83 | 23.97 |
| September | 185.00 | 23.63 | 356.50 | 23.84 | 105.00 | 23.84 |
| October | 326.83 | 22.58 | 126.83 | 22.96 | 19.50 | 22.99 |
| November | 476.67 | 21.83 | 167.17 | 21.64 | 167.17 | 21.53 |
| December | 533.00 | 21.51 | 346.83 | 21.35 | 346.83 | 21.28 |
| Annual Sum or Average | 3809.17 | 22.23 | 2964.50 | 22.50 | 1468.83 | 22.35 |
| Minimum of Months | 57.50 | 21.51 | 52.50 | 21.35 | 0.00 | 21.28 |
| Maximum of Months | 533.00 | 24.00 | 524.33 | 24.00 | 346.83 | 24.00 |
Report: ComfortReportSimple55Monthly
For: T NE APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 744.00 | 21.14 | 525.00 | 21.12 | 525.00 | 21.12 |
| February | 672.00 | 21.48 | 355.00 | 21.35 | 355.00 | 21.29 |
| March | 744.00 | 21.91 | 259.17 | 21.70 | 259.17 | 21.58 |
| April | 516.17 | 22.94 | 71.50 | 22.85 | 43.50 | 22.73 |
| May | 255.67 | 23.54 | 203.33 | 23.74 | 0.00 | 23.74 |
| June | 56.50 | 23.91 | 451.00 | 23.98 | 9.50 | 23.98 |
| July | 130.50 | 24.00 | 735.83 | 24.00 | 130.50 | 24.00 |
| August | 75.33 | 23.89 | 635.67 | 23.98 | 70.33 | 23.97 |
| September | 225.00 | 23.59 | 509.00 | 23.85 | 123.83 | 23.84 |
| October | 526.67 | 22.62 | 141.33 | 22.89 | 29.50 | 22.92 |
| November | 715.67 | 21.54 | 312.00 | 21.41 | 312.00 | 21.34 |
| December | 744.00 | 21.11 | 647.83 | 21.11 | 647.83 | 21.10 |
| Annual Sum or Average | 5405.50 | 22.01 | 4846.67 | 22.34 | 2506.17 | 22.17 |
| Minimum of Months | 56.50 | 21.11 | 71.50 | 21.11 | 0.00 | 21.10 |
| Maximum of Months | 744.00 | 24.00 | 735.83 | 24.00 | 647.83 | 24.00 |
Report: ComfortReportSimple55Monthly
For: T N1 APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 744.00 | 21.16 | 466.67 | 21.14 | 466.67 | 21.13 |
| February | 672.00 | 21.49 | 339.33 | 21.36 | 339.33 | 21.29 |
| March | 744.00 | 21.91 | 234.00 | 21.72 | 234.00 | 21.60 |
| April | 573.67 | 23.10 | 43.17 | 22.99 | 37.83 | 22.88 |
| May | 289.00 | 23.69 | 156.83 | 23.80 | 0.00 | 23.80 |
| June | 65.00 | 23.98 | 365.83 | 24.00 | 7.17 | 24.00 |
| July | 126.50 | 24.00 | 733.17 | 24.00 | 126.50 | 24.00 |
| August | 69.17 | 23.97 | 609.83 | 23.99 | 66.50 | 23.99 |
| September | 225.83 | 23.71 | 481.83 | 23.89 | 117.67 | 23.89 |
| October | 537.33 | 22.87 | 131.67 | 23.08 | 27.00 | 23.10 |
| November | 720.00 | 21.58 | 291.17 | 21.44 | 291.17 | 21.37 |
| December | 744.00 | 21.12 | 617.33 | 21.11 | 617.33 | 21.11 |
| Annual Sum or Average | 5510.50 | 22.09 | 4470.83 | 22.37 | 2331.17 | 22.21 |
| Minimum of Months | 65.00 | 21.12 | 43.17 | 21.11 | 0.00 | 21.11 |
| Maximum of Months | 744.00 | 24.00 | 733.17 | 24.00 | 617.33 | 24.00 |
Report: ComfortReportSimple55Monthly
For: T N2 APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 744.00 | 21.16 | 466.83 | 21.14 | 466.83 | 21.13 |
| February | 672.00 | 21.49 | 338.17 | 21.36 | 338.17 | 21.29 |
| March | 744.00 | 21.92 | 232.67 | 21.72 | 232.67 | 21.60 |
| April | 572.67 | 23.10 | 42.83 | 22.99 | 37.33 | 22.88 |
| May | 287.67 | 23.69 | 157.17 | 23.80 | 0.00 | 23.80 |
| June | 65.17 | 23.98 | 366.00 | 24.00 | 7.50 | 24.00 |
| July | 126.17 | 24.00 | 732.50 | 24.00 | 126.17 | 24.00 |
| August | 69.33 | 23.97 | 610.50 | 23.99 | 66.67 | 23.99 |
| September | 225.67 | 23.71 | 482.83 | 23.89 | 118.00 | 23.89 |
| October | 537.33 | 22.86 | 131.17 | 23.07 | 27.33 | 23.10 |
| November | 720.00 | 21.58 | 292.83 | 21.44 | 292.83 | 21.36 |
| December | 744.00 | 21.12 | 618.17 | 21.11 | 618.17 | 21.11 |
| Annual Sum or Average | 5508.00 | 22.09 | 4471.67 | 22.37 | 2331.67 | 22.21 |
| Minimum of Months | 65.17 | 21.12 | 42.83 | 21.11 | 0.00 | 21.11 |
| Maximum of Months | 744.00 | 24.00 | 732.50 | 24.00 | 618.17 | 24.00 |
Report: ComfortReportSimple55Monthly
For: T S1 APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 521.17 | 21.69 | 171.17 | 21.55 | 171.17 | 21.46 |
| February | 454.67 | 21.91 | 147.33 | 21.71 | 147.33 | 21.59 |
| March | 494.67 | 22.21 | 111.83 | 22.00 | 111.83 | 21.86 |
| April | 385.83 | 23.15 | 31.67 | 23.07 | 20.83 | 22.98 |
| May | 233.83 | 23.71 | 90.50 | 23.79 | 0.00 | 23.79 |
| June | 62.00 | 23.98 | 220.00 | 23.99 | 7.50 | 23.99 |
| July | 102.67 | 24.00 | 520.17 | 24.00 | 102.67 | 24.00 |
| August | 51.83 | 23.97 | 392.17 | 23.99 | 50.50 | 23.99 |
| September | 165.33 | 23.76 | 354.83 | 23.91 | 95.50 | 23.91 |
| October | 297.50 | 22.95 | 131.00 | 23.26 | 17.17 | 23.29 |
| November | 472.17 | 22.06 | 118.33 | 21.87 | 118.33 | 21.74 |
| December | 533.00 | 21.66 | 265.83 | 21.47 | 265.83 | 21.38 |
| Annual Sum or Average | 3774.67 | 22.42 | 2554.83 | 22.67 | 1108.67 | 22.54 |
| Minimum of Months | 51.83 | 21.66 | 31.67 | 21.47 | 0.00 | 21.38 |
| Maximum of Months | 533.00 | 24.00 | 520.17 | 24.00 | 265.83 | 24.00 |
Report: ComfortReportSimple55Monthly
For: T S2 APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 520.83 | 21.69 | 171.83 | 21.54 | 171.83 | 21.46 |
| February | 454.33 | 21.91 | 147.83 | 21.71 | 147.83 | 21.59 |
| March | 494.50 | 22.20 | 112.17 | 22.00 | 112.17 | 21.86 |
| April | 385.67 | 23.15 | 31.67 | 23.07 | 20.67 | 22.98 |
| May | 233.67 | 23.71 | 90.33 | 23.79 | 0.00 | 23.79 |
| June | 62.50 | 23.98 | 219.50 | 23.99 | 7.67 | 23.99 |
| July | 102.67 | 24.00 | 520.00 | 24.00 | 102.67 | 24.00 |
| August | 51.83 | 23.97 | 391.67 | 23.99 | 50.50 | 23.99 |
| September | 166.00 | 23.75 | 353.83 | 23.90 | 96.00 | 23.91 |
| October | 298.67 | 22.94 | 130.17 | 23.26 | 17.00 | 23.28 |
| November | 472.67 | 22.06 | 118.17 | 21.87 | 118.17 | 21.74 |
| December | 533.00 | 21.66 | 265.67 | 21.47 | 265.67 | 21.38 |
| Annual Sum or Average | 3776.33 | 22.42 | 2552.83 | 22.67 | 1110.17 | 22.54 |
| Minimum of Months | 51.83 | 21.66 | 31.67 | 21.47 | 0.00 | 21.38 |
| Maximum of Months | 533.00 | 24.00 | 520.00 | 24.00 | 265.67 | 24.00 |
Report: ComfortReportSimple55Monthly
For: T CORRIDOR
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 739.67 | 21.27 | 168.50 | 21.11 | 168.50 | 21.00 |
| February | 625.33 | 21.64 | 170.33 | 21.57 | 147.00 | 21.45 |
| March | 631.33 | 22.13 | 107.17 | 22.20 | 68.83 | 22.13 |
| April | 455.00 | 24.07 | 497.67 | 24.63 | 273.17 | 24.71 |
| May | 485.00 | 25.63 | 681.00 | 25.73 | 448.17 | 25.75 |
| June | 699.17 | 26.35 | 720.00 | 26.35 | 699.17 | 26.35 |
| July | 744.00 | 26.40 | 744.00 | 26.40 | 744.00 | 26.40 |
| August | 744.00 | 26.19 | 744.00 | 26.19 | 744.00 | 26.19 |
| September | 720.00 | 25.74 | 720.00 | 25.74 | 720.00 | 25.74 |
| October | 719.50 | 24.38 | 736.17 | 24.39 | 714.83 | 24.39 |
| November | 645.67 | 21.91 | 225.00 | 21.99 | 188.33 | 21.94 |
| December | 744.00 | 20.99 | 219.50 | 20.80 | 219.50 | 20.68 |
| Annual Sum or Average | 7952.67 | 23.89 | 5733.33 | 24.38 | 5135.50 | 24.55 |
| Minimum of Months | 455.00 | 20.99 | 107.17 | 20.80 | 68.83 | 20.68 |
| Maximum of Months | 744.00 | 26.40 | 744.00 | 26.40 | 744.00 | 26.40 |
Report: ComfortReportSimple55Monthly
For: G CORRIDOR
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 744.00 | 20.50 | 307.83 | 20.09 | 307.83 | 19.87 |
| February | 672.00 | 20.98 | 217.33 | 20.53 | 217.33 | 20.26 |
| March | 744.00 | 21.56 | 132.00 | 21.16 | 132.00 | 20.86 |
| April | 341.50 | 23.21 | 190.17 | 23.96 | 20.50 | 23.88 |
| May | 104.33 | 25.26 | 635.00 | 26.18 | 70.33 | 26.21 |
| June | 238.00 | 27.38 | 713.83 | 27.17 | 237.33 | 27.22 |
| July | 713.67 | 27.14 | 744.00 | 27.14 | 713.67 | 27.14 |
| August | 506.50 | 27.03 | 743.50 | 26.97 | 506.50 | 26.99 |
| September | 412.67 | 26.52 | 708.17 | 26.54 | 404.50 | 26.56 |
| October | 220.50 | 24.69 | 559.33 | 25.33 | 160.17 | 25.41 |
| November | 588.00 | 22.22 | 117.00 | 22.10 | 67.50 | 21.83 |
| December | 744.00 | 20.40 | 330.33 | 19.95 | 330.33 | 19.71 |
| Annual Sum or Average | 6029.17 | 23.25 | 5398.50 | 24.12 | 3168.00 | 24.15 |
| Minimum of Months | 104.33 | 20.40 | 117.00 | 19.95 | 20.50 | 19.71 |
| Maximum of Months | 744.00 | 27.38 | 744.00 | 27.17 | 713.67 | 27.22 |
Report: ComfortReportSimple55Monthly
For: M CORRIDOR
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 732.17 | 23.02 | 499.33 | 23.04 | 499.00 | 23.06 |
| February | 624.00 | 23.55 | 439.67 | 23.64 | 414.33 | 23.67 |
| March | 510.33 | 24.12 | 555.17 | 24.29 | 400.17 | 24.31 |
| April | 471.17 | 25.57 | 685.67 | 25.55 | 469.83 | 25.56 |
| May | 577.00 | 25.97 | 744.00 | 25.96 | 577.00 | 25.97 |
| June | 715.17 | 26.21 | 720.00 | 26.21 | 715.17 | 26.21 |
| July | 744.00 | 26.19 | 744.00 | 26.19 | 744.00 | 26.19 |
| August | 744.00 | 26.11 | 744.00 | 26.11 | 744.00 | 26.11 |
| September | 720.00 | 25.99 | 720.00 | 25.99 | 720.00 | 25.99 |
| October | 744.00 | 25.57 | 744.00 | 25.57 | 744.00 | 25.57 |
| November | 676.17 | 24.07 | 683.00 | 24.13 | 645.83 | 24.13 |
| December | 744.00 | 22.85 | 544.67 | 22.85 | 544.67 | 22.85 |
| Annual Sum or Average | 8002.00 | 24.94 | 7823.50 | 25.05 | 7218.00 | 25.08 |
| Minimum of Months | 471.17 | 22.85 | 439.67 | 22.85 | 400.17 | 22.85 |
| Maximum of Months | 744.00 | 26.21 | 744.00 | 26.21 | 744.00 | 26.21 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_GSW
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 515.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 492.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 524.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 6145.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_GNW
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 8760.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_OFFICE
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 140.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 133.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 161.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 140.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 154.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 154.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 140.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 161.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 140.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 147.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 140.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 140.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 1750.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 133.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 161.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_GNE
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 8760.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_GN1
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 8760.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_GN2
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 8760.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_GS1
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 515.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 492.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 524.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 6145.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_GS2
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 515.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 492.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 524.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 6145.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_MSW
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 515.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 492.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 524.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 6145.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_MNW
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 8760.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_MSE
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 515.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 492.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 524.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 6145.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_MNE
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 8760.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_MN1
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 8760.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_MN2
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 8760.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_MS1
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 515.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 492.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 524.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 6145.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_MS2
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 515.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 492.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 524.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 6145.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_TSW
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 515.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 492.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 524.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 6145.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_TNW
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 8760.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_TSE
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 515.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 492.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 524.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 6145.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_TNE
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 8760.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_TN1
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 8760.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_TN2
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 8760.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_TS1
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 515.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 492.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 524.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 6145.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_TS2
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 515.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 492.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 506.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 524.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 510.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 6145.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 473.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 533.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_T CORRIDOR
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 8760.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_G CORRIDOR
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 8760.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: OCCUP_M CORRIDOR
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 8760.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: DXReportMonthly
For: SPLIT GSW COOLING COIL
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 9704109.99 | 2596806.52 | 17.98 | 9704109.99 | -0.0 | 0.00 | 0.08 | 01-JAN-16:20 | 0.00 | 01-JAN-00:10 | 400.13 | 01-JAN-16:20 | 400.13 | 01-JAN-16:20 | 0.00 | 12-JAN-15:30 | 106.03 | 01-JAN-16:20 | 0.00 | 01-JAN-00:10 |
| February | 39923965.36 | 10668232.33 | 35.92 | 39923965.36 | 0.00 | 0.00 | 0.14 | 20-FEB-16:10 | 0.00 | 01-FEB-00:10 | 703.01 | 20-FEB-16:10 | 703.01 | 20-FEB-16:10 | 0.00 | 20-FEB-16:20 | 186.28 | 20-FEB-16:10 | 0.00 | 01-FEB-00:10 |
| March | 42682253.24 | 11442408.87 | 42.08 | 42682253.24 | -0.0 | 0.00 | 0.13 | 21-MAR-16:07 | 0.00 | 01-MAR-00:10 | 690.10 | 21-MAR-16:07 | 690.10 | 21-MAR-16:07 | 0.00 | 14-MAR-16:20 | 185.48 | 21-MAR-16:07 | 0.00 | 01-MAR-00:10 |
| April | 0.851135E+09 | 0.232041E+09 | 354.04 | 0.850013E+09 | 1122143.30 | 0.00 | 0.37 | 21-APR-15:10 | 0.00 | 01-APR-00:10 | 1903.20 | 21-APR-15:10 | 1903.20 | 21-APR-15:10 | 41.75 | 29-APR-10:10 | 543.67 | 21-APR-15:10 | 0.00 | 01-APR-00:10 |
| May | 0.216054E+10 | 0.591137E+09 | 640.73 | 0.211062E+10 | 49922754.09 | 0.00 | 0.46 | 19-MAY-17:05 | 0.00 | 01-MAY-03:10 | 2383.05 | 19-MAY-17:03 | 2383.05 | 19-MAY-17:03 | 260.01 | 24-MAY-13:30 | 691.39 | 19-MAY-17:03 | 0.00 | 01-MAY-00:10 |
| June | 0.337877E+10 | 0.945826E+09 | 718.95 | 0.326604E+10 | 0.112726E+09 | 0.00 | 0.57 | 15-JUN-17:00 | 0.00 | 12-JUN-05:05 | 2829.34 | 15-JUN-17:00 | 2829.34 | 15-JUN-17:00 | 389.13 | 19-JUN-19:00 | 848.69 | 15-JUN-17:00 | 0.00 | 01-JUN-00:10 |
| July | 0.437449E+10 | 0.117319E+10 | 744.00 | 0.371957E+10 | 0.654920E+09 | 0.00 | 0.54 | 26-JUL-17:30 | 0.05 | 05-JUL-06:00 | 2962.79 | 27-JUL-17:20 | 2769.22 | 26-JUL-17:23 | 609.58 | 20-JUL-16:12 | 846.85 | 26-JUL-17:30 | 0.00 | 01-JUL-00:10 |
| August | 0.414375E+10 | 0.110933E+10 | 744.00 | 0.374572E+10 | 0.398027E+09 | 0.00 | 0.56 | 07-AUG-16:10 | 0.01 | 17-AUG-06:00 | 2928.38 | 06-AUG-17:10 | 2909.72 | 07-AUG-16:04 | 425.59 | 02-AUG-07:00 | 866.09 | 07-AUG-16:05 | 0.00 | 01-AUG-00:10 |
| September | 0.384871E+10 | 0.100583E+10 | 720.00 | 0.347339E+10 | 0.375325E+09 | 0.00 | 0.55 | 19-SEP-16:10 | 0.00 | 25-SEP-06:00 | 2913.67 | 19-SEP-16:04 | 2913.67 | 19-SEP-16:04 | 487.00 | 09-SEP-09:40 | 827.37 | 19-SEP-16:04 | 0.00 | 01-SEP-00:10 |
| October | 0.233330E+10 | 0.603450E+09 | 673.59 | 0.219654E+10 | 0.136762E+09 | 0.00 | 0.51 | 01-OCT-15:10 | 0.00 | 07-OCT-00:20 | 2770.11 | 05-OCT-16:10 | 2708.50 | 05-OCT-16:03 | 415.04 | 04-OCT-10:30 | 758.49 | 01-OCT-15:10 | 0.00 | 01-OCT-00:10 |
| November | 0.615735E+09 | 0.161719E+09 | 299.98 | 0.613770E+09 | 1965618.71 | 0.00 | 0.33 | 09-NOV-15:10 | 0.00 | 01-NOV-02:70 | 1788.90 | 09-NOV-15:10 | 1788.90 | 09-NOV-15:10 | 54.66 | 02-NOV-15:20 | 456.08 | 09-NOV-15:10 | 0.00 | 01-NOV-00:10 |
| December | 3042689.94 | 817571.64 | 4.50 | 3042689.94 | 0.00 | 0.00 | 0.06 | 16-DEC-16:10 | 0.00 | 01-DEC-00:10 | 301.57 | 16-DEC-16:10 | 301.57 | 16-DEC-16:10 | 0.00 | 16-DEC-15:20 | 80.84 | 16-DEC-16:10 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.218018E+11 | 0.584805E+10 | 4995.77 | 0.200710E+11 | 0.173077E+10 | 0.00 | ||||||||||||||
| Minimum of Months | 3042689.94 | 817571.64 | 4.50 | 3042689.94 | -0.0 | 0.00 | 0.06 | 0.00 | 301.57 | 301.57 | 0.00 | 80.84 | 0.00 | |||||||
| Maximum of Months | 0.437449E+10 | 0.117319E+10 | 744.00 | 0.374572E+10 | 0.654920E+09 | 0.00 | 0.57 | 0.05 | 2962.79 | 2913.67 | 609.58 | 866.09 | 0.00 |
Report: DXReportMonthly
For: SPLIT GNW COOLING COIL
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
| April | 0.540276E+09 | 0.148718E+09 | 274.92 | 0.539700E+09 | 576832.33 | 0.00 | 0.32 | 21-APR-15:10 | 0.00 | 01-APR-00:10 | 1642.74 | 21-APR-16:30 | 1642.74 | 21-APR-16:30 | 21.54 | 29-APR-10:00 | 470.60 | 21-APR-15:10 | 0.00 | 01-APR-00:10 |
| May | 0.207126E+10 | 0.566814E+09 | 635.30 | 0.202096E+10 | 50295778.12 | 0.00 | 0.46 | 19-MAY-17:10 | 0.00 | 01-MAY-02:20 | 2357.89 | 19-MAY-17:17 | 2357.89 | 19-MAY-17:17 | 260.21 | 24-MAY-13:40 | 683.23 | 19-MAY-17:10 | 0.00 | 01-MAY-00:10 |
| June | 0.343273E+10 | 0.958787E+09 | 719.33 | 0.331739E+10 | 0.115342E+09 | 0.00 | 0.60 | 15-JUN-17:00 | 0.00 | 12-JUN-05:05 | 2921.78 | 15-JUN-17:00 | 2921.78 | 15-JUN-17:00 | 394.63 | 19-JUN-19:00 | 872.52 | 15-JUN-17:00 | 0.00 | 01-JUN-00:10 |
| July | 0.435994E+10 | 0.116783E+10 | 744.00 | 0.370392E+10 | 0.656027E+09 | 0.00 | 0.55 | 26-JUL-17:30 | 0.05 | 05-JUL-06:00 | 2979.30 | 26-JUL-17:50 | 2774.12 | 26-JUL-17:30 | 635.11 | 20-JUL-16:25 | 850.94 | 26-JUL-17:30 | 0.00 | 01-JUL-00:10 |
| August | 0.386957E+10 | 0.103739E+10 | 744.00 | 0.347992E+10 | 0.389646E+09 | 0.00 | 0.54 | 07-AUG-16:10 | 0.01 | 17-AUG-06:00 | 2823.47 | 06-AUG-17:30 | 2810.95 | 06-AUG-17:30 | 441.06 | 02-AUG-07:00 | 833.70 | 07-AUG-16:10 | 0.00 | 01-AUG-00:10 |
| September | 0.311589E+10 | 0.819131E+09 | 712.03 | 0.277416E+10 | 0.341731E+09 | 0.00 | 0.45 | 19-SEP-16:40 | 0.00 | 24-SEP-07:00 | 2349.99 | 20-SEP-17:00 | 2344.41 | 20-SEP-17:00 | 438.71 | 22-SEP-09:40 | 671.93 | 19-SEP-16:40 | 0.00 | 01-SEP-00:10 |
| October | 0.131243E+10 | 0.343584E+09 | 537.70 | 0.121102E+10 | 0.101412E+09 | 0.00 | 0.42 | 05-OCT-16:10 | 0.00 | 01-OCT-07:12 | 2260.46 | 05-OCT-16:20 | 2181.14 | 05-OCT-16:03 | 362.77 | 04-OCT-10:30 | 619.17 | 05-OCT-16:10 | 0.00 | 01-OCT-00:10 |
| November | 29621724.91 | 7826645.99 | 36.60 | 29354943.66 | 266781.25 | 0.00 | 0.15 | 03-NOV-16:10 | 0.00 | 01-NOV-00:10 | 773.11 | 03-NOV-16:10 | 773.11 | 03-NOV-16:10 | 19.11 | 02-NOV-16:03 | 201.26 | 03-NOV-16:10 | 0.00 | 01-NOV-00:10 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.187317E+11 | 0.505008E+10 | 4403.89 | 0.170764E+11 | 0.165530E+10 | 0.00 | ||||||||||||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Maximum of Months | 0.435994E+10 | 0.116783E+10 | 744.00 | 0.370392E+10 | 0.656027E+09 | 0.00 | 0.60 | 0.05 | 2979.30 | 2921.78 | 635.11 | 872.52 | 0.00 |
Report: DXReportMonthly
For: SPLIT OFFICE COOLING COIL
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.123335E+09 | 32737870.28 | 73.67 | 0.123335E+09 | -0.0 | 0.00 | 0.20 | 12-JAN-15:00 | 0.00 | 01-JAN-00:10 | 1193.32 | 12-JAN-15:00 | 1193.32 | 12-JAN-15:00 | 0.00 | 13-JAN-14:10 | 311.51 | 12-JAN-15:00 | 0.00 | 01-JAN-00:10 |
| February | 0.166851E+09 | 44014258.56 | 71.50 | 0.166851E+09 | 0.00 | 0.00 | 0.25 | 22-FEB-14:00 | 0.00 | 01-FEB-00:10 | 1467.63 | 22-FEB-14:00 | 1467.63 | 22-FEB-14:00 | 0.00 | 07-FEB-10:00 | 382.01 | 22-FEB-14:00 | 0.00 | 01-FEB-00:10 |
| March | 0.313669E+09 | 82917170.40 | 126.17 | 0.313669E+09 | 0.00 | 0.00 | 0.25 | 16-MAR-14:40 | 0.00 | 01-MAR-00:10 | 1465.48 | 16-MAR-14:40 | 1465.48 | 16-MAR-14:40 | 0.00 | 08-MAR-12:10 | 381.47 | 16-MAR-14:40 | 0.00 | 01-MAR-00:10 |
| April | 0.937931E+09 | 0.247378E+09 | 171.09 | 0.937619E+09 | 312580.64 | 0.00 | 0.99 | 21-APR-08:62 | 0.00 | 01-APR-00:10 | 6763.26 | 19-APR-08:62 | 6763.26 | 19-APR-08:62 | 52.90 | 18-APR-16:00 | 1525.95 | 19-APR-08:62 | 0.00 | 01-APR-00:10 |
| May | 0.187141E+10 | 0.492048E+09 | 229.76 | 0.182848E+10 | 42923984.14 | 0.00 | 1.00 | 01-MAY-08:62 | 0.00 | 01-MAY-00:10 | 7319.33 | 25-MAY-08:62 | 7037.92 | 19-MAY-07:02 | 1313.57 | 25-MAY-08:62 | 1605.36 | 31-MAY-08:62 | 0.00 | 01-MAY-00:10 |
| June | 0.270725E+10 | 0.735244E+09 | 323.86 | 0.262689E+10 | 80356414.74 | 0.00 | 1.00 | 01-JUN-07:02 | 0.00 | 01-JUN-00:10 | 7491.20 | 28-JUN-07:02 | 7202.21 | 22-JUN-07:02 | 1650.23 | 29-JUN-08:62 | 1652.81 | 21-JUN-08:62 | 0.00 | 01-JUN-00:10 |
| July | 0.301345E+10 | 0.784111E+09 | 368.88 | 0.265014E+10 | 0.363311E+09 | 0.00 | 1.00 | 03-JUL-07:02 | 0.00 | 01-JUL-00:10 | 8067.18 | 21-JUL-07:02 | 7126.33 | 03-JUL-07:02 | 3628.08 | 21-JUL-07:03 | 1696.64 | 26-JUL-08:62 | 0.00 | 01-JUL-00:10 |
| August | 0.327416E+10 | 0.843783E+09 | 384.28 | 0.297984E+10 | 0.294324E+09 | 0.00 | 1.00 | 01-AUG-07:02 | 0.00 | 01-AUG-00:10 | 7824.25 | 02-AUG-07:02 | 7216.35 | 24-AUG-07:02 | 2583.69 | 02-AUG-07:03 | 1672.79 | 07-AUG-08:62 | 0.00 | 01-AUG-00:10 |
| September | 0.276629E+10 | 0.702391E+09 | 299.01 | 0.256685E+10 | 0.199440E+09 | 0.00 | 1.00 | 01-SEP-07:02 | 0.00 | 01-SEP-00:10 | 7786.40 | 22-SEP-07:02 | 7171.66 | 19-SEP-07:02 | 2545.94 | 14-SEP-07:03 | 1618.41 | 15-SEP-08:62 | 0.00 | 01-SEP-00:10 |
| October | 0.196191E+10 | 0.491144E+09 | 224.07 | 0.186444E+10 | 97467833.51 | 0.00 | 1.00 | 02-OCT-07:02 | 0.00 | 01-OCT-00:10 | 7580.88 | 04-OCT-07:03 | 7175.26 | 02-OCT-07:02 | 1803.93 | 04-OCT-08:62 | 1606.42 | 04-OCT-07:03 | 0.00 | 01-OCT-00:10 |
| November | 0.833030E+09 | 0.213399E+09 | 142.28 | 0.824327E+09 | 8702505.66 | 0.00 | 1.00 | 09-NOV-09:02 | 0.00 | 01-NOV-00:10 | 6927.43 | 10-NOV-09:02 | 6927.43 | 10-NOV-09:02 | 276.06 | 03-NOV-08:62 | 1562.27 | 10-NOV-09:02 | 0.00 | 01-NOV-00:10 |
| December | 0.121302E+09 | 32377645.07 | 87.50 | 0.121302E+09 | -0.0 | 0.00 | 0.14 | 07-DEC-15:10 | 0.00 | 01-DEC-00:10 | 784.29 | 07-DEC-15:10 | 784.29 | 07-DEC-15:10 | 0.00 | 07-DEC-15:00 | 207.78 | 07-DEC-15:10 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.180906E+11 | 0.470154E+10 | 2502.05 | 0.170037E+11 | 0.108684E+10 | 0.00 | ||||||||||||||
| Minimum of Months | 0.121302E+09 | 32377645.07 | 71.50 | 0.121302E+09 | -0.0 | 0.00 | 0.14 | 0.00 | 784.29 | 784.29 | 0.00 | 207.78 | 0.00 | |||||||
| Maximum of Months | 0.327416E+10 | 0.843783E+09 | 384.28 | 0.297984E+10 | 0.363311E+09 | 0.00 | 1.00 | 0.00 | 8067.18 | 7216.35 | 3628.08 | 1696.64 | 0.00 |
Report: DXReportMonthly
For: SPLIT GNE COOLING COIL
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
| April | 0.544107E+09 | 0.149452E+09 | 294.56 | 0.543366E+09 | 741259.48 | 0.00 | 0.32 | 21-APR-15:10 | 0.00 | 01-APR-00:10 | 1523.58 | 21-APR-15:10 | 1523.58 | 21-APR-15:10 | 32.03 | 29-APR-09:40 | 438.49 | 21-APR-15:10 | 0.00 | 01-APR-00:10 |
| May | 0.209473E+10 | 0.571450E+09 | 651.32 | 0.204183E+10 | 52901651.92 | 0.00 | 0.41 | 19-MAY-17:10 | 0.00 | 01-MAY-02:20 | 1982.22 | 19-MAY-17:05 | 1982.22 | 19-MAY-17:05 | 244.78 | 24-MAY-13:30 | 579.14 | 19-MAY-17:05 | 0.00 | 01-MAY-00:10 |
| June | 0.348277E+10 | 0.968581E+09 | 718.33 | 0.336375E+10 | 0.119025E+09 | 0.00 | 0.55 | 15-JUN-17:00 | 0.00 | 12-JUN-05:05 | 2539.77 | 15-JUN-17:00 | 2539.77 | 15-JUN-17:00 | 382.60 | 19-JUN-19:00 | 764.10 | 15-JUN-17:00 | 0.00 | 01-JUN-00:10 |
| July | 0.440176E+10 | 0.117431E+10 | 744.00 | 0.373790E+10 | 0.663863E+09 | 0.00 | 0.55 | 03-JUL-17:00 | 0.07 | 05-JUL-06:00 | 2652.13 | 26-JUL-18:00 | 2622.31 | 03-JUL-17:00 | 647.16 | 21-JUL-07:40 | 796.55 | 03-JUL-17:00 | 0.00 | 01-JUL-00:10 |
| August | 0.391001E+10 | 0.104399E+10 | 744.00 | 0.351310E+10 | 0.396911E+09 | 0.00 | 0.51 | 07-AUG-16:10 | 0.01 | 17-AUG-06:00 | 2495.27 | 07-AUG-18:00 | 2494.48 | 07-AUG-18:00 | 534.34 | 02-AUG-07:40 | 743.48 | 07-AUG-16:10 | 0.00 | 01-AUG-00:10 |
| September | 0.313346E+10 | 0.820980E+09 | 713.56 | 0.278284E+10 | 0.350626E+09 | 0.00 | 0.41 | 16-SEP-16:03 | 0.00 | 25-SEP-02:00 | 2087.87 | 15-SEP-16:10 | 1990.42 | 20-SEP-17:00 | 463.47 | 09-SEP-09:20 | 578.51 | 15-SEP-13:00 | 0.00 | 01-SEP-00:10 |
| October | 0.124906E+10 | 0.326966E+09 | 539.15 | 0.115222E+10 | 96836217.03 | 0.00 | 0.37 | 03-OCT-14:10 | 0.00 | 06-OCT-22:10 | 1920.49 | 03-OCT-15:10 | 1811.87 | 05-OCT-16:03 | 397.46 | 04-OCT-10:30 | 540.59 | 03-OCT-14:10 | 0.00 | 01-OCT-00:10 |
| November | 22244081.77 | 5896245.71 | 29.06 | 22124774.37 | 119307.40 | 0.00 | 0.10 | 03-NOV-16:05 | 0.00 | 01-NOV-00:10 | 484.93 | 03-NOV-16:05 | 484.93 | 03-NOV-16:05 | 13.28 | 03-NOV-13:00 | 127.16 | 03-NOV-16:05 | 0.00 | 01-NOV-00:10 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.188381E+11 | 0.506162E+10 | 4433.97 | 0.171571E+11 | 0.168102E+10 | 0.00 | ||||||||||||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Maximum of Months | 0.440176E+10 | 0.117431E+10 | 744.00 | 0.373790E+10 | 0.663863E+09 | 0.00 | 0.55 | 0.07 | 2652.13 | 2622.31 | 647.16 | 796.55 | 0.00 |
Report: DXReportMonthly
For: SPLIT GN1 COOLING COIL
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
| April | 0.472477E+09 | 0.129743E+09 | 310.44 | 0.471729E+09 | 747925.15 | 0.00 | 0.28 | 21-APR-15:10 | 0.00 | 01-APR-00:10 | 1238.16 | 21-APR-17:07 | 1238.16 | 21-APR-17:07 | 22.31 | 29-APR-09:50 | 352.98 | 21-APR-15:10 | 0.00 | 01-APR-00:10 |
| May | 0.181798E+10 | 0.496139E+09 | 671.59 | 0.176864E+10 | 49341394.98 | 0.00 | 0.38 | 19-MAY-17:20 | 0.00 | 01-MAY-03:40 | 1658.77 | 19-MAY-17:17 | 1658.77 | 19-MAY-17:17 | 208.43 | 24-MAY-13:40 | 485.52 | 19-MAY-17:03 | 0.00 | 01-MAY-00:10 |
| June | 0.293106E+10 | 0.816400E+09 | 720.00 | 0.282240E+10 | 0.108660E+09 | 0.00 | 0.51 | 15-JUN-17:02 | 0.01 | 13-JUN-05:40 | 2088.89 | 15-JUN-17:05 | 2088.89 | 15-JUN-17:05 | 316.71 | 19-JUN-19:00 | 631.36 | 15-JUN-17:05 | 0.00 | 01-JUN-00:10 |
| July | 0.370986E+10 | 0.990827E+09 | 744.00 | 0.312014E+10 | 0.589726E+09 | 0.00 | 0.50 | 03-JUL-17:00 | 0.08 | 05-JUL-06:00 | 2181.09 | 26-JUL-18:00 | 2126.44 | 03-JUL-17:00 | 568.49 | 20-JUL-16:25 | 651.21 | 03-JUL-17:00 | 0.00 | 01-JUL-00:10 |
| August | 0.325848E+10 | 0.871663E+09 | 744.00 | 0.290414E+10 | 0.354343E+09 | 0.00 | 0.47 | 07-AUG-16:06 | 0.03 | 31-AUG-06:00 | 2064.29 | 07-AUG-18:00 | 2055.34 | 07-AUG-18:00 | 418.91 | 03-AUG-07:25 | 610.51 | 07-AUG-16:04 | 0.00 | 01-AUG-00:10 |
| September | 0.259377E+10 | 0.680984E+09 | 719.30 | 0.228370E+10 | 0.310065E+09 | 0.00 | 0.37 | 22-SEP-16:03 | 0.00 | 25-SEP-04:00 | 1708.64 | 22-SEP-16:03 | 1646.58 | 20-SEP-17:05 | 395.63 | 22-SEP-09:40 | 477.14 | 22-SEP-16:03 | 0.00 | 01-SEP-00:10 |
| October | 0.115065E+10 | 0.301098E+09 | 608.93 | 0.105417E+10 | 96480986.27 | 0.00 | 0.35 | 04-OCT-16:40 | 0.00 | 01-OCT-07:12 | 1617.51 | 04-OCT-16:40 | 1500.01 | 05-OCT-16:03 | 330.44 | 04-OCT-10:30 | 445.36 | 03-OCT-14:10 | 0.00 | 01-OCT-00:10 |
| November | 25928870.57 | 6857702.70 | 45.31 | 25515761.87 | 413108.70 | 0.00 | 0.12 | 03-NOV-16:05 | 0.00 | 01-NOV-00:10 | 525.39 | 03-NOV-16:05 | 525.39 | 03-NOV-16:05 | 30.31 | 02-NOV-19:00 | 137.36 | 03-NOV-16:05 | 0.00 | 01-NOV-00:10 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.159602E+11 | 0.429371E+10 | 4563.57 | 0.144504E+11 | 0.150978E+10 | 0.00 | ||||||||||||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Maximum of Months | 0.370986E+10 | 0.990827E+09 | 744.00 | 0.312014E+10 | 0.589726E+09 | 0.00 | 0.51 | 0.08 | 2181.09 | 2126.44 | 568.49 | 651.21 | 0.00 |
Report: DXReportMonthly
For: SPLIT GN2 COOLING COIL
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
| April | 0.476760E+09 | 0.130890E+09 | 312.67 | 0.476003E+09 | 757413.61 | 0.00 | 0.29 | 21-APR-15:10 | 0.00 | 01-APR-00:10 | 1237.69 | 21-APR-17:10 | 1237.69 | 21-APR-17:10 | 22.65 | 29-APR-09:50 | 353.56 | 21-APR-15:10 | 0.00 | 01-APR-00:10 |
| May | 0.182152E+10 | 0.497060E+09 | 672.83 | 0.177213E+10 | 49390329.43 | 0.00 | 0.38 | 19-MAY-17:10 | 0.00 | 01-MAY-03:40 | 1652.60 | 19-MAY-17:13 | 1652.60 | 19-MAY-17:13 | 208.13 | 24-MAY-13:40 | 484.25 | 19-MAY-17:05 | 0.00 | 01-MAY-00:10 |
| June | 0.293382E+10 | 0.817100E+09 | 720.00 | 0.282511E+10 | 0.108712E+09 | 0.00 | 0.51 | 15-JUN-17:00 | 0.01 | 13-JUN-05:40 | 2083.94 | 15-JUN-17:08 | 2083.94 | 15-JUN-17:08 | 316.22 | 19-JUN-19:00 | 629.97 | 15-JUN-17:00 | 0.00 | 01-JUN-00:10 |
| July | 0.371164E+10 | 0.991245E+09 | 744.00 | 0.312181E+10 | 0.589834E+09 | 0.00 | 0.50 | 03-JUL-17:00 | 0.08 | 05-JUL-06:00 | 2177.26 | 26-JUL-18:00 | 2127.31 | 03-JUL-17:00 | 568.66 | 20-JUL-16:25 | 651.40 | 03-JUL-17:00 | 0.00 | 01-JUL-00:10 |
| August | 0.326044E+10 | 0.872127E+09 | 744.00 | 0.290597E+10 | 0.354471E+09 | 0.00 | 0.47 | 07-AUG-16:10 | 0.03 | 31-AUG-06:00 | 2058.00 | 07-AUG-18:00 | 2049.09 | 07-AUG-18:00 | 420.69 | 03-AUG-07:25 | 609.46 | 07-AUG-16:10 | 0.00 | 01-AUG-00:10 |
| September | 0.259478E+10 | 0.681215E+09 | 719.13 | 0.228457E+10 | 0.310214E+09 | 0.00 | 0.37 | 16-SEP-16:03 | 0.00 | 25-SEP-04:00 | 1702.84 | 22-SEP-16:03 | 1642.21 | 20-SEP-17:05 | 395.56 | 22-SEP-09:40 | 476.23 | 16-SEP-16:03 | 0.00 | 01-SEP-00:10 |
| October | 0.114789E+10 | 0.300386E+09 | 608.11 | 0.105179E+10 | 96100698.87 | 0.00 | 0.34 | 04-OCT-16:30 | 0.00 | 01-OCT-07:12 | 1610.30 | 04-OCT-16:30 | 1495.32 | 05-OCT-16:10 | 331.44 | 04-OCT-10:30 | 445.76 | 03-OCT-14:10 | 0.00 | 01-OCT-00:10 |
| November | 25569636.55 | 6763538.79 | 44.75 | 25173400.77 | 396235.78 | 0.00 | 0.12 | 03-NOV-16:05 | 0.00 | 01-NOV-00:10 | 520.05 | 03-NOV-16:05 | 520.05 | 03-NOV-16:05 | 28.39 | 02-NOV-19:00 | 135.98 | 03-NOV-16:05 | 0.00 | 01-NOV-00:10 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.159724E+11 | 0.429679E+10 | 4565.49 | 0.144625E+11 | 0.150988E+10 | 0.00 | ||||||||||||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Maximum of Months | 0.371164E+10 | 0.991245E+09 | 744.00 | 0.312181E+10 | 0.589834E+09 | 0.00 | 0.51 | 0.08 | 2177.26 | 2127.31 | 568.66 | 651.40 | 0.00 |
Report: DXReportMonthly
For: SPLIT GS1 COOLING COIL
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 37543219.50 | 10005968.17 | 49.50 | 37543219.50 | -0.0 | 0.00 | 0.11 | 01-JAN-13:50 | 0.00 | 01-JAN-00:10 | 522.02 | 01-JAN-13:50 | 522.02 | 01-JAN-13:50 | 0.00 | 01-JAN-12:40 | 137.33 | 01-JAN-13:50 | 0.00 | 01-JAN-00:10 |
| February | 57590343.57 | 15365031.41 | 53.58 | 57590343.57 | 0.00 | 0.00 | 0.14 | 22-FEB-14:00 | 0.00 | 01-FEB-00:10 | 615.21 | 22-FEB-14:00 | 615.21 | 22-FEB-14:00 | 0.00 | 06-FEB-14:40 | 162.95 | 22-FEB-14:00 | 0.00 | 01-FEB-00:10 |
| March | 62016491.57 | 16601244.49 | 65.93 | 62016491.57 | -0.0 | 0.00 | 0.13 | 21-MAR-16:07 | 0.00 | 01-MAR-00:10 | 596.52 | 21-MAR-16:07 | 596.52 | 21-MAR-16:07 | 0.00 | 14-MAR-14:20 | 160.31 | 21-MAR-16:07 | 0.00 | 01-MAR-00:10 |
| April | 0.830377E+09 | 0.225534E+09 | 421.02 | 0.828842E+09 | 1534362.20 | 0.00 | 0.34 | 21-APR-15:10 | 0.00 | 01-APR-00:10 | 1497.82 | 21-APR-15:10 | 1497.82 | 21-APR-15:10 | 43.88 | 29-APR-10:10 | 430.00 | 21-APR-15:10 | 0.00 | 01-APR-00:10 |
| May | 0.192512E+10 | 0.525261E+09 | 682.23 | 0.187589E+10 | 49226449.85 | 0.00 | 0.38 | 19-MAY-17:03 | 0.00 | 01-MAY-07:35 | 1685.70 | 19-MAY-17:03 | 1685.70 | 19-MAY-17:03 | 209.51 | 24-MAY-13:30 | 494.98 | 19-MAY-17:03 | 0.00 | 01-MAY-00:10 |
| June | 0.288958E+10 | 0.806815E+09 | 720.00 | 0.278305E+10 | 0.106530E+09 | 0.00 | 0.48 | 15-JUN-16:40 | 0.00 | 13-JUN-05:40 | 2013.83 | 05-JUN-17:00 | 2013.83 | 05-JUN-17:00 | 314.36 | 03-JUN-18:30 | 617.31 | 05-JUN-17:00 | 0.00 | 01-JUN-00:10 |
| July | 0.374018E+10 | 0.100042E+10 | 744.00 | 0.314978E+10 | 0.590409E+09 | 0.00 | 0.49 | 03-JUL-17:00 | 0.08 | 05-JUL-06:00 | 2149.90 | 26-JUL-17:30 | 2131.25 | 03-JUL-17:00 | 543.09 | 20-JUL-16:12 | 653.96 | 03-JUL-17:00 | 0.00 | 01-JUL-00:10 |
| August | 0.355221E+10 | 0.948911E+09 | 744.00 | 0.318723E+10 | 0.364985E+09 | 0.00 | 0.48 | 07-AUG-16:08 | 0.04 | 17-AUG-06:00 | 2139.82 | 07-AUG-16:01 | 2139.82 | 07-AUG-16:01 | 404.39 | 03-AUG-07:25 | 644.61 | 07-AUG-16:04 | 0.00 | 01-AUG-00:10 |
| September | 0.335603E+10 | 0.875504E+09 | 720.00 | 0.300795E+10 | 0.348075E+09 | 0.00 | 0.49 | 19-SEP-14:10 | 0.03 | 25-SEP-07:50 | 2236.01 | 20-SEP-14:10 | 2227.91 | 19-SEP-14:10 | 452.42 | 09-SEP-09:30 | 637.69 | 19-SEP-14:10 | 0.00 | 01-SEP-00:10 |
| October | 0.224109E+10 | 0.578875E+09 | 733.58 | 0.210625E+10 | 0.134842E+09 | 0.00 | 0.47 | 01-OCT-15:10 | 0.00 | 07-OCT-03:00 | 2143.79 | 03-OCT-14:00 | 2135.38 | 01-OCT-15:10 | 383.60 | 04-OCT-10:30 | 603.90 | 01-OCT-15:10 | 0.00 | 01-OCT-00:10 |
| November | 0.774218E+09 | 0.203056E+09 | 399.30 | 0.771379E+09 | 2838630.35 | 0.00 | 0.33 | 09-NOV-14:00 | 0.00 | 01-NOV-21:03 | 1537.47 | 09-NOV-14:00 | 1537.47 | 09-NOV-14:00 | 57.96 | 03-NOV-11:50 | 392.45 | 09-NOV-14:00 | 0.00 | 01-NOV-00:10 |
| December | 11906118.66 | 3189176.63 | 19.25 | 11906118.66 | 0.00 | 0.00 | 0.09 | 16-DEC-15:10 | 0.00 | 01-DEC-00:10 | 407.43 | 16-DEC-15:10 | 407.43 | 16-DEC-15:10 | 0.00 | 17-DEC-14:20 | 108.68 | 16-DEC-15:10 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.194779E+11 | 0.520954E+10 | 5352.40 | 0.178794E+11 | 0.159844E+10 | 0.00 | ||||||||||||||
| Minimum of Months | 11906118.66 | 3189176.63 | 19.25 | 11906118.66 | -0.0 | 0.00 | 0.09 | 0.00 | 407.43 | 407.43 | 0.00 | 108.68 | 0.00 | |||||||
| Maximum of Months | 0.374018E+10 | 0.100042E+10 | 744.00 | 0.318723E+10 | 0.590409E+09 | 0.00 | 0.49 | 0.08 | 2236.01 | 2227.91 | 543.09 | 653.96 | 0.00 |
Report: DXReportMonthly
For: SPLIT GS2 COOLING COIL
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 39691928.25 | 10583099.38 | 53.33 | 39691928.25 | -0.0 | 0.00 | 0.11 | 01-JAN-13:50 | 0.00 | 01-JAN-00:10 | 508.59 | 01-JAN-13:50 | 508.59 | 01-JAN-13:50 | 0.00 | 12-JAN-14:40 | 133.87 | 01-JAN-13:50 | 0.00 | 01-JAN-00:10 |
| February | 62912517.27 | 16776389.72 | 56.83 | 62912517.27 | 0.00 | 0.00 | 0.14 | 22-FEB-14:00 | 0.00 | 01-FEB-00:10 | 650.41 | 22-FEB-14:00 | 650.41 | 22-FEB-14:00 | 0.00 | 20-FEB-15:50 | 172.10 | 22-FEB-14:00 | 0.00 | 01-FEB-00:10 |
| March | 74412797.82 | 19904330.17 | 78.00 | 74412797.82 | -0.0 | 0.00 | 0.14 | 21-MAR-16:10 | 0.00 | 01-MAR-00:10 | 635.74 | 21-MAR-16:10 | 635.74 | 21-MAR-16:10 | 0.00 | 14-MAR-15:40 | 170.65 | 21-MAR-16:10 | 0.00 | 01-MAR-00:10 |
| April | 0.929312E+09 | 0.251726E+09 | 453.52 | 0.927504E+09 | 1808351.94 | 0.00 | 0.35 | 21-APR-15:10 | 0.00 | 01-APR-00:10 | 1558.08 | 21-APR-15:10 | 1558.08 | 21-APR-15:10 | 46.77 | 29-APR-10:00 | 446.58 | 21-APR-15:10 | 0.00 | 01-APR-00:10 |
| May | 0.213892E+10 | 0.581410E+09 | 698.01 | 0.208474E+10 | 54181815.31 | 0.00 | 0.39 | 21-MAY-16:02 | 0.00 | 01-MAY-07:35 | 1793.95 | 21-MAY-16:02 | 1793.95 | 21-MAY-16:02 | 214.94 | 24-MAY-13:30 | 519.28 | 21-MAY-16:02 | 0.00 | 01-MAY-00:10 |
| June | 0.318100E+10 | 0.883817E+09 | 720.00 | 0.306565E+10 | 0.115354E+09 | 0.00 | 0.49 | 15-JUN-17:00 | 0.03 | 13-JUN-05:40 | 2119.64 | 05-JUN-17:00 | 2119.64 | 05-JUN-17:00 | 333.77 | 03-JUN-18:30 | 647.73 | 05-JUN-17:00 | 0.00 | 01-JUN-00:10 |
| July | 0.409008E+10 | 0.108984E+10 | 744.00 | 0.346797E+10 | 0.622110E+09 | 0.00 | 0.51 | 03-JUL-17:00 | 0.11 | 05-JUL-06:00 | 2251.55 | 26-JUL-17:50 | 2245.79 | 03-JUL-17:00 | 554.12 | 20-JUL-16:02 | 686.84 | 03-JUL-17:00 | 0.00 | 01-JUL-00:10 |
| August | 0.388124E+10 | 0.103272E+10 | 744.00 | 0.349532E+10 | 0.385921E+09 | 0.00 | 0.50 | 06-AUG-17:10 | 0.06 | 17-AUG-06:00 | 2300.96 | 06-AUG-17:10 | 2271.03 | 06-AUG-17:04 | 429.45 | 02-AUG-07:00 | 678.00 | 06-AUG-17:10 | 0.00 | 01-AUG-00:10 |
| September | 0.366690E+10 | 0.953218E+09 | 720.00 | 0.329866E+10 | 0.368239E+09 | 0.00 | 0.50 | 19-SEP-14:10 | 0.05 | 30-SEP-06:00 | 2327.67 | 20-SEP-14:10 | 2325.99 | 19-SEP-14:10 | 473.64 | 09-SEP-09:30 | 664.05 | 19-SEP-14:00 | 0.00 | 01-SEP-00:10 |
| October | 0.244667E+10 | 0.630808E+09 | 739.00 | 0.230328E+10 | 0.143386E+09 | 0.00 | 0.49 | 01-OCT-15:10 | 0.00 | 13-OCT-08:40 | 2278.95 | 01-OCT-15:10 | 2278.95 | 01-OCT-15:10 | 395.24 | 04-OCT-10:30 | 641.85 | 01-OCT-15:10 | 0.00 | 01-OCT-00:10 |
| November | 0.837227E+09 | 0.219402E+09 | 413.63 | 0.834043E+09 | 3183672.07 | 0.00 | 0.33 | 09-NOV-14:00 | 0.00 | 01-NOV-22:10 | 1583.70 | 09-NOV-14:00 | 1583.70 | 09-NOV-14:00 | 59.69 | 03-NOV-11:50 | 403.82 | 09-NOV-14:00 | 0.00 | 01-NOV-00:10 |
| December | 16948559.52 | 4539114.33 | 31.17 | 16948559.52 | -0.0 | 0.00 | 0.10 | 16-DEC-15:10 | 0.00 | 01-DEC-00:10 | 461.70 | 16-DEC-15:10 | 461.70 | 16-DEC-15:10 | 0.00 | 17-DEC-14:30 | 122.94 | 16-DEC-15:10 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.213653E+11 | 0.569475E+10 | 5451.50 | 0.196711E+11 | 0.169418E+10 | 0.00 | ||||||||||||||
| Minimum of Months | 16948559.52 | 4539114.33 | 31.17 | 16948559.52 | -0.0 | 0.00 | 0.10 | 0.00 | 461.70 | 461.70 | 0.00 | 122.94 | 0.00 | |||||||
| Maximum of Months | 0.409008E+10 | 0.108984E+10 | 744.00 | 0.349532E+10 | 0.622110E+09 | 0.00 | 0.51 | 0.11 | 2327.67 | 2325.99 | 554.12 | 686.84 | 0.00 |
Report: DXReportMonthly
For: SPLIT MSW COOLING COIL
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.165829E+09 | 44115161.84 | 73.29 | 0.165829E+09 | -0.0 | 0.00 | 0.18 | 12-JAN-15:00 | 0.00 | 01-JAN-00:10 | 2244.19 | 12-JAN-15:00 | 2244.19 | 12-JAN-15:00 | 0.00 | 12-JAN-16:20 | 587.20 | 12-JAN-15:00 | 0.00 | 01-JAN-00:10 |
| February | 0.518470E+09 | 0.136956E+09 | 119.08 | 0.518470E+09 | -0.0 | 0.00 | 0.29 | 20-FEB-16:10 | 0.00 | 01-FEB-00:10 | 3666.49 | 20-FEB-16:10 | 3666.49 | 20-FEB-16:10 | 0.00 | 19-FEB-17:00 | 948.26 | 20-FEB-16:10 | 0.00 | 01-FEB-00:10 |
| March | 0.906645E+09 | 0.239734E+09 | 212.74 | 0.906645E+09 | -0.0 | 0.00 | 0.30 | 14-MAR-16:15 | 0.00 | 01-MAR-00:10 | 3719.56 | 14-MAR-16:15 | 3719.56 | 14-MAR-16:15 | 0.00 | 12-MAR-16:05 | 968.04 | 14-MAR-16:15 | 0.00 | 01-MAR-00:10 |
| April | 0.376733E+10 | 0.100955E+10 | 524.39 | 0.376179E+10 | 5535716.57 | 0.00 | 0.46 | 21-APR-15:10 | 0.00 | 01-APR-00:10 | 5650.37 | 21-APR-15:10 | 5650.37 | 21-APR-15:10 | 117.83 | 29-APR-09:50 | 1591.22 | 21-APR-15:10 | 0.00 | 01-APR-00:10 |
| May | 0.637597E+10 | 0.172924E+10 | 698.15 | 0.623583E+10 | 0.140148E+09 | 0.00 | 0.51 | 19-MAY-17:08 | 0.00 | 01-MAY-07:35 | 6283.40 | 19-MAY-17:05 | 6283.40 | 19-MAY-17:05 | 660.92 | 24-MAY-13:30 | 1808.71 | 19-MAY-17:05 | 0.00 | 01-MAY-00:10 |
| June | 0.856529E+10 | 0.238803E+10 | 720.00 | 0.828732E+10 | 0.277963E+09 | 0.00 | 0.60 | 15-JUN-17:00 | 0.01 | 12-JUN-05:05 | 6994.51 | 15-JUN-17:00 | 6994.51 | 15-JUN-17:00 | 986.60 | 19-JUN-19:00 | 2100.29 | 05-JUN-17:00 | 0.00 | 01-JUN-00:10 |
| July | 0.985998E+10 | 0.265172E+10 | 744.00 | 0.840363E+10 | 0.145635E+10 | 0.00 | 0.53 | 26-JUL-17:30 | 0.03 | 05-JUL-06:00 | 6910.85 | 27-JUL-17:20 | 6412.47 | 26-JUL-17:23 | 1386.42 | 20-JUL-16:02 | 1964.77 | 26-JUL-17:30 | 0.00 | 01-JUL-00:10 |
| August | 0.865714E+10 | 0.233241E+10 | 743.06 | 0.782724E+10 | 0.829896E+09 | 0.00 | 0.52 | 07-AUG-16:10 | 0.00 | 17-AUG-05:30 | 6411.20 | 07-AUG-16:10 | 6411.20 | 07-AUG-16:10 | 925.45 | 02-AUG-11:40 | 1919.16 | 07-AUG-16:10 | 0.00 | 01-AUG-00:10 |
| September | 0.751626E+10 | 0.198104E+10 | 710.08 | 0.678061E+10 | 0.735654E+09 | 0.00 | 0.50 | 19-SEP-16:10 | 0.00 | 11-SEP-05:50 | 6299.46 | 19-SEP-16:06 | 6299.46 | 19-SEP-16:06 | 1035.07 | 09-SEP-09:40 | 1801.28 | 19-SEP-16:06 | 0.00 | 01-SEP-00:10 |
| October | 0.456980E+10 | 0.118596E+10 | 587.36 | 0.430533E+10 | 0.264475E+09 | 0.00 | 0.48 | 01-OCT-15:10 | 0.00 | 01-OCT-07:12 | 6129.80 | 05-OCT-16:10 | 6033.58 | 01-OCT-15:10 | 915.22 | 04-OCT-10:40 | 1703.16 | 01-OCT-15:10 | 0.00 | 01-OCT-00:10 |
| November | 0.130882E+10 | 0.343728E+09 | 259.67 | 0.130557E+10 | 3252696.95 | 0.00 | 0.33 | 09-NOV-15:10 | 0.00 | 01-NOV-00:10 | 4315.63 | 09-NOV-15:10 | 4315.63 | 09-NOV-15:10 | 120.37 | 03-NOV-12:00 | 1098.79 | 09-NOV-15:10 | 0.00 | 01-NOV-00:10 |
| December | 39893794.53 | 10689388.86 | 25.73 | 39893794.53 | 0.00 | 0.00 | 0.12 | 16-DEC-15:30 | 0.00 | 01-DEC-00:10 | 1489.04 | 16-DEC-15:30 | 1489.04 | 16-DEC-15:30 | 0.00 | 16-DEC-15:30 | 395.38 | 16-DEC-15:30 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.522514E+11 | 0.140532E+11 | 5417.55 | 0.485381E+11 | 0.371327E+10 | 0.00 | ||||||||||||||
| Minimum of Months | 39893794.53 | 10689388.86 | 25.73 | 39893794.53 | -0.0 | 0.00 | 0.12 | 0.00 | 1489.04 | 1489.04 | 0.00 | 395.38 | 0.00 | |||||||
| Maximum of Months | 0.985998E+10 | 0.265172E+10 | 744.00 | 0.840363E+10 | 0.145635E+10 | 0.00 | 0.60 | 0.03 | 6994.51 | 6994.51 | 1386.42 | 2100.29 | 0.00 |
Report: DXReportMonthly
For: SPLIT MNW COOLING COIL
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| February | 18860912.49 | 5068227.52 | 14.50 | 18860912.49 | -0.0 | 0.00 | 0.08 | 21-FEB-17:05 | 0.00 | 01-FEB-00:10 | 928.11 | 21-FEB-17:05 | 928.11 | 21-FEB-17:05 | 0.00 | 20-FEB-16:20 | 248.10 | 21-FEB-17:05 | 0.00 | 01-FEB-00:10 |
| March | 0.148878E+09 | 39850341.14 | 66.86 | 0.148878E+09 | 0.00 | 0.00 | 0.15 | 16-MAR-16:05 | 0.00 | 01-MAR-00:10 | 1770.03 | 16-MAR-16:05 | 1770.03 | 16-MAR-16:05 | 0.00 | 16-MAR-16:30 | 468.23 | 16-MAR-16:05 | 0.00 | 01-MAR-00:10 |
| April | 0.285046E+10 | 0.769383E+09 | 478.00 | 0.284620E+10 | 4260680.19 | 0.00 | 0.42 | 21-APR-15:10 | 0.00 | 01-APR-00:10 | 5055.67 | 21-APR-16:17 | 5055.67 | 21-APR-16:17 | 84.84 | 18-APR-18:30 | 1432.28 | 21-APR-15:10 | 0.00 | 01-APR-00:10 |
| May | 0.617008E+10 | 0.167370E+10 | 695.27 | 0.602920E+10 | 0.140879E+09 | 0.00 | 0.51 | 19-MAY-17:10 | 0.00 | 01-MAY-07:35 | 6229.46 | 19-MAY-17:17 | 6229.46 | 19-MAY-17:17 | 660.34 | 24-MAY-13:30 | 1791.26 | 19-MAY-17:03 | 0.00 | 01-MAY-00:10 |
| June | 0.865832E+10 | 0.240962E+10 | 720.00 | 0.837566E+10 | 0.282665E+09 | 0.00 | 0.62 | 15-JUN-17:00 | 0.01 | 12-JUN-05:05 | 7216.39 | 15-JUN-17:00 | 7216.39 | 15-JUN-17:00 | 1004.94 | 19-JUN-19:00 | 2146.71 | 15-JUN-17:00 | 0.00 | 01-JUN-00:10 |
| July | 0.979870E+10 | 0.263264E+10 | 744.00 | 0.834214E+10 | 0.145656E+10 | 0.00 | 0.54 | 26-JUL-17:40 | 0.03 | 05-JUL-06:00 | 6932.42 | 27-JUL-17:20 | 6436.05 | 26-JUL-17:40 | 1435.41 | 20-JUL-16:12 | 1975.61 | 26-JUL-17:30 | 0.00 | 01-JUL-00:10 |
| August | 0.805177E+10 | 0.217239E+10 | 742.81 | 0.724009E+10 | 0.811685E+09 | 0.00 | 0.51 | 07-AUG-16:10 | 0.00 | 17-AUG-05:30 | 6161.14 | 06-AUG-17:30 | 6159.82 | 07-AUG-16:04 | 922.87 | 02-AUG-07:00 | 1847.13 | 07-AUG-16:04 | 0.00 | 01-AUG-00:10 |
| September | 0.595247E+10 | 0.157792E+10 | 696.79 | 0.529253E+10 | 0.659939E+09 | 0.00 | 0.41 | 18-SEP-16:40 | 0.00 | 05-SEP-05:15 | 5169.69 | 01-SEP-16:13 | 5023.20 | 18-SEP-16:40 | 894.69 | 22-SEP-09:50 | 1461.17 | 01-SEP-16:13 | 0.00 | 01-SEP-00:10 |
| October | 0.244049E+10 | 0.642134E+09 | 452.96 | 0.224990E+10 | 0.190593E+09 | 0.00 | 0.39 | 05-OCT-16:20 | 0.00 | 01-OCT-03:20 | 4983.91 | 05-OCT-16:20 | 4803.70 | 05-OCT-16:17 | 757.12 | 04-OCT-10:40 | 1367.22 | 05-OCT-16:10 | 0.00 | 01-OCT-00:10 |
| November | 49122393.64 | 12982097.09 | 25.83 | 48938350.69 | 184042.94 | 0.00 | 0.13 | 03-NOV-16:10 | 0.00 | 01-NOV-00:10 | 1576.72 | 03-NOV-16:05 | 1576.72 | 03-NOV-16:05 | 18.47 | 03-NOV-14:00 | 411.86 | 03-NOV-16:10 | 0.00 | 01-NOV-00:10 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.441392E+11 | 0.119357E+11 | 4637.02 | 0.405924E+11 | 0.354677E+10 | 0.00 | ||||||||||||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | -0.0 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Maximum of Months | 0.979870E+10 | 0.263264E+10 | 744.00 | 0.837566E+10 | 0.145656E+10 | 0.00 | 0.62 | 0.03 | 7216.39 | 7216.39 | 1435.41 | 2146.71 | 0.00 |
Report: DXReportMonthly
For: SPLIT MSE COOLING COIL
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.124328E+09 | 33070471.74 | 57.80 | 0.124328E+09 | 0.00 | 0.00 | 0.15 | 12-JAN-15:00 | 0.00 | 01-JAN-00:10 | 1815.13 | 12-JAN-15:00 | 1815.13 | 12-JAN-15:00 | 0.00 | 12-JAN-13:50 | 476.74 | 12-JAN-15:00 | 0.00 | 01-JAN-00:10 |
| February | 0.530410E+09 | 0.140117E+09 | 125.75 | 0.530410E+09 | 0.00 | 0.00 | 0.27 | 20-FEB-15:00 | 0.00 | 01-FEB-00:10 | 3143.01 | 20-FEB-15:00 | 3143.01 | 20-FEB-15:00 | 0.00 | 20-FEB-15:00 | 816.09 | 20-FEB-15:00 | 0.00 | 01-FEB-00:10 |
| March | 0.905959E+09 | 0.239878E+09 | 225.61 | 0.905959E+09 | 0.00 | 0.00 | 0.25 | 16-MAR-14:10 | 0.00 | 01-MAR-00:10 | 2986.48 | 16-MAR-14:10 | 2986.48 | 16-MAR-14:10 | 0.00 | 06-MAR-11:30 | 776.99 | 16-MAR-14:10 | 0.00 | 01-MAR-00:10 |
| April | 0.386004E+10 | 0.103192E+10 | 549.10 | 0.385378E+10 | 6255319.45 | 0.00 | 0.46 | 21-APR-14:10 | 0.00 | 01-APR-00:10 | 5305.20 | 21-APR-14:20 | 5305.20 | 21-APR-14:20 | 148.24 | 29-APR-09:40 | 1499.31 | 21-APR-14:20 | 0.00 | 01-APR-00:10 |
| May | 0.645263E+10 | 0.174390E+10 | 708.64 | 0.630599E+10 | 0.146646E+09 | 0.00 | 0.47 | 19-MAY-14:00 | 0.00 | 01-MAY-07:35 | 5493.70 | 19-MAY-14:00 | 5493.70 | 19-MAY-14:00 | 665.00 | 28-MAY-09:20 | 1605.22 | 19-MAY-14:00 | 0.00 | 01-MAY-00:10 |
| June | 0.867090E+10 | 0.240600E+10 | 720.00 | 0.838361E+10 | 0.287290E+09 | 0.00 | 0.55 | 15-JUN-16:04 | 0.01 | 12-JUN-05:05 | 5973.62 | 05-JUN-17:00 | 5973.62 | 05-JUN-17:00 | 954.89 | 19-JUN-19:00 | 1812.53 | 05-JUN-17:00 | 0.00 | 01-JUN-00:10 |
| July | 0.995636E+10 | 0.266560E+10 | 744.00 | 0.847734E+10 | 0.147901E+10 | 0.00 | 0.51 | 03-JUL-17:00 | 0.05 | 05-JUL-06:00 | 5947.31 | 27-JUL-14:10 | 5849.11 | 03-JUL-17:00 | 1418.95 | 20-JUL-09:10 | 1786.93 | 03-JUL-17:00 | 0.00 | 01-JUL-00:10 |
| August | 0.874878E+10 | 0.234626E+10 | 742.89 | 0.789874E+10 | 0.850042E+09 | 0.00 | 0.48 | 07-AUG-16:10 | 0.00 | 17-AUG-05:15 | 5549.95 | 07-AUG-16:04 | 5549.95 | 07-AUG-16:04 | 1120.41 | 02-AUG-07:40 | 1671.75 | 07-AUG-16:04 | 0.00 | 01-AUG-00:10 |
| September | 0.755948E+10 | 0.198429E+10 | 710.26 | 0.680012E+10 | 0.759360E+09 | 0.00 | 0.48 | 19-SEP-14:00 | 0.00 | 11-SEP-05:15 | 5645.07 | 19-SEP-13:50 | 5645.07 | 19-SEP-13:50 | 1253.07 | 09-SEP-09:30 | 1620.52 | 19-SEP-14:00 | 0.00 | 01-SEP-00:10 |
| October | 0.444110E+10 | 0.115160E+10 | 584.86 | 0.418437E+10 | 0.256731E+09 | 0.00 | 0.46 | 01-OCT-15:10 | 0.00 | 01-OCT-06:00 | 5476.40 | 05-OCT-11:30 | 5391.03 | 01-OCT-15:10 | 984.09 | 04-OCT-10:40 | 1527.48 | 01-OCT-15:10 | 0.00 | 01-OCT-00:10 |
| November | 0.125667E+10 | 0.330318E+09 | 268.72 | 0.125389E+10 | 2782517.15 | 0.00 | 0.32 | 09-NOV-14:00 | 0.00 | 01-NOV-00:10 | 3844.95 | 09-NOV-14:00 | 3844.95 | 09-NOV-14:00 | 134.28 | 03-NOV-11:50 | 982.65 | 09-NOV-14:00 | 0.00 | 01-NOV-00:10 |
| December | 25011021.75 | 6706472.24 | 18.57 | 25011021.75 | 0.00 | 0.00 | 0.09 | 16-DEC-15:10 | 0.00 | 01-DEC-00:10 | 992.77 | 16-DEC-15:10 | 992.77 | 16-DEC-15:10 | 0.00 | 16-DEC-14:20 | 265.02 | 16-DEC-15:10 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.525317E+11 | 0.140797E+11 | 5456.20 | 0.487436E+11 | 0.378812E+10 | 0.00 | ||||||||||||||
| Minimum of Months | 25011021.75 | 6706472.24 | 18.57 | 25011021.75 | 0.00 | 0.00 | 0.09 | 0.00 | 992.77 | 992.77 | 0.00 | 265.02 | 0.00 | |||||||
| Maximum of Months | 0.995636E+10 | 0.266560E+10 | 744.00 | 0.847734E+10 | 0.147901E+10 | 0.00 | 0.55 | 0.05 | 5973.62 | 5973.62 | 1418.95 | 1812.53 | 0.00 |
Report: DXReportMonthly
For: SPLIT MNE COOLING COIL
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| February | 14634576.07 | 3939003.68 | 14.00 | 14634576.07 | 0.00 | 0.00 | 0.05 | 21-FEB-17:10 | 0.00 | 01-FEB-00:10 | 550.19 | 21-FEB-17:10 | 550.19 | 21-FEB-17:10 | 0.00 | 21-FEB-17:10 | 147.71 | 21-FEB-17:10 | 0.00 | 01-FEB-00:10 |
| March | 0.126209E+09 | 33846793.15 | 68.97 | 0.126209E+09 | 0.00 | 0.00 | 0.11 | 22-MAR-16:10 | 0.00 | 01-MAR-00:10 | 1283.31 | 22-MAR-16:10 | 1283.31 | 22-MAR-16:10 | 0.00 | 21-MAR-17:00 | 341.20 | 22-MAR-16:10 | 0.00 | 01-MAR-00:10 |
| April | 0.292326E+10 | 0.787317E+09 | 503.53 | 0.291846E+10 | 4803416.92 | 0.00 | 0.41 | 21-APR-15:10 | 0.00 | 01-APR-00:10 | 4704.44 | 21-APR-15:10 | 4704.44 | 21-APR-15:10 | 97.05 | 29-APR-09:20 | 1333.97 | 21-APR-15:10 | 0.00 | 01-APR-00:10 |
| May | 0.624666E+10 | 0.168862E+10 | 705.69 | 0.609932E+10 | 0.147343E+09 | 0.00 | 0.45 | 19-MAY-17:10 | 0.00 | 01-MAY-07:35 | 5131.58 | 19-MAY-17:05 | 5131.58 | 19-MAY-17:05 | 628.38 | 24-MAY-13:30 | 1490.69 | 19-MAY-17:00 | 0.00 | 01-MAY-00:10 |
| June | 0.876405E+10 | 0.242735E+10 | 720.00 | 0.847236E+10 | 0.291691E+09 | 0.00 | 0.57 | 15-JUN-17:00 | 0.01 | 12-JUN-05:05 | 6124.07 | 15-JUN-17:00 | 6124.07 | 15-JUN-17:00 | 975.13 | 19-JUN-19:00 | 1838.73 | 15-JUN-17:00 | 0.00 | 01-JUN-00:10 |
| July | 0.989448E+10 | 0.264629E+10 | 744.00 | 0.841607E+10 | 0.147841E+10 | 0.00 | 0.52 | 03-JUL-17:00 | 0.05 | 05-JUL-06:00 | 5997.36 | 26-JUL-18:00 | 5851.94 | 03-JUL-17:00 | 1474.85 | 21-JUL-07:00 | 1785.23 | 03-JUL-17:00 | 0.00 | 01-JUL-00:10 |
| August | 0.814421E+10 | 0.218725E+10 | 742.49 | 0.731154E+10 | 0.832671E+09 | 0.00 | 0.47 | 07-AUG-16:10 | 0.00 | 17-AUG-05:05 | 5349.97 | 07-AUG-18:00 | 5349.97 | 07-AUG-18:00 | 1191.07 | 02-AUG-07:40 | 1600.67 | 07-AUG-16:10 | 0.00 | 01-AUG-00:10 |
| September | 0.599796E+10 | 0.158368E+10 | 697.78 | 0.531056E+10 | 0.687397E+09 | 0.00 | 0.36 | 01-SEP-16:03 | 0.00 | 05-SEP-05:03 | 4332.44 | 15-SEP-16:10 | 4026.85 | 02-SEP-16:20 | 1006.09 | 09-SEP-09:20 | 1207.43 | 01-SEP-16:03 | 0.00 | 01-SEP-00:10 |
| October | 0.229526E+10 | 0.603926E+09 | 456.16 | 0.211305E+10 | 0.182215E+09 | 0.00 | 0.33 | 03-OCT-14:10 | 0.00 | 01-OCT-02:50 | 3974.88 | 03-OCT-15:10 | 3786.97 | 05-OCT-16:03 | 848.97 | 04-OCT-10:30 | 1128.69 | 03-OCT-14:10 | 0.00 | 01-OCT-00:10 |
| November | 39366854.97 | 10451887.95 | 27.17 | 39259034.11 | 107820.86 | 0.00 | 0.08 | 09-NOV-15:10 | 0.00 | 01-NOV-00:10 | 923.57 | 09-NOV-15:10 | 923.57 | 09-NOV-15:10 | 14.70 | 03-NOV-13:30 | 244.38 | 09-NOV-15:10 | 0.00 | 01-NOV-00:10 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.444461E+11 | 0.119727E+11 | 4679.79 | 0.408215E+11 | 0.362464E+10 | 0.00 | ||||||||||||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Maximum of Months | 0.989448E+10 | 0.264629E+10 | 744.00 | 0.847236E+10 | 0.147841E+10 | 0.00 | 0.57 | 0.05 | 6124.07 | 6124.07 | 1474.85 | 1838.73 | 0.00 |
Report: DXReportMonthly
For: SPLIT MN1 COOLING COIL
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| February | 10387782.80 | 2796922.75 | 13.17 | 10387782.80 | -0.0 | 0.00 | 0.05 | 21-FEB-17:05 | 0.00 | 01-FEB-00:10 | 472.79 | 21-FEB-17:05 | 472.79 | 21-FEB-17:05 | 0.00 | 21-FEB-17:20 | 126.96 | 21-FEB-17:05 | 0.00 | 01-FEB-00:10 |
| March | 0.132104E+09 | 35411679.16 | 83.44 | 0.132100E+09 | 3949.52 | 0.00 | 0.11 | 22-MAR-16:05 | 0.00 | 01-MAR-00:10 | 1148.06 | 22-MAR-16:05 | 1148.06 | 22-MAR-16:05 | 3.27 | 10-MAR-23:00 | 305.20 | 22-MAR-16:05 | 0.00 | 01-MAR-00:10 |
| April | 0.236148E+10 | 0.637656E+09 | 518.76 | 0.235688E+10 | 4598492.45 | 0.00 | 0.35 | 21-APR-15:10 | 0.00 | 01-APR-00:10 | 3530.23 | 21-APR-16:15 | 3530.23 | 21-APR-16:15 | 76.50 | 18-APR-21:00 | 1008.71 | 21-APR-15:10 | 0.00 | 01-APR-00:10 |
| May | 0.499850E+10 | 0.135597E+10 | 722.96 | 0.487251E+10 | 0.125995E+09 | 0.00 | 0.40 | 19-MAY-17:17 | 0.00 | 01-MAY-07:35 | 4063.12 | 19-MAY-17:25 | 4063.12 | 19-MAY-17:25 | 500.05 | 24-MAY-13:30 | 1185.78 | 19-MAY-17:03 | 0.00 | 01-MAY-00:10 |
| June | 0.692757E+10 | 0.192690E+10 | 720.00 | 0.667609E+10 | 0.251482E+09 | 0.00 | 0.50 | 15-JUN-17:00 | 0.03 | 12-JUN-05:05 | 4795.27 | 15-JUN-17:03 | 4795.27 | 15-JUN-17:03 | 774.07 | 19-JUN-19:00 | 1453.03 | 15-JUN-17:00 | 0.00 | 01-JUN-00:10 |
| July | 0.801575E+10 | 0.214830E+10 | 744.00 | 0.674640E+10 | 0.126934E+10 | 0.00 | 0.46 | 03-JUL-17:00 | 0.05 | 05-JUL-06:00 | 4781.48 | 26-JUL-18:00 | 4573.88 | 03-JUL-17:00 | 1243.82 | 20-JUL-16:25 | 1408.43 | 03-JUL-17:00 | 0.00 | 01-JUL-00:10 |
| August | 0.662864E+10 | 0.178332E+10 | 744.00 | 0.590007E+10 | 0.728571E+09 | 0.00 | 0.42 | 07-AUG-16:04 | 0.01 | 31-AUG-06:00 | 4298.46 | 07-AUG-18:00 | 4290.82 | 07-AUG-18:00 | 872.90 | 02-AUG-07:00 | 1278.91 | 07-AUG-16:04 | 0.00 | 01-AUG-00:10 |
| September | 0.495316E+10 | 0.130930E+10 | 710.44 | 0.434861E+10 | 0.604553E+09 | 0.00 | 0.33 | 01-SEP-16:03 | 0.00 | 11-SEP-05:07 | 3445.06 | 15-SEP-16:10 | 3280.80 | 20-SEP-17:03 | 802.47 | 22-SEP-09:40 | 984.40 | 01-SEP-16:03 | 0.00 | 01-SEP-00:10 |
| October | 0.218651E+10 | 0.574352E+09 | 560.06 | 0.199837E+10 | 0.188142E+09 | 0.00 | 0.30 | 05-OCT-16:03 | 0.00 | 01-OCT-07:12 | 3287.75 | 04-OCT-16:17 | 3081.58 | 05-OCT-16:03 | 691.73 | 04-OCT-10:40 | 914.24 | 03-OCT-14:10 | 0.00 | 01-OCT-00:10 |
| November | 46801837.61 | 12402560.03 | 36.33 | 46419415.81 | 382421.80 | 0.00 | 0.10 | 03-NOV-16:10 | 0.00 | 01-NOV-00:10 | 1015.99 | 03-NOV-16:10 | 1015.99 | 03-NOV-16:10 | 37.58 | 02-NOV-18:50 | 266.49 | 03-NOV-16:10 | 0.00 | 01-NOV-00:10 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.362609E+11 | 0.978640E+10 | 4853.15 | 0.330878E+11 | 0.317307E+10 | 0.00 | ||||||||||||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | -0.0 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Maximum of Months | 0.801575E+10 | 0.214830E+10 | 744.00 | 0.674640E+10 | 0.126934E+10 | 0.00 | 0.50 | 0.05 | 4795.27 | 4795.27 | 1243.82 | 1453.03 | 0.00 |
Report: DXReportMonthly
For: SPLIT MN2 COOLING COIL
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| February | 11275099.49 | 3035342.10 | 13.50 | 11275099.49 | 0.00 | 0.00 | 0.05 | 21-FEB-17:05 | 0.00 | 01-FEB-00:10 | 483.09 | 21-FEB-17:05 | 483.09 | 21-FEB-17:05 | 0.00 | 22-FEB-16:10 | 129.71 | 21-FEB-17:05 | 0.00 | 01-FEB-00:10 |
| March | 0.135776E+09 | 36394945.04 | 85.25 | 0.135772E+09 | 4709.05 | 0.00 | 0.11 | 22-MAR-16:10 | 0.00 | 01-MAR-00:10 | 1157.89 | 22-MAR-16:10 | 1157.89 | 22-MAR-16:10 | 3.60 | 10-MAR-23:00 | 307.76 | 22-MAR-16:10 | 0.00 | 01-MAR-00:10 |
| April | 0.237302E+10 | 0.640701E+09 | 520.48 | 0.236842E+10 | 4603510.88 | 0.00 | 0.35 | 21-APR-15:10 | 0.00 | 01-APR-00:10 | 3528.13 | 21-APR-16:15 | 3528.13 | 21-APR-16:15 | 76.31 | 18-APR-21:00 | 1009.53 | 21-APR-15:10 | 0.00 | 01-APR-00:10 |
| May | 0.500382E+10 | 0.135731E+10 | 723.16 | 0.487772E+10 | 0.126097E+09 | 0.00 | 0.40 | 19-MAY-17:17 | 0.00 | 01-MAY-07:35 | 4048.36 | 19-MAY-17:17 | 4048.36 | 19-MAY-17:17 | 500.23 | 24-MAY-13:30 | 1182.01 | 19-MAY-17:03 | 0.00 | 01-MAY-00:10 |
| June | 0.693220E+10 | 0.192804E+10 | 720.00 | 0.668064E+10 | 0.251563E+09 | 0.00 | 0.50 | 15-JUN-17:00 | 0.03 | 12-JUN-05:05 | 4781.29 | 15-JUN-17:03 | 4781.29 | 15-JUN-17:03 | 773.46 | 19-JUN-19:00 | 1449.21 | 15-JUN-17:00 | 0.00 | 01-JUN-00:10 |
| July | 0.801937E+10 | 0.214915E+10 | 744.00 | 0.674976E+10 | 0.126961E+10 | 0.00 | 0.46 | 03-JUL-17:00 | 0.05 | 05-JUL-06:00 | 4769.07 | 26-JUL-18:00 | 4578.93 | 03-JUL-17:00 | 1243.80 | 20-JUL-16:25 | 1409.75 | 03-JUL-17:00 | 0.00 | 01-JUL-00:10 |
| August | 0.663253E+10 | 0.178424E+10 | 744.00 | 0.590366E+10 | 0.728868E+09 | 0.00 | 0.42 | 07-AUG-16:04 | 0.01 | 31-AUG-06:00 | 4284.01 | 07-AUG-18:00 | 4276.42 | 07-AUG-18:00 | 875.67 | 02-AUG-07:00 | 1275.94 | 07-AUG-16:04 | 0.00 | 01-AUG-00:10 |
| September | 0.495570E+10 | 0.130991E+10 | 710.34 | 0.435074E+10 | 0.604957E+09 | 0.00 | 0.33 | 01-SEP-16:03 | 0.00 | 11-SEP-05:03 | 3446.48 | 15-SEP-16:10 | 3267.48 | 20-SEP-17:03 | 802.94 | 22-SEP-09:40 | 982.41 | 01-SEP-16:03 | 0.00 | 01-SEP-00:10 |
| October | 0.218245E+10 | 0.573314E+09 | 559.42 | 0.199516E+10 | 0.187295E+09 | 0.00 | 0.30 | 03-OCT-15:10 | 0.00 | 01-OCT-07:12 | 3270.24 | 04-OCT-16:17 | 3069.89 | 05-OCT-16:03 | 693.55 | 04-OCT-10:40 | 914.73 | 03-OCT-14:10 | 0.00 | 01-OCT-00:10 |
| November | 46620366.92 | 12356333.49 | 35.49 | 46274337.78 | 346029.14 | 0.00 | 0.10 | 03-NOV-16:10 | 0.00 | 01-NOV-00:10 | 999.72 | 03-NOV-16:10 | 999.72 | 03-NOV-16:10 | 31.10 | 02-NOV-18:50 | 262.28 | 03-NOV-16:10 | 0.00 | 01-NOV-00:10 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.362928E+11 | 0.979446E+10 | 4855.64 | 0.331194E+11 | 0.317334E+10 | 0.00 | ||||||||||||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Maximum of Months | 0.801937E+10 | 0.214915E+10 | 744.00 | 0.674976E+10 | 0.126961E+10 | 0.00 | 0.50 | 0.05 | 4781.29 | 4781.29 | 1243.80 | 1449.21 | 0.00 |
Report: DXReportMonthly
For: SPLIT MS1 COOLING COIL
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.390605E+09 | 0.103668E+09 | 163.87 | 0.390605E+09 | 0.00 | 0.00 | 0.21 | 12-JAN-15:00 | 0.00 | 01-JAN-00:10 | 2209.31 | 12-JAN-15:00 | 2209.31 | 12-JAN-15:00 | 0.00 | 01-JAN-12:00 | 575.47 | 12-JAN-15:00 | 0.00 | 01-JAN-00:10 |
| February | 0.698667E+09 | 0.184484E+09 | 198.78 | 0.698667E+09 | 0.00 | 0.00 | 0.29 | 20-FEB-15:00 | 0.00 | 01-FEB-00:10 | 3075.05 | 20-FEB-15:00 | 3075.05 | 20-FEB-15:00 | 0.00 | 06-FEB-14:40 | 795.39 | 20-FEB-15:00 | 0.00 | 01-FEB-00:10 |
| March | 0.104374E+10 | 0.276155E+09 | 300.34 | 0.104372E+10 | 16721.69 | 0.00 | 0.27 | 16-MAR-15:10 | 0.00 | 01-MAR-00:10 | 2842.45 | 16-MAR-15:10 | 2842.45 | 16-MAR-15:10 | 6.75 | 10-MAR-23:00 | 737.66 | 16-MAR-15:10 | 0.00 | 01-MAR-00:10 |
| April | 0.333032E+10 | 0.892193E+09 | 592.43 | 0.332433E+10 | 5989000.39 | 0.00 | 0.40 | 21-APR-14:10 | 0.00 | 01-APR-00:10 | 4100.92 | 21-APR-15:10 | 4100.92 | 21-APR-15:10 | 112.61 | 29-APR-09:50 | 1166.13 | 21-APR-15:10 | 0.00 | 01-APR-00:10 |
| May | 0.520749E+10 | 0.141264E+10 | 724.05 | 0.508214E+10 | 0.125345E+09 | 0.00 | 0.40 | 19-MAY-17:05 | 0.00 | 01-MAY-07:35 | 4138.38 | 19-MAY-14:00 | 4138.38 | 19-MAY-14:00 | 503.07 | 24-MAY-13:30 | 1222.36 | 19-MAY-14:00 | 0.00 | 01-MAY-00:10 |
| June | 0.683418E+10 | 0.190512E+10 | 720.00 | 0.658732E+10 | 0.246859E+09 | 0.00 | 0.48 | 15-JUN-16:08 | 0.02 | 13-JUN-05:40 | 4632.82 | 05-JUN-17:00 | 4632.82 | 05-JUN-17:00 | 752.00 | 19-JUN-19:00 | 1420.57 | 05-JUN-17:00 | 0.00 | 01-JUN-00:10 |
| July | 0.807759E+10 | 0.216783E+10 | 744.00 | 0.680770E+10 | 0.126989E+10 | 0.00 | 0.45 | 03-JUL-17:00 | 0.06 | 05-JUL-06:00 | 4669.39 | 26-JUL-18:00 | 4572.35 | 03-JUL-17:00 | 1190.24 | 20-JUL-16:02 | 1410.32 | 03-JUL-17:00 | 0.00 | 01-JUL-00:10 |
| August | 0.723828E+10 | 0.194516E+10 | 744.00 | 0.648933E+10 | 0.748942E+09 | 0.00 | 0.44 | 07-AUG-16:10 | 0.02 | 17-AUG-06:00 | 4449.91 | 07-AUG-16:10 | 4449.91 | 07-AUG-16:10 | 827.53 | 02-AUG-07:00 | 1350.38 | 07-AUG-16:10 | 0.00 | 01-AUG-00:10 |
| September | 0.653574E+10 | 0.171784E+10 | 719.21 | 0.585104E+10 | 0.684695E+09 | 0.00 | 0.45 | 19-SEP-14:10 | 0.00 | 24-SEP-07:00 | 4710.63 | 19-SEP-14:10 | 4710.63 | 19-SEP-14:10 | 966.29 | 09-SEP-09:40 | 1357.97 | 19-SEP-14:00 | 0.00 | 01-SEP-00:10 |
| October | 0.445216E+10 | 0.115322E+10 | 690.85 | 0.418452E+10 | 0.267646E+09 | 0.00 | 0.44 | 01-OCT-15:10 | 0.00 | 07-OCT-00:20 | 4736.03 | 18-OCT-13:20 | 4605.70 | 01-OCT-15:10 | 843.51 | 04-OCT-10:50 | 1308.68 | 01-OCT-15:10 | 0.00 | 01-OCT-00:10 |
| November | 0.169126E+10 | 0.443382E+09 | 372.45 | 0.168615E+10 | 5106058.66 | 0.00 | 0.34 | 09-NOV-14:00 | 0.00 | 01-NOV-02:50 | 3639.94 | 09-NOV-14:00 | 3639.94 | 09-NOV-14:00 | 135.91 | 03-NOV-11:50 | 927.76 | 09-NOV-14:00 | 0.00 | 01-NOV-00:10 |
| December | 0.187934E+09 | 50260053.73 | 118.95 | 0.187934E+09 | -0.0 | 0.00 | 0.16 | 16-DEC-14:40 | 0.00 | 01-DEC-00:10 | 1710.40 | 16-DEC-14:40 | 1710.40 | 16-DEC-14:40 | 0.00 | 06-DEC-13:20 | 451.14 | 16-DEC-14:40 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.456880E+11 | 0.122520E+11 | 6088.92 | 0.423335E+11 | 0.335449E+10 | 0.00 | ||||||||||||||
| Minimum of Months | 0.187934E+09 | 50260053.73 | 118.95 | 0.187934E+09 | -0.0 | 0.00 | 0.16 | 0.00 | 1710.40 | 1710.40 | 0.00 | 451.14 | 0.00 | |||||||
| Maximum of Months | 0.807759E+10 | 0.216783E+10 | 744.00 | 0.680770E+10 | 0.126989E+10 | 0.00 | 0.48 | 0.06 | 4736.03 | 4710.63 | 1190.24 | 1420.57 | 0.00 |
Report: DXReportMonthly
For: SPLIT MS2 COOLING COIL
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.390922E+09 | 0.103749E+09 | 163.46 | 0.390922E+09 | -0.0 | 0.00 | 0.21 | 12-JAN-15:00 | 0.00 | 01-JAN-00:10 | 2209.59 | 12-JAN-15:00 | 2209.59 | 12-JAN-15:00 | 0.00 | 12-JAN-15:40 | 575.51 | 12-JAN-15:00 | 0.00 | 01-JAN-00:10 |
| February | 0.707885E+09 | 0.186902E+09 | 200.86 | 0.707885E+09 | 0.00 | 0.00 | 0.29 | 20-FEB-15:00 | 0.00 | 01-FEB-00:10 | 3087.17 | 20-FEB-15:00 | 3087.17 | 20-FEB-15:00 | 0.00 | 06-FEB-13:00 | 798.35 | 20-FEB-15:00 | 0.00 | 01-FEB-00:10 |
| March | 0.105288E+10 | 0.278555E+09 | 302.03 | 0.105286E+10 | 16945.24 | 0.00 | 0.27 | 16-MAR-15:10 | 0.00 | 01-MAR-00:10 | 2842.73 | 16-MAR-15:10 | 2842.73 | 16-MAR-15:10 | 6.79 | 10-MAR-23:00 | 737.69 | 16-MAR-15:10 | 0.00 | 01-MAR-00:10 |
| April | 0.334124E+10 | 0.895007E+09 | 593.21 | 0.333524E+10 | 5996687.62 | 0.00 | 0.40 | 21-APR-14:20 | 0.00 | 01-APR-00:10 | 4105.61 | 21-APR-15:10 | 4105.61 | 21-APR-15:10 | 113.32 | 29-APR-10:00 | 1167.81 | 21-APR-14:20 | 0.00 | 01-APR-00:10 |
| May | 0.521286E+10 | 0.141398E+10 | 724.53 | 0.508742E+10 | 0.125445E+09 | 0.00 | 0.40 | 19-MAY-14:00 | 0.00 | 01-MAY-07:35 | 4146.43 | 19-MAY-14:00 | 4146.43 | 19-MAY-14:00 | 502.79 | 24-MAY-13:30 | 1224.50 | 19-MAY-14:00 | 0.00 | 01-MAY-00:10 |
| June | 0.683889E+10 | 0.190628E+10 | 720.00 | 0.659195E+10 | 0.246941E+09 | 0.00 | 0.48 | 15-JUN-16:04 | 0.02 | 13-JUN-05:40 | 4622.38 | 05-JUN-17:00 | 4622.38 | 05-JUN-17:00 | 751.02 | 19-JUN-19:00 | 1417.46 | 05-JUN-17:00 | 0.00 | 01-JUN-00:10 |
| July | 0.808129E+10 | 0.216869E+10 | 744.00 | 0.681114E+10 | 0.127016E+10 | 0.00 | 0.46 | 03-JUL-17:00 | 0.06 | 05-JUL-06:00 | 4657.74 | 26-JUL-18:00 | 4576.82 | 03-JUL-17:00 | 1190.72 | 20-JUL-16:02 | 1411.48 | 03-JUL-17:00 | 0.00 | 01-JUL-00:10 |
| August | 0.724212E+10 | 0.194604E+10 | 744.00 | 0.649292E+10 | 0.749202E+09 | 0.00 | 0.44 | 07-AUG-16:06 | 0.02 | 17-AUG-06:00 | 4452.15 | 29-AUG-13:00 | 4441.78 | 07-AUG-16:04 | 830.40 | 02-AUG-07:00 | 1347.83 | 07-AUG-16:04 | 0.00 | 01-AUG-00:10 |
| September | 0.653784E+10 | 0.171826E+10 | 718.87 | 0.585287E+10 | 0.684973E+09 | 0.00 | 0.45 | 19-SEP-14:00 | 0.00 | 24-SEP-07:00 | 4715.80 | 19-SEP-14:00 | 4715.80 | 19-SEP-14:00 | 970.30 | 09-SEP-09:40 | 1359.89 | 19-SEP-14:00 | 0.00 | 01-SEP-00:10 |
| October | 0.444651E+10 | 0.115171E+10 | 690.21 | 0.417946E+10 | 0.267047E+09 | 0.00 | 0.44 | 01-OCT-15:10 | 0.00 | 07-OCT-00:20 | 4744.59 | 18-OCT-13:20 | 4602.66 | 01-OCT-15:10 | 844.67 | 04-OCT-10:50 | 1307.75 | 01-OCT-15:10 | 0.00 | 01-OCT-00:10 |
| November | 0.169334E+10 | 0.443901E+09 | 371.61 | 0.168830E+10 | 5047113.33 | 0.00 | 0.34 | 09-NOV-14:00 | 0.00 | 01-NOV-02:40 | 3648.73 | 09-NOV-14:00 | 3648.73 | 09-NOV-14:00 | 136.13 | 03-NOV-11:50 | 929.83 | 09-NOV-14:00 | 0.00 | 01-NOV-00:10 |
| December | 0.191090E+09 | 51096572.98 | 118.60 | 0.191090E+09 | -0.0 | 0.00 | 0.17 | 16-DEC-14:50 | 0.00 | 01-DEC-00:10 | 1725.33 | 16-DEC-14:50 | 1725.33 | 16-DEC-14:50 | 0.00 | 17-DEC-13:30 | 454.97 | 16-DEC-14:50 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.457369E+11 | 0.122642E+11 | 6091.40 | 0.423820E+11 | 0.335482E+10 | 0.00 | ||||||||||||||
| Minimum of Months | 0.191090E+09 | 51096572.98 | 118.60 | 0.191090E+09 | -0.0 | 0.00 | 0.17 | 0.00 | 1725.33 | 1725.33 | 0.00 | 454.97 | 0.00 | |||||||
| Maximum of Months | 0.808129E+10 | 0.216869E+10 | 744.00 | 0.681114E+10 | 0.127016E+10 | 0.00 | 0.48 | 0.06 | 4744.59 | 4715.80 | 1190.72 | 1417.46 | 0.00 |
Report: DXReportMonthly
For: SPLIT TSW COOLING COIL
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.141106E+09 | 37498841.81 | 85.07 | 0.141106E+09 | 0.00 | 0.00 | 0.24 | 12-JAN-15:10 | 0.00 | 01-JAN-00:10 | 1732.87 | 12-JAN-15:10 | 1732.87 | 12-JAN-15:10 | 0.00 | 12-JAN-15:30 | 448.91 | 12-JAN-15:10 | 0.00 | 01-JAN-00:10 |
| February | 0.304679E+09 | 80189713.70 | 105.25 | 0.304679E+09 | -0.0 | 0.00 | 0.32 | 20-FEB-15:30 | 0.00 | 01-FEB-00:10 | 2261.10 | 20-FEB-15:30 | 2261.10 | 20-FEB-15:30 | 0.00 | 06-FEB-14:10 | 582.29 | 20-FEB-15:30 | 0.00 | 01-FEB-00:10 |
| March | 0.481318E+09 | 0.126783E+09 | 153.72 | 0.481318E+09 | 0.00 | 0.00 | 0.34 | 14-MAR-16:15 | 0.00 | 01-MAR-00:10 | 2404.80 | 14-MAR-16:15 | 2404.80 | 14-MAR-16:15 | 0.00 | 14-MAR-16:50 | 621.69 | 14-MAR-16:15 | 0.00 | 01-MAR-00:10 |
| April | 0.190515E+10 | 0.510436E+09 | 383.33 | 0.190354E+10 | 1609084.79 | 0.00 | 0.54 | 21-APR-15:10 | 0.00 | 01-APR-00:10 | 3780.36 | 21-APR-15:10 | 3780.36 | 21-APR-15:10 | 63.52 | 29-APR-10:00 | 1050.79 | 21-APR-15:10 | 0.00 | 01-APR-00:10 |
| May | 0.339833E+10 | 0.923693E+09 | 587.32 | 0.333404E+10 | 64290856.30 | 0.00 | 0.59 | 19-MAY-16:40 | 0.00 | 01-MAY-02:00 | 4174.61 | 19-MAY-16:40 | 4174.61 | 19-MAY-16:40 | 418.76 | 24-MAY-13:30 | 1191.81 | 19-MAY-16:30 | 0.00 | 01-MAY-00:10 |
| June | 0.489570E+10 | 0.136873E+10 | 696.92 | 0.476326E+10 | 0.132434E+09 | 0.00 | 0.71 | 15-JUN-16:30 | 0.00 | 02-JUN-05:05 | 4698.93 | 15-JUN-16:40 | 4698.93 | 15-JUN-16:40 | 581.63 | 19-JUN-19:00 | 1387.99 | 05-JUN-17:00 | 0.00 | 01-JUN-00:10 |
| July | 0.558416E+10 | 0.150788E+10 | 740.62 | 0.482838E+10 | 0.755781E+09 | 0.00 | 0.62 | 02-JUL-16:00 | 0.00 | 05-JUL-03:00 | 4512.97 | 27-JUL-17:20 | 4326.19 | 02-JUL-16:01 | 796.67 | 21-JUL-11:30 | 1296.27 | 02-JUL-16:00 | 0.00 | 01-JUL-00:10 |
| August | 0.477189E+10 | 0.129096E+10 | 718.47 | 0.436803E+10 | 0.403864E+09 | 0.00 | 0.62 | 07-AUG-16:10 | 0.00 | 12-AUG-06:00 | 4333.21 | 07-AUG-16:10 | 4333.21 | 07-AUG-16:10 | 572.61 | 02-AUG-11:40 | 1276.90 | 07-AUG-16:10 | 0.00 | 01-AUG-00:10 |
| September | 0.388857E+10 | 0.102907E+10 | 606.67 | 0.355799E+10 | 0.330577E+09 | 0.00 | 0.58 | 19-SEP-16:10 | 0.00 | 02-SEP-05:40 | 4142.03 | 19-SEP-15:30 | 4142.03 | 19-SEP-15:30 | 612.50 | 09-SEP-10:00 | 1167.87 | 19-SEP-16:10 | 0.00 | 01-SEP-00:10 |
| October | 0.206650E+10 | 0.536572E+09 | 382.25 | 0.195948E+10 | 0.107024E+09 | 0.00 | 0.55 | 01-OCT-15:10 | 0.00 | 01-OCT-00:10 | 4029.63 | 05-OCT-16:10 | 3951.22 | 05-OCT-16:03 | 556.50 | 04-OCT-11:00 | 1095.34 | 01-OCT-15:10 | 0.00 | 01-OCT-00:10 |
| November | 0.558310E+09 | 0.146215E+09 | 175.18 | 0.557144E+09 | 1165686.85 | 0.00 | 0.36 | 09-NOV-15:10 | 0.00 | 01-NOV-00:10 | 2597.79 | 03-NOV-15:30 | 2597.79 | 03-NOV-15:30 | 67.74 | 02-NOV-15:20 | 658.32 | 09-NOV-15:10 | 0.00 | 01-NOV-00:10 |
| December | 90709521.82 | 24208240.12 | 65.31 | 90709521.82 | -0.0 | 0.00 | 0.18 | 16-DEC-15:30 | 0.00 | 01-DEC-00:10 | 1238.27 | 16-DEC-15:30 | 1238.27 | 16-DEC-15:30 | 0.00 | 30-DEC-15:10 | 325.94 | 16-DEC-15:30 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.280864E+11 | 0.758224E+10 | 4700.11 | 0.262897E+11 | 0.179675E+10 | 0.00 | ||||||||||||||
| Minimum of Months | 90709521.82 | 24208240.12 | 65.31 | 90709521.82 | -0.0 | 0.00 | 0.18 | 0.00 | 1238.27 | 1238.27 | 0.00 | 325.94 | 0.00 | |||||||
| Maximum of Months | 0.558416E+10 | 0.150788E+10 | 740.62 | 0.482838E+10 | 0.755781E+09 | 0.00 | 0.71 | 0.00 | 4698.93 | 4698.93 | 796.67 | 1387.99 | 0.00 |
Report: DXReportMonthly
For: SPLIT TNW COOLING COIL
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| February | 30159295.92 | 8070994.64 | 24.00 | 30159295.92 | 0.00 | 0.00 | 0.11 | 19-FEB-17:10 | 0.00 | 01-FEB-00:10 | 758.28 | 19-FEB-17:10 | 758.28 | 19-FEB-17:10 | 0.00 | 19-FEB-16:50 | 201.67 | 19-FEB-17:10 | 0.00 | 01-FEB-00:10 |
| March | 0.125231E+09 | 33418044.82 | 74.00 | 0.125231E+09 | 0.00 | 0.00 | 0.19 | 14-MAR-16:40 | 0.00 | 01-MAR-00:10 | 1292.11 | 14-MAR-16:40 | 1292.11 | 14-MAR-16:40 | 0.00 | 14-MAR-16:40 | 342.04 | 14-MAR-16:40 | 0.00 | 01-MAR-00:10 |
| April | 0.147505E+10 | 0.398733E+09 | 352.69 | 0.147385E+10 | 1200311.20 | 0.00 | 0.48 | 21-APR-15:10 | 0.00 | 01-APR-00:10 | 3376.65 | 21-APR-15:10 | 3376.65 | 21-APR-15:10 | 42.90 | 18-APR-18:20 | 946.23 | 21-APR-15:10 | 0.00 | 01-APR-00:10 |
| May | 0.328737E+10 | 0.894400E+09 | 586.83 | 0.322241E+10 | 64966812.97 | 0.00 | 0.59 | 19-MAY-17:00 | 0.00 | 01-MAY-01:50 | 4139.66 | 19-MAY-17:05 | 4139.66 | 19-MAY-17:05 | 415.53 | 24-MAY-13:30 | 1177.72 | 19-MAY-17:00 | 0.00 | 01-MAY-00:10 |
| June | 0.494307E+10 | 0.138033E+10 | 698.26 | 0.480761E+10 | 0.135458E+09 | 0.00 | 0.72 | 15-JUN-17:00 | 0.00 | 01-JUN-05:30 | 4825.56 | 15-JUN-17:00 | 4825.56 | 15-JUN-17:00 | 595.74 | 19-JUN-19:00 | 1411.90 | 15-JUN-17:00 | 0.00 | 01-JUN-00:10 |
| July | 0.555050E+10 | 0.149826E+10 | 740.61 | 0.479169E+10 | 0.758811E+09 | 0.00 | 0.62 | 26-JUL-17:30 | 0.00 | 05-JUL-02:50 | 4526.45 | 26-JUL-17:40 | 4306.55 | 06-JUL-17:00 | 785.54 | 20-JUL-16:25 | 1280.83 | 26-JUL-17:30 | 0.00 | 01-JUL-00:10 |
| August | 0.443353E+10 | 0.120286E+10 | 718.33 | 0.403663E+10 | 0.396901E+09 | 0.00 | 0.60 | 07-AUG-16:06 | 0.00 | 12-AUG-06:00 | 4155.47 | 07-AUG-16:04 | 4155.47 | 07-AUG-16:04 | 551.58 | 02-AUG-11:40 | 1228.52 | 07-AUG-16:06 | 0.00 | 01-AUG-00:10 |
| September | 0.305778E+10 | 0.816240E+09 | 587.52 | 0.276099E+10 | 0.296797E+09 | 0.00 | 0.48 | 01-SEP-16:13 | 0.00 | 02-SEP-05:30 | 3462.39 | 01-SEP-16:13 | 3320.89 | 18-SEP-16:30 | 516.04 | 22-SEP-10:10 | 969.17 | 01-SEP-16:03 | 0.00 | 01-SEP-00:10 |
| October | 0.107332E+10 | 0.283895E+09 | 299.13 | 0.994596E+09 | 78724048.21 | 0.00 | 0.45 | 05-OCT-16:10 | 0.00 | 01-OCT-00:10 | 3310.73 | 05-OCT-16:20 | 3209.93 | 05-OCT-16:08 | 439.03 | 04-OCT-11:00 | 901.35 | 05-OCT-16:10 | 0.00 | 01-OCT-00:10 |
| November | 30048566.73 | 7939093.01 | 20.83 | 30011737.80 | 36828.92 | 0.00 | 0.14 | 09-NOV-16:10 | 0.00 | 01-NOV-00:10 | 961.78 | 09-NOV-16:10 | 961.78 | 09-NOV-16:10 | 8.07 | 03-NOV-14:10 | 251.97 | 09-NOV-16:10 | 0.00 | 01-NOV-00:10 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.240061E+11 | 0.652414E+10 | 4102.21 | 0.222732E+11 | 0.173289E+10 | 0.00 | ||||||||||||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Maximum of Months | 0.555050E+10 | 0.149826E+10 | 740.61 | 0.480761E+10 | 0.758811E+09 | 0.00 | 0.72 | 0.00 | 4825.56 | 4825.56 | 785.54 | 1411.90 | 0.00 |
Report: DXReportMonthly
For: SPLIT TSE COOLING COIL
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 93692766.54 | 24926411.63 | 73.07 | 93692766.54 | 0.00 | 0.00 | 0.22 | 12-JAN-15:00 | 0.00 | 01-JAN-00:10 | 1423.37 | 12-JAN-15:00 | 1423.37 | 12-JAN-15:00 | 0.00 | 12-JAN-15:00 | 370.21 | 12-JAN-15:00 | 0.00 | 01-JAN-00:10 |
| February | 0.279669E+09 | 73655364.43 | 105.13 | 0.279669E+09 | 0.00 | 0.00 | 0.29 | 20-FEB-15:00 | 0.00 | 01-FEB-00:10 | 1915.63 | 20-FEB-15:00 | 1915.63 | 20-FEB-15:00 | 0.00 | 06-FEB-14:00 | 495.21 | 20-FEB-15:00 | 0.00 | 01-FEB-00:10 |
| March | 0.441107E+09 | 0.116446E+09 | 162.08 | 0.441107E+09 | 0.00 | 0.00 | 0.28 | 21-MAR-15:10 | 0.00 | 01-MAR-00:10 | 1825.35 | 21-MAR-15:10 | 1825.35 | 21-MAR-15:10 | 0.00 | 14-MAR-14:00 | 476.79 | 21-MAR-15:10 | 0.00 | 01-MAR-00:10 |
| April | 0.189776E+10 | 0.507046E+09 | 396.76 | 0.189572E+10 | 2041811.23 | 0.00 | 0.55 | 21-APR-14:10 | 0.00 | 01-APR-00:10 | 3542.46 | 21-APR-14:10 | 3542.46 | 21-APR-14:10 | 84.23 | 29-APR-09:40 | 986.54 | 21-APR-14:10 | 0.00 | 01-APR-00:10 |
| May | 0.341554E+10 | 0.924253E+09 | 602.16 | 0.334700E+10 | 68545367.74 | 0.00 | 0.58 | 19-MAY-14:00 | 0.00 | 01-MAY-01:50 | 3777.17 | 19-MAY-14:00 | 3777.17 | 19-MAY-14:00 | 398.97 | 28-MAY-09:20 | 1084.51 | 19-MAY-14:00 | 0.00 | 01-MAY-00:10 |
| June | 0.495418E+10 | 0.137619E+10 | 696.62 | 0.481389E+10 | 0.140293E+09 | 0.00 | 0.66 | 15-JUN-15:10 | 0.00 | 01-JUN-05:05 | 3989.79 | 15-JUN-15:10 | 3989.79 | 15-JUN-15:10 | 550.34 | 19-JUN-19:00 | 1197.79 | 15-JUN-15:10 | 0.00 | 01-JUN-00:10 |
| July | 0.563695E+10 | 0.151252E+10 | 741.00 | 0.486327E+10 | 0.773681E+09 | 0.00 | 0.61 | 26-JUL-14:00 | 0.00 | 05-JUL-02:50 | 4069.81 | 26-JUL-14:00 | 3834.05 | 26-JUL-14:00 | 855.14 | 20-JUL-09:10 | 1186.41 | 26-JUL-14:00 | 0.00 | 01-JUL-00:10 |
| August | 0.482379E+10 | 0.129667E+10 | 719.98 | 0.440447E+10 | 0.419319E+09 | 0.00 | 0.58 | 07-AUG-16:10 | 0.00 | 14-AUG-02:40 | 3698.32 | 27-AUG-13:00 | 3698.32 | 27-AUG-13:00 | 646.30 | 02-AUG-08:30 | 1096.90 | 07-AUG-16:10 | 0.00 | 01-AUG-00:10 |
| September | 0.390446E+10 | 0.102742E+10 | 615.29 | 0.355705E+10 | 0.347413E+09 | 0.00 | 0.58 | 19-SEP-14:00 | 0.00 | 02-SEP-05:40 | 3792.33 | 20-SEP-13:30 | 3784.48 | 19-SEP-13:50 | 769.11 | 09-SEP-09:30 | 1068.82 | 19-SEP-14:00 | 0.00 | 01-SEP-00:10 |
| October | 0.199026E+10 | 0.515928E+09 | 385.74 | 0.188438E+10 | 0.105878E+09 | 0.00 | 0.54 | 03-OCT-14:00 | 0.00 | 01-OCT-00:10 | 3670.33 | 03-OCT-13:50 | 3463.55 | 03-OCT-13:50 | 590.37 | 04-OCT-10:50 | 1016.61 | 03-OCT-14:00 | 0.00 | 01-OCT-00:10 |
| November | 0.505082E+09 | 0.132374E+09 | 177.42 | 0.504059E+09 | 1022557.70 | 0.00 | 0.34 | 09-NOV-14:00 | 0.00 | 01-NOV-00:10 | 2262.17 | 09-NOV-14:00 | 2262.17 | 09-NOV-14:00 | 75.64 | 03-NOV-12:00 | 576.05 | 09-NOV-14:00 | 0.00 | 01-NOV-00:10 |
| December | 57032238.27 | 15249729.42 | 55.57 | 57032238.27 | 0.00 | 0.00 | 0.14 | 16-DEC-14:40 | 0.00 | 01-DEC-00:10 | 869.53 | 16-DEC-14:40 | 869.53 | 16-DEC-14:40 | 0.00 | 16-DEC-14:10 | 230.34 | 16-DEC-14:40 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.279995E+11 | 0.752268E+10 | 4730.83 | 0.261413E+11 | 0.185819E+10 | 0.00 | ||||||||||||||
| Minimum of Months | 57032238.27 | 15249729.42 | 55.57 | 57032238.27 | 0.00 | 0.00 | 0.14 | 0.00 | 869.53 | 869.53 | 0.00 | 230.34 | 0.00 | |||||||
| Maximum of Months | 0.563695E+10 | 0.151252E+10 | 741.00 | 0.486327E+10 | 0.773681E+09 | 0.00 | 0.66 | 0.00 | 4069.81 | 3989.79 | 855.14 | 1197.79 | 0.00 |
Report: DXReportMonthly
For: SPLIT TNE COOLING COIL
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| February | 16454216.33 | 4422216.28 | 20.67 | 16454216.33 | 0.00 | 0.00 | 0.06 | 20-FEB-15:10 | 0.00 | 01-FEB-00:10 | 361.50 | 20-FEB-15:10 | 361.50 | 20-FEB-15:10 | 0.00 | 20-FEB-15:40 | 96.92 | 20-FEB-15:10 | 0.00 | 01-FEB-00:10 |
| March | 84579122.44 | 22645512.06 | 66.56 | 84579122.44 | 0.00 | 0.00 | 0.13 | 22-MAR-16:05 | 0.00 | 01-MAR-00:10 | 801.37 | 22-MAR-16:05 | 801.37 | 22-MAR-16:05 | 0.00 | 14-MAR-16:30 | 212.61 | 22-MAR-16:05 | 0.00 | 01-MAR-00:10 |
| April | 0.146300E+10 | 0.394775E+09 | 368.86 | 0.146154E+10 | 1467144.37 | 0.00 | 0.48 | 21-APR-15:10 | 0.00 | 01-APR-00:10 | 3097.82 | 21-APR-15:10 | 3097.82 | 21-APR-15:10 | 55.96 | 29-APR-09:30 | 868.29 | 21-APR-15:10 | 0.00 | 01-APR-00:10 |
| May | 0.330455E+10 | 0.895267E+09 | 602.72 | 0.323521E+10 | 69337045.35 | 0.00 | 0.54 | 19-MAY-14:00 | 0.00 | 01-MAY-01:40 | 3472.01 | 19-MAY-14:00 | 3472.01 | 19-MAY-14:00 | 393.66 | 24-MAY-13:30 | 1003.42 | 19-MAY-14:00 | 0.00 | 01-MAY-00:10 |
| June | 0.500239E+10 | 0.138786E+10 | 697.67 | 0.485929E+10 | 0.143102E+09 | 0.00 | 0.66 | 15-JUN-16:30 | 0.00 | 01-JUN-05:15 | 4021.48 | 15-JUN-17:00 | 4021.48 | 15-JUN-17:00 | 565.27 | 19-JUN-19:00 | 1191.64 | 15-JUN-16:30 | 0.00 | 01-JUN-00:10 |
| July | 0.560299E+10 | 0.150288E+10 | 741.00 | 0.482720E+10 | 0.775786E+09 | 0.00 | 0.58 | 02-JUL-16:10 | 0.00 | 05-JUL-02:50 | 3830.72 | 26-JUL-17:40 | 3654.88 | 02-JUL-16:10 | 880.00 | 21-JUL-07:40 | 1112.92 | 26-JUL-14:00 | 0.00 | 01-JUL-00:10 |
| August | 0.448591E+10 | 0.120948E+10 | 718.06 | 0.407307E+10 | 0.412846E+09 | 0.00 | 0.55 | 07-AUG-16:10 | 0.00 | 14-AUG-02:30 | 3522.97 | 07-AUG-16:10 | 3522.97 | 07-AUG-16:10 | 694.59 | 02-AUG-07:40 | 1048.98 | 07-AUG-16:10 | 0.00 | 01-AUG-00:10 |
| September | 0.307027E+10 | 0.815458E+09 | 597.27 | 0.275462E+10 | 0.315648E+09 | 0.00 | 0.43 | 15-SEP-13:00 | 0.00 | 02-SEP-05:15 | 2890.03 | 15-SEP-13:00 | 2688.32 | 20-SEP-14:20 | 614.15 | 09-SEP-09:30 | 814.43 | 15-SEP-13:00 | 0.00 | 01-SEP-00:10 |
| October | 0.987686E+09 | 0.261152E+09 | 301.95 | 0.909861E+09 | 77824308.16 | 0.00 | 0.41 | 03-OCT-14:10 | 0.00 | 01-OCT-00:10 | 2699.48 | 03-OCT-14:10 | 2488.73 | 03-OCT-14:10 | 491.25 | 04-OCT-10:50 | 761.95 | 03-OCT-14:10 | 0.00 | 01-OCT-00:10 |
| November | 20626085.15 | 5474887.65 | 19.00 | 20593154.54 | 32930.62 | 0.00 | 0.09 | 09-NOV-15:10 | 0.00 | 01-NOV-00:10 | 574.90 | 09-NOV-15:10 | 574.90 | 09-NOV-15:10 | 6.09 | 03-NOV-13:50 | 151.88 | 09-NOV-15:10 | 0.00 | 01-NOV-00:10 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.240385E+11 | 0.649942E+10 | 4133.74 | 0.222424E+11 | 0.179604E+10 | 0.00 | ||||||||||||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Maximum of Months | 0.560299E+10 | 0.150288E+10 | 741.00 | 0.485929E+10 | 0.775786E+09 | 0.00 | 0.66 | 0.00 | 4021.48 | 4021.48 | 880.00 | 1191.64 | 0.00 |
Report: DXReportMonthly
For: SPLIT TN1 COOLING COIL
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| February | 6850271.42 | 1845274.68 | 14.50 | 6850271.42 | 0.00 | 0.00 | 0.04 | 21-FEB-17:10 | 0.00 | 01-FEB-00:10 | 238.85 | 21-FEB-17:10 | 238.85 | 21-FEB-17:10 | 0.00 | 20-FEB-15:30 | 64.19 | 21-FEB-17:10 | 0.00 | 01-FEB-00:10 |
| March | 49981894.58 | 13409289.90 | 48.67 | 49981894.58 | -0.0 | 0.00 | 0.11 | 22-MAR-16:10 | 0.00 | 01-MAR-00:10 | 626.47 | 22-MAR-16:10 | 626.47 | 22-MAR-16:10 | 0.00 | 22-MAR-16:40 | 166.66 | 22-MAR-16:10 | 0.00 | 01-MAR-00:10 |
| April | 0.111704E+10 | 0.303226E+09 | 364.15 | 0.111594E+10 | 1105358.68 | 0.00 | 0.41 | 21-APR-15:10 | 0.00 | 01-APR-00:10 | 2360.05 | 21-APR-15:10 | 2360.05 | 21-APR-15:10 | 36.30 | 29-APR-09:50 | 669.64 | 21-APR-15:10 | 0.00 | 01-APR-00:10 |
| May | 0.261516E+10 | 0.713211E+09 | 612.72 | 0.255711E+10 | 58053149.46 | 0.00 | 0.47 | 19-MAY-17:10 | 0.00 | 01-MAY-02:20 | 2710.89 | 19-MAY-17:03 | 2710.89 | 19-MAY-17:03 | 316.62 | 24-MAY-13:30 | 785.81 | 19-MAY-17:00 | 0.00 | 01-MAY-00:10 |
| June | 0.400147E+10 | 0.111826E+10 | 710.68 | 0.387871E+10 | 0.122752E+09 | 0.00 | 0.59 | 15-JUN-17:00 | 0.00 | 11-JUN-05:05 | 3266.24 | 15-JUN-17:00 | 3266.24 | 15-JUN-17:00 | 450.46 | 19-JUN-19:00 | 976.19 | 15-JUN-17:00 | 0.00 | 01-JUN-00:10 |
| July | 0.459211E+10 | 0.123794E+10 | 742.67 | 0.392728E+10 | 0.664830E+09 | 0.00 | 0.53 | 01-JUL-17:00 | 0.00 | 05-JUL-05:30 | 3154.41 | 26-JUL-17:50 | 3019.97 | 01-JUL-17:00 | 672.76 | 20-JUL-16:25 | 919.43 | 01-JUL-17:00 | 0.00 | 01-JUL-00:10 |
| August | 0.367233E+10 | 0.994807E+09 | 729.37 | 0.331188E+10 | 0.360449E+09 | 0.00 | 0.50 | 07-AUG-16:10 | 0.00 | 14-AUG-05:05 | 2893.78 | 07-AUG-16:01 | 2893.78 | 07-AUG-16:01 | 489.15 | 02-AUG-08:40 | 868.68 | 07-AUG-16:10 | 0.00 | 01-AUG-00:10 |
| September | 0.249904E+10 | 0.666361E+09 | 610.39 | 0.222357E+10 | 0.275472E+09 | 0.00 | 0.39 | 01-SEP-16:03 | 0.00 | 04-SEP-05:05 | 2333.31 | 01-SEP-15:10 | 2216.51 | 02-SEP-16:05 | 462.46 | 14-SEP-10:30 | 662.52 | 01-SEP-15:10 | 0.00 | 01-SEP-00:10 |
| October | 0.812069E+09 | 0.215089E+09 | 308.71 | 0.742357E+09 | 69711855.44 | 0.00 | 0.37 | 03-OCT-14:10 | 0.00 | 01-OCT-00:10 | 2220.49 | 03-OCT-14:10 | 2057.23 | 05-OCT-16:03 | 404.23 | 04-OCT-11:00 | 630.31 | 03-OCT-14:10 | 0.00 | 01-OCT-00:10 |
| November | 13281542.00 | 3531473.16 | 16.17 | 13271519.50 | 10022.50 | 0.00 | 0.07 | 09-NOV-15:10 | 0.00 | 01-NOV-00:10 | 425.79 | 09-NOV-15:10 | 425.79 | 09-NOV-15:10 | 2.54 | 03-NOV-14:20 | 112.78 | 09-NOV-15:10 | 0.00 | 01-NOV-00:10 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.193793E+11 | 0.526768E+10 | 4158.02 | 0.178269E+11 | 0.155238E+10 | 0.00 | ||||||||||||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | -0.0 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Maximum of Months | 0.459211E+10 | 0.123794E+10 | 742.67 | 0.392728E+10 | 0.664830E+09 | 0.00 | 0.59 | 0.00 | 3266.24 | 3266.24 | 672.76 | 976.19 | 0.00 |
Report: DXReportMonthly
For: SPLIT TN2 COOLING COIL
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| February | 7241836.26 | 1950609.67 | 15.17 | 7241836.26 | 0.00 | 0.00 | 0.04 | 21-FEB-17:10 | 0.00 | 01-FEB-00:10 | 239.74 | 21-FEB-17:10 | 239.74 | 21-FEB-17:10 | 0.00 | 19-FEB-16:40 | 64.43 | 21-FEB-17:10 | 0.00 | 01-FEB-00:10 |
| March | 50854151.87 | 13642667.41 | 49.42 | 50854151.87 | 0.00 | 0.00 | 0.11 | 22-MAR-16:10 | 0.00 | 01-MAR-00:10 | 628.58 | 22-MAR-16:10 | 628.58 | 22-MAR-16:10 | 0.00 | 14-MAR-16:15 | 167.20 | 22-MAR-16:10 | 0.00 | 01-MAR-00:10 |
| April | 0.112349E+10 | 0.304906E+09 | 365.65 | 0.112238E+10 | 1117056.57 | 0.00 | 0.41 | 21-APR-15:10 | 0.00 | 01-APR-00:10 | 2361.36 | 21-APR-15:10 | 2361.36 | 21-APR-15:10 | 36.96 | 29-APR-09:50 | 669.86 | 21-APR-15:10 | 0.00 | 01-APR-00:10 |
| May | 0.262027E+10 | 0.714456E+09 | 613.34 | 0.256209E+10 | 58178782.27 | 0.00 | 0.47 | 19-MAY-17:00 | 0.00 | 01-MAY-02:20 | 2692.82 | 19-MAY-17:05 | 2692.82 | 19-MAY-17:05 | 316.54 | 24-MAY-13:30 | 781.26 | 19-MAY-16:30 | 0.00 | 01-MAY-00:10 |
| June | 0.400463E+10 | 0.111891E+10 | 710.29 | 0.388178E+10 | 0.122849E+09 | 0.00 | 0.59 | 15-JUN-17:00 | 0.00 | 11-JUN-05:05 | 3249.15 | 15-JUN-17:00 | 3249.15 | 15-JUN-17:00 | 449.37 | 19-JUN-19:00 | 971.26 | 15-JUN-16:50 | 0.00 | 01-JUN-00:10 |
| July | 0.459473E+10 | 0.123841E+10 | 742.67 | 0.392959E+10 | 0.665136E+09 | 0.00 | 0.53 | 01-JUL-17:00 | 0.00 | 05-JUL-05:30 | 3139.14 | 26-JUL-17:50 | 3007.29 | 01-JUL-17:00 | 672.83 | 20-JUL-16:25 | 915.64 | 01-JUL-17:00 | 0.00 | 01-JUL-00:10 |
| August | 0.367534E+10 | 0.995421E+09 | 729.37 | 0.331455E+10 | 0.360786E+09 | 0.00 | 0.50 | 07-AUG-16:10 | 0.00 | 14-AUG-05:05 | 2881.37 | 07-AUG-16:01 | 2881.37 | 07-AUG-16:01 | 494.72 | 02-AUG-08:40 | 865.02 | 07-AUG-16:10 | 0.00 | 01-AUG-00:10 |
| September | 0.250266E+10 | 0.667214E+09 | 610.45 | 0.222669E+10 | 0.275976E+09 | 0.00 | 0.39 | 01-SEP-15:10 | 0.00 | 04-SEP-05:05 | 2330.17 | 01-SEP-15:10 | 2207.66 | 02-SEP-16:05 | 466.09 | 14-SEP-10:30 | 661.57 | 01-SEP-15:10 | 0.00 | 01-SEP-00:10 |
| October | 0.813965E+09 | 0.215578E+09 | 308.50 | 0.744304E+09 | 69660855.88 | 0.00 | 0.37 | 03-OCT-14:10 | 0.00 | 01-OCT-00:10 | 2220.72 | 03-OCT-14:10 | 2043.11 | 05-OCT-16:03 | 406.10 | 04-OCT-11:00 | 630.27 | 03-OCT-14:10 | 0.00 | 01-OCT-00:10 |
| November | 13653374.42 | 3630163.22 | 16.50 | 13642552.95 | 10821.47 | 0.00 | 0.07 | 09-NOV-15:10 | 0.00 | 01-NOV-00:10 | 434.88 | 09-NOV-15:10 | 434.88 | 09-NOV-15:10 | 2.75 | 03-NOV-14:10 | 115.16 | 09-NOV-15:10 | 0.00 | 01-NOV-00:10 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.194068E+11 | 0.527411E+10 | 4161.36 | 0.178531E+11 | 0.155371E+10 | 0.00 | ||||||||||||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Maximum of Months | 0.459473E+10 | 0.123841E+10 | 742.67 | 0.392959E+10 | 0.665136E+09 | 0.00 | 0.59 | 0.00 | 3249.15 | 3249.15 | 672.83 | 971.26 | 0.00 |
Report: DXReportMonthly
For: SPLIT TS1 COOLING COIL
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.141384E+09 | 37573710.85 | 101.57 | 0.141384E+09 | -0.0 | 0.00 | 0.24 | 12-JAN-15:00 | 0.00 | 01-JAN-00:10 | 1421.13 | 12-JAN-15:00 | 1421.13 | 12-JAN-15:00 | 0.00 | 12-JAN-16:10 | 368.53 | 12-JAN-15:00 | 0.00 | 01-JAN-00:10 |
| February | 0.267201E+09 | 70453791.74 | 121.42 | 0.267201E+09 | -0.0 | 0.00 | 0.30 | 20-FEB-15:00 | 0.00 | 01-FEB-00:10 | 1758.77 | 20-FEB-15:00 | 1758.77 | 20-FEB-15:00 | 0.00 | 05-FEB-14:40 | 454.58 | 20-FEB-15:00 | 0.00 | 01-FEB-00:10 |
| March | 0.367399E+09 | 97108541.84 | 158.42 | 0.367399E+09 | 0.00 | 0.00 | 0.28 | 16-MAR-15:10 | 0.00 | 01-MAR-00:10 | 1675.94 | 16-MAR-15:10 | 1675.94 | 16-MAR-15:10 | 0.00 | 06-MAR-15:00 | 434.07 | 16-MAR-15:10 | 0.00 | 01-MAR-00:10 |
| April | 0.154644E+10 | 0.415382E+09 | 403.46 | 0.154478E+10 | 1659374.98 | 0.00 | 0.48 | 21-APR-14:20 | 0.00 | 01-APR-00:10 | 2775.34 | 21-APR-14:30 | 2775.34 | 21-APR-14:30 | 62.69 | 29-APR-10:00 | 782.07 | 21-APR-14:30 | 0.00 | 01-APR-00:10 |
| May | 0.272633E+10 | 0.742785E+09 | 611.24 | 0.266908E+10 | 57258542.24 | 0.00 | 0.50 | 19-MAY-14:00 | 0.00 | 01-MAY-02:40 | 2943.89 | 19-MAY-14:00 | 2943.89 | 19-MAY-14:00 | 320.20 | 24-MAY-13:30 | 856.01 | 19-MAY-14:00 | 0.00 | 01-MAY-00:10 |
| June | 0.395265E+10 | 0.110629E+10 | 709.00 | 0.383303E+10 | 0.119617E+09 | 0.00 | 0.58 | 15-JUN-16:01 | 0.00 | 11-JUN-05:05 | 3198.71 | 15-JUN-16:01 | 3198.71 | 15-JUN-16:01 | 434.32 | 19-JUN-19:00 | 965.13 | 15-JUN-16:01 | 0.00 | 01-JUN-00:10 |
| July | 0.462626E+10 | 0.124787E+10 | 742.67 | 0.396395E+10 | 0.662313E+09 | 0.00 | 0.55 | 02-JUL-16:01 | 0.00 | 05-JUL-05:30 | 3249.44 | 26-JUL-14:10 | 3141.01 | 02-JUL-16:01 | 697.32 | 21-JUL-11:30 | 958.30 | 26-JUL-14:10 | 0.00 | 01-JUL-00:10 |
| August | 0.401374E+10 | 0.108421E+10 | 729.52 | 0.364576E+10 | 0.367974E+09 | 0.00 | 0.53 | 07-AUG-16:10 | 0.00 | 14-AUG-05:05 | 3070.77 | 07-AUG-16:04 | 3070.77 | 07-AUG-16:04 | 493.59 | 02-AUG-11:30 | 918.16 | 07-AUG-16:04 | 0.00 | 01-AUG-00:10 |
| September | 0.334444E+10 | 0.883552E+09 | 628.45 | 0.303323E+10 | 0.311218E+09 | 0.00 | 0.54 | 19-SEP-14:00 | 0.00 | 04-SEP-05:05 | 3227.16 | 19-SEP-14:10 | 3227.16 | 19-SEP-14:10 | 577.95 | 09-SEP-09:50 | 917.08 | 19-SEP-14:00 | 0.00 | 01-SEP-00:10 |
| October | 0.183941E+10 | 0.477209E+09 | 419.58 | 0.173880E+10 | 0.100605E+09 | 0.00 | 0.52 | 03-OCT-14:00 | 0.00 | 01-OCT-00:10 | 3191.08 | 03-OCT-13:50 | 3010.65 | 03-OCT-13:50 | 516.17 | 04-OCT-11:00 | 886.74 | 03-OCT-14:00 | 0.00 | 01-OCT-00:10 |
| November | 0.519781E+09 | 0.136202E+09 | 197.14 | 0.518779E+09 | 1002530.83 | 0.00 | 0.35 | 09-NOV-14:10 | 0.00 | 01-NOV-00:10 | 2139.70 | 09-NOV-14:20 | 2139.70 | 09-NOV-14:20 | 67.86 | 03-NOV-12:00 | 543.81 | 09-NOV-14:20 | 0.00 | 01-NOV-00:10 |
| December | 96223857.49 | 25677252.05 | 81.37 | 96223857.49 | 0.00 | 0.00 | 0.17 | 16-DEC-14:50 | 0.00 | 01-DEC-00:10 | 1010.52 | 16-DEC-14:50 | 1010.52 | 16-DEC-14:50 | 0.00 | 04-DEC-15:00 | 266.20 | 16-DEC-14:50 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.234413E+11 | 0.632431E+10 | 4903.83 | 0.218196E+11 | 0.162165E+10 | 0.00 | ||||||||||||||
| Minimum of Months | 96223857.49 | 25677252.05 | 81.37 | 96223857.49 | -0.0 | 0.00 | 0.17 | 0.00 | 1010.52 | 1010.52 | 0.00 | 266.20 | 0.00 | |||||||
| Maximum of Months | 0.462626E+10 | 0.124787E+10 | 742.67 | 0.396395E+10 | 0.662313E+09 | 0.00 | 0.58 | 0.00 | 3249.44 | 3227.16 | 697.32 | 965.13 | 0.00 |
Report: DXReportMonthly
For: SPLIT TS2 COOLING COIL
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.143303E+09 | 38078283.73 | 101.99 | 0.143303E+09 | 0.00 | 0.00 | 0.24 | 12-JAN-15:00 | 0.00 | 01-JAN-00:10 | 1422.89 | 12-JAN-15:00 | 1422.89 | 12-JAN-15:00 | 0.00 | 12-JAN-13:40 | 368.92 | 12-JAN-15:00 | 0.00 | 01-JAN-00:10 |
| February | 0.270908E+09 | 71418581.69 | 122.58 | 0.270908E+09 | -0.0 | 0.00 | 0.30 | 20-FEB-15:00 | 0.00 | 01-FEB-00:10 | 1766.26 | 20-FEB-15:00 | 1766.26 | 20-FEB-15:00 | 0.00 | 05-FEB-15:20 | 456.36 | 20-FEB-15:00 | 0.00 | 01-FEB-00:10 |
| March | 0.372776E+09 | 98512605.91 | 159.75 | 0.372776E+09 | 0.00 | 0.00 | 0.28 | 16-MAR-15:10 | 0.00 | 01-MAR-00:10 | 1676.57 | 16-MAR-15:10 | 1676.57 | 16-MAR-15:10 | 0.00 | 14-MAR-16:40 | 434.17 | 16-MAR-15:10 | 0.00 | 01-MAR-00:10 |
| April | 0.155369E+10 | 0.417205E+09 | 404.01 | 0.155202E+10 | 1676040.10 | 0.00 | 0.48 | 21-APR-14:10 | 0.00 | 01-APR-00:10 | 2782.26 | 21-APR-14:20 | 2782.26 | 21-APR-14:20 | 63.48 | 29-APR-10:00 | 783.80 | 21-APR-14:20 | 0.00 | 01-APR-00:10 |
| May | 0.273171E+10 | 0.744071E+09 | 611.75 | 0.267432E+10 | 57387534.05 | 0.00 | 0.50 | 19-MAY-14:00 | 0.00 | 01-MAY-02:30 | 2950.62 | 19-MAY-14:00 | 2950.62 | 19-MAY-14:00 | 320.10 | 24-MAY-13:20 | 857.62 | 19-MAY-14:00 | 0.00 | 01-MAY-00:10 |
| June | 0.395597E+10 | 0.110697E+10 | 708.22 | 0.383624E+10 | 0.119723E+09 | 0.00 | 0.59 | 15-JUN-15:10 | 0.00 | 11-JUN-05:05 | 3187.25 | 15-JUN-16:01 | 3187.25 | 15-JUN-16:01 | 433.17 | 19-JUN-19:00 | 963.56 | 15-JUN-15:10 | 0.00 | 01-JUN-00:10 |
| July | 0.462898E+10 | 0.124835E+10 | 742.67 | 0.396635E+10 | 0.662636E+09 | 0.00 | 0.55 | 02-JUL-16:01 | 0.00 | 05-JUL-05:30 | 3255.35 | 26-JUL-14:10 | 3131.85 | 02-JUL-16:01 | 698.48 | 21-JUL-11:30 | 959.66 | 26-JUL-14:10 | 0.00 | 01-JUL-00:10 |
| August | 0.401671E+10 | 0.108477E+10 | 729.52 | 0.364844E+10 | 0.368274E+09 | 0.00 | 0.53 | 07-AUG-16:10 | 0.00 | 14-AUG-05:05 | 3058.28 | 07-AUG-16:04 | 3058.28 | 07-AUG-16:04 | 494.22 | 02-AUG-11:30 | 914.49 | 07-AUG-16:04 | 0.00 | 01-AUG-00:10 |
| September | 0.334760E+10 | 0.884166E+09 | 628.49 | 0.303600E+10 | 0.311594E+09 | 0.00 | 0.54 | 19-SEP-14:00 | 0.00 | 04-SEP-05:05 | 3231.61 | 19-SEP-14:00 | 3231.61 | 19-SEP-14:00 | 583.24 | 09-SEP-09:50 | 918.20 | 19-SEP-14:00 | 0.00 | 01-SEP-00:10 |
| October | 0.184040E+10 | 0.477379E+09 | 418.75 | 0.173997E+10 | 0.100433E+09 | 0.00 | 0.52 | 03-OCT-13:50 | 0.00 | 01-OCT-00:10 | 3193.13 | 03-OCT-13:50 | 3013.03 | 03-OCT-13:50 | 517.26 | 04-OCT-11:00 | 886.73 | 03-OCT-14:00 | 0.00 | 01-OCT-00:10 |
| November | 0.524000E+09 | 0.137280E+09 | 198.78 | 0.523000E+09 | 999439.84 | 0.00 | 0.35 | 09-NOV-14:00 | 0.00 | 01-NOV-00:10 | 2146.48 | 09-NOV-14:10 | 2146.48 | 09-NOV-14:10 | 68.80 | 03-NOV-12:00 | 545.51 | 09-NOV-14:00 | 0.00 | 01-NOV-00:10 |
| December | 98335325.17 | 26236358.63 | 82.54 | 98335325.17 | -0.0 | 0.00 | 0.17 | 16-DEC-14:40 | 0.00 | 01-DEC-00:10 | 1015.80 | 16-DEC-14:40 | 1015.80 | 16-DEC-14:40 | 0.00 | 16-DEC-13:20 | 267.54 | 16-DEC-14:40 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.234844E+11 | 0.633443E+10 | 4909.04 | 0.218617E+11 | 0.162272E+10 | 0.00 | ||||||||||||||
| Minimum of Months | 98335325.17 | 26236358.63 | 82.54 | 98335325.17 | -0.0 | 0.00 | 0.17 | 0.00 | 1015.80 | 1015.80 | 0.00 | 267.54 | 0.00 | |||||||
| Maximum of Months | 0.462898E+10 | 0.124835E+10 | 742.67 | 0.396635E+10 | 0.662636E+09 | 0.00 | 0.59 | 0.00 | 3255.35 | 3231.61 | 698.48 | 963.56 | 0.00 |
Report: WindowReportMonthly
For: GWINDOW1 S SWA
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 212.47 | 160.54 | 51.93 | 290.22 | 164.39 | 0.00 | 0.00 | 0.00 |
| February | 202.34 | 143.70 | 58.64 | 284.84 | 143.04 | 0.00 | 0.00 | 0.00 |
| March | 157.89 | 89.51 | 68.38 | 231.74 | 123.04 | 0.00 | 0.00 | 0.00 |
| April | 112.04 | 43.39 | 68.65 | 184.75 | 78.18 | 0.00 | 0.00 | 0.00 |
| May | 77.50 | 10.94 | 66.56 | 142.85 | 45.95 | 0.00 | 0.00 | 0.00 |
| June | 67.08 | 4.56 | 62.53 | 155.77 | 20.96 | 0.00 | 0.00 | 0.00 |
| July | 68.31 | 6.56 | 61.75 | 157.23 | 16.34 | 0.00 | 0.00 | 0.00 |
| August | 85.66 | 21.87 | 63.79 | 180.85 | 25.77 | 0.00 | 0.00 | 0.00 |
| September | 137.12 | 72.04 | 65.07 | 258.48 | 54.76 | 0.00 | 0.00 | 0.00 |
| October | 184.46 | 124.87 | 59.60 | 294.27 | 92.26 | 0.00 | 0.00 | 0.00 |
| November | 223.02 | 170.40 | 52.61 | 314.05 | 150.47 | 0.00 | 0.00 | 0.00 |
| December | 219.07 | 164.36 | 54.71 | 291.75 | 180.37 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 145.23 | 84.04 | 61.20 | 231.84 | 91.03 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 67.08 | 4.56 | 51.93 | 142.85 | 16.34 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 223.02 | 170.40 | 68.65 | 314.05 | 180.37 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: GWINDOW1 W SWA
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 58.11 | 32.75 | 25.35 | 62.28 | 119.60 | 0.00 | 0.00 | 0.00 |
| February | 65.40 | 34.70 | 30.70 | 77.01 | 103.56 | 0.00 | 0.00 | 0.00 |
| March | 89.22 | 47.81 | 41.41 | 119.35 | 83.63 | 0.00 | 0.00 | 0.00 |
| April | 102.43 | 55.24 | 47.18 | 158.83 | 50.67 | 0.00 | 0.00 | 0.00 |
| May | 110.31 | 58.95 | 51.37 | 191.36 | 29.86 | 0.00 | 0.00 | 0.00 |
| June | 107.65 | 57.86 | 49.79 | 212.36 | 13.91 | 0.00 | 0.00 | 0.00 |
| July | 95.60 | 47.56 | 48.05 | 189.41 | 10.67 | 0.00 | 0.00 | 0.00 |
| August | 92.37 | 47.02 | 45.36 | 173.89 | 16.85 | 0.00 | 0.00 | 0.00 |
| September | 94.73 | 52.85 | 41.88 | 166.06 | 36.55 | 0.00 | 0.00 | 0.00 |
| October | 81.36 | 47.47 | 33.89 | 121.15 | 63.71 | 0.00 | 0.00 | 0.00 |
| November | 67.84 | 41.14 | 26.70 | 80.68 | 110.37 | 0.00 | 0.00 | 0.00 |
| December | 55.05 | 29.90 | 25.14 | 55.04 | 133.35 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 85.08 | 46.13 | 38.94 | 134.20 | 64.20 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 55.05 | 29.90 | 25.14 | 55.04 | 10.67 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 110.31 | 58.95 | 51.37 | 212.36 | 133.35 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: GWINDOW1 W NWA
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 58.11 | 32.75 | 25.35 | 66.62 | 111.39 | 0.00 | 0.00 | 0.00 |
| February | 65.40 | 34.70 | 30.70 | 81.71 | 96.53 | 0.00 | 0.00 | 0.00 |
| March | 89.22 | 47.81 | 41.41 | 123.77 | 78.97 | 0.00 | 0.00 | 0.00 |
| April | 102.43 | 55.24 | 47.18 | 161.12 | 48.53 | 0.00 | 0.00 | 0.00 |
| May | 110.31 | 58.95 | 51.37 | 191.70 | 29.70 | 0.00 | 0.00 | 0.00 |
| June | 107.65 | 57.86 | 49.79 | 212.23 | 13.98 | 0.00 | 0.00 | 0.00 |
| July | 95.60 | 47.56 | 48.05 | 189.44 | 10.69 | 0.00 | 0.00 | 0.00 |
| August | 92.37 | 47.02 | 45.36 | 174.56 | 16.63 | 0.00 | 0.00 | 0.00 |
| September | 94.73 | 52.85 | 41.88 | 167.54 | 35.63 | 0.00 | 0.00 | 0.00 |
| October | 81.36 | 47.47 | 33.89 | 123.36 | 61.50 | 0.00 | 0.00 | 0.00 |
| November | 67.84 | 41.14 | 26.70 | 85.08 | 100.55 | 0.00 | 0.00 | 0.00 |
| December | 55.05 | 29.90 | 25.14 | 59.03 | 125.23 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 85.08 | 46.13 | 38.94 | 136.58 | 60.61 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 55.05 | 29.90 | 25.14 | 59.03 | 10.69 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 110.31 | 58.95 | 51.37 | 212.23 | 125.23 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: GWINDOW1 N NWA
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 31.32 | 0.00 | 31.32 | 6.83 | 177.96 | 0.00 | 0.00 | 0.00 |
| February | 38.24 | 0.00 | 38.24 | 19.88 | 152.27 | 0.00 | 0.00 | 0.00 |
| March | 50.06 | 0.01 | 50.06 | 41.47 | 123.66 | 0.00 | 0.00 | 0.00 |
| April | 57.98 | 0.63 | 57.35 | 72.11 | 73.45 | 0.00 | 0.00 | 0.00 |
| May | 68.64 | 5.06 | 63.58 | 116.32 | 42.47 | 0.00 | 0.00 | 0.00 |
| June | 72.72 | 8.82 | 63.90 | 163.20 | 20.25 | 0.00 | 0.00 | 0.00 |
| July | 67.08 | 6.26 | 60.82 | 150.18 | 15.62 | 0.00 | 0.00 | 0.00 |
| August | 57.15 | 1.47 | 55.67 | 115.94 | 24.39 | 0.00 | 0.00 | 0.00 |
| September | 49.61 | 0.05 | 49.56 | 85.01 | 54.41 | 0.00 | 0.00 | 0.00 |
| October | 41.14 | 0.00 | 41.14 | 41.11 | 96.09 | 0.00 | 0.00 | 0.00 |
| November | 33.21 | 0.00 | 33.21 | 10.18 | 161.39 | 0.00 | 0.00 | 0.00 |
| December | 31.07 | 0.00 | 31.07 | 4.17 | 202.25 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 49.91 | 1.87 | 48.04 | 69.12 | 95.08 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 31.07 | 0.00 | 31.07 | 4.17 | 15.62 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 72.72 | 8.82 | 63.90 | 163.20 | 202.25 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: GWINDOW1 S SEA
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 212.47 | 160.54 | 51.93 | 289.15 | 166.55 | 0.00 | 0.00 | 0.00 |
| February | 202.34 | 143.70 | 58.64 | 281.67 | 148.02 | 0.00 | 0.00 | 0.00 |
| March | 157.89 | 89.51 | 68.38 | 227.19 | 129.37 | 0.00 | 0.00 | 0.00 |
| April | 112.04 | 43.39 | 68.65 | 176.77 | 90.75 | 0.00 | 0.00 | 0.00 |
| May | 77.50 | 10.94 | 66.56 | 129.94 | 62.82 | 0.00 | 0.00 | 0.00 |
| June | 67.08 | 4.56 | 62.53 | 134.99 | 38.50 | 0.00 | 0.00 | 0.00 |
| July | 68.31 | 6.56 | 61.75 | 134.48 | 35.33 | 0.00 | 0.00 | 0.00 |
| August | 85.66 | 21.87 | 63.79 | 163.02 | 47.33 | 0.00 | 0.00 | 0.00 |
| September | 137.12 | 72.04 | 65.07 | 244.36 | 79.82 | 0.00 | 0.00 | 0.00 |
| October | 184.46 | 124.87 | 59.60 | 285.74 | 110.44 | 0.00 | 0.00 | 0.00 |
| November | 223.02 | 170.40 | 52.61 | 310.41 | 158.96 | 0.00 | 0.00 | 0.00 |
| December | 219.07 | 164.36 | 54.71 | 289.68 | 183.85 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 145.23 | 84.04 | 61.20 | 221.86 | 104.09 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 67.08 | 4.56 | 51.93 | 129.94 | 35.33 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 223.02 | 170.40 | 68.65 | 310.41 | 183.85 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: GWINDOW1 E SEA
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 55.33 | 30.11 | 25.21 | 52.29 | 116.55 | 0.00 | 0.00 | 0.00 |
| February | 73.58 | 41.85 | 31.73 | 82.82 | 100.71 | 0.00 | 0.00 | 0.00 |
| March | 90.84 | 49.92 | 40.92 | 114.53 | 82.58 | 0.00 | 0.00 | 0.00 |
| April | 109.73 | 60.95 | 48.78 | 160.85 | 54.25 | 0.00 | 0.00 | 0.00 |
| May | 113.13 | 61.45 | 51.68 | 184.11 | 37.78 | 0.00 | 0.00 | 0.00 |
| June | 113.31 | 63.06 | 50.25 | 205.72 | 23.65 | 0.00 | 0.00 | 0.00 |
| July | 101.74 | 53.27 | 48.46 | 182.67 | 21.75 | 0.00 | 0.00 | 0.00 |
| August | 96.64 | 49.43 | 47.21 | 166.58 | 28.80 | 0.00 | 0.00 | 0.00 |
| September | 95.76 | 54.62 | 41.14 | 153.22 | 48.91 | 0.00 | 0.00 | 0.00 |
| October | 73.53 | 39.64 | 33.90 | 97.60 | 73.47 | 0.00 | 0.00 | 0.00 |
| November | 65.99 | 38.40 | 27.60 | 67.99 | 111.06 | 0.00 | 0.00 | 0.00 |
| December | 55.01 | 29.13 | 25.89 | 47.90 | 131.42 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 87.06 | 47.63 | 39.43 | 126.49 | 69.09 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 55.01 | 29.13 | 25.21 | 47.90 | 21.75 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 113.31 | 63.06 | 51.68 | 205.72 | 131.42 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: GWINDOW1 E NEA
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 55.33 | 30.11 | 25.21 | 55.87 | 105.33 | 0.00 | 0.00 | 0.00 |
| February | 73.58 | 41.85 | 31.73 | 88.27 | 89.50 | 0.00 | 0.00 | 0.00 |
| March | 90.84 | 49.92 | 40.92 | 120.90 | 73.07 | 0.00 | 0.00 | 0.00 |
| April | 109.73 | 60.95 | 48.78 | 168.29 | 44.66 | 0.00 | 0.00 | 0.00 |
| May | 113.13 | 61.45 | 51.68 | 193.51 | 27.35 | 0.00 | 0.00 | 0.00 |
| June | 113.31 | 63.06 | 50.25 | 220.16 | 12.85 | 0.00 | 0.00 | 0.00 |
| July | 101.74 | 53.27 | 48.46 | 198.95 | 10.07 | 0.00 | 0.00 | 0.00 |
| August | 96.64 | 49.43 | 47.21 | 180.28 | 15.40 | 0.00 | 0.00 | 0.00 |
| September | 95.76 | 54.62 | 41.14 | 165.00 | 32.54 | 0.00 | 0.00 | 0.00 |
| October | 73.53 | 39.64 | 33.90 | 104.84 | 58.43 | 0.00 | 0.00 | 0.00 |
| November | 65.99 | 38.40 | 27.60 | 74.07 | 94.52 | 0.00 | 0.00 | 0.00 |
| December | 55.01 | 29.13 | 25.89 | 51.19 | 118.92 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 87.06 | 47.63 | 39.43 | 135.26 | 56.74 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 55.01 | 29.13 | 25.21 | 51.19 | 10.07 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 113.31 | 63.06 | 51.68 | 220.16 | 118.92 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: GWINDOW1 N NEA
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 31.32 | 0.00 | 31.32 | 6.70 | 177.38 | 0.00 | 0.00 | 0.00 |
| February | 38.24 | 0.00 | 38.24 | 19.43 | 152.16 | 0.00 | 0.00 | 0.00 |
| March | 50.06 | 0.01 | 50.06 | 40.85 | 123.14 | 0.00 | 0.00 | 0.00 |
| April | 57.98 | 0.63 | 57.35 | 70.84 | 73.45 | 0.00 | 0.00 | 0.00 |
| May | 68.64 | 5.06 | 63.58 | 115.56 | 42.23 | 0.00 | 0.00 | 0.00 |
| June | 72.72 | 8.82 | 63.90 | 162.74 | 20.08 | 0.00 | 0.00 | 0.00 |
| July | 67.08 | 6.26 | 60.82 | 149.84 | 15.46 | 0.00 | 0.00 | 0.00 |
| August | 57.15 | 1.47 | 55.67 | 115.59 | 24.22 | 0.00 | 0.00 | 0.00 |
| September | 49.61 | 0.05 | 49.56 | 84.62 | 54.10 | 0.00 | 0.00 | 0.00 |
| October | 41.14 | 0.00 | 41.14 | 40.84 | 95.47 | 0.00 | 0.00 | 0.00 |
| November | 33.21 | 0.00 | 33.21 | 9.77 | 160.62 | 0.00 | 0.00 | 0.00 |
| December | 31.07 | 0.00 | 31.07 | 4.00 | 201.95 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 49.91 | 1.87 | 48.04 | 68.65 | 94.75 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 31.07 | 0.00 | 31.07 | 4.00 | 15.46 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 72.72 | 8.82 | 63.90 | 162.74 | 201.95 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: GWINDOW1 N N1A
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 31.32 | 0.00 | 31.32 | 6.44 | 180.96 | 0.00 | 0.00 | 0.00 |
| February | 38.24 | 0.00 | 38.24 | 19.21 | 155.50 | 0.00 | 0.00 | 0.00 |
| March | 50.06 | 0.01 | 50.06 | 40.50 | 126.46 | 0.00 | 0.00 | 0.00 |
| April | 57.98 | 0.63 | 57.35 | 71.24 | 75.85 | 0.00 | 0.00 | 0.00 |
| May | 68.64 | 5.06 | 63.58 | 116.84 | 42.70 | 0.00 | 0.00 | 0.00 |
| June | 72.72 | 8.82 | 63.90 | 165.01 | 19.94 | 0.00 | 0.00 | 0.00 |
| July | 67.08 | 6.26 | 60.82 | 152.30 | 15.10 | 0.00 | 0.00 | 0.00 |
| August | 57.15 | 1.47 | 55.67 | 118.05 | 23.73 | 0.00 | 0.00 | 0.00 |
| September | 49.61 | 0.05 | 49.56 | 86.55 | 53.37 | 0.00 | 0.00 | 0.00 |
| October | 41.14 | 0.00 | 41.14 | 41.57 | 96.23 | 0.00 | 0.00 | 0.00 |
| November | 33.21 | 0.00 | 33.21 | 9.66 | 164.88 | 0.00 | 0.00 | 0.00 |
| December | 31.07 | 0.00 | 31.07 | 3.91 | 205.21 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 49.91 | 1.87 | 48.04 | 69.53 | 96.38 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 31.07 | 0.00 | 31.07 | 3.91 | 15.10 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 72.72 | 8.82 | 63.90 | 165.01 | 205.21 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: GWINDOW1 N N2A
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 31.32 | 0.00 | 31.32 | 6.43 | 180.91 | 0.00 | 0.00 | 0.00 |
| February | 38.24 | 0.00 | 38.24 | 19.18 | 155.51 | 0.00 | 0.00 | 0.00 |
| March | 50.06 | 0.01 | 50.06 | 40.46 | 126.45 | 0.00 | 0.00 | 0.00 |
| April | 57.98 | 0.63 | 57.35 | 71.15 | 75.90 | 0.00 | 0.00 | 0.00 |
| May | 68.64 | 5.06 | 63.58 | 116.80 | 42.70 | 0.00 | 0.00 | 0.00 |
| June | 72.72 | 8.82 | 63.90 | 164.99 | 19.94 | 0.00 | 0.00 | 0.00 |
| July | 67.08 | 6.26 | 60.82 | 152.29 | 15.10 | 0.00 | 0.00 | 0.00 |
| August | 57.15 | 1.47 | 55.67 | 118.03 | 23.73 | 0.00 | 0.00 | 0.00 |
| September | 49.61 | 0.05 | 49.56 | 86.54 | 53.36 | 0.00 | 0.00 | 0.00 |
| October | 41.14 | 0.00 | 41.14 | 41.56 | 96.20 | 0.00 | 0.00 | 0.00 |
| November | 33.21 | 0.00 | 33.21 | 9.65 | 164.82 | 0.00 | 0.00 | 0.00 |
| December | 31.07 | 0.00 | 31.07 | 3.90 | 205.20 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 49.91 | 1.87 | 48.04 | 69.51 | 96.37 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 31.07 | 0.00 | 31.07 | 3.90 | 15.10 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 72.72 | 8.82 | 63.90 | 164.99 | 205.20 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: GWINDOW1 S S1A
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 212.47 | 160.54 | 51.93 | 287.03 | 171.02 | 0.00 | 0.00 | 0.00 |
| February | 202.34 | 143.70 | 58.64 | 281.41 | 149.48 | 0.00 | 0.00 | 0.00 |
| March | 157.89 | 89.51 | 68.38 | 228.49 | 128.39 | 0.00 | 0.00 | 0.00 |
| April | 112.04 | 43.39 | 68.65 | 183.43 | 80.96 | 0.00 | 0.00 | 0.00 |
| May | 77.50 | 10.94 | 66.56 | 143.47 | 46.29 | 0.00 | 0.00 | 0.00 |
| June | 67.08 | 4.56 | 62.53 | 157.60 | 20.70 | 0.00 | 0.00 | 0.00 |
| July | 68.31 | 6.56 | 61.75 | 159.32 | 15.85 | 0.00 | 0.00 | 0.00 |
| August | 85.66 | 21.87 | 63.79 | 182.81 | 25.15 | 0.00 | 0.00 | 0.00 |
| September | 137.12 | 72.04 | 65.07 | 259.85 | 53.86 | 0.00 | 0.00 | 0.00 |
| October | 184.46 | 124.87 | 59.60 | 294.70 | 92.29 | 0.00 | 0.00 | 0.00 |
| November | 223.02 | 170.40 | 52.61 | 312.41 | 154.19 | 0.00 | 0.00 | 0.00 |
| December | 219.07 | 164.36 | 54.71 | 288.29 | 186.87 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 145.23 | 84.04 | 61.20 | 231.19 | 93.47 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 67.08 | 4.56 | 51.93 | 143.47 | 15.85 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 223.02 | 170.40 | 68.65 | 312.41 | 186.87 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: GWINDOW1 S S2A
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 212.47 | 160.54 | 51.93 | 286.87 | 171.25 | 0.00 | 0.00 | 0.00 |
| February | 202.34 | 143.70 | 58.64 | 281.01 | 150.07 | 0.00 | 0.00 | 0.00 |
| March | 157.89 | 89.51 | 68.38 | 227.88 | 129.17 | 0.00 | 0.00 | 0.00 |
| April | 112.04 | 43.39 | 68.65 | 182.74 | 81.82 | 0.00 | 0.00 | 0.00 |
| May | 77.50 | 10.94 | 66.56 | 142.70 | 46.99 | 0.00 | 0.00 | 0.00 |
| June | 67.08 | 4.56 | 62.53 | 156.49 | 21.30 | 0.00 | 0.00 | 0.00 |
| July | 68.31 | 6.56 | 61.75 | 158.18 | 16.48 | 0.00 | 0.00 | 0.00 |
| August | 85.66 | 21.87 | 63.79 | 181.83 | 25.87 | 0.00 | 0.00 | 0.00 |
| September | 137.12 | 72.04 | 65.07 | 259.14 | 54.73 | 0.00 | 0.00 | 0.00 |
| October | 184.46 | 124.87 | 59.60 | 294.23 | 92.92 | 0.00 | 0.00 | 0.00 |
| November | 223.02 | 170.40 | 52.61 | 312.11 | 154.69 | 0.00 | 0.00 | 0.00 |
| December | 219.07 | 164.36 | 54.71 | 287.91 | 187.47 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 145.23 | 84.04 | 61.20 | 230.55 | 94.12 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 67.08 | 4.56 | 51.93 | 142.70 | 16.48 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 223.02 | 170.40 | 68.65 | 312.11 | 187.47 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MWINDOW1 S SWA
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 212.47 | 160.54 | 51.93 | 284.68 | 171.75 | 0.00 | 0.00 | 0.00 |
| February | 202.34 | 143.70 | 58.64 | 276.61 | 154.87 | 0.00 | 0.00 | 0.00 |
| March | 157.89 | 89.51 | 68.38 | 220.54 | 138.44 | 0.00 | 0.00 | 0.00 |
| April | 112.04 | 43.39 | 68.65 | 178.57 | 85.29 | 0.00 | 0.00 | 0.00 |
| May | 77.50 | 10.94 | 66.56 | 140.11 | 48.14 | 0.00 | 0.00 | 0.00 |
| June | 67.08 | 4.56 | 62.53 | 154.74 | 21.47 | 0.00 | 0.00 | 0.00 |
| July | 68.31 | 6.56 | 61.75 | 157.39 | 16.08 | 0.00 | 0.00 | 0.00 |
| August | 85.66 | 21.87 | 63.79 | 181.62 | 24.86 | 0.00 | 0.00 | 0.00 |
| September | 137.12 | 72.04 | 65.07 | 258.80 | 53.00 | 0.00 | 0.00 | 0.00 |
| October | 184.46 | 124.87 | 59.60 | 293.70 | 90.84 | 0.00 | 0.00 | 0.00 |
| November | 223.02 | 170.40 | 52.61 | 313.18 | 148.91 | 0.00 | 0.00 | 0.00 |
| December | 219.07 | 164.36 | 54.71 | 287.99 | 184.35 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 145.23 | 84.04 | 61.20 | 228.63 | 94.53 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 67.08 | 4.56 | 51.93 | 140.11 | 16.08 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 223.02 | 170.40 | 68.65 | 313.18 | 184.35 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MWINDOW1 W SWA
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 58.11 | 32.75 | 25.35 | 60.05 | 125.48 | 0.00 | 0.00 | 0.00 |
| February | 65.40 | 34.70 | 30.70 | 73.16 | 112.43 | 0.00 | 0.00 | 0.00 |
| March | 89.22 | 47.81 | 41.41 | 112.80 | 94.47 | 0.00 | 0.00 | 0.00 |
| April | 102.43 | 55.24 | 47.18 | 154.71 | 55.32 | 0.00 | 0.00 | 0.00 |
| May | 110.31 | 58.95 | 51.37 | 189.06 | 31.30 | 0.00 | 0.00 | 0.00 |
| June | 107.65 | 57.86 | 49.79 | 211.20 | 14.28 | 0.00 | 0.00 | 0.00 |
| July | 95.60 | 47.56 | 48.05 | 189.19 | 10.53 | 0.00 | 0.00 | 0.00 |
| August | 92.37 | 47.02 | 45.36 | 174.23 | 16.29 | 0.00 | 0.00 | 0.00 |
| September | 94.73 | 52.85 | 41.88 | 166.39 | 35.44 | 0.00 | 0.00 | 0.00 |
| October | 81.36 | 47.47 | 33.89 | 121.11 | 62.77 | 0.00 | 0.00 | 0.00 |
| November | 67.84 | 41.14 | 26.70 | 80.36 | 109.21 | 0.00 | 0.00 | 0.00 |
| December | 55.05 | 29.90 | 25.14 | 53.69 | 136.63 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 85.08 | 46.13 | 38.94 | 132.42 | 66.79 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 55.05 | 29.90 | 25.14 | 53.69 | 10.53 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 110.31 | 58.95 | 51.37 | 211.20 | 136.63 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MWINDOW1 W NWA
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 58.11 | 32.75 | 25.35 | 64.91 | 115.61 | 0.00 | 0.00 | 0.00 |
| February | 65.40 | 34.70 | 30.70 | 78.17 | 103.98 | 0.00 | 0.00 | 0.00 |
| March | 89.22 | 47.81 | 41.41 | 116.90 | 89.34 | 0.00 | 0.00 | 0.00 |
| April | 102.43 | 55.24 | 47.18 | 156.17 | 54.25 | 0.00 | 0.00 | 0.00 |
| May | 110.31 | 58.95 | 51.37 | 189.30 | 31.26 | 0.00 | 0.00 | 0.00 |
| June | 107.65 | 57.86 | 49.79 | 211.12 | 14.33 | 0.00 | 0.00 | 0.00 |
| July | 95.60 | 47.56 | 48.05 | 189.24 | 10.53 | 0.00 | 0.00 | 0.00 |
| August | 92.37 | 47.02 | 45.36 | 174.85 | 16.13 | 0.00 | 0.00 | 0.00 |
| September | 94.73 | 52.85 | 41.88 | 167.79 | 34.72 | 0.00 | 0.00 | 0.00 |
| October | 81.36 | 47.47 | 33.89 | 123.37 | 60.71 | 0.00 | 0.00 | 0.00 |
| November | 67.84 | 41.14 | 26.70 | 85.07 | 99.89 | 0.00 | 0.00 | 0.00 |
| December | 55.05 | 29.90 | 25.14 | 58.18 | 127.45 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 85.08 | 46.13 | 38.94 | 134.83 | 62.98 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 55.05 | 29.90 | 25.14 | 58.18 | 10.53 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 110.31 | 58.95 | 51.37 | 211.12 | 127.45 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MWINDOW1 N NWA
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 31.32 | 0.00 | 31.32 | 5.73 | 185.24 | 0.00 | 0.00 | 0.00 |
| February | 38.24 | 0.00 | 38.24 | 16.30 | 164.54 | 0.00 | 0.00 | 0.00 |
| March | 50.06 | 0.01 | 50.06 | 33.62 | 140.81 | 0.00 | 0.00 | 0.00 |
| April | 57.98 | 0.63 | 57.35 | 65.73 | 82.41 | 0.00 | 0.00 | 0.00 |
| May | 68.64 | 5.06 | 63.58 | 113.35 | 44.60 | 0.00 | 0.00 | 0.00 |
| June | 72.72 | 8.82 | 63.90 | 162.00 | 20.73 | 0.00 | 0.00 | 0.00 |
| July | 67.08 | 6.26 | 60.82 | 150.36 | 15.36 | 0.00 | 0.00 | 0.00 |
| August | 57.15 | 1.47 | 55.67 | 117.06 | 23.60 | 0.00 | 0.00 | 0.00 |
| September | 49.61 | 0.05 | 49.56 | 86.10 | 52.94 | 0.00 | 0.00 | 0.00 |
| October | 41.14 | 0.00 | 41.14 | 41.74 | 94.77 | 0.00 | 0.00 | 0.00 |
| November | 33.21 | 0.00 | 33.21 | 10.58 | 160.26 | 0.00 | 0.00 | 0.00 |
| December | 31.07 | 0.00 | 31.07 | 3.86 | 206.23 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 49.91 | 1.87 | 48.04 | 67.47 | 98.98 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 31.07 | 0.00 | 31.07 | 3.86 | 15.36 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 72.72 | 8.82 | 63.90 | 162.00 | 206.23 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MWINDOW1 S SEA
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 212.47 | 160.54 | 51.93 | 283.96 | 171.00 | 0.00 | 0.00 | 0.00 |
| February | 202.34 | 143.70 | 58.64 | 275.14 | 154.79 | 0.00 | 0.00 | 0.00 |
| March | 157.89 | 89.51 | 68.38 | 219.14 | 137.96 | 0.00 | 0.00 | 0.00 |
| April | 112.04 | 43.39 | 68.65 | 177.58 | 85.05 | 0.00 | 0.00 | 0.00 |
| May | 77.50 | 10.94 | 66.56 | 139.54 | 47.86 | 0.00 | 0.00 | 0.00 |
| June | 67.08 | 4.56 | 62.53 | 154.32 | 21.28 | 0.00 | 0.00 | 0.00 |
| July | 68.31 | 6.56 | 61.75 | 157.08 | 15.91 | 0.00 | 0.00 | 0.00 |
| August | 85.66 | 21.87 | 63.79 | 181.31 | 24.69 | 0.00 | 0.00 | 0.00 |
| September | 137.12 | 72.04 | 65.07 | 258.38 | 52.65 | 0.00 | 0.00 | 0.00 |
| October | 184.46 | 124.87 | 59.60 | 293.45 | 90.22 | 0.00 | 0.00 | 0.00 |
| November | 223.02 | 170.40 | 52.61 | 312.47 | 148.23 | 0.00 | 0.00 | 0.00 |
| December | 219.07 | 164.36 | 54.71 | 287.14 | 183.83 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 145.23 | 84.04 | 61.20 | 227.94 | 94.15 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 67.08 | 4.56 | 51.93 | 139.54 | 15.91 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 223.02 | 170.40 | 68.65 | 312.47 | 183.83 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MWINDOW1 E SEA
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 55.33 | 30.11 | 25.21 | 50.22 | 120.51 | 0.00 | 0.00 | 0.00 |
| February | 73.58 | 41.85 | 31.73 | 79.44 | 105.75 | 0.00 | 0.00 | 0.00 |
| March | 90.84 | 49.92 | 40.92 | 109.31 | 88.10 | 0.00 | 0.00 | 0.00 |
| April | 109.73 | 60.95 | 48.78 | 161.34 | 50.60 | 0.00 | 0.00 | 0.00 |
| May | 113.13 | 61.45 | 51.68 | 190.89 | 28.68 | 0.00 | 0.00 | 0.00 |
| June | 113.31 | 63.06 | 50.25 | 219.05 | 13.08 | 0.00 | 0.00 | 0.00 |
| July | 101.74 | 53.27 | 48.46 | 198.69 | 9.88 | 0.00 | 0.00 | 0.00 |
| August | 96.64 | 49.43 | 47.21 | 179.94 | 15.05 | 0.00 | 0.00 | 0.00 |
| September | 95.76 | 54.62 | 41.14 | 163.87 | 32.35 | 0.00 | 0.00 | 0.00 |
| October | 73.53 | 39.64 | 33.90 | 102.53 | 59.76 | 0.00 | 0.00 | 0.00 |
| November | 65.99 | 38.40 | 27.60 | 69.03 | 103.37 | 0.00 | 0.00 | 0.00 |
| December | 55.01 | 29.13 | 25.89 | 47.09 | 132.13 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 87.06 | 47.63 | 39.43 | 131.13 | 63.07 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 55.01 | 29.13 | 25.21 | 47.09 | 9.88 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 113.31 | 63.06 | 51.68 | 219.05 | 132.13 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MWINDOW1 E NEA
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 55.33 | 30.11 | 25.21 | 54.10 | 109.33 | 0.00 | 0.00 | 0.00 |
| February | 73.58 | 41.85 | 31.73 | 84.24 | 96.67 | 0.00 | 0.00 | 0.00 |
| March | 90.84 | 49.92 | 40.92 | 113.34 | 83.06 | 0.00 | 0.00 | 0.00 |
| April | 109.73 | 60.95 | 48.78 | 162.76 | 49.62 | 0.00 | 0.00 | 0.00 |
| May | 113.13 | 61.45 | 51.68 | 191.12 | 28.63 | 0.00 | 0.00 | 0.00 |
| June | 113.31 | 63.06 | 50.25 | 218.96 | 13.11 | 0.00 | 0.00 | 0.00 |
| July | 101.74 | 53.27 | 48.46 | 198.74 | 9.88 | 0.00 | 0.00 | 0.00 |
| August | 96.64 | 49.43 | 47.21 | 180.58 | 14.89 | 0.00 | 0.00 | 0.00 |
| September | 95.76 | 54.62 | 41.14 | 165.31 | 31.67 | 0.00 | 0.00 | 0.00 |
| October | 73.53 | 39.64 | 33.90 | 104.82 | 57.69 | 0.00 | 0.00 | 0.00 |
| November | 65.99 | 38.40 | 27.60 | 73.94 | 93.85 | 0.00 | 0.00 | 0.00 |
| December | 55.01 | 29.13 | 25.89 | 50.22 | 121.19 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 87.06 | 47.63 | 39.43 | 133.34 | 58.96 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 55.01 | 29.13 | 25.21 | 50.22 | 9.88 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 113.31 | 63.06 | 51.68 | 218.96 | 121.19 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MWINDOW1 N NEA
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 31.32 | 0.00 | 31.32 | 5.54 | 184.38 | 0.00 | 0.00 | 0.00 |
| February | 38.24 | 0.00 | 38.24 | 15.56 | 164.51 | 0.00 | 0.00 | 0.00 |
| March | 50.06 | 0.01 | 50.06 | 32.43 | 140.67 | 0.00 | 0.00 | 0.00 |
| April | 57.98 | 0.63 | 57.35 | 64.69 | 82.31 | 0.00 | 0.00 | 0.00 |
| May | 68.64 | 5.06 | 63.58 | 112.70 | 44.26 | 0.00 | 0.00 | 0.00 |
| June | 72.72 | 8.82 | 63.90 | 161.56 | 20.52 | 0.00 | 0.00 | 0.00 |
| July | 67.08 | 6.26 | 60.82 | 150.02 | 15.18 | 0.00 | 0.00 | 0.00 |
| August | 57.15 | 1.47 | 55.67 | 116.72 | 23.41 | 0.00 | 0.00 | 0.00 |
| September | 49.61 | 0.05 | 49.56 | 85.68 | 52.62 | 0.00 | 0.00 | 0.00 |
| October | 41.14 | 0.00 | 41.14 | 41.34 | 94.13 | 0.00 | 0.00 | 0.00 |
| November | 33.21 | 0.00 | 33.21 | 10.03 | 159.28 | 0.00 | 0.00 | 0.00 |
| December | 31.07 | 0.00 | 31.07 | 3.65 | 205.81 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 49.91 | 1.87 | 48.04 | 66.93 | 98.61 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 31.07 | 0.00 | 31.07 | 3.65 | 15.18 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 72.72 | 8.82 | 63.90 | 161.56 | 205.81 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MWINDOW1 N N1A
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 31.32 | 0.00 | 31.32 | 5.31 | 188.38 | 0.00 | 0.00 | 0.00 |
| February | 38.24 | 0.00 | 38.24 | 15.54 | 168.59 | 0.00 | 0.00 | 0.00 |
| March | 50.06 | 0.01 | 50.06 | 32.49 | 144.75 | 0.00 | 0.00 | 0.00 |
| April | 57.98 | 0.63 | 57.35 | 66.12 | 83.16 | 0.00 | 0.00 | 0.00 |
| May | 68.64 | 5.06 | 63.58 | 114.93 | 44.02 | 0.00 | 0.00 | 0.00 |
| June | 72.72 | 8.82 | 63.90 | 164.53 | 20.11 | 0.00 | 0.00 | 0.00 |
| July | 67.08 | 6.26 | 60.82 | 152.71 | 14.79 | 0.00 | 0.00 | 0.00 |
| August | 57.15 | 1.47 | 55.67 | 119.11 | 23.07 | 0.00 | 0.00 | 0.00 |
| September | 49.61 | 0.05 | 49.56 | 87.43 | 52.33 | 0.00 | 0.00 | 0.00 |
| October | 41.14 | 0.00 | 41.14 | 41.82 | 95.88 | 0.00 | 0.00 | 0.00 |
| November | 33.21 | 0.00 | 33.21 | 9.75 | 165.03 | 0.00 | 0.00 | 0.00 |
| December | 31.07 | 0.00 | 31.07 | 3.50 | 209.85 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 49.91 | 1.87 | 48.04 | 68.04 | 100.50 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 31.07 | 0.00 | 31.07 | 3.50 | 14.79 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 72.72 | 8.82 | 63.90 | 164.53 | 209.85 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MWINDOW1 N N2A
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 31.32 | 0.00 | 31.32 | 5.31 | 188.30 | 0.00 | 0.00 | 0.00 |
| February | 38.24 | 0.00 | 38.24 | 15.49 | 168.63 | 0.00 | 0.00 | 0.00 |
| March | 50.06 | 0.01 | 50.06 | 32.40 | 144.80 | 0.00 | 0.00 | 0.00 |
| April | 57.98 | 0.63 | 57.35 | 66.06 | 83.18 | 0.00 | 0.00 | 0.00 |
| May | 68.64 | 5.06 | 63.58 | 114.90 | 44.01 | 0.00 | 0.00 | 0.00 |
| June | 72.72 | 8.82 | 63.90 | 164.51 | 20.10 | 0.00 | 0.00 | 0.00 |
| July | 67.08 | 6.26 | 60.82 | 152.70 | 14.79 | 0.00 | 0.00 | 0.00 |
| August | 57.15 | 1.47 | 55.67 | 119.10 | 23.06 | 0.00 | 0.00 | 0.00 |
| September | 49.61 | 0.05 | 49.56 | 87.42 | 52.32 | 0.00 | 0.00 | 0.00 |
| October | 41.14 | 0.00 | 41.14 | 41.80 | 95.85 | 0.00 | 0.00 | 0.00 |
| November | 33.21 | 0.00 | 33.21 | 9.73 | 164.95 | 0.00 | 0.00 | 0.00 |
| December | 31.07 | 0.00 | 31.07 | 3.49 | 209.83 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 49.91 | 1.87 | 48.04 | 68.02 | 100.49 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 31.07 | 0.00 | 31.07 | 3.49 | 14.79 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 72.72 | 8.82 | 63.90 | 164.51 | 209.83 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MWINDOW1 S S1A
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 212.47 | 160.54 | 51.93 | 281.21 | 179.46 | 0.00 | 0.00 | 0.00 |
| February | 202.34 | 143.70 | 58.64 | 273.35 | 161.59 | 0.00 | 0.00 | 0.00 |
| March | 157.89 | 89.51 | 68.38 | 218.36 | 142.61 | 0.00 | 0.00 | 0.00 |
| April | 112.04 | 43.39 | 68.65 | 178.83 | 85.96 | 0.00 | 0.00 | 0.00 |
| May | 77.50 | 10.94 | 66.56 | 141.72 | 47.56 | 0.00 | 0.00 | 0.00 |
| June | 67.08 | 4.56 | 62.53 | 157.33 | 20.86 | 0.00 | 0.00 | 0.00 |
| July | 68.31 | 6.56 | 61.75 | 159.77 | 15.51 | 0.00 | 0.00 | 0.00 |
| August | 85.66 | 21.87 | 63.79 | 183.59 | 24.34 | 0.00 | 0.00 | 0.00 |
| September | 137.12 | 72.04 | 65.07 | 260.01 | 52.44 | 0.00 | 0.00 | 0.00 |
| October | 184.46 | 124.87 | 59.60 | 293.88 | 91.46 | 0.00 | 0.00 | 0.00 |
| November | 223.02 | 170.40 | 52.61 | 311.15 | 153.36 | 0.00 | 0.00 | 0.00 |
| December | 219.07 | 164.36 | 54.71 | 284.15 | 191.76 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 145.23 | 84.04 | 61.20 | 228.27 | 96.92 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 67.08 | 4.56 | 51.93 | 141.72 | 15.51 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 223.02 | 170.40 | 68.65 | 311.15 | 191.76 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MWINDOW1 S S2A
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 212.47 | 160.54 | 51.93 | 281.19 | 179.42 | 0.00 | 0.00 | 0.00 |
| February | 202.34 | 143.70 | 58.64 | 273.27 | 161.65 | 0.00 | 0.00 | 0.00 |
| March | 157.89 | 89.51 | 68.38 | 218.29 | 142.61 | 0.00 | 0.00 | 0.00 |
| April | 112.04 | 43.39 | 68.65 | 178.79 | 85.96 | 0.00 | 0.00 | 0.00 |
| May | 77.50 | 10.94 | 66.56 | 141.70 | 47.55 | 0.00 | 0.00 | 0.00 |
| June | 67.08 | 4.56 | 62.53 | 157.31 | 20.86 | 0.00 | 0.00 | 0.00 |
| July | 68.31 | 6.56 | 61.75 | 159.76 | 15.50 | 0.00 | 0.00 | 0.00 |
| August | 85.66 | 21.87 | 63.79 | 183.57 | 24.33 | 0.00 | 0.00 | 0.00 |
| September | 137.12 | 72.04 | 65.07 | 260.00 | 52.43 | 0.00 | 0.00 | 0.00 |
| October | 184.46 | 124.87 | 59.60 | 293.88 | 91.44 | 0.00 | 0.00 | 0.00 |
| November | 223.02 | 170.40 | 52.61 | 311.14 | 153.33 | 0.00 | 0.00 | 0.00 |
| December | 219.07 | 164.36 | 54.71 | 284.11 | 191.76 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 145.23 | 84.04 | 61.20 | 228.24 | 96.92 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 67.08 | 4.56 | 51.93 | 141.70 | 15.50 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 223.02 | 170.40 | 68.65 | 311.14 | 191.76 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: TWINDOW1 S SWA
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 212.47 | 160.54 | 51.93 | 285.91 | 159.43 | 0.00 | 0.00 | 0.00 |
| February | 202.34 | 143.70 | 58.64 | 278.48 | 141.65 | 0.00 | 0.00 | 0.00 |
| March | 157.89 | 89.51 | 68.38 | 223.06 | 125.41 | 0.00 | 0.00 | 0.00 |
| April | 112.04 | 43.39 | 68.65 | 178.39 | 77.22 | 0.00 | 0.00 | 0.00 |
| May | 77.50 | 10.94 | 66.56 | 137.28 | 44.81 | 0.00 | 0.00 | 0.00 |
| June | 67.08 | 4.56 | 62.53 | 149.60 | 20.62 | 0.00 | 0.00 | 0.00 |
| July | 68.31 | 6.56 | 61.75 | 152.10 | 15.62 | 0.00 | 0.00 | 0.00 |
| August | 85.66 | 21.87 | 63.79 | 176.88 | 23.90 | 0.00 | 0.00 | 0.00 |
| September | 137.12 | 72.04 | 65.07 | 255.11 | 50.26 | 0.00 | 0.00 | 0.00 |
| October | 184.46 | 124.87 | 59.60 | 294.61 | 81.59 | 0.00 | 0.00 | 0.00 |
| November | 223.02 | 170.40 | 52.61 | 316.53 | 133.79 | 0.00 | 0.00 | 0.00 |
| December | 219.07 | 164.36 | 54.71 | 289.36 | 172.44 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 145.23 | 84.04 | 61.20 | 227.73 | 86.96 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 67.08 | 4.56 | 51.93 | 137.28 | 15.62 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 223.02 | 170.40 | 68.65 | 316.53 | 172.44 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: TWINDOW1 W SWA
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 58.11 | 32.75 | 25.35 | 59.34 | 115.71 | 0.00 | 0.00 | 0.00 |
| February | 65.40 | 34.70 | 30.70 | 72.87 | 102.15 | 0.00 | 0.00 | 0.00 |
| March | 89.22 | 47.81 | 41.41 | 113.15 | 84.52 | 0.00 | 0.00 | 0.00 |
| April | 102.43 | 55.24 | 47.18 | 154.19 | 49.64 | 0.00 | 0.00 | 0.00 |
| May | 110.31 | 58.95 | 51.37 | 186.87 | 28.98 | 0.00 | 0.00 | 0.00 |
| June | 107.65 | 57.86 | 49.79 | 207.58 | 13.72 | 0.00 | 0.00 | 0.00 |
| July | 95.60 | 47.56 | 48.05 | 185.59 | 10.20 | 0.00 | 0.00 | 0.00 |
| August | 92.37 | 47.02 | 45.36 | 170.97 | 15.63 | 0.00 | 0.00 | 0.00 |
| September | 94.73 | 52.85 | 41.88 | 163.79 | 33.43 | 0.00 | 0.00 | 0.00 |
| October | 81.36 | 47.47 | 33.89 | 120.72 | 55.57 | 0.00 | 0.00 | 0.00 |
| November | 67.84 | 41.14 | 26.70 | 80.18 | 96.76 | 0.00 | 0.00 | 0.00 |
| December | 55.05 | 29.90 | 25.14 | 53.04 | 127.14 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 85.08 | 46.13 | 38.94 | 130.94 | 60.92 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 55.05 | 29.90 | 25.14 | 53.04 | 10.20 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 110.31 | 58.95 | 51.37 | 207.58 | 127.14 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: TWINDOW1 W NWA
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 58.11 | 32.75 | 25.35 | 65.18 | 109.51 | 0.00 | 0.00 | 0.00 |
| February | 65.40 | 34.70 | 30.70 | 78.57 | 97.36 | 0.00 | 0.00 | 0.00 |
| March | 89.22 | 47.81 | 41.41 | 117.71 | 81.67 | 0.00 | 0.00 | 0.00 |
| April | 102.43 | 55.24 | 47.18 | 156.31 | 48.83 | 0.00 | 0.00 | 0.00 |
| May | 110.31 | 58.95 | 51.37 | 187.19 | 29.01 | 0.00 | 0.00 | 0.00 |
| June | 107.65 | 57.86 | 49.79 | 207.44 | 13.78 | 0.00 | 0.00 | 0.00 |
| July | 95.60 | 47.56 | 48.05 | 185.65 | 10.23 | 0.00 | 0.00 | 0.00 |
| August | 92.37 | 47.02 | 45.36 | 171.84 | 15.51 | 0.00 | 0.00 | 0.00 |
| September | 94.73 | 52.85 | 41.88 | 165.98 | 32.71 | 0.00 | 0.00 | 0.00 |
| October | 81.36 | 47.47 | 33.89 | 124.84 | 53.05 | 0.00 | 0.00 | 0.00 |
| November | 67.84 | 41.14 | 26.70 | 86.42 | 90.99 | 0.00 | 0.00 | 0.00 |
| December | 55.05 | 29.90 | 25.14 | 58.65 | 120.80 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 85.08 | 46.13 | 38.94 | 134.05 | 58.43 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 55.05 | 29.90 | 25.14 | 58.65 | 10.23 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 110.31 | 58.95 | 51.37 | 207.44 | 120.80 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: TWINDOW1 N NWA
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 31.32 | 0.00 | 31.32 | 6.29 | 176.09 | 0.00 | 0.00 | 0.00 |
| February | 38.24 | 0.00 | 38.24 | 17.21 | 154.67 | 0.00 | 0.00 | 0.00 |
| March | 50.06 | 0.01 | 50.06 | 35.48 | 129.45 | 0.00 | 0.00 | 0.00 |
| April | 57.98 | 0.63 | 57.35 | 66.48 | 74.33 | 0.00 | 0.00 | 0.00 |
| May | 68.64 | 5.06 | 63.58 | 111.39 | 41.94 | 0.00 | 0.00 | 0.00 |
| June | 72.72 | 8.82 | 63.90 | 156.86 | 20.07 | 0.00 | 0.00 | 0.00 |
| July | 67.08 | 6.26 | 60.82 | 145.21 | 15.03 | 0.00 | 0.00 | 0.00 |
| August | 57.15 | 1.47 | 55.67 | 112.85 | 22.78 | 0.00 | 0.00 | 0.00 |
| September | 49.61 | 0.05 | 49.56 | 83.68 | 50.02 | 0.00 | 0.00 | 0.00 |
| October | 41.14 | 0.00 | 41.14 | 44.19 | 83.12 | 0.00 | 0.00 | 0.00 |
| November | 33.21 | 0.00 | 33.21 | 12.44 | 146.50 | 0.00 | 0.00 | 0.00 |
| December | 31.07 | 0.00 | 31.07 | 4.35 | 196.08 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 49.91 | 1.87 | 48.04 | 66.62 | 92.21 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 31.07 | 0.00 | 31.07 | 4.35 | 15.03 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 72.72 | 8.82 | 63.90 | 156.86 | 196.08 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: TWINDOW1 S SEA
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 212.47 | 160.54 | 51.93 | 284.66 | 158.28 | 0.00 | 0.00 | 0.00 |
| February | 202.34 | 143.70 | 58.64 | 276.38 | 140.85 | 0.00 | 0.00 | 0.00 |
| March | 157.89 | 89.51 | 68.38 | 220.68 | 124.12 | 0.00 | 0.00 | 0.00 |
| April | 112.04 | 43.39 | 68.65 | 176.13 | 76.40 | 0.00 | 0.00 | 0.00 |
| May | 77.50 | 10.94 | 66.56 | 135.96 | 44.28 | 0.00 | 0.00 | 0.00 |
| June | 67.08 | 4.56 | 62.53 | 148.97 | 20.31 | 0.00 | 0.00 | 0.00 |
| July | 68.31 | 6.56 | 61.75 | 151.65 | 15.37 | 0.00 | 0.00 | 0.00 |
| August | 85.66 | 21.87 | 63.79 | 176.39 | 23.63 | 0.00 | 0.00 | 0.00 |
| September | 137.12 | 72.04 | 65.07 | 254.21 | 49.65 | 0.00 | 0.00 | 0.00 |
| October | 184.46 | 124.87 | 59.60 | 293.62 | 80.36 | 0.00 | 0.00 | 0.00 |
| November | 223.02 | 170.40 | 52.61 | 315.04 | 132.60 | 0.00 | 0.00 | 0.00 |
| December | 219.07 | 164.36 | 54.71 | 288.11 | 171.36 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 145.23 | 84.04 | 61.20 | 226.44 | 86.17 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 67.08 | 4.56 | 51.93 | 135.96 | 15.37 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 223.02 | 170.40 | 68.65 | 315.04 | 171.36 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: TWINDOW1 E SEA
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 55.33 | 30.11 | 25.21 | 51.51 | 112.76 | 0.00 | 0.00 | 0.00 |
| February | 73.58 | 41.85 | 31.73 | 80.92 | 97.03 | 0.00 | 0.00 | 0.00 |
| March | 90.84 | 49.92 | 40.92 | 111.42 | 79.82 | 0.00 | 0.00 | 0.00 |
| April | 109.73 | 60.95 | 48.78 | 161.64 | 46.07 | 0.00 | 0.00 | 0.00 |
| May | 113.13 | 61.45 | 51.68 | 188.98 | 26.91 | 0.00 | 0.00 | 0.00 |
| June | 113.31 | 63.06 | 50.25 | 215.31 | 12.53 | 0.00 | 0.00 | 0.00 |
| July | 101.74 | 53.27 | 48.46 | 194.92 | 9.57 | 0.00 | 0.00 | 0.00 |
| August | 96.64 | 49.43 | 47.21 | 176.65 | 14.46 | 0.00 | 0.00 | 0.00 |
| September | 95.76 | 54.62 | 41.14 | 161.51 | 30.75 | 0.00 | 0.00 | 0.00 |
| October | 73.53 | 39.64 | 33.90 | 103.05 | 53.50 | 0.00 | 0.00 | 0.00 |
| November | 65.99 | 38.40 | 27.60 | 70.99 | 93.18 | 0.00 | 0.00 | 0.00 |
| December | 55.01 | 29.13 | 25.89 | 48.45 | 124.56 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 87.06 | 47.63 | 39.43 | 130.61 | 58.25 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 55.01 | 29.13 | 25.21 | 48.45 | 9.57 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 113.31 | 63.06 | 51.68 | 215.31 | 124.56 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: TWINDOW1 E NEA
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 55.33 | 30.11 | 25.21 | 55.09 | 103.86 | 0.00 | 0.00 | 0.00 |
| February | 73.58 | 41.85 | 31.73 | 85.56 | 90.66 | 0.00 | 0.00 | 0.00 |
| March | 90.84 | 49.92 | 40.92 | 115.43 | 76.14 | 0.00 | 0.00 | 0.00 |
| April | 109.73 | 60.95 | 48.78 | 163.61 | 45.15 | 0.00 | 0.00 | 0.00 |
| May | 113.13 | 61.45 | 51.68 | 189.29 | 26.92 | 0.00 | 0.00 | 0.00 |
| June | 113.31 | 63.06 | 50.25 | 215.19 | 12.58 | 0.00 | 0.00 | 0.00 |
| July | 101.74 | 53.27 | 48.46 | 194.99 | 9.58 | 0.00 | 0.00 | 0.00 |
| August | 96.64 | 49.43 | 47.21 | 177.54 | 14.33 | 0.00 | 0.00 | 0.00 |
| September | 95.76 | 54.62 | 41.14 | 163.68 | 30.05 | 0.00 | 0.00 | 0.00 |
| October | 73.53 | 39.64 | 33.90 | 106.98 | 50.68 | 0.00 | 0.00 | 0.00 |
| November | 65.99 | 38.40 | 27.60 | 76.17 | 85.54 | 0.00 | 0.00 | 0.00 |
| December | 55.01 | 29.13 | 25.89 | 51.42 | 115.20 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 87.06 | 47.63 | 39.43 | 133.06 | 54.89 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 55.01 | 29.13 | 25.21 | 51.42 | 9.58 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 113.31 | 63.06 | 51.68 | 215.19 | 115.20 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: TWINDOW1 N NEA
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 31.32 | 0.00 | 31.32 | 5.92 | 175.00 | 0.00 | 0.00 | 0.00 |
| February | 38.24 | 0.00 | 38.24 | 16.09 | 153.98 | 0.00 | 0.00 | 0.00 |
| March | 50.06 | 0.01 | 50.06 | 33.63 | 128.09 | 0.00 | 0.00 | 0.00 |
| April | 57.98 | 0.63 | 57.35 | 64.23 | 73.53 | 0.00 | 0.00 | 0.00 |
| May | 68.64 | 5.06 | 63.58 | 109.91 | 41.29 | 0.00 | 0.00 | 0.00 |
| June | 72.72 | 8.82 | 63.90 | 156.21 | 19.74 | 0.00 | 0.00 | 0.00 |
| July | 67.08 | 6.26 | 60.82 | 144.72 | 14.76 | 0.00 | 0.00 | 0.00 |
| August | 57.15 | 1.47 | 55.67 | 112.32 | 22.50 | 0.00 | 0.00 | 0.00 |
| September | 49.61 | 0.05 | 49.56 | 82.74 | 49.46 | 0.00 | 0.00 | 0.00 |
| October | 41.14 | 0.00 | 41.14 | 42.84 | 81.64 | 0.00 | 0.00 | 0.00 |
| November | 33.21 | 0.00 | 33.21 | 11.36 | 144.57 | 0.00 | 0.00 | 0.00 |
| December | 31.07 | 0.00 | 31.07 | 4.06 | 195.42 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 49.91 | 1.87 | 48.04 | 65.60 | 91.37 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 31.07 | 0.00 | 31.07 | 4.06 | 14.76 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 72.72 | 8.82 | 63.90 | 156.21 | 195.42 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: TWINDOW1 N N1A
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 31.32 | 0.00 | 31.32 | 6.16 | 177.84 | 0.00 | 0.00 | 0.00 |
| February | 38.24 | 0.00 | 38.24 | 17.23 | 156.25 | 0.00 | 0.00 | 0.00 |
| March | 50.06 | 0.01 | 50.06 | 35.85 | 130.29 | 0.00 | 0.00 | 0.00 |
| April | 57.98 | 0.63 | 57.35 | 67.34 | 75.11 | 0.00 | 0.00 | 0.00 |
| May | 68.64 | 5.06 | 63.58 | 113.17 | 41.93 | 0.00 | 0.00 | 0.00 |
| June | 72.72 | 8.82 | 63.90 | 160.08 | 19.73 | 0.00 | 0.00 | 0.00 |
| July | 67.08 | 6.26 | 60.82 | 148.24 | 14.67 | 0.00 | 0.00 | 0.00 |
| August | 57.15 | 1.47 | 55.67 | 115.51 | 22.59 | 0.00 | 0.00 | 0.00 |
| September | 49.61 | 0.05 | 49.56 | 85.39 | 50.06 | 0.00 | 0.00 | 0.00 |
| October | 41.14 | 0.00 | 41.14 | 44.45 | 84.66 | 0.00 | 0.00 | 0.00 |
| November | 33.21 | 0.00 | 33.21 | 12.44 | 147.26 | 0.00 | 0.00 | 0.00 |
| December | 31.07 | 0.00 | 31.07 | 4.23 | 198.34 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 49.91 | 1.87 | 48.04 | 67.77 | 92.93 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 31.07 | 0.00 | 31.07 | 4.23 | 14.67 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 72.72 | 8.82 | 63.90 | 160.08 | 198.34 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: TWINDOW1 N N2A
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 31.32 | 0.00 | 31.32 | 6.14 | 177.76 | 0.00 | 0.00 | 0.00 |
| February | 38.24 | 0.00 | 38.24 | 17.14 | 156.20 | 0.00 | 0.00 | 0.00 |
| March | 50.06 | 0.01 | 50.06 | 35.69 | 130.20 | 0.00 | 0.00 | 0.00 |
| April | 57.98 | 0.63 | 57.35 | 67.16 | 75.06 | 0.00 | 0.00 | 0.00 |
| May | 68.64 | 5.06 | 63.58 | 113.08 | 41.90 | 0.00 | 0.00 | 0.00 |
| June | 72.72 | 8.82 | 63.90 | 160.05 | 19.71 | 0.00 | 0.00 | 0.00 |
| July | 67.08 | 6.26 | 60.82 | 148.21 | 14.66 | 0.00 | 0.00 | 0.00 |
| August | 57.15 | 1.47 | 55.67 | 115.48 | 22.57 | 0.00 | 0.00 | 0.00 |
| September | 49.61 | 0.05 | 49.56 | 85.33 | 50.02 | 0.00 | 0.00 | 0.00 |
| October | 41.14 | 0.00 | 41.14 | 44.35 | 84.52 | 0.00 | 0.00 | 0.00 |
| November | 33.21 | 0.00 | 33.21 | 12.35 | 147.11 | 0.00 | 0.00 | 0.00 |
| December | 31.07 | 0.00 | 31.07 | 4.21 | 198.30 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 49.91 | 1.87 | 48.04 | 67.69 | 92.87 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 31.07 | 0.00 | 31.07 | 4.21 | 14.66 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 72.72 | 8.82 | 63.90 | 160.05 | 198.30 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: TWINDOW1 S S1A
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 212.47 | 160.54 | 51.93 | 284.28 | 163.06 | 0.00 | 0.00 | 0.00 |
| February | 202.34 | 143.70 | 58.64 | 276.97 | 145.02 | 0.00 | 0.00 | 0.00 |
| March | 157.89 | 89.51 | 68.38 | 222.31 | 127.76 | 0.00 | 0.00 | 0.00 |
| April | 112.04 | 43.39 | 68.65 | 178.92 | 78.27 | 0.00 | 0.00 | 0.00 |
| May | 77.50 | 10.94 | 66.56 | 139.26 | 44.95 | 0.00 | 0.00 | 0.00 |
| June | 67.08 | 4.56 | 62.53 | 152.95 | 20.33 | 0.00 | 0.00 | 0.00 |
| July | 68.31 | 6.56 | 61.75 | 155.20 | 15.28 | 0.00 | 0.00 | 0.00 |
| August | 85.66 | 21.87 | 63.79 | 179.45 | 23.72 | 0.00 | 0.00 | 0.00 |
| September | 137.12 | 72.04 | 65.07 | 256.63 | 50.33 | 0.00 | 0.00 | 0.00 |
| October | 184.46 | 124.87 | 59.60 | 294.34 | 83.66 | 0.00 | 0.00 | 0.00 |
| November | 223.02 | 170.40 | 52.61 | 315.30 | 137.02 | 0.00 | 0.00 | 0.00 |
| December | 219.07 | 164.36 | 54.71 | 287.54 | 176.10 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 145.23 | 84.04 | 61.20 | 228.23 | 88.52 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 67.08 | 4.56 | 51.93 | 139.26 | 15.28 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 223.02 | 170.40 | 68.65 | 315.30 | 176.10 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: TWINDOW1 S S2A
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 212.47 | 160.54 | 51.93 | 284.19 | 162.97 | 0.00 | 0.00 | 0.00 |
| February | 202.34 | 143.70 | 58.64 | 276.82 | 144.99 | 0.00 | 0.00 | 0.00 |
| March | 157.89 | 89.51 | 68.38 | 222.14 | 127.68 | 0.00 | 0.00 | 0.00 |
| April | 112.04 | 43.39 | 68.65 | 178.76 | 78.22 | 0.00 | 0.00 | 0.00 |
| May | 77.50 | 10.94 | 66.56 | 139.18 | 44.92 | 0.00 | 0.00 | 0.00 |
| June | 67.08 | 4.56 | 62.53 | 152.91 | 20.31 | 0.00 | 0.00 | 0.00 |
| July | 68.31 | 6.56 | 61.75 | 155.18 | 15.27 | 0.00 | 0.00 | 0.00 |
| August | 85.66 | 21.87 | 63.79 | 179.42 | 23.71 | 0.00 | 0.00 | 0.00 |
| September | 137.12 | 72.04 | 65.07 | 256.58 | 50.29 | 0.00 | 0.00 | 0.00 |
| October | 184.46 | 124.87 | 59.60 | 294.30 | 83.56 | 0.00 | 0.00 | 0.00 |
| November | 223.02 | 170.40 | 52.61 | 315.21 | 136.93 | 0.00 | 0.00 | 0.00 |
| December | 219.07 | 164.36 | 54.71 | 287.45 | 176.02 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 145.23 | 84.04 | 61.20 | 228.14 | 88.47 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 67.08 | 4.56 | 51.93 | 139.18 | 15.27 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 223.02 | 170.40 | 68.65 | 315.21 | 176.02 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: TWINDOW14
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 13.28 | 7.23 | 6.05 | 12.55 | 27.67 | 20.33 | 0.00 | 0.00 |
| February | 17.66 | 10.04 | 7.61 | 19.80 | 24.26 | 2.83 | 0.00 | 0.00 |
| March | 21.80 | 11.98 | 9.82 | 26.92 | 20.55 | 1.00 | 0.00 | 0.00 |
| April | 26.33 | 14.63 | 11.70 | 38.17 | 12.62 | 16.83 | 0.00 | 0.00 |
| May | 27.14 | 14.75 | 12.40 | 43.92 | 7.87 | 35.33 | 0.00 | 0.00 |
| June | 27.19 | 15.13 | 12.06 | 49.43 | 4.13 | 24.17 | 0.00 | 0.00 |
| July | 24.41 | 12.78 | 11.63 | 44.44 | 3.46 | 135.00 | 0.00 | 0.00 |
| August | 23.19 | 11.86 | 11.33 | 40.50 | 4.79 | 139.00 | 0.00 | 0.00 |
| September | 22.98 | 13.11 | 9.87 | 37.69 | 9.00 | 252.67 | 0.00 | 0.00 |
| October | 17.64 | 9.51 | 8.13 | 24.46 | 14.67 | 180.17 | 0.00 | 0.00 |
| November | 15.83 | 9.21 | 6.62 | 17.39 | 23.37 | 26.50 | 0.00 | 0.00 |
| December | 13.20 | 6.99 | 6.21 | 11.80 | 30.17 | 52.83 | 0.00 | 0.00 |
| Annual Sum or Average | 20.89 | 11.43 | 9.46 | 30.62 | 15.17 | 886.67 | 0.00 | 0.00 |
| Minimum of Months | 13.20 | 6.99 | 6.05 | 11.80 | 3.46 | 1.00 | 0.00 | 0.00 |
| Maximum of Months | 27.19 | 15.13 | 12.40 | 49.43 | 30.17 | 252.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ENTRANCE DOOR
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 39.54 | 21.52 | 18.02 | 38.59 | 79.84 | 0.00 | 0.00 | 0.00 |
| February | 52.58 | 29.91 | 22.68 | 60.96 | 69.35 | 0.00 | 0.00 | 0.00 |
| March | 64.92 | 35.68 | 29.24 | 82.90 | 57.67 | 0.00 | 0.00 | 0.00 |
| April | 78.42 | 43.56 | 34.86 | 114.87 | 37.42 | 0.00 | 0.00 | 0.00 |
| May | 80.84 | 43.91 | 36.93 | 130.24 | 24.88 | 0.00 | 0.00 | 0.00 |
| June | 80.97 | 45.06 | 35.91 | 145.16 | 14.00 | 0.00 | 0.00 | 0.00 |
| July | 72.71 | 38.07 | 34.63 | 130.24 | 12.02 | 9.33 | 0.00 | 0.00 |
| August | 69.06 | 35.32 | 33.74 | 118.49 | 16.51 | 0.00 | 0.00 | 0.00 |
| September | 68.43 | 39.03 | 29.40 | 110.27 | 29.75 | 4.50 | 0.00 | 0.00 |
| October | 52.55 | 28.33 | 24.22 | 70.65 | 47.76 | 0.67 | 0.00 | 0.00 |
| November | 47.16 | 27.44 | 19.72 | 50.54 | 74.37 | 0.00 | 0.00 | 0.00 |
| December | 39.31 | 20.81 | 18.50 | 35.79 | 88.81 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 62.22 | 34.04 | 28.18 | 90.81 | 45.92 | 14.50 | 0.00 | 0.00 |
| Minimum of Months | 39.31 | 20.81 | 18.02 | 35.79 | 12.02 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 80.97 | 45.06 | 36.93 | 145.16 | 88.81 | 9.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MWINDOW14
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 13.28 | 7.23 | 6.05 | 11.57 | 30.86 | 178.83 | 0.00 | 0.00 |
| February | 17.66 | 10.04 | 7.61 | 18.52 | 27.24 | 85.50 | 0.00 | 0.00 |
| March | 21.80 | 11.98 | 9.82 | 25.25 | 23.10 | 54.17 | 0.00 | 0.00 |
| April | 26.33 | 14.63 | 11.70 | 37.07 | 13.87 | 55.67 | 0.00 | 0.00 |
| May | 27.14 | 14.75 | 12.40 | 43.70 | 8.34 | 67.67 | 0.00 | 0.00 |
| June | 27.19 | 15.13 | 12.06 | 49.99 | 4.24 | 69.17 | 0.00 | 0.00 |
| July | 24.41 | 12.78 | 11.63 | 45.13 | 3.47 | 191.33 | 0.00 | 0.00 |
| August | 23.19 | 11.86 | 11.33 | 40.94 | 4.90 | 214.50 | 0.00 | 0.00 |
| September | 22.98 | 13.11 | 9.87 | 37.60 | 9.39 | 318.67 | 0.00 | 0.00 |
| October | 17.64 | 9.51 | 8.13 | 23.39 | 16.41 | 304.00 | 0.00 | 0.00 |
| November | 15.83 | 9.21 | 6.62 | 16.03 | 26.79 | 201.67 | 0.00 | 0.00 |
| December | 13.20 | 6.99 | 6.21 | 10.83 | 33.66 | 296.67 | 0.00 | 0.00 |
| Annual Sum or Average | 20.89 | 11.43 | 9.46 | 30.04 | 16.81 | 2037.83 | 0.00 | 0.00 |
| Minimum of Months | 13.20 | 6.99 | 6.05 | 10.83 | 3.47 | 54.17 | 0.00 | 0.00 |
| Maximum of Months | 27.19 | 15.13 | 12.40 | 49.99 | 33.66 | 318.67 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: GWINDOW1 S SWA
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.569082E+09 | 0.430004E+09 | 0.139079E+09 | 0.777333E+09 | 0.440293E+09 |
| February | 0.489495E+09 | 0.347638E+09 | 0.141858E+09 | 0.689091E+09 | 0.346042E+09 |
| March | 0.422895E+09 | 0.239752E+09 | 0.183143E+09 | 0.620690E+09 | 0.329556E+09 |
| April | 0.290400E+09 | 0.112456E+09 | 0.177944E+09 | 0.478859E+09 | 0.202640E+09 |
| May | 0.207588E+09 | 29308895.00 | 0.178279E+09 | 0.382597E+09 | 0.123078E+09 |
| June | 0.173878E+09 | 11809415.54 | 0.162068E+09 | 0.403764E+09 | 54325160.47 |
| July | 0.182972E+09 | 17574380.96 | 0.165397E+09 | 0.421129E+09 | 43755181.15 |
| August | 0.229443E+09 | 58582872.53 | 0.170860E+09 | 0.484395E+09 | 69022339.58 |
| September | 0.355405E+09 | 0.186733E+09 | 0.168672E+09 | 0.669971E+09 | 0.141931E+09 |
| October | 0.494068E+09 | 0.334439E+09 | 0.159628E+09 | 0.788169E+09 | 0.247096E+09 |
| November | 0.578056E+09 | 0.441679E+09 | 0.136377E+09 | 0.814016E+09 | 0.390025E+09 |
| December | 0.586752E+09 | 0.440209E+09 | 0.146543E+09 | 0.781425E+09 | 0.483105E+09 |
| Annual Sum or Average | 0.458003E+10 | 0.265019E+10 | 0.192985E+10 | 0.731144E+10 | 0.287087E+10 |
| Minimum of Months | 0.173878E+09 | 11809415.54 | 0.136377E+09 | 0.382597E+09 | 43755181.15 |
| Maximum of Months | 0.586752E+09 | 0.441679E+09 | 0.183143E+09 | 0.814016E+09 | 0.483105E+09 |
Report: WindowEnergyReportMonthly
For: GWINDOW1 W SWA
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.155634E+09 | 87728367.98 | 67905531.93 | 0.166810E+09 | 0.320324E+09 |
| February | 0.158206E+09 | 83935057.27 | 74271395.22 | 0.186311E+09 | 0.250540E+09 |
| March | 0.238956E+09 | 0.128054E+09 | 0.110902E+09 | 0.319666E+09 | 0.223992E+09 |
| April | 0.265486E+09 | 0.143191E+09 | 0.122295E+09 | 0.411682E+09 | 0.131325E+09 |
| May | 0.295459E+09 | 0.157880E+09 | 0.137579E+09 | 0.512546E+09 | 79968710.68 |
| June | 0.279027E+09 | 0.149962E+09 | 0.129065E+09 | 0.550427E+09 | 36043690.27 |
| July | 0.256063E+09 | 0.127377E+09 | 0.128686E+09 | 0.507317E+09 | 28572873.29 |
| August | 0.247408E+09 | 0.125926E+09 | 0.121481E+09 | 0.465746E+09 | 45130866.53 |
| September | 0.245542E+09 | 0.136979E+09 | 0.108562E+09 | 0.430426E+09 | 94726241.52 |
| October | 0.217902E+09 | 0.127131E+09 | 90770275.31 | 0.324494E+09 | 0.170644E+09 |
| November | 0.175845E+09 | 0.106629E+09 | 69216710.67 | 0.209126E+09 | 0.286091E+09 |
| December | 0.147434E+09 | 80086886.16 | 67346787.14 | 0.147430E+09 | 0.357169E+09 |
| Annual Sum or Average | 0.268296E+10 | 0.145488E+10 | 0.122808E+10 | 0.423198E+10 | 0.202453E+10 |
| Minimum of Months | 0.147434E+09 | 80086886.16 | 67346787.14 | 0.147430E+09 | 28572873.29 |
| Maximum of Months | 0.295459E+09 | 0.157880E+09 | 0.137579E+09 | 0.550427E+09 | 0.357169E+09 |
Report: WindowEnergyReportMonthly
For: GWINDOW1 W NWA
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.155634E+09 | 87728367.98 | 67905531.93 | 0.178429E+09 | 0.298341E+09 |
| February | 0.158206E+09 | 83935057.27 | 74271395.22 | 0.197676E+09 | 0.233535E+09 |
| March | 0.238956E+09 | 0.128054E+09 | 0.110902E+09 | 0.331512E+09 | 0.211524E+09 |
| April | 0.265486E+09 | 0.143191E+09 | 0.122295E+09 | 0.417634E+09 | 0.125799E+09 |
| May | 0.295459E+09 | 0.157880E+09 | 0.137579E+09 | 0.513443E+09 | 79553912.86 |
| June | 0.279027E+09 | 0.149962E+09 | 0.129065E+09 | 0.550091E+09 | 36227209.33 |
| July | 0.256063E+09 | 0.127377E+09 | 0.128686E+09 | 0.507402E+09 | 28623309.11 |
| August | 0.247408E+09 | 0.125926E+09 | 0.121481E+09 | 0.467548E+09 | 44542631.59 |
| September | 0.245542E+09 | 0.136979E+09 | 0.108562E+09 | 0.434260E+09 | 92342480.64 |
| October | 0.217902E+09 | 0.127131E+09 | 90770275.31 | 0.330401E+09 | 0.164721E+09 |
| November | 0.175845E+09 | 0.106629E+09 | 69216710.67 | 0.220539E+09 | 0.260633E+09 |
| December | 0.147434E+09 | 80086886.16 | 67346787.14 | 0.158098E+09 | 0.335408E+09 |
| Annual Sum or Average | 0.268296E+10 | 0.145488E+10 | 0.122808E+10 | 0.430703E+10 | 0.191125E+10 |
| Minimum of Months | 0.147434E+09 | 80086886.16 | 67346787.14 | 0.158098E+09 | 28623309.11 |
| Maximum of Months | 0.295459E+09 | 0.157880E+09 | 0.137579E+09 | 0.550091E+09 | 0.335408E+09 |
Report: WindowEnergyReportMonthly
For: GWINDOW1 N NWA
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 83878188.20 | 0.00 | 83878188.20 | 18282085.78 | 0.476643E+09 |
| February | 92512121.34 | 0.00 | 92512121.34 | 48091293.24 | 0.368370E+09 |
| March | 0.134083E+09 | 15028.79 | 0.134068E+09 | 0.111075E+09 | 0.331219E+09 |
| April | 0.150287E+09 | 1624148.27 | 0.148663E+09 | 0.186915E+09 | 0.190390E+09 |
| May | 0.183844E+09 | 13547143.77 | 0.170297E+09 | 0.311553E+09 | 0.113742E+09 |
| June | 0.188495E+09 | 22859994.57 | 0.165635E+09 | 0.423005E+09 | 52483632.91 |
| July | 0.179655E+09 | 16759739.40 | 0.162895E+09 | 0.402247E+09 | 41834409.61 |
| August | 0.153063E+09 | 3945204.69 | 0.149118E+09 | 0.310527E+09 | 65320769.64 |
| September | 0.128581E+09 | 121021.29 | 0.128460E+09 | 0.220345E+09 | 0.141024E+09 |
| October | 0.110198E+09 | 0.00 | 0.110198E+09 | 0.110096E+09 | 0.257379E+09 |
| November | 86092241.07 | 0.00 | 86092241.07 | 26396951.41 | 0.418325E+09 |
| December | 83228616.05 | 0.00 | 83228616.05 | 11175652.49 | 0.541712E+09 |
| Annual Sum or Average | 0.157392E+10 | 58872280.77 | 0.151504E+10 | 0.217971E+10 | 0.299844E+10 |
| Minimum of Months | 83228616.05 | 0.00 | 83228616.05 | 11175652.49 | 41834409.61 |
| Maximum of Months | 0.188495E+09 | 22859994.57 | 0.170297E+09 | 0.423005E+09 | 0.541712E+09 |
Report: WindowEnergyReportMonthly
For: GWINDOW1 S SEA
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.569082E+09 | 0.430004E+09 | 0.139079E+09 | 0.774468E+09 | 0.446097E+09 |
| February | 0.489495E+09 | 0.347638E+09 | 0.141858E+09 | 0.681409E+09 | 0.358093E+09 |
| March | 0.422895E+09 | 0.239752E+09 | 0.183143E+09 | 0.608506E+09 | 0.346501E+09 |
| April | 0.290400E+09 | 0.112456E+09 | 0.177944E+09 | 0.458184E+09 | 0.235225E+09 |
| May | 0.207588E+09 | 29308895.00 | 0.178279E+09 | 0.348018E+09 | 0.168269E+09 |
| June | 0.173878E+09 | 11809415.54 | 0.162068E+09 | 0.349888E+09 | 99794771.22 |
| July | 0.182972E+09 | 17574380.96 | 0.165397E+09 | 0.360187E+09 | 94640250.81 |
| August | 0.229443E+09 | 58582872.53 | 0.170860E+09 | 0.436635E+09 | 0.126768E+09 |
| September | 0.355405E+09 | 0.186733E+09 | 0.168672E+09 | 0.633385E+09 | 0.206895E+09 |
| October | 0.494068E+09 | 0.334439E+09 | 0.159628E+09 | 0.765322E+09 | 0.295796E+09 |
| November | 0.578056E+09 | 0.441679E+09 | 0.136377E+09 | 0.804593E+09 | 0.412028E+09 |
| December | 0.586752E+09 | 0.440209E+09 | 0.146543E+09 | 0.775891E+09 | 0.492434E+09 |
| Annual Sum or Average | 0.458003E+10 | 0.265019E+10 | 0.192985E+10 | 0.699649E+10 | 0.328254E+10 |
| Minimum of Months | 0.173878E+09 | 11809415.54 | 0.136377E+09 | 0.348018E+09 | 94640250.81 |
| Maximum of Months | 0.586752E+09 | 0.441679E+09 | 0.183143E+09 | 0.804593E+09 | 0.492434E+09 |
Report: WindowEnergyReportMonthly
For: GWINDOW1 E SEA
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.148185E+09 | 80652622.40 | 67531952.08 | 0.140047E+09 | 0.312170E+09 |
| February | 0.178006E+09 | 0.101243E+09 | 76762452.48 | 0.200370E+09 | 0.243646E+09 |
| March | 0.243302E+09 | 0.133715E+09 | 0.109587E+09 | 0.306770E+09 | 0.221193E+09 |
| April | 0.284415E+09 | 0.157987E+09 | 0.126428E+09 | 0.416926E+09 | 0.140622E+09 |
| May | 0.302996E+09 | 0.164587E+09 | 0.138408E+09 | 0.493122E+09 | 0.101183E+09 |
| June | 0.293688E+09 | 0.163443E+09 | 0.130245E+09 | 0.533229E+09 | 61293033.36 |
| July | 0.272492E+09 | 0.142688E+09 | 0.129804E+09 | 0.489267E+09 | 58248643.22 |
| August | 0.258836E+09 | 0.132392E+09 | 0.126443E+09 | 0.446175E+09 | 77150963.81 |
| September | 0.248200E+09 | 0.141572E+09 | 0.106628E+09 | 0.397150E+09 | 0.126777E+09 |
| October | 0.196953E+09 | 0.106167E+09 | 90785895.55 | 0.261403E+09 | 0.196789E+09 |
| November | 0.171049E+09 | 99520035.89 | 71528678.58 | 0.176243E+09 | 0.287861E+09 |
| December | 0.147347E+09 | 78008575.33 | 69338838.79 | 0.128283E+09 | 0.352001E+09 |
| Annual Sum or Average | 0.274547E+10 | 0.150198E+10 | 0.124349E+10 | 0.398898E+10 | 0.217893E+10 |
| Minimum of Months | 0.147347E+09 | 78008575.33 | 67531952.08 | 0.128283E+09 | 58248643.22 |
| Maximum of Months | 0.302996E+09 | 0.164587E+09 | 0.138408E+09 | 0.533229E+09 | 0.352001E+09 |
Report: WindowEnergyReportMonthly
For: GWINDOW1 E NEA
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.148185E+09 | 80652622.40 | 67531952.08 | 0.149637E+09 | 0.282122E+09 |
| February | 0.178006E+09 | 0.101243E+09 | 76762452.48 | 0.213536E+09 | 0.216530E+09 |
| March | 0.243302E+09 | 0.133715E+09 | 0.109587E+09 | 0.323810E+09 | 0.195717E+09 |
| April | 0.284415E+09 | 0.157987E+09 | 0.126428E+09 | 0.436217E+09 | 0.115747E+09 |
| May | 0.302996E+09 | 0.164587E+09 | 0.138408E+09 | 0.518294E+09 | 73251780.71 |
| June | 0.293688E+09 | 0.163443E+09 | 0.130245E+09 | 0.570651E+09 | 33312086.53 |
| July | 0.272492E+09 | 0.142688E+09 | 0.129804E+09 | 0.532879E+09 | 26959440.61 |
| August | 0.258836E+09 | 0.132392E+09 | 0.126443E+09 | 0.482852E+09 | 41255773.92 |
| September | 0.248200E+09 | 0.141572E+09 | 0.106628E+09 | 0.427681E+09 | 84353094.09 |
| October | 0.196953E+09 | 0.106167E+09 | 90785895.55 | 0.280813E+09 | 0.156499E+09 |
| November | 0.171049E+09 | 99520035.89 | 71528678.58 | 0.191985E+09 | 0.244991E+09 |
| December | 0.147347E+09 | 78008575.33 | 69338838.79 | 0.137103E+09 | 0.318508E+09 |
| Annual Sum or Average | 0.274547E+10 | 0.150198E+10 | 0.124349E+10 | 0.426546E+10 | 0.178925E+10 |
| Minimum of Months | 0.147347E+09 | 78008575.33 | 67531952.08 | 0.137103E+09 | 26959440.61 |
| Maximum of Months | 0.302996E+09 | 0.164587E+09 | 0.138408E+09 | 0.570651E+09 | 0.318508E+09 |
Report: WindowEnergyReportMonthly
For: GWINDOW1 N NEA
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 83878188.20 | 0.00 | 83878188.20 | 17939779.43 | 0.475100E+09 |
| February | 92512121.34 | 0.00 | 92512121.34 | 47013724.11 | 0.368115E+09 |
| March | 0.134083E+09 | 15028.79 | 0.134068E+09 | 0.109415E+09 | 0.329813E+09 |
| April | 0.150287E+09 | 1624148.27 | 0.148663E+09 | 0.183628E+09 | 0.190386E+09 |
| May | 0.183844E+09 | 13547143.77 | 0.170297E+09 | 0.309505E+09 | 0.113097E+09 |
| June | 0.188495E+09 | 22859994.57 | 0.165635E+09 | 0.421809E+09 | 52037120.29 |
| July | 0.179655E+09 | 16759739.40 | 0.162895E+09 | 0.401326E+09 | 41395377.08 |
| August | 0.153063E+09 | 3945204.69 | 0.149118E+09 | 0.309600E+09 | 64871473.20 |
| September | 0.128581E+09 | 121021.29 | 0.128460E+09 | 0.219330E+09 | 0.140222E+09 |
| October | 0.110198E+09 | 0.00 | 0.110198E+09 | 0.109380E+09 | 0.255694E+09 |
| November | 86092241.07 | 0.00 | 86092241.07 | 25334817.52 | 0.416321E+09 |
| December | 83228616.05 | 0.00 | 83228616.05 | 10720203.91 | 0.540910E+09 |
| Annual Sum or Average | 0.157392E+10 | 58872280.77 | 0.151504E+10 | 0.216500E+10 | 0.298796E+10 |
| Minimum of Months | 83228616.05 | 0.00 | 83228616.05 | 10720203.91 | 41395377.08 |
| Maximum of Months | 0.188495E+09 | 22859994.57 | 0.170297E+09 | 0.421809E+09 | 0.540910E+09 |
Report: WindowEnergyReportMonthly
For: GWINDOW1 N N1A
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 83878188.20 | 0.00 | 83878188.20 | 17235702.13 | 0.484687E+09 |
| February | 92512121.34 | 0.00 | 92512121.34 | 46461433.50 | 0.376193E+09 |
| March | 0.134083E+09 | 15028.79 | 0.134068E+09 | 0.108467E+09 | 0.338708E+09 |
| April | 0.150287E+09 | 1624148.27 | 0.148663E+09 | 0.184664E+09 | 0.196596E+09 |
| May | 0.183844E+09 | 13547143.77 | 0.170297E+09 | 0.312943E+09 | 0.114360E+09 |
| June | 0.188495E+09 | 22859994.57 | 0.165635E+09 | 0.427714E+09 | 51683319.43 |
| July | 0.179655E+09 | 16759739.40 | 0.162895E+09 | 0.407922E+09 | 40448507.71 |
| August | 0.153063E+09 | 3945204.69 | 0.149118E+09 | 0.316177E+09 | 63565553.51 |
| September | 0.128581E+09 | 121021.29 | 0.128460E+09 | 0.224348E+09 | 0.138328E+09 |
| October | 0.110198E+09 | 0.00 | 0.110198E+09 | 0.111339E+09 | 0.257753E+09 |
| November | 86092241.07 | 0.00 | 86092241.07 | 25045761.48 | 0.427371E+09 |
| December | 83228616.05 | 0.00 | 83228616.05 | 10461014.55 | 0.549630E+09 |
| Annual Sum or Average | 0.157392E+10 | 58872280.77 | 0.151504E+10 | 0.219278E+10 | 0.303932E+10 |
| Minimum of Months | 83228616.05 | 0.00 | 83228616.05 | 10461014.55 | 40448507.71 |
| Maximum of Months | 0.188495E+09 | 22859994.57 | 0.170297E+09 | 0.427714E+09 | 0.549630E+09 |
Report: WindowEnergyReportMonthly
For: GWINDOW1 N N2A
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 83878188.20 | 0.00 | 83878188.20 | 17231306.87 | 0.484556E+09 |
| February | 92512121.34 | 0.00 | 92512121.34 | 46399559.76 | 0.376213E+09 |
| March | 0.134083E+09 | 15028.79 | 0.134068E+09 | 0.108369E+09 | 0.338681E+09 |
| April | 0.150287E+09 | 1624148.27 | 0.148663E+09 | 0.184433E+09 | 0.196722E+09 |
| May | 0.183844E+09 | 13547143.77 | 0.170297E+09 | 0.312844E+09 | 0.114367E+09 |
| June | 0.188495E+09 | 22859994.57 | 0.165635E+09 | 0.427663E+09 | 51674627.25 |
| July | 0.179655E+09 | 16759739.40 | 0.162895E+09 | 0.407886E+09 | 40435776.23 |
| August | 0.153063E+09 | 3945204.69 | 0.149118E+09 | 0.316138E+09 | 63553646.10 |
| September | 0.128581E+09 | 121021.29 | 0.128460E+09 | 0.224309E+09 | 0.138303E+09 |
| October | 0.110198E+09 | 0.00 | 0.110198E+09 | 0.111320E+09 | 0.257667E+09 |
| November | 86092241.07 | 0.00 | 86092241.07 | 25014372.06 | 0.427216E+09 |
| December | 83228616.05 | 0.00 | 83228616.05 | 10439148.50 | 0.549602E+09 |
| Annual Sum or Average | 0.157392E+10 | 58872280.77 | 0.151504E+10 | 0.219205E+10 | 0.303899E+10 |
| Minimum of Months | 83228616.05 | 0.00 | 83228616.05 | 10439148.50 | 40435776.23 |
| Maximum of Months | 0.188495E+09 | 22859994.57 | 0.170297E+09 | 0.427663E+09 | 0.549602E+09 |
Report: WindowEnergyReportMonthly
For: GWINDOW1 S S1A
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.569082E+09 | 0.430004E+09 | 0.139079E+09 | 0.768773E+09 | 0.458056E+09 |
| February | 0.489495E+09 | 0.347638E+09 | 0.141858E+09 | 0.680778E+09 | 0.361624E+09 |
| March | 0.422895E+09 | 0.239752E+09 | 0.183143E+09 | 0.611989E+09 | 0.343885E+09 |
| April | 0.290400E+09 | 0.112456E+09 | 0.177944E+09 | 0.475441E+09 | 0.209847E+09 |
| May | 0.207588E+09 | 29308895.00 | 0.178279E+09 | 0.384259E+09 | 0.123994E+09 |
| June | 0.173878E+09 | 11809415.54 | 0.162068E+09 | 0.408501E+09 | 53643223.04 |
| July | 0.182972E+09 | 17574380.96 | 0.165397E+09 | 0.426722E+09 | 42440073.54 |
| August | 0.229443E+09 | 58582872.53 | 0.170860E+09 | 0.489642E+09 | 67371775.00 |
| September | 0.355405E+09 | 0.186733E+09 | 0.168672E+09 | 0.673521E+09 | 0.139603E+09 |
| October | 0.494068E+09 | 0.334439E+09 | 0.159628E+09 | 0.789314E+09 | 0.247191E+09 |
| November | 0.578056E+09 | 0.441679E+09 | 0.136377E+09 | 0.809772E+09 | 0.399649E+09 |
| December | 0.586752E+09 | 0.440209E+09 | 0.146543E+09 | 0.772162E+09 | 0.500518E+09 |
| Annual Sum or Average | 0.458003E+10 | 0.265019E+10 | 0.192985E+10 | 0.729088E+10 | 0.294782E+10 |
| Minimum of Months | 0.173878E+09 | 11809415.54 | 0.136377E+09 | 0.384259E+09 | 42440073.54 |
| Maximum of Months | 0.586752E+09 | 0.441679E+09 | 0.183143E+09 | 0.809772E+09 | 0.500518E+09 |
Report: WindowEnergyReportMonthly
For: GWINDOW1 S S2A
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.569082E+09 | 0.430004E+09 | 0.139079E+09 | 0.768344E+09 | 0.458674E+09 |
| February | 0.489495E+09 | 0.347638E+09 | 0.141858E+09 | 0.679815E+09 | 0.363041E+09 |
| March | 0.422895E+09 | 0.239752E+09 | 0.183143E+09 | 0.610359E+09 | 0.345969E+09 |
| April | 0.290400E+09 | 0.112456E+09 | 0.177944E+09 | 0.473668E+09 | 0.212090E+09 |
| May | 0.207588E+09 | 29308895.00 | 0.178279E+09 | 0.382197E+09 | 0.125867E+09 |
| June | 0.173878E+09 | 11809415.54 | 0.162068E+09 | 0.405620E+09 | 55213252.58 |
| July | 0.182972E+09 | 17574380.96 | 0.165397E+09 | 0.423669E+09 | 44147841.68 |
| August | 0.229443E+09 | 58582872.53 | 0.170860E+09 | 0.487025E+09 | 69278483.66 |
| September | 0.355405E+09 | 0.186733E+09 | 0.168672E+09 | 0.671685E+09 | 0.141868E+09 |
| October | 0.494068E+09 | 0.334439E+09 | 0.159628E+09 | 0.788065E+09 | 0.248881E+09 |
| November | 0.578056E+09 | 0.441679E+09 | 0.136377E+09 | 0.808978E+09 | 0.400946E+09 |
| December | 0.586752E+09 | 0.440209E+09 | 0.146543E+09 | 0.771144E+09 | 0.502126E+09 |
| Annual Sum or Average | 0.458003E+10 | 0.265019E+10 | 0.192985E+10 | 0.727057E+10 | 0.296810E+10 |
| Minimum of Months | 0.173878E+09 | 11809415.54 | 0.136377E+09 | 0.382197E+09 | 44147841.68 |
| Maximum of Months | 0.586752E+09 | 0.441679E+09 | 0.183143E+09 | 0.808978E+09 | 0.502126E+09 |
Report: WindowEnergyReportMonthly
For: MWINDOW1 S SWA
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.569082E+09 | 0.430004E+09 | 0.139079E+09 | 0.762474E+09 | 0.460024E+09 |
| February | 0.489495E+09 | 0.347638E+09 | 0.141858E+09 | 0.669185E+09 | 0.374650E+09 |
| March | 0.422895E+09 | 0.239752E+09 | 0.183143E+09 | 0.590683E+09 | 0.370787E+09 |
| April | 0.290400E+09 | 0.112456E+09 | 0.177944E+09 | 0.462849E+09 | 0.221076E+09 |
| May | 0.207588E+09 | 29308895.00 | 0.178279E+09 | 0.375271E+09 | 0.128925E+09 |
| June | 0.173878E+09 | 11809415.54 | 0.162068E+09 | 0.401085E+09 | 55650788.75 |
| July | 0.182972E+09 | 17574380.96 | 0.165397E+09 | 0.421564E+09 | 43067141.57 |
| August | 0.229443E+09 | 58582872.53 | 0.170860E+09 | 0.486459E+09 | 66577686.51 |
| September | 0.355405E+09 | 0.186733E+09 | 0.168672E+09 | 0.670808E+09 | 0.137384E+09 |
| October | 0.494068E+09 | 0.334439E+09 | 0.159628E+09 | 0.786648E+09 | 0.243308E+09 |
| November | 0.578056E+09 | 0.441679E+09 | 0.136377E+09 | 0.811751E+09 | 0.385975E+09 |
| December | 0.586752E+09 | 0.440209E+09 | 0.146543E+09 | 0.771340E+09 | 0.493760E+09 |
| Annual Sum or Average | 0.458003E+10 | 0.265019E+10 | 0.192985E+10 | 0.721012E+10 | 0.298118E+10 |
| Minimum of Months | 0.173878E+09 | 11809415.54 | 0.136377E+09 | 0.375271E+09 | 43067141.57 |
| Maximum of Months | 0.586752E+09 | 0.441679E+09 | 0.183143E+09 | 0.811751E+09 | 0.493760E+09 |
Report: WindowEnergyReportMonthly
For: MWINDOW1 W SWA
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.155634E+09 | 87728367.98 | 67905531.93 | 0.160843E+09 | 0.336090E+09 |
| February | 0.158206E+09 | 83935057.27 | 74271395.22 | 0.176989E+09 | 0.271982E+09 |
| March | 0.238956E+09 | 0.128054E+09 | 0.110902E+09 | 0.302114E+09 | 0.253029E+09 |
| April | 0.265486E+09 | 0.143191E+09 | 0.122295E+09 | 0.401019E+09 | 0.143393E+09 |
| May | 0.295459E+09 | 0.157880E+09 | 0.137579E+09 | 0.506366E+09 | 83835197.41 |
| June | 0.279027E+09 | 0.149962E+09 | 0.129065E+09 | 0.547441E+09 | 37024286.34 |
| July | 0.256063E+09 | 0.127377E+09 | 0.128686E+09 | 0.506721E+09 | 28191739.11 |
| August | 0.247408E+09 | 0.125926E+09 | 0.121481E+09 | 0.466656E+09 | 43635773.96 |
| September | 0.245542E+09 | 0.136979E+09 | 0.108562E+09 | 0.431282E+09 | 91859275.78 |
| October | 0.217902E+09 | 0.127131E+09 | 90770275.31 | 0.324369E+09 | 0.168120E+09 |
| November | 0.175845E+09 | 0.106629E+09 | 69216710.67 | 0.208298E+09 | 0.283066E+09 |
| December | 0.147434E+09 | 80086886.16 | 67346787.14 | 0.143800E+09 | 0.365961E+09 |
| Annual Sum or Average | 0.268296E+10 | 0.145488E+10 | 0.122808E+10 | 0.417590E+10 | 0.210619E+10 |
| Minimum of Months | 0.147434E+09 | 80086886.16 | 67346787.14 | 0.143800E+09 | 28191739.11 |
| Maximum of Months | 0.295459E+09 | 0.157880E+09 | 0.137579E+09 | 0.547441E+09 | 0.365961E+09 |
Report: WindowEnergyReportMonthly
For: MWINDOW1 W NWA
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.155634E+09 | 87728367.98 | 67905531.93 | 0.173853E+09 | 0.309651E+09 |
| February | 0.158206E+09 | 83935057.27 | 74271395.22 | 0.189101E+09 | 0.251551E+09 |
| March | 0.238956E+09 | 0.128054E+09 | 0.110902E+09 | 0.313104E+09 | 0.239296E+09 |
| April | 0.265486E+09 | 0.143191E+09 | 0.122295E+09 | 0.404793E+09 | 0.140618E+09 |
| May | 0.295459E+09 | 0.157880E+09 | 0.137579E+09 | 0.507025E+09 | 83715928.05 |
| June | 0.279027E+09 | 0.149962E+09 | 0.129065E+09 | 0.547216E+09 | 37135502.93 |
| July | 0.256063E+09 | 0.127377E+09 | 0.128686E+09 | 0.506864E+09 | 28207053.87 |
| August | 0.247408E+09 | 0.125926E+09 | 0.121481E+09 | 0.468323E+09 | 43190616.97 |
| September | 0.245542E+09 | 0.136979E+09 | 0.108562E+09 | 0.434924E+09 | 89990476.55 |
| October | 0.217902E+09 | 0.127131E+09 | 90770275.31 | 0.330446E+09 | 0.162595E+09 |
| November | 0.175845E+09 | 0.106629E+09 | 69216710.67 | 0.220499E+09 | 0.258921E+09 |
| December | 0.147434E+09 | 80086886.16 | 67346787.14 | 0.155840E+09 | 0.341365E+09 |
| Annual Sum or Average | 0.268296E+10 | 0.145488E+10 | 0.122808E+10 | 0.425199E+10 | 0.198624E+10 |
| Minimum of Months | 0.147434E+09 | 80086886.16 | 67346787.14 | 0.155840E+09 | 28207053.87 |
| Maximum of Months | 0.295459E+09 | 0.157880E+09 | 0.137579E+09 | 0.547216E+09 | 0.341365E+09 |
Report: WindowEnergyReportMonthly
For: MWINDOW1 N NWA
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 83878188.20 | 0.00 | 83878188.20 | 15338757.74 | 0.496134E+09 |
| February | 92512121.34 | 0.00 | 92512121.34 | 39430098.71 | 0.398055E+09 |
| March | 0.134083E+09 | 15028.79 | 0.134068E+09 | 90057885.29 | 0.377148E+09 |
| April | 0.150287E+09 | 1624148.27 | 0.148663E+09 | 0.170380E+09 | 0.213613E+09 |
| May | 0.183844E+09 | 13547143.77 | 0.170297E+09 | 0.303609E+09 | 0.119453E+09 |
| June | 0.188495E+09 | 22859994.57 | 0.165635E+09 | 0.419908E+09 | 53720582.09 |
| July | 0.179655E+09 | 16759739.40 | 0.162895E+09 | 0.402730E+09 | 41153535.12 |
| August | 0.153063E+09 | 3945204.69 | 0.149118E+09 | 0.313544E+09 | 63200274.48 |
| September | 0.128581E+09 | 121021.29 | 0.128460E+09 | 0.223178E+09 | 0.137215E+09 |
| October | 0.110198E+09 | 0.00 | 0.110198E+09 | 0.111791E+09 | 0.253843E+09 |
| November | 86092241.07 | 0.00 | 86092241.07 | 27420342.46 | 0.415386E+09 |
| December | 83228616.05 | 0.00 | 83228616.05 | 10332745.37 | 0.552373E+09 |
| Annual Sum or Average | 0.157392E+10 | 58872280.77 | 0.151504E+10 | 0.212772E+10 | 0.312129E+10 |
| Minimum of Months | 83228616.05 | 0.00 | 83228616.05 | 10332745.37 | 41153535.12 |
| Maximum of Months | 0.188495E+09 | 22859994.57 | 0.170297E+09 | 0.419908E+09 | 0.552373E+09 |
Report: WindowEnergyReportMonthly
For: MWINDOW1 S SEA
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.569082E+09 | 0.430004E+09 | 0.139079E+09 | 0.760551E+09 | 0.458000E+09 |
| February | 0.489495E+09 | 0.347638E+09 | 0.141858E+09 | 0.665626E+09 | 0.374468E+09 |
| March | 0.422895E+09 | 0.239752E+09 | 0.183143E+09 | 0.586938E+09 | 0.369518E+09 |
| April | 0.290400E+09 | 0.112456E+09 | 0.177944E+09 | 0.460290E+09 | 0.220449E+09 |
| May | 0.207588E+09 | 29308895.00 | 0.178279E+09 | 0.373744E+09 | 0.128178E+09 |
| June | 0.173878E+09 | 11809415.54 | 0.162068E+09 | 0.400006E+09 | 55156870.44 |
| July | 0.182972E+09 | 17574380.96 | 0.165397E+09 | 0.420715E+09 | 42605742.51 |
| August | 0.229443E+09 | 58582872.53 | 0.170860E+09 | 0.485618E+09 | 66118924.09 |
| September | 0.355405E+09 | 0.186733E+09 | 0.168672E+09 | 0.669714E+09 | 0.136465E+09 |
| October | 0.494068E+09 | 0.334439E+09 | 0.159628E+09 | 0.785976E+09 | 0.241655E+09 |
| November | 0.578056E+09 | 0.441679E+09 | 0.136377E+09 | 0.809933E+09 | 0.384208E+09 |
| December | 0.586752E+09 | 0.440209E+09 | 0.146543E+09 | 0.769086E+09 | 0.492362E+09 |
| Annual Sum or Average | 0.458003E+10 | 0.265019E+10 | 0.192985E+10 | 0.718820E+10 | 0.296918E+10 |
| Minimum of Months | 0.173878E+09 | 11809415.54 | 0.136377E+09 | 0.373744E+09 | 42605742.51 |
| Maximum of Months | 0.586752E+09 | 0.441679E+09 | 0.183143E+09 | 0.809933E+09 | 0.492362E+09 |
Report: WindowEnergyReportMonthly
For: MWINDOW1 E SEA
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.148185E+09 | 80652622.40 | 67531952.08 | 0.134521E+09 | 0.322776E+09 |
| February | 0.178006E+09 | 0.101243E+09 | 76762452.48 | 0.192170E+09 | 0.255832E+09 |
| March | 0.243302E+09 | 0.133715E+09 | 0.109587E+09 | 0.292779E+09 | 0.235954E+09 |
| April | 0.284415E+09 | 0.157987E+09 | 0.126428E+09 | 0.418204E+09 | 0.131155E+09 |
| May | 0.302996E+09 | 0.164587E+09 | 0.138408E+09 | 0.511268E+09 | 76821770.60 |
| June | 0.293688E+09 | 0.163443E+09 | 0.130245E+09 | 0.567767E+09 | 33892612.99 |
| July | 0.272492E+09 | 0.142688E+09 | 0.129804E+09 | 0.532160E+09 | 26471758.88 |
| August | 0.258836E+09 | 0.132392E+09 | 0.126443E+09 | 0.481963E+09 | 40318300.07 |
| September | 0.248200E+09 | 0.141572E+09 | 0.106628E+09 | 0.424742E+09 | 83863222.91 |
| October | 0.196953E+09 | 0.106167E+09 | 90785895.55 | 0.274605E+09 | 0.160062E+09 |
| November | 0.171049E+09 | 99520035.89 | 71528678.58 | 0.178931E+09 | 0.267923E+09 |
| December | 0.147347E+09 | 78008575.33 | 69338838.79 | 0.126113E+09 | 0.353892E+09 |
| Annual Sum or Average | 0.274547E+10 | 0.150198E+10 | 0.124349E+10 | 0.413522E+10 | 0.198896E+10 |
| Minimum of Months | 0.147347E+09 | 78008575.33 | 67531952.08 | 0.126113E+09 | 26471758.88 |
| Maximum of Months | 0.302996E+09 | 0.164587E+09 | 0.138408E+09 | 0.567767E+09 | 0.353892E+09 |
Report: WindowEnergyReportMonthly
For: MWINDOW1 E NEA
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.148185E+09 | 80652622.40 | 67531952.08 | 0.144900E+09 | 0.292821E+09 |
| February | 0.178006E+09 | 0.101243E+09 | 76762452.48 | 0.203782E+09 | 0.233859E+09 |
| March | 0.243302E+09 | 0.133715E+09 | 0.109587E+09 | 0.303581E+09 | 0.222477E+09 |
| April | 0.284415E+09 | 0.157987E+09 | 0.126428E+09 | 0.421871E+09 | 0.128607E+09 |
| May | 0.302996E+09 | 0.164587E+09 | 0.138408E+09 | 0.511907E+09 | 76674574.03 |
| June | 0.293688E+09 | 0.163443E+09 | 0.130245E+09 | 0.567549E+09 | 33982894.40 |
| July | 0.272492E+09 | 0.142688E+09 | 0.129804E+09 | 0.532317E+09 | 26471881.95 |
| August | 0.258836E+09 | 0.132392E+09 | 0.126443E+09 | 0.483666E+09 | 39875489.02 |
| September | 0.248200E+09 | 0.141572E+09 | 0.106628E+09 | 0.428493E+09 | 82076951.33 |
| October | 0.196953E+09 | 0.106167E+09 | 90785895.55 | 0.280748E+09 | 0.154528E+09 |
| November | 0.171049E+09 | 99520035.89 | 71528678.58 | 0.191661E+09 | 0.243271E+09 |
| December | 0.147347E+09 | 78008575.33 | 69338838.79 | 0.134511E+09 | 0.324597E+09 |
| Annual Sum or Average | 0.274547E+10 | 0.150198E+10 | 0.124349E+10 | 0.420499E+10 | 0.185924E+10 |
| Minimum of Months | 0.147347E+09 | 78008575.33 | 67531952.08 | 0.134511E+09 | 26471881.95 |
| Maximum of Months | 0.302996E+09 | 0.164587E+09 | 0.138408E+09 | 0.567549E+09 | 0.324597E+09 |
Report: WindowEnergyReportMonthly
For: MWINDOW1 N NEA
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 83878188.20 | 0.00 | 83878188.20 | 14840422.39 | 0.493836E+09 |
| February | 92512121.34 | 0.00 | 92512121.34 | 37652389.75 | 0.397979E+09 |
| March | 0.134083E+09 | 15028.79 | 0.134068E+09 | 86853347.55 | 0.376775E+09 |
| April | 0.150287E+09 | 1624148.27 | 0.148663E+09 | 0.167677E+09 | 0.213359E+09 |
| May | 0.183844E+09 | 13547143.77 | 0.170297E+09 | 0.301846E+09 | 0.118538E+09 |
| June | 0.188495E+09 | 22859994.57 | 0.165635E+09 | 0.418776E+09 | 53180119.81 |
| July | 0.179655E+09 | 16759739.40 | 0.162895E+09 | 0.401822E+09 | 40666394.82 |
| August | 0.153063E+09 | 3945204.69 | 0.149118E+09 | 0.312619E+09 | 62709845.18 |
| September | 0.128581E+09 | 121021.29 | 0.128460E+09 | 0.222095E+09 | 0.136386E+09 |
| October | 0.110198E+09 | 0.00 | 0.110198E+09 | 0.110730E+09 | 0.252109E+09 |
| November | 86092241.07 | 0.00 | 86092241.07 | 26002465.39 | 0.412866E+09 |
| December | 83228616.05 | 0.00 | 83228616.05 | 9774874.68 | 0.551255E+09 |
| Annual Sum or Average | 0.157392E+10 | 58872280.77 | 0.151504E+10 | 0.211069E+10 | 0.310966E+10 |
| Minimum of Months | 83228616.05 | 0.00 | 83228616.05 | 9774874.68 | 40666394.82 |
| Maximum of Months | 0.188495E+09 | 22859994.57 | 0.170297E+09 | 0.418776E+09 | 0.551255E+09 |
Report: WindowEnergyReportMonthly
For: MWINDOW1 N N1A
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 83878188.20 | 0.00 | 83878188.20 | 14226017.96 | 0.504552E+09 |
| February | 92512121.34 | 0.00 | 92512121.34 | 37585032.21 | 0.407859E+09 |
| March | 0.134083E+09 | 15028.79 | 0.134068E+09 | 87012844.80 | 0.387709E+09 |
| April | 0.150287E+09 | 1624148.27 | 0.148663E+09 | 0.171380E+09 | 0.215550E+09 |
| May | 0.183844E+09 | 13547143.77 | 0.170297E+09 | 0.307825E+09 | 0.117890E+09 |
| June | 0.188495E+09 | 22859994.57 | 0.165635E+09 | 0.426460E+09 | 52128013.57 |
| July | 0.179655E+09 | 16759739.40 | 0.162895E+09 | 0.409031E+09 | 39620286.05 |
| August | 0.153063E+09 | 3945204.69 | 0.149118E+09 | 0.319037E+09 | 61780020.97 |
| September | 0.128581E+09 | 121021.29 | 0.128460E+09 | 0.226630E+09 | 0.135637E+09 |
| October | 0.110198E+09 | 0.00 | 0.110198E+09 | 0.112006E+09 | 0.256807E+09 |
| November | 86092241.07 | 0.00 | 86092241.07 | 25272416.19 | 0.427755E+09 |
| December | 83228616.05 | 0.00 | 83228616.05 | 9375773.46 | 0.562057E+09 |
| Annual Sum or Average | 0.157392E+10 | 58872280.77 | 0.151504E+10 | 0.214584E+10 | 0.316934E+10 |
| Minimum of Months | 83228616.05 | 0.00 | 83228616.05 | 9375773.46 | 39620286.05 |
| Maximum of Months | 0.188495E+09 | 22859994.57 | 0.170297E+09 | 0.426460E+09 | 0.562057E+09 |
Report: WindowEnergyReportMonthly
For: MWINDOW1 N N2A
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 83878188.20 | 0.00 | 83878188.20 | 14214148.00 | 0.504347E+09 |
| February | 92512121.34 | 0.00 | 92512121.34 | 37469505.57 | 0.407954E+09 |
| March | 0.134083E+09 | 15028.79 | 0.134068E+09 | 86790229.81 | 0.387826E+09 |
| April | 0.150287E+09 | 1624148.27 | 0.148663E+09 | 0.171225E+09 | 0.215590E+09 |
| May | 0.183844E+09 | 13547143.77 | 0.170297E+09 | 0.307759E+09 | 0.117867E+09 |
| June | 0.188495E+09 | 22859994.57 | 0.165635E+09 | 0.426417E+09 | 52112107.48 |
| July | 0.179655E+09 | 16759739.40 | 0.162895E+09 | 0.408998E+09 | 39604692.19 |
| August | 0.153063E+09 | 3945204.69 | 0.149118E+09 | 0.319000E+09 | 61764315.49 |
| September | 0.128581E+09 | 121021.29 | 0.128460E+09 | 0.226586E+09 | 0.135607E+09 |
| October | 0.110198E+09 | 0.00 | 0.110198E+09 | 0.111969E+09 | 0.256714E+09 |
| November | 86092241.07 | 0.00 | 86092241.07 | 25222244.98 | 0.427549E+09 |
| December | 83228616.05 | 0.00 | 83228616.05 | 9346084.03 | 0.562019E+09 |
| Annual Sum or Average | 0.157392E+10 | 58872280.77 | 0.151504E+10 | 0.214500E+10 | 0.316895E+10 |
| Minimum of Months | 83228616.05 | 0.00 | 83228616.05 | 9346084.03 | 39604692.19 |
| Maximum of Months | 0.188495E+09 | 22859994.57 | 0.170297E+09 | 0.426417E+09 | 0.562019E+09 |
Report: WindowEnergyReportMonthly
For: MWINDOW1 S S1A
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.569082E+09 | 0.430004E+09 | 0.139079E+09 | 0.753189E+09 | 0.480667E+09 |
| February | 0.489495E+09 | 0.347638E+09 | 0.141858E+09 | 0.661286E+09 | 0.390926E+09 |
| March | 0.422895E+09 | 0.239752E+09 | 0.183143E+09 | 0.584855E+09 | 0.381962E+09 |
| April | 0.290400E+09 | 0.112456E+09 | 0.177944E+09 | 0.463531E+09 | 0.222813E+09 |
| May | 0.207588E+09 | 29308895.00 | 0.178279E+09 | 0.379594E+09 | 0.127392E+09 |
| June | 0.173878E+09 | 11809415.54 | 0.162068E+09 | 0.407798E+09 | 54075082.79 |
| July | 0.182972E+09 | 17574380.96 | 0.165397E+09 | 0.427937E+09 | 41531468.16 |
| August | 0.229443E+09 | 58582872.53 | 0.170860E+09 | 0.491717E+09 | 65190270.31 |
| September | 0.355405E+09 | 0.186733E+09 | 0.168672E+09 | 0.673950E+09 | 0.135923E+09 |
| October | 0.494068E+09 | 0.334439E+09 | 0.159628E+09 | 0.787139E+09 | 0.244975E+09 |
| November | 0.578056E+09 | 0.441679E+09 | 0.136377E+09 | 0.806506E+09 | 0.397511E+09 |
| December | 0.586752E+09 | 0.440209E+09 | 0.146543E+09 | 0.761071E+09 | 0.513615E+09 |
| Annual Sum or Average | 0.458003E+10 | 0.265019E+10 | 0.192985E+10 | 0.719857E+10 | 0.305658E+10 |
| Minimum of Months | 0.173878E+09 | 11809415.54 | 0.136377E+09 | 0.379594E+09 | 41531468.16 |
| Maximum of Months | 0.586752E+09 | 0.441679E+09 | 0.183143E+09 | 0.806506E+09 | 0.513615E+09 |
Report: WindowEnergyReportMonthly
For: MWINDOW1 S S2A
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.569082E+09 | 0.430004E+09 | 0.139079E+09 | 0.753141E+09 | 0.480551E+09 |
| February | 0.489495E+09 | 0.347638E+09 | 0.141858E+09 | 0.661088E+09 | 0.391057E+09 |
| March | 0.422895E+09 | 0.239752E+09 | 0.183143E+09 | 0.584681E+09 | 0.381975E+09 |
| April | 0.290400E+09 | 0.112456E+09 | 0.177944E+09 | 0.463414E+09 | 0.222817E+09 |
| May | 0.207588E+09 | 29308895.00 | 0.178279E+09 | 0.379531E+09 | 0.127369E+09 |
| June | 0.173878E+09 | 11809415.54 | 0.162068E+09 | 0.407755E+09 | 54058975.48 |
| July | 0.182972E+09 | 17574380.96 | 0.165397E+09 | 0.427904E+09 | 41515393.75 |
| August | 0.229443E+09 | 58582872.53 | 0.170860E+09 | 0.491683E+09 | 65174236.31 |
| September | 0.355405E+09 | 0.186733E+09 | 0.168672E+09 | 0.673912E+09 | 0.135893E+09 |
| October | 0.494068E+09 | 0.334439E+09 | 0.159628E+09 | 0.787125E+09 | 0.244911E+09 |
| November | 0.578056E+09 | 0.441679E+09 | 0.136377E+09 | 0.806465E+09 | 0.397423E+09 |
| December | 0.586752E+09 | 0.440209E+09 | 0.146543E+09 | 0.760970E+09 | 0.513598E+09 |
| Annual Sum or Average | 0.458003E+10 | 0.265019E+10 | 0.192985E+10 | 0.719767E+10 | 0.305634E+10 |
| Minimum of Months | 0.173878E+09 | 11809415.54 | 0.136377E+09 | 0.379531E+09 | 41515393.75 |
| Maximum of Months | 0.586752E+09 | 0.441679E+09 | 0.183143E+09 | 0.806465E+09 | 0.513598E+09 |
Report: WindowEnergyReportMonthly
For: TWINDOW1 S SWA
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.569082E+09 | 0.430004E+09 | 0.139079E+09 | 0.765772E+09 | 0.427007E+09 |
| February | 0.489495E+09 | 0.347638E+09 | 0.141858E+09 | 0.673704E+09 | 0.342679E+09 |
| March | 0.422895E+09 | 0.239752E+09 | 0.183143E+09 | 0.597454E+09 | 0.335893E+09 |
| April | 0.290400E+09 | 0.112456E+09 | 0.177944E+09 | 0.462391E+09 | 0.200165E+09 |
| May | 0.207588E+09 | 29308895.00 | 0.178279E+09 | 0.367682E+09 | 0.120023E+09 |
| June | 0.173878E+09 | 11809415.54 | 0.162068E+09 | 0.387758E+09 | 53436562.74 |
| July | 0.182972E+09 | 17574380.96 | 0.165397E+09 | 0.407396E+09 | 41834263.44 |
| August | 0.229443E+09 | 58582872.53 | 0.170860E+09 | 0.473751E+09 | 64002766.37 |
| September | 0.355405E+09 | 0.186733E+09 | 0.168672E+09 | 0.661243E+09 | 0.130282E+09 |
| October | 0.494068E+09 | 0.334439E+09 | 0.159628E+09 | 0.789088E+09 | 0.218525E+09 |
| November | 0.578056E+09 | 0.441679E+09 | 0.136377E+09 | 0.820440E+09 | 0.346773E+09 |
| December | 0.586752E+09 | 0.440209E+09 | 0.146543E+09 | 0.775032E+09 | 0.461866E+09 |
| Annual Sum or Average | 0.458003E+10 | 0.265019E+10 | 0.192985E+10 | 0.718171E+10 | 0.274249E+10 |
| Minimum of Months | 0.173878E+09 | 11809415.54 | 0.136377E+09 | 0.367682E+09 | 41834263.44 |
| Maximum of Months | 0.586752E+09 | 0.441679E+09 | 0.183143E+09 | 0.820440E+09 | 0.461866E+09 |
Report: WindowEnergyReportMonthly
For: TWINDOW1 W SWA
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.155634E+09 | 87728367.98 | 67905531.93 | 0.158944E+09 | 0.309920E+09 |
| February | 0.158206E+09 | 83935057.27 | 74271395.22 | 0.176292E+09 | 0.247127E+09 |
| March | 0.238956E+09 | 0.128054E+09 | 0.110902E+09 | 0.303057E+09 | 0.226366E+09 |
| April | 0.265486E+09 | 0.143191E+09 | 0.122295E+09 | 0.399652E+09 | 0.128663E+09 |
| May | 0.295459E+09 | 0.157880E+09 | 0.137579E+09 | 0.500502E+09 | 77629791.39 |
| June | 0.279027E+09 | 0.149962E+09 | 0.129065E+09 | 0.538049E+09 | 35572727.06 |
| July | 0.256063E+09 | 0.127377E+09 | 0.128686E+09 | 0.497095E+09 | 27332138.53 |
| August | 0.247408E+09 | 0.125926E+09 | 0.121481E+09 | 0.457925E+09 | 41860925.93 |
| September | 0.245542E+09 | 0.136979E+09 | 0.108562E+09 | 0.424536E+09 | 86640244.00 |
| October | 0.217902E+09 | 0.127131E+09 | 90770275.31 | 0.323341E+09 | 0.148831E+09 |
| November | 0.175845E+09 | 0.106629E+09 | 69216710.67 | 0.207832E+09 | 0.250791E+09 |
| December | 0.147434E+09 | 80086886.16 | 67346787.14 | 0.142060E+09 | 0.340530E+09 |
| Annual Sum or Average | 0.268296E+10 | 0.145488E+10 | 0.122808E+10 | 0.412929E+10 | 0.192126E+10 |
| Minimum of Months | 0.147434E+09 | 80086886.16 | 67346787.14 | 0.142060E+09 | 27332138.53 |
| Maximum of Months | 0.295459E+09 | 0.157880E+09 | 0.137579E+09 | 0.538049E+09 | 0.340530E+09 |
Report: WindowEnergyReportMonthly
For: TWINDOW1 W NWA
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.155634E+09 | 87728367.98 | 67905531.93 | 0.174575E+09 | 0.293303E+09 |
| February | 0.158206E+09 | 83935057.27 | 74271395.22 | 0.190079E+09 | 0.235539E+09 |
| March | 0.238956E+09 | 0.128054E+09 | 0.110902E+09 | 0.315286E+09 | 0.218732E+09 |
| April | 0.265486E+09 | 0.143191E+09 | 0.122295E+09 | 0.405160E+09 | 0.126561E+09 |
| May | 0.295459E+09 | 0.157880E+09 | 0.137579E+09 | 0.501380E+09 | 77704861.08 |
| June | 0.279027E+09 | 0.149962E+09 | 0.129065E+09 | 0.537689E+09 | 35727276.19 |
| July | 0.256063E+09 | 0.127377E+09 | 0.128686E+09 | 0.497257E+09 | 27395831.80 |
| August | 0.247408E+09 | 0.125926E+09 | 0.121481E+09 | 0.460265E+09 | 41532268.35 |
| September | 0.245542E+09 | 0.136979E+09 | 0.108562E+09 | 0.430210E+09 | 84794456.89 |
| October | 0.217902E+09 | 0.127131E+09 | 90770275.31 | 0.334363E+09 | 0.142099E+09 |
| November | 0.175845E+09 | 0.106629E+09 | 69216710.67 | 0.223994E+09 | 0.235849E+09 |
| December | 0.147434E+09 | 80086886.16 | 67346787.14 | 0.157079E+09 | 0.323556E+09 |
| Annual Sum or Average | 0.268296E+10 | 0.145488E+10 | 0.122808E+10 | 0.422734E+10 | 0.184279E+10 |
| Minimum of Months | 0.147434E+09 | 80086886.16 | 67346787.14 | 0.157079E+09 | 27395831.80 |
| Maximum of Months | 0.295459E+09 | 0.157880E+09 | 0.137579E+09 | 0.537689E+09 | 0.323556E+09 |
Report: WindowEnergyReportMonthly
For: TWINDOW1 N NWA
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 83878188.20 | 0.00 | 83878188.20 | 16845747.59 | 0.471630E+09 |
| February | 92512121.34 | 0.00 | 92512121.34 | 41637044.20 | 0.374185E+09 |
| March | 0.134083E+09 | 15028.79 | 0.134068E+09 | 95023415.48 | 0.346729E+09 |
| April | 0.150287E+09 | 1624148.27 | 0.148663E+09 | 0.172308E+09 | 0.192675E+09 |
| May | 0.183844E+09 | 13547143.77 | 0.170297E+09 | 0.298359E+09 | 0.112333E+09 |
| June | 0.188495E+09 | 22859994.57 | 0.165635E+09 | 0.406573E+09 | 52024456.02 |
| July | 0.179655E+09 | 16759739.40 | 0.162895E+09 | 0.388924E+09 | 40251309.53 |
| August | 0.153063E+09 | 3945204.69 | 0.149118E+09 | 0.302258E+09 | 61016551.02 |
| September | 0.128581E+09 | 121021.29 | 0.128460E+09 | 0.216888E+09 | 0.129653E+09 |
| October | 0.110198E+09 | 0.00 | 0.110198E+09 | 0.118366E+09 | 0.222637E+09 |
| November | 86092241.07 | 0.00 | 86092241.07 | 32250433.57 | 0.379722E+09 |
| December | 83228616.05 | 0.00 | 83228616.05 | 11647288.68 | 0.525172E+09 |
| Annual Sum or Average | 0.157392E+10 | 58872280.77 | 0.151504E+10 | 0.210108E+10 | 0.290803E+10 |
| Minimum of Months | 83228616.05 | 0.00 | 83228616.05 | 11647288.68 | 40251309.53 |
| Maximum of Months | 0.188495E+09 | 22859994.57 | 0.170297E+09 | 0.406573E+09 | 0.525172E+09 |
Report: WindowEnergyReportMonthly
For: TWINDOW1 S SEA
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.569082E+09 | 0.430004E+09 | 0.139079E+09 | 0.762432E+09 | 0.423937E+09 |
| February | 0.489495E+09 | 0.347638E+09 | 0.141858E+09 | 0.668608E+09 | 0.340737E+09 |
| March | 0.422895E+09 | 0.239752E+09 | 0.183143E+09 | 0.591064E+09 | 0.332431E+09 |
| April | 0.290400E+09 | 0.112456E+09 | 0.177944E+09 | 0.456524E+09 | 0.198025E+09 |
| May | 0.207588E+09 | 29308895.00 | 0.178279E+09 | 0.364144E+09 | 0.118602E+09 |
| June | 0.173878E+09 | 11809415.54 | 0.162068E+09 | 0.386141E+09 | 52654940.88 |
| July | 0.182972E+09 | 17574380.96 | 0.165397E+09 | 0.406170E+09 | 41156454.77 |
| August | 0.229443E+09 | 58582872.53 | 0.170860E+09 | 0.472453E+09 | 63294278.67 |
| September | 0.355405E+09 | 0.186733E+09 | 0.168672E+09 | 0.658911E+09 | 0.128686E+09 |
| October | 0.494068E+09 | 0.334439E+09 | 0.159628E+09 | 0.786433E+09 | 0.215227E+09 |
| November | 0.578056E+09 | 0.441679E+09 | 0.136377E+09 | 0.816580E+09 | 0.343712E+09 |
| December | 0.586752E+09 | 0.440209E+09 | 0.146543E+09 | 0.771677E+09 | 0.458968E+09 |
| Annual Sum or Average | 0.458003E+10 | 0.265019E+10 | 0.192985E+10 | 0.714114E+10 | 0.271743E+10 |
| Minimum of Months | 0.173878E+09 | 11809415.54 | 0.136377E+09 | 0.364144E+09 | 41156454.77 |
| Maximum of Months | 0.586752E+09 | 0.441679E+09 | 0.183143E+09 | 0.816580E+09 | 0.458968E+09 |
Report: WindowEnergyReportMonthly
For: TWINDOW1 E SEA
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.148185E+09 | 80652622.40 | 67531952.08 | 0.137975E+09 | 0.302022E+09 |
| February | 0.178006E+09 | 0.101243E+09 | 76762452.48 | 0.195762E+09 | 0.234724E+09 |
| March | 0.243302E+09 | 0.133715E+09 | 0.109587E+09 | 0.298415E+09 | 0.213790E+09 |
| April | 0.284415E+09 | 0.157987E+09 | 0.126428E+09 | 0.418965E+09 | 0.119420E+09 |
| May | 0.302996E+09 | 0.164587E+09 | 0.138408E+09 | 0.506167E+09 | 72082832.14 |
| June | 0.293688E+09 | 0.163443E+09 | 0.130245E+09 | 0.558081E+09 | 32475208.82 |
| July | 0.272492E+09 | 0.142688E+09 | 0.129804E+09 | 0.522075E+09 | 25629527.70 |
| August | 0.258836E+09 | 0.132392E+09 | 0.126443E+09 | 0.473133E+09 | 38730907.63 |
| September | 0.248200E+09 | 0.141572E+09 | 0.106628E+09 | 0.418634E+09 | 79695321.59 |
| October | 0.196953E+09 | 0.106167E+09 | 90785895.55 | 0.276002E+09 | 0.143288E+09 |
| November | 0.171049E+09 | 99520035.89 | 71528678.58 | 0.183999E+09 | 0.241515E+09 |
| December | 0.147347E+09 | 78008575.33 | 69338838.79 | 0.129781E+09 | 0.333628E+09 |
| Annual Sum or Average | 0.274547E+10 | 0.150198E+10 | 0.124349E+10 | 0.411899E+10 | 0.183700E+10 |
| Minimum of Months | 0.147347E+09 | 78008575.33 | 67531952.08 | 0.129781E+09 | 25629527.70 |
| Maximum of Months | 0.302996E+09 | 0.164587E+09 | 0.138408E+09 | 0.558081E+09 | 0.333628E+09 |
Report: WindowEnergyReportMonthly
For: TWINDOW1 E NEA
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.148185E+09 | 80652622.40 | 67531952.08 | 0.147564E+09 | 0.278186E+09 |
| February | 0.178006E+09 | 0.101243E+09 | 76762452.48 | 0.206990E+09 | 0.219335E+09 |
| March | 0.243302E+09 | 0.133715E+09 | 0.109587E+09 | 0.309175E+09 | 0.203941E+09 |
| April | 0.284415E+09 | 0.157987E+09 | 0.126428E+09 | 0.424079E+09 | 0.117035E+09 |
| May | 0.302996E+09 | 0.164587E+09 | 0.138408E+09 | 0.506985E+09 | 72103966.05 |
| June | 0.293688E+09 | 0.163443E+09 | 0.130245E+09 | 0.557762E+09 | 32602876.15 |
| July | 0.272492E+09 | 0.142688E+09 | 0.129804E+09 | 0.522270E+09 | 25671104.19 |
| August | 0.258836E+09 | 0.132392E+09 | 0.126443E+09 | 0.475511E+09 | 38389167.38 |
| September | 0.248200E+09 | 0.141572E+09 | 0.106628E+09 | 0.424260E+09 | 77885014.89 |
| October | 0.196953E+09 | 0.106167E+09 | 90785895.55 | 0.286535E+09 | 0.135753E+09 |
| November | 0.171049E+09 | 99520035.89 | 71528678.58 | 0.197431E+09 | 0.221711E+09 |
| December | 0.147347E+09 | 78008575.33 | 69338838.79 | 0.137721E+09 | 0.308551E+09 |
| Annual Sum or Average | 0.274547E+10 | 0.150198E+10 | 0.124349E+10 | 0.419628E+10 | 0.173117E+10 |
| Minimum of Months | 0.147347E+09 | 78008575.33 | 67531952.08 | 0.137721E+09 | 25671104.19 |
| Maximum of Months | 0.302996E+09 | 0.164587E+09 | 0.138408E+09 | 0.557762E+09 | 0.308551E+09 |
Report: WindowEnergyReportMonthly
For: TWINDOW1 N NEA
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 83878188.20 | 0.00 | 83878188.20 | 15869133.21 | 0.468733E+09 |
| February | 92512121.34 | 0.00 | 92512121.34 | 38929132.67 | 0.372501E+09 |
| March | 0.134083E+09 | 15028.79 | 0.134068E+09 | 90080667.83 | 0.343076E+09 |
| April | 0.150287E+09 | 1624148.27 | 0.148663E+09 | 0.166496E+09 | 0.190583E+09 |
| May | 0.183844E+09 | 13547143.77 | 0.170297E+09 | 0.294388E+09 | 0.110594E+09 |
| June | 0.188495E+09 | 22859994.57 | 0.165635E+09 | 0.404893E+09 | 51160179.21 |
| July | 0.179655E+09 | 16759739.40 | 0.162895E+09 | 0.387626E+09 | 39533398.25 |
| August | 0.153063E+09 | 3945204.69 | 0.149118E+09 | 0.300834E+09 | 60260005.12 |
| September | 0.128581E+09 | 121021.29 | 0.128460E+09 | 0.214450E+09 | 0.128209E+09 |
| October | 0.110198E+09 | 0.00 | 0.110198E+09 | 0.114745E+09 | 0.218659E+09 |
| November | 86092241.07 | 0.00 | 86092241.07 | 29447222.38 | 0.374736E+09 |
| December | 83228616.05 | 0.00 | 83228616.05 | 10883834.59 | 0.523414E+09 |
| Annual Sum or Average | 0.157392E+10 | 58872280.77 | 0.151504E+10 | 0.206864E+10 | 0.288146E+10 |
| Minimum of Months | 83228616.05 | 0.00 | 83228616.05 | 10883834.59 | 39533398.25 |
| Maximum of Months | 0.188495E+09 | 22859994.57 | 0.170297E+09 | 0.404893E+09 | 0.523414E+09 |
Report: WindowEnergyReportMonthly
For: TWINDOW1 N N1A
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 83878188.20 | 0.00 | 83878188.20 | 16504049.42 | 0.476325E+09 |
| February | 92512121.34 | 0.00 | 92512121.34 | 41681654.95 | 0.378000E+09 |
| March | 0.134083E+09 | 15028.79 | 0.134068E+09 | 96025657.91 | 0.348964E+09 |
| April | 0.150287E+09 | 1624148.27 | 0.148663E+09 | 0.174548E+09 | 0.194693E+09 |
| May | 0.183844E+09 | 13547143.77 | 0.170297E+09 | 0.303109E+09 | 0.112318E+09 |
| June | 0.188495E+09 | 22859994.57 | 0.165635E+09 | 0.414938E+09 | 51134226.12 |
| July | 0.179655E+09 | 16759739.40 | 0.162895E+09 | 0.397044E+09 | 39294495.74 |
| August | 0.153063E+09 | 3945204.69 | 0.149118E+09 | 0.309376E+09 | 60500007.54 |
| September | 0.128581E+09 | 121021.29 | 0.128460E+09 | 0.221324E+09 | 0.129750E+09 |
| October | 0.110198E+09 | 0.00 | 0.110198E+09 | 0.119058E+09 | 0.226740E+09 |
| November | 86092241.07 | 0.00 | 86092241.07 | 32242322.44 | 0.381706E+09 |
| December | 83228616.05 | 0.00 | 83228616.05 | 11319263.04 | 0.531226E+09 |
| Annual Sum or Average | 0.157392E+10 | 58872280.77 | 0.151504E+10 | 0.213717E+10 | 0.293065E+10 |
| Minimum of Months | 83228616.05 | 0.00 | 83228616.05 | 11319263.04 | 39294495.74 |
| Maximum of Months | 0.188495E+09 | 22859994.57 | 0.170297E+09 | 0.414938E+09 | 0.531226E+09 |
Report: WindowEnergyReportMonthly
For: TWINDOW1 N N2A
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 83878188.20 | 0.00 | 83878188.20 | 16432555.76 | 0.476102E+09 |
| February | 92512121.34 | 0.00 | 92512121.34 | 41454212.14 | 0.377883E+09 |
| March | 0.134083E+09 | 15028.79 | 0.134068E+09 | 95596188.31 | 0.348725E+09 |
| April | 0.150287E+09 | 1624148.27 | 0.148663E+09 | 0.174085E+09 | 0.194557E+09 |
| May | 0.183844E+09 | 13547143.77 | 0.170297E+09 | 0.302872E+09 | 0.112229E+09 |
| June | 0.188495E+09 | 22859994.57 | 0.165635E+09 | 0.414857E+09 | 51086562.37 |
| July | 0.179655E+09 | 16759739.40 | 0.162895E+09 | 0.396977E+09 | 39253805.04 |
| August | 0.153063E+09 | 3945204.69 | 0.149118E+09 | 0.309299E+09 | 60454676.83 |
| September | 0.128581E+09 | 121021.29 | 0.128460E+09 | 0.221168E+09 | 0.129648E+09 |
| October | 0.110198E+09 | 0.00 | 0.110198E+09 | 0.118799E+09 | 0.226366E+09 |
| November | 86092241.07 | 0.00 | 86092241.07 | 32008794.01 | 0.381306E+09 |
| December | 83228616.05 | 0.00 | 83228616.05 | 11265438.37 | 0.531116E+09 |
| Annual Sum or Average | 0.157392E+10 | 58872280.77 | 0.151504E+10 | 0.213481E+10 | 0.292873E+10 |
| Minimum of Months | 83228616.05 | 0.00 | 83228616.05 | 11265438.37 | 39253805.04 |
| Maximum of Months | 0.188495E+09 | 22859994.57 | 0.170297E+09 | 0.414857E+09 | 0.531116E+09 |
Report: WindowEnergyReportMonthly
For: TWINDOW1 S S1A
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.569082E+09 | 0.430004E+09 | 0.139079E+09 | 0.761416E+09 | 0.436728E+09 |
| February | 0.489495E+09 | 0.347638E+09 | 0.141858E+09 | 0.670057E+09 | 0.350827E+09 |
| March | 0.422895E+09 | 0.239752E+09 | 0.183143E+09 | 0.595444E+09 | 0.342185E+09 |
| April | 0.290400E+09 | 0.112456E+09 | 0.177944E+09 | 0.463752E+09 | 0.202889E+09 |
| May | 0.207588E+09 | 29308895.00 | 0.178279E+09 | 0.372997E+09 | 0.120401E+09 |
| June | 0.173878E+09 | 11809415.54 | 0.162068E+09 | 0.396435E+09 | 52687482.73 |
| July | 0.182972E+09 | 17574380.96 | 0.165397E+09 | 0.415690E+09 | 40933525.02 |
| August | 0.229443E+09 | 58582872.53 | 0.170860E+09 | 0.480636E+09 | 63538866.82 |
| September | 0.355405E+09 | 0.186733E+09 | 0.168672E+09 | 0.665179E+09 | 0.130449E+09 |
| October | 0.494068E+09 | 0.334439E+09 | 0.159628E+09 | 0.788364E+09 | 0.224071E+09 |
| November | 0.578056E+09 | 0.441679E+09 | 0.136377E+09 | 0.817259E+09 | 0.355164E+09 |
| December | 0.586752E+09 | 0.440209E+09 | 0.146543E+09 | 0.770160E+09 | 0.471654E+09 |
| Annual Sum or Average | 0.458003E+10 | 0.265019E+10 | 0.192985E+10 | 0.719739E+10 | 0.279153E+10 |
| Minimum of Months | 0.173878E+09 | 11809415.54 | 0.136377E+09 | 0.372997E+09 | 40933525.02 |
| Maximum of Months | 0.586752E+09 | 0.441679E+09 | 0.183143E+09 | 0.817259E+09 | 0.471654E+09 |
Report: WindowEnergyReportMonthly
For: TWINDOW1 S S2A
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.569082E+09 | 0.430004E+09 | 0.139079E+09 | 0.761180E+09 | 0.436506E+09 |
| February | 0.489495E+09 | 0.347638E+09 | 0.141858E+09 | 0.669692E+09 | 0.350750E+09 |
| March | 0.422895E+09 | 0.239752E+09 | 0.183143E+09 | 0.594982E+09 | 0.341965E+09 |
| April | 0.290400E+09 | 0.112456E+09 | 0.177944E+09 | 0.463336E+09 | 0.202750E+09 |
| May | 0.207588E+09 | 29308895.00 | 0.178279E+09 | 0.372769E+09 | 0.120310E+09 |
| June | 0.173878E+09 | 11809415.54 | 0.162068E+09 | 0.396351E+09 | 52639541.98 |
| July | 0.182972E+09 | 17574380.96 | 0.165397E+09 | 0.415624E+09 | 40892649.70 |
| August | 0.229443E+09 | 58582872.53 | 0.170860E+09 | 0.480564E+09 | 63493556.92 |
| September | 0.355405E+09 | 0.186733E+09 | 0.168672E+09 | 0.665054E+09 | 0.130348E+09 |
| October | 0.494068E+09 | 0.334439E+09 | 0.159628E+09 | 0.788250E+09 | 0.223800E+09 |
| November | 0.578056E+09 | 0.441679E+09 | 0.136377E+09 | 0.817027E+09 | 0.354933E+09 |
| December | 0.586752E+09 | 0.440209E+09 | 0.146543E+09 | 0.769912E+09 | 0.471464E+09 |
| Annual Sum or Average | 0.458003E+10 | 0.265019E+10 | 0.192985E+10 | 0.719474E+10 | 0.278985E+10 |
| Minimum of Months | 0.173878E+09 | 11809415.54 | 0.136377E+09 | 0.372769E+09 | 40892649.70 |
| Maximum of Months | 0.586752E+09 | 0.441679E+09 | 0.183143E+09 | 0.817027E+09 | 0.471464E+09 |
Report: WindowEnergyReportMonthly
For: TWINDOW14
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 35557491.82 | 19352925.03 | 16204566.78 | 33625142.56 | 74103673.20 |
| February | 42713214.31 | 24293751.38 | 18419462.93 | 47889695.95 | 58681531.34 |
| March | 58381347.06 | 32085546.91 | 26295800.15 | 72091469.99 | 55038354.68 |
| April | 68246563.70 | 37909637.08 | 30336926.62 | 98923730.35 | 32720558.99 |
| May | 72705021.67 | 39493347.19 | 33211674.48 | 0.117636E+09 | 21074167.32 |
| June | 70471642.79 | 39218817.94 | 31252824.85 | 0.128130E+09 | 10704708.15 |
| July | 65385600.53 | 34238620.08 | 31146980.45 | 0.119031E+09 | 9253939.27 |
| August | 62108639.14 | 31768036.26 | 30340602.88 | 0.108487E+09 | 12819322.86 |
| September | 59556541.34 | 33970741.09 | 25585800.25 | 97691962.98 | 23321060.40 |
| October | 47259759.28 | 25475314.11 | 21784445.17 | 65503508.61 | 39280149.09 |
| November | 41043835.27 | 23880237.70 | 17163597.57 | 45079424.18 | 60571102.79 |
| December | 35356611.78 | 18718475.18 | 16638136.60 | 31598764.44 | 80799420.18 |
| Annual Sum or Average | 0.658786E+09 | 0.360405E+09 | 0.298381E+09 | 0.965688E+09 | 0.478368E+09 |
| Minimum of Months | 35356611.78 | 18718475.18 | 16204566.78 | 31598764.44 | 9253939.27 |
| Maximum of Months | 72705021.67 | 39493347.19 | 33211674.48 | 0.128130E+09 | 80799420.18 |
Report: WindowEnergyReportMonthly
For: ENTRANCE DOOR
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.105899E+09 | 57637826.98 | 48261232.60 | 0.103353E+09 | 0.213833E+09 |
| February | 0.127211E+09 | 72352837.43 | 54857744.52 | 0.147476E+09 | 0.167775E+09 |
| March | 0.173874E+09 | 95558743.61 | 78315436.92 | 0.222048E+09 | 0.154467E+09 |
| April | 0.203255E+09 | 0.112904E+09 | 90350917.24 | 0.297749E+09 | 96992956.89 |
| May | 0.216534E+09 | 0.117621E+09 | 98912631.77 | 0.348833E+09 | 66629250.59 |
| June | 0.209882E+09 | 0.116803E+09 | 93078690.10 | 0.376262E+09 | 36287690.75 |
| July | 0.194735E+09 | 0.101971E+09 | 92763459.12 | 0.348844E+09 | 32191679.02 |
| August | 0.184975E+09 | 94613117.88 | 90361866.05 | 0.317355E+09 | 44217448.09 |
| September | 0.177374E+09 | 0.101173E+09 | 76200880.52 | 0.285830E+09 | 77122721.28 |
| October | 0.140751E+09 | 75871825.28 | 64879499.07 | 0.189231E+09 | 0.127919E+09 |
| November | 0.122239E+09 | 71121290.78 | 51117464.97 | 0.130997E+09 | 0.192767E+09 |
| December | 0.105301E+09 | 55748277.42 | 49552511.43 | 95871278.26 | 0.237859E+09 |
| Annual Sum or Average | 0.196203E+10 | 0.107338E+10 | 0.888652E+09 | 0.286385E+10 | 0.144806E+10 |
| Minimum of Months | 0.105301E+09 | 55748277.42 | 48261232.60 | 95871278.26 | 32191679.02 |
| Maximum of Months | 0.216534E+09 | 0.117621E+09 | 98912631.77 | 0.376262E+09 | 0.237859E+09 |
Report: WindowEnergyReportMonthly
For: MWINDOW14
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 35557491.82 | 19352925.03 | 16204566.78 | 30984221.41 | 82651395.64 |
| February | 42713214.31 | 24293751.38 | 18419462.93 | 44797560.55 | 65902843.91 |
| March | 58381347.06 | 32085546.91 | 26295800.15 | 67637352.11 | 61860569.49 |
| April | 68246563.70 | 37909637.08 | 30336926.62 | 96074880.84 | 35949084.49 |
| May | 72705021.67 | 39493347.19 | 33211674.48 | 0.117048E+09 | 22337154.68 |
| June | 70471642.79 | 39218817.94 | 31252824.85 | 0.129580E+09 | 10990254.73 |
| July | 65385600.53 | 34238620.08 | 31146980.45 | 0.120873E+09 | 9298385.63 |
| August | 62108639.14 | 31768036.26 | 30340602.88 | 0.109655E+09 | 13116715.53 |
| September | 59556541.34 | 33970741.09 | 25585800.25 | 97466433.07 | 24337347.33 |
| October | 47259759.28 | 25475314.11 | 21784445.17 | 62634727.45 | 43940900.63 |
| November | 41043835.27 | 23880237.70 | 17163597.57 | 41557560.63 | 69443195.56 |
| December | 35356611.78 | 18718475.18 | 16638136.60 | 29006216.87 | 90141917.71 |
| Annual Sum or Average | 0.658786E+09 | 0.360405E+09 | 0.298381E+09 | 0.947315E+09 | 0.529970E+09 |
| Minimum of Months | 35356611.78 | 18718475.18 | 16204566.78 | 29006216.87 | 9298385.63 |
| Maximum of Months | 72705021.67 | 39493347.19 | 33211674.48 | 0.129580E+09 | 90141917.71 |
Report: WindowZoneSummaryMonthly
For: G SW APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 342.86 | 274.34 | 270.58 | 193.30 | 77.28 | 0.00 | 0.00 |
| February | 353.98 | 238.73 | 267.73 | 178.39 | 89.34 | 0.00 | 0.00 |
| March | 347.26 | 202.85 | 247.11 | 137.32 | 109.78 | 0.00 | 0.00 |
| April | 342.15 | 127.42 | 214.46 | 98.63 | 115.83 | 0.00 | 0.00 |
| May | 334.00 | 75.60 | 187.82 | 69.89 | 117.93 | 0.00 | 0.00 |
| June | 368.13 | 34.86 | 174.73 | 62.41 | 112.32 | 0.00 | 0.00 |
| July | 346.49 | 26.85 | 163.92 | 54.12 | 109.80 | 0.00 | 0.00 |
| August | 354.68 | 42.56 | 178.04 | 68.89 | 109.15 | 0.00 | 0.00 |
| September | 424.18 | 90.95 | 231.85 | 124.89 | 106.96 | 0.00 | 0.00 |
| October | 413.01 | 153.56 | 265.82 | 172.33 | 93.49 | 0.00 | 0.00 |
| November | 385.77 | 251.88 | 290.86 | 211.54 | 79.32 | 0.00 | 0.00 |
| December | 334.51 | 301.44 | 274.11 | 194.26 | 79.86 | 0.00 | 0.00 |
| Annual Sum or Average | 362.12 | 151.32 | 230.31 | 130.17 | 100.14 | 0.00 | 0.00 |
| Minimum of Months | 334.00 | 26.85 | 163.92 | 54.12 | 77.28 | 0.00 | 0.00 |
| Maximum of Months | 424.18 | 301.44 | 290.86 | 211.54 | 117.93 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: G NW APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 67.00 | 282.90 | 89.42 | 32.75 | 56.67 | 0.00 | 0.00 |
| February | 97.16 | 244.37 | 103.64 | 34.70 | 68.94 | 0.00 | 0.00 |
| March | 162.55 | 199.94 | 139.28 | 47.82 | 91.46 | 0.00 | 0.00 |
| April | 232.43 | 121.18 | 160.41 | 55.87 | 104.54 | 0.00 | 0.00 |
| May | 307.17 | 71.32 | 178.95 | 64.00 | 114.95 | 0.00 | 0.00 |
| June | 374.96 | 33.76 | 180.37 | 66.68 | 113.70 | 0.00 | 0.00 |
| July | 339.23 | 25.91 | 162.68 | 53.81 | 108.86 | 0.00 | 0.00 |
| August | 290.20 | 40.71 | 149.52 | 48.49 | 101.03 | 0.00 | 0.00 |
| September | 252.44 | 89.92 | 144.34 | 52.89 | 91.44 | 0.00 | 0.00 |
| October | 162.93 | 156.06 | 122.50 | 47.47 | 75.03 | 0.00 | 0.00 |
| November | 89.53 | 256.20 | 101.06 | 41.14 | 59.92 | 0.00 | 0.00 |
| December | 54.52 | 318.80 | 86.12 | 29.90 | 56.22 | 0.00 | 0.00 |
| Annual Sum or Average | 202.99 | 152.98 | 134.98 | 48.00 | 86.98 | 0.00 | 0.00 |
| Minimum of Months | 54.52 | 25.91 | 86.12 | 29.90 | 56.22 | 0.00 | 0.00 |
| Maximum of Months | 374.96 | 318.80 | 180.37 | 66.68 | 114.95 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: OFFICE
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 335.20 | 276.86 | 267.80 | 190.66 | 77.14 | 0.00 | 0.00 |
| February | 360.00 | 244.24 | 275.92 | 185.55 | 90.37 | 0.00 | 0.00 |
| March | 335.96 | 206.19 | 248.73 | 139.44 | 109.29 | 0.00 | 0.00 |
| April | 330.23 | 137.61 | 221.77 | 104.34 | 117.43 | 0.00 | 0.00 |
| May | 309.35 | 95.90 | 190.63 | 72.39 | 118.24 | 0.00 | 0.00 |
| June | 338.58 | 60.02 | 180.39 | 67.61 | 112.78 | 0.00 | 0.00 |
| July | 315.19 | 55.12 | 170.05 | 59.84 | 110.22 | 0.00 | 0.00 |
| August | 326.80 | 73.33 | 182.30 | 71.30 | 111.00 | 0.00 | 0.00 |
| September | 392.64 | 123.79 | 232.87 | 126.66 | 106.21 | 0.00 | 0.00 |
| October | 381.13 | 181.70 | 258.00 | 164.50 | 93.49 | 0.00 | 0.00 |
| November | 372.51 | 264.12 | 289.01 | 208.80 | 80.21 | 0.00 | 0.00 |
| December | 328.50 | 306.20 | 274.08 | 193.48 | 80.60 | 0.00 | 0.00 |
| Annual Sum or Average | 343.55 | 168.38 | 232.29 | 131.66 | 100.63 | 0.00 | 0.00 |
| Minimum of Months | 309.35 | 55.12 | 170.05 | 59.84 | 77.14 | 0.00 | 0.00 |
| Maximum of Months | 392.64 | 306.20 | 289.01 | 208.80 | 118.24 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: G NE APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 49.01 | 269.16 | 86.64 | 30.11 | 56.53 | 0.00 | 0.00 |
| February | 93.69 | 227.66 | 111.82 | 41.85 | 69.97 | 0.00 | 0.00 |
| March | 151.82 | 186.29 | 140.90 | 49.93 | 90.97 | 0.00 | 0.00 |
| April | 233.89 | 112.86 | 167.71 | 61.58 | 106.13 | 0.00 | 0.00 |
| May | 308.35 | 68.86 | 181.76 | 66.51 | 115.26 | 0.00 | 0.00 |
| June | 382.82 | 32.85 | 186.03 | 71.88 | 114.15 | 0.00 | 0.00 |
| July | 348.72 | 25.44 | 168.81 | 59.53 | 109.28 | 0.00 | 0.00 |
| August | 295.38 | 39.13 | 153.79 | 50.90 | 102.88 | 0.00 | 0.00 |
| September | 245.51 | 82.54 | 145.36 | 54.67 | 90.70 | 0.00 | 0.00 |
| October | 140.06 | 148.28 | 114.68 | 39.64 | 75.04 | 0.00 | 0.00 |
| November | 70.34 | 241.63 | 99.21 | 38.40 | 60.81 | 0.00 | 0.00 |
| December | 38.35 | 304.03 | 86.09 | 29.13 | 56.96 | 0.00 | 0.00 |
| Annual Sum or Average | 196.94 | 144.51 | 136.97 | 49.49 | 87.47 | 0.00 | 0.00 |
| Minimum of Months | 38.35 | 25.44 | 86.09 | 29.13 | 56.53 | 0.00 | 0.00 |
| Maximum of Months | 382.82 | 304.03 | 186.03 | 71.88 | 115.26 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: G N1 APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 6.44 | 180.96 | 31.32 | 0.00 | 31.32 | 0.00 | 0.00 |
| February | 19.21 | 155.50 | 38.24 | 0.00 | 38.24 | 0.00 | 0.00 |
| March | 40.50 | 126.46 | 50.06 | 0.01 | 50.06 | 0.00 | 0.00 |
| April | 71.24 | 75.85 | 57.98 | 0.63 | 57.35 | 0.00 | 0.00 |
| May | 116.84 | 42.70 | 68.64 | 5.06 | 63.58 | 0.00 | 0.00 |
| June | 165.01 | 19.94 | 72.72 | 8.82 | 63.90 | 0.00 | 0.00 |
| July | 152.30 | 15.10 | 67.08 | 6.26 | 60.82 | 0.00 | 0.00 |
| August | 118.05 | 23.73 | 57.15 | 1.47 | 55.67 | 0.00 | 0.00 |
| September | 86.55 | 53.37 | 49.61 | 0.05 | 49.56 | 0.00 | 0.00 |
| October | 41.57 | 96.23 | 41.14 | 0.00 | 41.14 | 0.00 | 0.00 |
| November | 9.66 | 164.88 | 33.21 | 0.00 | 33.21 | 0.00 | 0.00 |
| December | 3.91 | 205.21 | 31.07 | 0.00 | 31.07 | 0.00 | 0.00 |
| Annual Sum or Average | 69.53 | 96.38 | 49.91 | 1.87 | 48.04 | 0.00 | 0.00 |
| Minimum of Months | 3.91 | 15.10 | 31.07 | 0.00 | 31.07 | 0.00 | 0.00 |
| Maximum of Months | 165.01 | 205.21 | 72.72 | 8.82 | 63.90 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: G N2 APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 6.43 | 180.91 | 31.32 | 0.00 | 31.32 | 0.00 | 0.00 |
| February | 19.18 | 155.51 | 38.24 | 0.00 | 38.24 | 0.00 | 0.00 |
| March | 40.46 | 126.45 | 50.06 | 0.01 | 50.06 | 0.00 | 0.00 |
| April | 71.15 | 75.90 | 57.98 | 0.63 | 57.35 | 0.00 | 0.00 |
| May | 116.80 | 42.70 | 68.64 | 5.06 | 63.58 | 0.00 | 0.00 |
| June | 164.99 | 19.94 | 72.72 | 8.82 | 63.90 | 0.00 | 0.00 |
| July | 152.29 | 15.10 | 67.08 | 6.26 | 60.82 | 0.00 | 0.00 |
| August | 118.03 | 23.73 | 57.15 | 1.47 | 55.67 | 0.00 | 0.00 |
| September | 86.54 | 53.36 | 49.61 | 0.05 | 49.56 | 0.00 | 0.00 |
| October | 41.56 | 96.20 | 41.14 | 0.00 | 41.14 | 0.00 | 0.00 |
| November | 9.65 | 164.82 | 33.21 | 0.00 | 33.21 | 0.00 | 0.00 |
| December | 3.90 | 205.20 | 31.07 | 0.00 | 31.07 | 0.00 | 0.00 |
| Annual Sum or Average | 69.51 | 96.37 | 49.91 | 1.87 | 48.04 | 0.00 | 0.00 |
| Minimum of Months | 3.90 | 15.10 | 31.07 | 0.00 | 31.07 | 0.00 | 0.00 |
| Maximum of Months | 164.99 | 205.20 | 72.72 | 8.82 | 63.90 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: G S1 APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 287.03 | 171.02 | 212.47 | 160.54 | 51.93 | 0.00 | 0.00 |
| February | 281.41 | 149.48 | 202.34 | 143.70 | 58.64 | 0.00 | 0.00 |
| March | 228.49 | 128.39 | 157.89 | 89.51 | 68.38 | 0.00 | 0.00 |
| April | 183.43 | 80.96 | 112.04 | 43.39 | 68.65 | 0.00 | 0.00 |
| May | 143.47 | 46.29 | 77.50 | 10.94 | 66.56 | 0.00 | 0.00 |
| June | 157.60 | 20.70 | 67.08 | 4.56 | 62.53 | 0.00 | 0.00 |
| July | 159.32 | 15.85 | 68.31 | 6.56 | 61.75 | 0.00 | 0.00 |
| August | 182.81 | 25.15 | 85.66 | 21.87 | 63.79 | 0.00 | 0.00 |
| September | 259.85 | 53.86 | 137.12 | 72.04 | 65.07 | 0.00 | 0.00 |
| October | 294.70 | 92.29 | 184.46 | 124.87 | 59.60 | 0.00 | 0.00 |
| November | 312.41 | 154.19 | 223.02 | 170.40 | 52.61 | 0.00 | 0.00 |
| December | 288.29 | 186.87 | 219.07 | 164.36 | 54.71 | 0.00 | 0.00 |
| Annual Sum or Average | 231.19 | 93.47 | 145.23 | 84.04 | 61.20 | 0.00 | 0.00 |
| Minimum of Months | 143.47 | 15.85 | 67.08 | 4.56 | 51.93 | 0.00 | 0.00 |
| Maximum of Months | 312.41 | 186.87 | 223.02 | 170.40 | 68.65 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: G S2 APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 286.87 | 171.25 | 212.47 | 160.54 | 51.93 | 0.00 | 0.00 |
| February | 281.01 | 150.07 | 202.34 | 143.70 | 58.64 | 0.00 | 0.00 |
| March | 227.88 | 129.17 | 157.89 | 89.51 | 68.38 | 0.00 | 0.00 |
| April | 182.74 | 81.82 | 112.04 | 43.39 | 68.65 | 0.00 | 0.00 |
| May | 142.70 | 46.99 | 77.50 | 10.94 | 66.56 | 0.00 | 0.00 |
| June | 156.49 | 21.30 | 67.08 | 4.56 | 62.53 | 0.00 | 0.00 |
| July | 158.18 | 16.48 | 68.31 | 6.56 | 61.75 | 0.00 | 0.00 |
| August | 181.83 | 25.87 | 85.66 | 21.87 | 63.79 | 0.00 | 0.00 |
| September | 259.14 | 54.73 | 137.12 | 72.04 | 65.07 | 0.00 | 0.00 |
| October | 294.23 | 92.92 | 184.46 | 124.87 | 59.60 | 0.00 | 0.00 |
| November | 312.11 | 154.69 | 223.02 | 170.40 | 52.61 | 0.00 | 0.00 |
| December | 287.91 | 187.47 | 219.07 | 164.36 | 54.71 | 0.00 | 0.00 |
| Annual Sum or Average | 230.55 | 94.12 | 145.23 | 84.04 | 61.20 | 0.00 | 0.00 |
| Minimum of Months | 142.70 | 16.48 | 67.08 | 4.56 | 51.93 | 0.00 | 0.00 |
| Maximum of Months | 312.11 | 187.47 | 223.02 | 170.40 | 68.65 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: M SW APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 334.20 | 286.71 | 270.58 | 193.30 | 77.28 | 0.00 | 0.00 |
| February | 340.80 | 258.32 | 267.73 | 178.39 | 89.34 | 0.00 | 0.00 |
| March | 328.28 | 227.85 | 247.11 | 137.32 | 109.78 | 0.00 | 0.00 |
| April | 331.54 | 138.87 | 214.46 | 98.63 | 115.83 | 0.00 | 0.00 |
| May | 328.92 | 79.19 | 187.82 | 69.89 | 117.93 | 0.00 | 0.00 |
| June | 365.94 | 35.75 | 174.73 | 62.41 | 112.32 | 0.00 | 0.00 |
| July | 346.42 | 26.45 | 163.92 | 54.12 | 109.80 | 0.00 | 0.00 |
| August | 355.79 | 41.08 | 178.04 | 68.89 | 109.15 | 0.00 | 0.00 |
| September | 424.86 | 88.11 | 231.85 | 124.89 | 106.96 | 0.00 | 0.00 |
| October | 412.44 | 151.24 | 265.82 | 172.33 | 93.49 | 0.00 | 0.00 |
| November | 384.72 | 249.30 | 290.86 | 211.54 | 79.32 | 0.00 | 0.00 |
| December | 328.85 | 308.16 | 274.11 | 194.26 | 79.86 | 0.00 | 0.00 |
| Annual Sum or Average | 356.81 | 157.08 | 230.31 | 130.17 | 100.14 | 0.00 | 0.00 |
| Minimum of Months | 328.28 | 26.45 | 163.92 | 54.12 | 77.28 | 0.00 | 0.00 |
| Maximum of Months | 424.86 | 308.16 | 290.86 | 211.54 | 117.93 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: M NW APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 63.48 | 293.69 | 89.42 | 32.75 | 56.67 | 0.00 | 0.00 |
| February | 89.12 | 263.17 | 103.64 | 34.70 | 68.94 | 0.00 | 0.00 |
| March | 146.56 | 226.19 | 139.28 | 47.82 | 91.46 | 0.00 | 0.00 |
| April | 220.83 | 135.59 | 160.41 | 55.87 | 104.54 | 0.00 | 0.00 |
| May | 301.83 | 75.03 | 178.95 | 64.00 | 114.95 | 0.00 | 0.00 |
| June | 372.63 | 34.57 | 180.37 | 66.68 | 113.70 | 0.00 | 0.00 |
| July | 339.21 | 25.50 | 162.68 | 53.81 | 108.86 | 0.00 | 0.00 |
| August | 291.62 | 39.42 | 149.52 | 48.49 | 101.03 | 0.00 | 0.00 |
| September | 253.80 | 87.55 | 144.34 | 52.89 | 91.44 | 0.00 | 0.00 |
| October | 163.61 | 153.98 | 122.50 | 47.47 | 75.03 | 0.00 | 0.00 |
| November | 90.03 | 254.53 | 101.06 | 41.14 | 59.92 | 0.00 | 0.00 |
| December | 52.92 | 324.56 | 86.12 | 29.90 | 56.22 | 0.00 | 0.00 |
| Annual Sum or Average | 199.31 | 158.97 | 134.98 | 48.00 | 86.98 | 0.00 | 0.00 |
| Minimum of Months | 52.92 | 25.50 | 86.12 | 29.90 | 56.22 | 0.00 | 0.00 |
| Maximum of Months | 372.63 | 324.56 | 180.37 | 66.68 | 114.95 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: M SE APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 327.17 | 284.50 | 267.80 | 190.66 | 77.14 | 0.00 | 0.00 |
| February | 349.53 | 255.49 | 275.92 | 185.55 | 90.37 | 0.00 | 0.00 |
| March | 322.03 | 219.64 | 248.73 | 139.44 | 109.29 | 0.00 | 0.00 |
| April | 331.61 | 128.33 | 221.77 | 104.34 | 117.43 | 0.00 | 0.00 |
| May | 326.65 | 72.76 | 190.63 | 72.39 | 118.24 | 0.00 | 0.00 |
| June | 372.24 | 33.23 | 180.39 | 67.61 | 112.78 | 0.00 | 0.00 |
| July | 355.01 | 25.04 | 170.05 | 59.84 | 110.22 | 0.00 | 0.00 |
| August | 359.89 | 38.38 | 182.30 | 71.30 | 111.00 | 0.00 | 0.00 |
| September | 418.98 | 81.74 | 232.87 | 126.66 | 106.21 | 0.00 | 0.00 |
| October | 394.41 | 148.42 | 258.00 | 164.50 | 93.49 | 0.00 | 0.00 |
| November | 376.35 | 246.44 | 289.01 | 208.80 | 80.21 | 0.00 | 0.00 |
| December | 324.70 | 306.42 | 274.08 | 193.48 | 80.60 | 0.00 | 0.00 |
| Annual Sum or Average | 354.71 | 152.87 | 232.29 | 131.66 | 100.63 | 0.00 | 0.00 |
| Minimum of Months | 322.03 | 25.04 | 170.05 | 59.84 | 77.14 | 0.00 | 0.00 |
| Maximum of Months | 418.98 | 306.42 | 289.01 | 208.80 | 118.24 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: M NE APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 45.30 | 279.36 | 86.64 | 30.11 | 56.53 | 0.00 | 0.00 |
| February | 84.42 | 245.80 | 111.82 | 41.85 | 69.97 | 0.00 | 0.00 |
| March | 134.02 | 211.98 | 140.90 | 49.93 | 90.97 | 0.00 | 0.00 |
| April | 220.97 | 125.45 | 167.71 | 61.58 | 106.13 | 0.00 | 0.00 |
| May | 303.01 | 72.07 | 181.76 | 66.51 | 115.26 | 0.00 | 0.00 |
| June | 380.44 | 33.54 | 186.03 | 71.88 | 114.15 | 0.00 | 0.00 |
| July | 348.69 | 24.99 | 168.81 | 59.53 | 109.28 | 0.00 | 0.00 |
| August | 296.82 | 37.82 | 153.79 | 50.90 | 102.88 | 0.00 | 0.00 |
| September | 247.00 | 80.28 | 145.36 | 54.67 | 90.70 | 0.00 | 0.00 |
| October | 140.62 | 146.28 | 114.68 | 39.64 | 75.04 | 0.00 | 0.00 |
| November | 70.63 | 239.80 | 99.21 | 38.40 | 60.81 | 0.00 | 0.00 |
| December | 36.57 | 309.71 | 86.09 | 29.13 | 56.96 | 0.00 | 0.00 |
| Annual Sum or Average | 192.85 | 150.15 | 136.97 | 49.49 | 87.47 | 0.00 | 0.00 |
| Minimum of Months | 36.57 | 24.99 | 86.09 | 29.13 | 56.53 | 0.00 | 0.00 |
| Maximum of Months | 380.44 | 309.71 | 186.03 | 71.88 | 115.26 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: M N1 APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 5.31 | 188.38 | 31.32 | 0.00 | 31.32 | 0.00 | 0.00 |
| February | 15.54 | 168.59 | 38.24 | 0.00 | 38.24 | 0.00 | 0.00 |
| March | 32.49 | 144.75 | 50.06 | 0.01 | 50.06 | 0.00 | 0.00 |
| April | 66.12 | 83.16 | 57.98 | 0.63 | 57.35 | 0.00 | 0.00 |
| May | 114.93 | 44.02 | 68.64 | 5.06 | 63.58 | 0.00 | 0.00 |
| June | 164.53 | 20.11 | 72.72 | 8.82 | 63.90 | 0.00 | 0.00 |
| July | 152.71 | 14.79 | 67.08 | 6.26 | 60.82 | 0.00 | 0.00 |
| August | 119.11 | 23.07 | 57.15 | 1.47 | 55.67 | 0.00 | 0.00 |
| September | 87.43 | 52.33 | 49.61 | 0.05 | 49.56 | 0.00 | 0.00 |
| October | 41.82 | 95.88 | 41.14 | 0.00 | 41.14 | 0.00 | 0.00 |
| November | 9.75 | 165.03 | 33.21 | 0.00 | 33.21 | 0.00 | 0.00 |
| December | 3.50 | 209.85 | 31.07 | 0.00 | 31.07 | 0.00 | 0.00 |
| Annual Sum or Average | 68.04 | 100.50 | 49.91 | 1.87 | 48.04 | 0.00 | 0.00 |
| Minimum of Months | 3.50 | 14.79 | 31.07 | 0.00 | 31.07 | 0.00 | 0.00 |
| Maximum of Months | 164.53 | 209.85 | 72.72 | 8.82 | 63.90 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: M N2 APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 5.31 | 188.30 | 31.32 | 0.00 | 31.32 | 0.00 | 0.00 |
| February | 15.49 | 168.63 | 38.24 | 0.00 | 38.24 | 0.00 | 0.00 |
| March | 32.40 | 144.80 | 50.06 | 0.01 | 50.06 | 0.00 | 0.00 |
| April | 66.06 | 83.18 | 57.98 | 0.63 | 57.35 | 0.00 | 0.00 |
| May | 114.90 | 44.01 | 68.64 | 5.06 | 63.58 | 0.00 | 0.00 |
| June | 164.51 | 20.10 | 72.72 | 8.82 | 63.90 | 0.00 | 0.00 |
| July | 152.70 | 14.79 | 67.08 | 6.26 | 60.82 | 0.00 | 0.00 |
| August | 119.10 | 23.06 | 57.15 | 1.47 | 55.67 | 0.00 | 0.00 |
| September | 87.42 | 52.32 | 49.61 | 0.05 | 49.56 | 0.00 | 0.00 |
| October | 41.80 | 95.85 | 41.14 | 0.00 | 41.14 | 0.00 | 0.00 |
| November | 9.73 | 164.95 | 33.21 | 0.00 | 33.21 | 0.00 | 0.00 |
| December | 3.49 | 209.83 | 31.07 | 0.00 | 31.07 | 0.00 | 0.00 |
| Annual Sum or Average | 68.02 | 100.49 | 49.91 | 1.87 | 48.04 | 0.00 | 0.00 |
| Minimum of Months | 3.49 | 14.79 | 31.07 | 0.00 | 31.07 | 0.00 | 0.00 |
| Maximum of Months | 164.51 | 209.83 | 72.72 | 8.82 | 63.90 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: M S1 APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 281.21 | 179.46 | 212.47 | 160.54 | 51.93 | 0.00 | 0.00 |
| February | 273.35 | 161.59 | 202.34 | 143.70 | 58.64 | 0.00 | 0.00 |
| March | 218.36 | 142.61 | 157.89 | 89.51 | 68.38 | 0.00 | 0.00 |
| April | 178.83 | 85.96 | 112.04 | 43.39 | 68.65 | 0.00 | 0.00 |
| May | 141.72 | 47.56 | 77.50 | 10.94 | 66.56 | 0.00 | 0.00 |
| June | 157.33 | 20.86 | 67.08 | 4.56 | 62.53 | 0.00 | 0.00 |
| July | 159.77 | 15.51 | 68.31 | 6.56 | 61.75 | 0.00 | 0.00 |
| August | 183.59 | 24.34 | 85.66 | 21.87 | 63.79 | 0.00 | 0.00 |
| September | 260.01 | 52.44 | 137.12 | 72.04 | 65.07 | 0.00 | 0.00 |
| October | 293.88 | 91.46 | 184.46 | 124.87 | 59.60 | 0.00 | 0.00 |
| November | 311.15 | 153.36 | 223.02 | 170.40 | 52.61 | 0.00 | 0.00 |
| December | 284.15 | 191.76 | 219.07 | 164.36 | 54.71 | 0.00 | 0.00 |
| Annual Sum or Average | 228.27 | 96.92 | 145.23 | 84.04 | 61.20 | 0.00 | 0.00 |
| Minimum of Months | 141.72 | 15.51 | 67.08 | 4.56 | 51.93 | 0.00 | 0.00 |
| Maximum of Months | 311.15 | 191.76 | 223.02 | 170.40 | 68.65 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: M S2 APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 281.19 | 179.42 | 212.47 | 160.54 | 51.93 | 0.00 | 0.00 |
| February | 273.27 | 161.65 | 202.34 | 143.70 | 58.64 | 0.00 | 0.00 |
| March | 218.29 | 142.61 | 157.89 | 89.51 | 68.38 | 0.00 | 0.00 |
| April | 178.79 | 85.96 | 112.04 | 43.39 | 68.65 | 0.00 | 0.00 |
| May | 141.70 | 47.55 | 77.50 | 10.94 | 66.56 | 0.00 | 0.00 |
| June | 157.31 | 20.86 | 67.08 | 4.56 | 62.53 | 0.00 | 0.00 |
| July | 159.76 | 15.50 | 68.31 | 6.56 | 61.75 | 0.00 | 0.00 |
| August | 183.57 | 24.33 | 85.66 | 21.87 | 63.79 | 0.00 | 0.00 |
| September | 260.00 | 52.43 | 137.12 | 72.04 | 65.07 | 0.00 | 0.00 |
| October | 293.88 | 91.44 | 184.46 | 124.87 | 59.60 | 0.00 | 0.00 |
| November | 311.14 | 153.33 | 223.02 | 170.40 | 52.61 | 0.00 | 0.00 |
| December | 284.11 | 191.76 | 219.07 | 164.36 | 54.71 | 0.00 | 0.00 |
| Annual Sum or Average | 228.24 | 96.92 | 145.23 | 84.04 | 61.20 | 0.00 | 0.00 |
| Minimum of Months | 141.70 | 15.50 | 67.08 | 4.56 | 51.93 | 0.00 | 0.00 |
| Maximum of Months | 311.14 | 191.76 | 223.02 | 170.40 | 68.65 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: T SW APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 335.95 | 265.84 | 270.58 | 193.30 | 77.28 | 0.00 | 0.00 |
| February | 343.46 | 235.91 | 267.73 | 178.39 | 89.34 | 0.00 | 0.00 |
| March | 331.75 | 205.46 | 247.11 | 137.32 | 109.78 | 0.00 | 0.00 |
| April | 330.85 | 125.13 | 214.46 | 98.63 | 115.83 | 0.00 | 0.00 |
| May | 323.85 | 73.50 | 187.82 | 69.89 | 117.93 | 0.00 | 0.00 |
| June | 357.17 | 34.33 | 174.73 | 62.41 | 112.32 | 0.00 | 0.00 |
| July | 337.53 | 25.65 | 163.92 | 54.12 | 109.80 | 0.00 | 0.00 |
| August | 347.78 | 39.46 | 178.04 | 68.89 | 109.15 | 0.00 | 0.00 |
| September | 418.60 | 83.39 | 231.85 | 124.89 | 106.96 | 0.00 | 0.00 |
| October | 413.62 | 135.44 | 265.82 | 172.33 | 93.49 | 0.00 | 0.00 |
| November | 389.76 | 223.60 | 290.86 | 211.54 | 79.32 | 0.00 | 0.00 |
| December | 330.81 | 287.99 | 274.11 | 194.26 | 79.86 | 0.00 | 0.00 |
| Annual Sum or Average | 354.98 | 144.20 | 230.31 | 130.17 | 100.14 | 0.00 | 0.00 |
| Minimum of Months | 323.85 | 25.65 | 163.92 | 54.12 | 77.28 | 0.00 | 0.00 |
| Maximum of Months | 418.60 | 287.99 | 290.86 | 211.54 | 117.93 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: T NW APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 64.37 | 278.49 | 89.42 | 32.75 | 56.67 | 0.00 | 0.00 |
| February | 90.44 | 246.69 | 103.64 | 34.70 | 68.94 | 0.00 | 0.00 |
| March | 149.09 | 207.02 | 139.28 | 47.82 | 91.46 | 0.00 | 0.00 |
| April | 221.68 | 122.05 | 160.41 | 55.87 | 104.54 | 0.00 | 0.00 |
| May | 297.74 | 70.10 | 178.95 | 64.00 | 114.95 | 0.00 | 0.00 |
| June | 363.85 | 33.41 | 180.37 | 66.68 | 113.70 | 0.00 | 0.00 |
| July | 330.49 | 24.88 | 162.68 | 53.81 | 108.86 | 0.00 | 0.00 |
| August | 284.41 | 38.00 | 149.52 | 48.49 | 101.03 | 0.00 | 0.00 |
| September | 249.52 | 82.60 | 144.34 | 52.89 | 91.44 | 0.00 | 0.00 |
| October | 167.54 | 134.69 | 122.50 | 47.47 | 75.03 | 0.00 | 0.00 |
| November | 93.49 | 232.11 | 101.06 | 41.14 | 59.92 | 0.00 | 0.00 |
| December | 54.10 | 307.98 | 86.12 | 29.90 | 56.22 | 0.00 | 0.00 |
| Annual Sum or Average | 197.72 | 147.70 | 134.98 | 48.00 | 86.98 | 0.00 | 0.00 |
| Minimum of Months | 54.10 | 24.88 | 86.12 | 29.90 | 56.22 | 0.00 | 0.00 |
| Maximum of Months | 363.85 | 307.98 | 180.37 | 66.68 | 114.95 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: T SE APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 328.63 | 263.50 | 267.80 | 190.66 | 77.14 | 0.00 | 0.00 |
| February | 352.19 | 232.77 | 275.92 | 185.55 | 90.37 | 0.00 | 0.00 |
| March | 326.27 | 198.11 | 248.73 | 139.44 | 109.29 | 0.00 | 0.00 |
| April | 331.89 | 116.59 | 221.77 | 104.34 | 117.43 | 0.00 | 0.00 |
| May | 321.83 | 68.09 | 190.63 | 72.39 | 118.24 | 0.00 | 0.00 |
| June | 363.28 | 31.84 | 180.39 | 67.61 | 112.78 | 0.00 | 0.00 |
| July | 345.89 | 24.26 | 170.05 | 59.84 | 110.22 | 0.00 | 0.00 |
| August | 351.80 | 36.85 | 182.30 | 71.30 | 111.00 | 0.00 | 0.00 |
| September | 412.93 | 77.60 | 232.87 | 126.66 | 106.21 | 0.00 | 0.00 |
| October | 395.28 | 132.47 | 258.00 | 164.50 | 93.49 | 0.00 | 0.00 |
| November | 380.81 | 220.56 | 289.01 | 208.80 | 80.21 | 0.00 | 0.00 |
| December | 326.49 | 285.85 | 274.08 | 193.48 | 80.60 | 0.00 | 0.00 |
| Annual Sum or Average | 352.91 | 140.27 | 232.29 | 131.66 | 100.63 | 0.00 | 0.00 |
| Minimum of Months | 321.83 | 24.26 | 170.05 | 59.84 | 77.14 | 0.00 | 0.00 |
| Maximum of Months | 412.93 | 285.85 | 289.01 | 208.80 | 118.24 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: T NE APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 47.56 | 265.41 | 86.64 | 30.11 | 56.53 | 0.00 | 0.00 |
| February | 87.54 | 230.53 | 111.82 | 41.85 | 69.97 | 0.00 | 0.00 |
| March | 138.89 | 194.06 | 140.90 | 49.93 | 90.97 | 0.00 | 0.00 |
| April | 223.08 | 113.91 | 167.71 | 61.58 | 106.13 | 0.00 | 0.00 |
| May | 298.58 | 67.59 | 181.76 | 66.51 | 115.26 | 0.00 | 0.00 |
| June | 371.33 | 32.25 | 186.03 | 71.88 | 114.15 | 0.00 | 0.00 |
| July | 339.65 | 24.27 | 168.81 | 59.53 | 109.28 | 0.00 | 0.00 |
| August | 289.43 | 36.41 | 153.79 | 50.90 | 102.88 | 0.00 | 0.00 |
| September | 243.10 | 76.19 | 145.36 | 54.67 | 90.70 | 0.00 | 0.00 |
| October | 145.82 | 128.33 | 114.68 | 39.64 | 75.04 | 0.00 | 0.00 |
| November | 75.87 | 218.46 | 99.21 | 38.40 | 60.81 | 0.00 | 0.00 |
| December | 39.18 | 294.31 | 86.09 | 29.13 | 56.96 | 0.00 | 0.00 |
| Annual Sum or Average | 192.12 | 139.73 | 136.97 | 49.49 | 87.47 | 0.00 | 0.00 |
| Minimum of Months | 39.18 | 24.27 | 86.09 | 29.13 | 56.53 | 0.00 | 0.00 |
| Maximum of Months | 371.33 | 294.31 | 186.03 | 71.88 | 115.26 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: T N1 APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 6.16 | 177.84 | 31.32 | 0.00 | 31.32 | 0.00 | 0.00 |
| February | 17.23 | 156.25 | 38.24 | 0.00 | 38.24 | 0.00 | 0.00 |
| March | 35.85 | 130.29 | 50.06 | 0.01 | 50.06 | 0.00 | 0.00 |
| April | 67.34 | 75.11 | 57.98 | 0.63 | 57.35 | 0.00 | 0.00 |
| May | 113.17 | 41.93 | 68.64 | 5.06 | 63.58 | 0.00 | 0.00 |
| June | 160.08 | 19.73 | 72.72 | 8.82 | 63.90 | 0.00 | 0.00 |
| July | 148.24 | 14.67 | 67.08 | 6.26 | 60.82 | 0.00 | 0.00 |
| August | 115.51 | 22.59 | 57.15 | 1.47 | 55.67 | 0.00 | 0.00 |
| September | 85.39 | 50.06 | 49.61 | 0.05 | 49.56 | 0.00 | 0.00 |
| October | 44.45 | 84.66 | 41.14 | 0.00 | 41.14 | 0.00 | 0.00 |
| November | 12.44 | 147.26 | 33.21 | 0.00 | 33.21 | 0.00 | 0.00 |
| December | 4.23 | 198.34 | 31.07 | 0.00 | 31.07 | 0.00 | 0.00 |
| Annual Sum or Average | 67.77 | 92.93 | 49.91 | 1.87 | 48.04 | 0.00 | 0.00 |
| Minimum of Months | 4.23 | 14.67 | 31.07 | 0.00 | 31.07 | 0.00 | 0.00 |
| Maximum of Months | 160.08 | 198.34 | 72.72 | 8.82 | 63.90 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: T N2 APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 6.14 | 177.76 | 31.32 | 0.00 | 31.32 | 0.00 | 0.00 |
| February | 17.14 | 156.20 | 38.24 | 0.00 | 38.24 | 0.00 | 0.00 |
| March | 35.69 | 130.20 | 50.06 | 0.01 | 50.06 | 0.00 | 0.00 |
| April | 67.16 | 75.06 | 57.98 | 0.63 | 57.35 | 0.00 | 0.00 |
| May | 113.08 | 41.90 | 68.64 | 5.06 | 63.58 | 0.00 | 0.00 |
| June | 160.05 | 19.71 | 72.72 | 8.82 | 63.90 | 0.00 | 0.00 |
| July | 148.21 | 14.66 | 67.08 | 6.26 | 60.82 | 0.00 | 0.00 |
| August | 115.48 | 22.57 | 57.15 | 1.47 | 55.67 | 0.00 | 0.00 |
| September | 85.33 | 50.02 | 49.61 | 0.05 | 49.56 | 0.00 | 0.00 |
| October | 44.35 | 84.52 | 41.14 | 0.00 | 41.14 | 0.00 | 0.00 |
| November | 12.35 | 147.11 | 33.21 | 0.00 | 33.21 | 0.00 | 0.00 |
| December | 4.21 | 198.30 | 31.07 | 0.00 | 31.07 | 0.00 | 0.00 |
| Annual Sum or Average | 67.69 | 92.87 | 49.91 | 1.87 | 48.04 | 0.00 | 0.00 |
| Minimum of Months | 4.21 | 14.66 | 31.07 | 0.00 | 31.07 | 0.00 | 0.00 |
| Maximum of Months | 160.05 | 198.30 | 72.72 | 8.82 | 63.90 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: T S1 APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 284.28 | 163.06 | 212.47 | 160.54 | 51.93 | 0.00 | 0.00 |
| February | 276.97 | 145.02 | 202.34 | 143.70 | 58.64 | 0.00 | 0.00 |
| March | 222.31 | 127.76 | 157.89 | 89.51 | 68.38 | 0.00 | 0.00 |
| April | 178.92 | 78.27 | 112.04 | 43.39 | 68.65 | 0.00 | 0.00 |
| May | 139.26 | 44.95 | 77.50 | 10.94 | 66.56 | 0.00 | 0.00 |
| June | 152.95 | 20.33 | 67.08 | 4.56 | 62.53 | 0.00 | 0.00 |
| July | 155.20 | 15.28 | 68.31 | 6.56 | 61.75 | 0.00 | 0.00 |
| August | 179.45 | 23.72 | 85.66 | 21.87 | 63.79 | 0.00 | 0.00 |
| September | 256.63 | 50.33 | 137.12 | 72.04 | 65.07 | 0.00 | 0.00 |
| October | 294.34 | 83.66 | 184.46 | 124.87 | 59.60 | 0.00 | 0.00 |
| November | 315.30 | 137.02 | 223.02 | 170.40 | 52.61 | 0.00 | 0.00 |
| December | 287.54 | 176.10 | 219.07 | 164.36 | 54.71 | 0.00 | 0.00 |
| Annual Sum or Average | 228.23 | 88.52 | 145.23 | 84.04 | 61.20 | 0.00 | 0.00 |
| Minimum of Months | 139.26 | 15.28 | 67.08 | 4.56 | 51.93 | 0.00 | 0.00 |
| Maximum of Months | 315.30 | 176.10 | 223.02 | 170.40 | 68.65 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: T S2 APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 284.19 | 162.97 | 212.47 | 160.54 | 51.93 | 0.00 | 0.00 |
| February | 276.82 | 144.99 | 202.34 | 143.70 | 58.64 | 0.00 | 0.00 |
| March | 222.14 | 127.68 | 157.89 | 89.51 | 68.38 | 0.00 | 0.00 |
| April | 178.76 | 78.22 | 112.04 | 43.39 | 68.65 | 0.00 | 0.00 |
| May | 139.18 | 44.92 | 77.50 | 10.94 | 66.56 | 0.00 | 0.00 |
| June | 152.91 | 20.31 | 67.08 | 4.56 | 62.53 | 0.00 | 0.00 |
| July | 155.18 | 15.27 | 68.31 | 6.56 | 61.75 | 0.00 | 0.00 |
| August | 179.42 | 23.71 | 85.66 | 21.87 | 63.79 | 0.00 | 0.00 |
| September | 256.58 | 50.29 | 137.12 | 72.04 | 65.07 | 0.00 | 0.00 |
| October | 294.30 | 83.56 | 184.46 | 124.87 | 59.60 | 0.00 | 0.00 |
| November | 315.21 | 136.93 | 223.02 | 170.40 | 52.61 | 0.00 | 0.00 |
| December | 287.45 | 176.02 | 219.07 | 164.36 | 54.71 | 0.00 | 0.00 |
| Annual Sum or Average | 228.14 | 88.47 | 145.23 | 84.04 | 61.20 | 0.00 | 0.00 |
| Minimum of Months | 139.18 | 15.27 | 67.08 | 4.56 | 51.93 | 0.00 | 0.00 |
| Maximum of Months | 315.21 | 176.02 | 223.02 | 170.40 | 68.65 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: T CORRIDOR
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 12.55 | 27.67 | 13.28 | 7.23 | 6.05 | 0.00 | 0.00 |
| February | 19.80 | 24.26 | 17.66 | 10.04 | 7.61 | 0.00 | 0.00 |
| March | 26.92 | 20.55 | 21.80 | 11.98 | 9.82 | 0.00 | 0.00 |
| April | 38.17 | 12.62 | 26.33 | 14.63 | 11.70 | 0.00 | 0.00 |
| May | 43.92 | 7.87 | 27.14 | 14.75 | 12.40 | 0.00 | 0.00 |
| June | 49.43 | 4.13 | 27.19 | 15.13 | 12.06 | 0.00 | 0.00 |
| July | 44.44 | 3.46 | 24.41 | 12.78 | 11.63 | 0.00 | 0.00 |
| August | 40.50 | 4.79 | 23.19 | 11.86 | 11.33 | 0.00 | 0.00 |
| September | 37.69 | 9.00 | 22.98 | 13.11 | 9.87 | 0.00 | 0.00 |
| October | 24.46 | 14.67 | 17.64 | 9.51 | 8.13 | 0.00 | 0.00 |
| November | 17.39 | 23.37 | 15.83 | 9.21 | 6.62 | 0.00 | 0.00 |
| December | 11.80 | 30.17 | 13.20 | 6.99 | 6.21 | 0.00 | 0.00 |
| Annual Sum or Average | 30.62 | 15.17 | 20.89 | 11.43 | 9.46 | 0.00 | 0.00 |
| Minimum of Months | 11.80 | 3.46 | 13.20 | 6.99 | 6.05 | 0.00 | 0.00 |
| Maximum of Months | 49.43 | 30.17 | 27.19 | 15.13 | 12.40 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: G CORRIDOR
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 38.59 | 79.84 | 39.54 | 21.52 | 18.02 | 0.00 | 0.00 |
| February | 60.96 | 69.35 | 52.58 | 29.91 | 22.68 | 0.00 | 0.00 |
| March | 82.90 | 57.67 | 64.92 | 35.68 | 29.24 | 0.00 | 0.00 |
| April | 114.87 | 37.42 | 78.42 | 43.56 | 34.86 | 0.00 | 0.00 |
| May | 130.24 | 24.88 | 80.84 | 43.91 | 36.93 | 0.00 | 0.00 |
| June | 145.16 | 14.00 | 80.97 | 45.06 | 35.91 | 0.00 | 0.00 |
| July | 130.24 | 12.02 | 72.71 | 38.07 | 34.63 | 0.00 | 0.00 |
| August | 118.49 | 16.51 | 69.06 | 35.32 | 33.74 | 0.00 | 0.00 |
| September | 110.27 | 29.75 | 68.43 | 39.03 | 29.40 | 0.00 | 0.00 |
| October | 70.65 | 47.76 | 52.55 | 28.33 | 24.22 | 0.00 | 0.00 |
| November | 50.54 | 74.37 | 47.16 | 27.44 | 19.72 | 0.00 | 0.00 |
| December | 35.79 | 88.81 | 39.31 | 20.81 | 18.50 | 0.00 | 0.00 |
| Annual Sum or Average | 90.81 | 45.92 | 62.22 | 34.04 | 28.18 | 0.00 | 0.00 |
| Minimum of Months | 35.79 | 12.02 | 39.31 | 20.81 | 18.02 | 0.00 | 0.00 |
| Maximum of Months | 145.16 | 88.81 | 80.97 | 45.06 | 36.93 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: M CORRIDOR
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 11.57 | 30.86 | 13.28 | 7.23 | 6.05 | 0.00 | 0.00 |
| February | 18.52 | 27.24 | 17.66 | 10.04 | 7.61 | 0.00 | 0.00 |
| March | 25.25 | 23.10 | 21.80 | 11.98 | 9.82 | 0.00 | 0.00 |
| April | 37.07 | 13.87 | 26.33 | 14.63 | 11.70 | 0.00 | 0.00 |
| May | 43.70 | 8.34 | 27.14 | 14.75 | 12.40 | 0.00 | 0.00 |
| June | 49.99 | 4.24 | 27.19 | 15.13 | 12.06 | 0.00 | 0.00 |
| July | 45.13 | 3.47 | 24.41 | 12.78 | 11.63 | 0.00 | 0.00 |
| August | 40.94 | 4.90 | 23.19 | 11.86 | 11.33 | 0.00 | 0.00 |
| September | 37.60 | 9.39 | 22.98 | 13.11 | 9.87 | 0.00 | 0.00 |
| October | 23.39 | 16.41 | 17.64 | 9.51 | 8.13 | 0.00 | 0.00 |
| November | 16.03 | 26.79 | 15.83 | 9.21 | 6.62 | 0.00 | 0.00 |
| December | 10.83 | 33.66 | 13.20 | 6.99 | 6.21 | 0.00 | 0.00 |
| Annual Sum or Average | 30.04 | 16.81 | 20.89 | 11.43 | 9.46 | 0.00 | 0.00 |
| Minimum of Months | 10.83 | 3.47 | 13.20 | 6.99 | 6.05 | 0.00 | 0.00 |
| Maximum of Months | 49.99 | 33.66 | 27.19 | 15.13 | 12.40 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: G SW APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.918323E+09 | 0.734798E+09 | 0.724716E+09 | 0.517732E+09 | 0.206984E+09 | 0.00 | 0.00 |
| February | 0.856349E+09 | 0.577530E+09 | 0.647702E+09 | 0.431573E+09 | 0.216129E+09 | 0.00 | 0.00 |
| March | 0.930112E+09 | 0.543305E+09 | 0.661851E+09 | 0.367806E+09 | 0.294044E+09 | 0.00 | 0.00 |
| April | 0.886848E+09 | 0.330270E+09 | 0.555886E+09 | 0.255647E+09 | 0.300239E+09 | 0.00 | 0.00 |
| May | 0.894588E+09 | 0.202492E+09 | 0.503047E+09 | 0.187189E+09 | 0.315858E+09 | 0.00 | 0.00 |
| June | 0.954180E+09 | 90358562.86 | 0.452905E+09 | 0.161771E+09 | 0.291133E+09 | 0.00 | 0.00 |
| July | 0.928029E+09 | 71911221.13 | 0.439035E+09 | 0.144952E+09 | 0.294083E+09 | 0.00 | 0.00 |
| August | 0.949975E+09 | 0.113987E+09 | 0.476851E+09 | 0.184509E+09 | 0.292342E+09 | 0.00 | 0.00 |
| September | 0.109949E+10 | 0.235745E+09 | 0.600946E+09 | 0.323712E+09 | 0.277234E+09 | 0.00 | 0.00 |
| October | 0.110621E+10 | 0.411285E+09 | 0.711969E+09 | 0.461570E+09 | 0.250399E+09 | 0.00 | 0.00 |
| November | 0.999906E+09 | 0.652881E+09 | 0.753901E+09 | 0.548308E+09 | 0.205594E+09 | 0.00 | 0.00 |
| December | 0.895960E+09 | 0.807379E+09 | 0.734186E+09 | 0.520296E+09 | 0.213890E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.114200E+11 | 0.477194E+10 | 0.726300E+10 | 0.410507E+10 | 0.315793E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.856349E+09 | 71911221.13 | 0.439035E+09 | 0.144952E+09 | 0.205594E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.110621E+10 | 0.807379E+09 | 0.753901E+09 | 0.548308E+09 | 0.315858E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: G NW APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.179454E+09 | 0.757727E+09 | 0.239512E+09 | 87728367.98 | 0.151784E+09 | 0.00 | 0.00 |
| February | 0.235042E+09 | 0.591180E+09 | 0.250719E+09 | 83935057.27 | 0.166784E+09 | 0.00 | 0.00 |
| March | 0.435365E+09 | 0.535522E+09 | 0.373039E+09 | 0.128069E+09 | 0.244969E+09 | 0.00 | 0.00 |
| April | 0.602448E+09 | 0.314088E+09 | 0.415773E+09 | 0.144815E+09 | 0.270958E+09 | 0.00 | 0.00 |
| May | 0.822727E+09 | 0.191027E+09 | 0.479303E+09 | 0.171427E+09 | 0.307876E+09 | 0.00 | 0.00 |
| June | 0.971884E+09 | 87498314.21 | 0.467522E+09 | 0.172822E+09 | 0.294701E+09 | 0.00 | 0.00 |
| July | 0.908584E+09 | 69393512.77 | 0.435718E+09 | 0.144137E+09 | 0.291581E+09 | 0.00 | 0.00 |
| August | 0.777262E+09 | 0.109049E+09 | 0.400471E+09 | 0.129872E+09 | 0.270599E+09 | 0.00 | 0.00 |
| September | 0.654320E+09 | 0.233082E+09 | 0.374122E+09 | 0.137100E+09 | 0.237022E+09 | 0.00 | 0.00 |
| October | 0.436388E+09 | 0.417991E+09 | 0.328099E+09 | 0.127131E+09 | 0.200968E+09 | 0.00 | 0.00 |
| November | 0.232057E+09 | 0.664079E+09 | 0.261938E+09 | 0.106629E+09 | 0.155309E+09 | 0.00 | 0.00 |
| December | 0.146014E+09 | 0.853861E+09 | 0.230662E+09 | 80086886.16 | 0.150575E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.640154E+10 | 0.482450E+10 | 0.425688E+10 | 0.151375E+10 | 0.274313E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.146014E+09 | 69393512.77 | 0.230662E+09 | 80086886.16 | 0.150575E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.971884E+09 | 0.853861E+09 | 0.479303E+09 | 0.172822E+09 | 0.307876E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: OFFICE
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.897788E+09 | 0.741540E+09 | 0.717267E+09 | 0.510656E+09 | 0.206611E+09 | 0.00 | 0.00 |
| February | 0.870911E+09 | 0.590872E+09 | 0.667501E+09 | 0.448881E+09 | 0.218620E+09 | 0.00 | 0.00 |
| March | 0.899831E+09 | 0.552248E+09 | 0.666197E+09 | 0.373467E+09 | 0.292730E+09 | 0.00 | 0.00 |
| April | 0.855959E+09 | 0.356697E+09 | 0.574815E+09 | 0.270443E+09 | 0.304372E+09 | 0.00 | 0.00 |
| May | 0.828555E+09 | 0.256867E+09 | 0.510584E+09 | 0.193896E+09 | 0.316688E+09 | 0.00 | 0.00 |
| June | 0.877589E+09 | 0.155560E+09 | 0.467566E+09 | 0.175252E+09 | 0.292313E+09 | 0.00 | 0.00 |
| July | 0.844200E+09 | 0.147635E+09 | 0.455464E+09 | 0.160263E+09 | 0.295201E+09 | 0.00 | 0.00 |
| August | 0.875306E+09 | 0.196415E+09 | 0.488279E+09 | 0.190975E+09 | 0.297304E+09 | 0.00 | 0.00 |
| September | 0.101772E+10 | 0.320857E+09 | 0.603604E+09 | 0.328305E+09 | 0.275300E+09 | 0.00 | 0.00 |
| October | 0.102081E+10 | 0.486674E+09 | 0.691021E+09 | 0.440607E+09 | 0.250414E+09 | 0.00 | 0.00 |
| November | 0.965545E+09 | 0.684599E+09 | 0.749105E+09 | 0.541199E+09 | 0.207906E+09 | 0.00 | 0.00 |
| December | 0.879858E+09 | 0.820119E+09 | 0.734100E+09 | 0.518218E+09 | 0.215882E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.108341E+11 | 0.531008E+10 | 0.732550E+10 | 0.415216E+10 | 0.317334E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.828555E+09 | 0.147635E+09 | 0.455464E+09 | 0.160263E+09 | 0.206611E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.102081E+10 | 0.820119E+09 | 0.749105E+09 | 0.541199E+09 | 0.316688E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: G NE APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.131277E+09 | 0.720923E+09 | 0.232063E+09 | 80652622.40 | 0.151410E+09 | 0.00 | 0.00 |
| February | 0.226658E+09 | 0.550753E+09 | 0.270518E+09 | 0.101243E+09 | 0.169275E+09 | 0.00 | 0.00 |
| March | 0.406642E+09 | 0.498947E+09 | 0.377385E+09 | 0.133730E+09 | 0.243655E+09 | 0.00 | 0.00 |
| April | 0.606235E+09 | 0.292524E+09 | 0.434702E+09 | 0.159611E+09 | 0.275091E+09 | 0.00 | 0.00 |
| May | 0.825883E+09 | 0.184433E+09 | 0.486839E+09 | 0.178134E+09 | 0.308705E+09 | 0.00 | 0.00 |
| June | 0.992261E+09 | 85150212.43 | 0.482183E+09 | 0.186303E+09 | 0.295880E+09 | 0.00 | 0.00 |
| July | 0.933999E+09 | 68149237.96 | 0.452147E+09 | 0.159448E+09 | 0.292699E+09 | 0.00 | 0.00 |
| August | 0.791138E+09 | 0.104813E+09 | 0.411899E+09 | 0.136337E+09 | 0.275561E+09 | 0.00 | 0.00 |
| September | 0.636368E+09 | 0.213933E+09 | 0.376780E+09 | 0.141693E+09 | 0.235088E+09 | 0.00 | 0.00 |
| October | 0.375142E+09 | 0.397143E+09 | 0.307151E+09 | 0.106167E+09 | 0.200984E+09 | 0.00 | 0.00 |
| November | 0.182323E+09 | 0.626316E+09 | 0.257141E+09 | 99520035.89 | 0.157621E+09 | 0.00 | 0.00 |
| December | 0.102714E+09 | 0.814309E+09 | 0.230576E+09 | 78008575.33 | 0.152567E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.621064E+10 | 0.455739E+10 | 0.431939E+10 | 0.156085E+10 | 0.275854E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.102714E+09 | 68149237.96 | 0.230576E+09 | 78008575.33 | 0.151410E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.992261E+09 | 0.814309E+09 | 0.486839E+09 | 0.186303E+09 | 0.308705E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: G N1 APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 17235702.13 | 0.484687E+09 | 83878188.20 | 0.00 | 83878188.20 | 0.00 | 0.00 |
| February | 46461433.50 | 0.376193E+09 | 92512121.34 | 0.00 | 92512121.34 | 0.00 | 0.00 |
| March | 0.108467E+09 | 0.338708E+09 | 0.134083E+09 | 15028.79 | 0.134068E+09 | 0.00 | 0.00 |
| April | 0.184664E+09 | 0.196596E+09 | 0.150287E+09 | 1624148.27 | 0.148663E+09 | 0.00 | 0.00 |
| May | 0.312943E+09 | 0.114360E+09 | 0.183844E+09 | 13547143.77 | 0.170297E+09 | 0.00 | 0.00 |
| June | 0.427714E+09 | 51683319.43 | 0.188495E+09 | 22859994.57 | 0.165635E+09 | 0.00 | 0.00 |
| July | 0.407922E+09 | 40448507.71 | 0.179655E+09 | 16759739.40 | 0.162895E+09 | 0.00 | 0.00 |
| August | 0.316177E+09 | 63565553.51 | 0.153063E+09 | 3945204.69 | 0.149118E+09 | 0.00 | 0.00 |
| September | 0.224348E+09 | 0.138328E+09 | 0.128581E+09 | 121021.29 | 0.128460E+09 | 0.00 | 0.00 |
| October | 0.111339E+09 | 0.257753E+09 | 0.110198E+09 | 0.00 | 0.110198E+09 | 0.00 | 0.00 |
| November | 25045761.48 | 0.427371E+09 | 86092241.07 | 0.00 | 86092241.07 | 0.00 | 0.00 |
| December | 10461014.55 | 0.549630E+09 | 83228616.05 | 0.00 | 83228616.05 | 0.00 | 0.00 |
| Annual Sum or Average | 0.219278E+10 | 0.303932E+10 | 0.157392E+10 | 58872280.77 | 0.151504E+10 | 0.00 | 0.00 |
| Minimum of Months | 10461014.55 | 40448507.71 | 83228616.05 | 0.00 | 83228616.05 | 0.00 | 0.00 |
| Maximum of Months | 0.427714E+09 | 0.549630E+09 | 0.188495E+09 | 22859994.57 | 0.170297E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: G N2 APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 17231306.87 | 0.484556E+09 | 83878188.20 | 0.00 | 83878188.20 | 0.00 | 0.00 |
| February | 46399559.76 | 0.376213E+09 | 92512121.34 | 0.00 | 92512121.34 | 0.00 | 0.00 |
| March | 0.108369E+09 | 0.338681E+09 | 0.134083E+09 | 15028.79 | 0.134068E+09 | 0.00 | 0.00 |
| April | 0.184433E+09 | 0.196722E+09 | 0.150287E+09 | 1624148.27 | 0.148663E+09 | 0.00 | 0.00 |
| May | 0.312844E+09 | 0.114367E+09 | 0.183844E+09 | 13547143.77 | 0.170297E+09 | 0.00 | 0.00 |
| June | 0.427663E+09 | 51674627.25 | 0.188495E+09 | 22859994.57 | 0.165635E+09 | 0.00 | 0.00 |
| July | 0.407886E+09 | 40435776.23 | 0.179655E+09 | 16759739.40 | 0.162895E+09 | 0.00 | 0.00 |
| August | 0.316138E+09 | 63553646.10 | 0.153063E+09 | 3945204.69 | 0.149118E+09 | 0.00 | 0.00 |
| September | 0.224309E+09 | 0.138303E+09 | 0.128581E+09 | 121021.29 | 0.128460E+09 | 0.00 | 0.00 |
| October | 0.111320E+09 | 0.257667E+09 | 0.110198E+09 | 0.00 | 0.110198E+09 | 0.00 | 0.00 |
| November | 25014372.06 | 0.427216E+09 | 86092241.07 | 0.00 | 86092241.07 | 0.00 | 0.00 |
| December | 10439148.50 | 0.549602E+09 | 83228616.05 | 0.00 | 83228616.05 | 0.00 | 0.00 |
| Annual Sum or Average | 0.219205E+10 | 0.303899E+10 | 0.157392E+10 | 58872280.77 | 0.151504E+10 | 0.00 | 0.00 |
| Minimum of Months | 10439148.50 | 40435776.23 | 83228616.05 | 0.00 | 83228616.05 | 0.00 | 0.00 |
| Maximum of Months | 0.427663E+09 | 0.549602E+09 | 0.188495E+09 | 22859994.57 | 0.170297E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: G S1 APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.768773E+09 | 0.458056E+09 | 0.569082E+09 | 0.430004E+09 | 0.139079E+09 | 0.00 | 0.00 |
| February | 0.680778E+09 | 0.361624E+09 | 0.489495E+09 | 0.347638E+09 | 0.141858E+09 | 0.00 | 0.00 |
| March | 0.611989E+09 | 0.343885E+09 | 0.422895E+09 | 0.239752E+09 | 0.183143E+09 | 0.00 | 0.00 |
| April | 0.475441E+09 | 0.209847E+09 | 0.290400E+09 | 0.112456E+09 | 0.177944E+09 | 0.00 | 0.00 |
| May | 0.384259E+09 | 0.123994E+09 | 0.207588E+09 | 29308895.00 | 0.178279E+09 | 0.00 | 0.00 |
| June | 0.408501E+09 | 53643223.04 | 0.173878E+09 | 11809415.54 | 0.162068E+09 | 0.00 | 0.00 |
| July | 0.426722E+09 | 42440073.54 | 0.182972E+09 | 17574380.96 | 0.165397E+09 | 0.00 | 0.00 |
| August | 0.489642E+09 | 67371775.00 | 0.229443E+09 | 58582872.53 | 0.170860E+09 | 0.00 | 0.00 |
| September | 0.673521E+09 | 0.139603E+09 | 0.355405E+09 | 0.186733E+09 | 0.168672E+09 | 0.00 | 0.00 |
| October | 0.789314E+09 | 0.247191E+09 | 0.494068E+09 | 0.334439E+09 | 0.159628E+09 | 0.00 | 0.00 |
| November | 0.809772E+09 | 0.399649E+09 | 0.578056E+09 | 0.441679E+09 | 0.136377E+09 | 0.00 | 0.00 |
| December | 0.772162E+09 | 0.500518E+09 | 0.586752E+09 | 0.440209E+09 | 0.146543E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.729088E+10 | 0.294782E+10 | 0.458003E+10 | 0.265019E+10 | 0.192985E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.384259E+09 | 42440073.54 | 0.173878E+09 | 11809415.54 | 0.136377E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.809772E+09 | 0.500518E+09 | 0.586752E+09 | 0.441679E+09 | 0.183143E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: G S2 APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.768344E+09 | 0.458674E+09 | 0.569082E+09 | 0.430004E+09 | 0.139079E+09 | 0.00 | 0.00 |
| February | 0.679815E+09 | 0.363041E+09 | 0.489495E+09 | 0.347638E+09 | 0.141858E+09 | 0.00 | 0.00 |
| March | 0.610359E+09 | 0.345969E+09 | 0.422895E+09 | 0.239752E+09 | 0.183143E+09 | 0.00 | 0.00 |
| April | 0.473668E+09 | 0.212090E+09 | 0.290400E+09 | 0.112456E+09 | 0.177944E+09 | 0.00 | 0.00 |
| May | 0.382197E+09 | 0.125867E+09 | 0.207588E+09 | 29308895.00 | 0.178279E+09 | 0.00 | 0.00 |
| June | 0.405620E+09 | 55213252.58 | 0.173878E+09 | 11809415.54 | 0.162068E+09 | 0.00 | 0.00 |
| July | 0.423669E+09 | 44147841.68 | 0.182972E+09 | 17574380.96 | 0.165397E+09 | 0.00 | 0.00 |
| August | 0.487025E+09 | 69278483.66 | 0.229443E+09 | 58582872.53 | 0.170860E+09 | 0.00 | 0.00 |
| September | 0.671685E+09 | 0.141868E+09 | 0.355405E+09 | 0.186733E+09 | 0.168672E+09 | 0.00 | 0.00 |
| October | 0.788065E+09 | 0.248881E+09 | 0.494068E+09 | 0.334439E+09 | 0.159628E+09 | 0.00 | 0.00 |
| November | 0.808978E+09 | 0.400946E+09 | 0.578056E+09 | 0.441679E+09 | 0.136377E+09 | 0.00 | 0.00 |
| December | 0.771144E+09 | 0.502126E+09 | 0.586752E+09 | 0.440209E+09 | 0.146543E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.727057E+10 | 0.296810E+10 | 0.458003E+10 | 0.265019E+10 | 0.192985E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.382197E+09 | 44147841.68 | 0.173878E+09 | 11809415.54 | 0.136377E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.808978E+09 | 0.502126E+09 | 0.586752E+09 | 0.441679E+09 | 0.183143E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: M SW APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.895130E+09 | 0.767927E+09 | 0.724716E+09 | 0.517732E+09 | 0.206984E+09 | 0.00 | 0.00 |
| February | 0.824473E+09 | 0.624931E+09 | 0.647702E+09 | 0.431573E+09 | 0.216129E+09 | 0.00 | 0.00 |
| March | 0.879264E+09 | 0.610283E+09 | 0.661851E+09 | 0.367806E+09 | 0.294044E+09 | 0.00 | 0.00 |
| April | 0.859357E+09 | 0.359959E+09 | 0.555886E+09 | 0.255647E+09 | 0.300239E+09 | 0.00 | 0.00 |
| May | 0.880974E+09 | 0.212097E+09 | 0.503047E+09 | 0.187189E+09 | 0.315858E+09 | 0.00 | 0.00 |
| June | 0.948512E+09 | 92661386.62 | 0.452905E+09 | 0.161771E+09 | 0.291133E+09 | 0.00 | 0.00 |
| July | 0.927863E+09 | 70836629.70 | 0.439035E+09 | 0.144952E+09 | 0.294083E+09 | 0.00 | 0.00 |
| August | 0.952943E+09 | 0.110042E+09 | 0.476851E+09 | 0.184509E+09 | 0.292342E+09 | 0.00 | 0.00 |
| September | 0.110123E+10 | 0.228384E+09 | 0.600946E+09 | 0.323712E+09 | 0.277234E+09 | 0.00 | 0.00 |
| October | 0.110467E+10 | 0.405082E+09 | 0.711969E+09 | 0.461570E+09 | 0.250399E+09 | 0.00 | 0.00 |
| November | 0.997194E+09 | 0.646186E+09 | 0.753901E+09 | 0.548308E+09 | 0.205594E+09 | 0.00 | 0.00 |
| December | 0.880787E+09 | 0.825368E+09 | 0.734186E+09 | 0.520296E+09 | 0.213890E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.112524E+11 | 0.495376E+10 | 0.726300E+10 | 0.410507E+10 | 0.315793E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.824473E+09 | 70836629.70 | 0.439035E+09 | 0.144952E+09 | 0.205594E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.110467E+10 | 0.825368E+09 | 0.753901E+09 | 0.548308E+09 | 0.315858E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: M NW APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.170014E+09 | 0.786607E+09 | 0.239512E+09 | 87728367.98 | 0.151784E+09 | 0.00 | 0.00 |
| February | 0.215596E+09 | 0.636672E+09 | 0.250719E+09 | 83935057.27 | 0.166784E+09 | 0.00 | 0.00 |
| March | 0.392536E+09 | 0.605818E+09 | 0.373039E+09 | 0.128069E+09 | 0.244969E+09 | 0.00 | 0.00 |
| April | 0.572398E+09 | 0.351457E+09 | 0.415773E+09 | 0.144815E+09 | 0.270958E+09 | 0.00 | 0.00 |
| May | 0.808422E+09 | 0.200957E+09 | 0.479303E+09 | 0.171427E+09 | 0.307876E+09 | 0.00 | 0.00 |
| June | 0.965868E+09 | 89600488.53 | 0.467522E+09 | 0.172822E+09 | 0.294701E+09 | 0.00 | 0.00 |
| July | 0.908538E+09 | 68304123.22 | 0.435718E+09 | 0.144137E+09 | 0.291581E+09 | 0.00 | 0.00 |
| August | 0.781067E+09 | 0.105590E+09 | 0.400471E+09 | 0.129872E+09 | 0.270599E+09 | 0.00 | 0.00 |
| September | 0.657837E+09 | 0.226940E+09 | 0.374122E+09 | 0.137100E+09 | 0.237022E+09 | 0.00 | 0.00 |
| October | 0.438218E+09 | 0.412419E+09 | 0.328099E+09 | 0.127131E+09 | 0.200968E+09 | 0.00 | 0.00 |
| November | 0.233356E+09 | 0.659743E+09 | 0.261938E+09 | 0.106629E+09 | 0.155309E+09 | 0.00 | 0.00 |
| December | 0.141732E+09 | 0.869297E+09 | 0.230662E+09 | 80086886.16 | 0.150575E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.628558E+10 | 0.501340E+10 | 0.425688E+10 | 0.151375E+10 | 0.274313E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.141732E+09 | 68304123.22 | 0.230662E+09 | 80086886.16 | 0.150575E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.965868E+09 | 0.869297E+09 | 0.479303E+09 | 0.172822E+09 | 0.307876E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: M SE APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.876303E+09 | 0.762008E+09 | 0.717267E+09 | 0.510656E+09 | 0.206611E+09 | 0.00 | 0.00 |
| February | 0.845580E+09 | 0.618084E+09 | 0.667501E+09 | 0.448881E+09 | 0.218620E+09 | 0.00 | 0.00 |
| March | 0.862517E+09 | 0.588272E+09 | 0.666197E+09 | 0.373467E+09 | 0.292730E+09 | 0.00 | 0.00 |
| April | 0.859526E+09 | 0.332636E+09 | 0.574815E+09 | 0.270443E+09 | 0.304372E+09 | 0.00 | 0.00 |
| May | 0.874893E+09 | 0.194882E+09 | 0.510584E+09 | 0.193896E+09 | 0.316688E+09 | 0.00 | 0.00 |
| June | 0.964858E+09 | 86133493.40 | 0.467566E+09 | 0.175252E+09 | 0.292313E+09 | 0.00 | 0.00 |
| July | 0.950861E+09 | 67063239.96 | 0.455464E+09 | 0.160263E+09 | 0.295201E+09 | 0.00 | 0.00 |
| August | 0.963935E+09 | 0.102791E+09 | 0.488279E+09 | 0.190975E+09 | 0.297304E+09 | 0.00 | 0.00 |
| September | 0.108599E+10 | 0.211863E+09 | 0.603604E+09 | 0.328305E+09 | 0.275300E+09 | 0.00 | 0.00 |
| October | 0.105639E+10 | 0.397530E+09 | 0.691021E+09 | 0.440607E+09 | 0.250414E+09 | 0.00 | 0.00 |
| November | 0.975509E+09 | 0.638775E+09 | 0.749105E+09 | 0.541199E+09 | 0.207906E+09 | 0.00 | 0.00 |
| December | 0.869671E+09 | 0.820726E+09 | 0.734100E+09 | 0.518218E+09 | 0.215882E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.111860E+11 | 0.482076E+10 | 0.732550E+10 | 0.415216E+10 | 0.317334E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.845580E+09 | 67063239.96 | 0.455464E+09 | 0.160263E+09 | 0.206611E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.108599E+10 | 0.820726E+09 | 0.749105E+09 | 0.541199E+09 | 0.316688E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: M NE APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.121333E+09 | 0.748250E+09 | 0.232063E+09 | 80652622.40 | 0.151410E+09 | 0.00 | 0.00 |
| February | 0.204226E+09 | 0.594630E+09 | 0.270518E+09 | 0.101243E+09 | 0.169275E+09 | 0.00 | 0.00 |
| March | 0.358947E+09 | 0.567764E+09 | 0.377385E+09 | 0.133730E+09 | 0.243655E+09 | 0.00 | 0.00 |
| April | 0.572752E+09 | 0.325170E+09 | 0.434702E+09 | 0.159611E+09 | 0.275091E+09 | 0.00 | 0.00 |
| May | 0.811572E+09 | 0.193032E+09 | 0.486839E+09 | 0.178134E+09 | 0.308705E+09 | 0.00 | 0.00 |
| June | 0.986110E+09 | 86947721.66 | 0.482183E+09 | 0.186303E+09 | 0.295880E+09 | 0.00 | 0.00 |
| July | 0.933926E+09 | 66925518.97 | 0.452147E+09 | 0.159448E+09 | 0.292699E+09 | 0.00 | 0.00 |
| August | 0.795005E+09 | 0.101305E+09 | 0.411899E+09 | 0.136337E+09 | 0.275561E+09 | 0.00 | 0.00 |
| September | 0.640224E+09 | 0.208099E+09 | 0.376780E+09 | 0.141693E+09 | 0.235088E+09 | 0.00 | 0.00 |
| October | 0.376634E+09 | 0.391793E+09 | 0.307151E+09 | 0.106167E+09 | 0.200984E+09 | 0.00 | 0.00 |
| November | 0.183083E+09 | 0.621557E+09 | 0.257141E+09 | 99520035.89 | 0.157621E+09 | 0.00 | 0.00 |
| December | 97948810.64 | 0.829515E+09 | 0.230576E+09 | 78008575.33 | 0.152567E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.608176E+10 | 0.473499E+10 | 0.431939E+10 | 0.156085E+10 | 0.275854E+10 | 0.00 | 0.00 |
| Minimum of Months | 97948810.64 | 66925518.97 | 0.230576E+09 | 78008575.33 | 0.151410E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.986110E+09 | 0.829515E+09 | 0.486839E+09 | 0.186303E+09 | 0.308705E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: M N1 APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 14226017.96 | 0.504552E+09 | 83878188.20 | 0.00 | 83878188.20 | 0.00 | 0.00 |
| February | 37585032.21 | 0.407859E+09 | 92512121.34 | 0.00 | 92512121.34 | 0.00 | 0.00 |
| March | 87012844.80 | 0.387709E+09 | 0.134083E+09 | 15028.79 | 0.134068E+09 | 0.00 | 0.00 |
| April | 0.171380E+09 | 0.215550E+09 | 0.150287E+09 | 1624148.27 | 0.148663E+09 | 0.00 | 0.00 |
| May | 0.307825E+09 | 0.117890E+09 | 0.183844E+09 | 13547143.77 | 0.170297E+09 | 0.00 | 0.00 |
| June | 0.426460E+09 | 52128013.57 | 0.188495E+09 | 22859994.57 | 0.165635E+09 | 0.00 | 0.00 |
| July | 0.409031E+09 | 39620286.05 | 0.179655E+09 | 16759739.40 | 0.162895E+09 | 0.00 | 0.00 |
| August | 0.319037E+09 | 61780020.97 | 0.153063E+09 | 3945204.69 | 0.149118E+09 | 0.00 | 0.00 |
| September | 0.226630E+09 | 0.135637E+09 | 0.128581E+09 | 121021.29 | 0.128460E+09 | 0.00 | 0.00 |
| October | 0.112006E+09 | 0.256807E+09 | 0.110198E+09 | 0.00 | 0.110198E+09 | 0.00 | 0.00 |
| November | 25272416.19 | 0.427755E+09 | 86092241.07 | 0.00 | 86092241.07 | 0.00 | 0.00 |
| December | 9375773.46 | 0.562057E+09 | 83228616.05 | 0.00 | 83228616.05 | 0.00 | 0.00 |
| Annual Sum or Average | 0.214584E+10 | 0.316934E+10 | 0.157392E+10 | 58872280.77 | 0.151504E+10 | 0.00 | 0.00 |
| Minimum of Months | 9375773.46 | 39620286.05 | 83228616.05 | 0.00 | 83228616.05 | 0.00 | 0.00 |
| Maximum of Months | 0.426460E+09 | 0.562057E+09 | 0.188495E+09 | 22859994.57 | 0.170297E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: M N2 APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 14214148.00 | 0.504347E+09 | 83878188.20 | 0.00 | 83878188.20 | 0.00 | 0.00 |
| February | 37469505.57 | 0.407954E+09 | 92512121.34 | 0.00 | 92512121.34 | 0.00 | 0.00 |
| March | 86790229.81 | 0.387826E+09 | 0.134083E+09 | 15028.79 | 0.134068E+09 | 0.00 | 0.00 |
| April | 0.171225E+09 | 0.215590E+09 | 0.150287E+09 | 1624148.27 | 0.148663E+09 | 0.00 | 0.00 |
| May | 0.307759E+09 | 0.117867E+09 | 0.183844E+09 | 13547143.77 | 0.170297E+09 | 0.00 | 0.00 |
| June | 0.426417E+09 | 52112107.48 | 0.188495E+09 | 22859994.57 | 0.165635E+09 | 0.00 | 0.00 |
| July | 0.408998E+09 | 39604692.19 | 0.179655E+09 | 16759739.40 | 0.162895E+09 | 0.00 | 0.00 |
| August | 0.319000E+09 | 61764315.49 | 0.153063E+09 | 3945204.69 | 0.149118E+09 | 0.00 | 0.00 |
| September | 0.226586E+09 | 0.135607E+09 | 0.128581E+09 | 121021.29 | 0.128460E+09 | 0.00 | 0.00 |
| October | 0.111969E+09 | 0.256714E+09 | 0.110198E+09 | 0.00 | 0.110198E+09 | 0.00 | 0.00 |
| November | 25222244.98 | 0.427549E+09 | 86092241.07 | 0.00 | 86092241.07 | 0.00 | 0.00 |
| December | 9346084.03 | 0.562019E+09 | 83228616.05 | 0.00 | 83228616.05 | 0.00 | 0.00 |
| Annual Sum or Average | 0.214500E+10 | 0.316895E+10 | 0.157392E+10 | 58872280.77 | 0.151504E+10 | 0.00 | 0.00 |
| Minimum of Months | 9346084.03 | 39604692.19 | 83228616.05 | 0.00 | 83228616.05 | 0.00 | 0.00 |
| Maximum of Months | 0.426417E+09 | 0.562019E+09 | 0.188495E+09 | 22859994.57 | 0.170297E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: M S1 APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.753189E+09 | 0.480667E+09 | 0.569082E+09 | 0.430004E+09 | 0.139079E+09 | 0.00 | 0.00 |
| February | 0.661286E+09 | 0.390926E+09 | 0.489495E+09 | 0.347638E+09 | 0.141858E+09 | 0.00 | 0.00 |
| March | 0.584855E+09 | 0.381962E+09 | 0.422895E+09 | 0.239752E+09 | 0.183143E+09 | 0.00 | 0.00 |
| April | 0.463531E+09 | 0.222813E+09 | 0.290400E+09 | 0.112456E+09 | 0.177944E+09 | 0.00 | 0.00 |
| May | 0.379594E+09 | 0.127392E+09 | 0.207588E+09 | 29308895.00 | 0.178279E+09 | 0.00 | 0.00 |
| June | 0.407798E+09 | 54075082.79 | 0.173878E+09 | 11809415.54 | 0.162068E+09 | 0.00 | 0.00 |
| July | 0.427937E+09 | 41531468.16 | 0.182972E+09 | 17574380.96 | 0.165397E+09 | 0.00 | 0.00 |
| August | 0.491717E+09 | 65190270.31 | 0.229443E+09 | 58582872.53 | 0.170860E+09 | 0.00 | 0.00 |
| September | 0.673950E+09 | 0.135923E+09 | 0.355405E+09 | 0.186733E+09 | 0.168672E+09 | 0.00 | 0.00 |
| October | 0.787139E+09 | 0.244975E+09 | 0.494068E+09 | 0.334439E+09 | 0.159628E+09 | 0.00 | 0.00 |
| November | 0.806506E+09 | 0.397511E+09 | 0.578056E+09 | 0.441679E+09 | 0.136377E+09 | 0.00 | 0.00 |
| December | 0.761071E+09 | 0.513615E+09 | 0.586752E+09 | 0.440209E+09 | 0.146543E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.719857E+10 | 0.305658E+10 | 0.458003E+10 | 0.265019E+10 | 0.192985E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.379594E+09 | 41531468.16 | 0.173878E+09 | 11809415.54 | 0.136377E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.806506E+09 | 0.513615E+09 | 0.586752E+09 | 0.441679E+09 | 0.183143E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: M S2 APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.753141E+09 | 0.480551E+09 | 0.569082E+09 | 0.430004E+09 | 0.139079E+09 | 0.00 | 0.00 |
| February | 0.661088E+09 | 0.391057E+09 | 0.489495E+09 | 0.347638E+09 | 0.141858E+09 | 0.00 | 0.00 |
| March | 0.584681E+09 | 0.381975E+09 | 0.422895E+09 | 0.239752E+09 | 0.183143E+09 | 0.00 | 0.00 |
| April | 0.463414E+09 | 0.222817E+09 | 0.290400E+09 | 0.112456E+09 | 0.177944E+09 | 0.00 | 0.00 |
| May | 0.379531E+09 | 0.127369E+09 | 0.207588E+09 | 29308895.00 | 0.178279E+09 | 0.00 | 0.00 |
| June | 0.407755E+09 | 54058975.48 | 0.173878E+09 | 11809415.54 | 0.162068E+09 | 0.00 | 0.00 |
| July | 0.427904E+09 | 41515393.75 | 0.182972E+09 | 17574380.96 | 0.165397E+09 | 0.00 | 0.00 |
| August | 0.491683E+09 | 65174236.31 | 0.229443E+09 | 58582872.53 | 0.170860E+09 | 0.00 | 0.00 |
| September | 0.673912E+09 | 0.135893E+09 | 0.355405E+09 | 0.186733E+09 | 0.168672E+09 | 0.00 | 0.00 |
| October | 0.787125E+09 | 0.244911E+09 | 0.494068E+09 | 0.334439E+09 | 0.159628E+09 | 0.00 | 0.00 |
| November | 0.806465E+09 | 0.397423E+09 | 0.578056E+09 | 0.441679E+09 | 0.136377E+09 | 0.00 | 0.00 |
| December | 0.760970E+09 | 0.513598E+09 | 0.586752E+09 | 0.440209E+09 | 0.146543E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.719767E+10 | 0.305634E+10 | 0.458003E+10 | 0.265019E+10 | 0.192985E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.379531E+09 | 41515393.75 | 0.173878E+09 | 11809415.54 | 0.136377E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.806465E+09 | 0.513598E+09 | 0.586752E+09 | 0.441679E+09 | 0.183143E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: T SW APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.899803E+09 | 0.712014E+09 | 0.724716E+09 | 0.517732E+09 | 0.206984E+09 | 0.00 | 0.00 |
| February | 0.830901E+09 | 0.570712E+09 | 0.647702E+09 | 0.431573E+09 | 0.216129E+09 | 0.00 | 0.00 |
| March | 0.888549E+09 | 0.550297E+09 | 0.661851E+09 | 0.367806E+09 | 0.294044E+09 | 0.00 | 0.00 |
| April | 0.857563E+09 | 0.324347E+09 | 0.555886E+09 | 0.255647E+09 | 0.300239E+09 | 0.00 | 0.00 |
| May | 0.867403E+09 | 0.196871E+09 | 0.503047E+09 | 0.187189E+09 | 0.315858E+09 | 0.00 | 0.00 |
| June | 0.925783E+09 | 88985696.41 | 0.452905E+09 | 0.161771E+09 | 0.291133E+09 | 0.00 | 0.00 |
| July | 0.904033E+09 | 68707658.48 | 0.439035E+09 | 0.144952E+09 | 0.294083E+09 | 0.00 | 0.00 |
| August | 0.931497E+09 | 0.105686E+09 | 0.476851E+09 | 0.184509E+09 | 0.292342E+09 | 0.00 | 0.00 |
| September | 0.108501E+10 | 0.216158E+09 | 0.600946E+09 | 0.323712E+09 | 0.277234E+09 | 0.00 | 0.00 |
| October | 0.110783E+10 | 0.362755E+09 | 0.711969E+09 | 0.461570E+09 | 0.250399E+09 | 0.00 | 0.00 |
| November | 0.101027E+10 | 0.579560E+09 | 0.753901E+09 | 0.548308E+09 | 0.205594E+09 | 0.00 | 0.00 |
| December | 0.886048E+09 | 0.771352E+09 | 0.734186E+09 | 0.520296E+09 | 0.213890E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.111947E+11 | 0.454745E+10 | 0.726300E+10 | 0.410507E+10 | 0.315793E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.830901E+09 | 68707658.48 | 0.439035E+09 | 0.144952E+09 | 0.205594E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.110783E+10 | 0.771352E+09 | 0.753901E+09 | 0.548308E+09 | 0.315858E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: T NW APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.172408E+09 | 0.745920E+09 | 0.239512E+09 | 87728367.98 | 0.151784E+09 | 0.00 | 0.00 |
| February | 0.218792E+09 | 0.596800E+09 | 0.250719E+09 | 83935057.27 | 0.166784E+09 | 0.00 | 0.00 |
| March | 0.399318E+09 | 0.554470E+09 | 0.373039E+09 | 0.128069E+09 | 0.244969E+09 | 0.00 | 0.00 |
| April | 0.574591E+09 | 0.316359E+09 | 0.415773E+09 | 0.144815E+09 | 0.270958E+09 | 0.00 | 0.00 |
| May | 0.797469E+09 | 0.187769E+09 | 0.479303E+09 | 0.171427E+09 | 0.307876E+09 | 0.00 | 0.00 |
| June | 0.943111E+09 | 86600845.36 | 0.467522E+09 | 0.172822E+09 | 0.294701E+09 | 0.00 | 0.00 |
| July | 0.885184E+09 | 66649836.64 | 0.435718E+09 | 0.144137E+09 | 0.291581E+09 | 0.00 | 0.00 |
| August | 0.761764E+09 | 0.101790E+09 | 0.400471E+09 | 0.129872E+09 | 0.270599E+09 | 0.00 | 0.00 |
| September | 0.646759E+09 | 0.214109E+09 | 0.374122E+09 | 0.137100E+09 | 0.237022E+09 | 0.00 | 0.00 |
| October | 0.448752E+09 | 0.360760E+09 | 0.328099E+09 | 0.127131E+09 | 0.200968E+09 | 0.00 | 0.00 |
| November | 0.242314E+09 | 0.601641E+09 | 0.261938E+09 | 0.106629E+09 | 0.155309E+09 | 0.00 | 0.00 |
| December | 0.144898E+09 | 0.824899E+09 | 0.230662E+09 | 80086886.16 | 0.150575E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.623536E+10 | 0.465777E+10 | 0.425688E+10 | 0.151375E+10 | 0.274313E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.144898E+09 | 66649836.64 | 0.230662E+09 | 80086886.16 | 0.150575E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.943111E+09 | 0.824899E+09 | 0.479303E+09 | 0.172822E+09 | 0.307876E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: T SE APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.880200E+09 | 0.705752E+09 | 0.717267E+09 | 0.510656E+09 | 0.206611E+09 | 0.00 | 0.00 |
| February | 0.852023E+09 | 0.563114E+09 | 0.667501E+09 | 0.448881E+09 | 0.218620E+09 | 0.00 | 0.00 |
| March | 0.873878E+09 | 0.530620E+09 | 0.666197E+09 | 0.373467E+09 | 0.292730E+09 | 0.00 | 0.00 |
| April | 0.860257E+09 | 0.302212E+09 | 0.574815E+09 | 0.270443E+09 | 0.304372E+09 | 0.00 | 0.00 |
| May | 0.861984E+09 | 0.182359E+09 | 0.510584E+09 | 0.193896E+09 | 0.316688E+09 | 0.00 | 0.00 |
| June | 0.941618E+09 | 82525557.37 | 0.467566E+09 | 0.175252E+09 | 0.292313E+09 | 0.00 | 0.00 |
| July | 0.926436E+09 | 64976860.58 | 0.455464E+09 | 0.160263E+09 | 0.295201E+09 | 0.00 | 0.00 |
| August | 0.942261E+09 | 98700304.32 | 0.488279E+09 | 0.190975E+09 | 0.297304E+09 | 0.00 | 0.00 |
| September | 0.107031E+10 | 0.201145E+09 | 0.603604E+09 | 0.328305E+09 | 0.275300E+09 | 0.00 | 0.00 |
| October | 0.105873E+10 | 0.354809E+09 | 0.691021E+09 | 0.440607E+09 | 0.250414E+09 | 0.00 | 0.00 |
| November | 0.987053E+09 | 0.571701E+09 | 0.749105E+09 | 0.541199E+09 | 0.207906E+09 | 0.00 | 0.00 |
| December | 0.874473E+09 | 0.765612E+09 | 0.734100E+09 | 0.518218E+09 | 0.215882E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.111292E+11 | 0.442353E+10 | 0.732550E+10 | 0.415216E+10 | 0.317334E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.852023E+09 | 64976860.58 | 0.455464E+09 | 0.160263E+09 | 0.206611E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.107031E+10 | 0.765612E+09 | 0.749105E+09 | 0.541199E+09 | 0.316688E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: T NE APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.127393E+09 | 0.710879E+09 | 0.232063E+09 | 80652622.40 | 0.151410E+09 | 0.00 | 0.00 |
| February | 0.211777E+09 | 0.557694E+09 | 0.270518E+09 | 0.101243E+09 | 0.169275E+09 | 0.00 | 0.00 |
| March | 0.372002E+09 | 0.519764E+09 | 0.377385E+09 | 0.133730E+09 | 0.243655E+09 | 0.00 | 0.00 |
| April | 0.578224E+09 | 0.295267E+09 | 0.434702E+09 | 0.159611E+09 | 0.275091E+09 | 0.00 | 0.00 |
| May | 0.799722E+09 | 0.181046E+09 | 0.486839E+09 | 0.178134E+09 | 0.308705E+09 | 0.00 | 0.00 |
| June | 0.962476E+09 | 83583725.60 | 0.482183E+09 | 0.186303E+09 | 0.295880E+09 | 0.00 | 0.00 |
| July | 0.909709E+09 | 65017475.56 | 0.452147E+09 | 0.159448E+09 | 0.292699E+09 | 0.00 | 0.00 |
| August | 0.775210E+09 | 97515332.96 | 0.411899E+09 | 0.136337E+09 | 0.275561E+09 | 0.00 | 0.00 |
| September | 0.630108E+09 | 0.197491E+09 | 0.376780E+09 | 0.141693E+09 | 0.235088E+09 | 0.00 | 0.00 |
| October | 0.390576E+09 | 0.343708E+09 | 0.307151E+09 | 0.106167E+09 | 0.200984E+09 | 0.00 | 0.00 |
| November | 0.196668E+09 | 0.566237E+09 | 0.257141E+09 | 99520035.89 | 0.157621E+09 | 0.00 | 0.00 |
| December | 0.104926E+09 | 0.788286E+09 | 0.230576E+09 | 78008575.33 | 0.152567E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.605879E+10 | 0.440649E+10 | 0.431939E+10 | 0.156085E+10 | 0.275854E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.104926E+09 | 65017475.56 | 0.230576E+09 | 78008575.33 | 0.151410E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.962476E+09 | 0.788286E+09 | 0.486839E+09 | 0.186303E+09 | 0.308705E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: T N1 APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 16504049.42 | 0.476325E+09 | 83878188.20 | 0.00 | 83878188.20 | 0.00 | 0.00 |
| February | 41681654.95 | 0.378000E+09 | 92512121.34 | 0.00 | 92512121.34 | 0.00 | 0.00 |
| March | 96025657.91 | 0.348964E+09 | 0.134083E+09 | 15028.79 | 0.134068E+09 | 0.00 | 0.00 |
| April | 0.174548E+09 | 0.194693E+09 | 0.150287E+09 | 1624148.27 | 0.148663E+09 | 0.00 | 0.00 |
| May | 0.303109E+09 | 0.112318E+09 | 0.183844E+09 | 13547143.77 | 0.170297E+09 | 0.00 | 0.00 |
| June | 0.414938E+09 | 51134226.12 | 0.188495E+09 | 22859994.57 | 0.165635E+09 | 0.00 | 0.00 |
| July | 0.397044E+09 | 39294495.74 | 0.179655E+09 | 16759739.40 | 0.162895E+09 | 0.00 | 0.00 |
| August | 0.309376E+09 | 60500007.54 | 0.153063E+09 | 3945204.69 | 0.149118E+09 | 0.00 | 0.00 |
| September | 0.221324E+09 | 0.129750E+09 | 0.128581E+09 | 121021.29 | 0.128460E+09 | 0.00 | 0.00 |
| October | 0.119058E+09 | 0.226740E+09 | 0.110198E+09 | 0.00 | 0.110198E+09 | 0.00 | 0.00 |
| November | 32242322.44 | 0.381706E+09 | 86092241.07 | 0.00 | 86092241.07 | 0.00 | 0.00 |
| December | 11319263.04 | 0.531226E+09 | 83228616.05 | 0.00 | 83228616.05 | 0.00 | 0.00 |
| Annual Sum or Average | 0.213717E+10 | 0.293065E+10 | 0.157392E+10 | 58872280.77 | 0.151504E+10 | 0.00 | 0.00 |
| Minimum of Months | 11319263.04 | 39294495.74 | 83228616.05 | 0.00 | 83228616.05 | 0.00 | 0.00 |
| Maximum of Months | 0.414938E+09 | 0.531226E+09 | 0.188495E+09 | 22859994.57 | 0.170297E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: T N2 APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 16432555.76 | 0.476102E+09 | 83878188.20 | 0.00 | 83878188.20 | 0.00 | 0.00 |
| February | 41454212.14 | 0.377883E+09 | 92512121.34 | 0.00 | 92512121.34 | 0.00 | 0.00 |
| March | 95596188.31 | 0.348725E+09 | 0.134083E+09 | 15028.79 | 0.134068E+09 | 0.00 | 0.00 |
| April | 0.174085E+09 | 0.194557E+09 | 0.150287E+09 | 1624148.27 | 0.148663E+09 | 0.00 | 0.00 |
| May | 0.302872E+09 | 0.112229E+09 | 0.183844E+09 | 13547143.77 | 0.170297E+09 | 0.00 | 0.00 |
| June | 0.414857E+09 | 51086562.37 | 0.188495E+09 | 22859994.57 | 0.165635E+09 | 0.00 | 0.00 |
| July | 0.396977E+09 | 39253805.04 | 0.179655E+09 | 16759739.40 | 0.162895E+09 | 0.00 | 0.00 |
| August | 0.309299E+09 | 60454676.83 | 0.153063E+09 | 3945204.69 | 0.149118E+09 | 0.00 | 0.00 |
| September | 0.221168E+09 | 0.129648E+09 | 0.128581E+09 | 121021.29 | 0.128460E+09 | 0.00 | 0.00 |
| October | 0.118799E+09 | 0.226366E+09 | 0.110198E+09 | 0.00 | 0.110198E+09 | 0.00 | 0.00 |
| November | 32008794.01 | 0.381306E+09 | 86092241.07 | 0.00 | 86092241.07 | 0.00 | 0.00 |
| December | 11265438.37 | 0.531116E+09 | 83228616.05 | 0.00 | 83228616.05 | 0.00 | 0.00 |
| Annual Sum or Average | 0.213481E+10 | 0.292873E+10 | 0.157392E+10 | 58872280.77 | 0.151504E+10 | 0.00 | 0.00 |
| Minimum of Months | 11265438.37 | 39253805.04 | 83228616.05 | 0.00 | 83228616.05 | 0.00 | 0.00 |
| Maximum of Months | 0.414857E+09 | 0.531116E+09 | 0.188495E+09 | 22859994.57 | 0.170297E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: T S1 APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.761416E+09 | 0.436728E+09 | 0.569082E+09 | 0.430004E+09 | 0.139079E+09 | 0.00 | 0.00 |
| February | 0.670057E+09 | 0.350827E+09 | 0.489495E+09 | 0.347638E+09 | 0.141858E+09 | 0.00 | 0.00 |
| March | 0.595444E+09 | 0.342185E+09 | 0.422895E+09 | 0.239752E+09 | 0.183143E+09 | 0.00 | 0.00 |
| April | 0.463752E+09 | 0.202889E+09 | 0.290400E+09 | 0.112456E+09 | 0.177944E+09 | 0.00 | 0.00 |
| May | 0.372997E+09 | 0.120401E+09 | 0.207588E+09 | 29308895.00 | 0.178279E+09 | 0.00 | 0.00 |
| June | 0.396435E+09 | 52687482.73 | 0.173878E+09 | 11809415.54 | 0.162068E+09 | 0.00 | 0.00 |
| July | 0.415690E+09 | 40933525.02 | 0.182972E+09 | 17574380.96 | 0.165397E+09 | 0.00 | 0.00 |
| August | 0.480636E+09 | 63538866.82 | 0.229443E+09 | 58582872.53 | 0.170860E+09 | 0.00 | 0.00 |
| September | 0.665179E+09 | 0.130449E+09 | 0.355405E+09 | 0.186733E+09 | 0.168672E+09 | 0.00 | 0.00 |
| October | 0.788364E+09 | 0.224071E+09 | 0.494068E+09 | 0.334439E+09 | 0.159628E+09 | 0.00 | 0.00 |
| November | 0.817259E+09 | 0.355164E+09 | 0.578056E+09 | 0.441679E+09 | 0.136377E+09 | 0.00 | 0.00 |
| December | 0.770160E+09 | 0.471654E+09 | 0.586752E+09 | 0.440209E+09 | 0.146543E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.719739E+10 | 0.279153E+10 | 0.458003E+10 | 0.265019E+10 | 0.192985E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.372997E+09 | 40933525.02 | 0.173878E+09 | 11809415.54 | 0.136377E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.817259E+09 | 0.471654E+09 | 0.586752E+09 | 0.441679E+09 | 0.183143E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: T S2 APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.761180E+09 | 0.436506E+09 | 0.569082E+09 | 0.430004E+09 | 0.139079E+09 | 0.00 | 0.00 |
| February | 0.669692E+09 | 0.350750E+09 | 0.489495E+09 | 0.347638E+09 | 0.141858E+09 | 0.00 | 0.00 |
| March | 0.594982E+09 | 0.341965E+09 | 0.422895E+09 | 0.239752E+09 | 0.183143E+09 | 0.00 | 0.00 |
| April | 0.463336E+09 | 0.202750E+09 | 0.290400E+09 | 0.112456E+09 | 0.177944E+09 | 0.00 | 0.00 |
| May | 0.372769E+09 | 0.120310E+09 | 0.207588E+09 | 29308895.00 | 0.178279E+09 | 0.00 | 0.00 |
| June | 0.396351E+09 | 52639541.98 | 0.173878E+09 | 11809415.54 | 0.162068E+09 | 0.00 | 0.00 |
| July | 0.415624E+09 | 40892649.70 | 0.182972E+09 | 17574380.96 | 0.165397E+09 | 0.00 | 0.00 |
| August | 0.480564E+09 | 63493556.92 | 0.229443E+09 | 58582872.53 | 0.170860E+09 | 0.00 | 0.00 |
| September | 0.665054E+09 | 0.130348E+09 | 0.355405E+09 | 0.186733E+09 | 0.168672E+09 | 0.00 | 0.00 |
| October | 0.788250E+09 | 0.223800E+09 | 0.494068E+09 | 0.334439E+09 | 0.159628E+09 | 0.00 | 0.00 |
| November | 0.817027E+09 | 0.354933E+09 | 0.578056E+09 | 0.441679E+09 | 0.136377E+09 | 0.00 | 0.00 |
| December | 0.769912E+09 | 0.471464E+09 | 0.586752E+09 | 0.440209E+09 | 0.146543E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.719474E+10 | 0.278985E+10 | 0.458003E+10 | 0.265019E+10 | 0.192985E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.372769E+09 | 40892649.70 | 0.173878E+09 | 11809415.54 | 0.136377E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.817027E+09 | 0.471464E+09 | 0.586752E+09 | 0.441679E+09 | 0.183143E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: T CORRIDOR
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 33625142.56 | 74103673.20 | 35557491.82 | 19352925.03 | 16204566.78 | 0.00 | 0.00 |
| February | 47889695.95 | 58681531.34 | 42713214.31 | 24293751.38 | 18419462.93 | 0.00 | 0.00 |
| March | 72091469.99 | 55038354.68 | 58381347.06 | 32085546.91 | 26295800.15 | 0.00 | 0.00 |
| April | 98923730.35 | 32720558.99 | 68246563.70 | 37909637.08 | 30336926.62 | 0.00 | 0.00 |
| May | 0.117636E+09 | 21074167.32 | 72705021.67 | 39493347.19 | 33211674.48 | 0.00 | 0.00 |
| June | 0.128130E+09 | 10704708.15 | 70471642.79 | 39218817.94 | 31252824.85 | 0.00 | 0.00 |
| July | 0.119031E+09 | 9253939.27 | 65385600.53 | 34238620.08 | 31146980.45 | 0.00 | 0.00 |
| August | 0.108487E+09 | 12819322.86 | 62108639.14 | 31768036.26 | 30340602.88 | 0.00 | 0.00 |
| September | 97691962.98 | 23321060.40 | 59556541.34 | 33970741.09 | 25585800.25 | 0.00 | 0.00 |
| October | 65503508.61 | 39280149.09 | 47259759.28 | 25475314.11 | 21784445.17 | 0.00 | 0.00 |
| November | 45079424.18 | 60571102.79 | 41043835.27 | 23880237.70 | 17163597.57 | 0.00 | 0.00 |
| December | 31598764.44 | 80799420.18 | 35356611.78 | 18718475.18 | 16638136.60 | 0.00 | 0.00 |
| Annual Sum or Average | 0.965688E+09 | 0.478368E+09 | 0.658786E+09 | 0.360405E+09 | 0.298381E+09 | 0.00 | 0.00 |
| Minimum of Months | 31598764.44 | 9253939.27 | 35356611.78 | 18718475.18 | 16204566.78 | 0.00 | 0.00 |
| Maximum of Months | 0.128130E+09 | 80799420.18 | 72705021.67 | 39493347.19 | 33211674.48 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: G CORRIDOR
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.103353E+09 | 0.213833E+09 | 0.105899E+09 | 57637826.98 | 48261232.60 | 0.00 | 0.00 |
| February | 0.147476E+09 | 0.167775E+09 | 0.127211E+09 | 72352837.43 | 54857744.52 | 0.00 | 0.00 |
| March | 0.222048E+09 | 0.154467E+09 | 0.173874E+09 | 95558743.61 | 78315436.92 | 0.00 | 0.00 |
| April | 0.297749E+09 | 96992956.89 | 0.203255E+09 | 0.112904E+09 | 90350917.24 | 0.00 | 0.00 |
| May | 0.348833E+09 | 66629250.59 | 0.216534E+09 | 0.117621E+09 | 98912631.77 | 0.00 | 0.00 |
| June | 0.376262E+09 | 36287690.75 | 0.209882E+09 | 0.116803E+09 | 93078690.10 | 0.00 | 0.00 |
| July | 0.348844E+09 | 32191679.02 | 0.194735E+09 | 0.101971E+09 | 92763459.12 | 0.00 | 0.00 |
| August | 0.317355E+09 | 44217448.09 | 0.184975E+09 | 94613117.88 | 90361866.05 | 0.00 | 0.00 |
| September | 0.285830E+09 | 77122721.28 | 0.177374E+09 | 0.101173E+09 | 76200880.52 | 0.00 | 0.00 |
| October | 0.189231E+09 | 0.127919E+09 | 0.140751E+09 | 75871825.28 | 64879499.07 | 0.00 | 0.00 |
| November | 0.130997E+09 | 0.192767E+09 | 0.122239E+09 | 71121290.78 | 51117464.97 | 0.00 | 0.00 |
| December | 95871278.26 | 0.237859E+09 | 0.105301E+09 | 55748277.42 | 49552511.43 | 0.00 | 0.00 |
| Annual Sum or Average | 0.286385E+10 | 0.144806E+10 | 0.196203E+10 | 0.107338E+10 | 0.888652E+09 | 0.00 | 0.00 |
| Minimum of Months | 95871278.26 | 32191679.02 | 0.105301E+09 | 55748277.42 | 48261232.60 | 0.00 | 0.00 |
| Maximum of Months | 0.376262E+09 | 0.237859E+09 | 0.216534E+09 | 0.117621E+09 | 98912631.77 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: M CORRIDOR
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 30984221.41 | 82651395.64 | 35557491.82 | 19352925.03 | 16204566.78 | 0.00 | 0.00 |
| February | 44797560.55 | 65902843.91 | 42713214.31 | 24293751.38 | 18419462.93 | 0.00 | 0.00 |
| March | 67637352.11 | 61860569.49 | 58381347.06 | 32085546.91 | 26295800.15 | 0.00 | 0.00 |
| April | 96074880.84 | 35949084.49 | 68246563.70 | 37909637.08 | 30336926.62 | 0.00 | 0.00 |
| May | 0.117048E+09 | 22337154.68 | 72705021.67 | 39493347.19 | 33211674.48 | 0.00 | 0.00 |
| June | 0.129580E+09 | 10990254.73 | 70471642.79 | 39218817.94 | 31252824.85 | 0.00 | 0.00 |
| July | 0.120873E+09 | 9298385.63 | 65385600.53 | 34238620.08 | 31146980.45 | 0.00 | 0.00 |
| August | 0.109655E+09 | 13116715.53 | 62108639.14 | 31768036.26 | 30340602.88 | 0.00 | 0.00 |
| September | 97466433.07 | 24337347.33 | 59556541.34 | 33970741.09 | 25585800.25 | 0.00 | 0.00 |
| October | 62634727.45 | 43940900.63 | 47259759.28 | 25475314.11 | 21784445.17 | 0.00 | 0.00 |
| November | 41557560.63 | 69443195.56 | 41043835.27 | 23880237.70 | 17163597.57 | 0.00 | 0.00 |
| December | 29006216.87 | 90141917.71 | 35356611.78 | 18718475.18 | 16638136.60 | 0.00 | 0.00 |
| Annual Sum or Average | 0.947315E+09 | 0.529970E+09 | 0.658786E+09 | 0.360405E+09 | 0.298381E+09 | 0.00 | 0.00 |
| Minimum of Months | 29006216.87 | 9298385.63 | 35356611.78 | 18718475.18 | 16204566.78 | 0.00 | 0.00 |
| Maximum of Months | 0.129580E+09 | 90141917.71 | 72705021.67 | 39493347.19 | 33211674.48 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
| January | 8.14 | 3.28 | -3.0 | 3.49 | -5.4 | 41.12 | 223.64 | 0.00 |
| February | 10.27 | 3.71 | -4.6 | 3.82 | -5.0 | 51.61 | 245.22 | 0.00 |
| March | 12.55 | 4.68 | -5.5 | 4.62 | -3.1 | 72.41 | 273.25 | 0.00 |
| April | 19.23 | 8.50 | -2.7 | 4.72 | 3.38 | 79.21 | 314.56 | 0.00 |
| May | 23.84 | 12.23 | 2.64 | 5.25 | 8.38 | 86.83 | 326.20 | 0.00 |
| June | 27.86 | 15.03 | 5.88 | 4.15 | 14.09 | 80.19 | 344.14 | 0.01 |
| July | 27.54 | 18.92 | 14.64 | 3.53 | 17.44 | 86.25 | 283.04 | 0.01 |
| August | 26.28 | 17.11 | 12.00 | 3.28 | 15.48 | 80.55 | 269.68 | 0.02 |
| September | 23.38 | 15.82 | 11.20 | 2.23 | 11.29 | 66.71 | 294.09 | 0.00 |
| October | 18.30 | 12.02 | 7.27 | 3.24 | 6.21 | 54.59 | 257.93 | 0.01 |
| November | 11.18 | 5.22 | -1.5 | 3.40 | -3.3 | 40.23 | 258.80 | 0.00 |
| December | 6.79 | 1.84 | -4.8 | 2.82 | -8.9 | 42.65 | 217.21 | 0.00 |
| Annual Sum or Average | 17.98 | 9.90 | 2.67 | 3.71 | 4.26 | 65.29 | 275.60 | 0.00 |
| Minimum of Months | 6.79 | 1.84 | -5.5 | 2.23 | -8.9 | 40.23 | 217.21 | 0.00 |
| Maximum of Months | 27.86 | 18.92 | 14.64 | 5.25 | 17.44 | 86.83 | 344.14 | 0.02 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
| January | 20.60 | 03-JAN-14:00 | 8.39 | -5.0 | 9.80 | 2.22 | 118.50 | 530.50 |
| February | 23.30 | 20-FEB-14:00 | 8.88 | -7.8 | 4.10 | 4.10 | 55.00 | 955.00 |
| March | 25.00 | 21-MAR-15:00 | 9.53 | -8.3 | 6.20 | 5.54 | 50.00 | 873.00 |
| April | 32.20 | 21-APR-13:00 | 15.21 | 2.80 | 13.90 | 18.28 | 265.50 | 638.50 |
| May | 35.00 | 19-MAY-13:00 | 17.23 | 6.10 | 10.30 | 21.78 | 145.00 | 874.50 |
| June | 38.90 | 02-JUN-15:00 | 16.22 | -1.1 | 4.60 | 20.40 | 234.50 | 284.00 |
| July | 38.30 | 01-JUL-16:00 | 19.19 | 8.90 | 3.60 | 26.81 | 165.50 | 256.50 |
| August | 37.20 | 07-AUG-15:00 | 17.89 | 6.70 | 5.70 | 24.66 | 143.50 | 615.00 |
| September | 33.90 | 19-SEP-13:00 | 16.85 | 6.70 | 3.10 | 17.75 | 113.00 | 912.00 |
| October | 32.80 | 01-OCT-14:00 | 15.90 | 4.40 | 5.70 | 16.12 | 127.50 | 736.50 |
| November | 23.90 | 03-NOV-15:00 | 13.45 | 6.10 | 5.70 | 12.22 | 48.50 | 648.50 |
| December | 18.30 | 10-DEC-14:00 | 7.97 | -2.8 | 7.20 | 4.10 | 123.00 | 52.50 |
| Annual Sum or Average | ||||||||
| Minimum of Months | 18.30 | 7.97 | -8.3 | 3.10 | 2.22 | 48.50 | 52.50 | |
| Maximum of Months | 38.90 | 19.19 | 8.90 | 13.90 | 26.81 | 265.50 | 955.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
| January | -4.4 | 27-JAN-06:00 | -7.5 | -15.0 | 3.60 | -23.6 | 0.00 | 0.00 |
| February | -5.6 | 03-FEB-06:00 | -7.5 | -11.7 | 1.50 | -23.9 | 0.00 | 0.00 |
| March | -3.9 | 02-MAR-04:00 | -6.5 | -12.8 | 1.50 | -21.3 | 0.00 | 0.00 |
| April | 3.30 | 12-APR-05:00 | -1.8 | -9.4 | 2.10 | -14.9 | 37.00 | 217.50 |
| May | 9.40 | 02-MAY-05:00 | 3.98 | -2.2 | 3.60 | -7.6 | 51.00 | 277.50 |
| June | 15.00 | 13-JUN-04:00 | 4.43 | -10.6 | 2.10 | -4.3 | 0.00 | 0.00 |
| July | 17.80 | 05-JUL-05:00 | 15.98 | 15.00 | 4.10 | 4.31 | 39.00 | 249.00 |
| August | 16.70 | 31-AUG-05:00 | 13.89 | 12.20 | 4.10 | 2.64 | 36.00 | 126.50 |
| September | 8.30 | 30-SEP-05:00 | 5.77 | 3.30 | 1.50 | -7.3 | 0.00 | 0.00 |
| October | 6.70 | 11-OCT-05:00 | 5.82 | 5.00 | 1.50 | -5.5 | 0.00 | 0.00 |
| November | -0.6 | 17-NOV-03:00 | -3.1 | -6.7 | 1.50 | -18.1 | 0.00 | 0.00 |
| December | -4.4 | 27-DEC-06:00 | -5.1 | -6.1 | 2.10 | -18.6 | 0.00 | 0.00 |
| Annual Sum or Average | ||||||||
| Minimum of Months | -5.6 | -7.5 | -15.0 | 1.50 | -23.9 | 0.00 | 0.00 | |
| Maximum of Months | 17.80 | 15.98 | 15.00 | 4.10 | 4.31 | 51.00 | 277.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| SITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
| January | 10.18 | 12-JAN-15:00 | 18.90 | 2.80 | 3.60 | 6.15 | 70.50 | 491.50 |
| February | 11.42 | 13-FEB-16:00 | 12.80 | 10.60 | 4.10 | 6.55 | 34.00 | 18.50 |
| March | 10.75 | 10-MAR-18:00 | 13.30 | 8.90 | 1.50 | 8.54 | 0.00 | 0.00 |
| April | 15.74 | 29-APR-13:00 | 30.00 | 6.70 | 4.10 | 18.28 | 336.50 | 432.50 |
| May | 19.12 | 24-MAY-12:00 | 27.80 | 15.00 | 5.20 | 17.57 | 188.50 | 862.00 |
| June | 20.21 | 03-JUN-14:00 | 33.90 | 13.90 | 8.80 | 23.66 | 264.50 | 316.00 |
| July | 22.88 | 20-JUL-15:39 | 25.53 | 21.87 | 2.93 | 18.99 | 184.00 | 15.83 |
| August | 21.18 | 02-AUG-11:00 | 30.60 | 17.20 | 3.60 | 20.75 | 154.50 | 850.00 |
| September | 20.65 | 14-SEP-09:00 | 25.00 | 18.90 | 2.10 | 14.47 | 126.50 | 835.50 |
| October | 19.64 | 03-OCT-13:00 | 32.80 | 13.30 | 2.60 | 21.44 | 224.50 | 577.50 |
| November | 13.57 | 03-NOV-14:00 | 23.30 | 7.20 | 0.00 | 10.88 | 72.50 | 802.00 |
| December | 8.30 | 10-DEC-12:00 | 17.20 | -0.6 | 5.70 | 1.58 | 198.50 | 507.50 |
| Annual Sum or Average | ||||||||
| Minimum of Months | 8.30 | 12.80 | -0.6 | 0.00 | 1.58 | 0.00 | 0.00 | |
| Maximum of Months | 22.88 | 33.90 | 21.87 | 8.80 | 23.66 | 336.50 | 862.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| SITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
| January | 9.00 | 16-JAN-01:00 | 9.00 | 9.00 | 2.10 | 4.51 | 0.00 | 0.00 |
| February | 10.60 | 13-FEB-13:09 | 12.20 | 11.24 | 5.53 | 5.71 | 147.33 | 0.00 |
| March | 10.00 | 11-MAR-00:00 | 10.60 | 10.24 | 2.10 | 6.15 | 0.00 | 0.00 |
| April | 10.60 | 17-APR-01:00 | 17.80 | 13.38 | 7.20 | 3.48 | 0.00 | 0.00 |
| May | 15.00 | 24-MAY-10:00 | 25.60 | 18.41 | 7.20 | 15.39 | 171.00 | 872.50 |
| June | 17.20 | 19-JUN-17:00 | 23.90 | 19.20 | 3.60 | 15.39 | 86.00 | 324.00 |
| July | 22.20 | 20-JUL-14:00 | 24.40 | 22.82 | 4.60 | 17.93 | 283.00 | 59.50 |
| August | 18.90 | 01-AUG-20:00 | 22.20 | 19.91 | 4.60 | 17.75 | 0.00 | 0.00 |
| September | 19.40 | 22-SEP-01:00 | 20.60 | 19.76 | 1.50 | 16.30 | 0.00 | 0.00 |
| October | 17.20 | 03-OCT-19:00 | 23.30 | 19.11 | 4.60 | 18.46 | 0.00 | 0.00 |
| November | 10.00 | 01-NOV-09:00 | 13.30 | 11.28 | 3.10 | 8.94 | 123.50 | 0.00 |
| December | 6.10 | 13-DEC-00:00 | 8.30 | 7.10 | 7.70 | 3.06 | 0.00 | 0.00 |
| Annual Sum or Average | ||||||||
| Minimum of Months | 6.10 | 8.30 | 7.10 | 1.50 | 3.06 | 0.00 | 0.00 | |
| Maximum of Months | 22.20 | 25.60 | 22.82 | 7.70 | 18.46 | 283.00 | 872.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| SITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
| January | 18.00 | 13.00 | 16.00 | 15.16 | 28.38 | 0.00 |
| February | 18.00 | 13.00 | 16.00 | 15.21 | 35.58 | 0.00 |
| March | 18.00 | 13.00 | 16.00 | 16.80 | 47.71 | 0.00 |
| April | 18.00 | 13.00 | 16.00 | 19.62 | 58.45 | 0.00 |
| May | 18.00 | 13.00 | 16.00 | 22.88 | 63.58 | 0.00 |
| June | 18.00 | 13.00 | 16.00 | 25.71 | 66.73 | 0.00 |
| July | 18.00 | 13.00 | 16.00 | 27.35 | 58.19 | 0.00 |
| August | 18.00 | 13.00 | 16.00 | 27.33 | 54.44 | 0.00 |
| September | 18.00 | 13.00 | 16.00 | 25.68 | 50.89 | 0.00 |
| October | 18.00 | 13.00 | 16.00 | 22.83 | 39.37 | 0.00 |
| November | 18.00 | 13.00 | 16.00 | 19.57 | 32.11 | 0.00 |
| December | 18.00 | 13.00 | 16.00 | 16.77 | 26.90 | 0.00 |
| Annual Sum or Average | 18.00 | 13.00 | 16.00 | 21.28 | 46.90 | 0.00 |
| Minimum of Months | 18.00 | 13.00 | 16.00 | 15.16 | 26.90 | 0.00 |
| Maximum of Months | 18.00 | 13.00 | 16.00 | 27.35 | 66.73 | 0.00 |
Report: WaterHeaterReportMonthly
For: G SW APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.113493E+10 | -952037319.4 | 0.00 | 0.00 | 744.00 | 0.00 | -182892636.5 | 59.44 | 0.00 | 0.00 |
| February | 0.102389E+10 | -859057924.5 | 0.00 | 0.00 | 672.00 | 0.00 | -164834122.5 | 59.44 | 0.00 | 0.00 |
| March | 0.109878E+10 | -916754709.1 | 0.00 | 0.00 | 744.00 | 0.00 | -182026928.2 | 59.44 | 0.00 | 0.00 |
| April | 0.997896E+09 | -828608718.0 | 0.00 | 0.00 | 720.00 | 0.00 | -169287272.2 | 59.44 | 0.00 | 0.00 |
| May | 0.958831E+09 | -786077305.5 | 0.00 | 0.00 | 744.00 | 0.00 | -172753200.8 | 59.44 | 0.00 | 0.00 |
| June | 0.868698E+09 | -701771715.2 | 0.00 | 0.00 | 720.00 | 0.00 | -166926396.1 | 59.44 | 0.00 | 0.00 |
| July | 0.862567E+09 | -690087024.0 | 0.00 | 0.00 | 744.00 | 0.00 | -172480063.4 | 59.44 | 0.00 | 0.00 |
| August | 0.862861E+09 | -690374722.8 | 0.00 | 0.00 | 744.00 | 0.00 | -172486714.6 | 59.44 | 0.00 | 0.00 |
| September | 0.869464E+09 | -702536626.5 | 0.00 | 0.00 | 720.00 | 0.00 | -166927368.0 | 59.44 | 0.00 | 0.00 |
| October | 0.959702E+09 | -787146309.0 | 0.00 | 0.00 | 744.00 | 0.00 | -172555229.8 | 59.44 | 0.00 | 0.00 |
| November | 0.999843E+09 | -829648392.7 | 0.00 | 0.00 | 720.00 | 0.00 | -170194480.9 | 59.44 | 0.00 | 0.00 |
| December | 0.110025E+10 | -917530380.4 | 0.00 | 0.00 | 744.00 | 0.00 | -182722026.9 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.117377E+11 | -0.966163E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.207609E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.862567E+09 | -952037319.4 | 0.00 | 0.00 | 672.00 | 0.00 | -182892636.5 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.113493E+10 | -690087024.0 | 0.00 | 0.00 | 744.00 | 0.00 | -164834122.5 | 59.44 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: G NW APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.113839E+10 | -952037062.9 | 0.00 | 0.00 | 744.00 | 0.00 | -186350325.9 | 59.44 | 0.00 | 0.00 |
| February | 0.102684E+10 | -859058271.7 | 0.00 | 0.00 | 672.00 | 0.00 | -167780080.1 | 59.44 | 0.00 | 0.00 |
| March | 0.110156E+10 | -916751981.5 | 0.00 | 0.00 | 744.00 | 0.00 | -184807446.9 | 59.44 | 0.00 | 0.00 |
| April | 0.998982E+09 | -828608368.4 | 0.00 | 0.00 | 720.00 | 0.00 | -170373547.3 | 59.44 | 0.00 | 0.00 |
| May | 0.958879E+09 | -786077081.2 | 0.00 | 0.00 | 744.00 | 0.00 | -172802030.9 | 59.44 | 0.00 | 0.00 |
| June | 0.868697E+09 | -701769868.3 | 0.00 | 0.00 | 720.00 | 0.00 | -166927007.5 | 59.44 | 0.00 | 0.00 |
| July | 0.862567E+09 | -690087178.8 | 0.00 | 0.00 | 744.00 | 0.00 | -172480038.9 | 59.44 | 0.00 | 0.00 |
| August | 0.862861E+09 | -690374387.8 | 0.00 | 0.00 | 744.00 | 0.00 | -172486992.3 | 59.44 | 0.00 | 0.00 |
| September | 0.869468E+09 | -702536578.8 | 0.00 | 0.00 | 720.00 | 0.00 | -166931041.3 | 59.44 | 0.00 | 0.00 |
| October | 0.960041E+09 | -787143886.2 | 0.00 | 0.00 | 744.00 | 0.00 | -172897154.6 | 59.44 | 0.00 | 0.00 |
| November | 0.100444E+10 | -829648379.9 | 0.00 | 0.00 | 720.00 | 0.00 | -174794086.2 | 59.44 | 0.00 | 0.00 |
| December | 0.110382E+10 | -917532509.8 | 0.00 | 0.00 | 744.00 | 0.00 | -186284643.0 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.117565E+11 | -0.966163E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.209491E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.862567E+09 | -952037062.9 | 0.00 | 0.00 | 672.00 | 0.00 | -186350325.9 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.113839E+10 | -690087178.8 | 0.00 | 0.00 | 744.00 | 0.00 | -166927007.5 | 59.44 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: G NE APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.113849E+10 | -952037520.6 | 0.00 | 0.00 | 744.00 | 0.00 | -186456432.0 | 59.44 | 0.00 | 0.00 |
| February | 0.102686E+10 | -859057084.1 | 0.00 | 0.00 | 672.00 | 0.00 | -167800659.7 | 59.44 | 0.00 | 0.00 |
| March | 0.110161E+10 | -916751521.4 | 0.00 | 0.00 | 744.00 | 0.00 | -184853765.8 | 59.44 | 0.00 | 0.00 |
| April | 0.998654E+09 | -828605074.2 | 0.00 | 0.00 | 720.00 | 0.00 | -170049011.5 | 59.44 | 0.00 | 0.00 |
| May | 0.958796E+09 | -786064435.5 | 0.00 | 0.00 | 744.00 | 0.00 | -172731837.8 | 59.44 | 0.00 | 0.00 |
| June | 0.868695E+09 | -701781272.6 | 0.00 | 0.00 | 720.00 | 0.00 | -166914109.3 | 59.44 | 0.00 | 0.00 |
| July | 0.862571E+09 | -690084380.2 | 0.00 | 0.00 | 744.00 | 0.00 | -172486425.9 | 59.44 | 0.00 | 0.00 |
| August | 0.862863E+09 | -690381063.9 | 0.00 | 0.00 | 744.00 | 0.00 | -172481680.4 | 59.44 | 0.00 | 0.00 |
| September | 0.869469E+09 | -702549839.7 | 0.00 | 0.00 | 720.00 | 0.00 | -166919267.0 | 59.44 | 0.00 | 0.00 |
| October | 0.960051E+09 | -787153016.8 | 0.00 | 0.00 | 744.00 | 0.00 | -172897677.8 | 59.44 | 0.00 | 0.00 |
| November | 0.100454E+10 | -829647558.7 | 0.00 | 0.00 | 720.00 | 0.00 | -174887732.7 | 59.44 | 0.00 | 0.00 |
| December | 0.110388E+10 | -917533267.2 | 0.00 | 0.00 | 744.00 | 0.00 | -186347213.1 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.117565E+11 | -0.966165E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.209483E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.862571E+09 | -952037520.6 | 0.00 | 0.00 | 672.00 | 0.00 | -186456432.0 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.113849E+10 | -690084380.2 | 0.00 | 0.00 | 744.00 | 0.00 | -166914109.3 | 59.44 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: G N1 APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.113829E+10 | -952035812.6 | 0.00 | 0.00 | 744.00 | 0.00 | -186251305.3 | 59.44 | 0.00 | 0.00 |
| February | 0.102658E+10 | -859059500.0 | 0.00 | 0.00 | 672.00 | 0.00 | -167516820.1 | 59.44 | 0.00 | 0.00 |
| March | 0.110110E+10 | -916755090.2 | 0.00 | 0.00 | 744.00 | 0.00 | -184341828.0 | 59.44 | 0.00 | 0.00 |
| April | 0.997972E+09 | -828614233.3 | 0.00 | 0.00 | 720.00 | 0.00 | -169358214.8 | 59.44 | 0.00 | 0.00 |
| May | 0.958674E+09 | -786077022.9 | 0.00 | 0.00 | 744.00 | 0.00 | -172596526.0 | 59.44 | 0.00 | 0.00 |
| June | 0.868698E+09 | -701771825.5 | 0.00 | 0.00 | 720.00 | 0.00 | -166926137.5 | 59.44 | 0.00 | 0.00 |
| July | 0.862567E+09 | -690087214.5 | 0.00 | 0.00 | 744.00 | 0.00 | -172479929.4 | 59.44 | 0.00 | 0.00 |
| August | 0.862861E+09 | -690374764.2 | 0.00 | 0.00 | 744.00 | 0.00 | -172486690.0 | 59.44 | 0.00 | 0.00 |
| September | 0.869464E+09 | -702536627.0 | 0.00 | 0.00 | 720.00 | 0.00 | -166927476.3 | 59.44 | 0.00 | 0.00 |
| October | 0.959791E+09 | -787146062.1 | 0.00 | 0.00 | 744.00 | 0.00 | -172644482.2 | 59.44 | 0.00 | 0.00 |
| November | 0.100332E+10 | -829647370.5 | 0.00 | 0.00 | 720.00 | 0.00 | -173668460.6 | 59.44 | 0.00 | 0.00 |
| December | 0.110360E+10 | -917533718.7 | 0.00 | 0.00 | 744.00 | 0.00 | -186070966.5 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.117529E+11 | -0.966164E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.209127E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.862567E+09 | -952035812.6 | 0.00 | 0.00 | 672.00 | 0.00 | -186251305.3 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.113829E+10 | -690087214.5 | 0.00 | 0.00 | 744.00 | 0.00 | -166926137.5 | 59.44 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: G N2 APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.113829E+10 | -952035831.8 | 0.00 | 0.00 | 744.00 | 0.00 | -186257562.6 | 59.44 | 0.00 | 0.00 |
| February | 0.102657E+10 | -859059426.5 | 0.00 | 0.00 | 672.00 | 0.00 | -167511856.0 | 59.44 | 0.00 | 0.00 |
| March | 0.110109E+10 | -916753390.6 | 0.00 | 0.00 | 744.00 | 0.00 | -184336903.5 | 59.44 | 0.00 | 0.00 |
| April | 0.997946E+09 | -828610522.1 | 0.00 | 0.00 | 720.00 | 0.00 | -169335515.1 | 59.44 | 0.00 | 0.00 |
| May | 0.958671E+09 | -786077962.3 | 0.00 | 0.00 | 744.00 | 0.00 | -172593146.9 | 59.44 | 0.00 | 0.00 |
| June | 0.868694E+09 | -701782003.7 | 0.00 | 0.00 | 720.00 | 0.00 | -166912368.6 | 59.44 | 0.00 | 0.00 |
| July | 0.862572E+09 | -690083404.4 | 0.00 | 0.00 | 744.00 | 0.00 | -172488278.4 | 59.44 | 0.00 | 0.00 |
| August | 0.862863E+09 | -690382851.3 | 0.00 | 0.00 | 744.00 | 0.00 | -172480576.7 | 59.44 | 0.00 | 0.00 |
| September | 0.869462E+09 | -702543977.8 | 0.00 | 0.00 | 720.00 | 0.00 | -166918490.2 | 59.44 | 0.00 | 0.00 |
| October | 0.959789E+09 | -787151296.9 | 0.00 | 0.00 | 744.00 | 0.00 | -172637451.5 | 59.44 | 0.00 | 0.00 |
| November | 0.100333E+10 | -829652710.8 | 0.00 | 0.00 | 720.00 | 0.00 | -173674249.7 | 59.44 | 0.00 | 0.00 |
| December | 0.110360E+10 | -917532481.4 | 0.00 | 0.00 | 744.00 | 0.00 | -186072456.9 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.117529E+11 | -0.966167E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.209122E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.862572E+09 | -952035831.8 | 0.00 | 0.00 | 672.00 | 0.00 | -186257562.6 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.113829E+10 | -690083404.4 | 0.00 | 0.00 | 744.00 | 0.00 | -166912368.6 | 59.44 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: G S1 APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.113247E+10 | -952035754.6 | 0.00 | 0.00 | 744.00 | 0.00 | -180438673.5 | 59.44 | 0.00 | 0.00 |
| February | 0.102172E+10 | -859060297.2 | 0.00 | 0.00 | 672.00 | 0.00 | -162664161.8 | 59.44 | 0.00 | 0.00 |
| March | 0.109661E+10 | -916752630.5 | 0.00 | 0.00 | 744.00 | 0.00 | -179861694.2 | 59.44 | 0.00 | 0.00 |
| April | 0.996792E+09 | -828610666.3 | 0.00 | 0.00 | 720.00 | 0.00 | -168181029.8 | 59.44 | 0.00 | 0.00 |
| May | 0.958645E+09 | -786076863.7 | 0.00 | 0.00 | 744.00 | 0.00 | -172568281.3 | 59.44 | 0.00 | 0.00 |
| June | 0.868698E+09 | -701770976.1 | 0.00 | 0.00 | 720.00 | 0.00 | -166926579.9 | 59.44 | 0.00 | 0.00 |
| July | 0.862567E+09 | -690086853.8 | 0.00 | 0.00 | 744.00 | 0.00 | -172480202.3 | 59.44 | 0.00 | 0.00 |
| August | 0.862861E+09 | -690374703.5 | 0.00 | 0.00 | 744.00 | 0.00 | -172486744.4 | 59.44 | 0.00 | 0.00 |
| September | 0.869464E+09 | -702536627.7 | 0.00 | 0.00 | 720.00 | 0.00 | -166927372.8 | 59.44 | 0.00 | 0.00 |
| October | 0.959641E+09 | -787146802.1 | 0.00 | 0.00 | 744.00 | 0.00 | -172494549.4 | 59.44 | 0.00 | 0.00 |
| November | 0.998483E+09 | -829649782.5 | 0.00 | 0.00 | 720.00 | 0.00 | -168833322.0 | 59.44 | 0.00 | 0.00 |
| December | 0.109767E+10 | -917533931.7 | 0.00 | 0.00 | 744.00 | 0.00 | -180137530.7 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.117256E+11 | -0.966164E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.206400E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.862567E+09 | -952035754.6 | 0.00 | 0.00 | 672.00 | 0.00 | -180438673.5 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.113247E+10 | -690086853.8 | 0.00 | 0.00 | 744.00 | 0.00 | -162664161.8 | 59.44 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: G S2 APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.113237E+10 | -952036973.5 | 0.00 | 0.00 | 744.00 | 0.00 | -180334524.6 | 59.44 | 0.00 | 0.00 |
| February | 0.102150E+10 | -859060433.6 | 0.00 | 0.00 | 672.00 | 0.00 | -162441437.9 | 59.44 | 0.00 | 0.00 |
| March | 0.109627E+10 | -916753837.8 | 0.00 | 0.00 | 744.00 | 0.00 | -179520679.3 | 59.44 | 0.00 | 0.00 |
| April | 0.996588E+09 | -828608659.1 | 0.00 | 0.00 | 720.00 | 0.00 | -167979748.3 | 59.44 | 0.00 | 0.00 |
| May | 0.958610E+09 | -786069347.1 | 0.00 | 0.00 | 744.00 | 0.00 | -172540437.0 | 59.44 | 0.00 | 0.00 |
| June | 0.868696E+09 | -701772594.3 | 0.00 | 0.00 | 720.00 | 0.00 | -166923241.2 | 59.44 | 0.00 | 0.00 |
| July | 0.862569E+09 | -690087731.5 | 0.00 | 0.00 | 744.00 | 0.00 | -172481018.9 | 59.44 | 0.00 | 0.00 |
| August | 0.862862E+09 | -690375353.3 | 0.00 | 0.00 | 744.00 | 0.00 | -172486394.5 | 59.44 | 0.00 | 0.00 |
| September | 0.869463E+09 | -702540240.8 | 0.00 | 0.00 | 720.00 | 0.00 | -166922862.8 | 59.44 | 0.00 | 0.00 |
| October | 0.959638E+09 | -787146941.8 | 0.00 | 0.00 | 744.00 | 0.00 | -172491525.3 | 59.44 | 0.00 | 0.00 |
| November | 0.998367E+09 | -829649983.4 | 0.00 | 0.00 | 720.00 | 0.00 | -168716962.2 | 59.44 | 0.00 | 0.00 |
| December | 0.109740E+10 | -917533435.0 | 0.00 | 0.00 | 744.00 | 0.00 | -179870814.7 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.117243E+11 | -0.966164E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.206271E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.862569E+09 | -952036973.5 | 0.00 | 0.00 | 672.00 | 0.00 | -180334524.6 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.113237E+10 | -690087731.5 | 0.00 | 0.00 | 744.00 | 0.00 | -162441437.9 | 59.44 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: M SW APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.208488E+10 | -0.190408E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -180802550.4 | 59.44 | 0.00 | 0.00 |
| February | 0.187973E+10 | -0.171812E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -161609549.0 | 59.44 | 0.00 | 0.00 |
| March | 0.201041E+10 | -0.183351E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -176895747.9 | 59.44 | 0.00 | 0.00 |
| April | 0.182503E+10 | -0.165723E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -167799667.6 | 59.44 | 0.00 | 0.00 |
| May | 0.174471E+10 | -0.157216E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172558456.2 | 59.44 | 0.00 | 0.00 |
| June | 0.157048E+10 | -0.140355E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -166923180.2 | 59.44 | 0.00 | 0.00 |
| July | 0.155266E+10 | -0.138017E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172480493.1 | 59.44 | 0.00 | 0.00 |
| August | 0.155325E+10 | -0.138076E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172484843.8 | 59.44 | 0.00 | 0.00 |
| September | 0.157202E+10 | -0.140509E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -166930643.5 | 59.44 | 0.00 | 0.00 |
| October | 0.174709E+10 | -0.157430E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172790857.5 | 59.44 | 0.00 | 0.00 |
| November | 0.183028E+10 | -0.165930E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -170977614.2 | 59.44 | 0.00 | 0.00 |
| December | 0.201664E+10 | -0.183507E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -181574487.3 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.213872E+11 | -0.193233E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.206383E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.155266E+10 | -0.190408E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -181574487.3 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.208488E+10 | -0.138017E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161609549.0 | 59.44 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: M NW APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.208992E+10 | -0.190408E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -185839824.5 | 59.44 | 0.00 | 0.00 |
| February | 0.188394E+10 | -0.171812E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -165815762.2 | 59.44 | 0.00 | 0.00 |
| March | 0.201357E+10 | -0.183351E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -180057311.8 | 59.44 | 0.00 | 0.00 |
| April | 0.182545E+10 | -0.165723E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -168224203.9 | 59.44 | 0.00 | 0.00 |
| May | 0.174471E+10 | -0.157215E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172567067.7 | 59.44 | 0.00 | 0.00 |
| June | 0.157048E+10 | -0.140356E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -166920788.2 | 59.44 | 0.00 | 0.00 |
| July | 0.155266E+10 | -0.138017E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172485372.7 | 59.44 | 0.00 | 0.00 |
| August | 0.155325E+10 | -0.138076E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172482843.0 | 59.44 | 0.00 | 0.00 |
| September | 0.157204E+10 | -0.140509E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -166951057.9 | 59.44 | 0.00 | 0.00 |
| October | 0.174765E+10 | -0.157430E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -173342060.1 | 59.44 | 0.00 | 0.00 |
| November | 0.183493E+10 | -0.165931E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -175626440.4 | 59.44 | 0.00 | 0.00 |
| December | 0.202116E+10 | -0.183507E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186090468.7 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.214098E+11 | -0.193233E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.208640E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.155266E+10 | -0.190408E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -186090468.7 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.208992E+10 | -0.138017E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -165815762.2 | 59.44 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: M SE APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.208486E+10 | -0.190408E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -180781533.6 | 59.44 | 0.00 | 0.00 |
| February | 0.187940E+10 | -0.171812E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -161276387.4 | 59.44 | 0.00 | 0.00 |
| March | 0.201017E+10 | -0.183352E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -176649381.6 | 59.44 | 0.00 | 0.00 |
| April | 0.182490E+10 | -0.165723E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -167676753.3 | 59.44 | 0.00 | 0.00 |
| May | 0.174468E+10 | -0.157215E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172534310.7 | 59.44 | 0.00 | 0.00 |
| June | 0.157048E+10 | -0.140356E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -166920732.9 | 59.44 | 0.00 | 0.00 |
| July | 0.155266E+10 | -0.138017E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172485386.2 | 59.44 | 0.00 | 0.00 |
| August | 0.155325E+10 | -0.138076E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172482980.5 | 59.44 | 0.00 | 0.00 |
| September | 0.157202E+10 | -0.140509E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -166933496.5 | 59.44 | 0.00 | 0.00 |
| October | 0.174713E+10 | -0.157430E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172825913.9 | 59.44 | 0.00 | 0.00 |
| November | 0.183024E+10 | -0.165930E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -170942267.7 | 59.44 | 0.00 | 0.00 |
| December | 0.201654E+10 | -0.183507E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -181470884.2 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.213863E+11 | -0.193233E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.206298E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.155266E+10 | -0.190408E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -181470884.2 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.208486E+10 | -0.138017E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161276387.4 | 59.44 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: M NE APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.209013E+10 | -0.190408E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186046179.8 | 59.44 | 0.00 | 0.00 |
| February | 0.188381E+10 | -0.171812E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -165689351.3 | 59.44 | 0.00 | 0.00 |
| March | 0.201324E+10 | -0.183351E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -179732473.9 | 59.44 | 0.00 | 0.00 |
| April | 0.182526E+10 | -0.165723E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -168035783.3 | 59.44 | 0.00 | 0.00 |
| May | 0.174469E+10 | -0.157215E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172536752.9 | 59.44 | 0.00 | 0.00 |
| June | 0.157048E+10 | -0.140355E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -166922754.0 | 59.44 | 0.00 | 0.00 |
| July | 0.155266E+10 | -0.138017E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172480898.2 | 59.44 | 0.00 | 0.00 |
| August | 0.155325E+10 | -0.138076E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172484792.4 | 59.44 | 0.00 | 0.00 |
| September | 0.157204E+10 | -0.140509E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -166948242.5 | 59.44 | 0.00 | 0.00 |
| October | 0.174763E+10 | -0.157430E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -173326799.9 | 59.44 | 0.00 | 0.00 |
| November | 0.183503E+10 | -0.165931E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -175725048.3 | 59.44 | 0.00 | 0.00 |
| December | 0.202125E+10 | -0.183507E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -186179913.5 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.214095E+11 | -0.193234E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.208611E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.155266E+10 | -0.190408E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -186179913.5 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.209013E+10 | -0.138017E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -165689351.3 | 59.44 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: M N1 APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.208945E+10 | -0.190408E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -185374333.1 | 59.44 | 0.00 | 0.00 |
| February | 0.188284E+10 | -0.171812E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -164718988.0 | 59.44 | 0.00 | 0.00 |
| March | 0.201193E+10 | -0.183351E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -178419257.1 | 59.44 | 0.00 | 0.00 |
| April | 0.182492E+10 | -0.165722E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -167693273.0 | 59.44 | 0.00 | 0.00 |
| May | 0.174466E+10 | -0.157215E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172510403.9 | 59.44 | 0.00 | 0.00 |
| June | 0.157048E+10 | -0.140356E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -166920814.7 | 59.44 | 0.00 | 0.00 |
| July | 0.155266E+10 | -0.138017E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172485382.7 | 59.44 | 0.00 | 0.00 |
| August | 0.155324E+10 | -0.138076E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172482766.3 | 59.44 | 0.00 | 0.00 |
| September | 0.157201E+10 | -0.140509E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -166928617.6 | 59.44 | 0.00 | 0.00 |
| October | 0.174709E+10 | -0.157430E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172781746.6 | 59.44 | 0.00 | 0.00 |
| November | 0.183341E+10 | -0.165930E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -174114908.1 | 59.44 | 0.00 | 0.00 |
| December | 0.202074E+10 | -0.183507E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -185674463.3 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.214034E+11 | -0.193233E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.208010E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.155266E+10 | -0.190408E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -185674463.3 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.208945E+10 | -0.138017E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -164718988.0 | 59.44 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: M N2 APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.208947E+10 | -0.190408E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -185389561.0 | 59.44 | 0.00 | 0.00 |
| February | 0.188282E+10 | -0.171812E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -164699607.5 | 59.44 | 0.00 | 0.00 |
| March | 0.201190E+10 | -0.183351E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -178388200.3 | 59.44 | 0.00 | 0.00 |
| April | 0.182491E+10 | -0.165722E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -167682129.7 | 59.44 | 0.00 | 0.00 |
| May | 0.174466E+10 | -0.157215E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172509664.9 | 59.44 | 0.00 | 0.00 |
| June | 0.157048E+10 | -0.140356E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -166920816.1 | 59.44 | 0.00 | 0.00 |
| July | 0.155266E+10 | -0.138017E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172485382.8 | 59.44 | 0.00 | 0.00 |
| August | 0.155324E+10 | -0.138076E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172482766.4 | 59.44 | 0.00 | 0.00 |
| September | 0.157201E+10 | -0.140509E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -166928772.1 | 59.44 | 0.00 | 0.00 |
| October | 0.174709E+10 | -0.157430E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172785169.5 | 59.44 | 0.00 | 0.00 |
| November | 0.183343E+10 | -0.165930E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -174129480.9 | 59.44 | 0.00 | 0.00 |
| December | 0.202074E+10 | -0.183507E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -185672063.7 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.214034E+11 | -0.193233E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.208007E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.155266E+10 | -0.190408E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -185672063.7 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.208947E+10 | -0.138017E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -164699607.5 | 59.44 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: M S1 APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.208180E+10 | -0.190408E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -177721358.0 | 59.44 | 0.00 | 0.00 |
| February | 0.187715E+10 | -0.171812E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -159024554.1 | 59.44 | 0.00 | 0.00 |
| March | 0.200847E+10 | -0.183351E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -174962830.7 | 59.44 | 0.00 | 0.00 |
| April | 0.182456E+10 | -0.165723E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -167334849.0 | 59.44 | 0.00 | 0.00 |
| May | 0.174466E+10 | -0.157215E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172509353.5 | 59.44 | 0.00 | 0.00 |
| June | 0.157048E+10 | -0.140355E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -166922154.9 | 59.44 | 0.00 | 0.00 |
| July | 0.155266E+10 | -0.138017E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172481129.0 | 59.44 | 0.00 | 0.00 |
| August | 0.155325E+10 | -0.138076E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172484577.9 | 59.44 | 0.00 | 0.00 |
| September | 0.157201E+10 | -0.140509E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -166921002.3 | 59.44 | 0.00 | 0.00 |
| October | 0.174683E+10 | -0.157430E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172530832.0 | 59.44 | 0.00 | 0.00 |
| November | 0.182861E+10 | -0.165930E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -169302983.3 | 59.44 | 0.00 | 0.00 |
| December | 0.201366E+10 | -0.183507E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -178592855.2 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.213741E+11 | -0.193233E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.205079E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.155266E+10 | -0.190408E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -178592855.2 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.208180E+10 | -0.138017E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -159024554.1 | 59.44 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: M S2 APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.208181E+10 | -0.190408E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -177729236.5 | 59.44 | 0.00 | 0.00 |
| February | 0.187712E+10 | -0.171812E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -158997840.4 | 59.44 | 0.00 | 0.00 |
| March | 0.200846E+10 | -0.183351E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -174953324.9 | 59.44 | 0.00 | 0.00 |
| April | 0.182456E+10 | -0.165723E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -167331402.0 | 59.44 | 0.00 | 0.00 |
| May | 0.174466E+10 | -0.157215E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172508409.0 | 59.44 | 0.00 | 0.00 |
| June | 0.157048E+10 | -0.140356E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -166920814.7 | 59.44 | 0.00 | 0.00 |
| July | 0.155266E+10 | -0.138017E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172485381.6 | 59.44 | 0.00 | 0.00 |
| August | 0.155324E+10 | -0.138076E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172482764.4 | 59.44 | 0.00 | 0.00 |
| September | 0.157201E+10 | -0.140509E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -166922826.5 | 59.44 | 0.00 | 0.00 |
| October | 0.174684E+10 | -0.157430E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -172531785.7 | 59.44 | 0.00 | 0.00 |
| November | 0.182861E+10 | -0.165930E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -169312127.4 | 59.44 | 0.00 | 0.00 |
| December | 0.201365E+10 | -0.183507E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -178586519.1 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.213741E+11 | -0.193233E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.205076E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.155266E+10 | -0.190408E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -178586519.1 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.208181E+10 | -0.138017E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -158997840.4 | 59.44 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: T SW APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.113504E+10 | -952037333.3 | 0.00 | 0.00 | 744.00 | 0.00 | -183002612.4 | 59.44 | 0.00 | 0.00 |
| February | 0.102349E+10 | -859059517.2 | 0.00 | 0.00 | 672.00 | 0.00 | -164427078.0 | 59.44 | 0.00 | 0.00 |
| March | 0.109764E+10 | -916752078.3 | 0.00 | 0.00 | 744.00 | 0.00 | -180891634.8 | 59.44 | 0.00 | 0.00 |
| April | 0.998982E+09 | -828613811.4 | 0.00 | 0.00 | 720.00 | 0.00 | -170368294.3 | 59.44 | 0.00 | 0.00 |
| May | 0.959518E+09 | -786069668.7 | 0.00 | 0.00 | 744.00 | 0.00 | -173448522.4 | 59.44 | 0.00 | 0.00 |
| June | 0.868735E+09 | -701780941.5 | 0.00 | 0.00 | 720.00 | 0.00 | -166953613.9 | 59.44 | 0.00 | 0.00 |
| July | 0.862575E+09 | -690083359.0 | 0.00 | 0.00 | 744.00 | 0.00 | -172491530.0 | 59.44 | 0.00 | 0.00 |
| August | 0.862917E+09 | -690381027.7 | 0.00 | 0.00 | 744.00 | 0.00 | -172536139.6 | 59.44 | 0.00 | 0.00 |
| September | 0.870003E+09 | -702547518.9 | 0.00 | 0.00 | 720.00 | 0.00 | -167455807.0 | 59.44 | 0.00 | 0.00 |
| October | 0.963191E+09 | -787149218.5 | 0.00 | 0.00 | 744.00 | 0.00 | -176041459.3 | 59.44 | 0.00 | 0.00 |
| November | 0.100479E+10 | -829648428.6 | 0.00 | 0.00 | 720.00 | 0.00 | -175140307.0 | 59.44 | 0.00 | 0.00 |
| December | 0.110084E+10 | -917531341.3 | 0.00 | 0.00 | 744.00 | 0.00 | -183313005.2 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.117477E+11 | -0.966165E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.208607E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.862575E+09 | -952037333.3 | 0.00 | 0.00 | 672.00 | 0.00 | -183313005.2 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.113504E+10 | -690083359.0 | 0.00 | 0.00 | 744.00 | 0.00 | -164427078.0 | 59.44 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: T NW APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.113819E+10 | -952034855.3 | 0.00 | 0.00 | 744.00 | 0.00 | -186157274.0 | 59.44 | 0.00 | 0.00 |
| February | 0.102589E+10 | -859061197.6 | 0.00 | 0.00 | 672.00 | 0.00 | -166825028.6 | 59.44 | 0.00 | 0.00 |
| March | 0.109948E+10 | -916752218.2 | 0.00 | 0.00 | 744.00 | 0.00 | -182726549.5 | 59.44 | 0.00 | 0.00 |
| April | 0.999460E+09 | -828613244.3 | 0.00 | 0.00 | 720.00 | 0.00 | -170846758.0 | 59.44 | 0.00 | 0.00 |
| May | 0.959509E+09 | -786078153.7 | 0.00 | 0.00 | 744.00 | 0.00 | -173430359.4 | 59.44 | 0.00 | 0.00 |
| June | 0.868733E+09 | -701773992.8 | 0.00 | 0.00 | 720.00 | 0.00 | -166958848.0 | 59.44 | 0.00 | 0.00 |
| July | 0.862571E+09 | -690086612.6 | 0.00 | 0.00 | 744.00 | 0.00 | -172484837.5 | 59.44 | 0.00 | 0.00 |
| August | 0.862921E+09 | -690378926.4 | 0.00 | 0.00 | 744.00 | 0.00 | -172542424.1 | 59.44 | 0.00 | 0.00 |
| September | 0.870148E+09 | -702539112.4 | 0.00 | 0.00 | 720.00 | 0.00 | -167609096.9 | 59.44 | 0.00 | 0.00 |
| October | 0.964490E+09 | -787148691.8 | 0.00 | 0.00 | 744.00 | 0.00 | -177341354.6 | 59.44 | 0.00 | 0.00 |
| November | 0.100780E+10 | -829646558.4 | 0.00 | 0.00 | 720.00 | 0.00 | -178153789.9 | 59.44 | 0.00 | 0.00 |
| December | 0.110395E+10 | -917533429.8 | 0.00 | 0.00 | 744.00 | 0.00 | -186420895.1 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.117631E+11 | -0.966165E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.210150E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.862571E+09 | -952034855.3 | 0.00 | 0.00 | 672.00 | 0.00 | -186420895.1 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.113819E+10 | -690086612.6 | 0.00 | 0.00 | 744.00 | 0.00 | -166825028.6 | 59.44 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: T SE APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.113499E+10 | -952037930.4 | 0.00 | 0.00 | 744.00 | 0.00 | -182948296.6 | 59.44 | 0.00 | 0.00 |
| February | 0.102323E+10 | -859058201.6 | 0.00 | 0.00 | 672.00 | 0.00 | -164170213.1 | 59.44 | 0.00 | 0.00 |
| March | 0.109739E+10 | -916755379.0 | 0.00 | 0.00 | 744.00 | 0.00 | -180637197.0 | 59.44 | 0.00 | 0.00 |
| April | 0.998649E+09 | -828608004.1 | 0.00 | 0.00 | 720.00 | 0.00 | -170040671.9 | 59.44 | 0.00 | 0.00 |
| May | 0.959350E+09 | -786071723.7 | 0.00 | 0.00 | 744.00 | 0.00 | -173277996.7 | 59.44 | 0.00 | 0.00 |
| June | 0.868741E+09 | -701772507.9 | 0.00 | 0.00 | 720.00 | 0.00 | -166968890.7 | 59.44 | 0.00 | 0.00 |
| July | 0.862571E+09 | -690087665.8 | 0.00 | 0.00 | 744.00 | 0.00 | -172483537.0 | 59.44 | 0.00 | 0.00 |
| August | 0.862915E+09 | -690376428.6 | 0.00 | 0.00 | 744.00 | 0.00 | -172538669.8 | 59.44 | 0.00 | 0.00 |
| September | 0.869949E+09 | -702544713.5 | 0.00 | 0.00 | 720.00 | 0.00 | -167404300.9 | 59.44 | 0.00 | 0.00 |
| October | 0.963157E+09 | -787152524.7 | 0.00 | 0.00 | 744.00 | 0.00 | -176004265.1 | 59.44 | 0.00 | 0.00 |
| November | 0.100465E+10 | -829649260.2 | 0.00 | 0.00 | 720.00 | 0.00 | -175001578.2 | 59.44 | 0.00 | 0.00 |
| December | 0.110079E+10 | -917533581.9 | 0.00 | 0.00 | 744.00 | 0.00 | -183261101.1 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.117464E+11 | -0.966165E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.208474E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.862571E+09 | -952037930.4 | 0.00 | 0.00 | 672.00 | 0.00 | -183261101.1 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.113499E+10 | -690087665.8 | 0.00 | 0.00 | 744.00 | 0.00 | -164170213.1 | 59.44 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: T NE APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.113845E+10 | -952037744.8 | 0.00 | 0.00 | 744.00 | 0.00 | -186408421.1 | 59.44 | 0.00 | 0.00 |
| February | 0.102591E+10 | -859058322.4 | 0.00 | 0.00 | 672.00 | 0.00 | -166853090.5 | 59.44 | 0.00 | 0.00 |
| March | 0.109941E+10 | -916752466.2 | 0.00 | 0.00 | 744.00 | 0.00 | -182656345.2 | 59.44 | 0.00 | 0.00 |
| April | 0.999110E+09 | -828612798.0 | 0.00 | 0.00 | 720.00 | 0.00 | -170496978.2 | 59.44 | 0.00 | 0.00 |
| May | 0.959344E+09 | -786068442.4 | 0.00 | 0.00 | 744.00 | 0.00 | -173275352.6 | 59.44 | 0.00 | 0.00 |
| June | 0.868736E+09 | -701782023.1 | 0.00 | 0.00 | 720.00 | 0.00 | -166953654.4 | 59.44 | 0.00 | 0.00 |
| July | 0.862575E+09 | -690083595.2 | 0.00 | 0.00 | 744.00 | 0.00 | -172490987.4 | 59.44 | 0.00 | 0.00 |
| August | 0.862920E+09 | -690382725.3 | 0.00 | 0.00 | 744.00 | 0.00 | -172536864.7 | 59.44 | 0.00 | 0.00 |
| September | 0.870070E+09 | -702539667.6 | 0.00 | 0.00 | 720.00 | 0.00 | -167530577.7 | 59.44 | 0.00 | 0.00 |
| October | 0.964388E+09 | -787150809.7 | 0.00 | 0.00 | 744.00 | 0.00 | -177237139.4 | 59.44 | 0.00 | 0.00 |
| November | 0.100807E+10 | -829648281.1 | 0.00 | 0.00 | 720.00 | 0.00 | -178426522.2 | 59.44 | 0.00 | 0.00 |
| December | 0.110409E+10 | -917534220.0 | 0.00 | 0.00 | 744.00 | 0.00 | -186559453.7 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.117631E+11 | -0.966165E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.210143E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.862575E+09 | -952037744.8 | 0.00 | 0.00 | 672.00 | 0.00 | -186559453.7 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.113845E+10 | -690083595.2 | 0.00 | 0.00 | 744.00 | 0.00 | -166853090.5 | 59.44 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: T N1 APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.113836E+10 | -952036301.7 | 0.00 | 0.00 | 744.00 | 0.00 | -186319264.6 | 59.44 | 0.00 | 0.00 |
| February | 0.102590E+10 | -859059959.5 | 0.00 | 0.00 | 672.00 | 0.00 | -166841537.5 | 59.44 | 0.00 | 0.00 |
| March | 0.109940E+10 | -916753547.0 | 0.00 | 0.00 | 744.00 | 0.00 | -182644929.8 | 59.44 | 0.00 | 0.00 |
| April | 0.998905E+09 | -828612085.8 | 0.00 | 0.00 | 720.00 | 0.00 | -170292440.9 | 59.44 | 0.00 | 0.00 |
| May | 0.959159E+09 | -786076434.3 | 0.00 | 0.00 | 744.00 | 0.00 | -173082299.6 | 59.44 | 0.00 | 0.00 |
| June | 0.868707E+09 | -701771544.1 | 0.00 | 0.00 | 720.00 | 0.00 | -166935556.7 | 59.44 | 0.00 | 0.00 |
| July | 0.862568E+09 | -690086897.4 | 0.00 | 0.00 | 744.00 | 0.00 | -172481463.7 | 59.44 | 0.00 | 0.00 |
| August | 0.862882E+09 | -690374653.9 | 0.00 | 0.00 | 744.00 | 0.00 | -172507681.2 | 59.44 | 0.00 | 0.00 |
| September | 0.869900E+09 | -702540315.3 | 0.00 | 0.00 | 720.00 | 0.00 | -167359329.8 | 59.44 | 0.00 | 0.00 |
| October | 0.963624E+09 | -787152068.3 | 0.00 | 0.00 | 744.00 | 0.00 | -176472325.1 | 59.44 | 0.00 | 0.00 |
| November | 0.100797E+10 | -829645579.1 | 0.00 | 0.00 | 720.00 | 0.00 | -178323502.6 | 59.44 | 0.00 | 0.00 |
| December | 0.110405E+10 | -917534152.6 | 0.00 | 0.00 | 744.00 | 0.00 | -186512044.6 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.117614E+11 | -0.966164E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.209977E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.862568E+09 | -952036301.7 | 0.00 | 0.00 | 672.00 | 0.00 | -186512044.6 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.113836E+10 | -690086897.4 | 0.00 | 0.00 | 744.00 | 0.00 | -166841537.5 | 59.44 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: T N2 APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.113836E+10 | -952036383.4 | 0.00 | 0.00 | 744.00 | 0.00 | -186328302.9 | 59.44 | 0.00 | 0.00 |
| February | 0.102589E+10 | -859059888.1 | 0.00 | 0.00 | 672.00 | 0.00 | -166834760.5 | 59.44 | 0.00 | 0.00 |
| March | 0.109938E+10 | -916753714.1 | 0.00 | 0.00 | 744.00 | 0.00 | -182629405.5 | 59.44 | 0.00 | 0.00 |
| April | 0.998886E+09 | -828611912.7 | 0.00 | 0.00 | 720.00 | 0.00 | -170273731.3 | 59.44 | 0.00 | 0.00 |
| May | 0.959152E+09 | -786077431.7 | 0.00 | 0.00 | 744.00 | 0.00 | -173074759.6 | 59.44 | 0.00 | 0.00 |
| June | 0.868708E+09 | -701771993.2 | 0.00 | 0.00 | 720.00 | 0.00 | -166935706.3 | 59.44 | 0.00 | 0.00 |
| July | 0.862568E+09 | -690087261.8 | 0.00 | 0.00 | 744.00 | 0.00 | -172481189.2 | 59.44 | 0.00 | 0.00 |
| August | 0.862882E+09 | -690374709.8 | 0.00 | 0.00 | 744.00 | 0.00 | -172507778.8 | 59.44 | 0.00 | 0.00 |
| September | 0.869900E+09 | -702540338.3 | 0.00 | 0.00 | 720.00 | 0.00 | -167359685.0 | 59.44 | 0.00 | 0.00 |
| October | 0.963642E+09 | -787151705.5 | 0.00 | 0.00 | 744.00 | 0.00 | -176490258.6 | 59.44 | 0.00 | 0.00 |
| November | 0.100798E+10 | -829645456.3 | 0.00 | 0.00 | 720.00 | 0.00 | -178334512.7 | 59.44 | 0.00 | 0.00 |
| December | 0.110405E+10 | -917533379.9 | 0.00 | 0.00 | 744.00 | 0.00 | -186514746.9 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.117614E+11 | -0.966164E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.209976E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.862568E+09 | -952036383.4 | 0.00 | 0.00 | 672.00 | 0.00 | -186514746.9 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.113836E+10 | -690087261.8 | 0.00 | 0.00 | 744.00 | 0.00 | -166834760.5 | 59.44 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: T S1 APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.113419E+10 | -952036320.8 | 0.00 | 0.00 | 744.00 | 0.00 | -182155038.3 | 59.44 | 0.00 | 0.00 |
| February | 0.102261E+10 | -859060062.5 | 0.00 | 0.00 | 672.00 | 0.00 | -163551856.0 | 59.44 | 0.00 | 0.00 |
| March | 0.109678E+10 | -916753167.7 | 0.00 | 0.00 | 744.00 | 0.00 | -180027689.2 | 59.44 | 0.00 | 0.00 |
| April | 0.998305E+09 | -828612495.7 | 0.00 | 0.00 | 720.00 | 0.00 | -169692786.8 | 59.44 | 0.00 | 0.00 |
| May | 0.959170E+09 | -786066163.7 | 0.00 | 0.00 | 744.00 | 0.00 | -173103468.1 | 59.44 | 0.00 | 0.00 |
| June | 0.868706E+09 | -701781599.7 | 0.00 | 0.00 | 720.00 | 0.00 | -166924268.2 | 59.44 | 0.00 | 0.00 |
| July | 0.862572E+09 | -690083273.9 | 0.00 | 0.00 | 744.00 | 0.00 | -172489068.8 | 59.44 | 0.00 | 0.00 |
| August | 0.862880E+09 | -690381553.4 | 0.00 | 0.00 | 744.00 | 0.00 | -172498217.1 | 59.44 | 0.00 | 0.00 |
| September | 0.869768E+09 | -702547005.4 | 0.00 | 0.00 | 720.00 | 0.00 | -167221449.5 | 59.44 | 0.00 | 0.00 |
| October | 0.962135E+09 | -787145177.4 | 0.00 | 0.00 | 744.00 | 0.00 | -174989882.8 | 59.44 | 0.00 | 0.00 |
| November | 0.100384E+10 | -829649730.3 | 0.00 | 0.00 | 720.00 | 0.00 | -174186682.3 | 59.44 | 0.00 | 0.00 |
| December | 0.110005E+10 | -917534355.9 | 0.00 | 0.00 | 744.00 | 0.00 | -182517689.8 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.117410E+11 | -0.966165E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.207936E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.862572E+09 | -952036320.8 | 0.00 | 0.00 | 672.00 | 0.00 | -182517689.8 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.113419E+10 | -690083273.9 | 0.00 | 0.00 | 744.00 | 0.00 | -163551856.0 | 59.44 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: T S2 APARTMENT WATER HEATER
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.113419E+10 | -952036324.1 | 0.00 | 0.00 | 744.00 | 0.00 | -182154863.5 | 59.44 | 0.00 | 0.00 |
| February | 0.102259E+10 | -859060071.1 | 0.00 | 0.00 | 672.00 | 0.00 | -163531949.4 | 59.44 | 0.00 | 0.00 |
| March | 0.109677E+10 | -916753198.2 | 0.00 | 0.00 | 744.00 | 0.00 | -180014126.3 | 59.44 | 0.00 | 0.00 |
| April | 0.998291E+09 | -828612424.1 | 0.00 | 0.00 | 720.00 | 0.00 | -169678516.9 | 59.44 | 0.00 | 0.00 |
| May | 0.959165E+09 | -786066748.6 | 0.00 | 0.00 | 744.00 | 0.00 | -173098169.1 | 59.44 | 0.00 | 0.00 |
| June | 0.868706E+09 | -701781594.1 | 0.00 | 0.00 | 720.00 | 0.00 | -166924653.9 | 59.44 | 0.00 | 0.00 |
| July | 0.862572E+09 | -690083278.7 | 0.00 | 0.00 | 744.00 | 0.00 | -172489036.9 | 59.44 | 0.00 | 0.00 |
| August | 0.862880E+09 | -690381537.9 | 0.00 | 0.00 | 744.00 | 0.00 | -172498387.9 | 59.44 | 0.00 | 0.00 |
| September | 0.869770E+09 | -702547011.1 | 0.00 | 0.00 | 720.00 | 0.00 | -167222606.7 | 59.44 | 0.00 | 0.00 |
| October | 0.962153E+09 | -787145659.4 | 0.00 | 0.00 | 744.00 | 0.00 | -175007203.1 | 59.44 | 0.00 | 0.00 |
| November | 0.100384E+10 | -829649897.7 | 0.00 | 0.00 | 720.00 | 0.00 | -174191294.4 | 59.44 | 0.00 | 0.00 |
| December | 0.110005E+10 | -917534205.2 | 0.00 | 0.00 | 744.00 | 0.00 | -182514167.0 | 59.44 | 0.00 | 0.00 |
| Annual Sum or Average | 0.117410E+11 | -0.966165E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.207932E+10 | 59.44 | 0.00 | 0.00 |
| Minimum of Months | 0.862572E+09 | -952036324.1 | 0.00 | 0.00 | 672.00 | 0.00 | -182514167.0 | 59.44 | 0.00 | 0.00 |
| Maximum of Months | 0.113419E+10 | -690083278.7 | 0.00 | 0.00 | 744.00 | 0.00 | -163531949.4 | 59.44 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
| January | 276.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 268.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 351.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 373.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 408.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 398.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 400.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 377.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 365.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 318.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 295.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 289.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 4125.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 268.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 408.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT GSW HEATING COIL
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.349459E+09 | 1137.31 | 28-JAN-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.329671E+09 | 1033.72 | 03-FEB-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.257001E+09 | 1101.24 | 02-MAR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 320471.43 | 94.01 | 13-APR-05:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 30736829.34 | 732.25 | 28-NOV-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.333299E+09 | 1055.22 | 27-DEC-07:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.130049E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.349459E+09 | 1137.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT GNW HEATING COIL
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.109124E+10 | 1468.27 | 28-JAN-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.887361E+09 | 1471.71 | 09-FEB-01:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.617240E+09 | 1378.39 | 02-MAR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 16396858.78 | 439.20 | 01-APR-01:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.152514E+09 | 1029.59 | 28-NOV-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.107900E+10 | 1325.57 | 31-DEC-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.384376E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.109124E+10 | 1471.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT OFFICE HEATING COIL
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 1740244.89 | 9002.91 | 27-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 873698.73 | 4991.88 | 03-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 1999823.13 | 9610.62 | 02-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 5766467.72 | 9610.62 | 27-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 10380234.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 5766467.72 | 9610.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT GNE HEATING COIL
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.109495E+10 | 1495.99 | 28-JAN-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.840969E+09 | 1467.36 | 09-FEB-01:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.585378E+09 | 1390.08 | 02-MAR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 13252103.44 | 440.23 | 01-APR-01:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.153740E+09 | 1057.38 | 28-NOV-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.107067E+10 | 1353.87 | 31-DEC-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.375896E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.109495E+10 | 1495.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT GN1 HEATING COIL
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.622359E+09 | 1001.73 | 28-JAN-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.478136E+09 | 977.62 | 03-FEB-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.283070E+09 | 904.12 | 02-MAR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 2350280.99 | 184.99 | 01-APR-01:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 45903716.31 | 661.62 | 28-NOV-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.636691E+09 | 901.81 | 31-DEC-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.206851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.636691E+09 | 1001.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT GN2 HEATING COIL
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.624426E+09 | 1002.74 | 28-JAN-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.476952E+09 | 979.02 | 03-FEB-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.283368E+09 | 903.44 | 02-MAR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 2323495.71 | 182.11 | 01-APR-01:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 46061327.40 | 664.26 | 28-NOV-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.637220E+09 | 904.28 | 31-DEC-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.207035E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.637220E+09 | 1002.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT GS1 HEATING COIL
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 58548135.06 | 660.20 | 27-JAN-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 54012996.47 | 543.08 | 03-FEB-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 56924348.91 | 658.49 | 02-MAR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 573120.28 | 110.80 | 28-NOV-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 66315419.29 | 626.57 | 27-DEC-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.236374E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 66315419.29 | 660.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT GS2 HEATING COIL
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 57750332.67 | 659.32 | 27-JAN-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 48532819.43 | 545.06 | 03-FEB-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 50064659.20 | 650.31 | 02-MAR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 376481.50 | 91.54 | 28-NOV-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 68305087.87 | 645.32 | 27-DEC-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.225029E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 68305087.87 | 659.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT MSW HEATING COIL
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.424039E+09 | 2363.26 | 26-JAN-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.213599E+09 | 1852.27 | 02-FEB-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 90009495.08 | 1751.35 | 02-MAR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.147573E+09 | 2272.41 | 28-NOV-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.646376E+09 | 2403.71 | 27-DEC-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.152160E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.646376E+09 | 2403.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT MNW HEATING COIL
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.171206E+10 | 3027.79 | 28-JAN-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.921027E+09 | 2820.49 | 09-FEB-01:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.263723E+09 | 2355.41 | 01-MAR-23:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.490994E+09 | 2575.24 | 28-NOV-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.215356E+10 | 2882.83 | 31-DEC-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.554137E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.215356E+10 | 3027.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT MSE HEATING COIL
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.425313E+09 | 2383.85 | 27-JAN-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.194673E+09 | 1903.52 | 02-FEB-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 81589051.10 | 1794.51 | 02-MAR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.150630E+09 | 2366.32 | 28-NOV-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.653003E+09 | 2413.61 | 27-DEC-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.150521E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.653003E+09 | 2413.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT MNE HEATING COIL
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.170346E+10 | 3114.19 | 28-JAN-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.847997E+09 | 2788.73 | 09-FEB-01:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.258578E+09 | 2454.27 | 01-MAR-23:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.497207E+09 | 2658.52 | 28-NOV-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.213589E+10 | 2970.41 | 31-DEC-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.544313E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.213589E+10 | 3114.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT MN1 HEATING COIL
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.701950E+09 | 1969.44 | 28-JAN-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.353998E+09 | 1696.53 | 03-FEB-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 84913819.53 | 1447.71 | 02-MAR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.133784E+09 | 1631.44 | 28-NOV-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.104827E+10 | 1831.01 | 31-DEC-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.232292E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.104827E+10 | 1969.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT MN2 HEATING COIL
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.707306E+09 | 1973.22 | 28-JAN-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.352143E+09 | 1700.34 | 03-FEB-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 84326433.52 | 1447.93 | 02-MAR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.134667E+09 | 1635.70 | 28-NOV-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.105068E+10 | 1835.35 | 31-DEC-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.232913E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.105068E+10 | 1973.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT MS1 HEATING COIL
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 50507596.31 | 1092.86 | 27-JAN-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 4493454.29 | 440.40 | 02-FEB-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 5804099.31 | 492.19 | 02-MAR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 18397262.81 | 975.78 | 28-NOV-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 80400581.97 | 1398.67 | 27-DEC-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.159603E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 80400581.97 | 1398.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT MS2 HEATING COIL
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 50497450.43 | 1095.91 | 27-JAN-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 4547382.17 | 440.31 | 02-FEB-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 5652224.72 | 484.94 | 02-MAR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 18740552.65 | 986.60 | 28-NOV-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 80969002.75 | 1398.12 | 27-DEC-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.160407E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 80969002.75 | 1398.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT TSW HEATING COIL
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.148831E+10 | 2481.60 | 28-JAN-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.105047E+10 | 2645.57 | 09-FEB-01:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.736007E+09 | 2198.34 | 02-MAR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.135967E+09 | 1712.01 | 11-APR-02:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 1818627.51 | 414.05 | 02-MAY-07:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 34812359.93 | 776.30 | 25-OCT-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.831588E+09 | 2356.27 | 28-NOV-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.174437E+10 | 2471.87 | 27-DEC-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.602335E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.174437E+10 | 2645.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT TNW HEATING COIL
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.222557E+10 | 2739.44 | 28-JAN-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.153302E+10 | 2850.20 | 09-FEB-01:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.993241E+09 | 2366.17 | 02-MAR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.160379E+09 | 1764.32 | 11-APR-02:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 1412960.84 | 262.73 | 02-MAY-05:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 371620.05 | 146.06 | 25-SEP-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 69320387.84 | 886.64 | 25-OCT-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.127832E+10 | 2425.63 | 28-NOV-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.258796E+10 | 2653.15 | 31-DEC-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.884959E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.258796E+10 | 2850.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT TSE HEATING COIL
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.146852E+10 | 2529.05 | 28-JAN-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.100556E+10 | 2643.25 | 09-FEB-01:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.702249E+09 | 2246.07 | 02-MAR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.120991E+09 | 1718.60 | 11-APR-02:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 935635.77 | 335.60 | 02-MAY-05:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 81769.17 | 91.52 | 25-SEP-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 39066764.10 | 825.57 | 25-OCT-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.823981E+09 | 2399.23 | 28-NOV-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.172533E+10 | 2482.97 | 27-DEC-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.588672E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.172533E+10 | 2643.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT TNE HEATING COIL
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.220992E+10 | 2780.74 | 28-JAN-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.146589E+10 | 2856.23 | 09-FEB-01:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.937166E+09 | 2403.11 | 02-MAR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.143391E+09 | 1768.74 | 11-APR-02:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 859613.95 | 351.34 | 02-MAY-05:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 455780.41 | 199.00 | 25-SEP-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 75309125.77 | 970.56 | 25-OCT-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.126017E+10 | 2462.17 | 28-NOV-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.257423E+10 | 2686.97 | 31-DEC-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.866739E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.257423E+10 | 2856.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT TN1 HEATING COIL
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.152603E+10 | 1998.71 | 28-JAN-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.100853E+10 | 1875.82 | 10-FEB-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.607975E+09 | 1774.16 | 02-MAR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 76875859.35 | 999.04 | 11-APR-02:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 15699697.09 | 561.90 | 25-OCT-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.833251E+09 | 1758.23 | 28-NOV-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.184836E+10 | 1912.70 | 31-DEC-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.591672E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.184836E+10 | 1998.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT TN2 HEATING COIL
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.152920E+10 | 2001.58 | 28-JAN-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.100775E+10 | 1878.34 | 10-FEB-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.608822E+09 | 1776.24 | 02-MAR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 77077962.89 | 999.58 | 11-APR-02:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 16362699.64 | 573.33 | 25-OCT-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.836948E+09 | 1760.41 | 28-NOV-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.185032E+10 | 1915.24 | 31-DEC-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.592649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.185032E+10 | 2001.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT TS1 HEATING COIL
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.848638E+09 | 1712.59 | 28-JAN-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.577626E+09 | 1656.21 | 09-FEB-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.384680E+09 | 1587.42 | 02-MAR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 56803369.54 | 927.67 | 11-APR-02:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 4139278.46 | 387.11 | 25-OCT-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.447425E+09 | 1686.80 | 28-NOV-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.105968E+10 | 1821.73 | 27-DEC-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.337899E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.105968E+10 | 1821.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT TS2 HEATING COIL
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.850632E+09 | 1716.72 | 28-JAN-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.577222E+09 | 1655.40 | 09-FEB-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.385709E+09 | 1590.62 | 02-MAR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 57001666.12 | 928.91 | 11-APR-02:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 4306674.75 | 394.89 | 25-OCT-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.449191E+09 | 1690.53 | 28-NOV-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.106155E+10 | 1822.13 | 27-DEC-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.338561E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.106155E+10 | 1822.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SPLIT GSW COOLING COIL
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 9704109.99 | 9704109.99 | 400.13 | 01-JAN-16:20 | 400.13 | 0.00 |
| February | 0.00 | 0.00 | 39923965.36 | 39923965.36 | 703.01 | 20-FEB-16:10 | 703.01 | 0.00 |
| March | 0.00 | 0.00 | 42682253.24 | 42682253.24 | 690.10 | 21-MAR-16:07 | 690.10 | 0.00 |
| April | 0.00 | 0.00 | 0.851135E+09 | 0.850013E+09 | 1903.20 | 21-APR-15:10 | 1903.20 | 0.00 |
| May | 0.00 | 0.00 | 0.216054E+10 | 0.211062E+10 | 2383.05 | 19-MAY-17:03 | 2383.05 | 0.00 |
| June | 0.00 | 0.00 | 0.337877E+10 | 0.326604E+10 | 2829.34 | 15-JUN-17:00 | 2829.34 | 0.00 |
| July | 0.00 | 0.00 | 0.437449E+10 | 0.371957E+10 | 2962.79 | 27-JUL-17:20 | 2690.33 | 0.00 |
| August | 0.00 | 0.00 | 0.414375E+10 | 0.374572E+10 | 2928.38 | 06-AUG-17:10 | 2894.83 | 0.00 |
| September | 0.00 | 0.00 | 0.384871E+10 | 0.347339E+10 | 2913.67 | 19-SEP-16:04 | 2913.67 | 0.00 |
| October | 0.00 | 0.00 | 0.233330E+10 | 0.219654E+10 | 2770.11 | 05-OCT-16:10 | 2708.12 | 0.00 |
| November | 0.00 | 0.00 | 0.615735E+09 | 0.613770E+09 | 1788.90 | 09-NOV-15:10 | 1788.90 | 0.00 |
| December | 0.00 | 0.00 | 3042689.94 | 3042689.94 | 301.57 | 16-DEC-16:10 | 301.57 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.218018E+11 | 0.200710E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 3042689.94 | 3042689.94 | 301.57 | 301.57 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.437449E+10 | 0.374572E+10 | 2962.79 | 2913.67 | 0.00 |
Report: CoilReportMonthly
For: SPLIT GNW COOLING COIL
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.540276E+09 | 0.539700E+09 | 1642.74 | 21-APR-16:30 | 1642.74 | 0.00 |
| May | 0.00 | 0.00 | 0.207126E+10 | 0.202096E+10 | 2357.89 | 19-MAY-17:17 | 2357.89 | 0.00 |
| June | 0.00 | 0.00 | 0.343273E+10 | 0.331739E+10 | 2921.78 | 15-JUN-17:00 | 2921.78 | 0.00 |
| July | 0.00 | 0.00 | 0.435994E+10 | 0.370392E+10 | 2979.30 | 26-JUL-17:50 | 2768.90 | 0.00 |
| August | 0.00 | 0.00 | 0.386957E+10 | 0.347992E+10 | 2823.47 | 06-AUG-17:30 | 2810.95 | 0.00 |
| September | 0.00 | 0.00 | 0.311589E+10 | 0.277416E+10 | 2349.99 | 20-SEP-17:00 | 2344.41 | 0.00 |
| October | 0.00 | 0.00 | 0.131243E+10 | 0.121102E+10 | 2260.46 | 05-OCT-16:20 | 2177.47 | 0.00 |
| November | 0.00 | 0.00 | 29621724.91 | 29354943.66 | 773.11 | 03-NOV-16:10 | 773.11 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.187317E+11 | 0.170764E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.435994E+10 | 0.370392E+10 | 2979.30 | 2921.78 | 0.00 |
Report: CoilReportMonthly
For: SPLIT OFFICE COOLING COIL
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.123335E+09 | 0.123335E+09 | 1193.32 | 12-JAN-15:00 | 1193.32 | 0.00 |
| February | 0.00 | 0.00 | 0.166851E+09 | 0.166851E+09 | 1467.63 | 22-FEB-14:00 | 1467.63 | 0.00 |
| March | 0.00 | 0.00 | 0.313669E+09 | 0.313669E+09 | 1465.48 | 16-MAR-14:40 | 1465.48 | 0.00 |
| April | 0.00 | 0.00 | 0.937931E+09 | 0.937619E+09 | 6763.26 | 19-APR-08:62 | 6763.26 | 0.00 |
| May | 0.00 | 0.00 | 0.187141E+10 | 0.182848E+10 | 7319.33 | 25-MAY-08:62 | 6005.76 | 0.00 |
| June | 0.00 | 0.00 | 0.270725E+10 | 0.262689E+10 | 7491.20 | 28-JUN-07:02 | 5955.26 | 0.00 |
| July | 0.00 | 0.00 | 0.301345E+10 | 0.265014E+10 | 8067.18 | 21-JUL-07:02 | 4519.82 | 0.00 |
| August | 0.00 | 0.00 | 0.327416E+10 | 0.297984E+10 | 7824.25 | 02-AUG-07:02 | 5364.15 | 0.00 |
| September | 0.00 | 0.00 | 0.276629E+10 | 0.256685E+10 | 7786.40 | 22-SEP-07:02 | 5412.17 | 0.00 |
| October | 0.00 | 0.00 | 0.196191E+10 | 0.186444E+10 | 7580.88 | 04-OCT-07:03 | 5798.15 | 0.00 |
| November | 0.00 | 0.00 | 0.833030E+09 | 0.824327E+09 | 6927.43 | 10-NOV-09:02 | 6927.43 | 0.00 |
| December | 0.00 | 0.00 | 0.121302E+09 | 0.121302E+09 | 784.29 | 07-DEC-15:10 | 784.29 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.180906E+11 | 0.170037E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.121302E+09 | 0.121302E+09 | 784.29 | 784.29 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.327416E+10 | 0.297984E+10 | 8067.18 | 6927.43 | 0.00 |
Report: CoilReportMonthly
For: SPLIT GNE COOLING COIL
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.544107E+09 | 0.543366E+09 | 1523.58 | 21-APR-15:10 | 1523.58 | 0.00 |
| May | 0.00 | 0.00 | 0.209473E+10 | 0.204183E+10 | 1982.22 | 19-MAY-17:05 | 1982.22 | 0.00 |
| June | 0.00 | 0.00 | 0.348277E+10 | 0.336375E+10 | 2539.77 | 15-JUN-17:00 | 2539.77 | 0.00 |
| July | 0.00 | 0.00 | 0.440176E+10 | 0.373790E+10 | 2652.13 | 26-JUL-18:00 | 2449.30 | 0.00 |
| August | 0.00 | 0.00 | 0.391001E+10 | 0.351310E+10 | 2495.27 | 07-AUG-18:00 | 2494.48 | 0.00 |
| September | 0.00 | 0.00 | 0.313346E+10 | 0.278284E+10 | 2087.87 | 15-SEP-16:10 | 1878.52 | 0.00 |
| October | 0.00 | 0.00 | 0.124906E+10 | 0.115222E+10 | 1920.49 | 03-OCT-15:10 | 1743.19 | 0.00 |
| November | 0.00 | 0.00 | 22244081.77 | 22124774.37 | 484.93 | 03-NOV-16:05 | 484.93 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.188381E+11 | 0.171571E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.440176E+10 | 0.373790E+10 | 2652.13 | 2539.77 | 0.00 |
Report: CoilReportMonthly
For: SPLIT GN1 COOLING COIL
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.472477E+09 | 0.471729E+09 | 1238.16 | 21-APR-17:07 | 1238.16 | 0.00 |
| May | 0.00 | 0.00 | 0.181798E+10 | 0.176864E+10 | 1658.77 | 19-MAY-17:17 | 1658.77 | 0.00 |
| June | 0.00 | 0.00 | 0.293106E+10 | 0.282240E+10 | 2088.89 | 15-JUN-17:05 | 2088.89 | 0.00 |
| July | 0.00 | 0.00 | 0.370986E+10 | 0.312014E+10 | 2181.09 | 26-JUL-18:00 | 2008.07 | 0.00 |
| August | 0.00 | 0.00 | 0.325848E+10 | 0.290414E+10 | 2064.29 | 07-AUG-18:00 | 2055.34 | 0.00 |
| September | 0.00 | 0.00 | 0.259377E+10 | 0.228370E+10 | 1708.64 | 22-SEP-16:03 | 1568.36 | 0.00 |
| October | 0.00 | 0.00 | 0.115065E+10 | 0.105417E+10 | 1617.51 | 04-OCT-16:40 | 1426.88 | 0.00 |
| November | 0.00 | 0.00 | 25928870.57 | 25515761.87 | 525.39 | 03-NOV-16:05 | 525.39 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.159602E+11 | 0.144504E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.370986E+10 | 0.312014E+10 | 2181.09 | 2088.89 | 0.00 |
Report: CoilReportMonthly
For: SPLIT GN2 COOLING COIL
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.476760E+09 | 0.476003E+09 | 1237.69 | 21-APR-17:10 | 1237.69 | 0.00 |
| May | 0.00 | 0.00 | 0.182152E+10 | 0.177213E+10 | 1652.60 | 19-MAY-17:13 | 1652.60 | 0.00 |
| June | 0.00 | 0.00 | 0.293382E+10 | 0.282511E+10 | 2083.94 | 15-JUN-17:08 | 2083.94 | 0.00 |
| July | 0.00 | 0.00 | 0.371164E+10 | 0.312181E+10 | 2177.26 | 26-JUL-18:00 | 2004.46 | 0.00 |
| August | 0.00 | 0.00 | 0.326044E+10 | 0.290597E+10 | 2058.00 | 07-AUG-18:00 | 2049.09 | 0.00 |
| September | 0.00 | 0.00 | 0.259478E+10 | 0.228457E+10 | 1702.84 | 22-SEP-16:03 | 1562.84 | 0.00 |
| October | 0.00 | 0.00 | 0.114789E+10 | 0.105179E+10 | 1610.30 | 04-OCT-16:30 | 1418.43 | 0.00 |
| November | 0.00 | 0.00 | 25569636.55 | 25173400.77 | 520.05 | 03-NOV-16:05 | 520.05 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.159724E+11 | 0.144625E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.371164E+10 | 0.312181E+10 | 2177.26 | 2083.94 | 0.00 |
Report: CoilReportMonthly
For: SPLIT GS1 COOLING COIL
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 37543219.50 | 37543219.50 | 522.02 | 01-JAN-13:50 | 522.02 | 0.00 |
| February | 0.00 | 0.00 | 57590343.57 | 57590343.57 | 615.21 | 22-FEB-14:00 | 615.21 | 0.00 |
| March | 0.00 | 0.00 | 62016491.57 | 62016491.57 | 596.52 | 21-MAR-16:07 | 596.52 | 0.00 |
| April | 0.00 | 0.00 | 0.830377E+09 | 0.828842E+09 | 1497.82 | 21-APR-15:10 | 1497.82 | 0.00 |
| May | 0.00 | 0.00 | 0.192512E+10 | 0.187589E+10 | 1685.70 | 19-MAY-17:03 | 1685.70 | 0.00 |
| June | 0.00 | 0.00 | 0.288958E+10 | 0.278305E+10 | 2013.83 | 05-JUN-17:00 | 2013.83 | 0.00 |
| July | 0.00 | 0.00 | 0.374018E+10 | 0.314978E+10 | 2149.90 | 26-JUL-17:30 | 2009.60 | 0.00 |
| August | 0.00 | 0.00 | 0.355221E+10 | 0.318723E+10 | 2139.82 | 07-AUG-16:01 | 2139.82 | 0.00 |
| September | 0.00 | 0.00 | 0.335603E+10 | 0.300795E+10 | 2236.01 | 20-SEP-14:10 | 2193.33 | 0.00 |
| October | 0.00 | 0.00 | 0.224109E+10 | 0.210625E+10 | 2143.79 | 03-OCT-14:00 | 2002.04 | 0.00 |
| November | 0.00 | 0.00 | 0.774218E+09 | 0.771379E+09 | 1537.47 | 09-NOV-14:00 | 1537.47 | 0.00 |
| December | 0.00 | 0.00 | 11906118.66 | 11906118.66 | 407.43 | 16-DEC-15:10 | 407.43 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.194779E+11 | 0.178794E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 11906118.66 | 11906118.66 | 407.43 | 407.43 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.374018E+10 | 0.318723E+10 | 2236.01 | 2193.33 | 0.00 |
Report: CoilReportMonthly
For: SPLIT GS2 COOLING COIL
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 39691928.25 | 39691928.25 | 508.59 | 01-JAN-13:50 | 508.59 | 0.00 |
| February | 0.00 | 0.00 | 62912517.27 | 62912517.27 | 650.41 | 22-FEB-14:00 | 650.41 | 0.00 |
| March | 0.00 | 0.00 | 74412797.82 | 74412797.82 | 635.74 | 21-MAR-16:10 | 635.74 | 0.00 |
| April | 0.00 | 0.00 | 0.929312E+09 | 0.927504E+09 | 1558.08 | 21-APR-15:10 | 1558.08 | 0.00 |
| May | 0.00 | 0.00 | 0.213892E+10 | 0.208474E+10 | 1793.95 | 21-MAY-16:02 | 1793.95 | 0.00 |
| June | 0.00 | 0.00 | 0.318100E+10 | 0.306565E+10 | 2119.64 | 05-JUN-17:00 | 2119.64 | 0.00 |
| July | 0.00 | 0.00 | 0.409008E+10 | 0.346797E+10 | 2251.55 | 26-JUL-17:50 | 2094.76 | 0.00 |
| August | 0.00 | 0.00 | 0.388124E+10 | 0.349532E+10 | 2300.96 | 06-AUG-17:10 | 2270.78 | 0.00 |
| September | 0.00 | 0.00 | 0.366690E+10 | 0.329866E+10 | 2327.67 | 20-SEP-14:10 | 2285.32 | 0.00 |
| October | 0.00 | 0.00 | 0.244667E+10 | 0.230328E+10 | 2278.95 | 01-OCT-15:10 | 2278.95 | 0.00 |
| November | 0.00 | 0.00 | 0.837227E+09 | 0.834043E+09 | 1583.70 | 09-NOV-14:00 | 1583.70 | 0.00 |
| December | 0.00 | 0.00 | 16948559.52 | 16948559.52 | 461.70 | 16-DEC-15:10 | 461.70 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.213653E+11 | 0.196711E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 16948559.52 | 16948559.52 | 461.70 | 461.70 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.409008E+10 | 0.349532E+10 | 2327.67 | 2285.32 | 0.00 |
Report: CoilReportMonthly
For: SPLIT MSW COOLING COIL
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.165829E+09 | 0.165829E+09 | 2244.19 | 12-JAN-15:00 | 2244.19 | 0.00 |
| February | 0.00 | 0.00 | 0.518470E+09 | 0.518470E+09 | 3666.49 | 20-FEB-16:10 | 3666.49 | 0.00 |
| March | 0.00 | 0.00 | 0.906645E+09 | 0.906645E+09 | 3719.56 | 14-MAR-16:15 | 3719.56 | 0.00 |
| April | 0.00 | 0.00 | 0.376733E+10 | 0.376179E+10 | 5650.37 | 21-APR-15:10 | 5650.37 | 0.00 |
| May | 0.00 | 0.00 | 0.637597E+10 | 0.623583E+10 | 6283.40 | 19-MAY-17:05 | 6283.40 | 0.00 |
| June | 0.00 | 0.00 | 0.856529E+10 | 0.828732E+10 | 6994.51 | 15-JUN-17:00 | 6994.51 | 0.00 |
| July | 0.00 | 0.00 | 0.985998E+10 | 0.840363E+10 | 6910.85 | 27-JUL-17:20 | 6264.47 | 0.00 |
| August | 0.00 | 0.00 | 0.865714E+10 | 0.782724E+10 | 6411.20 | 07-AUG-16:10 | 6411.20 | 0.00 |
| September | 0.00 | 0.00 | 0.751626E+10 | 0.678061E+10 | 6299.46 | 19-SEP-16:06 | 6299.46 | 0.00 |
| October | 0.00 | 0.00 | 0.456980E+10 | 0.430533E+10 | 6129.80 | 05-OCT-16:10 | 5993.52 | 0.00 |
| November | 0.00 | 0.00 | 0.130882E+10 | 0.130557E+10 | 4315.63 | 09-NOV-15:10 | 4315.63 | 0.00 |
| December | 0.00 | 0.00 | 39893794.53 | 39893794.53 | 1489.04 | 16-DEC-15:30 | 1489.04 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.522514E+11 | 0.485381E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 39893794.53 | 39893794.53 | 1489.04 | 1489.04 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.985998E+10 | 0.840363E+10 | 6994.51 | 6994.51 | 0.00 |
Report: CoilReportMonthly
For: SPLIT MNW COOLING COIL
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 18860912.49 | 18860912.49 | 928.11 | 21-FEB-17:05 | 928.11 | 0.00 |
| March | 0.00 | 0.00 | 0.148878E+09 | 0.148878E+09 | 1770.03 | 16-MAR-16:05 | 1770.03 | 0.00 |
| April | 0.00 | 0.00 | 0.285046E+10 | 0.284620E+10 | 5055.67 | 21-APR-16:17 | 5055.67 | 0.00 |
| May | 0.00 | 0.00 | 0.617008E+10 | 0.602920E+10 | 6229.46 | 19-MAY-17:17 | 6229.46 | 0.00 |
| June | 0.00 | 0.00 | 0.865832E+10 | 0.837566E+10 | 7216.39 | 15-JUN-17:00 | 7216.39 | 0.00 |
| July | 0.00 | 0.00 | 0.979870E+10 | 0.834214E+10 | 6932.42 | 27-JUL-17:20 | 6261.88 | 0.00 |
| August | 0.00 | 0.00 | 0.805177E+10 | 0.724009E+10 | 6161.14 | 06-AUG-17:30 | 6140.77 | 0.00 |
| September | 0.00 | 0.00 | 0.595247E+10 | 0.529253E+10 | 5169.69 | 01-SEP-16:13 | 4873.85 | 0.00 |
| October | 0.00 | 0.00 | 0.244049E+10 | 0.224990E+10 | 4983.91 | 05-OCT-16:20 | 4803.21 | 0.00 |
| November | 0.00 | 0.00 | 49122393.64 | 48938350.69 | 1576.72 | 03-NOV-16:05 | 1576.72 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.441392E+11 | 0.405924E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.979870E+10 | 0.837566E+10 | 7216.39 | 7216.39 | 0.00 |
Report: CoilReportMonthly
For: SPLIT MSE COOLING COIL
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.124328E+09 | 0.124328E+09 | 1815.13 | 12-JAN-15:00 | 1815.13 | 0.00 |
| February | 0.00 | 0.00 | 0.530410E+09 | 0.530410E+09 | 3143.01 | 20-FEB-15:00 | 3143.01 | 0.00 |
| March | 0.00 | 0.00 | 0.905959E+09 | 0.905959E+09 | 2986.48 | 16-MAR-14:10 | 2986.48 | 0.00 |
| April | 0.00 | 0.00 | 0.386004E+10 | 0.385378E+10 | 5305.20 | 21-APR-14:20 | 5305.20 | 0.00 |
| May | 0.00 | 0.00 | 0.645263E+10 | 0.630599E+10 | 5493.70 | 19-MAY-14:00 | 5493.70 | 0.00 |
| June | 0.00 | 0.00 | 0.867090E+10 | 0.838361E+10 | 5973.62 | 05-JUN-17:00 | 5973.62 | 0.00 |
| July | 0.00 | 0.00 | 0.995636E+10 | 0.847734E+10 | 5947.31 | 27-JUL-14:10 | 5259.63 | 0.00 |
| August | 0.00 | 0.00 | 0.874878E+10 | 0.789874E+10 | 5549.95 | 07-AUG-16:04 | 5549.95 | 0.00 |
| September | 0.00 | 0.00 | 0.755948E+10 | 0.680012E+10 | 5645.07 | 19-SEP-13:50 | 5645.07 | 0.00 |
| October | 0.00 | 0.00 | 0.444110E+10 | 0.418437E+10 | 5476.40 | 05-OCT-11:30 | 4872.49 | 0.00 |
| November | 0.00 | 0.00 | 0.125667E+10 | 0.125389E+10 | 3844.95 | 09-NOV-14:00 | 3844.95 | 0.00 |
| December | 0.00 | 0.00 | 25011021.75 | 25011021.75 | 992.77 | 16-DEC-15:10 | 992.77 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.525317E+11 | 0.487436E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 25011021.75 | 25011021.75 | 992.77 | 992.77 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.995636E+10 | 0.847734E+10 | 5973.62 | 5973.62 | 0.00 |
Report: CoilReportMonthly
For: SPLIT MNE COOLING COIL
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 14634576.07 | 14634576.07 | 550.19 | 21-FEB-17:10 | 550.19 | 0.00 |
| March | 0.00 | 0.00 | 0.126209E+09 | 0.126209E+09 | 1283.31 | 22-MAR-16:10 | 1283.31 | 0.00 |
| April | 0.00 | 0.00 | 0.292326E+10 | 0.291846E+10 | 4704.44 | 21-APR-15:10 | 4704.44 | 0.00 |
| May | 0.00 | 0.00 | 0.624666E+10 | 0.609932E+10 | 5131.58 | 19-MAY-17:05 | 5131.58 | 0.00 |
| June | 0.00 | 0.00 | 0.876405E+10 | 0.847236E+10 | 6124.07 | 15-JUN-17:00 | 6124.07 | 0.00 |
| July | 0.00 | 0.00 | 0.989448E+10 | 0.841607E+10 | 5997.36 | 26-JUL-18:00 | 5533.55 | 0.00 |
| August | 0.00 | 0.00 | 0.814421E+10 | 0.731154E+10 | 5349.97 | 07-AUG-18:00 | 5349.97 | 0.00 |
| September | 0.00 | 0.00 | 0.599796E+10 | 0.531056E+10 | 4332.44 | 15-SEP-16:10 | 3873.04 | 0.00 |
| October | 0.00 | 0.00 | 0.229526E+10 | 0.211305E+10 | 3974.88 | 03-OCT-15:10 | 3597.93 | 0.00 |
| November | 0.00 | 0.00 | 39366854.97 | 39259034.11 | 923.57 | 09-NOV-15:10 | 923.57 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.444461E+11 | 0.408215E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.989448E+10 | 0.847236E+10 | 6124.07 | 6124.07 | 0.00 |
Report: CoilReportMonthly
For: SPLIT MN1 COOLING COIL
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 10387782.80 | 10387782.80 | 472.79 | 21-FEB-17:05 | 472.79 | 0.00 |
| March | 0.00 | 0.00 | 0.132104E+09 | 0.132100E+09 | 1148.06 | 22-MAR-16:05 | 1148.06 | 0.00 |
| April | 0.00 | 0.00 | 0.236148E+10 | 0.235688E+10 | 3530.23 | 21-APR-16:15 | 3530.23 | 0.00 |
| May | 0.00 | 0.00 | 0.499850E+10 | 0.487251E+10 | 4063.12 | 19-MAY-17:25 | 4063.12 | 0.00 |
| June | 0.00 | 0.00 | 0.692757E+10 | 0.667609E+10 | 4795.27 | 15-JUN-17:03 | 4795.27 | 0.00 |
| July | 0.00 | 0.00 | 0.801575E+10 | 0.674640E+10 | 4781.48 | 26-JUL-18:00 | 4400.54 | 0.00 |
| August | 0.00 | 0.00 | 0.662864E+10 | 0.590007E+10 | 4298.46 | 07-AUG-18:00 | 4290.82 | 0.00 |
| September | 0.00 | 0.00 | 0.495316E+10 | 0.434861E+10 | 3445.06 | 15-SEP-16:10 | 3069.87 | 0.00 |
| October | 0.00 | 0.00 | 0.218651E+10 | 0.199837E+10 | 3287.75 | 04-OCT-16:17 | 2885.22 | 0.00 |
| November | 0.00 | 0.00 | 46801837.61 | 46419415.81 | 1015.99 | 03-NOV-16:10 | 1015.99 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.362609E+11 | 0.330878E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.801575E+10 | 0.674640E+10 | 4795.27 | 4795.27 | 0.00 |
Report: CoilReportMonthly
For: SPLIT MN2 COOLING COIL
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 11275099.49 | 11275099.49 | 483.09 | 21-FEB-17:05 | 483.09 | 0.00 |
| March | 0.00 | 0.00 | 0.135776E+09 | 0.135772E+09 | 1157.89 | 22-MAR-16:10 | 1157.89 | 0.00 |
| April | 0.00 | 0.00 | 0.237302E+10 | 0.236842E+10 | 3528.13 | 21-APR-16:15 | 3528.13 | 0.00 |
| May | 0.00 | 0.00 | 0.500382E+10 | 0.487772E+10 | 4048.36 | 19-MAY-17:17 | 4048.36 | 0.00 |
| June | 0.00 | 0.00 | 0.693220E+10 | 0.668064E+10 | 4781.29 | 15-JUN-17:03 | 4781.29 | 0.00 |
| July | 0.00 | 0.00 | 0.801937E+10 | 0.674976E+10 | 4769.07 | 26-JUL-18:00 | 4388.90 | 0.00 |
| August | 0.00 | 0.00 | 0.663253E+10 | 0.590366E+10 | 4284.01 | 07-AUG-18:00 | 4276.42 | 0.00 |
| September | 0.00 | 0.00 | 0.495570E+10 | 0.435074E+10 | 3446.48 | 15-SEP-16:10 | 3071.40 | 0.00 |
| October | 0.00 | 0.00 | 0.218245E+10 | 0.199516E+10 | 3270.24 | 04-OCT-16:17 | 2869.25 | 0.00 |
| November | 0.00 | 0.00 | 46620366.92 | 46274337.78 | 999.72 | 03-NOV-16:10 | 999.72 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.362928E+11 | 0.331194E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.801937E+10 | 0.674976E+10 | 4781.29 | 4781.29 | 0.00 |
Report: CoilReportMonthly
For: SPLIT MS1 COOLING COIL
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.390605E+09 | 0.390605E+09 | 2209.31 | 12-JAN-15:00 | 2209.31 | 0.00 |
| February | 0.00 | 0.00 | 0.698667E+09 | 0.698667E+09 | 3075.05 | 20-FEB-15:00 | 3075.05 | 0.00 |
| March | 0.00 | 0.00 | 0.104374E+10 | 0.104372E+10 | 2842.45 | 16-MAR-15:10 | 2842.45 | 0.00 |
| April | 0.00 | 0.00 | 0.333032E+10 | 0.332433E+10 | 4100.92 | 21-APR-15:10 | 4100.92 | 0.00 |
| May | 0.00 | 0.00 | 0.520749E+10 | 0.508214E+10 | 4138.38 | 19-MAY-14:00 | 4138.38 | 0.00 |
| June | 0.00 | 0.00 | 0.683418E+10 | 0.658732E+10 | 4632.82 | 05-JUN-17:00 | 4632.82 | 0.00 |
| July | 0.00 | 0.00 | 0.807759E+10 | 0.680770E+10 | 4669.39 | 26-JUL-18:00 | 4317.14 | 0.00 |
| August | 0.00 | 0.00 | 0.723828E+10 | 0.648933E+10 | 4449.91 | 07-AUG-16:10 | 4449.91 | 0.00 |
| September | 0.00 | 0.00 | 0.653574E+10 | 0.585104E+10 | 4710.63 | 19-SEP-14:10 | 4710.63 | 0.00 |
| October | 0.00 | 0.00 | 0.445216E+10 | 0.418452E+10 | 4736.03 | 18-OCT-13:20 | 4288.80 | 0.00 |
| November | 0.00 | 0.00 | 0.169126E+10 | 0.168615E+10 | 3639.94 | 09-NOV-14:00 | 3639.94 | 0.00 |
| December | 0.00 | 0.00 | 0.187934E+09 | 0.187934E+09 | 1710.40 | 16-DEC-14:40 | 1710.40 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.456880E+11 | 0.423335E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.187934E+09 | 0.187934E+09 | 1710.40 | 1710.40 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.807759E+10 | 0.680770E+10 | 4736.03 | 4710.63 | 0.00 |
Report: CoilReportMonthly
For: SPLIT MS2 COOLING COIL
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.390922E+09 | 0.390922E+09 | 2209.59 | 12-JAN-15:00 | 2209.59 | 0.00 |
| February | 0.00 | 0.00 | 0.707885E+09 | 0.707885E+09 | 3087.17 | 20-FEB-15:00 | 3087.17 | 0.00 |
| March | 0.00 | 0.00 | 0.105288E+10 | 0.105286E+10 | 2842.73 | 16-MAR-15:10 | 2842.73 | 0.00 |
| April | 0.00 | 0.00 | 0.334124E+10 | 0.333524E+10 | 4105.61 | 21-APR-15:10 | 4105.61 | 0.00 |
| May | 0.00 | 0.00 | 0.521286E+10 | 0.508742E+10 | 4146.43 | 19-MAY-14:00 | 4146.43 | 0.00 |
| June | 0.00 | 0.00 | 0.683889E+10 | 0.659195E+10 | 4622.38 | 05-JUN-17:00 | 4622.38 | 0.00 |
| July | 0.00 | 0.00 | 0.808129E+10 | 0.681114E+10 | 4657.74 | 26-JUL-18:00 | 4306.16 | 0.00 |
| August | 0.00 | 0.00 | 0.724212E+10 | 0.649292E+10 | 4452.15 | 29-AUG-13:00 | 3814.06 | 0.00 |
| September | 0.00 | 0.00 | 0.653784E+10 | 0.585287E+10 | 4715.80 | 19-SEP-14:00 | 4715.80 | 0.00 |
| October | 0.00 | 0.00 | 0.444651E+10 | 0.417946E+10 | 4744.59 | 18-OCT-13:20 | 4297.48 | 0.00 |
| November | 0.00 | 0.00 | 0.169334E+10 | 0.168830E+10 | 3648.73 | 09-NOV-14:00 | 3648.73 | 0.00 |
| December | 0.00 | 0.00 | 0.191090E+09 | 0.191090E+09 | 1725.33 | 16-DEC-14:50 | 1725.33 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.457369E+11 | 0.423820E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.191090E+09 | 0.191090E+09 | 1725.33 | 1725.33 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.808129E+10 | 0.681114E+10 | 4744.59 | 4715.80 | 0.00 |
Report: CoilReportMonthly
For: SPLIT TSW COOLING COIL
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.141106E+09 | 0.141106E+09 | 1732.87 | 12-JAN-15:10 | 1732.87 | 0.00 |
| February | 0.00 | 0.00 | 0.304679E+09 | 0.304679E+09 | 2261.10 | 20-FEB-15:30 | 2261.10 | 0.00 |
| March | 0.00 | 0.00 | 0.481318E+09 | 0.481318E+09 | 2404.80 | 14-MAR-16:15 | 2404.80 | 0.00 |
| April | 0.00 | 0.00 | 0.190515E+10 | 0.190354E+10 | 3780.36 | 21-APR-15:10 | 3780.36 | 0.00 |
| May | 0.00 | 0.00 | 0.339833E+10 | 0.333404E+10 | 4174.61 | 19-MAY-16:40 | 4174.61 | 0.00 |
| June | 0.00 | 0.00 | 0.489570E+10 | 0.476326E+10 | 4698.93 | 15-JUN-16:40 | 4698.93 | 0.00 |
| July | 0.00 | 0.00 | 0.558416E+10 | 0.482838E+10 | 4512.97 | 27-JUL-17:20 | 4116.13 | 0.00 |
| August | 0.00 | 0.00 | 0.477189E+10 | 0.436803E+10 | 4333.21 | 07-AUG-16:10 | 4333.21 | 0.00 |
| September | 0.00 | 0.00 | 0.388857E+10 | 0.355799E+10 | 4142.03 | 19-SEP-15:30 | 4142.03 | 0.00 |
| October | 0.00 | 0.00 | 0.206650E+10 | 0.195948E+10 | 4029.63 | 05-OCT-16:10 | 3951.00 | 0.00 |
| November | 0.00 | 0.00 | 0.558310E+09 | 0.557144E+09 | 2597.79 | 03-NOV-15:30 | 2597.79 | 0.00 |
| December | 0.00 | 0.00 | 90709521.82 | 90709521.82 | 1238.27 | 16-DEC-15:30 | 1238.27 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.280864E+11 | 0.262897E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 90709521.82 | 90709521.82 | 1238.27 | 1238.27 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.558416E+10 | 0.482838E+10 | 4698.93 | 4698.93 | 0.00 |
Report: CoilReportMonthly
For: SPLIT TNW COOLING COIL
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 30159295.92 | 30159295.92 | 758.28 | 19-FEB-17:10 | 758.28 | 0.00 |
| March | 0.00 | 0.00 | 0.125231E+09 | 0.125231E+09 | 1292.11 | 14-MAR-16:40 | 1292.11 | 0.00 |
| April | 0.00 | 0.00 | 0.147505E+10 | 0.147385E+10 | 3376.65 | 21-APR-15:10 | 3376.65 | 0.00 |
| May | 0.00 | 0.00 | 0.328737E+10 | 0.322241E+10 | 4139.66 | 19-MAY-17:05 | 4139.66 | 0.00 |
| June | 0.00 | 0.00 | 0.494307E+10 | 0.480761E+10 | 4825.56 | 15-JUN-17:00 | 4825.56 | 0.00 |
| July | 0.00 | 0.00 | 0.555050E+10 | 0.479169E+10 | 4526.45 | 26-JUL-17:40 | 4245.64 | 0.00 |
| August | 0.00 | 0.00 | 0.443353E+10 | 0.403663E+10 | 4155.47 | 07-AUG-16:04 | 4155.47 | 0.00 |
| September | 0.00 | 0.00 | 0.305778E+10 | 0.276099E+10 | 3462.39 | 01-SEP-16:13 | 3304.67 | 0.00 |
| October | 0.00 | 0.00 | 0.107332E+10 | 0.994596E+09 | 3310.73 | 05-OCT-16:20 | 3206.26 | 0.00 |
| November | 0.00 | 0.00 | 30048566.73 | 30011737.80 | 961.78 | 09-NOV-16:10 | 961.78 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.240061E+11 | 0.222732E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.555050E+10 | 0.480761E+10 | 4825.56 | 4825.56 | 0.00 |
Report: CoilReportMonthly
For: SPLIT TSE COOLING COIL
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 93692766.54 | 93692766.54 | 1423.37 | 12-JAN-15:00 | 1423.37 | 0.00 |
| February | 0.00 | 0.00 | 0.279669E+09 | 0.279669E+09 | 1915.63 | 20-FEB-15:00 | 1915.63 | 0.00 |
| March | 0.00 | 0.00 | 0.441107E+09 | 0.441107E+09 | 1825.35 | 21-MAR-15:10 | 1825.35 | 0.00 |
| April | 0.00 | 0.00 | 0.189776E+10 | 0.189572E+10 | 3542.46 | 21-APR-14:10 | 3542.46 | 0.00 |
| May | 0.00 | 0.00 | 0.341554E+10 | 0.334700E+10 | 3777.17 | 19-MAY-14:00 | 3777.17 | 0.00 |
| June | 0.00 | 0.00 | 0.495418E+10 | 0.481389E+10 | 3989.79 | 15-JUN-15:10 | 3989.79 | 0.00 |
| July | 0.00 | 0.00 | 0.563695E+10 | 0.486327E+10 | 4069.81 | 26-JUL-14:00 | 3834.05 | 0.00 |
| August | 0.00 | 0.00 | 0.482379E+10 | 0.440447E+10 | 3698.32 | 27-AUG-13:00 | 3698.32 | 0.00 |
| September | 0.00 | 0.00 | 0.390446E+10 | 0.355705E+10 | 3792.33 | 20-SEP-13:30 | 3726.57 | 0.00 |
| October | 0.00 | 0.00 | 0.199026E+10 | 0.188438E+10 | 3670.33 | 03-OCT-13:50 | 3463.55 | 0.00 |
| November | 0.00 | 0.00 | 0.505082E+09 | 0.504059E+09 | 2262.17 | 09-NOV-14:00 | 2262.17 | 0.00 |
| December | 0.00 | 0.00 | 57032238.27 | 57032238.27 | 869.53 | 16-DEC-14:40 | 869.53 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.279995E+11 | 0.261413E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 57032238.27 | 57032238.27 | 869.53 | 869.53 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.563695E+10 | 0.486327E+10 | 4069.81 | 3989.79 | 0.00 |
Report: CoilReportMonthly
For: SPLIT TNE COOLING COIL
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 16454216.33 | 16454216.33 | 361.50 | 20-FEB-15:10 | 361.50 | 0.00 |
| March | 0.00 | 0.00 | 84579122.44 | 84579122.44 | 801.37 | 22-MAR-16:05 | 801.37 | 0.00 |
| April | 0.00 | 0.00 | 0.146300E+10 | 0.146154E+10 | 3097.82 | 21-APR-15:10 | 3097.82 | 0.00 |
| May | 0.00 | 0.00 | 0.330455E+10 | 0.323521E+10 | 3472.01 | 19-MAY-14:00 | 3472.01 | 0.00 |
| June | 0.00 | 0.00 | 0.500239E+10 | 0.485929E+10 | 4021.48 | 15-JUN-17:00 | 4021.48 | 0.00 |
| July | 0.00 | 0.00 | 0.560299E+10 | 0.482720E+10 | 3830.72 | 26-JUL-17:40 | 3575.67 | 0.00 |
| August | 0.00 | 0.00 | 0.448591E+10 | 0.407307E+10 | 3522.97 | 07-AUG-16:10 | 3522.97 | 0.00 |
| September | 0.00 | 0.00 | 0.307027E+10 | 0.275462E+10 | 2890.03 | 15-SEP-13:00 | 2661.87 | 0.00 |
| October | 0.00 | 0.00 | 0.987686E+09 | 0.909861E+09 | 2699.48 | 03-OCT-14:10 | 2488.73 | 0.00 |
| November | 0.00 | 0.00 | 20626085.15 | 20593154.54 | 574.90 | 09-NOV-15:10 | 574.90 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.240385E+11 | 0.222424E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.560299E+10 | 0.485929E+10 | 4021.48 | 4021.48 | 0.00 |
Report: CoilReportMonthly
For: SPLIT TN1 COOLING COIL
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 6850271.42 | 6850271.42 | 238.85 | 21-FEB-17:10 | 238.85 | 0.00 |
| March | 0.00 | 0.00 | 49981894.58 | 49981894.58 | 626.47 | 22-MAR-16:10 | 626.47 | 0.00 |
| April | 0.00 | 0.00 | 0.111704E+10 | 0.111594E+10 | 2360.05 | 21-APR-15:10 | 2360.05 | 0.00 |
| May | 0.00 | 0.00 | 0.261516E+10 | 0.255711E+10 | 2710.89 | 19-MAY-17:03 | 2710.89 | 0.00 |
| June | 0.00 | 0.00 | 0.400147E+10 | 0.387871E+10 | 3266.24 | 15-JUN-17:00 | 3266.24 | 0.00 |
| July | 0.00 | 0.00 | 0.459211E+10 | 0.392728E+10 | 3154.41 | 26-JUL-17:50 | 2937.17 | 0.00 |
| August | 0.00 | 0.00 | 0.367233E+10 | 0.331188E+10 | 2893.78 | 07-AUG-16:01 | 2893.78 | 0.00 |
| September | 0.00 | 0.00 | 0.249904E+10 | 0.222357E+10 | 2333.31 | 01-SEP-15:10 | 2148.22 | 0.00 |
| October | 0.00 | 0.00 | 0.812069E+09 | 0.742357E+09 | 2220.49 | 03-OCT-14:10 | 2038.08 | 0.00 |
| November | 0.00 | 0.00 | 13281542.00 | 13271519.50 | 425.79 | 09-NOV-15:10 | 425.79 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.193793E+11 | 0.178269E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.459211E+10 | 0.392728E+10 | 3266.24 | 3266.24 | 0.00 |
Report: CoilReportMonthly
For: SPLIT TN2 COOLING COIL
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 7241836.26 | 7241836.26 | 239.74 | 21-FEB-17:10 | 239.74 | 0.00 |
| March | 0.00 | 0.00 | 50854151.87 | 50854151.87 | 628.58 | 22-MAR-16:10 | 628.58 | 0.00 |
| April | 0.00 | 0.00 | 0.112349E+10 | 0.112238E+10 | 2361.36 | 21-APR-15:10 | 2361.36 | 0.00 |
| May | 0.00 | 0.00 | 0.262027E+10 | 0.256209E+10 | 2692.82 | 19-MAY-17:05 | 2692.82 | 0.00 |
| June | 0.00 | 0.00 | 0.400463E+10 | 0.388178E+10 | 3249.15 | 15-JUN-17:00 | 3249.15 | 0.00 |
| July | 0.00 | 0.00 | 0.459473E+10 | 0.392959E+10 | 3139.14 | 26-JUL-17:50 | 2922.63 | 0.00 |
| August | 0.00 | 0.00 | 0.367534E+10 | 0.331455E+10 | 2881.37 | 07-AUG-16:01 | 2881.37 | 0.00 |
| September | 0.00 | 0.00 | 0.250266E+10 | 0.222669E+10 | 2330.17 | 01-SEP-15:10 | 2146.07 | 0.00 |
| October | 0.00 | 0.00 | 0.813965E+09 | 0.744304E+09 | 2220.72 | 03-OCT-14:10 | 2038.77 | 0.00 |
| November | 0.00 | 0.00 | 13653374.42 | 13642552.95 | 434.88 | 09-NOV-15:10 | 434.88 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.194068E+11 | 0.178531E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.459473E+10 | 0.392959E+10 | 3249.15 | 3249.15 | 0.00 |
Report: CoilReportMonthly
For: SPLIT TS1 COOLING COIL
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.141384E+09 | 0.141384E+09 | 1421.13 | 12-JAN-15:00 | 1421.13 | 0.00 |
| February | 0.00 | 0.00 | 0.267201E+09 | 0.267201E+09 | 1758.77 | 20-FEB-15:00 | 1758.77 | 0.00 |
| March | 0.00 | 0.00 | 0.367399E+09 | 0.367399E+09 | 1675.94 | 16-MAR-15:10 | 1675.94 | 0.00 |
| April | 0.00 | 0.00 | 0.154644E+10 | 0.154478E+10 | 2775.34 | 21-APR-14:30 | 2775.34 | 0.00 |
| May | 0.00 | 0.00 | 0.272633E+10 | 0.266908E+10 | 2943.89 | 19-MAY-14:00 | 2943.89 | 0.00 |
| June | 0.00 | 0.00 | 0.395265E+10 | 0.383303E+10 | 3198.71 | 15-JUN-16:01 | 3198.71 | 0.00 |
| July | 0.00 | 0.00 | 0.462626E+10 | 0.396395E+10 | 3249.44 | 26-JUL-14:10 | 3055.39 | 0.00 |
| August | 0.00 | 0.00 | 0.401374E+10 | 0.364576E+10 | 3070.77 | 07-AUG-16:04 | 3070.77 | 0.00 |
| September | 0.00 | 0.00 | 0.334444E+10 | 0.303323E+10 | 3227.16 | 19-SEP-14:10 | 3227.16 | 0.00 |
| October | 0.00 | 0.00 | 0.183941E+10 | 0.173880E+10 | 3191.08 | 03-OCT-13:50 | 3010.65 | 0.00 |
| November | 0.00 | 0.00 | 0.519781E+09 | 0.518779E+09 | 2139.70 | 09-NOV-14:20 | 2139.70 | 0.00 |
| December | 0.00 | 0.00 | 96223857.49 | 96223857.49 | 1010.52 | 16-DEC-14:50 | 1010.52 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.234413E+11 | 0.218196E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 96223857.49 | 96223857.49 | 1010.52 | 1010.52 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.462626E+10 | 0.396395E+10 | 3249.44 | 3227.16 | 0.00 |
Report: CoilReportMonthly
For: SPLIT TS2 COOLING COIL
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.143303E+09 | 0.143303E+09 | 1422.89 | 12-JAN-15:00 | 1422.89 | 0.00 |
| February | 0.00 | 0.00 | 0.270908E+09 | 0.270908E+09 | 1766.26 | 20-FEB-15:00 | 1766.26 | 0.00 |
| March | 0.00 | 0.00 | 0.372776E+09 | 0.372776E+09 | 1676.57 | 16-MAR-15:10 | 1676.57 | 0.00 |
| April | 0.00 | 0.00 | 0.155369E+10 | 0.155202E+10 | 2782.26 | 21-APR-14:20 | 2782.26 | 0.00 |
| May | 0.00 | 0.00 | 0.273171E+10 | 0.267432E+10 | 2950.62 | 19-MAY-14:00 | 2950.62 | 0.00 |
| June | 0.00 | 0.00 | 0.395597E+10 | 0.383624E+10 | 3187.25 | 15-JUN-16:01 | 3187.25 | 0.00 |
| July | 0.00 | 0.00 | 0.462898E+10 | 0.396635E+10 | 3255.35 | 26-JUL-14:10 | 3061.50 | 0.00 |
| August | 0.00 | 0.00 | 0.401671E+10 | 0.364844E+10 | 3058.28 | 07-AUG-16:04 | 3058.28 | 0.00 |
| September | 0.00 | 0.00 | 0.334760E+10 | 0.303600E+10 | 3231.61 | 19-SEP-14:00 | 3231.61 | 0.00 |
| October | 0.00 | 0.00 | 0.184040E+10 | 0.173997E+10 | 3193.13 | 03-OCT-13:50 | 3013.03 | 0.00 |
| November | 0.00 | 0.00 | 0.524000E+09 | 0.523000E+09 | 2146.48 | 09-NOV-14:10 | 2146.48 | 0.00 |
| December | 0.00 | 0.00 | 98335325.17 | 98335325.17 | 1015.80 | 16-DEC-14:40 | 1015.80 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.234844E+11 | 0.218617E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 98335325.17 | 98335325.17 | 1015.80 | 1015.80 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.462898E+10 | 0.396635E+10 | 3255.35 | 3231.61 | 0.00 |
Report: FanReportMonthly
For: SPLIT GSW SUPPLY FAN
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 18880493.31 | 0.42 | 58.79 | 28-JAN-06:00 | 1.06 |
| February | 20422366.03 | 0.43 | 59.06 | 20-FEB-16:10 | 1.23 |
| March | 16906551.86 | 0.37 | 58.35 | 21-MAR-16:07 | 1.23 |
| April | 71501649.19 | 0.60 | 160.85 | 21-APR-15:10 | 1.17 |
| May | 0.178287E+09 | 1.04 | 199.39 | 19-MAY-17:05 | 1.16 |
| June | 0.280123E+09 | 1.19 | 251.09 | 15-JUN-17:00 | 1.14 |
| July | 0.339993E+09 | 1.18 | 235.97 | 26-JUL-17:30 | 1.14 |
| August | 0.325968E+09 | 1.18 | 242.91 | 07-AUG-16:10 | 1.13 |
| September | 0.300107E+09 | 1.19 | 238.78 | 19-SEP-16:10 | 1.14 |
| October | 0.184783E+09 | 1.09 | 221.58 | 01-OCT-15:10 | 1.15 |
| November | 52486312.45 | 0.56 | 142.76 | 09-NOV-15:10 | 1.18 |
| December | 17487060.89 | 0.38 | 54.54 | 27-DEC-07:40 | 1.06 |
| Annual Sum or Average | 0.180694E+10 | 0.80 | |||
| Minimum of Months | 16906551.86 | 0.37 | 54.54 | 1.06 | |
| Maximum of Months | 0.339993E+09 | 1.19 | 251.09 | 1.23 |
Report: FanReportMonthly
For: G SW APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.73 | 20.01 | 01-JAN-00:10 | 0.73 |
| February | 48400714.57 | 0.73 | 20.01 | 01-FEB-00:10 | 0.73 |
| March | 53586505.42 | 0.73 | 20.01 | 01-MAR-00:10 | 0.73 |
| April | 51857908.47 | 0.73 | 20.01 | 01-APR-00:10 | 0.73 |
| May | 53586505.42 | 0.73 | 20.01 | 01-MAY-00:10 | 0.73 |
| June | 51857908.47 | 0.73 | 20.01 | 01-JUN-00:10 | 0.73 |
| July | 53586505.42 | 0.72 | 20.01 | 01-JUL-00:10 | 0.72 |
| August | 53586505.42 | 0.72 | 20.01 | 01-AUG-00:10 | 0.72 |
| September | 51857908.47 | 0.72 | 20.01 | 01-SEP-00:10 | 0.72 |
| October | 53586505.42 | 0.72 | 20.01 | 01-OCT-00:10 | 0.73 |
| November | 51857908.47 | 0.73 | 20.01 | 01-NOV-00:10 | 0.73 |
| December | 53586505.42 | 0.73 | 20.01 | 01-DEC-00:10 | 0.73 |
| Annual Sum or Average | 0.630938E+09 | 0.73 | |||
| Minimum of Months | 48400714.57 | 0.72 | 20.01 | 0.72 | |
| Maximum of Months | 53586505.42 | 0.73 | 20.01 | 0.73 |
Report: FanReportMonthly
For: G SW APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.73 | 20.01 | 01-JAN-00:10 | 0.73 |
| February | 48400714.57 | 0.73 | 20.01 | 01-FEB-00:10 | 0.73 |
| March | 53586505.42 | 0.73 | 20.01 | 01-MAR-00:10 | 0.73 |
| April | 51857908.47 | 0.73 | 20.01 | 01-APR-00:10 | 0.73 |
| May | 53586505.42 | 0.73 | 20.01 | 01-MAY-00:10 | 0.73 |
| June | 51857908.47 | 0.72 | 20.01 | 01-JUN-00:10 | 0.73 |
| July | 53586505.42 | 0.72 | 20.01 | 01-JUL-00:10 | 0.72 |
| August | 53586505.42 | 0.72 | 20.01 | 01-AUG-00:10 | 0.72 |
| September | 51857908.47 | 0.72 | 20.01 | 01-SEP-00:10 | 0.72 |
| October | 53586505.42 | 0.72 | 20.01 | 01-OCT-00:10 | 0.73 |
| November | 51857908.47 | 0.73 | 20.01 | 01-NOV-00:10 | 0.73 |
| December | 53586505.42 | 0.73 | 20.01 | 01-DEC-00:10 | 0.73 |
| Annual Sum or Average | 0.630938E+09 | 0.73 | |||
| Minimum of Months | 48400714.57 | 0.72 | 20.01 | 0.72 | |
| Maximum of Months | 53586505.42 | 0.73 | 20.01 | 0.73 |
Report: FanReportMonthly
For: SPLIT GNW SUPPLY FAN
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 56320141.01 | 0.89 | 75.78 | 28-JAN-06:00 | 1.06 |
| February | 45797519.91 | 0.77 | 75.96 | 09-FEB-01:00 | 1.06 |
| March | 31856336.80 | 0.60 | 71.14 | 02-MAR-06:00 | 1.06 |
| April | 46478408.84 | 0.51 | 139.05 | 21-APR-15:10 | 1.18 |
| May | 0.170869E+09 | 1.03 | 196.74 | 19-MAY-17:10 | 1.15 |
| June | 0.284029E+09 | 1.19 | 257.54 | 15-JUN-17:00 | 1.13 |
| July | 0.338555E+09 | 1.18 | 236.85 | 26-JUL-17:30 | 1.13 |
| August | 0.304746E+09 | 1.19 | 233.63 | 07-AUG-16:10 | 1.14 |
| September | 0.244017E+09 | 1.18 | 193.87 | 19-SEP-16:40 | 1.16 |
| October | 0.104550E+09 | 0.88 | 179.28 | 05-OCT-16:10 | 1.16 |
| November | 10312317.55 | 0.27 | 62.45 | 03-NOV-16:10 | 1.21 |
| December | 55688190.85 | 0.83 | 68.41 | 31-DEC-07:00 | 1.06 |
| Annual Sum or Average | 0.169322E+10 | 0.88 | |||
| Minimum of Months | 10312317.55 | 0.27 | 62.45 | 1.06 | |
| Maximum of Months | 0.338555E+09 | 1.19 | 257.54 | 1.21 |
Report: FanReportMonthly
For: G NW APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.73 | 20.01 | 01-JAN-00:10 | 0.73 |
| February | 48400714.57 | 0.73 | 20.01 | 01-FEB-00:10 | 0.73 |
| March | 53586505.42 | 0.73 | 20.01 | 01-MAR-00:10 | 0.73 |
| April | 51857908.47 | 0.73 | 20.01 | 01-APR-00:10 | 0.73 |
| May | 53586505.42 | 0.73 | 20.01 | 01-MAY-00:10 | 0.73 |
| June | 51857908.47 | 0.73 | 20.01 | 01-JUN-00:10 | 0.73 |
| July | 53586505.42 | 0.72 | 20.01 | 01-JUL-00:10 | 0.72 |
| August | 53586505.42 | 0.72 | 20.01 | 01-AUG-00:10 | 0.72 |
| September | 51857908.47 | 0.72 | 20.01 | 01-SEP-00:10 | 0.72 |
| October | 53586505.42 | 0.72 | 20.01 | 01-OCT-00:10 | 0.73 |
| November | 51857908.47 | 0.73 | 20.01 | 01-NOV-00:10 | 0.73 |
| December | 53586505.42 | 0.73 | 20.01 | 01-DEC-00:10 | 0.73 |
| Annual Sum or Average | 0.630938E+09 | 0.73 | |||
| Minimum of Months | 48400714.57 | 0.72 | 20.01 | 0.72 | |
| Maximum of Months | 53586505.42 | 0.73 | 20.01 | 0.73 |
Report: FanReportMonthly
For: G NW APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.73 | 20.01 | 01-JAN-00:10 | 0.73 |
| February | 48400714.57 | 0.73 | 20.01 | 01-FEB-00:10 | 0.73 |
| March | 53586505.42 | 0.73 | 20.01 | 01-MAR-00:10 | 0.73 |
| April | 51857908.47 | 0.73 | 20.01 | 01-APR-00:10 | 0.73 |
| May | 53586505.42 | 0.73 | 20.01 | 01-MAY-00:10 | 0.73 |
| June | 51857908.47 | 0.72 | 20.01 | 01-JUN-00:10 | 0.73 |
| July | 53586505.42 | 0.72 | 20.01 | 01-JUL-00:10 | 0.72 |
| August | 53586505.42 | 0.72 | 20.01 | 01-AUG-00:10 | 0.72 |
| September | 51857908.47 | 0.72 | 20.01 | 01-SEP-00:10 | 0.72 |
| October | 53586505.42 | 0.72 | 20.01 | 01-OCT-00:10 | 0.73 |
| November | 51857908.47 | 0.73 | 20.01 | 01-NOV-00:10 | 0.73 |
| December | 53586505.42 | 0.73 | 20.01 | 01-DEC-00:10 | 0.73 |
| Annual Sum or Average | 0.630938E+09 | 0.73 | |||
| Minimum of Months | 48400714.57 | 0.72 | 20.01 | 0.72 | |
| Maximum of Months | 53586505.42 | 0.73 | 20.01 | 0.73 |
Report: FanReportMonthly
For: SPLIT OFFICE SUPPLY FAN
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.129461E+10 | 1.06 | 483.35 | 01-JAN-00:10 | 1.06 |
| February | 0.116932E+10 | 1.06 | 483.35 | 01-FEB-00:10 | 1.06 |
| March | 0.129461E+10 | 1.06 | 483.35 | 01-MAR-00:10 | 1.06 |
| April | 0.125285E+10 | 1.06 | 483.35 | 01-APR-00:10 | 1.06 |
| May | 0.129461E+10 | 1.06 | 483.35 | 01-MAY-00:10 | 1.06 |
| June | 0.125285E+10 | 1.05 | 483.35 | 01-JUN-00:10 | 1.06 |
| July | 0.129461E+10 | 1.05 | 483.35 | 01-JUL-00:10 | 1.05 |
| August | 0.129461E+10 | 1.05 | 483.35 | 01-AUG-00:10 | 1.05 |
| September | 0.125285E+10 | 1.05 | 483.35 | 01-SEP-00:10 | 1.05 |
| October | 0.129461E+10 | 1.05 | 483.35 | 01-OCT-00:10 | 1.06 |
| November | 0.125285E+10 | 1.06 | 483.35 | 01-NOV-00:10 | 1.06 |
| December | 0.129461E+10 | 1.06 | 483.35 | 01-DEC-00:10 | 1.06 |
| Annual Sum or Average | 0.152430E+11 | 1.06 | |||
| Minimum of Months | 0.116932E+10 | 1.05 | 483.35 | 1.05 | |
| Maximum of Months | 0.129461E+10 | 1.06 | 483.35 | 1.06 |
Report: FanReportMonthly
For: SPLIT GNE SUPPLY FAN
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 56242181.95 | 0.94 | 76.84 | 28-JAN-06:00 | 1.06 |
| February | 43196398.33 | 0.76 | 75.37 | 09-FEB-01:00 | 1.06 |
| March | 30067946.58 | 0.56 | 71.40 | 02-MAR-06:00 | 1.06 |
| April | 46591723.98 | 0.53 | 129.57 | 21-APR-15:10 | 1.18 |
| May | 0.172550E+09 | 1.06 | 166.76 | 19-MAY-17:10 | 1.16 |
| June | 0.287179E+09 | 1.19 | 225.50 | 15-JUN-17:00 | 1.14 |
| July | 0.340740E+09 | 1.17 | 222.30 | 03-JUL-17:00 | 1.14 |
| August | 0.306956E+09 | 1.18 | 208.33 | 07-AUG-16:10 | 1.14 |
| September | 0.244728E+09 | 1.18 | 164.81 | 16-SEP-16:03 | 1.16 |
| October | 99476890.10 | 0.88 | 152.47 | 03-OCT-14:10 | 1.17 |
| November | 9736803.04 | 0.26 | 54.31 | 28-NOV-05:00 | 1.06 |
| December | 54994775.78 | 0.85 | 69.54 | 31-DEC-07:00 | 1.06 |
| Annual Sum or Average | 0.169246E+10 | 0.88 | |||
| Minimum of Months | 9736803.04 | 0.26 | 54.31 | 1.06 | |
| Maximum of Months | 0.340740E+09 | 1.19 | 225.50 | 1.18 |
Report: FanReportMonthly
For: G NE APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.73 | 20.01 | 01-JAN-00:10 | 0.73 |
| February | 48400714.57 | 0.73 | 20.01 | 01-FEB-00:10 | 0.73 |
| March | 53586505.42 | 0.73 | 20.01 | 01-MAR-00:10 | 0.73 |
| April | 51857908.47 | 0.73 | 20.01 | 01-APR-00:10 | 0.73 |
| May | 53586505.42 | 0.73 | 20.01 | 01-MAY-00:10 | 0.73 |
| June | 51857908.47 | 0.73 | 20.01 | 01-JUN-00:10 | 0.73 |
| July | 53586505.42 | 0.72 | 20.01 | 01-JUL-00:10 | 0.72 |
| August | 53586505.42 | 0.72 | 20.01 | 01-AUG-00:10 | 0.72 |
| September | 51857908.47 | 0.72 | 20.01 | 01-SEP-00:10 | 0.72 |
| October | 53586505.42 | 0.72 | 20.01 | 01-OCT-00:10 | 0.73 |
| November | 51857908.47 | 0.73 | 20.01 | 01-NOV-00:10 | 0.73 |
| December | 53586505.42 | 0.73 | 20.01 | 01-DEC-00:10 | 0.73 |
| Annual Sum or Average | 0.630938E+09 | 0.73 | |||
| Minimum of Months | 48400714.57 | 0.72 | 20.01 | 0.72 | |
| Maximum of Months | 53586505.42 | 0.73 | 20.01 | 0.73 |
Report: FanReportMonthly
For: G NE APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.73 | 20.01 | 01-JAN-00:10 | 0.73 |
| February | 48400714.57 | 0.73 | 20.01 | 01-FEB-00:10 | 0.73 |
| March | 53586505.42 | 0.73 | 20.01 | 01-MAR-00:10 | 0.73 |
| April | 51857908.47 | 0.73 | 20.01 | 01-APR-00:10 | 0.73 |
| May | 53586505.42 | 0.73 | 20.01 | 01-MAY-00:10 | 0.73 |
| June | 51857908.47 | 0.72 | 20.01 | 01-JUN-00:10 | 0.73 |
| July | 53586505.42 | 0.72 | 20.01 | 01-JUL-00:10 | 0.72 |
| August | 53586505.42 | 0.72 | 20.01 | 01-AUG-00:10 | 0.72 |
| September | 51857908.47 | 0.72 | 20.01 | 01-SEP-00:10 | 0.72 |
| October | 53586505.42 | 0.72 | 20.01 | 01-OCT-00:10 | 0.73 |
| November | 51857908.47 | 0.73 | 20.01 | 01-NOV-00:10 | 0.73 |
| December | 53586505.42 | 0.73 | 20.01 | 01-DEC-00:10 | 0.73 |
| Annual Sum or Average | 0.630938E+09 | 0.73 | |||
| Minimum of Months | 48400714.57 | 0.72 | 20.01 | 0.72 | |
| Maximum of Months | 53586505.42 | 0.73 | 20.01 | 0.73 |
Report: FanReportMonthly
For: SPLIT GN1 SUPPLY FAN
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 31652676.46 | 0.80 | 50.95 | 28-JAN-06:00 | 1.06 |
| February | 24317628.46 | 0.63 | 49.72 | 03-FEB-05:00 | 1.06 |
| March | 14396710.25 | 0.42 | 45.98 | 02-MAR-06:00 | 1.06 |
| April | 40008537.24 | 0.54 | 104.41 | 21-APR-15:10 | 1.19 |
| May | 0.149905E+09 | 1.09 | 139.66 | 19-MAY-17:20 | 1.17 |
| June | 0.242187E+09 | 1.19 | 186.24 | 15-JUN-17:02 | 1.15 |
| July | 0.287571E+09 | 1.18 | 181.61 | 03-JUL-17:00 | 1.14 |
| August | 0.256327E+09 | 1.19 | 170.92 | 07-AUG-16:06 | 1.15 |
| September | 0.202947E+09 | 1.19 | 135.79 | 22-SEP-16:03 | 1.17 |
| October | 91653744.60 | 1.00 | 126.85 | 04-OCT-16:40 | 1.17 |
| November | 4469409.66 | 0.17 | 42.62 | 03-NOV-16:05 | 1.22 |
| December | 32381564.48 | 0.74 | 45.87 | 31-DEC-07:00 | 1.06 |
| Annual Sum or Average | 0.137782E+10 | 0.85 | |||
| Minimum of Months | 4469409.66 | 0.17 | 42.62 | 1.06 | |
| Maximum of Months | 0.287571E+09 | 1.19 | 186.24 | 1.22 |
Report: FanReportMonthly
For: G N1 APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.73 | 20.01 | 01-JAN-00:10 | 0.73 |
| February | 48400714.57 | 0.73 | 20.01 | 01-FEB-00:10 | 0.73 |
| March | 53586505.42 | 0.73 | 20.01 | 01-MAR-00:10 | 0.73 |
| April | 51857908.47 | 0.73 | 20.01 | 01-APR-00:10 | 0.73 |
| May | 53586505.42 | 0.73 | 20.01 | 01-MAY-00:10 | 0.73 |
| June | 51857908.47 | 0.73 | 20.01 | 01-JUN-00:10 | 0.73 |
| July | 53586505.42 | 0.72 | 20.01 | 01-JUL-00:10 | 0.72 |
| August | 53586505.42 | 0.72 | 20.01 | 01-AUG-00:10 | 0.72 |
| September | 51857908.47 | 0.72 | 20.01 | 01-SEP-00:10 | 0.72 |
| October | 53586505.42 | 0.72 | 20.01 | 01-OCT-00:10 | 0.73 |
| November | 51857908.47 | 0.73 | 20.01 | 01-NOV-00:10 | 0.73 |
| December | 53586505.42 | 0.73 | 20.01 | 01-DEC-00:10 | 0.73 |
| Annual Sum or Average | 0.630938E+09 | 0.73 | |||
| Minimum of Months | 48400714.57 | 0.72 | 20.01 | 0.72 | |
| Maximum of Months | 53586505.42 | 0.73 | 20.01 | 0.73 |
Report: FanReportMonthly
For: G N1 APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.73 | 20.01 | 01-JAN-00:10 | 0.73 |
| February | 48400714.57 | 0.73 | 20.01 | 01-FEB-00:10 | 0.73 |
| March | 53586505.42 | 0.73 | 20.01 | 01-MAR-00:10 | 0.73 |
| April | 51857908.47 | 0.73 | 20.01 | 01-APR-00:10 | 0.73 |
| May | 53586505.42 | 0.73 | 20.01 | 01-MAY-00:10 | 0.73 |
| June | 51857908.47 | 0.72 | 20.01 | 01-JUN-00:10 | 0.73 |
| July | 53586505.42 | 0.72 | 20.01 | 01-JUL-00:10 | 0.72 |
| August | 53586505.42 | 0.72 | 20.01 | 01-AUG-00:10 | 0.72 |
| September | 51857908.47 | 0.72 | 20.01 | 01-SEP-00:10 | 0.72 |
| October | 53586505.42 | 0.72 | 20.01 | 01-OCT-00:10 | 0.73 |
| November | 51857908.47 | 0.73 | 20.01 | 01-NOV-00:10 | 0.73 |
| December | 53586505.42 | 0.73 | 20.01 | 01-DEC-00:10 | 0.73 |
| Annual Sum or Average | 0.630938E+09 | 0.73 | |||
| Minimum of Months | 48400714.57 | 0.72 | 20.01 | 0.72 | |
| Maximum of Months | 53586505.42 | 0.73 | 20.01 | 0.73 |
Report: FanReportMonthly
For: SPLIT GN2 SUPPLY FAN
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 31754151.47 | 0.80 | 50.99 | 28-JAN-06:00 | 1.06 |
| February | 24254619.16 | 0.63 | 49.79 | 03-FEB-05:00 | 1.06 |
| March | 14410209.26 | 0.42 | 45.94 | 02-MAR-06:00 | 1.06 |
| April | 40363878.62 | 0.54 | 104.59 | 21-APR-15:10 | 1.19 |
| May | 0.150190E+09 | 1.09 | 139.21 | 19-MAY-17:10 | 1.17 |
| June | 0.242394E+09 | 1.19 | 185.82 | 15-JUN-17:00 | 1.15 |
| July | 0.287692E+09 | 1.18 | 181.67 | 03-JUL-17:00 | 1.14 |
| August | 0.256464E+09 | 1.19 | 170.59 | 07-AUG-16:10 | 1.15 |
| September | 0.203014E+09 | 1.19 | 135.49 | 16-SEP-16:03 | 1.17 |
| October | 91436257.87 | 0.99 | 126.25 | 04-OCT-16:30 | 1.17 |
| November | 4448049.29 | 0.17 | 42.19 | 03-NOV-16:05 | 1.22 |
| December | 32404750.27 | 0.74 | 45.99 | 31-DEC-07:00 | 1.06 |
| Annual Sum or Average | 0.137883E+10 | 0.85 | |||
| Minimum of Months | 4448049.29 | 0.17 | 42.19 | 1.06 | |
| Maximum of Months | 0.287692E+09 | 1.19 | 185.82 | 1.22 |
Report: FanReportMonthly
For: G N2 APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.73 | 20.01 | 01-JAN-00:10 | 0.73 |
| February | 48400714.57 | 0.73 | 20.01 | 01-FEB-00:10 | 0.73 |
| March | 53586505.42 | 0.73 | 20.01 | 01-MAR-00:10 | 0.73 |
| April | 51857908.47 | 0.73 | 20.01 | 01-APR-00:10 | 0.73 |
| May | 53586505.42 | 0.73 | 20.01 | 01-MAY-00:10 | 0.73 |
| June | 51857908.47 | 0.73 | 20.01 | 01-JUN-00:10 | 0.73 |
| July | 53586505.42 | 0.72 | 20.01 | 01-JUL-00:10 | 0.72 |
| August | 53586505.42 | 0.72 | 20.01 | 01-AUG-00:10 | 0.72 |
| September | 51857908.47 | 0.72 | 20.01 | 01-SEP-00:10 | 0.72 |
| October | 53586505.42 | 0.72 | 20.01 | 01-OCT-00:10 | 0.73 |
| November | 51857908.47 | 0.73 | 20.01 | 01-NOV-00:10 | 0.73 |
| December | 53586505.42 | 0.73 | 20.01 | 01-DEC-00:10 | 0.73 |
| Annual Sum or Average | 0.630938E+09 | 0.73 | |||
| Minimum of Months | 48400714.57 | 0.72 | 20.01 | 0.72 | |
| Maximum of Months | 53586505.42 | 0.73 | 20.01 | 0.73 |
Report: FanReportMonthly
For: G N2 APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.73 | 20.01 | 01-JAN-00:10 | 0.73 |
| February | 48400714.57 | 0.73 | 20.01 | 01-FEB-00:10 | 0.73 |
| March | 53586505.42 | 0.73 | 20.01 | 01-MAR-00:10 | 0.73 |
| April | 51857908.47 | 0.73 | 20.01 | 01-APR-00:10 | 0.73 |
| May | 53586505.42 | 0.73 | 20.01 | 01-MAY-00:10 | 0.73 |
| June | 51857908.47 | 0.72 | 20.01 | 01-JUN-00:10 | 0.73 |
| July | 53586505.42 | 0.72 | 20.01 | 01-JUL-00:10 | 0.72 |
| August | 53586505.42 | 0.72 | 20.01 | 01-AUG-00:10 | 0.72 |
| September | 51857908.47 | 0.72 | 20.01 | 01-SEP-00:10 | 0.72 |
| October | 53586505.42 | 0.72 | 20.01 | 01-OCT-00:10 | 0.73 |
| November | 51857908.47 | 0.73 | 20.01 | 01-NOV-00:10 | 0.73 |
| December | 53586505.42 | 0.73 | 20.01 | 01-DEC-00:10 | 0.73 |
| Annual Sum or Average | 0.630938E+09 | 0.73 | |||
| Minimum of Months | 48400714.57 | 0.72 | 20.01 | 0.72 | |
| Maximum of Months | 53586505.42 | 0.73 | 20.01 | 0.73 |
Report: FanReportMonthly
For: SPLIT GS1 SUPPLY FAN
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 6135533.13 | 0.18 | 42.90 | 01-JAN-13:50 | 1.22 |
| February | 7624157.83 | 0.21 | 51.67 | 22-FEB-14:00 | 1.22 |
| March | 8159907.32 | 0.21 | 50.43 | 21-MAR-16:07 | 1.23 |
| April | 69660956.33 | 0.72 | 127.41 | 21-APR-15:10 | 1.18 |
| May | 0.158807E+09 | 1.11 | 142.60 | 19-MAY-17:03 | 1.17 |
| June | 0.239283E+09 | 1.19 | 180.06 | 15-JUN-16:40 | 1.16 |
| July | 0.290250E+09 | 1.18 | 182.84 | 03-JUL-17:00 | 1.15 |
| August | 0.279125E+09 | 1.18 | 180.72 | 07-AUG-16:08 | 1.15 |
| September | 0.261378E+09 | 1.19 | 182.93 | 19-SEP-14:10 | 1.15 |
| October | 0.177413E+09 | 1.19 | 176.33 | 01-OCT-15:10 | 1.15 |
| November | 63937381.99 | 0.68 | 123.05 | 09-NOV-14:00 | 1.18 |
| December | 4391985.22 | 0.15 | 34.46 | 16-DEC-15:10 | 1.23 |
| Annual Sum or Average | 0.156617E+10 | 0.77 | |||
| Minimum of Months | 4391985.22 | 0.15 | 34.46 | 1.15 | |
| Maximum of Months | 0.290250E+09 | 1.19 | 182.93 | 1.23 |
Report: FanReportMonthly
For: G S1 APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.73 | 20.01 | 01-JAN-00:10 | 0.73 |
| February | 48400714.57 | 0.73 | 20.01 | 01-FEB-00:10 | 0.73 |
| March | 53586505.42 | 0.73 | 20.01 | 01-MAR-00:10 | 0.73 |
| April | 51857908.47 | 0.73 | 20.01 | 01-APR-00:10 | 0.73 |
| May | 53586505.42 | 0.73 | 20.01 | 01-MAY-00:10 | 0.73 |
| June | 51857908.47 | 0.73 | 20.01 | 01-JUN-00:10 | 0.73 |
| July | 53586505.42 | 0.72 | 20.01 | 01-JUL-00:10 | 0.72 |
| August | 53586505.42 | 0.72 | 20.01 | 01-AUG-00:10 | 0.72 |
| September | 51857908.47 | 0.72 | 20.01 | 01-SEP-00:10 | 0.72 |
| October | 53586505.42 | 0.72 | 20.01 | 01-OCT-00:10 | 0.73 |
| November | 51857908.47 | 0.73 | 20.01 | 01-NOV-00:10 | 0.73 |
| December | 53586505.42 | 0.73 | 20.01 | 01-DEC-00:10 | 0.73 |
| Annual Sum or Average | 0.630938E+09 | 0.73 | |||
| Minimum of Months | 48400714.57 | 0.72 | 20.01 | 0.72 | |
| Maximum of Months | 53586505.42 | 0.73 | 20.01 | 0.73 |
Report: FanReportMonthly
For: G S1 APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.73 | 20.01 | 01-JAN-00:10 | 0.73 |
| February | 48400714.57 | 0.73 | 20.01 | 01-FEB-00:10 | 0.73 |
| March | 53586505.42 | 0.73 | 20.01 | 01-MAR-00:10 | 0.73 |
| April | 51857908.47 | 0.73 | 20.01 | 01-APR-00:10 | 0.73 |
| May | 53586505.42 | 0.73 | 20.01 | 01-MAY-00:10 | 0.73 |
| June | 51857908.47 | 0.72 | 20.01 | 01-JUN-00:10 | 0.73 |
| July | 53586505.42 | 0.72 | 20.01 | 01-JUL-00:10 | 0.72 |
| August | 53586505.42 | 0.72 | 20.01 | 01-AUG-00:10 | 0.72 |
| September | 51857908.47 | 0.72 | 20.01 | 01-SEP-00:10 | 0.72 |
| October | 53586505.42 | 0.72 | 20.01 | 01-OCT-00:10 | 0.73 |
| November | 51857908.47 | 0.73 | 20.01 | 01-NOV-00:10 | 0.73 |
| December | 53586505.42 | 0.73 | 20.01 | 01-DEC-00:10 | 0.73 |
| Annual Sum or Average | 0.630938E+09 | 0.73 | |||
| Minimum of Months | 48400714.57 | 0.72 | 20.01 | 0.72 | |
| Maximum of Months | 53586505.42 | 0.73 | 20.01 | 0.73 |
Report: FanReportMonthly
For: SPLIT GS2 SUPPLY FAN
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 6280320.94 | 0.19 | 41.82 | 01-JAN-13:50 | 1.22 |
| February | 7794028.57 | 0.21 | 54.57 | 22-FEB-14:00 | 1.22 |
| March | 8858879.19 | 0.22 | 53.68 | 21-MAR-16:10 | 1.22 |
| April | 77818112.67 | 0.77 | 132.34 | 21-APR-15:10 | 1.18 |
| May | 0.175986E+09 | 1.13 | 149.10 | 21-MAY-16:02 | 1.17 |
| June | 0.262388E+09 | 1.19 | 187.20 | 15-JUN-17:00 | 1.15 |
| July | 0.316677E+09 | 1.17 | 192.04 | 03-JUL-17:00 | 1.14 |
| August | 0.304153E+09 | 1.18 | 189.80 | 06-AUG-17:10 | 1.14 |
| September | 0.284914E+09 | 1.18 | 190.50 | 19-SEP-14:10 | 1.15 |
| October | 0.193416E+09 | 1.19 | 187.41 | 01-OCT-15:10 | 1.15 |
| November | 69065944.00 | 0.71 | 126.62 | 09-NOV-14:00 | 1.18 |
| December | 4923881.71 | 0.16 | 38.98 | 16-DEC-15:10 | 1.23 |
| Annual Sum or Average | 0.171228E+10 | 0.78 | |||
| Minimum of Months | 4923881.71 | 0.16 | 38.98 | 1.14 | |
| Maximum of Months | 0.316677E+09 | 1.19 | 192.04 | 1.23 |
Report: FanReportMonthly
For: G S2 APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.73 | 20.01 | 01-JAN-00:10 | 0.73 |
| February | 48400714.57 | 0.73 | 20.01 | 01-FEB-00:10 | 0.73 |
| March | 53586505.42 | 0.73 | 20.01 | 01-MAR-00:10 | 0.73 |
| April | 51857908.47 | 0.73 | 20.01 | 01-APR-00:10 | 0.73 |
| May | 53586505.42 | 0.73 | 20.01 | 01-MAY-00:10 | 0.73 |
| June | 51857908.47 | 0.73 | 20.01 | 01-JUN-00:10 | 0.73 |
| July | 53586505.42 | 0.72 | 20.01 | 01-JUL-00:10 | 0.72 |
| August | 53586505.42 | 0.72 | 20.01 | 01-AUG-00:10 | 0.72 |
| September | 51857908.47 | 0.72 | 20.01 | 01-SEP-00:10 | 0.72 |
| October | 53586505.42 | 0.72 | 20.01 | 01-OCT-00:10 | 0.73 |
| November | 51857908.47 | 0.73 | 20.01 | 01-NOV-00:10 | 0.73 |
| December | 53586505.42 | 0.73 | 20.01 | 01-DEC-00:10 | 0.73 |
| Annual Sum or Average | 0.630938E+09 | 0.73 | |||
| Minimum of Months | 48400714.57 | 0.72 | 20.01 | 0.72 | |
| Maximum of Months | 53586505.42 | 0.73 | 20.01 | 0.73 |
Report: FanReportMonthly
For: G S2 APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.73 | 20.01 | 01-JAN-00:10 | 0.73 |
| February | 48400714.57 | 0.73 | 20.01 | 01-FEB-00:10 | 0.73 |
| March | 53586505.42 | 0.73 | 20.01 | 01-MAR-00:10 | 0.73 |
| April | 51857908.47 | 0.73 | 20.01 | 01-APR-00:10 | 0.73 |
| May | 53586505.42 | 0.73 | 20.01 | 01-MAY-00:10 | 0.73 |
| June | 51857908.47 | 0.72 | 20.01 | 01-JUN-00:10 | 0.73 |
| July | 53586505.42 | 0.72 | 20.01 | 01-JUL-00:10 | 0.72 |
| August | 53586505.42 | 0.72 | 20.01 | 01-AUG-00:10 | 0.72 |
| September | 51857908.47 | 0.72 | 20.01 | 01-SEP-00:10 | 0.72 |
| October | 53586505.42 | 0.72 | 20.01 | 01-OCT-00:10 | 0.73 |
| November | 51857908.47 | 0.73 | 20.01 | 01-NOV-00:10 | 0.73 |
| December | 53586505.42 | 0.73 | 20.01 | 01-DEC-00:10 | 0.73 |
| Annual Sum or Average | 0.630938E+09 | 0.73 | |||
| Minimum of Months | 48400714.57 | 0.72 | 20.01 | 0.72 | |
| Maximum of Months | 53586505.42 | 0.73 | 20.01 | 0.73 |
Report: FanReportMonthly
For: SPLIT MSW SUPPLY FAN
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 36102422.88 | 0.36 | 184.53 | 12-JAN-15:00 | 1.21 |
| February | 54589458.01 | 0.34 | 300.67 | 20-FEB-16:10 | 1.20 |
| March | 80668578.36 | 0.39 | 305.71 | 14-MAR-16:15 | 1.19 |
| April | 0.312812E+09 | 0.89 | 470.52 | 21-APR-15:10 | 1.16 |
| May | 0.523299E+09 | 1.13 | 521.81 | 19-MAY-17:08 | 1.15 |
| June | 0.708090E+09 | 1.19 | 618.19 | 15-JUN-17:00 | 1.14 |
| July | 0.768269E+09 | 1.18 | 547.40 | 26-JUL-17:30 | 1.14 |
| August | 0.684492E+09 | 1.19 | 538.51 | 07-AUG-16:10 | 1.14 |
| September | 0.589836E+09 | 1.18 | 520.01 | 19-SEP-16:10 | 1.15 |
| October | 0.362893E+09 | 0.95 | 497.77 | 01-OCT-15:10 | 1.15 |
| November | 0.115972E+09 | 0.51 | 343.80 | 09-NOV-15:10 | 1.18 |
| December | 37235548.17 | 0.36 | 125.87 | 27-DEC-06:00 | 1.06 |
| Annual Sum or Average | 0.427426E+10 | 0.81 | |||
| Minimum of Months | 36102422.88 | 0.34 | 125.87 | 1.06 | |
| Maximum of Months | 0.768269E+09 | 1.19 | 618.19 | 1.21 |
Report: FanReportMonthly
For: M SW APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.107173E+09 | 0.73 | 40.01 | 01-JAN-00:10 | 0.73 |
| February | 96801429.15 | 0.73 | 40.01 | 01-FEB-00:10 | 0.73 |
| March | 0.107173E+09 | 0.73 | 40.01 | 01-MAR-00:10 | 0.73 |
| April | 0.103716E+09 | 0.73 | 40.01 | 01-APR-00:10 | 0.73 |
| May | 0.107173E+09 | 0.73 | 40.01 | 01-MAY-00:10 | 0.73 |
| June | 0.103716E+09 | 0.73 | 40.01 | 01-JUN-00:10 | 0.73 |
| July | 0.107173E+09 | 0.72 | 40.01 | 01-JUL-00:10 | 0.72 |
| August | 0.107173E+09 | 0.72 | 40.01 | 01-AUG-00:10 | 0.72 |
| September | 0.103716E+09 | 0.72 | 40.01 | 01-SEP-00:10 | 0.72 |
| October | 0.107173E+09 | 0.72 | 40.01 | 01-OCT-00:10 | 0.73 |
| November | 0.103716E+09 | 0.73 | 40.01 | 01-NOV-00:10 | 0.73 |
| December | 0.107173E+09 | 0.73 | 40.01 | 01-DEC-00:10 | 0.73 |
| Annual Sum or Average | 0.126188E+10 | 0.73 | |||
| Minimum of Months | 96801429.15 | 0.72 | 40.01 | 0.72 | |
| Maximum of Months | 0.107173E+09 | 0.73 | 40.01 | 0.73 |
Report: FanReportMonthly
For: M SW APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.107173E+09 | 0.73 | 40.01 | 01-JAN-00:10 | 0.73 |
| February | 96801429.15 | 0.73 | 40.01 | 01-FEB-00:10 | 0.73 |
| March | 0.107173E+09 | 0.73 | 40.01 | 01-MAR-00:10 | 0.73 |
| April | 0.103716E+09 | 0.73 | 40.01 | 01-APR-00:10 | 0.73 |
| May | 0.107173E+09 | 0.73 | 40.01 | 01-MAY-00:10 | 0.73 |
| June | 0.103716E+09 | 0.73 | 40.01 | 01-JUN-00:10 | 0.73 |
| July | 0.107173E+09 | 0.72 | 40.01 | 01-JUL-00:10 | 0.72 |
| August | 0.107173E+09 | 0.72 | 40.01 | 01-AUG-00:10 | 0.72 |
| September | 0.103716E+09 | 0.72 | 40.01 | 01-SEP-00:10 | 0.72 |
| October | 0.107173E+09 | 0.72 | 40.01 | 01-OCT-00:10 | 0.73 |
| November | 0.103716E+09 | 0.73 | 40.01 | 01-NOV-00:10 | 0.73 |
| December | 0.107173E+09 | 0.73 | 40.01 | 01-DEC-00:10 | 0.73 |
| Annual Sum or Average | 0.126188E+10 | 0.73 | |||
| Minimum of Months | 96801429.15 | 0.72 | 40.01 | 0.72 | |
| Maximum of Months | 0.107173E+09 | 0.73 | 40.01 | 0.73 |
Report: FanReportMonthly
For: SPLIT MNW SUPPLY FAN
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 89556952.84 | 0.73 | 158.38 | 28-JAN-06:00 | 1.06 |
| February | 49785453.87 | 0.45 | 147.54 | 09-FEB-01:00 | 1.06 |
| March | 26418119.97 | 0.24 | 148.46 | 16-MAR-16:05 | 1.22 |
| April | 0.237981E+09 | 0.81 | 423.07 | 21-APR-15:10 | 1.17 |
| May | 0.506385E+09 | 1.13 | 516.35 | 19-MAY-17:10 | 1.15 |
| June | 0.714645E+09 | 1.19 | 633.86 | 15-JUN-17:00 | 1.13 |
| July | 0.763003E+09 | 1.18 | 550.15 | 26-JUL-17:40 | 1.13 |
| August | 0.637415E+09 | 1.19 | 517.95 | 07-AUG-16:10 | 1.14 |
| September | 0.469052E+09 | 1.16 | 418.61 | 18-SEP-16:40 | 1.16 |
| October | 0.195062E+09 | 0.74 | 396.12 | 05-OCT-16:20 | 1.16 |
| November | 29733495.23 | 0.31 | 134.71 | 28-NOV-05:00 | 1.06 |
| December | 0.112652E+09 | 0.78 | 150.80 | 31-DEC-07:00 | 1.06 |
| Annual Sum or Average | 0.383169E+10 | 0.83 | |||
| Minimum of Months | 26418119.97 | 0.24 | 134.71 | 1.06 | |
| Maximum of Months | 0.763003E+09 | 1.19 | 633.86 | 1.22 |
Report: FanReportMonthly
For: M NW APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.107173E+09 | 0.73 | 40.01 | 01-JAN-00:10 | 0.73 |
| February | 96801429.15 | 0.73 | 40.01 | 01-FEB-00:10 | 0.73 |
| March | 0.107173E+09 | 0.73 | 40.01 | 01-MAR-00:10 | 0.73 |
| April | 0.103716E+09 | 0.73 | 40.01 | 01-APR-00:10 | 0.73 |
| May | 0.107173E+09 | 0.73 | 40.01 | 01-MAY-00:10 | 0.73 |
| June | 0.103716E+09 | 0.73 | 40.01 | 01-JUN-00:10 | 0.73 |
| July | 0.107173E+09 | 0.72 | 40.01 | 01-JUL-00:10 | 0.72 |
| August | 0.107173E+09 | 0.72 | 40.01 | 01-AUG-00:10 | 0.72 |
| September | 0.103716E+09 | 0.72 | 40.01 | 01-SEP-00:10 | 0.72 |
| October | 0.107173E+09 | 0.72 | 40.01 | 01-OCT-00:10 | 0.73 |
| November | 0.103716E+09 | 0.73 | 40.01 | 01-NOV-00:10 | 0.73 |
| December | 0.107173E+09 | 0.73 | 40.01 | 01-DEC-00:10 | 0.73 |
| Annual Sum or Average | 0.126188E+10 | 0.73 | |||
| Minimum of Months | 96801429.15 | 0.72 | 40.01 | 0.72 | |
| Maximum of Months | 0.107173E+09 | 0.73 | 40.01 | 0.73 |
Report: FanReportMonthly
For: M NW APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.107173E+09 | 0.73 | 40.01 | 01-JAN-00:10 | 0.73 |
| February | 96801429.15 | 0.73 | 40.01 | 01-FEB-00:10 | 0.73 |
| March | 0.107173E+09 | 0.73 | 40.01 | 01-MAR-00:10 | 0.73 |
| April | 0.103716E+09 | 0.73 | 40.01 | 01-APR-00:10 | 0.73 |
| May | 0.107173E+09 | 0.73 | 40.01 | 01-MAY-00:10 | 0.73 |
| June | 0.103716E+09 | 0.73 | 40.01 | 01-JUN-00:10 | 0.73 |
| July | 0.107173E+09 | 0.72 | 40.01 | 01-JUL-00:10 | 0.72 |
| August | 0.107173E+09 | 0.72 | 40.01 | 01-AUG-00:10 | 0.72 |
| September | 0.103716E+09 | 0.72 | 40.01 | 01-SEP-00:10 | 0.72 |
| October | 0.107173E+09 | 0.72 | 40.01 | 01-OCT-00:10 | 0.73 |
| November | 0.103716E+09 | 0.73 | 40.01 | 01-NOV-00:10 | 0.73 |
| December | 0.107173E+09 | 0.73 | 40.01 | 01-DEC-00:10 | 0.73 |
| Annual Sum or Average | 0.126188E+10 | 0.73 | |||
| Minimum of Months | 96801429.15 | 0.72 | 40.01 | 0.72 | |
| Maximum of Months | 0.107173E+09 | 0.73 | 40.01 | 0.73 |
Report: FanReportMonthly
For: SPLIT MSE SUPPLY FAN
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 32583704.84 | 0.34 | 149.82 | 12-JAN-15:00 | 1.22 |
| February | 54544191.83 | 0.34 | 258.76 | 20-FEB-15:00 | 1.20 |
| March | 80254980.59 | 0.41 | 246.36 | 16-MAR-14:10 | 1.20 |
| April | 0.320095E+09 | 0.93 | 444.61 | 21-APR-14:10 | 1.16 |
| May | 0.528661E+09 | 1.15 | 456.02 | 19-MAY-14:00 | 1.15 |
| June | 0.714150E+09 | 1.19 | 533.68 | 15-JUN-16:04 | 1.14 |
| July | 0.773176E+09 | 1.18 | 499.90 | 03-JUL-17:00 | 1.14 |
| August | 0.689355E+09 | 1.18 | 469.05 | 07-AUG-16:10 | 1.15 |
| September | 0.591310E+09 | 1.17 | 464.81 | 19-SEP-14:00 | 1.15 |
| October | 0.352426E+09 | 0.95 | 446.38 | 01-OCT-15:10 | 1.16 |
| November | 0.111901E+09 | 0.53 | 307.96 | 09-NOV-14:00 | 1.18 |
| December | 36167313.63 | 0.34 | 125.82 | 27-DEC-06:00 | 1.06 |
| Annual Sum or Average | 0.428463E+10 | 0.81 | |||
| Minimum of Months | 32583704.84 | 0.34 | 125.82 | 1.06 | |
| Maximum of Months | 0.773176E+09 | 1.19 | 533.68 | 1.22 |
Report: FanReportMonthly
For: M SE APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.107173E+09 | 0.73 | 40.01 | 01-JAN-00:10 | 0.73 |
| February | 96801429.15 | 0.73 | 40.01 | 01-FEB-00:10 | 0.73 |
| March | 0.107173E+09 | 0.73 | 40.01 | 01-MAR-00:10 | 0.73 |
| April | 0.103716E+09 | 0.73 | 40.01 | 01-APR-00:10 | 0.73 |
| May | 0.107173E+09 | 0.73 | 40.01 | 01-MAY-00:10 | 0.73 |
| June | 0.103716E+09 | 0.73 | 40.01 | 01-JUN-00:10 | 0.73 |
| July | 0.107173E+09 | 0.72 | 40.01 | 01-JUL-00:10 | 0.72 |
| August | 0.107173E+09 | 0.72 | 40.01 | 01-AUG-00:10 | 0.72 |
| September | 0.103716E+09 | 0.72 | 40.01 | 01-SEP-00:10 | 0.72 |
| October | 0.107173E+09 | 0.72 | 40.01 | 01-OCT-00:10 | 0.73 |
| November | 0.103716E+09 | 0.73 | 40.01 | 01-NOV-00:10 | 0.73 |
| December | 0.107173E+09 | 0.73 | 40.01 | 01-DEC-00:10 | 0.73 |
| Annual Sum or Average | 0.126188E+10 | 0.73 | |||
| Minimum of Months | 96801429.15 | 0.72 | 40.01 | 0.72 | |
| Maximum of Months | 0.107173E+09 | 0.73 | 40.01 | 0.73 |
Report: FanReportMonthly
For: M SE APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.107173E+09 | 0.73 | 40.01 | 01-JAN-00:10 | 0.73 |
| February | 96801429.15 | 0.73 | 40.01 | 01-FEB-00:10 | 0.73 |
| March | 0.107173E+09 | 0.73 | 40.01 | 01-MAR-00:10 | 0.73 |
| April | 0.103716E+09 | 0.73 | 40.01 | 01-APR-00:10 | 0.73 |
| May | 0.107173E+09 | 0.73 | 40.01 | 01-MAY-00:10 | 0.73 |
| June | 0.103716E+09 | 0.73 | 40.01 | 01-JUN-00:10 | 0.73 |
| July | 0.107173E+09 | 0.72 | 40.01 | 01-JUL-00:10 | 0.72 |
| August | 0.107173E+09 | 0.72 | 40.01 | 01-AUG-00:10 | 0.72 |
| September | 0.103716E+09 | 0.72 | 40.01 | 01-SEP-00:10 | 0.72 |
| October | 0.107173E+09 | 0.72 | 40.01 | 01-OCT-00:10 | 0.73 |
| November | 0.103716E+09 | 0.73 | 40.01 | 01-NOV-00:10 | 0.73 |
| December | 0.107173E+09 | 0.73 | 40.01 | 01-DEC-00:10 | 0.73 |
| Annual Sum or Average | 0.126188E+10 | 0.73 | |||
| Minimum of Months | 96801429.15 | 0.72 | 40.01 | 0.72 | |
| Maximum of Months | 0.107173E+09 | 0.73 | 40.01 | 0.73 |
Report: FanReportMonthly
For: SPLIT MNE SUPPLY FAN
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 88701328.40 | 0.75 | 162.16 | 28-JAN-06:00 | 1.06 |
| February | 45405328.70 | 0.42 | 145.21 | 09-FEB-01:00 | 1.06 |
| March | 24185552.37 | 0.25 | 127.80 | 01-MAR-23:00 | 1.06 |
| April | 0.243837E+09 | 0.85 | 394.03 | 21-APR-15:10 | 1.17 |
| May | 0.511835E+09 | 1.14 | 429.64 | 19-MAY-17:10 | 1.16 |
| June | 0.720647E+09 | 1.19 | 542.80 | 15-JUN-17:00 | 1.14 |
| July | 0.767846E+09 | 1.18 | 498.43 | 03-JUL-17:00 | 1.14 |
| August | 0.642562E+09 | 1.19 | 448.81 | 07-AUG-16:10 | 1.15 |
| September | 0.471236E+09 | 1.16 | 341.96 | 01-SEP-16:03 | 1.17 |
| October | 0.183400E+09 | 0.75 | 318.09 | 03-OCT-14:10 | 1.17 |
| November | 29154166.77 | 0.31 | 138.43 | 28-NOV-05:00 | 1.06 |
| December | 0.111219E+09 | 0.79 | 154.67 | 31-DEC-07:00 | 1.06 |
| Annual Sum or Average | 0.384003E+10 | 0.83 | |||
| Minimum of Months | 24185552.37 | 0.25 | 127.80 | 1.06 | |
| Maximum of Months | 0.767846E+09 | 1.19 | 542.80 | 1.17 |
Report: FanReportMonthly
For: M NE APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.107173E+09 | 0.73 | 40.01 | 01-JAN-00:10 | 0.73 |
| February | 96801429.15 | 0.73 | 40.01 | 01-FEB-00:10 | 0.73 |
| March | 0.107173E+09 | 0.73 | 40.01 | 01-MAR-00:10 | 0.73 |
| April | 0.103716E+09 | 0.73 | 40.01 | 01-APR-00:10 | 0.73 |
| May | 0.107173E+09 | 0.73 | 40.01 | 01-MAY-00:10 | 0.73 |
| June | 0.103716E+09 | 0.73 | 40.01 | 01-JUN-00:10 | 0.73 |
| July | 0.107173E+09 | 0.72 | 40.01 | 01-JUL-00:10 | 0.72 |
| August | 0.107173E+09 | 0.72 | 40.01 | 01-AUG-00:10 | 0.72 |
| September | 0.103716E+09 | 0.72 | 40.01 | 01-SEP-00:10 | 0.72 |
| October | 0.107173E+09 | 0.72 | 40.01 | 01-OCT-00:10 | 0.73 |
| November | 0.103716E+09 | 0.73 | 40.01 | 01-NOV-00:10 | 0.73 |
| December | 0.107173E+09 | 0.73 | 40.01 | 01-DEC-00:10 | 0.73 |
| Annual Sum or Average | 0.126188E+10 | 0.73 | |||
| Minimum of Months | 96801429.15 | 0.72 | 40.01 | 0.72 | |
| Maximum of Months | 0.107173E+09 | 0.73 | 40.01 | 0.73 |
Report: FanReportMonthly
For: M NE APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.107173E+09 | 0.73 | 40.01 | 01-JAN-00:10 | 0.73 |
| February | 96801429.15 | 0.73 | 40.01 | 01-FEB-00:10 | 0.73 |
| March | 0.107173E+09 | 0.73 | 40.01 | 01-MAR-00:10 | 0.73 |
| April | 0.103716E+09 | 0.73 | 40.01 | 01-APR-00:10 | 0.73 |
| May | 0.107173E+09 | 0.73 | 40.01 | 01-MAY-00:10 | 0.73 |
| June | 0.103716E+09 | 0.73 | 40.01 | 01-JUN-00:10 | 0.73 |
| July | 0.107173E+09 | 0.72 | 40.01 | 01-JUL-00:10 | 0.72 |
| August | 0.107173E+09 | 0.72 | 40.01 | 01-AUG-00:10 | 0.72 |
| September | 0.103716E+09 | 0.72 | 40.01 | 01-SEP-00:10 | 0.72 |
| October | 0.107173E+09 | 0.72 | 40.01 | 01-OCT-00:10 | 0.73 |
| November | 0.103716E+09 | 0.73 | 40.01 | 01-NOV-00:10 | 0.73 |
| December | 0.107173E+09 | 0.73 | 40.01 | 01-DEC-00:10 | 0.73 |
| Annual Sum or Average | 0.126188E+10 | 0.73 | |||
| Minimum of Months | 96801429.15 | 0.72 | 40.01 | 0.72 | |
| Maximum of Months | 0.107173E+09 | 0.73 | 40.01 | 0.73 |
Report: FanReportMonthly
For: SPLIT MN1 SUPPLY FAN
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 36197904.95 | 0.49 | 101.56 | 28-JAN-06:00 | 1.06 |
| February | 19141664.70 | 0.26 | 87.49 | 03-FEB-05:00 | 1.06 |
| March | 15593025.21 | 0.19 | 96.77 | 22-MAR-16:05 | 1.23 |
| April | 0.197573E+09 | 0.88 | 298.25 | 21-APR-15:10 | 1.18 |
| May | 0.411024E+09 | 1.17 | 341.35 | 19-MAY-17:17 | 1.17 |
| June | 0.572151E+09 | 1.19 | 428.71 | 15-JUN-17:00 | 1.15 |
| July | 0.623425E+09 | 1.18 | 392.90 | 03-JUL-17:00 | 1.15 |
| August | 0.524051E+09 | 1.19 | 358.02 | 07-AUG-16:04 | 1.16 |
| September | 0.389662E+09 | 1.19 | 278.14 | 01-SEP-16:03 | 1.17 |
| October | 0.174650E+09 | 0.92 | 259.15 | 05-OCT-16:03 | 1.18 |
| November | 10765691.66 | 0.19 | 84.13 | 28-NOV-05:00 | 1.06 |
| December | 54056744.04 | 0.63 | 94.42 | 31-DEC-07:00 | 1.06 |
| Annual Sum or Average | 0.302829E+10 | 0.79 | |||
| Minimum of Months | 10765691.66 | 0.19 | 84.13 | 1.06 | |
| Maximum of Months | 0.623425E+09 | 1.19 | 428.71 | 1.23 |
Report: FanReportMonthly
For: M N1 APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.107173E+09 | 0.73 | 40.01 | 01-JAN-00:10 | 0.73 |
| February | 96801429.15 | 0.73 | 40.01 | 01-FEB-00:10 | 0.73 |
| March | 0.107173E+09 | 0.73 | 40.01 | 01-MAR-00:10 | 0.73 |
| April | 0.103716E+09 | 0.73 | 40.01 | 01-APR-00:10 | 0.73 |
| May | 0.107173E+09 | 0.73 | 40.01 | 01-MAY-00:10 | 0.73 |
| June | 0.103716E+09 | 0.73 | 40.01 | 01-JUN-00:10 | 0.73 |
| July | 0.107173E+09 | 0.72 | 40.01 | 01-JUL-00:10 | 0.72 |
| August | 0.107173E+09 | 0.72 | 40.01 | 01-AUG-00:10 | 0.72 |
| September | 0.103716E+09 | 0.72 | 40.01 | 01-SEP-00:10 | 0.72 |
| October | 0.107173E+09 | 0.72 | 40.01 | 01-OCT-00:10 | 0.73 |
| November | 0.103716E+09 | 0.73 | 40.01 | 01-NOV-00:10 | 0.73 |
| December | 0.107173E+09 | 0.73 | 40.01 | 01-DEC-00:10 | 0.73 |
| Annual Sum or Average | 0.126188E+10 | 0.73 | |||
| Minimum of Months | 96801429.15 | 0.72 | 40.01 | 0.72 | |
| Maximum of Months | 0.107173E+09 | 0.73 | 40.01 | 0.73 |
Report: FanReportMonthly
For: M N1 APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.107173E+09 | 0.73 | 40.01 | 01-JAN-00:10 | 0.73 |
| February | 96801429.15 | 0.73 | 40.01 | 01-FEB-00:10 | 0.73 |
| March | 0.107173E+09 | 0.73 | 40.01 | 01-MAR-00:10 | 0.73 |
| April | 0.103716E+09 | 0.73 | 40.01 | 01-APR-00:10 | 0.73 |
| May | 0.107173E+09 | 0.73 | 40.01 | 01-MAY-00:10 | 0.73 |
| June | 0.103716E+09 | 0.72 | 40.01 | 01-JUN-00:10 | 0.73 |
| July | 0.107173E+09 | 0.72 | 40.01 | 01-JUL-00:10 | 0.72 |
| August | 0.107173E+09 | 0.72 | 40.01 | 01-AUG-00:10 | 0.72 |
| September | 0.103716E+09 | 0.72 | 40.01 | 01-SEP-00:10 | 0.72 |
| October | 0.107173E+09 | 0.72 | 40.01 | 01-OCT-00:10 | 0.73 |
| November | 0.103716E+09 | 0.73 | 40.01 | 01-NOV-00:10 | 0.73 |
| December | 0.107173E+09 | 0.73 | 40.01 | 01-DEC-00:10 | 0.73 |
| Annual Sum or Average | 0.126188E+10 | 0.73 | |||
| Minimum of Months | 96801429.15 | 0.72 | 40.01 | 0.72 | |
| Maximum of Months | 0.107173E+09 | 0.73 | 40.01 | 0.73 |
Report: FanReportMonthly
For: SPLIT MN2 SUPPLY FAN
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 36469939.30 | 0.49 | 101.74 | 28-JAN-06:00 | 1.06 |
| February | 19119568.61 | 0.25 | 87.67 | 03-FEB-05:00 | 1.06 |
| March | 15873502.54 | 0.20 | 97.58 | 22-MAR-16:10 | 1.23 |
| April | 0.198526E+09 | 0.88 | 298.49 | 21-APR-15:10 | 1.18 |
| May | 0.411441E+09 | 1.17 | 340.21 | 19-MAY-17:17 | 1.17 |
| June | 0.572489E+09 | 1.19 | 427.58 | 15-JUN-17:00 | 1.15 |
| July | 0.623671E+09 | 1.18 | 393.27 | 03-JUL-17:00 | 1.15 |
| August | 0.524324E+09 | 1.19 | 357.19 | 07-AUG-16:04 | 1.16 |
| September | 0.389839E+09 | 1.19 | 277.58 | 01-SEP-16:03 | 1.17 |
| October | 0.174336E+09 | 0.92 | 259.00 | 03-OCT-15:10 | 1.18 |
| November | 10796744.45 | 0.19 | 84.34 | 28-NOV-05:00 | 1.06 |
| December | 54175105.24 | 0.63 | 94.63 | 31-DEC-07:00 | 1.06 |
| Annual Sum or Average | 0.303106E+10 | 0.79 | |||
| Minimum of Months | 10796744.45 | 0.19 | 84.34 | 1.06 | |
| Maximum of Months | 0.623671E+09 | 1.19 | 427.58 | 1.23 |
Report: FanReportMonthly
For: M N2 APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.107173E+09 | 0.73 | 40.01 | 01-JAN-00:10 | 0.73 |
| February | 96801429.15 | 0.73 | 40.01 | 01-FEB-00:10 | 0.73 |
| March | 0.107173E+09 | 0.73 | 40.01 | 01-MAR-00:10 | 0.73 |
| April | 0.103716E+09 | 0.73 | 40.01 | 01-APR-00:10 | 0.73 |
| May | 0.107173E+09 | 0.73 | 40.01 | 01-MAY-00:10 | 0.73 |
| June | 0.103716E+09 | 0.73 | 40.01 | 01-JUN-00:10 | 0.73 |
| July | 0.107173E+09 | 0.72 | 40.01 | 01-JUL-00:10 | 0.72 |
| August | 0.107173E+09 | 0.72 | 40.01 | 01-AUG-00:10 | 0.72 |
| September | 0.103716E+09 | 0.72 | 40.01 | 01-SEP-00:10 | 0.72 |
| October | 0.107173E+09 | 0.72 | 40.01 | 01-OCT-00:10 | 0.73 |
| November | 0.103716E+09 | 0.73 | 40.01 | 01-NOV-00:10 | 0.73 |
| December | 0.107173E+09 | 0.73 | 40.01 | 01-DEC-00:10 | 0.73 |
| Annual Sum or Average | 0.126188E+10 | 0.73 | |||
| Minimum of Months | 96801429.15 | 0.72 | 40.01 | 0.72 | |
| Maximum of Months | 0.107173E+09 | 0.73 | 40.01 | 0.73 |
Report: FanReportMonthly
For: M N2 APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.107173E+09 | 0.73 | 40.01 | 01-JAN-00:10 | 0.73 |
| February | 96801429.15 | 0.73 | 40.01 | 01-FEB-00:10 | 0.73 |
| March | 0.107173E+09 | 0.73 | 40.01 | 01-MAR-00:10 | 0.73 |
| April | 0.103716E+09 | 0.73 | 40.01 | 01-APR-00:10 | 0.73 |
| May | 0.107173E+09 | 0.73 | 40.01 | 01-MAY-00:10 | 0.73 |
| June | 0.103716E+09 | 0.72 | 40.01 | 01-JUN-00:10 | 0.73 |
| July | 0.107173E+09 | 0.72 | 40.01 | 01-JUL-00:10 | 0.72 |
| August | 0.107173E+09 | 0.72 | 40.01 | 01-AUG-00:10 | 0.72 |
| September | 0.103716E+09 | 0.72 | 40.01 | 01-SEP-00:10 | 0.72 |
| October | 0.107173E+09 | 0.72 | 40.01 | 01-OCT-00:10 | 0.73 |
| November | 0.103716E+09 | 0.73 | 40.01 | 01-NOV-00:10 | 0.73 |
| December | 0.107173E+09 | 0.73 | 40.01 | 01-DEC-00:10 | 0.73 |
| Annual Sum or Average | 0.126188E+10 | 0.73 | |||
| Minimum of Months | 96801429.15 | 0.72 | 40.01 | 0.72 | |
| Maximum of Months | 0.107173E+09 | 0.73 | 40.01 | 0.73 |
Report: FanReportMonthly
For: SPLIT MS1 SUPPLY FAN
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 35294678.23 | 0.31 | 180.86 | 12-JAN-15:00 | 1.21 |
| February | 58673307.78 | 0.37 | 252.20 | 20-FEB-15:00 | 1.20 |
| March | 87771096.65 | 0.50 | 233.89 | 16-MAR-15:10 | 1.20 |
| April | 0.276947E+09 | 1.00 | 345.99 | 21-APR-14:10 | 1.17 |
| May | 0.428292E+09 | 1.17 | 346.98 | 19-MAY-17:05 | 1.17 |
| June | 0.565527E+09 | 1.19 | 416.42 | 15-JUN-16:08 | 1.16 |
| July | 0.628815E+09 | 1.18 | 394.35 | 03-JUL-17:00 | 1.15 |
| August | 0.571656E+09 | 1.19 | 378.55 | 07-AUG-16:10 | 1.16 |
| September | 0.512057E+09 | 1.19 | 389.25 | 19-SEP-14:10 | 1.16 |
| October | 0.353313E+09 | 1.12 | 382.21 | 01-OCT-15:10 | 1.16 |
| November | 0.140586E+09 | 0.65 | 290.85 | 09-NOV-14:00 | 1.18 |
| December | 20078868.29 | 0.28 | 143.05 | 16-DEC-14:40 | 1.22 |
| Annual Sum or Average | 0.367901E+10 | 0.85 | |||
| Minimum of Months | 20078868.29 | 0.28 | 143.05 | 1.15 | |
| Maximum of Months | 0.628815E+09 | 1.19 | 416.42 | 1.22 |
Report: FanReportMonthly
For: M S1 APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.107173E+09 | 0.73 | 40.01 | 01-JAN-00:10 | 0.73 |
| February | 96801429.15 | 0.73 | 40.01 | 01-FEB-00:10 | 0.73 |
| March | 0.107173E+09 | 0.73 | 40.01 | 01-MAR-00:10 | 0.73 |
| April | 0.103716E+09 | 0.73 | 40.01 | 01-APR-00:10 | 0.73 |
| May | 0.107173E+09 | 0.73 | 40.01 | 01-MAY-00:10 | 0.73 |
| June | 0.103716E+09 | 0.73 | 40.01 | 01-JUN-00:10 | 0.73 |
| July | 0.107173E+09 | 0.72 | 40.01 | 01-JUL-00:10 | 0.72 |
| August | 0.107173E+09 | 0.72 | 40.01 | 01-AUG-00:10 | 0.72 |
| September | 0.103716E+09 | 0.72 | 40.01 | 01-SEP-00:10 | 0.72 |
| October | 0.107173E+09 | 0.72 | 40.01 | 01-OCT-00:10 | 0.73 |
| November | 0.103716E+09 | 0.73 | 40.01 | 01-NOV-00:10 | 0.73 |
| December | 0.107173E+09 | 0.73 | 40.01 | 01-DEC-00:10 | 0.73 |
| Annual Sum or Average | 0.126188E+10 | 0.73 | |||
| Minimum of Months | 96801429.15 | 0.72 | 40.01 | 0.72 | |
| Maximum of Months | 0.107173E+09 | 0.73 | 40.01 | 0.73 |
Report: FanReportMonthly
For: M S1 APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.107173E+09 | 0.73 | 40.01 | 01-JAN-00:10 | 0.73 |
| February | 96801429.15 | 0.73 | 40.01 | 01-FEB-00:10 | 0.73 |
| March | 0.107173E+09 | 0.73 | 40.01 | 01-MAR-00:10 | 0.73 |
| April | 0.103716E+09 | 0.73 | 40.01 | 01-APR-00:10 | 0.73 |
| May | 0.107173E+09 | 0.73 | 40.01 | 01-MAY-00:10 | 0.73 |
| June | 0.103716E+09 | 0.73 | 40.01 | 01-JUN-00:10 | 0.73 |
| July | 0.107173E+09 | 0.72 | 40.01 | 01-JUL-00:10 | 0.72 |
| August | 0.107173E+09 | 0.72 | 40.01 | 01-AUG-00:10 | 0.72 |
| September | 0.103716E+09 | 0.72 | 40.01 | 01-SEP-00:10 | 0.72 |
| October | 0.107173E+09 | 0.72 | 40.01 | 01-OCT-00:10 | 0.73 |
| November | 0.103716E+09 | 0.73 | 40.01 | 01-NOV-00:10 | 0.73 |
| December | 0.107173E+09 | 0.73 | 40.01 | 01-DEC-00:10 | 0.73 |
| Annual Sum or Average | 0.126188E+10 | 0.73 | |||
| Minimum of Months | 96801429.15 | 0.72 | 40.01 | 0.72 | |
| Maximum of Months | 0.107173E+09 | 0.73 | 40.01 | 0.73 |
Report: FanReportMonthly
For: SPLIT MS2 SUPPLY FAN
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 35319844.31 | 0.31 | 180.87 | 12-JAN-15:00 | 1.21 |
| February | 59441051.13 | 0.38 | 253.14 | 20-FEB-15:00 | 1.19 |
| March | 88523751.93 | 0.51 | 233.90 | 16-MAR-15:10 | 1.20 |
| April | 0.277830E+09 | 1.00 | 346.69 | 21-APR-14:20 | 1.17 |
| May | 0.428708E+09 | 1.18 | 347.41 | 19-MAY-14:00 | 1.16 |
| June | 0.565870E+09 | 1.19 | 415.75 | 15-JUN-16:04 | 1.16 |
| July | 0.629064E+09 | 1.18 | 394.67 | 03-JUL-17:00 | 1.15 |
| August | 0.571915E+09 | 1.19 | 377.86 | 07-AUG-16:06 | 1.16 |
| September | 0.512178E+09 | 1.19 | 389.77 | 19-SEP-14:00 | 1.15 |
| October | 0.352850E+09 | 1.12 | 381.94 | 01-OCT-15:10 | 1.16 |
| November | 0.140771E+09 | 0.65 | 291.50 | 09-NOV-14:00 | 1.18 |
| December | 20372397.38 | 0.28 | 144.26 | 16-DEC-14:50 | 1.22 |
| Annual Sum or Average | 0.368284E+10 | 0.85 | |||
| Minimum of Months | 20372397.38 | 0.28 | 144.26 | 1.15 | |
| Maximum of Months | 0.629064E+09 | 1.19 | 415.75 | 1.22 |
Report: FanReportMonthly
For: M S2 APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.107173E+09 | 0.73 | 40.01 | 01-JAN-00:10 | 0.73 |
| February | 96801429.15 | 0.73 | 40.01 | 01-FEB-00:10 | 0.73 |
| March | 0.107173E+09 | 0.73 | 40.01 | 01-MAR-00:10 | 0.73 |
| April | 0.103716E+09 | 0.73 | 40.01 | 01-APR-00:10 | 0.73 |
| May | 0.107173E+09 | 0.73 | 40.01 | 01-MAY-00:10 | 0.73 |
| June | 0.103716E+09 | 0.73 | 40.01 | 01-JUN-00:10 | 0.73 |
| July | 0.107173E+09 | 0.72 | 40.01 | 01-JUL-00:10 | 0.72 |
| August | 0.107173E+09 | 0.72 | 40.01 | 01-AUG-00:10 | 0.72 |
| September | 0.103716E+09 | 0.72 | 40.01 | 01-SEP-00:10 | 0.72 |
| October | 0.107173E+09 | 0.72 | 40.01 | 01-OCT-00:10 | 0.73 |
| November | 0.103716E+09 | 0.73 | 40.01 | 01-NOV-00:10 | 0.73 |
| December | 0.107173E+09 | 0.73 | 40.01 | 01-DEC-00:10 | 0.73 |
| Annual Sum or Average | 0.126188E+10 | 0.73 | |||
| Minimum of Months | 96801429.15 | 0.72 | 40.01 | 0.72 | |
| Maximum of Months | 0.107173E+09 | 0.73 | 40.01 | 0.73 |
Report: FanReportMonthly
For: M S2 APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.107173E+09 | 0.73 | 40.01 | 01-JAN-00:10 | 0.73 |
| February | 96801429.15 | 0.73 | 40.01 | 01-FEB-00:10 | 0.73 |
| March | 0.107173E+09 | 0.73 | 40.01 | 01-MAR-00:10 | 0.73 |
| April | 0.103716E+09 | 0.73 | 40.01 | 01-APR-00:10 | 0.73 |
| May | 0.107173E+09 | 0.73 | 40.01 | 01-MAY-00:10 | 0.73 |
| June | 0.103716E+09 | 0.73 | 40.01 | 01-JUN-00:10 | 0.73 |
| July | 0.107173E+09 | 0.72 | 40.01 | 01-JUL-00:10 | 0.72 |
| August | 0.107173E+09 | 0.72 | 40.01 | 01-AUG-00:10 | 0.72 |
| September | 0.103716E+09 | 0.72 | 40.01 | 01-SEP-00:10 | 0.72 |
| October | 0.107173E+09 | 0.72 | 40.01 | 01-OCT-00:10 | 0.73 |
| November | 0.103716E+09 | 0.73 | 40.01 | 01-NOV-00:10 | 0.73 |
| December | 0.107173E+09 | 0.73 | 40.01 | 01-DEC-00:10 | 0.73 |
| Annual Sum or Average | 0.126188E+10 | 0.73 | |||
| Minimum of Months | 96801429.15 | 0.72 | 40.01 | 0.72 | |
| Maximum of Months | 0.107173E+09 | 0.73 | 40.01 | 0.73 |
Report: FanReportMonthly
For: SPLIT TSW SUPPLY FAN
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 90399336.24 | 0.77 | 141.08 | 12-JAN-15:10 | 1.20 |
| February | 80864648.78 | 0.71 | 184.63 | 20-FEB-15:30 | 1.19 |
| March | 79017950.69 | 0.66 | 196.33 | 14-MAR-16:15 | 1.19 |
| April | 0.164696E+09 | 0.74 | 310.59 | 21-APR-15:10 | 1.14 |
| May | 0.278036E+09 | 0.95 | 342.99 | 19-MAY-16:40 | 1.13 |
| June | 0.404116E+09 | 1.15 | 409.35 | 15-JUN-16:30 | 1.12 |
| July | 0.435062E+09 | 1.17 | 361.73 | 02-JUL-16:00 | 1.12 |
| August | 0.377044E+09 | 1.15 | 358.58 | 07-AUG-16:10 | 1.12 |
| September | 0.304726E+09 | 1.00 | 337.22 | 19-SEP-16:10 | 1.13 |
| October | 0.165447E+09 | 0.67 | 320.25 | 01-OCT-15:10 | 1.14 |
| November | 89956914.44 | 0.75 | 205.93 | 09-NOV-15:10 | 1.18 |
| December | 99741507.13 | 0.76 | 130.48 | 27-DEC-06:00 | 1.06 |
| Annual Sum or Average | 0.256911E+10 | 0.87 | |||
| Minimum of Months | 79017950.69 | 0.66 | 130.48 | 1.06 | |
| Maximum of Months | 0.435062E+09 | 1.17 | 409.35 | 1.20 |
Report: FanReportMonthly
For: T SW APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.73 | 20.01 | 01-JAN-00:10 | 0.73 |
| February | 48400714.57 | 0.73 | 20.01 | 01-FEB-00:10 | 0.73 |
| March | 53586505.42 | 0.73 | 20.01 | 01-MAR-00:10 | 0.73 |
| April | 51857908.47 | 0.73 | 20.01 | 01-APR-00:10 | 0.73 |
| May | 53586505.42 | 0.73 | 20.01 | 01-MAY-00:10 | 0.73 |
| June | 51857908.47 | 0.73 | 20.01 | 01-JUN-00:10 | 0.73 |
| July | 53586505.42 | 0.72 | 20.01 | 01-JUL-00:10 | 0.72 |
| August | 53586505.42 | 0.72 | 20.01 | 01-AUG-00:10 | 0.72 |
| September | 51857908.47 | 0.72 | 20.01 | 01-SEP-00:10 | 0.72 |
| October | 53586505.42 | 0.72 | 20.01 | 01-OCT-00:10 | 0.73 |
| November | 51857908.47 | 0.73 | 20.01 | 01-NOV-00:10 | 0.73 |
| December | 53586505.42 | 0.73 | 20.01 | 01-DEC-00:10 | 0.73 |
| Annual Sum or Average | 0.630938E+09 | 0.73 | |||
| Minimum of Months | 48400714.57 | 0.72 | 20.01 | 0.72 | |
| Maximum of Months | 53586505.42 | 0.73 | 20.01 | 0.73 |
Report: FanReportMonthly
For: T SW APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.73 | 20.01 | 01-JAN-00:10 | 0.73 |
| February | 48400714.57 | 0.73 | 20.01 | 01-FEB-00:10 | 0.73 |
| March | 53586505.42 | 0.73 | 20.01 | 01-MAR-00:10 | 0.73 |
| April | 51857908.47 | 0.73 | 20.01 | 01-APR-00:10 | 0.73 |
| May | 53586505.42 | 0.73 | 20.01 | 01-MAY-00:10 | 0.73 |
| June | 51857908.47 | 0.73 | 20.01 | 01-JUN-00:10 | 0.73 |
| July | 53586505.42 | 0.72 | 20.01 | 01-JUL-00:10 | 0.72 |
| August | 53586505.42 | 0.72 | 20.01 | 01-AUG-00:10 | 0.72 |
| September | 51857908.47 | 0.72 | 20.01 | 01-SEP-00:10 | 0.72 |
| October | 53586505.42 | 0.72 | 20.01 | 01-OCT-00:10 | 0.73 |
| November | 51857908.47 | 0.73 | 20.01 | 01-NOV-00:10 | 0.73 |
| December | 53586505.42 | 0.73 | 20.01 | 01-DEC-00:10 | 0.73 |
| Annual Sum or Average | 0.630938E+09 | 0.73 | |||
| Minimum of Months | 48400714.57 | 0.72 | 20.01 | 0.72 | |
| Maximum of Months | 53586505.42 | 0.73 | 20.01 | 0.73 |
Report: FanReportMonthly
For: SPLIT TNW SUPPLY FAN
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.117443E+09 | 0.90 | 144.56 | 28-JAN-06:00 | 1.06 |
| February | 83456464.47 | 0.78 | 150.41 | 09-FEB-01:00 | 1.06 |
| March | 62999144.12 | 0.65 | 124.86 | 02-MAR-06:00 | 1.06 |
| April | 0.131308E+09 | 0.71 | 279.42 | 21-APR-15:10 | 1.15 |
| May | 0.269150E+09 | 0.95 | 339.31 | 19-MAY-17:00 | 1.13 |
| June | 0.407658E+09 | 1.15 | 417.11 | 15-JUN-17:00 | 1.11 |
| July | 0.432472E+09 | 1.17 | 357.06 | 26-JUL-17:30 | 1.12 |
| August | 0.351250E+09 | 1.15 | 344.61 | 07-AUG-16:06 | 1.13 |
| September | 0.241258E+09 | 0.98 | 275.61 | 01-SEP-16:13 | 1.15 |
| October | 89374128.11 | 0.60 | 261.30 | 05-OCT-16:10 | 1.15 |
| November | 69938171.67 | 0.69 | 128.00 | 28-NOV-05:00 | 1.06 |
| December | 0.136566E+09 | 0.95 | 140.01 | 31-DEC-07:00 | 1.06 |
| Annual Sum or Average | 0.239287E+10 | 0.89 | |||
| Minimum of Months | 62999144.12 | 0.60 | 124.86 | 1.06 | |
| Maximum of Months | 0.432472E+09 | 1.17 | 417.11 | 1.15 |
Report: FanReportMonthly
For: T NW APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.73 | 20.01 | 01-JAN-00:10 | 0.73 |
| February | 48400714.57 | 0.73 | 20.01 | 01-FEB-00:10 | 0.73 |
| March | 53586505.42 | 0.73 | 20.01 | 01-MAR-00:10 | 0.73 |
| April | 51857908.47 | 0.73 | 20.01 | 01-APR-00:10 | 0.73 |
| May | 53586505.42 | 0.73 | 20.01 | 01-MAY-00:10 | 0.73 |
| June | 51857908.47 | 0.73 | 20.01 | 01-JUN-00:10 | 0.73 |
| July | 53586505.42 | 0.72 | 20.01 | 01-JUL-00:10 | 0.72 |
| August | 53586505.42 | 0.72 | 20.01 | 01-AUG-00:10 | 0.72 |
| September | 51857908.47 | 0.72 | 20.01 | 01-SEP-00:10 | 0.72 |
| October | 53586505.42 | 0.72 | 20.01 | 01-OCT-00:10 | 0.73 |
| November | 51857908.47 | 0.73 | 20.01 | 01-NOV-00:10 | 0.73 |
| December | 53586505.42 | 0.73 | 20.01 | 01-DEC-00:10 | 0.73 |
| Annual Sum or Average | 0.630938E+09 | 0.73 | |||
| Minimum of Months | 48400714.57 | 0.72 | 20.01 | 0.72 | |
| Maximum of Months | 53586505.42 | 0.73 | 20.01 | 0.73 |
Report: FanReportMonthly
For: T NW APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.73 | 20.01 | 01-JAN-00:10 | 0.73 |
| February | 48400714.57 | 0.73 | 20.01 | 01-FEB-00:10 | 0.73 |
| March | 53586505.42 | 0.73 | 20.01 | 01-MAR-00:10 | 0.73 |
| April | 51857908.47 | 0.73 | 20.01 | 01-APR-00:10 | 0.73 |
| May | 53586505.42 | 0.73 | 20.01 | 01-MAY-00:10 | 0.73 |
| June | 51857908.47 | 0.73 | 20.01 | 01-JUN-00:10 | 0.73 |
| July | 53586505.42 | 0.72 | 20.01 | 01-JUL-00:10 | 0.72 |
| August | 53586505.42 | 0.72 | 20.01 | 01-AUG-00:10 | 0.72 |
| September | 51857908.47 | 0.72 | 20.01 | 01-SEP-00:10 | 0.72 |
| October | 53586505.42 | 0.72 | 20.01 | 01-OCT-00:10 | 0.73 |
| November | 51857908.47 | 0.73 | 20.01 | 01-NOV-00:10 | 0.73 |
| December | 53586505.42 | 0.73 | 20.01 | 01-DEC-00:10 | 0.73 |
| Annual Sum or Average | 0.630938E+09 | 0.73 | |||
| Minimum of Months | 48400714.57 | 0.72 | 20.01 | 0.72 | |
| Maximum of Months | 53586505.42 | 0.73 | 20.01 | 0.73 |
Report: FanReportMonthly
For: SPLIT TSE SUPPLY FAN
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 84948156.07 | 0.74 | 132.75 | 28-JAN-06:00 | 1.06 |
| February | 76122519.55 | 0.69 | 157.02 | 20-FEB-15:00 | 1.19 |
| March | 73754012.77 | 0.64 | 150.45 | 21-MAR-15:10 | 1.20 |
| April | 0.162981E+09 | 0.75 | 292.59 | 21-APR-14:10 | 1.14 |
| May | 0.278754E+09 | 0.97 | 308.34 | 19-MAY-14:00 | 1.13 |
| June | 0.406920E+09 | 1.14 | 354.00 | 15-JUN-15:10 | 1.12 |
| July | 0.437094E+09 | 1.17 | 327.19 | 26-JUL-14:00 | 1.12 |
| August | 0.379332E+09 | 1.15 | 308.03 | 07-AUG-16:10 | 1.13 |
| September | 0.304602E+09 | 1.01 | 306.67 | 19-SEP-14:00 | 1.13 |
| October | 0.159355E+09 | 0.69 | 288.20 | 03-OCT-14:00 | 1.14 |
| November | 84957266.23 | 0.74 | 180.47 | 09-NOV-14:00 | 1.18 |
| December | 95389120.57 | 0.73 | 130.33 | 27-DEC-06:00 | 1.06 |
| Annual Sum or Average | 0.254421E+10 | 0.87 | |||
| Minimum of Months | 73754012.77 | 0.64 | 130.33 | 1.06 | |
| Maximum of Months | 0.437094E+09 | 1.17 | 354.00 | 1.20 |
Report: FanReportMonthly
For: T SE APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.73 | 20.01 | 01-JAN-00:10 | 0.73 |
| February | 48400714.57 | 0.73 | 20.01 | 01-FEB-00:10 | 0.73 |
| March | 53586505.42 | 0.73 | 20.01 | 01-MAR-00:10 | 0.73 |
| April | 51857908.47 | 0.73 | 20.01 | 01-APR-00:10 | 0.73 |
| May | 53586505.42 | 0.73 | 20.01 | 01-MAY-00:10 | 0.73 |
| June | 51857908.47 | 0.73 | 20.01 | 01-JUN-00:10 | 0.73 |
| July | 53586505.42 | 0.72 | 20.01 | 01-JUL-00:10 | 0.72 |
| August | 53586505.42 | 0.72 | 20.01 | 01-AUG-00:10 | 0.72 |
| September | 51857908.47 | 0.72 | 20.01 | 01-SEP-00:10 | 0.72 |
| October | 53586505.42 | 0.72 | 20.01 | 01-OCT-00:10 | 0.73 |
| November | 51857908.47 | 0.73 | 20.01 | 01-NOV-00:10 | 0.73 |
| December | 53586505.42 | 0.73 | 20.01 | 01-DEC-00:10 | 0.73 |
| Annual Sum or Average | 0.630938E+09 | 0.73 | |||
| Minimum of Months | 48400714.57 | 0.72 | 20.01 | 0.72 | |
| Maximum of Months | 53586505.42 | 0.73 | 20.01 | 0.73 |
Report: FanReportMonthly
For: T SE APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.73 | 20.01 | 01-JAN-00:10 | 0.73 |
| February | 48400714.57 | 0.73 | 20.01 | 01-FEB-00:10 | 0.73 |
| March | 53586505.42 | 0.73 | 20.01 | 01-MAR-00:10 | 0.73 |
| April | 51857908.47 | 0.73 | 20.01 | 01-APR-00:10 | 0.73 |
| May | 53586505.42 | 0.73 | 20.01 | 01-MAY-00:10 | 0.73 |
| June | 51857908.47 | 0.73 | 20.01 | 01-JUN-00:10 | 0.73 |
| July | 53586505.42 | 0.72 | 20.01 | 01-JUL-00:10 | 0.72 |
| August | 53586505.42 | 0.72 | 20.01 | 01-AUG-00:10 | 0.72 |
| September | 51857908.47 | 0.72 | 20.01 | 01-SEP-00:10 | 0.72 |
| October | 53586505.42 | 0.72 | 20.01 | 01-OCT-00:10 | 0.73 |
| November | 51857908.47 | 0.73 | 20.01 | 01-NOV-00:10 | 0.73 |
| December | 53586505.42 | 0.73 | 20.01 | 01-DEC-00:10 | 0.73 |
| Annual Sum or Average | 0.630938E+09 | 0.73 | |||
| Minimum of Months | 48400714.57 | 0.72 | 20.01 | 0.72 | |
| Maximum of Months | 53586505.42 | 0.73 | 20.01 | 0.73 |
Report: FanReportMonthly
For: SPLIT TNE SUPPLY FAN
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.115959E+09 | 0.96 | 145.91 | 28-JAN-06:00 | 1.06 |
| February | 78320197.41 | 0.76 | 149.87 | 09-FEB-01:00 | 1.06 |
| March | 56347484.31 | 0.60 | 126.10 | 02-MAR-06:00 | 1.06 |
| April | 0.129283E+09 | 0.72 | 256.40 | 21-APR-15:10 | 1.15 |
| May | 0.269981E+09 | 0.97 | 285.06 | 19-MAY-14:00 | 1.14 |
| June | 0.410497E+09 | 1.15 | 351.67 | 15-JUN-16:30 | 1.12 |
| July | 0.434500E+09 | 1.17 | 308.44 | 02-JUL-16:10 | 1.13 |
| August | 0.353795E+09 | 1.15 | 294.20 | 07-AUG-16:10 | 1.13 |
| September | 0.241340E+09 | 0.99 | 229.66 | 15-SEP-13:00 | 1.15 |
| October | 82697951.63 | 0.60 | 215.23 | 03-OCT-14:10 | 1.16 |
| November | 67835940.94 | 0.69 | 129.20 | 28-NOV-05:00 | 1.06 |
| December | 0.135075E+09 | 1.00 | 140.99 | 31-DEC-07:00 | 1.06 |
| Annual Sum or Average | 0.237563E+10 | 0.90 | |||
| Minimum of Months | 56347484.31 | 0.60 | 126.10 | 1.06 | |
| Maximum of Months | 0.434500E+09 | 1.17 | 351.67 | 1.16 |
Report: FanReportMonthly
For: T NE APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.73 | 20.01 | 01-JAN-00:10 | 0.73 |
| February | 48400714.57 | 0.73 | 20.01 | 01-FEB-00:10 | 0.73 |
| March | 53586505.42 | 0.73 | 20.01 | 01-MAR-00:10 | 0.73 |
| April | 51857908.47 | 0.73 | 20.01 | 01-APR-00:10 | 0.73 |
| May | 53586505.42 | 0.73 | 20.01 | 01-MAY-00:10 | 0.73 |
| June | 51857908.47 | 0.73 | 20.01 | 01-JUN-00:10 | 0.73 |
| July | 53586505.42 | 0.72 | 20.01 | 01-JUL-00:10 | 0.72 |
| August | 53586505.42 | 0.72 | 20.01 | 01-AUG-00:10 | 0.72 |
| September | 51857908.47 | 0.72 | 20.01 | 01-SEP-00:10 | 0.72 |
| October | 53586505.42 | 0.72 | 20.01 | 01-OCT-00:10 | 0.73 |
| November | 51857908.47 | 0.73 | 20.01 | 01-NOV-00:10 | 0.73 |
| December | 53586505.42 | 0.73 | 20.01 | 01-DEC-00:10 | 0.73 |
| Annual Sum or Average | 0.630938E+09 | 0.73 | |||
| Minimum of Months | 48400714.57 | 0.72 | 20.01 | 0.72 | |
| Maximum of Months | 53586505.42 | 0.73 | 20.01 | 0.73 |
Report: FanReportMonthly
For: T NE APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.73 | 20.01 | 01-JAN-00:10 | 0.73 |
| February | 48400714.57 | 0.73 | 20.01 | 01-FEB-00:10 | 0.73 |
| March | 53586505.42 | 0.73 | 20.01 | 01-MAR-00:10 | 0.73 |
| April | 51857908.47 | 0.73 | 20.01 | 01-APR-00:10 | 0.73 |
| May | 53586505.42 | 0.73 | 20.01 | 01-MAY-00:10 | 0.73 |
| June | 51857908.47 | 0.73 | 20.01 | 01-JUN-00:10 | 0.73 |
| July | 53586505.42 | 0.72 | 20.01 | 01-JUL-00:10 | 0.72 |
| August | 53586505.42 | 0.72 | 20.01 | 01-AUG-00:10 | 0.72 |
| September | 51857908.47 | 0.72 | 20.01 | 01-SEP-00:10 | 0.72 |
| October | 53586505.42 | 0.72 | 20.01 | 01-OCT-00:10 | 0.73 |
| November | 51857908.47 | 0.73 | 20.01 | 01-NOV-00:10 | 0.73 |
| December | 53586505.42 | 0.73 | 20.01 | 01-DEC-00:10 | 0.73 |
| Annual Sum or Average | 0.630938E+09 | 0.73 | |||
| Minimum of Months | 48400714.57 | 0.72 | 20.01 | 0.72 | |
| Maximum of Months | 53586505.42 | 0.73 | 20.01 | 0.73 |
Report: FanReportMonthly
For: SPLIT TN1 SUPPLY FAN
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 79536562.67 | 0.91 | 104.17 | 28-JAN-06:00 | 1.06 |
| February | 53149476.61 | 0.71 | 97.77 | 10-FEB-05:00 | 1.06 |
| March | 35934109.28 | 0.53 | 92.47 | 02-MAR-06:00 | 1.06 |
| April | 97476339.57 | 0.70 | 197.92 | 21-APR-15:10 | 1.17 |
| May | 0.214849E+09 | 0.99 | 226.07 | 19-MAY-17:10 | 1.15 |
| June | 0.330654E+09 | 1.17 | 288.17 | 15-JUN-17:00 | 1.14 |
| July | 0.357915E+09 | 1.18 | 255.52 | 01-JUL-17:00 | 1.14 |
| August | 0.290981E+09 | 1.17 | 243.50 | 07-AUG-16:10 | 1.14 |
| September | 0.197073E+09 | 1.02 | 186.92 | 01-SEP-16:03 | 1.16 |
| October | 65611172.72 | 0.54 | 177.89 | 03-OCT-14:10 | 1.17 |
| November | 44533327.65 | 0.62 | 91.64 | 28-NOV-05:00 | 1.06 |
| December | 96336031.40 | 0.96 | 99.69 | 31-DEC-07:00 | 1.06 |
| Annual Sum or Average | 0.186405E+10 | 0.88 | |||
| Minimum of Months | 35934109.28 | 0.53 | 91.64 | 1.06 | |
| Maximum of Months | 0.357915E+09 | 1.18 | 288.17 | 1.17 |
Report: FanReportMonthly
For: T N1 APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.73 | 20.01 | 01-JAN-00:10 | 0.73 |
| February | 48400714.57 | 0.73 | 20.01 | 01-FEB-00:10 | 0.73 |
| March | 53586505.42 | 0.73 | 20.01 | 01-MAR-00:10 | 0.73 |
| April | 51857908.47 | 0.73 | 20.01 | 01-APR-00:10 | 0.73 |
| May | 53586505.42 | 0.73 | 20.01 | 01-MAY-00:10 | 0.73 |
| June | 51857908.47 | 0.73 | 20.01 | 01-JUN-00:10 | 0.73 |
| July | 53586505.42 | 0.72 | 20.01 | 01-JUL-00:10 | 0.72 |
| August | 53586505.42 | 0.72 | 20.01 | 01-AUG-00:10 | 0.72 |
| September | 51857908.47 | 0.72 | 20.01 | 01-SEP-00:10 | 0.72 |
| October | 53586505.42 | 0.72 | 20.01 | 01-OCT-00:10 | 0.73 |
| November | 51857908.47 | 0.73 | 20.01 | 01-NOV-00:10 | 0.73 |
| December | 53586505.42 | 0.73 | 20.01 | 01-DEC-00:10 | 0.73 |
| Annual Sum or Average | 0.630938E+09 | 0.73 | |||
| Minimum of Months | 48400714.57 | 0.72 | 20.01 | 0.72 | |
| Maximum of Months | 53586505.42 | 0.73 | 20.01 | 0.73 |
Report: FanReportMonthly
For: T N1 APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.73 | 20.01 | 01-JAN-00:10 | 0.73 |
| February | 48400714.57 | 0.73 | 20.01 | 01-FEB-00:10 | 0.73 |
| March | 53586505.42 | 0.73 | 20.01 | 01-MAR-00:10 | 0.73 |
| April | 51857908.47 | 0.73 | 20.01 | 01-APR-00:10 | 0.73 |
| May | 53586505.42 | 0.73 | 20.01 | 01-MAY-00:10 | 0.73 |
| June | 51857908.47 | 0.72 | 20.01 | 01-JUN-00:10 | 0.73 |
| July | 53586505.42 | 0.72 | 20.01 | 01-JUL-00:10 | 0.72 |
| August | 53586505.42 | 0.72 | 20.01 | 01-AUG-00:10 | 0.72 |
| September | 51857908.47 | 0.72 | 20.01 | 01-SEP-00:10 | 0.72 |
| October | 53586505.42 | 0.72 | 20.01 | 01-OCT-00:10 | 0.73 |
| November | 51857908.47 | 0.73 | 20.01 | 01-NOV-00:10 | 0.73 |
| December | 53586505.42 | 0.73 | 20.01 | 01-DEC-00:10 | 0.73 |
| Annual Sum or Average | 0.630938E+09 | 0.73 | |||
| Minimum of Months | 48400714.57 | 0.72 | 20.01 | 0.72 | |
| Maximum of Months | 53586505.42 | 0.73 | 20.01 | 0.73 |
Report: FanReportMonthly
For: SPLIT TN2 SUPPLY FAN
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 79681664.73 | 0.91 | 104.30 | 28-JAN-06:00 | 1.06 |
| February | 53129127.35 | 0.71 | 97.87 | 10-FEB-05:00 | 1.06 |
| March | 36044245.62 | 0.53 | 92.55 | 02-MAR-06:00 | 1.06 |
| April | 98009257.97 | 0.71 | 197.99 | 21-APR-15:10 | 1.17 |
| May | 0.215240E+09 | 0.99 | 224.63 | 19-MAY-17:00 | 1.15 |
| June | 0.330850E+09 | 1.17 | 286.71 | 15-JUN-17:00 | 1.14 |
| July | 0.358056E+09 | 1.18 | 254.47 | 01-JUL-17:00 | 1.14 |
| August | 0.291167E+09 | 1.17 | 242.48 | 07-AUG-16:10 | 1.14 |
| September | 0.197328E+09 | 1.02 | 186.58 | 01-SEP-15:10 | 1.16 |
| October | 65798212.34 | 0.54 | 177.88 | 03-OCT-14:10 | 1.17 |
| November | 44746003.84 | 0.62 | 91.73 | 28-NOV-05:00 | 1.06 |
| December | 96414272.16 | 0.96 | 99.80 | 31-DEC-07:00 | 1.06 |
| Annual Sum or Average | 0.186646E+10 | 0.88 | |||
| Minimum of Months | 36044245.62 | 0.53 | 91.73 | 1.06 | |
| Maximum of Months | 0.358056E+09 | 1.18 | 286.71 | 1.17 |
Report: FanReportMonthly
For: T N2 APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.73 | 20.01 | 01-JAN-00:10 | 0.73 |
| February | 48400714.57 | 0.73 | 20.01 | 01-FEB-00:10 | 0.73 |
| March | 53586505.42 | 0.73 | 20.01 | 01-MAR-00:10 | 0.73 |
| April | 51857908.47 | 0.73 | 20.01 | 01-APR-00:10 | 0.73 |
| May | 53586505.42 | 0.73 | 20.01 | 01-MAY-00:10 | 0.73 |
| June | 51857908.47 | 0.73 | 20.01 | 01-JUN-00:10 | 0.73 |
| July | 53586505.42 | 0.72 | 20.01 | 01-JUL-00:10 | 0.72 |
| August | 53586505.42 | 0.72 | 20.01 | 01-AUG-00:10 | 0.72 |
| September | 51857908.47 | 0.72 | 20.01 | 01-SEP-00:10 | 0.72 |
| October | 53586505.42 | 0.72 | 20.01 | 01-OCT-00:10 | 0.73 |
| November | 51857908.47 | 0.73 | 20.01 | 01-NOV-00:10 | 0.73 |
| December | 53586505.42 | 0.73 | 20.01 | 01-DEC-00:10 | 0.73 |
| Annual Sum or Average | 0.630938E+09 | 0.73 | |||
| Minimum of Months | 48400714.57 | 0.72 | 20.01 | 0.72 | |
| Maximum of Months | 53586505.42 | 0.73 | 20.01 | 0.73 |
Report: FanReportMonthly
For: T N2 APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.73 | 20.01 | 01-JAN-00:10 | 0.73 |
| February | 48400714.57 | 0.73 | 20.01 | 01-FEB-00:10 | 0.73 |
| March | 53586505.42 | 0.73 | 20.01 | 01-MAR-00:10 | 0.73 |
| April | 51857908.47 | 0.73 | 20.01 | 01-APR-00:10 | 0.73 |
| May | 53586505.42 | 0.73 | 20.01 | 01-MAY-00:10 | 0.73 |
| June | 51857908.47 | 0.72 | 20.01 | 01-JUN-00:10 | 0.73 |
| July | 53586505.42 | 0.72 | 20.01 | 01-JUL-00:10 | 0.72 |
| August | 53586505.42 | 0.72 | 20.01 | 01-AUG-00:10 | 0.72 |
| September | 51857908.47 | 0.72 | 20.01 | 01-SEP-00:10 | 0.72 |
| October | 53586505.42 | 0.72 | 20.01 | 01-OCT-00:10 | 0.73 |
| November | 51857908.47 | 0.73 | 20.01 | 01-NOV-00:10 | 0.73 |
| December | 53586505.42 | 0.73 | 20.01 | 01-DEC-00:10 | 0.73 |
| Annual Sum or Average | 0.630938E+09 | 0.73 | |||
| Minimum of Months | 48400714.57 | 0.72 | 20.01 | 0.72 | |
| Maximum of Months | 53586505.42 | 0.73 | 20.01 | 0.73 |
Report: FanReportMonthly
For: SPLIT TS1 SUPPLY FAN
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 56112535.81 | 0.70 | 115.83 | 12-JAN-15:00 | 1.20 |
| February | 52448027.29 | 0.63 | 144.13 | 20-FEB-15:00 | 1.19 |
| March | 50825130.35 | 0.57 | 137.63 | 16-MAR-15:10 | 1.20 |
| April | 0.131241E+09 | 0.74 | 232.05 | 21-APR-14:20 | 1.16 |
| May | 0.223797E+09 | 0.99 | 243.05 | 19-MAY-14:00 | 1.15 |
| June | 0.326989E+09 | 1.17 | 285.12 | 15-JUN-16:01 | 1.14 |
| July | 0.360588E+09 | 1.18 | 265.72 | 02-JUL-16:01 | 1.14 |
| August | 0.317151E+09 | 1.17 | 257.57 | 07-AUG-16:10 | 1.14 |
| September | 0.261865E+09 | 1.04 | 262.91 | 19-SEP-14:00 | 1.14 |
| October | 0.145807E+09 | 0.69 | 251.37 | 03-OCT-14:00 | 1.14 |
| November | 66243126.63 | 0.68 | 170.34 | 09-NOV-14:10 | 1.18 |
| December | 63387681.73 | 0.69 | 94.99 | 27-DEC-06:00 | 1.06 |
| Annual Sum or Average | 0.205645E+10 | 0.85 | |||
| Minimum of Months | 50825130.35 | 0.57 | 94.99 | 1.06 | |
| Maximum of Months | 0.360588E+09 | 1.18 | 285.12 | 1.20 |
Report: FanReportMonthly
For: T S1 APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.73 | 20.01 | 01-JAN-00:10 | 0.73 |
| February | 48400714.57 | 0.73 | 20.01 | 01-FEB-00:10 | 0.73 |
| March | 53586505.42 | 0.73 | 20.01 | 01-MAR-00:10 | 0.73 |
| April | 51857908.47 | 0.73 | 20.01 | 01-APR-00:10 | 0.73 |
| May | 53586505.42 | 0.73 | 20.01 | 01-MAY-00:10 | 0.73 |
| June | 51857908.47 | 0.73 | 20.01 | 01-JUN-00:10 | 0.73 |
| July | 53586505.42 | 0.72 | 20.01 | 01-JUL-00:10 | 0.72 |
| August | 53586505.42 | 0.72 | 20.01 | 01-AUG-00:10 | 0.72 |
| September | 51857908.47 | 0.72 | 20.01 | 01-SEP-00:10 | 0.72 |
| October | 53586505.42 | 0.72 | 20.01 | 01-OCT-00:10 | 0.73 |
| November | 51857908.47 | 0.73 | 20.01 | 01-NOV-00:10 | 0.73 |
| December | 53586505.42 | 0.73 | 20.01 | 01-DEC-00:10 | 0.73 |
| Annual Sum or Average | 0.630938E+09 | 0.73 | |||
| Minimum of Months | 48400714.57 | 0.72 | 20.01 | 0.72 | |
| Maximum of Months | 53586505.42 | 0.73 | 20.01 | 0.73 |
Report: FanReportMonthly
For: T S1 APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.73 | 20.01 | 01-JAN-00:10 | 0.73 |
| February | 48400714.57 | 0.73 | 20.01 | 01-FEB-00:10 | 0.73 |
| March | 53586505.42 | 0.73 | 20.01 | 01-MAR-00:10 | 0.73 |
| April | 51857908.47 | 0.73 | 20.01 | 01-APR-00:10 | 0.73 |
| May | 53586505.42 | 0.73 | 20.01 | 01-MAY-00:10 | 0.73 |
| June | 51857908.47 | 0.72 | 20.01 | 01-JUN-00:10 | 0.73 |
| July | 53586505.42 | 0.72 | 20.01 | 01-JUL-00:10 | 0.72 |
| August | 53586505.42 | 0.72 | 20.01 | 01-AUG-00:10 | 0.72 |
| September | 51857908.47 | 0.72 | 20.01 | 01-SEP-00:10 | 0.72 |
| October | 53586505.42 | 0.72 | 20.01 | 01-OCT-00:10 | 0.73 |
| November | 51857908.47 | 0.73 | 20.01 | 01-NOV-00:10 | 0.73 |
| December | 53586505.42 | 0.73 | 20.01 | 01-DEC-00:10 | 0.73 |
| Annual Sum or Average | 0.630938E+09 | 0.73 | |||
| Minimum of Months | 48400714.57 | 0.72 | 20.01 | 0.72 | |
| Maximum of Months | 53586505.42 | 0.73 | 20.01 | 0.73 |
Report: FanReportMonthly
For: SPLIT TS2 SUPPLY FAN
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 56364882.96 | 0.70 | 115.96 | 12-JAN-15:00 | 1.20 |
| February | 52724988.47 | 0.63 | 144.70 | 20-FEB-15:00 | 1.19 |
| March | 51318668.21 | 0.57 | 137.66 | 16-MAR-15:10 | 1.20 |
| April | 0.131821E+09 | 0.74 | 232.67 | 21-APR-14:10 | 1.16 |
| May | 0.224201E+09 | 0.99 | 243.50 | 19-MAY-14:00 | 1.14 |
| June | 0.327196E+09 | 1.17 | 284.69 | 15-JUN-15:10 | 1.14 |
| July | 0.360734E+09 | 1.18 | 264.94 | 02-JUL-16:01 | 1.14 |
| August | 0.317320E+09 | 1.17 | 256.54 | 07-AUG-16:10 | 1.14 |
| September | 0.262051E+09 | 1.04 | 263.23 | 19-SEP-14:00 | 1.14 |
| October | 0.145872E+09 | 0.68 | 251.39 | 03-OCT-13:50 | 1.14 |
| November | 66670546.08 | 0.68 | 170.95 | 09-NOV-14:00 | 1.18 |
| December | 63648664.82 | 0.69 | 94.99 | 27-DEC-06:00 | 1.06 |
| Annual Sum or Average | 0.205992E+10 | 0.86 | |||
| Minimum of Months | 51318668.21 | 0.57 | 94.99 | 1.06 | |
| Maximum of Months | 0.360734E+09 | 1.18 | 284.69 | 1.20 |
Report: FanReportMonthly
For: T S2 APARTMENT ERV SUP FAN
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.73 | 20.01 | 01-JAN-00:10 | 0.73 |
| February | 48400714.57 | 0.73 | 20.01 | 01-FEB-00:10 | 0.73 |
| March | 53586505.42 | 0.73 | 20.01 | 01-MAR-00:10 | 0.73 |
| April | 51857908.47 | 0.73 | 20.01 | 01-APR-00:10 | 0.73 |
| May | 53586505.42 | 0.73 | 20.01 | 01-MAY-00:10 | 0.73 |
| June | 51857908.47 | 0.73 | 20.01 | 01-JUN-00:10 | 0.73 |
| July | 53586505.42 | 0.72 | 20.01 | 01-JUL-00:10 | 0.72 |
| August | 53586505.42 | 0.72 | 20.01 | 01-AUG-00:10 | 0.72 |
| September | 51857908.47 | 0.72 | 20.01 | 01-SEP-00:10 | 0.72 |
| October | 53586505.42 | 0.72 | 20.01 | 01-OCT-00:10 | 0.73 |
| November | 51857908.47 | 0.73 | 20.01 | 01-NOV-00:10 | 0.73 |
| December | 53586505.42 | 0.73 | 20.01 | 01-DEC-00:10 | 0.73 |
| Annual Sum or Average | 0.630938E+09 | 0.73 | |||
| Minimum of Months | 48400714.57 | 0.72 | 20.01 | 0.72 | |
| Maximum of Months | 53586505.42 | 0.73 | 20.01 | 0.73 |
Report: FanReportMonthly
For: T S2 APARTMENT ERV EXH FAN
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 53586505.42 | 0.73 | 20.01 | 01-JAN-00:10 | 0.73 |
| February | 48400714.57 | 0.73 | 20.01 | 01-FEB-00:10 | 0.73 |
| March | 53586505.42 | 0.73 | 20.01 | 01-MAR-00:10 | 0.73 |
| April | 51857908.47 | 0.73 | 20.01 | 01-APR-00:10 | 0.73 |
| May | 53586505.42 | 0.73 | 20.01 | 01-MAY-00:10 | 0.73 |
| June | 51857908.47 | 0.72 | 20.01 | 01-JUN-00:10 | 0.73 |
| July | 53586505.42 | 0.72 | 20.01 | 01-JUL-00:10 | 0.72 |
| August | 53586505.42 | 0.72 | 20.01 | 01-AUG-00:10 | 0.72 |
| September | 51857908.47 | 0.72 | 20.01 | 01-SEP-00:10 | 0.72 |
| October | 53586505.42 | 0.72 | 20.01 | 01-OCT-00:10 | 0.73 |
| November | 51857908.47 | 0.73 | 20.01 | 01-NOV-00:10 | 0.73 |
| December | 53586505.42 | 0.73 | 20.01 | 01-DEC-00:10 | 0.73 |
| Annual Sum or Average | 0.630938E+09 | 0.73 | |||
| Minimum of Months | 48400714.57 | 0.72 | 20.01 | 0.72 | |
| Maximum of Months | 53586505.42 | 0.73 | 20.01 | 0.73 |
Report: ZoneTemperatureOscillationReportMonthly
For: G SW APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: G NW APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: OFFICE
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: G NE APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: G N1 APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: G N2 APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: G S1 APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: G S2 APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: M SW APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: M NW APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: M SE APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: M NE APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: M N1 APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: M N2 APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: M S1 APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: M S2 APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: T SW APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: T NW APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: T SE APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: T NE APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: T N1 APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: T N2 APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: T S1 APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: T S2 APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: T CORRIDOR
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: G CORRIDOR
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: M CORRIDOR
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT GSW
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 21477299.83 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 31090598.36 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 28348960.72 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.303543E+09 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.769423E+09 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.122595E+10 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.151319E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.143530E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.130593E+10 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.788233E+09 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.214205E+09 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 18304632.53 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.765499E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 18304632.53 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.151319E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT GNW
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 56320141.01 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 45797519.91 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 31856336.80 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.195197E+09 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.737682E+09 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.124282E+10 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.150638E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.134213E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.106315E+10 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.448134E+09 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 18138963.54 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 55688190.85 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.674329E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 18138963.54 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.150638E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT OFFICE
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.132735E+10 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.121334E+10 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.137753E+10 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.150023E+10 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.178666E+10 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.198809E+10 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.207872E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.213839E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.195524E+10 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.178575E+10 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.146625E+10 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.132699E+10 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.199445E+11 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.121334E+10 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.213839E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT GNE
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 56242181.95 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 43196398.33 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 30067946.58 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.196044E+09 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.744001E+09 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.125576E+10 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.151505E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.135094E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.106571E+10 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.426443E+09 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 15633048.75 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 54994775.78 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.675408E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 15633048.75 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.151505E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT GN1
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 31652676.46 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 24317628.46 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 14396710.25 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.169751E+09 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.646044E+09 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.105859E+10 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.127840E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.112799E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.883930E+09 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.392752E+09 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 11327112.36 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 32381564.48 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.567153E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 11327112.36 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.127840E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT GN2
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 31754151.47 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 24254619.16 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 14410209.26 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.171254E+09 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.647250E+09 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.105949E+10 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.127894E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.112859E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.884229E+09 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.391822E+09 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 11211588.08 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 32404750.27 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.567561E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 11211588.08 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.127894E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT GS1
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 16141501.30 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 22989189.24 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 24761151.81 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.295195E+09 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.684068E+09 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.104610E+10 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.129067E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.122804E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.113688E+10 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.756288E+09 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.266993E+09 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 7581161.85 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.677570E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 7581161.85 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.129067E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT GS2
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 16863420.31 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 24570418.28 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 28763209.36 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.329544E+09 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.757396E+09 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.114621E+10 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.140652E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.133688E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.123813E+10 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.824224E+09 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.288468E+09 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 9462996.04 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.740703E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 9462996.04 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.140652E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT MSW
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 80217584.72 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.191545E+09 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.320402E+09 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.132236E+10 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.225254E+10 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.309612E+10 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.341999E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.301690E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.257088E+10 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.154885E+10 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.459700E+09 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 47924937.03 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.183274E+11 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 47924937.03 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.341999E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT MNW
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 89556952.84 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 54853681.39 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 66268461.11 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.100736E+10 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.218008E+10 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.312427E+10 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.339564E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.280980E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.204697E+10 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.837197E+09 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 42715592.32 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.112652E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.157674E+11 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 42715592.32 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.339564E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT MSE
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 65654176.58 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.194661E+09 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.320133E+09 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.135202E+10 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.227256E+10 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.312015E+10 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.343877E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.303562E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.257560E+10 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.150403E+10 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.442220E+09 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 42873785.87 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.183643E+11 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 42873785.87 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.343877E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT MNE
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 88701328.40 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 49344332.38 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 58032345.52 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.103115E+10 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.220046E+10 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.314799E+10 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.341413E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.282981E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.205492E+10 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.787325E+09 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 39606054.72 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.111219E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.158127E+11 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 39606054.72 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.341413E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT MN1
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 36197904.95 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 21938587.45 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 51004704.37 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.835229E+09 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.176699E+10 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.249905E+10 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.277173E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.230737E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.169896E+10 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.749002E+09 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 23168251.69 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 54056744.04 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.128147E+11 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 21938587.45 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.277173E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT MN2
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 36469939.30 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 22154910.70 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 52268447.58 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.839227E+09 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.176876E+10 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.250053E+10 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.277282E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.230857E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.169974E+10 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.747650E+09 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 23153077.95 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 54175105.24 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.128255E+11 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 22154910.70 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.277282E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT MS1
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.138963E+09 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.243158E+09 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.363926E+09 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.116914E+10 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.184093E+10 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.247064E+10 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.279664E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.251682E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.222990E+10 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.150653E+10 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.583969E+09 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 70338922.02 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.159310E+11 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 70338922.02 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.279664E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT MS2
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.139069E+09 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.246343E+09 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.367078E+09 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.117284E+10 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.184269E+10 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.247216E+10 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.279775E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.251796E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.223043E+10 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.150456E+10 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.584673E+09 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 71468970.37 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.159470E+11 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 71468970.37 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.279775E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT TSW
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.127898E+09 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.161054E+09 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.205801E+09 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.675132E+09 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.120173E+10 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.177285E+10 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.194294E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.166801E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.133380E+10 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.702019E+09 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.236172E+09 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.123950E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.101513E+11 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.123950E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.194294E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT TNW
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.117443E+09 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 91527459.11 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 96417188.95 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.530042E+09 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.116355E+10 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.178799E+10 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.193073E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.155411E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.105750E+10 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.373269E+09 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 77877264.68 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.136566E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.891702E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 77877264.68 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.193073E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT TSE
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.109875E+09 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.149778E+09 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.190200E+09 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.670027E+09 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.120301E+10 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.178311E+10 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.194962E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.167600E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.133202E+10 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.675283E+09 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.217332E+09 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.110639E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.100669E+11 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.109875E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.194962E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT TNE
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.115959E+09 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 82742413.69 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 78992996.37 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.524058E+09 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.116525E+10 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.179836E+10 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.193738E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.156328E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.105680E+10 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.343850E+09 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 73310828.59 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.135075E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.887505E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 73310828.59 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.193738E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT TN1
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 79536562.67 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 54994751.29 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 49343399.18 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.400703E+09 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.928059E+09 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.144891E+10 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.159586E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.128579E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.863435E+09 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.280701E+09 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 48064800.81 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 96336031.40 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.713173E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 48064800.81 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.159586E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT TN2
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 79681664.73 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 55079737.02 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 49686913.02 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.402915E+09 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.929696E+09 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.144976E+10 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.159646E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.128659E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.864542E+09 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.281376E+09 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 48376167.06 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 96414272.16 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.714058E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 48376167.06 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.159646E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT TS1
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 93686246.65 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.122902E+09 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.147934E+09 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.546623E+09 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.966582E+09 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.143328E+10 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.160845E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.140136E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.114542E+10 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.623016E+09 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.202445E+09 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 89064933.79 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.838076E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 89064933.79 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.160845E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: SPLIT TS2
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 94443166.69 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.124144E+09 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.149831E+09 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.549026E+09 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.968272E+09 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.143417E+10 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.160908E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.140209E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.114622E+10 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.623250E+09 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.203951E+09 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 89885023.45 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.839436E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 89885023.45 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.160908E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT GSW
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 18880493.31 | 9704109.99 | 0.349459E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 20422366.03 | 39923965.36 | 0.329671E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 16906551.86 | 42682253.24 | 0.257001E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 71501649.19 | 0.851135E+09 | 320471.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.178287E+09 | 0.216054E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.280123E+09 | 0.337877E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.339993E+09 | 0.437449E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.325968E+09 | 0.414375E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.300107E+09 | 0.384871E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.184783E+09 | 0.233330E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 52486312.45 | 0.615735E+09 | 30736829.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 17487060.89 | 3042689.94 | 0.333299E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.180694E+10 | 0.218018E+11 | 0.130049E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 16906551.86 | 3042689.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.339993E+09 | 0.437449E+10 | 0.349459E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT GNW
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 56320141.01 | 0.00 | 0.109124E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 45797519.91 | 0.00 | 0.887361E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 31856336.80 | 0.00 | 0.617240E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 46478408.84 | 0.540276E+09 | 16396858.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.170869E+09 | 0.207126E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.284029E+09 | 0.343273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.338555E+09 | 0.435994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.304746E+09 | 0.386957E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.244017E+09 | 0.311589E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.104550E+09 | 0.131243E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 10312317.55 | 29621724.91 | 0.152514E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 55688190.85 | 0.00 | 0.107900E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.169322E+10 | 0.187317E+11 | 0.384376E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 10312317.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.338555E+09 | 0.435994E+10 | 0.109124E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT OFFICE
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 0.129461E+10 | 0.123335E+09 | 1740244.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.116932E+10 | 0.166851E+09 | 873698.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.129461E+10 | 0.313669E+09 | 1999823.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.125285E+10 | 0.937931E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.129461E+10 | 0.187141E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.125285E+10 | 0.270725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.129461E+10 | 0.301345E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.129461E+10 | 0.327416E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.125285E+10 | 0.276629E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.129461E+10 | 0.196191E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.125285E+10 | 0.833030E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.129461E+10 | 0.121302E+09 | 5766467.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.152430E+11 | 0.180906E+11 | 10380234.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 0.116932E+10 | 0.121302E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.129461E+10 | 0.327416E+10 | 5766467.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT GNE
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 56242181.95 | 0.00 | 0.109495E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 43196398.33 | 0.00 | 0.840969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 30067946.58 | 0.00 | 0.585378E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 46591723.98 | 0.544107E+09 | 13252103.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.172550E+09 | 0.209473E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.287179E+09 | 0.348277E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.340740E+09 | 0.440176E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.306956E+09 | 0.391001E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.244728E+09 | 0.313346E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 99476890.10 | 0.124906E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 9736803.04 | 22244081.77 | 0.153740E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 54994775.78 | 0.00 | 0.107067E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.169246E+10 | 0.188381E+11 | 0.375896E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 9736803.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.340740E+09 | 0.440176E+10 | 0.109495E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT GN1
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 31652676.46 | 0.00 | 0.622359E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 24317628.46 | 0.00 | 0.478136E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 14396710.25 | 0.00 | 0.283070E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 40008537.24 | 0.472477E+09 | 2350280.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.149905E+09 | 0.181798E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.242187E+09 | 0.293106E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.287571E+09 | 0.370986E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.256327E+09 | 0.325848E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.202947E+09 | 0.259377E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 91653744.60 | 0.115065E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 4469409.66 | 25928870.57 | 45903716.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 32381564.48 | 0.00 | 0.636691E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.137782E+10 | 0.159602E+11 | 0.206851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 4469409.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.287571E+09 | 0.370986E+10 | 0.636691E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT GN2
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 31754151.47 | 0.00 | 0.624426E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 24254619.16 | 0.00 | 0.476952E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 14410209.26 | 0.00 | 0.283368E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 40363878.62 | 0.476760E+09 | 2323495.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.150190E+09 | 0.182152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.242394E+09 | 0.293382E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.287692E+09 | 0.371164E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.256464E+09 | 0.326044E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.203014E+09 | 0.259478E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 91436257.87 | 0.114789E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 4448049.29 | 25569636.55 | 46061327.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 32404750.27 | 0.00 | 0.637220E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.137883E+10 | 0.159724E+11 | 0.207035E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 4448049.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.287692E+09 | 0.371164E+10 | 0.637220E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT GS1
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 6135533.13 | 37543219.50 | 58548135.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 7624157.83 | 57590343.57 | 54012996.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 8159907.32 | 62016491.57 | 56924348.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 69660956.33 | 0.830377E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.158807E+09 | 0.192512E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.239283E+09 | 0.288958E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.290250E+09 | 0.374018E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.279125E+09 | 0.355221E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.261378E+09 | 0.335603E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.177413E+09 | 0.224109E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 63937381.99 | 0.774218E+09 | 573120.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 4391985.22 | 11906118.66 | 66315419.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.156617E+10 | 0.194779E+11 | 0.236374E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 4391985.22 | 11906118.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.290250E+09 | 0.374018E+10 | 66315419.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT GS2
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 6280320.94 | 39691928.25 | 57750332.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 7794028.57 | 62912517.27 | 48532819.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 8858879.19 | 74412797.82 | 50064659.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 77818112.67 | 0.929312E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.175986E+09 | 0.213892E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.262388E+09 | 0.318100E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.316677E+09 | 0.409008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.304153E+09 | 0.388124E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.284914E+09 | 0.366690E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.193416E+09 | 0.244667E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 69065944.00 | 0.837227E+09 | 376481.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 4923881.71 | 16948559.52 | 68305087.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.171228E+10 | 0.213653E+11 | 0.225029E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 4923881.71 | 16948559.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.316677E+09 | 0.409008E+10 | 68305087.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT MSW
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 36102422.88 | 0.165829E+09 | 0.424039E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 54589458.01 | 0.518470E+09 | 0.213599E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 80668578.36 | 0.906645E+09 | 90009495.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.312812E+09 | 0.376733E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.523299E+09 | 0.637597E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.708090E+09 | 0.856529E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.768269E+09 | 0.985998E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.684492E+09 | 0.865714E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.589836E+09 | 0.751626E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.362893E+09 | 0.456980E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.115972E+09 | 0.130882E+10 | 0.147573E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 37235548.17 | 39893794.53 | 0.646376E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.427426E+10 | 0.522514E+11 | 0.152160E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 36102422.88 | 39893794.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.768269E+09 | 0.985998E+10 | 0.646376E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT MNW
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 89556952.84 | 0.00 | 0.171206E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 49785453.87 | 18860912.49 | 0.921027E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 26418119.97 | 0.148878E+09 | 0.263723E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.237981E+09 | 0.285046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.506385E+09 | 0.617008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.714645E+09 | 0.865832E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.763003E+09 | 0.979870E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.637415E+09 | 0.805177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.469052E+09 | 0.595247E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.195062E+09 | 0.244049E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 29733495.23 | 49122393.64 | 0.490994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.112652E+09 | 0.00 | 0.215356E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.383169E+10 | 0.441392E+11 | 0.554137E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 26418119.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.763003E+09 | 0.979870E+10 | 0.215356E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT MSE
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 32583704.84 | 0.124328E+09 | 0.425313E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 54544191.83 | 0.530410E+09 | 0.194673E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 80254980.59 | 0.905959E+09 | 81589051.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.320095E+09 | 0.386004E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.528661E+09 | 0.645263E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.714150E+09 | 0.867090E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.773176E+09 | 0.995636E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.689355E+09 | 0.874878E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.591310E+09 | 0.755948E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.352426E+09 | 0.444110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.111901E+09 | 0.125667E+10 | 0.150630E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 36167313.63 | 25011021.75 | 0.653003E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.428463E+10 | 0.525317E+11 | 0.150521E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 32583704.84 | 25011021.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.773176E+09 | 0.995636E+10 | 0.653003E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT MNE
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 88701328.40 | 0.00 | 0.170346E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 45405328.70 | 14634576.07 | 0.847997E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 24185552.37 | 0.126209E+09 | 0.258578E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.243837E+09 | 0.292326E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.511835E+09 | 0.624666E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.720647E+09 | 0.876405E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.767846E+09 | 0.989448E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.642562E+09 | 0.814421E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.471236E+09 | 0.599796E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.183400E+09 | 0.229526E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 29154166.77 | 39366854.97 | 0.497207E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.111219E+09 | 0.00 | 0.213589E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.384003E+10 | 0.444461E+11 | 0.544313E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 24185552.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.767846E+09 | 0.989448E+10 | 0.213589E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT MN1
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 36197904.95 | 0.00 | 0.701950E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 19141664.70 | 10387782.80 | 0.353998E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 15593025.21 | 0.132104E+09 | 84913819.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.197573E+09 | 0.236148E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.411024E+09 | 0.499850E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.572151E+09 | 0.692757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.623425E+09 | 0.801575E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.524051E+09 | 0.662864E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.389662E+09 | 0.495316E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.174650E+09 | 0.218651E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 10765691.66 | 46801837.61 | 0.133784E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 54056744.04 | 0.00 | 0.104827E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.302829E+10 | 0.362609E+11 | 0.232292E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 10765691.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.623425E+09 | 0.801575E+10 | 0.104827E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT MN2
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 36469939.30 | 0.00 | 0.707306E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 19119568.61 | 11275099.49 | 0.352143E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 15873502.54 | 0.135776E+09 | 84326433.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.198526E+09 | 0.237302E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.411441E+09 | 0.500382E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.572489E+09 | 0.693220E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.623671E+09 | 0.801937E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.524324E+09 | 0.663253E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.389839E+09 | 0.495570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.174336E+09 | 0.218245E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 10796744.45 | 46620366.92 | 0.134667E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 54175105.24 | 0.00 | 0.105068E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.303106E+10 | 0.362928E+11 | 0.232913E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 10796744.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.623671E+09 | 0.801937E+10 | 0.105068E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT MS1
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 35294678.23 | 0.390605E+09 | 50507596.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 58673307.78 | 0.698667E+09 | 4493454.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 87771096.65 | 0.104374E+10 | 5804099.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.276947E+09 | 0.333032E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.428292E+09 | 0.520749E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.565527E+09 | 0.683418E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.628815E+09 | 0.807759E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.571656E+09 | 0.723828E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.512057E+09 | 0.653574E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.353313E+09 | 0.445216E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.140586E+09 | 0.169126E+10 | 18397262.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 20078868.29 | 0.187934E+09 | 80400581.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.367901E+10 | 0.456880E+11 | 0.159603E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 20078868.29 | 0.187934E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.628815E+09 | 0.807759E+10 | 80400581.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT MS2
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 35319844.31 | 0.390922E+09 | 50497450.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 59441051.13 | 0.707885E+09 | 4547382.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 88523751.93 | 0.105288E+10 | 5652224.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.277830E+09 | 0.334124E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.428708E+09 | 0.521286E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.565870E+09 | 0.683889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.629064E+09 | 0.808129E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.571915E+09 | 0.724212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.512178E+09 | 0.653784E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.352850E+09 | 0.444651E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.140771E+09 | 0.169334E+10 | 18740552.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 20372397.38 | 0.191090E+09 | 80969002.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.368284E+10 | 0.457369E+11 | 0.160407E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 20372397.38 | 0.191090E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.629064E+09 | 0.808129E+10 | 80969002.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT TSW
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 90399336.24 | 0.141106E+09 | 0.148831E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 80864648.78 | 0.304679E+09 | 0.105047E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 79017950.69 | 0.481318E+09 | 0.736007E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.164696E+09 | 0.190515E+10 | 0.135967E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.278036E+09 | 0.339833E+10 | 1818627.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.404116E+09 | 0.489570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.435062E+09 | 0.558416E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.377044E+09 | 0.477189E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.304726E+09 | 0.388857E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.165447E+09 | 0.206650E+10 | 34812359.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 89956914.44 | 0.558310E+09 | 0.831588E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 99741507.13 | 90709521.82 | 0.174437E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.256911E+10 | 0.280864E+11 | 0.602335E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 79017950.69 | 90709521.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.435062E+09 | 0.558416E+10 | 0.174437E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT TNW
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 0.117443E+09 | 0.00 | 0.222557E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 83456464.47 | 30159295.92 | 0.153302E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 62999144.12 | 0.125231E+09 | 0.993241E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.131308E+09 | 0.147505E+10 | 0.160379E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.269150E+09 | 0.328737E+10 | 1412960.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.407658E+09 | 0.494307E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.432472E+09 | 0.555050E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.351250E+09 | 0.443353E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.241258E+09 | 0.305778E+10 | 371620.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 89374128.11 | 0.107332E+10 | 69320387.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 69938171.67 | 30048566.73 | 0.127832E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.136566E+09 | 0.00 | 0.258796E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.239287E+10 | 0.240061E+11 | 0.884959E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 62999144.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.432472E+09 | 0.555050E+10 | 0.258796E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT TSE
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 84948156.07 | 93692766.54 | 0.146852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 76122519.55 | 0.279669E+09 | 0.100556E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 73754012.77 | 0.441107E+09 | 0.702249E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.162981E+09 | 0.189776E+10 | 0.120991E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.278754E+09 | 0.341554E+10 | 935635.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.406920E+09 | 0.495418E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.437094E+09 | 0.563695E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.379332E+09 | 0.482379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.304602E+09 | 0.390446E+10 | 81769.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.159355E+09 | 0.199026E+10 | 39066764.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 84957266.23 | 0.505082E+09 | 0.823981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 95389120.57 | 57032238.27 | 0.172533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.254421E+10 | 0.279995E+11 | 0.588672E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 73754012.77 | 57032238.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.437094E+09 | 0.563695E+10 | 0.172533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT TNE
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 0.115959E+09 | 0.00 | 0.220992E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 78320197.41 | 16454216.33 | 0.146589E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 56347484.31 | 84579122.44 | 0.937166E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.129283E+09 | 0.146300E+10 | 0.143391E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.269981E+09 | 0.330455E+10 | 859613.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.410497E+09 | 0.500239E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.434500E+09 | 0.560299E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.353795E+09 | 0.448591E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.241340E+09 | 0.307027E+10 | 455780.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 82697951.63 | 0.987686E+09 | 75309125.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 67835940.94 | 20626085.15 | 0.126017E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.135075E+09 | 0.00 | 0.257423E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.237563E+10 | 0.240385E+11 | 0.866739E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 56347484.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.434500E+09 | 0.560299E+10 | 0.257423E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT TN1
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 79536562.67 | 0.00 | 0.152603E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 53149476.61 | 6850271.42 | 0.100853E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 35934109.28 | 49981894.58 | 0.607975E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 97476339.57 | 0.111704E+10 | 76875859.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.214849E+09 | 0.261516E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.330654E+09 | 0.400147E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.357915E+09 | 0.459211E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.290981E+09 | 0.367233E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.197073E+09 | 0.249904E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 65611172.72 | 0.812069E+09 | 15699697.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 44533327.65 | 13281542.00 | 0.833251E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 96336031.40 | 0.00 | 0.184836E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.186405E+10 | 0.193793E+11 | 0.591672E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 35934109.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.357915E+09 | 0.459211E+10 | 0.184836E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT TN2
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 79681664.73 | 0.00 | 0.152920E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 53129127.35 | 7241836.26 | 0.100775E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 36044245.62 | 50854151.87 | 0.608822E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 98009257.97 | 0.112349E+10 | 77077962.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.215240E+09 | 0.262027E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.330850E+09 | 0.400463E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.358056E+09 | 0.459473E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.291167E+09 | 0.367534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.197328E+09 | 0.250266E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 65798212.34 | 0.813965E+09 | 16362699.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 44746003.84 | 13653374.42 | 0.836948E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 96414272.16 | 0.00 | 0.185032E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.186646E+10 | 0.194068E+11 | 0.592649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 36044245.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.358056E+09 | 0.459473E+10 | 0.185032E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT TS1
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 56112535.81 | 0.141384E+09 | 0.848638E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 52448027.29 | 0.267201E+09 | 0.577626E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 50825130.35 | 0.367399E+09 | 0.384680E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.131241E+09 | 0.154644E+10 | 56803369.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.223797E+09 | 0.272633E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.326989E+09 | 0.395265E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.360588E+09 | 0.462626E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.317151E+09 | 0.401374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.261865E+09 | 0.334444E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.145807E+09 | 0.183941E+10 | 4139278.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 66243126.63 | 0.519781E+09 | 0.447425E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 63387681.73 | 96223857.49 | 0.105968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.205645E+10 | 0.234413E+11 | 0.337899E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 50825130.35 | 96223857.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.360588E+09 | 0.462626E+10 | 0.105968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: SPLIT TS2
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 56364882.96 | 0.143303E+09 | 0.850632E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 52724988.47 | 0.270908E+09 | 0.577222E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 51318668.21 | 0.372776E+09 | 0.385709E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.131821E+09 | 0.155369E+10 | 57001666.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.224201E+09 | 0.273171E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.327196E+09 | 0.395597E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.360734E+09 | 0.462898E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.317320E+09 | 0.401671E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.262051E+09 | 0.334760E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.145872E+09 | 0.184040E+10 | 4306674.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 66670546.08 | 0.524000E+09 | 0.449191E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 63648664.82 | 98335325.17 | 0.106155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.205992E+10 | 0.234844E+11 | 0.338561E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 51318668.21 | 98335325.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.360734E+09 | 0.462898E+10 | 0.106155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT GSW
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 18880493.31 | 0.00 | 0.00 | 0.00 | 2596806.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 20422366.03 | 0.00 | 0.00 | 0.00 | 10668232.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 16906551.86 | 0.00 | 0.00 | 0.00 | 11442408.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 71501649.19 | 0.00 | 0.00 | 0.00 | 0.232041E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.178287E+09 | 0.00 | 0.00 | 0.00 | 0.591137E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.280123E+09 | 0.00 | 0.00 | 0.00 | 0.945826E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.339993E+09 | 0.00 | 0.00 | 0.00 | 0.117319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.325968E+09 | 0.00 | 0.00 | 0.00 | 0.110933E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.300107E+09 | 0.00 | 0.00 | 0.00 | 0.100583E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.184783E+09 | 0.00 | 0.00 | 0.00 | 0.603450E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 52486312.45 | 0.00 | 0.00 | 0.00 | 0.161719E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 17487060.89 | 0.00 | 0.00 | 0.00 | 817571.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.180694E+10 | 0.00 | 0.00 | 0.00 | 0.584805E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 16906551.86 | 0.00 | 0.00 | 0.00 | 817571.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.339993E+09 | 0.00 | 0.00 | 0.00 | 0.117319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT GNW
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 56320141.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 45797519.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 31856336.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 46478408.84 | 0.00 | 0.00 | 0.00 | 0.148718E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.170869E+09 | 0.00 | 0.00 | 0.00 | 0.566814E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.284029E+09 | 0.00 | 0.00 | 0.00 | 0.958787E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.338555E+09 | 0.00 | 0.00 | 0.00 | 0.116783E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.304746E+09 | 0.00 | 0.00 | 0.00 | 0.103739E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.244017E+09 | 0.00 | 0.00 | 0.00 | 0.819131E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.104550E+09 | 0.00 | 0.00 | 0.00 | 0.343584E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 10312317.55 | 0.00 | 0.00 | 0.00 | 7826645.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 55688190.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.169322E+10 | 0.00 | 0.00 | 0.00 | 0.505008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 10312317.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.338555E+09 | 0.00 | 0.00 | 0.00 | 0.116783E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT OFFICE
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 0.129461E+10 | 0.00 | 0.00 | 0.00 | 32737870.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.116932E+10 | 0.00 | 0.00 | 0.00 | 44014258.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.129461E+10 | 0.00 | 0.00 | 0.00 | 82917170.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.125285E+10 | 0.00 | 0.00 | 0.00 | 0.247378E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.129461E+10 | 0.00 | 0.00 | 0.00 | 0.492048E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.125285E+10 | 0.00 | 0.00 | 0.00 | 0.735244E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.129461E+10 | 0.00 | 0.00 | 0.00 | 0.784111E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.129461E+10 | 0.00 | 0.00 | 0.00 | 0.843783E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.125285E+10 | 0.00 | 0.00 | 0.00 | 0.702391E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.129461E+10 | 0.00 | 0.00 | 0.00 | 0.491144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.125285E+10 | 0.00 | 0.00 | 0.00 | 0.213399E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.129461E+10 | 0.00 | 0.00 | 0.00 | 32377645.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.152430E+11 | 0.00 | 0.00 | 0.00 | 0.470154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 0.116932E+10 | 0.00 | 0.00 | 0.00 | 32377645.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.129461E+10 | 0.00 | 0.00 | 0.00 | 0.843783E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT GNE
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 56242181.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 43196398.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 30067946.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 46591723.98 | 0.00 | 0.00 | 0.00 | 0.149452E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.172550E+09 | 0.00 | 0.00 | 0.00 | 0.571450E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.287179E+09 | 0.00 | 0.00 | 0.00 | 0.968581E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.340740E+09 | 0.00 | 0.00 | 0.00 | 0.117431E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.306956E+09 | 0.00 | 0.00 | 0.00 | 0.104399E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.244728E+09 | 0.00 | 0.00 | 0.00 | 0.820980E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 99476890.10 | 0.00 | 0.00 | 0.00 | 0.326966E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 9736803.04 | 0.00 | 0.00 | 0.00 | 5896245.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 54994775.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.169246E+10 | 0.00 | 0.00 | 0.00 | 0.506162E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 9736803.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.340740E+09 | 0.00 | 0.00 | 0.00 | 0.117431E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT GN1
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 31652676.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 24317628.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 14396710.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 40008537.24 | 0.00 | 0.00 | 0.00 | 0.129743E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.149905E+09 | 0.00 | 0.00 | 0.00 | 0.496139E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.242187E+09 | 0.00 | 0.00 | 0.00 | 0.816400E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.287571E+09 | 0.00 | 0.00 | 0.00 | 0.990827E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.256327E+09 | 0.00 | 0.00 | 0.00 | 0.871663E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.202947E+09 | 0.00 | 0.00 | 0.00 | 0.680984E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 91653744.60 | 0.00 | 0.00 | 0.00 | 0.301098E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 4469409.66 | 0.00 | 0.00 | 0.00 | 6857702.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 32381564.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.137782E+10 | 0.00 | 0.00 | 0.00 | 0.429371E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 4469409.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.287571E+09 | 0.00 | 0.00 | 0.00 | 0.990827E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT GN2
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 31754151.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 24254619.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 14410209.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 40363878.62 | 0.00 | 0.00 | 0.00 | 0.130890E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.150190E+09 | 0.00 | 0.00 | 0.00 | 0.497060E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.242394E+09 | 0.00 | 0.00 | 0.00 | 0.817100E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.287692E+09 | 0.00 | 0.00 | 0.00 | 0.991245E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.256464E+09 | 0.00 | 0.00 | 0.00 | 0.872127E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.203014E+09 | 0.00 | 0.00 | 0.00 | 0.681215E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 91436257.87 | 0.00 | 0.00 | 0.00 | 0.300386E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 4448049.29 | 0.00 | 0.00 | 0.00 | 6763538.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 32404750.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.137883E+10 | 0.00 | 0.00 | 0.00 | 0.429679E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 4448049.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.287692E+09 | 0.00 | 0.00 | 0.00 | 0.991245E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT GS1
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 6135533.13 | 0.00 | 0.00 | 0.00 | 10005968.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 7624157.83 | 0.00 | 0.00 | 0.00 | 15365031.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 8159907.32 | 0.00 | 0.00 | 0.00 | 16601244.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 69660956.33 | 0.00 | 0.00 | 0.00 | 0.225534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.158807E+09 | 0.00 | 0.00 | 0.00 | 0.525261E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.239283E+09 | 0.00 | 0.00 | 0.00 | 0.806815E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.290250E+09 | 0.00 | 0.00 | 0.00 | 0.100042E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.279125E+09 | 0.00 | 0.00 | 0.00 | 0.948911E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.261378E+09 | 0.00 | 0.00 | 0.00 | 0.875504E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.177413E+09 | 0.00 | 0.00 | 0.00 | 0.578875E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 63937381.99 | 0.00 | 0.00 | 0.00 | 0.203056E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 4391985.22 | 0.00 | 0.00 | 0.00 | 3189176.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.156617E+10 | 0.00 | 0.00 | 0.00 | 0.520954E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 4391985.22 | 0.00 | 0.00 | 0.00 | 3189176.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.290250E+09 | 0.00 | 0.00 | 0.00 | 0.100042E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT GS2
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 6280320.94 | 0.00 | 0.00 | 0.00 | 10583099.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 7794028.57 | 0.00 | 0.00 | 0.00 | 16776389.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 8858879.19 | 0.00 | 0.00 | 0.00 | 19904330.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 77818112.67 | 0.00 | 0.00 | 0.00 | 0.251726E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.175986E+09 | 0.00 | 0.00 | 0.00 | 0.581410E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.262388E+09 | 0.00 | 0.00 | 0.00 | 0.883817E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.316677E+09 | 0.00 | 0.00 | 0.00 | 0.108984E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.304153E+09 | 0.00 | 0.00 | 0.00 | 0.103272E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.284914E+09 | 0.00 | 0.00 | 0.00 | 0.953218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.193416E+09 | 0.00 | 0.00 | 0.00 | 0.630808E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 69065944.00 | 0.00 | 0.00 | 0.00 | 0.219402E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 4923881.71 | 0.00 | 0.00 | 0.00 | 4539114.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.171228E+10 | 0.00 | 0.00 | 0.00 | 0.569475E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 4923881.71 | 0.00 | 0.00 | 0.00 | 4539114.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.316677E+09 | 0.00 | 0.00 | 0.00 | 0.108984E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT MSW
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 36102422.88 | 0.00 | 0.00 | 0.00 | 44115161.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 54589458.01 | 0.00 | 0.00 | 0.00 | 0.136956E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 80668578.36 | 0.00 | 0.00 | 0.00 | 0.239734E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.312812E+09 | 0.00 | 0.00 | 0.00 | 0.100955E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.523299E+09 | 0.00 | 0.00 | 0.00 | 0.172924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.708090E+09 | 0.00 | 0.00 | 0.00 | 0.238803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.768269E+09 | 0.00 | 0.00 | 0.00 | 0.265172E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.684492E+09 | 0.00 | 0.00 | 0.00 | 0.233241E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.589836E+09 | 0.00 | 0.00 | 0.00 | 0.198104E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.362893E+09 | 0.00 | 0.00 | 0.00 | 0.118596E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.115972E+09 | 0.00 | 0.00 | 0.00 | 0.343728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 37235548.17 | 0.00 | 0.00 | 0.00 | 10689388.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.427426E+10 | 0.00 | 0.00 | 0.00 | 0.140532E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 36102422.88 | 0.00 | 0.00 | 0.00 | 10689388.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.768269E+09 | 0.00 | 0.00 | 0.00 | 0.265172E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT MNW
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 89556952.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 49785453.87 | 0.00 | 0.00 | 0.00 | 5068227.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 26418119.97 | 0.00 | 0.00 | 0.00 | 39850341.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.237981E+09 | 0.00 | 0.00 | 0.00 | 0.769383E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.506385E+09 | 0.00 | 0.00 | 0.00 | 0.167370E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.714645E+09 | 0.00 | 0.00 | 0.00 | 0.240962E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.763003E+09 | 0.00 | 0.00 | 0.00 | 0.263264E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.637415E+09 | 0.00 | 0.00 | 0.00 | 0.217239E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.469052E+09 | 0.00 | 0.00 | 0.00 | 0.157792E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.195062E+09 | 0.00 | 0.00 | 0.00 | 0.642134E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 29733495.23 | 0.00 | 0.00 | 0.00 | 12982097.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.112652E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.383169E+10 | 0.00 | 0.00 | 0.00 | 0.119357E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 26418119.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.763003E+09 | 0.00 | 0.00 | 0.00 | 0.263264E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT MSE
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 32583704.84 | 0.00 | 0.00 | 0.00 | 33070471.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 54544191.83 | 0.00 | 0.00 | 0.00 | 0.140117E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 80254980.59 | 0.00 | 0.00 | 0.00 | 0.239878E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.320095E+09 | 0.00 | 0.00 | 0.00 | 0.103192E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.528661E+09 | 0.00 | 0.00 | 0.00 | 0.174390E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.714150E+09 | 0.00 | 0.00 | 0.00 | 0.240600E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.773176E+09 | 0.00 | 0.00 | 0.00 | 0.266560E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.689355E+09 | 0.00 | 0.00 | 0.00 | 0.234626E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.591310E+09 | 0.00 | 0.00 | 0.00 | 0.198429E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.352426E+09 | 0.00 | 0.00 | 0.00 | 0.115160E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.111901E+09 | 0.00 | 0.00 | 0.00 | 0.330318E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 36167313.63 | 0.00 | 0.00 | 0.00 | 6706472.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.428463E+10 | 0.00 | 0.00 | 0.00 | 0.140797E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 32583704.84 | 0.00 | 0.00 | 0.00 | 6706472.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.773176E+09 | 0.00 | 0.00 | 0.00 | 0.266560E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT MNE
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 88701328.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 45405328.70 | 0.00 | 0.00 | 0.00 | 3939003.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 24185552.37 | 0.00 | 0.00 | 0.00 | 33846793.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.243837E+09 | 0.00 | 0.00 | 0.00 | 0.787317E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.511835E+09 | 0.00 | 0.00 | 0.00 | 0.168862E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.720647E+09 | 0.00 | 0.00 | 0.00 | 0.242735E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.767846E+09 | 0.00 | 0.00 | 0.00 | 0.264629E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.642562E+09 | 0.00 | 0.00 | 0.00 | 0.218725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.471236E+09 | 0.00 | 0.00 | 0.00 | 0.158368E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.183400E+09 | 0.00 | 0.00 | 0.00 | 0.603926E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 29154166.77 | 0.00 | 0.00 | 0.00 | 10451887.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.111219E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.384003E+10 | 0.00 | 0.00 | 0.00 | 0.119727E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 24185552.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.767846E+09 | 0.00 | 0.00 | 0.00 | 0.264629E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT MN1
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 36197904.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 19141664.70 | 0.00 | 0.00 | 0.00 | 2796922.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 15593025.21 | 0.00 | 0.00 | 0.00 | 35411679.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.197573E+09 | 0.00 | 0.00 | 0.00 | 0.637656E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.411024E+09 | 0.00 | 0.00 | 0.00 | 0.135597E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.572151E+09 | 0.00 | 0.00 | 0.00 | 0.192690E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.623425E+09 | 0.00 | 0.00 | 0.00 | 0.214830E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.524051E+09 | 0.00 | 0.00 | 0.00 | 0.178332E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.389662E+09 | 0.00 | 0.00 | 0.00 | 0.130930E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.174650E+09 | 0.00 | 0.00 | 0.00 | 0.574352E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 10765691.66 | 0.00 | 0.00 | 0.00 | 12402560.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 54056744.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.302829E+10 | 0.00 | 0.00 | 0.00 | 0.978640E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 10765691.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.623425E+09 | 0.00 | 0.00 | 0.00 | 0.214830E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT MN2
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 36469939.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 19119568.61 | 0.00 | 0.00 | 0.00 | 3035342.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 15873502.54 | 0.00 | 0.00 | 0.00 | 36394945.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.198526E+09 | 0.00 | 0.00 | 0.00 | 0.640701E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.411441E+09 | 0.00 | 0.00 | 0.00 | 0.135731E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.572489E+09 | 0.00 | 0.00 | 0.00 | 0.192804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.623671E+09 | 0.00 | 0.00 | 0.00 | 0.214915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.524324E+09 | 0.00 | 0.00 | 0.00 | 0.178424E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.389839E+09 | 0.00 | 0.00 | 0.00 | 0.130991E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.174336E+09 | 0.00 | 0.00 | 0.00 | 0.573314E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 10796744.45 | 0.00 | 0.00 | 0.00 | 12356333.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 54175105.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.303106E+10 | 0.00 | 0.00 | 0.00 | 0.979446E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 10796744.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.623671E+09 | 0.00 | 0.00 | 0.00 | 0.214915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT MS1
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 35294678.23 | 0.00 | 0.00 | 0.00 | 0.103668E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 58673307.78 | 0.00 | 0.00 | 0.00 | 0.184484E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 87771096.65 | 0.00 | 0.00 | 0.00 | 0.276155E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.276947E+09 | 0.00 | 0.00 | 0.00 | 0.892193E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.428292E+09 | 0.00 | 0.00 | 0.00 | 0.141264E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.565527E+09 | 0.00 | 0.00 | 0.00 | 0.190512E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.628815E+09 | 0.00 | 0.00 | 0.00 | 0.216783E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.571656E+09 | 0.00 | 0.00 | 0.00 | 0.194516E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.512057E+09 | 0.00 | 0.00 | 0.00 | 0.171784E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.353313E+09 | 0.00 | 0.00 | 0.00 | 0.115322E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.140586E+09 | 0.00 | 0.00 | 0.00 | 0.443382E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 20078868.29 | 0.00 | 0.00 | 0.00 | 50260053.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.367901E+10 | 0.00 | 0.00 | 0.00 | 0.122520E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 20078868.29 | 0.00 | 0.00 | 0.00 | 50260053.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.628815E+09 | 0.00 | 0.00 | 0.00 | 0.216783E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT MS2
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 35319844.31 | 0.00 | 0.00 | 0.00 | 0.103749E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 59441051.13 | 0.00 | 0.00 | 0.00 | 0.186902E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 88523751.93 | 0.00 | 0.00 | 0.00 | 0.278555E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.277830E+09 | 0.00 | 0.00 | 0.00 | 0.895007E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.428708E+09 | 0.00 | 0.00 | 0.00 | 0.141398E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.565870E+09 | 0.00 | 0.00 | 0.00 | 0.190628E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.629064E+09 | 0.00 | 0.00 | 0.00 | 0.216869E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.571915E+09 | 0.00 | 0.00 | 0.00 | 0.194604E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.512178E+09 | 0.00 | 0.00 | 0.00 | 0.171826E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.352850E+09 | 0.00 | 0.00 | 0.00 | 0.115171E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.140771E+09 | 0.00 | 0.00 | 0.00 | 0.443901E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 20372397.38 | 0.00 | 0.00 | 0.00 | 51096572.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.368284E+10 | 0.00 | 0.00 | 0.00 | 0.122642E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 20372397.38 | 0.00 | 0.00 | 0.00 | 51096572.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.629064E+09 | 0.00 | 0.00 | 0.00 | 0.216869E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT TSW
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 90399336.24 | 0.00 | 0.00 | 0.00 | 37498841.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 80864648.78 | 0.00 | 0.00 | 0.00 | 80189713.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 79017950.69 | 0.00 | 0.00 | 0.00 | 0.126783E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.164696E+09 | 0.00 | 0.00 | 0.00 | 0.510436E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.278036E+09 | 0.00 | 0.00 | 0.00 | 0.923693E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.404116E+09 | 0.00 | 0.00 | 0.00 | 0.136873E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.435062E+09 | 0.00 | 0.00 | 0.00 | 0.150788E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.377044E+09 | 0.00 | 0.00 | 0.00 | 0.129096E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.304726E+09 | 0.00 | 0.00 | 0.00 | 0.102907E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.165447E+09 | 0.00 | 0.00 | 0.00 | 0.536572E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 89956914.44 | 0.00 | 0.00 | 0.00 | 0.146215E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 99741507.13 | 0.00 | 0.00 | 0.00 | 24208240.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.256911E+10 | 0.00 | 0.00 | 0.00 | 0.758224E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 79017950.69 | 0.00 | 0.00 | 0.00 | 24208240.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.435062E+09 | 0.00 | 0.00 | 0.00 | 0.150788E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT TNW
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 0.117443E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 83456464.47 | 0.00 | 0.00 | 0.00 | 8070994.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 62999144.12 | 0.00 | 0.00 | 0.00 | 33418044.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.131308E+09 | 0.00 | 0.00 | 0.00 | 0.398733E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.269150E+09 | 0.00 | 0.00 | 0.00 | 0.894400E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.407658E+09 | 0.00 | 0.00 | 0.00 | 0.138033E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.432472E+09 | 0.00 | 0.00 | 0.00 | 0.149826E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.351250E+09 | 0.00 | 0.00 | 0.00 | 0.120286E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.241258E+09 | 0.00 | 0.00 | 0.00 | 0.816240E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 89374128.11 | 0.00 | 0.00 | 0.00 | 0.283895E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 69938171.67 | 0.00 | 0.00 | 0.00 | 7939093.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.136566E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.239287E+10 | 0.00 | 0.00 | 0.00 | 0.652414E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 62999144.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.432472E+09 | 0.00 | 0.00 | 0.00 | 0.149826E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT TSE
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 84948156.07 | 0.00 | 0.00 | 0.00 | 24926411.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 76122519.55 | 0.00 | 0.00 | 0.00 | 73655364.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 73754012.77 | 0.00 | 0.00 | 0.00 | 0.116446E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.162981E+09 | 0.00 | 0.00 | 0.00 | 0.507046E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.278754E+09 | 0.00 | 0.00 | 0.00 | 0.924253E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.406920E+09 | 0.00 | 0.00 | 0.00 | 0.137619E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.437094E+09 | 0.00 | 0.00 | 0.00 | 0.151252E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.379332E+09 | 0.00 | 0.00 | 0.00 | 0.129667E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.304602E+09 | 0.00 | 0.00 | 0.00 | 0.102742E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.159355E+09 | 0.00 | 0.00 | 0.00 | 0.515928E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 84957266.23 | 0.00 | 0.00 | 0.00 | 0.132374E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 95389120.57 | 0.00 | 0.00 | 0.00 | 15249729.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.254421E+10 | 0.00 | 0.00 | 0.00 | 0.752268E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 73754012.77 | 0.00 | 0.00 | 0.00 | 15249729.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.437094E+09 | 0.00 | 0.00 | 0.00 | 0.151252E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT TNE
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 0.115959E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 78320197.41 | 0.00 | 0.00 | 0.00 | 4422216.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 56347484.31 | 0.00 | 0.00 | 0.00 | 22645512.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.129283E+09 | 0.00 | 0.00 | 0.00 | 0.394775E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.269981E+09 | 0.00 | 0.00 | 0.00 | 0.895267E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.410497E+09 | 0.00 | 0.00 | 0.00 | 0.138786E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.434500E+09 | 0.00 | 0.00 | 0.00 | 0.150288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.353795E+09 | 0.00 | 0.00 | 0.00 | 0.120948E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.241340E+09 | 0.00 | 0.00 | 0.00 | 0.815458E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 82697951.63 | 0.00 | 0.00 | 0.00 | 0.261152E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 67835940.94 | 0.00 | 0.00 | 0.00 | 5474887.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.135075E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.237563E+10 | 0.00 | 0.00 | 0.00 | 0.649942E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 56347484.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.434500E+09 | 0.00 | 0.00 | 0.00 | 0.150288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT TN1
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 79536562.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 53149476.61 | 0.00 | 0.00 | 0.00 | 1845274.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 35934109.28 | 0.00 | 0.00 | 0.00 | 13409289.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 97476339.57 | 0.00 | 0.00 | 0.00 | 0.303226E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.214849E+09 | 0.00 | 0.00 | 0.00 | 0.713211E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.330654E+09 | 0.00 | 0.00 | 0.00 | 0.111826E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.357915E+09 | 0.00 | 0.00 | 0.00 | 0.123794E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.290981E+09 | 0.00 | 0.00 | 0.00 | 0.994807E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.197073E+09 | 0.00 | 0.00 | 0.00 | 0.666361E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 65611172.72 | 0.00 | 0.00 | 0.00 | 0.215089E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 44533327.65 | 0.00 | 0.00 | 0.00 | 3531473.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 96336031.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.186405E+10 | 0.00 | 0.00 | 0.00 | 0.526768E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 35934109.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.357915E+09 | 0.00 | 0.00 | 0.00 | 0.123794E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT TN2
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 79681664.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 53129127.35 | 0.00 | 0.00 | 0.00 | 1950609.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 36044245.62 | 0.00 | 0.00 | 0.00 | 13642667.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 98009257.97 | 0.00 | 0.00 | 0.00 | 0.304906E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.215240E+09 | 0.00 | 0.00 | 0.00 | 0.714456E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.330850E+09 | 0.00 | 0.00 | 0.00 | 0.111891E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.358056E+09 | 0.00 | 0.00 | 0.00 | 0.123841E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.291167E+09 | 0.00 | 0.00 | 0.00 | 0.995421E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.197328E+09 | 0.00 | 0.00 | 0.00 | 0.667214E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 65798212.34 | 0.00 | 0.00 | 0.00 | 0.215578E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 44746003.84 | 0.00 | 0.00 | 0.00 | 3630163.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 96414272.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.186646E+10 | 0.00 | 0.00 | 0.00 | 0.527411E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 36044245.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.358056E+09 | 0.00 | 0.00 | 0.00 | 0.123841E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT TS1
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 56112535.81 | 0.00 | 0.00 | 0.00 | 37573710.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 52448027.29 | 0.00 | 0.00 | 0.00 | 70453791.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 50825130.35 | 0.00 | 0.00 | 0.00 | 97108541.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.131241E+09 | 0.00 | 0.00 | 0.00 | 0.415382E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.223797E+09 | 0.00 | 0.00 | 0.00 | 0.742785E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.326989E+09 | 0.00 | 0.00 | 0.00 | 0.110629E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.360588E+09 | 0.00 | 0.00 | 0.00 | 0.124787E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.317151E+09 | 0.00 | 0.00 | 0.00 | 0.108421E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.261865E+09 | 0.00 | 0.00 | 0.00 | 0.883552E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.145807E+09 | 0.00 | 0.00 | 0.00 | 0.477209E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 66243126.63 | 0.00 | 0.00 | 0.00 | 0.136202E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 63387681.73 | 0.00 | 0.00 | 0.00 | 25677252.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.205645E+10 | 0.00 | 0.00 | 0.00 | 0.632431E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 50825130.35 | 0.00 | 0.00 | 0.00 | 25677252.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.360588E+09 | 0.00 | 0.00 | 0.00 | 0.124787E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: SPLIT TS2
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 56364882.96 | 0.00 | 0.00 | 0.00 | 38078283.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 52724988.47 | 0.00 | 0.00 | 0.00 | 71418581.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 51318668.21 | 0.00 | 0.00 | 0.00 | 98512605.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.131821E+09 | 0.00 | 0.00 | 0.00 | 0.417205E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.224201E+09 | 0.00 | 0.00 | 0.00 | 0.744071E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.327196E+09 | 0.00 | 0.00 | 0.00 | 0.110697E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.360734E+09 | 0.00 | 0.00 | 0.00 | 0.124835E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.317320E+09 | 0.00 | 0.00 | 0.00 | 0.108477E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.262051E+09 | 0.00 | 0.00 | 0.00 | 0.884166E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.145872E+09 | 0.00 | 0.00 | 0.00 | 0.477379E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 66670546.08 | 0.00 | 0.00 | 0.00 | 0.137280E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 63648664.82 | 0.00 | 0.00 | 0.00 | 26236358.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.205992E+10 | 0.00 | 0.00 | 0.00 | 0.633443E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 51318668.21 | 0.00 | 0.00 | 0.00 | 26236358.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.360734E+09 | 0.00 | 0.00 | 0.00 | 0.124835E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: G SW APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.841844E+09 | 0.00 | 0.00 | 52501.53 | 0.00 | 0.152087E+09 | 23320863.71 | 0.00 | 0.35 |
| February | 0.583474E+09 | 0.00 | 0.00 | 79929.04 | 0.00 | 0.180126E+09 | 10721110.23 | 0.00 | 0.35 |
| March | 0.567778E+09 | 1151564.22 | 0.00 | 55751.75 | 285161.16 | 0.120105E+09 | 9123568.26 | 0.00 | 0.35 |
| April | 0.302106E+09 | 52987213.42 | 0.00 | 430705.42 | 1085614.22 | 0.00 | 73252943.18 | 0.00 | 0.35 |
| May | 63392471.22 | 0.177617E+09 | 0.00 | 831071.08 | 0.00 | 0.00 | 0.112824E+09 | 0.00 | 0.35 |
| June | 19500.64 | 0.363104E+09 | 0.00 | 610864.40 | 0.00 | 0.00 | 43510454.23 | 0.00 | 0.35 |
| July | 0.00 | 0.669481E+09 | 0.00 | 30748.93 | 0.00 | 0.00 | 1271802.72 | 0.00 | 0.36 |
| August | 0.00 | 0.431657E+09 | 0.00 | 599860.95 | 0.00 | 0.00 | 26776271.11 | 0.00 | 0.35 |
| September | 0.00 | 0.296292E+09 | 0.00 | 1452596.96 | 0.00 | 0.00 | 0.112465E+09 | 0.00 | 0.36 |
| October | 23695334.66 | 71566546.07 | 0.00 | 3089466.45 | 0.00 | 0.00 | 0.410948E+09 | 0.00 | 0.35 |
| November | 0.560435E+09 | 420755.59 | 0.00 | 1668061.31 | 0.00 | 8417085.04 | 0.312770E+09 | 0.00 | 0.35 |
| December | 0.961619E+09 | 0.00 | 0.00 | 15183.83 | 0.00 | 0.150854E+09 | 7348352.82 | 0.00 | 0.35 |
| Annual Sum or Average | 0.390436E+10 | 0.206428E+10 | 0.00 | 8916741.66 | 1370775.38 | 0.611589E+09 | 0.114433E+10 | 0.00 | 0.35 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 15183.83 | 0.00 | 0.00 | 1271802.72 | 0.00 | 0.35 |
| Maximum of Months | 0.961619E+09 | 0.669481E+09 | 0.00 | 3089466.45 | 1085614.22 | 0.180126E+09 | 0.410948E+09 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: G NW APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.267452E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.690609E+09 | 0.00 | 0.00 | 0.35 |
| February | 0.202542E+09 | 0.00 | 0.00 | 0.00 | 210555.76 | 0.523329E+09 | 0.00 | 0.00 | 0.35 |
| March | 0.262098E+09 | 0.00 | 0.00 | 0.00 | 3597301.64 | 0.392670E+09 | 0.00 | 0.00 | 0.35 |
| April | 0.316492E+09 | 47713705.71 | 0.00 | 207270.03 | 6744397.89 | 2290459.76 | 38362573.45 | 0.00 | 0.35 |
| May | 68333968.35 | 0.176347E+09 | 0.00 | 789646.21 | 0.00 | 0.00 | 0.106574E+09 | 0.00 | 0.35 |
| June | 0.00 | 0.361074E+09 | 0.00 | 640951.92 | 0.00 | 0.00 | 42816141.31 | 0.00 | 0.35 |
| July | 0.00 | 0.670318E+09 | 0.00 | 31532.61 | 0.00 | 0.00 | 1275551.07 | 0.00 | 0.36 |
| August | 0.00 | 0.424198E+09 | 0.00 | 576979.80 | 0.00 | 0.00 | 28295331.55 | 0.00 | 0.35 |
| September | 1093811.04 | 0.277793E+09 | 0.00 | 1176526.67 | 0.00 | 0.00 | 0.116149E+09 | 0.00 | 0.36 |
| October | 0.156089E+09 | 63772468.48 | 0.00 | 1520712.35 | 0.00 | 0.00 | 0.287386E+09 | 0.00 | 0.35 |
| November | 0.706998E+09 | 248864.35 | 0.00 | 92233.27 | 0.00 | 67146425.65 | 28460783.60 | 0.00 | 0.35 |
| December | 0.361164E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.698574E+09 | 0.00 | 0.00 | 0.35 |
| Annual Sum or Average | 0.234226E+10 | 0.202147E+10 | 0.00 | 5035852.86 | 10552255.28 | 0.237462E+10 | 0.649320E+09 | 0.00 | 0.35 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
| Maximum of Months | 0.706998E+09 | 0.670318E+09 | 0.00 | 1520712.35 | 6744397.89 | 0.698574E+09 | 0.287386E+09 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: OFFICE
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.142974E+10 | 0.00 | 0.00 | 166077.90 | 0.00 | 801256.82 | 0.120627E+09 | 0.00 | 0.51 |
| February | 0.113878E+10 | 0.00 | 0.00 | 201845.00 | 0.00 | 150277.03 | 91921192.91 | 0.00 | 0.52 |
| March | 0.103852E+10 | 0.00 | 0.00 | 328592.04 | 0.00 | 330246.39 | 0.118564E+09 | 0.00 | 0.52 |
| April | 0.588267E+09 | 19580778.82 | 0.00 | 794138.86 | 8100379.00 | 0.00 | 98150785.81 | 0.00 | 0.52 |
| May | 0.387408E+09 | 91638382.65 | 0.00 | 858026.70 | 32596226.14 | 0.00 | 34793457.95 | 0.00 | 0.53 |
| June | 0.198725E+09 | 0.200356E+09 | 0.00 | 652837.41 | 75611457.19 | 0.00 | 10087138.05 | 0.00 | 0.53 |
| July | 0.177738E+09 | 0.321419E+09 | 0.00 | 381288.06 | 91587155.86 | 0.00 | 7382150.52 | 0.00 | 0.53 |
| August | 0.217782E+09 | 0.257250E+09 | 0.00 | 791034.93 | 40722534.31 | 0.00 | 17947135.38 | 0.00 | 0.53 |
| September | 0.427653E+09 | 0.157840E+09 | 0.00 | 1231665.60 | 11624360.03 | 0.00 | 42811970.51 | 0.00 | 0.53 |
| October | 0.750783E+09 | 53671149.45 | 0.00 | 2170425.64 | 3531858.04 | 0.00 | 0.134162E+09 | 0.00 | 0.52 |
| November | 0.123582E+10 | 43346.05 | 0.00 | 1293835.42 | 0.00 | 0.00 | 0.166213E+09 | 0.00 | 0.52 |
| December | 0.154349E+10 | 0.00 | 0.00 | 185445.09 | 0.00 | 2659067.03 | 0.168567E+09 | 0.00 | 0.51 |
| Annual Sum or Average | 0.913471E+10 | 0.110180E+10 | 0.00 | 9055212.67 | 0.263774E+09 | 3940847.27 | 0.101123E+10 | 0.00 | 0.52 |
| Minimum of Months | 0.177738E+09 | 0.00 | 0.00 | 166077.90 | 0.00 | 0.00 | 7382150.52 | 0.00 | 0.51 |
| Maximum of Months | 0.154349E+10 | 0.321419E+09 | 0.00 | 2170425.64 | 91587155.86 | 2659067.03 | 0.168567E+09 | 0.00 | 0.53 |
Report: MechanicalVentilationLoadsMonthly
For: G NE APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.276713E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.679512E+09 | 0.00 | 0.00 | 0.35 |
| February | 0.235211E+09 | 0.00 | 0.00 | 0.00 | 261585.35 | 0.490230E+09 | 0.00 | 0.00 | 0.35 |
| March | 0.295161E+09 | 0.00 | 0.00 | 0.00 | 3631389.99 | 0.358541E+09 | 0.00 | 0.00 | 0.35 |
| April | 0.318011E+09 | 48715102.03 | 0.00 | 239104.53 | 5390229.67 | 2007915.08 | 41710611.40 | 0.00 | 0.35 |
| May | 59824678.00 | 0.177847E+09 | 0.00 | 890318.07 | 0.00 | 0.00 | 0.116244E+09 | 0.00 | 0.35 |
| June | 0.00 | 0.363452E+09 | 0.00 | 671530.55 | 0.00 | 0.00 | 43323316.51 | 0.00 | 0.35 |
| July | 0.00 | 0.674848E+09 | 0.00 | 33730.46 | 0.00 | 0.00 | 1198313.10 | 0.00 | 0.36 |
| August | 0.00 | 0.429084E+09 | 0.00 | 597474.08 | 0.00 | 0.00 | 28772295.10 | 0.00 | 0.35 |
| September | 1055194.60 | 0.282447E+09 | 0.00 | 1224002.81 | 0.00 | 0.00 | 0.115831E+09 | 0.00 | 0.36 |
| October | 0.163633E+09 | 63749991.58 | 0.00 | 1445104.01 | 0.00 | 0.00 | 0.282862E+09 | 0.00 | 0.35 |
| November | 0.719736E+09 | 248850.39 | 0.00 | 47795.76 | 0.00 | 66073749.28 | 14846756.04 | 0.00 | 0.35 |
| December | 0.384037E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.674598E+09 | 0.00 | 0.00 | 0.35 |
| Annual Sum or Average | 0.245338E+10 | 0.204039E+10 | 0.00 | 5149060.26 | 9283205.01 | 0.227096E+10 | 0.644788E+09 | 0.00 | 0.35 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
| Maximum of Months | 0.719736E+09 | 0.674848E+09 | 0.00 | 1445104.01 | 5390229.67 | 0.679512E+09 | 0.282862E+09 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: G N1 APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.654951E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.311924E+09 | 0.00 | 0.00 | 0.35 |
| February | 0.482378E+09 | 0.00 | 0.00 | 0.00 | 267723.69 | 0.253460E+09 | 0.00 | 0.00 | 0.35 |
| March | 0.556992E+09 | 0.00 | 0.00 | 0.00 | 3499046.37 | 0.112110E+09 | 0.00 | 0.00 | 0.35 |
| April | 0.316059E+09 | 45999413.08 | 0.00 | 272396.95 | 6845472.10 | 0.00 | 65717995.42 | 0.00 | 0.35 |
| May | 39303745.35 | 0.174092E+09 | 0.00 | 949486.86 | 0.00 | 0.00 | 0.144130E+09 | 0.00 | 0.35 |
| June | 0.00 | 0.355733E+09 | 0.00 | 658555.23 | 0.00 | 0.00 | 43025328.75 | 0.00 | 0.35 |
| July | 0.00 | 0.663431E+09 | 0.00 | 33516.50 | 0.00 | 0.00 | 1108407.62 | 0.00 | 0.36 |
| August | 0.00 | 0.415268E+09 | 0.00 | 573123.04 | 0.00 | 0.00 | 27440381.58 | 0.00 | 0.36 |
| September | 0.00 | 0.267255E+09 | 0.00 | 1141891.74 | 0.00 | 0.00 | 0.119512E+09 | 0.00 | 0.36 |
| October | 59684534.61 | 61702299.51 | 0.00 | 1690898.99 | 0.00 | 0.00 | 0.391138E+09 | 0.00 | 0.35 |
| November | 0.769324E+09 | 277127.98 | 0.00 | 110808.39 | 0.00 | 10107083.30 | 50715584.65 | 0.00 | 0.35 |
| December | 0.761274E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.308346E+09 | 0.00 | 0.00 | 0.35 |
| Annual Sum or Average | 0.363997E+10 | 0.198376E+10 | 0.00 | 5430677.70 | 10612242.16 | 0.995947E+09 | 0.842788E+09 | 0.00 | 0.35 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
| Maximum of Months | 0.769324E+09 | 0.663431E+09 | 0.00 | 1690898.99 | 6845472.10 | 0.311924E+09 | 0.391138E+09 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: G N2 APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.653054E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.313710E+09 | 0.00 | 0.00 | 0.35 |
| February | 0.485936E+09 | 0.00 | 0.00 | 0.00 | 262670.21 | 0.249973E+09 | 0.00 | 0.00 | 0.35 |
| March | 0.556838E+09 | 0.00 | 0.00 | 0.00 | 3484183.32 | 0.112372E+09 | 0.00 | 0.00 | 0.35 |
| April | 0.315916E+09 | 46100748.05 | 0.00 | 276117.23 | 6708072.85 | 0.00 | 66238229.44 | 0.00 | 0.35 |
| May | 39385573.56 | 0.174136E+09 | 0.00 | 953343.63 | 0.00 | 0.00 | 0.144110E+09 | 0.00 | 0.35 |
| June | 0.00 | 0.355795E+09 | 0.00 | 658237.53 | 0.00 | 0.00 | 43058301.84 | 0.00 | 0.35 |
| July | 0.00 | 0.663495E+09 | 0.00 | 33635.24 | 0.00 | 0.00 | 1103327.63 | 0.00 | 0.36 |
| August | 0.00 | 0.415394E+09 | 0.00 | 573155.15 | 0.00 | 0.00 | 27473802.09 | 0.00 | 0.36 |
| September | 0.00 | 0.267355E+09 | 0.00 | 1141870.47 | 0.00 | 0.00 | 0.119519E+09 | 0.00 | 0.36 |
| October | 60497457.87 | 61687178.35 | 0.00 | 1684314.61 | 0.00 | 0.00 | 0.390546E+09 | 0.00 | 0.35 |
| November | 0.770214E+09 | 277241.66 | 0.00 | 108863.98 | 0.00 | 10107099.27 | 49606001.27 | 0.00 | 0.35 |
| December | 0.761058E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.308588E+09 | 0.00 | 0.00 | 0.35 |
| Annual Sum or Average | 0.364290E+10 | 0.198424E+10 | 0.00 | 5429537.83 | 10454926.38 | 0.994751E+09 | 0.841654E+09 | 0.00 | 0.35 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
| Maximum of Months | 0.770214E+09 | 0.663495E+09 | 0.00 | 1684314.61 | 6708072.85 | 0.313710E+09 | 0.390546E+09 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: G S1 APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.985917E+09 | 0.00 | 0.00 | 185240.74 | 0.00 | 13500652.20 | 69394392.61 | 0.00 | 0.35 |
| February | 0.790219E+09 | 0.00 | 0.00 | 127080.83 | 0.00 | 0.00 | 27722119.75 | 0.00 | 0.35 |
| March | 0.714824E+09 | 1114048.14 | 0.00 | 101811.99 | 170011.54 | 5473841.35 | 21268016.07 | 0.00 | 0.35 |
| April | 0.257562E+09 | 52475096.16 | 0.00 | 620053.52 | 144275.04 | 0.00 | 0.144082E+09 | 0.00 | 0.35 |
| May | 30642523.27 | 0.175859E+09 | 0.00 | 1013945.64 | 0.00 | 0.00 | 0.153723E+09 | 0.00 | 0.35 |
| June | 0.00 | 0.358286E+09 | 0.00 | 633859.63 | 0.00 | 0.00 | 43686835.53 | 0.00 | 0.35 |
| July | 0.00 | 0.663919E+09 | 0.00 | 32694.79 | 0.00 | 0.00 | 1085242.10 | 0.00 | 0.36 |
| August | 0.00 | 0.424852E+09 | 0.00 | 598253.20 | 0.00 | 0.00 | 25553961.51 | 0.00 | 0.35 |
| September | 0.00 | 0.289895E+09 | 0.00 | 1424910.26 | 0.00 | 0.00 | 0.113584E+09 | 0.00 | 0.36 |
| October | 2124088.71 | 70961719.76 | 0.00 | 3342122.06 | 0.00 | 0.00 | 0.433749E+09 | 0.00 | 0.35 |
| November | 0.423811E+09 | 473135.44 | 0.00 | 2263511.15 | 0.00 | 0.00 | 0.490090E+09 | 0.00 | 0.35 |
| December | 0.110422E+10 | 0.00 | 0.00 | 100705.42 | 0.00 | 411020.32 | 67975036.14 | 0.00 | 0.35 |
| Annual Sum or Average | 0.430932E+10 | 0.203783E+10 | 0.00 | 10444189.23 | 314286.59 | 19385513.87 | 0.159191E+10 | 0.00 | 0.35 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 32694.79 | 0.00 | 0.00 | 1085242.10 | 0.00 | 0.35 |
| Maximum of Months | 0.110422E+10 | 0.663919E+09 | 0.00 | 3342122.06 | 170011.54 | 13500652.20 | 0.490090E+09 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: G S2 APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.984869E+09 | 0.00 | 0.00 | 194646.46 | 0.00 | 12961425.05 | 72753381.02 | 0.00 | 0.35 |
| February | 0.787655E+09 | 0.00 | 0.00 | 142072.08 | 0.00 | 0.00 | 34142858.69 | 0.00 | 0.35 |
| March | 0.717560E+09 | 1118367.81 | 0.00 | 127335.61 | 140574.39 | 3100617.05 | 26760120.55 | 0.00 | 0.35 |
| April | 0.232961E+09 | 52556292.12 | 0.00 | 767044.11 | 42152.51 | 0.00 | 0.171958E+09 | 0.00 | 0.35 |
| May | 18239526.48 | 0.177397E+09 | 0.00 | 1211882.08 | 0.00 | 0.00 | 0.164674E+09 | 0.00 | 0.35 |
| June | 0.00 | 0.362099E+09 | 0.00 | 708146.31 | 0.00 | 0.00 | 41241368.62 | 0.00 | 0.35 |
| July | 0.00 | 0.687509E+09 | 0.00 | 34959.65 | 0.00 | 0.00 | 719865.27 | 0.00 | 0.36 |
| August | 0.00 | 0.436910E+09 | 0.00 | 644315.99 | 0.00 | 0.00 | 22434722.85 | 0.00 | 0.35 |
| September | 0.00 | 0.300514E+09 | 0.00 | 1571496.06 | 0.00 | 0.00 | 0.109354E+09 | 0.00 | 0.36 |
| October | 1184889.34 | 72769055.08 | 0.00 | 3628324.50 | 0.00 | 0.00 | 0.430509E+09 | 0.00 | 0.35 |
| November | 0.403873E+09 | 475948.21 | 0.00 | 2422979.92 | 0.00 | 0.00 | 0.511725E+09 | 0.00 | 0.35 |
| December | 0.109350E+10 | 0.00 | 0.00 | 143536.47 | 0.00 | 1683392.57 | 82126092.66 | 0.00 | 0.35 |
| Annual Sum or Average | 0.423984E+10 | 0.209135E+10 | 0.00 | 11596739.26 | 182726.90 | 17745434.68 | 0.166840E+10 | 0.00 | 0.35 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 34959.65 | 0.00 | 0.00 | 719865.27 | 0.00 | 0.35 |
| Maximum of Months | 0.109350E+10 | 0.687509E+09 | 0.00 | 3628324.50 | 140574.39 | 12961425.05 | 0.511725E+09 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: M SW APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.173335E+10 | 0.00 | 0.00 | 669450.15 | 0.00 | 0.170629E+09 | 0.189277E+09 | 0.00 | 0.35 |
| February | 0.136526E+10 | 0.00 | 0.00 | 1139429.03 | 0.00 | 0.104923E+09 | 0.178577E+09 | 0.00 | 0.35 |
| March | 0.122321E+10 | 2390949.27 | 0.00 | 1714972.54 | 0.00 | 57582164.10 | 0.275176E+09 | 0.00 | 0.35 |
| April | 0.366295E+09 | 0.110032E+09 | 0.00 | 3047950.10 | 0.00 | 0.00 | 0.418414E+09 | 0.00 | 0.35 |
| May | 46590000.61 | 0.366462E+09 | 0.00 | 2922289.56 | 0.00 | 0.00 | 0.290499E+09 | 0.00 | 0.35 |
| June | 0.00 | 0.744765E+09 | 0.00 | 1504457.20 | 0.00 | 0.00 | 76368559.48 | 0.00 | 0.35 |
| July | 0.00 | 0.134459E+10 | 0.00 | 61470.85 | 0.00 | 0.00 | 2739772.98 | 0.00 | 0.36 |
| August | 119393.34 | 0.851392E+09 | 0.00 | 1147447.79 | 0.00 | 0.00 | 59632689.70 | 0.00 | 0.35 |
| September | 10697079.22 | 0.566222E+09 | 0.00 | 2505961.36 | 0.00 | 0.00 | 0.225976E+09 | 0.00 | 0.36 |
| October | 0.251798E+09 | 0.139332E+09 | 0.00 | 5164872.07 | 0.00 | 0.00 | 0.612653E+09 | 0.00 | 0.35 |
| November | 0.114779E+10 | 674182.64 | 0.00 | 3196219.30 | 0.00 | 83987601.48 | 0.489010E+09 | 0.00 | 0.35 |
| December | 0.186779E+10 | 0.00 | 0.00 | 200707.01 | 0.00 | 0.304412E+09 | 95738937.99 | 0.00 | 0.35 |
| Annual Sum or Average | 0.801290E+10 | 0.412586E+10 | 0.00 | 23275226.96 | 0.00 | 0.721533E+09 | 0.291406E+10 | 0.00 | 0.35 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 61470.85 | 0.00 | 0.00 | 2739772.98 | 0.00 | 0.35 |
| Maximum of Months | 0.186779E+10 | 0.134459E+10 | 0.00 | 5164872.07 | 0.00 | 0.304412E+09 | 0.612653E+09 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: M NW APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.925775E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.995283E+09 | 0.00 | 0.00 | 0.35 |
| February | 0.100591E+10 | 0.00 | 0.00 | 46533.06 | 0.00 | 0.492919E+09 | 9050688.95 | 0.00 | 0.35 |
| March | 0.127205E+10 | 1656362.90 | 0.00 | 263573.65 | 260702.43 | 0.129104E+09 | 51845658.90 | 0.00 | 0.35 |
| April | 0.440527E+09 | 0.108767E+09 | 0.00 | 2155969.42 | 224174.80 | 0.00 | 0.329171E+09 | 0.00 | 0.35 |
| May | 48832475.61 | 0.364572E+09 | 0.00 | 2829256.16 | 0.00 | 0.00 | 0.287380E+09 | 0.00 | 0.35 |
| June | 0.00 | 0.740793E+09 | 0.00 | 1572086.73 | 0.00 | 0.00 | 75486588.52 | 0.00 | 0.35 |
| July | 0.00 | 0.134499E+10 | 0.00 | 62685.03 | 0.00 | 0.00 | 2790164.47 | 0.00 | 0.36 |
| August | 30283.07 | 0.836283E+09 | 0.00 | 1111713.48 | 0.00 | 0.00 | 62397755.00 | 0.00 | 0.36 |
| September | 25777228.70 | 0.528941E+09 | 0.00 | 1986931.08 | 0.00 | 0.00 | 0.220208E+09 | 0.00 | 0.36 |
| October | 0.486147E+09 | 0.122874E+09 | 0.00 | 2310531.94 | 0.00 | 0.00 | 0.384612E+09 | 0.00 | 0.35 |
| November | 0.127140E+10 | 397152.99 | 0.00 | 112516.16 | 3629.53 | 0.263270E+09 | 29314614.33 | 0.00 | 0.35 |
| December | 0.795995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131928E+10 | 0.00 | 0.00 | 0.35 |
| Annual Sum or Average | 0.627245E+10 | 0.404927E+10 | 0.00 | 12451796.72 | 488506.76 | 0.319986E+10 | 0.145226E+10 | 0.00 | 0.35 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
| Maximum of Months | 0.127205E+10 | 0.134499E+10 | 0.00 | 2829256.16 | 260702.43 | 0.131928E+10 | 0.384612E+09 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: M SE APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.176077E+10 | 0.00 | 0.00 | 478069.06 | 0.00 | 0.172041E+09 | 0.160311E+09 | 0.00 | 0.35 |
| February | 0.135842E+10 | 0.00 | 0.00 | 1172482.32 | 0.00 | 97638142.24 | 0.203341E+09 | 0.00 | 0.35 |
| March | 0.120701E+10 | 2374801.70 | 0.00 | 1725372.41 | 7300.62 | 55641470.57 | 0.300424E+09 | 0.00 | 0.35 |
| April | 0.337156E+09 | 0.110296E+09 | 0.00 | 3482361.22 | 0.00 | 0.00 | 0.450743E+09 | 0.00 | 0.35 |
| May | 37086272.61 | 0.369628E+09 | 0.00 | 3281026.33 | 0.00 | 0.00 | 0.300352E+09 | 0.00 | 0.35 |
| June | 0.00 | 0.749855E+09 | 0.00 | 1585111.97 | 0.00 | 0.00 | 77270039.30 | 0.00 | 0.35 |
| July | 0.00 | 0.135655E+10 | 0.00 | 69505.04 | 0.00 | 0.00 | 2629041.55 | 0.00 | 0.36 |
| August | 151576.90 | 0.863151E+09 | 0.00 | 1216025.19 | 0.00 | 0.00 | 60439577.17 | 0.00 | 0.35 |
| September | 13105850.45 | 0.576791E+09 | 0.00 | 2688038.06 | 0.00 | 0.00 | 0.222829E+09 | 0.00 | 0.36 |
| October | 0.260083E+09 | 0.139641E+09 | 0.00 | 5111229.62 | 0.00 | 0.00 | 0.609260E+09 | 0.00 | 0.35 |
| November | 0.113155E+10 | 678932.63 | 0.00 | 3099098.89 | 0.00 | 88899267.95 | 0.501561E+09 | 0.00 | 0.35 |
| December | 0.185603E+10 | 0.00 | 0.00 | 155720.97 | 0.00 | 0.323020E+09 | 91746850.44 | 0.00 | 0.35 |
| Annual Sum or Average | 0.796135E+10 | 0.416897E+10 | 0.00 | 24064041.06 | 7300.62 | 0.737240E+09 | 0.298091E+10 | 0.00 | 0.35 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 69505.04 | 0.00 | 0.00 | 2629041.55 | 0.00 | 0.35 |
| Maximum of Months | 0.185603E+10 | 0.135655E+10 | 0.00 | 5111229.62 | 7300.62 | 0.323020E+09 | 0.609260E+09 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: M NE APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.928914E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.984984E+09 | 0.00 | 0.00 | 0.35 |
| February | 0.105159E+10 | 0.00 | 0.00 | 39042.58 | 0.00 | 0.449989E+09 | 9821424.45 | 0.00 | 0.35 |
| March | 0.128507E+10 | 1667387.31 | 0.00 | 234473.03 | 214083.69 | 0.123638E+09 | 53607865.96 | 0.00 | 0.35 |
| April | 0.406365E+09 | 0.109280E+09 | 0.00 | 2526062.34 | 0.00 | 0.00 | 0.368630E+09 | 0.00 | 0.35 |
| May | 40017775.11 | 0.367812E+09 | 0.00 | 3176819.15 | 0.00 | 0.00 | 0.296551E+09 | 0.00 | 0.35 |
| June | 0.00 | 0.745713E+09 | 0.00 | 1649574.68 | 0.00 | 0.00 | 76382150.58 | 0.00 | 0.35 |
| July | 0.00 | 0.135650E+10 | 0.00 | 70703.82 | 0.00 | 0.00 | 2681271.05 | 0.00 | 0.36 |
| August | 61454.42 | 0.848691E+09 | 0.00 | 1180163.40 | 0.00 | 0.00 | 63236956.19 | 0.00 | 0.36 |
| September | 21577739.92 | 0.542148E+09 | 0.00 | 2167009.19 | 0.00 | 0.00 | 0.223723E+09 | 0.00 | 0.36 |
| October | 0.484294E+09 | 0.123025E+09 | 0.00 | 2154589.59 | 0.00 | 0.00 | 0.392238E+09 | 0.00 | 0.35 |
| November | 0.127573E+10 | 398582.50 | 0.00 | 73619.19 | 0.00 | 0.267305E+09 | 16539998.15 | 0.00 | 0.35 |
| December | 0.848371E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126398E+10 | 0.00 | 0.00 | 0.35 |
| Annual Sum or Average | 0.634199E+10 | 0.409524E+10 | 0.00 | 13272056.96 | 214083.69 | 0.308990E+10 | 0.150341E+10 | 0.00 | 0.35 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
| Maximum of Months | 0.128507E+10 | 0.135650E+10 | 0.00 | 3176819.15 | 214083.69 | 0.126398E+10 | 0.392238E+09 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: M N1 APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.169691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.256998E+09 | 0.00 | 0.00 | 0.35 |
| February | 0.139656E+10 | 0.00 | 0.00 | 35619.45 | 0.00 | 0.150464E+09 | 12100728.67 | 0.00 | 0.35 |
| March | 0.138695E+10 | 1507699.78 | 0.00 | 316625.10 | 261419.05 | 42085335.19 | 97995909.04 | 0.00 | 0.35 |
| April | 0.333162E+09 | 0.105295E+09 | 0.00 | 2421245.97 | 85478.42 | 0.00 | 0.470721E+09 | 0.00 | 0.35 |
| May | 14798007.48 | 0.357593E+09 | 0.00 | 2965106.02 | 0.00 | 0.00 | 0.336817E+09 | 0.00 | 0.35 |
| June | 0.00 | 0.726126E+09 | 0.00 | 1518574.76 | 0.00 | 0.00 | 78238407.11 | 0.00 | 0.35 |
| July | 0.00 | 0.132850E+10 | 0.00 | 65037.21 | 0.00 | 0.00 | 2436086.52 | 0.00 | 0.36 |
| August | 0.00 | 0.820880E+09 | 0.00 | 1133647.55 | 0.00 | 0.00 | 58529527.25 | 0.00 | 0.36 |
| September | 3841335.54 | 0.515412E+09 | 0.00 | 2054942.25 | 0.00 | 0.00 | 0.242496E+09 | 0.00 | 0.36 |
| October | 0.236709E+09 | 0.119960E+09 | 0.00 | 2811500.67 | 0.00 | 0.00 | 0.656328E+09 | 0.00 | 0.35 |
| November | 0.153856E+10 | 446340.19 | 0.00 | 154315.00 | 0.00 | 31936243.33 | 63540432.84 | 0.00 | 0.35 |
| December | 0.171277E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.431569E+09 | 0.00 | 0.00 | 0.35 |
| Annual Sum or Average | 0.832027E+10 | 0.397572E+10 | 0.00 | 13476613.99 | 346897.47 | 0.913053E+09 | 0.201920E+10 | 0.00 | 0.35 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
| Maximum of Months | 0.171277E+10 | 0.132850E+10 | 0.00 | 2965106.02 | 261419.05 | 0.431569E+09 | 0.656328E+09 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: M N2 APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.169059E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.262759E+09 | 0.00 | 0.00 | 0.35 |
| February | 0.139632E+10 | 0.00 | 0.00 | 37942.49 | 0.00 | 0.150854E+09 | 12574351.46 | 0.00 | 0.35 |
| March | 0.138565E+10 | 1513227.49 | 0.00 | 325318.96 | 247875.94 | 42085334.56 | 0.100261E+09 | 0.00 | 0.35 |
| April | 0.330861E+09 | 0.105335E+09 | 0.00 | 2438416.11 | 43673.31 | 0.00 | 0.473343E+09 | 0.00 | 0.35 |
| May | 14812902.23 | 0.357683E+09 | 0.00 | 2969324.60 | 0.00 | 0.00 | 0.336841E+09 | 0.00 | 0.35 |
| June | 0.00 | 0.726235E+09 | 0.00 | 1517525.54 | 0.00 | 0.00 | 78316426.42 | 0.00 | 0.35 |
| July | 0.00 | 0.132865E+10 | 0.00 | 65277.48 | 0.00 | 0.00 | 2431869.25 | 0.00 | 0.36 |
| August | 0.00 | 0.821157E+09 | 0.00 | 1133229.59 | 0.00 | 0.00 | 58611510.32 | 0.00 | 0.36 |
| September | 3840395.87 | 0.515678E+09 | 0.00 | 2055240.84 | 0.00 | 0.00 | 0.242532E+09 | 0.00 | 0.36 |
| October | 0.239015E+09 | 0.119946E+09 | 0.00 | 2799680.07 | 0.00 | 0.00 | 0.654467E+09 | 0.00 | 0.35 |
| November | 0.153832E+10 | 446959.63 | 0.00 | 152236.84 | 0.00 | 32666430.04 | 62483976.80 | 0.00 | 0.35 |
| December | 0.170855E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.435839E+09 | 0.00 | 0.00 | 0.35 |
| Annual Sum or Average | 0.830796E+10 | 0.397664E+10 | 0.00 | 13494192.53 | 291549.25 | 0.924204E+09 | 0.202186E+10 | 0.00 | 0.35 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
| Maximum of Months | 0.170855E+10 | 0.132865E+10 | 0.00 | 2969324.60 | 247875.94 | 0.435839E+09 | 0.654467E+09 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: M S1 APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.174565E+10 | 0.00 | 0.00 | 1559160.19 | 0.00 | 801484.74 | 0.475083E+09 | 0.00 | 0.35 |
| February | 0.130222E+10 | 0.00 | 0.00 | 1833106.89 | 0.00 | 0.00 | 0.452161E+09 | 0.00 | 0.35 |
| March | 0.110407E+10 | 2301410.00 | 0.00 | 2347438.81 | 0.00 | 0.00 | 0.537683E+09 | 0.00 | 0.35 |
| April | 0.243118E+09 | 0.106955E+09 | 0.00 | 3530987.40 | 0.00 | 0.00 | 0.573751E+09 | 0.00 | 0.35 |
| May | 13481886.98 | 0.360311E+09 | 0.00 | 3060485.21 | 0.00 | 0.00 | 0.339021E+09 | 0.00 | 0.35 |
| June | 0.00 | 0.730976E+09 | 0.00 | 1453275.76 | 0.00 | 0.00 | 79265450.02 | 0.00 | 0.35 |
| July | 0.00 | 0.132882E+10 | 0.00 | 64591.71 | 0.00 | 0.00 | 2378042.53 | 0.00 | 0.36 |
| August | 0.00 | 0.839423E+09 | 0.00 | 1164609.76 | 0.00 | 0.00 | 55560299.76 | 0.00 | 0.36 |
| September | 0.00 | 0.559885E+09 | 0.00 | 2612084.86 | 0.00 | 0.00 | 0.235442E+09 | 0.00 | 0.36 |
| October | 30763979.95 | 0.139176E+09 | 0.00 | 6119253.42 | 0.00 | 0.00 | 0.840155E+09 | 0.00 | 0.35 |
| November | 0.959078E+09 | 771653.77 | 0.00 | 4573147.23 | 0.00 | 0.00 | 0.839194E+09 | 0.00 | 0.35 |
| December | 0.199304E+10 | 0.00 | 0.00 | 983030.12 | 0.00 | 15508011.58 | 0.380975E+09 | 0.00 | 0.35 |
| Annual Sum or Average | 0.739142E+10 | 0.406862E+10 | 0.00 | 29301171.34 | 0.00 | 16309496.31 | 0.481067E+10 | 0.00 | 0.35 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 64591.71 | 0.00 | 0.00 | 2378042.53 | 0.00 | 0.35 |
| Maximum of Months | 0.199304E+10 | 0.132882E+10 | 0.00 | 6119253.42 | 0.00 | 15508011.58 | 0.840155E+09 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: M S2 APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.174789E+10 | 0.00 | 0.00 | 1554980.46 | 0.00 | 801474.04 | 0.472506E+09 | 0.00 | 0.35 |
| February | 0.129281E+10 | 0.00 | 0.00 | 1858578.72 | 0.00 | 0.00 | 0.462478E+09 | 0.00 | 0.35 |
| March | 0.109997E+10 | 2300780.03 | 0.00 | 2367631.24 | 0.00 | 0.00 | 0.542142E+09 | 0.00 | 0.35 |
| April | 0.242114E+09 | 0.106958E+09 | 0.00 | 3547153.92 | 0.00 | 0.00 | 0.574889E+09 | 0.00 | 0.35 |
| May | 12793306.18 | 0.360398E+09 | 0.00 | 3065554.92 | 0.00 | 0.00 | 0.339748E+09 | 0.00 | 0.35 |
| June | 0.00 | 0.731087E+09 | 0.00 | 1453313.32 | 0.00 | 0.00 | 79346460.64 | 0.00 | 0.35 |
| July | 0.00 | 0.132897E+10 | 0.00 | 64851.27 | 0.00 | 0.00 | 2373757.89 | 0.00 | 0.36 |
| August | 0.00 | 0.839663E+09 | 0.00 | 1165518.10 | 0.00 | 0.00 | 55636877.00 | 0.00 | 0.36 |
| September | 0.00 | 0.560045E+09 | 0.00 | 2612485.10 | 0.00 | 0.00 | 0.235480E+09 | 0.00 | 0.36 |
| October | 32401908.27 | 0.139163E+09 | 0.00 | 6105441.69 | 0.00 | 0.00 | 0.838896E+09 | 0.00 | 0.35 |
| November | 0.959353E+09 | 772194.98 | 0.00 | 4572704.73 | 0.00 | 0.00 | 0.838739E+09 | 0.00 | 0.35 |
| December | 0.199055E+10 | 0.00 | 0.00 | 984461.62 | 0.00 | 15508023.35 | 0.383620E+09 | 0.00 | 0.35 |
| Annual Sum or Average | 0.737788E+10 | 0.406936E+10 | 0.00 | 29352675.10 | 0.00 | 16309497.39 | 0.482585E+10 | 0.00 | 0.35 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 64851.27 | 0.00 | 0.00 | 2373757.89 | 0.00 | 0.35 |
| Maximum of Months | 0.199055E+10 | 0.132897E+10 | 0.00 | 6105441.69 | 0.00 | 15508023.35 | 0.838896E+09 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: T SW APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.295601E+09 | 0.00 | 0.00 | 456031.22 | 0.00 | 0.615153E+09 | 91185251.44 | 0.00 | 0.35 |
| February | 0.274010E+09 | 0.00 | 0.00 | 637939.79 | 0.00 | 0.431090E+09 | 65547871.75 | 0.00 | 0.35 |
| March | 0.304623E+09 | 1229220.24 | 0.00 | 762612.69 | 0.00 | 0.334665E+09 | 64620222.21 | 0.00 | 0.35 |
| April | 0.206001E+09 | 55284582.44 | 0.00 | 828986.89 | 709396.61 | 66523948.35 | 71935085.62 | 0.00 | 0.35 |
| May | 91339590.95 | 0.184243E+09 | 0.00 | 719389.55 | 2220.98 | 126066.23 | 64438457.83 | 0.00 | 0.35 |
| June | 10581649.76 | 0.373034E+09 | 0.00 | 471987.41 | 0.00 | 0.00 | 33068864.80 | 0.00 | 0.35 |
| July | 1053041.76 | 0.647912E+09 | 0.00 | 25609.88 | 0.00 | 0.00 | 2397327.75 | 0.00 | 0.36 |
| August | 11538147.01 | 0.416038E+09 | 0.00 | 342865.74 | 0.00 | 0.00 | 32145380.38 | 0.00 | 0.36 |
| September | 73773840.10 | 0.269488E+09 | 0.00 | 680272.01 | 0.00 | 0.00 | 58028137.51 | 0.00 | 0.36 |
| October | 0.280471E+09 | 67794026.62 | 0.00 | 1599630.64 | 0.00 | 13758536.11 | 93762814.97 | 0.00 | 0.35 |
| November | 0.281920E+09 | 281743.89 | 0.00 | 1187193.51 | 0.00 | 0.382677E+09 | 0.117659E+09 | 0.00 | 0.35 |
| December | 0.310187E+09 | 0.00 | 0.00 | 307589.91 | 0.00 | 0.703319E+09 | 84806938.18 | 0.00 | 0.35 |
| Annual Sum or Average | 0.214110E+10 | 0.201530E+10 | 0.00 | 8020109.25 | 711617.58 | 0.254731E+10 | 0.779596E+09 | 0.00 | 0.35 |
| Minimum of Months | 1053041.76 | 0.00 | 0.00 | 25609.88 | 0.00 | 0.00 | 2397327.75 | 0.00 | 0.35 |
| Maximum of Months | 0.310187E+09 | 0.647912E+09 | 0.00 | 1599630.64 | 709396.61 | 0.703319E+09 | 0.117659E+09 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: T NW APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.129380E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.820827E+09 | 0.00 | 0.00 | 0.35 |
| February | 0.145935E+09 | 0.00 | 0.00 | 61208.28 | 0.00 | 0.580257E+09 | 6062034.52 | 0.00 | 0.35 |
| March | 0.233776E+09 | 911045.92 | 0.00 | 177589.55 | 55441.26 | 0.423496E+09 | 18340762.31 | 0.00 | 0.35 |
| April | 0.199272E+09 | 54895929.51 | 0.00 | 579455.91 | 926668.41 | 79684524.74 | 57294285.01 | 0.00 | 0.35 |
| May | 91300355.07 | 0.183574E+09 | 0.00 | 699872.81 | 0.00 | 83871.36 | 64248609.10 | 0.00 | 0.35 |
| June | 9692782.91 | 0.371613E+09 | 0.00 | 509091.29 | 0.00 | 0.00 | 33597598.52 | 0.00 | 0.35 |
| July | 901802.19 | 0.649762E+09 | 0.00 | 28713.12 | 0.00 | 0.00 | 2533409.43 | 0.00 | 0.36 |
| August | 11874448.52 | 0.410023E+09 | 0.00 | 335270.59 | 0.00 | 0.00 | 32557726.44 | 0.00 | 0.36 |
| September | 80088566.27 | 0.253866E+09 | 0.00 | 517200.64 | 20879.75 | 0.00 | 52446426.03 | 0.00 | 0.36 |
| October | 0.281654E+09 | 59692188.13 | 0.00 | 610955.52 | 162571.96 | 39191762.71 | 50830323.89 | 0.00 | 0.35 |
| November | 0.203483E+09 | 170457.28 | 0.00 | 46339.85 | 4373.79 | 0.526449E+09 | 3665980.48 | 0.00 | 0.35 |
| December | 0.119408E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.928256E+09 | 0.00 | 0.00 | 0.35 |
| Annual Sum or Average | 0.150677E+10 | 0.198451E+10 | 0.00 | 3565697.55 | 1169935.17 | 0.339825E+10 | 0.321577E+09 | 0.00 | 0.35 |
| Minimum of Months | 901802.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
| Maximum of Months | 0.281654E+09 | 0.649762E+09 | 0.00 | 699872.81 | 926668.41 | 0.928256E+09 | 64248609.10 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: T SE APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.312028E+09 | 0.00 | 0.00 | 296902.98 | 0.00 | 0.606123E+09 | 84337538.44 | 0.00 | 0.35 |
| February | 0.296085E+09 | 0.00 | 0.00 | 559635.86 | 0.00 | 0.407705E+09 | 70698553.38 | 0.00 | 0.35 |
| March | 0.319881E+09 | 1221002.14 | 0.00 | 686309.88 | 0.00 | 0.320150E+09 | 67295900.35 | 0.00 | 0.35 |
| April | 0.214123E+09 | 55446013.36 | 0.00 | 903515.73 | 651842.12 | 58813445.17 | 76244977.55 | 0.00 | 0.35 |
| May | 88219633.40 | 0.186237E+09 | 0.00 | 863735.86 | 0.00 | 107258.40 | 69951821.66 | 0.00 | 0.35 |
| June | 11886537.82 | 0.376263E+09 | 0.00 | 542161.66 | 0.00 | 0.00 | 31612122.20 | 0.00 | 0.35 |
| July | 656649.15 | 0.656647E+09 | 0.00 | 34294.61 | 0.00 | 0.00 | 2925940.57 | 0.00 | 0.36 |
| August | 11888810.02 | 0.423800E+09 | 0.00 | 406115.60 | 0.00 | 0.00 | 31881757.24 | 0.00 | 0.36 |
| September | 70847319.83 | 0.276991E+09 | 0.00 | 758206.49 | 0.00 | 0.00 | 61768670.20 | 0.00 | 0.36 |
| October | 0.278870E+09 | 68277214.93 | 0.00 | 1517267.19 | 0.00 | 18945977.93 | 91619128.20 | 0.00 | 0.35 |
| November | 0.293611E+09 | 284389.32 | 0.00 | 1027796.08 | 0.00 | 0.371777E+09 | 0.118756E+09 | 0.00 | 0.35 |
| December | 0.329398E+09 | 0.00 | 0.00 | 203417.27 | 0.00 | 0.690811E+09 | 78650964.80 | 0.00 | 0.35 |
| Annual Sum or Average | 0.222750E+10 | 0.204517E+10 | 0.00 | 7799359.20 | 651842.12 | 0.247443E+10 | 0.785744E+09 | 0.00 | 0.35 |
| Minimum of Months | 656649.15 | 0.00 | 0.00 | 34294.61 | 0.00 | 0.00 | 2925940.57 | 0.00 | 0.35 |
| Maximum of Months | 0.329398E+09 | 0.656647E+09 | 0.00 | 1517267.19 | 651842.12 | 0.690811E+09 | 0.118756E+09 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: T NE APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.117719E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.828276E+09 | 0.00 | 0.00 | 0.35 |
| February | 0.169107E+09 | 0.00 | 0.00 | 33446.51 | 0.00 | 0.557977E+09 | 4360854.21 | 0.00 | 0.35 |
| March | 0.263276E+09 | 900292.49 | 0.00 | 107072.16 | 1228.85 | 0.400615E+09 | 12155150.47 | 0.00 | 0.35 |
| April | 0.213329E+09 | 55114021.54 | 0.00 | 635339.38 | 682392.36 | 69911801.03 | 57838597.24 | 0.00 | 0.35 |
| May | 87377642.60 | 0.185629E+09 | 0.00 | 842254.96 | 0.00 | 107219.36 | 70491732.29 | 0.00 | 0.35 |
| June | 11123558.45 | 0.374696E+09 | 0.00 | 575161.32 | 0.00 | 0.00 | 32027591.88 | 0.00 | 0.35 |
| July | 696733.75 | 0.658027E+09 | 0.00 | 36719.00 | 0.00 | 0.00 | 2871709.41 | 0.00 | 0.36 |
| August | 12139045.07 | 0.418125E+09 | 0.00 | 395864.45 | 0.00 | 0.00 | 32417060.93 | 0.00 | 0.36 |
| September | 78655517.19 | 0.263242E+09 | 0.00 | 577910.02 | 0.00 | 0.00 | 55177651.93 | 0.00 | 0.36 |
| October | 0.286384E+09 | 60113976.71 | 0.00 | 495109.67 | 0.00 | 43869985.26 | 43035977.90 | 0.00 | 0.35 |
| November | 0.201197E+09 | 168606.71 | 0.00 | 28923.92 | 0.00 | 0.525028E+09 | 2442487.78 | 0.00 | 0.35 |
| December | 96362296.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.948992E+09 | 0.00 | 0.00 | 0.35 |
| Annual Sum or Average | 0.153737E+10 | 0.201602E+10 | 0.00 | 3727801.38 | 683621.21 | 0.337478E+10 | 0.312819E+09 | 0.00 | 0.35 |
| Minimum of Months | 696733.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
| Maximum of Months | 0.286384E+09 | 0.658027E+09 | 0.00 | 842254.96 | 682392.36 | 0.948992E+09 | 70491732.29 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: T N1 APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.193755E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.762592E+09 | 0.00 | 0.00 | 0.35 |
| February | 0.236961E+09 | 0.00 | 0.00 | 16275.90 | 0.00 | 0.498744E+09 | 3024002.46 | 0.00 | 0.35 |
| March | 0.334665E+09 | 832980.63 | 0.00 | 64547.50 | 58538.99 | 0.341454E+09 | 9185734.49 | 0.00 | 0.35 |
| April | 0.247188E+09 | 52788778.63 | 0.00 | 516507.37 | 889048.79 | 39782460.30 | 66600503.85 | 0.00 | 0.35 |
| May | 82528133.37 | 0.180353E+09 | 0.00 | 768243.00 | 0.00 | 0.00 | 85199335.25 | 0.00 | 0.35 |
| June | 3371066.82 | 0.365810E+09 | 0.00 | 551242.84 | 0.00 | 0.00 | 40719826.32 | 0.00 | 0.35 |
| July | 462511.75 | 0.655323E+09 | 0.00 | 22522.75 | 0.00 | 0.00 | 2218102.81 | 0.00 | 0.36 |
| August | 5519009.22 | 0.408422E+09 | 0.00 | 390068.05 | 0.00 | 0.00 | 35649533.00 | 0.00 | 0.36 |
| September | 70135802.55 | 0.251902E+09 | 0.00 | 520135.99 | 0.00 | 0.00 | 64280188.98 | 0.00 | 0.36 |
| October | 0.327261E+09 | 58039275.44 | 0.00 | 440938.21 | 82390.36 | 7213975.85 | 58420079.19 | 0.00 | 0.35 |
| November | 0.285522E+09 | 185712.99 | 0.00 | 21064.90 | 3578.08 | 0.450585E+09 | 2835712.97 | 0.00 | 0.35 |
| December | 0.158506E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.895454E+09 | 0.00 | 0.00 | 0.35 |
| Annual Sum or Average | 0.194588E+10 | 0.197366E+10 | 0.00 | 3311546.51 | 1033556.21 | 0.299583E+10 | 0.368133E+09 | 0.00 | 0.35 |
| Minimum of Months | 462511.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
| Maximum of Months | 0.334665E+09 | 0.655323E+09 | 0.00 | 768243.00 | 889048.79 | 0.895454E+09 | 85199335.25 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: T N2 APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.192256E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.763926E+09 | 0.00 | 0.00 | 0.35 |
| February | 0.237727E+09 | 0.00 | 0.00 | 16984.04 | 0.00 | 0.497966E+09 | 3109130.02 | 0.00 | 0.35 |
| March | 0.334478E+09 | 833462.08 | 0.00 | 65262.74 | 46366.01 | 0.341698E+09 | 9301293.62 | 0.00 | 0.35 |
| April | 0.247286E+09 | 52820282.53 | 0.00 | 520870.98 | 844948.28 | 40015819.61 | 66514807.07 | 0.00 | 0.35 |
| May | 82102832.83 | 0.180452E+09 | 0.00 | 770770.15 | 0.00 | 0.00 | 85726645.88 | 0.00 | 0.35 |
| June | 3761345.96 | 0.365905E+09 | 0.00 | 551838.27 | 0.00 | 0.00 | 40387953.08 | 0.00 | 0.35 |
| July | 462878.15 | 0.655483E+09 | 0.00 | 22839.76 | 0.00 | 0.00 | 2220926.46 | 0.00 | 0.36 |
| August | 5862672.57 | 0.408679E+09 | 0.00 | 390756.05 | 0.00 | 0.00 | 35367183.78 | 0.00 | 0.36 |
| September | 70316594.92 | 0.252248E+09 | 0.00 | 519919.09 | 0.00 | 0.00 | 64163826.43 | 0.00 | 0.36 |
| October | 0.327193E+09 | 58092707.82 | 0.00 | 442619.99 | 58671.25 | 7451970.06 | 57937994.88 | 0.00 | 0.35 |
| November | 0.282921E+09 | 185615.78 | 0.00 | 21444.57 | 1930.66 | 0.452933E+09 | 2841368.24 | 0.00 | 0.35 |
| December | 0.156104E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.897811E+09 | 0.00 | 0.00 | 0.35 |
| Annual Sum or Average | 0.194047E+10 | 0.197470E+10 | 0.00 | 3323305.65 | 951916.20 | 0.300180E+10 | 0.367571E+09 | 0.00 | 0.35 |
| Minimum of Months | 462878.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
| Maximum of Months | 0.334478E+09 | 0.655483E+09 | 0.00 | 770770.15 | 844948.28 | 0.897811E+09 | 85726645.88 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: T S1 APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.420311E+09 | 0.00 | 0.00 | 483557.18 | 0.00 | 0.483917E+09 | 0.121725E+09 | 0.00 | 0.35 |
| February | 0.391058E+09 | 0.00 | 0.00 | 589551.39 | 0.00 | 0.312559E+09 | 88863562.95 | 0.00 | 0.35 |
| March | 0.423013E+09 | 1195627.31 | 0.00 | 603146.11 | 0.00 | 0.229823E+09 | 74330870.19 | 0.00 | 0.35 |
| April | 0.243267E+09 | 53956343.38 | 0.00 | 792770.58 | 177074.48 | 30250515.05 | 90483310.25 | 0.00 | 0.35 |
| May | 81661286.76 | 0.181373E+09 | 0.00 | 783547.65 | 0.00 | 0.00 | 86499790.48 | 0.00 | 0.35 |
| June | 4271542.11 | 0.367673E+09 | 0.00 | 513365.21 | 0.00 | 0.00 | 40362576.99 | 0.00 | 0.35 |
| July | 466550.22 | 0.653625E+09 | 0.00 | 22485.24 | 0.00 | 0.00 | 2228897.09 | 0.00 | 0.36 |
| August | 4406541.23 | 0.415821E+09 | 0.00 | 394840.06 | 0.00 | 0.00 | 35904264.72 | 0.00 | 0.36 |
| September | 60551905.77 | 0.270491E+09 | 0.00 | 706140.65 | 0.00 | 0.00 | 72265005.44 | 0.00 | 0.36 |
| October | 0.286281E+09 | 68035938.83 | 0.00 | 1550175.81 | 0.00 | 762966.52 | 0.124541E+09 | 0.00 | 0.35 |
| November | 0.407822E+09 | 322414.25 | 0.00 | 1141497.89 | 0.00 | 0.254219E+09 | 0.145627E+09 | 0.00 | 0.35 |
| December | 0.429334E+09 | 0.00 | 0.00 | 350956.49 | 0.00 | 0.579840E+09 | 0.110961E+09 | 0.00 | 0.35 |
| Annual Sum or Average | 0.275244E+10 | 0.201249E+10 | 0.00 | 7932034.27 | 177074.48 | 0.189137E+10 | 0.993792E+09 | 0.00 | 0.35 |
| Minimum of Months | 466550.22 | 0.00 | 0.00 | 22485.24 | 0.00 | 0.00 | 2228897.09 | 0.00 | 0.35 |
| Maximum of Months | 0.429334E+09 | 0.653625E+09 | 0.00 | 1550175.81 | 177074.48 | 0.579840E+09 | 0.145627E+09 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: T S2 APARTMENT
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.420292E+09 | 0.00 | 0.00 | 484630.91 | 0.00 | 0.484613E+09 | 0.120997E+09 | 0.00 | 0.35 |
| February | 0.389694E+09 | 0.00 | 0.00 | 597157.42 | 0.00 | 0.312799E+09 | 90274159.85 | 0.00 | 0.35 |
| March | 0.421937E+09 | 1195288.53 | 0.00 | 611583.50 | 0.00 | 0.230829E+09 | 74546685.70 | 0.00 | 0.35 |
| April | 0.241998E+09 | 53964174.73 | 0.00 | 799558.72 | 170895.33 | 30758246.76 | 91423414.90 | 0.00 | 0.35 |
| May | 82100613.36 | 0.181471E+09 | 0.00 | 787314.51 | 0.00 | 0.00 | 86147597.99 | 0.00 | 0.35 |
| June | 4271988.11 | 0.367773E+09 | 0.00 | 513831.95 | 0.00 | 0.00 | 40419201.67 | 0.00 | 0.35 |
| July | 466925.82 | 0.653793E+09 | 0.00 | 22691.77 | 0.00 | 0.00 | 2231306.06 | 0.00 | 0.36 |
| August | 4407655.77 | 0.416045E+09 | 0.00 | 395966.21 | 0.00 | 0.00 | 35960362.50 | 0.00 | 0.36 |
| September | 60491090.59 | 0.270716E+09 | 0.00 | 707443.21 | 0.00 | 0.00 | 72368016.84 | 0.00 | 0.36 |
| October | 0.286165E+09 | 68050501.25 | 0.00 | 1550233.32 | 0.00 | 1269262.27 | 0.123947E+09 | 0.00 | 0.35 |
| November | 0.406986E+09 | 322976.76 | 0.00 | 1143173.50 | 0.00 | 0.255122E+09 | 0.145442E+09 | 0.00 | 0.35 |
| December | 0.427678E+09 | 0.00 | 0.00 | 354030.33 | 0.00 | 0.579479E+09 | 0.112996E+09 | 0.00 | 0.35 |
| Annual Sum or Average | 0.274649E+10 | 0.201333E+10 | 0.00 | 7967615.34 | 170895.33 | 0.189487E+10 | 0.996753E+09 | 0.00 | 0.35 |
| Minimum of Months | 466925.82 | 0.00 | 0.00 | 22691.77 | 0.00 | 0.00 | 2231306.06 | 0.00 | 0.35 |
| Maximum of Months | 0.427678E+09 | 0.653793E+09 | 0.00 | 1550233.32 | 170895.33 | 0.579479E+09 | 0.145442E+09 | 0.00 | 0.36 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 09:14:34
Custom Monthly Report| SITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
| January | 0.117290E+12 | 0.165069E+11 | 0.00 | 0.155091E+10 | 0.773475E+10 |
| February | 0.112158E+12 | 0.152178E+11 | 0.00 | 0.123105E+10 | 0.864192E+10 |
| March | 0.153283E+12 | 0.166121E+11 | 0.00 | 0.115774E+10 | 0.108422E+11 |
| April | 0.147040E+12 | 0.947512E+10 | 0.00 | 0.659530E+09 | 0.541178E+11 |
| May | 0.146382E+12 | 0.265545E+10 | 0.00 | 0.298825E+09 | 0.108919E+12 |
| June | 0.139610E+12 | -0.364735E+10 | 0.00 | -66502706.0 | 0.157032E+12 |
| July | 0.144336E+12 | -0.725648E+10 | 0.00 | -227504468.8 | 0.182518E+12 |
| August | 0.136351E+12 | -0.284897E+10 | 0.00 | -61451607.1 | 0.157803E+12 |
| September | 0.134478E+12 | 0.965785E+09 | 0.00 | 0.302232E+09 | 0.127210E+12 |
| October | 0.133817E+12 | 0.939574E+10 | 0.00 | 0.829913E+09 | 0.659410E+11 |
| November | 0.114818E+12 | 0.148892E+11 | 0.00 | 0.140329E+10 | 0.166831E+11 |
| December | 0.102024E+12 | 0.148543E+11 | 0.00 | 0.171490E+10 | 0.774003E+10 |
| Annual Sum or Average | 0.158159E+13 | 0.868196E+11 | 0.00 | 0.879293E+10 | 0.905183E+12 |
| Minimum of Months | 0.102024E+12 | -0.725648E+10 | 0.00 | -227504468.8 | 0.773475E+10 |
| Maximum of Months | 0.153283E+12 | 0.166121E+11 | 0.00 | 0.171490E+10 | 0.182518E+12 |